Energy Conservation Program: Test Procedure for Compact Fluorescent Lamps, 59385-59420 [2016-19967]
Download as PDF
Vol. 81
Monday,
No. 167
August 29, 2016
Part IV
Department of Energy
mstockstill on DSK3G9T082PROD with RULES4
10 CFR Parts 429 and 430
Energy Conservation Program: Test Procedure for Compact Fluorescent
Lamps; Final Rule
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
PO 00000
Frm 00001
Fmt 4717
Sfmt 4717
E:\FR\FM\29AUR4.SGM
29AUR4
59386
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[Docket No. EERE–2015–BT–TP–0014]
RIN 1904–AC74
Energy Conservation Program: Test
Procedure for Compact Fluorescent
Lamps
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
This final rule amends the
U.S. Department of Energy’s (DOE) test
procedures for medium base compact
fluorescent lamps (MBCFLs) and adopts
test procedures for new metrics for all
CFLs including hybrid CFLs and CFLs
with bases other than medium screw
base. In this final rule, DOE replaces
references to ENERGY STAR® testing
requirements with references to the
latest versions of the relevant industry
standard test methods referenced by the
ENERGY STAR testing requirements,
with certain modifications. In addition,
DOE adopts new test procedures to
support the ongoing energy
conservation standards rulemaking for
general service lamps (GSLs), the
recently revised final test procedure and
energy conservation standards for
ceiling fan light kits (CFLKs), and the
labeling requirements specified by the
Federal Trade Commission (FTC). The
test procedures will also support the
ENERGY STAR program requirements
for lamps and luminaires. Specifically,
this final rule adopts test methods for
new metrics including color rendering
index (CRI), correlated color
temperature (CCT), power factor, and
start time. DOE also adopts test
procedures for additional CFL
categories, including non-integrated
CFLs and integrated CFLs that are not
MBCFLs. This final rule also revises the
sampling plan for performance metrics
and incorporates methods to measure
standby mode power.
DATES: The effective date of this rule is
September 28, 2016. Representations
must be based on testing in accordance
with the final rule starting February 27,
2017. The incorporation by reference of
certain publications listed in this rule
was approved by the Director of the
Federal Register on September 28, 2016.
ADDRESSES: The docket, which includes
Federal Register notices, public meeting
attendee lists and transcripts,
comments, and other supporting
documents/materials, is available for
review at www.regulations.gov. All
documents in the docket are listed in
mstockstill on DSK3G9T082PROD with RULES4
SUMMARY:
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
the www.regulations.gov index.
However, some documents listed in the
index, such as those containing
information that is exempt from public
disclosure, may not be publicly
available.
A link to the docket Web page can be
found at https://www1.eere.energy.gov/
buildings/appliance_standards/
product.aspx/productid/28. This Web
page will contain a link to the docket for
this notice on the www.regulations.gov
site. The www.regulations.gov Web page
will contain simple instructions on how
to access all documents, including
public comments, in the docket.
For further information on how to
review the docket, contact Ms. Emily
Marchetti at (202) 586–6636 or by email:
medium_base_compact_fluorescent_
lamps@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Ms.
Lucy deButts, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Office, EE–2J, 1000
Independence Avenue SW.,
Washington, DC, 20585–0121.
Telephone: (202) 287–1604. Email:
medium_base_compact_fluorescent_
lamps@ee.doe.gov.
Mr. Peter Cochran, U.S. Department of
Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue
SW., Washington, DC 20585–0121.
Telephone: (202) 586–9496. Email:
peter.cochran@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final
rule incorporates by reference into part
430 specific sections of the following
industry standards:
(1) American National Standards Institute
and International Electrotechnical
Commission (ANSI) C78.901–2014, American
National Standard for Electric Lamps—
Single-Based Fluorescent Lamps—
Dimensional and Electrical Characteristics.
Copies of ANSI C78.901–2014 can be
obtained from ANSI Attn: Customer Service
Department, 25 W 43rd Street, 4th Floor,
New York, NY, 10036, or by going to https://
webstore.ansi.org/.
(2) CIE 13.3–1995 (‘‘CIE 13.3’’), Technical
Report: Method of Measuring and Specifying
Colour Rendering Properties of Light
Sources, 1995, ISBN 3 900 734 57 7.
(3) CIE 15:2004 (‘‘CIE 15’’), Technical
Report: Colorimetry, 3rd edition, 2004, ISBN
978 3 901906 33 6.
Copies of CIE 13.3 and CIE 15 can be
obtained from Commission Internationale de
l’Eclairage, Central Bureau, Kegelgasse 27, A–
1030, Vienna, Austria, 011 + 43 1 714 31 87
0, or by going to https://www.cie.co.at.
(4) IEC 62301 (‘‘IEC 62301–W’’), Household
electrical appliances—Measurement of
standby power (Edition 2.0, 2011–01).
A copy of IEC 62301 can be obtained from
the American National Standards Institute,
25 W. 43rd Street, 4th Floor, New York, NY
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
10036, (212) 642–4900, or by going to https://
webstore.ansi.org.
(5) Illuminating Engineering Society of
North America (IES) LM–54–12, IES Guide to
Lamp Seasoning.
(6) IES LM–65–14, IES Approved Method
for Life Testing of Single-Based Fluorescent
Lamps.
(7) IES LM–66–14, (‘‘IES LM–66’’), IES
Approved Method for the Electrical and
Photometric Measurements of Single-Based
Fluorescent Lamps.
(8) IESNA LM–78–07, IESNA Approved
Method for Total Luminous Flux
Measurement of Lamps Using an Integrating
Sphere Photometer. Copies of IES LM–54–12,
IES LM–65–14, IES LM–66 and IES LM–78–
07 can be obtained from IES, 120 Wall Street,
Floor 17, New York, NY 10005–4001, or by
going to www.ies.org/store.
For a further discussion of these
standards, see section IV.M.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Final Rule
III. Discussion
A. Amendments to Appendix W to Subpart
B of 10 CFR part 430
1. Updates to Industry Test Methods
2. Clarifications to General Test Conditions
and Setup
3. Clarifications to Definitions
4. Test Procedures for Existing and New
Metrics
5. Test Procedures for New CFL Categories
6. Test Procedure for Standby Mode Energy
Consumption
7. Rounding Values
B. Amendments to Definitions at 10 CFR
430.2
1. Compact Fluorescent Lamp
2. Correlated Color Temperature
3. Lifetime of a Compact Fluorescent Lamp
C. Amendments to Materials Incorporated
by Reference at 10 CFR 430.3
D. Amendments to 10 CFR 430.23(y)
E. Amendments to Laboratory
Accreditation Requirements at 10 CFR
430.25
F. Clarifications to Energy Conservation
Standard Text at 10 CFR 430.32(u)
1. Initial Lamp Efficacy
2. Lumen Maintenance at 1,000 Hours
3. Lumen Maintenance at 40 Percent of
Lifetime
4. Rapid Cycle Stress Test
5. Lifetime
G. Amendments to Certification Report
Requirements
H. Amendments to 10 CFR 429.35
1. Initial Lamp Efficacy and Lumen
Maintenance
2. Rapid Cycle Stress Testing
3. Lifetime of a Compact Fluorescent Lamp
4. New Metrics
5. Reuse of Samples
6. Lamp Failures
I. Federal Trade Commission (FTC)
Labeling Requirements
J. Effective Date
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Description of Materials Incorporated
by Reference
N. Congressional Notification
V. Approval of the Office of the Secretary
mstockstill on DSK3G9T082PROD with RULES4
I. Authority and Background
A. Authority
Title III of the Energy Policy and
Conservation Act of 1975 (42 U.S.C.
6291, et seq.; ‘‘EPCA’’ or, ‘‘the Act’’) sets
forth a variety of provisions designed to
improve energy efficiency.1 Part B of
title III, which for editorial reasons was
redesignated as Part A upon
incorporation into the U.S. Code (42
U.S.C. 6291–6309, as codified),
established the ‘‘Energy Conservation
Program for Consumer Products Other
Than Automobiles.’’ CFLs are among
the consumer products affected by these
provisions.
Under EPCA, the energy conservation
program consists essentially of four
parts: (1) Testing, (2) labeling, (3)
Federal energy conservation standards,
and (4) certification and enforcement
procedures. The testing requirements
consist of test procedures that
manufacturers of covered products must
use as the basis for (1) certifying to DOE
that their products comply with the
applicable energy conservation
standards adopted under EPCA (42
U.S.C. 6295(s)) and (2) making
representations about the energy use or
efficiency of the products (42 U.S.C.
6293(c)).
EPCA sets forth the criteria and
procedures DOE must follow when
prescribing or amending test procedures
for covered products. EPCA provides, in
relevant part, that any new or amended
test procedure shall be reasonably
designed to produce test results that
measure energy efficiency, energy use,
or estimated annual operating cost of a
covered product during a representative
average use cycle or period of use, and
shall not be unduly burdensome to
conduct. (42 U.S.C. 6293(b)(3))
1 All references to EPCA refer to the statute as
amended through the Energy Efficiency
Improvement Act of 2015, Public Law 114–11
(April 30, 2015).
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
In addition, if DOE determines that a
test procedure amendment is warranted,
it must publish a proposed test
procedure and offer the public an
opportunity to present oral and written
comments. (42 U.S.C. 6293(b)(2))
Finally, in any rulemaking to amend a
test procedure, DOE must determine to
what extent, if any, the proposed test
procedure would alter the measured
energy efficiency of the covered product
as determined under the existing test
procedure. (42 U.S.C. 6293(e)(1))
EPCA also requires that, at least once
every 7 years, DOE evaluate test
procedures for each type of covered
equipment, including MBCFLs, to
determine whether amended test
procedures would more accurately or
fully comply with the requirements for
the test procedures to not be unduly
burdensome to conduct and be
reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle. (42 U.S.C. 6293(b)(1)(A))
Finally, EPCA directs DOE to amend
its test procedures for all covered
products to integrate measures of
standby mode and off mode energy
consumption, if technically feasible. (42
U.S.C. 6295(gg)(2)(A)) DOE has
determined that, while no CFLs are
capable of operating under off mode,
some CFLs are capable of operating
under standby mode. Consequently,
DOE adopts a test procedure for
measuring standby mode power in
appendix W, as detailed in section
III.A.6 of this final rule.
B. Background
The Energy Policy Act of 2005 (Public
Law 109–58) amended EPCA to require
that MBCFL test procedures be based on
the August 2001 version of the ENERGY
STAR® Program Requirements for CFLs.
(42 U.S.C. 6293(b)(12)) Consistent with
this requirement, DOE published a final
rule on December 8, 2006 (December
2006 final rule) that established DOE’s
current test procedures for MBCFLs
under 10 CFR part 430, subpart B,
appendix W. 71 FR 71340. The
December 2006 final rule established
test procedures for initial lamp efficacy,
lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of
lifetime, rapid cycle stress test, and
lifetime for MBCFLs. Id.
EPCA, however, also requires that at
least once every 7 years, DOE must
conduct an evaluation of all covered
products and either amend the test
procedures (if the Secretary determines
that amended test procedures would
more accurately or fully comply with
the requirements of 42 U.S.C.
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
59387
6293(b)(3)) or publish a determination
in the Federal Register not to amend
them. (42 U.S.C. 6293(b)(1)(A)) The
ENERGY STAR Program Requirements
for CFLs have been updated several
times since 2001 to reflect current best
practices and technological
developments. This final rule amends
the CFL test procedure to directly
reference the latest industry standards
in accordance with this EPCA
requirement.
On July 31, 2015, DOE issued a NOPR
(July 2015 NOPR) to amend and expand
its test procedures for CFLs. 80 FR
45723. DOE then held a public meeting
to discuss these proposed amendments
on August 31, 2015, and allowed for
written comments to be submitted
through October 14, 2015. This rule
addresses comments that were received
on the proposal and finalizes many of
the proposed changes to appendix W to
subpart B of 10 CFR part 430 and to 10
CFR part 429.
II. Synopsis of the Final Rule
In this final rule, DOE replaces the
existing references to ENERGY STAR
program requirements with direct
references to the latest versions of the
appropriate industry test methods from
the Illuminating Engineering Society of
North America (IES) (see section III.A.1
for further details). Directly referencing
the latest industry standards will allow
DOE to adopt current best practices and
technological developments in its test
procedures.
DOE also adopts, in this rule, test
procedures for additional CFL categories
and metrics to support energy
conservation standard rulemakings for
GSLs and CFLKs. DOE’s existing test
procedures apply only to integrated
CFLs with medium screw bases (i.e.,
MBCFLs). Integrated CFLs (also referred
to as self-ballasted or integrally
ballasted) contain all components
necessary for the starting and stable
operation of the lamp, do not include
any replaceable or interchangeable
parts, and are connected directly to a
branch circuit through an American
National Standards Institute (ANSI) base
and corresponding ANSI standard lampholder (socket). Non-integrated CFLs
(also referred to as pin-base) require an
external ballast to function, and mainly
have pin bases, (e.g., 2-pin or 4-pin). On
March 17, 2016, DOE issued a NOPR
(March 2016 NOPR) that proposes a new
definition for general service lamp that
includes both non-integrated CFLs and
integrated CFLs. 81 FR 14527. The
March 2016 NOPR also proposes
minimum efficacy and power factor
standards for certain types of general
service lamps and additional metrics for
E:\FR\FM\29AUR4.SGM
29AUR4
59388
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
MBCFLs. On January 6, 2016, DOE
issued a final rule (January 2016 final
rule) establishing amended energy
conservation standards for CFLs, both
integrated and non-integrated, packaged
with a CFLK. 81 FR 579.
DOE is also adopting these new test
procedures to support: (1) The Federal
Trade Commission (FTC) labeling
requirements for lighting products as
specified in 16 CFR 305.15; and (2) the
U.S. Environmental Protection Agency’s
ENERGY STAR program for lamps and
luminaires. Under the FTC Lighting
Facts labeling requirement,
manufacturers are required to include
basic and consistent information about
certain types of light bulbs (lamps)
including information about the lumen
output, input power, life, and correlated
color temperature (CCT) on the lamp
packaging. Regarding ENERGY STAR,
DOE’s adopted CFL test procedure
provides test methods for certain
metrics included in the ENERGY STAR
specification for lamps 2 and
luminaires.3 The ENERGY STAR lamps
specification includes, among others,
metrics for initial lamp efficacy, lumen
maintenance at 1,000 hours, lumen
maintenance at 40 percent of lifetime,
rapid cycle stress test, lifetime, CCT,
color rendering index (CRI), power
factor, and start time. The ENERGY
STAR luminaires specification includes,
among others, metrics for efficacy,
lumen maintenance at 40 percent of
lifetime, lifetime, CCT, CRI, power
factor, and start time.
Table II.1 summarizes the metrics
adopted in this final rule and which
agency requires them.
TABLE II.1—CFL METRICS IN DOE REGULATIONS, FTC LABELING REQUIREMENTS, AND THE ENERGY STAR PROGRAM
DOE proposed or established regulations
EPA ENERGY
STAR program
for lamps or
luminaires
GSL
CFLK
FTC labeling
requirements
X
—
X
X
X
X
X
X
X
X
X
—
—
X
X
X
X
—
—
—
X
X
—
—
—
X
—
—
—
—
X
X
X
X
X
X
X
X
X
X
*
—
—
—
—
X
—
—
—
—
—
—
—
—
—
X
X
X
X
X
Metric
MBCFL
Integrated CFLs
Efficacy .................................................................................
CCT ......................................................................................
CRI .......................................................................................
Lumen maintenance at 1,000 hours ....................................
Lumen maintenance at 40% of lifetime ...............................
Lifetime .................................................................................
Rapid Cycle Stress Test ......................................................
Power Factor ........................................................................
Start Time ............................................................................
Standby Mode Energy Consumption ...................................
X
........................
........................
X
X
X
X
........................
........................
........................
Non-Integrated CFLs
Efficacy .................................................................................
CCT ......................................................................................
CRI .......................................................................................
Lumen maintenance at 40% of lifetime ...............................
Lifetime .................................................................................
—
—
—
—
—
* In the March 2016 NOPR, DOE notes that the backstop provision in 6296(i)(6)(A)(v) is automatically triggered. The backstop provision requires all lamps that meet the definition of a general service lamp (which includes many non-integrated compact fluorescent lamps) comply with
a minimum efficacy standard of 45 lumens per watt. 81 FR 14528, 14540 (March 17, 2016).
mstockstill on DSK3G9T082PROD with RULES4
Additionally, DOE establishes a test
procedure for CFL standby mode power
measurement, as directed by EPCA.
However, this test procedure will only
apply to integrated CFLs because nonintegrated CFLs are not capable of
standby mode operation (see section
III.A.6).
Finally, DOE also revises the current
sampling plan in 10 CFR 429.35. This
revised sampling plan is consistent with
ENERGY STAR Lamps Specification
V2.0, as detailed in section III.H.
III. Discussion
1. Updates to Industry Test Methods
DOE’s existing MBCFL test
procedures contained in appendix W to
subpart B of 10 CFR part 430 are based
on the August 2001 version of the
ENERGY STAR program requirements
for CFLs,4 which has since been
updated several times. In the July 2015
NOPR, DOE proposed replacing the
existing references to ENERGY STAR
program requirements with direct
references to the latest versions of the
appropriate industry test methods from
the IES. DOE explained that directly
referencing the latest industry standards
would allow DOE to adopt current best
practices and technological
developments in its test procedures. As
a result, DOE proposed to directly
incorporate by reference in appendix W
the latest versions of the following
industry test procedures: IES LM–66–
14,5 IES LM–65–14,6 and IES LM–54–
12.7 DOE also proposed to no longer
incorporate by reference the August
2001 version of the ENERGY STAR
Program Requirements for CFLs,
previously approved for appendix W.
2 ENERGY STAR® Program Requirements Product
Specification for Lamps (Light Bulbs), Eligibility
Criteria, Version 2.0. December 31, 2015.
Washington, DC. https://www.energystar.gov/sites/
default/files/ENERGY%20STAR%20Lamps%20V2_
0%20Program%20Requirements.pdf.
3 ENERGY STAR® Program Requirements Product
Specification for Luminaires (Light Fixtures),
Eligibility Criteria, Version 2.0. May 29, 2015.
Washington, DC. https://www.energystar.gov/sites/
default/files/asset/document/
Luminaires%20V2%200%20Final.pdf.
4 ENERGY STAR® Program Requirements for
CFLs Partner Commitments, Version 2.0,
Washington, DC (Aug. 9, 2001).
www.energystar.gov/ia/partners/product_specs/
program_reqs/archive/CFLs_Program_
RequirementsV2.0.pdf.
5 IES Approved Method for the Electrical and
Photometric Measurements of Single-Based
Fluorescent Lamps (approved December 30, 2014).
6 IES Approved Method for Life Testing of SingleBased Fluorescent Lamps (approved December 30,
2014).
7 IES Guide to Lamp Seasoning (approved
October 22, 2012).
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
A. Amendments to Appendix W to
Subpart B of 10 CFR part 430
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
DOE compared the currently
referenced versions and the new
updated versions of the relevant
industry standards to determine, as
directed by EPCA, whether adopting the
latest industry standards would alter
measured energy efficiency for MBCFLs
as determined under the current DOE
test procedure. DOE determined that
these changes would have a de minimis
effect on measured values.
Both the National Electrical
Manufacturers Association (NEMA) and
OSRAM SYLVANIA, Inc. (OSI)
supported the incorporation by
reference of IES LM–66–14 and IES LM–
65–14 stating that it would not
significantly affect the testing or
measured values. (NEMA, No. 9 at pp.
3,8; OSI, No. 5 at pp. 2–3) 8
DOE received comments regarding the
provisions on cycling lamps during
seasoning in IES LM–54–12. Under the
current test procedure, in accordance
with IES LM–54–1991, all lamps are
seasoned at a 3 hour on, 20 minute off
cycle for 100 operating hours. The latest
version of the standard, IES LM–54–12,
also specifies that lamps that are to be
lifetime tested shall be cycled during
seasoning. However, IES LM–54–12
does not specify a specific operating
cycle during seasoning for lifetime
testing. IES LM–54–12 also states that
lamps to be tested for other performance
metrics can be continuously burned (not
cycled) during seasoning to shorten the
time required for seasoning. In the July
2015 NOPR, DOE tentatively
determined that not providing a specific
operating cycle during seasoning for
lifetime testing and not requiring
cycling during seasoning for other
performance metrics would have a de
minimis impact on measured values.
The California Investor Owned
Utilities (CA IOUs) 9 and the Energy
Efficiency Advocates (EEAs),10
however, disagreed and recommended
that DOE require lamps to be cycled
(operated 3 hours and then turned off
8 DOE identifies comments received in response
to the July 2015 CFL TP NOPR on Docket No.
EERE–2015–BT–TP–0014 by the commenter, the
document number as listed in the docket
maintained at www.regulations.gov, and the page
number of that document where the comment
appears (for example: OSI, No. 5 at p. 7). If a
comment was made verbally during the August
2015 NOPR public meeting, DOE
9 The CA IOUs are Pacific Gas and Electric
Company (PG&E), Southern California Gas
Company (SCG), San Diego Gas and Electric
Company (SDG&E), and Southern California Edison
(SCE).
10 The EEAs are the Appliance Standards
Awareness Project (ASAP), American Council for
an Energy Efficient Economy (ACEEE), Alliance to
Save Energy (ASE), Natural Resources Defense
Council (NRDC), Northeast Energy Efficiency
Partnerships (NEEP), and Northwest Energy
Efficiency Alliance (NEEA).
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
for 20 minutes) during seasoning as was
specified in IES LM–54–1991. (CA
IOUs, No. 7 at p. 3; EEAs, No. 8 at p.
4)
DOE continues to find that cycling
during seasoning would have a de
minimis impact on measured values.
However, in this final rule, in order to
establish a more consistent test
procedure, DOE specifies cycling during
seasoning for all metrics. As discussed
in section III.H.5, in this final rule, DOE
requires that the same set of lamps be
used for measurement of initial lamp
efficacy, lumen maintenance, lifetime,
color measurements, start time, and
power factor. Because of this
requirement to use the same set of
lamps and the specification in IES LM–
54–12 that lamps should be cycled
during seasoning for lifetime
measurements, lamps used in DOE’s test
procedure must be cycled during
seasoning for all other measurements as
well. Rapid cycle stress testing is
conducted on a unique set of lamps—a
separate set of lamps than used for all
other metrics. However, DOE requires in
this final rule that lamps used for rapid
cycle stress testing also be cycled while
seasoned and thereby provides a
consistent methodology for seasoning
across all metrics.
To provide further consistency and
specificity in test method, in this final
rule, DOE specifies in this test
procedure how to cycle lamps.
Although section 6.2.2.1 of LM–54–12
states that for lifetime testing, lamps
should be cycled during seasoning, IES
LM–54–12 does not define the cycling
time. IES LM–54–1991 required that all
lamps be seasoned at a 3 hour (180
minutes) on, 20 minute off cycle for 100
operating hours. Additionally, section
6.4 of IES LM–65–14 states that the
standard life operating cycle shall be
180 minutes on, 20 minutes off.
Therefore, in this final rule, DOE
specifies in section 3.1.3 of appendix W
that lamps must be cycled during
seasoning, and the operating cycle must
be 180 minutes on, 20 minutes off in
accordance with section 6.4 of IES LM–
65–14. In this final rule, DOE
incorporates by reference IES LM–54–
12, and supplements its seasoning
requirements with the additional
requirements noted in this section.
DOE also received several comments
regarding how industry standards
incorporated by reference should be
cited within the DOE test procedure.
Both NEMA and OSI commented that in
the NOPR, DOE proposed text copied
directly from the referenced industry
standards for incorporation into the
CFR. NEMA recommended that instead,
DOE should incorporate these
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
59389
publications by reference, ensuring that
interested parties understand the
context. (NEMA, No. 9 at p. 2; OSI, No.
5 at p. 2) Philips Lighting (Philips)
expressed concern that when the DOE
test procedure deviates from a
document incorporated by reference it
adds another level of complexity and
possibly leads to confusion. (Philips,
Public Meeting Transcript, No. 4 at pp.
83–84) As a solution, Philips suggested
that DOE provide specific instructions
to the testing laboratory like ENERGY
STAR and other programs. (Philips,
Public Meeting Transcript, No. 4 at p.
68) Westinghouse stated that, although
they preferred DOE incorporate by
reference the entire document, it was
acceptable if only portions can be
referenced. Westinghouse stated that it
can cause confusion when DOE makes
modifications such that something not
in the referenced standard is included
in the DOE test procedure. In particular,
when auditing a test lab, Westinghouse
noted that the lab may meet
requirements based on the referenced
standard but not based on DOE’s test
procedure. (Westinghouse, Public
Meeting Transcript, No. 4 at p. 85)
DOE appreciates the feedback related
to incorporation by reference of industry
standards as well as ways to improve
the clarity of DOE’s test procedure. In
the NOPR and in this final rule, DOE
did not include text in the regulatory
language copied directly from an
industry standard and instead
incorporated by reference relevant
industry standards in 10 CFR 430.3 and
referenced sections of the incorporated
industry standards as relevant in DOE’s
test procedures. DOE lays out
instructions regarding the test setup
conditions, test methods, and
measurements for each CFL metric in
appendix W. In these instructions, DOE
references relevant sections of industry
standards, and provides further
clarification as needed. To generate
reliable and consistent results, DOE, in
some instances, provides further
clarification and/or exceptions to the
industry standards referenced. For
example, appendix W states that lamps
should be seasoned according to
sections 4, 5, 6.1, and 6.2.2.1 of IES LM–
54–12. To reduce test burden, DOE
provides further clarification in
appendix W that time during seasoning
can be counted toward time to failure
and lumen maintenance at 40 percent of
lifetime (see section III.A.2.e for further
details). IES LM–54–12 states that, for
lifetime testing, lamps shall be cycled
during seasoning, and for all other
performance metrics, lamps can be
continuously burned during seasoning.
E:\FR\FM\29AUR4.SGM
29AUR4
59390
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
To ensure consistent seasoning
requirements across all metrics, DOE
requires in this final rule that, for all
metrics, including lifetime, lamps must
be cycled during seasoning (as noted in
this section). Therefore, DOE’s test
procedure in appendix W is streamlined
to provide, at each step, only the
relevant sections of industry standards,
and any related additional instructions
and/or clarifications specific to the DOE
test procedure. In summary, DOE finds
that the test procedures for CFLs as
prescribed in this final rule address the
concerns of interested parties to provide
clear, unambiguous instruction
regarding the appropriate procedures for
testing CFLs.
mstockstill on DSK3G9T082PROD with RULES4
2. Clarifications to General Test
Conditions and Setup
a. Instrumentation
In the July 2015 NOPR, DOE proposed
that photometric measurements
including lumen output, CCT, and CRI
be carried out in an integrating sphere.
DOE made this proposal because of
potential differences in measured values
when conducting testing with an
integrating sphere versus a
goniophotometer and certain issues
with the use of goniophotometers. DOE
received comments related to its
proposal to only allow the use of
integrating spheres for photometric
measurements. P.R. China noted that
although the integrating sphere method
is simpler, the goniophotometer
measures luminous flux using an
absolute method and is therefore more
accurate. Specifically, P.R. China argued
that the goniophotometer method
should be allowed because integrating
spheres might lead to errors with largesized lamps or lamps with special
shapes. P.R. China added that additional
testing cost and/or burden could be
introduced by only allowing the use of
integrating spheres. (P.R. China, No. 10
at p. 3) However, NEMA and OSI were
supportive of using only an integrating
sphere for testing. (NEMA, No. 9 at p.
3; OSI, No. 5 at p. 3)
Both the integrating sphere and
goniophotometer methods are allowed
in IES LM–66–14. DOE understands that
both these methods are valid ways to
take photometric measurements.
However, DOE is concerned about the
potential difference in measured values
generated from the two different
measurement approaches. Because DOE
test procedures must yield repeatable
and reproducible results and
comparable measured values, DOE
determined that it must specify one
method of measurement. DOE believes
that the integrating sphere method is
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
preferable to the goniophotometer
method because of certain issues that
make goniophotometer testing more
variable and potentially less accurate.
The goniophotometer is potentially
problematic for lamps that emit light in
all directions as the setup may result in
a dead angle where some part of the
light output is blocked by the
equipment (e.g., the arm in which the
lamp is held). The goniophotometer
method also requires a precise scanning
resolution that may differ by lamp and
is not subject to a specific industry
requirement that could provide
consistency across measurements.
Integrating spheres can come in a range
of sizes and can accordingly be used to
test a variety of sizes and shapes of
lamps, including linear fluorescent
lamps, which are much larger than
CFLs. Therefore, DOE is not aware of
any constraints or limitations regarding
testing CFLs using integrating spheres.
DOE also proposed to incorporate by
reference IESNA LM–78–07 in the July
2015 NOPR, which provides more
specific guidance on measuring lumen
output in an integrated sphere. DOE did
not receive any comments related to
IESNA LM–78–07.
For these reasons, DOE requires that
all photometric measurements,
including lumen output, CCT, and CRI,
must be carried out using the integrating
sphere method. Additionally, to provide
a method for measuring lumen output in
an integrating sphere, DOE incorporates
by reference IESNA LM–78–07.
b. Ambient Temperature
In the July 2015 NOPR, DOE proposed
that photometric and electrical testing of
CFLs must be conducted at an ambient
temperature of 25 ± 1 °C. 80 FR 45731.
Section 4.3 of IES LM–66–14 states that
the ambient temperature during
photometric and electrical testing must
be maintained at 25 ± 1 °C unless the
CFL is designed to perform optimally
under non-standard conditions. Similar
requirements and allowance were given
in IES LM–66–1991. DOE’s review of
manufacturer-published product
literature suggests that photometric and
electrical testing of CFLs is typically
conducted at the standard 25 ± 1 °C
temperature conditions and possible
inconsistencies could arise between
represented values if testing occurred at
other temperatures.
OSI commented that the ambient
temperature requirement of 25 ± 1 °C is
acceptable for most lamps, but not for
non-integrated lamps specifically
designed for high ambient temperature
operation. (OSI, No. 5 at p. 3) General
Electric (GE) was also supportive of the
temperature range for testing for most
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
products, but requested an exclusion for
products that are specifically designed
for high ambient temperatures. (GE,
Public Meeting Transcript, No. 4 at pp.
32–33) NEMA commented that nonintegrated lamps specifically designed
for high ambient temperature operation
should not be tested at 25 °C. (NEMA,
No. 9 at p. 3)
DOE understands the concerns of
interested parties, but believes that it is
important to establish test procedures
that provide a consistent set of
measurements. That is, DOE believes
that adopting a consistent rating
condition across all CFL models will
make the results more comparable
among CFL models.
c. Input Voltage
In the July 2015 NOPR, DOE proposed
that if rated input voltage is a range that
includes 120 volts (V), the CFL must be
operated at 120 V when conducting the
DOE test procedures. If the CFL can be
operated with multiple rated input
voltages and is not rated for 120 V, the
CFL must be operated at the highest
rated input voltage. DOE determined
that requiring testing at a single input
voltage would limit testing variation
and ensure more accurate and
consistent measurements of time to
failure (see sections III.A.3.a and
III.A.4.b). In addition, section 5.1.1 of
IES LM–65–14 specifies that when the
rated input voltage of a lamp or ballast
is a range, a nominal value should be
selected for lifetime testing and reported
as a test condition. 80 FR 45732. NEMA
supported DOE’s proposal regarding
testing input voltage. (NEMA, No. 9 at
p. 3) DOE received no other comments
regarding input voltage. In this final
rule, DOE adopts a testing voltage
requirement that if a rated input voltage
is a range that includes 120 V, the CFL
must be operated at 120 V. If the CFL
with multiple rated input voltages is not
rated for 120 V, the CFL must be
operated at the highest rated input
voltage.
d. Lamp Orientation
In the July 2015 NOPR, DOE proposed
a clarification that lamp orientation
must be maintained throughout all
testing, including preparation (e.g.,
seasoning and preburning), storage, and
handling between tests. The intent of
DOE’s proposal was to minimize
changes in lamp operating
characteristics between various stages of
testing and allow for more accurate and
repeatable measurements. 80 FR 45732.
NEMA supported DOE’s proposal of
maintaining lamp orientation. (NEMA,
No. 9 at p. 3) DOE received no other
comments regarding lamp orientation.
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
In this final rule, DOE adopts a
requirement that lamp orientation must
be maintained throughout all testing,
including preparation (e.g., seasoning
and preburning), storage, and handling
between tests.
mstockstill on DSK3G9T082PROD with RULES4
e. Lamp Seasoning
In the July 2015 NOPR, DOE proposed
that the seasoning requirements in IES
LM–54–12 must be followed prior to the
testing of all CFLs. DOE also proposed
two additional provisions related to
lamp seasoning. First, DOE proposed
that unit operating time during
seasoning may be counted toward
lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of
lifetime, and time to failure if the
required operating cycle and test
conditions are satisfied as stated in the
test method for time to failure. This
would reduce testing burden by
minimizing the overall testing time
required for measuring time to failure
and lumen maintenance values. Second,
DOE proposed to require that, if a lamp
breaks, becomes defective, fails to
stabilize, exhibits abnormal behavior
such as swirling prior to the end of the
seasoning period, or stops producing
light, the lamp must be replaced with a
new unit. 80 FR 45732.
NEMA was supportive of the
proposed seasoning requirements.
(NEMA, No. 9 at p. 3) DOE received
several comments regarding its proposal
that a lamp that fails during seasoning
should not be included in the sample
set to determine the represented value
of metrics. DOE addresses these
comments in section III.H.6.
In this final rule, DOE adopts the
clarifications regarding seasoning as
noted in this section. As previously
stated in section III.A.1, to provide
consistency in test methodology, DOE
also requires in this final rule that lamps
must be cycled during seasoning for all
measurements and specifies an
operating cycle of 180 minutes on and
20 minutes off in accordance with
section 6.4 of IES LM–65–14.
f. Lamp Stabilization
In the July 2015 NOPR, DOE proposed
to disallow the ‘‘peak’’ method provided
in Annex B of IES LM–66–14, which
can serve as a time saving alternative to
the stabilization method specified in
section 6.2.1 of IES LM–66–14. IES LM–
66–14 states that the information in the
Annex is not intended to be a
recommended procedure, but is
presented as reference information; it
also notes that the stabilization method
specified in section 6.2.1 is preferred
because considerable testing and
experience with a given lamp design
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
may be required due to the number of
lamp designs and process variations that
exist when conducting the peak
according to Annex B. Because of the
variabilities that could arise from testing
using the peak method, DOE concluded
that the peak method could cause
inconsistent and potentially inaccurate
results. 80 FR 45732.
NEMA supported DOE’s proposal.
(NEMA, No. 9 at p. 3) DOE received no
other comments regarding the ‘‘peak’’
method for stabilization. In this final
rule, DOE disallows the ‘‘peak’’ method
provided for reference in Annex B of
IES LM–66–14.
g. Simulated Fixtures During Time to
Failure Testing
In the July 2015 NOPR, DOE proposed
not to allow the use of simulated
fixtures during time to failure testing of
CFLs. This proposal would remove
potential variation in the testing of CFLs
and ensure that all CFLs are tested in a
consistent manner. 80 FR 45732.
NEMA supported this proposal.
(NEMA, No. 9 at p. 3) DOE received no
other comments regarding testing of
lamps in fixtures. In this final rule, DOE
disallows the use of simulated fixtures
during time to failure testing of CFLs.
h. Ballasted Adapters
In the July 2015 NOPR, DOE proposed
that CFLs packaged with or designed
exclusively for use with ballasted
adapters must be tested as nonintegrated CFLs, without the inclusion
of the ballasted adapter. DOE proposed
to define a ‘‘ballasted adapter’’ as a
ballast that is not permanently attached
to a CFL, has no consumer-replaceable
components, and serves as an adapter
by incorporating both a lamp socket and
a lamp base. 80 FR 45732.
NEMA agreed with the proposed term
‘‘ballasted adapter.’’ (NEMA, No. 9 at p.
3) DOE received no other comments
regarding the definition for ‘‘ballast
adapter.’’ In this final rule, DOE adopts
the proposed definition for the term
‘‘ballasted adapter.’’
DOE also received comments related
to the inclusion of screw-base ballasted
adapters for non-integrated CFLs.
NEMA, OSI, and Philips stated that
screw-base ballasted adapters for nonintegrated CFLs should not be part of
the CFL test procedure, but rather
addressed in the fluorescent lamp
ballast (FLB) rulemaking.11 (NEMA, No.
9 at p. 2; OSI, No. 5 at p. 2; Philips, No.
6 at p. 3) DOE notes that it is not
proposing a test procedure for ballasted
11 Information regarding the Fluorescent Lamps
Ballast Rulemaking can be found at https://
www.regulations.gov/docket?D=EERE–2015–BT–
STD–0006.
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
59391
adapters in this rulemaking, only a test
procedure for compact fluorescent
lamps.
Philips disagreed with DOE’s
proposal that CFLs, packaged with or
designed exclusively for use with
ballasted adapters, must be tested as
non-integrated CFLs, without the
inclusion of the ballasted adapter.
Instead, Philips recommended that a
ballasted adapter sold with a lamp
should be tested as a system and the
system should be subject to the same
energy conservation standards as
integrated lamps. (Philips, No. 6 at p. 3)
DOE requires that non-integrated
CFLs be tested on reference ballasts as
specified in IES LM–66–14. This
ensures consistent test conditions for
measuring the performance
characteristics of non-integrated CFLs
that are externally ballasted. As noted in
this preamble, DOE defines ballasted
adapter as a component that is not
permanently attached to the CFL, and
therefore is similar to the external
ballasts used with non-integrated CFLs.
DOE reviewed CFLs that are compatible
with ballasted adapters and determined
that there was no technical reason they
could not be tested on a reference
ballast. Further, although the CFL may
be packaged with a certain ballasted
adapter, a consumer could choose to
replace it with a different ballasted
adapter or a manufacturer could pair the
same lamp with different ballasted
adapters. Thus, use of a reference ballast
allows for a consistent and comparable
assessment of the lamp’s performance.
Therefore, DOE continues to require that
CFLs packaged with or designed
exclusively for use with ballasted
adapters be tested as non-integrated
CFLs.
i. Multi-Level CFLs and Dimmable CFLs
Footnote 2 to the energy conservation
standards for MBCFLs codified at 10
CFR 430.32(u) includes the statement
that for multi-level or dimmable
systems, measurements shall be at the
highest setting. In the July 2015 NOPR,
DOE proposed to remove the footnote in
order to consolidate testing
requirements in the test procedure and
add language to the test procedure
addressing dimmable CFLs in the
general instruction section of appendix
W. The lumen output level and input
power can be adjusted for some CFLs
(i.e., dimmable), and thus not clarifying
the input power for testing these lamps
can introduce testing variation.
Therefore, to ensure consistent results,
DOE proposed that a dimmer not be
used in the circuit and that all CFLs be
tested at the labeled wattage, which
DOE defines as the highest wattage
E:\FR\FM\29AUR4.SGM
29AUR4
59392
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
marked on the lamp and/or lamp
packaging (see section III.A.3.f for
further details on the labeled wattage).
80 FR 45732–4573.
NEMA and OSI agreed that testing
should be conducted with no dimmer in
the circuit, but the CA IOUs proposed
testing dimmable CFLs at dimmed states
in addition to full power. (NEMA, No.
9 at p. 4; OSI, No. 5 at p. 3; CA IOUs,
No. 7 at p. 4) However, neither the
current energy conservation standards
nor those proposed in the March 2016
NOPR require measurements of
performance of CFLs at dimmed levels.
Therefore, DOE is not establishing test
procedures for CFLs to be tested at such
levels.
Both NEMA and OSI commented that
CFL testing should be conducted at
labeled voltage (which is an
independent variable), rather than at
labeled wattage (which is a dependent
variable). (NEMA, No. 9 at pp. 3–4; OSI,
No. 5 at p. 3) DOE agrees that wattage
is dependent on voltage and
understands that, during testing, the
electrical characteristics of the incoming
power to the lamp would be adjusted to
achieve a given wattage. Because voltage
and wattage are related quantities, DOE
notes that specifying either the voltage
or wattage will achieve the same result
when testing a given lamp. DOE’s
specification that the lamp be tested at
the labeled wattage is intended to
indicate that CFLs specified for a range
of wattages should be measured at the
highest wattage marked on the lamp.
This is consistent with the existing test
specifications for CFL testing and DOE’s
proposed definition of ‘‘labeled
wattage,’’ as discussed in section
III.A.3.f.
In this final rule, DOE removes the
text regarding multi-level or dimmable
systems from § 430.32(u) and, instead,
specifies in appendix W that dimmable
CFLs must be tested at their highest
labeled wattage. DOE believes
specifying that a dimmer cannot be used
in the circuit is an unnecessary addition
as DOE also specifies that dimmable
CFLs must be tested at their highest
labeled wattage. DOE therefore removes
this direction in the final rule.
3. Clarifications to Definitions
mstockstill on DSK3G9T082PROD with RULES4
a. Average Rated Life
In the July 2015 NOPR, DOE proposed
to remove the term ‘‘average rated life’’
and adopt the terms ‘‘lifetime of a
compact fluorescent lamp’’ and ‘‘time to
failure.’’ The existing definition of
‘‘average rated life’’ makes only general
reference to the sample size for time to
failure testing. DOE believes the use of
the word ‘‘average’’ in the term ‘‘average
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
rated life’’ may be confusing, and
although defined in appendix W, the
term is not otherwise used in appendix
W or in specifications of existing
MBCFL energy conservation standards.
Further, the term ‘‘rated life’’ is used as
a descriptor in appendix W, but is not
defined. Therefore, DOE proposed to
remove the term ‘‘average rated life’’
from appendix W and to add the
definition ‘‘lifetime of a compact
fluorescent lamp’’ at 10 CFR 430.2. 80
FR 45733. See section III.B.3 for more
detail.
In the July 2015 NOPR, DOE also
proposed to define ‘‘time to failure’’ in
appendix W to support the new
definition of ‘‘lifetime of a compact
fluorescent lamp’’ specified in 10 CFR
430.2. ‘‘Time to failure’’ in the context
of CFLs is the time elapsed between first
use and the point at which the lamp
fully extinguishes and no longer creates
light. 80 FR 45733.This definition aligns
with the definition of lamp failure in
section 8.2 of ANSI/IES RP–16–14.12
The EEAs were supportive of DOE’s
proposed changes related to lifetime,
but recommended that the definition of
‘‘time to failure’’ be the point at which
the lumen output falls below 70 percent
of initial lumen output. The EEAs stated
that 70 percent is a common threshold
within the lighting industry and
addresses a situation where the CFL
starts, but does not provide sufficient
light. (EEAs, No. 8 at p. 1)
DOE is only aware of 70 percent
initial lumen output to characterize
lifetime of light-emitting diode (LED)
lamps. This determination is based on
the understanding that the LED lamp
has reached the end of its useful life
when it achieves a lumen maintenance
of 70 percent. In the June 3, 2014
supplemental notice of proposed
rulemaking (SNOPR), DOE concluded
that there is no industry consensus for
how to characterize lifetime of LED
lamps in terms of performance metrics
other than lumen maintenance.
However, for other lighting
technologies, such as CFLs, industry
standards define lamp lifetime as the
time at which 50 percent of tested
samples stop producing light. 79 FR
32020, 32028. Therefore, in this final
rule, DOE defines ‘‘time to failure’’ as
the time elapsed between first use and
the point at which the CFL ceases to
produce measureable lumen output.
As noted in section III.A.1, DOE
references IES LM–65–14 for lifetime
testing of CFLs. Section 3.0 of IES LM–
65–14 specifies the terms ‘‘lamp
failure,’’ ‘‘lamp life,’’ and ‘‘rated lamp
12 Nomenclature and Definitions for Illuminating
Engineering (approved 2010).
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
life.’’ However, DOE is specifically
defining the terms, ‘‘time to failure’’ and
‘‘lifetime of a compact fluorescent
lamp’’ (see section III.B.3) to support its
lifetime testing of CFLs and align with
terminology used in other DOE lamp
test procedures. Although the
definitions in section 3.0 of IES LM–65–
14 are often analogous to DOE’s adopted
definitions for time to failure and
lifetime of a compact fluorescent lamp,
to avoid confusion regarding
terminology when executing the lifetime
test procedure for CFLs, DOE proposed
that section 3.0 of IES LM–65–14 should
be disregarded and replaced with the
DOE definitions used for lifetime testing
of CFLs. DOE did not receive any
comments regarding this proposal and
adopts it in this final rule.
b. Initial Performance Values
DOE proposed in the July 2015 NOPR
to (1) delete the term ‘‘initial
performance values;’’ (2) add a
definition for the term ‘‘initial lamp
efficacy;’’ (3) add a definition for the
term ‘‘measured initial input power;’’
(4) delete the term ‘‘rated luminous flux
or rated lumen output;’’ and (5) add a
definition for the term ‘‘measured initial
lumen output.’’ 80 FR 45733–45734.
The new terms clarify the measurement
of CFL initial performance values, and
eliminate the need for the terms ‘‘initial
performance values’’ and ‘‘rated
luminous flux or rated lumen output.’’
DOE did not receive any comments
related to deletion or addition of these
terms. Therefore, in this final rule, DOE
removes the terms ‘‘initial performance
values’’ and ‘‘rated luminous flux or
rated lumen output,’’ and adopts
definitions for ‘‘initial lamp efficacy,’’
‘‘measured initial input power,’’ and
‘‘measured initial lumen output.’’
c. Lumen Maintenance
In the July 2015NOPR, DOE proposed
to amend the definition of ‘‘lumen
maintenance’’ to clarify that calculated
lumen maintenance values are based on
measured lumen output as the existing
definition of ‘‘lumen maintenance’’ does
not clearly distinguish between rated
and measured values. The DOE
proposed to adopt the term ‘‘lumen
maintenance’’ in appendix W as the
lumen output measured at a given time
in the life of the lamp and expressed as
a percentage of the measured initial
lumen output. 80 FR 45734.
NEMA agreed with this clarification.
(NEMA, No. 9 at p. 5) DOE did not
receive any other comments on the term
‘‘lumen maintenance.’’ In this final rule,
DOE adopts the term ‘‘lumen
maintenance’’ and definition as
proposed in the July 2015 NOPR.
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
d. Rated Voltage
In appendix W, the term ‘‘rated
voltage’’ is defined as meaning the
voltage marked on the lamp. As
previously noted, in this final rule, DOE
requires measurement at the highest
rated input voltage for lamps rated at
multiple input voltages not including
120 V (see section III.A.2.c). In order to
support this test condition, in this final
rule, DOE adds clarifying text to the
definition of ‘‘rated voltage.’’
Specifically, in this final rule, DOE
replaces the term ‘‘rated voltage’’ with
‘‘rated input voltage,’’ defined as the
voltage(s) marked on the lamp as the
intended operating voltage, or if not
marked on the lamp, 120 V.
e. Rated Supply Frequency
In the July 2015 NOPR, DOE proposed
to remove from appendix W the term
‘‘rated supply frequency’’ because
appendix W does not use this term. 80
FR 45734.
NEMA agreed with removing this
term. (NEMA, No. 9 at p. 4) DOE did not
receive any other comments on
removing ‘‘rated supply frequency.’’ In
this final rule, DOE removes the term
‘‘rated supply frequency’’ from
appendix W.
mstockstill on DSK3G9T082PROD with RULES4
f. Rated Wattage
In the July 2015 NOPR, DOE proposed
to change the term ‘‘rated wattage’’ to
‘‘labeled wattage’’ and amend the
definition to clarify its applicability to
multi-level (i.e., multi-power) and
dimmable CFLs. 80 FR 45734.
Currently, in appendix W ‘‘rated
wattage’’ is defined as the wattage
marked on the lamp. The term is
intended to denote the wattage marked
on the lamp that should be used to
determine the applicable minimum
efficacy requirement for existing MBCFL
energy conservation standards as
specified in 10 CFR 430.32(u). However,
in ANSI standards, the rated wattage is
a targeted rather than actual value and
can sometimes differ from the value
displayed on the lamp packaging.
NEMA and OSI recommended DOE
not remove the term ‘‘rated wattage,’’
which they stated is widely used and
understood by the lighting industry, and
instead suggested adding the term
‘‘ANSI rated wattage’’ to differentiate
the ANSI-based wattages. (NEMA, No. 9
at p. 5; OSI, No. 5 at p. 4)
Although DOE understands that
‘‘rated wattage’’ is a commonly used
term in the lighting industry, DOE also
notes that its meaning may differ
depending on the context in which it is
used (i.e., referring to wattages
referenced in ANSI standards as
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
opposed to the wattage listed on the
CFL). Using the term ‘‘labeled wattage’’
will avoid any potential confusion when
applying DOE’s test procedures and
align with the definition of the term,
which specifies it as the wattage marked
on the lamp. Therefore, in this final
rule, DOE removes ‘‘rated wattage’’ and
defines ‘‘labeled wattage’’ as the highest
wattage marked on the lamp and/or
lamp packaging.
g. Self-Ballasted Compact Fluorescent
Lamp
The term ‘‘self-ballasted compact
fluorescent lamp,’’ as defined in
appendix W, means a CFL unit that
incorporates, permanently enclosed, all
elements that are necessary for the
starting and stable operation of the
lamp, and does not include any
replaceable or interchangeable parts.
The terms self-ballasted CFL, integrally
ballasted CFL, and integrated CFL are
used interchangeably in industry to
identify a CFL that contains all
components necessary for the starting
and stable operation of the lamp, does
not include any replaceable or
interchangeable parts, and is connected
directly to a branch circuit through an
ANSI base and corresponding ANSI
standard lamp-holder (socket). Because
DOE proposed to include test
procedures for additional categories of
CFLs, including integrated and nonintegrated CFLs, in the July 2015 NOPR,
DOE also proposed to define the
mutually exclusive terms ‘‘integrated
CFL’’ and ‘‘non-integrated CFL’’ to
clearly differentiate the applicability of
the relevant CFL test procedures and
energy conservation standards.
Specifically, DOE proposed to remove
the definition of ‘‘self-ballasted compact
fluorescent lamp’’ and add a new
definition for the term ‘‘integrated
compact fluorescent lamp’’ as an
integrally ballasted CFL that contains all
components necessary for the starting
and stable operation of the lamp, does
not include any replaceable or
interchangeable parts, and is connected
directly to a branch circuit through an
ANSI base and corresponding ANSI
standard lamp-holder (socket). DOE also
proposed to add a definition of ‘‘nonintegrated compact fluorescent lamp’’ as
‘‘a compact fluorescent lamp that is not
integrated.’’ 80 FR 45734.
OSI and NEMA stated that the
proposed definition for ‘‘nonintegrated’’ was unnecessarily broad
and encompassed all CFLs that are not
integrated CFLs. OSI and NEMA instead
suggested DOE incorporate the
following ANSI C78.901–2014
definition for non-integrated CFLs: a
CFL that has an ANSI pin base, does not
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
59393
incorporate a ballast, and appears in
ANSI C78.901–2014. (OSI, No. 5 at p. 5;
NEMA, No. 9 at p. 5) Additionally,
during the public meeting held to
discuss the July 2015 NOPR, OSI asked
why the term ‘‘integrated’’ was chosen
as opposed to ‘‘self-ballasted.’’ OSI also
inquired about the use of the term ‘‘pin
based’’ in the context of ‘‘nonintegrated.’’ (OSI, Public Meeting
Transcript, No. 4 at pp. 53–54) Philips
responded that UL 1993 13 uses the term
‘‘self-ballasted lamp’’ and acknowledged
that the IES struggled with the terms
when developing IES LM–65–14 and
IES LM–66–14, but ultimately both
documents use the terms integrated and
non-integrated when appropriate.
(Philips, Public Meeting Transcript, No.
4 at pp. 53–55)
The term ‘‘integrated’’ can be used
across lamp technologies to describe
lamps that contain all the necessary
components for operation, and thereby
provides consistency across DOE test
procedures for lamps. The term
supports the March 2016 NOPR and the
amended standards for CFLKs, both of
which apply to lamps that use ballasts
as well as drivers. Further, because this
test procedure applies to all CFLs, it is
DOE’s intent to set forth terminology
that includes all CFL types. Based on its
review of products, DOE determined
that a CFL is either ‘‘integrated’’ or
‘‘non-integrated’’ and intentionally
defined the terms to be mutually
exclusive (i.e., a CFL can be either
integrated or non-integrated, but not
both) and inclusive of all CFLs.
Therefore, DOE defines ‘‘non-integrated
compact fluorescent lamp’’ to include
any CFL that does not meet the
definition ‘‘integrated compact
fluorescent lamp’’ and does not limit
this definition by base type or inclusion
in industry standard. Hence, in this
final rule, DOE removes the definition
of ‘‘self-ballasted compact fluorescent
lamp’’ and adds new definitions for
‘‘integrated compact fluorescent lamp’’
and ‘‘non-integrated compact
fluorescent lamp.’’
4. Test Procedures for Existing and New
Metrics
a. Test Procedures for Initial Lamp
Efficacy, Lumen Maintenance, CCT,
CRI, and Power Factor
In the July 2015 NOPR, DOE proposed
to continue to include test procedures
for measuring initial lamp efficacy and
lumen maintenance and add test
procedures for measuring CCT, CRI, and
power factor in appendix W. DOE
13 UL. UL1993, ‘‘Self-Ballasted Lamps and Lamp
Adapters,’’ https://ulstandards.ul.com/standard/
?id=1993_4
E:\FR\FM\29AUR4.SGM
29AUR4
59394
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
proposed that the test procedures for
initial lamp efficacy, lumen
maintenance at 1,000 hours, lumen
maintenance at 40 percent of lifetime,
CCT, and CRI would apply to both
integrated and non-integrated lamps,
although the test procedure for power
factor would only apply to integrated
lamps. 80 FR 45735. The following
sections discuss these metrics and the
related comments received.
Initial Lamp Efficacy and Lumen
Maintenance
Although appendix W currently
specifies a test procedure for initial
lamp efficacy and lumen maintenance,
it does not explicitly state how to
measure and calculate initial lamp
efficacy and lumen maintenance values.
In order to standardize the CFL test
procedure and the calculation of these
values, DOE proposed that initial lamp
efficacy be determined as the measured
initial lumen output divided by the
measured initial input power. DOE
further proposed to reference IES LM–
66–14 for test conditions and setup to
measure initial lamp efficacy, lumen
maintenance at 1,000 hours, and lumen
maintenance at 40 percent of lifetime.
80 FR 45735. DOE did not receive any
comments regarding its proposals for
initial lamp efficacy and therefore, in
this final rule, adopts them as described
in the July 2015 NOPR.
Similarly, in the July 2015 NOPR,
DOE proposed to calculate lumen
maintenance at 1,000 hours as measured
lumen output at 1,000 hours divided by
the measured initial lumen output and
to calculate lumen maintenance at 40
percent of lifetime as the measured
lumen output at 40 percent of lifetime
of a compact fluorescent lamp divided
by the measured initial lumen output.
80 FR 45735.
DOE evaluated its existing energy
conservation standards and ongoing
standards rulemakings for CFLs as well
as FTC Lighting Facts labeling and
determined that a lumen maintenance at
1,000 hours metric is not required for
non-integrated CFLs. Therefore, in this
final rule, DOE is only adopting a test
procedure for lumen maintenance at
1,000 hours for integrated CFLs.
GE and Philips commented during the
public meeting for the July 2015 NOPR
that logistical testing issues arise if the
definition of lifetime is changed to a
measured quantity. GE and Philips
postulated that they could not measure
lumen maintenance at 40 percent of
measured lifetime because the point at
which lifetime is determined would be
later than the 40 percent of the lifetime
measurement point. (GE, Public Meeting
Transcript, No, 4 at pp. 44–47; Philips,
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
Public Meeting Transcript, No. 4 at pp.
21–22) Both NEMA and OSI proposed
measuring lumen maintenance at 40
percent of a rated lifetime rather than
the lifetime measured as proposed by
DOE. (NEMA, No 9 at pp. 4–5; OSI, No
5 at p. 4)
DOE acknowledges the logistical
concerns about measuring lumen
maintenance at 40 percent of the
lifetime of a CFL. In this final rule, DOE
is adopting that lumen maintenance at
40 percent of lifetime can be an
estimated value for initial certification
of new basic models or existing basic
models when retesting is required until
lifetime testing is complete. As
described in section 10 CFR 429.35(b),
certification reports must be submitted
for CFLs and represented values of
lifetime, lumen maintenance at 40
percent of lifetime, life, and rapid cycle
stress test surviving units are estimated
values until testing is complete. Upon
completion of lifetime testing, the next
annual certification report must include
final values for these metrics based on
the actual represented value for lifetime.
In this way, the time required to test for
lifetime, lumen maintenance at 40
percent of lifetime, life, and rapid cycle
stress will not delay the distribution in
commerce of a lamp. (See section III.G
for further details on certification
reports.)
