Notice of Petition for Waiver of AHT Incorporated From the Department of Energy Commercial Refrigeration Equipment Test Procedures and Partial Grant of Interim Waiver, 15345-15353 [2017-06107]
Download as PDF
Federal Register / Vol. 82, No. 58 / Tuesday, March 28, 2017 / Notices
5:00 p.m. on April 19, 2017. Agenda
updates and presentations will be
posted on the ASCAC Web site prior to
the meeting: https://science.energy.gov/
ascr/ascac/.
Public Participation: The meeting is
open to the public. Individuals and
representatives of organizations who
would like to offer comments and
suggestions may do so during the
meeting. Approximately 30 minutes will
be reserved for public comments. Time
allotted per speaker will depend on the
number who wish to speak but will not
exceed 10 minutes. Those wishing to
speak should submit your request at
least five days before the meeting. Those
not able to attend the meeting or who
have insufficient time to address the
committee are invited to send a written
statement to Christine Chalk, U.S.
Department of Energy, 1000
Independence Avenue SW.,
Washington, DC 20585, email to
Christine.Chalk@science.doe.gov. The
Designated Federal Officer is
empowered to conduct the meeting in a
fashion that will facilitate the orderly
conduct of business.
Minutes: The minutes of this meeting
will be available within 90 days on the
Advanced Scientific Computing Web
site at https://science.energy.gov/ascr/
ascac/.
Issued in Washington, DC, on March 22,
2017.
LaTanya R. Butler,
Deputy Committee Management Officer.
[FR Doc. 2017–06099 Filed 3–27–17; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF ENERGY
National Coal Council
Office of Fossil Energy,
Department of Energy.
ACTION: Notice of open meetings.
AGENCY:
This notice announces a
meeting of the National Coal Council
(NCC). The Federal Advisory Committee
Act requires that public notice of these
meetings be announced in the Federal
Register.
DATES: Wednesday, April 19, 2017 8:15
a.m. to 12:15 p.m.
ADDRESSES: Sheraton Suites, Old Town
Alexandria; 801 N. Saint Asaph St.;
Alexandria, VA 22314
FOR FURTHER INFORMATION CONTACT:
Daniel Matuszak, U.S. Department of
Energy, 4G–036/Forrestal Building,
1000 Independence Avenue SW.,
Washington, DC 20585–0001;
Telephone: 202–287–6915
SUPPLEMENTARY INFORMATION:
sradovich on DSK3GMQ082PROD with NOTICES
SUMMARY:
VerDate Sep<11>2014
17:14 Mar 27, 2017
Jkt 241001
Purpose of the Council: The National
Coal Council provides advice and
recommendations to the Secretary of
Energy on general policy matters
relating to coal and the coal industry.
Purpose of Meeting: The 2017 Spring
Meeting of the National Coal Council.
Tentative Agenda:
1. Call to order and opening remarks by
Mike Durham, Chair, National Coal
Council
2. Remarks by U.S. Department of
Energy Representative—TBD
3. Presentation by Steve Nelson, COO,
Longview Power LLC on Longview
Power’s State-of-the-Art Clean Coal
Technology Plant
4. Presentation by Anthony Leo, Vice
President, FuelCell Energy on the
ExxonMobil-FuelCell Energy Fuel
Cell Carbon Capture Pilot Plant at
Plant Barry
5. Presentation by David Denton, Senior
Director Business Development, RTI
International on ‘‘Advanced
Technologies for CO2 Capture &
Utilization: Power & Industrial
Applications’’
6. Presentation by Jared Moore,
Principal, Meridian Energy Policy
on ‘‘Thermal Hydrogen: Coal
Pathways Toward an Emissions
Free Hydrogen Economy’’
7. Council Business:
a. Finance report by Finance
Committee Chair Greg Workman
b. Coal Policy Committee report by
Coal Policy Committee Chair Deck
Slone
c. Communications Committee report
by Communications Committee
Chair Lisa Bradley
d. NCC Business Report by NCC CEO
Janet Gellici
8. Other Business
9. Adjourn
Attendees are requested to register in
advance for the meeting at: https://
www.nationalcoalcouncil.org/pageNCC-Events.html.
Public Participation: The meeting is
open to the public. If you would like to
file a written statement with the
Council, you may do so either before or
after the meeting. If you would like to
make oral statements regarding any item
on the agenda, you should contact
Daniel Matuszak, 202–287–6915 or
daniel.matuszak@hq.doe.gov (email).
You must make your request for an oral
statement at least 5 business days before
the meeting. Reasonable provision will
be made to include oral statements on
the scheduled agenda. The Chairperson
of the Council will lead the meeting in
a manner that facilitates the orderly
conduct of business. Oral statements are
limited to 10-minutes per organization
and per person.
PO 00000
Frm 00032
Fmt 4703
Sfmt 4703
15345
Minutes: A link to the transcript of the
meeting will be posted on the NCC Web
site at: https://
www.nationalcoalcouncil.org/.
Issued at Washington, DC, on March 22,
2017.
LaTanya R. Butler,
Deputy Committee Management Officer.
[FR Doc. 2017–06100 Filed 3–27–17; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF ENERGY
Office of Energy Efficiency and
Renewable Energy
[Case No. CR–006]
Notice of Petition for Waiver of AHT
Incorporated From the Department of
Energy Commercial Refrigeration
Equipment Test Procedures and Partial
Grant of Interim Waiver
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Notice of petition for waiver and
partial grant of interim waiver, and
request for public comment.
AGENCY:
This notice announces receipt
of and publishes a petition for waiver
from AHT Cooling Systems GmbH and
AHT Cooling Systems USA Inc. (AHT)
seeking an exemption from specified
portions of the U.S. Department of
Energy (DOE) test procedure for
determining the energy consumption of
multi-mode commercial refrigeration
equipment. ASHRAE Standard 72–2005,
incorporated by reference in Appendix
B, does not provide for defrost testing
with built-in cooling coils into the body
of AHT’s unique multi-mode
commercial refrigeration equipment
basic models. Consequently, AHT
submitted to DOE an alternate test
procedure that allows for testing of six
specified basic models with a different
defrost cycle. This notice also
announces that DOE has granted AHT
an interim waiver from the DOE
commercial refrigeration equipment test
procedures for the specified commercial
refrigeration equipment basic models,
subject to use of the alternative test
procedure as set forth in this notice.
DOE solicits comments, data, and
information concerning AHT’s petition
and its suggested alternate test
procedure.
DATES: DOE will accept comments, data,
and information with regard to the AHT
petition until April 27, 2017.
ADDRESSES: You may submit comments,
identified by Case Number CR–006, by
any of the following methods:
SUMMARY:
E:\FR\FM\28MRN1.SGM
28MRN1
15346
Federal Register / Vol. 82, No. 58 / Tuesday, March 28, 2017 / Notices
• Federal eRulemaking Portal: https://
www.regulations.gov. Follow the
instructions for submitting comments.
• Email: AS_Waiver_Requests@
ee.doe.gov. Include the case number
[Case No. CR–006] in the subject line of
the message. Submit electronic
comments in WordPerfect, Microsoft
Word, PDF, or ASCII file format, and
avoid the use of special characters or
any form of encryption.
• Postal Mail: Mr. Bryan Berringer,
U.S. Department of Energy, Building
Technologies Office, Mailstop EE–5B,
Petition for Waiver Case No. CR–006,
1000 Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–0371. If possible,
please submit all items on a compact
disc (CD), in which case it is not
necessary to include printed copies.
• Hand Delivery/Courier: Appliance
and Equipment Standards Program, U.S.
Department of Energy, Building
Technologies Office, 950 L’Enfant Plaza
SW., 6th Floor, Washington, DC 20024.
Telephone: (202) 586–6636. If possible,
please submit all items on a CD, in
which case it is not necessary to include
printed copies.
Docket: The docket, which includes
Federal Register notices, comments,
and other supporting documents/
materials, is available for review at
www.regulations.gov. All documents in
the docket are listed in the
www.regulations.gov index. However,
some documents listed in the index,
such as those containing information
that is exempt from public disclosure,
may not be publicly available.
FOR FURTHER INFORMATION CONTACT: Mr.
Bryan Berringer, U.S. Department of
Energy, Building Technologies Office,
Mailstop EE–5B, 1000 Independence
Avenue SW., Washington, DC 20585–
0121. Telephone: (202) 586–0371.
Email: Bryan.Berringer@ee.doe.gov.
Ms. Johanna Jochum, U.S. Department
of Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue
SW., Washington, DC 20585–0121.
Telephone: (202) 287–6307. Email:
Johanna.Jochum@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
sradovich on DSK3GMQ082PROD with NOTICES
I. Background and Authority
Title III, Part C of the Energy Policy
and Conservation Act of 1975 (EPCA),
Public Law 94–163 (42 U.S.C. 6311–
6316, as codified) established the
Energy Conservation Program for
Certain Industrial Equipment, which
includes the commercial refrigeration
equipment. Part C includes definitions,
test procedures, labeling provisions,
energy conservation standards, and the
authority to require information and
VerDate Sep<11>2014
17:14 Mar 27, 2017
Jkt 241001
reports from manufacturers. Further,
Part C authorizes the Secretary of
Energy to prescribe test procedures that
are reasonably designed to produce
results that measure energy efficiency,
energy use, or estimated operating costs
during a representative average-use
cycle, and that are not unduly
burdensome to conduct. (42 U.S.C.
