Energy Conservation Program: Test Procedure for Pumps, 4085-4158 [2016-00039]
Download as PDF
Vol. 81
Monday,
No. 15
January 25, 2016
Part II
Department of Energy
tkelley on DSK3SPTVN1PROD with RULES2
10 CFR Parts 429 and 431
Energy Conservation Program: Test Procedure for Pumps; Final Rule
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00001
Fmt 4717
Sfmt 4717
E:\FR\FM\25JAR2.SGM
25JAR2
4086
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[Docket No. EERE–2013–BT–TP–0055]
RIN 1905–AD50
Energy Conservation Program: Test
Procedure for Pumps
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
On April 1, 2015, the U.S.
Department of Energy (DOE) issued a
notice of proposed rulemaking (NOPR)
to establish new definitions and a new
test procedure for pumps. That
proposed rulemaking serves as the basis
for this final rule. This final rule
establishes a new test procedure for
pumps, as well as associated definitions
and parameters that establish the scope
of applicability of the test procedure.
Specifically, the pumps test procedure
adopted in this final rule incorporates
by reference the test procedure from the
Hydraulic Institute (HI)—standard 40.6–
2014, ‘‘Methods for Rotodynamic Pump
Efficiency Testing’’—with several
clarifications and modifications, related
to measuring the hydraulic power, shaft
power, and electric input power of
pumps, inclusive of electric motors and
any continuous or non-continuous
controls. The new pumps test procedure
will be used to determine the constant
load pump energy index (PEICL) for
pumps sold without continuous or noncontinuous controls and the variable
load pump energy index (PEIVL) for
pumps sold with continuous or noncontinuous controls. The final rule
incorporates certain recommendations
made by the commercial and industrial
pumps (CIP) Working Group, which was
established under the Appliance
Standards Rulemaking Federal Advisory
Committee (ASRAC), as well as
comments submitted by interested
parties in response to the April 2015
pumps test procedure NOPR.
DATES: The effective date of this rule is
February 24, 2016. Compliance with the
final rule will be mandatory for
representations of PEICL, PEIVL, the
constant load pump energy rating
(PERCL), and the variable load pump
energy rating (PERVL) made on or after
July 25, 2016. The incorporation by
reference of certain publications listed
in this rule is approved by the Director
of the Federal Register as of February
24, 2016.
ADDRESSES: The docket, which includes
Federal Register notices, public meeting
attendee lists and transcripts,
tkelley on DSK3SPTVN1PROD with RULES2
SUMMARY:
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
comments, and other supporting
documents/materials, is available for
review at regulations.gov. All
documents in the docket are listed in
the www.regulations.gov index.
However, some documents listed in the
index, such as those containing
information that is exempt from public
disclosure, may not be publicly
available.
A link to the docket Web page can be
found at: https://www1.eere.energy.gov/
buildings/appliance_standards/
product.aspx/productid/44. This Web
page contains a link to the docket for
this document on the regulations.gov
site. The www.regulations.gov Web page
contains simple instructions on how to
access all documents, including public
comments, in the docket.
For further information on how to
review the docket, contact Ms. Brenda
Edwards at (202) 586–2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Ashley Armstrong, U.S.
Department of Energy, Office of Energy
Efficiency and Renewable Energy,
Building Technologies Office, EE–5B,
1000 Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–6590. Email:
pumps@ee.doe.gov.
Jennifer Tiedeman, U.S. Department
of Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue
SW., Washington DC 20585–0121.
Telephone: (202) 287–6111. Email:
Jennifer.Tiedeman@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final
rule incorporates by reference into 10
CFR part 431 the following industry
standards:
(1) FM Class Number 1319, ‘‘Approval
Standard for Centrifugal Fire Pumps
(Horizontal, End Suction Type),’’
approved January 2015.
Copies of FM Class Number 1319 can
be obtained from: FM Global, 1151
Boston-Providence Turnpike, P.O. Box
9102, Norwood, MA 02062, (781) 762–
4300, or by visiting www.fmglobal.com.
(2) American National Standards
Institute (ANSI)/HI 1.1–1.2–2014
(‘‘ANSI/HI 1.1–1.2–2014’’), ‘‘American
National Standard for Rotodynamic
Centrifugal Pumps for Nomenclature
and Definitions;’’ approved October 30,
2014, sections 1.1, ‘‘Types and
nomenclature,’’ and 1.2.9,
‘‘Rotodynamic pump icons.’’
(3) ANSI/HI 2.1–2.2–2014 (‘‘ANSI/HI
2.1–2.2–2014 ’’), ‘‘American National
Standard for Rotodynamic Vertical
Pumps of Radial, Mixed, and Axial
Flow Types for Nomenclature and
Definitions,’’ approved April 8, 2014,
section 2.1, ‘‘Types and nomenclature.’’
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
(4) HI 40.6–2014, (‘‘HI 40.6–2014’’)
‘‘Methods for Rotodynamic Pump
Efficiency Testing,’’ (except for section
40.6.5.3, ‘‘Test report;’’ Appendix A,
section A.7, ‘‘Testing at temperatures
exceeding 30 °C (86 °F);’’ and Appendix
B, ‘‘Reporting of test results
(normative);’’) copyright 2014.
Copies of ANSI/HI 1.1–1.2–2014,
ANSI/HI 2.1–2.2–2014, and HI 40.6–
2014 can be obtained from: the
Hydraulic Institute at 6 Campus Drive,
First Floor North, Parsippany, NJ
07054–4406, (973) 267–9700, or by
visiting www.pumps.org.
(5) National Fire Protection
Association (NFPA) 20–2016, ‘‘Standard
for the Installation of Stationary Pumps
for Fire Protection,’’ 2016 Edition,
approved June 15, 2015.
Copies of NFPA 20–2016 can be
obtained from: the National Fire
Protection Association, 1 Batterymarch
Park, Quincy, MA 02169, (617) 770–
3000, or by visiting www.nfpa.org.
(6) UL 488, (‘‘ANSI/UL 448–2013’’),
‘‘Standard for Safety Centrifugal
Stationary Pumps for Fire-Protection
Service,’’ 10th Edition, June 8, 2007,
including revisions through July 12,
2013.
Copies of ANSI/UL448–2013 can be
obtained from: UL, 333 Pfingsten Road,
Northbrook, IL 60062, (847) 272–8800,
or by visiting https://ul.com.
This material is also available for
inspection at U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Program, Sixth Floor, 950
L’Enfant Plaza SW., Washington, DC
20024, (202) 586–2945, or at https://
energy.gov/eere/buildings/applianceand-equipment-standards-program.
See section IV.N. for additional
information about these standards.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Summary of the Final Rule
III. Discussion
A. Scope
1. Definitions Related to the Scope of
Covered Pumps
2. Equipment Categories
3. Scope Exclusions Based on Application
4. Parameters for Establishing the Scope of
Pumps in This Rulemaking
5. Drivers Other Than Electric Motors
6. Pumps Sold With Single-Phase
Induction Motors
B. Rating Metric: Constant and Variable
Load Pump Energy Index
1. Determination of the Pump Energy
Rating
2. PERSTD: Minimally Compliant Pump
C. Determination of Pump Performance
1. Incorporation by Reference of HI 40.6–
2014
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
2. Minor Modifications and Additions to
HI 40.6–2014
D. Determination of Motor Efficiency
1. Default Nominal Full Load Motor
Efficiency
2. Represented Nominal Full Load Motor
Efficiency for Pumps Sold With Motors
3. Determining Part Load Motor Losses
E. Test Methods for Different Pump
Configurations
1. Calculation-Based Test Methods
2. Testing-Based Methods
F. Representations of Energy Use and
Energy Efficiency
G. Sampling Plans for Pumps
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
1. The Need for, and Objectives of, Today’s
Rule
2. Significant Issues From Interested
Parties in Response to IRFA
3. Revised Assessment of Burden
Associated With This Test Procedure
Final Rule
4. Calculator Comments
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by
Reference
V. Approval of the Office of the Secretary
I. Authority and Background
Pumps are included in the list of
‘‘covered equipment’’ for which the U.S.
Department of Energy (DOE) is
authorized to establish and amend
energy conservation standards and test
procedures. (42 U.S.C. 6311(1)(A))
However, there are not currently any
Federal energy conservation standards
or test procedures for pumps. The
following sections discuss DOE’s
authority to establish test procedures for
pumps and relevant background
information regarding DOE’s
consideration of test procedures for this
equipment.
tkelley on DSK3SPTVN1PROD with RULES2
A. Authority
The Energy Policy and Conservation
Act of 1975 (EPCA), Public Law 94–163,
as amended by Public Law 95–619, Title
IV, Sec. 441(a), established the Energy
Conservation Program for Certain
Industrial Equipment under Title III,
Part C (42 U.S.C. 6311–6317, as
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
codified) 1 2 Included among the various
types of industrial equipment addressed
by EPCA are pumps, the subject of this
document. (42 U.S.C. 6311(1)(A))
Under EPCA, the energy conservation
program consists essentially of four
parts: (1) Testing, (2) labeling, (3)
Federal energy conservation standards,
and (4) certification and enforcement
procedures. The testing requirements
consist of test procedures that
manufacturers of covered products must
use as the basis for (1) certifying to DOE
that their products comply with the
applicable energy conservation
standards adopted under EPCA, (42
U.S.C. 6295(s) and 6316(a)(1)), and (2)
making representations about the
efficiency of that equipment. (42 U.S.C.
6314(d)) Similarly, DOE must use these
test procedures to determine whether
the products comply with any relevant
standards promulgated under EPCA.
DOE is authorized to prescribe energy
conservation standards and
corresponding test procedures for
statutorily covered equipment such as
pumps. While DOE is currently
evaluating whether to establish energy
conservation standards for pumps
(Docket No. EERE–2011–BT–STD–
0031), DOE must first establish a test
procedure that measures the energy use,
energy efficiency, or estimated operating
costs of such equipment. See, generally,
42 U.S.C. 6295(r) and 6316(a).
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered equipment.
EPCA provides that any test procedures
prescribed or amended under this
section shall be reasonably designed to
produce test results that measure energy
efficiency, energy use or estimated
annual operating cost of a covered
product during a representative average
use cycle or period of use, and shall not
be unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
In addition, before prescribing any
final test procedures, DOE must publish
proposed test procedures and offer the
public an opportunity to present oral
and written comments on them. (42
U.S.C. 6314(b)(1)–(2))
In this final rule, DOE is establishing
a test procedure for pumps concurrent
with its ongoing energy conservation
standards rulemaking for this
equipment (See Docket No. EERE–2011–
BT–STD–0031). As discussed further in
section I.B, DOE published a notice of
1 For editorial reasons, Part C was codified as Part
A–1 in the U.S. Code.
2 All references to EPCA in this document refer
to the statute as amended through the Energy
Efficiency Improvement Act of 2015, Public Law
114–11 (April 30, 2015).
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
4087
proposed rulemaking (NOPR) on April
1, 2015 presenting and requesting
public comment on DOE’s proposals
related to pumps definitions, metric,
and test procedure requirements (April
2015 pump test procedure NOPR). 80
FR 17586.
The pumps test procedure adopted in
this final rule includes methods
required to (1) measure the performance
of the covered equipment and (2) use
the measured results to calculate a
pump energy index (PEICL for pumps
sold without continuous or noncontinuous controls or PEIVL for pumps
sold with continuous or non-continuous
controls) to represent the power
consumption of the pump, inclusive of
a motor and any continuous or noncontinuous controls, normalized with
respect to the performance of a
minimally compliant pump. In this final
rule, DOE is also establishing the
specific styles and characteristics of
pumps to which the test procedure
applies.
Manufacturers will be required to
make all representations of pump
efficiency, overall (wire-to-water)
efficiency, bowl efficiency, driver power
input, pump power input (brake or shaft
horsepower), and/or pump power
output (hydraulic horsepower) using
methods that will generate values
consistent with the DOE test procedure
beginning 180 days after the publication
date of this final rule in the Federal
Register. Manufacturers also will be
required to use the new test procedure
and metric when making
representations regarding the PEICL,
PEIVL, PERCL, or PERVL of covered
equipment 180 days after the
publication date of any applicable
energy conservation standards final rule
in the Federal Register. However, DOE
notes that certification of compliance
with any energy conservation standards
for pumps would not be required until
the compliance date of any final rule
establishing such energy conservation
standards. See 42 U.S.C. 6314(d) and
Docket No. EERE–2011–BT–STD–0031.
B. Background
DOE does not currently regulate
pumps. In 2011, DOE issued a Request
for Information (RFI) to gather data and
information related to pumps in
anticipation of initiating rulemakings to
formally consider test procedures and
energy conservation standards for this
equipment. 76 FR 34192 (June 13, 2011).
In February 2013, DOE published a
Notice of Public Meeting and
Availability of the Framework
document to initiate an energy
conservation standard rulemaking for
pumps (78 FR 7304 Feb. 1, 2013) and
E:\FR\FM\25JAR2.SGM
25JAR2
4088
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
held a public meeting to discuss the
Framework document (the ‘‘pumps
Framework public meeting’’).
Following the pumps Framework
public meeting, DOE convened a
Commercial and Industrial Pumps
Working Group (‘‘CIP Working Group’’
or, in context, ‘‘Working Group’’)
through the Appliance Standards
Rulemaking Federal Advisory
Committee (ASRAC) to negotiate
standards and test procedures for
pumps as an alternative to the
traditional notice and comment
rulemaking process that DOE had
already begun. (Docket No. EERE–2013–
BT–NOC–0039) 3 The CIP Working
Group commenced negotiations at an
open meeting on December 18 and 19,
2013, and held six additional meetings
and two webinars to discuss definitions,
metrics, test procedures, and standard
levels for pumps.4 The CIP Working
Group concluded its negotiations on
June 19, 2014, with a consensus vote to
approve a term sheet containing
recommendations to DOE on
appropriate standard levels for pumps
as well as recommendations addressing
issues related to the metric and test
procedure for pumps (‘‘Working Group
recommendations’’).5 Subsequently,
ASRAC voted unanimously to approve
the Working Group recommendations
during a July 7, 2014 webinar.
Following approval of the Working
Group recommendations, DOE
published a NOPR implementing the
recommendations of the CIP Working
Group 6 and proposing a new test
procedure for pumps, as well as
associated definitions and parameters to
establish the applicability of the test
procedure (April 2015 pump test
procedure NOPR). 80 FR 17586 (April 1,
2015). On April 29, 2015, DOE held a
3 Information on the ASRAC, the CIP Working
Group, and meeting dates is available at https://
energy.gov/eere/buildings/appliance-standardsand-rulemaking-federal-advisory-committee.
4 Details of the negotiation sessions can be found
in the public meeting transcripts that are posted to
the docket for the Working Group (https://
www.regulations.gov/#!docketDetail;D=EERE-2013BT-NOC-0039).
5 The term sheet containing the Working Group
recommendations is available in the CIP Working
Group’s docket. (Docket No. EERE–2013–BT–NOC–
0039, No. 92) The ground rules of the CIP Working
Group define consensus as no more than two
negative votes. (Docket No. EERE–2013–BT–NOC–
0039, No. 18 at p. 2) Concurrence was assumed if
a voting member was absent, and overt dissent was
only evidenced by a negative vote. Abstention was
not construed as a negative vote.
6 DOE’s proposals in the April 2015 pumps test
procedure NOPR reflect the intent of the CIP
Working Group recommendations. However, DOE
proposed some slight modifications and significant
additional detail to ensure the technical integrity,
accuracy, repeatability, and enforceability of the
pumps test procedure and scope.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
public meeting to discuss and request
public comment on the April 2015
pumps test procedure NOPR (April 2015
NOPR public meeting).
DOE’s test procedure for pumps,
adopted in this final rule, reflects
certain recommendations of the CIP
Working Group, as well as input from
interested parties received in response
to the April 2015 pumps test procedure
NOPR. Provisions of this final rule that
are directly pertinent to any of the 14
approved Working Group
recommendations will be specified with
a citation to the specific
recommendation number (for example:
Docket No. EERE–2013–BT–NOC–0039,
No. 92, Recommendation #X at p. Y).
Additionally, in developing the
provisions of this final rule, DOE also
has referenced discussions from the CIP
Working Group meetings regarding
potential actions or comments that may
not have been formally approved as part
of the Working Group
recommendations. These references to
discussions or suggestions of the CIP
Working Group not found in the
Working Group recommendations will
have a citation to meeting transcripts
(for example: Docket No. EERE–2013–
BT–NOC–0039, No. X at p. Y).
Finally, in this final rule, DOE
responds to all comments received from
interested parties in response to the
proposals presented in the April 2015
pumps test procedure NOPR, either
during the April 2015 NOPR public
meeting or in subsequent written
comments. In response to the April 2015
pumps test procedure NOPR, DOE
received eight written comments in
addition to the verbal comments made
by interested parties during the April
2015 NOPR public meeting. The
commenters included: Wilo USA, LLC
(Wilo); the Hydraulic Institute (HI); the
National Electrical Manufacturers
Association (NEMA); the Appliance
Standards Awareness Project (ASAP),
Natural Resources Defense Council
(NRDC), Northwest Energy Efficiency
Alliance (NEEA), and Northwest Power
and Conservation Council (NPCC),
collectively referred to herein as the
energy efficiency advocates (EEAs); the
Air-Conditioning, Heating, &
Refrigeration Institute (AHRI); the
Association of Pool & Spa Professionals
(APSP); Pacific Gas and Electric
Company (PG&E), Southern California
Gas Company (SCG), Southern
California Edison (SCE), and San Diego
Gas and Electric Company (SDG&E),
collectively referred to herein as the CA
IOUs. DOE will identify comments
received in response to the April 2015
pumps test procedure NOPR by the
commenter, the number of document as
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
listed in the docket maintained at
www.regulations.gov (Docket No. EERE–
2013–BT–TP–0055), and the page
number of that document where the
comment appears (for example: HI, No.
8 at p. 4). If a comment was made
verbally during the NOPR public
meeting, DOE will also specifically
identify those as being located in the
NOPR public meeting transcript (for
example: HI, NOPR public meeting
transcript, No. 7 at p. 235). This final
rule also contains comments submitted
in response to the pumps energy
conservation standards rulemaking
(Docket No. EERE–2011–BT–STD–0031)
and such comments will be identified
with that docket number.
II. Summary of the Final Rule
In this final rule, DOE is establishing
a new subpart Y to part 431 of Title 10
of the Code of Federal Regulations that
contains definitions and a test
procedure applicable to pumps. This
final rule also contains sampling plans
for pumps for the purposes of making
representations regarding the energy
consumption of applicable pumps and
demonstrating compliance with any
energy conservation standards that DOE
adopts.
DOE notes that equipment meeting
the pump definition is already covered
equipment. In this final rule, DOE is
establishing definitions for the term
pump, certain pump components, and
several categories and configurations of
pumps. While the range of equipment
included in DOE’s definition of pump is
broad, the test procedure established by
this rulemaking is limited to a specific
scope of pumps, as described in section
III.A of this final rule; specifically
certain kinds of rotodynamic pumps 7
for which standards are being
considered in DOE’s energy
conservation standards rulemaking.
(Docket No. EERE–2011–BT–STD–0031)
DOE’s approach adopted in this final
rule establishes a new metric, the pump
energy index (PEI), to rate the energy
performance of pumps subject to this
test procedure. The test procedure
contains methods for determining
constant load pump energy index
(PEICL) for pumps sold without
continuous or non-continuous controls
and the variable load pump energy
index (PEIVL) for pumps sold with either
7 A rotodynamic (or centrifugal) pump is a kinetic
machine that continuously imparts energy to the
pumped fluid by means of a rotating impeller,
propeller, or rotor. This kind of pump is in contrast
to positive-displacement pumps, which have an
expanding cavity on the suction side and a
decreasing cavity on the discharge side that move
a constant volume of fluid for each cycle of
operation.
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
continuous or non-continuous controls.
Both PEICL and PEIVL describe the
weighted average performance of the
rated pump at specific load points,
normalized with respect to the
performance of a minimally compliant
pump without controls.
The test procedure contains methods
to determine the appropriate index for
all equipment for which this test
procedure applies using either
calculation-based methods and/or
testing-based methods. While both
methods include some amount of testing
and some amount of calculation, the
terms ‘‘calculation-based’’ and ‘‘testingbased’’ are used to distinguish between
methods in which the input power to
the pump is determined either by (a)
measuring the bare pump shaft input
power 8 and calculating efficiency, or
losses, of the motor and any continuous
control 9 (i.e., calculation-based method)
or (b) measuring the input power to the
driver,10 or motor, and any continuous
or non-continuous controls 11 for a given
pump directly (i.e., testing-based
method). For both the testing-based and
calculation-based approaches, the test
procedure for pumps established in this
final rule is based on the test methods
contained in HI Standard 40.6–2014,
‘‘Methods for Rotodynamic Pump
Efficiency Testing,’’ (‘‘HI 40.6–2014’’),
with slight modifications as noted in
section III.C.2.
The test procedure also prescribes the
specific categories and configurations of
pumps to which the calculation-based
and testing-based methods are
applicable. As discussed further in
section III.E.2, the testing-based
methods are applicable to all pumps
that are subject to the test procedure,
while the calculation-based methods are
only applicable to (1) pumps sold with
neither a motor nor controls (i.e., ‘‘bare
pump,’’ discussed later in section
III.A.1.a), (2) pumps sold with motors
that are subject to DOE’s energy
conservation standards for electric
motors 12 (with or without continuous
controls), and (3) pumps sold with
submersible motors (with or without
continuous controls).
Regardless of the metric (i.e., PEICL
versus PEIVL) or test method (i.e.,
calculation-based versus testing-based),
the results for the given pump are
divided by the calculated input power
to the motor for a hypothetical pump
that serves an identical hydraulic load
and minimally complies with any
energy conservation standards that DOE
may set as a result of the ongoing
standards rulemaking. (Docket No.
EERE–2011–BT–STD–0031) This
normalized metric results in a value that
is indexed to the standard (i.e., a value
of 1.0 for a pump that is minimally
compliant, and a value less than 1.0 for
a pump that is less consumptive than
the maximum the standard allows).
This final rule also establishes
requirements regarding the sampling
plan and representations for covered
pumps at subpart B of part 429 of Title
10 of the Code of Federal Regulations.
The sampling plan requirements are
similar to those for several other types
of commercial equipment and are
appropriate for pumps based on the
expected range of measurement
uncertainty and manufacturing
tolerances for this equipment. For those
pumps addressed by this test procedure,
DOE is also specifying the energy
consumption or energy efficiency
representations that may be made, in
addition to the regulated metric (PEICL
or PEIVL).
Beginning on the compliance date for
any energy conservation standards that
DOE may set, all pumps within the
scope of those energy conservation
standards would be required to be tested
in accordance with subpart Y of part
431 and must have their testing
performed in a manner consistent with
the applicable sampling requirements.
Manufacturers must make all
representations of pump efficiency,
4089
overall (wire-to-water) efficiency, bowl
efficiency, driver power input, pump
power input (brake or shaft
horsepower), and/or pump power
output (hydraulic horsepower) using
methods that will generate values
consistent with the DOE test procedure
beginning 180 days after the publication
date of this final rule in the Federal
Register. Similarly, all representations
regarding PEICL, PEIVL, PERCL, or PERVL
would be required to be made based on
values consistent with the adopted
pump test procedure 180 days after the
publication date of any final rule
establishing energy conservation
standards for those pumps that are
addressed by the test procedure. See 42
U.S.C. 6314(d). DOE understands that
manufacturers of pumps likely have
historical test data (e.g., existing pump
curves) which were developed with
methods consistent with the DOE test
procedure being adopted in this final
rule. DOE notes that it does not expect
manufacturers to regenerate all of the
historical test data unless the rating
resulting from the historical methods,
which is based on the same
methodology being adopted in this final
rule, would no longer be valid.
III. Discussion
This final rule places a new test
procedure for pumps and related
definitions in a new subpart Y of part
431, and adds new sampling plans and
reporting requirements for this
equipment in a new section 429.59 of 10
CFR part 429. Subpart Y contains
definitions, materials incorporated by
reference, and the test procedure for
certain categories and configurations of
pumps established as a result of this
rulemaking, as well as any energy
conservation standards for pumps
resulting from the ongoing energy
conservation standard rulemaking, as
shown in Table III.1. (Docket No. EERE–
2011–BT–STD–0031)
TABLE III.1—SUMMARY OF RELEVANT PROVISIONS ADDRESSED IN THIS FINAL RULE, THEIR LOCATION WITHIN THE CODE
OF FEDERAL REGULATIONS, AND THE APPLICABLE PREAMBLE DISCUSSION
Applicable preamble
discussion
Proposal
Summary of additions
10 CFR 429.59 * ..................
tkelley on DSK3SPTVN1PROD with RULES2
Location
Sampling Plan ...................
Number of pumps to be tested to rate a pump basic
model and calculation of rating.
8 The term ‘‘pump shaft input power’’ is referred
to as ‘‘pump power input’’ in HI 40.6–2014. The
term ‘‘pump shaft input power’’ is used
synonymously with that term in this document.
9 DOE notes that for non-continuous controls, as
defined in section III.E.1.c, PEIVL can only be
determined using a ‘‘testing-based’’ method. If a
calculation-based method is desired, the pump
would instead be rated as a pump sold with a motor
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
and without speed controls using the PEICL metric.
See section III.E.1.c for further discussion.
10 The input power to the driver is referred to as
‘‘driver power input’’ in HI 40.6–2014. The term
‘‘input power to the driver’’ is used synonymously
with that term in this document.
11 In the case wherein a pump is sold with a
motor equipped with either continuous or noncontinuous controls and is rated using the testingbased method, the input power to the pump would
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
Section III.G.
be determined as the input power to the continuous
or non-continuous control. See section III.E.2.c.
12 All references to ‘‘motors that are subject to the
DOE’s energy conservation standards for electric
motors’’ refer to those motors that are subject to the
energy conservation standards for electric motors at
431.25(g) (as established in the May 2014 medium
electric motor energy conservation standard final
rule. 79 FR 30933 (May 29, 2014)). See section
III.D.1 and III.E.1 for more discussion.
E:\FR\FM\25JAR2.SGM
25JAR2
4090
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
TABLE III.1—SUMMARY OF RELEVANT PROVISIONS ADDRESSED IN THIS FINAL RULE, THEIR LOCATION WITHIN THE CODE
OF FEDERAL REGULATIONS, AND THE APPLICABLE PREAMBLE DISCUSSION—Continued
Applicable preamble
discussion
Location
Proposal
Summary of additions
10 CFR 431.461 ..................
Purpose and Scope ...........
10 CFR 431.462 ..................
Definitions ..........................
10 CFR 431.463 ..................
Incorporation by Reference
10 CFR 431.464 and Appendix A to Subpart Y of
Part 431.
10 CFR 431.466 ..................
Test Procedure ..................
Scope of pump regulations, as well as the proposed
test procedure and associated energy conservation
standards.
Definitions pertinent to establishing equipment classes
and testing applicable classes of pumps.
Description of industry standards incorporated by reference in the DOE test procedure or related definitions.
Instructions for determining the PEICL or PEIVL for applicable classes of pumps.
Energy Conservation
Standards.
Energy conservation standard for applicable classes of
pumps, in terms of PEI and associated C-Value.
Section III.A.
Section III.A.
Sections III.A and III.C.
Sections III.B, III.C, III.D,
and III.E.
Section III.A and Docket
EERE–2011–BT–STD–
0031.
* Note: DOE is also making minor modifications to 10 CFR 429.2; 429.11(a) and (b); 429.12(b)(13); 429.70; 429.72; 429.102; and 429.134 to
apply the general sampling requirements established in these sections to the equipment-specific sampling requirements for pumps at 10 CFR
429.59.
The following sections discuss DOE’s
new provisions regarding testing and
sampling requirements for pumps,
including:
(1) Scope,
(2) rating metric,
(3) determination of pump
performance,
(4) determination of motor efficiency,
(5) test methods for different
combinations of bare pumps, drivers
and controls,
(6) representations, and
(7) sampling plans.
These sections also present any
pertinent comments DOE received in
response to the April 2015 pumps test
procedure NOPR or the parallel pumps
energy conservation standards
rulemaking (Docket No. EERE–2011–
BT–STD–0031), as well as DOE’s
responses to those comments and the
resulting changes to the test procedure
as proposed in the NOPR.
tkelley on DSK3SPTVN1PROD with RULES2
A. Scope
The term ‘‘pump’’ is listed as a type
of covered equipment under EPCA;
however, that term is undefined. See 42
U.S.C. 6311(1)(A). In the April 2015
pumps test procedure NOPR, consistent
with recommendations from the CIP
Working Group (Docket No. EERE–
2013–BT–NOC–0039, No. 92,
Recommendations #4 and 6–8 at pp. 2–
4), DOE proposed definitions for the
term pump, as covered equipment, and
related components of pumps. 80 FR
17586, 17591 (April 1, 2015). In
addition, DOE proposed to define which
pumps would need to be tested using
the test procedure established in this
rulemaking by applying three criteria:
(1) The equipment category; (2) the
application; and (3) applicable
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
performance specifications—i.e.,
horsepower (hp), flow rate, head, design
temperature, and speed restrictions. Id.
In response to DOE’s proposed
definitions and scope of the test
procedure for pumps, HI commented
that it detected no inconsistencies with
the scope of the pump test procedure
and energy conservation standard
rulemakings. (HI, No. 8 at p. 4)
DOE’s criteria for establishing which
pumps will be subject to the test
procedure, including any additional
comments received by interested parties
on those particular topics, are discussed
in sections III.A.1 through III.A.6,
respectively.
1. Definitions Related to the Scope of
Covered Pumps
To help explain the scope for this rule
and the manner in which both the
procedure and related standards will be
applied to different pump
configurations and categories of pumps,
the aforementioned definitions for
pump, certain pump components, and
other specific pump characteristics, are
discussed in the following subsections.
a. Pumps and Related Components
As part of its collective efforts to help
DOE craft an appropriate regulatory
approach to pumps, the CIP Working
Group made a series of
recommendations regarding a variety of
potential definitions that would define
‘‘pump,’’ the covered equipment. In
particular, the Working Group offered a
definition for ‘‘pump’’ along with the
related terms ‘‘bare pump,’’
‘‘mechanical equipment,’’ ‘‘driver,’’ and
‘‘controls.’’ (Docket No. EERE–2013–
BT–NOC–0039, No. 92,
Recommendations #1 and 2 at pp. 1–2)
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
Accordingly, in the April 2015 pumps
test procedure NOPR, DOE proposed
adopting these recommended
definitions with slight modification. 80
FR 17586, 17591 (April 1, 2015).
Specifically, in the April 2015 pumps
test procedure NOPR, DOE proposed the
following terms:
• Pump means equipment that is
designed to move liquids (which may
include entrained gases, free solids, and
totally dissolved solids) by physical or
mechanical action and includes at least
a bare pump and, if included by the
manufacturer at the time of sale,
mechanical equipment, driver, and
controls.
• Bare pump means a pump
excluding mechanical equipment,
driver, and controls.
• Mechanical equipment means any
component of a pump that transfers
energy from a driver to the bare pump.
• Driver means the machine
providing mechanical input to drive a
bare pump directly or through the use
of mechanical equipment. Examples
include, but are not limited to, an
electric motor, internal combustion
engine, or gas/steam turbine.
• Control means any device that can
be used to operate the driver. Examples
include, but are not limited to,
continuous or non-continuous controls,
schedule-based controls, on/off
switches, and float switches.
80 FR 17586, 17591–92 (April 1, 2015).
HI expressed agreement with the
proposed definitions, except for the text
‘‘entrained gases’’ in the proposed
definition for pump. HI indicated that
the text ‘‘entrained gasses’’ should be
changed to ‘‘dissolved gasses’’ because
pumps within scope are not designed to
pump entrained gas, and small amounts
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
of entrained gas would result in a loss
of performance and efficiency. (HI, No.
8 at p. 4)
DOE understands that, whereas
dissolved gases are in solution and
would not appear as bubbles in the
pumped liquid, entrained gases are not
in solution and would appear as bubbles
in the pumped liquid. In addition, DOE
agrees that pumps within the scope of
this rulemaking are not designed to
pump entrained gas. This has been
acknowledged through the definition of
‘‘clean water pump,’’ as described in
section III.A.3 of this final rule, which
specifies that the total gas content of the
water must not exceed the saturation
volume.13 However, the definition for
‘‘pump’’ applies in general to all pumps,
which are covered under EPCA (see 42
U.S.C. 6311(1)(A)), and is broader than
the scope of this rulemaking. Changing
the language in the definition of
‘‘pump’’ from ‘‘dissolved gasses’’ to
‘‘entrained gasses’’ would suggest that
DOE’s coverage of pumps was limited.
In addition, such a change would limit
DOE’s coverage to a subset of the pumps
intended by the Working Group and
proposed in the NOPR. Therefore, DOE
declines to make the requested change.
DOE did not receive comments on
other aspects of the ‘‘pump’’ definition
or on the other terms discussed in this
section. As such, DOE is adopting
definitions for the terms ‘‘pump,’’ ‘‘bare
pump,’’ ‘‘mechanical equipment,’’
‘‘driver,’’ and ‘‘control’’ as proposed in
the April 2015 pumps test procedure
NOPR without further changes.
b. Definition of Categories of Controls
The definition of ‘‘control’’
established in this final rule is broad.
DOE acknowledges the definition may
include many different kinds of
electronic or mechanical devices that
can ‘‘control the driver’’ of a pump (e.g.,
continuous or non-continuous controls,
timers, and on/off switches). These
various controls may use a variety of
mechanisms to control the pump for
operational reasons, which may or may
not result in reduced energy
consumption.
In the April 2015 pumps test
procedure NOPR, DOE proposed
specific test methods for pumps that are
sold with motors that are paired with
controls that adjust the speed of the
driver, as DOE determined that these
were the most common type of controls
that reduced energy consumption in the
field. Similarly, DOE proposed that such
13 In general, entrained gasses, or gas bubbles,
will only form when the total gas content of the
water is above the saturation volume of the liquid.
Otherwise, gases are more likely to stay dissolved
in the liquid and not generate gas bubbles.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
pumps equipped with speed controls
could apply the PEIVL metric. 80 FR
17586, 17592–93 (April 1, 2015).
Additionally, DOE proposed that pumps
sold with motors and controls other
than speed controls 14 would be subject
to the appropriate bare pump and motor
test procedures and rated using PEICL.
Id.
To explicitly establish the kinds of
controls that may apply the PEIVL metric
under the test procedure, DOE proposed
to define the terms ‘‘continuous
control’’ and ‘‘non-continuous control’’
(see sections III.B and III.E for further
discussion of the PEIVL rating metric
and its applicability to pumps with
controls, respectively):
• Continuous control means a control
that adjusts the speed of the pump
driver continuously over the driver
operating speed range in response to
incremental changes in the required
pump flow, head, or power output.15 As
an example, variable speed drives
(VSDs), including variable frequency
drives and electronically commutated
motors (ECMs), meet the definition for
continuous controls.
• Non-continuous control means a
control that adjusts the speed of a driver
to one of a discrete number of noncontinuous preset operating speeds, and
does not respond to incremental
reductions in the required pump flow,
head, or power output. As an example,
multi-speed motors such as two-speed
motors meet the definition for noncontinuous controls.
80 FR 17586, 17592–93 (April 1, 2015).
DOE requested comment on the
proposed definitions of ‘‘continuous
control’’ and ‘‘non-continuous control.’’
DOE also requested comment on the
likelihood of a pump with continuous
or non-continuous controls being
distributed in commerce, but never
being paired with any sensor or
feedback mechanisms that would enable
energy savings. In response, HI
commented that it agrees with the
proposed definitions for continuous
control and non-continuous control, and
that it does not have data on pumps
with speed controls being distributed in
commerce without any sensor or
feedback mechanisms. (HI, No. 8 at p. 4)
During the public meeting, Regal
Beloit requested a clarification related to
DOE’s definitions of continuous control
and non-continuous control.
14 Here and throughout this final rule, DOE uses
the term ‘‘speed controls’’ to refer to continuous
and non-continuous controls, as defined in section
III.A.1.b of this document.
15 HI–40.6, as incorporated by reference, defines
pump power output as ‘‘the mechanical power
transferred to the liquid as it passes through the
pump, also known as pump hydraulic power.’’
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
4091
Specifically, Regal Beloit requested
clarification regarding whether pumps
sold with multi-pole motors and
‘‘single-speed controls, which would be
considered multi-speed,’’ would be
classified as pumps sold with noncontinuous controls. (Regal Beloit,
NOPR public meeting transcript, No. 7
at p. 98). With respect to Regal Beloit’s
use of the term ‘‘single-speed controls,’’
DOE believes that Regal Beloit is
referring to ‘‘multi-speed’’ permanent
split capacitor (PSC) motors, which are
PSC motors that are offered with two or
more discrete speed options. Depending
on the specific model, speeds may be
adjusted manually with a switch or
automatically with a type of control
logic. Similarly, multi-pole motors are
induction motors that are offered with
two or more discrete speed options.
Again, speeds may be adjusted
manually with a switch or automatically
with a type of control logic.
In this final rule, DOE clarifies that,
to the extent multi-pole motors and
multi-speed PSC motors control the
driver speed discretely (via manual
switch or control logic) in response to
incremental reductions in the required
flow, head, or pump power output, such
motors would meet the definition of
non-continuous controls and would be
tested in accordance with the applicable
test procedure for pumps sold with
motors and non-continuous controls
(see section III.E). DOE also clarifies in
this final rule that any control that can
achieve the specified load points on the
reference system curve (see section
III.E.2.c) meets DOE’s definition of
continuous control, as it can achieve the
specific flow rate and head values
specified by the reference system curve
in the test procedure.
CA IOUs asked during the April 2015
NOPR public meeting whether DOE
would consider differentiating between
two-speed and multi-speed motors, and
stated that if more discrete speeds are
available there is more opportunity to
match the pump and motor to the load.
(CA IOUs, NOPR public meeting
transcript, No. 7 at pp. 98–99) DOE
believes that in this context, CA IOUs is
referring to ‘‘multi-speed motors’’ as
motors with more than two discrete
speeds.
DOE believes the definition of noncontinuous control adequately covers all
motors with two or more discrete speeds
that are sold with any control
mechanism that controls the motor
speed discretely (e.g., manual switch or
control logic). Furthermore, the test
procedure for pumps sold with motors
and non-continuous controls, as
proposed in the April 2015 pumps test
procedure NOPR, contains provisions
E:\FR\FM\25JAR2.SGM
25JAR2
4092
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
that will typically allow motors with
three or more speeds to achieve a lower
(less consumptive) PEIVL rating than
motors with only two speeds. This
procedure is outlined in detail in
section III.E.2.c. Consequently, DOE
believes that motors with differing
numbers of discrete speed options are
already differentiated in the proposed
test procedure and has determined that
it is not necessary to further
differentiate between two-speed and
multi-speed motors.
After considering HI’s agreement with
the proposed definitions and the
questions raised by Regal Beloit and CA
IOUs, DOE is adopting, in this final rule,
the definitions for continuous and noncontinuous controls, as proposed in the
April 2015 pumps test procedure NOPR.
tkelley on DSK3SPTVN1PROD with RULES2
c. Definition of Basic Model
In the course of regulating consumer
products and commercial and industrial
equipment, DOE has developed the
concept of a ‘‘basic model’’ to determine
the specific product or equipment
configuration(s) to which the
regulations would apply. For the
purposes of applying pumps
regulations, DOE proposed to define
what constitutes a basic model of pump.
In the April 2015 pumps test
procedure NOPR, DOE defined a basic
model in a manner similar to the
definitions used for other commercial
and industrial equipment, with the
exception of two pump-specific issues.
Specifically, DOE proposed to define
basic model as it applies to pumps to
include all units of a given covered
equipment type (or class thereof)
manufactured by one manufacturer,
having the same primary energy source,
and having essentially identical
electrical, physical, and functional (or
hydraulic) characteristics that affect
energy consumption, energy efficiency,
water consumption, or water efficiency;
except that:
(1) Variation in the number of stages
particular radially split, multi-sage
vertical in-line casing diffuser (RSV) 16
and vertical turbine submersible (VTS)
pump units are sold with would not
result in different basic models; and
(2) pump models for which the bare
pump differs in impeller diameter, or
impeller trim, may be considered a
single basic model.
80 FR 17586, 17593 and 17641 (April 1,
2015).
The first modification to the basic
model definition applies to variation in
16 The acronym RSV abbreviates ‘‘radially split
vertical,’’ which is a key characteristic of the
radially split, multi-stage vertical in-line casing
diffuser equipment category.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
the number of stages for multi-stage bare
pumps,17 which DOE believes will
significantly reduce testing burden and
is consistent with DOE’s proposed test
procedure provision that such pumps be
tested with a specific number of stages,
as discussed in section III.C.2.c. DOE
did not receive any comments on the
exception to the general basic model
definition that different stage versions of
multi-stage pumps would be treated as
the same basic model and, as such, is
adopting this pump-specific provision
as proposed, with minor wording
revisions for clarity.
The second modification to the
typical basic model definition proposed
in the April 2015 pumps test procedure
NOPR was that a trimmed impeller,
though it may impact efficiency, would
not be a basis for requiring different bare
pump models to be rated as unique
basic models.18 DOE also proposed to
base the certified rating for a given
pump basic model on that model’s full
impeller diameter—specifically, all PEI
and PER representations for the
members of a basic model would be
based upon the full impeller model. 80
FR 17586, 17593–94 (April 1, 2015).
This proposal is consistent with the
Working Group recommendation that
the rating of a given pump basic model
should be based on testing at full
impeller diameter only and that DOE
not require testing at reduced impeller
diameters. (Docket No. EERE–2013–BT–
NOC–0039, No. 92, Recommendation #7
at p. 3)
Relevant to this proposed
requirement, DOE proposed to define
the term ‘‘full impeller’’ as it pertains to
the rating of pump models in
accordance with the test procedure.
Specifically, DOE proposed to define
full impeller as the maximum diameter
impeller with which the pump is
distributed in commerce in the United
States or the maximum impeller
diameter represented in the
manufacturer’s literature, whichever is
larger. For pumps that may only be sold
with a trimmed impeller due to a
custom application, DOE proposed to
define the full impeller as the maximum
diameter impeller with which the pump
is distributed in commerce. 80 FR
17586, 17593–94 (April 1, 2015)
Under DOE’s proposed definition of
‘‘full impeller,’’ manufacturers would
also be able to represent a model with
17 The implications of the resulting variation in
motor selection for pumps sold with motors or
motors and controls is discussed in section
III.A.1.d.
18 The implications of the resulting variation in
motor selection for pumps sold with motors or
motors and controls is discussed in section
III.A.1.d.
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
a trimmed impeller as less consumptive
than one with a full impeller. To do so,
they would treat that trimmed impeller
model as a different basic model and
test a representative number of units at
the maximum diameter distributed in
commerce of that trimmed basic model
listing. In such a case, the impeller trim
with which the pump is rated would
become the ‘‘full impeller diameter.’’ In
these cases, manufacturers could elect
to (1) group individual pump units with
bare pumps that vary only in impeller
diameter into a single basic model or (2)
establish separate basic models (with
unique ratings) for any number of
unique impeller trims, provided that the
PEI rating associated with any
individual model were based on the
maximum diameter impeller for that
basic model and that basic model is
compliant with any energy conservation
standards established as part of the
parallel pumps energy conservation
standards rulemaking. (Docket No.
EERE–2011–BT–STD–0031; 80 FR
17586, 17593–94 (April 1, 2015)).
DOE noted that, while manufacturers
would be able to group pump models
with various impeller trims under one
basic model with the same certified PEI
rating based on the full impeller
diameter, all representations of PEI and
PER for any individual model would be
(1) based on testing of the model with
the full impeller diameter in the basic
model and (2) rated using method A.1,
‘‘bare pump with default motor
efficiency and default motor part load
loss curve’’ (explained further in section
III.E), regardless of the actual impeller
size used with a given pump. Id.
At the April 2015 NOPR public
meeting, interested parties representing
HI 19 expressed concern regarding the
option to consider pumps with trimmed
impellers as separate basic models.
Specifically, one HI representative from
Patterson Pump Company noted that the
premise was contrary to the Working
Group’s agreement that all
representations for PEI would be done
using full impeller diameter, not
trimmed impeller diameter. Another HI
representative from Xylem (Mark
Handzel) stated that reporting is greatly
simplified if only reported for full
impeller diameter. (HI, NOPR public
meeting transcript, No. 7 at pp. 29, 32).
The CA IOUs responded that the
Working Group had only agreed to what
was going to be required for reporting
on a mandatory basis, and that its
19 Several interested parties identified themselves
as representing HI at the April 2015 NOPR public
meeting, including Bob Barbour from TACO, Inc.;
HI representatives from Xylem (Mark Handzel and
Raul Ruzicka), and Al Huber from Patterson Pump
Company.
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
preference was to maintain the
flexibility for manufacturers to
voluntarily report the information for
pumps with trimmed impellers. (CA
IOUs, NOPR public meeting transcript,
No. 7 at pp. 34, 36) Furthermore, in its
written comments, HI agreed with the
proposed definition of the term ‘‘basic
model,’’ which allows manufacturers
the option of rating pumps with
trimmed impellers as a single basic
model or separate basic models. (HI, No.
8 at p. 4) HI also agreed with DOE’s
proposed definition of full impeller and
the proposal that all pump models be
rated in a full impeller configuration
only. (HI, No. 8 at p. 5)
In response, DOE reaffirms that only
reporting PEI at full impeller diameter
will be mandatory. Given that some
interested parties stated that they prefer
maintaining the option of rating pumps
with trimmed impellers as separate
basic models, and HI did not indicate
concern with this option in the written
comments, DOE is maintaining the
option to rate pumps with trimmed
impellers as separate basic models in
this final rule. Furthermore, DOE notes
that in the case a manufacturer chooses
to rate pumps with trimmed impellers
as separate basic models, the full
impeller definition is still applicable
and all representations regarding the PEI
and PER must be based on the ‘‘full
impeller’’ diameter for that basic model.
Upon further review of the proposed
definition for ‘‘full impeller,’’ DOE has
determined that the language within the
definition is duplicative, and therefore,
potentially confusing. Specifically, in
the proposed definition, DOE referred to
both distribution in commerce and
representations in manufacturer
literature. However, DOE notes that 42
U.S.C. 4291(16) defines distribution in
commerce as meaning ‘‘to sell in
commerce, to import, to introduce or
deliver for introduction into commerce,
or to hold for sale or distribution after
introduction into commerce.’’ This
definition encompasses making
advertising materials such as
representations in manufacturer
literature. Accordingly, DOE has revised
the definition for full impeller diameter
as set forth in the regulatory text of this
rule (10 CFR 431.62).
d. Basic Models of Pumps Sold With
Motors or Motors and Speed Controls
In the April 2015 pumps test
procedure NOPR, DOE noted that, for
pumps sold with motors and pumps
sold with motors and continuous or
non-continuous controls, pump
manufacturers may pair a given pump
with several different motors that have
different performance characteristics. 80
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
FR 17586, 17594 (April 1, 2015). Under
the definition of basic model proposed
in the April 2015 pumps test procedure
NOPR and discussed in section III.A.1.c,
each unique pump and motor pairing
represents a unique basic model.
However, DOE noted that, consistent
with DOE’s practice with other products
and equipment, pump manufacturers
may elect to group similar individual
pump models within the same
equipment class into the same basic
model to reduce testing burden,
provided all representations regarding
the energy use of pumps within that
basic model are identical and based on
the most consumptive unit. See 76 FR
12422, 12423 (March 7, 2011). In
addition, consistent with DOE’s
treatment of variation in the number of
stages for multi-stage RSV and VTS
pumps and impeller trim, in the April
2015 pump test procedure NOPR, DOE
proposed that variation in motor sizing
as a result of different impeller trims or
different number of stages for multistage pumps would not serve as a basis
for differentiating basic models. 80 FR
17586, 17593 (April 1, 2015)
In response, HI recommended that
DOE clarify the definition of ‘‘basic
model,’’ stating that ‘‘pump
manufacturers may pair a given pump
with several different motors with
different performance characteristics,
and can include all combinations under
one basic model as long as the
representations regarding the energy use
is based on the most consumptive unit
for each given pole speed, given clean
water with a specific gravity of 1.0 . . .
[A]s variation in impeller trim of the
bare pump does not constitute a
characteristic that would differentiate
basic models, variation in motor sizing
as a result of different impeller trims
would also not serve as a basis for
differentiating basic models.’’ (HI, No. 8
at p. 5)
In general, DOE agrees with HI’s
interpretation. DOE agrees with HI that
pump manufacturers may pair a given
pump with several different motors with
different performance characteristics,
and can include all combinations under
one basic model if the certification of
energy use and all representations made
by the manufacturer, are based on the
most consumptive bare pump/motor
combination for each basic model and
are determined in accordance with the
DOE test procedure and applicable
sampling plans. Furthermore, because
variation in impeller trim of the bare
pump is not a basis for requiring models
to be rated as unique basic models, DOE
agrees that variation in the horsepower
rating of the paired motor as a result of
different impeller trims within a basic
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
4093
model would also not necessarily be a
basis for requiring units to be rated as
unique basic models. Similarly since
RSV and VTS pumps may be sold with
varying numbers of stages, the
horsepower rating of the paired motor
may also vary correspondingly. DOE
notes that this variation in motor
horsepower does not necessarily
constitute a characteristic that will
define separate basic models.
However, variation in motor sizing
(i.e., horsepower rating) may also be
associated with variation in motor
efficiency, which is a performance
characteristic; typically larger motors
are more efficient than smaller motors.
For this reason, in response to HI, DOE
clarifies that in order to group pumps
sold with motors (or motors and
controls) into a single basic model (in
contrast to grouping bare pumps with
variations in impeller trim into a single
basic model, as discussed in the
previous section), each motor offered in
a pump included in that basic model
must have motor efficiency rated at the
Federal minimum (see the appropriate
table for NEMA Design B motors at 10
CFR 431.25) 20 or the same number of
bands above the Federal minimum for
each respective motor horsepower (see
Table 3 of Appendix A to Subpart Y of
Part 431).) 21 For example, the Federal
minimum for a NEMA Design B 5 HP,
2-pole, enclosed motor in 10 CFR 431.25
is 88.5. A manufacturer is rating the
pump and motor combination with a
90.2 percent efficient motor. In Table 3
of Appendix A to Subpart Y of Part 431,
90.2 is two bands above 88.5. Therefore,
for a NEMA Design B 3 HP, 2-pole
enclosed motor, in order to be
considered as the same basic model, the
manufacturer cannot distribute it with a
motor with an efficiency less than 88.5
percent, which in Table 3 is two bands
above the Federal minimum. If the
manufacturer wishes to rate it with a
less efficient motor, it must be rated as
a separate basic model. This approach
will ensure that the PEI and PER
representations for the entire basic
model will be representative of the
performance across various impeller
trims and motor horsepower. DOE has
added this clarification to the definition
of basic model.