Although DOE is adopting test
methods for lumen maintenance at 40
percent of lifetime for both integrated
and non-integrated CFLs, DOE notes
that standards for lumen maintenance at
40 percent of lifetime are only
applicable for integrated CFLs,
specifically MBCFLs. Lumen
maintenance at 40 percent of lifetime for
non-integrated CFLs is only required to
the extent that manufacturers wish to
make representations regarding the
lumen maintenance of their products or
participate in the voluntary ENERGY
STAR program.
Correlated Color Temperature (CCT)
In the July 2015 NOPR, DOE proposed
to establish a test procedure for
measuring CCT in appendix W. The
term ‘‘correlated color temperature’’ is
defined in 10 CFR 430.2 as the absolute
temperature of a blackbody whose
chromaticity most nearly resembles that
of the light source. DOE proposed
adding the abbreviation ‘‘CCT’’ to this
definition as explained in section
III.B.2. DOE further proposed that CCT
be measured and calculated in
accordance with IES LM–66–14, which
references Commission Internationale
de l’Eclariage (CIE) 15:2004 (3rd
edition), ‘‘Colorimetry.’’ 80 FR 45735.
CIE 15:2004 was previously
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
incorporated by reference in a test
procedure final rule published on July
6, 2009 for general service fluorescent
lamps, incandescent reflector lamps
(IRLs), and general service incandescent
lamps (GSIL) for appendix R (hereafter
‘‘2009 GSFL, IRL, and GSIL Test
Procedure’’). 74 FR 31829, 31834.
Both the CA IOUs and the EEAs
supported the proposed methodology to
measure CCT. (CA IOUs, No. 7. at pp.
3–4; EEAs, No. 8 at p. 4) Likewise,
NEMA had no issues with the proposed
test procedure, but noted that the
proposed methodology would add
measurements to the existing
requirements. (NEMA, No. 9 at p. 6) OSI
added that the additional measurements
would have no regulatory benefit. (OSI,
No. 5 at p. 5) Although DOE agrees with
commenters that DOE has not set
standards or requirements regarding the
CCT of CFLs, as noted previously, this
test procedure supports the FTC
Lighting Facts labeling requirements for
lighting products, the ENERGY STAR
Lamps Specification V2.0 and the
ENERGY STAR Luminaires
Specification V2.0, all of which require
the CCT metric. Therefore, in this final
rule, DOE adopts the test procedure for
CCT and incorporates CIE 15:2004 by
reference for appendix W as proposed in
the July 2015 NOPR.
Color Rendering Index (CRI)
In the July 2015 NOPR, DOE proposed
establishing a test procedure for
measuring CRI in appendix W. DOE
proposed that CRI must be measured
and calculated in accordance with IES
LM–66–14, which references CIE 13.3–
1995, ‘‘Method of Measuring and
Specifying Colour Rendering Properties
of Light Sources.’’ DOE also proposed to
incorporate CIE 13.3–1995 by reference
for appendix W. 80 FR 45735. CIE 13.3–
1995 was previously incorporated by
reference for appendix R in the 2009
GSFL, IRL, and GSIL Test Procedure.
The CA IOUs and EEAs supported the
proposed test procedure for CRI. (CA
IOUs, No. 7 at pp. 3–4; EEAs, No. 8 at
p. 4) NEMA and OSI expressed the view
that a CRI test method would have no
regulatory benefit and should not be
included in the test method but agreed
the proposed methodology was
appropriate for measuring CRI. (NEMA,
No. 9 at p. 6; OSI, No. 5 at p. 5) Philips
commented that CRI should be excluded
from the test procedure, as the metric
would not yield substantial energy
savings. (Philips, No. 6 at p. 3)
The EEAs proposed testing color
under the new IES metric outlined in
IES TM–30–2015, IES Method for
Evaluating Light Source Color
Rendition. (EEAs, No. 8 at p. 4) IES TM–
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
30–2015 is a new methodology for
evaluating different color properties
than CRI.14 CRI is determined by
comparing a specific set of eight color
samples and calculating the average
term known as Ra. In contrast, IES TM–
30–2015 provides calculations and
directions for quantifying fidelity (Rf,
which is the closeness to a reference)
and gamut (Rg, which is the increase or
decrease in chroma).
DOE must specify test procedures in
order to determine whether the products
comply with any relevant standards
promulgated under EPCA. (42 U.S.C.
6295(s)) In the March 2016 NOPR, DOE
proposed that MBCFLs have a CRI of at
least 80. 81 FR 14554. Additionally,
ENERGY STAR Lamps Specification
V2.0 and Luminaire Specification V2.0
include a CRI requirement. Therefore, in
this final rule, DOE establishes a test
procedure for CRI and incorporates CIE
13.3–1995 by reference for appendix W.
As there are no existing standards for
IES TM–30–2015 color metrics for CFLs,
nor were any proposed in the March
2016 NOPR, DOE is not adopting test
procedures to evaluate color metrics
specified in IES TM–30–2015 in this
final rule.
In this final rule, DOE is adopting test
methods for determining CRI for both
integrated and non-integrated CFLs.
While DOE is only adopting
certification requirements for integrated
CFLs when complying with general
service lamps standards, if adopted,
DOE’s test procedure for CRI is
applicable to all CFLs and must be used
when making representations. (As
proposed in the March 2016 NOPR, 81
FR 14554) More specifically, if a
manufacturer of a non-integrated CFL
decides to make representations of CRI
in its product literature, manufacturer
catalogues, labeling, or for voluntary
energy-efficiency programs, the
manufacturer must use the DOE test
procedure, including sampling plan.
mstockstill on DSK3G9T082PROD with RULES4
Power Factor
In the July 2015 NOPR, DOE proposed
a test procedure for measuring power
factor for integrated CFLs based on
electrical measurements conducted in
accordance with section 5.0 of IES LM–
66–14. DOE also proposed to define
power factor in appendix W as the
measured root square mean (RMS) input
power (watts) divided by the product of
the measured RMS input voltage (volts)
and the measured RMS input current
(amps). 80 FR 45735. DOE did not
14 IES
Method for Evaluating Light Source Color
Rendition. https://www.ies.org/store/product/iesmethod-for-evaluating-light-source-color-rendition3368.cfm.
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
receive comments on the proposed
definition. In this final rule, DOE has
modified the definition slightly to align
with the definition in ENERGY STAR.
Therefore, DOE adopts the following
definition of power factor: power factor
means the measured input power
(watts) divided by the product of the
measured RMS input voltage (volts) and
the measured RMS input current
(amps).
The CA IOUs and EEAs commented
that they were supportive of the
requirement of testing power factor as
well as the proposed approach. (CA
IOUs, No. 7 at pp. 4; EEAs, No. 8 at pp.
3–4) GE, Philips, NEMA, and OSI
commented that power factor should be
excluded from the test procedure, with
Philips stating that the metric would not
yield substantial energy savings, and
NEMA and OSI stating that it would
have no regulatory benefit. (GE, Public
Meeting Transcript, No. 4 at pp. 140–
142; OSI, No. 5 at p. 5; Philips, No. 6
at p. 3)
In the March 2016 NOPR, DOE
proposed setting a minimum power
factor standard for MBCFLs. 81 FR
14528, 14554–14555 (March 17, 2016).
DOE notes that ENERGY STAR Lamps
Specification V2.0 also includes a
power factor requirement. As power
factor is required to demonstrate
compliance with the proposed GSL
energy conservation standards and to
support the ENERGY STAR
requirements, in this final rule, DOE is
establishing a test procedure for power
factor.
GE, NEMA, OSI, and Philips
commented that power factor is not
relevant to non-integrated CFLs because
it is a metric specific to the ballast. (GE,
Public Meeting Transcript, No. 4 at pp.
140–142; NEMA, No. 9 at p. 6; OSI, No.
5 at p. 5; Philips, No. 6 at p. 3) In
response, DOE clarifies that the power
factor test procedure is only applicable
to integrated CFLs.
DOE also received a comment from
the CA IOUs recommending that DOE
consider requiring the measurement and
reporting of total harmonic distortion of
current (abbreviated as THD in the
comment). (CA IOUs, No. 5 at p. 4) In
the March 2016 NOPR, DOE stated that
THD is directly related to power factor
and a power factor requirement will
effectively establish a standard for THD.
81 FR 14555–14556. Therefore, DOE is
not adopting a test procedure for total
harmonic distortion of current in this
final rule.
b. Test Procedures for Time to Failure
In the July 2015 NOPR, DOE proposed
test procedures for measuring time to
failure in appendix W for integrated and
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
59395
non-integrated CFLs. 80 FR 45735. DOE
determined that test conditions, setup,
and measurement of time to failure
should be as specified in IES LM–65–14.
DOE also proposed that use of simulated
fixtures during time to failure testing of
CFLs not be allowed. This proposed
provision was to prevent potential
variation in testing of CFLs and to
ensure that all CFLs are tested in a
consistent manner. 80 FR 45732. NEMA
agreed with DOE’s proposal to disallow
the use of simulated fixtures during
time to failure testing. (NEMA, No. 9 at
p. 3)
OSI requested that DOE not include
lifetime testing for pin base CFLs in the
test procedure, noting that initial lamp
efficacy is sufficient for reporting
metrics of these lamp types. (OSI, No. 5
at p. 2) NEMA agreed with OSI that DOE
should not include lifetime testing for
pin base CFLs. NEMA also stated that
lifetime testing would depend on the
ballast operating the non-integrated
CFL. (NEMA, No. 9 at pp. 2, 6)
DOE agrees with NEMA that the
specific ballast used affects the lifetime
of non-integrated CFLs; however, the
characteristics of the lamp also affect
this metric. Further, manufacturer
catalogs specify the lifetime of nonintegrated CFL products and lifetime is
also required by ENERGY STAR
Luminaires Specification V2.0.
Therefore, DOE finds that lifetime is an
important characteristic of the
performance of the non-integrated CFL.
Additionally, by using reference ballasts
when testing non-integrated CFLs, DOE
is able to assess the performance of the
non-integrated CFL in a comparable and
standardized way across all nonintegrated lamps. In this final rule, DOE
adopts the proposed test procedures for
time to failure for integrated and nonintegrated CFLs to be used to determine
lifetime.
c. Test Procedure for Rapid Cycle Stress
Test
In the July 2015 NOPR, DOE proposed
test procedures for conducting rapid
cycle stress testing for integrated and
non-integrated CFLs. DOE proposed that
test conditions, setup, and rapid cycle
stress testing be as specified in IES LM–
65–14, but retained the existing
operating cycle for rapid cycle stress
testing (i.e., CFLs must be cycled
continuously with each cycle consisting
of one 5-minute on period followed by
one 5-minute off period). 80 FR 45735.
DOE did not propose any modifications
to the rapid cycle stress test itself, but
did propose modifications to rounding
requirements (see section III.A.7),
removal of test procedure language from
the energy conservation standard
E:\FR\FM\29AUR4.SGM
29AUR4
59396
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
requirements (see section III.F.4), and
modifications to sample size (see
section III.H.2) for this test.
DOE received comments that rapid
cycle stress testing should not be
applied to non-integrated CFLs. GE
commented that rapid cycle stress
testing should not apply to nonintegrated CFLs because it is dependent
on the ballast paired with the lamp. (GE,
Public Meeting Transcript, No. 4 at pp.
140–142) OSI added that rapid cycle
stress testing was designed to stress the
ballast and not applicable to nonintegrated CFLs. (OSI, No. 5 at pp. 2, 5)
NEMA supported the test procedure for
rapid cycle stress testing with the
clarification that the test procedure
should not apply to non-integrated
CFLs. (NEMA, No. 9 at p. 6) Philips also
stated that non-integrated CFLs be
excluded from rapid cycle stress test
and questioned the energy savings
aspects related to measuring rapid cycle
stress test. (Philips, No. 6 at p. 3)
In light of the comments received
from interested parties, DOE evaluated
its existing energy conservation
standards and ongoing standards
rulemakings as well as FTC Lighting
Facts labeling and ENERGY STAR
specifications and determined that rapid
cycle stress testing of non-integrated
CFLs is not required by any of these
regulatory and non-regulatory programs.
Therefore, DOE is not adopting a test
procedure for rapid cycle stress testing
of non-integrated CFLs. DOE notes,
however, that the existing standards for
MBCFLs, the proposed standards in the
March 2016 NOPR, and the ENERGY
STAR Lamps Specification V2.0 all
contain a requirement for rapid cycle
stress testing for MBCFLs. Therefore,
DOE retains the test procedure for rapid
cycle stress testing for integrated CFLs.
d. Test Procedure for Start Time
In the July 2015 NOPR, DOE proposed
a test procedure for measuring start time
for integrated CFLs. In support of the
proposed start time test method, DOE
defined the terms ‘‘start time,’’ ‘‘start
plateau,’’ and ‘‘percent variability.’’
DOE also proposed that the lamp be
seasoned, stored at a certain
temperature, and tested according to a
certain operating procedure following
the seasoning. 80 FR 45735–45736.
DOE received comments regarding the
applicability of the start time metric.
NEMA, OSI, and Philips stated that start
time is not related to energy efficiency
and should not be part of the test
procedure. (NEMA, No. 9 at pp. 6,8;
OSI, No. 5 at p. 5; Philips, No. 6 at p.
3) NEMA and OSI stated that DOE
should abandon the effort to create a test
procedure for start time. (NEMA, No. 9
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
at p. 6; OSI, No. 5 at p. 5) GE, NEMA,
Philips, and OSI stated that start time is
not applicable to non-integrated CFLs.
(GE, Public Meeting Transcript, No. 4 at
pp. 140–142; NEMA, No. 9 at p. 8; OSI,
No. 5 at pp. 2,7; Philips, No. 6 at p. 3)
In the March 2016 NOPR, DOE
proposed a requirement for start time for
MBCFLs that the lamp must remain
continuously illuminated within one
second of application of electrical
power. 81 FR 14528, 14555 (March 17,
2016). ENERGY STAR Lamps
Specification V2.0 includes a
requirement for start time. DOE notes
that because the ongoing GSL
rulemaking considered a start time
metric for only integrated CFLs, the July
2015 NOPR proposed measuring start
time for only integrated CFLs. 80 FR
45736. In this final rule, DOE continues
to specify that only integrated lamps
must be tested for start time.
DOE received several comments
regarding the proposed definitions and
test procedures for start time. The CA
IOUs agreed with the proposed methods
for start time outlined in the July 2015
NOPR. (CA IOUs, No. 7 at pp. 3–4) The
EEAs stated that they supported DOE’s
test procedures for start plateau, percent
variability, and start time as long as they
are fully consistent with the ENERGY
STAR test procedure for start time.
(EEAs, No. 8 at p. 4)
If DOE were to require measuring and
reporting start time, OSI suggested using
the ENERGY STAR procedure, which it
stated is well understood. (OSI, No. 5 at
p. 5) NEMA noted that although the
ENERGY STAR test procedure for start
time is well understood, it should not be
required for lamps that are not ENERGY
STAR certified. (NEMA, No. 9 at p. 6)
Both Philips and Westinghouse
commented that DOE’s proposed start
time procedure seemed overly
complicated, and requested that DOE
harmonize with or simply adopt the
ENERGY STAR test procedure. (Philips,
Public Meeting Transcript, No. 4 at p.
65; Westinghouse, Public Meeting
Transcript, No. 4 at pp. 66–67)
When developing the start time test
procedure, DOE reviewed the August
2013 ‘‘ENERGY STAR Program
Requirements Product Specification for
Lamps Version 1.0: Start Time Test
Method.’’ 15 ENERGY STAR released
‘‘ENERGY STAR Program Requirements
for Lamps and Luminaires Start Time
15 ENERGY STAR® Program Requirements
Product Specification for Lamps Version 1.0: Start
Time Test Method. August 2013.
www.energystar.gov/sites/default/files/specs//
ENERGY%20STAR%20Lamps%20V1%200%20
Final%20Test%20Methods%20and
%20Recommended%20Practices.pdf.
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
Test Method’’ 16 in September 2015
(hereafter ‘‘ENERGY STAR Start Time
Test Method’’). For this final rule, DOE
reviewed the latest version of the
ENERGY STAR Start Time Test
Methods and determined that the only
differences between the two methods
are the applicable products and
referenced documents.17
DOE determined that its proposed
start time test method continues to align
with the ENERGY STAR Start Time Test
Method, while providing greater
specificity in order to ensure
consistency and reproducibility in
measurements. (DOE also notes section
11.4 of ENERGY STAR Lamps
Specification V2.0 references the DOE
test procedure for compact fluorescent
lamps (once final) for measuring start
time of fluorescent lamps.) The
following sections describe how the
proposed definitions and test
procedures for start time harmonize
with the ENERGY STAR Start Time Test
Methods as well as amendments to
these proposals that provide further
simplification and clarity.
Definitions
In the July 2015 NOPR, DOE proposed
definitions for the terms ‘‘start plateau,’’
‘‘percent variability,’’ and ‘‘start time.’’
80 FR 45754. DOE proposed to define
the term ‘‘start plateau’’ as the first 100
millisecond period of operation during
which the percent variability does not
exceed 5 percent and the average
measured lumen output is at least 10
percent of the measured initial lumen
output. 80 FR 45736. This definition
aligns with ENERGY STAR’s definition
of ‘‘initial plateau’’ as ‘‘the point at
which the average increase in the light
output over time levels out (reduces in
slope). This can be determined
mathematically or visually based on the
lamp output trace.’’
Both definitions are intended to
describe a time interval in which the
light output is relatively steady.
ENERGY STAR does not specify the
16 ENERGY STAR® Program Requirements for
Lamps and Luminaires Start Time Test Method.
September 2015. https://www.energystar.gov/sites/
default/files/ENERGY%20STAR%20Start%20
Time%20Test%20Method_1.pdf.
17 The August 2013 ENERGY STAR Start Time
Test Method applied to integrated CFLs and solidstate lighting (SSL) lamps. In contrast, the
September 2015 ENERGY STAR Start Time Test
Method applies to all integrated and externally
ballasted CFLs, and SSL lamps, light engines, and
luminaires. Both versions referenced IES LM–66,
‘‘IES Approved Method for Electrical and
Photometric Measurements of Single-Based
Compact Fluorescent Lamps.’’ However, the August
2013 ENERGY STAR Start Time Test Method
referenced the 2011 version of IES LM–66 and the
latest version references the 2014 version of IES
LM–66.
E:\FR\FM\29AUR4.SGM
29AUR4
mstockstill on DSK3G9T082PROD with RULES4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
method by which such a time interval
should be quantitatively and objectively
determined. In order to ensure
consistent and reproducible
measurements, DOE’s proposed
definition specifies the time period over
which lumen output should be steady as
100 milliseconds and described the
criteria for light output that must be met
during this time period. DOE selected
100 milliseconds to evenly capture
either 5 or 6 full cycles of the sampled
waveform (for 50 or 60 Hz input voltage,
respectively). 80 FR 45736. Section 5.4
of IES LM–28–12 states that by choosing
the integrating time to be a multiple of
the period of the line frequency (16.67
milliseconds for 60 Hz), for example,
100 milliseconds (6 line cycles for 60 Hz
and 5 line cycles for 50 Hz), the effect
of flicker for either line frequency can
be removed. Id.
Regarding the criteria for determining
stability of light output during the first
100 milliseconds, DOE proposed that
the percent variability not exceed 5
percent and that the average measured
lumen output over the time interval
should be at least 10 percent of the
measured initial lumen output. The first
criterion is intended to quantify when
the light output can be deemed ‘‘stable.’’
DOE determined that the criterion that
the percent variability cannot exceed 5
percent is sufficient to capture a 100
millisecond interval in which light
output is steady and subsequently
determine an appropriate start time. The
second criterion is intended to capture
the time at which light output is first
detected for a continuous period and
ensure that light is actually being
created from the lamp (e.g., a stable
output of zero if the lamp fails to turn
on is not acceptable).
In re-evaluating the latter criterion,
DOE found that requiring a specific
threshold of light output is unnecessary
for the start time metric. According to
the test procedures established in this
final rule, measured initial lumen
output must be determined using the
integrating sphere method. Therefore,
for comparison purposes, the average
lumen output in a 100 millisecond span
that occurs during the initial operation
of the lamp must also be determined
using the integrating sphere method.
However, DOE has determined that, due
to the precision of the measurement, the
integrating sphere may require
reconfiguration and additional setup to
measure the lumen output in the initial
milliseconds of lamp operation. DOE
has determined that including the latter
criterion does not merit requiring a
potentially complex test setup.
Removing this criterion would allow for
start time testing to be conducted using
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
either an integrating sphere or nonintegrating sphere method such as a
photodetector. Therefore, in this final
rule, DOE defines ‘‘start plateau’’ to
mean ‘‘the first 100 millisecond period
of operation during which the percent
variability does not exceed 5 percent.’’
To provide further clarity to the
definition of ‘‘start plateau,’’ DOE
proposed to define the term ‘‘percent
variability’’ as the range (calculated by
subtracting the minimum from the
maximum) expressed ‘‘as a percentage
of the mean for the contiguous set of
separate lumen output measurements
spanning the specified time period,
where each lumen output measurement
is the average value of the sampled
waveform over an interval
corresponding to one full cycle of
sinusoidal input voltage.’’ 80 FR 45736.
Because DOE is no longer requiring
lumen measurements to determine start
plateau, percent variability also does not
have to be based on lumen output.
Therefore, DOE is replacing the
specification of lumen output
measurements with light output values.
Additionally, DOE is providing a clearer
description of calculating a time-average
of measured light output values. In
summary, in this final rule, DOE is
specifying ‘‘percent variability’’ to be
‘‘the result of dividing the difference
between the maximum and minimum
values by the average value for a
contiguous set of separate time-averaged
light output values spanning the
specified time period. For a waveform of
measured light output values, the timeaveraged light output is computed over
one full cycle of sinusoidal input
voltage, as a moving average where the
measurement interval is incremented by
one sample for each successive
measurement value.’’
In the July 2015 NOPR, DOE proposed
to define the term ‘‘start time’’ as the
time, measured in milliseconds,
between the application of power to the
CFL and the point when the measured
full-cycle lumen output (the average
value of the sampled waveform over an
interval corresponding to one full cycle
of sinusoidal input voltage) reaches 98
percent of the average measured lumen
output of the start plateau. 80 FR 45754.
ENERGY STAR defines start time as
‘‘the time between the application of
power to the device and the point where
light output reaches 98% of the lamp’s
initial plateau.’’
GE commented that from the
consumer’s perspective the simplest
definition for start time is the time
between energizing the circuit and the
first light output. GE added that the
specification of 97 or 96 percent of the
plateau was not distinguishable. (GE,
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
59397
Public Meeting Transcript, No. 4 at pp.
68–70)
ENERGY STAR Lamps Specification
V2.0 describes start time as the time for
a lamp to remain continuously
illuminated after applying electrical
power. DOE agrees that the start time
metric is intended to capture the time of
detection of first continuous light
output. Hence, the 98 percent threshold
is not necessary for representative
measurements of start time. Therefore,
in this final rule, DOE removes this
element from the definition of start
time. Additionally, DOE provides a
clearer description of the point at which
start time should be determined. In
summary, DOE defines ‘‘start time’’ to
mean ‘‘the time, measured in
milliseconds, between the application of
power to the CFL and the beginning of
the start plateau.’’
Lamp Storage/Operating Cycle Post
Seasoning
In the July 2015 NOPR, DOE proposed
that, after seasoning, units must be
stored at 25 ± 5 °C ambient temperature
for a minimum of 16 hours prior to
testing, after which the ambient
temperature must be 25 ± 1 °C for a
minimum of 2 hours prior to testing.
DOE also determined that any units that
have been off for more than 24 hours
must be operated for 3 hours and then
be turned off for 16 to 24 hours prior to
testing. 80 FR 45736. ENERGY STAR
Start Time Test Method prescribes
similar specifications with the time
period characterized as 20 ± 4 hours.
During the public meeting for the July
2015 NOPR, OSI stated that 16 hours
after the lamp is seasoned before testing
was atypical for its test laboratories and
based on this schedule the time that
testing could begin would be outside the
normal work schedule. OSI added that
the rationale for the 16 hours after
seasoning was not well understood.
(OSI, Public Meeting Transcript, No. 4
at pp. 73–74) During the public meeting,
DOE noted that the proposed storage
and operating cycle post seasoning
requirements were consistent with
ENERGY STAR. (DOE, Public Meeting
Transcript, No. 4 at p. 75) OSI
acknowledged the ENERGY STAR
specification of the 16 hour period, but,
stated that ENERGY STAR testing does
not represent all of the testing that OSI
conducts because not all of their
products are submitted to ENERGY
STAR. OSI elaborated they did not have
a technical justification for or against
the time period, but that it could be a
potential cost burden. (OSI, Public
Meeting Transcript, No. 4 at p. 74)
Westinghouse Lighting (Westinghouse)
added that the scheduling and
E:\FR\FM\29AUR4.SGM
29AUR4
59398
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
subsequent cost issues described by OSI
are even more pronounced for them
because they use an independent testing
laboratory where not all Westinghouse
products may be tested at the same time.
(Westinghouse, Public Meeting
Transcript, No. 4 at pp. 74–76)
The proposed operating cycle ensures
that the lamp has been seasoned and
recently operated, but not so recently
that elements in the recent operation of
the lamp could directly affect start time.
DOE does clarify in this final rule that
the 3 hours that the unit must be
operated after being off for more than 24
hours is a minimum of 3 hours. This
specification is mainly for clarification
purposes; DOE does not find that
operating the lamp for a longer period
would affect the start time testing. Any
units that have been off for more than
24 hours must be operated for a
minimum of 3.0 hours and then be
turned off for 16 to 24 hours prior to
testing. DOE notes that the range of 16
to 24 hours in the off state provides an
8 hour range during which start time
testing may begin, which should allow
it to be conducted during normal
working hours. Therefore, DOE adopts
the proposed operating cycle and
ambient temperature requirements
described in this final rule.
Testing Methodology
For test setup and conditions for
measuring start time, DOE proposed in
the July 2015 NOPR to reference IES
LM–66–14 and IES LM–54–12. 80 FR
45735–45736. DOE proposed to adopt
the measurement circuit requirements
as specified in section 5.2 of IES LM–
66–14 and that lumen output
measurements be taken as specified in
section 6.3.1 of IES LM–66–14. DOE
also proposed to adopt seasoning
specifications as provided in sections 4,
5, 6.1, 6.2.2.1of IES LM–54–12. 80 FR
45736. Further, DOE proposed that a
multichannel oscilloscope with data
storage capability be connected to
record the input voltage to the CFL and
its lumen output. DOE specified that the
oscilloscope must be set to trigger at 10
V lamp input voltage, to have the
vertical scale set at a vertical resolution
that is 1 percent of measured initial
lumen output or finer, and to be set to
sample the lumen output waveform at a
minimum rate of 2 kHz. Id.
The proposed test setup and
conditions generally align with those
specified by ENERGY STAR. Section
4(B) of the ENERGY STAR Start Time
Test Method references IES LM–66–14
and IES LM–54–12. Section 5.A(2) of
the ENERGY STAR Start Time Test
Method requires a multichannel
oscilloscope with data storage capability
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
and section 7.1(F) also requires to set
the trigger level at 10 V. DOE’s proposal
for a minimum 2 kHz sampling rate is
also consistent with the ENERGY STAR
requirement for flicker testing,18 and
DOE understands that this requirement
would also provide sufficient horizontal
resolution for start time testing. DOE did
not receive any comments specific to
the proposed test setup and conditions
for start time. In this final rule, DOE
adopts the test setup and conditions as
proposed in the July 2015 NOPR.
In the July 2015 NOPR, DOE also
proposed that upon the trigger for start
time testing, the sampled lumen output
waveform must be recorded until the
measured lumen output has reached the
start plateau. 80 FR 45736. In addition,
DOE proposed in the NOPR that the
trace of full-cycle lumen output must be
calculated as a moving average, whereby
values are determined at least once
every millisecond and each value
represents the full-cycle interval in
which it is centered. Id. The August
2013 ENERGY STAR Start Time Test
Method provides an example of a light
output trace for compact fluorescent
lamps. Aligning with ENERGY STAR,
DOE’s proposed steps provide specifics
on recording such a light output trace
and how time-averaged values from the
light output trace should be calculated.
Specifically, in this final rule, DOE
states that, upon the trigger for start time
testing, the sampled light output must
be recorded until the start plateau (as
defined in this section) has been
determined. Additionally, in this final
rule, to determine the ‘‘percent
variability’’ of light output in
accordance with the start plateau
definition, DOE requires calculation of a
time-averaged light output value at least
once every millisecond where each
value represents the full-cycle interval
in which it is centered. DOE further
specifies that, for a waveform of
measured light output values, the timeaveraged light output is computed over
one full cycle of sinusoidal input
voltage, as a moving average where the
measurement interval is incremented by
one sample for each successive
measurement value.
Lamp Orientation
In the July 2015 NOPR, DOE proposed
that all units be tested in the base up
position, but that if the position is
18 ENERGY STAR® Program Requirements
Product Specification for Lamps Version 1.0—Light
Source Flicker Recommended Practice. August
2013. Washington, DC. www.energystar.gov/sites/
default/files/specs//ENERGY%20STAR%20
Lamps%20V1%200%20Final%20
Test%20Methods%20and%20Recommended
%20Practices.pdf.
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
restricted by the manufacturer, units
would be tested in the manufacturer
specified position. 80 FR 45755. Section
5(H) of the September 2015 ENERGY
STAR Start Time Test Method states the
samples be tested in the orientation(s) as
specified by the ENERGY STAR
specification or manufacturer specified
position if different. It should be noted
that ENERGY STAR Lamps
Specification V2.0 does not state the
testing orientation in section 11.4, Start
Time. However, for purposes of
consistency, DOE proposed that all
units for start time be tested in the base
up position, but that if the position is
restricted by the manufacturer, units
must be tested in the manufacturer
specified position. DOE did not receive
any comments specific to lamp
orientation for start time; and in this
final rule adopts the sample unit
orientation specification.
Hybrid Lamps
In the July 2015 NOPR, DOE proposed
measuring only integrated CFLs for start
time, which would include hybrid
lamps. 80 FR 45755. DOE also proposed
that hybrid CFLs must be tested with all
supplemental light sources turned off, if
possible. 80 FR 45737.
The EEAs cautioned that having the
supplemental light source off during
testing could yield inaccurate test
results for start time testing. (EEAs, No.
8 at p. 3) NEMA requested the start time
test procedure not apply to hybrid CFLs
or to not require that the supplementary
light source not be operating. (NEMA,
No. 9 at p .7) GE also requested that
hybrid CFLs be exempt from start time
testing because it could lead to
inaccurate results because one of the
primary functions of hybrid CFLs is to
allow for quicker start time through the
supplemental light source. (GE, Public
Meeting Transcript, No. 4 at pp. 59–60)
DOE has determined that hybrid
lamps should not be exempt from the
start time test procedure. The March
2016 NOPR proposes a start time metric
for medium base CFLs. If a hybrid CFL
meets the definition of medium base
CFL, then the applicable standard
applies to the hybrid CFL. Similarly,
ENERGY STAR Lamps Specification
V2.0 does not specify different start time
requirements for hybrid CFLs. DOE
determined that requiring the
supplemental light source be off, if
possible, is the most consistent manner
in which the various combinations of
primary and supplementary light
sources in hybrid CFLs can be tested.
Therefore, in this final rule, DOE retains
the requirement that hybrid CFLs be
tested for start time with the
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
supplemental light source turned off, if
possible.
mstockstill on DSK3G9T082PROD with RULES4
5. Test Procedures for New CFL
Categories
a. Test Procedures for Integrated CFLs
In the July 2015 NOPR, DOE proposed
test procedures for integrated CFLs
without exclusion of any base type.
NEMA, OSI, and Philips requested that
DOE exclude E12 19 and GU24-based
integrated lamps from the test
procedure. All three entities stated that
lamps with these bases represented a
small portion of the market. (NEMA, No.
9 at pp. 2,8; OSI, No. 5 at p. 7; Philips,
No. 6 at p. 3) NEMA and OSI further
stated that if a particular lamp has the
same technical specifications across
lamps with medium, E12, and GU24
base types, then DOE should only
require testing on MBCFLs. NEMA and
OSI argued that base type does not have
any effect on lamp performance.
(NEMA, No. 9 at pp. 2, 6; OSI, No. 5 at
pp. 2, 5)
Regarding the applicability of the test
procedure to integrated lamps with
certain base types, DOE notes that the
March 2016 NOPR proposed standards
for GU24 base integrated lamps. 81 FR
14551. Further, CFLK standards with
required compliance in 2019 are
applicable to CFLKs packaged with
CFLs of all base types. As both of these
standards will be supported by this test
procedure, DOE is obligated to establish
test procedures for CFLs of all base
types for the applicable metrics
addressed in those rules. Therefore, in
this final rule, DOE does not exclude
E12 and GU24-base lamps from the test
procedures for integrated CFLs.
Regarding lamps that have the same
technical specifications, manufacturers
must submit represented values of
required metrics for each basic model
before distribution in commerce. 10 CFR
429.12(a). Represented values of
measures of energy efficiency or energy
consumption must be the same for all
individual models represented by a
given basic model. 10 CFR 429.11(a).
However, DOE provides manufacturers
with the flexibility to group individual
models into basic models for the
purposes of certification to DOE,
provided that all representations
regarding the energy efficiency or
energy consumption of CFLs within that
basic model are identical and based on
the most consumptive unit. See 76 FR
19 DOE defines a candelabra base incandescent
lamp in 10 CFR 430.2 as a lamp that uses a
candelabra screw base as described in ANSI C81.61,
Specifications for Electric Bases, common
designations E11 and E12 . The base is not specific
to the light source, therefore a candelabra base lamp
can be either an E11 or E12 base.
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
12422, 12423 (March 7, 2011).
Therefore, it may be possible to group
lamps that have the same technical
specifications but different base types
into the same basic model. However, all
representations within a basic model
must have essentially identical
electrical, physical, and functional
characteristics that affect energy
efficiency (see definition of basic model
per 10 CFR 430.2). Accordingly, CFLs
that are in separate product classes and
thereby subject to separate standards
(e.g., integrated and non-integrated
CFLs) cannot be grouped in the same
basic model. Also, DOE does not believe
it is appropriate to group models of
lamps that have different testing
methods as defined in Appendix W into
the same basic model as they will not
have essentially identical electrical
characteristics.
b. Test Procedures for Non-Integrated
CFLs
In the July 2015 NOPR, DOE proposed
test procedures for non-integrated CFLs.
Specifically, DOE proposed adopting
section 5.2 of IES LM–66–14 for
electrical and photometric testing of
non-integrated CFLs, which specifies
procedures for determining initial lamp
efficacy, lumen maintenance at 40
percent of lifetime, CRI, and CCT. 80 FR
45737. To ensure repeatable and
consistent measurements, DOE
proposed that non-integrated CFLs must
be tested using the appropriate reference
ballasts as provided in section 5.2 of IES
LM–66–14, which specifies using
reference ballasts specifications listed in
ANSI C78.901–2014, ‘‘American
National Standard for Electric Lamps—
Single-Based Fluorescent Lamps—
Dimensional and Electrical
Characteristics,’’ (hereafter ‘‘ANSI
C78.901–2014’’). Id.
NEMA and OSI agreed with
referencing ANSI C78.901–2014 to
identify reference ballasts for nonintegrated CFLs, but also stated that
industry only has experience using
reference ballasts for photometry.
(NEMA, No. 9 at pp. 6–7; OSI, No. 5 at
pp. 5–6) Reference ballast
characteristics provide the necessary
functionality to operate a non-integrated
CFL and a standardized and consistent
method of testing non-integrated CFLs.
DOE does not find any technical reason
why reference ballasts cannot be used
for non-photometric measurements.
Therefore, in this final rule, DOE
requires using reference ballast
specifications in ANSI C78.901–2014 to
test non-integrated CFLs for all
measurements.
In the July 2015 NOPR, DOE noted
that certain non-integrated CFL designs
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
59399
do not have reference ballast
specifications listed in ANSI C78.901–
2014. For these lamp designs, DOE
proposed reference ballast
specifications. In cases where there are
no reference ballast specifications for a
lower wattage CFL, DOE proposed the
reference ballast specifications of the
corresponding full wattage version, if
they existed. For all other cases, DOE
developed reference ballast
specifications by matching the shape,
diameter, and base of the CFL without
reference ballast specifications to the
most similar CFL with specifications
that also had the closest wattage. 80 FR
45737. For any non-integrated CFLs that
do not have a reference ballast listed in
ANSI C78.901–2014 and for which DOE
has not specified reference ballast
characteristics in appendix W, DOE also
specified two principles that must be
employed to determine the appropriate
reference ballast specifications. For such
a lamp, DOE specified that,
manufacturers must use the
specifications in ANSI C78.901 2014 for
the higher wattage lamp for which it is
a replacement; otherwise, use the
specifications in ANSI C78.901 2014 for
a lamp with the most similar shape,
diameter, and base specifications, and
next closest wattage. OSI agreed with
DOE’s proposal to address lamps for
which reference ballast characteristics
are not specified. (OSI, No. 5 at pp. 5–
6) In this final rule, DOE is also
specifying the appropriate frequency
along with the reference ballast values
of current, impedance, and voltage.
To specify a consistent set of testing
procedures for non-integrated CFLs, in
the July 2015 NOPR, DOE proposed
several clarifications and specifications
regarding the circuits on which the
lamps must be tested. 80 FR 45737. DOE
proposed to test non-integrated CFLs
rated for operation on a choice of low
frequency or high frequency circuits at
low frequency only. Id.
GE, NEMA, and OSI stated they were
unaware of any dual-frequency
reference ballast specifications. (GE,
Public Meeting Transcript, No. 4 at pp.
56–57; NEMA, No. 9 at pp. 6–7; OSI,
No. 5 at p. 6) NEMA and OSI suggested
that DOE require testing at the
manufacturer-specified frequency.
(NEMA, No. 9 at pp. 6–7; OSI, No. 5 at
p. 6) GE stated that, because these
products are operating at high frequency
in application, testing them at low
frequency reference conditions when
high frequency reference conditions are
available would misrepresent their
efficacy. (GE, Public Meeting Transcript,
No. 4 at pp. 56–57)
As noted previously, in order to
establish a set of consistent
E:\FR\FM\29AUR4.SGM
29AUR4
mstockstill on DSK3G9T082PROD with RULES4
59400
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
specifications and conditions and to
follow industry standards for testing
non-integrated CFLs, in this final rule,
DOE is requiring the use of ANSI
C78.901–2014 for reference ballast
values per IES LM–66–14. There are
certain lamps for which ANSI C78.901–
2014 provides details for both low and
high frequency operation. For example,
a 36 W T5 single-based fluorescent lamp
on datasheet 78901–ANSI–4019–1
provides reference ballast characteristics
for low frequency operation and also
information on high frequency ballast
design. Manufacturers must use the
values designated as ‘‘reference ballast
characteristics’’ when testing lamps. If
more than one set of values is
designated as ‘‘reference ballast
characteristics,’’ then manufacturers
must use the values designated for low
frequency operation. DOE reviewed the
reference ballast specifications for nonintegrated CFLs and found that the
majority are specified for low frequency
operation. Therefore, in this final rule,
in order to maintain consistency and
comparability across testing, DOE
continues to require operating on low
frequency where reference ballast
characteristics for both low and high
frequency operation are provided.
DOE also proposed in the July 2015
NOPR that non-integrated CFLs rated for
multiple circuits including rapid start
(i.e., rapid start and either preheat start
or instant start) be tested on rapid start
circuits when rapid circuits are an
option to ensure consistent
measurements. 80 FR 45737.
NEMA and OSI disagreed with the
requirement to use rapid start circuits.
Both NEMA and OSI stated that rapid
start circuits have not typically been
used in testing of non-integrated CFLs
and expressed concerns regarding how
the testing would relate to certification,
compliance, and enforcement. (NEMA,
No. 9 at pp. 6–7; OSI, No. 5 at p. 6) GE
indicated that a rapid start circuit would
include cathode heat while use of a
programmed start circuit would exclude
cathode heat. GE explained that testing
without cathode heat is the most
representative of the current
applications. GE further added that
including cathode heat would decrease
the apparent lamp efficacy, and not be
reflective of how the product is used.
(GE, Public Meeting Transcript, No. 4 at
pp. 56–58)
In reviewing the reference circuits
specified for lamps, DOE has decided to
modify its proposed specifications for
reference circuits on which nonintegrated CFLs must be tested in this
final rule. In the July 2015 NOPR, DOE
proposed to specify that a rapid start
reference circuit be used when a non-
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
integrated CFL is rated for multiple
circuits in order to establish a consistent
set of test specifications. In preparation
for this final rule, DOE reviewed the
reference ballast specifications for nonintegrated CFLs and found that most
lamps are rated for preheat circuits.
DOE found that if a lamp was rated for
multiple circuits, further specifications
still may be needed to indicate the
circuit to use for testing. If a lamp is
rated for operation on both a preheat
and high frequency circuit, the reference
ballast characteristics provided describe
low frequency operation and therefore
the lamp must be tested on the low
frequency preheat circuit. If a lamp is
rated for operation on both a preheat
and rapid start circuit, DOE is
specifying in this final rule that the
lamp be tested on the preheat circuit in
order to maintain consistency and
comparability across testing.
In this final rule, DOE is not adopting
test procedures for lumen maintenance
at 1,000 hours or rapid cycle stress test
for non-integrated CFLs, as these
metrics are not being evaluated for
inclusion in, nor are they currently
required by, any DOE energy
conservation standards, FTC Lighting
Facts labeling requirements, or ENERGY
STAR program requirements. Therefore,
in this final rule, DOE adopts test
procedures for initial lamp efficacy,
lumen maintenance at 40 percent of
estimated lifetime, lifetime, CRI, and
CCT for non-integrated CFLs.
c. Test Procedures for Hybrid CFLs
In the July 2015 NOPR, DOE proposed
establishing a test procedure to measure
the applicable metrics for hybrid CFLs
in appendix W. That is, DOE proposed
that the same test procedures for
integrated CFLs would be applicable to
hybrid CFLs, with a few minor
clarifications regarding the
configuration and operation of hybrid
CFLs during testing. DOE considers
hybrid CFLs to be CFLs with an
additional light source of a different
technology that is not the primary
source of light. DOE proposed to define
the term ‘‘hybrid compact fluorescent
lamp’’ in appendix W as a CFL that
incorporates one or more supplemental
light sources of different technology. 80
FR 45737–45738. NEMA and OSI
proposed the definition of ‘‘a compact
fluorescent lamp that incorporates one
or more supplemental light sources of
different technology, such as halogen or
LED, which are energized and operated
independently and may or may not
operate simultaneously.’’ (NEMA, No. 9
at p. 7; OSI, No. 5 at p. 6) OSI stated
that there are different types of hybrid
lamps where either the main or the
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
supplemental light source operates or
both the main and supplemental light
sources operate. OSI requested that both
the definition and related test
procedures address these different
possible configurations of hybrid lamps.
(OSI, Public Meeting Transcript, No. 4
at p. 59)
DOE reviewed the definition
suggested by NEMA and OSI and notes
that there is significant overlap between
DOE’s proposed definition and the
alternate definition. Both definitions
contain a reference to a CFL as well as
supplemental technologies. DOE finds
that the example ‘‘such as halogen or
LED’’ is not necessary, as the DOE’s
proposed definition specifies that the
supplemental light sources would be of
‘‘different technology.’’ Further
providing such examples may be
misinterpreted by some users to limit
the types of applicable supplementary
sources. NEMA and OSI’s other
suggestion of ‘‘which are energized and
operated independently and may or may
not operate simultaneously’’ identifies
potential operating configurations of the
supplementary light sources. By not
specifying any configurations for the
operation of the supplementary light
source, DOE’s proposed definition does
not exclude the configurations
mentioned by NEMA and OSI or any
others. DOE’s proposed definition is
also consistent with industry definitions
of other hybrid technologies such as a
hybrid LED luminaire as defined in IES
RP–16–10, which also does not identify
the operating parameters of the different
light sources. For these reasons, DOE
retains the proposed definition from the
July 2015 NOPR of the term ‘‘hybrid
compact fluorescent lamp’’ as meaning
a CFL that incorporates one or more
supplemental light sources of different
technology. DOE believes that this is
consistent with the definition suggested
by interested parties, but is more general
and leaves less room for
misinterpretation of specific examples
or operating parameters.
In the July 2015 NOPR, DOE proposed
a test procedure for hybrid CFLs where
the supplemental light source is off (if
possible) and the lamp stabilized. Id. In
response to the proposal, the EEAs
encouraged DOE to incorporate
language defining a not-to-exceed time
to stabilization prior to taking
measurements to prevent extended
periods of operation of secondary
sources. (EEAs, No. 8 at p. 3)
DOE’s test procedure for hybrid CFLs
requires that the supplementary source
be turned off before initiating testing. In
the cases where supplementary source
cannot be turned off, the lamp must
adhere to stabilization criteria as
E:\FR\FM\29AUR4.SGM
29AUR4
mstockstill on DSK3G9T082PROD with RULES4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
specified in section 6.2.1 of IES LM–66–
14. This stabilization criteria involves a
series of time-related measurements to
determine stable light output and
electrical usage. Although the
supplementary source may have some
effect on the stabilization time, it is
more important that the lamp achieve
stabilization per an established criterion
in order to obtain accurate
measurements. Further, the
determination of a stable light output
will likely be predominantly influenced
by the CFL, which is the primary source
of light. Therefore, in this final rule,
DOE is not adding a not-to-exceed time
for stabilization for taking
measurements of hybrid CFLs.
NEMA was supportive of DOE’s
proposed test procedure for hybrid
lamps. However, NEMA requested that
start time not apply to hybrid CFLs.
NEMA added that if start time testing
was required for hybrid CFLs, the
supplementary light source should be
turned on. NEMA agreed with DOE’s
proposal to test hybrid CFLs as nonhybrid CFLs (that is with only the CFL
source active) for any measurements
besides start time. (NEMA, No. 9 at p.
7) The EEAs disagreed with DOE’s
proposal that hybrid lamps be tested for
efficacy with the supplemental light
source turned off. The EEAs argued that
having the supplemental light source off
during testing could yield inaccurate
test results for both start time testing
and energy efficiency. (EEAs, No. 8 at p.
3) DOE addressed start time testing in
section III.A.4.d. DOE disagrees with the
EEAs that testing hybrid CFLs with the
supplemental light source off (when
possible) would yield inaccurate results
for energy efficiency. Testing the hybrid
CFL with only the CFL light source
operating (when possible) would yield
comparable efficacy measurements
across basic models of CFLs. Further,
based on a review of available hybrid
CFLs, DOE has determined that many
supplemental light sources turn off
automatically or will likely be turned off
during normal operation (such as when
the supplemental light source is
intended to be a night light). Thus,
DOE’s test procedure is representative of
lamp operation under normal
conditions.
In this final rule, DOE adopts a
requirement that hybrid CFLs must be
tested with all supplemental light
sources turned off, if possible, and that
the lamp be stabilized in the operating
mode that corresponds to its primary
light source, according to test
procedures for CFLs in appendix W.
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
6. Test Procedure for Standby Mode
Energy Consumption
In the July 2015 NOPR, DOE proposed
a test procedure to measure standby
mode energy consumption for integrated
CFLs, where applicable, in appendix W.
80 FR 45738. EPCA directs DOE to
amend its test procedures for all covered
products to incorporate a measure of
standby and off mode energy
consumption in accordance with IEC
62301 and IEC 62087, if technically
feasible. (42 U.S.C. 6295(gg)(2))
DOE research indicated that some
integrated CFLs include controls, and
that these CFLs can operate in standby
mode but not off mode. DOE did not
find any non-integrated CFLs capable of
operation in standby mode or off mode,
and understands that any such circuitry
would likely be found in the ballast
rather than the lamp. Therefore, in the
July 2015 NOPR, DOE proposed that
standby mode power be measured only
for integrated CFLs that are capable of
standby mode operation. 80 FR 45738.
For integrated CFLs, DOE proposed
that standby mode power be measured
in accordance with IEC 62301. DOE also
proposed to approve IEC 62301, which
is already incorporated by reference in
10 CFR 430.3, for incorporation into
appendix W. DOE proposed that, when
measuring standby power for integrated
CFLs, the test conditions and setup
must be as prescribed in IEC 62301,
except for ambient temperature and
ambient airflow. Instead, DOE proposed
to prescribe the ambient temperature
and ambient airflow requirements in IES
LM–66–14 to minimize differences
between test procedures for active mode
and standby mode. DOE proposed to
season lamps in the same manner as test
procedures for the other applicable CFL
metrics, as described in section III.A.2.e,
and to measure standby mode power as
prescribed in section 5 of IEC 62301.
Finally, DOE proposed that standby
mode be initiated when the integrated
CFL is connected to the power supply
and lumen output is set to zero via
remote or other wireless/sensor control.
80 FR 45738.
NEMA and OSI commented that,
according to the definition proposed in
the July 2015 NOPR, CFLs operate in the
off mode when switched off. They also
stated that off mode consumes no power
nor produces any function. (NEMA, No.
9 at p. 7; OSI, No. 5 at p. 6)
DOE determined that it is not possible
for CFLs to meet the off mode criteria
because there is no condition in which
a CFL is connected to main power and
is not already in a mode accounted for
in either active or standby mode. That
is, DOE is not aware of any CFLs that,
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
59401
when provided with power, are not
operating in active mode (i.e.,
illuminated) or standby mode (i.e.,
facilitating the activation or deactivation
of active mode via remote switch,
internal sensor, or timer). In response to
the specific example raised by NEMA
and OSI, a CFL that is switched off is
not connected to a main power source
because the circuit is disrupted at the
switch and thus power is not being
provided to the CFL. Therefore, in this
final rule, DOE retains the position that
CFLs do not operate in off mode and has
not considered test procedures for such
modes of operation.
NEMA, Philips, and OSI also
requested that DOE explicitly exclude
CFLs that are not designed with standby
operation from standby mode power
measurements. (NEMA, No. 9 at p. 7;
OSI, No. 5 at p. 6; Philips, No. 6 at p.
4) DOE agrees with NEMA, OSI, and
Philips that only integrated CFLs
capable of operating in standby mode
should be tested for standby mode
energy consumption. In the July 2015
NOPR, DOE proposed regulatory
language for measuring standby power
in appendix W that stated standby mode
energy consumption should be
measured only for integrated CFLs that
are capable of standby mode operation.
80 FR 45755. For further clarity, in the
final rule DOE has moved this
instruction to the beginning of the
regulatory text for the standby mode test
procedure in appendix W.
DOE received comments from CA
IOUs to harmonize testing for standby
mode operation with the LED lamps test
procedure.20 (CA IOUs, No. 7 at pp. 4–
5) The CA IOUs wanted to ensure that
lamps capable of operation in network
mode were tested in network mode. (CA
IOUs, No. 7 at pp. 4–5) Specifically, CA
IOUs requested that DOE define
network mode and suggested that if a
product is designed to be connected to
a wireless network in order to fully
operate, then the test procedure should
specify that the lamp is to be connected
to the network before testing begins.
Connected lamps may require the use of
an external control system or hub to
serve as a communication point
between the lamp and end user, and the
CA IOUs asked DOE to specify a
maximum permissible distance the
control system can be from the lamp
during testing. (CA IOUs, No. 7 at pp.
4–5) The EEAs were supportive of the
20 Information regarding the Light-Emitting Diode
Lamps Test Procedure Rulemaking can be found on
regulations.gov, docket number EERE–2011–BT–
TP–0071 at www.regulations.gov/
#!docketDetail;D=EERE–2011-BT-TP–0071.
E:\FR\FM\29AUR4.SGM
29AUR4
mstockstill on DSK3G9T082PROD with RULES4
59402
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
CA IOUs comments. (EEAs, No. 8 at pp.
5–6)
DOE agrees that the test procedure
needs additional detail to specify that
lamps capable of operation in standby
mode must remain connected to the
external wireless network through the
entirety of the test for standby mode
energy consumption. If the lamp
becomes disconnected, the lamp may
exit standby mode or otherwise have its
power draw affected, which would yield
inaccurate test results. Therefore, in this
final rule DOE is adding detail to
section 4 of appendix W to specify that
integrated CFLs capable of connecting to
a communication network must be
connected to the network prior to
testing and must remain connected
throughout the duration of the test. DOE
did not specify a maximum distance the
integrated CFL can be from the control
system or hub during testing because
DOE believes the requirement for the
integrated CFL to remain connected
throughout the entire duration of the
test ensures that, if an integrated CFL is
moved to a distance such that it
disconnects from the communication
network, the test results would be
invalid.
CA IOUs also commented that
connected lamps may experience cycles
or power fluctuations when lamps are
communicating with the wireless
network, and requested the test
procedure provide instructions to
account for this in an average power
metric over a minimum 5-minute test
duration. (CA IOUs, No. 7 at pp. 4–5)
The EEAs were supportive of the CA
IOUs comments. (EEAs, No. 8 at pp. 5–
6)
DOE is requiring that standby mode
measurements be taken as specified in
section 5 of IEC 62301. DOE notes that
section 5 of IEC 62301 gives
manufacturers the flexibility to choose
the measurement method that best
applies to the nature of their products’
power supply. Further, each of the
methods available for use in IEC 62301
specifies that the product must have test
durations of at least 10 minutes, which
is an adequate test duration to ensure
wattage fluctuations have been
recorded. IEC 62301 also states that data
collection at equal intervals of 0.25
seconds or faster is recommended for
loads that are unsteady or where there
are any regular or irregular power
fluctuations. DOE finds that the
measurement instructions provided in
section 5.0 of the IEC 62301
appropriately account for any potential
power fluctuations, and is not
specifying additional instructions
regarding measurement of standby mode
power.
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
In addition, DOE is clarifying in this
final rule that standby mode testing
must be conducted prior to testing for
time to failure. DOE is also clarifying
that ambient conditions, power supply,
electrical settings, and instrumentation
must be the same as used for active
mode testing. These clarifications are
intended to ensure that test conditions
will be as consistent as possible.
7. Rounding Values
In the July 2015 NOPR, DOE proposed
amending certain rounding
requirements for existing metrics, as
DOE found the existing rounding
requirements for individual units in a
given test sample to be inconsistent
with the required standard level for
some metrics. For example, although
final values for lumen maintenance at
1,000 hours and lumen maintenance at
40 percent of lifetime must be rounded
to whole numbers, existing standards
for lumen maintenance at 1,000 hours
(90.0 percent) and lumen maintenance
at 40 percent of lifetime (80.0 percent)
are specified to the tenth of a percent in
10 CFR 430.32(u). In the July 2015
NOPR, DOE also proposed to move the
rounding requirements from appendix
W to 10 CFR 429.35. 80 FR 45738.
DOE noted in the July 2015 NOPR
that the rounding requirements for
lumen maintenance measurements are
to the nearest tenth for integrated CFLs,
and proposed the same requirement for
non-integrated CFLs. Id. Both NEMA
and OSI recommended that lumen
maintenance be rounded to the nearest
whole number. (NEMA, No. 9 at p. 8;
OSI, No. 5 at p. 7) NEMA further stated
that rounding lumen maintenance to the
nearest tenth of a percent is not
practical or meaningful. (NEMA, No. 9
at p. 8) DOE notes that the lumen
maintenance value of the standard is to
the tenth of a percent and was
established in the 2006 rule that
adopted standards for MBCFLs. 71 FR
71340, 71369 (Dec. 8, 2006). DOE
understands that at least 3 significant
figures are required in both the
numerator (maintained lumens) and
denominator (initial lumens) to yield 3
significant figures for lumen
maintenance values. DOE reviewed
product catalogs currently published by
OSI and several other CFL
manufacturers and determined that
lumen output values are often reported
to 3 or 4 significant figures. Therefore,
DOE has concluded that it is possible to
determine lumen maintenance to the
nearest tenth of a percent. To align with
existing standards, in this final rule,
DOE provides in 10 CFR 429.35 that
lumen maintenance at 1,000 hours and
lumen maintenance at 40 percent of
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
lifetime must be rounded to the nearest
tenth of a percent.
In the July 2015 NOPR, DOE proposed
that lifetime of a CFL be rounded to the
nearest hour and that these
requirements be located in 10 CFR
429.35. 80 FR 45738. Both NEMA and
OSI argued that lifetime should be
rounded to two significant digits.
(NEMA, No. 9 at p. 8; OSI, No. 5 at p.
7) NEMA further stated that expressing
lifetime to the nearest hour is
meaningless, as the uncertainty in an
individual time-to-failure measurement
is much larger than 1 hour. (NEMA, No.
