Medicare and Medicaid Programs; Fire Safety Requirements for Certain Health Care Facilities, 26871-26901 [2016-10043]
Download as PDF
Vol. 81
Wednesday,
No. 86
May 4, 2016
Part II
Department of Health and Human Services
srobinson on DSK5SPTVN1PROD with RULES2
Centers for Medicare & Medicaid Services
42 CFR Parts 403, 416, 418, et al.
Medicare and Medicaid Programs; Fire Safety Requirements for Certain
Health Care Facilities; Final Rule
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
PO 00000
Frm 00001
Fmt 4717
Sfmt 4717
E:\FR\FM\04MYR2.SGM
04MYR2
26872
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
DEPARTMENT OF HEALTH AND
HUMAN SERVICES
Centers for Medicare & Medicaid
Services
42 CFR Parts 403, 416, 418, 460, 482,
483, and 485
[CMS–3277–F]
RIN 0938–AR72
Medicare and Medicaid Programs; Fire
Safety Requirements for Certain Health
Care Facilities
Centers for Medicare &
Medicaid Services (CMS), HHS.
ACTION: Final rule.
AGENCY:
This final rule will amend the
fire safety standards for Medicare and
Medicaid participating hospitals,
critical access hospitals (CAHs), longterm care facilities, intermediate care
facilities for individuals with
intellectual disabilities (ICF–IID),
ambulatory surgery centers (ASCs),
hospices which provide inpatient
services, religious non-medical health
care institutions (RNHCIs), and
programs of all-inclusive care for the
elderly (PACE) facilities. Further, this
final rule will adopt the 2012 edition of
the Life Safety Code (LSC) and eliminate
references in our regulations to all
earlier editions of the Life Safety Code.
It will also adopt the 2012 edition of the
Health Care Facilities Code, with some
exceptions.
DATES: This regulation is effective July
5, 2016.
The incorporation by reference of
certain publications listed in the rule is
approved by the Director of the Federal
Register as of July 5, 2016.
FOR FURTHER INFORMATION CONTACT:
Kristin Shifflett, (410) 786–4133.
Danielle Shearer, (410) 786–6617.
SUPPLEMENTARY INFORMATION:
SUMMARY:
srobinson on DSK5SPTVN1PROD with RULES2
Acronyms
ABHR—Alcohol Based Hand Rubs
ADA—Americans with Disabilities Act
AHJ—Authority Having Jurisdiction
ASC—Ambulatory Surgical Center
ASHRAE—American Society of Heating,
Refrigeration, and Air Conditioning
Engineers
CAH—Critical Access Hospital
CDC—Centers for Disease Control and
Prevention
CFR—Code of Federal Regulations
CMS—Centers for Medicare & Medicaid
DOJ—Department of Justice
EES—Essential Electrical System
FR—Federal Register
FSES—Fire Safety Evaluation System
GAO—Government Accountability Office
HHS—Department of Health and Human
Services
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
HVAC—Heating, Ventilation, and Air
Conditioning
ICF–IID—Intermediate Care Facilities for
Individuals with Intellectual Disabilities
LSC—Life Safety Code
LTC—Long-term Care
NFPA—National Fire Protection Association
OPPS—Outpatient Prospective Payment
System
PACE—Programs of All-inclusive Care for the
Elderly
RFA—Regulatory Flexibility Act
RIA—Regulatory Impact Analysis
RNHCI—Religious Non-Medical Health Care
Institution
TIA—Tentative Interim Amendment
UMRA—Unfunded Mandates Reform Act
WAGD—Waste Anesthetic Gas Disposal
System
Definitions
Approved, Automatic Sprinkler
System; A fire protection system,
deemed acceptable by the Authority
Having Jurisdiction, consisting of an
integrated network of piping designed
in accordance with fire protection
engineering standards and including a
water supply, a water control valve, a
water flow alarm, a drain, and automatic
sprinklers which are fire suppression or
control devices that operate
automatically when their heat-actuated
element is heated to its thermal rating
or above, allowing water to discharge
over a specified area.
Deck: An exterior floor supported on
at least two opposing sides by an
adjacent structure and/or posts, piers, or
other independent supports.
Porch: An outside walking area
having a floor that is elevated more than
8 in. (203 mm) above grade.
Space: A portion of the health care
facility designated by the governing
body that serves a specific purpose.
Note: The word ‘‘space’’ takes its meaning
from the context in which it is used as it is
a definable area, such as a room, toilet room,
storage room, assembly room, corridor, or
lobby.
Non-Supervised Automatic Sprinkler
System: An automatic sprinkler system
lacking electrical supervisory
attachments and; therefore, unable to
provide a distinctive supervisory signal
to indicate a condition that would
impair the satisfactory operation of the
sprinkler system.
Supervised Automatic Sprinkler
System: An automatic sprinkler system
equipped with electrical supervisory
attachments, installed and monitored
for integrity in accordance with NFPA
72, National Fire Alarm and Signaling
Code, that provides a distinctive
supervisory signal to indicate a
condition that would impair the
satisfactory operation of the sprinkler
system.
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
Note: For a sprinkler system to be
considered supervised as required by NFPA
101, the supervision must be electrical as
contrasted with supervision via chaining and
locking of valves in the open position as
permitted for supervision by NFPA 13.
Supervision in accordance with NFPA 101
involves more than valve monitoring as any
condition that would impair satisfactory
operation of the sprinkler system must
provide a supervisory signal.
I. Background
A. Overview
The Life Safety Code (LSC) is a
compilation of fire safety requirements
for new and existing buildings, and is
updated and published every 3 years by
the National Fire Protection Association
(NFPA), a private, nonprofit
organization dedicated to reducing loss
of life due to fire. The LSC regulations
adopted by Centers for Medicare &
Medicaid Services (CMS) apply to
hospitals, long-term care facilities
(LTC), critical access hospitals (CAHs),
ambulatory surgical centers (ASC),
intermediate care facilities for
individuals with intellectual disabilities
(ICF–IIDs), hospice inpatient care
facilities, programs for all inclusive care
for the elderly (PACE), and religious
non-medical health care institutions
(RNHCIs). The Medicare and Medicaid
regulations have historically
incorporated these requirements by
reference, along with Secretarial waiver
authority. The statutory basis for
incorporating NFPA’s LSC into the
regulations we apply to Medicare and,
as applicable, Medicaid providers and
suppliers is the Secretary of the
Department of Health and Human
Services (the Secretary’s) authority to
stipulate health and safety regulations
for each type of Medicare and (if
applicable) Medicaid-participating
facility, as well as the Secretary’s
general rulemaking authority, set out at
sections 1102 and 1871 of the Social
Security Act (the Act).
In our regulations, issued pursuant to
the Act, we have stated that we believe
CMS has the authority to grant waivers
of some provisions of the LSC when
necessary; for instance, to hospitals
under section 1861(e)(9) of the Act, and
to LTC facilities at sections
1819(d)(2)(B) and 1919(d)(2)(B) of the
Act. Under our current regulations, the
Secretary may waive specific provisions
of the LSC for any type of facility, if
application of our rules would result in
unreasonable hardship for the facility,
and if the health and safety of its
patients would not be compromised by
such waiver.
We do not consider it always
necessary for a facility to be cited for a
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
deficiency before it can apply for or
receive a waiver. This is particularly the
case when we have evaluated specific
provisions of the LSC, determined that
a waiver would arguably apply to all
similarly-situated facilities with respect
to the LSC requirement in question, and
issued a public communication
describing the specifics of such a
categorical waiver, including any
particular requirements that must be
met in order for the waiver to apply to
a facility. Waiver approval in these
instances would be subject to a review
of documentation maintained by the
facility, verification of the applicability
of the waiver, and confirmation that the
terms and requirements of the waiver
have been implemented by the facility.
In most cases such verification occurs
when an onsite survey of the facility is
conducted. We plan to continue this
approach, but would like to clarify that
in those cases where we have issued a
prior public communication providing
for a categorical waiver, an advance
recommendation from a state survey
agency or accrediting organization (as
applicable), is not required in order for
a waiver to be granted. We have issued
categorical waivers of LSC requirements
when newer editions of the LSC
provided equally effective means of
ensuring life safety compared to
requirements of earlier LSC editions.
When CMS has evaluated the alternative
(such as examining new fire safety
research and technology), and
concluded that the specific alternative
would improve or maintain the safety of
the residents or patients of the facility,
CMS may defer to newer editions of the
LSC. CMS requires that providers
comply with any applicable non-waived
provisions of the version of the LSC
referenced in the categorical waiver.
In addition, the Secretary may accept
a state’s fire and safety code instead of
the LSC if CMS determines that the
protections of the state’s fire and safety
code are equivalent to, or more stringent
than, the protections offered by the LSC.
Further, the NFPA’s Fire Safety
Evaluation System (FSES), an
equivalency system, provides
alternatives to meeting various
provisions of the LSC, thereby achieving
the same level of fire protection as the
LSC. These flexibilities mitigate the
potential unnecessary burdens of
applying the requirements of the LSC to
all affected health care facilities.
On January 10, 2003, we published a
final rule in the Federal Register (68 FR
1374) adopting the 2000 edition of the
LSC. In that final rule, we required that
all affected providers and suppliers
meet the provisions of the 2000 edition
of the LSC, except for certain specific
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
sections. One of the exceptions to the
2000 edition of the LSC is the code’s use
of roller latches on corridor doors in
buildings that are fully protected by a
sprinkler system. We believe that roller
latches on corridor doors are a safety
hazard under all circumstances, and
prohibit their use on corridor doors in
all Medicare and applicable Medicaid
facilities. We also removed references to
all previous editions of the LSC.
In 2002, the Centers for Disease
Control and Prevention (CDC) published
on its Web site (https://www.cdc.gov/
handhygiene/Guidelines.html) an initial
set of hand hygiene guidelines for
health care settings. The guidelines
recommended the use of alcohol-based
hand rub (ABHR) dispensers. On
September 22, 2006, we published a
final rule (71 FR 55326) to allow certain
health care facilities to place ABHR
dispensers in exit corridors under
specified conditions. To accommodate
the placement of ABHR dispensers in
health care facilities, the NFPA
retroactively amended the 2000 edition
of the code. When CMS adopts an
edition of the LSC, it adopts that edition
as it existed on the day of publication
of the proposed rule. Since the changes
to the 2000 edition of the LSC occurred
after publication of the January 2003
final rule that adopted the 2000 edition
of the LSC, CMS was required to use the
notice and comment rulemaking process
to adopt the amendment that the NFPA
made to the code.
The September 2006 final rule also
required that LTC facilities, at a
minimum, install battery-powered
single station smoke alarms in resident
rooms and common areas if their
buildings were not fully sprinklered, or
if the building did not have systembased smoke detectors. A Government
Accountability Office (GAO) report
entitled ‘‘Nursing Home Fire Safety:
Recent Fires Highlight Weaknesses in
Federal Standards and Oversights’’
GAO–04–660, July 16, 2004 (https://
www.gao.gov/products/GAO-04-660)
examined two LTC facility fires
(Hartford and Nashville) in 2003, that
resulted in 31 total resident deaths. The
report examined Federal fire safety
standards and enforcement procedures,
as well as results from the fire
investigations of these two incidents. It
specifically cited requiring smoke
detectors in these facilities as one way
to strengthen the requirements. We
agreed with the GAO findings and
added this smoke alarm requirement in
response to the GAO report.
On August 13, 2008, we published a
final rule (73 FR 47075) to require all
LTC facilities to install automatic
sprinkler systems throughout their
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
26873
buildings in accordance with the
technical provisions of the 1999 edition
of NFPA 13, Standard for the
Installation of Sprinkler Systems, and to
test, inspect, and maintain sprinkler
systems in accordance with the
technical requirements of the 1998
edition of NFPA 25, Standard for the
Inspection, Testing and Maintenance of
Water-Based Fire Protection Systems.
The August 2008 final rule required all
LTC facilities to be equipped with
sprinkler systems by August 13, 2013.
This rule was also in response to the
July 2004 GAO report on nursing home
fire safety. In addition to its findings
related to smoke alarms, the GAO
recommended that fire safety standards
for unsprinklered LTC facilities be
strengthened and stated that sprinklers
were the single most effective fire
protection feature for LTC facilities.
On May 12, 2014 CMS also published
a final rule, ‘‘Part II Regulatory
Provisions to Promote Program
Efficiency, Transparency, and Burden
Reduction’’ (79 FR 27106) that allows
CMS to grant very limited extensions of
the due date for a facility that is
building a replacement facility or
undergoing major modifications to
unsprinklered living areas.
On October 24, 2011, we published a
proposed rule (76 FR 65891), to reform
hospital and critical access hospital
conditions of participation. Many of the
public comments received during the
comment period strongly encouraged
CMS to adopt the 2012 edition of the
LSC. The commenters stated that the
2012 edition of the LSC would clarify
several issues and would be beneficial
to facilities.
On April 16, 2014, we published a
proposed rule (79 FR 21552), ‘‘Fire
Safety Requirements for Certain Health
Care Facilities’’ that would amend the
fire safety standards. We proposed the
adoption of the 2012 edition of the
NFPA LSC and the elimination of
references to earlier editions of the LSC.
CMS must emphasize that the LSC is
not an accessibility code, and
compliance with the LSC does not
ensure compliance with the
requirements of the Americans with
Disabilities Act (ADA). State and local
government programs and services,
including health care facilities, are
required to comply with Title II of the
ADA. Private entities that operate public
accommodations such as nursing
homes, hospitals, and social service
center establishments are required to
comply with Title III of the ADA. The
same accessibility standards apply
regardless of whether health care
facilities are covered under Title II or
E:\FR\FM\04MYR2.SGM
04MYR2
26874
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Title III of the ADA.1 For more
information about the ADA’s
requirements, see the Department of
Justice’s Web site at https://www.ada.gov
or call 1–800–514–0301 (voice) or 1–
800–514–0383 (TTY).
B. 2012 Edition of the Life Safety Code
srobinson on DSK5SPTVN1PROD with RULES2
The 2012 edition of the LSC includes
new provisions that we believe are vital
to the health and safety of all patients
and staff. Our intention is to ensure that
patients and staff continue to experience
the highest degree of fire safety possible.
The term ‘‘Patient(s)’’ will be globally
used throughout this document, and
refers to patient, clients, residents and
all other terms used to describe the type
of individuals cared for in each provider
type.
The use of earlier editions of the code
can become problematic due to
advances in safety and technology, and
changes made to each edition of the
code. Newer buildings are typically
built to comply with the newer versions
of the LSC because state and local
jurisdictions, as well as non-CMSapproved accreditation programs, often
adopt and enforce newer versions of the
code as they become available.
Therefore, a health care facility that is
constructed or renovated in 2015 would
likely be required by its state and local
authorities to comply with a more
recent edition of the LSC, while also
being required to comply with the 2000
edition of the LSC in order to meet the
Medicare and applicable Medicaid
regulatory requirements. Requiring
compliance with two different editions
of the LSC at the same time can create
unnecessary conflicts, duplications, and
inconsistencies that increase
construction and compliance costs
without any fire safety or patient care
benefits. For example, the 2000 edition
of the LSC limits ABHRs to gel form,
whereas the 2012 edition of the LSC
expands to allow aerosol and gel
ABHRs. Limiting the choice of ABHRs
creates barriers to improved hand
hygiene, which has been shown to
reduce the number of health care
associated infections. We believe that
adopting the 2012 LSC would simplify
1 Facilities newly constructed or altered after
March 15, 2012 must comply with the 2010
Standards for Accessible Design (2010 Standards).
Facilities newly constructed or altered between
September 15, 2010 and March 15, 2012 had the
option of complying with either the 1991 Standards
for Accessible Design (1991 Standards) or the 2010
Standards. Facilities newly constructed between
January 26, 1993 and September 15, 2010, or altered
between January 26, 1992 and September 15, 2010
were required to comply with the 1991 Standards
under Title III and either the 1991 Standards or the
Uniform Federal Accessibility Standards under
Title II.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
and modernize the construction and
renovation process for affected health
care providers and suppliers, reduce
compliance-related burdens, and allow
for more resources to be used for patient
care.
The 2012 edition of the LSC contains
a new chapter,—‘‘Building
Rehabilitation.’’ This new chapter
allows for the application of the
requirements for new construction
versus the requirements for existing
construction to vary based on the type
and extent of rehabilitation work being
done to a given building. This chapter
sets out different types of building
rehabilitation work (that is, repair,
renovation, modification,
reconstruction, change of use, change of
occupancy and addition) to which
different standards apply.
Buildings that have not received, all
pre-construction governmental
approvals before the rule’s effective
date, or those buildings that begin
construction after the effective date of
this regulation, will be required to meet
the New Occupancy chapters of the
2012 edition of the LSC. Buildings
constructed before the effective date of
this regulation will be required to meet
the Existing Occupancy chapters of the
2012 edition of the LSC. Any changes
made to buildings will be required to
comply with Chapter 43—Building
Rehabilitation, which depending on the
changes being made, could require
compliance with the new or existing
occupancy chapters. In any instances
where mandatory LSC references do not
include existing chapters, such as
Chapter 43—Building Rehabilitation,
existing occupancies must ensure
buildings and equipment are in
compliance with provisions previously
adopted by CMS at the time they were
constructed or installed.
C. Incorporation by Reference
In this final rule we are incorporating
by reference the NFPA 101® 2012
edition of the LSC, issued August 11,
2011, and all Tentative Interim
Amendments issued prior to April 16,
2014; and the NFPA 99®2012 edition of
the Health Care Facilities Code, issued
August 11, 2011, and all Tentative
Interim Amendments issued prior to
April 16, 2014.
(1) NFPA 101, Life Safety Code, 2012
edition, issued August 11, 2011;
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
(2) NFPA 99, Standards for Health
Care Facilities Code of the National Fire
Protection Association 99, 2012 edition,
issued August 11, 2011.
(i) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(ii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(iii) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(iv) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(v) TIA 12–6 to NFPA 99, issued
March 3, 2014.
The materials that are incorporated by
reference are reasonably available to
interested parties and can be inspected
at the CMS Information Resource
Center, 7500 Security Boulevard,
Baltimore, MD. Copies may be obtained
from the National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000. If any changes in this
edition of the Code are incorporated by
reference, CMS will publish a document
in the Federal Register to announce the
changes.
The NFPA 101®2012 edition of the
LSC (including the TIAs) provides
minimum requirements, with due
regard to function, for the design,
operation and maintenance of buildings
and structures for safety to life from fire.
Its provisions also aid life safety in
similar emergencies.
The NFPA 99® 2012 edition of the
Health Care Facilities Code (including
the TIAs) provides minimum
requirements for health care facilities
for the installation, inspection, testing,
maintenance, performance, and safe
practices for facilities, material,
equipment, and appliances, including
other hazards associated with the
primary hazards.
Health Care Occupancies
The following are key provisions that
appear in the 2012 edition of the LSC
for Chapter 18, ‘‘New Health Care
Occupancies,’’ and Chapter 19,
‘‘Existing Health Care Occupancies.’’
We have provided the LSC citation and
a description of the 2012 requirement at
the beginning of each section discussed.
The 2012 edition of the LSC classifies
a ‘‘Health Care Occupancy’’ as a facility
having 4 or more patients on an
inpatient basis. We proposed that the
LSC exception for health care
occupancy facilities with fewer than
four occupants/patients would be
inapplicable to the Medicare and
Medicaid facilities; all health care
occupancies that provide care to one or
more patients would be required to
comply with the relevant requirements
of the 2012 edition of the LSC.
E:\FR\FM\04MYR2.SGM
04MYR2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Sections 18.2.3.4(2) and 19.2.3.4(2)—
Corridor Projections
This provision requires
noncontinuous projections to be no
more than 6 inches from the corridor
wall. In addition to following the
requirements of the LSC, health care
facilities must comply with the
requirements of the ADA, including the
requirements for protruding objects. The
2010 Standards for Accessible Design
(2010 Standards) generally limit the
protrusion of wall-mounted objects into
corridors to no more than 4 inches from
the wall when the object’s leading edge
is located more than 27 inches, but not
more than 80 inches, above the floor.
See Sections 204.1 and 307 of the 2010
Standards, available at https://
www.ada.gov/regs2010/
2010ADAStandards/
Guidance2010ADAstandards.htm 2
(‘‘2010 Standards’’). This requirement
protects persons who are blind or have
low vision from being injured by
bumping into a protruding object that
they cannot detect with a cane.
Although the LSC allows 6-inch
projections, under the ADA, objects
mounted above 27 inches and no more
than 80 inches high can only protrude
a maximum of 4 inches into the corridor
beyond a detectable surface mounted
less than 27 inches above the floor
(except for certain handrails which may
protrude up to 41⁄2″). See section 307 of
the 2010 standards for requirements for
handrails and post-mounted objects.
CMS intends to provide technical
assistance regarding strategies for how
to avoid noncompliance with the ADA’s
protruding objects requirement, as well
as how to modify non-compliant
protruding objects.
srobinson on DSK5SPTVN1PROD with RULES2
Sections 18.7.5.7.2 and 19.7.5.7.2—
Recycling
This new provision requires that
containers used solely for recycling
clean waste be limited to a maximum
capacity of 96 gallons. If the recycling
containers are located in a protected
hazardous area, container size will not
be limited.
Sections 18.3.6.3.9.1 and 19.3.6.3.5—
Roller Latches
A roller latch is a type of door
latching mechanism to keep a door
closed. The 2012 edition of the LSC
requires corridor doors to be provided
with a means for keeping the door
2 Regardless of which set of ADA Standards for
Acessible Design applied at the time a facility was
built or altered, the requirements for wall-mounted
protruding objects are essentially the same. See
Section 4.4 of the 1991 Standards, available at
https://www.ada.gov/1991standards/1991standardsarchive.html.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
closed that is acceptable to the authority
having jurisdiction. The LSC permits
roller latches capable of keeping the
door fully closed if a force of 5 pounds
is applied at the latch edge or roller
latches in fully sprinklered buildings.
However, we proposed not to adopt
these standards from the 2012 LSC.
Through fire investigations, roller
latches have proven to be an unreliable
door latching mechanism requiring
extensive maintenance to operate
properly. Many roller latches in fire
situations failed to provide adequate
protection to residents in their rooms
during an emergency. Roller latches will
be prohibited in existing and new
Health Care Occupancies for corridor
doors and doors to rooms containing
flammable or combustible materials.
These doors will be required to have
positive latching devices instead.
Sections 18.4.2 and 19.4.2—Sprinklers
in High-Rise Buildings
This provision requires buildings over
75′ (generally greater than 7 or 8 stories)
in height to have automatic sprinkler
systems installed throughout the
building. The 2012 LSC allows 12 years
from when the authority having
jurisdiction (which in this case is CMS)
officially adopts the 2012 edition of the
LSC for existing facilities to comply
with the sprinkler system installation
requirement. Therefore, those facilities
that are not already required to do so
will have 12 years following publication
of this final rule, which adopts the 2012
LSC, to install sprinklers in high-rise
buildings.
Sections 18.2.2.2.5.2 and 19.2.2.2.5.2—
Door Locking
Where the needs of patients require
specialized protective measures for their
safety, door-locking arrangements are
permitted by this section. For example,
locked psychiatric facilities are
designed such that the entire facility is
secure and obstructs patients and others
from improperly entering and exiting.
This provision allows interior doors to
be locked, subject to the following
requirements: (1) All staff must have
keys; (2) smoke detection systems must
be in place; (3) the facility must be fully
sprinklered; (4) the locks are electrical
locks that will release upon loss of
power to the device; and (5) the locks
release by independent activation of the
smoke detection system and the water
flow in the automatic sprinkler system.
Sections 18.3.2.6 and 19.3.2.6—Alcohol
Based Hand Rubs (ABHRs)
This provision explicitly allows
aerosol dispensers, in addition to gel
hand rub dispensers. The aerosol
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
26875
dispensers are subject to limitations on
size, quantity, and location, just as gel
dispensers are limited. Automatic
dispensers are also now permitted in
health care facilities, provided that the
following requirements are met: (1)
They do not release contents unless they
are activated; (2) the activation occurs
only when an object is within 4 inches
of the sensing device; (3) any object
placed in the activation zone and left in
place must not cause more than one
activation; (4) the dispenser must not
dispense more than the amount required
for hand hygiene consistent with the
label instructions; (5) the dispenser is
designed, constructed and operated in a
way to minimize accidental or
malicious dispensing; and (6) all
dispensers are tested in accordance with
the manufacturer’s care and use
instructions each time a new refill is
installed. The provision further defines
prior language regarding ‘‘above or
adjacent to an ignition source’’ as being
‘‘within 1 inch’’ of the ignition source.
Sections 18.3.5 and 19.3.5—
Extinguishment Requirements
This provision is related to sprinkler
system requirements and requires the
evacuation of a building or the
instituting of an approved fire watch
when a sprinkler system is out of
service for more than 10 hours in a 24hour period until the system has been
returned to service. We proposed not to
adopt this requirement. In its place, we
proposed that a health care occupancy
must evacuate a building or institute an
approved fire watch when a sprinkler
system is out of service for more than
4 hours. Based on comments received
from the industry, we are withdrawing
our proposal and adopting the
requirement as specified by NFPA for an
evacuation of a building or the
instituting of an approved fire watch
when a sprinkler system is out of
service for more than 10 hours in a 24hour period until the system has been
returned to service.
Section 18.3.2.3 and 19.3.2.3—
Anesthetizing Locations
This provision requires that
anesthetizing locations be protected in
accordance with the 2012 edition of
NFPA 99, Health Care Facilities Code.
Separate from the requirements of the
NFPA 99, we proposed that dedicated
supply and exhaust systems for
windowless anesthetizing locations
must be arranged to automatically vent
smoke and products of combustion to
prevent the circulation of smoke
originating from within and outside the
operating rooms.
E:\FR\FM\04MYR2.SGM
04MYR2
26876
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Sections 18.2.3.4 and 19.2.3.4—
Corridors
This provision allows for wheeled
equipment that is in use, medical
emergency equipment not in use, and
patient lift and transportation
equipment be permitted to be kept in
the corridors for more timely patient
care. This provision also allows
facilities to place fixed furniture in the
corridors, although the placement of
furniture or equipment must not
obstruct accessible routes required by
the ADA. See section 403.5 of the 2010
Standards.
Sections 18.3.2.5.3 and 19.3.2.5.3—
Cooking Facilities
Cooking facilities are allowed in a
smoke compartment where food is
prepared for 30 individuals or fewer (by
bed count). The cooking facility is
permitted to be open to the corridor,
provided that the following conditions
are met:
• The area being served is limited to
30 beds or less.
• The area is separated from other
portions of the facility by a smoke
barrier.
• The range hood and stovetop meet
certain standards—
++ A switch must be located in the
area that is used to deactivate the cook
top or range whenever the kitchen is not
under staff supervision.
++ The switch also has a timer, not
exceeding 120-minute capacity that
automatically shuts off after time runs
out.
• Two smoke detectors must be
located no closer than 20 feet and not
further than 25 feet from the cooktop or
range.
srobinson on DSK5SPTVN1PROD with RULES2
Sections 18.7.5.1 and 19.7.5.1—
Furnishings & Decorations
This provision allows combustible
decor in any health care occupancy as
´
long as the decor is flame-retardant or
treated with approved fire-retardant
coating that is listed and labeled, and
meet fire test standards. Additionally,
decor may not exceed—(1) 20 percent of
the wall, ceiling and doors, in any room
that is not protected by an approved
automatic sprinkler system; (2) 30
percent of the wall, ceiling and doors,
in any room (no maximum capacity)
that is not protected by an approved,
supervised automatic sprinkler system;
and (3) 50 percent of the wall, ceiling
and doors, in any room with a capacity
of 4 people (the actual number of
occupants in the room may be less than
its capacity) that is not protected by an
approved, supervised automatic
sprinkler system.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
Sections 18.5.2.3 and 19.5.2.3—
Fireplaces
This provision allows direct-vent gas
fireplaces in smoke compartments
without the 1 hour fire wall rating.
Fireplaces must not be located inside of
any patient sleeping room. Solid fuelburning fireplaces are permitted and can
be used only in areas other than patient
sleeping rooms, and must be separated
from sleeping rooms by construction of
no less than a 1 hour fire resistance wall
rating.
Outside Window or Door Requirements
Separate from the requirements of the
LSC, we proposed that every health care
occupancy patient sleeping room must
have an outside window or outside door
with an allowable sill height not to
exceed 36 inches above the floor with
certain exceptions, as follows:
• Newborn nurseries and rooms
intended for occupancy for less than 24
hours have no sill height requirements.
• Windows in atrium walls shall be
considered outside windows for the
purposes of this requirement.
• The window sill height in special
nursing care areas shall not exceed 60
inches above the floor.
Ambulatory Health Care Occupancies
The following are key provisions in
the 2012 edition of the LSC from
Chapter 20, ‘‘New Ambulatory Health
Care Occupancies’’ and Chapter 21,
‘‘Existing Ambulatory Health Care
Occupancies.’’ We have provided the
LSC citation and a description of the
requirement at the beginning of each
section discussed.
The 2012 edition of the LSC defines
an ‘‘Ambulatory Health Care
Occupancy’’ as a facility capable of
treating 4 or more patients
simultaneously on an outpatient basis.
CMS regulations at 42 CFR 416.44
require that all ASCs meet the
provisions applicable to Ambulatory
Health Care Occupancy, regardless of
the number of patients served. We
believe that hospital outpatient surgical
departments are comparable to ASCs
and thus should also be required to
meet the provisions applicable to
Ambulatory Health Care Occupancy
Chapters, regardless of the number of
patients served.
Sections 20.3.2.1 and 21.3.2.1—Doors
This provision requires all doors to
hazardous areas be self-closing or close
automatically.
Sections 20.3.2.6 and 21.3.2.6—ABHRs
This provision explicitly allows
aerosol dispensers, in addition to gel
hand rub dispensers. The aerosol
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
dispensers are subject to limitations on
size, quantity, and location, just as gel
dispensers are limited. Automatic
dispensers are also now permitted in
ambulatory care facilities, provided,
among other things, that—(1) they do
not release contents unless they are
activated; (2) the activation occurs only
when an object is within 4 inches of the
sensing device; (3) any object placed in
the activation zone and left in place
must not cause more than one
activation; (4) the dispenser must not
dispense more than the amount required
for hand hygiene consistent with the
label instructions; (5) the dispenser is
designed, constructed and operated in a
way to minimize accidental or
malicious dispensing; (6) all dispensers
are tested in accordance with the
manufacturer’s care and use instructions
each time a new refill is installed. The
provision further defines prior language
regarding ‘‘above or adjacent to an
ignition source’’ as being ‘‘within 1
inch’’ of the ignition source.
Sections 20.3.5 and 21.3.5—
Extinguishment Requirements
This provision is related to sprinkler
system requirements and requires the
evacuation of a building or the
instituting of an approved fire watch
when a sprinkler system is out of
service for more than 10 hours in a 24hour period until the system has been
returned to service. We proposed to
replace this requirement with a separate
requirement for evacuation or a fire
watch when a sprinkler system is out of
service for more than 4 hours. Based on
comments received from the industry,
we are withdrawing our proposal and
adopting the requirement as specified
by NFPA for an evacuation of a building
or the instituting of an approved fire
watch when a sprinkler system is out of
service for more than 10 hours in a 24hour period until the system has been
returned to service.
Section 20.3.2.3 and 21.3.2.3—
Anesthetizing Locations
This provision requires that
anesthetizing locations be protected in
accordance with the 2012 edition of
NFPA 99, Health Care Facilities Code.
The 2012 edition of NFPA 99 does not
require a smoke control ventilation
system in anesthetizing locations. We
proposed a requirement, separate from
the LSC and NFPA 99, to require air
supply and exhaust systems for
windowless anesthetizing locations that
is arranged to automatically vent smoke
and products of combustion to prevent
the circulation of smoke originating
from within and outside the operating
room.
E:\FR\FM\04MYR2.SGM
04MYR2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Residential Board and Care Occupancies
Both the 2000 and 2012 editions of
the LSC classify ‘‘board and care’’ as a
facility ‘‘used for lodging or boarding of
4 or more patients not related to the
owners or operators by blood or
marriage, for the purpose of providing
personal care services.’’ We proposed
that the LSC requirements would apply
to a facility regardless of the number of
patients served. We note that the only
CMS-regulated facilities that would be
subject to these provisions would be
intermediate care facilities for
individuals with intellectual disabilities
(ICF–IIDs), which are regulated under
42 CFR part 483, subpart I.
The following are key provisions that
appear in the 2012 edition of the LSC
for Chapter 32, ‘‘New Residential Board
and Care Occupancies’’ and Chapter 33,
‘‘Existing Residential Board and Care
Occupancies.’’ We are providing the
LSC citation and a description of the
requirement at the beginning of each
section discussed.
Section 32.2.3.5.3.2—Sprinklers
This revised provision has been
expanded to require that sprinkler
systems be installed in all habitable
areas, closets, roofed porches, balconies
and decks of new occupancies.
srobinson on DSK5SPTVN1PROD with RULES2
Sections 32.2.3.5.7 and 33.2.3.5.7—
Attics
This new provision requires attics of
new and existing facilities to be
sprinklered. For both new and existing
board and care facilities, if the attic is
used for living purposes, storage, or
housing of fuel fired equipment, it must
be protected with an automatic
approved sprinkler system. If the attic is
used for other purposes or is not used,
then it must meet one of the following
requirements: (1) Have a heat detection
system that activates the building fire
alarm system; (2) have automatic
sprinklers; (3) be of noncombustible or
limited-combustible construction; or (4)
be constructed of fire-retardant-treatedwood.
Section 32.3.3.4.7—Smoke Alarms
This provision will only affect newly
constructed facilities. Approved smoke
alarms are required to be installed
inside every sleeping room, outside
every sleeping area, in the immediate
vicinity of the bedrooms, and on all
levels within a resident unit.
Section 33.3.3.2.3—Hazardous Areas
This provision is for existing facilities
with impractical evacuation
capabilities. All hazardous areas must
be separated from other parts of the
building by smoke partitions.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
Waiver Authority
We proposed to retain our existing
authority to waive provisions of the LSC
under certain circumstances, further
reducing the exposure to additional cost
and burden for facilities with unique
situations. A waiver may be granted for
a specific LSC requirement if we
determine that—(1) the waiver would
not adversely affect patient/staff health
and safety; and (2) it would impose an
unreasonable hardship on the facility to
meet a specific LSC requirement. In
cases where a provider or supplier has
been cited for a LSC deficiency, the
provider or supplier may request a
waiver recommendation from its State
Survey Agency or Accrediting
Organization (AO) with a CMSapproved Medicare and applicable
Medicaid accreditation program. The
State Survey Agency or AO reviews the
request and makes a recommendation to
the appropriate CMS Regional Office.
The CMS Regional Office will review
the waiver request and the
recommendation and make a final
decision. CMS will not grant a waiver if
patient health and safety is
compromised.
The LSC recognizes alternative
systems, methods, or devices approved
as equivalent by the authority having
jurisdiction (AHJ) as being in
compliance with the LSC. CMS, as the
AHJ for certification, will determine
equivalency through the waiver
approval process.
State Fire Codes
In addition to the proposed waiver
option, a state may request that its state
fire safety requirements, imposed by
state law, be used in lieu of the 2012
edition of the LSC. The state must
submit the request to the appropriate
CMS Regional Office, and the Regional
Office will forward the request to CMS
central office for final determination.3
Fire Safety Evaluation System (FSES)
We retain our authority to apply the
Fire Safety Evaluation System (FSES)
option within the LSC as an alternative
approach to meeting the requirements of
the LSC. This includes the
determination of how the FSES will be
applied to each occupancy and which
edition of the FSES is most appropriate
to use.
3 CMS reminds such states that compliance with
state fire safety requirements, like compliance with
the LSC, does not ensure compliance with the ADA
requirements.
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
26877
D. 2012 Edition of the Health Care
Facilities Code
The 2012 edition of the NFPA 99,
‘‘Health Care Facilities Code,’’ addresses
requirements for both health care
occupancies and ambulatory care
occupancies, and serves as a resource
for those who are responsible for
protecting health care facilities from fire
and associated hazards. The purpose of
this Code is to provide minimum
requirements for the installation,
inspection, testing, maintenance,
performance, and safe practices for
health care facility materials, equipment
and appliances. This Code is a
compilation of documents that have
been developed over a 40-year period by
NFPA, and is intended to be used by
those persons involved in the design,
construction, inspection, and operation
of health care facilities, and in the
design, manufacture, and testing of
appliances and equipment used in
patient care areas of health care
facilities. It provides information on
subjects, for example, medical gas and
vacuum systems, electrical systems,
electrical equipment, and gas
equipment. The NFPA 99 applies
specific requirements in accordance
with the results of a risk-based
assessment methodology. A risk-based
approach allows for the application of
requirements based upon the types of
treatment and services being provided
to patients or residents rather than the
type of facility in which they are being
performed. In order to ensure the
minimum level of protection afforded
by NFPA 99 is applicable to all patient
and resident care areas within a health
care facility, CMS proposed the
adoption of the 2012 edition of NFPA
99, with the exception of chapters 7—
Information Technology and
Communications Systems for Health
Care Facilities; 8—Plumbing; 12—
Emergency Management; and 13—
Security Management. In the following
section, we describe the key provisions
within the NFPA 99.
The first three chapters of the NFPA
99 address the administration of the
NFPA 99, the referenced publications
and definitions.
Chapter 4—Fundamentals
Chapter 4 provides guidance on how
to apply NFPA 99 requirements to
health care facilities based upon
‘‘categories’’ determined when using a
risk-based methodology.
There are four categories utilized in
the risk assessment methodology,
depending on the types of treatment and
services being provided to patients or
residents. Section 4.1.1 of NFPA 99
E:\FR\FM\04MYR2.SGM
04MYR2
26878
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
describes Category 1 as, ‘‘Facility
systems in which failure of such
equipment or system is likely to cause
major injury or death of patients or
caregivers. . . .’’ Section A.4.1.1
provides examples of what a major
injury could include, such as
amputation or a burn to the eye. Section
4.1.2 describes Category 2 as, ‘‘Facility
systems in which failure of such
equipment is likely to cause minor
injury to patients or caregivers. . . .’’
Section A.4.1.2 describes a minor injury
as one that is not serious or involving
risk of life. Section 4.1.3 describes
Category 3 as, ‘‘Facility systems in
which failure of such equipment is not
likely to cause injury to patients or
caregivers, but can cause patient
discomfort. . . .’’ Section 4.1.4
describes Category 4 as, ‘‘Facility
systems in which failure of such
equipment would have no impact on
patient care. . . .’’
Section 4.2 requires that each facility
that is a health care or ambulatory
occupancy define its risk assessment
methodology, implement the
methodology, and document the results.
CMS does not require the submission of
risk assessment methods to CMS.
However, CMS, will confirm that
facilities are using risk assessment
methodologies when conducting onsite
surveys. We did not propose to require
the use of any particular risk assessment
procedure. However, if future situations
indicate the need to define a particular
risk assessment procedure, we would
pursue that through a separate notice
and comment rulemaking.
srobinson on DSK5SPTVN1PROD with RULES2
Chapter 5—Gas and Vacuum Systems
The hazards addressed in Chapter 5
include the ability of oxygen and
nitrous oxide to exacerbate fires, safety
concerns from the storage and use of
pressurized gas, and the reliance upon
medical gas and vacuum systems for
patient care. Chapter 5 does not
mandate the installation of any systems;
rather, if they are installed or are
required to be installed, the systems will
be required to comply with NFPA 99.
Chapter 5 covers the performance,
maintenance, installation, and testing of
the following:
• Nonflammable medical gas systems
with operating pressure below a gauge
pressure of 300 psi;
• Vacuum systems in health care
facilities;
• Waste anesthetic gas disposal
systems (WAGD); and
• Manufactured assemblies that are
intended for connection to the medical
gas, vacuum, or WAGD systems.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
Chapter 6—Electrical Systems
The hazards addressed in Chapter 6
are related to the electrical power
distribution systems in health care
facilities, and address issues such as
electrical shock, power continuity, fire,
electrocution, and explosions that might
be caused by faults in the electrical
system.
Chapter 6 covers the performance,
maintenance, and testing of the
electrical systems in health care
facilities.
Chapter 9—Heating, Ventilation, and
Air Conditioning (HVAC)
Chapter 9 requires HVAC systems
serving spaces- a portion of the health
care facility designated by the governing
body that serves a specific purpose or
providing health care functions to be in
accordance with the American Society
of Heating, Refrigeration and AirConditioning Engineers (ASHRAE)
Standard 170- Ventilation of Health
Care Facilities (2008 edition) (https://
www.ashrae.org).
Chapter 9 does not apply to existing
HVAC systems, but applies to the
construction of new health care
facilities, and the altered, renovated, or
modernized portions of existing systems
or individual components. Chapter 9
ensures minimum levels of heating,
ventilation, and air conditioning
performance in patient and resident care
areas. Some of the issues discussed in
Chapter 9 are:
• HVAC system energy conservation.
• Commissioning.
• Piping.
• Ductwork.
• Acoustics.
• Requirements for the ventilation of
medical gas storage and trans-filling
areas.
• Waste anesthetic gases.
• Plumes from medical procedures.
• Emergency power system rooms.
• Ventilation during construction.
Chapter 10—Electrical Equipment
Chapter 10 covers the performance,
maintenance, and testing of electrical
equipment in health care facilities.
Much of this chapter applies to
requirements for portable electrical
equipment in health care facilities, but
there are also requirements for fixedequipment and information on
administrative issues.
Chapter 11—Gas Equipment
The hazards addressed in Chapter 11
relate to general fire, explosions, and
mechanical issues associated with gas
equipment, including compressed gas
cylinders.
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
Chapter 14—Hyperbaric Facilities
Chapter 14 addresses the hazards
associated with hyperbaric facilities in
health care facilities, including
electrical, explosive, implosive, and fire
hazards. Chapter 14 sets forth minimum
safeguards for the protection of patients
and personnel administering hyperbaric
therapy and procedures. Chapter 14
contains requirements for hyperbaric
chamber manufacturers, hyperbaric
facility designers, and personnel
operating hyperbaric facilities. It also
contains requirements related to
construction of the hyperbaric chamber
itself and the equipment used for
supporting the hyperbaric chamber, as
well as administration and
maintenance. Many requirements in this
chapter are applicable only to new
construction and new facilities.
Chapter 15—Features of Fire Protection
Chapter 15 covers the performance,
maintenance, and testing of fire
protection equipment in health care
facilities. Issues addressed in this
chapter range from the use of flammable
liquids in an operating room to special
sprinkler protection. These fire
protection requirements are
independent of the risk-based approach,
as they are applicable to all patient care
areas in both new and existing facilities.
Chapter 15 has several sections taken
directly from the NFPA 101, including
requirements for the following:
• Construction and
compartmentalization of health care
facilities.
• Laboratories.
• Utilities.
• Heating, ventilation and air
conditioning systems.
• Elevators.
• Escalators.
• Conveyors.
• Rubbish Chutes.
• Incinerators.
• Laundry Chutes.
• Fire detection, alarm and
communication systems.
• Automatic sprinklers and other
extinguishing equipment.
• Compact storage including mobile
storage and maintenance.
• Testing of water based fire
protection systems.
These sections have requirements for
inspection, testing and maintenance
which apply to all facilities, as well as
specific requirements for existing
systems and equipment that also apply
to all facilities.
