Energy Conservation Program: Test Procedures for Central Air Conditioners and Heat Pumps; Correction, 55111-55115 [2016-19227]
Download as PDF
55111
Rules and Regulations
Federal Register
Vol. 81, No. 160
Thursday, August 18, 2016
This section of the FEDERAL REGISTER
contains regulatory documents having general
applicability and legal effect, most of which
are keyed to and codified in the Code of
Federal Regulations, which is published under
50 titles pursuant to 44 U.S.C. 1510.
The Code of Federal Regulations is sold by
the Superintendent of Documents. Prices of
new books are listed in the first FEDERAL
REGISTER issue of each week.
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[Docket No. EERE–2009–BT–TP–0004]
RIN 1904–AB94
Energy Conservation Program: Test
Procedures for Central Air
Conditioners and Heat Pumps;
Correction
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule; technical correction.
AGENCY:
On June 8, 2016, the U.S.
Department of Energy (DOE) published
a final rule in the Federal Register that
amended the test procedures for central
air conditioners and heat pumps. This
final rule corrects multiple editorial
errors in that final rule.
DATES: Effective Date: August 18, 2016.
FOR FURTHER INFORMATION CONTACT: Ms.
Ashley Armstrong, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Office, EE–5B, 1000
Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–6590. Email:
Ashley.Armstrong@ee.doe.gov.
Ms. Johanna Jochum, U.S. Department
of Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue
SW., Washington, DC 20585–0121.
Telephone: (202) 287–6307. Email:
Johanna.Jochum@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
SUMMARY:
rmajette on DSK2TPTVN1PROD with RULES
I. Background
On June 8, 2016, DOE’s Office of
Energy Efficiency and Renewable
Energy published a test procedure final
rule in the Federal Register titled, ‘‘Test
Procedures for Central Air Conditioners
and Heat Pumps’’ (‘‘June 2016 final
rule’’). 81 FR 36992. Since the
publication of that final rule, it has
VerDate Sep<11>2014
15:00 Aug 17, 2016
Jkt 238001
come to DOE’s attention that, due to a
technical oversight, certain portions of
the regulatory text adopted in the June
2016 final rule for 10 CFR part 429 and
appendix M to subpart B of 10 CFR part
430 (‘‘appendix M’’) contained editorial
errors.
As part of that final rule, DOE
amended 10 CFR 429.16, which
addresses certification of central air
conditioners and heat pumps, and 10
CFR 429.70, which addresses alternate
efficiency determination methods. This
correction addresses editorial errors in
§ 429.16(a)(1), (d)(1), (d)(2), and (e)(4).
Specifically, at § 429.16(a)(1), DOE
included a cross reference to paragraph
(c)(2) that should have referred to
paragraph (b)(2)(i). In § 429.16(d)(1) and
(2), DOE mistakenly transposed the
words ‘‘less’’ and ‘‘greater.’’ At
§ 429.16(e)(4), DOE erroneously referred
to cubic feet per minute (cfm) instead of
cubic feet per minute of standard air
(scfm). At § 429.16(e)(4)(viii), DOE
failed to remove regulatory text
associated with changes to the test
procedure for variable speed heat
pumps not adopted in the June 2016
final rule that had been proposed on
November 9, 2015 in a supplementary
notice of proposed rulemaking
(‘‘November 2015 SNOPR’’). 80 FR
69278. In order to remedy these errors,
DOE is issuing this final rule correction
to revise the text in these sections.
In addition, the June 2016 final rule
revised appendix M to subpart B of 10
CFR part 430 (‘‘appendix M’’), which
specifies the ‘‘Uniform Test Method for
the Measurement the Energy
Consumption of Central Air
Conditioners and Heat Pumps.’’ This
correction also addresses several
editorial errors in appendix M.
In section 3.11.1 of appendix M, ‘‘If
using the outdoor air enthalpy method
as the secondary test method,’’ DOE
erroneously numbered two subsections
with the number ‘‘3.11.1.1.’’ The second
of these two is renumbered to
‘‘3.11.1.2.’’
In section 4.1 of appendix M,
‘‘Seasonal Energy Efficiency Ratio
(SEER) Calculations,’’ DOE erroneously
numbered subsection 4.1.3 as ‘‘4.1.2.3,’’
which propagated errors in numbering
from that point through the end of
section 4.1 and created erroneous crossreferences to these sections. Section
4.1.2.3 is renumbered as section ‘‘4.1.3,’’
and the following section numbers
PO 00000
Frm 00001
Fmt 4700
Sfmt 4700
through the end of section 4.1 are
renumbered accordingly. Additionally,
cross-references to the renumbered
sections are revised.
Sections 2.11 and 3.19 of appendix M
contain errors in the tolerance allowed
between temperature measurements.
The preamble to the June 2016 final rule
states that the maximum allowable
temperature difference is 2.0 °F and that
it applies to the average measurements
for the test period. 81 FR 36991, 37028
(June 8, 2016). In section 2.11, DOE
erroneously referred to ‘‘maximum
difference between readings’’ rather
than adding the clarification discussed
in the preamble that ‘‘readings’’ referred
to the average temperatures measured
during the test period. In section 3.1.9,
DOE similarly failed to include the
clarifying information on the tolerance
and erroneously provided a tolerance of
1.5 °F rather than 2.0 °F. DOE is
correcting section 2.11 accordingly and
correcting 3.1.9 to refer directly to
section 2.11 rather than correcting the
provided tolerance.
Tables 8, 9, 15, 16, and 17 of
appendix M contained various errors in
testing tolerances for external resistance
to airflow, airflow nozzle pressure
difference, and electric voltage. In the
preamble of the June 2016 Final Rule,
DOE explained its intention to maintain
the external resistance to airflow
tolerance at 0.05 inches of water, to
maintain the airflow nozzle pressure
difference tolerance at 2.0%, and to
maintain the electric voltage tolerance at
2.0%. 81 FR 36991, 37036 (June 8,
2016). However, this was not reflected
in tables 8, 9, 15, 16 and 17 of appendix
M, and the tables are revised to reflect
these corrections.
In section 3.13.1.d of appendix M, P2x
was erroneously printed instead of Px in
two instances. This section provides
instructions for measurement of the
indoor unit low voltage power Px, which
is later subtracted from the
measurement of heating season total off
mode power (P2x) for coil-only split
systems and for blower coil split
systems for which a furnace or a
modular blower is the designated air
mover. Instances of P2x in section
3.13.1.d of appendix M are revised to Px.
Finally, many of the instructions in
the final rule that indicate that a default
cyclic degradation coefficient is to be
used if the tests to determine this value
are not conducted, but erroneously did
E:\FR\FM\18AUR1.SGM
18AUR1
55112
Federal Register / Vol. 81, No. 160 / Thursday, August 18, 2016 / Rules and Regulations
not specify that the default value is to
be used if the value determined using
the test exceeded the default value. 81
FR 36991, 37033 (June 8, 2016). DOE
intended that the default value is to be
used if the value determined using the
test exceeds the default value for the
cyclic degradation coefficient, and is
correcting this omission in this final
rule correction.
