Energy Conservation Program: Test Procedures for Central Air Conditioners and Heat Pumps, 36991-37120 [2016-12592]
Download as PDF
Vol. 81
Wednesday,
No. 110
June 8, 2016
Part II
Department of Energy
asabaliauskas on DSK3SPTVN1PROD with RULES
10 CFR Parts 429 and 430
Energy Conservation Program: Test Procedures for Central Air Conditioners
and Heat Pumps; Final Rule
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00001
Fmt 4717
Sfmt 4717
E:\FR\FM\08JNR2.SGM
08JNR2
36992
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[Docket No. EERE–2009–BT–TP–0004]
RIN 1904–AB94
Energy Conservation Program: Test
Procedures for Central Air
Conditioners and Heat Pumps
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
On November 9, 2015, the
U.S. Department of Energy (DOE) issued
a supplemental notice of proposed
rulemaking (SNOPR) to amend the test
procedure for central air conditioners
and heat pumps. That proposed
rulemaking serves as the basis for the
final rule. The final rule, in addition to
satisfying the agency’s obligation to
periodically review its test procedures
for covered equipment, amends specific
certification, compliance, and
enforcement provisions related to this
product. In the final rule DOE makes the
following amendments to the current
test procedure: a new basic model
definition as it pertains to central air
conditioners and heat pumps and
revised requirements for represented
values; revised alternative efficiency
determination methods; termination of
active waivers and interim waivers;
procedures to determine off mode
power consumption; changes to the test
procedure that would improve test
repeatability and reduce test burden;
and clarifications to ambiguous sections
of the test procedure intended also to
improve test repeatability and
reproducibility Some of these
amendments also include incorporation
by reference of updated industry
standards.
DATES: The effective date of this rule is
July 8, 2016. The final rule changes will
be mandatory for representations of
efficiency starting December 5, 2016.
The incorporation by reference of
certain publications listed in this rule
was approved by the Director of the
Federal Register on July 8, 2016.
ADDRESSES: The docket, which includes
Federal Register notices, public meeting
attendee lists and transcripts,
comments, and other supporting
documents/materials, is available for
review at regulations.gov. All
documents in the docket are listed in
the regulations.gov index. However,
some documents listed in the index,
such as those containing information
that is exempt from public disclosure,
may not be publicly available.
asabaliauskas on DSK3SPTVN1PROD with RULES
SUMMARY:
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
A link to the docket Web page can be
found at: www1.eere.energy.gov/
buildings/appliance_standards/
rulemaking.aspx/ruleid/72. This Web
page will contain a link to the docket for
this notice on the regulations.gov site.
The regulations.gov Web page will
contain simple instructions on how to
access all documents, including public
comments, in the docket.
For further information on how to
review the docket, contact Ms. Brenda
Edwards at (202) 586–2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT:
Ashley Armstrong, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Program, EE–2J, 1000
Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–6590. Email:
Ashley.Armstrong@ee.doe.gov.
Johanna Jochum, U.S. Department of
Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue
SW., Washington, DC, 20585–0121.
Telephone: (202) 287–6307. Email:
Johanna.Jochum@hq.doe.gov.
For further information on how to
submit a comment, review other public
comments and the docket, or participate
in the public meeting, contact Ms.
Brenda Edwards at (202) 586–2945 or by
email: Brenda.Edwards@ee.doe.gov.
SUPPLEMENTARY INFORMATION: This final
rule incorporates by reference into part
430 specific sections, figures, and tables
in the following industry standards:
(1) ANSI/AHRI 210/240–2008 with
Addenda 1 and 2, (‘‘AHRI 210/240–
2008’’): 2008 Standard for Performance
Rating of Unitary Air-Conditioning &
Air-Source Heat Pump Equipment,
ANSI approved 27 October 2011;
(2) ANSI/AHRI 1230–2010 with
Addendum 2, (‘‘AHRI 1230–2010’’):
2010 Standard for Performance Rating of
Variable Refrigerant Flow (VRF) MultiSplit Air-Conditioning and Heat Pump
Equipment, ANSI approved August 2,
2010;
Copies of AHRI 210/240–2008 and
AHRI 1230–2010 can be obtained from
the Air-Conditioning, Heating, and
Refrigeration Institute, 2111 Wilson
Boulevard, Suite 500, Arlington, VA
22201, USA, 703–524–8800, or by going
to https://www.ahrinet.org/site/686/
Standards/HVACR-Industry-Standards/
Search-Standards .
(3) ANSI/ASHRAE 23.1–2010,
(‘‘ASHRAE 23.1–2010’’): Methods of
Testing for Rating the Performance of
Positive Displacement Refrigerant
Compressors and Condensing Units that
Operate at Subcritical Temperatures of
the Refrigerant, ANSI approved January
28, 2010;
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
(4) ANSI/ASHRAE Standard 37–2009,
(‘‘ANSI/ASHRAE 37–2009’’), Methods
of Testing for Rating Electrically Driven
Unitary Air-Conditioning and Heat
Pump Equipment, ANSI approved June
25, 2009;
(5) ANSI/ASHRAE 41.1–2013,
(‘‘ANSI/ASHRAE 41.1–2013’’): Standard
Method for Temperature Measurement,
ANSI approved January 30, 2013;
(6) ANSI/ASHRAE 41.6–2014,
(‘‘ASHRAE 41.6–2014’’): Standard
Method for Humidity Measurement,
ANSI approved July 3, 2014;
(7) ANSI/ASHRAE 41.9–2011,
(‘‘ASHRAE 41.9–2011’’): Standard
Methods for Volatile-Refrigerant Mass
Flow Measurements Using Calorimeters,
ANSI approved February 3, 2011
(8) ANSI/ASHRAE 116–2010,
(‘‘ASHRAE 116–2010’’): Methods of
Testing for Rating Seasonal Efficiency of
Unitary Air Conditioners and Heat
Pumps, ANSI approved February 24,
2010.
(9) ANSI/ASHRAE 41.2–1987
(Reaffirmed 1992), (‘‘ASHRAE 41.2–
1987 (RA 1992)’’): ‘‘Standard Methods
for Laboratory Airflow Measurement’’,
ANSI approved October 1, 1987.
Copies of ASHRAE 23.1–2010, ANSI/
ASHRAE 37–2009, ANSI/ASHRAE
41.1–2013, ASHRAE 41.6–2014,
ASHRAE 41.9–2011, ASHRAE 116–
2010, and ASHRAE 41.2–1987 (RA
1992) can be purchased from ASHRAE’s
Web site at https://www.ashrae.org/
resources—publications.
(10) ANSI/AMCA 210–2007, ANSI/
ASHRAE 51–2007, (‘‘AMCA 210–2007’’)
Laboratory Methods of Testing Fans for
Certified Aerodynamic Performance
Rating, August 17, 2007;
Copies of AMCA 210–2007 can be
purchased from AMCA’s Web site at
https://www.amca.org/store/index.php.
For a further discussion of these
standards, see section IV.N.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Summary of the Final Rule
III. Discussion
A. Definitions, Testing, Represented
Values, and Compliance of Basic Models
of Central Air Conditioners and Heat
Pumps
1. Basic Model Definition
2. Additional Definitions
3. Determination of Represented Values
4. Compliance with Federal (National or
Regional) Standards
5. Certification Reports
6. Represented Values
7. Product-Specific Enforcement Provisions
B. Alternative Efficiency Determination
Methods
1. General Background
2. Terminology
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
3. Elimination of the Pre-Approval
Requirement
4. AEDM Validation
5. AEDM Verification Testing
6. Failure to Meet Certified Represented
Values
7. Action Following a Determination of
Noncompliance
8. AEDM for Off Mode
C. Waiver Procedures
1. Air-to-Water Heat Pumps and Air
Conditioners
2. Clarification of the Test Procedure
Pertaining to Multi-Circuit Products
3. Clarification of the Test Procedure
Pertaining to Multi-Blower Products
D. Measurement of Off Mode Power
Consumption
1. Test Temperatures
2. Calculation and Weighting of P1 and P2
3. Time Delay Credit and Removal of
Calculations for Off Mode Energy
Consumption and Annual Performance
Factor
4. Impacts on Product Reliability
5. Off Mode Power Consumption for
Intelligent Compressor Heat Control
6. Off Mode Test Voltage for Dual-Voltage
Units
7. Off Mode Test Tolerance
8. Organization of Off Mode Test Procedure
9. Certification
10. Compliance Dates
E. Test Repeatability Improvement and
Test Burden Reduction
1. Indoor Fan Speed Settings for Blower
Coil or Single-Package Systems
2. Air Volume Rate Adjustment for CoilOnly Systems
3. Requirements for the Refrigerant Lines
and Mass Flow Meter
4. Outdoor Room Temperature Variation
5. Method of Measuring Inlet Air
Temperature on the Outdoor Side
6. Requirements for the Air Sampling
Device
7. Variation in Maximum Compressor
Speed with Outdoor Temperature
8. Refrigerant Charging Requirements
9. Alternative Arrangement for Thermal
Loss Prevention for Cyclic Tests
10. Test Unit Voltage Supply
11. Coefficient of Cyclic Degradation
12. Break-in Periods Prior to Testing
13. Industry Standards that are
Incorporated by Reference
14. References to ASHRAE 116–1995 (RA
2005)
15. Additional Changes Based on AHRI
210/240-Draft
16. Damping Pressure Transducer Signals
17. Clarify Inputs for the Demand Defrost
Credit Equation
18. Improving Test Consistency Associated
with Indoor Unit Air Inlet Geometry
F. Clarification of Test Procedure
Provisions
1. Manufacturer Consultation
2. Incorporation by Reference of AHRI
1230–2010
3. Replacement of the Informative
Guidance Table for Using the Federal
Test Procedure
4. Clarifying the Definition of a Mini-Split
System
5. Clarifying the Definition of a Multi-Split
System
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
6. Clarifying the Housing for Uncased Coil
7. Test Procedure Reprint
G. Additional Comments from Interested
Parties
1. Wet Coil Performance
2. Barometric Pressure Correction
3. Inlet Screen
H. Compliance with other Energy Policy
and Conservation Act Requirements
1. Dates
2. Measured Energy Use
3. Test Burden
4. Potential Incorporation of International
Electrotechnical Commission Standard
62301 and International Electrotechnical
Commission Standard 62087
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under the Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by
Reference
V. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III, Part B 1 of the Energy Policy
and Conservation Act of 1975 (‘‘EPCA’’
or ‘‘the Act’’), Public Law 94–163 (42
U.S.C. 6291–6309, as codified) sets forth
a variety of provisions designed to
improve energy efficiency and
established the Energy Conservation
Program for Consumer Products Other
Than Automobiles.2 These products
include single-phase central air
conditioners and central air
conditioning heat pumps 3 with rated
cooling capacities less than 65,000
British thermal units per hour (Btu/h),
which are the focus of this Final Rule.
(42 U.S.C. 6291(1)–(2), (21) and
6292(a)(3))
Under EPCA, DOE’s energy
conservation program generally consists
of four parts: (1) testing; (2) labeling; (3)
Federal energy conservation standards;
1 For editorial reasons, Part B was codified as Part
A in the U.S. Code.
2 All references to EPCA in this document refer
to the statute as amended through the Energy
Efficiency Improvement Act of 2015, Public Law
114–11 (Apr. 30, 2015).
3 Where this notice uses the term ‘‘CAC/HP’’, they
are in reference specifically to central air
conditioners and heat pumps as defined by EPCA.
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
36993
and (4) certification and enforcement.
The testing requirements consist of test
procedures that manufacturers of
covered products must use as the basis
for: (1) certifying to DOE that their
products comply with applicable energy
conservation standards adopted
pursuant to EPCA, and (2) making other
representations about the efficiency of
those products. (42 U.S.C. 6293(c); 42
U.S.C. 6295(s)) Similarly, DOE must use
these test procedures to determine
whether covered products comply with
any relevant standards promulgated
under EPCA. (42 U.S.C. 6295(s))
EPCA sets forth criteria and
procedures DOE must follow when
prescribing or amending test procedures
for covered products. (42 U.S.C.
6293(b)(3)) EPCA provides, in relevant
part, that any test procedures prescribed
or amended under this section shall be
reasonably designed to produce test
results which measure the energy
efficiency, energy use, or estimated
annual operating cost of a covered
product during a representative average
use cycle or period of use, and shall not
be unduly burdensome to conduct. Id.
In addition, if DOE determines that a
test procedure amendment is warranted,
it must publish proposed test
procedures and offer the public an
opportunity to present oral and written
comments on them. (42 U.S.C.
6293(b)(2)) Finally, in any rulemaking to
amend a test procedure, DOE must
determine to what extent, if any, the
amended test procedure would alter the
measured energy efficiency of any
covered product as determined under
the existing test procedure. (42 U.S.C.
6293(e)(1))
The Energy Independence and
Security Act of 2007 (EISA 2007), Public
Law 110–140, amended EPCA to require
that, at least once every 7 years, DOE
must review test procedures for all
covered products and either amend the
test procedures (if the Secretary
determines that amended test
procedures would more accurately or
fully comply with the requirements of
42 U.S.C. 6293(b)(3)) or publish a notice
in the Federal Register of any
determination not to amend a test
procedure. (42 U.S.C. 6293(b)(1)(A))
DOE last published a test procedure
final rule for central air conditioners
and heat pumps on October 22, 2007. 72
FR 59906. The existing DOE test method
for central air conditioners and heat
pumps adopted pursuant to that rule
appears at Title 10 of the Code of
Federal Regulations (CFR) Part 430,
Subpart B, Appendix M (‘‘Uniform Test
Method for Measuring the Energy
Consumption of Central Air
Conditioners and Heat Pumps’’). That
E:\FR\FM\08JNR2.SGM
08JNR2
36994
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
procedure establishes the currently
permitted means for determining energy
efficiency and annual energy
consumption of these products. The
amendments in this final rule will not
alter the measured efficiency of central
air conditioners and heat pumps.
EISA 2007 also established that the
Department’s test procedures for all
covered products must account for
standby mode and off mode energy
consumption. (42 U.S.C. 6295(gg)(2)(A))
For central air conditioners and heat
pumps, standby mode is incorporated
into the SEER metric, while off mode
power consumption is separately
regulated. This final rule includes
modifications relevant to the
determination of both SEER (including
standby mode) and off mode power
consumption.
10 CFR 430.27 allows manufacturers
to submit an application for an interim
waiver and/or a petition for a waiver
granting relief from adhering to the test
procedure requirements found under 10
CFR part 430, subpart B, appendix M.
For those waivers that are active,
however, 10 CFR 430.27(l) requires DOE
to amend its regulations so as to
eliminate any need for the continuation
of such waivers. To this end, this final
rule amends the test procedure
concerning several waivers.
B. Background
This final rule addresses proposals
and comments from three separate
rulemakings, two guidance documents,
and two working groups: (1) proposals
for off mode test procedures made in
earlier notices as part of this rulemaking
(Docket No. EERE–2009–BT–TP–0004);
(2) proposals regarding alternative
efficiency determination methods
(AEDMs) (Docket No. EERE–2011–BT–
TP–0024); (3) the recommendations of
the regional standards enforcement
Working Group (Regional Standards
Enforcement Working Group) (Docket
No. EERE–2011–BT–CE–0077); (4) a
draft guidance document related to
testing and rating split systems with
blower coil units (Docket No. EERE–
2014–BT–GUID–0033); (5) a draft
guidance document that deals with
selecting units for testing, rating, and
certifying split-system combinations,
including discussion of basic models
and of condensing units and evaporator
coils sold separately for replacement
installation (Docket No. EERE–2014–
BT–GUID–0032); and (6) stakeholder
comments from a request for
information regarding energy
conservation standards as well as the
recommendations of the central air
conditioner and heat pump energy
conservation standards Working Group
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
(CAC/HP ECS Working Group) (Docket
No. EERE–2014–BT–STD–0048).
1. Proposals for Off Mode Test
Procedures
DOE’s initial proposals for estimating
off mode power consumption in the test
procedure for central air conditioners
and heat pumps were shared with the
public in a notice of proposed
rulemaking published in the Federal
Register on June 2, 2010 (June 2010
NOPR; 75 FR 31224) and at a public
meeting at DOE headquarters in
Washington, DC, on June 11, 2010
(Public Meeting Transcript, Doc. ID.
EERE–2009–BT–TP–0004–0005).
Subsequently, DOE published a
supplemental notice of proposed
rulemaking (SNOPR) on April 1, 2011,
in response to comments received on
the June 2010 NOPR and due to the
results of additional laboratory testing
conducted by DOE. (April 2011 SNOPR)
76 FR 18105, 18127. DOE received
additional comments in response to the
April 2011 SNOPR and proposed an
amended version of the off mode
procedure that addressed those
comments in a second SNOPR on
October 24, 2011 (October 2011
SNOPR). 76 FR 65616. DOE received
additional comments during the
comment period of the October 24, 2011
SNOPR and the subsequent extended
comment period. 76 FR 79135.
Between the April 2011 and October
2011 SNOPRs, DOE published a direct
final rule (DFR) in the Federal Register
on June 27, 2011, that set forth amended
energy conservation standards for
central air conditioners and central air
conditioning heat pumps, including a
new standard for off mode electrical
power consumption. (June 2011 DFR) 76
FR 37408. Under the June 2011 DFR,
central air conditioning and heat pump
units manufactured on or after January
1, 2015, would be subject to the
published standard for off mode
electrical power consumption. 10 CFR
430.32(c)(6). However, DOE has issued
an enforcement policy statement
regarding off mode standards for central
air conditioners and central air
conditioning heat pumps 4 (July 2014
Enforcement Policy Statement)
specifying that DOE will not assert civil
penalty authority for violation of the off
mode standard until 180 days following
publication of a final rule establishing a
test method for measuring off mode
electrical power consumption.
4 Available at: https://energy.gov/sites/prod/files/
2014/07/f17/
Enforcement%20Policy%20Statement%20%20cac%20off%20mode.pdf (Last accessed March
30, 2015.)
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
2. Proposals for AEDMs
DOE also pursued, in a request for
information (RFI) published on April
18, 2011, (AEDM RFI) (76 FR 21673)
and a NOPR published on May 31, 2012,
(AEDM NOPR) (77 FR 32038) revisions
to its existing alternative efficiency
determination methods (AEDM) and
alternative rating methods (ARM)
requirements to improve the approach
by which manufacturers may use
modeling techniques as the basis to
certify consumer products and
commercial and industrial equipment
covered under EPCA. DOE also
published a final rule regarding AEDM
requirements for commercial and
industrial equipment only (Commercial
Equipment AEDM FR). 78 FR 79579
(Dec. 31, 2013).
3. Regional Enforcement Standards
Working Group and Guidance
Documents
On June 13, 2014, DOE published a
notice of intent to form a working group
to negotiate enforcement of regional
standards for central air conditioners
and requested nominations from parties
interested in serving as members of the
Regional Standards Enforcement
Working Group. 79 FR 33870. On July
16, 2014, the Department published a
notice of membership announcing the
eighteen nominees that were selected to
serve as members of the Regional
Standards Enforcement Working Group,
in addition to two members from
Appliance Standards and Rulemaking
Federal Advisory Committee (ASRAC),
and one DOE representative. 79 FR
41456. The Regional Standards
Enforcement Working Group identified
a number of issues related to testing and
certification that are being addressed in
this rule. In addition, all
nongovernmental participants of the
Regional Standards Enforcement
Working Group approved the final
report contingent on upon the issuance
of the final guidance on Docket No.
EERE–2014–BT–GUID–0032 0032 and
Docket No. EERE–2014–BT–GUID–0033
consistent with the understanding of the
Regional Standards Enforcement
Working Group as set forth in its
recommendations. (Docket No. EERE–
2011–BT–CE–0077–0070, Attachment)
The amendments in this final rule
supplant the August 19 and 20, 2014
draft guidance documents; DOE will not
finalize the draft guidance documents
and instead has provided any necessary
clarity through this final rule. DOE
believes the amendments are consistent
with the intent of the Regional
Standards Enforcement Working Group.
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
4. Energy Conservation Standards and
Working Group
On November 5, 2014, DOE published
a request for information for energy
conservation standards (ECS) for central
air conditioners and heat pumps
(November 2014 ECS RFI). 79 FR 65603.
In response, several stakeholders
provided comments suggesting that DOE
amend the current test procedure.
On July 14, 2015, DOE published a
notice of intent to establish the central
air conditioners and heat pumps
working group (CAC/HP ECS Working
Group) to negotiate a notice of proposed
rulemaking (NOPR) for energy
conservation standards. 80 FR 40938.
This working group was established
under ASRAC. Ultimately, the CAC/HP
ECS Working Group consisted of 15
members, including one member from
ASRAC and one DOE representative. On
January 19, 2016, the CAC/HP ECS
Working Group successfully reached
consensus on amended energy
conservation standards and the
associated compliance date for certain
product classes of central air
conditioners and central air
conditioning heat pumps, on limited
aspects of the proposed, amended test
procedure appendix M1, and also on a
handful of other miscellaneous issues
related to the standards rulemaking as
well as to this test procedure final rule.
(ASRAC Working Group Term Sheet,
Docket No. EERE–2014–BT–STD–0048,
No. 0076)
asabaliauskas on DSK3SPTVN1PROD with RULES
5. Current Rulemaking
Prior to the conclusion of the CAC/HP
ECS Working Group, on November 9,
2015, DOE published a third
supplemental notice of proposed
rulemaking (November 2015 SNOPR) for
the test procedure of central air
conditioners and heat pumps. 80 FR
69278. The SNOPR responded to
relevant comments from the guidance
documents and rulemaking dockets
discussed in this section.
This final rule addresses certain
comments received in response to the
November 2015 SNOPR. Some of the
provisions of the SNOPR, particularly
related to changes proposed for
appendix M1, will be addressed in a
separate notice. This final rule, along
with the separate final rule addressing
Appendix M1, will fulfill DOE’s
obligation to periodically review its test
procedures under 42 U.S.C.
6293(b)(1)(A).
II. Summary of the Final Rule
This final rule clarifies aspects of
DOE’s test procedure for central air
conditioners and heat pumps to
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
improve the consistency and accuracy
of the results generated when using that
procedure. The rule primarily clarifies
how to test for compliance with the
current energy conservation standards.
The rule also amends certain
certification, compliance, and
enforcement provisions. While the
changes adopted in this rulemaking may
impact test burden in certain cases, as
discussed in section III.H.3, DOE has
determined that this final rule will not
change the measured energy efficiency
of central air conditioners and heat
pumps when compared to the current
test procedure. Any proposed
amendments that would change the
measured energy efficiency will be
addressed as part of the new appendix
M1, in a separate notice, which will be
used in conjunction with amended
standards.
DOE revises the basic model
definition, adds additional definitions
for clarity, makes certain revisions to
the testing requirements for
determination of represented values,
adds certain certification reporting
requirements, revises requirements for
determination of represented values,
and adds product-specific enforcement
provisions.
DOE updates requirements for
Alternative Rating Methods (ARMs)
used to determine performance metrics
for central air conditioners and heat
pumps based on the regulations for
Alternative Efficiency Determination
Methods (AEDMs) that are used to
estimate performance for commercial
HVAC equipment. Specifically, for
central air conditioners and heat pumps,
DOE makes the following amendments:
(1) Revising the nomenclature regarding
ARMs; (2) rescinding DOE’s preapproval of an ARM prior to use; (3)
creating AEDM validation requirements;
(4) revising the AEDM verification
testing process; (5) specifying actions a
manufacturer could take following a
verification test failure; and (6)
clarifying consequences to
manufacturers for invalid represented
values.
DOE revises the test procedure such
that tests of multi-circuit products,
triple-capacity northern heat pump
products, and multi-blower products
can be performed without the need of an
interim waiver or a waiver. Existing
interim waivers and waivers for these
products, as applicable, regarding these
products will terminate 180 days after
publication of this final rule.
DOE also terminates the existing
waivers for air-to-water heat pump
products integrated with domestic water
heating because, as discussed in section
III.C.1, DOE has determined that these
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
36995
waivers are not valid because they do
not provide a method for measurement
of the efficiency metrics used to
determine compliance with applicable
standards.
DOE adopts test methods and
calculations for off mode power that do
not impact the measured energy with
respect to the current energy
conservation standard. Specifically, the
adopted test procedure includes the
following:
(1) Provision of an option to conduct
the off mode tests in a temperaturecontrolled room rather than a
psychrometric room;
(2) Elimination of ambient condition
requirements for units whose off mode
power consumption can be measured
without control of ambient temperature;
(3) Alteration of the off mode
multiplier for modulated compressors;
(4) Addition of requirements on the
heating season off mode power
measurement for units having a
crankcase heater whose controls cycle
or vary crankcase heater power over
time;
(5) Clarification of test sample set-up
and power measurement testing
methodology and components;
(6) Addition of requirement to
eliminate the time delay effect on the off
mode power measurement; and
(7) Elimination of the condition where
P2 is equal to zero in the off mode
power consumption calculation.
In this final rule DOE also improves
the repeatability/reproducibility and
reduces the test burden of the test
procedure. Specifically, DOE amends
the following:
(1) Clarification of fan speed settings;
(2) Clarification of insulation
requirements for refrigerant lines and
addition of a requirement for insulating
mass flow meters;
(3) Addition of a requirement to
demonstrate inlet air temperature
uniformity for the outdoor unit using
thermocouples;
(4) Addition of a requirement that
outdoor air conditions be measured
using sensors measuring the air
captured by the air sampling device(s)
rather than the temperature sensors
located in the air stream approaching
the inlets;
(5) Addition of a requirement that the
air sampling device and the tubing that
transfers the collected air to the dry bulb
temperature sensor be at least two
inches from the test chamber floor, and
a requirement that humidity
measurements be based on dry bulb
temperature measurements made at the
same location as the corresponding wet
bulb temperature measurements used to
determine humidity;
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
36996
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
(6) Clarification of maximum speed
for variable-speed compressors;
(7) Addition of requirements that
improve consistency of refrigerant
charging procedures;
(8) Allowance of an alternative
arrangement for cyclic tests to replace
the currently-required damper in the
inlet portion of the indoor air ductwork
for single-package ducted units;
(9) Clarification of the proper supply
voltage for testing;
(10) Revision of the determination of
the coefficient of cyclic degradation
(CD);
(11) Option for a break-in period of up
to 20 hours;
(12) Update of references to industry
standards where appropriate;
(13) Inclusion of information from the
draft AHRI 210/240;
(14) Addition of provisions regarding
damping of pressure transducer signals
to avoid exceeding test operating
tolerances due to high frequency
fluctuations;
(15) Clarification of inputs for the
demand defrost credit equation; and
(16) Improvement of test consistency
associated with indoor unit air inlet
geometry.
DOE also provides additional detail
and specificity with respect to several
provisions. Specifically, DOE adds
reference to an industry standard for
testing variable refrigerant flow multisplit systems; replaces the informative
guidance table for using the test
procedure; clarifies the definition of
multi-split systems; clarifies the
definition of mini-split systems, which
DOE now calls multi-head mini-split
systems; and clarifies the housing for
uncased coils.
Lastly, DOE addresses comments
received from stakeholders in response
to the November 2015 SNOPR that were
unrelated to any of DOE’s proposals.
Specifically, this includes the following:
(1) Water condensation metric;
(2) Barometric pressure correction ;
and
(3) Inlet screen.
Given the difficulty of writing
amendatory instructions to implement
the many small changes throughout
appendix M, DOE has provided a full reprint of appendix M in the regulatory
text of this final rule.
DOE revises the test procedure in this
final rule as reflected in the revised
Appendix M to Subpart B of 10 CFR
part 430 effective on July 8, 2016. The
amended test procedure is mandatory
for representations of efficiency as of
December 5, 2016.
III. Discussion
This final rule amends the test
procedure for central air conditioners
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
and heat pumps in appendix M to
subpart B of Part 430 and adds new
product-specific certification and
enforcement provisions in 10 CFR
429.12, 429.16, 429.70, and 429.134.
The rule also amends certain definitions
found in 10 CFR 430.2 and updates
certain materials incorporated by
reference in 10 CFR 430.3.
In response to the November 2015
SNOPR, the following 25 interested
parties submitted written comments:
Advanced Distributor Products LLC;
Air-Conditioning, Heating, and
Refrigeration Institute (AHRI); American
Council for an Energy Efficient
Economy (ACEEE); Appliance
Standards Awareness Project (ASAP);
First Co.; Goodman Global, Inc.;
Heating, Air Conditioning &
Refrigeration Distributors International
(HARDI); Ingersoll Rand; Johnson
Controls Inc. (JCI); Lennox International
Inc; LG Electronics U.S.A., Inc;
Mitsubishi Electric Cooling & Heating;
Natural Resources Defense Council
(NRDC); Nortek Global HVAC;
Northwest Energy Efficiency Alliance
(NEEA); Northwest Power and
Conservation Council (NPCC); Pacific
Gas and Electric Company (PG&E);
Rheem Manufacturing Company
(Rheem); San Diego Gas and Electric
Company (SDG&E); Southern California
Edison (SCE); Southern California Gas
Company (SCG); Unico, Inc.; United
Refrigeration, Inc. (URI); United
Technologies Climate, Controls &
Security (UTC), also known as Carrier
Corporation. NEEA and NPCC
submitted a joint comment. PG&E,
SDG&E, SCG, and SCE, hereafter
referred to as the California InvestorOwned Utilities (California IOUs), also
submitted a joint comment. ACEEE,
ASAP, and NRDC, hereafter referred to
as the Efficiency Advocates, also
submitted a joint comment.
Interested parties provided comments
on a range of issues, including those
DOE identified in the November 2015
SNOPR, as well as several other
pertinent issues related to DOE’s
proposal. Commenters also offered
thoughts on further opportunities to
improve the clarity of the test
procedure. These issues, as well as
DOE’s responses to them and the
resulting changes to DOE’s proposal, are
discussed in the subsequent sections. A
parenthetical reference at the end of a
comment quotation or paraphrase
provides the location of the item in the
public record.5
5 The
parenthetical reference provides a reference
for information located in the docket of DOE’s
rulemaking to amend the test procedures for central
air conditioners and heat pumps. (Docket No.
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
A. Definitions, Testing, Represented
Values, and Compliance of Basic
Models of Central Air Conditioners and
Heat Pumps
On August 19 and 20, 2014, DOE
issued two draft guidance documents
regarding the test procedure for central
air conditioners and heat pumps. One
guidance document dealt with testing
and rating split systems with blower
coil indoor units (Docket No. EERE–
2014–BT–GUID–0033); and the other
dealt more generally with selecting
units for testing, rating, and certifying
split-system combinations, including
discussion of basic models and of
condensing units and evaporator coils
sold separately for replacement
installation (Docket No. EERE–2014–
BT–GUID–0032). The comments in
response to these draft guidance
documents were discussed in the
November 2015 SNOPR. DOE proposed
changes to the substance of the draft
guidance that reflects the comments
received as well as the
recommendations of the Regional
Standards Enforcement Working Group
(Docket No. EERE–2011–BT–CE–0077–
0070, Attachment). DOE makes
additional modifications in this final
rule in response to comment on the
November 2015 SNOPR as well as the
recommendations of the CAC/HP ECS
Working Group (Docket No. Docket No.
EERE–2014–BT–STD–0048, No. 76).
The adopted changes supplant the two
draft guidance documents; DOE will not
finalize the draft guidance documents
and has instead provided any necessary
clarity through this final rule.
1. Basic Model Definition
In the November 2015 SNOPR, DOE
proposed modifying its basic model
definition for central air conditioners
and heat pumps. 80 FR at 69282–4 (Nov.
9, 2015). Under DOE’s proposal,
manufacturers could consider each
individual model/combination its own
basic model, or manufacturers could
assign all individual models of the same
single-package system or all individual
combinations using the same model of
outdoor unit (for outdoor unit
manufacturers (OUM)) or model of
indoor unit (for independent coil
manufacturers (ICM)) to the same basic
model. DOE proposed to further define
(for both single-package units and split
systems) the physical characteristics
necessary to assign individual models or
EERE–2009–BT–TP–0004, which is maintained at
https://www.regulations.gov/#!docketDetail;D=EERE2009-BT-TP-0004). The references are arranged as
follows: (commenter name, comment docket ID
number, page of that document).
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
combinations to the same basic model.
80 FR 69278, 69282–83 (Nov. 9, 2015).
DOE proposed that, if a manufacturer
chooses to assign each individual model
or combination to its own basic model,
the manufacturer must test each
individual model/combination—and
that an AEDM could not be applied. 80
FR 69278, 69283 (Nov. 9, 2015). If
manufacturers assign all individual
combinations of a model of outdoor unit
(for OUMs) or model of indoor unit (for
ICMs) to a single basic model, DOE
further proposed that each individual
combination within a basic model must
be certified with a rating determined for
that individual combination. However,
only one individual combination in
each basic model would have to be
tested (see section III.A.3.a), while the
others may be rated using an AEDM.
This option reduces testing burden but
increases risk. Specifically, if any one of
the combinations within a basic model
fails to meet the applicable standard,
then all of the combinations within the
basic model fail, and the entire basic
model must be taken off the market. 80
FR 69278 at 69283 (Nov. 9, 2015).
Comments on these proposals are
discussed in the following sections.
a. Basic Model Framework
The Joint Advocates of ACEEE, NRDC
and ASAP (‘‘Joint Advocates’’)
supported the proposed changes to the
definition of a basic model and related
testing and certification requirements.
The Joint Advocates stated that they
believe that the clarified testing
requirements would reduce testing
burden on manufacturers. (ACEEE,
NRDC and ASAP, No. 72 at p. 1) Nortek
supported DOE’s proposal that
manufacturers would have a choice in
how to assign individual models or
combinations to basic models. (Nortek,
No. 58 at p. 3) ADP and Lennox
supported the use of the basic model as
the basis for any enforcement action as
discussed in Section III.A.8 (80 FR
69278, 69297 (Nov. 9, 2015)) and the
proposed 10 CFR 429. (ADP, No. 59 at
p. 7; Lennox, No. 61 at p. 14)
NEEA and NPCC commented that
DOE’s proposed approach that all
combinations within the basic model
are deemed noncompliant if only one of
the combinations within a basic model
fails does not align with the other
aspects of DOE’s current proposal, in
which each and every combination has
its own certified rating. (NEEA and
NPCC, No. 64 at p. 2–3)
Carrier/UTC expressed the concern
that if one combination amongst
potentially hundreds of combinations
rated with a given outdoor unit fails
then the entire basic model will be
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
removed from the market and claimed
that it is excessively punitive. Further,
Carrier/UTC recommended a provision
for saving the remaining indoor
combinations of the basic model such as
testing the tested combination and one
(or more) other random indoor
combinations. Carrier/UTC stated that
the de-listing of the product should be
limited to the combination that failed,
not the entire basic model. (Carrier/
UTC, No. 62 at pp. 5–6)
NEEA and NPCC further commented
that they presume that DOE’s ratings
guidance of August 19 and 20, 2014,
would also be impacted by a
requirement to rate all outdoor and
indoor unit combinations and the
proposal with regard to testing-derived
versus AEDM-derived ratings. They
asserted that the proposal would seem
to require the rating of both coil-only
and blower coil combinations, with the
choice of either using the highest sales
volume combination being tested (and
all other combinations rated using an
AEDM), or testing each combination as
its own basic model. (NEEA and NPCC,
No. 64 at p. 2–3)
In response to NEEA and NPCC, DOE
disagrees that DOE cannot make a
determination of compliance on a basic
model basis simply because DOE
permits the manufacturer to make
different representations for
combinations within a basic model. In
response to NEAA, NPCC, and UTC/
Carrier, DOE notes that it developed the
proposal for the basic model framework
in an effort to balance manufacturer test
burden and risk. The determination of
compliance with the standard is made at
the basic model level, and the
manufacturer may choose how to group
models into basic models and whether
or not to make use of an AEDM for
represented values of combinations.
DOE expects that the individual
combinations grouped into a single
basic model would have similarities that
would make validation of one of the
individual model/combination’s
represented values a strong indication of
the accuracy of the represented values
of the other models/combinations—if
the represented values are indeed
different. DOE also notes that when
manufacturers use an AEDM and DOE
finds an invalid rating, manufacturers
can conduct re-testing to re-certify the
individual model/combination, as
described in section 429.70.
DOE also notes that, as stated in the
November 2015 SNOPR, this final rule
will supplant DOE’s draft ratings
guidance documents, which will not be
finalized. Finally, DOE notes in
response to NEEA and NPCC that the
basic model framework itself does not
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
36997
determine whether both coil-only and
blower coil combinations must be rated;
this is further discussed in section
III.A.3.a. Given the support for the basic
model framework voiced by many of the
commenters, DOE adopts the framework
as proposed in the SNOPR.
b. General Definition Comments
AHRI and several manufacturers
including UTC/Carrier, ADP, Lennox,
Nortek, and Unico agreed generally with
DOE’s proposal to modify its basic
model definition. (AHRI, No. 70 at p. 3;
UTC/Carrier, No. 62 at p. 5–6; ADP, No.
59 at p. 7; Lennox, No. 61 at p. 14;
Nortek, No. 58 at p. 3; Unico, No. 63 at
p. 4) Rheem recommended that DOE
adopt the industry standard definition
for basic model, as defined by AHRI.
(Rheem, No. 69 at p. 4) As described
below, several commenters requested
additional modifications to DOE’s
proposed definitions; these comments
are discussed below, along with
revisions to the proposed definitions.
c. Split Systems Manufactured by OUMs
and Single-Package Systems
For split systems manufactured by
OUMs and single-package systems,
AHRI, Lennox, Ingersoll Rand, Rheem,
and Nortek recommended the removal
of ‘‘the auxiliary refrigeration system
components if present (e.g., expansion
valve) and controls’’ from the proposed
basic model definition. Lennox and
Nortek commented that adding these
components to the definition can greatly
expand the number of basic models.
(AHRI, No. 70 at p. 3; Lennox, No. 61
at p. 4; Ingersoll Rand, No. 65 at p. 11;
Rheem, No. 69 at p. 4; Nortek, No. 58
at p. 3) Additionally, Lennox and
Nortek suggested that there would not
be a benefit to expanding the definition
of basic model beyond the currently
accepted industry practice as outlined
in AHRI’s certification program.
(Lennox, No. 61 at p. 4; Nortek, No. 58
at p. 3) DOE understands Lennox and
Nortek are referring to the concept of a
‘‘basic model group’’ as the term is
described in the AHRI Operations
Manual for Unitary Small AirConditioners and Air-Source Heat
Pumps, in section 1.5, ‘‘Basic Model
Groups (BMGs).’’
After reviewing the comments, DOE
acknowledges that while use of different
auxiliary refrigeration system
components may impact measured
performance, it may not do so
significantly—for example,
measurements made using two different
thermostatic expansion valves that both
maintain the same superheat should not
be different. In an effort to balance
manufacturer test burden with the
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
36998
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
regulatory needs of the program to
establish an appropriate basic model
definition, DOE has not included the
phrase ‘‘auxiliary refrigeration system
components if present (e.g., suction
accumulator, reversing valve, expansion
valve) and controls’’ in the ‘‘basic
model’’ definition for split systems
manufactured by OUMs or for singlepackage systems. DOE notes, however,
that each manufacturer is responsible
for minor variations in efficiency
differences resulting from such changes
in design.
For the definition of a basic model for
OUMs, Goodman agreed with DOE’s
overall direction. However, Goodman
commented that DOE’s proposed
definition was too rigid and would not
provide enough design flexibility to
manufacturers. Specifically, Goodman
cited the importance of the ability for a
manufacturer to vary many aspects of its
outdoor coils (e.g., style and fin depth)
and to source components, such as
compressors, from multiple component
manufacturers. Goodman asserted that
this flexibility in design would allow
manufacturers to provide combinations
that optimize their product offering to
consumers, while still yielding similar
performance and therefore meriting
classification under a single basic
model. Goodman suggested revised
basic model definitions for split systems
manufactured by OUMs and singlepackage systems in which the list of
parameters affecting performance (e.g.,
compressor and outdoor coil properties)
that had been proposed to define a
distinct model be instead provided as
guidance for the OUM to consider when
deciding whether two variations of a
design should have the same model
number. (Goodman, No. 73 at pp. 2–3)
In response to Goodman, DOE
recognizes the importance of allowing
manufacturers flexibility in design. DOE
agrees with Goodman that, for instance,
using compressors from different
compressor manufacturers in two
different models should not require the
manufacturer to classify these models as
two separate basic models, if the models
can still reasonably be described as
having ‘‘essentially identical
characteristics.’’ However, DOE believes
that Goodman’s suggested revised
definitions, by providing guidance but
no requirements, would allow widely
varying characteristics under the same
model of outdoor unit or single-package
unit. Rather than moving to definitions
that provide flexibility limited only by
guidance, DOE has instead modified the
definitions to allow some design
flexibility, while assuring that a large
departure from a given design would
require that the OUM establish a new
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
basic model. In the definitions
established in this final rule for basic
model for split systems manufactured
by OUMs and single-package systems,
DOE has removed certain requirements
proposed in the November 2015
SNOPR, and added tolerances for the
remaining requirements. Specifically,
these modifications from the proposal
include: (1) Establishing a five percent
tolerance for compressor displacement,
capacity, and power input; (2) removing
requirements for several outdoor coil
parameters; (3) adding a five percent
tolerance to the face area and total fin
surface area of the outdoor coil; (4)
adding a ten percent tolerance on
outdoor airflow, and (5) for singlepackage systems, allowing a ten percent
tolerance on indoor airflow and a
twenty percent tolerance on power
input to the indoor fan motor.
In the basic model definition
proposed in the November 2015 SNOPR
for split systems manufactured by
OUMs and single-package systems, DOE
specified that all individual models or
combinations in a basic model must
have the same or comparably
performing compressor(s) with the
‘‘same displacement rate (volume per
time) and same capacity and power
input when tested under the same
operating conditions.’’ 80 FR 69278,
69341 (Nov. 9, 2015). In order to
promote design flexibility, DOE is
adopting less stringent requirements in
the basic model definition amended in
this final rule by adding a five percent
tolerance to the displacement rate and
capacity and power input. DOE’s
research suggests that comparable
compressors made by different
manufacturers vary by less than two
percent in displacement rate and
capacity and power input when tested
under the same conditions. Therefore,
DOE believes that a five percent
tolerance allows manufacturers the
option to use comparably performing
compressors from different
manufacturers in models without
having to classify the models as separate
basic models. Additionally, in the
definition established in this final rule,
DOE explains that the tolerances on
compressor parameters refer to the
values rated by the compressor
manufacturer, not the performance of
individual compressors.
In this final rule, DOE is adopting less
stringent requirements for classifying as
comparably performing outdoor coil(s)
in the basic model definition for split
systems manufactured by OUMs and
single-package systems. To provide
more flexibility to manufacturers, DOE
is not adopting specifications in the
basic model definitions for: Coil depth,
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
fin style (e.g., wavy, louvered), fin
density (fins per inch), tube pattern,
tube diameter, tube wall thickness, and
tube internal enhancement. However,
DOE has added a five percent tolerance
to the face area and total fin surface area
for outdoor coils. This tolerance on the
outdoor coil areas will allow
manufacturers to vary their designs
while achieving similar performance,
such as adding another row
perpendicular to the airflow direction to
the outdoor coil to compensate for using
a more energy-consuming compressor.
Additionally, DOE is adding
tolerances to the requirements for
classifying as comparably performing
outdoor fan(s) in the basic model
definition for split systems
manufactured by OUMs and singlepackage systems. DOE is adding a ten
percent tolerance on outdoor fan
airflow. DOE believes that this tolerance
will allow manufacturers to make
adjustments to the fans, such as
increasing the number, diameter, or
design of fan blades, without classifying
comparably performing models as
separate basic models.
UTC/Carrier agreed with DOE’s
proposal to align the basic model
definition with that used by AHRI;
however, they asserted that the list of
additional reporting requirements is
excessive and burdensome. Specifically,
UTC/Carrier stated that some of these
components do not affect the
performance of the system, are
considered proprietary, and need not be
reported. Additionally, they stated that
some of these minor components may
change due to sourcing availability.
UTC/Carrier recommended that DOE
align the basic model exactly with
AHRI’s basic model group definition:
Compressor model, outdoor coil face
area, and outdoor airflow, and not
require any additional data to be
reported. (UTC/Carrier, No. 62 at p. 2)
For split systems manufactured by
OUMs, Lennox recommended that the
proposed OUM basic model definition
be revised to more closely align with
industry practices and recommended
that the definition of outdoor coil be
revised to protect business sensitive
information. (Lennox, No. 61 at p. 4)
Specifically, Lennox requested that the
definition of outdoor coil-only include
the words ‘‘same face area and depth,
style.’’ Lennox suggested that DOE
remove the remaining specification
requirements for outdoor coils so that
this sensitive business information
could not be made available to the
public and industry competitors
through a FOIA request. (Lennox, No. 61
at pp. 3–4)
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
DOE acknowledges the importance of
avoiding disclosure of proprietary or
sensitive business information;
however, in the November 2015 SNOPR
DOE did not propose any additional
certification requirements or
supplemental test instruction reporting
that would require disclosure of these
parameters about which UTC/Carrier
and Lennox cited concern. 80 FR 69278,
69338–39 (Nov. 9, 2015). Requirements
for reporting are limited to those items
listed in section 429.16(e), and mention
of a parameter as the basis for
distinguishing a model does not by itself
imply that the value of that parameter
must be reported in certification reports.
DOE notes that it is not requiring that
manufacturers report the sensitive
information such as surface area or coil
depth for which their basic model
determinations are made.
In response to UTC/Carrier, DOE
recognizes that minor components may
vary in manufacturer designs based on
availability from component
manufacturers. However, DOE believes
that the tolerances established in this
final rule (as previously discussed)
around most of the requirements in
DOE’s definition of basic model allow
for variation in component models and
manufacturers. DOE also believes that
the requirements included in DOE’s
definition of basic model are necessary
to ensure units are similar enough to be
classified as the same basic model. DOE
also notes that the definition established
in this final rule includes tolerances on
the compressor model ratings, outdoor
coil face area, and outdoor airflow;
therefore DOE’s definition allows more
flexibility for outdoor coil face area and
outdoor airflow than does the definition
of a split-system model group in the
AHRI Operations Manual.6
In response to Lennox, as previously
discussed, DOE has removed references
to fin material, style, or density or tube
thickness in the basic model definition
established in this final rule, which will
provide manufacturers with more
flexibility in offering a varied product
offering to consumers while limiting the
testing burden.
d. Requirements for Independent Coil
Manufacturers
Several commenters expressed
concern about the impact of the
proposed definition of basic model on
ICM test burden. Therefore comments
6 AHRI’s Operations Manual for Unitary Small
Air-Conditioners and Air-Source Heat Pumps
(Includes Mixed-Match Coils) (Rated Below 65,000
Btu/h) Certification Program (AHRI OM 210/240—
March 2015). Available at www.ahrinet.org/App_
Content/ahri/files/Certification/OM%20pdfs/USE_
OM.pdf (Last accessed March 31, 2016.)
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
regarding the ICM basic model
definition are addressed in the context
of testing required to determine
represented values in section III.A.3.d.
e. Off-Mode
Revisions to the test procedure as
stated in section III.D of this final rule
enable the determination of off mode
power consumption, which reflects the
operation of the contributing
components: crankcase heater and lowvoltage controls. In the November 2015
SNOPR, DOE proposed that if
individual combinations that are
otherwise identical are offered with
multiple options for off mode related
components, manufacturers at a
minimum must rate the individual
combination with the crankcase heater
and controls which are the most
consumptive. Under this proposal, if a
manufacturer wished to also make
representations for less consumptive off
mode options for the same individual
combination, the manufacturer could
provide separate ratings as long as the
manufacturer differentiated the
individual model numbers for these
ratings. These individual combinations
would be within the same basic model.
80 FR 69278, 69284 (Nov. 9, 2015).
In their comments, NEEA and NPCC
strongly supported DOE’s proposal to
require manufacturers to either rate and
certify all combinations using the most
consumptive off-mode power controls
and systems, or to differentiate models
they wish to certify with different offmode power controls and/or systems
with different model numbers, each
with its own certified rating. (NEEA and
NPCC, No. 64 at p. 4)
DOE received no other comments on
this proposal and adopts it in this final
rule.
f. Central Air Conditioner Definition
In the November 2015 SNOPR, DOE
proposed to clarify that a central air
conditioner or central air conditioning
heat pump may consist of: A singlepackage unit; an outdoor unit and one
or more indoor units (e.g., a single-split
or multi-split system); an indoor unit
only (rated as a combination by an ICM
with an OUM’s outdoor unit); or an
outdoor unit only (with no match, rated
by an OUM with the coil specified in
this test procedure). DOE proposed
adding these specifications to the
definition of central air conditioner or
central air conditioning heat pump in 10
CFR 430.2. In the certification reports
submitted by OUMs for split systems,
DOE proposed that manufacturers must
report the basic model number as well
as the individual model numbers of the
indoor unit(s) and the air mover where
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
36999
applicable. 80 FR 69278, 69284 (Nov. 9,
2015).
Lennox and ADP expressed concern
that modifying the CAC/HP definition to
include ‘‘an indoor unit’’ only may have
significant unintended consequences
with additional regulation now applying
to indoor units. They stated that the
indoor unit has no heating or cooling
capability without being installed as a
part of the system, that by itself, it is a
component, and that the proposed
definition is factually incorrect and
contradicts the DOE’s previous position
that they do not have authority to
regulate components of air conditioners.
Lennox recommended DOE keep the
existing definition. (Lennox, No. 61 at p.
10; ADP, No. 59 at p. 4)
DOE notes that the modification of the
CAC/HP definition does not change the
scope of DOE’s product coverage and is
in line with the current certification
requirements for CAC/HP. Specifically,
ICMs are currently responsible for
testing and certifying models of indoor
units they manufacture as part of a splitsystem combination. DOE received no
other comment on this topic. For these
reasons, DOE is adopting the CAC/HP
definition as proposed.
2. Additional Definitions
In the November 2015 SNOPR, in
order to specify differences in the
proposed basic model definition for
ICMs and OUMs, DOE proposed
definitions for an ICM and an OUM.
With respect to any given basic model,
a manufacturer could be an ICM or an
OUM. 80 FR 69278, 69284 (Nov. 9,
2015).
DOE also proposed to define variable
refrigerant flow (VRF) systems that are
single-phase and less than 65,000 Btu/
h as a kind of multi-split central air
conditioner and central air conditioning
heat pump system. Id.
Additionally, DOE proposed to clarify
several other definitions currently in 10
CFR 430.2 with minor wording changes
and move them to 10 CFR 430, Subpart
B, Appendix M. DOE also proposed to
remove entirely the definitions for
‘‘condenser-evaporator coil
combination’’ and ‘‘coil family,’’ as
those terms no longer appear in the
proposed regulations. Id.
DOE did not receive any comments on
these definitions and related changes
and adopts the proposals in this final
rule.
a. Indoor Unit
In the November 2015 SNOPR, DOE
proposed modifying the definition of
indoor unit to read as follows: ‘‘indoor
unit transfers heat between the
refrigerant and the indoor air, and
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37000
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
consists of an indoor coil and casing
and may include a cooling mode
expansion device and/or an air moving
device.’’ 80 FR 69278, 69284 (Nov. 9,
2015).
Goodman commented that the
definition for indoor unit does not fully
account for the range of indoor units
sold in the market. Specifically,
Goodman stated that including the
casing in the proposed indoor unit
definition is inconsistent with many
industry offerings. Goodman also
suggested a new definition for indoor
unit. (Goodman, No. 73 at p. 3–5)
AHRI and Nortek proposed a
definition for indoor units that does not
include casing and/or an expansion
device. AHRI and Nortek expressed
concern that the uncased coil would no
longer be within the scope of regulation,
which could open the doors for a
loophole in the regulation, or that
manufacturers would not be able to list
an uncased coil with an outdoor unit,
resulting in an illegal installation. AHRI
and Nortek proposed definitions for
uncased coil, cased coil, and service
coil. (AHRI, No. 70 at p. 8; Nortek, No.
58 at p. 3–4). Further, AHRI stated that
DOE should make clear that service
coils will not be rated in the future.
(AHRI, No. 70 at p. 8)
UTC/Carrier commented that the
exclusion of uncased coils from DOE
certification represents a significant
loophole as uncased coils are often
installed in various new construction
scenarios and should be certified.
According to UTC/Carrier, DOE should
further define the replacement
component service coils that are used
only when the current coils fail and are
considered service parts and, thus,
should not be certified to DOE; the
treatment of uncased coils in commerce
by manufacturers as service-only is
problematic. (UTC/Carrier, No. 62 at p.
3)
JCI commented that, while some
manufacturers use uncased service
coils, others supply service coils with
casings on them. In addition, JCI
commented that not all uncased coils
are service coils. According to JCI, there
are product families of uncased coils
very often sold for new construction
installations, or installation of new A/C
systems in the northern parts of the
United States. For example, JCI noted
that often in the northern United States,
a new home may be constructed with
only a furnace for heating and no
cooling, and that cooling may be added
later by installing an uncased coil into
the ductwork itself. JCI commented that
the uncased coil market is a vital part
of the northern U.S. market, and
uncased coils need to be allowed to be
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
rated as valid matches with a basic
outdoor model. (JCI, No. 66 at p. 12–13).
JCI also suggested definitions for
uncased coil, cased coil, service coil,
and indoor unit. (JCI, No. 66 at p. 13)
The California IOUs requested that
DOE allow manufacturers to rate
uncased coils with outdoor condensing
units. They reported that California
Building Energy Efficiency Standards
(Title 24) define the replacement of any
component containing refrigerant to be
a system alteration requiring verification
of refrigerant charge and airflow through
the coil. (see California Code of
Regulations, Title 24, Part 1, Article 1,
Section 150.2(b)(1)F) The California
IOUs stated that the replacement of an
indoor coil is an alteration whether the
coil is cased or uncased. DOE asserted
that DOE’s proposal to define uncased
coils as repair parts and to not require
them to be part of a rated model would
create a compliance problem for
contractors in California because
without ratings, the energy efficiency of
the system with an uncased coil is not
known. The California IOUs stated that
in applications where the existing coil
is removed from the existing case and
replaced with a new coil, which is then
connected to a new outdoor unit, the
efficiency rating is required to meet
Title 24. Therefore, the California IOUs
requested that DOE allow ratings of
combinations having uncased indoor
coils so that compliance with Title 24
can be verified. (California IOUs, No. 67
at p. 2)
ADP and Lennox commented that
they understand the intent of excluding
uncased coils is to differentiate between
indoor units used for legacy
replacements and new installations, but
believe that DOE’s proposal would
create a significant loophole. ADP and
Lennox commented that uncased coils
are used for new installations in a
significant number of markets in the
upper Midwest of the United States
where a long tradition of skilled sheet
metal workers exists. Additionally, they
asserted that Canada is a predominately
uncased coil market and relies on
manufacturer ratings that have been
certified with DOE and AHRI. Instead,
ADP suggests that DOE require
replacement coils not subject to
certification to carry a different model
number than those sold for installation
as a part of new, certified systems.
(ADP, No. 59 at p. 4–5; Lennox, No. 61
at p. 10)
After consideration of the comments
that uncased coils may be used for new
installations and that the exclusion of
uncased coils from the indoor unit
definition could result in a significant
loophole, DOE is adopting a revised
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
definition for an indoor unit such that
it ‘‘may or may not include . . . (e)
external cabinetry’’. To distinguish
newly installed cased and uncased coils
from replacement cased and uncased
coils, DOE has added a definition for
service coils and explicitly excluded
them in the indoor unit definition.
Indoor unit means part of a splitsystem air conditioner or heat pump
that includes (a) an arrangement of
refrigerant-to-air heat transfer coil(s) for
transfer of heat between the refrigerant
and the indoor air and (b) a condensate
drain pan, and may or may not include
(c) sheet metal or plastic parts not part
of external cabinetry to direct/route
airflow over the coil(s), (d) a cooling
mode expansion device, (e) external
cabinetry, and (f) an integrated indoor
blower (i.e. a device to move air
including its associated motor). A
separate designated air mover that may
be a furnace or a modular blower (as
defined in Appendix AA to the subpart)
may be considered to be part of the
indoor unit. A service coil is not an
indoor unit.
Service coil means an arrangement of
refrigerant-to-air heat transfer coil(s) and
condensate drain pan that may or may
not include sheet metal or plastic parts
to direct/route airflow over the coil(s),
external cabinetry, and/or a cooling
mode expansion device, and is sold
exclusively to replace an uncased coil or
cased coil that has already been placed
into service and is labeled accordingly.
DOE also acknowledges the benefit of
including definitions for both cased and
uncased coils, and adopts the following
definitions:
Cased coil means a coil-only indoor
unit with external cabinetry.
Uncased coil means a coil-only indoor
unit without external cabinetry.
In the November 2015 SNOPR, DOE
proposed to specify that if the indoor
unit does not ship with a cooling mode
expansion device, the system should be
tested using the device as specified in
the installation instructions provided
with the indoor unit, or if no device is
specified, using a thermostatic
expansion valve (TXV). 80 FR 69278,
69284 (Nov. 9, 2015).
Goodman commented that DOE
should not assume the use of TXV if a
metering (expansion) device is not
specified by the manufacturer.
Goodman commented that the majority
of systems installed today use fixed
orifice rather than TXV expansion
devices. (Goodman, No. 73 at p. 3–5)
DOE agrees that many product
offerings use fixed orifice or piston
expansion devices as standard
equipment and that it may be more
suitable to use a fixed orifice or piston
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
device if there are no detailed
instructions provided in installation
instructions regarding selection of an
expansion device. This is because a
system installed in the field without
such instructions may very well perform
poorly if an optimized device is not
selected. Because a TXV generally is
likely to provide better performance
over a range of operating conditions,
DOE believes the use of a fixed orifice
is more consistent with this potential for
poor field performance. Therefore, DOE
is modifying its proposal and requiring
instead that a fixed orifice or piston
expansion device be used if the
installation instructions do not specify a
metering (expansion) device.
b. Blower Coil and Coil-Only Indoor
Units
In the November 2015 SNOPR, DOE
proposed definitions for blower coil
indoor unit and coil-only indoor unit.
The motivation was to simplify the
description of the test requirements by
referring to blower coil units instead of
units ‘‘with an indoor fan installed’’ and
to coil-only units instead of units
‘‘without an indoor fan installed’’.
Blower coil indoor unit means the
indoor unit of a split-system central air
conditioner or heat pump that includes
a refrigerant-to-air heat exchanger coil,
may include a cooling-mode expansion
device, and includes either an indoor
blower housed with the coil or a
separate designated air mover such as a
furnace or a modular blower (as defined
in Appendix AA).
Blower coil system refers to a split
system that includes one or more blower
coil indoor units.
Coil-only indoor unit means the
indoor unit of a split-system central air
conditioner or heat pump that includes
a refrigerant-to-air heat exchanger coil
and may include a cooling-mode
expansion device, but does not include
an indoor blower housed with the coil,
and does not include a separate
designated air mover such as a furnace
or a modular blower (as defined in
Appendix AA). A coil-only indoor unit
is designed to use a separately-installed
furnace or a modular blower for indoor
air movement.
Coil-only system refers to a system
that includes one or more coil-only
indoor units. 80 FR 69278, 69286 (Nov.
9, 2015).
ADP and UTC/Carrier agreed with the
proposed definitions for blower coil and
coil-only indoor units. (ADP, No. 59 at
p. 6; UTC/Carrier, No. 62 at p. 3) Lennox
agreed with the proposed definitions
with the exceptions noted in other
sections. (Lennox, No. 61 at p. 13) Unico
agreed with the coil-only indoor
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
definition, except recommended
removing the word ‘‘modular’’ as there
is no definition. Unico commented that
the blower can be anywhere in the
system. (Unico, No. 63 at p. 2) JCI
suggested definitions for air handler,
blower coil, and coil-only. (JCI, No. 66
at p. 13)
Rheem commented that the proposed
definitions for blower coil and coil-only
indoor units exclude the customary
practice in the Northwest United States
where an uncased coil is installed in a
plenum for space-constrained
installations. Rheem stated that under
DOE’s proposal, a certified rating for
this system configuration would no
longer be available to consumers.
Rheem noted that there are building
inspectors who require an AHRI or DOE
certified combination including the
evaporator coil for replacements.
(Rheem, No. 69 at p. 5)
DOE acknowledges that by excluding
indoor units without a casing, the
customary practice identified by Rheem
would not be included. As noted in the
previous section, DOE has addressed
this by expanding the indoor unit
definition to include units which may
or may not have external cabinetry. The
blower coil and coil-only indoor unit
definitions then build on this updated
indoor unit definition. Further, DOE has
removed, from both the blower coil and
coil-only indoor unit definitions,
language redundant with the indoor
unit definition and is adopting amended
definitions:
In response to Unico’s comment
regarding ‘‘modular’’, the definition
explicitly refers to the definition of
‘‘modular blower’’ in appendix AA. In
response to JCI’s comment requesting a
definition for ‘‘air handler’’, DOE feels
that this is not necessary because there
are few distinctions in the test
procedure between test requirements for
blower coil indoor units that are air
handlers (as defined by JCI) and blower
coil indoor units that are not. In cases
where a distinction is needed, the
regulatory language adequately provides
the distinction, for example in section
3.13.1.d, ‘‘blower coil split systems for
which a furnace or a modular blower is
the dedicated air mover . . .’’, which
refers to blower coil split systems whose
indoor units are not ‘‘air handlers’’.
3. Determination of Represented Values
In the November 2015 SNOPR, DOE
proposed several regulatory changes
regarding the relationship between
represented values and an effective
enforcement plan. The changes are
described in the following sections.
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
37001
a. Single-Split-System Air Conditioners
Rated by OUMs
DOE proposed to make changes to 10
CFR 429.16 to revise the testing and
rating requirements for single-split
system air conditioners. These changes
were proposed to occur in two phases.
In the first phase, prior to the
compliance date of any amended energy
conservation standards, DOE proposed
only a slight change to the current
requirements. Specifically, DOE
proposed that for single-split system air
conditioners with single speed
condensing units, each model of
outdoor unit must be tested with the
model of coil-only indoor unit that is
likely to have the largest volume of
retail sales with the particular model of
outdoor unit. For split-system air
conditioners with other than single
speed condensing units, each model of
outdoor unit must also be tested with
the model of coil-only indoor unit likely
to have the largest sales volume unless
the model of outdoor unit is sold only
with model(s) of blower coil indoor
units, in which case it must be tested
and rated with the model of blower coil
indoor unit likely to have the highest
sales volume. However, any other
combination may be rated through
testing or use of an AEDM. Therefore,
both single speed and other than single
speed systems may be rated with
models of both coil-only or blower coil
indoor units, but if the system is sold
with a model of coil-only indoor unit,
it must, at a minimum, be tested in that
combination. 80 FR 69278, 69285–86
(Nov. 9, 2015).
In the second phase, DOE anticipated
that any amended energy conservation
standards would be based on blower
coil ratings. Therefore, DOE proposed
that all single-split-system air
conditioner basic models be tested and
rated with the model of blower coil
indoor unit likely to have the largest
volume of retail sales with that model
of outdoor unit. Manufacturers would
be required to also rate all other blower
coil and coil-only combinations within
the basic model but would be permitted
do so through testing or an AEDM. This
proposed change would also be
accounted for in the parallel energy
conservation standards rulemaking, and
would be contingent upon any proposed
amended standards being based on
blower coil ratings. Id.
DOE noted that these proposed testing
requirements, when combined with the
proposed definition for basic model,
require that each basic model have at
least one rating determined through
testing; no basic model can be rated
solely using an AEDM. Id.
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37002
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
DOE also proposed that in the
certification report, manufacturers state
whether each rating is for a coil-only or
blower coil combination. 80 FR 69278,
69286 (Nov. 9, 2015).
Following publication of the
November 2015 SNOPR, DOE held
meetings of the CAC/HP ECS Working
Group. The CAC/HP ECS Working
Group recommended consensus energy
conservation standards based on coilonly ratings rather than blower coil
ratings, making the second phase of
DOE’s proposal no longer applicable.
Many of the stakeholders who
submitted comments on DOE’s proposal
were also members of the CAC/HP ECS
Working Group, and as a result, their
positions may have changed over the
course of the negotiations. For these
reasons, DOE has included the
consensus recommendations of the
CAC/HP ECS Working Group that
pertain to DOE’s proposal but has not
included the comments of members of
the CAC/HP ECS Working Group on the
November 2015 SNOPR where the scope
of the Working Group recommendation
encompassed the scope of the comment.
With respect to the coil-only and
blower coil requirements, ADP agreed
with the proposed requirements of the
first phase approach. (ADP, No. 59 at p.
5–6;)
JCI agreed with the single speed
requirements in Appendix M but did
not agree with DOE’s proposed
requirement for two-stage units or
multi-stage units to be tested with a
coil-only indoor unit, if any coil-only
indoor units are listed with that outdoor
unit. JCI recommended that there
should be no change in the current
regulatory text for two-stage or
modulating equipment, and asserted
that the spirit of the current regulation
is met with blower coils remaining as
the highest sales volume tested
combination, even if there are limited
loose coil or coil-only ratings available.
(JCI, No. 66 at p. 5)
ADP had concerns that testing the
highest sales volume combination
(HSVC) with a blower coil in the second
phase (in appendix M1) would make it
more difficult for ICMs to accurately
rate their products because of the added
uncertainty of the indoor blower watts
and airflow performance. Under the
proposed second phase, with a blower
coil indoor unit as HSVC, the indoor
blower watt value is unknown by the
ICM, forcing the ICM to estimate the
watts, which introduces additional
uncertainty to ICM ratings. Although
ADP and Lennox recognized that ICMs
could test the HSVC blower coil, they
considered this to be an unreasonable
testing burden on ICMs. (ADP, No. 59 at
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
p. 5–6) ADP proposed that DOE require
the reporting of indoor watt data, indoor
air volume rates, and indoor air mover
settings and require that they be made
publicly available. (ADP, No. 59 at p. 5–
6) Unico stated that it preferred that the
HSVC be a coil-only indoor unit so that
they would be able to properly account
for the fan power when rating their
products. (Unico, No. 63 at p. 2)
Lennox; the Joint Advocates of
ACEEE, NRDC, and ASAP; UTC/Carrier;
Goodman; and Rheem had submitted
comments in regard to the two-phase
proposal related to coil-only and blower
coil requirements. As noted previously,
these stakeholders were members of the
CAC/HP ECS Working Group, and as
such the comments are not included
here.
JCI commented that the current
language used in Appendix M denoting
the HSVC match cannot be determined
with exact statistics and that it actually
inhibits the adoption of new and
promising advancements in product
design. (JCI, No. 66 at p. 4) In contrast,
Unico commented that, as an indoor
coil manufacturer, it believes it to be
important that the outdoor unit
manufacturer continue to test and rate
the HSVC, as this is an integral
requirement for their AEDM to maintain
accuracy. (Unico, No. 63 at p. 2)
UTC/Carrier also submitted a
comment related to removal of the
HSVC requirement. As noted
previously, UTC/Carrier was a member
of the CAC/HP ECS Working Group, and
as such the comment is not included
here.
In the term sheet, the CAC/HP ECS
Working Group recommended that DOE
implement the following requirements
for single-split system air conditioners
and suggested some implementing
regulatory text:
• Every combination distributed in
commerce must be rated.
Æ Every single-stage and two-stage
condensing unit distributed in
commerce (other than a condensing unit
for a 1-to-1 mini split) must have at least
1 coil-only rating that is representative
of the least efficient coil distributed in
commerce with a particular condensing
unit.
• Every condensing unit distributed
in commerce must have at least 1 tested
combination.
Æ For single-stage and two-stage
condensing units (other than
condensing units for a 1-to-1 mini split),
this must be a coil-only combination.
• All other combinations distributed
in commerce for a given condensing
unit may be rated based on the
application of an AEDM or testing in
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
accordance with the applicable
sampling plan.
(Docket No. EERE–2014–BT–STD–0048,
No. 76, Recommendation #7)
DOE notes that this recommendation
is similar to DOE’s Phase 1 proposal, as
it is based primarily on coil-only values.
In particular, single-stage and two-stage
condensing units may not ever have
only a blower coil represented value.
The Working Group recommendation is
consistent with ADP and Unico’s
comments requesting that the tested
combination be a coil-only unit but
inconsistent with JCI’s request that twostage units be tested with a blower coil.
Given the preponderance of
stakeholders supporting the
recommendation, and the fact that
multi-stage units may be tested and
rated with a blower coil, DOE believes
that adopting the Working Group
recommendation best addresses the
majority of stakeholder concerns. For
these reasons, and given that there is no
longer a need for a second-phase, DOE
is adopting the recommendation in the
term sheet, which will become effective
180 days after publication of this final
rule. DOE notes that while 1-to-1 minisplits are not expected to have a coilonly represented value, this exception
does not appear explicitly in the
regulatory text. DOE clarifies that since
ductless mini-splits are never
distributed in commerce as coil-only
units, there is no coil-only value that
would be representative. Therefore
these units only require blower coil
represented values. DOE also notes that
the Working Group recommendation
that every condensing unit distributed
in commerce have at least one tested
combination was based on the premise
that manufacturers would group
multiple individual combinations with
a single model of outdoor unit into a
basic model, as allowed in the adopted
basic model definition. If manufacturers
instead choose to make every individual
combination (using the same model of
outdoor unit) a separate basic model,
each individual combination would be
required to be tested. This aligns with
the basic model framework discussed in
section III.A.1.a.
DOE also adopts these
recommendations for space-constrained
split-system air conditioners given that
they are subject to the same test
procedure provisions and sampling
plans as non-space-constrained singlesplit-system air conditioners.
DOE notes that both the current test
procedure and the test procedure
proposed in the November 2015 SNOPR
requires that the test conditions used for
testing coil-only units be the same as
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
those used for units with single-speed
compressors. For example, section 3.2.1
of the current Appendix M indicates
that these tests, listed in Table 4 of
Appendix M as proposed, are, ‘‘. . . for
a unit . . . with no indoor blower
installed.’’ Because the regulatory
approach finalized in this notice
requires that two-stage condensing units
have a coil-only test, DOE has removed
‘‘coil-only units’’ from the description of
the units that must be tested using the
Table 4 tests.
DOE notes that the CAC/HP ECS
Working Group recommendation also
removes the requirement that the tested
combination be the HSVC. DOE believes
the Working Group recommendation
adequately addresses JCI’s concern
about using the highest sales volume as
a tested combination, but is inconsistent
with Unico’s request that OUMs test and
rate the HSVC. DOE will address this
aspect of the recommendation in the
separate notice and has not adopted it
in this final rule.
Goodman commented that DOE has
not adequately accounted for the
inherent variability and uncertainty
existing in the psychrometric test
procedures in determining that the
proposed change requiring two-stage
units to be tested as coil-only would not
affect the certified values. Goodman
commented that the test methods
specified by DOE, AHRI and ASHRAE
have an uncertainty for steady state
testing of approximately 6–8%.
Goodman also noted that ISO
16491:2012 Annex B lists several factors
associated with the indoor air enthalpy
method that contribute to uncertainty.
Moreover, Table A.3 of ISO 16491:2012
indicates that for typical cooling
capacity methods, relative expanded
uncertainty might be 6.8%. Goodman
commented that even at 0.05 SEER or
0.05 EER below the regional
requirements, new test data would
therefore either require the OUM to test
additional samples or would cause a
once-compliant unit to be marked as
non-compliant for the regional
standards. (Goodman, No. 73 at p. 17)
In response to Goodman’s concern
about this change impacting measured
energy use, DOE notes that current
regulations require testing with the
evaporator coil that has the largest
volume of retail sales with the particular
model of condensing unit. DOE
understands that, for two-stage units,
this is typically a coil-only combination
since many homeowners do not replace
the furnace at the same time when they
replace their split-system air
conditioning system and therefore that
manufacturers should represent twostage units as coil-only combinations. At
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
the manufacturer’s discretion, the twostage units could also be represented as
blower-coil combinations. Therefore,
DOE does not believe the adopted
requirements for two-stage units will
change the impacted energy use,
b. Split-System Heat Pumps and SpaceConstrained Split-System Heat Pumps
The current requirements for splitsystem heat pumps in 10 CFR 429.16
require testing a condenser-evaporator
coil combination with the evaporator
coil likely to have the largest volume of
retail sales with the particular model of
condensing unit.
In the November 2015 SNOPR, DOE
proposed to slightly modify the wording
explaining the testing requirement for
split-system heat pumps to refer to the
‘‘evaporator coil’’ and condensing unit’’
as the ‘‘indoor unit’’ and ‘‘outdoor
unit’’, as the word ‘‘outdoor unit’’ is
more appropriate for heat pumps than
‘‘condensing unit’’. DOE also proposed
to apply this same test requirement to
space-constrained split-system heat
pumps. 80 FR 69278, 69286–87 (Nov. 9,
2015).
DOE received no comment on this
proposal, and in this final rule, DOE
adopts the wording modifications.
However, in the separate notice
regarding Appendix M1, DOE will
consider additional modifications based
on the recommendations of the CAC/HP
ECS Working Group with regard to splitsystem air conditioners.
c. Multi-Split, Multi-Circuit, and MultiHead Mini-Split Systems
The current requirements in 10 CFR
429.16(a)(2)(ii) specify that multi-split
systems and mini-split systems
designed for installation with more than
one indoor unit be tested using a ‘‘tested
combination’’ as defined in 10 CFR
430.2.
In the November 2015 SNOPR, DOE
proposed a slight modification to the
testing requirements for single-zonemultiple-coil7 and multi-split systems
and proposed to add similar
requirements for testing multi-circuit
systems (see section III.C.2 for more
information about these systems). DOE
also explained that these requirements
apply to VRF systems that are singlephase and less than 65,000 Btu/h. For
all multi-split, multi-circuit, and singlezone-multiple-coil split systems, DOE
7 The November 2015 SNOPR defined a singlezone-multiple-coil split system as representing a
split system that has one outdoor unit and that has
two or more coil-only or blower coil indoor units
connected with a single refrigeration circuit, where
the indoor units operate in unison in response to
a single indoor thermostat. In this final rule, DOE
has adopted the term multi-head mini-split system
instead.
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
37003
proposed that, at a minimum, each
model of outdoor unit must be tested as
part of a tested combination (as defined
in the CFR) composed entirely of nonducted indoor units. For any models of
outdoor units also sold with shortducted indoor units, DOE proposed a
second ‘‘tested combination’’ composed
entirely of short-ducted indoor units
would be required to be tested. DOE
also proposed that a manufacturer may
rate a mixed non-ducted/short-ducted
combination as the mean of the
represented values for the tested nonducted and short-ducted combinations.
80 FR 69278, 69287 (Nov. 9, 2015).
Under the November 2015 SNOPR
proposed definition of basic model,
these three combinations (non-ducted,
short-ducted, and mixed) would
represent a single basic model. When
certifying the basic model,
manufacturers should report something
like ‘‘* * *’’ for the indoor unit model
number and report the test sample size
as the total of all the units tested for the
basic model, not just the units tested for
each combination. For example, if the
manufacturer tests 2 units of a nonducted combination and two units of a
short-ducted combination, and also
rates a mixed combination, the
manufacturer should specify ‘‘4’’ as the
test sample size for the basic model,
while providing the rating for each
combination. DOE also proposed that
manufacturers be allowed to test and
rate specific individual combinations as
separate basic models, even if they share
the same model of outdoor unit. In this
case, the manufacturer would provide
the individual model numbers for the
indoor units rather than stating a
generic model, such as ‘‘* * *’’.
DOE also proposed adding a
requirement that, for any models of
outdoor units also sold with models of
small-duct, high velocity (SDHV) indoor
units, a ‘‘tested combination’’ composed
entirely of SDHV indoor units must be
used for testing and rating. However,
such a system would be certified as a
different basic model. 80 FR 69278,
69287 (Nov. 9, 2015).
In the November 2015 SNOPR, DOE
noted that multi-split systems consisting
of a model of outdoor unit paired with
models of non-ducted or short-ducted
units should meet the energy
conservation standards for split-system
air conditioners or heat pumps, while
systems consisting of a model of
outdoor unit paired with models of
SDHV indoor units should meet SDHV
standards. DOE also proposed
requirements for models of outdoor
units that were rated and distributed in
combinations that span multiple
product classes to be tested and certified
E:\FR\FM\08JNR2.SGM
08JNR2
37004
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
as compliant with the applicable
standard for each product class. Even if
a manufacturer would sell a
combination including models of both
SDHV and other non-ducted or shortducted indoor units, DOE proposed that
the manufacturer should not provide a
mixed rating for such combinations. 80
FR 69278, 69287–88 (Nov. 9, 2015).
asabaliauskas on DSK3SPTVN1PROD with RULES
Use of Term ‘‘Short-Ducted’’
DOE received several comments
regarding its use of short-ducted
systems as well as requests for lowstatic and mid-static terminology and
comments regarding conventional
ducted systems. Many of these systems
and ESP requirements were
recommended as part of the CAC/HP
ECS Working Group term sheet and will
be discussed in a separate notice.
In this final rule, DOE has not
adopted use of the term short-duct and
instead refers only to ducted units.
Mixed Represented Values for SDHV
and Other Indoor Units
Several stakeholders commented on
whether they supported represented
values for mixed multi-split systems
including models of both SDHV and
non-ducted or ducted indoor units, and
if so, how they should be rated and
whether the SDHV or split-system
standard would be most appropriate.
Nortek commented that some
manufacturers publish ratings in the
AHRI Directory for SDHV and nonducted as an average value and that it
is appropriate to maintain this practice
for this product as it is for the mixed
(ducted and non-ducted) indoor multisplit ratings. (Nortek, No. 58 at p. 13)
Unico commented that they publish
multi-split ratings for SDHV indoor
units, non-ducted indoor units and a
mixture of SDHV and non-ducted
indoor units. The mixed rating is
calculated as an average of the other
two, which are based on tests. This is
the same procedure used for ducted
(‘‘short-ducted’’) and non-ducted indoor
units. Unico requested the same
consideration as all other manufacturers
that have mixed (ducted and nonducted) indoor multi-split ratings.
(Unico, No. 63 at p. 3)
UTC/Carrier questioned whether there
is any data available on the frequency of
application of mixed SDHV and nonducted, ducted or short duct unit
systems to determine the need for a
separate system rating. Lacking this
data, UTC/Carrier recommended not
supporting mixed multi-split system
ratings for these systems. (UTC/Carrier,
No. 62 at p. 4)
Goodman agreed that SDHV should
not be intermixed with non-ducted or
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
other ducted indoor units, and that
SDHV ICMs should be required to rate
and certify such systems based upon the
external static pressure associated with
the SDHV indoor units. (Goodman, No.
73 at p. 13–14)
Unico agreed with DOE that the
SDHV test standard is appropriate for
testing the multi-split SDHV indoor
units. However, Unico asserted that, in
doing this, it is not necessary to apply
a standard for the mixed indoor
combinations since the ratings are based
on other ratings that already meet their
appropriate standard. (Unico, No. 63 at
p. 3)
NEEA and NPCC supported the rating
and certification of systems that are
distributed in combinations that span
more than one product class (such as
multi-split and SDHV) and stated that
these systems must be tested and rated
so as to meet the standards for all
product classes represented by the
various available combinations. NEEA
and NPCC suggested that each class
rating be listed separately, in
accordance with the testing and rating
requirements for that class, and be so
identified in the ratings documentation.
(NEEA and NPCC, No. 64 at p. 4)
After reviewing the comments, DOE
has determined that given that current
industry practice includes mixed
represented values for SDHV and other
non-ducted or ducted indoor units, DOE
will explicitly allow these mixed
represented values based on an average
of the represented values for each of the
homogenous indoor systems. DOE has
clarified this in 429.16. As noted in the
November 2015 SNOPR, SDHV
represented values must be a separate
basic model. Any represented values for
a mixed system including SDHV and
another style of unit (non-ducted or
ducted) must be in the same basic
model as the SDHV model.
Ability To Test Mixed Systems
Several stakeholders commented on
whether they supported having the
ability to test mixed systems (i.e.,
systems including both non-ducted and
ducted indoor units) using the test
procedure rather than using an average
of the other tested systems.
UTC/Carrier did not support mixed
system ratings nor test averaging due to
consumer confusion, proliferation of
ratings, and too many permutations.
(UTC/Carrier, No. 62 at p. 4) The
California IOUs commented that for all
types of split systems, it is important to
not have averaged ratings and cited as
an example that, for the California
Building Energy Efficiency Code (Title
24), the rating of the system being
installed is needed to demonstrate
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
compliance. For incentive programs
managed by Energy Efficiency Program
Administrators such as the California
IOUs, calculation and tracking of energy
savings require that the installed system
be known and its rating is available.
(California IOUs, No. 67 at p. 3)
AHRI and Nortek commented that
averaging of ducted and non-ducted
ratings has been a long-standing
industry practice. According to AHRI
and Nortek, the kind of indoor ducted
unit should be identified as part of the
rating so that the mixed ratings could
then be based on ratings for the specific
kinds of indoor units. (AHRI, No. 70 at
p. 16; Nortek, No. 58 at p. 13)
In response to UTC/Carrier, DOE
notes that given the test requirements to
make representations for individual
combinations other than the ‘‘tested
combination’’(as discussed later in this
section), and the limited amount of
permutations currently listed in the
AHRI directory, proliferation of
represented values is not expected. In
response to the California IOUs, DOE
notes that the averaged represented
values are based on represented values
for kinds of individual systems (i.e.,
ducted or non-ducted). As a result, an
additional averaged represented value
does not take away the availability of
non-averaged represented values.
AHRI and Nortek also commented
that, in industry practice, multi-split
ratings with mixed indoor unit types are
the numerical average of the ratings for
each of the homogeneous indoor
systems. They stated that the most
common mixture is ducted and nonducted indoor units. They asserted that
there is no test procedure that could
adequately test these combinations.
(AHRI, No. 70 at p. 16; Nortek, No. 58
at p. 13)
Unico did not support testing mixed
multi-split systems and commented that
there is no adequate test procedure.
Unico commented that using a
numerical average of the individual (all
ducted or all non-ducted) ratings is the
best method to develop a rating for a
mixed multi-split system. (Unico, No.
63 at p. 3)
Rheem commented that
manufacturers should be permitted to
test mixed systems instead of using an
average to capture the interaction of the
compressor with the multiple styles of
indoor units. (Rheem, No. 69 at p. 5)
NEEA and NPCC commented that,
given that the rating method for mixed
multi-split systems will almost
invariably produce a rating that is
unrelated to how they actually operate
in the field, they see no value in
additional testing. However, NEEA and
NPCC have no objection to
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
manufacturers testing such systems if
the manufacturers believe the ratings
would be better or more reliable with
additional testing. (NEEA and NPCC,
No. 64 at p. 4)
DOE acknowledges that testing mixed
systems could capture interactions not
captured in an average; however Rheem
did not provide suggestions for how to
develop such a test procedure. Given
that several other stakeholders believe
there is not currently an adequate test
procedure to do so, DOE declines to add
one at this time.
asabaliauskas on DSK3SPTVN1PROD with RULES
Options for Averaging
Several stakeholders commented on
whether they support determining
represented values for mixed systems
using other than a straight mean, such
as a weighting by the number of nonducted or short-ducted units.
Unico did not support weighting
mixed multi-split systems. Unico
commented that indoor units are made
in various sizes so the number of indoor
units is not indicative of the load split.
In addition, Unico stated that indoor
units are designed to provide a range of
capacities so the load split is dependent
mostly on the application rather than
the indoor unit size. (Unico, No. 63 at
p. 3)
NEAA and NPCC expressed
ambivalence regarding the use of
weighting by the number of ducted and
non-ducted units in the system. They
asserted that any alignment of the actual
performance of such multi-zone variable
capacity systems in the field and their
weighted ratings would be purely
accidental. (NEEA and NPCC, No. 64 at
p. 4)
Given the lack of interest in weighting
mixed systems, DOE will continue to
allow mixed represented values only as
a straight average of two individual
systems represented values containing
homogenous kinds of indoor units (i.e.,
non-ducted, ducted, or SDHV) tested
with the appropriate method of test in
the DOE test procedure.
Determining Represented Values for
Specific Individual Combinations
Several stakeholders commented on
whether DOE’s proposed definition in
the June 2010 NOPR for ‘‘tested
combination’’ would be appropriate for
determining represented values for
specific individual combinations, or
whether manufacturers prefer more
flexibility, such as ability to test more
than 5 indoor units. See 75 FR 31223,
31231 (June 2, 2010).
UTC/Carrier commented that rating
multi-split systems with more than 5
units is unnecessary, because all
manufacturers offer indoor units with a
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
nominal capacity of up to at least 12,000
BTU/hr. (UTC/Carrier, No. 62 at p. 5)
Mitsubishi commented that the
original intent of the proposed ‘‘tested
combination’’ definition was to provide
variable-speed multi-split (VSMS)
system manufacturers with a method to
provide efficiency and capacity ratings
that would be representative of all the
combinations associated with a specific
outdoor unit. Mitsubishi stated that
DOE based the ‘‘tested combination’’
concept on the fact that the outdoor unit
is the primary driver for efficiency and
capacity and that DOE recognized that,
if a manufacturer had ‘‘specific’’
combinations that had higher
efficiencies than the ‘‘tested
combination,’’ then the manufacturer
could test and rate that ‘‘specific’’
combination and enter it into the AHRI
VSMS Directory of Certified Products.
Mitsubishi recommended that DOE
continue this process because it
provides the VSMS manufacturer with
the best opportunity to highlight topperforming combinations. (Mitsubishi,
No. 68 at p. 3)
Unico supported the proposed DOE
definition of ‘‘tested combination’’ and
stated that there is no need to rate
individual combinations unless the
manufacturer chooses to rate all
possible combinations (for example, if a
manufacturer has a limited number of
indoor models). Unico commented that
single-split systems (one indoor unit)
using the same outdoor unit used for
multi-split systems should continue to
be rated individually. (Unico, No. 63 at
p. 4)
NEEA and NPCC acknowledged that
combinations that might fall outside the
current definition of ‘‘tested
combination’’ systems do exist and are
installed on a regular basis. The testing
burden would be relatively small, as
only the largest-capacity systems are
capable of operating with more than 5
indoor units. (NEEA and NPCC, No. 64
at p. 4)
AHRI and Nortek commented that
they do not believe the tested
combination approach is appropriate for
rating specific individual models.
(AHRI, No. 70 at p. 16; Nortek, No. 58
at p. 13)
Rheem commented that the benefits of
mix match ratings for multi-split
systems are the same as those provided
by mix match ratings for split systems.
Rheem stated that consumers expect the
ratings provided by DOE to reflect the
operation of the system in their home
and concluded that outdoor units
should be rated to the worst case
scenario and manufacturers should use
an AEDM to determine the other
combinations of indoor and outdoor
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
37005
units. On the other hand, DOE notes
that Rheem also commented that a
configuration that represents the highest
sales volume should be established for
multi-split systems. (Rheem, No. 69 at p.
5)
After reviewing the comments, DOE
maintains its proposal to allow
manufacturers to rate individual
combinations as additional basic models
beyond the required tested
combinations. DOE agrees with Rheem
and Mitsubishi that consumers and
utilities often find benefit for having
represented values for a wide variety of
combinations that are available for
installation.
DOE also agrees with Unico that
single-split systems (one indoor unit)
using the same outdoor unit used for
multi-split systems must continue to be
rated individually.
Sample Size
Several stakeholders commented on
DOE’s request for information and data
on manufacturing and testing variability
associated with multi-split systems that
would allow it to understand how a
single unit may be representative of the
population and what tolerances would
need to be applied to represented values
based on a single unit sample in order
to account for variability.
Lennox commented that multi-split
products are subject to the same type of
variability as a conventional unit in
areas such as compressor variation, coil
performance variation, charging,
airflow, expansion device, etc. Lennox
did not support an allowance for OUM
manufacturers of multi-split products to
be rated based on a single unit test
while OUM manufacturers of
conventional products are required to
test a minimum of two samples to meet
statistical confidence levels. Lennox
asserted that all OUM-manufactured
products should be required to meet the
same minimum test requirements.
(Lennox, No. 61 at p. 14)
Mitsubishi and Rheem also
recommended that the ratings be
established based on the testing of at
least two samples. (Mitsubishi, No. 68 at
p. 3; Rheem, No. 69 at p. 6)
The California IOUs commented that,
in addition to manufacturing variances,
controls software creates an additional
source of variability in the performance
of multi-split systems. The California
IOUs asserted that software drives the
performance of these variable capacity
units based on the input from indoor
and outdoor sensors. They stated that,
until DOE-vetted data is available for
these controls, the use of results from a
single unit test for rating is inadvisable.
(California IOUs, No. 67 at p. 4)
E:\FR\FM\08JNR2.SGM
08JNR2
37006
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Unico commented that a single unit
test is adequate provided the
manufacturer rates a system
conservatively. Specifically, Unico said
that a manufacturer should not be
permitted to rate a product directly
using the result of the single test;
instead, the manufacturer can generate a
rating from a single test through
derating the measured performance.
Unico gave the example that the rated
capacity and efficiency of a system
should be at least 95 percent less than
the single test result. If two or more tests
are conducted, then Unico suggested
that the rating could be the mean value
or less. (Unico, No. 63 at p. 4)
Goodman suggested that, if DOE
mandates that ratings for a single given
kind of air conditioner (ducted,
non-ducted or mixed) be based on two
sample systems, then OUMs should be
able to use AEDMs to rate some of the
kinds of systems. Goodman stated that,
because many multi-split and
multi-head mini-split systems use the
same indoor products for multiple sizes
(e.g., a 2-ton system may use two 1-ton
indoor units while a 3-ton system may
use three of the exact same 1-ton indoor
units), a method to use an AEDM should
be developed for rating non-tested
systems. Goodman gave the example
that, if one OUM chose to test two
sample systems of non-ducted indoor
units, it should be able to rate ducted
and mixed systems based on an AEDM.
Goodman asserted that, if the OUM
chose to have a single rating for all
combinations of ducted indoor units,
then the AEDM would obviously have
to be used to rate the combination of
ducted indoor units with the lowest
efficiency rating. Goodman gave a
contrasting example that, if another
OUM chose to rate multiple different
combinations of ducted indoor units,
then each combination would be rated
using an AEDM. (Goodman, No. 73 at p.
13)
AHRI and Nortek recommended that
DOE maintain consistency with its
AEDM approach used in the commercial
HVAC equipment such that, at a
minimum, manufacturers would test
two low static units and apply the
AEDM to derive ratings for the high
static and mixed ratings. (AHRI, No. 70
at p. 16; Nortek, No. 58 at p. 13)
As previously noted, Rheem stated
that outdoor units should be rated to the
worst case scenario and manufacturers
should use an AEDM to determine the
other combinations of indoor and
outdoor units. (Rheem, No. 69 at p. 5)
After reviewing the comments, DOE
found that commenters did not provide
data on manufacturing and testing
variability that would support DOE
moving to a single unit sample
approach. In response to Goodman,
AHRI, Nortek, and Rheem, DOE notes
that DOE’s current regulations require
that represented values for a single kind
of system be based on testing a sample
of at least two units representative of
production units. For these reasons,
DOE is not moving to a single unit
sample approach and also declines to
require only the represented values of a
single kind of system to be based on
testing while allowing other kinds of
systems to be represented using an
AEDM, given that the adopted testing
requirements do not increase test
burden compared to the current
regulations. DOE is allowing use of an
AEDM for off-mode, as discussed in
section III.B.8.
Summary
In summary, Table III.2 provides an
example of allowable represented values
for multi-split, multi-circuit, and multihead mini-split systems.
TABLE III.2—EXAMPLE REPRESENTED VALUES FOR MULTI-SPLIT SYSTEMS
Basic model
Individual model (outdoor unit)
Individual model(s) (indoor unit)
ABC ..............................
ABC–ND1 .....................
ABC–SDHV ..................
ABC .............................
ABC .............................
ABC .............................
*** ..................................
2–A123; 3–JH746 .........
*** ..................................
asabaliauskas on DSK3SPTVN1PROD with RULES
d. Basic Models Rated by ICMs
In the November 2015 SNOPR, DOE
proposed to require ICMs to test and
provide certified ratings for each model
of indoor unit (i.e., basic model) with
the least-efficient model of outdoor unit
with which it will be paired, where the
least-efficient model of outdoor unit is
the outdoor unit in the lowest-SEER
combination as certified by the OUM. If
more than one model of outdoor unit
(with which the ICM wishes to rate the
model of indoor unit) has the same
lowest-SEER rating, the ICM may select
one for testing purposes. ICMs must rate
all other individual combinations of the
same model of indoor unit, but may
determine those ratings through testing
or use of an AEDM. 80 FR 69278, 69288
(Nov. 9, 2015).
AHRI, ADP, Lennox, Mortex, and
First Co. commented that DOE’s
proposed changes to the definition of
‘‘basic model’’ with respect to ICMs,
along with the proposed requirement to
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Ducted
rep. value
Sample
size
4
2
6
Nonducted
rep. value
Mix rep.
value (D/
ND)
SDHV
rep. value
Mix rep.
Value
(SDHV/D)
Mix rep.
value
(SDHV/
ND)
14
................
................
15
17
................
14.5
................
................
................
................
11.5
..................
..................
12.75
..................
..................
13.25
test at least one combination within
each basic model, presents a significant
testing burden to ICMs. (First Co., No.
56 at p. 1; AHRI, No. 70 at p. 3; ADP,
No. 59 at p. 1; Lennox, No. 61 at p. 4)
In order to avoid this burden, AHRI,
ADP, Lennox, and Mortex
recommended DOE adopt and define
the term ‘‘Similarity Group,’’ a group of
ICM basic models within a defined
range of coil geometries, with
performance substantiated by the same
validation test, and require testing of a
Similar Group rather than testing of
each basic model. The range of coil
geometries within a Similarity Group
would be defined by: face area within ±
1 square feet (e.g. 2–4, 4–6, etc.), fin
material (e.g. aluminum, copper), fin
style (e.g. wavy, louvered), fin density
within ± 1 fin per inch (e.g. 10–12, 13–
15, etc.), number of rows, tube pattern
(e.g. 1 × 0.625, 1 × 0.75, etc.), tube size
(e.g. outer diameter for round tube,
channel characteristic size for
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
microchannel), and tube internal
enhancement (e.g. smooth or enhanced).
(AHRI, No. 70 at p. 5; ADP, No. 59 at
p. 2–3; Mortex, No. 71 at p. 4–6;
Lennox, No. 61 at p. 5) AHRI, ADP,
Mortex, and Lennox noted that in the
proposed framework, Similarity Groups
may span AC and HP operations as well
as coil-only and blower coil
combinations. (AHRI, No. 70 at p. 6;
ADP, No. 59 at p. 3; Mortex, No. 71 at
p. 6; Lennox, No. 61 at p. 6)
However, the commenters noted that
the proposed Similarity Group concept
would not replace the concept or
definition of an ICM basic model.
Instead, a Similarity Group would be a
group of basic models for defining
AEDM validation test requirements, and
the ICM basic model would still be used
for other aspects of the certification and
enforcement scheme as noted in the
SNOPR. (AHRI, No. 70 at p. 7; ADP, No.
59 at p. 4; Mortex, No. 71 at p. 7;
Lennox, No. 61 at p. 7)
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
With regard to DOE’s proposed
definition of basic model for ICMs,
Lennox requested that tube wall
thickness not be required as part of a
certification report as to protect
business sensitive design information.
(Lennox, No. 61 at p. 3)
UTC/Carrier, Rheem, and the Joint
Advocates of ACEEE, NRDC, and ASAP
supported DOE’s proposal for ICMs to
test each model of indoor unit with the
lowest-SEER model of outdoor unit that
is certified as a part of a basic model by
an OUM. (UTC/Carrier, No. 62 at p. 6;
Rheem, No. 69 at p. 6; ACEEE, NRDC,
ASAP, No. 72 at p. 2) UTC/Carrier
appreciated leveling the playing field
closing this loophole advantage for
ICMs. (UTC/Carrier, No. 62 at p. 6)
On the other hand, AHRI, ADP,
Lennox, and Mortex commented that
testing is necessary to validate product
performance and each ICM’s AEDM, but
that the requirement to test every basic
model presents an excessive burden on
ICMs. (AHRI, No. 70 at p. 3; ADP, No.
59 at p. 1; Mortex, No. 71 at p. 3;
Lennox, No. 61 at p. 4) First Co. also
commented that the result of DOE’s
proposal is excessive testing. (First Co.,
No. 56 at p. 1)
AHRI analyzed data from the AHRI
Directory of Certified Product
Performance, considering air
conditioning, heat pump, coil-only and
air handler ratings, but omitting due to
time limitations air flow, external static
pressure and power input. The results
indicated that each ICM has between
287 and 604 basic models for which
they would have to bear the cost of
testing, which AHRI estimated would
increase several-fold if accounting for
the additional parameters. AHRI stated
that it used an estimate of testing costs
for one system at an independent lab of
$7,400 for AC and $10,000 for HP
because many ICMs do not have their
own labs. Therefore, by AHRI’s
calculations, the ICM with the smallest
number of basic models from their
analysis would be required to perform
574 tests for an estimated $5,740,000 in
testing costs. In addition, a test takes
approximately one day, so 574 tests
would take approximately two years to
complete. (AHRI, No. 70 at p. 4–5)
For these reasons, AHRI, ADP,
Mortex, and Lennox recommended that
DOE require all ICM ratings to be based
on an AEDM, where the ICM would test
and rate at least one combination of an
outdoor unit with the lowest SEER that
complies with standard per Similarity
Group. They also recommended that the
ICM perform at least one full-system test
per Similarity Group, or if the ICM was
rating HP combinations, the ICM test
one-third of the Similarity Groups with
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
HP systems in both heating and cooling
modes; and certify all combinations
before they are distributed in commerce.
(AHRI, No. 70 at p. 5–6; ADP, No. 59 at
p. 2–3; Mortex, No. 71 at p. 4–6;
Lennox, No. 61 at p. 5) AHRI, ADP,
Mortex, and Lennox noted that applying
this scheme to the AHRI Directory
results in between 26 and 64 tests for
the same ICM companies analyzed
above. AHRI, ADP, Mortex, and Lennox
believed that their suggested method
provides for an extremely high level of
AEDM validation while creating a
manageable testing burden on ICMs.
(AHRI, No. 70 at p. 6; ADP, No. 59 at
p. 3–4; Mortex, No. 71 at p. 6; Lennox,
No. 61 at p. 6–7)
First Co. and Unico also supported
AHRI’s approach. First Co. commented
that the use of a Similarity Group would
be a more realistic and workable
approach that would enable ICMs to
reduce testing for comparably
performing indoor coils and to validate
performance for the group by the same
test. (First Co., No. 56 at p. 1) Unico
recommended that DOE require the
OUM to have at least two tests for each
basic model (the outdoor unit) and the
ICM to have at least one test from each
Similarity Group in order to validate the
AEDM. Unico also noted that the ICM
testing requirements would increase
significantly compared to what they are
today even under AHRI’s suggestion.
(Unico, No. 63 at p. 4–5)
After reviewing the comments, DOE
agrees with the manufacturers that its
proposed definition of basic model with
respect to ICMs, combined with the
proposed testing requirements, may
result in a significant test burden for
ICMs. In order to balance the burden of
testing with the risk of enforcement
action, DOE is adopting aspects of the
suggested ‘‘Similarity Group’’ as a
replacement to its proposed definition
of basic model. Hence, the basic model
definition for ICMs established in this
final rule includes all individual
combinations having comparably
performing indoor coil(s) [plus or minus
one square foot face area, plus or minus
one fin per inch fin density, and the
same fin material, tube material, number
of tube rows, tube pattern, and tube
size].
DOE also agrees that manufacturers
should test one combination per what
the AHRI and manufacturer calls
‘‘Similarity Group’’, and what DOE will
call a basic model for ICMs. However,
DOE does not agree that testing should
only serve to validate AEDMs. In order
to accurately rate these non-engineeredto-order products by capturing the
variability in the manufacturing
processes, all combinations required to
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
37007
be tested must be tested according to the
sampling plan in 429.16, which
generally requires a sample of at least
two units of the basic model. DOE notes
that AHRI’s calculation of burden
assumes that ICMs have not been testing
under current regulations, which is not
consistent with existing DOE
regulations. In addition, by changing the
proposed definition of basic model to
align with the similarity group proposal,
DOE has significantly reduced the
proposed test burden on ICMs.
DOE notes that because basic models
do not span product classes, unlike in
the stakeholders’ proposal, each
Similarity Group is limited to either air
conditioners or heat pumps; however, in
response to the stakeholders’ request
that only one-third of Similarity Groups
need be tested in both cooling and
heating mode, DOE is not requiring
testing for basic models of heat pumps
as long as an equivalent basic model of
air conditioner has been tested.
DOE also notes that while off-mode
power consumption requirements apply
to ICMs, the represented values for offmode may be based on the results of
testing by the OUM according to the
requirements in 429.16.
In response to Lennox’s request to
remove tube wall thickness from the
definition of basic model, DOE notes
that the Similarity Group requirements
DOE is adopting in its basic model
definition for ICMs do not include tube
wall thickness; in addition, as noted in
section III.A.1.c, DOE did not propose
that manufacturers report this
information regardless of its inclusion
in this definition.
e. Single-Package Systems
In the current regulations, 10 CFR
429.16(a)(2)(i) states that each singlepackage system must have a sample of
sufficient size tested in accordance with
the applicable provisions of Subpart B.
In the November 2015 SNOPR, DOE
proposed that the lowest SEER
individual model within each basic
model must be tested. DOE expected
that in most cases, each single-package
system would represent its own basic
model. However, based on the
definition of basic model in section
III.A.1, this may not always be the case.
DOE noted that regardless, AEDMs do
not apply to single-package systems—
manufacturers may either test and rate
each individual single-package system
or, if multiple individual models are
assigned to the same basic model per
the proposed requirements in the basic
model definition, test only the lowest
SEER individual model within the basic
model and use that to determine the
E:\FR\FM\08JNR2.SGM
08JNR2
37008
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
rating for the basic model. 80 FR 69278,
69288 (Nov. 9, 2015).
DOE also proposed to specify this
same requirement for space-constrained
single-package air conditioners and heat
pumps. 80 FR 69278, 69288 (Nov. 9,
2015).
DOE requested comment on the
likelihood of multiple individual
models of single-package units meeting
the requirements proposed in the basic
model definition to be assigned to the
same basic model. DOE also requested
comment on whether, if manufacturers
are able to assign multiple individual
models to a single basic model,
manufacturers would want to use an
AEDM to rate other individual models
within the same basic model other than
the lowest SEER individual model.
In response, Lennox commented that
the use of basic models that meet the
defined requirements should not be
restricted to split-system products
because allowing groupings in a basic
model may allow the use of AEDMs for
single-package products to reduce
testing burden. (Lennox, No. 61 at p. 14)
UTC/Carrier supported that different
options would be assigned to
[individual models within] the same
basic model and supported the ability to
have unique ratings for units with
different options without additional
testing. (UTC/Carrier, No. 62 at p. 6–7)
JCI stated that it, in general, would
prefer to test single-package units,
especially the single-phase models. For
3-phase (commercial) products, JCI
would opt to utilize an AEDM. (JCI, No.
66 at p. 15)
Rheem disagreed that manufacturers
should not be allowed to use AEDM to
rate packaged units; Rheem would want
to use an AEDM to rate other individual
models within the basic model for
packaged units. (Rheem, No. 69 at p. 3,
6–7)
In response to these comments, DOE
is modifying the regulations to permit
the use of AEDMs for models of singlepackage units in cases where multiple
individual models are assigned to the
same basic model. The lowest SEER
individual model in the basic model
still will be required to be tested. DOE
believes that the lowest SEER model
will typically be similar to the highest
sales volume model.
f. Replacement Coils
In the November 2015 SNOPR, DOE
noted that its proposed definition of
‘‘indoor unit’’ refers to the box rather
than just a coil. Accordingly, legacy
indoor coil replacements and uncased
coils would not meet the definition of
indoor unit of a central air conditioner
or heat pump. Hence, they would not
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
need to be tested or certified as meeting
the standard. 80 FR 69278, 69289 (Nov.
9, 2015).
DOE received several comments in
response to this proposal. These
comments have been addressed as part
of DOE’s definition of ‘‘indoor unit,’’
discussed in section III.A.2.
Attaining a given efficiency level when
testing a combination having a lowerNGIFS indoor unit requires use of a
more efficient outdoor unit to
compensate. These outdoor unit models
must meet applicable Federal standards
when tested with the specified indoor
units.
g. Outdoor Units With No Match
For split-system central air
conditioners and heat pumps, current
DOE regulations require that
manufacturers test the condensing unit
and ‘‘the evaporator coil that is likely to
have the largest volume of retail sales
with the particular model of condensing
unit’’ (commonly referred to as the
highest sales volume combination or
HSVC). 10 CFR 4429.16(a)(2)(ii).
Effective January 1, 2010, the U.S.
Environmental Protection Agency (EPA)
banned the sale and distribution of
those central air conditioning systems
and heat pump systems that are
designed to use HCFC–22 refrigerant. 74
FR 66450 (Dec. 15, 2009). EPA’s
rulemaking included an exception for
the manufacture and importation of
replacement components, as long as
those components are not pre-charged
with HCFC–22. Id. at 66459–60.
Because complete HCFC–22 systems
can no longer be distributed,
manufacturers inquired how to test and
rate individual components. Because
the EPA prohibits distribution of new
HCFC–22 condensing unit and coil
combinations (i.e., complete systems),
there is no such thing as a HSVC, and
hence, testing and determination of
represented values of new HCFC–22
combinations cannot be conducted
using the existing test procedure.
Accordingly, DOE proposed a test
procedure that may be used for
determining represented values and
certifying the compliance of these
outdoor units. DOE proposed to specify
coil characteristics to be used when
testing models of outdoor units that do
not have a HSVC. Specifically, these
requirements included limitations on
indoor coil tube geometries and
dimensions and coil fin surface area. In
the November 2015 SNOPR, DOE
proposed to require the normalized
gross indoor fin surface (NGIFS)
calculated for the indoor unit used for
the test to be no more than 1.15. 80 FR
69278, 69289 (Nov. 9, 2015). NGIFS is
the fin surface area divided by the unit’s
capacity. By imposing a limit on this
value, the size of the indoor coil would
be consistent with older model designs
that would likely be installed in the
field and that do not include a common
design approach for improving
efficiency, i.e. use of larger coils.
General Comments
AHRI, URI, Nortek, HARDI, Goodman,
UTC/Carrier, Rheem, and JCI submitted
comments against adding the test
procedure provisions for outdoor units
with no match. (AHRI, No. 70 at p. 2;
United Refrigeration, Inc., No. 60 at p.
3–4; Nortek, No. 58 at p. 2; HARDI, No.
57 at p. 2; Goodman, No. 73 at p. 17–
18; UTC/Carrier, No. 62 at p. 22–23;
Rheem, No. 69 at p. 3; JCI, No. 66 at p.
5)
Nortek and UTC/Carrier expressed
concern that offering a test procedure
for units with no match could
potentially open up a larger loophole
than what DOE is attempting to fix with
this proposal. (Nortek, No. 58 at p. 2;
UTC/Carrier, No. 62 at p. 23) Similarly,
Nortek and HARDI noted that there have
been no instances of a company trying
to sell an outdoor unit without match
that failed to meet existing standards.
(Nortek, No. 58 at p. 2; HARDI No. 57
at p.1)
Conversely, Lennox, NEEA, NPCC,
and the Joint Advocates of ACEEE,
NRDC and ASAP concurred with DOE’s
proposal to require testing and rating of
dry-ship units. (Lennox, No. 61 at p. 2;
NEEA and NPCC, No. 64 at p. 3; ACEEE,
NRDC and ASAP, No. 72 at p. 2)
DOE acknowledges these comments
and responds to particular concerns
about its proposal in subsequent
sections.
URI commented that the Department’s
proposal not only would ban the
manufacture of new replacement units,
it also would impose significant cost
burdens on manufacturers and
distributors of replacement HCFC–22
components. URI suggested that under
DOE’s proposal, replacement unit
manufacturers that tested and certified
HCFC–22 products in good faith
reliance of the various test procedure
guidance documents issued by the
Department would be unable to
advertise or sell these units. URI
requested that DOE evaluate the impacts
of replacing rather than repairing and
maintaining an HCFC–22 unit,
particularly on those consumers who
live on a fixed income, and that DOE
assess whether, as a practical matter,
this test procedure amendment would
adversely impact the availability of
replacement components for the
installed base of HCFC–22 units.
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
(United Refrigeration, Inc., No. 60 at p.
8–9)
In response to URI, DOE’s approach in
developing the test procedure
requirements for outdoor units with no
match is based on the concept that the
test should produce results that measure
energy efficiency during a
representative average use cycle. (42
U.S.C. 6293 (b)(3)) Further, the test
procedure addresses the fact that these
units have no match. Unmatched
outdoor units are primarily used as a
low-cost alternative to replacement of
an entire legacy system when the
outdoor unit is no longer operational.
Specifically, in such installations, only
the outdoor unit would be replaced,
rather than both the outdoor unit and
indoor unit. In addition, such units
would be installed using HCFC–22,
which is no longer legal for use in new
systems.
DOE developed this amended test
procedure with the goal of ensuring that
the unmatched outdoor unit should be
compliant when tested with an indoor
unit that is representative of indoor
units in the field with which the
outdoor unit could be paired. DOE’s
goal was to provide a method of test,
consistent with the current standards,
that meets the statutory requirement of
measuring a representative average use
cycle. Hence, the indoor unit
specifications are intended to represent
among the lesser-efficient units that
could be paired with a given outdoor
unit with no match. DOE believes this
approach is consistent with the
requirement that the represented value
for a basic model reflect the
performance of the poorest-performing
model that is part of the basic model.
In response to URI’s comments
regarding evaluation of cost burdens
and impacts of the test procedure
change, DOE notes that its energy
conservation standard rulemakings have
already evaluated the costs and benefits
of specific efficiency levels for central
air conditioners and heat pumps. This
test procedure provides a mechanism of
assessing the performance of unmatched
outdoor units, which can then be used
to provide a reasonable level of
assurance that all field-match
combinations of the new, unmatched
outdoor units will achieve the
established efficiency levels. DOE is
now adopting the November 2015
SNOPR approach for testing and
determining represented values for
unmatched outdoor units based on
stakeholder comment.
Goodman had concerns about
unforeseen and unintended
consequences when moving forward
with alternate refrigerants at some date
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
in the future, especially as the
requirements for applying air
conditioners and heat pumps with these
likely A2L refrigerants is unknown.
Goodman stated that it expects that,
with currently known alternate
refrigerants, there may be a need for
certain low-income and elderly
consumers to have cost-effective
replacement air conditioners. Goodman
also noted that it has apprehensions that
providing a test procedure provides a
path for HCFC-22 ‘‘dry ship’’ products
to continue in the marketplace.
(Goodman, No. 73 at p. 18)
DOE responds that it cannot set test
procedure requirements based on
speculation about the potential cost
impact of future refrigerant changes on
air-conditioning product costs. In
response to the second comment, DOE
points out the suggestion of commenters
that DOE’s proposal will limit sales of
these units—URI for example indicated
that the test procedure will effectively
end the manufacturer of such
components (URI, No. 60 at p. 2). While
DOE does not agree with this
assessment, DOE also does not believe
that the approach will increase
manufacturer of such units.
DOE Authority
In its comments, JCI stated that it was
not certain that DOE has the authority
under EPCA to create a test procedure
to allow for units with no match. (JCI,
No. 66 at p. 6)
URI commented that the DOE’s
November 2015 SNOPR test procedure,
if finalized, would violate EPCA, as
amended, as well as the Administrative
Procedure Act. URI asserted that DOE
had proposed a restriction on
representations for already
manufactured and certified units and
that the proposal would invalidate the
expectation-backed investments of
manufacturers and distributors,
constituting a violation of the Fifth
Amendment to the U.S. Constitution.
URI characterized DOE’s proposal as an
effective ban on condensing units using
HCFC–22 that also would impose
significant cost burdens on consumers.
(United Refrigeration, Inc., No. 60 at p.
2, 3–5)
URI also commented that a test
procedure change for replacement
HCFC–22 systems is not needed, and
that DOE has not articulated a valid
basis for its proposal, as required by
EPCA. URI argued that DOE’s proposed
test procedure change for replacement
HCFC–22 systems would violate the
Administrative Procedure Act, which
requires an agency to ‘‘examine the
relevant data and articulate a
satisfactory explanation for its action
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
37009
including a ‘rational connection
between the facts found and the choice
made.’’’ 5 U.S.C. 553, Motor Vehicle
Manufacturers Ass’n v. State Farm
Mutual Automobile Insurance Co., 463
U.S. 29 (1983)). URI said that the DOE
did not only fail to explain why the
change to the test procedure for
replacement units is necessary, but also
failed to acknowledge the de facto ban
it is proposing for such units. URI
argued that DOE does not have the
authority to impose a ban on
replacement units and asserted that,
even assuming that DOE has the
authority to impose such a ban, that
EPCA prohibits the Department from
implementing such an action through a
test procedure amendment. (United
Refrigeration, Inc., No. 60 at p. 5)
URI also argued that DOE could not
circumvent the prohibition against
retroactive effect by belatedly
‘‘clarifying’’ that HCFC–22 condensing
components are basic models in and of
themselves, even assuming that the
EPCA would allow such a
comprehensive revision of the ‘‘basic
model’’ via test procedure rulemaking.
(United Refrigeration, Inc., No. 60 at p.
9)
Contrary to URI’s assertions, DOE is
not, in this rule, imposing a de facto ban
on condensing units using HCFC–22.
DOE is amending a test procedure and,
in accordance with the applicable
provisions of EPCA, is ensuring that the
test procedure is reasonably designed to
measure the energy efficiency and
energy use of unmatched outdoor units
in a manner that is comparable to that
of other complete systems. DOE clearly
articulated the basis for its proposal and
has explained again here the need for a
test procedure applicable to unmatched
outdoor units. Regarding the amended
definition of basic model in today’s rule,
DOE is not proposing that the
definition, as amended, be applied
retroactively.
Test Procedure Details Including
Specification of Indoor Unit
Stakeholders provided a range of
comments regarding whether the
proposed details of the test for outdoor
units with no match are suitable.
Nortek, Ingersoll Rand, and Goodman
questioned how DOE determined the
proposed value for NGIFS and that the
default coefficient of cyclic degradation
should be used for these units, and
requested that DOE provide supporting
evidence. (Nortek, No. 58 at p. 2;
Ingersoll Rand, No. 65 at p. 12;
Goodman, No. 73 at p. 18)
URI commented that it is simply
impossible for any HCFC–22
replacement component to meet the 13
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37010
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
SEER standard using the amended test
procedure, stating that the proposed coil
size limitation makes no sense as such
coils were used in HCFC–22 units rated
to 10 SEER. URI also asserted that the
proposed coefficient of cyclic
degradation improperly excludes units
that use thermostatic expansion valves,
rather than orifice tubes, to control the
flow of refrigerants, thus penalizing the
efficiency rating approximately 6% (for
example, a 13 SEER unit with a
thermostatic expansion valve would
instead rate at 12.2 SEER). (United
Refrigeration, Inc., No. 60 at p. 2, 7)
Goodman noted that by specifically
choosing the 1.15 maximum NGIFS
(especially without deference to the
type of fin used), DOE is choosing
indoor coils that are smaller, but not
smallest, in size. Goodman commented
that based on the information it has, the
value of 1.15 would favor one
manufacturer, which has all of its
‘‘no-match’’ units rated with indoor
coils having less than 1.15 NGIFS, while
at least two manufacturers have zero
‘‘no-match’’ units rated with indoor
coils having less than 1.15 NGIFS.
Goodman commented that DOE should
not ignore fin surface type in the NGIFS
calculation, and that if DOE’s intent is
intent is to specify an indoor coil size
such that it is virtually impossible for an
OUM to have an outdoor unit with no
match that can achieve 13 or 14 SEER
as a system, then DOE should choose an
NGIFS in the range of 0.90 or less using
the proposed NGIFS formula.
(Goodman, No. 73 at p. 18–19)
JCI commented for a 10 SEER product,
the value of NGIFS of 1.15 is too small.
The NGIFS of 10 SEER products made
by JCI was 1.25, and these products will
have been out of production for 10 years
by the time this SNPOR is effective. JCI
said that, at this point, when an outdoor
unit fails, approximately 40% to 50%
would be 13 SEER plus equipment. A
reasonable NGIFS for 13 SEER
equipment would be 1.30, which is the
average for JCI’s 13 SEER HCFC–22
product when the EPA ban on new
produced equipment shipped with
HCFC–22 took effect in 2010: averaging
the 10 SEER and 13 SEER values leaves
a value of 1.28. JCI believes this value
to be a more representative value for
NGIFS and recommends DOE adopt it.
(JCI, No. 66 at p. 5–6)
Ingersoll Rand provided data on the
61 HCFC–22 systems that they had on
the market before HCFC–22 was phased
out. For the HSVCs of these 61 models,
the NGIFS ranged from 0.9784 to 1.9082
with a mean of 1.2692 and a standard
deviation of 0.2215. Ingersoll Rand
recommended a value of 1.75 for the
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
final rule. (Ingersoll Rand, No. 65 at p.
12)
JCI commented that modern heat
exchanger technology such as that
found in microchannel heat exchangers
significantly reduces the refrigerant
charge and thus reduces the cycling
losses, resulting consistently in
degradation coefficient values under
0.10 with piston metering (expansion)
devices, or non-bleed TXVs. JCI
recommended that rather than requiring
use of the default degradation
coefficient value, DOE should specify
the type of expansion device it believes
would be used in the legacy indoor
units, which in most instances would be
a piston or fixed orifice construction.
(JCI, No. 66 at p. 6)
As mentioned above, DOE’s approach
in developing the test procedure
requirements for outdoor units with no
match is based on the concept that the
test should produce results which
measure energy efficiency during a
representative average use cycle (see 42
U.S.C. 6293(b)(3)) while also ensuring
that they will generally meet the
standard. By their nature, however,
neither the manufacturer nor DOE
knows exactly what the paired system
will be. DOE evaluated indoor unit
specifications representing units across
the spectrum that would likely be
paired with the ‘‘no match’’ units. To
ensure compliance, DOE proposed
indoor unit specifications that it
believed to be representative of a less
efficient unit that could be paired with
the given outdoor unit with no match.
In developing its proposal, DOE
developed the indoor unit specifications
(1.15 NGIFS and coefficient of cyclic
degradation equal to the default)
through reverse engineering 13 SEER
split-system blower coil air conditioners
designed to use HCFC–22. The 1.15
value is representative of the indoor
units associated with the evaluated
systems. All of these units had singlecapacity compressors, and the indoor
units had PSC fan motors. Although the
NGIFS for these units ranged from 1.0
to 1.7, almost identical to the range of
the data provided by Ingersoll Rand,
DOE does not feel that establishing an
NGIFS range is a valid approach, since
this would be equivalent to setting the
limit equal to the highest end of the
range. In any case, both of these datasets
are at odds with URI’s claim that the
1.15 NGIFS makes attaining 13 SEER
impossible. Regarding JCI’s claim that
the value is too small, the selected value
is for an indoor unit that was part of an
HCFC–22 unit rated at 13 SEER, hence
it is certainly representative of the
indoor units that may be installed in the
field. In fact, DOE’s selection of 1.15 did
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
not consider the 10 SEER units whose
indoor units are still in the field as well.
In addition, the actual performance of
the non-replaced legacy indoor units,
represented in terms of NGIFS,
generally will be significantly degraded.
Degradation of indoor unit performance
can be caused by numerous factors,
including foulants coating external coil
surfaces, caustic environments attacking
fin material and/or fin/tube contact,
inadequate air flow, and degraded oil
fouling the internal tube surfaces.
Consistent with the use of unmatched
outdoor units for such system repairs as
a low-cost alternative, it is questionable
whether installation consistently
addresses optimization of the system for
operation at the diminished efficiency
potential of the degraded legacy indoor
unit. Consequently it is expected that
laboratory testing of new models of
unmatched outdoor units significantly
overestimates the efficiency of these
units when paired with old legacy
indoor units in the field. The proposed
maximum NGIFS of the indoor unit to
be used in such a test is in the range of
the values for legacy indoor units, but,
because of the non-optimum field
conditions, choosing a value that is an
average or median for such legacy
indoor units is not representative. Based
on all of these considerations, DOE has
decided to lower the required NGIFS for
the test to 1.0. This level acknowledges
degradation of indoor unit performance
over time, questions regarding
optimization of the indoor/outdoor unit
match and of the installation, and that
the range of indoor units in the field
would also include 10 SEER units. This
value is representative of the 13 SEER
systems of both DOE’s and Ingersoll
Rand’s datasets. DOE notes that the
comments have not shown that this
value is unrepresentative of the
potential indoor unit pairings of nomatch outdoor units. Furthermore,
given that DOE believes this value is
representative and that an NGIFS range
is not a valid approach, DOE does not
believe there is a need for AEDM for
these units.
DOE understands that the type of fin
surface has an impact on coil
performance, as Goodman pointed out
in its comment. Most of the fins of the
evaporator coils of DOE’s dataset were
enhanced, having lanced or louvered
surfaces, so DOE’s assessment has
considered the possibility that the fin
surfaces would be enhanced. DOE
believes that selecting the NGIFS limit
based on enhanced-fin information is
appropriate because any manufacturer
conducting such a test would do so
using an indoor unit that has enhanced
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
fins, which would provide an advantage
to the manufacturers.
DOE notes JCI’s comment that when
an outdoor unit fails, 40% to 50% of the
indoor units would have been rated 13
SEER or higher. This suggests that at
least half would have been rated lower
than 13 SEER. JCI also suggested that
NGIFS might be 0.05 lower for a 10
SEER indoor unit than for 13 SEER. The
Ingersoll Rand comment indicates that
the NGIFS of their HCFC–22 models on
the market prior to the refrigerant’s
phase-out was as low as 0.9784. Since
the 13 SEER standard took effect in
2006, DOE presumes that these units all
had a SEER value no lower than 13.
DOE agrees with JCI that advanced
heat exchanger technology might
improve system efficiency. In particular,
microchannel heat exchangers may
reduce refrigerant charge sufficiently to
reduce degradation of performance
associated with unit cycling. However,
DOE is not convinced that the
expansion devices, be they thermostatic
expansion valves, pistons, or fixedorifice devices, of all legacy indoor units
are replaced with orifices optimized for
the new paired combination using the
intended refrigerant. DOE agrees that a
degradation coefficient less than the
default value may be achievable in a
laboratory test while using a fixed
orifice device, but is not convinced that
this will consistently be achieved with
field-paired combinations. JCI did not
comment on the consistency of the
replacement of the expansion devices in
unmatched outdoor unit installations,
so DOE cannot determine how many
such installations include expansion
devices that are optimized for the
outdoor/indoor unit combination. It is
reasonable to expect that numerous
such installations do not involve
installation of an optimized expansion
device, since unmatched outdoor units
are sold as a low-cost alternative to
purchase of an entirely new system, and
use of the existing expansion device
would also reduce cost. Further, DOE
notes that reduction of the cyclic
degradation coefficient, as proposed in
the November 2015 SNOPR, was based
on the observation that most modern
systems achieve degradation coefficients
well below 0.2. DOE did not intend to
assign this same value as the default for
outdoor units without a match. Based
on the same arguments regarding lack of
optimization of the expansion devices,
DOE does not believe it is appropriate
to adopt the new-test default of 0.2 for
these units and therefore is retaining the
current degradation coefficient for them
at 0.25.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Waiver Process and Change in the
Measurement
Nortek, Goodman, and HARDI
commented that manufacturers who
would like to sell a condensing unit
with no match should request a waiver
from DOE. (Nortek, No. 58 at p. 2;
Goodman, No. 73 at p. 18; HARDI, No.
57 at p. 2)
URI commented that the notice is
silent on how the proposed coil
limitation or NGIFS will improve the
measured energy efficiency of
replacement HCFC–22 condensing units
and that DOE’s view that these units
should have been tested pursuant to a
waiver doesn’t make sense in light of
guidance DOE issued in 2010, 2012, and
2014 . URI separately indicated that
DOE has not clarified whether the test
procedure change will alter the
measurement and/or whether the
standard would have to be adjusted as
required by EPCA. (United
Refrigeration, Inc., No. 60 at p. 6)
In response to Nortek, Goodman, and
HARDI, DOE notes that the waiver
process is a step towards establishing
new procedure provisions in the CFR
that address the test procedure issues
raised by the waiver. In this case, as
mentioned by some commenters, at the
time of publication of the November
2015 SNOPR, there had been no
petitions for waivers for outdoor units
with no match. Test procedure waivers
are not a long-term solution, however.
DOE’s regulations require DOE to
amend its test procedure to address an
issue raised through the waiver process.
Therefore, even though DOE has not
received any petitions for waivers for
outdoor units with no match, DOE has
long recognized the difficulty of
reconciling the current test procedure
language with the reality that
manufacturers have no highest sales
volume combination due to EPA
regulations and proposed a test method
to eliminate the regulatory incongruity
between EPA’s and DOE’s regulations.
DOE is finalizing a test procedure to
eliminate the issue.
In response to URI, DOE
acknowledges that its guidance
document indicated that an individual
condensing unit must meet the current
Federal standard when paired with the
appropriate other new part to make a
system when tested in accordance with
the DOE test procedure and sampling
plan. However, as noted in the
November 2015 SNOPR, generally when
a model cannot be tested in accordance
with the DOE test procedure,
manufacturers must submit a petition
for a test procedure waiver for DOE to
assign an alternative test method.
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
37011
Nothing in the guidance documents
indicated that this would not have been
the case for these units.
In response to URI’s comment
suggesting that measured energy use
must improve under a waiver
procedure, DOE notes that a test
procedure waiver is not intended to
impact measured energy efficiency.
Instead, a test procedure waiver
provides a manufacturer with an
alternative method of test that will yield
results comparable to the test procedure
in the DOE regulations. Test procedures
are not a mechanism to impact the
efficiency of a product, which is why
DOE has carefully evaluated the
characteristics of a paired system so as
to avoid impacting measured efficiency
relative to the current test procedure.
Transition From Coverage Under the
Guidance Documents
URI commented that the test
procedure would effectively end the
manufacture of such components six
months after the revised test procedure
goes into effect. URI contended that it
also would be prohibited from selling or
distributing its existing inventory of
properly certified and rated HCFC–22
replacement condensing units six
months after the effective date because
the notice makes clear that ‘‘any
representations, including compliance
certifications,’’ about the energy cost
and efficiency of replacement
condensing units must be based on the
revised test procedure. (United
Refrigeration, Inc., No. 60 at p. 2)
URI submitted that DOE should
clarify in the preamble and regulatory
text of a final test procedure that the
restriction on representations does not
apply to HCFC–22 condensing units that
were manufactured and certified
pursuant to the preceding DOE
guidance. (United Refrigeration, Inc.,
No. 60 at p. 2)
In a letter to the Secretary of Energy,
Lennox requested DOE to promptly
issue guidance to prevent the entry of
newly designed 14 SEER HCFC–22 drycharge products into the southern and
southwestern regions that do not meet
the requirements of the DOE test
procedure. Lennox commented that
DOE action on these issues is
particularly critical by early 2016, as
manufacturers ramp up production for
the 2016 summer air-conditioning sales
season in that timeframe. (Lennox, No.
61 at p. 2)
Lennox requested DOE include
mechanisms in the final rule to facilitate
a quick and orderly market transition
from legacy dry-shipped outdoor splitsystem central air conditioners and heat
pumps certified to DOE as compliant
E:\FR\FM\08JNR2.SGM
08JNR2
37012
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
that are not rated in accordance with the
test procedure final rule by requiring
manufacturers to discontinue all noncompliant ratings 180 days after the
final rule’s publication. (Lennox, No. 61
at p. 2–3)
JCI recommended that no later than
February 1, 2016, DOE should issue
enforcement guidance stating that DOE
will not seek civil penalties or
injunctive relief for the distribution in
commerce of a dry charged HCFC–22
unit (unit with no match), or for the
labeling requirements of that unit, if the
unit is manufactured prior to a date that
is 30 days after the date of publication
of the enforcement guidance. (JCI, No.
66 at p. 7)
On December 16, 2015, DOE issued an
enforcement policy stating that it would
begin investigating the methods
manufacturers were using to rate splitsystem central air conditioners that do
not have a highest sales volume
combination. Those investigations are
ongoing. DOE also stated that it would
seek civil penalties for violations related
to units manufactured on or after
February 1, 2016, that had not been
tested and properly certified as
compliant with the applicable
standards. As DOE indicated in the
policy statement, DOE will continue to
use its discretion in determining
whether or to what extent penalties are
appropriate, including an evaluation of
a manufacturer’s good faith efforts to
comply with the regulations. DOE notes
that this test procedure final rule does
not have retroactive application;
however, the units at issue have been
subject to the energy conservation
standards and certification requirements
since 2006.
DOE also notes that following the
close of the comment period for the
November 2015 SNOPR, on December 1,
2015, an ex parte meeting occurred
between AHRI, manufacturers, and DOE
regarding outdoor units with no match.
Representatives from Nortek,
Mitsubishi, Carrier, Lennox, Trane,
Rheem, JCI, ADM, Goodman, and Allied
Air attended. During this meeting, the
attendees requested that DOE require
that ratings of existing dry R–22 units
must be discontinued 180 days after the
date of the publication of the amended
test procedure in the Federal Register.
(Docket No. EERE–2009–BT–TP–0004–
0074) This recommendation indicates
that existing ratings for outdoor units
Basic model
asabaliauskas on DSK3SPTVN1PROD with RULES
AB12
AB12
AB12
CD13
CD13
CD13
EF12
EF12
EF12
Individual model # (outdoor unit)
..............................................................
..............................................................
..............................................................
.............................................................
.............................................................
.............................................................
..............................................................
..............................................................
..............................................................
DOE proposed to require that outdoor
unit model numbers cannot span
regions unless the model of outdoor unit
is compliant with all standards in all
possible combinations. If a model of
outdoor unit is certified below a
regional standard, then, under DOE’s
proposal, it must have a unique
individual model number for
distribution in each region. 80 FR at
69290 (Nov. 9, 2015).
For example:
The Joint Advocates of ACEEE, NRDC
and ASAP commented that the
approach proposed by DOE is workable
and provides clear requirements for
OUM rating systems. The Joint
Advocates also commented that
requiring a specific model number for
outdoor units that are certified only in
combinations that meet regional
standard(s), and therefore permitted to
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
ABC**#**–*** .................................................
ABC**#**–*** .................................................
ABC**#**–*** .................................................
CDESO**–*#* ................................................
CDESW**–*#* ...............................................
CDEN***–*#* .................................................
EFCS**#**–*** ...............................................
EFCS**#**–*** ...............................................
EFCN**#**–*** ..............................................
Frm 00022
Fmt 4701
Sfmt 4700
4. Compliance With Federal (National or
Regional) Standards
In the November 2015 SNOPR, DOE
proposed to add requirements to the
relevant provisions of section 430.32
that the least-efficient combination
within each basic model must comply
with the regional SEER and EER
standards. 80 FR 69278, 69290 (Nov. 9,
2015). In addition, as noted in section
III.A.1, DOE proposed that if any
individual combination within a basic
model fails to meet the standard, the
entire basic model (i.e., model of
outdoor unit) must be removed from the
market. In order to clarify the
limitations on sales of models of
outdoor units across regions with
different standards, DOE proposed to
add a limitation in section 429.16 that
any model of outdoor unit that is
certified in a combination that does not
meet all regional standards cannot also
be certified in a combination that meets
the regional standard(s). Further,
Individual model
# (indoor unit)
SO123
SW123
N123
SO123
SW123
N123
SO123
SW123
N123
be installed in those regions, will aid
enforcement. The Joint Advocates also
commented that DOE should clarify the
requirements for ICMs, specifically how
DOE would treat an ICM that attempts
to certify a combination with a rating
below 14 SEER using an outdoor unit
model that otherwise meets 14 SEER in
all combinations certified by the OUM.
(ACEEE, NRDC and ASAP, No. 72 at p.
3)
Based on this comment, DOE adopts
the limitation as proposed, with
wording modifications for clarity. DOE
has not added a limitation on ICMs
certifying a combination below an OUM
represented value, given that such a
value would reflect the performance the
consumer would experience. DOE has
not modified 430.32 in this rulemaking
and will instead do so in the regional
standards enforcement rulemaking.
PO 00000
with no match are invalid and supports
the need for a test procedure as finalized
in this notice. DOE is implementing this
recommendation consistent with EPCA,
as discussed in section III.H.1.
Certified rep.
value (SEER/
EER)
14.5/12.0
15.0/12.8
13.9/11.7
14.5/12.0
15.0/12.8
13.9/11.7
14.5/12.2
14.6/12.4
13.9/11.7
Permitted?
NO.
YES.
YES.
5. Certification Reports
To maximize test repeatability and
reproducibility for assessment and
enforcement testing, DOE proposed a
number of amendments to the
certification reporting requirements. 80
FR 69278, 69290 (Nov. 9, 2015).
Among these requirements, DOE
proposed to clarify what basic model
number and individual model numbers
must be reported for central air
conditioners and heat pumps. 80 FR
69278, 69290–91 (Nov. 9, 2015). DOE
proposed to require the reporting of the
sensible heat ratio (SHR) value
calculated based on full-load cooling
test conditions at the outdoor ambient
conditions: 82 °F dry bulb and 65 °F wet
bulb. 80 FR at 69326 (Nov. 9, 2015).
Finally, DOE also proposed to require
certain product-specific information at
10 CFR 429.16(c)(4) that would not be
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
displayed in DOE’s public database. 80
FR at 69291 (Nov. 9, 2015).
NEEA and NPCC supported DOE’s
proposals for certification reports,
specifically noting the importance that
all combinations of individual model
numbers within a basic model group
can be identified and to identify the
outdoor and indoor mini-split and
multi-split system units that are rated as
combinations. (NEEA and NPCC, No. 64
at p. 3) DOE adopts this provision in the
final rule.
Regarding the basic model provision,
AHRI commented that ICMs should be
required to identify in the certification
report the Similarity Group to which
each indoor unit belongs. (AHRI, No. 70
at p. 5–6) DOE notes that it has adopted
the Similarity Group structure
recommended by AHRI as the basis for
the basic model for ICMs. Hence,
identification of the Similarity Group is
not necessary.
The California IOUs commented that
the proposal to require reporting of SHR
is a good precedent for providing other
data from tests and requested that
results also be reported for all the tests
that are the inputs to calculation of
SEER and HSPF, as well as the results
of the AHRI maximum operational
conditions test.8 (California IOUs, No.
67 at p. 4) On the other hand, AHRI,
Lennox, ADP, UTC/Carrier, JCI,
Goodman, and Nortek believe that SHR
should not be reported as part of a
certification report. (AHRI, No. 70 at p.
10; Lennox, No. 61 at p. 9; ADP, No. 59
at p. 7; UTC/Carrier, No. 62 at p. 8; JCI,
No. 66 at p. 15–16; Goodman, No. 73 at
p. 14; Nortek, No. 58 at p. 7) JCI noted
that the publication of SHR should be
left to the manufacturer as part of their
technical literature, and UTC/Carrier
noted that that information is already
provided in the manufacturer’s product
data. (JCI, No. 66 at p. 12; UTC/Carrier,
No. 62 at p. 7) AHRI, Lennox, ADP,
Goodman, Nortek, and Rheem
commented that the requirement to add
reporting of SHR adds an excessive
burden. (AHRI, No. 70 at p. 10; Lennox,
No. 61 at p. 9; ADP, No. 59 at p. 7;
Goodman, No. 73 at p. 14; Nortek, No.
58 at p. 7: Rheem, No. 69 at p. 8) ADP
further commented that adding a
requirement for SHR is significant for
those OUM and ICM ratings developed
by AEDMs, as manufacturers may not
have this capability in their current
AEDM. (ADP, No. 59 at p. 7) JCI further
commented that the agreement made
between AHRI members and advocates
(presumably referring to the agreement
in advance of the 2011 Direct Final
8 This test is conducted with 115 °F air entering
the outdoor coil, see AHRI 210/240–2008, Table 13.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Rule) was intended to encourage
manufacturers to list SHR in
manufacturer technical literature, not to
make it a certified value. (JCI, No. 66 at
p. 15–16)
After reviewing these comments, DOE
agrees that the joint proposal from
stakeholders that served as the basis for
the 2011 Direct Final Rule regarding
central air conditioners stated that
manufacturers would make the SHR at
82 °F (at the rated airflow) available in
in manufacturer technical literature and
Web sites but that the SHR would not
be verified or certified by AHRI. The
parties agreed that DOE did not need to
take regulatory action to implement this
information sharing. (Docket No. EERE–
2011–BT–STD–0011, No. 16 at p. 7)
DOE did not account for this agreement
in the November 2015 SNOPR, and in
response to stakeholder comment
within this docket, proposed to require
reporting of SHR. However, given the
existing stakeholder agreement that
underlay the 2011 Direct Final Rule,
DOE is not adopting the proposed
requirement to certify SHR.
AHRI, ADP, Lennox, UTC/Carrier,
Ingersoll Rand, JCI, Nortek, Rheem,
Goodman, and Mitsubishi did not
support the additional reporting
requirements proposed by DOE and
commented that they are a significant
burden on manufacturers. (AHRI, No. 70
at p. 13–15; ADP, No. 59 at p. 7; Lennox,
No. 61 at p. 14–15; UTC/Carrier, No. 62
at p. 7; Ingersoll Rand, No. 65 at p. 12;
JCI, No. 66 at p. 15; Nortek, No. 58 at
p. 11; Rheem, No. 69 at p. 7; Goodman,
No. 73 at p. 14, 19; Mitsubishi, No. 68
at p. 2–3) AHRI, Lennox, UTC/Carrier,
Nortek, JCI, Rheem, Goodman, and
Mitsubishi also commented that some of
the required data is proprietary and puts
the manufacturer at risk. (AHRI, No. 70
at p. 13–15; Lennox, No. 61 at p. 14–15;
UTC/Carrier, No. 62 at p. 7; Nortek, No.
58 at p. 11; JCI, No. 66 at p. 12; Rheem,
No. 69 at p. 7; Goodman, No. 73 at p.
14, 19; Mitsubishi, No. 68 at p. 2) JCI
and Mitsubishi expressed concern that
confidential information could be
revealed in a FOIA request. (JCI, No. 66
at p. 12; Mitsubishi, No. 68 at p. 2)
AHRI and Lennox each provided a list
of information that they support DOE
requiring. (AHRI, No. 70 at p. 13–14;
Lennox, No. 61 at p. 14–15) Unico
agreed in its comments with AHRI’s
position on the reporting burden
associated with the certification
reporting requirements. (Unico, No. 63
at p. 6) Nortek commented that it
supports DOE requiring information that
is already being submitted to AHRI for
purposes of certification. (Nortek, No.
58 at p. 10–11) Mitsubishi commented
that manufacturers should not be
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
37013
required to provide any physical
information that is not needed to test
the system. (Mitsubishi, No. 68 at p. 3)
JCI commented that the only additional
reporting information that should be
added to the certification report is the
off mode standby metric, and that no
other unregulated items should be
added. (JCI, No. 66 at p. 12)
Some stakeholders listed specific
information that DOE should not require
manufacturers to report. AHRI, Rheem,
and JCI commented that DOE should not
require manufacturers to report the
orientation of a product’s indoor coils
and that, rather than reporting the
process for manually entering the
defrost cycle to DOE, manufacturers
should describe that process in the
product instructions. (AHRI, No. 70 at p.
13; Rheem, No. 69 at p. 7–8; JCI, No. 66
at p. 12) AHRI commented that for
variable speed products, compressor
frequency set points are proprietary to
the manufacturer and therefore should
not be reported to DOE. (AHRI, No. 70
at p. 15) Rheem commented that
variable speed heat pump minimum and
maximum speed blocks are proprietary
and therefore should not be reported.
(Rheem, No. 69 at p. 7–8) Goodman
commented that their product
nameplates do not explicitly state
nominal capacity, nor do the majority of
their competitors’ products. Goodman
recommended that the manufacturer
provide the specific model numbers of
the indoor unit tested rather than
nominal capacity of each indoor unit.
(Goodman, No. 73 at p. 6) Goodman also
suggested that, instead of requiring
manufacturers to solely report the
general type of expansion device, DOE
should require that manufacturers
submit the same information (for fixed
orifices, the orifice inside dimension
(I.D.) and length; or, for expansion
valves, the part number or model
number) manufacturers currently
submit to AHRI for each individual
combination of a split-system air
conditioner or split-system heat pump.
(Goodman, No. 73 at p. 3–5)
Rheem commented that the addition
of the requirement to certify airflow and
CD is a significant certification burden
on manufacturers. Rheem noted that the
documentation of the values measured
during the test of a single sample cannot
be applied to a second test, and that the
averages of multiple measured values
are even less applicable. Rheem stated
that the certification of CD requires that
manufacturers provide a conservative
value that would be applied to multiple
test samples. Rheem suggested that the
certification of a product should be
based on actual product performance, as
the use of a certified value of CD would
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37014
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
increase the variability of the test
procedure and require more
conservative ratings and redesign of
minimum efficiency equipment.
(Rheem, No. 69 at p. 7)
After reviewing the stakeholders’
comments, DOE maintains that the
certification reporting requirements
proposed in the November 2015
SNOPR, except for SHR as previously
discussed, are necessary for DOE to be
able to conduct testing. None of the
commenters indicated how DOE could
properly conduct testing without the
requested information. In the November
2015 NOPR, DOE proposed that this
information would not be made
available on the DOE public Web site.
While the information may be subject to
Freedom of Information Act (FOIA),
DOE will seek to protect this
information to the extent legally
permissible.
For these reasons, DOE has adopted
these requirements in the final rule,
with minor modifications as discussed
in relevant sections. In response to
Goodman, DOE notes that the model
numbers of indoor units are required in
addition to nominal capacity, which is
needed to verify appropriate unit
selection used for certification testing.
DOE also declines to require additional
information beyond the type of
expansion device, as DOE does not need
this information to conduct testing. In
response to Rheem, as noted in section
III.A.7, DOE is only requiring
manufacturers to report whether they
used a default value for CD or whether
they conducted the optional test;
manufacturers do not have to report the
CD value used.
In their comments, the California
IOUs requested that DOE require the
reporting of all test results that are
inputs to the calculation of SEER and
HSPF. In addition, they requested that
DOE collect the results of the AHRI
Maximum Operational Conditions tests,
which they acknowledge would require
adding these tests to Appendix M/M1.
As in the case of SHR, they argued that
this would not add to the test burden;
it would only add the additional
reporting of results, because all the
measurements required to calculate SHR
(e.g., indoor air flow and indoor
entering and leaving air conditions) are
required as part of the current test. The
California IOUs argued that consumers,
incentive programs, and energy
efficiency building codes need to have
SEER and HSPF values that are
calculated for specific climatic regions
to enhance the value of the published
SEER and HSPF that are calculated for
climatic region 4. They said this would
support the fair comparison of system
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
performance and annual energy use
costs. (California IOUs, No. 67 at p. 3–
4)
In this final rule, DOE declines to add
the additional reporting requirements
recommended by the California IOUs as
these are not necessary for DOE testing,
and existing programs currently operate
without the additional detail requested.
6. Represented Values
In the November 2015 SNOPR, DOE
proposed to make several additions to
the represented value requirements in
10 CFR 429.16. First, DOE proposed
adding a requirement that the
represented values of cooling capacity,
heating capacity, and sensible heat ratio
(SHR) must be the mean of the values
measured for the sample. Second, DOE
proposed to move the provisions
currently in 10 CFR 430.23 regarding
calculations of various measures of
energy efficiency and consumption for
central air conditioners to 10 CFR
429.16. DOE proposed minor changes to
the calculations of annual operating cost
to address other changes proposed in
Appendix M. 80 FR 69278, 69291 (Nov.
9, 2015).
Lennox, ADP, and UTC/Carrier
commented that SHR is currently
published by manufacturers and that
there is no benefit to adding a single
point SHR as a represented value
potentially subject to enforcement.
(Lennox, No. 61 at p. 9; ADP, No. 59 at
p. 7; UTC/Carrier, No. 62 at p. 8) On the
other hand, Unico supported the
requirement to submit SHR but only for
reporting purposes, not for testing and
enforcement. (Unico, No. 63 at p. 6)
Although DOE has determined that
manufacturers should not be required to
report SHR (see section III.A.5), DOE is
adopting requirements on the
represented values for SHR as proposed,
in order to generate consistency in any
representations of SHR made by
industry.
AHRI, Lennox, JCI, Ingersoll Rand,
Goodman, UTC/Carrier, and Nortek
disagreed with the requirement that the
represented capacity values must be the
mean of the tested values, and
recommended that DOE allow
manufacturers to rate capacity
conservatively. (AHRI, No. 70 at p. 10;
Lennox, No. 61 at p. 8, 15; JCI, No. 66
at p. 15–16; Ingersoll Rand, No. 65 at p.
5; Goodman, No. 73 at p. 15; UTC/
Carrier, No. 62 at p. 8; Nortek, No. 58
at p. 6) Rheem similarly commented
that the addition of the requirement to
certify cooling capacity and heating
capacity is a significant certification
burden and does not allow for
manufacturers to rate capacity
conservatively. (Rheem, No. 69 at p. 8)
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
Nortek commented that DOE’s proposal
adds significant and unnecessary
increased risk to a manufacturer due to
increased exposure from enforcement
testing. (Nortek, No. 58 at p. 6)
In its comments, Goodman noted that
there is variability from sample to
sample in any population of units.
(Goodman, No. 73 at p. 15) Lennox
commented that DOE’s proposed use of
mean values adds unnecessary risk and
complexity in associated voluntary
industry certification programs (VICP),
such as AHRI. Lennox commented that
manufacturers face stringent penalties
through the AHRI VCIP program in the
event of failure, and that manufacturers
manage their financial and market risk
through conservative ratings. Although
DOE and VICPs may have different
parameters for capacity metrics, Lennox
believed DOE’s proposal adds
unnecessary complexity, which may
confuse the consumer and bring into
question the validity of different
represented capacity values in the VICP
program versus the DOE CCMS value.
(Lennox, No. 61 at p. 8–9)
AHRI, Lennox, and JCI disagreed with
DOE’s proposal, stating that eliminating
the conservative rating capacity would
impact current ratings, which would
require re-rating products. They
contended that this requirement
represents a significant and unnecessary
burden that has no value to the
consumer. (AHRI, No. 70 at p. 10;
Lennox, No. 61 at p. 8; JCI, No. 66 at p.
7)
Several commenters recommended
alternatives to DOE’s proposal. Ingersoll
Rand recommended that the average
capacity on which to base the
appropriate standard be determined
using the same statistical method as
used for determining SEER, but that the
manufacturers be allowed to claim up to
5 percent lower in their rating. (Ingersoll
Rand, No. 65 at p. 5) UTC/Carrier
commented that the current procedure
of using the mean or the statistically
adjusted mean should be used and
manufacturers should be able to de-rate
the certified values as necessary to
account for testing uncertainties in the
audit facility as well as the
manufacturer’s test facility. (UTC/
Carrier, No. 62 at p. 8) AHRI and Nortek
commented that instead of
implementing the mean of measured
values for capacity, any represented
value of the energy efficiency or other
measure of energy consumption for
which consumers would favor higher
values should be less than or equal to
the lower of: (1) The mean of the
sample, or (2) the lower 90 percent
confidence limit (LCL) of the true mean
divided by 0.95. (AHRI, No. 70 at p. 10;
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
Nortek, No. 58 at p. 6–7) DOE
understands that AHRI and Nortek
supported DOE applying this approach
to capacity as well.
After reviewing the comments, DOE is
updating its proposal from the
November 2015 SNOPR, which required
represented values of cooling and
heating capacity to be the mean of the
sample. In this Final Rule, DOE is
requiring the represented value of
cooling (or heating) capacity to be a selfdeclared value that is no less than 95
percent of the mean of the cooling (or
heating) capacities measured for the
units in the sample selected for testing.
This will allow manufacturers the
flexibility to derate capacity with
conservative values as requested by
multiple commenters, while still
providing consumers with information
that is reasonably close to the
performance they may expect when
purchasing a system.
Goodman commented that DOE
provided no guidance on how to treat
systems rated by AEDM and that it is
unreasonable to expect manufacturers to
always rate at the exact value developed
by a computer program. (Goodman, No.
73 at p. 15)
DOE agrees with Goodman. DOE’s
intent had been for represented values
for systems rated by testing or AEDM to
be determined similarly but had
inadvertently left this requirement out
of the AEDM portion of the regulatory
text. To parallel the provision adopted
for tested combinations, DOE is
adopting a provision that the
represented value of cooling (or heating)
capacity must be no less than 95% of
the cooling (or heating) capacity output
simulated by the AEDM. DOE notes
that, if a manufacturer believes the
capacity predicted by the AEDM is more
than 5% off of what the manufacturer
would otherwise expect, then the
manufacturer should be evaluating the
validity of the AEDM in other respects.
Finally, DOE notes that Annual
Performance Factor (APF) is not used
for any regulatory program, and
therefore DOE has removed all
calculations and represented value
requirements for APF in this final rule.
7. Product-Specific Enforcement
Provisions
In the November 2015 SNOPR, DOE
proposed to verify certified cooling
capacity during assessment or
enforcement testing. DOE proposed to
measure the cooling capacity of each
tested unit pursuant to the test
requirements of 10 CFR part 430. If the
measurement is within five percent of
the certified cooling capacity, DOE
would use the certified cooling capacity
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
as the basis for determining SEER.
Otherwise, DOE would use the
measured cooling capacity as the basis
for determining SEER. 80 FR 69278,
69292 (Nov. 9, 2015).
DOE also proposed to require
manufacturers to report the cyclic
degradation coefficient (CD) value used
to determine efficiency ratings. DOE
proposed to run CD testing as part of any
assessment or verification testing,
except when testing an outdoor unit
with no match. If the measurement is
0.02 or more greater than the certified
value, DOE would use the measurement
as the basis for calculation of SEER or
HSPF. Otherwise, DOE would use the
certified value. For models of outdoor
units with no match, DOE would always
use the default value. 80 FR 69278,
69292 (Nov. 9, 2015).
Lennox, UTC/Carrier, Rheem, and JCI
disagreed with DOE’s proposal to use
rated values in cooling capacity and in
CD testing. The commenters proposed
that tested capacity and cyclic test
values should be used in all
determinations of efficiency and
compliance. (Lennox, No. 61 at p. 9;
UTC/Carrier, No. 62 at p. 8; Rheem, No.
69 at p. 2; JCI, No. 66 at p. 8) Rheem
commented that the proposal to enforce
SEER using certified values of cooling
capacity and CD has not been justified
or shown to provide representative and
repeatable results. (Rheem, No. 69 at p.
8) Unico supported the requirement to
submit cooling capacity and heating
capacity but only for reporting
purposes, not for testing and
enforcement. (Unico, No. 63 at p. 6)
In its comments, Lennox explained
that, given the variability in component
and manufacturing processes, product
capacity and power can vary slightly
from unit to unit. According to Lennox,
if products are manufactured within the
acceptable limits, the variations in
capacity and power tend to be linear.
Lennox added that DOE’s proposal to fix
capacity to the rated value in
determining efficiency if measured
within five percent of rating while
allowing power to be a variable from the
tested value can result in both false pass
and fail results. (Lennox, No. 61 at p. 9–
10) Lennox also commented that cyclic
CD testing is prone to variation from test
to test on the same unit within the same
facility—let alone lab to lab, and that
the industry has spent a tremendous
amount of resources studying variability
issues and has developed
recommendations for lab improvement.
In particular, Lennox commented, the
industry has developed a method for
compensating for differences in thermal
mass of the test facility used for testing.
(Lennox, No. 61 at p. 10)
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
37015
Nortek and JCI commented that the
proposal to use a tolerance to determine
if measured capacity is within 5 percent
of rated capacity and from there,
determining efficiency, would make it
necessary for manufacturers to report
capacity at all points necessary to
determine SEER and HSPF. (Nortek, No.
58 at p. 7; JCI, No. 66 at p. 7–8) JCI
commented that this is an increased
burden of reporting without additional
value. (JCI, No. 66 at p. 7–8) In addition
to this burden, Nortek expressed
concern that this could lead to
overrating capacity. As efficiency is not
tied to capacity, Nortek stated it is
unsure of the purpose of this proposal
and would like DOE to clarify the
purpose. (Nortek, No. 58 at p. 7)
Goodman commented that DOE’s
proposal to use certified rather than
tested values conflicts with DOE’s
acknowledgement that individual unit
performance varies from sample to
sample due to both individual unit
production differences as well as testing
differences. Goodman noted that
compressor suppliers would only certify
the performance of their product to
manufacturers to a ±5% tolerance.
Goodman commented that from a
statistics perspective, it is not correct to
suggest that in order to determine the
true mean of a population that modified
values would be used from actual
measurements. Goodman strongly
opposed DOE’s proposed regulatory
language in reference to the assessment
and enforcement testing of HVAC
products as it pertains to assumed
average performance values in the
determination of the performance of an
individual unit. Goodman strongly
suggested that DOE omit the proposed
10 CFR 429.134(g) in its entirety.
(Goodman, No. 73 at p. 21)
After reviewing the comments, DOE is
adopting modifications from its
proposal. For cooling capacity, DOE will
use the mean of any DOE test
measurements to determine SEER. DOE
notes that this adopted modification, by
eliminating the comparison to the
manufacturer’s represented value,
addresses JCI’s concern about additional
reporting burden and Goodman’s
concern about using modified (certified)
values rather than actual measurements.
In addition, DOE’s modification related
to the represented value for capacity, in
section III.A.6, addresses Nortek’s
concern about overrating.
In addition, DOE wishes to clarify that
when calculating SEER values,
manufacturers must use the tested
capacity value, not the certified capacity
value.
For the CD value, in section III.E.11,
based on stakeholder comments, DOE
E:\FR\FM\08JNR2.SGM
08JNR2
37016
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
has decided to allow manufacturers to
use the default value without testing.
The default value is conservative, and
DOE believes that manufacturers will
only opt to test if it will improve upon
the default value for that model. DOE
will follow the lead of the manufacturer
in determining whether to use the
default value or to test a given unit.
Therefore, instead of reporting the CD
value used, the manufacturer must
report whether the optional tests were
conducted to determine the CD value or
whether the default value was used. If
manufacturers report using the default
value, DOE will also use the default
value. If manufacturers conduct
optional testing, DOE will also conduct
testing to determine CD. The result for
each unit tested (either the tested value
or the default value, as selected
according to the criteria for the cyclic
test in 10 CFR part 430, subpart B,
Appendix M, section 3.5e) will be used
to determine the applicable standards
for purposes of compliance.
asabaliauskas on DSK3SPTVN1PROD with RULES
B. Alternative Efficiency Determination
Methods
1. General Background
For certain consumer products and
commercial equipment, DOE’s existing
regulations allow the use of an
alternative efficiency determination
method (AEDM) or alternative rating
method (ARM), in lieu of actual testing,
to estimate the ratings of energy
consumption or efficiency of basic
models by simulating their energy
consumption or efficiency at the test
conditions required by the applicable
DOE test procedure. The simulation
method permitted by DOE for use in
rating split-system central air
conditioners and heat pumps, in
accordance with 10 CFR 429.70(e), is
referred to as an ARM. In contrast to an
AEDM, an ARM must be approved by
DOE prior to its use.
DOE published a Notice of Proposed
Rulemaking (AEDM NOPR) in the
Federal Register on May 31, 2012. 77
FR 32038. In the AEDM NOPR, DOE
proposed the elimination of ARMs, and
the expansion of AEDM applicability to
those products for which DOE allowed
the use of an ARM (i.e., split-system
central air conditioners and heat
pumps). 77 FR at 32055. Furthermore,
DOE proposed a number of
requirements that manufacturers must
meet in order to use an AEDM, as well
as a method that DOE would employ to
determine if an AEDM was used
appropriately along with specific
consequences for misuse of an AEDM.
77 FR at 32055–56. DOE subsequently
published a final rule, related to
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
commercial HVAC equipment only, on
December 31, 2013 (78 FR 79579).
In the November 2015 SNOPR, DOE
proposed modifications to the central
air conditioner and heat pump AEDM
requirements that were proposed in the
AEDM NOPR. 80 FR 69278, 69292 (Nov.
9, 2015). In response to DOE’s proposal,
AHRI, Nortek, and Ingersoll Rand
recommended that DOE align the CAC/
HP AEDM proposal with commercial
equipment AEDM provisions because
the commercial and residential
technologies, testing methods, and
simulation approaches were nearly
identical. (AHRI, No. 70 at p. 9; Nortek,
No. 58 at p. 5; Ingersoll Rand, No. 65 at
p. 11)
In response to that comment, DOE
notes that its proposal was based off the
commercial equipment AEDM
provisions with slight modifications
appropriate to the residential product,
and as such declines to make the AEDM
provisions identical to those for
commercial equipment. However,
revisions to specific aspects of the
proposal based on stakeholder
comments are discussed in subsequent
sections.
First Co. commented that the DOE’s
proposed modifications in the
November 2015 SNOPR require
manufacturers to develop an AEDM for
heat pumps. First Co. noted that any
AEDMs used by an ICM to rate systems
would require coefficient data from the
OUM, which is not required to be
publicly disclosed and which is not
currently available to ICMs. First Co.
commented that this issue must be
addressed in the rule. (First Co., No. 56
at p. 1)
In response to First Co.’s comment,
DOE notes that its proposal in the
November 2015 SNOPR did not require
use of an AEDM. 80 FR 69278, 69292
(Nov. 9, 2015). Manufacturers may
choose to test all individual
combinations within a basic model
rather than applying an AEDM.
Therefore, DOE has not made any
changes to its proposal in response to
First Co.’s concerns.
AHRI, ADP, Mortex, and Lennox
commented that, for ICMs, certified
ratings must be less than or equal to
AEDM output. (AHRI, No. 70 at p. 5–6;
ADP, No. 59 at p. 2–3; Mortex, No. 71
at p. 4–6; Lennox, No. 61 at p. 5)
In response, DOE notes that in 10 CFR
429.16, DOE adopted the requirement
that represented values of efficiency
must be less than or equal to the output
of the AEDM, while represented values
of power must be greater than or equal
to the output of the AEDM. In addition,
under 10 CFR 429.70(a), represented
values must never be ‘‘better’’ (overrate
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
efficiency or underrate consumption)
than the output of the AEDM. These
requirements apply to all
manufacturers, not just ICMs.
2. Terminology
In the AEDM NOPR, DOE proposed to
eliminate the term ‘‘alternate rating
method’’ (ARM) and instead use the
term ‘‘alternative efficiency
determination method’’ (AEDM) to refer
to any modeling technique used to rate
and certify covered products. 77 FR
32038, 32040 (May 31, 2012). In the
November 2015 SNOPR, DOE continued
to propose the use of one term, AEDM,
to refer to all modeling techniques used
to develop certified ratings of covered
products. 80 FR 69278, 69293 (Nov. 9,
2015).
Lennox, Goodman, Ingersoll Rand,
and AHRI supported DOE’s proposal to
eliminate the term ‘‘ARM’’ and instead
use the term ‘‘AEDM.’’ (Lennox, No. 61
at p. 7; Goodman, No. 73 at p. 7;
Ingersoll Rand, No. 65 at p. 11; AHRI,
No. 70 at p. 9) There, DOE has
eliminated the term ‘‘ARM’’ in this final
rule, using only ‘‘AEDM.’’
3. Elimination of the Pre-Approval
Requirement
In the November 2015 SNOPR, DOE
proposed to eliminate the pre-approval
process for ARMs for split-system
central air conditioners and heat pumps.
In lieu of this, DOE also proposed that
manufacturers may only apply an
AEDM if it (1) is derived from a
mathematical model that estimates
performance as measured by the
applicable DOE test procedure; and (2)
has been validated with individual
combinations that meet current Federal
energy conservation standards (as
discussed in the next section).
Furthermore, DOE proposed records
retention requirements and additional
manufacturer requirements to permit
DOE to audit AEDMs through
simulations, review of data and
analyses, and/or certification testing. 80
FR 69278, 69294 (Nov. 9, 2015).
Lennox agreed that elimination of the
pre-approval for AEDMs could reduce
time to market, facilitate innovation,
and eliminate the time required to
complete the approval process. (Lennox,
No. 61 at p. 7) In this final rule, DOE
has eliminated the pre-approval
requirement as proposed in the
November 2015 SNOPR.
4. AEDM Validation
a. Outdoor Unit Manufacturers
In the November 2015 SNOPR, DOE
noted that in its proposed revisions to
the determination of certified ratings for
central air conditioners and heat pumps,
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
manufacturers must test each basic
model. Specifically for split-system air
conditioners and heat pumps, OUMs
must test each model of outdoor unit
with at least one model of indoor unit
(highest sales volume). Manufacturers
would only be able to use AEDMs for
other individual combinations within
the same basic model—in other words,
other combinations of models of indoor
units with the same model of outdoor
unit. In the November 2015 SNOPR,
DOE did not seek to require additional
testing to validate an AEDM beyond
what is proposed under 10 CFR
429.16(a)(1)(ii). 80 FR 69278, 69294
(Nov. 9, 2015).
DOE also proposed in the November
2015 SNOPR to adopt test requirements
similar to those used for AEDM
validation for commercial HVAC and
water heating equipment, as published
in the AEDM final rule 78 FR 79579,
79584 (Dec. 31, 2013). Specifically, DOE
proposed that (1) for energy-efficiency
metrics, the predicted efficiency using
the AEDM may not be more than 3
percent greater than that determined
through testing; (2) for energy
consumption metrics, the predicted
efficiency using the AEDM may not be
more than 3 percent less than that
determined through testing; and (3) the
predicted efficiency or consumption for
each individual combination calculated
using the AEDM must comply with the
applicable Federal energy conservation
standard. Furthermore, the test results
used to validate the AEDM must meet
or exceed the applicable Federal
standards, and the test must have been
performed in accordance with the
applicable DOE test procedure. If DOE
has ordered the use of an alternative test
method for a particular basic model
through the issuance of a waiver, that
alternative test method should apply in
lieu of the DOE test procedure. 80 FR
69278, 69296 (Nov. 9, 2015).
In the November 2015 SNOPR, DOE
proposed a validation tolerance of 3
percent for AEDMs because the
variability in a manufacturer’s lab and
within a basic model should be more
limited than lab-to-lab variability. DOE
proposed tolerances for verification
testing of 5 percent to account for added
lab-to-lab variability. 80 FR 69278,
69296 (Nov. 9, 2015).
ADP, Lennox, UTC/Carrier, Rheem,
and Unico agreed with DOE’s proposal
to not require additional testing to
validate an AEDM beyond the testing
required under 429.16(a)(2)(ii) for splitsystem air conditioners and heat pumps
where manufacturers must test each
basic model—that is, each model of
outdoor unit with at least one model of
HSV indoor unit. (ADP, No. 59 at p. 7;
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Lennox, No. 61 at p. 15; UTC/Carrier,
No. 62 at p. 8; Rheem, No. 69 at p. 8;
Unico, No. 63 at p. 6)
Unico commented that single-split
systems manufactured and rated by an
OUM should continue to validate their
AEDM using the HSVC measured
results. (Unico, No. 63 at p. 6) The
California IOUs commented that it is
critical that an AEDM be validated fully
and in a manner that allows DOE to use
lab-testing data to disallow an AEDM if
it is inaccurate. (California IOUs, No. 67
at p. 4)
Lennox, JCI, AHRI, First Co., Ingersoll
Rand, UTC/Carrier, Rheem, and Nortek
recommended that DOE align the CAC/
HP AEDM validation tolerance proposal
with commercial equipment AEDM
provisions of 5 percent. (Lennox, No. 61
at p. 8; JCI, No. 66 at pp. 3–4; AHRI, No.
70 at p. 9; First Co., No. 56 at p. 2;
Ingersoll Rand, No. 65 at p. 11; UTC/
Carrier, No. 62 at p. 8; Rheem, No. 69
at p. 2; Nortek, No. 58 at p. 5) AHRI,
Lennox, JCI, and Nortek further
commented that lab variability is an
inherent part of the testing process
regardless of whether all testing is
conducted in a manufacturer’s lab or
lab-to-lab. They asserted that the
fundamental issue is that HVAC
equipment relies on accurate air
property measurements (wet bulb/dew
point) and the variability of the test
alone is greater than five percent.
(AHRI, No. 70 at p. 9; Nortek, No. 58 at
p. 5; JCI, No. 66 at pp. 3–4; Lennox, No.
61 at p. 8) AHRI and Nortek also
commented that it is crucial that
manufacturers be permitted to apply the
AEDM across basic models in order to
align the CAC/HP AEDM validation
tolerance with the commercial
equipment AEDM provisions. (AHRI,
No. 70 at p. 9; Nortek, No. 58 at p. 5)
Given the support in the comments
related to AEDM validation for OUMs,
DOE maintains its proposal to not
require any additional testing to validate
an AEDM beyond that required for
certification. DOE notes that while the
proposal applied to split systems only,
in this final rule, it applies to singlepackage systems as well. After
reviewing the comments, DOE has
adopted a validation tolerance of 4%
rather than the proposed 3%. DOE notes
that manufacturers did not provide
evidence of the comparison of withinlab variability to lab-to-lab variability
nor did they request a higher
verification tolerance, indicating that a
5% tolerance appropriately captures
lab-to-lab variability. In addition, DOE
notes that in its own enforcement
testing, it obtains results within 3%. For
these reasons, DOE believes that a
validation tolerance of 4% balances the
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
37017
manufacturers’ concerns regarding
within-lab variability with the
understanding that such variability is by
nature less than lab-to-lab variability
and with DOE’s own experience with
such testing variability. In response to
AHRI and Nortek’s additional comment,
while at least one individual model or
combination within each basic model
must be tested, DOE did not propose
that AEDMs be specific to basic models;
they can be applied across basic models.
b. Independent Coil Manufacturers
In the November 2015 SNOPR, DOE
noted that in its proposed revisions to
the determination of certified ratings for
central air conditioners and heat pumps,
ICMs must test each model of indoor
unit with at least one model of outdoor
unit (lowest SEER). Manufacturers
would only be able to use AEDMs for
other individual combinations within
the same basic model. Additionally,
DOE did not require additional testing
to validate an AEDM beyond that
proposed to be required to determine
the certified ratings. 80 FR 69278, 69294
(Nov. 9, 2015). DOE also proposed the
same additional test requirements for
ICMs as for OUMs, as discussed in the
previous section. 80 FR 69278, 69296
(Nov. 9, 2015).
Rheem commented that ICMs should
validate their AEDMs in the same
manner as an OUM. Rheem agreed that
ICM ratings would improve when
indoor units are tested with outdoor
units. Rheem further commented that
ICM ratings would also improve when
a particular indoor coil is tested with
multiple outdoor units of different
capacities and that the process should
properly consider what effects
refrigerant mass flow variations across
tonnages have on the performance of a
single indoor unit. (Rheem, No. 69 at p.
8) UTC/Carrier also supported DOE’s
proposal and appreciates DOE for
closing what it perceived as a loophole
in the current regulations and requiring
ICMs to test in a similar fashion to
OUMs. (UTC/Carrier, No. 62 at p. 9)
On the other hand, Unico commented
that DOE should replace the term ‘‘basic
model’’ with ‘‘Similarity Group,’’
essentially requiring AEDM validation
based on the testing requirements for a
Similarity Group. (Unico, No. 63 at p. 6)
As discussed in section III.A.3.d, AHRI,
ADP, Mortex, and Lennox
recommended that, to validate an
AEDM, an ICM (1) test and rate at least
one combination per Similarity Group
with an outdoor unit with the lowest
SEER that complies with standard; (2)
perform at least one full-system test per
Similarity Group; (3) if rating HP
combinations, test one-third of
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37018
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Similarity Groups with HP systems in
both heating and cooling modes; and (4)
if an ICM has only one Similarity
Group, the manufacturer must test a
minimum of two combinations to
validate the AEDM. (AHRI, No. 70 at p.
5–6; ADP, No. 59 at p. 2–3; Mortex, No.