II. Provisions of the Proposed
Regulations
This section details the specific
regulatory changes for each affected
E:\FR\FM\04MYR2.SGM
04MYR2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
provider and supplier. Due to the
similar content and structure of the
regulations for the various providers
and suppliers, most of the information
presented repeats for each provider.
srobinson on DSK5SPTVN1PROD with RULES2
1. Religious Nonmedical Health Care
Institutions: Condition of Participation:
Life Safety From Fire (§ 403.744)
In § 403.744, we proposed to maintain
most of the current provisions for
Religious Nonmedical Health Care
Institutions (RNHCI) published in the
Federal Register on January 10, 2003
(68 FR 1374), except if they conflicted
with the 2012 LSC and the requirements
were within the provisions detailed in
Section I of this preamble regardless of
the number of patients the facility
served.
In addition, we proposed to—
• Retain the requirements at
§ 403.744(a)(1)(ii) related to the
prohibition of roller latches in health
care facilities. We also proposed to
update the LSC chapter reference from
‘‘19.3.6.3.2 exception number 2’’ to
‘‘19.3.6.3.5 numbers 1 and 2 and
19.3.6.3.6 number 2’’.
• Modify the requirements specific to
ABHRs, since most of the requirements
in our regulation are now included in
the 2012 edition of the LSC. Therefore,
we proposed to remove the
requirements at § 403.744(a)(4)(i), (ii),
(iv) and (v).
• Retain the requirements at
§ 403.744(a)(4)(iii) related to protection
against inappropriate access, and
redesignate it at § 403.744(a)(4).
• Add a new requirement at
§ 403.744(a)(5) that required facilities
with sprinkler systems that were out of
service for more than 4 hours in a 24hour period to evacuate the building or
portion of the building affected by the
system outage, or establish a fire watch
until the system is back in service,
notwithstanding the lower standard of
the LSC.
• Add a new requirement at
§ 403.744(a)(6) to require window sills
must not exceed 36 inches above the
floor.
• Retain the requirement at
§ 403.744(b) related to the Secretary’s
waiver authority and state imposed
codes. We did not propose to make any
changes to this section.
• Remove the requirements at
§ 403.744(c) related to the phase-in
period for compliance with emergency
lighting. In the 2003 final rule, we
allowed facilities until March 13, 2006,
to upgrade their emergency lighting
equipment. This phase-in period has
now expired and is no longer a
necessary regulatory provision.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
• Add a new Condition of
Participation at § 403.745 requiring
RNHCIs to comply with the 2012
edition of the NFPA 99.
• Chapters 7, 8, 12, and 13 of the
NFPA 99 would not apply to RNHCIs.
• Allow for waivers of these
provisions under the same conditions
and procedures that we currently use for
waivers of applicable provisions of the
LSC.
2. Ambulatory Surgery Centers:
Condition for Coverage: Environment
(§ 416.44)
In § 416.44, we proposed that all
ASCs meet the provisions applicable to
Ambulatory Health Care Centers in the
2012 edition of the LSC, except as
detailed in section I of this preamble,
regardless of the number of patients the
facility serves. We also proposed to
retain the provision at § 416.44(b)(2) and
(b)(3) related to the Secretary’s waiver
authority and state imposed codes. We
did not propose to make any changes to
these provisions.
In addition, we proposed to—
• Remove the requirements at
§ 416.44(b)(4) related to the phase-in
period for compliance with emergency
lighting. This phase-in period has now
expired and this phase-in provision is
no longer a necessary regulatory
provision.
• Modify the requirements specific to
ABHRs since most of the requirements
are now included in the 2012 edition of
the LSC. Specifically, we proposed to
remove the requirements at
§ 416.44(b)(5)(i), (ii), (iv), (A) through
(G), and (v).
• Retain the requirements at
§ 416.44(b)(5)(iii) related to protection
against inappropriate access and
redesignate it at § 416.44(b)(4).
• Add a new requirement at
§ 416.44(b)(5) to require a facility with
a sprinkler system that is out of service
for more than 4 hours in a 24-hour
period to evacuate the building or
portion of the building affected by the
system outage, or establish a fire watch
until the system is back in service,
notwithstanding the lower standard of
the 2012 LSC.
• Add a new requirement at
§ 416.44(b)(6) to require facilities with
windowless anesthetizing locations to
have an air supply and exhaust system
that automatically vents smoke and
products of combustion, prevents
recirculation of smoke originating
within the operating room, and prevents
the circulation of smoke entering the
system intake.
• Add a new paragraph at § 416.44(c)
requiring ASCs to comply with the 2012
edition of the NFPA 99.
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
26879
• Chapters 7, 8, 12, and 13 of the
NFPA 99 would not apply to ASCs.
• Allow for waivers of these
provisions under the same conditions
and procedures that we currently use for
waivers of applicable provisions of the
LSC.
3. Hospice Care: Condition of
Participation: Hospices That Provides
Inpatient Care Directly (§ 418.110)
In § 418.110, we proposed that all
inpatient hospice facilities meet the
provisions applicable to health care
occupancies in the 2012 edition of the
LSC, with the exceptions discussed in
section I of this preamble, regardless of
the number of patients they serve. We
note that this is not a change in
requirements, but merely a clarification
that, for LSC purposes, an inpatient
hospice facility is considered a health
care occupancy. The LSC does not apply
to hospice care that is provided in a
patient’s home.
In addition, we proposed to—
• Retain the requirements at
§ 418.110(d)(1)(ii) related to the
prohibition of roller latches in health
care facilities. We proposed to update
the LSC chapter reference from
‘‘19.3.6.3.2 exception number 2’’ to
‘‘19.3.6.3.5 numbers 1 and 2 and
19.3.6.3.6 number 2.’’
• Retain the provision at
§ 418.110(d)(2) and (3) related to the
Secretary’s waiver authority and state
imposed codes. We did not propose any
changes to these provisions.
• Modify the requirements specific to
ABHRs because most of the
requirements are now included in the
2012 edition of the LSC. We proposed
to remove the requirements at
§ 418.110(d)(4)(i), (ii) and (iv). We
proposed to retain the requirements at
§ 418.110(d)(4)(iii) related to protection
against inappropriate access and
redesignate this requirement at
§ 418.110(d)(4).
• Add a new requirement at
§ 418.110(d)(5) to require a facility with
a sprinkler system that is out of service
for more than 4 hours in a 24-hour
period to evacuate the building or
portion of the building affected by the
system outage, or establish a fire watch
until the system is back in service,
notwithstanding the lower standard of
the 2012 LSC.
• Add a new requirement at
§ 418.110(d)(6) to require that window
sills must not exceed 36 inches.
• Add a new paragraph at
§ 418.110(e) requiring hospices to
comply with the 2012 edition of the
NFPA 99.
• Chapters 7, 8, 12, and 13 of the
NFPA 99 not would apply to hospices.
E:\FR\FM\04MYR2.SGM
04MYR2
26880
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
srobinson on DSK5SPTVN1PROD with RULES2
• Allow for waivers of these
provisions under the same conditions
and procedures that we currently use for
waivers of applicable provisions of the
LSC.
4. Programs of All-Inclusive Care for the
Elderly (PACE): Condition of
Participation: Physical Environment
(§ 460.72)
In § 460.72, we proposed to retain
most of the provisions of the existing
final regulation for Programs of AllInclusive Care for the Elderly (PACE)
published in the Federal Register on
January 10, 2003 (68 FR 1374),
regardless of the number of patients the
PACE facility serves. PACE providers
will continue to be required to meet LSC
specifications for the type of facilities in
which the programs are located (that is,
hospitals and office buildings).
In addition, we proposed to—
• Retain the requirements at
§ 460.72(b)(1)(ii) related to the
prohibition of roller latches in health
care facilities. We proposed to update
the LSC chapter reference from
‘‘19.3.6.3.2 exception number 2’’ to
‘‘19.3.6.3.5 numbers 1 and 2 and
19.3.6.3.6 number 2.’’
• Retain the provision at
§ 460.72(b)(2)(i) and (ii) related to the
Secretary’s waiver authority and state
imposed codes. We did not propose to
make any changes to these provisions.
• Remove the requirement at
§ 460.72(b)(3) related to the phase-in
period for compliance with emergency
lighting. This phase-in period has now
expired and is no longer a necessary
regulatory provision.
• Remove the requirements at
§ 460.72(b)(4) related to the phase-in
period for the prohibition of roller
latches in health care facilities. This
phase-in period has now ended and is
no longer a necessary regulatory
provision.
• Modify the requirements specific to
ABHRs because most of the
requirements are now located in the
2012 edition of the LSC. We proposed
to remove the requirements at
§ 460.72(b)(5)(i), (ii), (iv) and (v). We
proposed to retain the requirements at
§ 460.72(b)(5)(iii) related to protection
against inappropriate access, and
redesignate it to § 460.72(b)(3). We
proposed to add a new requirement at
§ 460.72(b)(4) to require a facility with
a sprinkler system that is out of service
for more than 4 hours in a 24-hour
period to evacuate the building or
portion of the building affected by the
system outage, or establish a fire watch
until the system is back in service,
notwithstanding the lower standard of
the 2012 LSC.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
• Add a new paragraph at § 460.72(d)
to require PACE centers to comply with
the 2012 edition of the NFPA 99.
• Chapters 7, 8, 12, and 13 of the
NFPA 99 would not apply to PACEs.
• Allow for waivers of these
provisions under the same conditions
and procedures that we currently use for
waivers of applicable provisions of the
LSC.
5. Hospitals: Condition of Participation:
Physical Environment (§ 482.41)
In § 482.41, we proposed that the
hospitals meet the health care
occupancy provisions of the 2012
edition of the LSC, regardless of the
number of patients the hospital serves.
There can be multiple occupancy
classifications within a single hospital.
Therefore, multiple chapters of the code
may be applied to a single hospital in
accordance with the Multiple
Occupancies provisions in 18.1.3 and
19.1.3. We also proposed that hospital
outpatient surgical departments are
comparable to ASCs and thus should be
required to meet the provisions
applicable to Ambulatory Health Care
Occupancy chapters, regardless of the
number of patients served.
In addition, we proposed to—
• Retain most of the provisions from
the existing final regulation for hospitals
published in the Federal Register on
January 10, 2003 (68 FR 1374).
• Retain the requirements at
§ 482.41(b)(1)(ii) related to the
prohibition of roller latches in health
care facilities. We proposed to update
the LSC chapter reference from
‘‘19.3.6.3.2 exception number 2’’ to
‘‘19.3.6.3.5 numbers 1 and 2 and
19.3.6.3.6 number 2.’’
• Retain the provision at
§ 482.41(b)(2) and (3) related to the
Secretary’s waiver authority and state
imposed codes. We did not propose to
make any changes to these provisions.
• Remove the requirements at
§ 482.41(b)(4) related to the phase-in
period for compliance with emergency
lighting. This phase-in period has now
ended, and is no longer a necessary
regulatory provision.
• Remove the requirements at
§ 482.41(b)(5) related to the phase-in
period of the prohibition on roller
latches in health care facilities. This
phase-in period has now expired and is
no longer a necessary regulatory
provision.
• Retain the requirements at
§ 482.41(b)(6) through (b)(8), and
redesignate them at § 482.41(b)(4)
through (b)(6), without changes.
• Modify the requirements specific to
ABHRs since most of the requirements
are now located in the 2012 edition of
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
the LSC. We proposed to remove the
requirements at § 482.41(b)(9)(i), (ii), (iv)
and (v). We proposed to retain the
requirement at § 482.41(b)(9)(iii) related
to protection against inappropriate
access and redesignate it at
§ 482.41(b)(7).
• Add a new requirement at
§ 482.41(b)(8) to require a facility with
a sprinkler system that is out of service
for more than 4 hours in a 24-hour
period to evacuate the building or
portion of the building affected by the
system outage, or establish a fire watch
until the system is back in service,
notwithstanding the lower standard of
the 2012 LSC.
• Add a new requirement at
§ 482.41(b)(9) that to require facilities
with windowless anesthetizing
locations to have an air supply and
exhaust system that automatically vents
smoke and products of combustion,
prevents recirculation of smoke
originating within the surgical suite,
and prevents the circulation of smoke
entering the system intake.
• Add a new requirement at
§ 482.41(b)(10) to require a minimum 36
inch window sill, with certain
exceptions for newborn nurseries,
rooms intended for occupancy for less
than 24 hours, and special nursing care
areas.
• Add a new paragraph at § 482.41(c)
requiring hospitals to comply with the
2012 edition of the NFPA 99.
• Chapters 7, 8, 12, and 13 of the
NFPA 99 would not apply to hospitals.
• Allow for waivers of these
provisions under the same conditions
and procedures that we currently use for
waivers of applicable provisions of the
LSC.
6. Long-Term Care Facilities: Condition
of Participation: Physical Environment
(§ 483.70)
In § 483.70, we proposed to retain
most of the provisions of the existing
final regulation for LTC facilities
published in the Federal Register on
January 10, 2003 (68 FR 1374) regardless
of the number of residents the facility
serves.
In addition, we proposed to—
• Retain the requirements at
§ 483.70(a)(1)(ii) related to the
prohibition of roller latches in health
care facilities. We proposed to update
the LSC chapter reference from
‘‘19.3.6.3.2 exception number 2’’ to
‘‘19.3.6.3.5 numbers 1 and 2 and
19.3.6.3.6 number 2.’’
• Retain the provision at
§ 483.70(a)(2) and (3) related to the
Secretary’s waiver authority and state
imposed codes. We did not propose to
make any changes to these provisions.
E:\FR\FM\04MYR2.SGM
04MYR2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
srobinson on DSK5SPTVN1PROD with RULES2
• Remove the requirements at
§ 483.70(a)(4) related to the phase-in
period for compliance with emergency
lighting. This phase-in period has now
expired and is no longer a necessary
regulatory provision.
• Remove the requirements at
§ 483.70(a)(5) related to the phase-in
period for the prohibition of roller
latches in health care facilities. This
phase-in period has now ended and is
no longer a necessary regulatory
provision.
• Modify the requirements specific to
ABHRs since most of the requirements
are now included in the 2012 edition of
the LSC. Specifically, we proposed to
remove the requirements at
§ 483.70(a)(6)(i), (ii), (iv) and (v). We
proposed to retain the requirement at
§ 483.70(a)(6)(iii) related to protection
against inappropriate access, and
redesignate it at § 483.70(a)(4).
• Retain the requirements at
§ 483.70(a)(7)(i), (ii), (iii), (A) and (B)
related to installation, inspection,
testing and maintenance of battery
operated single station smoke alarms,
without changes. We proposed to
redesignate these requirements at
§ 483.70(a)(5) (i), (ii), (iii) (A) and (B).
• Retain the requirements at
§ 483.70(a)(8)(i) and (ii) related to the
installation of supervised automatic
sprinklers and the testing, inspection
and maintenance of the sprinkler
system. We proposed to redesignate
these requirements as § 483.70(a)(6)(i)
and (ii), without changes.
• Add a new requirement at
§ 483.70(a)(7) to require a minimum 36
inch window sill.
• Add a new paragraph at § 483.70(b)
to require LTC facilities to comply with
the 2012 edition of the NFPA 99.
• Chapters 7, 8, 12, and 13 of the
NFPA 99 would not apply to LTC
facilities.
• Allow for waivers of these
provisions under the same conditions
and procedures that we currently use for
waivers of applicable provisions of the
LSC.
7. Intermediate Care Facilities for
Individuals With Intellectual
Disabilities: Condition of Participation:
Physical Environment (§ 483.470)
In § 483.470, we proposed to retain
most of the provisions of the existing
regulation for ICFs/IID. In accordance
with the regulatory requirements at
§ 483.470 (j)(2), ICFs/IID will continue
to be permitted to meet either the
Residential Board and Care Occupancies
chapter or the Health Care Occupancy
chapter of the LSC, as appropriate, in
accordance with the determination of
the State survey agency, regardless of
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
the number of patients the facility
serves.
In addition, we proposed to—
• Not adopt the provisions at
Chapters 32.3.2.11.2 and 33.3.2.11.2,
related to ‘‘lockups.’’ Lock-ups, as
described in the LSC, are not
appropriate under any circumstances for
board and care facilities.
• Retain the requirements at
§ 483.470(j)(1)(ii) related to the
prohibition of roller latches in health
care facilities. We proposed to update
the LSC chapter reference from
‘‘19.3.6.3.2 exception number 2’’ to
‘‘19.3.6.3.5 numbers 1 and 2 and
19.3.6.3.6 number 2.’’
• Retain the requirements at
§ 483.470(j)(2), (3), and (4).
• Remove the requirements at
§ 483.470(j)(5) related to the phase-in
period for compliance with emergency
lighting. This phase-in period has
expired and is no longer a necessary
regulatory provision.
• Remove § 483.470(j)(6) related to
the phase-in period for the prohibition
of roller latches in health care facilities.
This phase-in period has now ended
and is no longer a necessary regulatory
provision.
• Retain the provision at
§ 483.470(j)(7)(A) and (B) related to the
Secretary’s waiver authority and state
imposed codes. We proposed to
redesignate these provisions at
§ 483.470(j)(5)(A) and (B) without
change.
• Modify the requirements specific to
ABHRs since most of the requirements
are now included in the 2012 edition of
the LSC. Specifically, we proposed to
remove the requirements at
§ 483.470(j)(7)(ii)(A), (B), (D) and (E).
We proposed to retain the requirements
at § 483.470(j)(7)(ii)(C) related to
protection against inappropriate access,
and redesignate it at § 483.470(j)(5)(ii).
• Add a new requirement at
§ 483.470(j)(5)(iii) to require a facility
with a sprinkler system that is out of
service for more than 4 hours in a 24hour period to evacuate the building or
portion of the building affected by the
system outage, or establish a fire watch
until the system is back in service,
notwithstanding the lower standard of
the 2012 LSC.
• Add a new paragraph at
§ 483.470(j)(5)(iv) to require ICF–IIDs to
comply with the 2012 edition of the
NFPA 99.
• Chapters 7, 8, 12, and 13 of the
NFPA 99 would not apply to ICF–IIDs.
• Allow for waivers of these
provisions under the same conditions
and procedures that we currently use for
waivers of applicable provisions of the
LSC.
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
26881
8. Critical Access Hospitals: Condition
of Participation: Physical Plant and
Environment (§ 485.623)
In § 485.623, we proposed to retain
most of the provisions of the existing
final regulation for Critical Access
Hospitals (CAHs) published in the
Federal Register on January 10, 2003
(68 FR 1374), regardless of the number
of patients the facility serves.
In addition, we proposed to—
• Retain the requirements at
§ 485.623(d)(1)(ii) related to the
prohibition of roller latches in health
care facilities. We proposed to update
the LSC chapter reference from
‘‘19.3.6.3.2 exception number 2’’ to
‘‘19.3.6.3.5 numbers 1 and 2 and
19.3.6.3.6 number 2.’’
• Retain the requirements at
§ 485.623(d)(2) through (d)(4), without
any changes.
• Remove the requirement at
§ 485.623(d)(5) related to the phase-in
period for compliance with emergency
lighting. This phase-in period has now
expired and is no longer a necessary
regulatory provision.
• Remove the requirement at
§ 485.623(d)(6) related to the phase-in
period of the prohibition on roller
latches in health care facilities. This
phase-in period has also expired and is
no longer a necessary regulatory
provision.
• Modify the requirements specific to
ABHRs since most of the requirements
are now incorporated in the 2012
edition of the LSC. Specifically, we
proposed to remove the requirements at
§ 485.623(d)(7)(i), (ii), (iv) and (v). We
proposed to retain the requirement at
§ 485.623(d)(7)(iii) related to protection
against inappropriate access and
redesignate it at § 485.623(d)(5).
• Add a new requirement at
§ 485.623(d)(6) to require a facility with
a sprinkler system that is out of service
for more than 4 hours in a 24-hour
period to evacuate the building or
portion of the building affected by the
system outage, or establish a fire watch
until the system is back in service,
notwithstanding the lower standard of
the 2012 LSC.
• Add a new requirement at
§ 485.623(d)(7) to require facilities with
windowless anesthetizing locations to
have an air supply and exhaust system
that automatically vents smoke and
products of combustion, prevents
recirculation of smoke originating
within the surgical suite, and prevents
the circulation of smoke entering the
system intake.
• Add a new requirement at
§ 485.623(d)(8) to require a minimum 36
inch window sill, with the exception of
E:\FR\FM\04MYR2.SGM
04MYR2
26882
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
newborn nurseries, rooms intended for
occupancy for less than 24 hours, and
special nursing care areas. Windows in
atrium walls are considered outside
windows for the purposes of this
provision.
• Add a new paragraph at
§ 485.623(e) requiring CAHs to comply
with the 2012 edition of the NFPA 99.
• Chapters 7, 8, 12, and 13 of the
NFPA 99 would not apply to CAHs.
• Allow for waivers of these
provisions under the same conditions
and procedures that we currently use for
waivers of applicable provisions of the
LSC.
srobinson on DSK5SPTVN1PROD with RULES2
III. Analysis of and Responses to Public
Comments
We received over 362 public
comments concerning the LSC proposed
rule, ‘‘Fire Safety Requirements for
Certain Health Care Facilities’’ (79 FR
21552), which this rule is finalizing.
The majority of the comments were
from medical societies, hospital
associations, hospitals, medical centers,
LTC facilities, and advocate groups for
different provider types. The remaining
comments were from individual
physicians, nurses, facility engineers,
and private citizens. A summary of the
major issues and our responses follow:
LSC—Health Care Occupancies
We note that only the following CMSregulated facilities would be subject to
these comments, unless otherwise
specified: Hospitals, CAHs, LTC
facilities, hospices, RNHCIs, and PACE
facilities.
Comment: One commenter
recommended adding language to the
LTC requirements at § 483.70, similar to
other provider sections, about
establishing a firewatch or evacuating a
building when a sprinkler system is out
of service for more than 4 hours in a 24
hour period. The commenter stated that
adding this requirement to the LTC
regulations would provide protection
for the residents of nursing homes when
the sprinkler system is out of service.
Response: We thank the commenter
for their comment. We agree that
requiring additional safety measures
when a sprinkler system is out of
service for a significant amount of time
is important in the LTC facility
environment. We originally intended to
include this regulatory requirement in
the proposed rule; however, it was
inadvertently left out of regulations text.
We would like to clarify that we have
removed the 4 hour requirement and are
now following the LSC requirement of
implementing a fire watch or building
evacuation if the sprinkler system is out
for more than 10 hours in a 24-hour
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
period. We have made the appropriate
correction in this final rule, and have
included the appropriate language in
the regulation text at § 483.70(a)(8).
Comment: One commenter stated that
the proposed rule does not address
whether a hospital that is not fully
sprinklered and provides swing beds
needs to meet the more stringent
requirements from S & C–13–55–LSC
that applies to hospitals.
Response: The survey and
certification memorandum that the
commenter references is related to the
requirements for the installation and
maintenance of automatic sprinkler
systems in LTC facilities. Swing beds
are not considered to be LTC facilities.
Rather, swing beds are part of a hospital
or CAH and must meet the LSC
provisions applicable to those facilitytypes. Therefore, swing beds are only
required to meet certain specified
regulations for LTC facilities, not
including the LTC facility sprinkler
system requirements.
Comment: CMS solicited public
comment to determine if a phase-in
period of 12 years is enough time for
facilities to install fully compliant
sprinkler systems in high-rise buildings,
and asked whether other provider types
are, or may be, located in a high-rise
building. We received very few
responses to this solicitation. The
majority of the commenters who
responded stated that 12 years was
enough time to fully sprinkler a highrise healthcare facility, and some
commenters stated that 12 years was
more than enough time. We did not
receive any comments stating that this
was not enough time to install sprinkler
systems in high-rise buildings.
Commenters also stated that ambulatory
care and residential board and care
occupancies may also be located within
high-rise hospital buildings.
Response: We agree with commenters
that 12 years is an appropriate phase-in
period, and we are finalizing this
proposal with a phase-in period of 12
years from the publication date of this
rule. We thank the commenters for the
input on other occupancy types that
could be located in high-rise buildings.
Since these occupancy types are located
in hospital buildings, we have already
accounted for them in our total number
of high-rise hospital buildings.
Comment: One commenter asked
whether an alternative care setting used
to provide services to PACE participants
would be required to meet the ABHR
requirements and the sprinkler system
outage requirement.
Response: All PACE center facilities
are required to meet the requirements
found at 42 CFR 460.72, ‘‘Physical
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
Environment’’. This includes meeting
all the requirements for the specific
occupancy type they fall under within
the LSC. This requirement also applies
to the type of setting in which a center
is located, which would include
alternative care settings.
Comment: Some commenters have
expressed concern regarding cooking
facilities that are open to the corridor.
One commenter did not support cooking
facilities being open to the corridor and
believes that it could increase the
number of fires in these facilities due to
misuse. Other commenters supported
having cooking facilities that are open to
the corridor and believed it would
promote person-centered care and make
for a more home-like atmosphere. A few
commenters suggested changes to this
requirement, including—
• Requiring that an operational
exhaust hood for the cooking facility
should not contribute to nor create an
egress corridor return air plenum (an air
pressure differential between different
parts of a building);
• Requiring that the activate/
deactivate switch be hidden from view;
• Requiring that staff must be present
when a range hood or stovetop is in use;
and
• Requiring that cooking facilities be
screened off when not in use to prevent
resident access.
Response: We appreciate the
suggestions concerning cooking
facilities in LTC facilities; however we
feel that the LSC includes many
requirements to make sure that cooking
facilities are safe. All facilities are
ultimately responsible for assuring the
safety of all residents at all times, and
they may choose to implement
additional safety precautions, such as
those described above, to further assure
safety. Since other fire safety standards
prohibit the use of a corridor as a
plenum in the facility ventilation
system, the introduction of a cooking
exhaust fan would need to be accounted
for in the design and not create a
corridor plenum situation.
Comment: One commenter suggested
that, in addition to installing sprinklers
in existing high-rise health care
occupancies, we should also require
existing non high-rise health care
occupancies to install sprinkler systems
throughout their buildings.
Response: While we encourage all
facilities to install sprinklers, there is
not enough evidence for CMS to support
requiring all facilities to be retrofitted
for sprinklers. In the event that the
NFPA should incorporate a requirement
for universal sprinklers into a future
edition of the LSC, we would strongly
consider adopting such a change.
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Comment: Some commenters stated
that medical equipment should not be
permanently fixed in the corridors. This
could present a safety issue during a fire
or evacuation and also makes the
corridor smaller in size.
Response: We follow the LSC
requirement for medical equipment in
the corridors, which allows any
equipment that is in use, including
medical emergency equipment and
patient lift and transportation
equipment to be permitted to be kept in
the corridors for more timely patient
care. Facilities may place fixed furniture
in the corridors, although the placement
of furniture or equipment must not
obstruct accessible routes required by
the ADA. The potential risks of this
change are low because the LSC has
shifted to a ‘‘defend in place’’ approach
that does not rely upon evacuation as
the primary means of fire safety.
Comment: One commenter suggested
that CMS only permit decorations in
rooms that have sprinklers in them.
Furthermore, the commenter stated that,
with such sprinkler protection, there
would not be a need to mandate a
maximum percentage of space that
could be covered by decorations.
Response: The NFPA, through its
committee of experts and consensus
process, determined that decorations
may not exceed—(1) 20 percent of the
wall, ceiling and doors, in any room that
is not protected by an approved
automatic sprinkler system; (2) 30
percent of the wall, ceiling and doors,
in any room that is not protected by an
approved, supervised automatic
sprinkler system; and (3) 50 percent of
the wall, ceiling and doors, in any room
with a capacity of 4 people (the actual
number of occupants in the room may
be less than its capacity) that is not
protected by an approved, supervised
automatic sprinkler system. We believe
that it is appropriate to adopt these
consensus standards. We also note that
the health care occupancy type that is
most likely to have a significant amount
´
of room decor is a LTC facility, given
that patients reside in such facilities for
longer periods of time, and that all LTC
facilities are required to have sprinklers
installed throughout their buildings.
Comment: One commenter
recommended that two smoke detectors
be located no closer than 20 feet and not
further than 25 feet from a fireplace.
Response: There are currently no
requirements for smoke detectors within
a certain distance of a fireplace. If a
facility wants to add additional smoke
detectors closer to fireplaces they are
free to do so. An electrically supervised
(connected to the facility fire alarm
panel) carbon monoxide detector is
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
required in the room containing the
fireplace to increase the level of safety
for the residents or patients in the
facility. We believe that the current
requirements for sprinklers and smoke
detectors are sufficient to assure
resident safety, particularly because
fireplaces are only in open areas and not
permitted in resident rooms. The health
care occupancy type that is most likely
to have a fireplace is a LTC facility,
because there are more options for the
location of fireplaces in LTC facilities,
making the facilities feel more homelike. All LTC facilities should be fully
sprinklered, with smoke detectors in
designated areas of the facilities, such as
corridors and resident sleeping areas.
LSC—ASC
We note that the only CMS-regulated
facilities that would be subject to these
comments would be ambulatory surgical
centers, which are regulated under 42
CFR part 416.
Comment: One commenter believes
that we should allow grandfathering for
ASCs that meet previous editions of the
LSC. The commenter states that trying
to modify an existing facility to meet
provisions in the 2012 edition of the
LSC would have significant cost
implications for existing ASCs, and may
cause ASCs to close.
Response: For existing ASCs, most
provisions in the 2012 edition of the
LSC are similar to past editions.
Furthermore, existing facilities in
compliance with previous editions of
the LSC are not required to upgrade to
a later edition of the LSC for certain
provisions, unless there is a building
renovation, which could require
compliance with new occupancy
chapters. In addition, an ASC may also
request a waiver for a specific provision
of the LSC, further reducing the
exposure to additional costs and burden
for ASCs with unique situations that can
justify the application of waivers and
will not endanger the health and safety
of patients. A waiver may be granted for
a specific LSC requirement if we
determine: (1) The waiver would not
adversely affect patient and staff health
and safety; and (2) it would impose an
unreasonable hardship on the facility to
meet a specific LSC requirement.
Comment: One commenter suggested
an increase to Medicare reimbursements
to freestanding ASCs, stating that the
current reimbursement model is not
sufficient.
Response: We thank the commenter
for this comment; however,
reimbursement rates are beyond the
scope of this rule. We recommend
submitting such comments separately to
CMS or commenting on the next
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
26883
Outpatient Prospective Payment
System/Ambulatory Surgical Centers
(OPPS/ASC) proposed rule.
LSC—Board & Care
We note that the only CMS-regulated
facilities that would be subject to these
comments would be intermediate care
facilities for individuals with
intellectual disabilities (ICF–IIDs),
which are regulated under 42 CFR part
483, subpart I.
Comment: One commenter expressed
concern about a process that permits
board and care occupancies to assess
their own evacuation capacity. The
commenter notes that facilities have
strong incentive to overestimate their
evacuation capability in order to avoid
more stringent requirements. The
commenter believes that this provision
would undermine CMS’ efforts to
improve safety.
Response: CMS looks at the
assessment of evacuation capabilities as
part of the survey process to verify the
accuracy of the self-evaluation. CMS
requires surveyors to independently
determine the evacuation difficulty
score at each survey and use the
determined evacuation difficulty score
to perform the survey.
Comment: CMS solicited comments
regarding whether or not CMS should
require existing facilities to install
smoke alarms in accordance with
section 9.6.2.10, which would require
the addition of smoke alarms inside
sleeping rooms, outside every sleeping
area, in the immediate vicinity of the
bedrooms, and on all levels within the
resident units. The commenters who
responded to this solicitation
unanimously agreed that CMS should
not require existing residential board
and care facilities to install smoke
alarms inside sleeping rooms, outside
every sleeping area, in the immediate
vicinity of the bedrooms, and on all
levels within the resident units. All of
the commenters believed that it would
be an undue burden, and suggested that,
in order for them to meet this
requirement, a payment rate adjustment
would be in order.
Response: We agree that a regulation
to require smoke alarms is not necessary
at this time, as there is not enough
evidence for us to make it a requirement
to upgrade existing facilities. We
strongly encourage existing residential
board and care facilities to install smoke
alarms inside sleeping rooms, outside
every sleeping area, in the immediate
vicinity of the bedrooms, and on all
levels within the resident units to
provide an additional level of safety.
With regards to any payment rate
adjustment, we remind commenters that
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
26884
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
payment rates are not within the scope
of this rule, but recommend submitting
comments on such issues separately to
CMS.
Comment: The LSC requires newly
constructed residential board and care
occupancies to install sprinklers in
habitable areas, closets, roofed porches,
balconies and decks. In the proposed
rule, CMS recommended that existing
facilities also install sprinklers in the
same areas. Commenters stated that
CMS should continue to recommend,
but not require, sprinklers for existing
residential board and care. The
commenters also stated that if CMS
were to require the installation of
sprinklers in those areas that they
would need to have at least a 5 year
phase-in period, and that a payment rate
adjustment would be in order for
affected facilities.
Response: We thank the commenters
for their comments regarding this topic.
We would like to clarify that sprinklers
are only required for new residential
board and care construction and
existing facilities rated as impractical
evacuation capability. The facility itself
determines their evacuation capability,
and must ensure that the appropriate
safety protections are in place to protect
the patients and staff within the
building, if they are determined to have
an impractical evacuation capabilities.
CMS regulations require the use of
NFPA 101A, Guide on Alternative
Approaches to Life Safety, 2010 Edition,
Chapter 6, Evacuation Capability
Determination for Board and Care
Occupancies to determine the
evacuation difficulty index. CMS
continues to recommend that existing
facilities install sprinklers in habitable
areas, closets, roofed porches, balconies
and decks as an additional safety
precaution. Decks being an exterior floor
supported on at least two opposing
sides by an adjacent structure and/or
posts, piers, or other independent
supports and, porches being an outside
walking area having a floor that is
elevated more than 8 in. (203 mm)
above grade. With regards to any
payment rate adjustment, we remind
commenters that payment rates are not
within the scope of this rule, but
recommend submitting such comments
separately to CMS.
Comment: A few commenters
expressed concern with having to install
sprinklers in attics used for living
purposes, storage, or housing of fuelfired equipment. Commenters also
expressed concern with having to install
either a heat detection system that
activates the building fire alarm, or
having automatic sprinklers, or
constructing attics of noncombustible or
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
limited-combustible construction or
constructing attics of fire-retardanttreated-wood if the attic is used for
other purposes. The commenters stated
that compliance with this provision
would be expensive and possibly
warrant a payment rate adjustment. The
commenters requested a minimum 5year phase-in period to install new
protection systems in attics.
Response: A 5-year phase-in period is,
we believe, significantly more time than
is actually needed to meet this
requirement. According to the
information gathered by CMS from the
installation of sprinklers in LTC
facilities requirement, which was
required to be in compliance by August
13, 2013, most LTC facilities were able
to install sprinklers throughout their
entire buildings in 5 years. Attics have
much less square footage than an entire
building. We believe that 3 years from
the effective date of this rule would be
an ample amount of time to come into
compliance with this requirement,
therefore, we are finalizing a 3-year
phase-in period. With regards to any
payment rate adjustment, we remind
commenters that payment rates are not
within the scope of this rule, but
recommend submitting such comments
separately to CMS.
Comment: One commenter requested
additional explanation regarding our
proposed exclusion of the lock-up
provisions contained within the board
and care occupancy chapters of the LSC.
The commenter proposed an alternative
to this exclusion, which would allow
lock-ups while requiring a specific
staffing ratio requirement.
Response: Lock-ups are incidental use
areas where occupants are restrained
and such occupants are mostly
incapable of self-preservation because of
security measures not under the
occupants’ control. Lock-ups are
prohibited in Medicare and Medicaid
participating ICF–IID facilities. The
health and safety regulations for ICF–
IIDs at 42 CFR 483.450 effectively
prohibit the use of lock-up spaces as
described in the LSC; therefore, there
should be no lock-up space in the
building.
LSC—General
Comment: Some commenters
questioned whether Tentative Interim
Amendments (TIAs) that have been
written with regards to the NFPA 101
and NFPA 99 apply, since some of them
were published after CMS published the
proposed rule.
Response: Because the TIAs are
considered a component of the LSC, the
following TIAs issued prior to the
publication of the proposed rule on
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
April 16, 2014, will apply to all
facilities. We have also included
language in the final regulations text to
this effect. The following TIAs will
apply:
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(vi) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(vii) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(viii) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(ix) TIA 12–6 to NFPA 99, issued
March 3, 2014.
Comment: Some commenters agree
with the continued prohibition of roller
latches in facilities, as they are a safety
concern. However, some commenters
stated that some doors are not required
to latch (that is, toilet rooms, bathrooms)
and that roller latches should be
allowed on those particular doors with
no penalty. A few commenters also
discussed the importance of roller
latches in psychiatric units. Those
commenters stated that roller latches
have limited uses on psychiatric units to
address patients barricading themselves
in their rooms or using hanging points
(on the levers) for potential suicides.
Response: CMS would like to clarify
that roller latches are prohibited on all
corridor doors. However, doors to toilet
rooms, bathrooms, shower rooms, sink
closets, and similar auxiliary spaces that
do not contain flammable or
combustible materials would be allowed
to have roller latches. We do not believe
that permitting the use of roller latches
in auxiliary spaces presents a danger to
patients or staff. Therefore, we have
revised the proposed regulatory
requirement throughout this rule to
clarify this distinction. We note that this
requirement is different than the 2012
LSC requirement for door latching.
Comment: A few commenters
expressed concern with Chapter 43,
‘‘Renovation’’, of the NFPA 101. The
commenters suggested that the date of
submission of construction plans to the
State for plan review should be the
‘‘trigger’’ to apply chapter 43. They also
stated that facilities have no control
over when plans are actually reviewed;
for example, a building may be designed
under the current 2000 NFPA 101 code,
but may not be approved until after the
final publication of this rule, which
means they would have to meet the
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
2012 NFPA 101 code. Commenters also
asked CMS to define ‘‘constructed’’ in
reference to determining whether a
building is consider new or existing.
Response: Buildings that have not yet
received all pre-construction
governmental approvals required by the
jurisdictions in which the building is to
be built before the rule’s effective date,
or those buildings that begin
construction after the effective date of
this regulation, would be required to
meet the New Occupancy chapters of
the 2012 edition of the LSC. While we
share the commenter’s concern
regarding plans that may be under
review for a lengthy period of time, we
do not believe that it is in the best
interest of patient and staff safety to
permit constructing of a building that
does not meet the codes that are
effective as of the day that construction
begins.
Comment: One commenter suggested
that hospitals and ASCs should be
required to test their emergency
generators when they are disconnected
from the normal utility.
Response: Facilities are required to
test their load emergency power systems
on a monthly basis, per the
requirements of section 8.4.1, 2010
edition of NFPA 110, Standard for
Emergency and Standby Power Systems.
Comment: Some commenters
suggested that CMS should provide
training for surveyors and providers
regarding the new codes, updated
guidance, and forms. One commenter
suggested that CMS not only provide
training for State fire authorities, but
also for architects, engineers, and
building officials.
Response: CMS agrees that training is
very important, and does provide
training for state surveyors who work
with CMS to enforce these regulations.
However, we do not provide training for
any provider/supplier type for any
health and safety rules, including those
related to the LSC. We encourage
providers/suppliers, architects,
engineers or building officials to contact
the NFPA and their relevant industry
associations to identify their specific
training needs and appropriate offerings
that may address those needs with
regards to the LSC.
Comment: Many commenters support
the adoption of the 2012 NFPA 101 LSC.
However, the majority of those
commenters also stated that CMS
should adopt the 2012 NFPA 101 in its
entirety, without any changes to the
provisions.
Response: Through our surveys,
comments, and experience, we have
determined that for the health and
safety of patients and staff we could not
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
adopt the LSC in its entirety. We believe
that the provisions that we have not
adopted are not appropriate for
Medicare and Medicaid providers and
suppliers. For example, we continue to
prohibit roller latches on corridor doors
because, in our view, they present a
safety hazard. Also, we are not adopting
the provision regarding lock-ups
because lock-ups are prohibited in the
ICF–IIDs regulations, separate from the
LSC. This practice is permitted under
the National Technology Transfer and
Advancement Act (https://www.gpo.gov/
fdsys/pkg/PLAW-104publ113/pdf/
PLAW-104publ113.pdf), which does not
mandate that we use an entire code
without exceptions if we determine it is
impractical or unnecessary to do so.
Comment: Several commenters
requested CMS to revise the rule to
allow health care facilities to choose
other codes that are nationally
recognized, such as the International
Building Code and International Fire
Code. The commenters asserted that
referencing only the NFPA’s LSC creates
conflict for many jurisdictions that
enforce other equivalent or more
stringent fire and life safety
requirements. The commenters further
stated that, by not referencing other
applicable codes, CMS favors one code
to the detriment of other codes.
Response: We continue to specifically
cite the LSC because under sections
1819(d)(2)(B) and 1919(d)(2)(B) of the
Act, nursing homes must meet the
provisions of ‘‘such edition (as specified
by the Secretary in regulation) of the
LSC of the National Fire Protection
Association . . . . ’’ To avoid confusion,
and to be consistent for all provider
types, we require the LSC for all
facilities. This is especially applicable
for facilities with mixed occupancies.
For example, a health care facility’s
west wing could be a nursing home
while the rest of the facility is a
hospital. It would be impractical as well
as burdensome for the facility to follow
the LSC for the nursing home and
another health and safety code for the
hospital. The regulation reflects this by
requiring a single code for all health
care facilities. The NFPA and the IBC
organizations try to align their
respective requirements as much as
possible and the 2012 LSC is a reflection
of that effort. We also note that
jurisdictions are permitted to enforce
more stringent requirements on top of
those required by the Federal LSC
requirements.
Comment: Some commenters
requested CMS to adopt updated
versions of the LSC more quickly in the
future. One commenter requested that
CMS should adopt any updated version
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
26885
of the LSC within 90 days of the LSC
publication.
Response: We cannot adopt the LSC
within 90 days of the LSC publication
because we are required to give notice
to the public that we are proposing to
revise a regulation. Once we notify the
public of the proposal, the public must
have the opportunity to comment on the
revisions, and we must respond to the
comments before the update becomes
final and legally enforceable. We do
review each edition of the NFPA 101
and NFPA 99 every 3 years to see if
there are any significant provisions that
we need to adopt and will continue to
do so. We have reviewed the 2015
edition of the LSC and do not feel that
there are any significant provisions that
need to be addressed at this time.
Comment: Many commenters have
suggested that CMS develop a process to
be able to permit a facility to apply for
a waiver prior to being cited for a
deficiency. The commenters stated that
it is currently standard practice for CMS
to decline to review any requests for
waivers filed before there has been a
deficiency cited during a survey.
Response: We agree and have
implemented a process to approve
categorical waivers. We do not consider
it always necessary for a facility to be
cited for a deficiency before it can apply
for or receive a waiver. This is
particularly the case when we have
evaluated specific provisions of the
LSC, determined that a waiver would
apply to all similarly-situated facilities
with respect to the LSC requirement in
question, and issued a public
communication describing the specifics
of such a categorical waiver, including
any particular requirements that must
be met in order for the waiver to apply
to a facility. Facilities may still submit
requests for non-categorical waivers,
which is currently done after a citation
of a deficiency is found on a fire safety
survey. The waiver request includes the
reason why the waiver of a specific life
safety requirement cannot be complied
with, and is submitted as part of the
facility Plan of Correction of
Deficiencies found on the survey to the
State Agency or Regional Office for
review and approval/disapproval by the
CMS Regional Office. For example, CMS
released the following Survey & Cert
(S&C) Memos on categorical waivers,
and the application process:
• April 19, 2013—S&C: 13–25: Relative
Humidity (RH): Waiver of LSC
Anesthetizing Location Requirements;
Discussion of Ambulatory Surgical
Center (ASC) Operating Room
Requirements https://www.cms.gov/
Medicare/Provider-Enrollment-and-
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
26886
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Certification/
SurveyCertificationGenInfo/
Downloads/Survey-and-Cert-Letter13-25.pdf.