DOE did not receive any other
comments from interested parties
regarding basic models for pumps sold
20 For submersible motors, refer to the default
motor efficiency values in this test procedure,
shown in Table 2 of Appendix A to Subpart Y of
Part 431, with further discussion in section
III.D.1.b.
21 See section III.D.1.b for further discussion of
Table 3.
E:\FR\FM\25JAR2.SGM
25JAR2
4094
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
with motors or motors and speed
controls.
a. Definitions of Pump Equipment
Categories
As noted, in the April 2015 pumps
2. Equipment Categories
test procedure NOPR, DOE proposed
In the April 2015 pumps test
specific definitions for the five
categories of pumps (i.e., ESCC, ESFM,
procedure NOPR, DOE proposed that
IL, RSV, and VTS) to establish the
the test procedure be applicable to the
pumps to which the proposed test
following pump equipment categories:
procedure is applicable. 80 FR 17586,
end suction close-coupled (ESCC), end
17595–96 and 17641–42 (April 1, 2015).
suction frame mounted (ESFM), in-line
To assist in defining these five pump
(IL), RSV, and VTS pumps. 80 FR
categories, DOE also proposed the
17586, 17594–95 (April 1, 2015). DOE
following definitions for several specific
also proposed that the test procedure
characteristics of the five pumps
would not be applicable to certain
categories for which the test procedure
categories of pumps, including
is applicable—namely rotodynamic
circulators, dedicated purpose pool
pump, single-axis flow pump, and end
pumps, axial/mixed flow pumps, and
suction pump:
positive displacement pumps. Id. at
• Rotodynamic pump means a pump
17597. These proposals were based on
in which energy is continuously
the recommendation of the Working
imparted to the pumped fluid by means
Group. (Docket No. EERE–2013–BT–
of a rotating impeller, propeller, or
NOC–0039, No. 92, Recommendation
rotor.
#4, 5A, 5B, and 6 at p. 2) DOE also noted
• Single axis flow pump means a
that, while intended to be consistent
pump in which the liquid inlet of the
with this test procedure, the scope of
bare pump is on the same axis as the
any energy conservation standards
liquid discharge of the bare pump.
• End suction pump means a
proposed for pumps would be discussed
rotodynamic pump that is single-stage
as part of a separate rulemaking. Id.
and in which the liquid enters the bare
DOE requested comment on the
pump in a direction parallel to the
proposed applicability of the test
impeller shaft and on the end opposite
procedure to the five pump equipment
the bare pump’s driver-end.
categories noted above, namely ESCC,
Id.
ESFM, IL, RSV, and VTS pumps. HI
Based on these three definitions
commented that it agrees that the
proposed test procedure was applicable involving general pump characteristics,
DOE proposed to define the following
to the five pump equipment categories
five pump equipment categories to
noted. (HI, No. 8 at p. 5) HI also agreed
which the test procedure applies as
that circulators and pool pumps should
follows:
be handled under two separate
(1) End suction frame mounted
rulemakings. (HI, No. 8 at p. 7) No other
(ESFM) pump means an end suction
interested parties provided comments
pump wherein:
on the scope of applicability of the
(a) the bare pump has its own
proposed test procedure. As the
impeller shaft and bearings and so does
amendments DOE is making to the
not rely on the motor shaft to serve as
proposed test procedure provisions do
the impeller shaft;
not significantly change the test
(b) the pump requires attachment to a
methods or approach specified in the
rigid foundation to function as designed
pump test procedure, and receiving no
and cannot function as designed when
dissenting comments, DOE adopts its
supported only by the supply and
discharge piping to which it is
proposal that the test procedure
connected; and
provisions established in this final rule
(c) the pump does not include a
are applicable to the same scope of
basket strainer.
pumps discussed in the April 2015
Examples include, but are not limited
pumps test procedure NOPR. 80 FR
to, pumps complying with ANSI/HI
17586, 17591–17601 (April 1, 2015).
nomenclature OH0 and OH1, as
The specific definitions and
described in ANSI/HI 1.1–1.2–2014.
specifications DOE proposed to
(2) End suction close-coupled (ESCC)
establish the scope of the test procedure, pump means an end suction pump in
and any comments DOE received on
which:
those definitions, are discussed in the
(a) the motor shaft also serves as the
subsequent sections III.A.2.a, III.A.2.b,
impeller shaft for the bare pump;
III.A.2.c, and III.A.2.d. The final
(b) the pump requires attachment to a
equipment category definitions DOE is
rigid foundation to function as designed
adopting in this final rule are presented and cannot function as designed when
supported only by the supply and
in section III.A.2.e.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
discharge piping to which it is
connected; and
(c) the pump does not include a
basket strainer.
Examples include, but are not limited
to, pumps complying with ANSI/HI
nomenclature OH7, as described in
ANSI/HI 1.1–1.2–2014.
(3) In-line (IL) pump means a singlestage, single axis flow, rotodynamic
pump in which:
(a) liquid is discharged through a
volute in a plane perpendicular to the
impeller shaft; and
(b) the pump requires attachment to a
rigid foundation to function as designed
and cannot function as designed when
supported only by the supply and
discharge piping to which it is
connected.
Examples include, but are not limited
to, pumps complying with ANSI/HI
nomenclature OH3, OH4, or OH5, as
described in ANSI/HI 1.1–1.2–2014.
(4) Radially split, multi-stage, vertical,
in-line, diffuser casing (RSV) pump
means a vertically suspended, multistage, single axis flow, rotodynamic
pump in which:
(a) liquid is discharged in a plane
perpendicular to the impeller shaft;
(b) each stage (or bowl) consists of an
impeller and diffuser; and.
(c) no external part of such a pump is
designed to be submerged in the
pumped liquid.
Examples include, but are not limited
to, pumps complying with ANSI/HI
nomenclature VS8, as described in the
ANSI/HI 2.1–2.2–2008).
(5) Vertical turbine submersible (VTS)
pump means a single-stage or multistage rotodynamic pump that is
designed to be operated with the motor
and stage(s) (or bowl(s)) fully submerged
in the pumped liquid, and in which:
(a) each stage of this pump consists of
an impeller and diffuser and
(b) liquid enters and exits each stage
of the bare pump in a direction parallel
to the impeller shaft.
Examples include, but are not limited
to, pumps complying with ANSI/HI
nomenclature VS0, as described in
ANSI/HI 2.1–2.2–2008.
Id.
In the April 2015 pumps test
procedure NOPR, DOE requested
comment on the proposed equipment
category definitions and related
terminology. Comments DOE received
on these definitions and DOE’s
responses to those comments are
discussed in the following subsections.
DOE notes that comments regarding the
exclusion of circulators and dedicatedpurpose pool pumps, which are
addressed in sections III.A.2.b and
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
III.A.2.c of this final rule, are also
pertinent to the definitions of the ESCC,
ESFM, IL, RSV, and VTS equipment
categories and are also discussed in this
section.
HI Nomenclature
DOE noted that any references to HI
nomenclature in ANSI/HI 1.1–1.2–2014
or ANSI/HI 2.1–2.2–2008 were
incorporated into the definitions of the
aforementioned pump equipment
categories as examples only and
clarified that, in cases where there is a
conflict between the description
provided in ANSI/HI 1.1–1.2–2014 or
ANSI/HI 2.1–2.2–2008, as applicable,
and DOE’s definitions established at 10
CFR 431.462, the language in the
regulatory text would prevail. Id.
DOE requested comment on whether
the references to ANSI/HI nomenclature
are necessary as part of the equipment
definitions in the regulatory text;
whether such references would be likely
to cause confusion due to
inconsistencies; and whether discussing
the ANSI/HI nomenclature in this
preamble would provide sufficient
reference material for manufacturers
when determining the appropriate
equipment category for their pump
models. At the April 2015 NOPR public
meeting, an HI representative from
Xylem (Mark Handzel) advocated the
use of ANSI/HI nomenclature without
new DOE nomenclature. (HI, NOPR
public meeting transcript, No. 7 at p. 63)
In written comments, HI indicated that
it affirms the importance of any pump
rulemaking using ANSI/HI designations
and nomenclature, citing common usage
by U.S. pump manufacturers,
distributors, engineering consulting
firms, and pump users. (HI, No. 8 at p.
6) HI also commented that all references
to ANSI/HI 2.1–2.2–2008 should be
changed to ANSI/HI 2.1–2.2–2014
because the latter is the current version.
(HI, No. 8 at p. 13) The EEAs
commented that they support the
proposed definitions for the pump types
to which the proposed test procedures
would be applicable; they also indicated
that they believe this approach would
both limit the risk that a manufacturer
could make a small change to a pump
design in order to avoid having to meet
the pump efficiency standards and help
to provide clarity to manufacturers.
(EEAs, No. 10 at p. 1)
After reviewing the comments, DOE is
maintaining its definitions for the pump
equipment categories presented in the
April 2015 pumps test procedure NOPR,
which references the ANSI/HI
nomenclature as illustrative only. DOE
believes that this approach strikes the
best balance between the needs of the
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
industry and the ability of DOE to
enforce its regulations for pumps
appropriately. DOE reiterates that the
scope of the rulemaking is not limited
to pumps meeting the ANSI/HI
nomenclature referenced in the
definitions and that any pump model
meeting one of the DOE equipment
category definitions is considered to be
part of that equipment category,
whether or not the pump is considered
by the industry to be part of one of the
referenced ANSI/HI nomenclature
subgroups or a different subgroup.
Further, in preparing this final rule,
DOE reviewed the ANSI/HI
nomenclature to ensure that all
applicable categories of pumps that
would meet DOE’s proposed equipment
definitions were listed. Upon review,
DOE noticed that the styles of pumps
identified as OH2, OH3A, OH5A, and
OH6 in ANSI/HI 1.1–1.2–2014 may be
considered by some parties to meet
ESCC, ESFM, or IL pump definitions
because they share some similar
characteristics with those categories of
pumps. DOE wishes to clarify that the
styles of pumps generally considered to
be OH2, OH3A, OH5A, and OH6 are
covered equipment in that they meet the
definition of ‘‘pump,’’ but are not
subject to the test procedure established
in this final rule, since they do not fall
within the specific scope of pumps to
which the test procedure is applicable.
Specifically, DOE determined that
OH3A and OH5A are not within the
scope of this rule because they do not
meet the definition of end-suction pump
(i.e., liquid does not enter pump in a
direction parallel to the impeller shaft
due to inlet adapter) and do not meet
the definition of IL pump (i.e., the flow
inlet and outlet are on the same plane
but not on the same axis). In addition,
DOE believes that the majority of these
OH3A and OH5A pumps are nonclogging and thus would also be
excluded because they do not meet
DOE’s definition of clean water pump,
as discussed further in section III.A.3.
Regarding OH6 pumps, DOE notes
that such pumps include a high speed
integral gear such that the impeller shaft
will rotate faster than the driver. While
these pumps meet the definition of IL
pumps, they are excluded from the
scope of pumps subject to this test
procedure because they operate at
impeller speeds greater than the
nominal speed limitations discussed in
section III.A.4 and III.C.2.c. In addition,
the impellers and drivers of OH6 pumps
rotate at different speeds and, thus,
would be excluded based on DOE’s
revised specifications regarding the
impeller and driver rotating speeds of
pumps addressed by this test procedure
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
4095
(see section III.A.4). Similarly, DOE
notes that OH2 pumps would meet the
definition of an ESFM pump, but would
be excluded because such pumps are
designed specifically for pumping
hydrocarbon fluids, as noted by the
American Petroleum Institute Standard
610 certification and, as such, are not
clean water pumps. For these reasons,
DOE is not referencing OH2, OH3A,
OH5A, or OH6 nomenclature in the
definitions of ESCC, ESFM, IL, RSV, and
VTS established in this rulemaking.
Finally, DOE notes that in April 2014,
HI released an updated version of ANSI/
HI 2.1–2.2, ANSI/HI 2.1–2.2–2014. DOE
reviewed ANSI/HI 2.1–2.2–2014 and
found the documents to be substantially
the same as ANSI/HI 2.1–2.2¥2008,
with the exception of the addition of a
new definition and description for pipe
length, more detailed characteristics
identified on some of the figures, and
slight reorganization of the sections to
improve document flow. DOE notes that
none of these minor changes affect the
content pertinent to the references to
ANSI/HI 2.1–2.2–2008 nomenclature
proposed in the April 2015 pumps test
procedure NOPR. As such, DOE believes
that it is appropriate to reference the
most up-to-date industry standard and
is updating all references in the RSV
and VTS equipment category definitions
from ANSI/HI 2.1–2.2–2008 to ANSI/HI
2.1–2.2–2014 in this final rule.
Specific Styles of IL Pumps
In response to DOE’s request for
comment on all proposed pump
definitions in general, HI commented
that twin head pumps, which combine
two impeller assemblies into a common
single axis flow casing with a single
inlet and discharge, were not included
in DOE’s definitions and should be
added to the rulemaking scope. (HI, No.
8 at p. 3) DOE notes that such pumps
are a style of IL pump and, thus subject
to the test procedure and standards as
an IL pump, but DOE understands that
this inclusion was not explicitly laid out
in the NOPR. As such, twin head pumps
meet the definition of IL pumps as
proposed in the April 2015 pumps test
procedure NOPR. Specifically, twin
head pumps are single-axis flow,
rotodynamic pumps with single-stage
impellers and in which liquid is
discharged through a volute in a plane
perpendicular to the impeller shaft.
However, to clarify the applicability of
the IL pump definition and DOE’s pump
test procedure to twin head pumps,
DOE is adopting in this final rule a
definition of twin head pump as set
forth in the regulatory text of this rule
(10 CFR 431.62).
E:\FR\FM\25JAR2.SGM
25JAR2
4096
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
In this final rule, DOE is also
clarifying the testing and certification
requirements for such pumps. For the
purposes of applying the DOE test
procedure to and certifying twin head
pumps, DOE is clarifying that such
pumps should be tested configured with
a single impeller assembly, as discussed
further in section III.C.2.c.
RSV Pump Definition
DOE also requested specific comment
on whether it needed to clarify the flow
direction to distinguish RSV pumps
from other similar pumps when
determining test procedure and
standards applicability and on whether
any additional language would be
necessary in the proposed RSV
definition in the April 2015 pumps test
procedure NOPR to make the exclusion
of immersible pumps clearer. HI
commented that it believes the icons
shown and the definition found in
ANSI/HI 2.1–2.2–2014 provide
sufficient clarity to the flow direction,
and that it does not believe any
additional language is necessary. (HI,
No. 8 at pp. 6–7) DOE reviewed the
figures in ANSI/HI 2.1–2.2–2014 and
believes that the figure is illustrative of
the general equipment characteristics
for RSV pumps. The description
accompanying the figure also describes
the manner in which liquid enters and
exits the pump. Specifically, section
2.1.3.6 of ANSI/HI 2.1–2.2–2014 states
that, for RSV pumps, ‘‘fluid enters one
nozzle of the in-line casing and is
directed to the inlet of an internal multistage diffuser pump. After traveling
through multiple stages, the liquid exits
at the top stage of the pump where the
flow is redirected via the outer sleeve to
the opposing nozzle of the in-line
casing.’’ As DOE’s definition of RSV
pump references the figures and
description in ANSI/HI 2.1–2.2–2014,
and this description of flow path
through the pump is not inconsistent or
conflicting with DOE’s definition of
RSV pump, DOE does not believe that
further clarification is necessary in this
regard.
Regarding the exclusion of immersible
pumps, HI commented that it did not
believe any additional clarification was
necessary. (HI, No. 8 at pp. 6–7)
Therefore, in this final rule, DOE has
determined that the adopted language is
sufficient to exclude any immersible
pumps from treatment as an RSV pump
for purposes of DOE’s regulations.
VTS Equipment Terminology
Upon review of CIP Working Group
transcripts and slides, DOE also
determined that interested parties had
requested the equipment category
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
‘‘vertical turbine submersible’’ be
termed ‘‘submersible turbine,’’ given
that some of these pumps are installed
horizontally. (CIP Working Group
transcript, No. 14 at p. 263) DOE notes
that the definition proposed for vertical
turbine submersible is silent as to
installation orientation and, as a result,
would include horizontally installed
pumps. DOE believes that referring to
submersible turbine pumps as ‘‘vertical
turbine submersible,’’ when
horizontally mounted submersible
turbine pumps are also included in the
equipment category, as defined, could
lead to confusion among manufacturers
and in the market place. As such, and
given that changing the defined term
from vertical turbine submersible to
submersible turbine would not change
the scope of the definition, DOE is
revising the nomenclature in this final
rule to match that used in the CIP
Working Group, which more accurately
describes the subject equipment. In the
preamble to this final rule, DOE has
retained the VTS abbreviation for the
submersible turbine equipment category
for consistency with the April 2015
pump test procedure NOPR, pumps
energy conservation standards
rulemaking (Docket No. EERE–2011–
BT–STD–0031), and all Working Group
discussions and recommendations to
date (Docket No. EERE–2013–BT–NOC–
0039). However, DOE is adopting the
acronym ‘‘ST’’ for the regulatory text for
long-term consistency with the defined
term.
ESFM Equipment Terminology
Similarly, the ‘‘end suction frame
mounted’’ category proposed in the
NOPR had been referred to as ‘‘end
suction frame mounted/own bearings’’
in the CIP Working Group
documentation. (See for example,
EERE–2013–BT–NOC–0039–0092 at p. 2
and EERE–2013–BT–NOC–0039–0031 at
p. 4) The proposed end suction frame
mounted definition would be inclusive
of own bearings pumps, or any endsuction pump that ‘‘does not rely on the
motor shaft to serve as the impeller
shaft.’’ 80 FR 17586, 17641 (April 1,
2015). DOE intended the ESFM and
ESCC equipment category definitions
proposed in the April 2015 pumps test
procedure NOPR to be mutually
exclusive, whereby pumps that are close
coupled to the motor and share a single
impeller and motor shaft would be part
of the ESCC equipment category, and all
other end suction pumps that are
mechanically-coupled to the motor and
for which the bare pump and motor
have separate shafts would be part of
the ESFM equipment category.
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
DOE understands that there are
several coupling and mounting methods
for pairing a bare pump and motor, in
addition to frame mounting, and that
referring to the ESFM equipment
category based only on that criteria may
be misleading. To clarify the
applicability of the previously defined
end suction frame mounted equipment
category to own bearing pumps, and
given that changing the term itself
would not change the scope of the
definition, DOE is revising the
nomenclature in this final rule to match
that used in the CIP Working Group.
Therefore, in this final rule, DOE is
defining this equipment category as
end-suction frame mounted/own
bearing and adding to the definition the
term ‘‘mechanically-coupled’’ to clarify
that the ESFM equipment is, in fact,
inclusive of many coupling methods.
DOE is further adopting a specific
definition for ‘‘mechanically-coupled,’’
as mutually exclusive with ‘‘closecoupled,’’ to explicitly establish the
coupling methods to which the ESFM
equipment category applies. The
definition of mechanically-coupled
consists of text that was in the proposed
definition for ESFM and does not
change the scope of ESFM from the
proposal.
b. Circulators
Circulators, which are a specific kind
of rotodynamic pump, are small, lowhead pumps similar to the IL
configuration pumps that are generally
used to circulate water in hydronic
space conditioning or potable water
systems in buildings.
The CIP Working Group
recommended that circulators be
addressed as part of a separate
rulemaking process that would involve
informal negotiation between interested
parties followed by an ASRAC-approved
negotiation. (Docket No. EERE–2013–
BT–NOC–0039, No. 92,
Recommendation #5A at p. 2)
In the April 2015 test procedure
NOPR, DOE also proposed to exclude
circulators from the rulemaking, and
proposed a definition that would be
mutually exclusive from the other
pumps in the rulemaking. Specifically,
DOE proposed definitions for
circulators, ESCC, ESFM, and IL pumps
that were mutually exclusive, based on
the assumption that circulators require
only the support of the supply and
discharge piping to function as
designed, whereas ESCC, ESFM, and IL
pumps require attachment to a rigid
foundation to function as designed. In
response to the proposed circulator
definition, DOE received comments
from several interested parties,
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
addressed below. However, DOE has not
yet received any formal proposals or
requests for negotiation from the
interested parties.
The EEAs and CA IOUs expressed
concern that the portion of the proposed
circulator definition that describes
circulators as ‘‘requir[ing] only the
support of the supply and discharge
piping to which it is connected to
function as designed,’’ may lead to the
design of circulators with alternative
mounting intended to circumvent
regulation. (EEAs, No. 10 at p. 1; CA
IOUs, No. 13 at pp. 4–5) HI agreed that
no pump definition should be
associated with a rigid foundation, as in
the industry rigid foundation has a
different connotation than DOE is using.
(HI, No. 8 at pp. 5–6, 10). HI also
disagreed with the proposed circulator
definition, commenting that there are
many end suction and close-coupled IL
pumps that would meet the proposed
circulator definition but that are not
considered circulators. Instead, HI
stated its belief that such pumps should
be included in the scope of pumps
considered in this rulemaking. As a
result, HI recommended revising the
definitions of circulator, ESFM, ESCC,
and IL pumps, as well as other related
definitions. (HI, No. 8 at pp. 7–8)
Following the close of the comment
period, the HI circulator pump
committee resubmitted revised
definitions for circulator and IL pumps,
and other related definitions. (HI, No. 15
at pp. 1–3)
DOE reviewed both sets of HI’s
recommended definitions and found
them to be essentially the same.
Specifically, HI’s circulator pump
committee offered the following revised
definitions of IL pumps and circulator
pumps, which were also included in
HI’s comments submitted in response to
the April 2015 pumps test procedure
NOPR:
‘‘In-line pump means a single-stage,
single-axis flow, dry rotor, rotodynamic
pump that has a shaft input power
greater than or equal to one horsepower
and less than or equal to two hundred
horsepower at BEP and full impeller
diameter, in which liquid is discharged
through a volute in a plane
perpendicular to the shaft, except for:
Those that are short-coupled or closecoupled, have a maximum hydraulic
power that is less than or equal to five
horsepower at the full impeller diameter
and over the full range of operation, and
are distributed in commerce with a
horizontal motor. Examples include, but
are not limited to, pumps complying
with ANSI/HI nomenclature OH3, OH4,
or OH5, as described in ANSI/HI 1.1–
1.2–2014, within the specified
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
horsepower range. Pumps complying
with ANSI/HI nomenclature CP1, CP2,
and CP3, as described in ANSI/HI 1.1–
1.2–2014, would not meet the definition
of in-line pump.’’ (HI, No. 8 at pp. 5–
6; HI, No. 15 at p. 1)
‘‘Circulator pump means a single
stage, in-line, rotodynamic pump that
meets one of the following descriptions:
i. [Wet Rotor Circulator] A single-axis
flow, close-coupled, wet rotor pump
that: (1) Has a maximum hydraulic
power greater than or equal to 1/40 hp
and less than or equal to 5 hp at full
impeller diameter and over the full
range of operation, (2) is distributed in
commerce with a horizontal motor, and
(3) discharges the pumped liquid
through a volute in a plane
perpendicular to the shaft. Examples
include, but are not limited to, pumps
complying with ANSI/HI 1.1–1.2–2014
nomenclature CP1; or
ii. [Dry Rotor Two-Piece Circulator] A
single-axis flow, close-coupled, dry
rotor pump that: (1) Has a maximum
hydraulic power greater than or equal to
1/40 hp and less than or equal to 5 hp
at full impeller diameter and over the
full range of operation, (2) is distributed
in commerce with a horizontal motor,
and (3) discharges the pumped liquid
through a volute in a plane
perpendicular to the shaft. Examples
include, but are not limited to, pumps
complying with ANSI/HI 1.1–1.2–2014
nomenclature CP2; or
iii. [Dry Rotor Three-Piece Circulator]
A single-axis flow, short-coupled, dry
rotor pump, either flexibly or rigidly
coupled that: (1) Has a maximum
hydraulic power greater than or equal to
1/40 hp and less than or equal to 5 hp
at full impeller diameter and over the
full range of operation, (2) is distributed
in commerce with a horizontal motor,
and (3) discharges the pumped liquid
through a volute in a place
perpendicular to the shaft. Examples
include, but are not limited to, pumps
complying with ANSI/HI 1.1–1.2–2014
nomenclature CP3.’’
(HI, No. 8 at pp. 8–9; HI, No. 15 at
p. 1)
HI also recommended several
supporting definitions, including
definitions for single-axis flow pump,
close-coupled pump, short-coupled
pump, rigid-coupled pump, flexiblycoupled pump, hydraulic power, wet
rotor pump, dry rotor pump, horizontal
motor, and non-horizontal motor. (HI,
No. 8 at pp. 9–10; HI, No. 15 at pp. 2–
3)
The EEAs and CA IOUs also stated
that they are collectively discussing an
improved definition of circulators with
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
4097
HI. (EEAs, No. 10 at p. 1; CA IOUs, No.
13 at pp. 4–5)
In light of the continued discussions
among these interested parties regarding
future definitions, test procedures, and
energy conservation standards for
circulators, DOE has decided to refrain
from defining the term ‘‘circulator’’ in
this rulemaking. Rather than explicitly
define the term circulator in this rule,
DOE has modified the definitions of
ESCC, ESFM, IL, VTS, and RSV to
specifically exclude certain categories of
pumps that are widely considered
circulators by the industry, using many
of the criteria and characteristics of
circulators indicated by HI in its
comments and proposed in the April
2015 pumps test procedure NOPR.
In particular, in its definition of IL
pump, DOE excluded pumps that are
commonly marketed and sold as
circulators in the pump industry by
utilizing the design features of a
horizontal motor, as well as a hydraulic
power less than or equal to 5 hp. This
is consistent with HI’s suggested
definition of IL pump as well as
circulator pump, which includes
reference to a horizontal motor and a
horsepower range of 1/40 to 5 hydraulic
hp. DOE agrees that a horizontal motor,
which is a motor that is required to be
oriented with the motor shaft in a
horizontal position in order to operate
as designed, is a distinguishing feature
of a circulator. To clearly establish this
characteristic, DOE is also defining the
term horizontal motor in this
rulemaking based on the definition HI
suggested in its comments. Specifically,
HI’s proposed definition and the
definition DOE is adopting in this final
rule are as follows:
Horizontal motor means a motor that
requires the motor shaft to be in a
horizontal position to function as
designed, as specified in the
manufacturer literature.
DOE notes that it is maintaining a
lower shaft limit of 1 hp for the IL pump
equipment category and only
specifically excluding those pumps that
have both: (1) A hydraulic output of less
than 5 hp and (2) a horizontal motor. As
such, any IL pumps that have a shaft
horsepower greater than or equal to 1 hp
and hydraulic output less than 5 hp and
are not sold with a horizontal motor, as
well as IL pumps that have a hydraulic
output greater than or equal to 5 hp and
shaft horsepower less than or equal to
200 hp and are sold with a horizontal
or non-horizontal motor, would
continue to be included in the IL pump
definition and subject to the test
procedure established in this final rule.
DOE notes that the majority of pumps
that are commonly referred to as
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
4098
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
circulators have a shaft input power less
than 1 hp. Such pumps may operate
with or without horizontal motors. As
such, the lower shaft power limit in the
IL pump definition excludes these
pumps from the scope of this
rulemaking.
DOE also acknowledges that HI
recommended establishing the
hydraulic horsepower threshold over
the full range of operation of the pump.
(HI, No. 8 at pp. 5–6 and 8–9; HI, No.
15 at p. 1) However, DOE notes that the
other horsepower thresholds referenced
in this final rule reference pump shaft
input power as measured at BEP. DOE
also notes that the test procedure
established in this final rule contains a
specific and repeatable methodology for
determining BEP of a tested pump.
Conversely, in the proposed test
procedure, DOE did not define the ‘‘full
range of operation’’ of a pump or
propose a method for how to determine
it. Since it is important that DOE’s test
procedures be as precise and
unambiguous as possible, DOE believes
that it is important that the hydraulic
horsepower of a pump be determined in
a consistent manner when determining
whether or not the pump meets the
definition of an IL pump and, thus, is
subject to DOE’s pumps test procedure
establish in this final rule. Therefore, in
this final rule, DOE is establishing the
hydraulic horsepower threshold for
circulator pumps as determined at BEP.
That is, DOE will exclude from the
definition of IL pump, IL pumps with a
hydraulic horsepower less than 5 hp, as
determined at full impeller diameter
and BEP, and that are distributed in
commerce with a horizontal motor, as
those pumps are considered to be
circulator pumps.
Consistent with the changes to the IL
definition, DOE is also incorporating
horsepower limits into the ESCC, ESFM,
RSV, and VTS equipment category
definitions. DOE notes that, in the April
2015 pumps test procedure NOPR, DOE
proposed to establish the scope of the
test procedure using a horsepower range
of greater than or equal to 1 hp and less
than 200 hp that was applicable to all
ESCC, ESFM, IL, RSV, and VTS pumps.
80 FR 17586, 17600 (April 1, 2015).
However, to maintain consistent format
among the five defined equipment
categories, DOE is including this
established horsepower range in each of
the equipment category definitions
explicitly rather than in a separate scope
limitation. DOE discusses the
horsepower range and other parameters
used to establish the scope of the test
procedure in section III.A.4.
Additionally, DOE has added the
design feature of a ‘‘dry rotor’’ to the
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
definition of an IL pump 22 and added
a definition of dry rotor pump, as
suggested by HI. This feature excludes
pumps that comply with ANSI/HI
nomenclature CP1, also referred to as
wet rotor circulators, as described in
ANSI/HI 1.1–1.2–2014. This definition
is also consistent with HI’s proposed IL
and circulator pump definitions. DOE
notes that wet rotor pumps were
proposed to be excluded from the scope
of the test procedure in the April 2015
pumps test procedure NOPR under the
definition of ‘‘sealless pump.’’
Specifically, DOE proposed a definition
of sealless pump to include both: (1) A
pump that transmits torque from the
motor to the bare pump using a
magnetic coupling and (2) a pump in
which the motor shaft also serves as the
impeller shaft for the bare pump and the
motor rotor is immersed in the pumped
fluid. 80 FR at 17641–42. HI’s proposed
definition of wet rotor is identical to the
second clause of DOE’s proposed
sealless pump definition. As such, in
this final rule, DOE defines dry rotor
pump, consistent with the definition
proposed by HI, and to incorporate the
term dry rotor into the ESFM, ESCC, IL,
RSV, and VTS equipment category
definitions. Given the mutually
exclusive relationship between wet and
dry rotor pumps, the definitions of
ESCC, ESFM, IL, RSV, and VTS pumps,
as established in section III.A.2.a, now
implicitly exclude wet rotor pumps
from the scope of this test procedure.
This implicit exclusion of wet rotor
pumps alleviates the need to explicitly
exclude wet rotor pumps using the
definition of sealless pump as proposed
in the NOPR. Further discussion of
modifications to the definition of
sealless pump are found in section
III.A.2.b.
DOE also acknowledges the concern
from interested parties regarding the
potential issues associated with
referencing attachment to a rigid
foundation. As noted in the NOPR, DOE
initially proposed such a design feature
to clearly differentiate and exclude
circulators from other, similar categories
of pumps that would be subject to the
proposed test procedure. However, DOE
has, based on comments received from
interested parties, revised its approach
to the exclusion of circulators and,
consequently, this design feature is no
longer needed in the definitions of IL,
ESCC, and ESFM. Instead, DOE has
made other modifications to the
22 In the NOPR, DOE had excluded sealless
pumps, including wet rotor pumps, from the scope
of the rulemaking in addition to explicitly limiting
the defined pump categories to dry rotor pumps. 80
FR 17586, 17598–99 (April 1, 2015) See section
III.A.3.b.
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
applicable definitions to continue to
exclude circulators from the equipment
categories addressed in this rulemaking,
as discussed above.
In addition to the parameters
necessary to exclude circulators from
the scope of pumps for which the test
procedure is applicable, the CA IOUs
commented that certain multi-stage
pumps should be included in the
definition of a circulator, as proposed by
DOE. CA IOUs also provided an
example of a commercially available
style of pump that they believe to be a
multi-stage circulator. (CA IOUs, No. 13
at pp. 4–5) DOE reviewed the example
style of pump provided by the CA IOUs
and found that this specific style of
pump is available in sizes from 0.5 to 75
motor hp, depending on impeller
diameter and number of stages. DOE
also concluded that specific models
within this general pump family,
namely those with shaft horsepower
greater than or equal to 1 hp, meet the
definition of an RSV pump and
therefore are included in the scope of
this rulemaking. Conversely, other
models within the same pump family
with shaft horsepower less than 1 hp do
not meet the definition of an RSV pump
and are not subject to the test procedure
established in this rulemaking.
Consequently, given that DOE has
withdrawn its proposal to define
circulators at this time, DOE has
determined that it does not need to
define or address these small RSV
pumps in this rulemaking.
c. Pool Pumps
The CIP Working Group formally
recommended that DOE initiate a
separate rulemaking for dedicatedpurpose pool pumps (DPPPs) by
December 2014. (Docket No. EERE–
2013–BT–NOC–0039, No. 92,
Recommendation #5A at p. 2) In the
April 2015 pumps test procedure NOPR,
DOE proposed defining a ‘‘dedicatedpurpose pool pump’’ as an end suction
pump designed specifically to circulate
water in a pool and that includes an
integrated basket strainer. 80 FR 17586,
17641 (April 1, 2015). DOE developed
this proposed definition to help
distinguish a DPPP from other
categories of pumps under
consideration in this rulemaking
(Docket No. EERE–2013–BT–TP–0055).
In response, APSP requested that DOE
continue to keep pool pumps separate
from the scope of pumps considered in
this rulemaking (APSP, No. 12 at p.1),
and the CA IOUs encouraged ASRAC to
establish a new working group for
DPPP. (CA IOUs, No. 13 at pp. 1–2) In
July 2015, DOE issued a RFI on DPPPs
requesting data and information from
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
interested parties on this equipment
(July 2015 DPPP RFI). 80 FR 38032 (July
3, 2015). On August 25, 2015, DOE also
published a notice of intent to establish
a working group for DPPPs. 80 FR
51483. See https://
www1.eere.energy.gov/buildings/
appliance_standards/rulemaking.aspx/
ruleid/14 for more updates and
information on the DPPP rulemaking.
DOE also received several comments
regarding its proposed definition.
During the April 2015 NOPR public
meeting, CA IOUs expressed that the
defining characteristic of a pool pump
may not be the strainer basket, as not all
pool pumps have them. (CA IOUs,
NOPR public meeting transcript, No. 7
at pp. 57–58, 68) An HI representative
from Xylem (Mark Handzel) responded
that commercial pool pumps without
basket strainers would be considered
under one of the equipment categories
addressed in this rulemaking. (HI,
NOPR public meeting transcript, No. 7
at pp. 58–59) An HI representative from
Xylem (Paul Ruzicka) also suggested
that, on the residential side, pool pumps
are double insulated products. (HI,
NOPR public meeting transcript, No. 7
at pp. 69–70)
In written comments, the EEAs and
the CA IOUs noted that many pool
pumps, including booster pumps, do
not include an integrated basket
strainer, and that not all pool pumps are
designed specifically to circulate water
(EEAs, No. 10 at p. 2; CA IOUs, No. 13
at p. 2–3). The CA IOUs noted that 40
percent of California residential inground pools have booster pumps that
are operated 2.5 hours per day. The size
is typically 3⁄4 nameplate horsepower
with a service factor of 1.5. The CA
IOUs recommended that these be
considered pool pumps and excluded
from this rulemaking, further noting that
these manufacturers were not involved
in the CIP Working Group deliberations.
The CA IOUs also stated that mass
market commodity pool pumps are
unique because either the pump is
secured directly to the motor; or the
pump and motor are each factory
secured to a common frame. (CA IOUs,
No. 13 at pp. 2–4)
In separate written comments, APSP
and the CA IOUs recommended the
following definition:
‘‘A ‘pool pump’ is a pump with the
following characteristics:
• An integral end suction pump and
motor combination specifically
designed for pool and spa applications.
• The impeller is attached to a motor
(or motor and controller) served by
single-phase power five total
horsepower or less.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
• The pump is secured directly to the
motor, or the pump and motor are
factory secured to a common frame.’’
(APSP, No. 12 at p. 1; CA IOUs, No. 13
at p. 3–4)
DOE’s original intent in proposing a
definition for DPPP in the April 2015
pumps test procedure NOPR was to
properly exclude them from this
rulemaking. Upon review, DOE agrees
with certain of the submitted comments
on the proposed definition, such as that
all pumps associated with pools may
not include an integrated basket
strainer. For example, DOE is aware that
booster pumps are not typically sold
with integrated basket strainers and
some filter pumps may be sold
separately from the strainer, as
discussed in the July 2015 DPPP RFI. 80
FR 26475, 26481 (May 8, 2015).
Therefore, after reviewing the
comments submitted by interested
parties, DOE has decided to refrain from
adopting a definition for DPPP in this
final rule. Instead, in this final rule,
DOE is excluding DPPP from the
definitions for ESCC and ESFM pumps,
and DOE will define DPPP in the
separate DPPP rulemaking that was
initiated with the RFI.
d. Axial/Mixed Flow and Positive
Displacement Pumps
‘‘Axial/mixed flow pump’’ is a term
used by the pump industry to describe
a rotodynamic pump that is used to
move large volumes of liquid at high
flow rates and low heads. These pumps
are typically custom-designed and used
in applications such as dewatering,
flood control, and storm water
management.
Positive displacement (PD) pumps are
a style of pump that operates by first
opening an increasing volume to
suction; this volume is then filled,
closed, moved to discharge, and
displaced. PD pumps operate at nearconstant flow over their range of
operational pressures and can often
produce higher pressure than a
centrifugal pump, at a given flow rate.
PD pumps also excel at maintaining
flow and efficiency for liquids more
viscous than water. When used in clean
water applications, PD pumps are
typically chosen for high pressure,
constant flow applications such as high
pressure power washing, oil field water
injection, and low-flow metering
processes.
The CIP Working Group
recommended excluding both of these
types of pumps from prospective energy
conservation standards. (Docket No.
EERE–2013–BT–NOC–0039, No. 92,
Recommendation #6 at p. 2) The
primary reason for excluding these
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
4099
pumps from this test procedure
rulemaking is their low market share in
the considered horsepower range and
low potential for energy savings.
(Docket No. EERE–2013–BT–NOC–0039,
No. 14 at pp. 114 and 372–73) In
addition, the CIP Working Group
acknowledged that PD pumps are more
commonly used in non-clean water
applications and provide a different
utility than the categories of pumps
addressed in this rulemaking. (Docket
No. EERE–2013–BT–NOC–0039, No. 14
at p. 114) Therefore, in the April 2015
pumps test procedure NOPR, DOE
proposed to exclude these pumps from
the scope of this rulemaking and the
parallel energy conservation standards
rulemaking, but determined that both
axial/mixed flow and PD pumps were
implicitly excluded based on the
proposed equipment category
definitions and scope parameters, so
that explicit exclusions were not
necessary. 80 FR 17586, 17597–98
(April 1, 2015). In the April 2015 pumps
test procedure NOPR, DOE requested
comment on the proposed exclusion
and the assertion that such pumps were
explicitly excluded based on the
existing definitions and scope
parameters. Id.
HI commented that both positive
displacement and axial/mixed flow
pumps should be added to the list of
equipment excluded from the scope of
pumps in this final rule. HI noted that
PD pumps represent a small percentage
of the overall pump market and are
generally used for niche applications,
such as viscous or shear-sensitive
liquids. As a result, such pumps have a
distinct difference in design compared
with rotodynamic pumps. HI also
suggested differentiating and excluding
axial/mixed flow pumps using a specific
speed limit of 4,500,23 where pumps
with a specific speed greater than 4,500
would be considered axial/mixed flow.
(HI, No. 8 at p. 11)
In response to HI, DOE notes that the
April 2015 pumps test procedure NOPR
does not include PD pumps within its
scope of applicability. All equipment to
which the April 2015 pumps test
procedure NOPR and this final rule
applies is explicitly defined as types of
rotodynamic pumps. Further,
rotodynamic pumps are explicitly
defined in the April 2015 pumps test
procedure NOPR and this final rule as
continuously imparting energy to the
pumped fluid by means of a rotating
impeller, propeller, or rotor. Such
definition necessarily does not include
23 Specific speed is a quasi-dimensionless
quantity used to describe relative pump geometry
and flow characteristics.
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
4100
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
PD pumps, which do not continuously
impart energy to the pumped fluid and
do not contain an impeller, propeller, or
rotor. As such, no PD pumps meet the
definition of any equipment within the
scope of this test procedure, as
discussed in section III.A.2.a. Therefore,
DOE does not believe it is necessary to
explicitly exclude PD pumps, which is
consistent with the comments submitted
by HI.
Regarding axial/mixed flow pumps,
DOE agrees with HI that axial/mixed
flow pumps, which are designed to
accommodate high flow-to-head-ratio
applications, should not be subject to
the test procedure established in this
final rule. DOE notes that the definitions
of IL, RSV, and VTS implicitly exclude
axial/mixed flow pumps through
specific design features. Specifically,
the definitions of IL and RSV pumps
exclude axial/mixed flow pumps by
specifying single axis flow and a liquid
inlet in a plane perpendicular to the
impeller shaft. In contrast, the liquid
intake in axial/mixed flow pumps is
typically parallel to the impeller shaft;
as such, these pumps do not meet the
definition of an RSV or IL pump. DOE
understands that less typical piping
configurations could allow an axial/
mixed flow pump to be built with the
liquid inlet in a plane perpendicular to
the impeller shaft. However, such a
configuration would not satisfy the
definition of single axis flow and, as
such, these pumps would not meet the
definition of an RSV or IL pump.
Additionally, the definition of VTS
pump excludes axial/mixed flow pumps
by specifying that the pump must be
designed to operate with the motor and
stage(s) fully submerged in the pumped
liquid. Axial/mixed flow pumps are not
designed to be completely submerged in
the pumped liquid and, therefore do not
meet the definition of a VTS pump.
In summary, DOE believes that the
definitions of IL, RSV, and VTS
equipment categories are sufficient to
exclude pumps that are referred to as
axial/mixed flow. As a result, DOE
maintains that a specific speed
limitation or other criteria for these
categories is unnecessary, and DOE has
not included a specific speed range for
these pumps in the parameters for
establishing the scope of this
rulemaking described in section III.A.4.
With respect to the end suction
pumps defined in this final rule, DOE
agrees that additional scope parameters
are necessary to limit the scope of this
rulemaking to end suction pumps and
not inadvertently include axial/mixed
flow pumps. DOE agrees with HI’s
suggestion of a specific speed limit to
accomplish the exclusion of axial/mixed
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
flow pumps. However, DOE reviewed
the specific speeds of all end suction
pumps submitted by manufacturers
during the energy conservation
standards rulemaking and identified
multiple end suction pumps with
specific speeds in the range of 4,500 to
5,000.24 DOE notes these data were
voluntarily submitted by manufacturers
who self-classified their pumps into
equipment types with the
understanding that the rulemaking was
not intended to include axial/mixed
flow pumps. DOE reviewed literature
for the specific pumps end suction
pumps with specific speeds in the range
of 4,500 to 5,000 and found them to be
marketed as end suction pumps.
Furthermore, DOE notes that the
performance data for these pumps were
included in the energy conservation
standards rulemaking analysis.
Consequently, DOE finds it appropriate
to explicitly include within the scope of
this rule, as established in
§ 431.464(a)(1)(ii), all end suction
pumps with specific speeds up to and
including 5,000 and exclude pumps
with specific speeds greater than 5,000.
e. Final Equipment Category Definitions
After consideration of all comments,
definitions for pump equipment
categories subject to this test procedure
are as set forth in the regulatory text of
this rule (10 CFR 431.62).
DOE received no comments on DOE’s
other supporting definitions proposed
in the April 2015 pumps test procedure
NOPR, namely rotodynamic pump,
single axis flow pump, and end suction
pump. Therefore, DOE is adopting those
definitions as proposed.
3. Scope Exclusions Based on
Application
In an effort to meet the intent and
recommendations of the CIP Working
Group to include only those pumps
intended to pump clean water in the
scope of this test procedure rulemaking
(Docket No. EERE–2013–BT–NOC–0039,
No. 92, Recommendation #8 at pp. 3–4),
DOE proposed to define ‘‘clean water
pump’’ in the April 2015 pumps test
procedure NOPR. 80 FR 17586, 17598
(April 1, 2015). DOE also proposed
defining several kinds of clean water
pumps that are designed for specific
applications and that the CIP Working
Group had indicated should be
excluded from the scope of this test
procedure and DOE’s standards
rulemaking efforts that are being
considered in a separate rulemaking.
(Docket No. EERE–2011–BT–STD–0031)
24 All values for specific speed in this final rule
pertain to calculations using U.S. customary units.
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
These proposed definitions, comments
DOE received regarding the proposed
definitions, and DOE’s responses to
those comments are discussed in the
subsequent sections III.A.3.a and
III.A.3.b.
a. Definition of Clean Water Pump
In the NOPR, DOE proposed defining
‘‘clean water pump’’ as a pump that is
designed for use in pumping water with
a maximum non-absorbent free solid
content of 0.25 kilograms per cubic
meter, and with a maximum dissolved
solid content of 50 kilograms per cubic
meter, provided that the total gas
content of the water does not exceed the
saturation volume, and disregarding any
additives necessary to prevent the water
from freezing at a minimum of ¥10 °C.
DOE also noted that several common
pumps would not meet the definition of
clean water pumps, as they are not
designed for pumping clean water,
including wastewater, sump, slurry, or
solids handling pumps; pumps designed
for pumping hydrocarbon product
fluids; chemical process pumps; and
sanitary pumps. DOE also proposed to
incorporate by reference the definition
for ‘‘clear water’’ established in HI 40.6–
2014 to describe the characteristics of
the fluid to be used when testing pumps
in accordance with the DOE test
procedure. 80 FR 17586, 17598 (April 1,
2015).
DOE requested comment on the
definition of ‘‘clean water pump’’
proposed in the April 2015 pumps test
procedure NOPR and its proposal to
incorporate by reference the definition
of ‘‘clear water’’ in HI 40.6–2014 to
describe the testing fluid to be used
when testing pumps in accordance with
the DOE test procedure. In response to
these proposals, HI commented that it
agrees with the definition of ‘‘clean
water pump’’ as set forth in the NOPR,
and that it agrees with incorporating by
reference the definition of ‘‘clear water’’
in HI 40.6–2014. (HI, No. 8 at p. 11)
DOE received no other comments on
these terms and has determined that the
definitions proposed in the NOPR are
sufficient for the purposes of applying
DOE’s test procedure. However, for
consistency, DOE is making the minor
modification of translating the
definition to use all U.S. customary
units. As such, DOE is adopting the
definition of clean water pump and
incorporating by reference the definition
of ‘‘clear water’’ in HI 40.6–2014 as
proposed in the April 2015 pumps test
procedure NOPR, with only the minor
modification regarding units noted
previously.
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
b. Exclusion of Specific Kinds of Clean
Water Pumps
tkelley on DSK3SPTVN1PROD with RULES2
In the April 2015 pumps test
procedure NOPR, DOE also proposed
defining several kinds of pumps that
meet the definition of clean water
pumps discussed in section III.A.3.a,
but that the CIP Working Group
recommended be excluded from this
pumps test procedure rulemaking.
Specifically, in the April 2015 pump
test procedure NOPR, DOE proposed
that the test procedure would not apply
to the following:
• Fire pumps;
• self-priming pumps;
• prime-assist pumps;
• sealless pumps;
• pumps designed to be used in a
nuclear facility subject to 10 CFR part
50—Domestic Licensing of Production
and Utilization Facilities; and
• a pump meeting the design and
construction requirements set forth in
Military Specification MIL–P–17639F,
‘‘Pumps, Centrifugal, Miscellaneous
Service, Naval Shipboard Use’’ (as
amended).
80 FR 17586, 17598–17600 (April 1,
2015).
Accordingly, DOE proposed the
following definitions of fire pump, selfpriming pump, prime-assist pump, and
sealless pump:
• Fire pump means a pump that is
compliant with National Fire Protection
Association (NFPA) 20–2016,25
‘‘Standard for the Installation of
Stationary Pumps for Fire Protection,’’
and either (1) American National
Standards Institute (ANSI)/UL listed
under ANSI/UL 448–2013, ‘‘Standard
for Safety Centrifugal Stationary Pumps
for Fire-Protection Service,’’ or (2) FM
approved under the January 2015
edition 26 of FM Class Number 1319,
25 DOE notes that in the April 2015 pumps test
procedure NOPR, DOE proposed to reference NFPA
20–2013. However, on May 26, 2015, NFPA
released a revised version of NFPA 20. DOE
reviewed the new NFPA 20–2016 and finds it to be
consistent with NFPA 20–2013 for the purposes of
defining the characteristics of a ‘‘fire pump’’ in the
context of DOE’s regulations for pumps. DOE finds
it most appropriate to reference the most up-to-date
version of the NFPA Standard, as that version
would be the version currently in use for specifying
the necessary characteristics of fire pumps in the
industry. Therefore, in this final rule, DOE is
updating the definition of fire pump to reference
NFPA 20–2016.
26 Similar to NFPA 20–2016, DOE notes that, in
January 2015, FM Global released an updated
version of the FM Class Number 1319 standard.
DOE reviewed the new January 2015 edition and
notes that it contains only editorial changes as
compared to the October 2008 edition proposed in
the NOPR. DOE believes that it is most appropriate
to reference the most up-to-date version of the FM
standard, as that version is the version currently in
use for specifying the necessary characteristics of
fire pumps in the industry. Therefore, in this final
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
‘‘Approval Standard for Centrifugal Fire
Pumps (Horizontal, End Suction Type).’’
• Self-priming pump means a pump
designed to lift liquid that originates
below the center line of the pump
impeller. Such a pump requires initial
manual priming from a dry start
condition, but requires no subsequent
manual re-priming.
• Prime-assist pump means a pump
designed to lift liquid that originates
below the center line of the pump
impeller. Such a pump requires no
manual intervention to prime or reprime from a dry-start condition. Such
a pump includes a vacuum pump or air
compressor to remove air from the
suction line to automatically perform
the prime or re-prime function.
• Sealless pump means either:
Æ A pump that transmits torque from
the motor to the bare pump using a
magnetic coupling; or
Æ A pump in which the motor shaft
also serves as the impeller shaft for the
bare pump, and the motor rotor is
immersed in the pumped fluid.