6314(a)(3)) The test procedure for
commercial refrigeration equipment is
contained in Title 10 of the CFR part
431, subpart C, appendix B, Amended
Uniform Test Method for the
Measurement of Energy Consumption of
Commercial Refrigerators, Freezers, and
Refrigerator-Freezers.
DOE’s regulations set forth at 10 CFR
431.401 contain provisions that allow a
person to seek a waiver from the test
procedure requirements for a particular
basic model of a type of covered
industrial equipment when: (1) The
petitioner’s basic model for which the
petition for waiver was submitted
contains one or more design
characteristics that prevent testing
according to the prescribed test
procedure, or (2) the prescribed test
procedures may evaluate the basic
model in a manner so unrepresentative
of its true energy consumption
characteristics as to provide materially
inaccurate comparative data. 10 CFR
431.401(a)(1). A petitioner must include
in its petition any alternate test
procedures known to the petitioner to
evaluate the basic model in a manner
representative of its energy
consumption. 10 CFR 431.401(b)(1)(iii).
DOE may grant a waiver subject to
conditions, including adherence to
alternate test procedures. 10 CFR
431.401(f)(2). As soon as practicable
after the granting of any waiver, DOE
will publish in the Federal Register a
notice of proposed rulemaking to amend
its regulations so as to eliminate any
need for the continuation of such
waiver. As soon thereafter as
practicable, DOE will publish in the
Federal Register a final rule. 10 CFR
431.401(l).
The waiver process also allows DOE
to grant an interim waiver if it appears
likely that the petition for waiver will be
granted and/or if DOE determines that it
would be desirable for public policy
reasons to grant immediate relief
pending a determination on the petition
for waiver. 10 CFR 431.401(e)(2). Within
one year of issuance of an interim
waiver, DOE will either: (i) Publish in
the Federal Register a determination on
the petition for waiver; or (ii) publish in
the Federal Register a new or amended
test procedure that addresses the issues
presented in the waiver. 10 CFR
431.401(h)(1). When DOE amends the
PO 00000
Frm 00033
Fmt 4703
Sfmt 4703
test procedure to address the issues
presented in a waiver, the waiver will
automatically terminate on the date on
which use of that test procedure is
required to demonstrate compliance. 10
CFR 431.401(h)(2).
II. Petition for Waiver of Test Procedure
and Application for Interim Waiver
On October 25, 2016, AHT filed a
petition for waiver and application for
interim waiver from the test procedure
applicable to commercial refrigeration
equipment set forth in 10 CFR part 431,
subpart C, appendix B (AHT
subsequently sent DOE a letter on
March 6, 2017, which responded to
questions from DOE. The information
from this letter is also represented in
this notice). AHT has designed several
basic models multi-mode commercial
refrigeration equipment that use unique
built-in cooling coils deep freeze, freeze,
or refrigerate food as needed. Because
the cooling coils are built into the body
of the units and do not get covered in
frost, the coils do not need to be
defrosted prior to testing. However, the
DOE test procedure and ASHRAE
Standard 72–2005, incorporated by
reference in Appendix B, assumes that
commercial refrigerators or freezers
need to be defrosted, or melt the ice
from the evaporator coils, for the
equipment to function effectively. In
particular, the test procedure requires
that all refrigerators and freezers with
evaporator coils be tested with a full
defrost cycle, along with additional
defrost cycles in a 24-hour period,
depending on how long the test runs
(ANSI/ASHRAE Standard 72–2005,
‘‘Method of Testing Commercial
Refrigerators and Freezers,’’ § 7.8
(Defrost Adequacy Assurance). ASHRAE
72–2005 is incorporated by reference in
the DOE test procedure. 10 CFR
431.63(d)(1)). AHT appliances, however,
have no need to defrost their coils.
Thus, rather than running one or more
defrosting cycles a day to keep the
machines operating efficiently, AHT
appliances have a defrost (in the generic
sense rather than as defined by DOE/
ASHRAE) function that operates, under
standard conditions, once per week, and
at most (through a manual override)
twice per week. As a result, the DOE test
procedure, which provides for at least
one full defrost cycle in a 24-hour
period, is not appropriate for these
models. Consequently, AHT submitted
to DOE an alternate test procedure that
allows for testing of six specified basic
models with a different defrost cycle.
As previously noted, an interim
waiver may be granted if it appears
likely that the petition for waiver will be
granted, and/or if DOE determines that
E:\FR\FM\28MRN1.SGM
28MRN1
sradovich on DSK3GMQ082PROD with NOTICES
Federal Register / Vol. 82, No. 58 / Tuesday, March 28, 2017 / Notices
it would be desirable for public policy
reasons to grant immediate relief
pending a determination of the petition
for waiver. See 10 CFR 431.401(e)(2).
AHT’s petition for waiver claims that
the DOE test procedure at 10 CFR part
431, subpart C, appendix B does not
apply to AHT’s advanced models, and
would grossly overstate the energy used
by these models. These models are
multi-mode (i.e., are capable of
operating in the ice cream freezer,
commercial freezer, and commercial
refrigerator temperature ranges) and do
not have a typical defrosting cycle (i.e.,
the cooling coils are built into the body
and require defrosts once per week).
To address multi-mode operation,
AHT requested that the basic models
shall be tested and rated only for
operation as ice cream freezers (with
integrated average temperature of
¥15 °F ± 2.0 °F and use total display
area (TDA) to determine associated
energy conservation standards).
To address infrequent defrosts, AHT
requested in its October 25, 2016
petition that the basic models shall be
subject to an alternate two-part test
procedure. AHT specified that the first
part would be a 24-hour test starting in
steady state conditions and including
eight hours of door opening (according
to ASHRAE Standard 72). The energy
consumed in this test would be
recorded ET1. The second part would be
a defrost cycle test starting after steady
state conditions were established and
ending after the defrost cycle was
complete. The duration of the defrost
cycle, tDI, and the energy consumed
during the defrost cycle, ET2, would be
recorded and combined with ET1 based
on a once-per-week defrost frequency.
In AHT’s March 6, 2017 letter, AHT
noted that although the standard
duration of the defrost cycle was onceper-week, the basic models have an
optional manual override that allows up
to two defrost cycles per week and
recommended revising the October 25
test procedure to reflect that. DOE has
incorporated this proposal into the
alternate test procedure, but requests
that AHT or commenting parties
provide additional data and/or
information on how commonly the
manual override is used.
With regard to the first issue, multimode operation, DOE has taken the
position in the most recent commercial
refrigeration equipment test procedure
final rule, that self-contained equipment
or remote condensing equipment with
thermostats capable of operating at
temperatures that span multiple
equipment categories must be certified
and comply with DOE’s regulations for
each applicable equipment category. See
VerDate Sep<11>2014
17:14 Mar 27, 2017
Jkt 241001
79 FR 22291. In light of that policy
determination, DOE declines at this
time to provide AHT an interim waiver
allowing testing only in the ice cream
freezer mode. However, DOE seeks
comment as part of the waiver
determination process to determine if its
previously stated position provides for a
test requirement imposing an undue
burden.
Regarding the second issue of
infrequent defrosts, DOE has reviewed
AHT’s alternate procedure (based on the
May 6, 2017 modification) and
concludes that AHT’s alternate test
procedure results would be
representative of the models’ true
energy consumptions and allow for the
accurate measurement of the energy use
of these equipment, while alleviating
the testing problems associated with
AHT’s implementation of commercial
refrigeration equipment testing for the
specified multi-mode models. DOE also
understands that absent a partial grant
of an interim waiver, AHT’s equipment
cannot be tested and rated for energy
consumption on a basis representative
of its true energy consumption
characteristics. Consequently, DOE has
determined that this part of AHT’s
petition for waiver will likely be
granted. Furthermore, DOE has
determined that it is desirable for public
policy reasons to grant AHT immediate
relief for this part of the test procedure,
pending a determination of the petition
for waiver.
III. Summary of Grant of Interim
Waiver
For the reasons stated above, DOE has
partially granted AHT’s application for
interim waiver from testing for its
specified commercial refrigeration
equipment basic models. The substance
of the interim waiver is summarized
below.
AHT is required to test and rate the
AHT commercial refrigeration
equipment multi-mode basic models
SYDNEY, MIAMI, PARIS,
MANHATTAN, MALTA, and IBIZA,
according to the alternate test procedure
as set forth in section IV, ‘‘Alternate
Test Procedure.’’
AHT is permitted to make
representations about the energy use of
this basic model for compliance,
marketing, or other purposes only to the
extent that such products have been
tested in accordance with the provisions
set forth in the alternate test procedure
and such representations fairly disclose
the results of such testing in accordance
with 10 CFR 431.66.
DOE makes decisions on waivers and
interim waivers for only those basic
models specifically set out in the
PO 00000
Frm 00034
Fmt 4703
Sfmt 4703
15347
petition, not future models that may be
manufactured by the petitioner. AHT
may request that DOE extend the scope
of a waiver or an interim waiver to
include additional basic models
employing the same technology as the
basic models set forth in the original
petition consistent with 10 CFR
431.401(g). In addition, DOE notes that
granting of an interim waiver or waiver
does not release a petitioner from the
certification requirements set forth at 10
CFR part 431. See also 10 CFR
431.401(a) and (i).
The interim waiver shall remain in
effect consistent with 10 CFR
431.401(h). Furthermore, this interim
waiver is conditioned upon the
presumed validity of statements,
representations, and documents
provided by the petitioner. DOE may
rescind or modify a waiver or interim
waiver at any time upon a
determination that the factual basis
underlying the petition for waiver or
interim waiver is incorrect, or upon a
determination that the results from the
alternate test procedure are
unrepresentative of the basic model’s
true energy consumption characteristics.