71 at p. 4–6; Lennox, No. 61 at p. 5)
AHRI, ADP, Mortex, and Lennox
suggested that for ICMs to validate an
AEDM, test results should be required to
be more than five percent below output
from the AEDM. The commenters noted
that DOE has proposed three percent on
the supposition that a manufacturer’s
lab will have less variation, but that
many ICMs do not have labs and will
rely on external labs for testing and that
there is no basis to suggest that the
testing variation will be significantly
different between testing commercial
and consumer products. (AHRI, No. 70
at p. 5–6; ADP, No. 59 at p. 2–3; Mortex,
No. 71 at p. 4–6; Lennox, No. 61 at p.
5)
AHRI, ADP, Mortex, and Lennox also
suggested that ICMs only be permitted
to rate basic models within Similarity
Groups validated by a tested
combination. (AHRI, No. 70 at p. 5–6;
ADP, No. 59 at p. 2–3; Mortex, No. 71
at p. 4–6; Lennox, No. 61 at p. 5)
As discussed in section III.A.3.d, DOE
is adopting the suggested Similarity
Group requirements as the basic model
definition for ICMs and is requiring
testing of one combination per basic
model (with the exception of heat
pumps) according to the sampling plan
in 429.16. With these changes, DOE
believes that the testing requirements
for certification remain sufficient for
validating an AEDM. In addition, DOE
believes that the additional
requirements on test data used for
validation address AHRI’s concern
regarding a need for additional testing
for ICMs with only a single Similarity
Group. Therefore DOE is not requiring
ICMs to conduct any additional testing
for AEDM validation beyond that
required for certification.
Furthermore, after reviewing these
comments, DOE has adopted a
validation tolerance of four percent
rather than the proposed 3 percent, for
ICMs as well as OUMs.
In response to AHRI, ADP, Mortex,
and Lennox, DOE notes that the request
that ICMs only be permitted to rate basic
models within Similarity Groups
validated by a tested combination is
consistent with its adopted
requirements regarding use and
validation of AEDMs, although in the
adopted framework, manufacturers may
only use AEDMs to rate individual
combinations within basic models
validated by a tested combination.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
5. AEDM Verification Testing
DOE may randomly select and test a
single unit of a basic model pursuant to
10 CFR 429.104. This authority extends
to all DOE covered products, including
those certified using an AEDM. In
conducting enforcement testing, DOE
tests a retail unit or a unit provided by
the manufacturer if a retail unit is not
available. 10 CFR 429.110(c). A selected
unit is tested using the applicable DOE
test procedure at an independent, thirdparty laboratory accredited to the
International Organization for
Standardization (ISO)/International
Electrotechnical Commission (IEC),
‘‘General requirements for the
competence of testing and calibration
laboratories,’’ ISO/IEC 17025:2005E. 10
CFR 429.110(a). DOE may conduct
testing at an independent, third-party
testing facility or a manufacturer’s
facility upon DOE’s request if the former
is not capable of testing such a unit. 10
CFR 429.110(a).
In the November 2015 SNOPR DOE
explained that verification testing
conducted by DOE is conducted with no
communication between the lab and the
manufacturer without DOE
authorization. 80 FR 69278, 69296 (Nov.
9, 2015). Thus, DOE proposed a method
for determining that a combination rated
using an AEDM does not meet its
certified rating. Specifically, DOE
proposed that an individual
combination would be considered as
having not met its certified rating if,
even after applying the five percent
tolerance between the test results and
the rating as specified in the proposed
10 CFR 429.70(e)(5)(vi), the test results
indicate the individual combination
being tested is less efficient or consumes
more energy than indicated by its
certified rating. DOE noted that this
approach will not penalize
manufacturers for applying conservative
ratings to their products. That is, if the
test results indicate that the individual
combination being tested is more
efficient or consumes less energy than
indicated by its certified rating, DOE
would consider that individual
combination to meet its certified rating.
80 FR 69278, 69296 (Nov. 9, 2015).
In the November 2015 SNOPR, DOE
also proposed providing manufacturers
with a test report that includes a
description of test set-up, test
conditions, and test results when an
individual combination rated using an
AEDM fails to meet the certified rating.
Under this proposal, DOE would also
provide the manufacturer with an
opportunity to respond to the lab report
by presenting all claims regarding
testing validity, and if the manufacturer
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
was not on-site for initial set-up, to
purchase an additional unit from retail
to test following the requirements in
429.110(a)(3). Under the proposed
procedure, DOE would consider any
response offered by the manufacturer
within a designated time frame before
deciding upon the validity of the test
results. Only after considering the
manufacturer’s response and
determining it to be unsatisfactory
would DOE declare the manufacturer’s
rating for the basic model invalid and
require the manufacturer to take
subsequent action, as described in
section III.B.6. 80 FR 69278, 69297
(Nov. 9, 2015).
AHRI and Nortek commented that
DOE’s proposal was unclear regarding
the difference between AEDM
validation testing and verification
testing. (AHRI, No. 70 at p. 9; Nortek,
No. 58 at p. 5) In response, DOE notes
that manufacturers must conduct
validation testing in order to use an
AEDM to determine represented values
and to certify compliance to DOE. DOE
may conduct AEDM verification testing
to verify the validity of an AEDM.
ADP, Lennox, UTC/Carrier, and Unico
agreed with DOE’s proposal that
manufacturers should not be penalized
for being conservative in their ratings
for any of the metrics. They stated that,
given the testing uncertainties,
manufacturing variation, etc.,
manufacturers need to be conservative
to ensure their product performs at the
rated level. (ADP, No. 59 at p. 8;
Lennox, No. 61 at p. 15; UTC/Carrier,
No. 62 at p. 9; Unico, No. 63 at p. 7)
Rheem also agreed with the proposal to
allow conservative ratings. (Rheem, No.
69 at p. 9)
JCI and Lennox commented that there
appears to be a typographical error on
(5) AEDM Verification Testing. (v)
Tolerance. The text shows ‘‘For
efficiency metrics, the result from a DOE
verification test must be greater than or
equal to 1.05 multiplied by the certified
rating.’’ JCI and Lennox believe the
language should read: ‘‘must be greater
than or equal to 0.95 multiplied by the
certified rating’’. (JCI, No. 66 at p. 3;
Lennox, No. 61 at p. 15)
Given the agreement of the
commenters, DOE finalizes its proposed
five percent tolerance in verifying an
AEDM’s performance and allowance for
manufacturers to make conservative
representations in this final rule. In
response to JCI and Lennox’s comments,
DOE acknowledges that the November
2015 SNOPR included a typographical
error in the tolerances, which has been
corrected in this final rule. DOE did not
receive comments on other aspects of its
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
AEDM verification testing proposals and
adopts them as proposed in the SNOPR.
6. Failure To Meet Certified Represented
Values
In the November 2015 SNOPR DOE
proposed that manufacturers need not
re-validate the AEDM in response to the
first determination of an invalid rating
for models certified with that AEDM. In
such cases, the manufacturer must
conduct additional testing and re-rate
and re-certify the individual
combinations within the basic model
that were improperly rated using the
AEDM. 80 FR 69278, 69297 (Nov. 9,
2015).
DOE also proposed that if DOE has
determined that a manufacturer made
invalid ratings on individual
combinations within two or more basic
models rated using the manufacturer’s
AEDM within a 24 month period, the
manufacturer must test the least
efficient and most efficient combination
within each basic model in addition to
the combination specified in
429.16(a)(1)(ii). The twenty-four month
period begins with a DOE determination
that a rating is invalid through the
process outlined above. If DOE has
determined that a manufacturer made
invalid ratings on more than four basic
models rated using the manufacturer’s
AEDM within a 24-month period, the
manufacturer may no longer use an
AEDM. 80 FR 69278, 69297 (Nov. 9,
2015).
DOE also proposed additional
requirements for manufacturers to
regain the privilege of using an AEDM,
including identifying the cause(s) for
failure, taking corrective action,
performing six new tests per basic
model, and obtaining DOE
authorization. 80 FR 69278, 69297 (Nov.
9, 2015).
DOE created its proposal under the
expectation that each manufacturer will
use only a single AEDM for all central
air conditioner and central air
conditioning heat pumps. Several
stakeholders responded to DOE’s
question on whether manufactures
typically apply more than one AEDM,
and if they do, then what the differences
are between such AEDMs.
ADP commented that they use one
AEDM. (ADP, No. 59 at p. 8) Unico
commented that a single AEDM may
incorporate several calculation methods,
but that the AEDM should be designed
to choose the most accurate calculation
method and is still one AEDM. (Unico,
No. 63 at p. 7)
Lennox commented that while the
concept of an AEDM’s function is the
same, different AEDMs may be
optimized for application, ease of use,
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
outputs or integration into other
business processes. Lennox
recommended that AEDMs not be
restricted to a singular application.
(Lennox, No. 61 at p. 15) UTC/Carrier
suggested that multiple AEDMs could
be applied for different products, such
as packaged systems versus splits and
variable speed versus single-stage. UTC/
Carrier argued that a dedicated AEDM
would more accurately reflect product
performance for consumer benefit (UTC/
Carrier No. 62 at p. 9) JCI commented
that they would likely utilize one AEDM
for split AC units, one for split HP units,
and possibly one for single-package
units, with a possible additional one a
two stage product and another for
multistage product. JCI stated the
primary differences are the additional
simulation conditions and required
additional input. (JCI, No. 66 at p. 16)
Rheem commented that manufacturers
may choose to have multiple AEDMs
based on design technologies to ensure
rating accuracy for each technology, i.e.,
micro-channel vs. fin and tube
performance modeling. (Rheem, No. 69
at p. 9)
After reviewing the comments, DOE
acknowledges that some manufacturers
may have more than one AEDM but will
likely have fewer than five. DOE
believes that its proposal is still valid
under these circumstances and has
adopted it as proposed. DOE has
adopted a requirement for
manufacturers to provide a ‘‘name’’ for
the AEDM used to rate each individual
model or combination, although for
some manufacturers it may be the same
for all. If DOE finds that there is a
proliferation of AEDMs and that DOE’s
requirements for re-validation, redetermination of represented values,
and/or re-certification following the
failure of a model to meet its certified
represented value are no longer
sufficient to ensure that represented
values generated with AEDMs are
reliable, DOE may revisit these
requirements.
AHRI and Nortek disagreed with the
proposal to invalidate an AEDM after
four failures within 24 months and
recommended that DOE implement an
option to ‘‘save’’ the HSVC and
remaining basic model ratings, similar
to the provisions within the AHRI
Certification Program. (AHRI, No. 70 at
p. 9; Nortek, No. 58 at p. 6) Ingersoll
Rand recommended that DOE adopt the
AHRI proposal for additional testing
should there be ‘‘excessive’’ failures of
AEDM rated products. (Ingersoll Rand,
No. 65 at p. 11) JCI commented that it
appears that if a basic model is deemed
invalid that all mix match ratings
associated with that basic outdoor
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
37019
model would be made invalid and be
required to be recertified. JCI believes
this is very punitive and does not take
into account that the invalid ratings may
be due to other factors. JCI also agreed
with other commenters that there
should be a method to ‘‘save’’ all of the
other mix match ratings associated with
that basic outdoor model. (JCI, No. 66 at
p. 4)
UTC/Carrier recommended that the
number of failures in 24 month period
before the AEDM is invalidated should
scale to the number of basic models for
that particular manufacturer. (UTC/
Carrier, No. 62 at p. 8)
Goodman expressed concern over the
result of an initial assessment test in
which the basic model being tested
failed to achieve its ratings. Goodman
commented that if the manufacturer is
permitted to review the setup of test
arrangement before the test is finished,
the cause of failure could be eliminated.
(Goodman, No. 73 at p. 7)
In response to AHRI, Nortek, and JCI,
DOE’s proposal does permit a
manufacturer to ‘‘save’’ all represented
values with minimal effort at the first
failure and with additional testing at the
second, third and fourth failures. If,
after all of that additional testing, the
AEDM is still not accurate, DOE is
unsure what would be ‘‘saved’’. DOE
notes that the tested combination of
each basic model would not have been
rated using the AEDM and thus would
be unaffected by a failure of the AEDM.
In response to Ingersoll Rand, DOE
views five failures in two years as
excessive, as DOE has already provided
a 5% tolerance. In response to UTC/
Carrier, DOE disagrees that the number
of failures should scale to the number of
basic models. DOE believes that if a
manufacturer has five basic models that
test outside of the 5% tolerance,
especially following feedback from the
four previous failures, that there must
be a significant problem with the
AEDM. In response to Goodman, DOE
notes that although it has not provided
an allowance for a manufacturer to
review the test set up prior to testing,
DOE will provide the manufacturer with
documentation related to the test set up
and allows the manufacturer to present
claims regarding the validity. DOE
believes this accomplishes the same
result.
Unico commented that for ICM
ratings, if a rating is invalid, if the same
basic model was tested and passed, only
the system tested that failed is re-rated.
For an ICM, the same failure is not
considered a failure of the AEDM unless
the outdoor unit has been tested and
shown to meet the OUM rating. Unico
argued that, from an engineering view,
E:\FR\FM\08JNR2.SGM
08JNR2
37020
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
the calculation method should only be
changed if the measured data is
[in]consistent with the AEDM input.
Unico also expressed the view that,
since the ICM does not manufacture the
outdoor unit, the ICM should not be
held responsible for the OUM
information. According to Unico, ICM
ratings are likely to be doubly
conservative if one considers that the
OUM ratings are conservative and this
is added to the conservative ICM rating.
Unico also urged DOE to consider that
the ratings are based on tests of the
outdoor unit (OUM basic model testing)
and of the indoor unit (ICM Similarity
Group testing), asserting that this is
more testing than the OUM product
alone. (Unico, No. 63 at p. 4)
In response to Unico, DOE does not
agree that ICMs should have different
consequences for failures than OUMs.
All manufacturers use AEDMs at their
own risk and are responsible for
ensuring the accuracy of the AEDM,
including the accuracy of the testing
used to validate the AEDM.
7. Action Following a Determination of
Noncompliance
If an individual model or combination
is determined to be noncompliant, then
all other individual models or
combinations within that basic model
are considered noncompliant. DOE’s
proposal in the November 2015 SNOPR
with respect to AEDMs did not include
a provision that other basic models
rated with the AEDM would be
considered noncompliant. However,
DOE noted that an AEDM must be
validated using test data for individual
combinations that meet the current
Federal energy conservation standards.
Therefore, if a noncompliant model was
used for validation of an AEDM, a
manufacturer must re-validate the
AEDM with test data for a compliant
basic model in order to continue using
the AEDM. The requirements for
additional testing based on invalid
ratings, as discussed in the previous
sections, may also apply. 80 FR 69278,
69298 (Nov. 9, 2015).
DOE notes that it did not receive
comments related to this discussion in
the November 2015 SNOPR.
8. AEDM for Off Mode
In the November 2015 SNOPR, DOE
listed several requirements a
manufacturer must meet to use an
AEDM in certifying ratings, including
PW,OFF. 80 FR 69278, 69339 (Nov. 9,
2015).
AHRI, Ingersoll Rand, Nortek,
Lennox, and JCI recommended that use
of an AEDM be permitted to generate
ratings for off mode power across units
of similar construction. (AHRI, No. 70 at
p. 9; Ingersoll Rand, No. 65 at p. 4;
Nortek, No. 58 at p. 5; Lennox, No. 61
at p. 7; JCI, No. 66 at p. 9) Additionally,
Lennox recommended that use of an
AEDM be permitted to generate ratings
for off mode power for units that use the
same off mode components (Lennox,
No. 61 at p. 7), while AHRI and Nortek
recommended that an AEDM be
permitted to be used to generate ratings
across tonnages. (AHRI, No. 70 at p. 9;
Nortek, No. 58 at p. 5) Rheem
recommended that manufacturers be
permitted to use an AEDM to generate
ratings for off mode power across
similar control systems that would
consume the same off-mode power.
Rheem also expressed the view that the
AEDM should be validated based on
testing of a single model with the same
control system. Rheem further
commented that manufacturers should
be able to rate the off mode power
consumption of both single-package and
split systems with varying compressors,
coils, and auxiliary refrigeration system
components if the models are in the
same basic model or have common
control and motor types. (Rheem, No. 69
at p. 3, 7)
DOE agrees with stakeholders that, for
units with a similar pairing of
compressor, crankcase heater and
common control, an AEDM is capable of
providing an off mode represented value
without the manufacturer needing to
test each basic model. In response to the
commenters’ request, DOE has
eliminated the requirement to test each
basic model for off-mode power.
Instead, at a minimum, among models
with similar off-mode construction
(even spanning different basic models, a
manufacturer must test at least one
individual model or combination for off-
mode power, and may use an AEDM for
the rest. DOE notes that in all cases, the
AEDM-generated represented value may
be subject to verification testing, and
thus the responsibility is on the
manufacturer to determine which
model(s) or combination(s) should be
tested for off-mode as part of AEDM
validation. DOE also notes that an
AEDM may be used for off-mode power
for multi-split, multi-circuit, and multihead mini-split systems, even though an
AEDM may not be used for the
efficiency metrics.
C. Waiver Procedures
In the November 2015 SNOPR, DOE
stated that a total of four waivers (and
one interim waiver) for central air
conditioner and heat pump products
would terminate 180 days after the
publication of this final rule notice in
the Federal Register. 80 FR 69278,
69298–300 (Nov. 9, 2015). The waivers
to be terminated are listed in Table III.4.
In the June 2010 NOPR, DOE
proposed a test method for testing
Triple-Capacity Northern Heat Pumps
which would replace the waiver test
procedure granted to Hallowell
International (see 75 FR 6013 (Feb. 5,
2010)) for testing its line of boosted
compression heat pumps. 75 FR at
31238 (June 2, 2010). The November
2015 SNOPR reproposed the same
procedure initially proposed in the June
2010 NOPR. 80 FR 69278, 69298 (Nov.
9, 2015). DOE did not receive comments
regarding this test procedure and is
therefore finalizing it in this final rule.
The Hallowell waiver will terminate on
December 5, 2016.
DOE received comments on the
proposed test procedure revisions
related to waivers for Multi-Zone
Unitary Small Air Conditioners and
Heat Pumps from ECR International
(ECR) and Multi-blower AirConditioning and Heating Equipment
from Cascade Group. Additionally, DOE
has further reviewed the proposed
approach for the waivers for air-to-water
heat pumps granted to Daikin for their
Altherma heat pumps. These waivers
and associated comments are discussed
in the following sub-sections.
asabaliauskas on DSK3SPTVN1PROD with RULES
TABLE III.4—WAIVERS TO BE TERMINATED
Scope
Decision & Order
ECR International, Inc., Multi-zone Unitary Small Air Conditioners and Heat Pumps .........................................
(Petition & Interim Waiver, 78 FR
47681, 8/6/2013).
76 FR 11438, 3/2/2011.
75 FR 34731, 6/18/2010.
75 FR 6013, 2/5/2010.
73 FR 50787, 8/28/2008.
Daikin AC (Americas), Inc., Heat Pump & Water Heater Combination ................................................................
Daikin AC (Americas), Inc., Heat Pump & Water Heater Combination ................................................................
Hallowell International, Triple-Capacity Northern Heat Pumps .............................................................................
Cascade Group, LLC, Multi-blower Air-Conditioning and Heating Equipment .....................................................
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
1. Air-to-Water Heat Pumps and Air
Conditioners
2. Clarification of the Test Procedure
Pertaining to Multi-Circuit Products
In the November 2015 SNOPR, DOE
had determined that the Daikin
Altherma air-to-water heat pumps with
integrated domestic water heating rely
exclusively on refrigerant-to-water heat
exchange on the indoor side, and thus
would not be required to be tested and
rated for the purpose of compliance
with DOE standards for central air
conditioners or heat pumps. 80 FR
69278, 69298 (Nov. 9, 2015). DOE
received no comment on these waivers.
DOE further considered the regulatory
status of air-to-water heat pumps and
notes that EPCA defines Central Air
Conditioner as ‘‘a product, other than a
packaged terminal air conditioner,
which—(A) is powered by single phase
electric current; (B) is air-cooled; (C) is
rated below 65,000 Btu per hour; (D) is
not contained within the same cabinet
as a furnace the rated capacity of which
is above 225,000 Btu per hour; and (E)
is a heat pump or a cooling only unit.’’
(42 U.S.C. 6291(21)) The definition does
not exclude products that transfer
cooling or heating to a water loop on the
indoor side. Hence, DOE concludes that
these products are covered under
regulations for CAC/HP. DOE does agree
that the existing test procedures for
CAC/HP do not fully address test
methods for air-to-water systems.
Specifically, they do not provide
instructions regarding how to set up the
water loop in the test, nor whether any
power input associated with the waterbased thermal distribution system
should be incorporated into the
efficiency metrics.
The Daikin waivers called for testing
of the Altherma air-to-water heat pumps
using European standard EN 14511 to
determine EER and COP, and that these
measurements are the only allowed
representations of the performance of
these products. (See for example 75 FR
34731, 34733 (June 18, 2010).) DOE now
considers these waivers to be invalid,
because they did not provide a method
to determine SEER and HSPF, the
metrics that must be reported to DOE to
certify compliance with the applicable
efficiency standards. Hence, these
waivers are considered to be terminated,
effective immediately. DOE will work
with manufacturers of air-to-water heat
pumps and air-to-water air conditioners
as needed to help develop test
procedures for providing SEER, HSPF,
and average off-mode power represented
values that may become the basis of
replacement waivers.
The ECR waiver for Multi-zone
Unitary Small Air Conditioners and
Heat Pumps concerns a split system that
has one outdoor unit with multiple
circuits. In the November 2015 SNOPR,
DOE proposed to define such a product
as a multiple-circuit (or multi-circuit)
system (see Section 1.2 in Appendix M).
The November 2015 SNOPR also
proposed to provide a test procedure for
multi-circuit products using a common
duct approach for the indoor air flow
measurement, similar to the approach
used for multi-split units (see Section
2.4.1.b in Appendix M), thus allowing a
single test for each operating condition.
80 FR 69278, 69299 (Nov. 9, 2015).
In their comments, AHRI and Nortek
stated that multi-circuit products are
different than multi-split systems.
According to AHRI and Nortek, the
outdoor unit has multiple separate
circuits, each serving a separate indoor
unit. They commented that multi-circuit
products should be considered as
multiple units whose outdoor portions
are all contained within one outdoor
unit cabinet. (AHRI, No. 70 at p. 18;
Nortek, No. 58 at p. 14–15). AHRI and
Nortek also commented that utilizing a
common duct at zero static pressure
with indoor sections of differing
airflows will load the indoor sections
unequally and may not yield the same
air flows as when individually ducted.
AHRI and Nortek commented that
without each circuit having individual
performance data collected, the test
would not reflect the true performance
of the system. Id.
Rheem stated that each circuit should
be tested individually and the efficiency
certified separately but did not elaborate
on this comment. (Rheem, No. 69 at p.
9)
Lennox supported DOE’s proposal of
the common duct approach for multicircuit products. (Lennox, No. 61 at p.
16)
DOE believes that a multi-circuit
system is a single unit rather than
multiple units, one for each circuit, as
suggested by Rheem. All of the
individual circuits within the multicircuit system share the same outdoor
coil and fan(s) and therefore are affected
by the operation of the other circuits.
The outdoor unit containing the
multiple circuits is shipped as a single
unit, not as separate units. Therefore,
DOE adopts its November 2015 SNOPR
proposal to require manufacturers to
certify the multi-circuit system as a
single system, which is consistent with
the existing ECR waiver.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
37021
DOE noted in the November 2015
SNOPR that the common duct testing
approach has been adopted by industry
standards and is an accepted method for
testing systems, such as multi-split
systems, having multiple indoor units.
80 FR 69299 (Nov. 9, 2015). In fact, the
indoor units of multi-split systems do
not all have the same capacity or air
flow rate. Hence, it is not clear why the
common-duct approach is suitable for
multi-split systems but would not be
suitable for multi-circuit systems. In this
final rule, DOE adopts the common-duct
testing approach proposed in the
November 2015 SNOPR for multi-circuit
systems. However, considering that
there might be manufacturers and/or
test laboratories that wish to use the
approach of the waiver, in which
individual measurements are made for
each indoor section, DOE has modified
the provisions in section 2.4.1.b for
multi-circuit systems to allow use of
either the common-duct approach or
separate air flow measurement for each
indoor unit of the multi-circuit system.
Both approaches should yield the same
performance since all the indoor
sections are subject to the same external
static pressure.
Because DOE has adopted test
procedure amendments that allow
multi-circuit systems to be tested
without a waiver, testing in accordance
with the ECR waiver may not be used
for representations after 180 days
following publication of this final rule.
3. Clarification of the Test Procedure
Pertaining to Multi-Blower Products
The Cascade Group waiver concerns
multi-blower products. The test
procedure amendments, as proposed in
the June 2010 NOPR enable testing of
multi-blower products. 75 FR 31237
(June 2, 2010). In the November 2015
SNOPR, DOE proposed amending
Appendix M to Subpart B of 10 CFR
part 430 with language in sections
3.1.4.1.1d and 3.1.4.2e to provide
detailed instructions on obtaining the
Cooling full-load air volume rate and
cooling minimum air volume rate. 80 FR
69278, 69300 (Nov. 9, 2015).
In response to DOE’s November 2015
SNOPR, Rheem stated that, if there are
options for obtaining the maximum or
minimum airflow configuration, the
option for each with the highest energy
consumption should be tested. (Rheem,
No. 69 at p. 9)
DOE notes that in tests for products
other than multi-blower systems, the
test procedures do not require use of the
most energy-consumptive control
setting options to achieve the specified
air flow rates. Hence, DOE declines to
require this approach for multi-blower
E:\FR\FM\08JNR2.SGM
08JNR2
37022
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
products. Therefore, DOE adopts the test
approach initially proposed in the June
2010 NOPR and modified in the
November 2015 SNOPR.
Because DOE has adopted test
procedure amendments that allow
multi-blower systems to be tested
without a waiver, testing in accordance
with the Cascade Group waiver may not
be used for representations after 180
days following publication of this final
rule.
asabaliauskas on DSK3SPTVN1PROD with RULES
D. Measurement of Off Mode Power
Consumption
In the June 2010 NOPR, DOE
proposed a first draft of testing
procedures and calculations for off
mode power consumption. 75 FR 31223,
31238 (June 2, 2010). In the following
April 2011 SNOPR, DOE proposed a
second draft, revising said testing
procedures and calculations based on
stakeholder-identified issues and
changes to the test procedure proposals
in the 2010 June NOPR and on DOEconducted laboratory testing. 76 FR
18105, 18111 (April 1, 2011). In the
October 2011 SNOPR, DOE proposed a
third draft, further revising the testing
procedures and calculations for off
mode power consumption based
primarily on stakeholder comments
received during the April 2011 SNOPR
comment period regarding testing
burden on manufacturers. 76 FR 65616,
65618–22 (Oct. 24, 2011). In the
November 2015 SNOPR, DOE proposed
a fourth draft discussing and revising
test settings and the calculation method
in response to stakeholders’ comments.
76 FR 69278, 69300–05 (Nov. 9, 2015).
Based on further comments DOE
received in the November 2015 SNOPR
comment period, DOE is modifying its
approach and is adopting the off mode
test procedure.
1. Test Temperatures
In the November 2015 SNOPR, DOE
proposed to require manufacturers to
include the temperatures at which the
crankcase heater is designed to turn on
and turn off, if applicable, in their
certification reports. 80 FR 69278, 69301
(Nov. 9, 2015). DOE proposed to replace
the ‘‘shoulder season’’ off mode test (P1)
at 82 °F with a test at 72±2 °F and
replace the ‘‘heating season’’ off mode
test (P2) at 57 °F with a test at a
temperature which is 5±2 °F below a
manufacturer-specified turn-on
temperature. Id.
In response to the October 2011
SNOPR, the California IOUs
recommended that P1 be measured at a
temperature that is 3–5 °F above the
manufacturer’s reported ‘‘off’’ set point.
(California IOUs, No. 33 at p. 2) DOE
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
requested comment on this
recommendation in the December 2011
extension notice. 76 FR 79135 (Dec. 21,
2011). AHRI responded to the California
IOUs’ recommendation, indicating that
the first test should instead be
conducted at 72 °F to verify whether the
crankcase heater is on, and suggesting
that 72 °F is more appropriate than 82
°F because 72 °F is ‘‘the top of the
shoulder season.’’ (AHRI, No. 41 at p. 2)
In response to the November 2015
SNOPR, Rheem expressed its preference
for the shoulder season off mode test to
be at 82±2 °F instead of 72±2 °F in order
to reduce the test condition
transitioning time after the B test.
(Rheem, No. 69 at p. 9)
Although DOE acknowledges that
there may be added test burden to
reduce the temperature in the test room,
DOE agrees with AHRI that 72 °F is
more representative of conditions
during actual use. Accordingly, today’s
final rule adopts the requirement that
this test be conducted at 72±2 °F. There
were no comments against the proposal
to replace the ‘‘heating season’’ off mode
test (P2) at 57 °F with a test at a
temperature which is 5±2 °F below a
manufacturer-specified turn-on
temperature. Hence, DOE adopts the
proposal in this final rule.
Ingersoll Rand requested an option
that off mode tests be allowed to take
place in a climate controlled enclosure
rather than a psychrometric room.
(Ingersoll Rand, No. 65 at p. 4) In
considering this suggestion, DOE
noticed that, although the proposed test
procedure does not specify that off
mode tests should be conducted in
psychrometric rooms, the proposed
procedure requires off mode tests be
done after the B, B1, or B2 test, thus
implying that it be conducted in a
psychrometric room. DOE agrees that
the off mode test results will not be
affected by humidity levels. The
proposal of the November 2015 SNOPR
involves conducting the off mode test
after the B, B1, or B2 test, and
approaching the target 72 °F test
temperature at a rate of change of no
more than 20 °F per hour. 80 FR 69278,
69374 (Nov. 9, 2015). The test procedure
in this final rule modifies this procedure
by allowing the off mode test to be
conducted in a temperature-controlled
room, but to otherwise maintain the
proposed requirements with regard to
ambient temperature, i.e. starting the
test when the ambient temperature is 82
°F (as required for the B, B1, or B2 test)
and subsequently ramping down the
ambient temperature as required by the
proposed procedure. The final test
procedure also acknowledges the initial
intent to conduct the test after the B, B1,
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
or B2 test by requiring that the
compressor shell temperature be at least
81 °F before starting the ambienttemperature rampdown. This
requirement prevents a test lab from
moving a test sample from a storage
room that might be much colder than 82
°F into the test room and starting the
test with a cold compressor.
Lennox suggested that DOE allow
manufacturers to simply energizing the
crankcase heater for non-variable type
heaters to reduce the test burden, so that
such units could be tested with no
temperature control requirement.
(Lennox, No. 61 at p. 16) In considering
Lennox’s comment, DOE agrees that this
option could be adopted for many fixedpower-input crankcase heaters,
including those without controls and
those controlled by thermostats that
measure ambient temperature whose
sensing elements are not affected by the
heater. However, DOE understands that,
if the thermostat’s action is affected by
the crankcase heater’s heat output (i.e. if
the sensing element is close enough to
the heater to be affected by the heat), the
unit should be tested with a controlled
ambient temperature because in such
cases the ambient temperatures at which
the thermostat switches the heater on
and off would differ from its rated cutin and cut-out temperatures, due to the
warming effect of the heater.
Several comments recommended a
third off-mode test at low temperatures.
JCI recommended for air conditioners
whose crankcase heaters are turned off
during winter a third test at 5 °F below
the winter cut-off temperature. (JCI, No.
66 at p. 16) The joint NEEA/NPCC
comment requested a third test below
freezing to establish the slope of a
variable power crankcase heating
system and to capture the energy use of
electric resistance drain pan heaters
which could consume considerable
energy in off mode for conditions below
freezing. (NEEA and NPCC, No. 64 at p.
4) The joint ACEEE/NRDC/ASAP
comment made a similar
recommendation (ACEEE, NRDC, ASAP,
No. 72 at p. 3) As mentioned in the
November 2015 SNOPR, the intent of
the off mode power consumption value
(PW,OFF) is that it be a representation of
the off mode power consumption for the
shoulder and heating seasons, and DOE
has not found that the additional
accuracy gained from the additional test
point merits the additional test burden,
as discussed in the November 2015
SNOPR. 80 FR 69278, 69301 (Nov. 9,
2015). As DOE is required to consider
test burden in its development of test
procedures, DOE is not adopting a third
test in this final rule.
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
2. Calculation and Weighting of P1 and
P2
DOE proposed to give equal weighting
to P1 and P2 for the calculation of the
off mode power rating (PW,OFF). 76 FR
65616, 65620 (Oct. 24, 2011). (See also
80 FR 69278, 69301 (Nov. 9, 2015)).
The Joint Efficiency Advocates (NEEA
and NPCC) strongly urged DOE to adopt
a temperature bin-weighting
methodology that would include the
energy contribution of drain pan heaters
and suggested considering the AHRIproposed bin method. (NEEA and
NPCC, No. 64 at p. 5) The Joint
Advocates of ACEEE, NRDC and ASAP
also recommended the bin method due
to their concern that the current
averaging method would underestimate
the off mode power consumed for units
with variable output crankcase heaters.
(ACEEE, NRDC and ASAP, No. 72 at p.
3) NEEA and NPCC also commented
that with manufacturers providing turnon and turn-off temperatures for
crankcase heaters, it would be easy to
construct a bin method calculation.
Further, they indicated that DOE has not
shown data to justify the selection of a
50–50 weighting of P1 and P2. (NEEA
and NPCC, No. 64 at p. 5)
DOE is aware that drain pan heaters
may be used in heat pumps that have
drain pans to collect defrost melt water.
However, heat pumps are not
considered to have off-mode hours in
sub-freezing winter conditions when
drain pan heaters might be required.
Their energy use is captured as part of
the active-mode heating tests in 17 °F
ambient conditions (e.g. the H3, H31,
and H32 tests) that are part of the HSPF
determination. To clarify, DOE has
added a new section 2.2.f to Appendix
M that indicates that such heaters are
energized for active-mode testing.
DOE initially proposed to adopt the
50–50 weighting of the off mode in the
October 2011 SNOPR 75 FR at 65620
(Oct. 24, 2011). This decision was made
in light of disagreement regarding what
represents an appropriate shoulder
season, concern about regional variation
in shoulder season characteristics, and
the fact that EPCA did not grant DOE
authority to set regional off-mode
standards. A 50–50 weighting of P1 and
P2 provides a representative national
estimate of off mode power input.
Depending on the assumptions made
regarding the shoulder season, the
climate region examined, whether the
product is an air conditioner or a heat
pump, and the details of the crankcase
heater control, the relative
representativeness of P1 and P2 may
change. In light of this variability and
uncertainty, it is not clear that a bin
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
calculation would have more meaning
than the 50–50 averaging. Therefore,
DOE is adopting the 50–50 weighting as
proposed.
There were additional comments
concerning the calculation of P1 and P2
for products with variable speed
compressors. Nortek, Unico, JCI, Rheem,
Goodman and AHRI each provided an
estimate of 70 Watts for variable speed
products’ crankcase heaters and
commented that 70 Watts is an accurate
average value. They argued that,
considering that the standard singlecapacity products’ crankcase heaters
require no more than 40 Watts, the ratio
of 70 to 40, which is 1.75, should be a
reasonable multiplier. (Nortek, No. 58 at
p. 8; Unico, No. 63 at p. 9; JCI, No. 66
at p. 9; Rheem, No. 69 at p. 10; AHRI,
No. 70 at p. 11; Goodman, No. 73 at p.
8) Lennox recommended that DOE
adopt the same requirement for
modulating or variable speed systems as
adopted for multiple compressor
systems, with a multiplier factor of 2.
(Lennox, No. 61 at p. 16)
In contrast, a joint comment from
NEEA and NPCC and a comment from
the California IOUs disagreed with
DOE’s proposal to adjust the off-mode
measurements for large-capacity,
multiple or modulated compressors.
NEEA and NPCC argued that
appropriately-designed crankcase
heaters for large-capacity compressors
should pass the off-mode standard and
that it is unnecessary to have a
multiplier. (NEEA and NPCC, No. 64 at
p. 5) The California IOUs commented
that off mode power consumption
should be on a per-system basis rather
than per-compressor. (California IOUs,
No. 67 at p. 2–4)
Based on these comments, DOE is
adopting 1.75 as the multiplier for
modulated compressors (including
variable-speed compressors). DOE
adopts as the effective multiplier for a
compressor system consisting of
multiple single-stage compressors a
value equal to the number of singlestage compressors. As addressed in the
November 2015 SNOPR, DOE believes
that large-capacity and multiplecompressor systems require higher
wattage crankcase heaters because they
are likely to have larger surface area and
more thermal mass, including more
lubricant. Also, manufacturers have
been using higher-wattage crankcase
heaters for modulating compressors to
address the higher perceived risk
associated with oil frothing on restart
for these compressors, due to their
higher controls complexity. DOE does
not have sufficient evidence that largercapacity, multiple-, or modulating
compressor systems can operate safely
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
37023
with the same levels of crankcase
heating and hence retains the multiplier
for these compressors in the off-mode
test. DOE agrees that modulated
compressors (including variable speed
products) require more crankcase heater
power, and selected the 1.75 factor on
this basis (this is equal to the typical
70W mentioned above for variablespeed compressors divided by the
typical 40W power draw for typical
single-stage compressor crankcase
heaters).
Although not indicated clearly in the
comments, DOE understands
‘‘modulated’’ in the comments to refer
to any compressor that is not singlecapacity. DOE clarifies in this final rule
that the 1.75 multiplier applies to the
number of compressors that are not
single-stage, including two-stage
compressors and variable speed
compressors. This is less than a factor
of 2, which would be the effective
adjustment for a two-compressor
system, but there is insufficient data
showing variable speed products should
have the same requirement as multiple
compressor systems.
3. Time Delay Credit and Removal of
Calculations for Off Mode Energy
Consumption and Annual Performance
Factor
In the November 2015 SNOPR, DOE
proposed to adopt, for crankcase heaters
that incorporate a time delay before
turning on, a credit that would be
proportional to the duration of the
delay, as implemented in the
calculation of the off mode energy
consumption. (The original proposed
calculation method for PW,OFF did not
include any adjustment associated with
the time delay). DOE also proposed, for
products in which a time delay relay is
installed but the duration of the delay
is not specified in the manufacturer’s
installation instructions shipped with
the product or in the certification report,
a default period of non-operation of 15
minutes out of every hour, resulting in
a 25% savings in shoulder-season off
mode energy consumption. DOE notes
that the impact on crankcase heater
energy use was extended in the proposal
to the entire off-mode energy
consumption because, for an air
conditioner or heat pump with a
crankcase heater, most of the off mode
energy use is associated with the heater.
To reduce potential instances of the
misuse of this incentive, DOE also
proposed requiring manufacturers to
include in certification reports the
duration of the crankcase heater time
delay for both the shoulder and heating
seasons. 80 FR 69278, 69303–04 (Nov. 9,
2015).
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37024
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
DOE received a joint comment from
NEEA and NPCC that stated, among
other things, that the impact of a time
delay in a system is difficult to measure
accurately. NEEA and NPCC also
expressed the opinion that sometimes
the time delay behavior is an artifact of
temperature control, because it takes a
certain time for the compressor to cool
after a run cycle. (NEEA and NPCC, No.
64 at p. 6) The California IOUs
recommended care be taken in adopting
such a credit, and requested that it be
vetted appropriately before being
implemented. (California IOUs, No. 67
at p. 5)
Upon further review of the function of
the time delay relay and its potential
impact on off mode power
consumption, DOE concludes that the
proposed credit is not consistent with
the intent of its off mode definition. A
definition for off mode was initially
proposed in the July 2010 NOPR. For air
conditioners, it was proposed to
include, ‘‘all times during the noncooling season of an air conditioner.
This mode includes the ‘shoulder
seasons’ between the cooling and
heating seasons when the unit provides
no cooling to the building and the entire
heating season, when the unit is idle.’’
75 FR at 31249 (June 2, 2010). The
definition for off mode season in today’s
notice is not identical but has
essentially the same meaning, for
example for an air conditioner, referring
to both the shoulder season and the
heating season. The shoulder season is
defined as the period between the
months of the year that require heating
or cooling. The off mode season lasts
months. Hence, the impact of a
crankcase heater time delay of a fraction
of an hour, as is typical for such relays,
would insignificantly reduce average
crankcase heater on-time or energy use.
The time delay credit was proposed in
the November 2015 SNOPR to apply
only to the off mode energy use
calculation, and to the annual
performance factor, APF, but not to the
off-mode metric PW,OFF. DOE does not
currently have, and has not proposed to
establish, standards or reporting
requirements for off mode energy use or
annual performance factor, nor are these
parameters needed for representations,
such as for product labeling. Hence,
DOE is not adopting in Appendix M the
proposed provisions for calculating off
mode energy use, as well as the
proposed time delay credit, and has
removed the provisions for calculating
annual performance factor.
4. Impacts on Product Reliability
Addressing concerns from
stakeholders, in the November 2015
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
SNOPR, DOE stated that it expected that
the proposed off mode test method
would allow manufacturers to meet the
June 2011 off mode standards without
compromising the reliability of central
air conditioners and heat pumps. DOE
requested comments on the issue of
compressor reliability as it relates to
crankcase heater operation. 80 FR
69278, 69304 (Nov. 9, 2015).
Lennox, JCI, and Rheem expressed
concerns that regulating crankcase
heater power will have a negative
impact on products. (Lennox, No. 61 at
p. 17; JCI, No. 66 at p. 17; Rheem, No.
69 at p. 11) NEEA/NPCC strongly agreed
with DOE that manufacturers will be
able to meet off mode power
consumption standards without adverse
impact on product reliability. (NEEA/
NPCC, No. 64 at p. 7) UTC/Carrier and
the California IOUs suggested that DOE
should seek comments or obtain
information on research conducted by
compressor manufacturers or
independent entities. (UTC/Carrier, No.
62 at p. 12; California IOUs, No. 67 at
p. 5) However, no party provided any
data indicating that the proposal would
have such an impact. Also, DOE has
modified many of the details of the test
procedure as requested by stakeholders
to address concerns, for example,
adjusting the measurement of PW,OFF for
modulating- or multiple-compressor
systems for consistency with their
typically higher crankcase heater
wattages. In this final rule, DOE has
modified the proposed off mode test
procedure consistent with information,
provided by stakeholders, that might
affect crankcase heater performance as
measured by the test procedure such
that application of the off mode
standard using the final test procedure
should have minimal impact on the
reliability of CAC/HP systems.
5. Off Mode Power Consumption for
Intelligent Compressor Heat Control
In a general response to the off mode
test procedure proposed in the
November 2015 SNOPR, Ingersoll Rand
commented that the proposed off mode
test procedure cannot accurately reflect
off mode energy consumption for their
intelligent crankcase heater control,
which cycles the heater to provide the
appropriate average heat input. They
requested that they be allowed to use an
alternative test method for measurement
of the heating season off-mode power
consumption, P2, for products with this
feature. The requested alternative test
suggested by Ingersoll Rand would
consist of a test period for measurement
of input power that includes three
complete crankcase heater cycles, or 18
hours, whichever is shorter, rather than
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
the 5-minute test period of the proposed
test. Ingersoll Rand provided test data
showing typical operation of the
crankcase heater. (Ingersoll Rand, No.
65 at p. 14–23) DOE carefully reviewed
Ingersoll Rand’s data and agrees that
longer tests are needed for heaters
whose controls cycle or vary crankcase
heater power over time. Rather than
authorizing an alternative method
specific to Ingersoll Rand, the final rule
adopts an additional provision in the
measurement of heating season off mode
power consumption (P2), using the
approach suggested by Ingersoll Rand
for such controls: three complete heater
cycles or 18 hours, whichever is shorter.
The final rule also requires that this
approach be used for measuring the
shoulder season off-mode power
consumption, P1, if the heater is
energized and cycles or varies input
power for that measurement.
6. Off Mode Test Voltage for DualVoltage Units
In its comments on the off mode test
procedure proposal of the November
2015 SNOPR, Ingersoll Rand stated that
the proposal did not specify how to test
units with a dual voltage rating. They
further recommended that for such
systems, the higher voltage should be
the test voltage for off mode tests.
(Ingersoll Rand, No 65 at p. 4). They
also commented that the same
tolerances be adopted as are used for
performance testing. DOE notes that the
current test procedure incorporates by
reference section 6.1.3.2 of AHRI 210/
240–2008, which provides requirements
for setting voltage for testing products
with dual nameplate voltages. The
standard requires that 230 V be used for
208–230 V dual-voltage units and that
testing for all other dual nameplate
voltage units be conducted at either the
lower of the two voltages or at both
voltages. Ingersoll Rand did not provide
explanations supporting their
suggestion to instead use the higher
voltage (Ingersoll Rand, No. 65 at p. 4),
and DOE sees no reason to depart from
these established requirements for offmode testing. DOE agrees with the need
to specify tolerances, which are
discussed in the next section.
7. Off Mode Test Tolerance
DOE recognized that the November
2015 SNOPR did not address all
relevant test tolerances for the off mode
power consumption test. DOE proposed
tolerances for outdoor temperatures in
the November 2015 SNOPR, but did not
clarify whether test tolerances for power
supply voltage for off mode testing
should be different than for active mode
testing. DOE adopts in this final rule the
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
same test tolerances used for active
mode testing (see, for example, Table 7
in section 3.3 of Appendix M). These
tolerances are 2.0 percent as the test
operating tolerance and 1.5 percent as
the test condition tolerance, both as a
percentage of measured voltage.
asabaliauskas on DSK3SPTVN1PROD with RULES
8. Organization of Off Mode Test
Procedure
In addition to revising the proposed
off-mode test procedure in response to
stakeholder comments, as discussed in
previous sections, DOE also modifies
the proposed off mode test procedure in
this final rule. These modifications do
not affect the measurement but should
help to ensure consistency between tests
conducted in different labs.
First, DOE has provided greater detail
regarding test sample set-up and
connection of power measurement
devices for off-mode testing. This
includes provisions for providing power
to the control circuit for all kinds of
units and specifically addresses the
options when testing coil-only units for
which a furnace or a modular blower is
the designated air mover. (See section
3.13.1.a of Appendix M as finalized in
this notice.)
Second, the test procedure now
provides greater specification regarding
which power inputs are to be included
as part of the low voltage power Px.
(See, for example, section 3.13.1.d of
Appendix M as finalized.)
Third, the test procedure indicates
that for units with time delay relays, the
measurement is to be made after the
time delay has elapsed.
In addition, DOE notes that in the
calculation of off-mode seasonal power
consumption in section 4.3, P2 should
never equal to zero. As described in the
November 2015 SNOPR, DOE intended
that the off mode power rating PW,OFF be
equal to the arithmetic mean of P1 and
P2, without discussion of any special
cases in which P2 is equal to zero. 80
FR at 69301 (Nov. 9, 2015). The
provisions for calculating PW,OFF for
cases in which P2 is equal to zero
should not have appeared in the
Appendix M regulatory language
presented in the notice. Hence this
notice shows the intended calculation,
that PW,OFF be equal to the average of P1
and P2.
9. Certification
In the November 2015 SNOPR, DOE
proposed that manufacturers report offmode power in their certification
reports. 80 FR 69278, 69291 (Nov. 9,
2015). In response, AHRI and Rheem
suggested that the off mode ratings
should be reported as pass/fail with a
5% tolerance. AHRI did not explicitly
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
clarify what they meant by a 5%
tolerance, but DOE assumes this means
that the model would rate as ‘‘pass’’
even if the measured value (or the
average of the values measured for the
sample of units) is as much as 5%
greater than the standard. AHRI stated
that first, it is difficult to accurately
measure the power consumption
because of the inaccuracies in common
measurement devices, and second,
because consumers do not compare
products using this metric,
manufacturers have no incentive to
report it. (AHRI No. 70 at p. 11; Rheem
No. 69 at p. 3)
DOE requires that manufacturers
report the value of all regulated
efficiency metrics rather than simply an
indication of whether units pass or fail
the energy conservation standard. If a
manufacturer does not wish to reveal
how much lower than the off-mode
power consumption standard a model
performs, it has the option to rate at the
standard level as long as the represented
value is consistent with the
measurements, sampling plan and
represented value requirements in 10
CFR 429. Accordingly, DOE maintains
the requirement to report the actual
value for off-mode power.
DOE also proposed to require
manufacturers to include in the
certification reports the temperatures at
which the crankcase heater is designed
to turn on and turn off for the heating
season, if applicable. 80 FR 69278,
69301 (Nov. 9, 2015).
After finalization of the off mode test
procedure based on stakeholder
comments, DOE recognized that the
only product-specific temperature
needed to be known to properly conduct
the test is the turn-on temperature (i.e.
the cut-in temperature). This is the
temperature below which the thermostat
would energize the heater. The heating
season off-mode power is measured at
an ambient temperature 5 +/- 2 °F below
this turn-on temperature. The
temperature at which the crankcase
heater of an air conditioner is designed
to turn off for the heating season (i.e.
below which the heater would no longer
be energized) will not be needed to
conduct the tests. This is because the
test procedure as finalized does not call
for a test at a temperature near this
lower turn off temperature. Hence DOE
is requiring reporting only of the
temperature at which the crankcase
heater is designed to turn on.
10. Compliance Dates
Rheem, Nortek, Goodman and JCI
expressed concern with complying with
the off mode power rating within 180
days of publication of the final test
PO 00000
Frm 00035
Fmt 4701
Sfmt 4700
37025
procedure. (Rheem, No. 69 at p. 3;
Nortek, No. 58 at p. 7; Goodman, No. 73
at p. 20; JCI, No. 66 at p. 9) JCI
commented that at least one test year is
needed to complete the work to comply.
(JCI, No. 66 at p. 9) JCI further suggested
that they would agree with requiring the
off mode test for any new basic model
starting 180 days after the publication of
final rule, but that all existing basic
models should be granted an extended
period of 5 years for compliance. (JCI,
No. 66 at p. 9) Nortek commented that
manufacturers should have at least two
years to comply with this change,
otherwise DOE must explicitly permit
all existing products to be grandfathered
in until the new energy conservation
standard goes into effect. (Nortek, No.
58 at p. 7) Goodman commented that
manufacturers are statutorily provided
with five years to comply with energy
conservation standards, which DOE has
reduced to less than six months.
Goodman requested that DOE provide at
least half of the required statutory time
(two-and-a-half years) to comply with
the off-mode standard compliance and
certification requirements. Goodman
noted that DOE could not presently
assert civil penalties for off-mode
because there is no final method of test.
(Goodman, No. 73 at p. 20–21)
DOE understands that the
stakeholders’ concern with the
compliance date is due to the test
burden related to measuring off mode
power consumption. In this final rule,
DOE has considerably reduced the test
burden in the following aspects: (a)
manufacturers do not need to test each
basic model for off mode power
consumption and instead are allowed to
use an AEDM for off mode with certain
requirements (discussed in section
III.B.8); (b) all units are allowed to be
tested for off mode power consumption
in a temperature-controlled room rather
than a psychrometric room; and (c) for
units having a compressor crankcase
heater whose power consumption can
be determined without ambient
condition requirements (e.g. the heater’s
wattage when energized does not vary
with ambient temperature),
manufacturers do not need to use
temperature-controlled test facilities.
With the test procedure allowances
stated above, DOE believes that the off
mode test burden has been reduced
significantly and manufacturers should
be able to provide the off mode power
represented values within 180 days as
required by statute.
E. Test Repeatability Improvement and
Test Burden Reduction
42 U.S.C. 6293(b)(3) states that any
test procedure prescribed or amended
E:\FR\FM\08JNR2.SGM
08JNR2
37026
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
shall be reasonably designed to produce
test results which measure energy
efficiency and energy use of a covered
product during a representative average
period of use and shall not be unduly
burdensome to conduct. This section
discusses clarifications to improve test
procedure repeatability and to reduce
test burden. None of the clarifications
listed in this section would alter the
average measured energy consumption
of a representative set of models.
1. Indoor Fan Speed Settings for Blower
Coil or Single-Package Systems
Indoor unit fan speed is typically
adjustable to assure that the required air
volume rate is provided for the range of
field-installed ductwork systems that
the unit might use for air distribution.
The DOE test procedure has specific
requirements for fan speed adjustment,
external static pressure, and air volume
rate during the test. For a ducted blower
coil system, DOE’s test procedure
requires that (a) external static pressure
be no less than a minimum value that
depends on cooling capacity 9 and
product class, ranging from 1.10 to 1.20
inches of water column (in. wc.) for
small-duct, high-velocity systems and
from 0.10 to 0.20 in. wc. for all other
systems except non-ducted (see 10 CFR
part 430, subpart B, Appendix M, Table
2); and that (b) the air volume rate
divided by the total cooling capacity not
exceed a maximum value of 37.5 cubic
feet per minute of standard air (scfm)
per 1000 Btu/h of cooling capacity 10
(see 10 CFR part 430, subpart B,
Appendix M, Section 3.1.4.1.1). In the
November 2015 SNOPR, DOE proposed
that blower coil products be tested using
the lowest speed setting that satisfies
the minimum static pressure and the
maximum air volume rate requirements,
if applicable, if more than one of these
settings satisfies both requirements.
This clarification was proposed to be
added to section 2.3.1.a of Appendix M.
80 FR 69278, 69305 (Nov. 9, 2015).
Rheem agreed that the most logical
and energy efficient method to set up an
indoor fan on a central air conditioner
or heat pump system is to set the indoor
blower to the lowest fan setting that
meets all of the air volume rate
requirements. Rheem also agreed that
lab to lab repeatability will improve
with this requirement. (Rheem, No. 69
at p. 11)
JCI expressed concern that testing
above the rated airflow would be
permitted (JCI, No. 66 at p. 11).
9 Or heating capacity for heating-only heat
pumps.
10 Such a requirement does not exist for heatingonly heat pumps.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
However, JCI expressed agreement with
the proposal provided DOE establishes
a tolerance relative to the rated airflow
before adjusting speed settings (JCI, No.
66 at p. 17). In response to JCI, DOE did
not intend to imply that the tested
airflow is allowed to exceed the rated
airflow. In this final rule, DOE has
clarified this in sections 2.3.1.a and
2.3.2.a of the regulatory text by
referencing section 3.1.4 for information
on air volume rate control settings.
Section 3.1.4 outlines a procedure in
which the air volume rate is always set
to the rated value or reduced to meet the
static pressure requirement.
Further, DOE notes that in the current
test procedure (section 3.1.4 of
Appendix M) the air flow may be
adjusted downwards from the rated air
flow by up to 5 percent to meet the
static pressure requirement before
adjusting speed settings (i.e., if the ESP
is lower than required when running at
the rated air flow, the code tester fan
can be adjusted to increase ESP and
decrease airflow, without increasing the
fan speed setting, until airflow is 95
percent of rated airflow). The June 2010
NOPR proposed increasing this
tolerance such that switching to a higher
speed setting would be required when
the air volume rate drops below 90
percent of the rated air volume rate
without meeting the external static
pressure requirement—a 10 percent
tolerance below rated. 75 FR at 31234
(June 2, 2010).
NEEA commented that they do not
support widening the gap between rated
performance in the lab and actual
performance in the field. NEEA
requested that DOE research the
adequacy of the 5 percent tolerance with
an ESP testing minimum of 0.5 in. w.c.
(NEEA, No. 7 at pp. 3–4). DOE does not
believe that the air volume rate
measurement in the field is very precise,
if it is measured directly at all when
systems are installed. This is because
the apparatus used to measure air flow
with this precision in the laboratory is
very bulky and is not used for field
installations. Hence, the increase from 5
to 10 percent tolerance would not
increase the gap between field and
laboratory operation. DOE adopts the
tolerance as proposed.
DOE identified potential sources of
confusion in section 3.1.4 and has
improved the language for setting the air
volume rate of ducted blower coil
systems that use blower motors other
than constant-air-volume-rate indoor
blower motors. These changes do not
alter the test method but rather provide
clearer instructions for adjusting the
indoor fan and the test apparatus
PO 00000
Frm 00036
Fmt 4701
Sfmt 4700
settings to set the air volume rate in
accordance with the test procedure.
Improper fan speeds implemented
during testing may have a marked
impact on product performance, and
inconsistent implementation of speed
settings and adjustments may be
detrimental to test repeatability. DOE
therefore proposed that manufacturers
could include in their certification
report a certified air volume rate and
certified instructions for setting fan
speed or controls to achieve that air
volume rate. 80 FR 69278, 69305 (Nov.
9, 2015). The requirement has been
adopted by DOE in the final rule. As
part of the section 3.1.4 changes, DOE
added instructions for testing if there is
no certified air volume rate.
Additionally, absent fan speed
instructions for installation, DOE added
instructions to use the as-shipped
settings.
DOE also adds specificity on which
test conditions to use for determining
air volume rates. For instance, the A (for
single-stage units) or A2 test is specified
for determining the cooling full-load air
volume rate. Another modification
places the 37.5 cubic feet per minute of
standard air (scfm) per 1,000 Btu/h of
capacity check as a last step in the
process, after both the air volume rate
and external static pressure
requirements are met.
AHRI asked DOE to provide
information on how the airflow 450
scfm per ton ceiling was derived and
why it is still relevant. (AHRI, No. 70 at
p. 13) DOE notes that the 450 scfm/ton
ceiling is identical to the 37.5 scfm per
1,000 Btu/h maximum air flow
requirement that is in the CAC/HP test
procedure. This requirement has been in
the DOE test procedure since it was
initially established. On January 11,
2001, DOE published a NOPR in which
it discussed whether this upper limit on
air flow should remain in the test
procedure, expressed interest in further
discussion to resolve the question, but
proposed not to change the limit. 66 FR
6774. The final rule completing that
rulemaking did not again discuss the
issue. 70 FR 59122 (Oct. 11, 2005).
DOE agrees with AHRI that the limit
is not needed for blower coil systems.
Increased air flow can improve heat
transfer from the indoor coil. However,
higher air flow for blower coil systems
is at the expense of considerable fan
power, which both reduces cooling
capacity and increases system power.
There is an optimum air flow for which
efficiency would be maximized,
typically near 400 scfm per ton, but it
is different for each system. In a blower
coil system test, the added fan power
required to move additional air is
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
incorporated in the measurement.
Hence, a manufacturer would not have
incentive to increase rated airflow
unreasonably. On the other hand, not
setting an upper bound on air flow in
the test procedure gives manufacturers
more design flexibility. For these
reasons, DOE has removed the 450 scfm
per ton requirement for blower coil
systems in this final rule notice. DOE
does, however, expect that certified
airflow rates will be consistent with
installation instructions, since
ultimately the test procedure is
intended to reflect field performance.
For consistency with the furnace fan
test procedure, DOE proposed to add to
Appendix M the definition for ‘‘airflowcontrol setting’’ that has been adopted
in Appendix AA to refer to control
settings used to obtain fan motor
operation for specific functions. 80 FR
69278, 69305 (Nov. 9, 2015). DOE did
not receive comments on this proposal
and is retaining it as proposed.
2. Air Volume Rate Adjustment for CoilOnly Systems
In the current DOE test procedure, for
a coil-only system, the pressure drop
across the indoor unit must not exceed
0.3 inches of water for the A test (or A2
test for two-capacity or variable-capacity
systems), and the maximum air volume
rate per capacity must not exceed 37.5
cubic feet per minute of standard air
(scfm) per 1000 Btu/h. (10 CFR part 430,
subpart B, Appendix M, Section
3.1.4.1.1) For such systems, higher air
volume rates enhance the heat transfer
rate of the indoor coil, and therefore
may maximize the measured system
capacity and efficiency. In addition, the
energy use and heat input attributed to
the fan energy for such products is a
fixed default value in the test procedure,
and is set at 365 W per 1,000 scfm (see,
for example, 10 CFR part 430, subpart
B, Appendix M, Section 3.3(d)). Thus,
the impact from fan power on the
efficiency measurement if air volume
rate is increased may be more modest
than for a blower coil unit, for which
fan input power would increase more
rapidly due to the increase of internal
pressure drop as well as air volume rate.
To prevent rating based on excessive air
volume rates, a maximum pressure drop
of 0.3 in. wc. is specified for the indoor
coil assembly. To minimize potential
testing variability due to the use of
different air volume rates, in the
November 2015 SNOPR, DOE proposed
to require for coil-only systems for
which the maximum air flow (37.5
scfm/1,000 Btuh) or maximum pressure
drop (0.3 in wc) are exceeded when
using the specified air flow rate, that the
air flow rate must be reduced so that
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
both are satisfied. This is specified in
section 3.1.4.1.1.c of Appendix M as
proposed. 80 FR 69278, 69305 (Nov. 9,
2015). DOE did not receive comments
on this proposal other than the AHRI
comment regarding the 450 scfm per ton
upper limit on air flow discussed above.
DOE believes that the 0.3 in wc coil
pressure drop maximum provides a
limit on airflow that is comparable, i.e.
exceeding the 450 scfm per ton limit
would generally involve also exceeding
the 0.3 in wc limit. Hence, DOE sees
little need to maintain the 450 scfm per
ton limit only for coil-only systems and,
consistent with the approach discussed
above for blower coil systems, has
removed this limit for coil-only systems.
3. Requirements for the Refrigerant
Lines and Mass Flow Meter
Section 2.2(a) of 10 CFR part 430,
subpart B, Appendix M provides
instructions for insulating the ‘‘lowpressure’’ line(s) of a split system. In the
cooling mode, the vapor refrigerant line
connecting the indoor and outdoor units
operates at low refrigerant pressure.
However, in the heating mode, it
operates at high pressure. To improve
clarity and ensure that the language of
the test procedure refers specifically to
the actual functions of the refrigerant
lines, DOE proposed in the November
2015 SNOPR to refer to the lines as
‘‘vapor refrigerant line’’ and ‘‘liquid
refrigerant line’’. 80 FR 69278, 69306
(Nov. 9, 2015).
Because DOE seeks to minimize test
variability associated with the use of
insulation, the November 2015 SNOPR
included a proposal for determining the
insulation requirement for the test based
on the materials and information
shipped with the test unit. Under this
proposal, test laboratories would install
the insulation shipped with the unit. If
the unit is not shipped with insulation,
the test laboratory would install the
insulation specified in the installation
manuals shipped with the unit. If
instructions for refrigerant line
insulation are not provided, liquid line
insulation would be used only for
heating-only heat pumps. These
proposed requirements were intended to
reduce test burden and improve test
repeatability. 80 FR 69278, 69306 (Nov.
9, 2015).
Additionally, DOE proposed to add
requirements to Appendix M, section
2.10.3 to require use of a thermal barrier
to prevent thermal transfers between the
flow meter and the test chamber floor if
the meter is not mounted on a pedestal
or other support elevating it at least two
feet from the floor. 80 FR 69278, 69306
(Nov. 9, 2015).
PO 00000
Frm 00037
Fmt 4701
Sfmt 4700
37027
DOE requested comment on these
proposals. Many stakeholders agreed
with the proposals. (NEEA and NPCC,
No. 64 at p.8; ADP, No. 59 at p.9; UTC/
Carrier, No. 62 at p. 13; Rheem, No. 69
at p. 11) DOE did not receive any
comments opposing these proposals.
Therefore, in this final rule, DOE adopts
these proposals and adds a specification
that insulation should remain the same
for heating mode and cooling mode.
4. Outdoor Room Temperature Variation
The current DOE test procedure
requires that a portion of the air
approaching the outdoor unit’s coil is
sampled using an air sampling device,
often called an air sampling tree. (See
Appendix M, section 2.5). To ensure
that the measured temperature
accurately represents the average
temperature approaching the coil even if
there might be variation in the outdoor
room conditions, the November 2015
SNOPR proposed to require
demonstration of air temperature
uniformity over all of the air-inlet
surfaces of the outdoor unit using
thermocouples, if sampling tree air
collection is not performed on all inletair faces of the outdoor unit.
Specifically, DOE proposed requiring
that the thermocouples be evenly
distributed over the inlet air surfaces
such that there is one thermocouple
measurement representing each square
foot of air-inlet area. The maximum
temperature spread to demonstrate
uniformity, i.e., the maximum allowable
difference in temperature between the
measurements at the warmest location
and at the coolest location, would be 1.5
°F. If this value is exceeded, DOE
proposed that sampling tree collection
of air would be required from all airinlet surfaces of the outdoor unit. DOE
proposed in the November 2015 SNOPR
to add these requirements to Appendix
M, section 2.11.b. 80 FR 69278, 69306–
07 (Nov. 9, 2015).
In its comments on the November
2015 SNOPR, Rheem agreed with DOE’s
proposal. (Rheem, No. 69 at p. 12) UTC/
Carrier also supported this proposal,
indicating that although it will be
challenging for testing facilities, it
should reduce testing uncertainty.
(UTC/Carrier, No. 62 at p. 14). DOE
recognizes that some of these proposed
requirements could represent
challenges, since they involve both
addition of instrumentation and could
require adjustment of outdoor room air
circulation patterns in order to assure
that the maximum temperature
difference is not exceeded.
Some stakeholders indicated that
aspects of the proposal were not clear.
JCI and AHRI commented that the
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37028
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
proposal did not specify if the 1.5 °F
maximum range for the observed
temperatures measured by the
thermocouples applies to time averages
or instantaneous measurements made at
any time during the test period, with
AHRI adding that the tolerance should
apply to the time-average
measurements. (JCI, No. 66 at p.18;
AHRI, No. 70 at p. 13; ADP, No. 59 at
p. 10; Lennox, No. 61 at p. 17). JCI,
AHRI, ADP, and Lennox commented
that the regulatory text portion of the
notice requires that the thermocouple
grid be used to verify temperature
uniformity whether or not air samplers
are used on all air inlet faces of the
outdoor unit, while the preamble
discussion (section III.E.3 of the notice)
indicates that the thermocouple grid is
not needed if air samplers are used on
all air inlet faces—the commenters
questioned the requirement for use of
the thermocouple grid if air samplers
are used on all faces. (JCI, No. 66 at
p.18; AHRI, No. 70 at p. 13; ADP, No.
59 at p. 10; Lennox, No. 61 at p. 17). In
response, DOE notes that DOE intended
that the tolerance apply to the average
temperatures measured during the test
period and that the thermocouple grid
be waived if the air samplers are used
on all air inlet faces. DOE revised
Appendix M for consistency with the
intent of the proposal. DOE notes that
time variation of the air inlet
temperature is already addressed by the
test operating tolerance requirement of
ANSI/ASHRAE 37–2009.
JCI and Ingersoll Rand suggested
increasing the allowed variation
between thermocouples on the
thermocouple grid or sampler to 2.5F.
(JCI, No. 66 at p.11; Ingersoll Rand, No.
65 at p. 5) In response, DOE notes that
the proposal was somewhat lenient in
allowing only one inlet air face to be
measured with an air sampler if the
temperature uniformity requirement is
met. If, for example, the outdoor unit
has four air inlet faces and the face with
an air sampler is measuring high just
within the allowed tolerance, while all
the others are reading low, the actual
average outdoor air condition would be
up to 1.9 °F lower than measured by the
air sampler if the maximum allowed
tolerance were 2.5 °F.11 Hence DOE is
reluctant to allow significant departure
from the proposed 1.5 °F tolerance.
However, DOE has increased the
tolerance to 2.0 °F, noting that the
accuracy of thermocouples is at best
11 For example, if the air approaching the airsampled face were 95 °F while the air approaching
the other faces were 92.5 °F, the actual average inlet
air temperature would be 93.1 °F, nearly 2 °F lower
than the temperature measured by the air sampler.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
nearly +/- 1 °F without careful
calibration, thus making imposition of a
1.5 °F maximum range impractical.
JCI commented that they have had
excellent experience with regard to the
balance of entering air when using a 3sided air sampler for products with 4
inlet air surfaces. (JCI, No. 66 at p.17)
However, the comment did not provide
DOE details to clarify what this means
in terms of air temperature uniformity
and how they determined that the 3sided approach is sufficient. For
example, if testing using four air
samplers with separate measurements
has always shown that any three of the
air samplers provides an average
temperature that is negligibly different
than the full four-air-sampler average,
such results would indicate strongly
that the fourth air sampler was not
necessary. DOE may consider such
information and potential revision of
the temperature uniformity
requirements in a future rulemaking if
such data can be provided.
AHRI and JCI commented that the
requirement to provide thermocouples
for every square foot of outdoor coil
surface would increase test burden,
potentially requiring use of up to 40
thermocouples for larger units. (AHRI,
No. 70 at pp. 12–13; JCI, No. 66 at p.11).
DOE notes that the thermocouples are
not required if all air-inlet faces of the
outdoor unit are measured using air
samplers. DOE also notes that the 2015
draft version of AHRI Standard 210/240
calls for use of 16 thermocouples per air
sampler. If using four air samplers, this
adds up to 64 thermocouples. DOE has
modified the requirement so that the
thermocouple density would be 16 per
face or one per square foot of inlet area,
whichever is less. However, as noted
before, the thermocouples are not
required if air samplers are used on all
air inlet faces.
Ingersoll Rand commented that DOE
should specify the location of the
thermocouples, indicating that poor
choice of location could, contrary to
ASHRAE 37 requirements, lead to the
thermocouple grid blocking the natural
recirculation of condenser discharge air
to the air inlet that may be inherent to
the product design. The comment
recommended that the thermocouples
be mounted on an air sampler. Ingersoll
Rand also recommended adding a
specification to correlate the average
thermocouple reading to the dry bulb
temperature measurement of the
sampled air, similar to the requirements
of the thermopile used on the indoor
side. (Ingersoll Rand, No. 65 at p. 5) In
response, DOE notes that thermocouple
requirement applies only if all air inlet
faces of the outdoor unit are not
PO 00000
Frm 00038
Fmt 4701
Sfmt 4700
measured using air samplers. DOE has
modified the test procedure language to
indicate that natural recirculation of
discharge air back to the air inlet should
be avoided when mounting the
thermocouples, and that they should be
located 6 to 24 inches from the air inlet
face. Certainly any thermocouple that
blocks discharge air flow will register a
high measurement that is outside of the
specified tolerance. Regarding the
correlation of thermocouple
measurements with the air sampler dry
bulb temperature measurement, DOE
has not adopted this recommendation
because it is not clear what its purpose
would be. For the indoor side, such
correlation helps to calibrate the
thermocouple grid measurement for the
cyclic test, but the outdoor air inlet
temperature measurements are not used
in a similar way for any of part of the
tests. DOE adopts the amendments as
proposed except for the changes
discussed in this section, including (a)
adopting 16 as the maximum number of
thermocouples per inlet face, (b)
increasing the maximum temperature
range from 1.5 °F to 2.0 °F, (c) clarifying
that the maximum range applies to the
average measurements for the test
period, and (d) clarifying that the
thermocouples should not interfere with
condenser discharge air flow.
5. Method of Measuring Inlet Air
Temperature on the Outdoor Side
The average dry bulb temperature of
air approaching the air inlet faces of the
outdoor unit can be measured using air
samplers or using thermocouple grids.
To improve test repeatability, in the
November 2015 SNOPR, DOE sought to
ensure that temperature measurements
taken during the test are as accurate as
possible. DOE proposed that the air
sampler dry bulb measurement (rather
than the thermocouple grids) be the
basis of comparison with the outdoor air
dry bulb temperature requirement for
the test. 80 FR 69278, 69307 (Nov. 9,
2015).
Rheem and ADP agreed with DOE’s
proposal in the November 2015 SNOPR.
(Rheem, No. 69 at p. 12; ADP, No. 59
at p. 10) There were no comments
against the proposal. Hence, DOE adopts
the proposal in this final test rule.
6. Requirements for the Air Sampling
Device
In the November 2015 SNOPR, DOE
proposed to require that no part of the
room air sampling device or the means
of air conveyance to the dry bulb
temperature sensor be within two
inches of the test chamber floor. DOE
also proposed to require those surfaces
of the air sampling device and the
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
means of air conveyance that are not in
contact with the indoor and outdoor
room air be insulated. 80 FR 69278,
69307 (Nov. 9, 2015).
DOE also proposed to require that
humidity measurements and dry bulb
temperature measurements used to
determine the moisture content of air be
made at the same location in the air
sampling device. As discussed in
section III.E.14, DOE also proposed
several amendments to air sampling
procedures that are included in a draft
revision of AHRI 210/240. 80 FR 69278,
69307 (Nov. 9, 2015).
Many stakeholders supported these
proposals. (JCI, No. 66 at p.18; ADP, No.
59 at p. 10; UTC/Carrier, No. 62 at p. 14;
Unico, No. 63 at p. 9; Rheem, No. 69 at
p. 12). There were no comments against
the proposals. Therefore, DOE adopts
the proposals.
7. Variation in Maximum Compressor
Speed With Outdoor Temperature
In the November 2015 SNOPR, DOE
proposed that the maximum compressor
speed be defined for the test procedure
as the absolute maximum speed at
which the compressor operates,
allowing for a different maximum for
heating mode as opposed to cooling
mode. One implication of this proposal
is that the maximum speed cannot be
different for different cooling mode test
conditions, and likewise it cannot be
different for different heating mode test
conditions. 80 FR 69278, 69307 (Nov. 9,
2015).
Some stakeholders supported this
proposal and others did not. In its
comments, Rheem tentatively agreed
with the proposal but indicated it would
support DOE conducting further studies.
(Rheem, No. 69 at p. 12) AHRI also
proposed further study on the issue
without further specificity. (AHRI, No.
70 at p. 17) UTC/Carrier requested
clarification, although commented that
the proposal seemed to be current
industry practice. (UTC/Carrier, No. 62
at p. 14) JCI and Goodman also agreed
that the maximum speed should be held
constant. (JCI, No. 66 at p. 18; Goodman,
No. 73 at pp. 8–9)
In contrast, Ingersoll Rand and
Lennox commented that they do not
support the proposal to fix the
maximum compressor speed because it
limits the potential performance
benefits of heat pumps. (Ingersoll Rand,
No. 65 at p. 11; Lennox, No. 61 at p. 11)
Ingersoll Rand commented that this
proposal will become a bigger problem
when the heating load line of Appendix
M1 is implemented. (Ingersoll Rand, No.
65 at p. 11) Lennox conducted testing
on a three ton system and determined
that operation at the 17 degree test point
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
could be enhanced by 40 percent
capacity and 10 percent HSPF by
allowing the speed of the compressor to
change with outdoor air temperature.
(Lennox, No. 61 at p. 11) Mitsubishi
recommended that the current testing
process remain the same and that the
optional testing method for HSPF
should allow manufacturers to obtain
ratings that incorporate the varying of
the maximum compressor speed with
outdoor temperatures. (Mitsubishi, No.
68 at p. 4)
DOE agrees with JCI and Goodman
that the maximum speed should be the
same for the different test conditions.
DOE notes that a unit’s performance is
calculated based on test results using
extrapolation and interpolation
assuming that capacity and power vary
linearly with outdoor temperature (i.e.,
the capacity and power vary a fixed
amount in Btu/h for each additional
degree that the outdoor temperature
rises). For example, equations 4.2.2–3
and 4.2.2.–4 in Appendix M of the
current test procedure are used with k
set equal to 2 to calculate heat pump
capacity and power input when
operating at maximum speed. The
performance for temperatures below 17
°F and above 45 °F ambient
temperatures is calculated based on
tests conducted at 17 °F and 47 °F.
Specifically, an equation for capacity as
a function of ambient temperature is
determined based on the measured
capacities at 17 °F and 47 °F. This
equation is then used to calculate
capacity for all ambient conditions
cooler than 17 °F and warmer than 45
°F. The same is done to determine heat
pump power input for these
temperature ranges. In a similar fashion,
performance for temperatures between
17 °F and 45 °F are calculated based on
tests conducted at 17 °F and 35 °F. The
following example shows how allowing
different compressor speeds for the
pairs of tests used to determine
performance can lead to nonrepresentative results.
The heat pump in question varies its
maximum compressor speed in heating
mode—its performance is shown in
Figure 2 of the Oak Ridge National
Laboratory review of variable-speed heat
pump test procedures. (Review of Test
Procedure For Determining HSPF’s of
Residential Variable-Speed Heat Pumps,
Docket No. EERE–2009–BT–TP–0004,
No. 49 at p. 5) The maximum-speed
capacity of this heat pump clearly does
not vary linearly between outdoor
temperatures of 17 °F and 47 °F. Use of
the test procedure’s equation to
represent this heat pump’s performance
below 17 °F would indicate that its
capacity increases as temperature drops
PO 00000
Frm 00039
Fmt 4701
Sfmt 4700
37029
below 17 °F, which clearly is not true.
This example shows that allowing
different maximum compressor speeds
can lead to nonsensical results. Hence,
DOE is maintaining its proposal,
consistent with its understanding of the
test procedure’s original intent, that
maximum speed be the same speed for
all test conditions of the particular
operating (heating or cooling) mode that
uses maximum speed. DOE has,
however, modified the test procedure in
this notice such that the maximum
speed for a given operating mode
(heating or cooling) used for the test
conditions required to rate the product
does not have to be the absolute
maximum used by the product for that
operating mode. Hence, a heat pump
could use a higher maximum
compressor speed when operating in a
5 °F ambient condition than used for the
required tests in 17 °F, 35 °F, and 47 °F
conditions. This provision assures that
cold-climate variable speed heat pumps,
those that boost compressor speed in
very low ambient temperatures to
reduce the amount of heat provided by
resistance heating, can be tested using
appropriate compressor speeds for the
tested operating conditions. DOE has
implemented the requirements
discussed in this section differently
than proposed. Instead of adding the
proposed clarifications for maximum
and minimum compressor speed in the
definition of ‘‘variable-speed
compressor system’’, DOE has provided
clarification regarding compressor speed
requirements in sections 3.2 and 3.6,
which describe the tests that are
required to be conducted for cooling
and heating modes.
DOE does agree that variable-speed
heat pumps that have the capability to
increase speed and thus heating
capacity in lower ambient temperatures
should have a test method that
accurately reflects the performance of
this potentially energy-saving feature
(e.g., see Lennox, No. 61 at p. 11).
However, it is DOE’s belief that
accurately accounting for such a feature
requires more careful consideration of
test procedure changes beyond simply
allowing the compressor speed to vary
for the test conditions required by the
current procedure. DOE will consider
such revisions in a future rulemaking. In
the meantime, if a manufacturer feels
that more accurate representation of a
unit’s performance would be obtained
with an alternative test procedure, the
manufacturer has the option of
petitioning for a test procedure waiver.
JCI and Goodman recommended using
a different term than ‘‘maximum
compressor speed’’. (JCI, No. 66 at p. 18;
Goodman, No. 73 at pp. 8–9) Goodman
E:\FR\FM\08JNR2.SGM
08JNR2
37030
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
recommended adopting the term ‘‘full’’,
as was proposed in the AHRI 210/240
Draft. DOE agrees and has modified the
terminology accordingly, renaming the
term ‘‘maximum compressor speed’’ to
‘‘full speed’’ to be consistent with AHRI
210/240 Draft.
The California IOUs commented that
DOE should require the OUM to provide
testing controls that allow fixed
minimum, intermediate, and maximum
speed/capacity controls settings.
(California IOUs, No. 67 at p. 5) Rather
than requiring provision of a test
controller, DOE is requiring the
provision as part of certification
reporting of information that specifies
the compressor frequency set points and
settings for multi-step or variableposition components.
8. Refrigerant Charging Requirements
In the November 2015 SNOPR, DOE
proposed to require that near-azeotropic
and zeotropic refrigerant blends be
charged in the liquid state rather than
the vapor state. This was proposed for
section 2.2.5.7 of Appendix M. 80 FR
69278, 69307 (Nov. 9, 2015).
DOE also proposed in the June 2010
NOPR to adopt into the test procedure
select parts of the 2008 AHRI General
Operations Manual indicating that the
refrigerant charge cannot be changed
after system setup. 75 FR at 31224,
31234–35 (June 2, 2010). DOE retained
this requirement in the November 2015
SNOPR, specifically proposing that once
the system has been charged with
refrigerant consistent with the
installation instructions shipped with
the unit (or with other provisions of the
test procedure, if the installation
instructions are not provided or not
clear), all tests must be conducted with
this charge. 80 FR 69278, 69307 (Nov.
9, 2015).
Also, because the charging procedure
would be different for systems with
different metering devices, DOE also
proposed to require manufacturers to
report the type of metering device used
during certification testing. 80 FR
69278, 69308 (Nov. 9, 2015).
If charging instructions are not
provided in the manufacturer’s
installation instructions shipped with
the unit, DOE proposed standardized
charging procedures consistent with the
type of expansion device to ensure
consistency between testing and field
practice. For a unit equipped with a
fixed orifice type metering device for
which the manufacturer’s installation
instructions shipped with the unit do
not provide refrigerant charging
procedures, DOE proposed that the unit
be charged at the A or A2 test condition,
requiring addition of charge until the
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
superheat temperature measured at the
suction line upstream of the compressor
is 12 °F.12 For a unit equipped with a
TXV or electronic expansion valve
(EXV) type metering device for which
the manufacturer’s installation
instructions shipped with the unit do
not provide refrigerant charging
procedures, DOE proposed that the unit
be charged at the A or A2 condition,
requiring addition of charge until the
subcooling 13 temperature measured at
the condenser outlet is 10 °F plus or
minus the proposed tolerance range.14
80 FR 69278, 69308 (Nov. 9, 2015).
For heating-only heat pumps for
which refrigerant charging instructions
are not provided in the manufacturer’s
installation instructions shipped with
the unit, the proposed standardized
charging procedure would be followed
while performing refrigerant charging at
the H1 or H12 condition. DOE also
proposed that charging be done for the
H1 or H12 test condition for cooling/
heating heat pumps which fail to
operate properly in heating mode when
charged using the standardized charging
procedure for the A or A2 test condition.
In such cases, some of the tests
conducted using the initial charge may
have to be repeated to ensure that all
tests (cooling and heating) are
conducted using the same refrigerant
charge. DOE proposed to add this
requirement to use the same charge for
all tests to Appendix M in a new section
2.2.5.8. 80 FR 69278, 69308 (Nov. 9,
2015).
DOE understands that manufacturers
may provide installation instructions
with different charging procedures for
the indoor and outdoor units. In such
cases, DOE proposed to require charging
based on the installation instructions
shipped with the outdoor unit for OUM
products and based on the installation
instructions shipped with the indoor
unit for ICM products, unless otherwise
specified by either installation
instructions. 80 FR 69278, 69308 (Nov.
9, 2015).
DOE also proposed that one or more
refrigerant line pressure gauges be
installed during the setup of single12 The range of superheating temperatures was
generalized from industry-accepted practice and
state-level authority regulations on refrigerant
charging for non-TXV systems.
13 The degree of subcooling or subcooling
temperature is the extent to which a fluid is cooler
than its refrigerant bubble point temperature at the
measured pressure, i.e., the bubble point
temperature at a fluid’s measured pressure minus
its measured temperature. Bubble point temperature
is the temperate at a given pressure at which vapor
bubbles just begin to form in the refrigerant liquid.
14 The range of subcooling temperatures was
generalized from manufacturer-published and
technician-provided service instructions and are
typical of industry practice.
PO 00000
Frm 00040
Fmt 4701
Sfmt 4700
package and split-system central air
conditioner and heat pump products,
depending on which parameters are
used to set charge, unless otherwise
specified by the installation
instructions. DOE also proposed that the
refrigerant charge be verified per the
charging instructions provided in the
installation instructions shipped with
the unit, or, if no charging instructions
are provided, the refrigerant charge
would be verified based on the
standardized charging procedure
described above. 80 FR 69278, 69308
(Nov. 9, 2015).
As discussed in section III.E.14, DOE
included in its proposal several aspects
of the charging procedures that are
included in a draft revision of AHRI
210/240. 80 FR 69278, 69308 (Nov. 9,
2015).
UTC/Carrier, Unico, Rheem, and JCI
supported the November 2015 SNOPR
proposal to require charging nearazeotropic and zeotropic refrigerant
blends in the liquid state only. (UTC/
Carrier, No. 62 at p. 14; Unico, No. 63
at p. 9; Rheem, No. 69 at p. 12; JCI, No.
66 at p. 18) There were no comments
that disagreed with this proposal, so
DOE is adopting it unchanged.
The California IOUs supported giving
priority to the OUM charging
instructions if the indoor and outdoor
unit instructions differ but did not
explain why the OUM charging
instructions should take priority if both
components include instructions and
they are not consistent. DOE responds
that integration of a system
incorporating an OUM’s outdoor unit
and an ICM’s indoor unit is the
responsibility of the ICM. Consequently,
DOE adopts the charging instruction
priority as proposed, i.e. ICM
instruction priority in this case.
The California IOUs also commented
that providing generic superheat and
subcooling temperatures is not
appropriate or necessary, adding that
manufacturers are required to include
other types of installation instructions
and should be required to do the same
with something as basic as refrigerant
charge. (California IOUs, No. 67 at p. 5)
In response, DOE notes that most CAC/
HP systems are shipped with
installation instructions which discuss
how to set refrigerant charge, and that
it expects the provisions proposed to
address cases where such instructions
are not provided will not have to be
used frequently. DOE notes further that
providing clarity in the test procedure
regarding how to address these
situations will ensure that there is no
question during testing about how to
test products shipped without
instructions.
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Rheem added that it provides
refrigerant charging instructions that are
dependent on the design of the unit; the
charging instructions are different for
different expansion devices (Rheem, No.
69 at p. 15). Consequently, DOE is
adopting the proposal to provide
standardized charging procedures that
are based on the type of expansion
device. Rheem commented that if the
manufacturer does not specify a target
superheat or subcooling point, 10 °F +/
¥ 1 °F superheat should be used for
systems with a fixed refrigerant
restrictor and 10 °F +/¥ 0.6 °F
subcooling should be used for systems
with a TXV or electronic expansion
valve. (Rheem, No. 69 at p. 15). As
mentioned above, DOE does not expect
the ‘‘generic’’ values of 12 °F superheat
and 10 °F subcooling to be used
frequently and notes that manufacturers
that desire that different target values be
used should be sure to include
installation instructions with the units.
DOE did not receive other comments
regarding the specific values of the
targets in case instructions are not
provided, and DOE’s research suggests
that the proposed values are a good
representation of the ranges of values
provided in installations instructions for
existing products. Hence, DOE is
adopting the target values proposed in
case instructions are not provided.
Unico did not support charging to a
specific subcooling value in heating
unless the product is heating-only
(Unico, No. 63 at p. 10).
Responding to DOE’s question about
confirming proper operation in the H1
or H12 test for heat pumps following
charging at the A or A2 test condition,
JCI requested that manufacturers be
permitted to set charge levels in either
heating or cooling mode (JCI, No. 66 at
p. 19). Rheem agreed with the proposal
to test a heat pump in the H1 or H12 test
in case it does not operate properly in
heating mode with a charge set in the
cooling mode, provided a definition of
nonfunctional is added to the test
procedure. (Rheem, No. 69 at p. 13) In
response, DOE added explanation in
section 2.2.5.2.b that shutdown of a unit
by its limiting devices would constitute
non-operation.
DOE notes that the proposal in the
November 2015 SNOPR requires that
the installation instructions shipped
with the system be consulted for
instructions about how to charge the
unit, and that the generic instructions be
used only if no instructions are
provided with the unit. Hence, a
manufacturer has the option of requiring
that charge be adjusted in cooling mode
or to higher subcooling levels than
indicated in section 2.2.5.4 of the
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
November 2015 SNOPR, both of which
would address Unico’s concerns.
Likewise, a manufacturer could specify
that charge be set in either heating or
cooling mode, which addresses JCI’s
concerns. 80 FR 69278, 69308 (Nov. 9,
2015).
In order to clarify that the
manufacturer can specify the operating
mode to be used for setting charge, DOE
has added language to section 2.2.5.2 of
this final rule notice allowing
manufacturers the option of specifying
tests for charging other than the A or A2
test. DOE maintains, however, the
requirement that air volume rate must
be determined by the A or A2 test.
Goodman disagreed that all singlepackage units must be pressure-verified,
requesting an option for manufacturers
to specify whether or not to connect
pressure measurement devices
(Goodman, No. 73 at p. 9). In response,
section 2.2.5.5 of this final rule notice
allows for manufacturers to specify in
installation instructions whether or not
pressure measurement instruments
should be attached. Otherwise, DOE is
adopting the proposal regarding
refrigerant pressure gauges.
For the final rule, DOE has explicitly
designated the charging tolerances as
test condition tolerances (see section
2.2.5.4). This clarifies that the charging
tolerances refer to the maximum
permissible differences between the
average value of the measured
temperature and the specified
temperature in the DOE test procedure.
Also for the final rule, DOE has
relaxed the tolerance on subcooling in
section 2.2.5.4 from +/¥ 0.6 °F (the
maximum tolerance listed in the draft
version of AHRI 210/240) to +/¥ 2.0 °F.
DOE is adopting this change for two
reasons. First, in re-examining past
tests, DOE has observed considerable
variation in subcooling temperatures
even for properly installed systems that
are operating correctly. DOE believes a
test condition tolerance of +/¥ 0.6 °F
will unnecessarily increase the
difficulty of testing these units. Second,
the minimum accuracy requirements in
the current test procedure on the
temperature and pressure instruments
could result in as much as a 3.0 °F
measurement uncertainty on
subcooling. Using today’s typical
instrumentation, however, the expected
measurement uncertainty is about 1.0
°F. DOE does not wish to require tighter
tolerances than measurement
uncertainties. Based on this, DOE
settled on the average, a 2.0 °F test
condition tolerance on subcooling.
DOE analyzed the impact of this
tolerance change on capacity and EER
by simulating performance across split-
PO 00000
Frm 00041
Fmt 4701
Sfmt 4700
37031
system and single-package airconditioners as well as split-system heat
pumps, varying the subcooling. On both
capacity and EER, the impact of a 2.0 °F
fluctuation was less than 1% of the
capacity and EER at baseline
subcooling. DOE concluded that the
advantages of increasing the tolerance in
reducing test burden outweighed this
impact. Hence, as mentioned, DOE is
adopting the 2.0 °F tolerance on
subcooling.
DOE received no other comments on
proposals concerned with changing the
refrigerant charge after setup, reporting
the type of metering device, refrigerant
charge verification, and/or any other
DOE proposals. Consequently, DOE is
adopting these proposals for this final
rule notice.
9. Alternative Arrangement for Thermal
Loss Prevention for Cyclic Tests
In the November 2015 SNOPR, DOE
proposed an alternative testing
arrangement to prevent thermal losses
during the compressor OFF period that
would eliminate the need to install a
damper in the inlet duct that conveys
indoor chamber air to the indoor coil.
The proposed alternative testing
arrangement would allow the use of a
duct configuration that relies on
changes in duct height, rather than a
damper, to eliminate natural convection
thermal transfer out of the indoor duct
during OFF periods of the ‘‘cold’’ (for
tests of cooling mode) or heat (for tests
of heating mode) generated by the
system during the ON periods. An
example of such an arrangement would
be an upturned duct installed at the
inlet of the indoor duct, such that the
indoor duct inlet opening, facing
upwards, is sufficiently high to prevent
natural convection transfer out of the
duct. The approach was developed for
situations where insufficient space is
available to install a damper box for
both the inlet and outlet ductwork—the
approach still requires use of a damper
box on the outlet. DOE also proposed to
require installation of a dry bulb
temperature sensor near the inlet
opening of the indoor duct at a
centerline location not higher than the
lowest elevation of the duct edges at the
inlet. Measurement and recording of dry
bulb temperature at this location would
be required at least every minute during
the compressor OFF period to confirm
that no thermal loss occurs. DOE
proposed a maximum permissible
variation in temperature measured at
this location during the OFF period of
±1.0 °F. 80 FR 69278, 69308–09 (Nov. 9,
2015). ADP supported this approach.
(ADP, No. 59 at p. 11)
E:\FR\FM\08JNR2.SGM
08JNR2
37032
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
Rheem commented that the currently
required damper in the inlet portion of
the indoor air ductwork has not been a
source of variation in their test results.
Rheem plans to continue using the
current damper configuration. Rheem
did not support an optional
configuration. (Rheem, No. 69 at p. 13,
14) Rheem has not explained their
objection to allowing use of the
alternative approach sufficiently for
DOE to understand the concern. Hence,
in this final rule, DOE is adopting the
option to allow an alternative testing
arrangement to prevent thermal losses
for cyclic testing. If the alternative
testing arrangement is used, installation
of a dry bulb temperature sensor near
the inlet opening of the indoor duct
would be required, as well as measuring
and recording the dry bulb temperature
from this sensor.
JCI agreed with the proposal, but was
concerned that it may not be possible to
maintain the 1.0 °F tolerance at the duct
inlet with continuous readings. (JCI, No.
66 at p.18). In response, DOE has
relaxed the requirement such that any
pair of 5-minute averages of the dry bulb
temperature at the inlet, measured at
least every minute during the
compressor OFF period of the cyclic
test, do not differ by more than 1.0 °F.
10. Test Unit Voltage Supply
In the November 2015 SNOPR, DOE
clarified that the outdoor voltage supply
requirement supersedes the indoor
requirement if the provisions result in a
difference for the indoor and outdoor
voltage supply. DOE proposed that both
the indoor and outdoor units be tested
at the nameplate voltage of the outdoor
unit. 80 FR 69278, 69309 (Nov. 9, 2015).
DOE received no comment on this
proposal, however DOE recognized that
it is possible that the nameplate voltages
of the indoor and outdoor units could be
so different that one unit cannot operate
with the other’s voltage supply. For
example, if the outdoor unit requires
230V while the indoor unit requires
120V, applying 230V to the indoor unit
would not be appropriate. DOE
reviewed the range of nameplate
voltages typically used for single-phase
products as listed in Table 1 on page 3
of AHRI Standard 110–2012, ‘‘AirConditioning, Heating and Refrigerating
Equipment Nameplate Voltages’’ and
determined that the only pair of
nameplate voltages for which the
electrical components for a product
rated with one could operate using the
voltage rated with the other are 208 V
(200 V) and 230V. Hence, DOE has
decided to require use of the outdoor
voltage supply for both indoor and
outdoor components only when one is
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
rated with 208V or 200V and the other
one is rated with 230V. For all other
voltage combinations, DOE will require
supplying each unit with its own
nameplate voltage.
11. Coefficient of Cyclic Degradation
The current test procedure gives
manufacturers the option to use a
default cyclic degradation coefficient for
cooling mode (CDc) value of 0.25 instead
of running the optional cyclic test. In
the November 2015 SNOPR, DOE
proposed to update the default cooling
CDc value in Appendix M to 0.2 based
on testing of 19 units for which the
measured degradation coefficient for
cooling ranged from 0.02 to 0.18. DOE
did not propose to update the default
heating CDh value. 80 FR 69278, 69309
(Nov. 9, 2015).
Responding to DOE’s proposal on the
coefficient of cyclic degradation,
stakeholders generally agreed with the
proposed default of 0.2 for cooling. (see,
e.g., AHRI, No. 70 at p. 12 or Ingersoll
Rand, No. 65 at p. 1) The test procedure
adopted in this final rule includes the
proposed value of 0.2 as the default
degradation coefficient for cooling for
single-speed and two-capacity units.
However, DOE is aware that units
with variable-speed compressors
consistently have a higher coefficient of
cyclic degradation than units with
single-speed or two-capacity
compressors. DOE reviewed the
California Energy Commission (CEC)
database of variable speed air
conditioners and observed that the
variable speed products rarely have a
cooling CDc as low as 0.2. In its review
of the CEC database, DOE noticed that
many variable speed units are listed as
multiple speed units. DOE separated the
variable speed units from this group
based on review of the product
specification sheets, thus leading to a
more complete list of variable speed
models. As a result DOE found that, of
639 listed models that have variablespeed operation, only 76 (i.e. 11%) are
rated with a CDc value less than or equal
to 0.2. As discussed above, DOE initially
proposed reducing the default value
from 0.25 to 0.2 based on test data
showing CDc values consistently below
0.2. However, these data did not include
measurements for variable-speed units.
Based on the clear evidence as
illustrated by the CEC database
information, the 0.2 value is not
representative of the cyclic performance
of variable-speed units. Hence, DOE has
maintained the current default cooling
CDc of 0.25 for variable speed products
and unmatched outdoor units (see
section III.A.3.g), while changing to a
PO 00000
Frm 00042
Fmt 4701
Sfmt 4700
default value of 0.2 for all other
products as proposed.
DOE also proposed significant
changes to the cyclic test. DOE proposed
that before determining CDc, three
‘‘warm up’’ cycles for a unit with a
single-speed compressor or two-speed
compressor or two ‘‘warm up’’ cycles for
a unit with a variable speed compressor
must be conducted. Then a minimum of
three complete cycles would be
conducted after the warm-up period,
taking a running average of CDc after
each additional cycle. If after three
cycles, the average of three cycles does
not differ from the average of two cycles
by more than 0.02, the three-cycle
average should be used. If it differs by
more than 0.02, up to two more valid
cycles must be conducted. If the average
CDc of the last three cycles are within
0.02 of or lower than the previous three
cycles, use the average CDc of all valid
cycles. After the fifth valid cycle, if the
average CDc of the last three cycles is
more than 0.02 higher than the previous
three cycles, the default value must be
used. DOE proposed the same changes
for the test method to determine the
heating coefficient of degradation. 80 FR
69278, 69309 (Nov. 9, 2015).
As a departure from the current test
procedure approach, DOE proposed that
manufacturers would have to conduct
cyclic testing to determine CDc for each
tested unit, rather than allowing them to
use the default and avoid cyclic testing.
Per the proposal, the default value
would be used only if stability was not
achieved during testing or when rating
outdoor units with no match. 80 FR
69278, 69309 (Nov. 9, 2015).
AHRI, Lennox, UTC/Carrier, Ingersoll
Rand, JCI, and Rheem commented that
manufacturers should be allowed to use
the default value without having to run
the cyclic test. (AHRI, No. 70 at p. 12;
Lennox, No. 61 at p. 18; UTC/Carrier,
No. 62 at p. 17; Ingersoll Rand, No. 65
at p. 2, JCI, No. 66 at p. 10; Rheem, No.
69 at p. 14) In contrast, NEEA
commented in response to the June 2010
NOPR that laboratory measurements are
often ‘‘at odds’’ with the 0.25 default
value, and suggested that testing is more
accurate and should always be
conducted. The comment did not
indicate whether the measurements
were generally higher or lower than the
default. (NEEA, No. 7 at p. 6)
Lennox, UTC/Carrier, Rheem and
AHRI suggested that a manufacturer
should be allowed to use the first two
cycles meeting a stability requirement,
rather than requiring three warm-up
cycles before official measurement
begins. (Lennox, No. 61 at p. 18; UTC/
Carrier, No. 62 at p. 17; Rheem, No. 69
at p. 14; AHRI, No. 70 at p.11). If
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
stability is not reached after eight
cycles, several manufacturers suggested
use of either a measured value or the
default value, whichever is lower, rather
than requiring use of the default value.
Lennox, Rheem and UTC/Carrier
suggested that this measured value be
the highest CDc recorded for any of the
eight test cycles. (Lennox, No. 61 at
p.18; Rheem, No. 69 at p. 14; UTC/
Carrier, No. 62 at p. 17) JCI suggested
that the measured value be the average
of the three highest measured CDc values
(JCI, No. 66 at p. 10), and Ingersoll Rand
suggested that the measured value be
the highest CDc recorded in cycles four
through eight (Ingersoll Rand, No. 65 at
p. 3).
After reviewing all the stakeholders’
comments, DOE has decided to allow
manufacturers to use the default value
without testing. Also, DOE is removing
the requirement to conduct three warmup cycles prior to making
measurements. In the test finalized in
this notice, a minimum of three cycles
must be measured, and the test may
then be terminated if the stability
requirement is achieved. The test will
still be required to continue for up to
eight cycles if stability is not achieved.
When the test is terminated, the highest
CDc value recorded for any one test cycle
would be used, unless it is higher than
the default CDc, in which case the
default would be used. The same
approach is also adopted for the heating
mode cyclic test. In response to the
NEEA comment, DOE’s data suggest that
most single-stage and two-stage units
have cyclic degradation coefficients less
than the default and, in DOE’s
experience, manufacturers of such
products nearly always run the cyclic
test. DOE specifically re-evaluated
selection of the default value so that it
is higher than the expected result, but
DOE retains in its procedures use of the
default value rather than testing to limit
test burden for cases where a low CDc is
not critical to assuring that the
represented value is compliant with the
standard (e.g. for variable-speed units,
which generally have higher CDc than
single-stage or two-stage units).
In order to improve the accuracy of
the cyclic test, DOE proposed in the
June 2010 NOPR a calibration step in
which the temperature difference
between measurements of the inlet and
outlet thermocouple grids used to make
the cyclic test capacity measurements is
checked during the steady state test
which precedes the cyclic test (e.g. the
steady state C test for cooling). If this
temperature difference compares
unfavorably to the more accurate dry
bulb temperature difference based on air
samplers and sample-air temperature
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
sensors (e.g. resistance temperature
detectors (RTDs)), the proposal required
that a calibration adjustment be made
for the thermocouple grid measurements
for use in the cyclic test. 75 FR 31235
(June 2, 2010). NEEA commented that
they have no objection to DOE’s
proposal. (NEEA, No. 7 at p. 4) In
contrast, AHRI disagreed with DOE’s
proposal and supported using the same
temperature devices between the steadystate tests and cyclic tests to calculate
CD in order to ensure consistency of
measurement between the two tests.
(AHRI, No. 6 at p. 3) DOE notes that
AHRI’s recommended solution, use of
the thermocouple grids for measurement
of the inlet/outlet temperature
difference for both the steady-state and
cyclic tests used as the basis for
calculating CD, does not fully resolve the
potential error in measurement if the
measured temperature difference is high
or low. In such a case, both the steady
state and cyclic capacity estimates may
be incorrect, and the overall
measurement less precise than if the
calibration step is taken. In order to
achieve the original goal of improving
the accuracy of the cyclic test, the test
procedure in this final rule notice
includes the proposed calibration step.
12. Break-in Periods Prior to Testing
DOE proposed in the November 2015
SNOPR to allow manufacturers the
option of specifying a break-in period to
be conducted prior to testing under the
DOE test procedure. DOE proposed to
limit the optional break-in period to 20
hours, which is consistent with the test
procedure final rule for commercial
HVAC equipment. DOE also proposed to
adopt the same provisions as the
commercial HVAC rule regarding the
requirement for manufacturers to report
the use of a break-in period and its
duration as part of the test data
underlying their product certifications,
the use of the same break-in period
specified in product certifications for
testing conducted by DOE, and use of
the 20 hour break-in period for products
certified using an AEDM. 80 FR 69278,
69310 (Nov. 9, 2015).
In response to the November 2015
SNOPR, Unico supported the option of
having a break-in period and had no
comment on the number of hours.
(Unico, No. 63 at p. 11) Several other
commenters requested longer break-in
periods than 20 hours. LG and Ingersoll
Rand commented that on average 40
hours of operation are required to reach
peak capacity and efficiency. (LG, No.
55 at pp. 1–2; Ingersoll Rand, No. 65 at
pp. 10–11) Rheem commented that
manufacturers should have the option of
up to a 48 hour break-in period. (Rheem,
PO 00000
Frm 00043
Fmt 4701
Sfmt 4700
37033
No. 69 at p. 14) Goodman commented
that at least 72 hours should be
permitted for break-in period testing
because they believe that shorter breakin periods could produce test results
that are inaccurate. (Goodman, No. 73 at
pp. 12–13) Lennox, UTC/Carrier, and
JCI also commented that some
compressor manufacturers recommend
up to 72 hours break-in. (Lennox, No. 61
at p. 19; UTC/Carrier, No. 62 at p. 17;
JCI, No. 66 at p. 19) UTC/Carrier
requested that DOE research directly
with compressor manufacturers to align
with their recommended compressor
break-in periods. (UTC/Carrier, No. 62
at p. 17) Lennox commented that
manufacturers should be able to specify
break-in conditions. (Lennox, No. 61 at
p. 19) JCI commented that if a
manufacturer is willing to pay for an
extended break-in time, it is reasonable
to allow it, as it more closely represents
what the consumer will see in the
installation. (JCI, No. 66 at p. 19)
LG and Ingersoll Rand further
commented that they have worked
towards a process for reducing the
required break-in period for scroll
compressors, and have developed a
process to reduce the required break-in
period to 12 hours. (LG, No. 55 at pp.
1–2; Ingersoll Rand, No. 65 at pp. 10–
11) LG commented that they will be
phasing in this new process through
2016, and requested DOE to adopt a
phase-in approach for the rule
implementation, with the limit being 40
hours on the rule effective date followed
by the final 20 hour limit that would
commence one year after the effective
date. (LG, No. 55 at pp. 1–2) Ingersoll
Rand recommended the effective date of
the maximum break-in time be January
1, 2017. (Ingersoll Rand, No. 65 at pp.
10–11)
In a supplemental response to the
October 2011 SNOPR, AHRI requested
that DOE implement an optional 75hour break-in period for testing central
air conditioners and heat pumps. It
stated that scroll compressors, which
are the type of compressors most
commonly used in central air
conditioners and heat pumps, achieve
their design efficiency after 75 hours of
operation. AHRI also cited a study of
compressor break-in periods to justify
this period of time.15 80 FR 69278,
69309–310 (Nov. 9, 2015).
In the November 2015 SNOPR, DOE
noted that, in reviewing the paper that
AHRI cited, while the data indicate that
products with scroll compressors do
appear to converge upon a more
15 Khalifa, H.E. ‘‘Break-in Behavior of Scroll
Compressors’’ (1996). International Compressor
Engineering Conference. Paper 1145.
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37034
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
consistent result after compressor breakin periods exceeding 75 hours, the most
significant improvement in compressor
performance and reduction in variation
among compressor models both appear
to occur during roughly the first 20
hours of run time.16 80 FR 69278, 69310
(Nov. 9, 2015). Considering the
improvements in break-in as discussed
in the comments of LG and IngersollRand, as well as the 1996 data which
shows that most of the break-in occurs
within 20 hours, DOE concludes that
setting the bread-in period at 20 hours
appropriately balances test burden and
full completion of the break-in process.
After reviewing the comments, DOE
maintains its proposal from the SNOPR,
and will allow a break-in period up to
a maximum of 20 hours. As noted in the
November 2015 SNOPR, DOE believes
that a lengthy break-in period is not
appropriate or justified. Since DOE
determined in the May 16, 2012
commercial HVAC equipment final rule
that a 20 hour maximum break-in time
would be sufficient for small
commercial air-conditioning products,
which are of a capacity similar to
central air-conditioning products, DOE
does not see justification for a break-in
period longer than 20 hours for central
air conditioners and heat pumps. DOE
acknowledges the research being done
to reduce the break-in period as
highlighted by LG and Ingersoll Rand,
but DOE notes that at this time, none of
the commenters has provided new
information or data that sufficiently
justifies the need for a longer break-in
period.
Some commenters also requested that
DOE provide additional specification
regarding the break-in. The California
IOUs recommended that DOE specify
the operation of systems during the
break in period or require the OUM to
specify how the break-in should be
done. (California IOUs, No. 67 at p. 5)
Rheem commented that the break-in
period should be at the A test cooling
condition after the unit is properly
charged. (Rheem, No. 69 at p. 14)
Without test results clearly showing
the benefits of a particular set of breakin conditions, DOE is reluctant to
require conditions for break-in that will
require it to be conducted in the
psychrometric chamber as part of a test,
due to the significant test burden that
such a requirement would impose. DOE
declines to add more specification to the
break-in period at this time but may
consider modifications in a future
rulemaking, provided sufficient
information is provided to justify
specific recommendations.
16 Ibid.
pp. 442–443.
VerDate Sep<11>2014
00:40 Jun 08, 2016
Jkt 238001
13. Industry Standards That Are
Incorporated by Reference
In the November 2015 SNOPR, DOE
proposed a number of updates to
industry standards that are incorporated
by reference. DOE proposed to update
the IBR from ARI 210/240–2006 to AHRI
210/240–2008; ASHRAE 37–2005,
Methods of Testing for Rating Unitary
Air-Conditioning and Heat Pump
Equipment to ANSI/ASHRAE 37–2009,
Methods of Testing for Rating
Electrically Driven Unitary AirConditioning and Heat Pump
Equipment; ASHRAE 41.9–2000,
Calorimeter Test Standard Methods for
Mass Flow Measurements of Volatile
Refrigerants to ASHRAE 41.9–2011,
Standard Methods for VolatileRefrigerant Mass Flow Measurements
Using Calorimeters; ASHRAE/AMCA
51–1999/210–1999, Laboratory Methods
of Testing Fans for Aerodynamic
Performance Rating to AMCA 210–2007,
Laboratory Methods of Testing Fans for
Certified Aerodynamic Performance
Rating; ASHRAE 41.1–1986 (Reaffirmed
2006), Standard Method for
Temperature Measurement, to ANSI/
ASHRAE 41.1–2013, Standard Method
for Temperature Measurement;
ASHRAE 41.6–1994, Standard Method
for Measurement of Moist Air Properties
to ASHRAE 41.6–2014, Standard
Method for Humidity Measurement; and
ASHRAE 23–2005, Methods of Testing
for Rating Positive Displacement
Refrigerant Compressors and
Condensing Units, to ASHRAE 23.1–
2010 Methods of Testing for Rating the
Performance of Positive Displacement
Refrigerant Compressors and
Condensing Units That Operate at
Subcritical Temperatures of the
Refrigerant. DOE expressed the view
that none of these updates includes
significant changes to the sections
referenced in the DOE test procedure
and thus will not impact the ratings or
energy conservation standards for
central air conditioners and heat
pumps.17 80 FR 69278, 69310–11 (Nov.
9, 2015).
In response, JCI encouraged DOE to
utilize industry standards to the fullest
extent possible. (JCI, No. 66 at p. 20)
Goodman requested that DOE, along
with other stakeholders, continue
participation in the revision of AHRI
210/240 to assist in getting to the point
where DOE can potentially adopt this
standard outright. (Goodman, No. 73 at
p. 16)
17 ANSI/ASHRAE 37–2009 only updates to more
recent versions of other standards it references.
AMCA 210–2007 made slight changes to the figure
referenced by DOE, which DOE has determined to
be insignificant.
PO 00000
Frm 00044
Fmt 4701
Sfmt 4700
Ingersoll Rand requested DOE to
remove all references to AMCA 210–
2007, because it is for standalone air
moving systems and does not match the
configuration used for ducted HVAC
equipment. (Ingersoll Rand, No. 65 at p.
13) AHRI and UTC/Carrier commented
that the reference to AMCA 210–2007 in
lieu of ASHRAE 116–1995 (RA 2005) for
the air flow measurement apparatus is
incorrect, and that instead the reference
should be to section 6.3 of ANSI/
ASHRAE 37–2009 or ASHRAE 41.2.
(AHRI, No. 70 at p. 12; UTC/Carrier, No.
62 at p. 18)
DOE believes that the referenced
sections are applicable to the airflow
measurements required in Appendix M,
as demonstrated by the installation
types referenced in section 5.1.1 of
AMCA 210–2007. DOE also notes that
AHRI 210/240–2008 references the same
sections of AMCA 210–2007 as
Appendix M does, but DOE has simply
chosen to reference AMCA 210–2007
directly. In response to AHRI and UTC/
Carrier, DOE notes that section 2.6 of
this final rule notice does reference
sections 6.2 and 6.3 of ANSI/ASHRAE
37–2009 for fabricating and operating
the Airflow Measurement Apparatus,
and the manufacturer may refer to either
Figure 12 of AMCA 210–2007 or Figure
14 of ASHRAE 41.2–1987 (RA 1992) for
guidance on placing the static pressure
taps and positioning the diffusion baffle.
For these reasons, DOE maintains its
incorporation by reference of AMCA
210–2007. DOE received no other
comments on these proposed updates to
industry standards, and in this final
rule, DOE adopts all references to
industry standards as proposed in the
November 2015 SNOPR.
In the November 2015 SNOPR, DOE
also proposed to revise the definition of
‘‘continuously recorded’’ based on
changes to ASHRAE 41.1. ASHRAE
41.1–1986 (RA 2006) specified the
maximum time interval of one minute
for sampling dry-bulb temperature
during a steady state test, with shorter
sampling intervals based on expected
rate of temperature change. The updated
version, ANSI/ASHRAE 41.1–2013,
does not contain specifications for
sampling intervals. DOE proposed to
require that dry-bulb temperature, wet
bulb temperature, dew point
temperature, and relative humidity data
be ‘‘continuously recorded,’’ that is,
sampled and recorded at 5 second
intervals or less. DOE proposed this
requirement as a means of verifying that
temperature condition requirements are
met for the duration of the test. 80 FR
69278, 69311 (Nov. 9, 2015).
UTC/Carrier and Rheem supported
the proposed sampling interval. (UTC/
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Carrier, No. 62 at p. 18; Rheem, No. 69
at p. 15) On the other hand, JCI
recommended a longer sampling
interval of 10 to 15 seconds, as there
may be capital investment and
programming required. (JCI, No. 66 at p.
20) Rheem commented that clarification
is needed on how measurements such as
the air leaving temperature are
calculated from the multitude of values
in the data sample. (Rheem, No. 69 at p.
15)
In response to JCI, DOE believes that
the current standard of care requires
digital data acquisition of all
temperature and humidity
measurements. DOE understands that
for measurements being taken and
recorded digitally, decreasing the
sampling interval generally should have
an insignificant impact on burden, since
state-of-the-art data acquisition systems
can easily record data at faster rates and
the cost of the additional data storage is
minimal. However, DOE understands
that any specific test laboratory may
require significant investment to
upgrade to a faster data rate, depending
on the capabilities of their current data
acquisition systems, and hence has
decided to increase the required
sampling interval to 15 seconds. In
response to Rheem’s request for
clarification, DOE believes that it is
common industry practice, when
continuously recording a parameter
such as air leaving temperature, to
average the value over the sampled
interval. However, to enhance clarity,
DOE has added words to sections 3.3.c
and 3.7.b of Appendix M indicating that
capacity is to be calculated using the
averages of the 30-minute continuouslyrecorded measurements made for the
parameters that are used to determine
capacity (e.g. indoor air inlet and outlet
temperatures).
asabaliauskas on DSK3SPTVN1PROD with RULES
14. References to ASHRAE Standard
116–1995 (RA 2005)
In the June 2010 NOPR, DOE
proposed referencing ASHRAE Standard
116–1995 (RA 2005) within the DOE test
procedure to provide additional
information about the equations used to
calculate SEER and HSPF for variablespeed systems. 75 FR 31223, 31243
(June 2, 2010). However, in section
III.H.4 of the November 2015 SNOPR,
DOE proposed to change the heating
load line, and as such the equations for
HSPF in ASHRAE 116–1995 (RA 2005)
are no longer applicable. In order to
prevent confusion, DOE proposed to
withdraw the original proposal made in
the June 2010 NOPR to reference
ASHRAE 116–1995 (RA 2005) for both
HSPF and SEER by removing those
VerDate Sep<11>2014
00:40 Jun 08, 2016
Jkt 238001
instances of these references. 80 FR
69278, 69311 (Nov. 9, 2015).
DOE also proposed to revise its
reference for the requirements of the air
flow measuring apparatus from
ASHRAE 116–1995 (RA 2005) to ANSI/
ASHRAE 37–2009. As this was the only
other reference to ASHRAE 116 in
Appendix M, DOE proposed to remove
the incorporation by reference to
ASHRAE 116–1995 (RA 2005) from the
Code of Federal Regulations related to
central air conditioners and heat pumps.
80 FR 69278, 69311 (Nov. 9, 2015).
AHRI, UTC/Carrier, Ingersoll Rand,
Goodman, Rheem, and JCI disagreed
with the proposal to withdraw the
incorporation by reference of ASHRAE
116–1995 (RA 2005). (AHRI, No. 70 at
p. 12; UTC/Carrier, No. 62 at pp. 17–18,
Ingersoll Rand, No. 65 at p. 3; Goodman,
No. 73 at p. 11; Rheem, No. 69 at p. 14;
JCI, No. 66 at p. 10) AHRI, UTC/Carrier,
Ingersoll Rand, Goodman, and JCI
suggested adding a reference to the
section on thermal mass correction to
the cyclic capacity (section 7.4.3.4.5) to
reduce variability. (AHRI, No. 70 at p.
12; UTC/Carrier, No. 62 at pp. 17–18,
Ingersoll Rand, No. 65 at p. 3; Goodman,
No. 73 at p. 11; JCI, No. 66 at p. 10)
DOE notes that the current test
procedure does not reference the
thermal mass correction to cyclic
capacity. DOE acknowledges that,
because ASHRAE 116 has been
incorporated by reference into the DOE
test procedure, and because the cyclic
test would first have been developed as
part of ASHRAE 116, it is
understandable that the prevailing
interpretation may have been that the
correction has always been included in
the DOE test procedure. DOE also
acknowledges that the thermal mass
stored in devices and connections
located between measured points must
be accounted for to ensure repeatability
and accuracy of a cyclic test. DOE
understands that accounting for thermal
mass in this way is common industry
practice. Therefore, DOE has included
provisions in section 3.5 of the final rule
requiring a thermal mass adjustment,
referencing section 7.4.3.4.5 of ASHRAE
116–2010. DOE notes that it has
updated the IBR from ASHRAE 116–
1995 (RA 2005) to ASHRAE 116–2010,
but the content of the referenced section
has not changed.
15. Additional Changes Based on AHRI
210/240-Draft
In August 2015, AHRI provided a
draft version of AHRI 210/240 for the
docket that will supersede the 2008
version once it is published. (AHRI
Standard 210/240-Draft, No. 45, See
EERE–2009–BT–TP–0004–0045) The
PO 00000
Frm 00045
Fmt 4701
Sfmt 4700
37035
draft version includes a number of
revisions from the 2008 version, some of
which already exist in DOE’s test
procedure, and some of which do not.
In the November 2015 SNOPR, DOE
proposed to adopt several of these
revisions. DOE noted that the final
published version of what is currently
the AHRI 210/240-Draft may not be
identical to the docketed draft, and that
if AHRI makes other than minor
editorial changes to the sections DOE
referenced in the SNOPR after
publication, DOE would adopt the
current draft content into its regulations
and not incorporate by reference the
modified test procedure. 80 FR 69278,
69312 (Nov. 9, 2015).
The AHRI 210/240-Draft added new
size requirements for the inlet duct to
the indoor unit, new external static
pressure requirements for units
intended to be installed with the airflow
to the outdoor coil ducted, and a new
requirement for the dew point
temperature of the indoor test room
when the air surrounding the indoor
unit is not supplied from the same
source as the air entering the indoor
unit. DOE proposed to adopt these three
revisions in the November 2015 SNOPR.
80 FR 69278, 69311 (Nov. 9, 2015).
DOE received comments from
Ingersoll Rand regarding the proposed
requirements for the inlet duct, which
are discussed in section III.E.18. DOE
did not receive any comments on the
new external static pressure and dew
point requirements and is adopting
these revisions in this final rule.
The AHRI 210/240-Draft included
differences as compared to the current
DOE test procedure for setting air
volume rates during testing. DOE
proposed to adopt three of these
changes because they would improve
repeatability and the consistency of
testing among different laboratories. 80
FR 69278, 69312 (Nov. 9, 2015). They
include (a) use of air volume rates
specified by manufacturers, (b) setting
ESP requirements for operating modes
other than full-load cooling, and (c)
establishing an instability criterion for
testing of units with constant-airvolume indoor blowers. DOE received
no comments regarding these proposals
and adopts them in this final rule.
DOE did receive several comments on
other proposals related to setting air
volume rates and has addressed these
comments and revisions in section
III.E.1.
The AHRI 210/240-Draft also
included a more thorough procedure for
setting of refrigerant charge than exists
in the DOE test procedure. DOE
proposed these changes because they
improve test repeatability.
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37036
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
The AHRI 210/240-Draft also specifies
both a target value tolerance and a
maximum tolerance but does not specify
in what circumstances each of these
apply. In response, UTC/Carrier
commented that they would like more
detail, as correct refrigerant charging has
a significant impact on performance and
product reliability. (UTC/Carrier, No. 62
at p. 18) DOE interprets this comment
as support of the additional detail
regarding instructions for setting charge
that were proposed in the November
2015 SNOPR, since the comment does
not provide clarification regarding
potential additional details that might
be needed.
As an elaboration on DOE’s past
methodology, DOE believed that the
AHRI 210/240-Draft did not clearly
delineate how target value and
maximum tolerances should be applied.
Following from this lack of clarity, in
the November 2015 SNOPR, DOE
proposed to adopt the most liberal
restriction on tolerance, the maximum
tolerance, disregarding the AHRI 210/
240-Draft target value. In addition, DOE
proposed tolerances on the measured
superheat and other parameters that
would be set to specified levels during
charging. 80 FR 69278, 69312 (Nov. 9,
2015). In this final rule, DOE continues
to reference the maximum tolerance
only. Additional comments regarding
the procedure for setting of refrigerant
charge, and revisions to the proposal are
discussed in section III.E.8.
Finally, the AHRI 210/240-Draft
included specifications for air sampling
that provide more detail than provided
in existing standards—DOE proposed
incorporation of a number of these air
sampling specifications into its test
procedures. DOE did not receive
comment on this proposal and is
adopting the specifications in this final
rule. However, DOE initially proposed
incorporation by reference of sections of
the AHRI 210/240-Draft, expecting that
the standard might be published prior to
this final rule. Because the AHRI
standard was not finalized in time to
incorporate the relevant sections of
AHRI 210/240 by reference, DOE
included the following provisions from
the AHRI 210/240 draft in this final rule
in order to finalize the proposal to adopt
Appendix E4 Air Sampling
Requirements in the November 2015
NOPR. DOE implemented these
provisions consistent with the way they
appear in the AHRI 210/240-Draft.
• DOE provided the definitions of Air
Sampling Device and Aspirating
Psychrometer to Section 1.2,
Definitions, in Appendix M.
• DOE provided Section 2.14, Air
Sampling Device and Aspirating
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Psychrometer Requirements, to
Appendix M based on E 4.4 and E 4.6
of AHRI 210/240-Draft.
• DOE integrated the outdoor test
setup instructions in E 4.2, E 4.4 and E
4.6 of AHRI 210/240-Draft and adopted
those in Section 2.11 of Appendix M,
with some revisions to improve clarity.
• In Section 2.11, DOE provided
additional instructions regarding
blockage of air sampling holes when
this is done to prevent sampling of
recirculated air. The revisions are
intended to preserve symmetry and
uniformity of air flow into the holes.
• In Section 2.11, DOE also clarified
that tubes conveying sampled air may
have reduced insulation requirements if
dry bulb temperature measurements are
made at the exit of each air sampler.
16. Damping Pressure Transducer
Signals
In the June 2010 NOPR, DOE
proposed to loosen the existing test
operating tolerance assigned to the
external resistance to airflow (ESP) from
0.05 to 0.12 in wc and the nozzle
pressure drop tolerance from 2.0 percent
to 8.0 percent. 75 FR 31223, 31234 (June
2, 2010).
In response to the June 2010 NOPR
proposal, NEEA commented that it
strongly disagreed with DOE’s proposal,
particularly for the ESP tolerance. NEEA
also commented that it strongly
supported another option presented by
DOE at the June 11, 2010 public
meeting, which is to lengthen the time
constant for the measurements by signal
integration and averaging, using a DOEspecified interval. (NEEA, No. 7 at p. 4)
AHRI commented that they disagreed
with DOE’s proposal to relax ESP and
nozzle pressure drop tolerances. AHRI
believed that the pressure transducer
fluctuation issues could be resolved by
implementing a time averaging routine
or some kind of electronic damping
algorithm that would provide the same
results as a liquid manometer, using an
algorithm agreed upon by AHRI
members. (AHRI, No. 6 at p. 3)
In the November 2015 SNOPR, rather
than proposing a revision of the
operating tolerances for external
resistance to airflow or nozzle pressure
drop, DOE proposed to add clarifying
language in the test procedure that
would allow for damping of the
measurement system to prevent highfrequency fluctuations from affecting
recorded pressure measurements. The
proposal allowed for damping of the
measurement system so that the time
constant for response to a step change
in pressure (i.e. the time required for the
indicated measurement to change 63%
of the way from its initial value to its
PO 00000
Frm 00046
Fmt 4701
Sfmt 4700
final value) would be no more than five
seconds. This damping could be
achieved in any portion of the
measurement system. 80 FR 69278,
69312 (Nov. 9, 2015).
Rheem agreed with DOE’s November
2015 SNOPR proposal regarding
operating tolerances for external
resistance to airflow or nozzle pressure
drop. (Rheem, No. 69 at p. 15) JCI also
agreed with that approach, but
suggested that the time constant for
response to a step pressure signal
should be increased to 10 or 15 seconds,
without providing an explanation why
the slower response is needed. (JCI, No.
66 at p. 20) No commenters disagreed
with the proposal. The intent of the
damping is to address fluctuations
associated with turbulence that would
have a frequency so high that they
would not be captured with a system
with a 5 second response time. In the
absence of more explanation regarding
why the 5 second response is
insufficient, DOE maintains this value
for the damping allowance and, due to
the absence of dissenting comments,
DOE adopts this revision in the test
procedure.
17. Clarify Inputs for the Demand
Defrost Credit Equation
In the June 2010 NOPR, DOE
proposed language in the test procedure
to clarify that manufacturers must
assign Dtdef (the greater of the time in
hours between defrost terminations and
1.5) the value of 6 hours if this limit is
reached during a frost accumulation test
and the heat pump has not completed
a defrost cycle. A sentence was also
proposed to be added in section 3.9.2 of
Appendix M to indicate that the
manufacturer must use a value of Dtmax,
that is either the maximum time
between defrosts as allowed by the
controls (in hours) or 12, whichever is
less. 75 FR at 31237 (June 2, 2010). In
the proposal of the November 2015
SNOPR, this was changed to indicate
that the value would be as provided in
the installation manuals shipped with
the unit. 80 FR at 69373 (Nov. 9, 2016).
AHRI supported DOE’s proposal to
clarify inputs to the demand defrost
credit equation with the understanding
that HSPF values would not be affected
by such clarifications. (AHRI, No. 6 at
p. 4) Ingersoll Rand stated that the facts
do not support AHRI’s understanding as
there are significant numbers of heat
pumps for which the reduction of the
maximum permissible test duration
from 12 to 6 hours would decrease the
calculated HSPF. Ingersoll Rand further
commented that reducing max duration
of frost accumulation tests from 12
hours to 6 hours and eliminating the
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
short-cut method for determining SEER
would reduce the rated performance of
AC/HP, which would be an adverse
situation for manufacturers. Ingersoll
Rand commented that this would
require re-rating of units that are above
13 SEER and un-rating units that are at
13 SEER. (Ingersoll Rand, No. 10 at p.
1)
As noted in the June 2010 SNOPR, for
most two-capacity and variable-speed
heat pumps the proposal for the 6-hour
limit reduces manufacturer test burden
when defrost does not occur. DOE
believes that when defrost does occur,
the proposal has a negligible impact on
the calculation of the average heating
capacity and power consumption at a 35
°F outdoor temperature. Shortening the
maximum duration of the frost
accumulation test affects heat pumps
that would otherwise conduct a defrost
after 6 but before 12 hours in two ways.
First, such heat pumps benefit slightly
from not having a defrost cycle factored
into their average heating capacity
calculation. Second, they earn a higher
demand defrost credit than they would
have earned previously. As a worst case
(e.g., unit’s demand defrost controls
actuate at 11.999 hours while the unit’s
maximum duration is 12 hours or more),
the approximated demand defrost credit
is now 1.017 compared to the ‘‘true’’
value of 1.000. 75 FR 31223, 31236–37
(June 2, 2010). The HSPF is directly
proportional to the demand defrost
credit factor (see Equation 4.2–1 of
Appendix M), hence, this would
represent a 1.7 percent increase in
HSPF. Ingersoll Rand did not provide
any justification for why it did not agree
with DOE’s analysis regarding the
impact of the change. Therefore, DOE
adopts this revision in the test
procedure.
18. Improving Test Consistency
Associated With Indoor Unit Air Inlet
Geometry
Ingersoll Rand commented that the
range of inlet geometries allowed by the
DOE test procedure for ducted units
may lead to different test results,
specifically different measurements of
static pressure and (for blower coil and
single-package units) fan input power,
depending on what specific inlet
geometry is selected for conducting a
test. They recommended that DOE adopt
the short duct minimal requirement
described in the draft version of AHRI
210/240–2015. (Ingersoll Rand, No. 65
at p. 6–10)
DOE first reviewed the inlet
configurations that Ingersoll Rand
evaluated and claimed are all compliant
with the DOE inlet equipment
connection requirements. DOE does not
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
agree that the current test procedure
allows Configuration #7, in which the
inlet plenum for measurement of inlet
static pressure is upstream of the
damper box. Section 2.5.1.1 of the
current test procedure states, ‘‘install
the inlet damper box upstream of the
inlet plenum.’’ This was proposed to be
modified in the November 2015 SNOPR
to read, ‘‘Install the airflow prevention
device upstream of the inlet plenum
. . .’’. Configuration #7 is inconsistent
with both descriptions. DOE notes that
the greatest deviation in static pressure
measurements presented by Ingersoll
Rand is associated with Configuration
#1, in which there is neither an inlet
plenum nor a damper box, and the inlet
static pressure simply measures room
pressure. In this case, the measured
inlet static pressure would generally be
higher than measured using an inlet
plenum, because part of the static
pressure within the room is converted to
inlet velocity pressure as the room air is
accelerated towards the unit’s inlet.
DOE agrees that for consistency it would
be beneficial to avoid Configuration #1
in testing. Hence, the final rule
established in today’s notice does not
allow use of this arrangement. DOE
believes that most units will be tested
with damper boxes (or other airflow
prevention devices) in order to conduct
the cyclic test, because of the measured
performance improvement associated
with use of the measured cyclic
degradation coefficient, which is often
less than the default coefficient that can
be used if the cyclic test is not
conducted. Hence, DOE does not believe
that many, if any, tests are conducted
using Configuration #1. Thus, adopting
this change should ensure test
consistency with inconsequential
impact on test burden.
Responding to potential
misinterpretation of the requirements
for air inlet geometry (e.g. regarding
Configuration #7 discussed above), DOE
made some clarifying revisions in this
final rule that were not part of the
proposals in the NOPR or SNOPRs. The
revisions include, (a) rearranging the
text of section 2.4.2 regarding the inlet
plenum for the indoor unit, (b)
clarifying that figures 7b and 7c of
ANSI/ASHRAE 37–2009 are for blower
coil indoor units or single-package units
while figure 8 is for coil-only units, and
(c) clarifying that when an inlet plenum
is not used that the length of straight
duct upstream of the unit’s inlet within
the airflow prevention device must still
adhere to the inlet plenum length
requirements, as illustrated in ANSI/
ASHRAE 37–2009, figures 7b, 7c, and 8.
PO 00000
Frm 00047
Fmt 4701
Sfmt 4700
37037
F. Clarification of Test Procedure
Provisions
This section discusses clarifications to
the test procedure to address test
procedure provisions that may lack
sufficient specificity to ensure
reproducibility. None of the
clarifications listed in this section
would alter the average measured
energy consumption of a representative
set of models.
1. Manufacturer Consultation
In the November 2015 SNOPR, DOE
proposed to clarify the test procedure
provisions regarding the specifications
for refrigerant charging prior to testing,
with input on certain details from the
AHRI 210/240-Draft, as discussed in
section III.E.15. Specifically, DOE
proposed to remove the current test
procedure’s allowance for contacting the
manufacturer to receive charging
instructions. In instances where
multiple sets of instructions are
specified or are included with the unit
and the instructions are unclear on
which set to test with, DOE proposed
the use of field installation criteria. 80
FR 69278, 69313 (Nov. 9, 2015).
ADP and Lennox commented that
before using standard sub-cooling and
superheat values, the test facility should
contact the manufacturer to obtain
instructions in cases where they have
been misplaced, and in all cases the test
facility should contact the manufacturer
to request the latest version of the
installation instructions. ADP and
Lennox commented that given the level
of inventory in the industry, testing an
off-the-shelf unit solely based on the
installation instructions in the box with
the unit could result in outdated
instructions being used. (ADP, No. 59 at
p. 10; Lennox, No. 61 at p. 17–18)
After reviewing these comments, DOE
maintains that it is not necessary to
contact the manufacturer for the latest
refrigerant charging requirements, and
that the instructions provided with the
unit should be used as the unit should
have been certified by the manufacturer
as compliant with the information
provided with the unit. Therefore, DOE
has adopted this provision in the final
rule.
In the November 2015 SNOPR, DOE
also proposed to revise language
proposed in previous NOPRs regarding
the metering of low-voltage transformers
to eliminate the need for
communication between third party test
laboratories and manufacturers. 80 FR
69278, 69313 (Nov. 9, 2015). No
comments were received on this
proposal, and DOE adopts this provision
in the final rule.
E:\FR\FM\08JNR2.SGM
08JNR2
37038
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
DOE also proposed to require
manufacturers to report on their
certification report whether the test was
conducted with or without an inlet
plenum installed in order to eliminate
the need for the test laboratory to
confirm this with the manufacturer. 80
FR 69278, 69313 (Nov. 9, 2015).
In response, AHRI, Nortek
commented that it is burdensome and
unnecessary to submit this data. (AHRI,
No. 70 at p. 14; Nortek, No. 58 at p. 11)
ADP, Unico, and Ingersoll Rand
commented that they agreed with AHRI
on this matter. (ADP, No. 59 at p. 7;
Unico, No. 63 at p. 6; Ingersoll Rand,
No. 65 at p. 12) JCI, UTC/Carrier,
Lennox, and Mitsubishi commented
generally that additional reporting
requirements impose an unnecessary
burden on manufacturers, which is
discussed in section III.A.5. (JCI, No. 66
at p. 12; UTC/Carrier, No. 62 at p. 7;
Lennox, No. 61 at pp. 14–15;
Mitsubishi, No. 68 at pp. 1–2)
As discussed in section III.E.18, DOE
has modified the test procedure to
require the use of an inlet plenum or an
inlet airflow prevention device that also
provides the function of an inlet
plenum, for ducted split-system or
single-package units. Hence, this
reporting requirement is not needed and
DOE has removed it in the final rule.
DOE proposed to amend references in
the test procedure to test setup
instructions or manufacturer
specifications by specifying that these
refer to the test setup instructions
included with the unit. DOE proposed
to implement this change in the
following sections: 2.2.2, 3.1.4.2(c),
3.1.4.4.2(c), 3.1.4.5(d), and 3.5.1(b)(3).
80 FR 69278, 69313 (Nov. 9, 2015). No
comments were received on this
proposal, and DOE adopts this provision
in the final rule.
2. Incorporation by Reference of AHRI
1230–2010
ANSI/AHRI Standard 1230–2010
‘‘Performance Rating of Variable
Refrigerant Flow (VFR) Multi-Split AirConditioning and Heat Pump
Equipment’’ with Addendum 2 (AHRI
1230–2010) prescribes test requirements
for both consumer and commercial
variable refrigerant flow multi-split
systems. In the November 2015 SNOPR,
DOE proposed to incorporate by
reference the sections of AHRI 1230–
2010 that are relevant to consumer
variable refrigerant flow multi-split
systems (namely, sections 3 (except 3.8,
3.9, 3.13, 3.14, 3.15, 3.16, 3.23, 3.24,
3.26, 3.27, 3.28, 3.29, 3.30, and 3.31),
5.1.3, 5.1.4, 6.1.5 (except Table 8), 6.1.6,
and 6.2) into the existing test procedure
for central air conditioners and heat
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
pumps at Appendix M to Subpart B of
10 CFR part 430. 80 FR 69278, 69313
(Nov. 9, 2015).
In response to this proposal, JCI,
AHRI, Nortek, Unico, Mitsubishi and
Rheem supported applying AHRI 1230
for VRF testing. (JCI, No. 66 at p. 20;
AHRI, No. 70 at p. 17; Nortek, No. 58
at p. 14; Unico, No. 63 at p. 12;
Mitsubishi, No. 68 at p. 4; Rheem, No.
69 at p. 15) In contrast, Goodman
commented that all products in the
residential market should be tested
using the same test procedure, and
suggested multi-split air conditioners
should be tested via AHRI 210/240.
(Goodman, No. 73 at p. 15–16) As
virtually all commenters support the use
of the industry test procedure AHRI
1230 for multi-split air conditioners,
DOE incorporates by reference certain
sections of AHRI 1230–2010 as
proposed.
DOE also proposed to define the terms
‘‘Multiple-split (or multi-split) system’’,
‘‘Small-duct, high-velocity system’’,
‘‘Tested combination’’, ‘‘Variable
refrigerant flow system’’ and ‘‘Variablespeed compressor system’’ in its list of
definitions in Appendix M to Subpart B
of 10 CFR part 430. 80 FR 69278, 69313
(Nov. 9, 2015).
Regarding tested combination, AHRI
had requested in response to the June
2010 NOPR that DOE use the ‘‘tested
combination’’ definition in AHRI 1230–
2010 (the definition appears in section
3.26 of this standard). (AHRI, No. 6 at
pp. 1–2) In the November 2015 SNOPR,
DOE proposed a definition which is
nearly identical to the AHRI 1230–2010
definition, except that (a) the AHRI
definition allows a maximum of 12
indoor units in the tested combination—
the DOE proposal calls for up to five
indoor units, (b) the DOE proposal
allows use of an indoor unit model
family other than the highest sales
volume family if the 95 percent capacity
threshold cannot be met with units of
the highest sales volume family, and (c)
DOE’s proposal provided clarification of
what is meant by indoor unit nominal
capacity. 80 FR at 69313–14 (Nov. 9,
2015). Commenters did not specifically
address these provisions in their
comments regarding the November 2015
SNOPR, and hence the final rule adopts
them.
In addition, both AHRI and
Mitsubishi had commented in response
to the June 2010 NOPR that DOE should
remove the requirement to turn off one
of the indoor units when testing at
minimum compressor speed. (AHRI, No.
6 at p. 2, Mitsubishi, No. 12 at p. 1) DOE
established this test requirement for
multi-split systems in a final rule
published October 22, 2007. 72 FR
PO 00000
Frm 00048
Fmt 4701
Sfmt 4700
59906–59909. DOE had initially
considered a more aggressive approach
in the October 2007 Final Rule for
turning off indoor units at part load in
which the number of operating units
would be proportional to the load level,
but settled instead on turning off just
one unit for minimum compressor
speed. Id. at 59909. Multi-split systems
have indoor units that respond
individually to separate thermostats.
The outdoor units are designed to
operate when one or more of the indoor
units are not operating. It certainly
would be expected that, for a large
percentage of the time that such a unit
operates at minimum compressor speed,
at least one of the indoor units would
have cycled off. The test approach
suggested by AHRI and Mitsubishi is
more consistent with the operation of
multi-head mini-split systems, for
which all of the indoor units operate in
unison in response to a single
thermostat, rather than the operation of
multi-split systems—for such systems,
all indoor units would always be
operating when the outdoor unit is at
minimum compressor speed. DOE is not
aware of any field test information that
shows that all of the indoor units of a
multi-split system continue to operate
when the compressor is at minimum
speed. Hence, DOE is maintaining the
requirement to turn off one indoor unit
for the minimum-speed tests.
Finally, Mitsubishi had also
commented, in response to the June
2010 NOPR, that the 50% requirement
be waived for multi-split systems with
cooling capacity less than 24,000 Btu/h,
and that the 95% to 105% capacity
requirement for match between indoor
and outdoor nominal capacities be
considered a guideline rather than a
requirement. (AHRI, No. 6 at p. 2,
Mitsubishi, No. 12 at pp. 1–2) The 50%
requirement (i.e. that none of the indoor
units of the tested combination have a
nominal cooling capacity greater than
50% of the outdoor unit’s nominal
cooling capacity) has been adopted by
DOE. DOE will not adopt the latter
recommendation, since it would
essentially eliminate any requirement
for capacity matching, but has instead
increased the flexibility of the
requirements by allowing use of model
families of indoor units other than the
highest sales volume model family, if all
of the tested combination requirements
cannot be met by the highest sales
volume family.18 DOE notes that it has
clarified this allowance in this final
18 Examples of model families include
configurations such as mid-range static ducted,
high-static ducted, wall-mount, ceiling-mount 4way cassette, ceiling-mount 2-way cassette, etc.
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
rule—whereas the proposed wording
referenced inability to meet the 95%
capacity threshold as the basis for
considering other model families, the
allowance in this final rule explicitly
states that if all the requirements for
‘‘tested combination’’ cannot be met by
indoor units selected from the highest
sales volume model family, that one or
more indoor units could be selected
from a different sales model family.
Comments received regarding the
term ‘‘multiple-split system’’ are
discussed in section III.F.5. DOE did not
receive comments on the other
definitions and adopts them as
proposed.
In the November 2015 SNOPR, DOE
also proposed to omit Table 8 of AHRI
1230–2010 from the IBR into Appendix
M and to set minimum ESP
requirements for systems with short-run
ducted indoor units in Table 3 of
Appendix M as follows: 0.03 in. w.c. for
units less than 28,800 Btu/h; 0.05 in.
w.c. for units between 29,000 Btu/h and
42,500 Btu/h; and 0.07 in. w.c. for units
greater than 43,000 Btu/h. Furthermore,
DOE proposed to define the term ‘‘short
duct systems,’’ to refer to ducted
systems whose indoor units can deliver
no more than 0.07 in. w.c. ESP when
delivering the full load air volume rate
for cooling operation. 80 FR 69278,
69314 (Nov. 9, 2015).
DOE received several comments in
response to its proposal related to short
duct systems and the required ESP.
However, the CAC/HP ECS Working
Group included recommendations to
DOE regarding definitions and ESP for
low-static and mid-static units rather
than short duct systems. (Docket No.
EERE–2014–BT–STD–0048, No. 76 at p.
1–2) Therefore, in this final rule, DOE
is not adopting a definition or ESP
requirement for short duct systems and
will consider changes to the ESP for
certain kinds of systems in a separate
notice.
3. Replacement of the Informative
Guidance Table for Using the Federal
Test Procedure
In the November 2015 SNOPR, DOE
proposed replacing the set of four tables
at the beginning of ‘‘Section 2, Testing
Conditions’’ of the current test
procedure (10 CFR part 430, subpart B,
Appendix M) with a more concise table
to provide guidance to manufacturers
regarding testing conditions, testing
procedures, and calculations
appropriate to a product class, system
configuration, modulating capability,
and special features of products. 80 FR
69278, 69314 (Nov. 9, 2015).
JCI commented the tables provide
adequate clarity but that the table would
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
be more viewable if placed in a portrait
view. (JCI, No. 66 at p, 20–21). UTC/
Carrier responded that they would like
any clarity DOE can provide. (UTC/
Carrier, No. 62 at p. 19) Rheem
expressed the preference of the current
table over the proposed table in the
November 2015 SNOPR and suggested
that DOE further clarify the proposed
table, including adding a title and
explanation of how it should be used.
Rheem also pointed out a possible error
under testing conditions for single-splitsystem coil-only. (Rheem, No. 69 at
p.16).
Given the general consensus on the
proposed table, DOE is adopting the
format of the proposed table in this final
rule with some clarification. DOE found
it difficult to fit the eight columns
within the table in the portrait view
suggested by JCI, and maintains the
landscape format. In response to Rheem,
the proposed table is titled ‘‘Informative
Guidance for Using Appendix M’’ and
an explanation of how it should be used
is given in section 2 (B) of this final rule
notice. DOE conducted further review
and revision to the proposed table to
clarify the sections each test should
refer to, including fixing the identified
error on single-split-system coil-only
test conditions.
4. Clarifying the Definition of a MiniSplit System
In the November 2015 SNOPR, DOE
proposed deleting the definition of
mini-split air conditioners and heat
pumps, and adding two definitions for:
(1) single-zone-multiple-coil split
system, representing a split system that
has one outdoor unit and that has two
or more coil-only or blower coil indoor
units connected with a single
refrigeration circuit, where the indoor
units operate in unison in response to
a single indoor thermostat; and (2)
single-split system, representing a split
system that has one outdoor unit and
that has one coil-only or blower coil
indoor unit connected to its other
component(s) with a single refrigeration
circuit. 80 FR 69278, 69314 (Nov. 9,
2015).
ADP, Lennox, and UTC/Carrier
supported DOE’s proposal. (ADP, No. 59
at p. 12; Lennox, No. 61 at p. 19; UTC/
Carrier, No. 62 at p. 20)
AHRI and Nortek proposed modifying
the current definition to reflect common
terminology used in the field. (AHRI,
No. 70 at p. 17–18; Nortek, No. 58 at p.
14) AHRI and Mitsubishi recommended
the terminology and definitions be
revised as follows: (1) single head minisplit system, representing split systems
that have a single outdoor section and
one indoor section, where the indoor
PO 00000
Frm 00049
Fmt 4701
Sfmt 4700
37039
section cycles on and off in unison in
response to a single indoor thermostat;
and (2) multi head mini-split system,
representing split systems that have a
single outdoor section and more than
one indoor sections, where the indoor
sections cycle on and off in unison in
response to a single indoor thermostat.
(AHRI, No. 70 at p. 17–18; Mitsubishi,
No. 68 at p. 4)
Goodman commented that they do not
support the terminology of ‘‘single-zonemultiple-coil split system’’ and that
there is no need to separate a one-to-one
split system and a one-to-multiple split
system. However, Goodman also
suggested using the terms single-head
mini-split and multi-head mini-split if
DOE desires to separate the definition of
mini-split into two categories.
(Goodman, No. 73 at p. 7)
Mitsubishi also specifically
recommended that the references to
‘‘coil-only’’ be removed since Appendix
M does not permit the matching of a
variable speed outdoor unit with a coil
without a blower that can match the
airflow required for each of the tests.
(Mitsubishi, No. 68 at p. 4)
In response to the recommended
terminology from AHRI, Nortek,
Mitsubishi, and Goodman, DOE is
adopting the term ‘‘multi-head minisplit system’’ in the regulatory text
rather than the proposed ‘‘single-zone
multiple-coil system.’’ However, DOE
believes it is important to specify that
this system has a single refrigerant
circuit, which is not part of the
definition proposed by AHRI and
Mitsubishi. In response to Mitsubishi,
DOE has removed ‘‘coil-only’’ from the
definition but cautions that this does
not mean that the definition does not
include systems with coil-only indoor
units. DOE notes that the definition is
not explicitly limited to variable-speed
units, although DOE is aware that most
of not all commercially available units
that fit the definition have variablespeed compressors. For these reasons,
DOE adopts the following definition for
‘‘multi-head mini-split system’’:
Multi-head mini-split system means a
split system that has one outdoor unit
and that has two or more indoor units
connected with a single refrigeration
circuit. The indoor units operate in
unison in response to a single indoor
thermostat.
DOE is adopting the definition for
single-split system as proposed in the
SNOPR. DOE is not adopting a
definition for ‘‘single-head mini-split,’’
as this variety of unit is included in the
‘‘single-split system’’ definition and
there are no different test procedure
requirements or energy conservation
standard levels that would require
E:\FR\FM\08JNR2.SGM
08JNR2
37040
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
establishing a separate definition to
distinguish these products.
5. Clarifying the Definition of a MultiSplit System
In the November 2015 SNOPR, DOE
proposed to clarify the definition of
multi-split system to specify that multisplit systems are to have only one
outdoor unit. (DOE notes that it
proposed to separately define multicircuit units as units that incorporate
multiple outdoor units into the same
package. This is discussed in section
III.C.1.) DOE also proposed to clarify
that if a model of outdoor unit could be
used both for single-zone-multiple-coil
split systems (multi-head mini-split
systems) and for multi-split systems, it
should be tested as a multi-split system.
80 FR 69278, 69315 (Nov. 9, 2015).
In response, the California IOUs
stated that the proposed definition was
unclear and recommended the following
definition: A multiple zone, multiple
coil, split system is a split system with
one outdoor unit and at least two coilonly or blower coil indoor units which
operate separately as required to
provide comfort in the zone each serves.
(California IOUs, No. 67 at p. 6). DOE
received no other comments on this
issue.
The multi-split system definition
suggested by California IOUs does not
specify that the outdoor units and the
indoor units are within a single
refrigerant circuit, and therefore multicircuit systems, which are tested
differently, would fit in this definition.
In order to preserve the distinction
between multi-split and multi-circuit
products, DOE adopts the proposed
multi-split system definition from the
November 2015 SNOPR, which clarifies
that for multi-split systems all
components are connected with a single
refrigerant circuit.
6. Clarifying the Housing for Uncased
Coil
The current test procedure provides
instructions for installing uncased coil
indoor units, indicating that an
enclosure be provided for them using 1
in. fiberglass ductboard (see Appendix
M, section 2.2.c). DOE is aware of issues
associated with the use of fiberglass
ductboard, as its lack of rigidity can
present challenges in maintaining tight
seals where it connects to upstream and
downstream ducts used in the test setup. DOE also notes that the
requirements of section 2.2.c regarding
both the ductboard and its installation
are unnecessarily limited in the
approaches listed for fabricating an
enclosure for the test. DOE is aware that
test laboratories fabricate enclosures for
testing uncased coils that consist of
materials other than just the listed
fiberboard or alternative insulation.
DOE also understands that the term
‘‘fiberboard’’ is not sufficiently
descriptive to assure that a foil-faced
fiberboard be used, which would be
consistent with the expectation that
such a casing provide a barrier to both
air flow and water vapor transmission.
As a result, DOE is clarifying these
instructions with additional language in
this final rule regarding the installation
of uncased coils, including (a)
indicating that the ductboard must be
foil-faced, (b) allowing alternative
housings, consisting of sheet metal or
similar material and separate insulation,
and (c) indicating that sizing and
installation of the casing should be done
as described in the installation
instructions shipped with the unit.
These clarifications are consistent with
DOE’s proposal in the November 2015
SNOPR and its understanding and
expectations of how these tests are being
conducted and should be conducted.
Although most ductboard material is
foil-faced, DOE has clarified that
alternative materials claimed to be
ductboard should not be used—without
the foil facing, the ductboard would not
present a sufficient barrier to vapor and
air penetration. These alternative
housing materials (i.e. alternatives to
foil-faced fiberboard) will allow for
more rigid construction of the coil
housing. Finally, DOE recognizes that
details regarding the fabrication and
installation of the housing may affect
test results and hence clarifies that they
should be performed as described in
installation instructions shipped with
the unit. These changes would not affect
any tests being conducted consistent
with existing requirements (e.g. for
negligible air leakage and installation
according to shipped instructions.) but
are intended to clarify set-up procedures
to enhance consistency of testing.
7. Test Procedure Reprint
DOE has reprinted the entirety of
Appendix M to 10 CFR part 430 Subpart
B in the regulatory text for this final rule
to improve clarity regarding the
revisions established by this final rule.
Table III.6 lists proposals from the
previous notices that appear in this
regulatory text reprint, and provides
reference to the respective revised
section(s) in the regulatory text.
TABLE III.6.—TEST PROCEDURE AMENDMENTS ADOPTED IN THIS FINAL RULE
[By original proposal]
Section
Proposal to . . .
Reference
Preamble
discussion
Regulatory text location *
June 2010 NOPR
A.7 ..........
A.9 ..........
A.10 ........
B.1 ..........
B.3 ..........
B.4 ..........
asabaliauskas on DSK3SPTVN1PROD with RULES
B.5 ..........
B.6 ..........
B.7 ..........
Add Calculations for Sensible Heat Ratio ...................................
Modify Definition of Tested Combination .....................................
Add Definitions Terms Regarding Standby Power ......................
Modify the Definition of ‘‘Tested Combination’’ ...........................
Clarify That Optional Tests May Be Conducted Without Forfeiting Use of the Default Value(s).
Allow a Wider Tolerance on Air Volume Rate To Yield More
Repeatable Laboratory Setups.
Change the Magnitude of the Test Operating Tolerance Specified for the External Resistance to Airflow.
Change the Magnitude of the Test Operating Tolerance Specified for the Nozzle Pressure Drop.
Modify Refrigerant Charging Procedures: Disallow Charge Manipulation after the Initial Charge.
Require All Tests be Performed with the Same Refrigerant
Charge Amount.
When Determining the Cyclic Degradation Coefficient CD, Correct the Indoor-Side Temperature Sensors Used During the
Cyclic Test To Align With the Temperature Sensors Used
During the Companion Steady-State Test, If Applicable:
Equation.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00050
75
75
75
75
75
FR
FR
FR
FR
FR
III.G.1
III.F.2
None
III.F.2
III.E.11
3.3c, 4.5.
10 CFR 430.2 Definitions.
Definitions.
10 CFR 430.2 Definitions.
3.2.1, 3.2.2.1, 3.2.3
75 FR 31233
III.E.1
3.1.4.1.1a.4(ii)
75 FR 31234
III.E.17
75 FR 31234
III.E.17
3.3d Table, 3.5h Table, 3.7a Table, 3.8.1 Table,
3.9f Table.
3.3d Table, 3.5h Table, 3.7a Table, 3.8.1 Table.
75 FR 31234
III.E.7
2.2.5.
75 FR 31235,
31250
75 FR 31235
III.F.1
2.2.5.8.
III.E.11
3.4c, 3.5i, 3.7e, 3.8
Fmt 4701
31229
31230
31231
31231
31233
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37041
TABLE III.6.—TEST PROCEDURE AMENDMENTS ADOPTED IN THIS FINAL RULE—Continued
[By original proposal]
Section
B.8 ..........
B.9 ..........
B.10 ........
B.11 ........
B.12 ........
B.13 ........
B.14 ........
B.17 ........
Proposal to . . .
Reference
When Determining the Cyclic Degradation Coefficient CD, Correct the Indoor-Side Temperature Sensors Used During the
Cyclic Test To Align With the Temperature Sensors Used
During the Companion Steady-State Test, If Applicable: Sampling Rate.
Clarify Inputs for the Demand Defrost Credit Equation ...............
Add Calculations for Sensible Heat Ratio ...................................
Incorporate Changes To Cover Testing and Rating of Ducted
Systems Having More Than One Indoor Blower.
Add Changes To Cover Triple-Capacity, Northern Heat Pumps
Specify Requirements for the Low-Voltage Transformer Used
When Testing for Off-Mode Power Consumption.
Add Testing Procedures and Calculations for Off Mode Power
Consumption.
Update Test Procedure References ............................................
Preamble
discussion
Regulatory text location *
75 FR 31236
None
3.3b, 3.7a, 3.9e, 3.11.1.1, 3.11.1.3, 3.11.2a.
75 FR 31236
75 FR 31237
75 FR 31237
III.E.17
III.G.1
III.C.3
75 FR 31238
75 FR 31238
III.C.4
III.F.1
3.9.2a.
3.3c, 4.5.
2.2.3, 2.2.3b, 2.4.1b, 3.1.4.1.1d, 3.1.4.2e,
3.1.4.4.2d, 3.1.4.5.2f, 3.2.2, 3.2.2.1, 3.6.2,
3.2.6, 3.6.7, 4.1.5, 4.1.5.1, 4.1.5.2, 4.2.7,
4.2.7.1, 4.2.7.2, 3.2.2.2 Table, 3.6.2 Table.
3.6.6, 4.2.6.
2.2d.
75 FR 31238
III.D
Definitions, 3.13, 4.3.
75 FR 31243
III.E.12
10 CFR 430.3 Definitions.
76 FR 18107
III.D
Definitions, 3.13, 4.3.
76 FR 18109
III.F.1
2.2d.
76 FR 18111
None
4.7.
75 FR 31238
III.D
Definitions, 3.13, 4.3.
76 FR 65618
76 FR 65620
76 FR 65620
III.D
III.D
III.D
Definitions, 3.13, 4.3.
Definitions.
Definitions, 3.13, 4.3.
76 FR 65621
76 FR 65622
III.D
III.D
Definitions, 3.13, 4.3.
Definitions, 3.13.
69282
69284
69285
69289
69290
69291
69292
69292
69292
69293
69294
69296
69296
69297
69297
69299
69299
III.A.1
III.A.2
III.A.3
III.A.4
III.A.5
III.A.6
III.A.7
III.B.1
III.B.2
III.B.3
III.B.4
III.B.5
III.B.6
III.B.7
III.B.8
III.C.2
III.C.3
430.2.
430.2.
429.16, 1.2.
429.16(a).
429.16(c).
429.16(a), 430.23.
429.134.
429.70(e).
429.70(e).
80 FR 69300
80 FR 69301
80 FR 69302
III.D.1
III.D.2
III.D.2
3.13.2.b.
3.13.1, 4.3.
3.13.1.e, 3.13.2.g.
80 FR 69302
III.D.7
3.13.1.c, 3.13.1.d, 3.13.2.c, 3.13.2.e, 3.13.2.f.
80
80
80
80
80
80
80
69302
69303
69304
69305
69306
69306
69307
III.D.7
III.D.7
III.D.3
III.E.1
III.E.3
III.E.4
III.E.5
3.13.1.e, 3.13.1.f, 3.13.2.g, 3.13.2.h.
3.13.1, 3.13.2.
429.16(a).
Table 2, 2.3.1.a, 3.1.4.1.1, 3.3(d).
2.2(a), 2.10.3.
2.5, 2.11.b, 3.1.8.
2.11.b.
80 FR 69307
80 FR 69307
III.E.6
III.E.7
2.5, 2.11.
3.2.4, 3.6.4, 4.1.4, 4.2.4.
80 FR 69307
80 FR 69308
III.E.8
III.E.9
2.2.5.8.
2.5(c).
80 FR 69309
80 FR 69309
III.E.10
III.E.11
2.7.
3.2.1, 3.2.2, 3.2.3, 3.2.4, 3.5, 3.6, 3.8.
April 2011 SNOPR
III.A .........
III.B .........
III.D ........
III.E .........
Revise Test Methods and Calculations for Off-Mode Power and
Energy Consumption.
Revise Requirements for Selecting the Low-Voltage Transformer Used During Off-Mode Test(s).
Add Calculation of the Energy Efficiency Ratio for Cooling
Mode Steady-State Tests.
Revise Off-Mode Performance Ratings .......................................
October 2011 SNOPR
III.A .........
III.C ........
III.D ........
III.D.1 .....
III.D.2 .....
Reduce Testing Burden and Complexity .....................................
Add Definition for Shoulder Season ............................................
Revise Test Methods and Calculations for Off-Mode Power and
Energy Consumption.
Add Provisions for Large Tonnage Systems ...............................
Add Requirements for Multi-Compressor Systems .....................
November 2015 SNOPR
III.A.1
III.A.2
III.A.3
III.A.4
III.A.5
III.A.6
III.A.7
III.B.1
III.B.2
III.B.3
III.B.4
III.B.5
III.B.6
III.B.7
III.B.8
III.C.2
III.C.3
......
......
......
......
......
......
......
......
......
......
......
......
......
......
......
.....
.....
III.D.1 .....
III.D.2 .....
III.D.3 .....
asabaliauskas on DSK3SPTVN1PROD with RULES
III.D.4 .....
III.D.5
III.D.6
III.D.8
III.E.1
III.E.2
III.E.3
III.E.4
.....
.....
.....
......
......
......
......
III.E.5 ......
III.E.6 ......
III.E.7 ......
III.E.8 ......
III.E.9 ......
III.E.10 ....
Basic Model Definition .................................................................
Additional Definitions ....................................................................
Determination of Certified Rating .................................................
Compliance with Federal (National or Regional) Standards .......
Certification Reports .....................................................................
Represented Values .....................................................................
Product-Specific Enforcement Provisions ....................................
AEDM General Background .........................................................
AED< Terminology .......................................................................
Elimination of the ARM Pre-Approval Requirement ....................
AEDM Validation ..........................................................................
AEDM Requirements for Independent Coil Manufacturers .........
AEDM Verification Testing ...........................................................
Failure to Meet Certified Ratings .................................................
Action Following a Determination of Noncompliance ..................
Termination of Waivers Pertaining to Multi-Circuit Products .......
Termination of Waiver and Clarification of the Test Procedure
Pertaining to Multi-Blower Products.
Off-Mode Test Temperatures .......................................................
Off-Mode Calculation and Weighting of P1 and P2 ....................
Off-Mode: Products with Large, Multiple or Modulated Compressors.
Off-Mode: Procedure for Measuring Low-Voltage Component
Power.
Off-Mode: Revision of Off-Mode Power Consumption Equations
Off-Mode Power Consumption for Split Systems ........................
Test Metric for Off-Mode Power Consumption ............................
Indoor Fan Speed Settings ..........................................................
Requirements for the Refrigerant Lines and Mass Flow Meter ..
Outdoor Room Temperature Variation ........................................
Method of Measuring Inlet Air Temperature on the Outdoor
Side.
Requirements for the Air Sampling Device .................................
Variation in Maximum Compressor Speed with Outdoor Temperature.
Refrigerant Charging Requirements ............................................
Alternative Arrangement for Thermal Loss Prevention for Cyclic
Tests.
Test Unit Voltage Supply .............................................................
Coefficient of Cyclic Degradation .................................................
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00051
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
FR
Fmt 4701
Sfmt 4700
429.70(e)(2).
429.16.
429.104, 429.70(e)(5).
429.70(e)(5)(iv).
429.110, 429.70.
429.16(a)(1)(ii)(A), 2.4.1b.
3.1.4.1.1.d, 3.1.4.2.e.
E:\FR\FM\08JNR2.SGM
08JNR2
37042
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
TABLE III.6.—TEST PROCEDURE AMENDMENTS ADOPTED IN THIS FINAL RULE—Continued
[By original proposal]
Section
III.E.11
III.E.12
III.E.13
III.E.14
Proposal to . . .
Preamble
discussion
Reference
....
....
....
....
Break-in Periods Prior to Testing .................................................
Industry Standards that are Incorporated by Reference .............
Withdrawing References to ASHRAE 116–1995 (RA 2005) .......
Additional Changes Based on AHRI 210/240-Draft ....................
80
80
80
80
69309
69310
69311
69311
III.E.12
III.E.13
III.E.14
III.E.15
III.E.15 ....
III.F.1 ......
Damping Pressure Transducer Signals .......................................
Manufacturer Consultation ...........................................................
80 FR 69312
80 FR 69313
III.E.16
III.F.1
III.F.2 ......
Incorporation by Reference of AHRI 1230–2010 ........................
80 FR 69313
III.F.2
III.F.3 ......
Replacement of the Informative Guidance Table for Using the
Federal Test Procedure.
Clarifying the Definition of a Mini-Split System ...........................
Clarifying the Definition of a Multi-Split System ..........................
80 FR 69314
III.F.3
Table 2, 2.2.5.4.a, 2.2.5.5, 2.3.1.a, 2.4.2, 2.5,
2.11, 3.1.3.1, 3.1.4.1.1, 3.1.5, 3.3(d).
2.6(a).
2.2.5, 2.4.2, 2.2.2, 3.1.4.2(c), 3.1.4.4.2(c),
3.1.4.5(d), 3.5.1(b)(3).
1, 3.12, 2.2.a, 2.2.b, 2.2.c, 2.2.1, 2.2.2,
2.2.3(a), 2.2.3(c), 2.2.4, 2.2.5, 2.4–2.12,
Table 3, section 3.1 (except sections 3.1.3,
3.1.4), 3.3, 3.4, 3.5, 3.7–3.10, 3.13, 4.
Table 1.
80 FR 69314
80 FR 69315
III.F.4
III.F.5
1.2.
1.2.
III.F.4 ......
III.F.5 ......
FR
FR
FR
FR
Regulatory text location *
3.1.7.
430.3.
* Section numbers in this column refer to the Appendix M test procedure finalized in this notice.
asabaliauskas on DSK3SPTVN1PROD with RULES
G. Additional Comments From
Interested Parties
This section discusses additional
comments made by interested parties
during this rulemaking that were
unrelated to any of DOE’s proposals.
1. Wet Coil Performance
NREL requested DOE require
reporting of latent load or amount of
water condensation removal at each test
condition to be able to compare
equipment performance between dry
and humid regions. NREL also
recommend adding two new coolingmode test conditions to provide better
representation of performance in hot dry
regions and three new test cooling-mode
conditions for hot humid regions.
(NREL, No. 14 at p. 1)
In the June 2010 NOPR DOE proposed
to add a calculation of the sensible heat
ratio (SHR) to its test procedure to
provide consumers and their contractors
with more information to allow them to
make more informed decisions
regarding product selections. 75 FR
31223, 31237 (June 2, 2010). In
response, UTC/Carrier and JCI noted in
its comments that SHR is currently
provided in manufacturer’s product
data. (UTC/Carrier, No. 62 at p. 7; JCI,
No. 66 at p. 12). In this final rule, DOE
agrees that SHR was intended to be
provided in manufacturer literature and
has not adopted the November 2015
SNOPR proposal to require SHR be
reported to DOE (see Section III.A.5)
The latent load and water condensate
rate can be calculated based on the SHR
in manufacturers’ product literature and
the rated cooling capacity, which
should provide sufficient representation
of wet coil performance.
The DOE test procedure requires units
to be tested at 80 °F dry bulb
temperature and 67 °F wet bulb
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
temperature during wet-coil cooling test
to represent typical indoor conditions.
DOE does not disagree that the
additional test points proposed by NREL
would provide additional representation
of performance in hot dry and hot
humid regions. However, requiring
those additional tests would impose
significant test burden on
manufacturers. Currently, for a singlecapacity air-conditioner, a manufacturer
must conduct four tests and generally
conducts in addition the dry and cyclic
tests. Adding five tests would roughly
double the test time for these units. It is
not clear how the five additional tests
recommended by NREL would improve
the accuracy or field-representativeness
of the measurements of SEER or EER.
Hence, DOE has determined not to
include these test points in the test
procedure.
2. Barometric Pressure Correction
AHRI and JCI proposed that DOE
implement a barometric pressure
correction specification for testing. They
suggested that barometric pressure be
corrected to the altitude where the mean
of the U.S. population lives. (AHRI, No.
70 at p. 13; JCI, No. 66 at p. 11) JCI
suggested addressing barometric
pressure by maintaining the enthalpy or
humidity ratio of the entering air,
indicating that this has been used
effectively for lab correlation. (JCI, No.
66 at p. 11)
DOE has noted the industry’s concern
regarding the impact of barometric
pressure on the repeatability of tests and
represented values. Currently, there is
no systematic data to demonstrate the
effect of barometric pressure on unit
performance. However, JCI did not
describe in sufficient detail how the
correlation it proposed would work, nor
PO 00000
Frm 00052
Fmt 4701
Sfmt 4700
provide data showing that it properly
addresses the barometric pressure issue.
DOE also notes that there has not been
a study leading to selection of a
standard altitude or pressure level. DOE
is not adopting a barometric pressure
correction in this final rule because an
approach for addressing it has not been
described in sufficient detail nor shown
to provide the correct adjustment for
pressure changes.
3. Inlet Screen
DOE proposed in the November 2015
SNOPR the use of a screen downstream
of the air mixer in the outlet of the
indoor unit if necessary to improve
temperature uniformity. 80 FR at 69278,
69353 (Nov. 9, 2015). Ingersoll Rand
commented that inlet and outlet screens
on the indoor unit air stream will
impose pressure drop, potentially
requiring an increase in the code tester
fan motor size. The code tester is the
airflow measuring apparatus as
discussed in section 2.6 of Appendix M.
They also recommended that regardless
of whether the cyclic test is carried out,
the measured performance should be
equivalent to the no damper test setup.
(Ingersoll Rand, No. 65 at p. 5–6) DOE
notes that the proposal included no
requirement for an inlet screen, and that
the screen in the outlet is an option to
help meet the temperature uniformity
requirements, but is not required if
other means are sufficient to attain
uniformity. Further, requirement for
temperature uniformity for the outlet
temperature measurement applies
whether or not an outlet damper box is
used, i.e., to conduct a cyclic test. DOE
has made no changes in response to the
Ingersoll Rand comment.
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
H. Compliance With Other Energy
Policy and Conservation Act
Requirements
This section discusses and responds
to comments related to compliance with
Energy Policy and Conservation Act
Requirements.
asabaliauskas on DSK3SPTVN1PROD with RULES
1. Dates
HARDI commented that given the
challenging and complex nature of the
test procedure, the comment period
should have been extended by 30 days.
HARDI believes that restricting the
comment period to 30 days has a
negative impact to smaller companies as
they may not have the means to fully
assess the true impact of such a
proposal in a narrow time frame.
(HARDI, No. 57 at p. 1) JCI requested
that the comment period remain open
an additional 60 days to finalize their
analysis of the proposed test procedure
and any resulting clarifying comments.