Id. at 17641–42.
HI commented that it agrees with the
definition of ‘‘fire pump’’ and
recommended alternate definitions for
‘‘self-priming pump,’’ ‘‘prime-assist
pump,’’ and ‘‘sealless pump’’ as follows:
• Self-priming pump means a pump
designed to lift liquid that originates
below the centerline of the pump inlet.
Further, such a pump must contain at
least one internal recirculation passage
and requires a manual filling of the
pump casing prior to initial start-up.
Such a pump must then be able to reprime after the initial start-up without
the use of external vacuum sources,
manual filling, or a foot valve.
• Prime-assist pump means a pump
designed to lift liquid that originates
below the centerline of the pump inlet.
Such a pump requires no manual
intervention to prime or re-prime from
a dry-start condition without the use of
a foot valve. Such a pump includes a
vacuum pump or air compressor and
venture/educator to remove air from the
suction line to automatically perform
the prime or re-prime function at any
point during the pump’s operating
cycle.
• A sealless pump means either:
Æ A hermetically sealed pump that
transmits torque from the motor to an
inner impeller rotor via magnetic force
through a containment shell;
Æ Or, a type of pump that has a
common shaft to link the pump and
motor in a single hermetically sealed
rule, DOE is updating the definition of fire pump
to reference the January 2015 edition of FM Class
Number 1319.
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
4101
unit. The pumped liquid is circulated
through the motor but is isolated from
the motor components by a stator liner.
(HI, No. 55 at pp. 11–12)
DOE considered these
recommendations and revised the
definitions of these excluded clean
water pumps in this final rule,
incorporating the key components of
HI’s proposals. Specifically, DOE agrees
with HI’s revised definitions for primeassist pump and self-priming pump and
is adopting them in this final rule with
some minor modifications for clarity.
DOE finds HI’s suggested definitions to
be consistent with DOE’s proposed
definitions but more precise, using
industry-specific language.
Regarding HI’s suggested definition of
sealless pump, DOE agrees with the
content of the definition. However, DOE
notes that, based on the modifications to
equipment category definitions
described in section III.A.2.a, DOE has
determined that it is no longer necessary
to explicitly exclude wet rotor pumps
(the second clause of HI’s sealless pump
definition) from the scope of this
rulemaking. Specifically, as explained
in section III.A.2.a, DOE is specifying in
its revised definitions that all ESCC,
ESFM, IL, RSV, and VTS pumps are
types of dry rotor pumps. Dry rotor
pump means a pump in which the
motor rotor is not immersed in the
pumped fluid. Conversely, a wet rotor
pump is one in which the motor rotor
is immersed in the pumped liquid.
Given the mutually exclusive
relationship between wet and dry rotor
pumps, the definitions of ESCC, ESFM,
IL, RSV, and VTS pumps, as established
in section III.A.2.a, now implicitly
exclude wet rotor pumps from the scope
of this test procedure. As a result, DOE
has simplified the sealless pump
exclusion in this final rule to exclude
magnet driven pumps only.
Accordingly, DOE is also modifying the
term ‘‘sealless pump’’ to ‘‘magnet driven
pump,’’ as DOE believes this term more
accurately describes the excluded
equipment. In addition, DOE is
modifying the definition of magnet
driven pump to be consistent with the
suggestions from HI, which DOE
believes is consistent with the portion of
the sealless pump definition proposed
in the April 2015 pumps test procedure
NOPR addressing magnet driven pumps,
but which uses more precise and
industry-specific terminology.
HI also commented that no pumps
designed to the Federal defense
specification MIL–P–17639 should be
included in this rulemaking. (HI, No. 8
at p. 12) HI stated that the specifications
included in the CIP Working Group
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
4102
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
term sheet also should be excluded,
specifically MIL–P–17881, MIL–P–
17840, MIL–P–18682, and MIL–P–18472
(commonly referred to as ‘‘MIL–SPEC’’).
DOE has therefore reviewed these
additional specifications in determining
exclusions in this final rule.
Pumps designed to these military
specifications must meet very specific
physical and/or operational
characteristics and comply with
complex and rigid reporting
requirements.27 These specifications
require that significant amounts of
design and test data be submitted to
various military design review agencies
to ensure that the pump can be operated
and maintained in harsh naval
environments. DOE believes there is
sufficient justification to exclude all of
the MIL–SPEC pumps identified by HI
from the scope of this rulemaking
without a risk of clean water pumps
being marketed or sold as MIL–SPEC for
actual use in other applications due to
the rigorous and burdensome
requirements associated with complying
with those regulations. DOE notes that,
as mentioned in the April 2015 pumps
test procedure NOPR, when considering
if a pump is designed and constructed
to the requirements set forth in any of
these specifications, DOE may request
that a manufacturer provide DOE with
copies of the original design and test
data that were submitted to appropriate
design review agencies, as required by
each of these specifications. 80 FR
17586, 17599 (April 1, 2015).
After reviewing and considering
comments, DOE is adopting in this final
rule that the following specific types of
clean water pumps are excluded from
the scope of this test procedure final
rule:
• Fire pumps;
• self-priming pumps;
• prime-assist pumps;
• magnet driven pumps;
• pumps designed to be used in a
nuclear facility subject to 10 CFR part
50—Domestic Licensing of Production
and Utilization Facilities; and
• pumps meeting the design and
construction requirements set forth in
Military Specification MIL–P–17639F,
‘‘Pumps, Centrifugal, Miscellaneous
Service, Naval Shipboard Use’’ (as
amended); MIL–P–17881D, ‘‘Pumps,
Centrifugal, Boiler Feed, (Multi-Stage)’’
(as amended); MIL–P–17840C, ‘‘Pumps,
Centrifugal, Close-Coupled, Navy
Standard (For Surface Ship
27 United States General Accounting Office,
Report to Congressional Committees, Acquisition
Reform: DOD Begins Program To Reform
Specifications and Standards, GAO/NSIAD–95–14.
October 11, 1994. Washington, DC. pp. 2–3.
https://www.gao.gov/archive/1995/ns95014.pdf.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
Application)’’ (as amended); MIL–P–
18682D, ‘‘Pump, Centrifugal, Main
Condenser Circulating, Naval
Shipboard’’ (as amended); and MIL–P–
18472G, ‘‘Pumps, Centrifugal,
Condensate, Feed Booster, Waste Heat
Boiler, And Distilling Plant’’ (as
amended).
Accordingly, DOE provides the
revised definitions of fire pump, selfpriming pump, prime-assist pump, and
magnet driven pump set forth in the
regulatory text of this rule (10 CFR
431.62).
4. Parameters for Establishing the Scope
of Pumps in This Rulemaking
In addition to limiting the types of
pumps that DOE will regulate at this
time through pump definitions and their
applications, DOE proposed in the April
2015 pumps test procedure NOPR to
further limit the scope of the pumps test
procedure considered in this
rulemaking by applying the following
performance and design characteristics:
• 1–200 hp (shaft power at the BEP at
full impeller diameter for the number of
stages 28 required for testing to the
standard); 29
• 25 gallons per minute (gpm) and
greater (at BEP at full impeller
diameter);
• 459 feet of head maximum (at BEP
at full impeller diameter);
• design temperature range from ¥10
to 120 °C;
• pumps designed for nominal 3,600
or 1,800 revolutions per minute (rpm)
driver speeds; and
• 6-inch or smaller bowl diameter for
VTS pumps (HI VS0).
(Docket No. EERE–2013–BT–NOC–0039,
No. 92, Recommendation #7 at p. 3); 80
FR 17586, 17600 (April 1, 2015).
Wilo commented that lower
thresholds for horsepower and BEP flow
rate should not be included as limiting
parameters on the scope of pumps
considered in the rule, citing
unspecified gains in energy savings that
could be realized by regulating smaller
models. (Wilo, Docket No. EERE–2011–
BT–STD–0031, No. 44 at pp. 1–2) 30 In
28 The number of ‘‘stages’’ in a multi-stage pump
refers to the number of bowl assemblies included
in that pump.
29 The CIP Working Group also recommended
that testing be required with three stages for RSV
pumps and nine stages for VTS pumps, unless a
model is not available with that specific number of
stages, in which case the pump would be tested
with the next closest number of stages. This
recommendation is discussed in more detail in
section III.C.2.c.
30 A notation in this form provides a reference for
information that is in the docket of DOE’s
rulemaking to develop energy conservation
standards for commercial and industrial pumps
(Docket No. EERE–2011–BT–STD–0031, which is
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
response to Wilo’s suggestion that DOE
apply the test procedure to pumps with
flow rates below 25 gpm or shaft input
power below 1 hp, DOE believes that
such a recommendation is inconsistent
with the scope of pumps the CIP
Working Group recommended for this
rulemaking. Given that such small
horsepower pumps were not considered
in the CIP Working Group discussions,
any data or information submitted to
DOE throughout those negotiations did
not consider small horsepower pumps.
As such, DOE is electing to maintain the
lower thresholds for horsepower and
BEP flow rate as proposed in the April
2015 pumps test procedure NOPR.
HI recommended in the April 2015
NOPR public meeting and written
comments that DOE establish scope
related to ‘‘driver and impeller’’ speed
rather than just driver speed. HI noted
that pumps do not all have 1:1 motor
rotating speed to impeller-rotating
speed, such as a gear pump. (HI, NOPR
public meeting transcript, No. 7 at p. 85;
HI, No. 8 at p. 13) HI further specified
as an example that a geared pump
designed to use a 2-pole motor could be
in scope but could not be tested
according to section I.C.1 of the test
procedure. (HI, No. 8 at p. 13)
DOE notes that the list shown in the
preamble of the April 2015 pump test
procedure NOPR, based on the CIP
Working Group recommendations,
included a limitation for pumps
designed for nominal driver speeds of
3,600 or 1,800 revolutions per minute
(rpm) driver. (Docket No. EERE–2013–
BT–NOC–0039, No. 92,
Recommendation #7 at p. 3); 80 FR
17586, 17600 (April 1, 2015). However,
in the regulatory text of the April 2015
pumps test procedure NOPR, DOE
modified this recommendation to
acknowledge that the pumps within the
scope of the proposed test procedure
include pumps paired with noninduction motors, which have wide
range of operating speeds. Specifically,
DOE proposed to limit the scope of the
proposed test procedure to pumps
designed to operate with either: (1) A 2or 4-pole induction motor, or (2) a noninduction motor with a speed of rotation
operating range that includes speeds of
rotation between 2,880 and 4,320 rpm
and/or 1,440 and 2,160 rpm. Id. at
17642. DOE proposed the speed ranges
of 2,880 to 4,320 and 1,440 to 2,160
based on the nominal rotating speeds of
3,600 and 1,800 for 2- and 4-pole
motors, respectively, and the allowed 20
maintained at www.regulations.gov). This particular
notation refers to a comment: (1) Submitted by
Wilo; (2) appearing in document number 44 of the
docket; and (3) appearing on pages 1–2 of that
document.
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
percent tolerance on rotating speed
proposed in the NOPR. Id. at 17609.
DOE notes that geared pumps were
never explicitly addressed by the CIP
Working Group; were not included in
the pump data which are the basis of
this final rule and the associated energy
conservation standard rulemaking; and
were not intended to be included in the
scope of the April 2015 pumps test
procedure NOPR. In addition, as
mentioned in section III.A.2.a, geared
pumps typically operate at impeller
speeds higher than the 1,800 and 3,600
nominal rotating speeds DOE referenced
in CIP Working Group discussions and
the April 2015 pumps test procedure
NOPR. In light of HI’s comment, DOE
agrees that it is worth clarifying that
such pumps are not subject to or
addressed by the test procedure
established in this final rule. To clarify
that pumps with higher impeller or
lower driver rotating speeds (i.e., geared
pumps) are not within the scope of this
rulemaking, DOE is modifying the
language establishing the rotating
speeds within the scope of the test
procedure adopted in this final rule to
note that the driver and impeller must
operate at the same speed.
During the April 2015 NOPR public
meeting, the CA IOUs expressed
concern regarding whether it was the
CIP Working Group’s intention to
address VTS pumps that operate at high
speed. Specifically, the CA IOUs
mentioned that it may not have been the
intent of HI to exclude a product
operating at a higher rpm and
recommended that HI consider the
language proposed in the April 2015
pumps test procedure NOPR to ensure
they support the scope of pumps
addressed by the proposed test
procedure. (CA IOUs, NOPR public
meeting transcript, No. 7 at pp. 86–88)
However, in its written comments, HI
did not recommend any changes to the
parameters other than the discussion on
impeller speed versus driver speed. (HI,
No. 8 at p. 13)
Wilo commented that manufacturers
may redesign to nominal speeds
excluded from the DOE regulation.
(Wilo, Docket No. EERE–2011–BT–
STD–0031, No. 44 at p. 2) Wilo
indicated that, for example, a pump
could be designed for use with 6-pole
motors at 1,200 rpm, or for use with
controls at 2,650 rpm. Wilo
recommended to instead apply the
minimum efficiency required per
equipment class (e.g., C-values at 1,800
rpm) to pumps of any speed and
specific speed, thereby eliminating
exceptions for speed and allowing for
enforcement across all motor speeds.
(Id.)
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
DOE’s data and analysis are based
solely on pumps with nominal rotating
speeds corresponding to those speed
ranges proposed in the 2015 pumps test
procedure NOPR. DOE notes that,
during the initial data request
underlying the parallel pumps test
procedure and energy conservation
standards rulemakings, DOE requested
data on six-pole pumps from
manufacturers. However, manufacturers
declined to provide such on the basis
that, while some pumps may be sold for
use with 6-pole motors, they are all
designed for use with 4- or 2-pole
motors. (Docket No. EERE–2013–BT–
NOC–0039, No. 46 at p. 198) As such,
manufacturers posited that these pumps
would already be captured in the
provided data for 4- and 2-pole, and any
efficiency improvements made to meet
the energy conservation standards for
those equipment classes would also
result in energy savings when the pump
was operated with a 6-pole motor.
Additionally, DOE finds it unlikely that,
for those pumps that can operate with
2-, 4-, or 6-pole motors, a manufacturer
would begin specifying that their pump
was inappropriate for operation in the
nominal speed ranges of 2,880 and
4,320 rpm and/or 1,440 and 2,160 rpm
to avoid regulation.
After considering these comments,
DOE maintains its position set forth in
the NOPR, and limits the test procedure
applicability to pumps designed for the
given motors or speeds. DOE notes that
pumps with lower or higher operating
speeds are covered as ‘‘pumps’’ and,
should DOE deem it necessary, DOE
could evaluate the need for a test
procedure or standards for pumps at
other rotating speeds in a future
rulemaking.
In summary, DOE is establishing in
this final rule the following scope
parameters:
• 25 gpm and greater (at BEP at full
impeller diameter);
• 459 feet of head maximum (at BEP
at full impeller diameter and the
number of stages specified for testing);
• design temperature range from 14 to
248 °F;
• designed to operate with either (1)
a 2- or 4-pole induction motor, or (2) a
non-induction motor with a speed of
rotation operating range that includes
speeds of rotation between 2,880 and
4,320 rpm and/or 1,440 and 2,160 rpm,
and in either case, the driver and
impeller must rotate at the same speed;
and
• 6-inch or smaller bowl diameter for
VTS pumps (HI VS0).
As discussed further in section III.B.2,
DOE is clarifying that the limitation on
pump total head of 459 feet must be
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
4103
ascertained based on the pump
operating at BEP, at full impeller
diameter, and with the number of stages
specified for testing.
Additionally, to exclude axial/mixed
flow pumps, DOE is applying a seventh
scope parameter for ESCC and ESFM
pumps, namely:
• For ESCC and ESFM pumps,
specific speed less than or equal to
5,000 when calculated using U.S.
customary units in accordance with the
DOE test procedure.
As discussed in section III.A.2.d, DOE
is setting this limit on specific speed
based on HI’s suggestion and data
submitted by manufacturers for end
suction pumps. DOE believes that a
specific speed limit for the remaining
equipment categories, namely IL, RSV,
and VTS, are unnecessary, as the
definitions for these categories include
design features that implicitly exclude
axial/mixed flow pumps.
In the April 2015 pumps test
procedure NOPR, DOE proposed
defining bowl diameter to specify
clearly and unambiguously the limiting
criterion for VTS pumps (i.e., bowl
diameter). 80 FR 17586, 17600 (April 1,
2015). Specifically, DOE proposed
defining ‘‘bowl diameter’’ as it applies
to VTS pumps as follows:
Bowl diameter means the maximum
dimension of an imaginary straight line
passing through and in the plane of the
circular shape of the intermediate bowl
or chamber of the bare pump that is
perpendicular to the pump shaft and
that intersects the circular shape of the
intermediate bowl or chamber of the
bare pump at both of its ends, where the
intermediate bowl or chamber is as
defined in ANSI/HI 2.1–2.2–2008.
With this definition, only those VTS
pumps with bowl diameters of 6 inches
or less would be required to be tested
under the test procedure. Id.
In response to DOE’s request for
comment on the proposed definition for
‘‘bowl diameter’’ as it would apply to
VTS pumps, HI commented that the
definition should reference the updated
2014 version of ANSI/HI 2.1–2.2–2008,
and recommended that the word
‘‘outermost’’ should be inserted before
the text ‘‘circular shape of the
intermediate bowl.’’ (HI, No. 8 at p. 13)
Based on previously submitted HI
comments regarding the energy
conservation standards rulemaking for
pumps, DOE understands that VTS (e.g.,
VS0) pumps are considered equivalent
to a style of pump referred to as
‘‘submersible multi-stage water pump’’
E:\FR\FM\25JAR2.SGM
25JAR2
4104
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
(MSS) in EU regulation 547.31 (HI,
Docket No. EERE–2011–BT–STD–0031,
No. 25 at p. 3) DOE also understands
that, according to EU 547, MSS pumps
are designed to be operated in a
borehole and have a nominal outer
diameter of either 4 or 6 inches.
DOE agrees with HI that including the
word ‘‘outermost’’ in the proposed bowl
diameter definition would improve the
clarity of the critical dimension and
ensure the definition is aligned with
how the pumps are treated in EU 547.
Therefore, in this final rule, DOE is
including the term outer diameter before
the text ‘‘circular shape of the
intermediate bowl’’ in the definition of
‘‘bowl diameter’’ proposed in the April
2015 pumps test procedure NOPR. DOE
has also determined that in order to
avoid confusion with the ANSI/HI 2.1–
2.2–2014 term ‘‘seal chamber,’’ the text
‘‘or chamber’’ should be removed from
the bowl diameter definition. The
revised definition reads as set forth in
the regulatory text of this rule (10 CFR
431.62).
tkelley on DSK3SPTVN1PROD with RULES2
5. Drivers Other Than Electric Motors
DOE recognizes that some pumps,
particularly in the agricultural sector,
may be sold and operated with drivers
other than electric motors (i.e., nonelectric drivers), such as engines, steam
turbines, or generators. In the April
2015 pump test procedure NOPR, in
accordance with the recommendations
of the CIP Working Group (Docket No.
EERE–2013–BT–NOC–0039, No. 92,
Recommendation #3 at p. 2), DOE
proposed that pumps sold with nonelectric drivers be rated as bare pumps
only. Specifically, based on DOE’s
proposed test procedure for bare pumps
discussed in detail in section III.E.1.a,
pumps sold with non-electric drivers
would determine the PEICL for the
pump based on the calculated
performance of the bare pump
combined with a default motor that is
minimally compliant with DOE’s energy
conservation standards for electric
motors 32 listed at 10 CFR 431.25. 80 FR
17586, 17600 (April 1, 2015). DOE noted
that by requiring testing and
certification in this manner, any
hydraulic improvements made to the
bare pump to comply with any
applicable energy conservation
standards that may apply to the bare
31 Council of the European Union. 2012.
Commission Regulation (EU) No 547/2012 of 25
June 2012 implementing Directive 2009/125/EC of
the European Parliament and of the Council with
regard to ecodesign requirements for water pumps.
Official Journal of the European Union. L 165, 26
June 2012.
32 In context, the terms ‘‘electric motor’’ and
‘‘motor’’ are used interchangeably.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
pump would also result in energy
savings when the pump was used with
a non-electric driver. Id.
DOE requested comment on its
proposal to test pumps sold with nonelectric drivers as bare pumps. HI
commented that it agrees that pumps
sold with non-electric drivers should be
tested as bare pumps, as recommended
by the CIP Working Group. (HI, No. 8 at
p. 13) DOE received no other comments
on the proposal and is adopting
provisions for testing pumps paired
with non-electric drivers as bare pumps
in this final rule, as proposed in the
April 2015 pumps test procedure NOPR.
6. Pumps Sold With Single-Phase
Induction Motors
In the April 2015 pumps test
procedure NOPR, DOE acknowledged
that some pumps within the scope of
this rulemaking may be distributed in
commerce with single-phase motors.
However, DOE determined that the
majority of pumps in the scope of this
test procedure rulemaking are sold with
polyphase induction motors. Moreover,
DOE noted that, to the extent that
pumps within the scope of the proposed
test procedure are distributed in
commerce with single-phase motors,
most of these pumps are offered for sale
with either single-phase or polyphase
induction motors of similar size,
depending on the power requirements
of customers.
Given that single-phase induction
motors are, in general, less efficient than
polyphase induction motors and, thus,
will result in different energy
consumption characteristics when
paired with the same bare pump, DOE
proposed that pumps sold with singlephase induction motors be tested and
rated in the bare pump configuration,
using the calculation-based method (see
section III.E.1.a for a more detailed
description of this method). DOE
believed that such an approach would
more equitably rate pumps sold with
single-phase motors and prevent pumps
sold with single-phase motors from
being penalized by the reduced energy
efficiency of the paired single-phase
motor, as compared to similarly-sized
polyphase motors. 80 FR 17586, 17600–
01 (April 1, 2015).
In response to DOE’s proposed
method for testing pumps sold with
single-phase induction motors, HI
agreed that it is appropriate to apply the
calculation-based test procedure to bare
pumps to determine the PEICL for such
pumps. However, HI also requested the
option of using single-phase motor wireto-water test data (that is, applying the
testing-based method for pumps sold
with motors, discussed in section
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
III.E.2.b) to determine the PEICL for such
pumps. (HI, No. 8 at p. 13) Given that
single-phase induction motors are, in
general, less efficient than polyphase
induction motors, determining the PEICL
for pumps sold with single-phase
induction motors based on the testingbased method for pumps sold with
motors will generally result in PEICL
ratings that are equivalent to or lower
than those determined by rating the
pump as a bare pump (as proposed in
the April 2015 pumps test procedure
NOPR). Therefore, use of the testingbased method will make it harder,
rather than easier, for pumps sold with
single-phase induction motors, to meet
the established standards. For these
reasons, DOE sees no reason why
manufactures could not be allowed to
employ the testing-based method for
pumps sold with motors to determine
the PEICL if they chose to. As such, DOE
is adopting provisions in this final rule
that allow manufacturers the option of
rating pumps sold with single-phase
motors as bare pumps (using a
calculation-based method) or as pumps
with motors using the testing-based
methods. DOE notes that if
manufacturers choose to employ the
testing-based methods for pumps sold
with motors, the denominator must still
be calculated based on the default motor
efficiency values for polyphase NEMA
Design B motor, as discussed in section
III.B.2. DOE also notes that, as for all
pumps subject to this test procedure
final rule, manufacturers must report
which test method was employed in
determining the certified PEICL rating
for the given basic model in the
certification report submitted to DOE.
These requirements are discussed in
more detail in the pumps energy
conservation standards rulemaking.
(Docket No. EERE–2011–BT–STD–0031)
B. Rating Metric: Constant and Variable
Load Pump Energy Index
After significant discussion in the CIP
Working Group open meeting, the
Working Group recommended that DOE
use a wire-to-water, power-based metric
for all pumps, regardless of how they
are sold. (Docket No. EERE–2013–BT–
NOC–0039, No. 92, Recommendation
#11 at p. 5) Specifically, the CIP
Working Group recommended that DOE
use the PEI metric to measure pump
energy performance, which is calculated
as a ratio of the PER (PERCL or PERVL)
of the tested pump divided by the
PERCL of a pump that would minimally
comply with any DOE energy
conservation standard for that pump
type (PERSTD). In both cases, PER
represents a pump’s power
consumption at a weighted average of
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
4105
three or four load points. The CIP
Working Group recommended a similar
metric for all pump configurations (i.e.,
bare pumps, pumps sold with a motor,
and pumps sold with a motor and
continuous or non-continuous controls)
to allow for better comparability and
more consistent application of the rating
metric for all pumps within the
recommended scope. This way, the
benefit of speed control, as compared to
a similar pump without speed control,
can be reflected in the measurement of
energy use or energy efficiency.
Accordingly, in the April 2015 pumps
test procedure NOPR, DOE proposed to
establish a test procedure to determine
the PEICL for pumps sold without
continuous or non-continuous controls
and PEIVL for pumps sold with
continuous or non-continuous controls.
80 FR 17586, 17601–02 (April 1, 2015).
As recommended by the CIP Working
Group, DOE proposed to determine the
PEICL or PEIVL as the ratio of a PERCL
or PERVL scaled with respect to a
‘‘standard pump energy rating’’ (PERSTD)
that represents the performance of a
bare pump of the same equipment class
that serves the same hydraulic load, has
the same flow and specific speed
characteristics, and is minimally
compliant with DOE’s energy
conservation standards. Id.
Specifically, for pumps sold without
continuous or non-continuous controls,
DOE proposed using the PEICL metric,
which would be evaluated as shown in
equation (1):
Where:
PERCL = the weighted average input power to
the motor at load points of 75, 100, and
110 percent of BEP flow (hp) and
PERSTD = the PERCL for a pump of the same
equipment class with the same flow and
specific speed characteristics that is
minimally compliant with DOE’s energy
conservation standards serving the same
hydraulic load (hp). A more detailed
discussion of the PERSTD value is
provided in section III.B.2.
Similarly, for pumps sold with a
motor and continuous or noncontinuous controls, DOE proposed to
use PEIVL, which would be evaluated as
shown in equation (2):
Where:
PERVL = the average input power to the
motor and continuous or non-continuous
controls at load points of 25, 50, 75, and
100 percent of BEP flow (hp) and
PERSTD = the PERCL for a pump of the same
equipment class with the same flow and
specific speed characteristics that is
minimally compliant with DOE’s energy
conservation standards serving the same
hydraulic load (hp).
sold with continuous or non-continuous
controls, by contrast, would follow a
system curve and achieve the desired
flow points by reducing the pump’s
speed of rotation rather than controlling
flow by throttling. By reducing speed,
power is reduced in proportion to the
cube of speed, resulting in lower power
requirements for any part load flow
points. As such, the PEIVL for a pump
sold with continuous or non-continuous
controls would be lower than the PEICL
for the same pump sold without
continuous or non-continuous controls.
In essence, consistent with the
recommendation of the CIP Working
Group, adopting the PEICL and PEIVL
metrics as proposed would illustrate the
inherent performance differences that
can occur when coupling a given pump
with continuous or non-continuous
controls. Id.
DOE noted in the April 2015 pumps
test procedure NOPR that, under the
proposed approach, the performance of
bare pumps or pumps paired with
motors (but without continuous or noncontinuous controls) would be
determined for the appropriate load
points along the single-speed pump
curve by increasing head (i.e., throttling)
as flow is decreased from the maximum
flow rate of the pump, while pumps
1. Determination of the Pump Energy
Rating
As mentioned above, PERCL and
PERVL represent the weighted average
input power to the pump determined at
three or four discrete load points for
PERCL or PERVL, respectively. In order
to determine the representative
performance of a given pump unit, DOE
must define a load profile and establish
specific load points at which to test a
given pump for pumps sold with speed
controls and pumps sold without such
speed controls (i.e., pumps sold as bare
pumps and pumps sold with motors).
Based on DOE’s research and
recommendations provided by the CIP
Working Group, DOE proposed adopting
two distinct load profiles to represent
constant speed and variable speed
pump operation, as shown in Table III.2.
TABLE III.2—LOAD PROFILES BASED ON PUMP CONFIGURATION
Constant Load Profile ....................
75%, 100%, and 110% of BEP
flow.
25%, 50%, 75%, and 100% of
BEP flow.
Lack of field data on load profiles and
the wide variation in system operation
also make it difficult to select
appropriate weights for the load
profiles. For these reasons, the CIP
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
Variable Load Profile .....................
Working Group members concluded
that equal weighting would at least
create a level playing field across
manufacturers (see, e.g., Docket No.
EERE–2013–BT–NOC–0039, No. 63 at p.
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
125), and DOE proposed to adopt this
recommendation in the April 2015
pumps test procedure NOPR. 80 FR
17586, 17604 (April 1, 2015).
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.001
Load points
ER25JA16.000
Load profile
Pumps Sold without Continuous or Non-Continuous Controls (i.e.,
bare pumps and pumps sold with motors).
Pumps Sold with Continuous or Non-Continuous Controls ....................
tkelley on DSK3SPTVN1PROD with RULES2
Pump configuration
4106
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
public meeting transcript, No. 7 at p.
110). Therefore, DOE is adopting, in this
final rule, a metric of PEICL for pumps
sold as bare pumps or pumps sold with
motors, but without continuous or noncontinuous controls, as proposed in the
April 2015 pumps test procedure NOPR,
where the PERCL would be evaluated as
the weighted average input power to the
motor at load points corresponding to
75, 100, and 110 percent of BEP flow,
as shown in equation (3):
Where:
wi = weighting at load point i (equal
weighting or 0.3333 in this case),
Piin,m = measured or calculated driver power
input to the motor at load point i (hp),
and
i = load point corresponding to 75, 100, or
110 percent of BEP flow as determined
in accordance with the DOE test
procedure.
Similarly, DOE is adopting a metric of
PEIVL for pumps sold with motors and
continuous or non-continuous controls,
where PERVL is calculated as shown in
equation (4):
Where:
wi = weighting at load point i (equal
weighting or 0.25 in this case),
Piin,c = measured or calculated driver power
input to the continuous or noncontinuous controls at load point i (hp),
and
i = load point corresponding to 25, 50, 75,
or 100 percent of BEP flow as
determined in accordance with the DOE
test procedure.
terminology by referring to driver power
input to the motor as Piin,m and driver
power input to the controls as Piin,c.
DOE notes that HI 40.6–2014 uses the
variable Pgr to refer to driver input
power and, for the purposes of applying
HI 40.6–2014 and the DOE test
procedure, DOE’s defined variable (i.e.,
Piin,m and Piin,c) should be treated as
equivalent to Pgr.
Id. at 17603.
DOE notes that, in the April 2015
pumps test procedure NOPR, DOE
proposed to refer to the driver power
input using the variable Piin regardless
of whether it applied to pumps sold
with motors, where the driver input
power is measured at the input to the
motor, or pumps sold with motors and
continuous or non-continuous controls,
where the driver power input is
measured at the input to the controls. In
this final rule, DOE is clarifying the
2. PERSTD: Minimally Compliant Pump
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
DOE proposed in the April 2015
pumps test procedure NOPR that the
PERCL or PERVL of the pump being rated
in the numerator of these equations
would be scaled based on PERCL of a
pump that would minimally comply
with the applicable standard for the
same class of pump to provide a rating
for each pump model that is indexed to
a standardized value. DOE noted that
scaling the PEICL and PEIVL metrics
based on a normalizing factor would
help compare values across and among
various pump types and sizes. 80 FR
17586, 17604 (April 1, 2015). DOE noted
that such an approach would be
consistent with the CIP Working
Group’s recommendations (Docket No.
EERE–2013–BT–NOC–0039, No. 92,
Recommendation #11 at pg. 5) and is
similar to the approach suggested by
Europump, a trade association of
European pump manufacturers.33 Id.
In the April 2015 pumps test
procedure NOPR, DOE proposed to
determine PERSTD as a baseline,
minimally compliant pump, inclusive of
a minimally compliant default motor,
defined as a function of flow and
specific speed. To do this, DOE
proposed to use an equation to
determine the efficiency of a minimally
compliant pump, shown in equation
(5): 34
ER25JA16.003
33 Europump. Extended Product Approach for
Pumps: A Europump Guide. April 8, 2013.
34 This equation reflects that shown in the April
2015 NOPR public meeting (Docket No. EERE–
2013–BT–TP–0055, No. 6 at p.49) and represents a
Id. at 17602.
correction from that published in the April 2015
pumps test procedure NOPR. 80 FR 17586, 17604
(April 1, 2015).
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.002
tkelley on DSK3SPTVN1PROD with RULES2
In response to DOE’s proposed
metrics, load points, and weights, HI
commented that it agrees with the PEICL
and PEIVL metric architecture (HI, No. 8
at p. 14), and the CA IOUs also
indicated their support of DOE’s
proposed approach (CA IOUs, NOPR
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
Where:
Q100% = BEP flow rate (gpm),
Ns = specific speed at 60 Hz and calculated
using U.S. customary units, and
C = a constant that is set for the twodimensional surface described by
equation (5), which is set based on the
speed of rotation and equipment type of
the pump model. The values of this
constant, or ‘‘C-values,’’ are used to
establish the minimum, mandatory
pump efficiency with a minimally
compliant pump and will be established
in the pump energy conservation
standard rulemaking.
DOE developed this equation based
on the equation used in the EU to
develop its regulations for clean water
pumps, translated to 60 Hz electrical
input power and U.S. customary
units.35 Id. HI commented that it agrees
with the corrected version of the
equation for minimum pump efficiency
equation (hpump,STD) presented during
the public meeting, except that the
555.6 value should be changed to 555.60
and a full significant digit analysis
should be conducted to ensure that two
decimal places can be carried for
efficiency. (HI, No. 8 at pp. 14–15) HI
also indicated that because all data in
the equation are supposed to be
normalized to 1,800 or 3,600 rpm, Q100%
should be clarified as the flow at BEP in
gallons per minute normalized to
synchronous speed at 60 Hz. In
response to HI’s suggested clarifications
to the pump efficiency equipment
presented in the April 2015 pump test
procedure NOPR and the slide deck
presented at the NOPR public meeting
(see Docket No. EERE–2013–BT–TP–
0055, No. 6 at p.49), DOE is clarifying
in this final rule that Q100% in the
minimum pump efficiency equation
(hpump,STD) is the BEP flow rate (gpm)
measured at 60 Hz and full impeller
diameter and normalized to nominal
speed of rotation of the pump (1,800 or
3,600 rpm). DOE has also revised the
equation for minimum pump efficiency
equation (hpump,STD) to match the
equation shared during the public
meeting, as suggested by HI.
Regarding the significance of the
555.6 value in equation (5) and its
impact on the number of significant
digits in the resultant minimally
compliant pump efficiency (h,pump,STD)
or final determination of PEICL or PEIVL,
DOE notes that all coefficients in the
listed equations in DOE’s pump test
procedure, including the equation for
mandatory pump efficiency with a
minimally compliant pump and will be
established in the pump energy
conservation standard rulemaking.
4107
the minimally compliant pump
efficiency, should be treated as
infinitely significant and should not
limit the number of significant digits
reported in the resultant value. As noted
in the April 2015 pumps test procedure
NOPR and discussed in more detail in
section III.C.2.f, all calculations should
be performed with raw measured values
and rounded only when determining
PERCL or PERVL and PEICL or PEIVL. 80
FR 17586, 17612 (April 1, 2015)
However, considering HI’s comment,
DOE acknowledges that testing
personnel or manufacturers may
inadvertently interpret equation
coefficients to be reflective of a given
degree of resolution, precision, or
significance. Therefore, to ensure that,
even if the coefficients are incorrectly
treated as carrying an indication of
measurement resolution or precision
such rounding does not impact the
significance of the reported PERCL and
PEICL or PERVL and PEIVL values, DOE
is adding values (zeros in most cases)
after the decimal to some of the
coefficients in the minimally compliant
pump efficiency equation, as shown in
equation (6):
Where:
Ns = specific speed,
nsp = nominal speed of rotation (rpm),
35 The equation to define the minimally
compliant pump in the EU is of the same form, but
employs different coefficients to reflect the fact that
the flow will be reported in m3/h at 50 Hz and the
specific speed will also be reported in metric units.
Specific speed is a dimensionless quantity, but has
a different magnitude when calculated using metric
versus U.S. customary units. DOE notes that an
exact translation from metric to U.S. customary
units is not possible due to the logarithmic
relationship of the terms.
VerDate Sep<11>2014
15:06 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.005 ER25JA16.006
DOE added sufficient significant
digits to ensure efficiency can be
reported to 4 significant digits (i.e., the
hundredths place for efficiencies greater
than 10 percent). DOE is also adding
zeros to the equations for calculating the
reference system curve (described in
section III.E.1.c) to similarly ensure
sufficient significance is maintained
throughout DOE’s test procedure
calculations.
In equation (6), the specific speed (Ns)
is a quasi-non-dimensional number
used to classify pumps based on their
relative geometry and hydraulic
characteristics. It is calculated as a
function of the rotational speed, flow
rate, head of the pump, and number of
stages as shown in equation (7) below:
ER25JA16.004
tkelley on DSK3SPTVN1PROD with RULES2
Where:
Q100% = BEP flow rate measured at full
impeller diameter and normalized to the
nominal speed of rotation for the tested
pump (gpm),
Ns = specific speed at 60 Hz and calculated
using U.S. customary units, and
C = a constant that is set for the twodimensional surface described by
equation (6) based on the speed of
rotation and equipment type of the pump
model. This constant, or ‘‘C-value,’’ is
used to establish the minimum,
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
DOE notes that, in the April 2015
pumps test procedure NOPR, the
definition of specific speed did not
indicate that the H100% term should be
normalized by the number of stages. 80
FR 17586, 17604 (April 1, 2015).
However, doing so is consistent with the
theoretical calculation of specific speed
for multi-stage pumps used in the pump
industry,36 as well as the CIP Working
Group discussions and analysis 37 and
treatment in the EU 547 regulations.38
DOE also noted this in the second
footnote to Table 1.2 in the Framework
document. (Docket No. EERE–2011–BT–
STD–0031, No. 13 at p. 7) To clarify
that, for multi-stage RSV and VTS
pumps the specific speed should be
calculated for a single stage only, DOE
is modifying equation (7) to clearly
specify that the head at BEP should be
divided by the number of stages with
which the pump is being tested.
Further, DOE also proposed using the
capital letter ‘‘N’’ to define nominal
speed of rotation. DOE notes that HI
40.6–2014 defines the ‘‘specified speed
of rotation’’ using the nomenclature
‘‘nsp.’’ While DOE believes that the
phrase ‘‘nominal speed of rotation’’ is
clearer and more consistent with DOE’s
regulatory approach, DOE believes
referencing the same nomenclature as
HI 40.6–2014 will reduce confusion
tkelley on DSK3SPTVN1PROD with RULES2
Where:
wi = weighting at load point i (equal
weighting or 0.3333 in this case);
Pu,i = the measured hydraulic output power
at load point i of the tested pump (hp); 39
ai = 0.947 for 75 percent of the BEP flow rate,
1.000 for 100 percent of the BEP flow
rate, and 0.985 for 110 percent of the
BEP flow rate;
hpump,STD = the minimally compliant pump
efficiency, as determined in accordance
with equation (6);
Li = the motor losses at load point i, as
determined in accordance with the
procedure specified for bare pumps in
sections III.D.1 and III.D.2; and
i = load point corresponding to 75, 100, or
110 percent of BEP flow, as determined
80 FR 17586, 17605 (April 1, 2015).
DOE also proposed in the April 2015
pumps test procedure NOPR that the
quotient of the hydraulic output power
divided by the minimally compliant
pump efficiency for the rated pump
would be used to determine the input
power to a minimally compliant pump
at each load point, and that the pump
hydraulic output power for the
minimally compliant pump would be
the same as that for the particular pump
being evaluated. Specifically, DOE
proposed that the hydraulic power in
equation (8) at 75, 100, and 110 percent
36 Wilson, S. Specific Speed. Grundfos White
Paper. Available at: https://www.grundfos.com/
content/dam/CBS/global/whitepapers/SpecificSpeed.pdf.
37 DOE’s PEI Calculator that was used to support
Working Group negotiations and analysis divided
the pump total head at 100 percent of BEP flow by
the number of stages for multi-stage pumps (See, for
example, Docket No. EERE–2013–BT–NOC–0039,
No. 95).
38 Council of the European Union. 2012.
Commission Regulation (EU) No 547/2012 of 25
June 2012 implementing Directive 2009/125/EC of
the European Parliament and of the Council with
regard to ecodesign requirements for water pumps.
Official Journal of the European Union. L 165, 26
June 2012.
39 In the April 2015 pumps test procedure NOPR,
DOE proposed to define pump hydraulic output
power using the variable nomenclature PHydro.
However, HI 40.6–2014 uses the nomenclature Pu to
refer to pump hydraulic output power. Therefore,
for consistency, DOE is adopting the nomenclature
Pu for hydraulic output power in this final rule.
VerDate Sep<11>2014
15:06 Jan 22, 2016
Jkt 238001
in accordance with the DOE test
procedure.
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
when conducting the pumps test
procedure. As such, in this final rule,
DOE is updating the variable used for
nominal speed of rotation to be
consistent with HI 40.6–2014.
As proposed in the April 2015 pumps
test procedure NOPR, the calculated
efficiency of the minimally compliant
pump reflects the pump efficiency at
BEP. To calculate PERSTD as the
weighted average input power to a
minimally compliant bare pump at the
same load points as PERCL, DOE
determined a method to translate the
default efficiency of a minimally
compliant pump at BEP to the load
points corresponding to 75 and 110
percent of BEP flow, as shown in
equation (8):
of BEP flow would be calculated using
the following equation (9):
Where:
Pu,i = the measured hydraulic output power
at load point i of the tested pump (hp);
Qi = the measured flow rate at load point i
of the tested pump (gpm);
Hi = pump total head at load point i of the
tested pump (ft);
i = load point corresponding to 75, 100, or
110 percent of BEP flow, as determined
in accordance with the DOE test
procedure; and
SG = the specific gravity of water at specified
test conditions.40
40 DOE notes that the specific gravity of the test
liquid specified in the DOE test procedure, which
is clear water as defined by section 40.6.5.5 of HI
40.6–2014, requires that the liquid be between 50–
86 °F, with a maximum kinematic viscosity of 1.6
× 10¥5ft2/s and a maximum density of 62.4 lb/ft3.
Based on these parameters, the specific gravity of
the test liquid will be between 1.000 and 0.995 and,
therefore, can be treated as unity when testing in
accordance with the DOE test procedure.
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.008
Q100% = BEP flow rate at full impeller and
nominal speed (gpm),
H100% = pump total head at BEP flow at full
impeller and nominal speed (ft), and
S = number of stages.
ER25JA16.007
4108
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
4109
Id.
As indicated in equation (8), the
calculated shaft input power for the
minimally compliant pump at each load
point is then combined with a
minimally compliant motor for that
default motor type and appropriate size,
as described in section III.D.1, and the
default part load loss curve, as
described in section III.D.2, to
determine the input power to the motor
at each load point. Id.
As noted previously, HI and CA IOUs
expressed their support of DOE’s
proposed approach. (HI, No. 8 at p. 7;
CA IOUs, NOPR public meeting
transcript, No. 7 at p. 110) HI also
pointed out in its written comments that
hpump,STD incorrectly appeared twice in
the middle term in the denominator in
equation (10) of the April 2015 pumps
test procedure NOPR. (HI, No. 8 at p. 15)
DOE acknowledges the correction and
has implemented the equation correctly
in this final rule document. Having
received no other comments, DOE is
adopting the calculation procedure for
PERSTD as proposed in the April 2015
pumps test procedure NOPR, with the
minor clarifications regarding the
number of digits reported for certain
equation coefficients and calculation of
specific speed for multi-stage pumps as
noted above and correcting the
erroneous terms that occurred in the
April 2015 pump test procedure NOPR.
Regarding the calculation of pump
hydraulic output power presented in
equation (9), DOE notes that the
equation presented in the April 2015
pumps test procedure NOPR specifies a
denominator of 3956. 80 FR 17586,
17605 (April 1, 2015). DOE notes that
this value represents the unit
conversion from the product of flow (Q)
in gpm, head in ft, and specific gravity
(which is dimensionless), to
horsepower. Conversely, DOE observes
that HI 40.6–2014 specifies a value of
3960 in section 40.6.6.2 in regards to
calculating pump efficiency. HI 40.6–
2014 does not specify a specific unit
conversion factor for the purposes of
calculating pump hydraulic output
power. Instead HI 40.6–2014 provides
the following equation (10) for
determining pump power output:
Where:
Pu = the measured hydraulic output power of
the tested pump,41
r = density,
Q = the volume rate of flow,
H = pump total head, and
g = acceleration due to gravity.
DOE is maintaining a unit conversion
factor of 3956 instead of the 3960 value
specified in HI 40.6–2014 and clarifying
that the 3960 calculation in section
40.6.6.2 of HI 40.6–2014 should not be
used. The calculation and rounding
requirements for the pumps test
procedure are described further in
section III.C.2.f.
PEICL or PEIVL. 80 FR 17586, 17606–07
(April 1, 2015).
However, as noted above, DOE
believes a unit conversion of 3956 is
more accurate. Therefore, to ensure
consistent calculations and results in
the DOE test procedure, in this final rule
41 For each of the quantities listed, HI 40.6–2014
provides multiple metric and U.S. customary units.
Appendix E also provides unit conversions.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
To determine PEICL or PEIVL for
applicable pumps, DOE proposed that
the test procedure would require
physically measuring the performance
of either: (1) The bare pump, under the
calculation-based methods (see section
III.E.1), or (2) the entire pump, inclusive
of any motor, continuous control, or
non-continuous control, under the
testing-based methods (see section
III.E.2). Specifically, the input power to
the pump at 75, 100, and 110 percent of
BEP flow for PEICL, or at 25, 50, 75, and
100 percent of BEP flow for PEIVL,
would be required for input into the
PEICL or PEIVL equations, respectively.
DOE proposed that, depending on
whether the calculation-based method
or testing-based method were applied, a
slightly different test method would
apply for measuring pump performance.
In the case of the calculation-based
method, only the bare pump
performance is physically measured—
the performance of the motor and any
continuous or non-continuous controls
would be addressed through a series of
calculations. In the case of the testingbased method, the input power to the
pump at the motor or at the continuous
or non-continuous control, if any, is
directly measured and used to calculate
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
42 The term ‘‘pump power input’’ in HI 40.6–2014
is defined as ‘‘the power transmitted to the pump
by its driver’’ and is synonymous with the term
‘‘pump shaft input power,’’ as used in this
document.
43 The term ‘‘driver power input’’ in HI 40.6–2014
is defined as ‘‘the power absorbed by the pump
driver’’ and is synonymous with the term ‘‘pump
input power to the driver,’’ as used in this
document.
44 The term ‘‘pump power output’’ in HI–40.6 is
defined as ‘‘the mechanical power transferred to the
liquid as it passes through the pump, also known
as pump hydraulic power.’’ It is used
synonymously with ‘‘pump hydraulic power’’ in
this document.
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.009
tkelley on DSK3SPTVN1PROD with RULES2
Where:
Pu = measured hydraulic output power (hp),
Q = measured flow rate (gpm),
H = measured pump total head (ft), and
SG = the specific gravity of the test fluid.
(HI, No. 8 at p. 10; HI, No. 15 at p. 3)
C. Determination of Pump Performance
Regarding the determination of bare
pump performance, the CIP Working
Group recommended that whatever
procedure DOE adopts, it should be
consistent with HI 40.6–2014 for
determining bare pump performance.
(Docket No. EERE–2013–BT–NOC–0039,
No. 92, Recommendation #10 at pg. 4)
In preparation of the April 2015 pump
test procedure NOPR, DOE reviewed HI
40.6–2014 and determined that it
contains the relevant test methods
needed to accurately characterize the
performance of the pumps that would
be addressed by this rulemaking, with a
few minor modifications noted in
section III.C.2. Specifically, HI 40.6–
2014 defines and explains how to
calculate pump power input,42 driver
power input (for testing-based
methods),43 pump power output,44
ER25JA16.065
As shown in equation (10), the unit
conversion factor can be derived from
the product of density and acceleration
due to gravity. An analysis was
performed to convert from the metric
units for density and acceleration due to
gravity specified in HI 40.6–2014 to the
appropriate units. This analysis found
the value of 3956 to be more accurate
and have a greater amount of precision
than the 3960 value specified in HI
40.6–2014. DOE notes that, in its
submitted comments, HI suggested a
definition for hydraulic power as ‘‘the
mechanical power transferred to the
liquid as it passes through the pump,
also known as pump output power.
(Refer to HI 40.6¥2014)’’ and provided
the following equation (11):
1. Incorporation by Reference of HI
40.6–2014
4110
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
pump efficiency,45 bowl efficiency,46
overall efficiency,47 and other relevant
quantities at the specified load points
necessary to determine PEICL and PEIVL.
HI 40.6–2014 also contains appropriate
specifications regarding the scope of
pumps covered by the test methods, test
methodology, standard rating
conditions, equipment specifications,
uncertainty calculations, and tolerances.
Accordingly, in the April 2015 pumps
test procedure NOPR, DOE proposed to
incorporate by reference HI 40.6–2014
as part of DOE’s test procedure for
measuring the energy consumption of
pumps, with the minor modifications
and exceptions listed in III.C.2.a
through III.C.2.f of the NOPR document
and discussed in more detail in section
III.C.2 of this final rule. 80 FR 17586,
17607–12 (April 1, 2015).
HI commented that it agrees with
using HI 40.6–2014 as the basis of DOE
test procedure for pumps. (HI, No. 8 at
p. 15) DOE received no other comments
on this proposal in the April 2015
pumps test procedure NOPR and,
therefore, is incorporating by reference
HI 40.6–2014 as the basis for the DOE
pumps test procedure, with the minor
modifications and exceptions listed in
section III.C.2 of this final rule.
2. Minor Modifications and Additions to
HI 40.6–2014
tkelley on DSK3SPTVN1PROD with RULES2
In general, DOE finds the test methods
contained within HI 40.6–2014 are
sufficiently specific and reasonably
designed to produce test results that
accurately measure the energy efficiency
and energy use of applicable pumps.
However, as proposed in the April 2015
pumps test procedure NOPR, DOE
believes a few minor modifications are
necessary to ensure repeatable and
reproducible test results and to provide
measurement methods and equipment
specifications for the entire scope of
pumps that DOE is addressing as part of
this final rule. DOE’s proposed
modifications and clarifications to HI
40.6–2014, comments received on those
topics, DOE’s responses to those
comments, and any changes to the April
2015 pumps test procedure NOPR
proposals that DOE is making as a result
are addressed in the subsequent sections
III.C.2.a through III.C.2.f.