• August 30, 2013—S&C: 13–58: 2000
Edition National Fire Protection
Association (NFPA) 101® LSC
Waivers https://www.cms.gov/
Medicare/Provider-Enrollment-andCertification/
SurveyCertificationGenInfo/
Downloads/Survey-and-Cert-Letter13-58.pdf.
• September 26, 2014—S&C: 14–46
Categorical Waiver for Power Strips
Use in Patient Care Areas https://
www.cms.gov/Medicare/ProviderEnrollment-and-Certification/
SurveyCertificationGenInfo/
Downloads/Survey-and-Cert-Letter14-46.pdf.
Comment: One commenter expressed
concern with the proposal that facilities
maintain antifreeze in their sprinkler
systems in certain proportions. The
commenter recommended that CMS
withdraw this requirement, or
reconsider its inclusion, until products
become available which do not require
more than 50 percent antifreeze (in
compliance with the proposed rule), but
which would still keep the sprinkler
systems from freezing.
Response: Where traditional
antifreeze solutions for existing systems
remain an option, consideration should
be given to alternatives to using
antifreeze. Antifreeze is not required to
prevent the freezing of systems. Owners
should investigate alternative methods
to prevent the freezing of wet pipe
systems in environments or locations
that may be subject to freezing.
Comment: A few commenters
suggested that CMS allow facilities the
opportunity to apply for a waiver rather
than install sprinklers if they can show
that staff and patients can be quickly
evacuated or that they offer the same
level of protection without the
sprinklers.
Response: Sprinklers are considered
to be a basic level of protection for new
and certain rehabilitated buildings, and
we do not believe that it would be in the
best interest of building occupants to
waive these sprinkler requirements.
Furthermore, we only require universal
retrofitting to add sprinklers in high-rise
health care occupancies, LTC facilities,
in the attics of board and care facilities.
Impractical evacuation capability
facilities are all required to be protected
throughout by an approved automatic
sprinkler system. There is strong
evidence that sprinklers in these
particular environments are an essential
fire safety feature; therefore we do not
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
believe it is in the best interest of
patients and staff to waive these
requirements under any circumstances.
https://www.facilitiesnet.com/firesafety/
article/Fire-Safety-FacilitiesManagement-Fire-Safety-Feature-1620.
Comment: Some commenters
expressed concern with the use of the
term ‘‘inappropriate access’’ in regards
to the placement of ABHRs. The
commenters requested clarification of
what is meant by the regulatory
requirement that dispensers are
installed in a manner that adequately
protects against inappropriate access.
Response: As stated in the ABHR final
rule published in September 22, 2006
(71 FR 55326), there are certain patients
or resident populations, such as
residents of dementia wards, who may
misuse ABHR solutions, which are both
toxic and flammable. As a toxic
substance, ABHR solutions are very
dangerous if they are ingested, placed in
the eyes, or otherwise misused. As a
flammable substance, ABHR solutions
could be used to start fires that endanger
lives and destroy property. Due to
disability or disease, some patients are
more likely to harm themselves or
others by inappropriately using ABHR
solutions. In order to avoid any and all
dangerous situations, a facility will have
to take all appropriate precautions to
secure the ABHR dispensers from
inappropriate access. This may mean
that facilities choose to not install
ABHR dispensers in corridors in or near
dementia or psychiatric units. It may
also mean that facilities choose to install
ABHR dispensers only in areas that can
be easily and frequently monitored,
such as in view of a nursing station or
a continuously monitored security
camera. These are just a few of the many
options that facilities may choose to
utilize in securing ABHR dispensers
against inappropriate access.
Comment: A few commenters
expressed concern with the requirement
in Chapter 8 of the 2012 edition of
NFPA 101, which stipulates that all
penetrations of a fire-rated wall or floor
must be protected by an ‘‘Approved Fire
Stop System or Device,’’ instead of
simply offering protection equivalent to
the surfaces penetrated, as was required
in the 2000 edition of NFPA 101. The
commenters stated that this requirement
would result in higher costs for new
facilities required to use proprietary
devices or systems. If CMS requires an
existing facility to meet this new
standard due to application for a new
provider agreement, the cost
implications could be even greater as
existing wires and other penetrating
elements would need to be removed
then reinstalled as necessary in order to
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
comply. The commenters requested that
existing facilities be exempted from this
requirement.
Response: The 2012 edition of NFPA
101, Section 8.3.5 states ‘‘The
provisions of 8.3.5 shall not apply to
approved existing materials and
methods of construction used to protect
existing through-penetrations and
existing membrane penetrations in fire
walls, fire barrier walls, or fire
resistance–rated horizontal assemblies,
unless otherwise required by Chapters
11 through 43.’’ Section 8.3.5.1 requires
firestop systems and devices; therefore,
this requirement would not be
applicable to existing installations.
Comment: Many commenters
expressed concerns with our proposed
regulation regarding fire watches. We
proposed to require a fire watch if a
sprinkler system is out for more than 4
hours. Commenters explained that most
system maintenance extends over an 8hour period of time during a normal
workday, and that, during the outage
additional staff with expertise in
sprinkler system operation are present
to address sprinkler system problems.
Additionally, during a sprinkler system
outage, the fire alarms are still
functioning to detect a fire. Therefore,
commenters recommend only requiring
the fire watch if the system will be out
of service for 10 hours or more.
Response: We agree that most
sprinkler system outages occur during a
regular work day with sufficient staff
levels to provide appropriate monitoring
and assure patient safety from fire.
Therefore, we are withdrawing the
proposal that all system shutdowns of
more than 4 hours would require a fire
watch. We believe a fire watch would
consist of dedicated staff with no other
duties constantly circulating throughout
the facility or the portion of the facility
affected by the sprinkler system
impairment looking for a fire, fire
hazards or hazardous conditions that
may affect the fire safety of the facility.
Facilities may wish to maintain
documentation of the rounds of a fire
watch, but this is not required.
Comment: The 2000 edition of the
NFPA 99 required separate ventilation
systems for windowless anesthetizing
locations in all newly constructed
health care occupancies. Although the
NFPA removed the ventilation system
requirement from the 2012 edition of
the NFPA 99, CMS proposed to retain
the ventilation requirement for all
hospitals and ASCs. Approximately one
third of commenters who submitted
comments on this rule commented on
this proposal. With the exception of two
commenters who supported the
proposal, the vast majority of
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
commenters who commented on this
issue strongly disagreed with this
proposal. The commenters stated that
installing and maintaining separate
ventilation systems in windowless
anesthetizing locations in existing
buildings would be a significant
expense, with estimates of $30,000 per
system per anesthetizing location. The
commenters stated that installing and
maintaining separate ventilation
systems as part of constructing a new
building is also a significant expense,
with estimates ranging from $75,000 to
$100,000 per anesthetizing location. The
commenters stated that installing and
maintaining ventilation systems in
windowless anesthetizing locations, and
thus incurring this large expense, is
unnecessary for the following reasons:
• Of the millions of surgical
procedures performed each year,
0.00092 percent per year results in
surgical fires;
• Surgical fires are largely
preventable, and training on prevention
of and prompt response to fires is much
more likely to be effective for patient
safety than installing and maintaining
ventilation systems;
• While anesthetics used to be
flammable, they are not flammable
anymore, which significantly reduces
the risk of fires in anesthetizing
locations;
• Most anesthetizing locations have
quick response sprinklers present to
extinguish any fire that may occur,
eliminating the need for a smoke
ventilation system. Healthcare
occupancies required to install
sprinklers to fulfill new construction or
renovation requirements would need to
install quick response sprinklers
through smoke compartments
containing patient rooms. If an
anesthetizing location is located in the
same compartment as the patient
sleeping rooms, then the anesthetizing
location would require quick response
sprinklers;
• The types of fires that occur in
anesthetizing locations produce such a
small amount of smoke that the smoke
would not compromise the ability of
staff to implement emergency
interventions to extinguish a fire;
• Staff in anesthetizing locations have
training in updated techniques to
quickly extinguish any fire that may
occur;
• Some facilities have smoke purge
systems that are just as capable of smoke
control as the proposed ventilation
system; and
• The proposed smoke ventilation
system may, under certain
circumstances, create an increased risk
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
for surgical infections in the affected
anesthetizing locations.
Response: In light of the concerns
raised by commenters, we agree that
requiring the installation of smoke
ventilation systems would not be an
effective use of hospital and ASC
resources. We agree that a focus on
preventing and quickly extinguishing
surgical fires will likely have a more
significant positive impact on patient
safety, and encourage hospitals, CAHs,
and ASCs to continue this important
work. We also agree that the presence of
quick response sprinkler heads,
alternative smoke purge systems, which
can continue to be used, and the use of
non-flammable anesthetics all
contribute to a very minimal risk of
smoke requiring ventilation in the first
place. Therefore, we have removed this
requirement from the regulations text
for hospitals, CAHs, and ASCs.
Comment: The LSC applies a specific
occupancy type to a facility that has 4
or more patients. Many commenters
disagreed with our proposal to require
all facilities to meet the occupancy
requirements regardless of the number
of patients because it would require
small facilities to meet more stringent
requirements. Commenters stated that
there is no evidence to support the need
for additional safety measures in these
facilities.
Response: We agree with the
commenters that meeting a more
stringent occupancy classification is not
necessary for very small health care
occupancies with less than 4 patients at
any given time, and therefore, are
withdrawing our proposal. This will not
affect any facilities as we are keeping
the requirement as it was in the 2000
edition of the LSC and are not making
any changes. ASCs continue to be
required to meet the occupancy
requirements for ambulatory care
occupancies ‘‘regardless of the number
of patients served.’’ While this
requirement is different from the
definition of ambulatory care occupancy
in the LSC, it is consistent with the
previous rule adopting the 2000 edition
of the NFPA 101 (68 FR 1374), which
applied the ambulatory care occupancy
chapter to all ASCs, regardless of the
number of patients served.
Comment: Many commenters
expressed concern with the window sill
height requirement. The 2000 edition of
the LSC required that newly constructed
health care occupancies cannot have a
sill height exceeding 36 inches above
the floor (with certain exceptions). The
NFPA removed this requirement from
the 2012 edition of the LSC. However,
CMS proposed to retain this
requirement and apply it to all facilities,
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
26887
whether they were new or existing
construction. The vast majority of the
commenters expressed concern with
retrofitting existing facilities to meet
this proposed requirement, and the
financial burden they would incur.
Commenters also disagreed with the
justification for the proposal.
Response: We agree with commenters
that requiring existing facilities to
change their existing window structures
to meet this requirement would be an
undue burden. We have revised the
regulation to assure that any facilities
built after the effective date of this final
rule will have to meet the 36 inch
window sill height requirement, in
accordance with the 2000 edition of the
LSC. Existing facilities that were not
required to meet this specification at the
time of construction would not be
required to change window sill heights
at this time. The Secretary does not have
statutory authority to require a
minimum window sill requirement,
however we believe that while window
sill height is not directly associated with
fire safety, but it is important to quality
of life and beneficial to the healing
process.
Comment: Many commenters
expressed concern with the corridor
projections requirement. The LSC
allows for 6″ corridor projections, but
the 2010 ADA Standards for Accessible
Design (2010 Standards) only allow 4″
corridor projections. The commenters
suggested only requiring 4″ corridor
projections in new construction and
newly renovated construction. The
commenters also noted that ABHR
dispensers, TV/computer monitors, and
computer kiosks often project more than
4″ and would have to be moved. A few
commenters stated that projections of 4″
or more should be allowed if alternative
means are used such as vertical guards.
Some commenters also asked why the
LSC and CMS allows fixed furniture in
corridors of LTC facilities up to 2 feet,
but will not allow projections of more
than 4″. One commenter suggested not
adopting section 7.2.2.4.4.5 regarding
the installation of handrails. This
section requires handrails be mounted
to provide a clearance of not less than
21⁄4 inches from the wall. The
commenter states that this is not ADA
compliant or IBC compliant, there is no
maximum distance from the wall, that
this wider gap increases the risk of
entrapment if a person’s hand slips
while going down the stairs, and that
this should also apply to existing
construction. One commenter also
questioned whether or not the ADA 4″
projections apply to areas that are not
patient treatment areas, like mechanical
or chemical rooms.
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
26888
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Response: As noted, CMS recognizes
that the LSC is not an accessibility code
and stresses that compliance with this
code is not a substitute for compliance
with the ADA. The 2010 ADA standards
address many concerns raised by
commenters, including the clear floor
width of walking surfaces in corridors
and handrail clearance. See Section
403.5 and 505.5 of the 2010 ADA
standards at https://www.ada.gov/
regs2010/2010ADAStandards/
2010ADAStandards.htm. In addition to
following the requirements of the LSC,
health care facilities are also required to
follow all requirements of the ADA.
Where there are conflicts between the
LSC and the ADA, the more stringent
standard takes precedence. Therefore,
facilities must comply with the ADA’s
requirements for protruding objects,
which establishes more stringent
protrusion limits so that a person using
a cane may avoid bodily harm. See
section 307.2 of the 2010 ADA
standards, available at https://
www.ada.gov/regs2010/
2010ADAStandards/
2010ADAStandards.htm (establishing a
4″ limit for wall-mounted protruding
objects and a 41⁄2″ limit for handrails).
Title II of the ADA applies to health care
programs and services of state and local
governments; and Title III of the ADA
applies to private entities providing
health care services. When structural
changes are made to existing facilities to
provide program access required by
Title II, the 2010 ADA standards are the
applicable accessibility standard. Newly
constructed or altered Title II and Title
III facilities must also comply with the
2010 ADA standards. Existing Title III
facilities are required to remove barriers
to accessibility when barrier removal is
readily achievable, and the 2010 ADA
standards are the applicable
accessibility standard. Changes to the
2010 ADA standards are beyond the
scope of this rule. Any questions
regarding the requirements of the ADA
should be directed to DOJ. Technical
assistance regarding ADA compliance
can be obtained at https://www.ada.gov
or 1–800–514–0301 (voice) and 1–800–
514–0383 (TTY).
Comment: One commenter suggested
that there be a requirement for each
provider or supplier to conduct an
annual inspection and maintenance of
fire door assemblies. Another
commenter explicitly disagreed with
this recommendation, stating that the
final rule should clarify that annual
inspection of doors in an egress path is
not required in healthcare, ambulatory
care, and business occupancies.
Specifically, the commenter stated that
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
hospitals are already performing visual
inspection of these door assemblies and
already assure latching and smooth
operation at all times. The commenter
asserted that conducting an additional
annual inspection would be
unnecessarily burdensome.
Response: As proposed, we will
maintain the required annual inspection
and maintenance of door assemblies.
This rule will thus require
documentation that the facility actually
inspected and performed maintenance
necessary on this important fire
protection feature. This inspection
could be combined with any other
maintenance effort that the facility may
be performing.
Comment: One commenter questioned
whether the requirement that a
recycling bin must be 96 gallons or less
would apply to recycling bins that are
stored outside.
Response: This requirement only
applies to any recycling bins located
within a building.
Comment: One commenter stated that
1 year is an adequate timeframe to allow
facilities to make necessary changes to
add smoke partitions around hazardous
areas, and that this requirement will not
require many facilities to make changes
because building codes have required
separation of hazardous areas for a long
period of time.
Response: Since most building codes
already require the separation of
hazardous areas, and facilities are
probably already meeting this
requirement, we agree that a 1 year
phase-in period from the effective date
of this final rule is appropriate to enable
affected facilities to comply with the
requirement for hazardous areas
separation. Affected facilities will have
1 year from the effective date of this
final rule to add smoke partitions
around hazardous areas that are not
already protected by this feature.
Comment: We proposed to adopt the
2012 edition of the NFPA 101, which
references the 2010 edition of NFPA
101A, Guide on Alternative Approaches
to Life Safety. One commenter
recommended that we adopt the 2013
edition of the NFPA 101A instead. The
commenter believes that there are some
very significant differences between the
2010 and 2013 editions of NFPA 101A,
including:
• Section 4.3.2 ‘‘Selection of Zones to
be Evaluated’’
• Section 4.6.9.3 ‘‘Mechanically
Assisted Systems’’
• Section 4.7.10 ‘‘Step 10—Determine
Equivalency Conclusion’’
• Worksheet 4.7.11 ‘‘Conclusions’’
Response: In order to be consistent
with the 2012 edition of the LSC, we are
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
not separately adopting the 2013 edition
of the NFPA 101A. We will continue to
follow the 2010 edition of the NFPA
101A. If we adopt a newer version of the
LSC in the future that also adopts the
2013 edition of the NFPA 101A, we will
review that document at that time.
Comment: One commenter suggested
that CMS and, by extension, those
accreditation organizations that perform
deeming surveys, should not cite LSC
deficiencies that are self-identified by
the provider or supplier. The
commenter believes that a survey policy
which encourages non-citation of selfidentified LSC deficiencies will provide
an incentive to hospital facility
managers to self-identify their LSC
deficiencies, record them on a list, and
manage the resolution of the
deficiencies.
Response: We applaud facilities that
self-identify LSC deficiencies; however,
CMS is most concerned with the safety
of patients and staff. Therefore, if the
facility is able to self-identify
deficiencies, they should be in the
process of fixing those deficiencies and
able to develop a suitable plan of
correction for any deficiencies that are
cited by surveyors.
Comment: A commenter is concerned
that the 2012 edition of the LSC eases
the requirements for smoke barriers in
existing facilities with less than 30 beds.
The commenter suggested that CMS
should require any facilities with less
than 30 beds that were originally built
with or added a smoke barrier dividing
the floor into at least two smoke
compartments to keep that smoke
barrier, even though the 2012 edition
would allow the facility to remove the
smoke barrier.
Response: We appreciate the
suggestion. We do not anticipate
facilities actively taking steps to remove
existing smoke barriers in light of this
change in the LSC. Should facilities
undertake construction at a future date,
they would still be required to meet the
2012 edition of the LSC. We believe that
the 2012 edition of the LSC assures the
appropriate level of safety for all
residents/patients.
NFPA 99—Health Care Facilities Code
Comment: Many commenters support
the adoption of the 2012 NFPA 99
Health Care Facilities code. However,
many commenters expressed confusion
as to why the NFPA 99 is not being
adopted in full, and some chapters are
being excluded.
Response: As stated in the proposed
rule, we will not be adopting Chapters
7, 8 and 13 because we have no
authority to regulate these specific
topics in health care facilities.
E:\FR\FM\04MYR2.SGM
04MYR2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Additionally, the content of Chapter 12,
Emergency management, is already
being addressed in a separate rule for
emergency preparedness. Although, we
have not adopted these chapters,
providers may use these chapters for
their individual facility needs.
Comment: Some commenters
encouraged the adoption of the 2012
edition of the NFPA 99 Health Care
Facilities code because it allows for the
use of relocatable power taps, which
provide additional electrical
receptacles. The 1999 edition of the
NFPA 99 does not allow the use of
relocatable power taps.
Response: We appreciate the support
of the commenters, and agree that
relocatable power taps can be
appropriately used in health care
environments. Therefore, we are
finalizing this change as proposed.
Comment: A few commenters
expressed concerns with multiple issues
found in the 2012 edition of the NFPA
99 that they believe would require a
facility to upgrade to be in compliance
with the following: Ductwork, HVAC
system designs, electrical and medical
gas system requirements, ground fault
protection requirements, piped medical
gas systems, and receptacle
requirements. The commenters
suggested that these sections be applied
only to new facilities and facilities being
remodeled.
Response: We appreciate the
opportunity to clarify the requirements
of NFPA 99. The 2012 edition of the
NFPA 99 does not divide its chapters
and requirements into new and existing.
We note that in the 2012 edition of
NFPA 99 Section 1.3.2 states
‘‘Construction and equipment
requirements shall be applied only to
new construction and new equipment,
except as modified in individual
chapters.’’ The sections described in the
comments do not have any modified
requirements; therefore, in accordance
with the requirements of NFPA 99,
these requirements only apply to new
construction and new equipment.
srobinson on DSK5SPTVN1PROD with RULES2
General or Other Comments
Comment: One commenter suggested
that we add a list of acronyms at the
beginning of the rule.
Response: We have added a list of
acronyms to the beginning of the
document. We have also spelled out
each acronym the first time it is used in
the rule.
IV. Provisions of the Final Regulations
We are adopting the provisions of this
rule as proposed, except for the
following changes and clarifications:
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
RNHCI—
We are clarifying that our adoption of
the 2012 edition of the NFPA 101 and
NFPA 99, includes the following TIAs
issued prior to April 16, 2014:
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(vi) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(vi) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(viii) TIA 12–5 to NFPA 99, issued
August 1, 2013
(ix) TIA 12–6 to NFPA 99, issued
March 3, 2014.
• We are clarifying that the
prohibition on roller latches applies
only to doors to corridors and to rooms
containing flammable or combustible
materials.
• We are revising the requirements
for the shutdown of a sprinkler system
for an extended period of time.
• We are revising the window sill
requirement for new construction only
to indicate that such sills must not be
higher than 36 inches above the floor.
ASCs—
We are clarifying that our adoption of
the 2012 edition of the NFPA 101 and
NFPA 99, includes the following TIAs
issued prior to April 16, 2014,
regardless of the number of patients
served:
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(vi) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(vii) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(viii) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(ix) TIA 12–6 to NFPA 99, issued
March 3, 2014.
• We are removing the requirements
for the installation of a dedicated air
supply and exhaust system in
windowless anesthetizing locations.
• We are revising the requirements
for door locking mechanisms on
hazardous areas.
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
26889
• We are revising the requirements
for the shutdown of a sprinkler system
for an extended period of time.
• We are revising the window sill
requirements for new construction only
to indicate that such sills must not be
higher than 36 inches above the floor.
Hospice—
We are clarifying that our adoption of
the 2012 edition of the NFPA 101 and
NFPA 99, includes the following TIAs
issued prior to April 16, 2014:
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(vi) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(vii) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(viii) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(ix) TIA 12–6 to NFPA 99, issued
March 3, 2014.
• We are clarifying that the
prohibition on roller latches applies
only to doors to corridors and to rooms
containing flammable or combustible
materials.
• We are revising the requirements
for the shutdown of a sprinkler system
for an extended period of time.
• We are revising the window sill
requirement for new construction only
to indicate that such sills must not be
higher than 36 inches above the floor.
PACE—
We are clarifying that our adoption of
the 2012 edition of the NFPA 101 and
NFPA 99, includes the following TIAs
issued prior to April 16, 2014:
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(vi) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(vii) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(viii) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(ix) TIA 12–6 to NFPA 99, issued
March 3, 2014.
• We are clarifying that the
prohibition on roller latches applies
E:\FR\FM\04MYR2.SGM
04MYR2
26890
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
only to doors to corridors and to rooms
containing flammable or combustible
materials.
• We are revising the requirements
for the shutdown of a sprinkler system
for an extended period of time.
srobinson on DSK5SPTVN1PROD with RULES2
Hospitals—
We are clarifying that our adoption of
the 2012 edition of the NFPA 101 and
NFPA 99, includes the following TIAs
issued prior to April 16, 2014:
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(vi) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(vii) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(viii) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(ix) TIA 12–6 to NFPA 99, issued
March 3, 2014.
• We are clarifying that the
prohibition on roller latches applies
only to doors to corridors and to rooms
containing flammable or combustible
materials.
• We are clarifying that all outpatient
surgical departments must meet
applicable provisions in Ambulatory
Health Care occupancy chapter,
regardless of the number of patients
served.
• We are revising the requirements
for the shutdown of a sprinkler system
for an extended period of time.
• We are removing the requirement
for installation of a dedicated air supply
and exhaust system in windowless
anesthetizing locations.
• We are revising the window sill
requirement for new construction only
to indicate that such sills must not be
higher than 36 inches above the floor.
LTC—
We are clarifying that our adoption of
the 2012 edition of the NFPA 101 and
NFPA 99, includes the following TIAs
issued prior to April 16, 2014:
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(vi) TIA 12–3 to NFPA 99, issued
August 9, 2012.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
(vii) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(viii) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(ix) TIA 12–6 to NFPA 99, issued
March 3, 2014.
• We are clarifying that the
prohibition on roller latches applies
only to doors leading into corridors and
leading into rooms containing
flammable or combustible materials.
• We are revising the requirements
for the shutdown of a sprinkler system
for an extended period of time.
ICF–IIDs—
We are clarifying that our adoption of
the 2012 edition of the NFPA 101 and
NFPA 99, includes the following TIAs
issued prior to April 16, 2014:
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(vi) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(vii) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(viii) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(ix) TIA 12–6 to NFPA 99, issued
March 3, 2014.
• We are clarifying that the
prohibition on roller latches applies
only to doors to corridors and to rooms
containing flammable or combustible
materials.
• We are revising the exclusion of
provisions related to ‘‘Lockups.’’
• We are revising the requirements
for the shutdown of a sprinkler system
for an extended period of time.
• We are revising the window sill
requirement for new construction only
to indicate that such sills must not be
higher than 36 inches above the floor.
CAHs—
We are clarifying that our adoption of
the 2012 edition of the NFPA 101 and
NFPA 99, includes the following TIAs
issued prior to April 16, 2014:
(i) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iii) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(iv) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–1 to NFPA 99, issued
August 11, 2011.
(vi) TIA 12–2 to NFPA 99, issued
August 11, 2011.
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
(vii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(viii) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(ix) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(x) TIA 12–6 to NFPA 99, issued
March 3, 2014.
• We are clarifying that the
prohibition on roller latches applies
only to doors to corridors and to rooms
containing flammable or combustible
materials.
• We are revising the requirements
for the shutdown of a sprinkler system
for an extended period of time.
• We are removing the requirement
for installation of a dedicated air supply
and exhaust system in windowless
anesthetizing locations.
• We are revising the window sill
requirement for new construction only
to indicate that such sills must not be
higher than 36 inches above the floor.
V. Collection of Information
Requirements
This final rule does not impose any
new reporting, recordkeeping or thirdparty disclosure requirements. However,
this final rule does reference the NFPA
99 that has several non-reported
recordkeeping requirements for medical
gas and vacuum systems, and electrical
equipment. We believe that
documenting maintenance and testing is
a usual and customary business practice
in accordance with the implementing
regulations of the Paperwork Reduction
Act of 1995 (PRA) at 5 CFR 1320.3(b)(2),
and it would not impose any additional
information collection burden beyond
that associated with the normal course
of business. Consequently, it need not
be reviewed by the Office of
Management and Budget under the
authority of the Paperwork Reduction
Act of 1995.
VI. Regulatory Impact Analysis
In accordance with the provisions of
Executive Order 12866, this regulation
was reviewed by the Office of
Management and Budget.
A. Overall Impact
We have examined the impacts of this
rule as required by Executive Order
12866 on Regulatory Planning and
Review (September 30, 1993), Executive
Order 13563 on Improving Regulation
and Regulatory Review (January 18,
2011), the Regulatory Flexibility Act
(RFA) (September 19, 1980, Pub. L. 96–
354), section 1102(b) of the Social
Security Act, section 202 of the
Unfunded Mandates Reform Act of 1995
(March 22, 1995; Pub. L. 104–4),
Executive Order 13132 on Federalism
E:\FR\FM\04MYR2.SGM
04MYR2
26891
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
(August 4, 1999) and the Congressional
Review Act (5 U.S.C. 804(2).
Executive Orders 12866 and 13563
direct agencies to assess all costs and
benefits of available regulatory
alternatives and, if regulation is
necessary, to select regulatory
approaches that maximize net benefits
(including potential economic,
environmental, public health and safety
effects, distributive impacts, and
equity). Executive Order 13563
emphasizes the importance of
quantifying both costs and benefits, of
reducing costs, of harmonizing rules,
and of promoting flexibility. A
regulatory impact analysis (RIA) must
be prepared for major rules with
economically significant effects ($100
million or more in any 1 year). The
overall economic impact for this rule is
estimated to be $18 million in the first
year of implementation, $12 million,
annually, for years 2 and 3 of
implementation, and $6 million,
annually, for years 4–12 of
implementation. We estimate that this
rulemaking is not ‘‘economically
significant’’ as measured by the $100
million threshold, and hence not a
major rule under the Congressional
Review Act. Accordingly, we have
prepared a Regulatory Impact Analysis
(RIA) that, to the best of our ability,
presents the costs and benefits of
rulemaking.
B. Statement of Need
The 2012 edition of the LSC includes
new provisions that we believe are vital
to the health and safety of all patients
and staff. Our intention is to ensure that
patients and staff continue to experience
the highest degree of fire safety possible.
The use of earlier editions of the code
can become problematic due to
advances in safety and technology and
changes made to each edition of the
code. Newer buildings are typically
built to comply with the newer versions
of the LSC because state and local
jurisdictions, as well as non-CMSapproved accreditation programs, often
adopt and enforce newer versions of the
code as they become available. We
believe that adopting the 2012 LSC
would simplify and modernize the
construction and renovation process for
affected health care providers and
suppliers, reduce compliance-related
burdens, and allow for more resources
to be used for patient care. Many health
care facilities complete unnecessary
work and incur unnecessary expense
without any gain in fire safety by
continuing to comply with the 2000
edition of the LSC.
The 2012 edition of the NFPA 99,
‘‘Health Care Facilities Code,’’ addresses
requirements for both health care
occupancies and ambulatory care
occupancies, and serves as a resource
for those who are responsible for
protecting health care facilities from fire
and associated hazards. The purpose of
this Code is to provide minimum
requirements for the installation,
inspection, testing, maintenance,
performance, and safe practices for
health care facility materials, equipment
and appliances. This Code is a
compilation of documents that have
been developed over a 40-year period by
NFPA, and is intended to be used by
those persons involved in the design,
construction, inspection, and operation
of health care facilities, and in the
design, manufacture, and testing of
appliances and equipment used in
patient care areas of health care
facilities. Many requirements of the LSC
already cross reference the NFPA 99,
and it addresses additional building
safety topics that are related to
important fire safety issues specific to
health care facilities.
We believe that it is in the best
interest of CMS to adopt the more recent
2012 edition of the NFPA 101 and the
2012 edition of the NFPA 99, in order
to be up to date with all of the latest
upgrades to health care facilities and
safety requirements.
C. Summary of Impacts
TABLE 1—TOTAL ANNUAL COST OF
IMPLEMENTATION FOR ALL YEARS
Millions
Year 1 of implementation .............
Years 2–3 of implementation .......
Years 4–12 of implementation .....
$18
24
53
Total Years 1–12 of implementation ......................................
95
Note: This cost may be less depending on
the number of States that have already adopted the 2012 edition of the LSC.
TABLE 2—TOTAL ANNUAL COST FOR IMPLEMENTATION IN YEAR 1
Cost per
affected
provider
Cost for all
providers
Requirement
Provider type affected
High-rise sprinkler installation ......................................
High-rise sprinkler installation ......................................
Self-closing or automatic closing doors on hazardous
areas.
Sprinklers in attics (used for living purposes, storage
or fuel fired equipment).
Heat detection systems in attics (not used for living
purposes).
Hazardous areas separated by smoke partitions ........
Upgrade existing or install new fire alarm system .......
Hospitals, partially sprinklered ......................................
Hospitals, non-sprinklered ............................................
ASCs .............................................................................
$34,075
117,028
1,047
$4,429,783
1,053,253
1,763,148
ICF–IIDs ........................................................................
4,500
5,980,500
ICF–IIDs ........................................................................
1,000
212,333
ICF–IIDs ........................................................................
ICF–IIDs ........................................................................
1,000
1,000
4,624,000
384,000
Total .......................................................................
..................................................................................
18,447,017
srobinson on DSK5SPTVN1PROD with RULES2
TABLE 3—TOTAL ANNUAL COST OF IMPLEMENTATION FOR YEARS 2–3
Cost per
affected
provider
Requirement
Provider type affected
High-rise sprinkler installation ......................................
High-rise sprinkler installation ......................................
Upgrade existing or install new fire alarm system .......
Sprinklers in attics (used for living purposes, storage
or fuel fired equipment).
Hospitals, partially sprinklered ......................................
Hospitals, non-sprinklered ............................................
ICF–IIDs ........................................................................
ICF–IIDs ........................................................................
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
E:\FR\FM\04MYR2.SGM
04MYR2
$34,075
117,028
1,000
4,500
Cost for all
providers
$4,429,783
1,053,253
384,000
5,980,500
26892
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
TABLE 3—TOTAL ANNUAL COST OF IMPLEMENTATION FOR YEARS 2–3—Continued
Cost per
affected
provider
Cost for all
providers
Requirement
Provider type affected
Heat detection systems in attics (not used for living
purposes).
ICF–IIDs ........................................................................
Total Annually ........................................................
..................................................................................
12,059,869
Overall Total Years 2–3 .................................
..................................................................................
24,119,738
1,000
212,333
TABLE 4—TOTAL COST OF IMPLEMENTATION FOR YEARS 4–12
Cost per
affected
provider
Cost for all
providers
Requirement
Provider type affected
High-rise sprinkler installation ......................................
High-rise sprinkler installation ......................................
Upgrade existing or install new fire alarm system .......
Hospitals, partially sprinklered ......................................
Hospitals, non-sprinklered ............................................
ICF–IIDs ........................................................................
Total Annually ........................................................
..................................................................................
5,867,036
Overall Total Years 4–12 ...............................
..................................................................................
52,803,324
D. Detailed Economic Analysis
1. Burden Assessment
srobinson on DSK5SPTVN1PROD with RULES2
Sprinklers in High-Rise Buildings
Section 19.4.2 of the LSC requires that
all existing high-rise buildings
containing health care occupancies be
protected throughout by an approved,
supervised automatic sprinkler system.
We feel that this requirement will only
affect hospitals and any other provider
type located in the same building as a
hospital (for example, an ASC that is
located in a hospital building). This
provision was added to the LSC in 2012
and we anticipate that there would be
a cost associated with installing the
sprinklers. Since this is a new provision
for the 2012 edition of the LSC, 14 states
have adopted this requirement,
accounting for an estimated 142 highrise facilities.
To develop the most accurate estimate
possible for this provision, we requested
data from all 50 states regarding the
sprinkler status of high-rise buildings
containing health care occupancies, and
the average square footage needing to be
sprinklered. Of the 50 states, we
received some data from 30 states.4 We
calculated the average number of highrise hospitals for all of the states that
responded. Overall, 15.64 percent of
4 The following states submitted data regarding
the sprinkler status of high-rise buildings
containing health care facilities—Arizona,
Arkansas, California, Colorado, Delaware, Hawaii,
Idaho, Iowa, Kansas, Louisiana, Maine, Maryland,
Massachusetts, Minnesota, Missouri, Montana,
Nebraska, Nevada, New Hampshire, New Mexico,
North Dakota, Oklahoma, Pennsylvania, Rhode
Island, South Dakota, Texas, Utah, Virginia,
Washington, and Wyoming.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
hospitals were located in high-rise
buildings. We also used the data
submitted to determine the average
number of fully, partially and nonsprinklered high-rise buildings in each
state for which we have data. First, we
calculated the percentages of fully,
partially, and non-sprinklered hospitals
for each state. We then averaged the
percentage of fully, partially and nonsprinklered buildings across all states
for which there was data, with a result
of 84.66 percent of hospitals in high-rise
buildings being fully sprinklered, 14.6
percent being partially sprinklered and
0.74 percent being non-sprinklered.
Next, we applied these percentages to
the states that did not respond to our
data request or that provided a limited
amount of data. For example, Alabama
has a total of 125 hospitals. Based on the
data from states that submitted
information, we know that, on average,
15.64 percent of hospitals have high-rise
buildings, for an estimated 20 high-rise
hospitals in Alabama. We used this
same methodology to estimate the
average number of high-rise hospitals in
all of the states that did not respond to
our data request or that provided only
a limited amount of data, for a total of
179 high-rise hospitals. Of the 179
estimated high-rise hospitals in states
that did not respond, we estimate there
are 151 fully sprinklered, 26 partially
sprinklered, and 2 non-sprinklered. We
note that these numbers do not directly
match because there was limited actual
data available for the state of
Massachusetts. The number of high-rise
hospitals in Massachusetts is included
in the count of states for which we have
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
$34,075
117,028
1,000
$4,429,783
1,053,253
384,000
reported data. However, because we did
not receive a breakdown of those highrise hospitals by their current sprinkler
status, we used the methodology
described to estimate the distribution of
fully sprinklered, partially sprinklered,
and non-sprinklered high-rise hospitals
in that state.
We combined this information with
the information from the states that
submitted data to develop an estimate of
515 high-rise facilities with health care
occupancies throughout all 37 states
and the District of Columbia that have
not adopted the 2012 NFPA 101 (336
high-rise facilities in states that
submitted data + 179 estimated highrise facilities in states that did not
submit data). We estimate that 376 of
those high-rise facilities are fully
sprinklered, 130 are partially
sprinklered, and 9 are not sprinklered.
We also requested that the 50 states
and the District of Columbia submit
information regarding the area
(measured in square feet) per partially
sprinklered and non-sprinklered facility
that does not currently have sprinklers.
Only 8 states supplied data regarding
the area to be sprinklered in partially
sprinklered facilities.5 In addition, 3
states supplied data regarding the area
to be sprinklered in non-sprinklered
facilities.6 We did not specify size and
5 The following states provided data regarding the
average square footage for partially sprinklered
high-rise facilities containing health care facilities—
California, Hawaii, Iowa, Kansas, Nebraska,
Pennsylvania, Virginia, and Washington.
6 The following states provided data regarding the
average square footage for non-sprinklered high-rise
facilities containing health care facilities—
California, Hawaii, and Iowa.
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
age data. Of the states that responded
with square footage data, we estimate
that an average partially sprinklered
facility would need to install sprinklers
to protect 37,173 square feet, and an
average non-sprinklered facility would
need to install sprinklers to protect
127,667 square feet. Regardless of the
square footage, any facility in a high-rise
building 75′ or over is required to be
sprinklered. We applied all of the data
submitted and averages calculated to
figure out the total average area that will
need to be sprinklered in all partially
sprinklered facilities and nonsprinklered facilities, and the cost
associated with that installation. Based
on the information provided by the
public in comments received on the
hospital conditions of participation (76
FR 65891), the cost per square foot to
install sprinklers is approximately $11.
We estimated that there are 130 partially
sprinklered facilities that would install
sprinklers to cover an average of 37,173
square feet per facility, for a total of
4,832,490 square feet. At an estimated
cost of $11 per square foot to install
sprinklers, we estimate a total cost of
$53,157,390 for all partially sprinklered
facilities (4,832,490 square feet × $11
per square foot). We estimate that an
average partially sprinklered facility
would spend $408,903 to complete the
sprinkler installation (37,173 square feet
per facility × $11 per square foot).
We estimated that there are 9 nonsprinklered facilities nationwide, and
that an average non-sprinklered facility
would install sprinklers for, 127,667
square feet, for a total of 1,149,003
square feet (9 facilities × 127,667 square
feet per facility). At an estimated cost of
$11 per square foot to install sprinklers,
we estimate that it would cost
$12,639,033 for all non-sprinklered
facilities to install sprinklers in their
facilities. We estimate that an average
non-sprinklered facility would spend
$1,404,337 per facility (127,667 square
feet × $11 per square foot).
Therefore, we estimate the total cost
associated with the installation of
sprinklers in partially sprinklered and
non-sprinklered facilities to be
$65,796,423 ($53,157,390 for all
partially sprinklered facilities +
$12,639,033 for all non-sprinklered
facilities). This cost would be
distributed over a phase-in period of 12
years, per the phase-in period
established within the LSC, or an
average yearly cost of $5.5 million.
Sprinklers Out of Service for More Than
10 Hours
We have removed the requirement for
a fire watch or building evacuation if
the sprinkler system is out of service for
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
more than 4 hours, and have adopted
the LSC requirements of a fire watch or
building evacuation if the sprinkler
system is out for more than 10 hours in
a 24-hour period. Based on comments
received from stakeholders, associations
and the public, sprinkler systems are
generally only out of service for 8 hours
in a 24-hour period. Therefore, we do
not anticipate additional costs
associated with this requirement. If
there is an event where the sprinkler
system would be out of service for more
than 10 hours in a 24-hour period, we
feel that it would be considered a
standard business practice to implement
a fire watch or building evacuation, as
the previous requirement was more
stringent and required a fire watch or
building evacuation after the sprinkler
system is out of service for more than
4 hours.
Doors to Hazardous Areas
Sections 20.3.2.1 and 21.3.2.1 of the
LSC requires all doors to hazardous
areas to be self-closing or automaticclosing. This requirement is only
located in sections 20.3.2.1 and 21.3.2.1,
which applies to Ambulatory health
care. This provision was added to the
LSC in 2003, and we anticipate that
there would be a cost associated with
installing the self-closing or automatic
closing doors. Since 2003, 35 states have
adopted this requirement, accounting
for an estimated 3,684 ASCs. As of
December 2013, there were 5,368 total
Medicare and applicable Medicaid
participating ASCs. The 1,684
remaining facilities would be required
to upgrade their door closing
mechanisms to meet this requirement.
The estimated cost per door is $349, and
we would assume the average facility
has 3 hazardous areas that would
require a replacement door closing
mechanism for a total cost of $1,047 per
facility. The anticipated cost is
$1,763,148.
Sprinklers or Heat Detection Systems in
Attics
Sections 32.2.3.5.7 and 33.2.3.5.7 of
the LSC requires attics of new and
existing residential board and care
occupancies, which, for our purposes,
are ICF–IIDs to be sprinklered if the attic
space is used for living purposes,
including storage and fuel fired
equipment. Facilities that do not use
their attics for living purposes may
choose to install a heat detection system
in place of the sprinklers. This
provision was added to the LSC in 2012.
Since this is a new provision for the
2012 edition of the LSC, only 14 states
have adopted this requirement,
accounting for an estimated 1,750 ICF–
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
26893
IIDs. We are not including those 1,750
facilities in our analysis. For purposes
of this analysis only, we assume that
about 10 percent (637) of facilities will
install a heat detection system because
they do not use the attic for living
purposes. As of December 2013, there
were 6,374 total Medicare participating
ICF–IIDs. After excluding those facilities
located in states that have already
adopted this requirement and those that
would install a heat detection system
instead of sprinklers, the 3,987
remaining facilities would be required
to install sprinklers in their attics to
meet this requirement. Installing
sprinklers into an unfinished attic is
less complicated than installing
sprinklers in a finished hospital,
therefore the cost per square foot would
be less to install in attics than hospitals.
The estimated cost per square foot to
install sprinklers in an attic is $3.00,
and the average estimated square
footage per attic per facility is 1500
square feet, for a total of $4,500 per ICF–
IID. We estimate that all ICF–IIDs would
spend $17,941,500 to install sprinklers
in their attic spaces. After soliciting
public comment, we have decided to
finalize a 3 year phase-in period, which
would make the cost $5,980,500 per
year over 3 years.
Facilities that do not use their attics
for living purposes may choose to install
a heat detection system in the attic
instead of sprinklers. As stated, for the
purposes of this analysis only, we
assume that about 10 percent (637) of
facilities will install a heat detection
system because they do not use the attic
for living purposes. We estimate the cost
to install a heat detection system to be
$1,000 per facility. The anticipated cost
would be $637,000 for all affected
facilities to install heat detection
systems. After soliciting public
comment, we have decided to finalize a
3 year phase-in period, which would
make the cost $212,333 per year over 3
years.