II. Need for Correction
As published, the adopted test
procedure text may potentially result in
confusion regarding how to correctly
conduct DOE’s central air conditioners
and heat pumps test procedure.
Because this final rule would simply
correct errors in the regulatory text
without making substantive changes to
the test procedures, the changes
addressed in this document are
technical in nature. Accordingly, DOE
finds that there is good cause under 5
U.S.C. 553(b)(B) to not issue a separate
notice to solicit public comment on the
changes contained in this document.
Issuing a separate notice to solicit
public comment would be
impracticable, unnecessary, and
contrary to the public interest.
III. Procedural Requirements
DOE has concluded that the
determinations made pursuant to the
various procedural requirements
applicable to the June 8, 2016 test
procedure final rule remain unchanged
for this final rule technical correction.
These determinations are set forth in the
June 8, 2016 final rule. 81 FR 36992.
List of Subjects
10 CFR Part 429
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Reporting and recordkeeping
requirements.
10 CFR Part 430
rmajette on DSK2TPTVN1PROD with RULES
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Energy conservation test procedures,
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Small
businesses.
Issued in Washington, DC, on August 5,
2016.
Kathleen Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
For the reasons stated in the
preamble, DOE amends parts 429 and
VerDate Sep<11>2014
15:00 Aug 17, 2016
Jkt 238001
430 of chapter II of title 10, Code of
Federal Regulations to read as follows:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
§ 429.16
[Amended]
2. Section 429.16 is amended:
a. In paragraph (a)(1), in the last row
of the table, by removing ‘‘(c)(2)’’ and
adding in its place ‘‘(b)(2)(i)’’;
■ b. In paragraph (d)(1) by removing
‘‘less’’ and adding in its place ‘‘greater’’;
■ c. In paragraph (d)(2) by removing
‘‘greater’’ and adding in its place ‘‘less’’;
■ d. In paragraph (e)(4) by:
■ i. Adding ‘‘of standard air’’ after ‘‘(in
cubic feet per minute’’;
■ ii. Removing the two instances of
‘‘(cfm)’’ and adding in its place
‘‘(scfm)’’; and
■ iii. Removing paragraph (viii).
■
■
PART 430—ENERGY CONSERVATION
PROGRAM FOR CONSUMER
PRODUCTS
3. The authority citation for part 430
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6309; 28 U.S.C.
2461 note.
4. Appendix M to subpart B of part
430 is amended by:
■ a. In section 2.11.b(2), first paragraph,
last sentence, removing ‘‘readings’’ and
adding in its place ‘‘average
temperatures measured during the test
period’’;
■ b. Revising section 3.1.9;
■ c. Revising section 3.2.1, introductory
text;
■ d. In section 3.2.3.d., adding a
sentence after the first sentence;
■ e. In section 3.3, paragraph d., revising
Table 8;
■ f. In section 3.5, paragraph h., revising
Table 9 and its footnotes;
■ g. In section 3.5.3, adding a sentence
after the second sentence;
■ h. Revising section 3.6.3.b.,
introductory text;
■ i. In section 3.7, paragraph a., revising
Table 15;
■ j. In section 3.8.a., removing the sixth
sentence;
■ k. In section 3.8.1, adding a sentence
after the third sentence and revising
Table 16;
■ l. In section 3.9, paragraph f., revising
Table 17;
■
PO 00000
Frm 00002
Fmt 4700
Sfmt 4700
m. In section 3.11, redesignating the
second section 3.11.1.1 (‘‘Official Test’’)
as section 3.11.1.2;
■ n. In section 3.13.1.d, removing the
two instances of ‘‘P2x’’ and adding in
their places ‘‘Px’’;
■ o. In section 4.1.1.b, adding a second
sentence;
■ p. In section 4.1.2.1.c, adding a
second sentence;
■ q. Redesignating sections 4.1.4.1 and
4.1.4.2 as sections 4.1.5.1 and 4.1.5.2,
respectively;
■ r. Redesignating section 4.1.4 as
section 4.1.5;
■ s. Redesignating sections 4.1.3.1,
4.1.3.2, and 4.1.3.3 as sections 4.1.4.1,
4.1.4.2, and 4.1.4.3, respectively;
■ t. Redesignating section 4.1.3 as
section 4.1.4;
■ u. Redesignating section 4.1.2.7 as
section 4.1.3.4;
■ v. Redesignating section 4.1.2.6 as
section 4.1.3.3;
■ w. Redesignating section 4.1.2.5 as
section 4.1.3.2;
■ x. Redesignating section 4.1.2.4 as
section 4.1.3.1;
■ y. Redesignating section 4.1.2.3 as
section 4.1.3;
■ z. In newly redesignated section
4.1.3.1, revising the equation and
related information immediately before
Table 18;
■ aa. In newly redesignated section
4.1.4.1, adding a sentence after the last
sentence of the section;
■ bb. In section 4.2.1, adding the
sentence ‘‘Evaluate the heating mode
˙
cyclic degradation factor CDh as
specified in section 3.8.1 of this
appendix.’’, after ‘‘Use Equation 4.2–2 to
determine BL(Tj). Obtain fractional bin
hours for the heating season, nj/N, from
Table 19.’’; and
■ cc. In section 4.2.3.1, adding the
sentence ‘‘Evaluate the heating mode
cyclic degradation factor CDh as
specified in section 3.8.1 of this
appendix.’’, after ‘‘d′(Tj) = the low
temperature cutoff factor,
dimensionless.’’;
The revisions and additions read as
follows.
■
Appendix M to Subpart B of Part 430—
Uniform Test Method for Measuring the
Energy Consumption of Central Air
Conditioners and Heat Pumps
*
*
*
*
*
3.1.9 Requirement for the Air Temperature
Distribution Entering the Outdoor Coil
Monitor the temperatures of the air
entering the outdoor coil using air sampling
devices and/or temperature sensor grids,
maintaining the required tolerances, if
applicable, as described in section 2.11 of
this appendix.
*
E:\FR\FM\18AUR1.SGM
*
*
18AUR1
*
*
Federal Register / Vol. 81, No. 160 / Thursday, August 18, 2016 / Rules and Regulations
3.2.1 Tests for a System Having a SingleSpeed Compressor and Fixed Cooling Air
Volume Rate
This set of tests is for single-speedcompressor units that do not have a cooling
minimum air volume rate or a cooling
intermediate air volume rate that is different
than the cooling full load air volume rate.