Goodman commented that the
Department has not complied with
federal law because it has failed to
provide a 60-day comment period on
this proposed test procedure per 42
U.S.C. 6293(b)(2). (Goodman, No. 73 at
p. 22)
DOE notes that it received a request
from AHRI to extend the comment
period while the comment period was
still open. (AHRI, No. 54, attachment 1).
DOE considered the request from AHRI,
but declined to do so. The November
2015 SNOPR represented the third
round of comment on the CAC test
procedure rulemaking. DOE is limited
by a statutory cap on the number of days
on which it can request public
comment, and after three rounds of
rulemaking, DOE is closer to that cap.
Consequently, DOE declined the request
and did not extend the comment period
for the CAC/HP TP SNOPR. (AHRI, No.
54, Attachment 2)
JCI commented that the raw scope of
changes proposed within the SNOPR
coupled with the CAC/HP ECS Working
Group and other DOE rulemaking
activities is such that a complete and
thorough review, understanding of the
proposed changes, and resulting
required laboratory changes, coupled
with potential rerating and off mode
standby test requirements make
complying with the new test procedure
within 180 days of being final
particularly challenging if not
impossible, and that the nature of many
of the proposed changes to the test
procedure require some level of capital
investment and software programming.
JCI formally requested that an additional
180 days were required to fully and
completely implement all of the
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
proposed changes in the SNOPR in
addition to the standard 180 days as
currently prescribed. (JCI, No. 66 at p.
2–3)
First Co. commented that the 180 day
effective date for AEDM compliance
proposed by DOE is unrealistic and
suggested an effective date of 18 months
from the date the rule is finalized. (First
Co., No. 56 at p. 1)
AHRI, ADP, Mortex, and Lennox
commented that even with the adoption
of the recommended ‘‘Similarity Group’’
framework, ICMs anticipate that the
industry will face significant challenges
to perform all the required testing in the
currently required time of 180 days after
the publication of the final rule. AHRI
formally petitions the Department to
extend the time period to comply to 360
days, as is consistent with its authority.
See 42 U.S.C. 6293(c)(3). (AHRI, No. 70
at p. 7; ADP, No. 59 at p. 4; Mortex, No.
71 at p. 6–7; Lennox, No. 61 at p. 7)
In response to JCI, DOE notes that this
final rule has a reduced scope from that
of the SNOPR. In addition, DOE has
made modifications to the off mode test
requirement proposals to reduce test
burden, as discussed in section III.D.10.
For these reasons, DOE believes that a
180 day time period will be sufficient to
implement the finalized test procedure.
In response to First Co., AHRI, ADP,
Mortex, and Lennox, DOE notes that 42
U.S.C. 6293(c)(3) allows individual
manufacturers to petition DOE for
additional time to comply. DOE cannot
grant this additional time based on a
blanket request from AHRI. However, as
discussed in section III.H.2, the changes
adopted in this final rule do not impact
measured energy use; and as such,
additional test burden is expected to be
limited.
2. Measured Energy Use
EPCA requires that if DOE determines
that the amended test procedure would
alter the measured efficiency of a
covered product, DOE must amend the
applicable energy conservation standard
accordingly. (42 U.S.C. 6293(e)(2)) In
the November 2015 SNOPR, DOE
determined that all proposed changes
for Appendix M would not alter the
measured efficiency of central air
conditioners and heat pumps. DOE
proposed all changes that it anticipated
might alter the measured efficiency for
Appendix M1, which will be addressed
in a separate notice.
AHRI, Nortek and UTC/Carrier
disagreed that the proposed changes to
Appendix M will not alter the measured
efficiency of a covered product. (AHRI,
No. 70 at p. 1–2; Nortek, No. 58 at p. 1;
UTC/Carrier, No. 62 at p. 23) UTC/
Carrier commented that this could be
PO 00000
Frm 00053
Fmt 4701
Sfmt 4700
37043
due to CD testing changing the resultant
SEER or HSPF, as it has slightly
different stability requirements, or could
be due to manufacturers losing the
ability to de-rate and require ratings to
be at the mean of the data/testing
results. (UTC/Carrier, No. 62 at p. 23)
AHRI contended that the following
proposed changes may impact
efficiency: Changes to the CD;
requirement that manufacturers rate to
the mean of the cooling capacity,
heating capacity, and sensible heat ratio
(SHR) and the prohibition on
manufacturers’ conservative ratings;
requirement that two-speed products
must be tested coil-only, which has the
potential to change ratings derived
previously using a blower coil or the
alternative rating method; and limit on
compressor break-in period. (AHRI, No.
70 at p. 1–2)
Rheem commented that that each of
the changes that have been proposed
made a difference in the rating of a
specific equipment sample subject to
verification or enforcement testing and
that it is not clear whether the
certification rating will increase or
decrease for each proposed change.
Rheem commented that it is not clear
how the conclusion that proposed
changes do not impact standards was
reached. (Rheem, No. 69 at p. 2)
DOE notes that with the exception of
compressor break-in period, DOE has
made modifications to its proposals on
all the topics for which UTC/Carrier and
AHRI expressed concern over change in
represented value. In addition, DOE
notes that the current test procedure
does not include a compressor break-in
period, and any change in represented
value for testing a specific unit with a
break-in period would only serve to
improve the value as compared to the
standard. For these reasons, DOE
confirms that the changes adopted in
this final rule do not alter the measured
efficiency of the covered product.
Nortek commented that if the test
procedure does not change the
efficiency, then all existing ratings are
still valid. (Nortek, No. 58 at p. 1)
Similarly, First Co. commented that the
final rule should make clear that ICM
test results remain valid until the energy
efficiency standard changes. Retesting is
not required merely because the OUM
discontinues the outdoor unit tested by
the ICM. (First Co., No. 56 at p. 2)
Finally, AHRI, ADP, Mortex, and
Lennox asked for clarity on using data
from existing tests to satisfy testing
requirements especially considering the
burden associated with outside lab
testing. These parties stated that, based
on the proposed framework, ICMs and
OUMs would expect that data from
E:\FR\FM\08JNR2.SGM
08JNR2
37044
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
existing tests performed to the current
test standard and meeting all other
requirements could be used to satisfy
the testing requirement for existing
products. In addition, they said that
ICMs and OUMs also expect that tests
will remain valid until the energy
conservation standard is changed and
Appendix M1 becomes effective. (AHRI,
No. 70 at p. 7; ADP, No. 59 at p. 4;
Mortex, No. 71 at p. 6–7; Lennox, No.
61 at p. 7)
DOE acknowledges that
manufacturers have large amounts of
pre-existing data that they currently use
to make representations about and
certify the performance of their
equipment and that regenerating all of
this data within the 180 day timeframe
would be burdensome. As such,
manufacturers may continue to use such
data to make representations about the
performance of models after the 180 day
timeframe, provided manufacturers are
confident that the values are consistent
with those that would be generated
under the adopted test procedure.
3. Test Burden
EPCA requires that any test
procedures prescribed or amended shall
be reasonably designed to produce test
results which measure energy
efficiency, energy use, or estimated
annual operating cost of a covered
product during a representative average
use cycle or period of use, and shall not
be unduly burdensome to conduct. (42
U.S.C. 6293(b)(3)) For the reasons that
follow, DOE has concluded that revising
the DOE test procedure, per the
amendments in this final rule, to
measure the energy consumption of
central air conditioners and heat pumps
in active mode and off mode would
produce the required test results and
would not result in any undue burden.
As discussed in section IV.B of this
final rule, the revised test procedures to
determine the active-mode and standbymode energy use would require use of
the same testing equipment and
facilities that manufacturers are
currently using for testing to determine
CAC/HP represented values for
certifying performance to DOE. While
this notice clarifies the test procedures,
and adopts into regulation the test
procedures associated with a number of
test procedure waivers, most of the
amendments would not affect test time
or the equipment and facilities required
to conduct testing. Possible changes in
test burden associated with the
amendments of this notice apply to off
mode testing.
The amendments include additional
testing to determine off mode energy
use, as required by EPCA. (42 U.S.C.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
6295(gg)(2)(A)) This additional testing
may require investment in additional
temperature-controlled facilities.
However, DOE’s revised test procedure
does not require that every individual
combination be tested for off mode,
allowing extensive use of AEDMs in
order to reduce test burden.
In addition, DOE carefully considered
the testing burden on manufacturers in
a modified off mode test procedure that
is less burdensome than the proposals it
made in the April 2011 SNOPR and
October 2011 SNOPR and that addresses
stakeholder comment regarding the test
burden of such prior proposals. DOE
made further changes to reduce test
burden of the off-mode test procedure in
response to comments regarding the
November 2015 SNOPR, specifically (a)
allowing the test to be conducted in a
temperature-controlled room rather than
a psychrometric test facility, and (b)
allowing the test to be conducted
without room temperature control for
more designs than allowed by the
proposal. Further discussion regarding
test burden associated with the
proposals set forth in this notice for
determining off mode power
consumption can be found in section
III.D.
The November 2015 SNOPR also
proposed amendments calling for
testing to determine performance for
ICMs. These amendments have been
revised in this final rule such that far
fewer models will have to be tested (see
the discussion in section III.A.1.d).
DOE allows manufacturers to develop
and apply an alternative efficiency
determination method to certify
products without the need of testing. In
this notice, DOE revises and clarifies
such requirements, as detailed in
section III.B, to continue to enable
manufacturers who wish to reduce
testing burden to utilize this method.
As detailed in section III.C,
manufacturers of certain products
covered by test procedure waivers have
already been using the alternative test
procedures provided to them for
certification testing. Thus, the inclusion
of those alternative test procedures into
the test procedure, as revised in this
notice, does not add test burden.
DOE set forth amendments to improve
test repeatability, improve the
readability and clarity of the test
procedure, and utilize industry
procedures that manufacturers may be
aware of in an effort to reduce the test
burden. Sections III.E, III.F, and III.G
present additional detail regarding such
amendments.
DOE carefully considered the impact
on testing burden and made efforts to
balance accuracy, repeatability, and test
PO 00000
Frm 00054
Fmt 4701
Sfmt 4700
burden during the course of the
development of all of the test procedure
amendments. Therefore, DOE
determined that the revisions to the
central air conditioner and heat pump
test procedure will produce test results
that measure energy consumption
during a period of representative use,
and that the test procedure will not be
unduly burdensome to conduct.
4. Potential Incorporation of
International Electrotechnical
Commission Standard 62301 and
International Electrotechnical
Commission Standard 62087
Under 42 U.S.C. 6295(gg)(2)(B), EPCA
directs DOE to consider IEC Standard
62301 and IEC Standard 62087 when
amending test procedures for covered
products to include standby mode and
off mode power measurements.
DOE reviewed IEC Standard 62301,
‘‘Household electrical appliances—
Measurement of standby power’’
(Edition 2.0 2011–01),19 and determined
that the procedures contained therein
are not sufficient to properly measure
off mode power for the unique
characteristics of the components that
contribute to off-mode power for CAC/
HP products, i.e., the crankcase heaters.
Therefore, DOE determined that
referencing IEC Standard 62301 is not
appropriate for the revised test
procedure that is the subject of this
rulemaking.
DOE reviewed IEC Standard 62087,
‘‘Methods of measurement for the power
consumption of audio, video, and
related equipment’’ (Edition 3.0 2011–
04), and determined that it would not be
applicable to measuring power
consumption of products such as central
air conditioners and heat pumps.
Therefore, DOE determined that
referencing IEC Standard 62087 is not
necessary for the revised test procedure
that is the subject of this rulemaking.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Order 12866
The Office of Management and Budget
(OMB) has determined that test
procedure rulemakings do not constitute
‘‘significant regulatory actions’’ under
section 3(f) of Executive Order 12866,
Regulatory Planning and Review, 58 FR
51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under
the Executive Order by the Office of
Information and Regulatory Affairs
(OIRA) in the Office of Management and
Budget.
19 IEC Standard 62301 covers measurement of
power consumption for standby mode and low
power modes, as defined therein.
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of a final regulatory flexibility analysis
(FRFA) for any final rule, unless the
agency certifies that the rule, if
promulgated, will not have a significant
economic impact on a substantial
number of small entities. As required by
Executive Order 13272, ‘‘Proper
Consideration of Small Entities in
Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s Web site: https://energy.gov/
gc/office-general-counsel.
DOE reviewed today’s final rule under
the provisions of the Regulatory
Flexibility Act and the procedures and
policies published on February 19,
2003. This final rule prescribes
clarifications to DOE’s already-existing
test procedures that will be used to test
compliance with energy conservation
standards for the products that are the
subject of this rulemaking. It also adds
a requirement to conduct testing to
determine off mode power
consumption. DOE has estimated the
impacts of the test procedure changes
on small business manufacturers.
For the purpose of the regulatory
flexibility analysis for this rule, DOE
adopts the Small Business
Administration (SBA) definition of a
small entity within this industry as a
manufacturing enterprise with 1,250
employees or fewer. DOE used the small
business size standards published by
the SBA to determine whether any small
entities would be required to comply
with the rule. The size standards are
codified at 13 CFR part 121. The
standards are listed by North American
Industry Classification System (NAICS)
code and industry description and are
available at https://www.sba.gov/sites/
default/files/files/Size_Standards_
Table.pdf.
Central air conditioner and heat pump
manufacturing is classified under
NAICS 333415, ‘‘Air-Conditioning and
Warm Air Heating Equipment and
Commercial and Industrial Refrigeration
Equipment Manufacturing.’’ 70 FR
12395 (March 11, 2005). DOE reviewed
AHRI’s listing of central air conditioner
and heat pump product manufacturer
members and surveyed the industry to
develop a list of domestic
manufacturers. As a result of this
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
review, DOE identified 24 domestic
small manufacturers of central air
conditioners and heat pumps.
Potential impacts of the amended test
procedure on all manufacturers,
including small businesses, come from
impacts associated with the cost of
proposed additional testing. In the June
2010 NOPR, DOE estimated the
incremental cost of the proposed
additional tests described in 10 CFR
part 430, subpart B, Appendix M
(proposed section 3.13) to be an increase
of $1,000 to $1,500 per unit tested,
indicating that the largest additional
cost would be associated with
conducting steady-state cooling mode
tests and the dry climate tests for the
SEER–HD rating). 75 FR 31243 (June 2,
2010). DOE has eliminated tests
associated with SEER–HD from this
rulemaking. DOE conservatively
estimates that off mode testing might
cost $1,000 (roughly one-fifth of the
$5000 cost of active mode testing—see
75 FR 31243 (June 2, 2010)). Assuming
two off mode tests per tested model, this
is an average test cost of $2,000 per
model. This estimate does not take into
consideration the possibility of the use
of AEDMs for establishing off-mode
represented values, which could
significantly reduce the off-mode testing
burden. It also does not take into
account the changes in off-mode testing
adopted in this final rule to reduce test
burden, i.e., specifically allowing more
units to test off-mode energy use in a
room without temperature control, and
clarifying that off-mode testing does not
need to be conducted in a
psychrometric chamber (see section
III.D for details).
The off mode test procedure primarily
measures energy use of outdoor units.
The off-mode power input represented
values for CAC/HP model combinations
including indoor units manufactured by
ICMs would be equal to the off-mode
represented values of other
combinations using the same outdoor
units. Hence, it is expected that smallbusiness ICM manufacturers would use
these same represented values rather
than retesting the outdoor units and
thus not be affected by the off-mode
testing required by this rule. Because
the incremental cost of running the
extra off mode tests is the same for all
other manufacturers, DOE believes that
they would incur comparable costs for
testing to certify off mode power use for
basic models as a result of this final test
procedure.
With respect to the provisions
addressing AEDMs, the amendments
contained herein will not increase the
testing or reporting burden of OUMs
who currently use, or are eligible to use,
PO 00000
Frm 00055
Fmt 4701
Sfmt 4700
37045
an AEDM to certify their products. The
amendments eliminate the ARM
nomenclature and treat these methods
as AEDMs, eliminate the pre-approval
requirement for product AEDMs, revise
the requirements for validation of an
AEDM in a way that would not require
more testing than that required by the
AEDM provisions included in the
March 7, 2011 Certification, Compliance
and Enforcement Final Rule (76 FR
12422) (‘‘March 2011 Final Rule’’), and
amend the process that DOE
promulgated in the March 2011 Final
Rule for validating AEDMs and
verifying certifications based on the use
of AEDMs. Because these AEDM-related
amendments will either have no effect
on test burden or decrease burden
related to testing and determination of
represented values of products (e.g.,
elimination of ARM pre-approval), DOE
has determined these amendments will
result in no significant change in testing
or reporting burden.
To evaluate the potential cost impact
of off-mode testing for small OUMs,
DOE estimated small manufacturers’
total cost of testing. As discussed above,
DOE identified 24 domestic small
business manufacturers of CAC/HP
products. Of these, only OUMs that
operate their own manufacturing
facilities (i.e., are not private labelers
selling only products manufactured by
other entities) and OUM importing
private labelers would be subject to the
additional requirements for testing
required by this rule. DOE identified 12
such manufacturers, but was able to
estimate the number of basic models
associated only with nine of these. DOE
calculated the additional testing
expense for these nine domestic small
businesses. Assuming the $2,000
estimate of additional test cost per basic
model, and that testing of basic models
may not have to be updated more than
once every five years, DOE estimated
that the annual cost impact of the
additional testing is $400 per basic
model when the cost is spread over five
years.
DOE currently requires that only one
combination associated with any given
outdoor unit be laboratory tested. 10
CFR 430.24(m). The majority of central
air conditioners and heat pumps offered
by a manufacturer are typically split
systems that are not required to be
laboratory tested but can be certified
using an AEDM that does not require
DOE testing of these units. DOE
reviewed available data for the nine
small businesses to estimate the
incremental testing cost burden those
firms might experience due to the
revised test procedure. These
manufacturers had an average of 35
E:\FR\FM\08JNR2.SGM
08JNR2
37046
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
models requiring testing. DOE
determined the numbers of models
using DOE’s Compliance Certification
Database (https://
www.regulations.doe.gov/certificationdata/). The additional testing cost for
final certification for 35 models was
estimated at $70,000. Meanwhile, these
certifications would be expected to last
the product life, estimated to be at least
five years. This test burden is therefore
estimated to be approximately $14,000
annually.
In addition to off-mode testing costs
facing small OUMs of central air
conditioners and heat pumps, this final
rule will require ICMs to conduct testing
for their basic models. However, DOE
has modified its definition of basic
model for ICM to match the Similarity
Group concept suggested by several
stakeholders (see section III.A.1.d).
Further, DOE has relaxed its
requirement for testing of ICM heat
pump combinations, such that only a
limited number of heat pump basic
models would require testing, i.e., those
for which a test has not been conducted
for an equivalent air-conditioner model.
DOE identified three domestic small
ICMs subject to testing costs under this
final rule.
To calculate the additional testing
costs facing small ICMs, DOE used data
provided by AHRI regarding what they
referred to as Similarity Groups and
which DOE is considering to be basic
models. Specifically, DOE assumed an
average of 42 basic models per ICM
based on the AHRI data. (AHRI, No. 70
at p. 6) DOE also assumed $7,500 in
added costs per test and two tests per
basic model. (AHRI, No. 70 at p. 4)
Assuming $15,000 in additional testing
costs per basic model (to cover two tests
per model), and that testing of basic
models may not have to be updated
more than once every five years, DOE
estimated that the total additional
testing cost for final certification of 42
basic models for each small ICM would
amount to costs averaging $126,000 per
year.
DOE will provide its certification and
final supporting statement of factual
basis to the Chief Counsel for Advocacy
of the SBA for review under 5 U.S.C.
605(b).
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of central air
conditioners and heat pumps must
certify to DOE that their products
comply with any applicable energy
conservation standards. In certifying
compliance, manufacturers must test
their products according to the DOE test
procedures for central air conditioners
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
and heat pumps, including any
amendments adopted for those test
procedures. DOE has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including
central air conditioners and heat pumps.
76 FR 12422 (March 7, 2011); 80 FR
5099 (Jan. 30, 2015). The collection-ofinformation requirement for the
certification and recordkeeping is
subject to review and approval by OMB
under the Paperwork Reduction Act
(PRA). This requirement has been
approved by OMB under OMB control
number 1910–1400. Public reporting
burden for the certification is estimated
to average 30 hours per response,
including the time for reviewing
instructions, searching existing data
sources, gathering and maintaining the
data needed, and completing and
reviewing the collection of information.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE amends its test
procedure for central air conditioners
and heat pumps. DOE has determined
that this final rule falls into a class of
actions that are categorically excluded
from review under the National
Environmental Policy Act of 1969 (42
U.S.C. 4321 et seq.) and DOE’s
implementing regulations at 10 CFR part
1021. Specifically, this rule amends the
existing test procedures without
affecting the amount, quality or
distribution of energy usage, and,
therefore, would not result in any
environmental impacts. Thus, this
rulemaking is covered by Categorical
Exclusion A5 under 10 CFR part 1021,
subpart D, which applies to any
rulemaking that interprets or amends an
existing rule without changing the
environmental effect of that rule.
Accordingly, neither an environmental
assessment nor an environmental
impact statement is required.
DOE’s CX determination for this rule
is available at https://energy.gov/nepa/
categorical-exclusion-cxdeterminations-cx.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999) imposes
certain requirements on agencies
formulating and implementing policies
PO 00000
Frm 00056
Fmt 4701
Sfmt 4700
or regulations that preempt State law or
that have Federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have Federalism implications. On
March 14, 2000, DOE published a
statement of policy describing the
intergovernmental consultation process
it will follow in the development of
such regulations. 65 FR 13735. DOE has
examined this final rule and has
determined that it would not have a
substantial direct effect on the States, on
the relationship between the national
government and the States, or on the
distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of this
rule. States can petition DOE for
exemption from such preemption to the
extent, and based on criteria, set forth in
EPCA. (42 U.S.C. 6297(d)) No further
action is required by Executive Order
13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, the rule meets
the relevant standards of Executive
Order 12988.
asabaliauskas on DSK3SPTVN1PROD with RULES
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
regulatory action likely to result in a
rule that may cause the expenditure by
State, local, and Tribal governments, in
the aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR
12820; also available at https://
energy.gov/gc/office-general-counsel.
DOE examined this final rule according
to UMRA and its statement of policy
and determined that the rule contains
neither an intergovernmental mandate,
nor a mandate that may result in the
expenditure of $100 million or more in
any year, so these requirements do not
apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
final rule will not have any impact on
the autonomy or integrity of the family
as an institution. Accordingly, DOE has
concluded that it is not necessary to
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights’’ 53 FR 8859
(March 18, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under the Treasury and
General Government Appropriations
Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). DOE has reviewed
this final rule under the OMB and DOE
guidelines and has concluded that it is
consistent with applicable policies in
those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB, a
Statement of Energy Effects for any
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgated or is
expected to lead to promulgation of a
final rule, and that: (1) Is a significant
regulatory action under Executive Order
12866, or any successor order; and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy; or (3) is designated by the
Administrator of OIRA as a significant
energy action. For any significant energy
action, the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use
associated with the rule’s
implementation, and of reasonable
alternatives to the action and their
expected benefits on energy supply,
distribution, and use.
The regulatory action is not a
significant regulatory action under
Executive Order 12866. Moreover, it
will not have a significant adverse effect
on the supply, distribution, or use of
energy, nor has it been designated as a
significant energy action by the
Administrator of OIRA. Therefore, it is
PO 00000
Frm 00057
Fmt 4701
Sfmt 4700
37047
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; FEAA) Section 32 essentially
provides in relevant part that, where a
proposed rule authorizes or requires use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (FTC)
concerning the impact of the
commercial or industry standards on
competition.
The rule incorporates testing methods
contained in the following commercial
standards: AHRI 210/240–2008,
Performance Rating of Unitary AirConditioning & Air-Source Heat Pump
Equipment; and AHRI 1230–2010,
Performance Rating of Variable
Refrigerant Flow Multi-Split AirConditioning and Heat Pump
Equipment. While the amended test
procedure is not exclusively based on
AHRI 210/240–2008 or AHRI 1230–
2010, one component of the test
procedure, namely test setup
requirements, adopts language from
AHRI 210/240–2008 without
amendment; and another component of
the test procedure, namely test setup
and test performance requirements for
multi-split systems, adopts language
from AHRI 1230–2010 without
amendment. DOE has evaluated these
standards and consulted with the
Attorney General and the Chairman of
the FTC and has concluded that this
final rule fully complies with the
requirements of section 32(b) of the
FEAA.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of this rule before its effective date. The
report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
N. Description of Materials Incorporated
by Reference
In this final rule, DOE is incorporating
by reference specific sections, figures,
and tables in the following two test
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37048
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
standards published by AHRI: ANSI/
AHRI 210/240–2008 with Addenda 1
and 2, titled ‘‘Performance Rating of
Unitary Air-Conditioning & Air-Source
Heat Pump Equipment;’’ and ANSI/
AHRI 1230–2010 with Addendum 2,
titled ‘‘Performance Rating of Variable
Refrigerant Flow (VRF) Multi-Split AirConditioning and Heat Pump
Equipment.’’ DOE is also updating its
incorporation by reference (IBR) to the
most recent versions of specific
standards, figures, and tables in the
following standards published by
ASHRAE: ASHRAE 23.1–2010 titled
‘‘Methods of Testing for Rating the
Performance of Positive Displacement
Refrigerant Compressors and
Condensing Units that Operate at
Subcritical Temperatures of the
Refrigerant’’, ANSI/ASHRAE 37–2009,
Methods of Testing for Rating
Electrically Driven Unitary AirConditioning and Heat Pump
Equipment, ANSI/ASHRAE 41.1–2013
titled ‘‘Standard Method for
Temperature Measurement’’, ASHRAE
41.6–2014 titled ‘‘Standard Method for
Humidity Measurement’’, and ASHRAE
41.9–2011 titled ‘‘Standard Methods for
Volatile-Refrigerant Mass Flow
Measurements Using Calorimeters’’.
Finally, DOE is updating its IBR to
specific figures in the most recent
version of the following test procedure
from ASHRAE and AMCA: ANSI/
AMCA 210–2007, ANSI/ASHRAE 51–
2007, Laboratory Methods of Testing
Fans for Certified Aerodynamic
Performance Rating.
AHRI 210/240–2008 is an industry
accepted test procedure that measures
the cooling and heating performance of
central air conditioners and heat pumps
and is applicable to products sold in
North America. The test procedure in
this final rule references various
sections of AHRI 210/240–2008 that
address test setup, test conditions, and
rating requirements. AHRI 210/240–
2008 is readily available on AHRI’s Web
site at https://www.ahrinet.org/site/686/
Standards/HVACR-Industry-Standards/
Search-Standards.
AHRI 1230–2010 is an industry
accepted test procedure that measures
the cooling and heating performance of
variable refrigerant flow (VRF) multisplit air conditioners and heat pumps
and is applicable to products sold in
North America. The test procedure in
this final rule for VRF multi-split
systems references various sections of
AHRI 1230–2010 that address test setup,
test conditions, and rating requirements.
AHRI 1230–2010 is readily available on
AHRI’s Web site at https://
www.ahrinet.org/site/686/Standards/
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
HVACR-Industry-Standards/SearchStandards.
ASHRAE 23.1–2010 is an industry
accepted test procedure for rating the
thermodynamic performance of positive
displacement refrigerant compressors
and condensing units that operate at
subcritical temperatures. The test
procedure in this final rule references
sections of ASHRAE 23.1–2010 that
address requirements, instruments,
methods of testing, and testing
procedure specific to compressor
calibration. ASHRAE 23.1–2010 can be
purchased from ASHRAE’s Web site at
https://www.ashrae.org/resourcespublications.
ANSI/ASHRAE 37–2009 is an
industry accepted standard that
provides test methods for determining
the cooling capacity of unitary airconditioning equipment and the cooling
or heating capacities, or both, of unitary
heat pump equipment. The test
procedure in this final rule references
various sections of ANSI/ASHRAE 37–
2009 that address test conditions and
test procedures, updating the IBR from
a previous version of this standard,
ASHRAE 37–2005. ANSI/ASHRAE 37–
2009 can be purchased from ASHRAE’s
Web site at https://www.ashrae.org/
resources-publications.
ANSI/ASHRAE 41.1–2013 is an
industry accepted method for measuring
temperature in testing heating,
refrigerating, and air-conditioning
equipment. The test procedure in this
final rule references sections of ANSI/
ASHRAE 41.1–2013 that address
requirements, instruments, and methods
for measuring temperature. ANSI/
ASHRAE 41.1–2013 can be purchased
from ASHRAE’s Web site at https://
www.ashrae.org/resources-publications.
ASHRAE 41.2–1987 (RA 1992) is an
industry accepted test method for
measuring airflow. The test procedure
in this final rule references sections of
ASHRAE 41.2–1987 (RA 1992) that
address test setup and test methods.
ASHRAE 41.2–1987 (RA 1992) can be
purchased from ASHRAE’s Web site at
https://www.ashrae.org/resourcespublications.
ASHRAE 41.6–2014 is an industry
accepted test method for measuring
humidity of moist air. The test
procedure in this final rule references
sections of ASHRAE 41.6–2014 that
address requirements, instruments, and
methods for measuring humidity.
ASHRAE 41.6–2014 can be purchased
from ASHRAE’s Web site at https://
www.ashrae.org/resources-publications.
ASHRAE 41.9–2011 is an industry
accepted standard that provides
recommended practices for measuring
the mass flow rate of volatile
PO 00000
Frm 00058
Fmt 4701
Sfmt 4700
refrigerants using calorimeters. The test
procedure in this final rule references
sections of ASHRAE 41.9–2011 that
address requirements, instruments, and
methods for measuring refrigerant flow
during compressor calibration. ASHRAE
41.9–2011 can be purchased from
ASHRAE’s Web site at https://
www.ashrae.org/resources-publications.
ANSI/ASHRAE Standard 116–2010 is
an industry accepted standard that
provides test methods and calculation
procedures for determining the
capacities and cooling seasonal
efficiency ratios for unitary airconditioning, and heat pump equipment
and heating seasonal performance
factors for heat pump equipment. The
test procedure in this final rule
references various sections of ANSI/
ASHRAE 116–2010 that addresses test
methods and calculations, updating the
IBR from a previous version of the
standard, ASHRAE 116–1995 (RA 2005).
ANSI/ASHRAE Standard 116–2010 can
be purchased from ASHRAE’s Web site
at https://www.ashrae.org/resourcespublications.
AMCA 210–2007 is an industry
accepted standard that establishes
uniform test methods for a laboratory
test of a fan or other air moving device
to determine its aerodynamic
performance in terms of air flow rate,
pressure developed, power
consumption, air density, speed of
rotation, and efficiency for rating or
guarantee purposes. The test procedure
in this final rule references various
sections of AMCA 210–2007 that
address test conditions, updating the
IBR from a previous version of this
standard, ASHRAE/AMCA 51–1999/
210–1999. AMCA 210–2007 can be
purchased from AMCA’s Web site at
https://www.amca.org/store/index.php.
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
List of Subjects
10 CFR Part 429
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Reporting and recordkeeping
requirements.
10 CFR Part 430
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Energy conservation test procedures,
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Small
businesses.
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Issued in Washington, DC, on May 19,
2016.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
For the reasons set forth in the
preamble, DOE amends parts 429 and
430 of chapter II of title 10, Code of
Federal Regulations, to read as follows:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
2. Section 429.12 is amended by
revising paragraphs (b)(8) and (12) to
read as follows:
■
§ 429.12 General requirements applicable
to certification reports.
*
*
*
*
*
(b) * * *
(8) The test sample size (i.e., number
of units tested for the basic model, or in
the case of single-split system or singlepackage central air conditioners and
central air conditioning heat pumps, or
multi-split, multi-circuit, or multi-head
mini-split systems other than the
‘‘tested combination,’’ for each
individual combination or individual
model). Enter ‘‘0’’ if an AEDM was used
in lieu of testing (and in the case of
central air conditioners and central air
conditioning heat pumps, this must be
indicated separately for each metric);
*
*
*
*
*
(12) If the test sample size is listed as
‘‘0’’ to indicate the certification is based
upon the use of an alternate way of
determining measures of energy
conservation, identify the method used
for determining measures of energy
Category
Equipment subcategory
Single-Package Unit ........................
Single-Package
AC
(including
Space-Constrained).
Single-Package
HP
(including
Space-Constrained).
Single-Split System AC with Single-Stage or Two-Stage Compressor (including Space-Constrained and Small-Duct, High
Velocity Systems (SDHV)).
Single-Split System AC with Other
Than Single-Stage or TwoStage Compressor (including
Space-Constrained and SDHV).
Single-Split-System HP (including
Space-Constrained and SDHV).
Multi-Split, Multi-Circuit, or MultiHead Mini-Split Split System—
non-SDHV.
Outdoor Unit and Indoor Unit (Distributed in Commerce by OUM).
Indoor Unit Only (Distributed in
Commerce by ICM).
Multi-Split, Multi-Circuit, or MultiHead Mini-Split Split System—
SDHV.
Single-Split-System Air Conditioner (including Space-Constrained and SDHV).
Single-Split-System Heat Pump
(including
Space-Constrained
and SDHV).
Multi-Split, Multi-Circuit, or MultiHead Mini-Split Split System—
SDHV.
asabaliauskas on DSK3SPTVN1PROD with RULES
Outdoor Unit with no Match ........................................................................
(2) PW,OFF. If individual models of
single-package systems or individual
combinations (or ‘‘tested
combinations’’) of split systems that are
otherwise identical are offered with
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Frm 00059
Fmt 4701
conservation (such as ‘‘AEDM,’’ or
linear interpolation). Manufacturers of
commercial packaged boilers,
commercial water heating equipment,
commercial refrigeration equipment,
commercial HVAC equipment, and
central air conditioners and central air
conditioning heat pumps must provide
the manufacturer’s designation (name or
other identifier) of the AEDM used; and
*
*
*
*
*
■ 3. Section 429.16 is revised to read as
follows:
§ 429.16 Central air conditioners and
central air conditioning heat pumps.
(a) Determination of Represented
Value—(1) Required represented values.
Determine the represented values
(including SEER, EER, HSPF, PW,OFF,
cooling capacity, and heating capacity,
as applicable) for the individual
models/combinations (or ‘‘tested
combinations’’) specified in the
following table.
Required represented values
Every individual model distributed in commerce.
Every individual combination distributed in commerce, including all
coil-only and blower coil combinations. For each model of outdoor
unit, this must include at least one coil-only value that is representative of the least efficient combination distributed in commerce with
the particular model of outdoor unit.
Every individual combination distributed in commerce, including all
coil-only and blower coil combinations.
Every individual combination distributed in commerce.
For each model of outdoor unit, at a minimum, a non-ducted ‘‘tested
combination.’’ For any model of outdoor unit also sold with models
of ducted indoor units, a ducted ‘‘tested combination.’’ Additional
representations are allowed, as described in paragraph (c)(3)(i) of
this section.
For each model of outdoor unit, an SDHV ‘‘tested combination.’’ Additional representations are allowed, as described in paragraph
(c)(3)(ii) of this section.
Every individual combination distributed in commerce.
For a model of indoor unit within each basic model, an SDHV ‘‘tested
combination.’’ Additional representations are allowed, as described
in section (c)(3)(ii).
Every model of outdoor unit distributed in commerce (tested with a
model of coil-only indoor unit as specified in paragraph (c)(2) of
this section).
multiple options for off mode-related
components, determine the represented
value for the individual model/
combination with the crankcase heater
and controls that are the most
PO 00000
37049
Sfmt 4700
consumptive. A manufacturer may also
determine represented values for
individual models/combinations with
less consumptive off mode options;
however, all such options must be
E:\FR\FM\08JNR2.SGM
08JNR2
37050
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
identified with different model numbers
for single-package systems or for
outdoor units (in the case of split
systems).
(3) Limitations for represented values
of individual combinations. The
following paragraphs explains the
limitations for represented values of
individual combinations (or ‘‘tested
combinations’’).
(i) Regional. A basic model may only
be certified as compliant with a regional
standard if all individual combinations
within that basic model meet the
regional standard for which it is
certified. If a model of outdoor unit is
certified below a regional standard, then
the model of outdoor unit must have a
unique model number for distribution
in each region. An ICM cannot certify a
basic model containing a representative
value that is more efficient than any
combination certified by an OUM
containing the same outdoor unit.
(ii) Multiple product classes. Models
of outdoor units that are rated and
distributed in individual combinations
that span multiple product classes must
be tested, rated, and certified pursuant
to paragraph (a) of this section as
compliant with the applicable standard
for each product class. This includes
multi-split systems, multi-circuit
systems, and multi-head mini-split
systems with a represented value for a
mixed combination including both
SDHV and either non-ducted or ducted
indoor units.
(4) Requirements. All represented
values under paragraph (a) of this
section must be based on testing in
accordance with the requirements in
paragraph (b) of this section or the
application of an AEDM or other
methodology as allowed in paragraph
(c) of this section.
(b) Units tested—(1) General. The
general requirements of § 429.11 apply
to central air conditioners and heat
pumps; and
(2) Individual model/combination
selection for testing. (i) The table
identifies the minimum testing
requirements for each basic model that
includes multiple individual models/
combinations. For each basic model that
includes only one individual model/
combination, that individual model/
combination must be tested.
Category
Equipment
subcategory
Single-Package Unit ......................
Single-Package AC (including
Space-Constrained).
Single-Package HP (including
Space-Constrained).
Single-Split-System AC with Single-Stage or Two-Stage Compressor (including Space-Constrained and Small- Duct, High
Velocity Systems (SDHV)).
Single-Split System AC with Other
Than Single-Stage or TwoStage Compressor (including
Space-Constrained and SDHV).
Single-Split-System HP (including
Space-Constrained and SDHV).
Multi-Split, Multi-Circuit, or MultiHead Mini-Split Split System—
non-SDHV.
The lowest
model.
Multi-Split, Multi-Circuit, or MultiHead Mini-Split Split System—
SDHV.
Single-Split-System Air Conditioner (including Space-Constrained and SDHV).
The model of outdoor unit ............
Single-Split-System Heat Pump
(including
Space-Constrained
and SDHV).
Nothing, as long as an equivalent
air conditioner basic model has
been tested.
If an equivalent air conditioner
basic model has not been tested, must test a model of indoor
unit.
Outdoor Unit and Indoor Unit (Distributed in Commerce by OUM).
asabaliauskas on DSK3SPTVN1PROD with RULES
Indoor Unit Only (Distributed in
Commerce by ICM).
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00060
Must test:
Fmt 4701
With:
SEER
individual
N/A.
The model of outdoor unit ............
The model of coil-only indoor unit
that is likely to have the largest
volume of retail sales with the
particular model of outdoor unit.
The model of outdoor unit ............
The model of indoor unit that is
likely to have the largest volume of retail sales with the particular model of outdoor unit.
The model of outdoor unit ............
At a minimum, a ‘‘tested combination’’ composed entirely of nonducted indoor units. For any
models of outdoor units also
sold with models of ducted indoor units, a second ‘‘tested
combination’’ composed entirely
of ducted indoor units must be
tested (in addition to the nonducted combination).
A ‘‘tested combination’’ composed
entirely of SDHV indoor units.
A model of indoor unit ..................
Sfmt 4700
E:\FR\FM\08JNR2.SGM
The least efficient model of outdoor unit with which it will be
paired where the least efficient
model of outdoor unit is the
model of outdoor unit in the
lowest SEER combination as
certified by the OUM. If there
are multiple models of outdoor
unit with the same lowest
SEER represented value, the
ICM may select one for testing
purposes.
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
A model of coil-only indoor unit
meeting the requirements of
section 2.2e of Appendix M to
subpart B of part 430.
and, x is the sample mean; n is the
number of samples; and xi is the ith
sample; Or,
(B) The upper 90 percent confidence
limit (UCL) of the true mean divided by
1.05, where:
And x is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.90 is the t
statistic for a 90 percent one-tailed
confidence interval with n¥1 degrees of
freedom (from appendix D). Round
represented values of off-mode power
consumption to the nearest watt.
(ii) SEER, EER, and HSPF. Any
represented value of the energy
efficiency or other measure of energy
consumption for which consumers
would favor higher values shall be less
than or equal to the lower of:
(A) The mean of the sample, where:
and, x is the sample mean; n is the
number of samples; and xi is the ith
sample; or,
(B) The lower 90 percent confidence
limit (LCL) of the true mean divided by
0.95, where:
And x is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.90 is the t
statistic for a 90 percent one-tailed
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00061
Fmt 4701
Sfmt 4700
confidence interval with n¥1 degrees of
freedom (from Appendix D). Round
represented values of EER, SEER, and
HSPF to the nearest 0.05.
(iii) Cooling Capacity. The
represented value of cooling capacity
must be a self-declared value that is no
less than 95 percent of the mean of the
cooling capacities measured for the
units in the sample, rounded:
(A) To the nearest 100 Btu/h if cooling
capacity is less than 20,000 Btu/h,
(B) To the nearest 200 Btu/h if cooling
capacity is greater than or equal to
20,000 Btu/h but less than 38,000 Btu/
h, and
(C) To the nearest 500 Btu/h if cooling
capacity is greater than or equal to
38,000 Btu/h and less than 65,000 Btu/
h.
(iv) Heating Capacity. The
represented value of heating capacity
must be a self-declared value that is no
less than 95 percent of the mean of the
heating capacities measured for the
units in the sample, rounded:
(A) To the nearest 100 Btu/h if heating
capacity is less than 20,000 Btu/h,
(B) To the nearest 200 Btu/h if heating
capacity is greater than or equal to
20,000 Btu/h but less than 38,000 Btu/
h, and
(C) To the nearest 500 Btu/h if heating
capacity is greater than or equal to
38,000 Btu/h and less than 65,000 Btu/
h.
(c) Determination of represented
values for all other individual models/
combinations besides those specified in
paragraph (b)(2) of this section—(1) All
basic models except outdoor units with
no match and multi-split systems, multicircuit systems, and multi-head minisplit systems. (i) For every individual
model/combination within a basic
model other than the individual model/
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.003
(ii) Each individual model/
combination (or ‘‘tested combination’’)
identified in paragraph (b)(2)(i) of this
section is not required to be tested for
PW,OFF. Instead, at a minimum, among
individual models/combinations with
similar off-mode construction (even
spanning different models of outdoor
units), a manufacturer must test at least
one individual model/combination for
PW,OFF.
(3) Sampling plans and representative
values. (i) For individual models (for
single-package systems) or individual
combinations (for split–systems,
including ‘‘tested combinations’’ for
multi-split, multi-circuit, and multihead mini-split systems) with
represented values determined through
testing, each individual model/
combination (or ‘‘tested combination’’)
must have a sample of sufficient size
tested in accordance with the applicable
provisions of this subpart. For heat
pumps (other than heating-only heat
pumps), all units of the sample
population must be tested in both the
cooling and heating modes and the
results used for determining all
representations. The represented values
for any individual model/combination
must be assigned such that:
(i) Off-Mode. Any represented value
of power consumption or other measure
of energy consumption for which
consumers would favor lower values
must be greater than or equal to the
higher of:
(A) The mean of the sample, where:
A ‘‘tested combination’’ composed
entirely of SDHV indoor units,
where the outdoor unit is the
least efficient model of outdoor
unit with which the SDHV indoor unit will be paired. The
least efficient model of outdoor
unit is the model of outdoor unit
in the lowest SEER combination as certified by the OUM. If
there are multiple models of
outdoor unit with the same lowest SEER represented value,
the ICM may select one for
testing purposes.
ER08JN16.002
asabaliauskas on DSK3SPTVN1PROD with RULES
Outdoor Unit with No Match
A model of indoor unit. .................
The model of outdoor unit ............
Multi-Split, Multi-Circuit, or MultiHead Mini-Split Split System—
SDHV.
With:
ER08JN16.001
Must test:
ER08JN16.000
Equipment
subcategory
Category
37051
37052
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
combination required to be tested
pursuant to paragraph (b)(2) of this
section, either—
(A) A sample of sufficient size,
comprised of production units or
representing production units, must be
tested as complete systems with the
resulting represented values for the
individual model/combination obtained
in accordance with paragraphs (b)(1)
and (3) of this section; or
(B) The represented values of the
measures of energy efficiency or energy
consumption must be assigned through
the application of an AEDM in
accordance with paragraph (d) of this
section and § 429.70. An AEDM may
only be used to rate individual models/
combinations in a basic model other
than the individual model/combination
required for mandatory testing under
paragraph (b)(2)(i) of this section. No
basic model may be rated with an
AEDM (except for determination of
PW,OFF).
(ii) For every individual model/
combination within a basic model tested
pursuant to paragraph (b)(2) of this
section, but for which PW,OFF testing was
not conducted, the represented value of
PW,OFF may be assigned through, either:
(A) The testing result from an
individual model/combination of
similar off-mode construction, or
(B) The application of an AEDM in
accordance with paragraph (d) of this
section and § 429.70.
(2) Outdoor units with no match. All
models of outdoor unit within a basic
model must be tested. No model of
outdoor unit may be rated with an
AEDM.
(3) Multi-split systems, multi-circuit
systems, and multi-head mini-split
systems. The following applies:
(i) For basic models composed of both
non-ducted and ducted combinations,
the represented value for the mixed
non-ducted/ducted combination is the
mean of the represented values for the
non-ducted and ducted combinations as
determined in accordance with
paragraph (b)(3)(i) of this section.
(ii) For basic models composed of
both SDHV and non-ducted or ducted
combinations, the represented value for
the mixed SDHV/non-ducted or SDHV/
ducted combination is the mean of the
represented values for the SDHV, nonducted, or ducted combinations, as
applicable, as determined in accordance
with paragraph (b)(3)(i) of this section.
(iii) All other individual combinations
of models of indoor units for the same
model of outdoor unit for which the
manufacturer chooses to make
representations must be rated as
separate basic models, and the
provisions in paragraphs (b)(1) through
(3) and (c)(3)(i) and (ii) of this section
apply.
(iv) For every individual combination
(or ‘‘tested combination’’) within a basic
model tested pursuant to paragraph
(b)(2) of this section, but for which
PW,OFF testing was not conducted, the
representative values of PW,OFF may be
assigned through either:
(A) The testing result from an
individual combination (or ‘‘tested
combination’’) of similar off-mode
construction, or
(B) Application of an AEDM in
accordance with paragraph (d) of this
section and § 429.70. No basic model
may be rated with an AEDM for SEER,
EER, or HSPF.
(d) Alternative efficiency
determination methods. In lieu of
testing, represented values of efficiency
or consumption may be determined
through the application of an AEDM
pursuant to the requirements of
§ 429.70(e) and the provisions of this
section.
(1) Power or energy consumption. Any
represented value of the average off
mode power consumption or other
measure of energy consumption of an
individual model/combination for
which consumers would favor lower
values must be greater than or equal to
the output of the AEDM but no less than
the standard.
(2) Energy efficiency. Any represented
value of the SEER, EER, HSPF or other
measure of energy efficiency of an
individual model/combination for
which consumers would favor higher
values must be less than or equal to the
output of the AEDM but no greater than
the standard.
(3) Cooling capacity. The represented
value of cooling capacity of an
individual model/combination must be
no less than 95% of the cooling capacity
output simulated by the AEDM.
(4) Heating capacity. The represented
value of heating capacity of an
individual model/combination must be
no less than 95% of the heating capacity
output simulated by the AEDM.
(e) Certification reports. This
paragraph specifies the information that
must be included in a certification
report.
(1) General. The requirements of
§ 429.12 apply to central air
conditioners and heat pumps.
(2) Public product-specific
information. Pursuant to § 429.12(b)(13),
for each individual model (for singlepackage systems) or individual
combination (for split–systems,
including ‘‘tested combinations’’ for
multi-split, multi-circuit, and multihead mini-split systems), a certification
report must include the following
public product-specific information:
The seasonal energy efficiency ratio
(SEER in British thermal units per Watthour (Btu/W-h)); the average off mode
power consumption (PW,OFF in Watts);
the cooling capacity in British thermal
units per hour (Btu/h); the region(s) in
which the basic model can be sold; and
(i) For heat pumps, the heating
seasonal performance factor (HSPF in
British thermal units per Watt-hour
(Btu/W-h));
(ii) For air conditioners (excluding
space constrained), the energy efficiency
ratio (EER in British thermal units per
Watt-hour (Btu/W-h));
(iii) For single-split-system
equipment, whether the represented
value is for a coil-only or blower coil
system; and
(iv) For multi-split, multiple-circuit,
and multi-head mini-split systems
(including VRF), whether the
represented value is for a non-ducted,
ducted, mixed non-ducted/ducted
system, SDHV, mixed non-ducted/
SDHV system, or mixed ducted/SDHV
system.
(3) Basic and individual model
numbers. The basic model number and
individual model number(s) required to
be reported under § 429.12(b)(6) must
consist of the following:
Individual model number(s)
asabaliauskas on DSK3SPTVN1PROD with RULES
Equipment type
Basic model number
1
Single-Package (including
Space-Constrained).
Single-Split System (including Space-Constrained).
VerDate Sep<11>2014
Number unique to the
basic model.
Number unique to the
basic model.
23:36 Jun 07, 2016
Jkt 238001
PO 00000
2
Package ............................
N/A ....................................
N/A.
Outdoor Unit ......................
Indoor Unit ........................
Air Mover (could be same
as indoor unit if fan is
part of indoor unit model
number).
Frm 00062
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
3
08JNR2
37053
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Individual model number(s)
Equipment type
Basic model number
1
2
When certifying a basic
model based on tested
combination(s): ***.
When certifying an individual combination: Indoor Unit(s).
N/A ....................................
Number unique to the
basic model.
Outdoor Unit ......................
Outdoor Unit with No
Match.
asabaliauskas on DSK3SPTVN1PROD with RULES
Multi-Split, Multi-Circuit,
and Multi-Head Mini-Split
System (including
SDHV).
Number unique to the
basic model.
Outdoor Unit ......................
(4) Additional product-specific
information. Pursuant to § 429.12(b)(13),
for each individual model/combination
(or ‘‘tested combination’’), a certification
report must include the following
additional product-specific information:
the cooling full load air volume rate for
the system or for each indoor unit as
applicable (in cubic feet per minute
(cfm)); the air volume rates for other test
conditions including minimum cooling
air volume rate, intermediate cooling air
volume rate, full load heating air
volume rate, minimum heating air
volume rate, intermediate heating air
volume rate, and nominal heating air
volume rate (cfm) for the system or for
each indoor unit as applicable, if
different from the cooling full load air
volume rate; whether the individual
model/combination uses a fixed orifice,
thermostatic expansion valve, electronic
expansion valve, or other type of
metering device; the duration of the
compressor break-in period, if used;
whether the optional tests were
conducted to determine the C value
used to represent cooling mode cycling
losses or whether the default value was
used; the temperature at which the
crankcase heater with controls is
designed to turn on, if applicable; the
maximum time between defrosts as
allowed by the controls (in hours); and
(i) For heat pumps, whether the
optional tests were conducted to
determine the C value or whether the
default value was used;
(ii) For multi-split, multiple-circuit,
and multi-head mini-split systems, the
number of indoor units tested with the
outdoor unit; the nominal cooling
capacity of each indoor unit and
outdoor unit in the combination; and
the indoor units that are not providing
heating or cooling for part-load tests;
(iii) For ducted systems having
multiple indoor fans within a single
indoor unit, the number of indoor fans;
the nominal cooling capacity of the
indoor unit and outdoor unit; and
which fan(s) were operating and the
allocation of the air volume rate to each
operational fan for each operating mode
used to determine represented values;
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
(iv) For blower coil systems, the
airflow-control settings associated with
full load cooling operation; and the
airflow-control settings or alternative
instructions for setting fan speeds for
tests other than full load cooling
operation to the speeds upon which the
represented value is based;
(v) For equipment with time-adaptive
defrost control, the frosting interval to
be used during frost accumulation tests
and the procedure for manually
initiating the defrost at the specified
time;
(vi) For models of indoor units
designed for both horizontal and
vertical installation or for both up-flow
and down-flow vertical installations, the
orientation used for testing;
(vii) For variable speed equipment,
the compressor frequency set points,
and the required dip switch/control
settings for step or variable components;
and
(viii) For variable speed heat pumps,
whether the unit controls restrict use of
minimum compressor speed operation
for some range of operating ambient
conditions, whether the unit controls
restrict use of maximum compressor
speed operation for any ambient
temperatures below 17 °F, and
whether the optional H42 low
temperature test was used to
characterize performance at
temperatures below 17 °F.
(f) Represented values for the Federal
Trade Commission. The following
represented value determinations shall
be followed to meet the requirements of
the Federal Trade Commission.
(1) Annual Operating Cost—Cooling.
Determine the represented value of
estimated annual operating cost for
cooling-only units or the cooling portion
of the estimated annual operating cost
for air-source heat pumps that provide
both heating and cooling by calculating
the product of:
(i) The quotient of the represented
value of cooling capacity, in Btu’s per
hour as determined in paragraph
(b)(3)(iii) of this section, divided by the
represented value of SEER, in Btu’s per
watt-hour, as determined in paragraph
(b)(3)(ii) of this section;
PO 00000
Frm 00063
Fmt 4701
Sfmt 4700
3
When certifying a basic
model based on tested
combination(s): ***
When certifying an individual combination: Air
Mover(s).
N/A.
(ii) The representative average use
cycle for cooling of 1,000 hours per
year;
(iii) A conversion factor of 0.001
kilowatt per watt; and
(iv) The representative average unit
cost of electricity in dollars per
kilowatt-hour as provided pursuant to
section 323(b)(2) of the Act.
(2) Annual Operating Cost—Heating.
Determine the represented value of
estimated annual operating cost for airsource heat pumps that provide only
heating or for the heating portion of the
estimated annual operating cost for airsource heat pumps that provide both
heating and cooling, as the product of:
(i) The quotient of the mean of the
standardized design heating
requirement for the sample, in Btu’s per
hour, nearest to the Region IV minimum
design heating requirement, determined
for each unit in the sample in section
4.2 of appendix M to subpart B of part
430, divided by the represented value of
heating seasonal performance factor
(HSPF), in Btu’s per watt-hour,
calculated for Region IV corresponding
to the above-mentioned standardized
design heating requirement, as
determined in paragraph (b)(3)(ii) of this
section;
(ii) The representative average use
cycle for heating of 2,080 hours per
year;
(iii) The adjustment factor of 0.77,
which serves to adjust the calculated
design heating requirement and heating
load hours to the actual load
experienced by a heating system;
(iv) A conversion factor of 0.001
kilowatt per watt; and
(v) The representative average unit
cost of electricity in dollars per
kilowatt-hour as provided pursuant to
section 323(b)(2) of the Act.
(3) Annual Operating Cost—Total.
Determine the represented value of
estimated annual operating cost for airsource heat pumps that provide both
heating and cooling by calculating the
sum of the quantity determined in
paragraph (f)(1) of this section added to
the quantity determined in paragraph
(f)(2) of this section.
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37054
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
(4) Regional Annual Operating Cost—
Cooling. Determine the represented
value of estimated regional annual
operating cost for cooling-only units or
the cooling portion of the estimated
regional annual operating cost for airsource heat pumps that provide both
heating and cooling by calculating the
product of:
(i) The quotient of the represented
value of cooling capacity, in Btu’s per
hour, determined in paragraph (b)(3)(iii)
of this section divided by the
represented value of SEER, in Btu’s per
watt-hour, determined in paragraph
(b)(3)(ii) of this section;
(ii) The estimated number of regional
cooling load hours per year determined
from Table 21 in section 4.4 of appendix
M to subpart B of part 430;
(iii) A conversion factor of 0.001
kilowatts per watt; and
(iv) The representative average unit
cost of electricity in dollars per
kilowatt-hour as provided pursuant to
section 323(b)(2) of the Act.
(5) Regional Annual Operating Cost—
Heating. Determine the represented
value of estimated regional annual
operating cost for air-source heat pumps
that provide only heating or for the
heating portion of the estimated regional
annual operating cost for air-source heat
pumps that provide both heating and
cooling as the product of:
(i) The estimated number of regional
heating load hours per year determined
from Table 21 in section 4.4 of appendix
M to subpart B of part 430;
(ii) The quotient of the mean of the
standardized design heating
requirement for the sample, in Btu’s per
hour, for the appropriate generalized
climatic region of interest (i.e.,
corresponding to the regional heating
load hours from ‘‘A’’) and determined
for each unit in the sample in section
4.2 of appendix M to subpart B of Part
430, divided by the represented value of
HSPF, in Btu’s per watt-hour, calculated
for the appropriate generalized climatic
region of interest and corresponding to
the above-mentioned standardized
design heating requirement, and
determined in paragraph (b)(3)(iii);
(iii) The adjustment factor of 0.77;
which serves to adjust the calculated
design heating requirement and heating
load hours to the actual load
experienced by a heating system;
(iv) A conversion factor of 0.001
kilowatts per watt; and
(v) The representative average unit
cost of electricity in dollars per
kilowatt-hour as provided pursuant to
section 323(b)(2) of the Act; and
(6) Regional Annual Operating Cost—
Total. For air-source heat pumps that
provide both heating and cooling, the
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
estimated regional annual operating cost
is the sum of the quantity determined in
paragraph (f)(4) of this section added to
the quantity determined in paragraph
(f)(5) of this section.
(7) Annual Operating Cost—
Rounding. Round any represented
values of estimated annual operating
cost determined in paragraphs (f)(1)
through (6) of this section to the nearest
dollar per year.
4. Section 429.70 is amended by
revising paragraph (e) to read as follows:
§ 429.70 Alternative methods for
determining energy efficiency or energy
use.
*
*
*
*
*
(e) Alternate Efficiency Determination
Method (AEDM) for central air
conditioners and heat pumps. This
paragraph (e) sets forth the requirements
for a manufacturer to use an AEDM to
rate central air conditioners and heat
pumps.
(1) Criteria an AEDM must satisfy. A
manufacturer may not apply an AEDM
to an individual model/combination to
determine its represented values (SEER,
EER, HSPF, and/or PW,OFF) pursuant to
this section unless authorized pursuant
to § 429.16(d) and:
(i) The AEDM is derived from a
mathematical model that estimates the
energy efficiency or energy
consumption characteristics of the
individual model or combination (SEER,
EER, HSPF, and/or PW,OFF) as measured
by the applicable DOE test procedure;
and
(ii) The manufacturer has validated
the AEDM in accordance with
paragraph (e)(2) of this section.
(2) Validation of an AEDM. Before
using an AEDM, the manufacturer must
validate the AEDM’s accuracy and
reliability as follows:
(i) The manufacturer must complete
testing of each basic model as required
under § 429.16(b)(2). Using the AEDM,
calculate the energy use or efficiency for
each of the tested individual models/
combinations within each basic model.
Compare the represented value based on
testing and the AEDM energy use or
efficiency output according to paragraph
(e)(2)(ii) of this section. The
manufacturer is responsible for ensuring
the accuracy and reliability of the
AEDM.
(ii) Individual model/combination
tolerances. This paragraph (e)(2)(ii)
provides the tolerances applicable to
individual models/combinations rated
using an AEDM.
(A) The predicted represented values
for each individual model/combination
calculated by applying the AEDM may
not be more than four percent greater
PO 00000
Frm 00064
Fmt 4701
Sfmt 4700
(for measures of efficiency) or less (for
measures of consumption) than the
values determined from the
corresponding test of the individual
model/combination.
(B) The predicted energy efficiency or
consumption for each individual model/
combination calculated by applying the
AEDM must meet or exceed the
applicable federal energy conservation
standard.
(iii) Additional test unit requirements.
(A) Each AEDM must be supported by
test data obtained from physical tests of
current individual models/
combinations; and
(B) Test results used to validate the
AEDM must meet or exceed current,
applicable Federal standards as
specified in part 430 of this chapter; and
(C) Each test must have been
performed in accordance with the
applicable DOE test procedure with
which compliance is required at the
time the individual models/
combinations used for validation are
distributed in commerce.
(3) AEDM records retention
requirements. If a manufacturer has
used an AEDM to determine
representative values pursuant to this
section, the manufacturer must have
available upon request for inspection by
the Department records showing:
(i) The AEDM, including the
mathematical model, the engineering or
statistical analysis, and/or computer
simulation or modeling that is the basis
of the AEDM;
(ii) Product information, complete test
data, AEDM calculations, and the
statistical comparisons from the units
tested that were used to validate the
AEDM pursuant to paragraph (e)(2) of
this section; and
(iii) Product information and AEDM
calculations for each individual model/
combination to which the AEDM has
been applied.
(4) Additional AEDM requirements. If
requested by the Department, the
manufacturer must:
(i) Conduct simulations before
representatives of the Department to
predict the performance of particular
individual models/combinations;
(ii) Provide analyses of previous
simulations conducted by the
manufacturer; and/or
(iii) Conduct certification testing of
individual models or combinations
selected by the Department.
(5) AEDM verification testing. DOE
may use the test data for a given
individual model/combination
generated pursuant to § 429.104 to
verify the represented value determined
by an AEDM as long as the following
process is followed:
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
(i) Selection of units. DOE will obtain
one or more units for test from retail, if
available. If units cannot be obtained
from retail, DOE will request that a unit
be provided by the manufacturer;
(ii) Lab requirements. DOE will
conduct testing at an independent,
third-party testing facility of its
choosing. In cases where no third-party
laboratory is capable of testing the
equipment, testing may be conducted at
a manufacturer’s facility upon DOE’s
request.
(iii) Testing. At no time during
verification testing may the lab and the
manufacturer communicate without
DOE authorization. If during test set-up
or testing, the lab indicates to DOE that
it needs additional information
regarding a given individual model or
combination in order to test in
accordance with the applicable DOE test
procedure, DOE may organize a meeting
between DOE, the manufacturer and the
lab to provide such information.
(iv) Failure to meet certified
represented value. If an individual
model/combination tests worse than its
certified represented value (i.e., lower
than the certified efficiency value or
higher than the certified consumption
value) by more than 5 percent, or the
test results in a different cooling
capacity than its certified cooling
capacity by more than 5 percent, DOE
will notify the manufacturer. DOE will
provide the manufacturer with all
documentation related to the test set up,
test conditions, and test results for the
unit. Within the timeframe allotted by
DOE, the manufacturer:
(A) May present any and all claims
regarding testing validity; and
(B) If not on site for the initial test setup, must test at least one additional unit
of the same individual model or
combination obtained from a retail
source at its own expense, following the
test requirements in § 429.110(a)(3).
When testing at an independent lab, the
manufacturer may choose to have DOE
and the manufacturer present.
(v) Tolerances. This paragraph
specifies the tolerances DOE will permit
when conducting verification testing.
(A) For consumption metrics, the
result from a DOE verification test must
be less than or equal to 1.05 multiplied
by the certified represented value.
(B) For efficiency metrics, the result
from a DOE verification test must be
greater than or equal to 0.95 multiplied
by the certified represented value.
(vi) Invalid represented value. If,
following discussions with the
manufacturer and a retest where
applicable, DOE determines that the
verification testing was conducted
appropriately in accordance with the
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
DOE test procedure, DOE will issue a
determination that the represented
values for the basic model are invalid.
The manufacturer must conduct
additional testing and re-rate and recertify the individual models/
combinations within the basic model
that were rated using the AEDM based
on all test data collected, including
DOE’s test data.
(vii) AEDM use. This paragraph
(e)(5)(vii) specifies when a
manufacturer’s use of an AEDM may be
restricted due to prior invalid
represented values.
(A) If DOE has determined that a
manufacturer made invalid represented
values on individual models/
combinations within two or more basic
models rated using the manufacturer’s
AEDM within a 24 month period, the
manufacturer must test the least
efficient and most efficient individual
model/combination within each basic
model in addition to the individual
model/combination specified in
§ 429.16(b)(2). The twenty-four month
period begins with a DOE determination
that a represented value is invalid
through the process outlined above.
(B) If DOE has determined that a
manufacturer made invalid represented
values on more than four basic models
rated using the manufacturer’s AEDM
within a 24-month period, the
manufacturer may no longer use an
AEDM.
(C) If a manufacturer has lost the
privilege of using an AEDM, the
manufacturer may regain the ability to
use an AEDM by:
(1) Investigating and identifying
cause(s) for failures;
(2) Taking corrective action to address
cause(s);
(3) Performing six new tests per basic
model, a minimum of two of which
must be performed by an independent,
third-party laboratory from units
obtained from retail to validate the
AEDM; and
(4) Obtaining DOE authorization to
resume use of an AEDM.
*
*
*
*
*
■ 5. Section 429.134 is amended by
adding paragraph (k) to read as follows:
§ 429.134 Product-specific enforcement
provisions.
*
*
*
*
*
(k) Central air conditioners and heat
pumps—(1) Verification of cooling
capacity. The cooling capacity of each
tested unit of the individual model (for
single-package systems) or individual
combination (for split systems) will be
measured pursuant to the test
requirements of § 430.23(m) of this
chapter. The mean of the
PO 00000
Frm 00065
Fmt 4701
Sfmt 4700
37055
measurement(s) (either the measured
cooling capacity for a single unit sample
or the average of the measured cooling
capacities for a multiple unit sample)
will be used to determine the applicable
standards for purposes of compliance.
(2) Verification of CD value. (i) For
central air conditioners and heat pumps
other than models of outdoor units with
no match, if manufacturers certify that
they did not conduct the optional tests
to determine the C and/or C value for
an individual model (for single-package
systems) or individual combination (for
split systems), as applicable, the default
C and/or C value will be used as the
basis for calculation of SEER or HSPF
for each unit tested. If manufacturers
certify that they conducted the optional
tests to determine the C and/or C
value for an individual model (for
single-package systems) or individual
combination (for split systems), as
applicable, the C and/or C value will
be measured pursuant to the test
requirements of § 430.23(m) of this
chapter for each unit tested and the
result for each unit tested (either the
tested value or the default value, as
selected according to the criteria for the
cyclic test in 10 CFR part 430, subpart
B, appendix M, section 3.5e) used as the
basis for calculation of SEER or HSPF
for that unit.
(ii) For models of outdoor units with
no match, DOE will use the default C
and/or C value pursuant to 10 CFR part
430.
*
*
*
*
*
PART 430–ENERGY CONSERVATION
PROGRAM FOR CONSUMER
PRODUCTS
6. The authority citation for part 430
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6309; 28 U.S.C.
2461 note.
7. Section 430.2 is amended by:
a. Removing the definition of ‘‘ARM/
simulation adjustment factor;’’
■ b. Revising the definitions of ‘‘basic
model’’ and ‘‘central air conditioner;’’
and
■ c. Removing the definitions of ‘‘coil
family,’’ ‘‘condenser-evaporator coil
combination’’, ‘‘condensing unit,’’
‘‘evaporator coil’’, ‘‘heat pump,’’
‘‘indoor unit,’’ ‘‘outdoor unit,’’ ‘‘small
duct, high velocity system,’’ and ‘‘tested
combination.’’
The revisions read as follows:
■
■
§ 430.2
Definitions.
*
*
*
*
*
Basic model means all units of a given
type of covered product (or class
thereof) manufactured by one
manufacturer; having the same primary
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37056
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
energy source; and, which have
essentially identical electrical, physical,
and functional (or hydraulic)
characteristics that affect energy
consumption, energy efficiency, water
consumption, or water efficiency; and
(1) With respect to general service
fluorescent lamps, general service
incandescent lamps, and incandescent
reflector lamps: Lamps that have
essentially identical light output and
electrical characteristics—including
lumens per watt (lm/W) and color
rendering index (CRI).
(2) With respect to faucets and
showerheads: Have the identical flow
control mechanism attached to or
installed within the fixture fittings, or
the identical water-passage design
features that use the same path of water
in the highest flow mode.
(3) With respect to furnace fans: Are
marketed and/or designed to be
installed in the same type of
installation; and
(4) With respect to central air
conditioners and central air
conditioning heat pumps essentially
identical electrical, physical, and
functional (or hydraulic) characteristics
means:
(i) For split systems manufactured by
outdoor unit manufacturers (OUMs): all
individual combinations having the
same model of outdoor unit, which
means comparably performing
compressor(s) [a variation of no more
than five percent in displacement rate
(volume per time) as rated by the
compressor manufacturer, and no more
than five percent in capacity and power
input for the same operating conditions
as rated by the compressor
manufacturer], outdoor coil(s) [no more
than five percent variation in face area
and total fin surface area; same fin
material; same tube material], and
outdoor fan(s) [no more than ten percent
variation in air flow and no more than
twenty percent variation in power
input];
(ii) For split systems having indoor
units manufactured by independent coil
manufacturers (ICMs): all individual
combinations having comparably
performing indoor coil(s) [plus or minus
one square foot face area, plus or minus
one fin per inch fin density, and the
same fin material, tube material, number
of tube rows, tube pattern, and tube
size]; and
(iii) For single-package systems: all
individual models having comparably
performing compressor(s) [no more than
five percent variation in displacement
rate (volume per time) rated by the
compressor manufacturer, and no more
than five percent variations in capacity
and power input rated by the
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
compressor manufacturer corresponding
to the same compressor rating
conditions], outdoor coil(s) and indoor
coil(s) [no more than five percent
variation in face area and total fin
surface area; same fin material; same
tube material], outdoor fan(s) [no more
than ten percent variation in outdoor air
flow], and indoor blower(s) [no more
than ten percent variation in indoor air
flow, with no more than twenty percent
variation in fan motor power input];
(iv) Except that,
(A) for single-package systems and
single-split systems, manufacturers may
instead choose to make each individual
model/combination its own basic model
provided the testing and represented
value requirements in 10 CFR 429.16 of
this chapter are met; and
(B) For multi-split, multi-circuit, and
multi-head mini-split combinations, a
basic model may not include both
individual small-duct, high velocity
(SDHV) combinations and non-SDHV
combinations even when they include
the same model of outdoor unit. The
manufacturer may choose to identify
specific individual combinations as
additional basic models.
*
*
*
*
*
Central air conditioner or central air
conditioning heat pump means a
product, other than a packaged terminal
air conditioner or packaged terminal
heat pump, which is powered by single
phase electric current, air cooled, rated
below 65,000 Btu per hour, not
contained within the same cabinet as a
furnace, the rated capacity of which is
above 225,000 Btu per hour, and is a
heat pump or a cooling unit only. A
central air conditioner or central air
conditioning heat pump may consist of:
a single-package unit; an outdoor unit
and one or more indoor units; an indoor
unit only; or an outdoor unit with no
match. In the case of an indoor unit only
or an outdoor unit with no match, the
unit must be tested and rated as a
system (combination of both an indoor
and an outdoor unit). For all central air
conditioner and central air conditioning
heat pump-related definitions, see
appendix M of subpart B of this part.
*
*
*
*
*
■ 8. Section 430.3 is amended by:
■ a. Adding paragraph (b)(2);
■ b. Revising paragraph (c)(1);
■ c. Adding paragraph (c)(3);
■ d. Revising paragraph (g)(2);
■ e. Removing paragraph (g)(3);
■ f. Redesignating paragraph (g)(4) as
(g)(3);
■ g. Adding a new paragraph (g)(4);
■ h. Removing ‘‘, M, ’’ in paragraph
(g)(5);
■ i. Removing paragraph (g)(10);
PO 00000
Frm 00066
Fmt 4701
Sfmt 4700
j. Redesignating paragraphs (g)(7)
through (9) as (g)(8) through (10);
■ k. Adding new paragraph (g)(7);
■ l. Revising newly redesignated
paragraphs (g)(8) through (10); and
■ m. Revising paragraph (g)(13).
The revisions and additions read as
follows:
■
§ 430.3 Materials incorporated by
reference.
*
*
*
*
*
(b) * * *
(2) ANSI/AMCA 210–07, ANSI/
ASHRAE 51–07 (‘‘AMCA 210–2007’’),
Laboratory Methods of Testing Fans for
Certified Aerodynamic Performance
Rating, ANSI approved August 17, 2007,
Section 8—Report and Results of Test,
Section 8.2—Performance graphical
representation of test results, IBR
approved for appendix M to subpart B,
as follows:
(i) Figure 2A—Static Pressure Tap,
and
(ii) Figure 12—Outlet Chamber
Setup—Multiple Nozzles in Chamber.
(c) * * *
(1) ANSI/AHRI 210/240–2008 with
Addenda 1 and 2 (’’AHRI 210/240–
2008’’), 2008 Standard for Performance
Rating of Unitary Air-Conditioning &
Air-Source Heat Pump Equipment,
ANSI approved October 27, 2011
(Addendum 1 dated June 2011 and
Addendum 2 dated March 2012), IBR
approved for appendix M to subpart B,
as follows:
(i) Section 6—Rating Requirements,
Section 6.1—Standard Ratings, 6.1.3—
Standard Rating Tests, 6.1.3.2—
Electrical Conditions;
(ii) Section 6—Rating Requirements,
Section 6.1—Standard Ratings, 6.1.3—
Standard Rating Tests, 6.1.3.4—
Outdoor-Coil Airflow Rate;
(iii) Section 6—Rating Requirements,
Section 6.1—Standard Ratings, 6.1.3—
Standard Rating Tests, 6.1.3.5—
Requirements for Separated Assemblies;
(iv) Figure D1—Tunnel Air Enthalpy
Test Method Arrangement;
(v) Figure D2—Loop Air Enthalpy
Test Method Arrangement; and
(vi) Figure D4—Room Air Enthalpy
Test Method Arrangement.
*
*
*
*
*
(3) ANSI/AHRI 1230–2010 with
Addendum 2 (‘‘AHRI 1230–2010’’),
2010 Standard for Performance Rating of
Variable Refrigerant Flow (VRF) MultiSplit Air-Conditioning and Heat Pump
Equipment (including Addendum 1
dated March 2011), ANSI approved
August 2, 2010 (Addendum 2 dated
June 2014), IBR approved for appendix
M to subpart B, as follows:
(i) Section 3—Definitions (except 3.8,
3.9, 3.13, 3.14, 3.15, 3.16, 3.23, 3.24,
3.26, 3.27, 3.28, 3.29, 3.30, and 3.31);
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
(ii) Section 5—Test Requirements,
Section 5.1 (untitled), 5.1.3–5.1.4;
(ii) Section 6—Rating Requirements,
Section 6.1—Standard Ratings, 6.1.5—
Airflow Requirements for Systems with
Capacities <65,000 Btu/h [19,000 W];
(iii) Section 6—Rating Requirements,
Section 6.1—Standard Ratings, 6.1.6—
Outdoor-Coil Airflow Rate (Applies to
all Air-to-Air Systems);
(iv) Section 6—Rating Requirements,
Section 6.2—Conditions for Standard
Rating Test for Air-cooled Systems <
65,000 Btu/h [19,000W] (except Table
8); and
(v) Table 4—Refrigerant Line Length
Correction Factors.
*
*
*
*
*
(g) * * *
(2) ANSI/ASHRAE 23.1–2010,
(‘‘ASHRAE 23.1–2010’’), Methods of
Testing for Rating the Performance of
Positive Displacement Refrigerant
Compressors and Condensing Units that
Operate at Subcritical Temperatures of
the Refrigerant, ANSI approved January
28, 2010, IBR approved for appendix M
to subpart B, as follows:
(i) Section 5—Requirements;
(ii) Section 6—Instruments;
(iii) Section 7—Methods of Testing;
and
(iv) Section 8—Compressor Testing.
*
*
*
*
*
(4) ANSI/ASHRAE Standard 37–2009,
(‘‘ANSI/ASHRAE 37–2009’’), Methods
of Testing for Rating Electrically Driven
Unitary Air-Conditioning and Heat
Pump Equipment, ANSI approved June
25, 2009, IBR approved for appendix M
to subpart B, as follows:
(i) Section 5—Instruments, Section
5.1—Temperature Measuring
Instruments: 5.1.1;
(ii) Section 5—Instruments, Section
5.2—Refrigerant, Liquid, and Barometric
Pressure Measuring Instruments;
(iii) Section 5—Instruments, Section
5.5—Volatile Refrigerant Flow
Measurement;
(iv) Section 6—Airflow and Air
Differential Pressure Measurement
Apparatus, Section 6.1—Enthalpy
Apparatus (Excluding Figure 3): 6.1.1–
6.1.2 and 6.1.4;
(v) Section 6—Airflow and Air
Differential Pressure Measurement
Apparatus, Section 6.2—Nozzle Airflow
Measuring Apparatus (Excluding Figure
5);
(vi) Section 6—Airflow and Air
Differential Pressure Measurement
Apparatus, Section 6.3—Nozzles
(Excluding Figure 6);
(vii) Section 6—Airflow and Air
Differential Pressure Measurement
Apparatus, Section 6.4—External Static
Pressure Measurements;
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
(viii) Section 6—Airflow and Air
Differential Pressure Measurement
Apparatus, Section 6.5—Recommended
Practices for Static Pressure
Measurements;
(ix) Section 7—Methods of Testing
and Calculation, Section 7.3—Indoor
and Outdoor Air Enthalpy Methods
(Excluding Table 1);
(x) Section 7—Methods of Testing and
Calculation, Section 7.4—Compressor
Calibration Method;
(xi) Section 7—Methods of Testing
and Calculation, Section 7.5—
Refrigerant Enthalpy Method;
(xii) Section 7—Methods of Testing
and Calculation, Section 7.7—Airflow
Rate Measurement, Section 7.7.2—
Calculations—Nozzle Airflow
Measuring Apparatus (Excluding Figure
10), 7.7.2.1–7.7.2.2;
(xiii) Section 8—Test Procedures,
Section 8.1—Test Room Requirements:
8.1.2–8.1.3;
(xiv) Section 8—Test Procedures,
Section 8.2—Equipment Installation;
(xv) Section 8—Test Procedures,
Section 8.6—Additional Requirements
for the Outdoor Air Enthalpy Method,
Section 8.6.2;
(xvii) Section 8—Test Procedures,
Section 8.6—Additional Requirements
for the Outdoor Air Enthalpy Method,
Table 2a—Test Tolerances (SI Units),
and
(xviii) Section 8—Test Procedures,
Section 8.6—Additional Requirements
for the Outdoor Air Enthalpy Method,
Table 2b—Test Tolerances (I–P Units);
(xix) Section 9—Data to be Recorded,
Section 9.2—Test Tolerances; and
(xx) Section 9—Data to be Recorded,
Table 3—Data to be Recorded.
*
*
*
*
*
(7) ANSI/ASHRAE Standard 41.1–
2013, (‘‘ANSI/ASHRAE 41.1–2013’’),
Standard Method for Temperature
Measurement, ANSI approved January
30, 2013, IBR approved for appendix M
to subpart B, as follows:
(i) Section 4—Classifications;
(ii) Section 5—Requirements, Section
5.3—Airstream Temperature
Measurements;
(iii) Section 6—Instruments; and
(iv) Section 7—Temperature Test
Methods (Informative).
(8) ANSI/ASHRAE Standard 41.2–
1987 (RA 1992), (‘‘ASHRAE 41.2–1987
(RA 1992)’’), Standard Methods for
Laboratory Airflow Measurement, ANSI
reaffirmed April 20, 1992, Section 5—
Section of Airflow-Measuring
Equipment and Systems, IBR approved
for appendix M to subpart B, as follows:
(i) Section 5.2—Test Ducts,, Section
5.2.2—Mixers, 5.2.2.1—Performance of
Mixers (excluding Figures 11 and 12
and Table 1); and
PO 00000
Frm 00067
Fmt 4701
Sfmt 4700
37057
(ii) Figure 14—Outlet Chamber Setup
for Multiple Nozzles in Chamber.
(9) ANSI/ASHRAE Standard 41.6–
2014, (‘‘ASHRAE 41.6–2014’’), Standard
Method for Humidity Measurement,
ANSI approved July 3, 2014, IBR
approved for appendix M to subpart B,
as follows:
(i) Section 4—Classifications;
(ii) Section 5—Requirements;
(iii) Section 6—Instruments and
Calibration; and
(iv) Section 7—Humidity
Measurement Methods.
(10) ANSI/ASHRAE 41.9–2011,
(‘‘ASHRAE 41.9–2011’’), Standard
Methods for Volatile-Refrigerant Mass
Flow Measurements Using Calorimeters,
ANSI approved February 3, 2011, IBR
approved for appendix M to subpart B,
as follows:
(i) Section 5—Requirements;
(ii) Section 6—Instruments;
(iii) Section 7—Secondary Refrigerant
Calorimeter Method;
(iv) Section 8—Secondary Fluid
Calorimeter Method;
(v) Section 9—Primary Refrigerant
Calorimeter Method; and
(vi) Section 11—Lubrication
Circulation Measurements.
*
*
*
*
*
(13) ANSI/ASHRAE Standard 116–
2010, (‘‘ASHRAE 116–2010’’), Methods
of Testing for Rating Seasonal Efficiency
of Unitary Air Conditioners and Heat
Pumps, ANSI approved February 24,
2010, Section 7—Methods of Test,
Section 7.4—Air Enthalpy Method—
Indoor Side (Primary Method), Section
7.4.3—Measurements, Section 7.4.3.4—
Temperature, Section 7.4.3.4.5, IBR
approved for appendix M to subpart B.
*
*
*
*
*
■ 9. Section 430.23 is amended by
revising paragraph (m) to read as
follows:
§ 430.23 Test procedures for the
measurement of energy and water
consumption.
*
*
*
*
*
(m) Central air conditioners and heat
pumps. (1) Determine cooling capacity
must be determined from the steadystate wet-coil test (A or A2 Test), as
described in section 3.3 of appendix M
to this subpart, and round off:
(i) To the nearest 50 Btu/h if cooling
capacity is less than 20,000 Btu/h,
(ii) To the nearest 100 Btu/h if cooling
capacity is greater than or equal to
20,000 Btu/h but less than 38,000 Btu/
h, and
(iii) To the nearest 250 Btu/h if
cooling capacity is greater than or equal
to 38,000 Btu/h and less than 65,000
Btu/h.
E:\FR\FM\08JNR2.SGM
08JNR2
37058
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
(2) Determine seasonal energy
efficiency ratio (SEER) as described in
section 4.1 of appendix M to this
subpart, and round off to the nearest
0.025 Btu/W-h.
(3) Determine energy efficiency ratio
(EER) as described in section 4.6 of
appendix M to this subpart, and round
off to the nearest 0.025 Btu/W-h.
(4) Determine heating seasonal
performance factors (HSPF) as described
in section 4.2 of appendix M to this
subpart, and round off to the nearest
0.025 Btu/W-h.
(5) Determine average off mode power
consumption as described in section 4.3
of appendix M to this subpart, and
round off to the nearest 0.5 W.
(6) Determine sensible heat ratio
(SHR), as described in section 4.5 of
appendix M to this subpart, and round
off to the nearest 0.5 percent (%).
(7) Determine all other measures of
energy efficiency or consumption or
other useful measures of performance
using appendix M of this subpart.
*
*
*
*
*
■ 10. Appendix M to subpart B of part
430 is revised to read as follows:
asabaliauskas on DSK3SPTVN1PROD with RULES
Appendix M to Subpart B of Part 430—
Uniform Test Method for Measuring the
Energy Consumption of Central Air
Conditioners and Heat Pumps
Note: Prior to December 5, 2016, any
representations, including compliance
certifications, made with respect to the
energy use, power, or efficiency of central air
conditioners and central air conditioning
heat pumps must be based on the results of
testing pursuant to either this appendix or
the procedures in Appendix M as it appeared
at 10 CFR part 430, subpart B, Appendix M,
in the 10 CFR parts 200 to 499 edition
revised as of January 1, 2015. Any
representations made with respect to the
energy use or efficiency of such central air
conditioners and central air conditioning
heat pumps must be in accordance with
whichever version is selected.
On or after December 5, 2016 and prior to
the compliance date for any amended energy
conservation standards, any representations,
including compliance certifications, made
with respect to the energy use, power, or
efficiency of central air conditioners and
central air conditioning heat pumps must be
based on the results of testing pursuant to
this appendix.
On or after the compliance date for any
amended energy conservation standards, any
representations, including compliance
certifications, made with respect to the
energy use, power, or efficiency of central air
conditioners and central air conditioning
heat pumps must be based on the results of
testing pursuant to appendix M1 of this
subpart.
1. Scope and Definitions
1.1 Scope
This test procedure provides a method of
determining SEER, EER, HSPF and PW,OFF for
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
central air conditioners and central air
conditioning heat pumps including the
following categories:
(a) Split-system air conditioners, including
single-split, multi-head mini-split, multi-split
(including VRF), and multi-circuit systems
(b) Split-system heat pumps, including
single-split, multi-head mini-split, multi-split
(including VRF), and multi-circuit systems
(c) Single-package air conditioners
(d) Single-package heat pumps
(e) Small-duct, high-velocity systems
(including VRF)
(f) Space-constrained products—air
conditioners
(g) Space-constrained products—heat
pumps
For purposes of this appendix, the
Department of Energy incorporates by
reference specific sections of several industry
standards, as listed in § 430.3. In cases where
there is a conflict, the language of the test
procedure in this appendix takes precedence
over the incorporated standards.
All section references refer to sections
within this appendix unless otherwise stated.
1.2 Definitions
Airflow-control settings are programmed or
wired control system configurations that
control a fan to achieve discrete, differing
ranges of airflow—often designated for
performing a specific function (e.g., cooling,
heating, or constant circulation)—without
manual adjustment other than interaction
with a user-operable control (i.e., a
thermostat) that meets the manufacturer
specifications for installed-use. For the
purposes of this appendix, manufacturer
specifications for installed-use are those
found in the product literature shipped with
the unit.
Air sampling device is an assembly
consisting of a manifold with several branch
tubes with multiple sampling holes that
draws an air sample from a critical location
from the unit under test (e.g. indoor air inlet,
indoor air outlet, outdoor air inlet, etc.).
Airflow prevention device denotes a device
that prevents airflow via natural convection
by mechanical means, such as an air damper
box, or by means of changes in duct height,
such as an upturned duct.
Aspirating psychrometer is a piece of
equipment with a monitored airflow section
that draws uniform airflow through the
measurement section and has probes for
measurement of air temperature and
humidity.
Blower coil indoor unit means an indoor
unit either with an indoor blower housed
with the coil or with a separate designated
air mover such as a furnace or a modular
blower (as defined in appendix AA to the
subpart).
Blower coil system refers to a split system
that includes one or more blower coil indoor
units.
Cased coil means a coil-only indoor unit
with external cabinetry.
Coefficient of Performance (COP) means
the ratio of the average rate of space heating
delivered to the average rate of electrical
energy consumed by the heat pump. These
rate quantities must be determined from a
single test or, if derived via interpolation,
must be determined at a single set of
PO 00000
Frm 00068
Fmt 4701
Sfmt 4700
operating conditions. COP is a dimensionless
quantity. When determined for a ducted coilonly system, COP must include the sections
3.7 and 3.9.1 of this appendix: default values
for the heat output and power input of a fan
motor.
Coil-only indoor unit means an indoor unit
that is distributed in commerce without an
indoor blower or separate designated air
mover. A coil-only indoor unit installed in
the field relies on a separately-installed
furnace or a modular blower for indoor air
movement. Coil-only system refers to a
system that includes only (one or more) coilonly indoor units.
Condensing unit removes the heat absorbed
by the refrigerant to transfer it to the outside
environment and consists of an outdoor coil,
compressor(s), and air moving device.
Constant-air-volume-rate indoor blower
means a fan that varies its operating speed to
provide a fixed air-volume-rate from a ducted
system.
Continuously recorded, when referring to a
dry bulb measurement, dry bulb temperature
used for test room control, wet bulb
temperature, dew point temperature, or
relative humidity measurements, means that
the specified value must be sampled at
regular intervals that are equal to or less than
15 seconds.
Cooling load factor (CLF) means the ratio
having as its numerator the total cooling
delivered during a cyclic operating interval
consisting of one ON period and one OFF
period, and as its denominator the total
cooling that would be delivered, given the
same ambient conditions, had the unit
operated continuously at its steady-state,
space-cooling capacity for the same total time
(ON + OFF) interval.
Crankcase heater means any electrically
powered device or mechanism for
intentionally generating heat within and/or
around the compressor sump volume.
Crankcase heater control may be achieved
using a timer or may be based on a change
in temperature or some other measurable
parameter, such that the crankcase heater is
not required to operate continuously. A
crankcase heater without controls operates
continuously when the compressor is not
operating.
Cyclic Test means a test where the unit’s
compressor is cycled on and off for specific
time intervals. A cyclic test provides half the
information needed to calculate a
degradation coefficient.
Damper box means a short section of duct
having an air damper that meets the
performance requirements of section 2.5.7 of
this appendix.
Degradation coefficient (CD) means a
parameter used in calculating the part load
factor. The degradation coefficient for cooling
is denoted by CDc. The degradation
coefficient for heating is denoted by CDh.
Demand-defrost control system means a
system that defrosts the heat pump outdoor
coil-only when measuring a predetermined
degradation of performance. The heat pump’s
controls either:
(1) Monitor one or more parameters that
always vary with the amount of frost
accumulated on the outdoor coil (e.g., coil to
air differential temperature, coil differential
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
air pressure, outdoor fan power or current,
optical sensors) at least once for every ten
minutes of compressor ON-time when space
heating or
(2) Operate as a feedback system that
measures the length of the defrost period and
adjusts defrost frequency accordingly. In all
cases, when the frost parameter(s) reaches a
predetermined value, the system initiates a
defrost. In a demand-defrost control system,
defrosts are terminated based on monitoring
a parameter(s) that indicates that frost has
been eliminated from the coil. (Note: Systems
that vary defrost intervals according to
outdoor dry-bulb temperature are not
demand-defrost systems.) A demand-defrost
control system, which otherwise meets the
above requirements, may allow time-initiated
defrosts if, and only if, such defrosts occur
after 6 hours of compressor operating time.
Design heating requirement (DHR) predicts
the space heating load of a residence when
subjected to outdoor design conditions.
Estimates for the minimum and maximum
DHR are provided for six generalized U.S.
climatic regions in section 4.2 of this
appendix.
Dry-coil tests are cooling mode tests where
the wet-bulb temperature of the air supplied
to the indoor unit is maintained low enough
that no condensate forms on the evaporator
coil.
Ducted system means an air conditioner or
heat pump that is designed to be
permanently installed equipment and
delivers conditioned air to the indoor space
through a duct(s). The air conditioner or heat
pump may be either a split-system or a
single-package unit.
Energy efficiency ratio (EER) means the
ratio of the average rate of space cooling
delivered to the average rate of electrical
energy consumed by the air conditioner or
heat pump. These rate quantities must be
determined from a single test or, if derived
via interpolation, must be determined at a
single set of operating conditions. EER is
expressed in units of Btu/h. When
determined for a ducted coil-only system,
EER must include, from this appendix, the
section 3.3 and 3.5.1 default values for the
heat output and power input of a fan motor.
Evaporator coil means an assembly that
absorbs heat from an enclosed space and
transfers the heat to a refrigerant.
Heat pump means a kind of central air
conditioner that utilizes an indoor
conditioning coil, compressor, and
refrigerant-to-outdoor air heat exchanger to
provide air heating, and may also provide air
cooling, air dehumidifying, air humidifying,
air circulating, and air cleaning.
Heat pump having a heat comfort
controller means a heat pump with controls
that can regulate the operation of the electric
resistance elements to assure that the air
temperature leaving the indoor section does
not fall below a specified temperature. Heat
pumps that actively regulate the rate of
electric resistance heating when operating
below the balance point (as the result of a
second stage call from the thermostat) but do
not operate to maintain a minimum delivery
temperature are not considered as having a
heat comfort controller.
Heating load factor (HLF) means the ratio
having as its numerator the total heating
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
delivered during a cyclic operating interval
consisting of one ON period and one OFF
period, and its denominator the heating
capacity measured at the same test
conditions used for the cyclic test, multiplied
by the total time interval (ON plus OFF) of
the cyclic-test.
Heating season means the months of the
year that require heating, e.g., typically, and
roughly, October through April.
Heating seasonal performance factor
(HSPF) means the total space heating
required during the heating season,
expressed in Btu’s, divided by the total
electrical energy consumed by the heat pump
system during the same season, expressed in
watt-hours. The HSPF used to evaluate
compliance with 10 CFR 430.32(c) is based
on Region IV, the minimum standardized
design heating requirement, and the
sampling plan stated in 10 CFR 429.16(a).
Independent coil manufacturer (ICM)
means a manufacturer that manufactures
indoor units but does not manufacture singlepackage units or outdoor units.
Indoor unit means a separate assembly of
a split system that includes—
(1) An arrangement of refrigerant-to-air
heat transfer coil(s) for transfer of heat
between the refrigerant and the indoor air,
(2) A condensate drain pan, and may or
may not include
(3) Sheet metal or plastic parts not part of
external cabinetry to direct/route airflow over
the coil(s),
(4) A cooling mode expansion device,
(5) External cabinetry, and
(6) An integrated indoor blower (i.e. a
device to move air including its associated
motor). A separate designated air mover that
may be a furnace or a modular blower (as
defined in appendix AA to the subpart) may
be considered to be part of the indoor unit.
A service coil is not an indoor unit.
Multi-head mini-split system means a split
system that has one outdoor unit and that has
two or more indoor units connected with a
single refrigeration circuit. The indoor units
operate in unison in response to a single
indoor thermostat.
Multiple-circuit (or multi-circuit) system
means a split system that has one outdoor
unit and that has two or more indoor units
installed on two or more refrigeration circuits
such that each refrigeration circuit serves a
compressor and one and only one indoor
unit, and refrigerant is not shared from
circuit to circuit.
Multiple-split (or multi-split) system means
a split system that has one outdoor unit and
two or more coil-only indoor units and/or
blower coil indoor units connected with a
single refrigerant circuit. The indoor units
operate independently and can condition
multiple zones in response to at least two
indoor thermostats or temperature sensors.
The outdoor unit operates in response to
independent operation of the indoor units
based on control input of multiple indoor
thermostats or temperature sensors, and/or
based on refrigeration circuit sensor input
(e.g., suction pressure).
Nominal capacity means the capacity that
is claimed by the manufacturer on the
product name plate. Nominal cooling
capacity is approximate to the air conditioner
PO 00000
Frm 00069
Fmt 4701
Sfmt 4700
37059
cooling capacity tested at A or A2 condition.
Nominal heating capacity is approximate to
the heat pump heating capacity tested in H12
test (or the optional H1N test).
Non-ducted indoor unit means an indoor
unit that is designed to be permanently
installed, mounted on room walls and/or
ceilings, and that directly heats or cools air
within the conditioned space.
Normalized Gross Indoor Fin Surface
(NGIFS) means the gross fin surface area of
the indoor unit coil divided by the cooling
capacity measured for the A or A2 Test,
whichever applies.
Off-mode power consumption means the
power consumption when the unit is
connected to its main power source but is
neither providing cooling nor heating to the
building it serves.
Off-mode season means, for central air
conditioners other than heat pumps, the
shoulder season and the entire heating
season; and for heat pumps, the shoulder
season only.
Outdoor unit means a separate assembly of
a split system that transfers heat between the
refrigerant and the outdoor air, and consists
of an outdoor coil, compressor(s), an air
moving device, and in addition for heat
pumps, may include a heating mode
expansion device, reversing valve, and/or
defrost controls.
Outdoor unit manufacturer (OUM) means
a manufacturer of single-package units,
outdoor units, and/or both indoor units and
outdoor units.
Part-load factor (PLF) means the ratio of
the cyclic EER (or COP for heating) to the
steady-state EER (or COP), where both EERs
(or COPs) are determined based on operation
at the same ambient conditions.
Seasonal energy efficiency ratio (SEER)
means the total heat removed from the
conditioned space during the annual cooling
season, expressed in Btu’s, divided by the
total electrical energy consumed by the
central air conditioner or heat pump during
the same season, expressed in watt-hours.
Service coil means an arrangement of
refrigerant-to-air heat transfer coil(s),
condensate drain pan, sheet metal or plastic
parts to direct/route airflow over the coil(s),
which may or may not include external
cabinetry and/or a cooling mode expansion
device, distributed in commerce solely for
the intent of replacing an uncased coil or
cased coil that has already been placed into
service, and that has been labeled
accordingly by the manufacturer.
Shoulder season means the months of the
year in between those months that require
cooling and those months that require
heating, e.g., typically, and roughly, April
through May, and September through
October.
Single-package unit means any central air
conditioner or heat pump that has all major
assemblies enclosed in one cabinet.
Single-split system means a split system
that has one outdoor unit and one indoor
unit connected with a single refrigeration
circuit. Small-duct, high-velocity system
means a split system for which all indoor
units are blower coil indoor units that
produce at least 1.2 inches (of water column)
of external static pressure when operated at
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37060
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
the full-load air volume rate certified by the
manufacturer of at least 220 scfm per rated
ton of cooling.
Split system means any air conditioner or
heat pump that has at least two separate
assemblies that are connected with
refrigerant piping when installed. One of
these assemblies includes an indoor coil that
exchanges heat with the indoor air to provide
heating or cooling, while one of the others
includes an outdoor coil that exchanges heat
with the outdoor air. Split systems may be
either blower coil systems or coil-only
systems.
Standard Air means dry air having a mass
density of 0.075 lb/ft3.
Steady-state test means a test where the
test conditions are regulated to remain as
constant as possible while the unit operates
continuously in the same mode.
Temperature bin means the 5 °F
increments that are used to partition the
outdoor dry-bulb temperature ranges of the
cooling (≥65 °F) and heating (<65 °F) seasons.
Test condition tolerance means the
maximum permissible difference between the
average value of the measured test parameter
and the specified test condition.
Test operating tolerance means the
maximum permissible range that a
measurement may vary over the specified test
interval. The difference between the
maximum and minimum sampled values
must be less than or equal to the specified
test operating tolerance.
Tested combination means a multi-head
mini-split, multi-split, or multi-circuit
system having the following features:
(1) The system consists of one outdoor unit
with one or more compressors matched with
between two and five indoor units;
(2) The indoor units must:
(i) Collectively, have a nominal cooling
capacity greater than or equal to 95 percent
and less than or equal to 105 percent of the
nominal cooling capacity of the outdoor unit;
(ii) Each represent the highest sales volume
model family, if this is possible while
meeting all the requirements of this section.
If this is not possible, one or more of the
indoor units may represent another indoor
model family in order that all the other
requirements of this section are met.
(iii) Individually not have a nominal
cooling capacity greater than 50 percent of
the nominal cooling capacity of the outdoor
unit, unless the nominal cooling capacity of
the outdoor unit is 24,000 Btu/h or less;
(iv) Operate at fan speeds consistent with
manufacturer’s specifications; and
(v) All be subject to the same minimum
external static pressure requirement while
able to produce the same external static
pressure at the exit of each outlet plenum
when connected in a manifold configuration
as required by the test procedure.
(3) Where referenced, ‘‘nominal cooling
capacity’’ means, for indoor units, the highest
cooling capacity listed in published product
literature for 95 °F outdoor dry bulb
temperature and 80 °F dry bulb, 67 °F wet
bulb indoor conditions, and for outdoor
units, the lowest cooling capacity listed in
published product literature for these
conditions. If incomplete or no operating
conditions are published, the highest (for
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
indoor units) or lowest (for outdoor units)
such cooling capacity available for sale must
be used.
Time-adaptive defrost control system is a
demand-defrost control system that measures
the length of the prior defrost period(s) and
uses that information to automatically
determine when to initiate the next defrost
cycle.
Time-temperature defrost control systems
initiate or evaluate initiating a defrost cycle
only when a predetermined cumulative
compressor ON-time is obtained. This
predetermined ON-time is generally a fixed
value (e.g., 30, 45, 90 minutes) although it
may vary based on the measured outdoor
dry-bulb temperature. The ON-time counter
accumulates if controller measurements (e.g.,
outdoor temperature, evaporator
temperature) indicate that frost formation
conditions are present, and it is reset/remains
at zero at all other times. In one application
of the control scheme, a defrost is initiated
whenever the counter time equals the
predetermined ON-time. The counter is reset
when the defrost cycle is completed.
In a second application of the control
scheme, one or more parameters are
measured (e.g., air and/or refrigerant
temperatures) at the predetermined,
cumulative, compressor ON-time. A defrost
is initiated only if the measured parameter(s)
falls within a predetermined range. The ONtime counter is reset regardless of whether or
not a defrost is initiated. If systems of this
second type use cumulative ON-time
intervals of 10 minutes or less, then the heat
pump may qualify as having a demand
defrost control system (see definition).
Triple-capacity, northern heat pump
means a heat pump that provides two stages
of cooling and three stages of heating. The
two common stages for both the cooling and
heating modes are the low capacity stage and
the high capacity stage. The additional
heating mode stage is the booster capacity
stage, which offers the highest heating
capacity output for a given set of ambient
operating conditions.
Triple-split system means a split system
that is composed of three separate
assemblies: An outdoor fan coil section, a
blower coil indoor unit, and an indoor
compressor section.
Two-capacity (or two-stage) compressor
system means a central air conditioner or
heat pump that has a compressor or a group
of compressors operating with only two
stages of capacity. For such systems, low
capacity means the compressor(s) operating
at low stage, or at low load test conditions.
The low compressor stage that operates for
heating mode tests may be the same or
different from the low compressor stage that
operates for cooling mode tests. For such
systems, high capacity means the
compressor(s) operating at high stage, or at
full load test conditions.
Two-capacity, northern heat pump means
a heat pump that has a factory or fieldselectable lock-out feature to prevent space
cooling at high-capacity. Two-capacity heat
pumps having this feature will typically have
two sets of ratings, one with the feature
disabled and one with the feature enabled.
The heat pump is a two-capacity northern
PO 00000
Frm 00070
Fmt 4701
Sfmt 4700
heat pump only when this feature is enabled
at all times. The certified indoor coil model
number must reflect whether the ratings
pertain to the lockout enabled option via the
inclusion of an extra identifier, such as
‘‘+LO’’. When testing as a two-capacity,
northern heat pump, the lockout feature must
remain enabled for all tests.
Uncased coil means a coil-only indoor unit
without external cabinetry.
Variable refrigerant flow (VRF) system
means a multi-split system with at least three
compressor capacity stages, distributing
refrigerant through a piping network to
multiple indoor blower coil units each
capable of individual zone temperature
control, through proprietary zone
temperature control devices and a common
communications network. Note: Single-phase
VRF systems less than 65,000 Btu/h are
central air conditioners and central air
conditioning heat pumps.
Variable-speed compressor system means a
central air conditioner or heat pump that has
a compressor that uses a variable-speed drive
to vary the compressor speed to achieve
variable capacities.
Wet-coil test means a test conducted at test
conditions that typically cause water vapor to
condense on the test unit evaporator coil.
2. Testing Overview and Conditions
(A) Test VRF systems using AHRI 1230–
2010 (incorporated by reference, see § 430.3)
and appendix M. Where AHRI 1230–2010
refers to the appendix C therein substitute
the provisions of this appendix. In cases
where there is a conflict, the language of the
test procedure in this appendix takes
precedence over AHRI 1230–2010.
For definitions use section 1 of appendix
M and section 3 of AHRI 1230–2010
(incorporated by reference, see § 430.3). For
rounding requirements, refer to § 430.23(m).
For determination of certified ratings, refer to
§ 429.16 of this chapter.
For test room requirements, refer to section
2.1 of this appendix. For test unit installation
requirements refer to sections 2.2.a, 2.2.b,
2.2.c, 2.2.1, 2.2.2, 2.2.3(a), 2.2.3(c), 2.2.4,
2.2.5, and 2.4 to 2.12 of this appendix, and
sections 5.1.3 and 5.1.4 of AHRI 1230–2010.
The ‘‘manufacturer’s published instructions,’’
as stated in section 8.2 of ANSI/ASHRAE 37–
2009 (incorporated by reference, see § 430.3)
and ‘‘manufacturer’s installation
instructions’’ discussed in this appendix
mean the manufacturer’s installation
instructions that come packaged with or
appear in the labels applied to the unit. This
does not include online manuals. Installation
instructions that appear in the labels applied
to the unit take precedence over installation
instructions that are shipped with the unit.
For general requirements for the test
procedure, refer to section 3.1 of this
appendix, except for sections 3.1.3 and 3.1.4,
which are requirements for indoor air volume
and outdoor air volume. For indoor air
volume and outdoor air volume
requirements, refer instead to section 6.1.5
(except where section 6.1.5 refers to Table 8,
refer instead to Table 3 of this appendix) and
6.1.6 of AHRI 1230–2010.
For the test method, refer to sections 3.3 to
3.5 and 3.7 to 3.13 of this appendix. For
cooling mode and heating mode test
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
conditions, refer to section 6.2 of AHRI 1230–
2010. For calculations of seasonal
performance descriptors, refer to section 4 of
this appendix.
(B) For systems other than VRF, only a
subset of the sections listed in this test
procedure apply when testing and
determining represented values for a
particular unit. Table 1 shows the sections of
the test procedure that apply to each system.
This table is meant to assist manufacturers in
finding the appropriate sections of the test
procedure; the appendix sections rather than
the table provide the specific requirements
for testing, and given the varied nature of
available units, manufacturers are
responsible for determining which sections
apply to each unit tested based on the unit’s
characteristics. To use this table, first refer to
the sections listed under ‘‘all units’’. Then
refer to additional requirements based on:
(1) System configuration(s),
(2) The compressor staging or modulation
capability, and
(3) Any special features.
Testing requirements for space-constrained
products do not differ from similar
equipment that is not space-constrained and
thus are not listed separately in this table. Air
conditioners and heat pumps are not listed
separately in this table, but heating
procedures and calculations apply only to
heat pumps.
asabaliauskas on DSK3SPTVN1PROD with RULES
Table 1—Informative Guidance for Using
Appendix M
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00071
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
37061
asabaliauskas on DSK3SPTVN1PROD with RULES
37062
VerDate Sep<11>2014
-
General
Testing procedures
General
Cooling
Jkt 238001
Gen-
Cool-
Heat-
era I
ing
ing
4.1
..
Heating
4.2
2.1; 2.2a-c; 2.2.1; 2.2.4; 2.2.4.1;
2.2.4.1 (1); 2.2.4.2; 2.2.5.1-5;
3.1; 3.1.1-3;
2.2.5.7-8; 2.3; 2.3.1; 2.3.2; 2.4;
3.1.5-9; 3.11;
3.1.4.7; 3.1.10; 3.7a,b,d;
PO 00000
2.4.1a,d; 2.5a-c; 2.5.1; 2.5.2-
4.4;
3.8a,d; 3.8.1; 3.9; 3.10
Requirements for all units (except VRF)
4.5
3.3; 3.4; 3.5a-i
3.12
2.5.4.2; 2.5.5- 2.13
Frm 00072
3.1.4.4.1; 3.1.4.4.2;
3.1.4.1.1; 3.1.4.l.la,b;
Single-split system- blower coil
2.2a(l)
3.1.4.4.3a-b; 3.1.4.5.1;
3.1.4.2a-b; 3.1.4.3a-b
Fmt 4701
3.1.4.5.2a-c; 3.1.4.6a-b
3.1.4.4.1; 3.1.4.4.2;
Sfmt 4725
3.1.4.1.1; 3.1.4.l.lc;
Single-split system -coil-only
3.1.4.4.3c;
2.2a(l ); 2.2d,e; 2.4.2
E:\FR\FM\08JNR2.SGM
3.1.4.2c; 3.5.1
:B
..
..,
..
E
3.1.4.5.2d;
Q,
Q,
"'
=
08JNR2
.(!l
=
..
=
..c
.....
..
"'
=
3.7c; 3.8b; 3.9f; 3.9.1b
Tri-split
2.2a(2)
Outdoor unit witb no match
2.2e
3.1.4.4.1; 3.1.4.4.2;
,!
= .,
"' =
E
=
.. ~
...=
="
"'
·;
"'
c.::
=
=
;e
3.1.4.1.1; 3.1.4.l.la,b;
Single-package
2.2.4.1(2); 2.2.5.6b; 2.4.2
3.1.4.4.3a-b; 3.1.4.5.1;
3.1.4.2a-b; 3.1.4.3a-b
3.1.4.5.2a-c; 3.1.4.6a-b
..:
E
;;
'C
~
ER08JN16.004
Calculations
=
=
u
!
"'
Heat pump
Heating-only heat pump
2.2.5.6.a
3.1.4.1.1 Table 4
3.1.4.4.3
..
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
23:36 Jun 07, 2016
Testing conditions
asabaliauskas on DSK3SPTVN1PROD with RULES
VerDate Sep<11>2014
3.2.3c
3.6.3
3.2.5
3.6.6
3.1.4.5.2 c- d
Triple-capacity northern heat pump
SDHV (non-VRF)
4.2.6
2.2b; 2.4.lc; 2.5.4.3
Jkt 238001
3.1.4.4.1; 3.1.4.4.2;
Single- zone-multi-coil split and non-
3.1.4.1.1; 3.1.4.1.la-b;
2.2a(1),(3); 2.2.3; 2.4.1b
3.1.4.4.3a-b; 3.1.4.5.1;
PO 00000
VRF multiple-split with duct
3.1.4.2a-b; 3.1.4.3a-b
3.1.4.5.2a-c; 3.1.4.6a-b
Frm 00073
3.1.4.1.2; 3.1.4.2d;
Single-zone-multi -coil split and non-
3.1.4.4.4; 3.1.4.5.2e; 3.1.4.6c;
2.2.a(1),(3); 2.2.3
3.1.4.3c; 3.2.4c;
VRF multiple-split, ductless
3.6.4.c; 3.8c
Fmt 4701
3.5c,g,h; 3.5.2; 3.8c
2.1; 2.2.a; 2.2.b; 2.2.c; 2.2.1; 2.2.2;
3.1 (except
2.2.3(a); 2.2.3(c);, 2.2.4; 2.2.5; 2.4-
3.1.3, 3.1.4)
2.12
3.1.4.1.lc;
3.3-3.5
3.7-3.10
4.4;
VRF multiple-splitt and
Sfmt 4725
4.5
4.1
VRFSDHVt
4.2
E:\FR\FM\08JNR2.SGM
3.11-3.13
Single speed compressor, fixed air
:E
:c
c.
"'
=
08JNR2
3.2.1
"'
u
4.1.1
4.2.1
3.2.2
3.6.2
4.1.2
4.2.2
3.2.3
3.6.3
4.1.3
4.2.3
3.2.4
Single speed compressor, VAV fan
~
...,
=
Two-capacity compressor
~
3.6.1
3.6.4
4.1.4
4.2.4
volume rate
3.1.10
Variable speed compressor
Heat pump with heat comfort controller
:J
..
..
]
...
..
c.
~
~
Units with a multi-speed outdoor fan
4.2.5
3.6.5
2.2.2
Single indoor unit having multiple
3.2.6
indoor blowers
3.6.2; 3.6.7
4.1.5
4.2.7
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
23:36 Jun 07, 2016
3.1.4.4.2c;
Two-capacity northern heat pump
00
37063
ER08JN16.005
asabaliauskas on DSK3SPTVN1PROD with RULES
37064
VerDate Sep<11>2014
Jkt 238001
PO 00000
Frm 00074
**Applies only to heat pumps; not to air conditioners.
Fmt 4701
tuse AHRI 1230-2010 (incorporated by reference, see§ 430.3), with the sections referenced in section 2(A) of this appendix, in conjunction with the sections set
Sfmt 4725
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.006
forth in the table to perform test setup, testing, and calculations for determining represented values for VRF multiple-split and VRF SDHV systems.
NOTE: For all units, use section 3.13 of this appendix for off mode testing procedures and section 4.3 ofthis appendix for off mode calculations. For all units
subject to an EER standard, use section 4.6 of this appendix to determine the energy efficiency ratio.
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
23:36 Jun 07, 2016
*Does not apply to heating-only heat pumps.
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
2.1 Test Room Requirements
a. Test using two side-by-side rooms: An
indoor test room and an outdoor test room.
For multiple-split, single-zone-multi-coil or
multi-circuit air conditioners and heat
pumps, however, use as many indoor test
rooms as needed to accommodate the total
number of indoor units. These rooms must
comply with the requirements specified in
sections 8.1.2 and 8.1.3 of ANSI/ASHRAE
37–2009 (incorporated by reference, see
§ 430.3).
b. Inside these test rooms, use artificial
loads during cyclic tests and frost
accumulation tests, if needed, to produce
stabilized room air temperatures. For one
room, select an electric resistance heater(s)
having a heating capacity that is
approximately equal to the heating capacity
of the test unit’s condenser. For the second
room, select a heater(s) having a capacity that
is close to the sensible cooling capacity of the
test unit’s evaporator. Cycle the heater
located in the same room as the test unit
evaporator coil ON and OFF when the test
unit cycles ON and OFF. Cycle the heater
located in the same room as the test unit
condensing coil ON and OFF when the test
unit cycles OFF and ON.
2.2 Test Unit Installation Requirements
a. Install the unit according to section 8.2
of ANSI/ASHRAE 37–2009 (incorporated by
reference, see § 430.3), subject to the
following additional requirements:
(1) When testing split systems, follow the
requirements given in section 6.1.3.5 of AHRI
210/240–2008 (incorporated by reference, see
§ 430.3). For the vapor refrigerant line(s), use
the insulation included with the unit; if no
insulation is provided, use insulation
meeting the specifications for the insulation
in the installation instructions included with
the unit by the manufacturer; if no insulation
is included with the unit and the installation
instructions do not contain provisions for
insulating the line(s), fully insulate the vapor
refrigerant line(s) with vapor proof insulation
having an inside diameter that matches the
refrigerant tubing and a nominal thickness of
at least 0.5 inches. For the liquid refrigerant
line(s), use the insulation included with the
unit; if no insulation is provided, use
insulation meeting the specifications for the
insulation in the installation instructions
included with the unit by the manufacturer;
if no insulation is included with the unit and
the installation instructions do not contain
provisions for insulating the line(s), leave the
liquid refrigerant line(s) exposed to the air for
air conditioners and heat pumps that heat
and cool; or, for heating-only heat pumps,
insulate the liquid refrigerant line(s) with
insulation having an inside diameter that
matches the refrigerant tubing and a nominal
thickness of at least 0.5 inches. Insulation
must be the same for the cooling and heating
tests.
(2) When testing split systems, if the
indoor unit does not ship with a cooling
mode expansion device, test the system using
the device as specified in the installation
instructions provided with the indoor unit. If
none is specified, test the system using a
fixed orifice or piston type expansion device
that is sized appropriately for the system.
VerDate Sep<11>2014
01:07 Jun 08, 2016
Jkt 238001
(3) When testing triple-split systems (see
section 1.2 of this appendix, Definitions), use
the tubing length specified in section 6.1.3.5
of AHRI 210/240–2008 (incorporated by
reference, see § 430.3) to connect the outdoor
coil, indoor compressor section, and indoor
coil while still meeting the requirement of
exposing 10 feet of the tubing to outside
conditions;
(4) When testing split systems having
multiple indoor coils, connect each indoor
blower coil unit to the outdoor unit using:
(a) 25 feet of tubing, or
(b) tubing furnished by the manufacturer,
whichever is longer.
At least 10 feet of the system
interconnection tubing shall be exposed to
the outside conditions. If they are needed to
make a secondary measurement of capacity
or for verification of refrigerant charge, install
refrigerant pressure measuring instruments as
described in section 8.2.5 of ANSI/ASHRAE
37–2009 (incorporated by reference, see
§ 430.3). Section 2.10 of this appendix
specifies which secondary methods require
refrigerant pressure measurements and
section 2.2.5.5 of this appendix discusses use
of pressure measurements to verify charge. At
a minimum, insulate the low-pressure line(s)
of a split system with insulation having an
inside diameter that matches the refrigerant
tubing and a nominal thickness of 0.5 inch.
b. For units designed for both horizontal
and vertical installation or for both up-flow
and down-flow vertical installations, use the
orientation for testing specified by the
manufacturer in the certification report.
Conduct testing with the following installed:
(1) The most restrictive filter(s);
(2) Supplementary heating coils; and
(3) Other equipment specified as part of the
unit, including all hardware used by a heat
comfort controller if so equipped (see section
1 of this appendix, Definitions). For smallduct, high-velocity systems, configure all
balance dampers or restrictor devices on or
inside the unit to fully open or lowest
restriction.
c. Testing a ducted unit without having an
indoor air filter installed is permissible as
long as the minimum external static pressure
requirement is adjusted as stated in Table 3,
note 3 (see section 3.1.4 of this appendix).
Except as noted in section 3.1.10 of this
appendix, prevent the indoor air
supplementary heating coils from operating
during all tests. For uncased coils, create an
enclosure using 1 inch fiberglass foil-faced
ductboard having a nominal density of 6
pounds per cubic foot. Or alternatively,
construct an enclosure using sheet metal or
a similar material and insulating material
having a thermal resistance (‘‘R’’ value)
between 4 and 6 hr·ft2· °F/Btu. Size the
enclosure and seal between the coil and/or
drainage pan and the interior of the enclosure
as specified in installation instructions
shipped with the unit. Also seal between the
plenum and inlet and outlet ducts. For cased
coils, no extra insulating or sealing is
allowed.
d. When testing a coil-only system, install
a toroidal-type transformer to power the
system’s low-voltage components, complying
with any additional requirements for the
transformer mentioned in the installation
PO 00000
Frm 00075
Fmt 4701
Sfmt 4700
37065
manuals included with the unit by the
system manufacturer. If the installation
manuals do not provide specifications for the
transformer, use a transformer having the
following features:
(1) A nominal volt-amp rating such that the
transformer is loaded between 25 and 90
percent of this rating for the highest level of
power measured during the off mode test
(section 3.13 of this appendix);
(2) Designed to operate with a primary
input of 230 V, single phase, 60 Hz; and
(3) That provides an output voltage that is
within the specified range for each lowvoltage component. Include the power
consumption of the components connected to
the transformer as part of the total system
power consumption during the off mode
tests; do not include the power consumed by
the transformer when no load is connected to
it.
e. Test an outdoor unit with no match (i.e.,
that is not distributed in commerce with any
indoor units) using a coil-only indoor unit
with a single cooling air volume rate whose
coil has:
(1) Round tubes of outer diameter no less
than 0.375 inches, and
(2) a normalized gross indoor fin surface
(NGIFS) no greater than 1.0 square inches per
British thermal unit per hour (sq. in./Btu/hr).
NGIFS is calculated as follows:
˙
NGIFS = 2 × Lf × Wf × Nf ÷ Qc (95)
Where:
Lf = Indoor coil fin length in inches, also
height of the coil transverse to the tubes.
Wf = Indoor coil fin width in inches, also
depth of the coil.
Nf = Number of fins.
˙
Qc(95) = the measured space cooling capacity
of the tested outdoor unit/indoor unit
combination as determined from the A2
or A Test whichever applies, Btu/h.
f If the outdoor unit or the outdoor portion
of a single-package unit has a drain pan
heater to prevent freezing of defrost water,
the heater shall be energized, subject to
control to de-energize it when not needed by
the heater’s thermostat or the unit’s control
system, for all tests.
2.2.1 Defrost Control Settings
Set heat pump defrost controls at the
normal settings which most typify those
encountered in generalized climatic region
IV. (Refer to Figure 1 and Table 19 of section
4.2 of this appendix for information on
region IV.) For heat pumps that use a timeadaptive defrost control system (see section
1.2 of this appendix, Definitions), the
manufacturer must specify in the
certification report the frosting interval to be
used during frost accumulation tests and
provide the procedure for manually initiating
the defrost at the specified time.
2.2.2 Special Requirements for Units
Having a Multiple-Speed Outdoor Fan
Configure the multiple-speed outdoor fan
according to the installation manual included
with the unit by the manufacturer, and
thereafter, leave it unchanged for all tests.
The controls of the unit must regulate the
operation of the outdoor fan during all lab
tests except dry coil cooling mode tests. For
dry coil cooling mode tests, the outdoor fan
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37066
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
must operate at the same speed used during
the required wet coil test conducted at the
same outdoor test conditions.
2.2.3 Special Requirements for Multi-Split
Air Conditioners and Heat Pumps and
Ducted Systems Using a Single Indoor
Section Containing Multiple Indoor Blowers
That Would Normally Operate Using Two or
More Indoor Thermostats
Because these systems will have more than
one indoor blower and possibly multiple
outdoor fans and compressor systems,
references in this test procedure to a singular
indoor blower, outdoor fan, and/or
compressor means all indoor blowers, all
outdoor fans, and all compressor systems that
are energized during the test.
a. Additional requirements for multi-split
air conditioners and heat pumps. For any test
where the system is operated at part load
(i.e., one or more compressors ‘‘off’’,
operating at the intermediate or minimum
compressor speed, or at low compressor
capacity), the manufacturer must designate in
the certification report the indoor coil(s) that
are not providing heating or cooling during
the test such that the sum of the nominal
heating or cooling capacity of the operational
indoor units is within 5 percent of the
intended part load heating or cooling
capacity. For variable-speed systems, the
manufacturer must designate in the
certification report at least one indoor unit
that is not providing heating or cooling for
all tests conducted at minimum compressor
speed. For all other part-load tests, the
manufacturer must choose to turn off zero,
one, two, or more indoor units. The chosen
configuration must remain unchanged for all
tests conducted at the same compressor
speed/capacity. For any indoor coil that is
not providing heating or cooling during a
test, cease forced airflow through this indoor
coil and block its outlet duct.
b. Additional requirements for ducted split
systems with a single indoor unit containing
multiple indoor blowers (or for singlepackage units with an indoor section
containing multiple indoor blowers) where
the indoor blowers are designed to cycle on
and off independently of one another and are
not controlled such that all indoor blowers
are modulated to always operate at the same
air volume rate or speed. For any test where
the system is operated at its lowest
capacity—i.e., the lowest total air volume
rate allowed when operating the single-speed
compressor or when operating at low
compressor capacity—indoor blowers
accounting for at least one-third of the fullload air volume rate must be turned off
unless prevented by the controls of the unit.
In such cases, turn off as many indoor
blowers as permitted by the unit’s controls.
Where more than one option exists for
meeting this ‘‘off’’ requirement, the
manufacturer shall indicate in its
certification report which indoor blower(s)
are turned off. The chosen configuration shall
remain unchanged for all tests conducted at
the same lowest capacity configuration. For
any indoor coil turned off during a test, cease
forced airflow through any outlet duct
connected to a switched-off indoor blower.
c. For test setups where the laboratory’s
physical limitations requires use of more
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
than the required line length of 25 feet as
listed in section 2.2.a(4) of this appendix,
then the actual refrigerant line length used by
the laboratory may exceed the required
length and the refrigerant line length
correction factors in Table 4 of AHRI 1230–
2010 are applied to the cooling capacity
measured for each cooling mode test.
2.2.4 Wet-Bulb Temperature Requirements
for the Air Entering the Indoor and Outdoor
Coils
2.2.4.1 Cooling Mode Tests
For wet-coil cooling mode tests, regulate
the water vapor content of the air entering
the indoor unit so that the wet-bulb
temperature is as listed in Tables 4 to 7. As
noted in these same tables, achieve a wetbulb temperature during dry-coil cooling
mode tests that results in no condensate
forming on the indoor coil. Controlling the
water vapor content of the air entering the
outdoor side of the unit is not required for
cooling mode tests except when testing:
(1) Units that reject condensate to the
outdoor coil during wet coil tests. Tables 4–
7 list the applicable wet-bulb temperatures.
(2) Single-package units where all or part
of the indoor section is located in the outdoor
test room. The average dew point
temperature of the air entering the outdoor
coil during wet coil tests must be within ±3.0
°F of the average dew point temperature of
the air entering the indoor coil over the 30minute data collection interval described in
section 3.3 of this appendix. For dry coil tests
on such units, it may be necessary to limit
the moisture content of the air entering the
outdoor coil of the unit to meet the
requirements of section 3.4 of this appendix.
2.2.4.2 Heating Mode Tests
For heating mode tests, regulate the water
vapor content of the air entering the outdoor
unit to the applicable wet-bulb temperature
listed in Tables 11 to 14. The wet-bulb
temperature entering the indoor side of the
heat pump must not exceed 60 °F.
Additionally, if the Outdoor Air Enthalpy
test method (section 2.10.1 of this appendix)
is used while testing a single-package heat
pump where all or part of the outdoor section
is located in the indoor test room, adjust the
wet-bulb temperature for the air entering the
indoor side to yield an indoor-side dew point
temperature that is as close as reasonably
possible to the dew point temperature of the
outdoor-side entering air.
2.2.5 Additional Refrigerant Charging
Requirements
2.2.5.1 Instructions To Use for Charging
a. Where the manufacturer’s installation
instructions contain two sets of refrigerant
charging criteria, one for field installations
and one for lab testing, use the field
installation criteria.
b. For systems consisting of an outdoor
unit manufacturer’s outdoor section and
indoor section with differing charging
procedures, adjust the refrigerant charge per
the outdoor installation instructions.
c. For systems consisting of an outdoor
unit manufacturer’s outdoor unit and an
independent coil manufacturer’s indoor unit
with differing charging procedures, adjust the
PO 00000
Frm 00076
Fmt 4701
Sfmt 4700
refrigerant charge per the indoor unit’s
installation instructions. If instructions are
provided only with the outdoor unit or are
provided only with an independent coil
manufacturer’s indoor unit, then use the
provided instructions.
2.2.5.2 Test(s) To Use for Charging
a. Use the tests or operating conditions
specified in the manufacturer’s installation
instructions for charging. The manufacturer’s
installation instructions may specify use of
tests other than the A or A2 test for charging,
but, unless the unit is a heating-only heat
pump, the air volume rate must be
determined by the A or A2 test as specified
in section 3.1 of this appendix.
b. If the manufacturer’s installation
instructions do not specify a test or operating
conditions for charging or there are no
manufacturer’s instructions, use the
following test(s):
(1) For air conditioners or cooling and
heating heat pumps, use the A or A2 test.
(2) For cooling and heating heat pumps
that do not operate in the H1 or H12 test (e.g.,
due to shut down by the unit limiting
devices) when tested using the charge
determined at the A or A2 test, and for
heating-only heat pumps, use the H1 or H12
test.
2.2.5.3 Parameters To Set and Their Target
Values
a. Consult the manufacturer’s installation
instructions regarding which parameters
(e.g., superheat) to set and their target values.
If the instructions provide ranges of values,
select target values equal to the midpoints of
the provided ranges.
b. In the event of conflicting information
between charging instructions (i.e., multiple
conditions given for charge adjustment where
all conditions specified cannot be met),
follow the following hierarchy.
(1) For fixed orifice systems:
(i) Superheat
(ii) High side pressure or corresponding
saturation or dew-point temperature
(iii) Low side pressure or corresponding
saturation or dew-point temperature
(iv) Low side temperature
(v) High side temperature
(vi) Charge weight
(2) For expansion valve systems:
(i) Subcooling
(ii) High side pressure or corresponding
saturation or dew-point temperature
(iii) Low side pressure or corresponding
saturation or dew-point temperature
(iv) Approach temperature (difference
between temperature of liquid leaving
condenser and condenser average inlet air
temperature)
(v) Charge weight
c. If there are no installation instructions
and/or they do not provide parameters and
target values, set superheat to a target value
of 12 °F for fixed orifice systems or set
subcooling to a target value of 10 °F for
expansion valve systems.
2.2.5.4 Charging Tolerances
a. If the manufacturer’s installation
instructions specify tolerances on target
values for the charging parameters, set the
values within these tolerances.
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
b. Otherwise, set parameter values within
the following test condition tolerances for the
different charging parameters:
(1) Superheat: +/¥ 2.0 °F
(2) Subcooling: +/¥ 2.0 °F
(3) High side pressure or corresponding
saturation or dew point temperature: +/¥ 4.0
psi or +/¥ 1.0 °F
(4) Low side pressure or corresponding
saturation or dew point temperature: +/¥ 2.0
psi or +/¥ 0.8 °F
(5) High side temperature: +/¥ 2.0 °F
(6) Low side temperature: +/¥ 2.0 °F
(7) Approach temperature: +/¥ 1.0 °F
(8) Charge weight: +/¥ 2.0 ounce
2.2.5.5 Special Charging Instructions
a. Cooling and Heating Heat Pumps
If, using the initial charge set in the A or
A2 test, the conditions are not within the
range specified in manufacturer’s installation
instructions for the H1 or H12 test, make as
small as possible an adjustment to obtain
conditions for this test in the specified range.
After this adjustment, recheck conditions in
the A or A2 test to confirm that they are still
within the specified range for the A or A2
test.
b. Single-Package Systems
Unless otherwise directed by the
manufacturer’s installation instructions,
install one or more refrigerant line pressure
gauges during the setup of the unit, located
depending on the parameters used to verify
or set charge, as described:
(1) Install a pressure gauge at the location
of the service valve on the liquid line if
charging is on the basis of subcooling, or high
side pressure or corresponding saturation or
dew point temperature;
(2) Install a pressure gauge at the location
of the service valve on the suction line if
charging is on the basis of superheat, or low
side pressure or corresponding saturation or
dew point temperature.
Use methods for installing pressure
gauge(s) at the required location(s) as
indicated in manufacturer’s instructions if
specified.
2.2.5.6 Near-Azeotropic and Zeotropic
Refrigerants
Perform charging of near-azeotropic and
zeotropic refrigerants only with refrigerant in
the liquid state.
2.2.5.7 Adjustment of Charge Between Tests
After charging the system as described in
this test procedure, use the set refrigerant
charge for all tests used to determine
performance. Do not adjust the refrigerant
charge at any point during testing. If
measurements indicate that refrigerant charge
has leaked during the test, repair the
refrigerant leak, repeat any necessary set-up
steps, and repeat all tests.
2.3 Indoor Air Volume Rates
If a unit’s controls allow for overspeeding
the indoor blower (usually on a temporary
basis), take the necessary steps to prevent
overspeeding during all tests.
2.3.1 Cooling Tests
a. Set indoor blower airflow-control
settings (e.g., fan motor pin settings, fan
motor speed) according to the requirements
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
that are specified in section 3.1.4 of this
appendix.
b. Express the Cooling full-load air volume
rate, the Cooling Minimum Air Volume Rate,
and the Cooling Intermediate Air Volume
Rate in terms of standard air.
2.3.2 Heating Tests
a. Set indoor blower airflow-control
settings (e.g., fan motor pin settings, fan
motor speed) according to the requirements
that are specified in section 3.1.4 of this
appendix.
b. Express the heating full-load air volume
rate, the heating minimum air volume rate,
the heating intermediate air volume rate, and
the heating nominal air volume rate in terms
of standard air.
2.4 Indoor Coil Inlet and Outlet Duct
Connections
Insulate and/or construct the outlet
plenum as described in section 2.4.1 of this
appendix and, if installed, the inlet plenum
described in section 2.4.2 of this appendix
with thermal insulation having a nominal
overall resistance (R-value) of at least 19 hr
• ft2 • °F/Btu.
2.4.1 Outlet Plenum for the Indoor Unit
a. Attach a plenum to the outlet of the
indoor coil. (Note: For some packaged
systems, the indoor coil may be located in
the outdoor test room.)
b. For systems having multiple indoor
coils, or multiple indoor blowers within a
single indoor section, attach a plenum to
each indoor coil or indoor blower outlet. In
order to reduce the number of required
airflow measurement apparati (section 2.6 of
this appendix), each such apparatus may
serve multiple outlet plenums connected to
a single common duct leading to the
apparatus. More than one indoor test room
may be used, which may use one or more
common ducts leading to one or more airflow
measurement apparati within each test room
that contains multiple indoor coils. At the
plane where each plenum enters a common
duct, install an adjustable airflow damper
and use it to equalize the static pressure in
each plenum. Each outlet air temperature
grid (section 2.5.4 of this appendix) and
airflow measuring apparatus are located
downstream of the inlet(s) to the common
duct. For multiple-circuit (or multi-circuit)
systems for which each indoor coil outlet is
measured separately and its outlet plenum is
not connected to a common duct connecting
multiple outlet plenums, the outlet air
temperature grid and airflow measuring
apparatus must be installed at each outlet
plenum.
c. For small-duct, high-velocity systems,
install an outlet plenum that has a diameter
that is equal to or less than the value listed
in Table 2. The limit depends only on the
Cooling full-load air volume rate (see section
3.1.4.1.1 of this appendix) and is effective
regardless of the flange dimensions on the
outlet of the unit (or an air supply plenum
adapter accessory, if installed in accordance
with the manufacturer’s installation
instructions).
d. Add a static pressure tap to each face of
the (each) outlet plenum, if rectangular, or at
four evenly distributed locations along the
PO 00000
Frm 00077
Fmt 4701
Sfmt 4700
37067
circumference of an oval or round plenum.
Create a manifold that connects the four
static pressure taps. Figure 9 of ANSI/
ASHRAE 37–2009 (incorporated by
reference, see § 430.3) shows allowed options
for the manifold configuration. The crosssectional dimensions of plenum shall be
equal to the dimensions of the indoor unit
outlet. See Figures 7a, 7b, and 7c of ANSI/
ASHRAE 37–2009 for the minimum length of
the (each) outlet plenum and the locations for
adding the static pressure taps for ducted
blower coil indoor units and single-package
systems. See Figure 8 of ANSI/ASHRAE 37–
2009 for coil-only indoor units.
TABLE 2—SIZE OF OUTLET PLENUM
FOR SMALL-DUCT HIGH-VELOCITY
INDOOR UNITS
Cooling full-load air volume
rate
(scfm)
≤500 ......................................
501 to 700 ............................
701 to 900 ............................
901 to 1100 ..........................
1101 to 1400 ........................
1401 to 1750 ........................
Maximum
diameter* of
outlet plenum
(inches)
6
7
8
9
10
11
* If the outlet plenum is rectangular, calculate its equivalent diameter using (4A/P,)
where A is the cross-sectional area and P is
the perimeter of the rectangular plenum, and
compare it to the listed maximum diameter.
2.4.2 Inlet Plenum for the Indoor Unit
Install an inlet plenum when testing a coilonly indoor unit, a ducted blower coil indoor
unit, or a single-package system. See Figures
7b and 7c of ANSI/ASHRAE 37–2009 for
cross-sectional dimensions, the minimum
length of the inlet plenum, and the locations
of the static-pressure taps for ducted blower
coil indoor units and single-package systems.
See Figure 8 of ANSI/ASHRAE 37–2009 for
coil-only indoor units. The inlet plenum duct
size shall equal the size of the inlet opening
of the air-handling (blower coil) unit or
furnace. For a ducted blower coil indoor unit
the set up may omit the inlet plenum if an
inlet airflow prevention device is installed
with a straight internally unobstructed duct
on its outlet end with a minimum length
equal to 1.5 times the square root of the
cross-sectional area of the indoor unit inlet.
See section 2.5.1.2 of this appendix for
requirements for the locations of static
pressure taps built into the inlet airflow
prevention device. For all of these
arrangements, make a manifold that connects
the four static-pressure taps using one of the
three configurations specified in section
2.4.1.d of this appendix. Never use an inlet
plenum when testing non-ducted indoor
units.
2.5 Indoor Coil Air Property Measurements
and Airflow Prevention Devices
Follow instructions for indoor coil air
property measurements as described in
section 2.14 of this appendix, unless
otherwise instructed in this section.
a. Measure the dry-bulb temperature and
water vapor content of the air entering and
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37068
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
leaving the indoor coil. If needed, use an air
sampling device to divert air to a sensor(s)
that measures the water vapor content of the
air. See section 5.3 of ANSI/ASHRAE 41.1–
2013 (incorporated by reference, see § 430.3)
for guidance on constructing an air sampling
device. No part of the air sampling device or
the tubing transferring the sampled air to the
sensor shall be within two inches of the test
chamber floor, and the transfer tubing shall
be insulated. The sampling device may also
be used for measurement of dry bulb
temperature by transferring the sampled air
to a remotely located sensor(s). The air
sampling device and the remotely located
temperature sensor(s) may be used to
determine the entering air dry bulb
temperature during any test. The air
sampling device and the remotely located
sensor(s) may be used to determine the
leaving air dry bulb temperature for all tests
except:
(1) Cyclic tests; and
(2) Frost accumulation tests.
b. Install grids of temperature sensors to
measure dry bulb temperatures of both the
entering and leaving airstreams of the indoor
unit. These grids of dry bulb temperature
sensors may be used to measure average dry
bulb temperature entering and leaving the
indoor unit in all cases (as an alternative to
the dry bulb sensor measuring the sampled
air). The leaving airstream grid is required for
measurement of average dry bulb
temperature leaving the indoor unit for the
two special cases noted above. The grids are
also required to measure the air temperature
distribution of the entering and leaving
airstreams as described in sections 3.1.8 and
3.1.9 of this appendix. Two such grids may
applied as a thermopile, to directly obtain the
average temperature difference rather than
directly measuring both entering and leaving
average temperatures.
c. Use of airflow prevention devices. Use
an inlet and outlet air damper box, or use an
inlet upturned duct and an outlet air damper
box when conducting one or both of the
cyclic tests listed in sections 3.2 and 3.6 of
this appendix on ducted systems. If not
conducting any cyclic tests, an outlet air
damper box is required when testing ducted
and non-ducted heat pumps that cycle off the
indoor blower during defrost cycles and there
is no other means for preventing natural or
forced convection through the indoor unit
when the indoor blower is off. Never use an
inlet damper box or an inlet upturned duct
when testing non-ducted indoor units. An
inlet upturned duct is a length of ductwork
installed upstream from the inlet such that
the indoor duct inlet opening, facing
upwards, is sufficiently high to prevent
natural convection transfer out of the duct. If
an inlet upturned duct is used, install a dry
bulb temperature sensor near the inlet
opening of the indoor duct at a centerline
location not higher than the lowest elevation
of the duct edges at the inlet, and ensure that
any pair of 5-minute averages of the dry bulb
temperature at this location, measured at
least every minute during the compressor
OFF period of the cyclic test, do not differ
by more than 1.0 °F.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
2.5.1 Test Set-Up on the Inlet Side of the
Indoor Coil: For Cases Where the Inlet
Airflow Prevention Device Is Installed
a. Install an airflow prevention device as
specified in section 2.5.1.1 or 2.5.1.2 of this
appendix, whichever applies.
b. For an inlet damper box, locate the grid
of entering air dry-bulb temperature sensors,
if used, and the air sampling device, or the
sensor used to measure the water vapor
content of the inlet air, at a location
immediately upstream of the damper box
inlet. For an inlet upturned duct, locate the
grid of entering air dry-bulb temperature
sensors, if used, and the air sampling device,
or the sensor used to measure the water
vapor content of the inlet air, at a location
at least one foot downstream from the
beginning of the insulated portion of the duct
but before the static pressure measurement.
2.5.1.1 If the Section 2.4.2 Inlet Plenum Is
Installed
Construct the airflow prevention device
having a cross-sectional flow area equal to or
greater than the flow area of the inlet
plenum. Install the airflow prevention device
upstream of the inlet plenum and construct
ductwork connecting it to the inlet plenum.
If needed, use an adaptor plate or a transition
duct section to connect the airflow
prevention device with the inlet plenum.
Insulate the ductwork and inlet plenum with
thermal insulation that has a nominal overall
resistance (R-value) of at least 19 hr • ft2 •
°F/Btu.
2.5.1.2 If the Section 2.4.2 Inlet Plenum Is
Not Installed
Construct the airflow prevention device
having a cross-sectional flow area equal to or
greater than the flow area of the air inlet of
the indoor unit. Install the airflow prevention
device immediately upstream of the inlet of
the indoor unit. If needed, use an adaptor
plate or a short transition duct section to
connect the airflow prevention device with
the unit’s air inlet. Add static pressure taps
at the center of each face of a rectangular
airflow prevention device, or at four evenly
distributed locations along the circumference
of an oval or round airflow prevention
device. Locate the pressure taps at a distance
from the indoor unit inlet equal to 0.5 times
the square root of the cross sectional area of
the indoor unit inlet. This location must be
between the damper and the inlet of the
indoor unit, if a damper is used. Make a
manifold that connects the four static
pressure taps using one of the configurations
shown in Figure 9 of ANSI/ASHRAE 37–
2009 (incorporated by reference, see § 430.3).
Insulate the ductwork with thermal
insulation that has a nominal overall
resistance (R-value) of at least 19 hr • ft2 •
°F/Btu.
2.5.2 Test Set-Up on the Inlet Side of the
Indoor Unit: For Cases Where No Airflow
Prevention Device Is Installed
If using the section 2.4.2 inlet plenum and
a grid of dry bulb temperature sensors, mount
the grid at a location upstream of the static
pressure taps described in section 2.4.2 of
this appendix, preferably at the entrance
plane of the inlet plenum. If the section 2.4.2
inlet plenum is not used (i.e. for non-ducted
PO 00000
Frm 00078
Fmt 4701
Sfmt 4700
units) locate a grid approximately 6 inches
upstream of the indoor unit inlet. In the case
of a system having multiple non-ducted
indoor units, do this for each indoor unit.
Position an air sampling device, or the sensor
used to measure the water vapor content of
the inlet air, immediately upstream of the
(each) entering air dry-bulb temperature
sensor grid. If a grid of sensors is not used,
position the entering air sampling device (or
the sensor used to measure the water vapor
content of the inlet air) as if the grid were
present.
2.5.3 Indoor Coil Static Pressure Difference
Measurement
Fabricate pressure taps meeting all
requirements described in section 6.5.2 of
ANSI/ASHRAE 37–2009 (incorporated by
reference, see § 430.3) and illustrated in
Figure 2A of AMCA 210–2007 (incorporated
by reference, see § 430.3), however, if
adhering strictly to the description in section
6.5.2 of ANSI/ASHRAE 37–2009, the
minimum pressure tap length of 2.5 times the
inner diameter of Figure 2A of AMCA 210–
2007 is waived. Use a differential pressure
measuring instrument that is accurate to
within ±0.01 inches of water and has a
resolution of at least 0.01 inches of water to
measure the static pressure difference
between the indoor coil air inlet and outlet.
Connect one side of the differential pressure
instrument to the manifolded pressure taps
installed in the outlet plenum. Connect the
other side of the instrument to the
manifolded pressure taps located in either
the inlet plenum or incorporated within the
airflow prevention device. For non-ducted
indoor units that are tested with multiple
outlet plenums, measure the static pressure
within each outlet plenum relative to the
surrounding atmosphere.
2.5.4 Test Set-Up on the Outlet Side of the
Indoor Coil
a. Install an interconnecting duct between
the outlet plenum described in section 2.4.1
of this appendix and the airflow measuring
apparatus described below in section 2.6 of
this appendix. The cross-sectional flow area
of the interconnecting duct must be equal to
or greater than the flow area of the outlet
plenum or the common duct used when
testing non-ducted units having multiple
indoor coils. If needed, use adaptor plates or
transition duct sections to allow the
connections. To minimize leakage, tape joints
within the interconnecting duct (and the
outlet plenum). Construct or insulate the
entire flow section with thermal insulation
having a nominal overall resistance (R-value)
of at least 19 hr • ft2 • °F/Btu.
b. Install a grid(s) of dry-bulb temperature
sensors inside the interconnecting duct. Also,
install an air sampling device, or the
sensor(s) used to measure the water vapor
content of the outlet air, inside the
interconnecting duct. Locate the dry-bulb
temperature grid(s) upstream of the air
sampling device (or the in-duct sensor(s)
used to measure the water vapor content of
the outlet air). Turn off the sampler fan motor
during the cyclic tests. Air leaving an indoor
unit that is sampled by an air sampling
device for remote water-vapor-content
measurement must be returned to the
interconnecting duct at a location:
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
(1) Downstream of the air sampling device;
(2) On the same side of the outlet air
damper as the air sampling device; and
(3) Upstream of the section 2.6 airflow
measuring apparatus.
2.5.4.1 Outlet Air Damper Box Placement
and Requirements
If using an outlet air damper box (see
section 2.5 of this appendix), the leakage rate
from the combination of the outlet plenum,
the closed damper, and the duct section that
connects these two components must not
exceed 20 cubic feet per minute when a
negative pressure of 1 inch of water column
is maintained at the plenum’s inlet.
2.5.4.2 Procedures To Minimize
Temperature Maldistribution
Use these procedures if necessary to
correct temperature maldistributions. Install
a mixing device(s) upstream of the outlet air,
dry-bulb temperature grid (but downstream
of the outlet plenum static pressure taps).
Use a perforated screen located between the
mixing device and the dry-bulb temperature
grid, with a maximum open area of 40
percent. One or both items should help to
meet the maximum outlet air temperature
distribution specified in section 3.1.8 of this
appendix. Mixing devices are described in
sections 5.3.2 and 5.3.3 of ANSI/ASHRAE
41.1–2013 and section 5.2.2 of ASHRAE
41.2–1987 (RA 1992) (incorporated by
reference, see § 430.3).
2.5.4.3 Minimizing Air Leakage
For small-duct, high-velocity systems,
install an air damper near the end of the
interconnecting duct, just prior to the
transition to the airflow measuring apparatus
of section 2.6 of this appendix. To minimize
air leakage, adjust this damper such that the
pressure in the receiving chamber of the
airflow measuring apparatus is no more than
0.5 inch of water higher than the surrounding
test room ambient. If applicable, in lieu of
installing a separate damper, use the outlet
air damper box of sections 2.5 and 2.5.4.1 of
this appendix if it allows variable
positioning. Also apply these steps to any
conventional indoor blower unit that creates
a static pressure within the receiving
chamber of the airflow measuring apparatus
that exceeds the test room ambient pressure
by more than 0.5 inches of water column.
2.5.5 Dry Bulb Temperature Measurement
a. Measure dry bulb temperatures as
specified in sections 4, 5.3, 6, and 7 of ANSI/
ASHRAE 41.1–2013 (incorporated by
reference, see § 430.3).
b. Distribute the sensors of a dry-bulb
temperature grid over the entire flow area.
The required minimum is 9 sensors per grid.
2.5.6 Water Vapor Content Measurement
Determine water vapor content by
measuring dry-bulb temperature combined
with the air wet-bulb temperature, dew point
temperature, or relative humidity. If used,
construct and apply wet-bulb temperature
sensors as specified in sections 4, 5, 6, 7.2,
7.3, and 7.4 of ASHRAE 41.6–2014
(incorporated by reference, see § 430.3). The
temperature sensor (wick removed) must be
accurate to within ±0.2 °F. If used, apply
dew point hygrometers as specified in
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
sections 4, 5, 6, 7.1, and 7.4 of ASHRAE
41.6–2014 (incorporated by reference, see
§ 430.3). The dew point hygrometers must be
accurate to within ±0.4 °F when operated at
conditions that result in the evaluation of
dew points above 35 °F. If used, a relative
humidity (RH) meter must be accurate to
within ±0.7% RH. Other means to determine
the psychrometric state of air may be used as
long as the measurement accuracy is
equivalent to or better than the accuracy
achieved from using a wet-bulb temperature
sensor that meets the above specifications.
2.5.7 Air Damper Box Performance
Requirements
If used (see section 2.5 of this appendix),
the air damper box(es) must be capable of
being completely opened or completely
closed within 10 seconds for each action.
2.6 Airflow Measuring Apparatus
a. Fabricate and operate an airflow
measuring apparatus as specified in section
6.2 and 6.3 of ANSI/ASHRAE 37–2009
(incorporated by reference, see § 430.3). Place
the static pressure taps and position the
diffusion baffle (settling means) relative to
the chamber inlet as indicated in Figure 12
of AMCA 210–2007 and/or Figure 14 of
ASHRAE 41.2–1987 (RA 1992) (incorporated
by reference, see § 430.3). When measuring
the static pressure difference across nozzles
and/or velocity pressure at nozzle throats
using electronic pressure transducers and a
data acquisition system, if high frequency
fluctuations cause measurement variations to
exceed the test tolerance limits specified in
section 9.2 and Table 2 of ANSI/ASHRAE
37–2009, dampen the measurement system
such that the time constant associated with
response to a step change in measurement
(time for the response to change 63% of the
way from the initial output to the final
output) is no longer than five seconds.
b. Connect the airflow measuring apparatus
to the interconnecting duct section described
in section 2.5.4 of this appendix. See sections
6.1.1, 6.1.2, and 6.1.4, and Figures 1, 2, and
4 of ANSI/ASHRAE 37–2009; and Figures
D1, D2, and D4 of AHRI 210/240–2008
(incorporated by reference, see § 430.3) for
illustrative examples of how the test
apparatus may be applied within a complete
laboratory set-up. Instead of following one of
these examples, an alternative set-up may be
used to handle the air leaving the airflow
measuring apparatus and to supply properly
conditioned air to the test unit’s inlet. The
alternative set-up, however, must not
interfere with the prescribed means for
measuring airflow rate, inlet and outlet air
temperatures, inlet and outlet water vapor
contents, and external static pressures, nor
create abnormal conditions surrounding the
test unit. (Note: Do not use an enclosure as
described in section 6.1.3 of ANSI/ASHRAE
37–2009 when testing triple-split units.)
2.7 Electrical Voltage Supply
Perform all tests at the voltage specified in
section 6.1.3.2 of AHRI 210/240–2008
(incorporated by reference, see § 430.3) for
‘‘Standard Rating Tests.’’ If either the indoor
or the outdoor unit has a 208V or 200V
nameplate voltage and the other unit has a
230V nameplate rating, select the voltage
PO 00000
Frm 00079
Fmt 4701
Sfmt 4700
37069
supply on the outdoor unit for testing.
Otherwise, supply each unit with its own
nameplate voltage. Measure the supply
voltage at the terminals on the test unit using
a volt meter that provides a reading that is
accurate to within ±1.0 percent of the
measured quantity.
2.8 Electrical Power and Energy
Measurements
a. Use an integrating power (watt-hour)
measuring system to determine the electrical
energy or average electrical power supplied
to all components of the air conditioner or
heat pump (including auxiliary components
such as controls, transformers, crankcase
heater, integral condensate pump on nonducted indoor units, etc.). The watt-hour
measuring system must give readings that are
accurate to within ±0.5 percent. For cyclic
tests, this accuracy is required during both
the ON and OFF cycles. Use either two
different scales on the same watt-hour meter
or two separate watt-hour meters. Activate
the scale or meter having the lower power
rating within 15 seconds after beginning an
OFF cycle. Activate the scale or meter having
the higher power rating within 15 seconds
prior to beginning an ON cycle. For ducted
blower coil systems, the ON cycle lasts from
compressor ON to indoor blower OFF. For
ducted coil-only systems, the ON cycle lasts
from compressor ON to compressor OFF. For
non-ducted units, the ON cycle lasts from
indoor blower ON to indoor blower OFF.
When testing air conditioners and heat
pumps having a variable-speed compressor,
avoid using an induction watt/watt-hour
meter.
b. When performing section 3.5 and/or 3.8
cyclic tests on non-ducted units, provide
instrumentation to determine the average
electrical power consumption of the indoor
blower motor to within ±1.0 percent. If
required according to sections 3.3, 3.4, 3.7,
3.9.1 of this appendix, and/or 3.10 of this
appendix, this same instrumentation
requirement (to determine the average
electrical power consumption of the indoor
blower motor to within ±1.0 percent) applies
when testing air conditioners and heat
pumps having a variable-speed constant-airvolume-rate indoor blower or a variablespeed, variable-air-volume-rate indoor
blower.
2.9 Time Measurements
Make elapsed time measurements using an
instrument that yields readings accurate to
within ±0.2 percent.
2.10 Test Apparatus for the Secondary
Space Conditioning Capacity Measurement
For all tests, use the indoor air enthalpy
method to measure the unit’s capacity. This
method uses the test set-up specified in
sections 2.4 to 2.6 of this appendix. In
addition, for all steady-state tests, conduct a
second, independent measurement of
capacity as described in section 3.1.1 of this
appendix. For split systems, use one of the
following secondary measurement methods:
Outdoor air enthalpy method, compressor
calibration method, or refrigerant enthalpy
method. For single-package units, use either
the outdoor air enthalpy method or the
compressor calibration method as the
secondary measurement.
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37070
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
2.10.1 Outdoor Air Enthalpy Method
a. To make a secondary measurement of
indoor space conditioning capacity using the
outdoor air enthalpy method, do the
following:
(1) Measure the electrical power
consumption of the test unit;
(2) Measure the air-side capacity at the
outdoor coil; and
(3) Apply a heat balance on the refrigerant
cycle.
b. The test apparatus required for the
outdoor air enthalpy method is a subset of
the apparatus used for the indoor air
enthalpy method. Required apparatus
includes the following:
(1) On the outlet side, an outlet plenum
containing static pressure taps (sections 2.4,
2.4.1, and 2.5.3 of this appendix),
(2) An airflow measuring apparatus
(section 2.6 of this appendix),
(3) A duct section that connects these two
components and itself contains the
instrumentation for measuring the dry-bulb
temperature and water vapor content of the
air leaving the outdoor coil (sections 2.5.4,
2.5.5, and 2.5.6 of this appendix), and
(4) On the inlet side, a sampling device and
temperature grid (section 2.11.b of this
appendix).
c. During the preliminary tests described in
sections 3.11.1 and 3.11.1.1 of this appendix,
measure the evaporator and condenser
temperatures or pressures. On both the
outdoor coil and the indoor coil, solder a
thermocouple onto a return bend located at
or near the midpoint of each coil or at points
not affected by vapor superheat or liquid
subcooling. Alternatively, if the test unit is
not sensitive to the refrigerant charge, install
pressure gages to the access valves or to ports
created from tapping into the suction and
discharge lines according to sections 7.4.2
and 8.2.5 of ASHRAE 37–2009. Use this
alternative approach when testing a unit
charged with a zeotropic refrigerant having a
temperature glide in excess of 1 °F at the
specified test conditions.
2.10.2 Compressor Calibration Method
Measure refrigerant pressures and
temperatures to determine the evaporator
superheat and the enthalpy of the refrigerant
that enters and exits the indoor coil.
Determine refrigerant flow rate or, when the
superheat of the refrigerant leaving the
evaporator is less than 5 °F, total capacity
from separate calibration tests conducted
under identical operating conditions. When
using this method, install instrumentation
and measure refrigerant properties according
to section 7.4.2 and 8.2.5 of ANSI/ASHRAE
37–2009 (incorporated by reference, see
§ 430.3). If removing the refrigerant before
applying refrigerant lines and subsequently
recharging, use the steps in 7.4.2 of ANSI/
ASHRAE 37–2009 in addition to the methods
of section 2.2.5 of this appendix to confirm
the refrigerant charge. Use refrigerant
temperature and pressure measuring
instruments that meet the specifications
given in sections 5.1.1 and 5.2 of ANSI/
ASHRAE 37–2009.
2.10.3 Refrigerant Enthalpy Method
For this method, calculate space
conditioning capacity by determining the
VerDate Sep<11>2014
00:24 Jun 08, 2016
Jkt 238001
refrigerant enthalpy change for the indoor
coil and directly measuring the refrigerant
flow rate. Use section 7.5.2 of ANSI/ASHRAE
37–2009 (incorporated by reference, see
§ 430.3) for the requirements for this method,
including the additional instrumentation
requirements, and information on placing the
flow meter and a sight glass. Use refrigerant
temperature, pressure, and flow measuring
instruments that meet the specifications
given in sections 5.1.1, 5.2, and 5.5.1 of
ANSI/ASHRAE 37–2009. Refrigerant flow
measurement device(s), if used, must be
either elevated at least two feet from the test
chamber floor or placed upon insulating
material having a total thermal resistance of
at least R–12 and extending at least one foot
laterally beyond each side of the device(s)’
exposed surfaces.
2.11 Measurement of Test Room Ambient
Conditions
Follow instructions for setting up air
sampling device and aspirating psychrometer
as described in section 2.14 of this appendix,
unless otherwise instructed in this section.
a. If using a test set-up where air is ducted
directly from the conditioning apparatus to
the indoor coil inlet (see Figure 2, Loop AirEnthalpy Test Method Arrangement, of
ANSI/ASHRAE 37–2009 (incorporated by
reference, see § 430.3)), add instrumentation
to permit measurement of the indoor test
room dry-bulb temperature.
b. On the outdoor side, use one of the
following two approaches, except that
approach (1) is required for all evaporativelycooled units and units that transfer
condensate to the outdoor unit for
evaporation using condenser heat.
(1) Use sampling tree air collection on all
air-inlet surfaces of the outdoor unit.
(2) Use sampling tree air collection on one
or more faces of the outdoor unit and
demonstrate air temperature uniformity as
follows. Install a grid of evenly-distributed
thermocouples on each air-permitting face on
the inlet of the outdoor unit. Install the
thermocouples on the air sampling device,
locate them individually or attach them to a
wire structure. If not installed on the air
sampling device, install the thermocouple
grid 6 to 24 inches from the unit. The
thermocouples shall be evenly spaced across
the coil inlet surface and be installed to avoid
sampling of discharge air or blockage of air
recirculation. The grid of thermocouples
must provide at least 16 measuring points per
face or one measurement per square foot of
inlet face area, whichever is less. This grid
must be constructed and used as per section
5.3 of ANSI/ASHRAE 41.1–2013
(incorporated by reference, see § 430.3). The
maximum difference between the readings of
any two pairs of these individual
thermocouples located at any of the faces of
the inlet of the outdoor unit, must not exceed
2.0 °F, otherwise approach (1) must be used.
The air sampling devices shall be located
at the geometric center of each side; the
branches may be oriented either parallel or
perpendicular to the longer edges of the air
inlet area. The air sampling devices in the
outdoor air inlet location shall be sized such
that they cover at least 75% of the face area
of the side of the coil that they are measuring.
PO 00000
Frm 00080
Fmt 4701
Sfmt 4700
Air distribution at the test facility point of
supply to the unit shall be reviewed and may
require remediation prior to the beginning of
testing. Mixing fans can be used to ensure
adequate air distribution in the test room. If
used, mixing fans shall be oriented such that
they are pointed away from the air intake so
that the mixing fan exhaust does not affect
the outdoor coil air volume rate. Particular
attention should be given to prevent the
mixing fans from affecting (enhancing or
limiting) recirculation of condenser fan
exhaust air back through the unit. Any fan
used to enhance test room air mixing shall
not cause air velocities in the vicinity of the
test unit to exceed 500 feet per minute.
The air sampling device may be larger than
the face area of the side being measured,
however care shall be taken to prevent
discharge air from being sampled. If an air
sampling device dimension extends beyond
the inlet area of the unit, holes shall be
blocked in the air sampling device to prevent
sampling of discharge air. Holes can be
blocked to reduce the region of coverage of
the intake holes both in the direction of the
trunk axis or perpendicular to the trunk axis.
For intake hole region reduction in the
direction of the trunk axis, block holes of one
or more adjacent pairs of branches (the
branches of a pair connect opposite each
other at the same trunk location) at either the
outlet end or the closed end of the trunk. For
intake hole region reduction perpendicular to
the trunk axis, block off the same number of
holes on each branch on both sides of the
trunk.
A maximum of four (4) air sampling
devices shall be connected to each aspirating
psychrometer. In order to proportionately
divide the flow stream for multiple air
sampling devices for a given aspirating
psychrometer, the tubing or conduit
conveying sampled air to the psychrometer
shall be of equivalent lengths for each air
sampling device. Preferentially, the air
sampling device should be hard connected to
the aspirating psychrometer, but if space
constraints do not allow this, the assembly
shall have a means of allowing a flexible tube
to connect the air sampling device to the
aspirating psychrometer. The tubing or
conduit shall be insulated and routed to
prevent heat transfer to the air stream. Any
surface of the air conveying tubing in contact
with surrounding air at a different
temperature than the sampled air shall be
insulated with thermal insulation with a
nominal thermal resistance (R-value) of at
least 19 hr · ft2 · °F/Btu. Alternatively the
conduit may have lower thermal resistance if
additional sensor(s) are used to measure dry
bulb temperature at the outlet of each air
sampling device. No part of the air sampling
device or the tubing conducting the sampled
air to the sensors shall be within two inches
of the test chamber floor.
Pairs of measurements (e.g., dry bulb
temperature and wet bulb temperature) used
to determine water vapor content of sampled
air shall be measured in the same location.
2.12 Measurement of Indoor Blower Speed
When required, measure fan speed using a
revolution counter, tachometer, or
stroboscope that gives readings accurate to
within ±1.0 percent.
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
2.13
Measurement of Barometric Pressure
Determine the average barometric pressure
during each test. Use an instrument that
meets the requirements specified in section
5.2 of ANSI/ASHRAE 37–2009 (incorporated
by reference, see § 430.3).
2.14 Air Sampling Device and Aspirating
Psychrometer Requirements
Air temperature measurements shall be
made in accordance with ANSI/ASHRAE
41.1–2013, unless otherwise instructed in
this section.
2.14.1
Air Sampling Device Requirements
The air sampling device is intended to
draw in a sample of the air at the critical
locations of a unit under test. It shall be
constructed of stainless steel, plastic or other
suitable, durable materials. It shall have a
main flow trunk tube with a series of branch
tubes connected to the trunk tube. Holes
shall be on the side of the sampler facing the
upstream direction of the air source. Other
sizes and rectangular shapes can be used, and
shall be scaled accordingly with the
following guidelines:
(1) Minimum hole density of 6 holes per
square foot of area to be sampled
(2) Sampler branch tube pitch (spacing) of
6 ± 3 in
(3) Manifold trunk to branch diameter ratio
having a minimum of 3:1 ratio
(4) Hole pitch (spacing) shall be equally
distributed over the branch (1/2 pitch from
the closed end to the nearest hole)
(5) Maximum individual hole to branch
diameter ratio of 1:2 (1:3 preferred)
The minimum average velocity through the
air sampling device holes shall be 2.5 ft/s as
determined by evaluating the sum of the
open area of the holes as compared to the
flow area in the aspirating psychrometer.
asabaliauskas on DSK3SPTVN1PROD with RULES
2.14.2
Aspirating Psychrometer
The psychrometer consists of a flow
section and a fan to draw air through the flow
section and measures an average value of the
sampled air stream. At a minimum, the flow
section shall have a means for measuring the
dry bulb temperature (typically, a resistance
temperature device (RTD) and a means for
measuring the humidity (RTD with wetted
sock, chilled mirror hygrometer, or relative
humidity sensor). The aspirating
psychrometer shall include a fan that either
can be adjusted manually or automatically to
maintain required velocity across the sensors.
The psychrometer shall be made from
suitable material which may be plastic (such
as polycarbonate), aluminum or other
metallic materials. All psychrometers for a
given system being tested, shall be
constructed of the same material.
Psychrometers shall be designed such that
radiant heat from the motor (for driving the
fan that draws sampled air through the
psychrometer) does not affect sensor
measurements. For aspirating psychrometers,
velocity across the wet bulb sensor shall be
1000 ± 200 ft/min. For all other
psychrometers, velocity shall be as specified
by the sensor manufacturer.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
3. Testing Procedures
3.1 General Requirements
If, during the testing process, an equipment
set-up adjustment is made that would have
altered the performance of the unit during
any already completed test, then repeat all
tests affected by the adjustment. For cyclic
tests, instead of maintaining an air volume
rate, for each airflow nozzle, maintain the
static pressure difference or velocity pressure
during an ON period at the same pressure
difference or velocity pressure as measured
during the steady-state test conducted at the
same test conditions.
Use the testing procedures in this section
to collect the data used for calculating:
(1) Performance metrics for central air
conditioners and heat pumps during the
cooling season;
(2) Performance metrics for heat pumps
during the heating season; and
(3) Power consumption metric(s) for
central air conditioners and heat pumps
during the off mode season(s).
3.1.1 Primary and Secondary Test Methods
For all tests, use the indoor air enthalpy
method test apparatus to determine the unit’s
space conditioning capacity. The procedure
and data collected, however, differ slightly
depending upon whether the test is a steadystate test, a cyclic test, or a frost
accumulation test. The following sections
described these differences. For all steadystate tests (i.e., the A, A2, A1, B, B2, B1, C,
C1, EV, F1, G1, H01, H1, H12, H11, HIN, H3,
H32, and H31 Tests), in addition, use one of
the acceptable secondary methods specified
in section 2.10 of this appendix to determine
indoor space conditioning capacity. Calculate
this secondary check of capacity according to
section 3.11 of this appendix. The two
capacity measurements must agree to within
6 percent to constitute a valid test. For this
capacity comparison, use the indoor air
enthalpy method capacity that is calculated
in section 7.3 of ANSI/ASHRAE 37–2009
(and, if testing a coil-only system, compare
capacities before before making the after-test
fan heat adjustments described in section 3.3,
3.4, 3.7, and 3.10 of this appendix). However,
include the appropriate section 3.3 to 3.5 and
3.7 to 3.10 fan heat adjustments within the
indoor air enthalpy method capacities used
for the section 4 seasonal calculations of this
appendix.
3.1.2 Manufacturer-Provided Equipment
Overrides
Where needed, the manufacturer must
provide a means for overriding the controls
of the test unit so that the compressor(s)
operates at the specified speed or capacity
and the indoor blower operates at the
specified speed or delivers the specified air
volume rate.
3.1.3 Airflow Through the Outdoor Coil
For all tests, meet the requirements given
in section 6.1.3.4 of AHRI 210/240–2008
(incorporated by reference, see § 430.3) when
obtaining the airflow through the outdoor
coil.
3.1.3.1 Double-Ducted
For products intended to be installed with
the outdoor airflow ducted, the unit shall be
PO 00000
Frm 00081
Fmt 4701
Sfmt 4700
37071
installed with outdoor coil ductwork
installed per manufacturer installation
instructions and shall operate between 0.10
and 0.15 in H2O external static pressure.
External static pressure measurements shall
be made in accordance with ANSI/ASHRAE
37–2009 section 6.4 and 6.5.
3.1.4 Airflow Through the Indoor Coil
Airflow setting(s) shall be determined
before testing begins. Unless otherwise
specified within this or its subsections, no
changes shall be made to the airflow
setting(s) after initiation of testing.
3.1.4.1 Cooling Full-Load Air Volume Rate
3.1.4.1.1. Cooling Full-Load Air Volume
Rate for Ducted Units
Identify the certified cooling full-load air
volume rate and certified instructions for
setting fan speed or controls. If there is no
certified Cooling full-load air volume rate,
use a value equal to the certified cooling
capacity of the unit times 400 scfm per
12,000 Btu/h. If there are no instructions for
setting fan speed or controls, use the asshipped settings. Use the following
procedure to confirm and, if necessary, adjust
the Cooling full-load air volume rate and the
fan speed or control settings to meet each test
procedure requirement:
a. For all ducted blower coil systems,
except those having a constant-air-volumerate indoor blower:
Step (1) Operate the unit under conditions
specified for the A (for single-stage units) or
A2 test using the certified fan speed or
controls settings, and adjust the exhaust fan
of the airflow measuring apparatus to achieve
the certified Cooling full-load air volume
rate;
Step (2) Measure the external static
pressure;
Step (3) If this external static pressure is
equal to or greater than the applicable
minimum external static pressure cited in
Table 3, the pressure requirement is satisfied;
proceed to step 7 of this section. If this
external static pressure is not equal to or
greater than the applicable minimum
external static pressure cited in Table 3,
proceed to step 4 of this section;
Step (4) Increase the external static
pressure by adjusting the exhaust fan of the
airflow measuring apparatus until either
(i) The applicable Table 3 minimum is
equaled or
(ii) The measured air volume rate equals 90
percent or less of the Cooling full-load air
volume rate, whichever occurs first;
Step (5) If the conditions of step 4 (i) of this
section occur first, the pressure requirement
is satisfied; proceed to step 7 of this section.
If the conditions of step 4 (ii) of this section
occur first, proceed to step 6 of this section;
Step (6) Make an incremental change to the
setup of the indoor blower (e.g., next highest
fan motor pin setting, next highest fan motor
speed) and repeat the evaluation process
beginning above, at step 1 of this section. If
the indoor blower setup cannot be further
changed, increase the external static pressure
by adjusting the exhaust fan of the airflow
measuring apparatus until the applicable
Table 3 minimum is equaled; proceed to step
7 of this section;
E:\FR\FM\08JNR2.SGM
08JNR2
37072
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Step (7) The airflow constraints have been
satisfied. Use the measured air volume rate
as the Cooling full-load air volume rate. Use
the final fan speed or control settings for all
tests that use the Cooling full-load air volume
rate.
b. For ducted blower coil systems with a
constant-air-volume-rate indoor blower. For
all tests that specify the Cooling full-load air
volume rate, obtain an external static
pressure as close to (but not less than) the
applicable Table 3 value that does not cause
automatic shutdown of the indoor blower or
air volume rate variation QVar, defined as
follows, greater than 10 percent.
where:
Qmax = maximum measured airflow value
Qmin = minimum measured airflow value
QVar = airflow variance, percent
Additional test steps as described in
section 3.3.(e) of this appendix are
required if the measured external static
pressure exceeds the target value by
more than 0.03 inches of water.
c. For coil-only indoor units. For the
A or A2 Test, (exclusively), the pressure
drop across the indoor coil assembly
must not exceed 0.30 inches of water. If
this pressure drop is exceeded, reduce
the air volume rate until the measured
pressure drop equals the specified
maximum. Use this reduced air volume
rate for all tests that require the Cooling
full-load air volume rate.