See 10 CFR 431.401(k).
IV. Alternate Test Procedure
EPCA requires that manufacturers use
DOE test procedures when making
representations about the energy
consumption and energy consumption
costs of equipment covered by the
statute. (42 U.S.C. 6293(c); 6314(d))
Consistent representations about the
energy efficiency of covered equipment
are important for consumers evaluating
equipment when making purchasing
decisions and for manufacturers to
demonstrate compliance with
applicable DOE energy conservation
standards. Pursuant to its regulations
applicable to waivers and interim
waivers from applicable test procedures
at 10 CFR 431.401, and after considering
public comments on the petition, DOE
will announce its decision as to an
alternate test procedure for AHT in a
subsequent Decision and Order.
During the period of the interim
waiver granted in this notice, AHT shall
test the multi-mode basic models listed
in section III in each mode (ice-cream
freezer, freezer, and refrigerator mode)
according to the test procedure for
commercial refrigeration equipment
prescribed by DOE at 10 CFR part 431,
subpart C, appendix B, for basic models,
with the following modifications for
defrost testing in ASHRAE 72–2005
(incorporated by reference at 10 CFR
431.63(d)), laid out in two parts:
The first part shall be a 24-hour test
starting in steady state conditions and
E:\FR\FM\28MRN1.SGM
28MRN1
15348
Federal Register / Vol. 82, No. 58 / Tuesday, March 28, 2017 / Notices
established. The defrost cycle is initiated and
terminates after the defrost cycle is complete.
The energy consumed during this defrost
cycle, ET2, and the duration of the defrost
cycle, tDI, shall be recorded.
Based on the measured energy
consumption in these two tests, the daily
energy consumption (DEC) in kWh shall be
calculated as
Where:
DEC = Daily Energy Consumption in
kilowatt-hours (kWh);
ET1 = energy expended during the first part
of the test, in kWh;
ET2 = energy expended during the second
part of the test, in kWh;
Etd = energy expended by defrosts per week
tNDI = normalized length of defrosting time
per day, in minutes;
tDS = sum of defrost time per week;
D = maximum number of defrosts per week
7 = conversion factor of days per week;
1440 = conversion factor to adjust to a 24hour period in minutes per day.
send a copy of such comments to the
petitioner. The contact information for
the petitioner’s representative is Scott
Blake Harris, Chairman, Harris,
Wiltshire & Grannis, 1919 M Street,
Eighth Floor, Washington, DC. 20036.
All comment submissions must include
the agency name and Case Number CR–
006 for this proceeding. Submit
electronic comments in WordPerfect,
Microsoft Word, Portable Document
Format (PDF), or text (American
Standard Code for Information
Interchange (ASCII)) file format and
avoid the use of special characters or
any form of encryption. Wherever
possible, include the electronic
signature of the author. DOE does not
accept telefacsimiles (faxes).
Pursuant to 10 CFR 1004.11, any
person submitting information that he
or she believes to be confidential and
exempt by law from public disclosure
should submit two copies to DOE: One
copy of the document marked
‘‘confidential’’ with all of the
information believed to be confidential
included, and one copy of the document
marked ‘‘non-confidential’’ with all of
the information believed to be
confidential deleted. DOE will make its
own determination about the
confidential status of the information
and treat it according to its
determination.
Issued in Washington, DC, on March 23,
2017.
Steven Chalk,
Acting Assistant Secretary for Energy
Efficiency and Renewable Energy.
V. Summary and Request for Comments
Through this notice, DOE announces
receipt of AHT’s petition for waiver
from the DOE test procedure for certain
basic models of AHT commercial
refrigeration equipment, and announces
DOE’s decision to grant AHT an interim
waiver from the test procedure for its
commercial refrigeration equipment.
DOE is publishing AHT’s petition for
waiver in its entirety, pursuant to 10
CFR 431.401(b)(1)(iv). The petition
contains no confidential information.
The petition includes a suggested
alternate test procedure to determine the
energy consumption of its commercial
refrigeration equipment. DOE will
consider public comments on the
petition in issuing its Decision and
Order.
DOE solicits comments from
interested parties on all aspects of the
petition, including the suggested
alternate test procedure and calculation
methodology. Pursuant to 10 CFR
431.401(d), any person submitting
written comments to DOE must also
VerDate Sep<11>2014
17:14 Mar 27, 2017
Jkt 241001
PO 00000
Frm 00035
Fmt 4703
Sfmt 4703
Before the United States Department of
Energy, Washington, DC 20585
Docket No. EERE–2013–BT–TP–0025;
In the Matter of Energy Efficiency
Program: Test Procedure for
Commercial Refrigeration Equipment
RIN 1904–AC99
I. PETITION OF AHT COOLING
SYSTEMS FOR WAIVER OF TEST
PROCEDURE FOR COMMERCIAL
REFRIGERATION EQUIPMENT
AHT Cooling Systems GmbH and
AHT Cooling Systems USA Inc.
(collectively AHT) 1 respectfully submit
this Petition for Waiver and Application
for Interim Waiver 2 from DOE’s test
procedure for commercial refrigeration
equipment.3
AHT is a world leader in the
production of plug-in refrigerators and
freezers for the commercial sector. It
currently manufactures its products in
Austria, and imports them into the
United States through its wholly-owned
subsidiary in South Carolina. AHT USA
is also about to open a new
manufacturing facility in the Charleston
1 AHT’s U.S. subsidiary is AHT Cooling Systems
USA Inc., 3235 Industry Drive, North Charleston,
South Carolina 29418 (tel. 843–767–6855). AHT’s
worldwide headquarters are AHT Cooling Systems
GmbH, Werkgasse 57, 8786 Rottenmann, Austria
(tel. 011–43–3614/2451–0).
2 See 10 CFR § 431.401 (petitions for waiver and
interim waiver).
3 Id. Part 431, Subpart C, Appendix B.
E:\FR\FM\28MRN1.SGM
28MRN1
EN28MR17.000
sradovich on DSK3GMQ082PROD with NOTICES
including eight hours of door opening
(according ASHRAE 72–2005). The energy
consumed in this test shall be recorded, ET1.
The second part shall be a defrost cycle test
starting after steady state conditions are
Federal Register / Vol. 82, No. 58 / Tuesday, March 28, 2017 / Notices
area. AHT products are distributed to
major supermarket retail chains,
convenience stores, wholesalers, and
consumer-packaged goods companies
throughout the United States and
Canada. AHT’s pursuit of innovation
has led it continuously to develop and
market cutting-edge technology. Its
philosophy focuses on sustainability,
energy efficiency, innovation, and
customer benefit. AHT’s products, as is
reflected by their use of propane as a
refrigerant, are among the most energy
efficient and environmentally friendly
in the world.
Commercial refrigeration equipment,
such as AHT’s, will soon be subject to
a new regulatory regime. This includes
new test procedures 4 and efficiency
standards.5 The new procedures will
apply to representations of energy
efficiency or use made on and after
March 28, 2017. The new standards will
apply to products manufactured on or
after March 27, 2017.
In part because of their advanced
design and features, many AHT
commercial refrigerators and freezers
cannot be fairly evaluated by DOE’s
mandated testing protocols. First,
because of their implicit assumptions, it
is not clear which of the DOE tests
should be applied to the AHT
appliances. Second, any of the DOE
tests would overstate the amount of
energy used by the AHT appliances.
Accordingly, a waiver of those test
requirements is necessary.
I. Basic Models for Which a Waiver Is
Requested
The basic models for which a waiver
is requested are set forth in Appendix I.
These models are all display
merchandisers with transparent doors.
They are distributed in commerce under
the AHT brand name.
II. Need for the Requested Waiver
As noted, the DOE test procedures
will take effect on March 28, 2017. It is
not clear which DOE test procedure
should apply to AHT’s advanced
models, and all would grossly overstate
the energy used by these models. There
are two critical features of the AHT
models that raise issues under the
forthcoming testing procedure.
sradovich on DSK3GMQ082PROD with NOTICES
A. The AHT Appliances Are MultiMode.
The AHT appliances for which we
seek a waiver are all multi-mode
models; they have three modes of
4 Id. Part 431, Subpart C, Appendix B, as adopted,
79 FR 22277 (April 21, 2014).
5 Id. § 431.66, as adopted, 79 FR 17725 (March 28,
2014).
VerDate Sep<11>2014
17:14 Mar 27, 2017
Jkt 241001
operation among which the user can
choose merely by turning a switch. In
one mode, the units operate as an ice
cream freezer. In another mode, they
operate as a regular commercial freezer.
In yet another mode, they operate as a
commercial refrigerator. The advantage
to a user of having a single appliance
that can operate in three different modes
is obvious. And if a retail operator can
purchase one appliance that can operate
in three modes, rather than having to
buy multiple appliances to meet the
same needs, there are sustainability
benefits as well. The problem is that the
DOE rules implicitly assume that an
appliance is exclusively an ice cream
freezer, exclusively a standard
commercial freezer, or exclusively a
commercial refrigerator.6 And the DOE
rules mandate different testing protocols
for an ice cream freezer than they do for
a standard commercial freezer or a
commercial refrigerator.