Conduct two steady-state wet coil tests, the
A and B Tests. Use the two optional dry-coil
tests, the steady-state C Test and the cyclic
D Test, to determine the cooling mode cyclic
degradation coefficient, CDc. If the two
55113
optional tests are conducted but yield a
tested CDc that exceeds the default CDc or if
the two optional tests are not conducted,
assign CDc the default value of 0.25 (for
outdoor units with no match) or 0.20 (for all
other systems). Table 4 specifies test
conditions for these four tests.
d. * * * If the two optional tests are
conducted but yield a tested CDc (k = 2) that
exceeds the default CDc (k = 2) or if the two
optional tests are not conducted, assign CDc
(k = 2) the default value. ***
*
3.3. * * *
*
*
*
*
*
3.2.3 Tests for a Unit Having a TwoCapacity Compressor (See Section 1.2 of
This Appendix, Definitions)
*
*
*
*
*
*
*
*
d. * * *
*
TABLE 8—TEST OPERATING AND TEST CONDITION TOLERANCES FOR SECTION 3.3 STEADY-STATE WET COIL COOLING
MODE TESTS AND SECTION 3.4 DRY COIL COOLING MODE TESTS
Test operating
tolerance 1
Indoor dry-bulb, °F:
Entering temperature ............................................................................................................................
Leaving temperature .............................................................................................................................
Indoor wet-bulb, °F:
Entering temperature ............................................................................................................................
Leaving temperature .............................................................................................................................
Outdoor dry-bulb, °F:
Entering temperature ............................................................................................................................
Leaving temperature .............................................................................................................................
Outdoor wet-bulb, °F:
Entering temperature ............................................................................................................................
Leaving temperature .............................................................................................................................
External resistance to airflow, inches of water ............................................................................................
Electrical voltage, % of rdg. .........................................................................................................................
Nozzle pressure drop, % of rdg. .................................................................................................................
Test condition
tolerance 1
2.0
2.0
0.5
1.0
2 0.3
2 1.0
2.0
0.5
3 2.0
4 0.3
1.0
3 1.0
5 0.02
0.05
2.0
2.0
1.5
1 See
section 1.2 of this appendix, Definitions.
applies during wet coil tests; does not apply during steady-state, dry coil cooling mode tests.
applies when using the outdoor air enthalpy method.
4 Only applies during wet coil cooling mode tests where the unit rejects condensate to the outdoor coil.
5 Only applies when testing non-ducted units.
2 Only
3 Only
*
*
*
*
3.5 * * *
h. * * *
*
TABLE 9—TEST OPERATING AND TEST CONDITION TOLERANCES FOR CYCLIC DRY COIL COOLING MODE TESTS
Test operating
tolerance 1
Indoor entering dry-bulb temperature 2, °F ..................................................................................................
Indoor entering wet-bulb temperature, °F ...................................................................................................
Outdoor entering dry-bulb temperature 2, °F ...............................................................................................
External resistance to airflow 2, inches of water .........................................................................................
Airflow nozzle pressure difference or velocity pressure 2, % of reading .....................................................
Electrical voltage 5, % of rdg. ......................................................................................................................
Test condition
tolerance 1
2.0
..............................
2.0
0.05
2.0
2.0
0.5
(3)
0.5
4 2.0
1.5
1 See
section 1.2 of this appendix, Definitions.
during the interval that air flows through the indoor (outdoor) coil except for the first 30 seconds after flow initiation. For units having a
variable-speed indoor blower that ramps, the tolerances listed for the external resistance to airflow apply from 30 seconds after achieving full
speed until ramp down begins.
3 Shall at no time exceed a wet-bulb temperature that results in condensate forming on the indoor coil.
4 The test condition shall be the average nozzle pressure difference or velocity pressure measured during the steady-state dry coil test.
5 Applies during the interval when at least one of the following—the compressor, the outdoor fan, or, if applicable, the indoor blower—are operating except for the first 30 seconds after compressor start-up.
2 Applies
rmajette on DSK2TPTVN1PROD with RULES
*
*
*
*
systems and outdoor units with no match,
and 0.20 for all other systems.* * *
*
3.5.3 Cooling-Mode Cyclic-Degradation
Coefficient Calculation
*
*
*
*
*
* * * If the two optional tests are
conducted but yield a tested CDc that exceeds
the default CDc or if the two optional tests are
not conducted, assign CDc the default value
of 0.25 for variable-speed compressor
VerDate Sep<11>2014
15:00 Aug 17, 2016
Jkt 238001
PO 00000
3.6.3 Tests for a Heat Pump Having a TwoCapacity Compressor (see Section 1.2 of This
Appendix, Definitions), Including TwoCapacity, Northern Heat Pumps (see Section
1.2 of This Appendix, Definitions)
*
*
*
*
*
b. Conduct the optional high temperature
cyclic test (H1C1) to determine the heating
mode cyclic-degradation coefficient, CDh. If
Frm 00003
Fmt 4700
Sfmt 4700
E:\FR\FM\18AUR1.SGM
18AUR1
55114
Federal Register / Vol. 81, No. 160 / Thursday, August 18, 2016 / Rules and Regulations
this optional test is conducted but yields a
tested CDh that exceeds the default CDh or if
the optional test is not conducted, assign CDh
the default value of 0.25. If a two-capacity
heat pump locks out low capacity operation
at lower outdoor temperatures, conduct the
high temperature cyclic test (H1C2) to
determine the high-capacity heating mode
cyclic-degradation coefficient, CDh (k=2). If
this optional test at high capacity is
conducted but yields a tested CDh (k = 2) that
exceeds the default CDh (k = 2) or if the
optional test is not conducted, assign CDh the
default value. The default CDh (k=2) is the
same value as determined or assigned for the
low-capacity cyclic-degradation coefficient,
CDh [or equivalently, CDh (k=1)]. Table 12
specifies test conditions for these nine tests.
*
*
3.7
*
*
*
* * *
a. * * *
TABLE 15—TEST OPERATING AND TEST CONDITION TOLERANCES FOR SECTION 3.7 AND SECTION 3.10 STEADY-STATE
HEATING MODE TESTS
Test condition
tolerance 1
Test operating
tolerance 1
Indoor dry-bulb, °F:
Entering temperature ............................................................................................................................
Leaving temperature .............................................................................................................................
Indoor wet-bulb, °F:
Entering temperature ............................................................................................................................
Leaving temperature .............................................................................................................................
Outdoor dry-bulb, °F:
Entering temperature ............................................................................................................................
Leaving temperature .............................................................................................................................
Outdoor wet-bulb, °F:
Entering temperature ............................................................................................................................
Leaving temperature .............................................................................................................................
External resistance to airflow, inches of water ............................................................................................
Electrical voltage, % of rdg ..........................................................................................................................
Nozzle pressure drop, % of rdg ..................................................................................................................
2.0
2.0
0.5
1.0
1.0
2.0
0.5
2 2.0
1.0
0.3
2 1.0
3 0.02
0.05
2.0
2.0
1.5
1 See
section 1.2 of this appendix, Definitions.
applies when the Outdoor Air Enthalpy Method is used.