9) However, rounding to the nearest
whole hour is consistent with the unit
of time used for lifetime metrics for
other lamp technologies, such as LED,21
and is a level of accuracy a laboratory
is capable of measuring with a standard
time-keeping device. In this final rule,
DOE adopts a rounding requirement to
the nearest whole hour for lifetime. DOE
notes that manufacturers can make
representations of lifetime to the nearest
two significant digits provided that the
value is lower than the actual measured
lifetime when rounded to the nearest
hour (i.e., manufacturers are reporting a
conservative value for lifetime).
DOE did not receive any comments on
the proposal to round initial lamp
efficacy values to the nearest tenth of a
lumen per watt, input power to the
nearest tenth of a watt, lumen output to
three significant digits, or rapid cycle
stress values to whole numbers.
Therefore, in this final rule, DOE adopts
these requirements.
Additionally, in the July 2015 NOPR,
DOE proposed rounding requirements
for new proposed metrics of CRI, CCT,
start time, standby mode power, and
power factor based on industry standard
reporting precision, as determined
based on a review of manufacturer
catalogs. DOE also proposed locating
those rounding requirements in 10 CFR
429.35. 80 FR 45738. DOE did not
receive any comments related to this
proposal. Therefore, in this final rule,
DOE adopts the rounding requirements
for these metrics as proposed in the July
2015 NOPR, specifically: CRI be
rounded to the nearest whole number;
start time be rounded to the nearest
whole number in milliseconds; CCT be
rounded to the nearest 100 K; standby
mode power rounded to the nearest
tenth of a watt; and power factor be
rounded to the nearest hundredths
place.
21 See LED final rule test procedure. 81 FR 43404
(July 1, 2016).
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
B. Amendments to Definitions at 10 CFR
430.2
1. Compact Fluorescent Lamp
In the July 2015 NOPR, DOE proposed
to add a definition of ‘‘compact
fluorescent lamp’’ in 10 CFR 430.2. 80
FR 45738–45739. DOE reviewed its
definitions for other lighting products
and considered the existing definition of
the term ‘‘fluorescent lamp’’ at 10 CFR
430.2 as a basis for its definition of
‘‘compact fluorescent lamp.’’ DOE also
consulted the current IES definition of
‘‘compact fluorescent lamp’’ contained
in IES RP–16–10 and the description of
compact fluorescent lamps in IES LM–
66–14, which includes elements of the
lamp characteristics and discusses
elements of light output generation.
During the public meeting for the July
2015 NOPR, OSI inquired why DOE did
not adopt the IES RP–16–10 definition
rather than developing a novel
definition for compact fluorescent lamp.
(OSI, Public Meeting Transcript, No. 4
at pp. 16–20) Lucidity Lights stated that
IES labors over the exact wording in
definitions and also encouraged DOE to
use the exact wording in IES RP–16–10.
(Lucidity Lights, Public Meeting
Transcript. No. 4 at p. 22) Both NEMA
and OSI also recommended that DOE
use definitions from or reference IES
RP–16–10. (NEMA, No. 9 at p. 5; OSI,
No. 5 at pp. 2–3) NEMA stated that the
proposed definition for CFL was
technically correct, but raised concern
that it expanded the scope of the
definition. (NEMA, No. 9 at p. 8)
DOE appreciates the work that
members of the IES did in developing
the definitions in IES RP–16–10. DOE
reviewed IES RP–16–10 and IES LM–
66–14 in developing this final rule. DOE
considered: (1) Use of the term
fluorescent lamp; (2) tube diameter; (3)
general features (i.e., amalgam, cold
chamber); (4) lamp geometry; and (5)
base specification and lamp
configuration in the definition. The
following paragraphs provide additional
details on each of these elements.
The definition of CFL in section
6.5.6.1.4 of IES RP–16–10 includes the
phrase ‘‘a fluorescent lamp with . . .’’
DOE cannot use this element in 10 CFR
430.2 to define a CFL because 10 CFR
430.2 already defines the term
fluorescent lamp, which establishes a
fluorescent lamp as a low pressure
mercury electric-discharge source in
which a fluorescent coating transforms
some of the ultraviolet energy generated
by the mercury discharge into light, and
is limited to six specific lamps, all of
which are longer than 22 inches and are
double ended. If DOE adopted a
definition of CFL that contained the
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
term ‘‘fluorescent lamp,’’ it would
include these large lamp lengths and
base configurations that are not CFLs.
The definition of CFL in IES RP–16–
10 also specifies that the diameter of the
lamp’s tube must be less than or equal
to that of a T5. However, DOE’s review
of ANSI standards and manufacturer’s
lamp marketing materials indicated that
there are CFLs with tube diameters
greater than T5. Specifically, ANSI
C78.901–2014 includes within their list
of data sheets a handful of ‘‘square’’
shaped CFLs that are listed with a
corresponding T6 tube diameter. DOE
also found manufacturer data sheets of
lamps greater than T5 in diameter that
were single-ended and folded or bent
fluorescent lamps and characterized as
CFLs. Therefore, DOE determined that
diameter could be a limiting
specification that may exclude lamps
that should be categorized as CFLs.
Therefore, in this final rule, DOE does
not include specification of the tube
diameter in the definition of ‘‘compact
fluorescent lamp.’’
The IES RP–16–10 definition also
states that the lamp designs generally
include amalgam and a cold chamber, or
a cold spot, to control the mercury
vapor pressure and light output. These
features are general and not distinctive
for all CFLs. Therefore, in this final rule,
DOE does not include this description
in the definition of ‘‘compact
fluorescent lamp.’’
The IES RP–16–10 definition of
‘‘compact fluorescent lamp’’ specifies
that tube construction must be glass and
describes the configuration of the glass
tube as folded, bent, or bridged to create
a long discharge path. The IES LM–66–
14 description of fluorescent lamps
notes that a fluorescent lamp can be
made compact in two ways. Fluorescent
lamps with electrodes (typically long,
tubular lamps) can be made compact by
folding the tube one or more times or
spiraling it in a helix in such a way that
both electrodes are configured to have
one connection, leading to single base
construction. IES LM–66 also notes that
induction-driven electrodeless
fluorescent lamps are compact because
the discharge current is required to form
a closed loop inside the structure.
Because fluorescent lamps with a
compact size do not necessarily include
a glass tube with a specific geometry,
DOE does not add such a description to
the definition of ‘‘compact fluorescent
lamp.’’
Both of the introductory sections of
IES LM–65–14 and LM–66–14 discuss
that there are two types of CFLs:
Integrated and non-integrated. Further,
the titles of both IES LM–65–14 and
LM–66–14 contain the phrase ‘‘single-
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
59403
based.’’ DOE agrees with these IES
documents in the importance of
clarifying that CFLs are integrated or
non-integrated and single-based.
Therefore, DOE retains those terms in
the definition of ‘‘compact fluorescent
lamp’’ adopted in this final rule. IES
LM–66–14 also specifically excludes Ushaped and circline fluorescent lamps
from its CFL definition. DOE agrees
with IES LM–66–14 that U-shaped and
circline lamps are not CFLs. Therefore,
to ensure such lamps are not
inadvertently misclassified, DOE also
retains these exclusions in the
definition of ‘‘compact fluorescent
lamp’’ adopted in this final rule.
In summary, DOE has incorporated
language from IES RP–16–10 and IES
LM–66–14 that helps clearly define
CFLs without erroneously excluding or
including lamps. In this final rule, DOE
defines a compact fluorescent lamp
(CFL) as an integrated or non-integrated
single-base, low-pressure mercury,
electric-discharge source in which a
fluorescing coating transforms some of
the ultraviolet energy generated by the
mercury discharge into light; the term
does not include circline or U-shaped
lamps.
2. Correlated Color Temperature
In the July 2015 NOPR, DOE proposed
modifying the definition of ‘‘correlated
color temperature’’ in 10 CFR 430.2 by
adding the abbreviation ‘‘CCT.’’ DOE
explained that a similar abbreviation
exists in 10 CFR 430.2 for the definition
of color rendering index or CRI. The
abbreviation ‘‘CCT’’ is widely used in
industry as well as by ENERGY STAR
and in 10 CFR part 430, subpart B,
appendix R. 80 FR 45739.
Both NEMA and OSI submitted
written comments in support of the
proposed change. (NEMA, No. 9 at p. 8;
OSI, No. 5 at p. 7) OSI also suggested
that DOE harmonize the definition with
IES RP–16–10. (OSI, Public Meeting
Transcript, No. 4 at pp. 16–19) Section
4.6.4.2 of IES RP–16–10 defines
‘‘correlated color temperature of a light
source’’ as the absolute temperature
whose chromaticity most nearly
resembles that of the light source. Other
than the added abbreviation of ‘‘or CCT’’
and the phrase ‘‘of a light source,’’
DOE’s definition (defined by EPCA) is
the same as IES RP–16–10. Therefore, in
this final rule, DOE adopts the
abbreviation ‘‘CCT’’ into the term
‘‘correlated color temperature’’ and
makes no other changes to the
definition.
E:\FR\FM\29AUR4.SGM
29AUR4
mstockstill on DSK3G9T082PROD with RULES4
59404
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
3. Lifetime of a Compact Fluorescent
Lamp
DOE proposed to define ‘‘lifetime of a
compact fluorescent lamp’’ in 10 CFR
430.2 as the time to failure of 50 percent
of the sample size (as defined and
calculated in 10 CFR 429.35(a)(1)) in
accordance with the test procedures
described in section 3.3 of appendix W.
80 FR 45733.
NEMA and Philips raised concerns
that replacing ‘‘average rated life’’ with
‘‘lifetime of a compact fluorescent
lamp’’ might result in unintended
consequences; specifically, lumen
maintenance of a lamp could not be
determined until the lamp’s lifetime is
known. (NEMA, No. 9 at pp. 4–5;
Philips, No. 6 at p. 4) DOE addresses
lumen maintenance measurements in
section III.A.4.a.
NEMA proposed replacing ‘‘average
rated life’’ with ‘‘rated life,’’ noting that
the latter term appears in the CFR and
is similar to the term ‘‘rated lamp life’’
defined in ‘‘Nomenclature and
Definitions for Illuminating
Engineering’’ from the IES (IES RP–16).
NEMA stated the determination of
lifetime should be independent of a
specific sample size and allow for the
use of more stable statistical estimators
of the population median value than
failure of 50 percent of the sample.
Therefore, NEMA recommended that
DOE define ‘‘rated life’’ as median time
to failure of the population of CFLs. For
further support, NEMA stated that EPCA
defines ‘‘life’’ and ‘‘lifetime’’ as the
length of operating time of a statistically
large group of lamps between first use
and failure of 50 percent of the group.
NEMA also cited the IES Lighting
Handbook which states in section 13.3
that for incandescent, fluorescent, and
HID lamps, rated lamp life is the total
operating time at which, under normal
operating conditions, 50% of any large
group of initially installed lamps is
expected to have failed. This is a
statistically determined estimate of the
median operational life. NEMA stated
that by adopting the definition in the
IES Lighting Handbook, DOE would
indicate that the lifetime is the median
value of a large group of lamps and is
statistically determined. NEMA also
noted that DOE should not restrict the
sample size to a multiple of two if
statistical estimation of the population
median value is accepted. (NEMA, No.
9 at pp. 4–5, 10)
OSI also proposed the term ‘‘rated
life’’ citing 10 CFR part 430 and IES RP–
16–10. OSI agreed with NEMA that
lifetime should be determined
independent of a specific sample size.
OSI recommended a definition similar
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
to the one in the IES Lighting
Handbook, defining rated life as the
total operating time at which, under
normal operating conditions, 50 percent
of any large group of initially installed
lamps is expected to have failed,
referencing the historic ENERGY STAR
and IES definition. (OSI, No. 5 at pp. 4–
5)
In general, NEMA and OSI stated
lifetime is poorly estimated by the
arithmetic mean of the time to failure of
the two middle sample units when
sorted in order. (NEMA, No. 9, p. 10;
OSI, No. 5 at p. 9) During the public
meeting for the July 2015 NOPR, both
GE and Westinghouse stated the middle
value of a sample was a poor indicator
of the median and instead
recommended using an entire
population. (GE, Public Meeting
Transcript, No. 4 at pp. 14–15, 25–26;
Westinghouse, Public Meeting
Transcript, No. 4 at pp. 15–16) GE
added that the intent of the statutory
language was to indicate a median value
for lifetime, that DOE has the
opportunity to clearly specify this and,
further, that this value should represent
50 percent failure of the population to
align with the industry standard for
rated lifetime of lamps. (GE, Public
Meeting Transcript, No. 4 at pp. 25–26)
DOE understands that the IES
Lighting Handbook and EPCA describe
‘‘rated lamp life’’ and ‘‘lifetime’’/‘‘life’’
to be based on a large group of lamps
rather than a specific number of lamps.
Further, the IES Lighting Handbook
states that ‘‘rated lamp life’’ is when 50
percent of any large group of lamps is
expected to have failed and that it is a
statistically determined estimate of the
median operational life. However, DOE
notes that it must prescribe test
procedures that provide consistent and
reproducible results, and allow for
comparison of represented values across
basic models. Therefore, rather than
allow any number of lamps to be used
to determine the represented value of
lifetime, DOE must specify a minimum
sample size.
Commenters did not suggest a specific
minimum sample size, and as proposed
in the July 2015 NOPR, DOE is adopting
a minimum sample size of 10 for testing
the initial lamp efficacy, lumen
maintenance at 1,000 hours, lumen
maintenance at 40 percent of lifetime,
lifetime, CCT, CRI, power factor, and
standby mode power. DOE is requiring
that the same sample of 10 units be used
for testing these metrics, and that a
minimum of three units from the same
sample of units be tested for start time.
(Due to the nature of the test, a unique
sample set is required for rapid cycle
stress testing.) Each of these metrics
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
contribute to the overall performance of
a CFL, and because they are
fundamentally related, directly and/or
indirectly impact each other. Therefore,
the same set of sample units and sample
size should result in more accurate
measurements of all metrics, including
lifetime. Manufacturers may, at their
discretion, use a larger sample size to
determine a representative value of
lifetime if they believe it is warranted.
However, the same sample set and size
must also be used for testing initial
lamp efficacy, lumen maintenance at
1,000 hours, lumen maintenance at 40
percent of lifetime, lifetime, CCT, CRI,
power factor, and standby mode power;
the total number of units in the sample
set must be a multiple of two; and a
minimum of three units from the sample
set must be used for start time. If the
same sample of units is not available for
the testing of additional metrics for an
existing model, the basic model must be
retested using the same sample set for
all metrics.
DOE notes that the statutory
definition of lifetime does not include
any mention of a statistical method that
can be used and DOE is hesitant to
allow for any statistical method to
determine lifetime. Commenters did not
provide explicit suggestions regarding
any applicable statistical methods in
their comments. In addition, neither the
IES Lighting Handbook nor any other
industry standard provides a specific
statistical method that should be used to
determine the lifetime of compact
fluorescent lamps. Further, DOE notes
that the median of a sample is a robust
statistical descriptor of the central
tendency of the sample (and thereby the
population) that deals well with outlier
values, which may be the case in
lifetime testing of CFLs. Although other
statistical tools can be used to describe
the variance about the median or
estimate adjusted median values if other
attributes about the population are
known (e.g., the distribution is a Pareto
distribution or a weighted median if the
precision of each data point is known
and is significantly variable), these more
advanced statistical tools are
unnecessary, as they would not provide
a better description of the expected
lifetime of the lamp, as defined by
EPCA, than the median value.
Therefore, DOE finalizes its proposal
in the July 2015 NOPR, that lifetime of
a CFL be calculated as the operating
time between first use and failure of 50
percent of the sample units; the sample
size must be at least 10 units; and the
represented value of lifetime must be
the median time to failure of the sample
(calculated as the arithmetic mean of the
time to failure of the two middle sample
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
units when the numbers are sorted in
value order). DOE believes that this
definition provides the appropriate
specificity to produce consistent and
repeatable results while aligning with
EPCA’s definition of ‘‘lifetime’’ and
‘‘life’’ as the ‘‘length of operating time
of a statistically large group of lamps
between first use and failure of 50
percent of the group.’’ In order to
provide a clear and consistent test
procedure, DOE specifies ‘‘group’’ as a
minimum sample size of 10 units for
CFLs, but reiterates that manufacturers
are not prevented from testing
significantly more than 10 CFLs
provided the total number tested is a
multiple of two.
C. Amendments to Materials
Incorporated by Reference at 10 CFR
430.3
In the July 2015 NOPR, DOE proposed
to incorporate by reference ANSI
C78.901–2014, IES LM–54–12, IES LM–
65–14, and IES LM–78–07 industry
standards and to extend the
incorporation by reference of CIE 13.3–
1995, CIE 15:2004, IES LM–66–14, and
IEC 62301 into DOE’s test procedure for
CFLs in appendix W.
As noted in section III.A.1, DOE
proposed in the July 2015 NOPR to
incorporate by reference IES LM–54–12,
IES LM–65–14, and IES LM–66–14 for
appendix W for seasoning, time to
failure measurements, and electrical and
photometric measurements respectively.
80 FR 45727. In response to this
proposal, both NEMA and OSI agreed
with the incorporation of IES LM–54–
12, IES LM–65–14, and IES LM–66–14.
(NEMA, No. 9 at pp. 3, 8; OSI, No. 5 at
pp. 2–3) The CA IOUs noted that the IES
LM–54–12 removes the requirement of
cycling during seasoning for metrics
other than lifetime and did not agree
with DOE’s proposal to, accordingly,
also remove the cycling requirements in
its test procedure. (CA IOUs, No. 7 at p.
3) DOE is requiring cycling for all
metrics, see section III.A.1 for further
details. In this final rule, DOE
incorporates by reference these test
methods into 10 CFR 430.3 for appendix
W or extends the incorporation by
reference of these test procedures to
appendix W.
As noted in section III.A.2.a, DOE also
proposed in the July 2015 NOPR to
incorporate by reference IESNA LM–78–
07 for appendix W for measurements
using an integrating sphere photometer.
80 FR 45731. DOE did not receive any
comments related to incorporating
IESNA LM–78–07. Therefore, in this
final rule, DOE incorporates by
reference this test method into 10 CFR
430.3 for appendix W.
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
As noted in section III.A.4.a, in the
July 2015 NOPR DOE proposed
incorporating CIE 13.3–1995 and CIE
15:2004 (3rd edition) for appendix W for
measuring and calculating CRI and CCT
respectively. 80 FR 45739. The CA IOUs
were supportive of incorporating by
reference both CIE 13.3–1995 and CIE
15:2004 (3rd edition). (CA IOUs, No. 7
at pp. 3–4) Therefore in this final rule,
DOE extends the incorporation by
reference of these test procedures to
appendix W.
As noted in section III.A.5.b, in the
July 2015 NOPR DOE proposed
incorporating by reference ANSI
C78.901–2014 for appendix W to
include reference ballast specifications
for non-integrated CFLs. 80 FR 45739.
NEMA supported incorporating by
reference ANSI C78.901–2014. (NEMA,
No. 9 at pp. 6–7) Therefore in this final
rule, DOE incorporates by reference this
industry standard into 10 CFR 430.3 for
appendix W.
As noted in section III.A.6, in the July
2015 NOPR, DOE proposed
incorporating by reference IEC 62301 for
appendix W for measuring standby
mode energy consumption. 80 FR
45739. DOE did not receive any
comments related to this proposal. DOE
notes that 10 CFR 430.3 presently has
two different versions of IEC 62301
incorporated. DOE is extending the
incorporation by reference of the edition
2.0, 2011–01 version of IEC 62301 to
appendix W.
D. Amendments to 10 CFR 430.23(y)
In the July 2015 NOPR, DOE proposed
to revise and add text at 10 CFR
430.23(y) to reflect other proposed
changes to the scope and applicability
of DOE’s CFL test procedures. 80 FR
45739. Specifically, the existing text at
10 CFR 430.23(y) indicates that, for
MBCFLs, the initial lamp efficacy,
lumen maintenance at 1,000 hours,
lumen maintenance at 40-percent of
rated life, and lamp life must be
measured, and the rapid cycle stress test
conducted, in accordance with section 4
of appendix W of this subpart. DOE
proposed to delete the text ‘‘medium
base’’ to reflect the inclusion of
additional CFL categories. Id. In
addition, in the July 2015 NOPR, DOE
also proposed to specify in 10 CFR
430.23(y) the relevant sections of
appendix W to be used to measure the
following metrics: Initial lamp efficacy,
lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of
lifetime, CRI, CCT, power factor, time to
failure, rapid cycle stress test, start time,
and standby mode energy consumption.
80 FR 45739–45740.
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
59405
Both NEMA and OSI submitted
comments requesting that DOE retain
the term ‘‘medium base’’ in the title of
the term because they did not think
non-integrated CFLs should be part of
the test procedures. (NEMA, No. 9 at p.
7; OSI, No. 5 at p. 6) DOE did not
receive any other comments related to
this proposed modification. As DOE has
stated previously, the test procedures
that are the subject of this final rule
address integrated and non-integrated
CFLs in support of existing and
potential standards, as well as
requirements of FTC’s Lighting Facts
Label and ENERGY STAR Program
Requirements for Lamps and
Luminaires (see section II for further
details). Therefore, in this final rule,
DOE is removing the reference to
‘‘medium base’’ and specifying all
applicable metrics for CFLs.
E. Amendments to Laboratory
Accreditation Requirements at 10 CFR
430.25
In the July 2015 NOPR, DOE proposed
to amend 10 CFR 430.25 to extend the
laboratory accreditation requirements
for MBCFL testing to additional CFL
categories and metrics covered under
the proposed new and amended test
procedures. 80 FR 45740. Specifically,
DOE proposed to replace the text
‘‘medium base compact fluorescent
lamps’’ with the text ‘‘compact
fluorescent lamps’’ and specify that if a
manufacturer’s or importer’s laboratory
is accredited, it may conduct the
applicable testing. Id.
NEMA and OSI raised concerns that
expanding testing in an accredited lab
from MBCFLs to all CFLs would
increase the testing burden, adding that
non-integrated CFLs typically are not
tested in accredited laboratories.
Additionally, NEMA and OSI asked that
this potential requirement be addressed
in both the manufacturing impact
analysis, as well as testing burden
analyzed in the regulatory flexibility
analysis. (NEMA, No. 9 at p. 9; OSI, No.
5 at p. 7)
Testing in accredited laboratories
helps ensure that measurements are
consistent and reproducible. Therefore,
in this final rule, DOE removes the
phrase ‘‘medium base’’ and specifies
that if a manufacturer’s or importer’s
laboratory is accredited, it may conduct
the applicable testing in 10 CFR 430.25.
See section IV.B for a discussion of test
burden.
F. Clarifications to Energy Conservation
Standard Text at 10 CFR 430.32(u)
MBCFL energy conservation
standards are codified in a table at 10
CFR 430.32(u). Certain language in the
E:\FR\FM\29AUR4.SGM
29AUR4
59406
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
MBCFL energy conservation standards
table provides clarification relevant to
test procedures (e.g., sampling, test
methods, and test calculations).
Although this clarifying language is not
in conflict with the specifications in the
test procedures for MBCFLs contained
in appendix W and in 10 CFR 429.35,
for simplicity DOE proposed to modify
the text in the MBCFL energy
conservation standards table to remove
specific test procedure language and
instead reference the relevant parts of
the MBCFL test procedures. In addition,
in the introductory paragraph of 10 CFR
430.32(u), DOE proposed to replace the
text ‘‘bare lamp and covered lamp’’ with
the text ‘‘bare or covered.’’ DOE
considered these revisions to be
clarifications that do not modify the
energy conservation standards. 80 FR
45740–45741.
NEMA and OSI in general agreed with
separating the test procedure
specifications from section (u) with
certain exceptions discussed in the next
sections. (NEMA, No. 9 at p. 9; OSI, No.
5 at p. 8) In this final rule, DOE retains
the change to the first sentence in 10
CFR 430.32(u) to read as ‘‘A bare or
covered (no reflector) medium base
compact fluorescent lamp manufactured
on or after January 1, 2006 . . .’’
Revisions to specific metrics in the table
at 10 CFR 430.32(u) and related
comments received are described in the
subsequent sections.
1. Initial Lamp Efficacy
In the July 2015 NOPR, DOE proposed
amending the first column of the table
in 10 CFR 430.32(u) by replacing the
seven instances of the text ‘‘lamp
power’’ with the text ‘‘labeled wattage.’’
80 FR 45740. DOE proposed to use
labeled wattage as that is the term DOE
is using to define the wattage marked on
the lamp that should be used to
determine the applicable minimum
efficacy requirement (see section
III.A.3.f). DOE also proposed deleting
the current text in footnote 1. Id.
NEMA and OSI recommended using
the term ‘‘rated wattage’’ rather than
‘‘labeled wattage.’’ (NEMA, No. 9 at p.
9; OSI, No. 5 at pp. 8–9) As discussed
in section III.A.3.f, DOE disagrees with
NEMA and OSI about using the term
‘‘rated wattage’’ because DOE believes it
may cause confusion or be easily
misinterpreted. Instead, DOE retains in
this final rule the term ‘‘labeled
wattage.’’
In the July CFL TP NOPR, DOE also
proposed to remove the text from
footnote 2 indicating that for multi-level
or dimmable systems, measurements
shall be at the highest setting, and
acceptable measurement error is ±3
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
percent. NEMA and OSI suggested
keeping the 3 percent measurement
error for efficacy and extend it to all
other parameters. (NEMA, No. 9 at p. 9;
OSI, No. 5 at pp. 8–9) DOE has
determined that a 3 percent tolerance is
not necessary. DOE addresses
measurement error in sample size,
confidence limit, and de-rating values as
provided in 10 CFR 429.35. Because this
allowance for determining compliance
with existing standards already exists in
10 CFR 430.32(u), the 3 percent
tolerance for efficacy has been
maintained but moved to 10 CFR
429.35.
2. Lumen Maintenance at 1,000 Hours
In the July 2015 NOPR, DOE proposed
amending the text for 1,000-hour lumen
maintenance in the second column of
the table in 10 CFR 430.32(u), which
indicates that the average of at least 5
lamps must have a minimum 90.0
percent of initial (100-hour) lumen
output at 1,000 hours of rated life. DOE
proposed to delete this text and only
state the standard as ≥90.0 percent. DOE
also provided specific other changes to
the table to correspond with
terminology in the amended test
procedure. 80 FR 45740. DOE did not
receive any comments regarding these
specific changes. Therefore, in this final
rule, DOE modifies 10 CFR 430.32(u) to
remove test procedure text and to align
the terminology with the amended test
procedure.
3. Lumen Maintenance at 40 Percent of
Lifetime
In the July 2015 NOPR, DOE proposed
amending the text for lumen
maintenance in the second column of
the table in 10 CFR 430.32(u), which
indicates 80.0 percent of initial (100hour) rating at 40 percent of rated life
(per ANSI C78.5 Clause 4.10). 80 FR
45740–45741. DOE proposed to delete
this text and state only the standard as
≥80.0 percent and other modifications to
the table to read lumen maintenance at
40 percent of lifetime. Id. DOE did not
receive any comments regarding these
specific changes. Therefore, in this final
rule, DOE modifies 10 CFR 430.32(u) to
remove test procedure text and to align
the terminology with the amended test
procedure. In addition, for clarity DOE
includes a footnote on the term
‘‘lifetime’’ that states ‘‘Lifetime refers to
lifetime of a compact fluorescent lamp
as defined in 10 CFR 430.2.’’
4. Rapid Cycle Stress Test
In the July 2015 NOPR, DOE proposed
amending the text in the second column
of the table for rapid cycle stress test in
10 CFR 430.32(u). 80 FR 45741. DOE
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
proposed to delete the first two
sentences of this text and to state that
each lamp must be cycled once for every
2 hours of lifetime and at least 5 lamps
must meet or exceed the minimum
number of cycles. Id.
NEMA and OSI responded that the
row in the table that codifies MBCFL
energy conservation standards at 10 CFR
430.32(u) specifically retains the term
‘‘rated lifetime.’’ (NEMA, No. 9 at p. 9;
OSI, No. 5 at p. 8) In this final rule, DOE
defines the term ‘‘lifetime of a compact
fluorescent lamp’’ to be used in the new
and amended test procedures (see
section III.A.3.a for further details).
Therefore, to align with the test
procedures, DOE amends table 10 CFR
430.32(u) in this final rule to state that
each lamp must be cycled once for every
2 hours of lifetime and at least 5 lamps
must meet or exceed the minimum
number of cycles. In addition, for clarity
DOE includes a footnote on the term
‘‘lifetime’’ that states ‘‘Lifetime refers to
lifetime of a compact fluorescent lamp
as defined in 10 CFR 430.2.’’
5. Lifetime
In the July 2015 NOPR, DOE proposed
amending 10 CFR 430.32(u) by deleting
the term ‘‘average rated lamp life’’ and
replacing it with the term ‘‘lifetime.’’ 80
FR 45741. DOE also proposed to amend
the text in the second column pertaining
to lifetime to only state the standard as
≥6,000 hours and that DOE will no
longer allow the use of statistical
methods at 80 percent of rated life to
determine the represented value of
lifetime. Id. NEMA and OSI stated that
the row should retain the text ‘‘≥6,000
hours as declared by the manufacturer
on packaging.’’ (NEMA, No. 9 at p. 9;
OSI, No. 5 at p. 8) In this final rule, DOE
defines the term ‘‘lifetime of a compact
fluorescent lamp’’ and provides test
procedures for the measurement and
reporting of this value. To avoid
potential confusion regarding how
lifetime should be measured, DOE
removes the language ‘‘as declared by
the manufacturer on packaging’’ in this
final rule. In addition, for clarity DOE
includes a footnote on the term
‘‘lifetime’’ that states ‘‘Lifetime refers to
lifetime of a compact fluorescent lamp
as defined in 10 CFR 430.2.’’
G. Amendments to Certification Report
Requirements
In the July 2015 NOPR, DOE
recognized that testing of CFL lifetime
and lumen maintenance at 40 percent of
lifetime require considerably more time
than testing of other required CFL
metrics. DOE proposed to allow new
basic models of CFLs to be distributed
prior to completion of the full testing for
E:\FR\FM\29AUR4.SGM
29AUR4
mstockstill on DSK3G9T082PROD with RULES4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
lifetime and lumen maintenance at 40
percent of lifetime, as well as prior to
completion for the rapid cycle stress test
because it is also dependent on lifetime.
DOE’s proposal was similar to other
lighting technologies in that prior to
distribution of the new basic model of
CFL, manufacturers may submit an
initial certification report based on
estimated values of lifetime, 40 percent
lumen maintenance, and rapid cycle
stress test if the testing for lifetime is not
complete. In such a case, the
certification report would be required to
specifically describe a prediction
method that would be generally
representative of the methods specified
in appendix W. Manufacturers would be
required to maintain relevant records, in
accordance with 10 CFR 429.71, of the
development of all estimated values and
any associated initial test data. DOE also
proposed amendments to the
certification report to address the new
and additional metrics that are being
adopted in this final rule and are
required for compliance with DOE’s
energy conservation standards. 80 FR
45741.
Philips commented that there
currently are no restrictions with
respect to the prediction models that
may be used, so selection of the
prediction model should be at the
discretion of the manufacturer, and
should only be disclosed to defend it to
the DOE if challenged. (Philips, No. 6 at
p. 4) NEMA and OSI similarly objected
to the proposed requirements that
manufacturers must disclose the
prediction method and that it must
represent one of the methods in
appendix W. (NEMA, No. 9 at p. 9; OSI,
No. 5 at p. 8; Philips p. 4)
The EEAs opposed DOE’s proposal to
allow manufacturers to estimate values
for lifetime and rapid cycle stress prior
to the completion of testing for time to
failure, and particularly opposed the
proposal that manufacturers be
permitted to develop their own
prediction methods for these estimates.
(EEAs, No. 8 at p. 5) The EEAs stated
that, by the time DOE received a full
certification report showing that a given
model did not meet the standard,
manufacturers may be retiring the
model and it will have been in
commerce for a significant portion of its
intended market life. The EEAs also
suggested it may be theoretically
possible to extrapolate lumen
depreciation provided a common
approach based on industry standard
methods is used. (EEAs, No. 8 at p. 5)
Based on a review of the market, DOE
found that most CFLs have a lifetime of
10,000 hours or longer and therefore, it
may take more than a year to complete
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
the necessary lifetime measurements.
Therefore, to accommodate such long
testing time, DOE believes that the use
of estimated values for lifetime, lumen
maintenance at 40 percent of lifetime,
and rapid cycle stress testing are
required. In response to the concerns of
CA IOUs and the EEAs regarding the
accuracy of such methods, DOE notes
that DOE is not aware of any industrywide accepted method for extrapolation
of lumen depreciation for CFLs.
Therefore, DOE is not requiring a
specific prediction method for estimated
values. However, DOE is requiring
manufacturers to specify the method of
prediction and that this method must be
generally representative of DOE’s test
procedures for CFLs in appendix W. In
addition, DOE is adding a requirement
to the certification report that
manufacturers must state whether
values of lifetime, lumen maintenance
at 40 percent of lifetime, and rapid cycle
stress testing are based on estimated or
measured values. DOE believes that, as
noted by CA IOUs and EEAs, such
information regarding the prediction
methods used by manufacturers is
necessary in order to verify that such
predictions are valid and based on
sound engineering judgement and
calculations. Therefore, DOE believes
that these requirements regarding the
prediction method are adequate and
necessary to ensure estimated values are
reliable, representative, and consistent
with test conditions, setup, and
methods specified in DOE’s test
procedures for CFLs.
In addition, DOE notes that there is
precedent for allowing products to be
distributed in commerce based on
estimated values. DOE allows initial
certification reports for GSFLs and
incandescent reflector lamps and also
requires that manufacturers include a
description of any testing or analysis the
manufacturer performed. 10 CFR
429.12(e)(2) Under EPCA, MBCFLs may
be marketed before completion of
testing for lifetime and lumen
maintenance at 40 percent of lifetime
with supporting engineering predictions
and analysis. 42 U.S.C. 6293(b)(12)(C).
Therefore, by allowing new basic
models of CFLs to be distributed in
commerce based on estimated values
determined by prediction methods
representative of DOE’s test procedures
for CFLs, DOE is ensuring products are
available to consumers in a reasonable
time while still requiring a rigorous
process to ensure that all representative
values are as accurate and precise as
possible. In this final rule, DOE also
clarifies that for existing basic models
that require retesting, manufacturers
may submit an initial certification
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
59407
report based on estimated values of
lifetime, 40 percent lumen maintenance,
and rapid cycle stress if the testing for
lifetime is not complete.
The EEAs also recommended that
DOE take action to enhance industry
adherence with the CFL test procedure.
They noted that under two CFL
verification testing programs, ENERGY
STAR and the Program for the
Evaluation and Assessment of
Residential Lighting (PEARL), a
significant number of ENERGY STARqualified CFLs were found to be
noncompliant with ENERGY STAR
program requirements. The EEAs noted
that these results varied between
brands, but the overall consumer
dissatisfaction and perception of poor
CFL quality applied throughout the
industry, regardless of a particular
brand’s performance. The EEAs
suggested DOE collect and analyze
performance data for CFLs sold in the
retail distribution chain and adopt an
enhanced enforcement strategy focused
on brands, rather than only basic
models. The EEAs recommended that
DOE require manufacturers to submit
data that support the enhanced
enforcement strategy and to tighten data
submission requirements to prevent
manufacturers from submitting
incomplete or incorrect test data that
may misrepresent the quality of
products being verified. (EEAs, No. 8 at
pp. 6–7)
DOE currently has enforcement
procedures in place for, among many
other products, CFLs that are subject to
energy conservation standards. For more
information please refer to DOE’s
‘‘Implementation, Certification, and
Enforcement’’ Web site at https://
energy.gov/eere/buildings/
implementation-certification-andenforcement.
Additionally in the July 2015 NOPR,
DOE proposed that if, prior to
completion of testing, a manufacturer
ceases to distribute in commerce a basic
model, the manufacturer must submit a
full certification report and provide all
of the information listed in 10 CFR
429.12(b), including the productspecific information required by 10 CFR
429.35(b)(2), as part of its notification to
DOE that the model has been
discontinued. 80 FR 45741. DOE did not
receive any comments regarding this
proposal and adopts it in this final rule.
This provision will help alleviate
potential issues envisioned by the EEAs
that models will be retired without any
accountability for compliance with the
standards.
Further, for this final rule, DOE
separated the certification report
requirements for medium base CFLs that
E:\FR\FM\29AUR4.SGM
29AUR4
59408
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
are showing compliance with the
current energy conservation standards,
integrated CFLs that would need to
show compliance with potential GSL
energy conservation standards, and nonintegrated CFLs which may need to
show compliance with potential GSL
energy conservations standards. DOE
separated these requirements in order to
clarify that different values must be
reported when certifying compliance to
existing standards in 430.32(u) (as it
appears in 10 CFR parts 200–499 edition
revised as of January 1, 2016) for
medium base CFLs; general service
lamp energy conservation standards (if
adopted) for integrated CFLs; and
general service lamp energy
conservations standards (if adopted) for
non-integrated CFLs.
mstockstill on DSK3G9T082PROD with RULES4
H. Amendments to 10 CFR 429.35
The text of the 10 CFR 429.35 title
currently addresses bare or covered (no
reflector) MBCFLs. DOE proposed in the
July 2015 NOPR to remove this text and
identical text found in § 429.35(a)(1)
and (a)(2), and replace it with the text
‘‘compact fluorescent lamps’’ to reflect
the inclusion of additional CFL
categories. 80 FR 45741. DOE did not
receive any comments on this proposal
and therefore adopts this change in the
final rule.
In addition, DOE also proposed to
clarify and amend the sampling
requirements for existing and new
metrics, provide clarification on reuse of
samples, and address failures of sample
units. 80 FR 45741. DOE concluded that
these clarifications and amendments
would not have a significant effect on
measured values or test burden. Id. In
general, the EEAs were supportive of
DOE’s proposed changes to sampling
requirements. (EEAs, No. 8 at pp. 2–4)
DOE received comments related to the
specific proposals to 10 CFR 429.35 and
discusses these in detail in the
following sections.
1. Initial Lamp Efficacy and Lumen
Maintenance
Currently, in 10 CFR 429.35, sampling
requirements are specified for efficacy,
1,000-hour lumen maintenance, and
lumen maintenance at 40 percent of
rated life. In the July 2015 NOPR, DOE
proposed to replace the terms efficacy,
1,000-hour lumen maintenance, and
lumen maintenance, respectively, with
the terms initial lamp efficacy, lumen
maintenance at 1,000 hours, and lumen
maintenance at 40 percent of lifetime.
80 FR 45741–45742.
DOE also proposed to create a
separate sampling requirement section
for initial lamp efficacy in order to
include an allowance of 3 percent
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
tolerance on the represented value of
this metric (see section III.F.1).
Specifically, DOE proposed that, to
account for measurement error, the
represented value for initial lamp
efficacy of MBCFLs may include 3
percent added to the lower of (a) the
mean of the sample and (b) the lower
97.5 percent LCL of the true mean
divided by 0.95. For example, if the
lower value is the mean of the sample
at 60.0 lumens per watt, then the 1.03
multiplier could be applied to yield a
represented value for initial lamp
efficacy of up to 61.8 lumens per watt.
DOE concluded that this clarification
does not result in a significant impact to
measured values. DOE received
comments on this proposal and
addresses them in section III.F.1. In this
final rule, DOE adopts the proposal
regarding the 3 percent tolerance for
initial lamp efficacy as described in this
preamble.
Additionally, DOE proposed to
expand the sample size from a
minimum of 5 units to a minimum of 10
units for initial lamp efficacy, 1,000
hour lumen maintenance, and lumen
maintenance at 40 percent of lifetime.
80 FR 45742. Further DOE proposed
that if more than 10 units are tested as
part of the sample for these three
metrics, the total number of units must
be a multiple of two so that an equal
number of units can be tested base up
and base down. DOE also notes that,
because the sample set must be the same
for all metrics, if the sample size is
greater than 10, the same larger sample
set must be used for the other metrics
required to utilize the sample set (see
III.H.5).
In the July 2015 CFL TP NOR, DOE
also proposed that half of the units be
tested base up and half of the units be
tested base down, rather than testing all
units base up as currently required.
Testing in both the base up and base
down positions provides an accurate
representation of performance under
both orientations since the end-use
orientation is unknown. 80 FR 45742.
OSI raised concerns that adding
another orientation besides base up will
effectively double testing costs by
increasing the number of units under
test as well as increasing the
infrastructure required. OSI also stated
that in many cases, manufacturers have
evaluated products only in the base up
position. (OSI, No. 5 at p. 8) NEMA
stated that modifying the orientation
specification would change measured
values and add test burden. (NEMA, No.
9 at pp. 3, 8)
Test burden is discussed in section
IV.B. DOE notes that ENERGY STAR has
required both a sample size of 10 and
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
that half be tested in the base up
position and the other half in the base
down position orientations since
version 3.0 of the ‘‘ENERGY STAR®
Program Requirements for CFLs’’, which
was finalized in 2003.22 CA IOUs
commented (and DOE verified) that
according to ENERGY STAR 64 percent
of integrated CFLs shipped in 2014 were
ENERGY STAR certified. (CA IOUs, No.
7 at p. 4) Therefore, a majority of
integrated CFLs have already been
evaluated in both orientations.
NEMA and OSI stated that if testing
of non-integrated CFLs is necessary, that
these lamps should only be tested in the
base up position as base down testing is
not representative of actual usage.
Further, both NEMA and OSI raised
concerns about the burden related to
testing non-integrated CFLs in both base
up and base down orientations. (NEMA,
No. 9 at p. 10; OSI, No. 5 at p. 8)
Test burden is discussed in section
IV.B. Contrary to the assertion of NEMA
and OSI that base down orientation
would not be representative of actual
use for non-integrated CFLs, DOE has
identified fixtures for non-integrated
CFLs classified as ‘‘chandelier,’’
‘‘decorative pendant,’’ and ‘‘sconce/
marker light’’ all with base down lamp
orientations.23 DOE retains in this final
rule that, for both integrated and nonintegrated CFLs, half the sample size be
tested in the base up and the other half
in base down orientation.
In the July 2015 NOPR, DOE also
proposed to specify in 10 CFR 429.35
that any represented value of lumen
maintenance at 40 percent of lifetime
must be based on a lifetime value that
is equal to or greater than the
represented value of lifetime. DOE did
not receive any comments regarding this
proposal; therefore, DOE adopts it in
this final rule.
2. Rapid Cycle Stress Testing
In the July 2015 NOPR, DOE proposed
to restrict the sample size for rapid cycle
stress testing to an exact number of
units. 80 FR 45742. Currently, the
sampling size for rapid cycle stress
testing is specified at 10 CFR
429.35(a)(2)(ii) as no less than 6 unique
units. DOE proposed specifying that
exactly 6 unique units must be tested
22 Version 3.0 of the CFL lamps specification was
superseded by other versions of the CFL lamp
specification and then ultimately the CFL
specification was replaced by the overall lamp
specification. However, the original specification
can be found at https://www.energystar.gov/
products/spec by searching lighting, light bulbs
(CFLs) and historic in status.
23 DOE conducted a search using eLumit, an
independently owned, industry-neutral company
that is a lighting search and specification tool for
design professionals. www.eLumit.com.
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
per basic model for rapid cycle stress
testing with the rationale that this new
specification will minimize confusion
and improve consistency in the number
of samples used for testing. 80 FR
45742. This new sampling requirement
is consistent with the sample size
requirement for rapid cycle stress
testing in the ENERGY STAR Lamps
Specification V2.0. DOE did not receive
any comments related to the sample size
for rapid-cycle stress testing and
therefore adopts the requirement in this
final rule that the sample size for rapidcycle stress testing be 6 unique units.
NEMA and OSI stated that lamp
orientation has little effect on the rapid
cycle stress testing and suggested that
testing half of the lamps base up and
half base down would be an additional
burden that would not affect the results
of the rapid-cycle stress test. (NEMA,
No. 9 at p. 10; OSI, No. 5 at p. 8)
Rapid cycle stress testing is intended
to stress the lamp’s electrical
components to evaluate the performance
of a lamp undergoing repeated cycling.
Lamp orientation affects the thermal
conditions of the lamp. Because
temperature has some impact on the
performance of a lamp’s electrical
components, testing in both base up and
base down orientations will provide a
more comprehensive set of results for
assessing rapid cycle stress. Therefore,
in this final rule, DOE specifies in
appendix W that for rapid cycle stress
testing half of the units must be tested
in the base up position, and half of the
units must be tested in the base down
position, but that if the position is
restricted by the manufacturer, units
must be tested in the manufacturerspecified position.
In the July 2015 CFL NOPR, DOE also
proposed a new paragraph in 10 CFR
429.35 that any represented value of
rapid cycle stress test surviving units
must be based on a lifetime value that
is equal to or greater than the
represented value of lifetime. 80 FR
45742. DOE did not receive any
comments on this proposal and
therefore, adopts it in this final rule.
3. Lifetime of a Compact Fluorescent
Lamp
In the July 2015 NOPR, DOE proposed
clarifying the sampling requirements for
the lifetime of a CFL, including the
position in which lamps are tested.
Specifically DOE proposed to align the
sampling requirements for lifetime with
the sampling requirements for initial
lamp efficacy and lumen maintenance.
DOE clarified that if more than 10 units
are tested as part of the sample, the total
number of units must be a multiple of
two and the time to failure value as
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
determined per section 3.3 of appendix
W must be used to determine the
represented value of lifetime. 80 FR
45742. DOE did not receive any
comments regarding this proposal and
therefore, in this final rule, adopts it as
proposed.
4. New Metrics
As discussed in section III.A.4 in this
document, DOE establishes test
procedures for measuring new metrics
including CRI, power factor, CCT, start
time, and standby mode energy
consumption. For CRI, power factor,
CCT, and standby mode power, in the
July 2015 NOPR, DOE proposed
requiring a sample size of at least 10
(half base up and half base down).
Testing in both the base up and base
down positions provides an accurate
representation of performance under
both orientations since the end-use
orientation is unknown. DOE also
proposed specifying within the
sampling requirements for CRI, power
factor, CCT, and standby mode power,
that, if more than 10 units are tested as
part of the sample, the total number of
units must be a multiple of two.
DOE proposed to specify the same
sampling requirements for CRI and
power factor as those specified for
initial lamp efficacy, lumen
maintenance at 1,000 hours, and lumen
maintenance at 40 percent of lifetime in
10 CFR 429.35. Thus, for CRI and power
factor, DOE determined that
representations of these metrics be equal
to the lesser of the mean of the sample
and the 97.5 percent LCL divided by
0.95. Since higher values are desirable
for CRI and power factor, use of the
lesser of the mean and LCL ensures that
a representative value is reported.
Because there are no targeted upper or
lower bound values for CCT, DOE
proposed to specify in 10 CFR 429.35
that representations of CCT be the mean
of the sample.
For the start time, DOE proposed a
sample size of three units in 10 CFR
429.35. DOE believes this is an
appropriate sample size to determine an
accurate value for the lamp start time.
Further, DOE proposed that for start
time, representations be equal to the
greater of the mean of the sample and
the 97.5 percent upper confidence limit
(UCL) divided by 1.05, since lower
values are desirable.
For standby mode power, DOE
proposed to specify in 10 CFR 429.35 a
sample size of at least 10 units,
consistent with that used for the active
mode power metric and initial lamp
efficacy. DOE determined that
representations should be equal to the
greater of the mean of the sample and
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
59409
the 97.5 percent UCL divided by 1.05,
as lower values are desirable.
DOE notes that the current sampling
requirements already require 10 units
for determining lifetime, and that
several of these metrics (e.g., CRI, CCT,
and power factor values) can be
determined in the course of lifetime
testing. Additionally, this sampling plan
is consistent with the sampling
requirements for these metrics in the
ENERGY STAR Lamps Specification
v2.0.
OSI stated that power factor, CRI, and
start time requirements are not
necessary and thus the proposed
sampling requirements should not be
included. (OSI, No. 5 at p. 9) As noted
previously, DOE is establishing test
procedures that include sampling
requirements for power factor, CRI, and
start time, in support of the ongoing
GSL standards rulemaking (see section
II for further details). Therefore, DOE
retains the sampling plan for these
metrics in this final rule. However, DOE
notes that power factor and start time
measurements are not applicable to or
required for non-integrated CFLs.
NEMA and OSI also commented on
DOE’s use of the lower confidence level
(LCL), UCL, and statistical divisor in
determining represented values. They
argued that DOE’s current methodology
is biased and statistically incorrect and
recommended DOE use only the sample
mean as it is the best estimator of the
population parameters. (NEMA, No. 9 at
p. 10; OSI, No. 5 at p. 9)
Confidence limits are a valid
statistical method used to understand
the accuracy of the sample mean. By
using confidence limits, DOE is able to
implement a conservative approach,
ensuring that products on the market
perform at least as well as represented
by manufacturers, by requiring the
lower confidence limit value if it is less
than the sample mean when higher
values are desirable and requiring the
upper confidence limit if it is greater
than the sample mean when lower
values are desirable. DOE finds this
methodology more appropriate in
determining represented values than
relying only on the sample mean.
Therefore, in this final rule, DOE retains
the confidence limit methodology for
existing metrics and implements it for
new metrics, where applicable.
DOE also clarifies that on or after 180
days after publication of this final rule,
manufacturers of MBCFLs must use the
test procedures established in this final
rule to certify compliance with existing
standards and for any representations
regarding energy use or efficiency, and
manufacturers of other CFLs without
existing standards must use the test
E:\FR\FM\29AUR4.SGM
29AUR4
59410
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
procedures for any representations
regarding energy use or efficiency. As of
the compliance date of any standards
adopted in the GSL ECS rulemaking,
manufacturers must use the test
procedures established in this final rule
to certify compliance with GSL
standards, if adopted. (See section III.J
for further details regarding effective
dates.) Further, in this final rule, DOE
specifies sampling requirements specific
to metrics of integrated CFLs and nonintegrated CFLs.
5. Reuse of Samples
In the July 2015 NOPR, DOE proposed
to specify in 10 CFR 429.35 that the
same sample of units must be used to
determine initial lamp efficacy, lumen
maintenance at 1,000 hours, lumen
maintenance at 40 percent of lifetime,
lifetime, CRI, CCT, power factor, start
time, and standby mode power. 80 FR
45743.
NEMA and OSI commented that reuse
of samples should not be mandatory
except in the case of lumen
maintenance values where a ratio is
required involving the initial
measurements. NEMA and OSI stated
that the manufacturer should be
permitted to use representative samples
and make measurements in parallel to
reduce the time burden of measurement.
OSI also stated that this requirement
would preclude large sample size life
tests in which the lamps would run
uninterrupted until failure. NEMA
added that it is restrictive to require the
same samples for all tests completed for
one basic model. (NEMA, No. 9 at p. 10–
11; OSI, No. 5 at p. 9) Philips
commented that manufacturers should
be allowed to test larger populations for
lifetime than for photometric-related
measurements. (Philips, Public Meeting
Transcript, No. 4 at p. 90) GE
recommended that, rather than
requiring the reuse of a sample across
all tests, DOE should require that all test
units must be drawn from the same
population. (GE, Public Meeting
Transcript, No. 4 at pp. 91–95)
By requiring the same sample set to be
used across all metrics, DOE ensures
sample units are not selected to obtain
favorable measurements for one metric
over others and that all representative
values are internally consistent and
representative of the population (to the
extent the selected test sample is
representative of the population). The
lifetime measurement is just an
extension of the other photometric
measurements taken at different points
in time of the same lamp. DOE believes
taking these photometric measurements
such as efficacy, lumen maintenance,
and lifetime on the same set of lamps
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
will result in a better characterization of
the photometric performance of the
population by minimizing the variation
that may be introduced into the
measurement by using different test
units for different metrics. Hence, the
requirement of the same sample set
allows for a more accurate assessment of
a basic model’s compliance with
standards for all metrics. Therefore,
DOE retains in this final notice that the
same sample of units must be used as
the basis for representations for standby
power, power factor, CCT, CRI, initial
lumen output, input power, initial lamp
efficacy, lumen maintenance at 1,000
hours, lumen maintenance at 40 percent
of lifetime, and lifetime; no less than
three units from the same sample of
units must be used when testing for the
start time; and exactly six unique units
must be used for rapid cycle stress
testing. Additionally, in this final rule,
DOE specifies that sample units must be
comprised of production units. For
those basic models that currently make
representations of the energy efficiency
metrics described in this test procedure,
including medium base CFLs,
manufacturers must ensure that
representations, including certifications,
are made in accordance with the DOE
test procedure, including sampling plan.
While DOE believes manufacturers have
been following these testing procedures,
including sampling plans, for making
current representations, DOE clarifies
that a manufacturer may need to retest
in the event that the current
representations are not supported by the
test when measured in accordance with
the method being adopted in this final
rule, including the sampling plan.
6. Lamp Failures
In the July 2015 NOPR, DOE also
clarified that, if a lamp breaks, becomes
defective, fails to stabilize, exhibits
abnormal behavior such as swirling or
stops producing light, prior to the end
of the seasoning period, the lamp must
be replaced with a new unit. 80 FR
45732. If a lamp fails after the seasoning
period, the lamp’s measurements must
be included when calculating
represented values. Id.
The CA IOUs stated that lamps that
fail during lamp seasoning (‘‘early
failure lamps’’) should also be
maintained in the sample and new units
should be added until the required units
pass the seasoning period. The CA IOUs
stated that not including units that fail
during the seasoning period in the
sample set will result in inaccurate
measurements of metrics. The CA IOUs
gave the example where a manufacturer
might test 100 units, 90 of which would
fail during seasoning, and report the
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
lifetime of the lamp based on the 10
units that passed. The CA IOUs asserted
that these early failures cause consumer
dissatisfaction related to CFL lifetime.
Citing an ENERGY STAR report 24 the
CA IOUs stated that the majority of
verification testing failures for CFLs in
ENERGY STAR are related to tests for
product lifetime (e.g., interim life test,
lumen maintenance, and rapid cycle
stress tests). Additionally, the CA IOUs
and the EEAs cited a study conducted
by PEARL that found that 2 to 12
percent of the CFLs tested failed to
reach 40 percent of rated life. (CA IOUs,
No. 7 at pp. 1–3; CA IOUs, Public
Meeting Transcript, No. 4 at pp. 38–41,
89)
The CA IOUs further stated that the
number of ‘‘early failures’’ should be
recorded along with the time and
manner of failure. The CA IOUs also
suggested that DOE require the entire
sample set to be discarded if one unit
fails during seasoning in order to
incentivize manufacturers to produce
higher quality products. Additionally,
the CA IOUs recommended DOE
evaluate data on early CFL failures to
verify that the majority of early failures
occur in the first 100 hours of operation
and increase this time interval for
recording early failures, if necessary.
(CA IOUs, No. 7 at p. 3)
The EEAs supported CA IOUs written
comments related to early failures,
noting that ignoring early failures would
make it difficult to develop metrics to
address these failures. The EEAs added
that lamps that fail during seasoning
would fall in the category of
manufacturing defect, a category of
lamp failure identified in IES LM–65–
14. (EEAs, No. 8 at p. 3) GE (with
Philips concurring) agreed that failures
of lamps ‘‘right out of the box’’
represented a manufacturing defect and
stated it is appropriate to remove these
from the sample during seasoning. (GE,
Public Meeting Transcript, No. 4 at p.
38, Philips, Public Meeting Transcript,
No. 4 at p. 38) Westinghouse stated that
its products were not experiencing
industry failures within the warranty
period, and definitely not within the
first 100 hours. Westinghouse added
that lamps that did fail early would not
pass DOE’s verification testing and
therefore, would not be available on the
market. (Westinghouse, Public Meeting
Transcript, No. 4, at pp. 40–41)
DOE evaluated the reports cited by
CA IOUs and EEAs in their comments,
specifically, ENERGY STAR verification
24 Overview of CFL Verification Testing Results
Jan 2010-Apr 2014. EPA. 2014. www.energystar.gov/
sites/default/files/specs/
Presentation%20Verification%20Testing%207-3114.pdf.
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
mstockstill on DSK3G9T082PROD with RULES4
test report of 2014 and the study
conducted by PEARL. While both of
these reports indicate that there are
lamps that fail to meet metrics related
to product lifetime, neither support that
these failures are due to lamps failing in
the first 100 hours of the lamp lifetime.
Both documents only report failures
before 40 percent of rated life as one
aggregated value with no data on actual
time of failure. Further, DOE evaluated
results of a study conducted by the
California Public Utility Commission
that provided data on the number of
hours before failure for 72 models of
MBCFLs with a sample set of 3601
lamps that were tested on 10 different
cycling times. Of the 360 lamps tested
on the 180 minute cycling time, the
same as the cycling time for lifetime
testing, none of the lamps failed during
the first 100 hours of testing.25
Based on available data, DOE finds
that it is not common for CFLs to fail
before the seasoning period; therefore,
the requirement that a sample unit be
replaced if it fails during seasoning will
not result in appreciably less accurate
measurements. DOE notes that its
proposed method for addressing lamp
failures aligns with ANSI C78.5–2003,26
which provides specifications on
integrated CFLs and is referenced by IES
LM–65–14 (incorporated by reference).