Hazardous Area Separation
Section 33.3.3.2.3 of the LSC requires
all hazardous areas in existing
residential board and care occupancies
(which, under our regulations, are ICF–
IIDs) with impractical evacuation
capabilities to be separated from other
parts of the building by a smoke
partition. This provision was added to
the LSC in 2012 and we anticipate there
being a cost associated with installing
the smoke partition. Since this is a new
provision for 2012, only 14 states have
adopted this requirement, accounting
for 1,750 ICF–IIDs. As of December
2013, there were 6,374 total Medicare
and applicable Medicaid participating
E:\FR\FM\04MYR2.SGM
04MYR2
26894
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
ICF–IIDs. We do not collect data
regarding the evacuation capability of
each ICF–IID. Therefore, for purposes of
this analysis only, we assume that the
4,624 remaining facilities will need to
install a smoke partition around all
hazardous areas to meet this
requirement. The estimated cost per
smoke partition is $500, and we assume
that an average ICF–IID would need to
install 2 smoke partitions for a total of
$1,000 per facility. The anticipated cost
is $4,624,000.
Fire Alarm System Upgrade
Section 33.3.3.4.6.2 of the LSC
requires that, when an existing
residential board and care occupancy
(that is, ICF–IIDs) installs a new fire
alarm system, or the existing fire alarm
system is replaced, notification of
emergency forces should be handled in
accordance with section 9.6.4. Section
9.6.4states that notification of
emergency forces should alert the
municipal fire department and fire
brigade (if provided) of fire or other
emergency. This provision was added to
the LSC in 2012, and we anticipate there
being a cost associated with upgrading
a new or existing fire alarm system.
Since this is a new provision for 2012,
only 14 states have adopted this
requirement, accounting for 1,750 ICF–
IIDs. As of December 2013, there were
6,374 total Medicare participating ICF–
IIDs. The 4,624 remaining facilities
would be required to add emergency
notifications capabilities when they
choose to update or install a new fire
alarm system. The estimated cost per
upgrade is $1,000. For purposes of this
analysis only, we assume that about 8.3
percent (384) of facilities will do this in
any given year, for an annual cost of
$384,000 over a 12-year period.
($1,000 per upgraded alarm system ×
384 facilities in any given year =
$384,000)
srobinson on DSK5SPTVN1PROD with RULES2
2. Benefits to Patients/Residents
As a result of this rule, we believe that
there would be a decreased risk of
premature death. A decreased risk of
premature death is valuable to people
and that value is symbolized by their
willingness to pay for such benefits. The
Department of Transportation found in
a recent literature review that
willingness to pay for reductions in the
risk of premature death equivalent to
saving one life in expectation is
typically over $9 million (https://
www.dot.gov/sites/dot.dev/files/docs/
VSL%20Guidance%202013.pdf).
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
Although we are not quantifying the
number of lives that would be saved
upon implementation of this rule due to
the lack of data that could provide a
reliable point estimate, we believe that
there is potential for such a result. In
order to ‘‘break even’’ on the cost of this
rule—in other words, in order for the
total costs of implementing this rule to
equal the total benefits of doing so—this
rule would need to save 1.3 lives per
year for 12 years at a 7 percent discount
rate and a value of $9 million per life
saved would cause the rule to break
even. It would take about 1.1 lives per
year for 12 years at a 3 percent discount
rate. Given our review of the current
literature on fire safety in health care
facilities, we are confident that
implementing the 2012 LSC will save at
least that number of lives.
E. Alternatives Considered
As a regulatory alternative, we could
have chosen not to update our fire safety
provisions. We believe that this is not
an acceptable alternative because many
health care facilities complete
unnecessary work and incur
unnecessary expense without any gain
in fire safety by continuing to comply
with the 2000 edition of the LSC. Many
states have adopted subsequent editions
of the LSC. This has caused confusion
for, and imposed additional burdens on,
health care facilities, that must request
waivers or modify designs to meet the
requirements of both the state- and
federally-adopted editions of the LSC.
Updating the LSC would not only
relieve the regulatory burden on health
care providers, but also assist in
ensuring the health and safety of
patients and staff.
We considered an alternative phase-in
period for the requirement to install
sprinklers in high rise health care
occupancies. The LSC allows for a 12year phase-in period, which would
begin on the day a final rule is
published. We considered shortening
this period in order to accelerate
compliance. However, based on our
recent experience with requiring LTC
facilities to install sprinklers within 5
years, and the difficulties that several
facilities have faced in meeting this
deadline, we have learned that a shorter
phase-in period is not always feasible
for facilities. We also considered a
longer phase-in period, but believe that
extending beyond 12 years set out in the
LSC may not sufficiently convey the
importance of this requirement to
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
improving patient and staff safety in
these buildings.
We considered not including separate
requirements for window sill heights.
Although the NFPA has removed these
requirements from the LSC, because the
total concept approach of all health care
facilities should be designed,
constructed, maintained and operated to
minimize the possibility of a fire
emergency requiring the evacuation of
occupants can be achieved without
reliance on such window sill
requirements, we felt that this was an
important issues that still needed to be
required for the safety of patients,
visitors, and staff. Window sill height
requirements were eliminated from the
2012 edition of the LSC. We believe that
this requirement is essential to allow
easier access for emergency personnel in
the event of a fire or other emergency
situation and it is important to quality
of life and the healing process. This
will, however, only be required in new
facilities.
We considered not including the
adoption of the NFPA 99 Health care
Facilities code. However, many
requirements of the LSC already crossreference the NFPA 99, therefore we
decided to adopt the NFPA 99 because
it addresses additional building safety
topics that are related to important fire
safety issues specific to health care
facilities. The requirements of NFPA 99,
like those in NFPA 101, will be legally
enforceable to the extent specified in
this rule.
We also considered adoption of
chapters 7, 8, 12, and 13 of the NFPA
99, related to information technology,
plumbing, emergency management, and
security management. We believe that
information technology, plumbing and
security management are not within the
scope of the conditions of participation
and conditions for coverage. In addition,
emergency management topics are
addressed in our December 27, 2013
proposed rule, ‘‘Medicare and Medicaid
Programs: Emergency Preparedness
Requirements for Medicare and
Medicaid Participating Providers and
Suppliers’’ (78 FR 79081).
F. Accounting Statement
As required by OMB Circular A–4
(available at https://
www.whitehouse.gov/omb/circulars_
a004_a-4), we have prepared an
accounting statement in Table X
showing the classification of the
transfers and costs associated with the
provisions of this rule for CY 2015.
E:\FR\FM\04MYR2.SGM
04MYR2
26895
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
TABLE 5—ACCOUNTING STATEMENT: CLASSIFICATION OF ESTIMATED COSTS BETWEEN 2016 AND 2027
Units
Category
Estimates
Year dollar
Costs *
Annualized Monetized ($million/year) ......................................
8.6
8.2
Discount rate
(%)
2015
2015
Period covered
7
3
2016–2027
2016–2027
srobinson on DSK5SPTVN1PROD with RULES2
* Costs are associated with the provisions of the life safety code.
G. Regulatory Flexibility Act (RFA)
The RFA requires agencies to analyze
options for regulatory relief of small
entities, if a rule has a significant impact
on a substantial number of small
entities. For purposes of the RFA, small
entities include small businesses,
nonprofit organizations, and
government agencies. Individuals and
states are not included in the definition
of a small entity. For purposes of the
RFA, most of the providers and
suppliers that would be affected by this
rule (hospitals, ASCs, and ICF–IIDs) are
considered to be small entities, either by
virtue of their nonprofit or government
status or by having yearly revenues
below industry threshold established by
the Small Business Administration (for
details, see the Small Business
Administration’s Web site at https://
www.sba.gov/content/small-businesssize-standards).
• We estimate that the following
affected facilities are expected to spend
less than $3,500 in any given year on a
per average facility basis; all LTC
facilities, all hospices with inpatient
care facilities, all PACE facilities, all
RNHCIs, all existing ASCs, all existing
CAHs, and all existing fully sprinklered
hospitals.
• We estimate that the average
affected ICF–IID will spend $5,400–
$8,900 in the first year, which requires
the most significant investment and, by
year four, that amount drops to $3,400
per year.
• We estimate that the average
affected partially sprinklered high-rise
hospital and the average affected nonsprinklered high-rise hospitals will
spend $36,475–$119,428 each year
during the 12 year phase-in period to
install sprinklers. After the installation
of sprinklers, we estimate that the
annual cost decreases to $2,400 per
year.
• We estimate that newly constructed
hospitals will spend $2,400, newly
constructed CAHs will spend $2,400
and newly constructed ASCs will spend
$2,400, respectively, in any given year.
The Department of Health and Human
Services uses as its measure of
significant economic impact on a
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
substantial number of small entities a
change in revenues of more than 3 to 5
percent. Therefore, the Secretary
proposes to certify that this rule will not
have a significant impact on a
substantial number of small entities,
since the impact will be less than 3
percent of the revenue. The preceding
economic analysis, together with the
remainder of this preamble, constitutes
that analysis.
In addition, section 1102(b) of the Act
requires us to prepare a regulatory
impact analysis if a rule may have a
significant impact on the operations of
a substantial number of small rural
hospitals. This analysis must conform to
the provisions of section 604 of the
RFA. For purposes of section 1102(b) of
the Act, we define a small rural hospital
as a hospital that is located outside of
a metropolitan statistical area and has
fewer than 100 beds. We believe that
this rule will not have a significant
impact on the operations of a substantial
number of small rural hospitals.
J. Congressional Review Act
H. Unfunded Mandates Reform Act
(UMRA)
42 CFR Part 418
Section 202 of the Unfunded
Mandates Reform Act of 1995 (UMRA)
also requires that agencies assess
anticipated costs and benefits before
issuing any rule whose mandates
require spending in any 1 year of $100
million in 1995 dollars, updated
annually for inflation. In 2015, that
threshold is approximately $144
million. This rule will not have an
impact on the expenditures of state,
local, or tribal governments in the
aggregate, or on the private sector of
$144 million in any one year.
This regulation is subject to the
Congressional Review Act provisions of
the Small Business Regulatory
Enforcement Fairness Act of 1996 (5
U.S.C. 801 et seq.) and has been
transmitted to the Congress and the
Comptroller General for review.
In accordance with the provisions of
Executive Order 12866, this rule was
reviewed by the Office of Management
and Budget.
List of Subjects
42 CFR Part 403
Health insurance, Hospitals,
Intergovernmental relations,
Incorporation by reference, Medicare,
Reporting and recordkeeping
requirements.
42 CFR Part 416
Health facilities, Kidney diseases,
Incorporation by reference, Medicare,
Reporting and recordkeeping
requirements.
Health facilities, Hospice care,
Incorporation by reference, Medicare,
Reporting and recordkeeping
requirements.
42 CFR Part 460
Aged, Health, Incorporation by
reference, Medicare, Medicaid,
Reporting and recordkeeping
requirements.
42 CFR Part 482
Grant programs—health, Hospitals,
Incorporation by reference, Medicaid,
Medicare, Reporting and recordkeeping
requirements.
I. Federalism
42 CFR Part 483
Executive Order 13132 establishes
certain requirements that an agency
must meet when it promulgates a
proposed rule (and subsequent final
rule) that imposes substantial direct
requirement costs on state and local
governments, preempts state law, or
otherwise has Federalism implications.
This rule has no Federalism
implications.
Grant programs—health, Health
facilities, Health professions, Health
records, Incorporation by reference,
Medicaid, Medicare, Nursing homes,
Nutrition, Reporting and recordkeeping
requirements, Safety.
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
42 CFR Part 485
Grant programs—health, Health
facilities, Incorporation by reference,
E:\FR\FM\04MYR2.SGM
04MYR2
26896
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Medicaid, Medicare, Reporting and
recordkeeping requirements.
For the reasons set forth in the
preamble, the Centers for Medicare &
Medicaid Services amends 42 CFR
chapter IV as set forth below:
PART 403—SPECIAL PROGRAMS AND
PROJECTS
1. The authority citation for part 403
continues to read as follows:
■
Authority: 42 U.S.C. 1395b–3 and Secs.
1102 and 1871 of the Social Security Act (42
U.S.C. 1302 and 1395hh).
2. Amend § 403.744 by—
a. Revising paragraphs (a)(1)(i) and
(ii).
■ b. Revising paragraph (a)(4).
■ c. Adding paragraphs (a)(5) and (6).
■ d. Revising paragraphs (b)(1) and (c).
The revisions and additions read as
follows:
■
■
srobinson on DSK5SPTVN1PROD with RULES2
§ 403.744 Condition of participation: Life
safety from fire.
(a)
(1) * * *
(i) The RNHCI must meet the
applicable provisions and must proceed
in accordance with the Life Safety Code
(NFPA 101 and Tentative Interim
Amendments TIA 12–1, TIA 12–2, TIA
12–3, and TIA 12–4).
(ii) Notwithstanding paragraph
(a)(1)(i) of this section, corridor doors
and doors to rooms containing
flammable or combustible materials
must be provided with positive latching
hardware. Roller latches are prohibited
on such doors.
*
*
*
*
*
(4) The RNHCI may place alcoholbased hand rub dispensers in its facility
if the dispensers are installed in a
manner that adequately protects against
inappropriate access.
(5) When a sprinkler system is shut
down for more than 10 hours the RHNCI
must:
(i) Evacuate the building or portion of
the building affected by the system
outage until the system is back in
service, or
(ii) Establish a fire watch until the
system is back in service.
(6) Building must have an outside
window or outside door in every
sleeping room, and for any building
constructed after July 5, 2016 the sill
height must not exceed 36 inches above
the floor. Windows in atrium walls are
considered outside windows for the
purposes of this requirement.
(b) * * *
(1) In consideration of a
recommendation by the State survey
agency or Accrediting Organization, or
at the discretion of the Secretary, may
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
waive, for periods deemed appropriate,
specific provisions of the Life Safety
Code, which would result in
unreasonable hardship upon a RNHCI
facility, but only if the waiver will not
adversely affect the health and safety of
the patients.
*
*
*
*
*
(c) The standards incorporated by
reference in this section are approved
for incorporation by reference by the
Director of the Office of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information
Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the
National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html. If any
changes in this edition of the Code are
incorporated by reference, CMS will
publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000.
(i) NFPA 101, Life Safety Code, 2012
edition, issued August 11, 2011;
(ii) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(iii) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(iv) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(v) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(2) [Reserved]
■ 3. Add § 403.745 to read as follows:
§ 403.745 Condition of participation:
Building Safety.
(a) Standard: Building Safety. Except
as otherwise provided in this section the
RNHCI must meet the applicable
provisions and must proceed in
accordance with the Health Care
Facilities Code (NFPA 99 and Tentative
Interim Amendments TIA 12–2, TIA 12–
3, TIA 12–4, TIA 12–5 and TIA 12–6).
(b) Standard: Exceptions. Chapters 7,
8, 12, and 13 of the adopted Health Care
Facilities Code do not apply to a RNHCI.
(c) Waiver. If application of the Health
Care Facilities Code required under
paragraph (a) of this section would
result in unreasonable hardship for the
RNHCI, CMS may waive specific
provisions of the Health Care Facilities
Code, but only if the waiver does not
adversely affect the health and safety of
individuals.
(d) Incorporation by reference. The
standards incorporated by reference in
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
this section are approved for
incorporation by reference by the
Director of the Office of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information
Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the
National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html. If any
changes in this edition of the Code are
incorporated by reference, CMS will
publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000.
(i) NFPA 99, Standards for Health
Care Facilities Code of the National Fire
Protection Association 99, 2012 edition,
issued August 11, 2011.
(ii) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(iii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(iv) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(v) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(vi) TIA 12–6 to NFPA 99, issued
March 3, 2014.
(2) [Reserved]
PART 416—AMBULATORY SURGICAL
SERVICES
4. The authority citation for part 416
continues to read as follows:
■
Authority: Secs. 1102 and 1871 of the
Social Security Act (42 U.S.C. 1302 and
1395hh).
5. Amend § 416.44 by—
a. Revising paragraphs (b)(1) and (2).
b. Removing paragraph (b)(4).
c. Redesignating paragraph (b)(5) as
paragraph (b)(4).
■ d. Revising newly redesignated
paragraph (b)(4).
■ e. Adding new paragraphs (b)(5), and
(6).
■ f. Redesignating paragraphs (c) and (d)
as paragraphs (d) and (e).
■ g. Adding new paragraphs (c) and (f).
The revisions and additions read as
follows:
■
■
■
■
§ 416.44 Condition for coverage—
Environment.
*
*
*
*
*
(b) * * *
(1) Except as otherwise provided in
this section, the ASC must meet the
provisions applicable to Ambulatory
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Health Care Occupancies and must
proceed in accordance with the Life
Safety Code (NFPA 101 and Tentative
Interim Amendments TIA 12–1, TIA 12–
2, TIA 12–3, and TIA 12–4).
(2) In consideration of a
recommendation by the State survey
agency or Accrediting Organization or at
the discretion of the Secretary, may
waive, for periods deemed appropriate,
specific provisions of the Life Safety
Code, which would result in
unreasonable hardship upon an ASC,
but only if the waiver will not adversely
affect the health and safety of the
patients.
* * *
(4) An ASC may place alcohol-based
hand rub dispensers in its facility if the
dispensers are installed in a manner that
adequately protects against
inappropriate access.
(5) When a sprinkler system is shut
down for more than 10 hours, the ASC
must:
(i) Evacuate the building or portion of
the building affected by the system
outage until the system is back in
service, or
(ii) Establish a fire watch until the
system is back in service.
(6) Beginning July 5, 2017, an ASC
must be in compliance with Chapter
21.3.2.1, Doors to hazardous areas.
(c) Standard: Building Safety. Except
as otherwise provided in this section,
the ASC must meet the applicable
provisions and must proceed in
accordance with the 2012 edition of the
Health Care Facilities Code (NFPA 99,
and Tentative Interim Amendments TIA
12–2, TIA 12–3, TIA 12–4, TIA 12–5
and TIA 12–6).
(1) Chapters 7, 8, 12, and 13 of the
adopted Health Care Facilities Code do
not apply to an ASC.
(2) If application of the Health Care
Facilities Code required under
paragraph (c) of this section would
result in unreasonable hardship for the
ASC, CMS may waive specific
provisions of the Health Care Facilities
Code, but only if the waiver does not
adversely affect the health and safety of
patients.
*
*
*
*
*
(f) The standards incorporated by
reference in this section are approved
for incorporation by reference by the
Director of the Office of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information
Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the
National Archives and Records
Administration (NARA). For
information on the availability of this
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html. If any
changes in this edition of the Code are
incorporated by reference, CMS will
publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000.
(i) NFPA 99, Standards for Health
Care Facilities Code of the National Fire
Protection Association 99, 2012 edition,
issued August 11, 2011.
(ii) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(iii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(iv) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(v) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(vi) TIA 12–6 to NFPA 99, issued
March 3, 2014.
(vii) NFPA 101, Life Safety Code,
2012 edition, issued August 11, 2011;
(viii) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ix) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(x) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(xi) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(2) [Reserved]
PART 418—HOSPICE CARE
6. The authority citation for part 418
continues to read as follows:
■
Authority: Secs. 1102 and 1871 of the
Social Security Act (42 U.S.C. 1302 and
1395hh).
§ 418.108
[Amended]
7. Amend § 418.108 by—
a. Amending paragraph (a)(2) by
removing the reference ‘‘§ 418.110(b)
and (e)’’ and by adding in its place the
reference ‘‘§ 418.110(b) and (f)’’.
■ b. Amending paragraph (b)(1)(ii) by
removing the reference ‘‘§ 418.110(e)’’
and by adding in its place the reference
‘‘§ 418.110(f)’’.
■ 8. Amend § 418.110 by—
■ a. Revising paragraphs (d)(1)(i) and
(ii).
■ b. Revising paragraphs (d)(2) and (4).
■ c. Adding paragraphs (d)(5) and (6).
■ d. Redesignating paragraphs (e)
through (o) as (f) through (p).
■ e. Adding new paragraph (e).
■ f. Amending newly redesignated
paragraph (g)(4) introductory text by
removing the reference ‘‘paragraph
(f)(2)(iv) and (f)(2)(v) of this section’’
and adding in its place the reference
■
■
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
26897
‘‘paragraphs (g)(2)(iv) and (g)(2)(v) of
this section’’.
■ g. Amending newly redesignated
paragraph (n)(9) by removing the
reference ‘‘paragraph (n) of this section’’
and adding in its place the reference
‘‘paragraph (o) of this section’’.
■ h. Amending newly redesignated
paragraph (n)(13) by removing the
reference ‘‘§ 418.110(m)(11)’’ and
adding in its place the reference
‘‘paragraph (n)(11) of this section’’.
■ i. Adding paragraph (q).
The revisions and additions read as
follows:
§ 418.110 Condition of participation:
Hospices that provide inpatient care
directly.
*
*
*
*
*
(d) * * *
(1) * * *
(i) The hospice must meet the
applicable provisions and must proceed
in accordance with the Life Safety Code
(NFPA 101 and Tentative Interim
Amendments TIA 12–1, TIA 12–2, TIA
12–3, and TIA 12–4.)
(ii) Notwithstanding paragraph
(d)(1)(i) of this section, corridor doors
and doors to rooms containing
flammable or combustible materials
must be provided with positive latching
hardware. Roller latches are prohibited
on such doors.
(2) In consideration of a
recommendation by the State survey
agency or Accrediting Organization or at
the discretion of the Secretary, may
waive, for periods deemed appropriate,
specific provisions of the Life Safety
Code, which would result in
unreasonable hardship upon a hospice
facility, but only if the waiver will not
adversely affect the health and safety of
the patients.
*
*
*
*
*
(4) A hospice may place alcohol-based
hand rub dispensers in its facility if the
dispensers are installed in a manner that
adequately protects against access by
vulnerable populations.
(5) When a sprinkler system is shut
down for more than 10 hours, the
hospice must:
(i) Evacuate the building or portion of
the building affected by the system
outage until the system is back in
service, or
(ii) Establish a fire watch until the
system is back in service.
(6) Buildings must have an outside
window or outside door in every
sleeping room, and for any building
constructed after July 5, 2016 the sill
height must not exceed 36 inches above
the floor. Windows in atrium walls are
considered outside windows for the
purposes of this requirement.
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
26898
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
(e) Standard: Building Safety. Except
as otherwise provided in this section,
the hospice must meet the applicable
provisions and must proceed in
accordance with the Health Care
Facilities Code (NFPA 99 and Tentative
Interim Amendments TIA 12–2, TIA 12–
3, TIA 12–4, TIA 12–5 and TIA 12–6).
(1) Chapters 7, 8, 12, and 13 of the
adopted Health Care Facilities Code do
not apply to a hospice.
(2) If application of the Health Care
Facilities Code required under
paragraph (e) of this section would
result in unreasonable hardship for the
hospice, CMS may waive specific
provisions of the Health Care Facilities
Code, but only if the waiver does not
adversely affect the health and safety of
patients.
*
*
*
*
*
(q) The standards incorporated by
reference in this section are approved
for incorporation by reference by the
Director of the Office of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information
Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the
National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html. If any
changes in this edition of the Code are
incorporated by reference, CMS will
publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000.
(i) NFPA 99, Standards for Health
Care Facilities Code of the National Fire
Protection Association 99, 2012 edition,
issued August 11, 2011.
(ii) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(iii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(iv) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(v) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(vi) TIA 12–6 to NFPA 99, issued
March 3, 2014.
(vii) NFPA 101, Life Safety Code,
2012 edition, issued August 11, 2011;
(viii) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ix) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(x) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(xi) TIA 12–4 to NFPA 101, issued
October 22, 2013.
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
(2) [Reserved]
PART 460—PROGRAMS OF ALL
INCLUSIVE CARE FOR THE ELDERLY
(PACE)
9. The authority citation for part 460
continues to read as follows:
■
Authority: Secs. 1102, 1871, 1894(f), and
1934(f) of the Social Security Act (42 U.S.C.
1302 and 1395, 1395eee(f), and 1396u–4(f)).
10. Amend § 460.72 by—
a. Revising paragraphs (b)(1)(i) and
(ii).
■ b. Revising paragraph (b)(2)(ii)
■ c. Removing paragraphs (b)(3) and (4).
■ d. Redesignating paragraph (b)(5) as
paragraph (b)(3).
■ e. Revising newly redesignated
paragraph (b)(3).
■ f. Adding new paragraphs (b)(4), (d),
and (e).
The revisions and addition read as
follows:
■
■
§ 460.72
Physical environment.
*
*
*
*
*
(b) * * *
(1) * * *
(i) A PACE center must meet the
applicable provisions and must proceed
in accordance with the Life Safety Code
(NFPA 101 and Tentative Interim
Amendments TIA 12–1, TIA 12–2, TIA
12–3, and TIA 12–4.)
(ii) Notwithstanding paragraph
(b)(1)(i) of this section, corridor doors
and doors to rooms containing
flammable or combustible materials
must be provided with positive latching
hardware. Roller latches are prohibited
on such doors.
(2) * * *
(ii) In consideration of a
recommendation by the State survey
agency or Accrediting Organization or at
the discretion of the Secretary, may
waive, for periods deemed appropriate,
specific provisions of the Life Safety
Code, which would result in
unreasonable hardship upon a PACE
facility, but only if the waiver will not
adversely affect the health and safety of
the patients.
(3) A PACE center may install
alcohol-based hand rub dispensers in its
facility if the dispensers are installed in
a manner that adequately protects
against inappropriate access.
(4) When a sprinkler system is shut
down for more than 10 hours in a 24hour period, the PACE must:
(i) Evacuate the building or portion of
the building affected by the system
outage until the system is back in
service, or
(ii) Establish a fire watch until the
system is back in service.
*
*
*
*
*
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
(d) Standard: Building Safety. Except
as otherwise provided in this section, a
PACE center must meet the applicable
provisions and must proceed in
accordance with the Health Care
Facilities Code (NFPA 99 and Tentative
Interim Amendments TIA 12–2, TIA 12–
3, TIA 12–4, TIA 12–5 and TIA 12–6).
(1) Chapters 7, 8, 12, and 13 of the
adopted Health Care Facilities Code do
not apply to a PACE center.
(2) If application of the Health Care
Facilities Code required under
paragraph (d) of this section would
result in unreasonable hardship for the
PACE center, CMS may waive specific
provisions of the Health Care Facilities
Code, but only if the waiver does not
adversely affect the health and safety of
patients.
(e) The standards incorporated by
reference in this section are approved
for incorporation by reference by the
Director of the Office of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information
Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the
National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html. If any
changes in this edition of the Code are
incorporated by reference, CMS will
publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000.
(i) NFPA 99, Standards for Health
Care Facilities Code of the National Fire
Protection Association 99, 2012 edition,
issued August 11, 2011.
(ii) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(iii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(iv) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(v) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(vi) TIA 12–6 to NFPA 99, issued
March 3, 2014.
(vii) NFPA 101, Life Safety Code,
2012 edition, issued August 11, 2011;
(viii) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ix) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(x) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(xi) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(2) [Reserved]
E:\FR\FM\04MYR2.SGM
04MYR2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
PART 482—CONDITIONS OF
PARTICIPATION FOR HOSPITALS
11. The authority citation for part 482
continues to read as follows:
■
Authority: Secs. 1102, 1871, and 1881 of
the Social Security Act (42 U.S.C. 1302,
1395hh, and 1395rr), unless otherwise noted.
12. Amend § 482.41 by—
a. Revising paragraphs (b)(1)(i) and ii).
b. Revising paragraph (b)(2).
c. Removing paragraphs (b)(4) and
(b)(5).
■ d. Redesignating paragraphs (b)(6)
through (9) as paragraphs (b)(4) through
(7), respectively.
■ e. Revising newly redesignated
paragraph (b)(7).
■ f. Adding new paragraphs (b)(8), and
(9).
■ g. Redesignating paragraph (c) as
paragraph (d).
■ h. Adding new paragraphs (c) and (e).
The revisions and additions read as
follows:
■
■
■
■
§ 482.41 Condition of participation:
Physical environment.
srobinson on DSK5SPTVN1PROD with RULES2
*
*
*
*
*
(b) * * *
(1) * * *
(i) The hospital must meet the
applicable provisions and must proceed
in accordance with the Life Safety Code
(NFPA 101 and Tentative Interim
Amendments TIA 12–1, TIA 12–2, TIA
12–3, and TIA 12–4.)
(ii) Notwithstanding paragraph
(b)(1)(i) of this section, corridor doors
and doors to rooms containing
flammable or combustible materials
must be provided with positive latching
hardware. Roller latches are prohibited
on such doors.
(2) In consideration of a
recommendation by the State survey
agency or Accrediting Organization or at
the discretion of the Secretary, may
waive, for periods deemed appropriate,
specific provisions of the Life Safety
Code, which would result in
unreasonable hardship upon a hospital,
but only if the waiver will not adversely
affect the health and safety of the
patients.
*
*
*
*
*
(7) A hospital may install alcoholbased hand rub dispensers in its facility
if the dispensers are installed in a
manner that adequately protects against
inappropriate access;
(8) When a sprinkler system is shut
down for more than 10 hours, the
hospital must:
(i) Evacuate the building or portion of
the building affected by the system
outage until the system is back in
service, or
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
(ii) Establish a fire watch until the
system is back in service.
(9) Buildings must have an outside
window or outside door in every
sleeping room, and for any building
constructed after July 5, 2016 the sill
height must not exceed 36 inches above
the floor. Windows in atrium walls are
considered outside windows for the
purposes of this requirement.
(i) The sill height requirement does
not apply to newborn nurseries and
rooms intended for occupancy for less
than 24 hours.
(ii) The sill height in special nursing
care areas of new occupancies must not
exceed 60 inches.
(c) Standard: Building safety. Except
as otherwise provided in this section,
the hospital must meet the applicable
provisions and must proceed in
accordance with the Health Care
Facilities Code (NFPA 99 and Tentative
Interim Amendments TIA 12–2, TIA 12–
3, TIA 12–4, TIA 12–5 and TIA 12–6).
(1) Chapters 7, 8, 12, and 13 of the
adopted Health Care Facilities Code do
not apply to a hospital.
(2) If application of the Health Care
Facilities Code required under
paragraph (c) of this section would
result in unreasonable hardship for the
hospital, CMS may waive specific
provisions of the Health Care Facilities
Code, but only if the waiver does not
adversely affect the health and safety of
patients.
*
*
*
*
*
(e) The standards incorporated by
reference in this section are approved
for incorporation by reference by the
Director of the Office of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information
Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the
National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html. If any
changes in this edition of the Code are
incorporated by reference, CMS will
publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000.
(i) NFPA 99, Standards for Health
Care Facilities Code of the National Fire
Protection Association 99, 2012 edition,
issued August 11, 2011.
(ii) TIA 12–2 to NFPA 99, issued
August 11, 2011.
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
26899
(iii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(iv) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(v) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(vi) TIA 12–6 to NFPA 99, issued
March 3, 2014.
(vii) NFPA 101, Life Safety Code,
2012 edition, issued August 11, 2011;
(viii) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ix) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(x) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(xi) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(2) [Reserved]
PART 483—REQUIREMENTS FOR
STATES AND LONG TERM CARE
FACILITIES
13. The authority citation for part 483
continues to read as follows:
■
Authority: Secs. 1102, 1128I, 1819, 1871
and 1919 of the Social Security Act (42
U.S.C. 1302, 1320a–7, 1395i, 1395hh and
1396r).
§ 483.15
[Amended]
14. In § 483.15, amend paragraph
(h)(4) by removing the reference
‘‘§ 483.70(d)(2)(iv) of this part’’ and by
adding in its place the reference
‘‘§ 483.70(e)(2)(iv)’’.
■ 15. Amend § 483.70 by—
■ a. Revising paragraphs (a)(1)(i) and ii).
■ b. Revising paragraph (a)(2).
■ c. Removing paragraphs (a)(4) and (5).
■ d. Redesignating paragraphs (a)(6)
through (8) as paragraphs (a)(4) through
(6), respectively.
■ e. Revising newly redesignated
paragraph (a)(4).
■ f. Adding new paragraphs (a)(7) and
(8).
■ g. Redesignating paragraphs (b)
through (h) as paragraphs (c) through (i).
■ h. Adding new paragraphs (b) and (j).
The revisions read as follows:
■
§ 483.70
Physical environment.
*
*
*
*
*
(a) * * *
(1) * * *
(i) The LTC facility must meet the
applicable provisions and must proceed
in accordance with the Life Safety Code
(NFPA 101 and Tentative Interim
Amendments TIA 12–1, TIA 12–2, TIA
12–3, and TIA 12–4.)
(ii) Notwithstanding paragraph
(a)(1)(i) of this section, corridor doors
and doors to rooms containing
flammable or combustible materials
must be provided with positive latching
hardware. Roller latches are prohibited
on such doors.
E:\FR\FM\04MYR2.SGM
04MYR2
srobinson on DSK5SPTVN1PROD with RULES2
26900
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
(2) In consideration of a
recommendation by the State survey
agency or Accrediting Organization or at
the discretion of the Secretary, may
waive, for periods deemed appropriate,
specific provisions of the Life Safety
Code, which would result in
unreasonable hardship upon a long-term
care facility, but only if the waiver will
not adversely affect the health and
safety of the patients.
*
*
*
*
*
(4) A long-term care facility may
install alcohol-based hand rub
dispensers in its facility if the
dispensers are installed in a manner that
adequately protects against
inappropriate access.
*
*
*
*
*
(7) Buildings must have an outside
window or outside door in every
sleeping room, and for any building
constructed after July 5, 2016 the sill
height must not exceed 36 inches above
the floor. Windows in atrium walls are
considered outside windows for the
purposes of this requirement.
(8) When a sprinkler system is shut
down for more than 10 hours, the ASC
must:
(i) Evacuate the building or portion of
the building affected by the system
outage until the system is back in
service, or
(ii) Establish a fire watch until the
system is back in service.
(b) Standard: Building safety. Except
as otherwise provided in this section,
the LTC facility must meet the
applicable provisions and must proceed
in accordance with the Health Care
Facilities Code (NFPA 99 and Tentative
Interim Amendments TIA 12–2, TIA 12–
3, TIA 12–4, TIA 12–5 and TIA 12–6).
(1) Chapters 7, 8, 12, and 13 of the
adopted Health Care Facilities Code do
not apply to a LTC facility.
(2) If application of the Health Care
Facilities Code required under
paragraph (b) of this section would
result in unreasonable hardship for the
LTC facility, CMS may waive specific
provisions of the Health Care Facilities
Code, but only if the waiver does not
adversely affect the health and safety of
residents.
*
*
*
*
*
(j) The standards incorporated by
reference in this section are approved
for incorporation by reference by the
Director of the Office of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information
Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the
National Archives and Records
Administration (NARA). For
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html. If any
changes in this edition of the Code are
incorporated by reference, CMS will
publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000.
(i) NFPA 99, Standards for Health
Care Facilities Code of the National Fire
Protection Association 99, 2012 edition,
issued August 11, 2011.
(ii) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(iii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(iv) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(v) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(vi) TIA 12–6 to NFPA 99, issued
March 3, 2014.
(vii) NFPA 101, Life Safety Code,
2012 edition, issued August 11, 2011;
(viii) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ix) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(x) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(xi) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(2) [Reserved]
■ 16. Amend § 483.470 by—
■ a. Revising paragraphs (j)(1)(i) and (ii).
■ b. Adding paragraphs (j)(1)(iii) and
(iv).
■ c. Removing paragraphs (j)(5) and (6).
■ d. Redesignating paragraph (j)(7) as
paragraph (j)(5).
■ e. Revising newly redesignated
paragraph (j)(5).
■ f. Adding paragraph (m).
The revisions and additions read as
follows:
§ 483.470 Condition of participation:
Physical environment.
*
*
*
*
*
(j) * * *
(1) * * *
(i) The facility must meet the
applicable provisions of either the
Health Care Occupancies Chapters or
the Residential Board and Care
Occupancies Chapter and must proceed
in accordance with the Life Safety Code
(NFPA 101 and Tentative Interim
Amendments TIA 12–1, TIA 12–2, TIA
12–3, and TIA 12–4.)
(ii) Notwithstanding paragraph (j)(1)(i)
of this section, corridor doors and doors
to rooms containing flammable or
combustible materials must be provided
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
with positive latching hardware. Roller
latches are prohibited on such doors.
(iii) Chapters 32.3.2.11.2 and
33.3.2.11.2 of the adopted 2012 Life
Safety Code do not apply to a facility.
(iv) Beginning July 5, 2019, an ICF–
IID must be in compliance with Chapter
33.2.3.5.7.1, Sprinklers in attics, or
Chapter 33.2.3.5.7.2, Heat detection
systems in attics of the Life Safety Code.
*
*
*
*
*
(5) Facilities that meet the Life Safety
Code definition of a health care
occupancy. (i) In consideration of a
recommendation by the State survey
agency or Accrediting Organization or at
the discretion of the Secretary, may
waive, for periods deemed appropriate,
specific provisions of the Life Safety
Code, which would result in
unreasonable hardship upon a
residential board and care facility, but
only if the waiver will not adversely
affect the health and safety of the
patients.
(ii) A facility may install alcoholbased hand rub dispensers if the
dispensers are installed in a manner that
adequately protects against
inappropriate access.
(iii) When a sprinkler system is shut
down for more than 10 hours, the ICF–
IID must:
(A) Evacuate the building or portion
of the building affected by the system
outage until the system is back in
service, or
(B) Establish a fire watch until the
system is back in service.
(iv) Beginning July 5, 2019, an ICF–
IID must be in compliance with Chapter
33.2.3.5.7.1, sprinklers in attics, or
Chapter 33.2.3.5.7.2, heat detection
systems in attics of the Life Safety Code.
(v) Except as otherwise provided in
this section, ICF–IIDs must meet the
applicable provisions and must proceed
in accordance with the Health Care
Facilities Code (NFPA 99 and Tentative
Interim Amendments TIA 12–2, TIA 12–
3, TIA 12–4, TIA 12–5 and TIA 12–6).
(A) Chapter 7,8,12 and 13 of the
adopted Health Care Facilities Code
does not apply to an ICF–IID.
(B) If application of the Health Care
Facilities Code required under
paragraph
(j)(5)(iv) of this section would result
in unreasonable hardship for the ICF–
IID, CMS may waive specific provisions
of the Health Care Facilities Code, but
only if the waiver does not adversely
affect the health and safety of clients.
*
*
*
*
*
(m) The standards incorporated by
reference in this section are approved
for incorporation by reference by the
Director of the Office of the Federal
E:\FR\FM\04MYR2.SGM
04MYR2
Federal Register / Vol. 81, No. 86 / Wednesday, May 4, 2016 / Rules and Regulations
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information
Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the
National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html. If any
changes in this edition of the Code are
incorporated by reference, CMS will
publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000.
(i) NFPA 99, Standards for Health
Care Facilities Code of the National Fire
Protection Association 99, 2012 edition,
issued August 11, 2011.
(ii) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(iii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(iv) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(v) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(vi) TIA 12–6 to NFPA 99, issued
March 3, 2014.
(vii) NFPA 101, Life Safety Code,
2012 edition, issued August 11, 2011;
(viii) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ix) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(x) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(xi) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(2) [Reserved]
PART 485—CONDITIONS OF
PARTICIPATION: SPECIALIZED
PROVIDERS
17. The authority citation for part 485
continues to read as follows:
■
Authority: Secs. 1102 and 1871 of the
Social Security Act (42 U.S.C. 1302 and
1395(hh)).
18. Amend § 485.623 by—
a. Revising paragraphs (d)(1)(i) and
(ii).
■ b. Revising paragraph (d)(2).
■ c. Removing paragraphs (d)(5) and (6).
■ d. Redesignating paragraph (d)(7) as
paragraph (d)(5).
■ e. Revising newly redesignated
paragraph (d)(5).
■ f. Adding paragraphs (d)(6), (7), (e),
and (f).
The revisions and additions read as
follows:
srobinson on DSK5SPTVN1PROD with RULES2
■
■
VerDate Sep<11>2014
19:05 May 03, 2016
Jkt 238001
§ 485.623 Condition of participation:
Physical plant and environment.
*
*
*
*
*
(d) * * *
(1) * * *
(i) The CAH must meet the applicable
provisions and must proceed in
accordance with the Life Safety Code
(NFPA 101 and Tentative Interim
Amendments TIA 12–1, TIA 12–2, TIA
12–3, and TIA 12–4.)
(ii) Notwithstanding paragraph
(d)(1)(i) of this section, corridor doors
and doors to rooms containing
flammable or combustible materials
must be provided with positive latching
hardware. Roller latches are prohibited
on such doors.
(2) In consideration of a
recommendation by the State survey
agency or Accrediting Organization or at
the discretion of the Secretary, may
waive, for periods deemed appropriate,
specific provisions of the Life Safety
Code, which would result in
unreasonable hardship upon a CAH, but
only if the waiver will not adversely
affect the health and safety of the
patients.
*
*
*
*
*
(5) A CAH may install alcohol-based
hand rub dispensers in its facility if the
dispensers are installed in a manner that
adequately protects against
inappropriate access.
(6) When a sprinkler system is shut
down for more than 10 hours, the CAH
must:
(i) Evacuate the building or portion of
the building affected by the system
outage until the system is back in
service, or
(ii) Establish a fire watch until the
system is back in service.
(7) Buildings must have an outside
window or outside door in every
sleeping room, and for any building
constructed after July 5, 2016 the sill
height must not exceed 36 inches above
the floor. Windows in atrium walls are
considered outside windows for the
purposes of this requirement.
(i) The sill height requirement does
not apply to newborn nurseries and
rooms intended for occupancy for less
than 24 hours.
(ii) Special nursing care areas of new
occupancies shall not exceed 60 inches.
(e) Standard: Building safety. Except
as otherwise provided in this section,
the CAH must meet the applicable
provisions and must proceed in
accordance with the Health Care
Facilities Code (NFPA 99 and Tentative
Interim Amendments TIA 12–2, TIA 12–
3, TIA 12–4, TIA 12–5 and TIA 12–6).
(1) Chapters 7, 8, 12, and 13 of the
adopted Health Care Facilities Code do
not apply to a CAH.
PO 00000
Frm 00031
Fmt 4701
Sfmt 9990
26901
(2) If application of the Health Care
Facilities Code required under
paragraph (e) of this section would
result in unreasonable hardship for the
CAH, CMS may waive specific
provisions of the Health Care Facilities
Code, but only if the waiver does not
adversely affect the health and safety of
patients.
(f) The standards incorporated by
reference in this section are approved
for incorporation by reference by the
Director of the Office of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information
Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the
National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html. If any
changes in this edition of the Code are
incorporated by reference, CMS will
publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org,
1.617.770.3000.
(i) NFPA 99, Standards for Health
Care Facilities Code of the National Fire
Protection Association 99, 2012 edition,
issued August 11, 2011.
(ii) TIA 12–2 to NFPA 99, issued
August 11, 2011.
(iii) TIA 12–3 to NFPA 99, issued
August 9, 2012.
(iv) TIA 12–4 to NFPA 99, issued
March 7, 2013.
(v) TIA 12–5 to NFPA 99, issued
August 1, 2013.
(vi) TIA 12–6 to NFPA 99, issued
March 3, 2014.