45 The term ‘‘pump efficiency’’ is defined in HI
40.6–2014 as a ratio of pump power output to pump
power input.
46 The term ‘‘bowl efficiency’’ is defined in HI
40.6–2014 as a ratio of pump power output to bowl
assembly power input and is applicable only to
VTS and RSV pumps.
47 The term ‘‘overall efficiency’’ is defined in HI
40.6–2014 as a ratio of pump power output to driver
power input and describes the combined efficiency
of a pump and driver.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
a. Sections Excluded From DOE’s
Incorporation by Reference
While DOE is referencing HI 40.6–
2014 as the basis for its test procedure,
in the April 2015 pumps test procedure
NOPR, DOE noted that some sections of
the standard are not applicable to DOE’s
regulatory framework. Specifically, DOE
noted that section 40.6.5.3 provides
requirements regarding the generation of
a test report and appendix ‘‘B’’ provides
guidance on test report formatting, both
of which are not required for testing and
rating pumps in accordance with DOE’s
procedure. In addition, DOE noted that
section A.7 of appendix A, ‘‘Testing at
temperatures exceeding 30 °C (86 °F),’’
HI 40.6–2014 addresses testing at
temperatures above 30 °C (86 °F), which
is inconsistent with DOE’s proposal to
only test with liquids meeting the
definition of ‘‘clear water’’ established
in section 40.6.5.5 of HI 40.6–2014. As
such, DOE proposed not incorporating
by reference section 40.6.5.3, section
A.7, and appendix B of HI 40.6–2014. 80
FR 17586, 17608 (April 1, 2015).
HI commented that it agrees with the
proposal to not incorporate by reference
section 40.6.5.3, section A.7, and
appendix B of HI 40.6–2014 as part of
the DOE test procedure. (HI, No. 8 at 15)
DOE received no other comments on
this proposal in the April 2015 pumps
test procedure NOPR and, as such, is
adopting the proposal in the April 2015
pumps test procedure NOPR to
incorporate by reference HI 40.6–2014
except for section 40.6.5.3, section A.7,
and appendix B in this final rule.
In reviewing the relevant sections of
HI 40.6–2014, DOE also noted that
section 40.6.4.1, ‘‘Vertically suspended
pumps,’’ which contains specific testing
instructions for vertically suspended
VS1 and VS3 pumps, mentions VS0
pumps. Specifically, section 40.6.4.1
states ‘‘A variation to this is pump type
VS0 . . . [a] VS0 [pump] is evaluated as
a pump end only similar to the bowl
performance and efficiency described
for the line-shafted product.’’ DOE notes
that this language in HI 40.6–2014 is
intended to exclude VS0 pumps from
the specifications in section 40.6.4.1
and specify that testing for VS0, as a
type of vertical turbine pump, must
consider only bowl assembly total head
and, for VTS bare pumps, only the bowl
assembly power input, as defined in
section 40.6.2 of HI 40.6–2014.
However, DOE believes that the
language of section 40.6.4.1 is somewhat
confusing and may lead to
misinterpretation by some not familiar
with all the varieties of vertical turbine
and vertically suspended pumps and
their specific testing considerations.
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
Therefore, in this final rule, DOE is
clarifying that the specifications of
section 40.6.4.1 of HI 40.6–2014 do not
apply to VTS pumps and that the
performance of VTS bare pumps
considers the bowl performance only.
For VTS pumps sold with motors
evaluated using the testing-based
approaches discussed in section III.E.2,
the bowl assembly total head and driver
power input are to be used to determine
the pump performance.
b. Data Collection and Determination of
Stabilization
In order to ensure the repeatability of
test data and results, the DOE pump test
procedure must provide instructions
regarding how to sample and collect
data at each load point such that the
collected data are taken at stabilized
conditions that accurately and precisely
represent the performance of the pump
at that load point. Section 40.6.5.5.1 of
HI 40.6–2014 provides that all
measurements shall be made under
steady state conditions, which are
described as follows: (1) No vortexing,
(2) margins as specified in ANSI/HI
9.6.1 Rotodynamic Pumps Guideline for
NPSH Margin, and (3) when the mean
value of all measured quantities
required for the test data point remains
constant within the permissible
amplitudes of fluctuations defined in
Table 40.6.3.2.2 over a minimum period
of 10 seconds before performance data
are collected. HI 40.6–2014 does not
specify the measurement interval for
determination of steady state operation.
However, DOE understands that a
minimum of two stabilization
measurements are required to calculate
an average. DOE proposed in the April
2015 pumps test procedure NOPR that
the stabilization measurement interval
should not be greater than 5 seconds,
thereby allowing for no fewer than two
separate measurements that each have
an integration time of no more than 5
seconds. 80 FR 17586, 17606 (April 1,
2015).
Section 40.6.3.2.2 of HI 40.6–2014,
‘‘Permissible fluctuations,’’ also
provides that permissible damping
devices may be used to minimize noise
and large fluctuations in the data in
order to achieve the specifications noted
in Table 40.6.3.2.2. In the April 2015
pumps test procedure NOPR, DOE
proposed to specify that damping
devices would only be permitted to
integrate up to the measurement interval
to ensure that each stabilization data
point is reflective of a separate
measurement. 80 FR 17586, 17606
(April 1, 2015).
DOE requested comment on its
proposal to require that data be
E:\FR\FM\25JAR2.SGM
25JAR2
4111
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
collected at least every 5 seconds for all
measured quantities. HI commented that
collecting stabilization data every 5
seconds is not standard industry
practice, and that this practice would
require manufacturers to obtain
automated data acquisition systems,
posing additional and unnecessary
burden not agreed to by the CIP
Working Group. (HI, No. 8 at pp. 15–16)
HI recommended that steady-state
operation be verified by recording flow
at the beginning and end of the data
acquisition and checking that the
difference in flow is within the
allowable fluctuation identified in HI
40.6–2014 (Table 40.6.3.2.2). HI also
stated that the two flow readings should
be separated by a minimum of 5
seconds.
DOE also requested comment on its
proposal to allow damping devices, as
described in section 40.6.3.2.2, but with
integration limited to the data collection
interval and HI commented that it
agrees with this proposal except with
respect to the interval used for data
collection. (HI, No. 8 at p. 16)
After reviewing HI’s comments and
considering the proposal in the April
2015 pump test procedure NOPR, DOE
maintains that at least two unique
measurements, at a minimum, are
necessary to determine stabilization
prior to recording a measurement at a
given load point. DOE also agrees with
HI that it is appropriate to continue to
reference the requirements for
permissible fluctuations and minimum
duration of stabilization testing, as
detailed in HI 40.6–2014 sections
40.6.3.2.2 and 40.6.5.5.1. However, in
light of HI’s concern regarding
automated data collection requirements
if the interval of data collection is
specified as 5 seconds, DOE has
determined that a threshold for the data
collection interval does not need to be
specified to determine steady state
operation provided the other
requirements for stabilization are
satisfied. That is, provided that at least
two unique measurements are recorded,
their mean computed, and that the two
unique measurements are not farther
away from the mean than the tolerance
specified in the ‘‘permissible amplitude
of fluctuation’’ table (Table 40.6.3.2.2)
in HI 40.6–2014, the pump can be
determined to be stabilized and data
recorded for the purposes of conducting
the DOE test procedure. DOE notes that
section 40.6.5.5.1 requires that steady
state be determined for a minimum of
10 seconds, but that a longer time can
be used if necessary, in which case the
two unique measurements could be
recorded more than 5 seconds apart. For
example, if a facility were not equipped
with a data acquisition system,
stabilization could be determined over 1
minute and data taken every 30 seconds
to determine stabilized operation at
each flow point.
Regarding the use of damping devices,
DOE is maintaining the requirements
that the integration time for each
measurement cannot be greater than the
measurement interval. This is necessary
to ensure that the measurements used to
determine stabilization are, in fact,
unique. Therefore, in this test procedure
final rule, DOE is adopting stabilization
requirements consistent with HI section
40.6.3.2.2 and section 40.6.5.5.1, except
that at least two unique measurements
must be used to determine stabilization
and any damping devices are only
permitted to integrate up to the data
collection interval. DOE notes that, for
physical dampening devices, the
pressure indicator/signal must register
99 percent of a sudden change in
pressure over the measurement interval
to satisfy the requirement for unique
measurements, consistent with annex D
of ISO 3966:2008(E), ‘‘Measurement of
fluid flow in closed conduits—Velocity
area method using Pitot static tubes,’’
which is referenced in HI 40.6–2014 for
measuring flow with pitot tubes.
c. Modifications Regarding Test
Consistency and Repeatability
Sections 40.6.5.6 and 40.6.5.7 of HI
40.6–2014 specify test arrangements and
test conditions. However, DOE finds
that the standardized test conditions
described in these sections are not
sufficient to produce accurate and
repeatable test results. To address these
potential sources of variability or
ambiguity, in the April 2015 pumps test
procedure NOPR, DOE proposed to
adopt several additional requirements
regarding the nominal pump speed, the
input power characteristics, and the
number of stages to test for multi-stage
pumps to further specify the procedures
for testing pumps in a standardized and
repeatable manner. 80 FR 17586, 17608
(April 1, 2015).
Pump Speed
The rotating speed of a pump affects
the efficiency and PEICL or PEIVL of that
pump. To limit variability and increase
repeatability within the test procedure,
DOE proposed in the April 2015 pumps
test procedure NOPR to require all test
data to be normalized to one of two
nominal speeds—1,800 or 3,600 rpm at
60 Hz. Specifically, pumps designed to
operate at any speed of rotation between
2,880 and 4,320 rpm would be rated at
3,600 rpm, and pumps designed to
operate at any speed of rotation between
1,440 and 2,160 rpm would be rated at
1,800 rpm, as noted in Table III.3. 80 FR
17586, 17609 (April 1, 2015).
TABLE III.3—NOMINAL SPEED OF ROTATION FOR DIFFERENT CONFIGURATIONS OF PUMPS
Pump configuration
Pump design speed of rotation
Style of motor
Bare Pump .....................................
2,880 and 4,320 rpm ....................
1,440 and 2,160 rpm ....................
N/A ................................................
N/A ................................................
N/A ................................................
N/A ...........................................................................
Pump + Motor OR .........................
Pump + Motor + Control ................
tkelley on DSK3SPTVN1PROD with RULES2
N/A ................................................
DOE proposed that, for pumps sold
without motors, the nominal speed
would be selected based on the speed of
rotation for which the pump is designed
to be operated, while for pumps sold
with motors, the nominal speed of
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
2-pole Induction Motor .............................................
4-pole Induction Motor .............................................
Non-Induction Motor Designed to Operate between
2,880 and 4,320 rpm.
Non-Induction Motor Designed to Operate between
1,440 and 2,160 rpm.
rotation would be selected based on the
speed(s) for which the motor is designed
to operate. DOE also clarified that
pumps designed to operate at speeds
that include both ranges would be rated
at both nominal speeds of rotations
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
Nominal speed
of rotation for
rating
3,600
1,800
3,600
1,800
3,600
rpm.
rpm.
rpm.
rpm.
rpm.
1,800 rpm.
since each nominal speed rating
represents a different basic model of
pump. Finally, DOE noted that these
speed ranges are not exclusive. That is,
if a pump were to be designed to operate
from 2,600 to 4,000 rpm, such a pump
E:\FR\FM\25JAR2.SGM
25JAR2
4112
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
would have a nominal speed of rotation
of 3,600 rpm for the purposes of testing
and rating the pump, even though part
of the operating range of the pump (i.e.,
2,600 to 2,880 rpm) falls outside DOE’s
specified speed ranges.
In DOE’s April 2015 pumps test
procedure NOPR proposal, DOE
acknowledged that it may not be
feasible to operate pumps during the
test at exactly the nominal speeds of
3,600 or 1,800 rpm and noted that
section 40.6.5.5.2 of HI 40.6–2014
allows for tested speeds up to 20
percent off of the nominal speed,
provided the tested speed does not vary
more than ±1 percent at each load point
as required by section 40.6.3.2.2 of HI
40.6–2014. However, to ensure
consistent and comparable test results,
DOE proposed that all data collected
during the test procedure at the speed
measured during the test should be
adjusted to the nominal speed prior to
use in subsequent calculations and the
PEICL or PEIVL of a given pump should
be based on the nominal speed. Id. For
pumps sold with motors and continuous
or non-continuous controls and that are
tested using the testing-based method
described in section III.E.2.c, DOE
proposed that this adjustment to the
nominal speed only apply at the 100
percent of BEP flow load point and that
subsequent part load points be
measured at reduced speed and used in
subsequent calculations without
adjustment. DOE also proposed to use
the methods in HI 40.6–2014 section
40.6.6.1.1, ‘‘Translation of the test
results into data based on the specified
speed of rotation (for frequency) and
density’’ to adjust any data from the
tested speed to the nominal speed. Id.
DOE requested comment on its
proposal to require data collected at the
pump speed measured during testing to
be normalized to the nominal speeds of
1,800 and 3,600 rpm. HI commented
that it agrees with the proposal. (HI, No.
8 at p. 16)
Therefore, in this test procedure final
rule, DOE is opting to adopt the
operating speed limits proposed in the
April 2015 pumps test procedure NOPR
and discussed in section III.A.4 for the
purposes of applying this test procedure
final rule.
DOE also requested comment on its
proposal to adopt the requirements in
HI 40.6–2014 regarding the deviation of
tested speed from nominal speed and
the variation of speed during the test,
specifically regarding whether
maintaining tested speed within ±1
percent of the nominal speed is feasible
and whether this approach would
produce more accurate and repeatable
test results. HI commented that it does
not believe it is feasible to maintain
tested speed within ±1 percent of the
specified nominal speed because typical
motor speed-load curves do not meet
this criterion. (HI, No. 8 at p. 16)
However, HI also noted that data could
be collected and rotating speed
maintained at ±1 percent for a particular
data collection point. DOE believes that
HI may have misinterpreted the
proposal in the April 2015 pumps test
procedure NOPR. In the NOPR, DOE
proposed maintaining the speed of
rotation at each test point within the ±1
percent speed tolerance, but that the
speed of rotation at each test point
could vary from the nominal speed of
rotation ±20 percent, consistent with HI
40.6¥2014. DOE agrees that the ±1
percent speed tolerance is applicable to
determining stabilization at each data
collection point only and is not
determined relative to nominal speed
and, therefore, is adopting the April
2015 pump test procedure NOPR
proposal to adopt the nominal speed
tolerances listed in section 40.6.5.5.2 of
HI 40.6–2014, as well as the
stabilization requirements provided in
section 40.6.3.2.2 of HI 40.6–2014 in
this test procedure final rule.
Additionally, DOE is adopting the
provisions that all measured data be
translated to the nominal rating speed.
Power Supply Characteristics
Because pump power consumption is
a component of the proposed metric,
inclusive of any motor and continuous
or non-continuous controls, measuring
power consumption is an important
element of the test. The characteristics
of the power supplied to the pump
affect the accuracy and repeatability of
the measured power consumption of the
pump. As such, to ensure accurate and
repeatable measurement of power
consumption, in the April 2015 pumps
test procedure NOPR, DOE specified
nominal values for voltage, frequency,
voltage unbalance, total harmonic
distortion (THD), and impedance levels,
as well as tolerances about each of these
quantities, that must be maintained at
the input terminals to the motor,
continuous control, or non-continuous
control, as applicable when performing
the testing-based methods or when
using a calibrated motor to determine
bare pump performance. 80 FR 17586,
17610 (April 1, 2015).
To determine the appropriate power
supply characteristics for testing pumps
with motors (but without continuous or
non-continuous controls) and pumps
with both motors and continuous or
non-continuous controls, DOE
examined applicable test methods for
electric motors and VSD systems. DOE
determined that the Institute of
Electrical and Electronics Engineers
(IEEE) Standard 112–2004, ‘‘IEEE
Standard Test Procedure for Polyphase
Induction Motors and Generators,’’
(IEEE 112–2004) and the Canadian
Standards Association (CSA) C390–10,
‘‘Test methods, marking requirements,
and energy efficiency levels for threephase induction motors,’’ (CSA C390–
10) are the most relevant test methods
for measuring input power to electric
motors, as they are the test methods
incorporated by reference as the DOE
test procedure for electric motors. Other
widely referenced industry standard test
methods for motors include: IEC 60034–
1 Edition 12.0 2010–02, ‘‘Rotating
electrical machines—Part 1: Rating and
performance’’ (IEC 60034–1:2010) and
NEMA MG 1–2014, ‘‘Motors and
Generators’’ (NEMA MG 1–2014). DOE
also identified both AHRI 1210–2011,
‘‘2011 Standard for Performance Rating
of Variable Frequency Drives,’’ (AHRI
1210–2011) and the 2013 version of
CSA Standard C838, ‘‘Energy efficiency
test methods for three-phase variable
frequency drive systems,’’ (CSA C838–
13) as applicable methods for measuring
the performance of VSD control
systems. A summary of DOE’s proposed
power supply characteristics and the
requirements of the industry standards
DOE referenced in developing such a
proposal are summarized in Table III.4.
tkelley on DSK3SPTVN1PROD with RULES2
TABLE III.4—SUMMARY OF TOLERANCES PROPOSED BY DOE IN THE APRIL 2015 PUMPS TEST PROCEDURE NOPR AND
REFERENCED IN RELEVANT INDUSTRY STANDARDS
Reference document
Section
Voltage
unbalance
Voltage tolerance
Frequency
tolerance
April 2015 Pumps Test Procedure
NOPR Proposal.
HI 40.6–2014 (calibrated motors) .....
III.C.2.c ....
±0.5% ......
±0.5% .................
±0.5% .................
C.4.1 ........
..................
±5% ....................
±1%.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
E:\FR\FM\25JAR2.SGM
Voltage waveform
distortion
THD ≤5%.
25JAR2
Source
impedance
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
4113
TABLE III.4—SUMMARY OF TOLERANCES PROPOSED BY DOE IN THE APRIL 2015 PUMPS TEST PROCEDURE NOPR AND
REFERENCED IN RELEVANT INDUSTRY STANDARDS—Continued
Reference document
Section
Voltage
unbalance
Voltage tolerance
Frequency
tolerance
CSA C390–10 (motors) ....................
5.2 ...........
±0.5% ......
±0.5% .................
±0.5% .................
IEC 60034–1:2010 (motors) .............
7.3 ...........
9.11 ..........
..................
..................
±5% * (zone A) ...
............................
±2% * (zone A).
............................
IEEE 112–2004 (motors) ..................
NEMA MG 1–2014 (motors) .............
3.1 ...........
7.7.3.2 .....
≤0.5% ......
≤1% .........
............................
............................
±0.5% .................
±0.5% .................
..................
≤1% †.
≤0.5% ......
±0.5% ......
±10% ** ...............
±5% **.
AHRI 1210–2011 (VFDs) ..................
CSA C838–13 (VFDs) ......................
12.44.1 .....
12.45 ........
5.1.2 .........
5.3 ...........
±0.5% .................
±0.5% .................
±0.5% .................
±0.5% .................
Voltage waveform
distortion
Source
impedance
THD ≤5% (to
20th).
THD ≤5% (to
100th).
THD ≤5%.
deviation factor
≤10%.
............................
THD ≤5% (to
20th).
≤1%.
1% < value ≤3%
of VFD.
tkelley on DSK3SPTVN1PROD with RULES2
* Values are for the overall bounds of the hexagonal surface in IEC Figure 12.
** NEMA states that performance within these voltage and frequency variations will not necessarily be in accordance with the standards established for operation at rated voltage and frequency.
† NEMA states that performance will not necessarily be the same as when the motor is operating with a balanced voltage at the motor
terminals.
HI commented that it disagrees with
the power conditioning requirements
proposed in the April 2015 pumps test
procedure NOPR; knows of no pump
test labs that meet them; and views
them as a significant and unnecessary
burden to manufacturers that were not
agreed to by the CIP Working Group. HI
specifically cited costs associated with
the proposed limitation on voltage
unbalance, and noted that the nominal
motor efficiency values used for the
calculation method have a less stringent
tolerance of 2 percent. HI also indicated
that testing with unconditioned power
will result in a lower efficiency value
and a higher PEI value than when
testing with conditioned power. HI
proposed that whereas conditioned
power, as proposed in the April 2015
pumps test procedure NOPR, should be
used for DOE enforcement testing and
motor calibration, manufacturer test labs
should only be held to the 3 percent
limit for driver input power fluctuation
specified in HI 40.6–2014. (HI, No. 8 at
pp. 16–18)
Regal Beloit stated during the April
2015 NOPR public meeting that motor
manufacturers faced similar challenges
when motor standards were introduced,
and third-party test labs adapted to help
meet the power conditioning
requirements. Regal Beloit also
indicated that AHRI 1210 was not
developed for pumps, and CSA C838
would be preferred. In addition, Regal
Beloit expressed concern that any
loosening of the power conditioning
requirements could hinder
differentiation between lower and
higher performing products. (Regal
Beloit, NOPR public meeting transcript,
No. 7 at pp. 137–46)
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
As noted in the April 2015 pumps test
procedure NOPR, DOE recognizes that
driver efficiency can vary: (a) When the
input voltage level is not exactly at the
nameplate voltage, (b) when the
fundamental frequency of the input
voltage waveform is not exactly 60 Hz,
(c) when input voltage phases are
unbalanced, and/or (d) when the input
voltage waveform is not strictly
sinusoidal. However, DOE
acknowledges the concerns of HI
regarding the burden of providing
power meeting strict voltage, frequency,
voltage unbalance, and THD limits. As
EPCA requires DOE test procedures to
not be unduly burdensome to conduct
(42 U.S.C. 6314(a)(2)), DOE, in this final
rule, is reconsidering the proposed
requirements regarding the power
supply characteristics to find a
compromise among repeatability,
accuracy, and test burden.
DOE notes that HI’s proposal of a ±3
percent tolerance on power is not
feasible without some parameters
around power supply characteristics, as
variation in voltage unbalance,
harmonics, voltage, and frequency will
affect the variability in the measurement
of input power to the pump insofar as
it will affect the performance and
efficiency of the motor. That is, for
example, increased voltage unbalance
will affect motor performance such that
testing the same pump sold with a
motor under differing voltage unbalance
conditions will result in different
measured pump performance. This can
be viewed either as: (1) Different
(typically lower) hydraulic output for
the same input power to the motor or (2)
different (typically increased) input
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
power to the motor to deliver the same
hydraulic output power.
Under the latter scenario, DOE has
developed an approach to correlate
variability in power supply
characteristics with variability in the
measured input power to the motor.
Similarly, DOE separately considered
how variability in power supply
characteristics would impact input
power to the continuous or noncontinuous controls. Specifically, DOE
determined, for each power supply
characteristic (i.e., voltage, frequency,
voltage unbalance, and voltage THD) the
level of variability that was associated
with HI’s proposed acceptable tolerance
of ±3 percent on driver input power. As
such, DOE considered each of the power
supply variables individually to
determine if alternative, less
burdensome requirements were feasible.
Regarding the impact of variation in
voltage, section 12.44.1 of NEMA MG 1–
2014 specifies that AC motors shall
operate successfully under running
conditions at rated load with a variation
in the voltage up to ±10 percent of rated
(nameplate) voltage with rated
frequency for induction motors.
Similarly, according to Figure 5–1 in the
DOE Advanced Manufacturing Office
(AMO) ‘‘Premium Efficiency Motor
Selection and Application Guide’’
(AMO motor handbook), the efficiency
of a ‘‘pre-EPAct’’ 48 standard efficiency
motor varies by less than ±3 percent
when operated at ±10 percent of
nameplate voltage. Section 2.2.2 of
ANSI C84.1–2011 states that the
nominal voltage of a system is near the
voltage level at which the system
48 Energy Policy Act of 2005, Public Law 109–58,
119 Stat. 594
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
4114
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
normally operates, and that systems
generally operate at voltage levels about
5 to 10 percent below the maximum
system voltage for which system
components are designed. DOE also
notes that section C.4.1 of HI 40.6–2014
indicates that when a calibrated motor
is used to determine the pump input
power, the voltage shall be the same as
used during the calibration of the motor
with a tolerance of ±5 percent; this
specification is consistent with the ±5
percent outermost limits in Figure 12 of
IEC 60034–1:2010 for zone A
(continuous operation). In consideration
of these standards, DOE has determined
that, within reasonable limits, motor
performance does not appear to be
strongly affected by variation in voltage.
However, DOE believes that it is
important to ensure voltage is
maintained within those reasonable
limits. Therefore, in this final rule, DOE
is adopting a tolerance on voltage
consistent with the requirements in HI
40.6–2014 of ±5.0 percent of the
nominal rated voltage. DOE believes
such a proposal provides representative
measurements without imposing undue
test burden on manufacturers.
Considering the impact of frequency
on the rated performance of pumps and
motors, the AMO motor handbook states
that a premium efficiency motor is
usually 0.5 to 2.0 percent more efficient
when operating at 60 Hz than when the
same motor is driven by a 50-Hz power
supply, suggesting that motor
performance is not strongly dependent
on frequency. However, section C.4.1 of
HI 40.6–2014 indicates that when a
calibrated motor is used to determine
the pump input power, the frequency
shall be the same as used during the
calibration of the motor with a tolerance
of ±1 percent. DOE believes that the HI
requirement would be equally
applicable to determining the
performance of pumps sold with motors
and pumps sold with motors and
continuous or non-continuous controls
under the testing-based methods to
ensure repeatable and accurate
measurements. Therefore, in this final
rule, DOE is relaxing the proposal in the
April 2015 pumps test procedure NOPR
to instead limit frequency variation of
±1.0 percent of nameplate frequency,
consistent with HI 40.6–2014. DOE also
notes that the U.S. electric grid typically
provides power at a frequency within
these bounds and, as such, DOE believe
such a tolerance will not impose undue
test burden. Further, DOE believes that
maintaining tolerances consistent with
the typical U.S. electric power supply is
necessary to ensure repeatability of the
test and ensure that the test is
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
representative of the energy
consumption of the equipment.
Specifically, a specification of ±1
percent is consistent with the ±1 percent
tolerance for continuous operation
across all durations of off-nominal
frequency specified in the North
American Electric Reliability
Corporation (NERC) Standard PRC–024–
1, ‘‘Generator Frequency and Voltage
Protective Relay Settings.’’
Regarding voltage unbalance, DOE
notes that motor performance will vary
as a function of voltage unbalance.
Specifically, NEMA MG 1–2014
includes a horsepower derating curve
for up to 5 percent voltage unbalance
and recommends limiting voltage
unbalance to 1 percent, noting that
motor performance will not necessarily
be the same as when the motor is
operating with a balanced voltage at the
motor terminals. Similarly, Table 5–3 in
the AMO motor handbook relates a
voltage unbalance of 3 percent to a
decrease in motor efficiency of 2 to 3
percent, compared with a decrease of 5
percent or more for a voltage unbalance
of 5 percent.49 DOE notes that a
variation of 3 percent in motor
efficiency equates to a 3 percent
variability in measured input power to
the motor.
Given the dependence of motor, and
thus pump, performance on voltage
unbalance, DOE then evaluated the
relative burden associated with
providing different levels of voltage
unbalance in the test facility, in an effort
to determine a level of voltage
unbalance that would not be unduly
burdensome to specify in the test
procedure. DOE researched typical
levels of voltage unbalance available on
the national electric grid, based on
utility standards and specifications for
generation and distribution of power.
NEMA MG 1–2014 states that if a motor
is subjected to more than 1 percent
voltage unbalance the manufacturer
should be consulted regarding this
unusual service condition, and the
AMO motor handbook states that
unbalances exceeding 1 percent will
void most manufacturers’ warranties.
DOE also found that PG&E Electric Rule
No. 2 states that the voltage balance
between phases for service delivery
voltages will be maintained by PG&E as
close as practicable to 2.5 percent.50
Similarly, Annex C of ANSI C84.1–2011
indicates that approximately 98 percent
49 DOE Office of Energy Efficiency and Renewable
Energy (EERE), Premium Efficiency Motor Selection
and Application Guide—A Handbook for Industry
(February 2014, www.energy.gov/eere/amo/motorsystems).
50 Accessed on August 21, 2015, at www.pge.com/
tariffs/tm2/pdf/ELEC_RULES_2.pdf.
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
of the electric supply systems surveyed
were found to be below 3.0 percent
voltage unbalance, and 66 percent were
found to be below 1.0 percent; the
standard states that electric supply
systems should be designed and
operated to limit the maximum voltage
unbalance to 3 percent when measured
at the electric-utility revenue meter
under no-load conditions.51 Therefore,
DOE determines 3.0 percent voltage
unbalance provides a reasonable
tolerance, would be generally available
to most testing facilities using gridsupplied power and would limit the
impact on input power to less than 3
percent, consistent with HI’s
recommendation.
Regarding limitations on harmonic
distortion on the power supply, the
AMO publication, ‘‘Improving Motor
and Drive System Performance’’ (AMO
motor sourcebook) states that electrical
equipment is often rated to handle 5
percent THD (as defined in IEEE Std
519), and notes that motors are typically
much less sensitive to harmonics than
computers or communication systems.52
Similarly, IEC 60034–1:2010 specifies a
limit of 5 percent voltage THD,
measured to the 100th harmonic. In
addition, for bus voltage of 1.0 kV or
less at the point of common coupling
(PCC), section 5.1 of IEEE Std 519–2014
recommends line-to-neutral harmonic
voltage limits of 5.0 percent individual
harmonic distortion and 8.0 percent
voltage THD for weekly 95th percentile
short time (10 min) values, measured to
the 50th harmonic. The IEEE standard
also indicates that daily 99th percentile
very short time (3 second) values should
be less than 1.5 times these values.
NEMA MG 1–2014 uses different
metrics (voltage waveform deviation
factor and harmonic voltage factor or
HVF) to establish harmonic voltage
limits and horsepower derating factors
for motors. However, the NEMA metrics
are not directly comparable to voltage
THD, and the HVF derating curve was
developed under the assumption that
any voltage unbalance or even
harmonics are negligible.53 In
51 American National Standard For Electric Power
Systems and Equipment—Voltage Ratings (60
Hertz).
52 DOE EERE, Improving Motor and Drive System
Performance—A Sourcebook for Industry (February
2014, www.energy.gov/eere/amo/motor-systems).
53 NEMA’s voltage deviation factor is calculated
as the maximum difference between corresponding
ordinates of the voltage waveform and of the
equivalent sine wave, divided by the maximum
ordinate of the equivalent sine wave when the
waves are superimposed such that the maximum
difference is minimized. Harmonic voltage factor
(HVF) is calculated by squaring the ratio of
harmonic voltage to rated voltage for each odd
harmonic not divisible by three (up to some
specified order, e.g., the 13th harmonic in IEC
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
consideration of these recommendations
regarding voltage THD limits and
potentially significant impacts on motor
performance, in this final rule, DOE is
limiting voltage THD to ≤12.0 percent
(corresponding to the IEEE 3-second
limit but measured to the 40th
harmonic) in this final rule to ensure
representative and repeatable
measurements. DOE also notes that a
limit of ≤12.0 percent voltage THD is
not unduly burdensome for test labs as
it is within the bounds of standardized
voltage THD limits placed on grid
operators and, thus, is generally
available on the national electric power
grid.
DOE also discussed source impedance
in the NOPR and considered adopting
specifications in AHRI 1210–2011
(source impedance ≤1 percent) or CSA
C838–13 (source impedance > 1.0
percent of VFD and ≤ 3.0 percent of
VFD) for motors and speed controls. 80
FR 17586, 17611–12 (April 1, 2015).
DOE understands that a nonlinear load
can distort the voltage waveform,
depending on the magnitudes of the
source impedance and current
distortion.54 However, DOE also
understands that motors are not a
significant source of harmonics in the
current waveform if the steel core is not
magnetically saturated,55 and that motor
efficiency is not greatly affected by
harmonics in the voltage waveform if
voltage THD is sufficiently limited.
Therefore, in this final rule, DOE is not
specifying source impedance
requirements. DOE believes that the
adopted requirements for the preceding
four power supply characteristics (i.e.,
voltage unbalance, voltage, frequency,
and voltage THD) will sufficiently limit
variability in motor performance
resulting from variations in the
characteristics of the mains power
supplied to the motor.
Regarding the impact of variation in
power supply characteristics on
continuous and non-continuous
60034–1:2010), dividing each result by the order of
the corresponding harmonic, and then taking the
square root of the sum of these quotients. Voltage
THD is calculated by taking the square root of the
sum of squares of each RMS harmonic voltage (up
to some specified order, e.g., the 50th harmonic in
IEEE 519–2014), and then dividing by the RMS
fundamental voltage.
54 IEEE Std 1560–2005, ‘‘IEEE Standard for
Methods of Measurement of Radio-Frequency
Power-Line Interference Filter in the Range of 100
Hz to 10 GHz’’ (February 2006).
55 Fire Protection Research Foundation,
‘‘Evaluation of the Impact on Non-Linear Power On
Wiring Requirements for Commercial Buildings’’
(June 2011, www.nfpa.org/research/fire-protectionresearch-foundation/projects-reports-andproceedings/electrical-safety/new-technologies-andelectrical-safety/evaluation-of-the-impact-on-nonlinear-power).
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
controls, DOE understands that motors,
continuous controls, and noncontinuous controls all have similar
power conditioning requirements
because they will be subjected to similar
electrical conditions in the field. That
is, based on DOE’s research,
manufacturers appear to have designed
motors to be reasonably tolerant of
variability in power supply
characteristics (or power quality) that
are characteristic of typical grid
operation, but their performance is
significantly impacted at levels outside
the bounds of that commonly
experienced in their field. While less
information is available of the response
of continuous and non-continuous
controls to these power supply
variables, DOE expects this relationship
to be true for such controls as well. For
example, NEMA guidance published in
2007 states that adjustable frequency
controls can operate on power systems
with a voltage unbalance not exceeding
3 percent.56 In addition, guidance
published by the Electric Power
Research Institute (EPRI) in 2001
indicates that VSDs should be specified
to operate without any problem for a
voltage unbalance of 2 percent.57
Consequently, DOE is applying, in this
final rule, the same power conditioning
requirements to pumps tested with
motors and pumps tested with motors
and continuous or non-continuous
controls.
DOE notes that these requirements are
applicable to pumps sold with motors
and pumps sold with motors and
continuous or non-continuous controls
rated using the testing-based method, as
such methods require measurement of
electrical input power to the motor or
control. Commensurately, these
requirements are applicable to any
pumps rated using a calculation-based
method, including bare pumps, pumps
sold with applicable electric motors,
and pumps sold with applicable electric
motors and continuous controls, when
the bare pump is tested using a
calibrated motor to determine pump
shaft input power. Pumps evaluated
based on the calculation method where
the input power to the motor is
determined using equipment other than
a calibrated motor would not have to
meet these requirements, as variations
in voltage, frequency, voltage
unbalance, and voltage THD are not
56 NEMA
Application Guide for AC Adjustable
Speed Drive Systems (December 2007, www.nema.
org/Standards/Pages/Application-Guide-for-ACAdjustable-Speed-Drive-Systems.aspx).
57 EPRI Guide to the Industrial Application of
Motors and Variable-Speed Drives (September 2001,
www.epri.com/abstracts/Pages/ProductAbstract.
aspx?ProductId=000000000001005983).
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
4115
expected to significantly affect the
tested pump’s energy performance.
Number of Stages for Multi-Stage Pumps
RSV and VTS pumps are typically
multi-stage pumps that may be offered
in a variety of stages.58 The energy
consumption characteristics of such
multi-stage pumps vary, approximately
linearly, as a function of the number of
stages. However, to simplify
certification requirements and limit
testing burden, DOE proposed in the
April 2015 pumps test procedure NOPR
that certification of RSV and VTS
pumps be based on testing with the
following number of stages:
• RSV: 3 stages; and
• VTS: 9 stages.
If a model is not available with that
specific number of stages, the model
would be tested with the next closest
number of stages distributed in
commerce by the manufacturer, or the
next higher number of stages if both the
next lower and next higher number of
stages are equivalently close to the
required number of stages. This is
consistent with DOE’s proposal,
discussed previously in section III.A.1.c,
that variation in number of stages for
RSV and VTS pumps would not be a
characteristic that constitutes different
basic models. 80 FR 17586, 17610 (April
1, 2015).
In response to DOE’s proposal
regarding testing of multi-stage RSV and
VTS pumps, HI commented that it
agrees with this proposal. (HI, No. 8 at
p. 18) DOE received no other comments
on this proposal and has, therefore,
adopted the provisions for testing multistage RSV and VTS pumps proposed in
the April 2015 pumps test procedure
NOPR with no modifications.
Twin Head Pumps
A twin head pump is a type of IL
pump that contains two impeller
assemblies, mounted in two volutes that
share a single inlet and discharge in a
common casing. In response to the April
2015 pumps test procedure NOPR, DOE
received comment from HI
recommending that DOE include twin
head pumps in this rulemaking and
align their test procedure with
Europump guidelines.59 (HI, No. 8 at p.
3) These guidelines recommend testing
a twin head pump by incorporating one
58 The stages of VTS pumps are also commonly
referred to as ‘‘bowls.’’ See section 2.1.3.1 and
Figure 2.1.3.1 of ANSI/HI 2.1–2.2–2014.
59 Guideline on the application of COMMISSION
REGULATION (EU) No 547/2012 implementing
Directive 2009/125/EC of the European Parliament
and of the Council with regard to ecodesign
requirements for water pumps (12th of September
2012)).
E:\FR\FM\25JAR2.SGM
25JAR2
4116
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
of the impeller assemblies into an
adequate IL type pump casing.
DOE agrees with HI’s
recommendation and, as discussed in
section III.A.2.a, originally intended to
include these pumps as a category of IL
pumps. To clarify DOE’s original intent
in this final rule, DOE is adopting a
definition of twin head pump,
specifying that twin head pumps are a
subset of the IL pump equipment
category, and modifying the test
procedure in this final rule to be
consistent with the EU guidelines.
DOE’s definition for twin head pump
and the modified IL definition are
presented in section III.A.2.a. However,
DOE also acknowledges that
clarifications to the test procedure
proposed in the April 2015 pumps test
procedure NOPR are necessary to
explicitly specify the procedures for
testing twin head pumps in accordance
with the DOE test procedure. As such,
DOE is establishing explicit instructions
for configuring twin head pumps in this
final rule.
In general, twin head pumps, as a
subset of IL pumps, are tested in
accordance with the test procedure for
IL pumps. Specifically, twin head
pumps, which are essentially two IL
pumps packaged together in a single
casing, are to be tested using an
equivalent single-head IL configuration.
That is, to test a twin head pump, one
of the two impeller assemblies is to be
incorporated into an adequate, IL style,
single impeller volute and casing. An
adequate, IL style, single impeller volute
and casing means a volute and casing
for which any physical and functional
characteristics that affect energy
consumption and energy efficiency are
essentially identical to their
corresponding characteristics for a
single impeller in the twin head pump
volute and casing.
d. Determination of Pump Shaft Input
Power at Specified Flow Rates
Where:
hpump,i = pump efficiency at load point i (%);
Pu,i = pump hydraulic output power at load
point i (hp);
Pi = pump shaft input power at load point i
(hp);
Piin,m = measured driver power input to the
calibrated motor at load point i (hp);
hmotor,i = the calibrated motor efficiency 60 at
load point i (%); and
i = load point corresponding to 40, 60, 75,
90, 100, 110 or 120 percent of expected
BEP flow.
measurements—specifically, pump shaft
input power, input power to the pump
at the driver, or input power to the
continuous or non-continuous
controls—must be adjusted to reflect the
power input at the specific load points
specified in the test procedure. To
adjust the measured power input values,
DOE proposed that the measured input
power and flow data corresponding to
the load point from 60 percent of
expected BEP flow to 120 percent of
expected BEP flow be linearly regressed
and the input power at the specific load
point of 75, 100, and 110 percent of BEP
flow be determined from that regression
equation. 80 FR 17586, 17610–11 (April
1, 2015).
In response to the April 2015 pumps
test procedure NOPR, HI commented
that it agrees with DOE’s proposal to use
a linear regression of the pump input
power with respect to flow rate at all the
tested load points greater than or equal
to 60 percent of expected BEP flow to
determine the pump shaft input power
at the specified load points of 75, 100,
and 110 percent of BEP flow. (HI, No.
8 at p. 18) DOE received no other
comments on the proposal and, as such,
is adopting it as proposed in the April
2015 pump test procedure NOPR with
no revisions or modifications.
Determination of Pump Shaft Input
Power for Pumps With BEP at the
Maximum Allowable Flow
60 Note: to determine pump shaft input power
based on the measured driver input power, a
calibrated motor and the calibrated motor
efficiencies at each load point i must be used where
they are known with ‘‘sufficient accuracy,’’
meaning that the efficiency of the motor combined
with the power measurement device uncertainty
must not exceed ±2.5 percent, as required by Table
40.6.3.2.3 in HI 40.6–2014.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
HI 40.6–2014 contains a method for
determining the BEP of tested pumps
based on the flow rate at which the
maximum pump efficiency occurs. DOE
recognizes that there may be some
unique pump models that do not exhibit
the typical parabolic relationship of
pump efficiency to flow rate. Instead,
for some pumps, pump efficiency will
continue to increase as a function of
flow until reaching the maximum
allowable flow that can be developed
without damaging the pump, also
referred to as ‘‘pump run-out.’’
Similarly, the expected BEP of some
pumps may be only slightly below the
maximum allowable flow. For such
pumps, it may not be possible to use the
procedure described in HI 40.6–2014 to
determine the BEP, since the pump
cannot safely operate at flows of 110
and/or 120 percent of the expected BEP
of the pump. In such cases, DOE
proposed in the April 2015 pumps test
procedure NOPR that the seven flow
points for determination of BEP should
be 40, 50, 60, 70, 80, 90, and 100
percent of the expected maximum
allowable flow rate of the pump instead
of the seven flow points described in
section 40.6.5.5.1 of HI 40.6–2014. In
addition, in such cases, DOE proposed
that the specified constant load flow
points should be 100, 90, and 65 percent
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.064
tkelley on DSK3SPTVN1PROD with RULES2
The pump efficiency at each of these
load points is then used to determine
the tested BEP for a given pump and, in
particular, the flow rate associated with
the BEP of the pump (i.e., BEP flow).
Then, based on the determined BEP
flow, the pump shaft input power or
input power to the motor is determined
at each of the specified load points, as
discussed in section III.B.
In the April 2015 pumps test
procedure NOPR, DOE observed that the
specific load points measured in the test
protocol may not be exactly at 75, 100,
or 110 percent of the BEP flow load
points specified in the test procedure
and, thus, the relevant power input
HI 40.6–2014 provides a specific
procedure for determining BEP for a
given pump based on seven load points
at 40, 60, 75, 90, 100, 110 and 120
percent of the expected BEP flow of the
pump. The test protocol in section
40.6.6.2 of HI 40.6–2014 requires that
the hydraulic power and the pump shaft
input power, or input power to the
motor for pumps tested using the
testing-based methods, be measured at
each of the seven load points. HI 40.6–
2014 further specifies that the pump
efficiency be determined as the
hydraulic power divided by the shaft
input power, or as the hydraulic power
divided by the product of the measured
input power to the motor and the
known efficiency of a calibrated motor,
depending on how the pump is tested.
The equations for calculating pump
efficiency are shown in equation (12):
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
of the BEP flow rate. 80 FR 17586,
17611 (April 1, 2015).
In response, HI commented that it
disagreed with this proposal because in
order to determine the location of the
BEP, testing must occur at rates of flow
greater than 100 percent of expected
BEP flow. (HI, No. 8, p. 18) DOE notes
that the proposal in the April 2015
pumps test procedure NOPR is specified
with respect to the expected maximum
allowable flow rate, or the expected
BEP, of the pump, not the measured
BEP flow. That is, under the NOPR
proposal, pumps with the expected BEP
occurring at the maximum allowable
flow, as defined in ANSI/HI 1.1–1.2–
2014, would be tested at the alternative
load points specified in test procedure
for pumps with BEP at run-out.
DOE acknowledges that pump
manufacturers must have some
knowledge of the expected operational
characteristics of their pump, including
the expected BEP and expected
maximum allowable flow, in order to
determine the appropriate load points
for determining BEP. However, DOE
notes that this is the case for all pumps,
not just pumps with BEP at run-out.
That is, the specific load points used to
determine BEP for all pumps are
specified with respect to the expected
operating characteristics of the pump
(i.e., BEP flow rate, as specified in
section 40.6.5.5.1 of HI 40.6–2014, or
maximum allowable flow for pumps
with BEP at run-out). DOE believes this
is necessary since the BEP and flow
characteristics of different load points
could vary widely and it is important
that the data captured during the test
procedure effectively and fully
characterize the performance of the
pump over the pump’s operating ranges.
DOE also understands that significant
design, engineering, and modeling are
involved with creating pump models for
specific applications and design
parameters and, as such, DOE finds it
unlikely that the BEP of a pump will
occur at or near a pump’s maximum
allowable flow without the pump
manufacturer having some expectation
that this will occur based on the
inherent design characteristics of the
pump. As such, DOE believes that the
proposed test procedure for pumps with
BEP at or near run-out is consistent with
the HI 40.6–2014 industry test protocols
and appropriate for determining the
performance of such pumps and no
additional changes are necessary. DOE
also notes that the maximum efficiency
point (or BEP), in the case of pumps
with BEP at the maximum allowable
flow rate will occur at the maximum
flow rate tested and will not be a
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
parabolic maxima, as is the case for
most pumps.
DOE notes that, in the April 2015
NOPR, DOE referred to pumps with BEP
at run-out as corresponding to those
with their expected BEP at the expected
maximum allowable flow. DOE
recognizes that pumps with their
maximum allowable flow occurring
between 100 and 120 percent of BEP
flow would also not be able to be tested
in accordance with the proposed test
procedure, as not all of the load points
specified in the procedure could be
measured in accordance with the test
procedure. As such, DOE is adopting, in
this final rule, the proposal described in
the April 2015 pumps test procedure
NOPR, except that DOE is clarifying that
pumps with maximum allowable flow
occurring between 100 and 120 of BEP
flow also qualify as pumps with BEP at
run-out and must apply the appropriate
test procedure. To ensure that the DOE
test procedure is consistent and
adequately captures the range of flow
rates with which the pump is expected
to operate, DOE is maintaining in this
final rule that load points for
determination of BEP are specified with
respect to the expected maximum
allowable flow of the pump, for pumps
with the expected BEP within 20
percent of the expected maximum
allowable flow. In the final rule, DOE is
also clarifying the specific load points
that must be used in determining pump
or driver input power in accordance
with the procedure described in section
III.C.2.d.
e. Measurement Equipment for TestingBased Methods
In the April 2015 pumps test
procedure NOPR, DOE noted that HI
40.6–2014 does not contain all the
necessary methods and calculations to
determine pump power consumption
for the range of equipment that will be
addressed by this final rule (i.e., pumps
inclusive of motors and continuous or
non-continuous controls). For the
purposes of determining most quantities
relevant to the determination of PEICL or
PEIVL for pumps rated using the
calculation-based methods, DOE
proposed to incorporate by reference HI
40.6–2014, appendix C, which specifies
the required instrumentation to measure
head, speed, flow rate, torque,
temperature, and electrical input power
to the motor. However, DOE noted that,
for the purposes of measuring input
power to the driver for pumps sold with
a motor and continuous or noncontinuous controls rated using the
testing-based method, the equipment
specified in section C.4.3.1, ‘‘electric
power input to the motor,’’ of HI 40.6–
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
4117
2014 may not be sufficient. Based on the
specifications in CSA C838–13 and
AHRI 1210–2011, since these test
standards are the most relevant
references for measuring input power to
such controls, DOE proposed that
electrical measurements for determining
VSD efficiency be taken using
equipment capable of measuring
current, voltage, and real power up to at
least the 40th harmonic of fundamental
supply source frequency 61 and have an
accuracy level of ±0.2 percent of full
scale when measured at the
fundamental supply source frequency.
80 FR 17586, 17611–12 (April 1, 2015).
DOE requested comment on the type
and accuracy of required measurement
equipment, especially the equipment
required for electrical power
measurements for pumps sold with
motors having continuous or noncontinuous controls. AHRI commented
that AHRI 1210–2011 specifies
appropriate power supply tolerances so
that both pump manufacturers and DOE
enforcement testing can be confident
with the establishment and verification
of ratings of VFDs sold with pumps.
(AHRI, No. 11 at pp. 1–2) AHRI also
indicated that any harmonics in the
power system can affect the measured
performance of the pump when tested
with a motor or motor and continuous
or non-continuous control. In addition,
AHRI notified DOE that VFD
manufacturers are working to expand
the scope of AHRI 1210–2011 to include
a higher horsepower upper limit and to
include additional load points.
HI commented that it disagrees with
the requirements in AHRI 1210–2011
and CSA C838–13, asserting that they
were not agreed to by the CIP Working
Group and would be excessively
burdensome. (HI, No. 8 at pp. 18–19) HI
also indicated that pump manufacturers
do not have the same equipment as
motor and drive test laboratories and
should not be expected to have the same
level of instrumentation. HI
recommended that DOE instead require
the ±2.0 percent maximum permissible
measurement device uncertainty
specified in Table 40.6.3.2.3 of HI 40.6–
2014 for driver input power.
In response to HI’s concerns regarding
the burden of such additional
instrumentation, DOE notes that, in the
April 2015 pumps test procedure NOPR
proposal, such sophisticated electric
measurement equipment was only
proposed to be required for the
61 CSA C838–13 requires measurement up to the
50th harmonic. However, DOE believes that
measurement up to the 40th harmonic is sufficient,
and the difference between the two types of
frequency measurement equipment will not be
appreciable.
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
4118
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
measurement of input power to the
continuous or non-continuous control
when rating the pump under the testingbased methods. For other pump
configurations and when testing a pump
using the calculation-based methods,
the electrical measurement equipment
specified in HI 40.6–2014 section
C.4.3.1 of appendix C would apply. DOE
also notes that several interested parties,
including HI, previously commented
that such measurement equipment was
necessary due to the potential impact of
the continuous control on line
harmonics and other equipment on the
circuit. (Docket No. EERE–2011–BT–
STD–0031, CA IOUs, Framework public
meeting transcript No. 19 at p. 236;
Docket No. EERE–2011–BT–STD–0031,
HI, No. 25 at p. 35) HI also previously
noted that this additional
instrumentation is manageable and
within the capabilities of what most of
the HI members are doing today.