Section 6.1.2 of ANSI C78.5–2003 notes
that ‘‘. . . if a unit fails to stabilize or
exhibits abnormal behavior, the lamp
shall be discarded. Testing shall resume
with a suitable replacement specimen
procured and prepared in the same
manner as the original specimen. The
use of replacement specimens shall be
documented in the test report.’’ Further,
section 3.1 of IES LM–65–14 states that
lamp failures due to manufacturing
defects are reported but not included in
the calculation of lamp lifetime.
Therefore, in this final rule, DOE retains
the requirement that, if a lamp breaks,
becomes defective, fails to stabilize,
exhibits abnormal behavior such as
swirling or stops producing light prior
to the end of the seasoning period, the
lamp must be replaced with a new unit.
DOE also notes that ANSI C78.5–2003
and IES LM–65–14 recommend
respectively, recording replacement of
sample units and failures. Because such
data can be informative, in this final
rule, DOE adds the requirement that
manufacturers must provide in the
25 CFL
Laboratory Testing Report: Results from a
CFL Switching Cycle and Photometric Laboratory
Study. December 9, 2015. California Public Utilities
Commission.
26 American National Standard For Electric
Lamps: Specifications for Performance of SelfBallasted Compact Fluorescent lamps (approved
2003).
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
certification report, the number of
sample units replaced within each
unique sample set used in determining
represented values and believes that
such information could be helpful to
consumers or interested parties in
determining more reliable CFL models,
as requested by the CA IOUs and EEAs.
I. Federal Trade Commission (FTC)
Labeling Requirements
As discussed throughout this
document, the CFL test procedure
adopted in this final rule is intended,
among other things, to support FTC’s
Lighting Facts Labeling program.
Accordingly, in the July 2015 NOPR,
DOE proposed adding provisions to 10
CFR 429 for initial lumen output, input
power, CCT, estimated annual energy
cost, and life (in years) for MBCFLs to
enable FTC to allow manufacturers to
submit data through DOE’s Compliance
Certification Management System
(CCMS) for the FTC labeling
requirements. 80 FR 45743. Except for
CCT, these metrics are already being
determined as part of the existing test
procedures in appendix W. For
example, initial lumen output and input
power (a standalone metric and also
part of the calculation for estimated
annual energy cost) are the two
quantities required to calculate the
existing metric of initial lamp efficacy.
Furthermore, the life (expressed in
years) is determined by dividing the
existing metric of lifetime by an average
operating hour value specified by FTC.
NEMA stated that the test procedures
should not be developed for lamps not
regulated by FTC. NEMA highlighted
the fact that FTC’s label does not cover
non-integrated CFLs and reiterated that
non-integrated CFLs should not be
included in the test procedure. (NEMA,
No. 9 at p. 2)
As noted previously, the test
procedures that are the subject of this
rulemaking are intended to support
existing and potential standards for
CFLs and ENERGY STAR lamp and
luminaire specifications, as well as
support the FTC Lighting Facts labeling
requirements. DOE did not receive any
other comments related to the proposed
provisions for DOE to collect FTC
Lighting Facts labeling data through
DOE’s CCMS. Therefore, in this final
rule, DOE adopts the provisions as
described in this preamble.
J. Effective Date
In the July 2015 NOPR, DOE specified
that the effective date for the amended
test procedures would be 30 days after
publication of the final rule in the
Federal Register. 80 FR 45743.
Representations based on the amended
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
59411
and new test procedures would be
required as of 180 days after publication
of the final rule. (42 U.S.C. 6293(c)(2))
DOE received several comments
regarding these dates and certifications
of compliance for products according to
the new and amended test procedures.
NEMA and OSI asked DOE to provide
clarification on the need to retest lamps
that are already certified in the CCMS
database, or if industry is allowed to use
existing test reports for current
products. (NEMA, No. 9 at p. 2; OSI, No.
5 at p. 2) OSI also sought clarification
from DOE regarding the disposition of
existing inventory if retesting is
required for current products. (OSI,
No.5 at p. 2)
Representations related to the metrics
addressed in the amended Appendix W
must reflect testing in accordance with
Appendix W not later than February 27,
2017. Representations are not required
by DOE for CFLs not currently subject
to standards (although they may be
required by the FTC). In contrast,
certifications of compliance are required
for medium base CFLs, which are
currently subject to standards; those
certifications must reflect testing in
accordance with the amended Appendix
W as of the next annual certification
date or February 27, 2017, whichever is
later. DOE also reiterates, as noted
throughout this document, that the new
and amended test procedures are not
anticipated to result in changes in
measured energy consumption or other
performance metrics for any products
that are currently subject to energy
conservation standards and thus
required to certify compliance to DOE.
Therefore, existing medium base CFLs
may not require re-testing if their
representative values continue to be
valid.
Certifications of compliance for basic
models of CFLs with any new and/or
amended energy conservation standards
must reflect testing in accordance with
Appendix W as amended in this final
rule, prior to distribution in commerce,
and annually thereafter by the filing
date specified in 10 CFR 429.12(d);
however, no basic model is required to
be certified until it is required to
comply with energy conservation
standards. Therefore, for CFLs not
currently subject to standards, the initial
certification report must be filed by the
compliance date of any new energy
conservation standards.
NEMA and OSI stated that due to the
additional testing required by the new
and amended test procedures
established in this final rule, it was not
practical to certify all lamps to the new
and amended test procedures by the
next annual filing date for certification.
E:\FR\FM\29AUR4.SGM
29AUR4
mstockstill on DSK3G9T082PROD with RULES4
59412
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
In particular, OSI cited changes to the
sample size and orientation; and NEMA
added testing for rapid cycle stress.
NEMA and OSI noted that publication
of the final rule for the ongoing GSL
standards rulemaking is expected before
the end of 2017. They requested that
until March 1, 2018, only new CFLs
certified after the publication of this test
procedure final rule be required to be
tested under the new and amended CFL
test procedures established by it; and
after March 1, 2018, all CFLs must be
tested under the new and amended CFL
test procedures. NEMA and OSI
reasoned this would minimize testing
burden on industry for current products
that are expected to be rendered
obsolete by the ongoing GSL standards
rulemaking. (NEMA, No. 9 at p. 11; OSI,
No. 5 at p. 9)
The change in sample size and
orientation requirements adopted in this
final rule align with ENERGY STAR
Lamps Specification V2.0 (effective
January 1, 2017) and its previous
version, with the only exception being
that DOE is requiring 3 units tested base
up, and 3 units tested base down for the
rapid cycle stress test. DOE notes that
two thirds of compact fluorescent lamps
already comply with ENERGY STAR,
which already requires 10 units to be
tested, and does not believe the change
in orientation requirements for the rapid
cycle stress test would require an
extensive change to the existing test
setup. While DOE is adopting test
procedures for additional metrics,
several of these metrics (e.g., CCT, CRI,
power factor) can be determined
simultaneously with existing metrics
such as efficacy, and therefore testing
new metrics would not require a
significant amount of additional time to
conduct.
Further for new basic models or
existing basic models that require
retesting because their certified values
are no longer valid, if a metric requires
a longer period of time to test (lifetime,
lumen maintenance at 40 percent of
lifetime), DOE allows for the reporting
of estimated values until the testing is
complete. Therefore, DOE finds that
manufacturers should be able to certify
and make representations of all
applicable CFL products within 180
days of the publication of this final rule.
Hence, the effective date for the new
and amended test procedures discussed
in this final rule will be 30 days after
publication of this document in the
Federal Register. Representations must
reflect testing in accordance with the
new and amended test procedure not
later than 180 days after publication of
the final rule. (42 U.S.C. 6293(c)(2))
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
After the effective date and prior to
180 days following publication of this
CFL test procedure final rule,
manufacturers may voluntarily begin to
make representations with respect to the
energy use or efficiency of CFLs
(including but not limited to MBCFLs)
using the results of testing pursuant to
this final rule. On or after 180 days after
publication of this final rule, any
representations including certifications
of compliance (if required), made with
respect to the energy use or efficiency of
CFLs (including but not limited to
MBCFLs) must be made in accordance
with the results of testing pursuant to
the new and amended test procedures.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Order 12866
The Office of Management and Budget
(OMB) has determined that test
procedure rulemakings do not constitute
‘‘significant regulatory actions’’ under
section 3(f) of Executive Order 12866,
Regulatory Planning and Review, 58 FR
51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under
the Executive Order by the Office of
Information and Regulatory Affairs
(OIRA) in OMB.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility
analysis (IFRA) for any rule that by law
must be proposed for public comment
and a final regulatory flexibility analysis
(FRFA) for any such rule that an agency
adopts as a final rule, unless the agency
certifies that the rule, if promulgated,
will not have a significant economic
impact on a substantial number of small
entities. As required by Executive Order
13272, ‘‘Proper Consideration of Small
Entities in Agency Rulemaking,’’ 67 FR
53461 (August 16, 2002), DOE
published procedures and policies on
February 19, 2003 to ensure that the
potential impacts of its rules on small
entities are properly considered during
the DOE rulemaking process. 68 FR
7990. DOE has made its procedures and
policies available on the Office of the
General Counsel’s Web site: https://
energy.gov/gc/office-general-counsel.
DOE reviewed this final rule, which
amends and establishes new test
procedures for CFLs, under the
provisions of the Regulatory Flexibility
Act and the procedures and policies
published on February 19, 2003. DOE
certifies that the rule will not have a
significant economic impact on a
substantial number of small entities.
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
The factual basis for this certification is
as follows.
The Small Business Administration
(SBA) considers a business entity to be
a small business, if, together with its
affiliates, it employs less than a
threshold number of workers specified
in 13 CFR part 121. These size standards
and codes are established by the North
American Industry Classification
System (NAICS). Manufacturing of CFLs
is classified under NAICS 335110,
‘‘Electric Lamp Bulb and Part
Manufacturing.’’ The SBA sets a
threshold of 1,250 employees or less for
an entity to be considered as a small
business for this category.
DOE conducted a focused market
survey reviewing information from trade
associations such as NEMA; ENERGY
STAR programs; market reports (e.g.
Hoover’s reports); and individual
company Web sites to identify
companies that sell products covered by
this rulemaking. DOE then determined
the number of small businesses based
on SBA definition. In its estimation of
a company’s number of employees, DOE
also includes any parent companies
and/or subsidiaries. In the July 2015
NOPR, DOE identified 26 manufacturers
that would be considered small
businesses. 80 FR 45744. Westinghouse
indicated the number of small
businesses identified by DOE was less
than expected, noting that there are only
a handful of large-size businesses in the
market. (Westinghouse, Public Meeting
Transcript, No. 4 at pp. 134–136)
For this final rule, DOE reviewed its
estimated number of small businesses.
DOE updated its list of small businesses
by reviewing information from trade
associations such as NEMA; ENERGY
STAR programs; market reports (e.g.
Hoover’s reports); and individual
company Web sites to identify
companies that sell CFLs in the United
States. DOE screened out companies
that do not offer products covered by
this rulemaking, do not meet the
definition of a ‘‘small business,’’ or are
completely foreign owned and operated.
DOE determined that there are no small
businesses that maintain domestic
production facilities for CFLs.
Based on the criteria outlined earlier
and the reasons discussed above, DOE
certifies that the test procedures
adopted in this final rule would not
have a significant economic impact on
a substantial number of small entities,
and the preparation of a final regulatory
flexibility analysis is not warranted.
DOE has submitted a certification and
supporting statement of factual basis to
the Chief Counsel for Advocacy of the
SBA for review under 5 U.S.C. 605(b).
E:\FR\FM\29AUR4.SGM
29AUR4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of CFLs must certify to
DOE that their products comply with
any applicable energy conservation
standards. To certify compliance,
manufacturers must first obtain test data
for their products according to the DOE
test procedures, including any
amendments adopted for those test
procedures. DOE has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including CFLs.
See generally 10 CFR part 429, subpart
B. The collection-of-information
requirement for the certification and
recordkeeping is subject to review and
approval by OMB under the Paperwork
Reduction Act (PRA). This requirement
has been approved by OMB under OMB
control number 1910–1400. Public
reporting burden for the certification is
estimated to average 30 hours per
response including the time for
reviewing instructions, searching
existing data sources, gathering and
maintaining the data needed, and
completing and reviewing the collection
of information.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
current valid OMB Control Number.
mstockstill on DSK3G9T082PROD with RULES4
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE is approving
test procedure amendments that it
expects will be used to develop and
implement future energy conservation
standards for CFLs. DOE has determined
that this rule falls into a class of actions
that are categorically excluded from
review under the National
Environmental Policy Act of 1969 (42
U.S.C. 4321 et seq.) and DOE’s
implementing regulations at 10 CFR part
1021. Specifically, this rule amends an
existing rule without affecting the
amount, quality or distribution of
energy usage, and, therefore, will not
result in any environmental impacts.
Thus, this rulemaking is covered by
Categorical Exclusion A5 under 10 CFR
part 1021, subpart D, which applies to
any rulemaking that interprets or
amends an existing rule without
changing the environmental effect of
that rule. Accordingly, neither an
environmental assessment nor an
environmental impact statement is
required.
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999), imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have Federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have Federalism implications. On
March 14, 2000, DOE published a
statement of policy describing the
intergovernmental consultation process
it will follow in the development of
such regulations. 65 FR 13735. DOE
examined this final rule and determined
that it will not have a substantial direct
effect on the States, on the relationship
between the national government and
the States, or on the distribution of
power and responsibilities among the
various levels of government. EPCA
governs and prescribes Federal
preemption of State regulations as to
energy conservation for the products
that are the subject of this final rule.
States can petition DOE for exemption
from such preemption to the extent, and
based on criteria, set forth in EPCA. (42
U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) Clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
59413
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, this final rule
meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
regulatory action resulting in a rule that
may cause the expenditure by State,
local, and Tribal governments, in the
aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR
12820; also available at https://
energy.gov/gc/office-general-counsel.
DOE examined this final rule according
to UMRA and its statement of policy
and determined that the rule contains
neither an intergovernmental mandate
nor a mandate that may result in the
expenditure of $100 million or more in
any year, so these requirements do not
apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Public Law 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
E:\FR\FM\29AUR4.SGM
29AUR4
59414
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
that may affect family well-being. This
final rule will not have any impact on
the autonomy or integrity of the family
as an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights’’ 53 FR 8859
(March 18, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
mstockstill on DSK3G9T082PROD with RULES4
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). DOE has reviewed
this final rule under the OMB and DOE
guidelines and has concluded that it is
consistent with applicable policies in
those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB, a
Statement of Energy Effects for any
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgated or is
expected to lead to promulgation of a
final rule, and that (1) is a significant
regulatory action under Executive Order
12866, or any successor order; and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy; or (3) is designated by the
Administrator of OIRA as a significant
energy action. For any significant energy
action, the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use if the
regulation is implemented, and of
reasonable alternatives to the action and
their expected benefits on energy
supply, distribution, and use.
This regulatory action is not a
significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Public Law
95–91; 42 U.S.C. 7101), DOE must
comply with section 32 of the Federal
Energy Administration Act of 1974, as
amended by the Federal Energy
Administration Authorization Act of
1977. (15 U.S.C. 788; FEAA) Section 32
essentially provides in relevant part
that, where a proposed rule authorizes
or requires use of commercial standards,
the notice of proposed rulemaking must
inform the public of the use and
background of such standards. In
addition, section 32(c) requires DOE to
consult with the Attorney General and
the Chairman of the Federal Trade
Commission (FTC) concerning the
impact of the commercial or industry
standards on competition.
This final rule incorporates by
reference the testing methods and
modifications to the test procedures that
are contained in the following
commercial standards:
(1) ANSI C78.901–2014, ‘‘American
National Standard for Electric Lamps—
Single-Based Fluorescent Lamps—
Dimensional and Electrical Characteristics,’’
2014;
(2) CIE 13.3–1995, ‘‘Technical Report:
Method of Measuring and Specifying Colour
Rendering Properties of Light Sources,’’ 1995;
(3) CIE 15:2004, ‘‘Technical Report:
Colorimetry, 3rd edition,’’ 2004;
(4) IES LM–54–12, ‘‘IES Guide to Lamp
Seasoning,’’ 2012;
(5) IES LM–65–14, ‘‘IES Approved Method
for Life Testing of Single-Based Fluorescent
Lamps,’’ 2014;
(6) IES LM–66–14, ‘‘IES Approved Method
for the Electrical and Photometric
Measurements of Single-Based Fluorescent
Lamps,’’ 2014;
(7) IESNA LM–78–07, :IESNA Approved
Method for Total Luminous Flux
Measurement of Lamp Using an Integrated
Sphere Photometer,’’ 2007; and
(8) IEC Standard 62301 (Edition 2.0, 2011–
01), ‘‘Household electrical appliances—
Measurement of standby power,’’ 2011.
Although these test procedures are
not exclusively based on these industry
testing standards, some components of
the DOE test procedure adopt
definitions, test parameters, and
measurement techniques from them
without amendment. The Department
has evaluated these industry testing
standards and is unable to conclude
whether they fully comply with the
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
requirements of section 32(b) of the
FEAA (i.e., that they were developed in
a manner that fully provides for public
participation, comment, and review).
DOE has consulted with both the
Attorney General and the Chairman of
the FTC about the impact on
competition of using the methods
contained in these standards and has
received no comments objecting to their
use.
M. Description of Materials
Incorporated by Reference
DOE incorporates by reference the test
standard published by ANSI, titled
‘‘American National Standard for
Electric Lamps—Single-Based
Fluorescent Lamps—Dimensional and
Electrical Characteristics,’’ ANSI
C78.901–2014. ANSI C78.901–2014 is
an industry accepted test standard that
specifies physical and electrical
characteristics of non-integrated CFLs
and is applicable to products sold in
North America. It is used to identify the
appropriate reference ballast
specifications for CFL as described in
this final rule. ANSI C78.901–2014 is
readily available on ANSI’s Web site at
https://webstore.ansi.org/.
DOE incorporates by reference the test
standard published by IES, titled ‘‘IES
Guide to Lamp Seasoning,’’ IES LM–54–
12. IES LM–54–12 is an industry
accepted test standard that specifies a
method for seasoning CFLs prior to
testing and is applicable to products
sold in North America. The test
procedures adopted in this final rule
reference various sections of IES LM–
54–12 that address seasoning of CFLs
prior to testing. IES LM–54–12 is readily
available on IES’s Web site at
www.ies.org/store.
DOE also incorporates by reference
the test standard published by IES,
titled ‘‘IES Approved Method for Life
Testing of Single-Based Fluorescent
Lamps,’’ IES LM–65–14. IES LM–65–14
is an industry accepted test standard
that specifies a method for measuring
the time to failure of CFLs and is
applicable to products sold in North
America. The test procedures adopted
in this final rule reference various
sections of IES LM–65–14 that address
test conditions and procedures for
measuring time to failure and rapid
cycle stress testing of CFLs. IES LM–65–
14 is readily available on IES’s Web site
at www.ies.org/store.
DOE also incorporates by reference
specific sections of the test standard
published by IES, titled ‘‘IES Approved
Method: Electrical and Photometric
Measurements of Single-Based
Fluorescent Lamps,’’ IES LM–66–14. IES
LM–66–14 is an industry accepted test
E:\FR\FM\29AUR4.SGM
29AUR4
mstockstill on DSK3G9T082PROD with RULES4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
standard that specifies a method for
measuring electrical and photometric
characteristics of CFLs and is applicable
to products sold in North America. The
test procedures adopted in this final
rule reference various sections of IES
LM–66–14 that address test conditions
and procedures for taking electrical and
photometric measurements of CFLs. IES
LM–66–14 is readily available on IES’s
Web site at www.ies.org/store.
DOE also incorporates by reference
the test standard published by IES,
titled ‘‘IESNA Approved Method for
Total Luminous Flux Measurement of
Lamps Using an Integrating Sphere
Photometer,’’ IESNA LM–78–07. IESNA
LM–78–07 is an industry accepted test
standard that specifies a method for
measuring lumen output in an
integrated sphere and is applicable to
products sold in North America. The
test procedures adopted in this final
rule reference sections of IESNA LM–
78–07 that address measurements of
lumen output. IESNA LM–78–07 is
readily available on IES’s Web site at
www.ies.org/store.
DOE also incorporates by reference
certain sections of the test standard
published by IEC, titled ‘‘Household
electrical appliances—Measurement of
standby power,’’ IEC Standard 62301
(Edition 2.0). IEC Standard 62301
(Edition 2.0) is an industry accepted test
standard that describes measurements of
electrical power consumption in
standby mode, off mode, and network
mode. The test procedures adopted in
this final rule reference sections of IEC
Standard 62301 (Edition 2.0) for testing
standby mode power consumption of
CFLs. IEC Standard 62301 (Edition 2.0)
is readily available on ANSI’s Web site
at https://webstore.iec.ch/home.
DOE also incorporates by reference
the test standard published by CIE,
titled ‘‘Technical Report: Method of
Measuring and Specifying Colour
Rendering Properties of Light Sources,’’
CIE 13.3–1995. CIE 13.3–1995 is an
industry accepted test standard that
specifies method of measuring and
specifying color rendering properties of
light sources based on resultant color
shifts of test objects. The test procedures
adopted in this final rule reference
sections of CIE 13.3–1995 for testing CRI
of CFLs. CIE 13.3–1995 is readily
available on CIE’s Web site at https://
www.techstreet.com/cie/.
DOE incorporates by reference the test
standard published by CIE, titled
‘‘Technical Report: Colorimetry,’’ CIE
15:2004. CIE 15:2004 is an industry
accepted test standard that summarizes
colorimetric data. The test procedures
adopted in this final rule reference
sections of CIE 15:2004 for testing CCT
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
of CFLs. CIE 15:2004 is readily available
on CIE’s Web site at https://
www.techstreet.com/cie/.
DOE removes previously incorporated
reference to ‘‘ENERGY STAR Program
Requirements for [Compact Fluorescent
Lamps] CFLs, approved August 9,
2001.’’ These provided specifications
including test procedures for ENERGY
STAR qualified CFLs. The test
procedures adopted in this final rule no
longer reference ‘‘ENERGY STAR
Program Requirements for [Compact
Fluorescent Lamps] CFLs, approved
August 9, 2001.’’
N. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of this rule before its effective date. The
report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
List of Subjects
10 CFR Part 429
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Reporting and recordkeeping
requirements.
10 CFR Part 430
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Small
businesses.
Issued in Washington, DC, on August 11,
2016.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
For the reasons stated in the
preamble, DOE amends parts 429 and
430 of Chapter II of Title 10, Code of
Federal Regulations as set forth below:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
2. Section 429.12 is amended by
revising paragraph (f) to read as follows:
■
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
59415
§ 429.12 General requirements applicable
to certification reports.
*
*
*
*
*
(f) Discontinued model filing. When
production of a basic model has ceased
and it is no longer being sold or offered
for sale by the manufacturer or private
labeler, the manufacturer must report
this discontinued status to DOE as part
of the next annual certification report
following such cessation. For each basic
model, the report must include the
information specified in paragraphs
(b)(1) through (7) of this section, except
that for integrated light-emitting diode
lamps and for compact fluorescent
lamps, the manufacturer must submit a
full certification report, including all of
the information required by paragraph
(b) of this section and the productspecific information required by
§ 429.56(b)(2) or § 429.35(b)(2),
respectively.
*
*
*
*
*
■ 3. Section 429.35 is revised to read as
follows:
§ 429.35
Compact fluorescent lamps.
(a) Determination of Represented
Value. Manufacturers must determine
represented values, which include the
certified ratings, for each basic model of
compact fluorescent lamp by testing, in
conjunction with the following
sampling provisions:
(1) Units to be tested. (i) The
requirements of § 429.11(a) are
applicable except that the sample must
be comprised of production units; and
(ii)(A) For each basic model of
integrated compact fluorescent lamp,
the minimum number of units tested
shall be no less than 10 units when
testing for the initial lumen output,
input power, initial lamp efficacy,
lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of
lifetime, lifetime, CCT, CRI, power
factor, and standby mode power. If more
than 10 units are tested as part of the
sample, the total number of units must
be a multiple of 2. The same sample of
units must be used as the basis for
representations for initial lumen output,
input power, initial lamp efficacy,
lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of
lifetime, lifetime, CCT, CRI, power
factor, and standby mode power. No less
than three units from the same sample
of units must be used when testing for
the start time. Exactly six unique units
(i.e., units that have not previously been
tested under this paragraph (a)(1)(ii) but
are representative of the same basic
model tested under this paragraph
(a)(1)(ii)) must be used for rapid cycle
stress testing.
E:\FR\FM\29AUR4.SGM
29AUR4
Where:
x is the sample mean of the characteristic
value;
s is the sample standard deviation;
n is the number of units in the sample, and
t0.975 is the t statistic for a 97.5% one-tailed
Ò
confidence interval with n-1 degrees of
freedom (from appendix A of this
subpart).
mstockstill on DSK3G9T082PROD with RULES4
(B) Represented values of input
power, standby mode power, start time
or other measure of energy consumption
of a basic model for which consumers
would favor lower values must be
greater than or equal to the higher of:
(1) The mean of the sample,
Where:
¯
x is the sample mean,
n is the number of units in the sample, and
Ò
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
Where:
¯
x is the sample mean of the characteristic
value;
s is the sample standard deviation;
Ò
n is the number of units in the sample, and
Ò
t0.975 is the t statistic for a 97.5% one-tailed
Ò
confidence interval with n-1 degrees of
freedom (from appendix A of this
subpart).
(C) The represented value of CCT
must be equal to the mean of the
sample,
Where:
¯
x is the sample mean,
n is the number of units in the sample, and
Ò
xi is the ith unit.
Ò
(D) The represented value of lifetime
must be equal to or less than the median
time to failure of the sample (calculated
as the arithmetic mean of the time to
failure of the two middle sample units
when the numbers are sorted in value
order).
(E) The represented value of the
results of rapid cycle stress testing must
be
(1) Expressed in the number of
surviving units and
(2) Based on a lifetime value that is
equal to or greater than the represented
value of lifetime.
(2) The represented value of life (in
years) of a compact fluorescent lamp
must be calculated by dividing the
represented lifetime of a compact
fluorescent lamp as determined in (a)(1)
of this section by the estimated annual
operating hours as specified in 16 CFR
305.15(b)(3)(iii).
(3) The represented value of the
estimated annual energy cost for a
compact fluorescent lamp, expressed in
dollars per year, must be the product of
the input power in kilowatts, an
electricity cost rate as specified in 16
CFR 305.15(b)(1)(ii), and an estimated
average annual use as specified in 16
CFR 305.15(b)(1)(ii).
(4) For compliance with standards
specified in § 430.32(u) as it appeared in
10 CFR parts 200–499 edition revised as
of January 1, 2016, initial lamp efficacy
may include a 3 percent tolerance added
to the value determined in accordance
with paragraph (a)(1)(iii)(A) of this
section.
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
(5) The represented value of lumen
maintenance at 40 percent of lifetime
must be based on a lifetime value that
is equal to or greater than the
represented value of lifetime.
(6) Estimated values may be used for
representations when initially testing a
new basic model or when new/
additional testing is required.
(b) Certification reports. (1) The
requirements of § 429.12 are applicable
to compact fluorescent lamps; and
(2) Values reported in certification
reports are represented values. Pursuant
to § 429.12(b)(13), a certification report
shall include the following public
product-specific information:
(i) For each basic model of medium
base CFL when certifying compliance to
the standards in § 430.32(u) as it
appeared in 10 CFR parts 200–499
edition revised as of January 1, 2016, the
testing laboratory’s ILAC accreditation
body’s identification number or other
approved identification assigned by the
ILAC accreditation body, the date of
first manufacture, the seasoning time in
hours (h), the initial lumen output in
lumens (lm), the input power in watts
(W), the initial lamp efficacy in lumens
per watt (lm/W), the number of sample
units replaced during the seasoning
period within each unique sample set
used in determining the represented
value, the lumen maintenance at 40
percent of lifetime in percent (%) (and
whether value is estimated), the lifetime
in hours (h) (and whether value is
estimated), life in years (and whether
value is estimated), the lumen
maintenance at 1,000 hours in percent
(%), and the results of rapid cycle stress
testing in number of units passed. or the
initial certification of new basic models
or any subsequent certification based on
new testing, estimates of lifetime, life,
lumen maintenance at 40 percent of
lifetime, and rapid cycle stress test
surviving units may be reported (if
indicated in the certification report)
until testing is complete. When
reporting estimated values, the
certification report must specifically
describe the prediction method, which
must be generally representative of the
methods specified in appendix W.
Manufacturers are required to maintain
records in accordance with § 429.71 of
the development of all estimated values
and any associated initial test data.
(ii) For each basic model of integrated
CFL when certifying compliance with
general service lamp energy
conservation standards, the testing
laboratory’s ILAC accreditation body’s
identification number or other
identification assigned by the ILAC
accreditation body, the date of first
manufacture, a statement that the
E:\FR\FM\29AUR4.SGM
29AUR4
ER29AU16.017
Or,
(2) The lower 97.5-percent confidence
limit (LCL) of the true mean divided by
0.95,
Or,
(2) The upper 97.5-percent confidence
limit (UCL) of the true mean divided by
1.05,
ER29AU16.016
Where:
x is the sample mean,
n is the number of units in the sample, and
xi is the ith unit;
xi is the ith unit;
Ò
ER29AU16.015
(B) For each basic model of nonintegrated compact fluorescent lamp,
the minimum number of units tested
shall be no less than 10 units when
testing for the initial lumen output,
input power, initial lamp efficacy,
lumen maintenance at 40 percent of
lifetime, lifetime, CCT, and CRI. If more
than 10 units are tested as part of the
sample, the total number of units must
be a multiple of 2. The same sample of
units must be used as the basis for
representations for initial lumen output,
input power, initial lamp efficacy,
lumen maintenance at 40 percent of
lifetime, lifetime, CCT, and CRI.
(iii) For each basic model, a sample of
sufficient size shall be randomly
selected and tested to ensure that:
(A) Represented values of initial
lumen output, initial lamp efficacy,
lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of
lifetime, CRI, power factor, or other
measure of energy consumption of a
basic model for which consumers would
favor higher values must be less than or
equal to the lower of:
(1) The mean of the sample,
ER29AU16.018
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
ER29AU16.014
59416
mstockstill on DSK3G9T082PROD with RULES4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
compact fluorescent lamp is integrated,
the seasoning time in hours (h), the
initial lumen output in lumens (lm), the
input power in watts (W), the initial
lamp efficacy in lumens per watt (lm/
W), the CCT in kelvin (K), CRI, the
lumen maintenance at 1,000 hours in
percent (%), the lumen maintenance at
40 percent of lifetime in percent (%)
(and whether value is estimated), start
time in milliseconds, power factor,
standby mode energy consumption in
watts (W), the results of rapid cycle
stress testing in number of units passed,
the lifetime in hours (h) (and whether
value is estimated), life in years (and
whether value is estimated), and the
number of sample units replaced during
the seasoning period within the sample
set used in determining the represented
value. Estimates of lifetime, life, lumen
maintenance at 40 percent of lifetime,
and rapid cycle stress test surviving
units may be reported (if indicated in
the certification report) until testing is
complete. When reporting estimated
values, the certification report must
specifically describe the prediction
method, which must be generally
representative of the methods specified
in appendix W. Manufacturers are
required to maintain records in
accordance with § 429.71 of the
development of all estimated values and
any associated initial test data.
(iii) For each basic model of nonintegrated CFL when certifying
compliance with general service lamp
energy conservation standards, the
testing laboratory’s ILAC accreditation
body’s identification number or other
identification assigned by the ILAC
accreditation body, the date of first
manufacture, a statement that the
compact fluorescent lamp is nonintegrated, the initial lumen output in
lumens (lm), the input power in watts
(W), the initial lamp efficacy in lumens
per watt (lm/W), the CCT in kelvin (K),
CRI, the lumen maintenance at 40
percent of lifetime in percent (%) (and
whether value is estimated), the lifetime
in hours (h) (and whether value is
estimated), and the number of sample
units replaced during the seasoning
period within each unique sample set
used in determining the represented
value. Estimates of lifetime and lumen
maintenance at 40 percent of lifetime
may be reported (if indicated in the
certification report) until testing is
complete. When reporting estimated
values, the certification report must
specifically describe the prediction
method, which must be generally
representative of the methods specified
in appendix W. Manufacturers are
required to maintain records in
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
accordance with § 429.71 of the
development of all estimated values and
any associated initial test data.
(c) Rounding requirements. For
represented values,
(1) Round input power to the nearest
tenth of a watt.
(2) Round lumen output to three
significant digits.
(3) Round initial lamp efficacy to the
nearest tenth of a lumen per watt.
(4) Round lumen maintenance at
1,000 hours to the nearest tenth of a
percent.
(5) Round lumen maintenance at 40
percent of lifetime to the nearest tenth
of a percent.
(6) Round CRI to the nearest whole
number.
(7) Round power factor to the nearest
hundredths place.
(8) Round lifetime to the nearest
whole hour.
(9) Round CCT to the nearest 100
kelvin (K).
(10) Round standby mode power to
the nearest tenth of a watt; and
(11) Round start time to the nearest
whole millisecond.
PART 430—ENERGY CONSERVATION
PROGRAM FOR CONSUMER
PRODUCTS
4. The authority citation for part 430
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6309; 28 U.S.C.
2461 note.
5. Section 430.2 is amended by:
a. Adding in alphabetical order a
definition for ‘‘compact fluorescent
lamp’’;
■ b. Revising the definition of
‘‘correlated color temperature’’; and
■ c. Adding in alphabetical order
adefinition for ‘‘lifetime of a compact
fluorescent lamp’’.
The additions and revision read as
follows:
■
■
§ 430.2
Definitions.
*
*
*
*
*
Compact fluorescent lamp (CFL)
means an integrated or non-integrated
single-base, low-pressure mercury,
electric-discharge source in which a
fluorescing coating transforms some of
the ultraviolet energy generated by the
mercury discharge into light; the term
does not include circline or U-shaped
lamps.
*
*
*
*
*
Correlated color temperature (CCT)
means the absolute temperature of a
blackbody whose chromaticity most
nearly resembles that of the light source.
*
*
*
*
*
Lifetime of a compact fluorescent
lamp means the length of operating time
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
59417
between first use and failure of 50
percent of the sample units (as specified
in § 429.35(a)(1) of this chapter),
determined in accordance with the test
procedures described in section 3.3 of
appendix W to subpart B of this part.
*
*
*
*
*
■ 6. Section 430.3 is amended by:
■ a. Redesignating paragraphs (e)(8)
through (19) as paragraphs (e)(9)
through (20), respectively, and adding
new paragraph (e)(8);
■ b. Removing ‘‘appendix R’’ in
paragraphs (l)(1) and (2) and adding in
its place ‘‘appendices R and W’’;
■ c. Redesignating paragraph (o)(9) as
(o)(13), paragraph (o)(10) as (o)(14),
paragraph (o)(11) as (o)(15), and
paragraph (o)(12) as (o)(16), paragraph
(o)(8) as (o)(10), and paragraph (o)(7) as
(o)(8),;
■ d. Adding new paragraphs (o)(7), (9),
(11), and (12);
■ e. Adding paragraph (p)(7); and
■ f. Removing paragraph (v).
The additions read as follows:
§ 430.3 Materials incorporated by
reference.
*
*
*
*
*
(e) * * *
(8) ANSI C78.901–2014, American
National Standard for Electric Lamps—
Single-Based Fluorescent Lamps—
Dimensional and Electrical
Characteristics, ANSI approved July 2,
2014; IBR approved for appendix W to
subpart B.
*
*
*
*
*
(o) * * *
(7) IES LM–54–12, IES Guide to Lamp
Seasoning, approved October 22, 2012;
IBR approved for appendix W to subpart
B, as follows:
(i) Section 4—Physical/Environmental
Test Conditions;
(ii) Section 5—Electrical Test
Conditions;
(iii) Section 6—Test Procedure
Requirements: Section 6.1—Test
Preparation; and
(iv) Section 6—Test Procedure
Requirements, Section 6.2—Seasoning
Test Procedures: Section 6.2.2.1—
Discharge Lamps: Discharge Lamps
except T5 fluorescent.
*
*
*
*
*
(9) IES LM–65–14, IES Approved
Method for Life Testing of Single-Based
Fluorescent Lamps, approved December
30, 2014; IBR approved for appendix W
to subpart B, as follows:
(i) Section 4.0—Ambient and Physical
Conditions;
(ii) Section 5.0—Electrical Conditions;
and
(iii) Section 6.0—Lamp Test
Procedures
*
*
*
*
*
E:\FR\FM\29AUR4.SGM
29AUR4
59418
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
(11) IES LM–66–14, (‘‘IES LM–66’’),
IES Approved Method for the Electrical
and Photometric Measurements of
Single-Based Fluorescent Lamps,
approved December 30, 2014; IBR
approved for appendix W to subpart B,
as follows:
(i) Section 4.0—Ambient and Physical
Conditions;
(ii) Section 5.0—Power Source
Characteristics; and
(iii) Section 6.0—Testing Procedures
Requirements.
(12) IESNA LM–78–07, IESNA
Approved Method for Total Luminous
Flux Measurement of Lamps Using an
Integrating Sphere Photometer,
approved January 28, 2007; IBR
approved for appendix W to subpart B.
*
*
*
*
*
(p) * * *
(7) IEC 62301, (‘‘IEC 62301–W’’),
Household electrical appliances—
Measurement of standby power,
(Edition 2.0, 2011–01), Section 5—
Measurements, IBR approved for
appendix W to subpart B.
*
*
*
*
*
■ 7. Section 430.23 is amended by
revising paragraph (y) to read as follows:
§ 430.23 Test procedures for the
measurement of energy and water
consumption.
*
*
*
*
*
(y) Compact fluorescent lamps. (1)
Measure initial lumen output, input
power, initial lamp efficacy, lumen
maintenance at 1,000 hours, lumen
maintenance at 40 percent of lifetime of
a compact fluorescent lamp (as defined
in 10 CFR 430.2), color rendering index
(CRI), correlated color temperature
(CCT), power factor, start time, standby
mode energy consumption, and time to
failure in accordance with appendix W
of this subpart. Express time to failure
in hours.
(2) Conduct the rapid cycle stress test
in accordance with section 3.3 of
appendix W of this subpart.
*
*
*
*
*
■ 8. Section 430.25 is revised to read as
follows:
mstockstill on DSK3G9T082PROD with RULES4
§ 430.25 Laboratory Accreditation
Program.
The testing for general service
fluorescent lamps, general service
incandescent lamps (with the exception
of lifetime testing), incandescent
reflector lamps, compact fluorescent
lamps, fluorescent lamp ballasts, and
integrated light-emitting diode lamps
must be conducted by test laboratories
accredited by an Accreditation Body
that is a signatory member to the
International Laboratory Accreditation
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
Cooperation (ILAC) Mutual Recognition
Arrangement (MRA). A manufacturer’s
or importer’s own laboratory, if
accredited, may conduct the applicable
testing.
■ 9. Appendix W to subpart B of part
430 is revised to read as follows:
Appendix W to Subpart B of Part 430—
Uniform Test Method for Measuring the
Energy Consumption of Compact
Fluorescent Lamps
Note: Before February 27, 2017, any
representations, including certifications of
compliance, made with respect to the energy
use or efficiency of medium base compact
fluorescent lamps must be made in
accordance with the results of testing
pursuant either to this appendix, or to the
applicable test requirements set forth in 10
CFR parts 429 and 430 as they appeared in
the 10 CFR parts 200 to 499 annual edition
revised as of January 1, 2016.
On or after February 27, 2017, any
representations, including certifications of
compliance (if required), made with respect
to the energy use or efficiency of CFLs must
be made in accordance with the results of
testing pursuant to this appendix.
1. Scope:
1.1. Integrated compact fluorescent lamps.
1.1.1. This appendix specifies the test
methods required to measure the initial lamp
efficacy, lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of lifetime,
time to failure, power factor, correlated color
temperature (CCT), color rendering index
(CRI), and start time of an integrated compact
fluorescent lamp.
1.1.2. This appendix describes how to
conduct rapid cycle stress testing for
integrated compact fluorescent lamps.
1.1.3. This appendix specifies test methods
required to measure standby mode energy
consumption applicable to integrated CFLs
capable of operation in standby mode (as
defined in § 430.2), such as those that can be
controlled wirelessly.
1.2. Non-integrated compact fluorescent
lamps.
1.2.1. This appendix specifies the test
methods required to measure the initial lamp
efficacy, lumen maintenance at 40 percent of
lifetime, time to failure, CCT, and CRI for
non-integrated compact fluorescent lamps.
2. Definitions:
2.1. Ballasted adapter means a ballast that
is not permanently attached to a compact
fluorescent lamp, has no consumerreplaceable components, and serves as an
adapter by incorporating both a lamp socket
and a lamp base.
2.2. Hybrid compact fluorescent lamp
means a compact fluorescent lamp that
incorporates one or more supplemental light
sources of different technology.
2.3. Initial lamp efficacy means the lamp
efficacy (as defined in § 430.2) at the end of
the seasoning period, as calculated pursuant
to section 3.2.2.9 of this appendix.
2.4. Integrated compact fluorescent lamp
means an integrally ballasted compact
fluorescent lamp that contains all
components necessary for the starting and
stable operation of the lamp, contains an
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
ANSI standard base, does not include any
replaceable or interchangeable parts, and is
capable of being connected directly to a
branch circuit through a corresponding ANSI
standard lamp-holder (socket).
2.5. Labeled wattage means the highest
wattage marked on the lamp and/or lamp
packaging.
2.6. Lumen maintenance means the lumen
output measured at a given time in the life
of the lamp and expressed as a percentage of
the measured initial lumen output.
2.7. Measured initial input power means
the input power to the lamp, measured at the
end of the lamp seasoning period, and
expressed in watts (W).
2.8. Measured initial lumen output means
the lumen output of the lamp measured at
the end of the lamp seasoning period,
expressed in lumens (lm).
2.9. Non-integrated compact fluorescent
lamp means a compact fluorescent lamp that
is not an integrated compact fluorescent
lamp.
2.10. Percent variability means the result of
dividing the difference between the
maximum and minimum values by the
average value for a contiguous set of separate
time-averaged light output values spanning
the specified time period. For a waveform of
measured light output values, the timeaveraged light output is computed over one
full cycle of sinusoidal input voltage, as a
moving average where the measurement
interval is incremented by one sample for
each successive measurement value.
2.11. Power factor means the measured
input power (watts) divided by the product
of the measured RMS input voltage (volts)
and the measured RMS input current (amps).
2.12. Rated input voltage means the
voltage(s) marked on the lamp as the
intended operating voltage or, if not marked
on the lamp, 120 V.
2.13. Start plateau means the first 100
millisecond period of operation during
which the percent variability does not exceed
5 percent.
2.14. Start time means the time, measured
in milliseconds, between the application of
power to the compact fluorescent lamp and
the beginning of the start plateau.
2.15. Time to failure means the time
elapsed between first use and the point at
which the compact fluorescent lamp (for a
hybrid CFL, the primary light source) ceases
to produce measureable lumen output.
3. Active Mode Test Procedures
3.1. General Instructions.
3.1.1. In cases where there is a conflict, the
language of the test procedure in this
appendix takes precedence over any
materials incorporated by reference.
3.1.2. Maintain lamp operating orientation
throughout seasoning and testing, including
storage and handling between tests.
3.1.3. Season CFLs prior to photometric
and electrical testing in accordance with
sections 4, 5, 6.1, and 6.2.2.1 of IES LM–54–
12 (incorporated by reference, see § 430.3).
Season the CFL for a minimum of 100 hours
in accordance with section 6.2.2.1 of IES
LM–54–12. During the 100 hour seasoning
period, cycle the CFL (operate the lamps for
180 minutes, 20 minutes off) as specified in
section 6.4 of IES LM–65–14 (incorporated by
reference; see § 430.3).
E:\FR\FM\29AUR4.SGM
29AUR4
mstockstill on DSK3G9T082PROD with RULES4
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
3.1.3.1. Unit operating time during
seasoning may be counted toward time to
failure, lumen maintenance at 40 percent of
lifetime of a compact fluorescent lamp (as
defined in § 430.2), and lumen maintenance
at 1,000 hours if the required operating cycle
and test conditions for time to failure testing
per section 3.3.1 of this appendix are
satisfied.
3.1.3.2. If a lamp breaks, becomes
defective, fails to stabilize, exhibits abnormal
behavior (such as swirling), or stops
producing light prior to the end of the
seasoning period, the lamp must be replaced
with a new unit. If a lamp exhibits one of the
conditions listed in the previous sentence
after the seasoning period, the lamp’s
measurements must be included in the
sample. Record number of lamps replaced, if
any.
3.1.4. Conduct all testing with the lamp
operating at labeled wattage. This
requirement applies to all CFLs, including
those that are dimmable or multi-level.
3.1.5. Operate the CFL at the rated input
voltage throughout testing. For a CFL with
multiple rated input voltages including 120
volts, operate the CFL at 120 volts. If a CFL
with multiple rated input voltages is not
rated for 120 volts, operate the CFL at the
highest rated input voltage.
3.1.6. Test CFLs packaged with ballasted
adapters or designed exclusively for use with
ballasted adapters as non-integrated CFLs,
with no ballasted adapter in the circuit.
3.1.7. Conduct all testing of hybrid CFLs
with all supplemental light sources in the
lamp turned off, if possible. Before taking
measurements, verify that the lamp has
stabilized in the operating mode that
corresponds to its primary light source.
3.2. Test Procedures for Determining Initial
Lamp Efficacy, Lumen Maintenance, CCT,
CRI, and Power Factor.
Determine initial lamp efficacy, lumen
maintenance at 40 percent of lifetime of a
compact fluorescent lamp (as defined in in
§ 430.2), CCT, and CRI for integrated and
non-integrated CFLs. Determine lumen
maintenance at 1,000 hours and power factor
for integrated CFLs only.
3.2.1. Test Conditions and Setup
3.2.1.1. Test half of the units in the sample
in the base up position, and half of the units
in the base down position; if the position is
restricted by the manufacturer, test the units
in the manufacturer-specified position.
3.2.1.2. Establish ambient conditions,
power supply, auxiliary equipment, circuit
setup, lamp connections, and
instrumentation in accordance with the
specifications in sections (and corresponding
subsections) 4.0, 5.0 and 6.0 of IES LM–66–
14 (incorporated by reference; see § 430.3),
except maintain ambient temperature at 25 ±
1 °C (77 ± 1.8 °F).
3.2.1.3. Non-integrated CFLs must adhere
to the reference ballast requirements in
section 5.2 of IES LM–66 (incorporated by
reference; see § 430.3).
3.2.1.3.1. Test non-integrated lamps rated
for operation on and having reference ballast
characteristics for either low frequency or
high frequency circuits (e.g., many preheat
start lamps) at low frequency.
3.2.1.3.2. For low frequency operation, test
non-integrated lamps rated for operation on
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
either preheat start (starter) or rapid start (no
starter) circuits on preheat.
3.2.1.3.3. Operate non-integrated CFLs not
listed in ANSI C78.901–2014 (incorporated
by reference; see § 430.3) using the following
reference ballast settings:
3.2.1.3.3.1. Operate 25–28 W, T5 twin
2G11-based lamps that are lower wattage
replacements of 40 W, T5 twin 2G11-based
lamps using the following reference ballast
settings: 60 Hz, 400 volts, 0.270 amps, and
1240 ohms.
3.2.1.3.3.2. Operate 14–15 W, T4 quad
G24q-2-based lamps that are lower wattage
replacements of 18 W, T4 quad G24q-2-based
lamps using the following reference ballast
settings: 60 Hz, 220 volts, 0.220 amps, and
815 ohms.
3.2.1.3.3.3. Operate 21 W, T4 quad G24q3-based lamps that are lower wattage
replacements of 26 W, T4 quad G24q-3-based
lamps using the following reference ballast
settings: 60 Hz, 220 volts, 0.315 amps, and
546 ohms.
3.2.1.3.3.4. Operate 21 W, T4 quad G24d3-based lamps that are lower wattage
replacements of 26 W, T4 quad G24d-3-based
lamps using the following reference ballast
settings: 60 Hz, 220 volts, 0.315 amps, and
546 ohms.
3.2.1.3.3.5. Operate 21 W, T4 multi (6)
GX24q-3-based lamps that are lower wattage
replacements of 26 W, T4 multi (6) GX24q3-based lamps using the following reference
ballast settings: 60 Hz, 220 volts, 0.315 amps,
and 546 ohms.
3.2.1.3.3.6. Operate 27–28 W, T4 multi (6)
GX24q-3-based lamps that are lower wattage
replacements of 32 W, T4 multi (6) GX24q3-based lamps using the following reference
ballast settings: 20–26 kHz, 200 volts, 0.320
amps, and 315 ohms.
3.2.1.3.3.7. Operate 33–38 W, T4 multi (6)
GX24q-4-based lamps that are lower wattage
replacements of 42 W, T4 multi (6) GX24q4-based lamps using the following reference
ballast settings: 20–26 kHz, 270 volts, 0.320
amps, and 420 ohms.
3.2.1.3.3.8. Operate 10 W, T4 square
GR10q-4-based lamps using the following
reference ballast settings: 60 Hz, 236 volts,
0.165 amps, and 1,200 ohms.
3.2.1.3.3.9. Operate 16 W, T4 square
GR10q-4-based lamps using the following
reference ballast settings: 60 Hz, 220 volts,
0.195 amps, and 878 ohms.
3.2.1.3.3.10. Operate 21 W, T4 square
GR10q-4-based lamps using the following
reference ballast settings: 60 Hz, 220 volts,
0.260 amps, and 684 ohms.
3.2.1.3.3.11. Operate 28 W, T6 square
GR10q-4-based lamps using the following
reference ballast settings: 60 Hz, 236 volts,
0.320 amps, and 578 ohms.
3.2.1.3.3.12. Operate 38 W, T6 square
GR10q-4-based lamps using the following
reference ballast settings: 60 Hz, 236 volts,
0.430 amps, and 439 ohms.
3.2.1.3.3.13. Operate 55 W, T6 square
GRY10q-3-based lamps using the following
reference ballast settings: 60 Hz, 236 volts,
0.430 amps, and 439 ohms.
3.2.1.3.3.14. For all other lamp designs not
listed in ANSI C78.901–2014 (incorporated
by reference; see § 430.3) or section 3.2.1.3.3
of this appendix:
PO 00000
Frm 00035
Fmt 4701
Sfmt 4700
59419
3.2.1.3.3.14.1. If the lamp is a lower
wattage replacement of a lamp with
specifications in ANSI C78.901–2014, use the
reference ballast characteristics of the
corresponding higher wattage lamp
replacement in ANSI C78.901–2014.
3.2.1.3.3.14.2. For all other lamps, use the
reference ballast characteristics in ANSI
C78.901–2014 for a lamp with the most
similar shape, diameter, and base
specifications, and next closest wattage.
3.2.2. Test Methods, Measurements, and
Calculations
3.2.2.1. Season CFLs. (See section 3.1.3 of
this appendix.)
3.2.2.2. Stabilize CFLs as specified in
section 6.2.1 of IES LM–66 (incorporated by
reference; see § 430.3).
3.2.2.3. Measure the input power (in
watts), the input voltage (in volts), and the
input current (in amps) as specified in
section 5.0 of IES LM–66 (incorporated by
reference; see § 430.3).
3.2.2.4. Measure initial lumen output as
specified in section 6.3.1 of IES LM–66
(incorporated by reference; see § 430.3) and
in accordance with IESNA LM–78–07
(incorporated by reference; see § 430.3).
3.2.2.5. Measure lumen output at 1,000
hours as specified in section 6.3.1 of IES LM–
66 (incorporated by reference; see § 430.3)
and in accordance with IESNA LM–78–07
(incorporated by reference; see § 430.3).
3.2.2.6. Measure lumen output at 40
percent of lifetime of a compact fluorescent
lamp (as defined in 10 CFR 430.2) as
specified in section 6.3.1 of IES LM–66
(incorporated by reference; see § 430.3) and
in accordance with IESNA LM–78–07
(incorporated by reference; see § 430.3).
3.2.2.7. Determine CCT as specified in
section 6.4 of IES LM–66 (incorporated by
reference; see § 430.3) and in accordance
with CIE 15 (incorporated by reference; see
§ 430.3).
3.2.2.8. Determine CRI as specified in
section 6.4 of IES LM–66 (incorporated by
reference; see § 430.3) and in accordance
with CIE 13.3 (incorporated by reference; see
§ 430.3).
3.2.2.9. Determine initial lamp efficacy by
dividing measured initial lumen output by
the measured initial input power.
3.2.2.10. Determine lumen maintenance at
1,000 hours by dividing measured lumen
output at 1,000 hours by the measured initial
lumen output.
3.2.2.11. Determine lumen maintenance at
40 percent of lifetime of a compact
fluorescent lamp (as defined in § 430.2) by
dividing measured lumen output at 40
percent of lifetime of a compact fluorescent
lamp (as defined in § 430.2) by the measured
initial lumen output.
3.2.2.12. Determine power factor by
dividing the measured input power (watts)
by the product of measured RMS input
voltage (volts) and measured RMS input
current (amps).
3.3. Test Method for Time to Failure and
Rapid Cycle Stress Test.
Determine time to failure for integrated and
non-integrated CFLs. Conduct rapid cycle
stress testing for integrated CFLs only.
Disregard section 3.0 of IES LM–65–14.
3.3.1. Test Conditions and Setup
E:\FR\FM\29AUR4.SGM
29AUR4
59420
Federal Register / Vol. 81, No. 167 / Monday, August 29, 2016 / Rules and Regulations
3.3.1.1. Test half of the units in the base
up position and half of the units in the base
down position; if the position is restricted by
the manufacturer, test in the manufacturerspecified position.
3.3.1.2. Establish the ambient and physical
conditions and electrical conditions in
accordance with the specifications in
sections 4.0 and 5.0 of IES LM–65–14
(incorporated by reference; see § 430.3). Do
not, however, test lamps in fixtures or
luminaires.
3.3.1.3. Non-integrated CFLs must adhere
to ballast requirements as specified in section
3.2.1.3 of this appendix.
3.3.2. Test Methods and Measurements
3.3.2.1. Season CFLs. (See section 3.1.3 of
this appendix.)
3.3.2.2. Measure time to failure of CFLs as
specified in section 6.0 of IES LM–65–14
(incorporated by reference; see § 430.3).
3.3.2.3. Conduct rapid cycle stress testing
of integrated CFLs as specified in section 6.0
of IES LM–65–14 (incorporated by reference;
see § 430.3), except cycle the lamp
continuously with each cycle consisting of
one 5-minute ON period followed by one 5minute OFF period.
3.4. Test Method for Start Time.
Determine start time for integrated CFLs
only.
3.4.1. Test Conditions and Setup
3.4.1.1. Test all units in the base up
position; if the position is restricted by the
manufacturer, test units in the manufacturerspecified position.
3.4.1.2. Establish the ambient conditions,
power supply, auxiliary equipment, circuit
setup, lamp connections, and
instrumentation in accordance with the
specifications in sections 4.0 and 5.0 of IES
LM–66 (incorporated by reference; see
§ 430.3), except maintain ambient
temperature at 25 ± 1 °C (77 ± 1.8 °F).
3.4.2. Test Methods and Measurement
3.4.2.1. Season CFLs. (See section 3.1.3 of
this appendix.)
3.4.2.2. After seasoning, store units at 25 ±
5 °C ambient temperature for a minimum of
16 hours prior to the test, after which the
ambient temperature must be 25 ± 1 °C for
a minimum of 2 hours immediately prior to
the test. Any units that have been off for
more than 24 hours must be operated for a
minimum of 3.0 hours and then be turned off
for 16 to 24 hours prior to testing.
3.4.2.3. Connect multichannel oscilloscope
with data storage capability to record input
voltage to CFL and light output. Set
oscilloscope to trigger at 10 V lamp input
voltage. Set oscilloscope vertical scale such
that vertical resolution is 1 percent of
measured initial light output or finer. Set
oscilloscope to sample the light output
waveform at a minimum rate of 2 kHz.
3.4.2.4. Operate the CFL at the rated
voltage and frequency.
3.4.2.5. Upon the commencement of start
time testing, record sampled light output
until start plateau has been determined.
3.4.2.6. Calculate the time-averaged light
output value at least once every millisecond
where the time-averaged light output is
computed over one full cycle of sinusoidal
input voltage, as a moving average where the
measurement interval is incremented by one
sample for each successive measurement
value.