DOE testing rules often require that
products be tested in their default
configuration, or in the typical
configuration. In the case of the AHT
multi-mode appliances however, there
isn’t a ‘‘default’’ configuration or one
‘‘typical’’ configuration. The machines
are designed to be easily and equally
usable in all three modes. DOE
precedent also suggests that when there
is no default or typical mode for testing
purposes, products with multiple
configurations should be tested in the
most energy consumptive mode. In this
case, that would mean that AHT should
test its products in the ice cream freezer
mode and treat them as such for
regulatory purposes.
Accordingly, AHT asks for a ‘‘waiver’’
to be allowed to do precisely that.
The only obvious alternative to testing
in the most energy consumptive mode
would be to require testing in all three
modes. But such a requirement would
be unique, burdensome, and
inconsistent with the Energy Policy and
Conservation Act (EPCA), which
requires that the test procedures ‘‘shall
be reasonably designed’’ and ‘‘shall not
be unduly burdensome to conduct.’’ 7
Moreover, in this situation it is not clear
how one would evaluate whether an
appliance passed a multiple test regime,
particularly since testing the appliances
as ice cream freezers would require
using total display area (TDA) as the
normalizing metric, while testing them
in the other modes would require using
volume as a normalizing metric. Such a
testing regime would be both confusing
and burdensome.
6 Id.
7 42
PO 00000
§ 431.66.
U.S.C. 6293(b)(3).
Frm 00036
Fmt 4703
Sfmt 4703
15349
Finally, testing these appliances as ice
cream freezers makes most sense
because DOE has determined that TDA
is the best metric for display equipment
with transparent doors, and is moving
increasingly in that direction in its
testing protocols. As DOE has
concluded, ‘‘where the function is to
display merchandise for sale, TDA best
quantifies the ability of a piece of
equipment to perform that function.’’ 8
That is surely true here.
B. The AHT Appliances Do Not Have a
Typical Defrosting Cycle.
The AHT appliances are innovative,
and perhaps unique, in one other
respect: Their cooling coils are built into
the body of the units. This means the
cooling coils are not exposed to the air
and do not get covered with frost. This
also means the coils do not need to be
defrosted. The DOE test procedure
understandably assumes that
commercial refrigerators and freezers
have cooling or evaporator coils that
need to be defrosted for the equipment
to function effectively. Indeed, the
Technical Support Document for the
test procedure essentially defines
‘‘defrosting’’ to mean melting ice from
evaporator coils:
As the air in the refrigerated space is
cooled, water vapor condenses on the
surface of the evaporator coil. . . .
There are several methods available for
defrosting the evaporator coil. . .9
In addition, the ASHRAE test
procedure mandated by the DOE
regulations provides that the defrost
adequacy assurance test ‘‘shall verify
that any defrost setting and arrangement
is adequate to melt all frost and ice from
coils and flues and drain it out of the
refrigerator.’’ 10 Based on the
assumption that all refrigerators and
freezers that have evaporator coils from
which frost must be melted regularly in
order to function, the test procedure
calls for starting testing with a full
defrost cycle, and may require
additional defrost cycles in a 24-hour
period before the test is complete
(depending on the expected operation of
the model).
AHT appliances, however, have no
need to defrost their coils. Rather, small
amounts of frost can build up on the
inner walls of the cabinet when the
8 79
FR 17725, 17741 (March 28, 2014).
Technical Support Document: Energy
Efficiency Program for Consumer Products and
Commercial and Industrial Equipment; Commercial
Refrigeration Equipment (Feb. 2014), § 3.3.1.11
(Defrost Cycle; Defrost Mechanism).
10 ANSI/ASHRAE Standard 72–2005, ‘‘Method of
Testing Commercial Refrigerators and Freezers,’’
§ 7.8 (Defrost Adequacy Assurance). ASHRAE 72–
2005 is incorporated by reference in the DOE test
procedure. 10 CFR 431.63(d)(1).
9 DOE,
E:\FR\FM\28MRN1.SGM
28MRN1
Federal Register / Vol. 82, No. 58 / Tuesday, March 28, 2017 / Notices
appliances are in a freezer mode. But
this is a strictly esthetic matter that is
easily resolved. Thus, rather than
running one or more defrosting cycles a
day to keep the machines operating
efficiently, AHT appliances have a
defrost (in the generic sense rather than
as defined by DOE/ASHRAE) function
that operates just once per week to keep
the machines looking good.11 As a
result, the test procedure, which
provides for at least one full defrost
cycle in a 24-hour period is not
appropriate for these models. It would
overstate the energy usage from the
defrosting function by at least a factor
of seven.
Accordingly, AHT asks for a waiver to
test its appliances with the defrost cycle
activated in a way that reflects the
actual operation of the units. To this
end, AHT proposes to test the
appliances in two phases. Phase one
shall be a 24-hour test according to
ASHRAE 72 including eight hours of
door openings but without defrost. The
second phase should be a separate
measurement of the energy used during
the defrost cycle. One-seventh of the
measured energy in phase two should
be added to the energy measured in
phase one. This approach would
translate the once-a-week defrost cycle
into an average daily energy usage
factor.
Where
DEC = Daily Energy Consumption in
kilowatt-hours (kWh);
ET1 = energy expended during the first part
of the test, in kWh;
ET2 = energy expended during the second
part of the test, in kWh;
t
NDI = normalized length of defrosting time
per day, in minutes;
t
DI = length of time of one defrosting cycle,
in minutes;
7 = conversion factor of days per week;
1440 = conversion factor to adjust to a 24hour period in minutes per day.
applicable on and after the March 28,
2017, compliance date. Without waiver
relief, AHT will be at a competitive
disadvantage in the market for these
important products and would suffer
economic hardship. AHT would be
subject to requirements that clearly
should not apply to such products.
sradovich on DSK3GMQ082PROD with NOTICES
The waiver shall continue until DOE
adopts an applicable amended test
procedure.
IV. Request for Interim Waiver
AHT also requests an interim waiver
for its testing and rating of the basic
models listed in Appendix I. Based on
its merits, the petition for waiver is
likely to be granted. Further, it is
essential that an interim waiver be
granted, as AHT plans to distribute
units of the models that would be
affected by the DOE rule as otherwise
11 We also note that AHT appliances have a
manual override, such that a user could activate the
VerDate Sep<11>2014
18:16 Mar 27, 2017
Jkt 241001
III. Proposed Alternate Test Procedure
In line with the waivers outlined
above, AHT proposes the following
alternate test procedure to evaluate the
performance of the basic models listed
in Appendix I of this petition and
application.
Effective March 28, 2017, AHT shall
be required to test the performance of
the basic models listed in Appendix I
according to the test procedures for
commercial refrigeration equipment
prescribed by DOE at 10 CFR part 431,
Subpart C, Appendix B, except as
follows.
V. Other Manufacturers
A list of manufacturers of all other
basic models distributed in commerce
in the United States and known to AHT
to incorporate overall design
characteristic(s) similar to those found
in the basic model(s) that are the subject
of the petition is set forth in Appendix
II.
*
*
*
*
*
AHT requests expedited treatment of
the Petition and Application.
Respectfully submitted,
Scott Blake Harris
John A. Hodges
Harris, Wiltshire & Grannis LLP
1919 M Street, NW Washington, DC
defrost cycle a second time in any one week period.
PO 00000
Frm 00037
Fmt 4703
Sfmt 4703
The basic models shall be tested and
rated as ice cream freezers (Integrated
Average Temperature of ¥15 °F
+/¥2.0 °F and use of TDA).
The basic models shall be subject to
the following testing instead of the
corresponding defrost testing in the test
procedure.
THE FIRST PART shall be a 24-hour test
starting in steady state conditions and
including eight hours of door opening
(according ASHRAE Standard 72). The
energy consumed in this test shall be
recorded, ET1.
THE SECOND PART shall be a defrost
cycle test starting after steady state
conditions are established. The defrost
cycle is initiated and terminates after
the defrost cycle is complete. The
energy consumed during this defrost
cycle, ET2, and the duration of the
defrost cycle, tDI, shall be recorded.
Based on the measured energy
consumption in these two tests, the
daily energy consumption (DEC) in kWh
shall be calculated as
20036, (202) 730–1313
Counsel to AHT Cooling Systems GmbH and
AHT Cooling Systems USA Inc.
October 25, 2016
Appendix I
The waiver and interim waiver
requested herein should apply to testing
and rating of the following basic models
that are manufactured by AHT:
SYDNEY ∧ * MIAMI ∧ *
PARIS ∧ *
MANHATTAN ∧ *
MALTA ∧ * IBIZA ∧ *
II. The models use the following
model number layout:
SYDNEY, MIAMI, etc.—Represent the
name of the model platform.
(∧)—Represents characters in the model
number that correspond to the size.
(*)—Represents characters in the model
number that correspond to marketing
features.
The * and ∧ characters have no impact
on the compartment function, product
class, or test method.
BILLING CODE 6450–01–P
But the default automatic setting, and we expect the
typical use, is one defrost cycle per week.
E:\FR\FM\28MRN1.SGM
28MRN1
EN28MR17.001
15350
Federal Register / Vol. 82, No. 58 / Tuesday, March 28, 2017 / Notices
15351
APPENDIX II
The following are manufacturers of all other basic models distributed in commerce in the
United States and known to AHT to incorporate overall design characteristic(s) similar to those
found in the basic model(s) that are the subject of the petition for waiver.