(Docket No. EERE–2011–BT–STD–0031;
HI, public meeting transcript, No. 19 at
p. 235)
In addition, given the power
conditioning requirements adopted in
section III.C.2.c, DOE believes that the
more sophisticated electrical
measurement equipment capable of
measuring true root mean square (RMS)
voltage, true RMS current, and real
power for distorted waveforms is
required to ensure that the incoming
power is within the specifications for
those pump configurations where it is
required and that the power
measurement is accurate. Specifically,
DOE is requiring, as discussed at length
in section III.C.2.c, certain voltage,
frequency, voltage unbalance, and
voltage THD levels be maintained when
testing: (1) Bare pumps using a
calibrated motor, (2) pumps sold with
motors using the testing-based methods,
and (3) pumps sold with motors and
continuous or non-continuous controls
using the testing-based method. In order
to verify that these requirements are
met, measurement equipment must be
capable of accurately measuring real
power, true RMS voltage, frequency,
voltage unbalance, and voltage THD.
DOE notes that, in section C.4.3, HI 40.6
specifies that driver input power to the
motor should be calculated as the
product of (1) line volts, (2) line amps,
and (3) power factor. As HI 40.6–2014
specifies the measurement of power
factor, DOE believes that the electric
equipment capable of measuring at least
real power, true RMS voltage, and true
RMS current is already required by HI
40.6–2014, as such measurements are
necessary for determining power factor.
Some watt meters and watt-hour
meters would not be sufficient for
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
accurate measurement of real power for
distorted voltage waveforms or distorted
current waveforms; this is because such
instruments incorrectly assume that the
waveforms are perfectly sinusoidal (i.e.,
free of the harmonics that are
introduced by non-linear loads).62 DOE
is therefore requiring the use of
instruments that accurately measure
true RMS current, true RMS voltage, and
real power for distorted waveforms with
harmonic frequencies ranging from the
fundamental frequency (60 Hz) up to
and including the 40th harmonic (2400
Hz).
However, with respect to the required
accuracy of any electrical measurement
equipment, DOE acknowledges the
concern from HI regarding the
additional burden associated with
acquiring instrumentation consistent
with the specifications provided in the
NOPR. As such, DOE reviewed available
and applicable test methods for motors
and controls, including AHRI 1210–
2011 and CSA C838–13. DOE notes that
AHRI 1210–2011 in turn references IEC
61000–4–7, ‘‘Testing and measurement
techniques—General guide on
harmonics and interharmonics
measurements and instrumentation, for
power supply systems and equipment
connected thereto,’’ regarding the
necessary characteristics for electric
measurement equipment. IEC 61000–4–
7 provides requirements for Class I
instruments and recommends their use
where precise measurements are
necessary, such as for verifying
compliance with standards. The
maximum error on power for IEC Class
I instruments is ±1 percent of measured
value for readings greater than or equal
to 150 W (0.2 hp). However, IEC 61000–
4–7 states that the error limits refer to
single-frequency (i.e., sinusoidal)
steady-state waveforms, in the operating
frequency range, applied to the
instrument under rated operating
conditions to be indicated by the
manufacturer.
The requirements in IEC 61000–4–7
generally align with those in section
5.7.3 of CSA C390–10, which specifies
that motor input power measurements
shall have a maximum uncertainty of
±1.0 percent of the reading (including
all errors from the power meter, current
transformers, and potential/voltage
transformers). However, CSA also states
that the specified uncertainties shall
apply only at the rated full load (i.e.,
near rated power factor) of the motor
62 PG&E, ‘‘Voltage and Current Measurement of
Non-Sinusoidal AC Power’’ (October 2004, https://
www.pge.com/includes/docs/pdfs/mybusiness/
customerservice/energystatus/powerquality/
nonsinusoidal_power.pdf, accessed September 8,
2015).
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
under test. While both IEC 61000–4–7
and CSA C390–10 recommend
instrument tolerances of ±1.0 percent,
DOE notes that their application of that
tolerance is not the same as the
tolerance DOE is adopting in this final
rule, which applies to the measured
power at each test point and with the
power supply characteristics
experienced during the test.
DOE recognizes that the accuracy of
input power measurements can be
compromised to some extent when
voltage and/or current waveforms are
displaced and/or distorted. In addition,
DOE recognizes that motors will not
always be fully loaded during pump
testing, that motors may be operated
somewhat above nameplate voltage (as
allowed in this final rule), and that
some distortion of the voltage waveform
is permitted in this final rule. Therefore,
DOE believes it is appropriate to allow
electrical equipment accuracy of ±2.0
percent of measured value, consistent
with the tolerance specified in section
40.6.3.2.3 of HI 40.6–2014 and HI’s
request. DOE is adopting such a
requirement in this final rule.
DOE also recognizes that current and
voltage instrument transformers can be
used in conjunction with electrical
measurement equipment to measure
current and voltage. Usage of instrument
transformers can introduce additional
losses and errors to the measurement
system. DOE is clarifying in this final
rule that the combined accuracy of all
instruments used to measure a
parameter must meet the prescribed
accuracy requirements for electrical
measurement equipment. Section C.4.1
of AHRI 1210–2011 indicates that
combined accuracy should be calculated
by multiplying the accuracies of
individual instruments. In contrast,
section 5.7.2 of CSA C838–2013
indicates that if all components of the
power measuring system cannot be
calibrated together as a system, the total
error shall be calculated from the square
root of the sum of the squares of all the
errors. DOE understands that it is more
accurate to combine independent
accuracies (i.e., uncertainties or errors)
by summing them in quadrature.63 DOE
is therefore using the root sum of
squares to calculate the combined
accuracy of multiple instruments used
in a single measurement, consistent
with conventional error propagation
methods.
Therefore, in this final rule, DOE is
specifying the characteristics of the
63 National Institute of Standards and Technology
(NIST) Guidelines for Evaluating and Expressing
the Uncertainty of NIST Measurement Results
(https://physics.nist.gov/Pubs/guidelines/sec5.html,
accessed September 8, 2015).
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
electrical measurement equipment that
must be used when measuring input
power to the motor, continuous
controls, or non-continuous controls.
Specifically, the electrical measurement
equipment in such cases must be
capable of measuring true RMS current,
true RMS voltage, and real power up to
at least the 40th harmonic of
fundamental supply source frequency
and have an accuracy level of ±2.0
percent of the measured value when
measured at the fundamental supply
source frequency. DOE notes that
standard electrical measurement
equipment meeting the requirements of
HI 40.6–2014 section C.4.3.1 may still
be used when testing any pumps under
the calculation-based methods (i.e., bare
pumps, pump sold with motors, and
4119
pumps sold with motors and continuous
or non-continuous controls), provided a
calibrated motor is not used to
determine the pump shaft input power.
The electrical measurement equipment
requirements being adopted in this
pumps test procedure final rule are
summarized in Table III.5.
TABLE III.5—ELECTRICAL MEASUREMENT REQUIREMENTS FOR DIFFERENT CONFIGURATIONS OF PUMPS FOR THE
CALCULATION BASED AND TESTING BASED APPROACHES
Electrical measurement requirements
Pump
configuration
Bare Pump ...........................
Pump + Motor or Pump +
Motor + Continuous or
Non-Continuous Controls.
HI 40.6–2014, section C.4.3.1, unless testing with a
calibrated motor.
HI 40.6–2014, section C.4.3.1, unless testing with a
calibrated motor.
While DOE acknowledges that these
requirements may represent a burden
for some manufacturers and test labs
who do not already have such
equipment, DOE has minimized the
additional burden associated with this
requirement, to the extent possible, by
only requiring more sophisticated
power measurement equipment in those
cases where it is necessary to verify that
the test procedure power conditioning
requirements are being met. DOE also
notes that, for many pumps, the testingbased approaches are optional and a
manufacturer could elect to determine
the PEI using the calculation-based
approach and avoid having to purchase
and use the more accurate and
expensive electrical measurement
equipment necessary for conducting
testing under the testing-based
approach. The burden associated with
this test procedure, and in particular the
required test equipment, is discussed
further in section IV.B.
tkelley on DSK3SPTVN1PROD with RULES2
f. Calculations and Rounding
DOE notes HI 40.6–2014 does not
specify how to round values for
calculation and reporting purposes.
DOE recognizes that the manner in
which values are rounded can affect the
resulting PER or PEI, and all PER or PEI
values should be reported with the same
number of significant digits. In the April
2015 pumps test procedure NOPR, DOE
proposed to require that all calculations
be performed with the raw measured
data, to ensure accuracy, and that the
VerDate Sep<11>2014
13:56 Jan 22, 2016
Testing-based test method
or
Calculation-based test method
with a calibrated motor
Calculation-based test method
without a calibrated motor
Jkt 238001
Not Applicable.
Equipment capable of measuring true RMS current,
true RMS voltage, and real power up to at least the
40th harmonic of fundamental supply source frequency and have an accuracy level of ±2.0 percent
of the measured value when measured at the fundamental supply source frequency.
PERCL and PEICL or PERVL and PEIVL be
reported to the nearest 0.01. 80 FR
17586, 17612 (April 1, 2015).
DOE requested comment on its
proposal to conduct all calculations
using raw measured values and that the
PERCL and PEICL or PERVL and PEIVL, as
applicable, be reported to the nearest
0.01. In response, HI commented that it
understands and agrees that the
requirement is to normalize raw data to
nominal speed, and the PERCL, PEICL,
PERVL and PEIVL would be reported to
the nearest 0.01. (HI, No. 8 at p. 19) In
the April 2015 NOPR public meeting, a
representative of HI (Paul Ruzicka)
suggested that DOE clarify that
calculations be performed with ‘‘raw
normalized data,’’ since all data are to
be corrected to nominal speed. (HI,
NOPR public meeting transcript, No. 7
at pp. 165–66)
DOE appreciates HI’s confirmation of
the proposed approach. In response to
HI’s suggestion that DOE clarify that all
calculations are to be performed with
‘‘raw normalized data,’’ DOE notes that
the normalization to nominal speed is
also a calculation and that such
calculation is also to be performed with
raw measured data. Also, some
collected data do not need to be
normalized to nominal speed. As such,
DOE finds it clearer to continue to
specify that all calculations be
performed with raw measured data,
including the normalization to nominal
speed.
PO 00000
Frm 00035
Fmt 4701
Sfmt 4700
In addition, in preparing the final rule
test procedure provisions, DOE
reviewed the calculations, uncertainty,
and significance of measured values
used to determine the PERCL and PEICL
or PERVL and PEIVL, as applicable.
Based on this analysis, DOE determined
that while PEICL and PEIVL are to be
reported to 0.01, the precision of the
measurement equipment specified in
the NOPR is not sufficient to determine
PERCL and PERVL to 0.01, especially for
large pumps. As such, in this final rule,
DOE is continuing to specify that all
calculations be performed with the raw
measured data, to ensure accuracy, and
that the PEICL and PEIVL be reported to
the nearest 0.01. However, DOE is
specifying, in this final rule, that PERCL
and PERVL need only be specified to
three significant digits, which is
equivalent to or better than the level of
significance specified for PEICL and
PEIVL. DOE also agrees with HI that all
data should be corrected to nominal
speed prior to performing subsequent
calculations, as described in section
III.C.2.c.
D. Determination of Motor Efficiency
The PEICL and PEIVL metrics both
describe the performance of a pump and
an accompanying motor, including
continuous or non-continuous controls,
if applicable. As such, the performance
of the applicable motor must be
determined to calculate the PEICL or
PEIVL of a given pump model.
E:\FR\FM\25JAR2.SGM
25JAR2
4120
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
In the April 2015 pumps test
procedure NOPR, DOE proposed that
the motor efficiency would be
determined based on the configuration
in which the pump was sold. For
determining the default motor efficiency
of a minimally compliant pump
(PERSTD) and for determining the default
motor efficiency used to calculate PERCL
for bare pumps, DOE proposed to
specify the nominal full load motor
efficiency that corresponds to the
applicable Federal minimum standard.
For determining PERCL or PERVL for
pumps sold with motors or with motors
and continuous or non-continuous
controls, DOE proposed to use either (1)
the physically tested performance of the
motor paired with that pump when
using testing-based methods, or (2) the
represented nominal full load motor
efficiency (i.e., the nameplate and
certified rating) of the motor (other than
submersible) distributed in commerce
with that pump model when using the
calculation-based test method. 80 FR
17586, 17612–13 (April 1, 2015). The
specific procedures for determining the
applicable Federal minimum and
represented nominal full load motor
efficiency values are described in
section III.D.1 and III.D.2, respectively.
Based on DOE’s proposed test
procedure, the applicable Federal
minimum or the represented nominal
full load motor efficiency would then be
used to determine the full load losses,
in horsepower, associated with that
motor. The full load losses would then
be adjusted using an algorithm to reflect
the motor performance at partial loads,
corresponding to the load points
specified in the DOE test. These losses
would then be combined with the
measured pump shaft input power at
each load point to determine the PERCL
or PERVL for that pump, as described in
section III.B. Id. Section III.E.1 describes
how the Federal minimum or
represented nominal full load motor
efficiency is used in the calculationbased method when calculating overall
pump power consumption.
1. Default Nominal Full Load Motor
Efficiency
For determining the default motor
efficiency of a minimally compliant
pump (PERSTD) and for determining the
default motor efficiency used to
calculate PERCL for bare pumps, DOE
proposed to specify the nominal full
load motor efficiency that corresponds
to the applicable Federal minimum
standard. In the April 2015 pumps test
procedure NOPR, DOE proposed that
the ‘‘default’’ nominal full load motor
efficiency values be based on the
minimum nominal full load motor
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
efficiency standards for polyphase,
NEMA Design B motors from 1 to 500
hp, defined in 10 CFR part 431, subpart
B for medium and large electric motors,
except for submersible motors.
Specifically, at the time of the proposal,
the values in Table 5 of 10 CFR
431.25(h) defined the nominal full load
motor efficiency standards, by number
of poles and horsepower for the
applicable motors. 80 FR 17586, 17612–
13 (April 1, 2015). DOE is using the
term ‘‘default nominal full load
efficiency’’ throughout this document to
refer to the default values used in this
test procedure for determining PERSTD
and for bare pumps, PERCL
corresponding to the applicable Federal
minimum energy conservation
standards. See section III.D.1.a for a
discussion regarding electric motors
covered by DOE’s energy conservation
standards at 10 CFR 431.25 and section
III.D.1.b for a discussion regarding
submersible motors.
a. Covered Electric Motors
For the determination of PERSTD for
all pumps (except ST pumps) and
PERCL for bare pumps (see section
III.E.1.a), default nominal full load
motor efficiency values are required. As
mentioned previously, DOE believes the
nominal full load motor efficiency
standards specified for NEMA Design B
motors are appropriate for the pumps
(except ST pumps) to which this test
procedure is applicable. In the April
2015 pumps test procedure NOPR, DOE
also proposed to specify the selection of
the default motor characteristics used
for calculating PERCL and PERSTD based
on the configuration in which the pump
is being sold. Specifically, for bare
pumps, DOE proposed that the default
nominal full load motor efficiency for
determining PERCL and PERSTD would
be based on the following criteria:
• The number of poles selected for
the default motor would be equivalent
to the nominal speed of the rated pump
(i.e., 2 poles correspond to 3,600 rpm
and 4 poles correspond to 1,800 rpm);
• the motor horsepower selected for a
given pump would be required to be
either equivalent to, or the next highest
horsepower-rated level greater than, the
measured pump shaft input power at
120 percent of BEP flow, as determined
based on an extrapolation of the linear
regression of pump input power
(discussed in section III.C.2.d); and
• the lower standard (i.e., less
stringent) of either the open or enclosed
construction at the appropriate motor
horsepower and number of poles. 80 FR
17586, 17612–13 (April 1, 2015).
As mentioned previously, the
appropriate table at 10 CFR 431.25 is the
PO 00000
Frm 00036
Fmt 4701
Sfmt 4700
table of nominal full load motor
efficiency standards that is currently
required for compliance of NEMA
Design B polyphase motors.
For pumps sold either with motors or
with motors and continuous or noncontinuous controls, selection of a
default nominal full load motor
efficiency for calculation of PERSTD is
also required. This default nominal full
load motor efficiency is also based on
the applicable Federal minimum
standards. In this case, DOE proposed
that the motor horsepower and number
of poles selected for determining the
default nominal full load motor
efficiency for use in the calculation of
PERSTD should be equivalent to the
horsepower and poles of the motor with
which the pump model is distributed in
commerce. Similar to the case for bare
pumps, DOE also proposed that the
default nominal full load motor
efficiency corresponding to the
minimally compliant motor in PERSTD
would still be the minimum of the open
and enclosed standards for the
appropriate motor horsepower and
number of poles. That is, regardless of
the motor construction (i.e., open or
enclosed) of the motor with which the
pump is being rated, the minimum
nominal full load motor efficiency
standard listed in the applicable table
for polyphase NEMA Design B motors at
10 CFR 431.25 for the given motor
horsepower and number of poles would
be used. Id.
DOE requested comment on its
proposal to determine the default motor
horsepower for rating bare pumps based
on the pump shaft input power at 120
percent of BEP flow and, in response, HI
commented that it agrees with this
proposal. (HI, No. 8 at p. 19) DOE also
requested comment on its proposal to
specify the default nominal full load
motor efficiency based on the applicable
minimally allowed nominal full load
motor efficiency specified in DOE’s
energy conservation standards for
NEMA Design B motors at 10 CFR
431.25 for all pumps except pumps sold
with submersible motors. HI
commented that each NEMA MG 1
nominal efficiency value is the average
efficiency of a large population of
motors of the same design, so for any
given nominal efficiency value, half of
the corresponding population would be
lower. (HI, No. 8 at p. 19) HI indicated
that the NEMA MG 1 minimum
efficiency values should be used instead
so that the test method for determining
PEICL and PEIVL are not disadvantaged.
Wilo similarly commented that the use
of NEMA nominal efficiencies would
cause 50 percent of borderline pumps to
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
fail. (Wilo, Docket No. EERE–2011–BT–
STD–0031, No. 44 at p. 2)
DOE acknowledges the comments
from HI and Wilo regarding the use of
nominal full load motor efficiency
values from 10 CFR 431.25. DOE notes
that these values represent the
minimum Federal efficiency standard
for applicable covered motors and, as
such, believes that referencing an
alternative, lower efficiency value
would be inappropriate and
inconsistent with DOE’s regulatory
framework. However, in response to the
specific concern voiced regarding a
potential disadvantage when using the
testing-based method, DOE will follow
the method the manufacturer used to
determine the representative value
when conducting enforcement testing.
In other words, if a pump manufacturer
has used the calculation-based rating
method to determine the representative
value for a pump basic model, then DOE
would also use the calculation-based
approach, which relies on the nominal
full load motor efficiency values from
the table and not the actual motor tested
performance. Conversely, if a
manufacturer elected to use the testingbased approach, DOE would also assess
compliance using the testing-based
approach which would account for the
actual tested efficiency of the motor
incorporated into the pump. Thus, a
manufacturer need not be concerned
that the actual efficiency of an
individual motor would have a
disparate effect on the measured
efficiency during assessment or
enforcement testing.
In this final rule, DOE is adopting the
default nominal full load motor
efficiency values for bare pumps and the
method for determining PERSTD
proposed in the April 2015 pumps test
procedure NOPR. That is, the default
nominal full load motor efficiency for
bare pumps and for determining PERSTD
for all pumps (besides VTS pumps) is
determined by referencing the
applicable energy conservation
standards found at 10 CFR 431.25 for
NEMA Design B motors that are
required at the time the pump model is
being certified. At the time of
publication of this document, the
appropriate motor Federal energy
conservation standards for NEMA
Design B polyphase motors can be
found at 10 CFR 431.25(h).
DOE notes that, if DOE were to amend
the energy conservation standards for
NEMA Design B polyphase motors, the
represented values for pump PEI would
no longer remain valid, and
manufacturers would need to revise
their represented values to reflect the
amended nominal full load motor
efficiency standards and recertify at the
first annual certification date after the
compliance date for the amended motor
Federal energy conservation standards.
As a result of the methodology being
adopted today, which will result in
changes to represented values for
pumps when the Federal energy
conservation standards for NEMA
Design B polyphase motors changes,
DOE does not believe that any actual
design or manufacturing changes will be
required from the pump manufacturer
since the bare pump will remain the
same and is unaffected by the motor
standard. Instead, DOE is ensuring that
pump ratings still reflect differential
representations depending on the
efficiency of the motor that is being sold
with the pump. DOE understands that
certain motors that were minimally
compliant with the previous motor
standard may no longer be able to be
sold once manufacturers are required to
comply with amended standards for
motors (if adopted) and thus, DOE
believes a methodology which reflects
this reality is best. Because the PEI is an
indexed value that is meant to compare
the performance of the pump being
tested to that of a theoretical
‘‘minimally-compliant’’ pump, the
default nominal full load motor
efficiency for that ‘‘minimallycompliant pump’’ must reflect any
changes in the motor standard and
available products in the market. If DOE
did not adopt a methodology that
acknowledges potential changes to the
energy conservation standards for
NEMA Design B motors, then pump
represented values could be artificially
inflated when compliance with
amended energy conservation standards
4121
for motors is required and could result
in a situation where a compliant pump
could be less efficient due to the credit
being given from the amended energy
conservation standards for motors.
For these reasons, DOE is specifying
in the pumps test procedure adopted in
this final rule that when determining
PERSTD for all pumps (except VTS
pumps) and PERCL for bare pumps, the
default nominal full load motor
efficiency value that is used must be the
energy conservation standard for NEMA
Design B polyphase motors that is
required at the time the pump model is
being certified and must be updated
with an annual certification. As this
amended default nominal full load
motor efficiency will occur in both the
numerator and the denominator of the
PEI metric, such a test procedure
provision will not lead to changes in the
relative ratings of bare pump models
using the calculation-based approach.
b. Submersible Motors
DOE notes that submersible motors
are not currently subject to the DOE
energy conservation standards for
electric motors specified at 10 CFR
431.25. Therefore, for the purposes of
calculating PEICL for bare VTS pumps or
PERSTD for any pumps sold with
submersible motors, DOE requires a
default assumption regarding full load
efficiency for submersible motors. In the
April 2015 pumps test procedure NOPR,
DOE constructed a table of motor full
load efficiencies by motor horsepower,
similar to the table of energy
conservation standards for electric
motors at 10 CFR 431.25(h), as shown in
Table III.6. 80 FR 17586, 17614–15
(April 1, 2015).
As it was not DOE’s intent to impact
the rated efficiency of submersible
motors through this rulemaking, DOE
deflated the minimum submersible
motor efficiency that DOE observed by
using the maximum number of ‘‘bands’’
across a horsepower range to ensure that
the value represented a worst-case
value. Where no data were available,
DOE applied the same number of NEMA
bands across the range of motor
horsepower and numbers of poles.
tkelley on DSK3SPTVN1PROD with RULES2
TABLE III.6—TWO-POLE MOTOR SUBMERSIBLE MOTOR FULL LOAD EFFICIENCY BY MOTOR HORSEPOWER RELATIVE TO
THE FULL LOAD EFFICIENCY IN IN TABLE 5 OF 10 CFR 431.25(h)
Minimum
observed full load
efficiency
(2-poles)
(%)
Motor horsepower
(hp)
1 .................................................................................................................................
1.5 ..............................................................................................................................
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00037
Fmt 4701
Sfmt 4700
Observed number
of ‘‘bands’’ below
the full load
efficiency in Table
5 of 10 CFR
431.25(h)
Default number
of ‘‘bands’’ below
the full load
efficiency in Table
5 of 10 CFR
431.25(h)
67
67
6
11
11
..............................
E:\FR\FM\25JAR2.SGM
25JAR2
4122
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
TABLE III.6—TWO-POLE MOTOR SUBMERSIBLE MOTOR FULL LOAD EFFICIENCY BY MOTOR HORSEPOWER RELATIVE TO
THE FULL LOAD EFFICIENCY IN IN TABLE 5 OF 10 CFR 431.25(h)—Continued
Minimum
observed full load
efficiency
(2-poles)
(%)
Default number
of ‘‘bands’’ below
the full load
efficiency in Table
5 of 10 CFR
431.25(h)
73
75
76
77
75
72.2
76.4
79
79.9
83
83
84
83.8
87
86
86
88
87
87
Motor horsepower
(hp)
Observed number
of ‘‘bands’’ below
the full load
efficiency in Table
5 of 10 CFR
431.25(h)
9
9
10
10
13
15
13
12
12
10
11
11
12
10
13
13
12
14
14
..............................
..............................
..............................
15
..............................
..............................
..............................
..............................
12
..............................
..............................
..............................
..............................
14
..............................
..............................
..............................
..............................
..............................
2 .................................................................................................................................
3 .................................................................................................................................
5 .................................................................................................................................
7.5 ..............................................................................................................................
10 ...............................................................................................................................
15 ...............................................................................................................................
20 ...............................................................................................................................
25 ...............................................................................................................................
30 ...............................................................................................................................
40 ...............................................................................................................................
50 ...............................................................................................................................
60 ...............................................................................................................................
75 ...............................................................................................................................
100 .............................................................................................................................
125 .............................................................................................................................
150 .............................................................................................................................
175 .............................................................................................................................
200 .............................................................................................................................
250 .............................................................................................................................
Id.
In response to the April 2015 pumps
test procedure NOPR proposal, HI
commented in the public meeting that
several of the minimum motor
efficiency values are higher than what is
being published. (HI, NOPR public
meeting transcript, No. 7 at pp. 159–60).
In written comments, HI provided
corrected efficiencies for several values.
(HI, No. 8 at pp. 19–20)
DOE thanks HI for submitting data to
assist in constructing a submersible
motor efficiency table that is
representative of minimally efficient
submersible motors. DOE has revised its
proposed submersible efficiency values
to accommodate the lower values
provided by HI, as shown in Table III.7.
TABLE III.7—REVISED SUBMERSIBLE MOTOR FULL LOAD EFFICIENCY BY MOTOR HORSEPOWER
Motor horsepower
(hp)
Minimum observed full load
efficiency
(%)
2 poles
tkelley on DSK3SPTVN1PROD with RULES2
1 ........................................
1.5 .....................................
2 ........................................
3 ........................................
5 ........................................
7.5 .....................................
10 ......................................
15 ......................................
20 ......................................
25 ......................................
30 ......................................
40 ......................................
50 ......................................
60 ......................................
75 ......................................
100 ....................................
125 ....................................
150 ....................................
200 ....................................
250 ....................................
67
67
73
75
76
77
75
72.2
76.4
79
79.9
83
83
82.4
83.8
87
86
86
87
87
4 poles
13:56 Jan 22, 2016
2 poles
........................
........................
........................
........................
........................
........................
........................
........................
........................
........................
81.8
........................
85.1
85.4
86.2
........................
........................
86.1
........................
........................
During the April 2015 NOPR public
meeting, Nidec Corporation (Nidec)
expressed that the levels of submersible
motors should be consistent with the
requirements for vertical motors. Nidec
also stated that there be two sets of
default efficiency values: one for a dry
VerDate Sep<11>2014
Observed number of ‘‘bands’’
below the full load efficiency in
Table 5 of 10 CFR 431.25(h)
Jkt 238001
Binned number of ‘‘bands’’
below the full load efficiency for
NEMA design B motors in
CFR 431.25
4 poles
6
11
9
9
10
10
13
15
13
12
12
10
11
13
12
10
13
13
13
14
2 poles
4 poles
........................
........................
........................
........................
........................
........................
........................
........................
........................
........................
13
........................
13
14
14
........................
........................
........................
15
........................
11
........................
........................
........................
........................
15
........................
........................
........................
........................
13
........................
........................
........................
........................
14
........................
........................
........................
........................
11
........................
........................
........................
........................
15
........................
........................
........................
........................
14
........................
........................
........................
........................
15
........................
........................
........................
........................
rotor and one for a wet rotor. (Nidec,
NOPR public meeting transcript, No. 7
at pp. 160–61) Nidec added that the
type with air could use Table 12–12
from NEMA MG 1. (Nidec, NOPR public
meeting transcript, No. 7 at p. 163)
PO 00000
Frm 00038
Fmt 4701
Sfmt 4700
Resulting default nominal full
load submersible motor
efficiency
2 poles
55
66
68
70
74
68
70
72
72
74
77
78.5
80
81.5
81.5
81.5
84
84
85.5
86.5
4 poles
68
70
70
75.5
75.5
74
74
75.5
77
78.5
80
81.5
82.5
84
85.5
84
84
85.5
86.5
86.5
In response to Nidec’s comment, DOE
notes that all equipment categories that
are subject to the test procedure,
including VTS pumps that are most
commonly paired with submersible
motors, are defined as dry rotor pumps.
As such, wet rotor submersible motors
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
and wet rotor submersible pumps are
not subject to the test procedure, and a
table of minimum efficiency values for
them is not necessary. DOE notes that,
in response to Nidec’s comment
regarding ‘‘the type [of motor] with air,’’
DOE believes Nidec is referring to nonhermitically sealed units (i.e., nonsubmersible motors) and confirming
that Table 12–12 in NEMA MG–1
(which is consistent with DOE’s
minimum efficiency standards for
electric motors at 10 CFR 431.25) is
appropriate for such non-submersible
motors. While DOE’s application of the
minimum efficiency standards for
electric motors in this final rule is
limited to NEMA Design B motors, DOE
notes that NEMA’s comment is
consistent with the approach being
taken in this final rule.
HI stated that DOE needs to
emphasize that single-phase motors are
not part of the minimum efficiency
tables. (HI, No. 8 at pp. 19–21) DOE
notes that in this test procedure, as
described in section III.A.6, all pumps
sold with single-phase motors,
including single-phase submersible
motors, may be rated as bare pumps in
order to not be penalized for the
inherently lower efficiencies of singlephase equipment. In the bare pump
approach, the default submersible motor
efficiency values presented in Table III.7
are used in calculating both the
numerator (PERCL or PERVL) and
denominator (PERSTD) of PEI; the lower
efficiency of a single-phase motor is not
taken into account. DOE notes that, as
described in section III.A.6, pumps sold
with single-phase submersible motors
may also apply the testing-based
approach, if desired by the
manufacturer. However, in such a case,
the default motor efficiency used to
determine PERSTD would continue to be
the default nominal submersible motor
efficiency presented in Table III.7.
In regard to selection of default motor
size for submersible motors, in the April
2015 pumps test procedure NOPR, DOE
proposed to apply the same sizing
method proposed for other categories of
pumps, described in section III.D.1 of
this NOPR. At the April 2015 NOPR
public meeting, HI stated that
submersible motors are sold utilizing
full NEMA motor service factors and
recommended amending the
submersible motor sizing to account for
this sizing approach. (HI, NOPR public
meeting transcript, No. 7 at p. 150) In
its written comments, HI noted that
DOE needs to emphasize that
submersible pumps are typically loaded
to the fully utilized service factor of the
motor. (HI, No. 8 at pp. 19–20)
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
In response to HI’s suggestion, DOE
has reviewed the typical service factors
of submersible motors offered for sale
with pumps within the scope of this test
procedure. DOE determined that the
majority of submersible motors
exhibited service factors of 1.15. DOE
notes that this value is also consistent
with the service factor prescribed in
table 12–4 of NEMA MG–1 2009 for
Design A, B, and C polyphase, squirrel
cage, general-purpose, alternatingcurrent motors of the open type with a
motor horsepower greater than 1 hp. In
light of this, DOE is revising its
requirements for the default motor
sizing of submersible motors in this
final rule to reflect the service factors
observed in the industry. That is, DOE
is specifying that, for VTS bare pumps,
the default submersible motor
horsepower be determined as the motor
horsepower that is equal to or the next
highest motor horsepower greater than
the pump shaft input power (in
horsepower) at 120 percent of BEP flow
divided by the service factor, or 1.15.
DOE notes that some motors less than 3
horsepower may have a higher service
factor, but by using the same value for
all pumps, DOE is simplifying the
procedure and does not expect this
simplification to significantly impact
the PEI for VTS bare pumps. This is
because the same service factor (1.15) is
used for the given pump’s PERCL and for
PERSTD, so the two efficiency values
essentially cancel out and do not
significantly impact the rating.
DOE reiterates that this default service
factor is only necessary for determining
the default motor efficiency for
submersible motors. For pumps sold
with submersible motors and pumps
sold with submersible motors and
continuous or non-continuous controls,
the actual submersible motor size with
which the pump is distributed in
commerce is used when determining
motor efficiency for use in calculating
PERCL, PERVL, and PERSTD.
In summary, in this final rule, DOE
will allow the use of default nominal
full load submersible motor efficiency
values presented in Table III.7 to rate (1)
VTS bare pumps, (2) pumps sold with
submersible motors, and (3) pumps sold
with submersible motors and
continuous or non-continuous controls
as an option instead of using the testingbased approach. DOE believes that
allowing the calculation-based method
to be used for pumps sold with
submersible motors may also reduce the
testing burden for some manufacturers.
However, if manufacturers wish to
account for the use of submersible
motors with a higher efficiency than the
default nominal full load submersible
PO 00000
Frm 00039
Fmt 4701
Sfmt 4700
4123
motor efficiency, they may choose to
rate the pump model using the testingbased, wire-to-water method described
in section III.E.2.
2. Represented Nominal Full Load
Motor Efficiency for Pumps Sold With
Motors
For pumps sold with motors or
motors and continuous or noncontinuous controls that are rated using
the calculation-based approach, DOE
proposed in the April 2015 pumps test
procedure NOPR that the nominal full
load motor efficiency used in
determining the PERCL or PERVL will be
the value that is certified to DOE as the
nominal full load motor efficiency in
accordance with the standards and test
procedures for electric motors at 10 CFR
431, subpart B. 80 FR 17586, 17613–14
(April 1, 2015). As noted in the April
2015 pumps test procedure NOPR and
described in greater detail in section
III.E.1.b and III.E.2, this verifiable and
standardized represented nominal full
load motor efficiency is only available
for motors that are subject to DOE’s test
procedure for electric motors and, as
such, DOE proposed in the April 2015
pump test procedure NOPR, that only
pumps sold with motors subject to
DOE’s electric motor test procedure and
energy conservation standards would be
able to conduct the proposed
calculation-based approach. Id. at
17618, 17626–28. DOE notes that these
represented nominal full load efficiency
values correspond to the certified value
submitted on the motor manufacturer’s
certification report and on the
nameplate of the motor itself. Therefore,
if the motor manufacturer elects to
certify conservatively at the Federal
energy conservation standard level, this
is the value the pump manufacturer
must use in its calculations for pumps
sold with motors subject to DOE’s
Federal energy conservation standards.
For pumps sold with submersible
motors and rated using the calculationbased approach, DOE also proposed that
the nominal full load motor efficiency
values would be the same as the default
nominal full load submersible motor
efficiency values used to determine the
PERCL for bare pumps and PERSTD. Id.
at 17614. These values are
representative of minimally efficient
submersible motors and are discussed
further in section III.D.1.b. As noted
previously, if manufacturers wish to
represent the efficiency of pumps sold
with submersible motors that are more
efficient than the assumed value, then
they may perform the testing-based
method described in section III.E.2.b in
section.
E:\FR\FM\25JAR2.SGM
25JAR2
4124
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
DOE received no comments on these
proposals and is adopting the provisions
for specifying the represented nominal
full load motor efficiency for motors
subject to DOE’s electric motor test
procedure and the default nominal full
load submersible motor efficiency for
submersible motors, as proposed. DOE
notes that, for pumps sold with motors
not addressed by DOE’s electric motor
test procedure (except submersible
motors), the calculation-based methods
described in section III.E.1.b would not
apply, and no assumption regarding
nominal efficiency of the motor paired
Where:
yi = the part load loss factor at load point i,
Pi = the shaft input power to the bare pump
at load point i (hp),
MotorHP = the motor horsepower (hp), and
i = load point corresponding to 75, 100, or
110 percent of BEP flow for uncontrolled
pumps or 25, 50, 75, or 100 percent of
BEP flow for pumps sold with a motor
Where:
Lfull64 = motor losses at full load (hp),
MotorHP = the motor horsepower (hp), and
hmotor,full = the default or rated nominal full
load motor efficiency as determined in
3. Determining Part Load Motor Losses
As described in section III.B.2, default
nominal full load motor efficiency is
converted to motor losses, in
horsepower, at each load point to
determine the input power to the motor
and continuous or non-continuous
controls.
Id.
In the proposal, the full load losses of
the motor would be determined based
on the full load motor efficiency, which
would be the default nominal full load
motor efficiency described in section
accordance with section III.D.1 or III.D.2,
respectively (%).
Id.
Finally, DOE proposed that the part
load losses at each specified load point
when determining PERSTD. This same
approach is used to determine PERCL
under the calculation-based approach,
which is described in greater detail in
section III.E.2.b. In the April 2015
pumps test procedure NOPR, DOE
proposed to determine the part load
losses of the motor at each load point by
applying an algorithm to the full load
losses of the motor. 80 FR 17615.
Specifically, DOE proposed to
determine a part load loss factor (yi) at
each load point based on the following
equation (13):
III.D.1 for bare pumps and when
determining PERSTD, or the represented
nominal full load motor efficiency
described in section III.D.2 for pumps
sold with applicable motors.
Specifically, DOE proposed that the full
load motor losses would be calculated
as shown in equation (14):
would be determined based on the
product of the full load losses and the
part load loss factor at that load point,
as shown in equation (15):
which a default nominal full load motor efficiency
applies, as well as pumps rated with motors and
pumps rated with motors and controls, for with the
nominal full load motor efficiency with which the
pump is rated applies (not a default value),
depending on the context. Therefore, in this final
rule, DOE is updating the terminology to use the
nomenclature Lfull and describe the term as
equivalent to ‘‘motor losses at full load,’’
referencing the relevant procedure for determining
full load motor losses based on the pump
configuration.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00040
Fmt 4701
Sfmt 4700
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.011 ER25JA16.012
64 DOE notes that, in the April 2015 pumps test
procedure NOPR, DOE proposed to define this term
using the nomenclature Lfull,default and described it
as equivalent to ‘‘default motor losses at full load.’’
However, upon further review, DOE finds this
terminology confusing because this equation
applies both to pumps rated as bare pumps, for
a value of 1.000 should be used as the
part load loss factor.
This change is needed because the
proposed part load loss curves were not
developed to be representative of
ER25JA16.013
motors. DOE notes that, in making the
change requested by interested parties
to account for service factor in sizing
submersible motors (see section
III.D.1.b), DOE is making a slight
modification to the part load loss factors
for VTS pumps to specify that where
These calculated part load motor
losses at each of the specified load
points would then be combined with
the measured pump shaft input power
and weighted equally to calculate PERCL
or PERVL via the calculation-based
approach and PERSTD, as described in
section III.E.1.b and III.B.2, respectively.
Id. at 17615–16.
DOE requested comment on the
development and use of the motor part
load loss factor curves to describe part
load performance of covered motors and
submersible motors, including the
default motor specified in section III.D.1
for bare pumps and calculation of
PERSTD. DOE received no comments on
the proposal and, as such, is adopting
the proposed methodology presented in
the April 2015 pumps test procedure
NOPR with no modification for pumps,
except those sold with submersible
ER25JA16.010
tkelley on DSK3SPTVN1PROD with RULES2
Where:
Li = motor losses at load point i (hp),
Lfull = motor losses at full load (hp),
yi = part load loss factor at load point i, and
i = load point corresponding to 75, 100, or
110 percent of BEP flow for uncontrolled
pumps or 25, 50, 75, or 100 percent of
BEP flow for pumps sold with a motor
and continuous or non-continuous
controls.
with the pump is permitted when
determining PERCL or PERVL. However,
an assumption regarding the default
efficiency of the minimally compliant
motor that can be paired with a given
pump would still be required to
calculate PERSTD. See Section III.D.1; 80
FR 17586, 17613–14 (April 1, 2015).
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
performance above the full load of the
motor. This modification implicitly
assumes that the motor efficiency curve
is flat between full load and the service
factor (i.e., 1.15). DOE expects the full
load losses of the motor to be more
representative of the performance of
motors beyond full load operation than
extending the curve, which would
assume that losses would decrease
(efficiency would increase) above full
load. DOE has not made any other
revisions to the part load loss factors.
DOE also notes that such is the case for
all pumps; that is, the ratio of pump
shaft input power to motor horsepower
should not exceed a value of 1 for any
pump. As such, to ensure that the part
load loss factor equation is not applied
inappropriately, DOE is adding this
clarification as applicable to all pumps
tested under the test procedure.
E. Test Methods for Different Pump
Configurations
As previously discussed, the PEICL
and PEIVL for a given pump is
determined by first calculating the
PERCL or PERVL, as applicable, for the
given pump. For all pumps, the PERCL
or PERVL is then scaled based on a
calculated PERSTD (i.e., the PERCL of a
pump that would minimally comply
with the applicable standard). (Docket
No. EERE–2011–BT–STD–0031) The
process for determining the PERSTD is
described in section III.B.2.
In the April 2015 pumps test
procedure NOPR, DOE proposed that
different test methods for determining
the PERCL and PERVL of applicable
pumps would apply based on the
configuration of the pump model and
the characteristics of the motor and
controls it may be sold with. 80 FR
17586, 17616 (April 1, 2015). For
example, the available test method(s) for
pumps sold alone (i.e., bare pumps)
would be different than those for pumps
sold with motors or pumps sold with
motors and continuous or noncontinuous controls. Further, the
available test methods for pumps sold
with motors that are covered by DOE’s
energy conservation standards for
electric motors at 10 CFR 431.25(g) (as
established by the energy conservation
standards established in the May 2014
medium electric motor energy
conservation standard final rule (79 FR
30933 (May 29, 2014)) 65 would be
different than the available test methods
4125
for pumps sold with motors that are not
covered by DOE’s test procedure for
electric motors. Specifically, DOE
proposed defining the applicability of
the proposed test methods based on the
following:
• Two potential approaches: (1)
Testing-based versus (2) calculationbased;
• three potential configurations: (1)
Bare pumps, (2) pumps sold with
motors, and (3) pumps sold with motors
and controls; and
• two different sub-configuration
criteria:
(1) Whether the pump was sold with:
(a) a motor covered by DOE’s electric
motor energy conservation standards,
(b) a submersible motor, (c) a motor that
is not covered by DOE’s electric motor
energy conservation standards and is
not a submersible motor, or (d) no
motor; and
(2) whether the pump was sold with:
(a) continuous controls, (b) noncontinuous controls, or (c) neither
continuous or non-continuous controls.
The applicability of DOE’s proposed
test methods to different configurations
of pumps is summarized in Table III.8.
Id. at 17627.
TABLE III.8—APPLICABILITY OF CALCULATION-BASED AND TESTING-BASED TEST PROCEDURE OPTIONS BASED ON PUMP
CONFIGURATION
Pump configuration
Pump sub-configuration
Calculation-based test method
Bare Pump ...............
Bare Pump .................................................
Pump + Motor ..........
Pump + Motor Covered by DOE’s Electric
Motor Energy Conservation Standards
OR Pump + Submersible Motor.
A.1: Tested Pump Efficiency of Bare
Pump + Default Nominal Full Load
Motor Efficiency + Default Motor Part
Load Loss Curve.
B.1: Tested Pump Efficiency of Bare
Pump + Represented Nominal Full
Load Motor Efficiency for Actual Motor
Paired with Pump + Default Motor Part
Load Loss Curve.
Not Applicable ...........................................
tkelley on DSK3SPTVN1PROD with RULES2
Pump + Motor +
Speed Controls.
Pump + Motor Not Covered by DOE’s
Electric Motor Energy Conservation
Standards (Except Submersible Motors).
Pump + Motor Covered by DOE’s Electric C.1: Tested Pump Efficiency of Bare
Motor Energy Conservation Standards
Pump + Represented Nominal Full
+ Continuous Control OR Pump + SubLoad Motor Efficiency for Actual Motor
mersible Motor + Continuous Control.
Paired with Pump + Default Motor/Control Part Load Loss Curve + Assumed
System Curve.
Pump + Motor Covered by DOE’s Electric Not Applicable ...........................................
Motor Energy Conservation Standards
+ Non-Continuous Control OR Pump +
Submersible Motor + Non-Continuous
Control.
Pump + Motor Not Covered by DOE’s Not Applicable ...........................................
Electric Motor Energy Conservation
Standards (Except Submersible Motors)
+ Continuous or Non-Continuous Controls.
65 DOE recognizes that the scope of the electric
motor standards at 10 CFR 431.25 may change in
the future as a result of potential future
VerDate Sep<11>2014
Testing-based test method
13:56 Jan 22, 2016
Jkt 238001
rulemakings. Since the scope of such future motors
standards is unknown, DOE wishes to clearly and
unambiguously establish the specific motors which,
PO 00000
Frm 00041
Fmt 4701
Sfmt 4700
Not Applicable.
B.2: Tested Wire-to-Water Performance.
B.2: Tested Wire-to-Water Performance.
C.2: Tested Wire-to-Water Performance.
C.2: Tested Wire-to-Water Performance.
C.2: Tested Wire-to-Water Performance.
when sold with an applicable bare pump, would be
eligible to apply the calculation-based test methods
described in this section.
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
4126
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
DOE’s proposed applicability of
testing-based and calculation-based test
methods, as shown in Table III.8, was
designed to maximize the number of
pumps that can be rated using the less
burdensome calculation-based methods
A.1, B.1, and C.1. DOE also proposed
the applicability of the various test
methods to maximize flexibility in
rating equipment. That is, where
possible, DOE proposed to allow either
the calculation-based or the testingbased method to be used to determine
the PEI of applicable pump models. 80
FR 17627–28. In this case, if a
manufacturer wished to represent the
improved performance of a given pump,
for example from a motor with
improved part load efficiency
performance, and believed that the
assumptions made in the calculation
method would not adequately represent
the improved performance of that
pump, the manufacturer would be able
to use the testing-based methods to rate
the PEICL or PEIVL of that pump model
to capture the improved performance of
the pump as tested.
DOE also noted that, since the
measured performance of individual
units can vary from the average
performance of the population or from
DOE’s assumed values used in the
calculation-based approach, it is
theoretically possible for the
calculation-based approach to generate
ratings that are better or worse than the
testing-based approach. To address this
possibility, DOE proposed that
manufacturers report the test method
(i.e., calculation-based or testing-based)
used to determine the PEI for each
model and that DOE would use the
same method used by the manufacturer
to generate the rating when performing
assessment or enforcement testing. Id. at
17628.
DOE requested comment on its
proposal to establish calculation-based
test methods as the required test method
for bare pumps and testing-based
methods as the required test method for
pumps sold with motors that are not
regulated by DOE’s electric motor
energy conservation standards, except
for submersible motors, or for pumps
sold with any motors and with noncontinuous controls. DOE also requested
comment on the proposal to allow either
testing-based methods or calculationbased methods to be used to rate pumps
sold with continuous control-equipped
motors that are either (1) regulated by
DOE’s electric motor standards or (2)
submersible motors. In addition, DOE
requested comment on the level of
burden associated with reporting the
test method used by a manufacturer to
certify a given pump basic model as
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
compliant with any energy conservation
standards DOE may set.
HI commented that it agrees with
these proposals, and that it is not too
burdensome to note the test method in
the certification report, as proposed in
the April 2015 pumps test procedure
NOPR. (HI, No. 8 at p. 23) Wilo
commented that the calculation-based
test methods should be eliminated
entirely. Wilo indicated that one
problem is that DOE is not responsible
for providing tools to determine
compliance, so each manufacturer will
be responsible for creating its own
potentially erroneous evaluation tool.
Wilo also indicated that a second
problem is that there are no standard
efficiencies for VFDs, so a manufacturer
could use a minimally performing VFD
to create a better performing PEI value
for a given pump sold with motor and
controls. (Wilo, Docket No. EERE–2011–
BT–STD–0031, No. 44 at pp. 3–4)
In response to Wilo’s comment
regarding the calculation-based
approach, DOE notes that DOE
developed the calculation-based
approach with extensive feedback and
input from the CIP Working Group and
believes that it is appropriate for the
categories and configurations of pumps
for which DOE proposed it would be
applicable. DOE also notes that, as
described in the April 2015 pumps test
procedure NOPR, the calculation-based
approach is significantly less
burdensome than the testing-based
approach since a manufacturer may
elect to determine the PEI rating for
several pump models sold with different
combinations of motors and/or
continuous controls based on the
physical test of the bare pump only.
That is, manufacturers may test a
representative sample of bare pumps
(see section III.G for a description of
DOE’s sampling provisions for pumps)
and all subsequent ratings of that bare
pump sold with any combination of
motors that are covered by DOE’s energy
conservation standards, submersible
motors, and continuous controls may be
calculated using the calculation-based
approach with no additional physical
testing. Due to the potentially large
burden associated with requiring
physical testing of each potential
combination of a bare pump, motor, and
continuous control, as well as the
existing concerns of manufacturers and
other interested parties regarding the
proposed test procedure (see section
IV.B), DOE is electing to maintain the
calculation-based procedure as an
option for applicable pumps.
DOE also notes that the calculationbased procedure is required for bare
pumps, as testing-based methods do not
PO 00000
Frm 00042
Fmt 4701
Sfmt 4700
apply to bare pumps because a PEI
rating (which includes the efficiency of
the motor) cannot be determined based
on a test of the bare pump alone. For all
other pump configurations, the
calculation-based method is only
offered as an option, should
manufacturers choose to employ it.
Therefore, if Wilo prefers to use the
testing-based approach to certify their
equipment, it may do so for all
configurations of pumps except bare
pumps.
Regarding the accuracy or validity of
any evaluation tools to implement any
calculations associated with either the
calculation-based or testing-based
approach, DOE notes that manufacturers
must rate pumps in accordance with the
test procedure. The calculation-based
approach required by the regulations
provides sufficient detail for
manufacturers to develop reliable tools.
Nonetheless, manufacturers are
responsible for ensuring that any
calculations are performed correctly,
whether performed using an evaluation
tool or by hand, for both the calculationbased and the testing-based approaches.
In response to Wilo’s comment
regarding the potential for a
manufacturer to improve the PEI rating
of a given pump model sold with a
motor, but without continuous controls,
by pairing the pump with continuous
controls, DOE acknowledges that the
PEI for pumps sold with continuous
controls tested using either the
calculation-based or testing-based
approach will be better (i.e., lower) than
that of the same pump sold and tested
with a motor only. However, consistent
with the feedback provided by the CIP
Working Group, DOE believes that
decreased PEI is reflective and
representative of the improved energy
performance customers are likely to
observe in the field. That is, the load
points and, in the case of controlledmotors, the system curve, assumed for
these pumps (discussed in section III.B
and III.E.2.c, respectively) are
representative of the operation of such
pumps in the field. DOE also notes that,
as mentioned in the April 2015 pumps
test procedure NOPR, the testing-based
method is intended to allow for more
granular differentiation of equipment
performance, including differentiation
of the performance of different models
or styles of continuous controls. In
particular, DOE noted in the April 2015
pumps test procedure NOPR that the
ability of the testing-based method to
differentiate among the performance of
various continuous controls was
particularly important for pumps sold
with motors and continuous controls,
since DOE is only assuming a single
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
Where:
wi = weighting at load point i (equal
weighting or 1⁄3 in this case),
Piin,m = calculated input power to the motor
at load point i (hp),
Pi = the shaft input power to the bare pump
at load point i (hp),
Li = default motor losses at load point i (hp),
and
i = load point corresponding to 75, 100, or
110 percent of BEP flow as determined
66 The calculation-based test method was
designed to capture the dynamic response of a
control that can continuously respond to changes in
load and reduce power consumption at all load
points below BEP. Therefore, pumps sold with noncontinuous controls would instead use the testingbased method described in section III.E.2.c, which
captures some reduction in power consumption at
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
• section III.E.2.c: The testing-based
approach for pumps sold with motors
and continuous or non-continuous
controls.