3.4.2.7. Determine start time.
4. Standby Mode Test Procedure
Measure standby mode energy
consumption for only integrated CFLs that
are capable of operating in standby mode.
The standby mode test method in this section
may be completed before or after the active
test method for determining lumen output,
input power, CCT, CRI, and power factor in
section 3 of this appendix. The standby mode
test method in this section must be
completed before the active mode test
method for determining time to failure in
section 3.3 of this appendix. The standby
mode test method must be completed in
accordance with applicable provisions in
section 3.1.
4.1. Test Conditions and Setup
4.1.1. Position half of the units in the
sample in the base up position and half of the
Factor
10. Section 430.32 is amended by
revising paragraph (u) to read as
follows:
■
§ 430.32 Energy and water conservation
standards and their compliance dates.
*
*
*
*
*
(u) Compact fluorescent lamps. (1)
Medium Base Compact Fluorescent
Lamps. A bare or covered (no reflector)
medium base compact fluorescent lamp
manufactured on or after January 1,
2006, must meet the following
requirements:
Requirements
Labeled Wattage (Watts) & Configuration * ..............................................
Bare Lamp:
Labeled Wattage < 15 .......................................................................
Labeled Wattage ≥ 15 .......................................................................
Covered Lamp (no reflector):
Labeled Wattage < 15 .......................................................................
15 ≤ Labeled Wattage < 19 ..............................................................
19 ≤ Labeled Wattage < 25 ..............................................................
Labeled Wattage ≥ 25 .......................................................................
Lumen Maintenance at 1,000 Hours ........................................................
Lumen Maintenance at 40 Percent of Lifetime ** .....................................
Rapid Cycle Stress Test ...........................................................................
Lifetime ** ..................................................................................................
mstockstill on DSK3G9T082PROD with RULES4
units in the base down position; if the
position is restricted by the manufacturer,
test units in the manufacturer-specified
position.
4.1.2. Establish the ambient conditions
(including air flow), power supply, electrical
settings, and instrumentation in accordance
with the specifications in sections 4.0, 5.0
and 6.0 of IES LM–66 (incorporated by
reference; see § 430.3), except maintain
ambient temperature at 25 ± 1 °C (77 ±
1.8 °F).
4.2. Test Methods, Measurements, and
Calculations
4.2.1. Season CFLs. (See section 3.1.3 of
this appendix.)
4.2.2. Connect the integrated CFL to the
manufacturer-specified wireless control
network (if applicable) and configure the
integrated CFL in standby mode by sending
a signal to the integrated CFL instructing it
to have zero light output. The integrated CFL
must remain connected to the network
throughout the entire duration of the test.
4.2.3. Stabilize the integrated CFL prior to
measurement as specified in section 5 of IEC
62301–W (incorporated by reference; see
§ 430.3).
4.2.4. Measure the standby mode energy
consumption in watts as specified in section
5 of IEC 62301–W (incorporated by reference;
see § 430.3).
Measured initial lamp efficacy (lumens per watt) must be at least:
45.0.
60.0.
40.0.
48.0.
50.0.
55.0.
≥90.0%.
≥80.0%.
Each lamp must be cycled once for every 2 hours of lifetime.** At least
5 lamps must meet or exceed the minimum number of cycles.
≥6,000 hours.
* Use labeled wattage to determine the appropriate efficacy requirements in this table; do not use measured wattage for this purpose.
** Lifetime refers to lifetime of a compact fluorescent lamp as defined in 10 CFR 430.2.
*
(2) [Reserved].
*
*
*
*
[FR Doc. 2016–19967 Filed 8–26–16; 8:45 am]
BILLING CODE 6450–01–P
VerDate Sep<11>2014
18:00 Aug 26, 2016
Jkt 238001
PO 00000
Frm 00036
Fmt 4701
Sfmt 9990
E:\FR\FM\29AUR4.SGM
29AUR4
Agencies
[Federal Register Volume 81, Number 167 (Monday, August 29, 2016)]
[Rules and Regulations]
[Pages 59385-59420]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2016-19967]
[[Page 59385]]
Vol. 81
Monday,
No. 167
August 29, 2016
Part IV
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 430
Energy Conservation Program: Test Procedure for Compact Fluorescent
Lamps; Final Rule
Federal Register / Vol. 81 , No. 167 / Monday, August 29, 2016 /
Rules and Regulations
[[Page 59386]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[Docket No. EERE-2015-BT-TP-0014]
RIN 1904-AC74
Energy Conservation Program: Test Procedure for Compact
Fluorescent Lamps
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: This final rule amends the U.S. Department of Energy's (DOE)
test procedures for medium base compact fluorescent lamps (MBCFLs) and
adopts test procedures for new metrics for all CFLs including hybrid
CFLs and CFLs with bases other than medium screw base. In this final
rule, DOE replaces references to ENERGY STAR[supreg] testing
requirements with references to the latest versions of the relevant
industry standard test methods referenced by the ENERGY STAR testing
requirements, with certain modifications. In addition, DOE adopts new
test procedures to support the ongoing energy conservation standards
rulemaking for general service lamps (GSLs), the recently revised final
test procedure and energy conservation standards for ceiling fan light
kits (CFLKs), and the labeling requirements specified by the Federal
Trade Commission (FTC). The test procedures will also support the
ENERGY STAR program requirements for lamps and luminaires.
Specifically, this final rule adopts test methods for new metrics
including color rendering index (CRI), correlated color temperature
(CCT), power factor, and start time. DOE also adopts test procedures
for additional CFL categories, including non-integrated CFLs and
integrated CFLs that are not MBCFLs. This final rule also revises the
sampling plan for performance metrics and incorporates methods to
measure standby mode power.
DATES: The effective date of this rule is September 28, 2016.
Representations must be based on testing in accordance with the final
rule starting February 27, 2017. The incorporation by reference of
certain publications listed in this rule was approved by the Director
of the Federal Register on September 28, 2016.
ADDRESSES: The docket, which includes Federal Register notices, public
meeting attendee lists and transcripts, comments, and other supporting
documents/materials, is available for review at www.regulations.gov.
All documents in the docket are listed in the www.regulations.gov
index. However, some documents listed in the index, such as those
containing information that is exempt from public disclosure, may not
be publicly available.
A link to the docket Web page can be found at https://www1.eere.energy.gov/buildings/appliance_standards/product.aspx/productid/28. This Web page will contain a link to the docket for this
notice on the www.regulations.gov site. The www.regulations.gov Web
page will contain simple instructions on how to access all documents,
including public comments, in the docket.
For further information on how to review the docket, contact Ms.
Emily Marchetti at (202) 586-6636 or by email:
medium_base_compact_fluorescent_lamps@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Ms. Lucy deButts, U.S. Department of
Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Office, EE-2J, 1000 Independence Avenue SW., Washington,
DC, 20585-0121. Telephone: (202) 287-1604. Email:
medium_base_compact_fluorescent_lamps@ee.doe.gov.
Mr. Peter Cochran, U.S. Department of Energy, Office of the General
Counsel, GC-33, 1000 Independence Avenue SW., Washington, DC 20585-
0121. Telephone: (202) 586-9496. Email: peter.cochran@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final rule incorporates by reference
into part 430 specific sections of the following industry standards:
(1) American National Standards Institute and International
Electrotechnical Commission (ANSI) C78.901-2014, American National
Standard for Electric Lamps--Single-Based Fluorescent Lamps--
Dimensional and Electrical Characteristics. Copies of ANSI C78.901-
2014 can be obtained from ANSI Attn: Customer Service Department, 25
W 43rd Street, 4th Floor, New York, NY, 10036, or by going to https://webstore.ansi.org/.
(2) CIE 13.3-1995 (``CIE 13.3''), Technical Report: Method of
Measuring and Specifying Colour Rendering Properties of Light
Sources, 1995, ISBN 3 900 734 57 7.
(3) CIE 15:2004 (``CIE 15''), Technical Report: Colorimetry, 3rd
edition, 2004, ISBN 978 3 901906 33 6.
Copies of CIE 13.3 and CIE 15 can be obtained from Commission
Internationale de l'Eclairage, Central Bureau, Kegelgasse 27, A-
1030, Vienna, Austria, 011 + 43 1 714 31 87 0, or by going to https://www.cie.co.at.
(4) IEC 62301 (``IEC 62301-W''), Household electrical
appliances--Measurement of standby power (Edition 2.0, 2011-01).
A copy of IEC 62301 can be obtained from the American National
Standards Institute, 25 W. 43rd Street, 4th Floor, New York, NY
10036, (212) 642-4900, or by going to https://webstore.ansi.org.
(5) Illuminating Engineering Society of North America (IES) LM-
54-12, IES Guide to Lamp Seasoning.
(6) IES LM-65-14, IES Approved Method for Life Testing of
Single-Based Fluorescent Lamps.
(7) IES LM-66-14, (``IES LM-66''), IES Approved Method for the
Electrical and Photometric Measurements of Single-Based Fluorescent
Lamps.
(8) IESNA LM-78-07, IESNA Approved Method for Total Luminous
Flux Measurement of Lamps Using an Integrating Sphere Photometer.
Copies of IES LM-54-12, IES LM-65-14, IES LM-66 and IES LM-78-07 can
be obtained from IES, 120 Wall Street, Floor 17, New York, NY 10005-
4001, or by going to www.ies.org/store.
For a further discussion of these standards, see section IV.M.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Final Rule
III. Discussion
A. Amendments to Appendix W to Subpart B of 10 CFR part 430
1. Updates to Industry Test Methods
2. Clarifications to General Test Conditions and Setup
3. Clarifications to Definitions
4. Test Procedures for Existing and New Metrics
5. Test Procedures for New CFL Categories
6. Test Procedure for Standby Mode Energy Consumption
7. Rounding Values
B. Amendments to Definitions at 10 CFR 430.2
1. Compact Fluorescent Lamp
2. Correlated Color Temperature
3. Lifetime of a Compact Fluorescent Lamp
C. Amendments to Materials Incorporated by Reference at 10 CFR
430.3
D. Amendments to 10 CFR 430.23(y)
E. Amendments to Laboratory Accreditation Requirements at 10 CFR
430.25
F. Clarifications to Energy Conservation Standard Text at 10 CFR
430.32(u)
1. Initial Lamp Efficacy
2. Lumen Maintenance at 1,000 Hours
3. Lumen Maintenance at 40 Percent of Lifetime
4. Rapid Cycle Stress Test
5. Lifetime
G. Amendments to Certification Report Requirements
H. Amendments to 10 CFR 429.35
1. Initial Lamp Efficacy and Lumen Maintenance
2. Rapid Cycle Stress Testing
3. Lifetime of a Compact Fluorescent Lamp
4. New Metrics
5. Reuse of Samples
6. Lamp Failures
I. Federal Trade Commission (FTC) Labeling Requirements
J. Effective Date
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
[[Page 59387]]
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Description of Materials Incorporated by Reference
N. Congressional Notification
V. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III of the Energy Policy and Conservation Act of 1975 (42
U.S.C. 6291, et seq.; ``EPCA'' or, ``the Act'') sets forth a variety of
provisions designed to improve energy efficiency.\1\ Part B of title
III, which for editorial reasons was redesignated as Part A upon
incorporation into the U.S. Code (42 U.S.C. 6291-6309, as codified),
established the ``Energy Conservation Program for Consumer Products
Other Than Automobiles.'' CFLs are among the consumer products affected
by these provisions.
---------------------------------------------------------------------------
\1\ All references to EPCA refer to the statute as amended
through the Energy Efficiency Improvement Act of 2015, Public Law
114-11 (April 30, 2015).
---------------------------------------------------------------------------
Under EPCA, the energy conservation program consists essentially of
four parts: (1) Testing, (2) labeling, (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. The
testing requirements consist of test procedures that manufacturers of
covered products must use as the basis for (1) certifying to DOE that
their products comply with the applicable energy conservation standards
adopted under EPCA (42 U.S.C. 6295(s)) and (2) making representations
about the energy use or efficiency of the products (42 U.S.C. 6293(c)).
EPCA sets forth the criteria and procedures DOE must follow when
prescribing or amending test procedures for covered products. EPCA
provides, in relevant part, that any new or amended test procedure
shall be reasonably designed to produce test results that measure
energy efficiency, energy use, or estimated annual operating cost of a
covered product during a representative average use cycle or period of
use, and shall not be unduly burdensome to conduct. (42 U.S.C.
6293(b)(3))
In addition, if DOE determines that a test procedure amendment is
warranted, it must publish a proposed test procedure and offer the
public an opportunity to present oral and written comments. (42 U.S.C.
6293(b)(2)) Finally, in any rulemaking to amend a test procedure, DOE
must determine to what extent, if any, the proposed test procedure
would alter the measured energy efficiency of the covered product as
determined under the existing test procedure. (42 U.S.C. 6293(e)(1))
EPCA also requires that, at least once every 7 years, DOE evaluate
test procedures for each type of covered equipment, including MBCFLs,
to determine whether amended test procedures would more accurately or
fully comply with the requirements for the test procedures to not be
unduly burdensome to conduct and be reasonably designed to produce test
results that reflect energy efficiency, energy use, and estimated
operating costs during a representative average use cycle. (42 U.S.C.
6293(b)(1)(A))
Finally, EPCA directs DOE to amend its test procedures for all
covered products to integrate measures of standby mode and off mode
energy consumption, if technically feasible. (42 U.S.C. 6295(gg)(2)(A))
DOE has determined that, while no CFLs are capable of operating under
off mode, some CFLs are capable of operating under standby mode.
Consequently, DOE adopts a test procedure for measuring standby mode
power in appendix W, as detailed in section III.A.6 of this final rule.
B. Background
The Energy Policy Act of 2005 (Public Law 109-58) amended EPCA to
require that MBCFL test procedures be based on the August 2001 version
of the ENERGY STAR[supreg] Program Requirements for CFLs. (42 U.S.C.
6293(b)(12)) Consistent with this requirement, DOE published a final
rule on December 8, 2006 (December 2006 final rule) that established
DOE's current test procedures for MBCFLs under 10 CFR part 430, subpart
B, appendix W. 71 FR 71340. The December 2006 final rule established
test procedures for initial lamp efficacy, lumen maintenance at 1,000
hours, lumen maintenance at 40 percent of lifetime, rapid cycle stress
test, and lifetime for MBCFLs. Id.
EPCA, however, also requires that at least once every 7 years, DOE
must conduct an evaluation of all covered products and either amend the
test procedures (if the Secretary determines that amended test
procedures would more accurately or fully comply with the requirements
of 42 U.S.C. 6293(b)(3)) or publish a determination in the Federal
Register not to amend them. (42 U.S.C. 6293(b)(1)(A)) The ENERGY STAR
Program Requirements for CFLs have been updated several times since
2001 to reflect current best practices and technological developments.
This final rule amends the CFL test procedure to directly reference the
latest industry standards in accordance with this EPCA requirement.
On July 31, 2015, DOE issued a NOPR (July 2015 NOPR) to amend and
expand its test procedures for CFLs. 80 FR 45723. DOE then held a
public meeting to discuss these proposed amendments on August 31, 2015,
and allowed for written comments to be submitted through October 14,
2015. This rule addresses comments that were received on the proposal
and finalizes many of the proposed changes to appendix W to subpart B
of 10 CFR part 430 and to 10 CFR part 429.
II. Synopsis of the Final Rule
In this final rule, DOE replaces the existing references to ENERGY
STAR program requirements with direct references to the latest versions
of the appropriate industry test methods from the Illuminating
Engineering Society of North America (IES) (see section III.A.1 for
further details). Directly referencing the latest industry standards
will allow DOE to adopt current best practices and technological
developments in its test procedures.
DOE also adopts, in this rule, test procedures for additional CFL
categories and metrics to support energy conservation standard
rulemakings for GSLs and CFLKs. DOE's existing test procedures apply
only to integrated CFLs with medium screw bases (i.e., MBCFLs).
Integrated CFLs (also referred to as self-ballasted or integrally
ballasted) contain all components necessary for the starting and stable
operation of the lamp, do not include any replaceable or
interchangeable parts, and are connected directly to a branch circuit
through an American National Standards Institute (ANSI) base and
corresponding ANSI standard lamp-holder (socket). Non-integrated CFLs
(also referred to as pin-base) require an external ballast to function,
and mainly have pin bases, (e.g., 2-pin or 4-pin). On March 17, 2016,
DOE issued a NOPR (March 2016 NOPR) that proposes a new definition for
general service lamp that includes both non-integrated CFLs and
integrated CFLs. 81 FR 14527. The March 2016 NOPR also proposes minimum
efficacy and power factor standards for certain types of general
service lamps and additional metrics for
[[Page 59388]]
MBCFLs. On January 6, 2016, DOE issued a final rule (January 2016 final
rule) establishing amended energy conservation standards for CFLs, both
integrated and non-integrated, packaged with a CFLK. 81 FR 579.
DOE is also adopting these new test procedures to support: (1) The
Federal Trade Commission (FTC) labeling requirements for lighting
products as specified in 16 CFR 305.15; and (2) the U.S. Environmental
Protection Agency's ENERGY STAR program for lamps and luminaires. Under
the FTC Lighting Facts labeling requirement, manufacturers are required
to include basic and consistent information about certain types of
light bulbs (lamps) including information about the lumen output, input
power, life, and correlated color temperature (CCT) on the lamp
packaging. Regarding ENERGY STAR, DOE's adopted CFL test procedure
provides test methods for certain metrics included in the ENERGY STAR
specification for lamps \2\ and luminaires.\3\ The ENERGY STAR lamps
specification includes, among others, metrics for initial lamp
efficacy, lumen maintenance at 1,000 hours, lumen maintenance at 40
percent of lifetime, rapid cycle stress test, lifetime, CCT, color
rendering index (CRI), power factor, and start time. The ENERGY STAR
luminaires specification includes, among others, metrics for efficacy,
lumen maintenance at 40 percent of lifetime, lifetime, CCT, CRI, power
factor, and start time.
---------------------------------------------------------------------------
\2\ ENERGY STAR[supreg] Program Requirements Product
Specification for Lamps (Light Bulbs), Eligibility Criteria, Version
2.0. December 31, 2015. Washington, DC. https://www.energystar.gov/sites/default/files/ENERGY%20STAR%20Lamps%20V2_0%20Program%20Requirements.pdf.
\3\ ENERGY STAR[supreg] Program Requirements Product
Specification for Luminaires (Light Fixtures), Eligibility Criteria,
Version 2.0. May 29, 2015. Washington, DC. https://www.energystar.gov/sites/default/files/asset/document/Luminaires%20V2%200%20Final.pdf.
---------------------------------------------------------------------------
Table II.1 summarizes the metrics adopted in this final rule and
which agency requires them.
Table II.1--CFL Metrics in DOE Regulations, FTC Labeling Requirements, and the ENERGY STAR Program
--------------------------------------------------------------------------------------------------------------------------------------------------------
DOE proposed or established regulations EPA ENERGY STAR
--------------------------------------------------- FTC labeling program for
Metric requirements lamps or
MBCFL GSL CFLK luminaires
--------------------------------------------------------------------------------------------------------------------------------------------------------
Integrated CFLs
--------------------------------------------------------------------------------------------------------------------------------------------------------
Efficacy........................................................... X X X X X
CCT................................................................ ............... -- -- X X
CRI................................................................ ............... X -- -- X
Lumen maintenance at 1,000 hours................................... X X X -- X
Lumen maintenance at 40% of lifetime............................... X X X -- X
Lifetime........................................................... X X X X X
Rapid Cycle Stress Test............................................ X X X -- X
Power Factor....................................................... ............... X -- -- X
Start Time......................................................... ............... X -- -- X
Standby Mode Energy Consumption.................................... ............... X -- -- X
--------------------------------------------------------------------------------------------------------------------------------------------------------
Non-Integrated CFLs
--------------------------------------------------------------------------------------------------------------------------------------------------------
Efficacy........................................................... -- * X -- X
CCT................................................................ -- -- -- -- X
CRI................................................................ -- -- -- -- X
Lumen maintenance at 40% of lifetime............................... -- -- -- -- X
Lifetime........................................................... -- -- -- -- X
--------------------------------------------------------------------------------------------------------------------------------------------------------
* In the March 2016 NOPR, DOE notes that the backstop provision in 6296(i)(6)(A)(v) is automatically triggered. The backstop provision requires all
lamps that meet the definition of a general service lamp (which includes many non-integrated compact fluorescent lamps) comply with a minimum efficacy
standard of 45 lumens per watt. 81 FR 14528, 14540 (March 17, 2016).
Additionally, DOE establishes a test procedure for CFL standby mode
power measurement, as directed by EPCA. However, this test procedure
will only apply to integrated CFLs because non-integrated CFLs are not
capable of standby mode operation (see section III.A.6).
Finally, DOE also revises the current sampling plan in 10 CFR
429.35. This revised sampling plan is consistent with ENERGY STAR Lamps
Specification V2.0, as detailed in section III.H.
III. Discussion
A. Amendments to Appendix W to Subpart B of 10 CFR part 430
1. Updates to Industry Test Methods
DOE's existing MBCFL test procedures contained in appendix W to
subpart B of 10 CFR part 430 are based on the August 2001 version of
the ENERGY STAR program requirements for CFLs,\4\ which has since been
updated several times. In the July 2015 NOPR, DOE proposed replacing
the existing references to ENERGY STAR program requirements with direct
references to the latest versions of the appropriate industry test
methods from the IES. DOE explained that directly referencing the
latest industry standards would allow DOE to adopt current best
practices and technological developments in its test procedures. As a
result, DOE proposed to directly incorporate by reference in appendix W
the latest versions of the following industry test procedures: IES LM-
66-14,\5\ IES LM-65-14,\6\ and IES LM-54-12.\7\ DOE also proposed to no
longer incorporate by reference the August 2001 version of the ENERGY
STAR Program Requirements for CFLs, previously approved for appendix W.
---------------------------------------------------------------------------
\4\ ENERGY STAR[supreg] Program Requirements for CFLs Partner
Commitments, Version 2.0, Washington, DC (Aug. 9, 2001).
www.energystar.gov/ia/partners/product_specs/program_reqs/archive/CFLs_Program_RequirementsV2.0.pdf.
\5\ IES Approved Method for the Electrical and Photometric
Measurements of Single-Based Fluorescent Lamps (approved December
30, 2014).
\6\ IES Approved Method for Life Testing of Single-Based
Fluorescent Lamps (approved December 30, 2014).
\7\ IES Guide to Lamp Seasoning (approved October 22, 2012).
---------------------------------------------------------------------------
[[Page 59389]]
DOE compared the currently referenced versions and the new updated
versions of the relevant industry standards to determine, as directed
by EPCA, whether adopting the latest industry standards would alter
measured energy efficiency for MBCFLs as determined under the current
DOE test procedure. DOE determined that these changes would have a de
minimis effect on measured values.
Both the National Electrical Manufacturers Association (NEMA) and
OSRAM SYLVANIA, Inc. (OSI) supported the incorporation by reference of
IES LM-66-14 and IES LM-65-14 stating that it would not significantly
affect the testing or measured values. (NEMA, No. 9 at pp. 3,8; OSI,
No. 5 at pp. 2-3) \8\
---------------------------------------------------------------------------
\8\ DOE identifies comments received in response to the July
2015 CFL TP NOPR on Docket No. EERE-2015-BT-TP-0014 by the
commenter, the document number as listed in the docket maintained at
www.regulations.gov, and the page number of that document where the
comment appears (for example: OSI, No. 5 at p. 7). If a comment was
made verbally during the August 2015 NOPR public meeting, DOE
---------------------------------------------------------------------------
DOE received comments regarding the provisions on cycling lamps
during seasoning in IES LM-54-12. Under the current test procedure, in
accordance with IES LM-54-1991, all lamps are seasoned at a 3 hour on,
20 minute off cycle for 100 operating hours. The latest version of the
standard, IES LM-54-12, also specifies that lamps that are to be
lifetime tested shall be cycled during seasoning. However, IES LM-54-12
does not specify a specific operating cycle during seasoning for
lifetime testing. IES LM-54-12 also states that lamps to be tested for
other performance metrics can be continuously burned (not cycled)
during seasoning to shorten the time required for seasoning. In the
July 2015 NOPR, DOE tentatively determined that not providing a
specific operating cycle during seasoning for lifetime testing and not
requiring cycling during seasoning for other performance metrics would
have a de minimis impact on measured values.
The California Investor Owned Utilities (CA IOUs) \9\ and the
Energy Efficiency Advocates (EEAs),\10\ however, disagreed and
recommended that DOE require lamps to be cycled (operated 3 hours and
then turned off for 20 minutes) during seasoning as was specified in
IES LM-54-1991. (CA IOUs, No. 7 at p. 3; EEAs, No. 8 at p. 4)
---------------------------------------------------------------------------
\9\ The CA IOUs are Pacific Gas and Electric Company (PG&E),
Southern California Gas Company (SCG), San Diego Gas and Electric
Company (SDG&E), and Southern California Edison (SCE).
\10\ The EEAs are the Appliance Standards Awareness Project
(ASAP), American Council for an Energy Efficient Economy (ACEEE),
Alliance to Save Energy (ASE), Natural Resources Defense Council
(NRDC), Northeast Energy Efficiency Partnerships (NEEP), and
Northwest Energy Efficiency Alliance (NEEA).
---------------------------------------------------------------------------
DOE continues to find that cycling during seasoning would have a de
minimis impact on measured values. However, in this final rule, in
order to establish a more consistent test procedure, DOE specifies
cycling during seasoning for all metrics. As discussed in section
III.H.5, in this final rule, DOE requires that the same set of lamps be
used for measurement of initial lamp efficacy, lumen maintenance,
lifetime, color measurements, start time, and power factor. Because of
this requirement to use the same set of lamps and the specification in
IES LM-54-12 that lamps should be cycled during seasoning for lifetime
measurements, lamps used in DOE's test procedure must be cycled during
seasoning for all other measurements as well. Rapid cycle stress
testing is conducted on a unique set of lamps--a separate set of lamps
than used for all other metrics. However, DOE requires in this final
rule that lamps used for rapid cycle stress testing also be cycled
while seasoned and thereby provides a consistent methodology for
seasoning across all metrics.
To provide further consistency and specificity in test method, in
this final rule, DOE specifies in this test procedure how to cycle
lamps. Although section 6.2.2.1 of LM-54-12 states that for lifetime
testing, lamps should be cycled during seasoning, IES LM-54-12 does not
define the cycling time. IES LM-54-1991 required that all lamps be
seasoned at a 3 hour (180 minutes) on, 20 minute off cycle for 100
operating hours. Additionally, section 6.4 of IES LM-65-14 states that
the standard life operating cycle shall be 180 minutes on, 20 minutes
off. Therefore, in this final rule, DOE specifies in section 3.1.3 of
appendix W that lamps must be cycled during seasoning, and the
operating cycle must be 180 minutes on, 20 minutes off in accordance
with section 6.4 of IES LM-65-14. In this final rule, DOE incorporates
by reference IES LM-54-12, and supplements its seasoning requirements
with the additional requirements noted in this section.
DOE also received several comments regarding how industry standards
incorporated by reference should be cited within the DOE test
procedure. Both NEMA and OSI commented that in the NOPR, DOE proposed
text copied directly from the referenced industry standards for
incorporation into the CFR. NEMA recommended that instead, DOE should
incorporate these publications by reference, ensuring that interested
parties understand the context. (NEMA, No. 9 at p. 2; OSI, No. 5 at p.
2) Philips Lighting (Philips) expressed concern that when the DOE test
procedure deviates from a document incorporated by reference it adds
another level of complexity and possibly leads to confusion. (Philips,
Public Meeting Transcript, No. 4 at pp. 83-84) As a solution, Philips
suggested that DOE provide specific instructions to the testing
laboratory like ENERGY STAR and other programs. (Philips, Public
Meeting Transcript, No. 4 at p. 68) Westinghouse stated that, although
they preferred DOE incorporate by reference the entire document, it was
acceptable if only portions can be referenced. Westinghouse stated that
it can cause confusion when DOE makes modifications such that something
not in the referenced standard is included in the DOE test procedure.
In particular, when auditing a test lab, Westinghouse noted that the
lab may meet requirements based on the referenced standard but not
based on DOE's test procedure. (Westinghouse, Public Meeting
Transcript, No. 4 at p. 85)
DOE appreciates the feedback related to incorporation by reference
of industry standards as well as ways to improve the clarity of DOE's
test procedure. In the NOPR and in this final rule, DOE did not include
text in the regulatory language copied directly from an industry
standard and instead incorporated by reference relevant industry
standards in 10 CFR 430.3 and referenced sections of the incorporated
industry standards as relevant in DOE's test procedures. DOE lays out
instructions regarding the test setup conditions, test methods, and
measurements for each CFL metric in appendix W. In these instructions,
DOE references relevant sections of industry standards, and provides
further clarification as needed. To generate reliable and consistent
results, DOE, in some instances, provides further clarification and/or
exceptions to the industry standards referenced. For example, appendix
W states that lamps should be seasoned according to sections 4, 5, 6.1,
and 6.2.2.1 of IES LM-54-12. To reduce test burden, DOE provides
further clarification in appendix W that time during seasoning can be
counted toward time to failure and lumen maintenance at 40 percent of
lifetime (see section III.A.2.e for further details). IES LM-54-12
states that, for lifetime testing, lamps shall be cycled during
seasoning, and for all other performance metrics, lamps can be
continuously burned during seasoning.
[[Page 59390]]
To ensure consistent seasoning requirements across all metrics, DOE
requires in this final rule that, for all metrics, including lifetime,
lamps must be cycled during seasoning (as noted in this section).
Therefore, DOE's test procedure in appendix W is streamlined to
provide, at each step, only the relevant sections of industry
standards, and any related additional instructions and/or
clarifications specific to the DOE test procedure. In summary, DOE
finds that the test procedures for CFLs as prescribed in this final
rule address the concerns of interested parties to provide clear,
unambiguous instruction regarding the appropriate procedures for
testing CFLs.
2. Clarifications to General Test Conditions and Setup
a. Instrumentation
In the July 2015 NOPR, DOE proposed that photometric measurements
including lumen output, CCT, and CRI be carried out in an integrating
sphere. DOE made this proposal because of potential differences in
measured values when conducting testing with an integrating sphere
versus a goniophotometer and certain issues with the use of
goniophotometers. DOE received comments related to its proposal to only
allow the use of integrating spheres for photometric measurements. P.R.
China noted that although the integrating sphere method is simpler, the
goniophotometer measures luminous flux using an absolute method and is
therefore more accurate. Specifically, P.R. China argued that the
goniophotometer method should be allowed because integrating spheres
might lead to errors with large-sized lamps or lamps with special
shapes. P.R. China added that additional testing cost and/or burden
could be introduced by only allowing the use of integrating spheres.
(P.R. China, No. 10 at p. 3) However, NEMA and OSI were supportive of
using only an integrating sphere for testing. (NEMA, No. 9 at p. 3;
OSI, No. 5 at p. 3)
Both the integrating sphere and goniophotometer methods are allowed
in IES LM-66-14. DOE understands that both these methods are valid ways
to take photometric measurements. However, DOE is concerned about the
potential difference in measured values generated from the two
different measurement approaches. Because DOE test procedures must
yield repeatable and reproducible results and comparable measured
values, DOE determined that it must specify one method of measurement.
DOE believes that the integrating sphere method is preferable to the
goniophotometer method because of certain issues that make
goniophotometer testing more variable and potentially less accurate.
The goniophotometer is potentially problematic for lamps that emit
light in all directions as the setup may result in a dead angle where
some part of the light output is blocked by the equipment (e.g., the
arm in which the lamp is held). The goniophotometer method also
requires a precise scanning resolution that may differ by lamp and is
not subject to a specific industry requirement that could provide
consistency across measurements. Integrating spheres can come in a
range of sizes and can accordingly be used to test a variety of sizes
and shapes of lamps, including linear fluorescent lamps, which are much
larger than CFLs. Therefore, DOE is not aware of any constraints or
limitations regarding testing CFLs using integrating spheres.
DOE also proposed to incorporate by reference IESNA LM-78-07 in the
July 2015 NOPR, which provides more specific guidance on measuring
lumen output in an integrated sphere. DOE did not receive any comments
related to IESNA LM-78-07.
For these reasons, DOE requires that all photometric measurements,
including lumen output, CCT, and CRI, must be carried out using the
integrating sphere method. Additionally, to provide a method for
measuring lumen output in an integrating sphere, DOE incorporates by
reference IESNA LM-78-07.
b. Ambient Temperature
In the July 2015 NOPR, DOE proposed that photometric and electrical
testing of CFLs must be conducted at an ambient temperature of 25
1 [deg]C. 80 FR 45731. Section 4.3 of IES LM-66-14 states
that the ambient temperature during photometric and electrical testing
must be maintained at 25 1 [deg]C unless the CFL is
designed to perform optimally under non-standard conditions. Similar
requirements and allowance were given in IES LM-66-1991. DOE's review
of manufacturer-published product literature suggests that photometric
and electrical testing of CFLs is typically conducted at the standard
25 1 [deg]C temperature conditions and possible
inconsistencies could arise between represented values if testing
occurred at other temperatures.
OSI commented that the ambient temperature requirement of 25 1 [deg]C is acceptable for most lamps, but not for non-
integrated lamps specifically designed for high ambient temperature
operation. (OSI, No. 5 at p. 3) General Electric (GE) was also
supportive of the temperature range for testing for most products, but
requested an exclusion for products that are specifically designed for
high ambient temperatures. (GE, Public Meeting Transcript, No. 4 at pp.
32-33) NEMA commented that non-integrated lamps specifically designed
for high ambient temperature operation should not be tested at 25
[deg]C. (NEMA, No. 9 at p. 3)
DOE understands the concerns of interested parties, but believes
that it is important to establish test procedures that provide a
consistent set of measurements. That is, DOE believes that adopting a
consistent rating condition across all CFL models will make the results
more comparable among CFL models.
c. Input Voltage
In the July 2015 NOPR, DOE proposed that if rated input voltage is
a range that includes 120 volts (V), the CFL must be operated at 120 V
when conducting the DOE test procedures. If the CFL can be operated
with multiple rated input voltages and is not rated for 120 V, the CFL
must be operated at the highest rated input voltage. DOE determined
that requiring testing at a single input voltage would limit testing
variation and ensure more accurate and consistent measurements of time
to failure (see sections III.A.3.a and III.A.4.b). In addition, section
5.1.1 of IES LM-65-14 specifies that when the rated input voltage of a
lamp or ballast is a range, a nominal value should be selected for
lifetime testing and reported as a test condition. 80 FR 45732. NEMA
supported DOE's proposal regarding testing input voltage. (NEMA, No. 9
at p. 3) DOE received no other comments regarding input voltage. In
this final rule, DOE adopts a testing voltage requirement that if a
rated input voltage is a range that includes 120 V, the CFL must be
operated at 120 V. If the CFL with multiple rated input voltages is not
rated for 120 V, the CFL must be operated at the highest rated input
voltage.
d. Lamp Orientation
In the July 2015 NOPR, DOE proposed a clarification that lamp
orientation must be maintained throughout all testing, including
preparation (e.g., seasoning and preburning), storage, and handling
between tests. The intent of DOE's proposal was to minimize changes in
lamp operating characteristics between various stages of testing and
allow for more accurate and repeatable measurements. 80 FR 45732. NEMA
supported DOE's proposal of maintaining lamp orientation. (NEMA, No. 9
at p. 3) DOE received no other comments regarding lamp orientation.
[[Page 59391]]
In this final rule, DOE adopts a requirement that lamp orientation must
be maintained throughout all testing, including preparation (e.g.,
seasoning and preburning), storage, and handling between tests.
e. Lamp Seasoning
In the July 2015 NOPR, DOE proposed that the seasoning requirements
in IES LM-54-12 must be followed prior to the testing of all CFLs. DOE
also proposed two additional provisions related to lamp seasoning.
First, DOE proposed that unit operating time during seasoning may be
counted toward lumen maintenance at 1,000 hours, lumen maintenance at
40 percent of lifetime, and time to failure if the required operating
cycle and test conditions are satisfied as stated in the test method
for time to failure. This would reduce testing burden by minimizing the
overall testing time required for measuring time to failure and lumen
maintenance values. Second, DOE proposed to require that, if a lamp
breaks, becomes defective, fails to stabilize, exhibits abnormal
behavior such as swirling prior to the end of the seasoning period, or
stops producing light, the lamp must be replaced with a new unit. 80 FR
45732.
NEMA was supportive of the proposed seasoning requirements. (NEMA,
No. 9 at p. 3) DOE received several comments regarding its proposal
that a lamp that fails during seasoning should not be included in the
sample set to determine the represented value of metrics. DOE addresses
these comments in section III.H.6.
In this final rule, DOE adopts the clarifications regarding
seasoning as noted in this section. As previously stated in section
III.A.1, to provide consistency in test methodology, DOE also requires
in this final rule that lamps must be cycled during seasoning for all
measurements and specifies an operating cycle of 180 minutes on and 20
minutes off in accordance with section 6.4 of IES LM-65-14.
f. Lamp Stabilization
In the July 2015 NOPR, DOE proposed to disallow the ``peak'' method
provided in Annex B of IES LM-66-14, which can serve as a time saving
alternative to the stabilization method specified in section 6.2.1 of
IES LM-66-14. IES LM-66-14 states that the information in the Annex is
not intended to be a recommended procedure, but is presented as
reference information; it also notes that the stabilization method
specified in section 6.2.1 is preferred because considerable testing
and experience with a given lamp design may be required due to the
number of lamp designs and process variations that exist when
conducting the peak according to Annex B. Because of the variabilities
that could arise from testing using the peak method, DOE concluded that
the peak method could cause inconsistent and potentially inaccurate
results. 80 FR 45732.
NEMA supported DOE's proposal. (NEMA, No. 9 at p. 3) DOE received
no other comments regarding the ``peak'' method for stabilization. In
this final rule, DOE disallows the ``peak'' method provided for
reference in Annex B of IES LM-66-14.
g. Simulated Fixtures During Time to Failure Testing
In the July 2015 NOPR, DOE proposed not to allow the use of
simulated fixtures during time to failure testing of CFLs. This
proposal would remove potential variation in the testing of CFLs and
ensure that all CFLs are tested in a consistent manner. 80 FR 45732.
NEMA supported this proposal. (NEMA, No. 9 at p. 3) DOE received no
other comments regarding testing of lamps in fixtures. In this final
rule, DOE disallows the use of simulated fixtures during time to
failure testing of CFLs.
h. Ballasted Adapters
In the July 2015 NOPR, DOE proposed that CFLs packaged with or
designed exclusively for use with ballasted adapters must be tested as
non-integrated CFLs, without the inclusion of the ballasted adapter.
DOE proposed to define a ``ballasted adapter'' as a ballast that is not
permanently attached to a CFL, has no consumer-replaceable components,
and serves as an adapter by incorporating both a lamp socket and a lamp
base. 80 FR 45732.
NEMA agreed with the proposed term ``ballasted adapter.'' (NEMA,
No. 9 at p. 3) DOE received no other comments regarding the definition
for ``ballast adapter.'' In this final rule, DOE adopts the proposed
definition for the term ``ballasted adapter.''
DOE also received comments related to the inclusion of screw-base
ballasted adapters for non-integrated CFLs. NEMA, OSI, and Philips
stated that screw-base ballasted adapters for non-integrated CFLs
should not be part of the CFL test procedure, but rather addressed in
the fluorescent lamp ballast (FLB) rulemaking.\11\ (NEMA, No. 9 at p.
2; OSI, No. 5 at p. 2; Philips, No. 6 at p. 3) DOE notes that it is not
proposing a test procedure for ballasted adapters in this rulemaking,
only a test procedure for compact fluorescent lamps.
---------------------------------------------------------------------------
\11\ Information regarding the Fluorescent Lamps Ballast
Rulemaking can be found at https://www.regulations.gov/docket?D=EERE-2015-BT-STD-0006.
---------------------------------------------------------------------------
Philips disagreed with DOE's proposal that CFLs, packaged with or
designed exclusively for use with ballasted adapters, must be tested as
non-integrated CFLs, without the inclusion of the ballasted adapter.
Instead, Philips recommended that a ballasted adapter sold with a lamp
should be tested as a system and the system should be subject to the
same energy conservation standards as integrated lamps. (Philips, No. 6
at p. 3)
DOE requires that non-integrated CFLs be tested on reference
ballasts as specified in IES LM-66-14. This ensures consistent test
conditions for measuring the performance characteristics of non-
integrated CFLs that are externally ballasted. As noted in this
preamble, DOE defines ballasted adapter as a component that is not
permanently attached to the CFL, and therefore is similar to the
external ballasts used with non-integrated CFLs. DOE reviewed CFLs that
are compatible with ballasted adapters and determined that there was no
technical reason they could not be tested on a reference ballast.
Further, although the CFL may be packaged with a certain ballasted
adapter, a consumer could choose to replace it with a different
ballasted adapter or a manufacturer could pair the same lamp with
different ballasted adapters. Thus, use of a reference ballast allows
for a consistent and comparable assessment of the lamp's performance.
Therefore, DOE continues to require that CFLs packaged with or designed
exclusively for use with ballasted adapters be tested as non-integrated
CFLs.
i. Multi-Level CFLs and Dimmable CFLs
Footnote 2 to the energy conservation standards for MBCFLs codified
at 10 CFR 430.32(u) includes the statement that for multi-level or
dimmable systems, measurements shall be at the highest setting. In the
July 2015 NOPR, DOE proposed to remove the footnote in order to
consolidate testing requirements in the test procedure and add language
to the test procedure addressing dimmable CFLs in the general
instruction section of appendix W. The lumen output level and input
power can be adjusted for some CFLs (i.e., dimmable), and thus not
clarifying the input power for testing these lamps can introduce
testing variation. Therefore, to ensure consistent results, DOE
proposed that a dimmer not be used in the circuit and that all CFLs be
tested at the labeled wattage, which DOE defines as the highest wattage
[[Page 59392]]
marked on the lamp and/or lamp packaging (see section III.A.3.f for
further details on the labeled wattage). 80 FR 45732-4573.
NEMA and OSI agreed that testing should be conducted with no dimmer
in the circuit, but the CA IOUs proposed testing dimmable CFLs at
dimmed states in addition to full power. (NEMA, No. 9 at p. 4; OSI, No.
5 at p. 3; CA IOUs, No. 7 at p. 4) However, neither the current energy
conservation standards nor those proposed in the March 2016 NOPR
require measurements of performance of CFLs at dimmed levels.
Therefore, DOE is not establishing test procedures for CFLs to be
tested at such levels.
Both NEMA and OSI commented that CFL testing should be conducted at
labeled voltage (which is an independent variable), rather than at
labeled wattage (which is a dependent variable). (NEMA, No. 9 at pp. 3-
4; OSI, No. 5 at p. 3) DOE agrees that wattage is dependent on voltage
and understands that, during testing, the electrical characteristics of
the incoming power to the lamp would be adjusted to achieve a given
wattage. Because voltage and wattage are related quantities, DOE notes
that specifying either the voltage or wattage will achieve the same
result when testing a given lamp. DOE's specification that the lamp be
tested at the labeled wattage is intended to indicate that CFLs
specified for a range of wattages should be measured at the highest
wattage marked on the lamp. This is consistent with the existing test
specifications for CFL testing and DOE's proposed definition of
``labeled wattage,'' as discussed in section III.A.3.f.
In this final rule, DOE removes the text regarding multi-level or
dimmable systems from Sec. 430.32(u) and, instead, specifies in
appendix W that dimmable CFLs must be tested at their highest labeled
wattage. DOE believes specifying that a dimmer cannot be used in the
circuit is an unnecessary addition as DOE also specifies that dimmable
CFLs must be tested at their highest labeled wattage. DOE therefore
removes this direction in the final rule.
3. Clarifications to Definitions
a. Average Rated Life
In the July 2015 NOPR, DOE proposed to remove the term ``average
rated life'' and adopt the terms ``lifetime of a compact fluorescent
lamp'' and ``time to failure.'' The existing definition of ``average
rated life'' makes only general reference to the sample size for time
to failure testing. DOE believes the use of the word ``average'' in the
term ``average rated life'' may be confusing, and although defined in
appendix W, the term is not otherwise used in appendix W or in
specifications of existing MBCFL energy conservation standards.
Further, the term ``rated life'' is used as a descriptor in appendix W,
but is not defined. Therefore, DOE proposed to remove the term
``average rated life'' from appendix W and to add the definition
``lifetime of a compact fluorescent lamp'' at 10 CFR 430.2. 80 FR
45733. See section III.B.3 for more detail.
In the July 2015 NOPR, DOE also proposed to define ``time to
failure'' in appendix W to support the new definition of ``lifetime of
a compact fluorescent lamp'' specified in 10 CFR 430.2. ``Time to
failure'' in the context of CFLs is the time elapsed between first use
and the point at which the lamp fully extinguishes and no longer
creates light. 80 FR 45733.This definition aligns with the definition
of lamp failure in section 8.2 of ANSI/IES RP-16-14.\12\
---------------------------------------------------------------------------
\12\ Nomenclature and Definitions for Illuminating Engineering
(approved 2010).
---------------------------------------------------------------------------
The EEAs were supportive of DOE's proposed changes related to
lifetime, but recommended that the definition of ``time to failure'' be
the point at which the lumen output falls below 70 percent of initial
lumen output. The EEAs stated that 70 percent is a common threshold
within the lighting industry and addresses a situation where the CFL
starts, but does not provide sufficient light. (EEAs, No. 8 at p. 1)
DOE is only aware of 70 percent initial lumen output to
characterize lifetime of light-emitting diode (LED) lamps. This
determination is based on the understanding that the LED lamp has
reached the end of its useful life when it achieves a lumen maintenance
of 70 percent. In the June 3, 2014 supplemental notice of proposed
rulemaking (SNOPR), DOE concluded that there is no industry consensus
for how to characterize lifetime of LED lamps in terms of performance
metrics other than lumen maintenance. However, for other lighting
technologies, such as CFLs, industry standards define lamp lifetime as
the time at which 50 percent of tested samples stop producing light. 79
FR 32020, 32028. Therefore, in this final rule, DOE defines ``time to
failure'' as the time elapsed between first use and the point at which
the CFL ceases to produce measureable lumen output.
As noted in section III.A.1, DOE references IES LM-65-14 for
lifetime testing of CFLs. Section 3.0 of IES LM-65-14 specifies the
terms ``lamp failure,'' ``lamp life,'' and ``rated lamp life.''
However, DOE is specifically defining the terms, ``time to failure''
and ``lifetime of a compact fluorescent lamp'' (see section III.B.3) to
support its lifetime testing of CFLs and align with terminology used in
other DOE lamp test procedures. Although the definitions in section 3.0
of IES LM-65-14 are often analogous to DOE's adopted definitions for
time to failure and lifetime of a compact fluorescent lamp, to avoid
confusion regarding terminology when executing the lifetime test
procedure for CFLs, DOE proposed that section 3.0 of IES LM-65-14
should be disregarded and replaced with the DOE definitions used for
lifetime testing of CFLs. DOE did not receive any comments regarding
this proposal and adopts it in this final rule.
b. Initial Performance Values
DOE proposed in the July 2015 NOPR to (1) delete the term ``initial
performance values;'' (2) add a definition for the term ``initial lamp
efficacy;'' (3) add a definition for the term ``measured initial input
power;'' (4) delete the term ``rated luminous flux or rated lumen
output;'' and (5) add a definition for the term ``measured initial
lumen output.'' 80 FR 45733-45734. The new terms clarify the
measurement of CFL initial performance values, and eliminate the need
for the terms ``initial performance values'' and ``rated luminous flux
or rated lumen output.'' DOE did not receive any comments related to
deletion or addition of these terms. Therefore, in this final rule, DOE
removes the terms ``initial performance values'' and ``rated luminous
flux or rated lumen output,'' and adopts definitions for ``initial lamp
efficacy,'' ``measured initial input power,'' and ``measured initial
lumen output.''
c. Lumen Maintenance
In the July 2015NOPR, DOE proposed to amend the definition of
``lumen maintenance'' to clarify that calculated lumen maintenance
values are based on measured lumen output as the existing definition of
``lumen maintenance'' does not clearly distinguish between rated and
measured values. The DOE proposed to adopt the term ``lumen
maintenance'' in appendix W as the lumen output measured at a given
time in the life of the lamp and expressed as a percentage of the
measured initial lumen output. 80 FR 45734.
NEMA agreed with this clarification. (NEMA, No. 9 at p. 5) DOE did
not receive any other comments on the term ``lumen maintenance.'' In
this final rule, DOE adopts the term ``lumen maintenance'' and
definition as proposed in the July 2015 NOPR.
[[Page 59393]]
d. Rated Voltage
In appendix W, the term ``rated voltage'' is defined as meaning the
voltage marked on the lamp. As previously noted, in this final rule,
DOE requires measurement at the highest rated input voltage for lamps
rated at multiple input voltages not including 120 V (see section
III.A.2.c). In order to support this test condition, in this final
rule, DOE adds clarifying text to the definition of ``rated voltage.''
Specifically, in this final rule, DOE replaces the term ``rated
voltage'' with ``rated input voltage,'' defined as the voltage(s)
marked on the lamp as the intended operating voltage, or if not marked
on the lamp, 120 V.
e. Rated Supply Frequency
In the July 2015 NOPR, DOE proposed to remove from appendix W the
term ``rated supply frequency'' because appendix W does not use this
term. 80 FR 45734.
NEMA agreed with removing this term. (NEMA, No. 9 at p. 4) DOE did
not receive any other comments on removing ``rated supply frequency.''
In this final rule, DOE removes the term ``rated supply frequency''
from appendix W.
f. Rated Wattage
In the July 2015 NOPR, DOE proposed to change the term ``rated
wattage'' to ``labeled wattage'' and amend the definition to clarify
its applicability to multi-level (i.e., multi-power) and dimmable CFLs.
80 FR 45734. Currently, in appendix W ``rated wattage'' is defined as
the wattage marked on the lamp. The term is intended to denote the
wattage marked on the lamp that should be used to determine the
applicable minimum efficacy requirement for existing MBCFL energy
conservation standards as specified in 10 CFR 430.32(u). However, in
ANSI standards, the rated wattage is a targeted rather than actual
value and can sometimes differ from the value displayed on the lamp
packaging.
NEMA and OSI recommended DOE not remove the term ``rated wattage,''
which they stated is widely used and understood by the lighting
industry, and instead suggested adding the term ``ANSI rated wattage''
to differentiate the ANSI-based wattages. (NEMA, No. 9 at p. 5; OSI,
No. 5 at p. 4)
Although DOE understands that ``rated wattage'' is a commonly used
term in the lighting industry, DOE also notes that its meaning may
differ depending on the context in which it is used (i.e., referring to
wattages referenced in ANSI standards as opposed to the wattage listed
on the CFL). Using the term ``labeled wattage'' will avoid any
potential confusion when applying DOE's test procedures and align with
the definition of the term, which specifies it as the wattage marked on
the lamp. Therefore, in this final rule, DOE removes ``rated wattage''
and defines ``labeled wattage'' as the highest wattage marked on the
lamp and/or lamp packaging.
g. Self-Ballasted Compact Fluorescent Lamp
The term ``self-ballasted compact fluorescent lamp,'' as defined in
appendix W, means a CFL unit that incorporates, permanently enclosed,
all elements that are necessary for the starting and stable operation
of the lamp, and does not include any replaceable or interchangeable
parts. The terms self-ballasted CFL, integrally ballasted CFL, and
integrated CFL are used interchangeably in industry to identify a CFL
that contains all components necessary for the starting and stable
operation of the lamp, does not include any replaceable or
interchangeable parts, and is connected directly to a branch circuit
through an ANSI base and corresponding ANSI standard lamp-holder
(socket). Because DOE proposed to include test procedures for
additional categories of CFLs, including integrated and non-integrated
CFLs, in the July 2015 NOPR, DOE also proposed to define the mutually
exclusive terms ``integrated CFL'' and ``non-integrated CFL'' to
clearly differentiate the applicability of the relevant CFL test
procedures and energy conservation standards. Specifically, DOE
proposed to remove the definition of ``self-ballasted compact
fluorescent lamp'' and add a new definition for the term ``integrated
compact fluorescent lamp'' as an integrally ballasted CFL that contains
all components necessary for the starting and stable operation of the
lamp, does not include any replaceable or interchangeable parts, and is
connected directly to a branch circuit through an ANSI base and
corresponding ANSI standard lamp-holder (socket). DOE also proposed to
add a definition of ``non-integrated compact fluorescent lamp'' as ``a
compact fluorescent lamp that is not integrated.'' 80 FR 45734.
OSI and NEMA stated that the proposed definition for ``non-
integrated'' was unnecessarily broad and encompassed all CFLs that are
not integrated CFLs. OSI and NEMA instead suggested DOE incorporate the
following ANSI C78.901-2014 definition for non-integrated CFLs: a CFL
that has an ANSI pin base, does not incorporate a ballast, and appears
in ANSI C78.901-2014. (OSI, No. 5 at p. 5; NEMA, No. 9 at p. 5)
Additionally, during the public meeting held to discuss the July 2015
NOPR, OSI asked why the term ``integrated'' was chosen as opposed to
``self-ballasted.'' OSI also inquired about the use of the term ``pin
based'' in the context of ``non-integrated.'' (OSI, Public Meeting
Transcript, No. 4 at pp. 53-54) Philips responded that UL 1993 \13\
uses the term ``self-ballasted lamp'' and acknowledged that the IES
struggled with the terms when developing IES LM-65-14 and IES LM-66-14,
but ultimately both documents use the terms integrated and non-
integrated when appropriate. (Philips, Public Meeting Transcript, No. 4
at pp. 53-55)
---------------------------------------------------------------------------
\13\ UL. UL1993, ``Self-Ballasted Lamps and Lamp Adapters,''
https://ulstandards.ul.com/standard/?id=1993_4
---------------------------------------------------------------------------
The term ``integrated'' can be used across lamp technologies to
describe lamps that contain all the necessary components for operation,
and thereby provides consistency across DOE test procedures for lamps.
The term supports the March 2016 NOPR and the amended standards for
CFLKs, both of which apply to lamps that use ballasts as well as
drivers. Further, because this test procedure applies to all CFLs, it
is DOE's intent to set forth terminology that includes all CFL types.
Based on its review of products, DOE determined that a CFL is either
``integrated'' or ``non-integrated'' and intentionally defined the
terms to be mutually exclusive (i.e., a CFL can be either integrated or
non-integrated, but not both) and inclusive of all CFLs. Therefore, DOE
defines ``non-integrated compact fluorescent lamp'' to include any CFL
that does not meet the definition ``integrated compact fluorescent
lamp'' and does not limit this definition by base type or inclusion in
industry standard. Hence, in this final rule, DOE removes the
definition of ``self-ballasted compact fluorescent lamp'' and adds new
definitions for ``integrated compact fluorescent lamp'' and ``non-
integrated compact fluorescent lamp.''
4. Test Procedures for Existing and New Metrics
a. Test Procedures for Initial Lamp Efficacy, Lumen Maintenance, CCT,
CRI, and Power Factor
In the July 2015 NOPR, DOE proposed to continue to include test
procedures for measuring initial lamp efficacy and lumen maintenance
and add test procedures for measuring CCT, CRI, and power factor in
appendix W. DOE
[[Page 59394]]
proposed that the test procedures for initial lamp efficacy, lumen
maintenance at 1,000 hours, lumen maintenance at 40 percent of
lifetime, CCT, and CRI would apply to both integrated and non-
integrated lamps, although the test procedure for power factor would
only apply to integrated lamps. 80 FR 45735. The following sections
discuss these metrics and the related comments received.
Initial Lamp Efficacy and Lumen Maintenance
Although appendix W currently specifies a test procedure for
initial lamp efficacy and lumen maintenance, it does not explicitly
state how to measure and calculate initial lamp efficacy and lumen
maintenance values. In order to standardize the CFL test procedure and
the calculation of these values, DOE proposed that initial lamp
efficacy be determined as the measured initial lumen output divided by
the measured initial input power. DOE further proposed to reference IES
LM-66-14 for test conditions and setup to measure initial lamp
efficacy, lumen maintenance at 1,000 hours, and lumen maintenance at 40
percent of lifetime. 80 FR 45735. DOE did not receive any comments
regarding its proposals for initial lamp efficacy and therefore, in
this final rule, adopts them as described in the July 2015 NOPR.
Similarly, in the July 2015 NOPR, DOE proposed to calculate lumen
maintenance at 1,000 hours as measured lumen output at 1,000 hours
divided by the measured initial lumen output and to calculate lumen
maintenance at 40 percent of lifetime as the measured lumen output at
40 percent of lifetime of a compact fluorescent lamp divided by the
measured initial lumen output. 80 FR 45735.