3 Only applies when testing non-ducted units.
2 Only
*
*
*
*
3.8.1 * * *
* * * If the optional cyclic test is
conducted but yields a tested CDh that
exceeds the default CDh or if the optional test
*
is not conducted, assign CDh the default
value of 0.25.* * *
*
*
*
*
*
TABLE 16—TEST OPERATING AND TEST CONDITION TOLERANCES FOR CYCLIC HEATING MODE TESTS
Test operating
tolerance 1
Indoor entering dry-bulb temperature,2 °F ..................................................................................................
Indoor entering wet-bulb temperature,2 °F ..................................................................................................
Outdoor entering dry-bulb temperature,2 °F ................................................................................................
Outdoor entering wet-bulb temperature,2 °F ...............................................................................................
External resistance to air-flow,2 inches of water .........................................................................................
Airflow nozzle pressure difference or velocity pressure,2 % of reading ......................................................
Electrical voltage,4 % of rdg .........................................................................................................................
2.0
1.0
2.0
2.0
0.05
2.0
2.0
Test condition
tolerance 1
0.5
0.5
1.0
3 2.0
1.5
1 See
section 1.2 of this appendix, Definitions.
during the interval that air flows through the indoor (outdoor) coil except for the first 30 seconds after flow initiation. For units having a
variable-speed indoor blower that ramps, the tolerances listed for the external resistance to airflow shall apply from 30 seconds after achieving
full speed until ramp down begins.
3 The test condition shall be the average nozzle pressure difference or velocity pressure measured during the steady-state test conducted at
the same test conditions.
4 Applies during the interval that at least one of the following—the compressor, the outdoor fan, or, if applicable, the indoor blower—are operating, except for the first 30 seconds after compressor start-up.
2 Applies
*
*
*
*
3.9 * * *
f. * * *
*
rmajette on DSK2TPTVN1PROD with RULES
TABLE 17—TEST OPERATING AND TEST CONDITION TOLERANCES FOR FROST ACCUMULATION HEATING MODE TESTS
Test operating tolerance 1
Sub-interval H 2
Indoor entering dry-bulb temperature, °F ..................................................................
Indoor entering wet-bulb temperature, °F .................................................................
Outdoor entering dry-bulb temperature, °F ...............................................................
VerDate Sep<11>2014
15:00 Aug 17, 2016
Jkt 238001
PO 00000
Frm 00004
Fmt 4700
Sfmt 4700
Sub-interval D 3
Sub-interval H 2
4 4.0
18AUR1
0.5
10.0
2.0
1.0
2.0
E:\FR\FM\18AUR1.SGM
Test condition
tolerance 1
1.0
Federal Register / Vol. 81, No. 160 / Thursday, August 18, 2016 / Rules and Regulations
55115
TABLE 17—TEST OPERATING AND TEST CONDITION TOLERANCES FOR FROST ACCUMULATION HEATING MODE TESTS—
Continued
Test operating tolerance 1
Sub-interval H 2
Outdoor entering wet-bulb temperature, °F ...............................................................
External resistance to airflow, inches of water ..........................................................
Electrical voltage, % of rdg ........................................................................................
1.5
0.05
2.0
Test condition
tolerance 1
Sub-interval D 3
Sub-interval H 2
..............................
..............................
..............................
0.5
5 0.02
1.5
1 See
section 1.2 of this appendix, Definitions.
2 Applies when the heat pump is in the heating mode, except for the first 10 minutes after termination of a defrost cycle.
3 Applies during a defrost cycle and during the first 10 minutes after the termination of a defrost cycle when the heat pump is operating in the
heating mode.
4 For heat pumps that turn off the indoor blower during the defrost cycle, the noted tolerance only applies during the 10 minute interval that follows defrost termination.
5 Only applies when testing non-ducted heat pumps.
*
*
4.1.1
*
*
*
* * *
b. * * * Evaluate the cooling mode cyclic
degradation factor CDc as specified in section
3.5.3 of this appendix.
*
*
4.1.2.1
*
*
*
* * *
c. * * * Evaluate the cooling mode cyclic
degradation factor CDc as specified in section
3.5.3 of this appendix.
*
*
*
*
*
4.1.3.1 * * *
nj/N = fractional bin hours for the cooling
season; the ratio of the number of hours
during the cooling season when the
outdoor temperature fell within the
range represented by bin temperature Tj
to the total number of hours in the
cooling season, dimensionless.
Obtain the fractional bin hours for the
cooling season, nj/N, from Table 18. Use
Equations 4.1.3–1 and 4.1.3–2, respectively,
˙
˙
to evaluate Qck=1(Tj) and Eck=1(Tj). Evaluate
the cooling mode cyclic degradation factor
CDc as specified in section 3.5.3 of this
appendix.
*
Sections
*
*
*
*
4.1.4.1 * * *
* * * Evaluate the cooling mode cyclic
degradation factor CDc as specified in section
3.5.3 of this appendix.
*
*
*
*
*
Appendix M to Subpart B of Part 430—
[Amended]
5. In the table below, for each section
of appendix M to subpart B of part 430
indicated in the left column, remove the
language indicated in the middle
column from wherever it appears in that
section, and add the language indicated
in the right column.
■
Remove
Add
3.2.2.1, 3.2.3.a ...
A default value of CD may be used in lieu of conducting the
cyclic test. The default value of CDc is 0.20.
3.2.4.a ................
A default value for CDc may be used in lieu of conducting the
cyclic test. The default value of CDc is 0.25.
3.6.1 ...................
A default value for CDh may be used in lieu of conducting the
cyclic test. The default value of CDh is 0.25.
3.6.2, 3.6.4.a ......
A default value for CDh may be used in lieu of conducting the
cyclic. The default value of CDh is 0.25.
If the two optional tests are conducted but yield a tested CDc
that exceeds the default CDc or if the two optional tests are
not conducted, assign CDc the default value of 0.20.
If the two optional tests are conducted but yield a tested CDc
that exceeds the default CDc or if the two optional tests are
not conducted, assign CDc the default value of 0.25.
If this optional test is conducted but yields a tested CDh that
exceeds the default CDh or if the optional test is not conducted, assign CDh the default value of 0.25.
If this optional test is conducted but yields a tested CDh that
exceeds the default CDh or if the optional test is not conducted, assign CDh the default value of 0.25.
c
Appendix M to Subpart B of Part 430—
[Amended]
6. For each newly redesignated
section of appendix M to subpart B of
part 430 in the first column, remove the
cross reference sections in the middle
column, and add in their places, the
cross reference sections in the right
column.
[FR Doc. 2016–19227 Filed 8–17–16; 8:45 am]
rmajette on DSK2TPTVN1PROD with RULES
Remove
4.1.3 ..........................
4.1.4.3 .......................