1. Calculation-Based Test Methods
In the April 2015 pumps test
procedure NOPR, DOE proposed that
the following calculation-based test
methods would be used to rate (1)
pumps sold as bare pumps (method
A.1); (2) pumps sold either with (a)
motors that are regulated by DOE’s
electric motor standards or (b)
submersible motors (method B.1); and
(3) pumps sold with motors that are
either (a) regulated by DOE’s electric
motor standards or (b) submersible
motors, and that are equipped with
continuous controls 66 67 (method C.1).
80 FR 17586, 17616 (April 1, 2015).
Regardless of the pump configuration
or characteristics, the calculation-based
test method for the applicable pump
types includes the following steps:
(1) Physical testing of the bare pump,
in accordance with HI 40.6–2014, to
determine the pump BEP and pump
shaft input power at 75, 100, and 110 of
actual BEP flow, adjusted to nominal
speed;
(2) Determining the part load losses of
the motor (or default motor) and any
continuous or non-continuous controls
applicable to the rated pump model at
each load point;
(3) Taking the sum of the pump shaft
input power at nominal speed and the
calculated part load motor losses at each
load point in the constant load or
variable load profiles, as applicable, to
in accordance with the DOE test
procedure.
Id.
The part load motor losses for the bare
pump would be determined for the bare
pump based on a default nominal full
load motor efficiency, representative of
a motor that is minimally compliant
with DOE’s electric motor energy
conservation standards (or the default
minimum motor efficiency for
some reduced flow rates. DOE discussed this
approach with the CIP Working Group, which
generally agreed with it, although such a
recommendation was not specifically included in
the CIP Working Group recommendations. (Docket
No. EERE–2013–BT–NOC–0039, No. 107 at pp. 49–
50)
PO 00000
Frm 00043
Fmt 4701
Sfmt 4700
determine the input power to the pump
at each load point;
(4) Determining the PERCL or PERVL,
as applicable, for the given pump as the
weighted average of the input power to
the pump at the applicable load points;
(5) Determining the PERSTD for the
minimally compliant pump, as
described in section III.B.2; and
(6) Dividing the PERCL or PERVL from
step 4 by the PERSTD for that pump
model to determine PEICL or PEIVL,
respectively.
The specific test methods for bare
pumps, pumps sold with motors, and
pumps sold with motors and continuous
controls are described in more detail in
the following sections III.E.1.a, III.E.1.b,
and III.E.1.c, respectively.
a. Calculation-Based Test Method A.1:
Bare Pump
As described previously, DOE
proposed in the April 2015 pumps test
procedure NOPR that the bare pump
PERCL would be determined based on
the measured pump shaft input power
at 75, 100, and 110 percent of BEP flow.
80 FR 17586, 17616–17 (April 1, 2015).
Section III.C of this final rule describes
the test method for determining pump
shaft input power at the specified load
points, which is based on HI 40.6–2014.
DOE proposed that the measured pump
shaft input power at the three constantload flow points would then be
combined with the part load motor
losses at each load point and equally
weighted to determine PERCL for that
bare pump, as shown in equation (16):
submersible motors), as described in
section III.D.1, and the default motor
loss curve, as described in section
III.D.2. Id.
As presented in section III.B, the
PEICL for a bare pump can then be
calculated as the PERCL for a given
pump divided by the PERSTD for a pump
that is minimally compliant with DOE’s
pump standards sold without controls,
as shown in equation (17):
67 DOE notes that some pumps sold with
continuous controls, such as pumps sold with
ECMs, may not be eligible to apply the calculationbased method based on the fact that ECMs are not:
(1) A type of motor covered by DOE’s energy
conservation standards for covered motors or (2) a
submersible motor (see section III.E). These pumps
would instead apply a testing-based method.
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.014
system performance curve to represent
all applicable continuous controls, as
described in section III.E.1.c, and the
testing-based method may provide an
opportunity for manufacturers to
differentiate among the performance of
different continuous control
technologies. Id. at 17627–28.
In this test procedure final rule, DOE
is adopting the test method applicability
proposed in the April 2015 pumps test
procedure NOPR and shown in Table
III.8 with no modifications. As proposed
in the NOPR, DOE is also adopting
requirements that manufacturers report
the test method used to determine the
ratings for applicable pump models and
provisions that when conducting
assessment and enforcement testing
DOE will use the same method reported
by manufacturers.
The specific test methods, any
comments DOE received on the
proposed methods and applicability,
and the final test methods DOE is
adopting in this final rule are discussed
in the following sections:
• Section III.E.1.a: The calculationbased approach for bare pumps (method
A.1),
• section III.E.1.b: The calculationbased approach for pumps sold with
applicable motors,
• section III.E.1.c: The calculationbased approach for pumps sold with
applicable motors and continuous
controls,
• section III.E.2.b: The testing-based
approach for pumps sold with motors,
and
4127
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
Where:
PERSTD = the PERCL for a pump of the same
equipment class with the same flow and
specific speed characteristics that is
minimally compliant with DOE’s energy
conservation standards serving the same
hydraulic load (hp). The procedure for
determining PERSTD is described in
detail in section III.B.2.
tkelley on DSK3SPTVN1PROD with RULES2
For bare pumps, DOE proposed
establishing the calculation-based
approach (method A.1) as the only
applicable test procedure, as testingbased methods do not apply to bare
pumps because a PEI rating (which
includes the efficiency of the motor)
cannot be determined based on a test of
the bare pump alone.
DOE received no specific comments
on the proposed test procedure for bare
pumps and is adopting the calculationbased test procedure, as proposed.
b. Calculation-Based Test Method B.1:
Pump Sold With a Motor
For pumps sold with motors that
either are regulated by DOE’s electric
motor standards or are submersible
motors, DOE proposed to allow the use
of the applicable calculation-based
method (method B.1), in addition to the
testing-based method (method B.2,
discussed in section III.E.2.b). In these
cases, DOE proposed that the
calculation-based test procedure would
be similar to that for pumps sold alone
(method A.1) except that the
represented nominal full load motor
efficiency, or losses, would be that of
the motor with which the pump is sold
when determining PERCL, as opposed to
the default nominal full load motor
efficiency assumed in the bare pump
case. For motors covered by DOE’s
electric motor standards, DOE proposed
that the represented nominal full load
motor efficiency be determined in
accordance with the DOE electric motor
test procedure specified at 10 CFR
431.16 and appendix B to subpart B of
part 431 (see section III.D.2) and
applicable procedures for determining
the represented value (also specified in
10 CFR part 429 and 431). For pumps
sold with submersible motors rated
using the calculation-based method, the
default nominal full load submersible
motor efficiency would be determined
from Table III.6 (see section III.D.1.b).
DOE also reiterated that this calculationbased method would not apply to
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
pumps sold with motors that are not
subject to DOE’s electric motor
standards (except for submersible
motors). 80 FR 17586, 17618 (April 1,
2015).
The PEICL for pumps sold with motors
would then be calculated using a similar
approach that would be applied to bare
pumps shown in equations (16) and
(17), above, except that the default part
load losses of the motor at each load
point would be determined based on the
represented nominal full load motor
efficiency, as described in section
III.D.2. Id.
As previously discussed in section
III.B.2, in determining PERSTD, DOE
proposed to use the electric motor
efficiency standards listed at 10 CFR
431.25 for polyphase NEMA Design B
motors as the default nominal full load
motor efficiency of the minimally
compliant pump for pumps sold with
motors other than submersible motors.
Similarly, for pumps sold with
submersible motors, the default nominal
full load motor efficiency would be that
specified in Table III.6 in section
III.D.1.b for both the rated pump model
and PERSTD. Id.
In the April 2015 pump test
procedure NOPR, DOE requested
comment on several specific items
related to the proposed calculationbased test procedure for pumps sold
with applicable motors. Specifically,
DOE requested comment on its proposal
to determine the part load losses of
motors covered by DOE’s electric motor
energy conservation standards using the
represented nominal full load motor
efficiency, as determined in accordance
with DOE’s electric motor test
procedure, and the same default motor
part load loss curve used in test method
A.1. In response, HI commented that it
could not comment on this issue. (HI,
No. 8 at p. 21) DOE received no
additional comments on this proposal.
DOE requested comment on its
proposal that pumps sold with motors
that are not addressed by DOE’s electric
motors test procedure (except
submersible motors) would be rated
based on the testing-based approach,
and HI commented that it agrees with
this proposal. (HI, No. 8 at p. 21) DOE
received no additional comments on
this proposal and has determined that
no revisions are necessary.
PO 00000
Frm 00044
Fmt 4701
Sfmt 4700
DOE also requested comment on its
proposal to determine the PERCL of
pumps sold with submersible motors
using the proposed default nominal full
load efficiency values for submersible
motors and to apply the same default
motor part load loss curve to the default
motor in test method A.1 to the bare
pump. HI commented that it agrees with
the proposal as long its concerns
regarding submersible motor efficiency,
as detailed in section III.D.1.b of this
final rule, are addressed. (HI, No. 8 at p.
21) DOE received no other comments on
this proposal.
Based on the comments received from
interested parties, DOE is adopting the
proposed test method B.1 for pumps
sold with motors covered by DOE’s
electric motor test procedure. For
pumps sold with submersible motors,
the default nominal full load
submersible motor efficiency values
used in the calculation of PERCL and
PERSTD are the values shown in Table
III.7, which are revised based on the
input from HI.
c. Calculation-Based Test Method C.1:
Pump Sold With a Motor and
Continuous Controls
For pumps sold with continuous
controls and motors that are either (a)
regulated by DOE’s electric motor
standards for electric motors or (b)
submersible motors, DOE proposed, in
the April 2015 pumps test procedure
NOPR, to allow use of either the
applicable calculation-based method
(method C.1, discussed in this section
III.E.1.c) or the testing-based method
(method C.2, discussed in section
III.E.2.c). 80 FR 17618–19. The proposed
calculation-based approach for pumps
sold with motors and continuous
controls determines the PEIVL metric,
which accounts for the power reduction
resulting from reducing speed to
achieve a given flow rate, as opposed to
throttling. In this case, DOE proposed
that the PEIVL would be determined as
the PERVL of the given pump divided by
the PERSTD, where the PERSTD would be
determined in accordance with the
procedures in section III.B.2, and the
PERVL would be determined as the
weighted average input power to the
pump at 25, 50, 75, and 100 percent of
BEP flow, as shown in equation (18):
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.015
4128
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
Where:
wi = weighting at load point i (equal
weighting or 1⁄4 in this case),
Piin,c = measured or calculated driver power
input to the continuous or noncontinuous controls at load point i (hp),
and
i = 25, 50, 75, and 100 percent of BEP flow,
as determined in accordance with the
DOE test procedure.
4129
Where:
H = the total system head (ft),
Q = the flow rate (gpm),
Q100% = flow rate at 100 percent of BEP flow
(gpm), and
H100% = total pump head at 100 percent of
BEP flow (ft).
DOE’s approach for developing the
proposed system curve is discussed in
detail in the April 2015 pump test
procedure NOPR. Id. at 17619–20.
To determine the pump shaft input
power at 25, 50, and 75 percent of BEP
flow, DOE proposed to apply the
reference system curve discussed in
section III.E.1.c and assume that
continuous speed reduction is applied
to achieve the reduced load points.
Specifically, the reduction in pump
shaft input power at part loadings was
assumed to be equivalent to the relative
reduction in pump hydraulic output
power assumed by the system curve, as
shown in equation (20):
tkelley on DSK3SPTVN1PROD with RULES2
Id.
Similar to the calculation-based
approaches for bare pumps and pumps
sold with motors, the input power to the
VerDate Sep<11>2014
15:06 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00045
Fmt 4701
Sfmt 4700
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.017 ER25JA16.018
percent of BEP flow load points would
be calculated based on an assumed
system curve. In particular, consistent
with CIP Working Group discussions
(Docket No. EERE–2013–BT–NOC–0039,
No. 107 at pp. 49–50), DOE proposed to
use a quadratic reference system curve,
which goes through the BEP and an
offset on the y-axis, representative of a
static head component to the system
curve. The reference system curve
equation is shown in equation (19) and
depicted in Figure III.1:
ER25JA16.016
pump when sold with motors and
continuous controls would be
determined by adding together the
pump shaft input power and the
combined losses from the motor and
continuous controls at each of the load
points. However, in the case of
determining PERVL for pumps sold with
motors and continuous controls, DOE
proposed that only the input power at
the 100 percent of BEP flow load point
would be determined through testing,
and the remaining 25, 50, and 75
4130
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
Where:
Pi = shaft input power to the bare pump at
load point i (hp),
P100% = shaft input power to the bare pump
at 100 percent of BEP flow (hp),
Qi = flow rate at load point i (gpm),
Q100% = flow rate at 100 percent of BEP flow
(gpm), and
i = 25, 50, and 75 percent of BEP flow as
determined in accordance with the DOE
test procedure.
Id. at 17620–21.
Where:
zi = the part load loss factor for the motor and
continuous controls at load point i;
Finally, to calculate the PERVL for
pumps sold with applicable motors and
continuous controls, DOE proposed to
apply a separate algorithm for
determining the part load losses of the
motor and continuous controls together,
to account for the additional losses as a
result of inefficiencies from the
continuous control and increased
inefficiencies in the speed-controlled
motor due to harmonic distortion. Based
on data DOE collected regarding VFD
performance, DOE determined that four
part load loss equations would be the
most appropriate way to represent the
combined efficiency of the motor and
continuous control as a function of the
output power of the motor and,
therefore, proposed to use the
polynomial expression shown in
equation (21) to estimate the aggregate
part load losses of motors and
continuous controls at each load point:
a,b,c = coefficients based on motor
horsepower, see Table III.9;
Pi = the shaft input power to the bare pump
at load point i (hp);
MotorHP = the horsepower of the motor with
which the pump is being rated (hp); and
i = 25, 50, 75, and 100 percent of BEP flow
as determined in accordance with the
DOE test procedure.
TABLE III.9—MOTOR AND CONTINUOUS CONTROL PART LOAD LOSS FACTOR EQUATION COEFFICIENTS FOR EQUATION
(21)
Coefficients for equation (21)
a
The development of DOE’s part load
loss factor equations for motors and
continuous controls are also described
in detail in the April 2015 pumps test
procedure NOPR. 80 FR 17586, 17621
(April 1, 2015).
To determine the resultant PEIVL
rating for pumps sold with applicable
motors and continuous controls and
rated based on the calculation-based
approach, the PERVL determined based
on the reference system curve and
default motor and control losses would
be divided by the PERSTD, determined in
accordance with the procedure
described in section III.B.2. DOE notes
that, although the PERVL of the tested
pump only requires the 100 percent of
BEP flow load point to be determined
experimentally, the full HI 40.6–2014
test would still be required, and the
pump hydraulic output power at 75,
100, and 110 percent of BEP flow would
still be necessary for determining the
PERSTD of the given pump. Id. at 17621–
22.
In response to DOE’s proposed
calculation-based approach for pumps
sold with application motors and
VerDate Sep<11>2014
15:06 Jan 22, 2016
Jkt 238001
continuous controls, HI commented that
it is in agreement with the calculationbased test method for pumps sold with
motors and continuous controls,
provided that the corrected version of
NOPR equation (6) presented at the
April 2015 NOPR public meeting is
used. (HI, No. 8 at pp. 21–22) HI also
specifically indicated that it agrees with
the proposed system curve shape, and
that it agrees that the curve should go
through the statically loaded offset.
Regal Beloit commented that it
accepts the structure of the pump
energy conservation standards NOPR
and the April 2015 pumps test
procedure NOPR as presented with
respect to motor-drive efficiency testing
and evaluation, and encouraged the use
of the forthcoming industry standard
IEC 61800–9–2 once it is published and
at such time as the DOE seeks to revise
the pumps test procedure. (Regal Beloit,
No. 9 at p. 1) DOE understands that the
IEC standard will serve as a 60 Hz
version of the 50 Hz European industry
standard BS EN 50598. DOE will review
the IEC standard once it is available,
PO 00000
Frm 00046
Fmt 4701
Sfmt 4700
¥0.4658
¥1.3198
¥1.5122
¥0.8914
c
1.4965
2.9551
3.0777
2.8846
0.5303
0.1052
0.1847
0.2625
and may consider it for future
rulemaking activity.
DOE received no other comments on
this test method, and confirms that the
final rule uses the corrected equation for
determining the minimum standard
pump efficiency presented at the April
2015 NOPR public meeting.
d. Other Calculation Methods for
Determination of Pump Performance
In the April 2015 pumps test
procedure NOPR, DOE proposed that
each bare pump model be physically
tested in accordance with the test
procedure and that calculations alone
could not be used to determine bare
pump performance. DOE noted that the
calculation-based test procedure for
certain applicable pumps already
contains provisions for tested bare
pump performance to be combined with
default or tested performance data
regarding the motor or motor with
continuous or non-continuous controls
to calculate the PER of multiple pump
basic models. Therefore, DOE proposed
that, beyond the calculations proposed
in the April 2015 pumps test procedure
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.020
tkelley on DSK3SPTVN1PROD with RULES2
≤5 .....................................................................................................................................
>5 and ≤20 .......................................................................................................................
>20 and ≤50 .....................................................................................................................
>50 ...................................................................................................................................
b
ER25JA16.019
Motor horsepower
(hp)
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
additional measurements are made of
bare pump performance or pump shaft
input power, in addition to input power
to the motor. See section III.C.2.d.
Specifically, in the case of pumps sold
with motors or motors with continuous
or non-continuous controls measured
using testing-based methods, DOE noted
that input power to the pump shaft is
not measured directly in the proposed
test procedure. As such, DOE proposed
that the BEP for such pumps be
determined using a similar procedure to
that discussed in section III.C.2.d for
calculation-based methods; however,
BEP would be determined using the
maxima of what is typically known as
overall efficiency (i.e., the input power
to the driver or continuous control, if
any, divided by the pump hydraulic
output power at the nominal speed),
rather than pump efficiency. 80 FR
17586, 17623 (April 1, 2015).
DOE requested comment on its
proposal to require manufacturers to
2. Testing-Based Methods
determine BEP for pumps rated with a
testing-based method by using the ratio
Testing-based methods directly
of input power to the driver or
measure the input power to the motor,
continuous control, if any, over pump
continuous control, or non-continuous
control at the load points of interest (i.e., hydraulic output. DOE also requested
75, 100, and 110 percent of BEP flow for input on the degree to which this
uncontrolled pumps and 25, 50, 75, and method may yield significantly different
100 percent of BEP flow for pumps sold BEPs from the case in which BEP is
determined based on pump efficiency.
with a motor and speed controls). As
HI commented that BEP can only be
such, as discussed previously, these
determined when testing the bare pump.
methods cannot be applied to bare
HI also indicated that determining BEP
pumps. In addition, these test methods
through a wire-to-water (i.e., testingare the only test methods applicable to
based) method will cause the
pumps sold with motors that are not
manufacturers to have to test each motor
addressed by DOE’s electric motor test
configuration sold with the bare pump,
procedure (except submersible motors)
increasing the burden. HI recommended
or that are sold with non-continuous
that the manufacturer be given the
controls and are an optional procedure
option to determine BEP by testing as a
for all pumps sold with motors or
bare pump or by testing using a wire to
motors with continuous controls.
The following sections describe DOE’s water test. HI also recommended that
proposals, any comments received from BEP be instead defined as the pump
hydraulic power operating point
interested parties, and the final test
provisions DOE is adopting in this final consisting of both flow and head
conditions that result in the maximum
rule on the following topics:
efficiency of the certified unit. (HI, No.
• How to determine BEP for pumps
8 at pp. 22–23).
rated using the testing-based method
After review, DOE has determined
(section III.E.2.a),
that the HI proposal would yield
• the testing-based approach for
different efficiency ratings for the same
pumps sold with motors (method B.2;
pump. In response to HI’s comment,
described in section III.E.2.b), and
DOE notes that DOE initially proposed
• the testing-based approach for
pumps sold with motors and continuous that the BEP when applying the testingor non-continuous controls (method B.3; based methods would be based on the
overall efficiency in order to reduce
described in section III.E.2.c).
burden when conducting testing. That
a. The Best Efficiency Point for Pumps
is, when testing a pump in accordance
Testing Using Testing-Based Methods
with the testing-based method, DOE
In the April 2015 pumps test
proposed that the overall efficiency
procedure NOPR, DOE noted that when would be used to determine pump
testing some pumps using testing-based efficiency so that the pump shaft input
power would not have to be separately
methods, it is not possible to determine
BEP as a ratio of pump input power over determined, since measurements of
pump shaft input power are not
pump hydraulic power unless
tkelley on DSK3SPTVN1PROD with RULES2
NOPR, DOE would not permit use of
other algorithms or alternative
efficiency determination methods to
determine the rated performance of
covered pumps or pump components
(i.e., motors or controls). 80 FR 17586,
17622–23 (April 1, 2015).
DOE requested comment on its
proposal to require testing of each
individual bare pump as the basis for a
certified PEICL or PEIVL rating for one or
more pump basic models. DOE also
requested comment on its proposal to
limit the use of calculations and
algorithms in the determination of
pump performance to the calculationbased methods proposed in the NOPR.
HI commented that it agrees with these
proposals. (HI, No. 8 at p. 22) DOE
received no additional comments on
these proposals and, consistent with the
comments submitted by HI, is adopting
such calculation methods as discussed
in this section III.E.1 in this final rule.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00047
Fmt 4701
Sfmt 4700
4131
otherwise needed when conducting the
test procedure. If DOE were instead to
specify that BEP be determined based
on the pump efficiency only, pumps
tested using the testing-based
approaches would either need to have
additional instrumentation installed
(e.g., a torque sensor) to measure pump
shaft input power or, in some cases,
would require duplicative testing of the
pump with a calibrated motor if a torque
sensor could not be inserted between
the bare pump and motor based on the
pump design. For example, ESCC and
VTS pumps would not be able to be
tested using the testing-based methods
to determine BEP based on pump
efficiency in the same test, unless a
calibrated motor with the same
characteristics as the motor with which
the pump model was to be distributed
in commerce was used.
In response to HI’s concern regarding
the increased burden of determining the
BEP based on overall efficiency, DOE
finds this statement to be erroneous,
since the determination of BEP based on
overall efficiency would only be
required for the testing-based
approaches and the testing-based
approaches already require each basic
model to be tested. Under the proposed
approach, no incremental testing would
be necessary. To the extent that
manufacturers wish to use the
calculation-based methods to determine
the PEI of applicable pumps, the BEP of
the bare pump, based on pump
efficiency, must be used. However,
these data are irrelevant to determining
the PEI of pumps under the testingbased approach, since the two methods
are mutually exclusive. That is, the PEI
of a given pump cannot be determined
via both calculation-based and testingbased approaches. DOE has ensured that
this is clear in the regulatory text
included in this final rule.
Regarding HI’s proposal to optionally
allow manufacturers to use either pump
efficiency or overall efficiency, DOE
believes that such an approach could
potentially result in variability in the
BEP, and thus PEI, for the same pump
model. This is unacceptable since each
pump model can have only one certified
PEI value associated with it and that
value must be repeatable and consistent
among test facilities.
DOE believes that the approach
proposed in the April 2015 pumps test
procedure NOPR will result in
representations that are more
straightforward and consistent, as well
as less burdensome, for those pumps
rated using the testing-based approach.
As such, DOE is adopting, in this final
rule, the approach proposed in the April
2015 pump test procedure NOPR to
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
determine the BEP of pumps rated using
the testing-based approach based on
overall efficiency, as opposed to pump
efficiency.
Regarding HI’s comment that BEP
should be determined as the load point
associated with maximum efficiency,
which consists of both head and flow
points, DOE acknowledges HI’s
comments and agrees that the BEP for
each pump represents the flow and head
points representing maximum efficiency
at full impeller diameter. In particular,
DOE notes that DOE’s definition of BEP,
as adopted in this final rule, specifies
BEP with respect to a load point,
consisting of both flow and head
conditions. However, in this test
procedure final rule, DOE in general
refers to BEP flow, since DOE’s
specified load points are characterized
with respect to BEP flow only. DOE
understands that the head and flow of
a given pump, at full impeller diameter
and without throttling, are inextricably
linked, so it is not necessary to
independently account for and specify
both parameters. That is, for example,
by specifying the flow at 100 percent of
BEP, the power calculated at that load
point will, necessarily, also be reflective
of head at 100 percent of BEP flow,
since the data are all based on the same
curve. It is not possible to determine the
power input at, for example, 50 percent
of BEP flow and 100 percent of BEP
head without throttling the pump,
trimming the impeller, or otherwise
physically altering the tested equipment
or test set-up such that the data
generated would no longer be reflective
of the pump model being tested. As
such, DOE does not believe that any
additional specifications or
clarifications regarding the BEP load
point are necessary in the pumps test
procedure.
Where:
wi = weighting at load point i (equal
weighting or 1⁄3 in this case),
Piin,m = measured or calculated driver power
input to the motor at load point i (hp),
and
i = load point at 75, 100, or 110 percent of
BEP flow as determined in accordance
with the DOE test procedure.
method C.2. For pumps sold with
motors not regulated by DOE’s electric
motor standards (excluding submersible
motors) that are equipped with either
continuous or non-continuous controls,
DOE also noted that only these testingbased methods (method C.2) would
apply, as is the case for pumps sold
with motors not regulated by DOE’s
electric motor standards (excluding
submersible motors) without controls
(discussed in section III.E.2.b). 80 FR
17586, 17627 (April 1, 2015).
For pumps sold with continuous
controls and motors that are (1)
regulated by DOE’s electric motor
standards for electric motors or (2)
submersible motors, the testing-based
approach discussed herein (method C.2)
would be optional, and such pumps
may also be tested under the
calculation-based approach, as
discussed in section III.E.1.c. Id.
Regarding the specific procedures
contained in the testing-based approach
for pumps sold with motors and
continuous or non-continuous controls,
DOE proposed that the PEIVL may be
determined by wire-to-water testing,
based on the procedure specified in HI
40.6, section 40.6.4.4, except that the
input power:
80 FR 17586, 17623 (April 1, 2015).
DOE received no comments on the
proposed testing-based approach for
pumps sold with motors and, as such,
is adopting the provisions discussed in
the April 2015 pumps test procedure
NOPR with no changes.
tkelley on DSK3SPTVN1PROD with RULES2
c. Testing-Based Test Method C.2: Pump
Sold With a Motor and Speed Controls
For pumps sold with non-continuous
control-equipped motors that are either
(1) regulated by DOE’s electric motor
standards for electric motors or (2)
submersible motors, as defined in
section III.E.1.c, DOE proposed in the
April 2015 pumps test procedure NOPR
that the calculation-based method C.1
would not be applicable because these
controls are not able to follow the
reference system curve described in
section III.E.1.c. Instead, pumps sold
with non-continuous controls would
have to be tested using the testing-based
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
b. Testing-Based Test Method B.2: Pump
Sold With a Motor
For pumps sold with motors that are
not regulated by DOE’s electric motor
PO 00000
Frm 00048
Fmt 4701
Sfmt 4700
standards (except for submersible
motors), DOE proposed that use of the
testing-based method B.2, discussed in
this section III.E.2.b, would be required
because the nominal full load efficiency
of the motor, as determined using a
specific standardized procedure, is not
available for those motors. For pumps
sold with motors subject to DOE’s
electric motor standards or submersible
motors, the testing-based approach
discussed in this section III.E.2.b would
be optional.
In the April 2015 pumps test
procedure NOPR, DOE also proposed
that, for pumps sold with motors, the
PEICL could be determined by wire-towater testing, as specified in HI 40.6–
2014, section 40.6.4.4. In this case, the
PERCL would become an average of the
measured power input to the motor at
the three specified load points, as
shown in equation (22):
• Is the ‘‘driver input power’’ defined
in table 40.6.2.1 of HI 40.6–2014 and
referenced in table 40.6.3.2.3, section
40.6.4.4, and section 40.6.6.2,
• refers to the input power to the
continuous or non-continuous control,
and
• is determined in accordance with
the tolerances and requirements for
measuring electrical power described in
section III.C.2.e.
80 FR 17623–24.
DOE clarified that, with the proposed
approach, pump manufacturers would
determine the BEP of the pump,
inclusive of motor and continuous or
non-continuous controls, as described
in section III.E.2.a, and then adjust the
operating speed of the motor and the
head until the specified head and flow
conditions are reached (i.e., 25, 50, and
75 percent of BEP flow and the
associated head pressures determined
by the reference system curve in section
III.E.1.c). To ensure this method C.2
results in consistent and repeatable
ratings, DOE also proposed tolerances
around each load point of 10 percent
about (i.e., above and below) the target
flow and head load points defined on
the reference system curve for each
pump. Similarly, DOE also proposed
that the measured data would be
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.021
4132
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
4133
specified by the reference system curve
using the following equation (23):
Where:
Pi = the corrected driver power input to the
continuous or non-continuous controls
at load point i (hp),
Hsp,i = the specified total system head at load
point i based on the reference system
curve (ft),68
HM,j = the measured total system head at load
point j (ft),
Qsp,i = the specified total system flow rate at
load point i based on the reference
system curve (gpm),
QM,j = the measured total system flow rate at
load point j (gpm),
PM,j = the measured shaft input power to the
bare pump at load point j,
i = specified load point at 25, 50, 75, or 100
percent of BEP flow as determined in
accordance with the DOE test procedure,
and
j = measured load point corresponding to
specified load point i.
Where:
wi = weighting at load point i (equal
weighting or 1⁄4 in this case),
Piin,c = measured or calculated driver power
input to the continuous or noncontinuous controls at load point i (hp),
and
i = load point at 25, 50, 75, or 100 percent
of BEP flow, as determined in
accordance with the DOE test procedure.
speed motors, that are not able to follow
the reference system curve directly at all
load points. For example, in the case of
a pump sold with a two-speed motor,
the pump will operate at full speed (i.e.,
the nominal speed) for some of the load
points and reduced speed at the other
load points, as shown in Figure III.2.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
HI 40.6–2014 provides a list of subscripts for use
in applying the HI 40.6–2014 test method.
Specifically, Table 40.6.2.2b defines the subscript
‘‘sp’’ as denoting ‘‘specified’’ values and the
subscript ‘‘M’’ as denoting measured values. For the
PO 00000
Frm 00049
Fmt 4701
Sfmt 4700
sake of clarity and continuity, in this final rule,
DOE is adopting subscripts consistent with the
defined HI nomenclature.
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.023
68 DOE notes that in the April 2015 pumps test
procedure NOPR, DOE proposed to define the
tested and ‘‘reference’’ head and flow values using
the subscript ‘‘T’’ for tested and ‘‘R’’ for rated (e.g.,
HR, HT, QR, QT). DOE notes that Table 40.6.2.2b of
Id. at 17625.
In the April 2015 pumps test
procedure NOPR proposal, DOE also
noted that some pumps are sold with
non-continuous controls, such as multi-
Id. at 17624–25.
Under DOE’s proposed approach, the
PER would become the mean of the
measured power input to the
continuous or non-continuous control at
the four specified load points based on
the assumed system curve (as in method
C.1), as shown in equation (24):
ER25JA16.022
tkelley on DSK3SPTVN1PROD with RULES2
extrapolated to the exact load points
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
For pumps sold with non-continuous
controls, DOE proposed to modify this
testing-based method C.2 for pumps
sold with motors and continuous or
non-continuous controls to specify that
the head measurements associated with
each of the specified flow points would
not have to be achieved within 10
percent of the specified head, as
described by the reference system
curve—only the flow rate would need to
be achieved within 10 percent of the
specified value. Id. at 17626. Instead,
DOE proposed to require that the
measured pump total head
corresponding to the 25, 50, 75 and 100
percent of BEP flow points could not be
lower than 10 percent below that
defined by referenced system curve.
DOE also proposed that, in this case, the
measured head and flow rate would not
be corrected to the reference system
curve. Instead, the tested load points
would be used directly in further
calculations of PEIVL. Id.
DOE requested comment on the
proposed testing-based method for
pumps sold with motors and continuous
or non-continuous controls, as well as
the proposed testing-based method for
determining the input power to the
pump for pumps sold with motors and
non-continuous controls. In addition,
DOE requested comment on any other
type of non-continuous control that may
be sold with a pump and for which the
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
proposed test procedure would not
apply.
HI commented that it agrees with the
optional testing-based methods, but also
indicated that any pump sold with an
ON/OFF control should be tested or
calculated using a PEICL method. (HI,
No. 8 at p. 23) DOE agrees with HI that
ON/OFF switches do not constitute a
type of continuous or non-continuous
control for which the calculation-based
or testing-based methods (C.1 and C.2,
respectively) or the PEIVL metric, would
be applicable. Consistent with the April
2015 pumps test procedure NOPR
section III.A.1.a and public meeting
slide 45, DOE has revised Table 1 in
appendix A accordingly to clarify that
(1) the calculation-based and testingbased methods to determine PEIVL
apply to pumps sold with motors and
continuous or non-continuous controls
only; whereas, (2) the test methods for
pumps sold with motors (methods B.1
and B.2) apply to pumps sold with
motors and controls other than
continuous and non-continuous
controls.
F. Representations of Energy Use and
Energy Efficiency
As noted previously, manufacturers of
any pumps within the scope of the
pump test procedure will be required to
use the test procedure established in
this rulemaking when making
representations about the energy
efficiency or energy use of their
PO 00000
Frm 00050
Fmt 4701
Sfmt 4700
equipment. Specifically, 42 U.S.C.
6314(d) provides that ‘‘[n]o
manufacturer . . . may make any
representation . . . respecting the
energy consumption of such equipment
or cost of energy consumed by such
equipment, unless such equipment has
been tested in accordance with such test
procedure and such representation
fairly discloses the results of such
testing.’’
In the April 2015 pumps test
procedure NOPR, DOE noted that
performing the proposed test procedure
for pumps requires a key component
(C-value) that is being addressed
through the parallel standards
rulemaking for pumps (Docket No.
EERE–2011–BT–STD–0031). 80 FR
17586, 17628 (April 1, 2015). Because of
this dependency, DOE clarified that
manufacturers of equipment that are
addressed by this test procedure and
any applicable standards that DOE may
set would have 180 days after the
promulgation of those standards to
begin using the DOE procedure.
With respect to representations,
generally, DOE stated its understanding
that manufacturers often make
representations (graphically or in
numerical form) of energy use metrics,
including pump efficiency, overall
(wire-to-water) efficiency, bowl
efficiency, driver power input, pump
power input (brake or shaft
horsepower), and/or pump power
output (hydraulic horsepower) and may
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.024
tkelley on DSK3SPTVN1PROD with RULES2
4134
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
make these representations at multiple
impeller trims, operating speeds, and
number of stages for a given pump. DOE
proposed in the April 2015 pumps test
procedure NOPR to allow manufacturers
to continue making these
representations. Id.
DOE also proposed that any
representations of PEI and PER must be
made in accordance with the DOE test
procedure, and there may only be one
PEI or PER representation for each basic
model. In other words, representations
of PEI and PER that differ from the full
impeller PEI and PER cannot be made
at alternate speeds, stages, or impeller
trims. Additionally, if the PEI and PER
for a basic model is rated using any
method other than method A.1, ‘‘bare
pump with default motor efficiency and
default motor part load loss curve,’’
such a basic model may not include
individual models with alternate stages
or impeller trims.
If a manufacturer wishes to make
unique representations of PEI or PER
based on a trimmed impeller, the
manufacturer must certify the trimmed
impeller as a separate basic model. In
such a case, the ‘‘trimmed impeller’’
being rated would become the ‘‘full
impeller’’ for the new basic model (i.e.,
the maximum diameter impeller
distributed in commerce for that pump
model) (see section III.A.1.c). 80 FR
17586, 17628 (April 1, 2015).
In response to DOE’s language
regarding representations in the April
2015 pumps test procedure NOPR, HI
stated its concern with the somewhat
vague language used around 42 U.S.C.
6314(d) prohibited representation. HI
emphasized that it is imperative that
pump manufacturers be allowed to
continue using pre-existing efficiency
curves and sizing software that is used
directly by end users and distributors to
purchase pumps. HI noted its
interpretation that the following text:
‘‘Manufacturers often make these
representations at multiple impeller
trims, operating speeds, and number of
stages for a given pump. DOE proposes
to allow manufacturers to continue
making these representations.’’ indicates
that existing performance and efficiency
data can continue to be used and that
only representations of PER and PEI fall
under [the requirements of] 42 U.S.C.
6314(d) ‘‘Prohibited Representation.’’ HI
requested that DOE clearly articulate in
the final rule that prohibited
representation under 42 U.S.C. 6314(d)
applies only to PER and PEI
representations. (HI, No. 8 at p. 1)
In response to HI’s comment
regarding the nature of representations
manufacturers are allowed to make
regarding the performance of their
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
equipment under 42 U.S.C. 6314(d),
DOE reiterates that, beginning 180 days
after publication of this final rule in the
Federal Register, all representations
regarding PERCL and PERVL must be
made in accordance with the DOE test
procedure. Similarly, all representations
regarding PEICL and PEIVL must be made
in accordance with the DOE test
procedure beginning 180 days after
publication of a final rule in the Federal
Register that sets C-values (i.e., a final
rule in the parallel energy conservation
standards rulemaking). However,
regarding other measures of energy use,
energy efficiency, or related
performance metrics for pumps, DOE
clarifies that such representations must
be made using methods that will
generate values consistent with the DOE
test procedure, as finalized in this final
rule. DOE acknowledges that
manufacturers have large amounts of
pre-existing data that they currently use
to market and make representations
about the performance of their
equipment and that regenerating all of
this data within the 180 day timeframe
would be burdensome. As such,
manufacturers may continue to use such
data to make representations about the
performance of applicable pump models
after the 180 day timeframe, provided
manufacturers are confident that the
values are consistent with those that
would be generated under the adopted
test procedure.
In the April 2015 NOPR public
meeting, the EEAs noted that it would
be helpful if DOE could have its
certification materials available prior to
the compliance date so that
manufacturers can make early
representations of PEI. (EEAs, NOPR
public meeting transcript, No. 7 at pp.
191–192) The EEAs also noted that it
would be helpful for all the fields in the
certification report to show up in the
database, or that they would determine
which items the utility programs would
need. (EEAs, NOPR public meeting
transcript, No. 7 at pp. 206–207) DOE
discusses compliance certification
reporting in the parallel energy
conservation standards rulemaking, and
has considered the stakeholder
comments in that rule.
G. Sampling Plans for Pumps
DOE provides in subpart B to 10 CFR
part 429 sampling plans for all covered
equipment. The purpose of these
sampling plans is to provide uniform
statistical methods for determining
compliance with prescribed energy
conservation standards and for making
representations of energy consumption
and energy efficiency on labels and in
other locations such as marketing
PO 00000
Frm 00051
Fmt 4701
Sfmt 4700
4135
materials. In the April 2015 pumps test
procedure NOPR, DOE proposed that,
for pumps, the same statistical sampling
plans used for other commercial and
industrial equipment would be
applicable and proposed to add the
sampling plan to 10 CFR 429.59. 80 FR
17586, 17628–29 (April 1, 2015).
Under the proposal, DOE proposed
that a sample of sufficient size must be
randomly selected and tested to ensure
compliance and that a minimum of two
units must be tested to certify a basic
model as compliant. DOE also proposed
to apply the same statistical sampling
procedures, including the confidence
limit and derating factor, that are
applicable to many other types of
commercial and industrial equipment,
as DOE believes equipment variability
and measurement repeatability
associated with the measurements
proposed for rating pumps are similar to
the variability and measurement
repeatability associated with energy
efficiency or consumption measurement
required for other commercial
equipment. Id.
Finally, DOE proposed that DOE
would determine compliance in an
enforcement matter based on the
arithmetic mean of a sample not to
exceed four units. Id.
DOE received no comments on this
proposal. However, upon reviewing the
April 2015 pump test procedure NOPR
proposals, DOE identified several
provisions that require clarification to
ensure that DOE’s certification and
enforcement provisions are clear and
consistent.
First, in the April 2015 pumps test
procedure NOPR, the equations for the
upper confidence limit (UCL) and lower
confidence limit (LCL) in section 429.60
both referenced a confidence limit of
0.95. 80 FR 17586, 17640 (April 1,
2015). However, the UCL and LCL were
proposed to be divided by a de-rating
factor of 1.01 and 0.99, respectively. Id.
DOE notes that the confidence limit of
the t-statistic and the de-rating factor in
the denominator, collectively, are
intended to capture the likely variability
in pump testing resulting from the
allowable test tolerances and instrument
accuracy (discussed in sections III.C),
lab-to-lab variability, and manufacturing
tolerances contained within each model.
In the April 2015 pumps test procedure
NOPR, DOE had proposed a confidence
limit of 99 percent, expecting a 95
percent confidence limit would exceed
the amount of variability in PEI that
would occur in pump ratings.
Specifically, because PEI is an indexed
value, with values that range from zero
to one, this decreases the amount of
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
4136
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
variability that may occur in each
individual measurement.
DOE received no comments from
interested parties in response to the
proposal in the April 2015 pumps test
procedure NOPR. However, DOE
reevaluated the April 2015 pumps test
procedure NOPR proposal and
determined that the resultant values
may yield overly conservative results
that would effectively require such
pumps to meet a more stringent
standard than that considered in the
associated pumps energy conservation
standards rule (Docket No. EERE–2011–
BT–STD–0031). Therefore, in this final
rule, DOE is correcting the confidence
limit and derating factor adopted in this
final rule to better reflect the likely
variability in test results expected to
result from the pumps test procedure,
lab-to-lab variability, and manufacturing
tolerances. Specifically, for the purpose
of regulating pumps, a confidence limit
of 0.95 and de-rating factor of 1.05 or
0.95 is required due to the combined
impacts of test tolerances, experimental
variability in conducting the test
procedure, and manufacturing
variability for this equipment. That is,
given the likely variation of measured
PEIs within a sample of pump units of
the same model, a confidence limit of
0.95 is necessary to ensure that the
statistical requirements in the sampling
plan for pumps are consistent with the
magnitude of the variance between
tested units within a sample resulting
from manufacturing tolerances and
experimental uncertainty inherent in
the test procedure. Therefore, DOE is
adopting a confidence limit of 0.95 and
de-rating factors of 1.05 and 0.95 as
applicable to pumps in this test
procedure final rule.
Also, regarding testing pumps for
enforcement purposes, DOE is
clarifying, in this final rule, the
procedure for determining BEP when
the ‘‘expected BEP’’ may not be known
to DOE. As discussed in section
III.C.2.d, the procedure for determining
BEP described in section 40.6.5.5.1 of HI
40.6–2014 requires that the flow points
are to be 40, 60, 75, 90, 100, 110, and
120 percent of the expected BEP of the
pump model and that if the BEP rate of
flow is displaced by more than 5
percent, the test must be repeated. In the
case of enforcement testing, DOE will
follow the same procedure as
manufacturers in determining the BEP
of the pump. In this final rule, DOE is
clarifying that DOE will use the volume
rate of flow (flow rate) at BEP and
nominal speed certified by the
manufacturer for that pump model as
the expected BEP when performing the
BEP test. In the case that the BEP rate
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
of flow is more than 5 percent displaced
from the certified value, DOE will also
retest the pump as required by the test
procedure. However, if the retested BEP
rate of flow is still more than 5 percent
displaced from the manufacturer’s
certified value, DOE will use the mean
of the tested values as the volume rate
of flow (flow rate) at BEP and nominal
speed in subsequent calculations when
determining the PEI for that model.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Order 12866
The Office of Management and Budget
(OMB) has determined that test
procedure rulemakings do not constitute
‘‘significant regulatory actions’’ under
section 3(f) of Executive Order 12866,
Regulatory Planning and Review, 58 FR
51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under
the Executive Order by the Office of
Information and Regulatory Affairs
(OIRA) in OMB.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601, et seq.) requires preparation
of a regulatory flexibility analysis for
any rule that by law must be proposed
for public comment, unless the agency
certifies that the rule, if promulgated,
will not have a significant economic
impact on a substantial number of small
entities. As required by Executive Order
13272, ‘‘Proper Consideration of Small
Entities in Agency Rulemaking,’’ 67 FR
53461 (August 16, 2002), DOE
published procedures and policies on
February 19, 2003, to ensure that the
potential impacts of its rules on small
entities are properly considered during
the DOE rulemaking process. 68 FR
7990. DOE has made its procedures and
policies available on the Office of the
General Counsel’s Web site: https://
energy.gov/gc/office-general-counsel.
DOE reviewed today’s final rule,
which establishes new test procedures
for pumps, under the provisions of the
Regulatory Flexibility Act and the
procedures and policies published on
February 19, 2003. DOE concludes that
the final rule DOE is adopting will not
result in a significant impact on a
substantial number of small entities.
The factual basis set forth in the
following sections.
1. The Need for, and Objectives of,
Today’s Rule
While DOE is currently evaluating
whether to establish energy
conservation standards for pumps, DOE
must first establish a test procedure that
PO 00000
Frm 00052
Fmt 4701
Sfmt 4700
measures the energy use, energy
efficiency, or estimated operating costs
of a given type of covered equipment
before establishing any new energy
conservation standards for that
equipment. See, generally, 42 U.S.C.
6295(r) and 6316(a). To fulfill these
requirements, DOE is establishing the
test procedure for pumps, described in
this final rule, concurrent with its
ongoing energy conservation standards
rulemaking for this equipment. See
Docket No. EERE–2011–BT–STD–0031.
In this test procedure, DOE prescribes
test methods for measuring the energy
consumption of certain pumps,
inclusive of motors and controls
(continuous or non-continuous), if they
are included with the pump when
distributed in commerce. In addition,
this final rule establishes a new subpart
Y to part 431 of Title 10 of the Code of
Federal Regulations that contains DOE’s
new test procedure for pumps, as well
as definitions pertinent to establishing
the scope of pumps to which the
adopted test procedure is applicable.
This final rule also contains sampling
plans for pumps for the purposes of
demonstrating compliance with any
energy conservation standards that DOE
adopts.
DOE’s test procedure contains
methods to determine the energy
consumption for all equipment for
which this test procedure applies using
either calculation-based methods and/or
testing-based methods. While both
methods include some amount of testing
and some amount of calculation, the
terms ‘‘calculation-based’’ and ‘‘testingbased’’ are used to distinguish between
methods in which the input power to
the pump is determined either by (a)
measuring the bare pump shaft input
power 69 and calculating efficiency, or
losses, of the motor and any continuous
control 70 (i.e., calculation-based
method) or (b) measuring the input
power to the driver,71 or motor, and any
continuous or non-continuous
controls 72 for a given pump directly
69 The term ‘‘pump shaft input power’’ is referred
to as ‘‘pump power input’’ in HI 40.6–2014. The
term ‘‘pump shaft input power’’ is used
synonymously with that term in this document.
70 DOE notes that for non-continuous controls, as
defined in section III.E.1.c, PEIVL can only be
determined using a ‘‘testing-based’’ method. If a
calculation-based method is desired, the pump
would instead be rated as a pump sold with a motor
and without speed controls using the PEICL metric.
See section III.E.1.c for further discussion.
71 The input power to the driver is referred to as
‘‘driver power input’’ in HI 40.6–2014. The term
‘‘input power to the driver’’ is used synonymously
with that term in this document.
72 In the case that a pump is sold with a motor
equipped with either continuous or non-continuous
controls and is rated using the testing-based
method, the input power to the pump would be
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
(i.e., testing-based method). As such, the
test procedure includes measurements
and calculations of the produced
hydraulic power, pump shaft input
power, electric input power to the
motor, and electrical input power to the
continuous or non-continuous controls,
as applicable, which are substantially
based on the test methods contained in
the industry test standard HI Standard
40.6–2014, ‘‘Methods for Rotodynamic
Pump Efficiency Testing,’’ (‘‘HI 40.6–
2014’’), with slight modifications as
noted in section III.C.2.
This test procedure final rule also
contains requirements regarding (1) the
characteristics, categories, and
configurations of pumps to which the
adopted test procedure is applicable; (2)
the specific manner in which pumps
must be tested to determine any
applicable representations regarding the
performance of pumps subject to the test
procedure; and (3) the number of pump
units that must be tested to determine
the representative value for each basic
model. As noted in the April 2015
pump test procedure NOPR and further
elaborated in section III.F, DOE’s new
pumps test procedure requires a key
component (C-value) that is being
addressed through the parallel
standards rulemaking for pumps
(Docket No. EERE–2011–BT–STD–
0031). 80 FR 17586, 17628 (April 1,
2015). As such, the use of this test
procedure as the basis for any
representations regarding the energy
efficiency or energy use of pumps
would not be required until 180 days
after the publication of any energy
conservation standards final rule in the
Federal Register, Therefore, DOE notes
that the test methods, definitions, and
sampling plans contained in this final
rule do not introduce any incremental
burden to any manufacturers, since the
use of such test methods is not required
by this test procedure final rule by itself.
That is, any burden associated with
testing pumps in accordance with the
requirements of this test procedure final
rule is not be required until the
promulgation of any energy
conservation standards final rule for
pumps. On this basis, DOE maintains
that this final rule has no incremental
burden associated with it and a final
regulatory flexibility analysis is not
required.
While DOE maintains that this final
rule has no incremental burden
associated with it when viewed as a
stand-alone rulemaking, DOE recognizes
that pump energy conservation
standards are currently being
determined as the input power to the continuous
or non-continuous control. See section III.E.2.c.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
considered in an associated rulemaking
(Docket No. EERE–2011–BT–STD–0031)
and may be proposed or promulgated in
the near future. Therefore, to consider
the aggregate impacts of developing
certified ratings for applicable pump
models for the purposes of making
representations regarding the energy use
of such equipment or certifying
compliance to DOE under any future
energy conservation standards, DOE is
also estimating the full burden of
conducting the testing required by this
test procedure final rule for each pump
model. Therefore, while such is not
required yet, DOE is presenting the
results from conducting the regulatory
flexibility analysis to develop estimates
of the costs associated with testing
equipment consistent with the
requirements of this test procedure final
rule, as would be required to certify
compliance with the potential energy
conservation standard. DOE presents the
results of such analysis in the following
sections.