HARRIS, WllTSHIRE & GRANNIS LLP I 1919 M STREET I EIGHTH FLOOR I WASHINGTON DC 20036 IT 202 730 1300 I F 202 730 130 I
VerDate Sep<11>2014
17:14 Mar 27, 2017
Jkt 241001
PO 00000
Frm 00038
Fmt 4703
Sfmt 4725
E:\FR\FM\28MRN1.SGM
28MRN1
EN28MR17.002
sradovich on DSK3GMQ082PROD with NOTICES
AMF Sales & Associates (importing LUCKDR)
ARNEGUSA
Avanti Products LLC Beverage
Air
Dellfrio (importing Liebherr cabinets)
Electrolux Home Products
Excellence
Fogel de Centroamerica S.A.
Foshan City Shunde District Sansheng Electrical Manufacture Co., Ltd.
Hill phoenix
Hussmann
Innovative Display Works Inc.
Jiangsu Baixue Electric Appliances Co., Ltd.
Metalfrio Solutions Mexico S.A.
Mimet S.A.
Minus Forty Technologies Corp. MTL
Cool
NovumUSA
Ojeda USA
Panasonic
PREMIERE Corporation
Sanden Venda
Silver King
Stajac Industries
Thermell Manufacturing
True Manufacturing Co.
Turbo-Air
Vestfrost Solutions
15352
Federal Register / Vol. 82, No. 58 / Tuesday, March 28, 2017 / Notices
6March 2017
Ms. Ashley Armstrong
Office ofEnergy Efficiency
United States Department of Energy
1000 Independent Avenue, SW
Washington, DC
Re: AHT Petition for Waiver & Interim Waiver
Dear Ashley:
We are writing to respond to your e-mail of February 21, 2017, asking for additional information
about the multi-mode commercial refrigeration equipment as to which AHT has sought a testing
watver.
As set forth in our waiver petition, the defrost cycle 1 on the six covered AHT models 2 operates
just once per week, rather than once per day as the mandated testing assumes- meaning that the
mandated testing overestimates the amount of energy actually used in the defrost cycle by a
factor of seven. As we also noted in our petition, the AHT appliances have a manual override,
such that a user could activate the defrost cycle a second time in any one week period. But the
default setting, which we expect to be the typical use, is one defrost cycle per week.
You asked, first, how the manual override worked. Simply put, the factory default is set such that
the defrost cycle operates once per week. As noted, if the customer wants an additional defrost
cycle, there is an override allowing one, and only one, additional defrost per week. AHT assures
there can be no more than two defrosts per week by setting the parameter "minimum interval
between defrosts" to 84 hours. This is equivalent to 3.5 days, and it cannot be changed by the
customer. Thus the operation of any defrost cycle means that there cannot be another defrost
cycle- whether by default or by override- for 84 hours. This defrost cycle "lock" guarantees
there can be no more than one defrost cycle in 3.5 days, or two defrost cycles in any seven-day
period. There are no other ways for the defrost cycle to operate. Specifically, there are no
controls or systems that allow ambient conditions to initiate or end a defrost cycle.
You also asked for test data showing how AHT' s proposed alternative test procedure would
work (and how long the defrost cycle operates). We have attached a PowerPoint providing this
information 3 Test 1 shows the model in question tested as a commercial refrigerator using the
It is a defrost cycle in the colloquial sense rather than as defined by DOE/ASHRAE.
The PowerPoint contains confidential, trade secret and proprietary infonnation and, thus, is entitled to
exemption from pnblic disclosnre. We thus request that it be treated in its entirely as confidential, and that it not be
disclosed to third parties. We believe it is entitled to full protection of all confidentiality and non- disclosure provisions
in the Freedom of Infonnation Act, and other statutes and rules.
HARRIS, WllTSHIRE & GRANNIS LLP
VerDate Sep<11>2014
17:14 Mar 27, 2017
Jkt 241001
I 1919 M STREET I EIGHTH
PO 00000
Frm 00039
FLOOR I WASHINGTON DC 20036 I T 202 730 1300 I F 202 730 130 I
Fmt 4703
Sfmt 4725
E:\FR\FM\28MRN1.SGM
28MRN1
EN28MR17.003
sradovich on DSK3GMQ082PROD with NOTICES
Sydney; Miami; Paris; Manhallan; Malta; and lbiza.
Federal Register / Vol. 82, No. 58 / Tuesday, March 28, 2017 / Notices
BILLING CODE 6450–01–C
DEPARTMENT OF ENERGY
Federal Energy Regulatory
Commission
[Docket No. CP17–62–000]
sradovich on DSK3GMQ082PROD with NOTICES
Gulf South Pipeline Company, LP;
Notice Extending Comment Date
On March 1, 2017, the Commission
issued a notice of application (March 1
Notice) in the above captioned
proceeding.1 To give interested parties
who were not on the original landowner
list an opportunity to comment, the
comment due date on the March 1
Notice is hereby extended from March
22, 2017 to April 12, 2017.
As stated in the March 1 Notice, in its
application, Gulf South Pipeline
Company, LP requests to amend its
certificate issued by the Commission in
Docket No. CP15–517–000 to (i) install
1 Gulf South Pipeline Co., LP, 82 FR 12,814
(2017).
VerDate Sep<11>2014
17:14 Mar 27, 2017
Jkt 241001
a gas-fired Solar Titan 130 turbine
compressor unit in place of the
currently certificated gas-fired Solar
Mars 100 turbine compressor unit at the
Magasco Compressor Station, located in
Sabine County, Texas, increasing the
horsepower from 15,748 hp to 20,482 hp
and (ii) modify the emergency generator
from an 800 brake-horsepower (bhp)
unit to a 691 bhp unit. This amendment
will not require any additional
workspace or land disturbance beyond
what has been approved by the
Commission. The estimated cost of the
amendment is approximately $3
million, all as more fully set forth in the
application which is on file with the
Commission and open to public
inspection. The filing is available for
review at the Commission in the Public
Reference Room or may be viewed on
the Commission’s Web site web at
https://www.ferc.gov using the
‘‘eLibrary’’ link. Enter the docket
number excluding the last three digits in
the docket number field to access the
document. For assistance, contact FERC
at FERCOnlineSupport@ferc.gov or call
PO 00000
Frm 00040
Fmt 4703
Sfmt 4703
toll-free, (886) 208–3676 or TYY, (202)
502–8659.
Any questions regarding this
application may be directed to Kathy D.
Fort, Manager, Certificates & Tariffs,
Gulf South Pipeline Company, LP, 9
Greenway Plaza, Suite 2800, Houston,
Texas 77046, by telephone at (713) 479–
8252, or by email to kathy.fort@
bwpmlp.com.
Pursuant to section 157.9 of the
Commission’s rules, 18 CFR 157.9,
within 90 days of this Notice 2 the
Commission staff will either: Complete
its environmental assessment (EA) and
place it into the Commission’s public
record (eLibrary) for this proceeding; or
issue a Notice of Schedule for
Environmental Review. If a Notice of
Schedule for Environmental Review is
issued, it will indicate, among other
milestones, the anticipated date for the
Commission staff’s issuance of the EA
for this proposal. The filing of the EA
in the Commission’s public record for
this proceeding or the issuance of a
2 The 90-day timeframe restarts from the date of
this notice.
E:\FR\FM\28MRN1.SGM
28MRN1
EN28MR17.004
[FR Doc. 2017–06107 Filed 3–27–17; 8:45 am]
15353
Agencies
[Federal Register Volume 82, Number 58 (Tuesday, March 28, 2017)]
[Notices]
[Pages 15345-15353]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2017-06107]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
Office of Energy Efficiency and Renewable Energy
[Case No. CR-006]
Notice of Petition for Waiver of AHT Incorporated From the
Department of Energy Commercial Refrigeration Equipment Test Procedures
and Partial Grant of Interim Waiver
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Notice of petition for waiver and partial grant of interim
waiver, and request for public comment.
-----------------------------------------------------------------------
SUMMARY: This notice announces receipt of and publishes a petition for
waiver from AHT Cooling Systems GmbH and AHT Cooling Systems USA Inc.
(AHT) seeking an exemption from specified portions of the U.S.
Department of Energy (DOE) test procedure for determining the energy
consumption of multi-mode commercial refrigeration equipment. ASHRAE
Standard 72-2005, incorporated by reference in Appendix B, does not
provide for defrost testing with built-in cooling coils into the body
of AHT's unique multi-mode commercial refrigeration equipment basic
models. Consequently, AHT submitted to DOE an alternate test procedure
that allows for testing of six specified basic models with a different
defrost cycle. This notice also announces that DOE has granted AHT an
interim waiver from the DOE commercial refrigeration equipment test
procedures for the specified commercial refrigeration equipment basic
models, subject to use of the alternative test procedure as set forth
in this notice. DOE solicits comments, data, and information concerning
AHT's petition and its suggested alternate test procedure.
DATES: DOE will accept comments, data, and information with regard to
the AHT petition until April 27, 2017.
ADDRESSES: You may submit comments, identified by Case Number CR-006,
by any of the following methods:
[[Page 15346]]
Federal eRulemaking Portal: https://www.regulations.gov.
Follow the instructions for submitting comments.
Email: AS_Waiver_Requests@ee.doe.gov. Include the case
number [Case No. CR-006] in the subject line of the message. Submit
electronic comments in WordPerfect, Microsoft Word, PDF, or ASCII file
format, and avoid the use of special characters or any form of
encryption.
Postal Mail: Mr. Bryan Berringer, U.S. Department of
Energy, Building Technologies Office, Mailstop EE-5B, Petition for
Waiver Case No. CR-006, 1000 Independence Avenue SW., Washington, DC
20585-0121. Telephone: (202) 586-0371. If possible, please submit all
items on a compact disc (CD), in which case it is not necessary to
include printed copies.