(vii) NFPA 101, Life Safety Code,
2012 edition, issued August 11, 2011;
(viii) TIA 12–1 to NFPA 101, issued
August 11, 2011.
(ix) TIA 12–2 to NFPA 101, issued
October 30, 2012.
(x) TIA 12–3 to NFPA 101, issued
October 22, 2013.
(xi) TIA 12–4 to NFPA 101, issued
October 22, 2013.
(2) [Reserved]
Dated: March 11, 2016.
Andrew M. Slavitt,
Acting Administrator, Centers for Medicare
& Medicaid Services.
Dated: March 30, 2016.
Sylvia M. Burwell,
Secretary, Department of Health and Human
Services.
[FR Doc. 2016–10043 Filed 5–3–16; 8:45 am]
BILLING CODE 4120–01–P
E:\FR\FM\04MYR2.SGM
04MYR2
Agencies
[Federal Register Volume 81, Number 86 (Wednesday, May 4, 2016)]
[Rules and Regulations]
[Pages 26871-26901]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2016-10043]
[[Page 26871]]
Vol. 81
Wednesday,
No. 86
May 4, 2016
Part II
Department of Health and Human Services
-----------------------------------------------------------------------
Centers for Medicare & Medicaid Services
-----------------------------------------------------------------------
42 CFR Parts 403, 416, 418, et al.
Medicare and Medicaid Programs; Fire Safety Requirements for Certain
Health Care Facilities; Final Rule
Federal Register / Vol. 81 , No. 86 / Wednesday, May 4, 2016 / Rules
and Regulations
[[Page 26872]]
-----------------------------------------------------------------------
DEPARTMENT OF HEALTH AND HUMAN SERVICES
Centers for Medicare & Medicaid Services
42 CFR Parts 403, 416, 418, 460, 482, 483, and 485
[CMS-3277-F]
RIN 0938-AR72
Medicare and Medicaid Programs; Fire Safety Requirements for
Certain Health Care Facilities
AGENCY: Centers for Medicare & Medicaid Services (CMS), HHS.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: This final rule will amend the fire safety standards for
Medicare and Medicaid participating hospitals, critical access
hospitals (CAHs), long-term care facilities, intermediate care
facilities for individuals with intellectual disabilities (ICF-IID),
ambulatory surgery centers (ASCs), hospices which provide inpatient
services, religious non-medical health care institutions (RNHCIs), and
programs of all-inclusive care for the elderly (PACE) facilities.
Further, this final rule will adopt the 2012 edition of the Life Safety
Code (LSC) and eliminate references in our regulations to all earlier
editions of the Life Safety Code. It will also adopt the 2012 edition
of the Health Care Facilities Code, with some exceptions.
DATES: This regulation is effective July 5, 2016.
The incorporation by reference of certain publications listed in
the rule is approved by the Director of the Federal Register as of July
5, 2016.
FOR FURTHER INFORMATION CONTACT: Kristin Shifflett, (410) 786-4133.
Danielle Shearer, (410) 786-6617.
SUPPLEMENTARY INFORMATION:
Acronyms
ABHR--Alcohol Based Hand Rubs
ADA--Americans with Disabilities Act
AHJ--Authority Having Jurisdiction
ASC--Ambulatory Surgical Center
ASHRAE--American Society of Heating, Refrigeration, and Air
Conditioning Engineers
CAH--Critical Access Hospital
CDC--Centers for Disease Control and Prevention
CFR--Code of Federal Regulations
CMS--Centers for Medicare & Medicaid
DOJ--Department of Justice
EES--Essential Electrical System
FR--Federal Register
FSES--Fire Safety Evaluation System
GAO--Government Accountability Office
HHS--Department of Health and Human Services
HVAC--Heating, Ventilation, and Air Conditioning
ICF-IID--Intermediate Care Facilities for Individuals with
Intellectual Disabilities
LSC--Life Safety Code
LTC--Long-term Care
NFPA--National Fire Protection Association
OPPS--Outpatient Prospective Payment System
PACE--Programs of All-inclusive Care for the Elderly
RFA--Regulatory Flexibility Act
RIA--Regulatory Impact Analysis
RNHCI--Religious Non-Medical Health Care Institution
TIA--Tentative Interim Amendment
UMRA--Unfunded Mandates Reform Act
WAGD--Waste Anesthetic Gas Disposal System
Definitions
Approved, Automatic Sprinkler System; A fire protection system,
deemed acceptable by the Authority Having Jurisdiction, consisting of
an integrated network of piping designed in accordance with fire
protection engineering standards and including a water supply, a water
control valve, a water flow alarm, a drain, and automatic sprinklers
which are fire suppression or control devices that operate
automatically when their heat-actuated element is heated to its thermal
rating or above, allowing water to discharge over a specified area.
Deck: An exterior floor supported on at least two opposing sides by
an adjacent structure and/or posts, piers, or other independent
supports.
Porch: An outside walking area having a floor that is elevated more
than 8 in. (203 mm) above grade.
Space: A portion of the health care facility designated by the
governing body that serves a specific purpose.
Note: The word ``space'' takes its meaning from the context in
which it is used as it is a definable area, such as a room, toilet
room, storage room, assembly room, corridor, or lobby.
Non-Supervised Automatic Sprinkler System: An automatic sprinkler
system lacking electrical supervisory attachments and; therefore,
unable to provide a distinctive supervisory signal to indicate a
condition that would impair the satisfactory operation of the sprinkler
system.
Supervised Automatic Sprinkler System: An automatic sprinkler
system equipped with electrical supervisory attachments, installed and
monitored for integrity in accordance with NFPA 72, National Fire Alarm
and Signaling Code, that provides a distinctive supervisory signal to
indicate a condition that would impair the satisfactory operation of
the sprinkler system.
Note: For a sprinkler system to be considered supervised as
required by NFPA 101, the supervision must be electrical as
contrasted with supervision via chaining and locking of valves in
the open position as permitted for supervision by NFPA 13.
Supervision in accordance with NFPA 101 involves more than valve
monitoring as any condition that would impair satisfactory operation
of the sprinkler system must provide a supervisory signal.
I. Background
A. Overview
The Life Safety Code (LSC) is a compilation of fire safety
requirements for new and existing buildings, and is updated and
published every 3 years by the National Fire Protection Association
(NFPA), a private, nonprofit organization dedicated to reducing loss of
life due to fire. The LSC regulations adopted by Centers for Medicare &
Medicaid Services (CMS) apply to hospitals, long-term care facilities
(LTC), critical access hospitals (CAHs), ambulatory surgical centers
(ASC), intermediate care facilities for individuals with intellectual
disabilities (ICF-IIDs), hospice inpatient care facilities, programs
for all inclusive care for the elderly (PACE), and religious non-
medical health care institutions (RNHCIs). The Medicare and Medicaid
regulations have historically incorporated these requirements by
reference, along with Secretarial waiver authority. The statutory basis
for incorporating NFPA's LSC into the regulations we apply to Medicare
and, as applicable, Medicaid providers and suppliers is the Secretary
of the Department of Health and Human Services (the Secretary's)
authority to stipulate health and safety regulations for each type of
Medicare and (if applicable) Medicaid-participating facility, as well
as the Secretary's general rulemaking authority, set out at sections
1102 and 1871 of the Social Security Act (the Act).
In our regulations, issued pursuant to the Act, we have stated that
we believe CMS has the authority to grant waivers of some provisions of
the LSC when necessary; for instance, to hospitals under section
1861(e)(9) of the Act, and to LTC facilities at sections 1819(d)(2)(B)
and 1919(d)(2)(B) of the Act. Under our current regulations, the
Secretary may waive specific provisions of the LSC for any type of
facility, if application of our rules would result in unreasonable
hardship for the facility, and if the health and safety of its patients
would not be compromised by such waiver.
We do not consider it always necessary for a facility to be cited
for a
[[Page 26873]]
deficiency before it can apply for or receive a waiver. This is
particularly the case when we have evaluated specific provisions of the
LSC, determined that a waiver would arguably apply to all similarly-
situated facilities with respect to the LSC requirement in question,
and issued a public communication describing the specifics of such a
categorical waiver, including any particular requirements that must be
met in order for the waiver to apply to a facility. Waiver approval in
these instances would be subject to a review of documentation
maintained by the facility, verification of the applicability of the
waiver, and confirmation that the terms and requirements of the waiver
have been implemented by the facility. In most cases such verification
occurs when an onsite survey of the facility is conducted. We plan to
continue this approach, but would like to clarify that in those cases
where we have issued a prior public communication providing for a
categorical waiver, an advance recommendation from a state survey
agency or accrediting organization (as applicable), is not required in
order for a waiver to be granted. We have issued categorical waivers of
LSC requirements when newer editions of the LSC provided equally
effective means of ensuring life safety compared to requirements of
earlier LSC editions. When CMS has evaluated the alternative (such as
examining new fire safety research and technology), and concluded that
the specific alternative would improve or maintain the safety of the
residents or patients of the facility, CMS may defer to newer editions
of the LSC. CMS requires that providers comply with any applicable non-
waived provisions of the version of the LSC referenced in the
categorical waiver.
In addition, the Secretary may accept a state's fire and safety
code instead of the LSC if CMS determines that the protections of the
state's fire and safety code are equivalent to, or more stringent than,
the protections offered by the LSC. Further, the NFPA's Fire Safety
Evaluation System (FSES), an equivalency system, provides alternatives
to meeting various provisions of the LSC, thereby achieving the same
level of fire protection as the LSC. These flexibilities mitigate the
potential unnecessary burdens of applying the requirements of the LSC
to all affected health care facilities.
On January 10, 2003, we published a final rule in the Federal
Register (68 FR 1374) adopting the 2000 edition of the LSC. In that
final rule, we required that all affected providers and suppliers meet
the provisions of the 2000 edition of the LSC, except for certain
specific sections. One of the exceptions to the 2000 edition of the LSC
is the code's use of roller latches on corridor doors in buildings that
are fully protected by a sprinkler system. We believe that roller
latches on corridor doors are a safety hazard under all circumstances,
and prohibit their use on corridor doors in all Medicare and applicable
Medicaid facilities. We also removed references to all previous
editions of the LSC.
In 2002, the Centers for Disease Control and Prevention (CDC)
published on its Web site (https://www.cdc.gov/handhygiene/Guidelines.html) an initial set of hand hygiene guidelines for health
care settings. The guidelines recommended the use of alcohol-based hand
rub (ABHR) dispensers. On September 22, 2006, we published a final rule
(71 FR 55326) to allow certain health care facilities to place ABHR
dispensers in exit corridors under specified conditions. To accommodate
the placement of ABHR dispensers in health care facilities, the NFPA
retroactively amended the 2000 edition of the code. When CMS adopts an
edition of the LSC, it adopts that edition as it existed on the day of
publication of the proposed rule. Since the changes to the 2000 edition
of the LSC occurred after publication of the January 2003 final rule
that adopted the 2000 edition of the LSC, CMS was required to use the
notice and comment rulemaking process to adopt the amendment that the
NFPA made to the code.
The September 2006 final rule also required that LTC facilities, at
a minimum, install battery-powered single station smoke alarms in
resident rooms and common areas if their buildings were not fully
sprinklered, or if the building did not have system-based smoke
detectors. A Government Accountability Office (GAO) report entitled
``Nursing Home Fire Safety: Recent Fires Highlight Weaknesses in
Federal Standards and Oversights'' GAO-04-660, July 16, 2004 (https://www.gao.gov/products/GAO-04-660) examined two LTC facility fires
(Hartford and Nashville) in 2003, that resulted in 31 total resident
deaths. The report examined Federal fire safety standards and
enforcement procedures, as well as results from the fire investigations
of these two incidents. It specifically cited requiring smoke detectors
in these facilities as one way to strengthen the requirements. We
agreed with the GAO findings and added this smoke alarm requirement in
response to the GAO report.
On August 13, 2008, we published a final rule (73 FR 47075) to
require all LTC facilities to install automatic sprinkler systems
throughout their buildings in accordance with the technical provisions
of the 1999 edition of NFPA 13, Standard for the Installation of
Sprinkler Systems, and to test, inspect, and maintain sprinkler systems
in accordance with the technical requirements of the 1998 edition of
NFPA 25, Standard for the Inspection, Testing and Maintenance of Water-
Based Fire Protection Systems. The August 2008 final rule required all
LTC facilities to be equipped with sprinkler systems by August 13,
2013. This rule was also in response to the July 2004 GAO report on
nursing home fire safety. In addition to its findings related to smoke
alarms, the GAO recommended that fire safety standards for
unsprinklered LTC facilities be strengthened and stated that sprinklers
were the single most effective fire protection feature for LTC
facilities.
On May 12, 2014 CMS also published a final rule, ``Part II
Regulatory Provisions to Promote Program Efficiency, Transparency, and
Burden Reduction'' (79 FR 27106) that allows CMS to grant very limited
extensions of the due date for a facility that is building a
replacement facility or undergoing major modifications to unsprinklered
living areas.
On October 24, 2011, we published a proposed rule (76 FR 65891), to
reform hospital and critical access hospital conditions of
participation. Many of the public comments received during the comment
period strongly encouraged CMS to adopt the 2012 edition of the LSC.
The commenters stated that the 2012 edition of the LSC would clarify
several issues and would be beneficial to facilities.
On April 16, 2014, we published a proposed rule (79 FR 21552),
``Fire Safety Requirements for Certain Health Care Facilities'' that
would amend the fire safety standards. We proposed the adoption of the
2012 edition of the NFPA LSC and the elimination of references to
earlier editions of the LSC.
CMS must emphasize that the LSC is not an accessibility code, and
compliance with the LSC does not ensure compliance with the
requirements of the Americans with Disabilities Act (ADA). State and
local government programs and services, including health care
facilities, are required to comply with Title II of the ADA. Private
entities that operate public accommodations such as nursing homes,
hospitals, and social service center establishments are required to
comply with Title III of the ADA. The same accessibility standards
apply regardless of whether health care facilities are covered under
Title II or
[[Page 26874]]
Title III of the ADA.\1\ For more information about the ADA's
requirements, see the Department of Justice's Web site at https://www.ada.gov or call 1-800-514-0301 (voice) or 1-800-514-0383 (TTY).
---------------------------------------------------------------------------
\1\ Facilities newly constructed or altered after March 15, 2012
must comply with the 2010 Standards for Accessible Design (2010
Standards). Facilities newly constructed or altered between
September 15, 2010 and March 15, 2012 had the option of complying
with either the 1991 Standards for Accessible Design (1991
Standards) or the 2010 Standards. Facilities newly constructed
between January 26, 1993 and September 15, 2010, or altered between
January 26, 1992 and September 15, 2010 were required to comply with
the 1991 Standards under Title III and either the 1991 Standards or
the Uniform Federal Accessibility Standards under Title II.
---------------------------------------------------------------------------
B. 2012 Edition of the Life Safety Code
The 2012 edition of the LSC includes new provisions that we believe
are vital to the health and safety of all patients and staff. Our
intention is to ensure that patients and staff continue to experience
the highest degree of fire safety possible. The term ``Patient(s)''
will be globally used throughout this document, and refers to patient,
clients, residents and all other terms used to describe the type of
individuals cared for in each provider type.
The use of earlier editions of the code can become problematic due
to advances in safety and technology, and changes made to each edition
of the code. Newer buildings are typically built to comply with the
newer versions of the LSC because state and local jurisdictions, as
well as non-CMS-approved accreditation programs, often adopt and
enforce newer versions of the code as they become available. Therefore,
a health care facility that is constructed or renovated in 2015 would
likely be required by its state and local authorities to comply with a
more recent edition of the LSC, while also being required to comply
with the 2000 edition of the LSC in order to meet the Medicare and
applicable Medicaid regulatory requirements. Requiring compliance with
two different editions of the LSC at the same time can create
unnecessary conflicts, duplications, and inconsistencies that increase
construction and compliance costs without any fire safety or patient
care benefits. For example, the 2000 edition of the LSC limits ABHRs to
gel form, whereas the 2012 edition of the LSC expands to allow aerosol
and gel ABHRs. Limiting the choice of ABHRs creates barriers to
improved hand hygiene, which has been shown to reduce the number of
health care associated infections. We believe that adopting the 2012
LSC would simplify and modernize the construction and renovation
process for affected health care providers and suppliers, reduce
compliance-related burdens, and allow for more resources to be used for
patient care.
The 2012 edition of the LSC contains a new chapter,--``Building
Rehabilitation.'' This new chapter allows for the application of the
requirements for new construction versus the requirements for existing
construction to vary based on the type and extent of rehabilitation
work being done to a given building. This chapter sets out different
types of building rehabilitation work (that is, repair, renovation,
modification, reconstruction, change of use, change of occupancy and
addition) to which different standards apply.
Buildings that have not received, all pre-construction governmental
approvals before the rule's effective date, or those buildings that
begin construction after the effective date of this regulation, will be
required to meet the New Occupancy chapters of the 2012 edition of the
LSC. Buildings constructed before the effective date of this regulation
will be required to meet the Existing Occupancy chapters of the 2012
edition of the LSC. Any changes made to buildings will be required to
comply with Chapter 43--Building Rehabilitation, which depending on the
changes being made, could require compliance with the new or existing
occupancy chapters. In any instances where mandatory LSC references do
not include existing chapters, such as Chapter 43--Building
Rehabilitation, existing occupancies must ensure buildings and
equipment are in compliance with provisions previously adopted by CMS
at the time they were constructed or installed.
C. Incorporation by Reference
In this final rule we are incorporating by reference the NFPA
101[supreg] 2012 edition of the LSC, issued August 11, 2011, and all
Tentative Interim Amendments issued prior to April 16, 2014; and the
NFPA 99[supreg]2012 edition of the Health Care Facilities Code, issued
August 11, 2011, and all Tentative Interim Amendments issued prior to
April 16, 2014.
(1) NFPA 101, Life Safety Code, 2012 edition, issued August 11,
2011;
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(2) NFPA 99, Standards for Health Care Facilities Code of the
National Fire Protection Association 99, 2012 edition, issued August
11, 2011.
(i) TIA 12-2 to NFPA 99, issued August 11, 2011.
(ii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(iii) TIA 12-4 to NFPA 99, issued March 7, 2013.
(iv) TIA 12-5 to NFPA 99, issued August 1, 2013.
(v) TIA 12-6 to NFPA 99, issued March 3, 2014.
The materials that are incorporated by reference are reasonably
available to interested parties and can be inspected at the CMS
Information Resource Center, 7500 Security Boulevard, Baltimore, MD.
Copies may be obtained from the National Fire Protection Association, 1
Batterymarch Park, Quincy, MA 02169, www.nfpa.org, 1.617.770.3000. If
any changes in this edition of the Code are incorporated by reference,
CMS will publish a document in the Federal Register to announce the
changes.
The NFPA 101[supreg]2012 edition of the LSC (including the TIAs)
provides minimum requirements, with due regard to function, for the
design, operation and maintenance of buildings and structures for
safety to life from fire. Its provisions also aid life safety in
similar emergencies.
The NFPA 99[supreg] 2012 edition of the Health Care Facilities Code
(including the TIAs) provides minimum requirements for health care
facilities for the installation, inspection, testing, maintenance,
performance, and safe practices for facilities, material, equipment,
and appliances, including other hazards associated with the primary
hazards.
Health Care Occupancies
The following are key provisions that appear in the 2012 edition of
the LSC for Chapter 18, ``New Health Care Occupancies,'' and Chapter
19, ``Existing Health Care Occupancies.'' We have provided the LSC
citation and a description of the 2012 requirement at the beginning of
each section discussed.
The 2012 edition of the LSC classifies a ``Health Care Occupancy''
as a facility having 4 or more patients on an inpatient basis. We
proposed that the LSC exception for health care occupancy facilities
with fewer than four occupants/patients would be inapplicable to the
Medicare and Medicaid facilities; all health care occupancies that
provide care to one or more patients would be required to comply with
the relevant requirements of the 2012 edition of the LSC.
[[Page 26875]]
Sections 18.2.3.4(2) and 19.2.3.4(2)--Corridor Projections
This provision requires noncontinuous projections to be no more
than 6 inches from the corridor wall. In addition to following the
requirements of the LSC, health care facilities must comply with the
requirements of the ADA, including the requirements for protruding
objects. The 2010 Standards for Accessible Design (2010 Standards)
generally limit the protrusion of wall-mounted objects into corridors
to no more than 4 inches from the wall when the object's leading edge
is located more than 27 inches, but not more than 80 inches, above the
floor. See Sections 204.1 and 307 of the 2010 Standards, available at
https://www.ada.gov/regs2010/2010ADAStandards/Guidance2010ADAstandards.htm \2\ (``2010 Standards''). This requirement
protects persons who are blind or have low vision from being injured by
bumping into a protruding object that they cannot detect with a cane.
---------------------------------------------------------------------------
\2\ Regardless of which set of ADA Standards for Acessible
Design applied at the time a facility was built or altered, the
requirements for wall-mounted protruding objects are essentially the
same. See Section 4.4 of the 1991 Standards, available at https://www.ada.gov/1991standards/1991standards-archive.html.
---------------------------------------------------------------------------
Although the LSC allows 6-inch projections, under the ADA, objects
mounted above 27 inches and no more than 80 inches high can only
protrude a maximum of 4 inches into the corridor beyond a detectable
surface mounted less than 27 inches above the floor (except for certain
handrails which may protrude up to 4\1/2\''). See section 307 of the
2010 standards for requirements for handrails and post-mounted objects.
CMS intends to provide technical assistance regarding strategies for
how to avoid noncompliance with the ADA's protruding objects
requirement, as well as how to modify non-compliant protruding objects.
Sections 18.7.5.7.2 and 19.7.5.7.2--Recycling
This new provision requires that containers used solely for
recycling clean waste be limited to a maximum capacity of 96 gallons.
If the recycling containers are located in a protected hazardous area,
container size will not be limited.
Sections 18.3.6.3.9.1 and 19.3.6.3.5--Roller Latches
A roller latch is a type of door latching mechanism to keep a door
closed. The 2012 edition of the LSC requires corridor doors to be
provided with a means for keeping the door closed that is acceptable to
the authority having jurisdiction. The LSC permits roller latches
capable of keeping the door fully closed if a force of 5 pounds is
applied at the latch edge or roller latches in fully sprinklered
buildings. However, we proposed not to adopt these standards from the
2012 LSC. Through fire investigations, roller latches have proven to be
an unreliable door latching mechanism requiring extensive maintenance
to operate properly. Many roller latches in fire situations failed to
provide adequate protection to residents in their rooms during an
emergency. Roller latches will be prohibited in existing and new Health
Care Occupancies for corridor doors and doors to rooms containing
flammable or combustible materials. These doors will be required to
have positive latching devices instead.
Sections 18.4.2 and 19.4.2--Sprinklers in High-Rise Buildings
This provision requires buildings over 75' (generally greater than
7 or 8 stories) in height to have automatic sprinkler systems installed
throughout the building. The 2012 LSC allows 12 years from when the
authority having jurisdiction (which in this case is CMS) officially
adopts the 2012 edition of the LSC for existing facilities to comply
with the sprinkler system installation requirement. Therefore, those
facilities that are not already required to do so will have 12 years
following publication of this final rule, which adopts the 2012 LSC, to
install sprinklers in high-rise buildings.
Sections 18.2.2.2.5.2 and 19.2.2.2.5.2--Door Locking
Where the needs of patients require specialized protective measures
for their safety, door-locking arrangements are permitted by this
section. For example, locked psychiatric facilities are designed such
that the entire facility is secure and obstructs patients and others
from improperly entering and exiting. This provision allows interior
doors to be locked, subject to the following requirements: (1) All
staff must have keys; (2) smoke detection systems must be in place; (3)
the facility must be fully sprinklered; (4) the locks are electrical
locks that will release upon loss of power to the device; and (5) the
locks release by independent activation of the smoke detection system
and the water flow in the automatic sprinkler system.
Sections 18.3.2.6 and 19.3.2.6--Alcohol Based Hand Rubs (ABHRs)
This provision explicitly allows aerosol dispensers, in addition to
gel hand rub dispensers. The aerosol dispensers are subject to
limitations on size, quantity, and location, just as gel dispensers are
limited. Automatic dispensers are also now permitted in health care
facilities, provided that the following requirements are met: (1) They
do not release contents unless they are activated; (2) the activation
occurs only when an object is within 4 inches of the sensing device;
(3) any object placed in the activation zone and left in place must not
cause more than one activation; (4) the dispenser must not dispense
more than the amount required for hand hygiene consistent with the
label instructions; (5) the dispenser is designed, constructed and
operated in a way to minimize accidental or malicious dispensing; and
(6) all dispensers are tested in accordance with the manufacturer's
care and use instructions each time a new refill is installed. The
provision further defines prior language regarding ``above or adjacent
to an ignition source'' as being ``within 1 inch'' of the ignition
source.
Sections 18.3.5 and 19.3.5--Extinguishment Requirements
This provision is related to sprinkler system requirements and
requires the evacuation of a building or the instituting of an approved
fire watch when a sprinkler system is out of service for more than 10
hours in a 24-hour period until the system has been returned to
service. We proposed not to adopt this requirement. In its place, we
proposed that a health care occupancy must evacuate a building or
institute an approved fire watch when a sprinkler system is out of
service for more than 4 hours. Based on comments received from the
industry, we are withdrawing our proposal and adopting the requirement
as specified by NFPA for an evacuation of a building or the instituting
of an approved fire watch when a sprinkler system is out of service for
more than 10 hours in a 24-hour period until the system has been
returned to service.
Section 18.3.2.3 and 19.3.2.3--Anesthetizing Locations
This provision requires that anesthetizing locations be protected
in accordance with the 2012 edition of NFPA 99, Health Care Facilities
Code. Separate from the requirements of the NFPA 99, we proposed that
dedicated supply and exhaust systems for windowless anesthetizing
locations must be arranged to automatically vent smoke and products of
combustion to prevent the circulation of smoke originating from within
and outside the operating rooms.
[[Page 26876]]
Sections 18.2.3.4 and 19.2.3.4--Corridors
This provision allows for wheeled equipment that is in use, medical
emergency equipment not in use, and patient lift and transportation
equipment be permitted to be kept in the corridors for more timely
patient care. This provision also allows facilities to place fixed
furniture in the corridors, although the placement of furniture or
equipment must not obstruct accessible routes required by the ADA. See
section 403.5 of the 2010 Standards.
Sections 18.3.2.5.3 and 19.3.2.5.3--Cooking Facilities
Cooking facilities are allowed in a smoke compartment where food is
prepared for 30 individuals or fewer (by bed count). The cooking
facility is permitted to be open to the corridor, provided that the
following conditions are met:
The area being served is limited to 30 beds or less.
The area is separated from other portions of the facility
by a smoke barrier.
The range hood and stovetop meet certain standards--
++ A switch must be located in the area that is used to deactivate
the cook top or range whenever the kitchen is not under staff
supervision.
++ The switch also has a timer, not exceeding 120-minute capacity
that automatically shuts off after time runs out.
Two smoke detectors must be located no closer than 20 feet
and not further than 25 feet from the cooktop or range.
Sections 18.7.5.1 and 19.7.5.1--Furnishings & Decorations
This provision allows combustible decor in any health care
occupancy as long as the d[eacute]cor is flame-retardant or treated
with approved fire-retardant coating that is listed and labeled, and
meet fire test standards. Additionally, decor may not exceed--(1) 20
percent of the wall, ceiling and doors, in any room that is not
protected by an approved automatic sprinkler system; (2) 30 percent of
the wall, ceiling and doors, in any room (no maximum capacity) that is
not protected by an approved, supervised automatic sprinkler system;
and (3) 50 percent of the wall, ceiling and doors, in any room with a
capacity of 4 people (the actual number of occupants in the room may be
less than its capacity) that is not protected by an approved,
supervised automatic sprinkler system.
Sections 18.5.2.3 and 19.5.2.3--Fireplaces
This provision allows direct-vent gas fireplaces in smoke
compartments without the 1 hour fire wall rating. Fireplaces must not
be located inside of any patient sleeping room. Solid fuel-burning
fireplaces are permitted and can be used only in areas other than
patient sleeping rooms, and must be separated from sleeping rooms by
construction of no less than a 1 hour fire resistance wall rating.
Outside Window or Door Requirements
Separate from the requirements of the LSC, we proposed that every
health care occupancy patient sleeping room must have an outside window
or outside door with an allowable sill height not to exceed 36 inches
above the floor with certain exceptions, as follows:
Newborn nurseries and rooms intended for occupancy for
less than 24 hours have no sill height requirements.
Windows in atrium walls shall be considered outside
windows for the purposes of this requirement.
The window sill height in special nursing care areas shall
not exceed 60 inches above the floor.
Ambulatory Health Care Occupancies
The following are key provisions in the 2012 edition of the LSC
from Chapter 20, ``New Ambulatory Health Care Occupancies'' and Chapter
21, ``Existing Ambulatory Health Care Occupancies.'' We have provided
the LSC citation and a description of the requirement at the beginning
of each section discussed.
The 2012 edition of the LSC defines an ``Ambulatory Health Care
Occupancy'' as a facility capable of treating 4 or more patients
simultaneously on an outpatient basis. CMS regulations at 42 CFR 416.44
require that all ASCs meet the provisions applicable to Ambulatory
Health Care Occupancy, regardless of the number of patients served. We
believe that hospital outpatient surgical departments are comparable to
ASCs and thus should also be required to meet the provisions applicable
to Ambulatory Health Care Occupancy Chapters, regardless of the number
of patients served.
Sections 20.3.2.1 and 21.3.2.1--Doors
This provision requires all doors to hazardous areas be self-
closing or close automatically.
Sections 20.3.2.6 and 21.3.2.6--ABHRs
This provision explicitly allows aerosol dispensers, in addition to
gel hand rub dispensers. The aerosol dispensers are subject to
limitations on size, quantity, and location, just as gel dispensers are
limited. Automatic dispensers are also now permitted in ambulatory care
facilities, provided, among other things, that--(1) they do not release
contents unless they are activated; (2) the activation occurs only when
an object is within 4 inches of the sensing device; (3) any object
placed in the activation zone and left in place must not cause more
than one activation; (4) the dispenser must not dispense more than the
amount required for hand hygiene consistent with the label
instructions; (5) the dispenser is designed, constructed and operated
in a way to minimize accidental or malicious dispensing; (6) all
dispensers are tested in accordance with the manufacturer's care and
use instructions each time a new refill is installed. The provision
further defines prior language regarding ``above or adjacent to an
ignition source'' as being ``within 1 inch'' of the ignition source.
Sections 20.3.5 and 21.3.5--Extinguishment Requirements
This provision is related to sprinkler system requirements and
requires the evacuation of a building or the instituting of an approved
fire watch when a sprinkler system is out of service for more than 10
hours in a 24-hour period until the system has been returned to
service. We proposed to replace this requirement with a separate
requirement for evacuation or a fire watch when a sprinkler system is
out of service for more than 4 hours. Based on comments received from
the industry, we are withdrawing our proposal and adopting the
requirement as specified by NFPA for an evacuation of a building or the
instituting of an approved fire watch when a sprinkler system is out of
service for more than 10 hours in a 24-hour period until the system has
been returned to service.
Section 20.3.2.3 and 21.3.2.3--Anesthetizing Locations
This provision requires that anesthetizing locations be protected
in accordance with the 2012 edition of NFPA 99, Health Care Facilities
Code. The 2012 edition of NFPA 99 does not require a smoke control
ventilation system in anesthetizing locations. We proposed a
requirement, separate from the LSC and NFPA 99, to require air supply
and exhaust systems for windowless anesthetizing locations that is
arranged to automatically vent smoke and products of combustion to
prevent the circulation of smoke originating from within and outside
the operating room.
[[Page 26877]]
Residential Board and Care Occupancies
Both the 2000 and 2012 editions of the LSC classify ``board and
care'' as a facility ``used for lodging or boarding of 4 or more
patients not related to the owners or operators by blood or marriage,
for the purpose of providing personal care services.'' We proposed that
the LSC requirements would apply to a facility regardless of the number
of patients served. We note that the only CMS-regulated facilities that
would be subject to these provisions would be intermediate care
facilities for individuals with intellectual disabilities (ICF-IIDs),
which are regulated under 42 CFR part 483, subpart I.
The following are key provisions that appear in the 2012 edition of
the LSC for Chapter 32, ``New Residential Board and Care Occupancies''
and Chapter 33, ``Existing Residential Board and Care Occupancies.'' We
are providing the LSC citation and a description of the requirement at
the beginning of each section discussed.
Section 32.2.3.5.3.2--Sprinklers
This revised provision has been expanded to require that sprinkler
systems be installed in all habitable areas, closets, roofed porches,
balconies and decks of new occupancies.
Sections 32.2.3.5.7 and 33.2.3.5.7--Attics
This new provision requires attics of new and existing facilities
to be sprinklered. For both new and existing board and care facilities,
if the attic is used for living purposes, storage, or housing of fuel
fired equipment, it must be protected with an automatic approved
sprinkler system. If the attic is used for other purposes or is not
used, then it must meet one of the following requirements: (1) Have a
heat detection system that activates the building fire alarm system;
(2) have automatic sprinklers; (3) be of noncombustible or limited-
combustible construction; or (4) be constructed of fire-retardant-
treated-wood.
Section 32.3.3.4.7--Smoke Alarms
This provision will only affect newly constructed facilities.
Approved smoke alarms are required to be installed inside every
sleeping room, outside every sleeping area, in the immediate vicinity
of the bedrooms, and on all levels within a resident unit.
Section 33.3.3.2.3--Hazardous Areas
This provision is for existing facilities with impractical
evacuation capabilities. All hazardous areas must be separated from
other parts of the building by smoke partitions.
Waiver Authority
We proposed to retain our existing authority to waive provisions of
the LSC under certain circumstances, further reducing the exposure to
additional cost and burden for facilities with unique situations. A
waiver may be granted for a specific LSC requirement if we determine
that--(1) the waiver would not adversely affect patient/staff health
and safety; and (2) it would impose an unreasonable hardship on the
facility to meet a specific LSC requirement. In cases where a provider
or supplier has been cited for a LSC deficiency, the provider or
supplier may request a waiver recommendation from its State Survey
Agency or Accrediting Organization (AO) with a CMS-approved Medicare
and applicable Medicaid accreditation program. The State Survey Agency
or AO reviews the request and makes a recommendation to the appropriate
CMS Regional Office. The CMS Regional Office will review the waiver
request and the recommendation and make a final decision. CMS will not
grant a waiver if patient health and safety is compromised.
The LSC recognizes alternative systems, methods, or devices
approved as equivalent by the authority having jurisdiction (AHJ) as
being in compliance with the LSC. CMS, as the AHJ for certification,
will determine equivalency through the waiver approval process.
State Fire Codes
In addition to the proposed waiver option, a state may request that
its state fire safety requirements, imposed by state law, be used in
lieu of the 2012 edition of the LSC. The state must submit the request
to the appropriate CMS Regional Office, and the Regional Office will
forward the request to CMS central office for final determination.\3\
---------------------------------------------------------------------------
\3\ CMS reminds such states that compliance with state fire
safety requirements, like compliance with the LSC, does not ensure
compliance with the ADA requirements.
---------------------------------------------------------------------------
Fire Safety Evaluation System (FSES)
We retain our authority to apply the Fire Safety Evaluation System
(FSES) option within the LSC as an alternative approach to meeting the
requirements of the LSC. This includes the determination of how the
FSES will be applied to each occupancy and which edition of the FSES is
most appropriate to use.
D. 2012 Edition of the Health Care Facilities Code
The 2012 edition of the NFPA 99, ``Health Care Facilities Code,''
addresses requirements for both health care occupancies and ambulatory
care occupancies, and serves as a resource for those who are
responsible for protecting health care facilities from fire and
associated hazards. The purpose of this Code is to provide minimum
requirements for the installation, inspection, testing, maintenance,
performance, and safe practices for health care facility materials,
equipment and appliances. This Code is a compilation of documents that
have been developed over a 40-year period by NFPA, and is intended to
be used by those persons involved in the design, construction,
inspection, and operation of health care facilities, and in the design,
manufacture, and testing of appliances and equipment used in patient
care areas of health care facilities. It provides information on
subjects, for example, medical gas and vacuum systems, electrical
systems, electrical equipment, and gas equipment. The NFPA 99 applies
specific requirements in accordance with the results of a risk-based
assessment methodology. A risk-based approach allows for the
application of requirements based upon the types of treatment and
services being provided to patients or residents rather than the type
of facility in which they are being performed. In order to ensure the
minimum level of protection afforded by NFPA 99 is applicable to all
patient and resident care areas within a health care facility, CMS
proposed the adoption of the 2012 edition of NFPA 99, with the
exception of chapters 7--Information Technology and Communications
Systems for Health Care Facilities; 8--Plumbing; 12--Emergency
Management; and 13--Security Management. In the following section, we
describe the key provisions within the NFPA 99.
The first three chapters of the NFPA 99 address the administration
of the NFPA 99, the referenced publications and definitions.
Chapter 4--Fundamentals
Chapter 4 provides guidance on how to apply NFPA 99 requirements to
health care facilities based upon ``categories'' determined when using
a risk-based methodology.
There are four categories utilized in the risk assessment
methodology, depending on the types of treatment and services being
provided to patients or residents. Section 4.1.1 of NFPA 99
[[Page 26878]]
describes Category 1 as, ``Facility systems in which failure of such
equipment or system is likely to cause major injury or death of
patients or caregivers. . . .'' Section A.4.1.1 provides examples of
what a major injury could include, such as amputation or a burn to the
eye. Section 4.1.2 describes Category 2 as, ``Facility systems in which
failure of such equipment is likely to cause minor injury to patients
or caregivers. . . .'' Section A.4.1.2 describes a minor injury as one
that is not serious or involving risk of life. Section 4.1.3 describes
Category 3 as, ``Facility systems in which failure of such equipment is
not likely to cause injury to patients or caregivers, but can cause
patient discomfort. . . .'' Section 4.1.4 describes Category 4 as,
``Facility systems in which failure of such equipment would have no
impact on patient care. . . .''
Section 4.2 requires that each facility that is a health care or
ambulatory occupancy define its risk assessment methodology, implement
the methodology, and document the results. CMS does not require the
submission of risk assessment methods to CMS. However, CMS, will
confirm that facilities are using risk assessment methodologies when
conducting onsite surveys. We did not propose to require the use of any
particular risk assessment procedure. However, if future situations
indicate the need to define a particular risk assessment procedure, we
would pursue that through a separate notice and comment rulemaking.
Chapter 5--Gas and Vacuum Systems
The hazards addressed in Chapter 5 include the ability of oxygen
and nitrous oxide to exacerbate fires, safety concerns from the storage
and use of pressurized gas, and the reliance upon medical gas and
vacuum systems for patient care. Chapter 5 does not mandate the
installation of any systems; rather, if they are installed or are
required to be installed, the systems will be required to comply with
NFPA 99. Chapter 5 covers the performance, maintenance, installation,
and testing of the following:
Nonflammable medical gas systems with operating pressure
below a gauge pressure of 300 psi;
Vacuum systems in health care facilities;
Waste anesthetic gas disposal systems (WAGD); and
Manufactured assemblies that are intended for connection
to the medical gas, vacuum, or WAGD systems.
Chapter 6--Electrical Systems
The hazards addressed in Chapter 6 are related to the electrical
power distribution systems in health care facilities, and address
issues such as electrical shock, power continuity, fire, electrocution,
and explosions that might be caused by faults in the electrical system.
Chapter 6 covers the performance, maintenance, and testing of the
electrical systems in health care facilities.
Chapter 9--Heating, Ventilation, and Air Conditioning (HVAC)
Chapter 9 requires HVAC systems serving spaces- a portion of the
health care facility designated by the governing body that serves a
specific purpose or providing health care functions to be in accordance
with the American Society of Heating, Refrigeration and Air-
Conditioning Engineers (ASHRAE) Standard 170- Ventilation of Health
Care Facilities (2008 edition) (https://www.ashrae.org).
Chapter 9 does not apply to existing HVAC systems, but applies to
the construction of new health care facilities, and the altered,
renovated, or modernized portions of existing systems or individual
components. Chapter 9 ensures minimum levels of heating, ventilation,
and air conditioning performance in patient and resident care areas.
Some of the issues discussed in Chapter 9 are:
HVAC system energy conservation.
Commissioning.
Piping.
Ductwork.
Acoustics.
Requirements for the ventilation of medical gas storage
and trans-filling areas.
Waste anesthetic gases.
Plumes from medical procedures.
Emergency power system rooms.
Ventilation during construction.
Chapter 10--Electrical Equipment
Chapter 10 covers the performance, maintenance, and testing of
electrical equipment in health care facilities. Much of this chapter
applies to requirements for portable electrical equipment in health
care facilities, but there are also requirements for fixed-equipment
and information on administrative issues.
Chapter 11--Gas Equipment
The hazards addressed in Chapter 11 relate to general fire,
explosions, and mechanical issues associated with gas equipment,
including compressed gas cylinders.
Chapter 14--Hyperbaric Facilities
Chapter 14 addresses the hazards associated with hyperbaric
facilities in health care facilities, including electrical, explosive,
implosive, and fire hazards. Chapter 14 sets forth minimum safeguards
for the protection of patients and personnel administering hyperbaric
therapy and procedures. Chapter 14 contains requirements for hyperbaric
chamber manufacturers, hyperbaric facility designers, and personnel
operating hyperbaric facilities. It also contains requirements related
to construction of the hyperbaric chamber itself and the equipment used
for supporting the hyperbaric chamber, as well as administration and
maintenance. Many requirements in this chapter are applicable only to
new construction and new facilities.
Chapter 15--Features of Fire Protection
Chapter 15 covers the performance, maintenance, and testing of fire
protection equipment in health care facilities. Issues addressed in
this chapter range from the use of flammable liquids in an operating
room to special sprinkler protection. These fire protection
requirements are independent of the risk-based approach, as they are
applicable to all patient care areas in both new and existing
facilities.
Chapter 15 has several sections taken directly from the NFPA 101,
including requirements for the following:
Construction and compartmentalization of health care
facilities.
Laboratories.
Utilities.
Heating, ventilation and air conditioning systems.
Elevators.
Escalators.
Conveyors.
Rubbish Chutes.
Incinerators.
Laundry Chutes.
Fire detection, alarm and communication systems.
Automatic sprinklers and other extinguishing equipment.
Compact storage including mobile storage and maintenance.
Testing of water based fire protection systems.
These sections have requirements for inspection, testing and
maintenance which apply to all facilities, as well as specific
requirements for existing systems and equipment that also apply to all
facilities.
II. Provisions of the Proposed Regulations
This section details the specific regulatory changes for each
affected
[[Page 26879]]
provider and supplier. Due to the similar content and structure of the
regulations for the various providers and suppliers, most of the
information presented repeats for each provider.
1. Religious Nonmedical Health Care Institutions: Condition of
Participation: Life Safety From Fire (Sec. 403.744)
In Sec. 403.744, we proposed to maintain most of the current
provisions for Religious Nonmedical Health Care Institutions (RNHCI)
published in the Federal Register on January 10, 2003 (68 FR 1374),
except if they conflicted with the 2012 LSC and the requirements were
within the provisions detailed in Section I of this preamble regardless
of the number of patients the facility served.
In addition, we proposed to--
Retain the requirements at Sec. 403.744(a)(1)(ii) related
to the prohibition of roller latches in health care facilities. We also
proposed to update the LSC chapter reference from ``19.3.6.3.2
exception number 2'' to ``19.3.6.3.5 numbers 1 and 2 and 19.3.6.3.6
number 2''.