TABLE 3—MINIMUM EXTERNAL STATIC PRESSURE FOR DUCTED BLOWER COIL SYSTEMS
Minimum external resistance 3
(inches of water)
Rated cooling 1or heating 2 capacity
(Btu/h)
Small-duct,
high-velocity
systems 4 5
Up Thru 28,800 ........................................................................................................................................................
29,000 to 42,500 ......................................................................................................................................................
43,000 and Above ...................................................................................................................................................
1.10
1.15
1.20
All other
systems
0.10
0.15
0.20
1 For air conditioners and air-conditioning heat pumps, the value certified by the manufacturer for the unit’s cooling capacity when operated at
the A or A2 Test conditions.
2 For heating-only heat pumps, the value certified by the manufacturer for the unit’s heating capacity when operated at the H1 or H1 Test con2
ditions.
3 For ducted units tested without an air filter installed, increase the applicable tabular value by 0.08 inches of water.
4 See section 1.2 of this appendix, Definitions, to determine if the equipment qualifies as a small-duct, high-velocity system.
5 If a closed-loop, air-enthalpy test apparatus is used on the indoor side, limit the resistance to airflow on the inlet side of the blower coil indoor
unit to a maximum value of 0.1 inch of water. Impose the balance of the airflow resistance on the outlet side of the indoor blower.
For non-ducted units, the Cooling
full-load air volume rate is the air
volume rate that results during each test
when the unit is operated at an external
static pressure of zero inches of water.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Cooling Minimum Air Volume
Identify the certified cooling
minimum air volume rate and certified
instructions for setting fan speed or
controls. If there is no certified cooling
minimum air volume rate, use the final
indoor blower control settings as
determined when setting the cooling
full-load air volume rate, and readjust
the exhaust fan of the airflow measuring
apparatus if necessary to reset to the
cooling full load air volume obtained in
section 3.1.4.1 of this appendix.
Otherwise, calculate the target external
static pressure and follow instructions a,
b, c, d, or e below. The target external
static pressure, DPst_i, for any test ‘‘i’’
with a specified air volume rate not
equal to the Cooling full-load air volume
rate is determined as follows:
where:
DPst_i = target minimum external static
pressure for test i;
DPst_full = minimum external static pressure
for test A or A2 (Table 3);
Qi = air volume rate for test i; and
Qfull = Cooling full-load air volume rate as
measured after setting and/or adjustment
PO 00000
Frm 00082
Fmt 4701
Sfmt 4700
as described in section 3.1.4.1.1 of this
appendix.
a. For a ducted blower coil system
without a constant-air-volume indoor
blower, adjust for external static
pressure as follows:
Step (1) Operate the unit under
conditions specified for the B1 test
using the certified fan speed or controls
settings, and adjust the exhaust fan of
the airflow measuring apparatus to
achieve the certified cooling minimum
air volume rate;
Step (2) Measure the external static
pressure;
Step (3) If this pressure is equal to or
greater than the minimum external
static pressure computed above, the
pressure requirement is satisfied;
proceed to step 7 of this section. If this
pressure is not equal to or greater than
the minimum external static pressure
computed above, proceed to step 4 of
this section;
Step (4) Increase the external static
pressure by adjusting the exhaust fan of
the airflow measuring apparatus until
either
(i) The pressure is equal to the
minimum external static pressure
computed above or
(ii) The measured air volume rate
equals 90 percent or less of the cooling
minimum air volume rate, whichever
occurs first;
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.008
3.1.4.1.2. Cooling Full-Load Air
Volume Rate for Non-ducted Units
3.1.4.2
Rate
ER08JN16.007
asabaliauskas on DSK3SPTVN1PROD with RULES
d. For ducted systems having multiple
indoor blowers within a single indoor
section, obtain the full-load air volume
rate with all indoor blowers operating
unless prevented by the controls of the
unit. In such cases, turn on the
maximum number of indoor blowers
permitted by the unit’s controls. Where
more than one option exists for meeting
this ‘‘on’’ indoor blower requirement,
which indoor blower(s) are turned on
must match that specified in the
certification report. Conduct section
3.1.4.1.1 setup steps for each indoor
blower separately. If two or more indoor
blowers are connected to a common
duct as per section 2.4.1 of this
appendix, temporarily divert their air
volume to the test room when
confirming or adjusting the setup
configuration of individual indoor
blowers. The allocation of the system’s
full-load air volume rate assigned to
each ‘‘on’’ indoor blower must match
that specified by the manufacturer in
the certification report.
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Step (5) If the conditions of step 4 (i)
of this section occur first, the pressure
requirement is satisfied; proceed to step
7 of this section. If the conditions of
step 4 (ii) of this section occur first,
proceed to step 6 of this section;
Step (6) Make an incremental change
to the setup of the indoor blower (e.g.,
next highest fan motor pin setting, next
highest fan motor speed) and repeat the
evaluation process beginning above, at
step 1 of this section. If the indoor
blower setup cannot be further changed,
increase the external static pressure by
adjusting the exhaust fan of the airflow
measuring apparatus until it equals the
minimum external static pressure
computed above; proceed to step 7 of
this section;
Step (7) The airflow constraints have
been satisfied. Use the measured air
volume rate as the cooling minimum air
volume rate. Use the final fan speed or
control settings for all tests that use the
cooling minimum air volume rate.
b. For ducted units with constant-airvolume indoor blowers, conduct all
tests that specify the cooling minimum
air volume rate—(i.e., the A1, B1, C1, F1,
and G1 Tests)—at an external static
pressure that does not cause an
automatic shutdown of the indoor
blower or air volume rate variation QVar,
defined in section 3.1.4.1.1.b of this
appendix, greater than 10 percent, while
being as close to, but not less than the
target minimum external static pressure.
Additional test steps as described in
section 3.3(e) of this appendix are
required if the measured external static
pressure exceeds the target value by
more than 0.03 inches of water.
c. For ducted two-capacity coil-only
systems, the cooling minimum air
volume rate is the higher of (1) the rate
specified by the installation instructions
included with the unit by the
manufacturer or (2) 75 percent of the
cooling full-load air volume rate. During
the laboratory tests on a coil-only
(fanless) system, obtain this cooling
minimum air volume rate regardless of
the pressure drop across the indoor coil
assembly.
d. For non-ducted units, the cooling
minimum air volume rate is the air
volume rate that results during each test
when the unit operates at an external
static pressure of zero inches of water
and at the indoor blower setting used at
low compressor capacity (two-capacity
system) or minimum compressor speed
(variable-speed system). For units
having a single-speed compressor and a
variable-speed variable-air-volume-rate
indoor blower, use the lowest fan setting
allowed for cooling.
e. For ducted systems having multiple
indoor blowers within a single indoor
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
section, operate the indoor blowers such
that the lowest air volume rate allowed
by the unit’s controls is obtained when
operating the lone single-speed
compressor or when operating at low
compressor capacity while meeting the
requirements of section 2.2.3.b of this
appendix for the minimum number of
blowers that must be turned off. Using
the target external static pressure and
the certified air volume rates, follow the
procedures described in section
3.1.4.2.a of this appendix if the indoor
blowers are not constant-air-volume
indoor blowers or as described in
section 3.1.4.2.b of this appendix if the
indoor blowers are constant-air-volume
indoor blowers. The sum of the
individual ‘‘on’’ indoor blowers’ air
volume rates is the cooling minimum air
volume rate for the system.
3.1.4.3 Cooling Intermediate Air
Volume Rate
Identify the certified cooling
intermediate air volume rate and
certified instructions for setting fan
speed or controls. If there is no certified
cooling intermediate air volume rate,
use the final indoor blower control
settings as determined when setting the
cooling full load air volume rate, and
readjust the exhaust fan of the airflow
measuring apparatus if necessary to
reset to the cooling full load air volume
obtained in section 3.1.4.1 of this
appendix. Otherwise, calculate target
minimum external static pressure as
described in section 3.1.4.2 of this
appendix, and set the air volume rate as
follows.
a. For a ducted blower coil system
without a constant-air-volume indoor
blower, adjust for external static
pressure as described in section
3.1.4.2.a of this appendix for cooling
minimum air volume rate.
b. For a ducted blower coil system
with a constant-air-volume indoor
blower, conduct the EV Test at an
external static pressure that does not
cause an automatic shutdown of the
indoor blower or air volume rate
variation QVar, defined in section
3.1.4.1.1.b of this appendix, greater than
10 percent, while being as close to, but
not less than the target minimum
external static pressure. Additional test
steps as described in section 3.3(e) of
this appendix are required if the
measured external static pressure
exceeds the target value by more than
0.03 inches of water.
c. For non-ducted units, the cooling
intermediate air volume rate is the air
volume rate that results when the unit
operates at an external static pressure of
zero inches of water and at the fan
PO 00000
Frm 00083
Fmt 4701
Sfmt 4700
37073
speed selected by the controls of the
unit for the EV Test conditions.
3.1.4.4
Rate
Heating Full-Load Air Volume
3.1.4.4.1 Ducted Heat Pumps Where
the Heating and Cooling Full-Load Air
Volume Rates Are the Same
a. Use the Cooling full-load air
volume rate as the heating full-load air
volume rate for:
(1) Ducted blower coil system heat
pumps that do not have a constant-airvolume indoor blower, and that operate
at the same airflow-control setting
during both the A (or A2) and the H1 (or
H12) Tests;
(2) Ducted blower coil system heat
pumps with constant-air-flow indoor
blowers that provide the same air flow
for the A (or A2) and the H1 (or H12)
Tests; and
(3) Ducted heat pumps that are tested
with a coil-only indoor unit (except
two-capacity northern heat pumps that
are tested only at low capacity cooling—
see section 3.1.4.4.2 of this appendix).
b. For heat pumps that meet the above
criteria ‘‘1’’ and ‘‘3,’’ no minimum
requirements apply to the measured
external or internal, respectively, static
pressure. Use the final indoor blower
control settings as determined when
setting the Cooling full-load air volume
rate, and readjust the exhaust fan of the
airflow measuring apparatus if
necessary to reset to the cooling fullload air volume obtained in section
3.1.4.1 of this appendix. For heat pumps
that meet the above criterion ‘‘2,’’ test at
an external static pressure that does not
cause an automatic shutdown of the
indoor blower or air volume rate
variation QVar, defined in section
3.1.4.1.1.b of this appendix, greater than
10 percent, while being as close to, but
not less than, the same Table 3
minimum external static pressure as
was specified for the A (or A2) cooling
mode test. Additional test steps as
described in section 3.9.1(c) of this
appendix are required if the measured
external static pressure exceeds the
target value by more than 0.03 inches of
water.
3.1.4.4.2 Ducted Heat Pumps Where
the Heating and Cooling Full-Load Air
Volume Rates Are Different Due to
Changes in Indoor Blower Operation,
i.e. Speed Adjustment by the System
Controls
Identify the certified heating full-load
air volume rate and certified
instructions for setting fan speed or
controls. If there is no certified heating
full-load air volume rate, use the final
indoor blower control settings as
E:\FR\FM\08JNR2.SGM
08JNR2
asabaliauskas on DSK3SPTVN1PROD with RULES
37074
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
determined when setting the cooling
full-load air volume rate, and readjust
the exhaust fan of the airflow measuring
apparatus if necessary to reset to the
cooling full load air volume obtained in
section 3.1.4.1 of this appendix.
Otherwise, calculate target minimum
external static pressure as described in
section 3.1.4.2 of this appendix and set
the air volume rate as follows.
a. For ducted blower coil system heat
pumps that do not have a constant-airvolume indoor blower, adjust for
external static pressure as described in
section 3.1.4.2.a of this appendix for
cooling minimum air volume rate.
b. For ducted heat pumps tested with
constant-air-volume indoor blowers
installed, conduct all tests that specify
the heating full-load air volume rate at
an external static pressure that does not
cause an automatic shutdown of the
indoor blower or air volume rate
variation QVar, defined in section
3.1.4.1.1.b of this appendix, greater than
10 percent, while being as close to, but
not less than the target minimum
external static pressure. Additional test
steps as described in section 3.9.1(c) of
this appendix are required if the
measured external static pressure
exceeds the target value by more than
0.03 inches of water.
c. When testing ducted, two-capacity
blower coil system northern heat pumps
(see section 1.2 of this appendix,
Definitions), use the appropriate
approach of the above two cases. For
coil-only system northern heat pumps,
the heating full-load air volume rate is
the lesser of the rate specified by the
manufacturer in the installation
instructions included with the unit or
133 percent of the cooling full-load air
volume rate. For this latter case, obtain
the heating full-load air volume rate
regardless of the pressure drop across
the indoor coil assembly.
d. For ducted systems having multiple
indoor blowers within a single indoor
section, obtain the heating full-load air
volume rate using the same ‘‘on’’ indoor
blowers as used for the Cooling full-load
air volume rate. Using the target
external static pressure and the certified
air volume rates, follow the procedures
as described in section 3.1.4.4.2.a of this
appendix if the indoor blowers are not
constant-air-volume indoor blowers or
as described in section 3.1.4.4.2.b of this
appendix if the indoor blowers are
constant-air-volume indoor blowers.
The sum of the individual ‘‘on’’ indoor
blowers’ air volume rates is the heating
full load air volume rate for the system.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
3.1.4.4.3 Ducted Heating-Only Heat
Pumps
Identify the certified heating full-load
air volume rate and certified
instructions for setting fan speed or
controls. If there is no certified heating
full-load air volume rate, use a value
equal to the certified heating capacity of
the unit times 400 scfm per 12,000 Btu/
h. If there are no instructions for setting
fan speed or controls, use the asshipped settings.
a. For all ducted heating-only blower
coil system heat pumps, except those
having a constant-air-volume-rate
indoor blower. Conduct the following
steps only during the first test, the H1
or H12 est:
Step (1) Adjust the exhaust fan of the
airflow measuring apparatus to achieve
the certified heating full-load air volume
rate.
Step (2) Measure the external static
pressure.
Step (3) If this pressure is equal to or
greater than the Table 3 minimum
external static pressure that applies
given the heating-only heat pump’s
rated heating capacity, the pressure
requirement is satisfied; proceed to step
7 of this section. If this pressure is not
equal to or greater than the applicable
Table 3 minimum external static
pressure, proceed to step 4 of this
section;
Step (4) Increase the external static
pressure by adjusting the exhaust fan of
the airflow measuring apparatus until
either (i) the pressure is equal to the
applicable Table 3 minimum external
static pressure or (ii) the measured air
volume rate equals 90 percent or less of
the heating full-load air volume rate,
whichever occurs first;
Step (5) If the conditions of step 4 (i)
of this section occur first, the pressure
requirement is satisfied; proceed to step
7 of this section. If the conditions of
step 4 (ii) of this section occur first,
proceed to step 6 of this section;
Step (6) Make an incremental change
to the setup of the indoor blower (e.g.,
next highest fan motor pin setting, next
highest fan motor speed) and repeat the
evaluation process beginning above, at
step 1 of this section. If the indoor
blower setup cannot be further changed,
increase the external static pressure by
adjusting the exhaust fan of the airflow
measuring apparatus until it equals the
applicable Table 3 minimum external
static pressure; proceed to step 7 of this
section;
Step (7) The airflow constraints have
been satisfied. Use the measured air
volume rate as the heating full-load air
volume rate. Use the final fan speed or
control settings for all tests that use the
heating full-load air volume rate.
PO 00000
Frm 00084
Fmt 4701
Sfmt 4700
b. For ducted heating-only blower coil
system heat pumps having a constantair-volume-rate indoor blower. For all
tests that specify the heating full-load
air volume rate, obtain an external static
pressure that does not cause an
automatic shutdown of the indoor
blower or air volume rate variation QVar,
defined in section 3.1.4.1.1.b of this
appendix, greater than 10 percent, while
being as close to, but not less than, the
applicable Table 3 minimum.
Additional test steps as described in
section 3.9.1(c) of this appendix are
required if the measured external static
pressure exceeds the target value by
more than 0.03 inches of water.
c. For ducted heating-only coil-only
system heat pumps in the H1 or H12
Test, (exclusively), the pressure drop
across the indoor coil assembly must
not exceed 0.30 inches of water. If this
pressure drop is exceeded, reduce the
air volume rate until the measured
pressure drop equals the specified
maximum. Use this reduced air volume
rate for all tests that require the heating
full-load air volume rate.
3.1.4.4.4 Non-Ducted Heat Pumps,
Including Non-Ducted Heating-Only
Heat Pumps
For non-ducted heat pumps, the
heating full-load air volume rate is the
air volume rate that results during each
test when the unit operates at an
external static pressure of zero inches of
water.
3.1.4.5
Rate
Heating Minimum Air Volume
3.1.4.5.1. Ducted Heat Pumps Where
the Heating and Cooling Minimum Air
Volume Rates Are the Same
a. Use the cooling minimum air
volume rate as the heating minimum air
volume rate for:
(1) Ducted blower coil system heat
pumps that do not have a constant-airvolume indoor blower, and that operates
at the same airflow-control setting
during both the A1 and the H11 tests;
(2) Ducted blower coil system heat
pumps with constant-air-flow indoor
blowers installed that provide the same
air flow for the A1 and the H11 Tests;
and
(3) Ducted coil-only system heat
pumps.
b. For heat pumps that meet the above
criteria ‘‘1’’ and ‘‘3,’’ no minimum
requirements apply to the measured
external or internal, respectively, static
pressure. Use the final indoor blower
control settings as determined when
setting the cooling minimum air volume
rate, and readjust the exhaust fan of the
airflow measuring apparatus if
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
necessary to reset to the cooling
minimum air volume rate obtained in
section 3.1.4.2 of this appendix. For
heat pumps that meet the above
criterion ‘‘2,’’ test at an external static
pressure that does not cause an
automatic shutdown of the indoor
blower or air volume rate variation QVar,
defined in section 3.1.4.1.1.b of this
appendix, greater than 10 percent, while
being as close to, but not less than, the
same target minimum external static
pressure as was specified for the A1
cooling mode test. Additional test steps
as described in section 3.9.1(c) of this
appendix are required if the measured
external static pressure exceeds the
target value by more than 0.03 inches of
water.
3.1.4.5.2. Ducted Heat Pumps Where
the Heating and Cooling Minimum Air
Volume Rates Are Different Due to
Changes in Indoor Blower Operation,
i.e., Speed Adjustment by the System
Controls
Identify the certified heating
minimum air volume rate and certified
instructions for setting fan speed or
controls. If there is no certified heating
minimum air volume rate, use the final
indoor blower control settings as
determined when setting the cooling
minimum air volume rate, and readjust
the exhaust fan of the airflow measuring
apparatus if necessary to reset to the
cooling minimum air volume obtained
in section 3.1.4.2 of this appendix.
Otherwise, calculate the target
minimum external static pressure as
described in section 3.1.4.2 of this
appendix.
a. For ducted blower coil system heat
pumps that do not have a constant-airvolume indoor blower, adjust for
external static pressure as described in
section 3.1.4.2.a of this appendix for
cooling minimum air volume rate.
b. For ducted heat pumps tested with
constant-air-volume indoor blowers
installed, conduct all tests that specify
the heating minimum air volume rate—
(i.e., the H01, H11, H21, and H31 Tests)—
at an external static pressure that does
not cause an automatic shutdown of the
indoor blower while being as close to,
but not less than the air volume rate
variation QVar, defined in section
3.1.4.1.1.b of this appendix, greater than
10 percent, while being as close to, but
not less than the target minimum
external static pressure. Additional test
steps as described in section 3.9.1.c of
this appendix are required if the
measured external static pressure
exceeds the target value by more than
0.03 inches of water.
c. For ducted two-capacity blower coil
system northern heat pumps, use the
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
appropriate approach of the above two
cases.
d. For ducted two-capacity coil-only
system heat pumps, use the cooling
minimum air volume rate as the heating
minimum air volume rate. For ducted
two-capacity coil-only system northern
heat pumps, use the cooling full-load air
volume rate as the heating minimum air
volume rate. For ducted two-capacity
heating-only coil-only system heat
pumps, the heating minimum air
volume rate is the higher of the rate
specified by the manufacturer in the test
setup instructions included with the
unit or 75 percent of the heating fullload air volume rate. During the
laboratory tests on a coil-only system,
obtain the heating minimum air volume
rate without regard to the pressure drop
across the indoor coil assembly.
e. For non-ducted heat pumps, the
heating minimum air volume rate is the
air volume rate that results during each
test when the unit operates at an
external static pressure of zero inches of
water and at the indoor blower setting
used at low compressor capacity (twocapacity system) or minimum
compressor speed (variable-speed
system). For units having a single-speed
compressor and a variable-speed,
variable-air-volume-rate indoor blower,
use the lowest fan setting allowed for
heating.
f. For ducted systems with multiple
indoor blowers within a single indoor
section, obtain the heating minimum air
volume rate using the same ‘‘on’’ indoor
blowers as used for the cooling
minimum air volume rate. Using the
target external static pressure and the
certified air volume rates, follow the
procedures as described in section
3.1.4.5.2.a of this appendix if the indoor
blowers are not constant-air-volume
indoor blowers or as described in
section 3.1.4.5.2.b of this appendix if
the indoor blowers are constant-airvolume indoor blowers. The sum of the
individual ‘‘on’’ indoor blowers’ air
volume rates is the heating full-load air
volume rate for the system.
3.1.4.6 Heating Intermediate Air
Volume Rate
Identify the certified heating
intermediate air volume rate and
certified instructions for setting fan
speed or controls. If there is no certified
heating intermediate air volume rate,
use the final indoor blower control
settings as determined when setting the
heating full-load air volume rate, and
readjust the exhaust fan of the airflow
measuring apparatus if necessary to
reset to the cooling full load air volume
obtained in section 3.1.4.2 of this
appendix. Calculate the target minimum
PO 00000
Frm 00085
Fmt 4701
Sfmt 4700
37075
external static pressure as described in
section 3.1.4.2 of this appendix.
a. For ducted blower coil system heat
pumps that do not have a constant-airvolume indoor blower, adjust for
external static pressure as described in
section 3.1.4.2.a of this appendix for
cooling minimum air volume rate.
b. For ducted heat pumps tested with
constant-air-volume indoor blowers
installed, conduct the H2V Test at an
external static pressure that does not
cause an automatic shutdown of the
indoor blower or air volume rate
variation QVar, defined in section
3.1.4.1.1.b of this appendix, greater than
10 percent, while being as close to, but
not less than the target minimum
external static pressure. Additional test
steps as described in section 3.9.1(c) of
this appendix are required if the
measured external static pressure
exceeds the target value by more than
0.03 inches of water.
c. For non-ducted heat pumps, the
heating intermediate air volume rate is
the air volume rate that results when the
heat pump operates at an external static
pressure of zero inches of water and at
the fan speed selected by the controls of
the unit for the H2V Test conditions.
3.1.4.7 Heating Nominal Air Volume
Rate
The manufacturer must specify the
heating nominal air volume rate and the
instructions for setting fan speed or
controls. Calculate target minimum
external static pressure as described in
section 3.1.4.2 of this appendix. Make
adjustments as described in section
3.1.4.6 of this appendix for heating
intermediate air volume rate so that the
target minimum external static pressure
is met or exceeded.
3.1.5 Indoor Test Room Requirement
When the Air Surrounding the Indoor
Unit Is Not Supplied From the Same
Source as the Air Entering the Indoor
Unit
If using a test set-up where air is
ducted directly from the air
reconditioning apparatus to the indoor
coil inlet (see Figure 2, Loop AirEnthalpy Test Method Arrangement, of
ANSI/ASHRAE 37–2009 (incorporated
by reference, see § 430.3)), maintain the
dry bulb temperature within the test
room within ±5.0 °F of the applicable
sections 3.2 and 3.6 dry bulb
temperature test condition for the air
entering the indoor unit. Dew point
shall be within 2 °F of the required
inlet conditions.
3.1.6 Air Volume Rate Calculations
For all steady-state tests and for frost
accumulation (H2, H21, H22, H2V) tests,
E:\FR\FM\08JNR2.SGM
08JNR2
37076
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37–2009. When using the outdoor air
enthalpy method, follow sections 7.7.2.1
and 7.7.2.2 of ANSI/ASHRAE 37–2009
to calculate the air volume rate through
the outdoor coil. To express air volume
rates in terms of standard air, use:
Where:
Ô
Vs = air volume rate of standard (dry) air, (ft3/
min)da
Ô
Vmx = air volume rate of the air-water vapor
mixture, (ft3/min)mx
v′n = specific volume of air-water vapor
mixture at the nozzle, ft3 per lbm of the
air-water vapor mixture
Wn = humidity ratio at the nozzle, lbm of
water vapor per lbm of dry air
0.075 = the density associated with standard
(dry) air, (lbm/ft3)
vn = specific volume of the dry air portion
of the mixture evaluated at the dry-bulb
temperature, vapor content, and
barometric pressure existing at the
nozzle, ft3 per lbm of dry air.
NOTE: In the first printing of ANSI/
ASHRAE 37–2009, the second IP equation for
3.1.7 Test Sequence
Manufacturers may optionally operate
the equipment under test for a ‘‘breakin’’ period, not to exceed 20 hours, prior
to conducting the test method specified
in this section. A manufacturer who
elects to use this optional compressor
break-in period in its certification
testing should record this information
(including the duration) in the test data
underlying the certified ratings that are
required to be maintained under 10 CFR
429.71. When testing a ducted unit
(except if a heating-only heat pump),
conduct the A or A2 Test first to
establish the cooling full-load air
volume rate. For ducted heat pumps
where the heating and cooling full-load
air volume rates are different, make the
first heating mode test one that requires
the heating full-load air volume rate. For
ducted heating-only heat pumps,
conduct the H1 or H12 Test first to
establish the heating full-load air
volume rate. When conducting a cyclic
test, always conduct it immediately after
the steady-state test that requires the
same test conditions. For variable-speed
systems, the first test using the cooling
minimum air volume rate should
precede the EV Test, and the first test
using the heating minimum air volume
rate must precede the H2V Test. The test
laboratory makes all other decisions on
the test sequence.
leaving the indoor coil using the grid of
individual sensors described in sections
2.5 and 2.5.4 of this appendix. For the
30-minute data collection interval used
to determine capacity, the maximum
spread among the outlet dry bulb
temperatures from any data sampling
must not exceed 1.5 °F. Install the
mixing devices described in section
2.5.4.2 of this appendix to minimize the
temperature spread.
follows the H12 Test. Set the heat
comfort controller to provide the
maximum supply air temperature. With
the heat pump operating and while
maintaining the heating full-load air
volume rate, measure the temperature of
the air leaving the indoor-side beginning
5 minutes after activating the heat
comfort controller. Sample the outlet
dry-bulb temperature at regular intervals
that span 5 minutes or less. Collect data
for 10 minutes, obtaining at least 3
samples. Calculate the average outlet
temperature over the 10-minute interval,
TCC.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Monitor the temperatures of the air
entering the outdoor coil using the grid
of temperature sensors described in
section 2.11 of this appendix. For the
30-minute data collection interval used
to determine capacity, the maximum
difference between dry bulb
temperatures measured at any of these
locations must not exceed 1.5 °F.
3.1.10 Control of Auxiliary Resistive
Heating Elements
Except as noted, disable heat pump
resistance elements used for heating
indoor air at all times, including during
defrost cycles and if they are normally
regulated by a heat comfort controller.
For heat pumps equipped with a heat
comfort controller, enable the heat
pump resistance elements only during
the below-described, short test. For
single-speed heat pumps covered under
section 3.6.1 of this appendix, the short
test follows the H1 or, if conducted, the
H1C Test. For two-capacity heat pumps
and heat pumps covered under section
3.6.2 of this appendix, the short test
PO 00000
Frm 00086
Fmt 4701
Sfmt 4700
3.2 Cooling Mode Tests for Different
Types of Air Conditioners and Heat
Pumps
3.2.1 Tests for a System Having a
Single-Speed Compressor and Fixed
Cooling Air Volume Rate
This set of tests is for single-speedcompressor units that do not have a
cooling minimum air volume rate or a
cooling intermediate air volume rate
that is different than the cooling full
load air volume rate. Conduct two
steady-state wet coil tests, the A and B
Tests. Use the two optional dry-coil
tests, the steady-state C Test and the
cyclic D Test, to determine the cooling
mode cyclic degradation coefficient,
CDc. A default value for CDc may be used
in lieu of conducting the cyclic test. The
default value of CDc is 0.20. If testing
outdoor units of central air conditioners
or heat pumps that are not sold with
indoor units, assign CDc the default
value of 0.25. Table 4 specifies test
conditions for these four tests.
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.010
3.1.8 Requirement for the Air
Temperature Distribution Leaving the
Indoor Coil
For at least the first cooling mode test
and the first heating mode test, monitor
the temperature distribution of the air
3.1.9 Requirement for the Air
Temperature Distribution Entering the
Outdoor Coil
ER08JN16.009
asabaliauskas on DSK3SPTVN1PROD with RULES
calculate the air volume rate through the
indoor coil as specified in sections
7.7.2.1 and 7.7.2.2 of ANSI/ASHRAE
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37077
TABLE 4—COOLING MODE TEST CONDITIONS FOR UNITS HAVING A SINGLE-SPEED COMPRESSOR AND A FIXED COOLING
AIR VOLUME RATE
Air entering indoor unit
temperature (°F)
Test description
Dry bulb
A Test—required (steady, wet coil) .........................
B Test—required (steady, wet coil) .........................
C Test—optional (steady, dry coil) ..........................
D Test—optional (cyclic, dry coil) ............................
Air entering outdoor unit
temperature (°F)
Wet bulb
80
80
80
80
Dry bulb
67
67
(3)
(3)
Cooling air volume
rate
Wet bulb
95
82
82
82
1 75
1 65
........................
........................
Cooling full-load.2
Cooling full-load.2
Cooling full-load.2
( 4)
1 The
specified test condition only applies if the unit rejects condensate to the outdoor coil.
in section 3.1.4.1 of this appendix.
entering air must have a low enough moisture content so no condensate forms on the indoor coil. (It is recommended that an indoor wetbulb temperature of 57 °F or less be used.)
4 Maintain the airflow nozzles static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the C Test.
2 Defined
3 The
3.2.2 Tests for a Unit Having a SingleSpeed Compressor Where the Indoor
Section Uses a Single Variable-Speed
Variable-Air-Volume Rate Indoor
Blower or mUltiple Indoor Blowers
3.2.2.1 Indoor Blower Capacity
Modulation That Correlates With the
Outdoor Dry Bulb Temperature or
Systems With a Single Indoor cOil but
Multiple Indoor Blowers
the two optional dry-coil tests, the
steady-state C1 test and the cyclic D1
test, to determine the cooling mode
cyclic degradation coefficient, CDc. A
default value for CDc may be used in
lieu of conducting the cyclic test. The
default value of CDc is 0.20.
Conduct four steady-state wet coil
tests: The A2, A1, B2, and B1 tests. Use
3.2.2.2 Indoor Blower Capacity
Modulation Based on Adjusting the
Sensible to Total (S/T) Cooling Capacity
Ratio
The testing requirements are the same
as specified in section 3.2.1 of this
appendix and Table 4. Use a cooling
full-load air volume rate that represents
a normal installation. If performed,
conduct the steady-state C Test and the
cyclic D Test with the unit operating in
the same S/T capacity control mode as
used for the B Test.
TABLE 5—COOLING MODE TEST CONDITIONS FOR UNITS WITH A SINGLE-SPEED COMPRESSOR THAT MEET THE SECTION
3.2.2.1 INDOOR UNIT REQUIREMENTS
Air entering indoor unit
temperature (°F)
Test description
Dry bulb
A2 Test—required (steady, wet coil) ........................
A1 Test—required (steady, wet coil) ........................
B2 Test—required (steady, wet coil) ........................
B1 Test—required (steady, wet coil) ........................
C1 Test4—optional (steady, dry coil) .......................
D1 Test4—optional (cyclic, dry coil) .........................
Air entering outdoor unit
temperature (°F)
Wet bulb
80
80
80
80
80
80
Dry bulb
67
67
67
67
(4)
(4)
Cooling air volume
rate
Wet bulb
95
95
82
82
82
82
1 75
1 75
1 65
1 65
........................
........................
Cooling
Cooling
Cooling
Cooling
Cooling
( 5)
full-load.2
minimum.3
full-load.2
minimum.3
minimum.3
1 The
specified test condition only applies if the unit rejects condensate to the outdoor coil.
in section 3.1.4.1 of this appendix.
in section 3.1.4.2 of this appendix.
4 The entering air must have a low enough moisture content so no condensate forms on the indoor coil. (It is recommended that an indoor wetbulb temperature of 57 °F or less be used.)
5 Maintain the airflow nozzles static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the C1 Test.
2 Defined
3 Defined
asabaliauskas on DSK3SPTVN1PROD with RULES
3.2.3 Tests for a Unit Having a TwoCapacity Compressor (See Section 1.2 of
This Appendix, Definitions)
a. Conduct four steady-state wet coil
tests: the A2, B2, B1, and F1 Tests. Use
the two optional dry-coil tests, the
steady-state C1 Test and the cyclic D1
Test, to determine the cooling-mode
cyclic-degradation coefficient, CDc. A
default value for CDc may be used in
lieu of conducting the cyclic test. The
default value of CDc is 0.20. Table 6
specifies test conditions for these six
tests.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
b. For units having a variable speed
indoor blower that is modulated to
adjust the sensible to total (S/T) cooling
capacity ratio, use cooling full-load and
cooling minimum air volume rates that
represent a normal installation.
Additionally, if conducting the dry-coil
tests, operate the unit in the same S/T
capacity control mode as used for the B1
Test.
c. Test two-capacity, northern heat
pumps (see section 1.2 of this appendix,
Definitions) in the same way as a single
speed heat pump with the unit
operating exclusively at low compressor
PO 00000
Frm 00087
Fmt 4701
Sfmt 4700
capacity (see section 3.2.1 of this
appendix and Table 4).
d. If a two-capacity air conditioner or
heat pump locks out low-capacity
operation at higher outdoor
temperatures, then use the two dry-coil
tests, the steady-state C2 Test and the
cyclic D2 Test, to determine the coolingmode cyclic-degradation coefficient that
only applies to on/off cycling from high
capacity, CDc(k = 2). The default CDc(k
= 2) is the same value as determined or
assigned for the low-capacity cyclicdegradation coefficient, CDc [or
equivalently, CDc(k = 1)].
E:\FR\FM\08JNR2.SGM
08JNR2
37078
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
TABLE 6—COOLING MODE TEST CONDITIONS FOR UNITS HAVING A TWO-CAPACITY COMPRESSOR
Test description
Air entering indoor
unit temperature
(°F)
Dry bulb
Air entering outdoor
unit temperature
(°F)
Wet bulb
Dry bulb
Cooling air
volume rate
Compressor capacity
Wet bulb
80
67
95
1 75
High ...........................
Cooling Full-Load.2
80
67
82
1 65
High ...........................
Cooling Full-Load.2
80
67
82
1 65
Low ............................
Cooling Minimum.3
80
( 4)
82
........................
High ...........................
Cooling Full-Load.2
80
( 4)
82
........................
High ...........................
( 5)
80
( 4)
82
........................
Low ............................
Cooling Minimum.3
80
( 4)
82
........................
Low ............................
( 6)
80
A2 Test—required (steady,
wet coil).
B2 Test—required (steady,
wet coil).
B1 Test—required (steady,
wet coil).
C2 Test—optional (steady,
dry-coil).
D2 Test—optional (cyclic,
dry-coil).
C1 Test—optional (steady,
dry-coil).
D1 Test—optional (cyclic,
dry-coil).
F1 Test—required (steady,
wet coil).
67
67
1 53.5
Low ............................
Cooling Minimum.3
1 The
specified test condition only applies if the unit rejects condensate to the outdoor coil.
in section 3.1.4.1 of this appendix.
in section 3.1.4.2 of this appendix.
4 The entering air must have a low enough moisture content so no condensate forms on the indoor coil. DOE recommends using an indoor air
wet-bulb temperature of 57 °F or less.
5 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the C2 Test.
6 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the C1 Test.
2 Defined
3 Defined
cyclic degradation coefficient, CDc. A
default value for CDc may be used in
lieu of conducting the cyclic test. The
default value of CDc is 0.25. Table 7
specifies test conditions for these seven
tests. The compressor shall operate at
the same cooling full speed, measured
by RPM or power input frequency (Hz),
for both the A2 and B2 tests. The
compressor shall operate at the same
cooling minimum speed, measured by
RPM or power input frequency (Hz), for
the B1, F1, G1, and I1 tests. Determine the
cooling intermediate compressor speed
cited in Table 7 using:
where a tolerance of plus 5 percent or
the next higher inverter frequency step
from that calculated is allowed.
b. For units that modulate the indoor
blower speed to adjust the sensible to
total (S/T) cooling capacity ratio, use
cooling full-load, cooling intermediate,
and cooling minimum air volume rates
that represent a normal installation.
Additionally, if conducting the dry-coil
tests, operate the unit in the same S/T
capacity control mode as used for the F1
Test.
c. For multiple-split air conditioners
and heat pumps (except where noted),
the following procedures supersede the
above requirements: For all Table 7 tests
specified for a minimum compressor
speed, at least one indoor unit must be
turned off. The manufacturer shall
designate the particular indoor unit(s)
that is turned off. The manufacturer
must also specify the compressor speed
used for the Table 7 EV Test, a coolingmode intermediate compressor speed
that falls within 1⁄4 and 3⁄4 of the
difference between the full and
minimum cooling-mode speeds. The
manufacturer should prescribe an
intermediate speed that is expected to
yield the highest EER for the given EV
Test conditions and bracketed
compressor speed range. The
manufacturer can designate that one or
more indoor units are turned off for the
EV Test.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00088
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.011
a. Conduct five steady-state wet coil
tests: The A2, EV, B2, B1, and F1 Tests.
Use the two optional dry-coil tests, the
steady-state G1 Test and the cyclic I1
Test, to determine the cooling mode
asabaliauskas on DSK3SPTVN1PROD with RULES
3.2.4 Tests for a Unit Having a
Variable-Speed Compressor
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37079
TABLE 7—COOLING MODE TEST CONDITION FOR UNITS HAVING A VARIABLE-SPEED COMPRESSOR
Test description
Air entering indoor
unit temperature
(°F)
Dry bulb
Air entering outdoor
unit temperature
(°F)
Wet bulb
Dry bulb
Compressor
speed
Cooling air
volume rate
Wet bulb
80
67
95
1 75
Cooling Full ...............
Cooling Full-Load.2
80
67
82
1 65
Cooling Full ...............
Cooling Full-Load.2
80
67
87
1 69
Cooling Intermediate
Cooling Intermediate.3
80
67
82
1 65
Cooling Minimum ......
Cooling Minimum.4
80
67
67
1 53.5
Cooling Minimum .......
Cooling Minimum.4
80
( 6)
67
........................
Cooling Minimum ......
Cooling Minimum.4
80
A2 Test—required (steady,
wet coil).
B2 Test—required (steady,
wet coil).
EV Test—required
(steady, wet coil).
B1 Test—required (steady,
wet coil).
F1 Test—required (steady,
wet coil).
G1 Test 5—optional
(steady, dry-coil).
I1 Test 5—optional (cyclic,
dry-coil).
( 6)
67
........................
Cooling Minimum ......
(6)
1 The
specified test condition only applies if the unit rejects condensate to the outdoor coil.
in section 3.1.4.1 of this appendix.
3 Defined in section 3.1.4.3 of this appendix.
4 Defined in section 3.1.4.2 of this appendix.
5 The entering air must have a low enough moisture content so no condensate forms on the indoor coil. DOE recommends using an indoor air
wet bulb temperature of 57 °F or less.
6 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the G1 Test.
2 Defined
3.2.5 Cooling Mode Tests for Northern
Heat Pumps With Triple-Capacity
Compressors
Test triple-capacity, northern heat
pumps for the cooling mode in the same
way as specified in section 3.2.3 of this
appendix for units having a twocapacity compressor.
3.2.6 Tests for an Air Conditioner or
Heat Pump Having a Single Indoor Unit
Having Multiple Indoor Blowers and
Offering Two Stages of Compressor
Modulation
Conduct the cooling mode tests
specified in section 3.2.3 of this
appendix.
asabaliauskas on DSK3SPTVN1PROD with RULES
3.3 Test Procedures for Steady-State
Wet Coil Cooling Mode Tests (the A, A2,
A1, B, B2, B1, EV, and F1 Tests)
a. For the pretest interval, operate the
test room reconditioning apparatus and
the unit to be tested until maintaining
equilibrium conditions for at least 30
minutes at the specified section 3.2 test
conditions. Use the exhaust fan of the
airflow measuring apparatus and, if
installed, the indoor blower of the test
unit to obtain and then maintain the
indoor air volume rate and/or external
static pressure specified for the
particular test. Continuously record (see
section 1.2 of this appendix,
Definitions):
(1) The dry-bulb temperature of the
air entering the indoor coil,
(2) The water vapor content of the air
entering the indoor coil,
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
(3) The dry-bulb temperature of the
air entering the outdoor coil, and
(4) For the section 2.2.4 of this
appendix cases where its control is
required, the water vapor content of the
air entering the outdoor coil.
Refer to section 3.11 of this appendix
for additional requirements that depend
on the selected secondary test method.
b. After satisfying the pretest
equilibrium requirements, make the
measurements specified in Table 3 of
ANSI/ASHRAE 37–2009 for the indoor
air enthalpy method and the userselected secondary method. Make said
Table 3 measurements at equal intervals
that span 5 minutes or less. Continue
data sampling until reaching a 30minute period (e.g., seven consecutive
5-minute samples) where the test
tolerances specified in Table 8 are
satisfied. For those continuously
recorded parameters, use the entire data
set from the 30-minute interval to
evaluate Table 8 compliance. Determine
the average electrical power
consumption of the air conditioner or
heat pump over the same 30-minute
interval.
c. Calculate indoor-side total cooling
capacity and sensible cooling capacity
as specified in sections 7.3.3.1 and
7.3.3.3 of ANSI/ASHRAE 37–2009
(incorporated by reference, see § 430.3).
To calculate capacity, use the averages
of the measurements (e.g. inlet and
outlet dry bulb and wet bulb
temperatures measured at the
psychrometers) that are continuously
recorded for the same 30-minute
PO 00000
Frm 00089
Fmt 4701
Sfmt 4700
interval used as described above to
evaluate compliance with test
tolerances. Do not adjust the parameters
used in calculating capacity for the
permitted variations in test conditions.
Evaluate air enthalpies based on the
measured barometric pressure. Use the
values of the specific heat of air given
in section 7.3.3.1 of ANSI/ASHRAE 37–
2009 (incorporated by reference, see
§ 430.3) for calculation of the sensible
cooling capacities. Assign the average
total space cooling capacity, average
sensible cooling capacity, and electrical
power consumption over the 30-minute
data collection interval to the variables
˙
˙
˙
Qck(T), Qsck(T) and Eck(T), respectively.
For these three variables, replace the
‘‘T’’ with the nominal outdoor
temperature at which the test was
conducted. The superscript k is used
only when testing multi-capacity units.
Use the superscript k = 2 to denote a test
with the unit operating at high capacity
or full speed, k = 1 to denote low
capacity or minimum speed, and k = v
to denote the intermediate speed.
d. For coil-only system tests, decrease
˙
Qck(T) by
E:\FR\FM\08JNR2.SGM
08JNR2
37080
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Ô
where Vs is the average measured indoor
air volume rate expressed in units of
cubic feet per minute of standard air
(scfm).
TABLE 8—TEST OPERATING AND TEST CONDITION TOLERANCES FOR SECTION 3.3 STEADY-STATE WET COIL COOLING
MODE TESTS AND SECTION 3.4 DRY COIL COOLING MODE TESTS
Test operating
tolerance 1
Indoor dry-bulb, °F:
Entering temperature ........................................................................................................................................
Leaving temperature .........................................................................................................................................
Indoor wet-bulb, °F:
Entering temperature ........................................................................................................................................
Leaving temperature .........................................................................................................................................
Outdoor dry-bulb, °F:
Entering temperature ........................................................................................................................................
Leaving temperature .........................................................................................................................................
Outdoor wet-bulb, °F:
Entering temperature ........................................................................................................................................
Leaving temperature .........................................................................................................................................
External resistance to airflow, inches of water ........................................................................................................
Electrical voltage, % of rdg ......................................................................................................................................
Nozzle pressure drop, % of rdg ..............................................................................................................................
Test condition
tolerance 1
2.0
2.0
0.5
........................
1.0
2 0.3
........................
2 1.0
2.0
3 2.0
1.0
3 1.0
0.12
2.0
8.0
0.5
........................
4 0.3
........................
5 0.02
1.5
........................
1 See
section 1.2 of this appendix, Definitions.
applies during wet coil tests; does not apply during steady-state, dry coil cooling mode tests.
applies when using the outdoor air enthalpy method.
4 Only applies during wet coil cooling mode tests where the unit rejects condensate to the outdoor coil.
5 Only applies when testing non-ducted units.
2 Only
3 Only
(3) After re-establishing steady
readings of the fan motor power and
external static pressure, determine
average values for the indoor blower
˙
power (Efan,2) and the external static
pressure (DP2) by making measurements
over a 5-minute interval.
(4) Approximate the average power
consumption of the indoor blower
motor at DPmin using linear
extrapolation:
(5) Increase the total space cooling
˙
˙
capacity, Qck(T), by the quantity (Efan,1
˙
¥ Efan,min), when expressed on a Btu/h
basis. Decrease the total electrical
˙
power, Eck(T), by the same fan power
difference, now expressed in watts.
dry coil cooling mode tests as specified
in section 3.3 of this appendix for wet
coil tests. Prior to recording data during
the steady-state dry coil test, operate the
unit at least one hour after achieving dry
coil conditions. Drain the drain pan and
plug the drain opening. Thereafter, the
drain pan should remain completely
dry.
b. Denote the resulting total space
cooling capacity and electrical power
˙
˙
derived from the test as Qss,dry and Ess,dry.
With regard to a section 3.3 deviation,
˙
do not adjust Qss,dry for duct losses (i.e.,
do not apply section 7.3.3.3 of ANSI/
ASHRAE 37–2009). In preparing for the
section 3.5 cyclic tests of this appendix,
record the average indoor-side air
Ô
volume rate, V, specific heat of the air,
Cp,a (expressed on dry air basis),
specific volume of the air at the nozzles,
v′n, humidity ratio at the nozzles, Wn,
and either pressure difference or
velocity pressure for the flow nozzles.
3.4 Test Procedures for the SteadyState Dry-Coil Cooling-Mode Tests (the
C, C1, C2, and G1 Tests)
a. Except for the modifications noted
in this section, conduct the steady-state
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00090
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.013
˙
motor (Efan,1) and record the
corresponding external static pressure
(DP1) during or immediately following
the 30-minute interval used for
determining capacity.
(2) After completing the 30-minute
interval and while maintaining the same
test conditions, adjust the exhaust fan of
the airflow measuring apparatus until
the external static pressure increases to
approximately DP1 + (DP1 ¥ DPmin).
ER08JN16.012
asabaliauskas on DSK3SPTVN1PROD with RULES
e. For air conditioners and heat
pumps having a constant-air-volumerate indoor blower, the five additional
steps listed below are required if the
average of the measured external static
pressures exceeds the applicable
sections 3.1.4 minimum (or target)
external static pressure (DPmin) by 0.03
inches of water or more.
(1) Measure the average power
consumption of the indoor blower
asabaliauskas on DSK3SPTVN1PROD with RULES
For units having a variable-speed indoor
blower (that provides either a constant
or variable air volume rate) that will or
may be tested during the cyclic dry coil
cooling mode test with the indoor
blower turned off (see section 3.5 of this
appendix), include the electrical power
used by the indoor blower motor among
the recorded parameters from the 30minute test.
c. If the temperature sensors used to
provide the primary measurement of the
indoor-side dry bulb temperature
difference during the steady-state drycoil test and the subsequent cyclic drycoil test are different, include
measurements of the latter sensors
among the regularly sampled data.
Beginning at the start of the 30-minute
data collection period, measure and
compute the indoor-side air dry-bulb
temperature difference using both sets
of instrumentation, DT (Set SS) and DT
(Set CYC), for each equally spaced data
sample. If using a consistent data
sampling rate that is less than 1 minute,
calculate and record minutely averages
for the two temperature differences. If
using a consistent sampling rate of one
minute or more, calculate and record
the two temperature differences from
each data sample. After having recorded
the seventh (i = 7) set of temperature
differences, calculate the following ratio
using the first seven sets of values:
Each time a subsequent set of
temperature differences is recorded (if
sampling more frequently than every 5
minutes), calculate FCD using the most
recent seven sets of values. Continue
these calculations until the 30-minute
period is completed or until a value for
FCD is calculated that falls outside the
allowable range of 0.94–1.06. If the
latter occurs, immediately suspend the
test and identify the cause for the
disparity in the two temperature
difference measurements. Recalibration
of one or both sets of instrumentation
may be required. If all the values for FCD
are within the allowable range, save the
final value of the ratio from the 30minute test as FCD*. If the temperature
sensors used to provide the primary
measurement of the indoor-side dry
bulb temperature difference during the
steady-state dry-coil test and the
subsequent cyclic dry-coil test are the
same, set FCD* = 1.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
3.5 Test Procedures for the Cyclic DryCoil Cooling-Mode Tests (the D, D1, D2,
and I1 Tests)
After completing the steady-state drycoil test, remove the outdoor air
enthalpy method test apparatus, if
connected, and begin manual OFF/ON
cycling of the unit’s compressor. The
test set-up should otherwise be identical
to the set-up used during the steadystate dry coil test. When testing heat
pumps, leave the reversing valve during
the compressor OFF cycles in the same
position as used for the compressor ON
cycles, unless automatically changed by
the controls of the unit. For units having
a variable-speed indoor blower, the
manufacturer has the option of electing
at the outset whether to conduct the
cyclic test with the indoor blower
enabled or disabled. Always revert to
testing with the indoor blower disabled
if cyclic testing with the fan enabled is
unsuccessful.
a. For all cyclic tests, the measured
capacity must be adjusted for the
thermal mass stored in devices and
connections located between measured
points. Follow the procedure outlined
in section 7.4.3.4.5 of ASHRAE 116–
2010 (incorporated by reference, see
§ 430.3) to ensure any required
measurements are taken.
b. For units having a single-speed or
two-capacity compressor, cycle the
compressor OFF for 24 minutes and
then ON for 6 minutes (Dtcyc,dry = 0.5
hours). For units having a variablespeed compressor, cycle the compressor
OFF for 48 minutes and then ON for 12
minutes (Dtcyc,dry = 1.0 hours). Repeat
the OFF/ON compressor cycling pattern
until the test is completed. Allow the
controls of the unit to regulate cycling
of the outdoor fan. If an upturned duct
is used, measure the dry-bulb
temperature at the inlet of the device at
least once every minute and ensure that
its test operating tolerance is within 1.0
°F for each compressor OFF period.
c. Sections 3.5.1 and 3.5.2 of this
appendix specify airflow requirements
through the indoor coil of ducted and
non-ducted indoor units, respectively.
In all cases, use the exhaust fan of the
airflow measuring apparatus (covered
under section 2.6 of this appendix)
along with the indoor blower of the
unit, if installed and operating, to
approximate a step response in the
indoor coil airflow. Regulate the exhaust
fan to quickly obtain and then maintain
the flow nozzle static pressure
difference or velocity pressure at the
same value as was measured during the
steady-state dry coil test. The pressure
difference or velocity pressure should
be within 2 percent of the value from
PO 00000
Frm 00091
Fmt 4701
Sfmt 4700
37081
the steady-state dry coil test within 15
seconds after airflow initiation. For
units having a variable-speed indoor
blower that ramps when cycling on and/
or off, use the exhaust fan of the airflow
measuring apparatus to impose a step
response that begins at the initiation of
ramp up and ends at the termination of
ramp down.
d. For units having a variable-speed
indoor blower, conduct the cyclic dry
coil test using the pull-thru approach
described below if any of the following
occur when testing with the fan
operating:
(1) The test unit automatically cycles
off;
(2) Its blower motor reverses; or
(3) The unit operates for more than 30
seconds at an external static pressure
that is 0.1 inches of water or more
higher than the value measured during
the prior steady-state test.
For the pull-thru approach, disable
the indoor blower and use the exhaust
fan of the airflow measuring apparatus
to generate the specified flow nozzles
static pressure difference or velocity
pressure. If the exhaust fan cannot
deliver the required pressure difference
because of resistance created by the
unpowered indoor blower, temporarily
remove the indoor blower.
e. Conduct three complete compressor
OFF/ON cycles with the test tolerances
given in Table 9 satisfied. Calculate the
degradation coefficient CD for each
complete cycle. If all three CD values are
within 0.02 of the average CD then
stability has been achieved, and the
highest CD value of these three shall be
used. If stability has not been achieved,
conduct additional cycles, up to a
maximum of eight cycles total, until
stability has been achieved between
three consecutive cycles. Once stability
has been achieved, use the highest CD
value of the three consecutive cycles
that establish stability. If stability has
not been achieved after eight cycles, use
the highest CD from cycle one through
cycle eight, or the default CD, whichever
is lower.
f. With regard to the Table 9
parameters, continuously record the
dry-bulb temperature of the air entering
the indoor and outdoor coils during
periods when air flows through the
respective coils. Sample the water vapor
content of the indoor coil inlet air at
least every 2 minutes during periods
when air flows through the coil. Record
external static pressure and the air
volume rate indicator (either nozzle
pressure difference or velocity pressure)
at least every minute during the interval
that air flows through the indoor coil.
(These regular measurements of the
airflow rate indicator are in addition to
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.014
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37082
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
the required measurement at 15 seconds
after flow initiation.) Sample the
electrical voltage at least every 2
minutes beginning 30 seconds after
compressor start-up. Continue until the
compressor, the outdoor fan, and the
indoor blower (if it is installed and
operating) cycle off.
g. For ducted units, continuously
record the dry-bulb temperature of the
air entering (as noted above) and leaving
the indoor coil. Or if using a thermopile,
continuously record the difference
between these two temperatures during
the interval that air flows through the
indoor coil. For non-ducted units, make
the same dry-bulb temperature
measurements beginning when the
compressor cycles on and ending when
indoor coil airflow ceases.
h. Integrate the electrical power over
complete cycles of length Dtcyc,dry. For
ducted blower coil systems tested with
the unit’s indoor blower operating for
the cycling test, integrate electrical
power from indoor blower OFF to
indoor blower OFF. For all other ducted
units and for non-ducted units, integrate
electrical power from compressor OFF
to compressor OFF. (Some cyclic tests
will use the same data collection
intervals to determine the electrical
energy and the total space cooling. For
other units, terminate data collection
used to determine the electrical energy
before terminating data collection used
to determine total space cooling.)
TABLE 9—TEST OPERATING AND TEST CONDITION TOLERANCES FOR CYCLIC DRY COIL COOLING MODE TESTS
Test operating
tolerance 1
Indoor entering dry-bulb temperature,2 °F ..............................................................................................................
Indoor entering wet-bulb temperature, °F ...............................................................................................................
Outdoor entering dry-bulb temperature,2 °F ............................................................................................................
External resistance to airflow,2 inches of water ......................................................................................................
Airflow nozzle pressure difference or velocity pressure,2 % of reading .................................................................
Electrical voltage 5, % of rdg. ..................................................................................................................................
Test condition
tolerance 1
2.0
........................
2.0
0.12
8.0
2.0
0.5
(3)
0.5
........................
4 2.0
1.5
1See
section 1.2 of this appendix, Definitions.
during the interval that air flows through the indoor (outdoor) coil except for the first 30 seconds after flow initiation. For units having a
variable-speed indoor blower that ramps, the tolerances listed for the external resistance to airflow apply from 30 seconds after achieving full
speed until ramp down begins.
3Shall at no time exceed a wet-bulb temperature that results in condensate forming on the indoor coil.
4The test condition shall be the average nozzle pressure difference or velocity pressure measured during the steady-state dry coil test.
5Applies during the interval when at least one of the following—the compressor, the outdoor fan, or, if applicable, the indoor blower—are operating except for the first 30 seconds after compressor start-up.
2Applies
measured electrical energy consumption
as ecyc,dry and express it in units of watt-
hours. Calculate the total space cooling
delivered, qcyc,dry, in units of Btu using,
Where,
Ô
V, Cp,a, v′n (or vn), Wn, and FCD* are the
values recorded during the section 3.4
dry coil steady-state test and
Tal(t) = dry bulb temperature of the air
entering the indoor coil at time t, °F.
Ta2(t) = dry bulb temperature of the air
leaving the indoor coil at time t, °F.
t1 = for ducted units, the elapsed time when
airflow is initiated through the indoor
coil; for non-ducted units, the elapsed
time when the compressor is cycled on,
hr.
t2 = the elapsed time when indoor coil
airflow ceases, hr.
7.4.3.4.5 of ASHRAE 116–2010
(incorporated by reference, see § 430.3).
blower that has been disabled (and
possibly removed), start and stop the
indoor airflow at the same instances as
if the fan were enabled. For all other
ducted coil-only systems, cycle the
indoor coil airflow in unison with the
cycling of the compressor. If air damper
boxes are used, close them on the inlet
and outlet side during the OFF period.
Airflow through the indoor coil should
stop within 3 seconds after the
automatic controls of the test unit (act
to) de-energize the indoor blower. For
ducted coil-only systems (excluding the
special case where a variable-speed fan
is temporarily removed), increase ecyc,dry
by the quantity,
asabaliauskas on DSK3SPTVN1PROD with RULES
Adjust the total space cooling
delivered, qcyc,dry, according to
calculation method outlined in section
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
3.5.1 Procedures When Testing Ducted
Systems
The automatic controls that are
normally installed with the test unit
must govern the OFF/ON cycling of the
air moving equipment on the indoor
side (exhaust fan of the airflow
measuring apparatus and, if installed,
the indoor blower of the test unit). For
example, for ducted coil-only systems
rated based on using a fan time delay
relay, control the indoor coil airflow
according to the rated ON and/or OFF
delays provided by the relay. For ducted
units having a variable-speed indoor
PO 00000
Frm 00092
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.015
If the Table 9 tolerances are satisfied
over the complete cycle, record the
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
3.5.2 Procedures When Testing NonDucted Indoor Units
Round the calculated value for CDc to
the nearest 0.01. If CDc is negative, then
set it equal to zero.
3.6 Heating Mode Tests for Different
Types of Heat Pumps, Including
Heating-Only Heat Pumps
3.6.1 Tests for a Heat Pump Having a
Single-Speed Compressor and Fixed
Heating Air Volume Rate
This set of tests is for single-speedcompressor heat pumps that do not have
a heating minimum air volume rate or
a heating intermediate air volume rate
that is different than the heating full
load air volume rate. Conduct the
optional high temperature cyclic (H1C)
test to determine the heating mode
cyclic-degradation coefficient, CDh. A
default value for CDh may be used in
lieu of conducting the cyclic test. The
default value of CDh is 0.25. Test
conditions for the four tests are
specified in Table 10.
where:
ER08JN16.017
Do not use airflow prevention devices
when conducting cyclic tests on non-
the cooling load factor dimensionless
ER08JN16.020
Use the two dry-coil tests to
determine the cooling-mode cyclicdegradation coefficient, CDc. Append
‘‘(k = 2)’’ to the coefficient if it
corresponds to a two-capacity unit
cycling at high capacity. The default
value for two-capacity units cycling at
high capacity, however, is the lowcapacity coefficient, i.e., CDc(k = 2) =
CDc. Evaluate CDc using the above
results and those from the section 3.4
dry-coil steady-state test.
the average energy efficiency ratio
during the steady-state dry coil cooling
mode test, Btu/W·h
ER08JN16.019
3.5.3 Cooling-Mode CyclicDegradation Coefficient Calculation
the average energy efficiency ratio
during the cyclic dry coil cooling mode
test, Btu/W·h
ER08JN16.018
ducted indoor units. Until the last OFF/
ON compressor cycle, airflow through
the indoor coil must cycle off and on in
unison with the compressor. For the last
OFF/ON compressor cycle—the one
used to determine ecyc,dry and qcyc,dry—
use the exhaust fan of the airflow
measuring apparatus and the indoor
blower of the test unit to have indoor
airflow start 3 minutes prior to
compressor cut-on and end three
minutes after compressor cutoff.
Subtract the electrical energy used by
the indoor blower during the 3 minutes
prior to compressor cut-on from the
integrated electrical energy, ecyc,dry. Add
the electrical energy used by the indoor
blower during the 3 minutes after
compressor cutoff to the integrated
cooling capacity, qcyc,dry. For the case
where the non-ducted indoor unit uses
a variable-speed indoor blower which is
disabled during the cyclic test, correct
ecyc,dry and qcyc,dry using the same
approach as prescribed in section 3.5.1
of this appendix for ducted units having
a disabled variable-speed indoor blower.
VerDate Sep<11>2014
01:07 Jun 08, 2016
Jkt 238001
PO 00000
Frm 00093
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.016
asabaliauskas on DSK3SPTVN1PROD with RULES
Ô
where Vs is the average indoor air
volume rate from the section 3.4 dry coil
steady-state test and is expressed in
units of cubic feet per minute of
standard air (scfm). For units having a
variable-speed indoor blower that is
disabled during the cyclic test, increase
ecyc,dry and decrease qcyc,dry based on:
a. The product of [t2 ¥ t1] and the
indoor blower power measured during
or following the dry coil steady-state
test; or,
b. The following algorithm if the
indoor blower ramps its speed when
cycling.
(1) Measure the electrical power
consumed by the variable-speed indoor
blower at a minimum of three operating
conditions: At the speed/air volume
rate/external static pressure that was
measured during the steady-state test, at
operating conditions associated with the
midpoint of the ramp-up interval, and at
conditions associated with the midpoint
of the ramp-down interval. For these
measurements, the tolerances on the
airflow volume or the external static
pressure are the same as required for the
section 3.4 steady-state test.
(2) For each case, determine the fan
power from measurements made over a
minimum of 5 minutes.
(3) Approximate the electrical energy
consumption of the indoor blower if it
had operated during the cyclic test
using all three power measurements.
Assume a linear profile during the ramp
intervals. The manufacturer must
provide the durations of the ramp-up
and ramp-down intervals. If the test
setup instructions included with the
unit by the manufacturer specifies a
ramp interval that exceeds 45 seconds,
use a 45-second ramp interval
nonetheless when estimating the fan
energy.
37083
37084
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
TABLE 10—HEATING MODE TEST CONDITIONS FOR UNITS HAVING A SINGLE-SPEED COMPRESSOR AND A FIXED-SPEED
INDOOR BLOWER, A CONSTANT AIR VOLUME RATE INDOOR BLOWER, OR NO INDOOR BLOWER
Air entering indoor unit
temperature
(°F)
Test description
Dry bulb
H1 Test (required, steady) .......................................
H1C Test (optional, cyclic) .......................................
H2 Test (required) ....................................................
H3 Test (required, steady) .......................................
Air entering outdoor unit
temperature
(°F)
Wet bulb
70
70
70
70
Dry bulb
60 (max)
60 (max)
60 (max)
60 (max)
Heating air volume
rate
Wet bulb
47
47
35
17
43
43
33
15
Heating Full-load.1
(2).
Heating Full-load.1
Heating Full-load.1
1 Defined
in section 3.1.4.4 of this appendix.
the airflow nozzles static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the H1 Test.
2 Maintain
3.6.2 Tests for a heat pump having a
single-speed compressor and a single
indoor unit having either (1) a variable
speed, variable-air-rate indoor blower
whose capacity modulation correlates
with outdoor dry bulb temperature or
(2) multiple indoor blowers. Conduct
five tests: Two high temperature tests
(H12 and H11), one frost accumulation
test (H22), and two low temperature
tests (H32 and H31). Conducting an
additional frost accumulation test (H21)
is optional. Conduct the optional high
temperature cyclic (H1C1) test to
determine the heating mode cyclicdegradation coefficient, CDh. A default
value for CDh may be used in lieu of
conducting the cyclic. The default value
of CDh is 0.25. Test conditions for the
seven tests are specified in Table 11. If
the optional H21 test is not performed,
use the following equations to
approximate the capacity and electrical
power of the heat pump at the H21 test
conditions:
˙
and Ehk=2(35) are determined from the
H22 test and evaluated as specified in
section 3.9 of this appendix; and the
˙
˙
quantities Qhk=2(17), Ehk=2(17),
˙
˙
Qhk=1(17), and Ehk=1(17), are determined
from the H32 and H31 tests and
evaluated as specified in section 3.10 of
this appendix.
where:
˙
˙
The quantities Qhk=2(47), Ehk=2(47),
˙
˙
Qhk=1(47), and Ehk=1(47) are determined
from the H12 and H11 tests and
evaluated as specified in section 3.7 of
˙
this appendix; the quantities Qhk=2(35)
TABLE 11—HEATING MODE TEST CONDITIONS FOR UNITS WITH A SINGLE-SPEED COMPRESSOR THAT MEET THE SECTION
3.6.2 INDOOR UNIT REQUIREMENTS
Dry bulb
H12 Test (required, steady) .....................................
H11 Test (required, steady) .....................................
H1C1 Test (optional, cyclic) .....................................
H22 Test (required) ..................................................
H21 Test (optional) ...................................................
H32 Test (required, steady) .....................................
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Wet bulb
70
70
70
70
70
70
Frm 00094
Fmt 4701
Dry bulb
60 (max)
60 (max)
60 (max)
60 (max)
60 (max)
60 (max)
Sfmt 4700
Heating air volume
rate
Wet bulb
47
47
47
35
35
17
E:\FR\FM\08JNR2.SGM
43
43
43
33
33
15
08JNR2
Heating
Heating
(3)
Heating
Heating
Heating
Full-load.1
Minimum.2
Full-load.1
Minimum.2
Full-load.1
ER08JN16.022
asabaliauskas on DSK3SPTVN1PROD with RULES
Test description
Air entering outdoor unit
temperature
(°F)
ER08JN16.021
Air entering indoor unit
temperature
(°F)
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37085
TABLE 11—HEATING MODE TEST CONDITIONS FOR UNITS WITH A SINGLE-SPEED COMPRESSOR THAT MEET THE SECTION
3.6.2 INDOOR UNIT REQUIREMENTS—Continued
Air entering indoor unit
temperature
(°F)
Test description
Dry bulb
H31 Test (required, steady) .....................................
Air entering outdoor unit
temperature
(°F)
Wet bulb
Dry bulb
60 (max)
70
Heating air volume
rate
Wet bulb
17
15
Heating Minimum.2
1 Defined
in section 3.1.4.4 of this appendix.
in section 3.1.4.5 of this appendix.
the airflow nozzles static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the H11 test.
2 Defined
3 Maintain
3.6.3 Tests for a Heat Pump Having a
Two-Capacity Compressor (see Section
1.2 of This Appendix, Definitions),
Including Two-Capacity, Northern Heat
Pumps (see Section 1.2 of This
Appendix, Definitions)
a. Conduct one maximum temperature
test (H01), two high temperature tests
(H12 and H11), one frost accumulation
˙
Determine the quantities Qhk=1 (47)
˙
and Ehk=1 (47) from the H11 test and
evaluate them according to section 3.7
of this appendix. Determine the
˙
˙
quantities Qhk=1 (17) and Ehk=1 (17) from
the H31 test and evaluate them
according to section 3.10 of this
appendix.
test (H22), and one low temperature test
(H32). Conduct an additional frost
accumulation test (H21) and low
temperature test (H31) if both of the
following conditions exist:
(1) Knowledge of the heat pump’s
capacity and electrical power at low
compressor capacity for outdoor
temperatures of 37 °F and less is needed
to complete the section 4.2.3 of this
appendix seasonal performance
calculations; and
(2) The heat pump’s controls allow
low-capacity operation at outdoor
temperatures of 37 °F and less.
If the above two conditions are met,
an alternative to conducting the H21
frost accumulation is to use the
following equations to approximate the
capacity and electrical power:
b. Conduct the optional high
temperature cyclic test (H1C1) to
determine the heating mode cyclicdegradation coefficient, CDh. A default
value for CDh may be used in lieu of
conducting the cyclic. The default value
of CDh is 0.25. If a two-capacity heat
pump locks out low capacity operation
at lower outdoor temperatures, conduct
the high temperature cyclic test (H1C2)
to determine the high-capacity heating
mode cyclic-degradation coefficient,
CDh (k=2). The default CDh (k=2) is the
same value as determined or assigned
for the low-capacity cyclic-degradation
coefficient, CDh [or equivalently, CDh
(k=1)]. Table 12 specifies test conditions
for these nine tests.
TABLE 12—HEATING MODE TEST CONDITIONS FOR UNITS HAVING A TWO-CAPACITY COMPRESSOR
Test description
Air entering indoor unit
temperature (°F)
H01 Test (required,
steady).
H12 Test (required,
steady).
H1C2 Test (optional,7 cyclic).
H11 Test (required) ..........
H1C1 Test (optional, cyclic).
H22 Test (required) ..........
H21 Test 5 6 (required) ......
H32 Test (required,
steady).
H31 Test 5 (required,
steady).
Wet bulb
Dry bulb
Compressor capacity
Heating air volume
rate
Wet bulb
70
60(max)
62
56.5
Low ............................
Heating Minimum.1
70
60(max)
47
43
High ...........................
Heating Full-Load.2
70
60(max)
47
43
High ...........................
( 3)
70
70
60(max)
60(max)
47
47
43
43
Low ............................
Low ............................
Heating Minimum.1
(4)
70
70
70
60(max)
60(max)
60(max)
35
35
17
33
33
15
High ...........................
Low ............................
High ...........................
Heating Full-Load.2
Heating Minimum.1
Heating Full-Load.2
70
60(max)
17
15
Low ............................
Heating Minimum.1
1 Defined
in section 3.1.4.5 of this appendix.
in section 3.1.4.4 of this appendix.
3 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the H12 test.
4 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the H11 test.
2 Defined
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00095
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.023
asabaliauskas on DSK3SPTVN1PROD with RULES
Dry bulb
Air entering outdoor unit
temperature (°F)
37086
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
5 Required only if the heat pump’s performance when operating at low compressor capacity and outdoor temperatures less than 37 °F is needed to complete the section 4.2.3 HSPF calculations.
6 If table note #5 applies, the section 3.6.3 equations for Q k=1 (35) and E k=1 (17) may be used in lieu of conducting the H2 test.
˙h
˙h
1
7 Required only if the heat pump locks out low capacity operation at lower outdoor temperatures.
test (H22). Conduct the optional
maximum temperature cyclic (H0C1)
test to determine the heating mode
cyclic-degradation coefficient, CDh. A
default value for CDh may be used in
lieu of conducting the cyclic. The
default value of CDh is 0.25. Test
conditions for the eight tests are
specified in Table 13. The compressor
shall operate at the same heating full
speed, measured by RPM or power
input frequency (Hz), for the H12, H22,
and H32 tests. The compressor shall
operate at the same heating minimum
speed, measured by RPM or power
input frequency (Hz), for the H01, H0C1,
and H11 tests. Determine the heating
intermediate compressor speed cited in
Table 13 using the heating mode full
and minimum compressors speeds and:
Heating intermediate speed
Where a tolerance of plus 5 percent or
the next higher inverter frequency step
from that calculated is allowed.
If the H22 test is not done, use the
following equations to approximate the
capacity and electrical power at the H22
test conditions:
˙
b. Determine the quantities Qhk=2(47)
˙
and from Ehk=2(47) from the H12 test and
evaluate them according to section 3.7
of this appendix. Determine the
˙
˙
quantities Qhk=2(17) and Ehk=2(17) from
the H32 test and evaluate them
according to section 3.10 of this
appendix. For heat pumps where the
heating mode full compressor speed
exceeds its cooling mode full
compressor speed, conduct the H1N test
if the manufacturer requests it. If the
H1N test is done, operate the heat
pump’s compressor at the same speed as
the speed used for the cooling mode A2
test. Refer to the last sentence of section
4.2 of this appendix to see how the
results of the H1N test may be used in
calculating the heating seasonal
performance factor.
3.6.4 Tests for a Heat Pump Having a
Variable-Speed Compressor
a. Conduct one maximum temperature
test (H01), two high temperature tests
(H12 and H11), one frost accumulation
test (H2V), and one low temperature test
(H32). Conducting one or both of the
following tests is optional: An
additional high temperature test (H1N)
and an additional frost accumulation
TABLE 13—HEATING MODE TEST CONDITIONS FOR UNITS HAVING A VARIABLE-SPEED COMPRESSOR
Test description
Air entering indoor unit
temperature (°F)
Dry bulb
H01 test (required, steady)
H0C1 test (optional, cyclic)
H12 test (required, steady)
H11 test (required, steady)
H1N test (optional, steady)
H22 test (optional) ............
H2V test (required) ...........
H32 test (required, steady)
Wet bulb
Air entering outdoor unit
temperature (°F)
Dry bulb
60(max)
60(max)
60(max)
60(max)
60(max)
60(max)
60(max)
60(max)
70
70
70
70
70
70
70
70
Compressor speed
Heating air volume
rate
Wet bulb
62
62
47
47
47
35
35
17
56.5
56.5
43
43
43
33
33
15
Heating Minimum ......
Heating Minimum ......
Heating Full ...............
Heating Minimum ......
Cooling Full ...............
Heating Full ...............
Heating Intermediate
Heating Full ...............
Heating
( 2)
Heating
Heating
Heating
Heating
Heating
Heating
Minimum.1
Full-Load.3
Minimum.1
Nominal.4
Full-Load.3
Intermediate.5
Full-Load.3
1 Defined
in section 3.1.4.5 of this appendix.
the airflow nozzle(s) static pressure difference or velocity pressure during an ON period at the same pressure or velocity as measured during the H01 test.
3 Defined in section 3.1.4.4 of this appendix.
4 Defined in section 3.1.4.7 of this appendix.
5 Defined in section 3.1.4.6 of this appendix.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
minimum compressor speed, at least
one indoor unit must be turned off. The
manufacturer shall designate the
particular indoor unit(s) that is turned
PO 00000
Frm 00096
Fmt 4701
Sfmt 4700
off. The manufacturer must also specify
the compressor speed used for the Table
13 H2V test, a heating mode
intermediate compressor speed that falls
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.025
c. For multiple-split heat pumps
(only), the following procedures
supersede the above requirements. For
all Table 13 tests specified for a
ER08JN16.024
asabaliauskas on DSK3SPTVN1PROD with RULES
2 Maintain
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
within 1⁄4 and 3⁄4 of the difference
between the full and minimum heating
mode speeds. The manufacturer should
prescribe an intermediate speed that is
expected to yield the highest COP for
the given H2V test conditions and
bracketed compressor speed range. The
manufacturer can designate that one or
more specific indoor units are turned off
for the H2V test.
3.6.5 Additional Test for a Heat Pump
Having a Heat Comfort Controller
Test any heat pump that has a heat
comfort controller (see section 1.2 of
this appendix, Definitions) according to
section 3.6.1, 3.6.2, or 3.6.3, whichever
applies, with the heat comfort controller
disabled. Additionally, conduct the
abbreviated test described in section
3.1.10 of this appendix with the heat
comfort controller active to determine
the system’s maximum supply air
temperature. (Note: Heat pumps having
a variable speed compressor and a heat
comfort controller are not covered in the
test procedure at this time.)
3.6.6 Heating Mode Tests for Northern
Heat Pumps With Triple-Capacity
Compressors
Test triple-capacity, northern heat
pumps for the heating mode as follows:
a. Conduct one maximumtemperature test (H01), two hightemperature tests (H12 and H11), one
frost accumulation test (H22), two lowtemperature tests (H32, H33), and one
37087
minimum-temperature test (H43).
Conduct an additional frost
accumulation test (H21) and lowtemperature test (H31) if both of the
following conditions exist: (1)
Knowledge of the heat pump’s capacity
and electrical power at low compressor
capacity for outdoor temperatures of 37
°F and less is needed to complete the
section 4.2.6 seasonal performance
calculations; and (2) the heat pump’s
controls allow low-capacity operation at
outdoor temperatures of 37 °F and less.
If the above two conditions are met, an
alternative to conducting the H21 frost
accumulation test to determine
˙
˙
Qhk=1(35) and Ehk=1(35) is to use the
following equations to approximate this
capacity and electrical power:
b. Conducting a frost accumulation
test (H23) with the heat pump operating
at its booster capacity is optional. If this
optional test is not conducted,
˙
˙
determine Qhk=3(35) and Ehk=3(35) using
the following equations to approximate
this capacity and electrical power:
˙
Determine the quantities Qhk=2(47)
˙
and Ehk=2(47) from the H12 test and
evaluate them according to section 3.7
of this appendix. Determine the
˙
˙
quantities Qhk=2(35) and Ehk=2(35) from
the H22 test and evaluate them
according to section 3.9.1 of this
appendix. Determine the quantities
˙
˙
Qhk=2(17) and Ehk=2(17) from the H32
˙
test, determine the quantities Qhk=3(17)
˙
and Ehk=3(17) from the H33 test, and
˙
determine the quantities Qhk=3(2) and
˙
Ehk=3(2) from the H43 test. Evaluate all
six quantities according to section 3.10
of this appendix. Use the paired values
˙
˙
of Qhk=3(35) and Ehk=3(35) derived from
conducting the H23 frost accumulation
test and calculated as specified in
section 3.9.1 of this appendix or use the
paired values calculated using the above
default equations, whichever contribute
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00097
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.027
from conducting the H21 frost
accumulation test and evaluated as
specified in section 3.9.1 of this
appendix or use the paired values
calculated using the above default
equations, whichever contribute to a
higher Region IV HSPF based on the
DHRmin.
ER08JN16.026
asabaliauskas on DSK3SPTVN1PROD with RULES
In evaluating the above equations,
˙
determine the quantities Qhk=1(47) from
the H11 test and evaluate them
according to section 3.7 of this
appendix. Determine the quantities
˙
˙
Qhk=1(17) and Ehk=1(17) from the H31 test
and evaluate them according to section
3.10 of this appendix. Use the paired
˙
˙
values of Qhk=1(35) and Ehk=1(35) derived
37088
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
to a higher Region IV HSPF based on the
DHRmin.
c. Conduct the optional hightemperature cyclic test (H1C1) to
determine the heating mode cyclicdegradation coefficient, CDh. A default
value for CDh may be used in lieu of
conducting the cyclic. The default value
of CDh is 0.25. If a triple-capacity heat
pump locks out low capacity operation
at lower outdoor temperatures, conduct
the high-temperature cyclic test (H1C2)
to determine the high-capacity heating
mode cyclic-degradation coefficient,
CDh (k = 2). The default CDh (k = 2) is
the same value as determined or
assigned for the low-capacity cyclicdegradation coefficient, CDh [or
equivalently, CDh (k = 1)]. Finally, if a
triple-capacity heat pump locks out both
low and high capacity operation at the
lowest outdoor temperatures, conduct
the low-temperature cyclic test (H3C3)
to determine the booster-capacity
heating mode cyclic-degradation
coefficient, CDh (k = 3). The default CDh
(k = 3) is the same value as determined
or assigned for the high-capacity cyclicdegradation coefficient, CDh [or
equivalently, CDh (k = 2)]. Table 14
specifies test conditions for all 13 tests.
TABLE 14—HEATING MODE TEST CONDITIONS FOR UNITS WITH A TRIPLE-CAPACITY COMPRESSOR
Test description
Air entering indoor unit
temperature
(°F)
Dry bulb
Wet bulb
Air entering outdoor unit
temperature
(°F)
Dry bulb
Compressor capacity
Heating air volume
rate
Wet bulb
70
60(max)
62
56.5
Low ............................
Heating Minimum.1
70
60(max)
47
43
High ...........................
Heating Full-Load.2
70
60(max)
47
43
High ...........................
(3)
70
70
60(max)
60(max)
47
47
43
43
Low ............................
Low ............................
Heating Minimum.1
(4)
70
60(max)
35
33
Booster ......................
Heating Full-Load.2
70
70
70
60(max)
60(max)
60(max)
35
35
17
33
33
15
High ...........................
Low ............................
Booster ......................
Heating Full-Load.2
Heating Minimum.1
Heating Full-Load.2
70
60(max)
17
15
Booster ......................
( 7)
70
60(max)
17
15
High ...........................
Heating Full-Load.2
70
60(max)
17
15
Low ............................
Heating Minimum.1
70
H01 Test (required,
steady).
H12 Test (required,
steady).
H1C2 Test (optional 8, cyclic).
H11 Test (required) ..........
H1C1 Test (optional, cyclic).
H23 Test (optional,
steady).
H22 Test (required) ..........
H21 Test (required) ..........
H33 Test (required,
steady).
H3C3 Test 5 6 (optional,
cyclic).
H32 Test (required,
steady).
H31 Test 5 (required,
steady).
H43 Test (required,
steady).
60(max)
2
1
Booster ......................
Heating Full-Load.2
1 Defined
in section 3.1.4.5 of this appendix.
in section 3.1.4.4 of this appendix.
the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the H12 test.
4 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the H11 test.
5 Required only if the heat pump’s performance when operating at low compressor capacity and outdoor temperatures less than 37 °F is needed to complete the section 4.2.6 HSPF calculations.
6 If table note 5 applies, the section 3.6.6 equations for Q k=1(35) and E k=1(17) may be used in lieu of conducting the H2 test.
˙h
˙h
1
7 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the H33 test.
8 Required only if the heat pump locks out low capacity operation at lower outdoor temperatures.
2 Defined
3 Maintain
3.6.7 Tests for a Heat Pump Having a
Single Indoor Unit Having Multiple
Indoor Blowers and Offering Two Stages
of Compressor Modulation
asabaliauskas on DSK3SPTVN1PROD with RULES
Conduct the heating mode tests
specified in section 3.6.3 of this
appendix.
3.7 Test Procedures for Steady-State
Maximum Temperature and High
Temperature Heating Mode Tests (the
H01, H1, H12, H11, and H1N Tests)
a. For the pretest interval, operate the
test room reconditioning apparatus and
the heat pump until equilibrium
conditions are maintained for at least 30
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
minutes at the specified section 3.6 test
conditions. Use the exhaust fan of the
airflow measuring apparatus and, if
installed, the indoor blower of the heat
pump to obtain and then maintain the
indoor air volume rate and/or the
external static pressure specified for the
particular test. Continuously record the
dry-bulb temperature of the air entering
the indoor coil, and the dry-bulb
temperature and water vapor content of
the air entering the outdoor coil. Refer
to section 3.11 of this appendix for
additional requirements that depend on
the selected secondary test method.
After satisfying the pretest equilibrium
requirements, make the measurements
PO 00000
Frm 00098
Fmt 4701
Sfmt 4700
specified in Table 3 of ANSI/ASHRAE
37–2009 (incorporated by reference, see
§ 430.3) for the indoor air enthalpy
method and the user-selected secondary
method. Make said Table 3
measurements at equal intervals that
span 5 minutes or less. Continue data
sampling until a 30-minute period (e.g.,
seven consecutive 5-minute samples) is
reached where the test tolerances
specified in Table 15 are satisfied. For
those continuously recorded
parameters, use the entire data set for
the 30-minute interval when evaluating
Table 15 compliance. Determine the
average electrical power consumption of
E:\FR\FM\08JNR2.SGM
08JNR2
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37089
the heat pump over the same 30-minute
interval.
TABLE 15—TEST OPERATING AND TEST CONDITION TOLERANCES FOR SECTION 3.7 AND SECTION 3.10 STEADY-STATE
HEATING MODE TESTS
Test operating
tolerance 1
Indoor dry-bulb, °F:
Entering temperature ........................................................................................................................................
Leaving temperature .........................................................................................................................................
Indoor wet-bulb, °F:
Entering temperature ........................................................................................................................................
Leaving temperature .........................................................................................................................................
Outdoor dry-bulb, °F:
Entering temperature ........................................................................................................................................
Leaving temperature .........................................................................................................................................
Outdoor wet-bulb, °F:
Entering temperature ........................................................................................................................................
Leaving temperature .........................................................................................................................................
External resistance to airflow, inches of water ........................................................................................................
Electrical voltage, % of rdg ......................................................................................................................................
Nozzle pressure drop, % of rdg ..............................................................................................................................
Test condition
tolerance 1
2.0
2.0
0.5
1.0
1.0
2.0
0.5
2 2.0
1.0
0.3
2 1.0
0.12
2.0
8.0
3 0.02
1.5
1 See
section 1.2 of this appendix, Definitions.
applies when the Outdoor Air Enthalpy Method is used.
3 Only applies when testing non-ducted units.
asabaliauskas on DSK3SPTVN1PROD with RULES
b. Calculate indoor-side total heating
capacity as specified in sections 7.3.4.1
and 7.3.4.3 of ANSI/ASHRAE 37–2009
(incorporated by reference, see § 430.3).
To calculate capacity, use the averages
of the measurements (e.g. inlet and
outlet dry bulb temperatures measured
at the psychrometers) that are
continuously recorded for the same 30minute interval used as described above
to evaluate compliance with test
tolerances. Do not adjust the parameters
used in calculating capacity for the
permitted variations in test conditions.
Assign the average space heating
capacity and electrical power over the
30-minute data collection interval to the
˙
˙
variables Qhk and Ehk(T) respectively.
The ‘‘T’’ and superscripted ‘‘k’’ are the
same as described in section 3.3 of this
appendix. Additionally, for the heating
mode, use the superscript to denote
results from the optional H1N test, if
conducted.
c. For coil-only system heat pumps,
˙
increase Qhk(T) by
Ô
where Vs is the average measured indoor
air volume rate expressed in units of
cubic feet per minute of standard air
(scfm). During the 30-minute data
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
collection interval of a high temperature
test, pay attention to preventing a
defrost cycle. Prior to this time, allow
the heat pump to perform a defrost cycle
if automatically initiated by its own
controls. As in all cases, wait for the
heat pump’s defrost controls to
automatically terminate the defrost
cycle. Heat pumps that undergo a
defrost should operate in the heating
mode for at least 10 minutes after
defrost termination prior to beginning
the 30-minute data collection interval.
For some heat pumps, frost may
accumulate on the outdoor coil during
a high temperature test. If the indoor
coil leaving air temperature or the
difference between the leaving and
entering air temperatures decreases by
more than 1.5 °F over the 30-minute
data collection interval, then do not use
the collected data to determine capacity.
Instead, initiate a defrost cycle. Begin
collecting data no sooner than 10
minutes after defrost termination.
Collect 30 minutes of new data during
which the Table 15 test tolerances are
satisfied. In this case, use only the
results from the second 30-minute data
˙
collection interval to evaluate Qhk(47)
˙
and Ehk(47).
d. If conducting the cyclic heating
mode test, which is described in section
3.8 of this appendix, record the average
Ô
indoor-side air volume rate, V, specific
heat of the air, Cp,a (expressed on dry air
basis), specific volume of the air at the
nozzles, vn′ (or vn), humidity ratio at the
nozzles, Wn, and either pressure
difference or velocity pressure for the
flow nozzles. If either or both of the
PO 00000
Frm 00099
Fmt 4701
Sfmt 4700
below criteria apply, determine the
average, steady-state, electrical power
consumption of the indoor blower
˙
motor (Efan,1):
(1) The section 3.8 cyclic test will be
conducted and the heat pump has a
variable-speed indoor blower that is
expected to be disabled during the
cyclic test; or
(2) The heat pump has a (variablespeed) constant-air volume-rate indoor
blower and during the steady-state test
the average external static pressure (DP1)
exceeds the applicable section 3.1.4.4
minimum (or targeted) external static
pressure (DPmin) by 0.03 inches of water
or more.
˙
Determine Efan,1 by making
measurements during the 30-minute
data collection interval, or immediately
following the test and prior to changing
the test conditions. When the above ‘‘2’’
criteria applies, conduct the following
˙
four steps after determining Efan,1 (which
corresponds to DP1):
(i) While maintaining the same test
conditions, adjust the exhaust fan of the
airflow measuring apparatus until the
external static pressure increases to
approximately DP1 + (DP1 ¥ DPmin).
(ii) After re-establishing steady
readings for fan motor power and
external static pressure, determine
average values for the indoor blower
˙
power (Efan,2) and the external static
pressure (DP2) by making measurements
over a 5-minute interval.
(iii) Approximate the average power
consumption of the indoor blower
motor if the 30-minute test had been
conducted at DPmin using linear
extrapolation:
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.028
2 Only
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
3.8 Test Procedures for the Cyclic
Heating Mode Tests (the H0C1, H1C,
H1C1 and H1C2 Tests)
a. Except as noted below, conduct the
cyclic heating mode test as specified in
d. If a heat pump defrost cycle is
manually or automatically initiated
immediately prior to or during the OFF/
ON cycling, operate the heat pump
continuously until 10 minutes after
defrost termination. After that, begin
cycling the heat pump immediately or
delay until the specified test conditions
have been re-established. Pay attention
to preventing defrosts after beginning
the cycling process. For heat pumps that
cycle off the indoor blower during a
defrost cycle, make no effort here to
restrict the air movement through the
indoor coil while the fan is off. Resume
the OFF/ON cycling while conducting a
minimum of two complete compressor
OFF/ON cycles before determining qcyc
and ecyc.
PO 00000
Frm 00100
Fmt 4701
Sfmt 4700
3.8.1 Heating Mode CyclicDegradation Coefficient Calculation
Use the results from the required
cyclic test and the required steady-state
test that were conducted at the same test
conditions to determine the heating
mode cyclic-degradation coefficient
CDh. Add ‘‘(k = 2)’’ to the coefficient if
it corresponds to a two-capacity unit
cycling at high capacity. For the below
calculation of the heating mode cyclic
degradation coefficient, do not include
the duct loss correction from section
7.3.3.3 of ANSI/ASHRAE 37–2009
(incorporated by reference, see § 430.3)
˙
in determining Qhk(Tcyc) (or qcyc). The
default value for two-capacity units
cycling at high capacity, however, is the
low-capacity coefficient, i.e., CDh (k = 2)
= CDh. The tested CDh is calculated as
follows:
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.031
where FCD* is the value recorded during
the section 3.7 steady-state test
conducted at the same test condition.
b. For ducted coil-only system heat
pumps (excluding the special case
where a variable-speed fan is
temporarily removed), increase qcyc by
the amount calculated using Equation
3.5–3. Additionally, increase ecyc by the
amount calculated using Equation 3.5–
2. In making these calculations, Ô the
use
average indoor air volume rate (Vs)
determined from the section 3.7 steadystate heating mode test conducted at the
same test conditions.
c. For non-ducted heat pumps,
subtract the electrical energy used by
the indoor blower during the 3 minutes
after compressor cutoff from the nonducted heat pump’s integrated heating
capacity, qcyc.
Each time a subsequent set of
temperature differences is recorded (if
sampling more frequently than every 5
minutes), calculate FCD using the most
recent seven sets of values. Continue
these calculations until the 30-minute
period is completed or until a value for
FCD is calculated that falls outside the
allowable range of 0.94–1.06. If the
latter occurs, immediately suspend the
test and identify the cause for the
disparity in the two temperature
difference measurements. Recalibration
of one or both sets of instrumentation
may be required. If all the values for FCD
are within the allowable range, save the
final value of the ratio from the 30minute test as FCD*. If the temperature
sensors used to provide the primary
measurement of the indoor-side dry
bulb temperature difference during the
steady-state dry-coil test and the
subsequent cyclic dry-coil test are the
same, set FCD* = 1.
section 3.5 of this appendix. As adapted
to the heating mode, replace section 3.5
references to ‘‘the steady-state dry coil
test’’ with ‘‘the heating mode steadystate test conducted at the same test
conditions as the cyclic heating mode
test.’’ Use the test tolerances in Table 16
rather than Table 9. Record the outdoor
coil entering wet-bulb temperature
according to the requirements given in
section 3.5 of this appendix for the
outdoor coil entering dry-bulb
temperature. Drop the subscript ‘‘dry’’
used in variables cited in section 3.5 of
this appendix when referring to
quantities from the cyclic heating mode
test. The default CD value for heating is
0.25. If available, use electric resistance
heaters (see section 2.1 of this appendix)
to minimize the variation in the inlet air
temperature. Determine the total space
heating delivered during the cyclic
heating test, qcyc, as specified in section
3.5 of this appendix except for making
the following changes:
(1) When evaluating Equation 3.5–1,
Ô
use the values of V, Cp,a,vn′, (or vn), and
Wn that were recorded during the
section 3.7 steady-state test conducted
at the same test conditions.
ER08JN16.030
asabaliauskas on DSK3SPTVN1PROD with RULES
(iv) Decrease the total space heating
˙
˙
capacity, Qhk(T), by the quantity (Efan,1
˙
¥ Efan,min), when expressed on a Btu/h
basis. Decrease the total electrical
˙
power, Ehk(T) by the same fan power
difference, now expressed in watts.
e. If the temperature sensors used to
provide the primary measurement of the
indoor-side dry bulb temperature
difference during the steady-state drycoil test and the subsequent cyclic drycoil test are different, include
measurements of the latter sensors
among the regularly sampled data.
Beginning at the start of the 30-minute
data collection period, measure and
compute the indoor-side air dry-bulb
temperature difference using both sets
of instrumentation, DT (Set SS) and DT
(Set CYC), for each equally spaced data
sample. If using a consistent data
sampling rate that is less than 1 minute,
calculate and record minutely averages
for the two temperature differences. If
using a consistent sampling rate of one
minute or more, calculate and record
the two temperature differences from
each data sample. After having recorded
the seventh (i = 7) set of temperature
differences, calculate the following ratio
using the first seven sets of values:
ER08JN16.029
37090
37091
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
the average coefficient of performance
during the cyclic heating mode test,
dimensionless.
the average coefficient of performance
during the steady-state heating mode
test conducted at the same test
conditions—i.e., same outdoor dry bulb
temperature, Tcyc, and speed/capacity, k, the heating load factor, dimensionless.
if applicable—as specified for the cyclic Tcyc = the nominal outdoor temperature at
heating mode test, dimensionless.
which the cyclic heating mode test is
conducted, 62 or 47 °F.
Dtcyc = the duration of the OFF/ON intervals;
0.5 hours when testing a heat pump
having a single-speed or two-capacity
compressor and 1.0 hour when testing a
heat pump having a variable-speed
compressor.
Round the calculated value for CDh to
the nearest 0.01. If CDh is negative, then
set it equal to zero.
TABLE 16—TEST OPERATING AND TEST CONDITION TOLERANCES FOR CYCLIC HEATING MODE TESTS
Test operating
tolerance 1
Indoor entering dry-bulb temperature,2 °F ..............................................................................................................
Indoor entering wet-bulb temperature,2 °F ..............................................................................................................
Outdoor entering dry-bulb temperature,2 °F ............................................................................................................
Outdoor entering wet-bulb temperature,2 °F ...........................................................................................................
External resistance to air-flow,2 inches of water .....................................................................................................
Airflow nozzle pressure difference or velocity pressure,2% of reading ...................................................................
Electrical voltage,4% of rdg ......................................................................................................................................
Test condition
tolerance 1
2.0
1.0
2.0
2.0
0.12
2.0
8.0
0.5
0.5
1.0
3 2.0
1.5
1 See
section 1.2 of this appendix, Definitions.
during the interval that air flows through the indoor (outdoor) coil except for the first 30 seconds after flow initiation. For units having a
variable-speed indoor blower that ramps, the tolerances listed for the external resistance to airflow shall apply from 30 seconds after achieving
full speed until ramp down begins.
3 The test condition shall be the average nozzle pressure difference or velocity pressure measured during the steady-state test conducted at
the same test conditions.
4 Applies during the interval that at least one of the following—the compressor, the outdoor fan, or, if applicable, the indoor blower—are operating, except for the first 30 seconds after compressor start-up.
VerDate Sep<11>2014
01:07 Jun 08, 2016
Jkt 238001
PO 00000
Frm 00101
Fmt 4701
Sfmt 4700
controls which are likely to cause
defrosts at intervals exceeding one hour,
the preliminary test period must consist
of a heating interval lasting at least one
hour followed by a defrost cycle that is
either manually or automatically
initiated. In all cases, the heat pump’s
own controls must govern when a
defrost cycle terminates.
c. The official test period begins when
the preliminary test period ends, at
defrost termination. The official test
period ends at the termination of the
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.033
a. Confirm that the defrost controls of
the heat pump are set as specified in
section 2.2.1 of this appendix. Operate
the test room reconditioning apparatus
and the heat pump for at least 30
minutes at the specified section 3.6 test
conditions before starting the
‘‘preliminary’’ test period. The
preliminary test period must
immediately precede the ‘‘official’’ test
period, which is the heating and defrost
interval over which data are collected
for evaluating average space heating
capacity and average electrical power
consumption.
b. For heat pumps containing defrost
controls which are likely to cause
defrosts at intervals less than one hour,
the preliminary test period starts at the
termination of an automatic defrost
cycle and ends at the termination of the
next occurring automatic defrost cycle.
For heat pumps containing defrost
ER08JN16.032
asabaliauskas on DSK3SPTVN1PROD with RULES
3.9 Test Procedures for Frost
Accumulation Heating Mode Tests (the
H2, H22, H2V, and H21 Tests)
ER08JN16.034
2 Applies
37092
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
next occurring automatic defrost cycle.
When testing a heat pump that uses a
time-adaptive defrost control system
(see section 1.2 of this appendix,
Definitions), however, manually initiate
the defrost cycle that ends the official
test period at the instant indicated by
instructions provided by the
manufacturer. If the heat pump has not
undergone a defrost after 6 hours,
immediately conclude the test and use
the results from the full 6-hour period
to calculate the average space heating
capacity and average electrical power
consumption.
For heat pumps that turn the indoor
blower off during the defrost cycle, take
steps to cease forced airflow through the
indoor coil and block the outlet duct
whenever the heat pump’s controls
cycle off the indoor blower. If it is
installed, use the outlet damper box
described in section 2.5.4.1 of this
appendix to affect the blocked outlet
duct.
d. Defrost termination occurs when
the controls of the heat pump actuate
the first change in converting from
defrost operation to normal heating
operation. Defrost initiation occurs
when the controls of the heat pump first
alter its normal heating operation in
order to eliminate possible
accumulations of frost on the outdoor
coil.
e. To constitute a valid frost
accumulation test, satisfy the test
tolerances specified in Table 17 during
both the preliminary and official test
periods. As noted in Table 17, test
operating tolerances are specified for
two sub-intervals: (1) When heating,
except for the first 10 minutes after the
termination of a defrost cycle (subinterval H, as described in Table 17) and
(2) when defrosting, plus these same
first 10 minutes after defrost termination
(sub-interval D, as described in Table
17). Evaluate compliance with Table 17
test condition tolerances and the
majority of the test operating tolerances
using the averages from measurements
recorded only during sub-interval H.
Continuously record the dry bulb
temperature of the air entering the
indoor coil, and the dry bulb
temperature and water vapor content of
the air entering the outdoor coil. Sample
the remaining parameters listed in Table
17 at equal intervals that span 5 minutes
or less.
f. For the official test period, collect
and use the following data to calculate
average space heating capacity and
electrical power. During heating and
defrosting intervals when the controls of
the heat pump have the indoor blower
on, continuously record the dry-bulb
temperature of the air entering (as noted
above) and leaving the indoor coil. If
using a thermopile, continuously record
the difference between the leaving and
entering dry-bulb temperatures during
the interval(s) that air flows through the
indoor coil. For coil-only system heat
pumps, determine the corresponding
cumulative time (in hours) of indoor
coil airflow, Dta. Sample measurements
used in calculating the air volume rate
(refer to sections 7.7.2.1 and 7.7.2.2 of
ANSI/ASHRAE 37–2009) at equal
intervals that span 10 minutes or less.
(Note: In the first printing of ANSI/
ASHRAE 37–2009, the second IP
equation for Qmi should read:) Record
the electrical energy consumed,
expressed in watt-hours, from defrost
termination to defrost termination,
eDEFk(35), as well as the corresponding
elapsed time in hours, DtFR.
TABLE 17—TEST OPERATING AND TEST CONDITION TOLERANCES FOR FROST ACCUMULATION HEATING MODE TESTS
Test operating tolerance 1
Sub-interval
Indoor entering dry-bulb temperature, °F ..................................................................
Indoor entering wet-bulb temperature, °F .................................................................
Outdoor entering dry-bulb temperature, °F ...............................................................
Outdoor entering wet-bulb temperature, °F ...............................................................
External resistance to airflow, inches of water ..........................................................
Electrical voltage, % of rdg ........................................................................................
H2
2.0
1.0
2.0
1.5
0.12
2.0
Sub-interval
D3
Test condition
tolerance 1
Sub-interval H 2
4 4.0
0.5
10.0
..............................
..............................
..............................
1.0
0.5
5 0.02
1.5
1 See section 1.2 of this appendix, Definitions.
2 Applies when the heat pump is in the heating mode, except for the first 10 minutes after termination of a defrost cycle.
3 Applies during a defrost cycle and during the first 10 minutes after the termination of a defrost cycle when the heat pump is operating in the
heating mode.
4 For heat pumps that turn off the indoor blower during the defrost cycle, the noted tolerance only applies during the 10 minute interval that follows defrost termination.
5 Only applies when testing non-ducted heat pumps.
Where,
Ô
V = the average indoor air volume rate
measured during sub-interval H, cfm.
Cp,a = 0.24 + 0.444 · Wn, the constant pressure
specific heat of the air-water vapor
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
mixture that flows through the indoor
coil and is expressed on a dry air basis,
Btu/lbmda · °F.
Frm 00102
Fmt 4701
Sfmt 4700
vn′ = specific volume of the air-water vapor
mixture at the nozzle,
ft3/lbmmx.
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.035
asabaliauskas on DSK3SPTVN1PROD with RULES
3.9.1 Average Space Heating Capacity
and Electrical Power Calculations
a. Evaluate average space heating
˙
capacity, Qhk(35), when expressed in
units of Btu per hour, using:
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37093
DtFR = t2 ¥ t1, the elapsed time from defrost
termination to defrost termination, hr.
Tal(t) = dry bulb temperature of the air
entering the indoor coil at elapsed time
t, °F; only recorded when indoor coil
airflow occurs; assigned the value of zero
during periods (if any) where the indoor
blower cycles off.
Ta2(t) = dry bulb temperature of the air
leaving the indoor coil at elapsed time t,
°F; only recorded when indoor coil
airflow occurs; assigned the value of zero
during periods (if any) where the indoor
blower cycles off.
t1 = the elapsed time when the defrost
termination occurs that begins the
official test period, hr.
t2 = the elapsed time when the next
automatically occurring defrost
termination occurs, thus ending the
official test period, hr.
vn = specific volume of the dry air portion
of the mixture evaluated at the dry-bulb
temperature, vapor content, and
barometric pressure existing at the
nozzle, ft3 per lbm of dry air.
To account for the effect of duct losses
between the outlet of the indoor unit
and the section 2.5.4 dry-bulb
˙
temperature grid, adjust Qhk(35) in
accordance with section 7.3.4.3 of
For coil-only system heat pumps,
˙
increase Qhk(35) by,
Ô
where Vs is the average indoor air
volume rate measured during the frost
accumulation heating mode test and is
expressed in units of cubic feet per
minute of standard air (scfm).
c. For heat pumps having a constantair-volume-rate indoor blower, the five
additional steps listed below are
required if the average of the external
static pressures measured during subinterval H exceeds the applicable
section 3.1.4.4, 3.1.4.5, or 3.1.4.6
minimum (or targeted) external static
pressure (DPmin) by 0.03 inches of water
or more:
(1) Measure the average power
consumption of the indoor blower
˙
motor (Efan,1) and record the
corresponding external static pressure
(DP1) during or immediately following
the frost accumulation heating mode
test. Make the measurement at a time
when the heat pump is heating, except
for the first 10 minutes after the
termination of a defrost cycle.
(2) After the frost accumulation
heating mode test is completed and
while maintaining the same test
conditions, adjust the exhaust fan of the
airflow measuring apparatus until the
external static pressure increases to
approximately DP1 + (DP1 ¥ DPmin).
(3) After re-establishing steady
readings for the fan motor power and
external static pressure, determine
average values for the indoor blower
˙
power (Efan,2) and the external static
pressure (DP2) by making measurements
over a 5-minute interval.
(4) Approximate the average power
consumption of the indoor blower
motor had the frost accumulation
heating mode test been conducted at
DPmin using linear extrapolation:
(5) Decrease the total heating capacity,
˙
˙
Qhk(35), by the quantity [(Efan,1 ¥
˙ fan,min)· (Dta/DtFR], when expressed on a
E
Btu/h basis. Decrease the total electrical
power, Ehk(35), by the same quantity,
now expressed in watts.
3.9.2
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00103
Fmt 4701
Sfmt 4700
Demand Defrost Credit
a. Assign the demand defrost credit,
Fdef, that is used in section 4.2 of this
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.037
ER08JN16.038
ER08JN16.039
ANSI/ASHRAE 37–2009 (incorporated
by reference, see § 430.3).
b. Evaluate average electrical power,
˙
Ehk(35), when expressed in units of
watts, using:
ER08JN16.036
asabaliauskas on DSK3SPTVN1PROD with RULES
Wn = humidity ratio of the air-water vapor
mixture at the nozzle, lbm of water vapor
per lbm of dry air.
37094
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
appendix to the value of 1 in all cases
except for heat pumps having a
demand-defrost control system (see
section 1.2 of this appendix,
Definitions). For such qualifying heat
pumps, evaluate Fdef using,
where:
Dtdef = the time between defrost terminations
(in hours) or 1.5, whichever is greater. A
value of 6 must be assigned to Dtdef if
this limit is reached during a frost
accumulation test and the heat pump has
not completed a defrost cycle.
Dtmax = maximum time between defrosts as
allowed by the controls (in hours) or 12,
whichever is less, as provided in the
certification report.
‘‘preliminary’’ test where the outdoor
air-side test apparatus is disconnected.
Conduct a preliminary test prior to the
first section 3.2 of this appendix steadystate cooling mode test and prior to the
first section 3.6 of this appendix steadystate heating mode test. No other
preliminary tests are required so long as
the unit operates the outdoor fan during
all cooling mode steady-state tests at the
same speed and all heating mode
steady-state tests at the same speed. If
using more than one outdoor fan speed
for the cooling mode steady-state tests,
however, conduct a preliminary test
prior to each cooling mode test where a
different fan speed is first used. This
same requirement applies for the
heating mode tests.
consecutive readings taken at one
minute intervals. Make these
consecutive readings after reestablishing equilibrium conditions and
before initiating the official test.
3.11.1.1
a. Continue (preliminary test was
conducted) or begin (no preliminary
test) the official test by making
measurements for both the indoor and
outdoor air enthalpy methods at equal
intervals that span 5 minutes or less.
Discontinue these measurements only
after obtaining a 30-minute period
where the specified test condition and
test operating tolerances are satisfied.
To constitute a valid official test:
(1) Achieve the energy balance
specified in section 3.1.1 of this
appendix; and,
(2) For cases where a preliminary test
is conducted, the capacities determined
using the indoor air enthalpy method
from the official and preliminary test
periods must agree within 2.0 percent.
b. For space cooling tests, calculate
capacity from the outdoor air-enthalpy
measurements as specified in sections
7.3.3.2 and 7.3.3.3 of ANSI/ASHRAE
37–2009 (incorporated by reference, see
§ 430.3). Calculate heating capacity
based on outdoor air-enthalpy
measurements as specified in sections
7.3.4.2 and 7.3.3.4.3 of the same
ASHRAE Standard. Adjust the outdoorside capacity according to section
7.3.3.4 of ANSI/ASHRAE 37–2009 to
account for line losses when testing
split systems. Use the outdoor unit fan
power as measured during the official
test and not the value measured during
the preliminary test, as described in
section 8.6.2 of ANSI/ASHRAE 37–
2009, when calculating the capacity.
3.10 Test Procedures for Steady-State
Low Temperature Heating Mode Tests
(the H3, H32, and H31 tests).
Except for the modifications noted in
this section, conduct the low
temperature heating mode test using the
same approach as specified in section
3.7 of this appendix for the maximum
and high temperature tests. After
satisfying the section 3.7 requirements
for the pretest interval but before
beginning to collect data to determine
Qhk(17) and Ehk(17), conduct a defrost
cycle. This defrost cycle may be
manually or automatically initiated. The
defrost sequence must be terminated by
the action of the heat pump’s defrost
controls. Begin the 30-minute data
collection interval described in section
3.7 of this appendix, from which
Qhk(17) and Ehk(17) are determined, no
sooner than 10 minutes after defrost
termination. Defrosts should be
prevented over the 30-minute data
collection interval.
asabaliauskas on DSK3SPTVN1PROD with RULES
3.11 Additional Requirements for the
Secondary Test Methods
3.11.1 If Using the Outdoor Air
Enthalpy Method as the Secondary Test
Method
During the ‘‘official’’ test, the outdoor
air-side test apparatus described in
section 2.10.1 of this appendix is
connected to the outdoor unit. To help
compensate for any effect that the
addition of this test apparatus may have
on the unit’s performance, conduct a
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Preliminary Test
3.11.1.1.1 If a Preliminary Test
Precedes the Official Test
a. The test conditions for the
preliminary test are the same as
specified for the official test. Connect
the indoor air-side test apparatus to the
indoor coil; disconnect the outdoor airside test apparatus. Allow the test room
reconditioning apparatus and the unit
being tested to operate for at least one
hour. After attaining equilibrium
conditions, measure the following
quantities at equal intervals that span 5
minutes or less:
(1) The section 2.10.1 of this appendix
evaporator and condenser temperatures
or pressures;
(2) Parameters required according to
the indoor air enthalpy method.
Continue these measurements until a
30-minute period (e.g., seven
consecutive 5-minute samples) is
obtained where the Table 8 or Table 15,
whichever applies, test tolerances are
satisfied.
b. After collecting 30 minutes of
steady-state data, reconnect the outdoor
air-side test apparatus to the unit.
Adjust the exhaust fan of the outdoor
airflow measuring apparatus until
averages for the evaporator and
condenser temperatures, or the
saturated temperatures corresponding to
the measured pressures, agree within
±0.5 °F of the averages achieved when
the outdoor air-side test apparatus was
disconnected. Calculate the averages for
the reconnected case using five or more
PO 00000
Frm 00104
Fmt 4701
Sfmt 4700
Connect the outdoor-side test
apparatus to the unit. Adjust the
exhaust fan of the outdoor airflow
measuring apparatus to achieve the
same external static pressure as
measured during the prior preliminary
test conducted with the unit operating
in the same cooling or heating mode at
the same outdoor fan speed.
3.11.1.1
E:\FR\FM\08JNR2.SGM
Official Test
08JNR2
ER08JN16.040
b. For two-capacity heat pumps and
for section 3.6.2 units, evaluate the
above equation using the Dtdef that
applies based on the frost accumulation
test conducted at high capacity and/or
at the heating full-load air volume rate.
For variable-speed heat pumps, evaluate
Dtdef based on the required frost
accumulation test conducted at the
intermediate compressor speed.
3.11.1.1.2 If a Preliminary Test Does
Not Precede the Official Test
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
a. Conduct separate calibration tests
using a calorimeter to determine the
refrigerant flow rate. Or for cases where
the superheat of the refrigerant leaving
the evaporator is less than 5 °F, use the
calorimeter to measure total capacity
rather than refrigerant flow rate.
Conduct these calibration tests at the
same test conditions as specified for the
tests in this appendix. Operate the unit
for at least one hour or until obtaining
equilibrium conditions before collecting
data that will be used in determining
the average refrigerant flow rate or total
capacity. Sample the data at equal
intervals that span 5 minutes or less.
Determine average flow rate or average
capacity from data sampled over a 30minute period where the Table 8
(cooling) or the Table 15 (heating)
tolerances are satisfied. Otherwise,
conduct the calibration tests according
to sections 5, 6, 7, and 8 of ASHRAE
23.1–2010 (incorporated by reference,
see § 430.3); sections 5, 6, 7, 8, 9, and
11 of ASHRAE 41.9–2011 (incorporated
by reference, see § 430.3); and section
7.4 of ANSI/ASHRAE 37–2009
(incorporated by reference, see § 430.3).
b. Calculate space cooling and space
heating capacities using the compressor
calibration method measurements as
specified in section 7.4.5 and 7.4.6
respectively, of ANSI/ASHRAE 37–
2009.
3.11.3 If Using the RefrigerantEnthalpy Method as the Secondary Test
Method
Conduct this secondary method
according to section 7.5 of ANSI/
ASHRAE 37–2009. Calculate space
cooling and heating capacities using the
refrigerant-enthalpy method
measurements as specified in sections
7.5.4 and 7.5.5, respectively, of the same
ASHRAE Standard.
asabaliauskas on DSK3SPTVN1PROD with RULES
3.12 Rounding of Space Conditioning
Capacities for Reporting Purposes
a. When reporting rated capacities,
round them off as specified in § 430.23
(for a single unit) and in 10 CFR 429.16
(for a sample).
b. For the capacities used to perform
the calculations in section 4 of this
appendix, however, round only to the
nearest integer.
3.13 Laboratory Testing To Determine
Off Mode Average Power Ratings
Voltage tolerances: As a percentage of
reading, test operating tolerance shall be
2.0 percent and test condition tolerance
shall be 1.5 percent (see section 1.2 of
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
this appendix for definitions of these
tolerances).
Conduct one of the following tests: If
the central air conditioner or heat pump
lacks a compressor crankcase heater,
perform the test in section 3.13.1 of this
appendix; if the central air conditioner
or heat pump has a compressor
crankcase heater that lacks controls and
is not self-regulating, perform the test in
section 3.13.1 of this appendix; if the
central air conditioner or heat pump has
a crankcase heater with a fixed power
input controlled with a thermostat that
measures ambient temperature and
whose sensing element temperature is
not affected by the heater, perform the
test in section 3.13.1 of this appendix;
if the central air conditioner or heat
pump has a compressor crankcase
heater equipped with self-regulating
control or with controls for which the
sensing element temperature is affected
by the heater, perform the test in section
3.13.2 of this appendix.
3.13.1 This Test Determines the off
Mode Average Power Rating for Central
Air Conditioners and Heat Pumps That
Lack a Compressor Crankcase Heater, or
Have a Compressor Crankcase Heating
System That Can Be Tested Without
Control of Ambient Temperature During
the Test. This Test Has No Ambient
Condition Requirements
a. Test Sample Set-up and Power
Measurement: For coil-only systems,
provide a furnace or modular blower
that is compatible with the system to
serve as an interface with the thermostat
(if used for the test) and to provide lowvoltage control circuit power. Make all
control circuit connections between the
furnace (or modular blower) and the
outdoor unit as specified by the
manufacturer’s installation instructions.
Measure power supplied to both the
furnace or modular blower and power
supplied to the outdoor unit.
Alternatively, provide a compatible
transformer to supply low-voltage
control circuit power, as described in
section 2.2.d of this appendix. Measure
transformer power, either supplied to
the primary winding or supplied by the
secondary winding of the transformer,
and power supplied to the outdoor unit.
For blower coil and single-package
systems, make all control circuit
connections between components as
specified by the manufacturer’s
installation instructions, and provide
power and measure power supplied to
all system components.
b. Configure Controls: Configure the
controls of the central air conditioner or
heat pump so that it operates as if
connected to a building thermostat that
is set to the OFF position. Use a
PO 00000
Frm 00105
Fmt 4701
Sfmt 4700
compatible building thermostat if
necessary to achieve this configuration.
For a thermostat-controlled crankcase
heater with a fixed power input, bypass
the crankcase heater thermostat if
necessary to energize the heater.
c. Measure P2x: If the unit has a
crankcase heater time delay, make sure
that time delay function is disabled or
wait until delay time has passed.
Determine the average power from nonzero value data measured over a 5minute interval of the non-operating
central air conditioner or heat pump
and designate the average power as P2x,
the heating season total off mode power.
d. Measure P2x for coil-only split
systems and for blower coil split
systems for which a furnace or a
modular blower is the designated air
mover: Disconnect all low-voltage
wiring for the outdoor components and
outdoor controls from the low-voltage
transformer. Determine the average
power from non-zero value data
measured over a 5-minute interval of the
power supplied to the (remaining) lowvoltage components of the central air
conditioner or heat pump, or lowvoltage power, P2x. This power
measurement does not include line
power supplied to the outdoor unit. It
is the line power supplied to the air
mover, or, if a compatible transformer is
used instead of an air mover, it is the
line power supplied to the transformer
primary coil. If a compatible transformer
is used instead of an air mover and
power output of the low-voltage
secondary circuit is measured, Px is
zero.
e. Calculate P2: Set the number of
compressors equal to the unit’s number
of single-stage compressors plus 1.75
times the unit’s number of compressors
that are not single-stage.
For single-package systems and
blower coil split systems for which the
designated air mover is not a furnace or
modular blower, divide the heating
season total off mode power (P2x) by the
number of compressors to calculate P2,
the heating season per-compressor off
mode power. Round P2 to the nearest
watt. The expression for calculating P2
is as follows:
For coil-only split systems and blower
coil split systems for which a furnace or
a modular blower is the designated air
mover, subtract the low-voltage power
(Px ) from the heating season total off
mode power (P2x) and divide by the
number of compressors to calculate P2,
the heating season per-compressor off
mode power. Round P2 to the nearest
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.041
3.11.2 If Using the Compressor
Calibration Method as the Secondary
Test Method
37095
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
asabaliauskas on DSK3SPTVN1PROD with RULES
3.13.2 This test determines the off
mode average power rating for central
air conditioners and heat pumps for
which ambient temperature can affect
the measurement of crankcase heater
power.
a. Test Sample Set-up and Power
Measurement: Set up the test and
measurement as described in section
3.13.1.a of this appendix.
b. Configure Controls: Position a
temperature sensor to measure the
outdoor dry-bulb temperature in the air
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00106
Fmt 4701
Sfmt 4700
For coil-only split systems and blower
coil split systems for which a furnace or
a modular blower is the designated air
mover, subtract the low-voltage power
(Px) from the shoulder season total off
mode power (P1x) and divide by the
number of compressors to calculate P1,
the shoulder season per-compressor off
mode power. Round to the nearest watt.
The expression for calculating P1 is as
follows:
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.045
For coil-only split systems and blower
coil split systems for which a furnace or
a modular blower is the designated air
mover, subtract the low-voltage power
(Px) from the shoulder season total off
mode power (P1x) and divide by the
number of compressors to calculate P1,
the shoulder season per-compressor off
mode power. Round P1 to the nearest
watt. The expression for calculating P1
is as follows:
conditioner or heat pump over a 5minute interval and designate it as P2x,
the heating season total off mode power.
For units with crankcase heaters whose
controls cycle or vary crankcase heater
power over time, the test period shall
consist of three complete crankcase
heater cycles or 18 hours, whichever
comes first. Designate the average power
over the test period as P2x, the heating
season total off mode power.
f. Measure Px for coil-only split
systems and for blower coil split
systems for which a furnace or modular
blower is the designated air mover:
Disconnect all low-voltage wiring for
the outdoor components and outdoor
controls from the low-voltage
transformer. Determine the average
power from non-zero value data
measured over a 5-minute interval of the
power supplied to the (remaining) lowvoltage components of the central air
conditioner or heat pump, or lowvoltage power, Px. This power
measurement does not include line
power supplied to the outdoor unit. It
is the line power supplied to the air
mover, or, if a compatible transformer is
used instead of an air mover, it is the
line power supplied to the transformer
primary coil. If a compatible transformer
is used instead of an air mover and
power output of the low-voltage
secondary circuit is measured, Px is
zero.
g. Calculate P1:
Set the number of compressors equal
to the unit’s number of single-stage
compressors plus 1.75 times the unit’s
number of compressors that are not
single-stage.
For single-package systems and
blower coil split systems for which the
air mover is not a furnace or modular
blower, divide the shoulder season total
off mode power (P1x) by the number of
compressors to calculate P1, the
shoulder season per-compressor off
mode power. Round to the nearest watt.
The expression for calculating P1 is as
follows:
ER08JN16.044
f. Shoulder-season per-compressor off
mode power, P1: If the system does not
have a crankcase heater, has a crankcase
heater without controls that is not selfregulating, or has a value for the
crankcase heater turn-on temperature
(as certified in the DOE Compliance
Certification Database) that is higher
than 71 °F, P1 is equal to P2.
Otherwise, de-energize the crankcase
heater (by removing the thermostat
bypass or otherwise disconnecting only
the power supply to the crankcase
heater) and repeat the measurement as
described in section 3.13.1.c of this
appendix. Designate the measured
average power as P1x, the shoulder
season total off mode power.
Determine the number of compressors
as described in section 3.13.1.e of this
appendix.
For single-package systems and
blower coil systems for which the
designated air mover is not a furnace or
modular blower, divide the shoulder
season total off mode power (P1x) by the
number of compressors to calculate P1,
the shoulder season per-compressor off
mode power. Round P1 to the nearest
watt. The expression for calculating P1
is as follows:
between 2 and 6 inches from the
crankcase heater control temperature
sensor or, if no such temperature sensor
exists, position it in the air between 2
and 6 inches from the crankcase heater.
Utilize the temperature measurements
from this sensor for this portion of the
test procedure. Configure the controls of
the central air conditioner or heat pump
so that it operates as if connected to a
building thermostat that is set to the
OFF position. Use a compatible building
thermostat if necessary to achieve this
configuration.
Conduct the test after completion of
the B, B1, or B2 test. Alternatively, start
the test when the outdoor dry-bulb
temperature is at 82 °F and the
temperature of the compressor shell (or
temperature of each compressor’s shell
if there is more than one compressor) is
at least 81 °F. Then adjust the outdoor
temperature at a rate of change of no
more than 20 °F per hour and achieve
an outdoor dry-bulb temperature of 72
°F. Maintain this temperature within +/
¥2 °F while making the power
measurement, as described in section
3.13.2.c of this appendix.
c. Measure P1x: If the unit has a
crankcase heater time delay, make sure
that time delay function is disabled or
wait until delay time has passed.
Determine the average power from nonzero value data measured over a 5minute interval of the non-operating
central air conditioner or heat pump
and designate the average power as P1x,
the shoulder season total off mode
power. For units with crankcase heaters
which operate during this part of the
test and whose controls cycle or vary
crankcase heater power over time, the
test period shall consist of three
complete crankcase heater cycles or 18
hours, whichever comes first. Designate
the average power over the test period
as P1x, the shoulder season total off
mode power.
d. Reduce outdoor temperature:
Approach the target outdoor dry-bulb
temperature by adjusting the outdoor
temperature at a rate of change of no
more than 20 °F per hour. This target
temperature is five degrees Fahrenheit
less than the temperature specified by
the manufacturer in the DOE
Compliance Certification Database at
which the crankcase heater turns on.
Maintain the target temperature within
+/¥2 °F while making the power
measurement, as described in section
3.13.2.e of this appendix.
e. Measure P2x: If the unit has a
crankcase heater time delay, make sure
that time delay function is disabled or
wait until delay time has passed.
Determine the average non-zero power
of the non-operating central air
ER08JN16.043
watt. The expression for calculating P2
is as follows:
ER08JN16.042
37096
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
For coil-only split systems and blower
coil split systems for which a furnace or
a modular blower is the designated air
mover, subtract the low-voltage power
(Px) from the heating season total off
mode power (P2x) and divide by the
number of compressors to calculate P2,
the heating season per-compressor off
mode power. Round to the nearest watt.
The expression for calculating P2 is as
follows:
4. Calculations of Seasonal Performance
Descriptors
4.1 Seasonal Energy Efficiency Ratio
(SEER) Calculations. SEER must be
calculated as follows:
For equipment covered under sections
4.1.2, 4.1.3, and 4.1.4 of this appendix,
evaluate the seasonal energy efficiency
ratio,
Where:
˙
Qck=2(95) = the space cooling capacity
determined from the A2 test and
calculated as specified in section 3.3 of
this appendix, Btu/h.
1.1 = sizing factor, dimensionless.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00107
Fmt 4701
Sfmt 4700
The temperatures 95 °F and 65 °F in
the building load equation represent the
selected outdoor design temperature
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.047
ER08JN16.048
referenced, evaluate BL(Tj) for cooling
using,
ER08JN16.046
asabaliauskas on DSK3SPTVN1PROD with RULES
Additionally, for sections 4.1.2, 4.1.3,
and 4.1.4 of this appendix, use a
building cooling load, BL(Tj). When
ER08JN16.049
ER08JN16.050
h. Calculate P2:
Determine the number of compressors
as described in section 3.13.2.g of this
appendix.
For single-package systems and
blower coil split systems for which the
air mover is not a furnace, divide the
heating season total off mode power
(P1x) by the number of compressors to
calculate P2, the heating season percompressor off mode power. Round to
the nearest watt. The expression for
calculating P2 is as follows:
37097
37098
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
and the zero-load base temperature,
respectively.
4.1.1 SEER Calculations for a Blower
Coil System Having a Single-Speed
Compressor and Either a Fixed-Speed
Indoor Blower or a Constant-AirVolume-Rate Indoor Blower, or a CoilOnly System Air Conditioner or Heat
Pump
SEER = PLF(0.5) * EERB
Where:
a. Evaluate the seasonal energy
efficiency ratio, expressed in units of
Btu/watt-hour, using:
PLF(0.5) = 1 ¥ 0.5 · CDc, the part-load
performance factor evaluated at a cooling
load factor of 0.5, dimensionless.
Equation 4.1–2 to calculate the building
˙
load, BL(Tj). Evaluate Qc(Tj) using,
ER08JN16.052
a. For the space cooling season, assign
nj/N as specified in Table 18. Use
4.1.2.1 Units covered by section
3.2.2.1 of this appendix where indoor
blower capacity modulation correlates
with the outdoor dry bulb temperature.
The manufacturer must provide
information on how the indoor air
volume rate or the indoor blower speed
varies over the outdoor temperature
range of 67 °F to 102 °F. Calculate SEER
using Equation 4.1–1. Evaluate the
quantity qc(Tj)/N in Equation 4.1–1
using,
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00108
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.051
asabaliauskas on DSK3SPTVN1PROD with RULES
b. Refer to section 3.3 of this appendix
regarding the definition and calculation
˙
˙
of Qc(82) and Ec(82).
4.1.2 SEER Calculations for an Air
Conditioner or Heat Pump Having a
Single-Speed Compressor and a
Variable-Speed Variable-Air-VolumeRate Indoor Blower
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37099
sections 3.2.2.1, 3.1.4 to 3.1.4.2, and 3.3
of this appendix regarding the
definitions and calculations of
˙
˙
˙
Qck=1(82), Qck=1(95), Qck=2(82), and
˙
Qck=2(95).
˙
Ec(Tj) = the electrical power consumption of
the test unit when operating at outdoor
temperature Tj, W.
c. The quantities X(Tj) and nj/N are
the same quantities as used in Equation
4.1.2–1.
˙
d. Evaluate Ec(Tj) using,
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00109
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.053
ER08JN16.054
denotes the fan speed used by the unit
when the outdoor temperature equals Tj.
For units where indoor air volume rate
is the primary control variable, the three
FPc’s are similarly defined only now
being expressed in terms of air volume
rates rather than fan speeds. Refer to
Where:
PLFj = 1 ¥ CDc · [1 ¥ X(Tj)], the part load
factor, dimensionless.
asabaliauskas on DSK3SPTVN1PROD with RULES
b. For units where indoor blower
speed is the primary control variable,
FPck=1 denotes the fan speed used
during the required A1 and B1 tests (see
section 3.2.2.1 of this appendix), FPck=2
denotes the fan speed used during the
required A2 and B2 tests, and FPc(Tj)
37100
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
4.1.2.2 Units Covered by Section
3.2.2.2 of This Appendix Where Indoor
Blower Capacity Modulation Is Used To
Adjust the Sensible to Total Cooling
Capacity Ratio
˙
˙
where Qck=1 (82) and Eck=1 (82) are
˙
determined from the B1 test, Qck=1 (67)
˙
and Eck=1 (67) are determined from the
F1 test, and all four quantities are
calculated as specified in section 3.3 of
this appendix. Evaluate the space
˙
cooling capacity, Qck=2 (Tj), and
˙
electrical power consumption, Eck=2 (Tj),
Calculate SEER using Equation 4.1–1.
Evaluate the space cooling capacity,
˙
Qck=1 (Tj), and electrical power
˙
consumption, Eck=1 (Tj), of the test unit
when operating at low compressor
capacity and outdoor temperature Tj
using,
of the test unit when operating at high
compressor capacity and outdoor
temperature Tj using,
ER08JN16.056
ER08JN16.057
Calculate SEER as specified in section
4.1.1 of this appendix.
4.1.2.3 SEER Calculations for an Air
Conditioner or Heat Pump Having a
Two-Capacity Compressor
VerDate Sep<11>2014
01:07 Jun 08, 2016
Jkt 238001
PO 00000
Frm 00110
Fmt 4701
Sfmt 4725
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.055
asabaliauskas on DSK3SPTVN1PROD with RULES
e. The parameters FPck=1, and FPck=2,
and FPc(Tj) are the same quantities that
are used when evaluating Equation
4.1.2–2. Refer to sections 3.2.2.1, 3.1.4
to 3.1.4.2, and 3.3 of this appendix
regarding the definitions and
˙
˙
calculations of Eck=1(82), Eck=1(95),
˙
˙
Eck=2(82), and Eck=2(95).
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37101
˙
˙
where Qck=2(95) and Eck=2(95) are
˙
determined from the A2 test, Qck=2(82),
˙
and Eck=2(82), are determined from the
B2test, and all are calculated as
specified in section 3.3 of this appendix.
The calculation of Equation 4.1–1
quantities qc(Tj)/N and ec(Tj)/N differs
depending on whether the test unit
would operate at low capacity (section
4.1.2.4 of this appendix), cycle between
low and high capacity (section 4.1.2.5 of
this appendix), or operate at high
capacity (sections 4.1.2.6 and 4.1.2.7 of
this appendix) in responding to the
building load. For units that lock out
low capacity operation at higher
outdoor temperatures, the manufacturer
must supply information regarding this
temperature so that the appropriate
equations are used. Use Equation 4.1–2
to calculate the building load, BL(Tj), for
each temperature bin.
4.1.2.4 Steady-state space cooling
capacity at low compressor capacity is
greater than or equal to the building
˙
cooling load at temperature Tj, Qck=1(Tj)
≥BL(Tj).
Where:
˙
Xk=1(Tj) = BL(Tj)/Qck=1(Tj), the cooling mode
low capacity load factor for temperature
bin j, dimensionless.
PLFj = 1 ¥ CDc · [1 ¥ Xk=1(Tj)], the part load
factor, dimensionless.
TABLE 18—DISTRIBUTION OF FRACTIONAL HOURS WITHIN COOLING SEASON TEMPERATURE BINS
Bin
temperature
range, °F
Bin number, j
1
2
3
4
5
6
7
8
...................................................................................................................................................
...................................................................................................................................................
...................................................................................................................................................
...................................................................................................................................................
...................................................................................................................................................
...................................................................................................................................................
...................................................................................................................................................
...................................................................................................................................................
67
72
77
82
87
92
97
102
Fraction
of total
temperature
bin hours,
nj/N
0.214
0.231
0.216
0.161
0.104
0.052
0.018
0.004
ER08JN16.060
˙
load at temperature Tj, Qck=1(Tj) 2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00111
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.059
asabaliauskas on DSK3SPTVN1PROD with RULES
4.1.2.5 Unit alternates between high
(k=2) and low (k=1) compressor
capacity to satisfy the building cooling
65–69
70–74
75–79
80–84
85–89
90–94
95–99
100–104
Representative
temperature
for bin, °F
37102
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Obtain the fractional bin hours for the
cooling season, nj/N, from Table 18. Use
Equations 4.1.3–1 and 4.1.3–2,
Where:
˙
respectively, to evaluate Qck=1(Tj) and
˙
Eck=1(Tj). Use Equations 4.1.3–3 and
4.1.3–4, respectively, to evaluate
˙
˙
Qck=2(Tj) and Eck=2(Tj).
4.1.2.6 Unit only operates at high (k =
2) compressor capacity at temperature Tj
and its capacity is greater than the
˙
building cooling load, BL(Tj)
ER08JN16.063
Calculate SEER using Equation 4.1–1.
Evaluate the space cooling capacity,
ER08JN16.062
Obtain the fractional bin hours for the
cooling season, nj/N, from Table 18. Use
Equations 4.1.3–3 and 4.1.3–4,
˙
respectively, to evaluate Qck=2(Tj) and
˙
Eck=2(Tj).
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00112
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.061
asabaliauskas on DSK3SPTVN1PROD with RULES
4.1.2.7 Unit must operate continuously
at high (k = 2) compressor capacity at
˙
temperature Tj, BL(Tj) ≥Qck=2(Tj).
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37103
˙
˙
where Qck=1(82) and Eck=1(82) are
˙
determined from the B1 test, Qck=1(67)
˙
and Eck=1(67) are determined from the
F1 test, and all four quantities are
calculated as specified in section 3.3 of
this appendix. Evaluate the space
˙
cooling capacity, Qck=2(Tj), and
˙
electrical power consumption, Eck=2(Tj),
of the test unit when operating at full
compressor speed and outdoor
temperature Tj. Use Equations 4.1.3–3
and 4.1.3–4, respectively, where
˙
˙
Qck=2(95) and Eck=2(95) are determined
˙
˙
from the A2 test, Qck=2(82) and Eck=2(82)
are determined from the B2 test, and all
four quantities are calculated as
specified in section 3.3 of this appendix.
Calculate the space cooling capacity,
˙
Qck=v(Tj), and electrical power
˙
consumption, Eck=v(Tj), of the test unit
when operating at outdoor temperature
Tj and the intermediate compressor
speed used during the section 3.2.4 (and
Table 7) EV test of this appendix using,
˙
˙
Equation 4.1.4–3 Qck=v(Tj) = Qck=v(87)
+ MQ * (Tj ¥ 87)
˙
˙
Equation 4.1.4–4 Eck=v(Tj) = Ehk=v(87) +
ME * (Tj ¥ 87)
˙
˙
where Qck=v(87) and Eck=v(87) are
determined from the EV test and
calculated as specified in section 3.3 of
this appendix. Approximate the slopes
of the k=v intermediate speed cooling
capacity and electrical power input
curves, MQ and ME, as follows:
Use Equations 4.1.4–1 and 4.1.4–2,
˙
respectively, to calculate Qck=1(87) and
˙
Eck=1(87).
4.1.3.1 Steady-state space cooling
capacity when operating at minimum
compressor speed is greater than or
equal to the building cooling load at
˙
temperature Tj, Qck=1(Tj) ≥BL(Tj).
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00113
Fmt 4701
Sfmt 4700
The matching occurs with the unit
operating at compressor speed k = i.
E:\FR\FM\08JNR2.SGM
ER08JN16.067
4.1.3.2 Unit operates at an
intermediate compressor speed (k=i) in
order to match the building cooling load
˙
at temperature Tj,Qck=1(Tj)
˙
respectively, to evaluate Qck=l (Tj) and
˙
Eck=l (Tj).
ER08JN16.066
Obtain the fractional bin hours for the
cooling season, nj/N, from Table 18. Use
Equations 4.1.3–1 and 4.1.3–2,
˙
Qck=i(Tj) = BL(Tj), the space cooling capacity
delivered by the unit in matching the
building load at temperature Tj, Btu/h.
Where:
VerDate Sep<11>2014
during the cooling season when the
outdoor temperature fell within the
range represented by bin temperature Tj
to the total number of hours in the
cooling season, dimensionless.
08JNR2
ER08JN16.065
asabaliauskas on DSK3SPTVN1PROD with RULES
Where:
˙
Xk=1(Tj) = BL(Tj)/Qck=1(Tj), the cooling mode
minimum speed load factor for
temperature bin j, dimensionless.
PLFj = 1 ¥ CDc · [1 ¥ Xk=1(Tj)], the part load
factor, dimensionless.
nj/N = fractional bin hours for the cooling
season; the ratio of the number of hours
37104
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
EERk=i(Tj) = the steady-state energy efficiency
ratio of the test unit when operating at
a compressor speed of k = i and
temperature Tj, Btu/h per W.
Obtain the fractional bin hours for the
cooling season, nj/N, from Table 18. For
each temperature bin where the unit
operates at an intermediate compressor
speed, determine the energy efficiency
ratio EERk=i(Tj) using,
For each unit, determine the
coefficients A, B, and C by conducting
the following calculations once:
EERk=i(Tj) = A + B · Tj + C · Tj2.
as specified in section 4.1.2.7 of this
appendix with the understanding that
˙
˙
Qck=2(Tj) and Eck=2(Tj) correspond to full
compressor speed operation and are
derived from the results of the tests
specified in section 3.2.4 of this
appendix.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
Calculate SEER using Eq. 4.1–1,
where qc(Tj)/N and ec(Tj)/N are
evaluated as specified in the applicable
subsection.
4.1.4.1 For Multiple Indoor Blower
Systems That Are Connected to a Single,
Single-Speed Outdoor Unit
a. Calculate the space cooling
˙
capacity, Qck=1(Tj), and electrical power
˙
consumption, Eck=1(Tj), of the test unit
when operating at the cooling minimum
air volume rate and outdoor temperature
Tj using the equations given in section
4.1.2.1 of this appendix. Calculate the
˙
space cooling capacity, Qck=2(Tj), and
PO 00000
Frm 00114
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.071
˙
electrical power consumption, Eck=2(Tj),
of the test unit when operating at the
cooling full-load air volume rate and
outdoor temperature Tj using the
equations given in section 4.1.2.1 of this
appendix. In evaluating the section
4.1.2.1 equations, determine the
˙
˙
quantities Qck=1(82) and Eck=1(82) from
˙
˙
the B1 test, Qck=1(95) and Eck=1(95) from
˙
˙
the Al test, Qck=2(82) and Eck=2(82) from
˙
˙
the B2 test, and Qck=2(95) and Eck=2(95)
from the A2 test. Evaluate all eight
quantities as specified in section 3.3 of
this appendix. Refer to section 3.2.2.1
and Table 5 of this appendix for
additional information on the four
referenced laboratory tests.
b. Determine the cooling mode cyclic
degradation coefficient, CDc, as per
sections 3.2.2.1 and 3.5 to 3.5.3 of this
ER08JN16.070
4.1.4 SEER Calculations for an Air
Conditioner or Heat Pump Having a
Single Indoor Unit With Multiple
Indoor Blowers
ER08JN16.072
Equations 4.1.4–3 and 4.1–2 and solving
for outdoor temperature.
T2 = the outdoor temperature at which the
unit, when operating at full compressor
speed, provides a space cooling capacity
˙
that is equal to the building load (Qck=2
(T2) = BL(T2)), °F. Determine T2 by
equating Equations 4.1.3–3 and 4.1–2
and solving for outdoor temperature.
ER08JN16.069
4.1.3–1 and 4.1–2 and solving for
outdoor temperature.
Tv = the outdoor temperature at which the
unit, when operating at the intermediate
compressor speed used during the
section 3.2.4 EV test of this appendix,
provides a space cooling capacity that is
˙
equal to the building load (Qck=v (Tv) =
BL(Tv)), °F. Determine Tv by equating
4.1.3.3 Unit must operate continuously
at full (k = 2) compressor speed at
˙
temperature Tj, BL(Tj) ≥Qck=2(Tj).
Evaluate the Equation 4.1–1 quantities
asabaliauskas on DSK3SPTVN1PROD with RULES
Where:
T1 = the outdoor temperature at which the
unit, when operating at minimum
compressor speed, provides a space
cooling capacity that is equal to the
˙
building load (Qck=l (Tl) = BL(T1)), °F.
Determine T1 by equating Equations
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37105
appendix. Assign this same value to
CDc(K=2).
c. Except for using the above values
˙
˙
˙
˙
of Qck=1(Tj), Eck=1(Tj), Eck=2(Tj), Qck=2(Tj),
CDc, and CDc (K=2), calculate the
quantities qc(Tj)/N and ec(Tj)/N as
specified in section 4.1.3.1 of this
˙
appendix for cases where Qck=1(Tj) ≥
BL(Tj). For all other outdoor bin
temperatures, Tj, calculate qc(Tj)/N and
ec(Tj)/N as specified in section 4.1.3.3 of
˙
this appendix if Qck=2(Tj) > BL(Tj) or as
specified in section 4.1.3.4 of this
˙
appendix if Qck=2(Tj) ≤ BL(Tj).
4.2 Heating Seasonal Performance
Factor (HSPF) Calculations
4.1.4.2 For multiple indoor blower
systems that are connected to either a
lone outdoor unit having a two-capacity
compressor or to two separate singlespeed outdoor units of identical model,
calculate the quantities qc(Tj)/N and
ec(Tj)/N as specified in section 4.1.3 of
this appendix.
Unless an approved alternative
efficiency determination method is
used, as set forth in 10 CFR 429.70(e),
HSPF must be calculated as follows: Six
generalized climatic regions are
depicted in Figure 1 and otherwise
defined in Table 19. For each of these
regions and for each applicable
standardized design heating
requirement, evaluate the heating
seasonal performance factor using,
Where:
eh(Tj)/N = The ratio of the electrical energy
consumed by the heat pump during
periods of the space heating season when
the outdoor temperature fell within the
range represented by bin temperature Tj
to the total number of hours in the
heating season (N), W. For heat pumps
having a heat comfort controller, this
ratio may also include electrical energy
used by resistive elements to maintain a
minimum air delivery temperature (see
4.2.5).
RH(Tj)/N = The ratio of the electrical energy
used for resistive space heating during
periods when the outdoor temperature
fell within the range represented by bin
temperature Tj to the total number of
hours in the heating season (N), W.
Except as noted in section 4.2.5 of this
appendix, resistive space heating is
modeled as being used to meet that
portion of the building load that the heat
pump does not meet because of
insufficient capacity or because the heat
pump automatically turns off at the
lowest outdoor temperatures. For heat
pumps having a heat comfort controller,
all or part of the electrical energy used
by resistive heaters at a particular bin
temperature may be reflected in eh(Tj)/N
(see section 4.2.5 of this appendix).
Tj = the outdoor bin temperature, °F. Outdoor
temperatures are ‘‘binned’’ such that
calculations are only performed based
one temperature within the bin. Bins of
5 °F are used.
nj/N = Fractional bin hours for the heating
season; the ratio of the number of hours
during the heating season when the
outdoor temperature fell within the
range represented by bin temperature Tj
to the total number of hours in the
heating season, dimensionless. Obtain
nj/N values from Table 19.
j = the bin number, dimensionless.
J = for each generalized climatic region, the
total number of temperature bins,
dimensionless. Referring to Table 19, J is
the highest bin number (j) having a
nonzero entry for the fractional bin hours
for the generalized climatic region of
interest.
Fdef = the demand defrost credit described in
section 3.9.2 of this appendix,
dimensionless.
BL(Tj) = the building space conditioning load
corresponding to an outdoor temperature
of Tj; the heating season building load
also depends on the generalized climatic
region’s outdoor design temperature and
the design heating requirement, Btu/h.
TABLE 19—GENERALIZED CLIMATIC REGION INFORMATION
Region No.
I
Heating Load Hours, HLH .......................
Outdoor Design Temperature, TOD ..........
750
37
III
1,250
27
Tj (°F) ...................................................
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
IV
1,750
17
V
2,250
5
VI
2,750
¥10
* 2,750
30
.106
.092
.086
.076
.078
.087
.102
.094
.074
.055
.047
.038
.029
.018
.010
.005
.002
.001
.113
.206
.215
.204
.141
.076
.034
.008
.003
0
0
0
0
0
0
0
0
0
Fractional Bin Hours, nj/N
62 ........................................................
57 ........................................................
52 ........................................................
47 ........................................................
42 ........................................................
37 ........................................................
32 ........................................................
27 ........................................................
22 ........................................................
17 ......................................................
12 ......................................................
7 ........................................................
2 ........................................................
¥3 ....................................................
¥8 ....................................................
¥13 ..................................................
¥18 ..................................................
¥23 ..................................................
.291
.239
.194
.129
.081
.041
.019
.005
.001
0
0
0
0
0
0
0
0
0
.215
.189
.163
.143
.112
.088
.056
.024
.008
.002
0
0
0
0
0
0
0
0
.153
.142
.138
.137
.135
.118
.092
.047
.021
.009
.005
.002
.001
0
0
0
0
0
.132
.111
.103
.093
.100
.109
.126
.087
.055
.036
.026
.013
.006
.002
.001
0
0
0
* Pacific Coast Region.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00115
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.073
asabaliauskas on DSK3SPTVN1PROD with RULES
j
II
37106
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Evaluate the building heating load
using
C = 0.77, a correction factor which tends to
improve the agreement between
calculated and measured building loads,
dimensionless.
DHR = the design heating requirement (see
section 1.2 of this appendix, Definitions),
Btu/h.
Calculate the minimum and
maximum design heating requirements
for each generalized climatic region as
follows:
˙
where Qhk(47) is expressed in units of
Btu/h and otherwise defined as follows:
a. For a single-speed heat pump tested
as per section 3.6.1 of this appendix,
˙
˙
Qhk(47) = Qh(47), the space heating
capacity determined from the H1 test.
b. For a variable-speed heat pump, a
section 3.6.2 single-speed heat pump, or
a two-capacity heat pump not covered
˙
˙
by item 3, Qnk(47) = Qnk=2(47), the space
heating capacity determined from the
H12 test.
c. For two-capacity, northern heat
pumps (see section 1.2 of this appendix,
˙
˙
Definitions), Qkh(47) = Qk=1h(47), the
space heating capacity determined from
the H11 test.
If the optional H1N test is conducted
on a variable-speed heat pump, the
manufacturer has the option of defining
˙
Qkh(47) as specified above in item 2 or
˙
˙
as Qkh(47) = Qk = Nh(47), the space
heating capacity determined from the
H1N test.
For all heat pumps, HSPF accounts
for the heating delivered and the energy
consumed by auxiliary resistive
elements when operating below the
balance point. This condition occurs
when the building load exceeds the
space heating capacity of the heat pump
condenser. For HSPF calculations for all
heat pumps, see either section 4.2.1,
4.2.2, 4.2.3, or 4.2.4 of this appendix,
whichever applies.
For heat pumps with heat comfort
controllers (see section 1.2 of this
appendix, Definitions), HSPF also
accounts for resistive heating
contributed when operating above the
heat-pump-plus-comfort-controller
balance point as a result of maintaining
a minimum supply temperature. For
heat pumps having a heat comfort
controller, see section 4.2.5 of this
appendix for the additional steps
required for calculating the HSPF.
TABLE 20—STANDARDIZED DESIGN
HEATING REQUIREMENTS
[Btu/h]
5,000
10,000
15,000
20,000
25,000
30,000
35,000
40,000
50,000
60,000
70,000
80,000
90,000
100,000
110,000
130,000
ER08JN16.075
ER08JN16.076
4.2.1 Additional steps for
calculating the HSPF of a blower coil
system heat pump having a single-speed
compressor and either a fixed-speed
indoor blower or a constant-air-volumerate indoor blower installed, or a coilonly system heat pump.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00116
Fmt 4701
Sfmt 4725
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.074
asabaliauskas on DSK3SPTVN1PROD with RULES
Where:
TOD = the outdoor design temperature, °F. An
outdoor design temperature is specified
for each generalized climatic region in
Table 19.
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37107
˙
Eh(Tj) = the electrical power consumption of
the heat pump when operating at
outdoor temperature Tj, W.
d(Tj) = the heat pump low temperature cutout factor, dimensionless.
˙
PLFj = 1 ¥ CDh · [1 ¥X(Tj)] the part load
factor, dimensionless.
Use Equation 4.2–2 to determine
BL(Tj). Obtain fractional bin hours for
the heating season, nj/N, from Table 19.
Determine the low temperature cutout factor using
Where:
Toff = the outdoor temperature when the
compressor is automatically shut off, °F.
(If no such temperature exists, Tj is
always greater than Toff and Ton).
Ton = the outdoor temperature when the
compressor is automatically turned back
on, if applicable, following an automatic
shut-off, °F.
˙
˙
where Qh(47) and Eh(47) are determined
from the H1 test and calculated as
specified in section 3.7 of this appendix;
˙
˙
Qh(35) and Eh(35) are determined from
the H2 test and calculated as specified
in section 3.9.1 of this appendix; and
˙
˙
Qh(17) and Eh(17) are determined from
the H3 test and calculated as specified
in section 3.10 of this appendix.
4.2.2 Additional steps for calculating
the HSPF of a heat pump having a
single-speed compressor and a variablespeed, variable-air-volume-rate indoor
blower.
The manufacturer must provide
information about how the indoor air
volume rate or the indoor blower speed
varies over the outdoor temperature
whichever is less; the heating mode load
factor for temperature bin j,
dimensionless.
˙
˙
Calculate Qh(Tj) and Eh(Tj) using,
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00117
Fmt 4701
Sfmt 4700
in Equation 4.2–1 as specified in section
4.2.1 of this appendix with the
exception of replacing references to the
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.079
ER08JN16.078
range of 65 °F to ¥23 °F. Calculate the
quantities
ER08JN16.077
asabaliauskas on DSK3SPTVN1PROD with RULES
ER08JN16.080
˙
Qh(Tj) = the space heating capacity of the
heat pump when operating at outdoor
temperature Tj, Btu/h.
37108
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
3.6.2 of this appendix. In addition,
evaluate the space heating capacity and
electrical power consumption of the
˙
˙
heat pump Qh(Tj) and Eh(Tj) using
For units where indoor blower speed
is the primary control variable, FPhk=1
denotes the fan speed used during the
required H11 and H31 tests (see Table
11), FPhk=2 denotes the fan speed used
during the required H12, H22, and H32
tests, and FPh(Tj) denotes the fan speed
used by the unit when the outdoor
temperature equals Tj. For units where
indoor air volume rate is the primary
control variable, the three FPh’s are
similarly defined only now being
expressed in terms of air volume rates
rather than fan speeds. Determine
˙
˙
Qhk=1(47) and Ehk=1(47) from the H11
˙
˙
test, and Qhk=2(47) and Ehk=2(47) from
the H12 test. Calculate all four quantities
as specified in section 3.7 of this
˙
appendix. Determine Qhk=1(35) and
˙
Ehk=1(35) as specified in section 3.6.2 of
˙
this appendix; determine Qhk=2(35) and
˙
Ehk=2(35) and from the H22 test and the
calculation specified in section 3.9 of
˙
this appendix. Determine Qhk=1(17) and
˙
˙
Ehk=1(17 from the H31 test, and Qhk=2(17)
˙
and Ehk=2(17) from the H32 test.
Calculate all four quantities as specified
in section 3.10 of this appendix.
whether the heat pump would operate
at low capacity (section 4.2.3.1 of this
appendix), cycle between low and high
capacity (section 4.2.3.2 of this
appendix), or operate at high capacity
(sections 4.2.3.3 and 4.2.3.4 of this
appendix) in responding to the building
load. For heat pumps that lock out low
capacity operation at low outdoor
temperatures, the manufacturer must
supply information regarding the cutoff
temperature(s) so that the appropriate
equations can be selected.
a. Evaluate the space heating capacity
and electrical power consumption of the
heat pump when operating at low
compressor capacity and outdoor
temperature Tj using
4.2.3 Additional Steps for Calculating
the HSPF of a Heat Pump Having a TwoCapacity Compressor
ER08JN16.082
The calculation of the Equation 4.2–
1 quantities differ depending upon
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00118
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.081
asabaliauskas on DSK3SPTVN1PROD with RULES
H1C test and section 3.6.1 of this
appendix with the H1C1 test and section
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37109
test. Calculate all six quantities as
specified in section 3.7 of this appendix.
˙
˙
Determine Qhk=2(35) and Ehk=2(35) from
the H22 test and, if required as described
in section 3.6.3 of this appendix,
˙
˙
determine Qhk=1(35) and Ehk=1(35) from
the H21 test. Calculate the required 35
°F quantities as specified in section 3.9
˙
of this appendix. Determine Qhk=2(17)
˙
and Ehk=2(17) from the H32 test and, if
required as described in section 3.6.3 of
˙
this appendix, determine Qhk=1(17) and
˙
Ehk=1(17) from the H31 test. Calculate
the required 17 °F quantities as
specified in section 3.10 of this
appendix.
Where:
˙
Xk=1(Tj) = BL(Tj)/Qhk=1(Tj), the heating mode
low capacity load factor for temperature
bin j, dimensionless.
PLFj = 1 ¥ CDh · [ 1 ¥ Xk=1(Tj) ], the part
load factor, dimensionless.
d′(Tj) = the low temperature cutoff factor,
dimensionless.
Determine the low temperature cutout factor using
where Toff and Ton are defined in section
4.2.1 of this appendix. Use the
calculations given in section 4.2.3.3 of
this appendix, and not the above, if:
a. The heat pump locks out low
capacity operation at low outdoor
temperatures and
b. Tj is below this lockout threshold
temperature.
4.2.3.2 Heat pump alternates between
high (k=2) and low (k=1) compressor
capacity to satisfy the building heating
˙
load at a temperature Tj, Qhk=1(Tj)
˙
ER08JN16.085
4.2.3.1 Steady-state space heating
capacity when operating at low
compressor capacity is greater than or
equal to the building heating load at
˙
temperature Tj, Qhk=1(Tj) ≥BL(Tj).
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00119
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.083
asabaliauskas on DSK3SPTVN1PROD with RULES
b. Evaluate the space heating capacity
and electrical power consumption
˙
˙
(Qhk=2(Tj) and Ehk=2 (Tj)) of the heat
pump when operating at high
compressor capacity and outdoor
temperature Tj by solving Equations
4.2.2–3 and 4.2.2–4, respectively, for
˙
˙
k=2. Determine Qhk=1(62) and Ehk=1(62)
˙
from the H01 test, Qhk=1(47) and
˙
Ehk=1(47) from the H11 test, and
˙
˙
Qhk=2(47) and Ehk=2(47) from the H12
37110
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
˙
2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00120
Fmt 4701
Sfmt 4725
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.086
ER08JN16.087
ER08JN16.088
4.2.3.3 Heat pump only operates at
high (k=2) compressor capacity at
temperature Tj and its capacity is greater
than the building heating load, BL(Tj)
If the H1C2 test described in section
3.6.3 and Table 12 of this appendix is
not conducted, set CDh (k=2) equal to
asabaliauskas on DSK3SPTVN1PROD with RULES
Determine the low temperature cutout factor, d′(Tj), using Equation 4.2.3–
3.
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
Calculate HSPF using Equation 4.2–1.
Evaluate the space heating capacity,
˙
˙
where Qhk=1(62) and Ehk=1(62) are
˙
determined from the H01 test, Qhk=1(47)
˙
and Ehk=1(47) are determined from the
H11 test, and all four quantities are
calculated as specified in section 3.7 of
this appendix.
˙
Qhk=1(Tj), and electrical power
˙
consumption, Ehk=1(Tj), of the heat
pump when operating at minimum
compressor speed and outdoor
temperature Tj using
4.2.4.1 Steady-state space heating
capacity when operating at minimum
compressor speed is greater than or
equal to the building heating load at
˙
temperature Tj, Qhk=1(Tj ≥BL(Tj).
Evaluate the Equation 4.2–1 quantities
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00121
Fmt 4701
Sfmt 4700
outdoor temperature Tj and the
intermediate compressor speed used
during the section 3.6.4 H2V test of this
appendix using
˙
˙
Equation 4.2.4–3 Qhk=v(Tj = Qhk=v (35)
+ MQ*(Tj ¥ 35)
˙
˙
Equation 4.2.4–4 Ehk=v(Tj = Ehk=v (35) +
ME * (Tj ¥ 35)
˙
˙
where Qhk=v(35) and Ehk=v(35) are
determined from the H2V test and
calculated as specified in section 3.9 of
this appendix. Approximate the slopes
of the k=v intermediate speed heating
capacity and electrical power input
curves, MQ and ME, as follows:
E:\FR\FM\08JNR2.SGM
ER08JN16.090
asabaliauskas on DSK3SPTVN1PROD with RULES
Evaluate the space heating capacity,
˙
Qhk=2(Tj), and electrical power
˙
consumption, Ehk=2(Tj), of the heat
pump when operating at full
compressor speed and outdoor
temperature Tj by solving Equations
4.2.2–3 and 4.2.2–4, respectively, for
k=2. Determine the Equation 4.2.2–3
˙
and 4.2.2–4 quantities Qhk=2(47) and
˙
Ehk=2(47) from the H12 test and the
calculations specified in section 3.7 of
˙
this appendix. Determine Qhk=2(35) and
˙
Ehk=2(35) from the H22 test and the
calculations specified in section 3.9 of
this appendix or, if the H22 test is not
conducted, by conducting the
calculations specified in section 3.6.4 of
˙
this appendix. Determine Qhk=2(17) and
˙
Ehk=2(17) from the H32 test and the
calculations specified in section 3.10 of
this appendix. Calculate the space
˙
heating capacity, Qhk=v(Tj), and
˙
electrical power consumption, Ehk=v(Tj),
of the heat pump when operating at
08JNR2
ER08JN16.089
4.2.4 Additional Steps for Calculating
the HSPF of a Heat Pump Having a
Variable-Speed Compressor
37111
37112
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
as specified in section 4.2.3.1 of this
appendix. Except now use Equations
˙
4.2.4–1 and 4.2.4–2 to evaluate Qhk=1(Tj)
˙
and Ehk=1(Tj), respectively, and replace
section 4.2.3.1 references to ‘‘low
capacity’’ and section 3.6.3 of this
appendix with ‘‘minimum speed’’ and
section 3.6.4 of this appendix. Also, the
last sentence of section 4.2.3.1 of this
appendix does not apply.
4.2.4.2 Heat pump operates at an
intermediate compressor speed (k=i) in
order to match the building heating load
˙
at a temperature Tj, Qhk=1(Tj) 2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00122
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.091
ER08JN16.092
ER08JN16.093
For each temperature bin where the
heat pump operates at an intermediate
Where:
T3 = the outdoor temperature at which the
heat pump, when operating at minimum
compressor speed, provides a space
heating capacity that is equal to the
˙
building load (Qhk=1(T3) = BL(T3)), °F.
Determine T3 by equating Equations
4.2.4–1 and 4.2–2 and solving for
outdoor temperature.
asabaliauskas on DSK3SPTVN1PROD with RULES
˙
Qhk=i(Tj) = BL(Tj), the space heating capacity
delivered by the unit in matching the
building load at temperature (Tj), Btu/h.
The matching occurs with the heat pump
operating at compressor speed k=i.
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
˙
at temperature Tj, BL(Tj) ≥Qhk=2(Tj). Evaluate
the Equation 4.2–1 quantities
nominal temperature of the air leaving the
heat pump condenser coil using,
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00123
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
ER08JN16.096
Ô Ô
where Vs, Vmx, v′n (or vn), and Wn are defined
following Equation 3–1. For each outdoor bin
temperature listed in Table 19, calculate the
a fixed-speed indoor blower or a constant-airvolume-rate indoor blower installed, or a
coil-only system heat pump.
Calculate the space heating capacity and
electrical power of the heat pump without
the heat comfort controller being active as
specified in section 4.2.1 of this appendix
(Equations 4.2.1–4 and 4.2.1–5) for each
outdoor bin temperature, Tj, that is listed in
Table 19. Denote these capacities and
electrical powers by using the subscript ‘‘hp’’
instead of ‘‘h.’’ Calculate the mass flow rate
(expressed in pounds-mass of dry air per
hour) and the specific heat of the indoor air
(expressed in Btu/lbmda · °F) from the results
of the H1 test using:
ER08JN16.095
building load (i.e., is delayed until a second
stage call from the indoor thermostat). With
a heat comfort controller, resistive heating
can occur even though the heat pump
condenser has adequate capacity to meet the
building load (i.e., both on during a first stage
call from the indoor thermostat). As a result,
the outdoor temperature where the heat
pump compressor no longer cycles (i.e., starts
to run continuously), will be lower than if
the heat pump did not have the heat comfort
controller.
4.2.5.1 Blower coil system heat pump
having a heat comfort controller: Additional
steps for calculating the HSPF of a heat pump
having a single-speed compressor and either
08JNR2
ER08JN16.094
as specified in section 4.2.3.4 of this
appendix with the understanding that
˙
˙
Qhk=2(Tj) and Ehk=2(Tj) correspond to full
compressor speed operation and are derived
from the results of the specified section 3.6.4
tests of this appendix.
4.2.5 Heat Pumps Having a Heat Comfort
Controller
Heat pumps having heat comfort
controllers, when set to maintain a typical
minimum air delivery temperature, will
cause the heat pump condenser to operate
less because of a greater contribution from
the resistive elements. With a conventional
heat pump, resistive heating is only initiated
if the heat pump condenser cannot meet the
ER08JN16.097
requirements for calculating COPhk=i(Tj). For
each temperature bin where T3 >Tj >Tvh,
4.2.4.3 Heat pump must operate
continuously at full (k=2) compressor speed
asabaliauskas on DSK3SPTVN1PROD with RULES
For multiple-split heat pumps (only), the
following procedures supersede the above
37113
37114
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
determined according to section 3.1.9 of this
˙
˙
appendix), determine Qh(Tj) and Eh(Tj) as
specified in section 4.2.1 of this appendix
˙
˙
˙
˙
(i.e., Qh(Tj) = Qhp(Tj) and Ehp(Tj) = Ehp(Tj)).
Note: Even though To(Tj) ≥Tcc, resistive
heating may be required; evaluate Equation
4.2.1–2 for all bins.
Case 2. For outdoor bin temperatures
˙
where To(Tj) > Tcc, determine Qh(Tj) and
˙
˙
˙
˙
˙
Eh(Tj) using Qh(Tj) = Qhp(Tj) + QCC(Tj) Eh(Tj)
˙
˙
= Ehp(Tj) + ECC(Tj)
where:
Note: Even though To(Tj) 2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00124
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.100
ER08JN16.099
ER08JN16.098
asabaliauskas on DSK3SPTVN1PROD with RULES
ER08JN16.101
Evaluate eh(Tj)/N, RH(Tj)/N, X(Tj), PLFj,
and d(Tj) as specified in section 4.2.1 of this
appendix with the exception of replacing
references to the H1C test and section 3.6.1
of this appendix with the H1C1 test and
section 3.6.2 of this appendix. For each bin
calculation, use the space heating capacity
and electrical power from Case 1 or Case 2,
whichever applies.
ER08JN16.102
Evaluate eh(Tj/N), RH(Tj)/N, X(Tj), PLFj,
and d(Tj) as specified in section 4.2.1 of this
appendix. For each bin calculation, use the
space heating capacity and electrical power
from Case 1 or Case 2, whichever applies.
Case 1. For outdoor bin temperatures
where To(Tj) is equal to or greater than TCC
(the maximum supply temperature
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37115
heat pump condenser coil when operating at
low capacity using,
Repeat the above calculations to determine
˙
the mass flow rate (mdak=2) and the specific
heat of the indoor air (Cp,dak=2) when
operating at high capacity by using the
results of the H12 test. For each outdoor bin
temperature listed in Table 19, calculate the
nominal temperature of the air leaving the
heat pump condenser coil when operating at
high capacity using,
Evaluate eh(Tj)/N, RH(Tj)/N, Xk=1(Tj), and/
or Xk=2(Tj), PLFj, and d′(Tj) or d″(Tj) as
specified in section 4.2.3.1. 4.2.3.2, 4.2.3.3, or
4.2.3.4 of this appendix, whichever applies,
for each temperature bin. To evaluate these
quantities, use the low-capacity space
heating capacity and the low-capacity
electrical power from Case 1 or Case 2,
whichever applies; use the high-capacity
space heating capacity and the high-capacity
electrical power from Case 3 or Case 4,
whichever applies.
Case 1. For outdoor bin temperatures
where Tok=1(Tj) is equal to or greater than TCC
(the maximum supply temperature
determined according to section 3.1.9 of this
˙
˙
appendix), determine Qhk=1(Tj) and Ehk=1(Tj)
as specified in section 4.2.3 of this appendix
˙
˙
˙
(i.e., Qhk=1(Tj) = Qhpk=1(Tj) and Ehk=1(Tj) =
˙
Ehpk=1(Tj).
Note: Even though Tok=1(Tj) ≥TCC, resistive
heating may be required; evaluate RH(Tj)/N
for all bins.
Case 2. For outdoor bin temperatures
˙
where Tok=1(Tj)
temperature listed in Table 19, calculate the
nominal temperature of the air leaving the
01:07 Jun 08, 2016
Jkt 238001
PO 00000
Frm 00125
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.106
ER08JN16.104
ER08JN16.105
VerDate Sep<11>2014
ER08JN16.103
asabaliauskas on DSK3SPTVN1PROD with RULES
ER08JN16.107
Ô Ô
where Vs, Vmx, v′n (or vn), and Wn are defined
following Equation 3–1. For each outdoor bin
37116
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
˙
heating load at temperature Tj, Qhk=1(Tj) ≥
BL(Tj)., and the heat pump permits low
compressor capacity at Tj.
Evaluate the quantities
using Eqs. 4.2.3–1 and 4.2.3–2, respectively.
Determine the equation inputs Xk=1(Tj), PLFj,
and d′(Tj) as specified in section 4.2.3.1 of
this appendix. In calculating the part load
factor, PLFj, use the low-capacity cyclic-
degradation coefficient CDh, [or equivalently,
CDh(k = 1)] determined in accordance with
section 3.6.6 of this appendix.
4.2.6.2 Heat pump only operates at high (k
= 2) compressor capacity at temperature Tj
and its capacity is greater than or equal to the
˙
building heating load, BL(Tj) < Qhk=2(Tj).
Evaluate the quantities
as specified in section 4.2.3.3 of this
appendix. Determine the equation inputs
Xk=2(Tj), PLFj, and d′(Tj) as specified in
section 4.2.3.3 of this appendix. In
calculating the part load factor, PLFj, use the
high-capacity cyclic-degradation coefficient,
CDh(k = 2) determined in accordance with
section 3.6.6 of this appendix.
4.2.6.3 Heat pump only operates at high (k
= 3) compressor capacity at temperature Tj
and its capacity is greater than or equal to the
˙
building heating load, BL(Tj) ≤ Qhk=3(Tj).
ER08JN16.111
˙
˙
Qhk=3(35) and Ehk=3(35) as specified in
section 3.6.6 of this appendix.
4.2.6.1 Steady-state space heating capacity
when operating at low compressor capacity
is greater than or equal to the building
ER08JN16.112
at high compressor capacity and outdoor
temperature Tj by solving Equations 4.2.2–3
and 4.2.2–4, respectively, for k = 2.
˙
˙
Determine Qhk=1(62) and Ehk=1(62) from the
˙
˙
H01 test, Qhk=1(47) and Ehk=1(47) from the H11
˙
˙
test, and Qhk=2(47) and Ehk=2(47) from the H12
test, evaluated as specified in section 3.7 of
this appendix. Determine the equation input
˙
˙
for Qhk=2(35) and Ehk=2(35) from the H22,
evaluated as specified in section 3.9.1 of this
˙
appendix. Also, determine Qhk=2(17) and
˙
Ehk=2(17) from the H32 test, evaluated as
specified in section 3.10 of this appendix.
c. Evaluate the space heating capacity and
electrical power consumption of the heat
pump when operating at booster compressor
capacity and outdoor temperature Tj using
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00126
Fmt 4701
Sfmt 4725
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.109
ER08JN16.110
capacity and outdoor temperature Tj using
the equations given in section 4.2.3 of this
˙
˙
appendix for Qhk=1(Tj) and Ehk=1(Tj)) In
evaluating the section 4.2.3 equations,
˙
˙
Determine Qhk=1(62) and Ehk=1(62) from the
˙
˙
H01 test, Qhk=1(47) and Ehk=1(47) from the H11
˙
˙
test, and Qhk=2(47) and Ehk=2(47) from the H12
test. Calculate all four quantities as specified
in section 3.7 of this appendix. If, in
accordance with section 3.6.6 of this
appendix, the H31 test is conducted,
˙
˙
calculate Qhk=1(17) and Ehk=1(17) as specified
in section 3.10 of this appendix and
˙
˙
determine Qhk=1(35) and Ehk=1(35) as
specified in section 3.6.6 of this appendix.
b. Evaluate the space heating capacity and
˙
electrical power consumption (Qhk=2(Tj) and
˙
Ehk=2(Tj)) of the heat pump when operating
˙
˙
Determine Qhk=3(17) and Ehk=3(17) from the
˙
˙
H33 test and determine Qhk=2(2) and Ehk=3(2)
from the H43 test. Calculate all four
quantities as specified in section 3.10 of this
appendix. Determine the equation input for
asabaliauskas on DSK3SPTVN1PROD with RULES
heating (also section 4.2.6.8 of this appendix)
in responding to the building load. As
applicable, the manufacturer must supply
information regarding the outdoor
temperature range at which each stage of
compressor capacity is active. As an
informative example, data may be submitted
in this manner: At the low (k = 1) compressor
capacity, the outdoor temperature range of
operation is 40 °F ≤ T ≤ 65 °F; At the high
(k = 2) compressor capacity, the outdoor
temperature range of operation is 20 °F ≤ T
≤ 50 °F; At the booster (k = 3) compressor
capacity, the outdoor temperature range of
operation is ¥20 °F ≤ T ≤ 30 °F.
a. Evaluate the space heating capacity and
electrical power consumption of the heat
pump when operating at low compressor
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37117
where
˙
Xk=3(Tj) = BL(Tj)/Qhk=3(Tj) and PLFj = 1 ¥
CDh(k = 3) * [1 ¥ Xk=3(Tj)
Determine the low temperature cut-out
factor, d′(Tj), using Eq. 4.2.3–3. Use the
booster-capacity cyclic-degradation
coefficient, CDh(k = 3) determined in
accordance with section 3.6.6 of this
appendix.