VerDate Sep<11>2014
4.1.2.4
4.1.2.5
4.1.2.6
4.1.2.7
4.1.2.7
18:35 Aug 17, 2016
Add
Jkt 238001
DEPARTMENT OF TRANSPORTATION
Federal Aviation Administration
14 CFR Part 440
[Docket No.: FAA–2014–1012; Amdt. No.
440–4]
RIN 2120–AK44
4.1.3.1
4.1.3.2
4.1.3.3
4.1.3.4
4.1.3.4
Final rule.
The FAA is amending its
commercial space regulations governing
reciprocal waivers of claims to require
that customers waive claims against all
the customers involved in a launch or
reentry, including those signing a
different set of reciprocal waivers. Also,
customers of a customer contracting
directly with a licensee or permittee
will not have to sign a waiver directly
with the licensee or permittee, other
customers, or the FAA. The FAA is also
adding an appendix to provide
permittees with an example of a Waiver
of Claims and Assumption of
Responsibility for Permitted Activities
with No Customer.
SUMMARY:
■
Section
ACTION:
BILLING CODE 6450–01–P
Reciprocal Waivers of Claims for
Licensed or Permitted Launch and
Reentry Activities
Federal Aviation
Administration (FAA), DOT.
AGENCY:
PO 00000
Frm 00005
Fmt 4700
Sfmt 4700
E:\FR\FM\18AUR1.SGM
18AUR1
Agencies
[Federal Register Volume 81, Number 160 (Thursday, August 18, 2016)]
[Rules and Regulations]
[Pages 55111-55115]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2016-19227]
========================================================================
Rules and Regulations
Federal Register
________________________________________________________________________
This section of the FEDERAL REGISTER contains regulatory documents
having general applicability and legal effect, most of which are keyed
to and codified in the Code of Federal Regulations, which is published
under 50 titles pursuant to 44 U.S.C. 1510.
The Code of Federal Regulations is sold by the Superintendent of Documents.
Prices of new books are listed in the first FEDERAL REGISTER issue of each
week.
========================================================================
Federal Register / Vol. 81, No. 160 / Thursday, August 18, 2016 /
Rules and Regulations
[[Page 55111]]
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[Docket No. EERE-2009-BT-TP-0004]
RIN 1904-AB94
Energy Conservation Program: Test Procedures for Central Air
Conditioners and Heat Pumps; Correction
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule; technical correction.
-----------------------------------------------------------------------
SUMMARY: On June 8, 2016, the U.S. Department of Energy (DOE) published
a final rule in the Federal Register that amended the test procedures
for central air conditioners and heat pumps. This final rule corrects
multiple editorial errors in that final rule.
DATES: Effective Date: August 18, 2016.
FOR FURTHER INFORMATION CONTACT: Ms. Ashley Armstrong, U.S. Department
of Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Office, EE-5B, 1000 Independence Avenue SW., Washington,
DC 20585-0121. Telephone: (202) 586-6590. Email:
Ashley.Armstrong@ee.doe.gov.
Ms. Johanna Jochum, U.S. Department of Energy, Office of the
General Counsel, GC-33, 1000 Independence Avenue SW., Washington, DC
20585-0121. Telephone: (202) 287-6307. Email:
Johanna.Jochum@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
I. Background
On June 8, 2016, DOE's Office of Energy Efficiency and Renewable
Energy published a test procedure final rule in the Federal Register
titled, ``Test Procedures for Central Air Conditioners and Heat Pumps''
(``June 2016 final rule''). 81 FR 36992. Since the publication of that
final rule, it has come to DOE's attention that, due to a technical
oversight, certain portions of the regulatory text adopted in the June
2016 final rule for 10 CFR part 429 and appendix M to subpart B of 10
CFR part 430 (``appendix M'') contained editorial errors.
As part of that final rule, DOE amended 10 CFR 429.16, which
addresses certification of central air conditioners and heat pumps, and
10 CFR 429.70, which addresses alternate efficiency determination
methods. This correction addresses editorial errors in Sec.
429.16(a)(1), (d)(1), (d)(2), and (e)(4). Specifically, at Sec.
429.16(a)(1), DOE included a cross reference to paragraph (c)(2) that
should have referred to paragraph (b)(2)(i). In Sec. 429.16(d)(1) and
(2), DOE mistakenly transposed the words ``less'' and ``greater.'' At
Sec. 429.16(e)(4), DOE erroneously referred to cubic feet per minute
(cfm) instead of cubic feet per minute of standard air (scfm). At Sec.
429.16(e)(4)(viii), DOE failed to remove regulatory text associated
with changes to the test procedure for variable speed heat pumps not
adopted in the June 2016 final rule that had been proposed on November
9, 2015 in a supplementary notice of proposed rulemaking (``November
2015 SNOPR''). 80 FR 69278. In order to remedy these errors, DOE is
issuing this final rule correction to revise the text in these
sections.
In addition, the June 2016 final rule revised appendix M to subpart
B of 10 CFR part 430 (``appendix M''), which specifies the ``Uniform
Test Method for the Measurement the Energy Consumption of Central Air
Conditioners and Heat Pumps.'' This correction also addresses several
editorial errors in appendix M.
In section 3.11.1 of appendix M, ``If using the outdoor air
enthalpy method as the secondary test method,'' DOE erroneously
numbered two subsections with the number ``3.11.1.1.'' The second of
these two is renumbered to ``3.11.1.2.''
In section 4.1 of appendix M, ``Seasonal Energy Efficiency Ratio
(SEER) Calculations,'' DOE erroneously numbered subsection 4.1.3 as
``4.1.2.3,'' which propagated errors in numbering from that point
through the end of section 4.1 and created erroneous cross-references
to these sections. Section 4.1.2.3 is renumbered as section ``4.1.3,''
and the following section numbers through the end of section 4.1 are
renumbered accordingly. Additionally, cross-references to the
renumbered sections are revised.
Sections 2.11 and 3.19 of appendix M contain errors in the
tolerance allowed between temperature measurements. The preamble to the
June 2016 final rule states that the maximum allowable temperature
difference is 2.0[emsp14][deg]F and that it applies to the average
measurements for the test period. 81 FR 36991, 37028 (June 8, 2016). In
section 2.11, DOE erroneously referred to ``maximum difference between
readings'' rather than adding the clarification discussed in the
preamble that ``readings'' referred to the average temperatures
measured during the test period. In section 3.1.9, DOE similarly failed
to include the clarifying information on the tolerance and erroneously
provided a tolerance of 1.5[emsp14][deg]F rather than
2.0[emsp14][deg]F. DOE is correcting section 2.11 accordingly and
correcting 3.1.9 to refer directly to section 2.11 rather than
correcting the provided tolerance.