Modify the requirements specific to ABHRs, since most of
the requirements in our regulation are now included in the 2012 edition
of the LSC. Therefore, we proposed to remove the requirements at Sec.
403.744(a)(4)(i), (ii), (iv) and (v).
Retain the requirements at Sec. 403.744(a)(4)(iii)
related to protection against inappropriate access, and redesignate it
at Sec. 403.744(a)(4).
Add a new requirement at Sec. 403.744(a)(5) that required
facilities with sprinkler systems that were out of service for more
than 4 hours in a 24-hour period to evacuate the building or portion of
the building affected by the system outage, or establish a fire watch
until the system is back in service, notwithstanding the lower standard
of the LSC.
Add a new requirement at Sec. 403.744(a)(6) to require
window sills must not exceed 36 inches above the floor.
Retain the requirement at Sec. 403.744(b) related to the
Secretary's waiver authority and state imposed codes. We did not
propose to make any changes to this section.
Remove the requirements at Sec. 403.744(c) related to the
phase-in period for compliance with emergency lighting. In the 2003
final rule, we allowed facilities until March 13, 2006, to upgrade
their emergency lighting equipment. This phase-in period has now
expired and is no longer a necessary regulatory provision.
Add a new Condition of Participation at Sec. 403.745
requiring RNHCIs to comply with the 2012 edition of the NFPA 99.
Chapters 7, 8, 12, and 13 of the NFPA 99 would not apply
to RNHCIs.
Allow for waivers of these provisions under the same
conditions and procedures that we currently use for waivers of
applicable provisions of the LSC.
2. Ambulatory Surgery Centers: Condition for Coverage: Environment
(Sec. 416.44)
In Sec. 416.44, we proposed that all ASCs meet the provisions
applicable to Ambulatory Health Care Centers in the 2012 edition of the
LSC, except as detailed in section I of this preamble, regardless of
the number of patients the facility serves. We also proposed to retain
the provision at Sec. 416.44(b)(2) and (b)(3) related to the
Secretary's waiver authority and state imposed codes. We did not
propose to make any changes to these provisions.
In addition, we proposed to--
Remove the requirements at Sec. 416.44(b)(4) related to
the phase-in period for compliance with emergency lighting. This phase-
in period has now expired and this phase-in provision is no longer a
necessary regulatory provision.
Modify the requirements specific to ABHRs since most of
the requirements are now included in the 2012 edition of the LSC.
Specifically, we proposed to remove the requirements at Sec.
416.44(b)(5)(i), (ii), (iv), (A) through (G), and (v).
Retain the requirements at Sec. 416.44(b)(5)(iii) related
to protection against inappropriate access and redesignate it at Sec.
416.44(b)(4).
Add a new requirement at Sec. 416.44(b)(5) to require a
facility with a sprinkler system that is out of service for more than 4
hours in a 24-hour period to evacuate the building or portion of the
building affected by the system outage, or establish a fire watch until
the system is back in service, notwithstanding the lower standard of
the 2012 LSC.
Add a new requirement at Sec. 416.44(b)(6) to require
facilities with windowless anesthetizing locations to have an air
supply and exhaust system that automatically vents smoke and products
of combustion, prevents recirculation of smoke originating within the
operating room, and prevents the circulation of smoke entering the
system intake.
Add a new paragraph at Sec. 416.44(c) requiring ASCs to
comply with the 2012 edition of the NFPA 99.
Chapters 7, 8, 12, and 13 of the NFPA 99 would not apply
to ASCs.
Allow for waivers of these provisions under the same
conditions and procedures that we currently use for waivers of
applicable provisions of the LSC.
3. Hospice Care: Condition of Participation: Hospices That Provides
Inpatient Care Directly (Sec. 418.110)
In Sec. 418.110, we proposed that all inpatient hospice facilities
meet the provisions applicable to health care occupancies in the 2012
edition of the LSC, with the exceptions discussed in section I of this
preamble, regardless of the number of patients they serve. We note that
this is not a change in requirements, but merely a clarification that,
for LSC purposes, an inpatient hospice facility is considered a health
care occupancy. The LSC does not apply to hospice care that is provided
in a patient's home.
In addition, we proposed to--
Retain the requirements at Sec. 418.110(d)(1)(ii) related
to the prohibition of roller latches in health care facilities. We
proposed to update the LSC chapter reference from ``19.3.6.3.2
exception number 2'' to ``19.3.6.3.5 numbers 1 and 2 and 19.3.6.3.6
number 2.''
Retain the provision at Sec. 418.110(d)(2) and (3)
related to the Secretary's waiver authority and state imposed codes. We
did not propose any changes to these provisions.
Modify the requirements specific to ABHRs because most of
the requirements are now included in the 2012 edition of the LSC. We
proposed to remove the requirements at Sec. 418.110(d)(4)(i), (ii) and
(iv). We proposed to retain the requirements at Sec.
418.110(d)(4)(iii) related to protection against inappropriate access
and redesignate this requirement at Sec. 418.110(d)(4).
Add a new requirement at Sec. 418.110(d)(5) to require a
facility with a sprinkler system that is out of service for more than 4
hours in a 24-hour period to evacuate the building or portion of the
building affected by the system outage, or establish a fire watch until
the system is back in service, notwithstanding the lower standard of
the 2012 LSC.
Add a new requirement at Sec. 418.110(d)(6) to require
that window sills must not exceed 36 inches.
Add a new paragraph at Sec. 418.110(e) requiring hospices
to comply with the 2012 edition of the NFPA 99.
Chapters 7, 8, 12, and 13 of the NFPA 99 not would apply
to hospices.
[[Page 26880]]
Allow for waivers of these provisions under the same
conditions and procedures that we currently use for waivers of
applicable provisions of the LSC.
4. Programs of All-Inclusive Care for the Elderly (PACE): Condition of
Participation: Physical Environment (Sec. 460.72)
In Sec. 460.72, we proposed to retain most of the provisions of
the existing final regulation for Programs of All-Inclusive Care for
the Elderly (PACE) published in the Federal Register on January 10,
2003 (68 FR 1374), regardless of the number of patients the PACE
facility serves. PACE providers will continue to be required to meet
LSC specifications for the type of facilities in which the programs are
located (that is, hospitals and office buildings).
In addition, we proposed to--
Retain the requirements at Sec. 460.72(b)(1)(ii) related
to the prohibition of roller latches in health care facilities. We
proposed to update the LSC chapter reference from ``19.3.6.3.2
exception number 2'' to ``19.3.6.3.5 numbers 1 and 2 and 19.3.6.3.6
number 2.''
Retain the provision at Sec. 460.72(b)(2)(i) and (ii)
related to the Secretary's waiver authority and state imposed codes. We
did not propose to make any changes to these provisions.
Remove the requirement at Sec. 460.72(b)(3) related to
the phase-in period for compliance with emergency lighting. This phase-
in period has now expired and is no longer a necessary regulatory
provision.
Remove the requirements at Sec. 460.72(b)(4) related to
the phase-in period for the prohibition of roller latches in health
care facilities. This phase-in period has now ended and is no longer a
necessary regulatory provision.
Modify the requirements specific to ABHRs because most of
the requirements are now located in the 2012 edition of the LSC. We
proposed to remove the requirements at Sec. 460.72(b)(5)(i), (ii),
(iv) and (v). We proposed to retain the requirements at Sec.
460.72(b)(5)(iii) related to protection against inappropriate access,
and redesignate it to Sec. 460.72(b)(3). We proposed to add a new
requirement at Sec. 460.72(b)(4) to require a facility with a
sprinkler system that is out of service for more than 4 hours in a 24-
hour period to evacuate the building or portion of the building
affected by the system outage, or establish a fire watch until the
system is back in service, notwithstanding the lower standard of the
2012 LSC.
Add a new paragraph at Sec. 460.72(d) to require PACE
centers to comply with the 2012 edition of the NFPA 99.
Chapters 7, 8, 12, and 13 of the NFPA 99 would not apply
to PACEs.
Allow for waivers of these provisions under the same
conditions and procedures that we currently use for waivers of
applicable provisions of the LSC.
5. Hospitals: Condition of Participation: Physical Environment (Sec.
482.41)
In Sec. 482.41, we proposed that the hospitals meet the health
care occupancy provisions of the 2012 edition of the LSC, regardless of
the number of patients the hospital serves. There can be multiple
occupancy classifications within a single hospital. Therefore, multiple
chapters of the code may be applied to a single hospital in accordance
with the Multiple Occupancies provisions in 18.1.3 and 19.1.3. We also
proposed that hospital outpatient surgical departments are comparable
to ASCs and thus should be required to meet the provisions applicable
to Ambulatory Health Care Occupancy chapters, regardless of the number
of patients served.
In addition, we proposed to--
Retain most of the provisions from the existing final
regulation for hospitals published in the Federal Register on January
10, 2003 (68 FR 1374).
Retain the requirements at Sec. 482.41(b)(1)(ii) related
to the prohibition of roller latches in health care facilities. We
proposed to update the LSC chapter reference from ``19.3.6.3.2
exception number 2'' to ``19.3.6.3.5 numbers 1 and 2 and 19.3.6.3.6
number 2.''
Retain the provision at Sec. 482.41(b)(2) and (3) related
to the Secretary's waiver authority and state imposed codes. We did not
propose to make any changes to these provisions.
Remove the requirements at Sec. 482.41(b)(4) related to
the phase-in period for compliance with emergency lighting. This phase-
in period has now ended, and is no longer a necessary regulatory
provision.
Remove the requirements at Sec. 482.41(b)(5) related to
the phase-in period of the prohibition on roller latches in health care
facilities. This phase-in period has now expired and is no longer a
necessary regulatory provision.
Retain the requirements at Sec. 482.41(b)(6) through
(b)(8), and redesignate them at Sec. 482.41(b)(4) through (b)(6),
without changes.
Modify the requirements specific to ABHRs since most of
the requirements are now located in the 2012 edition of the LSC. We
proposed to remove the requirements at Sec. 482.41(b)(9)(i), (ii),
(iv) and (v). We proposed to retain the requirement at Sec.
482.41(b)(9)(iii) related to protection against inappropriate access
and redesignate it at Sec. 482.41(b)(7).
Add a new requirement at Sec. 482.41(b)(8) to require a
facility with a sprinkler system that is out of service for more than 4
hours in a 24-hour period to evacuate the building or portion of the
building affected by the system outage, or establish a fire watch until
the system is back in service, notwithstanding the lower standard of
the 2012 LSC.
Add a new requirement at Sec. 482.41(b)(9) that to
require facilities with windowless anesthetizing locations to have an
air supply and exhaust system that automatically vents smoke and
products of combustion, prevents recirculation of smoke originating
within the surgical suite, and prevents the circulation of smoke
entering the system intake.
Add a new requirement at Sec. 482.41(b)(10) to require a
minimum 36 inch window sill, with certain exceptions for newborn
nurseries, rooms intended for occupancy for less than 24 hours, and
special nursing care areas.
Add a new paragraph at Sec. 482.41(c) requiring hospitals
to comply with the 2012 edition of the NFPA 99.
Chapters 7, 8, 12, and 13 of the NFPA 99 would not apply
to hospitals.
Allow for waivers of these provisions under the same
conditions and procedures that we currently use for waivers of
applicable provisions of the LSC.
6. Long-Term Care Facilities: Condition of Participation: Physical
Environment (Sec. 483.70)
In Sec. 483.70, we proposed to retain most of the provisions of
the existing final regulation for LTC facilities published in the
Federal Register on January 10, 2003 (68 FR 1374) regardless of the
number of residents the facility serves.
In addition, we proposed to--
Retain the requirements at Sec. 483.70(a)(1)(ii) related
to the prohibition of roller latches in health care facilities. We
proposed to update the LSC chapter reference from ``19.3.6.3.2
exception number 2'' to ``19.3.6.3.5 numbers 1 and 2 and 19.3.6.3.6
number 2.''
Retain the provision at Sec. 483.70(a)(2) and (3) related
to the Secretary's waiver authority and state imposed codes. We did not
propose to make any changes to these provisions.
[[Page 26881]]
Remove the requirements at Sec. 483.70(a)(4) related to
the phase-in period for compliance with emergency lighting. This phase-
in period has now expired and is no longer a necessary regulatory
provision.
Remove the requirements at Sec. 483.70(a)(5) related to
the phase-in period for the prohibition of roller latches in health
care facilities. This phase-in period has now ended and is no longer a
necessary regulatory provision.
Modify the requirements specific to ABHRs since most of
the requirements are now included in the 2012 edition of the LSC.
Specifically, we proposed to remove the requirements at Sec.
483.70(a)(6)(i), (ii), (iv) and (v). We proposed to retain the
requirement at Sec. 483.70(a)(6)(iii) related to protection against
inappropriate access, and redesignate it at Sec. 483.70(a)(4).
Retain the requirements at Sec. 483.70(a)(7)(i), (ii),
(iii), (A) and (B) related to installation, inspection, testing and
maintenance of battery operated single station smoke alarms, without
changes. We proposed to redesignate these requirements at Sec.
483.70(a)(5) (i), (ii), (iii) (A) and (B).
Retain the requirements at Sec. 483.70(a)(8)(i) and (ii)
related to the installation of supervised automatic sprinklers and the
testing, inspection and maintenance of the sprinkler system. We
proposed to redesignate these requirements as Sec. 483.70(a)(6)(i) and
(ii), without changes.
Add a new requirement at Sec. 483.70(a)(7) to require a
minimum 36 inch window sill.
Add a new paragraph at Sec. 483.70(b) to require LTC
facilities to comply with the 2012 edition of the NFPA 99.
Chapters 7, 8, 12, and 13 of the NFPA 99 would not apply
to LTC facilities.
Allow for waivers of these provisions under the same
conditions and procedures that we currently use for waivers of
applicable provisions of the LSC.
7. Intermediate Care Facilities for Individuals With Intellectual
Disabilities: Condition of Participation: Physical Environment (Sec.
483.470)
In Sec. 483.470, we proposed to retain most of the provisions of
the existing regulation for ICFs/IID. In accordance with the regulatory
requirements at Sec. 483.470 (j)(2), ICFs/IID will continue to be
permitted to meet either the Residential Board and Care Occupancies
chapter or the Health Care Occupancy chapter of the LSC, as
appropriate, in accordance with the determination of the State survey
agency, regardless of the number of patients the facility serves.
In addition, we proposed to--
Not adopt the provisions at Chapters 32.3.2.11.2 and
33.3.2.11.2, related to ``lockups.'' Lock-ups, as described in the LSC,
are not appropriate under any circumstances for board and care
facilities.
Retain the requirements at Sec. 483.470(j)(1)(ii) related
to the prohibition of roller latches in health care facilities. We
proposed to update the LSC chapter reference from ``19.3.6.3.2
exception number 2'' to ``19.3.6.3.5 numbers 1 and 2 and 19.3.6.3.6
number 2.''
Retain the requirements at Sec. 483.470(j)(2), (3), and
(4).
Remove the requirements at Sec. 483.470(j)(5) related to
the phase-in period for compliance with emergency lighting. This phase-
in period has expired and is no longer a necessary regulatory
provision.
Remove Sec. 483.470(j)(6) related to the phase-in period
for the prohibition of roller latches in health care facilities. This
phase-in period has now ended and is no longer a necessary regulatory
provision.
Retain the provision at Sec. 483.470(j)(7)(A) and (B)
related to the Secretary's waiver authority and state imposed codes. We
proposed to redesignate these provisions at Sec. 483.470(j)(5)(A) and
(B) without change.
Modify the requirements specific to ABHRs since most of
the requirements are now included in the 2012 edition of the LSC.
Specifically, we proposed to remove the requirements at Sec.
483.470(j)(7)(ii)(A), (B), (D) and (E). We proposed to retain the
requirements at Sec. 483.470(j)(7)(ii)(C) related to protection
against inappropriate access, and redesignate it at Sec.
483.470(j)(5)(ii).
Add a new requirement at Sec. 483.470(j)(5)(iii) to
require a facility with a sprinkler system that is out of service for
more than 4 hours in a 24-hour period to evacuate the building or
portion of the building affected by the system outage, or establish a
fire watch until the system is back in service, notwithstanding the
lower standard of the 2012 LSC.
Add a new paragraph at Sec. 483.470(j)(5)(iv) to require
ICF-IIDs to comply with the 2012 edition of the NFPA 99.
Chapters 7, 8, 12, and 13 of the NFPA 99 would not apply
to ICF-IIDs.
Allow for waivers of these provisions under the same
conditions and procedures that we currently use for waivers of
applicable provisions of the LSC.
8. Critical Access Hospitals: Condition of Participation: Physical
Plant and Environment (Sec. 485.623)
In Sec. 485.623, we proposed to retain most of the provisions of
the existing final regulation for Critical Access Hospitals (CAHs)
published in the Federal Register on January 10, 2003 (68 FR 1374),
regardless of the number of patients the facility serves.
In addition, we proposed to--
Retain the requirements at Sec. 485.623(d)(1)(ii) related
to the prohibition of roller latches in health care facilities. We
proposed to update the LSC chapter reference from ``19.3.6.3.2
exception number 2'' to ``19.3.6.3.5 numbers 1 and 2 and 19.3.6.3.6
number 2.''
Retain the requirements at Sec. 485.623(d)(2) through
(d)(4), without any changes.
Remove the requirement at Sec. 485.623(d)(5) related to
the phase-in period for compliance with emergency lighting. This phase-
in period has now expired and is no longer a necessary regulatory
provision.
Remove the requirement at Sec. 485.623(d)(6) related to
the phase-in period of the prohibition on roller latches in health care
facilities. This phase-in period has also expired and is no longer a
necessary regulatory provision.
Modify the requirements specific to ABHRs since most of
the requirements are now incorporated in the 2012 edition of the LSC.
Specifically, we proposed to remove the requirements at Sec.
485.623(d)(7)(i), (ii), (iv) and (v). We proposed to retain the
requirement at Sec. 485.623(d)(7)(iii) related to protection against
inappropriate access and redesignate it at Sec. 485.623(d)(5).
Add a new requirement at Sec. 485.623(d)(6) to require a
facility with a sprinkler system that is out of service for more than 4
hours in a 24-hour period to evacuate the building or portion of the
building affected by the system outage, or establish a fire watch until
the system is back in service, notwithstanding the lower standard of
the 2012 LSC.
Add a new requirement at Sec. 485.623(d)(7) to require
facilities with windowless anesthetizing locations to have an air
supply and exhaust system that automatically vents smoke and products
of combustion, prevents recirculation of smoke originating within the
surgical suite, and prevents the circulation of smoke entering the
system intake.
Add a new requirement at Sec. 485.623(d)(8) to require a
minimum 36 inch window sill, with the exception of
[[Page 26882]]
newborn nurseries, rooms intended for occupancy for less than 24 hours,
and special nursing care areas. Windows in atrium walls are considered
outside windows for the purposes of this provision.
Add a new paragraph at Sec. 485.623(e) requiring CAHs to
comply with the 2012 edition of the NFPA 99.
Chapters 7, 8, 12, and 13 of the NFPA 99 would not apply
to CAHs.
Allow for waivers of these provisions under the same
conditions and procedures that we currently use for waivers of
applicable provisions of the LSC.
III. Analysis of and Responses to Public Comments
We received over 362 public comments concerning the LSC proposed
rule, ``Fire Safety Requirements for Certain Health Care Facilities''
(79 FR 21552), which this rule is finalizing. The majority of the
comments were from medical societies, hospital associations, hospitals,
medical centers, LTC facilities, and advocate groups for different
provider types. The remaining comments were from individual physicians,
nurses, facility engineers, and private citizens. A summary of the
major issues and our responses follow:
LSC--Health Care Occupancies
We note that only the following CMS-regulated facilities would be
subject to these comments, unless otherwise specified: Hospitals, CAHs,
LTC facilities, hospices, RNHCIs, and PACE facilities.
Comment: One commenter recommended adding language to the LTC
requirements at Sec. 483.70, similar to other provider sections, about
establishing a firewatch or evacuating a building when a sprinkler
system is out of service for more than 4 hours in a 24 hour period. The
commenter stated that adding this requirement to the LTC regulations
would provide protection for the residents of nursing homes when the
sprinkler system is out of service.
Response: We thank the commenter for their comment. We agree that
requiring additional safety measures when a sprinkler system is out of
service for a significant amount of time is important in the LTC
facility environment. We originally intended to include this regulatory
requirement in the proposed rule; however, it was inadvertently left
out of regulations text. We would like to clarify that we have removed
the 4 hour requirement and are now following the LSC requirement of
implementing a fire watch or building evacuation if the sprinkler
system is out for more than 10 hours in a 24-hour period. We have made
the appropriate correction in this final rule, and have included the
appropriate language in the regulation text at Sec. 483.70(a)(8).
Comment: One commenter stated that the proposed rule does not
address whether a hospital that is not fully sprinklered and provides
swing beds needs to meet the more stringent requirements from S & C-13-
55-LSC that applies to hospitals.
Response: The survey and certification memorandum that the
commenter references is related to the requirements for the
installation and maintenance of automatic sprinkler systems in LTC
facilities. Swing beds are not considered to be LTC facilities. Rather,
swing beds are part of a hospital or CAH and must meet the LSC
provisions applicable to those facility-types. Therefore, swing beds
are only required to meet certain specified regulations for LTC
facilities, not including the LTC facility sprinkler system
requirements.
Comment: CMS solicited public comment to determine if a phase-in
period of 12 years is enough time for facilities to install fully
compliant sprinkler systems in high-rise buildings, and asked whether
other provider types are, or may be, located in a high-rise building.
We received very few responses to this solicitation. The majority of
the commenters who responded stated that 12 years was enough time to
fully sprinkler a high-rise healthcare facility, and some commenters
stated that 12 years was more than enough time. We did not receive any
comments stating that this was not enough time to install sprinkler
systems in high-rise buildings. Commenters also stated that ambulatory
care and residential board and care occupancies may also be located
within high-rise hospital buildings.
Response: We agree with commenters that 12 years is an appropriate
phase-in period, and we are finalizing this proposal with a phase-in
period of 12 years from the publication date of this rule. We thank the
commenters for the input on other occupancy types that could be located
in high-rise buildings. Since these occupancy types are located in
hospital buildings, we have already accounted for them in our total
number of high-rise hospital buildings.
Comment: One commenter asked whether an alternative care setting
used to provide services to PACE participants would be required to meet
the ABHR requirements and the sprinkler system outage requirement.
Response: All PACE center facilities are required to meet the
requirements found at 42 CFR 460.72, ``Physical Environment''. This
includes meeting all the requirements for the specific occupancy type
they fall under within the LSC. This requirement also applies to the
type of setting in which a center is located, which would include
alternative care settings.
Comment: Some commenters have expressed concern regarding cooking
facilities that are open to the corridor. One commenter did not support
cooking facilities being open to the corridor and believes that it
could increase the number of fires in these facilities due to misuse.
Other commenters supported having cooking facilities that are open to
the corridor and believed it would promote person-centered care and
make for a more home-like atmosphere. A few commenters suggested
changes to this requirement, including--
Requiring that an operational exhaust hood for the cooking
facility should not contribute to nor create an egress corridor return
air plenum (an air pressure differential between different parts of a
building);
Requiring that the activate/deactivate switch be hidden
from view;
Requiring that staff must be present when a range hood or
stovetop is in use; and
Requiring that cooking facilities be screened off when not
in use to prevent resident access.
Response: We appreciate the suggestions concerning cooking
facilities in LTC facilities; however we feel that the LSC includes
many requirements to make sure that cooking facilities are safe. All
facilities are ultimately responsible for assuring the safety of all
residents at all times, and they may choose to implement additional
safety precautions, such as those described above, to further assure
safety. Since other fire safety standards prohibit the use of a
corridor as a plenum in the facility ventilation system, the
introduction of a cooking exhaust fan would need to be accounted for in
the design and not create a corridor plenum situation.
Comment: One commenter suggested that, in addition to installing
sprinklers in existing high-rise health care occupancies, we should
also require existing non high-rise health care occupancies to install
sprinkler systems throughout their buildings.
Response: While we encourage all facilities to install sprinklers,
there is not enough evidence for CMS to support requiring all
facilities to be retrofitted for sprinklers. In the event that the NFPA
should incorporate a requirement for universal sprinklers into a future
edition of the LSC, we would strongly consider adopting such a change.
[[Page 26883]]
Comment: Some commenters stated that medical equipment should not
be permanently fixed in the corridors. This could present a safety
issue during a fire or evacuation and also makes the corridor smaller
in size.
Response: We follow the LSC requirement for medical equipment in
the corridors, which allows any equipment that is in use, including
medical emergency equipment and patient lift and transportation
equipment to be permitted to be kept in the corridors for more timely
patient care. Facilities may place fixed furniture in the corridors,
although the placement of furniture or equipment must not obstruct
accessible routes required by the ADA. The potential risks of this
change are low because the LSC has shifted to a ``defend in place''
approach that does not rely upon evacuation as the primary means of
fire safety.
Comment: One commenter suggested that CMS only permit decorations
in rooms that have sprinklers in them. Furthermore, the commenter
stated that, with such sprinkler protection, there would not be a need
to mandate a maximum percentage of space that could be covered by
decorations.
Response: The NFPA, through its committee of experts and consensus
process, determined that decorations may not exceed--(1) 20 percent of
the wall, ceiling and doors, in any room that is not protected by an
approved automatic sprinkler system; (2) 30 percent of the wall,
ceiling and doors, in any room that is not protected by an approved,
supervised automatic sprinkler system; and (3) 50 percent of the wall,
ceiling and doors, in any room with a capacity of 4 people (the actual
number of occupants in the room may be less than its capacity) that is
not protected by an approved, supervised automatic sprinkler system. We
believe that it is appropriate to adopt these consensus standards. We
also note that the health care occupancy type that is most likely to
have a significant amount of room d[eacute]cor is a LTC facility, given
that patients reside in such facilities for longer periods of time, and
that all LTC facilities are required to have sprinklers installed
throughout their buildings.
Comment: One commenter recommended that two smoke detectors be
located no closer than 20 feet and not further than 25 feet from a
fireplace.
Response: There are currently no requirements for smoke detectors
within a certain distance of a fireplace. If a facility wants to add
additional smoke detectors closer to fireplaces they are free to do so.
An electrically supervised (connected to the facility fire alarm panel)
carbon monoxide detector is required in the room containing the
fireplace to increase the level of safety for the residents or patients
in the facility. We believe that the current requirements for
sprinklers and smoke detectors are sufficient to assure resident
safety, particularly because fireplaces are only in open areas and not
permitted in resident rooms. The health care occupancy type that is
most likely to have a fireplace is a LTC facility, because there are
more options for the location of fireplaces in LTC facilities, making
the facilities feel more home-like. All LTC facilities should be fully
sprinklered, with smoke detectors in designated areas of the
facilities, such as corridors and resident sleeping areas.
LSC--ASC
We note that the only CMS-regulated facilities that would be
subject to these comments would be ambulatory surgical centers, which
are regulated under 42 CFR part 416.
Comment: One commenter believes that we should allow grandfathering
for ASCs that meet previous editions of the LSC. The commenter states
that trying to modify an existing facility to meet provisions in the
2012 edition of the LSC would have significant cost implications for
existing ASCs, and may cause ASCs to close.
Response: For existing ASCs, most provisions in the 2012 edition of
the LSC are similar to past editions. Furthermore, existing facilities
in compliance with previous editions of the LSC are not required to
upgrade to a later edition of the LSC for certain provisions, unless
there is a building renovation, which could require compliance with new
occupancy chapters. In addition, an ASC may also request a waiver for a
specific provision of the LSC, further reducing the exposure to
additional costs and burden for ASCs with unique situations that can
justify the application of waivers and will not endanger the health and
safety of patients. A waiver may be granted for a specific LSC
requirement if we determine: (1) The waiver would not adversely affect
patient and staff health and safety; and (2) it would impose an
unreasonable hardship on the facility to meet a specific LSC
requirement.
Comment: One commenter suggested an increase to Medicare
reimbursements to freestanding ASCs, stating that the current
reimbursement model is not sufficient.
Response: We thank the commenter for this comment; however,
reimbursement rates are beyond the scope of this rule. We recommend
submitting such comments separately to CMS or commenting on the next
Outpatient Prospective Payment System/Ambulatory Surgical Centers
(OPPS/ASC) proposed rule.
LSC--Board & Care
We note that the only CMS-regulated facilities that would be
subject to these comments would be intermediate care facilities for
individuals with intellectual disabilities (ICF-IIDs), which are
regulated under 42 CFR part 483, subpart I.
Comment: One commenter expressed concern about a process that
permits board and care occupancies to assess their own evacuation
capacity. The commenter notes that facilities have strong incentive to
overestimate their evacuation capability in order to avoid more
stringent requirements. The commenter believes that this provision
would undermine CMS' efforts to improve safety.
Response: CMS looks at the assessment of evacuation capabilities as
part of the survey process to verify the accuracy of the self-
evaluation. CMS requires surveyors to independently determine the
evacuation difficulty score at each survey and use the determined
evacuation difficulty score to perform the survey.
Comment: CMS solicited comments regarding whether or not CMS should
require existing facilities to install smoke alarms in accordance with
section 9.6.2.10, which would require the addition of smoke alarms
inside sleeping rooms, outside every sleeping area, in the immediate
vicinity of the bedrooms, and on all levels within the resident units.
The commenters who responded to this solicitation unanimously agreed
that CMS should not require existing residential board and care
facilities to install smoke alarms inside sleeping rooms, outside every
sleeping area, in the immediate vicinity of the bedrooms, and on all
levels within the resident units. All of the commenters believed that
it would be an undue burden, and suggested that, in order for them to
meet this requirement, a payment rate adjustment would be in order.
Response: We agree that a regulation to require smoke alarms is not
necessary at this time, as there is not enough evidence for us to make
it a requirement to upgrade existing facilities. We strongly encourage
existing residential board and care facilities to install smoke alarms
inside sleeping rooms, outside every sleeping area, in the immediate
vicinity of the bedrooms, and on all levels within the resident units
to provide an additional level of safety. With regards to any payment
rate adjustment, we remind commenters that
[[Page 26884]]
payment rates are not within the scope of this rule, but recommend
submitting comments on such issues separately to CMS.
Comment: The LSC requires newly constructed residential board and
care occupancies to install sprinklers in habitable areas, closets,
roofed porches, balconies and decks. In the proposed rule, CMS
recommended that existing facilities also install sprinklers in the
same areas. Commenters stated that CMS should continue to recommend,
but not require, sprinklers for existing residential board and care.
The commenters also stated that if CMS were to require the installation
of sprinklers in those areas that they would need to have at least a 5
year phase-in period, and that a payment rate adjustment would be in
order for affected facilities.
Response: We thank the commenters for their comments regarding this
topic. We would like to clarify that sprinklers are only required for
new residential board and care construction and existing facilities
rated as impractical evacuation capability. The facility itself
determines their evacuation capability, and must ensure that the
appropriate safety protections are in place to protect the patients and
staff within the building, if they are determined to have an
impractical evacuation capabilities. CMS regulations require the use of
NFPA 101A, Guide on Alternative Approaches to Life Safety, 2010
Edition, Chapter 6, Evacuation Capability Determination for Board and
Care Occupancies to determine the evacuation difficulty index. CMS
continues to recommend that existing facilities install sprinklers in
habitable areas, closets, roofed porches, balconies and decks as an
additional safety precaution. Decks being an exterior floor supported
on at least two opposing sides by an adjacent structure and/or posts,
piers, or other independent supports and, porches being an outside
walking area having a floor that is elevated more than 8 in. (203 mm)
above grade. With regards to any payment rate adjustment, we remind
commenters that payment rates are not within the scope of this rule,
but recommend submitting such comments separately to CMS.
Comment: A few commenters expressed concern with having to install
sprinklers in attics used for living purposes, storage, or housing of
fuel-fired equipment. Commenters also expressed concern with having to
install either a heat detection system that activates the building fire
alarm, or having automatic sprinklers, or constructing attics of
noncombustible or limited-combustible construction or constructing
attics of fire-retardant-treated-wood if the attic is used for other
purposes. The commenters stated that compliance with this provision
would be expensive and possibly warrant a payment rate adjustment. The
commenters requested a minimum 5-year phase-in period to install new
protection systems in attics.
Response: A 5-year phase-in period is, we believe, significantly
more time than is actually needed to meet this requirement. According
to the information gathered by CMS from the installation of sprinklers
in LTC facilities requirement, which was required to be in compliance
by August 13, 2013, most LTC facilities were able to install sprinklers
throughout their entire buildings in 5 years. Attics have much less
square footage than an entire building. We believe that 3 years from
the effective date of this rule would be an ample amount of time to
come into compliance with this requirement, therefore, we are
finalizing a 3-year phase-in period. With regards to any payment rate
adjustment, we remind commenters that payment rates are not within the
scope of this rule, but recommend submitting such comments separately
to CMS.
Comment: One commenter requested additional explanation regarding
our proposed exclusion of the lock-up provisions contained within the
board and care occupancy chapters of the LSC. The commenter proposed an
alternative to this exclusion, which would allow lock-ups while
requiring a specific staffing ratio requirement.
Response: Lock-ups are incidental use areas where occupants are
restrained and such occupants are mostly incapable of self-preservation
because of security measures not under the occupants' control. Lock-ups
are prohibited in Medicare and Medicaid participating ICF-IID
facilities. The health and safety regulations for ICF-IIDs at 42 CFR
483.450 effectively prohibit the use of lock-up spaces as described in
the LSC; therefore, there should be no lock-up space in the building.
LSC--General
Comment: Some commenters questioned whether Tentative Interim
Amendments (TIAs) that have been written with regards to the NFPA 101
and NFPA 99 apply, since some of them were published after CMS
published the proposed rule.
Response: Because the TIAs are considered a component of the LSC,
the following TIAs issued prior to the publication of the proposed rule
on April 16, 2014, will apply to all facilities. We have also included
language in the final regulations text to this effect. The following
TIAs will apply:
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(v) TIA 12-2 to NFPA 99, issued August 11, 2011.
(vi) TIA 12-3 to NFPA 99, issued August 9, 2012.
(vii) TIA 12-4 to NFPA 99, issued March 7, 2013.
(viii) TIA 12-5 to NFPA 99, issued August 1, 2013.
(ix) TIA 12-6 to NFPA 99, issued March 3, 2014.
Comment: Some commenters agree with the continued prohibition of
roller latches in facilities, as they are a safety concern. However,
some commenters stated that some doors are not required to latch (that
is, toilet rooms, bathrooms) and that roller latches should be allowed
on those particular doors with no penalty. A few commenters also
discussed the importance of roller latches in psychiatric units. Those
commenters stated that roller latches have limited uses on psychiatric
units to address patients barricading themselves in their rooms or
using hanging points (on the levers) for potential suicides.
Response: CMS would like to clarify that roller latches are
prohibited on all corridor doors. However, doors to toilet rooms,
bathrooms, shower rooms, sink closets, and similar auxiliary spaces
that do not contain flammable or combustible materials would be allowed
to have roller latches. We do not believe that permitting the use of
roller latches in auxiliary spaces presents a danger to patients or
staff. Therefore, we have revised the proposed regulatory requirement
throughout this rule to clarify this distinction. We note that this
requirement is different than the 2012 LSC requirement for door
latching.
Comment: A few commenters expressed concern with Chapter 43,
``Renovation'', of the NFPA 101. The commenters suggested that the date
of submission of construction plans to the State for plan review should
be the ``trigger'' to apply chapter 43. They also stated that
facilities have no control over when plans are actually reviewed; for
example, a building may be designed under the current 2000 NFPA 101
code, but may not be approved until after the final publication of this
rule, which means they would have to meet the
[[Page 26885]]
2012 NFPA 101 code. Commenters also asked CMS to define ``constructed''
in reference to determining whether a building is consider new or
existing.
Response: Buildings that have not yet received all pre-construction
governmental approvals required by the jurisdictions in which the
building is to be built before the rule's effective date, or those
buildings that begin construction after the effective date of this
regulation, would be required to meet the New Occupancy chapters of the
2012 edition of the LSC. While we share the commenter's concern
regarding plans that may be under review for a lengthy period of time,
we do not believe that it is in the best interest of patient and staff
safety to permit constructing of a building that does not meet the
codes that are effective as of the day that construction begins.
Comment: One commenter suggested that hospitals and ASCs should be
required to test their emergency generators when they are disconnected
from the normal utility.
Response: Facilities are required to test their load emergency
power systems on a monthly basis, per the requirements of section
8.4.1, 2010 edition of NFPA 110, Standard for Emergency and Standby
Power Systems.
Comment: Some commenters suggested that CMS should provide training
for surveyors and providers regarding the new codes, updated guidance,
and forms. One commenter suggested that CMS not only provide training
for State fire authorities, but also for architects, engineers, and
building officials.
Response: CMS agrees that training is very important, and does
provide training for state surveyors who work with CMS to enforce these
regulations. However, we do not provide training for any provider/
supplier type for any health and safety rules, including those related
to the LSC. We encourage providers/suppliers, architects, engineers or
building officials to contact the NFPA and their relevant industry
associations to identify their specific training needs and appropriate
offerings that may address those needs with regards to the LSC.
Comment: Many commenters support the adoption of the 2012 NFPA 101
LSC. However, the majority of those commenters also stated that CMS
should adopt the 2012 NFPA 101 in its entirety, without any changes to
the provisions.
Response: Through our surveys, comments, and experience, we have
determined that for the health and safety of patients and staff we
could not adopt the LSC in its entirety. We believe that the provisions
that we have not adopted are not appropriate for Medicare and Medicaid
providers and suppliers. For example, we continue to prohibit roller
latches on corridor doors because, in our view, they present a safety
hazard. Also, we are not adopting the provision regarding lock-ups
because lock-ups are prohibited in the ICF-IIDs regulations, separate
from the LSC. This practice is permitted under the National Technology
Transfer and Advancement Act (https://www.gpo.gov/fdsys/pkg/PLAW-104publ113/pdf/PLAW-104publ113.pdf), which does not mandate that we use
an entire code without exceptions if we determine it is impractical or
unnecessary to do so.
Comment: Several commenters requested CMS to revise the rule to
allow health care facilities to choose other codes that are nationally
recognized, such as the International Building Code and International
Fire Code. The commenters asserted that referencing only the NFPA's LSC
creates conflict for many jurisdictions that enforce other equivalent
or more stringent fire and life safety requirements. The commenters
further stated that, by not referencing other applicable codes, CMS
favors one code to the detriment of other codes.
Response: We continue to specifically cite the LSC because under
sections 1819(d)(2)(B) and 1919(d)(2)(B) of the Act, nursing homes must
meet the provisions of ``such edition (as specified by the Secretary in
regulation) of the LSC of the National Fire Protection Association . .
. . '' To avoid confusion, and to be consistent for all provider types,
we require the LSC for all facilities. This is especially applicable
for facilities with mixed occupancies. For example, a health care
facility's west wing could be a nursing home while the rest of the
facility is a hospital. It would be impractical as well as burdensome
for the facility to follow the LSC for the nursing home and another
health and safety code for the hospital. The regulation reflects this
by requiring a single code for all health care facilities. The NFPA and
the IBC organizations try to align their respective requirements as
much as possible and the 2012 LSC is a reflection of that effort. We
also note that jurisdictions are permitted to enforce more stringent
requirements on top of those required by the Federal LSC requirements.
Comment: Some commenters requested CMS to adopt updated versions of
the LSC more quickly in the future. One commenter requested that CMS
should adopt any updated version of the LSC within 90 days of the LSC
publication.
Response: We cannot adopt the LSC within 90 days of the LSC
publication because we are required to give notice to the public that
we are proposing to revise a regulation. Once we notify the public of
the proposal, the public must have the opportunity to comment on the
revisions, and we must respond to the comments before the update
becomes final and legally enforceable. We do review each edition of the
NFPA 101 and NFPA 99 every 3 years to see if there are any significant
provisions that we need to adopt and will continue to do so. We have
reviewed the 2015 edition of the LSC and do not feel that there are any
significant provisions that need to be addressed at this time.
Comment: Many commenters have suggested that CMS develop a process
to be able to permit a facility to apply for a waiver prior to being
cited for a deficiency. The commenters stated that it is currently
standard practice for CMS to decline to review any requests for waivers
filed before there has been a deficiency cited during a survey.
Response: We agree and have implemented a process to approve
categorical waivers. We do not consider it always necessary for a
facility to be cited for a deficiency before it can apply for or
receive a waiver. This is particularly the case when we have evaluated
specific provisions of the LSC, determined that a waiver would apply to
all similarly-situated facilities with respect to the LSC requirement
in question, and issued a public communication describing the specifics
of such a categorical waiver, including any particular requirements
that must be met in order for the waiver to apply to a facility.
Facilities may still submit requests for non-categorical waivers, which
is currently done after a citation of a deficiency is found on a fire
safety survey. The waiver request includes the reason why the waiver of
a specific life safety requirement cannot be complied with, and is
submitted as part of the facility Plan of Correction of Deficiencies
found on the survey to the State Agency or Regional Office for review
and approval/disapproval by the CMS Regional Office. For example, CMS
released the following Survey & Cert (S&C) Memos on categorical
waivers, and the application process:
April 19, 2013--S&C: 13-25: Relative Humidity (RH): Waiver of
LSC Anesthetizing Location Requirements; Discussion of Ambulatory
Surgical Center (ASC) Operating Room Requirements https://www.cms.gov/
Medicare/Provider-Enrollment-and-
[[Page 26886]]
Certification/SurveyCertificationGenInfo/Downloads/Survey-and-Cert-
Letter-13-25.pdf.
August 30, 2013--S&C: 13-58: 2000 Edition National Fire
Protection Association (NFPA) 101[supreg] LSC Waivers https://www.cms.gov/Medicare/Provider-Enrollment-and-Certification/SurveyCertificationGenInfo/Downloads/Survey-and-Cert-Letter-13-58.pdf.
September 26, 2014--S&C: 14-46 Categorical Waiver for Power
Strips Use in Patient Care Areas https://www.cms.gov/Medicare/Provider-Enrollment-and-Certification/SurveyCertificationGenInfo/Downloads/Survey-and-Cert-Letter-14-46.pdf.
Comment: One commenter expressed concern with the proposal that
facilities maintain antifreeze in their sprinkler systems in certain
proportions. The commenter recommended that CMS withdraw this
requirement, or reconsider its inclusion, until products become
available which do not require more than 50 percent antifreeze (in
compliance with the proposed rule), but which would still keep the
sprinkler systems from freezing.
Response: Where traditional antifreeze solutions for existing
systems remain an option, consideration should be given to alternatives
to using antifreeze. Antifreeze is not required to prevent the freezing
of systems. Owners should investigate alternative methods to prevent
the freezing of wet pipe systems in environments or locations that may
be subject to freezing.
Comment: A few commenters suggested that CMS allow facilities the
opportunity to apply for a waiver rather than install sprinklers if
they can show that staff and patients can be quickly evacuated or that
they offer the same level of protection without the sprinklers.
Response: Sprinklers are considered to be a basic level of
protection for new and certain rehabilitated buildings, and we do not
believe that it would be in the best interest of building occupants to
waive these sprinkler requirements. Furthermore, we only require
universal retrofitting to add sprinklers in high-rise health care
occupancies, LTC facilities, in the attics of board and care
facilities. Impractical evacuation capability facilities are all
required to be protected throughout by an approved automatic sprinkler
system. There is strong evidence that sprinklers in these particular
environments are an essential fire safety feature; therefore we do not
believe it is in the best interest of patients and staff to waive these
requirements under any circumstances. https://www.facilitiesnet.com/firesafety/article/Fire-Safety-Facilities-Management-Fire-Safety-Feature-1620.