DOE evaluated its existing energy conservation standards and
ongoing standards rulemakings for CFLs as well as FTC Lighting Facts
labeling and determined that a lumen maintenance at 1,000 hours metric
is not required for non-integrated CFLs. Therefore, in this final rule,
DOE is only adopting a test procedure for lumen maintenance at 1,000
hours for integrated CFLs.
GE and Philips commented during the public meeting for the July
2015 NOPR that logistical testing issues arise if the definition of
lifetime is changed to a measured quantity. GE and Philips postulated
that they could not measure lumen maintenance at 40 percent of measured
lifetime because the point at which lifetime is determined would be
later than the 40 percent of the lifetime measurement point. (GE,
Public Meeting Transcript, No, 4 at pp. 44-47; Philips, Public Meeting
Transcript, No. 4 at pp. 21-22) Both NEMA and OSI proposed measuring
lumen maintenance at 40 percent of a rated lifetime rather than the
lifetime measured as proposed by DOE. (NEMA, No 9 at pp. 4-5; OSI, No 5
at p. 4)
DOE acknowledges the logistical concerns about measuring lumen
maintenance at 40 percent of the lifetime of a CFL. In this final rule,
DOE is adopting that lumen maintenance at 40 percent of lifetime can be
an estimated value for initial certification of new basic models or
existing basic models when retesting is required until lifetime testing
is complete. As described in section 10 CFR 429.35(b), certification
reports must be submitted for CFLs and represented values of lifetime,
lumen maintenance at 40 percent of lifetime, life, and rapid cycle
stress test surviving units are estimated values until testing is
complete. Upon completion of lifetime testing, the next annual
certification report must include final values for these metrics based
on the actual represented value for lifetime. In this way, the time
required to test for lifetime, lumen maintenance at 40 percent of
lifetime, life, and rapid cycle stress will not delay the distribution
in commerce of a lamp. (See section III.G for further details on
certification reports.)
Although DOE is adopting test methods for lumen maintenance at 40
percent of lifetime for both integrated and non-integrated CFLs, DOE
notes that standards for lumen maintenance at 40 percent of lifetime
are only applicable for integrated CFLs, specifically MBCFLs. Lumen
maintenance at 40 percent of lifetime for non-integrated CFLs is only
required to the extent that manufacturers wish to make representations
regarding the lumen maintenance of their products or participate in the
voluntary ENERGY STAR program.
Correlated Color Temperature (CCT)
In the July 2015 NOPR, DOE proposed to establish a test procedure
for measuring CCT in appendix W. The term ``correlated color
temperature'' is defined in 10 CFR 430.2 as the absolute temperature of
a blackbody whose chromaticity most nearly resembles that of the light
source. DOE proposed adding the abbreviation ``CCT'' to this definition
as explained in section III.B.2. DOE further proposed that CCT be
measured and calculated in accordance with IES LM-66-14, which
references Commission Internationale de l'Eclariage (CIE) 15:2004 (3rd
edition), ``Colorimetry.'' 80 FR 45735. CIE 15:2004 was previously
incorporated by reference in a test procedure final rule published on
July 6, 2009 for general service fluorescent lamps, incandescent
reflector lamps (IRLs), and general service incandescent lamps (GSIL)
for appendix R (hereafter ``2009 GSFL, IRL, and GSIL Test Procedure'').
74 FR 31829, 31834.
Both the CA IOUs and the EEAs supported the proposed methodology to
measure CCT. (CA IOUs, No. 7. at pp. 3-4; EEAs, No. 8 at p. 4)
Likewise, NEMA had no issues with the proposed test procedure, but
noted that the proposed methodology would add measurements to the
existing requirements. (NEMA, No. 9 at p. 6) OSI added that the
additional measurements would have no regulatory benefit. (OSI, No. 5
at p. 5) Although DOE agrees with commenters that DOE has not set
standards or requirements regarding the CCT of CFLs, as noted
previously, this test procedure supports the FTC Lighting Facts
labeling requirements for lighting products, the ENERGY STAR Lamps
Specification V2.0 and the ENERGY STAR Luminaires Specification V2.0,
all of which require the CCT metric. Therefore, in this final rule, DOE
adopts the test procedure for CCT and incorporates CIE 15:2004 by
reference for appendix W as proposed in the July 2015 NOPR.
Color Rendering Index (CRI)
In the July 2015 NOPR, DOE proposed establishing a test procedure
for measuring CRI in appendix W. DOE proposed that CRI must be measured
and calculated in accordance with IES LM-66-14, which references CIE
13.3-1995, ``Method of Measuring and Specifying Colour Rendering
Properties of Light Sources.'' DOE also proposed to incorporate CIE
13.3-1995 by reference for appendix W. 80 FR 45735. CIE 13.3-1995 was
previously incorporated by reference for appendix R in the 2009 GSFL,
IRL, and GSIL Test Procedure.
The CA IOUs and EEAs supported the proposed test procedure for CRI.
(CA IOUs, No. 7 at pp. 3-4; EEAs, No. 8 at p. 4) NEMA and OSI expressed
the view that a CRI test method would have no regulatory benefit and
should not be included in the test method but agreed the proposed
methodology was appropriate for measuring CRI. (NEMA, No. 9 at p. 6;
OSI, No. 5 at p. 5) Philips commented that CRI should be excluded from
the test procedure, as the metric would not yield substantial energy
savings. (Philips, No. 6 at p. 3)
The EEAs proposed testing color under the new IES metric outlined
in IES TM-30-2015, IES Method for Evaluating Light Source Color
Rendition. (EEAs, No. 8 at p. 4) IES TM-
[[Page 59395]]
30-2015 is a new methodology for evaluating different color properties
than CRI.\14\ CRI is determined by comparing a specific set of eight
color samples and calculating the average term known as Ra.
In contrast, IES TM-30-2015 provides calculations and directions for
quantifying fidelity (Rf, which is the closeness to a
reference) and gamut (Rg, which is the increase or decrease
in chroma).
---------------------------------------------------------------------------
\14\ IES Method for Evaluating Light Source Color Rendition.
https://www.ies.org/store/product/ies-method-for-evaluating-light-source-color-rendition-3368.cfm.
---------------------------------------------------------------------------
DOE must specify test procedures in order to determine whether the
products comply with any relevant standards promulgated under EPCA. (42
U.S.C. 6295(s)) In the March 2016 NOPR, DOE proposed that MBCFLs have a
CRI of at least 80. 81 FR 14554. Additionally, ENERGY STAR Lamps
Specification V2.0 and Luminaire Specification V2.0 include a CRI
requirement. Therefore, in this final rule, DOE establishes a test
procedure for CRI and incorporates CIE 13.3-1995 by reference for
appendix W. As there are no existing standards for IES TM-30-2015 color
metrics for CFLs, nor were any proposed in the March 2016 NOPR, DOE is
not adopting test procedures to evaluate color metrics specified in IES
TM-30-2015 in this final rule.
In this final rule, DOE is adopting test methods for determining
CRI for both integrated and non-integrated CFLs. While DOE is only
adopting certification requirements for integrated CFLs when complying
with general service lamps standards, if adopted, DOE's test procedure
for CRI is applicable to all CFLs and must be used when making
representations. (As proposed in the March 2016 NOPR, 81 FR 14554) More
specifically, if a manufacturer of a non-integrated CFL decides to make
representations of CRI in its product literature, manufacturer
catalogues, labeling, or for voluntary energy-efficiency programs, the
manufacturer must use the DOE test procedure, including sampling plan.
Power Factor
In the July 2015 NOPR, DOE proposed a test procedure for measuring
power factor for integrated CFLs based on electrical measurements
conducted in accordance with section 5.0 of IES LM-66-14. DOE also
proposed to define power factor in appendix W as the measured root
square mean (RMS) input power (watts) divided by the product of the
measured RMS input voltage (volts) and the measured RMS input current
(amps). 80 FR 45735. DOE did not receive comments on the proposed
definition. In this final rule, DOE has modified the definition
slightly to align with the definition in ENERGY STAR. Therefore, DOE
adopts the following definition of power factor: power factor means the
measured input power (watts) divided by the product of the measured RMS
input voltage (volts) and the measured RMS input current (amps).
The CA IOUs and EEAs commented that they were supportive of the
requirement of testing power factor as well as the proposed approach.
(CA IOUs, No. 7 at pp. 4; EEAs, No. 8 at pp. 3-4) GE, Philips, NEMA,
and OSI commented that power factor should be excluded from the test
procedure, with Philips stating that the metric would not yield
substantial energy savings, and NEMA and OSI stating that it would have
no regulatory benefit. (GE, Public Meeting Transcript, No. 4 at pp.
140-142; OSI, No. 5 at p. 5; Philips, No. 6 at p. 3)
In the March 2016 NOPR, DOE proposed setting a minimum power factor
standard for MBCFLs. 81 FR 14528, 14554-14555 (March 17, 2016). DOE
notes that ENERGY STAR Lamps Specification V2.0 also includes a power
factor requirement. As power factor is required to demonstrate
compliance with the proposed GSL energy conservation standards and to
support the ENERGY STAR requirements, in this final rule, DOE is
establishing a test procedure for power factor.
GE, NEMA, OSI, and Philips commented that power factor is not
relevant to non-integrated CFLs because it is a metric specific to the
ballast. (GE, Public Meeting Transcript, No. 4 at pp. 140-142; NEMA,
No. 9 at p. 6; OSI, No. 5 at p. 5; Philips, No. 6 at p. 3) In response,
DOE clarifies that the power factor test procedure is only applicable
to integrated CFLs.
DOE also received a comment from the CA IOUs recommending that DOE
consider requiring the measurement and reporting of total harmonic
distortion of current (abbreviated as THD in the comment). (CA IOUs,
No. 5 at p. 4) In the March 2016 NOPR, DOE stated that THD is directly
related to power factor and a power factor requirement will effectively
establish a standard for THD. 81 FR 14555-14556. Therefore, DOE is not
adopting a test procedure for total harmonic distortion of current in
this final rule.
b. Test Procedures for Time to Failure
In the July 2015 NOPR, DOE proposed test procedures for measuring
time to failure in appendix W for integrated and non-integrated CFLs.
80 FR 45735. DOE determined that test conditions, setup, and
measurement of time to failure should be as specified in IES LM-65-14.
DOE also proposed that use of simulated fixtures during time to failure
testing of CFLs not be allowed. This proposed provision was to prevent
potential variation in testing of CFLs and to ensure that all CFLs are
tested in a consistent manner. 80 FR 45732. NEMA agreed with DOE's
proposal to disallow the use of simulated fixtures during time to
failure testing. (NEMA, No. 9 at p. 3)
OSI requested that DOE not include lifetime testing for pin base
CFLs in the test procedure, noting that initial lamp efficacy is
sufficient for reporting metrics of these lamp types. (OSI, No. 5 at p.
2) NEMA agreed with OSI that DOE should not include lifetime testing
for pin base CFLs. NEMA also stated that lifetime testing would depend
on the ballast operating the non-integrated CFL. (NEMA, No. 9 at pp. 2,
6)
DOE agrees with NEMA that the specific ballast used affects the
lifetime of non-integrated CFLs; however, the characteristics of the
lamp also affect this metric. Further, manufacturer catalogs specify
the lifetime of non-integrated CFL products and lifetime is also
required by ENERGY STAR Luminaires Specification V2.0. Therefore, DOE
finds that lifetime is an important characteristic of the performance
of the non-integrated CFL. Additionally, by using reference ballasts
when testing non-integrated CFLs, DOE is able to assess the performance
of the non-integrated CFL in a comparable and standardized way across
all non-integrated lamps. In this final rule, DOE adopts the proposed
test procedures for time to failure for integrated and non-integrated
CFLs to be used to determine lifetime.
c. Test Procedure for Rapid Cycle Stress Test
In the July 2015 NOPR, DOE proposed test procedures for conducting
rapid cycle stress testing for integrated and non-integrated CFLs. DOE
proposed that test conditions, setup, and rapid cycle stress testing be
as specified in IES LM-65-14, but retained the existing operating cycle
for rapid cycle stress testing (i.e., CFLs must be cycled continuously
with each cycle consisting of one 5-minute on period followed by one 5-
minute off period). 80 FR 45735. DOE did not propose any modifications
to the rapid cycle stress test itself, but did propose modifications to
rounding requirements (see section III.A.7), removal of test procedure
language from the energy conservation standard
[[Page 59396]]
requirements (see section III.F.4), and modifications to sample size
(see section III.H.2) for this test.
DOE received comments that rapid cycle stress testing should not be
applied to non-integrated CFLs. GE commented that rapid cycle stress
testing should not apply to non-integrated CFLs because it is dependent
on the ballast paired with the lamp. (GE, Public Meeting Transcript,
No. 4 at pp. 140-142) OSI added that rapid cycle stress testing was
designed to stress the ballast and not applicable to non-integrated
CFLs. (OSI, No. 5 at pp. 2, 5) NEMA supported the test procedure for
rapid cycle stress testing with the clarification that the test
procedure should not apply to non-integrated CFLs. (NEMA, No. 9 at p.
6) Philips also stated that non-integrated CFLs be excluded from rapid
cycle stress test and questioned the energy savings aspects related to
measuring rapid cycle stress test. (Philips, No. 6 at p. 3)
In light of the comments received from interested parties, DOE
evaluated its existing energy conservation standards and ongoing
standards rulemakings as well as FTC Lighting Facts labeling and ENERGY
STAR specifications and determined that rapid cycle stress testing of
non-integrated CFLs is not required by any of these regulatory and non-
regulatory programs. Therefore, DOE is not adopting a test procedure
for rapid cycle stress testing of non-integrated CFLs. DOE notes,
however, that the existing standards for MBCFLs, the proposed standards
in the March 2016 NOPR, and the ENERGY STAR Lamps Specification V2.0
all contain a requirement for rapid cycle stress testing for MBCFLs.
Therefore, DOE retains the test procedure for rapid cycle stress
testing for integrated CFLs.
d. Test Procedure for Start Time
In the July 2015 NOPR, DOE proposed a test procedure for measuring
start time for integrated CFLs. In support of the proposed start time
test method, DOE defined the terms ``start time,'' ``start plateau,''
and ``percent variability.'' DOE also proposed that the lamp be
seasoned, stored at a certain temperature, and tested according to a
certain operating procedure following the seasoning. 80 FR 45735-45736.
DOE received comments regarding the applicability of the start time
metric. NEMA, OSI, and Philips stated that start time is not related to
energy efficiency and should not be part of the test procedure. (NEMA,
No. 9 at pp. 6,8; OSI, No. 5 at p. 5; Philips, No. 6 at p. 3) NEMA and
OSI stated that DOE should abandon the effort to create a test
procedure for start time. (NEMA, No. 9 at p. 6; OSI, No. 5 at p. 5) GE,
NEMA, Philips, and OSI stated that start time is not applicable to non-
integrated CFLs. (GE, Public Meeting Transcript, No. 4 at pp. 140-142;
NEMA, No. 9 at p. 8; OSI, No. 5 at pp. 2,7; Philips, No. 6 at p. 3)
In the March 2016 NOPR, DOE proposed a requirement for start time
for MBCFLs that the lamp must remain continuously illuminated within
one second of application of electrical power. 81 FR 14528, 14555
(March 17, 2016). ENERGY STAR Lamps Specification V2.0 includes a
requirement for start time. DOE notes that because the ongoing GSL
rulemaking considered a start time metric for only integrated CFLs, the
July 2015 NOPR proposed measuring start time for only integrated CFLs.
80 FR 45736. In this final rule, DOE continues to specify that only
integrated lamps must be tested for start time.
DOE received several comments regarding the proposed definitions
and test procedures for start time. The CA IOUs agreed with the
proposed methods for start time outlined in the July 2015 NOPR. (CA
IOUs, No. 7 at pp. 3-4) The EEAs stated that they supported DOE's test
procedures for start plateau, percent variability, and start time as
long as they are fully consistent with the ENERGY STAR test procedure
for start time. (EEAs, No. 8 at p. 4)
If DOE were to require measuring and reporting start time, OSI
suggested using the ENERGY STAR procedure, which it stated is well
understood. (OSI, No. 5 at p. 5) NEMA noted that although the ENERGY
STAR test procedure for start time is well understood, it should not be
required for lamps that are not ENERGY STAR certified. (NEMA, No. 9 at
p. 6) Both Philips and Westinghouse commented that DOE's proposed start
time procedure seemed overly complicated, and requested that DOE
harmonize with or simply adopt the ENERGY STAR test procedure.
(Philips, Public Meeting Transcript, No. 4 at p. 65; Westinghouse,
Public Meeting Transcript, No. 4 at pp. 66-67)
When developing the start time test procedure, DOE reviewed the
August 2013 ``ENERGY STAR Program Requirements Product Specification
for Lamps Version 1.0: Start Time Test Method.'' \15\ ENERGY STAR
released ``ENERGY STAR Program Requirements for Lamps and Luminaires
Start Time Test Method'' \16\ in September 2015 (hereafter ``ENERGY
STAR Start Time Test Method''). For this final rule, DOE reviewed the
latest version of the ENERGY STAR Start Time Test Methods and
determined that the only differences between the two methods are the
applicable products and referenced documents.\17\
---------------------------------------------------------------------------
\15\ ENERGY STAR[supreg] Program Requirements Product
Specification for Lamps Version 1.0: Start Time Test Method. August
2013. www.energystar.gov/sites/default/files/specs//ENERGY%20STAR%20Lamps%20V1%200%20Final%20Test%20Methods%20and%20Recommended%20Practices.pdf.
\16\ ENERGY STAR[supreg] Program Requirements for Lamps and
Luminaires Start Time Test Method. September 2015. https://www.energystar.gov/sites/default/files/ENERGY%20STAR%20Start%20Time%20Test%20Method_1.pdf.
\17\ The August 2013 ENERGY STAR Start Time Test Method applied
to integrated CFLs and solid-state lighting (SSL) lamps. In
contrast, the September 2015 ENERGY STAR Start Time Test Method
applies to all integrated and externally ballasted CFLs, and SSL
lamps, light engines, and luminaires. Both versions referenced IES
LM-66, ``IES Approved Method for Electrical and Photometric
Measurements of Single-Based Compact Fluorescent Lamps.'' However,
the August 2013 ENERGY STAR Start Time Test Method referenced the
2011 version of IES LM-66 and the latest version references the 2014
version of IES LM-66.
---------------------------------------------------------------------------
DOE determined that its proposed start time test method continues
to align with the ENERGY STAR Start Time Test Method, while providing
greater specificity in order to ensure consistency and reproducibility
in measurements. (DOE also notes section 11.4 of ENERGY STAR Lamps
Specification V2.0 references the DOE test procedure for compact
fluorescent lamps (once final) for measuring start time of fluorescent
lamps.) The following sections describe how the proposed definitions
and test procedures for start time harmonize with the ENERGY STAR Start
Time Test Methods as well as amendments to these proposals that provide
further simplification and clarity.
Definitions
In the July 2015 NOPR, DOE proposed definitions for the terms
``start plateau,'' ``percent variability,'' and ``start time.'' 80 FR
45754. DOE proposed to define the term ``start plateau'' as the first
100 millisecond period of operation during which the percent
variability does not exceed 5 percent and the average measured lumen
output is at least 10 percent of the measured initial lumen output. 80
FR 45736. This definition aligns with ENERGY STAR's definition of
``initial plateau'' as ``the point at which the average increase in the
light output over time levels out (reduces in slope). This can be
determined mathematically or visually based on the lamp output trace.''
Both definitions are intended to describe a time interval in which
the light output is relatively steady. ENERGY STAR does not specify the
[[Page 59397]]
method by which such a time interval should be quantitatively and
objectively determined. In order to ensure consistent and reproducible
measurements, DOE's proposed definition specifies the time period over
which lumen output should be steady as 100 milliseconds and described
the criteria for light output that must be met during this time period.
DOE selected 100 milliseconds to evenly capture either 5 or 6 full
cycles of the sampled waveform (for 50 or 60 Hz input voltage,
respectively). 80 FR 45736. Section 5.4 of IES LM-28-12 states that by
choosing the integrating time to be a multiple of the period of the
line frequency (16.67 milliseconds for 60 Hz), for example, 100
milliseconds (6 line cycles for 60 Hz and 5 line cycles for 50 Hz), the
effect of flicker for either line frequency can be removed. Id.
Regarding the criteria for determining stability of light output
during the first 100 milliseconds, DOE proposed that the percent
variability not exceed 5 percent and that the average measured lumen
output over the time interval should be at least 10 percent of the
measured initial lumen output. The first criterion is intended to
quantify when the light output can be deemed ``stable.'' DOE determined
that the criterion that the percent variability cannot exceed 5 percent
is sufficient to capture a 100 millisecond interval in which light
output is steady and subsequently determine an appropriate start time.
The second criterion is intended to capture the time at which light
output is first detected for a continuous period and ensure that light
is actually being created from the lamp (e.g., a stable output of zero
if the lamp fails to turn on is not acceptable).
In re-evaluating the latter criterion, DOE found that requiring a
specific threshold of light output is unnecessary for the start time
metric. According to the test procedures established in this final
rule, measured initial lumen output must be determined using the
integrating sphere method. Therefore, for comparison purposes, the
average lumen output in a 100 millisecond span that occurs during the
initial operation of the lamp must also be determined using the
integrating sphere method. However, DOE has determined that, due to the
precision of the measurement, the integrating sphere may require
reconfiguration and additional setup to measure the lumen output in the
initial milliseconds of lamp operation. DOE has determined that
including the latter criterion does not merit requiring a potentially
complex test setup. Removing this criterion would allow for start time
testing to be conducted using either an integrating sphere or non-
integrating sphere method such as a photodetector. Therefore, in this
final rule, DOE defines ``start plateau'' to mean ``the first 100
millisecond period of operation during which the percent variability
does not exceed 5 percent.''
To provide further clarity to the definition of ``start plateau,''
DOE proposed to define the term ``percent variability'' as the range
(calculated by subtracting the minimum from the maximum) expressed ``as
a percentage of the mean for the contiguous set of separate lumen
output measurements spanning the specified time period, where each
lumen output measurement is the average value of the sampled waveform
over an interval corresponding to one full cycle of sinusoidal input
voltage.'' 80 FR 45736.
Because DOE is no longer requiring lumen measurements to determine
start plateau, percent variability also does not have to be based on
lumen output. Therefore, DOE is replacing the specification of lumen
output measurements with light output values. Additionally, DOE is
providing a clearer description of calculating a time-average of
measured light output values. In summary, in this final rule, DOE is
specifying ``percent variability'' to be ``the result of dividing the
difference between the maximum and minimum values by the average value
for a contiguous set of separate time-averaged light output values
spanning the specified time period. For a waveform of measured light
output values, the time-averaged light output is computed over one full
cycle of sinusoidal input voltage, as a moving average where the
measurement interval is incremented by one sample for each successive
measurement value.''
In the July 2015 NOPR, DOE proposed to define the term ``start
time'' as the time, measured in milliseconds, between the application
of power to the CFL and the point when the measured full-cycle lumen
output (the average value of the sampled waveform over an interval
corresponding to one full cycle of sinusoidal input voltage) reaches 98
percent of the average measured lumen output of the start plateau. 80
FR 45754. ENERGY STAR defines start time as ``the time between the
application of power to the device and the point where light output
reaches 98% of the lamp's initial plateau.''
GE commented that from the consumer's perspective the simplest
definition for start time is the time between energizing the circuit
and the first light output. GE added that the specification of 97 or 96
percent of the plateau was not distinguishable. (GE, Public Meeting
Transcript, No. 4 at pp. 68-70)
ENERGY STAR Lamps Specification V2.0 describes start time as the
time for a lamp to remain continuously illuminated after applying
electrical power. DOE agrees that the start time metric is intended to
capture the time of detection of first continuous light output. Hence,
the 98 percent threshold is not necessary for representative
measurements of start time. Therefore, in this final rule, DOE removes
this element from the definition of start time. Additionally, DOE
provides a clearer description of the point at which start time should
be determined. In summary, DOE defines ``start time'' to mean ``the
time, measured in milliseconds, between the application of power to the
CFL and the beginning of the start plateau.''
Lamp Storage/Operating Cycle Post Seasoning
In the July 2015 NOPR, DOE proposed that, after seasoning, units
must be stored at 25 5 [deg]C ambient temperature for a
minimum of 16 hours prior to testing, after which the ambient
temperature must be 25 1 [deg]C for a minimum of 2 hours
prior to testing. DOE also determined that any units that have been off
for more than 24 hours must be operated for 3 hours and then be turned
off for 16 to 24 hours prior to testing. 80 FR 45736. ENERGY STAR Start
Time Test Method prescribes similar specifications with the time period
characterized as 20 4 hours.
During the public meeting for the July 2015 NOPR, OSI stated that
16 hours after the lamp is seasoned before testing was atypical for its
test laboratories and based on this schedule the time that testing
could begin would be outside the normal work schedule. OSI added that
the rationale for the 16 hours after seasoning was not well understood.
(OSI, Public Meeting Transcript, No. 4 at pp. 73-74) During the public
meeting, DOE noted that the proposed storage and operating cycle post
seasoning requirements were consistent with ENERGY STAR. (DOE, Public
Meeting Transcript, No. 4 at p. 75) OSI acknowledged the ENERGY STAR
specification of the 16 hour period, but, stated that ENERGY STAR
testing does not represent all of the testing that OSI conducts because
not all of their products are submitted to ENERGY STAR. OSI elaborated
they did not have a technical justification for or against the time
period, but that it could be a potential cost burden. (OSI, Public
Meeting Transcript, No. 4 at p. 74) Westinghouse Lighting
(Westinghouse) added that the scheduling and
[[Page 59398]]
subsequent cost issues described by OSI are even more pronounced for
them because they use an independent testing laboratory where not all
Westinghouse products may be tested at the same time. (Westinghouse,
Public Meeting Transcript, No. 4 at pp. 74-76)
The proposed operating cycle ensures that the lamp has been
seasoned and recently operated, but not so recently that elements in
the recent operation of the lamp could directly affect start time. DOE
does clarify in this final rule that the 3 hours that the unit must be
operated after being off for more than 24 hours is a minimum of 3
hours. This specification is mainly for clarification purposes; DOE
does not find that operating the lamp for a longer period would affect
the start time testing. Any units that have been off for more than 24
hours must be operated for a minimum of 3.0 hours and then be turned
off for 16 to 24 hours prior to testing. DOE notes that the range of 16
to 24 hours in the off state provides an 8 hour range during which
start time testing may begin, which should allow it to be conducted
during normal working hours. Therefore, DOE adopts the proposed
operating cycle and ambient temperature requirements described in this
final rule.
Testing Methodology
For test setup and conditions for measuring start time, DOE
proposed in the July 2015 NOPR to reference IES LM-66-14 and IES LM-54-
12. 80 FR 45735-45736. DOE proposed to adopt the measurement circuit
requirements as specified in section 5.2 of IES LM-66-14 and that lumen
output measurements be taken as specified in section 6.3.1 of IES LM-
66-14. DOE also proposed to adopt seasoning specifications as provided
in sections 4, 5, 6.1, 6.2.2.1of IES LM-54-12. 80 FR 45736. Further,
DOE proposed that a multichannel oscilloscope with data storage
capability be connected to record the input voltage to the CFL and its
lumen output. DOE specified that the oscilloscope must be set to
trigger at 10 V lamp input voltage, to have the vertical scale set at a
vertical resolution that is 1 percent of measured initial lumen output
or finer, and to be set to sample the lumen output waveform at a
minimum rate of 2 kHz. Id.
The proposed test setup and conditions generally align with those
specified by ENERGY STAR. Section 4(B) of the ENERGY STAR Start Time
Test Method references IES LM-66-14 and IES LM-54-12. Section 5.A(2) of
the ENERGY STAR Start Time Test Method requires a multichannel
oscilloscope with data storage capability and section 7.1(F) also
requires to set the trigger level at 10 V. DOE's proposal for a minimum
2 kHz sampling rate is also consistent with the ENERGY STAR requirement
for flicker testing,\18\ and DOE understands that this requirement
would also provide sufficient horizontal resolution for start time
testing. DOE did not receive any comments specific to the proposed test
setup and conditions for start time. In this final rule, DOE adopts the
test setup and conditions as proposed in the July 2015 NOPR.
---------------------------------------------------------------------------
\18\ ENERGY STAR[supreg] Program Requirements Product
Specification for Lamps Version 1.0--Light Source Flicker
Recommended Practice. August 2013. Washington, DC.
www.energystar.gov/sites/default/files/specs//ENERGY%20STAR%20
Lamps%20V1%200%20Final%20
Test%20Methods%20and%20Recommended%20Practices.pdf.
---------------------------------------------------------------------------
In the July 2015 NOPR, DOE also proposed that upon the trigger for
start time testing, the sampled lumen output waveform must be recorded
until the measured lumen output has reached the start plateau. 80 FR
45736. In addition, DOE proposed in the NOPR that the trace of full-
cycle lumen output must be calculated as a moving average, whereby
values are determined at least once every millisecond and each value
represents the full-cycle interval in which it is centered. Id. The
August 2013 ENERGY STAR Start Time Test Method provides an example of a
light output trace for compact fluorescent lamps. Aligning with ENERGY
STAR, DOE's proposed steps provide specifics on recording such a light
output trace and how time-averaged values from the light output trace
should be calculated. Specifically, in this final rule, DOE states
that, upon the trigger for start time testing, the sampled light output
must be recorded until the start plateau (as defined in this section)
has been determined. Additionally, in this final rule, to determine the
``percent variability'' of light output in accordance with the start
plateau definition, DOE requires calculation of a time-averaged light
output value at least once every millisecond where each value
represents the full-cycle interval in which it is centered. DOE further
specifies that, for a waveform of measured light output values, the
time-averaged light output is computed over one full cycle of
sinusoidal input voltage, as a moving average where the measurement
interval is incremented by one sample for each successive measurement
value.
Lamp Orientation
In the July 2015 NOPR, DOE proposed that all units be tested in the
base up position, but that if the position is restricted by the
manufacturer, units would be tested in the manufacturer specified
position. 80 FR 45755. Section 5(H) of the September 2015 ENERGY STAR
Start Time Test Method states the samples be tested in the
orientation(s) as specified by the ENERGY STAR specification or
manufacturer specified position if different. It should be noted that
ENERGY STAR Lamps Specification V2.0 does not state the testing
orientation in section 11.4, Start Time. However, for purposes of
consistency, DOE proposed that all units for start time be tested in
the base up position, but that if the position is restricted by the
manufacturer, units must be tested in the manufacturer specified
position. DOE did not receive any comments specific to lamp orientation
for start time; and in this final rule adopts the sample unit
orientation specification.
Hybrid Lamps
In the July 2015 NOPR, DOE proposed measuring only integrated CFLs
for start time, which would include hybrid lamps. 80 FR 45755. DOE also
proposed that hybrid CFLs must be tested with all supplemental light
sources turned off, if possible. 80 FR 45737.
The EEAs cautioned that having the supplemental light source off
during testing could yield inaccurate test results for start time
testing. (EEAs, No. 8 at p. 3) NEMA requested the start time test
procedure not apply to hybrid CFLs or to not require that the
supplementary light source not be operating. (NEMA, No. 9 at p .7) GE
also requested that hybrid CFLs be exempt from start time testing
because it could lead to inaccurate results because one of the primary
functions of hybrid CFLs is to allow for quicker start time through the
supplemental light source. (GE, Public Meeting Transcript, No. 4 at pp.
59-60)
DOE has determined that hybrid lamps should not be exempt from the
start time test procedure. The March 2016 NOPR proposes a start time
metric for medium base CFLs. If a hybrid CFL meets the definition of
medium base CFL, then the applicable standard applies to the hybrid
CFL. Similarly, ENERGY STAR Lamps Specification V2.0 does not specify
different start time requirements for hybrid CFLs. DOE determined that
requiring the supplemental light source be off, if possible, is the
most consistent manner in which the various combinations of primary and
supplementary light sources in hybrid CFLs can be tested. Therefore, in
this final rule, DOE retains the requirement that hybrid CFLs be tested
for start time with the
[[Page 59399]]
supplemental light source turned off, if possible.
5. Test Procedures for New CFL Categories
a. Test Procedures for Integrated CFLs
In the July 2015 NOPR, DOE proposed test procedures for integrated
CFLs without exclusion of any base type. NEMA, OSI, and Philips
requested that DOE exclude E12 \19\ and GU24-based integrated lamps
from the test procedure. All three entities stated that lamps with
these bases represented a small portion of the market. (NEMA, No. 9 at
pp. 2,8; OSI, No. 5 at p. 7; Philips, No. 6 at p. 3) NEMA and OSI
further stated that if a particular lamp has the same technical
specifications across lamps with medium, E12, and GU24 base types, then
DOE should only require testing on MBCFLs. NEMA and OSI argued that
base type does not have any effect on lamp performance. (NEMA, No. 9 at
pp. 2, 6; OSI, No. 5 at pp. 2, 5)
---------------------------------------------------------------------------
\19\ DOE defines a candelabra base incandescent lamp in 10 CFR
430.2 as a lamp that uses a candelabra screw base as described in
ANSI C81.61, Specifications for Electric Bases, common designations
E11 and E12 . The base is not specific to the light source,
therefore a candelabra base lamp can be either an E11 or E12 base.
---------------------------------------------------------------------------
Regarding the applicability of the test procedure to integrated
lamps with certain base types, DOE notes that the March 2016 NOPR
proposed standards for GU24 base integrated lamps. 81 FR 14551.
Further, CFLK standards with required compliance in 2019 are applicable
to CFLKs packaged with CFLs of all base types. As both of these
standards will be supported by this test procedure, DOE is obligated to
establish test procedures for CFLs of all base types for the applicable
metrics addressed in those rules. Therefore, in this final rule, DOE
does not exclude E12 and GU24-base lamps from the test procedures for
integrated CFLs.
Regarding lamps that have the same technical specifications,
manufacturers must submit represented values of required metrics for
each basic model before distribution in commerce. 10 CFR 429.12(a).
Represented values of measures of energy efficiency or energy
consumption must be the same for all individual models represented by a
given basic model. 10 CFR 429.11(a). However, DOE provides
manufacturers with the flexibility to group individual models into
basic models for the purposes of certification to DOE, provided that
all representations regarding the energy efficiency or energy
consumption of CFLs within that basic model are identical and based on
the most consumptive unit. See 76 FR 12422, 12423 (March 7, 2011).
Therefore, it may be possible to group lamps that have the same
technical specifications but different base types into the same basic
model. However, all representations within a basic model must have
essentially identical electrical, physical, and functional
characteristics that affect energy efficiency (see definition of basic
model per 10 CFR 430.2). Accordingly, CFLs that are in separate product
classes and thereby subject to separate standards (e.g., integrated and
non-integrated CFLs) cannot be grouped in the same basic model. Also,
DOE does not believe it is appropriate to group models of lamps that
have different testing methods as defined in Appendix W into the same
basic model as they will not have essentially identical electrical
characteristics.
b. Test Procedures for Non-Integrated CFLs
In the July 2015 NOPR, DOE proposed test procedures for non-
integrated CFLs. Specifically, DOE proposed adopting section 5.2 of IES
LM-66-14 for electrical and photometric testing of non-integrated CFLs,
which specifies procedures for determining initial lamp efficacy, lumen
maintenance at 40 percent of lifetime, CRI, and CCT. 80 FR 45737. To
ensure repeatable and consistent measurements, DOE proposed that non-
integrated CFLs must be tested using the appropriate reference ballasts
as provided in section 5.2 of IES LM-66-14, which specifies using
reference ballasts specifications listed in ANSI C78.901-2014,
``American National Standard for Electric Lamps--Single-Based
Fluorescent Lamps--Dimensional and Electrical Characteristics,''
(hereafter ``ANSI C78.901-2014''). Id.
NEMA and OSI agreed with referencing ANSI C78.901-2014 to identify
reference ballasts for non-integrated CFLs, but also stated that
industry only has experience using reference ballasts for photometry.
(NEMA, No. 9 at pp. 6-7; OSI, No. 5 at pp. 5-6) Reference ballast
characteristics provide the necessary functionality to operate a non-
integrated CFL and a standardized and consistent method of testing non-
integrated CFLs. DOE does not find any technical reason why reference
ballasts cannot be used for non-photometric measurements. Therefore, in
this final rule, DOE requires using reference ballast specifications in
ANSI C78.901-2014 to test non-integrated CFLs for all measurements.
In the July 2015 NOPR, DOE noted that certain non-integrated CFL
designs do not have reference ballast specifications listed in ANSI
C78.901-2014. For these lamp designs, DOE proposed reference ballast
specifications. In cases where there are no reference ballast
specifications for a lower wattage CFL, DOE proposed the reference
ballast specifications of the corresponding full wattage version, if
they existed. For all other cases, DOE developed reference ballast
specifications by matching the shape, diameter, and base of the CFL
without reference ballast specifications to the most similar CFL with
specifications that also had the closest wattage. 80 FR 45737. For any
non-integrated CFLs that do not have a reference ballast listed in ANSI
C78.901-2014 and for which DOE has not specified reference ballast
characteristics in appendix W, DOE also specified two principles that
must be employed to determine the appropriate reference ballast
specifications. For such a lamp, DOE specified that, manufacturers must
use the specifications in ANSI C78.901 2014 for the higher wattage lamp
for which it is a replacement; otherwise, use the specifications in
ANSI C78.901 2014 for a lamp with the most similar shape, diameter, and
base specifications, and next closest wattage. OSI agreed with DOE's
proposal to address lamps for which reference ballast characteristics
are not specified. (OSI, No. 5 at pp. 5-6) In this final rule, DOE is
also specifying the appropriate frequency along with the reference
ballast values of current, impedance, and voltage.
To specify a consistent set of testing procedures for non-
integrated CFLs, in the July 2015 NOPR, DOE proposed several
clarifications and specifications regarding the circuits on which the
lamps must be tested. 80 FR 45737. DOE proposed to test non-integrated
CFLs rated for operation on a choice of low frequency or high frequency
circuits at low frequency only. Id.
GE, NEMA, and OSI stated they were unaware of any dual-frequency
reference ballast specifications. (GE, Public Meeting Transcript, No. 4
at pp. 56-57; NEMA, No. 9 at pp. 6-7; OSI, No. 5 at p. 6) NEMA and OSI
suggested that DOE require testing at the manufacturer-specified
frequency. (NEMA, No. 9 at pp. 6-7; OSI, No. 5 at p. 6) GE stated that,
because these products are operating at high frequency in application,
testing them at low frequency reference conditions when high frequency
reference conditions are available would misrepresent their efficacy.
(GE, Public Meeting Transcript, No. 4 at pp. 56-57)
As noted previously, in order to establish a set of consistent
[[Page 59400]]
specifications and conditions and to follow industry standards for
testing non-integrated CFLs, in this final rule, DOE is requiring the
use of ANSI C78.901-2014 for reference ballast values per IES LM-66-14.
There are certain lamps for which ANSI C78.901-2014 provides details
for both low and high frequency operation. For example, a 36 W T5
single-based fluorescent lamp on datasheet 78901-ANSI-4019-1 provides
reference ballast characteristics for low frequency operation and also
information on high frequency ballast design. Manufacturers must use
the values designated as ``reference ballast characteristics'' when
testing lamps. If more than one set of values is designated as
``reference ballast characteristics,'' then manufacturers must use the
values designated for low frequency operation. DOE reviewed the
reference ballast specifications for non-integrated CFLs and found that
the majority are specified for low frequency operation. Therefore, in
this final rule, in order to maintain consistency and comparability
across testing, DOE continues to require operating on low frequency
where reference ballast characteristics for both low and high frequency
operation are provided.
DOE also proposed in the July 2015 NOPR that non-integrated CFLs
rated for multiple circuits including rapid start (i.e., rapid start
and either preheat start or instant start) be tested on rapid start
circuits when rapid circuits are an option to ensure consistent
measurements. 80 FR 45737.
NEMA and OSI disagreed with the requirement to use rapid start
circuits. Both NEMA and OSI stated that rapid start circuits have not
typically been used in testing of non-integrated CFLs and expressed
concerns regarding how the testing would relate to certification,
compliance, and enforcement. (NEMA, No. 9 at pp. 6-7; OSI, No. 5 at p.
6) GE indicated that a rapid start circuit would include cathode heat
while use of a programmed start circuit would exclude cathode heat. GE
explained that testing without cathode heat is the most representative
of the current applications. GE further added that including cathode
heat would decrease the apparent lamp efficacy, and not be reflective
of how the product is used. (GE, Public Meeting Transcript, No. 4 at
pp. 56-58)
In reviewing the reference circuits specified for lamps, DOE has
decided to modify its proposed specifications for reference circuits on
which non-integrated CFLs must be tested in this final rule. In the
July 2015 NOPR, DOE proposed to specify that a rapid start reference
circuit be used when a non-integrated CFL is rated for multiple
circuits in order to establish a consistent set of test specifications.
In preparation for this final rule, DOE reviewed the reference ballast
specifications for non-integrated CFLs and found that most lamps are
rated for preheat circuits. DOE found that if a lamp was rated for
multiple circuits, further specifications still may be needed to
indicate the circuit to use for testing. If a lamp is rated for
operation on both a preheat and high frequency circuit, the reference
ballast characteristics provided describe low frequency operation and
therefore the lamp must be tested on the low frequency preheat circuit.
If a lamp is rated for operation on both a preheat and rapid start
circuit, DOE is specifying in this final rule that the lamp be tested
on the preheat circuit in order to maintain consistency and
comparability across testing.
In this final rule, DOE is not adopting test procedures for lumen
maintenance at 1,000 hours or rapid cycle stress test for non-
integrated CFLs, as these metrics are not being evaluated for inclusion
in, nor are they currently required by, any DOE energy conservation
standards, FTC Lighting Facts labeling requirements, or ENERGY STAR
program requirements. Therefore, in this final rule, DOE adopts test
procedures for initial lamp efficacy, lumen maintenance at 40 percent
of estimated lifetime, lifetime, CRI, and CCT for non-integrated CFLs.
c. Test Procedures for Hybrid CFLs
In the July 2015 NOPR, DOE proposed establishing a test procedure
to measure the applicable metrics for hybrid CFLs in appendix W. That
is, DOE proposed that the same test procedures for integrated CFLs
would be applicable to hybrid CFLs, with a few minor clarifications
regarding the configuration and operation of hybrid CFLs during
testing. DOE considers hybrid CFLs to be CFLs with an additional light
source of a different technology that is not the primary source of
light. DOE proposed to define the term ``hybrid compact fluorescent
lamp'' in appendix W as a CFL that incorporates one or more
supplemental light sources of different technology. 80 FR 45737-45738.
NEMA and OSI proposed the definition of ``a compact fluorescent lamp
that incorporates one or more supplemental light sources of different
technology, such as halogen or LED, which are energized and operated
independently and may or may not operate simultaneously.'' (NEMA, No. 9
at p. 7; OSI, No. 5 at p. 6) OSI stated that there are different types
of hybrid lamps where either the main or the supplemental light source
operates or both the main and supplemental light sources operate. OSI
requested that both the definition and related test procedures address
these different possible configurations of hybrid lamps. (OSI, Public
Meeting Transcript, No. 4 at p. 59)
DOE reviewed the definition suggested by NEMA and OSI and notes
that there is significant overlap between DOE's proposed definition and
the alternate definition. Both definitions contain a reference to a CFL
as well as supplemental technologies. DOE finds that the example ``such
as halogen or LED'' is not necessary, as the DOE's proposed definition
specifies that the supplemental light sources would be of ``different
technology.'' Further providing such examples may be misinterpreted by
some users to limit the types of applicable supplementary sources. NEMA
and OSI's other suggestion of ``which are energized and operated
independently and may or may not operate simultaneously'' identifies
potential operating configurations of the supplementary light sources.
By not specifying any configurations for the operation of the
supplementary light source, DOE's proposed definition does not exclude
the configurations mentioned by NEMA and OSI or any others. DOE's
proposed definition is also consistent with industry definitions of
other hybrid technologies such as a hybrid LED luminaire as defined in
IES RP-16-10, which also does not identify the operating parameters of
the different light sources. For these reasons, DOE retains the
proposed definition from the July 2015 NOPR of the term ``hybrid
compact fluorescent lamp'' as meaning a CFL that incorporates one or
more supplemental light sources of different technology. DOE believes
that this is consistent with the definition suggested by interested
parties, but is more general and leaves less room for misinterpretation
of specific examples or operating parameters.
In the July 2015 NOPR, DOE proposed a test procedure for hybrid
CFLs where the supplemental light source is off (if possible) and the
lamp stabilized. Id. In response to the proposal, the EEAs encouraged
DOE to incorporate language defining a not-to-exceed time to
stabilization prior to taking measurements to prevent extended periods
of operation of secondary sources. (EEAs, No. 8 at p. 3)
DOE's test procedure for hybrid CFLs requires that the
supplementary source be turned off before initiating testing. In the
cases where supplementary source cannot be turned off, the lamp must
adhere to stabilization criteria as
[[Page 59401]]
specified in section 6.2.1 of IES LM-66-14. This stabilization criteria
involves a series of time-related measurements to determine stable
light output and electrical usage. Although the supplementary source
may have some effect on the stabilization time, it is more important
that the lamp achieve stabilization per an established criterion in
order to obtain accurate measurements. Further, the determination of a
stable light output will likely be predominantly influenced by the CFL,
which is the primary source of light. Therefore, in this final rule,
DOE is not adding a not-to-exceed time for stabilization for taking
measurements of hybrid CFLs.
NEMA was supportive of DOE's proposed test procedure for hybrid
lamps. However, NEMA requested that start time not apply to hybrid
CFLs. NEMA added that if start time testing was required for hybrid
CFLs, the supplementary light source should be turned on. NEMA agreed
with DOE's proposal to test hybrid CFLs as non-hybrid CFLs (that is
with only the CFL source active) for any measurements besides start
time. (NEMA, No. 9 at p. 7) The EEAs disagreed with DOE's proposal that
hybrid lamps be tested for efficacy with the supplemental light source
turned off. The EEAs argued that having the supplemental light source
off during testing could yield inaccurate test results for both start
time testing and energy efficiency. (EEAs, No. 8 at p. 3) DOE addressed
start time testing in section III.A.4.d. DOE disagrees with the EEAs
that testing hybrid CFLs with the supplemental light source off (when
possible) would yield inaccurate results for energy efficiency. Testing
the hybrid CFL with only the CFL light source operating (when possible)
would yield comparable efficacy measurements across basic models of
CFLs. Further, based on a review of available hybrid CFLs, DOE has
determined that many supplemental light sources turn off automatically
or will likely be turned off during normal operation (such as when the
supplemental light source is intended to be a night light). Thus, DOE's
test procedure is representative of lamp operation under normal
conditions.
In this final rule, DOE adopts a requirement that hybrid CFLs must
be tested with all supplemental light sources turned off, if possible,
and that the lamp be stabilized in the operating mode that corresponds
to its primary light source, according to test procedures for CFLs in
appendix W.
6. Test Procedure for Standby Mode Energy Consumption
In the July 2015 NOPR, DOE proposed a test procedure to measure
standby mode energy consumption for integrated CFLs, where applicable,
in appendix W. 80 FR 45738. EPCA directs DOE to amend its test
procedures for all covered products to incorporate a measure of standby
and off mode energy consumption in accordance with IEC 62301 and IEC
62087, if technically feasible. (42 U.S.C. 6295(gg)(2))
DOE research indicated that some integrated CFLs include controls,
and that these CFLs can operate in standby mode but not off mode. DOE
did not find any non-integrated CFLs capable of operation in standby
mode or off mode, and understands that any such circuitry would likely
be found in the ballast rather than the lamp. Therefore, in the July
2015 NOPR, DOE proposed that standby mode power be measured only for
integrated CFLs that are capable of standby mode operation. 80 FR
45738.
For integrated CFLs, DOE proposed that standby mode power be
measured in accordance with IEC 62301. DOE also proposed to approve IEC
62301, which is already incorporated by reference in 10 CFR 430.3, for
incorporation into appendix W. DOE proposed that, when measuring
standby power for integrated CFLs, the test conditions and setup must
be as prescribed in IEC 62301, except for ambient temperature and
ambient airflow. Instead, DOE proposed to prescribe the ambient
temperature and ambient airflow requirements in IES LM-66-14 to
minimize differences between test procedures for active mode and
standby mode. DOE proposed to season lamps in the same manner as test
procedures for the other applicable CFL metrics, as described in
section III.A.2.e, and to measure standby mode power as prescribed in
section 5 of IEC 62301. Finally, DOE proposed that standby mode be
initiated when the integrated CFL is connected to the power supply and
lumen output is set to zero via remote or other wireless/sensor
control. 80 FR 45738.
NEMA and OSI commented that, according to the definition proposed
in the July 2015 NOPR, CFLs operate in the off mode when switched off.
They also stated that off mode consumes no power nor produces any
function. (NEMA, No. 9 at p. 7; OSI, No. 5 at p. 6)
DOE determined that it is not possible for CFLs to meet the off
mode criteria because there is no condition in which a CFL is connected
to main power and is not already in a mode accounted for in either
active or standby mode. That is, DOE is not aware of any CFLs that,
when provided with power, are not operating in active mode (i.e.,
illuminated) or standby mode (i.e., facilitating the activation or
deactivation of active mode via remote switch, internal sensor, or
timer). In response to the specific example raised by NEMA and OSI, a
CFL that is switched off is not connected to a main power source
because the circuit is disrupted at the switch and thus power is not
being provided to the CFL. Therefore, in this final rule, DOE retains
the position that CFLs do not operate in off mode and has not
considered test procedures for such modes of operation.
NEMA, Philips, and OSI also requested that DOE explicitly exclude
CFLs that are not designed with standby operation from standby mode
power measurements. (NEMA, No. 9 at p. 7; OSI, No. 5 at p. 6; Philips,
No. 6 at p. 4) DOE agrees with NEMA, OSI, and Philips that only
integrated CFLs capable of operating in standby mode should be tested
for standby mode energy consumption. In the July 2015 NOPR, DOE
proposed regulatory language for measuring standby power in appendix W
that stated standby mode energy consumption should be measured only for
integrated CFLs that are capable of standby mode operation. 80 FR
45755. For further clarity, in the final rule DOE has moved this
instruction to the beginning of the regulatory text for the standby
mode test procedure in appendix W.
DOE received comments from CA IOUs to harmonize testing for standby
mode operation with the LED lamps test procedure.\20\ (CA IOUs, No. 7
at pp. 4-5) The CA IOUs wanted to ensure that lamps capable of
operation in network mode were tested in network mode. (CA IOUs, No. 7
at pp. 4-5) Specifically, CA IOUs requested that DOE define network
mode and suggested that if a product is designed to be connected to a
wireless network in order to fully operate, then the test procedure
should specify that the lamp is to be connected to the network before
testing begins. Connected lamps may require the use of an external
control system or hub to serve as a communication point between the
lamp and end user, and the CA IOUs asked DOE to specify a maximum
permissible distance the control system can be from the lamp during
testing. (CA IOUs, No. 7 at pp. 4-5) The EEAs were supportive of the
[[Page 59402]]
CA IOUs comments. (EEAs, No. 8 at pp. 5-6)
---------------------------------------------------------------------------
\20\ Information regarding the Light-Emitting Diode Lamps Test
Procedure Rulemaking can be found on regulations.gov, docket number
EERE-2011-BT-TP-0071 at www.regulations.gov/#!docketDetail;D=EERE-
2011-BT-TP-0071.
---------------------------------------------------------------------------
DOE agrees that the test procedure needs additional detail to
specify that lamps capable of operation in standby mode must remain
connected to the external wireless network through the entirety of the
test for standby mode energy consumption. If the lamp becomes
disconnected, the lamp may exit standby mode or otherwise have its
power draw affected, which would yield inaccurate test results.
Therefore, in this final rule DOE is adding detail to section 4 of
appendix W to specify that integrated CFLs capable of connecting to a
communication network must be connected to the network prior to testing
and must remain connected throughout the duration of the test. DOE did
not specify a maximum distance the integrated CFL can be from the
control system or hub during testing because DOE believes the
requirement for the integrated CFL to remain connected throughout the
entire duration of the test ensures that, if an integrated CFL is moved
to a distance such that it disconnects from the communication network,
the test results would be invalid.
CA IOUs also commented that connected lamps may experience cycles
or power fluctuations when lamps are communicating with the wireless
network, and requested the test procedure provide instructions to
account for this in an average power metric over a minimum 5-minute
test duration. (CA IOUs, No. 7 at pp. 4-5) The EEAs were supportive of
the CA IOUs comments. (EEAs, No. 8 at pp. 5-6)
DOE is requiring that standby mode measurements be taken as
specified in section 5 of IEC 62301. DOE notes that section 5 of IEC
62301 gives manufacturers the flexibility to choose the measurement
method that best applies to the nature of their products' power supply.
Further, each of the methods available for use in IEC 62301 specifies
that the product must have test durations of at least 10 minutes, which
is an adequate test duration to ensure wattage fluctuations have been
recorded. IEC 62301 also states that data collection at equal intervals
of 0.25 seconds or faster is recommended for loads that are unsteady or
where there are any regular or irregular power fluctuations. DOE finds
that the measurement instructions provided in section 5.0 of the IEC
62301 appropriately account for any potential power fluctuations, and
is not specifying additional instructions regarding measurement of
standby mode power.
In addition, DOE is clarifying in this final rule that standby mode
testing must be conducted prior to testing for time to failure. DOE is
also clarifying that ambient conditions, power supply, electrical
settings, and instrumentation must be the same as used for active mode
testing. These clarifications are intended to ensure that test
conditions will be as consistent as possible.
7. Rounding Values
In the July 2015 NOPR, DOE proposed amending certain rounding
requirements for existing metrics, as DOE found the existing rounding
requirements for individual units in a given test sample to be
inconsistent with the required standard level for some metrics. For
example, although final values for lumen maintenance at 1,000 hours and
lumen maintenance at 40 percent of lifetime must be rounded to whole
numbers, existing standards for lumen maintenance at 1,000 hours (90.0
percent) and lumen maintenance at 40 percent of lifetime (80.0 percent)
are specified to the tenth of a percent in 10 CFR 430.32(u). In the
July 2015 NOPR, DOE also proposed to move the rounding requirements
from appendix W to 10 CFR 429.35. 80 FR 45738.
DOE noted in the July 2015 NOPR that the rounding requirements for
lumen maintenance measurements are to the nearest tenth for integrated
CFLs, and proposed the same requirement for non-integrated CFLs. Id.
Both NEMA and OSI recommended that lumen maintenance be rounded to the
nearest whole number. (NEMA, No. 9 at p. 8; OSI, No. 5 at p. 7) NEMA
further stated that rounding lumen maintenance to the nearest tenth of
a percent is not practical or meaningful. (NEMA, No. 9 at p. 8) DOE
notes that the lumen maintenance value of the standard is to the tenth
of a percent and was established in the 2006 rule that adopted
standards for MBCFLs. 71 FR 71340, 71369 (Dec. 8, 2006). DOE
understands that at least 3 significant figures are required in both
the numerator (maintained lumens) and denominator (initial lumens) to
yield 3 significant figures for lumen maintenance values. DOE reviewed
product catalogs currently published by OSI and several other CFL
manufacturers and determined that lumen output values are often
reported to 3 or 4 significant figures. Therefore, DOE has concluded
that it is possible to determine lumen maintenance to the nearest tenth
of a percent. To align with existing standards, in this final rule, DOE
provides in 10 CFR 429.35 that lumen maintenance at 1,000 hours and
lumen maintenance at 40 percent of lifetime must be rounded to the
nearest tenth of a percent.
In the July 2015 NOPR, DOE proposed that lifetime of a CFL be
rounded to the nearest hour and that these requirements be located in
10 CFR 429.35. 80 FR 45738. Both NEMA and OSI argued that lifetime
should be rounded to two significant digits. (NEMA, No. 9 at p. 8; OSI,
No. 5 at p. 7) NEMA further stated that expressing lifetime to the
nearest hour is meaningless, as the uncertainty in an individual time-
to-failure measurement is much larger than 1 hour. (NEMA, No. 9)
However, rounding to the nearest whole hour is consistent with the unit
of time used for lifetime metrics for other lamp technologies, such as
LED,\21\ and is a level of accuracy a laboratory is capable of
measuring with a standard time-keeping device. In this final rule, DOE
adopts a rounding requirement to the nearest whole hour for lifetime.
DOE notes that manufacturers can make representations of lifetime to
the nearest two significant digits provided that the value is lower
than the actual measured lifetime when rounded to the nearest hour
(i.e., manufacturers are reporting a conservative value for lifetime).
---------------------------------------------------------------------------
\21\ See LED final rule test procedure. 81 FR 43404 (July 1,
2016).