Tables 8, 9, 15, 16, and 17 of appendix M contained various errors
in testing tolerances for external resistance to airflow, airflow
nozzle pressure difference, and electric voltage. In the preamble of
the June 2016 Final Rule, DOE explained its intention to maintain the
external resistance to airflow tolerance at 0.05 inches of water, to
maintain the airflow nozzle pressure difference tolerance at 2.0%, and
to maintain the electric voltage tolerance at 2.0%. 81 FR 36991, 37036
(June 8, 2016). However, this was not reflected in tables 8, 9, 15, 16
and 17 of appendix M, and the tables are revised to reflect these
corrections.
In section 3.13.1.d of appendix M, P2x was erroneously
printed instead of Px in two instances. This section
provides instructions for measurement of the indoor unit low voltage
power Px, which is later subtracted from the measurement of
heating season total off mode power (P2x) for coil-only
split systems and for blower coil split systems for which a furnace or
a modular blower is the designated air mover. Instances of
P2x in section 3.13.1.d of appendix M are revised to
Px.
Finally, many of the instructions in the final rule that indicate
that a default cyclic degradation coefficient is to be used if the
tests to determine this value are not conducted, but erroneously did
[[Page 55112]]
not specify that the default value is to be used if the value
determined using the test exceeded the default value. 81 FR 36991,
37033 (June 8, 2016). DOE intended that the default value is to be used
if the value determined using the test exceeds the default value for
the cyclic degradation coefficient, and is correcting this omission in
this final rule correction.
II. Need for Correction
As published, the adopted test procedure text may potentially
result in confusion regarding how to correctly conduct DOE's central
air conditioners and heat pumps test procedure.
Because this final rule would simply correct errors in the
regulatory text without making substantive changes to the test
procedures, the changes addressed in this document are technical in
nature. Accordingly, DOE finds that there is good cause under 5 U.S.C.
553(b)(B) to not issue a separate notice to solicit public comment on
the changes contained in this document. Issuing a separate notice to
solicit public comment would be impracticable, unnecessary, and
contrary to the public interest.
III. Procedural Requirements
DOE has concluded that the determinations made pursuant to the
various procedural requirements applicable to the June 8, 2016 test
procedure final rule remain unchanged for this final rule technical
correction. These determinations are set forth in the June 8, 2016
final rule. 81 FR 36992.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Reporting and recordkeeping
requirements.
10 CFR Part 430
Administrative practice and procedure, Confidential business
information, Energy conservation, Energy conservation test procedures,
Household appliances, Imports, Incorporation by reference,
Intergovernmental relations, Small businesses.
Issued in Washington, DC, on August 5, 2016.
Kathleen Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
For the reasons stated in the preamble, DOE amends parts 429 and
430 of chapter II of title 10, Code of Federal Regulations to read as
follows:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
Sec. 429.16 [Amended]
0
2. Section 429.16 is amended:
0
a. In paragraph (a)(1), in the last row of the table, by removing
``(c)(2)'' and adding in its place ``(b)(2)(i)'';
0
b. In paragraph (d)(1) by removing ``less'' and adding in its place
``greater'';
0
c. In paragraph (d)(2) by removing ``greater'' and adding in its place
``less'';
0
d. In paragraph (e)(4) by:
0
i. Adding ``of standard air'' after ``(in cubic feet per minute'';
0
ii. Removing the two instances of ``(cfm)'' and adding in its place
``(scfm)''; and
0
iii. Removing paragraph (viii).
PART 430--ENERGY CONSERVATION PROGRAM FOR CONSUMER PRODUCTS
0
3. The authority citation for part 430 continues to read as follows:
Authority: 42 U.S.C. 6291-6309; 28 U.S.C. 2461 note.
0
4. Appendix M to subpart B of part 430 is amended by:
0
a. In section 2.11.b(2), first paragraph, last sentence, removing
``readings'' and adding in its place ``average temperatures measured
during the test period'';
0
b. Revising section 3.1.9;
0
c. Revising section 3.2.1, introductory text;
0
d. In section 3.2.3.d., adding a sentence after the first sentence;
0
e. In section 3.3, paragraph d., revising Table 8;
0
f. In section 3.5, paragraph h., revising Table 9 and its footnotes;
0
g. In section 3.5.3, adding a sentence after the second sentence;
0
h. Revising section 3.6.3.b., introductory text;
0
i. In section 3.7, paragraph a., revising Table 15;
0
j. In section 3.8.a., removing the sixth sentence;
0
k. In section 3.8.1, adding a sentence after the third sentence and
revising Table 16;
0
l. In section 3.9, paragraph f., revising Table 17;
0
m. In section 3.11, redesignating the second section 3.11.1.1
(``Official Test'') as section 3.11.1.2;
0
n. In section 3.13.1.d, removing the two instances of
``P2x'' and adding in their places ``Px'';
0
o. In section 4.1.1.b, adding a second sentence;
0
p. In section 4.1.2.1.c, adding a second sentence;
0
q. Redesignating sections 4.1.4.1 and 4.1.4.2 as sections 4.1.5.1 and
4.1.5.2, respectively;
0
r. Redesignating section 4.1.4 as section 4.1.5;
0
s. Redesignating sections 4.1.3.1, 4.1.3.2, and 4.1.3.3 as sections
4.1.4.1, 4.1.4.2, and 4.1.4.3, respectively;
0
t. Redesignating section 4.1.3 as section 4.1.4;
0
u. Redesignating section 4.1.2.7 as section 4.1.3.4;
0
v. Redesignating section 4.1.2.6 as section 4.1.3.3;
0
w. Redesignating section 4.1.2.5 as section 4.1.3.2;
0
x. Redesignating section 4.1.2.4 as section 4.1.3.1;
0
y. Redesignating section 4.1.2.3 as section 4.1.3;
0
z. In newly redesignated section 4.1.3.1, revising the equation and
related information immediately before Table 18;
0
aa. In newly redesignated section 4.1.4.1, adding a sentence after the
last sentence of the section;
0
bb. In section 4.2.1, adding the sentence ``Evaluate the heating mode
cyclic degradation factor [Cdot]D\h\ as specified in section
3.8.1 of this appendix.'', after ``Use Equation 4.2-2 to determine
BL(Tj). Obtain fractional bin hours for the heating season, nj/N, from
Table 19.''; and
0
cc. In section 4.2.3.1, adding the sentence ``Evaluate the heating mode
cyclic degradation factor CD\h\ as specified in section
3.8.1 of this appendix.'', after ``[delta]'(Tj) = the low temperature
cutoff factor, dimensionless.'';
The revisions and additions read as follows.
Appendix M to Subpart B of Part 430--Uniform Test Method for Measuring
the Energy Consumption of Central Air Conditioners and Heat Pumps
* * * * *
3.1.9 Requirement for the Air Temperature Distribution Entering the
Outdoor Coil
Monitor the temperatures of the air entering the outdoor coil
using air sampling devices and/or temperature sensor grids,
maintaining the required tolerances, if applicable, as described in
section 2.11 of this appendix.