Hand Delivery/Courier: Appliance and Equipment Standards
Program, U.S. Department of Energy, Building Technologies Office, 950
L'Enfant Plaza SW., 6th Floor, Washington, DC 20024. Telephone: (202)
586-6636. If possible, please submit all items on a CD, in which case
it is not necessary to include printed copies.
Docket: The docket, which includes Federal Register notices,
comments, and other supporting documents/materials, is available for
review at www.regulations.gov. All documents in the docket are listed
in the www.regulations.gov index. However, some documents listed in the
index, such as those containing information that is exempt from public
disclosure, may not be publicly available.
FOR FURTHER INFORMATION CONTACT: Mr. Bryan Berringer, U.S. Department
of Energy, Building Technologies Office, Mailstop EE-5B, 1000
Independence Avenue SW., Washington, DC 20585-0121. Telephone: (202)
586-0371. Email: Bryan.Berringer@ee.doe.gov.
Ms. Johanna Jochum, U.S. Department of Energy, Office of the
General Counsel, GC-33, 1000 Independence Avenue SW., Washington, DC
20585-0121. Telephone: (202) 287-6307. Email:
Johanna.Jochum@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
I. Background and Authority
Title III, Part C of the Energy Policy and Conservation Act of 1975
(EPCA), Public Law 94-163 (42 U.S.C. 6311-6316, as codified)
established the Energy Conservation Program for Certain Industrial
Equipment, which includes the commercial refrigeration equipment. Part
C includes definitions, test procedures, labeling provisions, energy
conservation standards, and the authority to require information and
reports from manufacturers. Further, Part C authorizes the Secretary of
Energy to prescribe test procedures that are reasonably designed to
produce results that measure energy efficiency, energy use, or
estimated operating costs during a representative average-use cycle,
and that are not unduly burdensome to conduct. (42 U.S.C. 6314(a)(3))
The test procedure for commercial refrigeration equipment is contained
in Title 10 of the CFR part 431, subpart C, appendix B, Amended Uniform
Test Method for the Measurement of Energy Consumption of Commercial
Refrigerators, Freezers, and Refrigerator-Freezers.
DOE's regulations set forth at 10 CFR 431.401 contain provisions
that allow a person to seek a waiver from the test procedure
requirements for a particular basic model of a type of covered
industrial equipment when: (1) The petitioner's basic model for which
the petition for waiver was submitted contains one or more design
characteristics that prevent testing according to the prescribed test
procedure, or (2) the prescribed test procedures may evaluate the basic
model in a manner so unrepresentative of its true energy consumption
characteristics as to provide materially inaccurate comparative data.
10 CFR 431.401(a)(1). A petitioner must include in its petition any
alternate test procedures known to the petitioner to evaluate the basic
model in a manner representative of its energy consumption. 10 CFR
431.401(b)(1)(iii).
DOE may grant a waiver subject to conditions, including adherence
to alternate test procedures. 10 CFR 431.401(f)(2). As soon as
practicable after the granting of any waiver, DOE will publish in the
Federal Register a notice of proposed rulemaking to amend its
regulations so as to eliminate any need for the continuation of such
waiver. As soon thereafter as practicable, DOE will publish in the
Federal Register a final rule. 10 CFR 431.401(l).
The waiver process also allows DOE to grant an interim waiver if it
appears likely that the petition for waiver will be granted and/or if
DOE determines that it would be desirable for public policy reasons to
grant immediate relief pending a determination on the petition for
waiver. 10 CFR 431.401(e)(2). Within one year of issuance of an interim
waiver, DOE will either: (i) Publish in the Federal Register a
determination on the petition for waiver; or (ii) publish in the
Federal Register a new or amended test procedure that addresses the
issues presented in the waiver. 10 CFR 431.401(h)(1). When DOE amends
the test procedure to address the issues presented in a waiver, the
waiver will automatically terminate on the date on which use of that
test procedure is required to demonstrate compliance. 10 CFR
431.401(h)(2).
II. Petition for Waiver of Test Procedure and Application for Interim
Waiver
On October 25, 2016, AHT filed a petition for waiver and
application for interim waiver from the test procedure applicable to
commercial refrigeration equipment set forth in 10 CFR part 431,
subpart C, appendix B (AHT subsequently sent DOE a letter on March 6,
2017, which responded to questions from DOE. The information from this
letter is also represented in this notice). AHT has designed several
basic models multi-mode commercial refrigeration equipment that use
unique built-in cooling coils deep freeze, freeze, or refrigerate food
as needed. Because the cooling coils are built into the body of the
units and do not get covered in frost, the coils do not need to be
defrosted prior to testing. However, the DOE test procedure and ASHRAE
Standard 72-2005, incorporated by reference in Appendix B, assumes that
commercial refrigerators or freezers need to be defrosted, or melt the
ice from the evaporator coils, for the equipment to function
effectively. In particular, the test procedure requires that all
refrigerators and freezers with evaporator coils be tested with a full
defrost cycle, along with additional defrost cycles in a 24-hour
period, depending on how long the test runs (ANSI/ASHRAE Standard 72-
2005, ``Method of Testing Commercial Refrigerators and Freezers,''
Sec. 7.8 (Defrost Adequacy Assurance). ASHRAE 72-2005 is incorporated
by reference in the DOE test procedure. 10 CFR 431.63(d)(1)). AHT
appliances, however, have no need to defrost their coils. Thus, rather
than running one or more defrosting cycles a day to keep the machines
operating efficiently, AHT appliances have a defrost (in the generic
sense rather than as defined by DOE/ASHRAE) function that operates,
under standard conditions, once per week, and at most (through a manual
override) twice per week. As a result, the DOE test procedure, which
provides for at least one full defrost cycle in a 24-hour period, is
not appropriate for these models. Consequently, AHT submitted to DOE an
alternate test procedure that allows for testing of six specified basic
models with a different defrost cycle.
As previously noted, an interim waiver may be granted if it appears
likely that the petition for waiver will be granted, and/or if DOE
determines that
[[Page 15347]]
it would be desirable for public policy reasons to grant immediate
relief pending a determination of the petition for waiver. See 10 CFR
431.401(e)(2).
AHT's petition for waiver claims that the DOE test procedure at 10
CFR part 431, subpart C, appendix B does not apply to AHT's advanced
models, and would grossly overstate the energy used by these models.
These models are multi-mode (i.e., are capable of operating in the ice
cream freezer, commercial freezer, and commercial refrigerator
temperature ranges) and do not have a typical defrosting cycle (i.e.,
the cooling coils are built into the body and require defrosts once per
week).
To address multi-mode operation, AHT requested that the basic
models shall be tested and rated only for operation as ice cream
freezers (with integrated average temperature of -15[emsp14][deg]F
2.0[emsp14][deg]F and use total display area (TDA) to
determine associated energy conservation standards).
To address infrequent defrosts, AHT requested in its October 25,
2016 petition that the basic models shall be subject to an alternate
two-part test procedure. AHT specified that the first part would be a
24-hour test starting in steady state conditions and including eight
hours of door opening (according to ASHRAE Standard 72). The energy
consumed in this test would be recorded ET1. The second part would be a
defrost cycle test starting after steady state conditions were
established and ending after the defrost cycle was complete. The
duration of the defrost cycle, tDI, and the energy consumed
during the defrost cycle, ET2, would be recorded and combined with ET1
based on a once-per-week defrost frequency. In AHT's March 6, 2017
letter, AHT noted that although the standard duration of the defrost
cycle was once-per-week, the basic models have an optional manual
override that allows up to two defrost cycles per week and recommended
revising the October 25 test procedure to reflect that. DOE has
incorporated this proposal into the alternate test procedure, but
requests that AHT or commenting parties provide additional data and/or
information on how commonly the manual override is used.
With regard to the first issue, multi-mode operation, DOE has taken
the position in the most recent commercial refrigeration equipment test
procedure final rule, that self-contained equipment or remote
condensing equipment with thermostats capable of operating at
temperatures that span multiple equipment categories must be certified
and comply with DOE's regulations for each applicable equipment
category. See 79 FR 22291. In light of that policy determination, DOE
declines at this time to provide AHT an interim waiver allowing testing
only in the ice cream freezer mode. However, DOE seeks comment as part
of the waiver determination process to determine if its previously
stated position provides for a test requirement imposing an undue
burden.
Regarding the second issue of infrequent defrosts, DOE has reviewed
AHT's alternate procedure (based on the May 6, 2017 modification) and
concludes that AHT's alternate test procedure results would be
representative of the models' true energy consumptions and allow for
the accurate measurement of the energy use of these equipment, while
alleviating the testing problems associated with AHT's implementation
of commercial refrigeration equipment testing for the specified multi-
mode models. DOE also understands that absent a partial grant of an
interim waiver, AHT's equipment cannot be tested and rated for energy
consumption on a basis representative of its true energy consumption
characteristics. Consequently, DOE has determined that this part of
AHT's petition for waiver will likely be granted. Furthermore, DOE has
determined that it is desirable for public policy reasons to grant AHT
immediate relief for this part of the test procedure, pending a
determination of the petition for waiver.
III. Summary of Grant of Interim Waiver
For the reasons stated above, DOE has partially granted AHT's
application for interim waiver from testing for its specified
commercial refrigeration equipment basic models. The substance of the
interim waiver is summarized below.
AHT is required to test and rate the AHT commercial refrigeration
equipment multi-mode basic models SYDNEY, MIAMI, PARIS, MANHATTAN,
MALTA, and IBIZA, according to the alternate test procedure as set
forth in section IV, ``Alternate Test Procedure.''