However, DOE is not determining the
significance of that burden with respect
to manufacturers’ financial situation or
status as a small entity. As the use of the
testing requirements contained in this
final rule is contingent upon the energy
conservation standards rulemaking,
DOE is analyzing the effect of the
combined burden associated with both
the test procedure and energy
conservation standard rulemakings in
the manufacturer impact analysis
performed as part of the energy
conservation standard rulemaking (see
docket EERE–2011–BT–STD–0031). The
costs described in the following
subsections are referenced in the
manufacturer impact analysis in the
pumps energy conservation standard
rulemaking to estimate the burden
associated with testing. However, DOE
reiterates that the estimates provided in
this test procedure regulatory flexibility
analysis serve only to provide
information about the possible burden
manufacturers may incur while testing
pumps using this DOE test procedure;
they do not represent actual burden
incurred by the industry as there is no
incremental burden associated with this
test procedure final rule until and
unless the associated pumps energy
conservation standard final rule is
published.
2. Significant Issues From Interested
Parties in Response to IRFA
Within the April 2015 pumps test
procedure NOPR, DOE conducted an
initial regulatory flexibility analysis
(IRFA). 80 FR 17586, 17629–33 (April 1,
2015). In response to DOE’s April 2015
pumps test procedure NOPR estimate of
PO 00000
Frm 00053
Fmt 4701
Sfmt 4700
4137
testing burden, DOE received written
and verbal comments at the April 2015
NOPR public meeting, as well as
throughout the comment period.
Comments related to the potential
burden include comments related to
potential anticompetitive effects of the
proposed test procedure; cost of test
facility(s); labor costs; quantity of
manufacturers potentially affected; and
manufacturer sales to assess burden. In
this final rule, DOE addresses these
comments and presents a revised
assessment of potential burden related
to test procedure final rule.
Anticompetitive Effects of Burden and
Expense
Consistent with DOE’s requirements
to comply with section 32(c) of the
Federal Energy Administration Act of
1974, as amended by the Federal Energy
Administration Authorization Act of
1977 (15 U.S.C. 788; see section IV.L),
DOE is required to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (FTC)
concerning the impact of the proposed
test procedure on competition in the
pumps industry. The U.S. Department
of Justice (DOJ) reviewed the April 2015
pumps test procedure NOPR, attended
the April 2015 NOPR public meeting,
and consulted with members of the
industry in preparing their comments
and conclusions regarding any
anticompetitive effects of the pumps test
procedure. In response to the proposed
test procedure, DOJ commented that it
is not able to determine whether or not
the proposed test procedure (or
associated energy conservation
standard) will lessen competition
within the industry. However, DOJ
noted that it is concerned about the
possibility of anticompetitive effects
resulting from the burden and expense
of compliance. (DOJ, No. 14 at p. 2)
In this final rule, DOE reviews the
potential burden and expense related to
testing, but does not analyze the
potential effects on competition.
However, DOE notes that it has taken
steps, in the test procedure adopted in
this final rule to minimize burden on
manufacturers related to testing and
rating equipment in accordance with
such procedures.
Burden of Test Facility(s)
In the April 2015 pumps test
procedure NOPR, DOE estimated the
burden to manufacturers associated
with performing testing in accordance
with the proposed test procedure. 80 FR
17586, 17629–33 (April 1, 2015). DOE
estimated that in order to determine the
performance of any covered pump
models for the purposes of making
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
4138
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
representations or certifying compliance
under any future energy conservation
standards for pumps, each manufacturer
would have to either (a) have the units
tested in-house or (b) have the units
tested at a third party testing facility. In
addition, if the manufacturer elected to
test pumps in-house, each manufacturer
would have to undertake the following
burden-inducing activities:
(1) Construct and maintain a test
facility that is capable of testing pumps
in compliance with the test procedure,
including acquisition and calibration of
any necessary measurement equipment,
and
(2) conduct the DOE test procedure on
two units of each covered pump model.
Id.
Because pumps are newly regulated
equipment and there are no existing
testing requirements for pumps, the
capabilities of existing testing facilities
may vary widely from one manufacturer
to another. In the April 2015 pumps test
procedure NOPR, DOE based it’s
assessment of testing burden on the
conservative assumption that pump
manufacturers would have no existing
testing infrastructure and would have to
bear the full cost of constructing a new
testing facility generally capable of
conducting testing in accordance with
the proposed test procedure. DOE
estimated the capital cost of
constructing the two types of facilities:
A facility equipped to perform the
calculation-based test methods
(described in section, III.E.1), which
varied between $91,000 and $277,000,
and a facility equipped to perform the
testing-based test methods (described in
section, III.E.2), which varied between
$72,000 and $213,000. DOE amortized
these capital costs to determine an
annual payment amount over an
estimated 7-year loan period because
DOE’s research indicated this was the
typical loan period for pump
manufacturers. DOE’s final calculations
regarding the cost of constructing a test
lab assumed that the majority of pump
models would be certified based on the
bare pump configuration and
subsequent ratings for the same bare
pump sold with any number of
applicable motors and continuous
controls could be generated using the
calculation-based approach. In addition,
DOE estimated the ongoing cost of
testing between $161.61 and $430.96
per unit, plus calibration activities of
$1,241.67 per year. 80 FR 17586, 17632
(April 1, 2015) Based on these
assumptions, DOE estimated the
amortized total burden associated with
the test procedure ranged between
$61,000 and $221,000 annually for
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
small manufacturers affected by this
rule. Id.
DOE requested specific comments and
feedback on a number of assumptions
made in the April 2015 pumps test
procedure NOPR regulatory flexibility
analysis. Regarding the cost of
constructing a test facility capable of
performing the test procedure presented
in the April 2015 pumps test procedure
NOPR, HI stated that the estimates of
materials and costs to build a pump
testing facility as presented are greatly
underestimated and would be in excess
of $1 million. HI indicated that DOE’s
facility description leaves out many
expensive machines and other
equipment that would be required for
this testing. (HI, No. 0008 at pp. 24–25)
DOE disagrees with the comments
from HI regarding the cost of the testing
facility and the effect of burden on
manufacturers and the industry. DOE
notes that, in the April 2015 pumps test
procedure NOPR initial regulatory
flexibility analysis (IRFA), DOE used the
most burdensome assumptions to
estimate the burden associated with
complying with the test procedure,
resulting in estimates lower than the $1
million HI suggested. DOE notes that the
estimated costs in the IRFA were based
on the construction of a facility capable
of conducting the DOE test procedure
for pumps within the scope of the
rulemaking. Because of a lack of
information on existing testing facilities
in the industry, as well as the potential
variability in the capabilities of these
existing facilities, DOE assumed that no
manufacturers would have existing test
capabilities and all manufacturers
would have to construct new test
laboratories in order to comply with the
test procedure. DOE also assumed in the
IRFA that no third party laboratories
were available to conduct testing in
accordance with the DOE test
procedure. 80 FR 17586, 17631 (April 1,
2015).
DOE recognizes that many pump
manufacturers already have pump test
facilities and conduct pump testing as
part of an existing manufacturing
quality control process, to develop
pump performance information for new
and existing products, and to
demonstrate the performance of specific
pump units for customers. As such, for
the purposes of estimating testing
burden associated with this test
procedure final rule, DOE has revised
the baseline assumptions regarding the
existing test lab capabilities of
manufacturers and has estimated the
incremental burden associated with just
those test procedure requirements that
would not typically exist in current
manufacturer facilities. DOE describes
PO 00000
Frm 00054
Fmt 4701
Sfmt 4700
these updated assumptions and analysis
in section IV.B.3.
Regarding the capabilities of existing
test laboratories, HI commented that it
disagrees with DOE’s assumption in the
NOPR that the use of a non-calibrated
test motor and VFD with a torque meter
would be the most common and least
costly approach for testing bare pumps
in accordance with the proposed DOE
test procedure. (HI, No. 0008 at p. 24)
Additionally, HI noted that it did not
find anything in the NOPR preamble
that mentions recertification
requirements. (HI, No. 0008 at p. 25)
DOE acknowledges comments from HI
on the underestimated cost estimates to
build a pump testing facility and
suggestions of components. DOE
disagrees with HI that a VFD control
would not be the most common
approach for testing pumps in
accordance with the DOE test
procedure. DOE conducted a literature
search for pump configurations and
determined that almost all controls
available to be paired with pumps are
VFD controls. DOE also reiterates that
the estimates used in the IRFA were not
meant to be the least costly for
manufacturers. The cost estimates for
constructing a test facility were meant to
be the most burdensome on
manufacturers to show the most costly
approach to building a test facility. DOE
acknowledges the comment from HI
regarding recertification requirements
and clarifies that the estimates for
recertification requirements in the April
2015 pumps test procedure NOPR IRFA
are for pumps which have been
redesigned to capture market
preferences or other customer
requirements. DOE estimates that 10
percent of basic models per
manufacturer will be redesigned and
tested each year, and the Department
has included the costs of testing newly
redesigned pumps in this DOE test
procedure final rule regulatory
flexibility analysis (see section IV.B.3).
To further clarify these costs, DOE has
removed the terminology used in the
April 2015 pumps test procedure NOPR
IRFA regarding recertification that was
unclear. Instead, in this final rule, DOE
uses redesigned and tested to refer to
pumps that would require new
certifications each year, as their energy
performance will have changed as a
result of the equipment redesign. DOE
notes that only those pump models for
which the energy consumption
characteristics have changed necessitate
a new basic model certification and that
pump models whose energy
consumption characteristics have not
changed do not need to be recertified.
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
HI agreed that, for most pump models,
only physical testing of the underlying
bare pump model is required, and
subsequent rating for that bare pump
sold with a motor or motor and
continuous control can be based on
calculations only. (HI, No. 0008 at p. 24)
HI also stated that all pumps listed
within the scope as outlined in the term
sheet can be evaluated in accordance
with the methodology described in the
April 2015 pumps test procedure NOPR
if the corrected equation presented by
DOE at the April 29, 2015 public
meeting is used. (HI, No. 0008 at p. 24)
HI stated that it could not comment on
the number of pump models per
manufacturer that would be required to
use the test (wire-to-water) method to
certify pump performance based on a
lack of data, but stated that 100 percent
of pumps would need to be tested to
certify because of the new testing
requirements and sampling provisions.
(HI, No. 0008 at p. 25)
DOE appreciates the comment from
HI that only physical testing of the
underlying bare pump is required and
that subsequent configurations can be
based on calculations. DOE agrees with
HI that 100 percent of pumps would
need to be tested to certify compliance
with a proposed PEI standard, if
adopted in a standards final rule. This
is true for PEICL and PEIVL because these
values cannot be calculated without the
finalized C-Values from the energy
conservation standards rulemaking. In
addition, the PERCL and PERVL metrics
contain specific assumptions regarding
the representative performance of
pumps and pump components that are
not part of the industry’s current test
methods. However, as noted in section
III.F, DOE recognizes that manufacturers
already make some representations
regarding the performance of relevant
pumps (e.g., pump efficiency, BEP
efficiency, and pump total head or
volume rate of flow (flow rate) at BEP
and full impeller) based on testing using
test standards consistent with or similar
to HI 40.6–2014, which DOE is
incorporating by reference as the basis
for the DOE test procedure. As such,
DOE notes that, while all PEICL, PEIVL,
PERCL, and PERVL ratings must be
newly-generated, some existing test data
that were collected consistent with the
methods DOE is incorporating by
reference into the DOE test procedure
may be used, provided manufacturers
are confident any such values are
equivalent to those that would be
generated using the new DOE test
procedure.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
Quantity of Manufacturers Potentially
Affected
To calculate the burden associated
with testing pumps on aper
manufacturer or per model basis, DOE
collected information on the number of
manufacturers in the pumps industry,
and the numbers of models per
manufacturer. DOE then focused this
analysis on the small entities as part of
the regulatory flexibility analysis. To
determine which pump manufacturers
were small entities, DOE referenced the
Small Business Administration (SBA)
size threshold for ‘‘Pump and Pumping
Equipment Manufacturing’’ (North
American Industry Classification
System code 333911).73 The SBA sets a
threshold of 500 employees or less for
an entity to be considered as a small
business for this category, as established
at 13 CFR 121.201.
In the April 2015 pumps test
procedure NOPR, DOE conducted a
focused inquiry into small business
manufacturers of equipment covered by
this rulemaking. DOE identified 68
distinct manufacturers of covered pump
products sold in the U.S. DOE then
analyzed those 68 to determine which
would be considered a small business.
After removing entities that are foreign
owned or operated, DOE determined
that there were 25 small businesses in
the analysis. These 25 companies
represent 29 percent of pump
manufacturers with facilities in the
United States. 80 FR 17586, 17629
(April 1, 2015).
In response to DOE’s assessment of
the number of small manufacturers
subject to the pumps test procedure
rule, HI commented that the HI
organization currently has 106 member
companies (pump manufacturers and
associate members) and is aware of
more entities within the market. HI
believes that the identification of 68
distinct pump manufacturers in the U.S.
is low. (HI, No. at pp. 23–24)
DOE appreciates the comment from
HI that there are more manufacturers in
the pump manufacturing industry that
are not included in this analysis. DOE
notes that although HI might have
associate members, if the member does
not manufacture a pump, the associate
member is not part of the analysis.
During its market survey, DOE used
available public information to identify
potential small manufacturers. DOE’s
research involved the review of
individual company Web sites and
marketing research tools (e.g., Dun and
Bradstreet reports, Manta, Hoovers) to
create a list of companies that
73 See https://www.sba.gov/sites/default/files/files/
Size_Standards_Table.pdf.
PO 00000
Frm 00055
Fmt 4701
Sfmt 4700
4139
manufacture pumps covered by this
rulemaking. DOE also contacted HI to
obtain information about pump
manufacturing companies that
participate in the national association.
DOE identified 86 potential businesses
of covered pump products sold in the
U.S., but reduced that number to 68 by
determining which businesses were
located in the United States. From these
manufacturers, DOE eliminated 29 from
the analysis because they had more than
500 employees. DOE removed an
additional 16 manufacturers because
they either had foreign parent
companies or had domestic parent
companies with 500 or more employees.
After removing entities that are foreign
owned or operated, DOE determined
that there were 25 small businesses to
investigate for this analysis. The
regulatory flexibility analysis
investigated manufacturers who
manufacture pumps within the scope of
this rulemaking, are considered a small
business according to SBA standards,
and are not foreign-owned or operated.
Thus, there are fewer manufacturers
analyzed in the regulatory flexibility
analysis than are present in the
industry.
In summary, DOE agrees with HI that
68 distinct manufacturers is low on an
industry-wide basis, but that is because
the number was reduced by other
criteria before being presented in the
April 2015 pumps test procedure NOPR.
DOE notes that HI is not disagreeing
with DOE’s assessment of the quantity
of small businesses, but rather the
potential size of total pump
manufacturers in the U.S. Following the
April 2015 pumps test procedure NOPR,
DOE has not identified any more (or
different) manufacturers that meet the
criteria (domestic headquarters, not
owned by another entity, meets the SBA
threshold of 500 employees or fewer) to
be considered a small business.
Therefore, in this final rule, DOE
maintains the quantity of 25 small
businesses for purposes of analyzing the
potential burden. Within the 25 small
businesses, DOE has, however,
identified an additional manufacturer
that produces pumps that are within the
scope of this rulemaking and have
included this manufacturer in this DOE
pumps test procedure final rule
regulatory flexibility analysis (raising
the total from 15 to 16).
Manufacturer Sales To Assess Burden
In the April 2015 pumps test
procedure NOPR, DOE used average
sales to assist in assessing the potential
burden. 80 FR 17586, 17629 (April 1,
2015). HI commented that it has no
alternative to offer other than using the
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
4140
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
average sales, but noted that it does not
understand what DOE is presenting in
Table IV.2 [of the April 2015 pumps test
procedure NOPR]. (HI, No. 0008 at p.
25)
DOE agrees with HI that there is no
better alternative to using average sales
as the financial indicator for assessing
the burden on manufacturers. DOE
notes that Table IV.2 in the April 2015
pumps test procedure NOPR displays
the results of the initial regulatory
flexibility analysis. 80 FR 17586, 17633
(April 1, 2015). The columns indicate
the range of number of employees in
each row; the number of small
businesses within each employee size
range; the average number of basic
models produced by manufacturers in
each employee size range; and the
average sales of the manufacturers in
each employee size range as determined
from available data sources. Using the
estimated potential testing burden,
number of basic models, and the average
annual sales, DOE determined the
potential burden as a percentage of sales
of each group of small businesses (as
defined by ranges of numbers of
employees). Because DOE maintains
that this final rule has no incremental
burden associated with it when viewed
as a stand-alone rulemaking, DOE is
only presenting the estimates of the
costs associated with testing equipment
consistent with the requirements of this
test procedure final rule, as would be
required to certify compliance with
potential energy conservation standards.
As such, this table of impacts on
manufacturers as a result of conducting
this test procedure is no longer included
in this regulatory flexibility analysis.
HI commented that there will be a
significant burden on both small and
large entities and believes that this
estimated value would vary depending
on the size of the pump manufacturer.
(HI, No. 0008 at pp. 25–26)
DOE agrees that the estimated burden
may vary based on the size of the
manufacturers if energy conservation
standards are promulgated. DOE only
considered the aggregate effects on
small manufacturers of developing
certified ratings for applicable pump
models for the purposes of making
representations regarding the energy use
of such equipment or certifying
compliance to DOE under any future
energy conservation standards. The
estimated burden of conducting the
DOE test procedure presented in the
April 2015 pumps test procedure NOPR
showed that, as the number of
employees increased, so did the number
of basic models and average sales. As a
result, as the number of employees
increased, the average estimated burden,
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
as a percentage of average annual sales,
decreased. Based on this analysis, it is
likely that the burden may vary based
on the size of manufacturer.
DOE cannot confirm HI’s comment
that there will be a significant burden
on large manufacturers because the
regulatory flexibility analysis aims to
assess whether there is a significant
economic impact on a substantial
number of small entities. DOE did not
assess the impact of the rule on large
entities. However, DOE notes that the
parallel energy conservation standards
rulemaking includes a full manufacturer
impact analysis (Docket No. EERE–
2011–BT–STD–0031).
3. Revised Assessment of Burden
Associated With This Test Procedure
Final Rule
In the initial regulatory flexibility
analysis portion of the April 2015
pumps test procedure NOPR, DOE
estimated the most burdensome costs
for manufacturers to conduct the DOE
test procedure. In the initial regulatory
flexibility analysis DOE recognized that,
because testing is not currently required
or standardized, testing facilities may
vary widely from one pump
manufacturer to another. For the
purposes of estimating testing burden in
the initial regulatory flexibility analysis,
DOE estimated the burden associated
with a situation where a given pump
manufacturer did not have existing test
facilities at all and would be required to
construct such facilities to test
equipment in accordance with the test
procedure. In light of comments
received regarding the burden
associated with testing, DOE revised the
analysis and gathered additional
information to better characterize the
expected burden associated with testing
basic models in accordance with the
DOE test procedure.
DOE is analyzing the effect of the
combined burden associated with both
the test procedure and energy
conservation standards rulemakings in
the manufacturer impact analysis
performed as part of the energy
conservation standards rulemaking (see
docket EERE–2011–BT–STD–0031). The
costs described in the following
subsection are referenced in the
manufacturer impact analysis in the
pumps energy conservation standards
rulemaking to estimate the burden
associated with testing. However, DOE
reiterates that the estimates provided
serve only to provide information about
the possible burden manufacturers may
incur while testing pumps using this
DOE test procedure; they do not
represent actual burden incurred by the
industry as there is no incremental
PO 00000
Frm 00056
Fmt 4701
Sfmt 4700
burden associated with this test
procedure final rule until and unless the
associated pumps energy conservation
standards final rule is published.
The DOE test procedure will require
pump manufacturers to conduct the
calculation-based method or the testingbased method, depending on the type
and configuration of the pump(s) being
tested. DOE is adopting the less
burdensome calculation-based test
method as the required test method for
bare pumps, and as optional test
methods for pumps other than bare
pumps. This includes pumps sold with
motors that are covered by DOE’s
electric motor energy conservation
standards or submersible motors and
pumps sold with either of these two
motor styles that are also sold with
continuous controls (see section III.E for
a more thorough description of the
applicability of the calculation-based
approach to different pump
configurations). DOE is also requiring
that manufacturers use a testing-based
method where pumps are sold either
with motors that are not covered by
DOE’s electric motor energy
conservation standards (except
submersible motors) or with noncontinuous controls.
Both the calculation-based method
and the testing-based method require
physical testing of pumps at some level
and, as such, utilize a similar basic
testing facility. DOE recognizes that all
manufacturers, regardless of HI
membership, have access to test
facilities to be able to produce pump
curves that characterize the performance
of their equipment. As such, DOE
estimated that all manufacturers would
be able to conduct the DOE test
procedure in an available test facility.
Sixteen of 25 small manufacturers
identified in DOE’s survey of
manufacturers produce pumps that fall
within the scope of this rulemaking and
would be required to perform testing;
the other 9 produce pump types that are
not within the scope of pumps for
which this test procedure is applicable.
Of the 16 manufacturers that produce
pumps within the scope of this
rulemaking, 8 are members of HI
according to their listing on HI’s Web
site.74
As member companies of HI, DOE
assumes that manufacturers with pumps
within the scope of this test procedure
would test pumps in accordance with
HI’s most current industry testing
standards. That is, DOE assumes that
manufacturers that are HI members
already conduct testing in accordance
74 See https://www.pumps.org/member_
companies.aspx.
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
with HI 40.6–2014. In HI 40.6–2014,
manufacturers are required to test their
pumps in an ISO 9906 Grade 2B test
facility, which is the same grade test
facility prescribed in HI 14.6–2011.
Because the calculation-based method
described in this test procedure is
equivalent to HI 40.6–2014, as
recommended by the Working Group,
manufacturers who are members of HI
would already be capable of testing
pumps in accordance to the testingbased method in this test procedure.
There is no incremental cost to calibrate
measurement instrumentation for these
manufacturers because HI 40.6–2014
prescribes calibration intervals for all
instruments in the test facility. The
testing-based method in this test
procedure requires electrical
measurement equipment capable of
measuring true RMS current, true RMS
voltage, and real power up to at least the
40th harmonic of fundamental supply
source frequency with an accuracy level
of ±2.0 percent of full scale when
measured at the fundamental supply
source frequency, as discussed in
section III.C.2.e. Electrical equipment
accuracy of ±2.0 percent of reading is
consistent with the value specified in
section 40.6.3.2.3 of HI 40.6–2014.
Therefore, the is no incremental cost to
conduct testing for HI member
companies when testing pumps
pursuant to the testing-based method or
the calculation-based method.
Manufacturers who are not members
of HI need to purchase electrical
measurement equipment with ±2.0
percent accuracy to conduct the testingbased method of the DOE test
procedure. DOE determined that the
average cost of such equipment is
approximately $5,218.42 based on a
review of available products on the
market. Unlike the manufacturers who
are HI members, the non-HI
manufacturers may not perform regular
equipment calibration and, as such, will
incur an additional cost to calibrate the
instruments in the test facility. DOE
assumed that each testing facility would
need to calibrate the instrumentation
used in the test loop as specified in HI
40.6–2014 appendix D. The flowmeter,
torque sensor, and power quality meter
all should be calibrated once a year. The
pressure transducer should be calibrated
every 4 months and a laser tachometer
should be calibrated every 3 years.
These calibrations, together, cost a
manufacturer about $1,241.67 per year.
DOE analyzed the estimated burden
for 7 years for the 16 small
manufacturers that produce pumps
within the scope of the DOE test
procedure. DOE used an analysis period
of 7 years based on the assumption that
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
the machinery qualifies for a 7-year
depreciation schedule under the
Modified Accelerated Cost Recovery
System (MACRS).75 The average, and
representative, of the likely burden to
manufacturers is $6,334 for the capital
costs associated with constructing a test
facility capable of conducting the DOE
test procedure. This burden ranges
between $0 and $12,668.
Both methods of the test procedure
require test personnel to set up,
conduct, and remove each pump in
accordance with that procedure. DOE
estimated the cost of labor using the
median hourly wage of $41.44 for the
overall category of an engineer.76
Including fringe benefits, which are
estimated to be nominally 30 percent of
total compensation, the total hourly cost
to an employer is estimated to be
$53.87.77
Based on conversations with test
engineers, DOE estimates it would take
between 1 and 2 hours of an engineer’s
time to complete the test procedure per
unit tested, which would result in a cost
of $53.87 to $107.74 per unit based on
an engineer’s labor rate of $53.87 per
hour. DOE estimates that setting up and
removing the pumps from the test stand
would require 2 to 6 hours of the
engineer’s time depending on the size of
the pump and any other fittings that
need to be configured to enable testing,
resulting in a cost between $107.74 to
$323.22 per unit based on the labor rate
of $53.87 per hour for an engineer. The
total cost of testing a pump, including
setup, tests, and takedown ranges
between $161.61 and $430.96 per unit.
DOE estimates that the time required to
conduct the calculation-based method
of test would be the same as the time
required to conduct the test-based
method (wire-to-water test).
DOE also estimates that pump
manufacturers would redesign covered
pump models or introduce new pump
models each year. As such, DOE
estimates that a certain portion of the
pump models that a given pump
manufacturer offers for sale would need
to be tested each year. DOE estimates
that approximately 10 percent of
manufacturers’ unique pump models
would need to be tested each year.
75 Department of the Treasury, Internal Revenue
Service. How to Depreciate Property. IRS Pub. 926.
76 U.S. Department of Labor, Bureau of Labor
Statistics. 2012. National Occupational
Employment and Wage Estimates. Washington, DC
Available at https://www.bls.gov/oes/2012/may/oes_
nat.htm#17-0000.
77 U.S. Department of Labor, Bureau of Labor
Statistics. 2014. Employer Costs for Employee
Compensation—Management, Professional, and
Related Employees. Washington, DC Available at:
https://www.bls.gov/news.release/pdf/ecec.pdf.
PO 00000
Frm 00057
Fmt 4701
Sfmt 4700
4141
DOE amortized the capital costs
against the recurring burden of testing
pumps described in this analysis for
each small manufacturer identified to
produce pumps covered under the
scope of the DOE test procedure. DOE
notes that the labor component
represents the majority of the overall
cost associated with testing, while the
much more variable capital costs are
only 23 percent of the total test cost.
The representative amortized burden for
testing each unit of a basic model is
$561.16. As discussed in the sampling
provisions in section III.G, this test
procedure will require manufacturers to
test at least two units of each pump
basic model to develop a certified
rating. This results in an average cost of
$1,122.32 to test two units of each basic
model.
While analyzing the potential burdens
of testing pumps in-house, DOE
recognized that the price per basic
model was higher for some
manufacturers than for others. For
manufacturers with higher costs of
testing per basic model may elect to
send their pumps to a third-party test
facility to mitigate these costs. DOE
anticipates that third party testing
facilities will update their test facilities
to be able to provide testing for pump
manufacturers in accordance with the
DOE test procedure. Based on market
research and discussions with third
party test lab personnel, DOE estimates
that testing pumps in a third party test
facility according to the DOE test
procedure will cost approximately
$2,500 per unit.
4. Calculator Comments
Wilo indicated that one problem is
that DOE is not responsible for
providing tools to determine
compliance, so each manufacturer
would be responsible for creating its
own potentially erroneous evaluation
tool. (Wilo, No. 0044 at p. 3–4) HI
requested that DOE share the latest
version of the PEI calculator with the
pump industry as an easy means of
determining whether their products fall
within or outside the scope of the
efficiency levels specified in the
rulemaking. (HI, No. 0002 at p. 1) HI
also requested that DOE provide a PEI
calculator so that all calculations for PEI
are performed exactly the same way by
all members of the pump industry,
government agencies and interested
parties. (HI, No. 0007 at p. 2) HI
commented that the calculator could be
used to report data to interested
utilities. (HI, No. 0007 at p. 10) HI also
commented that the complexity of the
rating systems will cause a significant
burden on all manufacturers to develop
E:\FR\FM\25JAR2.SGM
25JAR2
4142
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
a tool which quickly evaluates product.
This is even more important for small
and medium-sized companies that may
not have the resources to develop such
an analytic tool on their own. (HI, No.
0008 at p. 2)
In response to the comments
submitted by Wilo and HI, DOE made
the PEI calculator available on the
pumps test procedure rulemaking Web
site.78 Under the provisions in this
pumps test procedure final rule, the PEI
calculations must be performed using
measured values—that is, using results
from testing actual pumps in accordance
with the proposed test method and
sampling plan. The PEI calculator
provided to the public is not considered
an Alternative Efficiency Determination
Method (AEDM) by the Department and
is not to be used to simulate or estimate
the efficiency of a pump. DOE has
provided this ‘‘calculator’’ as a
convenience at the request of interested
parties. DOE notes that manufacturers
should consult section III.B of this final
rule and the adopted regulatory text at
10 CFR 431.464 and appendix A of
subpart Y for the formulas for
calculating PEI and should not rely on
this spreadsheet. DOE also notes that
while this calculator is an excel-based
version of the calculations in the test
procedure proposal, DOE did not rely
on this document to develop the
proposal itself.
Based on the estimates presented,
DOE believes that the test procedure
amendments will not have a significant
economic impact on a substantial
number of small entities, and the
preparation of a final regulatory
flexibility analysis is not required. DOE
will transmit the certification and
supporting statement of factual basis to
the Chief Counsel for Advocacy of the
Small Business Administration for
review under 5 U.S.C. 605(b).
C. Review Under the Paperwork
Reduction Act of 1995
All collections of information from
the public by a Federal agency must
receive prior approval from OMB. DOE
has established regulations for the
certification and recordkeeping
requirements for covered consumer
products and industrial equipment. 10
CFR part 429, subpart B. DOE published
a NOPR proposing energy conservation
standards for pumps on April 24, 2015.
80 FR 22938. In an application to renew
the OMB information collection
approval for DOE’s certification and
recordkeeping requirements, DOE
78 https://www1.eere.energy.gov/buildings/
appliance_standards/product.aspx/productid/
44#testprocedures.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
included an estimated burden for
manufacturers of pumps in case DOE
ultimately sets energy conservation
standards for this equipment. OMB has
approved the revised information
collection for DOE’s certification and
recordkeeping requirements. 80 FR 5099
(January 30, 2015). In the April 2015
pumps test procedure NOPR, DOE
estimated that it will take each
respondent approximately 30 hours
total per company per year to comply
with the certification and recordkeeping
requirements based on 20 hours of
technician/technical work and 10 hours
clerical work to actually submit the
Compliance and Certification
Management System templates. 80 FR
17586, 17633 (April 15, 2015).
In response to DOE’s April 2015
pump test procedure NOPR, HI
commented that the hours shown are
low and will vary by the number of
basic models covered. (HI, No. at p. 26)
DOE appreciates the comment
submitted by HI regarding the burden
estimate to comply with the proposed
recordkeeping requirements. DOE
recognizes that recordkeeping burden
may vary substantially based on
company preferences and practices as
well as the number of basic models each
manufacturer will test. However, DOE
maintains that, on average, it will take
manufacturers approximately 30 hours
to comply with the certification and
recordkeeping requirements. In
addition, DOE notes that, while this test
procedure rulemaking includes
recordkeeping requirements that are
associated with executing and
maintaining the test data for this
equipment, the certification
requirements would be established in a
final rule establishing energy
conservation standards for pumps.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE amends its test
procedure for pumps. DOE has
determined that this rule falls into a
class of actions that are categorically
excluded from review under the
National Environmental Policy Act of
1969 (42 U.S.C. 4321 et seq.) and DOE’s
implementing regulations at 10 CFR part
1021. Specifically, this rule amends an
existing rule without affecting the
amount, quality or distribution of
energy usage, and, therefore, will not
PO 00000
Frm 00058
Fmt 4701
Sfmt 4700
result in any environmental impacts.
Thus, this rulemaking is covered by
Categorical Exclusion A5 under 10 CFR
part 1021, subpart D, which applies to
any rulemaking that interprets or
amends an existing rule without
changing the environmental effect of
that rule. Accordingly, neither an
environmental assessment nor an
environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999), imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have Federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have Federalism implications. On
March 14, 2000, DOE published a
statement of policy describing the
intergovernmental consultation process
it will follow in the development of
such regulations. 65 FR 13735. DOE
examined this final rule and determined
that it will not have a substantial direct
effect on the States, on the relationship
between the national government and
the States, or on the distribution of
power and responsibilities among the
various levels of government. EPCA
governs and prescribes Federal
preemption of State regulations as to
energy conservation for the products
that are the subject of this final rule.
States can petition DOE for exemption
from such preemption to the extent, and
based on criteria, set forth in EPCA. (42
U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
requires that Executive agencies make
every reasonable effort to ensure that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, this final rule
meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
regulatory action resulting in a rule that
may cause the expenditure by State,
local, and Tribal governments, in the
aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR
12820; also available at https://
energy.gov/gc/office-general-counsel.
DOE examined this final rule according
to UMRA and its statement of policy
and determined that the rule contains
neither an intergovernmental mandate
nor a mandate that may result in the
expenditure of $100 million or more in
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
any year, so these requirements do not
apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
final rule will not have any impact on
the autonomy or integrity of the family
as an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights’’ 53 FR 8859
(March 18, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). DOE has reviewed
this final rule under the OMB and DOE
guidelines and has concluded that it is
consistent with applicable policies in
those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB a Statement
of Energy Effects for any significant
energy action. A ‘‘significant energy
action’’ is defined as any action by an
agency that promulgated or is expected
to lead to promulgation of a final rule,
and that: (1) Is a significant regulatory
action under Executive Order 12866, or
any successor order; and (2) is likely to
have a significant adverse effect on the
supply, distribution, or use of energy; or
(3) is designated by the Administrator of
OIRA as a significant energy action. For
any significant energy action, the agency
must give a detailed statement of any
PO 00000
Frm 00059
Fmt 4701
Sfmt 4700
4143
adverse effects on energy supply,
distribution, or use if the regulation is
implemented, and of reasonable
alternatives to the action and their
expected benefits on energy supply,
distribution, and use.
This regulatory action is not a
significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; FEAA) Section 32 essentially
provides in relevant part that, where a
proposed rule authorizes or requires use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (FTC)
concerning the impact of the
commercial or industry standards on
competition.
The final rule incorporates by
reference the testing methods contained
in HI 40.6–2014, ‘‘Methods for
Rotodynamic Pump Efficiency Testing,’’
except section 40.6.5.3, ‘‘Test report;’’
section A.7, ‘‘Testing at temperatures
exceeding 30 °C (86 14;°F);’’ and
appendix B, ‘‘Reporting of test results.’’
In addition, the final rule’s definitions
incorporate by reference the following
standards:
(1) Sections 1.1, ‘‘types and
nomenclature,’’ and 1.2.9, ‘‘rotodynamic
pump icons,’’ of the 2014 version of
ANSI/HI 1.1–1.2–2014, ‘‘American
National Standard for Rotodynamic
Centrifugal Pumps for Nomenclature
and Definitions;’’
(2) section 2.1, ‘‘types and
nomenclature,’’ of the 2014 version of
ANSI/HI 2.1–2.2, ‘‘American National
Standard for Rotodynamic Vertical
Pumps of Radial, Mixed, and Axial
Flow Types for Nomenclature and
Definitions.’’
(3) FM Class Number 1319, ‘‘Approval
Standard for Centrifugal Fire Pumps
E:\FR\FM\25JAR2.SGM
25JAR2
4144
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
(Horizontal, End Suction Type),’’
approved January 2015.
(4) NFPA 20–2016, ‘‘Standard for the
Installation of Stationary Pumps for Fire
Protection,’’ approved 2016.
(5) ANSI/UL 448–2013, ‘‘Standard for
Safety Centrifugal Stationary Pumps for
Fire-Protection Service,’’ approved
2013.
While this test procedure is not
exclusively based on these industry
testing standards, some components of
the DOE test procedure adopt
definitions, test parameters,
measurement techniques, and
additional calculations from them
without amendment. The Department
has evaluated these industry testing
standards and is unable to conclude
whether they would fully comply with
the requirements of section 32(b) of the
FEAA, (i.e., that they were developed in
a manner that fully provides for public
participation, comment, and review).
DOE has consulted with both the
Attorney General and the Chairman of
the FTC about the impact on
competition of using the methods
contained in this standard, as well as
the effects of the rule in general, if
promulgated. Regarding any impact on
competition that the adopted test
procedure may have, the DOJ reviewed
the April 2015 pumps test procedure
NOPR, attended the April 2015 NOPR
public meeting, and consulted with
members of the industry in preparing
their comments and conclusions
regarding any anticompetitive effects of
the pumps test procedure. In response
to the proposed test procedure, DOJ
commented that it is not able to
determine whether or not the proposed
test procedure (or associated energy
conservation standard) will lessen
competition within the industry.
However, DOJ noted that it is concerned
about the possibility of anticompetitive
effects resulting from the burden and
expense of compliance. (DOJ, No. 14 at
p. 2) In response to DOJ’s concern
regarding the burden of conducting the
test procedure, DOE has revised several
of the requirements, which DOE
believes will mitigate DOJ’s (and
manufacturers’) concerns. DOE
addresses these concerns regarding the
burden related to testing pumps in
accordance with the test procedure in
section IV.B.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of this rule before its effective date. The
report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
N. Description of Materials Incorporated
by Reference
In this final rule, DOE is incorporating
by reference specific sections from a
method of test published by HI, titled
‘‘Methods for Rotodynamic Pump
Efficiency Testing.’’ Specifically, the
test procedure codified by this final rule
references HI 40.6–2014, except section
40.6.5.3, ‘‘Test report;’’ section A.7,
‘‘Testing at temperatures exceeding 30
°C (86 °F);’’ and appendix B, ‘‘Reporting
of test results.’’ HI 40.6–2014 is an
industry-accepted standard used to
specify methods of testing for
determining the head, flow rate, pump
power input, driver power input, pump
power output, and other relevant
parameters necessary to determine the
PEICL or PEIVL of applicable pumps, as
described in this final rule.
In addition, the final rule’s definitions
incorporate by reference the following
sections of the following standards:
(1) Sections 1.1, ‘‘types and
nomenclature,’’ and 1.2.9, ‘‘rotodynamic
pump icons,’’ of the 2014 version of
ANSI/HI 1.1–1.2–2014, ‘‘American
National Standard for Rotodynamic
Centrifugal Pumps for Nomenclature
and Definitions;’’ and
(2) section 2.1, ‘‘types and
nomenclature,’’ of the 2014 version of
ANSI/HI 2.1–2.2, ‘‘American National
Standard for Rotodynamic Vertical
Pumps of Radial, Mixed, and Axial
Flow Types for Nomenclature and
Definitions.’’
(3) FM Class Number 1319, ‘‘Approval
Standard for Centrifugal Fire Pumps
(Horizontal, End Suction Type),’’
approved January 2015.
(4) NFPA 20–2016, ‘‘Standard for the
Installation of Stationary Pumps for Fire
Protection,’’ approved 2015.
(5) ANSI/UL 448–2013, ‘‘Standard for
Safety Centrifugal Stationary Pumps for
Fire-Protection Service,’’ ANSI
approved 2013.
ANSI/HI 1.1–1.2–2014 and ANSI/HI
2.1–2.2–2014 describe and define
specific pump characteristics relevant to
the differentiation of pump categories
and configurations when applying the
DOE test procedure. The FM, NFPA,
and ANSI/UL standards describe the
relevant technical characteristics and
testing requirements to certify certain
pumps as fire pumps.
Copies of all HI standards may be
purchased from the Hydraulic Institute
at 6 Campus Drive, First Floor North,
Parsippany, NJ, 07054–4406, or by going
to www.pumps.org.
Copies of FM Class Number 1319 can
be obtained from: FM Global, 1151
Boston-Providence Turnpike, P.O. Box
9102, Norwood, MA 02062, (781) 762–
4300. www.fmglobal.com.
PO 00000
Frm 00060
Fmt 4701
Sfmt 4700
Copies of NFPA 20–2016 can be
obtained from: the National Fire
Protection Association, 1 Batterymarch
Park, Quincy, MA 02169, (617) 770–
3000. www.nfpa.org.
Copies of ANSI/UL 448–2013 can be
obtained from: UL, 333 Pfingsten Road,
Northbrook, IL 60062, (847) 272–8800.
https://ul.com.
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
List of Subjects
10 CFR Part 429
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Imports, Intergovernmental relations,
Small businesses.
10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Imports, Incorporation by reference,
Intergovernmental relations, Small
businesses.
Issued in Washington, DC, on December
30, 2015.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
For the reasons stated in the
preamble, DOE amends parts 429 and
431 of Chapter II, subchapter D of Title
10, Code of Federal Regulations as set
forth below:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
2. In § 429.2 revise paragraph (a) to
read as follows:
■
§ 429.2
Definitions.
(a) The definitions found in §§ 430.2,
431.2, 431.62, 431.72, 431.82, 431.92,
431.102, 431.132, 431.152, 431.172,
431.192, 431.202, 431.222, 431.242,
431.262, 431.282, 431.292, 431.302,
431.322, 431.442 and 431.462 of this
chapter apply for purposes of this part.
*
*
*
*
*
§ 429.11
[Amended]
3. In paragraphs (a) and (b) remove
‘‘429.54’’ and add ‘‘429.62’’ in its place.
■ 4. Add § 429.59 to read as follows:
■
E:\FR\FM\25JAR2.SGM
25JAR2
¯
and x is the sample mean; n is the
number of samples; and xi is the
maximum of the ith sample;
Or,
(B) The upper 95 percent confidence
limit (UCL) of the true mean divided by
1.05, where:
¯
and x is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.95 is the t
statistic for a 95 percent one-tailed
confidence interval with n–1 degrees of
freedom (from appendix A of subpart B).
(b) [Reserved]
§ 429.70
§ 429.71
tkelley on DSK3SPTVN1PROD with RULES2
¯
and x is the sample mean; n is the
number of samples; and xi is the
maximum of the ith sample;
Or,
(B) The lower 95 percent confidence
limit (LCL) of the true mean divided by
0.95, where:
Maintenance of records.
*
*
*
*
*
(d) When considering if a pump is
subject to energy conservation standards
under part 431 of this chapter, DOE may
need to determine if a pump was
designed and constructed to the
requirements set forth in Military
Specifications: MIL–P–17639F, MIL–P–
17881D, MIL–P–17840C, MIL–P–
18682D, or MIL–P–18472G. In this case,
a manufacturer must provide DOE with
copies of the original design and test
data that were submitted to appropriate
design review agencies, as required by
MIL–P–17639F, MIL–P–17881D, MIL–
P–17840C, MIL–P–18682D, or MIL–P–
18472G. Military specifications and
standards are available for review at
https://everyspec.com/MIL-SPECS.
§ 429.72
[Amended]
7. Amend § 429.72(a) by removing
‘‘429.54’’ and adding in its place
‘‘429.62’’.
■
§ 429.102
¯
and x is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.95 is the t
statistic for a 95 percent one-tailed
confidence interval with n–1 degrees of
freedom (from appendix A to subpart B
of part 429);
and
(ii) Any measure of energy efficiency
of a basic model must be less than or
equal to the lower of:
(A) The mean of the sample, where:
[Amended]
5. Amend § 429.70(a) by removing
‘‘429.54’’ and adding ‘‘429.62’’ in its
place.
■ 6. In § 429.71, add paragraph (d) to
read as follows:
■
[Amended]
8. Amend § 429.102(a)(1) by removing
‘‘429.54’’ and adding in its place
‘‘429.62’’.
■ 9. Section 429.110 is amended by:
■ a. Redesignating paragraphs (e)(1)(iv)
through (vi) as (e)(1)(v) through (vii),
respectively; and
■ b. Adding a new paragraph (e)(1)(iv).
The addition reads as follows:
■
§ 429.110
Enforcement testing.
*
*
*
*
*
(e) * * *
(1) * * *
(iv) For pumps, DOE will use an
initial sample size of not more than four
units and will determine compliance
based on the arithmetic mean of the
sample.
*
*
*
*
*
■ 10. Section 429.134 is amended by
adding paragraph (h) to read as follows:
§ 429.134 Product-specific enforcement
provisions.
*
*
*
*
*
(h) Pumps. (1) The volume rate of
flow (flow rate) at BEP and nominal
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00061
Fmt 4701
Sfmt 4700
speed of rotation of each tested unit of
the basic model will be measured
pursuant to the test requirements of
§ 431.464 of this chapter, where the
value of volume rate of flow (flow rate)
at BEP and nominal speed of rotation
certified by the manufacturer will be
treated as the expected BEP flow rate.
The results of the measurement(s) will
be compared to the value of volume rate
of flow (flow rate) at BEP and nominal
speed of rotation certified by the
manufacturer. The certified volume rate
of flow (flow rate) at BEP and nominal
speed of rotation will be considered
valid only if the measurement(s) (either
the measured volume rate of flow (flow
rate) at BEP and nominal speed of
rotation for a single unit sample or the
average of the measured flow rates for
a multiple unit sample) is within five
percent of the certified volume rate of
flow (flow rate) at BEP and nominal
speed of rotation.
(i) If the representative value of
volume rate of flow (flow rate) at BEP
and nominal speed of rotation is found
to be valid, the measured volume rate of
flow (flow rate) at BEP and nominal
speed of rotation will be used in
subsequent calculations of constant load
pump energy rating (PERCL) and
constant load pump energy index
(PEICL) or variable load pump energy
rating (PERVL) and variable load pump
energy index (PEIVL) for that basic
model.
(ii) If the representative value of
volume rate of flow (flow rate) at BEP
and nominal speed of rotation is found
to be invalid, the mean of all the
measured volume rate of flow (flow rate)
at BEP and nominal speed of rotation
values determined from the tested
unit(s) will serve as the new expected
BEP flow rate and the unit(s) will be
retested until such time as the measured
volume rate of flow (flow rate) at BEP
and nominal speed of rotation is within
5 percent of the expected BEP flow rate.
(2) DOE will test each pump unit
according to the test method specified
by the manufacturer in the certification
report submitted pursuant to
§ 429.59(b).
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
11. The authority citation for part 431
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
12. Add subpart Y to part 431 to read
as follows:
■
Subpart Y—Pumps
Sec.
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.028
Pumps.
(a) Determination of represented
value. Manufacturers must determine
the represented value, which includes
the certified rating, for each basic model
by testing (which includes the
calculation-based methods in the test
procedure), in conjunction with the
following sampling provisions.
Manufacturers must update represented
values to account for any change in the
applicable motor standards in § 431.25
of this chapter and certify amended
values as of the next annual
certification.
(1) Units to be tested. The
requirements of § 429.11 are applicable
to pumps; and for each basic model, a
sample of sufficient size shall be
randomly selected and tested to ensure
that—
(i) Any value of the constant or
variable load pump energy index or
other measure of energy consumption
must be greater than or equal to the
higher of:
(A) The mean of the sample, where:
ER25JA16.026 ER25JA16.027
§ 429.59
4145
ER25JA16.025
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
4146
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
431.461 Purpose and scope.
431.462 Definitions.
431.463 Materials incorporated by
reference.
431.464 Test procedure for measuring and
determining energy consumption of
pumps.
Appendix A to Subpart Y of Part 431—
Uniform Test Method for the
Measurement of Energy Consumption of
Pumps
Subpart Y—Pumps
§ 431.461
Purpose and scope.
This subpart contains definitions, test
procedures, and energy conservation
requirements for pumps, pursuant to
Part A–1 of Title III of the Energy Policy
and Conservation Act, as amended, 42
U.S.C. 6311–6317.
tkelley on DSK3SPTVN1PROD with RULES2
§ 431.462
Definitions.
The following definitions are
applicable to this subpart, including
appendix A. In cases where there is a
conflict, the language of the definitions
adopted in this section takes precedence
over any descriptions or definitions
found in the 2014 version of ANSI/HI
1.1–1.2, ‘‘American National Standard
for Rotodynamic Centrifugal Pumps for
Nomenclature and Definitions’’ (ANSI/
HI 1.1–1.2–2014) (incorporated by
reference, see § 431.463), or the 2014
version of ANSI/HI 2.1–2.2, ‘‘American
National Standard for Rotodynamic
Vertical Pumps of Radial, Mixed, and
Axial Flow Types for Nomenclature and
Definitions’’ (ANSI/HI 2.1–2.2–2014)
(incorporated by reference, see
§ 431.463). In cases where definitions
reference design intent, DOE will
consider marketing materials, labels and
certifications, and equipment design to
determine design intent.
Bare pump means a pump excluding
mechanical equipment, driver, and
controls.
Basic model means all units of a given
class of pump manufactured by one
manufacturer, having the same primary
energy source, and having essentially
identical electrical, physical, and
functional (or hydraulic) characteristics
that affect energy consumption, energy
efficiency, water consumption, or water
efficiency; except that:
(1) For RSV and ST pumps, all
variations in numbers of stages of the
bare pump must be considered a single
basic model;
(2) Pump models for which the bare
pump differs in impeller diameter, or
impeller trim, may be considered a
single basic model; and
(3) Pump models for which the bare
pump differs in number of stages or
impeller diameter and which are sold
with motors (or motors and controls) of
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
varying horsepower may only be
considered a single basic model if:
(i) for ESCC, ESFM, IL, and RSV
pumps, each motor offered in the basic
model has a nominal full load motor
efficiency rated at the Federal minimum
(see the current table for NEMA Design
B motors at 10 CFR 431.25) or the same
number of bands above the Federal
minimum for each respective motor
horsepower (see Table 3 of Appendix A
to Subpart Y of Part 431); or
(ii) for ST pumps, each motor offered
in the basic model has a full load motor
efficiency at the default nominal full
load submersible motor efficiency
shown in Table 2 of appendix A to
subpart Y of part 431 or the same
number of bands above the default
nominal full load submersible motor
efficiency for each respective motor
horsepower (see Table 3 of Appendix A
to Subpart Y of Part 431).
Best efficiency point (BEP) means the
pump hydraulic power operating point
(consisting of both flow and head
conditions) that results in the maximum
efficiency.
Bowl diameter means the maximum
dimension of an imaginary straight line
passing through and in the plane of the
circular shape of the intermediate bowl
of the bare pump that is perpendicular
to the pump shaft and that intersects the
outermost circular shape of the
intermediate bowl of the bare pump at
both of its ends, where the intermediate
bowl is as defined in ANSI/HI 2.1–2.2–
2014.