* * * * *
[[Page 55113]]
3.2.1 Tests for a System Having a Single-Speed Compressor and Fixed
Cooling Air Volume Rate
This set of tests is for single-speed-compressor units that do
not have a cooling minimum air volume rate or a cooling intermediate
air volume rate that is different than the cooling full load air
volume rate. Conduct two steady-state wet coil tests, the A and B
Tests. Use the two optional dry-coil tests, the steady-state C Test
and the cyclic D Test, to determine the cooling mode cyclic
degradation coefficient, CD\c\. If the two optional tests
are conducted but yield a tested CD\c\ that exceeds the
default CD\c\ or if the two optional tests are not
conducted, assign CD\c\ the default value of 0.25 (for
outdoor units with no match) or 0.20 (for all other systems). Table
4 specifies test conditions for these four tests.
* * * * *
3.2.3 Tests for a Unit Having a Two-Capacity Compressor (See Section
1.2 of This Appendix, Definitions)
* * * * *
d. * * * If the two optional tests are conducted but yield a
tested CD\c\ (k = 2) that exceeds the default
CD\c\ (k = 2) or if the two optional tests are not
conducted, assign CD\c\ (k = 2) the default value. ***
* * * * *
3.3. * * *
d. * * *
Table 8--Test Operating and Test Condition Tolerances for Section 3.3
Steady-State Wet Coil Cooling Mode Tests and Section 3.4 Dry Coil
Cooling Mode Tests
------------------------------------------------------------------------
Test operating Test condition
tolerance \1\ tolerance \1\
------------------------------------------------------------------------
Indoor dry-bulb, [deg]F:
Entering temperature.......... 2.0 0.5
Leaving temperature........... 2.0
Indoor wet-bulb, [deg]F:
Entering temperature.......... 1.0 \2\ 0.3
Leaving temperature........... \2\ 1.0
Outdoor dry-bulb, [deg]F:
Entering temperature.......... 2.0 0.5
Leaving temperature........... \3\ 2.0
Outdoor wet-bulb, [deg]F:
Entering temperature.......... 1.0 \4\ 0.3
Leaving temperature........... \3\ 1.0
External resistance to airflow, 0.05 \5\ 0.02
inches of water..................
Electrical voltage, % of rdg...... 2.0 1.5
Nozzle pressure drop, % of rdg.... 2.0
------------------------------------------------------------------------
\1\ See section 1.2 of this appendix, Definitions.
\2\ Only applies during wet coil tests; does not apply during steady-
state, dry coil cooling mode tests.
\3\ Only applies when using the outdoor air enthalpy method.
\4\ Only applies during wet coil cooling mode tests where the unit
rejects condensate to the outdoor coil.
\5\ Only applies when testing non-ducted units.
* * * * *
3.5 * * *
h. * * *
Table 9--Test Operating and Test Condition Tolerances for Cyclic Dry
Coil Cooling Mode Tests
------------------------------------------------------------------------
Test operating Test condition
tolerance \1\ tolerance \1\
------------------------------------------------------------------------
Indoor entering dry-bulb 2.0 0.5
temperature \2\, [deg]F..........
Indoor entering wet-bulb ................. (\3\)
temperature, [deg]F..............
Outdoor entering dry-bulb 2.0 0.5
temperature \2\, [deg]F..........
External resistance to airflow 0.05
\2\, inches of water.............
Airflow nozzle pressure difference 2.0 \4\ 2.0
or velocity pressure \2\, % of
reading..........................
Electrical voltage \5\, % of rdg.. 2.0 1.5
------------------------------------------------------------------------
\1\ See section 1.2 of this appendix, Definitions.
\2\ Applies during the interval that air flows through the indoor
(outdoor) coil except for the first 30 seconds after flow initiation.
For units having a variable-speed indoor blower that ramps, the
tolerances listed for the external resistance to airflow apply from 30
seconds after achieving full speed until ramp down begins.
\3\ Shall at no time exceed a wet-bulb temperature that results in
condensate forming on the indoor coil.
\4\ The test condition shall be the average nozzle pressure difference
or velocity pressure measured during the steady-state dry coil test.
\5\ Applies during the interval when at least one of the following--the
compressor, the outdoor fan, or, if applicable, the indoor blower--are
operating except for the first 30 seconds after compressor start-up.
* * * * *
3.5.3 Cooling-Mode Cyclic-Degradation Coefficient Calculation
* * * If the two optional tests are conducted but yield a tested
CD\c\ that exceeds the default CD\c\ or if the
two optional tests are not conducted, assign CD\c\ the
default value of 0.25 for variable-speed compressor systems and
outdoor units with no match, and 0.20 for all other systems.* * *
* * * * *
3.6.3 Tests for a Heat Pump Having a Two-Capacity Compressor (see
Section 1.2 of This Appendix, Definitions), Including Two-Capacity,
Northern Heat Pumps (see Section 1.2 of This Appendix, Definitions)
* * * * *
b. Conduct the optional high temperature cyclic test
(H1C1) to determine the heating mode cyclic-degradation
coefficient, CD\h\. If
[[Page 55114]]
this optional test is conducted but yields a tested CD\h\
that exceeds the default CD\h\ or if the optional test is
not conducted, assign CD\h\ the default value of 0.25. If
a two-capacity heat pump locks out low capacity operation at lower
outdoor temperatures, conduct the high temperature cyclic test
(H1C2) to determine the high-capacity heating mode
cyclic-degradation coefficient, CD\h\ (k=2). If this
optional test at high capacity is conducted but yields a tested
CD\h\ (k = 2) that exceeds the default CD\h\
(k = 2) or if the optional test is not conducted, assign
CD\h\ the default value. The default CD\h\
(k=2) is the same value as determined or assigned for the low-
capacity cyclic-degradation coefficient, CD\h\ [or
equivalently, CD\h\ (k=1)]. Table 12 specifies test
conditions for these nine tests.
* * * * *
3.7 * * *
a. * * *
Table 15--Test Operating and Test Condition Tolerances for Section 3.7
and Section 3.10 Steady-State Heating Mode Tests
------------------------------------------------------------------------
Test operating Test condition
tolerance \1\ tolerance \1\
------------------------------------------------------------------------
Indoor dry-bulb, [deg]F:
Entering temperature.......... 2.0 0.5
Leaving temperature........... 2.0
Indoor wet-bulb, [deg]F:
Entering temperature.......... 1.0
Leaving temperature........... 1.0
Outdoor dry-bulb, [deg]F:
Entering temperature.......... 2.0 0.5
Leaving temperature........... \2\ 2.0
Outdoor wet-bulb, [deg]F:
Entering temperature.......... 1.0 0.3
Leaving temperature........... \2\ 1.0
External resistance to airflow, 0.05 \3\ 0.02
inches of water..................
Electrical voltage, % of rdg...... 2.0 1.5
Nozzle pressure drop, % of rdg.... 2.0
------------------------------------------------------------------------
\1\ See section 1.2 of this appendix, Definitions.