Comment: Some commenters expressed concern with the use of the term
``inappropriate access'' in regards to the placement of ABHRs. The
commenters requested clarification of what is meant by the regulatory
requirement that dispensers are installed in a manner that adequately
protects against inappropriate access.
Response: As stated in the ABHR final rule published in September
22, 2006 (71 FR 55326), there are certain patients or resident
populations, such as residents of dementia wards, who may misuse ABHR
solutions, which are both toxic and flammable. As a toxic substance,
ABHR solutions are very dangerous if they are ingested, placed in the
eyes, or otherwise misused. As a flammable substance, ABHR solutions
could be used to start fires that endanger lives and destroy property.
Due to disability or disease, some patients are more likely to harm
themselves or others by inappropriately using ABHR solutions. In order
to avoid any and all dangerous situations, a facility will have to take
all appropriate precautions to secure the ABHR dispensers from
inappropriate access. This may mean that facilities choose to not
install ABHR dispensers in corridors in or near dementia or psychiatric
units. It may also mean that facilities choose to install ABHR
dispensers only in areas that can be easily and frequently monitored,
such as in view of a nursing station or a continuously monitored
security camera. These are just a few of the many options that
facilities may choose to utilize in securing ABHR dispensers against
inappropriate access.
Comment: A few commenters expressed concern with the requirement in
Chapter 8 of the 2012 edition of NFPA 101, which stipulates that all
penetrations of a fire-rated wall or floor must be protected by an
``Approved Fire Stop System or Device,'' instead of simply offering
protection equivalent to the surfaces penetrated, as was required in
the 2000 edition of NFPA 101. The commenters stated that this
requirement would result in higher costs for new facilities required to
use proprietary devices or systems. If CMS requires an existing
facility to meet this new standard due to application for a new
provider agreement, the cost implications could be even greater as
existing wires and other penetrating elements would need to be removed
then reinstalled as necessary in order to comply. The commenters
requested that existing facilities be exempted from this requirement.
Response: The 2012 edition of NFPA 101, Section 8.3.5 states ``The
provisions of 8.3.5 shall not apply to approved existing materials and
methods of construction used to protect existing through-penetrations
and existing membrane penetrations in fire walls, fire barrier walls,
or fire resistance-rated horizontal assemblies, unless otherwise
required by Chapters 11 through 43.'' Section 8.3.5.1 requires firestop
systems and devices; therefore, this requirement would not be
applicable to existing installations.
Comment: Many commenters expressed concerns with our proposed
regulation regarding fire watches. We proposed to require a fire watch
if a sprinkler system is out for more than 4 hours. Commenters
explained that most system maintenance extends over an 8-hour period of
time during a normal workday, and that, during the outage additional
staff with expertise in sprinkler system operation are present to
address sprinkler system problems. Additionally, during a sprinkler
system outage, the fire alarms are still functioning to detect a fire.
Therefore, commenters recommend only requiring the fire watch if the
system will be out of service for 10 hours or more.
Response: We agree that most sprinkler system outages occur during
a regular work day with sufficient staff levels to provide appropriate
monitoring and assure patient safety from fire. Therefore, we are
withdrawing the proposal that all system shutdowns of more than 4 hours
would require a fire watch. We believe a fire watch would consist of
dedicated staff with no other duties constantly circulating throughout
the facility or the portion of the facility affected by the sprinkler
system impairment looking for a fire, fire hazards or hazardous
conditions that may affect the fire safety of the facility. Facilities
may wish to maintain documentation of the rounds of a fire watch, but
this is not required.
Comment: The 2000 edition of the NFPA 99 required separate
ventilation systems for windowless anesthetizing locations in all newly
constructed health care occupancies. Although the NFPA removed the
ventilation system requirement from the 2012 edition of the NFPA 99,
CMS proposed to retain the ventilation requirement for all hospitals
and ASCs. Approximately one third of commenters who submitted comments
on this rule commented on this proposal. With the exception of two
commenters who supported the proposal, the vast majority of
[[Page 26887]]
commenters who commented on this issue strongly disagreed with this
proposal. The commenters stated that installing and maintaining
separate ventilation systems in windowless anesthetizing locations in
existing buildings would be a significant expense, with estimates of
$30,000 per system per anesthetizing location. The commenters stated
that installing and maintaining separate ventilation systems as part of
constructing a new building is also a significant expense, with
estimates ranging from $75,000 to $100,000 per anesthetizing location.
The commenters stated that installing and maintaining ventilation
systems in windowless anesthetizing locations, and thus incurring this
large expense, is unnecessary for the following reasons:
Of the millions of surgical procedures performed each
year, 0.00092 percent per year results in surgical fires;
Surgical fires are largely preventable, and training on
prevention of and prompt response to fires is much more likely to be
effective for patient safety than installing and maintaining
ventilation systems;
While anesthetics used to be flammable, they are not
flammable anymore, which significantly reduces the risk of fires in
anesthetizing locations;
Most anesthetizing locations have quick response
sprinklers present to extinguish any fire that may occur, eliminating
the need for a smoke ventilation system. Healthcare occupancies
required to install sprinklers to fulfill new construction or
renovation requirements would need to install quick response sprinklers
through smoke compartments containing patient rooms. If an
anesthetizing location is located in the same compartment as the
patient sleeping rooms, then the anesthetizing location would require
quick response sprinklers;
The types of fires that occur in anesthetizing locations
produce such a small amount of smoke that the smoke would not
compromise the ability of staff to implement emergency interventions to
extinguish a fire;
Staff in anesthetizing locations have training in updated
techniques to quickly extinguish any fire that may occur;
Some facilities have smoke purge systems that are just as
capable of smoke control as the proposed ventilation system; and
The proposed smoke ventilation system may, under certain
circumstances, create an increased risk for surgical infections in the
affected anesthetizing locations.
Response: In light of the concerns raised by commenters, we agree
that requiring the installation of smoke ventilation systems would not
be an effective use of hospital and ASC resources. We agree that a
focus on preventing and quickly extinguishing surgical fires will
likely have a more significant positive impact on patient safety, and
encourage hospitals, CAHs, and ASCs to continue this important work. We
also agree that the presence of quick response sprinkler heads,
alternative smoke purge systems, which can continue to be used, and the
use of non-flammable anesthetics all contribute to a very minimal risk
of smoke requiring ventilation in the first place. Therefore, we have
removed this requirement from the regulations text for hospitals, CAHs,
and ASCs.
Comment: The LSC applies a specific occupancy type to a facility
that has 4 or more patients. Many commenters disagreed with our
proposal to require all facilities to meet the occupancy requirements
regardless of the number of patients because it would require small
facilities to meet more stringent requirements. Commenters stated that
there is no evidence to support the need for additional safety measures
in these facilities.
Response: We agree with the commenters that meeting a more
stringent occupancy classification is not necessary for very small
health care occupancies with less than 4 patients at any given time,
and therefore, are withdrawing our proposal. This will not affect any
facilities as we are keeping the requirement as it was in the 2000
edition of the LSC and are not making any changes. ASCs continue to be
required to meet the occupancy requirements for ambulatory care
occupancies ``regardless of the number of patients served.'' While this
requirement is different from the definition of ambulatory care
occupancy in the LSC, it is consistent with the previous rule adopting
the 2000 edition of the NFPA 101 (68 FR 1374), which applied the
ambulatory care occupancy chapter to all ASCs, regardless of the number
of patients served.
Comment: Many commenters expressed concern with the window sill
height requirement. The 2000 edition of the LSC required that newly
constructed health care occupancies cannot have a sill height exceeding
36 inches above the floor (with certain exceptions). The NFPA removed
this requirement from the 2012 edition of the LSC. However, CMS
proposed to retain this requirement and apply it to all facilities,
whether they were new or existing construction. The vast majority of
the commenters expressed concern with retrofitting existing facilities
to meet this proposed requirement, and the financial burden they would
incur. Commenters also disagreed with the justification for the
proposal.
Response: We agree with commenters that requiring existing
facilities to change their existing window structures to meet this
requirement would be an undue burden. We have revised the regulation to
assure that any facilities built after the effective date of this final
rule will have to meet the 36 inch window sill height requirement, in
accordance with the 2000 edition of the LSC. Existing facilities that
were not required to meet this specification at the time of
construction would not be required to change window sill heights at
this time. The Secretary does not have statutory authority to require a
minimum window sill requirement, however we believe that while window
sill height is not directly associated with fire safety, but it is
important to quality of life and beneficial to the healing process.
Comment: Many commenters expressed concern with the corridor
projections requirement. The LSC allows for 6'' corridor projections,
but the 2010 ADA Standards for Accessible Design (2010 Standards) only
allow 4'' corridor projections. The commenters suggested only requiring
4'' corridor projections in new construction and newly renovated
construction. The commenters also noted that ABHR dispensers, TV/
computer monitors, and computer kiosks often project more than 4'' and
would have to be moved. A few commenters stated that projections of 4''
or more should be allowed if alternative means are used such as
vertical guards. Some commenters also asked why the LSC and CMS allows
fixed furniture in corridors of LTC facilities up to 2 feet, but will
not allow projections of more than 4''. One commenter suggested not
adopting section 7.2.2.4.4.5 regarding the installation of handrails.
This section requires handrails be mounted to provide a clearance of
not less than 2\1/4\ inches from the wall. The commenter states that
this is not ADA compliant or IBC compliant, there is no maximum
distance from the wall, that this wider gap increases the risk of
entrapment if a person's hand slips while going down the stairs, and
that this should also apply to existing construction. One commenter
also questioned whether or not the ADA 4'' projections apply to areas
that are not patient treatment areas, like mechanical or chemical
rooms.
[[Page 26888]]
Response: As noted, CMS recognizes that the LSC is not an
accessibility code and stresses that compliance with this code is not a
substitute for compliance with the ADA. The 2010 ADA standards address
many concerns raised by commenters, including the clear floor width of
walking surfaces in corridors and handrail clearance. See Section 403.5
and 505.5 of the 2010 ADA standards at https://www.ada.gov/regs2010/2010ADAStandards/2010ADAStandards.htm. In addition to following the
requirements of the LSC, health care facilities are also required to
follow all requirements of the ADA. Where there are conflicts between
the LSC and the ADA, the more stringent standard takes precedence.
Therefore, facilities must comply with the ADA's requirements for
protruding objects, which establishes more stringent protrusion limits
so that a person using a cane may avoid bodily harm. See section 307.2
of the 2010 ADA standards, available at https://www.ada.gov/regs2010/2010ADAStandards/2010ADAStandards.htm (establishing a 4'' limit for
wall-mounted protruding objects and a 4\1/2\'' limit for handrails).
Title II of the ADA applies to health care programs and services of
state and local governments; and Title III of the ADA applies to
private entities providing health care services. When structural
changes are made to existing facilities to provide program access
required by Title II, the 2010 ADA standards are the applicable
accessibility standard. Newly constructed or altered Title II and Title
III facilities must also comply with the 2010 ADA standards. Existing
Title III facilities are required to remove barriers to accessibility
when barrier removal is readily achievable, and the 2010 ADA standards
are the applicable accessibility standard. Changes to the 2010 ADA
standards are beyond the scope of this rule. Any questions regarding
the requirements of the ADA should be directed to DOJ. Technical
assistance regarding ADA compliance can be obtained at https://www.ada.gov or 1-800-514-0301 (voice) and 1-800-514-0383 (TTY).
Comment: One commenter suggested that there be a requirement for
each provider or supplier to conduct an annual inspection and
maintenance of fire door assemblies. Another commenter explicitly
disagreed with this recommendation, stating that the final rule should
clarify that annual inspection of doors in an egress path is not
required in healthcare, ambulatory care, and business occupancies.
Specifically, the commenter stated that hospitals are already
performing visual inspection of these door assemblies and already
assure latching and smooth operation at all times. The commenter
asserted that conducting an additional annual inspection would be
unnecessarily burdensome.
Response: As proposed, we will maintain the required annual
inspection and maintenance of door assemblies. This rule will thus
require documentation that the facility actually inspected and
performed maintenance necessary on this important fire protection
feature. This inspection could be combined with any other maintenance
effort that the facility may be performing.
Comment: One commenter questioned whether the requirement that a
recycling bin must be 96 gallons or less would apply to recycling bins
that are stored outside.
Response: This requirement only applies to any recycling bins
located within a building.
Comment: One commenter stated that 1 year is an adequate timeframe
to allow facilities to make necessary changes to add smoke partitions
around hazardous areas, and that this requirement will not require many
facilities to make changes because building codes have required
separation of hazardous areas for a long period of time.
Response: Since most building codes already require the separation
of hazardous areas, and facilities are probably already meeting this
requirement, we agree that a 1 year phase-in period from the effective
date of this final rule is appropriate to enable affected facilities to
comply with the requirement for hazardous areas separation. Affected
facilities will have 1 year from the effective date of this final rule
to add smoke partitions around hazardous areas that are not already
protected by this feature.
Comment: We proposed to adopt the 2012 edition of the NFPA 101,
which references the 2010 edition of NFPA 101A, Guide on Alternative
Approaches to Life Safety. One commenter recommended that we adopt the
2013 edition of the NFPA 101A instead. The commenter believes that
there are some very significant differences between the 2010 and 2013
editions of NFPA 101A, including:
Section 4.3.2 ``Selection of Zones to be Evaluated''
Section 4.6.9.3 ``Mechanically Assisted Systems''
Section 4.7.10 ``Step 10--Determine Equivalency Conclusion''
Worksheet 4.7.11 ``Conclusions''
Response: In order to be consistent with the 2012 edition of the
LSC, we are not separately adopting the 2013 edition of the NFPA 101A.
We will continue to follow the 2010 edition of the NFPA 101A. If we
adopt a newer version of the LSC in the future that also adopts the
2013 edition of the NFPA 101A, we will review that document at that
time.
Comment: One commenter suggested that CMS and, by extension, those
accreditation organizations that perform deeming surveys, should not
cite LSC deficiencies that are self-identified by the provider or
supplier. The commenter believes that a survey policy which encourages
non-citation of self-identified LSC deficiencies will provide an
incentive to hospital facility managers to self-identify their LSC
deficiencies, record them on a list, and manage the resolution of the
deficiencies.
Response: We applaud facilities that self-identify LSC
deficiencies; however, CMS is most concerned with the safety of
patients and staff. Therefore, if the facility is able to self-identify
deficiencies, they should be in the process of fixing those
deficiencies and able to develop a suitable plan of correction for any
deficiencies that are cited by surveyors.
Comment: A commenter is concerned that the 2012 edition of the LSC
eases the requirements for smoke barriers in existing facilities with
less than 30 beds. The commenter suggested that CMS should require any
facilities with less than 30 beds that were originally built with or
added a smoke barrier dividing the floor into at least two smoke
compartments to keep that smoke barrier, even though the 2012 edition
would allow the facility to remove the smoke barrier.
Response: We appreciate the suggestion. We do not anticipate
facilities actively taking steps to remove existing smoke barriers in
light of this change in the LSC. Should facilities undertake
construction at a future date, they would still be required to meet the
2012 edition of the LSC. We believe that the 2012 edition of the LSC
assures the appropriate level of safety for all residents/patients.
NFPA 99--Health Care Facilities Code
Comment: Many commenters support the adoption of the 2012 NFPA 99
Health Care Facilities code. However, many commenters expressed
confusion as to why the NFPA 99 is not being adopted in full, and some
chapters are being excluded.
Response: As stated in the proposed rule, we will not be adopting
Chapters 7, 8 and 13 because we have no authority to regulate these
specific topics in health care facilities.
[[Page 26889]]
Additionally, the content of Chapter 12, Emergency management, is
already being addressed in a separate rule for emergency preparedness.
Although, we have not adopted these chapters, providers may use these
chapters for their individual facility needs.
Comment: Some commenters encouraged the adoption of the 2012
edition of the NFPA 99 Health Care Facilities code because it allows
for the use of relocatable power taps, which provide additional
electrical receptacles. The 1999 edition of the NFPA 99 does not allow
the use of relocatable power taps.
Response: We appreciate the support of the commenters, and agree
that relocatable power taps can be appropriately used in health care
environments. Therefore, we are finalizing this change as proposed.
Comment: A few commenters expressed concerns with multiple issues
found in the 2012 edition of the NFPA 99 that they believe would
require a facility to upgrade to be in compliance with the following:
Ductwork, HVAC system designs, electrical and medical gas system
requirements, ground fault protection requirements, piped medical gas
systems, and receptacle requirements. The commenters suggested that
these sections be applied only to new facilities and facilities being
remodeled.
Response: We appreciate the opportunity to clarify the requirements
of NFPA 99. The 2012 edition of the NFPA 99 does not divide its
chapters and requirements into new and existing. We note that in the
2012 edition of NFPA 99 Section 1.3.2 states ``Construction and
equipment requirements shall be applied only to new construction and
new equipment, except as modified in individual chapters.'' The
sections described in the comments do not have any modified
requirements; therefore, in accordance with the requirements of NFPA
99, these requirements only apply to new construction and new
equipment.
General or Other Comments
Comment: One commenter suggested that we add a list of acronyms at
the beginning of the rule.
Response: We have added a list of acronyms to the beginning of the
document. We have also spelled out each acronym the first time it is
used in the rule.
IV. Provisions of the Final Regulations
We are adopting the provisions of this rule as proposed, except for
the following changes and clarifications:
RNHCI--
We are clarifying that our adoption of the 2012 edition of the NFPA
101 and NFPA 99, includes the following TIAs issued prior to April 16,
2014:
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(v) TIA 12-2 to NFPA 99, issued August 11, 2011.
(vi) TIA 12-3 to NFPA 99, issued August 9, 2012.
(vi) TIA 12-4 to NFPA 99, issued March 7, 2013.
(viii) TIA 12-5 to NFPA 99, issued August 1, 2013
(ix) TIA 12-6 to NFPA 99, issued March 3, 2014.
We are clarifying that the prohibition on roller latches
applies only to doors to corridors and to rooms containing flammable or
combustible materials.
We are revising the requirements for the shutdown of a
sprinkler system for an extended period of time.
We are revising the window sill requirement for new
construction only to indicate that such sills must not be higher than
36 inches above the floor.
ASCs--
We are clarifying that our adoption of the 2012 edition of the NFPA
101 and NFPA 99, includes the following TIAs issued prior to April 16,
2014, regardless of the number of patients served:
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(v) TIA 12-2 to NFPA 99, issued August 11, 2011.
(vi) TIA 12-3 to NFPA 99, issued August 9, 2012.
(vii) TIA 12-4 to NFPA 99, issued March 7, 2013.
(viii) TIA 12-5 to NFPA 99, issued August 1, 2013.
(ix) TIA 12-6 to NFPA 99, issued March 3, 2014.
We are removing the requirements for the installation of a
dedicated air supply and exhaust system in windowless anesthetizing
locations.
We are revising the requirements for door locking
mechanisms on hazardous areas.
We are revising the requirements for the shutdown of a
sprinkler system for an extended period of time.
We are revising the window sill requirements for new
construction only to indicate that such sills must not be higher than
36 inches above the floor.
Hospice--
We are clarifying that our adoption of the 2012 edition of the NFPA
101 and NFPA 99, includes the following TIAs issued prior to April 16,
2014:
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(v) TIA 12-2 to NFPA 99, issued August 11, 2011.
(vi) TIA 12-3 to NFPA 99, issued August 9, 2012.
(vii) TIA 12-4 to NFPA 99, issued March 7, 2013.
(viii) TIA 12-5 to NFPA 99, issued August 1, 2013.
(ix) TIA 12-6 to NFPA 99, issued March 3, 2014.
We are clarifying that the prohibition on roller latches
applies only to doors to corridors and to rooms containing flammable or
combustible materials.
We are revising the requirements for the shutdown of a
sprinkler system for an extended period of time.
We are revising the window sill requirement for new
construction only to indicate that such sills must not be higher than
36 inches above the floor.
PACE--
We are clarifying that our adoption of the 2012 edition of the NFPA
101 and NFPA 99, includes the following TIAs issued prior to April 16,
2014:
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(v) TIA 12-2 to NFPA 99, issued August 11, 2011.
(vi) TIA 12-3 to NFPA 99, issued August 9, 2012.
(vii) TIA 12-4 to NFPA 99, issued March 7, 2013.
(viii) TIA 12-5 to NFPA 99, issued August 1, 2013.
(ix) TIA 12-6 to NFPA 99, issued March 3, 2014.
We are clarifying that the prohibition on roller latches
applies
[[Page 26890]]
only to doors to corridors and to rooms containing flammable or
combustible materials.
We are revising the requirements for the shutdown of a
sprinkler system for an extended period of time.
Hospitals--
We are clarifying that our adoption of the 2012 edition of the NFPA
101 and NFPA 99, includes the following TIAs issued prior to April 16,
2014:
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(v) TIA 12-2 to NFPA 99, issued August 11, 2011.
(vi) TIA 12-3 to NFPA 99, issued August 9, 2012.
(vii) TIA 12-4 to NFPA 99, issued March 7, 2013.
(viii) TIA 12-5 to NFPA 99, issued August 1, 2013.
(ix) TIA 12-6 to NFPA 99, issued March 3, 2014.
We are clarifying that the prohibition on roller latches
applies only to doors to corridors and to rooms containing flammable or
combustible materials.
We are clarifying that all outpatient surgical departments
must meet applicable provisions in Ambulatory Health Care occupancy
chapter, regardless of the number of patients served.
We are revising the requirements for the shutdown of a
sprinkler system for an extended period of time.
We are removing the requirement for installation of a
dedicated air supply and exhaust system in windowless anesthetizing
locations.
We are revising the window sill requirement for new
construction only to indicate that such sills must not be higher than
36 inches above the floor.
LTC--
We are clarifying that our adoption of the 2012 edition of the NFPA
101 and NFPA 99, includes the following TIAs issued prior to April 16,
2014:
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(v) TIA 12-2 to NFPA 99, issued August 11, 2011.
(vi) TIA 12-3 to NFPA 99, issued August 9, 2012.
(vii) TIA 12-4 to NFPA 99, issued March 7, 2013.
(viii) TIA 12-5 to NFPA 99, issued August 1, 2013.
(ix) TIA 12-6 to NFPA 99, issued March 3, 2014.
We are clarifying that the prohibition on roller latches
applies only to doors leading into corridors and leading into rooms
containing flammable or combustible materials.
We are revising the requirements for the shutdown of a
sprinkler system for an extended period of time.
ICF-IIDs--
We are clarifying that our adoption of the 2012 edition of the NFPA
101 and NFPA 99, includes the following TIAs issued prior to April 16,
2014:
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(v) TIA 12-2 to NFPA 99, issued August 11, 2011.
(vi) TIA 12-3 to NFPA 99, issued August 9, 2012.
(vii) TIA 12-4 to NFPA 99, issued March 7, 2013.
(viii) TIA 12-5 to NFPA 99, issued August 1, 2013.
(ix) TIA 12-6 to NFPA 99, issued March 3, 2014.
We are clarifying that the prohibition on roller latches
applies only to doors to corridors and to rooms containing flammable or
combustible materials.
We are revising the exclusion of provisions related to
``Lockups.''
We are revising the requirements for the shutdown of a
sprinkler system for an extended period of time.
We are revising the window sill requirement for new
construction only to indicate that such sills must not be higher than
36 inches above the floor.
CAHs--
We are clarifying that our adoption of the 2012 edition of the NFPA
101 and NFPA 99, includes the following TIAs issued prior to April 16,
2014:
(i) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iii) TIA 12-3 to NFPA 101, issued October 22, 2013.
(iv) TIA 12-4 to NFPA 101, issued October 22, 2013.
(v) TIA 12-1 to NFPA 99, issued August 11, 2011.
(vi) TIA 12-2 to NFPA 99, issued August 11, 2011.
(vii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(viii) TIA 12-4 to NFPA 99, issued March 7, 2013.
(ix) TIA 12-5 to NFPA 99, issued August 1, 2013.
(x) TIA 12-6 to NFPA 99, issued March 3, 2014.
We are clarifying that the prohibition on roller latches
applies only to doors to corridors and to rooms containing flammable or
combustible materials.
We are revising the requirements for the shutdown of a
sprinkler system for an extended period of time.
We are removing the requirement for installation of a
dedicated air supply and exhaust system in windowless anesthetizing
locations.
We are revising the window sill requirement for new
construction only to indicate that such sills must not be higher than
36 inches above the floor.
V. Collection of Information Requirements
This final rule does not impose any new reporting, recordkeeping or
third-party disclosure requirements. However, this final rule does
reference the NFPA 99 that has several non-reported recordkeeping
requirements for medical gas and vacuum systems, and electrical
equipment. We believe that documenting maintenance and testing is a
usual and customary business practice in accordance with the
implementing regulations of the Paperwork Reduction Act of 1995 (PRA)
at 5 CFR 1320.3(b)(2), and it would not impose any additional
information collection burden beyond that associated with the normal
course of business. Consequently, it need not be reviewed by the Office
of Management and Budget under the authority of the Paperwork Reduction
Act of 1995.
VI. Regulatory Impact Analysis
In accordance with the provisions of Executive Order 12866, this
regulation was reviewed by the Office of Management and Budget.
A. Overall Impact
We have examined the impacts of this rule as required by Executive
Order 12866 on Regulatory Planning and Review (September 30, 1993),
Executive Order 13563 on Improving Regulation and Regulatory Review
(January 18, 2011), the Regulatory Flexibility Act (RFA) (September 19,
1980, Pub. L. 96-354), section 1102(b) of the Social Security Act,
section 202 of the Unfunded Mandates Reform Act of 1995 (March 22,
1995; Pub. L. 104-4), Executive Order 13132 on Federalism
[[Page 26891]]
(August 4, 1999) and the Congressional Review Act (5 U.S.C. 804(2).
Executive Orders 12866 and 13563 direct agencies to assess all
costs and benefits of available regulatory alternatives and, if
regulation is necessary, to select regulatory approaches that maximize
net benefits (including potential economic, environmental, public
health and safety effects, distributive impacts, and equity). Executive
Order 13563 emphasizes the importance of quantifying both costs and
benefits, of reducing costs, of harmonizing rules, and of promoting
flexibility. A regulatory impact analysis (RIA) must be prepared for
major rules with economically significant effects ($100 million or more
in any 1 year). The overall economic impact for this rule is estimated
to be $18 million in the first year of implementation, $12 million,
annually, for years 2 and 3 of implementation, and $6 million,
annually, for years 4-12 of implementation. We estimate that this
rulemaking is not ``economically significant'' as measured by the $100
million threshold, and hence not a major rule under the Congressional
Review Act. Accordingly, we have prepared a Regulatory Impact Analysis
(RIA) that, to the best of our ability, presents the costs and benefits
of rulemaking.
B. Statement of Need
The 2012 edition of the LSC includes new provisions that we believe
are vital to the health and safety of all patients and staff. Our
intention is to ensure that patients and staff continue to experience
the highest degree of fire safety possible. The use of earlier editions
of the code can become problematic due to advances in safety and
technology and changes made to each edition of the code. Newer
buildings are typically built to comply with the newer versions of the
LSC because state and local jurisdictions, as well as non-CMS-approved
accreditation programs, often adopt and enforce newer versions of the
code as they become available. We believe that adopting the 2012 LSC
would simplify and modernize the construction and renovation process
for affected health care providers and suppliers, reduce compliance-
related burdens, and allow for more resources to be used for patient
care. Many health care facilities complete unnecessary work and incur
unnecessary expense without any gain in fire safety by continuing to
comply with the 2000 edition of the LSC.
The 2012 edition of the NFPA 99, ``Health Care Facilities Code,''
addresses requirements for both health care occupancies and ambulatory
care occupancies, and serves as a resource for those who are
responsible for protecting health care facilities from fire and
associated hazards. The purpose of this Code is to provide minimum
requirements for the installation, inspection, testing, maintenance,
performance, and safe practices for health care facility materials,
equipment and appliances. This Code is a compilation of documents that
have been developed over a 40-year period by NFPA, and is intended to
be used by those persons involved in the design, construction,
inspection, and operation of health care facilities, and in the design,
manufacture, and testing of appliances and equipment used in patient
care areas of health care facilities. Many requirements of the LSC
already cross reference the NFPA 99, and it addresses additional
building safety topics that are related to important fire safety issues
specific to health care facilities.
We believe that it is in the best interest of CMS to adopt the more
recent 2012 edition of the NFPA 101 and the 2012 edition of the NFPA
99, in order to be up to date with all of the latest upgrades to health
care facilities and safety requirements.
C. Summary of Impacts
Table 1--Total Annual Cost of Implementation for All Years
------------------------------------------------------------------------
Millions
------------------------------------------------------------------------
Year 1 of implementation..................................... $18
Years 2-3 of implementation.................................. 24
Years 4-12 of implementation................................. 53
----------
Total Years 1-12 of implementation......................... 95
------------------------------------------------------------------------
Note: This cost may be less depending on the number of States that have
already adopted the 2012 edition of the LSC.
Table 2--Total Annual Cost for Implementation in Year 1
----------------------------------------------------------------------------------------------------------------
Cost per
Requirement Provider type affected affected Cost for all
provider providers
----------------------------------------------------------------------------------------------------------------
High-rise sprinkler installation.............. Hospitals, partially sprinklered $34,075 $4,429,783
High-rise sprinkler installation.............. Hospitals, non-sprinklered...... 117,028 1,053,253
Self-closing or automatic closing doors on ASCs............................ 1,047 1,763,148
hazardous areas.
Sprinklers in attics (used for living ICF-IIDs........................ 4,500 5,980,500
purposes, storage or fuel fired equipment).
Heat detection systems in attics (not used for ICF-IIDs........................ 1,000 212,333
living purposes).
Hazardous areas separated by smoke partitions. ICF-IIDs........................ 1,000 4,624,000
Upgrade existing or install new fire alarm ICF-IIDs........................ 1,000 384,000
system.
-------------------------------
Total..................................... ................................ .............. 18,447,017
----------------------------------------------------------------------------------------------------------------
Table 3--Total Annual Cost of Implementation for Years 2-3
----------------------------------------------------------------------------------------------------------------
Cost per
Requirement Provider type affected affected Cost for all
provider providers
----------------------------------------------------------------------------------------------------------------
High-rise sprinkler installation.............. Hospitals, partially sprinklered $34,075 $4,429,783
High-rise sprinkler installation.............. Hospitals, non-sprinklered...... 117,028 1,053,253
Upgrade existing or install new fire alarm ICF-IIDs........................ 1,000 384,000
system.
Sprinklers in attics (used for living ICF-IIDs........................ 4,500 5,980,500
purposes, storage or fuel fired equipment).
[[Page 26892]]
Heat detection systems in attics (not used for ICF-IIDs........................ 1,000 212,333
living purposes).
-------------------------------
Total Annually............................ ................................ .............. 12,059,869
-------------------------------
Overall Total Years 2-3............... ................................ .............. 24,119,738
----------------------------------------------------------------------------------------------------------------
Table 4--Total Cost of Implementation for Years 4-12
----------------------------------------------------------------------------------------------------------------
Cost per
Requirement Provider type affected affected Cost for all
provider providers
----------------------------------------------------------------------------------------------------------------
High-rise sprinkler installation.............. Hospitals, partially sprinklered $34,075 $4,429,783
High-rise sprinkler installation.............. Hospitals, non-sprinklered...... 117,028 1,053,253
Upgrade existing or install new fire alarm ICF-IIDs........................ 1,000 384,000
system.
-------------------------------
Total Annually............................ ................................ .............. 5,867,036
-------------------------------
Overall Total Years 4-12.............. ................................ .............. 52,803,324
----------------------------------------------------------------------------------------------------------------
D. Detailed Economic Analysis
1. Burden Assessment
Sprinklers in High-Rise Buildings
Section 19.4.2 of the LSC requires that all existing high-rise
buildings containing health care occupancies be protected throughout by
an approved, supervised automatic sprinkler system. We feel that this
requirement will only affect hospitals and any other provider type
located in the same building as a hospital (for example, an ASC that is
located in a hospital building). This provision was added to the LSC in
2012 and we anticipate that there would be a cost associated with
installing the sprinklers. Since this is a new provision for the 2012
edition of the LSC, 14 states have adopted this requirement, accounting
for an estimated 142 high-rise facilities.
To develop the most accurate estimate possible for this provision,
we requested data from all 50 states regarding the sprinkler status of
high-rise buildings containing health care occupancies, and the average
square footage needing to be sprinklered. Of the 50 states, we received
some data from 30 states.\4\ We calculated the average number of high-
rise hospitals for all of the states that responded. Overall, 15.64
percent of hospitals were located in high-rise buildings. We also used
the data submitted to determine the average number of fully, partially
and non-sprinklered high-rise buildings in each state for which we have
data. First, we calculated the percentages of fully, partially, and
non-sprinklered hospitals for each state. We then averaged the
percentage of fully, partially and non-sprinklered buildings across all
states for which there was data, with a result of 84.66 percent of
hospitals in high-rise buildings being fully sprinklered, 14.6 percent
being partially sprinklered and 0.74 percent being non-sprinklered.
---------------------------------------------------------------------------
\4\ The following states submitted data regarding the sprinkler
status of high-rise buildings containing health care facilities--
Arizona, Arkansas, California, Colorado, Delaware, Hawaii, Idaho,
Iowa, Kansas, Louisiana, Maine, Maryland, Massachusetts, Minnesota,
Missouri, Montana, Nebraska, Nevada, New Hampshire, New Mexico,
North Dakota, Oklahoma, Pennsylvania, Rhode Island, South Dakota,
Texas, Utah, Virginia, Washington, and Wyoming.
---------------------------------------------------------------------------
Next, we applied these percentages to the states that did not
respond to our data request or that provided a limited amount of data.
For example, Alabama has a total of 125 hospitals. Based on the data
from states that submitted information, we know that, on average, 15.64
percent of hospitals have high-rise buildings, for an estimated 20
high-rise hospitals in Alabama. We used this same methodology to
estimate the average number of high-rise hospitals in all of the states
that did not respond to our data request or that provided only a
limited amount of data, for a total of 179 high-rise hospitals. Of the
179 estimated high-rise hospitals in states that did not respond, we
estimate there are 151 fully sprinklered, 26 partially sprinklered, and
2 non-sprinklered. We note that these numbers do not directly match
because there was limited actual data available for the state of
Massachusetts. The number of high-rise hospitals in Massachusetts is
included in the count of states for which we have reported data.
However, because we did not receive a breakdown of those high-rise
hospitals by their current sprinkler status, we used the methodology
described to estimate the distribution of fully sprinklered, partially
sprinklered, and non-sprinklered high-rise hospitals in that state.
We combined this information with the information from the states
that submitted data to develop an estimate of 515 high-rise facilities
with health care occupancies throughout all 37 states and the District
of Columbia that have not adopted the 2012 NFPA 101 (336 high-rise
facilities in states that submitted data + 179 estimated high-rise
facilities in states that did not submit data). We estimate that 376 of
those high-rise facilities are fully sprinklered, 130 are partially
sprinklered, and 9 are not sprinklered.
We also requested that the 50 states and the District of Columbia
submit information regarding the area (measured in square feet) per
partially sprinklered and non-sprinklered facility that does not
currently have sprinklers. Only 8 states supplied data regarding the
area to be sprinklered in partially sprinklered facilities.\5\ In
addition, 3 states supplied data regarding the area to be sprinklered
in non-sprinklered facilities.\6\ We did not specify size and
[[Page 26893]]
age data. Of the states that responded with square footage data, we
estimate that an average partially sprinklered facility would need to
install sprinklers to protect 37,173 square feet, and an average non-
sprinklered facility would need to install sprinklers to protect
127,667 square feet. Regardless of the square footage, any facility in
a high-rise building 75' or over is required to be sprinklered. We
applied all of the data submitted and averages calculated to figure out
the total average area that will need to be sprinklered in all
partially sprinklered facilities and non-sprinklered facilities, and
the cost associated with that installation. Based on the information
provided by the public in comments received on the hospital conditions
of participation (76 FR 65891), the cost per square foot to install
sprinklers is approximately $11. We estimated that there are 130
partially sprinklered facilities that would install sprinklers to cover
an average of 37,173 square feet per facility, for a total of 4,832,490
square feet. At an estimated cost of $11 per square foot to install
sprinklers, we estimate a total cost of $53,157,390 for all partially
sprinklered facilities (4,832,490 square feet x $11 per square foot).
We estimate that an average partially sprinklered facility would spend
$408,903 to complete the sprinkler installation (37,173 square feet per
facility x $11 per square foot).
---------------------------------------------------------------------------
\5\ The following states provided data regarding the average
square footage for partially sprinklered high-rise facilities
containing health care facilities--California, Hawaii, Iowa, Kansas,
Nebraska, Pennsylvania, Virginia, and Washington.
\6\ The following states provided data regarding the average
square footage for non-sprinklered high-rise facilities containing
health care facilities--California, Hawaii, and Iowa.
---------------------------------------------------------------------------
We estimated that there are 9 non-sprinklered facilities
nationwide, and that an average non-sprinklered facility would install
sprinklers for, 127,667 square feet, for a total of 1,149,003 square
feet (9 facilities x 127,667 square feet per facility). At an estimated
cost of $11 per square foot to install sprinklers, we estimate that it
would cost $12,639,033 for all non-sprinklered facilities to install
sprinklers in their facilities. We estimate that an average non-
sprinklered facility would spend $1,404,337 per facility (127,667
square feet x $11 per square foot).
Therefore, we estimate the total cost associated with the
installation of sprinklers in partially sprinklered and non-sprinklered
facilities to be $65,796,423 ($53,157,390 for all partially sprinklered
facilities + $12,639,033 for all non-sprinklered facilities). This cost
would be distributed over a phase-in period of 12 years, per the phase-
in period established within the LSC, or an average yearly cost of $5.5
million.
Sprinklers Out of Service for More Than 10 Hours
We have removed the requirement for a fire watch or building
evacuation if the sprinkler system is out of service for more than 4
hours, and have adopted the LSC requirements of a fire watch or
building evacuation if the sprinkler system is out for more than 10
hours in a 24-hour period. Based on comments received from
stakeholders, associations and the public, sprinkler systems are
generally only out of service for 8 hours in a 24-hour period.
Therefore, we do not anticipate additional costs associated with this
requirement. If there is an event where the sprinkler system would be
out of service for more than 10 hours in a 24-hour period, we feel that
it would be considered a standard business practice to implement a fire
watch or building evacuation, as the previous requirement was more
stringent and required a fire watch or building evacuation after the
sprinkler system is out of service for more than 4 hours.
Doors to Hazardous Areas
Sections 20.3.2.1 and 21.3.2.1 of the LSC requires all doors to
hazardous areas to be self-closing or automatic-closing. This
requirement is only located in sections 20.3.2.1 and 21.3.2.1, which
applies to Ambulatory health care. This provision was added to the LSC
in 2003, and we anticipate that there would be a cost associated with
installing the self-closing or automatic closing doors. Since 2003, 35
states have adopted this requirement, accounting for an estimated 3,684
ASCs. As of December 2013, there were 5,368 total Medicare and
applicable Medicaid participating ASCs. The 1,684 remaining facilities
would be required to upgrade their door closing mechanisms to meet this
requirement. The estimated cost per door is $349, and we would assume
the average facility has 3 hazardous areas that would require a
replacement door closing mechanism for a total cost of $1,047 per
facility. The anticipated cost is $1,763,148.
Sprinklers or Heat Detection Systems in Attics
Sections 32.2.3.5.7 and 33.2.3.5.7 of the LSC requires attics of
new and existing residential board and care occupancies, which, for our
purposes, are ICF-IIDs to be sprinklered if the attic space is used for
living purposes, including storage and fuel fired equipment. Facilities
that do not use their attics for living purposes may choose to install
a heat detection system in place of the sprinklers. This provision was
added to the LSC in 2012. Since this is a new provision for the 2012
edition of the LSC, only 14 states have adopted this requirement,
accounting for an estimated 1,750 ICF-IIDs. We are not including those
1,750 facilities in our analysis. For purposes of this analysis only,
we assume that about 10 percent (637) of facilities will install a heat
detection system because they do not use the attic for living purposes.
As of December 2013, there were 6,374 total Medicare participating ICF-
IIDs. After excluding those facilities located in states that have
already adopted this requirement and those that would install a heat
detection system instead of sprinklers, the 3,987 remaining facilities
would be required to install sprinklers in their attics to meet this
requirement. Installing sprinklers into an unfinished attic is less
complicated than installing sprinklers in a finished hospital,
therefore the cost per square foot would be less to install in attics
than hospitals. The estimated cost per square foot to install
sprinklers in an attic is $3.00, and the average estimated square
footage per attic per facility is 1500 square feet, for a total of
$4,500 per ICF-IID. We estimate that all ICF-IIDs would spend
$17,941,500 to install sprinklers in their attic spaces. After
soliciting public comment, we have decided to finalize a 3 year phase-
in period, which would make the cost $5,980,500 per year over 3 years.
Facilities that do not use their attics for living purposes may
choose to install a heat detection system in the attic instead of
sprinklers. As stated, for the purposes of this analysis only, we
assume that about 10 percent (637) of facilities will install a heat
detection system because they do not use the attic for living purposes.
We estimate the cost to install a heat detection system to be $1,000
per facility. The anticipated cost would be $637,000 for all affected
facilities to install heat detection systems. After soliciting public
comment, we have decided to finalize a 3 year phase-in period, which
would make the cost $212,333 per year over 3 years.
Hazardous Area Separation
Section 33.3.3.2.3 of the LSC requires all hazardous areas in
existing residential board and care occupancies (which, under our
regulations, are ICF-IIDs) with impractical evacuation capabilities to
be separated from other parts of the building by a smoke partition.
This provision was added to the LSC in 2012 and we anticipate there
being a cost associated with installing the smoke partition. Since this
is a new provision for 2012, only 14 states have adopted this
requirement, accounting for 1,750 ICF-IIDs. As of December 2013, there
were 6,374 total Medicare and applicable Medicaid participating
[[Page 26894]]
ICF-IIDs. We do not collect data regarding the evacuation capability of
each ICF-IID. Therefore, for purposes of this analysis only, we assume
that the 4,624 remaining facilities will need to install a smoke
partition around all hazardous areas to meet this requirement. The
estimated cost per smoke partition is $500, and we assume that an
average ICF-IID would need to install 2 smoke partitions for a total of
$1,000 per facility. The anticipated cost is $4,624,000.
Fire Alarm System Upgrade
Section 33.3.3.4.6.2 of the LSC requires that, when an existing
residential board and care occupancy (that is, ICF-IIDs) installs a new
fire alarm system, or the existing fire alarm system is replaced,
notification of emergency forces should be handled in accordance with
section 9.6.4. Section 9.6.4states that notification of emergency
forces should alert the municipal fire department and fire brigade (if
provided) of fire or other emergency. This provision was added to the
LSC in 2012, and we anticipate there being a cost associated with
upgrading a new or existing fire alarm system. Since this is a new
provision for 2012, only 14 states have adopted this requirement,
accounting for 1,750 ICF-IIDs. As of December 2013, there were 6,374
total Medicare participating ICF-IIDs. The 4,624 remaining facilities
would be required to add emergency notifications capabilities when they
choose to update or install a new fire alarm system. The estimated cost
per upgrade is $1,000. For purposes of this analysis only, we assume
that about 8.3 percent (384) of facilities will do this in any given
year, for an annual cost of $384,000 over a 12-year period.