AHT is permitted to make representations about the energy use of
this basic model for compliance, marketing, or other purposes only to
the extent that such products have been tested in accordance with the
provisions set forth in the alternate test procedure and such
representations fairly disclose the results of such testing in
accordance with 10 CFR 431.66.
DOE makes decisions on waivers and interim waivers for only those
basic models specifically set out in the petition, not future models
that may be manufactured by the petitioner. AHT may request that DOE
extend the scope of a waiver or an interim waiver to include additional
basic models employing the same technology as the basic models set
forth in the original petition consistent with 10 CFR 431.401(g). In
addition, DOE notes that granting of an interim waiver or waiver does
not release a petitioner from the certification requirements set forth
at 10 CFR part 431. See also 10 CFR 431.401(a) and (i).
The interim waiver shall remain in effect consistent with 10 CFR
431.401(h). Furthermore, this interim waiver is conditioned upon the
presumed validity of statements, representations, and documents
provided by the petitioner. DOE may rescind or modify a waiver or
interim waiver at any time upon a determination that the factual basis
underlying the petition for waiver or interim waiver is incorrect, or
upon a determination that the results from the alternate test procedure
are unrepresentative of the basic model's true energy consumption
characteristics. See 10 CFR 431.401(k).
IV. Alternate Test Procedure
EPCA requires that manufacturers use DOE test procedures when
making representations about the energy consumption and energy
consumption costs of equipment covered by the statute. (42 U.S.C.
6293(c); 6314(d)) Consistent representations about the energy
efficiency of covered equipment are important for consumers evaluating
equipment when making purchasing decisions and for manufacturers to
demonstrate compliance with applicable DOE energy conservation
standards. Pursuant to its regulations applicable to waivers and
interim waivers from applicable test procedures at 10 CFR 431.401, and
after considering public comments on the petition, DOE will announce
its decision as to an alternate test procedure for AHT in a subsequent
Decision and Order.
During the period of the interim waiver granted in this notice, AHT
shall test the multi-mode basic models listed in section III in each
mode (ice-cream freezer, freezer, and refrigerator mode) according to
the test procedure for commercial refrigeration equipment prescribed by
DOE at 10 CFR part 431, subpart C, appendix B, for basic models, with
the following modifications for defrost testing in ASHRAE 72-2005
(incorporated by reference at 10 CFR 431.63(d)), laid out in two parts:
The first part shall be a 24-hour test starting in steady state
conditions and
[[Page 15348]]
including eight hours of door opening (according ASHRAE 72-2005).
The energy consumed in this test shall be recorded, ET1.
The second part shall be a defrost cycle test starting after
steady state conditions are established. The defrost cycle is
initiated and terminates after the defrost cycle is complete. The
energy consumed during this defrost cycle, ET2, and the duration of
the defrost cycle, tDI, shall be recorded.
Based on the measured energy consumption in these two tests, the
daily energy consumption (DEC) in kWh shall be calculated as
[GRAPHIC] [TIFF OMITTED] TN28MR17.000
Where:
DEC = Daily Energy Consumption in kilowatt-hours (kWh);
ET1 = energy expended during the first part of the test, in kWh;
ET2 = energy expended during the second part of the test, in kWh;
Etd = energy expended by defrosts per week
tNDI = normalized length of defrosting time per day, in minutes;
tDS = sum of defrost time per week;
D = maximum number of defrosts per week
7 = conversion factor of days per week;
1440 = conversion factor to adjust to a 24-hour period in minutes
per day.
V. Summary and Request for Comments
Through this notice, DOE announces receipt of AHT's petition for
waiver from the DOE test procedure for certain basic models of AHT
commercial refrigeration equipment, and announces DOE's decision to
grant AHT an interim waiver from the test procedure for its commercial
refrigeration equipment. DOE is publishing AHT's petition for waiver in
its entirety, pursuant to 10 CFR 431.401(b)(1)(iv). The petition
contains no confidential information. The petition includes a suggested
alternate test procedure to determine the energy consumption of its
commercial refrigeration equipment. DOE will consider public comments
on the petition in issuing its Decision and Order.
DOE solicits comments from interested parties on all aspects of the
petition, including the suggested alternate test procedure and
calculation methodology. Pursuant to 10 CFR 431.401(d), any person
submitting written comments to DOE must also send a copy of such
comments to the petitioner. The contact information for the
petitioner's representative is Scott Blake Harris, Chairman, Harris,
Wiltshire & Grannis, 1919 M Street, Eighth Floor, Washington, DC.
20036. All comment submissions must include the agency name and Case
Number CR-006 for this proceeding. Submit electronic comments in
WordPerfect, Microsoft Word, Portable Document Format (PDF), or text
(American Standard Code for Information Interchange (ASCII)) file
format and avoid the use of special characters or any form of
encryption. Wherever possible, include the electronic signature of the
author. DOE does not accept telefacsimiles (faxes).
Pursuant to 10 CFR 1004.11, any person submitting information that
he or she believes to be confidential and exempt by law from public
disclosure should submit two copies to DOE: One copy of the document
marked ``confidential'' with all of the information believed to be
confidential included, and one copy of the document marked ``non-
confidential'' with all of the information believed to be confidential
deleted. DOE will make its own determination about the confidential
status of the information and treat it according to its determination.
Issued in Washington, DC, on March 23, 2017.
Steven Chalk,
Acting Assistant Secretary for Energy Efficiency and Renewable Energy.
Before the United States Department of Energy, Washington, DC 20585
Docket No. EERE-2013-BT-TP-0025;
In the Matter of Energy Efficiency Program: Test Procedure for
Commercial Refrigeration Equipment
RIN 1904-AC99
I. PETITION OF AHT COOLING SYSTEMS FOR WAIVER OF TEST PROCEDURE FOR
COMMERCIAL REFRIGERATION EQUIPMENT
AHT Cooling Systems GmbH and AHT Cooling Systems USA Inc.
(collectively AHT) \1\ respectfully submit this Petition for Waiver and
Application for Interim Waiver \2\ from DOE's test procedure for
commercial refrigeration equipment.\3\
---------------------------------------------------------------------------
\1\ AHT's U.S. subsidiary is AHT Cooling Systems USA Inc., 3235
Industry Drive, North Charleston, South Carolina 29418 (tel. 843-
767-6855). AHT's worldwide headquarters are AHT Cooling Systems
GmbH, Werkgasse 57, 8786 Rottenmann, Austria (tel. 011-43-3614/2451-
0).
\2\ See 10 CFR Sec. 431.401 (petitions for waiver and interim
waiver).
\3\ Id. Part 431, Subpart C, Appendix B.
---------------------------------------------------------------------------
AHT is a world leader in the production of plug-in refrigerators
and freezers for the commercial sector. It currently manufactures its
products in Austria, and imports them into the United States through
its wholly-owned subsidiary in South Carolina. AHT USA is also about to
open a new manufacturing facility in the Charleston
[[Page 15349]]
area. AHT products are distributed to major supermarket retail chains,
convenience stores, wholesalers, and consumer-packaged goods companies
throughout the United States and Canada. AHT's pursuit of innovation
has led it continuously to develop and market cutting-edge technology.
Its philosophy focuses on sustainability, energy efficiency,
innovation, and customer benefit. AHT's products, as is reflected by
their use of propane as a refrigerant, are among the most energy
efficient and environmentally friendly in the world.
Commercial refrigeration equipment, such as AHT's, will soon be
subject to a new regulatory regime. This includes new test procedures
\4\ and efficiency standards.\5\ The new procedures will apply to
representations of energy efficiency or use made on and after March 28,
2017. The new standards will apply to products manufactured on or after
March 27, 2017.
---------------------------------------------------------------------------
\4\ Id. Part 431, Subpart C, Appendix B, as adopted, 79 FR 22277
(April 21, 2014).
\5\ Id. Sec. 431.66, as adopted, 79 FR 17725 (March 28, 2014).
---------------------------------------------------------------------------
In part because of their advanced design and features, many AHT
commercial refrigerators and freezers cannot be fairly evaluated by
DOE's mandated testing protocols. First, because of their implicit
assumptions, it is not clear which of the DOE tests should be applied
to the AHT appliances. Second, any of the DOE tests would overstate the
amount of energy used by the AHT appliances. Accordingly, a waiver of
those test requirements is necessary.
I. Basic Models for Which a Waiver Is Requested
The basic models for which a waiver is requested are set forth in
Appendix I. These models are all display merchandisers with transparent
doors. They are distributed in commerce under the AHT brand name.
II. Need for the Requested Waiver
As noted, the DOE test procedures will take effect on March 28,
2017. It is not clear which DOE test procedure should apply to AHT's
advanced models, and all would grossly overstate the energy used by
these models. There are two critical features of the AHT models that
raise issues under the forthcoming testing procedure.
A. The AHT Appliances Are Multi-Mode.
The AHT appliances for which we seek a waiver are all multi-mode
models; they have three modes of operation among which the user can
choose merely by turning a switch. In one mode, the units operate as an
ice cream freezer. In another mode, they operate as a regular
commercial freezer. In yet another mode, they operate as a commercial
refrigerator. The advantage to a user of having a single appliance that
can operate in three different modes is obvious. And if a retail
operator can purchase one appliance that can operate in three modes,
rather than having to buy multiple appliances to meet the same needs,
there are sustainability benefits as well. The problem is that the DOE
rules implicitly assume that an appliance is exclusively an ice cream
freezer, exclusively a standard commercial freezer, or exclusively a
commercial refrigerator.\6\ And the DOE rules mandate different testing
protocols for an ice cream freezer than they do for a standard
commercial freezer or a commercial refrigerator.