\2\ Only applies when the Outdoor Air Enthalpy Method is used.
\3\ Only applies when testing non-ducted units.
* * * * *
3.8.1 * * *
* * * If the optional cyclic test is conducted but yields a
tested CD\h\ that exceeds the default CD\h\ or
if the optional test is not conducted, assign CD\h\ the
default value of 0.25.* * *
* * * * *
Table 16--Test Operating and Test Condition Tolerances for Cyclic
Heating Mode Tests
------------------------------------------------------------------------
Test operating Test condition
tolerance \1\ tolerance \1\
------------------------------------------------------------------------
Indoor entering dry-bulb 2.0 0.5
temperature,\2\ [deg]F...........
Indoor entering wet-bulb 1.0
temperature,\2\ [deg]F...........
Outdoor entering dry-bulb 2.0 0.5
temperature,\2\ [deg]F...........
Outdoor entering wet-bulb 2.0 1.0
temperature,\2\ [deg]F...........
External resistance to air- 0.05
flow,\2\ inches of water.........
Airflow nozzle pressure difference 2.0 \3\ 2.0
or velocity pressure,\2\ % of
reading..........................
Electrical voltage,\4\ % of rdg... 2.0 1.5
------------------------------------------------------------------------
\1\ See section 1.2 of this appendix, Definitions.
\2\ Applies during the interval that air flows through the indoor
(outdoor) coil except for the first 30 seconds after flow initiation.
For units having a variable-speed indoor blower that ramps, the
tolerances listed for the external resistance to airflow shall apply
from 30 seconds after achieving full speed until ramp down begins.
\3\ The test condition shall be the average nozzle pressure difference
or velocity pressure measured during the steady-state test conducted
at the same test conditions.
\4\ Applies during the interval that at least one of the following--the
compressor, the outdoor fan, or, if applicable, the indoor blower--are
operating, except for the first 30 seconds after compressor start-up.
* * * * *
3.9 * * *
f. * * *
Table 17--Test Operating and Test Condition Tolerances for Frost Accumulation Heating Mode Tests
----------------------------------------------------------------------------------------------------------------
Test operating tolerance \1\ Test condition
-------------------------------------- tolerance \1\
------------------
Sub-interval H Sub-interval D Sub-interval H
\2\ \3\ \2\
----------------------------------------------------------------------------------------------------------------
Indoor entering dry-bulb temperature, [deg]F........... 2.0 \4\ 4.0 0.5
Indoor entering wet-bulb temperature, [deg]F........... 1.0
Outdoor entering dry-bulb temperature, [deg]F.......... 2.0 10.0 1.0
[[Page 55115]]
Outdoor entering wet-bulb temperature, [deg]F.......... 1.5 ................. 0.5
External resistance to airflow, inches of water........ 0.05 ................. \5\ 0.02
Electrical voltage, % of rdg........................... 2.0 ................. 1.5
----------------------------------------------------------------------------------------------------------------
\1\ See section 1.2 of this appendix, Definitions.
\2\ Applies when the heat pump is in the heating mode, except for the first 10 minutes after termination of a
defrost cycle.
\3\ Applies during a defrost cycle and during the first 10 minutes after the termination of a defrost cycle when
the heat pump is operating in the heating mode.
\4\ For heat pumps that turn off the indoor blower during the defrost cycle, the noted tolerance only applies
during the 10 minute interval that follows defrost termination.
\5\ Only applies when testing non-ducted heat pumps.
* * * * *
4.1.1 * * *
b. * * * Evaluate the cooling mode cyclic degradation factor
CD\c\ as specified in section 3.5.3 of this appendix.
* * * * *
4.1.2.1 * * *
c. * * * Evaluate the cooling mode cyclic degradation factor
CD\c\ as specified in section 3.5.3 of this appendix.
* * * * *
4.1.3.1 * * *
nj/N = fractional bin hours for the cooling season; the
ratio of the number of hours during the cooling season when the
outdoor temperature fell within the range represented by bin
temperature Tj to the total number of hours in the
cooling season, dimensionless.
Obtain the fractional bin hours for the cooling season,
nj/N, from Table 18. Use Equations 4.1.3-1 and 4.1.3-2,
respectively, to evaluate Qck=1(Tj)
and [Edot]ck=1(Tj). Evaluate the
cooling mode cyclic degradation factor CD\c\ as specified
in section 3.5.3 of this appendix.
* * * * *
4.1.4.1 * * *
* * * Evaluate the cooling mode cyclic degradation factor
CD\c\ as specified in section 3.5.3 of this appendix.
* * * * *
Appendix M to Subpart B of Part 430--[Amended]
0
5. In the table below, for each section of appendix M to subpart B of
part 430 indicated in the left column, remove the language indicated in
the middle column from wherever it appears in that section, and add the
language indicated in the right column.
------------------------------------------------------------------------
Sections Remove Add
------------------------------------------------------------------------
3.2.2.1, 3.2.3.a....... A default value of If the two optional
CD\c\ may be used in tests are conducted
lieu of conducting the but yield a tested
cyclic test. The CD\c\ that exceeds
default value of CD\c\ the default CD\c\ or
is 0.20. if the two optional
tests are not
conducted, assign
CD\c\ the default
value of 0.20.
3.2.4.a................ A default value for If the two optional
CD\c\ may be used in tests are conducted
lieu of conducting the but yield a tested
cyclic test. The CD\c\ that exceeds
default value of CD\c\ the default CD\c\ or
is 0.25. if the two optional
tests are not
conducted, assign
CD\c\ the default
value of 0.25.
3.6.1.................. A default value for If this optional test
CD\h\ may be used in is conducted but
lieu of conducting the yields a tested CD\h\
cyclic test. The that exceeds the
default value of CD\h\ default CD\h\ or if
is 0.25. the optional test is
not conducted, assign
CD\h\ the default
value of 0.25.
3.6.2, 3.6.4.a......... A default value for If this optional test
CD\h\ may be used in is conducted but
lieu of conducting the yields a tested CD\h\
cyclic. The default that exceeds the
value of CD\h\ is 0.25. default CD\h\ or if
the optional test is
not conducted, assign
CD\h\ the default
value of 0.25.
------------------------------------------------------------------------
Appendix M to Subpart B of Part 430--[Amended]
0
6. For each newly redesignated section of appendix M to subpart B of
part 430 in the first column, remove the cross reference sections in
the middle column, and add in their places, the cross reference
sections in the right column.
------------------------------------------------------------------------
Section Remove Add
------------------------------------------------------------------------
4.1.3............................................. 4.1.2.4 4.1.3.1
4.1.2.5 4.1.3.2
4.1.2.6 4.1.3.3
4.1.2.7 4.1.3.4
4.1.4.3........................................... 4.1.2.7 4.1.3.4
------------------------------------------------------------------------
[FR Doc. 2016-19227 Filed 8-17-16; 8:45 am]
BILLING CODE 6450-01-P