4.2.6.4 Heat pump alternates between high
(k = 2) and low (k = 1) compressor capacity
to satisfy the building heating load at a
˙
˙
temperature Tj, Qhk=1(Tj) < BL(Tj) < Qhk=2(Tj).
Evaluate the quantities
as specified in section 4.2.3.2 of this
appendix. Determine the equation inputs
Xk=1(Tj), Xk=2(Tj), and d′(Tj) as specified in
section 4.2.3.2 of this appendix.
4.2.6.5 Heat pump alternates between high
(k = 2) and booster (k = 3) compressor
capacity to satisfy the building heating load
˙
at a temperature Tj, Qhk=2(Tj) < BL (Tj) <
˙
Qhk=3(Tj).
and Xk=3(Tj) = Xk=2(Tj) = the heating mode,
booster capacity load factor for temperature
bin j, dimensionless. Determine the low
temperature cut-out factor, d′(Tj), using Eq.
4.2.3–3.
4.2.6.6 Heat pump only operates at low (k
= 1) capacity at temperature Tj and its
capacity is less than the building heating
˙
load, BL(Tj) > Qhk=1(Tj).
where the low temperature cut-out factor,
d′(Tj), is calculated using Eq. 4.2.3–3.
4.2.6.7 Heat pump only operates at high (k
= 2) capacity at temperature Tj and its
capacity is less than the building heating
˙
load, BL(Tj) > Qhk=2(Tj).
Evaluate the quantities
as specified in section 4.2.3.4 of this
appendix. Calculate d″(Tj) using the equation
given in section 4.2.3.4 of this appendix.
4.2.6.8 Heat pump only operates at booster
(k = 3) capacity at temperature Tj and its
capacity is less than the building heating
˙
load, BL(Tj) > Qhk=3(Tj) or the system
converts to using only resistive heating.
where d″(Tj) is calculated as specified in
section 4.2.3.4 of this appendix if the heat
pump is operating at its booster compressor
capacity. If the heat pump system converts to
using only resistive heating at outdoor
temperature Tj, set d′(Tj) equal to zero.
4.2.7 Additional steps for calculating the
HSPF of a heat pump having a single indoor
unit with multiple indoor blowers. The
calculation of the Eq. 4.2–1 quantities eh(Tj)/
N and RH(Tj)/N are evaluated as specified in
the applicable subsection.
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00127
Fmt 4701
Sfmt 4700
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.116
ER08JN16.117
ER08JN16.116
ER08JN16.114
ER08JN16.115
VerDate Sep<11>2014
ER08JN16.113
asabaliauskas on DSK3SPTVN1PROD with RULES
where:
37118
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
section 4.2 of this appendix round the values
off as specified per § 430.23(m) of title 10 of
the Code of Federal Regulations.
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00128
Fmt 4701
Sfmt 4700
For all other outdoor bin temperatures, Tj,
calculate eh(Tj)/N and RHh(Tj)/N as specified
˙
in section 4.2.3.3 of this appendix if Qhk=2(Tj)
> BL(Tj) or as specified in section 4.2.3.4 of
˙
this appendix if Qhk=2(Tj) ≤ BL(Tj)
4.2.7.2 For multiple indoor blower heat
pumps connected to either a single outdoor
unit with a two-capacity compressor or to
two separate single-speed outdoor units of
identical model, calculate the quantities
eh(Tj)/N and RH(Tj)/N as specified in section
4.2.3 of this appendix.
4.3 Calculations of Off-Mode Power
Consumption
For central air conditioners and heat
pumps with a cooling capacity of: Less than
36,000 Btu/h, determine the off mode
represented value, PW,OFF, with the following
equation:
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.119
˙
˙
quantities Qhk=1(35) and Ehk=1(35) as specified
in section 3.6.2 of this appendix. Determine
˙
˙
Qhk=2(35) and Ehk=2(35) from the H22 frost
accumulation test as calculated according to
section 3.9.1 of this appendix. Determine the
˙
˙
quantities Qhk=1(17) and Ehk=1(17) from the
˙
˙
H31 test, and Qhk=2(17) and Ehk=2(17) from the
H32 test. Evaluate all four quantities
according to section 3.10 of this appendix.
Refer to section 3.6.2 and Table 11 of this
appendix for additional information on the
referenced laboratory tests.
b. Determine the heating mode cyclic
degradation coefficient, CDh, as per sections
3.6.2 and 3.8 to 3.8.1 of this appendix. Assign
this same value to CDh(k = 2).
c. Except for using the above values of
˙
˙
˙
˙
Qhk=1(Tj), Ehk=1(Tj), Qhk=2(Tj), Ehk=2(Tj), CDh,
and CDh(k = 2), calculate the quantities
eh(Tj)/N as specified in section 4.2.3.1 of this
˙
appendix for cases where Qhk=1(Tj) ≥ BL(Tj).
4.4 Rounding of SEER and HSPF for
Reporting Purposes
After calculating SEER according to section
4.1 of this appendix and HSPF according to
asabaliauskas on DSK3SPTVN1PROD with RULES
4.2.7.1 For multiple indoor blower heat
pumps that are connected to a singular,
single-speed outdoor unit:
a. Calculate the space heating capacity,
˙
Qhk=1(Tj), and electrical power consumption,
˙
Ehk=1(Tj), of the heat pump when operating at
the heating minimum air volume rate and
outdoor temperature Tj using Eqs. 4.2.2–3
and 4.2.2–4, respectively. Use these same
equations to calculate the space heating
˙
capacity, Qhk=2(Tj) and electrical power
˙
consumption, Ehk=2(Tj), of the test unit when
operating at the heating full-load air volume
rate and outdoor temperature Tj. In
evaluating Eqs. 4.2.2–3 and 4.2.2– 4,
˙
determine the quantities Qhk=1(47) and
˙
Ehk=1(47) from the H11 test; determine
˙
˙
Qhk=2(47) and Ehk=2(47) from the H12 test.
Evaluate all four quantities according to
section 3.7 of this appendix. Determine the
TABLE 21—REPRESENTATIVE COOLING
AND HEATING LOAD HOURS FOR
EACH GENERALIZED CLIMATIC REGION
Climatic region
I .................................
VerDate Sep<11>2014
Cooling
load
hours
CLHR
Heating
load
hours
HLHR
2,400
23:36 Jun 07, 2016
TABLE 21—REPRESENTATIVE COOLING
AND HEATING LOAD HOURS FOR
EACH GENERALIZED CLIMATIC REGION—Continued
Jkt 238001
750
Climatic region
II ................................
PO 00000
Frm 00129
Fmt 4701
Cooling
load
hours
CLHR
1,800
Sfmt 4700
Heating
load
hours
HLHR
1,250
37119
TABLE 21—REPRESENTATIVE COOLING
AND HEATING LOAD HOURS FOR
EACH GENERALIZED CLIMATIC REGION—Continued
Climatic region
III ...............................
E:\FR\FM\08JNR2.SGM
08JNR2
Cooling
load
hours
CLHR
1,200
Heating
load
hours
HLHR
1,750
ER08JN16.120
asabaliauskas on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
37120
Federal Register / Vol. 81, No. 110 / Wednesday, June 8, 2016 / Rules and Regulations
TABLE 21—REPRESENTATIVE COOLING
AND HEATING LOAD HOURS FOR
EACH GENERALIZED CLIMATIC REGION—Continued
Cooling
load
hours
CLHR
Climatic region
IV ..............................
Rating Values ...........
TABLE 21—REPRESENTATIVE COOLING
AND HEATING LOAD HOURS FOR
EACH GENERALIZED CLIMATIC REGION—Continued
Heating
load
hours
HLHR
800
1,000
2,250
2,080
Heating
load
hours
HLHR
Cooling
load
hours
CLHR
Climatic region
V ...............................
VI ..............................
4.5 Calculations of the SHR, which should
be computed for different equipment
configurations and test conditions specified
in Table 22.
400
200
2,750
2,750
TABLE 22—APPLICABLE TEST CONDITIONS FOR CALCULATION OF THE SENSIBLE HEAT RATIO
Reference
table No. of
Appendix M
Equipment configuration
Units Having a Single-Speed Compressor and a Fixed-Speed Indoor blower, a Constant Air Volume Rate Indoor blower, or No
Indoor blower.
Units Having a Single-Speed Compressor That Meet the section
3.2.2.1 Indoor Unit Requirements.
Units Having a Two-Capacity Compressor .......................................
Units Having a Variable-Speed Compressor .....................................
SHR computation
with results from
Computed values
4
B Test .................................
SHR(B)
5
B2 and B1 Tests ................
SHR(B1), SHR(B2)
6
7
B2 and B1 Tests ................
B2 and B1 Tests ................
SHR(B1), SHR(B2)
SHR(B1), SHR(B2)
The SHR is defined and calculated as
follows:
Where both the total and sensible cooling
capacities are determined from the same
cooling mode test and calculated from data
collected over the same 30-minute data
collection interval.
4.6 Calculations of the Energy Efficiency
Ratio (EER). Calculate the energy efficiency
ratio using,
˙
˙
where Qck(T) and Eck(T) are the space cooling
capacity and electrical power consumption
determined from the 30-minute data
collection interval of the same steady-state
wet coil cooling mode test and calculated as
specified in section 3.3 of this appendix. Add
the letter identification for each steady-state
test as a subscript (e.g., EERA2) to differentiate
among the resulting EER values.
ER08JN16.122
BILLING CODE 6450–01–P
VerDate Sep<11>2014
23:36 Jun 07, 2016
Jkt 238001
PO 00000
Frm 00130
Fmt 4701
Sfmt 9990
E:\FR\FM\08JNR2.SGM
08JNR2
ER08JN16.121
asabaliauskas on DSK3SPTVN1PROD with RULES
[FR Doc. 2016–12592 Filed 6–7–16; 8:45 am]
Agencies
[Federal Register Volume 81, Number 110 (Wednesday, June 8, 2016)]
[Rules and Regulations]
[Pages 36991-37120]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2016-12592]
[[Page 36991]]
Vol. 81
Wednesday,
No. 110
June 8, 2016
Part II
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 430
Energy Conservation Program: Test Procedures for Central Air
Conditioners and Heat Pumps; Final Rule
Federal Register / Vol. 81 , No. 110 / Wednesday, June 8, 2016 /
Rules and Regulations
[[Page 36992]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[Docket No. EERE-2009-BT-TP-0004]
RIN 1904-AB94
Energy Conservation Program: Test Procedures for Central Air
Conditioners and Heat Pumps
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: On November 9, 2015, the U.S. Department of Energy (DOE)
issued a supplemental notice of proposed rulemaking (SNOPR) to amend
the test procedure for central air conditioners and heat pumps. That
proposed rulemaking serves as the basis for the final rule. The final
rule, in addition to satisfying the agency's obligation to periodically
review its test procedures for covered equipment, amends specific
certification, compliance, and enforcement provisions related to this
product. In the final rule DOE makes the following amendments to the
current test procedure: a new basic model definition as it pertains to
central air conditioners and heat pumps and revised requirements for
represented values; revised alternative efficiency determination
methods; termination of active waivers and interim waivers; procedures
to determine off mode power consumption; changes to the test procedure
that would improve test repeatability and reduce test burden; and
clarifications to ambiguous sections of the test procedure intended
also to improve test repeatability and reproducibility Some of these
amendments also include incorporation by reference of updated industry
standards.
DATES: The effective date of this rule is July 8, 2016. The final rule
changes will be mandatory for representations of efficiency starting
December 5, 2016. The incorporation by reference of certain
publications listed in this rule was approved by the Director of the
Federal Register on July 8, 2016.
ADDRESSES: The docket, which includes Federal Register notices, public
meeting attendee lists and transcripts, comments, and other supporting
documents/materials, is available for review at regulations.gov. All
documents in the docket are listed in the regulations.gov index.
However, some documents listed in the index, such as those containing
information that is exempt from public disclosure, may not be publicly
available.
A link to the docket Web page can be found at:
www1.eere.energy.gov/buildings/appliance_standards/rulemaking.aspx/ruleid/72. This Web page will contain a link to the docket for this
notice on the regulations.gov site. The regulations.gov Web page will
contain simple instructions on how to access all documents, including
public comments, in the docket.
For further information on how to review the docket, contact Ms.
Brenda Edwards at (202) 586-2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Ashley Armstrong, U.S. Department of
Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Program, EE-2J, 1000 Independence Avenue SW., Washington,
DC 20585-0121. Telephone: (202) 586-6590. Email:
Ashley.Armstrong@ee.doe.gov.
Johanna Jochum, U.S. Department of Energy, Office of the General
Counsel, GC-33, 1000 Independence Avenue SW., Washington, DC, 20585-
0121. Telephone: (202) 287-6307. Email: Johanna.Jochum@hq.doe.gov.
For further information on how to submit a comment, review other
public comments and the docket, or participate in the public meeting,
contact Ms. Brenda Edwards at (202) 586-2945 or by email:
Brenda.Edwards@ee.doe.gov.
SUPPLEMENTARY INFORMATION: This final rule incorporates by reference
into part 430 specific sections, figures, and tables in the following
industry standards:
(1) ANSI/AHRI 210/240-2008 with Addenda 1 and 2, (``AHRI 210/240-
2008''): 2008 Standard for Performance Rating of Unitary Air-
Conditioning & Air-Source Heat Pump Equipment, ANSI approved 27 October
2011;
(2) ANSI/AHRI 1230-2010 with Addendum 2, (``AHRI 1230-2010''): 2010
Standard for Performance Rating of Variable Refrigerant Flow (VRF)
Multi-Split Air-Conditioning and Heat Pump Equipment, ANSI approved
August 2, 2010;
Copies of AHRI 210/240-2008 and AHRI 1230-2010 can be obtained from
the Air-Conditioning, Heating, and Refrigeration Institute, 2111 Wilson
Boulevard, Suite 500, Arlington, VA 22201, USA, 703-524-8800, or by
going to https://www.ahrinet.org/site/686/Standards/HVACR-Industry-Standards/Search-Standards .
(3) ANSI/ASHRAE 23.1-2010, (``ASHRAE 23.1-2010''): Methods of
Testing for Rating the Performance of Positive Displacement Refrigerant
Compressors and Condensing Units that Operate at Subcritical
Temperatures of the Refrigerant, ANSI approved January 28, 2010;
(4) ANSI/ASHRAE Standard 37-2009, (``ANSI/ASHRAE 37-2009''),
Methods of Testing for Rating Electrically Driven Unitary Air-
Conditioning and Heat Pump Equipment, ANSI approved June 25, 2009;
(5) ANSI/ASHRAE 41.1-2013, (``ANSI/ASHRAE 41.1-2013''): Standard
Method for Temperature Measurement, ANSI approved January 30, 2013;
(6) ANSI/ASHRAE 41.6-2014, (``ASHRAE 41.6-2014''): Standard Method
for Humidity Measurement, ANSI approved July 3, 2014;
(7) ANSI/ASHRAE 41.9-2011, (``ASHRAE 41.9-2011''): Standard Methods
for Volatile-Refrigerant Mass Flow Measurements Using Calorimeters,
ANSI approved February 3, 2011
(8) ANSI/ASHRAE 116-2010, (``ASHRAE 116-2010''): Methods of Testing
for Rating Seasonal Efficiency of Unitary Air Conditioners and Heat
Pumps, ANSI approved February 24, 2010.
(9) ANSI/ASHRAE 41.2-1987 (Reaffirmed 1992), (``ASHRAE 41.2-1987
(RA 1992)''): ``Standard Methods for Laboratory Airflow Measurement'',
ANSI approved October 1, 1987.
Copies of ASHRAE 23.1-2010, ANSI/ASHRAE 37-2009, ANSI/ASHRAE 41.1-
2013, ASHRAE 41.6-2014, ASHRAE 41.9-2011, ASHRAE 116-2010, and ASHRAE
41.2-1987 (RA 1992) can be purchased from ASHRAE's Web site at https://
www.ashrae.org/resources--publications.
(10) ANSI/AMCA 210-2007, ANSI/ASHRAE 51-2007, (``AMCA 210-2007'')
Laboratory Methods of Testing Fans for Certified Aerodynamic
Performance Rating, August 17, 2007;
Copies of AMCA 210-2007 can be purchased from AMCA's Web site at
https://www.amca.org/store/index.php.
For a further discussion of these standards, see section IV.N.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Summary of the Final Rule
III. Discussion
A. Definitions, Testing, Represented Values, and Compliance of
Basic Models of Central Air Conditioners and Heat Pumps
1. Basic Model Definition
2. Additional Definitions
3. Determination of Represented Values
4. Compliance with Federal (National or Regional) Standards
5. Certification Reports
6. Represented Values
7. Product-Specific Enforcement Provisions
B. Alternative Efficiency Determination Methods
1. General Background
2. Terminology
[[Page 36993]]
3. Elimination of the Pre-Approval Requirement
4. AEDM Validation
5. AEDM Verification Testing
6. Failure to Meet Certified Represented Values
7. Action Following a Determination of Noncompliance
8. AEDM for Off Mode
C. Waiver Procedures
1. Air-to-Water Heat Pumps and Air Conditioners
2. Clarification of the Test Procedure Pertaining to Multi-
Circuit Products
3. Clarification of the Test Procedure Pertaining to Multi-
Blower Products
D. Measurement of Off Mode Power Consumption
1. Test Temperatures
2. Calculation and Weighting of P1 and P2
3. Time Delay Credit and Removal of Calculations for Off Mode
Energy Consumption and Annual Performance Factor
4. Impacts on Product Reliability
5. Off Mode Power Consumption for Intelligent Compressor Heat
Control
6. Off Mode Test Voltage for Dual-Voltage Units
7. Off Mode Test Tolerance
8. Organization of Off Mode Test Procedure
9. Certification
10. Compliance Dates
E. Test Repeatability Improvement and Test Burden Reduction
1. Indoor Fan Speed Settings for Blower Coil or Single-Package
Systems
2. Air Volume Rate Adjustment for Coil-Only Systems
3. Requirements for the Refrigerant Lines and Mass Flow Meter
4. Outdoor Room Temperature Variation
5. Method of Measuring Inlet Air Temperature on the Outdoor Side
6. Requirements for the Air Sampling Device
7. Variation in Maximum Compressor Speed with Outdoor
Temperature
8. Refrigerant Charging Requirements
9. Alternative Arrangement for Thermal Loss Prevention for
Cyclic Tests
10. Test Unit Voltage Supply
11. Coefficient of Cyclic Degradation
12. Break-in Periods Prior to Testing
13. Industry Standards that are Incorporated by Reference
14. References to ASHRAE 116-1995 (RA 2005)
15. Additional Changes Based on AHRI 210/240-Draft
16. Damping Pressure Transducer Signals
17. Clarify Inputs for the Demand Defrost Credit Equation
18. Improving Test Consistency Associated with Indoor Unit Air
Inlet Geometry
F. Clarification of Test Procedure Provisions
1. Manufacturer Consultation
2. Incorporation by Reference of AHRI 1230-2010
3. Replacement of the Informative Guidance Table for Using the
Federal Test Procedure
4. Clarifying the Definition of a Mini-Split System
5. Clarifying the Definition of a Multi-Split System
6. Clarifying the Housing for Uncased Coil
7. Test Procedure Reprint
G. Additional Comments from Interested Parties
1. Wet Coil Performance
2. Barometric Pressure Correction
3. Inlet Screen
H. Compliance with other Energy Policy and Conservation Act
Requirements
1. Dates
2. Measured Energy Use
3. Test Burden
4. Potential Incorporation of International Electrotechnical
Commission Standard 62301 and International Electrotechnical
Commission Standard 62087
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under the Treasury and General Government
Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by Reference
V. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III, Part B \1\ of the Energy Policy and Conservation Act of
1975 (``EPCA'' or ``the Act''), Public Law 94-163 (42 U.S.C. 6291-6309,
as codified) sets forth a variety of provisions designed to improve
energy efficiency and established the Energy Conservation Program for
Consumer Products Other Than Automobiles.\2\ These products include
single-phase central air conditioners and central air conditioning heat
pumps \3\ with rated cooling capacities less than 65,000 British
thermal units per hour (Btu/h), which are the focus of this Final Rule.
(42 U.S.C. 6291(1)-(2), (21) and 6292(a)(3))
---------------------------------------------------------------------------
\1\ For editorial reasons, Part B was codified as Part A in the
U.S. Code.
\2\ All references to EPCA in this document refer to the statute
as amended through the Energy Efficiency Improvement Act of 2015,
Public Law 114-11 (Apr. 30, 2015).
\3\ Where this notice uses the term ``CAC/HP'', they are in
reference specifically to central air conditioners and heat pumps as
defined by EPCA.
---------------------------------------------------------------------------
Under EPCA, DOE's energy conservation program generally consists of
four parts: (1) testing; (2) labeling; (3) Federal energy conservation
standards; and (4) certification and enforcement. The testing
requirements consist of test procedures that manufacturers of covered
products must use as the basis for: (1) certifying to DOE that their
products comply with applicable energy conservation standards adopted
pursuant to EPCA, and (2) making other representations about the
efficiency of those products. (42 U.S.C. 6293(c); 42 U.S.C. 6295(s))
Similarly, DOE must use these test procedures to determine whether
covered products comply with any relevant standards promulgated under
EPCA. (42 U.S.C. 6295(s))
EPCA sets forth criteria and procedures DOE must follow when
prescribing or amending test procedures for covered products. (42
U.S.C. 6293(b)(3)) EPCA provides, in relevant part, that any test
procedures prescribed or amended under this section shall be reasonably
designed to produce test results which measure the energy efficiency,
energy use, or estimated annual operating cost of a covered product
during a representative average use cycle or period of use, and shall
not be unduly burdensome to conduct. Id.
In addition, if DOE determines that a test procedure amendment is
warranted, it must publish proposed test procedures and offer the
public an opportunity to present oral and written comments on them. (42
U.S.C. 6293(b)(2)) Finally, in any rulemaking to amend a test
procedure, DOE must determine to what extent, if any, the amended test
procedure would alter the measured energy efficiency of any covered
product as determined under the existing test procedure. (42 U.S.C.
6293(e)(1))
The Energy Independence and Security Act of 2007 (EISA 2007),
Public Law 110-140, amended EPCA to require that, at least once every 7
years, DOE must review test procedures for all covered products and
either amend the test procedures (if the Secretary determines that
amended test procedures would more accurately or fully comply with the
requirements of 42 U.S.C. 6293(b)(3)) or publish a notice in the
Federal Register of any determination not to amend a test procedure.
(42 U.S.C. 6293(b)(1)(A))
DOE last published a test procedure final rule for central air
conditioners and heat pumps on October 22, 2007. 72 FR 59906. The
existing DOE test method for central air conditioners and heat pumps
adopted pursuant to that rule appears at Title 10 of the Code of
Federal Regulations (CFR) Part 430, Subpart B, Appendix M (``Uniform
Test Method for Measuring the Energy Consumption of Central Air
Conditioners and Heat Pumps''). That
[[Page 36994]]
procedure establishes the currently permitted means for determining
energy efficiency and annual energy consumption of these products. The
amendments in this final rule will not alter the measured efficiency of
central air conditioners and heat pumps.
EISA 2007 also established that the Department's test procedures
for all covered products must account for standby mode and off mode
energy consumption. (42 U.S.C. 6295(gg)(2)(A)) For central air
conditioners and heat pumps, standby mode is incorporated into the SEER
metric, while off mode power consumption is separately regulated. This
final rule includes modifications relevant to the determination of both
SEER (including standby mode) and off mode power consumption.
10 CFR 430.27 allows manufacturers to submit an application for an
interim waiver and/or a petition for a waiver granting relief from
adhering to the test procedure requirements found under 10 CFR part
430, subpart B, appendix M. For those waivers that are active, however,
10 CFR 430.27(l) requires DOE to amend its regulations so as to
eliminate any need for the continuation of such waivers. To this end,
this final rule amends the test procedure concerning several waivers.
B. Background
This final rule addresses proposals and comments from three
separate rulemakings, two guidance documents, and two working groups:
(1) proposals for off mode test procedures made in earlier notices as
part of this rulemaking (Docket No. EERE-2009-BT-TP-0004); (2)
proposals regarding alternative efficiency determination methods
(AEDMs) (Docket No. EERE-2011-BT-TP-0024); (3) the recommendations of
the regional standards enforcement Working Group (Regional Standards
Enforcement Working Group) (Docket No. EERE-2011-BT-CE-0077); (4) a
draft guidance document related to testing and rating split systems
with blower coil units (Docket No. EERE-2014-BT-GUID-0033); (5) a draft
guidance document that deals with selecting units for testing, rating,
and certifying split-system combinations, including discussion of basic
models and of condensing units and evaporator coils sold separately for
replacement installation (Docket No. EERE-2014-BT-GUID-0032); and (6)
stakeholder comments from a request for information regarding energy
conservation standards as well as the recommendations of the central
air conditioner and heat pump energy conservation standards Working
Group (CAC/HP ECS Working Group) (Docket No. EERE-2014-BT-STD-0048).
1. Proposals for Off Mode Test Procedures
DOE's initial proposals for estimating off mode power consumption
in the test procedure for central air conditioners and heat pumps were
shared with the public in a notice of proposed rulemaking published in
the Federal Register on June 2, 2010 (June 2010 NOPR; 75 FR 31224) and
at a public meeting at DOE headquarters in Washington, DC, on June 11,
2010 (Public Meeting Transcript, Doc. ID. EERE-2009-BT-TP-0004-0005).
Subsequently, DOE published a supplemental notice of proposed
rulemaking (SNOPR) on April 1, 2011, in response to comments received
on the June 2010 NOPR and due to the results of additional laboratory
testing conducted by DOE. (April 2011 SNOPR) 76 FR 18105, 18127. DOE
received additional comments in response to the April 2011 SNOPR and
proposed an amended version of the off mode procedure that addressed
those comments in a second SNOPR on October 24, 2011 (October 2011
SNOPR). 76 FR 65616. DOE received additional comments during the
comment period of the October 24, 2011 SNOPR and the subsequent
extended comment period. 76 FR 79135.
Between the April 2011 and October 2011 SNOPRs, DOE published a
direct final rule (DFR) in the Federal Register on June 27, 2011, that
set forth amended energy conservation standards for central air
conditioners and central air conditioning heat pumps, including a new
standard for off mode electrical power consumption. (June 2011 DFR) 76
FR 37408. Under the June 2011 DFR, central air conditioning and heat
pump units manufactured on or after January 1, 2015, would be subject
to the published standard for off mode electrical power consumption. 10
CFR 430.32(c)(6). However, DOE has issued an enforcement policy
statement regarding off mode standards for central air conditioners and
central air conditioning heat pumps \4\ (July 2014 Enforcement Policy
Statement) specifying that DOE will not assert civil penalty authority
for violation of the off mode standard until 180 days following
publication of a final rule establishing a test method for measuring
off mode electrical power consumption.
---------------------------------------------------------------------------
\4\ Available at: https://energy.gov/sites/prod/files/2014/07/f17/Enforcement%20Policy%20Statement%20-%20cac%20off%20mode.pdf
(Last accessed March 30, 2015.)
---------------------------------------------------------------------------
2. Proposals for AEDMs
DOE also pursued, in a request for information (RFI) published on
April 18, 2011, (AEDM RFI) (76 FR 21673) and a NOPR published on May
31, 2012, (AEDM NOPR) (77 FR 32038) revisions to its existing
alternative efficiency determination methods (AEDM) and alternative
rating methods (ARM) requirements to improve the approach by which
manufacturers may use modeling techniques as the basis to certify
consumer products and commercial and industrial equipment covered under
EPCA. DOE also published a final rule regarding AEDM requirements for
commercial and industrial equipment only (Commercial Equipment AEDM
FR). 78 FR 79579 (Dec. 31, 2013).
3. Regional Enforcement Standards Working Group and Guidance Documents
On June 13, 2014, DOE published a notice of intent to form a
working group to negotiate enforcement of regional standards for
central air conditioners and requested nominations from parties
interested in serving as members of the Regional Standards Enforcement
Working Group. 79 FR 33870. On July 16, 2014, the Department published
a notice of membership announcing the eighteen nominees that were
selected to serve as members of the Regional Standards Enforcement
Working Group, in addition to two members from Appliance Standards and
Rulemaking Federal Advisory Committee (ASRAC), and one DOE
representative. 79 FR 41456. The Regional Standards Enforcement Working
Group identified a number of issues related to testing and
certification that are being addressed in this rule. In addition, all
nongovernmental participants of the Regional Standards Enforcement
Working Group approved the final report contingent on upon the issuance
of the final guidance on Docket No. EERE-2014-BT-GUID-0032 0032 and
Docket No. EERE-2014-BT-GUID-0033 consistent with the understanding of
the Regional Standards Enforcement Working Group as set forth in its
recommendations. (Docket No. EERE-2011-BT-CE-0077-0070, Attachment) The
amendments in this final rule supplant the August 19 and 20, 2014 draft
guidance documents; DOE will not finalize the draft guidance documents
and instead has provided any necessary clarity through this final rule.
DOE believes the amendments are consistent with the intent of the
Regional Standards Enforcement Working Group.
[[Page 36995]]
4. Energy Conservation Standards and Working Group
On November 5, 2014, DOE published a request for information for
energy conservation standards (ECS) for central air conditioners and
heat pumps (November 2014 ECS RFI). 79 FR 65603. In response, several
stakeholders provided comments suggesting that DOE amend the current
test procedure.
On July 14, 2015, DOE published a notice of intent to establish the
central air conditioners and heat pumps working group (CAC/HP ECS
Working Group) to negotiate a notice of proposed rulemaking (NOPR) for
energy conservation standards. 80 FR 40938. This working group was
established under ASRAC. Ultimately, the CAC/HP ECS Working Group
consisted of 15 members, including one member from ASRAC and one DOE
representative. On January 19, 2016, the CAC/HP ECS Working Group
successfully reached consensus on amended energy conservation standards
and the associated compliance date for certain product classes of
central air conditioners and central air conditioning heat pumps, on
limited aspects of the proposed, amended test procedure appendix M1,
and also on a handful of other miscellaneous issues related to the
standards rulemaking as well as to this test procedure final rule.
(ASRAC Working Group Term Sheet, Docket No. EERE-2014-BT-STD-0048, No.
0076)
5. Current Rulemaking
Prior to the conclusion of the CAC/HP ECS Working Group, on
November 9, 2015, DOE published a third supplemental notice of proposed
rulemaking (November 2015 SNOPR) for the test procedure of central air
conditioners and heat pumps. 80 FR 69278. The SNOPR responded to
relevant comments from the guidance documents and rulemaking dockets
discussed in this section.
This final rule addresses certain comments received in response to
the November 2015 SNOPR. Some of the provisions of the SNOPR,
particularly related to changes proposed for appendix M1, will be
addressed in a separate notice. This final rule, along with the
separate final rule addressing Appendix M1, will fulfill DOE's
obligation to periodically review its test procedures under 42 U.S.C.
6293(b)(1)(A).
II. Summary of the Final Rule
This final rule clarifies aspects of DOE's test procedure for
central air conditioners and heat pumps to improve the consistency and
accuracy of the results generated when using that procedure. The rule
primarily clarifies how to test for compliance with the current energy
conservation standards. The rule also amends certain certification,
compliance, and enforcement provisions. While the changes adopted in
this rulemaking may impact test burden in certain cases, as discussed
in section III.H.3, DOE has determined that this final rule will not
change the measured energy efficiency of central air conditioners and
heat pumps when compared to the current test procedure. Any proposed
amendments that would change the measured energy efficiency will be
addressed as part of the new appendix M1, in a separate notice, which
will be used in conjunction with amended standards.
DOE revises the basic model definition, adds additional definitions
for clarity, makes certain revisions to the testing requirements for
determination of represented values, adds certain certification
reporting requirements, revises requirements for determination of
represented values, and adds product-specific enforcement provisions.
DOE updates requirements for Alternative Rating Methods (ARMs) used
to determine performance metrics for central air conditioners and heat
pumps based on the regulations for Alternative Efficiency Determination
Methods (AEDMs) that are used to estimate performance for commercial
HVAC equipment. Specifically, for central air conditioners and heat
pumps, DOE makes the following amendments: (1) Revising the
nomenclature regarding ARMs; (2) rescinding DOE's pre-approval of an
ARM prior to use; (3) creating AEDM validation requirements; (4)
revising the AEDM verification testing process; (5) specifying actions
a manufacturer could take following a verification test failure; and
(6) clarifying consequences to manufacturers for invalid represented
values.
DOE revises the test procedure such that tests of multi-circuit
products, triple-capacity northern heat pump products, and multi-blower
products can be performed without the need of an interim waiver or a
waiver. Existing interim waivers and waivers for these products, as
applicable, regarding these products will terminate 180 days after
publication of this final rule.
DOE also terminates the existing waivers for air-to-water heat pump
products integrated with domestic water heating because, as discussed
in section III.C.1, DOE has determined that these waivers are not valid
because they do not provide a method for measurement of the efficiency
metrics used to determine compliance with applicable standards.
DOE adopts test methods and calculations for off mode power that do
not impact the measured energy with respect to the current energy
conservation standard. Specifically, the adopted test procedure
includes the following:
(1) Provision of an option to conduct the off mode tests in a
temperature-controlled room rather than a psychrometric room;
(2) Elimination of ambient condition requirements for units whose
off mode power consumption can be measured without control of ambient
temperature;
(3) Alteration of the off mode multiplier for modulated
compressors;
(4) Addition of requirements on the heating season off mode power
measurement for units having a crankcase heater whose controls cycle or
vary crankcase heater power over time;
(5) Clarification of test sample set-up and power measurement
testing methodology and components;
(6) Addition of requirement to eliminate the time delay effect on
the off mode power measurement; and
(7) Elimination of the condition where P2 is equal to zero in the
off mode power consumption calculation.
In this final rule DOE also improves the repeatability/
reproducibility and reduces the test burden of the test procedure.
Specifically, DOE amends the following:
(1) Clarification of fan speed settings;
(2) Clarification of insulation requirements for refrigerant lines
and addition of a requirement for insulating mass flow meters;
(3) Addition of a requirement to demonstrate inlet air temperature
uniformity for the outdoor unit using thermocouples;
(4) Addition of a requirement that outdoor air conditions be
measured using sensors measuring the air captured by the air sampling
device(s) rather than the temperature sensors located in the air stream
approaching the inlets;
(5) Addition of a requirement that the air sampling device and the
tubing that transfers the collected air to the dry bulb temperature
sensor be at least two inches from the test chamber floor, and a
requirement that humidity measurements be based on dry bulb temperature
measurements made at the same location as the corresponding wet bulb
temperature measurements used to determine humidity;
[[Page 36996]]
(6) Clarification of maximum speed for variable-speed compressors;
(7) Addition of requirements that improve consistency of
refrigerant charging procedures;
(8) Allowance of an alternative arrangement for cyclic tests to
replace the currently-required damper in the inlet portion of the
indoor air ductwork for single-package ducted units;
(9) Clarification of the proper supply voltage for testing;
(10) Revision of the determination of the coefficient of cyclic
degradation (CD);
(11) Option for a break-in period of up to 20 hours;
(12) Update of references to industry standards where appropriate;
(13) Inclusion of information from the draft AHRI 210/240;
(14) Addition of provisions regarding damping of pressure
transducer signals to avoid exceeding test operating tolerances due to
high frequency fluctuations;
(15) Clarification of inputs for the demand defrost credit
equation; and
(16) Improvement of test consistency associated with indoor unit
air inlet geometry.
DOE also provides additional detail and specificity with respect to
several provisions. Specifically, DOE adds reference to an industry
standard for testing variable refrigerant flow multi-split systems;
replaces the informative guidance table for using the test procedure;
clarifies the definition of multi-split systems; clarifies the
definition of mini-split systems, which DOE now calls multi-head mini-
split systems; and clarifies the housing for uncased coils.
Lastly, DOE addresses comments received from stakeholders in
response to the November 2015 SNOPR that were unrelated to any of DOE's
proposals. Specifically, this includes the following:
(1) Water condensation metric;
(2) Barometric pressure correction ; and
(3) Inlet screen.
Given the difficulty of writing amendatory instructions to
implement the many small changes throughout appendix M, DOE has
provided a full re-print of appendix M in the regulatory text of this
final rule.
DOE revises the test procedure in this final rule as reflected in
the revised Appendix M to Subpart B of 10 CFR part 430 effective on
July 8, 2016. The amended test procedure is mandatory for
representations of efficiency as of December 5, 2016.
III. Discussion
This final rule amends the test procedure for central air
conditioners and heat pumps in appendix M to subpart B of Part 430 and
adds new product-specific certification and enforcement provisions in
10 CFR 429.12, 429.16, 429.70, and 429.134. The rule also amends
certain definitions found in 10 CFR 430.2 and updates certain materials
incorporated by reference in 10 CFR 430.3.
In response to the November 2015 SNOPR, the following 25 interested
parties submitted written comments: Advanced Distributor Products LLC;
Air-Conditioning, Heating, and Refrigeration Institute (AHRI); American
Council for an Energy Efficient Economy (ACEEE); Appliance Standards
Awareness Project (ASAP); First Co.; Goodman Global, Inc.; Heating, Air
Conditioning & Refrigeration Distributors International (HARDI);
Ingersoll Rand; Johnson Controls Inc. (JCI); Lennox International Inc;
LG Electronics U.S.A., Inc; Mitsubishi Electric Cooling & Heating;
Natural Resources Defense Council (NRDC); Nortek Global HVAC; Northwest
Energy Efficiency Alliance (NEEA); Northwest Power and Conservation
Council (NPCC); Pacific Gas and Electric Company (PG&E); Rheem
Manufacturing Company (Rheem); San Diego Gas and Electric Company
(SDG&E); Southern California Edison (SCE); Southern California Gas
Company (SCG); Unico, Inc.; United Refrigeration, Inc. (URI); United
Technologies Climate, Controls & Security (UTC), also known as Carrier
Corporation. NEEA and NPCC submitted a joint comment. PG&E, SDG&E, SCG,
and SCE, hereafter referred to as the California Investor-Owned
Utilities (California IOUs), also submitted a joint comment. ACEEE,
ASAP, and NRDC, hereafter referred to as the Efficiency Advocates, also
submitted a joint comment.
Interested parties provided comments on a range of issues,
including those DOE identified in the November 2015 SNOPR, as well as
several other pertinent issues related to DOE's proposal. Commenters
also offered thoughts on further opportunities to improve the clarity
of the test procedure. These issues, as well as DOE's responses to them
and the resulting changes to DOE's proposal, are discussed in the
subsequent sections. A parenthetical reference at the end of a comment
quotation or paraphrase provides the location of the item in the public
record.\5\
---------------------------------------------------------------------------
\5\ The parenthetical reference provides a reference for
information located in the docket of DOE's rulemaking to amend the
test procedures for central air conditioners and heat pumps. (Docket
No. EERE-2009-BT-TP-0004, which is maintained at https://www.regulations.gov/#!docketDetail;D=EERE-2009-BT-TP-0004). The
references are arranged as follows: (commenter name, comment docket
ID number, page of that document).
---------------------------------------------------------------------------
A. Definitions, Testing, Represented Values, and Compliance of Basic
Models of Central Air Conditioners and Heat Pumps
On August 19 and 20, 2014, DOE issued two draft guidance documents
regarding the test procedure for central air conditioners and heat
pumps. One guidance document dealt with testing and rating split
systems with blower coil indoor units (Docket No. EERE-2014-BT-GUID-
0033); and the other dealt more generally with selecting units for
testing, rating, and certifying split-system combinations, including
discussion of basic models and of condensing units and evaporator coils
sold separately for replacement installation (Docket No. EERE-2014-BT-
GUID-0032). The comments in response to these draft guidance documents
were discussed in the November 2015 SNOPR. DOE proposed changes to the
substance of the draft guidance that reflects the comments received as
well as the recommendations of the Regional Standards Enforcement
Working Group (Docket No. EERE-2011-BT-CE-0077-0070, Attachment). DOE
makes additional modifications in this final rule in response to
comment on the November 2015 SNOPR as well as the recommendations of
the CAC/HP ECS Working Group (Docket No. Docket No. EERE-2014-BT-STD-
0048, No. 76). The adopted changes supplant the two draft guidance
documents; DOE will not finalize the draft guidance documents and has
instead provided any necessary clarity through this final rule.
1. Basic Model Definition
In the November 2015 SNOPR, DOE proposed modifying its basic model
definition for central air conditioners and heat pumps. 80 FR at 69282-
4 (Nov. 9, 2015). Under DOE's proposal, manufacturers could consider
each individual model/combination its own basic model, or manufacturers
could assign all individual models of the same single-package system or
all individual combinations using the same model of outdoor unit (for
outdoor unit manufacturers (OUM)) or model of indoor unit (for
independent coil manufacturers (ICM)) to the same basic model. DOE
proposed to further define (for both single-package units and split
systems) the physical characteristics necessary to assign individual
models or
[[Page 36997]]
combinations to the same basic model. 80 FR 69278, 69282-83 (Nov. 9,
2015).
DOE proposed that, if a manufacturer chooses to assign each
individual model or combination to its own basic model, the
manufacturer must test each individual model/combination--and that an
AEDM could not be applied. 80 FR 69278, 69283 (Nov. 9, 2015). If
manufacturers assign all individual combinations of a model of outdoor
unit (for OUMs) or model of indoor unit (for ICMs) to a single basic
model, DOE further proposed that each individual combination within a
basic model must be certified with a rating determined for that
individual combination. However, only one individual combination in
each basic model would have to be tested (see section III.A.3.a), while
the others may be rated using an AEDM. This option reduces testing
burden but increases risk. Specifically, if any one of the combinations
within a basic model fails to meet the applicable standard, then all of
the combinations within the basic model fail, and the entire basic
model must be taken off the market. 80 FR 69278 at 69283 (Nov. 9,
2015).
Comments on these proposals are discussed in the following
sections.
a. Basic Model Framework
The Joint Advocates of ACEEE, NRDC and ASAP (``Joint Advocates'')
supported the proposed changes to the definition of a basic model and
related testing and certification requirements. The Joint Advocates
stated that they believe that the clarified testing requirements would
reduce testing burden on manufacturers. (ACEEE, NRDC and ASAP, No. 72
at p. 1) Nortek supported DOE's proposal that manufacturers would have
a choice in how to assign individual models or combinations to basic
models. (Nortek, No. 58 at p. 3) ADP and Lennox supported the use of
the basic model as the basis for any enforcement action as discussed in
Section III.A.8 (80 FR 69278, 69297 (Nov. 9, 2015)) and the proposed 10
CFR 429. (ADP, No. 59 at p. 7; Lennox, No. 61 at p. 14)
NEEA and NPCC commented that DOE's proposed approach that all
combinations within the basic model are deemed noncompliant if only one
of the combinations within a basic model fails does not align with the
other aspects of DOE's current proposal, in which each and every
combination has its own certified rating. (NEEA and NPCC, No. 64 at p.
2-3)
Carrier/UTC expressed the concern that if one combination amongst
potentially hundreds of combinations rated with a given outdoor unit
fails then the entire basic model will be removed from the market and
claimed that it is excessively punitive. Further, Carrier/UTC
recommended a provision for saving the remaining indoor combinations of
the basic model such as testing the tested combination and one (or
more) other random indoor combinations. Carrier/UTC stated that the de-
listing of the product should be limited to the combination that
failed, not the entire basic model. (Carrier/UTC, No. 62 at pp. 5-6)
NEEA and NPCC further commented that they presume that DOE's
ratings guidance of August 19 and 20, 2014, would also be impacted by a
requirement to rate all outdoor and indoor unit combinations and the
proposal with regard to testing-derived versus AEDM-derived ratings.
They asserted that the proposal would seem to require the rating of
both coil-only and blower coil combinations, with the choice of either
using the highest sales volume combination being tested (and all other
combinations rated using an AEDM), or testing each combination as its
own basic model. (NEEA and NPCC, No. 64 at p. 2-3)
In response to NEEA and NPCC, DOE disagrees that DOE cannot make a
determination of compliance on a basic model basis simply because DOE
permits the manufacturer to make different representations for
combinations within a basic model. In response to NEAA, NPCC, and UTC/
Carrier, DOE notes that it developed the proposal for the basic model
framework in an effort to balance manufacturer test burden and risk.
The determination of compliance with the standard is made at the basic
model level, and the manufacturer may choose how to group models into
basic models and whether or not to make use of an AEDM for represented
values of combinations. DOE expects that the individual combinations
grouped into a single basic model would have similarities that would
make validation of one of the individual model/combination's
represented values a strong indication of the accuracy of the
represented values of the other models/combinations--if the represented
values are indeed different. DOE also notes that when manufacturers use
an AEDM and DOE finds an invalid rating, manufacturers can conduct re-
testing to re-certify the individual model/combination, as described in
section 429.70.
DOE also notes that, as stated in the November 2015 SNOPR, this
final rule will supplant DOE's draft ratings guidance documents, which
will not be finalized. Finally, DOE notes in response to NEEA and NPCC
that the basic model framework itself does not determine whether both
coil-only and blower coil combinations must be rated; this is further
discussed in section III.A.3.a. Given the support for the basic model
framework voiced by many of the commenters, DOE adopts the framework as
proposed in the SNOPR.
b. General Definition Comments
AHRI and several manufacturers including UTC/Carrier, ADP, Lennox,
Nortek, and Unico agreed generally with DOE's proposal to modify its
basic model definition. (AHRI, No. 70 at p. 3; UTC/Carrier, No. 62 at
p. 5-6; ADP, No. 59 at p. 7; Lennox, No. 61 at p. 14; Nortek, No. 58 at
p. 3; Unico, No. 63 at p. 4) Rheem recommended that DOE adopt the
industry standard definition for basic model, as defined by AHRI.
(Rheem, No. 69 at p. 4) As described below, several commenters
requested additional modifications to DOE's proposed definitions; these
comments are discussed below, along with revisions to the proposed
definitions.
c. Split Systems Manufactured by OUMs and Single-Package Systems
For split systems manufactured by OUMs and single-package systems,
AHRI, Lennox, Ingersoll Rand, Rheem, and Nortek recommended the removal
of ``the auxiliary refrigeration system components if present (e.g.,
expansion valve) and controls'' from the proposed basic model
definition. Lennox and Nortek commented that adding these components to
the definition can greatly expand the number of basic models. (AHRI,
No. 70 at p. 3; Lennox, No. 61 at p. 4; Ingersoll Rand, No. 65 at p.
11; Rheem, No. 69 at p. 4; Nortek, No. 58 at p. 3) Additionally, Lennox
and Nortek suggested that there would not be a benefit to expanding the
definition of basic model beyond the currently accepted industry
practice as outlined in AHRI's certification program. (Lennox, No. 61
at p. 4; Nortek, No. 58 at p. 3) DOE understands Lennox and Nortek are
referring to the concept of a ``basic model group'' as the term is
described in the AHRI Operations Manual for Unitary Small Air-
Conditioners and Air-Source Heat Pumps, in section 1.5, ``Basic Model
Groups (BMGs).''
After reviewing the comments, DOE acknowledges that while use of
different auxiliary refrigeration system components may impact measured
performance, it may not do so significantly--for example, measurements
made using two different thermostatic expansion valves that both
maintain the same superheat should not be different. In an effort to
balance manufacturer test burden with the
[[Page 36998]]
regulatory needs of the program to establish an appropriate basic model
definition, DOE has not included the phrase ``auxiliary refrigeration
system components if present (e.g., suction accumulator, reversing
valve, expansion valve) and controls'' in the ``basic model''
definition for split systems manufactured by OUMs or for single-package
systems. DOE notes, however, that each manufacturer is responsible for
minor variations in efficiency differences resulting from such changes
in design.
For the definition of a basic model for OUMs, Goodman agreed with
DOE's overall direction. However, Goodman commented that DOE's proposed
definition was too rigid and would not provide enough design
flexibility to manufacturers. Specifically, Goodman cited the
importance of the ability for a manufacturer to vary many aspects of
its outdoor coils (e.g., style and fin depth) and to source components,
such as compressors, from multiple component manufacturers. Goodman
asserted that this flexibility in design would allow manufacturers to
provide combinations that optimize their product offering to consumers,
while still yielding similar performance and therefore meriting
classification under a single basic model. Goodman suggested revised
basic model definitions for split systems manufactured by OUMs and
single-package systems in which the list of parameters affecting
performance (e.g., compressor and outdoor coil properties) that had
been proposed to define a distinct model be instead provided as
guidance for the OUM to consider when deciding whether two variations
of a design should have the same model number. (Goodman, No. 73 at pp.
2-3)
In response to Goodman, DOE recognizes the importance of allowing
manufacturers flexibility in design. DOE agrees with Goodman that, for
instance, using compressors from different compressor manufacturers in
two different models should not require the manufacturer to classify
these models as two separate basic models, if the models can still
reasonably be described as having ``essentially identical
characteristics.'' However, DOE believes that Goodman's suggested
revised definitions, by providing guidance but no requirements, would
allow widely varying characteristics under the same model of outdoor
unit or single-package unit. Rather than moving to definitions that
provide flexibility limited only by guidance, DOE has instead modified
the definitions to allow some design flexibility, while assuring that a
large departure from a given design would require that the OUM
establish a new basic model. In the definitions established in this
final rule for basic model for split systems manufactured by OUMs and
single-package systems, DOE has removed certain requirements proposed
in the November 2015 SNOPR, and added tolerances for the remaining
requirements. Specifically, these modifications from the proposal
include: (1) Establishing a five percent tolerance for compressor
displacement, capacity, and power input; (2) removing requirements for
several outdoor coil parameters; (3) adding a five percent tolerance to
the face area and total fin surface area of the outdoor coil; (4)
adding a ten percent tolerance on outdoor airflow, and (5) for single-
package systems, allowing a ten percent tolerance on indoor airflow and
a twenty percent tolerance on power input to the indoor fan motor.
In the basic model definition proposed in the November 2015 SNOPR
for split systems manufactured by OUMs and single-package systems, DOE
specified that all individual models or combinations in a basic model
must have the same or comparably performing compressor(s) with the
``same displacement rate (volume per time) and same capacity and power
input when tested under the same operating conditions.'' 80 FR 69278,
69341 (Nov. 9, 2015). In order to promote design flexibility, DOE is
adopting less stringent requirements in the basic model definition
amended in this final rule by adding a five percent tolerance to the
displacement rate and capacity and power input. DOE's research suggests
that comparable compressors made by different manufacturers vary by
less than two percent in displacement rate and capacity and power input
when tested under the same conditions. Therefore, DOE believes that a
five percent tolerance allows manufacturers the option to use
comparably performing compressors from different manufacturers in
models without having to classify the models as separate basic models.
Additionally, in the definition established in this final rule, DOE
explains that the tolerances on compressor parameters refer to the
values rated by the compressor manufacturer, not the performance of
individual compressors.
In this final rule, DOE is adopting less stringent requirements for
classifying as comparably performing outdoor coil(s) in the basic model
definition for split systems manufactured by OUMs and single-package
systems. To provide more flexibility to manufacturers, DOE is not
adopting specifications in the basic model definitions for: Coil depth,
fin style (e.g., wavy, louvered), fin density (fins per inch), tube
pattern, tube diameter, tube wall thickness, and tube internal
enhancement. However, DOE has added a five percent tolerance to the
face area and total fin surface area for outdoor coils. This tolerance
on the outdoor coil areas will allow manufacturers to vary their
designs while achieving similar performance, such as adding another row
perpendicular to the airflow direction to the outdoor coil to
compensate for using a more energy-consuming compressor.
Additionally, DOE is adding tolerances to the requirements for
classifying as comparably performing outdoor fan(s) in the basic model
definition for split systems manufactured by OUMs and single-package
systems. DOE is adding a ten percent tolerance on outdoor fan airflow.
DOE believes that this tolerance will allow manufacturers to make
adjustments to the fans, such as increasing the number, diameter, or
design of fan blades, without classifying comparably performing models
as separate basic models.
UTC/Carrier agreed with DOE's proposal to align the basic model
definition with that used by AHRI; however, they asserted that the list
of additional reporting requirements is excessive and burdensome.
Specifically, UTC/Carrier stated that some of these components do not
affect the performance of the system, are considered proprietary, and
need not be reported. Additionally, they stated that some of these
minor components may change due to sourcing availability. UTC/Carrier
recommended that DOE align the basic model exactly with AHRI's basic
model group definition: Compressor model, outdoor coil face area, and
outdoor airflow, and not require any additional data to be reported.
(UTC/Carrier, No. 62 at p. 2)
For split systems manufactured by OUMs, Lennox recommended that the
proposed OUM basic model definition be revised to more closely align
with industry practices and recommended that the definition of outdoor
coil be revised to protect business sensitive information. (Lennox, No.
61 at p. 4) Specifically, Lennox requested that the definition of
outdoor coil-only include the words ``same face area and depth,
style.'' Lennox suggested that DOE remove the remaining specification
requirements for outdoor coils so that this sensitive business
information could not be made available to the public and industry
competitors through a FOIA request. (Lennox, No. 61 at pp. 3-4)
[[Page 36999]]
DOE acknowledges the importance of avoiding disclosure of
proprietary or sensitive business information; however, in the November
2015 SNOPR DOE did not propose any additional certification
requirements or supplemental test instruction reporting that would
require disclosure of these parameters about which UTC/Carrier and
Lennox cited concern. 80 FR 69278, 69338-39 (Nov. 9, 2015).
Requirements for reporting are limited to those items listed in section
429.16(e), and mention of a parameter as the basis for distinguishing a
model does not by itself imply that the value of that parameter must be
reported in certification reports. DOE notes that it is not requiring
that manufacturers report the sensitive information such as surface
area or coil depth for which their basic model determinations are made.
In response to UTC/Carrier, DOE recognizes that minor components
may vary in manufacturer designs based on availability from component
manufacturers. However, DOE believes that the tolerances established in
this final rule (as previously discussed) around most of the
requirements in DOE's definition of basic model allow for variation in
component models and manufacturers. DOE also believes that the
requirements included in DOE's definition of basic model are necessary
to ensure units are similar enough to be classified as the same basic
model. DOE also notes that the definition established in this final
rule includes tolerances on the compressor model ratings, outdoor coil
face area, and outdoor airflow; therefore DOE's definition allows more
flexibility for outdoor coil face area and outdoor airflow than does
the definition of a split-system model group in the AHRI Operations
Manual.\6\
---------------------------------------------------------------------------
\6\ AHRI's Operations Manual for Unitary Small Air-Conditioners
and Air-Source Heat Pumps (Includes Mixed-Match Coils) (Rated Below
65,000 Btu/h) Certification Program (AHRI OM 210/240--March 2015).
Available at www.ahrinet.org/App_Content/ahri/files/Certification/OM%20pdfs/USE_OM.pdf (Last accessed March 31, 2016.)
---------------------------------------------------------------------------
In response to Lennox, as previously discussed, DOE has removed
references to fin material, style, or density or tube thickness in the
basic model definition established in this final rule, which will
provide manufacturers with more flexibility in offering a varied
product offering to consumers while limiting the testing burden.
d. Requirements for Independent Coil Manufacturers
Several commenters expressed concern about the impact of the
proposed definition of basic model on ICM test burden. Therefore
comments regarding the ICM basic model definition are addressed in the
context of testing required to determine represented values in section
III.A.3.d.
e. Off-Mode
Revisions to the test procedure as stated in section III.D of this
final rule enable the determination of off mode power consumption,
which reflects the operation of the contributing components: crankcase
heater and low-voltage controls. In the November 2015 SNOPR, DOE
proposed that if individual combinations that are otherwise identical
are offered with multiple options for off mode related components,
manufacturers at a minimum must rate the individual combination with
the crankcase heater and controls which are the most consumptive. Under
this proposal, if a manufacturer wished to also make representations
for less consumptive off mode options for the same individual
combination, the manufacturer could provide separate ratings as long as
the manufacturer differentiated the individual model numbers for these
ratings. These individual combinations would be within the same basic
model. 80 FR 69278, 69284 (Nov. 9, 2015).
In their comments, NEEA and NPCC strongly supported DOE's proposal
to require manufacturers to either rate and certify all combinations
using the most consumptive off-mode power controls and systems, or to
differentiate models they wish to certify with different off-mode power
controls and/or systems with different model numbers, each with its own
certified rating. (NEEA and NPCC, No. 64 at p. 4)
DOE received no other comments on this proposal and adopts it in
this final rule.
f. Central Air Conditioner Definition
In the November 2015 SNOPR, DOE proposed to clarify that a central
air conditioner or central air conditioning heat pump may consist of: A
single-package unit; an outdoor unit and one or more indoor units
(e.g., a single-split or multi-split system); an indoor unit only
(rated as a combination by an ICM with an OUM's outdoor unit); or an
outdoor unit only (with no match, rated by an OUM with the coil
specified in this test procedure). DOE proposed adding these
specifications to the definition of central air conditioner or central
air conditioning heat pump in 10 CFR 430.2. In the certification
reports submitted by OUMs for split systems, DOE proposed that
manufacturers must report the basic model number as well as the
individual model numbers of the indoor unit(s) and the air mover where
applicable. 80 FR 69278, 69284 (Nov. 9, 2015).
Lennox and ADP expressed concern that modifying the CAC/HP
definition to include ``an indoor unit'' only may have significant
unintended consequences with additional regulation now applying to
indoor units. They stated that the indoor unit has no heating or
cooling capability without being installed as a part of the system,
that by itself, it is a component, and that the proposed definition is
factually incorrect and contradicts the DOE's previous position that
they do not have authority to regulate components of air conditioners.
Lennox recommended DOE keep the existing definition. (Lennox, No. 61 at
p. 10; ADP, No. 59 at p. 4)
DOE notes that the modification of the CAC/HP definition does not
change the scope of DOE's product coverage and is in line with the
current certification requirements for CAC/HP. Specifically, ICMs are
currently responsible for testing and certifying models of indoor units
they manufacture as part of a split-system combination. DOE received no
other comment on this topic. For these reasons, DOE is adopting the
CAC/HP definition as proposed.
2. Additional Definitions
In the November 2015 SNOPR, in order to specify differences in the
proposed basic model definition for ICMs and OUMs, DOE proposed
definitions for an ICM and an OUM. With respect to any given basic
model, a manufacturer could be an ICM or an OUM. 80 FR 69278, 69284
(Nov. 9, 2015).
DOE also proposed to define variable refrigerant flow (VRF) systems
that are single-phase and less than 65,000 Btu/h as a kind of multi-
split central air conditioner and central air conditioning heat pump
system. Id.
Additionally, DOE proposed to clarify several other definitions
currently in 10 CFR 430.2 with minor wording changes and move them to
10 CFR 430, Subpart B, Appendix M. DOE also proposed to remove entirely
the definitions for ``condenser-evaporator coil combination'' and
``coil family,'' as those terms no longer appear in the proposed
regulations. Id.
DOE did not receive any comments on these definitions and related
changes and adopts the proposals in this final rule.
a. Indoor Unit
In the November 2015 SNOPR, DOE proposed modifying the definition
of indoor unit to read as follows: ``indoor unit transfers heat between
the refrigerant and the indoor air, and
[[Page 37000]]
consists of an indoor coil and casing and may include a cooling mode
expansion device and/or an air moving device.'' 80 FR 69278, 69284
(Nov. 9, 2015).
Goodman commented that the definition for indoor unit does not
fully account for the range of indoor units sold in the market.
Specifically, Goodman stated that including the casing in the proposed
indoor unit definition is inconsistent with many industry offerings.
Goodman also suggested a new definition for indoor unit. (Goodman, No.
73 at p. 3-5)
AHRI and Nortek proposed a definition for indoor units that does
not include casing and/or an expansion device. AHRI and Nortek
expressed concern that the uncased coil would no longer be within the
scope of regulation, which could open the doors for a loophole in the
regulation, or that manufacturers would not be able to list an uncased
coil with an outdoor unit, resulting in an illegal installation. AHRI
and Nortek proposed definitions for uncased coil, cased coil, and
service coil. (AHRI, No. 70 at p. 8; Nortek, No. 58 at p. 3-4).
Further, AHRI stated that DOE should make clear that service coils will
not be rated in the future. (AHRI, No. 70 at p. 8)
UTC/Carrier commented that the exclusion of uncased coils from DOE
certification represents a significant loophole as uncased coils are
often installed in various new construction scenarios and should be
certified. According to UTC/Carrier, DOE should further define the
replacement component service coils that are used only when the current
coils fail and are considered service parts and, thus, should not be
certified to DOE; the treatment of uncased coils in commerce by
manufacturers as service-only is problematic. (UTC/Carrier, No. 62 at
p. 3)
JCI commented that, while some manufacturers use uncased service
coils, others supply service coils with casings on them. In addition,
JCI commented that not all uncased coils are service coils. According
to JCI, there are product families of uncased coils very often sold for
new construction installations, or installation of new A/C systems in
the northern parts of the United States. For example, JCI noted that
often in the northern United States, a new home may be constructed with
only a furnace for heating and no cooling, and that cooling may be
added later by installing an uncased coil into the ductwork itself. JCI
commented that the uncased coil market is a vital part of the northern
U.S. market, and uncased coils need to be allowed to be rated as valid
matches with a basic outdoor model. (JCI, No. 66 at p. 12-13). JCI also
suggested definitions for uncased coil, cased coil, service coil, and
indoor unit. (JCI, No. 66 at p. 13)
The California IOUs requested that DOE allow manufacturers to rate
uncased coils with outdoor condensing units. They reported that
California Building Energy Efficiency Standards (Title 24) define the
replacement of any component containing refrigerant to be a system
alteration requiring verification of refrigerant charge and airflow
through the coil. (see California Code of Regulations, Title 24, Part
1, Article 1, Section 150.2(b)(1)F) The California IOUs stated that the
replacement of an indoor coil is an alteration whether the coil is
cased or uncased. DOE asserted that DOE's proposal to define uncased
coils as repair parts and to not require them to be part of a rated
model would create a compliance problem for contractors in California
because without ratings, the energy efficiency of the system with an
uncased coil is not known. The California IOUs stated that in
applications where the existing coil is removed from the existing case
and replaced with a new coil, which is then connected to a new outdoor
unit, the efficiency rating is required to meet Title 24. Therefore,
the California IOUs requested that DOE allow ratings of combinations
having uncased indoor coils so that compliance with Title 24 can be
verified. (California IOUs, No. 67 at p. 2)
ADP and Lennox commented that they understand the intent of
excluding uncased coils is to differentiate between indoor units used
for legacy replacements and new installations, but believe that DOE's
proposal would create a significant loophole. ADP and Lennox commented
that uncased coils are used for new installations in a significant
number of markets in the upper Midwest of the United States where a
long tradition of skilled sheet metal workers exists. Additionally,
they asserted that Canada is a predominately uncased coil market and
relies on manufacturer ratings that have been certified with DOE and
AHRI. Instead, ADP suggests that DOE require replacement coils not
subject to certification to carry a different model number than those
sold for installation as a part of new, certified systems. (ADP, No. 59
at p. 4-5; Lennox, No. 61 at p. 10)
After consideration of the comments that uncased coils may be used
for new installations and that the exclusion of uncased coils from the
indoor unit definition could result in a significant loophole, DOE is
adopting a revised definition for an indoor unit such that it ``may or
may not include . . . (e) external cabinetry''. To distinguish newly
installed cased and uncased coils from replacement cased and uncased
coils, DOE has added a definition for service coils and explicitly
excluded them in the indoor unit definition.
Indoor unit means part of a split-system air conditioner or heat
pump that includes (a) an arrangement of refrigerant-to-air heat
transfer coil(s) for transfer of heat between the refrigerant and the
indoor air and (b) a condensate drain pan, and may or may not include
(c) sheet metal or plastic parts not part of external cabinetry to
direct/route airflow over the coil(s), (d) a cooling mode expansion
device, (e) external cabinetry, and (f) an integrated indoor blower
(i.e. a device to move air including its associated motor). A separate
designated air mover that may be a furnace or a modular blower (as
defined in Appendix AA to the subpart) may be considered to be part of
the indoor unit. A service coil is not an indoor unit.
Service coil means an arrangement of refrigerant-to-air heat
transfer coil(s) and condensate drain pan that may or may not include
sheet metal or plastic parts to direct/route airflow over the coil(s),
external cabinetry, and/or a cooling mode expansion device, and is sold
exclusively to replace an uncased coil or cased coil that has already
been placed into service and is labeled accordingly.
DOE also acknowledges the benefit of including definitions for both
cased and uncased coils, and adopts the following definitions:
Cased coil means a coil-only indoor unit with external cabinetry.
Uncased coil means a coil-only indoor unit without external
cabinetry.
In the November 2015 SNOPR, DOE proposed to specify that if the
indoor unit does not ship with a cooling mode expansion device, the
system should be tested using the device as specified in the
installation instructions provided with the indoor unit, or if no
device is specified, using a thermostatic expansion valve (TXV). 80 FR
69278, 69284 (Nov. 9, 2015).
Goodman commented that DOE should not assume the use of TXV if a
metering (expansion) device is not specified by the manufacturer.
Goodman commented that the majority of systems installed today use
fixed orifice rather than TXV expansion devices. (Goodman, No. 73 at p.
3-5)
DOE agrees that many product offerings use fixed orifice or piston
expansion devices as standard equipment and that it may be more
suitable to use a fixed orifice or piston
[[Page 37001]]
device if there are no detailed instructions provided in installation
instructions regarding selection of an expansion device. This is
because a system installed in the field without such instructions may
very well perform poorly if an optimized device is not selected.
Because a TXV generally is likely to provide better performance over a
range of operating conditions, DOE believes the use of a fixed orifice
is more consistent with this potential for poor field performance.
Therefore, DOE is modifying its proposal and requiring instead that a
fixed orifice or piston expansion device be used if the installation
instructions do not specify a metering (expansion) device.
b. Blower Coil and Coil-Only Indoor Units
In the November 2015 SNOPR, DOE proposed definitions for blower
coil indoor unit and coil-only indoor unit. The motivation was to
simplify the description of the test requirements by referring to
blower coil units instead of units ``with an indoor fan installed'' and
to coil-only units instead of units ``without an indoor fan
installed''.
Blower coil indoor unit means the indoor unit of a split-system
central air conditioner or heat pump that includes a refrigerant-to-air
heat exchanger coil, may include a cooling-mode expansion device, and
includes either an indoor blower housed with the coil or a separate
designated air mover such as a furnace or a modular blower (as defined
in Appendix AA).
Blower coil system refers to a split system that includes one or
more blower coil indoor units.
Coil-only indoor unit means the indoor unit of a split-system
central air conditioner or heat pump that includes a refrigerant-to-air
heat exchanger coil and may include a cooling-mode expansion device,
but does not include an indoor blower housed with the coil, and does
not include a separate designated air mover such as a furnace or a
modular blower (as defined in Appendix AA). A coil-only indoor unit is
designed to use a separately-installed furnace or a modular blower for
indoor air movement.
Coil-only system refers to a system that includes one or more coil-
only indoor units. 80 FR 69278, 69286 (Nov. 9, 2015).
ADP and UTC/Carrier agreed with the proposed definitions for blower
coil and coil-only indoor units. (ADP, No. 59 at p. 6; UTC/Carrier, No.
62 at p. 3) Lennox agreed with the proposed definitions with the
exceptions noted in other sections. (Lennox, No. 61 at p. 13) Unico
agreed with the coil-only indoor definition, except recommended
removing the word ``modular'' as there is no definition. Unico
commented that the blower can be anywhere in the system. (Unico, No. 63
at p. 2) JCI suggested definitions for air handler, blower coil, and
coil-only. (JCI, No. 66 at p. 13)
Rheem commented that the proposed definitions for blower coil and
coil-only indoor units exclude the customary practice in the Northwest
United States where an uncased coil is installed in a plenum for space-
constrained installations. Rheem stated that under DOE's proposal, a
certified rating for this system configuration would no longer be
available to consumers. Rheem noted that there are building inspectors
who require an AHRI or DOE certified combination including the
evaporator coil for replacements. (Rheem, No. 69 at p. 5)
DOE acknowledges that by excluding indoor units without a casing,
the customary practice identified by Rheem would not be included. As
noted in the previous section, DOE has addressed this by expanding the
indoor unit definition to include units which may or may not have
external cabinetry. The blower coil and coil-only indoor unit
definitions then build on this updated indoor unit definition. Further,
DOE has removed, from both the blower coil and coil-only indoor unit
definitions, language redundant with the indoor unit definition and is
adopting amended definitions:
In response to Unico's comment regarding ``modular'', the
definition explicitly refers to the definition of ``modular blower'' in
appendix AA. In response to JCI's comment requesting a definition for
``air handler'', DOE feels that this is not necessary because there are
few distinctions in the test procedure between test requirements for
blower coil indoor units that are air handlers (as defined by JCI) and
blower coil indoor units that are not. In cases where a distinction is
needed, the regulatory language adequately provides the distinction,
for example in section 3.13.1.d, ``blower coil split systems for which
a furnace or a modular blower is the dedicated air mover . . .'', which
refers to blower coil split systems whose indoor units are not ``air
handlers''.
3. Determination of Represented Values
In the November 2015 SNOPR, DOE proposed several regulatory changes
regarding the relationship between represented values and an effective
enforcement plan. The changes are described in the following sections.
a. Single-Split-System Air Conditioners Rated by OUMs
DOE proposed to make changes to 10 CFR 429.16 to revise the testing
and rating requirements for single-split system air conditioners. These
changes were proposed to occur in two phases. In the first phase, prior
to the compliance date of any amended energy conservation standards,
DOE proposed only a slight change to the current requirements.
Specifically, DOE proposed that for single-split system air
conditioners with single speed condensing units, each model of outdoor
unit must be tested with the model of coil-only indoor unit that is
likely to have the largest volume of retail sales with the particular
model of outdoor unit. For split-system air conditioners with other
than single speed condensing units, each model of outdoor unit must
also be tested with the model of coil-only indoor unit likely to have
the largest sales volume unless the model of outdoor unit is sold only
with model(s) of blower coil indoor units, in which case it must be
tested and rated with the model of blower coil indoor unit likely to
have the highest sales volume. However, any other combination may be
rated through testing or use of an AEDM. Therefore, both single speed
and other than single speed systems may be rated with models of both
coil-only or blower coil indoor units, but if the system is sold with a
model of coil-only indoor unit, it must, at a minimum, be tested in
that combination. 80 FR 69278, 69285-86 (Nov. 9, 2015).
In the second phase, DOE anticipated that any amended energy
conservation standards would be based on blower coil ratings.
Therefore, DOE proposed that all single-split-system air conditioner
basic models be tested and rated with the model of blower coil indoor
unit likely to have the largest volume of retail sales with that model
of outdoor unit. Manufacturers would be required to also rate all other
blower coil and coil-only combinations within the basic model but would
be permitted do so through testing or an AEDM. This proposed change
would also be accounted for in the parallel energy conservation
standards rulemaking, and would be contingent upon any proposed amended
standards being based on blower coil ratings. Id.
DOE noted that these proposed testing requirements, when combined
with the proposed definition for basic model, require that each basic
model have at least one rating determined through testing; no basic
model can be rated solely using an AEDM. Id.
[[Page 37002]]
DOE also proposed that in the certification report, manufacturers
state whether each rating is for a coil-only or blower coil
combination. 80 FR 69278, 69286 (Nov. 9, 2015).
Following publication of the November 2015 SNOPR, DOE held meetings
of the CAC/HP ECS Working Group. The CAC/HP ECS Working Group
recommended consensus energy conservation standards based on coil-only
ratings rather than blower coil ratings, making the second phase of
DOE's proposal no longer applicable. Many of the stakeholders who
submitted comments on DOE's proposal were also members of the CAC/HP
ECS Working Group, and as a result, their positions may have changed
over the course of the negotiations. For these reasons, DOE has
included the consensus recommendations of the CAC/HP ECS Working Group
that pertain to DOE's proposal but has not included the comments of
members of the CAC/HP ECS Working Group on the November 2015 SNOPR
where the scope of the Working Group recommendation encompassed the
scope of the comment.
With respect to the coil-only and blower coil requirements, ADP
agreed with the proposed requirements of the first phase approach.
(ADP, No. 59 at p. 5-6;)
JCI agreed with the single speed requirements in Appendix M but did
not agree with DOE's proposed requirement for two-stage units or multi-
stage units to be tested with a coil-only indoor unit, if any coil-only
indoor units are listed with that outdoor unit. JCI recommended that
there should be no change in the current regulatory text for two-stage
or modulating equipment, and asserted that the spirit of the current
regulation is met with blower coils remaining as the highest sales
volume tested combination, even if there are limited loose coil or
coil-only ratings available. (JCI, No. 66 at p. 5)
ADP had concerns that testing the highest sales volume combination
(HSVC) with a blower coil in the second phase (in appendix M1) would
make it more difficult for ICMs to accurately rate their products
because of the added uncertainty of the indoor blower watts and airflow
performance. Under the proposed second phase, with a blower coil indoor
unit as HSVC, the indoor blower watt value is unknown by the ICM,
forcing the ICM to estimate the watts, which introduces additional
uncertainty to ICM ratings. Although ADP and Lennox recognized that
ICMs could test the HSVC blower coil, they considered this to be an
unreasonable testing burden on ICMs. (ADP, No. 59 at p. 5-6) ADP
proposed that DOE require the reporting of indoor watt data, indoor air
volume rates, and indoor air mover settings and require that they be
made publicly available. (ADP, No. 59 at p. 5-6) Unico stated that it
preferred that the HSVC be a coil-only indoor unit so that they would
be able to properly account for the fan power when rating their
products. (Unico, No. 63 at p. 2)
Lennox; the Joint Advocates of ACEEE, NRDC, and ASAP; UTC/Carrier;
Goodman; and Rheem had submitted comments in regard to the two-phase
proposal related to coil-only and blower coil requirements. As noted
previously, these stakeholders were members of the CAC/HP ECS Working
Group, and as such the comments are not included here.
JCI commented that the current language used in Appendix M denoting
the HSVC match cannot be determined with exact statistics and that it
actually inhibits the adoption of new and promising advancements in
product design. (JCI, No. 66 at p. 4) In contrast, Unico commented
that, as an indoor coil manufacturer, it believes it to be important
that the outdoor unit manufacturer continue to test and rate the HSVC,
as this is an integral requirement for their AEDM to maintain accuracy.
(Unico, No. 63 at p. 2)
UTC/Carrier also submitted a comment related to removal of the HSVC
requirement. As noted previously, UTC/Carrier was a member of the CAC/
HP ECS Working Group, and as such the comment is not included here.
In the term sheet, the CAC/HP ECS Working Group recommended that
DOE implement the following requirements for single-split system air
conditioners and suggested some implementing regulatory text:
Every combination distributed in commerce must be rated.
[cir] Every single-stage and two-stage condensing unit distributed
in commerce (other than a condensing unit for a 1-to-1 mini split) must
have at least 1 coil-only rating that is representative of the least
efficient coil distributed in commerce with a particular condensing
unit.
Every condensing unit distributed in commerce must have at
least 1 tested combination.
[cir] For single-stage and two-stage condensing units (other than
condensing units for a 1-to-1 mini split), this must be a coil-only
combination.
All other combinations distributed in commerce for a given
condensing unit may be rated based on the application of an AEDM or
testing in accordance with the applicable sampling plan.
(Docket No. EERE-2014-BT-STD-0048, No. 76, Recommendation #7)
DOE notes that this recommendation is similar to DOE's Phase 1
proposal, as it is based primarily on coil-only values. In particular,
single-stage and two-stage condensing units may not ever have only a
blower coil represented value. The Working Group recommendation is
consistent with ADP and Unico's comments requesting that the tested
combination be a coil-only unit but inconsistent with JCI's request
that two-stage units be tested with a blower coil. Given the
preponderance of stakeholders supporting the recommendation, and the
fact that multi-stage units may be tested and rated with a blower coil,
DOE believes that adopting the Working Group recommendation best
addresses the majority of stakeholder concerns. For these reasons, and
given that there is no longer a need for a second-phase, DOE is
adopting the recommendation in the term sheet, which will become
effective 180 days after publication of this final rule. DOE notes that
while 1-to-1 mini-splits are not expected to have a coil-only
represented value, this exception does not appear explicitly in the
regulatory text. DOE clarifies that since ductless mini-splits are
never distributed in commerce as coil-only units, there is no coil-only
value that would be representative. Therefore these units only require
blower coil represented values. DOE also notes that the Working Group
recommendation that every condensing unit distributed in commerce have
at least one tested combination was based on the premise that
manufacturers would group multiple individual combinations with a
single model of outdoor unit into a basic model, as allowed in the
adopted basic model definition. If manufacturers instead choose to make
every individual combination (using the same model of outdoor unit) a
separate basic model, each individual combination would be required to
be tested. This aligns with the basic model framework discussed in
section III.A.1.a.
DOE also adopts these recommendations for space-constrained split-
system air conditioners given that they are subject to the same test
procedure provisions and sampling plans as non-space-constrained
single-split-system air conditioners.
DOE notes that both the current test procedure and the test
procedure proposed in the November 2015 SNOPR requires that the test
conditions used for testing coil-only units be the same as
[[Page 37003]]
those used for units with single-speed compressors. For example,
section 3.2.1 of the current Appendix M indicates that these tests,
listed in Table 4 of Appendix M as proposed, are, ``. . . for a unit .
. . with no indoor blower installed.'' Because the regulatory approach
finalized in this notice requires that two-stage condensing units have
a coil-only test, DOE has removed ``coil-only units'' from the
description of the units that must be tested using the Table 4 tests.
DOE notes that the CAC/HP ECS Working Group recommendation also
removes the requirement that the tested combination be the HSVC. DOE
believes the Working Group recommendation adequately addresses JCI's
concern about using the highest sales volume as a tested combination,
but is inconsistent with Unico's request that OUMs test and rate the
HSVC. DOE will address this aspect of the recommendation in the
separate notice and has not adopted it in this final rule.
Goodman commented that DOE has not adequately accounted for the
inherent variability and uncertainty existing in the psychrometric test
procedures in determining that the proposed change requiring two-stage
units to be tested as coil-only would not affect the certified values.
Goodman commented that the test methods specified by DOE, AHRI and
ASHRAE have an uncertainty for steady state testing of approximately 6-
8%. Goodman also noted that ISO 16491:2012 Annex B lists several
factors associated with the indoor air enthalpy method that contribute
to uncertainty. Moreover, Table A.3 of ISO 16491:2012 indicates that
for typical cooling capacity methods, relative expanded uncertainty
might be 6.8%. Goodman commented that even at 0.05 SEER or 0.05 EER
below the regional requirements, new test data would therefore either
require the OUM to test additional samples or would cause a
once[hyphen]compliant unit to be marked as non[hyphen]compliant for the
regional standards. (Goodman, No. 73 at p. 17)
In response to Goodman's concern about this change impacting
measured energy use, DOE notes that current regulations require testing
with the evaporator coil that has the largest volume of retail sales
with the particular model of condensing unit. DOE understands that, for
two-stage units, this is typically a coil-only combination since many
homeowners do not replace the furnace at the same time when they
replace their split-system air conditioning system and therefore that
manufacturers should represent two-stage units as coil-only
combinations. At the manufacturer's discretion, the two-stage units
could also be represented as blower-coil combinations. Therefore, DOE
does not believe the adopted requirements for two-stage units will
change the impacted energy use,
b. Split-System Heat Pumps and Space-Constrained Split-System Heat
Pumps
The current requirements for split-system heat pumps in 10 CFR
429.16 require testing a condenser-evaporator coil combination with the
evaporator coil likely to have the largest volume of retail sales with
the particular model of condensing unit.
In the November 2015 SNOPR, DOE proposed to slightly modify the
wording explaining the testing requirement for split-system heat pumps
to refer to the ``evaporator coil'' and condensing unit'' as the
``indoor unit'' and ``outdoor unit'', as the word ``outdoor unit'' is
more appropriate for heat pumps than ``condensing unit''. DOE also
proposed to apply this same test requirement to space-constrained
split-system heat pumps. 80 FR 69278, 69286-87 (Nov. 9, 2015).
DOE received no comment on this proposal, and in this final rule,
DOE adopts the wording modifications. However, in the separate notice
regarding Appendix M1, DOE will consider additional modifications based
on the recommendations of the CAC/HP ECS Working Group with regard to
split-system air conditioners.
c. Multi-Split, Multi-Circuit, and Multi-Head Mini-Split Systems
The current requirements in 10 CFR 429.16(a)(2)(ii) specify that
multi-split systems and mini-split systems designed for installation
with more than one indoor unit be tested using a ``tested combination''
as defined in 10 CFR 430.2.
In the November 2015 SNOPR, DOE proposed a slight modification to
the testing requirements for single-zone-multiple-coil\7\ and multi-
split systems and proposed to add similar requirements for testing
multi-circuit systems (see section III.C.2 for more information about
these systems). DOE also explained that these requirements apply to VRF
systems that are single-phase and less than 65,000 Btu/h. For all
multi-split, multi-circuit, and single-zone-multiple-coil split
systems, DOE proposed that, at a minimum, each model of outdoor unit
must be tested as part of a tested combination (as defined in the CFR)
composed entirely of non-ducted indoor units. For any models of outdoor
units also sold with short-ducted indoor units, DOE proposed a second
``tested combination'' composed entirely of short-ducted indoor units
would be required to be tested. DOE also proposed that a manufacturer
may rate a mixed non-ducted/short-ducted combination as the mean of the
represented values for the tested non-ducted and short-ducted
combinations. 80 FR 69278, 69287 (Nov. 9, 2015).
---------------------------------------------------------------------------
\7\ The November 2015 SNOPR defined a single-zone-multiple-coil
split system as representing a split system that has one outdoor
unit and that has two or more coil-only or blower coil indoor units
connected with a single refrigeration circuit, where the indoor
units operate in unison in response to a single indoor thermostat.
In this final rule, DOE has adopted the term multi-head mini-split
system instead.
---------------------------------------------------------------------------
Under the November 2015 SNOPR proposed definition of basic model,
these three combinations (non-ducted, short-ducted, and mixed) would
represent a single basic model. When certifying the basic model,
manufacturers should report something like ``* * *'' for the indoor
unit model number and report the test sample size as the total of all
the units tested for the basic model, not just the units tested for
each combination. For example, if the manufacturer tests 2 units of a
non-ducted combination and two units of a short-ducted combination, and
also rates a mixed combination, the manufacturer should specify ``4''
as the test sample size for the basic model, while providing the rating
for each combination. DOE also proposed that manufacturers be allowed
to test and rate specific individual combinations as separate basic
models, even if they share the same model of outdoor unit. In this
case, the manufacturer would provide the individual model numbers for
the indoor units rather than stating a generic model, such as ``* *
*''.
DOE also proposed adding a requirement that, for any models of
outdoor units also sold with models of small-duct, high velocity (SDHV)
indoor units, a ``tested combination'' composed entirely of SDHV indoor
units must be used for testing and rating. However, such a system would
be certified as a different basic model. 80 FR 69278, 69287 (Nov. 9,
2015).
In the November 2015 SNOPR, DOE noted that multi-split systems
consisting of a model of outdoor unit paired with models of non-ducted
or short-ducted units should meet the energy conservation standards for
split-system air conditioners or heat pumps, while systems consisting
of a model of outdoor unit paired with models of SDHV indoor units
should meet SDHV standards. DOE also proposed requirements for models
of outdoor units that were rated and distributed in combinations that
span multiple product classes to be tested and certified
[[Page 37004]]
as compliant with the applicable standard for each product class. Even
if a manufacturer would sell a combination including models of both
SDHV and other non-ducted or short-ducted indoor units, DOE proposed
that the manufacturer should not provide a mixed rating for such
combinations. 80 FR 69278, 69287-88 (Nov. 9, 2015).
Use of Term ``Short-Ducted''
DOE received several comments regarding its use of short-ducted
systems as well as requests for low-static and mid-static terminology
and comments regarding conventional ducted systems. Many of these
systems and ESP requirements were recommended as part of the CAC/HP ECS
Working Group term sheet and will be discussed in a separate notice.
In this final rule, DOE has not adopted use of the term short-duct
and instead refers only to ducted units.
Mixed Represented Values for SDHV and Other Indoor Units
Several stakeholders commented on whether they supported
represented values for mixed multi-split systems including models of
both SDHV and non-ducted or ducted indoor units, and if so, how they
should be rated and whether the SDHV or split-system standard would be
most appropriate.
Nortek commented that some manufacturers publish ratings in the
AHRI Directory for SDHV and non-ducted as an average value and that it
is appropriate to maintain this practice for this product as it is for
the mixed (ducted and non-ducted) indoor multi-split ratings. (Nortek,
No. 58 at p. 13)
Unico commented that they publish multi-split ratings for SDHV
indoor units, non-ducted indoor units and a mixture of SDHV and non-
ducted indoor units. The mixed rating is calculated as an average of
the other two, which are based on tests. This is the same procedure
used for ducted (``short-ducted'') and non-ducted indoor units. Unico
requested the same consideration as all other manufacturers that have
mixed (ducted and non-ducted) indoor multi-split ratings. (Unico, No.
63 at p. 3)
UTC/Carrier questioned whether there is any data available on the
frequency of application of mixed SDHV and non-ducted, ducted or short
duct unit systems to determine the need for a separate system rating.
Lacking this data, UTC/Carrier recommended not supporting mixed multi-
split system ratings for these systems. (UTC/Carrier, No. 62 at p. 4)
Goodman agreed that SDHV should not be intermixed with
non[hyphen]ducted or other ducted indoor units, and that SDHV ICMs
should be required to rate and certify such systems based upon the
external static pressure associated with the SDHV indoor units.
(Goodman, No. 73 at p. 13-14)
Unico agreed with DOE that the SDHV test standard is appropriate
for testing the multi-split SDHV indoor units. However, Unico asserted
that, in doing this, it is not necessary to apply a standard for the
mixed indoor combinations since the ratings are based on other ratings
that already meet their appropriate standard. (Unico, No. 63 at p. 3)
NEEA and NPCC supported the rating and certification of systems
that are distributed in combinations that span more than one product
class (such as multi-split and SDHV) and stated that these systems must
be tested and rated so as to meet the standards for all product classes
represented by the various available combinations. NEEA and NPCC
suggested that each class rating be listed separately, in accordance
with the testing and rating requirements for that class, and be so
identified in the ratings documentation. (NEEA and NPCC, No. 64 at p.
4)
After reviewing the comments, DOE has determined that given that
current industry practice includes mixed represented values for SDHV
and other non-ducted or ducted indoor units, DOE will explicitly allow
these mixed represented values based on an average of the represented
values for each of the homogenous indoor systems. DOE has clarified
this in 429.16. As noted in the November 2015 SNOPR, SDHV represented
values must be a separate basic model. Any represented values for a
mixed system including SDHV and another style of unit (non-ducted or
ducted) must be in the same basic model as the SDHV model.
Ability To Test Mixed Systems
Several stakeholders commented on whether they supported having the
ability to test mixed systems (i.e., systems including both non-ducted
and ducted indoor units) using the test procedure rather than using an
average of the other tested systems.
UTC/Carrier did not support mixed system ratings nor test averaging
due to consumer confusion, proliferation of ratings, and too many
permutations. (UTC/Carrier, No. 62 at p. 4) The California IOUs
commented that for all types of split systems, it is important to not
have averaged ratings and cited as an example that, for the California
Building Energy Efficiency Code (Title 24), the rating of the system
being installed is needed to demonstrate compliance. For incentive
programs managed by Energy Efficiency Program Administrators such as
the California IOUs, calculation and tracking of energy savings require
that the installed system be known and its rating is available.
(California IOUs, No. 67 at p. 3)
AHRI and Nortek commented that averaging of ducted and non-ducted
ratings has been a long-standing industry practice. According to AHRI
and Nortek, the kind of indoor ducted unit should be identified as part
of the rating so that the mixed ratings could then be based on ratings
for the specific kinds of indoor units. (AHRI, No. 70 at p. 16; Nortek,
No. 58 at p. 13)
In response to UTC/Carrier, DOE notes that given the test
requirements to make representations for individual combinations other
than the ``tested combination''(as discussed later in this section),
and the limited amount of permutations currently listed in the AHRI
directory, proliferation of represented values is not expected. In
response to the California IOUs, DOE notes that the averaged
represented values are based on represented values for kinds of
individual systems (i.e., ducted or non-ducted). As a result, an
additional averaged represented value does not take away the
availability of non-averaged represented values.
AHRI and Nortek also commented that, in industry practice, multi-
split ratings with mixed indoor unit types are the numerical average of
the ratings for each of the homogeneous indoor systems. They stated
that the most common mixture is ducted and non-ducted indoor units.
They asserted that there is no test procedure that could adequately
test these combinations. (AHRI, No. 70 at p. 16; Nortek, No. 58 at p.
13)
Unico did not support testing mixed multi-split systems and
commented that there is no adequate test procedure. Unico commented
that using a numerical average of the individual (all ducted or all
non-ducted) ratings is the best method to develop a rating for a mixed
multi-split system. (Unico, No. 63 at p. 3)
Rheem commented that manufacturers should be permitted to test
mixed systems instead of using an average to capture the interaction of
the compressor with the multiple styles of indoor units. (Rheem, No. 69
at p. 5)
NEEA and NPCC commented that, given that the rating method for
mixed multi-split systems will almost invariably produce a rating that
is unrelated to how they actually operate in the field, they see no
value in additional testing. However, NEEA and NPCC have no objection
to
[[Page 37005]]
manufacturers testing such systems if the manufacturers believe the
ratings would be better or more reliable with additional testing. (NEEA
and NPCC, No. 64 at p. 4)
DOE acknowledges that testing mixed systems could capture
interactions not captured in an average; however Rheem did not provide
suggestions for how to develop such a test procedure. Given that
several other stakeholders believe there is not currently an adequate
test procedure to do so, DOE declines to add one at this time.
Options for Averaging
Several stakeholders commented on whether they support determining
represented values for mixed systems using other than a straight mean,
such as a weighting by the number of non-ducted or short-ducted units.
Unico did not support weighting mixed multi-split systems. Unico
commented that indoor units are made in various sizes so the number of
indoor units is not indicative of the load split. In addition, Unico
stated that indoor units are designed to provide a range of capacities
so the load split is dependent mostly on the application rather than
the indoor unit size. (Unico, No. 63 at p. 3)
NEAA and NPCC expressed ambivalence regarding the use of weighting
by the number of ducted and non-ducted units in the system. They
asserted that any alignment of the actual performance of such multi-
zone variable capacity systems in the field and their weighted ratings
would be purely accidental. (NEEA and NPCC, No. 64 at p. 4)
Given the lack of interest in weighting mixed systems, DOE will
continue to allow mixed represented values only as a straight average
of two individual systems represented values containing homogenous
kinds of indoor units (i.e., non-ducted, ducted, or SDHV) tested with
the appropriate method of test in the DOE test procedure.
Determining Represented Values for Specific Individual Combinations
Several stakeholders commented on whether DOE's proposed definition
in the June 2010 NOPR for ``tested combination'' would be appropriate
for determining represented values for specific individual
combinations, or whether manufacturers prefer more flexibility, such as
ability to test more than 5 indoor units. See 75 FR 31223, 31231 (June
2, 2010).
UTC/Carrier commented that rating multi-split systems with more
than 5 units is unnecessary, because all manufacturers offer indoor
units with a nominal capacity of up to at least 12,000 BTU/hr. (UTC/
Carrier, No. 62 at p. 5)
Mitsubishi commented that the original intent of the proposed
``tested combination'' definition was to provide variable-speed multi-
split (VSMS) system manufacturers with a method to provide efficiency
and capacity ratings that would be representative of all the
combinations associated with a specific outdoor unit. Mitsubishi stated
that DOE based the ``tested combination'' concept on the fact that the
outdoor unit is the primary driver for efficiency and capacity and that
DOE recognized that, if a manufacturer had ``specific'' combinations
that had higher efficiencies than the ``tested combination,'' then the
manufacturer could test and rate that ``specific'' combination and
enter it into the AHRI VSMS Directory of Certified Products. Mitsubishi
recommended that DOE continue this process because it provides the VSMS
manufacturer with the best opportunity to highlight top-performing
combinations. (Mitsubishi, No. 68 at p. 3)
Unico supported the proposed DOE definition of ``tested
combination'' and stated that there is no need to rate individual
combinations unless the manufacturer chooses to rate all possible
combinations (for example, if a manufacturer has a limited number of
indoor models). Unico commented that single-split systems (one indoor
unit) using the same outdoor unit used for multi-split systems should
continue to be rated individually. (Unico, No. 63 at p. 4)
NEEA and NPCC acknowledged that combinations that might fall
outside the current definition of ``tested combination'' systems do
exist and are installed on a regular basis. The testing burden would be
relatively small, as only the largest-capacity systems are capable of
operating with more than 5 indoor units. (NEEA and NPCC, No. 64 at p.
4)
AHRI and Nortek commented that they do not believe the tested
combination approach is appropriate for rating specific individual
models. (AHRI, No. 70 at p. 16; Nortek, No. 58 at p. 13)
Rheem commented that the benefits of mix match ratings for multi-
split systems are the same as those provided by mix match ratings for
split systems. Rheem stated that consumers expect the ratings provided
by DOE to reflect the operation of the system in their home and
concluded that outdoor units should be rated to the worst case scenario
and manufacturers should use an AEDM to determine the other
combinations of indoor and outdoor units. On the other hand, DOE notes
that Rheem also commented that a configuration that represents the
highest sales volume should be established for multi-split systems.
(Rheem, No. 69 at p. 5)
After reviewing the comments, DOE maintains its proposal to allow
manufacturers to rate individual combinations as additional basic
models beyond the required tested combinations. DOE agrees with Rheem
and Mitsubishi that consumers and utilities often find benefit for
having represented values for a wide variety of combinations that are
available for installation.
DOE also agrees with Unico that single-split systems (one indoor
unit) using the same outdoor unit used for multi-split systems must
continue to be rated individually.
Sample Size
Several stakeholders commented on DOE's request for information and
data on manufacturing and testing variability associated with multi-
split systems that would allow it to understand how a single unit may
be representative of the population and what tolerances would need to
be applied to represented values based on a single unit sample in order
to account for variability.
Lennox commented that multi-split products are subject to the same
type of variability as a conventional unit in areas such as compressor
variation, coil performance variation, charging, airflow, expansion
device, etc. Lennox did not support an allowance for OUM manufacturers
of multi-split products to be rated based on a single unit test while
OUM manufacturers of conventional products are required to test a
minimum of two samples to meet statistical confidence levels. Lennox
asserted that all OUM-manufactured products should be required to meet
the same minimum test requirements. (Lennox, No. 61 at p. 14)
Mitsubishi and Rheem also recommended that the ratings be
established based on the testing of at least two samples. (Mitsubishi,
No. 68 at p. 3; Rheem, No. 69 at p. 6)
The California IOUs commented that, in addition to manufacturing
variances, controls software creates an additional source of
variability in the performance of multi-split systems. The California
IOUs asserted that software drives the performance of these variable
capacity units based on the input from indoor and outdoor sensors. They
stated that, until DOE-vetted data is available for these controls, the
use of results from a single unit test for rating is inadvisable.
(California IOUs, No. 67 at p. 4)
[[Page 37006]]
Unico commented that a single unit test is adequate provided the
manufacturer rates a system conservatively. Specifically, Unico said
that a manufacturer should not be permitted to rate a product directly
using the result of the single test; instead, the manufacturer can
generate a rating from a single test through derating the measured
performance. Unico gave the example that the rated capacity and
efficiency of a system should be at least 95 percent less than the
single test result. If two or more tests are conducted, then Unico
suggested that the rating could be the mean value or less. (Unico, No.
63 at p. 4)
Goodman suggested that, if DOE mandates that ratings for a single
given kind of air conditioner (ducted, non[hyphen]ducted or mixed) be
based on two sample systems, then OUMs should be able to use AEDMs to
rate some of the kinds of systems. Goodman stated that, because many
multi[hyphen]split and multi[hyphen]head mini[hyphen]split systems use
the same indoor products for multiple sizes (e.g., a 2[hyphen]ton
system may use two 1[hyphen]ton indoor units while a 3[hyphen]ton
system may use three of the exact same 1[hyphen]ton indoor units), a
method to use an AEDM should be developed for rating non[hyphen]tested
systems. Goodman gave the example that, if one OUM chose to test two
sample systems of non[hyphen]ducted indoor units, it should be able to
rate ducted and mixed systems based on an AEDM. Goodman asserted that,
if the OUM chose to have a single rating for all combinations of ducted
indoor units, then the AEDM would obviously have to be used to rate the
combination of ducted indoor units with the lowest efficiency rating.
Goodman gave a contrasting example that, if another OUM chose to rate
multiple different combinations of ducted indoor units, then each
combination would be rated using an AEDM. (Goodman, No. 73 at p. 13)
AHRI and Nortek recommended that DOE maintain consistency with its
AEDM approach used in the commercial HVAC equipment such that, at a
minimum, manufacturers would test two low static units and apply the
AEDM to derive ratings for the high static and mixed ratings. (AHRI,
No. 70 at p. 16; Nortek, No. 58 at p. 13)
As previously noted, Rheem stated that outdoor units should be
rated to the worst case scenario and manufacturers should use an AEDM
to determine the other combinations of indoor and outdoor units.
(Rheem, No. 69 at p. 5)
After reviewing the comments, DOE found that commenters did not
provide data on manufacturing and testing variability that would
support DOE moving to a single unit sample approach. In response to
Goodman, AHRI, Nortek, and Rheem, DOE notes that DOE's current
regulations require that represented values for a single kind of system
be based on testing a sample of at least two units representative of
production units. For these reasons, DOE is not moving to a single unit
sample approach and also declines to require only the represented
values of a single kind of system to be based on testing while allowing
other kinds of systems to be represented using an AEDM, given that the
adopted testing requirements do not increase test burden compared to
the current regulations. DOE is allowing use of an AEDM for off-mode,
as discussed in section III.B.8.
Summary
In summary, Table III.2 provides an example of allowable
represented values for multi-split, multi-circuit, and multi-head mini-
split systems.
Table III.2--Example Represented Values for Multi-Split Systems
--------------------------------------------------------------------------------------------------------------------------------------------------------
Non-
Individual model Individual Sample Ducted ducted Mix rep. SDHV rep. Mix rep. Mix rep.
Basic model (outdoor unit) model(s) (indoor size rep. rep. value (D/ value Value value
unit) value value ND) (SDHV/D) (SDHV/ND)
--------------------------------------------------------------------------------------------------------------------------------------------------------
ABC............................. ABC................ ***............... 4 14 15 14.5 ......... .......... ..........
ABC-ND1......................... ABC................ 2-A123; 3-JH746... 2 ......... 17 ......... ......... .......... ..........
ABC-SDHV........................ ABC................ ***............... 6 ......... ......... ......... 11.5 12.75 13.25
--------------------------------------------------------------------------------------------------------------------------------------------------------
d. Basic Models Rated by ICMs
In the November 2015 SNOPR, DOE proposed to require ICMs to test
and provide certified ratings for each model of indoor unit (i.e.,
basic model) with the least-efficient model of outdoor unit with which
it will be paired, where the least-efficient model of outdoor unit is
the outdoor unit in the lowest-SEER combination as certified by the
OUM. If more than one model of outdoor unit (with which the ICM wishes
to rate the model of indoor unit) has the same lowest-SEER rating, the
ICM may select one for testing purposes. ICMs must rate all other
individual combinations of the same model of indoor unit, but may
determine those ratings through testing or use of an AEDM. 80 FR 69278,
69288 (Nov. 9, 2015).
AHRI, ADP, Lennox, Mortex, and First Co. commented that DOE's
proposed changes to the definition of ``basic model'' with respect to
ICMs, along with the proposed requirement to test at least one
combination within each basic model, presents a significant testing
burden to ICMs. (First Co., No. 56 at p. 1; AHRI, No. 70 at p. 3; ADP,
No. 59 at p. 1; Lennox, No. 61 at p. 4) In order to avoid this burden,
AHRI, ADP, Lennox, and Mortex recommended DOE adopt and define the term
``Similarity Group,'' a group of ICM basic models within a defined
range of coil geometries, with performance substantiated by the same
validation test, and require testing of a Similar Group rather than
testing of each basic model. The range of coil geometries within a
Similarity Group would be defined by: face area within 1
square feet (e.g. 2-4, 4-6, etc.), fin material (e.g. aluminum,
copper), fin style (e.g. wavy, louvered), fin density within 1 fin per inch (e.g. 10-12, 13-15, etc.), number of rows, tube
pattern (e.g. 1 x 0.625, 1 x 0.75, etc.), tube size (e.g. outer
diameter for round tube, channel characteristic size for microchannel),
and tube internal enhancement (e.g. smooth or enhanced). (AHRI, No. 70
at p. 5; ADP, No. 59 at p. 2-3; Mortex, No. 71 at p. 4-6; Lennox, No.
61 at p. 5) AHRI, ADP, Mortex, and Lennox noted that in the proposed
framework, Similarity Groups may span AC and HP operations as well as
coil-only and blower coil combinations. (AHRI, No. 70 at p. 6; ADP, No.
59 at p. 3; Mortex, No. 71 at p. 6; Lennox, No. 61 at p. 6)
However, the commenters noted that the proposed Similarity Group
concept would not replace the concept or definition of an ICM basic
model. Instead, a Similarity Group would be a group of basic models for
defining AEDM validation test requirements, and the ICM basic model
would still be used for other aspects of the certification and
enforcement scheme as noted in the SNOPR. (AHRI, No. 70 at p. 7; ADP,
No. 59 at p. 4; Mortex, No. 71 at p. 7; Lennox, No. 61 at p. 7)
[[Page 37007]]
With regard to DOE's proposed definition of basic model for ICMs,
Lennox requested that tube wall thickness not be required as part of a
certification report as to protect business sensitive design
information. (Lennox, No. 61 at p. 3)
UTC/Carrier, Rheem, and the Joint Advocates of ACEEE, NRDC, and
ASAP supported DOE's proposal for ICMs to test each model of indoor
unit with the lowest-SEER model of outdoor unit that is certified as a
part of a basic model by an OUM. (UTC/Carrier, No. 62 at p. 6; Rheem,
No. 69 at p. 6; ACEEE, NRDC, ASAP, No. 72 at p. 2) UTC/Carrier
appreciated leveling the playing field closing this loophole advantage
for ICMs. (UTC/Carrier, No. 62 at p. 6)
On the other hand, AHRI, ADP, Lennox, and Mortex commented that
testing is necessary to validate product performance and each ICM's
AEDM, but that the requirement to test every basic model presents an
excessive burden on ICMs. (AHRI, No. 70 at p. 3; ADP, No. 59 at p. 1;
Mortex, No. 71 at p. 3; Lennox, No. 61 at p. 4) First Co. also
commented that the result of DOE's proposal is excessive testing.
(First Co., No. 56 at p. 1)
AHRI analyzed data from the AHRI Directory of Certified Product
Performance, considering air conditioning, heat pump, coil-only and air
handler ratings, but omitting due to time limitations air flow,
external static pressure and power input. The results indicated that
each ICM has between 287 and 604 basic models for which they would have
to bear the cost of testing, which AHRI estimated would increase
several-fold if accounting for the additional parameters. AHRI stated
that it used an estimate of testing costs for one system at an
independent lab of $7,400 for AC and $10,000 for HP because many ICMs
do not have their own labs. Therefore, by AHRI's calculations, the ICM
with the smallest number of basic models from their analysis would be
required to perform 574 tests for an estimated $5,740,000 in testing
costs. In addition, a test takes approximately one day, so 574 tests
would take approximately two years to complete. (AHRI, No. 70 at p. 4-
5)
For these reasons, AHRI, ADP, Mortex, and Lennox recommended that
DOE require all ICM ratings to be based on an AEDM, where the ICM would
test and rate at least one combination of an outdoor unit with the
lowest SEER that complies with standard per Similarity Group. They also
recommended that the ICM perform at least one full-system test per
Similarity Group, or if the ICM was rating HP combinations, the ICM
test one-third of the Similarity Groups with HP systems in both heating
and cooling modes; and certify all combinations before they are
distributed in commerce. (AHRI, No. 70 at p. 5-6; ADP, No. 59 at p. 2-
3; Mortex, No. 71 at p. 4-6; Lennox, No. 61 at p. 5) AHRI, ADP, Mortex,
and Lennox noted that applying this scheme to the AHRI Directory
results in between 26 and 64 tests for the same ICM companies analyzed
above. AHRI, ADP, Mortex, and Lennox believed that their suggested
method provides for an extremely high level of AEDM validation while
creating a manageable testing burden on ICMs. (AHRI, No. 70 at p. 6;
ADP, No. 59 at p. 3-4; Mortex, No. 71 at p. 6; Lennox, No. 61 at p. 6-
7)
First Co. and Unico also supported AHRI's approach. First Co.
commented that the use of a Similarity Group would be a more realistic
and workable approach that would enable ICMs to reduce testing for
comparably performing indoor coils and to validate performance for the
group by the same test. (First Co., No. 56 at p. 1) Unico recommended
that DOE require the OUM to have at least two tests for each basic
model (the outdoor unit) and the ICM to have at least one test from
each Similarity Group in order to validate the AEDM. Unico also noted
that the ICM testing requirements would increase significantly compared
to what they are today even under AHRI's suggestion. (Unico, No. 63 at
p. 4-5)
After reviewing the comments, DOE agrees with the manufacturers
that its proposed definition of basic model with respect to ICMs,
combined with the proposed testing requirements, may result in a
significant test burden for ICMs. In order to balance the burden of
testing with the risk of enforcement action, DOE is adopting aspects of
the suggested ``Similarity Group'' as a replacement to its proposed
definition of basic model. Hence, the basic model definition for ICMs
established in this final rule includes all individual combinations
having comparably performing indoor coil(s) [plus or minus one square
foot face area, plus or minus one fin per inch fin density, and the
same fin material, tube material, number of tube rows, tube pattern,
and tube size].
DOE also agrees that manufacturers should test one combination per
what the AHRI and manufacturer calls ``Similarity Group'', and what DOE
will call a basic model for ICMs. However, DOE does not agree that
testing should only serve to validate AEDMs. In order to accurately
rate these non-engineered-to-order products by capturing the
variability in the manufacturing processes, all combinations required
to be tested must be tested according to the sampling plan in 429.16,
which generally requires a sample of at least two units of the basic
model. DOE notes that AHRI's calculation of burden assumes that ICMs
have not been testing under current regulations, which is not
consistent with existing DOE regulations. In addition, by changing the
proposed definition of basic model to align with the similarity group
proposal, DOE has significantly reduced the proposed test burden on
ICMs.
DOE notes that because basic models do not span product classes,
unlike in the stakeholders' proposal, each Similarity Group is limited
to either air conditioners or heat pumps; however, in response to the
stakeholders' request that only one-third of Similarity Groups need be
tested in both cooling and heating mode, DOE is not requiring testing
for basic models of heat pumps as long as an equivalent basic model of
air conditioner has been tested.
DOE also notes that while off-mode power consumption requirements
apply to ICMs, the represented values for off-mode may be based on the
results of testing by the OUM according to the requirements in 429.16.
In response to Lennox's request to remove tube wall thickness from
the definition of basic model, DOE notes that the Similarity Group
requirements DOE is adopting in its basic model definition for ICMs do
not include tube wall thickness; in addition, as noted in section
III.A.1.c, DOE did not propose that manufacturers report this
information regardless of its inclusion in this definition.
e. Single-Package Systems
In the current regulations, 10 CFR 429.16(a)(2)(i) states that each
single-package system must have a sample of sufficient size tested in
accordance with the applicable provisions of Subpart B. In the November
2015 SNOPR, DOE proposed that the lowest SEER individual model within
each basic model must be tested. DOE expected that in most cases, each
single-package system would represent its own basic model. However,
based on the definition of basic model in section III.A.1, this may not
always be the case. DOE noted that regardless, AEDMs do not apply to
single-package systems--manufacturers may either test and rate each
individual single-package system or, if multiple individual models are
assigned to the same basic model per the proposed requirements in the
basic model definition, test only the lowest SEER individual model
within the basic model and use that to determine the
[[Page 37008]]
rating for the basic model. 80 FR 69278, 69288 (Nov. 9, 2015).
DOE also proposed to specify this same requirement for space-
constrained single-package air conditioners and heat pumps. 80 FR
69278, 69288 (Nov. 9, 2015).
DOE requested comment on the likelihood of multiple individual
models of single-package units meeting the requirements proposed in the
basic model definition to be assigned to the same basic model. DOE also
requested comment on whether, if manufacturers are able to assign
multiple individual models to a single basic model, manufacturers would
want to use an AEDM to rate other individual models within the same
basic model other than the lowest SEER individual model.
In response, Lennox commented that the use of basic models that
meet the defined requirements should not be restricted to split-system
products because allowing groupings in a basic model may allow the use
of AEDMs for single-package products to reduce testing burden. (Lennox,
No. 61 at p. 14) UTC/Carrier supported that different options would be
assigned to [individual models within] the same basic model and
supported the ability to have unique ratings for units with different
options without additional testing. (UTC/Carrier, No. 62 at p. 6-7)
JCI stated that it, in general, would prefer to test single-package
units, especially the single-phase models. For 3-phase (commercial)
products, JCI would opt to utilize an AEDM. (JCI, No. 66 at p. 15)
Rheem disagreed that manufacturers should not be allowed to use
AEDM to rate packaged units; Rheem would want to use an AEDM to rate
other individual models within the basic model for packaged units.
(Rheem, No. 69 at p. 3, 6-7)
In response to these comments, DOE is modifying the regulations to
permit the use of AEDMs for models of single-package units in cases
where multiple individual models are assigned to the same basic model.
The lowest SEER individual model in the basic model still will be
required to be tested. DOE believes that the lowest SEER model will
typically be similar to the highest sales volume model.
f. Replacement Coils
In the November 2015 SNOPR, DOE noted that its proposed definition
of ``indoor unit'' refers to the box rather than just a coil.
Accordingly, legacy indoor coil replacements and uncased coils would
not meet the definition of indoor unit of a central air conditioner or
heat pump. Hence, they would not need to be tested or certified as
meeting the standard. 80 FR 69278, 69289 (Nov. 9, 2015).
DOE received several comments in response to this proposal. These
comments have been addressed as part of DOE's definition of ``indoor
unit,'' discussed in section III.A.2.
g. Outdoor Units With No Match
For split-system central air conditioners and heat pumps, current
DOE regulations require that manufacturers test the condensing unit and
``the evaporator coil that is likely to have the largest volume of
retail sales with the particular model of condensing unit'' (commonly
referred to as the highest sales volume combination or HSVC). 10 CFR
4429.16(a)(2)(ii). Effective January 1, 2010, the U.S. Environmental
Protection Agency (EPA) banned the sale and distribution of those
central air conditioning systems and heat pump systems that are
designed to use HCFC-22 refrigerant. 74 FR 66450 (Dec. 15, 2009). EPA's
rulemaking included an exception for the manufacture and importation of
replacement components, as long as those components are not pre-charged
with HCFC-22. Id. at 66459-60.
Because complete HCFC-22 systems can no longer be distributed,
manufacturers inquired how to test and rate individual components.
Because the EPA prohibits distribution of new HCFC-22 condensing unit
and coil combinations (i.e., complete systems), there is no such thing
as a HSVC, and hence, testing and determination of represented values
of new HCFC-22 combinations cannot be conducted using the existing test
procedure.
Accordingly, DOE proposed a test procedure that may be used for
determining represented values and certifying the compliance of these
outdoor units. DOE proposed to specify coil characteristics to be used
when testing models of outdoor units that do not have a HSVC.
Specifically, these requirements included limitations on indoor coil
tube geometries and dimensions and coil fin surface area. In the
November 2015 SNOPR, DOE proposed to require the normalized gross
indoor fin surface (NGIFS) calculated for the indoor unit used for the
test to be no more than 1.15. 80 FR 69278, 69289 (Nov. 9, 2015). NGIFS
is the fin surface area divided by the unit's capacity. By imposing a
limit on this value, the size of the indoor coil would be consistent
with older model designs that would likely be installed in the field
and that do not include a common design approach for improving
efficiency, i.e. use of larger coils. Attaining a given efficiency
level when testing a combination having a lower-NGIFS indoor unit
requires use of a more efficient outdoor unit to compensate. These
outdoor unit models must meet applicable Federal standards when tested
with the specified indoor units.
General Comments
AHRI, URI, Nortek, HARDI, Goodman, UTC/Carrier, Rheem, and JCI
submitted comments against adding the test procedure provisions for
outdoor units with no match. (AHRI, No. 70 at p. 2; United
Refrigeration, Inc., No. 60 at p. 3-4; Nortek, No. 58 at p. 2; HARDI,
No. 57 at p. 2; Goodman, No. 73 at p. 17-18; UTC/Carrier, No. 62 at p.
22-23; Rheem, No. 69 at p. 3; JCI, No. 66 at p. 5)
Nortek and UTC/Carrier expressed concern that offering a test
procedure for units with no match could potentially open up a larger
loophole than what DOE is attempting to fix with this proposal.
(Nortek, No. 58 at p. 2; UTC/Carrier, No. 62 at p. 23) Similarly,
Nortek and HARDI noted that there have been no instances of a company
trying to sell an outdoor unit without match that failed to meet
existing standards. (Nortek, No. 58 at p. 2; HARDI No. 57 at p.1)
Conversely, Lennox, NEEA, NPCC, and the Joint Advocates of ACEEE,
NRDC and ASAP concurred with DOE's proposal to require testing and
rating of dry-ship units. (Lennox, No. 61 at p. 2; NEEA and NPCC, No.
64 at p. 3; ACEEE, NRDC and ASAP, No. 72 at p. 2)
DOE acknowledges these comments and responds to particular concerns
about its proposal in subsequent sections.
URI commented that the Department's proposal not only would ban the
manufacture of new replacement units, it also would impose significant
cost burdens on manufacturers and distributors of replacement HCFC-22
components. URI suggested that under DOE's proposal, replacement unit
manufacturers that tested and certified HCFC-22 products in good faith
reliance of the various test procedure guidance documents issued by the
Department would be unable to advertise or sell these units. URI
requested that DOE evaluate the impacts of replacing rather than
repairing and maintaining an HCFC-22 unit, particularly on those
consumers who live on a fixed income, and that DOE assess whether, as a
practical matter, this test procedure amendment would adversely impact
the availability of replacement components for the installed base of
HCFC-22 units.
[[Page 37009]]
(United Refrigeration, Inc., No. 60 at p. 8-9)
In response to URI, DOE's approach in developing the test procedure
requirements for outdoor units with no match is based on the concept
that the test should produce results that measure energy efficiency
during a representative average use cycle. (42 U.S.C. 6293 (b)(3))
Further, the test procedure addresses the fact that these units have no
match. Unmatched outdoor units are primarily used as a low-cost
alternative to replacement of an entire legacy system when the outdoor
unit is no longer operational. Specifically, in such installations,
only the outdoor unit would be replaced, rather than both the outdoor
unit and indoor unit. In addition, such units would be installed using
HCFC-22, which is no longer legal for use in new systems.
DOE developed this amended test procedure with the goal of ensuring
that the unmatched outdoor unit should be compliant when tested with an
indoor unit that is representative of indoor units in the field with
which the outdoor unit could be paired. DOE's goal was to provide a
method of test, consistent with the current standards, that meets the
statutory requirement of measuring a representative average use cycle.
Hence, the indoor unit specifications are intended to represent among
the lesser-efficient units that could be paired with a given outdoor
unit with no match. DOE believes this approach is consistent with the
requirement that the represented value for a basic model reflect the
performance of the poorest-performing model that is part of the basic
model.
In response to URI's comments regarding evaluation of cost burdens
and impacts of the test procedure change, DOE notes that its energy
conservation standard rulemakings have already evaluated the costs and
benefits of specific efficiency levels for central air conditioners and
heat pumps. This test procedure provides a mechanism of assessing the
performance of unmatched outdoor units, which can then be used to
provide a reasonable level of assurance that all field-match
combinations of the new, unmatched outdoor units will achieve the
established efficiency levels. DOE is now adopting the November 2015
SNOPR approach for testing and determining represented values for
unmatched outdoor units based on stakeholder comment.
Goodman had concerns about unforeseen and unintended consequences
when moving forward with alternate refrigerants at some date in the
future, especially as the requirements for applying air conditioners
and heat pumps with these likely A2L refrigerants is unknown. Goodman
stated that it expects that, with currently known alternate
refrigerants, there may be a need for certain low[hyphen]income and
elderly consumers to have cost-effective replacement air conditioners.
Goodman also noted that it has apprehensions that providing a test
procedure provides a path for HCFC[hyphen]22 ``dry ship'' products to
continue in the marketplace. (Goodman, No. 73 at p. 18)
DOE responds that it cannot set test procedure requirements based
on speculation about the potential cost impact of future refrigerant
changes on air-conditioning product costs. In response to the second
comment, DOE points out the suggestion of commenters that DOE's
proposal will limit sales of these units--URI for example indicated
that the test procedure will effectively end the manufacturer of such
components (URI, No. 60 at p. 2). While DOE does not agree with this
assessment, DOE also does not believe that the approach will increase
manufacturer of such units.
DOE Authority
In its comments, JCI stated that it was not certain that DOE has
the authority under EPCA to create a test procedure to allow for units
with no match. (JCI, No. 66 at p. 6)
URI commented that the DOE's November 2015 SNOPR test procedure, if
finalized, would violate EPCA, as amended, as well as the
Administrative Procedure Act. URI asserted that DOE had proposed a
restriction on representations for already manufactured and certified
units and that the proposal would invalidate the expectation-backed
investments of manufacturers and distributors, constituting a violation
of the Fifth Amendment to the U.S. Constitution. URI characterized
DOE's proposal as an effective ban on condensing units using HCFC-22
that also would impose significant cost burdens on consumers. (United
Refrigeration, Inc., No. 60 at p. 2, 3-5)
URI also commented that a test procedure change for replacement
HCFC-22 systems is not needed, and that DOE has not articulated a valid
basis for its proposal, as required by EPCA. URI argued that DOE's
proposed test procedure change for replacement HCFC-22 systems would
violate the Administrative Procedure Act, which requires an agency to
``examine the relevant data and articulate a satisfactory explanation
for its action including a `rational connection between the facts found
and the choice made.''' 5 U.S.C. 553, Motor Vehicle Manufacturers Ass'n
v. State Farm Mutual Automobile Insurance Co., 463 U.S. 29 (1983)). URI
said that the DOE did not only fail to explain why the change to the
test procedure for replacement units is necessary, but also failed to
acknowledge the de facto ban it is proposing for such units. URI argued
that DOE does not have the authority to impose a ban on replacement
units and asserted that, even assuming that DOE has the authority to
impose such a ban, that EPCA prohibits the Department from implementing
such an action through a test procedure amendment. (United
Refrigeration, Inc., No. 60 at p. 5)
URI also argued that DOE could not circumvent the prohibition
against retroactive effect by belatedly ``clarifying'' that HCFC-22
condensing components are basic models in and of themselves, even
assuming that the EPCA would allow such a comprehensive revision of the
``basic model'' via test procedure rulemaking. (United Refrigeration,
Inc., No. 60 at p. 9)
Contrary to URI's assertions, DOE is not, in this rule, imposing a
de facto ban on condensing units using HCFC-22. DOE is amending a test
procedure and, in accordance with the applicable provisions of EPCA, is
ensuring that the test procedure is reasonably designed to measure the
energy efficiency and energy use of unmatched outdoor units in a manner
that is comparable to that of other complete systems. DOE clearly
articulated the basis for its proposal and has explained again here the
need for a test procedure applicable to unmatched outdoor units.
Regarding the amended definition of basic model in today's rule, DOE is
not proposing that the definition, as amended, be applied
retroactively.
Test Procedure Details Including Specification of Indoor Unit
Stakeholders provided a range of comments regarding whether the
proposed details of the test for outdoor units with no match are
suitable.
Nortek, Ingersoll Rand, and Goodman questioned how DOE determined
the proposed value for NGIFS and that the default coefficient of cyclic
degradation should be used for these units, and requested that DOE
provide supporting evidence. (Nortek, No. 58 at p. 2; Ingersoll Rand,
No. 65 at p. 12; Goodman, No. 73 at p. 18)
URI commented that it is simply impossible for any HCFC-22
replacement component to meet the 13
[[Page 37010]]
SEER standard using the amended test procedure, stating that the
proposed coil size limitation makes no sense as such coils were used in
HCFC-22 units rated to 10 SEER. URI also asserted that the proposed
coefficient of cyclic degradation improperly excludes units that use
thermostatic expansion valves, rather than orifice tubes, to control
the flow of refrigerants, thus penalizing the efficiency rating
approximately 6% (for example, a 13 SEER unit with a thermostatic
expansion valve would instead rate at 12.2 SEER). (United
Refrigeration, Inc., No. 60 at p. 2, 7)
Goodman noted that by specifically choosing the 1.15 maximum NGIFS
(especially without deference to the type of fin used), DOE is choosing
indoor coils that are smaller, but not smallest, in size. Goodman
commented that based on the information it has, the value of 1.15 would
favor one manufacturer, which has all of its ``no[hyphen]match'' units
rated with indoor coils having less than 1.15 NGIFS, while at least two
manufacturers have zero ``no[hyphen]match'' units rated with indoor
coils having less than 1.15 NGIFS. Goodman commented that DOE should
not ignore fin surface type in the NGIFS calculation, and that if DOE's
intent is intent is to specify an indoor coil size such that it is
virtually impossible for an OUM to have an outdoor unit with no match
that can achieve 13 or 14 SEER as a system, then DOE should choose an
NGIFS in the range of 0.90 or less using the proposed NGIFS formula.
(Goodman, No. 73 at p. 18-19)
JCI commented for a 10 SEER product, the value of NGIFS of 1.15 is
too small. The NGIFS of 10 SEER products made by JCI was 1.25, and
these products will have been out of production for 10 years by the
time this SNPOR is effective. JCI said that, at this point, when an
outdoor unit fails, approximately 40% to 50% would be 13 SEER plus
equipment. A reasonable NGIFS for 13 SEER equipment would be 1.30,
which is the average for JCI's 13 SEER HCFC-22 product when the EPA ban
on new produced equipment shipped with HCFC-22 took effect in 2010:
averaging the 10 SEER and 13 SEER values leaves a value of 1.28. JCI
believes this value to be a more representative value for NGIFS and
recommends DOE adopt it. (JCI, No. 66 at p. 5-6)
Ingersoll Rand provided data on the 61 HCFC-22 systems that they
had on the market before HCFC-22 was phased out. For the HSVCs of these
61 models, the NGIFS ranged from 0.9784 to 1.9082 with a mean of 1.2692
and a standard deviation of 0.2215. Ingersoll Rand recommended a value
of 1.75 for the final rule. (Ingersoll Rand, No. 65 at p. 12)
JCI commented that modern heat exchanger technology such as that
found in microchannel heat exchangers significantly reduces the
refrigerant charge and thus reduces the cycling losses, resulting
consistently in degradation coefficient values under 0.10 with piston
metering (expansion) devices, or non-bleed TXVs. JCI recommended that
rather than requiring use of the default degradation coefficient value,
DOE should specify the type of expansion device it believes would be
used in the legacy indoor units, which in most instances would be a
piston or fixed orifice construction. (JCI, No. 66 at p. 6)
As mentioned above, DOE's approach in developing the test procedure
requirements for outdoor units with no match is based on the concept
that the test should produce results which measure energy efficiency
during a representative average use cycle (see 42 U.S.C. 6293(b)(3))
while also ensuring that they will generally meet the standard. By
their nature, however, neither the manufacturer nor DOE knows exactly
what the paired system will be. DOE evaluated indoor unit
specifications representing units across the spectrum that would likely
be paired with the ``no match'' units. To ensure compliance, DOE
proposed indoor unit specifications that it believed to be
representative of a less efficient unit that could be paired with the
given outdoor unit with no match.
In developing its proposal, DOE developed the indoor unit
specifications (1.15 NGIFS and coefficient of cyclic degradation equal
to the default) through reverse engineering 13 SEER split-system blower
coil air conditioners designed to use HCFC-22. The 1.15 value is
representative of the indoor units associated with the evaluated
systems. All of these units had single-capacity compressors, and the
indoor units had PSC fan motors. Although the NGIFS for these units
ranged from 1.0 to 1.7, almost identical to the range of the data
provided by Ingersoll Rand, DOE does not feel that establishing an
NGIFS range is a valid approach, since this would be equivalent to
setting the limit equal to the highest end of the range. In any case,
both of these datasets are at odds with URI's claim that the 1.15 NGIFS
makes attaining 13 SEER impossible. Regarding JCI's claim that the
value is too small, the selected value is for an indoor unit that was
part of an HCFC-22 unit rated at 13 SEER, hence it is certainly
representative of the indoor units that may be installed in the field.
In fact, DOE's selection of 1.15 did not consider the 10 SEER units
whose indoor units are still in the field as well. In addition, the
actual performance of the non-replaced legacy indoor units, represented
in terms of NGIFS, generally will be significantly degraded.
Degradation of indoor unit performance can be caused by numerous
factors, including foulants coating external coil surfaces, caustic
environments attacking fin material and/or fin/tube contact, inadequate
air flow, and degraded oil fouling the internal tube surfaces.
Consistent with the use of unmatched outdoor units for such system
repairs as a low-cost alternative, it is questionable whether
installation consistently addresses optimization of the system for
operation at the diminished efficiency potential of the degraded legacy
indoor unit. Consequently it is expected that laboratory testing of new
models of unmatched outdoor units significantly overestimates the
efficiency of these units when paired with old legacy indoor units in
the field. The proposed maximum NGIFS of the indoor unit to be used in
such a test is in the range of the values for legacy indoor units, but,
because of the non-optimum field conditions, choosing a value that is
an average or median for such legacy indoor units is not
representative. Based on all of these considerations, DOE has decided
to lower the required NGIFS for the test to 1.0. This level
acknowledges degradation of indoor unit performance over time,
questions regarding optimization of the indoor/outdoor unit match and
of the installation, and that the range of indoor units in the field
would also include 10 SEER units. This value is representative of the
13 SEER systems of both DOE's and Ingersoll Rand's datasets. DOE notes
that the comments have not shown that this value is unrepresentative of
the potential indoor unit pairings of no-match outdoor units.
Furthermore, given that DOE believes this value is representative and
that an NGIFS range is not a valid approach, DOE does not believe there
is a need for AEDM for these units.
DOE understands that the type of fin surface has an impact on coil
performance, as Goodman pointed out in its comment. Most of the fins of
the evaporator coils of DOE's dataset were enhanced, having lanced or
louvered surfaces, so DOE's assessment has considered the possibility
that the fin surfaces would be enhanced. DOE believes that selecting
the NGIFS limit based on enhanced-fin information is appropriate
because any manufacturer conducting such a test would do so using an
indoor unit that has enhanced
[[Page 37011]]
fins, which would provide an advantage to the manufacturers.
DOE notes JCI's comment that when an outdoor unit fails, 40% to 50%
of the indoor units would have been rated 13 SEER or higher. This
suggests that at least half would have been rated lower than 13 SEER.
JCI also suggested that NGIFS might be 0.05 lower for a 10 SEER indoor
unit than for 13 SEER. The Ingersoll Rand comment indicates that the
NGIFS of their HCFC-22 models on the market prior to the refrigerant's
phase-out was as low as 0.9784. Since the 13 SEER standard took effect
in 2006, DOE presumes that these units all had a SEER value no lower
than 13.
DOE agrees with JCI that advanced heat exchanger technology might
improve system efficiency. In particular, microchannel heat exchangers
may reduce refrigerant charge sufficiently to reduce degradation of
performance associated with unit cycling. However, DOE is not convinced
that the expansion devices, be they thermostatic expansion valves,
pistons, or fixed-orifice devices, of all legacy indoor units are
replaced with orifices optimized for the new paired combination using
the intended refrigerant. DOE agrees that a degradation coefficient
less than the default value may be achievable in a laboratory test
while using a fixed orifice device, but is not convinced that this will
consistently be achieved with field-paired combinations. JCI did not
comment on the consistency of the replacement of the expansion devices
in unmatched outdoor unit installations, so DOE cannot determine how
many such installations include expansion devices that are optimized
for the outdoor/indoor unit combination. It is reasonable to expect
that numerous such installations do not involve installation of an
optimized expansion device, since unmatched outdoor units are sold as a
low-cost alternative to purchase of an entirely new system, and use of
the existing expansion device would also reduce cost. Further, DOE
notes that reduction of the cyclic degradation coefficient, as proposed
in the November 2015 SNOPR, was based on the observation that most
modern systems achieve degradation coefficients well below 0.2. DOE did
not intend to assign this same value as the default for outdoor units
without a match. Based on the same arguments regarding lack of
optimization of the expansion devices, DOE does not believe it is
appropriate to adopt the new-test default of 0.2 for these units and
therefore is retaining the current degradation coefficient for them at
0.25.
Waiver Process and Change in the Measurement
Nortek, Goodman, and HARDI commented that manufacturers who would
like to sell a condensing unit with no match should request a waiver
from DOE. (Nortek, No. 58 at p. 2; Goodman, No. 73 at p. 18; HARDI, No.
57 at p. 2)
URI commented that the notice is silent on how the proposed coil
limitation or NGIFS will improve the measured energy efficiency of
replacement HCFC-22 condensing units and that DOE's view that these
units should have been tested pursuant to a waiver doesn't make sense
in light of guidance DOE issued in 2010, 2012, and 2014 . URI
separately indicated that DOE has not clarified whether the test
procedure change will alter the measurement and/or whether the standard
would have to be adjusted as required by EPCA. (United Refrigeration,
Inc., No. 60 at p. 6)
In response to Nortek, Goodman, and HARDI, DOE notes that the
waiver process is a step towards establishing new procedure provisions
in the CFR that address the test procedure issues raised by the waiver.
In this case, as mentioned by some commenters, at the time of
publication of the November 2015 SNOPR, there had been no petitions for
waivers for outdoor units with no match. Test procedure waivers are not
a long-term solution, however. DOE's regulations require DOE to amend
its test procedure to address an issue raised through the waiver
process. Therefore, even though DOE has not received any petitions for
waivers for outdoor units with no match, DOE has long recognized the
difficulty of reconciling the current test procedure language with the
reality that manufacturers have no highest sales volume combination due
to EPA regulations and proposed a test method to eliminate the
regulatory incongruity between EPA's and DOE's regulations. DOE is
finalizing a test procedure to eliminate the issue.
In response to URI, DOE acknowledges that its guidance document
indicated that an individual condensing unit must meet the current
Federal standard when paired with the appropriate other new part to
make a system when tested in accordance with the DOE test procedure and
sampling plan. However, as noted in the November 2015 SNOPR, generally
when a model cannot be tested in accordance with the DOE test
procedure, manufacturers must submit a petition for a test procedure
waiver for DOE to assign an alternative test method. Nothing in the
guidance documents indicated that this would not have been the case for
these units.
In response to URI's comment suggesting that measured energy use
must improve under a waiver procedure, DOE notes that a test procedure
waiver is not intended to impact measured energy efficiency. Instead, a
test procedure waiver provides a manufacturer with an alternative
method of test that will yield results comparable to the test procedure
in the DOE regulations. Test procedures are not a mechanism to impact
the efficiency of a product, which is why DOE has carefully evaluated
the characteristics of a paired system so as to avoid impacting
measured efficiency relative to the current test procedure.
Transition From Coverage Under the Guidance Documents
URI commented that the test procedure would effectively end the
manufacture of such components six months after the revised test
procedure goes into effect. URI contended that it also would be
prohibited from selling or distributing its existing inventory of
properly certified and rated HCFC-22 replacement condensing units six
months after the effective date because the notice makes clear that
``any representations, including compliance certifications,'' about the
energy cost and efficiency of replacement condensing units must be
based on the revised test procedure. (United Refrigeration, Inc., No.
60 at p. 2)
URI submitted that DOE should clarify in the preamble and
regulatory text of a final test procedure that the restriction on
representations does not apply to HCFC-22 condensing units that were
manufactured and certified pursuant to the preceding DOE guidance.
(United Refrigeration, Inc., No. 60 at p. 2)
In a letter to the Secretary of Energy, Lennox requested DOE to
promptly issue guidance to prevent the entry of newly designed 14 SEER
HCFC-22 dry-charge products into the southern and southwestern regions
that do not meet the requirements of the DOE test procedure. Lennox
commented that DOE action on these issues is particularly critical by
early 2016, as manufacturers ramp up production for the 2016 summer
air-conditioning sales season in that timeframe. (Lennox, No. 61 at p.
2)
Lennox requested DOE include mechanisms in the final rule to
facilitate a quick and orderly market transition from legacy dry-
shipped outdoor split-system central air conditioners and heat pumps
certified to DOE as compliant
[[Page 37012]]
that are not rated in accordance with the test procedure final rule by
requiring manufacturers to discontinue all non-compliant ratings 180
days after the final rule's publication. (Lennox, No. 61 at p. 2-3)
JCI recommended that no later than February 1, 2016, DOE should
issue enforcement guidance stating that DOE will not seek civil
penalties or injunctive relief for the distribution in commerce of a
dry charged HCFC-22 unit (unit with no match), or for the labeling
requirements of that unit, if the unit is manufactured prior to a date
that is 30 days after the date of publication of the enforcement
guidance. (JCI, No. 66 at p. 7)
On December 16, 2015, DOE issued an enforcement policy stating that
it would begin investigating the methods manufacturers were using to
rate split-system central air conditioners that do not have a highest
sales volume combination. Those investigations are ongoing. DOE also
stated that it would seek civil penalties for violations related to
units manufactured on or after February 1, 2016, that had not been
tested and properly certified as compliant with the applicable
standards. As DOE indicated in the policy statement, DOE will continue
to use its discretion in determining whether or to what extent
penalties are appropriate, including an evaluation of a manufacturer's
good faith efforts to comply with the regulations. DOE notes that this
test procedure final rule does not have retroactive application;
however, the units at issue have been subject to the energy
conservation standards and certification requirements since 2006.
DOE also notes that following the close of the comment period for
the November 2015 SNOPR, on December 1, 2015, an ex parte meeting
occurred between AHRI, manufacturers, and DOE regarding outdoor units
with no match. Representatives from Nortek, Mitsubishi, Carrier,
Lennox, Trane, Rheem, JCI, ADM, Goodman, and Allied Air attended.
During this meeting, the attendees requested that DOE require that
ratings of existing dry R-22 units must be discontinued 180 days after
the date of the publication of the amended test procedure in the
Federal Register. (Docket No. EERE-2009-BT-TP-0004-0074) This
recommendation indicates that existing ratings for outdoor units with
no match are invalid and supports the need for a test procedure as
finalized in this notice. DOE is implementing this recommendation
consistent with EPCA, as discussed in section III.H.1.
4. Compliance With Federal (National or Regional) Standards
In the November 2015 SNOPR, DOE proposed to add requirements to the
relevant provisions of section 430.32 that the least-efficient
combination within each basic model must comply with the regional SEER
and EER standards. 80 FR 69278, 69290 (Nov. 9, 2015). In addition, as
noted in section III.A.1, DOE proposed that if any individual
combination within a basic model fails to meet the standard, the entire
basic model (i.e., model of outdoor unit) must be removed from the
market. In order to clarify the limitations on sales of models of
outdoor units across regions with different standards, DOE proposed to
add a limitation in section 429.16 that any model of outdoor unit that
is certified in a combination that does not meet all regional standards
cannot also be certified in a combination that meets the regional
standard(s). Further,
----------------------------------------------------------------------------------------------------------------
Individual model # Individual model # Certified rep.
Basic model (outdoor unit) (indoor unit) value (SEER/EER) Permitted?
----------------------------------------------------------------------------------------------------------------
AB12........................... ABC**#**-***...... SO123 14.5/12.0 NO.
AB12........................... ABC**#**-***...... SW123 15.0/12.8
AB12........................... ABC**#**-***...... N123 13.9/11.7
CD13........................... CDESO**-*#*....... SO123 14.5/12.0 YES.
CD13........................... CDESW**-*#*....... SW123 15.0/12.8
CD13........................... CDEN***-*#*....... N123 13.9/11.7
EF12........................... EFCS**#**-***..... SO123 14.5/12.2 YES.
EF12........................... EFCS**#**-***..... SW123 14.6/12.4
EF12........................... EFCN**#**-***..... N123 13.9/11.7
----------------------------------------------------------------------------------------------------------------
DOE proposed to require that outdoor unit model numbers cannot span
regions unless the model of outdoor unit is compliant with all
standards in all possible combinations. If a model of outdoor unit is
certified below a regional standard, then, under DOE's proposal, it
must have a unique individual model number for distribution in each
region. 80 FR at 69290 (Nov. 9, 2015).
For example:
The Joint Advocates of ACEEE, NRDC and ASAP commented that the
approach proposed by DOE is workable and provides clear requirements
for OUM rating systems. The Joint Advocates also commented that
requiring a specific model number for outdoor units that are certified
only in combinations that meet regional standard(s), and therefore
permitted to be installed in those regions, will aid enforcement. The
Joint Advocates also commented that DOE should clarify the requirements
for ICMs, specifically how DOE would treat an ICM that attempts to
certify a combination with a rating below 14 SEER using an outdoor unit
model that otherwise meets 14 SEER in all combinations certified by the
OUM. (ACEEE, NRDC and ASAP, No. 72 at p. 3)
Based on this comment, DOE adopts the limitation as proposed, with
wording modifications for clarity. DOE has not added a limitation on
ICMs certifying a combination below an OUM represented value, given
that such a value would reflect the performance the consumer would
experience. DOE has not modified 430.32 in this rulemaking and will
instead do so in the regional standards enforcement rulemaking.
5. Certification Reports
To maximize test repeatability and reproducibility for assessment
and enforcement testing, DOE proposed a number of amendments to the
certification reporting requirements. 80 FR 69278, 69290 (Nov. 9,
2015).
Among these requirements, DOE proposed to clarify what basic model
number and individual model numbers must be reported for central air
conditioners and heat pumps. 80 FR 69278, 69290-91 (Nov. 9, 2015). DOE
proposed to require the reporting of the sensible heat ratio (SHR)
value calculated based on full-load cooling test conditions at the
outdoor ambient conditions: 82[emsp14][deg]F dry bulb and
65[emsp14][deg]F wet bulb. 80 FR at 69326 (Nov. 9, 2015). Finally, DOE
also proposed to require certain product-specific information at 10 CFR
429.16(c)(4) that would not be
[[Page 37013]]
displayed in DOE's public database. 80 FR at 69291 (Nov. 9, 2015).
NEEA and NPCC supported DOE's proposals for certification reports,
specifically noting the importance that all combinations of individual
model numbers within a basic model group can be identified and to
identify the outdoor and indoor mini-split and multi-split system units
that are rated as combinations. (NEEA and NPCC, No. 64 at p. 3) DOE
adopts this provision in the final rule.
Regarding the basic model provision, AHRI commented that ICMs
should be required to identify in the certification report the
Similarity Group to which each indoor unit belongs. (AHRI, No. 70 at p.
5-6) DOE notes that it has adopted the Similarity Group structure
recommended by AHRI as the basis for the basic model for ICMs. Hence,
identification of the Similarity Group is not necessary.
The California IOUs commented that the proposal to require
reporting of SHR is a good precedent for providing other data from
tests and requested that results also be reported for all the tests
that are the inputs to calculation of SEER and HSPF, as well as the
results of the AHRI maximum operational conditions test.\8\ (California
IOUs, No. 67 at p. 4) On the other hand, AHRI, Lennox, ADP, UTC/
Carrier, JCI, Goodman, and Nortek believe that SHR should not be
reported as part of a certification report. (AHRI, No. 70 at p. 10;
Lennox, No. 61 at p. 9; ADP, No. 59 at p. 7; UTC/Carrier, No. 62 at p.
8; JCI, No. 66 at p. 15-16; Goodman, No. 73 at p. 14; Nortek, No. 58 at
p. 7) JCI noted that the publication of SHR should be left to the
manufacturer as part of their technical literature, and UTC/Carrier
noted that that information is already provided in the manufacturer's
product data. (JCI, No. 66 at p. 12; UTC/Carrier, No. 62 at p. 7) AHRI,
Lennox, ADP, Goodman, Nortek, and Rheem commented that the requirement
to add reporting of SHR adds an excessive burden. (AHRI, No. 70 at p.
10; Lennox, No. 61 at p. 9; ADP, No. 59 at p. 7; Goodman, No. 73 at p.
14; Nortek, No. 58 at p. 7: Rheem, No. 69 at p. 8) ADP further
commented that adding a requirement for SHR is significant for those
OUM and ICM ratings developed by AEDMs, as manufacturers may not have
this capability in their current AEDM. (ADP, No. 59 at p. 7) JCI
further commented that the agreement made between AHRI members and
advocates (presumably referring to the agreement in advance of the 2011
Direct Final Rule) was intended to encourage manufacturers to list SHR
in manufacturer technical literature, not to make it a certified value.
(JCI, No. 66 at p. 15-16)
---------------------------------------------------------------------------
\8\ This test is conducted with 115 [deg]F air entering the
outdoor coil, see AHRI 210/240-2008, Table 13.
---------------------------------------------------------------------------
After reviewing these comments, DOE agrees that the joint proposal
from stakeholders that served as the basis for the 2011 Direct Final
Rule regarding central air conditioners stated that manufacturers would
make the SHR at 82 [deg]F (at the rated airflow) available in in
manufacturer technical literature and Web sites but that the SHR would
not be verified or certified by AHRI. The parties agreed that DOE did
not need to take regulatory action to implement this information
sharing. (Docket No. EERE-2011-BT-STD-0011, No. 16 at p. 7) DOE did not
account for this agreement in the November 2015 SNOPR, and in response
to stakeholder comment within this docket, proposed to require
reporting of SHR. However, given the existing stakeholder agreement
that underlay the 2011 Direct Final Rule, DOE is not adopting the
proposed requirement to certify SHR.
AHRI, ADP, Lennox, UTC/Carrier, Ingersoll Rand, JCI, Nortek, Rheem,
Goodman, and Mitsubishi did not support the additional reporting
requirements proposed by DOE and commented that they are a significant
burden on manufacturers. (AHRI, No. 70 at p. 13-15; ADP, No. 59 at p.
7; Lennox, No. 61 at p. 14-15; UTC/Carrier, No. 62 at p. 7; Ingersoll
Rand, No. 65 at p. 12; JCI, No. 66 at p. 15; Nortek, No. 58 at p. 11;
Rheem, No. 69 at p. 7; Goodman, No. 73 at p. 14, 19; Mitsubishi, No. 68
at p. 2-3) AHRI, Lennox, UTC/Carrier, Nortek, JCI, Rheem, Goodman, and
Mitsubishi also commented that some of the required data is proprietary
and puts the manufacturer at risk. (AHRI, No. 70 at p. 13-15; Lennox,
No. 61 at p. 14-15; UTC/Carrier, No. 62 at p. 7; Nortek, No. 58 at p.
11; JCI, No. 66 at p. 12; Rheem, No. 69 at p. 7; Goodman, No. 73 at p.
14, 19; Mitsubishi, No. 68 at p. 2) JCI and Mitsubishi expressed
concern that confidential information could be revealed in a FOIA
request. (JCI, No. 66 at p. 12; Mitsubishi, No. 68 at p. 2)
AHRI and Lennox each provided a list of information that they
support DOE requiring. (AHRI, No. 70 at p. 13-14; Lennox, No. 61 at p.
14-15) Unico agreed in its comments with AHRI's position on the
reporting burden associated with the certification reporting
requirements. (Unico, No. 63 at p. 6) Nortek commented that it supports
DOE requiring information that is already being submitted to AHRI for
purposes of certification. (Nortek, No. 58 at p. 10-11) Mitsubishi
commented that manufacturers should not be required to provide any
physical information that is not needed to test the system.
(Mitsubishi, No. 68 at p. 3) JCI commented that the only additional
reporting information that should be added to the certification report
is the off mode standby metric, and that no other unregulated items
should be added. (JCI, No. 66 at p. 12)
Some stakeholders listed specific information that DOE should not
require manufacturers to report. AHRI, Rheem, and JCI commented that
DOE should not require manufacturers to report the orientation of a
product's indoor coils and that, rather than reporting the process for
manually entering the defrost cycle to DOE, manufacturers should
describe that process in the product instructions. (AHRI, No. 70 at p.
13; Rheem, No. 69 at p. 7-8; JCI, No. 66 at p. 12) AHRI commented that
for variable speed products, compressor frequency set points are
proprietary to the manufacturer and therefore should not be reported to
DOE. (AHRI, No. 70 at p. 15) Rheem commented that variable speed heat
pump minimum and maximum speed blocks are proprietary and therefore
should not be reported. (Rheem, No. 69 at p. 7-8) Goodman commented
that their product nameplates do not explicitly state nominal capacity,
nor do the majority of their competitors' products. Goodman recommended
that the manufacturer provide the specific model numbers of the indoor
unit tested rather than nominal capacity of each indoor unit. (Goodman,
No. 73 at p. 6) Goodman also suggested that, instead of requiring
manufacturers to solely report the general type of expansion device,
DOE should require that manufacturers submit the same information (for
fixed orifices, the orifice inside dimension (I.D.) and length; or, for
expansion valves, the part number or model number) manufacturers
currently submit to AHRI for each individual combination of a
split[hyphen]system air conditioner or split[hyphen]system heat pump.
(Goodman, No. 73 at p. 3-5)
Rheem commented that the addition of the requirement to certify
airflow and CD is a significant certification burden on
manufacturers. Rheem noted that the documentation of the values
measured during the test of a single sample cannot be applied to a
second test, and that the averages of multiple measured values are even
less applicable. Rheem stated that the certification of CD
requires that manufacturers provide a conservative value that would be
applied to multiple test samples. Rheem suggested that the
certification of a product should be based on actual product
performance, as the use of a certified value of CD would
[[Page 37014]]
increase the variability of the test procedure and require more
conservative ratings and redesign of minimum efficiency equipment.
(Rheem, No. 69 at p. 7)
After reviewing the stakeholders' comments, DOE maintains that the
certification reporting requirements proposed in the November 2015
SNOPR, except for SHR as previously discussed, are necessary for DOE to
be able to conduct testing. None of the commenters indicated how DOE
could properly conduct testing without the requested information. In
the November 2015 NOPR, DOE proposed that this information would not be
made available on the DOE public Web site. While the information may be
subject to Freedom of Information Act (FOIA), DOE will seek to protect
this information to the extent legally permissible.
For these reasons, DOE has adopted these requirements in the final
rule, with minor modifications as discussed in relevant sections. In
response to Goodman, DOE notes that the model numbers of indoor units
are required in addition to nominal capacity, which is needed to verify
appropriate unit selection used for certification testing. DOE also
declines to require additional information beyond the type of expansion
device, as DOE does not need this information to conduct testing. In
response to Rheem, as noted in section III.A.7, DOE is only requiring
manufacturers to report whether they used a default value for
CD or whether they conducted the optional test;
manufacturers do not have to report the CD value used.
In their comments, the California IOUs requested that DOE require
the reporting of all test results that are inputs to the calculation of
SEER and HSPF. In addition, they requested that DOE collect the results
of the AHRI Maximum Operational Conditions tests, which they
acknowledge would require adding these tests to Appendix M/M1. As in
the case of SHR, they argued that this would not add to the test
burden; it would only add the additional reporting of results, because
all the measurements required to calculate SHR (e.g., indoor air flow
and indoor entering and leaving air conditions) are required as part of
the current test. The California IOUs argued that consumers, incentive
programs, and energy efficiency building codes need to have SEER and
HSPF values that are calculated for specific climatic regions to
enhance the value of the published SEER and HSPF that are calculated
for climatic region 4. They said this would support the fair comparison
of system performance and annual energy use costs. (California IOUs,
No. 67 at p. 3-4)
In this final rule, DOE declines to add the additional reporting
requirements recommended by the California IOUs as these are not
necessary for DOE testing, and existing programs currently operate
without the additional detail requested.
6. Represented Values
In the November 2015 SNOPR, DOE proposed to make several additions
to the represented value requirements in 10 CFR 429.16. First, DOE
proposed adding a requirement that the represented values of cooling
capacity, heating capacity, and sensible heat ratio (SHR) must be the
mean of the values measured for the sample. Second, DOE proposed to
move the provisions currently in 10 CFR 430.23 regarding calculations
of various measures of energy efficiency and consumption for central
air conditioners to 10 CFR 429.16. DOE proposed minor changes to the
calculations of annual operating cost to address other changes proposed
in Appendix M. 80 FR 69278, 69291 (Nov. 9, 2015).
Lennox, ADP, and UTC/Carrier commented that SHR is currently
published by manufacturers and that there is no benefit to adding a
single point SHR as a represented value potentially subject to
enforcement. (Lennox, No. 61 at p. 9; ADP, No. 59 at p. 7; UTC/Carrier,
No. 62 at p. 8) On the other hand, Unico supported the requirement to
submit SHR but only for reporting purposes, not for testing and
enforcement. (Unico, No. 63 at p. 6)
Although DOE has determined that manufacturers should not be
required to report SHR (see section III.A.5), DOE is adopting
requirements on the represented values for SHR as proposed, in order to
generate consistency in any representations of SHR made by industry.
AHRI, Lennox, JCI, Ingersoll Rand, Goodman, UTC/Carrier, and Nortek
disagreed with the requirement that the represented capacity values
must be the mean of the tested values, and recommended that DOE allow
manufacturers to rate capacity conservatively. (AHRI, No. 70 at p. 10;
Lennox, No. 61 at p. 8, 15; JCI, No. 66 at p. 15-16; Ingersoll Rand,
No. 65 at p. 5; Goodman, No. 73 at p. 15; UTC/Carrier, No. 62 at p. 8;
Nortek, No. 58 at p. 6) Rheem similarly commented that the addition of
the requirement to certify cooling capacity and heating capacity is a
significant certification burden and does not allow for manufacturers
to rate capacity conservatively. (Rheem, No. 69 at p. 8) Nortek
commented that DOE's proposal adds significant and unnecessary
increased risk to a manufacturer due to increased exposure from
enforcement testing. (Nortek, No. 58 at p. 6)
In its comments, Goodman noted that there is variability from
sample to sample in any population of units. (Goodman, No. 73 at p. 15)
Lennox commented that DOE's proposed use of mean values adds
unnecessary risk and complexity in associated voluntary industry
certification programs (VICP), such as AHRI. Lennox commented that
manufacturers face stringent penalties through the AHRI VCIP program in
the event of failure, and that manufacturers manage their financial and
market risk through conservative ratings. Although DOE and VICPs may
have different parameters for capacity metrics, Lennox believed DOE's
proposal adds unnecessary complexity, which may confuse the consumer
and bring into question the validity of different represented capacity
values in the VICP program versus the DOE CCMS value. (Lennox, No. 61
at p. 8-9)
AHRI, Lennox, and JCI disagreed with DOE's proposal, stating that
eliminating the conservative rating capacity would impact current
ratings, which would require re-rating products. They contended that
this requirement represents a significant and unnecessary burden that
has no value to the consumer. (AHRI, No. 70 at p. 10; Lennox, No. 61 at
p. 8; JCI, No. 66 at p. 7)
Several commenters recommended alternatives to DOE's proposal.
Ingersoll Rand recommended that the average capacity on which to base
the appropriate standard be determined using the same statistical
method as used for determining SEER, but that the manufacturers be
allowed to claim up to 5 percent lower in their rating. (Ingersoll
Rand, No. 65 at p. 5) UTC/Carrier commented that the current procedure
of using the mean or the statistically adjusted mean should be used and
manufacturers should be able to de-rate the certified values as
necessary to account for testing uncertainties in the audit facility as
well as the manufacturer's test facility. (UTC/Carrier, No. 62 at p. 8)
AHRI and Nortek commented that instead of implementing the mean of
measured values for capacity, any represented value of the energy
efficiency or other measure of energy consumption for which consumers
would favor higher values should be less than or equal to the lower of:
(1) The mean of the sample, or (2) the lower 90 percent confidence
limit (LCL) of the true mean divided by 0.95. (AHRI, No. 70 at p. 10;
[[Page 37015]]
Nortek, No. 58 at p. 6-7) DOE understands that AHRI and Nortek
supported DOE applying this approach to capacity as well.
After reviewing the comments, DOE is updating its proposal from the
November 2015 SNOPR, which required represented values of cooling and
heating capacity to be the mean of the sample. In this Final Rule, DOE
is requiring the represented value of cooling (or heating) capacity to
be a self-declared value that is no less than 95 percent of the mean of
the cooling (or heating) capacities measured for the units in the
sample selected for testing. This will allow manufacturers the
flexibility to derate capacity with conservative values as requested by
multiple commenters, while still providing consumers with information
that is reasonably close to the performance they may expect when
purchasing a system.
Goodman commented that DOE provided no guidance on how to treat
systems rated by AEDM and that it is unreasonable to expect
manufacturers to always rate at the exact value developed by a computer
program. (Goodman, No. 73 at p. 15)
DOE agrees with Goodman. DOE's intent had been for represented
values for systems rated by testing or AEDM to be determined similarly
but had inadvertently left this requirement out of the AEDM portion of
the regulatory text. To parallel the provision adopted for tested
combinations, DOE is adopting a provision that the represented value of
cooling (or heating) capacity must be no less than 95% of the cooling
(or heating) capacity output simulated by the AEDM. DOE notes that, if
a manufacturer believes the capacity predicted by the AEDM is more than
5% off of what the manufacturer would otherwise expect, then the
manufacturer should be evaluating the validity of the AEDM in other
respects.
Finally, DOE notes that Annual Performance Factor (APF) is not used
for any regulatory program, and therefore DOE has removed all
calculations and represented value requirements for APF in this final
rule.
7. Product-Specific Enforcement Provisions
In the November 2015 SNOPR, DOE proposed to verify certified
cooling capacity during assessment or enforcement testing. DOE proposed
to measure the cooling capacity of each tested unit pursuant to the
test requirements of 10 CFR part 430. If the measurement is within five
percent of the certified cooling capacity, DOE would use the certified
cooling capacity as the basis for determining SEER. Otherwise, DOE
would use the measured cooling capacity as the basis for determining
SEER. 80 FR 69278, 69292 (Nov. 9, 2015).
DOE also proposed to require manufacturers to report the cyclic
degradation coefficient (CD) value used to determine
efficiency ratings. DOE proposed to run CD testing as part
of any assessment or verification testing, except when testing an
outdoor unit with no match. If the measurement is 0.02 or more greater
than the certified value, DOE would use the measurement as the basis
for calculation of SEER or HSPF. Otherwise, DOE would use the certified
value. For models of outdoor units with no match, DOE would always use
the default value. 80 FR 69278, 69292 (Nov. 9, 2015).
Lennox, UTC/Carrier, Rheem, and JCI disagreed with DOE's proposal
to use rated values in cooling capacity and in CD testing.
The commenters proposed that tested capacity and cyclic test values
should be used in all determinations of efficiency and compliance.
(Lennox, No. 61 at p. 9; UTC/Carrier, No. 62 at p. 8; Rheem, No. 69 at
p. 2; JCI, No. 66 at p. 8) Rheem commented that the proposal to enforce
SEER using certified values of cooling capacity and CD has
not been justified or shown to provide representative and repeatable
results. (Rheem, No. 69 at p. 8) Unico supported the requirement to
submit cooling capacity and heating capacity but only for reporting
purposes, not for testing and enforcement. (Unico, No. 63 at p. 6)
In its comments, Lennox explained that, given the variability in
component and manufacturing processes, product capacity and power can
vary slightly from unit to unit. According to Lennox, if products are
manufactured within the acceptable limits, the variations in capacity
and power tend to be linear. Lennox added that DOE's proposal to fix
capacity to the rated value in determining efficiency if measured
within five percent of rating while allowing power to be a variable
from the tested value can result in both false pass and fail results.
(Lennox, No. 61 at p. 9-10) Lennox also commented that cyclic
CD testing is prone to variation from test to test on the
same unit within the same facility--let alone lab to lab, and that the
industry has spent a tremendous amount of resources studying
variability issues and has developed recommendations for lab
improvement. In particular, Lennox commented, the industry has
developed a method for compensating for differences in thermal mass of
the test facility used for testing. (Lennox, No. 61 at p. 10)
Nortek and JCI commented that the proposal to use a tolerance to
determine if measured capacity is within 5 percent of rated capacity
and from there, determining efficiency, would make it necessary for
manufacturers to report capacity at all points necessary to determine
SEER and HSPF. (Nortek, No. 58 at p. 7; JCI, No. 66 at p. 7-8) JCI
commented that this is an increased burden of reporting without
additional value. (JCI, No. 66 at p. 7-8) In addition to this burden,
Nortek expressed concern that this could lead to overrating capacity.
As efficiency is not tied to capacity, Nortek stated it is unsure of
the purpose of this proposal and would like DOE to clarify the purpose.
(Nortek, No. 58 at p. 7)
Goodman commented that DOE's proposal to use certified rather than
tested values conflicts with DOE's acknowledgement that individual unit
performance varies from sample to sample due to both individual unit
production differences as well as testing differences. Goodman noted
that compressor suppliers would only certify the performance of their
product to manufacturers to a 5% tolerance. Goodman
commented that from a statistics perspective, it is not correct to
suggest that in order to determine the true mean of a population that
modified values would be used from actual measurements. Goodman
strongly opposed DOE's proposed regulatory language in reference to the
assessment and enforcement testing of HVAC products as it pertains to
assumed average performance values in the determination of the
performance of an individual unit. Goodman strongly suggested that DOE
omit the proposed 10 CFR 429.134(g) in its entirety. (Goodman, No. 73
at p. 21)
After reviewing the comments, DOE is adopting modifications from
its proposal. For cooling capacity, DOE will use the mean of any DOE
test measurements to determine SEER. DOE notes that this adopted
modification, by eliminating the comparison to the manufacturer's
represented value, addresses JCI's concern about additional reporting
burden and Goodman's concern about using modified (certified) values
rather than actual measurements. In addition, DOE's modification
related to the represented value for capacity, in section III.A.6,
addresses Nortek's concern about overrating.
In addition, DOE wishes to clarify that when calculating SEER
values, manufacturers must use the tested capacity value, not the
certified capacity value.
For the CD value, in section III.E.11, based on
stakeholder comments, DOE
[[Page 37016]]
has decided to allow manufacturers to use the default value without
testing. The default value is conservative, and DOE believes that
manufacturers will only opt to test if it will improve upon the default
value for that model. DOE will follow the lead of the manufacturer in
determining whether to use the default value or to test a given unit.
Therefore, instead of reporting the CD value used, the
manufacturer must report whether the optional tests were conducted to
determine the CD value or whether the default value was
used. If manufacturers report using the default value, DOE will also
use the default value. If manufacturers conduct optional testing, DOE
will also conduct testing to determine CD. The result for
each unit tested (either the tested value or the default value, as
selected according to the criteria for the cyclic test in 10 CFR part
430, subpart B, Appendix M, section 3.5e) will be used to determine the
applicable standards for purposes of compliance.
B. Alternative Efficiency Determination Methods
1. General Background
For certain consumer products and commercial equipment, DOE's
existing regulations allow the use of an alternative efficiency
determination method (AEDM) or alternative rating method (ARM), in lieu
of actual testing, to estimate the ratings of energy consumption or
efficiency of basic models by simulating their energy consumption or
efficiency at the test conditions required by the applicable DOE test
procedure. The simulation method permitted by DOE for use in rating
split-system central air conditioners and heat pumps, in accordance
with 10 CFR 429.70(e), is referred to as an ARM. In contrast to an
AEDM, an ARM must be approved by DOE prior to its use.
DOE published a Notice of Proposed Rulemaking (AEDM NOPR) in the
Federal Register on May 31, 2012. 77 FR 32038. In the AEDM NOPR, DOE
proposed the elimination of ARMs, and the expansion of AEDM
applicability to those products for which DOE allowed the use of an ARM
(i.e., split-system central air conditioners and heat pumps). 77 FR at
32055. Furthermore, DOE proposed a number of requirements that
manufacturers must meet in order to use an AEDM, as well as a method
that DOE would employ to determine if an AEDM was used appropriately
along with specific consequences for misuse of an AEDM. 77 FR at 32055-
56. DOE subsequently published a final rule, related to commercial HVAC
equipment only, on December 31, 2013 (78 FR 79579).
In the November 2015 SNOPR, DOE proposed modifications to the
central air conditioner and heat pump AEDM requirements that were
proposed in the AEDM NOPR. 80 FR 69278, 69292 (Nov. 9, 2015). In
response to DOE's proposal, AHRI, Nortek, and Ingersoll Rand
recommended that DOE align the CAC/HP AEDM proposal with commercial
equipment AEDM provisions because the commercial and residential
technologies, testing methods, and simulation approaches were nearly
identical. (AHRI, No. 70 at p. 9; Nortek, No. 58 at p. 5; Ingersoll
Rand, No. 65 at p. 11)
In response to that comment, DOE notes that its proposal was based
off the commercial equipment AEDM provisions with slight modifications
appropriate to the residential product, and as such declines to make
the AEDM provisions identical to those for commercial equipment.
However, revisions to specific aspects of the proposal based on
stakeholder comments are discussed in subsequent sections.
First Co. commented that the DOE's proposed modifications in the
November 2015 SNOPR require manufacturers to develop an AEDM for heat
pumps. First Co. noted that any AEDMs used by an ICM to rate systems
would require coefficient data from the OUM, which is not required to
be publicly disclosed and which is not currently available to ICMs.
First Co. commented that this issue must be addressed in the rule.
(First Co., No. 56 at p. 1)
In response to First Co.'s comment, DOE notes that its proposal in
the November 2015 SNOPR did not require use of an AEDM. 80 FR 69278,
69292 (Nov. 9, 2015). Manufacturers may choose to test all individual
combinations within a basic model rather than applying an AEDM.
Therefore, DOE has not made any changes to its proposal in response to
First Co.'s concerns.
AHRI, ADP, Mortex, and Lennox commented that, for ICMs, certified
ratings must be less than or equal to AEDM output. (AHRI, No. 70 at p.
5-6; ADP, No. 59 at p. 2-3; Mortex, No. 71 at p. 4-6; Lennox, No. 61 at
p. 5)
In response, DOE notes that in 10 CFR 429.16, DOE adopted the
requirement that represented values of efficiency must be less than or
equal to the output of the AEDM, while represented values of power must
be greater than or equal to the output of the AEDM. In addition, under
10 CFR 429.70(a), represented values must never be ``better'' (overrate
efficiency or underrate consumption) than the output of the AEDM. These
requirements apply to all manufacturers, not just ICMs.
2. Terminology
In the AEDM NOPR, DOE proposed to eliminate the term ``alternate
rating method'' (ARM) and instead use the term ``alternative efficiency
determination method'' (AEDM) to refer to any modeling technique used
to rate and certify covered products. 77 FR 32038, 32040 (May 31,
2012). In the November 2015 SNOPR, DOE continued to propose the use of
one term, AEDM, to refer to all modeling techniques used to develop
certified ratings of covered products. 80 FR 69278, 69293 (Nov. 9,
2015).
Lennox, Goodman, Ingersoll Rand, and AHRI supported DOE's proposal
to eliminate the term ``ARM'' and instead use the term ``AEDM.''
(Lennox, No. 61 at p. 7; Goodman, No. 73 at p. 7; Ingersoll Rand, No.
65 at p. 11; AHRI, No. 70 at p. 9) There, DOE has eliminated the term
``ARM'' in this final rule, using only ``AEDM.''
3. Elimination of the Pre-Approval Requirement
In the November 2015 SNOPR, DOE proposed to eliminate the pre-
approval process for ARMs for split-system central air conditioners and
heat pumps. In lieu of this, DOE also proposed that manufacturers may
only apply an AEDM if it (1) is derived from a mathematical model that
estimates performance as measured by the applicable DOE test procedure;
and (2) has been validated with individual combinations that meet
current Federal energy conservation standards (as discussed in the next
section). Furthermore, DOE proposed records retention requirements and
additional manufacturer requirements to permit DOE to audit AEDMs
through simulations, review of data and analyses, and/or certification
testing. 80 FR 69278, 69294 (Nov. 9, 2015).
Lennox agreed that elimination of the pre-approval for AEDMs could
reduce time to market, facilitate innovation, and eliminate the time
required to complete the approval process. (Lennox, No. 61 at p. 7) In
this final rule, DOE has eliminated the pre-approval requirement as
proposed in the November 2015 SNOPR.
4. AEDM Validation
a. Outdoor Unit Manufacturers
In the November 2015 SNOPR, DOE noted that in its proposed
revisions to the determination of certified ratings for central air
conditioners and heat pumps,
[[Page 37017]]
manufacturers must test each basic model. Specifically for split-system
air conditioners and heat pumps, OUMs must test each model of outdoor
unit with at least one model of indoor unit (highest sales volume).
Manufacturers would only be able to use AEDMs for other individual
combinations within the same basic model--in other words, other
combinations of models of indoor units with the same model of outdoor
unit. In the November 2015 SNOPR, DOE did not seek to require
additional testing to validate an AEDM beyond what is proposed under 10
CFR 429.16(a)(1)(ii). 80 FR 69278, 69294 (Nov. 9, 2015).
DOE also proposed in the November 2015 SNOPR to adopt test
requirements similar to those used for AEDM validation for commercial
HVAC and water heating equipment, as published in the AEDM final rule
78 FR 79579, 79584 (Dec. 31, 2013). Specifically, DOE proposed that (1)
for energy-efficiency metrics, the predicted efficiency using the AEDM
may not be more than 3 percent greater than that determined through
testing; (2) for energy consumption metrics, the predicted efficiency
using the AEDM may not be more than 3 percent less than that determined
through testing; and (3) the predicted efficiency or consumption for
each individual combination calculated using the AEDM must comply with
the applicable Federal energy conservation standard. Furthermore, the
test results used to validate the AEDM must meet or exceed the
applicable Federal standards, and the test must have been performed in
accordance with the applicable DOE test procedure. If DOE has ordered
the use of an alternative test method for a particular basic model
through the issuance of a waiver, that alternative test method should
apply in lieu of the DOE test procedure. 80 FR 69278, 69296 (Nov. 9,
2015).
In the November 2015 SNOPR, DOE proposed a validation tolerance of
3 percent for AEDMs because the variability in a manufacturer's lab and
within a basic model should be more limited than lab-to-lab
variability. DOE proposed tolerances for verification testing of 5
percent to account for added lab-to-lab variability. 80 FR 69278, 69296
(Nov. 9, 2015).
ADP, Lennox, UTC/Carrier, Rheem, and Unico agreed with DOE's
proposal to not require additional testing to validate an AEDM beyond
the testing required under 429.16(a)(2)(ii) for split-system air
conditioners and heat pumps where manufacturers must test each basic
model--that is, each model of outdoor unit with at least one model of
HSV indoor unit. (ADP, No. 59 at p. 7; Lennox, No. 61 at p. 15; UTC/
Carrier, No. 62 at p. 8; Rheem, No. 69 at p. 8; Unico, No. 63 at p. 6)
Unico commented that single-split systems manufactured and rated by
an OUM should continue to validate their AEDM using the HSVC measured
results. (Unico, No. 63 at p. 6) The California IOUs commented that it
is critical that an AEDM be validated fully and in a manner that allows
DOE to use lab-testing data to disallow an AEDM if it is inaccurate.