($1,000 per upgraded alarm system x 384 facilities in any given year =
$384,000)
2. Benefits to Patients/Residents
As a result of this rule, we believe that there would be a
decreased risk of premature death. A decreased risk of premature death
is valuable to people and that value is symbolized by their willingness
to pay for such benefits. The Department of Transportation found in a
recent literature review that willingness to pay for reductions in the
risk of premature death equivalent to saving one life in expectation is
typically over $9 million (https://www.dot.gov/sites/dot.dev/files/docs/VSL%20Guidance%202013.pdf). Although we are not quantifying the number
of lives that would be saved upon implementation of this rule due to
the lack of data that could provide a reliable point estimate, we
believe that there is potential for such a result. In order to ``break
even'' on the cost of this rule--in other words, in order for the total
costs of implementing this rule to equal the total benefits of doing
so--this rule would need to save 1.3 lives per year for 12 years at a 7
percent discount rate and a value of $9 million per life saved would
cause the rule to break even. It would take about 1.1 lives per year
for 12 years at a 3 percent discount rate. Given our review of the
current literature on fire safety in health care facilities, we are
confident that implementing the 2012 LSC will save at least that number
of lives.
E. Alternatives Considered
As a regulatory alternative, we could have chosen not to update our
fire safety provisions. We believe that this is not an acceptable
alternative because many health care facilities complete unnecessary
work and incur unnecessary expense without any gain in fire safety by
continuing to comply with the 2000 edition of the LSC. Many states have
adopted subsequent editions of the LSC. This has caused confusion for,
and imposed additional burdens on, health care facilities, that must
request waivers or modify designs to meet the requirements of both the
state- and federally-adopted editions of the LSC. Updating the LSC
would not only relieve the regulatory burden on health care providers,
but also assist in ensuring the health and safety of patients and
staff.
We considered an alternative phase-in period for the requirement to
install sprinklers in high rise health care occupancies. The LSC allows
for a 12-year phase-in period, which would begin on the day a final
rule is published. We considered shortening this period in order to
accelerate compliance. However, based on our recent experience with
requiring LTC facilities to install sprinklers within 5 years, and the
difficulties that several facilities have faced in meeting this
deadline, we have learned that a shorter phase-in period is not always
feasible for facilities. We also considered a longer phase-in period,
but believe that extending beyond 12 years set out in the LSC may not
sufficiently convey the importance of this requirement to improving
patient and staff safety in these buildings.
We considered not including separate requirements for window sill
heights. Although the NFPA has removed these requirements from the LSC,
because the total concept approach of all health care facilities should
be designed, constructed, maintained and operated to minimize the
possibility of a fire emergency requiring the evacuation of occupants
can be achieved without reliance on such window sill requirements, we
felt that this was an important issues that still needed to be required
for the safety of patients, visitors, and staff. Window sill height
requirements were eliminated from the 2012 edition of the LSC. We
believe that this requirement is essential to allow easier access for
emergency personnel in the event of a fire or other emergency situation
and it is important to quality of life and the healing process. This
will, however, only be required in new facilities.
We considered not including the adoption of the NFPA 99 Health care
Facilities code. However, many requirements of the LSC already cross-
reference the NFPA 99, therefore we decided to adopt the NFPA 99
because it addresses additional building safety topics that are related
to important fire safety issues specific to health care facilities. The
requirements of NFPA 99, like those in NFPA 101, will be legally
enforceable to the extent specified in this rule.
We also considered adoption of chapters 7, 8, 12, and 13 of the
NFPA 99, related to information technology, plumbing, emergency
management, and security management. We believe that information
technology, plumbing and security management are not within the scope
of the conditions of participation and conditions for coverage. In
addition, emergency management topics are addressed in our December 27,
2013 proposed rule, ``Medicare and Medicaid Programs: Emergency
Preparedness Requirements for Medicare and Medicaid Participating
Providers and Suppliers'' (78 FR 79081).
F. Accounting Statement
As required by OMB Circular A-4 (available at https://www.whitehouse.gov/omb/circulars_a004_a-4), we have prepared an
accounting statement in Table X showing the classification of the
transfers and costs associated with the provisions of this rule for CY
2015.
[[Page 26895]]
Table 5--Accounting Statement: Classification of Estimated Costs Between 2016 and 2027
----------------------------------------------------------------------------------------------------------------
Units
Category Estimates --------------------------------------------------------
Year dollar Discount rate (%) Period covered
----------------------------------------------------------------------------------------------------------------
Costs *
Annualized Monetized ($million/year) 8.6 2015 7 2016-2027
8.2 2015 3 2016-2027
----------------------------------------------------------------------------------------------------------------
* Costs are associated with the provisions of the life safety code.
G. Regulatory Flexibility Act (RFA)
The RFA requires agencies to analyze options for regulatory relief
of small entities, if a rule has a significant impact on a substantial
number of small entities. For purposes of the RFA, small entities
include small businesses, nonprofit organizations, and government
agencies. Individuals and states are not included in the definition of
a small entity. For purposes of the RFA, most of the providers and
suppliers that would be affected by this rule (hospitals, ASCs, and
ICF-IIDs) are considered to be small entities, either by virtue of
their nonprofit or government status or by having yearly revenues below
industry threshold established by the Small Business Administration
(for details, see the Small Business Administration's Web site at
https://www.sba.gov/content/small-business-size-standards).
We estimate that the following affected facilities are
expected to spend less than $3,500 in any given year on a per average
facility basis; all LTC facilities, all hospices with inpatient care
facilities, all PACE facilities, all RNHCIs, all existing ASCs, all
existing CAHs, and all existing fully sprinklered hospitals.
We estimate that the average affected ICF-IID will spend
$5,400-$8,900 in the first year, which requires the most significant
investment and, by year four, that amount drops to $3,400 per year.
We estimate that the average affected partially
sprinklered high-rise hospital and the average affected non-sprinklered
high-rise hospitals will spend $36,475-$119,428 each year during the 12
year phase-in period to install sprinklers. After the installation of
sprinklers, we estimate that the annual cost decreases to $2,400 per
year.
We estimate that newly constructed hospitals will spend
$2,400, newly constructed CAHs will spend $2,400 and newly constructed
ASCs will spend $2,400, respectively, in any given year.
The Department of Health and Human Services uses as its measure of
significant economic impact on a substantial number of small entities a
change in revenues of more than 3 to 5 percent. Therefore, the
Secretary proposes to certify that this rule will not have a
significant impact on a substantial number of small entities, since the
impact will be less than 3 percent of the revenue. The preceding
economic analysis, together with the remainder of this preamble,
constitutes that analysis.
In addition, section 1102(b) of the Act requires us to prepare a
regulatory impact analysis if a rule may have a significant impact on
the operations of a substantial number of small rural hospitals. This
analysis must conform to the provisions of section 604 of the RFA. For
purposes of section 1102(b) of the Act, we define a small rural
hospital as a hospital that is located outside of a metropolitan
statistical area and has fewer than 100 beds. We believe that this rule
will not have a significant impact on the operations of a substantial
number of small rural hospitals.
H. Unfunded Mandates Reform Act (UMRA)
Section 202 of the Unfunded Mandates Reform Act of 1995 (UMRA) also
requires that agencies assess anticipated costs and benefits before
issuing any rule whose mandates require spending in any 1 year of $100
million in 1995 dollars, updated annually for inflation. In 2015, that
threshold is approximately $144 million. This rule will not have an
impact on the expenditures of state, local, or tribal governments in
the aggregate, or on the private sector of $144 million in any one
year.
I. Federalism
Executive Order 13132 establishes certain requirements that an
agency must meet when it promulgates a proposed rule (and subsequent
final rule) that imposes substantial direct requirement costs on state
and local governments, preempts state law, or otherwise has Federalism
implications. This rule has no Federalism implications.
J. Congressional Review Act
This regulation is subject to the Congressional Review Act
provisions of the Small Business Regulatory Enforcement Fairness Act of
1996 (5 U.S.C. 801 et seq.) and has been transmitted to the Congress
and the Comptroller General for review.
In accordance with the provisions of Executive Order 12866, this
rule was reviewed by the Office of Management and Budget.
List of Subjects
42 CFR Part 403
Health insurance, Hospitals, Intergovernmental relations,
Incorporation by reference, Medicare, Reporting and recordkeeping
requirements.
42 CFR Part 416
Health facilities, Kidney diseases, Incorporation by reference,
Medicare, Reporting and recordkeeping requirements.
42 CFR Part 418
Health facilities, Hospice care, Incorporation by reference,
Medicare, Reporting and recordkeeping requirements.
42 CFR Part 460
Aged, Health, Incorporation by reference, Medicare, Medicaid,
Reporting and recordkeeping requirements.
42 CFR Part 482
Grant programs--health, Hospitals, Incorporation by reference,
Medicaid, Medicare, Reporting and recordkeeping requirements.
42 CFR Part 483
Grant programs--health, Health facilities, Health professions,
Health records, Incorporation by reference, Medicaid, Medicare, Nursing
homes, Nutrition, Reporting and recordkeeping requirements, Safety.
42 CFR Part 485
Grant programs--health, Health facilities, Incorporation by
reference,
[[Page 26896]]
Medicaid, Medicare, Reporting and recordkeeping requirements.
For the reasons set forth in the preamble, the Centers for Medicare
& Medicaid Services amends 42 CFR chapter IV as set forth below:
PART 403--SPECIAL PROGRAMS AND PROJECTS
0
1. The authority citation for part 403 continues to read as follows:
Authority: 42 U.S.C. 1395b-3 and Secs. 1102 and 1871 of the
Social Security Act (42 U.S.C. 1302 and 1395hh).
0
2. Amend Sec. 403.744 by--
0
a. Revising paragraphs (a)(1)(i) and (ii).
0
b. Revising paragraph (a)(4).
0
c. Adding paragraphs (a)(5) and (6).
0
d. Revising paragraphs (b)(1) and (c).
The revisions and additions read as follows:
Sec. 403.744 Condition of participation: Life safety from fire.
(a)
(1) * * *
(i) The RNHCI must meet the applicable provisions and must proceed
in accordance with the Life Safety Code (NFPA 101 and Tentative Interim
Amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4).
(ii) Notwithstanding paragraph (a)(1)(i) of this section, corridor
doors and doors to rooms containing flammable or combustible materials
must be provided with positive latching hardware. Roller latches are
prohibited on such doors.
* * * * *
(4) The RNHCI may place alcohol-based hand rub dispensers in its
facility if the dispensers are installed in a manner that adequately
protects against inappropriate access.
(5) When a sprinkler system is shut down for more than 10 hours the
RHNCI must:
(i) Evacuate the building or portion of the building affected by
the system outage until the system is back in service, or
(ii) Establish a fire watch until the system is back in service.
(6) Building must have an outside window or outside door in every
sleeping room, and for any building constructed after July 5, 2016 the
sill height must not exceed 36 inches above the floor. Windows in
atrium walls are considered outside windows for the purposes of this
requirement.
(b) * * *
(1) In consideration of a recommendation by the State survey agency
or Accrediting Organization, or at the discretion of the Secretary, may
waive, for periods deemed appropriate, specific provisions of the Life
Safety Code, which would result in unreasonable hardship upon a RNHCI
facility, but only if the waiver will not adversely affect the health
and safety of the patients.
* * * * *
(c) The standards incorporated by reference in this section are
approved for incorporation by reference by the Director of the Office
of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR
part 51. You may inspect a copy at the CMS Information Resource Center,
7500 Security Boulevard, Baltimore, MD or at the National Archives and
Records Administration (NARA). For information on the availability of
this material at NARA, call 202-741-6030, or go to: https://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. If any changes in this edition of the Code are
incorporated by reference, CMS will publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org, 1.617.770.3000.
(i) NFPA 101, Life Safety Code, 2012 edition, issued August 11,
2011;
(ii) TIA 12-1 to NFPA 101, issued August 11, 2011.
(iii) TIA 12-2 to NFPA 101, issued October 30, 2012.
(iv) TIA 12-3 to NFPA 101, issued October 22, 2013.
(v) TIA 12-4 to NFPA 101, issued October 22, 2013.
(2) [Reserved]
0
3. Add Sec. 403.745 to read as follows:
Sec. 403.745 Condition of participation: Building Safety.
(a) Standard: Building Safety. Except as otherwise provided in this
section the RNHCI must meet the applicable provisions and must proceed
in accordance with the Health Care Facilities Code (NFPA 99 and
Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5 and
TIA 12-6).
(b) Standard: Exceptions. Chapters 7, 8, 12, and 13 of the adopted
Health Care Facilities Code do not apply to a RNHCI.
(c) Waiver. If application of the Health Care Facilities Code
required under paragraph (a) of this section would result in
unreasonable hardship for the RNHCI, CMS may waive specific provisions
of the Health Care Facilities Code, but only if the waiver does not
adversely affect the health and safety of individuals.
(d) Incorporation by reference. The standards incorporated by
reference in this section are approved for incorporation by reference
by the Director of the Office of the Federal Register in accordance
with 5 U.S.C. 552(a) and 1 CFR part 51. You may inspect a copy at the
CMS Information Resource Center, 7500 Security Boulevard, Baltimore, MD
or at the National Archives and Records Administration (NARA). For
information on the availability of this material at NARA, call 202-741-
6030, or go to: https://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. If any changes in this
edition of the Code are incorporated by reference, CMS will publish a
document in the Federal Register to announce the changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org, 1.617.770.3000.
(i) NFPA 99, Standards for Health Care Facilities Code of the
National Fire Protection Association 99, 2012 edition, issued August
11, 2011.
(ii) TIA 12-2 to NFPA 99, issued August 11, 2011.
(iii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12-4 to NFPA 99, issued March 7, 2013.
(v) TIA 12-5 to NFPA 99, issued August 1, 2013.
(vi) TIA 12-6 to NFPA 99, issued March 3, 2014.
(2) [Reserved]
PART 416--AMBULATORY SURGICAL SERVICES
0
4. The authority citation for part 416 continues to read as follows:
Authority: Secs. 1102 and 1871 of the Social Security Act (42
U.S.C. 1302 and 1395hh).
0
5. Amend Sec. 416.44 by--
0
a. Revising paragraphs (b)(1) and (2).
0
b. Removing paragraph (b)(4).
0
c. Redesignating paragraph (b)(5) as paragraph (b)(4).
0
d. Revising newly redesignated paragraph (b)(4).
0
e. Adding new paragraphs (b)(5), and (6).
0
f. Redesignating paragraphs (c) and (d) as paragraphs (d) and (e).
0
g. Adding new paragraphs (c) and (f).
The revisions and additions read as follows:
Sec. 416.44 Condition for coverage--Environment.
* * * * *
(b) * * *
(1) Except as otherwise provided in this section, the ASC must meet
the provisions applicable to Ambulatory
[[Page 26897]]
Health Care Occupancies and must proceed in accordance with the Life
Safety Code (NFPA 101 and Tentative Interim Amendments TIA 12-1, TIA
12-2, TIA 12-3, and TIA 12-4).
(2) In consideration of a recommendation by the State survey agency
or Accrediting Organization or at the discretion of the Secretary, may
waive, for periods deemed appropriate, specific provisions of the Life
Safety Code, which would result in unreasonable hardship upon an ASC,
but only if the waiver will not adversely affect the health and safety
of the patients.
* * *
(4) An ASC may place alcohol-based hand rub dispensers in its
facility if the dispensers are installed in a manner that adequately
protects against inappropriate access.
(5) When a sprinkler system is shut down for more than 10 hours,
the ASC must:
(i) Evacuate the building or portion of the building affected by
the system outage until the system is back in service, or
(ii) Establish a fire watch until the system is back in service.
(6) Beginning July 5, 2017, an ASC must be in compliance with
Chapter 21.3.2.1, Doors to hazardous areas.
(c) Standard: Building Safety. Except as otherwise provided in this
section, the ASC must meet the applicable provisions and must proceed
in accordance with the 2012 edition of the Health Care Facilities Code
(NFPA 99, and Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-
4, TIA 12-5 and TIA 12-6).
(1) Chapters 7, 8, 12, and 13 of the adopted Health Care Facilities
Code do not apply to an ASC.
(2) If application of the Health Care Facilities Code required
under paragraph (c) of this section would result in unreasonable
hardship for the ASC, CMS may waive specific provisions of the Health
Care Facilities Code, but only if the waiver does not adversely affect
the health and safety of patients.
* * * * *
(f) The standards incorporated by reference in this section are
approved for incorporation by reference by the Director of the Office
of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR
part 51. You may inspect a copy at the CMS Information Resource Center,
7500 Security Boulevard, Baltimore, MD or at the National Archives and
Records Administration (NARA). For information on the availability of
this material at NARA, call 202-741-6030, or go to: https://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. If any changes in this edition of the Code are
incorporated by reference, CMS will publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org, 1.617.770.3000.
(i) NFPA 99, Standards for Health Care Facilities Code of the
National Fire Protection Association 99, 2012 edition, issued August
11, 2011.
(ii) TIA 12-2 to NFPA 99, issued August 11, 2011.
(iii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12-4 to NFPA 99, issued March 7, 2013.
(v) TIA 12-5 to NFPA 99, issued August 1, 2013.
(vi) TIA 12-6 to NFPA 99, issued March 3, 2014.
(vii) NFPA 101, Life Safety Code, 2012 edition, issued August 11,
2011;
(viii) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ix) TIA 12-2 to NFPA 101, issued October 30, 2012.
(x) TIA 12-3 to NFPA 101, issued October 22, 2013.
(xi) TIA 12-4 to NFPA 101, issued October 22, 2013.
(2) [Reserved]
PART 418--HOSPICE CARE
0
6. The authority citation for part 418 continues to read as follows:
Authority: Secs. 1102 and 1871 of the Social Security Act (42
U.S.C. 1302 and 1395hh).
Sec. 418.108 [Amended]
0
7. Amend Sec. 418.108 by--
0
a. Amending paragraph (a)(2) by removing the reference ``Sec.
418.110(b) and (e)'' and by adding in its place the reference ``Sec.
418.110(b) and (f)''.
0
b. Amending paragraph (b)(1)(ii) by removing the reference ``Sec.
418.110(e)'' and by adding in its place the reference ``Sec.
418.110(f)''.
0
8. Amend Sec. 418.110 by--
0
a. Revising paragraphs (d)(1)(i) and (ii).
0
b. Revising paragraphs (d)(2) and (4).
0
c. Adding paragraphs (d)(5) and (6).
0
d. Redesignating paragraphs (e) through (o) as (f) through (p).
0
e. Adding new paragraph (e).
0
f. Amending newly redesignated paragraph (g)(4) introductory text by
removing the reference ``paragraph (f)(2)(iv) and (f)(2)(v) of this
section'' and adding in its place the reference ``paragraphs (g)(2)(iv)
and (g)(2)(v) of this section''.
0
g. Amending newly redesignated paragraph (n)(9) by removing the
reference ``paragraph (n) of this section'' and adding in its place the
reference ``paragraph (o) of this section''.
0
h. Amending newly redesignated paragraph (n)(13) by removing the
reference ``Sec. 418.110(m)(11)'' and adding in its place the
reference ``paragraph (n)(11) of this section''.
0
i. Adding paragraph (q).
The revisions and additions read as follows:
Sec. 418.110 Condition of participation: Hospices that provide
inpatient care directly.
* * * * *
(d) * * *
(1) * * *
(i) The hospice must meet the applicable provisions and must
proceed in accordance with the Life Safety Code (NFPA 101 and Tentative
Interim Amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4.)
(ii) Notwithstanding paragraph (d)(1)(i) of this section, corridor
doors and doors to rooms containing flammable or combustible materials
must be provided with positive latching hardware. Roller latches are
prohibited on such doors.
(2) In consideration of a recommendation by the State survey agency
or Accrediting Organization or at the discretion of the Secretary, may
waive, for periods deemed appropriate, specific provisions of the Life
Safety Code, which would result in unreasonable hardship upon a hospice
facility, but only if the waiver will not adversely affect the health
and safety of the patients.
* * * * *
(4) A hospice may place alcohol-based hand rub dispensers in its
facility if the dispensers are installed in a manner that adequately
protects against access by vulnerable populations.
(5) When a sprinkler system is shut down for more than 10 hours,
the hospice must:
(i) Evacuate the building or portion of the building affected by
the system outage until the system is back in service, or
(ii) Establish a fire watch until the system is back in service.
(6) Buildings must have an outside window or outside door in every
sleeping room, and for any building constructed after July 5, 2016 the
sill height must not exceed 36 inches above the floor. Windows in
atrium walls are considered outside windows for the purposes of this
requirement.
[[Page 26898]]
(e) Standard: Building Safety. Except as otherwise provided in this
section, the hospice must meet the applicable provisions and must
proceed in accordance with the Health Care Facilities Code (NFPA 99 and
Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5 and
TIA 12-6).
(1) Chapters 7, 8, 12, and 13 of the adopted Health Care Facilities
Code do not apply to a hospice.
(2) If application of the Health Care Facilities Code required
under paragraph (e) of this section would result in unreasonable
hardship for the hospice, CMS may waive specific provisions of the
Health Care Facilities Code, but only if the waiver does not adversely
affect the health and safety of patients.
* * * * *
(q) The standards incorporated by reference in this section are
approved for incorporation by reference by the Director of the Office
of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR
part 51. You may inspect a copy at the CMS Information Resource Center,
7500 Security Boulevard, Baltimore, MD or at the National Archives and
Records Administration (NARA). For information on the availability of
this material at NARA, call 202-741-6030, or go to: https://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. If any changes in this edition of the Code are
incorporated by reference, CMS will publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org, 1.617.770.3000.
(i) NFPA 99, Standards for Health Care Facilities Code of the
National Fire Protection Association 99, 2012 edition, issued August
11, 2011.
(ii) TIA 12-2 to NFPA 99, issued August 11, 2011.
(iii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12-4 to NFPA 99, issued March 7, 2013.
(v) TIA 12-5 to NFPA 99, issued August 1, 2013.
(vi) TIA 12-6 to NFPA 99, issued March 3, 2014.
(vii) NFPA 101, Life Safety Code, 2012 edition, issued August 11,
2011;
(viii) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ix) TIA 12-2 to NFPA 101, issued October 30, 2012.
(x) TIA 12-3 to NFPA 101, issued October 22, 2013.
(xi) TIA 12-4 to NFPA 101, issued October 22, 2013.
(2) [Reserved]
PART 460--PROGRAMS OF ALL INCLUSIVE CARE FOR THE ELDERLY (PACE)
0
9. The authority citation for part 460 continues to read as follows:
Authority: Secs. 1102, 1871, 1894(f), and 1934(f) of the Social
Security Act (42 U.S.C. 1302 and 1395, 1395eee(f), and 1396u-4(f)).
0
10. Amend Sec. 460.72 by--
0
a. Revising paragraphs (b)(1)(i) and (ii).
0
b. Revising paragraph (b)(2)(ii)
0
c. Removing paragraphs (b)(3) and (4).
0
d. Redesignating paragraph (b)(5) as paragraph (b)(3).
0
e. Revising newly redesignated paragraph (b)(3).
0
f. Adding new paragraphs (b)(4), (d), and (e).
The revisions and addition read as follows:
Sec. 460.72 Physical environment.
* * * * *
(b) * * *
(1) * * *
(i) A PACE center must meet the applicable provisions and must
proceed in accordance with the Life Safety Code (NFPA 101 and Tentative
Interim Amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4.)
(ii) Notwithstanding paragraph (b)(1)(i) of this section, corridor
doors and doors to rooms containing flammable or combustible materials
must be provided with positive latching hardware. Roller latches are
prohibited on such doors.
(2) * * *
(ii) In consideration of a recommendation by the State survey
agency or Accrediting Organization or at the discretion of the
Secretary, may waive, for periods deemed appropriate, specific
provisions of the Life Safety Code, which would result in unreasonable
hardship upon a PACE facility, but only if the waiver will not
adversely affect the health and safety of the patients.
(3) A PACE center may install alcohol-based hand rub dispensers in
its facility if the dispensers are installed in a manner that
adequately protects against inappropriate access.
(4) When a sprinkler system is shut down for more than 10 hours in
a 24-hour period, the PACE must:
(i) Evacuate the building or portion of the building affected by
the system outage until the system is back in service, or
(ii) Establish a fire watch until the system is back in service.
* * * * *
(d) Standard: Building Safety. Except as otherwise provided in this
section, a PACE center must meet the applicable provisions and must
proceed in accordance with the Health Care Facilities Code (NFPA 99 and
Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5 and
TIA 12-6).
(1) Chapters 7, 8, 12, and 13 of the adopted Health Care Facilities
Code do not apply to a PACE center.
(2) If application of the Health Care Facilities Code required
under paragraph (d) of this section would result in unreasonable
hardship for the PACE center, CMS may waive specific provisions of the
Health Care Facilities Code, but only if the waiver does not adversely
affect the health and safety of patients.
(e) The standards incorporated by reference in this section are
approved for incorporation by reference by the Director of the Office
of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR
part 51. You may inspect a copy at the CMS Information Resource Center,
7500 Security Boulevard, Baltimore, MD or at the National Archives and
Records Administration (NARA). For information on the availability of
this material at NARA, call 202-741-6030, or go to: https://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. If any changes in this edition of the Code are
incorporated by reference, CMS will publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org, 1.617.770.3000.
(i) NFPA 99, Standards for Health Care Facilities Code of the
National Fire Protection Association 99, 2012 edition, issued August
11, 2011.
(ii) TIA 12-2 to NFPA 99, issued August 11, 2011.
(iii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12-4 to NFPA 99, issued March 7, 2013.
(v) TIA 12-5 to NFPA 99, issued August 1, 2013.
(vi) TIA 12-6 to NFPA 99, issued March 3, 2014.
(vii) NFPA 101, Life Safety Code, 2012 edition, issued August 11,
2011;
(viii) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ix) TIA 12-2 to NFPA 101, issued October 30, 2012.
(x) TIA 12-3 to NFPA 101, issued October 22, 2013.
(xi) TIA 12-4 to NFPA 101, issued October 22, 2013.
(2) [Reserved]
[[Page 26899]]
PART 482--CONDITIONS OF PARTICIPATION FOR HOSPITALS
0
11. The authority citation for part 482 continues to read as follows:
Authority: Secs. 1102, 1871, and 1881 of the Social Security
Act (42 U.S.C. 1302, 1395hh, and 1395rr), unless otherwise noted.
0
12. Amend Sec. 482.41 by--
0
a. Revising paragraphs (b)(1)(i) and ii).
0
b. Revising paragraph (b)(2).
0
c. Removing paragraphs (b)(4) and (b)(5).
0
d. Redesignating paragraphs (b)(6) through (9) as paragraphs (b)(4)
through (7), respectively.
0
e. Revising newly redesignated paragraph (b)(7).
0
f. Adding new paragraphs (b)(8), and (9).
0
g. Redesignating paragraph (c) as paragraph (d).
0
h. Adding new paragraphs (c) and (e).
The revisions and additions read as follows:
Sec. 482.41 Condition of participation: Physical environment.
* * * * *
(b) * * *
(1) * * *
(i) The hospital must meet the applicable provisions and must
proceed in accordance with the Life Safety Code (NFPA 101 and Tentative
Interim Amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4.)
(ii) Notwithstanding paragraph (b)(1)(i) of this section, corridor
doors and doors to rooms containing flammable or combustible materials
must be provided with positive latching hardware. Roller latches are
prohibited on such doors.
(2) In consideration of a recommendation by the State survey agency
or Accrediting Organization or at the discretion of the Secretary, may
waive, for periods deemed appropriate, specific provisions of the Life
Safety Code, which would result in unreasonable hardship upon a
hospital, but only if the waiver will not adversely affect the health
and safety of the patients.
* * * * *
(7) A hospital may install alcohol-based hand rub dispensers in its
facility if the dispensers are installed in a manner that adequately
protects against inappropriate access;
(8) When a sprinkler system is shut down for more than 10 hours,
the hospital must:
(i) Evacuate the building or portion of the building affected by
the system outage until the system is back in service, or
(ii) Establish a fire watch until the system is back in service.
(9) Buildings must have an outside window or outside door in every
sleeping room, and for any building constructed after July 5, 2016 the
sill height must not exceed 36 inches above the floor. Windows in
atrium walls are considered outside windows for the purposes of this
requirement.
(i) The sill height requirement does not apply to newborn nurseries
and rooms intended for occupancy for less than 24 hours.
(ii) The sill height in special nursing care areas of new
occupancies must not exceed 60 inches.
(c) Standard: Building safety. Except as otherwise provided in this
section, the hospital must meet the applicable provisions and must
proceed in accordance with the Health Care Facilities Code (NFPA 99 and
Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5 and
TIA 12-6).
(1) Chapters 7, 8, 12, and 13 of the adopted Health Care Facilities
Code do not apply to a hospital.
(2) If application of the Health Care Facilities Code required
under paragraph (c) of this section would result in unreasonable
hardship for the hospital, CMS may waive specific provisions of the
Health Care Facilities Code, but only if the waiver does not adversely
affect the health and safety of patients.
* * * * *
(e) The standards incorporated by reference in this section are
approved for incorporation by reference by the Director of the Office
of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR
part 51. You may inspect a copy at the CMS Information Resource Center,
7500 Security Boulevard, Baltimore, MD or at the National Archives and
Records Administration (NARA). For information on the availability of
this material at NARA, call 202-741-6030, or go to: https://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. If any changes in this edition of the Code are
incorporated by reference, CMS will publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org, 1.617.770.3000.
(i) NFPA 99, Standards for Health Care Facilities Code of the
National Fire Protection Association 99, 2012 edition, issued August
11, 2011.
(ii) TIA 12-2 to NFPA 99, issued August 11, 2011.
(iii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12-4 to NFPA 99, issued March 7, 2013.
(v) TIA 12-5 to NFPA 99, issued August 1, 2013.
(vi) TIA 12-6 to NFPA 99, issued March 3, 2014.
(vii) NFPA 101, Life Safety Code, 2012 edition, issued August 11,
2011;
(viii) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ix) TIA 12-2 to NFPA 101, issued October 30, 2012.
(x) TIA 12-3 to NFPA 101, issued October 22, 2013.
(xi) TIA 12-4 to NFPA 101, issued October 22, 2013.
(2) [Reserved]
PART 483--REQUIREMENTS FOR STATES AND LONG TERM CARE FACILITIES
0
13. The authority citation for part 483 continues to read as follows:
Authority: Secs. 1102, 1128I, 1819, 1871 and 1919 of the Social
Security Act (42 U.S.C. 1302, 1320a-7, 1395i, 1395hh and 1396r).
Sec. 483.15 [Amended]
0
14. In Sec. 483.15, amend paragraph (h)(4) by removing the reference
``Sec. 483.70(d)(2)(iv) of this part'' and by adding in its place the
reference ``Sec. 483.70(e)(2)(iv)''.
0
15. Amend Sec. 483.70 by--
0
a. Revising paragraphs (a)(1)(i) and ii).
0
b. Revising paragraph (a)(2).
0
c. Removing paragraphs (a)(4) and (5).
0
d. Redesignating paragraphs (a)(6) through (8) as paragraphs (a)(4)
through (6), respectively.
0
e. Revising newly redesignated paragraph (a)(4).
0
f. Adding new paragraphs (a)(7) and (8).
0
g. Redesignating paragraphs (b) through (h) as paragraphs (c) through
(i).
0
h. Adding new paragraphs (b) and (j).
The revisions read as follows:
Sec. 483.70 Physical environment.
* * * * *
(a) * * *
(1) * * *
(i) The LTC facility must meet the applicable provisions and must
proceed in accordance with the Life Safety Code (NFPA 101 and Tentative
Interim Amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4.)
(ii) Notwithstanding paragraph (a)(1)(i) of this section, corridor
doors and doors to rooms containing flammable or combustible materials
must be provided with positive latching hardware. Roller latches are
prohibited on such doors.
[[Page 26900]]
(2) In consideration of a recommendation by the State survey agency
or Accrediting Organization or at the discretion of the Secretary, may
waive, for periods deemed appropriate, specific provisions of the Life
Safety Code, which would result in unreasonable hardship upon a long-
term care facility, but only if the waiver will not adversely affect
the health and safety of the patients.
* * * * *
(4) A long-term care facility may install alcohol-based hand rub
dispensers in its facility if the dispensers are installed in a manner
that adequately protects against inappropriate access.
* * * * *
(7) Buildings must have an outside window or outside door in every
sleeping room, and for any building constructed after July 5, 2016 the
sill height must not exceed 36 inches above the floor. Windows in
atrium walls are considered outside windows for the purposes of this
requirement.
(8) When a sprinkler system is shut down for more than 10 hours,
the ASC must:
(i) Evacuate the building or portion of the building affected by
the system outage until the system is back in service, or
(ii) Establish a fire watch until the system is back in service.
(b) Standard: Building safety. Except as otherwise provided in this
section, the LTC facility must meet the applicable provisions and must
proceed in accordance with the Health Care Facilities Code (NFPA 99 and
Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5 and
TIA 12-6).
(1) Chapters 7, 8, 12, and 13 of the adopted Health Care Facilities
Code do not apply to a LTC facility.
(2) If application of the Health Care Facilities Code required
under paragraph (b) of this section would result in unreasonable
hardship for the LTC facility, CMS may waive specific provisions of the
Health Care Facilities Code, but only if the waiver does not adversely
affect the health and safety of residents.
* * * * *
(j) The standards incorporated by reference in this section are
approved for incorporation by reference by the Director of the Office
of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR
part 51. You may inspect a copy at the CMS Information Resource Center,
7500 Security Boulevard, Baltimore, MD or at the National Archives and
Records Administration (NARA). For information on the availability of
this material at NARA, call 202-741-6030, or go to: https://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. If any changes in this edition of the Code are
incorporated by reference, CMS will publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org, 1.617.770.3000.
(i) NFPA 99, Standards for Health Care Facilities Code of the
National Fire Protection Association 99, 2012 edition, issued August
11, 2011.
(ii) TIA 12-2 to NFPA 99, issued August 11, 2011.
(iii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12-4 to NFPA 99, issued March 7, 2013.
(v) TIA 12-5 to NFPA 99, issued August 1, 2013.
(vi) TIA 12-6 to NFPA 99, issued March 3, 2014.
(vii) NFPA 101, Life Safety Code, 2012 edition, issued August 11,
2011;
(viii) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ix) TIA 12-2 to NFPA 101, issued October 30, 2012.
(x) TIA 12-3 to NFPA 101, issued October 22, 2013.
(xi) TIA 12-4 to NFPA 101, issued October 22, 2013.
(2) [Reserved]
0
16. Amend Sec. 483.470 by--
0
a. Revising paragraphs (j)(1)(i) and (ii).
0
b. Adding paragraphs (j)(1)(iii) and (iv).
0
c. Removing paragraphs (j)(5) and (6).
0
d. Redesignating paragraph (j)(7) as paragraph (j)(5).
0
e. Revising newly redesignated paragraph (j)(5).
0
f. Adding paragraph (m).
The revisions and additions read as follows:
Sec. 483.470 Condition of participation: Physical environment.
* * * * *
(j) * * *
(1) * * *
(i) The facility must meet the applicable provisions of either the
Health Care Occupancies Chapters or the Residential Board and Care
Occupancies Chapter and must proceed in accordance with the Life Safety
Code (NFPA 101 and Tentative Interim Amendments TIA 12-1, TIA 12-2, TIA
12-3, and TIA 12-4.)
(ii) Notwithstanding paragraph (j)(1)(i) of this section, corridor
doors and doors to rooms containing flammable or combustible materials
must be provided with positive latching hardware. Roller latches are
prohibited on such doors.
(iii) Chapters 32.3.2.11.2 and 33.3.2.11.2 of the adopted 2012 Life
Safety Code do not apply to a facility.
(iv) Beginning July 5, 2019, an ICF-IID must be in compliance with
Chapter 33.2.3.5.7.1, Sprinklers in attics, or Chapter 33.2.3.5.7.2,
Heat detection systems in attics of the Life Safety Code.
* * * * *
(5) Facilities that meet the Life Safety Code definition of a
health care occupancy. (i) In consideration of a recommendation by the
State survey agency or Accrediting Organization or at the discretion of
the Secretary, may waive, for periods deemed appropriate, specific
provisions of the Life Safety Code, which would result in unreasonable
hardship upon a residential board and care facility, but only if the
waiver will not adversely affect the health and safety of the patients.
(ii) A facility may install alcohol-based hand rub dispensers if
the dispensers are installed in a manner that adequately protects
against inappropriate access.
(iii) When a sprinkler system is shut down for more than 10 hours,
the ICF-IID must:
(A) Evacuate the building or portion of the building affected by
the system outage until the system is back in service, or
(B) Establish a fire watch until the system is back in service.
(iv) Beginning July 5, 2019, an ICF-IID must be in compliance with
Chapter 33.2.3.5.7.1, sprinklers in attics, or Chapter 33.2.3.5.7.2,
heat detection systems in attics of the Life Safety Code.
(v) Except as otherwise provided in this section, ICF-IIDs must
meet the applicable provisions and must proceed in accordance with the
Health Care Facilities Code (NFPA 99 and Tentative Interim Amendments
TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5 and TIA 12-6).
(A) Chapter 7,8,12 and 13 of the adopted Health Care Facilities
Code does not apply to an ICF-IID.
(B) If application of the Health Care Facilities Code required
under paragraph
(j)(5)(iv) of this section would result in unreasonable hardship
for the ICF-IID, CMS may waive specific provisions of the Health Care
Facilities Code, but only if the waiver does not adversely affect the
health and safety of clients.
* * * * *
(m) The standards incorporated by reference in this section are
approved for incorporation by reference by the Director of the Office
of the Federal
[[Page 26901]]
Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. You may
inspect a copy at the CMS Information Resource Center, 7500 Security
Boulevard, Baltimore, MD or at the National Archives and Records
Administration (NARA). For information on the availability of this
material at NARA, call 202-741-6030, or go to: https://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. If any
changes in this edition of the Code are incorporated by reference, CMS
will publish a document in the Federal Register to announce the
changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org, 1.617.770.3000.
(i) NFPA 99, Standards for Health Care Facilities Code of the
National Fire Protection Association 99, 2012 edition, issued August
11, 2011.
(ii) TIA 12-2 to NFPA 99, issued August 11, 2011.
(iii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12-4 to NFPA 99, issued March 7, 2013.
(v) TIA 12-5 to NFPA 99, issued August 1, 2013.
(vi) TIA 12-6 to NFPA 99, issued March 3, 2014.
(vii) NFPA 101, Life Safety Code, 2012 edition, issued August 11,
2011;
(viii) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ix) TIA 12-2 to NFPA 101, issued October 30, 2012.
(x) TIA 12-3 to NFPA 101, issued October 22, 2013.
(xi) TIA 12-4 to NFPA 101, issued October 22, 2013.
(2) [Reserved]
PART 485--CONDITIONS OF PARTICIPATION: SPECIALIZED PROVIDERS
0
17. The authority citation for part 485 continues to read as follows:
Authority: Secs. 1102 and 1871 of the Social Security Act (42
U.S.C. 1302 and 1395(hh)).
0
18. Amend Sec. 485.623 by--
0
a. Revising paragraphs (d)(1)(i) and (ii).
0
b. Revising paragraph (d)(2).
0
c. Removing paragraphs (d)(5) and (6).
0
d. Redesignating paragraph (d)(7) as paragraph (d)(5).
0
e. Revising newly redesignated paragraph (d)(5).
0
f. Adding paragraphs (d)(6), (7), (e), and (f).
The revisions and additions read as follows:
Sec. 485.623 Condition of participation: Physical plant and
environment.
* * * * *
(d) * * *
(1) * * *
(i) The CAH must meet the applicable provisions and must proceed in
accordance with the Life Safety Code (NFPA 101 and Tentative Interim
Amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4.)
(ii) Notwithstanding paragraph (d)(1)(i) of this section, corridor
doors and doors to rooms containing flammable or combustible materials
must be provided with positive latching hardware. Roller latches are
prohibited on such doors.
(2) In consideration of a recommendation by the State survey agency
or Accrediting Organization or at the discretion of the Secretary, may
waive, for periods deemed appropriate, specific provisions of the Life
Safety Code, which would result in unreasonable hardship upon a CAH,
but only if the waiver will not adversely affect the health and safety
of the patients.
* * * * *
(5) A CAH may install alcohol-based hand rub dispensers in its
facility if the dispensers are installed in a manner that adequately
protects against inappropriate access.
(6) When a sprinkler system is shut down for more than 10 hours,
the CAH must:
(i) Evacuate the building or portion of the building affected by
the system outage until the system is back in service, or
(ii) Establish a fire watch until the system is back in service.
(7) Buildings must have an outside window or outside door in every
sleeping room, and for any building constructed after July 5, 2016 the
sill height must not exceed 36 inches above the floor. Windows in
atrium walls are considered outside windows for the purposes of this
requirement.
(i) The sill height requirement does not apply to newborn nurseries
and rooms intended for occupancy for less than 24 hours.
(ii) Special nursing care areas of new occupancies shall not exceed
60 inches.
(e) Standard: Building safety. Except as otherwise provided in this
section, the CAH must meet the applicable provisions and must proceed
in accordance with the Health Care Facilities Code (NFPA 99 and
Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5 and
TIA 12-6).
(1) Chapters 7, 8, 12, and 13 of the adopted Health Care Facilities
Code do not apply to a CAH.
(2) If application of the Health Care Facilities Code required
under paragraph (e) of this section would result in unreasonable
hardship for the CAH, CMS may waive specific provisions of the Health
Care Facilities Code, but only if the waiver does not adversely affect
the health and safety of patients.
(f) The standards incorporated by reference in this section are
approved for incorporation by reference by the Director of the Office
of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR
part 51. You may inspect a copy at the CMS Information Resource Center,
7500 Security Boulevard, Baltimore, MD or at the National Archives and
Records Administration (NARA). For information on the availability of
this material at NARA, call 202-741-6030, or go to: https://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. If any changes in this edition of the Code are
incorporated by reference, CMS will publish a document in the Federal
Register to announce the changes.
(1) National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169, www.nfpa.org, 1.617.770.3000.
(i) NFPA 99, Standards for Health Care Facilities Code of the
National Fire Protection Association 99, 2012 edition, issued August
11, 2011.
(ii) TIA 12-2 to NFPA 99, issued August 11, 2011.
(iii) TIA 12-3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12-4 to NFPA 99, issued March 7, 2013.
(v) TIA 12-5 to NFPA 99, issued August 1, 2013.
(vi) TIA 12-6 to NFPA 99, issued March 3, 2014.
(vii) NFPA 101, Life Safety Code, 2012 edition, issued August 11,
2011;
(viii) TIA 12-1 to NFPA 101, issued August 11, 2011.
(ix) TIA 12-2 to NFPA 101, issued October 30, 2012.
(x) TIA 12-3 to NFPA 101, issued October 22, 2013.
(xi) TIA 12-4 to NFPA 101, issued October 22, 2013.
(2) [Reserved]
Dated: March 11, 2016.
Andrew M. Slavitt,
Acting Administrator, Centers for Medicare & Medicaid Services.
Dated: March 30, 2016.
Sylvia M. Burwell,
Secretary, Department of Health and Human Services.
[FR Doc. 2016-10043 Filed 5-3-16; 8:45 am]
BILLING CODE 4120-01-P