---------------------------------------------------------------------------
DOE did not receive any comments on the proposal to round initial
lamp efficacy values to the nearest tenth of a lumen per watt, input
power to the nearest tenth of a watt, lumen output to three significant
digits, or rapid cycle stress values to whole numbers. Therefore, in
this final rule, DOE adopts these requirements.
Additionally, in the July 2015 NOPR, DOE proposed rounding
requirements for new proposed metrics of CRI, CCT, start time, standby
mode power, and power factor based on industry standard reporting
precision, as determined based on a review of manufacturer catalogs.
DOE also proposed locating those rounding requirements in 10 CFR
429.35. 80 FR 45738. DOE did not receive any comments related to this
proposal. Therefore, in this final rule, DOE adopts the rounding
requirements for these metrics as proposed in the July 2015 NOPR,
specifically: CRI be rounded to the nearest whole number; start time be
rounded to the nearest whole number in milliseconds; CCT be rounded to
the nearest 100 K; standby mode power rounded to the nearest tenth of a
watt; and power factor be rounded to the nearest hundredths place.
[[Page 59403]]
B. Amendments to Definitions at 10 CFR 430.2
1. Compact Fluorescent Lamp
In the July 2015 NOPR, DOE proposed to add a definition of
``compact fluorescent lamp'' in 10 CFR 430.2. 80 FR 45738-45739. DOE
reviewed its definitions for other lighting products and considered the
existing definition of the term ``fluorescent lamp'' at 10 CFR 430.2 as
a basis for its definition of ``compact fluorescent lamp.'' DOE also
consulted the current IES definition of ``compact fluorescent lamp''
contained in IES RP-16-10 and the description of compact fluorescent
lamps in IES LM-66-14, which includes elements of the lamp
characteristics and discusses elements of light output generation.
During the public meeting for the July 2015 NOPR, OSI inquired why DOE
did not adopt the IES RP-16-10 definition rather than developing a
novel definition for compact fluorescent lamp. (OSI, Public Meeting
Transcript, No. 4 at pp. 16-20) Lucidity Lights stated that IES labors
over the exact wording in definitions and also encouraged DOE to use
the exact wording in IES RP-16-10. (Lucidity Lights, Public Meeting
Transcript. No. 4 at p. 22) Both NEMA and OSI also recommended that DOE
use definitions from or reference IES RP-16-10. (NEMA, No. 9 at p. 5;
OSI, No. 5 at pp. 2-3) NEMA stated that the proposed definition for CFL
was technically correct, but raised concern that it expanded the scope
of the definition. (NEMA, No. 9 at p. 8)
DOE appreciates the work that members of the IES did in developing
the definitions in IES RP-16-10. DOE reviewed IES RP-16-10 and IES LM-
66-14 in developing this final rule. DOE considered: (1) Use of the
term fluorescent lamp; (2) tube diameter; (3) general features (i.e.,
amalgam, cold chamber); (4) lamp geometry; and (5) base specification
and lamp configuration in the definition. The following paragraphs
provide additional details on each of these elements.
The definition of CFL in section 6.5.6.1.4 of IES RP-16-10 includes
the phrase ``a fluorescent lamp with . . .'' DOE cannot use this
element in 10 CFR 430.2 to define a CFL because 10 CFR 430.2 already
defines the term fluorescent lamp, which establishes a fluorescent lamp
as a low pressure mercury electric-discharge source in which a
fluorescent coating transforms some of the ultraviolet energy generated
by the mercury discharge into light, and is limited to six specific
lamps, all of which are longer than 22 inches and are double ended. If
DOE adopted a definition of CFL that contained the term ``fluorescent
lamp,'' it would include these large lamp lengths and base
configurations that are not CFLs.
The definition of CFL in IES RP-16-10 also specifies that the
diameter of the lamp's tube must be less than or equal to that of a T5.
However, DOE's review of ANSI standards and manufacturer's lamp
marketing materials indicated that there are CFLs with tube diameters
greater than T5. Specifically, ANSI C78.901-2014 includes within their
list of data sheets a handful of ``square'' shaped CFLs that are listed
with a corresponding T6 tube diameter. DOE also found manufacturer data
sheets of lamps greater than T5 in diameter that were single-ended and
folded or bent fluorescent lamps and characterized as CFLs. Therefore,
DOE determined that diameter could be a limiting specification that may
exclude lamps that should be categorized as CFLs. Therefore, in this
final rule, DOE does not include specification of the tube diameter in
the definition of ``compact fluorescent lamp.''
The IES RP-16-10 definition also states that the lamp designs
generally include amalgam and a cold chamber, or a cold spot, to
control the mercury vapor pressure and light output. These features are
general and not distinctive for all CFLs. Therefore, in this final
rule, DOE does not include this description in the definition of
``compact fluorescent lamp.''
The IES RP-16-10 definition of ``compact fluorescent lamp''
specifies that tube construction must be glass and describes the
configuration of the glass tube as folded, bent, or bridged to create a
long discharge path. The IES LM-66-14 description of fluorescent lamps
notes that a fluorescent lamp can be made compact in two ways.
Fluorescent lamps with electrodes (typically long, tubular lamps) can
be made compact by folding the tube one or more times or spiraling it
in a helix in such a way that both electrodes are configured to have
one connection, leading to single base construction. IES LM-66 also
notes that induction-driven electrodeless fluorescent lamps are compact
because the discharge current is required to form a closed loop inside
the structure. Because fluorescent lamps with a compact size do not
necessarily include a glass tube with a specific geometry, DOE does not
add such a description to the definition of ``compact fluorescent
lamp.''
Both of the introductory sections of IES LM-65-14 and LM-66-14
discuss that there are two types of CFLs: Integrated and non-
integrated. Further, the titles of both IES LM-65-14 and LM-66-14
contain the phrase ``single-based.'' DOE agrees with these IES
documents in the importance of clarifying that CFLs are integrated or
non-integrated and single-based. Therefore, DOE retains those terms in
the definition of ``compact fluorescent lamp'' adopted in this final
rule. IES LM-66-14 also specifically excludes U-shaped and circline
fluorescent lamps from its CFL definition. DOE agrees with IES LM-66-14
that U-shaped and circline lamps are not CFLs. Therefore, to ensure
such lamps are not inadvertently misclassified, DOE also retains these
exclusions in the definition of ``compact fluorescent lamp'' adopted in
this final rule.
In summary, DOE has incorporated language from IES RP-16-10 and IES
LM-66-14 that helps clearly define CFLs without erroneously excluding
or including lamps. In this final rule, DOE defines a compact
fluorescent lamp (CFL) as an integrated or non-integrated single-base,
low-pressure mercury, electric-discharge source in which a fluorescing
coating transforms some of the ultraviolet energy generated by the
mercury discharge into light; the term does not include circline or U-
shaped lamps.
2. Correlated Color Temperature
In the July 2015 NOPR, DOE proposed modifying the definition of
``correlated color temperature'' in 10 CFR 430.2 by adding the
abbreviation ``CCT.'' DOE explained that a similar abbreviation exists
in 10 CFR 430.2 for the definition of color rendering index or CRI. The
abbreviation ``CCT'' is widely used in industry as well as by ENERGY
STAR and in 10 CFR part 430, subpart B, appendix R. 80 FR 45739.
Both NEMA and OSI submitted written comments in support of the
proposed change. (NEMA, No. 9 at p. 8; OSI, No. 5 at p. 7) OSI also
suggested that DOE harmonize the definition with IES RP-16-10. (OSI,
Public Meeting Transcript, No. 4 at pp. 16-19) Section 4.6.4.2 of IES
RP-16-10 defines ``correlated color temperature of a light source'' as
the absolute temperature whose chromaticity most nearly resembles that
of the light source. Other than the added abbreviation of ``or CCT''
and the phrase ``of a light source,'' DOE's definition (defined by
EPCA) is the same as IES RP-16-10. Therefore, in this final rule, DOE
adopts the abbreviation ``CCT'' into the term ``correlated color
temperature'' and makes no other changes to the definition.
[[Page 59404]]
3. Lifetime of a Compact Fluorescent Lamp
DOE proposed to define ``lifetime of a compact fluorescent lamp''
in 10 CFR 430.2 as the time to failure of 50 percent of the sample size
(as defined and calculated in 10 CFR 429.35(a)(1)) in accordance with
the test procedures described in section 3.3 of appendix W. 80 FR
45733.
NEMA and Philips raised concerns that replacing ``average rated
life'' with ``lifetime of a compact fluorescent lamp'' might result in
unintended consequences; specifically, lumen maintenance of a lamp
could not be determined until the lamp's lifetime is known. (NEMA, No.
9 at pp. 4-5; Philips, No. 6 at p. 4) DOE addresses lumen maintenance
measurements in section III.A.4.a.
NEMA proposed replacing ``average rated life'' with ``rated life,''
noting that the latter term appears in the CFR and is similar to the
term ``rated lamp life'' defined in ``Nomenclature and Definitions for
Illuminating Engineering'' from the IES (IES RP-16). NEMA stated the
determination of lifetime should be independent of a specific sample
size and allow for the use of more stable statistical estimators of the
population median value than failure of 50 percent of the sample.
Therefore, NEMA recommended that DOE define ``rated life'' as median
time to failure of the population of CFLs. For further support, NEMA
stated that EPCA defines ``life'' and ``lifetime'' as the length of
operating time of a statistically large group of lamps between first
use and failure of 50 percent of the group. NEMA also cited the IES
Lighting Handbook which states in section 13.3 that for incandescent,
fluorescent, and HID lamps, rated lamp life is the total operating time
at which, under normal operating conditions, 50% of any large group of
initially installed lamps is expected to have failed. This is a
statistically determined estimate of the median operational life. NEMA
stated that by adopting the definition in the IES Lighting Handbook,
DOE would indicate that the lifetime is the median value of a large
group of lamps and is statistically determined. NEMA also noted that
DOE should not restrict the sample size to a multiple of two if
statistical estimation of the population median value is accepted.
(NEMA, No. 9 at pp. 4-5, 10)
OSI also proposed the term ``rated life'' citing 10 CFR part 430
and IES RP-16-10. OSI agreed with NEMA that lifetime should be
determined independent of a specific sample size. OSI recommended a
definition similar to the one in the IES Lighting Handbook, defining
rated life as the total operating time at which, under normal operating
conditions, 50 percent of any large group of initially installed lamps
is expected to have failed, referencing the historic ENERGY STAR and
IES definition. (OSI, No. 5 at pp. 4-5)
In general, NEMA and OSI stated lifetime is poorly estimated by the
arithmetic mean of the time to failure of the two middle sample units
when sorted in order. (NEMA, No. 9, p. 10; OSI, No. 5 at p. 9) During
the public meeting for the July 2015 NOPR, both GE and Westinghouse
stated the middle value of a sample was a poor indicator of the median
and instead recommended using an entire population. (GE, Public Meeting
Transcript, No. 4 at pp. 14-15, 25-26; Westinghouse, Public Meeting
Transcript, No. 4 at pp. 15-16) GE added that the intent of the
statutory language was to indicate a median value for lifetime, that
DOE has the opportunity to clearly specify this and, further, that this
value should represent 50 percent failure of the population to align
with the industry standard for rated lifetime of lamps. (GE, Public
Meeting Transcript, No. 4 at pp. 25-26)
DOE understands that the IES Lighting Handbook and EPCA describe
``rated lamp life'' and ``lifetime''/``life'' to be based on a large
group of lamps rather than a specific number of lamps. Further, the IES
Lighting Handbook states that ``rated lamp life'' is when 50 percent of
any large group of lamps is expected to have failed and that it is a
statistically determined estimate of the median operational life.
However, DOE notes that it must prescribe test procedures that provide
consistent and reproducible results, and allow for comparison of
represented values across basic models. Therefore, rather than allow
any number of lamps to be used to determine the represented value of
lifetime, DOE must specify a minimum sample size.
Commenters did not suggest a specific minimum sample size, and as
proposed in the July 2015 NOPR, DOE is adopting a minimum sample size
of 10 for testing the initial lamp efficacy, lumen maintenance at 1,000
hours, lumen maintenance at 40 percent of lifetime, lifetime, CCT, CRI,
power factor, and standby mode power. DOE is requiring that the same
sample of 10 units be used for testing these metrics, and that a
minimum of three units from the same sample of units be tested for
start time. (Due to the nature of the test, a unique sample set is
required for rapid cycle stress testing.) Each of these metrics
contribute to the overall performance of a CFL, and because they are
fundamentally related, directly and/or indirectly impact each other.
Therefore, the same set of sample units and sample size should result
in more accurate measurements of all metrics, including lifetime.
Manufacturers may, at their discretion, use a larger sample size to
determine a representative value of lifetime if they believe it is
warranted. However, the same sample set and size must also be used for
testing initial lamp efficacy, lumen maintenance at 1,000 hours, lumen
maintenance at 40 percent of lifetime, lifetime, CCT, CRI, power
factor, and standby mode power; the total number of units in the sample
set must be a multiple of two; and a minimum of three units from the
sample set must be used for start time. If the same sample of units is
not available for the testing of additional metrics for an existing
model, the basic model must be retested using the same sample set for
all metrics.
DOE notes that the statutory definition of lifetime does not
include any mention of a statistical method that can be used and DOE is
hesitant to allow for any statistical method to determine lifetime.
Commenters did not provide explicit suggestions regarding any
applicable statistical methods in their comments. In addition, neither
the IES Lighting Handbook nor any other industry standard provides a
specific statistical method that should be used to determine the
lifetime of compact fluorescent lamps. Further, DOE notes that the
median of a sample is a robust statistical descriptor of the central
tendency of the sample (and thereby the population) that deals well
with outlier values, which may be the case in lifetime testing of CFLs.
Although other statistical tools can be used to describe the variance
about the median or estimate adjusted median values if other attributes
about the population are known (e.g., the distribution is a Pareto
distribution or a weighted median if the precision of each data point
is known and is significantly variable), these more advanced
statistical tools are unnecessary, as they would not provide a better
description of the expected lifetime of the lamp, as defined by EPCA,
than the median value.
Therefore, DOE finalizes its proposal in the July 2015 NOPR, that
lifetime of a CFL be calculated as the operating time between first use
and failure of 50 percent of the sample units; the sample size must be
at least 10 units; and the represented value of lifetime must be the
median time to failure of the sample (calculated as the arithmetic mean
of the time to failure of the two middle sample
[[Page 59405]]
units when the numbers are sorted in value order). DOE believes that
this definition provides the appropriate specificity to produce
consistent and repeatable results while aligning with EPCA's definition
of ``lifetime'' and ``life'' as the ``length of operating time of a
statistically large group of lamps between first use and failure of 50
percent of the group.'' In order to provide a clear and consistent test
procedure, DOE specifies ``group'' as a minimum sample size of 10 units
for CFLs, but reiterates that manufacturers are not prevented from
testing significantly more than 10 CFLs provided the total number
tested is a multiple of two.
C. Amendments to Materials Incorporated by Reference at 10 CFR 430.3
In the July 2015 NOPR, DOE proposed to incorporate by reference
ANSI C78.901-2014, IES LM-54-12, IES LM-65-14, and IES LM-78-07
industry standards and to extend the incorporation by reference of CIE
13.3-1995, CIE 15:2004, IES LM-66-14, and IEC 62301 into DOE's test
procedure for CFLs in appendix W.
As noted in section III.A.1, DOE proposed in the July 2015 NOPR to
incorporate by reference IES LM-54-12, IES LM-65-14, and IES LM-66-14
for appendix W for seasoning, time to failure measurements, and
electrical and photometric measurements respectively. 80 FR 45727. In
response to this proposal, both NEMA and OSI agreed with the
incorporation of IES LM-54-12, IES LM-65-14, and IES LM-66-14. (NEMA,
No. 9 at pp. 3, 8; OSI, No. 5 at pp. 2-3) The CA IOUs noted that the
IES LM-54-12 removes the requirement of cycling during seasoning for
metrics other than lifetime and did not agree with DOE's proposal to,
accordingly, also remove the cycling requirements in its test
procedure. (CA IOUs, No. 7 at p. 3) DOE is requiring cycling for all
metrics, see section III.A.1 for further details. In this final rule,
DOE incorporates by reference these test methods into 10 CFR 430.3 for
appendix W or extends the incorporation by reference of these test
procedures to appendix W.
As noted in section III.A.2.a, DOE also proposed in the July 2015
NOPR to incorporate by reference IESNA LM-78-07 for appendix W for
measurements using an integrating sphere photometer. 80 FR 45731. DOE
did not receive any comments related to incorporating IESNA LM-78-07.
Therefore, in this final rule, DOE incorporates by reference this test
method into 10 CFR 430.3 for appendix W.
As noted in section III.A.4.a, in the July 2015 NOPR DOE proposed
incorporating CIE 13.3-1995 and CIE 15:2004 (3rd edition) for appendix
W for measuring and calculating CRI and CCT respectively. 80 FR 45739.
The CA IOUs were supportive of incorporating by reference both CIE
13.3-1995 and CIE 15:2004 (3rd edition). (CA IOUs, No. 7 at pp. 3-4)
Therefore in this final rule, DOE extends the incorporation by
reference of these test procedures to appendix W.
As noted in section III.A.5.b, in the July 2015 NOPR DOE proposed
incorporating by reference ANSI C78.901-2014 for appendix W to include
reference ballast specifications for non-integrated CFLs. 80 FR 45739.
NEMA supported incorporating by reference ANSI C78.901-2014. (NEMA, No.
9 at pp. 6-7) Therefore in this final rule, DOE incorporates by
reference this industry standard into 10 CFR 430.3 for appendix W.
As noted in section III.A.6, in the July 2015 NOPR, DOE proposed
incorporating by reference IEC 62301 for appendix W for measuring
standby mode energy consumption. 80 FR 45739. DOE did not receive any
comments related to this proposal. DOE notes that 10 CFR 430.3
presently has two different versions of IEC 62301 incorporated. DOE is
extending the incorporation by reference of the edition 2.0, 2011-01
version of IEC 62301 to appendix W.
D. Amendments to 10 CFR 430.23(y)
In the July 2015 NOPR, DOE proposed to revise and add text at 10
CFR 430.23(y) to reflect other proposed changes to the scope and
applicability of DOE's CFL test procedures. 80 FR 45739. Specifically,
the existing text at 10 CFR 430.23(y) indicates that, for MBCFLs, the
initial lamp efficacy, lumen maintenance at 1,000 hours, lumen
maintenance at 40-percent of rated life, and lamp life must be
measured, and the rapid cycle stress test conducted, in accordance with
section 4 of appendix W of this subpart. DOE proposed to delete the
text ``medium base'' to reflect the inclusion of additional CFL
categories. Id. In addition, in the July 2015 NOPR, DOE also proposed
to specify in 10 CFR 430.23(y) the relevant sections of appendix W to
be used to measure the following metrics: Initial lamp efficacy, lumen
maintenance at 1,000 hours, lumen maintenance at 40 percent of
lifetime, CRI, CCT, power factor, time to failure, rapid cycle stress
test, start time, and standby mode energy consumption. 80 FR 45739-
45740.
Both NEMA and OSI submitted comments requesting that DOE retain the
term ``medium base'' in the title of the term because they did not
think non-integrated CFLs should be part of the test procedures. (NEMA,
No. 9 at p. 7; OSI, No. 5 at p. 6) DOE did not receive any other
comments related to this proposed modification. As DOE has stated
previously, the test procedures that are the subject of this final rule
address integrated and non-integrated CFLs in support of existing and
potential standards, as well as requirements of FTC's Lighting Facts
Label and ENERGY STAR Program Requirements for Lamps and Luminaires
(see section II for further details). Therefore, in this final rule,
DOE is removing the reference to ``medium base'' and specifying all
applicable metrics for CFLs.
E. Amendments to Laboratory Accreditation Requirements at 10 CFR 430.25
In the July 2015 NOPR, DOE proposed to amend 10 CFR 430.25 to
extend the laboratory accreditation requirements for MBCFL testing to
additional CFL categories and metrics covered under the proposed new
and amended test procedures. 80 FR 45740. Specifically, DOE proposed to
replace the text ``medium base compact fluorescent lamps'' with the
text ``compact fluorescent lamps'' and specify that if a manufacturer's
or importer's laboratory is accredited, it may conduct the applicable
testing. Id.
NEMA and OSI raised concerns that expanding testing in an
accredited lab from MBCFLs to all CFLs would increase the testing
burden, adding that non-integrated CFLs typically are not tested in
accredited laboratories. Additionally, NEMA and OSI asked that this
potential requirement be addressed in both the manufacturing impact
analysis, as well as testing burden analyzed in the regulatory
flexibility analysis. (NEMA, No. 9 at p. 9; OSI, No. 5 at p. 7)
Testing in accredited laboratories helps ensure that measurements
are consistent and reproducible. Therefore, in this final rule, DOE
removes the phrase ``medium base'' and specifies that if a
manufacturer's or importer's laboratory is accredited, it may conduct
the applicable testing in 10 CFR 430.25. See section IV.B for a
discussion of test burden.
F. Clarifications to Energy Conservation Standard Text at 10 CFR
430.32(u)
MBCFL energy conservation standards are codified in a table at 10
CFR 430.32(u). Certain language in the
[[Page 59406]]
MBCFL energy conservation standards table provides clarification
relevant to test procedures (e.g., sampling, test methods, and test
calculations). Although this clarifying language is not in conflict
with the specifications in the test procedures for MBCFLs contained in
appendix W and in 10 CFR 429.35, for simplicity DOE proposed to modify
the text in the MBCFL energy conservation standards table to remove
specific test procedure language and instead reference the relevant
parts of the MBCFL test procedures. In addition, in the introductory
paragraph of 10 CFR 430.32(u), DOE proposed to replace the text ``bare
lamp and covered lamp'' with the text ``bare or covered.'' DOE
considered these revisions to be clarifications that do not modify the
energy conservation standards. 80 FR 45740-45741.
NEMA and OSI in general agreed with separating the test procedure
specifications from section (u) with certain exceptions discussed in
the next sections. (NEMA, No. 9 at p. 9; OSI, No. 5 at p. 8) In this
final rule, DOE retains the change to the first sentence in 10 CFR
430.32(u) to read as ``A bare or covered (no reflector) medium base
compact fluorescent lamp manufactured on or after January 1, 2006 . .
.'' Revisions to specific metrics in the table at 10 CFR 430.32(u) and
related comments received are described in the subsequent sections.
1. Initial Lamp Efficacy
In the July 2015 NOPR, DOE proposed amending the first column of
the table in 10 CFR 430.32(u) by replacing the seven instances of the
text ``lamp power'' with the text ``labeled wattage.'' 80 FR 45740. DOE
proposed to use labeled wattage as that is the term DOE is using to
define the wattage marked on the lamp that should be used to determine
the applicable minimum efficacy requirement (see section III.A.3.f).
DOE also proposed deleting the current text in footnote 1. Id.
NEMA and OSI recommended using the term ``rated wattage'' rather
than ``labeled wattage.'' (NEMA, No. 9 at p. 9; OSI, No. 5 at pp. 8-9)
As discussed in section III.A.3.f, DOE disagrees with NEMA and OSI
about using the term ``rated wattage'' because DOE believes it may
cause confusion or be easily misinterpreted. Instead, DOE retains in
this final rule the term ``labeled wattage.''
In the July CFL TP NOPR, DOE also proposed to remove the text from
footnote 2 indicating that for multi-level or dimmable systems,
measurements shall be at the highest setting, and acceptable
measurement error is 3 percent. NEMA and OSI suggested
keeping the 3 percent measurement error for efficacy and extend it to
all other parameters. (NEMA, No. 9 at p. 9; OSI, No. 5 at pp. 8-9) DOE
has determined that a 3 percent tolerance is not necessary. DOE
addresses measurement error in sample size, confidence limit, and de-
rating values as provided in 10 CFR 429.35. Because this allowance for
determining compliance with existing standards already exists in 10 CFR
430.32(u), the 3 percent tolerance for efficacy has been maintained but
moved to 10 CFR 429.35.
2. Lumen Maintenance at 1,000 Hours
In the July 2015 NOPR, DOE proposed amending the text for 1,000-
hour lumen maintenance in the second column of the table in 10 CFR
430.32(u), which indicates that the average of at least 5 lamps must
have a minimum 90.0 percent of initial (100-hour) lumen output at 1,000
hours of rated life. DOE proposed to delete this text and only state
the standard as >=90.0 percent. DOE also provided specific other
changes to the table to correspond with terminology in the amended test
procedure. 80 FR 45740. DOE did not receive any comments regarding
these specific changes. Therefore, in this final rule, DOE modifies 10
CFR 430.32(u) to remove test procedure text and to align the
terminology with the amended test procedure.
3. Lumen Maintenance at 40 Percent of Lifetime
In the July 2015 NOPR, DOE proposed amending the text for lumen
maintenance in the second column of the table in 10 CFR 430.32(u),
which indicates 80.0 percent of initial (100-hour) rating at 40 percent
of rated life (per ANSI C78.5 Clause 4.10). 80 FR 45740-45741. DOE
proposed to delete this text and state only the standard as >=80.0
percent and other modifications to the table to read lumen maintenance
at 40 percent of lifetime. Id. DOE did not receive any comments
regarding these specific changes. Therefore, in this final rule, DOE
modifies 10 CFR 430.32(u) to remove test procedure text and to align
the terminology with the amended test procedure. In addition, for
clarity DOE includes a footnote on the term ``lifetime'' that states
``Lifetime refers to lifetime of a compact fluorescent lamp as defined
in 10 CFR 430.2.''
4. Rapid Cycle Stress Test
In the July 2015 NOPR, DOE proposed amending the text in the second
column of the table for rapid cycle stress test in 10 CFR 430.32(u). 80
FR 45741. DOE proposed to delete the first two sentences of this text
and to state that each lamp must be cycled once for every 2 hours of
lifetime and at least 5 lamps must meet or exceed the minimum number of
cycles. Id.
NEMA and OSI responded that the row in the table that codifies
MBCFL energy conservation standards at 10 CFR 430.32(u) specifically
retains the term ``rated lifetime.'' (NEMA, No. 9 at p. 9; OSI, No. 5
at p. 8) In this final rule, DOE defines the term ``lifetime of a
compact fluorescent lamp'' to be used in the new and amended test
procedures (see section III.A.3.a for further details). Therefore, to
align with the test procedures, DOE amends table 10 CFR 430.32(u) in
this final rule to state that each lamp must be cycled once for every 2
hours of lifetime and at least 5 lamps must meet or exceed the minimum
number of cycles. In addition, for clarity DOE includes a footnote on
the term ``lifetime'' that states ``Lifetime refers to lifetime of a
compact fluorescent lamp as defined in 10 CFR 430.2.''
5. Lifetime
In the July 2015 NOPR, DOE proposed amending 10 CFR 430.32(u) by
deleting the term ``average rated lamp life'' and replacing it with the
term ``lifetime.'' 80 FR 45741. DOE also proposed to amend the text in
the second column pertaining to lifetime to only state the standard as
>=6,000 hours and that DOE will no longer allow the use of statistical
methods at 80 percent of rated life to determine the represented value
of lifetime. Id. NEMA and OSI stated that the row should retain the
text ``>=6,000 hours as declared by the manufacturer on packaging.''
(NEMA, No. 9 at p. 9; OSI, No. 5 at p. 8) In this final rule, DOE
defines the term ``lifetime of a compact fluorescent lamp'' and
provides test procedures for the measurement and reporting of this
value. To avoid potential confusion regarding how lifetime should be
measured, DOE removes the language ``as declared by the manufacturer on
packaging'' in this final rule. In addition, for clarity DOE includes a
footnote on the term ``lifetime'' that states ``Lifetime refers to
lifetime of a compact fluorescent lamp as defined in 10 CFR 430.2.''
G. Amendments to Certification Report Requirements
In the July 2015 NOPR, DOE recognized that testing of CFL lifetime
and lumen maintenance at 40 percent of lifetime require considerably
more time than testing of other required CFL metrics. DOE proposed to
allow new basic models of CFLs to be distributed prior to completion of
the full testing for
[[Page 59407]]
lifetime and lumen maintenance at 40 percent of lifetime, as well as
prior to completion for the rapid cycle stress test because it is also
dependent on lifetime. DOE's proposal was similar to other lighting
technologies in that prior to distribution of the new basic model of
CFL, manufacturers may submit an initial certification report based on
estimated values of lifetime, 40 percent lumen maintenance, and rapid
cycle stress test if the testing for lifetime is not complete. In such
a case, the certification report would be required to specifically
describe a prediction method that would be generally representative of
the methods specified in appendix W. Manufacturers would be required to
maintain relevant records, in accordance with 10 CFR 429.71, of the
development of all estimated values and any associated initial test
data. DOE also proposed amendments to the certification report to
address the new and additional metrics that are being adopted in this
final rule and are required for compliance with DOE's energy
conservation standards. 80 FR 45741.
Philips commented that there currently are no restrictions with
respect to the prediction models that may be used, so selection of the
prediction model should be at the discretion of the manufacturer, and
should only be disclosed to defend it to the DOE if challenged.
(Philips, No. 6 at p. 4) NEMA and OSI similarly objected to the
proposed requirements that manufacturers must disclose the prediction
method and that it must represent one of the methods in appendix W.
(NEMA, No. 9 at p. 9; OSI, No. 5 at p. 8; Philips p. 4)
The EEAs opposed DOE's proposal to allow manufacturers to estimate
values for lifetime and rapid cycle stress prior to the completion of
testing for time to failure, and particularly opposed the proposal that
manufacturers be permitted to develop their own prediction methods for
these estimates. (EEAs, No. 8 at p. 5) The EEAs stated that, by the
time DOE received a full certification report showing that a given
model did not meet the standard, manufacturers may be retiring the
model and it will have been in commerce for a significant portion of
its intended market life. The EEAs also suggested it may be
theoretically possible to extrapolate lumen depreciation provided a
common approach based on industry standard methods is used. (EEAs, No.
8 at p. 5)
Based on a review of the market, DOE found that most CFLs have a
lifetime of 10,000 hours or longer and therefore, it may take more than
a year to complete the necessary lifetime measurements. Therefore, to
accommodate such long testing time, DOE believes that the use of
estimated values for lifetime, lumen maintenance at 40 percent of
lifetime, and rapid cycle stress testing are required. In response to
the concerns of CA IOUs and the EEAs regarding the accuracy of such
methods, DOE notes that DOE is not aware of any industry-wide accepted
method for extrapolation of lumen depreciation for CFLs. Therefore, DOE
is not requiring a specific prediction method for estimated values.
However, DOE is requiring manufacturers to specify the method of
prediction and that this method must be generally representative of
DOE's test procedures for CFLs in appendix W. In addition, DOE is
adding a requirement to the certification report that manufacturers
must state whether values of lifetime, lumen maintenance at 40 percent
of lifetime, and rapid cycle stress testing are based on estimated or
measured values. DOE believes that, as noted by CA IOUs and EEAs, such
information regarding the prediction methods used by manufacturers is
necessary in order to verify that such predictions are valid and based
on sound engineering judgement and calculations. Therefore, DOE
believes that these requirements regarding the prediction method are
adequate and necessary to ensure estimated values are reliable,
representative, and consistent with test conditions, setup, and methods
specified in DOE's test procedures for CFLs.
In addition, DOE notes that there is precedent for allowing
products to be distributed in commerce based on estimated values. DOE
allows initial certification reports for GSFLs and incandescent
reflector lamps and also requires that manufacturers include a
description of any testing or analysis the manufacturer performed. 10
CFR 429.12(e)(2) Under EPCA, MBCFLs may be marketed before completion
of testing for lifetime and lumen maintenance at 40 percent of lifetime
with supporting engineering predictions and analysis. 42 U.S.C.
6293(b)(12)(C).
Therefore, by allowing new basic models of CFLs to be distributed
in commerce based on estimated values determined by prediction methods
representative of DOE's test procedures for CFLs, DOE is ensuring
products are available to consumers in a reasonable time while still
requiring a rigorous process to ensure that all representative values
are as accurate and precise as possible. In this final rule, DOE also
clarifies that for existing basic models that require retesting,
manufacturers may submit an initial certification report based on
estimated values of lifetime, 40 percent lumen maintenance, and rapid
cycle stress if the testing for lifetime is not complete.
The EEAs also recommended that DOE take action to enhance industry
adherence with the CFL test procedure. They noted that under two CFL
verification testing programs, ENERGY STAR and the Program for the
Evaluation and Assessment of Residential Lighting (PEARL), a
significant number of ENERGY STAR-qualified CFLs were found to be
noncompliant with ENERGY STAR program requirements. The EEAs noted that
these results varied between brands, but the overall consumer
dissatisfaction and perception of poor CFL quality applied throughout
the industry, regardless of a particular brand's performance. The EEAs
suggested DOE collect and analyze performance data for CFLs sold in the
retail distribution chain and adopt an enhanced enforcement strategy
focused on brands, rather than only basic models. The EEAs recommended
that DOE require manufacturers to submit data that support the enhanced
enforcement strategy and to tighten data submission requirements to
prevent manufacturers from submitting incomplete or incorrect test data
that may misrepresent the quality of products being verified. (EEAs,
No. 8 at pp. 6-7)
DOE currently has enforcement procedures in place for, among many
other products, CFLs that are subject to energy conservation standards.
For more information please refer to DOE's ``Implementation,
Certification, and Enforcement'' Web site at https://energy.gov/eere/buildings/implementation-certification-and-enforcement.
Additionally in the July 2015 NOPR, DOE proposed that if, prior to
completion of testing, a manufacturer ceases to distribute in commerce
a basic model, the manufacturer must submit a full certification report
and provide all of the information listed in 10 CFR 429.12(b),
including the product-specific information required by 10 CFR
429.35(b)(2), as part of its notification to DOE that the model has
been discontinued. 80 FR 45741. DOE did not receive any comments
regarding this proposal and adopts it in this final rule. This
provision will help alleviate potential issues envisioned by the EEAs
that models will be retired without any accountability for compliance
with the standards.
Further, for this final rule, DOE separated the certification
report requirements for medium base CFLs that
[[Page 59408]]
are showing compliance with the current energy conservation standards,
integrated CFLs that would need to show compliance with potential GSL
energy conservation standards, and non-integrated CFLs which may need
to show compliance with potential GSL energy conservations standards.
DOE separated these requirements in order to clarify that different
values must be reported when certifying compliance to existing
standards in 430.32(u) (as it appears in 10 CFR parts 200-499 edition
revised as of January 1, 2016) for medium base CFLs; general service
lamp energy conservation standards (if adopted) for integrated CFLs;
and general service lamp energy conservations standards (if adopted)
for non-integrated CFLs.
H. Amendments to 10 CFR 429.35
The text of the 10 CFR 429.35 title currently addresses bare or
covered (no reflector) MBCFLs. DOE proposed in the July 2015 NOPR to
remove this text and identical text found in Sec. 429.35(a)(1) and
(a)(2), and replace it with the text ``compact fluorescent lamps'' to
reflect the inclusion of additional CFL categories. 80 FR 45741. DOE
did not receive any comments on this proposal and therefore adopts this
change in the final rule.
In addition, DOE also proposed to clarify and amend the sampling
requirements for existing and new metrics, provide clarification on
reuse of samples, and address failures of sample units. 80 FR 45741.
DOE concluded that these clarifications and amendments would not have a
significant effect on measured values or test burden. Id. In general,
the EEAs were supportive of DOE's proposed changes to sampling
requirements. (EEAs, No. 8 at pp. 2-4) DOE received comments related to
the specific proposals to 10 CFR 429.35 and discusses these in detail
in the following sections.
1. Initial Lamp Efficacy and Lumen Maintenance
Currently, in 10 CFR 429.35, sampling requirements are specified
for efficacy, 1,000-hour lumen maintenance, and lumen maintenance at 40
percent of rated life. In the July 2015 NOPR, DOE proposed to replace
the terms efficacy, 1,000-hour lumen maintenance, and lumen
maintenance, respectively, with the terms initial lamp efficacy, lumen
maintenance at 1,000 hours, and lumen maintenance at 40 percent of
lifetime. 80 FR 45741-45742.
DOE also proposed to create a separate sampling requirement section
for initial lamp efficacy in order to include an allowance of 3 percent
tolerance on the represented value of this metric (see section
III.F.1). Specifically, DOE proposed that, to account for measurement
error, the represented value for initial lamp efficacy of MBCFLs may
include 3 percent added to the lower of (a) the mean of the sample and
(b) the lower 97.5 percent LCL of the true mean divided by 0.95. For
example, if the lower value is the mean of the sample at 60.0 lumens
per watt, then the 1.03 multiplier could be applied to yield a
represented value for initial lamp efficacy of up to 61.8 lumens per
watt. DOE concluded that this clarification does not result in a
significant impact to measured values. DOE received comments on this
proposal and addresses them in section III.F.1. In this final rule, DOE
adopts the proposal regarding the 3 percent tolerance for initial lamp
efficacy as described in this preamble.
Additionally, DOE proposed to expand the sample size from a minimum
of 5 units to a minimum of 10 units for initial lamp efficacy, 1,000
hour lumen maintenance, and lumen maintenance at 40 percent of
lifetime. 80 FR 45742. Further DOE proposed that if more than 10 units
are tested as part of the sample for these three metrics, the total
number of units must be a multiple of two so that an equal number of
units can be tested base up and base down. DOE also notes that, because
the sample set must be the same for all metrics, if the sample size is
greater than 10, the same larger sample set must be used for the other
metrics required to utilize the sample set (see III.H.5).
In the July 2015 CFL TP NOR, DOE also proposed that half of the
units be tested base up and half of the units be tested base down,
rather than testing all units base up as currently required. Testing in
both the base up and base down positions provides an accurate
representation of performance under both orientations since the end-use
orientation is unknown. 80 FR 45742.
OSI raised concerns that adding another orientation besides base up
will effectively double testing costs by increasing the number of units
under test as well as increasing the infrastructure required. OSI also
stated that in many cases, manufacturers have evaluated products only
in the base up position. (OSI, No. 5 at p. 8) NEMA stated that
modifying the orientation specification would change measured values
and add test burden. (NEMA, No. 9 at pp. 3, 8)
Test burden is discussed in section IV.B. DOE notes that ENERGY
STAR has required both a sample size of 10 and that half be tested in
the base up position and the other half in the base down position
orientations since version 3.0 of the ``ENERGY STAR[supreg] Program
Requirements for CFLs'', which was finalized in 2003.\22\ CA IOUs
commented (and DOE verified) that according to ENERGY STAR 64 percent
of integrated CFLs shipped in 2014 were ENERGY STAR certified. (CA
IOUs, No. 7 at p. 4) Therefore, a majority of integrated CFLs have
already been evaluated in both orientations.
---------------------------------------------------------------------------
\22\ Version 3.0 of the CFL lamps specification was superseded
by other versions of the CFL lamp specification and then ultimately
the CFL specification was replaced by the overall lamp
specification. However, the original specification can be found at
https://www.energystar.gov/products/spec by searching lighting, light
bulbs (CFLs) and historic in status.
---------------------------------------------------------------------------
NEMA and OSI stated that if testing of non-integrated CFLs is
necessary, that these lamps should only be tested in the base up
position as base down testing is not representative of actual usage.
Further, both NEMA and OSI raised concerns about the burden related to
testing non-integrated CFLs in both base up and base down orientations.
(NEMA, No. 9 at p. 10; OSI, No. 5 at p. 8)
Test burden is discussed in section IV.B. Contrary to the assertion
of NEMA and OSI that base down orientation would not be representative
of actual use for non-integrated CFLs, DOE has identified fixtures for
non-integrated CFLs classified as ``chandelier,'' ``decorative
pendant,'' and ``sconce/marker light'' all with base down lamp
orientations.\23\ DOE retains in this final rule that, for both
integrated and non-integrated CFLs, half the sample size be tested in
the base up and the other half in base down orientation.
---------------------------------------------------------------------------
\23\ DOE conducted a search using eLumit, an independently
owned, industry-neutral company that is a lighting search and
specification tool for design professionals. www.eLumit.com.
---------------------------------------------------------------------------
In the July 2015 NOPR, DOE also proposed to specify in 10 CFR
429.35 that any represented value of lumen maintenance at 40 percent of
lifetime must be based on a lifetime value that is equal to or greater
than the represented value of lifetime. DOE did not receive any
comments regarding this proposal; therefore, DOE adopts it in this
final rule.
2. Rapid Cycle Stress Testing
In the July 2015 NOPR, DOE proposed to restrict the sample size for
rapid cycle stress testing to an exact number of units. 80 FR 45742.
Currently, the sampling size for rapid cycle stress testing is
specified at 10 CFR 429.35(a)(2)(ii) as no less than 6 unique units.
DOE proposed specifying that exactly 6 unique units must be tested
[[Page 59409]]
per basic model for rapid cycle stress testing with the rationale that
this new specification will minimize confusion and improve consistency
in the number of samples used for testing. 80 FR 45742. This new
sampling requirement is consistent with the sample size requirement for
rapid cycle stress testing in the ENERGY STAR Lamps Specification V2.0.
DOE did not receive any comments related to the sample size for rapid-
cycle stress testing and therefore adopts the requirement in this final
rule that the sample size for rapid-cycle stress testing be 6 unique
units.
NEMA and OSI stated that lamp orientation has little effect on the
rapid cycle stress testing and suggested that testing half of the lamps
base up and half base down would be an additional burden that would not
affect the results of the rapid-cycle stress test. (NEMA, No. 9 at p.
10; OSI, No. 5 at p. 8)
Rapid cycle stress testing is intended to stress the lamp's
electrical components to evaluate the performance of a lamp undergoing
repeated cycling. Lamp orientation affects the thermal conditions of
the lamp. Because temperature has some impact on the performance of a
lamp's electrical components, testing in both base up and base down
orientations will provide a more comprehensive set of results for
assessing rapid cycle stress. Therefore, in this final rule, DOE
specifies in appendix W that for rapid cycle stress testing half of the
units must be tested in the base up position, and half of the units
must be tested in the base down position, but that if the position is
restricted by the manufacturer, units must be tested in the
manufacturer-specified position.
In the July 2015 CFL NOPR, DOE also proposed a new paragraph in 10
CFR 429.35 that any represented value of rapid cycle stress test
surviving units must be based on a lifetime value that is equal to or
greater than the represented value of lifetime. 80 FR 45742. DOE did
not receive any comments on this proposal and therefore, adopts it in
this final rule.
3. Lifetime of a Compact Fluorescent Lamp
In the July 2015 NOPR, DOE proposed clarifying the sampling
requirements for the lifetime of a CFL, including the position in which
lamps are tested. Specifically DOE proposed to align the sampling
requirements for lifetime with the sampling requirements for initial
lamp efficacy and lumen maintenance. DOE clarified that if more than 10
units are tested as part of the sample, the total number of units must
be a multiple of two and the time to failure value as determined per
section 3.3 of appendix W must be used to determine the represented
value of lifetime. 80 FR 45742. DOE did not receive any comments
regarding this proposal and therefore, in this final rule, adopts it as
proposed.
4. New Metrics
As discussed in section III.A.4 in this document, DOE establishes
test procedures for measuring new metrics including CRI, power factor,
CCT, start time, and standby mode energy consumption. For CRI, power
factor, CCT, and standby mode power, in the July 2015 NOPR, DOE
proposed requiring a sample size of at least 10 (half base up and half
base down). Testing in both the base up and base down positions
provides an accurate representation of performance under both
orientations since the end-use orientation is unknown. DOE also
proposed specifying within the sampling requirements for CRI, power
factor, CCT, and standby mode power, that, if more than 10 units are
tested as part of the sample, the total number of units must be a
multiple of two.
DOE proposed to specify the same sampling requirements for CRI and
power factor as those specified for initial lamp efficacy, lumen
maintenance at 1,000 hours, and lumen maintenance at 40 percent of
lifetime in 10 CFR 429.35. Thus, for CRI and power factor, DOE
determined that representations of these metrics be equal to the lesser
of the mean of the sample and the 97.5 percent LCL divided by 0.95.
Since higher values are desirable for CRI and power factor, use of the
lesser of the mean and LCL ensures that a representative value is
reported.
Because there are no targeted upper or lower bound values for CCT,
DOE proposed to specify in 10 CFR 429.35 that representations of CCT be
the mean of the sample.
For the start time, DOE proposed a sample size of three units in 10
CFR 429.35. DOE believes this is an appropriate sample size to
determine an accurate value for the lamp start time. Further, DOE
proposed that for start time, representations be equal to the greater
of the mean of the sample and the 97.5 percent upper confidence limit
(UCL) divided by 1.05, since lower values are desirable.
For standby mode power, DOE proposed to specify in 10 CFR 429.35 a
sample size of at least 10 units, consistent with that used for the
active mode power metric and initial lamp efficacy. DOE determined that
representations should be equal to the greater of the mean of the
sample and the 97.5 percent UCL divided by 1.05, as lower values are
desirable.
DOE notes that the current sampling requirements already require 10
units for determining lifetime, and that several of these metrics
(e.g., CRI, CCT, and power factor values) can be determined in the
course of lifetime testing. Additionally, this sampling plan is
consistent with the sampling requirements for these metrics in the
ENERGY STAR Lamps Specification v2.0.
OSI stated that power factor, CRI, and start time requirements are
not necessary and thus the proposed sampling requirements should not be
included. (OSI, No. 5 at p. 9) As noted previously, DOE is establishing
test procedures that include sampling requirements for power factor,
CRI, and start time, in support of the ongoing GSL standards rulemaking
(see section II for further details). Therefore, DOE retains the
sampling plan for these metrics in this final rule. However, DOE notes
that power factor and start time measurements are not applicable to or
required for non-integrated CFLs.
NEMA and OSI also commented on DOE's use of the lower confidence
level (LCL), UCL, and statistical divisor in determining represented
values. They argued that DOE's current methodology is biased and
statistically incorrect and recommended DOE use only the sample mean as
it is the best estimator of the population parameters. (NEMA, No. 9 at
p. 10; OSI, No. 5 at p. 9)
Confidence limits are a valid statistical method used to understand
the accuracy of the sample mean. By using confidence limits, DOE is
able to implement a conservative approach, ensuring that products on
the market perform at least as well as represented by manufacturers, by
requiring the lower confidence limit value if it is less than the
sample mean when higher values are desirable and requiring the upper
confidence limit if it is greater than the sample mean when lower
values are desirable. DOE finds this methodology more appropriate in
determining represented values than relying only on the sample mean.
Therefore, in this final rule, DOE retains the confidence limit
methodology for existing metrics and implements it for new metrics,
where applicable.
DOE also clarifies that on or after 180 days after publication of
this final rule, manufacturers of MBCFLs must use the test procedures
established in this final rule to certify compliance with existing
standards and for any representations regarding energy use or
efficiency, and manufacturers of other CFLs without existing standards
must use the test
[[Page 59410]]
procedures for any representations regarding energy use or efficiency.
As of the compliance date of any standards adopted in the GSL ECS
rulemaking, manufacturers must use the test procedures established in
this final rule to certify compliance with GSL standards, if adopted.
(See section III.J for further details regarding effective dates.)
Further, in this final rule, DOE specifies sampling requirements
specific to metrics of integrated CFLs and non-integrated CFLs.
5. Reuse of Samples
In the July 2015 NOPR, DOE proposed to specify in 10 CFR 429.35
that the same sample of units must be used to determine initial lamp
efficacy, lumen maintenance at 1,000 hours, lumen maintenance at 40
percent of lifetime, lifetime, CRI, CCT, power factor, start time, and
standby mode power. 80 FR 45743.
NEMA and OSI commented that reuse of samples should not be
mandatory except in the case of lumen maintenance values where a ratio
is required involving the initial measurements. NEMA and OSI stated
that the manufacturer should be permitted to use representative samples
and make measurements in parallel to reduce the time burden of
measurement. OSI also stated that this requirement would preclude large
sample size life tests in which the lamps would run uninterrupted until
failure. NEMA added that it is restrictive to require the same samples
for all tests completed for one basic model. (NEMA, No. 9 at p. 10-11;
OSI, No. 5 at p. 9) Philips commented that manufacturers should be
allowed to test larger populations for lifetime than for photometric-
related measurements. (Philips, Public Meeting Transcript, No. 4 at p.
90) GE recommended that, rather than requiring the reuse of a sample
across all tests, DOE should require that all test units must be drawn
from the same population. (GE, Public Meeting Transcript, No. 4 at pp.
91-95)
By requiring the same sample set to be used across all metrics, DOE
ensures sample units are not selected to obtain favorable measurements
for one metric over others and that all representative values are
internally consistent and representative of the population (to the
extent the selected test sample is representative of the population).
The lifetime measurement is just an extension of the other photometric
measurements taken at different points in time of the same lamp. DOE
believes taking these photometric measurements such as efficacy, lumen
maintenance, and lifetime on the same set of lamps will result in a
better characterization of the photometric performance of the
population by minimizing the variation that may be introduced into the
measurement by using different test units for different metrics. Hence,
the requirement of the same sample set allows for a more accurate
assessment of a basic model's compliance with standards for all
metrics. Therefore, DOE retains in this final notice that the same
sample of units must be used as the basis for representations for
standby power, power factor, CCT, CRI, initial lumen output, input
power, initial lamp efficacy, lumen maintenance at 1,000 hours, lumen
maintenance at 40 percent of lifetime, and lifetime; no less than three
units from the same sample of units must be used when testing for the
start time; and exactly six unique units must be used for rapid cycle
stress testing. Additionally, in this final rule, DOE specifies that
sample units must be comprised of production units. For those basic
models that currently make representations of the energy efficiency
metrics described in this test procedure, including medium base CFLs,
manufacturers must ensure that representations, including
certifications, are made in accordance with the DOE test procedure,
including sampling plan. While DOE believes manufacturers have been
following these testing procedures, including sampling plans, for
making current representations, DOE clarifies that a manufacturer may
need to retest in the event that the current representations are not
supported by the test when measured in accordance with the method being
adopted in this final rule, including the sampling plan.
6. Lamp Failures
In the July 2015 NOPR, DOE also clarified that, if a lamp breaks,
becomes defective, fails to stabilize, exhibits abnormal behavior such
as swirling or stops producing light, prior to the end of the seasoning
period, the lamp must be replaced with a new unit. 80 FR 45732. If a
lamp fails after the seasoning period, the lamp's measurements must be
included when calculating represented values. Id.
The CA IOUs stated that lamps that fail during lamp seasoning
(``early failure lamps'') should also be maintained in the sample and
new units should be added until the required units pass the seasoning
period. The CA IOUs stated that not including units that fail during
the seasoning period in the sample set will result in inaccurate
measurements of metrics. The CA IOUs gave the example where a
manufacturer might test 100 units, 90 of which would fail during
seasoning, and report the lifetime of the lamp based on the 10 units
that passed. The CA IOUs asserted that these early failures cause
consumer dissatisfaction related to CFL lifetime. Citing an ENERGY STAR
report \24\ the CA IOUs stated that the majority of verification
testing failures for CFLs in ENERGY STAR are related to tests for
product lifetime (e.g., interim life test, lumen maintenance, and rapid
cycle stress tests). Additionally, the CA IOUs and the EEAs cited a
study conducted by PEARL that found that 2 to 12 percent of the CFLs
tested failed to reach 40 percent of rated life. (CA IOUs, No. 7 at pp.
1-3; CA IOUs, Public Meeting Transcript, No. 4 at pp. 38-41, 89)
---------------------------------------------------------------------------
\24\ Overview of CFL Verification Testing Results Jan 2010-Apr
2014. EPA. 2014. www.energystar.gov/sites/default/files/specs/Presentation%20Verification%20Testing%207-31-14.pdf.
---------------------------------------------------------------------------
The CA IOUs further stated that the number of ``early failures''
should be recorded along with the time and manner of failure. The CA
IOUs also suggested that DOE require the entire sample set to be
discarded if one unit fails during seasoning in order to incentivize
manufacturers to produce higher quality products. Additionally, the CA
IOUs recommended DOE evaluate data on early CFL failures to verify that
the majority of early failures occur in the first 100 hours of
operation and increase this time interval for recording early failures,
if necessary. (CA IOUs, No. 7 at p. 3)
The EEAs supported CA IOUs written comments related to early
failures, noting that ignoring early failures would make it difficult
to develop metrics to address these failures. The EEAs added that lamps
that fail during seasoning would fall in the category of manufacturing
defect, a category of lamp failure identified in IES LM-65-14. (EEAs,
No. 8 at p. 3) GE (with Philips concurring) agreed that failures of
lamps ``right out of the box'' represented a manufacturing defect and
stated it is appropriate to remove these from the sample during
seasoning. (GE, Public Meeting Transcript, No. 4 at p. 38, Philips,
Public Meeting Transcript, No. 4 at p. 38) Westinghouse stated that its
products were not experiencing industry failures within the warranty
period, and definitely not within the first 100 hours. Westinghouse
added that lamps that did fail early would not pass DOE's verification
testing and therefore, would not be available on the market.
(Westinghouse, Public Meeting Transcript, No. 4, at pp. 40-41)
DOE evaluated the reports cited by CA IOUs and EEAs in their
comments, specifically, ENERGY STAR verification
[[Page 59411]]
test report of 2014 and the study conducted by PEARL. While both of
these reports indicate that there are lamps that fail to meet metrics
related to product lifetime, neither support that these failures are
due to lamps failing in the first 100 hours of the lamp lifetime. Both
documents only report failures before 40 percent of rated life as one
aggregated value with no data on actual time of failure. Further, DOE
evaluated results of a study conducted by the California Public Utility
Commission that provided data on the number of hours before failure for
72 models of MBCFLs with a sample set of 3601 lamps that were tested on
10 different cycling times. Of the 360 lamps tested on the 180 minute
cycling time, the same as the cycling time for lifetime testing, none
of the lamps failed during the first 100 hours of testing.\25\
---------------------------------------------------------------------------
\25\ CFL Laboratory Testing Report: Results from a CFL Switching
Cycle and Photometric Laboratory Study. December 9, 2015. California
Public Utilities Commission.
---------------------------------------------------------------------------
Based on available data, DOE finds that it is not common for CFLs
to fail before the seasoning period; therefore, the requirement that a
sample unit be replaced if it fails during seasoning will not result in
appreciably less accurate measurements. DOE notes that its proposed
method for addressing lamp failures aligns with ANSI C78.5-2003,\26\
which provides specifications on integrated CFLs and is referenced by
IES LM-65-14 (incorporated by reference). Section 6.1.2 of ANSI C78.5-
2003 notes that ``. . . if a unit fails to stabilize or exhibits
abnormal behavior, the lamp shall be discarded. Testing shall resume
with a suitable replacement specimen procured and prepared in the same
manner as the original specimen. The use of replacement specimens shall
be documented in the test report.'' Further, section 3.1 of IES LM-65-
14 states that lamp failures due to manufacturing defects are reported
but not included in the calculation of lamp lifetime. Therefore, in
this final rule, DOE retains the requirement that, if a lamp breaks,
becomes defective, fails to stabilize, exhibits abnormal behavior such
as swirling or stops producing light prior to the end of the seasoning
period, the lamp must be replaced with a new unit. DOE also notes that
ANSI C78.5-2003 and IES LM-65-14 recommend respectively, recording
replacement of sample units and failures. Because such data can be
informative, in this final rule, DOE adds the requirement that
manufacturers must provide in the certification report, the number of
sample units replaced within each unique sample set used in determining
represented values and believes that such information could be helpful
to consumers or interested parties in determining more reliable CFL
models, as requested by the CA IOUs and EEAs.
---------------------------------------------------------------------------
\26\ American National Standard For Electric Lamps:
Specifications for Performance of Self-Ballasted Compact Fluorescent
lamps (approved 2003).
---------------------------------------------------------------------------
I. Federal Trade Commission (FTC) Labeling Requirements
As discussed throughout this document, the CFL test procedure
adopted in this final rule is intended, among other things, to support
FTC's Lighting Facts Labeling program. Accordingly, in the July 2015
NOPR, DOE proposed adding provisions to 10 CFR 429 for initial lumen
output, input power, CCT, estimated annual energy cost, and life (in
years) for MBCFLs to enable FTC to allow manufacturers to submit data
through DOE's Compliance Certification Management System (CCMS) for the
FTC labeling requirements. 80 FR 45743. Except for CCT, these metrics
are already being determined as part of the existing test procedures in
appendix W. For example, initial lumen output and input power (a
standalone metric and also part of the calculation for estimated annual
energy cost) are the two quantities required to calculate the existing
metric of initial lamp efficacy. Furthermore, the life (expressed in
years) is determined by dividing the existing metric of lifetime by an
average operating hour value specified by FTC.
NEMA stated that the test procedures should not be developed for
lamps not regulated by FTC. NEMA highlighted the fact that FTC's label
does not cover non-integrated CFLs and reiterated that non-integrated
CFLs should not be included in the test procedure. (NEMA, No. 9 at p.