(California IOUs, No. 67 at p. 4)
Lennox, JCI, AHRI, First Co., Ingersoll Rand, UTC/Carrier, Rheem,
and Nortek recommended that DOE align the CAC/HP AEDM validation
tolerance proposal with commercial equipment AEDM provisions of 5
percent. (Lennox, No. 61 at p. 8; JCI, No. 66 at pp. 3-4; AHRI, No. 70
at p. 9; First Co., No. 56 at p. 2; Ingersoll Rand, No. 65 at p. 11;
UTC/Carrier, No. 62 at p. 8; Rheem, No. 69 at p. 2; Nortek, No. 58 at
p. 5) AHRI, Lennox, JCI, and Nortek further commented that lab
variability is an inherent part of the testing process regardless of
whether all testing is conducted in a manufacturer's lab or lab-to-lab.
They asserted that the fundamental issue is that HVAC equipment relies
on accurate air property measurements (wet bulb/dew point) and the
variability of the test alone is greater than five percent. (AHRI, No.
70 at p. 9; Nortek, No. 58 at p. 5; JCI, No. 66 at pp. 3-4; Lennox, No.
61 at p. 8) AHRI and Nortek also commented that it is crucial that
manufacturers be permitted to apply the AEDM across basic models in
order to align the CAC/HP AEDM validation tolerance with the commercial
equipment AEDM provisions. (AHRI, No. 70 at p. 9; Nortek, No. 58 at p.
5)
Given the support in the comments related to AEDM validation for
OUMs, DOE maintains its proposal to not require any additional testing
to validate an AEDM beyond that required for certification. DOE notes
that while the proposal applied to split systems only, in this final
rule, it applies to single-package systems as well. After reviewing the
comments, DOE has adopted a validation tolerance of 4% rather than the
proposed 3%. DOE notes that manufacturers did not provide evidence of
the comparison of within-lab variability to lab-to-lab variability nor
did they request a higher verification tolerance, indicating that a 5%
tolerance appropriately captures lab-to-lab variability. In addition,
DOE notes that in its own enforcement testing, it obtains results
within 3%. For these reasons, DOE believes that a validation tolerance
of 4% balances the manufacturers' concerns regarding within-lab
variability with the understanding that such variability is by nature
less than lab-to-lab variability and with DOE's own experience with
such testing variability. In response to AHRI and Nortek's additional
comment, while at least one individual model or combination within each
basic model must be tested, DOE did not propose that AEDMs be specific
to basic models; they can be applied across basic models.
b. Independent Coil Manufacturers
In the November 2015 SNOPR, DOE noted that in its proposed
revisions to the determination of certified ratings for central air
conditioners and heat pumps, ICMs must test each model of indoor unit
with at least one model of outdoor unit (lowest SEER). Manufacturers
would only be able to use AEDMs for other individual combinations
within the same basic model. Additionally, DOE did not require
additional testing to validate an AEDM beyond that proposed to be
required to determine the certified ratings. 80 FR 69278, 69294 (Nov.
9, 2015). DOE also proposed the same additional test requirements for
ICMs as for OUMs, as discussed in the previous section. 80 FR 69278,
69296 (Nov. 9, 2015).
Rheem commented that ICMs should validate their AEDMs in the same
manner as an OUM. Rheem agreed that ICM ratings would improve when
indoor units are tested with outdoor units. Rheem further commented
that ICM ratings would also improve when a particular indoor coil is
tested with multiple outdoor units of different capacities and that the
process should properly consider what effects refrigerant mass flow
variations across tonnages have on the performance of a single indoor
unit. (Rheem, No. 69 at p. 8) UTC/Carrier also supported DOE's proposal
and appreciates DOE for closing what it perceived as a loophole in the
current regulations and requiring ICMs to test in a similar fashion to
OUMs. (UTC/Carrier, No. 62 at p. 9)
On the other hand, Unico commented that DOE should replace the term
``basic model'' with ``Similarity Group,'' essentially requiring AEDM
validation based on the testing requirements for a Similarity Group.
(Unico, No. 63 at p. 6) As discussed in section III.A.3.d, AHRI, ADP,
Mortex, and Lennox recommended that, to validate an AEDM, an ICM (1)
test and rate at least one combination per Similarity Group with an
outdoor unit with the lowest SEER that complies with standard; (2)
perform at least one full-system test per Similarity Group; (3) if
rating HP combinations, test one-third of
[[Page 37018]]
Similarity Groups with HP systems in both heating and cooling modes;
and (4) if an ICM has only one Similarity Group, the manufacturer must
test a minimum of two combinations to validate the AEDM. (AHRI, No. 70
at p. 5-6; ADP, No. 59 at p. 2-3; Mortex, No. 71 at p. 4-6; Lennox, No.
61 at p. 5)
AHRI, ADP, Mortex, and Lennox suggested that for ICMs to validate
an AEDM, test results should be required to be more than five percent
below output from the AEDM. The commenters noted that DOE has proposed
three percent on the supposition that a manufacturer's lab will have
less variation, but that many ICMs do not have labs and will rely on
external labs for testing and that there is no basis to suggest that
the testing variation will be significantly different between testing
commercial and consumer products. (AHRI, No. 70 at p. 5-6; ADP, No. 59
at p. 2-3; Mortex, No. 71 at p. 4-6; Lennox, No. 61 at p. 5)
AHRI, ADP, Mortex, and Lennox also suggested that ICMs only be
permitted to rate basic models within Similarity Groups validated by a
tested combination. (AHRI, No. 70 at p. 5-6; ADP, No. 59 at p. 2-3;
Mortex, No. 71 at p. 4-6; Lennox, No. 61 at p. 5)
As discussed in section III.A.3.d, DOE is adopting the suggested
Similarity Group requirements as the basic model definition for ICMs
and is requiring testing of one combination per basic model (with the
exception of heat pumps) according to the sampling plan in 429.16. With
these changes, DOE believes that the testing requirements for
certification remain sufficient for validating an AEDM. In addition,
DOE believes that the additional requirements on test data used for
validation address AHRI's concern regarding a need for additional
testing for ICMs with only a single Similarity Group. Therefore DOE is
not requiring ICMs to conduct any additional testing for AEDM
validation beyond that required for certification.
Furthermore, after reviewing these comments, DOE has adopted a
validation tolerance of four percent rather than the proposed 3
percent, for ICMs as well as OUMs.
In response to AHRI, ADP, Mortex, and Lennox, DOE notes that the
request that ICMs only be permitted to rate basic models within
Similarity Groups validated by a tested combination is consistent with
its adopted requirements regarding use and validation of AEDMs,
although in the adopted framework, manufacturers may only use AEDMs to
rate individual combinations within basic models validated by a tested
combination.
5. AEDM Verification Testing
DOE may randomly select and test a single unit of a basic model
pursuant to 10 CFR 429.104. This authority extends to all DOE covered
products, including those certified using an AEDM. In conducting
enforcement testing, DOE tests a retail unit or a unit provided by the
manufacturer if a retail unit is not available. 10 CFR 429.110(c). A
selected unit is tested using the applicable DOE test procedure at an
independent, third-party laboratory accredited to the International
Organization for Standardization (ISO)/International Electrotechnical
Commission (IEC), ``General requirements for the competence of testing
and calibration laboratories,'' ISO/IEC 17025:2005E. 10 CFR 429.110(a).
DOE may conduct testing at an independent, third-party testing facility
or a manufacturer's facility upon DOE's request if the former is not
capable of testing such a unit. 10 CFR 429.110(a).
In the November 2015 SNOPR DOE explained that verification testing
conducted by DOE is conducted with no communication between the lab and
the manufacturer without DOE authorization. 80 FR 69278, 69296 (Nov. 9,
2015). Thus, DOE proposed a method for determining that a combination
rated using an AEDM does not meet its certified rating. Specifically,
DOE proposed that an individual combination would be considered as
having not met its certified rating if, even after applying the five
percent tolerance between the test results and the rating as specified
in the proposed 10 CFR 429.70(e)(5)(vi), the test results indicate the
individual combination being tested is less efficient or consumes more
energy than indicated by its certified rating. DOE noted that this
approach will not penalize manufacturers for applying conservative
ratings to their products. That is, if the test results indicate that
the individual combination being tested is more efficient or consumes
less energy than indicated by its certified rating, DOE would consider
that individual combination to meet its certified rating. 80 FR 69278,
69296 (Nov. 9, 2015).
In the November 2015 SNOPR, DOE also proposed providing
manufacturers with a test report that includes a description of test
set-up, test conditions, and test results when an individual
combination rated using an AEDM fails to meet the certified rating.
Under this proposal, DOE would also provide the manufacturer with an
opportunity to respond to the lab report by presenting all claims
regarding testing validity, and if the manufacturer was not on-site for
initial set-up, to purchase an additional unit from retail to test
following the requirements in 429.110(a)(3). Under the proposed
procedure, DOE would consider any response offered by the manufacturer
within a designated time frame before deciding upon the validity of the
test results. Only after considering the manufacturer's response and
determining it to be unsatisfactory would DOE declare the
manufacturer's rating for the basic model invalid and require the
manufacturer to take subsequent action, as described in section
III.B.6. 80 FR 69278, 69297 (Nov. 9, 2015).
AHRI and Nortek commented that DOE's proposal was unclear regarding
the difference between AEDM validation testing and verification
testing. (AHRI, No. 70 at p. 9; Nortek, No. 58 at p. 5) In response,
DOE notes that manufacturers must conduct validation testing in order
to use an AEDM to determine represented values and to certify
compliance to DOE. DOE may conduct AEDM verification testing to verify
the validity of an AEDM.
ADP, Lennox, UTC/Carrier, and Unico agreed with DOE's proposal that
manufacturers should not be penalized for being conservative in their
ratings for any of the metrics. They stated that, given the testing
uncertainties, manufacturing variation, etc., manufacturers need to be
conservative to ensure their product performs at the rated level. (ADP,
No. 59 at p. 8; Lennox, No. 61 at p. 15; UTC/Carrier, No. 62 at p. 9;
Unico, No. 63 at p. 7) Rheem also agreed with the proposal to allow
conservative ratings. (Rheem, No. 69 at p. 9)
JCI and Lennox commented that there appears to be a typographical
error on (5) AEDM Verification Testing. (v) Tolerance. The text shows
``For efficiency metrics, the result from a DOE verification test must
be greater than or equal to 1.05 multiplied by the certified rating.''
JCI and Lennox believe the language should read: ``must be greater than
or equal to 0.95 multiplied by the certified rating''. (JCI, No. 66 at
p. 3; Lennox, No. 61 at p. 15)
Given the agreement of the commenters, DOE finalizes its proposed
five percent tolerance in verifying an AEDM's performance and allowance
for manufacturers to make conservative representations in this final
rule. In response to JCI and Lennox's comments, DOE acknowledges that
the November 2015 SNOPR included a typographical error in the
tolerances, which has been corrected in this final rule. DOE did not
receive comments on other aspects of its
[[Page 37019]]
AEDM verification testing proposals and adopts them as proposed in the
SNOPR.
6. Failure To Meet Certified Represented Values
In the November 2015 SNOPR DOE proposed that manufacturers need not
re-validate the AEDM in response to the first determination of an
invalid rating for models certified with that AEDM. In such cases, the
manufacturer must conduct additional testing and re-rate and re-certify
the individual combinations within the basic model that were improperly
rated using the AEDM. 80 FR 69278, 69297 (Nov. 9, 2015).
DOE also proposed that if DOE has determined that a manufacturer
made invalid ratings on individual combinations within two or more
basic models rated using the manufacturer's AEDM within a 24 month
period, the manufacturer must test the least efficient and most
efficient combination within each basic model in addition to the
combination specified in 429.16(a)(1)(ii). The twenty-four month period
begins with a DOE determination that a rating is invalid through the
process outlined above. If DOE has determined that a manufacturer made
invalid ratings on more than four basic models rated using the
manufacturer's AEDM within a 24-month period, the manufacturer may no
longer use an AEDM. 80 FR 69278, 69297 (Nov. 9, 2015).
DOE also proposed additional requirements for manufacturers to
regain the privilege of using an AEDM, including identifying the
cause(s) for failure, taking corrective action, performing six new
tests per basic model, and obtaining DOE authorization. 80 FR 69278,
69297 (Nov. 9, 2015).
DOE created its proposal under the expectation that each
manufacturer will use only a single AEDM for all central air
conditioner and central air conditioning heat pumps. Several
stakeholders responded to DOE's question on whether manufactures
typically apply more than one AEDM, and if they do, then what the
differences are between such AEDMs.
ADP commented that they use one AEDM. (ADP, No. 59 at p. 8) Unico
commented that a single AEDM may incorporate several calculation
methods, but that the AEDM should be designed to choose the most
accurate calculation method and is still one AEDM. (Unico, No. 63 at p.
7)
Lennox commented that while the concept of an AEDM's function is
the same, different AEDMs may be optimized for application, ease of
use, outputs or integration into other business processes. Lennox
recommended that AEDMs not be restricted to a singular application.
(Lennox, No. 61 at p. 15) UTC/Carrier suggested that multiple AEDMs
could be applied for different products, such as packaged systems
versus splits and variable speed versus single-stage. UTC/Carrier
argued that a dedicated AEDM would more accurately reflect product
performance for consumer benefit (UTC/Carrier No. 62 at p. 9) JCI
commented that they would likely utilize one AEDM for split AC units,
one for split HP units, and possibly one for single-package units, with
a possible additional one a two stage product and another for
multistage product. JCI stated the primary differences are the
additional simulation conditions and required additional input. (JCI,
No. 66 at p. 16) Rheem commented that manufacturers may choose to have
multiple AEDMs based on design technologies to ensure rating accuracy
for each technology, i.e., micro-channel vs. fin and tube performance
modeling. (Rheem, No. 69 at p. 9)
After reviewing the comments, DOE acknowledges that some
manufacturers may have more than one AEDM but will likely have fewer
than five. DOE believes that its proposal is still valid under these
circumstances and has adopted it as proposed. DOE has adopted a
requirement for manufacturers to provide a ``name'' for the AEDM used
to rate each individual model or combination, although for some
manufacturers it may be the same for all. If DOE finds that there is a
proliferation of AEDMs and that DOE's requirements for re-validation,
re-determination of represented values, and/or re-certification
following the failure of a model to meet its certified represented
value are no longer sufficient to ensure that represented values
generated with AEDMs are reliable, DOE may revisit these requirements.
AHRI and Nortek disagreed with the proposal to invalidate an AEDM
after four failures within 24 months and recommended that DOE implement
an option to ``save'' the HSVC and remaining basic model ratings,
similar to the provisions within the AHRI Certification Program. (AHRI,
No. 70 at p. 9; Nortek, No. 58 at p. 6) Ingersoll Rand recommended that
DOE adopt the AHRI proposal for additional testing should there be
``excessive'' failures of AEDM rated products. (Ingersoll Rand, No. 65
at p. 11) JCI commented that it appears that if a basic model is deemed
invalid that all mix match ratings associated with that basic outdoor
model would be made invalid and be required to be recertified. JCI
believes this is very punitive and does not take into account that the
invalid ratings may be due to other factors. JCI also agreed with other
commenters that there should be a method to ``save'' all of the other
mix match ratings associated with that basic outdoor model. (JCI, No.
66 at p. 4)
UTC/Carrier recommended that the number of failures in 24 month
period before the AEDM is invalidated should scale to the number of
basic models for that particular manufacturer. (UTC/Carrier, No. 62 at
p. 8)
Goodman expressed concern over the result of an initial assessment
test in which the basic model being tested failed to achieve its
ratings. Goodman commented that if the manufacturer is permitted to
review the setup of test arrangement before the test is finished, the
cause of failure could be eliminated. (Goodman, No. 73 at p. 7)
In response to AHRI, Nortek, and JCI, DOE's proposal does permit a
manufacturer to ``save'' all represented values with minimal effort at
the first failure and with additional testing at the second, third and
fourth failures. If, after all of that additional testing, the AEDM is
still not accurate, DOE is unsure what would be ``saved''. DOE notes
that the tested combination of each basic model would not have been
rated using the AEDM and thus would be unaffected by a failure of the
AEDM. In response to Ingersoll Rand, DOE views five failures in two
years as excessive, as DOE has already provided a 5% tolerance. In
response to UTC/Carrier, DOE disagrees that the number of failures
should scale to the number of basic models. DOE believes that if a
manufacturer has five basic models that test outside of the 5%
tolerance, especially following feedback from the four previous
failures, that there must be a significant problem with the AEDM. In
response to Goodman, DOE notes that although it has not provided an
allowance for a manufacturer to review the test set up prior to
testing, DOE will provide the manufacturer with documentation related
to the test set up and allows the manufacturer to present claims
regarding the validity. DOE believes this accomplishes the same result.
Unico commented that for ICM ratings, if a rating is invalid, if
the same basic model was tested and passed, only the system tested that
failed is re-rated. For an ICM, the same failure is not considered a
failure of the AEDM unless the outdoor unit has been tested and shown
to meet the OUM rating. Unico argued that, from an engineering view,
[[Page 37020]]
the calculation method should only be changed if the measured data is
[in]consistent with the AEDM input. Unico also expressed the view that,
since the ICM does not manufacture the outdoor unit, the ICM should not
be held responsible for the OUM information. According to Unico, ICM
ratings are likely to be doubly conservative if one considers that the
OUM ratings are conservative and this is added to the conservative ICM
rating. Unico also urged DOE to consider that the ratings are based on
tests of the outdoor unit (OUM basic model testing) and of the indoor
unit (ICM Similarity Group testing), asserting that this is more
testing than the OUM product alone. (Unico, No. 63 at p. 4)
In response to Unico, DOE does not agree that ICMs should have
different consequences for failures than OUMs. All manufacturers use
AEDMs at their own risk and are responsible for ensuring the accuracy
of the AEDM, including the accuracy of the testing used to validate the
AEDM.
7. Action Following a Determination of Noncompliance
If an individual model or combination is determined to be
noncompliant, then all other individual models or combinations within
that basic model are considered noncompliant. DOE's proposal in the
November 2015 SNOPR with respect to AEDMs did not include a provision
that other basic models rated with the AEDM would be considered
noncompliant. However, DOE noted that an AEDM must be validated using
test data for individual combinations that meet the current Federal
energy conservation standards. Therefore, if a noncompliant model was
used for validation of an AEDM, a manufacturer must re-validate the
AEDM with test data for a compliant basic model in order to continue
using the AEDM. The requirements for additional testing based on
invalid ratings, as discussed in the previous sections, may also apply.
80 FR 69278, 69298 (Nov. 9, 2015).
DOE notes that it did not receive comments related to this
discussion in the November 2015 SNOPR.
8. AEDM for Off Mode
In the November 2015 SNOPR, DOE listed several requirements a
manufacturer must meet to use an AEDM in certifying ratings, including
PW,OFF. 80 FR 69278, 69339 (Nov. 9, 2015).
AHRI, Ingersoll Rand, Nortek, Lennox, and JCI recommended that use
of an AEDM be permitted to generate ratings for off mode power across
units of similar construction. (AHRI, No. 70 at p. 9; Ingersoll Rand,
No. 65 at p. 4; Nortek, No. 58 at p. 5; Lennox, No. 61 at p. 7; JCI,
No. 66 at p. 9) Additionally, Lennox recommended that use of an AEDM be
permitted to generate ratings for off mode power for units that use the
same off mode components (Lennox, No. 61 at p. 7), while AHRI and
Nortek recommended that an AEDM be permitted to be used to generate
ratings across tonnages. (AHRI, No. 70 at p. 9; Nortek, No. 58 at p. 5)
Rheem recommended that manufacturers be permitted to use an AEDM to
generate ratings for off mode power across similar control systems that
would consume the same off-mode power. Rheem also expressed the view
that the AEDM should be validated based on testing of a single model
with the same control system. Rheem further commented that
manufacturers should be able to rate the off mode power consumption of
both single-package and split systems with varying compressors, coils,
and auxiliary refrigeration system components if the models are in the
same basic model or have common control and motor types. (Rheem, No. 69
at p. 3, 7)
DOE agrees with stakeholders that, for units with a similar pairing
of compressor, crankcase heater and common control, an AEDM is capable
of providing an off mode represented value without the manufacturer
needing to test each basic model. In response to the commenters'
request, DOE has eliminated the requirement to test each basic model
for off-mode power. Instead, at a minimum, among models with similar
off-mode construction (even spanning different basic models, a
manufacturer must test at least one individual model or combination for
off-mode power, and may use an AEDM for the rest. DOE notes that in all
cases, the AEDM-generated represented value may be subject to
verification testing, and thus the responsibility is on the
manufacturer to determine which model(s) or combination(s) should be
tested for off-mode as part of AEDM validation. DOE also notes that an
AEDM may be used for off-mode power for multi-split, multi-circuit, and
multi-head mini-split systems, even though an AEDM may not be used for
the efficiency metrics.
C. Waiver Procedures
In the November 2015 SNOPR, DOE stated that a total of four waivers
(and one interim waiver) for central air conditioner and heat pump
products would terminate 180 days after the publication of this final
rule notice in the Federal Register. 80 FR 69278, 69298-300 (Nov. 9,
2015). The waivers to be terminated are listed in Table III.4.
In the June 2010 NOPR, DOE proposed a test method for testing
Triple-Capacity Northern Heat Pumps which would replace the waiver test
procedure granted to Hallowell International (see 75 FR 6013 (Feb. 5,
2010)) for testing its line of boosted compression heat pumps. 75 FR at
31238 (June 2, 2010). The November 2015 SNOPR reproposed the same
procedure initially proposed in the June 2010 NOPR. 80 FR 69278, 69298
(Nov. 9, 2015). DOE did not receive comments regarding this test
procedure and is therefore finalizing it in this final rule. The
Hallowell waiver will terminate on December 5, 2016.
DOE received comments on the proposed test procedure revisions
related to waivers for Multi-Zone Unitary Small Air Conditioners and
Heat Pumps from ECR International (ECR) and Multi-blower Air-
Conditioning and Heating Equipment from Cascade Group. Additionally,
DOE has further reviewed the proposed approach for the waivers for air-
to-water heat pumps granted to Daikin for their Altherma heat pumps.
These waivers and associated comments are discussed in the following
sub-sections.
Table III.4--Waivers To Be Terminated
------------------------------------------------------------------------
Scope Decision & Order
------------------------------------------------------------------------
ECR International, Inc., (Petition & Interim Waiver, 78 FR 47681,
Multi-zone Unitary Small Air 8/6/2013).
Conditioners and Heat Pumps.
Daikin AC (Americas), Inc., 76 FR 11438, 3/2/2011.
Heat Pump & Water Heater
Combination.
Daikin AC (Americas), Inc., 75 FR 34731, 6/18/2010.
Heat Pump & Water Heater
Combination.
Hallowell International, 75 FR 6013, 2/5/2010.
Triple-Capacity Northern
Heat Pumps.
Cascade Group, LLC, Multi- 73 FR 50787, 8/28/2008.
blower Air-Conditioning and
Heating Equipment.
------------------------------------------------------------------------
[[Page 37021]]
1. Air-to-Water Heat Pumps and Air Conditioners
In the November 2015 SNOPR, DOE had determined that the Daikin
Altherma air-to-water heat pumps with integrated domestic water heating
rely exclusively on refrigerant-to-water heat exchange on the indoor
side, and thus would not be required to be tested and rated for the
purpose of compliance with DOE standards for central air conditioners
or heat pumps. 80 FR 69278, 69298 (Nov. 9, 2015). DOE received no
comment on these waivers.
DOE further considered the regulatory status of air-to-water heat
pumps and notes that EPCA defines Central Air Conditioner as ``a
product, other than a packaged terminal air conditioner, which--(A) is
powered by single phase electric current; (B) is air-cooled; (C) is
rated below 65,000 Btu per hour; (D) is not contained within the same
cabinet as a furnace the rated capacity of which is above 225,000 Btu
per hour; and (E) is a heat pump or a cooling only unit.'' (42 U.S.C.
6291(21)) The definition does not exclude products that transfer
cooling or heating to a water loop on the indoor side. Hence, DOE
concludes that these products are covered under regulations for CAC/HP.
DOE does agree that the existing test procedures for CAC/HP do not
fully address test methods for air-to-water systems. Specifically, they
do not provide instructions regarding how to set up the water loop in
the test, nor whether any power input associated with the water-based
thermal distribution system should be incorporated into the efficiency
metrics.
The Daikin waivers called for testing of the Altherma air-to-water
heat pumps using European standard EN 14511 to determine EER and COP,
and that these measurements are the only allowed representations of the
performance of these products. (See for example 75 FR 34731, 34733
(June 18, 2010).) DOE now considers these waivers to be invalid,
because they did not provide a method to determine SEER and HSPF, the
metrics that must be reported to DOE to certify compliance with the
applicable efficiency standards. Hence, these waivers are considered to
be terminated, effective immediately. DOE will work with manufacturers
of air-to-water heat pumps and air-to-water air conditioners as needed
to help develop test procedures for providing SEER, HSPF, and average
off-mode power represented values that may become the basis of
replacement waivers.
2. Clarification of the Test Procedure Pertaining to Multi-Circuit
Products
The ECR waiver for Multi-zone Unitary Small Air Conditioners and
Heat Pumps concerns a split system that has one outdoor unit with
multiple circuits. In the November 2015 SNOPR, DOE proposed to define
such a product as a multiple-circuit (or multi-circuit) system (see
Section 1.2 in Appendix M). The November 2015 SNOPR also proposed to
provide a test procedure for multi-circuit products using a common duct
approach for the indoor air flow measurement, similar to the approach
used for multi-split units (see Section 2.4.1.b in Appendix M), thus
allowing a single test for each operating condition. 80 FR 69278, 69299
(Nov. 9, 2015).
In their comments, AHRI and Nortek stated that multi-circuit
products are different than multi-split systems. According to AHRI and
Nortek, the outdoor unit has multiple separate circuits, each serving a
separate indoor unit. They commented that multi-circuit products should
be considered as multiple units whose outdoor portions are all
contained within one outdoor unit cabinet. (AHRI, No. 70 at p. 18;
Nortek, No. 58 at p. 14-15). AHRI and Nortek also commented that
utilizing a common duct at zero static pressure with indoor sections of
differing airflows will load the indoor sections unequally and may not
yield the same air flows as when individually ducted. AHRI and Nortek
commented that without each circuit having individual performance data
collected, the test would not reflect the true performance of the
system. Id.
Rheem stated that each circuit should be tested individually and
the efficiency certified separately but did not elaborate on this
comment. (Rheem, No. 69 at p. 9)
Lennox supported DOE's proposal of the common duct approach for
multi-circuit products. (Lennox, No. 61 at p. 16)
DOE believes that a multi-circuit system is a single unit rather
than multiple units, one for each circuit, as suggested by Rheem. All
of the individual circuits within the multi-circuit system share the
same outdoor coil and fan(s) and therefore are affected by the
operation of the other circuits. The outdoor unit containing the
multiple circuits is shipped as a single unit, not as separate units.
Therefore, DOE adopts its November 2015 SNOPR proposal to require
manufacturers to certify the multi-circuit system as a single system,
which is consistent with the existing ECR waiver.
DOE noted in the November 2015 SNOPR that the common duct testing
approach has been adopted by industry standards and is an accepted
method for testing systems, such as multi-split systems, having
multiple indoor units. 80 FR 69299 (Nov. 9, 2015). In fact, the indoor
units of multi-split systems do not all have the same capacity or air
flow rate. Hence, it is not clear why the common-duct approach is
suitable for multi-split systems but would not be suitable for multi-
circuit systems. In this final rule, DOE adopts the common-duct testing
approach proposed in the November 2015 SNOPR for multi-circuit systems.
However, considering that there might be manufacturers and/or test
laboratories that wish to use the approach of the waiver, in which
individual measurements are made for each indoor section, DOE has
modified the provisions in section 2.4.1.b for multi-circuit systems to
allow use of either the common-duct approach or separate air flow
measurement for each indoor unit of the multi-circuit system. Both
approaches should yield the same performance since all the indoor
sections are subject to the same external static pressure.
Because DOE has adopted test procedure amendments that allow multi-
circuit systems to be tested without a waiver, testing in accordance
with the ECR waiver may not be used for representations after 180 days
following publication of this final rule.
3. Clarification of the Test Procedure Pertaining to Multi-Blower
Products
The Cascade Group waiver concerns multi-blower products. The test
procedure amendments, as proposed in the June 2010 NOPR enable testing
of multi-blower products. 75 FR 31237 (June 2, 2010). In the November
2015 SNOPR, DOE proposed amending Appendix M to Subpart B of 10 CFR
part 430 with language in sections 3.1.4.1.1d and 3.1.4.2e to provide
detailed instructions on obtaining the Cooling full-load air volume
rate and cooling minimum air volume rate. 80 FR 69278, 69300 (Nov. 9,
2015).
In response to DOE's November 2015 SNOPR, Rheem stated that, if
there are options for obtaining the maximum or minimum airflow
configuration, the option for each with the highest energy consumption
should be tested. (Rheem, No. 69 at p. 9)
DOE notes that in tests for products other than multi-blower
systems, the test procedures do not require use of the most energy-
consumptive control setting options to achieve the specified air flow
rates. Hence, DOE declines to require this approach for multi-blower
[[Page 37022]]
products. Therefore, DOE adopts the test approach initially proposed in
the June 2010 NOPR and modified in the November 2015 SNOPR.
Because DOE has adopted test procedure amendments that allow multi-
blower systems to be tested without a waiver, testing in accordance
with the Cascade Group waiver may not be used for representations after
180 days following publication of this final rule.
D. Measurement of Off Mode Power Consumption
In the June 2010 NOPR, DOE proposed a first draft of testing
procedures and calculations for off mode power consumption. 75 FR
31223, 31238 (June 2, 2010). In the following April 2011 SNOPR, DOE
proposed a second draft, revising said testing procedures and
calculations based on stakeholder-identified issues and changes to the
test procedure proposals in the 2010 June NOPR and on DOE-conducted
laboratory testing. 76 FR 18105, 18111 (April 1, 2011). In the October
2011 SNOPR, DOE proposed a third draft, further revising the testing
procedures and calculations for off mode power consumption based
primarily on stakeholder comments received during the April 2011 SNOPR
comment period regarding testing burden on manufacturers. 76 FR 65616,
65618-22 (Oct. 24, 2011). In the November 2015 SNOPR, DOE proposed a
fourth draft discussing and revising test settings and the calculation
method in response to stakeholders' comments. 76 FR 69278, 69300-05
(Nov. 9, 2015). Based on further comments DOE received in the November
2015 SNOPR comment period, DOE is modifying its approach and is
adopting the off mode test procedure.
1. Test Temperatures
In the November 2015 SNOPR, DOE proposed to require manufacturers
to include the temperatures at which the crankcase heater is designed
to turn on and turn off, if applicable, in their certification reports.
80 FR 69278, 69301 (Nov. 9, 2015). DOE proposed to replace the
``shoulder season'' off mode test (P1) at 82[emsp14][deg]F with a test
at 722[emsp14][deg]F and replace the ``heating season'' off
mode test (P2) at 57[emsp14][deg]F with a test at a temperature which
is 52[emsp14][deg]F below a manufacturer-specified turn-on
temperature. Id.
In response to the October 2011 SNOPR, the California IOUs
recommended that P1 be measured at a temperature that is 3-5 [deg]F
above the manufacturer's reported ``off'' set point. (California IOUs,
No. 33 at p. 2) DOE requested comment on this recommendation in the
December 2011 extension notice. 76 FR 79135 (Dec. 21, 2011). AHRI
responded to the California IOUs' recommendation, indicating that the
first test should instead be conducted at 72[emsp14][deg]F to verify
whether the crankcase heater is on, and suggesting that 72 [deg]F is
more appropriate than 82 [deg]F because 72 [deg]F is ``the top of the
shoulder season.'' (AHRI, No. 41 at p. 2) In response to the November
2015 SNOPR, Rheem expressed its preference for the shoulder season off
mode test to be at 822[emsp14][deg]F instead of 722[emsp14][deg]F in order to reduce the test condition
transitioning time after the B test. (Rheem, No. 69 at p. 9)
Although DOE acknowledges that there may be added test burden to
reduce the temperature in the test room, DOE agrees with AHRI that
72[emsp14][deg]F is more representative of conditions during actual
use. Accordingly, today's final rule adopts the requirement that this
test be conducted at 722[emsp14][deg]F. There were no
comments against the proposal to replace the ``heating season'' off
mode test (P2) at 57[emsp14][deg]F with a test at a temperature which
is 52[emsp14][deg]F below a manufacturer-specified turn-on
temperature. Hence, DOE adopts the proposal in this final rule.
Ingersoll Rand requested an option that off mode tests be allowed
to take place in a climate controlled enclosure rather than a
psychrometric room. (Ingersoll Rand, No. 65 at p. 4) In considering
this suggestion, DOE noticed that, although the proposed test procedure
does not specify that off mode tests should be conducted in
psychrometric rooms, the proposed procedure requires off mode tests be
done after the B, B1, or B2 test, thus implying
that it be conducted in a psychrometric room. DOE agrees that the off
mode test results will not be affected by humidity levels. The proposal
of the November 2015 SNOPR involves conducting the off mode test after
the B, B1, or B2 test, and approaching the target
72[emsp14][deg]F test temperature at a rate of change of no more than
20 [deg]F per hour. 80 FR 69278, 69374 (Nov. 9, 2015). The test
procedure in this final rule modifies this procedure by allowing the
off mode test to be conducted in a temperature-controlled room, but to
otherwise maintain the proposed requirements with regard to ambient
temperature, i.e. starting the test when the ambient temperature is 82
[deg]F (as required for the B, B1, or B2 test)
and subsequently ramping down the ambient temperature as required by
the proposed procedure. The final test procedure also acknowledges the
initial intent to conduct the test after the B, B1, or
B2 test by requiring that the compressor shell temperature
be at least 81 [deg]F before starting the ambient-temperature rampdown.
This requirement prevents a test lab from moving a test sample from a
storage room that might be much colder than 82 [deg]F into the test
room and starting the test with a cold compressor.
Lennox suggested that DOE allow manufacturers to simply energizing
the crankcase heater for non-variable type heaters to reduce the test
burden, so that such units could be tested with no temperature control
requirement. (Lennox, No. 61 at p. 16) In considering Lennox's comment,
DOE agrees that this option could be adopted for many fixed-power-input
crankcase heaters, including those without controls and those
controlled by thermostats that measure ambient temperature whose
sensing elements are not affected by the heater. However, DOE
understands that, if the thermostat's action is affected by the
crankcase heater's heat output (i.e. if the sensing element is close
enough to the heater to be affected by the heat), the unit should be
tested with a controlled ambient temperature because in such cases the
ambient temperatures at which the thermostat switches the heater on and
off would differ from its rated cut-in and cut-out temperatures, due to
the warming effect of the heater.
Several comments recommended a third off-mode test at low
temperatures. JCI recommended for air conditioners whose crankcase
heaters are turned off during winter a third test at 5[emsp14][deg]F
below the winter cut-off temperature. (JCI, No. 66 at p. 16) The joint
NEEA/NPCC comment requested a third test below freezing to establish
the slope of a variable power crankcase heating system and to capture
the energy use of electric resistance drain pan heaters which could
consume considerable energy in off mode for conditions below freezing.
(NEEA and NPCC, No. 64 at p. 4) The joint ACEEE/NRDC/ASAP comment made
a similar recommendation (ACEEE, NRDC, ASAP, No. 72 at p. 3) As
mentioned in the November 2015 SNOPR, the intent of the off mode power
consumption value (PW,OFF) is that it be a representation of
the off mode power consumption for the shoulder and heating seasons,
and DOE has not found that the additional accuracy gained from the
additional test point merits the additional test burden, as discussed
in the November 2015 SNOPR. 80 FR 69278, 69301 (Nov. 9, 2015). As DOE
is required to consider test burden in its development of test
procedures, DOE is not adopting a third test in this final rule.
[[Page 37023]]
2. Calculation and Weighting of P1 and P2
DOE proposed to give equal weighting to P1 and P2 for the
calculation of the off mode power rating (PW,OFF). 76 FR 65616, 65620
(Oct. 24, 2011). (See also 80 FR 69278, 69301 (Nov. 9, 2015)).
The Joint Efficiency Advocates (NEEA and NPCC) strongly urged DOE
to adopt a temperature bin-weighting methodology that would include the
energy contribution of drain pan heaters and suggested considering the
AHRI-proposed bin method. (NEEA and NPCC, No. 64 at p. 5) The Joint
Advocates of ACEEE, NRDC and ASAP also recommended the bin method due
to their concern that the current averaging method would underestimate
the off mode power consumed for units with variable output crankcase
heaters. (ACEEE, NRDC and ASAP, No. 72 at p. 3) NEEA and NPCC also
commented that with manufacturers providing turn-on and turn-off
temperatures for crankcase heaters, it would be easy to construct a bin
method calculation. Further, they indicated that DOE has not shown data
to justify the selection of a 50-50 weighting of P1 and P2. (NEEA and
NPCC, No. 64 at p. 5)
DOE is aware that drain pan heaters may be used in heat pumps that
have drain pans to collect defrost melt water. However, heat pumps are
not considered to have off-mode hours in sub-freezing winter conditions
when drain pan heaters might be required. Their energy use is captured
as part of the active-mode heating tests in 17 [deg]F ambient
conditions (e.g. the H3, H31, and H32 tests) that
are part of the HSPF determination. To clarify, DOE has added a new
section 2.2.f to Appendix M that indicates that such heaters are
energized for active-mode testing.
DOE initially proposed to adopt the 50-50 weighting of the off mode
in the October 2011 SNOPR 75 FR at 65620 (Oct. 24, 2011). This decision
was made in light of disagreement regarding what represents an
appropriate shoulder season, concern about regional variation in
shoulder season characteristics, and the fact that EPCA did not grant
DOE authority to set regional off-mode standards. A 50-50 weighting of
P1 and P2 provides a representative national estimate of off mode power
input. Depending on the assumptions made regarding the shoulder season,
the climate region examined, whether the product is an air conditioner
or a heat pump, and the details of the crankcase heater control, the
relative representativeness of P1 and P2 may change. In light of this
variability and uncertainty, it is not clear that a bin calculation
would have more meaning than the 50-50 averaging. Therefore, DOE is
adopting the 50-50 weighting as proposed.
There were additional comments concerning the calculation of P1 and
P2 for products with variable speed compressors. Nortek, Unico, JCI,
Rheem, Goodman and AHRI each provided an estimate of 70 Watts for
variable speed products' crankcase heaters and commented that 70 Watts
is an accurate average value. They argued that, considering that the
standard single-capacity products' crankcase heaters require no more
than 40 Watts, the ratio of 70 to 40, which is 1.75, should be a
reasonable multiplier. (Nortek, No. 58 at p. 8; Unico, No. 63 at p. 9;
JCI, No. 66 at p. 9; Rheem, No. 69 at p. 10; AHRI, No. 70 at p. 11;
Goodman, No. 73 at p. 8) Lennox recommended that DOE adopt the same
requirement for modulating or variable speed systems as adopted for
multiple compressor systems, with a multiplier factor of 2. (Lennox,
No. 61 at p. 16)
In contrast, a joint comment from NEEA and NPCC and a comment from
the California IOUs disagreed with DOE's proposal to adjust the off-
mode measurements for large-capacity, multiple or modulated
compressors. NEEA and NPCC argued that appropriately-designed crankcase
heaters for large-capacity compressors should pass the off-mode
standard and that it is unnecessary to have a multiplier. (NEEA and
NPCC, No. 64 at p. 5) The California IOUs commented that off mode power
consumption should be on a per-system basis rather than per-compressor.
(California IOUs, No. 67 at p. 2-4)
Based on these comments, DOE is adopting 1.75 as the multiplier for
modulated compressors (including variable-speed compressors). DOE
adopts as the effective multiplier for a compressor system consisting
of multiple single-stage compressors a value equal to the number of
single-stage compressors. As addressed in the November 2015 SNOPR, DOE
believes that large-capacity and multiple-compressor systems require
higher wattage crankcase heaters because they are likely to have larger
surface area and more thermal mass, including more lubricant. Also,
manufacturers have been using higher-wattage crankcase heaters for
modulating compressors to address the higher perceived risk associated
with oil frothing on restart for these compressors, due to their higher
controls complexity. DOE does not have sufficient evidence that larger-
capacity, multiple-, or modulating compressor systems can operate
safely with the same levels of crankcase heating and hence retains the
multiplier for these compressors in the off-mode test. DOE agrees that
modulated compressors (including variable speed products) require more
crankcase heater power, and selected the 1.75 factor on this basis
(this is equal to the typical 70W mentioned above for variable-speed
compressors divided by the typical 40W power draw for typical single-
stage compressor crankcase heaters).
Although not indicated clearly in the comments, DOE understands
``modulated'' in the comments to refer to any compressor that is not
single-capacity. DOE clarifies in this final rule that the 1.75
multiplier applies to the number of compressors that are not single-
stage, including two-stage compressors and variable speed compressors.
This is less than a factor of 2, which would be the effective
adjustment for a two-compressor system, but there is insufficient data
showing variable speed products should have the same requirement as
multiple compressor systems.
3. Time Delay Credit and Removal of Calculations for Off Mode Energy
Consumption and Annual Performance Factor
In the November 2015 SNOPR, DOE proposed to adopt, for crankcase
heaters that incorporate a time delay before turning on, a credit that
would be proportional to the duration of the delay, as implemented in
the calculation of the off mode energy consumption. (The original
proposed calculation method for PW,OFF did not include any
adjustment associated with the time delay). DOE also proposed, for
products in which a time delay relay is installed but the duration of
the delay is not specified in the manufacturer's installation
instructions shipped with the product or in the certification report, a
default period of non-operation of 15 minutes out of every hour,
resulting in a 25% savings in shoulder-season off mode energy
consumption. DOE notes that the impact on crankcase heater energy use
was extended in the proposal to the entire off-mode energy consumption
because, for an air conditioner or heat pump with a crankcase heater,
most of the off mode energy use is associated with the heater. To
reduce potential instances of the misuse of this incentive, DOE also
proposed requiring manufacturers to include in certification reports
the duration of the crankcase heater time delay for both the shoulder
and heating seasons. 80 FR 69278, 69303-04 (Nov. 9, 2015).
[[Page 37024]]
DOE received a joint comment from NEEA and NPCC that stated, among
other things, that the impact of a time delay in a system is difficult
to measure accurately. NEEA and NPCC also expressed the opinion that
sometimes the time delay behavior is an artifact of temperature
control, because it takes a certain time for the compressor to cool
after a run cycle. (NEEA and NPCC, No. 64 at p. 6) The California IOUs
recommended care be taken in adopting such a credit, and requested that
it be vetted appropriately before being implemented. (California IOUs,
No. 67 at p. 5)
Upon further review of the function of the time delay relay and its
potential impact on off mode power consumption, DOE concludes that the
proposed credit is not consistent with the intent of its off mode
definition. A definition for off mode was initially proposed in the
July 2010 NOPR. For air conditioners, it was proposed to include, ``all
times during the non-cooling season of an air conditioner. This mode
includes the `shoulder seasons' between the cooling and heating seasons
when the unit provides no cooling to the building and the entire
heating season, when the unit is idle.'' 75 FR at 31249 (June 2, 2010).
The definition for off mode season in today's notice is not identical
but has essentially the same meaning, for example for an air
conditioner, referring to both the shoulder season and the heating
season. The shoulder season is defined as the period between the months
of the year that require heating or cooling. The off mode season lasts
months. Hence, the impact of a crankcase heater time delay of a
fraction of an hour, as is typical for such relays, would
insignificantly reduce average crankcase heater on-time or energy use.
The time delay credit was proposed in the November 2015 SNOPR to
apply only to the off mode energy use calculation, and to the annual
performance factor, APF, but not to the off-mode metric
PW,OFF. DOE does not currently have, and has not proposed to
establish, standards or reporting requirements for off mode energy use
or annual performance factor, nor are these parameters needed for
representations, such as for product labeling. Hence, DOE is not
adopting in Appendix M the proposed provisions for calculating off mode
energy use, as well as the proposed time delay credit, and has removed
the provisions for calculating annual performance factor.
4. Impacts on Product Reliability
Addressing concerns from stakeholders, in the November 2015 SNOPR,
DOE stated that it expected that the proposed off mode test method
would allow manufacturers to meet the June 2011 off mode standards
without compromising the reliability of central air conditioners and
heat pumps. DOE requested comments on the issue of compressor
reliability as it relates to crankcase heater operation. 80 FR 69278,
69304 (Nov. 9, 2015).
Lennox, JCI, and Rheem expressed concerns that regulating crankcase
heater power will have a negative impact on products. (Lennox, No. 61
at p. 17; JCI, No. 66 at p. 17; Rheem, No. 69 at p. 11) NEEA/NPCC
strongly agreed with DOE that manufacturers will be able to meet off
mode power consumption standards without adverse impact on product
reliability. (NEEA/NPCC, No. 64 at p. 7) UTC/Carrier and the California
IOUs suggested that DOE should seek comments or obtain information on
research conducted by compressor manufacturers or independent entities.
(UTC/Carrier, No. 62 at p. 12; California IOUs, No. 67 at p. 5)
However, no party provided any data indicating that the proposal would
have such an impact. Also, DOE has modified many of the details of the
test procedure as requested by stakeholders to address concerns, for
example, adjusting the measurement of PW,OFF for modulating-
or multiple-compressor systems for consistency with their typically
higher crankcase heater wattages. In this final rule, DOE has modified
the proposed off mode test procedure consistent with information,
provided by stakeholders, that might affect crankcase heater
performance as measured by the test procedure such that application of
the off mode standard using the final test procedure should have
minimal impact on the reliability of CAC/HP systems.
5. Off Mode Power Consumption for Intelligent Compressor Heat Control
In a general response to the off mode test procedure proposed in
the November 2015 SNOPR, Ingersoll Rand commented that the proposed off
mode test procedure cannot accurately reflect off mode energy
consumption for their intelligent crankcase heater control, which
cycles the heater to provide the appropriate average heat input. They
requested that they be allowed to use an alternative test method for
measurement of the heating season off-mode power consumption, P2, for
products with this feature. The requested alternative test suggested by
Ingersoll Rand would consist of a test period for measurement of input
power that includes three complete crankcase heater cycles, or 18
hours, whichever is shorter, rather than the 5-minute test period of
the proposed test. Ingersoll Rand provided test data showing typical
operation of the crankcase heater. (Ingersoll Rand, No. 65 at p. 14-23)
DOE carefully reviewed Ingersoll Rand's data and agrees that longer
tests are needed for heaters whose controls cycle or vary crankcase
heater power over time. Rather than authorizing an alternative method
specific to Ingersoll Rand, the final rule adopts an additional
provision in the measurement of heating season off mode power
consumption (P2), using the approach suggested by Ingersoll Rand for
such controls: three complete heater cycles or 18 hours, whichever is
shorter. The final rule also requires that this approach be used for
measuring the shoulder season off-mode power consumption, P1, if the
heater is energized and cycles or varies input power for that
measurement.
6. Off Mode Test Voltage for Dual-Voltage Units
In its comments on the off mode test procedure proposal of the
November 2015 SNOPR, Ingersoll Rand stated that the proposal did not
specify how to test units with a dual voltage rating. They further
recommended that for such systems, the higher voltage should be the
test voltage for off mode tests. (Ingersoll Rand, No 65 at p. 4). They
also commented that the same tolerances be adopted as are used for
performance testing. DOE notes that the current test procedure
incorporates by reference section 6.1.3.2 of AHRI 210/240-2008, which
provides requirements for setting voltage for testing products with
dual nameplate voltages. The standard requires that 230 V be used for
208-230 V dual-voltage units and that testing for all other dual
nameplate voltage units be conducted at either the lower of the two
voltages or at both voltages. Ingersoll Rand did not provide
explanations supporting their suggestion to instead use the higher
voltage (Ingersoll Rand, No. 65 at p. 4), and DOE sees no reason to
depart from these established requirements for off-mode testing. DOE
agrees with the need to specify tolerances, which are discussed in the
next section.
7. Off Mode Test Tolerance
DOE recognized that the November 2015 SNOPR did not address all
relevant test tolerances for the off mode power consumption test. DOE
proposed tolerances for outdoor temperatures in the November 2015
SNOPR, but did not clarify whether test tolerances for power supply
voltage for off mode testing should be different than for active mode
testing. DOE adopts in this final rule the
[[Page 37025]]
same test tolerances used for active mode testing (see, for example,
Table 7 in section 3.3 of Appendix M). These tolerances are 2.0 percent
as the test operating tolerance and 1.5 percent as the test condition
tolerance, both as a percentage of measured voltage.
8. Organization of Off Mode Test Procedure
In addition to revising the proposed off-mode test procedure in
response to stakeholder comments, as discussed in previous sections,
DOE also modifies the proposed off mode test procedure in this final
rule. These modifications do not affect the measurement but should help
to ensure consistency between tests conducted in different labs.
First, DOE has provided greater detail regarding test sample set-up
and connection of power measurement devices for off-mode testing. This
includes provisions for providing power to the control circuit for all
kinds of units and specifically addresses the options when testing
coil-only units for which a furnace or a modular blower is the
designated air mover. (See section 3.13.1.a of Appendix M as finalized
in this notice.)
Second, the test procedure now provides greater specification
regarding which power inputs are to be included as part of the low
voltage power Px. (See, for example, section 3.13.1.d of
Appendix M as finalized.)
Third, the test procedure indicates that for units with time delay
relays, the measurement is to be made after the time delay has elapsed.
In addition, DOE notes that in the calculation of off-mode seasonal
power consumption in section 4.3, P2 should never equal to zero. As
described in the November 2015 SNOPR, DOE intended that the off mode
power rating PW,OFF be equal to the arithmetic mean of P1
and P2, without discussion of any special cases in which P2 is equal to
zero. 80 FR at 69301 (Nov. 9, 2015). The provisions for calculating
PW,OFF for cases in which P2 is equal to zero should not
have appeared in the Appendix M regulatory language presented in the
notice. Hence this notice shows the intended calculation, that
PW,OFF be equal to the average of P1 and P2.
9. Certification
In the November 2015 SNOPR, DOE proposed that manufacturers report
off-mode power in their certification reports. 80 FR 69278, 69291 (Nov.
9, 2015). In response, AHRI and Rheem suggested that the off mode
ratings should be reported as pass/fail with a 5% tolerance. AHRI did
not explicitly clarify what they meant by a 5% tolerance, but DOE
assumes this means that the model would rate as ``pass'' even if the
measured value (or the average of the values measured for the sample of
units) is as much as 5% greater than the standard. AHRI stated that
first, it is difficult to accurately measure the power consumption
because of the inaccuracies in common measurement devices, and second,
because consumers do not compare products using this metric,
manufacturers have no incentive to report it. (AHRI No. 70 at p. 11;
Rheem No. 69 at p. 3)
DOE requires that manufacturers report the value of all regulated
efficiency metrics rather than simply an indication of whether units
pass or fail the energy conservation standard. If a manufacturer does
not wish to reveal how much lower than the off-mode power consumption
standard a model performs, it has the option to rate at the standard
level as long as the represented value is consistent with the
measurements, sampling plan and represented value requirements in 10
CFR 429. Accordingly, DOE maintains the requirement to report the
actual value for off-mode power.
DOE also proposed to require manufacturers to include in the
certification reports the temperatures at which the crankcase heater is
designed to turn on and turn off for the heating season, if applicable.
80 FR 69278, 69301 (Nov. 9, 2015).
After finalization of the off mode test procedure based on
stakeholder comments, DOE recognized that the only product-specific
temperature needed to be known to properly conduct the test is the
turn-on temperature (i.e. the cut-in temperature). This is the
temperature below which the thermostat would energize the heater. The
heating season off-mode power is measured at an ambient temperature 5
+/- 2 [deg]F below this turn-on temperature. The temperature at which
the crankcase heater of an air conditioner is designed to turn off for
the heating season (i.e. below which the heater would no longer be
energized) will not be needed to conduct the tests. This is because the
test procedure as finalized does not call for a test at a temperature
near this lower turn off temperature. Hence DOE is requiring reporting
only of the temperature at which the crankcase heater is designed to
turn on.
10. Compliance Dates
Rheem, Nortek, Goodman and JCI expressed concern with complying
with the off mode power rating within 180 days of publication of the
final test procedure. (Rheem, No. 69 at p. 3; Nortek, No. 58 at p. 7;
Goodman, No. 73 at p. 20; JCI, No. 66 at p. 9) JCI commented that at
least one test year is needed to complete the work to comply. (JCI, No.
66 at p. 9) JCI further suggested that they would agree with requiring
the off mode test for any new basic model starting 180 days after the
publication of final rule, but that all existing basic models should be
granted an extended period of 5 years for compliance. (JCI, No. 66 at
p. 9) Nortek commented that manufacturers should have at least two
years to comply with this change, otherwise DOE must explicitly permit
all existing products to be grandfathered in until the new energy
conservation standard goes into effect. (Nortek, No. 58 at p. 7)
Goodman commented that manufacturers are statutorily provided with five
years to comply with energy conservation standards, which DOE has
reduced to less than six months. Goodman requested that DOE provide at
least half of the required statutory time
(two[hyphen]and[hyphen]a[hyphen]half years) to comply with the
off[hyphen]mode standard compliance and certification requirements.
Goodman noted that DOE could not presently assert civil penalties for
off[hyphen]mode because there is no final method of test. (Goodman, No.
73 at p. 20-21)
DOE understands that the stakeholders' concern with the compliance
date is due to the test burden related to measuring off mode power
consumption. In this final rule, DOE has considerably reduced the test
burden in the following aspects: (a) manufacturers do not need to test
each basic model for off mode power consumption and instead are allowed
to use an AEDM for off mode with certain requirements (discussed in
section III.B.8); (b) all units are allowed to be tested for off mode
power consumption in a temperature-controlled room rather than a
psychrometric room; and (c) for units having a compressor crankcase
heater whose power consumption can be determined without ambient
condition requirements (e.g. the heater's wattage when energized does
not vary with ambient temperature), manufacturers do not need to use
temperature-controlled test facilities.
With the test procedure allowances stated above, DOE believes that
the off mode test burden has been reduced significantly and
manufacturers should be able to provide the off mode power represented
values within 180 days as required by statute.
E. Test Repeatability Improvement and Test Burden Reduction
42 U.S.C. 6293(b)(3) states that any test procedure prescribed or
amended
[[Page 37026]]
shall be reasonably designed to produce test results which measure
energy efficiency and energy use of a covered product during a
representative average period of use and shall not be unduly burdensome
to conduct. This section discusses clarifications to improve test
procedure repeatability and to reduce test burden. None of the
clarifications listed in this section would alter the average measured
energy consumption of a representative set of models.
1. Indoor Fan Speed Settings for Blower Coil or Single-Package Systems
Indoor unit fan speed is typically adjustable to assure that the
required air volume rate is provided for the range of field-installed
ductwork systems that the unit might use for air distribution. The DOE
test procedure has specific requirements for fan speed adjustment,
external static pressure, and air volume rate during the test. For a
ducted blower coil system, DOE's test procedure requires that (a)
external static pressure be no less than a minimum value that depends
on cooling capacity \9\ and product class, ranging from 1.10 to 1.20
inches of water column (in. wc.) for small-duct, high-velocity systems
and from 0.10 to 0.20 in. wc. for all other systems except non-ducted
(see 10 CFR part 430, subpart B, Appendix M, Table 2); and that (b) the
air volume rate divided by the total cooling capacity not exceed a
maximum value of 37.5 cubic feet per minute of standard air (scfm) per
1000 Btu/h of cooling capacity \10\ (see 10 CFR part 430, subpart B,
Appendix M, Section 3.1.4.1.1). In the November 2015 SNOPR, DOE
proposed that blower coil products be tested using the lowest speed
setting that satisfies the minimum static pressure and the maximum air
volume rate requirements, if applicable, if more than one of these
settings satisfies both requirements. This clarification was proposed
to be added to section 2.3.1.a of Appendix M. 80 FR 69278, 69305 (Nov.
9, 2015).
---------------------------------------------------------------------------
\9\ Or heating capacity for heating-only heat pumps.
\10\ Such a requirement does not exist for heating-only heat
pumps.
---------------------------------------------------------------------------
Rheem agreed that the most logical and energy efficient method to
set up an indoor fan on a central air conditioner or heat pump system
is to set the indoor blower to the lowest fan setting that meets all of
the air volume rate requirements. Rheem also agreed that lab to lab
repeatability will improve with this requirement. (Rheem, No. 69 at p.
11)
JCI expressed concern that testing above the rated airflow would be
permitted (JCI, No. 66 at p. 11). However, JCI expressed agreement with
the proposal provided DOE establishes a tolerance relative to the rated
airflow before adjusting speed settings (JCI, No. 66 at p. 17). In
response to JCI, DOE did not intend to imply that the tested airflow is
allowed to exceed the rated airflow. In this final rule, DOE has
clarified this in sections 2.3.1.a and 2.3.2.a of the regulatory text
by referencing section 3.1.4 for information on air volume rate control
settings. Section 3.1.4 outlines a procedure in which the air volume
rate is always set to the rated value or reduced to meet the static
pressure requirement.
Further, DOE notes that in the current test procedure (section
3.1.4 of Appendix M) the air flow may be adjusted downwards from the
rated air flow by up to 5 percent to meet the static pressure
requirement before adjusting speed settings (i.e., if the ESP is lower
than required when running at the rated air flow, the code tester fan
can be adjusted to increase ESP and decrease airflow, without
increasing the fan speed setting, until airflow is 95 percent of rated
airflow). The June 2010 NOPR proposed increasing this tolerance such
that switching to a higher speed setting would be required when the air
volume rate drops below 90 percent of the rated air volume rate without
meeting the external static pressure requirement--a 10 percent
tolerance below rated. 75 FR at 31234 (June 2, 2010).
NEEA commented that they do not support widening the gap between
rated performance in the lab and actual performance in the field. NEEA
requested that DOE research the adequacy of the 5 percent tolerance
with an ESP testing minimum of 0.5 in. w.c. (NEEA, No. 7 at pp. 3-4).
DOE does not believe that the air volume rate measurement in the field
is very precise, if it is measured directly at all when systems are
installed. This is because the apparatus used to measure air flow with
this precision in the laboratory is very bulky and is not used for
field installations. Hence, the increase from 5 to 10 percent tolerance
would not increase the gap between field and laboratory operation. DOE
adopts the tolerance as proposed.
DOE identified potential sources of confusion in section 3.1.4 and
has improved the language for setting the air volume rate of ducted
blower coil systems that use blower motors other than constant-air-
volume-rate indoor blower motors. These changes do not alter the test
method but rather provide clearer instructions for adjusting the indoor
fan and the test apparatus settings to set the air volume rate in
accordance with the test procedure.
Improper fan speeds implemented during testing may have a marked
impact on product performance, and inconsistent implementation of speed
settings and adjustments may be detrimental to test repeatability. DOE
therefore proposed that manufacturers could include in their
certification report a certified air volume rate and certified
instructions for setting fan speed or controls to achieve that air
volume rate. 80 FR 69278, 69305 (Nov. 9, 2015). The requirement has
been adopted by DOE in the final rule. As part of the section 3.1.4
changes, DOE added instructions for testing if there is no certified
air volume rate. Additionally, absent fan speed instructions for
installation, DOE added instructions to use the as-shipped settings.
DOE also adds specificity on which test conditions to use for
determining air volume rates. For instance, the A (for single-stage
units) or A2 test is specified for determining the cooling
full-load air volume rate. Another modification places the 37.5 cubic
feet per minute of standard air (scfm) per 1,000 Btu/h of capacity
check as a last step in the process, after both the air volume rate and
external static pressure requirements are met.
AHRI asked DOE to provide information on how the airflow 450 scfm
per ton ceiling was derived and why it is still relevant. (AHRI, No. 70
at p. 13) DOE notes that the 450 scfm/ton ceiling is identical to the
37.5 scfm per 1,000 Btu/h maximum air flow requirement that is in the
CAC/HP test procedure. This requirement has been in the DOE test
procedure since it was initially established. On January 11, 2001, DOE
published a NOPR in which it discussed whether this upper limit on air
flow should remain in the test procedure, expressed interest in further
discussion to resolve the question, but proposed not to change the
limit. 66 FR 6774. The final rule completing that rulemaking did not
again discuss the issue. 70 FR 59122 (Oct. 11, 2005).
DOE agrees with AHRI that the limit is not needed for blower coil
systems. Increased air flow can improve heat transfer from the indoor
coil. However, higher air flow for blower coil systems is at the
expense of considerable fan power, which both reduces cooling capacity
and increases system power. There is an optimum air flow for which
efficiency would be maximized, typically near 400 scfm per ton, but it
is different for each system. In a blower coil system test, the added
fan power required to move additional air is
[[Page 37027]]
incorporated in the measurement. Hence, a manufacturer would not have
incentive to increase rated airflow unreasonably. On the other hand,
not setting an upper bound on air flow in the test procedure gives
manufacturers more design flexibility. For these reasons, DOE has
removed the 450 scfm per ton requirement for blower coil systems in
this final rule notice. DOE does, however, expect that certified
airflow rates will be consistent with installation instructions, since
ultimately the test procedure is intended to reflect field performance.
For consistency with the furnace fan test procedure, DOE proposed
to add to Appendix M the definition for ``airflow-control setting''
that has been adopted in Appendix AA to refer to control settings used
to obtain fan motor operation for specific functions. 80 FR 69278,
69305 (Nov. 9, 2015). DOE did not receive comments on this proposal and
is retaining it as proposed.
2. Air Volume Rate Adjustment for Coil-Only Systems
In the current DOE test procedure, for a coil-only system, the
pressure drop across the indoor unit must not exceed 0.3 inches of
water for the A test (or A2 test for two-capacity or
variable-capacity systems), and the maximum air volume rate per
capacity must not exceed 37.5 cubic feet per minute of standard air
(scfm) per 1000 Btu/h. (10 CFR part 430, subpart B, Appendix M, Section
3.1.4.1.1) For such systems, higher air volume rates enhance the heat
transfer rate of the indoor coil, and therefore may maximize the
measured system capacity and efficiency. In addition, the energy use
and heat input attributed to the fan energy for such products is a
fixed default value in the test procedure, and is set at 365 W per
1,000 scfm (see, for example, 10 CFR part 430, subpart B, Appendix M,
Section 3.3(d)). Thus, the impact from fan power on the efficiency
measurement if air volume rate is increased may be more modest than for
a blower coil unit, for which fan input power would increase more
rapidly due to the increase of internal pressure drop as well as air
volume rate. To prevent rating based on excessive air volume rates, a
maximum pressure drop of 0.3 in. wc. is specified for the indoor coil
assembly. To minimize potential testing variability due to the use of
different air volume rates, in the November 2015 SNOPR, DOE proposed to
require for coil-only systems for which the maximum air flow (37.5
scfm/1,000 Btuh) or maximum pressure drop (0.3 in wc) are exceeded when
using the specified air flow rate, that the air flow rate must be
reduced so that both are satisfied. This is specified in section
3.1.4.1.1.c of Appendix M as proposed. 80 FR 69278, 69305 (Nov. 9,
2015). DOE did not receive comments on this proposal other than the
AHRI comment regarding the 450 scfm per ton upper limit on air flow
discussed above. DOE believes that the 0.3 in wc coil pressure drop
maximum provides a limit on airflow that is comparable, i.e. exceeding
the 450 scfm per ton limit would generally involve also exceeding the
0.3 in wc limit. Hence, DOE sees little need to maintain the 450 scfm
per ton limit only for coil-only systems and, consistent with the
approach discussed above for blower coil systems, has removed this
limit for coil-only systems.
3. Requirements for the Refrigerant Lines and Mass Flow Meter
Section 2.2(a) of 10 CFR part 430, subpart B, Appendix M provides
instructions for insulating the ``low-pressure'' line(s) of a split
system. In the cooling mode, the vapor refrigerant line connecting the
indoor and outdoor units operates at low refrigerant pressure. However,
in the heating mode, it operates at high pressure. To improve clarity
and ensure that the language of the test procedure refers specifically
to the actual functions of the refrigerant lines, DOE proposed in the
November 2015 SNOPR to refer to the lines as ``vapor refrigerant line''
and ``liquid refrigerant line''. 80 FR 69278, 69306 (Nov. 9, 2015).
Because DOE seeks to minimize test variability associated with the
use of insulation, the November 2015 SNOPR included a proposal for
determining the insulation requirement for the test based on the
materials and information shipped with the test unit. Under this
proposal, test laboratories would install the insulation shipped with
the unit. If the unit is not shipped with insulation, the test
laboratory would install the insulation specified in the installation
manuals shipped with the unit. If instructions for refrigerant line
insulation are not provided, liquid line insulation would be used only
for heating-only heat pumps. These proposed requirements were intended
to reduce test burden and improve test repeatability. 80 FR 69278,
69306 (Nov. 9, 2015).
Additionally, DOE proposed to add requirements to Appendix M,
section 2.10.3 to require use of a thermal barrier to prevent thermal
transfers between the flow meter and the test chamber floor if the
meter is not mounted on a pedestal or other support elevating it at
least two feet from the floor. 80 FR 69278, 69306 (Nov. 9, 2015).
DOE requested comment on these proposals. Many stakeholders agreed
with the proposals. (NEEA and NPCC, No. 64 at p.8; ADP, No. 59 at p.9;
UTC/Carrier, No. 62 at p. 13; Rheem, No. 69 at p. 11) DOE did not
receive any comments opposing these proposals. Therefore, in this final
rule, DOE adopts these proposals and adds a specification that
insulation should remain the same for heating mode and cooling mode.
4. Outdoor Room Temperature Variation
The current DOE test procedure requires that a portion of the air
approaching the outdoor unit's coil is sampled using an air sampling
device, often called an air sampling tree. (See Appendix M, section
2.5). To ensure that the measured temperature accurately represents the
average temperature approaching the coil even if there might be
variation in the outdoor room conditions, the November 2015 SNOPR
proposed to require demonstration of air temperature uniformity over
all of the air-inlet surfaces of the outdoor unit using thermocouples,
if sampling tree air collection is not performed on all inlet-air faces
of the outdoor unit. Specifically, DOE proposed requiring that the
thermocouples be evenly distributed over the inlet air surfaces such
that there is one thermocouple measurement representing each square
foot of air-inlet area. The maximum temperature spread to demonstrate
uniformity, i.e., the maximum allowable difference in temperature
between the measurements at the warmest location and at the coolest
location, would be 1.5 [deg]F. If this value is exceeded, DOE proposed
that sampling tree collection of air would be required from all air-
inlet surfaces of the outdoor unit. DOE proposed in the November 2015
SNOPR to add these requirements to Appendix M, section 2.11.b. 80 FR
69278, 69306-07 (Nov. 9, 2015).
In its comments on the November 2015 SNOPR, Rheem agreed with DOE's
proposal. (Rheem, No. 69 at p. 12) UTC/Carrier also supported this
proposal, indicating that although it will be challenging for testing
facilities, it should reduce testing uncertainty. (UTC/Carrier, No. 62
at p. 14). DOE recognizes that some of these proposed requirements
could represent challenges, since they involve both addition of
instrumentation and could require adjustment of outdoor room air
circulation patterns in order to assure that the maximum temperature
difference is not exceeded.
Some stakeholders indicated that aspects of the proposal were not
clear. JCI and AHRI commented that the
[[Page 37028]]
proposal did not specify if the 1.5 [deg]F maximum range for the
observed temperatures measured by the thermocouples applies to time
averages or instantaneous measurements made at any time during the test
period, with AHRI adding that the tolerance should apply to the time-
average measurements. (JCI, No. 66 at p.18; AHRI, No. 70 at p. 13; ADP,
No. 59 at p. 10; Lennox, No. 61 at p. 17). JCI, AHRI, ADP, and Lennox
commented that the regulatory text portion of the notice requires that
the thermocouple grid be used to verify temperature uniformity whether
or not air samplers are used on all air inlet faces of the outdoor
unit, while the preamble discussion (section III.E.3 of the notice)
indicates that the thermocouple grid is not needed if air samplers are
used on all air inlet faces--the commenters questioned the requirement
for use of the thermocouple grid if air samplers are used on all faces.
(JCI, No. 66 at p.18; AHRI, No. 70 at p. 13; ADP, No. 59 at p. 10;
Lennox, No. 61 at p. 17). In response, DOE notes that DOE intended that
the tolerance apply to the average temperatures measured during the
test period and that the thermocouple grid be waived if the air
samplers are used on all air inlet faces. DOE revised Appendix M for
consistency with the intent of the proposal. DOE notes that time
variation of the air inlet temperature is already addressed by the test
operating tolerance requirement of ANSI/ASHRAE 37-2009.
JCI and Ingersoll Rand suggested increasing the allowed variation
between thermocouples on the thermocouple grid or sampler to 2.5F.
(JCI, No. 66 at p.11; Ingersoll Rand, No. 65 at p. 5) In response, DOE
notes that the proposal was somewhat lenient in allowing only one inlet
air face to be measured with an air sampler if the temperature
uniformity requirement is met. If, for example, the outdoor unit has
four air inlet faces and the face with an air sampler is measuring high
just within the allowed tolerance, while all the others are reading
low, the actual average outdoor air condition would be up to 1.9 [deg]F
lower than measured by the air sampler if the maximum allowed tolerance
were 2.5 [deg]F.\11\ Hence DOE is reluctant to allow significant
departure from the proposed 1.5 [deg]F tolerance. However, DOE has
increased the tolerance to 2.0 [deg]F, noting that the accuracy of
thermocouples is at best nearly +/- 1 [deg]F without careful
calibration, thus making imposition of a 1.5 [deg]F maximum range
impractical.
---------------------------------------------------------------------------
\11\ For example, if the air approaching the air-sampled face
were 95 [deg]F while the air approaching the other faces were 92.5
[deg]F, the actual average inlet air temperature would be 93.1
[deg]F, nearly 2 [deg]F lower than the temperature measured by the
air sampler.
---------------------------------------------------------------------------
JCI commented that they have had excellent experience with regard
to the balance of entering air when using a 3-sided air sampler for
products with 4 inlet air surfaces. (JCI, No. 66 at p.17) However, the
comment did not provide DOE details to clarify what this means in terms
of air temperature uniformity and how they determined that the 3-sided
approach is sufficient. For example, if testing using four air samplers
with separate measurements has always shown that any three of the air
samplers provides an average temperature that is negligibly different
than the full four-air-sampler average, such results would indicate
strongly that the fourth air sampler was not necessary. DOE may
consider such information and potential revision of the temperature
uniformity requirements in a future rulemaking if such data can be
provided.
AHRI and JCI commented that the requirement to provide
thermocouples for every square foot of outdoor coil surface would
increase test burden, potentially requiring use of up to 40
thermocouples for larger units. (AHRI, No. 70 at pp. 12-13; JCI, No. 66
at p.11). DOE notes that the thermocouples are not required if all air-
inlet faces of the outdoor unit are measured using air samplers. DOE
also notes that the 2015 draft version of AHRI Standard 210/240 calls
for use of 16 thermocouples per air sampler. If using four air
samplers, this adds up to 64 thermocouples. DOE has modified the
requirement so that the thermocouple density would be 16 per face or
one per square foot of inlet area, whichever is less. However, as noted
before, the thermocouples are not required if air samplers are used on
all air inlet faces.
Ingersoll Rand commented that DOE should specify the location of
the thermocouples, indicating that poor choice of location could,
contrary to ASHRAE 37 requirements, lead to the thermocouple grid
blocking the natural recirculation of condenser discharge air to the
air inlet that may be inherent to the product design. The comment
recommended that the thermocouples be mounted on an air sampler.
Ingersoll Rand also recommended adding a specification to correlate the
average thermocouple reading to the dry bulb temperature measurement of
the sampled air, similar to the requirements of the thermopile used on
the indoor side. (Ingersoll Rand, No. 65 at p. 5) In response, DOE
notes that thermocouple requirement applies only if all air inlet faces
of the outdoor unit are not measured using air samplers. DOE has
modified the test procedure language to indicate that natural
recirculation of discharge air back to the air inlet should be avoided
when mounting the thermocouples, and that they should be located 6 to
24 inches from the air inlet face. Certainly any thermocouple that
blocks discharge air flow will register a high measurement that is
outside of the specified tolerance. Regarding the correlation of
thermocouple measurements with the air sampler dry bulb temperature
measurement, DOE has not adopted this recommendation because it is not
clear what its purpose would be. For the indoor side, such correlation
helps to calibrate the thermocouple grid measurement for the cyclic
test, but the outdoor air inlet temperature measurements are not used
in a similar way for any of part of the tests. DOE adopts the
amendments as proposed except for the changes discussed in this
section, including (a) adopting 16 as the maximum number of
thermocouples per inlet face, (b) increasing the maximum temperature
range from 1.5 [deg]F to 2.0 [deg]F, (c) clarifying that the maximum
range applies to the average measurements for the test period, and (d)
clarifying that the thermocouples should not interfere with condenser
discharge air flow.
5. Method of Measuring Inlet Air Temperature on the Outdoor Side
The average dry bulb temperature of air approaching the air inlet
faces of the outdoor unit can be measured using air samplers or using
thermocouple grids. To improve test repeatability, in the November 2015
SNOPR, DOE sought to ensure that temperature measurements taken during
the test are as accurate as possible. DOE proposed that the air sampler
dry bulb measurement (rather than the thermocouple grids) be the basis
of comparison with the outdoor air dry bulb temperature requirement for
the test. 80 FR 69278, 69307 (Nov. 9, 2015).
Rheem and ADP agreed with DOE's proposal in the November 2015
SNOPR. (Rheem, No. 69 at p. 12; ADP, No. 59 at p. 10) There were no
comments against the proposal. Hence, DOE adopts the proposal in this
final test rule.
6. Requirements for the Air Sampling Device
In the November 2015 SNOPR, DOE proposed to require that no part of
the room air sampling device or the means of air conveyance to the dry
bulb temperature sensor be within two inches of the test chamber floor.
DOE also proposed to require those surfaces of the air sampling device
and the
[[Page 37029]]
means of air conveyance that are not in contact with the indoor and
outdoor room air be insulated. 80 FR 69278, 69307 (Nov. 9, 2015).
DOE also proposed to require that humidity measurements and dry
bulb temperature measurements used to determine the moisture content of
air be made at the same location in the air sampling device. As
discussed in section III.E.14, DOE also proposed several amendments to
air sampling procedures that are included in a draft revision of AHRI
210/240. 80 FR 69278, 69307 (Nov. 9, 2015).
Many stakeholders supported these proposals. (JCI, No. 66 at p.18;
ADP, No. 59 at p. 10; UTC/Carrier, No. 62 at p. 14; Unico, No. 63 at p.
9; Rheem, No. 69 at p. 12). There were no comments against the
proposals. Therefore, DOE adopts the proposals.
7. Variation in Maximum Compressor Speed With Outdoor Temperature
In the November 2015 SNOPR, DOE proposed that the maximum
compressor speed be defined for the test procedure as the absolute
maximum speed at which the compressor operates, allowing for a
different maximum for heating mode as opposed to cooling mode. One
implication of this proposal is that the maximum speed cannot be
different for different cooling mode test conditions, and likewise it
cannot be different for different heating mode test conditions. 80 FR
69278, 69307 (Nov. 9, 2015).
Some stakeholders supported this proposal and others did not. In
its comments, Rheem tentatively agreed with the proposal but indicated
it would support DOE conducting further studies. (Rheem, No. 69 at p.
12) AHRI also proposed further study on the issue without further
specificity. (AHRI, No. 70 at p. 17) UTC/Carrier requested
clarification, although commented that the proposal seemed to be
current industry practice. (UTC/Carrier, No. 62 at p. 14) JCI and
Goodman also agreed that the maximum speed should be held constant.
(JCI, No. 66 at p. 18; Goodman, No. 73 at pp. 8-9)
In contrast, Ingersoll Rand and Lennox commented that they do not
support the proposal to fix the maximum compressor speed because it
limits the potential performance benefits of heat pumps. (Ingersoll
Rand, No. 65 at p. 11; Lennox, No. 61 at p. 11) Ingersoll Rand
commented that this proposal will become a bigger problem when the
heating load line of Appendix M1 is implemented. (Ingersoll Rand, No.
65 at p. 11) Lennox conducted testing on a three ton system and
determined that operation at the 17 degree test point could be enhanced
by 40 percent capacity and 10 percent HSPF by allowing the speed of the
compressor to change with outdoor air temperature. (Lennox, No. 61 at
p. 11) Mitsubishi recommended that the current testing process remain
the same and that the optional testing method for HSPF should allow
manufacturers to obtain ratings that incorporate the varying of the
maximum compressor speed with outdoor temperatures. (Mitsubishi, No. 68
at p. 4)
DOE agrees with JCI and Goodman that the maximum speed should be
the same for the different test conditions. DOE notes that a unit's
performance is calculated based on test results using extrapolation and
interpolation assuming that capacity and power vary linearly with
outdoor temperature (i.e., the capacity and power vary a fixed amount
in Btu/h for each additional degree that the outdoor temperature
rises). For example, equations 4.2.2-3 and 4.2.2.-4 in Appendix M of
the current test procedure are used with k set equal to 2 to calculate
heat pump capacity and power input when operating at maximum speed. The
performance for temperatures below 17 [deg]F and above 45 [deg]F
ambient temperatures is calculated based on tests conducted at 17
[deg]F and 47 [deg]F. Specifically, an equation for capacity as a
function of ambient temperature is determined based on the measured
capacities at 17 [deg]F and 47 [deg]F. This equation is then used to
calculate capacity for all ambient conditions cooler than 17 [deg]F and
warmer than 45 [deg]F. The same is done to determine heat pump power
input for these temperature ranges. In a similar fashion, performance
for temperatures between 17 [deg]F and 45 [deg]F are calculated based
on tests conducted at 17 [deg]F and 35 [deg]F. The following example
shows how allowing different compressor speeds for the pairs of tests
used to determine performance can lead to non-representative results.
The heat pump in question varies its maximum compressor speed in
heating mode--its performance is shown in Figure 2 of the Oak Ridge
National Laboratory review of variable-speed heat pump test procedures.
(Review of Test Procedure For Determining HSPF's of Residential
Variable-Speed Heat Pumps, Docket No. EERE-2009-BT-TP-0004, No. 49 at
p. 5) The maximum-speed capacity of this heat pump clearly does not
vary linearly between outdoor temperatures of 17 [deg]F and 47 [deg]F.
Use of the test procedure's equation to represent this heat pump's
performance below 17 [deg]F would indicate that its capacity increases
as temperature drops below 17 [deg]F, which clearly is not true. This
example shows that allowing different maximum compressor speeds can
lead to nonsensical results. Hence, DOE is maintaining its proposal,
consistent with its understanding of the test procedure's original
intent, that maximum speed be the same speed for all test conditions of
the particular operating (heating or cooling) mode that uses maximum
speed. DOE has, however, modified the test procedure in this notice
such that the maximum speed for a given operating mode (heating or
cooling) used for the test conditions required to rate the product does
not have to be the absolute maximum used by the product for that
operating mode. Hence, a heat pump could use a higher maximum
compressor speed when operating in a 5 [deg]F ambient condition than
used for the required tests in 17 [deg]F, 35 [deg]F, and 47 [deg]F
conditions. This provision assures that cold-climate variable speed
heat pumps, those that boost compressor speed in very low ambient
temperatures to reduce the amount of heat provided by resistance
heating, can be tested using appropriate compressor speeds for the
tested operating conditions. DOE has implemented the requirements
discussed in this section differently than proposed. Instead of adding
the proposed clarifications for maximum and minimum compressor speed in
the definition of ``variable-speed compressor system'', DOE has
provided clarification regarding compressor speed requirements in
sections 3.2 and 3.6, which describe the tests that are required to be
conducted for cooling and heating modes.
DOE does agree that variable-speed heat pumps that have the
capability to increase speed and thus heating capacity in lower ambient
temperatures should have a test method that accurately reflects the
performance of this potentially energy-saving feature (e.g., see
Lennox, No. 61 at p. 11). However, it is DOE's belief that accurately
accounting for such a feature requires more careful consideration of
test procedure changes beyond simply allowing the compressor speed to
vary for the test conditions required by the current procedure. DOE
will consider such revisions in a future rulemaking. In the meantime,
if a manufacturer feels that more accurate representation of a unit's
performance would be obtained with an alternative test procedure, the
manufacturer has the option of petitioning for a test procedure waiver.
JCI and Goodman recommended using a different term than ``maximum
compressor speed''. (JCI, No. 66 at p. 18; Goodman, No. 73 at pp. 8-9)
Goodman
[[Page 37030]]
recommended adopting the term ``full'', as was proposed in the AHRI
210/240 Draft. DOE agrees and has modified the terminology accordingly,
renaming the term ``maximum compressor speed'' to ``full speed'' to be
consistent with AHRI 210/240 Draft.
The California IOUs commented that DOE should require the OUM to
provide testing controls that allow fixed minimum, intermediate, and
maximum speed/capacity controls settings. (California IOUs, No. 67 at
p. 5) Rather than requiring provision of a test controller, DOE is
requiring the provision as part of certification reporting of
information that specifies the compressor frequency set points and
settings for multi-step or variable-position components.
8. Refrigerant Charging Requirements
In the November 2015 SNOPR, DOE proposed to require that near-
azeotropic and zeotropic refrigerant blends be charged in the liquid
state rather than the vapor state. This was proposed for section
2.2.5.7 of Appendix M. 80 FR 69278, 69307 (Nov. 9, 2015).
DOE also proposed in the June 2010 NOPR to adopt into the test
procedure select parts of the 2008 AHRI General Operations Manual
indicating that the refrigerant charge cannot be changed after system
setup. 75 FR at 31224, 31234-35 (June 2, 2010). DOE retained this
requirement in the November 2015 SNOPR, specifically proposing that
once the system has been charged with refrigerant consistent with the
installation instructions shipped with the unit (or with other
provisions of the test procedure, if the installation instructions are
not provided or not clear), all tests must be conducted with this
charge. 80 FR 69278, 69307 (Nov. 9, 2015).
Also, because the charging procedure would be different for systems
with different metering devices, DOE also proposed to require
manufacturers to report the type of metering device used during
certification testing. 80 FR 69278, 69308 (Nov. 9, 2015).
If charging instructions are not provided in the manufacturer's
installation instructions shipped with the unit, DOE proposed
standardized charging procedures consistent with the type of expansion
device to ensure consistency between testing and field practice. For a
unit equipped with a fixed orifice type metering device for which the
manufacturer's installation instructions shipped with the unit do not
provide refrigerant charging procedures, DOE proposed that the unit be
charged at the A or A2 test condition, requiring addition of
charge until the superheat temperature measured at the suction line
upstream of the compressor is 12 [deg]F.\12\ For a unit equipped with a
TXV or electronic expansion valve (EXV) type metering device for which
the manufacturer's installation instructions shipped with the unit do
not provide refrigerant charging procedures, DOE proposed that the unit
be charged at the A or A2 condition, requiring addition of
charge until the subcooling \13\ temperature measured at the condenser
outlet is 10 [deg]F plus or minus the proposed tolerance range.\14\ 80
FR 69278, 69308 (Nov. 9, 2015).
---------------------------------------------------------------------------
\12\ The range of superheating temperatures was generalized from
industry-accepted practice and state-level authority regulations on
refrigerant charging for non-TXV systems.
\13\ The degree of subcooling or subcooling temperature is the
extent to which a fluid is cooler than its refrigerant bubble point
temperature at the measured pressure, i.e., the bubble point
temperature at a fluid's measured pressure minus its measured
temperature. Bubble point temperature is the temperate at a given
pressure at which vapor bubbles just begin to form in the
refrigerant liquid.
\14\ The range of subcooling temperatures was generalized from
manufacturer-published and technician-provided service instructions
and are typical of industry practice.
---------------------------------------------------------------------------
For heating-only heat pumps for which refrigerant charging
instructions are not provided in the manufacturer's installation
instructions shipped with the unit, the proposed standardized charging
procedure would be followed while performing refrigerant charging at
the H1 or H12 condition. DOE also proposed that charging be
done for the H1 or H12 test condition for cooling/heating
heat pumps which fail to operate properly in heating mode when charged
using the standardized charging procedure for the A or A2
test condition. In such cases, some of the tests conducted using the
initial charge may have to be repeated to ensure that all tests
(cooling and heating) are conducted using the same refrigerant charge.
DOE proposed to add this requirement to use the same charge for all
tests to Appendix M in a new section 2.2.5.8. 80 FR 69278, 69308 (Nov.
9, 2015).
DOE understands that manufacturers may provide installation
instructions with different charging procedures for the indoor and
outdoor units. In such cases, DOE proposed to require charging based on
the installation instructions shipped with the outdoor unit for OUM
products and based on the installation instructions shipped with the
indoor unit for ICM products, unless otherwise specified by either
installation instructions. 80 FR 69278, 69308 (Nov. 9, 2015).
DOE also proposed that one or more refrigerant line pressure gauges
be installed during the setup of single-package and split-system
central air conditioner and heat pump products, depending on which
parameters are used to set charge, unless otherwise specified by the
installation instructions. DOE also proposed that the refrigerant
charge be verified per the charging instructions provided in the
installation instructions shipped with the unit, or, if no charging
instructions are provided, the refrigerant charge would be verified
based on the standardized charging procedure described above. 80 FR
69278, 69308 (Nov. 9, 2015).
As discussed in section III.E.14, DOE included in its proposal
several aspects of the charging procedures that are included in a draft
revision of AHRI 210/240. 80 FR 69278, 69308 (Nov. 9, 2015).
UTC/Carrier, Unico, Rheem, and JCI supported the November 2015
SNOPR proposal to require charging near-azeotropic and zeotropic
refrigerant blends in the liquid state only. (UTC/Carrier, No. 62 at p.
14; Unico, No. 63 at p. 9; Rheem, No. 69 at p. 12; JCI, No. 66 at p.
18) There were no comments that disagreed with this proposal, so DOE is
adopting it unchanged.
The California IOUs supported giving priority to the OUM charging
instructions if the indoor and outdoor unit instructions differ but did
not explain why the OUM charging instructions should take priority if
both components include instructions and they are not consistent. DOE
responds that integration of a system incorporating an OUM's outdoor
unit and an ICM's indoor unit is the responsibility of the ICM.
Consequently, DOE adopts the charging instruction priority as proposed,
i.e. ICM instruction priority in this case.
The California IOUs also commented that providing generic superheat
and subcooling temperatures is not appropriate or necessary, adding
that manufacturers are required to include other types of installation
instructions and should be required to do the same with something as
basic as refrigerant charge. (California IOUs, No. 67 at p. 5) In
response, DOE notes that most CAC/HP systems are shipped with
installation instructions which discuss how to set refrigerant charge,
and that it expects the provisions proposed to address cases where such
instructions are not provided will not have to be used frequently. DOE
notes further that providing clarity in the test procedure regarding
how to address these situations will ensure that there is no question
during testing about how to test products shipped without instructions.
[[Page 37031]]
Rheem added that it provides refrigerant charging instructions that
are dependent on the design of the unit; the charging instructions are
different for different expansion devices (Rheem, No. 69 at p. 15).
Consequently, DOE is adopting the proposal to provide standardized
charging procedures that are based on the type of expansion device.
Rheem commented that if the manufacturer does not specify a target
superheat or subcooling point, 10 [deg]F +/- 1 [deg]F superheat should
be used for systems with a fixed refrigerant restrictor and 10 [deg]F
+/- 0.6 [deg]F subcooling should be used for systems with a TXV or
electronic expansion valve. (Rheem, No. 69 at p. 15). As mentioned
above, DOE does not expect the ``generic'' values of 12 [deg]F
superheat and 10 [deg]F subcooling to be used frequently and notes that
manufacturers that desire that different target values be used should
be sure to include installation instructions with the units. DOE did
not receive other comments regarding the specific values of the targets
in case instructions are not provided, and DOE's research suggests that
the proposed values are a good representation of the ranges of values
provided in installations instructions for existing products. Hence,
DOE is adopting the target values proposed in case instructions are not
provided.
Unico did not support charging to a specific subcooling value in
heating unless the product is heating-only (Unico, No. 63 at p. 10).
Responding to DOE's question about confirming proper operation in
the H1 or H12 test for heat pumps following charging at the
A or A2 test condition, JCI requested that manufacturers be
permitted to set charge levels in either heating or cooling mode (JCI,
No. 66 at p. 19). Rheem agreed with the proposal to test a heat pump in
the H1 or H12 test in case it does not operate properly in
heating mode with a charge set in the cooling mode, provided a
definition of nonfunctional is added to the test procedure. (Rheem, No.
69 at p. 13) In response, DOE added explanation in section 2.2.5.2.b
that shutdown of a unit by its limiting devices would constitute non-
operation.
DOE notes that the proposal in the November 2015 SNOPR requires
that the installation instructions shipped with the system be consulted
for instructions about how to charge the unit, and that the generic
instructions be used only if no instructions are provided with the
unit. Hence, a manufacturer has the option of requiring that charge be
adjusted in cooling mode or to higher subcooling levels than indicated
in section 2.2.5.4 of the November 2015 SNOPR, both of which would
address Unico's concerns. Likewise, a manufacturer could specify that
charge be set in either heating or cooling mode, which addresses JCI's
concerns. 80 FR 69278, 69308 (Nov. 9, 2015).
In order to clarify that the manufacturer can specify the operating
mode to be used for setting charge, DOE has added language to section
2.2.5.2 of this final rule notice allowing manufacturers the option of
specifying tests for charging other than the A or A2 test.
DOE maintains, however, the requirement that air volume rate must be
determined by the A or A2 test.
Goodman disagreed that all single-package units must be pressure-
verified, requesting an option for manufacturers to specify whether or
not to connect pressure measurement devices (Goodman, No. 73 at p. 9).
In response, section 2.2.5.5 of this final rule notice allows for
manufacturers to specify in installation instructions whether or not
pressure measurement instruments should be attached. Otherwise, DOE is
adopting the proposal regarding refrigerant pressure gauges.
For the final rule, DOE has explicitly designated the charging
tolerances as test condition tolerances (see section 2.2.5.4). This
clarifies that the charging tolerances refer to the maximum permissible
differences between the average value of the measured temperature and
the specified temperature in the DOE test procedure.
Also for the final rule, DOE has relaxed the tolerance on
subcooling in section 2.2.5.4 from +/- 0.6 [deg]F (the maximum
tolerance listed in the draft version of AHRI 210/240) to +/- 2.0
[deg]F. DOE is adopting this change for two reasons. First, in re-
examining past tests, DOE has observed considerable variation in
subcooling temperatures even for properly installed systems that are
operating correctly. DOE believes a test condition tolerance of +/- 0.6
[deg]F will unnecessarily increase the difficulty of testing these
units. Second, the minimum accuracy requirements in the current test
procedure on the temperature and pressure instruments could result in
as much as a 3.0 [deg]F measurement uncertainty on subcooling. Using
today's typical instrumentation, however, the expected measurement
uncertainty is about 1.0 [deg]F. DOE does not wish to require tighter
tolerances than measurement uncertainties. Based on this, DOE settled
on the average, a 2.0 [deg]F test condition tolerance on subcooling.
DOE analyzed the impact of this tolerance change on capacity and
EER by simulating performance across split-system and single-package
air-conditioners as well as split-system heat pumps, varying the
subcooling. On both capacity and EER, the impact of a 2.0 [deg]F
fluctuation was less than 1% of the capacity and EER at baseline
subcooling. DOE concluded that the advantages of increasing the
tolerance in reducing test burden outweighed this impact. Hence, as
mentioned, DOE is adopting the 2.0 [deg]F tolerance on subcooling.
DOE received no other comments on proposals concerned with changing
the refrigerant charge after setup, reporting the type of metering
device, refrigerant charge verification, and/or any other DOE
proposals. Consequently, DOE is adopting these proposals for this final
rule notice.
9. Alternative Arrangement for Thermal Loss Prevention for Cyclic Tests
In the November 2015 SNOPR, DOE proposed an alternative testing
arrangement to prevent thermal losses during the compressor OFF period
that would eliminate the need to install a damper in the inlet duct
that conveys indoor chamber air to the indoor coil. The proposed
alternative testing arrangement would allow the use of a duct
configuration that relies on changes in duct height, rather than a
damper, to eliminate natural convection thermal transfer out of the
indoor duct during OFF periods of the ``cold'' (for tests of cooling
mode) or heat (for tests of heating mode) generated by the system
during the ON periods. An example of such an arrangement would be an
upturned duct installed at the inlet of the indoor duct, such that the
indoor duct inlet opening, facing upwards, is sufficiently high to
prevent natural convection transfer out of the duct. The approach was
developed for situations where insufficient space is available to
install a damper box for both the inlet and outlet ductwork--the
approach still requires use of a damper box on the outlet. DOE also
proposed to require installation of a dry bulb temperature sensor near
the inlet opening of the indoor duct at a centerline location not
higher than the lowest elevation of the duct edges at the inlet.
Measurement and recording of dry bulb temperature at this location
would be required at least every minute during the compressor OFF
period to confirm that no thermal loss occurs. DOE proposed a maximum
permissible variation in temperature measured at this location during
the OFF period of 1.0 [deg]F. 80 FR 69278, 69308-09 (Nov.
9, 2015). ADP supported this approach. (ADP, No. 59 at p. 11)
[[Page 37032]]
Rheem commented that the currently required damper in the inlet
portion of the indoor air ductwork has not been a source of variation
in their test results. Rheem plans to continue using the current damper
configuration. Rheem did not support an optional configuration. (Rheem,
No. 69 at p. 13, 14) Rheem has not explained their objection to
allowing use of the alternative approach sufficiently for DOE to
understand the concern. Hence, in this final rule, DOE is adopting the
option to allow an alternative testing arrangement to prevent thermal
losses for cyclic testing. If the alternative testing arrangement is
used, installation of a dry bulb temperature sensor near the inlet
opening of the indoor duct would be required, as well as measuring and
recording the dry bulb temperature from this sensor.
JCI agreed with the proposal, but was concerned that it may not be
possible to maintain the 1.0 [deg]F tolerance at the duct inlet with
continuous readings. (JCI, No. 66 at p.18). In response, DOE has
relaxed the requirement such that any pair of 5-minute averages of the
dry bulb temperature at the inlet, measured at least every minute
during the compressor OFF period of the cyclic test, do not differ by
more than 1.0 [deg]F.
10. Test Unit Voltage Supply
In the November 2015 SNOPR, DOE clarified that the outdoor voltage
supply requirement supersedes the indoor requirement if the provisions
result in a difference for the indoor and outdoor voltage supply. DOE
proposed that both the indoor and outdoor units be tested at the
nameplate voltage of the outdoor unit. 80 FR 69278, 69309 (Nov. 9,
2015).
DOE received no comment on this proposal, however DOE recognized
that it is possible that the nameplate voltages of the indoor and
outdoor units could be so different that one unit cannot operate with
the other's voltage supply. For example, if the outdoor unit requires
230V while the indoor unit requires 120V, applying 230V to the indoor
unit would not be appropriate. DOE reviewed the range of nameplate
voltages typically used for single-phase products as listed in Table 1
on page 3 of AHRI Standard 110-2012, ``Air-Conditioning, Heating and
Refrigerating Equipment Nameplate Voltages'' and determined that the
only pair of nameplate voltages for which the electrical components for
a product rated with one could operate using the voltage rated with the
other are 208 V (200 V) and 230V. Hence, DOE has decided to require use
of the outdoor voltage supply for both indoor and outdoor components
only when one is rated with 208V or 200V and the other one is rated
with 230V. For all other voltage combinations, DOE will require
supplying each unit with its own nameplate voltage.
11. Coefficient of Cyclic Degradation
The current test procedure gives manufacturers the option to use a
default cyclic degradation coefficient for cooling mode
(CDc) value of 0.25 instead of running the
optional cyclic test. In the November 2015 SNOPR, DOE proposed to
update the default cooling CDc value in Appendix
M to 0.2 based on testing of 19 units for which the measured
degradation coefficient for cooling ranged from 0.02 to 0.18. DOE did
not propose to update the default heating CDh
value. 80 FR 69278, 69309 (Nov. 9, 2015).
Responding to DOE's proposal on the coefficient of cyclic
degradation, stakeholders generally agreed with the proposed default of
0.2 for cooling. (see, e.g., AHRI, No. 70 at p. 12 or Ingersoll Rand,
No. 65 at p. 1) The test procedure adopted in this final rule includes
the proposed value of 0.2 as the default degradation coefficient for
cooling for single-speed and two-capacity units.
However, DOE is aware that units with variable-speed compressors
consistently have a higher coefficient of cyclic degradation than units
with single-speed or two-capacity compressors. DOE reviewed the
California Energy Commission (CEC) database of variable speed air
conditioners and observed that the variable speed products rarely have
a cooling CDc as low as 0.2. In its review of the
CEC database, DOE noticed that many variable speed units are listed as
multiple speed units. DOE separated the variable speed units from this
group based on review of the product specification sheets, thus leading
to a more complete list of variable speed models. As a result DOE found
that, of 639 listed models that have variable-speed operation, only 76
(i.e. 11%) are rated with a CDc value less than
or equal to 0.2. As discussed above, DOE initially proposed reducing
the default value from 0.25 to 0.2 based on test data showing
CDc values consistently below 0.2. However, these
data did not include measurements for variable-speed units. Based on
the clear evidence as illustrated by the CEC database information, the
0.2 value is not representative of the cyclic performance of variable-
speed units. Hence, DOE has maintained the current default cooling
CDc of 0.25 for variable speed products and
unmatched outdoor units (see section III.A.3.g), while changing to a
default value of 0.2 for all other products as proposed.
DOE also proposed significant changes to the cyclic test. DOE
proposed that before determining CDc, three
``warm up'' cycles for a unit with a single-speed compressor or two-
speed compressor or two ``warm up'' cycles for a unit with a variable
speed compressor must be conducted. Then a minimum of three complete
cycles would be conducted after the warm-up period, taking a running
average of CDc after each additional cycle. If
after three cycles, the average of three cycles does not differ from
the average of two cycles by more than 0.02, the three-cycle average
should be used. If it differs by more than 0.02, up to two more valid
cycles must be conducted. If the average CDc of
the last three cycles are within 0.02 of or lower than the previous
three cycles, use the average CDc of all valid
cycles. After the fifth valid cycle, if the average
CDc of the last three cycles is more than 0.02
higher than the previous three cycles, the default value must be used.
DOE proposed the same changes for the test method to determine the
heating coefficient of degradation. 80 FR 69278, 69309 (Nov. 9, 2015).
As a departure from the current test procedure approach, DOE
proposed that manufacturers would have to conduct cyclic testing to
determine CDc for each tested unit, rather than
allowing them to use the default and avoid cyclic testing. Per the
proposal, the default value would be used only if stability was not
achieved during testing or when rating outdoor units with no match. 80
FR 69278, 69309 (Nov. 9, 2015).
AHRI, Lennox, UTC/Carrier, Ingersoll Rand, JCI, and Rheem commented
that manufacturers should be allowed to use the default value without
having to run the cyclic test. (AHRI, No. 70 at p. 12; Lennox, No. 61
at p. 18; UTC/Carrier, No. 62 at p. 17; Ingersoll Rand, No. 65 at p. 2,
JCI, No. 66 at p. 10; Rheem, No. 69 at p. 14) In contrast, NEEA
commented in response to the June 2010 NOPR that laboratory
measurements are often ``at odds'' with the 0.25 default value, and
suggested that testing is more accurate and should always be conducted.
The comment did not indicate whether the measurements were generally
higher or lower than the default. (NEEA, No. 7 at p. 6)
Lennox, UTC/Carrier, Rheem and AHRI suggested that a manufacturer
should be allowed to use the first two cycles meeting a stability
requirement, rather than requiring three warm-up cycles before official
measurement begins. (Lennox, No. 61 at p. 18; UTC/Carrier, No. 62 at p.
17; Rheem, No. 69 at p. 14; AHRI, No. 70 at p.11). If
[[Page 37033]]
stability is not reached after eight cycles, several manufacturers
suggested use of either a measured value or the default value,
whichever is lower, rather than requiring use of the default value.
Lennox, Rheem and UTC/Carrier suggested that this measured value be the
highest CDc recorded for any of the eight test
cycles. (Lennox, No. 61 at p.18; Rheem, No. 69 at p. 14; UTC/Carrier,
No. 62 at p. 17) JCI suggested that the measured value be the average
of the three highest measured CDc values (JCI,
No. 66 at p. 10), and Ingersoll Rand suggested that the measured value
be the highest CDc recorded in cycles four
through eight (Ingersoll Rand, No. 65 at p. 3).
After reviewing all the stakeholders' comments, DOE has decided to
allow manufacturers to use the default value without testing. Also, DOE
is removing the requirement to conduct three warm-up cycles prior to
making measurements. In the test finalized in this notice, a minimum of
three cycles must be measured, and the test may then be terminated if
the stability requirement is achieved. The test will still be required
to continue for up to eight cycles if stability is not achieved. When
the test is terminated, the highest CDc value
recorded for any one test cycle would be used, unless it is higher than
the default CDc, in which case the default would
be used. The same approach is also adopted for the heating mode cyclic
test. In response to the NEEA comment, DOE's data suggest that most
single-stage and two-stage units have cyclic degradation coefficients
less than the default and, in DOE's experience, manufacturers of such
products nearly always run the cyclic test. DOE specifically re-
evaluated selection of the default value so that it is higher than the
expected result, but DOE retains in its procedures use of the default
value rather than testing to limit test burden for cases where a low
CDc is not critical to assuring that the
represented value is compliant with the standard (e.g. for variable-
speed units, which generally have higher CDc than
single-stage or two-stage units).
In order to improve the accuracy of the cyclic test, DOE proposed
in the June 2010 NOPR a calibration step in which the temperature
difference between measurements of the inlet and outlet thermocouple
grids used to make the cyclic test capacity measurements is checked
during the steady state test which precedes the cyclic test (e.g. the
steady state C test for cooling). If this temperature difference
compares unfavorably to the more accurate dry bulb temperature
difference based on air samplers and sample-air temperature sensors
(e.g. resistance temperature detectors (RTDs)), the proposal required
that a calibration adjustment be made for the thermocouple grid
measurements for use in the cyclic test. 75 FR 31235 (June 2, 2010).
NEEA commented that they have no objection to DOE's proposal. (NEEA,
No. 7 at p. 4) In contrast, AHRI disagreed with DOE's proposal and
supported using the same temperature devices between the steady-state
tests and cyclic tests to calculate CD in order to ensure
consistency of measurement between the two tests. (AHRI, No. 6 at p. 3)
DOE notes that AHRI's recommended solution, use of the thermocouple
grids for measurement of the inlet/outlet temperature difference for
both the steady-state and cyclic tests used as the basis for
calculating CD, does not fully resolve the potential error
in measurement if the measured temperature difference is high or low.
In such a case, both the steady state and cyclic capacity estimates may
be incorrect, and the overall measurement less precise than if the
calibration step is taken. In order to achieve the original goal of
improving the accuracy of the cyclic test, the test procedure in this
final rule notice includes the proposed calibration step.
12. Break-in Periods Prior to Testing
DOE proposed in the November 2015 SNOPR to allow manufacturers the
option of specifying a break-in period to be conducted prior to testing
under the DOE test procedure. DOE proposed to limit the optional break-
in period to 20 hours, which is consistent with the test procedure
final rule for commercial HVAC equipment. DOE also proposed to adopt
the same provisions as the commercial HVAC rule regarding the
requirement for manufacturers to report the use of a break-in period
and its duration as part of the test data underlying their product
certifications, the use of the same break-in period specified in
product certifications for testing conducted by DOE, and use of the 20
hour break-in period for products certified using an AEDM. 80 FR 69278,
69310 (Nov. 9, 2015).
In response to the November 2015 SNOPR, Unico supported the option
of having a break-in period and had no comment on the number of hours.
(Unico, No. 63 at p. 11) Several other commenters requested longer
break-in periods than 20 hours. LG and Ingersoll Rand commented that on
average 40 hours of operation are required to reach peak capacity and
efficiency. (LG, No. 55 at pp. 1-2; Ingersoll Rand, No. 65 at pp. 10-
11) Rheem commented that manufacturers should have the option of up to
a 48 hour break-in period. (Rheem, No. 69 at p. 14) Goodman commented
that at least 72 hours should be permitted for break-in period testing
because they believe that shorter break-in periods could produce test
results that are inaccurate. (Goodman, No. 73 at pp. 12-13) Lennox,
UTC/Carrier, and JCI also commented that some compressor manufacturers
recommend up to 72 hours break-in. (Lennox, No. 61 at p. 19; UTC/
Carrier, No. 62 at p. 17; JCI, No. 66 at p. 19) UTC/Carrier requested
that DOE research directly with compressor manufacturers to align with
their recommended compressor break-in periods. (UTC/Carrier, No. 62 at
p. 17) Lennox commented that manufacturers should be able to specify
break-in conditions. (Lennox, No. 61 at p. 19) JCI commented that if a
manufacturer is willing to pay for an extended break-in time, it is
reasonable to allow it, as it more closely represents what the consumer
will see in the installation. (JCI, No. 66 at p. 19)
LG and Ingersoll Rand further commented that they have worked
towards a process for reducing the required break-in period for scroll
compressors, and have developed a process to reduce the required break-
in period to 12 hours. (LG, No. 55 at pp. 1-2; Ingersoll Rand, No. 65
at pp. 10-11) LG commented that they will be phasing in this new
process through 2016, and requested DOE to adopt a phase-in approach
for the rule implementation, with the limit being 40 hours on the rule
effective date followed by the final 20 hour limit that would commence
one year after the effective date. (LG, No. 55 at pp. 1-2) Ingersoll
Rand recommended the effective date of the maximum break-in time be
January 1, 2017. (Ingersoll Rand, No. 65 at pp. 10-11)
In a supplemental response to the October 2011 SNOPR, AHRI
requested that DOE implement an optional 75-hour break-in period for
testing central air conditioners and heat pumps. It stated that scroll
compressors, which are the type of compressors most commonly used in
central air conditioners and heat pumps, achieve their design
efficiency after 75 hours of operation. AHRI also cited a study of
compressor break-in periods to justify this period of time.\15\ 80 FR
69278, 69309-310 (Nov. 9, 2015).
---------------------------------------------------------------------------
\15\ Khalifa, H.E. ``Break-in Behavior of Scroll Compressors''
(1996). International Compressor Engineering Conference. Paper 1145.
---------------------------------------------------------------------------
In the November 2015 SNOPR, DOE noted that, in reviewing the paper
that AHRI cited, while the data indicate that products with scroll
compressors do appear to converge upon a more
[[Page 37034]]
consistent result after compressor break-in periods exceeding 75 hours,
the most significant improvement in compressor performance and
reduction in variation among compressor models both appear to occur
during roughly the first 20 hours of run time.\16\ 80 FR 69278, 69310
(Nov. 9, 2015). Considering the improvements in break-in as discussed
in the comments of LG and Ingersoll-Rand, as well as the 1996 data
which shows that most of the break-in occurs within 20 hours, DOE
concludes that setting the bread-in period at 20 hours appropriately
balances test burden and full completion of the break-in process.
---------------------------------------------------------------------------
\16\ Ibid. pp. 442-443.
---------------------------------------------------------------------------
After reviewing the comments, DOE maintains its proposal from the
SNOPR, and will allow a break-in period up to a maximum of 20 hours. As
noted in the November 2015 SNOPR, DOE believes that a lengthy break-in
period is not appropriate or justified. Since DOE determined in the May
16, 2012 commercial HVAC equipment final rule that a 20 hour maximum
break-in time would be sufficient for small commercial air-conditioning
products, which are of a capacity similar to central air-conditioning
products, DOE does not see justification for a break-in period longer
than 20 hours for central air conditioners and heat pumps. DOE
acknowledges the research being done to reduce the break-in period as
highlighted by LG and Ingersoll Rand, but DOE notes that at this time,
none of the commenters has provided new information or data that
sufficiently justifies the need for a longer break-in period.
Some commenters also requested that DOE provide additional
specification regarding the break-in. The California IOUs recommended
that DOE specify the operation of systems during the break in period or
require the OUM to specify how the break-in should be done. (California
IOUs, No. 67 at p. 5) Rheem commented that the break-in period should
be at the A test cooling condition after the unit is properly charged.
(Rheem, No. 69 at p. 14)
Without test results clearly showing the benefits of a particular
set of break-in conditions, DOE is reluctant to require conditions for
break-in that will require it to be conducted in the psychrometric
chamber as part of a test, due to the significant test burden that such
a requirement would impose. DOE declines to add more specification to
the break-in period at this time but may consider modifications in a
future rulemaking, provided sufficient information is provided to
justify specific recommendations.
13. Industry Standards That Are Incorporated by Reference
In the November 2015 SNOPR, DOE proposed a number of updates to
industry standards that are incorporated by reference. DOE proposed to
update the IBR from ARI 210/240-2006 to AHRI 210/240-2008; ASHRAE 37-
2005, Methods of Testing for Rating Unitary Air-Conditioning and Heat
Pump Equipment to ANSI/ASHRAE 37-2009, Methods of Testing for Rating
Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment;
ASHRAE 41.9-2000, Calorimeter Test Standard Methods for Mass Flow
Measurements of Volatile Refrigerants to ASHRAE 41.9-2011, Standard
Methods for Volatile-Refrigerant Mass Flow Measurements Using
Calorimeters; ASHRAE/AMCA 51-1999/210-1999, Laboratory Methods of
Testing Fans for Aerodynamic Performance Rating to AMCA 210-2007,
Laboratory Methods of Testing Fans for Certified Aerodynamic
Performance Rating; ASHRAE 41.1-1986 (Reaffirmed 2006), Standard Method
for Temperature Measurement, to ANSI/ASHRAE 41.1-2013, Standard Method
for Temperature Measurement; ASHRAE 41.6-1994, Standard Method for
Measurement of Moist Air Properties to ASHRAE 41.6-2014, Standard
Method for Humidity Measurement; and ASHRAE 23-2005, Methods of Testing
for Rating Positive Displacement Refrigerant Compressors and Condensing
Units, to ASHRAE 23.1-2010 Methods of Testing for Rating the
Performance of Positive Displacement Refrigerant Compressors and
Condensing Units That Operate at Subcritical Temperatures of the
Refrigerant. DOE expressed the view that none of these updates includes
significant changes to the sections referenced in the DOE test
procedure and thus will not impact the ratings or energy conservation
standards for central air conditioners and heat pumps.\17\ 80 FR 69278,
69310-11 (Nov. 9, 2015).
---------------------------------------------------------------------------
\17\ ANSI/ASHRAE 37-2009 only updates to more recent versions of
other standards it references. AMCA 210-2007 made slight changes to
the figure referenced by DOE, which DOE has determined to be
insignificant.
---------------------------------------------------------------------------
In response, JCI encouraged DOE to utilize industry standards to
the fullest extent possible. (JCI, No. 66 at p. 20) Goodman requested
that DOE, along with other stakeholders, continue participation in the
revision of AHRI 210/240 to assist in getting to the point where DOE
can potentially adopt this standard outright. (Goodman, No. 73 at p.
16)
Ingersoll Rand requested DOE to remove all references to AMCA 210-
2007, because it is for standalone air moving systems and does not
match the configuration used for ducted HVAC equipment. (Ingersoll
Rand, No. 65 at p. 13) AHRI and UTC/Carrier commented that the
reference to AMCA 210-2007 in lieu of ASHRAE 116-1995 (RA 2005) for the
air flow measurement apparatus is incorrect, and that instead the
reference should be to section 6.3 of ANSI/ASHRAE 37-2009 or ASHRAE
41.2. (AHRI, No. 70 at p. 12; UTC/Carrier, No. 62 at p. 18)
DOE believes that the referenced sections are applicable to the
airflow measurements required in Appendix M, as demonstrated by the
installation types referenced in section 5.1.1 of AMCA 210-2007. DOE
also notes that AHRI 210/240-2008 references the same sections of AMCA
210-2007 as Appendix M does, but DOE has simply chosen to reference
AMCA 210-2007 directly. In response to AHRI and UTC/Carrier, DOE notes
that section 2.6 of this final rule notice does reference sections 6.2
and 6.3 of ANSI/ASHRAE 37-2009 for fabricating and operating the
Airflow Measurement Apparatus, and the manufacturer may refer to either
Figure 12 of AMCA 210-2007 or Figure 14 of ASHRAE 41.2-1987 (RA 1992)
for guidance on placing the static pressure taps and positioning the
diffusion baffle. For these reasons, DOE maintains its incorporation by
reference of AMCA 210-2007. DOE received no other comments on these
proposed updates to industry standards, and in this final rule, DOE
adopts all references to industry standards as proposed in the November
2015 SNOPR.
In the November 2015 SNOPR, DOE also proposed to revise the
definition of ``continuously recorded'' based on changes to ASHRAE
41.1. ASHRAE 41.1-1986 (RA 2006) specified the maximum time interval of
one minute for sampling dry-bulb temperature during a steady state
test, with shorter sampling intervals based on expected rate of
temperature change. The updated version, ANSI/ASHRAE 41.1-2013, does
not contain specifications for sampling intervals. DOE proposed to
require that dry-bulb temperature, wet bulb temperature, dew point
temperature, and relative humidity data be ``continuously recorded,''
that is, sampled and recorded at 5 second intervals or less. DOE
proposed this requirement as a means of verifying that temperature
condition requirements are met for the duration of the test. 80 FR
69278, 69311 (Nov. 9, 2015).
UTC/Carrier and Rheem supported the proposed sampling interval.
(UTC/
[[Page 37035]]
Carrier, No. 62 at p. 18; Rheem, No. 69 at p. 15) On the other hand,
JCI recommended a longer sampling interval of 10 to 15 seconds, as
there may be capital investment and programming required. (JCI, No. 66
at p. 20) Rheem commented that clarification is needed on how
measurements such as the air leaving temperature are calculated from
the multitude of values in the data sample. (Rheem, No. 69 at p. 15)
In response to JCI, DOE believes that the current standard of care
requires digital data acquisition of all temperature and humidity
measurements. DOE understands that for measurements being taken and
recorded digitally, decreasing the sampling interval generally should
have an insignificant impact on burden, since state-of-the-art data
acquisition systems can easily record data at faster rates and the cost
of the additional data storage is minimal. However, DOE understands
that any specific test laboratory may require significant investment to
upgrade to a faster data rate, depending on the capabilities of their
current data acquisition systems, and hence has decided to increase the
required sampling interval to 15 seconds. In response to Rheem's
request for clarification, DOE believes that it is common industry
practice, when continuously recording a parameter such as air leaving
temperature, to average the value over the sampled interval. However,
to enhance clarity, DOE has added words to sections 3.3.c and 3.7.b of
Appendix M indicating that capacity is to be calculated using the
averages of the 30-minute continuously-recorded measurements made for
the parameters that are used to determine capacity (e.g. indoor air
inlet and outlet temperatures).
14. References to ASHRAE Standard 116-1995 (RA 2005)
In the June 2010 NOPR, DOE proposed referencing ASHRAE Standard
116-1995 (RA 2005) within the DOE test procedure to provide additional
information about the equations used to calculate SEER and HSPF for
variable-speed systems. 75 FR 31223, 31243 (June 2, 2010). However, in
section III.H.4 of the November 2015 SNOPR, DOE proposed to change the
heating load line, and as such the equations for HSPF in ASHRAE 116-
1995 (RA 2005) are no longer applicable. In order to prevent confusion,
DOE proposed to withdraw the original proposal made in the June 2010
NOPR to reference ASHRAE 116-1995 (RA 2005) for both HSPF and SEER by
removing those instances of these references. 80 FR 69278, 69311 (Nov.
9, 2015).
DOE also proposed to revise its reference for the requirements of
the air flow measuring apparatus from ASHRAE 116-1995 (RA 2005) to
ANSI/ASHRAE 37-2009. As this was the only other reference to ASHRAE 116
in Appendix M, DOE proposed to remove the incorporation by reference to
ASHRAE 116-1995 (RA 2005) from the Code of Federal Regulations related
to central air conditioners and heat pumps. 80 FR 69278, 69311 (Nov. 9,
2015).
AHRI, UTC/Carrier, Ingersoll Rand, Goodman, Rheem, and JCI
disagreed with the proposal to withdraw the incorporation by reference
of ASHRAE 116-1995 (RA 2005). (AHRI, No. 70 at p. 12; UTC/Carrier, No.
62 at pp. 17-18, Ingersoll Rand, No. 65 at p. 3; Goodman, No. 73 at p.
11; Rheem, No. 69 at p. 14; JCI, No. 66 at p. 10) AHRI, UTC/Carrier,
Ingersoll Rand, Goodman, and JCI suggested adding a reference to the
section on thermal mass correction to the cyclic capacity (section
7.4.3.4.5) to reduce variability. (AHRI, No. 70 at p. 12; UTC/Carrier,
No. 62 at pp. 17-18, Ingersoll Rand, No. 65 at p. 3; Goodman, No. 73 at
p. 11; JCI, No. 66 at p. 10)
DOE notes that the current test procedure does not reference the
thermal mass correction to cyclic capacity. DOE acknowledges that,
because ASHRAE 116 has been incorporated by reference into the DOE test
procedure, and because the cyclic test would first have been developed
as part of ASHRAE 116, it is understandable that the prevailing
interpretation may have been that the correction has always been
included in the DOE test procedure. DOE also acknowledges that the
thermal mass stored in devices and connections located between measured
points must be accounted for to ensure repeatability and accuracy of a
cyclic test. DOE understands that accounting for thermal mass in this
way is common industry practice. Therefore, DOE has included provisions
in section 3.5 of the final rule requiring a thermal mass adjustment,
referencing section 7.4.3.4.5 of ASHRAE 116-2010. DOE notes that it has
updated the IBR from ASHRAE 116-1995 (RA 2005) to ASHRAE 116-2010, but
the content of the referenced section has not changed.
15. Additional Changes Based on AHRI 210/240-Draft
In August 2015, AHRI provided a draft version of AHRI 210/240 for
the docket that will supersede the 2008 version once it is published.
(AHRI Standard 210/240-Draft, No. 45, See EERE-2009-BT-TP-0004-0045)
The draft version includes a number of revisions from the 2008 version,
some of which already exist in DOE's test procedure, and some of which
do not. In the November 2015 SNOPR, DOE proposed to adopt several of
these revisions. DOE noted that the final published version of what is
currently the AHRI 210/240-Draft may not be identical to the docketed
draft, and that if AHRI makes other than minor editorial changes to the
sections DOE referenced in the SNOPR after publication, DOE would adopt
the current draft content into its regulations and not incorporate by
reference the modified test procedure. 80 FR 69278, 69312 (Nov. 9,
2015).
The AHRI 210/240-Draft added new size requirements for the inlet
duct to the indoor unit, new external static pressure requirements for
units intended to be installed with the airflow to the outdoor coil
ducted, and a new requirement for the dew point temperature of the
indoor test room when the air surrounding the indoor unit is not
supplied from the same source as the air entering the indoor unit. DOE
proposed to adopt these three revisions in the November 2015 SNOPR. 80
FR 69278, 69311 (Nov. 9, 2015).
DOE received comments from Ingersoll Rand regarding the proposed
requirements for the inlet duct, which are discussed in section
III.E.18. DOE did not receive any comments on the new external static
pressure and dew point requirements and is adopting these revisions in
this final rule.
The AHRI 210/240-Draft included differences as compared to the
current DOE test procedure for setting air volume rates during testing.
DOE proposed to adopt three of these changes because they would improve
repeatability and the consistency of testing among different
laboratories. 80 FR 69278, 69312 (Nov. 9, 2015). They include (a) use
of air volume rates specified by manufacturers, (b) setting ESP
requirements for operating modes other than full-load cooling, and (c)
establishing an instability criterion for testing of units with
constant-air-volume indoor blowers. DOE received no comments regarding
these proposals and adopts them in this final rule.
DOE did receive several comments on other proposals related to
setting air volume rates and has addressed these comments and revisions
in section III.E.1.
The AHRI 210/240-Draft also included a more thorough procedure for
setting of refrigerant charge than exists in the DOE test procedure.
DOE proposed these changes because they improve test repeatability.
[[Page 37036]]
The AHRI 210/240-Draft also specifies both a target value tolerance
and a maximum tolerance but does not specify in what circumstances each
of these apply. In response, UTC/Carrier commented that they would like
more detail, as correct refrigerant charging has a significant impact
on performance and product reliability. (UTC/Carrier, No. 62 at p. 18)
DOE interprets this comment as support of the additional detail
regarding instructions for setting charge that were proposed in the
November 2015 SNOPR, since the comment does not provide clarification
regarding potential additional details that might be needed.
As an elaboration on DOE's past methodology, DOE believed that the
AHRI 210/240-Draft did not clearly delineate how target value and
maximum tolerances should be applied. Following from this lack of
clarity, in the November 2015 SNOPR, DOE proposed to adopt the most
liberal restriction on tolerance, the maximum tolerance, disregarding
the AHRI 210/240-Draft target value. In addition, DOE proposed
tolerances on the measured superheat and other parameters that would be
set to specified levels during charging. 80 FR 69278, 69312 (Nov. 9,
2015). In this final rule, DOE continues to reference the maximum
tolerance only. Additional comments regarding the procedure for setting
of refrigerant charge, and revisions to the proposal are discussed in
section III.E.8.
Finally, the AHRI 210/240-Draft included specifications for air
sampling that provide more detail than provided in existing standards--
DOE proposed incorporation of a number of these air sampling
specifications into its test procedures. DOE did not receive comment on
this proposal and is adopting the specifications in this final rule.
However, DOE initially proposed incorporation by reference of sections
of the AHRI 210/240-Draft, expecting that the standard might be
published prior to this final rule. Because the AHRI standard was not
finalized in time to incorporate the relevant sections of AHRI 210/240
by reference, DOE included the following provisions from the AHRI 210/
240 draft in this final rule in order to finalize the proposal to adopt
Appendix E4 Air Sampling Requirements in the November 2015 NOPR. DOE
implemented these provisions consistent with the way they appear in the
AHRI 210/240-Draft.
DOE provided the definitions of Air Sampling Device and
Aspirating Psychrometer to Section 1.2, Definitions, in Appendix M.
DOE provided Section 2.14, Air Sampling Device and
Aspirating Psychrometer Requirements, to Appendix M based on E 4.4 and
E 4.6 of AHRI 210/240-Draft.
DOE integrated the outdoor test setup instructions in E
4.2, E 4.4 and E 4.6 of AHRI 210/240-Draft and adopted those in Section
2.11 of Appendix M, with some revisions to improve clarity.
In Section 2.11, DOE provided additional instructions
regarding blockage of air sampling holes when this is done to prevent
sampling of recirculated air. The revisions are intended to preserve
symmetry and uniformity of air flow into the holes.
In Section 2.11, DOE also clarified that tubes conveying
sampled air may have reduced insulation requirements if dry bulb
temperature measurements are made at the exit of each air sampler.
16. Damping Pressure Transducer Signals
In the June 2010 NOPR, DOE proposed to loosen the existing test
operating tolerance assigned to the external resistance to airflow
(ESP) from 0.05 to 0.12 in wc and the nozzle pressure drop tolerance
from 2.0 percent to 8.0 percent. 75 FR 31223, 31234 (June 2, 2010).
In response to the June 2010 NOPR proposal, NEEA commented that it
strongly disagreed with DOE's proposal, particularly for the ESP
tolerance. NEEA also commented that it strongly supported another
option presented by DOE at the June 11, 2010 public meeting, which is
to lengthen the time constant for the measurements by signal
integration and averaging, using a DOE-specified interval. (NEEA, No. 7
at p. 4)
AHRI commented that they disagreed with DOE's proposal to relax ESP
and nozzle pressure drop tolerances. AHRI believed that the pressure
transducer fluctuation issues could be resolved by implementing a time
averaging routine or some kind of electronic damping algorithm that
would provide the same results as a liquid manometer, using an
algorithm agreed upon by AHRI members. (AHRI, No. 6 at p. 3)
In the November 2015 SNOPR, rather than proposing a revision of the
operating tolerances for external resistance to airflow or nozzle
pressure drop, DOE proposed to add clarifying language in the test
procedure that would allow for damping of the measurement system to
prevent high-frequency fluctuations from affecting recorded pressure
measurements. The proposal allowed for damping of the measurement
system so that the time constant for response to a step change in
pressure (i.e. the time required for the indicated measurement to
change 63% of the way from its initial value to its final value) would
be no more than five seconds. This damping could be achieved in any
portion of the measurement system. 80 FR 69278, 69312 (Nov. 9, 2015).
Rheem agreed with DOE's November 2015 SNOPR proposal regarding
operating tolerances for external resistance to airflow or nozzle
pressure drop. (Rheem, No. 69 at p. 15) JCI also agreed with that
approach, but suggested that the time constant for response to a step
pressure signal should be increased to 10 or 15 seconds, without
providing an explanation why the slower response is needed. (JCI, No.
66 at p. 20) No commenters disagreed with the proposal. The intent of
the damping is to address fluctuations associated with turbulence that
would have a frequency so high that they would not be captured with a
system with a 5 second response time. In the absence of more
explanation regarding why the 5 second response is insufficient, DOE
maintains this value for the damping allowance and, due to the absence
of dissenting comments, DOE adopts this revision in the test procedure.
17. Clarify Inputs for the Demand Defrost Credit Equation
In the June 2010 NOPR, DOE proposed language in the test procedure
to clarify that manufacturers must assign [Delta][tau]def
(the greater of the time in hours between defrost terminations and 1.5)
the value of 6 hours if this limit is reached during a frost
accumulation test and the heat pump has not completed a defrost cycle.
A sentence was also proposed to be added in section 3.9.2 of Appendix M
to indicate that the manufacturer must use a value of
[Delta][tau]max, that is either the maximum time between
defrosts as allowed by the controls (in hours) or 12, whichever is
less. 75 FR at 31237 (June 2, 2010). In the proposal of the November
2015 SNOPR, this was changed to indicate that the value would be as
provided in the installation manuals shipped with the unit. 80 FR at
69373 (Nov. 9, 2016).
AHRI supported DOE's proposal to clarify inputs to the demand
defrost credit equation with the understanding that HSPF values would
not be affected by such clarifications. (AHRI, No. 6 at p. 4) Ingersoll
Rand stated that the facts do not support AHRI's understanding as there
are significant numbers of heat pumps for which the reduction of the
maximum permissible test duration from 12 to 6 hours would decrease the
calculated HSPF. Ingersoll Rand further commented that reducing max
duration of frost accumulation tests from 12 hours to 6 hours and
eliminating the
[[Page 37037]]
short-cut method for determining SEER would reduce the rated
performance of AC/HP, which would be an adverse situation for
manufacturers. Ingersoll Rand commented that this would require re-
rating of units that are above 13 SEER and un-rating units that are at
13 SEER. (Ingersoll Rand, No. 10 at p. 1)
As noted in the June 2010 SNOPR, for most two-capacity and
variable-speed heat pumps the proposal for the 6-hour limit reduces
manufacturer test burden when defrost does not occur. DOE believes that
when defrost does occur, the proposal has a negligible impact on the
calculation of the average heating capacity and power consumption at a
35 [deg]F outdoor temperature. Shortening the maximum duration of the
frost accumulation test affects heat pumps that would otherwise conduct
a defrost after 6 but before 12 hours in two ways. First, such heat
pumps benefit slightly from not having a defrost cycle factored into
their average heating capacity calculation. Second, they earn a higher
demand defrost credit than they would have earned previously. As a
worst case (e.g., unit's demand defrost controls actuate at 11.999
hours while the unit's maximum duration is 12 hours or more), the
approximated demand defrost credit is now 1.017 compared to the
``true'' value of 1.000. 75 FR 31223, 31236-37 (June 2, 2010). The HSPF
is directly proportional to the demand defrost credit factor (see
Equation 4.2-1 of Appendix M), hence, this would represent a 1.7
percent increase in HSPF. Ingersoll Rand did not provide any
justification for why it did not agree with DOE's analysis regarding
the impact of the change. Therefore, DOE adopts this revision in the
test procedure.
18. Improving Test Consistency Associated With Indoor Unit Air Inlet
Geometry
Ingersoll Rand commented that the range of inlet geometries allowed
by the DOE test procedure for ducted units may lead to different test
results, specifically different measurements of static pressure and
(for blower coil and single-package units) fan input power, depending
on what specific inlet geometry is selected for conducting a test. They
recommended that DOE adopt the short duct minimal requirement described
in the draft version of AHRI 210/240-2015. (Ingersoll Rand, No. 65 at
p. 6-10)
DOE first reviewed the inlet configurations that Ingersoll Rand
evaluated and claimed are all compliant with the DOE inlet equipment
connection requirements. DOE does not agree that the current test
procedure allows Configuration #7, in which the inlet plenum for
measurement of inlet static pressure is upstream of the damper box.
Section 2.5.1.1 of the current test procedure states, ``install the
inlet damper box upstream of the inlet plenum.'' This was proposed to
be modified in the November 2015 SNOPR to read, ``Install the airflow
prevention device upstream of the inlet plenum . . .''. Configuration
#7 is inconsistent with both descriptions. DOE notes that the greatest
deviation in static pressure measurements presented by Ingersoll Rand
is associated with Configuration #1, in which there is neither an inlet
plenum nor a damper box, and the inlet static pressure simply measures
room pressure. In this case, the measured inlet static pressure would
generally be higher than measured using an inlet plenum, because part
of the static pressure within the room is converted to inlet velocity
pressure as the room air is accelerated towards the unit's inlet. DOE
agrees that for consistency it would be beneficial to avoid
Configuration #1 in testing. Hence, the final rule established in
today's notice does not allow use of this arrangement. DOE believes
that most units will be tested with damper boxes (or other airflow
prevention devices) in order to conduct the cyclic test, because of the
measured performance improvement associated with use of the measured
cyclic degradation coefficient, which is often less than the default
coefficient that can be used if the cyclic test is not conducted.
Hence, DOE does not believe that many, if any, tests are conducted
using Configuration #1. Thus, adopting this change should ensure test
consistency with inconsequential impact on test burden.
Responding to potential misinterpretation of the requirements for
air inlet geometry (e.g. regarding Configuration #7 discussed above),
DOE made some clarifying revisions in this final rule that were not
part of the proposals in the NOPR or SNOPRs. The revisions include, (a)
rearranging the text of section 2.4.2 regarding the inlet plenum for
the indoor unit, (b) clarifying that figures 7b and 7c of ANSI/ASHRAE
37-2009 are for blower coil indoor units or single-package units while
figure 8 is for coil-only units, and (c) clarifying that when an inlet
plenum is not used that the length of straight duct upstream of the
unit's inlet within the airflow prevention device must still adhere to
the inlet plenum length requirements, as illustrated in ANSI/ASHRAE 37-
2009, figures 7b, 7c, and 8.
F. Clarification of Test Procedure Provisions
This section discusses clarifications to the test procedure to
address test procedure provisions that may lack sufficient specificity
to ensure reproducibility. None of the clarifications listed in this
section would alter the average measured energy consumption of a
representative set of models.
1. Manufacturer Consultation
In the November 2015 SNOPR, DOE proposed to clarify the test
procedure provisions regarding the specifications for refrigerant
charging prior to testing, with input on certain details from the AHRI
210/240-Draft, as discussed in section III.E.15. Specifically, DOE
proposed to remove the current test procedure's allowance for
contacting the manufacturer to receive charging instructions. In
instances where multiple sets of instructions are specified or are
included with the unit and the instructions are unclear on which set to
test with, DOE proposed the use of field installation criteria. 80 FR
69278, 69313 (Nov. 9, 2015).
ADP and Lennox commented that before using standard sub-cooling and
superheat values, the test facility should contact the manufacturer to
obtain instructions in cases where they have been misplaced, and in all
cases the test facility should contact the manufacturer to request the
latest version of the installation instructions. ADP and Lennox
commented that given the level of inventory in the industry, testing an
off-the-shelf unit solely based on the installation instructions in the
box with the unit could result in outdated instructions being used.
(ADP, No. 59 at p. 10; Lennox, No. 61 at p. 17-18)
After reviewing these comments, DOE maintains that it is not
necessary to contact the manufacturer for the latest refrigerant
charging requirements, and that the instructions provided with the unit
should be used as the unit should have been certified by the
manufacturer as compliant with the information provided with the unit.
Therefore, DOE has adopted this provision in the final rule.
In the November 2015 SNOPR, DOE also proposed to revise language
proposed in previous NOPRs regarding the metering of low-voltage
transformers to eliminate the need for communication between third
party test laboratories and manufacturers. 80 FR 69278, 69313 (Nov. 9,
2015). No comments were received on this proposal, and DOE adopts this
provision in the final rule.
[[Page 37038]]
DOE also proposed to require manufacturers to report on their
certification report whether the test was conducted with or without an
inlet plenum installed in order to eliminate the need for the test
laboratory to confirm this with the manufacturer. 80 FR 69278, 69313
(Nov. 9, 2015).
In response, AHRI, Nortek commented that it is burdensome and
unnecessary to submit this data. (AHRI, No. 70 at p. 14; Nortek, No. 58
at p. 11) ADP, Unico, and Ingersoll Rand commented that they agreed
with AHRI on this matter. (ADP, No. 59 at p. 7; Unico, No. 63 at p. 6;
Ingersoll Rand, No. 65 at p. 12) JCI, UTC/Carrier, Lennox, and
Mitsubishi commented generally that additional reporting requirements
impose an unnecessary burden on manufacturers, which is discussed in
section III.A.5. (JCI, No. 66 at p. 12; UTC/Carrier, No. 62 at p. 7;
Lennox, No. 61 at pp. 14-15; Mitsubishi, No. 68 at pp. 1-2)
As discussed in section III.E.18, DOE has modified the test
procedure to require the use of an inlet plenum or an inlet airflow
prevention device that also provides the function of an inlet plenum,
for ducted split-system or single-package units. Hence, this reporting
requirement is not needed and DOE has removed it in the final rule.
DOE proposed to amend references in the test procedure to test
setup instructions or manufacturer specifications by specifying that
these refer to the test setup instructions included with the unit. DOE
proposed to implement this change in the following sections: 2.2.2,
3.1.4.2(c), 3.1.4.4.2(c), 3.1.4.5(d), and 3.5.1(b)(3). 80 FR 69278,
69313 (Nov. 9, 2015). No comments were received on this proposal, and
DOE adopts this provision in the final rule.
2. Incorporation by Reference of AHRI 1230-2010
ANSI/AHRI Standard 1230-2010 ``Performance Rating of Variable
Refrigerant Flow (VFR) Multi-Split Air-Conditioning and Heat Pump
Equipment'' with Addendum 2 (AHRI 1230-2010) prescribes test
requirements for both consumer and commercial variable refrigerant flow
multi-split systems. In the November 2015 SNOPR, DOE proposed to
incorporate by reference the sections of AHRI 1230-2010 that are
relevant to consumer variable refrigerant flow multi-split systems
(namely, sections 3 (except 3.8, 3.9, 3.13, 3.14, 3.15, 3.16, 3.23,
3.24, 3.26, 3.27, 3.28, 3.29, 3.30, and 3.31), 5.1.3, 5.1.4, 6.1.5
(except Table 8), 6.1.6, and 6.2) into the existing test procedure for
central air conditioners and heat pumps at Appendix M to Subpart B of
10 CFR part 430. 80 FR 69278, 69313 (Nov. 9, 2015).
In response to this proposal, JCI, AHRI, Nortek, Unico, Mitsubishi
and Rheem supported applying AHRI 1230 for VRF testing. (JCI, No. 66 at
p. 20; AHRI, No. 70 at p. 17; Nortek, No. 58 at p. 14; Unico, No. 63 at
p. 12; Mitsubishi, No. 68 at p. 4; Rheem, No. 69 at p. 15) In contrast,
Goodman commented that all products in the residential market should be
tested using the same test procedure, and suggested multi-split air
conditioners should be tested via AHRI 210/240. (Goodman, No. 73 at p.
15-16) As virtually all commenters support the use of the industry test
procedure AHRI 1230 for multi-split air conditioners, DOE incorporates
by reference certain sections of AHRI 1230-2010 as proposed.
DOE also proposed to define the terms ``Multiple-split (or multi-
split) system'', ``Small-duct, high-velocity system'', ``Tested
combination'', ``Variable refrigerant flow system'' and ``Variable-
speed compressor system'' in its list of definitions in Appendix M to
Subpart B of 10 CFR part 430. 80 FR 69278, 69313 (Nov. 9, 2015).
Regarding tested combination, AHRI had requested in response to the
June 2010 NOPR that DOE use the ``tested combination'' definition in
AHRI 1230-2010 (the definition appears in section 3.26 of this
standard). (AHRI, No. 6 at pp. 1-2) In the November 2015 SNOPR, DOE
proposed a definition which is nearly identical to the AHRI 1230-2010
definition, except that (a) the AHRI definition allows a maximum of 12
indoor units in the tested combination--the DOE proposal calls for up
to five indoor units, (b) the DOE proposal allows use of an indoor unit
model family other than the highest sales volume family if the 95
percent capacity threshold cannot be met with units of the highest
sales volume family, and (c) DOE's proposal provided clarification of
what is meant by indoor unit nominal capacity. 80 FR at 69313-14 (Nov.
9, 2015). Commenters did not specifically address these provisions in
their comments regarding the November 2015 SNOPR, and hence the final
rule adopts them.
In addition, both AHRI and Mitsubishi had commented in response to
the June 2010 NOPR that DOE should remove the requirement to turn off
one of the indoor units when testing at minimum compressor speed.
(AHRI, No. 6 at p. 2, Mitsubishi, No. 12 at p. 1) DOE established this
test requirement for multi-split systems in a final rule published
October 22, 2007. 72 FR 59906-59909. DOE had initially considered a
more aggressive approach in the October 2007 Final Rule for turning off
indoor units at part load in which the number of operating units would
be proportional to the load level, but settled instead on turning off
just one unit for minimum compressor speed. Id. at 59909. Multi-split
systems have indoor units that respond individually to separate
thermostats. The outdoor units are designed to operate when one or more
of the indoor units are not operating. It certainly would be expected
that, for a large percentage of the time that such a unit operates at
minimum compressor speed, at least one of the indoor units would have
cycled off. The test approach suggested by AHRI and Mitsubishi is more
consistent with the operation of multi-head mini-split systems, for
which all of the indoor units operate in unison in response to a single
thermostat, rather than the operation of multi-split systems--for such
systems, all indoor units would always be operating when the outdoor
unit is at minimum compressor speed. DOE is not aware of any field test
information that shows that all of the indoor units of a multi-split
system continue to operate when the compressor is at minimum speed.
Hence, DOE is maintaining the requirement to turn off one indoor unit
for the minimum-speed tests.
Finally, Mitsubishi had also commented, in response to the June
2010 NOPR, that the 50% requirement be waived for multi-split systems
with cooling capacity less than 24,000 Btu/h, and that the 95% to 105%
capacity requirement for match between indoor and outdoor nominal
capacities be considered a guideline rather than a requirement. (AHRI,
No. 6 at p. 2, Mitsubishi, No. 12 at pp. 1-2) The 50% requirement (i.e.
that none of the indoor units of the tested combination have a nominal
cooling capacity greater than 50% of the outdoor unit's nominal cooling
capacity) has been adopted by DOE. DOE will not adopt the latter
recommendation, since it would essentially eliminate any requirement
for capacity matching, but has instead increased the flexibility of the
requirements by allowing use of model families of indoor units other
than the highest sales volume model family, if all of the tested
combination requirements cannot be met by the highest sales volume
family.\18\ DOE notes that it has clarified this allowance in this
final
[[Page 37039]]
rule--whereas the proposed wording referenced inability to meet the 95%
capacity threshold as the basis for considering other model families,
the allowance in this final rule explicitly states that if all the
requirements for ``tested combination'' cannot be met by indoor units
selected from the highest sales volume model family, that one or more
indoor units could be selected from a different sales model family.
---------------------------------------------------------------------------
\18\ Examples of model families include configurations such as
mid-range static ducted, high-static ducted, wall-mount, ceiling-
mount 4-way cassette, ceiling-mount 2-way cassette, etc.
---------------------------------------------------------------------------
Comments received regarding the term ``multiple-split system'' are
discussed in section III.F.5. DOE did not receive comments on the other
definitions and adopts them as proposed.
In the November 2015 SNOPR, DOE also proposed to omit Table 8 of
AHRI 1230-2010 from the IBR into Appendix M and to set minimum ESP
requirements for systems with short-run ducted indoor units in Table 3
of Appendix M as follows: 0.03 in. w.c. for units less than 28,800 Btu/
h; 0.05 in. w.c. for units between 29,000 Btu/h and 42,500 Btu/h; and
0.07 in. w.c. for units greater than 43,000 Btu/h. Furthermore, DOE
proposed to define the term ``short duct systems,'' to refer to ducted
systems whose indoor units can deliver no more than 0.07 in. w.c. ESP
when delivering the full load air volume rate for cooling operation. 80
FR 69278, 69314 (Nov. 9, 2015).
DOE received several comments in response to its proposal related
to short duct systems and the required ESP. However, the CAC/HP ECS
Working Group included recommendations to DOE regarding definitions and
ESP for low-static and mid-static units rather than short duct systems.
(Docket No. EERE-2014-BT-STD-0048, No. 76 at p. 1-2) Therefore, in this
final rule, DOE is not adopting a definition or ESP requirement for
short duct systems and will consider changes to the ESP for certain
kinds of systems in a separate notice.
3. Replacement of the Informative Guidance Table for Using the Federal
Test Procedure
In the November 2015 SNOPR, DOE proposed replacing the set of four
tables at the beginning of ``Section 2, Testing Conditions'' of the
current test procedure (10 CFR part 430, subpart B, Appendix M) with a
more concise table to provide guidance to manufacturers regarding
testing conditions, testing procedures, and calculations appropriate to
a product class, system configuration, modulating capability, and
special features of products. 80 FR 69278, 69314 (Nov. 9, 2015).
JCI commented the tables provide adequate clarity but that the
table would be more viewable if placed in a portrait view. (JCI, No. 66
at p, 20-21). UTC/Carrier responded that they would like any clarity
DOE can provide. (UTC/Carrier, No. 62 at p. 19) Rheem expressed the
preference of the current table over the proposed table in the November
2015 SNOPR and suggested that DOE further clarify the proposed table,
including adding a title and explanation of how it should be used.
Rheem also pointed out a possible error under testing conditions for
single-split-system coil-only. (Rheem, No. 69 at p.16).
Given the general consensus on the proposed table, DOE is adopting
the format of the proposed table in this final rule with some
clarification. DOE found it difficult to fit the eight columns within
the table in the portrait view suggested by JCI, and maintains the
landscape format. In response to Rheem, the proposed table is titled
``Informative Guidance for Using Appendix M'' and an explanation of how
it should be used is given in section 2 (B) of this final rule notice.
DOE conducted further review and revision to the proposed table to
clarify the sections each test should refer to, including fixing the
identified error on single-split-system coil-only test conditions.
4. Clarifying the Definition of a Mini-Split System
In the November 2015 SNOPR, DOE proposed deleting the definition of
mini-split air conditioners and heat pumps, and adding two definitions
for: (1) single-zone-multiple-coil split system, representing a split
system that has one outdoor unit and that has two or more coil-only or
blower coil indoor units connected with a single refrigeration circuit,
where the indoor units operate in unison in response to a single indoor
thermostat; and (2) single-split system, representing a split system
that has one outdoor unit and that has one coil-only or blower coil
indoor unit connected to its other component(s) with a single
refrigeration circuit. 80 FR 69278, 69314 (Nov. 9, 2015).
ADP, Lennox, and UTC/Carrier supported DOE's proposal. (ADP, No. 59
at p. 12; Lennox, No. 61 at p. 19; UTC/Carrier, No. 62 at p. 20)
AHRI and Nortek proposed modifying the current definition to
reflect common terminology used in the field. (AHRI, No. 70 at p. 17-
18; Nortek, No. 58 at p. 14) AHRI and Mitsubishi recommended the
terminology and definitions be revised as follows: (1) single head
mini-split system, representing split systems that have a single
outdoor section and one indoor section, where the indoor section cycles
on and off in unison in response to a single indoor thermostat; and (2)
multi head mini-split system, representing split systems that have a
single outdoor section and more than one indoor sections, where the
indoor sections cycle on and off in unison in response to a single
indoor thermostat. (AHRI, No. 70 at p. 17-18; Mitsubishi, No. 68 at p.
4)
Goodman commented that they do not support the terminology of
``single-zone-multiple-coil split system'' and that there is no need to
separate a one-to-one split system and a one-to-multiple split system.
However, Goodman also suggested using the terms single-head mini-split
and multi-head mini-split if DOE desires to separate the definition of
mini-split into two categories. (Goodman, No. 73 at p. 7)
Mitsubishi also specifically recommended that the references to
``coil-only'' be removed since Appendix M does not permit the matching
of a variable speed outdoor unit with a coil without a blower that can
match the airflow required for each of the tests. (Mitsubishi, No. 68
at p. 4)
In response to the recommended terminology from AHRI, Nortek,
Mitsubishi, and Goodman, DOE is adopting the term ``multi-head mini-
split system'' in the regulatory text rather than the proposed
``single-zone multiple-coil system.'' However, DOE believes it is
important to specify that this system has a single refrigerant circuit,
which is not part of the definition proposed by AHRI and Mitsubishi. In
response to Mitsubishi, DOE has removed ``coil-only'' from the
definition but cautions that this does not mean that the definition
does not include systems with coil-only indoor units. DOE notes that
the definition is not explicitly limited to variable-speed units,
although DOE is aware that most of not all commercially available units
that fit the definition have variable-speed compressors. For these
reasons, DOE adopts the following definition for ``multi-head mini-
split system'':
Multi-head mini-split system means a split system that has one
outdoor unit and that has two or more indoor units connected with a
single refrigeration circuit. The indoor units operate in unison in
response to a single indoor thermostat.
DOE is adopting the definition for single-split system as proposed
in the SNOPR. DOE is not adopting a definition for ``single-head mini-
split,'' as this variety of unit is included in the ``single-split
system'' definition and there are no different test procedure
requirements or energy conservation standard levels that would require
[[Page 37040]]
establishing a separate definition to distinguish these products.
5. Clarifying the Definition of a Multi-Split System
In the November 2015 SNOPR, DOE proposed to clarify the definition
of multi-split system to specify that multi-split systems are to have
only one outdoor unit. (DOE notes that it proposed to separately define
multi-circuit units as units that incorporate multiple outdoor units
into the same package. This is discussed in section III.C.1.) DOE also
proposed to clarify that if a model of outdoor unit could be used both
for single-zone-multiple-coil split systems (multi-head mini-split
systems) and for multi-split systems, it should be tested as a multi-
split system. 80 FR 69278, 69315 (Nov. 9, 2015).
In response, the California IOUs stated that the proposed
definition was unclear and recommended the following definition: A
multiple zone, multiple coil, split system is a split system with one
outdoor unit and at least two coil-only or blower coil indoor units
which operate separately as required to provide comfort in the zone
each serves. (California IOUs, No. 67 at p. 6). DOE received no other
comments on this issue.
The multi-split system definition suggested by California IOUs does
not specify that the outdoor units and the indoor units are within a
single refrigerant circuit, and therefore multi-circuit systems, which
are tested differently, would fit in this definition. In order to
preserve the distinction between multi-split and multi-circuit
products, DOE adopts the proposed multi-split system definition from
the November 2015 SNOPR, which clarifies that for multi-split systems
all components are connected with a single refrigerant circuit.
6. Clarifying the Housing for Uncased Coil
The current test procedure provides instructions for installing
uncased coil indoor units, indicating that an enclosure be provided for
them using 1 in. fiberglass ductboard (see Appendix M, section 2.2.c).
DOE is aware of issues associated with the use of fiberglass ductboard,
as its lack of rigidity can present challenges in maintaining tight
seals where it connects to upstream and downstream ducts used in the
test set-up. DOE also notes that the requirements of section 2.2.c
regarding both the ductboard and its installation are unnecessarily
limited in the approaches listed for fabricating an enclosure for the
test. DOE is aware that test laboratories fabricate enclosures for
testing uncased coils that consist of materials other than just the
listed fiberboard or alternative insulation. DOE also understands that
the term ``fiberboard'' is not sufficiently descriptive to assure that
a foil-faced fiberboard be used, which would be consistent with the
expectation that such a casing provide a barrier to both air flow and
water vapor transmission. As a result, DOE is clarifying these
instructions with additional language in this final rule regarding the
installation of uncased coils, including (a) indicating that the
ductboard must be foil-faced, (b) allowing alternative housings,
consisting of sheet metal or similar material and separate insulation,
and (c) indicating that sizing and installation of the casing should be
done as described in the installation instructions shipped with the
unit. These clarifications are consistent with DOE's proposal in the
November 2015 SNOPR and its understanding and expectations of how these
tests are being conducted and should be conducted. Although most
ductboard material is foil-faced, DOE has clarified that alternative
materials claimed to be ductboard should not be used--without the foil
facing, the ductboard would not present a sufficient barrier to vapor
and air penetration. These alternative housing materials (i.e.
alternatives to foil-faced fiberboard) will allow for more rigid
construction of the coil housing. Finally, DOE recognizes that details
regarding the fabrication and installation of the housing may affect
test results and hence clarifies that they should be performed as
described in installation instructions shipped with the unit. These
changes would not affect any tests being conducted consistent with
existing requirements (e.g. for negligible air leakage and installation
according to shipped instructions.) but are intended to clarify set-up
procedures to enhance consistency of testing.
7. Test Procedure Reprint
DOE has reprinted the entirety of Appendix M to 10 CFR part 430
Subpart B in the regulatory text for this final rule to improve clarity
regarding the revisions established by this final rule. Table III.6
lists proposals from the previous notices that appear in this
regulatory text reprint, and provides reference to the respective
revised section(s) in the regulatory text.
Table III.6.--Test Procedure Amendments Adopted in This Final Rule
[By original proposal]
----------------------------------------------------------------------------------------------------------------
Regulatory text
Section Proposal to . . . Reference Preamble discussion location *
----------------------------------------------------------------------------------------------------------------
June 2010 NOPR
----------------------------------------------------------------------------------------------------------------
A.7.......................... Add Calculations for 75 FR 31229 III.G.1 3.3c, 4.5.
Sensible Heat Ratio.
A.9.......................... Modify Definition of 75 FR 31230 III.F.2 10 CFR 430.2
Tested Combination. Definitions.
A.10......................... Add Definitions Terms 75 FR 31231 None Definitions.
Regarding Standby
Power.
B.1.......................... Modify the Definition 75 FR 31231 III.F.2 10 CFR 430.2
of ``Tested Definitions.
Combination''.
B.3.......................... Clarify That Optional 75 FR 31233 III.E.11 3.2.1, 3.2.2.1,
Tests May Be 3.2.3
Conducted Without
Forfeiting Use of
the Default Value(s).
B.4.......................... Allow a Wider 75 FR 31233 III.E.1 3.1.4.1.1a.4(ii)
Tolerance on Air
Volume Rate To Yield
More Repeatable
Laboratory Setups.
B.5.......................... Change the Magnitude 75 FR 31234 III.E.17 3.3d Table, 3.5h
of the Test Table, 3.7a
Operating Tolerance Table, 3.8.1
Specified for the Table, 3.9f
External Resistance Table.
to Airflow.
Change the Magnitude 75 FR 31234 III.E.17 3.3d Table, 3.5h
of the Test Table, 3.7a
Operating Tolerance Table, 3.8.1
Specified for the Table.
Nozzle Pressure Drop.
B.6.......................... Modify Refrigerant 75 FR 31234 III.E.7 2.2.5.
Charging Procedures:
Disallow Charge
Manipulation after
the Initial Charge.
B.7.......................... Require All Tests be 75 FR 31235, 31250 III.F.1 2.2.5.8.
Performed with the
Same Refrigerant
Charge Amount.
When Determining the 75 FR 31235 III.E.11 3.4c, 3.5i,
Cyclic Degradation 3.7e, 3.8
Coefficient CD,
Correct the Indoor-
Side Temperature
Sensors Used During
the Cyclic Test To
Align With the
Temperature Sensors
Used During the
Companion Steady-
State Test, If
Applicable: Equation.
[[Page 37041]]
B.8.......................... When Determining the 75 FR 31236 None 3.3b, 3.7a,
Cyclic Degradation 3.9e, 3.11.1.1,
Coefficient CD, 3.11.1.3,
Correct the Indoor- 3.11.2a.
Side Temperature
Sensors Used During
the Cyclic Test To
Align With the
Temperature Sensors
Used During the
Companion Steady-
State Test, If
Applicable: Sampling
Rate.
B.9.......................... Clarify Inputs for 75 FR 31236 III.E.17 3.9.2a.
the Demand Defrost
Credit Equation.
B.10......................... Add Calculations for 75 FR 31237 III.G.1 3.3c, 4.5.
Sensible Heat Ratio.
B.11......................... Incorporate Changes 75 FR 31237 III.C.3 2.2.3, 2.2.3b,
To Cover Testing and 2.4.1b,
Rating of Ducted 3.1.4.1.1d,
Systems Having More 3.1.4.2e,
Than One Indoor 3.1.4.4.2d,
Blower. 3.1.4.5.2f,
3.2.2, 3.2.2.1,
3.6.2, 3.2.6,
3.6.7, 4.1.5,
4.1.5.1,
4.1.5.2, 4.2.7,
4.2.7.1,
4.2.7.2,
3.2.2.2 Table,
3.6.2 Table.
B.12......................... Add Changes To Cover 75 FR 31238 III.C.4 3.6.6, 4.2.6.
Triple-Capacity,
Northern Heat Pumps.
B.13......................... Specify Requirements 75 FR 31238 III.F.1 2.2d.
for the Low-Voltage
Transformer Used
When Testing for Off-
Mode Power
Consumption.
B.14......................... Add Testing 75 FR 31238 III.D Definitions,
Procedures and 3.13, 4.3.
Calculations for Off
Mode Power
Consumption.
B.17......................... Update Test Procedure 75 FR 31243 III.E.12 10 CFR 430.3
References. Definitions.
----------------------------------------------------------------------------------------------------------------
April 2011 SNOPR
----------------------------------------------------------------------------------------------------------------
III.A........................ Revise Test Methods 76 FR 18107 III.D Definitions,
and Calculations for 3.13, 4.3.
Off-Mode Power and
Energy Consumption.
III.B........................ Revise Requirements 76 FR 18109 III.F.1 2.2d.
for Selecting the
Low-Voltage
Transformer Used
During Off-Mode
Test(s).
III.D........................ Add Calculation of 76 FR 18111 None 4.7.
the Energy
Efficiency Ratio for
Cooling Mode Steady-
State Tests.
III.E........................ Revise Off-Mode 75 FR 31238 III.D Definitions,
Performance Ratings. 3.13, 4.3.
----------------------------------------------------------------------------------------------------------------
October 2011 SNOPR
----------------------------------------------------------------------------------------------------------------
III.A........................ Reduce Testing Burden 76 FR 65618 III.D Definitions,
and Complexity. 3.13, 4.3.
III.C........................ Add Definition for 76 FR 65620 III.D Definitions.
Shoulder Season.
III.D........................ Revise Test Methods 76 FR 65620 III.D Definitions,
and Calculations for 3.13, 4.3.
Off-Mode Power and
Energy Consumption.
III.D.1...................... Add Provisions for 76 FR 65621 III.D Definitions,
Large Tonnage 3.13, 4.3.
Systems.
III.D.2...................... Add Requirements for 76 FR 65622 III.D Definitions,
Multi-Compressor 3.13.
Systems.
----------------------------------------------------------------------------------------------------------------
November 2015 SNOPR
----------------------------------------------------------------------------------------------------------------
III.A.1...................... Basic Model 80 FR 69282 III.A.1 430.2.
Definition.
III.A.2...................... Additional 80 FR 69284 III.A.2 430.2.
Definitions.
III.A.3...................... Determination of 80 FR 69285 III.A.3 429.16, 1.2.
Certified Rating.
III.A.4...................... Compliance with 80 FR 69289 III.A.4 429.16(a).
Federal (National or
Regional) Standards.
III.A.5...................... Certification Reports 80 FR 69290 III.A.5 429.16(c).
III.A.6...................... Represented Values... 80 FR 69291 III.A.6 429.16(a),
430.23.
III.A.7...................... Product-Specific 80 FR 69292 III.A.7 429.134.
Enforcement
Provisions.
III.B.1...................... AEDM General 80 FR 69292 III.B.1 429.70(e).
Background.
III.B.2...................... AED< Terminology..... 80 FR 69292 III.B.2 429.70(e).
III.B.3...................... Elimination of the 80 FR 69293 III.B.3 ................
ARM Pre-Approval
Requirement.
III.B.4...................... AEDM Validation...... 80 FR 69294 III.B.4 429.70(e)(2).
III.B.5...................... AEDM Requirements for 80 FR 69296 III.B.5 429.16.
Independent Coil
Manufacturers.
III.B.6...................... AEDM Verification 80 FR 69296 III.B.6 429.104,
Testing. 429.70(e)(5).
III.B.7...................... Failure to Meet 80 FR 69297 III.B.7 429.70(e)(5)(iv)
Certified Ratings. .
III.B.8...................... Action Following a 80 FR 69297 III.B.8 429.110, 429.70.
Determination of
Noncompliance.
III.C.2...................... Termination of 80 FR 69299 III.C.2 429.16(a)(1)(ii)
Waivers Pertaining (A), 2.4.1b.
to Multi-Circuit
Products.
III.C.3...................... Termination of Waiver 80 FR 69299 III.C.3 3.1.4.1.1.d,
and Clarification of 3.1.4.2.e.
the Test Procedure
Pertaining to Multi-
Blower Products.
III.D.1...................... Off-Mode Test 80 FR 69300 III.D.1 3.13.2.b.
Temperatures.
III.D.2...................... Off-Mode Calculation 80 FR 69301 III.D.2 3.13.1, 4.3.
and Weighting of P1
and P2.
III.D.3...................... Off-Mode: Products 80 FR 69302 III.D.2 3.13.1.e,
with Large, Multiple 3.13.2.g.
or Modulated
Compressors.
III.D.4...................... Off-Mode: Procedure 80 FR 69302 III.D.7 3.13.1.c,
for Measuring Low- 3.13.1.d,
Voltage Component 3.13.2.c,
Power. 3.13.2.e,
3.13.2.f.
III.D.5...................... Off-Mode: Revision of 80 FR 69302 III.D.7 3.13.1.e,
Off-Mode Power 3.13.1.f,
Consumption 3.13.2.g,
Equations. 3.13.2.h.
III.D.6...................... Off-Mode Power 80 FR 69303 III.D.7 3.13.1, 3.13.2.
Consumption for
Split Systems.
III.D.8...................... Test Metric for Off- 80 FR 69304 III.D.3 429.16(a).
Mode Power
Consumption.
III.E.1...................... Indoor Fan Speed 80 FR 69305 III.E.1 Table 2,
Settings. 2.3.1.a,
3.1.4.1.1,
3.3(d).
III.E.2...................... Requirements for the 80 FR 69306 III.E.3 2.2(a), 2.10.3.
Refrigerant Lines
and Mass Flow Meter.
III.E.3...................... Outdoor Room 80 FR 69306 III.E.4 2.5, 2.11.b,
Temperature 3.1.8.
Variation.
III.E.4...................... Method of Measuring 80 FR 69307 III.E.5 2.11.b.
Inlet Air
Temperature on the
Outdoor Side.
III.E.5...................... Requirements for the 80 FR 69307 III.E.6 2.5, 2.11.
Air Sampling Device.
III.E.6...................... Variation in Maximum 80 FR 69307 III.E.7 3.2.4, 3.6.4,
Compressor Speed 4.1.4, 4.2.4.
with Outdoor
Temperature.
III.E.7...................... Refrigerant Charging 80 FR 69307 III.E.8 2.2.5.8.
Requirements.
III.E.8...................... Alternative 80 FR 69308 III.E.9 2.5(c).
Arrangement for
Thermal Loss
Prevention for
Cyclic Tests.
III.E.9...................... Test Unit Voltage 80 FR 69309 III.E.10 2.7.
Supply.
III.E.10..................... Coefficient of Cyclic 80 FR 69309 III.E.11 3.2.1, 3.2.2,
Degradation. 3.2.3, 3.2.4,
3.5, 3.6, 3.8.
[[Page 37042]]
III.E.11..................... Break-in Periods 80 FR 69309 III.E.12 3.1.7.
Prior to Testing.
III.E.12..................... Industry Standards 80 FR 69310 III.E.13 430.3.
that are
Incorporated by
Reference.
III.E.13..................... Withdrawing 80 FR 69311 III.E.14 ................
References to ASHRAE
116-1995 (RA 2005).
III.E.14..................... Additional Changes 80 FR 69311 III.E.15 Table 2,
Based on AHRI 210/ 2.2.5.4.a,
240-Draft. 2.2.5.5,
2.3.1.a, 2.4.2,
2.5, 2.11,
3.1.3.1,
3.1.4.1.1,
3.1.5, 3.3(d).
III.E.15..................... Damping Pressure 80 FR 69312 III.E.16 2.6(a).
Transducer Signals.
III.F.1...................... Manufacturer 80 FR 69313 III.F.1 2.2.5, 2.4.2,
Consultation. 2.2.2,
3.1.4.2(c),
3.1.4.4.2(c),
3.1.4.5(d),
3.5.1(b)(3).
III.F.2...................... Incorporation by 80 FR 69313 III.F.2 1, 3.12, 2.2.a,
Reference of AHRI 2.2.b, 2.2.c,
1230-2010. 2.2.1, 2.2.2,
2.2.3(a),
2.2.3(c),
2.2.4, 2.2.5,
2.4-2.12, Table
3, section 3.1
(except
sections 3.1.3,
3.1.4), 3.3,
3.4, 3.5, 3.7-
3.10, 3.13, 4.
III.F.3...................... Replacement of the 80 FR 69314 III.F.3 Table 1.
Informative Guidance
Table for Using the
Federal Test
Procedure.
III.F.4...................... Clarifying the 80 FR 69314 III.F.4 1.2.
Definition of a Mini-
Split System.
III.F.5...................... Clarifying the 80 FR 69315 III.F.5 1.2.
Definition of a
Multi-Split System.
----------------------------------------------------------------------------------------------------------------
* Section numbers in this column refer to the Appendix M test procedure finalized in this notice.
G. Additional Comments From Interested Parties
This section discusses additional comments made by interested
parties during this rulemaking that were unrelated to any of DOE's
proposals.
1. Wet Coil Performance
NREL requested DOE require reporting of latent load or amount of
water condensation removal at each test condition to be able to compare
equipment performance between dry and humid regions. NREL also
recommend adding two new cooling-mode test conditions to provide better
representation of performance in hot dry regions and three new test
cooling-mode conditions for hot humid regions. (NREL, No. 14 at p. 1)
In the June 2010 NOPR DOE proposed to add a calculation of the
sensible heat ratio (SHR) to its test procedure to provide consumers
and their contractors with more information to allow them to make more
informed decisions regarding product selections. 75 FR 31223, 31237
(June 2, 2010). In response, UTC/Carrier and JCI noted in its comments
that SHR is currently provided in manufacturer's product data. (UTC/
Carrier, No. 62 at p. 7; JCI, No. 66 at p. 12). In this final rule, DOE
agrees that SHR was intended to be provided in manufacturer literature
and has not adopted the November 2015 SNOPR proposal to require SHR be
reported to DOE (see Section III.A.5) The latent load and water
condensate rate can be calculated based on the SHR in manufacturers'
product literature and the rated cooling capacity, which should provide
sufficient representation of wet coil performance.
The DOE test procedure requires units to be tested at 80 [deg]F dry
bulb temperature and 67 [deg]F wet bulb temperature during wet-coil
cooling test to represent typical indoor conditions. DOE does not
disagree that the additional test points proposed by NREL would provide
additional representation of performance in hot dry and hot humid
regions. However, requiring those additional tests would impose
significant test burden on manufacturers. Currently, for a single-
capacity air-conditioner, a manufacturer must conduct four tests and
generally conducts in addition the dry and cyclic tests. Adding five
tests would roughly double the test time for these units. It is not
clear how the five additional tests recommended by NREL would improve
the accuracy or field-representativeness of the measurements of SEER or
EER. Hence, DOE has determined not to include these test points in the
test procedure.
2. Barometric Pressure Correction
AHRI and JCI proposed that DOE implement a barometric pressure
correction specification for testing. They suggested that barometric
pressure be corrected to the altitude where the mean of the U.S.
population lives. (AHRI, No. 70 at p. 13; JCI, No. 66 at p. 11) JCI
suggested addressing barometric pressure by maintaining the enthalpy or
humidity ratio of the entering air, indicating that this has been used
effectively for lab correlation. (JCI, No. 66 at p. 11)
DOE has noted the industry's concern regarding the impact of
barometric pressure on the repeatability of tests and represented
values. Currently, there is no systematic data to demonstrate the
effect of barometric pressure on unit performance. However, JCI did not
describe in sufficient detail how the correlation it proposed would
work, nor provide data showing that it properly addresses the
barometric pressure issue.
DOE also notes that there has not been a study leading to selection
of a standard altitude or pressure level. DOE is not adopting a
barometric pressure correction in this final rule because an approach
for addressing it has not been described in sufficient detail nor shown
to provide the correct adjustment for pressure changes.
3. Inlet Screen
DOE proposed in the November 2015 SNOPR the use of a screen
downstream of the air mixer in the outlet of the indoor unit if
necessary to improve temperature uniformity. 80 FR at 69278, 69353
(Nov. 9, 2015). Ingersoll Rand commented that inlet and outlet screens
on the indoor unit air stream will impose pressure drop, potentially
requiring an increase in the code tester fan motor size. The code
tester is the airflow measuring apparatus as discussed in section 2.6
of Appendix M. They also recommended that regardless of whether the
cyclic test is carried out, the measured performance should be
equivalent to the no damper test setup. (Ingersoll Rand, No. 65 at p.
5-6) DOE notes that the proposal included no requirement for an inlet
screen, and that the screen in the outlet is an option to help meet the
temperature uniformity requirements, but is not required if other means
are sufficient to attain uniformity. Further, requirement for
temperature uniformity for the outlet temperature measurement applies
whether or not an outlet damper box is used, i.e., to conduct a cyclic
test. DOE has made no changes in response to the Ingersoll Rand
comment.
[[Page 37043]]
H. Compliance With Other Energy Policy and Conservation Act
Requirements
This section discusses and responds to comments related to
compliance with Energy Policy and Conservation Act Requirements.
1. Dates
HARDI commented that given the challenging and complex nature of
the test procedure, the comment period should have been extended by 30
days. HARDI believes that restricting the comment period to 30 days has
a negative impact to smaller companies as they may not have the means
to fully assess the true impact of such a proposal in a narrow time
frame. (HARDI, No. 57 at p. 1) JCI requested that the comment period
remain open an additional 60 days to finalize their analysis of the
proposed test procedure and any resulting clarifying comments. Goodman
commented that the Department has not complied with federal law because
it has failed to provide a 60-day comment period on this proposed test
procedure per 42 U.S.C. 6293(b)(2). (Goodman, No. 73 at p. 22)
DOE notes that it received a request from AHRI to extend the
comment period while the comment period was still open. (AHRI, No. 54,
attachment 1). DOE considered the request from AHRI, but declined to do
so. The November 2015 SNOPR represented the third round of comment on
the CAC test procedure rulemaking. DOE is limited by a statutory cap on
the number of days on which it can request public comment, and after
three rounds of rulemaking, DOE is closer to that cap. Consequently,
DOE declined the request and did not extend the comment period for the
CAC/HP TP SNOPR. (AHRI, No. 54, Attachment 2)
JCI commented that the raw scope of changes proposed within the
SNOPR coupled with the CAC/HP ECS Working Group and other DOE
rulemaking activities is such that a complete and thorough review,
understanding of the proposed changes, and resulting required
laboratory changes, coupled with potential rerating and off mode
standby test requirements make complying with the new test procedure
within 180 days of being final particularly challenging if not
impossible, and that the nature of many of the proposed changes to the
test procedure require some level of capital investment and software
programming. JCI formally requested that an additional 180 days were
required to fully and completely implement all of the proposed changes
in the SNOPR in addition to the standard 180 days as currently
prescribed. (JCI, No. 66 at p. 2-3)
First Co. commented that the 180 day effective date for AEDM
compliance proposed by DOE is unrealistic and suggested an effective
date of 18 months from the date the rule is finalized. (First Co., No.