---------------------------------------------------------------------------
\6\ Id. Sec. 431.66.
---------------------------------------------------------------------------
DOE testing rules often require that products be tested in their
default configuration, or in the typical configuration. In the case of
the AHT multi-mode appliances however, there isn't a ``default''
configuration or one ``typical'' configuration. The machines are
designed to be easily and equally usable in all three modes. DOE
precedent also suggests that when there is no default or typical mode
for testing purposes, products with multiple configurations should be
tested in the most energy consumptive mode. In this case, that would
mean that AHT should test its products in the ice cream freezer mode
and treat them as such for regulatory purposes.
Accordingly, AHT asks for a ``waiver'' to be allowed to do
precisely that.
The only obvious alternative to testing in the most energy
consumptive mode would be to require testing in all three modes. But
such a requirement would be unique, burdensome, and inconsistent with
the Energy Policy and Conservation Act (EPCA), which requires that the
test procedures ``shall be reasonably designed'' and ``shall not be
unduly burdensome to conduct.'' \7\ Moreover, in this situation it is
not clear how one would evaluate whether an appliance passed a multiple
test regime, particularly since testing the appliances as ice cream
freezers would require using total display area (TDA) as the
normalizing metric, while testing them in the other modes would require
using volume as a normalizing metric. Such a testing regime would be
both confusing and burdensome.
---------------------------------------------------------------------------
\7\ 42 U.S.C. 6293(b)(3).
---------------------------------------------------------------------------
Finally, testing these appliances as ice cream freezers makes most
sense because DOE has determined that TDA is the best metric for
display equipment with transparent doors, and is moving increasingly in
that direction in its testing protocols. As DOE has concluded, ``where
the function is to display merchandise for sale, TDA best quantifies
the ability of a piece of equipment to perform that function.'' \8\
That is surely true here.
---------------------------------------------------------------------------
\8\ 79 FR 17725, 17741 (March 28, 2014).
B. The AHT Appliances Do Not Have a Typical Defrosting Cycle.
The AHT appliances are innovative, and perhaps unique, in one other
respect: Their cooling coils are built into the body of the units. This
means the cooling coils are not exposed to the air and do not get
covered with frost. This also means the coils do not need to be
defrosted. The DOE test procedure understandably assumes that
commercial refrigerators and freezers have cooling or evaporator coils
that need to be defrosted for the equipment to function effectively.
Indeed, the Technical Support Document for the test procedure
essentially defines ``defrosting'' to mean melting ice from evaporator
coils:
As the air in the refrigerated space is cooled, water vapor
condenses on the surface of the evaporator coil. . . . There are
several methods available for defrosting the evaporator coil. . .\9\
---------------------------------------------------------------------------
\9\ DOE, Technical Support Document: Energy Efficiency Program
for Consumer Products and Commercial and Industrial Equipment;
Commercial Refrigeration Equipment (Feb. 2014), Sec. 3.3.1.11
(Defrost Cycle; Defrost Mechanism).
---------------------------------------------------------------------------
In addition, the ASHRAE test procedure mandated by the DOE
regulations provides that the defrost adequacy assurance test ``shall
verify that any defrost setting and arrangement is adequate to melt all
frost and ice from coils and flues and drain it out of the
refrigerator.'' \10\ Based on the assumption that all refrigerators and
freezers that have evaporator coils from which frost must be melted
regularly in order to function, the test procedure calls for starting
testing with a full defrost cycle, and may require additional defrost
cycles in a 24-hour period before the test is complete (depending on
the expected operation of the model).
---------------------------------------------------------------------------
\10\ ANSI/ASHRAE Standard 72-2005, ``Method of Testing
Commercial Refrigerators and Freezers,'' Sec. 7.8 (Defrost Adequacy
Assurance). ASHRAE 72-2005 is incorporated by reference in the DOE
test procedure. 10 CFR 431.63(d)(1).
---------------------------------------------------------------------------
AHT appliances, however, have no need to defrost their coils.
Rather, small amounts of frost can build up on the inner walls of the
cabinet when the
[[Page 15350]]
appliances are in a freezer mode. But this is a strictly esthetic
matter that is easily resolved. Thus, rather than running one or more
defrosting cycles a day to keep the machines operating efficiently, AHT
appliances have a defrost (in the generic sense rather than as defined
by DOE/ASHRAE) function that operates just once per week to keep the
machines looking good.\11\ As a result, the test procedure, which
provides for at least one full defrost cycle in a 24-hour period is not
appropriate for these models. It would overstate the energy usage from
the defrosting function by at least a factor of seven.
---------------------------------------------------------------------------
\11\ We also note that AHT appliances have a manual override,
such that a user could activate the defrost cycle a second time in
any one week period. But the default automatic setting, and we
expect the typical use, is one defrost cycle per week.
---------------------------------------------------------------------------
Accordingly, AHT asks for a waiver to test its appliances with the
defrost cycle activated in a way that reflects the actual operation of
the units. To this end, AHT proposes to test the appliances in two
phases. Phase one shall be a 24-hour test according to ASHRAE 72
including eight hours of door openings but without defrost. The second
phase should be a separate measurement of the energy used during the
defrost cycle. One-seventh of the measured energy in phase two should
be added to the energy measured in phase one. This approach would
translate the once-a-week defrost cycle into an average daily energy
usage factor.
III. Proposed Alternate Test Procedure
In line with the waivers outlined above, AHT proposes the following
alternate test procedure to evaluate the performance of the basic
models listed in Appendix I of this petition and application.
Effective March 28, 2017, AHT shall be required to test the
performance of the basic models listed in Appendix I according to the
test procedures for commercial refrigeration equipment prescribed by
DOE at 10 CFR part 431, Subpart C, Appendix B, except as follows.
The basic models shall be tested and rated as ice cream freezers
(Integrated Average Temperature of -15[emsp14][deg]F +/-
2.0[emsp14][deg]F and use of TDA).
The basic models shall be subject to the following testing instead
of the corresponding defrost testing in the test procedure.
The first part shall be a 24-hour test starting in steady state
conditions and including eight hours of door opening (according ASHRAE
Standard 72). The energy consumed in this test shall be recorded, ET1.
The second part shall be a defrost cycle test starting after steady
state conditions are established. The defrost cycle is initiated and
terminates after the defrost cycle is complete. The energy consumed
during this defrost cycle, ET2, and the duration of the defrost cycle,
tDI, shall be recorded.
Based on the measured energy consumption in these two tests, the
daily energy consumption (DEC) in kWh shall be calculated as
[GRAPHIC] [TIFF OMITTED] TN28MR17.001
Where
DEC = Daily Energy Consumption in kilowatt-hours (kWh);
ET1 = energy expended during the first part of the test, in kWh;
ET2 = energy expended during the second part of the test, in kWh;
\t\NDI = normalized length of defrosting time per day, in
minutes;
\t\DI = length of time of one defrosting cycle, in
minutes;
7 = conversion factor of days per week;
1440 = conversion factor to adjust to a 24-hour period in minutes
per day.
The waiver shall continue until DOE adopts an applicable amended
test procedure.
IV. Request for Interim Waiver
AHT also requests an interim waiver for its testing and rating of
the basic models listed in Appendix I. Based on its merits, the
petition for waiver is likely to be granted. Further, it is essential
that an interim waiver be granted, as AHT plans to distribute units of
the models that would be affected by the DOE rule as otherwise
applicable on and after the March 28, 2017, compliance date. Without
waiver relief, AHT will be at a competitive disadvantage in the market
for these important products and would suffer economic hardship. AHT
would be subject to requirements that clearly should not apply to such
products.
V. Other Manufacturers
A list of manufacturers of all other basic models distributed in
commerce in the United States and known to AHT to incorporate overall
design characteristic(s) similar to those found in the basic model(s)
that are the subject of the petition is set forth in Appendix II.
* * * * *
AHT requests expedited treatment of the Petition and Application.
Respectfully submitted,
Scott Blake Harris
John A. Hodges
Harris, Wiltshire & Grannis LLP
1919 M Street, NW Washington, DC
20036, (202) 730-1313
Counsel to AHT Cooling Systems GmbH and AHT Cooling Systems USA Inc.
October 25, 2016
Appendix I
The waiver and interim waiver requested herein should apply to
testing and rating of the following basic models that are manufactured
by AHT:
SYDNEY [supcaret] * MIAMI [supcaret] *
PARIS [supcaret] *
MANHATTAN [supcaret] *
MALTA [supcaret] * IBIZA [supcaret] *
II. The models use the following model number layout:
SYDNEY, MIAMI, etc.--Represent the name of the model platform.
([supcaret])--Represents characters in the model number that correspond
to the size.
(*)--Represents characters in the model number that correspond to
marketing features.
The * and [supcaret] characters have no impact on the compartment
function, product class, or test method.
BILLING CODE 6450-01-P
[[Page 15351]]
[GRAPHIC] [TIFF OMITTED] TN28MR17.002
[[Page 15352]]
[GRAPHIC] [TIFF OMITTED] TN28MR17.003
[[Page 15353]]
[GRAPHIC] [TIFF OMITTED] TN28MR17.004
[FR Doc. 2017-06107 Filed 3-27-17; 8:45 am]
BILLING CODE 6450-01-C