2)
As noted previously, the test procedures that are the subject of
this rulemaking are intended to support existing and potential
standards for CFLs and ENERGY STAR lamp and luminaire specifications,
as well as support the FTC Lighting Facts labeling requirements. DOE
did not receive any other comments related to the proposed provisions
for DOE to collect FTC Lighting Facts labeling data through DOE's CCMS.
Therefore, in this final rule, DOE adopts the provisions as described
in this preamble.
J. Effective Date
In the July 2015 NOPR, DOE specified that the effective date for
the amended test procedures would be 30 days after publication of the
final rule in the Federal Register. 80 FR 45743. Representations based
on the amended and new test procedures would be required as of 180 days
after publication of the final rule. (42 U.S.C. 6293(c)(2)) DOE
received several comments regarding these dates and certifications of
compliance for products according to the new and amended test
procedures.
NEMA and OSI asked DOE to provide clarification on the need to
retest lamps that are already certified in the CCMS database, or if
industry is allowed to use existing test reports for current products.
(NEMA, No. 9 at p. 2; OSI, No. 5 at p. 2) OSI also sought clarification
from DOE regarding the disposition of existing inventory if retesting
is required for current products. (OSI, No.5 at p. 2)
Representations related to the metrics addressed in the amended
Appendix W must reflect testing in accordance with Appendix W not later
than February 27, 2017. Representations are not required by DOE for
CFLs not currently subject to standards (although they may be required
by the FTC). In contrast, certifications of compliance are required for
medium base CFLs, which are currently subject to standards; those
certifications must reflect testing in accordance with the amended
Appendix W as of the next annual certification date or February 27,
2017, whichever is later. DOE also reiterates, as noted throughout this
document, that the new and amended test procedures are not anticipated
to result in changes in measured energy consumption or other
performance metrics for any products that are currently subject to
energy conservation standards and thus required to certify compliance
to DOE. Therefore, existing medium base CFLs may not require re-testing
if their representative values continue to be valid.
Certifications of compliance for basic models of CFLs with any new
and/or amended energy conservation standards must reflect testing in
accordance with Appendix W as amended in this final rule, prior to
distribution in commerce, and annually thereafter by the filing date
specified in 10 CFR 429.12(d); however, no basic model is required to
be certified until it is required to comply with energy conservation
standards. Therefore, for CFLs not currently subject to standards, the
initial certification report must be filed by the compliance date of
any new energy conservation standards.
NEMA and OSI stated that due to the additional testing required by
the new and amended test procedures established in this final rule, it
was not practical to certify all lamps to the new and amended test
procedures by the next annual filing date for certification.
[[Page 59412]]
In particular, OSI cited changes to the sample size and orientation;
and NEMA added testing for rapid cycle stress. NEMA and OSI noted that
publication of the final rule for the ongoing GSL standards rulemaking
is expected before the end of 2017. They requested that until March 1,
2018, only new CFLs certified after the publication of this test
procedure final rule be required to be tested under the new and amended
CFL test procedures established by it; and after March 1, 2018, all
CFLs must be tested under the new and amended CFL test procedures. NEMA
and OSI reasoned this would minimize testing burden on industry for
current products that are expected to be rendered obsolete by the
ongoing GSL standards rulemaking. (NEMA, No. 9 at p. 11; OSI, No. 5 at
p. 9)
The change in sample size and orientation requirements adopted in
this final rule align with ENERGY STAR Lamps Specification V2.0
(effective January 1, 2017) and its previous version, with the only
exception being that DOE is requiring 3 units tested base up, and 3
units tested base down for the rapid cycle stress test. DOE notes that
two thirds of compact fluorescent lamps already comply with ENERGY
STAR, which already requires 10 units to be tested, and does not
believe the change in orientation requirements for the rapid cycle
stress test would require an extensive change to the existing test
setup. While DOE is adopting test procedures for additional metrics,
several of these metrics (e.g., CCT, CRI, power factor) can be
determined simultaneously with existing metrics such as efficacy, and
therefore testing new metrics would not require a significant amount of
additional time to conduct.
Further for new basic models or existing basic models that require
retesting because their certified values are no longer valid, if a
metric requires a longer period of time to test (lifetime, lumen
maintenance at 40 percent of lifetime), DOE allows for the reporting of
estimated values until the testing is complete. Therefore, DOE finds
that manufacturers should be able to certify and make representations
of all applicable CFL products within 180 days of the publication of
this final rule. Hence, the effective date for the new and amended test
procedures discussed in this final rule will be 30 days after
publication of this document in the Federal Register. Representations
must reflect testing in accordance with the new and amended test
procedure not later than 180 days after publication of the final rule.
(42 U.S.C. 6293(c)(2))
After the effective date and prior to 180 days following
publication of this CFL test procedure final rule, manufacturers may
voluntarily begin to make representations with respect to the energy
use or efficiency of CFLs (including but not limited to MBCFLs) using
the results of testing pursuant to this final rule. On or after 180
days after publication of this final rule, any representations
including certifications of compliance (if required), made with respect
to the energy use or efficiency of CFLs (including but not limited to
MBCFLs) must be made in accordance with the results of testing pursuant
to the new and amended test procedures.
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget (OMB) has determined that test
procedure rulemakings do not constitute ``significant regulatory
actions'' under section 3(f) of Executive Order 12866, Regulatory
Planning and Review, 58 FR 51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under the Executive Order by the
Office of Information and Regulatory Affairs (OIRA) in OMB.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq.) requires
preparation of an initial regulatory flexibility analysis (IFRA) for
any rule that by law must be proposed for public comment and a final
regulatory flexibility analysis (FRFA) for any such rule that an agency
adopts as a final rule, unless the agency certifies that the rule, if
promulgated, will not have a significant economic impact on a
substantial number of small entities. As required by Executive Order
13272, ``Proper Consideration of Small Entities in Agency Rulemaking,''
67 FR 53461 (August 16, 2002), DOE published procedures and policies on
February 19, 2003 to ensure that the potential impacts of its rules on
small entities are properly considered during the DOE rulemaking
process. 68 FR 7990. DOE has made its procedures and policies available
on the Office of the General Counsel's Web site: https://energy.gov/gc/office-general-counsel.
DOE reviewed this final rule, which amends and establishes new test
procedures for CFLs, under the provisions of the Regulatory Flexibility
Act and the procedures and policies published on February 19, 2003. DOE
certifies that the rule will not have a significant economic impact on
a substantial number of small entities. The factual basis for this
certification is as follows.
The Small Business Administration (SBA) considers a business entity
to be a small business, if, together with its affiliates, it employs
less than a threshold number of workers specified in 13 CFR part 121.
These size standards and codes are established by the North American
Industry Classification System (NAICS). Manufacturing of CFLs is
classified under NAICS 335110, ``Electric Lamp Bulb and Part
Manufacturing.'' The SBA sets a threshold of 1,250 employees or less
for an entity to be considered as a small business for this category.
DOE conducted a focused market survey reviewing information from
trade associations such as NEMA; ENERGY STAR programs; market reports
(e.g. Hoover's reports); and individual company Web sites to identify
companies that sell products covered by this rulemaking. DOE then
determined the number of small businesses based on SBA definition. In
its estimation of a company's number of employees, DOE also includes
any parent companies and/or subsidiaries. In the July 2015 NOPR, DOE
identified 26 manufacturers that would be considered small businesses.
80 FR 45744. Westinghouse indicated the number of small businesses
identified by DOE was less than expected, noting that there are only a
handful of large-size businesses in the market. (Westinghouse, Public
Meeting Transcript, No. 4 at pp. 134-136)
For this final rule, DOE reviewed its estimated number of small
businesses. DOE updated its list of small businesses by reviewing
information from trade associations such as NEMA; ENERGY STAR programs;
market reports (e.g. Hoover's reports); and individual company Web
sites to identify companies that sell CFLs in the United States. DOE
screened out companies that do not offer products covered by this
rulemaking, do not meet the definition of a ``small business,'' or are
completely foreign owned and operated. DOE determined that there are no
small businesses that maintain domestic production facilities for CFLs.
Based on the criteria outlined earlier and the reasons discussed
above, DOE certifies that the test procedures adopted in this final
rule would not have a significant economic impact on a substantial
number of small entities, and the preparation of a final regulatory
flexibility analysis is not warranted. DOE has submitted a
certification and supporting statement of factual basis to the Chief
Counsel for Advocacy of the SBA for review under 5 U.S.C. 605(b).
[[Page 59413]]
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of CFLs must certify to DOE that their products
comply with any applicable energy conservation standards. To certify
compliance, manufacturers must first obtain test data for their
products according to the DOE test procedures, including any amendments
adopted for those test procedures. DOE has established regulations for
the certification and recordkeeping requirements for all covered
consumer products and commercial equipment, including CFLs. See
generally 10 CFR part 429, subpart B. The collection-of-information
requirement for the certification and recordkeeping is subject to
review and approval by OMB under the Paperwork Reduction Act (PRA).
This requirement has been approved by OMB under OMB control number
1910-1400. Public reporting burden for the certification is estimated
to average 30 hours per response including the time for reviewing
instructions, searching existing data sources, gathering and
maintaining the data needed, and completing and reviewing the
collection of information.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a current valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
In this final rule, DOE is approving test procedure amendments that
it expects will be used to develop and implement future energy
conservation standards for CFLs. DOE has determined that this rule
falls into a class of actions that are categorically excluded from
review under the National Environmental Policy Act of 1969 (42 U.S.C.
4321 et seq.) and DOE's implementing regulations at 10 CFR part 1021.
Specifically, this rule amends an existing rule without affecting the
amount, quality or distribution of energy usage, and, therefore, will
not result in any environmental impacts. Thus, this rulemaking is
covered by Categorical Exclusion A5 under 10 CFR part 1021, subpart D,
which applies to any rulemaking that interprets or amends an existing
rule without changing the environmental effect of that rule.
Accordingly, neither an environmental assessment nor an environmental
impact statement is required.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 4,
1999), imposes certain requirements on agencies formulating and
implementing policies or regulations that preempt State law or that
have Federalism implications. The Executive Order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States and
to carefully assess the necessity for such actions. The Executive Order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have Federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. 65 FR 13735. DOE examined this final
rule and determined that it will not have a substantial direct effect
on the States, on the relationship between the national government and
the States, or on the distribution of power and responsibilities among
the various levels of government. EPCA governs and prescribes Federal
preemption of State regulations as to energy conservation for the
products that are the subject of this final rule. States can petition
DOE for exemption from such preemption to the extent, and based on
criteria, set forth in EPCA. (42 U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
Eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically requires that Executive agencies make every reasonable
effort to ensure that the regulation: (1) Clearly specifies the
preemptive effect, if any; (2) Clearly specifies any effect on existing
Federal law or regulation; (3) provides a clear legal standard for
affected conduct while promoting simplification and burden reduction;
(4) specifies the retroactive effect, if any; (5) adequately defines
key terms; and (6) addresses other important issues affecting clarity
and general draftsmanship under any guidelines issued by the Attorney
General. Section 3(c) of Executive Order 12988 requires Executive
agencies to review regulations in light of applicable standards in
sections 3(a) and 3(b) to determine whether they are met or it is
unreasonable to meet one or more of them. DOE has completed the
required review and determined that, to the extent permitted by law,
this final rule meets the relevant standards of Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (UMRA)
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. Public Law 104-4, sec. 201 (codified at 2 U.S.C. 1531).
For a regulatory action resulting in a rule that may cause the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector of $100 million or more in any one year
(adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The UMRA also requires a Federal agency to
develop an effective process to permit timely input by elected officers
of State, local, and Tribal governments on a proposed ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect small governments. On March 18, 1997,
DOE published a statement of policy on its process for
intergovernmental consultation under UMRA. 62 FR 12820; also available
at https://energy.gov/gc/office-general-counsel. DOE examined this final
rule according to UMRA and its statement of policy and determined that
the rule contains neither an intergovernmental mandate nor a mandate
that may result in the expenditure of $100 million or more in any year,
so these requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Public Law 105-277) requires Federal agencies to issue a
Family Policymaking Assessment for any rule
[[Page 59414]]
that may affect family well-being. This final rule will not have any
impact on the autonomy or integrity of the family as an institution.
Accordingly, DOE has concluded that it is not necessary to prepare a
Family Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights'' 53 FR 8859 (March 18, 1988), that this regulation will not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (Feb. 22, 2002), and
DOE's guidelines were published at 67 FR 62446 (Oct. 7, 2002). DOE has
reviewed this final rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OMB,
a Statement of Energy Effects for any significant energy action. A
``significant energy action'' is defined as any action by an agency
that promulgated or is expected to lead to promulgation of a final
rule, and that (1) is a significant regulatory action under Executive
Order 12866, or any successor order; and (2) is likely to have a
significant adverse effect on the supply, distribution, or use of
energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any significant energy action, the
agency must give a detailed statement of any adverse effects on energy
supply, distribution, or use if the regulation is implemented, and of
reasonable alternatives to the action and their expected benefits on
energy supply, distribution, and use.
This regulatory action is not a significant regulatory action under
Executive Order 12866. Moreover, it would not have a significant
adverse effect on the supply, distribution, or use of energy, nor has
it been designated as a significant energy action by the Administrator
of OIRA. Therefore, it is not a significant energy action, and,
accordingly, DOE has not prepared a Statement of Energy Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Public Law 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of
the Federal Energy Administration Act of 1974, as amended by the
Federal Energy Administration Authorization Act of 1977. (15 U.S.C.
788; FEAA) Section 32 essentially provides in relevant part that, where
a proposed rule authorizes or requires use of commercial standards, the
notice of proposed rulemaking must inform the public of the use and
background of such standards. In addition, section 32(c) requires DOE
to consult with the Attorney General and the Chairman of the Federal
Trade Commission (FTC) concerning the impact of the commercial or
industry standards on competition.
This final rule incorporates by reference the testing methods and
modifications to the test procedures that are contained in the
following commercial standards:
(1) ANSI C78.901-2014, ``American National Standard for Electric
Lamps--Single-Based Fluorescent Lamps--Dimensional and Electrical
Characteristics,'' 2014;
(2) CIE 13.3-1995, ``Technical Report: Method of Measuring and
Specifying Colour Rendering Properties of Light Sources,'' 1995;
(3) CIE 15:2004, ``Technical Report: Colorimetry, 3rd edition,''
2004;
(4) IES LM-54-12, ``IES Guide to Lamp Seasoning,'' 2012;
(5) IES LM-65-14, ``IES Approved Method for Life Testing of
Single-Based Fluorescent Lamps,'' 2014;
(6) IES LM-66-14, ``IES Approved Method for the Electrical and
Photometric Measurements of Single-Based Fluorescent Lamps,'' 2014;
(7) IESNA LM-78-07, :IESNA Approved Method for Total Luminous
Flux Measurement of Lamp Using an Integrated Sphere Photometer,''
2007; and
(8) IEC Standard 62301 (Edition 2.0, 2011-01), ``Household
electrical appliances--Measurement of standby power,'' 2011.
Although these test procedures are not exclusively based on these
industry testing standards, some components of the DOE test procedure
adopt definitions, test parameters, and measurement techniques from
them without amendment. The Department has evaluated these industry
testing standards and is unable to conclude whether they fully comply
with the requirements of section 32(b) of the FEAA (i.e., that they
were developed in a manner that fully provides for public
participation, comment, and review). DOE has consulted with both the
Attorney General and the Chairman of the FTC about the impact on
competition of using the methods contained in these standards and has
received no comments objecting to their use.
M. Description of Materials Incorporated by Reference
DOE incorporates by reference the test standard published by ANSI,
titled ``American National Standard for Electric Lamps--Single-Based
Fluorescent Lamps--Dimensional and Electrical Characteristics,'' ANSI
C78.901-2014. ANSI C78.901-2014 is an industry accepted test standard
that specifies physical and electrical characteristics of non-
integrated CFLs and is applicable to products sold in North America. It
is used to identify the appropriate reference ballast specifications
for CFL as described in this final rule. ANSI C78.901-2014 is readily
available on ANSI's Web site at https://webstore.ansi.org/.
DOE incorporates by reference the test standard published by IES,
titled ``IES Guide to Lamp Seasoning,'' IES LM-54-12. IES LM-54-12 is
an industry accepted test standard that specifies a method for
seasoning CFLs prior to testing and is applicable to products sold in
North America. The test procedures adopted in this final rule reference
various sections of IES LM-54-12 that address seasoning of CFLs prior
to testing. IES LM-54-12 is readily available on IES's Web site at
www.ies.org/store.
DOE also incorporates by reference the test standard published by
IES, titled ``IES Approved Method for Life Testing of Single-Based
Fluorescent Lamps,'' IES LM-65-14. IES LM-65-14 is an industry accepted
test standard that specifies a method for measuring the time to failure
of CFLs and is applicable to products sold in North America. The test
procedures adopted in this final rule reference various sections of IES
LM-65-14 that address test conditions and procedures for measuring time
to failure and rapid cycle stress testing of CFLs. IES LM-65-14 is
readily available on IES's Web site at www.ies.org/store.
DOE also incorporates by reference specific sections of the test
standard published by IES, titled ``IES Approved Method: Electrical and
Photometric Measurements of Single-Based Fluorescent Lamps,'' IES LM-
66-14. IES LM-66-14 is an industry accepted test
[[Page 59415]]
standard that specifies a method for measuring electrical and
photometric characteristics of CFLs and is applicable to products sold
in North America. The test procedures adopted in this final rule
reference various sections of IES LM-66-14 that address test conditions
and procedures for taking electrical and photometric measurements of
CFLs. IES LM-66-14 is readily available on IES's Web site at
www.ies.org/store.
DOE also incorporates by reference the test standard published by
IES, titled ``IESNA Approved Method for Total Luminous Flux Measurement
of Lamps Using an Integrating Sphere Photometer,'' IESNA LM-78-07.
IESNA LM-78-07 is an industry accepted test standard that specifies a
method for measuring lumen output in an integrated sphere and is
applicable to products sold in North America. The test procedures
adopted in this final rule reference sections of IESNA LM-78-07 that
address measurements of lumen output. IESNA LM-78-07 is readily
available on IES's Web site at www.ies.org/store.
DOE also incorporates by reference certain sections of the test
standard published by IEC, titled ``Household electrical appliances--
Measurement of standby power,'' IEC Standard 62301 (Edition 2.0). IEC
Standard 62301 (Edition 2.0) is an industry accepted test standard that
describes measurements of electrical power consumption in standby mode,
off mode, and network mode. The test procedures adopted in this final
rule reference sections of IEC Standard 62301 (Edition 2.0) for testing
standby mode power consumption of CFLs. IEC Standard 62301 (Edition
2.0) is readily available on ANSI's Web site at https://webstore.iec.ch/home.
DOE also incorporates by reference the test standard published by
CIE, titled ``Technical Report: Method of Measuring and Specifying
Colour Rendering Properties of Light Sources,'' CIE 13.3-1995. CIE
13.3-1995 is an industry accepted test standard that specifies method
of measuring and specifying color rendering properties of light sources
based on resultant color shifts of test objects. The test procedures
adopted in this final rule reference sections of CIE 13.3-1995 for
testing CRI of CFLs. CIE 13.3-1995 is readily available on CIE's Web
site at https://www.techstreet.com/cie/.
DOE incorporates by reference the test standard published by CIE,
titled ``Technical Report: Colorimetry,'' CIE 15:2004. CIE 15:2004 is
an industry accepted test standard that summarizes colorimetric data.
The test procedures adopted in this final rule reference sections of
CIE 15:2004 for testing CCT of CFLs. CIE 15:2004 is readily available
on CIE's Web site at https://www.techstreet.com/cie/.
DOE removes previously incorporated reference to ``ENERGY STAR
Program Requirements for [Compact Fluorescent Lamps] CFLs, approved
August 9, 2001.'' These provided specifications including test
procedures for ENERGY STAR qualified CFLs. The test procedures adopted
in this final rule no longer reference ``ENERGY STAR Program
Requirements for [Compact Fluorescent Lamps] CFLs, approved August 9,
2001.''
N. Congressional Notification
As required by 5 U.S.C. 801, DOE will report to Congress on the
promulgation of this rule before its effective date. The report will
state that it has been determined that the rule is not a ``major rule''
as defined by 5 U.S.C. 804(2).
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this final
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Reporting and recordkeeping requirements.
10 CFR Part 430
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Incorporation by reference, Intergovernmental relations, Small
businesses.
Issued in Washington, DC, on August 11, 2016.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
For the reasons stated in the preamble, DOE amends parts 429 and
430 of Chapter II of Title 10, Code of Federal Regulations as set forth
below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317.
0
2. Section 429.12 is amended by revising paragraph (f) to read as
follows:
Sec. 429.12 General requirements applicable to certification reports.
* * * * *
(f) Discontinued model filing. When production of a basic model has
ceased and it is no longer being sold or offered for sale by the
manufacturer or private labeler, the manufacturer must report this
discontinued status to DOE as part of the next annual certification
report following such cessation. For each basic model, the report must
include the information specified in paragraphs (b)(1) through (7) of
this section, except that for integrated light-emitting diode lamps and
for compact fluorescent lamps, the manufacturer must submit a full
certification report, including all of the information required by
paragraph (b) of this section and the product-specific information
required by Sec. 429.56(b)(2) or Sec. 429.35(b)(2), respectively.
* * * * *
0
3. Section 429.35 is revised to read as follows:
Sec. 429.35 Compact fluorescent lamps.
(a) Determination of Represented Value. Manufacturers must
determine represented values, which include the certified ratings, for
each basic model of compact fluorescent lamp by testing, in conjunction
with the following sampling provisions:
(1) Units to be tested. (i) The requirements of Sec. 429.11(a) are
applicable except that the sample must be comprised of production
units; and
(ii)(A) For each basic model of integrated compact fluorescent
lamp, the minimum number of units tested shall be no less than 10 units
when testing for the initial lumen output, input power, initial lamp
efficacy, lumen maintenance at 1,000 hours, lumen maintenance at 40
percent of lifetime, lifetime, CCT, CRI, power factor, and standby mode
power. If more than 10 units are tested as part of the sample, the
total number of units must be a multiple of 2. The same sample of units
must be used as the basis for representations for initial lumen output,
input power, initial lamp efficacy, lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of lifetime, lifetime, CCT, CRI, power
factor, and standby mode power. No less than three units from the same
sample of units must be used when testing for the start time. Exactly
six unique units (i.e., units that have not previously been tested
under this paragraph (a)(1)(ii) but are representative of the same
basic model tested under this paragraph (a)(1)(ii)) must be used for
rapid cycle stress testing.
[[Page 59416]]
(B) For each basic model of non-integrated compact fluorescent
lamp, the minimum number of units tested shall be no less than 10 units
when testing for the initial lumen output, input power, initial lamp
efficacy, lumen maintenance at 40 percent of lifetime, lifetime, CCT,
and CRI. If more than 10 units are tested as part of the sample, the
total number of units must be a multiple of 2. The same sample of units
must be used as the basis for representations for initial lumen output,
input power, initial lamp efficacy, lumen maintenance at 40 percent of
lifetime, lifetime, CCT, and CRI.
(iii) For each basic model, a sample of sufficient size shall be
randomly selected and tested to ensure that:
(A) Represented values of initial lumen output, initial lamp
efficacy, lumen maintenance at 1,000 hours, lumen maintenance at 40
percent of lifetime, CRI, power factor, or other measure of energy
consumption of a basic model for which consumers would favor higher
values must be less than or equal to the lower of:
(1) The mean of the sample,
[GRAPHIC] [TIFF OMITTED] TR29AU16.014
Where:
x is the sample mean,
n is the number of units in the sample, and
xi is the i\th\ unit;
Or,
(2) The lower 97.5-percent confidence limit (LCL) of the true mean
divided by 0.95,
[GRAPHIC] [TIFF OMITTED] TR29AU16.015
Where:
x is the sample mean of the characteristic value;
s is the sample standard deviation;
n is the number of units in the sample, and
tg0.975 is the t statistic for a 97.5% one-tailed
confidence interval with n-1 degrees of freedom (from appendix A of
this subpart).
(B) Represented values of input power, standby mode power, start
time or other measure of energy consumption of a basic model for which
consumers would favor lower values must be greater than or equal to the
higher of:
(1) The mean of the sample,
[GRAPHIC] [TIFF OMITTED] TR29AU16.016
Where:
x is the sample mean,
ng is the number of units in the sample, and
xgi is the ith unit;
Or,
(2) The upper 97.5-percent confidence limit (UCL) of the true mean
divided by 1.05,
[GRAPHIC] [TIFF OMITTED] TR29AU16.017
Where:
x is the sample mean of the characteristic value;
sg is the sample standard deviation;
ng is the number of units in the sample, and
tg0.975 is the t statistic for a 97.5% one-tailed
confidence interval with n-1 degrees of freedom (from appendix A of
this subpart).
(C) The represented value of CCT must be equal to the mean of the
sample,
[GRAPHIC] [TIFF OMITTED] TR29AU16.018
Where:
x is the sample mean,
ng is the number of units in the sample, and
xgi is the ith unit.
(D) The represented value of lifetime must be equal to or less than
the median time to failure of the sample (calculated as the arithmetic
mean of the time to failure of the two middle sample units when the
numbers are sorted in value order).
(E) The represented value of the results of rapid cycle stress
testing must be
(1) Expressed in the number of surviving units and
(2) Based on a lifetime value that is equal to or greater than the
represented value of lifetime.
(2) The represented value of life (in years) of a compact
fluorescent lamp must be calculated by dividing the represented
lifetime of a compact fluorescent lamp as determined in (a)(1) of this
section by the estimated annual operating hours as specified in 16 CFR
305.15(b)(3)(iii).
(3) The represented value of the estimated annual energy cost for a
compact fluorescent lamp, expressed in dollars per year, must be the
product of the input power in kilowatts, an electricity cost rate as
specified in 16 CFR 305.15(b)(1)(ii), and an estimated average annual
use as specified in 16 CFR 305.15(b)(1)(ii).
(4) For compliance with standards specified in Sec. 430.32(u) as
it appeared in 10 CFR parts 200-499 edition revised as of January 1,
2016, initial lamp efficacy may include a 3 percent tolerance added to
the value determined in accordance with paragraph (a)(1)(iii)(A) of
this section.
(5) The represented value of lumen maintenance at 40 percent of
lifetime must be based on a lifetime value that is equal to or greater
than the represented value of lifetime.
(6) Estimated values may be used for representations when initially
testing a new basic model or when new/additional testing is required.
(b) Certification reports. (1) The requirements of Sec. 429.12 are
applicable to compact fluorescent lamps; and
(2) Values reported in certification reports are represented
values. Pursuant to Sec. 429.12(b)(13), a certification report shall
include the following public product-specific information:
(i) For each basic model of medium base CFL when certifying
compliance to the standards in Sec. 430.32(u) as it appeared in 10 CFR
parts 200-499 edition revised as of January 1, 2016, the testing
laboratory's ILAC accreditation body's identification number or other
approved identification assigned by the ILAC accreditation body, the
date of first manufacture, the seasoning time in hours (h), the initial
lumen output in lumens (lm), the input power in watts (W), the initial
lamp efficacy in lumens per watt (lm/W), the number of sample units
replaced during the seasoning period within each unique sample set used
in determining the represented value, the lumen maintenance at 40
percent of lifetime in percent (%) (and whether value is estimated),
the lifetime in hours (h) (and whether value is estimated), life in
years (and whether value is estimated), the lumen maintenance at 1,000
hours in percent (%), and the results of rapid cycle stress testing in
number of units passed. or the initial certification of new basic
models or any subsequent certification based on new testing, estimates
of lifetime, life, lumen maintenance at 40 percent of lifetime, and
rapid cycle stress test surviving units may be reported (if indicated
in the certification report) until testing is complete. When reporting
estimated values, the certification report must specifically describe
the prediction method, which must be generally representative of the
methods specified in appendix W. Manufacturers are required to maintain
records in accordance with Sec. 429.71 of the development of all
estimated values and any associated initial test data.
(ii) For each basic model of integrated CFL when certifying
compliance with general service lamp energy conservation standards, the
testing laboratory's ILAC accreditation body's identification number or
other identification assigned by the ILAC accreditation body, the date
of first manufacture, a statement that the
[[Page 59417]]
compact fluorescent lamp is integrated, the seasoning time in hours
(h), the initial lumen output in lumens (lm), the input power in watts
(W), the initial lamp efficacy in lumens per watt (lm/W), the CCT in
kelvin (K), CRI, the lumen maintenance at 1,000 hours in percent (%),
the lumen maintenance at 40 percent of lifetime in percent (%) (and
whether value is estimated), start time in milliseconds, power factor,
standby mode energy consumption in watts (W), the results of rapid
cycle stress testing in number of units passed, the lifetime in hours
(h) (and whether value is estimated), life in years (and whether value
is estimated), and the number of sample units replaced during the
seasoning period within the sample set used in determining the
represented value. Estimates of lifetime, life, lumen maintenance at 40
percent of lifetime, and rapid cycle stress test surviving units may be
reported (if indicated in the certification report) until testing is
complete. When reporting estimated values, the certification report
must specifically describe the prediction method, which must be
generally representative of the methods specified in appendix W.
Manufacturers are required to maintain records in accordance with Sec.
429.71 of the development of all estimated values and any associated
initial test data.
(iii) For each basic model of non-integrated CFL when certifying
compliance with general service lamp energy conservation standards, the
testing laboratory's ILAC accreditation body's identification number or
other identification assigned by the ILAC accreditation body, the date
of first manufacture, a statement that the compact fluorescent lamp is
non-integrated, the initial lumen output in lumens (lm), the input
power in watts (W), the initial lamp efficacy in lumens per watt (lm/
W), the CCT in kelvin (K), CRI, the lumen maintenance at 40 percent of
lifetime in percent (%) (and whether value is estimated), the lifetime
in hours (h) (and whether value is estimated), and the number of sample
units replaced during the seasoning period within each unique sample
set used in determining the represented value. Estimates of lifetime
and lumen maintenance at 40 percent of lifetime may be reported (if
indicated in the certification report) until testing is complete. When
reporting estimated values, the certification report must specifically
describe the prediction method, which must be generally representative
of the methods specified in appendix W. Manufacturers are required to
maintain records in accordance with Sec. 429.71 of the development of
all estimated values and any associated initial test data.
(c) Rounding requirements. For represented values,
(1) Round input power to the nearest tenth of a watt.
(2) Round lumen output to three significant digits.
(3) Round initial lamp efficacy to the nearest tenth of a lumen per
watt.
(4) Round lumen maintenance at 1,000 hours to the nearest tenth of
a percent.
(5) Round lumen maintenance at 40 percent of lifetime to the
nearest tenth of a percent.
(6) Round CRI to the nearest whole number.
(7) Round power factor to the nearest hundredths place.
(8) Round lifetime to the nearest whole hour.
(9) Round CCT to the nearest 100 kelvin (K).
(10) Round standby mode power to the nearest tenth of a watt; and
(11) Round start time to the nearest whole millisecond.
PART 430--ENERGY CONSERVATION PROGRAM FOR CONSUMER PRODUCTS
0
4. The authority citation for part 430 continues to read as follows:
Authority: 42 U.S.C. 6291-6309; 28 U.S.C. 2461 note.
0
5. Section 430.2 is amended by:
0
a. Adding in alphabetical order a definition for ``compact fluorescent
lamp'';
0
b. Revising the definition of ``correlated color temperature''; and
0
c. Adding in alphabetical order adefinition for ``lifetime of a compact
fluorescent lamp''.
The additions and revision read as follows:
Sec. 430.2 Definitions.
* * * * *
Compact fluorescent lamp (CFL) means an integrated or non-
integrated single-base, low-pressure mercury, electric-discharge source
in which a fluorescing coating transforms some of the ultraviolet
energy generated by the mercury discharge into light; the term does not
include circline or U-shaped lamps.
* * * * *
Correlated color temperature (CCT) means the absolute temperature
of a blackbody whose chromaticity most nearly resembles that of the
light source.
* * * * *
Lifetime of a compact fluorescent lamp means the length of
operating time between first use and failure of 50 percent of the
sample units (as specified in Sec. 429.35(a)(1) of this chapter),
determined in accordance with the test procedures described in section
3.3 of appendix W to subpart B of this part.
* * * * *
0
6. Section 430.3 is amended by:
0
a. Redesignating paragraphs (e)(8) through (19) as paragraphs (e)(9)
through (20), respectively, and adding new paragraph (e)(8);
0
b. Removing ``appendix R'' in paragraphs (l)(1) and (2) and adding in
its place ``appendices R and W'';
0
c. Redesignating paragraph (o)(9) as (o)(13), paragraph (o)(10) as
(o)(14), paragraph (o)(11) as (o)(15), and paragraph (o)(12) as
(o)(16), paragraph (o)(8) as (o)(10), and paragraph (o)(7) as (o)(8),;
0
d. Adding new paragraphs (o)(7), (9), (11), and (12);
0
e. Adding paragraph (p)(7); and
0
f. Removing paragraph (v).
The additions read as follows:
Sec. 430.3 Materials incorporated by reference.
* * * * *
(e) * * *
(8) ANSI C78.901-2014, American National Standard for Electric
Lamps--Single-Based Fluorescent Lamps--Dimensional and Electrical
Characteristics, ANSI approved July 2, 2014; IBR approved for appendix
W to subpart B.
* * * * *
(o) * * *
(7) IES LM-54-12, IES Guide to Lamp Seasoning, approved October 22,
2012; IBR approved for appendix W to subpart B, as follows:
(i) Section 4--Physical/Environmental Test Conditions;
(ii) Section 5--Electrical Test Conditions;
(iii) Section 6--Test Procedure Requirements: Section 6.1--Test
Preparation; and
(iv) Section 6--Test Procedure Requirements, Section 6.2--Seasoning
Test Procedures: Section 6.2.2.1--Discharge Lamps: Discharge Lamps
except T5 fluorescent.
* * * * *
(9) IES LM-65-14, IES Approved Method for Life Testing of Single-
Based Fluorescent Lamps, approved December 30, 2014; IBR approved for
appendix W to subpart B, as follows:
(i) Section 4.0--Ambient and Physical Conditions;
(ii) Section 5.0--Electrical Conditions; and
(iii) Section 6.0--Lamp Test Procedures
* * * * *
[[Page 59418]]
(11) IES LM-66-14, (``IES LM-66''), IES Approved Method for the
Electrical and Photometric Measurements of Single-Based Fluorescent
Lamps, approved December 30, 2014; IBR approved for appendix W to
subpart B, as follows:
(i) Section 4.0--Ambient and Physical Conditions;
(ii) Section 5.0--Power Source Characteristics; and
(iii) Section 6.0--Testing Procedures Requirements.
(12) IESNA LM-78-07, IESNA Approved Method for Total Luminous Flux
Measurement of Lamps Using an Integrating Sphere Photometer, approved
January 28, 2007; IBR approved for appendix W to subpart B.
* * * * *
(p) * * *
(7) IEC 62301, (``IEC 62301-W''), Household electrical appliances--
Measurement of standby power, (Edition 2.0, 2011-01), Section 5--
Measurements, IBR approved for appendix W to subpart B.
* * * * *
0
7. Section 430.23 is amended by revising paragraph (y) to read as
follows:
Sec. 430.23 Test procedures for the measurement of energy and water
consumption.
* * * * *
(y) Compact fluorescent lamps. (1) Measure initial lumen output,
input power, initial lamp efficacy, lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of lifetime of a compact fluorescent
lamp (as defined in 10 CFR 430.2), color rendering index (CRI),
correlated color temperature (CCT), power factor, start time, standby
mode energy consumption, and time to failure in accordance with
appendix W of this subpart. Express time to failure in hours.
(2) Conduct the rapid cycle stress test in accordance with section
3.3 of appendix W of this subpart.
* * * * *
0
8. Section 430.25 is revised to read as follows:
Sec. 430.25 Laboratory Accreditation Program.
The testing for general service fluorescent lamps, general service
incandescent lamps (with the exception of lifetime testing),
incandescent reflector lamps, compact fluorescent lamps, fluorescent
lamp ballasts, and integrated light-emitting diode lamps must be
conducted by test laboratories accredited by an Accreditation Body that
is a signatory member to the International Laboratory Accreditation
Cooperation (ILAC) Mutual Recognition Arrangement (MRA). A
manufacturer's or importer's own laboratory, if accredited, may conduct
the applicable testing.
0
9. Appendix W to subpart B of part 430 is revised to read as follows:
Appendix W to Subpart B of Part 430--Uniform Test Method for Measuring
the Energy Consumption of Compact Fluorescent Lamps
Note: Before February 27, 2017, any representations, including
certifications of compliance, made with respect to the energy use or
efficiency of medium base compact fluorescent lamps must be made in
accordance with the results of testing pursuant either to this
appendix, or to the applicable test requirements set forth in 10 CFR
parts 429 and 430 as they appeared in the 10 CFR parts 200 to 499
annual edition revised as of January 1, 2016.
On or after February 27, 2017, any representations, including
certifications of compliance (if required), made with respect to the
energy use or efficiency of CFLs must be made in accordance with the
results of testing pursuant to this appendix.
1. Scope:
1.1. Integrated compact fluorescent lamps.
1.1.1. This appendix specifies the test methods required to
measure the initial lamp efficacy, lumen maintenance at 1,000 hours,
lumen maintenance at 40 percent of lifetime, time to failure, power
factor, correlated color temperature (CCT), color rendering index
(CRI), and start time of an integrated compact fluorescent lamp.
1.1.2. This appendix describes how to conduct rapid cycle stress
testing for integrated compact fluorescent lamps.
1.1.3. This appendix specifies test methods required to measure
standby mode energy consumption applicable to integrated CFLs
capable of operation in standby mode (as defined in Sec. 430.2),
such as those that can be controlled wirelessly.
1.2. Non-integrated compact fluorescent lamps.
1.2.1. This appendix specifies the test methods required to
measure the initial lamp efficacy, lumen maintenance at 40 percent
of lifetime, time to failure, CCT, and CRI for non-integrated
compact fluorescent lamps.
2. Definitions:
2.1. Ballasted adapter means a ballast that is not permanently
attached to a compact fluorescent lamp, has no consumer-replaceable
components, and serves as an adapter by incorporating both a lamp
socket and a lamp base.
2.2. Hybrid compact fluorescent lamp means a compact fluorescent
lamp that incorporates one or more supplemental light sources of
different technology.
2.3. Initial lamp efficacy means the lamp efficacy (as defined
in Sec. 430.2) at the end of the seasoning period, as calculated
pursuant to section 3.2.2.9 of this appendix.
2.4. Integrated compact fluorescent lamp means an integrally
ballasted compact fluorescent lamp that contains all components
necessary for the starting and stable operation of the lamp,
contains an ANSI standard base, does not include any replaceable or
interchangeable parts, and is capable of being connected directly to
a branch circuit through a corresponding ANSI standard lamp-holder
(socket).
2.5. Labeled wattage means the highest wattage marked on the
lamp and/or lamp packaging.
2.6. Lumen maintenance means the lumen output measured at a
given time in the life of the lamp and expressed as a percentage of
the measured initial lumen output.
2.7. Measured initial input power means the input power to the
lamp, measured at the end of the lamp seasoning period, and
expressed in watts (W).
2.8. Measured initial lumen output means the lumen output of the
lamp measured at the end of the lamp seasoning period, expressed in
lumens (lm).
2.9. Non-integrated compact fluorescent lamp means a compact
fluorescent lamp that is not an integrated compact fluorescent lamp.
2.10. Percent variability means the result of dividing the
difference between the maximum and minimum values by the average
value for a contiguous set of separate time-averaged light output
values spanning the specified time period. For a waveform of
measured light output values, the time-averaged light output is
computed over one full cycle of sinusoidal input voltage, as a
moving average where the measurement interval is incremented by one
sample for each successive measurement value.
2.11. Power factor means the measured input power (watts)
divided by the product of the measured RMS input voltage (volts) and
the measured RMS input current (amps).
2.12. Rated input voltage means the voltage(s) marked on the
lamp as the intended operating voltage or, if not marked on the
lamp, 120 V.
2.13. Start plateau means the first 100 millisecond period of
operation during which the percent variability does not exceed 5
percent.
2.14. Start time means the time, measured in milliseconds,
between the application of power to the compact fluorescent lamp and
the beginning of the start plateau.
2.15. Time to failure means the time elapsed between first use
and the point at which the compact fluorescent lamp (for a hybrid
CFL, the primary light source) ceases to produce measureable lumen
output.
3. Active Mode Test Procedures
3.1. General Instructions.
3.1.1. In cases where there is a conflict, the language of the
test procedure in this appendix takes precedence over any materials
incorporated by reference.
3.1.2. Maintain lamp operating orientation throughout seasoning
and testing, including storage and handling between tests.
3.1.3. Season CFLs prior to photometric and electrical testing
in accordance with sections 4, 5, 6.1, and 6.2.2.1 of IES LM-54-12
(incorporated by reference, see Sec. 430.3). Season the CFL for a
minimum of 100 hours in accordance with section 6.2.2.1 of IES LM-
54-12. During the 100 hour seasoning period, cycle the CFL (operate
the lamps for 180 minutes, 20 minutes off) as specified in section
6.4 of IES LM-65-14 (incorporated by reference; see Sec. 430.3).
[[Page 59419]]
3.1.3.1. Unit operating time during seasoning may be counted
toward time to failure, lumen maintenance at 40 percent of lifetime
of a compact fluorescent lamp (as defined in Sec. 430.2), and lumen
maintenance at 1,000 hours if the required operating cycle and test
conditions for time to failure testing per section 3.3.1 of this
appendix are satisfied.
3.1.3.2. If a lamp breaks, becomes defective, fails to
stabilize, exhibits abnormal behavior (such as swirling), or stops
producing light prior to the end of the seasoning period, the lamp
must be replaced with a new unit. If a lamp exhibits one of the
conditions listed in the previous sentence after the seasoning
period, the lamp's measurements must be included in the sample.
Record number of lamps replaced, if any.
3.1.4. Conduct all testing with the lamp operating at labeled
wattage. This requirement applies to all CFLs, including those that
are dimmable or multi-level.
3.1.5. Operate the CFL at the rated input voltage throughout
testing. For a CFL with multiple rated input voltages including 120
volts, operate the CFL at 120 volts. If a CFL with multiple rated
input voltages is not rated for 120 volts, operate the CFL at the
highest rated input voltage.
3.1.6. Test CFLs packaged with ballasted adapters or designed
exclusively for use with ballasted adapters as non-integrated CFLs,
with no ballasted adapter in the circuit.
3.1.7. Conduct all testing of hybrid CFLs with all supplemental
light sources in the lamp turned off, if possible. Before taking
measurements, verify that the lamp has stabilized in the operating
mode that corresponds to its primary light source.
3.2. Test Procedures for Determining Initial Lamp Efficacy,
Lumen Maintenance, CCT, CRI, and Power Factor.
Determine initial lamp efficacy, lumen maintenance at 40 percent
of lifetime of a compact fluorescent lamp (as defined in in Sec.
430.2), CCT, and CRI for integrated and non-integrated CFLs.
Determine lumen maintenance at 1,000 hours and power factor for
integrated CFLs only.
3.2.1. Test Conditions and Setup
3.2.1.1. Test half of the units in the sample in the base up
position, and half of the units in the base down position; if the
position is restricted by the manufacturer, test the units in the
manufacturer-specified position.
3.2.1.2. Establish ambient conditions, power supply, auxiliary
equipment, circuit setup, lamp connections, and instrumentation in
accordance with the specifications in sections (and corresponding
subsections) 4.0, 5.0 and 6.0 of IES LM-66-14 (incorporated by
reference; see Sec. 430.3), except maintain ambient temperature at
25 1 [deg]C (77 1.8[emsp14][deg]F).
3.2.1.3. Non-integrated CFLs must adhere to the reference
ballast requirements in section 5.2 of IES LM-66 (incorporated by
reference; see Sec. 430.3).
3.2.1.3.1. Test non-integrated lamps rated for operation on and
having reference ballast characteristics for either low frequency or
high frequency circuits (e.g., many preheat start lamps) at low
frequency.
3.2.1.3.2. For low frequency operation, test non-integrated
lamps rated for operation on either preheat start (starter) or rapid
start (no starter) circuits on preheat.
3.2.1.3.3. Operate non-integrated CFLs not listed in ANSI
C78.901-2014 (incorporated by reference; see Sec. 430.3) using the
following reference ballast settings:
3.2.1.3.3.1. Operate 25-28 W, T5 twin 2G11-based lamps that are
lower wattage replacements of 40 W, T5 twin 2G11-based lamps using
the following reference ballast settings: 60 Hz, 400 volts, 0.270
amps, and 1240 ohms.
3.2.1.3.3.2. Operate 14-15 W, T4 quad G24q-2-based lamps that
are lower wattage replacements of 18 W, T4 quad G24q-2-based lamps
using the following reference ballast settings: 60 Hz, 220 volts,
0.220 amps, and 815 ohms.
3.2.1.3.3.3. Operate 21 W, T4 quad G24q-3-based lamps that are
lower wattage replacements of 26 W, T4 quad G24q-3-based lamps using
the following reference ballast settings: 60 Hz, 220 volts, 0.315
amps, and 546 ohms.
3.2.1.3.3.4. Operate 21 W, T4 quad G24d-3-based lamps that are
lower wattage replacements of 26 W, T4 quad G24d-3-based lamps using
the following reference ballast settings: 60 Hz, 220 volts, 0.315
amps, and 546 ohms.
3.2.1.3.3.5. Operate 21 W, T4 multi (6) GX24q-3-based lamps that
are lower wattage replacements of 26 W, T4 multi (6) GX24q-3-based
lamps using the following reference ballast settings: 60 Hz, 220
volts, 0.315 amps, and 546 ohms.
3.2.1.3.3.6. Operate 27-28 W, T4 multi (6) GX24q-3-based lamps
that are lower wattage replacements of 32 W, T4 multi (6) GX24q-3-
based lamps using the following reference ballast settings: 20-26
kHz, 200 volts, 0.320 amps, and 315 ohms.
3.2.1.3.3.7. Operate 33-38 W, T4 multi (6) GX24q-4-based lamps
that are lower wattage replacements of 42 W, T4 multi (6) GX24q-4-
based lamps using the following reference ballast settings: 20-26
kHz, 270 volts, 0.320 amps, and 420 ohms.
3.2.1.3.3.8. Operate 10 W, T4 square GR10q-4-based lamps using
the following reference ballast settings: 60 Hz, 236 volts, 0.165
amps, and 1,200 ohms.
3.2.1.3.3.9. Operate 16 W, T4 square GR10q-4-based lamps using
the following reference ballast settings: 60 Hz, 220 volts, 0.195
amps, and 878 ohms.
3.2.1.3.3.10. Operate 21 W, T4 square GR10q-4-based lamps using
the following reference ballast settings: 60 Hz, 220 volts, 0.260
amps, and 684 ohms.
3.2.1.3.3.11. Operate 28 W, T6 square GR10q-4-based lamps using
the following reference ballast settings: 60 Hz, 236 volts, 0.320
amps, and 578 ohms.
3.2.1.3.3.12. Operate 38 W, T6 square GR10q-4-based lamps using
the following reference ballast settings: 60 Hz, 236 volts, 0.430
amps, and 439 ohms.
3.2.1.3.3.13. Operate 55 W, T6 square GRY10q-3-based lamps using
the following reference ballast settings: 60 Hz, 236 volts, 0.430
amps, and 439 ohms.
3.2.1.3.3.14. For all other lamp designs not listed in ANSI
C78.901-2014 (incorporated by reference; see Sec. 430.3) or section
3.2.1.3.3 of this appendix:
3.2.1.3.3.14.1. If the lamp is a lower wattage replacement of a
lamp with specifications in ANSI C78.901-2014, use the reference
ballast characteristics of the corresponding higher wattage lamp
replacement in ANSI C78.901-2014.
3.2.1.3.3.14.2. For all other lamps, use the reference ballast
characteristics in ANSI C78.901-2014 for a lamp with the most
similar shape, diameter, and base specifications, and next closest
wattage.
3.2.2. Test Methods, Measurements, and Calculations
3.2.2.1. Season CFLs. (See section 3.1.3 of this appendix.)
3.2.2.2. Stabilize CFLs as specified in section 6.2.1 of IES LM-
66 (incorporated by reference; see Sec. 430.3).
3.2.2.3. Measure the input power (in watts), the input voltage
(in volts), and the input current (in amps) as specified in section
5.0 of IES LM-66 (incorporated by reference; see Sec. 430.3).
3.2.2.4. Measure initial lumen output as specified in section
6.3.1 of IES LM-66 (incorporated by reference; see Sec. 430.3) and
in accordance with IESNA LM-78-07 (incorporated by reference; see
Sec. 430.3).
3.2.2.5. Measure lumen output at 1,000 hours as specified in
section 6.3.1 of IES LM-66 (incorporated by reference; see Sec.
430.3) and in accordance with IESNA LM-78-07 (incorporated by
reference; see Sec. 430.3).
3.2.2.6. Measure lumen output at 40 percent of lifetime of a
compact fluorescent lamp (as defined in 10 CFR 430.2) as specified
in section 6.3.1 of IES LM-66 (incorporated by reference; see Sec.
430.3) and in accordance with IESNA LM-78-07 (incorporated by
reference; see Sec. 430.3).
3.2.2.7. Determine CCT as specified in section 6.4 of IES LM-66
(incorporated by reference; see Sec. 430.3) and in accordance with
CIE 15 (incorporated by reference; see Sec. 430.3).
3.2.2.8. Determine CRI as specified in section 6.4 of IES LM-66
(incorporated by reference; see Sec. 430.3) and in accordance with
CIE 13.3 (incorporated by reference; see Sec. 430.3).
3.2.2.9. Determine initial lamp efficacy by dividing measured
initial lumen output by the measured initial input power.
3.2.2.10. Determine lumen maintenance at 1,000 hours by dividing
measured lumen output at 1,000 hours by the measured initial lumen
output.
3.2.2.11. Determine lumen maintenance at 40 percent of lifetime
of a compact fluorescent lamp (as defined in Sec. 430.2) by
dividing measured lumen output at 40 percent of lifetime of a
compact fluorescent lamp (as defined in Sec. 430.2) by the measured
initial lumen output.
3.2.2.12. Determine power factor by dividing the measured input
power (watts) by the product of measured RMS input voltage (volts)
and measured RMS input current (amps).
3.3. Test Method for Time to Failure and Rapid Cycle Stress
Test.
Determine time to failure for integrated and non-integrated
CFLs. Conduct rapid cycle stress testing for integrated CFLs only.
Disregard section 3.0 of IES LM-65-14.
3.3.1. Test Conditions and Setup
[[Page 59420]]
3.3.1.1. Test half of the units in the base up position and half
of the units in the base down position; if the position is
restricted by the manufacturer, test in the manufacturer-specified
position.
3.3.1.2. Establish the ambient and physical conditions and
electrical conditions in accordance with the specifications in
sections 4.0 and 5.0 of IES LM-65-14 (incorporated by reference; see
Sec. 430.3). Do not, however, test lamps in fixtures or luminaires.
3.3.1.3. Non-integrated CFLs must adhere to ballast requirements
as specified in section 3.2.1.3 of this appendix.
3.3.2. Test Methods and Measurements
3.3.2.1. Season CFLs. (See section 3.1.3 of this appendix.)
3.3.2.2. Measure time to failure of CFLs as specified in section
6.0 of IES LM-65-14 (incorporated by reference; see Sec. 430.3).
3.3.2.3. Conduct rapid cycle stress testing of integrated CFLs
as specified in section 6.0 of IES LM-65-14 (incorporated by
reference; see Sec. 430.3), except cycle the lamp continuously with
each cycle consisting of one 5-minute ON period followed by one 5-
minute OFF period.
3.4. Test Method for Start Time.
Determine start time for integrated CFLs only.
3.4.1. Test Conditions and Setup
3.4.1.1. Test all units in the base up position; if the position
is restricted by the manufacturer, test units in the manufacturer-
specified position.
3.4.1.2. Establish the ambient conditions, power supply,
auxiliary equipment, circuit setup, lamp connections, and
instrumentation in accordance with the specifications in sections
4.0 and 5.0 of IES LM-66 (incorporated by reference; see Sec.
430.3), except maintain ambient temperature at 25 1
[deg]C (77 1.8[emsp14][deg]F).
3.4.2. Test Methods and Measurement
3.4.2.1. Season CFLs. (See section 3.1.3 of this appendix.)
3.4.2.2. After seasoning, store units at 25 5
[deg]C ambient temperature for a minimum of 16 hours prior to the
test, after which the ambient temperature must be 25 1
[deg]C for a minimum of 2 hours immediately prior to the test. Any
units that have been off for more than 24 hours must be operated for
a minimum of 3.0 hours and then be turned off for 16 to 24 hours
prior to testing.
3.4.2.3. Connect multichannel oscilloscope with data storage
capability to record input voltage to CFL and light output. Set
oscilloscope to trigger at 10 V lamp input voltage. Set oscilloscope
vertical scale such that vertical resolution is 1 percent of
measured initial light output or finer. Set oscilloscope to sample
the light output waveform at a minimum rate of 2 kHz.
3.4.2.4. Operate the CFL at the rated voltage and frequency.
3.4.2.5. Upon the commencement of start time testing, record
sampled light output until start plateau has been determined.
3.4.2.6. Calculate the time-averaged light output value at least
once every millisecond where the time-averaged light output is
computed over one full cycle of sinusoidal input voltage, as a
moving average where the measurement interval is incremented by one
sample for each successive measurement value.
3.4.2.7. Determine start time.
4. Standby Mode Test Procedure
Measure standby mode energy consumption for only integrated CFLs
that are capable of operating in standby mode. The standby mode test
method in this section may be completed before or after the active
test method for determining lumen output, input power, CCT, CRI, and
power factor in section 3 of this appendix. The standby mode test
method in this section must be completed before the active mode test
method for determining time to failure in section 3.3 of this
appendix. The standby mode test method must be completed in
accordance with applicable provisions in section 3.1.
4.1. Test Conditions and Setup
4.1.1. Position half of the units in the sample in the base up
position and half of the units in the base down position; if the
position is restricted by the manufacturer, test units in the
manufacturer-specified position.
4.1.2. Establish the ambient conditions (including air flow),
power supply, electrical settings, and instrumentation in accordance
with the specifications in sections 4.0, 5.0 and 6.0 of IES LM-66
(incorporated by reference; see Sec. 430.3), except maintain
ambient temperature at 25 1 [deg]C (77
1.8[emsp14][deg]F).
4.2. Test Methods, Measurements, and Calculations
4.2.1. Season CFLs. (See section 3.1.3 of this appendix.)
4.2.2. Connect the integrated CFL to the manufacturer-specified
wireless control network (if applicable) and configure the
integrated CFL in standby mode by sending a signal to the integrated
CFL instructing it to have zero light output. The integrated CFL
must remain connected to the network throughout the entire duration
of the test.
4.2.3. Stabilize the integrated CFL prior to measurement as
specified in section 5 of IEC 62301-W (incorporated by reference;
see Sec. 430.3).
4.2.4. Measure the standby mode energy consumption in watts as
specified in section 5 of IEC 62301-W (incorporated by reference;
see Sec. 430.3).
0
10. Section 430.32 is amended by revising paragraph (u) to read as
follows:
Sec. 430.32 Energy and water conservation standards and their
compliance dates.
* * * * *
(u) Compact fluorescent lamps. (1) Medium Base Compact Fluorescent
Lamps. A bare or covered (no reflector) medium base compact fluorescent
lamp manufactured on or after January 1, 2006, must meet the following
requirements:
------------------------------------------------------------------------
Factor Requirements
------------------------------------------------------------------------
Labeled Wattage (Watts) & Configuration Measured initial lamp efficacy
\*\. (lumens per watt) must be at
least:
Bare Lamp:
Labeled Wattage < 15............... 45.0.
Labeled Wattage >= 15.............. 60.0.
Covered Lamp (no reflector):
Labeled Wattage < 15............... 40.0.
15 <= Labeled Wattage < 19......... 48.0.
19 <= Labeled Wattage < 25......... 50.0.
Labeled Wattage >= 25.............. 55.0.
Lumen Maintenance at 1,000 Hours....... >=90.0%.
Lumen Maintenance at 40 Percent of >=80.0%.
Lifetime **.
Rapid Cycle Stress Test................ Each lamp must be cycled once
for every 2 hours of
lifetime.** At least 5 lamps
must meet or exceed the
minimum number of cycles.
Lifetime **............................ >=6,000 hours.
------------------------------------------------------------------------
* Use labeled wattage to determine the appropriate efficacy requirements
in this table; do not use measured wattage for this purpose.
** Lifetime refers to lifetime of a compact fluorescent lamp as defined
in 10 CFR 430.2.
(2) [Reserved].
* * * * *
[FR Doc. 2016-19967 Filed 8-26-16; 8:45 am]
BILLING CODE 6450-01-P