56 at p. 1)
AHRI, ADP, Mortex, and Lennox commented that even with the adoption
of the recommended ``Similarity Group'' framework, ICMs anticipate that
the industry will face significant challenges to perform all the
required testing in the currently required time of 180 days after the
publication of the final rule. AHRI formally petitions the Department
to extend the time period to comply to 360 days, as is consistent with
its authority. See 42 U.S.C. 6293(c)(3). (AHRI, No. 70 at p. 7; ADP,
No. 59 at p. 4; Mortex, No. 71 at p. 6-7; Lennox, No. 61 at p. 7)
In response to JCI, DOE notes that this final rule has a reduced
scope from that of the SNOPR. In addition, DOE has made modifications
to the off mode test requirement proposals to reduce test burden, as
discussed in section III.D.10. For these reasons, DOE believes that a
180 day time period will be sufficient to implement the finalized test
procedure. In response to First Co., AHRI, ADP, Mortex, and Lennox, DOE
notes that 42 U.S.C. 6293(c)(3) allows individual manufacturers to
petition DOE for additional time to comply. DOE cannot grant this
additional time based on a blanket request from AHRI. However, as
discussed in section III.H.2, the changes adopted in this final rule do
not impact measured energy use; and as such, additional test burden is
expected to be limited.
2. Measured Energy Use
EPCA requires that if DOE determines that the amended test
procedure would alter the measured efficiency of a covered product, DOE
must amend the applicable energy conservation standard accordingly. (42
U.S.C. 6293(e)(2)) In the November 2015 SNOPR, DOE determined that all
proposed changes for Appendix M would not alter the measured efficiency
of central air conditioners and heat pumps. DOE proposed all changes
that it anticipated might alter the measured efficiency for Appendix
M1, which will be addressed in a separate notice.
AHRI, Nortek and UTC/Carrier disagreed that the proposed changes to
Appendix M will not alter the measured efficiency of a covered product.
(AHRI, No. 70 at p. 1-2; Nortek, No. 58 at p. 1; UTC/Carrier, No. 62 at
p. 23) UTC/Carrier commented that this could be due to CD
testing changing the resultant SEER or HSPF, as it has slightly
different stability requirements, or could be due to manufacturers
losing the ability to de-rate and require ratings to be at the mean of
the data/testing results. (UTC/Carrier, No. 62 at p. 23) AHRI contended
that the following proposed changes may impact efficiency: Changes to
the CD; requirement that manufacturers rate to the mean of
the cooling capacity, heating capacity, and sensible heat ratio (SHR)
and the prohibition on manufacturers' conservative ratings; requirement
that two-speed products must be tested coil-only, which has the
potential to change ratings derived previously using a blower coil or
the alternative rating method; and limit on compressor break-in period.
(AHRI, No. 70 at p. 1-2)
Rheem commented that that each of the changes that have been
proposed made a difference in the rating of a specific equipment sample
subject to verification or enforcement testing and that it is not clear
whether the certification rating will increase or decrease for each
proposed change. Rheem commented that it is not clear how the
conclusion that proposed changes do not impact standards was reached.
(Rheem, No. 69 at p. 2)
DOE notes that with the exception of compressor break-in period,
DOE has made modifications to its proposals on all the topics for which
UTC/Carrier and AHRI expressed concern over change in represented
value. In addition, DOE notes that the current test procedure does not
include a compressor break-in period, and any change in represented
value for testing a specific unit with a break-in period would only
serve to improve the value as compared to the standard. For these
reasons, DOE confirms that the changes adopted in this final rule do
not alter the measured efficiency of the covered product.
Nortek commented that if the test procedure does not change the
efficiency, then all existing ratings are still valid. (Nortek, No. 58
at p. 1) Similarly, First Co. commented that the final rule should make
clear that ICM test results remain valid until the energy efficiency
standard changes. Retesting is not required merely because the OUM
discontinues the outdoor unit tested by the ICM. (First Co., No. 56 at
p. 2) Finally, AHRI, ADP, Mortex, and Lennox asked for clarity on using
data from existing tests to satisfy testing requirements especially
considering the burden associated with outside lab testing. These
parties stated that, based on the proposed framework, ICMs and OUMs
would expect that data from
[[Page 37044]]
existing tests performed to the current test standard and meeting all
other requirements could be used to satisfy the testing requirement for
existing products. In addition, they said that ICMs and OUMs also
expect that tests will remain valid until the energy conservation
standard is changed and Appendix M1 becomes effective. (AHRI, No. 70 at
p. 7; ADP, No. 59 at p. 4; Mortex, No. 71 at p. 6-7; Lennox, No. 61 at
p. 7)
DOE acknowledges that manufacturers have large amounts of pre-
existing data that they currently use to make representations about and
certify the performance of their equipment and that regenerating all of
this data within the 180 day timeframe would be burdensome. As such,
manufacturers may continue to use such data to make representations
about the performance of models after the 180 day timeframe, provided
manufacturers are confident that the values are consistent with those
that would be generated under the adopted test procedure.
3. Test Burden
EPCA requires that any test procedures prescribed or amended shall
be reasonably designed to produce test results which measure energy
efficiency, energy use, or estimated annual operating cost of a covered
product during a representative average use cycle or period of use, and
shall not be unduly burdensome to conduct. (42 U.S.C. 6293(b)(3)) For
the reasons that follow, DOE has concluded that revising the DOE test
procedure, per the amendments in this final rule, to measure the energy
consumption of central air conditioners and heat pumps in active mode
and off mode would produce the required test results and would not
result in any undue burden.
As discussed in section IV.B of this final rule, the revised test
procedures to determine the active-mode and standby-mode energy use
would require use of the same testing equipment and facilities that
manufacturers are currently using for testing to determine CAC/HP
represented values for certifying performance to DOE. While this notice
clarifies the test procedures, and adopts into regulation the test
procedures associated with a number of test procedure waivers, most of
the amendments would not affect test time or the equipment and
facilities required to conduct testing. Possible changes in test burden
associated with the amendments of this notice apply to off mode
testing.
The amendments include additional testing to determine off mode
energy use, as required by EPCA. (42 U.S.C. 6295(gg)(2)(A)) This
additional testing may require investment in additional temperature-
controlled facilities. However, DOE's revised test procedure does not
require that every individual combination be tested for off mode,
allowing extensive use of AEDMs in order to reduce test burden.
In addition, DOE carefully considered the testing burden on
manufacturers in a modified off mode test procedure that is less
burdensome than the proposals it made in the April 2011 SNOPR and
October 2011 SNOPR and that addresses stakeholder comment regarding the
test burden of such prior proposals. DOE made further changes to reduce
test burden of the off-mode test procedure in response to comments
regarding the November 2015 SNOPR, specifically (a) allowing the test
to be conducted in a temperature-controlled room rather than a
psychrometric test facility, and (b) allowing the test to be conducted
without room temperature control for more designs than allowed by the
proposal. Further discussion regarding test burden associated with the
proposals set forth in this notice for determining off mode power
consumption can be found in section III.D.
The November 2015 SNOPR also proposed amendments calling for
testing to determine performance for ICMs. These amendments have been
revised in this final rule such that far fewer models will have to be
tested (see the discussion in section III.A.1.d).
DOE allows manufacturers to develop and apply an alternative
efficiency determination method to certify products without the need of
testing. In this notice, DOE revises and clarifies such requirements,
as detailed in section III.B, to continue to enable manufacturers who
wish to reduce testing burden to utilize this method.
As detailed in section III.C, manufacturers of certain products
covered by test procedure waivers have already been using the
alternative test procedures provided to them for certification testing.
Thus, the inclusion of those alternative test procedures into the test
procedure, as revised in this notice, does not add test burden.
DOE set forth amendments to improve test repeatability, improve the
readability and clarity of the test procedure, and utilize industry
procedures that manufacturers may be aware of in an effort to reduce
the test burden. Sections III.E, III.F, and III.G present additional
detail regarding such amendments.
DOE carefully considered the impact on testing burden and made
efforts to balance accuracy, repeatability, and test burden during the
course of the development of all of the test procedure amendments.
Therefore, DOE determined that the revisions to the central air
conditioner and heat pump test procedure will produce test results that
measure energy consumption during a period of representative use, and
that the test procedure will not be unduly burdensome to conduct.
4. Potential Incorporation of International Electrotechnical Commission
Standard 62301 and International Electrotechnical Commission Standard
62087
Under 42 U.S.C. 6295(gg)(2)(B), EPCA directs DOE to consider IEC
Standard 62301 and IEC Standard 62087 when amending test procedures for
covered products to include standby mode and off mode power
measurements.
DOE reviewed IEC Standard 62301, ``Household electrical
appliances--Measurement of standby power'' (Edition 2.0 2011-01),\19\
and determined that the procedures contained therein are not sufficient
to properly measure off mode power for the unique characteristics of
the components that contribute to off-mode power for CAC/HP products,
i.e., the crankcase heaters. Therefore, DOE determined that referencing
IEC Standard 62301 is not appropriate for the revised test procedure
that is the subject of this rulemaking.
---------------------------------------------------------------------------
\19\ IEC Standard 62301 covers measurement of power consumption
for standby mode and low power modes, as defined therein.
---------------------------------------------------------------------------
DOE reviewed IEC Standard 62087, ``Methods of measurement for the
power consumption of audio, video, and related equipment'' (Edition 3.0
2011-04), and determined that it would not be applicable to measuring
power consumption of products such as central air conditioners and heat
pumps. Therefore, DOE determined that referencing IEC Standard 62087 is
not necessary for the revised test procedure that is the subject of
this rulemaking.
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget (OMB) has determined that test
procedure rulemakings do not constitute ``significant regulatory
actions'' under section 3(f) of Executive Order 12866, Regulatory
Planning and Review, 58 FR 51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under the Executive Order by the
Office of Information and Regulatory Affairs (OIRA) in the Office of
Management and Budget.
[[Page 37045]]
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq.) requires
preparation of a final regulatory flexibility analysis (FRFA) for any
final rule, unless the agency certifies that the rule, if promulgated,
will not have a significant economic impact on a substantial number of
small entities. As required by Executive Order 13272, ``Proper
Consideration of Small Entities in Agency Rulemaking,'' 67 FR 53461
(August 16, 2002), DOE published procedures and policies on February
19, 2003, to ensure that the potential impacts of its rules on small
entities are properly considered during the DOE rulemaking process. 68
FR 7990. DOE has made its procedures and policies available on the
Office of the General Counsel's Web site: https://energy.gov/gc/office-general-counsel.
DOE reviewed today's final rule under the provisions of the
Regulatory Flexibility Act and the procedures and policies published on
February 19, 2003. This final rule prescribes clarifications to DOE's
already-existing test procedures that will be used to test compliance
with energy conservation standards for the products that are the
subject of this rulemaking. It also adds a requirement to conduct
testing to determine off mode power consumption. DOE has estimated the
impacts of the test procedure changes on small business manufacturers.
For the purpose of the regulatory flexibility analysis for this
rule, DOE adopts the Small Business Administration (SBA) definition of
a small entity within this industry as a manufacturing enterprise with
1,250 employees or fewer. DOE used the small business size standards
published by the SBA to determine whether any small entities would be
required to comply with the rule. The size standards are codified at 13
CFR part 121. The standards are listed by North American Industry
Classification System (NAICS) code and industry description and are
available at https://www.sba.gov/sites/default/files/files/Size_Standards_Table.pdf.
Central air conditioner and heat pump manufacturing is classified
under NAICS 333415, ``Air-Conditioning and Warm Air Heating Equipment
and Commercial and Industrial Refrigeration Equipment Manufacturing.''
70 FR 12395 (March 11, 2005). DOE reviewed AHRI's listing of central
air conditioner and heat pump product manufacturer members and surveyed
the industry to develop a list of domestic manufacturers. As a result
of this review, DOE identified 24 domestic small manufacturers of
central air conditioners and heat pumps.
Potential impacts of the amended test procedure on all
manufacturers, including small businesses, come from impacts associated
with the cost of proposed additional testing. In the June 2010 NOPR,
DOE estimated the incremental cost of the proposed additional tests
described in 10 CFR part 430, subpart B, Appendix M (proposed section
3.13) to be an increase of $1,000 to $1,500 per unit tested, indicating
that the largest additional cost would be associated with conducting
steady-state cooling mode tests and the dry climate tests for the SEER-
HD rating). 75 FR 31243 (June 2, 2010). DOE has eliminated tests
associated with SEER-HD from this rulemaking. DOE conservatively
estimates that off mode testing might cost $1,000 (roughly one-fifth of
the $5000 cost of active mode testing--see 75 FR 31243 (June 2, 2010)).
Assuming two off mode tests per tested model, this is an average test
cost of $2,000 per model. This estimate does not take into
consideration the possibility of the use of AEDMs for establishing off-
mode represented values, which could significantly reduce the off-mode
testing burden. It also does not take into account the changes in off-
mode testing adopted in this final rule to reduce test burden, i.e.,
specifically allowing more units to test off-mode energy use in a room
without temperature control, and clarifying that off-mode testing does
not need to be conducted in a psychrometric chamber (see section III.D
for details).
The off mode test procedure primarily measures energy use of
outdoor units. The off-mode power input represented values for CAC/HP
model combinations including indoor units manufactured by ICMs would be
equal to the off-mode represented values of other combinations using
the same outdoor units. Hence, it is expected that small-business ICM
manufacturers would use these same represented values rather than
retesting the outdoor units and thus not be affected by the off-mode
testing required by this rule. Because the incremental cost of running
the extra off mode tests is the same for all other manufacturers, DOE
believes that they would incur comparable costs for testing to certify
off mode power use for basic models as a result of this final test
procedure.
With respect to the provisions addressing AEDMs, the amendments
contained herein will not increase the testing or reporting burden of
OUMs who currently use, or are eligible to use, an AEDM to certify
their products. The amendments eliminate the ARM nomenclature and treat
these methods as AEDMs, eliminate the pre-approval requirement for
product AEDMs, revise the requirements for validation of an AEDM in a
way that would not require more testing than that required by the AEDM
provisions included in the March 7, 2011 Certification, Compliance and
Enforcement Final Rule (76 FR 12422) (``March 2011 Final Rule''), and
amend the process that DOE promulgated in the March 2011 Final Rule for
validating AEDMs and verifying certifications based on the use of
AEDMs. Because these AEDM-related amendments will either have no effect
on test burden or decrease burden related to testing and determination
of represented values of products (e.g., elimination of ARM pre-
approval), DOE has determined these amendments will result in no
significant change in testing or reporting burden.
To evaluate the potential cost impact of off-mode testing for small
OUMs, DOE estimated small manufacturers' total cost of testing. As
discussed above, DOE identified 24 domestic small business
manufacturers of CAC/HP products. Of these, only OUMs that operate
their own manufacturing facilities (i.e., are not private labelers
selling only products manufactured by other entities) and OUM importing
private labelers would be subject to the additional requirements for
testing required by this rule. DOE identified 12 such manufacturers,
but was able to estimate the number of basic models associated only
with nine of these. DOE calculated the additional testing expense for
these nine domestic small businesses. Assuming the $2,000 estimate of
additional test cost per basic model, and that testing of basic models
may not have to be updated more than once every five years, DOE
estimated that the annual cost impact of the additional testing is $400
per basic model when the cost is spread over five years.
DOE currently requires that only one combination associated with
any given outdoor unit be laboratory tested. 10 CFR 430.24(m). The
majority of central air conditioners and heat pumps offered by a
manufacturer are typically split systems that are not required to be
laboratory tested but can be certified using an AEDM that does not
require DOE testing of these units. DOE reviewed available data for the
nine small businesses to estimate the incremental testing cost burden
those firms might experience due to the revised test procedure. These
manufacturers had an average of 35
[[Page 37046]]
models requiring testing. DOE determined the numbers of models using
DOE's Compliance Certification Database (https://www.regulations.doe.gov/certification-data/). The additional testing
cost for final certification for 35 models was estimated at $70,000.
Meanwhile, these certifications would be expected to last the product
life, estimated to be at least five years. This test burden is
therefore estimated to be approximately $14,000 annually.
In addition to off-mode testing costs facing small OUMs of central
air conditioners and heat pumps, this final rule will require ICMs to
conduct testing for their basic models. However, DOE has modified its
definition of basic model for ICM to match the Similarity Group concept
suggested by several stakeholders (see section III.A.1.d). Further, DOE
has relaxed its requirement for testing of ICM heat pump combinations,
such that only a limited number of heat pump basic models would require
testing, i.e., those for which a test has not been conducted for an
equivalent air-conditioner model. DOE identified three domestic small
ICMs subject to testing costs under this final rule.
To calculate the additional testing costs facing small ICMs, DOE
used data provided by AHRI regarding what they referred to as
Similarity Groups and which DOE is considering to be basic models.
Specifically, DOE assumed an average of 42 basic models per ICM based
on the AHRI data. (AHRI, No. 70 at p. 6) DOE also assumed $7,500 in
added costs per test and two tests per basic model. (AHRI, No. 70 at p.
4) Assuming $15,000 in additional testing costs per basic model (to
cover two tests per model), and that testing of basic models may not
have to be updated more than once every five years, DOE estimated that
the total additional testing cost for final certification of 42 basic
models for each small ICM would amount to costs averaging $126,000 per
year.
DOE will provide its certification and final supporting statement
of factual basis to the Chief Counsel for Advocacy of the SBA for
review under 5 U.S.C. 605(b).
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of central air conditioners and heat pumps must
certify to DOE that their products comply with any applicable energy
conservation standards. In certifying compliance, manufacturers must
test their products according to the DOE test procedures for central
air conditioners and heat pumps, including any amendments adopted for
those test procedures. DOE has established regulations for the
certification and recordkeeping requirements for all covered consumer
products and commercial equipment, including central air conditioners
and heat pumps. 76 FR 12422 (March 7, 2011); 80 FR 5099 (Jan. 30,
2015). The collection-of-information requirement for the certification
and recordkeeping is subject to review and approval by OMB under the
Paperwork Reduction Act (PRA). This requirement has been approved by
OMB under OMB control number 1910-1400. Public reporting burden for the
certification is estimated to average 30 hours per response, including
the time for reviewing instructions, searching existing data sources,
gathering and maintaining the data needed, and completing and reviewing
the collection of information.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
In this final rule, DOE amends its test procedure for central air
conditioners and heat pumps. DOE has determined that this final rule
falls into a class of actions that are categorically excluded from
review under the National Environmental Policy Act of 1969 (42 U.S.C.
4321 et seq.) and DOE's implementing regulations at 10 CFR part 1021.
Specifically, this rule amends the existing test procedures without
affecting the amount, quality or distribution of energy usage, and,
therefore, would not result in any environmental impacts. Thus, this
rulemaking is covered by Categorical Exclusion A5 under 10 CFR part
1021, subpart D, which applies to any rulemaking that interprets or
amends an existing rule without changing the environmental effect of
that rule. Accordingly, neither an environmental assessment nor an
environmental impact statement is required.
DOE's CX determination for this rule is available at https://energy.gov/nepa/categorical-exclusion-cx-determinations-cx.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 4, 1999)
imposes certain requirements on agencies formulating and implementing
policies or regulations that preempt State law or that have Federalism
implications. The Executive Order requires agencies to examine the
constitutional and statutory authority supporting any action that would
limit the policymaking discretion of the States and to carefully assess
the necessity for such actions. The Executive Order also requires
agencies to have an accountable process to ensure meaningful and timely
input by State and local officials in the development of regulatory
policies that have Federalism implications. On March 14, 2000, DOE
published a statement of policy describing the intergovernmental
consultation process it will follow in the development of such
regulations. 65 FR 13735. DOE has examined this final rule and has
determined that it would not have a substantial direct effect on the
States, on the relationship between the national government and the
States, or on the distribution of power and responsibilities among the
various levels of government. EPCA governs and prescribes Federal
preemption of State regulations as to energy conservation for the
products that are the subject of this rule. States can petition DOE for
exemption from such preemption to the extent, and based on criteria,
set forth in EPCA. (42 U.S.C. 6297(d)) No further action is required by
Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
Eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically requires that Executive agencies make every reasonable
effort to ensure that the regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly specifies any effect on existing
Federal law or regulation; (3) provides a clear legal standard for
affected conduct while promoting simplification and burden reduction;
(4) specifies the retroactive effect, if any; (5) adequately defines
key terms; and (6) addresses other important issues affecting clarity
and general draftsmanship under any guidelines issued by the Attorney
General. Section 3(c) of Executive Order 12988 requires Executive
agencies to
[[Page 37047]]
review regulations in light of applicable standards in sections 3(a)
and 3(b) to determine whether they are met or it is unreasonable to
meet one or more of them. DOE has completed the required review and
determined that, to the extent permitted by law, the rule meets the
relevant standards of Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (UMRA)
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. Public Law 104-4, sec. 201 (codified at 2 U.S.C. 1531).
For a regulatory action likely to result in a rule that may cause the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector of $100 million or more in any one year
(adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The UMRA also requires a Federal agency to
develop an effective process to permit timely input by elected officers
of State, local, and Tribal governments on a proposed ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect small governments. On March 18, 1997,
DOE published a statement of policy on its process for
intergovernmental consultation under UMRA. 62 FR 12820; also available
at https://energy.gov/gc/office-general-counsel. DOE examined this final
rule according to UMRA and its statement of policy and determined that
the rule contains neither an intergovernmental mandate, nor a mandate
that may result in the expenditure of $100 million or more in any year,
so these requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This final rule will not have any impact on the autonomy or integrity
of the family as an institution. Accordingly, DOE has concluded that it
is not necessary to prepare a Family Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights'' 53 FR 8859 (March 18, 1988), that this regulation will not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under the Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (Feb. 22, 2002), and
DOE's guidelines were published at 67 FR 62446 (Oct. 7, 2002). DOE has
reviewed this final rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OMB,
a Statement of Energy Effects for any significant energy action. A
``significant energy action'' is defined as any action by an agency
that promulgated or is expected to lead to promulgation of a final
rule, and that: (1) Is a significant regulatory action under Executive
Order 12866, or any successor order; and (2) is likely to have a
significant adverse effect on the supply, distribution, or use of
energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any significant energy action, the
agency must give a detailed statement of any adverse effects on energy
supply, distribution, or use associated with the rule's implementation,
and of reasonable alternatives to the action and their expected
benefits on energy supply, distribution, and use.
The regulatory action is not a significant regulatory action under
Executive Order 12866. Moreover, it will not have a significant adverse
effect on the supply, distribution, or use of energy, nor has it been
designated as a significant energy action by the Administrator of OIRA.
Therefore, it is not a significant energy action, and, accordingly, DOE
has not prepared a Statement of Energy Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of the
Federal Energy Administration Act of 1974, as amended by the Federal
Energy Administration Authorization Act of 1977. (15 U.S.C. 788; FEAA)
Section 32 essentially provides in relevant part that, where a proposed
rule authorizes or requires use of commercial standards, the notice of
proposed rulemaking must inform the public of the use and background of
such standards. In addition, section 32(c) requires DOE to consult with
the Attorney General and the Chairman of the Federal Trade Commission
(FTC) concerning the impact of the commercial or industry standards on
competition.
The rule incorporates testing methods contained in the following
commercial standards: AHRI 210/240-2008, Performance Rating of Unitary
Air-Conditioning & Air-Source Heat Pump Equipment; and AHRI 1230-2010,
Performance Rating of Variable Refrigerant Flow Multi-Split Air-
Conditioning and Heat Pump Equipment. While the amended test procedure
is not exclusively based on AHRI 210/240-2008 or AHRI 1230-2010, one
component of the test procedure, namely test setup requirements, adopts
language from AHRI 210/240-2008 without amendment; and another
component of the test procedure, namely test setup and test performance
requirements for multi-split systems, adopts language from AHRI 1230-
2010 without amendment. DOE has evaluated these standards and consulted
with the Attorney General and the Chairman of the FTC and has concluded
that this final rule fully complies with the requirements of section
32(b) of the FEAA.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will report to Congress on the
promulgation of this rule before its effective date. The report will
state that it has been determined that the rule is not a ``major rule''
as defined by 5 U.S.C. 804(2).
N. Description of Materials Incorporated by Reference
In this final rule, DOE is incorporating by reference specific
sections, figures, and tables in the following two test
[[Page 37048]]
standards published by AHRI: ANSI/AHRI 210/240-2008 with Addenda 1 and
2, titled ``Performance Rating of Unitary Air-Conditioning & Air-Source
Heat Pump Equipment;'' and ANSI/AHRI 1230-2010 with Addendum 2, titled
``Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split
Air-Conditioning and Heat Pump Equipment.'' DOE is also updating its
incorporation by reference (IBR) to the most recent versions of
specific standards, figures, and tables in the following standards
published by ASHRAE: ASHRAE 23.1-2010 titled ``Methods of Testing for
Rating the Performance of Positive Displacement Refrigerant Compressors
and Condensing Units that Operate at Subcritical Temperatures of the
Refrigerant'', ANSI/ASHRAE 37-2009, Methods of Testing for Rating
Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment,
ANSI/ASHRAE 41.1-2013 titled ``Standard Method for Temperature
Measurement'', ASHRAE 41.6-2014 titled ``Standard Method for Humidity
Measurement'', and ASHRAE 41.9-2011 titled ``Standard Methods for
Volatile-Refrigerant Mass Flow Measurements Using Calorimeters''.
Finally, DOE is updating its IBR to specific figures in the most recent
version of the following test procedure from ASHRAE and AMCA: ANSI/AMCA
210-2007, ANSI/ASHRAE 51-2007, Laboratory Methods of Testing Fans for
Certified Aerodynamic Performance Rating.
AHRI 210/240-2008 is an industry accepted test procedure that
measures the cooling and heating performance of central air
conditioners and heat pumps and is applicable to products sold in North
America. The test procedure in this final rule references various
sections of AHRI 210/240-2008 that address test setup, test conditions,
and rating requirements. AHRI 210/240-2008 is readily available on
AHRI's Web site at https://www.ahrinet.org/site/686/Standards/HVACR-Industry-Standards/Search-Standards.
AHRI 1230-2010 is an industry accepted test procedure that measures
the cooling and heating performance of variable refrigerant flow (VRF)
multi-split air conditioners and heat pumps and is applicable to
products sold in North America. The test procedure in this final rule
for VRF multi-split systems references various sections of AHRI 1230-
2010 that address test setup, test conditions, and rating requirements.
AHRI 1230-2010 is readily available on AHRI's Web site at https://www.ahrinet.org/site/686/Standards/HVACR-Industry-Standards/Search-Standards.
ASHRAE 23.1-2010 is an industry accepted test procedure for rating
the thermodynamic performance of positive displacement refrigerant
compressors and condensing units that operate at subcritical
temperatures. The test procedure in this final rule references sections
of ASHRAE 23.1-2010 that address requirements, instruments, methods of
testing, and testing procedure specific to compressor calibration.
ASHRAE 23.1-2010 can be purchased from ASHRAE's Web site at https://www.ashrae.org/resources-publications.
ANSI/ASHRAE 37-2009 is an industry accepted standard that provides
test methods for determining the cooling capacity of unitary air-
conditioning equipment and the cooling or heating capacities, or both,
of unitary heat pump equipment. The test procedure in this final rule
references various sections of ANSI/ASHRAE 37-2009 that address test
conditions and test procedures, updating the IBR from a previous
version of this standard, ASHRAE 37-2005. ANSI/ASHRAE 37-2009 can be
purchased from ASHRAE's Web site at https://www.ashrae.org/resources-publications.
ANSI/ASHRAE 41.1-2013 is an industry accepted method for measuring
temperature in testing heating, refrigerating, and air-conditioning
equipment. The test procedure in this final rule references sections of
ANSI/ASHRAE 41.1-2013 that address requirements, instruments, and
methods for measuring temperature. ANSI/ASHRAE 41.1-2013 can be
purchased from ASHRAE's Web site at https://www.ashrae.org/resources-publications.
ASHRAE 41.2-1987 (RA 1992) is an industry accepted test method for
measuring airflow. The test procedure in this final rule references
sections of ASHRAE 41.2-1987 (RA 1992) that address test setup and test
methods. ASHRAE 41.2-1987 (RA 1992) can be purchased from ASHRAE's Web
site at https://www.ashrae.org/resources-publications.
ASHRAE 41.6-2014 is an industry accepted test method for measuring
humidity of moist air. The test procedure in this final rule references
sections of ASHRAE 41.6-2014 that address requirements, instruments,
and methods for measuring humidity. ASHRAE 41.6-2014 can be purchased
from ASHRAE's Web site at https://www.ashrae.org/resources-publications.
ASHRAE 41.9-2011 is an industry accepted standard that provides
recommended practices for measuring the mass flow rate of volatile
refrigerants using calorimeters. The test procedure in this final rule
references sections of ASHRAE 41.9-2011 that address requirements,
instruments, and methods for measuring refrigerant flow during
compressor calibration. ASHRAE 41.9-2011 can be purchased from ASHRAE's
Web site at https://www.ashrae.org/resources-publications.
ANSI/ASHRAE Standard 116-2010 is an industry accepted standard that
provides test methods and calculation procedures for determining the
capacities and cooling seasonal efficiency ratios for unitary air-
conditioning, and heat pump equipment and heating seasonal performance
factors for heat pump equipment. The test procedure in this final rule
references various sections of ANSI/ASHRAE 116-2010 that addresses test
methods and calculations, updating the IBR from a previous version of
the standard, ASHRAE 116-1995 (RA 2005). ANSI/ASHRAE Standard 116-2010
can be purchased from ASHRAE's Web site at https://www.ashrae.org/resources-publications.
AMCA 210-2007 is an industry accepted standard that establishes
uniform test methods for a laboratory test of a fan or other air moving
device to determine its aerodynamic performance in terms of air flow
rate, pressure developed, power consumption, air density, speed of
rotation, and efficiency for rating or guarantee purposes. The test
procedure in this final rule references various sections of AMCA 210-
2007 that address test conditions, updating the IBR from a previous
version of this standard, ASHRAE/AMCA 51-1999/210-1999. AMCA 210-2007
can be purchased from AMCA's Web site at https://www.amca.org/store/index.php.
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this final
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Reporting and recordkeeping
requirements.
10 CFR Part 430
Administrative practice and procedure, Confidential business
information, Energy conservation, Energy conservation test procedures,
Household appliances, Imports, Incorporation by reference,
Intergovernmental relations, Small businesses.
[[Page 37049]]
Issued in Washington, DC, on May 19, 2016.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
For the reasons set forth in the preamble, DOE amends parts 429 and
430 of chapter II of title 10, Code of Federal Regulations, to read as
follows:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317.
0
2. Section 429.12 is amended by revising paragraphs (b)(8) and (12) to
read as follows:
Sec. 429.12 General requirements applicable to certification reports.
* * * * *
(b) * * *
(8) The test sample size (i.e., number of units tested for the
basic model, or in the case of single-split system or single-package
central air conditioners and central air conditioning heat pumps, or
multi-split, multi-circuit, or multi-head mini-split systems other than
the ``tested combination,'' for each individual combination or
individual model). Enter ``0'' if an AEDM was used in lieu of testing
(and in the case of central air conditioners and central air
conditioning heat pumps, this must be indicated separately for each
metric);
* * * * *
(12) If the test sample size is listed as ``0'' to indicate the
certification is based upon the use of an alternate way of determining
measures of energy conservation, identify the method used for
determining measures of energy conservation (such as ``AEDM,'' or
linear interpolation). Manufacturers of commercial packaged boilers,
commercial water heating equipment, commercial refrigeration equipment,
commercial HVAC equipment, and central air conditioners and central air
conditioning heat pumps must provide the manufacturer's designation
(name or other identifier) of the AEDM used; and
* * * * *
0
3. Section 429.16 is revised to read as follows:
Sec. 429.16 Central air conditioners and central air conditioning
heat pumps.
(a) Determination of Represented Value--(1) Required represented
values. Determine the represented values (including SEER, EER, HSPF,
PW,OFF, cooling capacity, and heating capacity, as
applicable) for the individual models/combinations (or ``tested
combinations'') specified in the following table.
------------------------------------------------------------------------
Equipment Required represented
Category subcategory values
------------------------------------------------------------------------
Single-Package Unit........... Single-Package AC Every individual
(including Space- model distributed in
Constrained). commerce.
Single-Package HP
(including Space-
Constrained).
Outdoor Unit and Indoor Unit Single-Split Every individual
(Distributed in Commerce by System AC with combination
OUM). Single-Stage or distributed in
Two-Stage commerce, including
Compressor all coil-only and
(including Space- blower coil
Constrained and combinations. For
Small-Duct, High each model of
Velocity Systems outdoor unit, this
(SDHV)). must include at
least one coil-only
value that is
representative of
the least efficient
combination
distributed in
commerce with the
particular model of
outdoor unit.
Single-Split Every individual
System AC with combination
Other Than distributed in
Single-Stage or commerce, including
Two-Stage all coil-only and
Compressor blower coil
(including Space- combinations.
Constrained and
SDHV).
Single-Split- Every individual
System HP combination
(including Space- distributed in
Constrained and commerce.
SDHV).
Multi-Split, For each model of
Multi-Circuit, outdoor unit, at a
or Multi-Head minimum, a non-
Mini-Split Split ducted ``tested
System--non-SDHV. combination.'' For
any model of outdoor
unit also sold with
models of ducted
indoor units, a
ducted ``tested
combination.''
Additional
representations are
allowed, as
described in
paragraph (c)(3)(i)
of this section.
Multi-Split, For each model of
Multi-Circuit, outdoor unit, an
or Multi-Head SDHV ``tested
Mini-Split Split combination.''
System--SDHV. Additional
representations are
allowed, as
described in
paragraph (c)(3)(ii)
of this section.
Indoor Unit Only (Distributed Single-Split- Every individual
in Commerce by ICM). System Air combination
Conditioner distributed in
(including Space- commerce.
Constrained and
SDHV).
Single-Split-
System Heat Pump
(including Space-
Constrained and
SDHV).
Multi-Split, For a model of indoor
Multi-Circuit, unit within each
or Multi-Head basic model, an SDHV
Mini-Split Split ``tested
System--SDHV. combination.''
Additional
representations are
allowed, as
described in section
(c)(3)(ii).
------------------------------------------------------------------------
Outdoor Unit with no Match....................... Every model of
outdoor unit
distributed in
commerce (tested
with a model of coil-
only indoor unit as
specified in
paragraph (c)(2) of
this section).
------------------------------------------------------------------------
(2) PW,OFF. If individual models of single-package
systems or individual combinations (or ``tested combinations'') of
split systems that are otherwise identical are offered with multiple
options for off mode-related components, determine the represented
value for the individual model/combination with the crankcase heater
and controls that are the most consumptive. A manufacturer may also
determine represented values for individual models/combinations with
less consumptive off mode options; however, all such options must be
[[Page 37050]]
identified with different model numbers for single-package systems or
for outdoor units (in the case of split systems).
(3) Limitations for represented values of individual combinations.
The following paragraphs explains the limitations for represented
values of individual combinations (or ``tested combinations'').
(i) Regional. A basic model may only be certified as compliant with
a regional standard if all individual combinations within that basic
model meet the regional standard for which it is certified. If a model
of outdoor unit is certified below a regional standard, then the model
of outdoor unit must have a unique model number for distribution in
each region. An ICM cannot certify a basic model containing a
representative value that is more efficient than any combination
certified by an OUM containing the same outdoor unit.
(ii) Multiple product classes. Models of outdoor units that are
rated and distributed in individual combinations that span multiple
product classes must be tested, rated, and certified pursuant to
paragraph (a) of this section as compliant with the applicable standard
for each product class. This includes multi-split systems, multi-
circuit systems, and multi-head mini-split systems with a represented
value for a mixed combination including both SDHV and either non-ducted
or ducted indoor units.
(4) Requirements. All represented values under paragraph (a) of
this section must be based on testing in accordance with the
requirements in paragraph (b) of this section or the application of an
AEDM or other methodology as allowed in paragraph (c) of this section.
(b) Units tested--(1) General. The general requirements of Sec.
429.11 apply to central air conditioners and heat pumps; and
(2) Individual model/combination selection for testing. (i) The
table identifies the minimum testing requirements for each basic model
that includes multiple individual models/combinations. For each basic
model that includes only one individual model/combination, that
individual model/combination must be tested.
----------------------------------------------------------------------------------------------------------------
Category Equipment subcategory Must test: With:
----------------------------------------------------------------------------------------------------------------
Single-Package Unit.................. Single-Package AC The lowest SEER N/A.
(including Space- individual model.
Constrained).
Single-Package HP
(including Space-
Constrained).
Outdoor Unit and Indoor Unit Single-Split-System AC The model of outdoor The model of coil-only
(Distributed in Commerce by OUM). with Single-Stage or unit. indoor unit that is
Two-Stage Compressor likely to have the
(including Space- largest volume of
Constrained and Small- retail sales with the
Duct, High Velocity particular model of
Systems (SDHV)). outdoor unit.
Single-Split System AC The model of outdoor The model of indoor
with Other Than Single- unit. unit that is likely to
Stage or Two-Stage have the largest
Compressor (including volume of retail sales
Space-Constrained and with the particular
SDHV). model of outdoor unit.
Single-Split-System HP
(including Space-
Constrained and SDHV).
Multi-Split, Multi- The model of outdoor At a minimum, a
Circuit, or Multi-Head unit. ``tested combination''
Mini-Split Split composed entirely of
System--non-SDHV. non-ducted indoor
units. For any models
of outdoor units also
sold with models of
ducted indoor units, a
second ``tested
combination'' composed
entirely of ducted
indoor units must be
tested (in addition to
the non-ducted
combination).
Multi-Split, Multi- The model of outdoor A ``tested
Circuit, or Multi-Head unit. combination'' composed
Mini-Split Split entirely of SDHV
System--SDHV. indoor units.
Indoor Unit Only (Distributed in Single-Split-System Air A model of indoor unit. The least efficient
Commerce by ICM). Conditioner (including model of outdoor unit
Space-Constrained and with which it will be
SDHV). paired where the least
efficient model of
outdoor unit is the
model of outdoor unit
in the lowest SEER
combination as
certified by the OUM.
If there are multiple
models of outdoor unit
with the same lowest
SEER represented
value, the ICM may
select one for testing
purposes.
Single-Split-System Nothing, as long as an
Heat Pump (including equivalent air
Space-Constrained and conditioner basic
SDHV). model has been tested.
If an equivalent air
conditioner basic
model has not been
tested, must test a
model of indoor unit.
[[Page 37051]]
Multi-Split, Multi- A model of indoor unit. A ``tested
Circuit, or Multi-Head combination'' composed
Mini-Split Split entirely of SDHV
System--SDHV. indoor units, where
the outdoor unit is
the least efficient
model of outdoor unit
with which the SDHV
indoor unit will be
paired. The least
efficient model of
outdoor unit is the
model of outdoor unit
in the lowest SEER
combination as
certified by the OUM.
If there are multiple
models of outdoor unit
with the same lowest
SEER represented
value, the ICM may
select one for testing
purposes.
----------------------------------------------------------------------------------------------------------------
Outdoor Unit with No Match The model of outdoor A model of coil-only
unit. indoor unit meeting
the requirements of
section 2.2e of
Appendix M to subpart
B of part 430.
----------------------------------------------------------------------------------------------------------------
(ii) Each individual model/combination (or ``tested combination'')
identified in paragraph (b)(2)(i) of this section is not required to be
tested for PW,OFF. Instead, at a minimum, among individual
models/combinations with similar off-mode construction (even spanning
different models of outdoor units), a manufacturer must test at least
one individual model/combination for PW,OFF.
(3) Sampling plans and representative values. (i) For individual
models (for single-package systems) or individual combinations (for
split-systems, including ``tested combinations'' for multi-split,
multi-circuit, and multi-head mini-split systems) with represented
values determined through testing, each individual model/combination
(or ``tested combination'') must have a sample of sufficient size
tested in accordance with the applicable provisions of this subpart.
For heat pumps (other than heating-only heat pumps), all units of the
sample population must be tested in both the cooling and heating modes
and the results used for determining all representations. The
represented values for any individual model/combination must be
assigned such that:
(i) Off-Mode. Any represented value of power consumption or other
measure of energy consumption for which consumers would favor lower
values must be greater than or equal to the higher of:
(A) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TR08JN16.000
and, x is the sample mean; n is the number of samples; and
xi is the ith sample; Or,
(B) The upper 90 percent confidence limit (UCL) of the true mean
divided by 1.05, where:
[GRAPHIC] [TIFF OMITTED] TR08JN16.001
And x is the sample mean; s is the sample standard deviation; n is the
number of samples; and t0.90 is the t statistic for a 90
percent one-tailed confidence interval with n-1 degrees of freedom
(from appendix D). Round represented values of off-mode power
consumption to the nearest watt.
(ii) SEER, EER, and HSPF. Any represented value of the energy
efficiency or other measure of energy consumption for which consumers
would favor higher values shall be less than or equal to the lower of:
(A) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TR08JN16.002
and, x is the sample mean; n is the number of samples; and
xi is the ith sample; or,
(B) The lower 90 percent confidence limit (LCL) of the true mean
divided by 0.95, where:
[GRAPHIC] [TIFF OMITTED] TR08JN16.003
And x is the sample mean; s is the sample standard deviation; n is the
number of samples; and t0.90 is the t statistic for a 90
percent one-tailed confidence interval with n-1 degrees of freedom
(from Appendix D). Round represented values of EER, SEER, and HSPF to
the nearest 0.05.
(iii) Cooling Capacity. The represented value of cooling capacity
must be a self-declared value that is no less than 95 percent of the
mean of the cooling capacities measured for the units in the sample,
rounded:
(A) To the nearest 100 Btu/h if cooling capacity is less than
20,000 Btu/h,
(B) To the nearest 200 Btu/h if cooling capacity is greater than or
equal to 20,000 Btu/h but less than 38,000 Btu/h, and
(C) To the nearest 500 Btu/h if cooling capacity is greater than or
equal to 38,000 Btu/h and less than 65,000 Btu/h.
(iv) Heating Capacity. The represented value of heating capacity
must be a self-declared value that is no less than 95 percent of the
mean of the heating capacities measured for the units in the sample,
rounded:
(A) To the nearest 100 Btu/h if heating capacity is less than
20,000 Btu/h,
(B) To the nearest 200 Btu/h if heating capacity is greater than or
equal to 20,000 Btu/h but less than 38,000 Btu/h, and
(C) To the nearest 500 Btu/h if heating capacity is greater than or
equal to 38,000 Btu/h and less than 65,000 Btu/h.
(c) Determination of represented values for all other individual
models/combinations besides those specified in paragraph (b)(2) of this
section--(1) All basic models except outdoor units with no match and
multi-split systems, multi-circuit systems, and multi-head mini-split
systems. (i) For every individual model/combination within a basic
model other than the individual model/
[[Page 37052]]
combination required to be tested pursuant to paragraph (b)(2) of this
section, either--
(A) A sample of sufficient size, comprised of production units or
representing production units, must be tested as complete systems with
the resulting represented values for the individual model/combination
obtained in accordance with paragraphs (b)(1) and (3) of this section;
or
(B) The represented values of the measures of energy efficiency or
energy consumption must be assigned through the application of an AEDM
in accordance with paragraph (d) of this section and Sec. 429.70. An
AEDM may only be used to rate individual models/combinations in a basic
model other than the individual model/combination required for
mandatory testing under paragraph (b)(2)(i) of this section. No basic
model may be rated with an AEDM (except for determination of
PW,OFF).
(ii) For every individual model/combination within a basic model
tested pursuant to paragraph (b)(2) of this section, but for which
PW,OFF testing was not conducted, the represented value of
PW,OFF may be assigned through, either:
(A) The testing result from an individual model/combination of
similar off-mode construction, or
(B) The application of an AEDM in accordance with paragraph (d) of
this section and Sec. 429.70.
(2) Outdoor units with no match. All models of outdoor unit within
a basic model must be tested. No model of outdoor unit may be rated
with an AEDM.
(3) Multi-split systems, multi-circuit systems, and multi-head
mini-split systems. The following applies:
(i) For basic models composed of both non-ducted and ducted
combinations, the represented value for the mixed non-ducted/ducted
combination is the mean of the represented values for the non-ducted
and ducted combinations as determined in accordance with paragraph
(b)(3)(i) of this section.
(ii) For basic models composed of both SDHV and non-ducted or
ducted combinations, the represented value for the mixed SDHV/non-
ducted or SDHV/ducted combination is the mean of the represented values
for the SDHV, non-ducted, or ducted combinations, as applicable, as
determined in accordance with paragraph (b)(3)(i) of this section.
(iii) All other individual combinations of models of indoor units
for the same model of outdoor unit for which the manufacturer chooses
to make representations must be rated as separate basic models, and the
provisions in paragraphs (b)(1) through (3) and (c)(3)(i) and (ii) of
this section apply.
(iv) For every individual combination (or ``tested combination'')
within a basic model tested pursuant to paragraph (b)(2) of this
section, but for which PW,OFF testing was not conducted, the
representative values of PW,OFF may be assigned through
either:
(A) The testing result from an individual combination (or ``tested
combination'') of similar off-mode construction, or
(B) Application of an AEDM in accordance with paragraph (d) of this
section and Sec. 429.70. No basic model may be rated with an AEDM for
SEER, EER, or HSPF.
(d) Alternative efficiency determination methods. In lieu of
testing, represented values of efficiency or consumption may be
determined through the application of an AEDM pursuant to the
requirements of Sec. 429.70(e) and the provisions of this section.
(1) Power or energy consumption. Any represented value of the
average off mode power consumption or other measure of energy
consumption of an individual model/combination for which consumers
would favor lower values must be greater than or equal to the output of
the AEDM but no less than the standard.
(2) Energy efficiency. Any represented value of the SEER, EER, HSPF
or other measure of energy efficiency of an individual model/
combination for which consumers would favor higher values must be less
than or equal to the output of the AEDM but no greater than the
standard.
(3) Cooling capacity. The represented value of cooling capacity of
an individual model/combination must be no less than 95% of the cooling
capacity output simulated by the AEDM.
(4) Heating capacity. The represented value of heating capacity of
an individual model/combination must be no less than 95% of the heating
capacity output simulated by the AEDM.
(e) Certification reports. This paragraph specifies the information
that must be included in a certification report.
(1) General. The requirements of Sec. 429.12 apply to central air
conditioners and heat pumps.
(2) Public product-specific information. Pursuant to Sec.
429.12(b)(13), for each individual model (for single-package systems)
or individual combination (for split-systems, including ``tested
combinations'' for multi-split, multi-circuit, and multi-head mini-
split systems), a certification report must include the following
public product-specific information: The seasonal energy efficiency
ratio (SEER in British thermal units per Watt-hour (Btu/W-h)); the
average off mode power consumption (PW,OFF in Watts); the
cooling capacity in British thermal units per hour (Btu/h); the
region(s) in which the basic model can be sold; and
(i) For heat pumps, the heating seasonal performance factor (HSPF
in British thermal units per Watt-hour (Btu/W-h));
(ii) For air conditioners (excluding space constrained), the energy
efficiency ratio (EER in British thermal units per Watt-hour (Btu/W-
h));
(iii) For single-split-system equipment, whether the represented
value is for a coil-only or blower coil system; and
(iv) For multi-split, multiple-circuit, and multi-head mini-split
systems (including VRF), whether the represented value is for a non-
ducted, ducted, mixed non-ducted/ducted system, SDHV, mixed non-ducted/
SDHV system, or mixed ducted/SDHV system.
(3) Basic and individual model numbers. The basic model number and
individual model number(s) required to be reported under Sec.
429.12(b)(6) must consist of the following:
----------------------------------------------------------------------------------------------------------------
Individual model number(s)
Equipment type Basic model number -----------------------------------------------------------
1 2 3
----------------------------------------------------------------------------------------------------------------
Single-Package (including Space- Number unique to Package........... N/A............... N/A.
Constrained). the basic model.
Single-Split System (including Number unique to Outdoor Unit...... Indoor Unit....... Air Mover (could
Space-Constrained). the basic model. be same as indoor
unit if fan is
part of indoor
unit model
number).
[[Page 37053]]
Multi-Split, Multi-Circuit, and Number unique to Outdoor Unit...... When certifying a When certifying a
Multi-Head Mini-Split System the basic model. basic model based basic model based
(including SDHV). on tested on tested
combination(s): combination(s):
***. ***
When certifying an When certifying an
individual individual
combination: combination: Air
Indoor Unit(s). Mover(s).
Outdoor Unit with No Match...... Number unique to Outdoor Unit...... N/A............... N/A.
the basic model.
----------------------------------------------------------------------------------------------------------------
(4) Additional product-specific information. Pursuant to Sec.
429.12(b)(13), for each individual model/combination (or ``tested
combination''), a certification report must include the following
additional product-specific information: the cooling full load air
volume rate for the system or for each indoor unit as applicable (in
cubic feet per minute (cfm)); the air volume rates for other test
conditions including minimum cooling air volume rate, intermediate
cooling air volume rate, full load heating air volume rate, minimum
heating air volume rate, intermediate heating air volume rate, and
nominal heating air volume rate (cfm) for the system or for each indoor
unit as applicable, if different from the cooling full load air volume
rate; whether the individual model/combination uses a fixed orifice,
thermostatic expansion valve, electronic expansion valve, or other type
of metering device; the duration of the compressor break-in period, if
used; whether the optional tests were conducted to determine the Cc
value used to represent cooling mode cycling losses or whether the
default value was used; the temperature at which the crankcase heater
with controls is designed to turn on, if applicable; the maximum time
between defrosts as allowed by the controls (in hours); and
(i) For heat pumps, whether the optional tests were conducted to
determine the Ch value or whether the default value was used;
(ii) For multi-split, multiple-circuit, and multi-head mini-split
systems, the number of indoor units tested with the outdoor unit; the
nominal cooling capacity of each indoor unit and outdoor unit in the
combination; and the indoor units that are not providing heating or
cooling for part-load tests;
(iii) For ducted systems having multiple indoor fans within a
single indoor unit, the number of indoor fans; the nominal cooling
capacity of the indoor unit and outdoor unit; and which fan(s) were
operating and the allocation of the air volume rate to each operational
fan for each operating mode used to determine represented values;
(iv) For blower coil systems, the airflow-control settings
associated with full load cooling operation; and the airflow-control
settings or alternative instructions for setting fan speeds for tests
other than full load cooling operation to the speeds upon which the
represented value is based;
(v) For equipment with time-adaptive defrost control, the frosting
interval to be used during frost accumulation tests and the procedure
for manually initiating the defrost at the specified time;
(vi) For models of indoor units designed for both horizontal and
vertical installation or for both up-flow and down-flow vertical
installations, the orientation used for testing;
(vii) For variable speed equipment, the compressor frequency set
points, and the required dip switch/control settings for step or
variable components; and
(viii) For variable speed heat pumps, whether the unit controls
restrict use of minimum compressor speed operation for some range of
operating ambient conditions, whether the unit controls restrict use of
maximum compressor speed operation for any ambient temperatures below
17 [deg]F, and whether the optional H42 low temperature test
was used to characterize performance at temperatures below 17 [deg]F.
(f) Represented values for the Federal Trade Commission. The
following represented value determinations shall be followed to meet
the requirements of the Federal Trade Commission.
(1) Annual Operating Cost--Cooling. Determine the represented value
of estimated annual operating cost for cooling-only units or the
cooling portion of the estimated annual operating cost for air-source
heat pumps that provide both heating and cooling by calculating the
product of:
(i) The quotient of the represented value of cooling capacity, in
Btu's per hour as determined in paragraph (b)(3)(iii) of this section,
divided by the represented value of SEER, in Btu's per watt-hour, as
determined in paragraph (b)(3)(ii) of this section;
(ii) The representative average use cycle for cooling of 1,000
hours per year;
(iii) A conversion factor of 0.001 kilowatt per watt; and
(iv) The representative average unit cost of electricity in dollars
per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act.
(2) Annual Operating Cost--Heating. Determine the represented value
of estimated annual operating cost for air-source heat pumps that
provide only heating or for the heating portion of the estimated annual
operating cost for air-source heat pumps that provide both heating and
cooling, as the product of:
(i) The quotient of the mean of the standardized design heating
requirement for the sample, in Btu's per hour, nearest to the Region IV
minimum design heating requirement, determined for each unit in the
sample in section 4.2 of appendix M to subpart B of part 430, divided
by the represented value of heating seasonal performance factor (HSPF),
in Btu's per watt-hour, calculated for Region IV corresponding to the
above-mentioned standardized design heating requirement, as determined
in paragraph (b)(3)(ii) of this section;
(ii) The representative average use cycle for heating of 2,080
hours per year;
(iii) The adjustment factor of 0.77, which serves to adjust the
calculated design heating requirement and heating load hours to the
actual load experienced by a heating system;
(iv) A conversion factor of 0.001 kilowatt per watt; and
(v) The representative average unit cost of electricity in dollars
per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act.
(3) Annual Operating Cost--Total. Determine the represented value
of estimated annual operating cost for air-source heat pumps that
provide both heating and cooling by calculating the sum of the quantity
determined in paragraph (f)(1) of this section added to the quantity
determined in paragraph (f)(2) of this section.
[[Page 37054]]
(4) Regional Annual Operating Cost--Cooling. Determine the
represented value of estimated regional annual operating cost for
cooling-only units or the cooling portion of the estimated regional
annual operating cost for air-source heat pumps that provide both
heating and cooling by calculating the product of:
(i) The quotient of the represented value of cooling capacity, in
Btu's per hour, determined in paragraph (b)(3)(iii) of this section
divided by the represented value of SEER, in Btu's per watt-hour,
determined in paragraph (b)(3)(ii) of this section;
(ii) The estimated number of regional cooling load hours per year
determined from Table 21 in section 4.4 of appendix M to subpart B of
part 430;
(iii) A conversion factor of 0.001 kilowatts per watt; and
(iv) The representative average unit cost of electricity in dollars
per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act.
(5) Regional Annual Operating Cost--Heating. Determine the
represented value of estimated regional annual operating cost for air-
source heat pumps that provide only heating or for the heating portion
of the estimated regional annual operating cost for air-source heat
pumps that provide both heating and cooling as the product of:
(i) The estimated number of regional heating load hours per year
determined from Table 21 in section 4.4 of appendix M to subpart B of
part 430;
(ii) The quotient of the mean of the standardized design heating
requirement for the sample, in Btu's per hour, for the appropriate
generalized climatic region of interest (i.e., corresponding to the
regional heating load hours from ``A'') and determined for each unit in
the sample in section 4.2 of appendix M to subpart B of Part 430,
divided by the represented value of HSPF, in Btu's per watt-hour,
calculated for the appropriate generalized climatic region of interest
and corresponding to the above-mentioned standardized design heating
requirement, and determined in paragraph (b)(3)(iii);
(iii) The adjustment factor of 0.77; which serves to adjust the
calculated design heating requirement and heating load hours to the
actual load experienced by a heating system;
(iv) A conversion factor of 0.001 kilowatts per watt; and
(v) The representative average unit cost of electricity in dollars
per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act;
and
(6) Regional Annual Operating Cost--Total. For air-source heat
pumps that provide both heating and cooling, the estimated regional
annual operating cost is the sum of the quantity determined in
paragraph (f)(4) of this section added to the quantity determined in
paragraph (f)(5) of this section.
(7) Annual Operating Cost--Rounding. Round any represented values
of estimated annual operating cost determined in paragraphs (f)(1)
through (6) of this section to the nearest dollar per year.
4. Section 429.70 is amended by revising paragraph (e) to read as
follows:
Sec. 429.70 Alternative methods for determining energy efficiency or
energy use.
* * * * *
(e) Alternate Efficiency Determination Method (AEDM) for central
air conditioners and heat pumps. This paragraph (e) sets forth the
requirements for a manufacturer to use an AEDM to rate central air
conditioners and heat pumps.
(1) Criteria an AEDM must satisfy. A manufacturer may not apply an
AEDM to an individual model/combination to determine its represented
values (SEER, EER, HSPF, and/or PW,OFF) pursuant to this
section unless authorized pursuant to Sec. 429.16(d) and:
(i) The AEDM is derived from a mathematical model that estimates
the energy efficiency or energy consumption characteristics of the
individual model or combination (SEER, EER, HSPF, and/or
PW,OFF) as measured by the applicable DOE test procedure;
and
(ii) The manufacturer has validated the AEDM in accordance with
paragraph (e)(2) of this section.
(2) Validation of an AEDM. Before using an AEDM, the manufacturer
must validate the AEDM's accuracy and reliability as follows:
(i) The manufacturer must complete testing of each basic model as
required under Sec. 429.16(b)(2). Using the AEDM, calculate the energy
use or efficiency for each of the tested individual models/combinations
within each basic model. Compare the represented value based on testing
and the AEDM energy use or efficiency output according to paragraph
(e)(2)(ii) of this section. The manufacturer is responsible for
ensuring the accuracy and reliability of the AEDM.
(ii) Individual model/combination tolerances. This paragraph
(e)(2)(ii) provides the tolerances applicable to individual models/
combinations rated using an AEDM.
(A) The predicted represented values for each individual model/
combination calculated by applying the AEDM may not be more than four
percent greater (for measures of efficiency) or less (for measures of
consumption) than the values determined from the corresponding test of
the individual model/combination.
(B) The predicted energy efficiency or consumption for each
individual model/combination calculated by applying the AEDM must meet
or exceed the applicable federal energy conservation standard.
(iii) Additional test unit requirements. (A) Each AEDM must be
supported by test data obtained from physical tests of current
individual models/combinations; and
(B) Test results used to validate the AEDM must meet or exceed
current, applicable Federal standards as specified in part 430 of this
chapter; and
(C) Each test must have been performed in accordance with the
applicable DOE test procedure with which compliance is required at the
time the individual models/combinations used for validation are
distributed in commerce.
(3) AEDM records retention requirements. If a manufacturer has used
an AEDM to determine representative values pursuant to this section,
the manufacturer must have available upon request for inspection by the
Department records showing:
(i) The AEDM, including the mathematical model, the engineering or
statistical analysis, and/or computer simulation or modeling that is
the basis of the AEDM;
(ii) Product information, complete test data, AEDM calculations,
and the statistical comparisons from the units tested that were used to
validate the AEDM pursuant to paragraph (e)(2) of this section; and
(iii) Product information and AEDM calculations for each individual
model/combination to which the AEDM has been applied.
(4) Additional AEDM requirements. If requested by the Department,
the manufacturer must:
(i) Conduct simulations before representatives of the Department to
predict the performance of particular individual models/combinations;
(ii) Provide analyses of previous simulations conducted by the
manufacturer; and/or
(iii) Conduct certification testing of individual models or
combinations selected by the Department.
(5) AEDM verification testing. DOE may use the test data for a
given individual model/combination generated pursuant to Sec. 429.104
to verify the represented value determined by an AEDM as long as the
following process is followed:
[[Page 37055]]
(i) Selection of units. DOE will obtain one or more units for test
from retail, if available. If units cannot be obtained from retail, DOE
will request that a unit be provided by the manufacturer;
(ii) Lab requirements. DOE will conduct testing at an independent,
third-party testing facility of its choosing. In cases where no third-
party laboratory is capable of testing the equipment, testing may be
conducted at a manufacturer's facility upon DOE's request.
(iii) Testing. At no time during verification testing may the lab
and the manufacturer communicate without DOE authorization. If during
test set-up or testing, the lab indicates to DOE that it needs
additional information regarding a given individual model or
combination in order to test in accordance with the applicable DOE test
procedure, DOE may organize a meeting between DOE, the manufacturer and
the lab to provide such information.
(iv) Failure to meet certified represented value. If an individual
model/combination tests worse than its certified represented value
(i.e., lower than the certified efficiency value or higher than the
certified consumption value) by more than 5 percent, or the test
results in a different cooling capacity than its certified cooling
capacity by more than 5 percent, DOE will notify the manufacturer. DOE
will provide the manufacturer with all documentation related to the
test set up, test conditions, and test results for the unit. Within the
timeframe allotted by DOE, the manufacturer:
(A) May present any and all claims regarding testing validity; and
(B) If not on site for the initial test set-up, must test at least
one additional unit of the same individual model or combination
obtained from a retail source at its own expense, following the test
requirements in Sec. 429.110(a)(3). When testing at an independent
lab, the manufacturer may choose to have DOE and the manufacturer
present.
(v) Tolerances. This paragraph specifies the tolerances DOE will
permit when conducting verification testing.
(A) For consumption metrics, the result from a DOE verification
test must be less than or equal to 1.05 multiplied by the certified
represented value.
(B) For efficiency metrics, the result from a DOE verification test
must be greater than or equal to 0.95 multiplied by the certified
represented value.
(vi) Invalid represented value. If, following discussions with the
manufacturer and a retest where applicable, DOE determines that the
verification testing was conducted appropriately in accordance with the
DOE test procedure, DOE will issue a determination that the represented
values for the basic model are invalid. The manufacturer must conduct
additional testing and re-rate and re-certify the individual models/
combinations within the basic model that were rated using the AEDM
based on all test data collected, including DOE's test data.
(vii) AEDM use. This paragraph (e)(5)(vii) specifies when a
manufacturer's use of an AEDM may be restricted due to prior invalid
represented values.
(A) If DOE has determined that a manufacturer made invalid
represented values on individual models/combinations within two or more
basic models rated using the manufacturer's AEDM within a 24 month
period, the manufacturer must test the least efficient and most
efficient individual model/combination within each basic model in
addition to the individual model/combination specified in Sec.
429.16(b)(2). The twenty-four month period begins with a DOE
determination that a represented value is invalid through the process
outlined above.
(B) If DOE has determined that a manufacturer made invalid
represented values on more than four basic models rated using the
manufacturer's AEDM within a 24-month period, the manufacturer may no
longer use an AEDM.
(C) If a manufacturer has lost the privilege of using an AEDM, the
manufacturer may regain the ability to use an AEDM by:
(1) Investigating and identifying cause(s) for failures;
(2) Taking corrective action to address cause(s);
(3) Performing six new tests per basic model, a minimum of two of
which must be performed by an independent, third-party laboratory from
units obtained from retail to validate the AEDM; and
(4) Obtaining DOE authorization to resume use of an AEDM.
* * * * *
0
5. Section 429.134 is amended by adding paragraph (k) to read as
follows:
Sec. 429.134 Product-specific enforcement provisions.
* * * * *
(k) Central air conditioners and heat pumps--(1) Verification of
cooling capacity. The cooling capacity of each tested unit of the
individual model (for single-package systems) or individual combination
(for split systems) will be measured pursuant to the test requirements
of Sec. 430.23(m) of this chapter. The mean of the measurement(s)
(either the measured cooling capacity for a single unit sample or the
average of the measured cooling capacities for a multiple unit sample)
will be used to determine the applicable standards for purposes of
compliance.
(2) Verification of CD value. (i) For central air
conditioners and heat pumps other than models of outdoor units with no
match, if manufacturers certify that they did not conduct the optional
tests to determine the Cc and/or Ch value for an individual model (for
single-package systems) or individual combination (for split systems),
as applicable, the default Cc and/or Ch value will be used as the basis
for calculation of SEER or HSPF for each unit tested. If manufacturers
certify that they conducted the optional tests to determine the Cc and/
or Ch value for an individual model (for single-package systems) or
individual combination (for split systems), as applicable, the Cc and/
or Ch value will be measured pursuant to the test requirements of Sec.
430.23(m) of this chapter for each unit tested and the result for each
unit tested (either the tested value or the default value, as selected
according to the criteria for the cyclic test in 10 CFR part 430,
subpart B, appendix M, section 3.5e) used as the basis for calculation
of SEER or HSPF for that unit.
(ii) For models of outdoor units with no match, DOE will use the
default Cc and/or Ch value pursuant to 10 CFR part 430.
* * * * *
PART 430-ENERGY CONSERVATION PROGRAM FOR CONSUMER PRODUCTS
0
6. The authority citation for part 430 continues to read as follows:
Authority: 42 U.S.C. 6291-6309; 28 U.S.C. 2461 note.
0
7. Section 430.2 is amended by:
0
a. Removing the definition of ``ARM/simulation adjustment factor;''
0
b. Revising the definitions of ``basic model'' and ``central air
conditioner;'' and
0
c. Removing the definitions of ``coil family,'' ``condenser-evaporator
coil combination'', ``condensing unit,'' ``evaporator coil'', ``heat
pump,'' ``indoor unit,'' ``outdoor unit,'' ``small duct, high velocity
system,'' and ``tested combination.''
The revisions read as follows:
Sec. 430.2 Definitions.
* * * * *
Basic model means all units of a given type of covered product (or
class thereof) manufactured by one manufacturer; having the same
primary
[[Page 37056]]
energy source; and, which have essentially identical electrical,
physical, and functional (or hydraulic) characteristics that affect
energy consumption, energy efficiency, water consumption, or water
efficiency; and
(1) With respect to general service fluorescent lamps, general
service incandescent lamps, and incandescent reflector lamps: Lamps
that have essentially identical light output and electrical
characteristics--including lumens per watt (lm/W) and color rendering
index (CRI).
(2) With respect to faucets and showerheads: Have the identical
flow control mechanism attached to or installed within the fixture
fittings, or the identical water-passage design features that use the
same path of water in the highest flow mode.
(3) With respect to furnace fans: Are marketed and/or designed to
be installed in the same type of installation; and
(4) With respect to central air conditioners and central air
conditioning heat pumps essentially identical electrical, physical, and
functional (or hydraulic) characteristics means:
(i) For split systems manufactured by outdoor unit manufacturers
(OUMs): all individual combinations having the same model of outdoor
unit, which means comparably performing compressor(s) [a variation of
no more than five percent in displacement rate (volume per time) as
rated by the compressor manufacturer, and no more than five percent in
capacity and power input for the same operating conditions as rated by
the compressor manufacturer], outdoor coil(s) [no more than five
percent variation in face area and total fin surface area; same fin
material; same tube material], and outdoor fan(s) [no more than ten
percent variation in air flow and no more than twenty percent variation
in power input];
(ii) For split systems having indoor units manufactured by
independent coil manufacturers (ICMs): all individual combinations
having comparably performing indoor coil(s) [plus or minus one square
foot face area, plus or minus one fin per inch fin density, and the
same fin material, tube material, number of tube rows, tube pattern,
and tube size]; and
(iii) For single-package systems: all individual models having
comparably performing compressor(s) [no more than five percent
variation in displacement rate (volume per time) rated by the
compressor manufacturer, and no more than five percent variations in
capacity and power input rated by the compressor manufacturer
corresponding to the same compressor rating conditions], outdoor
coil(s) and indoor coil(s) [no more than five percent variation in face
area and total fin surface area; same fin material; same tube
material], outdoor fan(s) [no more than ten percent variation in
outdoor air flow], and indoor blower(s) [no more than ten percent
variation in indoor air flow, with no more than twenty percent
variation in fan motor power input];
(iv) Except that,
(A) for single-package systems and single-split systems,
manufacturers may instead choose to make each individual model/
combination its own basic model provided the testing and represented
value requirements in 10 CFR 429.16 of this chapter are met; and
(B) For multi-split, multi-circuit, and multi-head mini-split
combinations, a basic model may not include both individual small-duct,
high velocity (SDHV) combinations and non-SDHV combinations even when
they include the same model of outdoor unit. The manufacturer may
choose to identify specific individual combinations as additional basic
models.
* * * * *
Central air conditioner or central air conditioning heat pump means
a product, other than a packaged terminal air conditioner or packaged
terminal heat pump, which is powered by single phase electric current,
air cooled, rated below 65,000 Btu per hour, not contained within the
same cabinet as a furnace, the rated capacity of which is above 225,000
Btu per hour, and is a heat pump or a cooling unit only. A central air
conditioner or central air conditioning heat pump may consist of: a
single-package unit; an outdoor unit and one or more indoor units; an
indoor unit only; or an outdoor unit with no match. In the case of an
indoor unit only or an outdoor unit with no match, the unit must be
tested and rated as a system (combination of both an indoor and an
outdoor unit). For all central air conditioner and central air
conditioning heat pump-related definitions, see appendix M of subpart B
of this part.
* * * * *
0
8. Section 430.3 is amended by:
0
a. Adding paragraph (b)(2);
0
b. Revising paragraph (c)(1);
0
c. Adding paragraph (c)(3);
0
d. Revising paragraph (g)(2);
0
e. Removing paragraph (g)(3);
0
f. Redesignating paragraph (g)(4) as (g)(3);
0
g. Adding a new paragraph (g)(4);
0
h. Removing ``, M, '' in paragraph (g)(5);
0
i. Removing paragraph (g)(10);
0
j. Redesignating paragraphs (g)(7) through (9) as (g)(8) through (10);
0
k. Adding new paragraph (g)(7);
0
l. Revising newly redesignated paragraphs (g)(8) through (10); and
0
m. Revising paragraph (g)(13).
The revisions and additions read as follows:
Sec. 430.3 Materials incorporated by reference.
* * * * *
(b) * * *
(2) ANSI/AMCA 210-07, ANSI/ASHRAE 51-07 (``AMCA 210-2007''),
Laboratory Methods of Testing Fans for Certified Aerodynamic
Performance Rating, ANSI approved August 17, 2007, Section 8--Report
and Results of Test, Section 8.2--Performance graphical representation
of test results, IBR approved for appendix M to subpart B, as follows:
(i) Figure 2A--Static Pressure Tap, and
(ii) Figure 12--Outlet Chamber Setup--Multiple Nozzles in Chamber.
(c) * * *
(1) ANSI/AHRI 210/240-2008 with Addenda 1 and 2 (''AHRI 210/240-
2008''), 2008 Standard for Performance Rating of Unitary Air-
Conditioning & Air-Source Heat Pump Equipment, ANSI approved October
27, 2011 (Addendum 1 dated June 2011 and Addendum 2 dated March 2012),
IBR approved for appendix M to subpart B, as follows:
(i) Section 6--Rating Requirements, Section 6.1--Standard Ratings,
6.1.3--Standard Rating Tests, 6.1.3.2--Electrical Conditions;
(ii) Section 6--Rating Requirements, Section 6.1--Standard Ratings,
6.1.3--Standard Rating Tests, 6.1.3.4--Outdoor-Coil Airflow Rate;
(iii) Section 6--Rating Requirements, Section 6.1--Standard
Ratings, 6.1.3--Standard Rating Tests, 6.1.3.5--Requirements for
Separated Assemblies;
(iv) Figure D1--Tunnel Air Enthalpy Test Method Arrangement;
(v) Figure D2--Loop Air Enthalpy Test Method Arrangement; and
(vi) Figure D4--Room Air Enthalpy Test Method Arrangement.
* * * * *
(3) ANSI/AHRI 1230-2010 with Addendum 2 (``AHRI 1230-2010''), 2010
Standard for Performance Rating of Variable Refrigerant Flow (VRF)
Multi-Split Air-Conditioning and Heat Pump Equipment (including
Addendum 1 dated March 2011), ANSI approved August 2, 2010 (Addendum 2
dated June 2014), IBR approved for appendix M to subpart B, as follows:
(i) Section 3--Definitions (except 3.8, 3.9, 3.13, 3.14, 3.15,
3.16, 3.23, 3.24, 3.26, 3.27, 3.28, 3.29, 3.30, and 3.31);
[[Page 37057]]
(ii) Section 5--Test Requirements, Section 5.1 (untitled), 5.1.3-
5.1.4;
(ii) Section 6--Rating Requirements, Section 6.1--Standard Ratings,
6.1.5--Airflow Requirements for Systems with Capacities <65,000 Btu/h
[19,000 W];
(iii) Section 6--Rating Requirements, Section 6.1--Standard
Ratings, 6.1.6--Outdoor-Coil Airflow Rate (Applies to all Air-to-Air
Systems);
(iv) Section 6--Rating Requirements, Section 6.2--Conditions for
Standard Rating Test for Air-cooled Systems < 65,000 Btu/h [19,000W]
(except Table 8); and
(v) Table 4--Refrigerant Line Length Correction Factors.
* * * * *
(g) * * *
(2) ANSI/ASHRAE 23.1-2010, (``ASHRAE 23.1-2010''), Methods of
Testing for Rating the Performance of Positive Displacement Refrigerant
Compressors and Condensing Units that Operate at Subcritical
Temperatures of the Refrigerant, ANSI approved January 28, 2010, IBR
approved for appendix M to subpart B, as follows:
(i) Section 5--Requirements;
(ii) Section 6--Instruments;
(iii) Section 7--Methods of Testing; and
(iv) Section 8--Compressor Testing.
* * * * *
(4) ANSI/ASHRAE Standard 37-2009, (``ANSI/ASHRAE 37-2009''),
Methods of Testing for Rating Electrically Driven Unitary Air-
Conditioning and Heat Pump Equipment, ANSI approved June 25, 2009, IBR
approved for appendix M to subpart B, as follows:
(i) Section 5--Instruments, Section 5.1--Temperature Measuring
Instruments: 5.1.1;
(ii) Section 5--Instruments, Section 5.2--Refrigerant, Liquid, and
Barometric Pressure Measuring Instruments;
(iii) Section 5--Instruments, Section 5.5--Volatile Refrigerant
Flow Measurement;
(iv) Section 6--Airflow and Air Differential Pressure Measurement
Apparatus, Section 6.1--Enthalpy Apparatus (Excluding Figure 3): 6.1.1-
6.1.2 and 6.1.4;
(v) Section 6--Airflow and Air Differential Pressure Measurement
Apparatus, Section 6.2--Nozzle Airflow Measuring Apparatus (Excluding
Figure 5);
(vi) Section 6--Airflow and Air Differential Pressure Measurement
Apparatus, Section 6.3--Nozzles (Excluding Figure 6);
(vii) Section 6--Airflow and Air Differential Pressure Measurement
Apparatus, Section 6.4--External Static Pressure Measurements;
(viii) Section 6--Airflow and Air Differential Pressure Measurement
Apparatus, Section 6.5--Recommended Practices for Static Pressure
Measurements;
(ix) Section 7--Methods of Testing and Calculation, Section 7.3--
Indoor and Outdoor Air Enthalpy Methods (Excluding Table 1);
(x) Section 7--Methods of Testing and Calculation, Section 7.4--
Compressor Calibration Method;
(xi) Section 7--Methods of Testing and Calculation, Section 7.5--
Refrigerant Enthalpy Method;
(xii) Section 7--Methods of Testing and Calculation, Section 7.7--
Airflow Rate Measurement, Section 7.7.2--Calculations--Nozzle Airflow
Measuring Apparatus (Excluding Figure 10), 7.7.2.1-7.7.2.2;
(xiii) Section 8--Test Procedures, Section 8.1--Test Room
Requirements: 8.1.2-8.1.3;
(xiv) Section 8--Test Procedures, Section 8.2--Equipment
Installation;
(xv) Section 8--Test Procedures, Section 8.6--Additional
Requirements for the Outdoor Air Enthalpy Method, Section 8.6.2;
(xvii) Section 8--Test Procedures, Section 8.6--Additional
Requirements for the Outdoor Air Enthalpy Method, Table 2a--Test
Tolerances (SI Units), and
(xviii) Section 8--Test Procedures, Section 8.6--Additional
Requirements for the Outdoor Air Enthalpy Method, Table 2b--Test
Tolerances (I-P Units);
(xix) Section 9--Data to be Recorded, Section 9.2--Test Tolerances;
and
(xx) Section 9--Data to be Recorded, Table 3--Data to be Recorded.
* * * * *
(7) ANSI/ASHRAE Standard 41.1-2013, (``ANSI/ASHRAE 41.1-2013''),
Standard Method for Temperature Measurement, ANSI approved January 30,
2013, IBR approved for appendix M to subpart B, as follows:
(i) Section 4--Classifications;
(ii) Section 5--Requirements, Section 5.3--Airstream Temperature
Measurements;
(iii) Section 6--Instruments; and
(iv) Section 7--Temperature Test Methods (Informative).
(8) ANSI/ASHRAE Standard 41.2-1987 (RA 1992), (``ASHRAE 41.2-1987
(RA 1992)''), Standard Methods for Laboratory Airflow Measurement, ANSI
reaffirmed April 20, 1992, Section 5--Section of Airflow-Measuring
Equipment and Systems, IBR approved for appendix M to subpart B, as
follows:
(i) Section 5.2--Test Ducts,, Section 5.2.2--Mixers, 5.2.2.1--
Performance of Mixers (excluding Figures 11 and 12 and Table 1); and
(ii) Figure 14--Outlet Chamber Setup for Multiple Nozzles in
Chamber.
(9) ANSI/ASHRAE Standard 41.6-2014, (``ASHRAE 41.6-2014''),
Standard Method for Humidity Measurement, ANSI approved July 3, 2014,
IBR approved for appendix M to subpart B, as follows:
(i) Section 4--Classifications;
(ii) Section 5--Requirements;
(iii) Section 6--Instruments and Calibration; and
(iv) Section 7--Humidity Measurement Methods.
(10) ANSI/ASHRAE 41.9-2011, (``ASHRAE 41.9-2011''), Standard
Methods for Volatile-Refrigerant Mass Flow Measurements Using
Calorimeters, ANSI approved February 3, 2011, IBR approved for appendix
M to subpart B, as follows:
(i) Section 5--Requirements;
(ii) Section 6--Instruments;
(iii) Section 7--Secondary Refrigerant Calorimeter Method;
(iv) Section 8--Secondary Fluid Calorimeter Method;
(v) Section 9--Primary Refrigerant Calorimeter Method; and
(vi) Section 11--Lubrication Circulation Measurements.
* * * * *
(13) ANSI/ASHRAE Standard 116-2010, (``ASHRAE 116-2010''), Methods
of Testing for Rating Seasonal Efficiency of Unitary Air Conditioners
and Heat Pumps, ANSI approved February 24, 2010, Section 7--Methods of
Test, Section 7.4--Air Enthalpy Method--Indoor Side (Primary Method),
Section 7.4.3--Measurements, Section 7.4.3.4--Temperature, Section
7.4.3.4.5, IBR approved for appendix M to subpart B.
* * * * *
0
9. Section 430.23 is amended by revising paragraph (m) to read as
follows:
Sec. 430.23 Test procedures for the measurement of energy and water
consumption.
* * * * *
(m) Central air conditioners and heat pumps. (1) Determine cooling
capacity must be determined from the steady-state wet-coil test (A or
A2 Test), as described in section 3.3 of appendix M to this subpart,
and round off:
(i) To the nearest 50 Btu/h if cooling capacity is less than 20,000
Btu/h,
(ii) To the nearest 100 Btu/h if cooling capacity is greater than
or equal to 20,000 Btu/h but less than 38,000 Btu/h, and
(iii) To the nearest 250 Btu/h if cooling capacity is greater than
or equal to 38,000 Btu/h and less than 65,000 Btu/h.
[[Page 37058]]
(2) Determine seasonal energy efficiency ratio (SEER) as described
in section 4.1 of appendix M to this subpart, and round off to the
nearest 0.025 Btu/W-h.
(3) Determine energy efficiency ratio (EER) as described in section
4.6 of appendix M to this subpart, and round off to the nearest 0.025
Btu/W-h.
(4) Determine heating seasonal performance factors (HSPF) as
described in section 4.2 of appendix M to this subpart, and round off
to the nearest 0.025 Btu/W-h.
(5) Determine average off mode power consumption as described in
section 4.3 of appendix M to this subpart, and round off to the nearest
0.5 W.
(6) Determine sensible heat ratio (SHR), as described in section
4.5 of appendix M to this subpart, and round off to the nearest 0.5
percent (%).
(7) Determine all other measures of energy efficiency or
consumption or other useful measures of performance using appendix M of
this subpart.
* * * * *
0
10. Appendix M to subpart B of part 430 is revised to read as follows:
Appendix M to Subpart B of Part 430--Uniform Test Method for Measuring
the Energy Consumption of Central Air Conditioners and Heat Pumps
Note: Prior to December 5, 2016, any representations, including
compliance certifications, made with respect to the energy use,
power, or efficiency of central air conditioners and central air
conditioning heat pumps must be based on the results of testing
pursuant to either this appendix or the procedures in Appendix M as
it appeared at 10 CFR part 430, subpart B, Appendix M, in the 10 CFR
parts 200 to 499 edition revised as of January 1, 2015. Any
representations made with respect to the energy use or efficiency of
such central air conditioners and central air conditioning heat
pumps must be in accordance with whichever version is selected.
On or after December 5, 2016 and prior to the compliance date
for any amended energy conservation standards, any representations,
including compliance certifications, made with respect to the energy
use, power, or efficiency of central air conditioners and central
air conditioning heat pumps must be based on the results of testing
pursuant to this appendix.
On or after the compliance date for any amended energy
conservation standards, any representations, including compliance
certifications, made with respect to the energy use, power, or
efficiency of central air conditioners and central air conditioning
heat pumps must be based on the results of testing pursuant to
appendix M1 of this subpart.
1. Scope and Definitions
1.1 Scope
This test procedure provides a method of determining SEER, EER,
HSPF and PW,OFF for central air conditioners and central
air conditioning heat pumps including the following categories:
(a) Split-system air conditioners, including single-split,
multi-head mini-split, multi-split (including VRF), and multi-
circuit systems
(b) Split-system heat pumps, including single-split, multi-head
mini-split, multi-split (including VRF), and multi-circuit systems
(c) Single-package air conditioners
(d) Single-package heat pumps
(e) Small-duct, high-velocity systems (including VRF)
(f) Space-constrained products--air conditioners
(g) Space-constrained products--heat pumps
For purposes of this appendix, the Department of Energy
incorporates by reference specific sections of several industry
standards, as listed in Sec. 430.3. In cases where there is a
conflict, the language of the test procedure in this appendix takes
precedence over the incorporated standards.
All section references refer to sections within this appendix
unless otherwise stated.
1.2 Definitions
Airflow-control settings are programmed or wired control system
configurations that control a fan to achieve discrete, differing
ranges of airflow--often designated for performing a specific
function (e.g., cooling, heating, or constant circulation)--without
manual adjustment other than interaction with a user-operable
control (i.e., a thermostat) that meets the manufacturer
specifications for installed-use. For the purposes of this appendix,
manufacturer specifications for installed-use are those found in the
product literature shipped with the unit.
Air sampling device is an assembly consisting of a manifold with
several branch tubes with multiple sampling holes that draws an air
sample from a critical location from the unit under test (e.g.
indoor air inlet, indoor air outlet, outdoor air inlet, etc.).
Airflow prevention device denotes a device that prevents airflow
via natural convection by mechanical means, such as an air damper
box, or by means of changes in duct height, such as an upturned
duct.
Aspirating psychrometer is a piece of equipment with a monitored
airflow section that draws uniform airflow through the measurement
section and has probes for measurement of air temperature and
humidity.
Blower coil indoor unit means an indoor unit either with an
indoor blower housed with the coil or with a separate designated air
mover such as a furnace or a modular blower (as defined in appendix
AA to the subpart).
Blower coil system refers to a split system that includes one or
more blower coil indoor units.
Cased coil means a coil-only indoor unit with external
cabinetry.
Coefficient of Performance (COP) means the ratio of the average
rate of space heating delivered to the average rate of electrical
energy consumed by the heat pump. These rate quantities must be
determined from a single test or, if derived via interpolation, must
be determined at a single set of operating conditions. COP is a
dimensionless quantity. When determined for a ducted coil-only
system, COP must include the sections 3.7 and 3.9.1 of this
appendix: default values for the heat output and power input of a
fan motor.
Coil-only indoor unit means an indoor unit that is distributed
in commerce without an indoor blower or separate designated air
mover. A coil-only indoor unit installed in the field relies on a
separately-installed furnace or a modular blower for indoor air
movement. Coil-only system refers to a system that includes only
(one or more) coil-only indoor units.
Condensing unit removes the heat absorbed by the refrigerant to
transfer it to the outside environment and consists of an outdoor
coil, compressor(s), and air moving device.
Constant-air-volume-rate indoor blower means a fan that varies
its operating speed to provide a fixed air-volume-rate from a ducted
system.
Continuously recorded, when referring to a dry bulb measurement,
dry bulb temperature used for test room control, wet bulb
temperature, dew point temperature, or relative humidity
measurements, means that the specified value must be sampled at
regular intervals that are equal to or less than 15 seconds.
Cooling load factor (CLF) means the ratio having as its
numerator the total cooling delivered during a cyclic operating
interval consisting of one ON period and one OFF period, and as its
denominator the total cooling that would be delivered, given the
same ambient conditions, had the unit operated continuously at its
steady-state, space-cooling capacity for the same total time (ON +
OFF) interval.
Crankcase heater means any electrically powered device or
mechanism for intentionally generating heat within and/or around the
compressor sump volume. Crankcase heater control may be achieved
using a timer or may be based on a change in temperature or some
other measurable parameter, such that the crankcase heater is not
required to operate continuously. A crankcase heater without
controls operates continuously when the compressor is not operating.
Cyclic Test means a test where the unit's compressor is cycled
on and off for specific time intervals. A cyclic test provides half
the information needed to calculate a degradation coefficient.
Damper box means a short section of duct having an air damper
that meets the performance requirements of section 2.5.7 of this
appendix.
Degradation coefficient (CD) means a parameter used
in calculating the part load factor. The degradation coefficient for
cooling is denoted by CD\c\. The degradation coefficient
for heating is denoted by CD\h\.
Demand-defrost control system means a system that defrosts the
heat pump outdoor coil-only when measuring a predetermined
degradation of performance. The heat pump's controls either:
(1) Monitor one or more parameters that always vary with the
amount of frost accumulated on the outdoor coil (e.g., coil to air
differential temperature, coil differential
[[Page 37059]]
air pressure, outdoor fan power or current, optical sensors) at
least once for every ten minutes of compressor ON-time when space
heating or
(2) Operate as a feedback system that measures the length of the
defrost period and adjusts defrost frequency accordingly. In all
cases, when the frost parameter(s) reaches a predetermined value,
the system initiates a defrost. In a demand-defrost control system,
defrosts are terminated based on monitoring a parameter(s) that
indicates that frost has been eliminated from the coil. (Note:
Systems that vary defrost intervals according to outdoor dry-bulb
temperature are not demand-defrost systems.) A demand-defrost
control system, which otherwise meets the above requirements, may
allow time-initiated defrosts if, and only if, such defrosts occur
after 6 hours of compressor operating time.
Design heating requirement (DHR) predicts the space heating load
of a residence when subjected to outdoor design conditions.
Estimates for the minimum and maximum DHR are provided for six
generalized U.S. climatic regions in section 4.2 of this appendix.
Dry-coil tests are cooling mode tests where the wet-bulb
temperature of the air supplied to the indoor unit is maintained low
enough that no condensate forms on the evaporator coil.
Ducted system means an air conditioner or heat pump that is
designed to be permanently installed equipment and delivers
conditioned air to the indoor space through a duct(s). The air
conditioner or heat pump may be either a split-system or a single-
package unit.
Energy efficiency ratio (EER) means the ratio of the average
rate of space cooling delivered to the average rate of electrical
energy consumed by the air conditioner or heat pump. These rate
quantities must be determined from a single test or, if derived via
interpolation, must be determined at a single set of operating
conditions. EER is expressed in units of Btu/h. When determined for
a ducted coil-only system, EER must include, from this appendix, the
section 3.3 and 3.5.1 default values for the heat output and power
input of a fan motor.
Evaporator coil means an assembly that absorbs heat from an
enclosed space and transfers the heat to a refrigerant.
Heat pump means a kind of central air conditioner that utilizes
an indoor conditioning coil, compressor, and refrigerant-to-outdoor
air heat exchanger to provide air heating, and may also provide air
cooling, air dehumidifying, air humidifying, air circulating, and
air cleaning.
Heat pump having a heat comfort controller means a heat pump
with controls that can regulate the operation of the electric
resistance elements to assure that the air temperature leaving the
indoor section does not fall below a specified temperature. Heat
pumps that actively regulate the rate of electric resistance heating
when operating below the balance point (as the result of a second
stage call from the thermostat) but do not operate to maintain a
minimum delivery temperature are not considered as having a heat
comfort controller.
Heating load factor (HLF) means the ratio having as its
numerator the total heating delivered during a cyclic operating
interval consisting of one ON period and one OFF period, and its
denominator the heating capacity measured at the same test
conditions used for the cyclic test, multiplied by the total time
interval (ON plus OFF) of the cyclic-test.
Heating season means the months of the year that require
heating, e.g., typically, and roughly, October through April.
Heating seasonal performance factor (HSPF) means the total space
heating required during the heating season, expressed in Btu's,
divided by the total electrical energy consumed by the heat pump
system during the same season, expressed in watt-hours. The HSPF
used to evaluate compliance with 10 CFR 430.32(c) is based on Region
IV, the minimum standardized design heating requirement, and the
sampling plan stated in 10 CFR 429.16(a).
Independent coil manufacturer (ICM) means a manufacturer that
manufactures indoor units but does not manufacture single-package
units or outdoor units.
Indoor unit means a separate assembly of a split system that
includes--
(1) An arrangement of refrigerant-to-air heat transfer coil(s)
for transfer of heat between the refrigerant and the indoor air,
(2) A condensate drain pan, and may or may not include
(3) Sheet metal or plastic parts not part of external cabinetry
to direct/route airflow over the coil(s),
(4) A cooling mode expansion device,
(5) External cabinetry, and
(6) An integrated indoor blower (i.e. a device to move air
including its associated motor). A separate designated air mover
that may be a furnace or a modular blower (as defined in appendix AA
to the subpart) may be considered to be part of the indoor unit. A
service coil is not an indoor unit.
Multi-head mini-split system means a split system that has one
outdoor unit and that has two or more indoor units connected with a
single refrigeration circuit. The indoor units operate in unison in
response to a single indoor thermostat.
Multiple-circuit (or multi-circuit) system means a split system
that has one outdoor unit and that has two or more indoor units
installed on two or more refrigeration circuits such that each
refrigeration circuit serves a compressor and one and only one
indoor unit, and refrigerant is not shared from circuit to circuit.
Multiple-split (or multi-split) system means a split system that
has one outdoor unit and two or more coil-only indoor units and/or
blower coil indoor units connected with a single refrigerant
circuit. The indoor units operate independently and can condition
multiple zones in response to at least two indoor thermostats or
temperature sensors. The outdoor unit operates in response to
independent operation of the indoor units based on control input of
multiple indoor thermostats or temperature sensors, and/or based on
refrigeration circuit sensor input (e.g., suction pressure).
Nominal capacity means the capacity that is claimed by the
manufacturer on the product name plate. Nominal cooling capacity is
approximate to the air conditioner cooling capacity tested at A or
A2 condition. Nominal heating capacity is approximate to the heat
pump heating capacity tested in H12 test (or the optional H1N test).
Non-ducted indoor unit means an indoor unit that is designed to
be permanently installed, mounted on room walls and/or ceilings, and
that directly heats or cools air within the conditioned space.
Normalized Gross Indoor Fin Surface (NGIFS) means the gross fin
surface area of the indoor unit coil divided by the cooling capacity
measured for the A or A2 Test, whichever applies.
Off-mode power consumption means the power consumption when the
unit is connected to its main power source but is neither providing
cooling nor heating to the building it serves.
Off-mode season means, for central air conditioners other than
heat pumps, the shoulder season and the entire heating season; and
for heat pumps, the shoulder season only.
Outdoor unit means a separate assembly of a split system that
transfers heat between the refrigerant and the outdoor air, and
consists of an outdoor coil, compressor(s), an air moving device,
and in addition for heat pumps, may include a heating mode expansion
device, reversing valve, and/or defrost controls.
Outdoor unit manufacturer (OUM) means a manufacturer of single-
package units, outdoor units, and/or both indoor units and outdoor
units.
Part-load factor (PLF) means the ratio of the cyclic EER (or COP
for heating) to the steady-state EER (or COP), where both EERs (or
COPs) are determined based on operation at the same ambient
conditions.
Seasonal energy efficiency ratio (SEER) means the total heat
removed from the conditioned space during the annual cooling season,
expressed in Btu's, divided by the total electrical energy consumed
by the central air conditioner or heat pump during the same season,
expressed in watt-hours.
Service coil means an arrangement of refrigerant-to-air heat
transfer coil(s), condensate drain pan, sheet metal or plastic parts
to direct/route airflow over the coil(s), which may or may not
include external cabinetry and/or a cooling mode expansion device,
distributed in commerce solely for the intent of replacing an
uncased coil or cased coil that has already been placed into
service, and that has been labeled accordingly by the manufacturer.
Shoulder season means the months of the year in between those
months that require cooling and those months that require heating,
e.g., typically, and roughly, April through May, and September
through October.
Single-package unit means any central air conditioner or heat
pump that has all major assemblies enclosed in one cabinet.
Single-split system means a split system that has one outdoor
unit and one indoor unit connected with a single refrigeration
circuit. Small-duct, high-velocity system means a split system for
which all indoor units are blower coil indoor units that produce at
least 1.2 inches (of water column) of external static pressure when
operated at
[[Page 37060]]
the full-load air volume rate certified by the manufacturer of at
least 220 scfm per rated ton of cooling.
Split system means any air conditioner or heat pump that has at
least two separate assemblies that are connected with refrigerant
piping when installed. One of these assemblies includes an indoor
coil that exchanges heat with the indoor air to provide heating or
cooling, while one of the others includes an outdoor coil that
exchanges heat with the outdoor air. Split systems may be either
blower coil systems or coil-only systems.
Standard Air means dry air having a mass density of 0.075 lb/
ft\3\.
Steady-state test means a test where the test conditions are
regulated to remain as constant as possible while the unit operates
continuously in the same mode.
Temperature bin means the 5 [deg]F increments that are used to
partition the outdoor dry-bulb temperature ranges of the cooling
(>=65 [deg]F) and heating (<65 [deg]F) seasons.
Test condition tolerance means the maximum permissible
difference between the average value of the measured test parameter
and the specified test condition.
Test operating tolerance means the maximum permissible range
that a measurement may vary over the specified test interval. The
difference between the maximum and minimum sampled values must be
less than or equal to the specified test operating tolerance.
Tested combination means a multi-head mini-split, multi-split,
or multi-circuit system having the following features:
(1) The system consists of one outdoor unit with one or more
compressors matched with between two and five indoor units;
(2) The indoor units must:
(i) Collectively, have a nominal cooling capacity greater than
or equal to 95 percent and less than or equal to 105 percent of the
nominal cooling capacity of the outdoor unit;
(ii) Each represent the highest sales volume model family, if
this is possible while meeting all the requirements of this section.
If this is not possible, one or more of the indoor units may
represent another indoor model family in order that all the other
requirements of this section are met.
(iii) Individually not have a nominal cooling capacity greater
than 50 percent of the nominal cooling capacity of the outdoor unit,
unless the nominal cooling capacity of the outdoor unit is 24,000
Btu/h or less;
(iv) Operate at fan speeds consistent with manufacturer's
specifications; and
(v) All be subject to the same minimum external static pressure
requirement while able to produce the same external static pressure
at the exit of each outlet plenum when connected in a manifold
configuration as required by the test procedure.
(3) Where referenced, ``nominal cooling capacity'' means, for
indoor units, the highest cooling capacity listed in published
product literature for 95 [deg]F outdoor dry bulb temperature and 80
[deg]F dry bulb, 67 [deg]F wet bulb indoor conditions, and for
outdoor units, the lowest cooling capacity listed in published
product literature for these conditions. If incomplete or no
operating conditions are published, the highest (for indoor units)
or lowest (for outdoor units) such cooling capacity available for
sale must be used.
Time-adaptive defrost control system is a demand-defrost control
system that measures the length of the prior defrost period(s) and
uses that information to automatically determine when to initiate
the next defrost cycle.
Time-temperature defrost control systems initiate or evaluate
initiating a defrost cycle only when a predetermined cumulative
compressor ON-time is obtained. This predetermined ON-time is
generally a fixed value (e.g., 30, 45, 90 minutes) although it may
vary based on the measured outdoor dry-bulb temperature. The ON-time
counter accumulates if controller measurements (e.g., outdoor
temperature, evaporator temperature) indicate that frost formation
conditions are present, and it is reset/remains at zero at all other
times. In one application of the control scheme, a defrost is
initiated whenever the counter time equals the predetermined ON-
time. The counter is reset when the defrost cycle is completed.
In a second application of the control scheme, one or more
parameters are measured (e.g., air and/or refrigerant temperatures)
at the predetermined, cumulative, compressor ON-time. A defrost is
initiated only if the measured parameter(s) falls within a
predetermined range. The ON-time counter is reset regardless of
whether or not a defrost is initiated. If systems of this second
type use cumulative ON-time intervals of 10 minutes or less, then
the heat pump may qualify as having a demand defrost control system
(see definition).
Triple-capacity, northern heat pump means a heat pump that
provides two stages of cooling and three stages of heating. The two
common stages for both the cooling and heating modes are the low
capacity stage and the high capacity stage. The additional heating
mode stage is the booster capacity stage, which offers the highest
heating capacity output for a given set of ambient operating
conditions.
Triple-split system means a split system that is composed of
three separate assemblies: An outdoor fan coil section, a blower
coil indoor unit, and an indoor compressor section.
Two-capacity (or two-stage) compressor system means a central
air conditioner or heat pump that has a compressor or a group of
compressors operating with only two stages of capacity. For such
systems, low capacity means the compressor(s) operating at low
stage, or at low load test conditions. The low compressor stage that
operates for heating mode tests may be the same or different from
the low compressor stage that operates for cooling mode tests. For
such systems, high capacity means the compressor(s) operating at
high stage, or at full load test conditions.
Two-capacity, northern heat pump means a heat pump that has a
factory or field-selectable lock-out feature to prevent space
cooling at high-capacity. Two-capacity heat pumps having this
feature will typically have two sets of ratings, one with the
feature disabled and one with the feature enabled. The heat pump is
a two-capacity northern heat pump only when this feature is enabled
at all times. The certified indoor coil model number must reflect
whether the ratings pertain to the lockout enabled option via the
inclusion of an extra identifier, such as ``+LO''. When testing as a
two-capacity, northern heat pump, the lockout feature must remain
enabled for all tests.
Uncased coil means a coil-only indoor unit without external
cabinetry.
Variable refrigerant flow (VRF) system means a multi-split
system with at least three compressor capacity stages, distributing
refrigerant through a piping network to multiple indoor blower coil
units each capable of individual zone temperature control, through
proprietary zone temperature control devices and a common
communications network. Note: Single-phase VRF systems less than
65,000 Btu/h are central air conditioners and central air
conditioning heat pumps.
Variable-speed compressor system means a central air conditioner
or heat pump that has a compressor that uses a variable-speed drive
to vary the compressor speed to achieve variable capacities.
Wet-coil test means a test conducted at test conditions that
typically cause water vapor to condense on the test unit evaporator
coil.
2. Testing Overview and Conditions
(A) Test VRF systems using AHRI 1230-2010 (incorporated by
reference, see Sec. 430.3) and appendix M. Where AHRI 1230-2010
refers to the appendix C therein substitute the provisions of this
appendix. In cases where there is a conflict, the language of the
test procedure in this appendix takes precedence over AHRI 1230-
2010.
For definitions use section 1 of appendix M and section 3 of
AHRI 1230-2010 (incorporated by reference, see Sec. 430.3). For
rounding requirements, refer to Sec. 430.23(m). For determination
of certified ratings, refer to Sec. 429.16 of this chapter.
For test room requirements, refer to section 2.1 of this
appendix. For test unit installation requirements refer to sections
2.2.a, 2.2.b, 2.2.c, 2.2.1, 2.2.2, 2.2.3(a), 2.2.3(c), 2.2.4, 2.2.5,
and 2.4 to 2.12 of this appendix, and sections 5.1.3 and 5.1.4 of
AHRI 1230-2010. The ``manufacturer's published instructions,'' as
stated in section 8.2 of ANSI/ASHRAE 37-2009 (incorporated by
reference, see Sec. 430.3) and ``manufacturer's installation
instructions'' discussed in this appendix mean the manufacturer's
installation instructions that come packaged with or appear in the
labels applied to the unit. This does not include online manuals.
Installation instructions that appear in the labels applied to the
unit take precedence over installation instructions that are shipped
with the unit.
For general requirements for the test procedure, refer to
section 3.1 of this appendix, except for sections 3.1.3 and 3.1.4,
which are requirements for indoor air volume and outdoor air volume.
For indoor air volume and outdoor air volume requirements, refer
instead to section 6.1.5 (except where section 6.1.5 refers to Table
8, refer instead to Table 3 of this appendix) and 6.1.6 of AHRI
1230-2010.
For the test method, refer to sections 3.3 to 3.5 and 3.7 to
3.13 of this appendix. For cooling mode and heating mode test
[[Page 37061]]
conditions, refer to section 6.2 of AHRI 1230-2010. For calculations
of seasonal performance descriptors, refer to section 4 of this
appendix.
(B) For systems other than VRF, only a subset of the sections
listed in this test procedure apply when testing and determining
represented values for a particular unit. Table 1 shows the sections
of the test procedure that apply to each system. This table is meant
to assist manufacturers in finding the appropriate sections of the
test procedure; the appendix sections rather than the table provide
the specific requirements for testing, and given the varied nature
of available units, manufacturers are responsible for determining
which sections apply to each unit tested based on the unit's
characteristics. To use this table, first refer to the sections
listed under ``all units''. Then refer to additional requirements
based on:
(1) System configuration(s),
(2) The compressor staging or modulation capability, and
(3) Any special features.
Testing requirements for space-constrained products do not
differ from similar equipment that is not space-constrained and thus
are not listed separately in this table. Air conditioners and heat
pumps are not listed separately in this table, but heating
procedures and calculations apply only to heat pumps.
Table 1--Informative Guidance for Using Appendix M
[[Page 37062]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.004
[[Page 37063]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.005
[[Page 37064]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.006
[[Page 37065]]
2.1 Test Room Requirements
a. Test using two side-by-side rooms: An indoor test room and an
outdoor test room. For multiple-split, single-zone-multi-coil or
multi-circuit air conditioners and heat pumps, however, use as many
indoor test rooms as needed to accommodate the total number of
indoor units. These rooms must comply with the requirements
specified in sections 8.1.2 and 8.1.3 of ANSI/ASHRAE 37-2009
(incorporated by reference, see Sec. 430.3).
b. Inside these test rooms, use artificial loads during cyclic
tests and frost accumulation tests, if needed, to produce stabilized
room air temperatures. For one room, select an electric resistance
heater(s) having a heating capacity that is approximately equal to
the heating capacity of the test unit's condenser. For the second
room, select a heater(s) having a capacity that is close to the
sensible cooling capacity of the test unit's evaporator. Cycle the
heater located in the same room as the test unit evaporator coil ON
and OFF when the test unit cycles ON and OFF. Cycle the heater
located in the same room as the test unit condensing coil ON and OFF
when the test unit cycles OFF and ON.
2.2 Test Unit Installation Requirements
a. Install the unit according to section 8.2 of ANSI/ASHRAE 37-
2009 (incorporated by reference, see Sec. 430.3), subject to the
following additional requirements:
(1) When testing split systems, follow the requirements given in
section 6.1.3.5 of AHRI 210/240-2008 (incorporated by reference, see
Sec. 430.3). For the vapor refrigerant line(s), use the insulation
included with the unit; if no insulation is provided, use insulation
meeting the specifications for the insulation in the installation
instructions included with the unit by the manufacturer; if no
insulation is included with the unit and the installation
instructions do not contain provisions for insulating the line(s),
fully insulate the vapor refrigerant line(s) with vapor proof
insulation having an inside diameter that matches the refrigerant
tubing and a nominal thickness of at least 0.5 inches. For the
liquid refrigerant line(s), use the insulation included with the
unit; if no insulation is provided, use insulation meeting the
specifications for the insulation in the installation instructions
included with the unit by the manufacturer; if no insulation is
included with the unit and the installation instructions do not
contain provisions for insulating the line(s), leave the liquid
refrigerant line(s) exposed to the air for air conditioners and heat
pumps that heat and cool; or, for heating-only heat pumps, insulate
the liquid refrigerant line(s) with insulation having an inside
diameter that matches the refrigerant tubing and a nominal thickness
of at least 0.5 inches. Insulation must be the same for the cooling
and heating tests.
(2) When testing split systems, if the indoor unit does not ship
with a cooling mode expansion device, test the system using the
device as specified in the installation instructions provided with
the indoor unit. If none is specified, test the system using a fixed
orifice or piston type expansion device that is sized appropriately
for the system.
(3) When testing triple-split systems (see section 1.2 of this
appendix, Definitions), use the tubing length specified in section
6.1.3.5 of AHRI 210/240-2008 (incorporated by reference, see Sec.
430.3) to connect the outdoor coil, indoor compressor section, and
indoor coil while still meeting the requirement of exposing 10 feet
of the tubing to outside conditions;
(4) When testing split systems having multiple indoor coils,
connect each indoor blower coil unit to the outdoor unit using:
(a) 25 feet of tubing, or
(b) tubing furnished by the manufacturer, whichever is longer.
At least 10 feet of the system interconnection tubing shall be
exposed to the outside conditions. If they are needed to make a
secondary measurement of capacity or for verification of refrigerant
charge, install refrigerant pressure measuring instruments as
described in section 8.2.5 of ANSI/ASHRAE 37-2009 (incorporated by
reference, see Sec. 430.3). Section 2.10 of this appendix specifies
which secondary methods require refrigerant pressure measurements
and section 2.2.5.5 of this appendix discusses use of pressure
measurements to verify charge. At a minimum, insulate the low-
pressure line(s) of a split system with insulation having an inside
diameter that matches the refrigerant tubing and a nominal thickness
of 0.5 inch.
b. For units designed for both horizontal and vertical
installation or for both up-flow and down-flow vertical
installations, use the orientation for testing specified by the
manufacturer in the certification report. Conduct testing with the
following installed:
(1) The most restrictive filter(s);
(2) Supplementary heating coils; and
(3) Other equipment specified as part of the unit, including all
hardware used by a heat comfort controller if so equipped (see
section 1 of this appendix, Definitions). For small-duct, high-
velocity systems, configure all balance dampers or restrictor
devices on or inside the unit to fully open or lowest restriction.
c. Testing a ducted unit without having an indoor air filter
installed is permissible as long as the minimum external static
pressure requirement is adjusted as stated in Table 3, note 3 (see
section 3.1.4 of this appendix). Except as noted in section 3.1.10
of this appendix, prevent the indoor air supplementary heating coils
from operating during all tests. For uncased coils, create an
enclosure using 1 inch fiberglass foil-faced ductboard having a
nominal density of 6 pounds per cubic foot. Or alternatively,
construct an enclosure using sheet metal or a similar material and
insulating material having a thermal resistance (``R'' value)
between 4 and 6 hr[middot]ft\2\[middot] [deg]F/Btu. Size the
enclosure and seal between the coil and/or drainage pan and the
interior of the enclosure as specified in installation instructions
shipped with the unit. Also seal between the plenum and inlet and
outlet ducts. For cased coils, no extra insulating or sealing is
allowed.
d. When testing a coil-only system, install a toroidal-type
transformer to power the system's low-voltage components, complying
with any additional requirements for the transformer mentioned in
the installation manuals included with the unit by the system
manufacturer. If the installation manuals do not provide
specifications for the transformer, use a transformer having the
following features:
(1) A nominal volt-amp rating such that the transformer is
loaded between 25 and 90 percent of this rating for the highest
level of power measured during the off mode test (section 3.13 of
this appendix);
(2) Designed to operate with a primary input of 230 V, single
phase, 60 Hz; and
(3) That provides an output voltage that is within the specified
range for each low-voltage component. Include the power consumption
of the components connected to the transformer as part of the total
system power consumption during the off mode tests; do not include
the power consumed by the transformer when no load is connected to
it.
e. Test an outdoor unit with no match (i.e., that is not
distributed in commerce with any indoor units) using a coil-only
indoor unit with a single cooling air volume rate whose coil has:
(1) Round tubes of outer diameter no less than 0.375 inches, and
(2) a normalized gross indoor fin surface (NGIFS) no greater
than 1.0 square inches per British thermal unit per hour (sq. in./
Btu/hr). NGIFS is calculated as follows:
NGIFS = 2 x Lf x Wf x Nf /
Qc (95)
Where:
Lf = Indoor coil fin length in inches, also height of the
coil transverse to the tubes.
Wf = Indoor coil fin width in inches, also depth of the
coil.
Nf = Number of fins.
Qc(95) = the measured space cooling capacity of the
tested outdoor unit/indoor unit combination as determined from the
A2 or A Test whichever applies, Btu/h.
f If the outdoor unit or the outdoor portion of a single-package
unit has a drain pan heater to prevent freezing of defrost water,
the heater shall be energized, subject to control to de-energize it
when not needed by the heater's thermostat or the unit's control
system, for all tests.
2.2.1 Defrost Control Settings
Set heat pump defrost controls at the normal settings which most
typify those encountered in generalized climatic region IV. (Refer
to Figure 1 and Table 19 of section 4.2 of this appendix for
information on region IV.) For heat pumps that use a time-adaptive
defrost control system (see section 1.2 of this appendix,
Definitions), the manufacturer must specify in the certification
report the frosting interval to be used during frost accumulation
tests and provide the procedure for manually initiating the defrost
at the specified time.
2.2.2 Special Requirements for Units Having a Multiple-Speed Outdoor
Fan
Configure the multiple-speed outdoor fan according to the
installation manual included with the unit by the manufacturer, and
thereafter, leave it unchanged for all tests. The controls of the
unit must regulate the operation of the outdoor fan during all lab
tests except dry coil cooling mode tests. For dry coil cooling mode
tests, the outdoor fan
[[Page 37066]]
must operate at the same speed used during the required wet coil
test conducted at the same outdoor test conditions.
2.2.3 Special Requirements for Multi-Split Air Conditioners and Heat
Pumps and Ducted Systems Using a Single Indoor Section Containing
Multiple Indoor Blowers That Would Normally Operate Using Two or More
Indoor Thermostats
Because these systems will have more than one indoor blower and
possibly multiple outdoor fans and compressor systems, references in
this test procedure to a singular indoor blower, outdoor fan, and/or
compressor means all indoor blowers, all outdoor fans, and all
compressor systems that are energized during the test.
a. Additional requirements for multi-split air conditioners and
heat pumps. For any test where the system is operated at part load
(i.e., one or more compressors ``off'', operating at the
intermediate or minimum compressor speed, or at low compressor
capacity), the manufacturer must designate in the certification
report the indoor coil(s) that are not providing heating or cooling
during the test such that the sum of the nominal heating or cooling
capacity of the operational indoor units is within 5 percent of the
intended part load heating or cooling capacity. For variable-speed
systems, the manufacturer must designate in the certification report
at least one indoor unit that is not providing heating or cooling
for all tests conducted at minimum compressor speed. For all other
part-load tests, the manufacturer must choose to turn off zero, one,
two, or more indoor units. The chosen configuration must remain
unchanged for all tests conducted at the same compressor speed/
capacity. For any indoor coil that is not providing heating or
cooling during a test, cease forced airflow through this indoor coil
and block its outlet duct.
b. Additional requirements for ducted split systems with a
single indoor unit containing multiple indoor blowers (or for
single-package units with an indoor section containing multiple
indoor blowers) where the indoor blowers are designed to cycle on
and off independently of one another and are not controlled such
that all indoor blowers are modulated to always operate at the same
air volume rate or speed. For any test where the system is operated
at its lowest capacity--i.e., the lowest total air volume rate
allowed when operating the single-speed compressor or when operating
at low compressor capacity--indoor blowers accounting for at least
one-third of the full-load air volume rate must be turned off unless
prevented by the controls of the unit. In such cases, turn off as
many indoor blowers as permitted by the unit's controls. Where more
than one option exists for meeting this ``off'' requirement, the
manufacturer shall indicate in its certification report which indoor
blower(s) are turned off. The chosen configuration shall remain
unchanged for all tests conducted at the same lowest capacity
configuration. For any indoor coil turned off during a test, cease
forced airflow through any outlet duct connected to a switched-off
indoor blower.
c. For test setups where the laboratory's physical limitations
requires use of more than the required line length of 25 feet as
listed in section 2.2.a(4) of this appendix, then the actual
refrigerant line length used by the laboratory may exceed the
required length and the refrigerant line length correction factors
in Table 4 of AHRI 1230-2010 are applied to the cooling capacity
measured for each cooling mode test.
2.2.4 Wet-Bulb Temperature Requirements for the Air Entering the Indoor
and Outdoor Coils
2.2.4.1 Cooling Mode Tests
For wet-coil cooling mode tests, regulate the water vapor
content of the air entering the indoor unit so that the wet-bulb
temperature is as listed in Tables 4 to 7. As noted in these same
tables, achieve a wet-bulb temperature during dry-coil cooling mode
tests that results in no condensate forming on the indoor coil.
Controlling the water vapor content of the air entering the outdoor
side of the unit is not required for cooling mode tests except when
testing:
(1) Units that reject condensate to the outdoor coil during wet
coil tests. Tables 4-7 list the applicable wet-bulb temperatures.
(2) Single-package units where all or part of the indoor section
is located in the outdoor test room. The average dew point
temperature of the air entering the outdoor coil during wet coil
tests must be within 3.0 [deg]F of the average dew point
temperature of the air entering the indoor coil over the 30-minute
data collection interval described in section 3.3 of this appendix.
For dry coil tests on such units, it may be necessary to limit the
moisture content of the air entering the outdoor coil of the unit to
meet the requirements of section 3.4 of this appendix.
2.2.4.2 Heating Mode Tests
For heating mode tests, regulate the water vapor content of the
air entering the outdoor unit to the applicable wet-bulb temperature
listed in Tables 11 to 14. The wet-bulb temperature entering the
indoor side of the heat pump must not exceed 60 [deg]F.
Additionally, if the Outdoor Air Enthalpy test method (section
2.10.1 of this appendix) is used while testing a single-package heat
pump where all or part of the outdoor section is located in the
indoor test room, adjust the wet-bulb temperature for the air
entering the indoor side to yield an indoor-side dew point
temperature that is as close as reasonably possible to the dew point
temperature of the outdoor-side entering air.
2.2.5 Additional Refrigerant Charging Requirements
2.2.5.1 Instructions To Use for Charging
a. Where the manufacturer's installation instructions contain
two sets of refrigerant charging criteria, one for field
installations and one for lab testing, use the field installation
criteria.
b. For systems consisting of an outdoor unit manufacturer's
outdoor section and indoor section with differing charging
procedures, adjust the refrigerant charge per the outdoor
installation instructions.
c. For systems consisting of an outdoor unit manufacturer's
outdoor unit and an independent coil manufacturer's indoor unit with
differing charging procedures, adjust the refrigerant charge per the
indoor unit's installation instructions. If instructions are
provided only with the outdoor unit or are provided only with an
independent coil manufacturer's indoor unit, then use the provided
instructions.
2.2.5.2 Test(s) To Use for Charging
a. Use the tests or operating conditions specified in the
manufacturer's installation instructions for charging. The
manufacturer's installation instructions may specify use of tests
other than the A or A2 test for charging, but, unless the
unit is a heating-only heat pump, the air volume rate must be
determined by the A or A2 test as specified in section
3.1 of this appendix.
b. If the manufacturer's installation instructions do not
specify a test or operating conditions for charging or there are no
manufacturer's instructions, use the following test(s):
(1) For air conditioners or cooling and heating heat pumps, use
the A or A2 test.
(2) For cooling and heating heat pumps that do not operate in
the H1 or H12 test (e.g., due to shut down by the unit
limiting devices) when tested using the charge determined at the A
or A2 test, and for heating-only heat pumps, use the H1
or H12 test.
2.2.5.3 Parameters To Set and Their Target Values
a. Consult the manufacturer's installation instructions
regarding which parameters (e.g., superheat) to set and their target
values. If the instructions provide ranges of values, select target
values equal to the midpoints of the provided ranges.
b. In the event of conflicting information between charging
instructions (i.e., multiple conditions given for charge adjustment
where all conditions specified cannot be met), follow the following
hierarchy.
(1) For fixed orifice systems:
(i) Superheat
(ii) High side pressure or corresponding saturation or dew-point
temperature
(iii) Low side pressure or corresponding saturation or dew-point
temperature
(iv) Low side temperature
(v) High side temperature
(vi) Charge weight
(2) For expansion valve systems:
(i) Subcooling
(ii) High side pressure or corresponding saturation or dew-point
temperature
(iii) Low side pressure or corresponding saturation or dew-point
temperature
(iv) Approach temperature (difference between temperature of
liquid leaving condenser and condenser average inlet air
temperature)
(v) Charge weight
c. If there are no installation instructions and/or they do not
provide parameters and target values, set superheat to a target
value of 12 [deg]F for fixed orifice systems or set subcooling to a
target value of 10 [deg]F for expansion valve systems.
2.2.5.4 Charging Tolerances
a. If the manufacturer's installation instructions specify
tolerances on target values for the charging parameters, set the
values within these tolerances.
[[Page 37067]]
b. Otherwise, set parameter values within the following test
condition tolerances for the different charging parameters:
(1) Superheat: +/- 2.0 [deg]F
(2) Subcooling: +/- 2.0 [deg]F
(3) High side pressure or corresponding saturation or dew point
temperature: +/- 4.0 psi or +/- 1.0 [deg]F
(4) Low side pressure or corresponding saturation or dew point
temperature: +/- 2.0 psi or +/- 0.8 [deg]F
(5) High side temperature: +/- 2.0 [deg]F
(6) Low side temperature: +/- 2.0 [deg]F
(7) Approach temperature: +/- 1.0 [deg]F
(8) Charge weight: +/- 2.0 ounce
2.2.5.5 Special Charging Instructions
a. Cooling and Heating Heat Pumps
If, using the initial charge set in the A or A2 test,
the conditions are not within the range specified in manufacturer's
installation instructions for the H1 or H12 test, make as
small as possible an adjustment to obtain conditions for this test
in the specified range. After this adjustment, recheck conditions in
the A or A2 test to confirm that they are still within
the specified range for the A or A2 test.
b. Single-Package Systems
Unless otherwise directed by the manufacturer's installation
instructions, install one or more refrigerant line pressure gauges
during the setup of the unit, located depending on the parameters
used to verify or set charge, as described:
(1) Install a pressure gauge at the location of the service
valve on the liquid line if charging is on the basis of subcooling,
or high side pressure or corresponding saturation or dew point
temperature;
(2) Install a pressure gauge at the location of the service
valve on the suction line if charging is on the basis of superheat,
or low side pressure or corresponding saturation or dew point
temperature.
Use methods for installing pressure gauge(s) at the required
location(s) as indicated in manufacturer's instructions if
specified.
2.2.5.6 Near-Azeotropic and Zeotropic Refrigerants
Perform charging of near-azeotropic and zeotropic refrigerants
only with refrigerant in the liquid state.
2.2.5.7 Adjustment of Charge Between Tests
After charging the system as described in this test procedure,
use the set refrigerant charge for all tests used to determine
performance. Do not adjust the refrigerant charge at any point
during testing. If measurements indicate that refrigerant charge has
leaked during the test, repair the refrigerant leak, repeat any
necessary set-up steps, and repeat all tests.
2.3 Indoor Air Volume Rates
If a unit's controls allow for overspeeding the indoor blower
(usually on a temporary basis), take the necessary steps to prevent
overspeeding during all tests.
2.3.1 Cooling Tests
a. Set indoor blower airflow-control settings (e.g., fan motor
pin settings, fan motor speed) according to the requirements that
are specified in section 3.1.4 of this appendix.
b. Express the Cooling full-load air volume rate, the Cooling
Minimum Air Volume Rate, and the Cooling Intermediate Air Volume
Rate in terms of standard air.
2.3.2 Heating Tests
a. Set indoor blower airflow-control settings (e.g., fan motor
pin settings, fan motor speed) according to the requirements that
are specified in section 3.1.4 of this appendix.
b. Express the heating full-load air volume rate, the heating
minimum air volume rate, the heating intermediate air volume rate,
and the heating nominal air volume rate in terms of standard air.
2.4 Indoor Coil Inlet and Outlet Duct Connections
Insulate and/or construct the outlet plenum as described in
section 2.4.1 of this appendix and, if installed, the inlet plenum
described in section 2.4.2 of this appendix with thermal insulation
having a nominal overall resistance (R-value) of at least 19 hr
ft\2\ [deg]F/Btu.
2.4.1 Outlet Plenum for the Indoor Unit
a. Attach a plenum to the outlet of the indoor coil. (Note: For
some packaged systems, the indoor coil may be located in the outdoor
test room.)
b. For systems having multiple indoor coils, or multiple indoor
blowers within a single indoor section, attach a plenum to each
indoor coil or indoor blower outlet. In order to reduce the number
of required airflow measurement apparati (section 2.6 of this
appendix), each such apparatus may serve multiple outlet plenums
connected to a single common duct leading to the apparatus. More
than one indoor test room may be used, which may use one or more
common ducts leading to one or more airflow measurement apparati
within each test room that contains multiple indoor coils. At the
plane where each plenum enters a common duct, install an adjustable
airflow damper and use it to equalize the static pressure in each
plenum. Each outlet air temperature grid (section 2.5.4 of this
appendix) and airflow measuring apparatus are located downstream of
the inlet(s) to the common duct. For multiple-circuit (or multi-
circuit) systems for which each indoor coil outlet is measured
separately and its outlet plenum is not connected to a common duct
connecting multiple outlet plenums, the outlet air temperature grid
and airflow measuring apparatus must be installed at each outlet
plenum.
c. For small-duct, high-velocity systems, install an outlet
plenum that has a diameter that is equal to or less than the value
listed in Table 2. The limit depends only on the Cooling full-load
air volume rate (see section 3.1.4.1.1 of this appendix) and is
effective regardless of the flange dimensions on the outlet of the
unit (or an air supply plenum adapter accessory, if installed in
accordance with the manufacturer's installation instructions).
d. Add a static pressure tap to each face of the (each) outlet
plenum, if rectangular, or at four evenly distributed locations
along the circumference of an oval or round plenum. Create a
manifold that connects the four static pressure taps. Figure 9 of
ANSI/ASHRAE 37-2009 (incorporated by reference, see Sec. 430.3)
shows allowed options for the manifold configuration. The cross-
sectional dimensions of plenum shall be equal to the dimensions of
the indoor unit outlet. See Figures 7a, 7b, and 7c of ANSI/ASHRAE
37-2009 for the minimum length of the (each) outlet plenum and the
locations for adding the static pressure taps for ducted blower coil
indoor units and single-package systems. See Figure 8 of ANSI/ASHRAE
37-2009 for coil-only indoor units.
Table 2--Size of Outlet Plenum for Small-Duct High-Velocity Indoor Units
------------------------------------------------------------------------
Maximum
diameter* of
Cooling full-load air volume rate (scfm) outlet plenum
(inches)
------------------------------------------------------------------------
<=500................................................... 6
501 to 700.............................................. 7
701 to 900.............................................. 8
901 to 1100............................................. 9
1101 to 1400............................................ 10
1401 to 1750............................................ 11
------------------------------------------------------------------------
* If the outlet plenum is rectangular, calculate its equivalent diameter
using (4A/P,) where A is the cross-sectional area and P is the
perimeter of the rectangular plenum, and compare it to the listed
maximum diameter.
2.4.2 Inlet Plenum for the Indoor Unit
Install an inlet plenum when testing a coil-only indoor unit, a
ducted blower coil indoor unit, or a single-package system. See
Figures 7b and 7c of ANSI/ASHRAE 37-2009 for cross-sectional
dimensions, the minimum length of the inlet plenum, and the
locations of the static-pressure taps for ducted blower coil indoor
units and single-package systems. See Figure 8 of ANSI/ASHRAE 37-
2009 for coil-only indoor units. The inlet plenum duct size shall
equal the size of the inlet opening of the air-handling (blower
coil) unit or furnace. For a ducted blower coil indoor unit the set
up may omit the inlet plenum if an inlet airflow prevention device
is installed with a straight internally unobstructed duct on its
outlet end with a minimum length equal to 1.5 times the square root
of the cross-sectional area of the indoor unit inlet. See section
2.5.1.2 of this appendix for requirements for the locations of
static pressure taps built into the inlet airflow prevention device.
For all of these arrangements, make a manifold that connects the
four static-pressure taps using one of the three configurations
specified in section 2.4.1.d of this appendix. Never use an inlet
plenum when testing non-ducted indoor units.
2.5 Indoor Coil Air Property Measurements and Airflow Prevention
Devices
Follow instructions for indoor coil air property measurements as
described in section 2.14 of this appendix, unless otherwise
instructed in this section.
a. Measure the dry-bulb temperature and water vapor content of
the air entering and
[[Page 37068]]
leaving the indoor coil. If needed, use an air sampling device to
divert air to a sensor(s) that measures the water vapor content of
the air. See section 5.3 of ANSI/ASHRAE 41.1-2013 (incorporated by
reference, see Sec. 430.3) for guidance on constructing an air
sampling device. No part of the air sampling device or the tubing
transferring the sampled air to the sensor shall be within two
inches of the test chamber floor, and the transfer tubing shall be
insulated. The sampling device may also be used for measurement of
dry bulb temperature by transferring the sampled air to a remotely
located sensor(s). The air sampling device and the remotely located
temperature sensor(s) may be used to determine the entering air dry
bulb temperature during any test. The air sampling device and the
remotely located sensor(s) may be used to determine the leaving air
dry bulb temperature for all tests except:
(1) Cyclic tests; and
(2) Frost accumulation tests.
b. Install grids of temperature sensors to measure dry bulb
temperatures of both the entering and leaving airstreams of the
indoor unit. These grids of dry bulb temperature sensors may be used
to measure average dry bulb temperature entering and leaving the
indoor unit in all cases (as an alternative to the dry bulb sensor
measuring the sampled air). The leaving airstream grid is required
for measurement of average dry bulb temperature leaving the indoor
unit for the two special cases noted above. The grids are also
required to measure the air temperature distribution of the entering
and leaving airstreams as described in sections 3.1.8 and 3.1.9 of
this appendix. Two such grids may applied as a thermopile, to
directly obtain the average temperature difference rather than
directly measuring both entering and leaving average temperatures.
c. Use of airflow prevention devices. Use an inlet and outlet
air damper box, or use an inlet upturned duct and an outlet air
damper box when conducting one or both of the cyclic tests listed in
sections 3.2 and 3.6 of this appendix on ducted systems. If not
conducting any cyclic tests, an outlet air damper box is required
when testing ducted and non-ducted heat pumps that cycle off the
indoor blower during defrost cycles and there is no other means for
preventing natural or forced convection through the indoor unit when
the indoor blower is off. Never use an inlet damper box or an inlet
upturned duct when testing non-ducted indoor units. An inlet
upturned duct is a length of ductwork installed upstream from the
inlet such that the indoor duct inlet opening, facing upwards, is
sufficiently high to prevent natural convection transfer out of the
duct. If an inlet upturned duct is used, install a dry bulb
temperature sensor near the inlet opening of the indoor duct at a
centerline location not higher than the lowest elevation of the duct
edges at the inlet, and ensure that any pair of 5-minute averages of
the dry bulb temperature at this location, measured at least every
minute during the compressor OFF period of the cyclic test, do not
differ by more than 1.0 [deg]F.
2.5.1 Test Set-Up on the Inlet Side of the Indoor Coil: For Cases Where
the Inlet Airflow Prevention Device Is Installed
a. Install an airflow prevention device as specified in section
2.5.1.1 or 2.5.1.2 of this appendix, whichever applies.
b. For an inlet damper box, locate the grid of entering air dry-
bulb temperature sensors, if used, and the air sampling device, or
the sensor used to measure the water vapor content of the inlet air,
at a location immediately upstream of the damper box inlet. For an
inlet upturned duct, locate the grid of entering air dry-bulb
temperature sensors, if used, and the air sampling device, or the
sensor used to measure the water vapor content of the inlet air, at
a location at least one foot downstream from the beginning of the
insulated portion of the duct but before the static pressure
measurement.
2.5.1.1 If the Section 2.4.2 Inlet Plenum Is Installed
Construct the airflow prevention device having a cross-sectional
flow area equal to or greater than the flow area of the inlet
plenum. Install the airflow prevention device upstream of the inlet
plenum and construct ductwork connecting it to the inlet plenum. If
needed, use an adaptor plate or a transition duct section to connect
the airflow prevention device with the inlet plenum. Insulate the
ductwork and inlet plenum with thermal insulation that has a nominal
overall resistance (R-value) of at least 19 hr ft\2\
[deg]F/Btu.
2.5.1.2 If the Section 2.4.2 Inlet Plenum Is Not Installed
Construct the airflow prevention device having a cross-sectional
flow area equal to or greater than the flow area of the air inlet of
the indoor unit. Install the airflow prevention device immediately
upstream of the inlet of the indoor unit. If needed, use an adaptor
plate or a short transition duct section to connect the airflow
prevention device with the unit's air inlet. Add static pressure
taps at the center of each face of a rectangular airflow prevention
device, or at four evenly distributed locations along the
circumference of an oval or round airflow prevention device. Locate
the pressure taps at a distance from the indoor unit inlet equal to
0.5 times the square root of the cross sectional area of the indoor
unit inlet. This location must be between the damper and the inlet
of the indoor unit, if a damper is used. Make a manifold that
connects the four static pressure taps using one of the
configurations shown in Figure 9 of ANSI/ASHRAE 37-2009
(incorporated by reference, see Sec. 430.3). Insulate the ductwork
with thermal insulation that has a nominal overall resistance (R-
value) of at least 19 hr ft\2\ [deg]F/Btu.
2.5.2 Test Set-Up on the Inlet Side of the Indoor Unit: For Cases Where
No Airflow Prevention Device Is Installed
If using the section 2.4.2 inlet plenum and a grid of dry bulb
temperature sensors, mount the grid at a location upstream of the
static pressure taps described in section 2.4.2 of this appendix,
preferably at the entrance plane of the inlet plenum. If the section
2.4.2 inlet plenum is not used (i.e. for non-ducted units) locate a
grid approximately 6 inches upstream of the indoor unit inlet. In
the case of a system having multiple non-ducted indoor units, do
this for each indoor unit. Position an air sampling device, or the
sensor used to measure the water vapor content of the inlet air,
immediately upstream of the (each) entering air dry-bulb temperature
sensor grid. If a grid of sensors is not used, position the entering
air sampling device (or the sensor used to measure the water vapor
content of the inlet air) as if the grid were present.
2.5.3 Indoor Coil Static Pressure Difference Measurement
Fabricate pressure taps meeting all requirements described in
section 6.5.2 of ANSI/ASHRAE 37-2009 (incorporated by reference, see
Sec. 430.3) and illustrated in Figure 2A of AMCA 210-2007
(incorporated by reference, see Sec. 430.3), however, if adhering
strictly to the description in section 6.5.2 of ANSI/ASHRAE 37-2009,
the minimum pressure tap length of 2.5 times the inner diameter of
Figure 2A of AMCA 210-2007 is waived. Use a differential pressure
measuring instrument that is accurate to within 0.01
inches of water and has a resolution of at least 0.01 inches of
water to measure the static pressure difference between the indoor
coil air inlet and outlet. Connect one side of the differential
pressure instrument to the manifolded pressure taps installed in the
outlet plenum. Connect the other side of the instrument to the
manifolded pressure taps located in either the inlet plenum or
incorporated within the airflow prevention device. For non-ducted
indoor units that are tested with multiple outlet plenums, measure
the static pressure within each outlet plenum relative to the
surrounding atmosphere.
2.5.4 Test Set-Up on the Outlet Side of the Indoor Coil
a. Install an interconnecting duct between the outlet plenum
described in section 2.4.1 of this appendix and the airflow
measuring apparatus described below in section 2.6 of this appendix.
The cross-sectional flow area of the interconnecting duct must be
equal to or greater than the flow area of the outlet plenum or the
common duct used when testing non-ducted units having multiple
indoor coils. If needed, use adaptor plates or transition duct
sections to allow the connections. To minimize leakage, tape joints
within the interconnecting duct (and the outlet plenum). Construct
or insulate the entire flow section with thermal insulation having a
nominal overall resistance (R-value) of at least 19 hr
ft\2\ [deg]F/Btu.
b. Install a grid(s) of dry-bulb temperature sensors inside the
interconnecting duct. Also, install an air sampling device, or the
sensor(s) used to measure the water vapor content of the outlet air,
inside the interconnecting duct. Locate the dry-bulb temperature
grid(s) upstream of the air sampling device (or the in-duct
sensor(s) used to measure the water vapor content of the outlet
air). Turn off the sampler fan motor during the cyclic tests. Air
leaving an indoor unit that is sampled by an air sampling device for
remote water-vapor-content measurement must be returned to the
interconnecting duct at a location:
[[Page 37069]]
(1) Downstream of the air sampling device;
(2) On the same side of the outlet air damper as the air
sampling device; and
(3) Upstream of the section 2.6 airflow measuring apparatus.
2.5.4.1 Outlet Air Damper Box Placement and Requirements
If using an outlet air damper box (see section 2.5 of this
appendix), the leakage rate from the combination of the outlet
plenum, the closed damper, and the duct section that connects these
two components must not exceed 20 cubic feet per minute when a
negative pressure of 1 inch of water column is maintained at the
plenum's inlet.
2.5.4.2 Procedures To Minimize Temperature Maldistribution
Use these procedures if necessary to correct temperature
maldistributions. Install a mixing device(s) upstream of the outlet
air, dry-bulb temperature grid (but downstream of the outlet plenum
static pressure taps). Use a perforated screen located between the
mixing device and the dry-bulb temperature grid, with a maximum open
area of 40 percent. One or both items should help to meet the
maximum outlet air temperature distribution specified in section
3.1.8 of this appendix. Mixing devices are described in sections
5.3.2 and 5.3.3 of ANSI/ASHRAE 41.1-2013 and section 5.2.2 of ASHRAE
41.2-1987 (RA 1992) (incorporated by reference, see Sec. 430.3).
2.5.4.3 Minimizing Air Leakage
For small-duct, high-velocity systems, install an air damper
near the end of the interconnecting duct, just prior to the
transition to the airflow measuring apparatus of section 2.6 of this
appendix. To minimize air leakage, adjust this damper such that the
pressure in the receiving chamber of the airflow measuring apparatus
is no more than 0.5 inch of water higher than the surrounding test
room ambient. If applicable, in lieu of installing a separate
damper, use the outlet air damper box of sections 2.5 and 2.5.4.1 of
this appendix if it allows variable positioning. Also apply these
steps to any conventional indoor blower unit that creates a static
pressure within the receiving chamber of the airflow measuring
apparatus that exceeds the test room ambient pressure by more than
0.5 inches of water column.
2.5.5 Dry Bulb Temperature Measurement
a. Measure dry bulb temperatures as specified in sections 4,
5.3, 6, and 7 of ANSI/ASHRAE 41.1-2013 (incorporated by reference,
see Sec. 430.3).
b. Distribute the sensors of a dry-bulb temperature grid over
the entire flow area. The required minimum is 9 sensors per grid.
2.5.6 Water Vapor Content Measurement
Determine water vapor content by measuring dry-bulb temperature
combined with the air wet-bulb temperature, dew point temperature,
or relative humidity. If used, construct and apply wet-bulb
temperature sensors as specified in sections 4, 5, 6, 7.2, 7.3, and
7.4 of ASHRAE 41.6-2014 (incorporated by reference, see Sec.
430.3). The temperature sensor (wick removed) must be accurate to
within 0.2 [deg]F. If used, apply dew point hygrometers
as specified in sections 4, 5, 6, 7.1, and 7.4 of ASHRAE 41.6-2014
(incorporated by reference, see Sec. 430.3). The dew point
hygrometers must be accurate to within 0.4 [deg]F when
operated at conditions that result in the evaluation of dew points
above 35 [deg]F. If used, a relative humidity (RH) meter must be
accurate to within 0.7% RH. Other means to determine the
psychrometric state of air may be used as long as the measurement
accuracy is equivalent to or better than the accuracy achieved from
using a wet-bulb temperature sensor that meets the above
specifications.
2.5.7 Air Damper Box Performance Requirements
If used (see section 2.5 of this appendix), the air damper
box(es) must be capable of being completely opened or completely
closed within 10 seconds for each action.
2.6 Airflow Measuring Apparatus
a. Fabricate and operate an airflow measuring apparatus as
specified in section 6.2 and 6.3 of ANSI/ASHRAE 37-2009
(incorporated by reference, see Sec. 430.3). Place the static
pressure taps and position the diffusion baffle (settling means)
relative to the chamber inlet as indicated in Figure 12 of AMCA 210-
2007 and/or Figure 14 of ASHRAE 41.2-1987 (RA 1992) (incorporated by
reference, see Sec. 430.3). When measuring the static pressure
difference across nozzles and/or velocity pressure at nozzle throats
using electronic pressure transducers and a data acquisition system,
if high frequency fluctuations cause measurement variations to
exceed the test tolerance limits specified in section 9.2 and Table
2 of ANSI/ASHRAE 37-2009, dampen the measurement system such that
the time constant associated with response to a step change in
measurement (time for the response to change 63% of the way from the
initial output to the final output) is no longer than five seconds.
b. Connect the airflow measuring apparatus to the
interconnecting duct section described in section 2.5.4 of this
appendix. See sections 6.1.1, 6.1.2, and 6.1.4, and Figures 1, 2,
and 4 of ANSI/ASHRAE 37-2009; and Figures D1, D2, and D4 of AHRI
210/240-2008 (incorporated by reference, see Sec. 430.3) for
illustrative examples of how the test apparatus may be applied
within a complete laboratory set-up. Instead of following one of
these examples, an alternative set-up may be used to handle the air
leaving the airflow measuring apparatus and to supply properly
conditioned air to the test unit's inlet. The alternative set-up,
however, must not interfere with the prescribed means for measuring
airflow rate, inlet and outlet air temperatures, inlet and outlet
water vapor contents, and external static pressures, nor create
abnormal conditions surrounding the test unit. (Note: Do not use an
enclosure as described in section 6.1.3 of ANSI/ASHRAE 37-2009 when
testing triple-split units.)
2.7 Electrical Voltage Supply
Perform all tests at the voltage specified in section 6.1.3.2 of
AHRI 210/240-2008 (incorporated by reference, see Sec. 430.3) for
``Standard Rating Tests.'' If either the indoor or the outdoor unit
has a 208V or 200V nameplate voltage and the other unit has a 230V
nameplate rating, select the voltage supply on the outdoor unit for
testing. Otherwise, supply each unit with its own nameplate voltage.
Measure the supply voltage at the terminals on the test unit using a
volt meter that provides a reading that is accurate to within 1.0 percent of the measured quantity.
2.8 Electrical Power and Energy Measurements
a. Use an integrating power (watt-hour) measuring system to
determine the electrical energy or average electrical power supplied
to all components of the air conditioner or heat pump (including
auxiliary components such as controls, transformers, crankcase
heater, integral condensate pump on non-ducted indoor units, etc.).
The watt-hour measuring system must give readings that are accurate
to within 0.5 percent. For cyclic tests, this accuracy
is required during both the ON and OFF cycles. Use either two
different scales on the same watt-hour meter or two separate watt-
hour meters. Activate the scale or meter having the lower power
rating within 15 seconds after beginning an OFF cycle. Activate the
scale or meter having the higher power rating within 15 seconds
prior to beginning an ON cycle. For ducted blower coil systems, the
ON cycle lasts from compressor ON to indoor blower OFF. For ducted
coil-only systems, the ON cycle lasts from compressor ON to
compressor OFF. For non-ducted units, the ON cycle lasts from indoor
blower ON to indoor blower OFF. When testing air conditioners and
heat pumps having a variable-speed compressor, avoid using an
induction watt/watt-hour meter.
b. When performing section 3.5 and/or 3.8 cyclic tests on non-
ducted units, provide instrumentation to determine the average
electrical power consumption of the indoor blower motor to within
1.0 percent. If required according to sections 3.3, 3.4,
3.7, 3.9.1 of this appendix, and/or 3.10 of this appendix, this same
instrumentation requirement (to determine the average electrical
power consumption of the indoor blower motor to within 1.0 percent) applies when testing air conditioners and heat
pumps having a variable-speed constant-air-volume-rate indoor blower
or a variable-speed, variable-air-volume-rate indoor blower.
2.9 Time Measurements
Make elapsed time measurements using an instrument that yields
readings accurate to within 0.2 percent.
2.10 Test Apparatus for the Secondary Space Conditioning Capacity
Measurement
For all tests, use the indoor air enthalpy method to measure the
unit's capacity. This method uses the test set-up specified in
sections 2.4 to 2.6 of this appendix. In addition, for all steady-
state tests, conduct a second, independent measurement of capacity
as described in section 3.1.1 of this appendix. For split systems,
use one of the following secondary measurement methods: Outdoor air
enthalpy method, compressor calibration method, or refrigerant
enthalpy method. For single-package units, use either the outdoor
air enthalpy method or the compressor calibration method as the
secondary measurement.
[[Page 37070]]
2.10.1 Outdoor Air Enthalpy Method
a. To make a secondary measurement of indoor space conditioning
capacity using the outdoor air enthalpy method, do the following:
(1) Measure the electrical power consumption of the test unit;
(2) Measure the air-side capacity at the outdoor coil; and
(3) Apply a heat balance on the refrigerant cycle.
b. The test apparatus required for the outdoor air enthalpy
method is a subset of the apparatus used for the indoor air enthalpy
method. Required apparatus includes the following:
(1) On the outlet side, an outlet plenum containing static
pressure taps (sections 2.4, 2.4.1, and 2.5.3 of this appendix),
(2) An airflow measuring apparatus (section 2.6 of this
appendix),
(3) A duct section that connects these two components and itself
contains the instrumentation for measuring the dry-bulb temperature
and water vapor content of the air leaving the outdoor coil
(sections 2.5.4, 2.5.5, and 2.5.6 of this appendix), and
(4) On the inlet side, a sampling device and temperature grid
(section 2.11.b of this appendix).
c. During the preliminary tests described in sections 3.11.1 and
3.11.1.1 of this appendix, measure the evaporator and condenser
temperatures or pressures. On both the outdoor coil and the indoor
coil, solder a thermocouple onto a return bend located at or near
the midpoint of each coil or at points not affected by vapor
superheat or liquid subcooling. Alternatively, if the test unit is
not sensitive to the refrigerant charge, install pressure gages to
the access valves or to ports created from tapping into the suction
and discharge lines according to sections 7.4.2 and 8.2.5 of ASHRAE
37-2009. Use this alternative approach when testing a unit charged
with a zeotropic refrigerant having a temperature glide in excess of
1 [deg]F at the specified test conditions.
2.10.2 Compressor Calibration Method
Measure refrigerant pressures and temperatures to determine the
evaporator superheat and the enthalpy of the refrigerant that enters
and exits the indoor coil. Determine refrigerant flow rate or, when
the superheat of the refrigerant leaving the evaporator is less than
5 [deg]F, total capacity from separate calibration tests conducted
under identical operating conditions. When using this method,
install instrumentation and measure refrigerant properties according
to section 7.4.2 and 8.2.5 of ANSI/ASHRAE 37-2009 (incorporated by
reference, see Sec. 430.3). If removing the refrigerant before
applying refrigerant lines and subsequently recharging, use the
steps in 7.4.2 of ANSI/ASHRAE 37-2009 in addition to the methods of
section 2.2.5 of this appendix to confirm the refrigerant charge.
Use refrigerant temperature and pressure measuring instruments that
meet the specifications given in sections 5.1.1 and 5.2 of ANSI/
ASHRAE 37-2009.
2.10.3 Refrigerant Enthalpy Method
For this method, calculate space conditioning capacity by
determining the refrigerant enthalpy change for the indoor coil and
directly measuring the refrigerant flow rate. Use section 7.5.2 of
ANSI/ASHRAE 37-2009 (incorporated by reference, see Sec. 430.3) for
the requirements for this method, including the additional
instrumentation requirements, and information on placing the flow
meter and a sight glass. Use refrigerant temperature, pressure, and
flow measuring instruments that meet the specifications given in
sections 5.1.1, 5.2, and 5.5.1 of ANSI/ASHRAE 37-2009. Refrigerant
flow measurement device(s), if used, must be either elevated at
least two feet from the test chamber floor or placed upon insulating
material having a total thermal resistance of at least R-12 and
extending at least one foot laterally beyond each side of the
device(s)' exposed surfaces.
2.11 Measurement of Test Room Ambient Conditions
Follow instructions for setting up air sampling device and
aspirating psychrometer as described in section 2.14 of this
appendix, unless otherwise instructed in this section.
a. If using a test set-up where air is ducted directly from the
conditioning apparatus to the indoor coil inlet (see Figure 2, Loop
Air-Enthalpy Test Method Arrangement, of ANSI/ASHRAE 37-2009
(incorporated by reference, see Sec. 430.3)), add instrumentation
to permit measurement of the indoor test room dry-bulb temperature.
b. On the outdoor side, use one of the following two approaches,
except that approach (1) is required for all evaporatively-cooled
units and units that transfer condensate to the outdoor unit for
evaporation using condenser heat.
(1) Use sampling tree air collection on all air-inlet surfaces
of the outdoor unit.
(2) Use sampling tree air collection on one or more faces of the
outdoor unit and demonstrate air temperature uniformity as follows.
Install a grid of evenly-distributed thermocouples on each air-
permitting face on the inlet of the outdoor unit. Install the
thermocouples on the air sampling device, locate them individually
or attach them to a wire structure. If not installed on the air
sampling device, install the thermocouple grid 6 to 24 inches from
the unit. The thermocouples shall be evenly spaced across the coil
inlet surface and be installed to avoid sampling of discharge air or
blockage of air recirculation. The grid of thermocouples must
provide at least 16 measuring points per face or one measurement per
square foot of inlet face area, whichever is less. This grid must be
constructed and used as per section 5.3 of ANSI/ASHRAE 41.1-2013
(incorporated by reference, see Sec. 430.3). The maximum difference
between the readings of any two pairs of these individual
thermocouples located at any of the faces of the inlet of the
outdoor unit, must not exceed 2.0 [deg]F, otherwise approach (1)
must be used.
The air sampling devices shall be located at the geometric
center of each side; the branches may be oriented either parallel or
perpendicular to the longer edges of the air inlet area. The air
sampling devices in the outdoor air inlet location shall be sized
such that they cover at least 75% of the face area of the side of
the coil that they are measuring.
Air distribution at the test facility point of supply to the
unit shall be reviewed and may require remediation prior to the
beginning of testing. Mixing fans can be used to ensure adequate air
distribution in the test room. If used, mixing fans shall be
oriented such that they are pointed away from the air intake so that
the mixing fan exhaust does not affect the outdoor coil air volume
rate. Particular attention should be given to prevent the mixing
fans from affecting (enhancing or limiting) recirculation of
condenser fan exhaust air back through the unit. Any fan used to
enhance test room air mixing shall not cause air velocities in the
vicinity of the test unit to exceed 500 feet per minute.
The air sampling device may be larger than the face area of the
side being measured, however care shall be taken to prevent
discharge air from being sampled. If an air sampling device
dimension extends beyond the inlet area of the unit, holes shall be
blocked in the air sampling device to prevent sampling of discharge
air. Holes can be blocked to reduce the region of coverage of the
intake holes both in the direction of the trunk axis or
perpendicular to the trunk axis. For intake hole region reduction in
the direction of the trunk axis, block holes of one or more adjacent
pairs of branches (the branches of a pair connect opposite each
other at the same trunk location) at either the outlet end or the
closed end of the trunk. For intake hole region reduction
perpendicular to the trunk axis, block off the same number of holes
on each branch on both sides of the trunk.
A maximum of four (4) air sampling devices shall be connected to
each aspirating psychrometer. In order to proportionately divide the
flow stream for multiple air sampling devices for a given aspirating
psychrometer, the tubing or conduit conveying sampled air to the
psychrometer shall be of equivalent lengths for each air sampling
device. Preferentially, the air sampling device should be hard
connected to the aspirating psychrometer, but if space constraints
do not allow this, the assembly shall have a means of allowing a
flexible tube to connect the air sampling device to the aspirating
psychrometer. The tubing or conduit shall be insulated and routed to
prevent heat transfer to the air stream. Any surface of the air
conveying tubing in contact with surrounding air at a different
temperature than the sampled air shall be insulated with thermal
insulation with a nominal thermal resistance (R-value) of at least
19 hr [middot] ft\2\ [middot] [deg]F/Btu. Alternatively the conduit
may have lower thermal resistance if additional sensor(s) are used
to measure dry bulb temperature at the outlet of each air sampling
device. No part of the air sampling device or the tubing conducting
the sampled air to the sensors shall be within two inches of the
test chamber floor.
Pairs of measurements (e.g., dry bulb temperature and wet bulb
temperature) used to determine water vapor content of sampled air
shall be measured in the same location.
2.12 Measurement of Indoor Blower Speed
When required, measure fan speed using a revolution counter,
tachometer, or stroboscope that gives readings accurate to within
1.0 percent.
[[Page 37071]]
2.13 Measurement of Barometric Pressure
Determine the average barometric pressure during each test. Use
an instrument that meets the requirements specified in section 5.2
of ANSI/ASHRAE 37-2009 (incorporated by reference, see Sec. 430.3).
2.14 Air Sampling Device and Aspirating Psychrometer Requirements
Air temperature measurements shall be made in accordance with
ANSI/ASHRAE 41.1-2013, unless otherwise instructed in this section.
2.14.1 Air Sampling Device Requirements
The air sampling device is intended to draw in a sample of the
air at the critical locations of a unit under test. It shall be
constructed of stainless steel, plastic or other suitable, durable
materials. It shall have a main flow trunk tube with a series of
branch tubes connected to the trunk tube. Holes shall be on the side
of the sampler facing the upstream direction of the air source.
Other sizes and rectangular shapes can be used, and shall be scaled
accordingly with the following guidelines:
(1) Minimum hole density of 6 holes per square foot of area to
be sampled
(2) Sampler branch tube pitch (spacing) of 6 3 in
(3) Manifold trunk to branch diameter ratio having a minimum of
3:1 ratio
(4) Hole pitch (spacing) shall be equally distributed over the
branch (1/2 pitch from the closed end to the nearest hole)
(5) Maximum individual hole to branch diameter ratio of 1:2 (1:3
preferred)
The minimum average velocity through the air sampling device
holes shall be 2.5 ft/s as determined by evaluating the sum of the
open area of the holes as compared to the flow area in the
aspirating psychrometer.
2.14.2 Aspirating Psychrometer
The psychrometer consists of a flow section and a fan to draw
air through the flow section and measures an average value of the
sampled air stream. At a minimum, the flow section shall have a
means for measuring the dry bulb temperature (typically, a
resistance temperature device (RTD) and a means for measuring the
humidity (RTD with wetted sock, chilled mirror hygrometer, or
relative humidity sensor). The aspirating psychrometer shall include
a fan that either can be adjusted manually or automatically to
maintain required velocity across the sensors.
The psychrometer shall be made from suitable material which may
be plastic (such as polycarbonate), aluminum or other metallic
materials. All psychrometers for a given system being tested, shall
be constructed of the same material. Psychrometers shall be designed
such that radiant heat from the motor (for driving the fan that
draws sampled air through the psychrometer) does not affect sensor
measurements. For aspirating psychrometers, velocity across the wet
bulb sensor shall be 1000 200 ft/min. For all other
psychrometers, velocity shall be as specified by the sensor
manufacturer.
3. Testing Procedures
3.1 General Requirements
If, during the testing process, an equipment set-up adjustment
is made that would have altered the performance of the unit during
any already completed test, then repeat all tests affected by the
adjustment. For cyclic tests, instead of maintaining an air volume
rate, for each airflow nozzle, maintain the static pressure
difference or velocity pressure during an ON period at the same
pressure difference or velocity pressure as measured during the
steady-state test conducted at the same test conditions.
Use the testing procedures in this section to collect the data
used for calculating:
(1) Performance metrics for central air conditioners and heat
pumps during the cooling season;
(2) Performance metrics for heat pumps during the heating
season; and
(3) Power consumption metric(s) for central air conditioners and
heat pumps during the off mode season(s).
3.1.1 Primary and Secondary Test Methods
For all tests, use the indoor air enthalpy method test apparatus
to determine the unit's space conditioning capacity. The procedure
and data collected, however, differ slightly depending upon whether
the test is a steady-state test, a cyclic test, or a frost
accumulation test. The following sections described these
differences. For all steady-state tests (i.e., the A, A2,
A1, B, B2, B1, C, C1,
EV, F1, G1, H01, H1,
H12, H11, HIN, H3,
H32, and H31 Tests), in addition, use one of
the acceptable secondary methods specified in section 2.10 of this
appendix to determine indoor space conditioning capacity. Calculate
this secondary check of capacity according to section 3.11 of this
appendix. The two capacity measurements must agree to within 6
percent to constitute a valid test. For this capacity comparison,
use the indoor air enthalpy method capacity that is calculated in
section 7.3 of ANSI/ASHRAE 37-2009 (and, if testing a coil-only
system, compare capacities before before making the after-test fan
heat adjustments described in section 3.3, 3.4, 3.7, and 3.10 of
this appendix). However, include the appropriate section 3.3 to 3.5
and 3.7 to 3.10 fan heat adjustments within the indoor air enthalpy
method capacities used for the section 4 seasonal calculations of
this appendix.
3.1.2 Manufacturer-Provided Equipment Overrides
Where needed, the manufacturer must provide a means for
overriding the controls of the test unit so that the compressor(s)
operates at the specified speed or capacity and the indoor blower
operates at the specified speed or delivers the specified air volume
rate.
3.1.3 Airflow Through the Outdoor Coil
For all tests, meet the requirements given in section 6.1.3.4 of
AHRI 210/240-2008 (incorporated by reference, see Sec. 430.3) when
obtaining the airflow through the outdoor coil.
3.1.3.1 Double-Ducted
For products intended to be installed with the outdoor airflow
ducted, the unit shall be installed with outdoor coil ductwork
installed per manufacturer installation instructions and shall
operate between 0.10 and 0.15 in H2O external static
pressure. External static pressure measurements shall be made in
accordance with ANSI/ASHRAE 37-2009 section 6.4 and 6.5.
3.1.4 Airflow Through the Indoor Coil
Airflow setting(s) shall be determined before testing begins.
Unless otherwise specified within this or its subsections, no
changes shall be made to the airflow setting(s) after initiation of
testing.
3.1.4.1 Cooling Full-Load Air Volume Rate
3.1.4.1.1. Cooling Full-Load Air Volume Rate for Ducted Units
Identify the certified cooling full-load air volume rate and
certified instructions for setting fan speed or controls. If there
is no certified Cooling full-load air volume rate, use a value equal
to the certified cooling capacity of the unit times 400 scfm per
12,000 Btu/h. If there are no instructions for setting fan speed or
controls, use the as-shipped settings. Use the following procedure
to confirm and, if necessary, adjust the Cooling full-load air
volume rate and the fan speed or control settings to meet each test
procedure requirement:
a. For all ducted blower coil systems, except those having a
constant-air-volume-rate indoor blower:
Step (1) Operate the unit under conditions specified for the A
(for single-stage units) or A2 test using the certified
fan speed or controls settings, and adjust the exhaust fan of the
airflow measuring apparatus to achieve the certified Cooling full-
load air volume rate;
Step (2) Measure the external static pressure;
Step (3) If this external static pressure is equal to or greater
than the applicable minimum external static pressure cited in Table
3, the pressure requirement is satisfied; proceed to step 7 of this
section. If this external static pressure is not equal to or greater
than the applicable minimum external static pressure cited in Table
3, proceed to step 4 of this section;
Step (4) Increase the external static pressure by adjusting the
exhaust fan of the airflow measuring apparatus until either
(i) The applicable Table 3 minimum is equaled or
(ii) The measured air volume rate equals 90 percent or less of
the Cooling full-load air volume rate, whichever occurs first;
Step (5) If the conditions of step 4 (i) of this section occur
first, the pressure requirement is satisfied; proceed to step 7 of
this section. If the conditions of step 4 (ii) of this section occur
first, proceed to step 6 of this section;
Step (6) Make an incremental change to the setup of the indoor
blower (e.g., next highest fan motor pin setting, next highest fan
motor speed) and repeat the evaluation process beginning above, at
step 1 of this section. If the indoor blower setup cannot be further
changed, increase the external static pressure by adjusting the
exhaust fan of the airflow measuring apparatus until the applicable
Table 3 minimum is equaled; proceed to step 7 of this section;
[[Page 37072]]
Step (7) The airflow constraints have been satisfied. Use the
measured air volume rate as the Cooling full-load air volume rate.
Use the final fan speed or control settings for all tests that use
the Cooling full-load air volume rate.
b. For ducted blower coil systems with a constant-air-volume-
rate indoor blower. For all tests that specify the Cooling full-load
air volume rate, obtain an external static pressure as close to (but
not less than) the applicable Table 3 value that does not cause
automatic shutdown of the indoor blower or air volume rate variation
QVar, defined as follows, greater than 10 percent.
[GRAPHIC] [TIFF OMITTED] TR08JN16.007
where:
Qmax = maximum measured airflow value
Qmin = minimum measured airflow value
QVar = airflow variance, percent
Additional test steps as described in section 3.3.(e) of this
appendix are required if the measured external static pressure exceeds
the target value by more than 0.03 inches of water.
c. For coil-only indoor units. For the A or A2 Test,
(exclusively), the pressure drop across the indoor coil assembly must
not exceed 0.30 inches of water. If this pressure drop is exceeded,
reduce the air volume rate until the measured pressure drop equals the
specified maximum. Use this reduced air volume rate for all tests that
require the Cooling full-load air volume rate.
Table 3--Minimum External Static Pressure for Ducted Blower Coil Systems
------------------------------------------------------------------------
Minimum external resistance
\3\ (inches of water)
-------------------------------
Rated cooling \1\or heating \2\ capacity Small-duct,
(Btu/h) high-velocity All other
systems 4 5 systems
------------------------------------------------------------------------
Up Thru 28,800.......................... 1.10 0.10
29,000 to 42,500........................ 1.15 0.15
43,000 and Above........................ 1.20 0.20
------------------------------------------------------------------------
\1\ For air conditioners and air-conditioning heat pumps, the value
certified by the manufacturer for the unit's cooling capacity when
operated at the A or A2 Test conditions.
\2\ For heating-only heat pumps, the value certified by the manufacturer
for the unit's heating capacity when operated at the H1 or H12 Test
conditions.
\3\ For ducted units tested without an air filter installed, increase
the applicable tabular value by 0.08 inches of water.
\4\ See section 1.2 of this appendix, Definitions, to determine if the
equipment qualifies as a small-duct, high-velocity system.
\5\ If a closed-loop, air-enthalpy test apparatus is used on the indoor
side, limit the resistance to airflow on the inlet side of the blower
coil indoor unit to a maximum value of 0.1 inch of water. Impose the
balance of the airflow resistance on the outlet side of the indoor
blower.
d. For ducted systems having multiple indoor blowers within a
single indoor section, obtain the full-load air volume rate with all
indoor blowers operating unless prevented by the controls of the unit.
In such cases, turn on the maximum number of indoor blowers permitted
by the unit's controls. Where more than one option exists for meeting
this ``on'' indoor blower requirement, which indoor blower(s) are
turned on must match that specified in the certification report.
Conduct section 3.1.4.1.1 setup steps for each indoor blower
separately. If two or more indoor blowers are connected to a common
duct as per section 2.4.1 of this appendix, temporarily divert their
air volume to the test room when confirming or adjusting the setup
configuration of individual indoor blowers. The allocation of the
system's full-load air volume rate assigned to each ``on'' indoor
blower must match that specified by the manufacturer in the
certification report.
3.1.4.1.2. Cooling Full-Load Air Volume Rate for Non-ducted Units
For non-ducted units, the Cooling full-load air volume rate is the
air volume rate that results during each test when the unit is operated
at an external static pressure of zero inches of water.
3.1.4.2 Cooling Minimum Air Volume Rate
Identify the certified cooling minimum air volume rate and
certified instructions for setting fan speed or controls. If there is
no certified cooling minimum air volume rate, use the final indoor
blower control settings as determined when setting the cooling full-
load air volume rate, and readjust the exhaust fan of the airflow
measuring apparatus if necessary to reset to the cooling full load air
volume obtained in section 3.1.4.1 of this appendix. Otherwise,
calculate the target external static pressure and follow instructions
a, b, c, d, or e below. The target external static pressure,
[Delta]Pst_i, for any test ``i'' with a specified air volume
rate not equal to the Cooling full-load air volume rate is determined
as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.008
where:
[Delta]Pst_i = target minimum external static pressure
for test i;
[Delta]Pst_full = minimum external static pressure for
test A or A2 (Table 3);
Qi = air volume rate for test i; and
Qfull = Cooling full-load air volume rate as measured
after setting and/or adjustment as described in section 3.1.4.1.1 of
this appendix.
a. For a ducted blower coil system without a constant-air-volume
indoor blower, adjust for external static pressure as follows:
Step (1) Operate the unit under conditions specified for the B1
test using the certified fan speed or controls settings, and adjust the
exhaust fan of the airflow measuring apparatus to achieve the certified
cooling minimum air volume rate;
Step (2) Measure the external static pressure;
Step (3) If this pressure is equal to or greater than the minimum
external static pressure computed above, the pressure requirement is
satisfied; proceed to step 7 of this section. If this pressure is not
equal to or greater than the minimum external static pressure computed
above, proceed to step 4 of this section;
Step (4) Increase the external static pressure by adjusting the
exhaust fan of the airflow measuring apparatus until either
(i) The pressure is equal to the minimum external static pressure
computed above or
(ii) The measured air volume rate equals 90 percent or less of the
cooling minimum air volume rate, whichever occurs first;
[[Page 37073]]
Step (5) If the conditions of step 4 (i) of this section occur
first, the pressure requirement is satisfied; proceed to step 7 of this
section. If the conditions of step 4 (ii) of this section occur first,
proceed to step 6 of this section;
Step (6) Make an incremental change to the setup of the indoor
blower (e.g., next highest fan motor pin setting, next highest fan
motor speed) and repeat the evaluation process beginning above, at step
1 of this section. If the indoor blower setup cannot be further
changed, increase the external static pressure by adjusting the exhaust
fan of the airflow measuring apparatus until it equals the minimum
external static pressure computed above; proceed to step 7 of this
section;
Step (7) The airflow constraints have been satisfied. Use the
measured air volume rate as the cooling minimum air volume rate. Use
the final fan speed or control settings for all tests that use the
cooling minimum air volume rate.
b. For ducted units with constant-air-volume indoor blowers,
conduct all tests that specify the cooling minimum air volume rate--
(i.e., the A1, B1, C1, F1,
and G1 Tests)--at an external static pressure that does not
cause an automatic shutdown of the indoor blower or air volume rate
variation QVar, defined in section 3.1.4.1.1.b of this
appendix, greater than 10 percent, while being as close to, but not
less than the target minimum external static pressure. Additional test
steps as described in section 3.3(e) of this appendix are required if
the measured external static pressure exceeds the target value by more
than 0.03 inches of water.
c. For ducted two-capacity coil-only systems, the cooling minimum
air volume rate is the higher of (1) the rate specified by the
installation instructions included with the unit by the manufacturer or
(2) 75 percent of the cooling full-load air volume rate. During the
laboratory tests on a coil-only (fanless) system, obtain this cooling
minimum air volume rate regardless of the pressure drop across the
indoor coil assembly.
d. For non-ducted units, the cooling minimum air volume rate is the
air volume rate that results during each test when the unit operates at
an external static pressure of zero inches of water and at the indoor
blower setting used at low compressor capacity (two-capacity system) or
minimum compressor speed (variable-speed system). For units having a
single-speed compressor and a variable-speed variable-air-volume-rate
indoor blower, use the lowest fan setting allowed for cooling.
e. For ducted systems having multiple indoor blowers within a
single indoor section, operate the indoor blowers such that the lowest
air volume rate allowed by the unit's controls is obtained when
operating the lone single-speed compressor or when operating at low
compressor capacity while meeting the requirements of section 2.2.3.b
of this appendix for the minimum number of blowers that must be turned
off. Using the target external static pressure and the certified air
volume rates, follow the procedures described in section 3.1.4.2.a of
this appendix if the indoor blowers are not constant-air-volume indoor
blowers or as described in section 3.1.4.2.b of this appendix if the
indoor blowers are constant-air-volume indoor blowers. The sum of the
individual ``on'' indoor blowers' air volume rates is the cooling
minimum air volume rate for the system.
3.1.4.3 Cooling Intermediate Air Volume Rate
Identify the certified cooling intermediate air volume rate and
certified instructions for setting fan speed or controls. If there is
no certified cooling intermediate air volume rate, use the final indoor
blower control settings as determined when setting the cooling full
load air volume rate, and readjust the exhaust fan of the airflow
measuring apparatus if necessary to reset to the cooling full load air
volume obtained in section 3.1.4.1 of this appendix. Otherwise,
calculate target minimum external static pressure as described in
section 3.1.4.2 of this appendix, and set the air volume rate as
follows.
a. For a ducted blower coil system without a constant-air-volume
indoor blower, adjust for external static pressure as described in
section 3.1.4.2.a of this appendix for cooling minimum air volume rate.
b. For a ducted blower coil system with a constant-air-volume
indoor blower, conduct the EV Test at an external static
pressure that does not cause an automatic shutdown of the indoor blower
or air volume rate variation QVar, defined in section
3.1.4.1.1.b of this appendix, greater than 10 percent, while being as
close to, but not less than the target minimum external static
pressure. Additional test steps as described in section 3.3(e) of this
appendix are required if the measured external static pressure exceeds
the target value by more than 0.03 inches of water.
c. For non-ducted units, the cooling intermediate air volume rate
is the air volume rate that results when the unit operates at an
external static pressure of zero inches of water and at the fan speed
selected by the controls of the unit for the EV Test
conditions.
3.1.4.4 Heating Full-Load Air Volume Rate
3.1.4.4.1 Ducted Heat Pumps Where the Heating and Cooling Full-Load Air
Volume Rates Are the Same
a. Use the Cooling full-load air volume rate as the heating full-
load air volume rate for:
(1) Ducted blower coil system heat pumps that do not have a
constant-air-volume indoor blower, and that operate at the same
airflow-control setting during both the A (or A2) and the H1
(or H12) Tests;
(2) Ducted blower coil system heat pumps with constant-air-flow
indoor blowers that provide the same air flow for the A (or
A2) and the H1 (or H12) Tests; and
(3) Ducted heat pumps that are tested with a coil-only indoor unit
(except two-capacity northern heat pumps that are tested only at low
capacity cooling--see section 3.1.4.4.2 of this appendix).
b. For heat pumps that meet the above criteria ``1'' and ``3,'' no
minimum requirements apply to the measured external or internal,
respectively, static pressure. Use the final indoor blower control
settings as determined when setting the Cooling full-load air volume
rate, and readjust the exhaust fan of the airflow measuring apparatus
if necessary to reset to the cooling full-load air volume obtained in
section 3.1.4.1 of this appendix. For heat pumps that meet the above
criterion ``2,'' test at an external static pressure that does not
cause an automatic shutdown of the indoor blower or air volume rate
variation QVar, defined in section 3.1.4.1.1.b of this
appendix, greater than 10 percent, while being as close to, but not
less than, the same Table 3 minimum external static pressure as was
specified for the A (or A2) cooling mode test. Additional
test steps as described in section 3.9.1(c) of this appendix are
required if the measured external static pressure exceeds the target
value by more than 0.03 inches of water.
3.1.4.4.2 Ducted Heat Pumps Where the Heating and Cooling Full-Load Air
Volume Rates Are Different Due to Changes in Indoor Blower Operation,
i.e. Speed Adjustment by the System Controls
Identify the certified heating full-load air volume rate and
certified instructions for setting fan speed or controls. If there is
no certified heating full-load air volume rate, use the final indoor
blower control settings as
[[Page 37074]]
determined when setting the cooling full-load air volume rate, and
readjust the exhaust fan of the airflow measuring apparatus if
necessary to reset to the cooling full load air volume obtained in
section 3.1.4.1 of this appendix. Otherwise, calculate target minimum
external static pressure as described in section 3.1.4.2 of this
appendix and set the air volume rate as follows.
a. For ducted blower coil system heat pumps that do not have a
constant-air-volume indoor blower, adjust for external static pressure
as described in section 3.1.4.2.a of this appendix for cooling minimum
air volume rate.
b. For ducted heat pumps tested with constant-air-volume indoor
blowers installed, conduct all tests that specify the heating full-load
air volume rate at an external static pressure that does not cause an
automatic shutdown of the indoor blower or air volume rate variation
QVar, defined in section 3.1.4.1.1.b of this appendix,
greater than 10 percent, while being as close to, but not less than the
target minimum external static pressure. Additional test steps as
described in section 3.9.1(c) of this appendix are required if the
measured external static pressure exceeds the target value by more than
0.03 inches of water.
c. When testing ducted, two-capacity blower coil system northern
heat pumps (see section 1.2 of this appendix, Definitions), use the
appropriate approach of the above two cases. For coil-only system
northern heat pumps, the heating full-load air volume rate is the
lesser of the rate specified by the manufacturer in the installation
instructions included with the unit or 133 percent of the cooling full-
load air volume rate. For this latter case, obtain the heating full-
load air volume rate regardless of the pressure drop across the indoor
coil assembly.
d. For ducted systems having multiple indoor blowers within a
single indoor section, obtain the heating full-load air volume rate
using the same ``on'' indoor blowers as used for the Cooling full-load
air volume rate. Using the target external static pressure and the
certified air volume rates, follow the procedures as described in
section 3.1.4.4.2.a of this appendix if the indoor blowers are not
constant-air-volume indoor blowers or as described in section
3.1.4.4.2.b of this appendix if the indoor blowers are constant-air-
volume indoor blowers. The sum of the individual ``on'' indoor blowers'
air volume rates is the heating full load air volume rate for the
system.
3.1.4.4.3 Ducted Heating-Only Heat Pumps
Identify the certified heating full-load air volume rate and
certified instructions for setting fan speed or controls. If there is
no certified heating full-load air volume rate, use a value equal to
the certified heating capacity of the unit times 400 scfm per 12,000
Btu/h. If there are no instructions for setting fan speed or controls,
use the as-shipped settings.
a. For all ducted heating-only blower coil system heat pumps,
except those having a constant-air-volume-rate indoor blower. Conduct
the following steps only during the first test, the H1 or
H12 est:
Step (1) Adjust the exhaust fan of the airflow measuring apparatus
to achieve the certified heating full-load air volume rate.
Step (2) Measure the external static pressure.
Step (3) If this pressure is equal to or greater than the Table 3
minimum external static pressure that applies given the heating-only
heat pump's rated heating capacity, the pressure requirement is
satisfied; proceed to step 7 of this section. If this pressure is not
equal to or greater than the applicable Table 3 minimum external static
pressure, proceed to step 4 of this section;
Step (4) Increase the external static pressure by adjusting the
exhaust fan of the airflow measuring apparatus until either (i) the
pressure is equal to the applicable Table 3 minimum external static
pressure or (ii) the measured air volume rate equals 90 percent or less
of the heating full-load air volume rate, whichever occurs first;
Step (5) If the conditions of step 4 (i) of this section occur
first, the pressure requirement is satisfied; proceed to step 7 of this
section. If the conditions of step 4 (ii) of this section occur first,
proceed to step 6 of this section;
Step (6) Make an incremental change to the setup of the indoor
blower (e.g., next highest fan motor pin setting, next highest fan
motor speed) and repeat the evaluation process beginning above, at step
1 of this section. If the indoor blower setup cannot be further
changed, increase the external static pressure by adjusting the exhaust
fan of the airflow measuring apparatus until it equals the applicable
Table 3 minimum external static pressure; proceed to step 7 of this
section;
Step (7) The airflow constraints have been satisfied. Use the
measured air volume rate as the heating full-load air volume rate. Use
the final fan speed or control settings for all tests that use the
heating full-load air volume rate.
b. For ducted heating-only blower coil system heat pumps having a
constant-air-volume-rate indoor blower. For all tests that specify the
heating full-load air volume rate, obtain an external static pressure
that does not cause an automatic shutdown of the indoor blower or air
volume rate variation QVar, defined in section 3.1.4.1.1.b
of this appendix, greater than 10 percent, while being as close to, but
not less than, the applicable Table 3 minimum. Additional test steps as
described in section 3.9.1(c) of this appendix are required if the
measured external static pressure exceeds the target value by more than
0.03 inches of water.
c. For ducted heating-only coil-only system heat pumps in the H1 or
H12 Test, (exclusively), the pressure drop across the indoor
coil assembly must not exceed 0.30 inches of water. If this pressure
drop is exceeded, reduce the air volume rate until the measured
pressure drop equals the specified maximum. Use this reduced air volume
rate for all tests that require the heating full-load air volume rate.
3.1.4.4.4 Non-Ducted Heat Pumps, Including Non-Ducted Heating-Only Heat
Pumps
For non-ducted heat pumps, the heating full-load air volume rate is
the air volume rate that results during each test when the unit
operates at an external static pressure of zero inches of water.
3.1.4.5 Heating Minimum Air Volume Rate
3.1.4.5.1. Ducted Heat Pumps Where the Heating and Cooling Minimum Air
Volume Rates Are the Same
a. Use the cooling minimum air volume rate as the heating minimum
air volume rate for:
(1) Ducted blower coil system heat pumps that do not have a
constant-air-volume indoor blower, and that operates at the same
airflow-control setting during both the A1 and the
H11 tests;
(2) Ducted blower coil system heat pumps with constant-air-flow
indoor blowers installed that provide the same air flow for the
A1 and the H11 Tests; and
(3) Ducted coil-only system heat pumps.
b. For heat pumps that meet the above criteria ``1'' and ``3,'' no
minimum requirements apply to the measured external or internal,
respectively, static pressure. Use the final indoor blower control
settings as determined when setting the cooling minimum air volume
rate, and readjust the exhaust fan of the airflow measuring apparatus
if
[[Page 37075]]
necessary to reset to the cooling minimum air volume rate obtained in
section 3.1.4.2 of this appendix. For heat pumps that meet the above
criterion ``2,'' test at an external static pressure that does not
cause an automatic shutdown of the indoor blower or air volume rate
variation QVar, defined in section 3.1.4.1.1.b of this
appendix, greater than 10 percent, while being as close to, but not
less than, the same target minimum external static pressure as was
specified for the A1 cooling mode test. Additional test
steps as described in section 3.9.1(c) of this appendix are required if
the measured external static pressure exceeds the target value by more
than 0.03 inches of water.
3.1.4.5.2. Ducted Heat Pumps Where the Heating and Cooling Minimum Air
Volume Rates Are Different Due to Changes in Indoor Blower Operation,
i.e., Speed Adjustment by the System Controls
Identify the certified heating minimum air volume rate and
certified instructions for setting fan speed or controls. If there is
no certified heating minimum air volume rate, use the final indoor
blower control settings as determined when setting the cooling minimum
air volume rate, and readjust the exhaust fan of the airflow measuring
apparatus if necessary to reset to the cooling minimum air volume
obtained in section 3.1.4.2 of this appendix. Otherwise, calculate the
target minimum external static pressure as described in section 3.1.4.2
of this appendix.
a. For ducted blower coil system heat pumps that do not have a
constant-air-volume indoor blower, adjust for external static pressure
as described in section 3.1.4.2.a of this appendix for cooling minimum
air volume rate.
b. For ducted heat pumps tested with constant-air-volume indoor
blowers installed, conduct all tests that specify the heating minimum
air volume rate--(i.e., the H01, H11,
H21, and H31 Tests)--at an external static
pressure that does not cause an automatic shutdown of the indoor blower
while being as close to, but not less than the air volume rate
variation QVar, defined in section 3.1.4.1.1.b of this
appendix, greater than 10 percent, while being as close to, but not
less than the target minimum external static pressure. Additional test
steps as described in section 3.9.1.c of this appendix are required if
the measured external static pressure exceeds the target value by more
than 0.03 inches of water.
c. For ducted two-capacity blower coil system northern heat pumps,
use the appropriate approach of the above two cases.
d. For ducted two-capacity coil-only system heat pumps, use the
cooling minimum air volume rate as the heating minimum air volume rate.
For ducted two-capacity coil-only system northern heat pumps, use the
cooling full-load air volume rate as the heating minimum air volume
rate. For ducted two-capacity heating-only coil-only system heat pumps,
the heating minimum air volume rate is the higher of the rate specified
by the manufacturer in the test setup instructions included with the
unit or 75 percent of the heating full-load air volume rate. During the
laboratory tests on a coil-only system, obtain the heating minimum air
volume rate without regard to the pressure drop across the indoor coil
assembly.
e. For non-ducted heat pumps, the heating minimum air volume rate
is the air volume rate that results during each test when the unit
operates at an external static pressure of zero inches of water and at
the indoor blower setting used at low compressor capacity (two-capacity
system) or minimum compressor speed (variable-speed system). For units
having a single-speed compressor and a variable-speed, variable-air-
volume-rate indoor blower, use the lowest fan setting allowed for
heating.
f. For ducted systems with multiple indoor blowers within a single
indoor section, obtain the heating minimum air volume rate using the
same ``on'' indoor blowers as used for the cooling minimum air volume
rate. Using the target external static pressure and the certified air
volume rates, follow the procedures as described in section 3.1.4.5.2.a
of this appendix if the indoor blowers are not constant-air-volume
indoor blowers or as described in section 3.1.4.5.2.b of this appendix
if the indoor blowers are constant-air-volume indoor blowers. The sum
of the individual ``on'' indoor blowers' air volume rates is the
heating full-load air volume rate for the system.
3.1.4.6 Heating Intermediate Air Volume Rate
Identify the certified heating intermediate air volume rate and
certified instructions for setting fan speed or controls. If there is
no certified heating intermediate air volume rate, use the final indoor
blower control settings as determined when setting the heating full-
load air volume rate, and readjust the exhaust fan of the airflow
measuring apparatus if necessary to reset to the cooling full load air
volume obtained in section 3.1.4.2 of this appendix. Calculate the
target minimum external static pressure as described in section 3.1.4.2
of this appendix.
a. For ducted blower coil system heat pumps that do not have a
constant-air-volume indoor blower, adjust for external static pressure
as described in section 3.1.4.2.a of this appendix for cooling minimum
air volume rate.
b. For ducted heat pumps tested with constant-air-volume indoor
blowers installed, conduct the H2V Test at an external
static pressure that does not cause an automatic shutdown of the indoor
blower or air volume rate variation QVar, defined in section
3.1.4.1.1.b of this appendix, greater than 10 percent, while being as
close to, but not less than the target minimum external static
pressure. Additional test steps as described in section 3.9.1(c) of
this appendix are required if the measured external static pressure
exceeds the target value by more than 0.03 inches of water.
c. For non-ducted heat pumps, the heating intermediate air volume
rate is the air volume rate that results when the heat pump operates at
an external static pressure of zero inches of water and at the fan
speed selected by the controls of the unit for the H2V Test
conditions.
3.1.4.7 Heating Nominal Air Volume Rate
The manufacturer must specify the heating nominal air volume rate
and the instructions for setting fan speed or controls. Calculate
target minimum external static pressure as described in section 3.1.4.2
of this appendix. Make adjustments as described in section 3.1.4.6 of
this appendix for heating intermediate air volume rate so that the
target minimum external static pressure is met or exceeded.
3.1.5 Indoor Test Room Requirement When the Air Surrounding the Indoor
Unit Is Not Supplied From the Same Source as the Air Entering the
Indoor Unit
If using a test set-up where air is ducted directly from the air
reconditioning apparatus to the indoor coil inlet (see Figure 2, Loop
Air-Enthalpy Test Method Arrangement, of ANSI/ASHRAE 37-2009
(incorporated by reference, see Sec. 430.3)), maintain the dry bulb
temperature within the test room within 5.0 [deg]F of the
applicable sections 3.2 and 3.6 dry bulb temperature test condition for
the air entering the indoor unit. Dew point shall be within 2 [deg]F of
the required inlet conditions.
3.1.6 Air Volume Rate Calculations
For all steady-state tests and for frost accumulation (H2,
H21, H22, H2V) tests,
[[Page 37076]]
calculate the air volume rate through the indoor coil as specified in
sections 7.7.2.1 and 7.7.2.2 of ANSI/ASHRAE 37-2009. When using the
outdoor air enthalpy method, follow sections 7.7.2.1 and 7.7.2.2 of
ANSI/ASHRAE 37-2009 to calculate the air volume rate through the
outdoor coil. To express air volume rates in terms of standard air,
use:
[GRAPHIC] [TIFF OMITTED] TR08JN16.009
Where:
Vis = air volume rate of standard (dry) air, (ft\3\/
min)da
Vimx = air volume rate of the air-water vapor mixture,
(ft\3\/min)mx
v'n = specific volume of air-water vapor mixture at the
nozzle, ft\3\ per lbm of the air-water vapor mixture
Wn = humidity ratio at the nozzle, lbm of water vapor per
lbm of dry air
0.075 = the density associated with standard (dry) air, (lbm/ft\3\)
vn = specific volume of the dry air portion of the
mixture evaluated at the dry-bulb temperature, vapor content, and
barometric pressure existing at the nozzle, ft\3\ per lbm of dry
air.
Note: In the first printing of ANSI/ASHRAE 37-2009, the second
IP equation for
[GRAPHIC] [TIFF OMITTED] TR08JN16.010
3.1.7 Test Sequence
Manufacturers may optionally operate the equipment under test for a
``break-in'' period, not to exceed 20 hours, prior to conducting the
test method specified in this section. A manufacturer who elects to use
this optional compressor break-in period in its certification testing
should record this information (including the duration) in the test
data underlying the certified ratings that are required to be
maintained under 10 CFR 429.71. When testing a ducted unit (except if a
heating-only heat pump), conduct the A or A2 Test first to
establish the cooling full-load air volume rate. For ducted heat pumps
where the heating and cooling full-load air volume rates are different,
make the first heating mode test one that requires the heating full-
load air volume rate. For ducted heating-only heat pumps, conduct the
H1 or H12 Test first to establish the heating full-load air
volume rate. When conducting a cyclic test, always conduct it
immediately after the steady-state test that requires the same test
conditions. For variable-speed systems, the first test using the
cooling minimum air volume rate should precede the EV Test,
and the first test using the heating minimum air volume rate must
precede the H2V Test. The test laboratory makes all other
decisions on the test sequence.
3.1.8 Requirement for the Air Temperature Distribution Leaving the
Indoor Coil
For at least the first cooling mode test and the first heating mode
test, monitor the temperature distribution of the air leaving the
indoor coil using the grid of individual sensors described in sections
2.5 and 2.5.4 of this appendix. For the 30-minute data collection
interval used to determine capacity, the maximum spread among the
outlet dry bulb temperatures from any data sampling must not exceed 1.5
[deg]F. Install the mixing devices described in section 2.5.4.2 of this
appendix to minimize the temperature spread.
3.1.9 Requirement for the Air Temperature Distribution Entering the
Outdoor Coil
Monitor the temperatures of the air entering the outdoor coil using
the grid of temperature sensors described in section 2.11 of this
appendix. For the 30-minute data collection interval used to determine
capacity, the maximum difference between dry bulb temperatures measured
at any of these locations must not exceed 1.5 [deg]F.
3.1.10 Control of Auxiliary Resistive Heating Elements
Except as noted, disable heat pump resistance elements used for
heating indoor air at all times, including during defrost cycles and if
they are normally regulated by a heat comfort controller. For heat
pumps equipped with a heat comfort controller, enable the heat pump
resistance elements only during the below-described, short test. For
single-speed heat pumps covered under section 3.6.1 of this appendix,
the short test follows the H1 or, if conducted, the H1C Test. For two-
capacity heat pumps and heat pumps covered under section 3.6.2 of this
appendix, the short test follows the H12 Test. Set the heat
comfort controller to provide the maximum supply air temperature. With
the heat pump operating and while maintaining the heating full-load air
volume rate, measure the temperature of the air leaving the indoor-side
beginning 5 minutes after activating the heat comfort controller.
Sample the outlet dry-bulb temperature at regular intervals that span 5
minutes or less. Collect data for 10 minutes, obtaining at least 3
samples. Calculate the average outlet temperature over the 10-minute
interval, TCC.
3.2 Cooling Mode Tests for Different Types of Air Conditioners and Heat
Pumps
3.2.1 Tests for a System Having a Single-Speed Compressor and Fixed
Cooling Air Volume Rate
This set of tests is for single-speed-compressor units that do not
have a cooling minimum air volume rate or a cooling intermediate air
volume rate that is different than the cooling full load air volume
rate. Conduct two steady-state wet coil tests, the A and B Tests. Use
the two optional dry-coil tests, the steady-state C Test and the cyclic
D Test, to determine the cooling mode cyclic degradation coefficient,
CD\c\. A default value for CD\c\ may be used in
lieu of conducting the cyclic test. The default value of
CD\c\ is 0.20. If testing outdoor units of central air
conditioners or heat pumps that are not sold with indoor units, assign
CD\c\ the default value of 0.25. Table 4 specifies test
conditions for these four tests.
[[Page 37077]]
Table 4--Cooling Mode Test Conditions for Units Having a Single-Speed Compressor and a Fixed Cooling Air Volume Rate
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air entering indoor unit Air entering outdoor unit
temperature ([deg]F) temperature ([deg]F)
Test description ---------------------------------------------------------------- Cooling air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb
--------------------------------------------------------------------------------------------------------------------------------------------------------
A Test--required (steady, wet coil)......... 80 67 95 \1\ 75 Cooling full-load.\2\
B Test--required (steady, wet coil)......... 80 67 82 \1\ 65 Cooling full-load.\2\
C Test--optional (steady, dry coil)......... 80 (\3\) 82 .............. Cooling full-load.\2\
D Test--optional (cyclic, dry coil)......... 80 (\3\) 82 .............. (\4\)
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ The specified test condition only applies if the unit rejects condensate to the outdoor coil.
\2\ Defined in section 3.1.4.1 of this appendix.
\3\ The entering air must have a low enough moisture content so no condensate forms on the indoor coil. (It is recommended that an indoor wet-bulb
temperature of 57 [deg]F or less be used.)
\4\ Maintain the airflow nozzles static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the C Test.
3.2.2 Tests for a Unit Having a Single-Speed Compressor Where the
Indoor Section Uses a Single Variable-Speed Variable-Air-Volume Rate
Indoor Blower or mUltiple Indoor Blowers
3.2.2.1 Indoor Blower Capacity Modulation That Correlates With the
Outdoor Dry Bulb Temperature or Systems With a Single Indoor cOil but
Multiple Indoor Blowers
Conduct four steady-state wet coil tests: The A2,
A1, B2, and B1 tests. Use the two
optional dry-coil tests, the steady-state C1 test and the
cyclic D1 test, to determine the cooling mode cyclic
degradation coefficient, CD\c\. A default value for
CD\c\ may be used in lieu of conducting the cyclic test. The
default value of CD\c\ is 0.20.
3.2.2.2 Indoor Blower Capacity Modulation Based on Adjusting the
Sensible to Total (S/T) Cooling Capacity Ratio
The testing requirements are the same as specified in section 3.2.1
of this appendix and Table 4. Use a cooling full-load air volume rate
that represents a normal installation. If performed, conduct the
steady-state C Test and the cyclic D Test with the unit operating in
the same S/T capacity control mode as used for the B Test.
Table 5--Cooling Mode Test Conditions for Units With a Single-Speed Compressor That Meet the Section 3.2.2.1 Indoor Unit Requirements
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air entering indoor unit Air entering outdoor unit
temperature ([deg]F) temperature ([deg]F)
Test description ---------------------------------------------------------------- Cooling air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb
--------------------------------------------------------------------------------------------------------------------------------------------------------
A2 Test--required (steady, wet coil)........ 80 67 95 \1\ 75 Cooling full-load.\2\
A1 Test--required (steady, wet coil)........ 80 67 95 \1\ 75 Cooling minimum.\3\
B2 Test--required (steady, wet coil)........ 80 67 82 \1\ 65 Cooling full-load.\2\
B1 Test--required (steady, wet coil)........ 80 67 82 \1\ 65 Cooling minimum.\3\
C1 Test\4\--optional (steady, dry coil)..... 80 (\4\) 82 .............. Cooling minimum.\3\
D1 Test\4\--optional (cyclic, dry coil)..... 80 (\4\) 82 .............. (\5\)
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ The specified test condition only applies if the unit rejects condensate to the outdoor coil.
\2\ Defined in section 3.1.4.1 of this appendix.
\3\ Defined in section 3.1.4.2 of this appendix.
\4\ The entering air must have a low enough moisture content so no condensate forms on the indoor coil. (It is recommended that an indoor wet-bulb
temperature of 57 [deg]F or less be used.)
\5\ Maintain the airflow nozzles static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the C1 Test.
3.2.3 Tests for a Unit Having a Two-Capacity Compressor (See Section
1.2 of This Appendix, Definitions)
a. Conduct four steady-state wet coil tests: the A2,
B2, B1, and F1 Tests. Use the two
optional dry-coil tests, the steady-state C1 Test and the
cyclic D1 Test, to determine the cooling-mode cyclic-
degradation coefficient, CD\c\. A default value for
CD\c\ may be used in lieu of conducting the cyclic test. The
default value of CD\c\ is 0.20. Table 6 specifies test
conditions for these six tests.
b. For units having a variable speed indoor blower that is
modulated to adjust the sensible to total (S/T) cooling capacity ratio,
use cooling full-load and cooling minimum air volume rates that
represent a normal installation. Additionally, if conducting the dry-
coil tests, operate the unit in the same S/T capacity control mode as
used for the B1 Test.
c. Test two-capacity, northern heat pumps (see section 1.2 of this
appendix, Definitions) in the same way as a single speed heat pump with
the unit operating exclusively at low compressor capacity (see section
3.2.1 of this appendix and Table 4).
d. If a two-capacity air conditioner or heat pump locks out low-
capacity operation at higher outdoor temperatures, then use the two
dry-coil tests, the steady-state C2 Test and the cyclic
D2 Test, to determine the cooling-mode cyclic-degradation
coefficient that only applies to on/off cycling from high capacity,
CD\c\(k = 2). The default CD\c\(k = 2) is the
same value as determined or assigned for the low-capacity cyclic-
degradation coefficient, CD\c\ [or equivalently,
CD\c\(k = 1)].
[[Page 37078]]
Table 6--Cooling Mode Test Conditions for Units Having a Two-Capacity Compressor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air entering indoor unit Air entering outdoor unit
temperature ([deg]F) temperature ([deg]F)
Test description ---------------------------------------------------------------- Compressor capacity Cooling air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb
--------------------------------------------------------------------------------------------------------------------------------------------------------
A2 Test--required (steady, wet 80 67 95 \1\ 75 High....................... Cooling Full-Load.\2\
coil).
B2 Test--required (steady, wet 80 67 82 \1\ 65 High....................... Cooling Full-Load.\2\
coil).
B1 Test--required (steady, wet 80 67 82 \1\ 65 Low........................ Cooling Minimum.\3\
coil).
C2 Test--optional (steady, dry- 80 (\4\) 82 .............. High....................... Cooling Full-Load.\2\
coil).
D2 Test--optional (cyclic, dry- 80 (\4\) 82 .............. High....................... (\5\)
coil).
C1 Test--optional (steady, dry- 80 (\4\) 82 .............. Low........................ Cooling Minimum.\3\
coil).
D1 Test--optional (cyclic, dry- 80 (\4\) 82 .............. Low........................ (\6\)
coil).
F1 Test--required (steady, wet 80 67 67 \1\ 53.5 Low........................ Cooling Minimum.\3\
coil).
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ The specified test condition only applies if the unit rejects condensate to the outdoor coil.
\2\ Defined in section 3.1.4.1 of this appendix.
\3\ Defined in section 3.1.4.2 of this appendix.
\4\ The entering air must have a low enough moisture content so no condensate forms on the indoor coil. DOE recommends using an indoor air wet-bulb
temperature of 57 [deg]F or less.
\5\ Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured
during the C2 Test.
\6\ Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured
during the C1 Test.
3.2.4 Tests for a Unit Having a Variable-Speed Compressor
a. Conduct five steady-state wet coil tests: The A2,
EV, B2, B1, and F1 Tests.
Use the two optional dry-coil tests, the steady-state G1
Test and the cyclic I1 Test, to determine the cooling mode
cyclic degradation coefficient, CD\c\. A default value for
CD\c\ may be used in lieu of conducting the cyclic test. The
default value of CD\c\ is 0.25. Table 7 specifies test
conditions for these seven tests. The compressor shall operate at the
same cooling full speed, measured by RPM or power input frequency (Hz),
for both the A2 and B2 tests. The compressor
shall operate at the same cooling minimum speed, measured by RPM or
power input frequency (Hz), for the B1, F1,
G1, and I1 tests. Determine the cooling
intermediate compressor speed cited in Table 7 using:
[GRAPHIC] [TIFF OMITTED] TR08JN16.011
where a tolerance of plus 5 percent or the next higher inverter
frequency step from that calculated is allowed.
b. For units that modulate the indoor blower speed to adjust the
sensible to total (S/T) cooling capacity ratio, use cooling full-load,
cooling intermediate, and cooling minimum air volume rates that
represent a normal installation. Additionally, if conducting the dry-
coil tests, operate the unit in the same S/T capacity control mode as
used for the F1 Test.
c. For multiple-split air conditioners and heat pumps (except where
noted), the following procedures supersede the above requirements: For
all Table 7 tests specified for a minimum compressor speed, at least
one indoor unit must be turned off. The manufacturer shall designate
the particular indoor unit(s) that is turned off. The manufacturer must
also specify the compressor speed used for the Table 7 EV
Test, a cooling-mode intermediate compressor speed that falls within
\1/4\ and \3/4\ of the difference between the full and minimum cooling-
mode speeds. The manufacturer should prescribe an intermediate speed
that is expected to yield the highest EER for the given EV
Test conditions and bracketed compressor speed range. The manufacturer
can designate that one or more indoor units are turned off for the
EV Test.
[[Page 37079]]
Table 7--Cooling Mode Test Condition for Units Having a Variable-Speed Compressor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air entering indoor unit Air entering outdoor unit
temperature ([deg]F) temperature ([deg]F)
Test description ---------------------------------------------------------------- Compressor speed Cooling air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb
--------------------------------------------------------------------------------------------------------------------------------------------------------
A2 Test--required (steady, wet 80 67 95 \1\ 75 Cooling Full............... Cooling Full-Load.\2\
coil).
B2 Test--required (steady, wet 80 67 82 \1\ 65 Cooling Full............... Cooling Full-Load.\2\
coil).
EV Test--required (steady, wet 80 67 87 \1\ 69 Cooling Intermediate....... Cooling Intermediate.\3\
coil).
B1 Test--required (steady, wet 80 67 82 \1\ 65 Cooling Minimum............ Cooling Minimum.\4\
coil).
F1 Test--required (steady, wet 80 67 67 \1\ 53.5 Cooling Minimum............ Cooling Minimum.\4\
coil).
G1 Test \5\--optional (steady, 80 (\6\) 67 .............. Cooling Minimum............ Cooling Minimum.\4\
dry-coil).
I1 Test \5\--optional (cyclic, 80 (\6\) 67 .............. Cooling Minimum............ (\6\)
dry-coil).
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ The specified test condition only applies if the unit rejects condensate to the outdoor coil.
\2\ Defined in section 3.1.4.1 of this appendix.
\3\ Defined in section 3.1.4.3 of this appendix.
\4\ Defined in section 3.1.4.2 of this appendix.
\5\ The entering air must have a low enough moisture content so no condensate forms on the indoor coil. DOE recommends using an indoor air wet bulb
temperature of 57 [deg]F or less.
\6\ Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the G1 Test.
3.2.5 Cooling Mode Tests for Northern Heat Pumps With Triple-Capacity
Compressors
Test triple-capacity, northern heat pumps for the cooling mode in
the same way as specified in section 3.2.3 of this appendix for units
having a two-capacity compressor.
3.2.6 Tests for an Air Conditioner or Heat Pump Having a Single Indoor
Unit Having Multiple Indoor Blowers and Offering Two Stages of
Compressor Modulation
Conduct the cooling mode tests specified in section 3.2.3 of this
appendix.
3.3 Test Procedures for Steady-State Wet Coil Cooling Mode Tests (the
A, A2, A1, B, B2, B1,
EV, and F1 Tests)
a. For the pretest interval, operate the test room reconditioning
apparatus and the unit to be tested until maintaining equilibrium
conditions for at least 30 minutes at the specified section 3.2 test
conditions. Use the exhaust fan of the airflow measuring apparatus and,
if installed, the indoor blower of the test unit to obtain and then
maintain the indoor air volume rate and/or external static pressure
specified for the particular test. Continuously record (see section 1.2
of this appendix, Definitions):
(1) The dry-bulb temperature of the air entering the indoor coil,
(2) The water vapor content of the air entering the indoor coil,
(3) The dry-bulb temperature of the air entering the outdoor coil,
and
(4) For the section 2.2.4 of this appendix cases where its control
is required, the water vapor content of the air entering the outdoor
coil.
Refer to section 3.11 of this appendix for additional requirements
that depend on the selected secondary test method.
b. After satisfying the pretest equilibrium requirements, make the
measurements specified in Table 3 of ANSI/ASHRAE 37-2009 for the indoor
air enthalpy method and the user-selected secondary method. Make said
Table 3 measurements at equal intervals that span 5 minutes or less.
Continue data sampling until reaching a 30-minute period (e.g., seven
consecutive 5-minute samples) where the test tolerances specified in
Table 8 are satisfied. For those continuously recorded parameters, use
the entire data set from the 30-minute interval to evaluate Table 8
compliance. Determine the average electrical power consumption of the
air conditioner or heat pump over the same 30-minute interval.
c. Calculate indoor-side total cooling capacity and sensible
cooling capacity as specified in sections 7.3.3.1 and 7.3.3.3 of ANSI/
ASHRAE 37-2009 (incorporated by reference, see Sec. 430.3). To
calculate capacity, use the averages of the measurements (e.g. inlet
and outlet dry bulb and wet bulb temperatures measured at the
psychrometers) that are continuously recorded for the same 30-minute
interval used as described above to evaluate compliance with test
tolerances. Do not adjust the parameters used in calculating capacity
for the permitted variations in test conditions. Evaluate air
enthalpies based on the measured barometric pressure. Use the values of
the specific heat of air given in section 7.3.3.1 of ANSI/ASHRAE 37-
2009 (incorporated by reference, see Sec. 430.3) for calculation of
the sensible cooling capacities. Assign the average total space cooling
capacity, average sensible cooling capacity, and electrical power
consumption over the 30-minute data collection interval to the
variables Qc\k\(T), Qsc\k\(T) and
Ec\k\(T), respectively. For these three variables, replace
the ``T'' with the nominal outdoor temperature at which the test was
conducted. The superscript k is used only when testing multi-capacity
units. Use the superscript k = 2 to denote a test with the unit
operating at high capacity or full speed, k = 1 to denote low capacity
or minimum speed, and k = v to denote the intermediate speed.
d. For coil-only system tests, decrease Qc\k\(T) by
[[Page 37080]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.012
where Vis is the average measured indoor air volume rate
expressed in units of cubic feet per minute of standard air (scfm).
Table 8--Test Operating and Test Condition Tolerances for Section 3.3
Steady-State Wet Coil Cooling Mode Tests and Section 3.4 Dry Coil
Cooling Mode Tests
------------------------------------------------------------------------
Test operating Test condition
tolerance \1\ tolerance \1\
------------------------------------------------------------------------
Indoor dry-bulb, [deg]F:
Entering temperature................ 2.0 0.5
Leaving temperature................. 2.0 ..............
Indoor wet-bulb, [deg]F:
Entering temperature................ 1.0 \2\ 0.3
Leaving temperature................. \2\ 1.0 ..............
Outdoor dry-bulb, [deg]F:
Entering temperature................ 2.0 0.5
Leaving temperature................. \3\ 2.0 ..............
Outdoor wet-bulb, [deg]F:
Entering temperature................ 1.0 \4\ 0.3
Leaving temperature................. \3\ 1.0 ..............
External resistance to airflow, inches 0.12 \5\ 0.02
of water...............................
Electrical voltage, % of rdg............ 2.0 1.5
Nozzle pressure drop, % of rdg.......... 8.0 ..............
------------------------------------------------------------------------
\1\ See section 1.2 of this appendix, Definitions.
\2\ Only applies during wet coil tests; does not apply during steady-
state, dry coil cooling mode tests.
\3\ Only applies when using the outdoor air enthalpy method.
\4\ Only applies during wet coil cooling mode tests where the unit
rejects condensate to the outdoor coil.
\5\ Only applies when testing non-ducted units.
e. For air conditioners and heat pumps having a constant-air-
volume-rate indoor blower, the five additional steps listed below are
required if the average of the measured external static pressures
exceeds the applicable sections 3.1.4 minimum (or target) external
static pressure ([Delta]Pmin) by 0.03 inches of water or
more.
(1) Measure the average power consumption of the indoor blower
motor (Efan,1) and record the corresponding external static
pressure ([Delta]P1) during or immediately following the 30-
minute interval used for determining capacity.
(2) After completing the 30-minute interval and while maintaining
the same test conditions, adjust the exhaust fan of the airflow
measuring apparatus until the external static pressure increases to
approximately [Delta]P1 + ([Delta]P1 -
[Delta]Pmin).
(3) After re-establishing steady readings of the fan motor power
and external static pressure, determine average values for the indoor
blower power (Efan,2) and the external static pressure
([Delta]P2) by making measurements over a 5-minute interval.
(4) Approximate the average power consumption of the indoor blower
motor at [Delta]Pmin using linear extrapolation:
[GRAPHIC] [TIFF OMITTED] TR08JN16.013
(5) Increase the total space cooling capacity, Qc\k\(T),
by the quantity (Efan,1 - Efan,min), when
expressed on a Btu/h basis. Decrease the total electrical power,
Ec\k\(T), by the same fan power difference, now expressed in
watts.
3.4 Test Procedures for the Steady-State Dry-Coil Cooling-Mode Tests
(the C, C1, C2, and G1 Tests)
a. Except for the modifications noted in this section, conduct the
steady-state dry coil cooling mode tests as specified in section 3.3 of
this appendix for wet coil tests. Prior to recording data during the
steady-state dry coil test, operate the unit at least one hour after
achieving dry coil conditions. Drain the drain pan and plug the drain
opening. Thereafter, the drain pan should remain completely dry.
b. Denote the resulting total space cooling capacity and electrical
power derived from the test as Qss,dry and
Ess,dry. With regard to a section 3.3 deviation, do not
adjust Qss,dry for duct losses (i.e., do not apply section
7.3.3.3 of ANSI/ASHRAE 37-2009). In preparing for the section 3.5
cyclic tests of this appendix, record the average indoor-side air
volume rate, Vi, specific heat of the air, Cp,a (expressed on dry air
basis), specific volume of the air at the nozzles, v'n,
humidity ratio at the nozzles, Wn, and either pressure
difference or velocity pressure for the flow nozzles.
[[Page 37081]]
For units having a variable-speed indoor blower (that provides either a
constant or variable air volume rate) that will or may be tested during
the cyclic dry coil cooling mode test with the indoor blower turned off
(see section 3.5 of this appendix), include the electrical power used
by the indoor blower motor among the recorded parameters from the 30-
minute test.
c. If the temperature sensors used to provide the primary
measurement of the indoor-side dry bulb temperature difference during
the steady-state dry-coil test and the subsequent cyclic dry- coil test
are different, include measurements of the latter sensors among the
regularly sampled data. Beginning at the start of the 30-minute data
collection period, measure and compute the indoor-side air dry-bulb
temperature difference using both sets of instrumentation, [Delta]T
(Set SS) and [Delta]T (Set CYC), for each equally spaced data sample.
If using a consistent data sampling rate that is less than 1 minute,
calculate and record minutely averages for the two temperature
differences. If using a consistent sampling rate of one minute or more,
calculate and record the two temperature differences from each data
sample. After having recorded the seventh (i = 7) set of temperature
differences, calculate the following ratio using the first seven sets
of values:
[GRAPHIC] [TIFF OMITTED] TR08JN16.014
Each time a subsequent set of temperature differences is recorded (if
sampling more frequently than every 5 minutes), calculate
FCD using the most recent seven sets of values. Continue
these calculations until the 30-minute period is completed or until a
value for FCD is calculated that falls outside the allowable
range of 0.94-1.06. If the latter occurs, immediately suspend the test
and identify the cause for the disparity in the two temperature
difference measurements. Recalibration of one or both sets of
instrumentation may be required. If all the values for FCD
are within the allowable range, save the final value of the ratio from
the 30-minute test as FCD*. If the temperature sensors used
to provide the primary measurement of the indoor-side dry bulb
temperature difference during the steady-state dry-coil test and the
subsequent cyclic dry-coil test are the same, set FCD* = 1.
3.5 Test Procedures for the Cyclic Dry-Coil Cooling-Mode Tests (the D,
D1, D2, and I1 Tests)
After completing the steady-state dry-coil test, remove the outdoor
air enthalpy method test apparatus, if connected, and begin manual OFF/
ON cycling of the unit's compressor. The test set-up should otherwise
be identical to the set-up used during the steady-state dry coil test.
When testing heat pumps, leave the reversing valve during the
compressor OFF cycles in the same position as used for the compressor
ON cycles, unless automatically changed by the controls of the unit.
For units having a variable-speed indoor blower, the manufacturer has
the option of electing at the outset whether to conduct the cyclic test
with the indoor blower enabled or disabled. Always revert to testing
with the indoor blower disabled if cyclic testing with the fan enabled
is unsuccessful.
a. For all cyclic tests, the measured capacity must be adjusted for
the thermal mass stored in devices and connections located between
measured points. Follow the procedure outlined in section 7.4.3.4.5 of
ASHRAE 116-2010 (incorporated by reference, see Sec. 430.3) to ensure
any required measurements are taken.
b. For units having a single-speed or two-capacity compressor,
cycle the compressor OFF for 24 minutes and then ON for 6 minutes
([Delta][tau]cyc,dry = 0.5 hours). For units having a
variable-speed compressor, cycle the compressor OFF for 48 minutes and
then ON for 12 minutes ([Delta][tau]cyc,dry = 1.0 hours).
Repeat the OFF/ON compressor cycling pattern until the test is
completed. Allow the controls of the unit to regulate cycling of the
outdoor fan. If an upturned duct is used, measure the dry-bulb
temperature at the inlet of the device at least once every minute and
ensure that its test operating tolerance is within 1.0 [deg]F for each
compressor OFF period.
c. Sections 3.5.1 and 3.5.2 of this appendix specify airflow
requirements through the indoor coil of ducted and non-ducted indoor
units, respectively. In all cases, use the exhaust fan of the airflow
measuring apparatus (covered under section 2.6 of this appendix) along
with the indoor blower of the unit, if installed and operating, to
approximate a step response in the indoor coil airflow. Regulate the
exhaust fan to quickly obtain and then maintain the flow nozzle static
pressure difference or velocity pressure at the same value as was
measured during the steady-state dry coil test. The pressure difference
or velocity pressure should be within 2 percent of the value from the
steady-state dry coil test within 15 seconds after airflow initiation.
For units having a variable-speed indoor blower that ramps when cycling
on and/or off, use the exhaust fan of the airflow measuring apparatus
to impose a step response that begins at the initiation of ramp up and
ends at the termination of ramp down.
d. For units having a variable-speed indoor blower, conduct the
cyclic dry coil test using the pull-thru approach described below if
any of the following occur when testing with the fan operating:
(1) The test unit automatically cycles off;
(2) Its blower motor reverses; or
(3) The unit operates for more than 30 seconds at an external
static pressure that is 0.1 inches of water or more higher than the
value measured during the prior steady-state test.
For the pull-thru approach, disable the indoor blower and use the
exhaust fan of the airflow measuring apparatus to generate the
specified flow nozzles static pressure difference or velocity pressure.
If the exhaust fan cannot deliver the required pressure difference
because of resistance created by the unpowered indoor blower,
temporarily remove the indoor blower.
e. Conduct three complete compressor OFF/ON cycles with the test
tolerances given in Table 9 satisfied. Calculate the degradation
coefficient CD for each complete cycle. If all three
CD values are within 0.02 of the average CD then
stability has been achieved, and the highest CD value of
these three shall be used. If stability has not been achieved, conduct
additional cycles, up to a maximum of eight cycles total, until
stability has been achieved between three consecutive cycles. Once
stability has been achieved, use the highest CD value of the
three consecutive cycles that establish stability. If stability has not
been achieved after eight cycles, use the highest CD from
cycle one through cycle eight, or the default CD, whichever
is lower.
f. With regard to the Table 9 parameters, continuously record the
dry-bulb temperature of the air entering the indoor and outdoor coils
during periods when air flows through the respective coils. Sample the
water vapor content of the indoor coil inlet air at least every 2
minutes during periods when air flows through the coil. Record external
static pressure and the air volume rate indicator (either nozzle
pressure difference or velocity pressure) at least every minute during
the interval that air flows through the indoor coil. (These regular
measurements of the airflow rate indicator are in addition to
[[Page 37082]]
the required measurement at 15 seconds after flow initiation.) Sample
the electrical voltage at least every 2 minutes beginning 30 seconds
after compressor start-up. Continue until the compressor, the outdoor
fan, and the indoor blower (if it is installed and operating) cycle
off.
g. For ducted units, continuously record the dry-bulb temperature
of the air entering (as noted above) and leaving the indoor coil. Or if
using a thermopile, continuously record the difference between these
two temperatures during the interval that air flows through the indoor
coil. For non-ducted units, make the same dry-bulb temperature
measurements beginning when the compressor cycles on and ending when
indoor coil airflow ceases.
h. Integrate the electrical power over complete cycles of length
[Delta][tau]cyc,dry. For ducted blower coil systems tested
with the unit's indoor blower operating for the cycling test, integrate
electrical power from indoor blower OFF to indoor blower OFF. For all
other ducted units and for non-ducted units, integrate electrical power
from compressor OFF to compressor OFF. (Some cyclic tests will use the
same data collection intervals to determine the electrical energy and
the total space cooling. For other units, terminate data collection
used to determine the electrical energy before terminating data
collection used to determine total space cooling.)
Table 9--Test Operating and Test Condition Tolerances for Cyclic Dry
Coil Cooling Mode Tests
------------------------------------------------------------------------
Test operating Test condition
tolerance \1\ tolerance \1\
------------------------------------------------------------------------
Indoor entering dry-bulb temperature,\2\ 2.0 0.5
[deg]F.................................
Indoor entering wet-bulb temperature, .............. (\3\)
[deg]F.................................
Outdoor entering dry-bulb 2.0 0.5
temperature,\2\ [deg]F.................
External resistance to airflow,\2\ 0.12 ..............
inches of water........................
Airflow nozzle pressure difference or 8.0 \4\ 2.0
velocity pressure,\2\ % of reading.....
Electrical voltage \5\, % of rdg........ 2.0 1.5
------------------------------------------------------------------------
\1\See section 1.2 of this appendix, Definitions.
\2\Applies during the interval that air flows through the indoor
(outdoor) coil except for the first 30 seconds after flow initiation.
For units having a variable-speed indoor blower that ramps, the
tolerances listed for the external resistance to airflow apply from 30
seconds after achieving full speed until ramp down begins.
\3\Shall at no time exceed a wet-bulb temperature that results in
condensate forming on the indoor coil.
\4\The test condition shall be the average nozzle pressure difference or
velocity pressure measured during the steady-state dry coil test.
\5\Applies during the interval when at least one of the following--the
compressor, the outdoor fan, or, if applicable, the indoor blower--are
operating except for the first 30 seconds after compressor start-up.
If the Table 9 tolerances are satisfied over the complete cycle,
record the measured electrical energy consumption as
ecyc,dry and express it in units of watt-hours. Calculate
the total space cooling delivered, qcyc,dry, in units of Btu
using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.015
Where,
Vi, Cp,a, v'n (or vn),
Wn, and FCD* are the values recorded during
the section 3.4 dry coil steady-state test and
Tal([tau]) = dry bulb temperature of the air entering the
indoor coil at time [tau], [deg]F.
Ta2([tau]) = dry bulb temperature of the air leaving the
indoor coil at time [tau], [deg]F.
[tau]1 = for ducted units, the elapsed time when airflow
is initiated through the indoor coil; for non-ducted units, the
elapsed time when the compressor is cycled on, hr.
[tau]2 = the elapsed time when indoor coil airflow
ceases, hr.
Adjust the total space cooling delivered, qcyc,dry,
according to calculation method outlined in section 7.4.3.4.5 of ASHRAE
116-2010 (incorporated by reference, see Sec. 430.3).
3.5.1 Procedures When Testing Ducted Systems
The automatic controls that are normally installed with the test
unit must govern the OFF/ON cycling of the air moving equipment on the
indoor side (exhaust fan of the airflow measuring apparatus and, if
installed, the indoor blower of the test unit). For example, for ducted
coil-only systems rated based on using a fan time delay relay, control
the indoor coil airflow according to the rated ON and/or OFF delays
provided by the relay. For ducted units having a variable-speed indoor
blower that has been disabled (and possibly removed), start and stop
the indoor airflow at the same instances as if the fan were enabled.
For all other ducted coil-only systems, cycle the indoor coil airflow
in unison with the cycling of the compressor. If air damper boxes are
used, close them on the inlet and outlet side during the OFF period.
Airflow through the indoor coil should stop within 3 seconds after the
automatic controls of the test unit (act to) de-energize the indoor
blower. For ducted coil-only systems (excluding the special case where
a variable-speed fan is temporarily removed), increase
ecyc,dry by the quantity,
[[Page 37083]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.016
where Vis is the average indoor air volume rate from the
section 3.4 dry coil steady-state test and is expressed in units of
cubic feet per minute of standard air (scfm). For units having a
variable-speed indoor blower that is disabled during the cyclic test,
increase ecyc,dry and decrease qcyc,dry based on:
a. The product of [[tau]2 - [tau]1] and the
indoor blower power measured during or following the dry coil steady-
state test; or,
b. The following algorithm if the indoor blower ramps its speed
when cycling.
(1) Measure the electrical power consumed by the variable-speed
indoor blower at a minimum of three operating conditions: At the speed/
air volume rate/external static pressure that was measured during the
steady-state test, at operating conditions associated with the midpoint
of the ramp-up interval, and at conditions associated with the midpoint
of the ramp-down interval. For these measurements, the tolerances on
the airflow volume or the external static pressure are the same as
required for the section 3.4 steady-state test.
(2) For each case, determine the fan power from measurements made
over a minimum of 5 minutes.
(3) Approximate the electrical energy consumption of the indoor
blower if it had operated during the cyclic test using all three power
measurements. Assume a linear profile during the ramp intervals. The
manufacturer must provide the durations of the ramp-up and ramp-down
intervals. If the test setup instructions included with the unit by the
manufacturer specifies a ramp interval that exceeds 45 seconds, use a
45-second ramp interval nonetheless when estimating the fan energy.
3.5.2 Procedures When Testing Non-Ducted Indoor Units
Do not use airflow prevention devices when conducting cyclic tests
on non-ducted indoor units. Until the last OFF/ON compressor cycle,
airflow through the indoor coil must cycle off and on in unison with
the compressor. For the last OFF/ON compressor cycle--the one used to
determine ecyc,dry and qcyc,dry--use the exhaust
fan of the airflow measuring apparatus and the indoor blower of the
test unit to have indoor airflow start 3 minutes prior to compressor
cut-on and end three minutes after compressor cutoff. Subtract the
electrical energy used by the indoor blower during the 3 minutes prior
to compressor cut-on from the integrated electrical energy,
ecyc,dry. Add the electrical energy used by the indoor
blower during the 3 minutes after compressor cutoff to the integrated
cooling capacity, qcyc,dry. For the case where the non-
ducted indoor unit uses a variable-speed indoor blower which is
disabled during the cyclic test, correct ecyc,dry and
qcyc,dry using the same approach as prescribed in section
3.5.1 of this appendix for ducted units having a disabled variable-
speed indoor blower.
3.5.3 Cooling-Mode Cyclic-Degradation Coefficient Calculation
Use the two dry-coil tests to determine the cooling-mode cyclic-
degradation coefficient, CD\c\. Append ``(k = 2)'' to the
coefficient if it corresponds to a two-capacity unit cycling at high
capacity. The default value for two-capacity units cycling at high
capacity, however, is the low-capacity coefficient, i.e.,
CD\c\(k = 2) = CD\c\. Evaluate CD\c\
using the above results and those from the section 3.4 dry-coil steady-
state test.
[GRAPHIC] [TIFF OMITTED] TR08JN16.017
where:
[GRAPHIC] [TIFF OMITTED] TR08JN16.018
the average energy efficiency ratio during the cyclic dry coil cooling
mode test, Btu/W[middot]h
[GRAPHIC] [TIFF OMITTED] TR08JN16.019
the average energy efficiency ratio during the steady-state dry coil
cooling mode test, Btu/W[middot]h
[GRAPHIC] [TIFF OMITTED] TR08JN16.020
the cooling load factor dimensionless
Round the calculated value for CD\c\ to the nearest 0.01. If
CD\c\ is negative, then set it equal to zero.
3.6 Heating Mode Tests for Different Types of Heat Pumps, Including
Heating-Only Heat Pumps
3.6.1 Tests for a Heat Pump Having a Single-Speed Compressor and Fixed
Heating Air Volume Rate
This set of tests is for single-speed-compressor heat pumps that do
not have a heating minimum air volume rate or a heating intermediate
air volume rate that is different than the heating full load air volume
rate. Conduct the optional high temperature cyclic (H1C) test to
determine the heating mode cyclic-degradation coefficient,
CD\h\. A default value for CD\h\ may be used in
lieu of conducting the cyclic test. The default value of
CD\h\ is 0.25. Test conditions for the four tests are
specified in Table 10.
[[Page 37084]]
Table 10--Heating Mode Test Conditions for Units Having a Single-Speed Compressor and a Fixed-Speed Indoor Blower, a Constant Air Volume Rate Indoor
Blower, or No Indoor Blower
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air entering indoor unit Air entering outdoor unit
temperature ([deg]F) temperature ([deg]F)
Test description ---------------------------------------------------------------- Heating air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb
--------------------------------------------------------------------------------------------------------------------------------------------------------
H1 Test (required, steady).................. 70 60 \(max)\ 47 43 Heating Full-load.\1\
H1C Test (optional, cyclic)................. 70 60 \(max)\ 47 43 (\2\).
H2 Test (required).......................... 70 60 \(max)\ 35 33 Heating Full-load.\1\
H3 Test (required, steady).................. 70 60 \(max)\ 17 15 Heating Full-load.\1\
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Defined in section 3.1.4.4 of this appendix.
\2\ Maintain the airflow nozzles static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the H1 Test.
3.6.2 Tests for a heat pump having a single-speed compressor and a
single indoor unit having either (1) a variable speed, variable-air-
rate indoor blower whose capacity modulation correlates with outdoor
dry bulb temperature or (2) multiple indoor blowers. Conduct five
tests: Two high temperature tests (H12 and H11),
one frost accumulation test (H22), and two low temperature
tests (H32 and H31). Conducting an additional
frost accumulation test (H21) is optional. Conduct the
optional high temperature cyclic (H1C1) test to determine
the heating mode cyclic-degradation coefficient, CD\h\. A
default value for CD\h\ may be used in lieu of conducting
the cyclic. The default value of CD\h\ is 0.25. Test
conditions for the seven tests are specified in Table 11. If the
optional H21 test is not performed, use the following
equations to approximate the capacity and electrical power of the heat
pump at the H21 test conditions:
[GRAPHIC] [TIFF OMITTED] TR08JN16.021
where:
[GRAPHIC] [TIFF OMITTED] TR08JN16.022
The quantities Qh\k=2\(47), Eh\k=2\(47),
Qh\k=1\(47), and Eh\k=1\(47) are determined from
the H12 and H11 tests and evaluated as specified
in section 3.7 of this appendix; the quantities Qh\k=2\(35)
and Eh\k=2\(35) are determined from the H22 test
and evaluated as specified in section 3.9 of this appendix; and the
quantities Qh\k=2\(17), Eh\k=2\(17),
Qh\k=1\(17), and Eh\k=1\(17), are determined from
the H32 and H31 tests and evaluated as specified
in section 3.10 of this appendix.
Table 11--Heating Mode Test Conditions for Units With a Single-Speed Compressor That Meet the Section 3.6.2 Indoor Unit Requirements
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air entering indoor unit Air entering outdoor unit
temperature ([deg]F) temperature ([deg]F)
Test description ---------------------------------------------------------------- Heating air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb
--------------------------------------------------------------------------------------------------------------------------------------------------------
H12 Test (required, steady)................. 70 60 \(max)\ 47 43 Heating Full-load.\1\
H11 Test (required, steady)................. 70 60 \(max)\ 47 43 Heating Minimum.\2\
H1C1 Test (optional, cyclic)................ 70 60 \(max)\ 47 43 (\3\)
H22 Test (required)......................... 70 60 \(max)\ 35 33 Heating Full-load.\1\
H21 Test (optional)......................... 70 60 \(max)\ 35 33 Heating Minimum.\2\
H32 Test (required, steady)................. 70 60 \(max)\ 17 15 Heating Full-load.\1\
[[Page 37085]]
H31 Test (required, steady)................. 70 60 \(max)\ 17 15 Heating Minimum.\2\
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Defined in section 3.1.4.4 of this appendix.
\2\ Defined in section 3.1.4.5 of this appendix.
\3\ Maintain the airflow nozzles static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the H11 test.
3.6.3 Tests for a Heat Pump Having a Two-Capacity Compressor (see
Section 1.2 of This Appendix, Definitions), Including Two-Capacity,
Northern Heat Pumps (see Section 1.2 of This Appendix, Definitions)
a. Conduct one maximum temperature test (H01), two high
temperature tests (H12 and H11), one frost
accumulation test (H22), and one low temperature test
(H32). Conduct an additional frost accumulation test
(H21) and low temperature test (H31) if both of
the following conditions exist:
(1) Knowledge of the heat pump's capacity and electrical power at
low compressor capacity for outdoor temperatures of 37 [deg]F and less
is needed to complete the section 4.2.3 of this appendix seasonal
performance calculations; and
(2) The heat pump's controls allow low-capacity operation at
outdoor temperatures of 37 [deg]F and less.
If the above two conditions are met, an alternative to conducting
the H21 frost accumulation is to use the following equations
to approximate the capacity and electrical power:
[GRAPHIC] [TIFF OMITTED] TR08JN16.023
Determine the quantities Qh\k=1\ (47) and
Eh\k=1\ (47) from the H11 test and evaluate them
according to section 3.7 of this appendix. Determine the quantities
Qh\k=1\ (17) and Eh\k=1\ (17) from the
H31 test and evaluate them according to section 3.10 of this
appendix.
b. Conduct the optional high temperature cyclic test
(H1C1) to determine the heating mode cyclic-degradation
coefficient, CD\h\. A default value for CD\h\ may
be used in lieu of conducting the cyclic. The default value of
CD\h\ is 0.25. If a two-capacity heat pump locks out low
capacity operation at lower outdoor temperatures, conduct the high
temperature cyclic test (H1C2) to determine the high-
capacity heating mode cyclic-degradation coefficient, CD\h\
(k=2). The default CD\h\ (k=2) is the same value as
determined or assigned for the low-capacity cyclic-degradation
coefficient, CD\h\ [or equivalently, CD\h\
(k=1)]. Table 12 specifies test conditions for these nine tests.
Table 12--Heating Mode Test Conditions for Units Having a Two-Capacity Compressor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air entering indoor unit Air entering outdoor unit
temperature ([deg]F) temperature ([deg]F)
Test description ---------------------------------------------------------------- Compressor capacity Heating air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb
--------------------------------------------------------------------------------------------------------------------------------------------------------
H01 Test (required, steady)... 70 60(max) 62 56.5 Low........................ Heating Minimum.\1\
H12 Test (required, steady)... 70 60(max) 47 43 High....................... Heating Full-Load.\2\
H1C2 Test (optional,\7\ 70 60(max) 47 43 High....................... (\3\)
cyclic).
H11 Test (required)........... 70 60(max) 47 43 Low........................ Heating Minimum.\1\
H1C1 Test (optional, cyclic).. 70 60(max) 47 43 Low........................ (\4\)
H22 Test (required)........... 70 60(max) 35 33 High....................... Heating Full-Load.\2\
H21 Test \5 6\ (required)..... 70 60(max) 35 33 Low........................ Heating Minimum.\1\
H32 Test (required, steady)... 70 60(max) 17 15 High....................... Heating Full-Load.\2\
H31 Test \5\ (required, 70 60(max) 17 15 Low........................ Heating Minimum.\1\
steady).
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Defined in section 3.1.4.5 of this appendix.
\2\ Defined in section 3.1.4.4 of this appendix.
\3\ Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured
during the H12 test.
\4\ Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured
during the H11 test.
[[Page 37086]]
\5\ Required only if the heat pump's performance when operating at low compressor capacity and outdoor temperatures less than 37 [deg]F is needed to
complete the section 4.2.3 HSPF calculations.
\6\ If table note #5 applies, the section 3.6.3 equations for Qhk=1 (35) and Ehk=1 (17) may be used in lieu of conducting the H21 test.
\7\ Required only if the heat pump locks out low capacity operation at lower outdoor temperatures.
3.6.4 Tests for a Heat Pump Having a Variable-Speed Compressor
a. Conduct one maximum temperature test (H01), two high
temperature tests (H12 and H11), one frost
accumulation test (H2V), and one low temperature test
(H32). Conducting one or both of the following tests is
optional: An additional high temperature test (H1N) and an
additional frost accumulation test (H22). Conduct the
optional maximum temperature cyclic (H0C1) test to determine
the heating mode cyclic-degradation coefficient, CD\h\. A
default value for CD\h\ may be used in lieu of conducting
the cyclic. The default value of CD\h\ is 0.25. Test
conditions for the eight tests are specified in Table 13. The
compressor shall operate at the same heating full speed, measured by
RPM or power input frequency (Hz), for the H12,
H22, and H32 tests. The compressor shall operate
at the same heating minimum speed, measured by RPM or power input
frequency (Hz), for the H01, H0C1, and
H11 tests. Determine the heating intermediate compressor
speed cited in Table 13 using the heating mode full and minimum
compressors speeds and:
Heating intermediate speed
[GRAPHIC] [TIFF OMITTED] TR08JN16.024
Where a tolerance of plus 5 percent or the next higher inverter
frequency step from that calculated is allowed.
If the H22 test is not done, use the following equations
to approximate the capacity and electrical power at the H22
test conditions:
[GRAPHIC] [TIFF OMITTED] TR08JN16.025
b. Determine the quantities Qhk=2(47) and
from Ehk=2(47) from the H12 test and
evaluate them according to section 3.7 of this appendix. Determine the
quantities Qhk=2(17) and
Ehk=2(17) from the H32 test and
evaluate them according to section 3.10 of this appendix. For heat
pumps where the heating mode full compressor speed exceeds its cooling
mode full compressor speed, conduct the H1N test if the
manufacturer requests it. If the H1N test is done, operate
the heat pump's compressor at the same speed as the speed used for the
cooling mode A2 test. Refer to the last sentence of section
4.2 of this appendix to see how the results of the H1N test
may be used in calculating the heating seasonal performance factor.
Table 13--Heating Mode Test Conditions for Units Having a Variable-Speed Compressor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air entering indoor unit Air entering outdoor unit
temperature ([deg]F) temperature ([deg]F)
Test description ---------------------------------------------------------------- Compressor speed Heating air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb
--------------------------------------------------------------------------------------------------------------------------------------------------------
H01 test (required, steady)... 70 60(max) 62 56.5 Heating Minimum............ Heating Minimum.\1\
H0C1 test (optional, cyclic).. 70 60(max) 62 56.5 Heating Minimum............ (\2\)
H12 test (required, steady)... 70 60(max) 47 43 Heating Full............... Heating Full-Load.\3\
H11 test (required, steady)... 70 60(max) 47 43 Heating Minimum............ Heating Minimum.\1\
H1N test (optional, steady)... 70 60(max) 47 43 Cooling Full............... Heating Nominal.\4\
H22 test (optional)........... 70 60(max) 35 33 Heating Full............... Heating Full-Load.\3\
H2V test (required)........... 70 60(max) 35 33 Heating Intermediate....... Heating Intermediate.\5\
H32 test (required, steady)... 70 60(max) 17 15 Heating Full............... Heating Full-Load.\3\
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Defined in section 3.1.4.5 of this appendix.
\2\ Maintain the airflow nozzle(s) static pressure difference or velocity pressure during an ON period at the same pressure or velocity as measured
during the H01 test.
\3\ Defined in section 3.1.4.4 of this appendix.
\4\ Defined in section 3.1.4.7 of this appendix.
\5\ Defined in section 3.1.4.6 of this appendix.
c. For multiple-split heat pumps (only), the following procedures
supersede the above requirements. For all Table 13 tests specified for
a minimum compressor speed, at least one indoor unit must be turned
off. The manufacturer shall designate the particular indoor unit(s)
that is turned off. The manufacturer must also specify the compressor
speed used for the Table 13 H2V test, a heating mode
intermediate compressor speed that falls
[[Page 37087]]
within \1/4\ and \3/4\ of the difference between the full and minimum
heating mode speeds. The manufacturer should prescribe an intermediate
speed that is expected to yield the highest COP for the given
H2V test conditions and bracketed compressor speed range.
The manufacturer can designate that one or more specific indoor units
are turned off for the H2V test.
3.6.5 Additional Test for a Heat Pump Having a Heat Comfort Controller
Test any heat pump that has a heat comfort controller (see section
1.2 of this appendix, Definitions) according to section 3.6.1, 3.6.2,
or 3.6.3, whichever applies, with the heat comfort controller disabled.
Additionally, conduct the abbreviated test described in section 3.1.10
of this appendix with the heat comfort controller active to determine
the system's maximum supply air temperature. (Note: Heat pumps having a
variable speed compressor and a heat comfort controller are not covered
in the test procedure at this time.)
3.6.6 Heating Mode Tests for Northern Heat Pumps With Triple-Capacity
Compressors
Test triple-capacity, northern heat pumps for the heating mode as
follows:
a. Conduct one maximum-temperature test (H01), two high-
temperature tests (H12 and H11), one frost
accumulation test (H22), two low-temperature tests
(H32, H33), and one minimum-temperature test
(H43). Conduct an additional frost accumulation test
(H21) and low- temperature test (H31) if both of
the following conditions exist: (1) Knowledge of the heat pump's
capacity and electrical power at low compressor capacity for outdoor
temperatures of 37 [deg]F and less is needed to complete the section
4.2.6 seasonal performance calculations; and (2) the heat pump's
controls allow low-capacity operation at outdoor temperatures of 37
[deg]F and less. If the above two conditions are met, an alternative to
conducting the H21 frost accumulation test to determine
Qhk=1(35) and Ehk=1(35) is
to use the following equations to approximate this capacity and
electrical power:
[GRAPHIC] [TIFF OMITTED] TR08JN16.026
In evaluating the above equations, determine the quantities
Qhk=1(47) from the H11 test and
evaluate them according to section 3.7 of this appendix. Determine the
quantities Qhk=1(17) and
Ehk=1(17) from the H31 test and
evaluate them according to section 3.10 of this appendix. Use the
paired values of Qhk=1(35) and
Ehk=1(35) derived from conducting the
H21 frost accumulation test and evaluated as specified in
section 3.9.1 of this appendix or use the paired values calculated
using the above default equations, whichever contribute to a higher
Region IV HSPF based on the DHRmin.
b. Conducting a frost accumulation test (H23) with the
heat pump operating at its booster capacity is optional. If this
optional test is not conducted, determine
Qhk=3(35) and Ehk=3(35)
using the following equations to approximate this capacity and
electrical power:
[GRAPHIC] [TIFF OMITTED] TR08JN16.027
Determine the quantities Qhk=2(47) and
Ehk=2(47) from the H12 test and
evaluate them according to section 3.7 of this appendix. Determine the
quantities Qhk=2(35) and
Ehk=2(35) from the H22 test and
evaluate them according to section 3.9.1 of this appendix. Determine
the quantities Qhk=2(17) and
Ehk=2(17) from the H32 test, determine
the quantities Qhk=3(17) and
Ehk=3(17) from the H33 test, and
determine the quantities Qhk=3(2) and
Ehk=3(2) from the H43 test. Evaluate
all six quantities according to section 3.10 of this appendix. Use the
paired values of Qhk=3(35) and
Ehk=3(35) derived from conducting the
H23 frost accumulation test and calculated as specified in
section 3.9.1 of this appendix or use the paired values calculated
using the above default equations, whichever contribute
[[Page 37088]]
to a higher Region IV HSPF based on the DHRmin.
c. Conduct the optional high-temperature cyclic test
(H1C1) to determine the heating mode cyclic-degradation
coefficient, CD\h\. A default value for CD\h\ may
be used in lieu of conducting the cyclic. The default value of
CD\h\ is 0.25. If a triple-capacity heat pump locks out low
capacity operation at lower outdoor temperatures, conduct the high-
temperature cyclic test (H1C2) to determine the high-
capacity heating mode cyclic-degradation coefficient, CD\h\
(k = 2). The default CD\h\ (k = 2) is the same value as
determined or assigned for the low-capacity cyclic-degradation
coefficient, CD\h\ [or equivalently, CD\h\ (k =
1)]. Finally, if a triple-capacity heat pump locks out both low and
high capacity operation at the lowest outdoor temperatures, conduct the
low-temperature cyclic test (H3C3) to determine the booster-
capacity heating mode cyclic-degradation coefficient, CD\h\
(k = 3). The default CD\h\ (k = 3) is the same value as
determined or assigned for the high-capacity cyclic-degradation
coefficient, CD\h\ [or equivalently, CD\h\ (k =
2)]. Table 14 specifies test conditions for all 13 tests.
Table 14--Heating Mode Test Conditions for Units With a Triple-Capacity Compressor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air entering indoor unit Air entering outdoor unit
temperature ([deg]F) temperature ([deg]F)
Test description ---------------------------------------------------------------- Compressor capacity Heating air volume rate
Dry bulb Wet bulb Dry bulb Wet bulb
--------------------------------------------------------------------------------------------------------------------------------------------------------
H01 Test (required, steady)... 70 60(max) 62 56.5 Low........................ Heating Minimum.\1\
H12 Test (required, steady)... 70 60(max) 47 43 High....................... Heating Full-Load.\2\
H1C2 Test (optional \8\, 70 60(max) 47 43 High....................... (\3\)
cyclic).
H11 Test (required)........... 70 60(max) 47 43 Low........................ Heating Minimum.\1\
H1C1 Test (optional, cyclic).. 70 60(max) 47 43 Low........................ (\4\)
H23 Test (optional, steady)... 70 60(max) 35 33 Booster.................... Heating Full-Load.\2\
H22 Test (required)........... 70 60(max) 35 33 High....................... Heating Full-Load.\2\
H21 Test (required)........... 70 60(max) 35 33 Low........................ Heating Minimum.\1\
H33 Test (required, steady)... 70 60(max) 17 15 Booster.................... Heating Full-Load.\2\
H3C3 Test \5\ \6\ (optional, 70 60(max) 17 15 Booster.................... (\7\)
cyclic).
H32 Test (required, steady)... 70 60(max) 17 15 High....................... Heating Full-Load.\2\
H31 Test \5\ (required, 70 60(max) 17 15 Low........................ Heating Minimum.\1\
steady).
H43 Test (required, steady)... 70 60(max) 2 1 Booster.................... Heating Full-Load.\2\
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Defined in section 3.1.4.5 of this appendix.
\2\ Defined in section 3.1.4.4 of this appendix.
\3\ Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured
during the H12 test.
\4\ Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured
during the H11 test.
\5\ Required only if the heat pump's performance when operating at low compressor capacity and outdoor temperatures less than 37 [deg]F is needed to
complete the section 4.2.6 HSPF calculations.
\6\ If table note \5\ applies, the section 3.6.6 equations for Qhk=1(35) and Ehk=1(17) may be used in lieu of conducting the H21 test.
\7\ Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured
during the H33 test.
\8\ Required only if the heat pump locks out low capacity operation at lower outdoor temperatures.
3.6.7 Tests for a Heat Pump Having a Single Indoor Unit Having Multiple
Indoor Blowers and Offering Two Stages of Compressor Modulation
Conduct the heating mode tests specified in section 3.6.3 of this
appendix.
3.7 Test Procedures for Steady-State Maximum Temperature and High
Temperature Heating Mode Tests (the H01, H1, H12,
H11, and H1N Tests)
a. For the pretest interval, operate the test room reconditioning
apparatus and the heat pump until equilibrium conditions are maintained
for at least 30 minutes at the specified section 3.6 test conditions.
Use the exhaust fan of the airflow measuring apparatus and, if
installed, the indoor blower of the heat pump to obtain and then
maintain the indoor air volume rate and/or the external static pressure
specified for the particular test. Continuously record the dry-bulb
temperature of the air entering the indoor coil, and the dry-bulb
temperature and water vapor content of the air entering the outdoor
coil. Refer to section 3.11 of this appendix for additional
requirements that depend on the selected secondary test method. After
satisfying the pretest equilibrium requirements, make the measurements
specified in Table 3 of ANSI/ASHRAE 37-2009 (incorporated by reference,
see Sec. 430.3) for the indoor air enthalpy method and the user-
selected secondary method. Make said Table 3 measurements at equal
intervals that span 5 minutes or less. Continue data sampling until a
30-minute period (e.g., seven consecutive 5-minute samples) is reached
where the test tolerances specified in Table 15 are satisfied. For
those continuously recorded parameters, use the entire data set for the
30-minute interval when evaluating Table 15 compliance. Determine the
average electrical power consumption of
[[Page 37089]]
the heat pump over the same 30-minute interval.
Table 15--Test Operating and Test Condition Tolerances for Section 3.7
and Section 3.10 Steady-State Heating Mode Tests
------------------------------------------------------------------------
Test operating Test condition
tolerance \1\ tolerance \1\
------------------------------------------------------------------------
Indoor dry-bulb, [deg]F:
Entering temperature................ 2.0 0.5
Leaving temperature................. 2.0
Indoor wet-bulb, [deg]F:
Entering temperature................ 1.0
Leaving temperature................. 1.0
Outdoor dry-bulb, [deg]F:
Entering temperature................ 2.0 0.5
Leaving temperature................. \2\ 2.0
Outdoor wet-bulb, [deg]F:
Entering temperature................ 1.0 0.3
Leaving temperature................. \2\ 1.0
External resistance to airflow, inches 0.12 \3\ 0.02
of water...............................
Electrical voltage, % of rdg............ 2.0 1.5
Nozzle pressure drop, % of rdg.......... 8.0
------------------------------------------------------------------------
\1\ See section 1.2 of this appendix, Definitions.
\2\ Only applies when the Outdoor Air Enthalpy Method is used.
\3\ Only applies when testing non-ducted units.
b. Calculate indoor-side total heating capacity as specified in
sections 7.3.4.1 and 7.3.4.3 of ANSI/ASHRAE 37-2009 (incorporated by
reference, see Sec. 430.3). To calculate capacity, use the averages of
the measurements (e.g. inlet and outlet dry bulb temperatures measured
at the psychrometers) that are continuously recorded for the same 30-
minute interval used as described above to evaluate compliance with
test tolerances. Do not adjust the parameters used in calculating
capacity for the permitted variations in test conditions. Assign the
average space heating capacity and electrical power over the 30-minute
data collection interval to the variables Qh\k\ and
Eh\k\(T) respectively. The ``T'' and superscripted ``k'' are
the same as described in section 3.3 of this appendix. Additionally,
for the heating mode, use the superscript to denote results from the
optional H1N test, if conducted.
c. For coil-only system heat pumps, increase Qh\k\(T) by
[GRAPHIC] [TIFF OMITTED] TR08JN16.028
where Vis is the average measured indoor air volume rate
expressed in units of cubic feet per minute of standard air (scfm).
During the 30-minute data collection interval of a high temperature
test, pay attention to preventing a defrost cycle. Prior to this time,
allow the heat pump to perform a defrost cycle if automatically
initiated by its own controls. As in all cases, wait for the heat
pump's defrost controls to automatically terminate the defrost cycle.
Heat pumps that undergo a defrost should operate in the heating mode
for at least 10 minutes after defrost termination prior to beginning
the 30-minute data collection interval. For some heat pumps, frost may
accumulate on the outdoor coil during a high temperature test. If the
indoor coil leaving air temperature or the difference between the
leaving and entering air temperatures decreases by more than 1.5 [deg]F
over the 30-minute data collection interval, then do not use the
collected data to determine capacity. Instead, initiate a defrost
cycle. Begin collecting data no sooner than 10 minutes after defrost
termination. Collect 30 minutes of new data during which the Table 15
test tolerances are satisfied. In this case, use only the results from
the second 30-minute data collection interval to evaluate
Qh\k\(47) and Eh\k\(47).
d. If conducting the cyclic heating mode test, which is described
in section 3.8 of this appendix, record the average indoor-side air
volume rate, Vi, specific heat of the air, Cp,a (expressed
on dry air basis), specific volume of the air at the nozzles,
vn' (or vn), humidity ratio at the nozzles,
Wn, and either pressure difference or velocity pressure for
the flow nozzles. If either or both of the below criteria apply,
determine the average, steady-state, electrical power consumption of
the indoor blower motor (Efan,1):
(1) The section 3.8 cyclic test will be conducted and the heat pump
has a variable-speed indoor blower that is expected to be disabled
during the cyclic test; or
(2) The heat pump has a (variable-speed) constant-air volume-rate
indoor blower and during the steady-state test the average external
static pressure ([Delta]P1) exceeds the applicable section
3.1.4.4 minimum (or targeted) external static pressure
([Delta]Pmin) by 0.03 inches of water or more.
Determine Efan,1 by making measurements during the 30-
minute data collection interval, or immediately following the test and
prior to changing the test conditions. When the above ``2'' criteria
applies, conduct the following four steps after determining
Efan,1 (which corresponds to [Delta]P1):
(i) While maintaining the same test conditions, adjust the exhaust
fan of the airflow measuring apparatus until the external static
pressure increases to approximately [Delta]P1 +
([Delta]P1 - [Delta]Pmin).
(ii) After re-establishing steady readings for fan motor power and
external static pressure, determine average values for the indoor
blower power (Efan,2) and the external static pressure
([Delta]P2) by making measurements over a 5-minute interval.
(iii) Approximate the average power consumption of the indoor
blower motor if the 30-minute test had been conducted at
[Delta]Pmin using linear extrapolation:
[[Page 37090]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.029
(iv) Decrease the total space heating capacity,
Qh\k\(T), by the quantity (Efan,1 -
Efan,min), when expressed on a Btu/h basis. Decrease the
total electrical power, Eh\k\(T) by the same fan power
difference, now expressed in watts.
e. If the temperature sensors used to provide the primary
measurement of the indoor-side dry bulb temperature difference during
the steady-state dry-coil test and the subsequent cyclic dry-coil test
are different, include measurements of the latter sensors among the
regularly sampled data. Beginning at the start of the 30-minute data
collection period, measure and compute the indoor-side air dry-bulb
temperature difference using both sets of instrumentation, [Delta]T
(Set SS) and [Delta]T (Set CYC), for each equally spaced data sample.
If using a consistent data sampling rate that is less than 1 minute,
calculate and record minutely averages for the two temperature
differences. If using a consistent sampling rate of one minute or more,
calculate and record the two temperature differences from each data
sample. After having recorded the seventh (i = 7) set of temperature
differences, calculate the following ratio using the first seven sets
of values:
[GRAPHIC] [TIFF OMITTED] TR08JN16.030
Each time a subsequent set of temperature differences is recorded (if
sampling more frequently than every 5 minutes), calculate
FCD using the most recent seven sets of values. Continue
these calculations until the 30-minute period is completed or until a
value for FCD is calculated that falls outside the allowable
range of 0.94-1.06. If the latter occurs, immediately suspend the test
and identify the cause for the disparity in the two temperature
difference measurements. Recalibration of one or both sets of
instrumentation may be required. If all the values for FCD
are within the allowable range, save the final value of the ratio from
the 30-minute test as FCD*. If the temperature sensors used
to provide the primary measurement of the indoor-side dry bulb
temperature difference during the steady-state dry-coil test and the
subsequent cyclic dry-coil test are the same, set FCD* = 1.
3.8 Test Procedures for the Cyclic Heating Mode Tests (the
H0C1, H1C, H1C1 and H1C2 Tests)
a. Except as noted below, conduct the cyclic heating mode test as
specified in section 3.5 of this appendix. As adapted to the heating
mode, replace section 3.5 references to ``the steady-state dry coil
test'' with ``the heating mode steady-state test conducted at the same
test conditions as the cyclic heating mode test.'' Use the test
tolerances in Table 16 rather than Table 9. Record the outdoor coil
entering wet-bulb temperature according to the requirements given in
section 3.5 of this appendix for the outdoor coil entering dry-bulb
temperature. Drop the subscript ``dry'' used in variables cited in
section 3.5 of this appendix when referring to quantities from the
cyclic heating mode test. The default CD value for heating
is 0.25. If available, use electric resistance heaters (see section 2.1
of this appendix) to minimize the variation in the inlet air
temperature. Determine the total space heating delivered during the
cyclic heating test, qcyc, as specified in section 3.5 of
this appendix except for making the following changes:
(1) When evaluating Equation 3.5-1, use the values of Vi,
Cp,a,vn', (or vn), and Wn
that were recorded during the section 3.7 steady-state test conducted
at the same test conditions.
[GRAPHIC] [TIFF OMITTED] TR08JN16.031
where FCD* is the value recorded during the section 3.7
steady-state test conducted at the same test condition.
b. For ducted coil-only system heat pumps (excluding the special
case where a variable-speed fan is temporarily removed), increase
qcyc by the amount calculated using Equation 3.5-3.
Additionally, increase ecyc by the amount calculated using
Equation 3.5-2. In making these calculations, use the average indoor
air volume rate (Vis) determined from the section 3.7
steady-state heating mode test conducted at the same test conditions.
c. For non-ducted heat pumps, subtract the electrical energy used
by the indoor blower during the 3 minutes after compressor cutoff from
the non-ducted heat pump's integrated heating capacity,
qcyc.
d. If a heat pump defrost cycle is manually or automatically
initiated immediately prior to or during the OFF/ON cycling, operate
the heat pump continuously until 10 minutes after defrost termination.
After that, begin cycling the heat pump immediately or delay until the
specified test conditions have been re-established. Pay attention to
preventing defrosts after beginning the cycling process. For heat pumps
that cycle off the indoor blower during a defrost cycle, make no effort
here to restrict the air movement through the indoor coil while the fan
is off. Resume the OFF/ON cycling while conducting a minimum of two
complete compressor OFF/ON cycles before determining qcyc
and ecyc.
3.8.1 Heating Mode Cyclic-Degradation Coefficient Calculation
Use the results from the required cyclic test and the required
steady-state test that were conducted at the same test conditions to
determine the heating mode cyclic-degradation coefficient
CD\h\. Add ``(k = 2)'' to the coefficient if it corresponds
to a two-capacity unit cycling at high capacity. For the below
calculation of the heating mode cyclic degradation coefficient, do not
include the duct loss correction from section 7.3.3.3 of ANSI/ASHRAE
37-2009 (incorporated by reference, see Sec. 430.3) in determining
Qh\k\(Tcyc) (or qcyc). The default
value for two-capacity units cycling at high capacity, however, is the
low-capacity coefficient, i.e., CD\h\ (k = 2) =
CD\h\. The tested CD\h\ is calculated as follows:
[[Page 37091]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.032
the average coefficient of performance during the cyclic heating mode
test, dimensionless.
[GRAPHIC] [TIFF OMITTED] TR08JN16.033
the average coefficient of performance during the steady-state heating
mode test conducted at the same test conditions--i.e., same outdoor dry
bulb temperature, Tcyc, and speed/capacity, k, if
applicable--as specified for the cyclic heating mode test,
dimensionless.
[GRAPHIC] [TIFF OMITTED] TR08JN16.034
the heating load factor, dimensionless.
Tcyc = the nominal outdoor temperature at which the
cyclic heating mode test is conducted, 62 or 47 [deg]F.
[Delta][tau]cyc = the duration of the OFF/ON intervals;
0.5 hours when testing a heat pump having a single-speed or two-
capacity compressor and 1.0 hour when testing a heat pump having a
variable-speed compressor.
Round the calculated value for CD\h\ to the nearest
0.01. If CD\h\ is negative, then set it equal to zero.
Table 16--Test Operating and Test Condition Tolerances for Cyclic
Heating Mode Tests
------------------------------------------------------------------------
Test operating Test condition
tolerance \1\ tolerance \1\
------------------------------------------------------------------------
Indoor entering dry-bulb temperature,\2\ 2.0 0.5
[deg]F.................................
Indoor entering wet-bulb temperature,\2\ 1.0
[deg]F.................................
Outdoor entering dry-bulb 2.0 0.5
temperature,\2\ [deg]F.................
Outdoor entering wet-bulb 2.0 1.0
temperature,\2\ [deg]F.................
External resistance to air-flow,\2\ 0.12
inches of water........................
Airflow nozzle pressure difference or 2.0 \3\ 2.0
velocity pressure,\2%\ of reading......
Electrical voltage,\4%\ of rdg.......... 8.0 1.5
------------------------------------------------------------------------
\1\ See section 1.2 of this appendix, Definitions.
\2\ Applies during the interval that air flows through the indoor
(outdoor) coil except for the first 30 seconds after flow initiation.
For units having a variable-speed indoor blower that ramps, the
tolerances listed for the external resistance to airflow shall apply
from 30 seconds after achieving full speed until ramp down begins.
\3\ The test condition shall be the average nozzle pressure difference
or velocity pressure measured during the steady-state test conducted
at the same test conditions.
\4\ Applies during the interval that at least one of the following--the
compressor, the outdoor fan, or, if applicable, the indoor blower--are
operating, except for the first 30 seconds after compressor start-up.
3.9 Test Procedures for Frost Accumulation Heating Mode Tests (the H2,
H22, H2V, and H21 Tests)
a. Confirm that the defrost controls of the heat pump are set as
specified in section 2.2.1 of this appendix. Operate the test room
reconditioning apparatus and the heat pump for at least 30 minutes at
the specified section 3.6 test conditions before starting the
``preliminary'' test period. The preliminary test period must
immediately precede the ``official'' test period, which is the heating
and defrost interval over which data are collected for evaluating
average space heating capacity and average electrical power
consumption.
b. For heat pumps containing defrost controls which are likely to
cause defrosts at intervals less than one hour, the preliminary test
period starts at the termination of an automatic defrost cycle and ends
at the termination of the next occurring automatic defrost cycle. For
heat pumps containing defrost controls which are likely to cause
defrosts at intervals exceeding one hour, the preliminary test period
must consist of a heating interval lasting at least one hour followed
by a defrost cycle that is either manually or automatically initiated.
In all cases, the heat pump's own controls must govern when a defrost
cycle terminates.
c. The official test period begins when the preliminary test period
ends, at defrost termination. The official test period ends at the
termination of the
[[Page 37092]]
next occurring automatic defrost cycle. When testing a heat pump that
uses a time-adaptive defrost control system (see section 1.2 of this
appendix, Definitions), however, manually initiate the defrost cycle
that ends the official test period at the instant indicated by
instructions provided by the manufacturer. If the heat pump has not
undergone a defrost after 6 hours, immediately conclude the test and
use the results from the full 6-hour period to calculate the average
space heating capacity and average electrical power consumption.
For heat pumps that turn the indoor blower off during the defrost
cycle, take steps to cease forced airflow through the indoor coil and
block the outlet duct whenever the heat pump's controls cycle off the
indoor blower. If it is installed, use the outlet damper box described
in section 2.5.4.1 of this appendix to affect the blocked outlet duct.
d. Defrost termination occurs when the controls of the heat pump
actuate the first change in converting from defrost operation to normal
heating operation. Defrost initiation occurs when the controls of the
heat pump first alter its normal heating operation in order to
eliminate possible accumulations of frost on the outdoor coil.
e. To constitute a valid frost accumulation test, satisfy the test
tolerances specified in Table 17 during both the preliminary and
official test periods. As noted in Table 17, test operating tolerances
are specified for two sub-intervals: (1) When heating, except for the
first 10 minutes after the termination of a defrost cycle (sub-interval
H, as described in Table 17) and (2) when defrosting, plus these same
first 10 minutes after defrost termination (sub-interval D, as
described in Table 17). Evaluate compliance with Table 17 test
condition tolerances and the majority of the test operating tolerances
using the averages from measurements recorded only during sub-interval
H. Continuously record the dry bulb temperature of the air entering the
indoor coil, and the dry bulb temperature and water vapor content of
the air entering the outdoor coil. Sample the remaining parameters
listed in Table 17 at equal intervals that span 5 minutes or less.
f. For the official test period, collect and use the following data
to calculate average space heating capacity and electrical power.
During heating and defrosting intervals when the controls of the heat
pump have the indoor blower on, continuously record the dry-bulb
temperature of the air entering (as noted above) and leaving the indoor
coil. If using a thermopile, continuously record the difference between
the leaving and entering dry-bulb temperatures during the interval(s)
that air flows through the indoor coil. For coil-only system heat
pumps, determine the corresponding cumulative time (in hours) of indoor
coil airflow, [Delta][tau]a. Sample measurements used in
calculating the air volume rate (refer to sections 7.7.2.1 and 7.7.2.2
of ANSI/ASHRAE 37-2009) at equal intervals that span 10 minutes or
less. (Note: In the first printing of ANSI/ASHRAE 37-2009, the second
IP equation for Qmi should read:) Record the electrical
energy consumed, expressed in watt-hours, from defrost termination to
defrost termination, eDEF\k\(35), as well as the
corresponding elapsed time in hours, [Delta][tau]FR.
Table 17--Test Operating and Test Condition Tolerances for Frost Accumulation Heating Mode Tests
----------------------------------------------------------------------------------------------------------------
Test operating tolerance \1\
-------------------------------------- Test condition
Sub-interval H Sub-interval D tolerance \1\ Sub-
\2\ \3\ interval H \2\
----------------------------------------------------------------------------------------------------------------
Indoor entering dry-bulb temperature, [deg]F........... 2.0 \4\ 4.0 0.5
Indoor entering wet-bulb temperature, [deg]F........... 1.0
Outdoor entering dry-bulb temperature, [deg]F.......... 2.0 10.0 1.0
Outdoor entering wet-bulb temperature, [deg]F.......... 1.5 ................. 0.5
External resistance to airflow, inches of water........ 0.12 ................. \5\ 0.02
Electrical voltage, % of rdg........................... 2.0 ................. 1.5
----------------------------------------------------------------------------------------------------------------
1 See section 1.2 of this appendix, Definitions.
2 Applies when the heat pump is in the heating mode, except for the first 10 minutes after termination of a
defrost cycle.
3 Applies during a defrost cycle and during the first 10 minutes after the termination of a defrost cycle when
the heat pump is operating in the heating mode.
4 For heat pumps that turn off the indoor blower during the defrost cycle, the noted tolerance only applies
during the 10 minute interval that follows defrost termination.
5 Only applies when testing non-ducted heat pumps.
3.9.1 Average Space Heating Capacity and Electrical Power Calculations
a. Evaluate average space heating capacity,
Qhk(35), when expressed in units of Btu per hour,
using:
[GRAPHIC] [TIFF OMITTED] TR08JN16.035
Where,
Vi = the average indoor air volume rate measured during sub-interval
H, cfm.
Cp,a = 0.24 + 0.444 [middot] Wn, the constant
pressure specific heat of the air-water vapor mixture that flows
through the indoor coil and is expressed on a dry air basis, Btu/
lbmda [middot] [deg]F.
vn' = specific volume of the air-water vapor mixture at
the nozzle, ft\3\/lbmmx.
[[Page 37093]]
Wn = humidity ratio of the air-water vapor mixture at the
nozzle, lbm of water vapor per lbm of dry air.
[Delta][tau]FR = [tau]2 - [tau]1,
the elapsed time from defrost termination to defrost termination,
hr.
[GRAPHIC] [TIFF OMITTED] TR08JN16.036
Tal([tau]) = dry bulb temperature of the air entering the
indoor coil at elapsed time [tau], [deg]F; only recorded when indoor
coil airflow occurs; assigned the value of zero during periods (if
any) where the indoor blower cycles off.
Ta2([tau]) = dry bulb temperature of the air leaving the
indoor coil at elapsed time [tau], [deg]F; only recorded when indoor
coil airflow occurs; assigned the value of zero during periods (if
any) where the indoor blower cycles off.
[tau]1 = the elapsed time when the defrost termination
occurs that begins the official test period, hr.
[tau]2 = the elapsed time when the next automatically
occurring defrost termination occurs, thus ending the official test
period, hr.
vn = specific volume of the dry air portion of the
mixture evaluated at the dry-bulb temperature, vapor content, and
barometric pressure existing at the nozzle, ft\3\ per lbm of dry
air.
To account for the effect of duct losses between the outlet of the
indoor unit and the section 2.5.4 dry-bulb temperature grid, adjust
Qhk(35) in accordance with section 7.3.4.3 of
ANSI/ASHRAE 37-2009 (incorporated by reference, see Sec. 430.3).
b. Evaluate average electrical power,
Ehk(35), when expressed in units of watts, using:
[GRAPHIC] [TIFF OMITTED] TR08JN16.037
For coil-only system heat pumps, increase
Qhk(35) by,
[GRAPHIC] [TIFF OMITTED] TR08JN16.038
where Vis is the average indoor air volume rate measured
during the frost accumulation heating mode test and is expressed in
units of cubic feet per minute of standard air (scfm).
c. For heat pumps having a constant-air-volume-rate indoor blower,
the five additional steps listed below are required if the average of
the external static pressures measured during sub-interval H exceeds
the applicable section 3.1.4.4, 3.1.4.5, or 3.1.4.6 minimum (or
targeted) external static pressure ([Delta]Pmin) by 0.03
inches of water or more:
(1) Measure the average power consumption of the indoor blower
motor (Efan,1) and record the corresponding external static
pressure ([Delta]P1) during or immediately following the
frost accumulation heating mode test. Make the measurement at a time
when the heat pump is heating, except for the first 10 minutes after
the termination of a defrost cycle.
(2) After the frost accumulation heating mode test is completed and
while maintaining the same test conditions, adjust the exhaust fan of
the airflow measuring apparatus until the external static pressure
increases to approximately [Delta]P1 + ([Delta]P1
- [Delta]Pmin).
(3) After re-establishing steady readings for the fan motor power
and external static pressure, determine average values for the indoor
blower power (Efan,2) and the external static pressure
([Delta]P2) by making measurements over a 5-minute interval.
(4) Approximate the average power consumption of the indoor blower
motor had the frost accumulation heating mode test been conducted at
[Delta]Pmin using linear extrapolation:
[GRAPHIC] [TIFF OMITTED] TR08JN16.039
(5) Decrease the total heating capacity,
Qhk(35), by the quantity [(Efan,1 -
Efan,min)[middot] ([Delta][tau]a/
[Delta][tau]FR], when expressed on a Btu/h basis. Decrease
the total electrical power, Ehk(35), by the same
quantity, now expressed in watts.
3.9.2 Demand Defrost Credit
a. Assign the demand defrost credit, Fdef, that is used
in section 4.2 of this
[[Page 37094]]
appendix to the value of 1 in all cases except for heat pumps having a
demand-defrost control system (see section 1.2 of this appendix,
Definitions). For such qualifying heat pumps, evaluate Fdef
using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.040
where:
[Delta][tau]def = the time between defrost terminations
(in hours) or 1.5, whichever is greater. A value of 6 must be
assigned to [Delta][tau]def if this limit is reached
during a frost accumulation test and the heat pump has not completed
a defrost cycle.
[Delta][tau]max = maximum time between defrosts as
allowed by the controls (in hours) or 12, whichever is less, as
provided in the certification report.
b. For two-capacity heat pumps and for section 3.6.2 units,
evaluate the above equation using the [Delta][tau]def that
applies based on the frost accumulation test conducted at high capacity
and/or at the heating full-load air volume rate. For variable-speed
heat pumps, evaluate [Delta][tau]def based on the required
frost accumulation test conducted at the intermediate compressor speed.
3.10 Test Procedures for Steady-State Low Temperature Heating Mode
Tests (the H3, H32, and H31 tests).
Except for the modifications noted in this section, conduct the low
temperature heating mode test using the same approach as specified in
section 3.7 of this appendix for the maximum and high temperature
tests. After satisfying the section 3.7 requirements for the pretest
interval but before beginning to collect data to determine
Qh\k\(17) and Eh\k\(17), conduct a defrost cycle.
This defrost cycle may be manually or automatically initiated. The
defrost sequence must be terminated by the action of the heat pump's
defrost controls. Begin the 30-minute data collection interval
described in section 3.7 of this appendix, from which
Qh\k\(17) and Eh\k\(17) are determined, no sooner
than 10 minutes after defrost termination. Defrosts should be prevented
over the 30-minute data collection interval.
3.11 Additional Requirements for the Secondary Test Methods
3.11.1 If Using the Outdoor Air Enthalpy Method as the Secondary Test
Method
During the ``official'' test, the outdoor air-side test apparatus
described in section 2.10.1 of this appendix is connected to the
outdoor unit. To help compensate for any effect that the addition of
this test apparatus may have on the unit's performance, conduct a
``preliminary'' test where the outdoor air-side test apparatus is
disconnected. Conduct a preliminary test prior to the first section 3.2
of this appendix steady-state cooling mode test and prior to the first
section 3.6 of this appendix steady-state heating mode test. No other
preliminary tests are required so long as the unit operates the outdoor
fan during all cooling mode steady-state tests at the same speed and
all heating mode steady-state tests at the same speed. If using more
than one outdoor fan speed for the cooling mode steady-state tests,
however, conduct a preliminary test prior to each cooling mode test
where a different fan speed is first used. This same requirement
applies for the heating mode tests.
3.11.1.1 Preliminary Test
3.11.1.1.1 If a Preliminary Test Precedes the Official Test
a. The test conditions for the preliminary test are the same as
specified for the official test. Connect the indoor air-side test
apparatus to the indoor coil; disconnect the outdoor air-side test
apparatus. Allow the test room reconditioning apparatus and the unit
being tested to operate for at least one hour. After attaining
equilibrium conditions, measure the following quantities at equal
intervals that span 5 minutes or less:
(1) The section 2.10.1 of this appendix evaporator and condenser
temperatures or pressures;
(2) Parameters required according to the indoor air enthalpy
method.
Continue these measurements until a 30-minute period (e.g., seven
consecutive 5-minute samples) is obtained where the Table 8 or Table
15, whichever applies, test tolerances are satisfied.
b. After collecting 30 minutes of steady-state data, reconnect the
outdoor air-side test apparatus to the unit. Adjust the exhaust fan of
the outdoor airflow measuring apparatus until averages for the
evaporator and condenser temperatures, or the saturated temperatures
corresponding to the measured pressures, agree within 0.5
[deg]F of the averages achieved when the outdoor air-side test
apparatus was disconnected. Calculate the averages for the reconnected
case using five or more consecutive readings taken at one minute
intervals. Make these consecutive readings after re-establishing
equilibrium conditions and before initiating the official test.
3.11.1.1.2 If a Preliminary Test Does Not Precede the Official Test
Connect the outdoor-side test apparatus to the unit. Adjust the
exhaust fan of the outdoor airflow measuring apparatus to achieve the
same external static pressure as measured during the prior preliminary
test conducted with the unit operating in the same cooling or heating
mode at the same outdoor fan speed.
3.11.1.1 Official Test
a. Continue (preliminary test was conducted) or begin (no
preliminary test) the official test by making measurements for both the
indoor and outdoor air enthalpy methods at equal intervals that span 5
minutes or less. Discontinue these measurements only after obtaining a
30-minute period where the specified test condition and test operating
tolerances are satisfied. To constitute a valid official test:
(1) Achieve the energy balance specified in section 3.1.1 of this
appendix; and,
(2) For cases where a preliminary test is conducted, the capacities
determined using the indoor air enthalpy method from the official and
preliminary test periods must agree within 2.0 percent.
b. For space cooling tests, calculate capacity from the outdoor
air-enthalpy measurements as specified in sections 7.3.3.2 and 7.3.3.3
of ANSI/ASHRAE 37-2009 (incorporated by reference, see Sec. 430.3).
Calculate heating capacity based on outdoor air-enthalpy measurements
as specified in sections 7.3.4.2 and 7.3.3.4.3 of the same ASHRAE
Standard. Adjust the outdoor-side capacity according to section 7.3.3.4
of ANSI/ASHRAE 37-2009 to account for line losses when testing split
systems. Use the outdoor unit fan power as measured during the official
test and not the value measured during the preliminary test, as
described in section 8.6.2 of ANSI/ASHRAE 37-2009, when calculating the
capacity.
[[Page 37095]]
3.11.2 If Using the Compressor Calibration Method as the Secondary Test
Method
a. Conduct separate calibration tests using a calorimeter to
determine the refrigerant flow rate. Or for cases where the superheat
of the refrigerant leaving the evaporator is less than 5 [deg]F, use
the calorimeter to measure total capacity rather than refrigerant flow
rate. Conduct these calibration tests at the same test conditions as
specified for the tests in this appendix. Operate the unit for at least
one hour or until obtaining equilibrium conditions before collecting
data that will be used in determining the average refrigerant flow rate
or total capacity. Sample the data at equal intervals that span 5
minutes or less. Determine average flow rate or average capacity from
data sampled over a 30-minute period where the Table 8 (cooling) or the
Table 15 (heating) tolerances are satisfied. Otherwise, conduct the
calibration tests according to sections 5, 6, 7, and 8 of ASHRAE 23.1-
2010 (incorporated by reference, see Sec. 430.3); sections 5, 6, 7, 8,
9, and 11 of ASHRAE 41.9-2011 (incorporated by reference, see Sec.
430.3); and section 7.4 of ANSI/ASHRAE 37-2009 (incorporated by
reference, see Sec. 430.3).
b. Calculate space cooling and space heating capacities using the
compressor calibration method measurements as specified in section
7.4.5 and 7.4.6 respectively, of ANSI/ASHRAE 37-2009.
3.11.3 If Using the Refrigerant-Enthalpy Method as the Secondary Test
Method
Conduct this secondary method according to section 7.5 of ANSI/
ASHRAE 37-2009. Calculate space cooling and heating capacities using
the refrigerant-enthalpy method measurements as specified in sections
7.5.4 and 7.5.5, respectively, of the same ASHRAE Standard.
3.12 Rounding of Space Conditioning Capacities for Reporting Purposes
a. When reporting rated capacities, round them off as specified in
Sec. 430.23 (for a single unit) and in 10 CFR 429.16 (for a sample).
b. For the capacities used to perform the calculations in section 4
of this appendix, however, round only to the nearest integer.
3.13 Laboratory Testing To Determine Off Mode Average Power Ratings
Voltage tolerances: As a percentage of reading, test operating
tolerance shall be 2.0 percent and test condition tolerance shall be
1.5 percent (see section 1.2 of this appendix for definitions of these
tolerances).
Conduct one of the following tests: If the central air conditioner
or heat pump lacks a compressor crankcase heater, perform the test in
section 3.13.1 of this appendix; if the central air conditioner or heat
pump has a compressor crankcase heater that lacks controls and is not
self-regulating, perform the test in section 3.13.1 of this appendix;
if the central air conditioner or heat pump has a crankcase heater with
a fixed power input controlled with a thermostat that measures ambient
temperature and whose sensing element temperature is not affected by
the heater, perform the test in section 3.13.1 of this appendix; if the
central air conditioner or heat pump has a compressor crankcase heater
equipped with self-regulating control or with controls for which the
sensing element temperature is affected by the heater, perform the test
in section 3.13.2 of this appendix.
3.13.1 This Test Determines the off Mode Average Power Rating for
Central Air Conditioners and Heat Pumps That Lack a Compressor
Crankcase Heater, or Have a Compressor Crankcase Heating System That
Can Be Tested Without Control of Ambient Temperature During the Test.
This Test Has No Ambient Condition Requirements
a. Test Sample Set-up and Power Measurement: For coil-only systems,
provide a furnace or modular blower that is compatible with the system
to serve as an interface with the thermostat (if used for the test) and
to provide low-voltage control circuit power. Make all control circuit
connections between the furnace (or modular blower) and the outdoor
unit as specified by the manufacturer's installation instructions.
Measure power supplied to both the furnace or modular blower and power
supplied to the outdoor unit. Alternatively, provide a compatible
transformer to supply low-voltage control circuit power, as described
in section 2.2.d of this appendix. Measure transformer power, either
supplied to the primary winding or supplied by the secondary winding of
the transformer, and power supplied to the outdoor unit. For blower
coil and single-package systems, make all control circuit connections
between components as specified by the manufacturer's installation
instructions, and provide power and measure power supplied to all
system components.
b. Configure Controls: Configure the controls of the central air
conditioner or heat pump so that it operates as if connected to a
building thermostat that is set to the OFF position. Use a compatible
building thermostat if necessary to achieve this configuration. For a
thermostat-controlled crankcase heater with a fixed power input, bypass
the crankcase heater thermostat if necessary to energize the heater.
c. Measure P2x: If the unit has a crankcase heater time
delay, make sure that time delay function is disabled or wait until
delay time has passed. Determine the average power from non-zero value
data measured over a 5-minute interval of the non-operating central air
conditioner or heat pump and designate the average power as
P2x, the heating season total off mode power.
d. Measure P2x for coil-only split systems and for
blower coil split systems for which a furnace or a modular blower is
the designated air mover: Disconnect all low-voltage wiring for the
outdoor components and outdoor controls from the low-voltage
transformer. Determine the average power from non-zero value data
measured over a 5-minute interval of the power supplied to the
(remaining) low-voltage components of the central air conditioner or
heat pump, or low-voltage power, P2x. This power measurement
does not include line power supplied to the outdoor unit. It is the
line power supplied to the air mover, or, if a compatible
transformer is used instead of an air mover, it is the line power
supplied to the transformer primary coil. If a compatible transformer
is used instead of an air mover and power output of the low-voltage
secondary circuit is measured, Px is zero.
e. Calculate P2: Set the number of compressors equal to the unit's
number of single-stage compressors plus 1.75 times the unit's number of
compressors that are not single-stage.
For single-package systems and blower coil split systems for which
the designated air mover is not a furnace or modular blower, divide the
heating season total off mode power (P2x) by the number of
compressors to calculate P2, the heating season per-compressor off mode
power. Round P2 to the nearest watt. The expression for calculating P2
is as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.041
For coil-only split systems and blower coil split systems for which
a furnace or a modular blower is the designated air mover, subtract the
low-voltage power (Px ) from the heating season total off
mode power (P2x) and divide by the number of compressors to
calculate P2, the heating season per-compressor off mode power. Round
P2 to the nearest
[[Page 37096]]
watt. The expression for calculating P2 is as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.042
f. Shoulder-season per-compressor off mode power, P1: If the system
does not have a crankcase heater, has a crankcase heater without
controls that is not self-regulating, or has a value for the crankcase
heater turn-on temperature (as certified in the DOE Compliance
Certification Database) that is higher than 71 [deg]F, P1 is equal to
P2.
Otherwise, de-energize the crankcase heater (by removing the
thermostat bypass or otherwise disconnecting only the power supply to
the crankcase heater) and repeat the measurement as described in
section 3.13.1.c of this appendix. Designate the measured average power
as P1x, the shoulder season total off mode power.
Determine the number of compressors as described in section
3.13.1.e of this appendix.
For single-package systems and blower coil systems for which the
designated air mover is not a furnace or modular blower, divide the
shoulder season total off mode power (P1x) by the number of
compressors to calculate P1, the shoulder season per-compressor off
mode power. Round P1 to the nearest watt. The expression for
calculating P1 is as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.043
For coil-only split systems and blower coil split systems for which
a furnace or a modular blower is the designated air mover, subtract the
low-voltage power (Px) from the shoulder season total off
mode power (P1x) and divide by the number of compressors to
calculate P1, the shoulder season per-compressor off mode power. Round
P1 to the nearest watt. The expression for calculating P1 is as
follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.044
3.13.2 This test determines the off mode average power rating for
central air conditioners and heat pumps for which ambient temperature
can affect the measurement of crankcase heater power.
a. Test Sample Set-up and Power Measurement: Set up the test and
measurement as described in section 3.13.1.a of this appendix.
b. Configure Controls: Position a temperature sensor to measure the
outdoor dry-bulb temperature in the air between 2 and 6 inches from the
crankcase heater control temperature sensor or, if no such temperature
sensor exists, position it in the air between 2 and 6 inches from the
crankcase heater. Utilize the temperature measurements from this sensor
for this portion of the test procedure. Configure the controls of the
central air conditioner or heat pump so that it operates as if
connected to a building thermostat that is set to the OFF position. Use
a compatible building thermostat if necessary to achieve this
configuration.
Conduct the test after completion of the B, B1, or
B2 test. Alternatively, start the test when the outdoor dry-
bulb temperature is at 82 [deg]F and the temperature of the compressor
shell (or temperature of each compressor's shell if there is more than
one compressor) is at least 81 [deg]F. Then adjust the outdoor
temperature at a rate of change of no more than 20 [deg]F per hour and
achieve an outdoor dry-bulb temperature of 72 [deg]F. Maintain this
temperature within +/-2 [deg]F while making the power measurement, as
described in section 3.13.2.c of this appendix.
c. Measure P1x: If the unit has a crankcase heater time
delay, make sure that time delay function is disabled or wait until
delay time has passed. Determine the average power from non-zero value
data measured over a 5-minute interval of the non-operating central air
conditioner or heat pump and designate the average power as
P1x, the shoulder season total off mode power. For units
with crankcase heaters which operate during this part of the test and
whose controls cycle or vary crankcase heater power over time, the test
period shall consist of three complete crankcase heater cycles or 18
hours, whichever comes first. Designate the average power over the test
period as P1x, the shoulder season total off mode power.
d. Reduce outdoor temperature: Approach the target outdoor dry-bulb
temperature by adjusting the outdoor temperature at a rate of change of
no more than 20 [deg]F per hour. This target temperature is five
degrees Fahrenheit less than the temperature specified by the
manufacturer in the DOE Compliance Certification Database at which the
crankcase heater turns on. Maintain the target temperature within +/-2
[deg]F while making the power measurement, as described in section
3.13.2.e of this appendix.
e. Measure P2x: If the unit has a crankcase heater time
delay, make sure that time delay function is disabled or wait until
delay time has passed. Determine the average non-zero power of the non-
operating central air conditioner or heat pump over a 5-minute interval
and designate it as P2x, the heating season total off mode
power. For units with crankcase heaters whose controls cycle or vary
crankcase heater power over time, the test period shall consist of
three complete crankcase heater cycles or 18 hours, whichever comes
first. Designate the average power over the test period as
P2x, the heating season total off mode power.
f. Measure Px for coil-only split systems and for blower
coil split systems for which a furnace or modular blower is the
designated air mover: Disconnect all low-voltage wiring for the outdoor
components and outdoor controls from the low-voltage transformer.
Determine the average power from non-zero value data measured over a 5-
minute interval of the power supplied to the (remaining) low-voltage
components of the central air conditioner or heat pump, or low-voltage
power, Px. This power measurement does not include line
power supplied to the outdoor unit. It is the line power supplied to
the air mover, or, if a compatible transformer is used
instead of an air mover, it is the line power supplied to the
transformer primary coil. If a compatible transformer is used instead
of an air mover and power output of the low-voltage secondary circuit
is measured, Px is zero.
g. Calculate P1:
Set the number of compressors equal to the unit's number of single-
stage compressors plus 1.75 times the unit's number of compressors that
are not single-stage.
For single-package systems and blower coil split systems for which
the air mover is not a furnace or modular blower, divide the shoulder
season total off mode power (P1x) by the number of compressors to
calculate P1, the shoulder season per-compressor off mode power. Round
to the nearest watt. The expression for calculating P1 is as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.045
For coil-only split systems and blower coil split systems for which
a furnace or a modular blower is the designated air mover, subtract the
low-voltage power (Px) from the shoulder season total off mode power
(P1x) and divide by the number of compressors to calculate P1, the
shoulder season per-compressor off mode power. Round to the nearest
watt. The expression for calculating P1 is as follows:
[[Page 37097]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.046
h. Calculate P2:
Determine the number of compressors as described in section
3.13.2.g of this appendix.
For single-package systems and blower coil split systems for which
the air mover is not a furnace, divide the heating season total off
mode power (P1x) by the number of compressors to calculate P2, the
heating season per-compressor off mode power. Round to the nearest
watt. The expression for calculating P2 is as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.047
For coil-only split systems and blower coil split systems for which
a furnace or a modular blower is the designated air mover, subtract the
low-voltage power (Px) from the heating season total off mode power
(P2x) and divide by the number of compressors to calculate P2, the
heating season per-compressor off mode power. Round to the nearest
watt. The expression for calculating P2 is as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.048
4. Calculations of Seasonal Performance Descriptors
4.1 Seasonal Energy Efficiency Ratio (SEER) Calculations. SEER must be
calculated as follows:
For equipment covered under sections 4.1.2, 4.1.3, and 4.1.4 of
this appendix, evaluate the seasonal energy efficiency ratio,
[GRAPHIC] [TIFF OMITTED] TR08JN16.049
Additionally, for sections 4.1.2, 4.1.3, and 4.1.4 of this
appendix, use a building cooling load, BL(Tj). When
referenced, evaluate BL(Tj) for cooling using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.050
Where:
Qc\k=2\(95) = the space cooling capacity determined from
the A2 test and calculated as specified in section 3.3 of
this appendix, Btu/h.
1.1 = sizing factor, dimensionless.
The temperatures 95 [deg]F and 65 [deg]F in the building load
equation represent the selected outdoor design temperature
[[Page 37098]]
and the zero-load base temperature, respectively.
4.1.1 SEER Calculations for a Blower Coil System Having a Single-Speed
Compressor and Either a Fixed-Speed Indoor Blower or a Constant-Air-
Volume-Rate Indoor Blower, or a Coil-Only System Air Conditioner or
Heat Pump
a. Evaluate the seasonal energy efficiency ratio, expressed in
units of Btu/watt-hour, using:
SEER = PLF(0.5) * EERB
Where:
[GRAPHIC] [TIFF OMITTED] TR08JN16.051
PLF(0.5) = 1 - 0.5 [middot] CD\c\, the part-load
performance factor evaluated at a cooling load factor of 0.5,
dimensionless.
b. Refer to section 3.3 of this appendix regarding the definition
and calculation of Qc(82) and Ec(82).
4.1.2 SEER Calculations for an Air Conditioner or Heat Pump Having a
Single-Speed Compressor and a Variable-Speed Variable-Air-Volume-Rate
Indoor Blower
4.1.2.1 Units covered by section 3.2.2.1 of this appendix where indoor
blower capacity modulation correlates with the outdoor dry bulb
temperature. The manufacturer must provide information on how the
indoor air volume rate or the indoor blower speed varies over the
outdoor temperature range of 67 [deg]F to 102 [deg]F. Calculate SEER
using Equation 4.1-1. Evaluate the quantity
qc(Tj)/N in Equation 4.1-1 using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.052
a. For the space cooling season, assign nj/N as
specified in Table 18. Use Equation 4.1-2 to calculate the building
load, BL(Tj). Evaluate Qc(Tj) using,
[[Page 37099]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.053
b. For units where indoor blower speed is the primary control
variable, FPc\k=1\ denotes the fan speed used during the
required A1 and B1 tests (see section 3.2.2.1 of
this appendix), FPc\k=2\ denotes the fan speed used during
the required A2 and B2 tests, and
FPc(Tj) denotes the fan speed used by the unit
when the outdoor temperature equals Tj. For units where
indoor air volume rate is the primary control variable, the three
FPc's are similarly defined only now being expressed in
terms of air volume rates rather than fan speeds. Refer to sections
3.2.2.1, 3.1.4 to 3.1.4.2, and 3.3 of this appendix regarding the
definitions and calculations of Qc\k=1\(82),
Qc\k=1\(95), Qc\k=2\(82), and
Qc\k=2\(95).
[GRAPHIC] [TIFF OMITTED] TR08JN16.054
Where:
PLFj = 1 - CD\c\ [middot] [1 -
X(Tj)], the part load factor, dimensionless.
Ec(Tj) = the electrical power consumption of
the test unit when operating at outdoor temperature Tj,
W.
c. The quantities X(Tj) and nj/N are the same
quantities as used in Equation 4.1.2-1.
d. Evaluate Ec(Tj) using,
[[Page 37100]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.055
e. The parameters FPc\k=1\, and FPc\k=2\, and
FPc(Tj) are the same quantities that are used
when evaluating Equation 4.1.2-2. Refer to sections 3.2.2.1, 3.1.4 to
3.1.4.2, and 3.3 of this appendix regarding the definitions and
calculations of Ec\k=1\(82), Ec\k=1\(95),
Ec\k=2\(82), and Ec\k=2\(95).
4.1.2.2 Units Covered by Section 3.2.2.2 of This Appendix Where Indoor
Blower Capacity Modulation Is Used To Adjust the Sensible to Total
Cooling Capacity Ratio
Calculate SEER as specified in section 4.1.1 of this appendix.
4.1.2.3 SEER Calculations for an Air Conditioner or Heat Pump Having a
Two-Capacity Compressor
Calculate SEER using Equation 4.1-1. Evaluate the space cooling
capacity, Qc\k=1\ (Tj), and electrical power
consumption, Ec\k=1\ (Tj), of the test unit when
operating at low compressor capacity and outdoor temperature
Tj using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.056
where Qc\k=1\ (82) and Ec\k=1\ (82) are
determined from the B1 test, Qc\k=1\ (67) and
Ec\k=1\ (67) are determined from the F1 test, and
all four quantities are calculated as specified in section 3.3 of this
appendix. Evaluate the space cooling capacity, Qc\k=2\
(Tj), and electrical power consumption, Ec\k=2\
(Tj), of the test unit when operating at high compressor
capacity and outdoor temperature Tj using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.057
[[Page 37101]]
where Qc\k=2\(95) and Ec\k=2\(95) are determined
from the A2 test, Qc\k=2\(82), and
Ec\k=2\(82), are determined from the B2test, and
all are calculated as specified in section 3.3 of this appendix.
The calculation of Equation 4.1-1 quantities
qc(Tj)/N and ec(Tj)/N
differs depending on whether the test unit would operate at low
capacity (section 4.1.2.4 of this appendix), cycle between low and high
capacity (section 4.1.2.5 of this appendix), or operate at high
capacity (sections 4.1.2.6 and 4.1.2.7 of this appendix) in responding
to the building load. For units that lock out low capacity operation at
higher outdoor temperatures, the manufacturer must supply information
regarding this temperature so that the appropriate equations are used.
Use Equation 4.1-2 to calculate the building load, BL(Tj),
for each temperature bin.
4.1.2.4 Steady-state space cooling capacity at low compressor capacity
is greater than or equal to the building cooling load at temperature
Tj, Qc\k=1\(Tj) >=BL(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.059
Where:
X\k=1\(Tj) = BL(Tj)/
Qc\k=1\(Tj), the cooling mode low capacity
load factor for temperature bin j, dimensionless.
PLFj = 1 - CD\c\ [middot] [1 -
X\k=1\(Tj)], the part load factor, dimensionless.
[GRAPHIC] [TIFF OMITTED] TR08JN16.060
Table 18--Distribution of Fractional Hours Within Cooling Season Temperature Bins
----------------------------------------------------------------------------------------------------------------
Fraction of
Bin Representative total
Bin number, j temperature temperature temperature
range, [deg]F for bin, bin hours, nj/
[deg]F N
----------------------------------------------------------------------------------------------------------------
1............................................................... 65-69 67 0.214
2............................................................... 70-74 72 0.231
3............................................................... 75-79 77 0.216
4............................................................... 80-84 82 0.161
5............................................................... 85-89 87 0.104
6............................................................... 90-94 92 0.052
7............................................................... 95-99 97 0.018
8............................................................... 100-104 102 0.004
----------------------------------------------------------------------------------------------------------------
4.1.2.5 Unit alternates between high (k=2) and low (k=1) compressor
capacity to satisfy the building cooling load at temperature
Tj, Qc\k=1\(Tj) j)
c\k=2\(Tj).
[[Page 37102]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.061
X\k=2\(Tj) = 1 - X\k=1\(Tj), the cooling mode,
high capacity load factor for temperature bin j, dimensionless.
Obtain the fractional bin hours for the cooling season,
nj/N, from Table 18. Use Equations 4.1.3-1 and 4.1.3-2,
respectively, to evaluate Qc\k=1\(Tj) and
Ec\k=1\(Tj). Use Equations 4.1.3-3 and 4.1.3-4,
respectively, to evaluate Qc\k=2\(Tj) and
Ec\k=2\(Tj).
4.1.2.6 Unit only operates at high (k = 2) compressor capacity at
temperature Tj and its capacity is greater than the building
cooling load, BL(Tj) c\k=2\(Tj).
This section applies to units that lock out low compressor capacity
operation at higher outdoor temperatures.
[GRAPHIC] [TIFF OMITTED] TR08JN16.062
Where:
X\k=2\(Tj) = BL(Tj)/
Qc\k=2\(Tj), the cooling mode high capacity
load factor for temperature bin j, dimensionless.
PLFj = 1 - CDc(k = 2) * [1 - Xk=2(Tj) the part load factor,
dimensionless.
[GRAPHIC] [TIFF OMITTED] TR08JN16.063
4.1.2.7 Unit must operate continuously at high (k = 2) compressor
capacity at temperature Tj, BL(Tj)
>=Qc\k=2\(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.064
Obtain the fractional bin hours for the cooling season, nj/
N, from Table 18. Use Equations 4.1.3-3 and 4.1.3-4, respectively, to
evaluate Qc\k=2\(Tj) and
Ec\k=2\(Tj).
4.1.3 SEER Calculations for an Air Conditioner or Heat Pump Having a
Variable-Speed Compressor
Calculate SEER using Equation 4.1-1. Evaluate the space cooling
capacity, Qc\k=1\(Tj), and electrical power
consumption, Ec\k=1\(Tj), of the test unit when
operating at minimum compressor speed and outdoor temperature
Tj. Use,
[[Page 37103]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.065
where Qc\k=1\(82) and Ec\k=1\(82) are determined
from the B1 test, Qc\k=1\(67) and
Ec\k=1\(67) are determined from the F1 test, and all four
quantities are calculated as specified in section 3.3 of this appendix.
Evaluate the space cooling capacity, Qc\k=2\(Tj),
and electrical power consumption, Ec\k=2\(Tj), of
the test unit when operating at full compressor speed and outdoor
temperature Tj. Use Equations 4.1.3-3 and 4.1.3-4,
respectively, where Qc\k=2\(95) and Ec\k=2\(95)
are determined from the A2 test, Qc\k=2\(82) and
Ec\k=2\(82) are determined from the B2 test, and
all four quantities are calculated as specified in section 3.3 of this
appendix. Calculate the space cooling capacity,
Qc\k=v\(Tj), and electrical power consumption,
Ec\k=v\(Tj), of the test unit when operating at
outdoor temperature Tj and the intermediate compressor speed
used during the section 3.2.4 (and Table 7) EV test of this
appendix using,
Equation 4.1.4-3 Qck=v(Tj) = Qck=v(87) + MQ * (Tj - 87)
Equation 4.1.4-4 Eck=v(Tj) = Ehk=v(87) + ME * (Tj - 87)
where Qc\k=v\(87) and Ec\k=v\(87) are determined
from the EV test and calculated as specified in section 3.3
of this appendix. Approximate the slopes of the k=v intermediate speed
cooling capacity and electrical power input curves, MQ and
ME, as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.066
Use Equations 4.1.4-1 and 4.1.4-2, respectively, to calculate
Qc\k=1\(87) and Ec\k=1\(87).
4.1.3.1 Steady-state space cooling capacity when operating at minimum
compressor speed is greater than or equal to the building cooling load
at temperature Tj, Qc\k=1\(Tj)
>=BL(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.067
Where:
X\k=1\(Tj) = BL(Tj)/
Qc\k=1\(Tj), the cooling mode minimum speed
load factor for temperature bin j, dimensionless.
PLFj = 1 - CD\c\ [middot] [1 -
X\k=1\(Tj)], the part load factor, dimensionless.
nj/N = fractional bin hours for the cooling season; the
ratio of the number of hours during the cooling season when the
outdoor temperature fell within the range represented by bin
temperature Tj to the total number of hours in the
cooling season, dimensionless.
Obtain the fractional bin hours for the cooling season,
nj/N, from Table 18. Use Equations 4.1.3-1 and 4.1.3-2,
respectively, to evaluate Qc\k=l\ (Tj) and
Ec\k=l\ (Tj).
4.1.3.2 Unit operates at an intermediate compressor speed (k=i) in
order to match the building cooling load at temperature
Tj,Qc\k=1\(Tj) j)
c\k=2\(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.068
Where:
Qc\k=i\(Tj) = BL(Tj), the space
cooling capacity delivered by the unit in matching the building load
at temperature Tj, Btu/h. The matching occurs with the
unit operating at compressor speed k = i.
[[Page 37104]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.069
EER\k=i\(Tj) = the steady-state energy efficiency ratio
of the test unit when operating at a compressor speed of k = i and
temperature Tj, Btu/h per W.
Obtain the fractional bin hours for the cooling season,
nj/N, from Table 18. For each temperature bin where the unit
operates at an intermediate compressor speed, determine the energy
efficiency ratio EER\k=i\(Tj) using,
EER\k=i\(Tj) = A + B [middot] Tj + C [middot]
Tj\2\.
For each unit, determine the coefficients A, B, and C by conducting
the following calculations once:
[GRAPHIC] [TIFF OMITTED] TR08JN16.070
Where:
T1 = the outdoor temperature at which the unit, when
operating at minimum compressor speed, provides a space cooling
capacity that is equal to the building load (Qc\k=l\
(Tl) = BL(T1)), [deg]F. Determine
T1 by equating Equations 4.1.3-1 and 4.1-2 and solving
for outdoor temperature.
Tv = the outdoor temperature at which the unit, when
operating at the intermediate compressor speed used during the
section 3.2.4 EV test of this appendix, provides a space
cooling capacity that is equal to the building load
(Qc\k=v\ (Tv) = BL(Tv)), [deg]F.
Determine Tv by equating Equations 4.1.4-3 and 4.1-2 and
solving for outdoor temperature.
T2 = the outdoor temperature at which the unit, when
operating at full compressor speed, provides a space cooling
capacity that is equal to the building load (Qc\k=2\
(T2) = BL(T2)), [deg]F. Determine
T2 by equating Equations 4.1.3-3 and 4.1-2 and solving
for outdoor temperature.
[GRAPHIC] [TIFF OMITTED] TR08JN16.071
4.1.3.3 Unit must operate continuously at full (k = 2) compressor speed
at temperature Tj, BL(Tj)
>=Qc\k=2\(Tj). Evaluate the Equation 4.1-1
quantities
[GRAPHIC] [TIFF OMITTED] TR08JN16.072
as specified in section 4.1.2.7 of this appendix with the understanding
that Qck=2(Tj) and
Eck=2(Tj) correspond to full
compressor speed operation and are derived from the results of the
tests specified in section 3.2.4 of this appendix.
4.1.4 SEER Calculations for an Air Conditioner or Heat Pump Having a
Single Indoor Unit With Multiple Indoor Blowers
Calculate SEER using Eq. 4.1-1, where qc(Tj)/N and
ec(Tj)/N are evaluated as specified in the applicable
subsection.
4.1.4.1 For Multiple Indoor Blower Systems That Are Connected to a
Single, Single-Speed Outdoor Unit
a. Calculate the space cooling capacity, Qck=1(Tj), and
electrical power consumption, Eck=1(Tj), of the test unit
when operating at the cooling minimum air volume rate and outdoor
temperature Tj using the equations given in section 4.1.2.1
of this appendix. Calculate the space cooling capacity,
Qck=2(Tj), and electrical power consumption,
Eck=2(Tj), of the test unit when operating at the cooling
full-load air volume rate and outdoor temperature Tj using
the equations given in section 4.1.2.1 of this appendix. In evaluating
the section 4.1.2.1 equations, determine the quantities
Qck=1(82) and Eck=1(82) from the B1 test,
Qck=1(95) and Eck=1(95) from the Al test,
Qck=2(82) and Eck=2(82) from the B2 test, and
Qck=2(95) and Eck=2(95) from the A2 test.
Evaluate all eight quantities as specified in section 3.3 of this
appendix. Refer to section 3.2.2.1 and Table 5 of this appendix for
additional information on the four referenced laboratory tests.
b. Determine the cooling mode cyclic degradation coefficient,
CDc, as per sections 3.2.2.1 and 3.5 to 3.5.3 of this
[[Page 37105]]
appendix. Assign this same value to CDc(K=2).
c. Except for using the above values of Qck=1(Tj),
Eck=1(Tj), Eck=2(Tj), Qck=2(Tj),
CDc, and CDc (K=2), calculate the quantities
qc(Tj)/N and ec(Tj)/N as
specified in section 4.1.3.1 of this appendix for cases where
Qck=1(Tj) >= BL(Tj). For all other outdoor bin
temperatures, Tj, calculate qc(Tj)/N and
ec(Tj)/N as specified in section 4.1.3.3 of this appendix if
Qck=2(Tj) > BL(Tj) or as specified in section
4.1.3.4 of this appendix if Qck=2(Tj) <= BL(Tj).
4.1.4.2 For multiple indoor blower systems that are connected to either
a lone outdoor unit having a two-capacity compressor or to two separate
single-speed outdoor units of identical model, calculate the quantities
qc(Tj)/N and ec(Tj)/N as specified in section
4.1.3 of this appendix.
4.2 Heating Seasonal Performance Factor (HSPF) Calculations
Unless an approved alternative efficiency determination method is
used, as set forth in 10 CFR 429.70(e), HSPF must be calculated as
follows: Six generalized climatic regions are depicted in Figure 1 and
otherwise defined in Table 19. For each of these regions and for each
applicable standardized design heating requirement, evaluate the
heating seasonal performance factor using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.073
Where:
eh(Tj)/N = The ratio of the electrical energy
consumed by the heat pump during periods of the space heating season
when the outdoor temperature fell within the range represented by
bin temperature Tj to the total number of hours in the
heating season (N), W. For heat pumps having a heat comfort
controller, this ratio may also include electrical energy used by
resistive elements to maintain a minimum air delivery temperature
(see 4.2.5).
RH(Tj)/N = The ratio of the electrical energy used for
resistive space heating during periods when the outdoor temperature
fell within the range represented by bin temperature Tj
to the total number of hours in the heating season (N), W. Except as
noted in section 4.2.5 of this appendix, resistive space heating is
modeled as being used to meet that portion of the building load that
the heat pump does not meet because of insufficient capacity or
because the heat pump automatically turns off at the lowest outdoor
temperatures. For heat pumps having a heat comfort controller, all
or part of the electrical energy used by resistive heaters at a
particular bin temperature may be reflected in
eh(Tj)/N (see section 4.2.5 of this appendix).
Tj = the outdoor bin temperature, [deg]F. Outdoor
temperatures are ``binned'' such that calculations are only
performed based one temperature within the bin. Bins of 5 [deg]F are
used.
nj/N = Fractional bin hours for the heating season; the
ratio of the number of hours during the heating season when the
outdoor temperature fell within the range represented by bin
temperature Tj to the total number of hours in the
heating season, dimensionless. Obtain nj/N values from
Table 19.
j = the bin number, dimensionless.
J = for each generalized climatic region, the total number of
temperature bins, dimensionless. Referring to Table 19, J is the
highest bin number (j) having a nonzero entry for the fractional bin
hours for the generalized climatic region of interest.
Fdef = the demand defrost credit described in section
3.9.2 of this appendix, dimensionless.
BL(Tj) = the building space conditioning load
corresponding to an outdoor temperature of Tj; the
heating season building load also depends on the generalized
climatic region's outdoor design temperature and the design heating
requirement, Btu/h.
Table 19--Generalized Climatic Region Information
--------------------------------------------------------------------------------------------------------------------------------------------------------
Region No. I II III IV V VI
--------------------------------------------------------------------------------------------------------------------------------------------------------
Heating Load Hours, HLH................................. 750 1,250 1,750 2,250 2,750 * 2,750
Outdoor Design Temperature, TOD......................... 37 27 17 5 -10 30
-----------------------------------------------------------------------------------------------
j Tj ([deg]F)........................................... Fractional Bin Hours, nj/N
-----------------------------------------------------------------------------------------------
1 62.................................................... .291 .215 .153 .132 .106 .113
2 57.................................................... .239 .189 .142 .111 .092 .206
3 52.................................................... .194 .163 .138 .103 .086 .215
4 47.................................................... .129 .143 .137 .093 .076 .204
5 42.................................................... .081 .112 .135 .100 .078 .141
6 37.................................................... .041 .088 .118 .109 .087 .076
7 32.................................................... .019 .056 .092 .126 .102 .034
8 27.................................................... .005 .024 .047 .087 .094 .008
9 22.................................................... .001 .008 .021 .055 .074 .003
10 17................................................... 0 .002 .009 .036 .055 0
11 12................................................... 0 0 .005 .026 .047 0
12 7.................................................... 0 0 .002 .013 .038 0
13 2.................................................... 0 0 .001 .006 .029 0
14 -3................................................... 0 0 0 .002 .018 0
15 -8................................................... 0 0 0 .001 .010 0
16 -13.................................................. 0 0 0 0 .005 0
17 -18.................................................. 0 0 0 0 .002 0
18 -23.................................................. 0 0 0 0 .001 0
--------------------------------------------------------------------------------------------------------------------------------------------------------
* Pacific Coast Region.
[[Page 37106]]
Evaluate the building heating load using
[GRAPHIC] [TIFF OMITTED] TR08JN16.074
Where:
TOD = the outdoor design temperature, [deg]F. An outdoor
design temperature is specified for each generalized climatic region
in Table 19.
C = 0.77, a correction factor which tends to improve the agreement
between calculated and measured building loads, dimensionless.
DHR = the design heating requirement (see section 1.2 of this
appendix, Definitions), Btu/h.
Calculate the minimum and maximum design heating requirements for
each generalized climatic region as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.075
where Qh\k\(47) is expressed in units of Btu/h and otherwise
defined as follows:
a. For a single-speed heat pump tested as per section 3.6.1 of this
appendix, Qh\k\(47) = Qh(47), the space heating
capacity determined from the H1 test.
b. For a variable-speed heat pump, a section 3.6.2 single-speed
heat pump, or a two-capacity heat pump not covered by item 3,
Qn\k\(47) = Qn\k=2\(47), the space heating
capacity determined from the H12 test.
c. For two-capacity, northern heat pumps (see section 1.2 of this
appendix, Definitions), Q\k\h(47) = Q\k=1\h(47),
the space heating capacity determined from the H11 test.
If the optional H1N test is conducted on a variable-
speed heat pump, the manufacturer has the option of defining
Q\k\h(47) as specified above in item 2 or as
Q\k\h(47) = Q\k = N\h(47), the space heating
capacity determined from the H1N test.
For all heat pumps, HSPF accounts for the heating delivered and the
energy consumed by auxiliary resistive elements when operating below
the balance point. This condition occurs when the building load exceeds
the space heating capacity of the heat pump condenser. For HSPF
calculations for all heat pumps, see either section 4.2.1, 4.2.2,
4.2.3, or 4.2.4 of this appendix, whichever applies.
For heat pumps with heat comfort controllers (see section 1.2 of
this appendix, Definitions), HSPF also accounts for resistive heating
contributed when operating above the heat-pump-plus-comfort-controller
balance point as a result of maintaining a minimum supply temperature.
For heat pumps having a heat comfort controller, see section 4.2.5 of
this appendix for the additional steps required for calculating the
HSPF.
Table 20--Standardized Design Heating Requirements
[Btu/h]
------------------------------------------------------------------------
------------------------------------------------------------------------
5,000 50,000
10,000 60,000
15,000 70,000
20,000 80,000
25,000 90,000
30,000 100,000
35,000 110,000
40,000 130,000
------------------------------------------------------------------------
4.2.1 Additional steps for calculating the HSPF of a blower coil
system heat pump having a single-speed compressor and either a fixed-
speed indoor blower or a constant-air-volume-rate indoor blower
installed, or a coil-only system heat pump.
[GRAPHIC] [TIFF OMITTED] TR08JN16.076
[[Page 37107]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.077
whichever is less; the heating mode load factor for temperature bin j,
dimensionless.
Qh(Tj) = the space heating capacity of the
heat pump when operating at outdoor temperature Tj, Btu/
h.
Eh(Tj) = the electrical power consumption of
the heat pump when operating at outdoor temperature Tj,
W.
[delta](Tj) = the heat pump low temperature cut-out
factor, dimensionless.
PLFj = 1 - CD\h\ [middot] [1 -
X(Tj)] the part load factor, dimensionless.
Use Equation 4.2-2 to determine BL(Tj). Obtain
fractional bin hours for the heating season, nj/N, from
Table 19.
Determine the low temperature cut-out factor using
[GRAPHIC] [TIFF OMITTED] TR08JN16.078
Where:
Toff = the outdoor temperature when the compressor is
automatically shut off, [deg]F. (If no such temperature exists,
Tj is always greater than Toff and
Ton).
Ton = the outdoor temperature when the compressor is
automatically turned back on, if applicable, following an automatic
shut-off, [deg]F.
Calculate Qh(Tj) and
Eh(Tj) using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.079
where Qh(47) and Eh(47) are determined from the
H1 test and calculated as specified in section 3.7 of this appendix;
Qh(35) and Eh(35) are determined from the H2 test
and calculated as specified in section 3.9.1 of this appendix; and
Qh(17) and Eh(17) are determined from the H3 test
and calculated as specified in section 3.10 of this appendix.
4.2.2 Additional steps for calculating the HSPF of a heat pump having a
single-speed compressor and a variable-speed, variable-air-volume-rate
indoor blower.
The manufacturer must provide information about how the indoor air
volume rate or the indoor blower speed varies over the outdoor
temperature range of 65 [deg]F to -23 [deg]F. Calculate the quantities
[GRAPHIC] [TIFF OMITTED] TR08JN16.080
in Equation 4.2-1 as specified in section 4.2.1 of this appendix with
the exception of replacing references to the
[[Page 37108]]
H1C test and section 3.6.1 of this appendix with the H1C1
test and section 3.6.2 of this appendix. In addition, evaluate the
space heating capacity and electrical power consumption of the heat
pump Qh(Tj) and Eh(Tj)
using
[GRAPHIC] [TIFF OMITTED] TR08JN16.081
For units where indoor blower speed is the primary control
variable, FPh\k=1\ denotes the fan speed used during the
required H11 and H31 tests (see Table 11),
FPh\k=2\ denotes the fan speed used during the required
H12, H22, and H32 tests, and
FPh(Tj) denotes the fan speed used by the unit
when the outdoor temperature equals Tj. For units where
indoor air volume rate is the primary control variable, the three
FPh's are similarly defined only now being expressed in
terms of air volume rates rather than fan speeds. Determine
Qh\k=1\(47) and Eh\k=1\(47) from the
H11 test, and Qh\k=2\(47) and
Eh\k=2\(47) from the H12 test. Calculate all four
quantities as specified in section 3.7 of this appendix. Determine
Qh\k=1\(35) and Eh\k=1\(35) as specified in
section 3.6.2 of this appendix; determine Qh\k=2\(35) and
Eh\k=2\(35) and from the H22 test and the
calculation specified in section 3.9 of this appendix. Determine
Qh\k=1\(17) and Eh\k=1\(17 from the
H31 test, and Qh\k=2\(17) and
Eh\k=2\(17) from the H32 test. Calculate all four
quantities as specified in section 3.10 of this appendix.
4.2.3 Additional Steps for Calculating the HSPF of a Heat Pump Having a
Two-Capacity Compressor
The calculation of the Equation 4.2-1 quantities differ depending
upon whether the heat pump would operate at low capacity (section
4.2.3.1 of this appendix), cycle between low and high capacity (section
4.2.3.2 of this appendix), or operate at high capacity (sections
4.2.3.3 and 4.2.3.4 of this appendix) in responding to the building
load. For heat pumps that lock out low capacity operation at low
outdoor temperatures, the manufacturer must supply information
regarding the cutoff temperature(s) so that the appropriate equations
can be selected.
[GRAPHIC] [TIFF OMITTED] TR08JN16.082
a. Evaluate the space heating capacity and electrical power
consumption of the heat pump when operating at low compressor capacity
and outdoor temperature Tj using
[[Page 37109]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.083
b. Evaluate the space heating capacity and electrical power
consumption (Qh\k=2\(Tj) and Eh\k=2\
(Tj)) of the heat pump when operating at high compressor
capacity and outdoor temperature Tj by solving Equations 4.2.2-3 and
4.2.2-4, respectively, for k=2. Determine Qh\k=1\(62) and
Eh\k=1\(62) from the H01 test,
Qh\k=1\(47) and Eh\k=1\(47) from the
H11 test, and Qh\k=2\(47) and
Eh\k=2\(47) from the H12 test. Calculate all six
quantities as specified in section 3.7 of this appendix. Determine
Qh\k=2\(35) and Eh\k=2\(35) from the
H22 test and, if required as described in section 3.6.3 of
this appendix, determine Qh\k=1\(35) and
Eh\k=1\(35) from the H21 test. Calculate the
required 35 [deg]F quantities as specified in section 3.9 of this
appendix. Determine Qh\k=2\(17) and Eh\k=2\(17)
from the H32 test and, if required as described in section
3.6.3 of this appendix, determine Qh\k=1\(17) and
Eh\k=1\(17) from the H31 test. Calculate the
required 17 [deg]F quantities as specified in section 3.10 of this
appendix.
4.2.3.1 Steady-state space heating capacity when operating at low
compressor capacity is greater than or equal to the building heating
load at temperature Tj, Qh\k=1\(Tj)
>=BL(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.084
Where:
X\k=1\(Tj) = BL(Tj)/
Qh\k=1\(Tj), the heating mode low capacity
load factor for temperature bin j, dimensionless.
PLFj = 1 - CD\h\ [middot] [ 1 -
X\k=1\(Tj) ], the part load factor, dimensionless.
[delta]'(Tj) = the low temperature cutoff factor,
dimensionless.
Determine the low temperature cut-out factor using
[GRAPHIC] [TIFF OMITTED] TR08JN16.085
where Toff and Ton are defined in section 4.2.1
of this appendix. Use the calculations given in section 4.2.3.3 of this
appendix, and not the above, if:
a. The heat pump locks out low capacity operation at low outdoor
temperatures and
b. Tj is below this lockout threshold temperature.
4.2.3.2 Heat pump alternates between high (k=2) and low (k=1)
compressor capacity to satisfy the building heating load at a
temperature Tj, Qhk=1(Tj)
j) hk=2(Tj).
[[Page 37110]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.086
Determine the low temperature cut-out factor,
[delta]'(Tj), using Equation 4.2.3-3.
4.2.3.3 Heat pump only operates at high (k=2) compressor capacity at
temperature Tj and its capacity is greater than the building
heating load, BL(Tj)
hk=2(Tj). This section applies to
units that lock out low compressor capacity operation at low outdoor
temperatures.
[GRAPHIC] [TIFF OMITTED] TR08JN16.087
If the H1C2 test described in section 3.6.3 and Table 12
of this appendix is not conducted, set CD\h\ (k=2) equal to
the default value specified in section 3.8.1 of this appendix.
Determine the low temperature cut-out factor,
[delta](Tj), using Equation 4.2.3-3.
4.2.3.4 Heat pump must operate continuously at high (k=2) compressor
capacity at temperature Tj, BL(Tj)
>=Qhk=2(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.088
[[Page 37111]]
4.2.4 Additional Steps for Calculating the HSPF of a Heat Pump Having a
Variable-Speed Compressor
Calculate HSPF using Equation 4.2-1. Evaluate the space heating
capacity, Qhk=1(Tj), and electrical
power consumption, Ehk=1(Tj), of the
heat pump when operating at minimum compressor speed and outdoor
temperature Tj using
[GRAPHIC] [TIFF OMITTED] TR08JN16.089
where Qhk=1(62) and
Ehk=1(62) are determined from the H01
test, Qhk=1(47) and
Ehk=1(47) are determined from the H11
test, and all four quantities are calculated as specified in section
3.7 of this appendix.
Evaluate the space heating capacity,
Qhk=2(Tj), and electrical power
consumption, Ehk=2(Tj), of the heat
pump when operating at full compressor speed and outdoor temperature
Tj by solving Equations 4.2.2-3 and 4.2.2-4, respectively,
for k=2. Determine the Equation 4.2.2-3 and 4.2.2-4 quantities
Qhk=2(47) and Ehk=2(47)
from the H12 test and the calculations specified in section
3.7 of this appendix. Determine Qhk=2(35) and
Ehk=2(35) from the H22 test and the
calculations specified in section 3.9 of this appendix or, if the
H22 test is not conducted, by conducting the calculations
specified in section 3.6.4 of this appendix. Determine
Qhk=2(17) and Ehk=2(17)
from the H32 test and the calculations specified in section
3.10 of this appendix. Calculate the space heating capacity,
Qhk=v(Tj), and electrical power
consumption, Ehk=v(Tj), of the heat
pump when operating at outdoor temperature Tj and the
intermediate compressor speed used during the section 3.6.4
H2V test of this appendix using
Equation 4.2.4-3 Qhk=v(Tj =
Qhk=v (35) + MQ*(Tj - 35)
Equation 4.2.4-4 Ehk=v(Tj =
Ehk=v (35) + ME * (Tj - 35)
where Qhk=v(35) and
Ehk=v(35) are determined from the H2V
test and calculated as specified in section 3.9 of this appendix.
Approximate the slopes of the k=v intermediate speed heating capacity
and electrical power input curves, MQ and ME, as
follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.090
4.2.4.1 Steady-state space heating capacity when operating at minimum
compressor speed is greater than or equal to the building heating load
at temperature Tj, Qhk=1(Tj
>=BL(Tj).
Evaluate the Equation 4.2-1 quantities
[[Page 37112]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.091
as specified in section 4.2.3.1 of this appendix. Except now use
Equations 4.2.4-1 and 4.2.4-2 to evaluate
Qhk=1(Tj) and
Ehk=1(Tj), respectively, and replace
section 4.2.3.1 references to ``low capacity'' and section 3.6.3 of
this appendix with ``minimum speed'' and section 3.6.4 of this
appendix. Also, the last sentence of section 4.2.3.1 of this appendix
does not apply.
4.2.4.2 Heat pump operates at an intermediate compressor speed (k=i) in
order to match the building heating load at a temperature
Tj, Qhk=1(Tj)
j) hk=2(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.092
and [delta](Tj) is evaluated using Equation 4.2.3-3 while,
Qhk=i(Tj) = BL(Tj), the
space heating capacity delivered by the unit in matching the
building load at temperature (Tj), Btu/h. The matching
occurs with the heat pump operating at compressor speed k=i.
COP\k=i\(Tj) = the steady-state coefficient of
performance of the heat pump when operating at compressor speed k=i
and temperature Tj, dimensionless.
For each temperature bin where the heat pump operates at an
intermediate compressor speed, determine COP\k=i\(Tj) using,
COP\k=i\(Tj) = A + B [middot] Tj + C [middot]
Tj.
For each heat pump, determine the coefficients A, B, and C by
conducting the following calculations once:
[GRAPHIC] [TIFF OMITTED] TR08JN16.093
Where:
T3 = the outdoor temperature at which the heat pump, when
operating at minimum compressor speed, provides a space heating
capacity that is equal to the building load
(Qhk=1(T3) = BL(T3)),
[deg]F. Determine T3 by equating Equations 4.2.4-1 and
4.2-2 and solving for outdoor temperature.
Tvh = the outdoor temperature at which the heat pump,
when operating at the intermediate compressor speed used during the
section 3.6.4 H2V test of this appendix, provides a space
heating capacity that is equal to the building load
(Qhk=v(Tvh) = BL(Tvh)),
[deg]F. Determine Tvh by equating Equations 4.2.4-3 and
4.2-2 and solving for outdoor temperature.
T4 = the outdoor temperature at which the heat pump, when
operating at full compressor speed, provides a space heating
capacity that is equal to the building load
(Qhk=2(T4) = BL(T4)),
[deg]F. Determine T4 by equating Equations 4.2.2-3 (k=2)
and 4.2-2 and solving for outdoor temperature.
[[Page 37113]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.094
For multiple-split heat pumps (only), the following procedures
supersede the above requirements for calculating
COPhk=i(Tj). For each temperature
bin where T3 >Tj >Tvh,
[GRAPHIC] [TIFF OMITTED] TR08JN16.095
4.2.4.3 Heat pump must operate continuously at full (k=2) compressor
speed at temperature Tj, BL(Tj)
>=Qhk=2(Tj). Evaluate the Equation
4.2-1 quantities
[GRAPHIC] [TIFF OMITTED] TR08JN16.096
as specified in section 4.2.3.4 of this appendix with the
understanding that Qhk=2(Tj) and
Eh\k=2\(Tj) correspond to full compressor
speed operation and are derived from the results of the specified
section 3.6.4 tests of this appendix.
4.2.5 Heat Pumps Having a Heat Comfort Controller
Heat pumps having heat comfort controllers, when set to maintain
a typical minimum air delivery temperature, will cause the heat pump
condenser to operate less because of a greater contribution from the
resistive elements. With a conventional heat pump, resistive heating
is only initiated if the heat pump condenser cannot meet the
building load (i.e., is delayed until a second stage call from the
indoor thermostat). With a heat comfort controller, resistive
heating can occur even though the heat pump condenser has adequate
capacity to meet the building load (i.e., both on during a first
stage call from the indoor thermostat). As a result, the outdoor
temperature where the heat pump compressor no longer cycles (i.e.,
starts to run continuously), will be lower than if the heat pump did
not have the heat comfort controller.
4.2.5.1 Blower coil system heat pump having a heat comfort
controller: Additional steps for calculating the HSPF of a heat pump
having a single-speed compressor and either a fixed-speed indoor
blower or a constant-air-volume-rate indoor blower installed, or a
coil-only system heat pump.
Calculate the space heating capacity and electrical power of the
heat pump without the heat comfort controller being active as
specified in section 4.2.1 of this appendix (Equations 4.2.1-4 and
4.2.1-5) for each outdoor bin temperature, Tj, that is
listed in Table 19. Denote these capacities and electrical powers by
using the subscript ``hp'' instead of ``h.'' Calculate the mass flow
rate (expressed in pounds-mass of dry air per hour) and the specific
heat of the indoor air (expressed in Btu/lbmda [middot]
[deg]F) from the results of the H1 test using:
[GRAPHIC] [TIFF OMITTED] TR08JN16.097
where Vis, Vimx, v'n (or
vn), and Wn are defined following Equation 3-
1. For each outdoor bin temperature listed in Table 19, calculate
the nominal temperature of the air leaving the heat pump condenser
coil using,
[[Page 37114]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.098
Evaluate eh(Tj/N), RH(Tj)/N,
X(Tj), PLFj, and [delta](Tj) as
specified in section 4.2.1 of this appendix. For each bin
calculation, use the space heating capacity and electrical power
from Case 1 or Case 2, whichever applies.
Case 1. For outdoor bin temperatures where
To(Tj) is equal to or greater than
TCC (the maximum supply temperature determined according
to section 3.1.9 of this appendix), determine
Qh(Tj) and Eh(Tj) as
specified in section 4.2.1 of this appendix (i.e.,
Qh(Tj) = Qhp(Tj) and
Ehp(Tj) = Ehp(Tj)).
Note: Even though To(Tj) >=Tcc,
resistive heating may be required; evaluate Equation 4.2.1-2 for all
bins.
Case 2. For outdoor bin temperatures where
To(Tj) > Tcc, determine
Qh(Tj) and Eh(Tj) using
Qh(Tj) = Qhp(Tj) +
QCC(Tj) Eh(Tj) =
Ehp(Tj) + ECC(Tj)
where:
[GRAPHIC] [TIFF OMITTED] TR08JN16.099
Note: Even though To(Tj) cc,
additional resistive heating may be required; evaluate Equation
4.2.1-2 for all bins.
4.2.5.2 Heat pump having a heat comfort controller: Additional steps
for calculating the HSPF of a heat pump having a single-speed
compressor and a variable-speed, variable-air-volume-rate indoor
blower.
Calculate the space heating capacity and electrical power of the
heat pump without the heat comfort controller being active as
specified in section 4.2.2 of this appendix (Equations 4.2.2-1 and
4.2.2-2) for each outdoor bin temperature, Tj, that is
listed in Table 19. Denote these capacities and electrical powers by
using the subscript ``hp'' instead of ``h.'' Calculate the mass flow
rate (expressed in pounds-mass of dry air per hour) and the specific
heat of the indoor air (expressed in Btu/lbmda [middot]
[deg]F) from the results of the H12 test using:
[GRAPHIC] [TIFF OMITTED] TR08JN16.100
where ViS, Vimx, v'n (or
vn), and Wn are defined following Equation 3-
1. For each outdoor bin temperature listed in Table 19, calculate
the nominal temperature of the air leaving the heat pump condenser
coil using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.101
Evaluate eh(Tj)/N, RH(Tj)/N,
X(Tj), PLFj, and [delta](Tj) as
specified in section 4.2.1 of this appendix with the exception of
replacing references to the H1C test and section 3.6.1 of this
appendix with the H1C1 test and section 3.6.2 of this
appendix. For each bin calculation, use the space heating capacity
and electrical power from Case 1 or Case 2, whichever applies.
Case 1. For outdoor bin temperatures where
To(Tj) is equal to or greater than
TCC (the maximum supply temperature determined according
to section 3.1.9 of this appendix), determine
Qh(Tj) and Eh(Tj) as
specified in section 4.2.2 of this appendix (i.e.
Qh(Tj) = Qhp(Tj) and
Eh(Tj) = Ehp(Tj)).
Note: Even though To(Tj) >=
TCC, resistive heating may be required; evaluate Equation
4.2.1-2 for all bins.
Case 2. For outdoor bin temperatures where
To(Tj) CC, determine
Qh(Tj) and Eh(Tj) using
Qh(Tj) = Qhp(Tj) +
QCC(Tj) Eh(Tj) =
Ehp(Tj) + ECC(Tj)
[GRAPHIC] [TIFF OMITTED] TR08JN16.102
Note: Even though To(Tj) cc,
additional resistive heating may be required; evaluate Equation
4.2.1-2 for all bins.
4.2.5.3 Heat pumps having a heat comfort controller: Additional
steps for calculating the HSPF of a heat pump having a two-capacity
compressor.
Calculate the space heating capacity and electrical power of the
heat pump without the heat comfort controller being active as
specified in section 4.2.3 of this appendix for both high and low
capacity and at each outdoor bin temperature, Tj, that is
listed in Table 19. Denote these capacities and electrical powers by
using the subscript ``hp'' instead of ``h.'' For the low capacity
case, calculate the mass flow rate (expressed in pounds-mass of dry
air per hour) and the specific heat of the indoor air (expressed in
Btu/lbmda [middot] [deg]F) from the results of the
H11 test using:
[[Page 37115]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.103
where Vis, Vimx, v'n (or
vn), and Wn are defined following Equation 3-
1. For each outdoor bin temperature listed in Table 19, calculate
the nominal temperature of the air leaving the heat pump condenser
coil when operating at low capacity using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.104
Repeat the above calculations to determine the mass flow rate
(mda\k=2\) and the specific heat of the indoor air
(Cp,da\k=2\) when operating at high capacity by using the
results of the H12 test. For each outdoor bin temperature
listed in Table 19, calculate the nominal temperature of the air
leaving the heat pump condenser coil when operating at high capacity
using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.105
Evaluate eh(Tj)/N, RH(Tj)/N,
X\k=1\(Tj), and/or X\k=2\(Tj),
PLFj, and [delta]'(Tj) or
[delta]''(Tj) as specified in section 4.2.3.1. 4.2.3.2,
4.2.3.3, or 4.2.3.4 of this appendix, whichever applies, for each
temperature bin. To evaluate these quantities, use the low-capacity
space heating capacity and the low-capacity electrical power from
Case 1 or Case 2, whichever applies; use the high-capacity space
heating capacity and the high-capacity electrical power from Case 3
or Case 4, whichever applies.
Case 1. For outdoor bin temperatures where
To\k=1\(Tj) is equal to or greater than
TCC (the maximum supply temperature determined according
to section 3.1.9 of this appendix), determine
Qh\k=1\(Tj) and
Eh\k=1\(Tj) as specified in section 4.2.3 of
this appendix (i.e., Qh\k=1\(Tj) =
Qhp\k=1\(Tj) and
Eh\k=1\(Tj) =
Ehp\k=1\(Tj).
Note: Even though To\k=1\(Tj)
>=TCC, resistive heating may be required; evaluate
RH(Tj)/N for all bins.
Case 2. For outdoor bin temperatures where
To\k=1\(Tj) CC, determine
Qh\k=1\(Tj) and
Eh\k=1\(Tj) using
Qh\k=1\(Tj) =
Qhp\k=1\(Tj) +
QCC\k=1\(Tj) Eh\k=1\(Tj)
= Ehp\k=1\(Tj) +
ECC\k=1\(Tj)
where,
[GRAPHIC] [TIFF OMITTED] TR08JN16.106
Note: Even though To\k=1\(Tj)
>=Tcc, additional resistive heating may be required;
evaluate RH(Tj)/N for all bins.
Case 3. For outdoor bin temperatures where
To\k=2\(Tj) is equal to or greater than
TCC, determine Qh\k=2\(Tj) and
Eh\k=2\(Tj) as specified in section 4.2.3 of
this appendix (i.e., Qh\k=2\(Tj) =
Qhp\k=2\(Tj) and
Eh\k=2\(Tj) =
Ehp\k=2\(Tj)).
Note: Even though To\k=2\(Tj)
CC, resistive heating may be required; evaluate
RH(Tj)/N for all bins.
Case 4. For outdoor bin temperatures where
To\k=2\(Tj) CC, determine
Qh\k=2\(Tj) and
Eh\k=2\(Tj) using
Qh\k=2\(Tj) =
Qhp\k=2\(Tj) +
QCC\k=2\(Tj) Eh\k=2\(Tj)
= Ehp\k=2\(Tj) +
ECC\k=2\(Tj)
where,
[GRAPHIC] [TIFF OMITTED] TR08JN16.107
Note: Even though To\k=2\(Tj)
cc, additional resistive heating may be required;
evaluate RH(Tj)/N for all bins.
4.2.5.4 Heat pumps having a heat comfort controller: Additional
steps for calculating the HSPF of a heat pump having a variable-
speed compressor. [Reserved]
4.2.6 Additional steps for calculating the HSPF of a heat pump
having a triple-capacity compressor.
The only triple-capacity heat pumps covered are triple-capacity,
northern heat pumps. For such heat pumps, the calculation of the Eq.
4.2-1 quantities
[GRAPHIC] [TIFF OMITTED] TR08JN16.108
differ depending on whether the heat pump would cycle on and off at
low capacity (section 4.2.6.1 of this appendix), cycle on and off at
high capacity (section 4.2.6.2 of this appendix), cycle on and off
at booster capacity (section 4.2.6.3 of this appendix), cycle
between low and high capacity (section 4.2.6.4 of this appendix),
cycle between high and booster capacity (section 4.2.6.5 of this
appendix), operate continuously at low capacity (4.2.6.6 of this
appendix), operate continuously at high capacity (section 4.2.6.7 of
this appendix), operate continuously at booster capacity (section
4.2.6.8 of this appendix), or heat solely using resistive
[[Page 37116]]
heating (also section 4.2.6.8 of this appendix) in responding to the
building load. As applicable, the manufacturer must supply
information regarding the outdoor temperature range at which each
stage of compressor capacity is active. As an informative example,
data may be submitted in this manner: At the low (k = 1) compressor
capacity, the outdoor temperature range of operation is 40 [deg]F <=
T <= 65 [deg]F; At the high (k = 2) compressor capacity, the outdoor
temperature range of operation is 20 [deg]F <= T <= 50 [deg]F; At
the booster (k = 3) compressor capacity, the outdoor temperature
range of operation is -20 [deg]F <= T <= 30 [deg]F.
a. Evaluate the space heating capacity and electrical power
consumption of the heat pump when operating at low compressor
capacity and outdoor temperature Tj using the equations given in
section 4.2.3 of this appendix for Qh\k=1\(Tj)
and Eh\k=1\(Tj)) In evaluating the section
4.2.3 equations, Determine Qh\k=1\(62) and
Eh\k=1\(62) from the H01 test,
Qh\k=1\(47) and Eh\k=1\(47) from the
H11 test, and Qh\k=2\(47) and
Eh\k=2\(47) from the H12 test. Calculate all
four quantities as specified in section 3.7 of this appendix. If, in
accordance with section 3.6.6 of this appendix, the H31
test is conducted, calculate Qh\k=1\(17) and
Eh\k=1\(17) as specified in section 3.10 of this appendix
and determine Qh\k=1\(35) and Eh\k=1\(35) as
specified in section 3.6.6 of this appendix.
b. Evaluate the space heating capacity and electrical power
consumption (Qh\k=2\(Tj) and
Eh\k=2\(Tj)) of the heat pump when operating
at high compressor capacity and outdoor temperature Tj by solving
Equations 4.2.2-3 and 4.2.2-4, respectively, for k = 2. Determine
Qh\k=1\(62) and Eh\k=1\(62) from the
H01 test, Qh\k=1\(47) and
Eh\k=1\(47) from the H11 test, and
Qh\k=2\(47) and Eh\k=2\(47) from the
H12 test, evaluated as specified in section 3.7 of this
appendix. Determine the equation input for Qh\k=2\(35)
and Eh\k=2\(35) from the H22, evaluated as
specified in section 3.9.1 of this appendix. Also, determine
Qh\k=2\(17) and Eh\k=2\(17) from the
H32 test, evaluated as specified in section 3.10 of this
appendix.
c. Evaluate the space heating capacity and electrical power
consumption of the heat pump when operating at booster compressor
capacity and outdoor temperature Tj using
[GRAPHIC] [TIFF OMITTED] TR08JN16.109
Determine Qh\k=3\(17) and Eh\k=3\(17) from
the H33 test and determine Qh\k=2\(2) and
Eh\k=3\(2) from the H43 test. Calculate all
four quantities as specified in section 3.10 of this appendix.
Determine the equation input for Qh\k=3\(35) and
Eh\k=3\(35) as specified in section 3.6.6 of this
appendix.
4.2.6.1 Steady-state space heating capacity when operating at low
compressor capacity is greater than or equal to the building heating
load at temperature Tj, Qh\k=1\(Tj)
>= BL(Tj)., and the heat pump permits low compressor
capacity at Tj.
Evaluate the quantities
[GRAPHIC] [TIFF OMITTED] TR08JN16.110
using Eqs. 4.2.3-1 and 4.2.3-2, respectively. Determine the equation
inputs X\k=1\(Tj), PLFj, and
[delta]'(Tj) as specified in section 4.2.3.1 of this
appendix. In calculating the part load factor, PLFj, use
the low-capacity cyclic-degradation coefficient CD\h\,
[or equivalently, CD\h\(k = 1)] determined in accordance
with section 3.6.6 of this appendix.
4.2.6.2 Heat pump only operates at high (k = 2) compressor capacity
at temperature Tj and its capacity is greater than or
equal to the building heating load, BL(Tj) <
Qh\k=2\(Tj).
Evaluate the quantities
[GRAPHIC] [TIFF OMITTED] TR08JN16.111
as specified in section 4.2.3.3 of this appendix. Determine the
equation inputs X\k=2\(Tj), PLFj, and
[delta]'(Tj) as specified in section 4.2.3.3 of this
appendix. In calculating the part load factor, PLFj, use
the high-capacity cyclic-degradation coefficient, CD\h\(k
= 2) determined in accordance with section 3.6.6 of this appendix.
4.2.6.3 Heat pump only operates at high (k = 3) compressor capacity
at temperature Tj and its capacity is greater than or
equal to the building heating load, BL(Tj) <=
Qh\k=3\(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.112
[[Page 37117]]
where
X\k=3\(Tj) = BL(Tj)/
Qh\k=3\(Tj) and PLFj = 1 -
CD\h\(k = 3) * [1 - X\k=3\(Tj)
Determine the low temperature cut-out factor,
[delta]'(Tj), using Eq. 4.2.3-3. Use the booster-capacity
cyclic-degradation coefficient, CD\h\(k = 3) determined
in accordance with section 3.6.6 of this appendix.
4.2.6.4 Heat pump alternates between high (k = 2) and low (k = 1)
compressor capacity to satisfy the building heating load at a
temperature Tj, Qh\k=1\(Tj) <
BL(Tj) < Qh\k=2\(Tj).
Evaluate the quantities
[GRAPHIC] [TIFF OMITTED] TR08JN16.113
as specified in section 4.2.3.2 of this appendix. Determine the
equation inputs X\k=1\(Tj), X\k=2\(Tj), and
[delta]'(Tj) as specified in section 4.2.3.2 of this
appendix.
4.2.6.5 Heat pump alternates between high (k = 2) and booster (k =
3) compressor capacity to satisfy the building heating load at a
temperature Tj, Qh\k=2\(Tj) < BL
(Tj) < Qh\k=3\(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.114
where:
[GRAPHIC] [TIFF OMITTED] TR08JN16.115
and X\k=3\(Tj) = X\k=2\(Tj) = the heating
mode, booster capacity load factor for temperature bin j,
dimensionless. Determine the low temperature cut-out factor,
[delta]'(Tj), using Eq. 4.2.3-3.
4.2.6.6 Heat pump only operates at low (k = 1) capacity at
temperature Tj and its capacity is less than the building
heating load, BL(Tj) > Qh\k=1\(Tj).
[GRAPHIC] [TIFF OMITTED] TR08JN16.116
where the low temperature cut-out factor, [delta]'(Tj), is
calculated using Eq. 4.2.3-3.
4.2.6.7 Heat pump only operates at high (k = 2) capacity at
temperature Tj and its capacity is less than the building heating
load, BL(Tj) > Qh\k=2\(Tj).
Evaluate the quantities
[GRAPHIC] [TIFF OMITTED] TR08JN16.117
as specified in section 4.2.3.4 of this appendix. Calculate
[delta]''(Tj) using the equation given in section 4.2.3.4 of this
appendix.
4.2.6.8 Heat pump only operates at booster (k = 3) capacity at
temperature Tj and its capacity is less than the building heating
load, BL(Tj) > Qh\k=3\(Tj) or the
system converts to using only resistive heating.
[GRAPHIC] [TIFF OMITTED] TR08JN16.116
where [delta]''(Tj) is calculated as specified in section 4.2.3.4 of
this appendix if the heat pump is operating at its booster
compressor capacity. If the heat pump system converts to using only
resistive heating at outdoor temperature Tj, set
[delta]'(Tj) equal to zero.
4.2.7 Additional steps for calculating the HSPF of a heat pump
having a single indoor unit with multiple indoor blowers. The
calculation of the Eq. 4.2-1 quantities
eh(Tj)/N and RH(Tj)/N are evaluated
as specified in the applicable subsection.
[[Page 37118]]
4.2.7.1 For multiple indoor blower heat pumps that are connected to
a singular, single-speed outdoor unit:
a. Calculate the space heating capacity, Qhk=1(Tj), and
electrical power consumption, Ehk=1(Tj), of the heat pump when
operating at the heating minimum air volume rate and outdoor
temperature Tj using Eqs. 4.2.2-3 and 4.2.2-4,
respectively. Use these same equations to calculate the space
heating capacity, Qhk=2(Tj) and electrical power consumption,
Ehk=2(Tj), of the test unit when operating at
the heating full-load air volume rate and outdoor temperature
Tj. In evaluating Eqs. 4.2.2-3 and 4.2.2- 4, determine
the quantities Qhk=1(47) and Ehk=1(47) from the H11 test;
determine Qhk=2(47) and Ehk=2(47) from the H12 test.
Evaluate all four quantities according to section 3.7 of this
appendix. Determine the quantities Qhk=1(35) and Ehk=1(35) as
specified in section 3.6.2 of this appendix. Determine Qhk=2(35) and
Ehk=2(35) from the H22 frost accumulation test as
calculated according to section 3.9.1 of this appendix. Determine
the quantities Qhk=1(17) and Ehk=1(17) from the H31 test,
and Qhk=2(17) and Ehk=2(17) from the H32 test. Evaluate
all four quantities according to section 3.10 of this appendix.
Refer to section 3.6.2 and Table 11 of this appendix for additional
information on the referenced laboratory tests.
b. Determine the heating mode cyclic degradation coefficient,
CDh, as per sections 3.6.2 and 3.8 to 3.8.1 of this
appendix. Assign this same value to CDh(k = 2).
c. Except for using the above values of Qhk=1(Tj), Ehk=1(Tj),
Qhk=2(Tj), Ehk=2(Tj), CDh, and CDh(k = 2),
calculate the quantities eh(Tj)/N as specified
in section 4.2.3.1 of this appendix for cases where Qhk=1(Tj) >=
BL(Tj). For all other outdoor bin temperatures,
Tj, calculate eh(Tj)/N and RHh(Tj)/
N as specified in section 4.2.3.3 of this appendix if Qhk=2(Tj) >
BL(Tj) or as specified in section 4.2.3.4 of this appendix if
Qhk=2(Tj) <= BL(Tj)
4.2.7.2 For multiple indoor blower heat pumps connected to either a
single outdoor unit with a two-capacity compressor or to two
separate single-speed outdoor units of identical model, calculate
the quantities eh(Tj)/N and RH(Tj)/
N as specified in section 4.2.3 of this appendix.
4.3 Calculations of Off-Mode Power Consumption
For central air conditioners and heat pumps with a cooling
capacity of: Less than 36,000 Btu/h, determine the off mode
represented value, PW,OFF, with the following equation:
[GRAPHIC] [TIFF OMITTED] TR08JN16.119
4.4 Rounding of SEER and HSPF for Reporting Purposes
After calculating SEER according to section 4.1 of this appendix
and HSPF according to section 4.2 of this appendix round the values
off as specified per Sec. 430.23(m) of title 10 of the Code of
Federal Regulations.
[[Page 37119]]
[GRAPHIC] [TIFF OMITTED] TR08JN16.120
Table 21--Representative Cooling and Heating Load Hours for Each
Generalized Climatic Region
------------------------------------------------------------------------
Cooling Heating
load load
Climatic region hours hours
CLHR HLHR
------------------------------------------------------------------------
I................................................. 2,400 750
II................................................ 1,800 1,250
III............................................... 1,200 1,750
[[Page 37120]]
IV................................................ 800 2,250
Rating Values..................................... 1,000 2,080
V................................................. 400 2,750
VI................................................ 200 2,750
------------------------------------------------------------------------
4.5 Calculations of the SHR, which should be computed for different
equipment configurations and test conditions specified in Table 22.
Table 22--Applicable Test Conditions for Calculation of the Sensible Heat Ratio
--------------------------------------------------------------------------------------------------------------------------------------------------------
Reference
Equipment configuration table No. of SHR computation with results from Computed values
Appendix M
--------------------------------------------------------------------------------------------------------------------------------------------------------
Units Having a Single-Speed Compressor 4 B Test........................................ SHR(B)
and a Fixed-Speed Indoor blower, a
Constant Air Volume Rate Indoor blower,
or No Indoor blower.
Units Having a Single-Speed Compressor 5 B2 and B1 Tests............................... SHR(B1), SHR(B2)
That Meet the section 3.2.2.1 Indoor
Unit Requirements.
Units Having a Two-Capacity Compressor... 6 B2 and B1 Tests............................... SHR(B1), SHR(B2)
Units Having a Variable-Speed Compressor. 7 B2 and B1 Tests............................... SHR(B1), SHR(B2)
--------------------------------------------------------------------------------------------------------------------------------------------------------
The SHR is defined and calculated as follows:
[GRAPHIC] [TIFF OMITTED] TR08JN16.121
Where both the total and sensible cooling capacities are
determined from the same cooling mode test and calculated from data
collected over the same 30-minute data collection interval.
4.6 Calculations of the Energy Efficiency Ratio (EER). Calculate the
energy efficiency ratio using,
[GRAPHIC] [TIFF OMITTED] TR08JN16.122
where Qck(T) and Eck(T) are the space cooling capacity and
electrical power consumption determined from the 30-minute data
collection interval of the same steady-state wet coil cooling mode
test and calculated as specified in section 3.3 of this appendix.
Add the letter identification for each steady-state test as a
subscript (e.g., EERA2) to differentiate among the resulting EER
values.
[FR Doc. 2016-12592 Filed 6-7-16; 8:45 am]
BILLING CODE 6450-01-P