Clean water pump means a pump that
is designed for use in pumping water
with a maximum non-absorbent free
solid content of 0.016 pounds per cubic
foot, and with a maximum dissolved
solid content of 3.1 pounds per cubic
foot, provided that the total gas content
of the water does not exceed the
saturation volume, and disregarding any
additives necessary to prevent the water
from freezing at a minimum of 14 °F.
Close-coupled pump means a pump
in which the motor shaft also serves as
the impeller shaft for the bare pump.
Continuous control means a control
that adjusts the speed of the pump
driver continuously over the driver
operating speed range in response to
incremental changes in the required
pump flow, head, or power output.
Control means any device that can be
used to operate the driver. Examples
include, but are not limited to,
continuous or non-continuous controls,
schedule-based controls, on/off
switches, and float switches.
Driver means the machine providing
mechanical input to drive a bare pump
directly or through the use of
mechanical equipment. Examples
PO 00000
Frm 00062
Fmt 4701
Sfmt 4700
include, but are not limited to, an
electric motor, internal combustion
engine, or gas/steam turbine.
Dry rotor pump means a pump in
which the motor rotor is not immersed
in the pumped fluid.
End suction close-coupled (ESCC)
pump means a close-coupled, dry rotor,
end suction pump that has a shaft input
power greater than or equal to 1 hp and
less than or equal to 200 hp at BEP and
full impeller diameter and that is not a
dedicated-purpose pool pump.
Examples include, but are not limited
to, pumps within the specified
horsepower range that comply with
ANSI/HI nomenclature OH7, as
described in ANSI/HI 1.1–1.2–2014.
End suction frame mounted/own
bearings (ESFM) pump means a
mechanically-coupled, dry rotor, end
suction pump that has a shaft input
power greater than or equal to 1 hp and
less than or equal to 200 hp at BEP and
full impeller diameter and that is not a
dedicated-purpose pool pump.
Examples include, but are not limited
to, pumps within the specified
horsepower range that comply with
ANSI/HI nomenclature OH0 and OH1,
as described in ANSI/HI 1.1–1.2–2014.
End suction pump means a singlestage, rotodynamic pump in which the
liquid enters the bare pump in a
direction parallel to the impeller shaft
and on the side opposite the bare
pump’s driver-end. The liquid is
discharged through a volute in a plane
perpendicular to the shaft.
Fire pump means a pump that is
compliant with NFPA 20–2016
(incorporated by reference, see
§ 431.463), ‘‘Standard for the
Installation of Stationary Pumps for Fire
Protection,’’ and is either:
(1) UL listed under ANSI/UL 448–
2013 (incorporated by reference, see
§ 431.463), ‘‘Standard for Safety
Centrifugal Stationary Pumps for FireProtection Service,’’ or
(2) FM Global (FM) approved under
the January 2015 edition of FM Class
Number 1319, ‘‘Approval Standard for
Centrifugal Fire Pumps (Horizontal, End
Suction Type),’’ (incorporated by
reference, see § 431.463).
Full impeller diameter means the
maximum diameter impeller with
which a given pump basic model is
distributed in commerce.
Horizontal motor means a motor that
requires the motor shaft to be in a
horizontal position to function as
designed, as specified in the
manufacturer literature.
In-line (IL) pump means a pump that
is either a twin-head pump or a singlestage, single-axis flow, dry rotor,
rotodynamic pump that has a shaft
E:\FR\FM\25JAR2.SGM
25JAR2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
input power greater than or equal to 1
hp and less than or equal to 200 hp at
BEP and full impeller diameter, in
which liquid is discharged through a
volute in a plane perpendicular to the
shaft. Such pumps do not include
pumps that are mechanically coupled or
close-coupled, have a pump power
output that is less than or equal to 5 hp
at BEP at full impeller diameter, and are
distributed in commerce with a
horizontal motor. Examples of in-line
pumps include, but are not limited to,
pumps within the specified horsepower
range that comply with ANSI/HI
nomenclature OH3, OH4, or OH5, as
described in ANSI/HI 1.1–1.2–2014.
Magnet driven pump means a pump
in which the bare pump is isolated from
the motor via a containment shell and
torque is transmitted from the motor to
the bare pump via magnetic force. The
motor shaft is not physically coupled to
the impeller or impeller shaft.
Mechanical equipment means any
component of a pump that transfers
energy from the driver to the bare pump.
Mechanically-coupled pump means a
pump in which the bare pump has its
own impeller shaft and bearings and so
does not rely on the motor shaft to serve
as the impeller shaft.
Non-continuous control means a
control that adjusts the speed of a driver
to one of a discrete number of noncontinuous preset operating speeds, and
does not respond to incremental
reductions in the required pump flow,
head, or power output.
Prime-assist pump means a pump
that:
(1) Is designed to lift liquid that
originates below the centerline of the
pump inlet;
(2) Requires no manual intervention
to prime or re-prime from a dry-start
condition; and
(3) Includes a device, such as a
vacuum pump or air compressor and
venturi eductor, to remove air from the
suction line in order to automatically
perform the prime or re-prime function
at any point during the pump’s
operating cycle.
Pump means equipment designed to
move liquids (which may include
entrained gases, free solids, and totally
dissolved solids) by physical or
mechanical action and includes a bare
pump and, if included by the
manufacturer at the time of sale,
mechanical equipment, driver, and
controls.
Radially split, multi-stage, vertical, inline diffuser casing (RSV) pump means
a vertically suspended, multi-stage,
single axis flow, dry rotor, rotodynamic
pump:
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
(1) That has a shaft input power
greater than or equal to 1 hp and less
than or equal to 200 hp at BEP and full
impeller diameter and at the number of
stages required for testing and
(2) In which liquid is discharged in a
place perpendicular to the impeller
shaft; and
(3) For which each stage (or bowl)
consists of an impeller and diffuser;
(4) For which no external part of such
a pump is designed to be submerged in
the pumped liquid; and
(5) Examples include, but are not
limited to, pumps complying with
ANSI/HI nomenclature VS8, as
described in ANSI/HI 2.1–2.2–2014.
Rotodynamic pump means a pump in
which energy is continuously imparted
to the pumped fluid by means of a
rotating impeller, propeller, or rotor.
Self-priming pump means a pump
that:
(1) Is designed to lift liquid that
originates below the centerline of the
pump inlet;
(2) Contains at least one internal
recirculation passage; and
(3) Requires a manual filling of the
pump casing prior to initial start-up, but
is able to re-prime after the initial startup without the use of external vacuum
sources, manual filling, or a foot valve.
Single axis flow pump means a pump
in which the liquid inlet of the bare
pump is on the same axis as the liquid
discharge of the bare pump.
Submersible turbine (ST) pump
means a single-stage or multi-stage, dry
rotor, rotodynamic pump that is
designed to be operated with the motor
and stage(s) fully submerged in the
pumped liquid; that has a shaft input
power greater than or equal to 1 hp and
less than or equal to 200 hp at BEP and
full impeller diameter and at the
number of stages required for testing;
and in which each stage of this pump
consists of an impeller and diffuser, and
liquid enters and exits each stage of the
bare pump in a direction parallel to the
impeller shaft. Examples include, but
are not limited to, pumps within the
specified horsepower range that comply
with ANSI/HI nomenclature VS0, as
described in ANSI/HI 2.1–2.2–2014.
Twin head pump means a dry rotor,
single-axis flow, rotodynamic pump that
contains two impeller assemblies,
which both share a common casing,
inlet, and discharge, and each of which
(1) Contains an impeller, impeller
shaft (or motor shaft in the case of closecoupled pumps), shaft seal or packing,
driver (if present), and mechanical
equipment (if present);
(2) Has a shaft input power that is
greater than or equal to 1 hp and less
PO 00000
Frm 00063
Fmt 4701
Sfmt 4700
4147
than or equal to 200 hp at best efficiency
point (BEP) and full impeller diameter;
(3) Has the same primary energy
source (if sold with a driver) and the
same electrical, physical, and functional
characteristics that affect energy
consumption or energy efficiency;
(4) Is mounted in its own volute; and
(5) Discharges liquid through its
volute and the common discharge in a
plane perpendicular to the impeller
shaft.
§ 431.463 Materials incorporated by
reference.
(a) General. DOE incorporates by
reference the following standards into
subpart Y of part 431. The material
listed has been approved for
incorporation by reference by the
Director of the Federal Register in
accordance with 5 U.S.C. 552(a) and 1
CFR part 51. Any subsequent
amendment to a standard by the
standard-setting organization will not
affect the DOE test procedures unless
and until amended by DOE. Material is
incorporated as it exists on the date of
the approval and a notice of any change
in the material will be published in the
Federal Register. All approved material
is available for inspection at the
National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: www.archives.gov/federal_
register/code_of_federal_regulations/
ibr_locations.html. Also, this material is
available for inspection at U.S.
Department of Energy, Office of Energy
Efficiency and Renewable Energy,
Building Technologies Program, Sixth
Floor, 950 L’Enfant Plaza SW.,
Washington, DC 20024, (202) 586–2945,
or go to: https://www1.eere.energy.gov/
buildings/appliance_standards. These
standards can be obtained from the
sources below.
(b) FM. FM Global, 1151 BostonProvidence Turnpike, P.O. Box 9102,
Norwood, MA 02062, (781) 762–4300.
www.fmglobal.com.
(1) FM Class Number 1319, ‘‘Approval
Standard for Centrifugal Fire Pumps
(Horizontal, End Suction Type),’’
January 2015, IBR approved for
§ 431.462.
(2) [Reserved]
(c) HI. Hydraulic Institute, 6 Campus
Drive, First Floor North, Parsippany, NJ
07054–4406, 973–267–9700.
www.Pumps.org.
(1) ANSI/HI 1.1–1.2–2014, (‘‘ANSI/HI
1.1–1.2–2014’’), ‘‘American National
Standard for Rotodynamic Centrifugal
Pumps for Nomenclature and
Definitions,’’ approved October 30,
2014, section 1.1, ‘‘Types and
E:\FR\FM\25JAR2.SGM
25JAR2
4148
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
nomenclature,’’ and section 1.2.9,
‘‘Rotodynamic pump icons,’’ IBR
approved for § 431.462.
(2) ANSI/HI 2.1–2.2–2014, (‘‘ANSI/HI
2.1–2.2–2014’’), ‘‘American National
Standard for Rotodynamic Vertical
Pumps of Radial, Mixed, and Axial
Flow Types for Nomenclature and
Definitions,’’ approved April 8, 2014,
section 2.1, ‘‘Types and nomenclature,’’
IBR approved for § 431.462.
(3) HI 40.6–2014, (‘‘HI 40.6–2014’’),
‘‘Methods for Rotodynamic Pump
Efficiency Testing,’’ (except section
40.6.5.3, ‘‘Test report;’’ Appendix A,
section A.7, ‘‘Testing at temperatures
exceeding 30 °C (86 °F);’’ and Appendix
B, ‘‘Reporting of test results
(normative);’’) copyright 2014, IBR
approved for appendix A to subpart Y
of part 431.
(d) NFPA. National Fire Protection
Association, 1 Batterymarch Park,
Quincy, MA 02169–7471, (617) 770–
3000. www.nfpa.org.
(1) NFPA 20, (‘‘NFPA 20–2016’’),
‘‘Standard for the Installation of
Stationary Pumps for Fire Protection,’’
2016 Edition, approved June 15, 2015,
IBR approved for § 431.462.
(2) [Reserved]
(e) UL. UL, 333 Pfingsten Road,
Northbrook, IL 60062, (847) 272–8800.
ul.com.
(1) UL 448, (‘‘ANSI/UL 448–2013’’),
‘‘Standard for Safety Centrifugal
Stationary Pumps for Fire-Protection
Service,’’ 10th Edition, June 8, 2007,
including revisions through July 12,
2013, IBR approved for § 431.462.
(2) [Reserved]
§ 431.464 Test procedure for measuring
and determining energy consumption of
pumps
(a) Scope. This section provides the
test procedures for determining the
constant and variable load pump energy
index for:
(1) The following categories of clean
water pumps:
(i) End suction close-coupled (ESCC);
(ii) End suction frame mounted/own
bearings (ESFM);
(iii) In-line (IL);
(iv) Radially split, multi-stage,
vertical, in-line casing diffuser (RSV);
and
(v) Submersible turbine (ST) pumps
(2) With the following characteristics:
(i) Flow rate of 25 gpm or greater at
BEP and full impeller diameter;
(ii) Maximum head of 459 feet at BEP
and full impeller diameter and the
number of stages required for testing
(see section 1.2.2 of appendix A of this
subpart);
(iii) Design temperature range from 14
to 248 °F;
(iv) Designed to operate with either:
(1) a 2- or 4-pole induction motor, or (2)
a non-induction motor with a speed of
rotation operating range that includes
speeds of rotation between 2,880 and
4,320 revolutions per minute and/or
1,440 and 2,160 revolutions per minute,
and in either case, the driver and
impeller must rotate at the same speed;
(v) For ST pumps, a 6-inch or smaller
bowl diameter; and
(vi) For ESCC and ESFM pumps, a
specific speed less than or equal to 5000
when calculated using U.S. customary
units.
(3) Except for the following pumps:
(i) Fire pumps;
(ii) Self-priming pumps;
(iii) Prime-assist pumps;
(iv) Magnet driven pumps;
(v) Pumps designed to be used in a
nuclear facility subject to 10 CFR part
50, ‘‘Domestic Licensing of Production
and Utilization Facilities;’’ and
(vi) Pumps meeting the design and
construction requirements set forth in
Military Specifications: MIL–P–17639F,
‘‘Pumps, Centrifugal, Miscellaneous
Service, Naval Shipboard Use’’ (as
amended); MIL–P–17881D, ‘‘Pumps,
Centrifugal, Boiler Feed, (Multi-Stage)’’
(as amended); MIL–P–17840C, ‘‘Pumps,
Centrifugal, Close-Coupled, Navy
Standard (For Surface Ship
Application)’’ (as amended); MIL–P–
18682D, ‘‘Pump, Centrifugal, Main
Condenser Circulating, Naval
Shipboard’’ (as amended); and MIL–P–
18472G, ‘‘Pumps, Centrifugal,
Condensate, Feed Booster, Waste Heat
Boiler, And Distilling Plant’’ (as
amended). Military specifications and
standards are available for review at
https://everyspec.com/MIL-SPECS.
(b) Testing and calculations.
Determine the applicable constant load
pump energy index (PEICL) or variable
load pump energy index (PEIVL) using
the test procedure set forth in appendix
A of this subpart Y.
Appendix A to Subpart Y of Part 431—
Uniform Test Method for the
Measurement of Energy Consumption of
Pumps
Note: Starting on July 25, 2016, any
representations made with respect to the
energy use or efficiency of pumps subject to
testing pursuant to 10 CFR 431.464 must be
made in accordance with the results of
testing pursuant to this appendix.
I. Test Procedure for Pumps
A. General. To determine the constant load
pump energy index (PEICL) for bare pumps
and pumps sold with electric motors or the
variable load pump energy index (PEIVL) for
pumps sold with electric motors and
continuous or non-continuous controls,
perform testing in accordance with HI 40.6–
2014, except section 40.6.5.3, ‘‘Test report;’’
section A.7, ‘‘Testing at temperatures
exceeding 30 °C (86 °F);’’ and appendix B,
‘‘Reporting of test results;’’ (incorporated by
reference, see § 431.463) with the
modifications and additions as noted
throughout the provisions below. Where HI
40.6–2014 refers to ‘‘pump,’’ the term refers
to the ‘‘bare pump,’’ as defined in § 431.462.
Also, for the purposes of applying this
appendix, the term ‘‘volume per unit time,’’
as defined in section 40.6.2, ‘‘Terms and
definitions,’’ of HI 40.6–2014 shall be
deemed to be synonymous with the term
‘‘flow rate’’ used throughout that standard
and this appendix. In addition, the
specifications of section 40.6.4.1 of HI 40.6–
2014 do not apply to ST pumps and the
performance of ST bare pumps considers the
bowl performance only.
A.1 Scope. Section II of this appendix is
applicable to all pumps and describes how to
calculate the pump energy index (section
II.A) based on the pump energy rating for the
minimally compliant reference pump
(PERSTD; section II.B) and the constant load
pump energy rating (PERCL) or variable load
pump energy rating (PERVL) determined in
accordance with one of sections III through
VII of this appendix, based on the
configuration in which the pump is
distributed in commerce and the applicable
testing method specified in sections III
through VII and as described in Table 1 of
this appendix.
tkelley on DSK3SPTVN1PROD with RULES2
TABLE 1—APPLICABILITY OF CALCULATION-BASED AND TESTING-BASED TEST PROCEDURE OPTIONS BASED ON PUMP
CONFIGURATION
Pump
configuration
Pump sub-configuration
Bare Pump ...........................
Bare Pump ......................................................................
OR
Pump + Single-Phase Induction Motor ...........................
OR
Pump + Driver Other Than Electric Motor ......................
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00064
Fmt 4701
Applicable test methods
Sfmt 4700
Section III: Test Procedure for Bare Pumps.
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
4149
TABLE 1—APPLICABILITY OF CALCULATION-BASED AND TESTING-BASED TEST PROCEDURE OPTIONS BASED ON PUMP
CONFIGURATION—Continued
Pump
configuration
Pump sub-configuration
Applicable test methods
Pump + Motor * ....................
Pump + Polyphase Motor Covered by DOE’s Electric
Motor Energy Conservation Standards **.
OR
Pump + Submersible Motor
Section IV: Testing-Based Approach for Pumps Sold
with Motors
OR
Section V: Calculation-Based Approach for Pumps Sold
with Motors.
Section IV: Testing-Based Approach for Pumps Sold
with Motors.
Pump + Motor + Continuous
Controls.
OR
Pump + Motor + Non-Continuous Controls.
Pump + Motor Not Covered by DOE’s Electric Motor
Energy Conservation Standards (Except Submersible
Motors) ** ***.
Pump + Polyphase Motor Covered by DOE’s Electric
Motor Energy Conservation Standards** + Continuous Control.
OR
Pump + Submersible Motor + Continuous Control .........
Pump + Polyphase Motor Covered by DOE’s Electric
Motor Energy Conservation Standards** + Non-Continuous Control.
OR
Pump + Submersible Motor + Non-Continuous Control
Pump + Motor Not Covered by DOE’s Electric Motor
Energy Conservation Standards (Except Submersible
Motors) ** *** + Continuous or Non-Continuous Controls.
Section VI: Testing-Based Approach for Pumps Sold
with Motors and Controls
OR
Section VII: Calculation-Based Approach for Pumps
Sold with Motors Controls.
Section VI: Testing-Based Approach for Pumps Sold
with Motors and Controls.
Section VI: Testing-Based Approach for Pumps Sold
with Motors and Controls.
tkelley on DSK3SPTVN1PROD with RULES2
* Also applies if unit is sold with controls other than continuous or non-continuous controls (e.g., ON/OFF switches).
** All references to ‘‘Motors Covered by DOE’s Electric Motor Energy Conservation Standards’’ refer to those listed at § 431.25(g) of this chapter.
*** Includes pumps sold with single-phase induction motors.
A.2 Section III of this appendix addresses
the test procedure applicable to bare pumps.
This test procedure also applies to pumps
sold with drivers other than motors and
pumps sold with single-phase induction
motors.
A.3 Section IV of this appendix addresses
the testing-based approach for pumps sold
with motors, which is applicable to all
pumps sold with electric motors, including
single-phase induction motors. This test
procedure also applies to pumps sold with
controls other than continuous or noncontinuous controls (e.g., on/off switches).
A.4 Section V of this appendix addresses
the calculation-based approach for pumps
sold with motors, which applies to:
(1) Pumps sold with polyphase electric
motors regulated by DOE’s energy
conservation standards for electric motors at
§ 431.25(g), and
(2) Pumps sold with submersible motors.
A.5 Section VI of this appendix addresses
the testing-based approach for pumps sold
with motors and controls, which is
applicable to all pumps sold with electric
motors (including single-phase induction
motors) and continuous or non-continuous
controls.
A.6 Section VII of this appendix
discusses the calculation-based approach for
pumps sold with motors and controls, which
applies to:
(1) Pumps sold with polyphase electric
motors regulated by DOE’s energy
conservation standards for electric motors at
§ 431.25(g) and continuous controls and
(2) Pumps sold with submersible motors
and continuous controls.
B. Measurement Equipment. For the
purposes of measuring pump power input,
driver power input to the motor or controls,
VerDate Sep<11>2014
15:06 Jan 22, 2016
Jkt 238001
and pump power output, the equipment
specified in HI 40.6–2014 Appendix C
(incorporated by reference, see § 431.463)
necessary to measure head, speed of rotation,
flow rate, temperature, torque, and electrical
power must be used and must comply with
the stated accuracy requirements in HI 40.6–
2014 Table 40.6.3.2.3 except as noted in
sections III.B, IV.B, V.B, VI.B, and VII.B of
this appendix. When more than one
instrument is used to measure a given
parameter, the combined accuracy,
calculated as the root sum of squares of
individual instrument accuracies, must meet
the specified accuracy requirements.
C. Test Conditions. Conduct testing at full
impeller diameter in accordance with the test
conditions, stabilization requirements, and
specifications of HI 40.6–2014 (incorporated
by reference, see § 431.463) section 40.6.3,
‘‘Pump efficiency testing;’’ section 40.6.4,
‘‘Considerations when determining the
efficiency of a pump;’’ section 40.6.5.4
(including appendix A), ‘‘Test
arrangements;’’ and section 40.6.5.5, ‘‘Test
conditions.’’. For ST pumps, head
measurements must be based on the bowl
assembly total head as described in section
A.5 of 40.6–2014 and the pump power input
or driver power input, as applicable, must be
based on the measured input power to the
driver or bare pump, respectively; section
40.6.4.1, ‘‘vertically suspended pumps,’’ does
not apply to ST pumps.
C.1 Nominal Speed of Rotation.
Determine the nominal speed of rotation
based on the range of speeds of rotation at
which the pump is designed to operate, in
accordance with sections I.C.1.1, I.C.1.2,
I.C.1.3, I.C.1.4, or I.C.1.5 of this appendix, as
applicable. When determining the range of
speeds at which the pump is designed to
PO 00000
Frm 00065
Fmt 4701
Sfmt 4700
operate, DOE will refer to published data,
marketing literature, and other publicallyavailable information about the pump model
and motor, as applicable.
C.1.1 For pumps sold without motors,
select the nominal speed of rotation based on
the speed for which the pump is designed.
For bare pumps designed for speeds of
rotation including 2,880 to 4,320 revolutions
per minute (rpm), the nominal speed of
rotation shall be 3,600 rpm. For bare pumps
designed for speeds of rotation including
1,440 to 2,160 rpm, the nominal speed of
rotation shall be 1,800 rpm.
C.1.2 For pumps sold with 4-pole
induction motors, the nominal speed of
rotation shall be 1,800 rpm.
C.1.3 For pumps sold with 2-pole
induction motors, the nominal speed of
rotation shall be 3,600 rpm.
C.1.4 For pumps sold with non-induction
motors where the operating range of the
pump and motor includes speeds of rotation
between 2,880 and 4,320 rpm, the nominal
speed of rotation shall be 3,600 rpm.
C.1.5 For pumps sold with non-induction
motors where the operating range of the
pump and motor includes speeds of rotation
between 1,440 and 2,160 rpm, the nominal
speed of rotation shall be 1,800 rpm.
C.2 Multi-stage Pumps. For RSV and ST
pumps, perform testing on the pump with
three stages for RSV pumps and nine stages
for ST pumps. If the basic model of pump
being tested is only available with fewer than
the required number of stages, test the pump
with the maximum number of stages with
which the basic model is distributed in
commerce in the United States. If the basic
model of pump being tested is only available
with greater than the required number of
stages, test the pump with the lowest number
E:\FR\FM\25JAR2.SGM
25JAR2
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
B.1. Determine the driver power input at
each load point corresponding to 75, 100, or
110 percent of the BEP flow rate as follows:
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
Where:
PEICL = the pump energy index for a constant
load (hp),
PERCL = the pump energy rating for a
constant load (hp), determined in
Where:
Piin,m = driver power input to the motor at
load point i (hp),
Pi = pump power input to the bare pump at
load point i (hp), calculated in
accordance with section II.B.1.1 of this
appendix,
Li = the part load motor losses at load point
i (hp), calculated in accordance with
section II.B.1.2 of this appendix, and
PO 00000
Frm 00066
Fmt 4701
Sfmt 4700
Where:
PEIVL = the pump energy index for a variable
load,
PERVL = the pump energy rating for a
variable load (hp) determined in
accordance with section VI (for pumps
sold with motors and continuous or noncontinuous controls rated using the
testing-based approach) or section VII of
this appendix (for pumps sold with
motors and continuous controls rated
using the calculation-based approach),
and
PERSTD = the PERCL for a pump that is
minimally compliant with DOE’s energy
conservation standards with the same
flow and specific speed characteristics as
the tested pump (hp), as determined in
accordance with section II.B of this
appendix.
B. Determine the pump energy rating for
the minimally compliant reference pump
(PERSTD), according to the following
equation:
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
B.1.1. Determine the pump power input to
the minimally compliant pump at each load
point corresponding to 75, 100, or 110
percent of the BEP flow rate as follows:
Where:
Pi = pump power input to the bare pump at
load point i (hp),
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.033
Where:
PERSTD = the PERCL for a pump that is
minimally compliant with DOE’s energy
conservation standards with the same
flow and specific speed characteristics as
the tested pump (hp),
wi = 0.3333,
Piin,m = calculated driver power input to the
motor at load point i for the minimally
compliant pump (hp), calculated in
accordance with section II.B.1of this
appendix, and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
II. Calculation of the Pump Energy Index
A. Determine the PEI of each tested pump
based on the configuration in which it is
sold, as follows:
A.1. For pumps rated as bare pumps or
pumps sold with motors, determine the PEICL
using the following equation:
accordance with either section III (for
bare pumps, pumps sold with singlephase induction motors, and pumps sold
with drivers other than electric motors),
section IV (for pumps sold with motors
and rated using the testing-based
approach), or section V (for pumps sold
with motors and rated using the
calculation-based approach) of this
appendix, and
PERSTD = the PERCL for a pump that is
minimally compliant with DOE’s energy
conservation standards with the same
flow and specific speed characteristics as
the tested pump (hp), as determined in
accordance with section II.B of this
appendix.
A.2 For pumps rated as pumps sold with
motors and continuous controls or noncontinuous controls, determine the PEIVL
using the following equation:
ER25JA16.032
procedures set forth in this appendix for the
rated pump. Perform all calculations using
raw measured values without rounding.
Round PERCL and PERVL to three significant
digits, and round PEICL, and PEIVL values, as
applicable, to the hundredths place (i.e.,
0.01).
D.4 Pumps with BEP at Run Out.
Test pumps for which the expected BEP
corresponds to a volume rate of flow that is
within 20 percent of the expected maximum
flow rate at which the pump is designed to
operate continuously or safely (i.e., pumps
with BEP at run-out) in accordance with the
test procedure specified in this appendix, but
with the following exceptions:
(1) Use the following seven flow points for
determination of BEP in sections III.D, IV.D,
V.D, VI.D, and VII.D of this appendix instead
of those specified in those sections: 40, 50,
60, 70, 80, 90, and 100 percent of the
expected.
(2) Use flow points of 60, 70, 80, 90, and
100 percent of the expected maximum flow
rate of the pump to determine pump power
input or driver power input at the specified
load points in section III.E.1.1, IV.E.1,
V.E.1.1, VI.E.1, and VII.E.1.1 of this appendix
instead of those specified in those sections.
(3) To determine of PERCL and PERSTD, use
load points of 65, 90, and 100 percent of the
BEP flow rate determined with the modified
flow points specified in this section I.D.4 of
this appendix instead of 75, 100, and 110
percent of BEP flow.
ER25JA16.030 ER25JA16.031
tkelley on DSK3SPTVN1PROD with RULES2
of stages with which the basic model is
distributed in commerce in the United States.
If the basic model of pump being tested is
available with both fewer and greater than
the required number of stages, but not the
required number of stages, test the pump
with the number of stages closest to the
required number of stages. If both the next
lower and next higher number of stages are
equivalently close to the required number of
stages, test the pump with the next higher
number of stages.
C.3 Twin Head Pumps. For twin head
pumps, perform testing on an equivalent
single impeller IL pump, constructed by
incorporating one of the driver and impeller
assemblies of the twin head pump being
rated into an adequate, IL style, single
impeller volute and casing. An adequate, IL
style, single impeller volute and casing
means a volute and casing for which any
physical and functional characteristics that
affect energy consumption and energy
efficiency are the same to their corresponding
characteristics for a single impeller in the
twin head pump volute and casing.
D. Data Collection and Analysis
D.1 Damping Devices. Use of damping
devices, as described in section 40.6.3.2.2 of
HI 40.6¥2014 (incorporated by reference, see
§ 431.463), are only permitted to integrate up
to the data collection interval used during
testing.
D.2 Stabilization. Record data at any
tested load point only under stabilized
conditions, as defined in HI 40.6–2014
section 40.6.5.5.1 (incorporated by reference,
see § 431.463), where a minimum of two
measurements are used to determine
stabilization.
D.3 Calculations and Rounding.
Normalize all measured data to the nominal
speed of rotation of 3,600 or 1,800 rpm based
on the nominal speed of rotation selected for
the pump in section I.C.1 of this appendix,
in accordance with the procedures specified
in section 40.6.6.1.1 of HI 40.6–2014
(incorporated by reference, see § 431.463).
Except for the ‘‘expected BEP flow rate,’’ all
terms and quantities refer to values
determined in accordance with the
ER25JA16.029
4150
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
ai = 0.947 for 75 percent of the BEP flow rate,
1.000 for 100 percent of the BEP flow
rate, and 0.985 for 110 percent of the
BEP flow rate;
Pu,i = the pump power output at load point
i of the tested pump (hp), as determined
in accordance with section II.B.1.1.2 of
this appendix;
hpump,STD = the minimally compliant pump
efficiency (%), calculated in accordance
with section II.B.1.1.1 of this appendix;
and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
B.1.1.1 Calculate the minimally compliant
pump efficiency based on the following
equation:
hpump,STD = ¥0.8500 × ln(Q100%)2 ¥0.3800 ×
ln(Ns) × ln(Q100%) ¥ 11.480 × ln(Ns)2 +
17.800 × ln(Q100%) + 179.80 × ln(Ns) ¥
(C + 555.60
C = the appropriate C-value for the category
and nominal speed of rotation of the
tested pump, as listed at § 431.466.
B.1.1.1.1 Determine the specific speed of
the rated pump using the following equation:
Where:
Ns = specific speed,
nsp = the nominal speed of rotation (rpm),
Q100% = the measured BEP flow rate of the
tested pump at full impeller and nominal
speed of rotation (gpm),
H100% = pump total head at 100 percent of
the BEP flow rate of the tested pump at
full impeller and nominal speed of
rotation (ft), and
S = the number of stages with which the
pump is being rated.
B.1.1.2 Determine the pump power
output at each load point corresponding to
75, 100, or 110 percent of the BEP flow rate
using the following equation:
4151
Pu,i = the measured pump power output at
load point i of the tested pump (hp),
Qi = the measured flow rate at load point i
of the tested pump (gpm),
Hi = pump total head at load point i of the
tested pump (ft),
SG = the specific gravity of water at specified
test conditions, which is equivalent to
1.00, and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
B.1.2 Determine the motor part load
losses at each load point corresponding to 75,
100, or 110 percent of the BEP flow rate as
follows:
Li = Lfull × yi
enclosed) from the table containing the
current energy conservation standards for
NEMA Design B motors at § 431.25, with the
number of poles relevant to the speed at
which the pump is being tested (see section
I.C.1 of this appendix) and the motor
horsepower determined in section II.B.1.2.1.1
of this appendix.
B.1.2.1.2.2. For ST pumps, the default
nominal full load motor efficiency is the
default nominal full load submersible motor
efficiency listed in Table 2 of this appendix,
with the number of poles relevant to the
speed at which the pump is being tested (see
section I.C.1 of this appendix) and the motor
horsepower determined in section II.B.1.2.1.1
of this appendix.
B.1.2.2 Determine the part load loss factor
at each load point corresponding to 75, 100,
or 110 percent of the BEP flow rate as
follows:
Where:
yi = the part load loss factor at load point i,
Pi = pump power input to the bare pump at
load point i (hp),
MotorHP = the motor horsepower (hp), as
determined in accordance with section
II.B.1.2.1.1 of this appendix,
tkelley on DSK3SPTVN1PROD with RULES2
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00067
Fmt 4701
Sfmt 4700
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.037
rating listed in Table 2 of this appendix that,
is either equivalent to, or the next highest
horsepower greater than, the pump power
input to the bare pump at 120 percent of the
BEP flow rate of the tested pump divided by
a service factor of 1.15.
• For pumps sold with motors, pumps sold
with motors and continuous controls, or
pumps sold with motors and non-continuous
controls, the motor horsepower is the rated
horsepower of the motor with which the
pump is being tested.
B.1.2.1.2 Determine the default nominal
full load motor efficiency as described in
section II.B.1.2.1.2.1 of this appendix for
pumps other than ST pumps or II.B.1.2.1.2.2
of this appendix for ST pumps.
B.1.2.1.2.1. For pumps other than ST
pumps, the default nominal full load motor
efficiency is the minimum of the nominal full
load motor efficiency standards (open or
ER25JA16.035 ER25JA16.036
Where:
Lfull = motor losses at full load (hp),
MotorHP = the motor horsepower as
determined in accordance with section
II.B.1.2.1.1 of this appendix (hp), and
hmotor,full = the default nominal full load
motor efficiency as determined in
accordance with section II.B.1.2.1.2 of
this appendix (%).
B.1.2.1.1 Determine the motor
horsepower as follows:
• For bare pumps other than ST pumps,
the motor horsepower is determined as the
horsepower rating listed in Table 2 of this
appendix that is either equivalent to, or the
next highest horsepower greater than, the
pump power input to the bare pump at 120
percent of the BEP flow rate of the tested
pump.
• For ST bare pumps, the motor
horsepower is determined as the horsepower
Where:
hpump,STD = minimally compliant pump
efficiency (%),
Q100% = the BEP flow rate of the tested pump
at full impeller and nominal speed of
rotation (gpm),
Ns = specific speed of the tested pump
determined in accordance with section
II.B.1.1.1.1 of this appendix, and
ER25JA16.034
Where:
Where:
Li = part load motor losses at load point i
(hp),
Lfull = motor losses at full load (hp), as
determined in accordance with section
II.B.1.2.1 of this appendix,
yi = part load loss factor at load point i
determined in accordance with section
II.B.1.2.2 of this appendix, and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
B.1.2.1 Determine the full load motor
losses using the appropriate motor efficiency
value and horsepower as shown in the
following equation:
4152
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
III. Test Procedure for Bare Pumps
A. Scope. This section III applies only to:
(1) Bare pumps,
(2) Pumps sold with drivers other than
electric motors, and
(3) Pumps sold with single-phase
induction motors.
B. Measurement Equipment. The
requirements regarding measurement
equipment presented in section I.B of this
appendix apply to this section III, and in
addition, when testing pumps using a
calibrated motor:
(1) Electrical measurement equipment
must be capable of measuring true RMS
current, true RMS voltage, and real power up
to the 40th harmonic of fundamental supply
source frequency, and
(2) Any instruments used to measure a
particular parameter specified in paragraph
(1) must have a combined accuracy of ±2.0
percent of the measured value at the
fundamental supply source frequency, where
combined accuracy is the root sum of squares
of individual instrument accuracies.
C. Test Conditions. The requirements
regarding test conditions presented in section
I.C of this appendix apply to this section III.
When testing pumps using a calibrated motor
the following conditions also apply to the
mains power supplied to the motor:
(1) Maintain the voltage within ±5 percent
of the rated value of the motor,
(2) Maintain the frequency within ±1
percent of the rated value of the motor,
(3) Maintain the voltage unbalance of the
power supply within ±3 percent of the rated
values of the motor, and
(2) Maintain total harmonic distortion
below 12 percent throughout the test.
D. Testing BEP for the Pump. Determine
the best efficiency point (BEP) of the pump
as follows:
D.1. Adjust the flow by throttling the pump
without changing the speed of rotation of the
pump and conduct the test at a minimum of
the following seven flow points: 40, 60, 75,
90, 100, 110, and 120 percent of the expected
BEP flow rate of the pump at the nominal
speed of rotation, as specified in HI 40.6–
2014, except section 40.6.5.3, section A.7,
and appendix B (incorporated by reference,
see § 431.463).
D.2. Determine the BEP flow rate as the
flow rate at the operating point of maximum
pump efficiency on the pump efficiency
curve, as determined in accordance with
section 40.6.6.3 of HI 40.6–2014
(incorporated by reference, see § 431.463),
where the pump efficiency is the ratio of the
pump power output divided by the pump
power input, as specified in Table 40.6.2.1 of
HI 40.6–2014, disregarding the calculations
provided in section 40.6.6.2.
E. Calculating the Constant Load Pump
Energy Rating. Determine the PERCL of each
tested pump using the following equation:
Where:
Lfull = motor losses at full load (hp);
MotorHP = the motor horsepower (hp), as
determined in accordance with section
II.E.1.2.1.1 of this appendix, and
hmotor,full = the default nominal full load
motor efficiency (%), as determined in
accordance with section III.E.1.2.1.2 of
this appendix.
E.1.2.1.1 Determine the motor
horsepower as follows:
• For bare pumps other than ST pumps,
determine the motor horsepower by selecting
the horsepower rating listed in Table 2 of this
appendix that is either equivalent to, or the
next highest horsepower greater than, the
pump power input to the bare pump at 120
percent of the BEP flow rate of the tested
pump.
Where:
PERCL = the pump energy rating for a
constant load (hp),
wi = 0.3333,
Piin,m = calculated driver power input to the
motor at load point i (hp), as determined
in accordance with section III.E.1 of this
appendix, and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
E.1 Determine the driver power input at
each load point corresponding to 75, 100, or
110 percent of the BEP flow rate as follows:
Piin,m = driver power input to the motor at
load point i (hp),
Pi = pump power input to the bare pump at
load point i (hp), as determined in
section III.E.1.1 of this appendix,
Li = the part load motor losses at load point
i (hp), as determined in accordance with
section III.E.1.2 of this appendix, and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
E.1.1 Determine the pump power input at
75, 100, 110, and 120 percent of the BEP flow
rate by employing a least squares regression
to determine a linear relationship between
the pump power input at the nominal speed
of rotation of the pump and the measured
flow rate at the following load points: 60, 75,
90, 100, 110, and 120 percent of the expected
BEP flow rate. Use the linear relationship to
determine the pump power input at the
nominal speed of rotation for the load points
of 75, 100, 110, and 120 percent of the BEP
flow rate.
E.1.2 Determine the motor part load
losses at each load point corresponding to 75,
100, or 110 percent of the BEP flow rate as
follows:
Li = Lfull × yi
Where:
Li = motor losses at load point i (hp),
Lfull = motor losses at full load (hp), as
determined in accordance with section
III.E.1.2.1 of this appendix,
yi = loss factor at load point i as determined
in accordance with section III.E.1.2.2 of
this appendix, and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
E.1.2.1 Determine the full load motor
losses using the appropriate motor efficiency
value and horsepower as shown in the
following equation:
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00068
Fmt 4701
Sfmt 4700
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.039 ER25JA16.040
• For ST bare pumps, determine the motor
horsepower by selecting the horsepower
rating listed in Table 2 of this appendix that,
is either equivalent to, or the next highest
horsepower greater than, the pump power
input to the bare pump at 120 percent of the
BEP flow rate of the tested pump divided by
a service factor of 1.15.
• For pumps sold with motors, pumps sold
with motors and continuous controls, or
ER25JA16.038
tkelley on DSK3SPTVN1PROD with RULES2
ER25JA16.041
Where:
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
4153
load motor efficiency standards (open or
enclosed) from the table containing the
current energy conservation standards for
NEMA Design B motors at § 431.25, with the
number of poles relevant to the speed at
which the pump is being tested (see section
I.C.1 of this appendix) and the motor
horsepower determined in section
III.E.1.2.1.1 of this appendix.
E.1.2.1.2.2. For ST pumps, the default
nominal full load motor efficiency is the
default nominal full load submersible motor
efficiency listed in Table 2 of this appendix,
with the number of poles relevant to the
speed at which the pump is being tested (see
section I.C.1 of this appendix) and the motor
horsepower determined in section
III.E.1.2.1.1 of this appendix;
E.1.2.2 Determine the loss factor at each
load point corresponding to 75, 100, or 110
percent of the BEP flow rate as follows:
Where:
yi = the part load loss factor at load point i,
Pi = pump power input to the bare pump at
load point i (hp), as determined in
accordance with section III.E.1.1 of this
appendix,
MotorHP = as determined in accordance with
section III.E.1.2.1 of this appendix (hp),
IV. Testing-Based Approach for Pumps Sold
With Motors
D.1 Adjust the flow by throttling the
pump without changing the speed of rotation
of the pump to a minimum of seven flow
points: 40, 60, 75, 90, 100, 110, and 120
percent of the expected BEP flow rate of the
pump at the nominal speed of rotation, as
specified in HI 40.6–2014, except section
40.6.5.3, section A.7, and appendix B
(incorporated by reference, see § 431.463).
D.2. Determine the BEP flow rate as the
flow rate at the operating point of maximum
overall efficiency on the pump efficiency
curve, as determined in accordance with
section 40.6.6.3 of HI 40.6–2014
(incorporated by reference, see § 431.463),
where the overall efficiency is the ratio of the
pump power output divided by the driver
power input, as specified in Table 40.6.2.1 of
HI 40.6–2014, disregarding the calculations
provided in section 40.6.6.2.
E. Calculating the Constant Load Pump
Energy Rating. Determine the PERCL of each
tested pump using the following equation:
E.1 Determine the driver power input at
75, 100, and 110 percent of the BEP flow rate
by employing a least squares regression to
determine a linear relationship between the
driver power input at the nominal speed of
rotation of the pump and the measured flow
rate at the following load points: 60, 75, 90,
100, 110, and 120 percent of the expected
BEP flow rate. Use the linear relationship to
determine the driver power input at the
nominal speed of rotation for the load points
of 75, 100, and 110 percent of the BEP flow
rate.
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
Where:
PERCL = the pump energy rating for a
constant load (hp),
wi = 0.3333,
Piin = measured driver power input to the
motor at load point i (hp) for the tested
pump as determined in accordance with
section IV.E.1 of this appendix, and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
PO 00000
Frm 00069
Fmt 4701
Sfmt 4700
V. Calculation-Based Approach for Pumps
Sold With Motors
A. Scope. This section V can only be used
in lieu of the test method in section IV of this
appendix to calculate the index for pumps
sold with motors listed in section V.A.1 or
V.A.2 of this appendix.
A.1 Pumps sold with motors subject to
DOE’s energy conservation standards for
polyphase electric motors at § 431.25(g), and
A.2. Pumps sold with submersible motors.
A.3. Pumps sold with motors not listed in
sections V.A.1 or V.A.2 of this appendix
cannot use this section V and must apply the
test method in section IV of this appendix.
B. Measurement Equipment. The
requirements regarding measurement
equipment presented in section I.B of this
appendix apply to this section V, and in
addition, when testing pumps using a
calibrated motor electrical measurement
equipment must:
(1) Be capable of measuring true RMS
current, true RMS voltage, and real power up
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.043 ER25JA16.044
A. Scope. This section IV applies only to
pumps sold with electric motors, including
single-phase induction motors.
B. Measurement Equipment. The
requirements regarding measurement
equipment presented in section I.B of this
appendix apply to this section IV, and in
addition, the electrical measurement
equipment must:
(1) Be capable of measuring true RMS
current, true RMS voltage, and real power up
to the 40th harmonic of fundamental supply
source frequency, and
(2) For all instruments used to measure a
given parameter, have a combined accuracy
of ±2.0 percent of the measured value at the
fundamental supply source frequency, where
combined accuracy is the root sum of squares
of individual instrument accuracies.
C. Test Conditions. The requirements
regarding test conditions presented in section
I.C of this appendix apply to this section IV.
The following conditions also apply to the
mains power supplied to the motor:
(1) Maintain the voltage within ±5 percent
of the rated value of the motor,
(2) Maintain the frequency within ±1
percent of the rated value of the motor,
(3) Maintain the voltage unbalance of the
power supply within ±3 percent of the rated
values of the motor, and
(4) Maintain total harmonic distortion
below 12 percent throughout the test.
D. Testing BEP for the Pump. Determine
the BEP of the pump as follows:
ER25JA16.042
tkelley on DSK3SPTVN1PROD with RULES2
pumps sold with motors and non-continuous
controls, the motor horsepower is the rated
horsepower of the motor with which the
pump is being tested.
E.1.2.1.2 Determine the default nominal
full load motor efficiency as described in
section III.E.1.2.1.2.1 of this appendix for
pumps other than ST pumps or III.E.1.2.1.2.2.
of this appendix for ST pumps.
E.1.2.1.2.1. For pumps other than ST
pumps, the default nominal full load motor
efficiency is the minimum of the nominal full
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
Where:
Piin,m = driver power input to the motor at
load point i (hp),
Pi = pump power input to the bare pump at
load point i, as determined in section
V.E.1.1 of this appendix (hp),
Li = the part load motor losses at load point
i as determined in accordance with
section V.E.1.2 of this appendix (hp),
and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
E.1.1 Determine the pump power input at
75, 100, 110, and 120 percent of the BEP flow
rate by employing a least squares regression
to determine a linear relationship between
the pump power input at the nominal speed
of rotation of the pump and the measured
flow rate at the following load points: 60, 75,
90, 100, 110, and 120 percent of the expected
BEP flow rate. Use the linear relationship to
determine the pump power input at the
nominal speed of rotation for the load points
of 75, 100, 110, and 120 percent of the BEP
flow rate.
E.1.2 Determine the motor part load
losses at each load point corresponding to 75,
100, or 110 percent of the BEP flow rate as
follows:
Li = Lfull × Yi
Where:
yi = the part load loss factor at load point i,
Pi = the pump power input to the bare pump
at load point i as determined in
tkelley on DSK3SPTVN1PROD with RULES2
Where:
Where:
Li = motor losses at load point i (hp),
Lfull = motor losses at full load as determined
in accordance with section V.E.1.2.1 of
this appendix (hp),
yi = part load loss factor at load point i as
determined in accordance with section
V.E.1.2.2 of this appendix, and
accordance with section V.E.1.1 of this
appendix (hp),
MotorHP = the horsepower of the motor with
which the pump model is being tested
(hp),
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00070
Fmt 4701
Sfmt 4700
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
E.1.2.1 Determine the full load motor
losses using the appropriate motor efficiency
value and horsepower as shown in the
following equation:
Where:
Lfull = motor losses at full load (hp),
MotorHP = the horsepower of the motor with
which the pump model is being tested
(hp), and
hmotor,full = the represented nominal full load
motor efficiency (i.e., nameplate/DOEcertified value) or default nominal full
load submersible motor efficiency as
determined in accordance with section
V.E.1.2.1.1 of this appendix (%).
E.1.2.1.1 For pumps sold with motors
other than submersible motors, determine the
represented nominal full load motor
efficiency as described in section
V.E.1.2.1.1.1 of this appendix. For pumps
sold with submersible motors determine the
default nominal full load submersible motor
efficiency as described in section
V.E.1.2.1.1.2 of this appendix.
E.1.2.1.1.1. For pumps sold with motors
other than submersible motors, the
represented nominal full load motor
efficiency is that of the motor with which the
given pump model is being tested, as
determined in accordance with the DOE test
procedure for electric motors at § 431.16 and
applicable representation procedures in parts
429 and 430.
E.1.2.1.1.2. For pumps sold with
submersible motors, the default nominal full
load submersible motor efficiency is that
listed in Table 2 of this appendix, with the
number of poles relevant to the speed at
which the pump is being tested (see section
I.C.1 of this appendix) and the motor
horsepower of the pump being tested.
E.1.2.2 Determine the loss factor at each
load point corresponding to 75, 100, or 110
percent of the BEP flow rate as follows:
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate, and
E:\FR\FM\25JAR2.SGM
ER25JA16.048
PERCL = the pump energy rating for a
constant load (hp),
wi = 0.3333,
Piin,m = calculated driver power input to the
motor at load point i for the tested pump
as determined in accordance with
section V.E.1 of this appendix (hp), and
i = load point corresponding to 75, 100, or
110 percent of the BEP flow rate.
E.1 Determine the driver power input at
each load point corresponding to 75, 100, or
110 percent of the BEP flow rate as follows:
ER25JA16.046 ER25JA16.047
to the 40th harmonic of fundamental supply
source frequency, and
(2) For all instruments used to measure a
given parameter, have a combined accuracy
of ±2.0 percent of the measured value at the
fundamental supply source frequency, where
combined accuracy is the root sum of squares
of individual instrument accuracies.
C. Test Conditions. The requirements
regarding test conditions presented in section
I.C of this appendix apply to this section V.
When testing pumps using a calibrated motor
the following conditions also apply to the
mains power supplied to the motor:
(1) Maintain the voltage within ±5 percent
of the rated value of the motor,
(2) Maintain the frequency within ±1
percent of the rated value of the motor,
(3) Maintain the voltage unbalance of the
power supply within ±3 percent of the rated
values of the motor, and
(4) Maintain total harmonic distortion
below 12 percent throughout the test.
D. Testing BEP for the Bare Pump.
Determine the best efficiency point (BEP) of
the pump as follows:
D.1 Adjust the flow by throttling the
pump without changing the speed of rotation
of the pump to a minimum of seven flow
points: 40, 60, 75, 90, 100, 110, and 120
percent of the expected BEP flow rate of the
pump at the nominal speed of rotation, as
specified in HI 40.6–2014, except section
40.6.5.3, section A.7, and appendix B
(incorporated by reference, see § 431.463).
D.2. Determine the BEP flow rate as the
flow rate at the operating point of maximum
pump efficiency on the pump efficiency
curve, as determined in accordance with
section 40.6.6.3 of HI 40.6–2014
(incorporated by reference, see § 431.463),
where pump efficiency is the ratio of the
pump power output divided by the pump
power input, as specified in Table 40.6.2.1 of
HI 40.6–2014 and the calculations provided
in section 40.6.6.2 are to be disregarded.
E. Calculating the Constant Load Pump
Energy Rating. Determine the PERCL of each
tested pump using the following equation:
25JAR2
ER25JA16.045
4154
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
4155
Where:
PERVL = the pump energy rating for a
variable load (hp);
wi = 0.25;
Piin,c = the normalized driver power input to
continuous or non-continuous controls
at load point i for the tested pump as
determined in accordance with section
VI.E.1 of this appendix; and
i = load point corresponding 25, 50, 75, or
100 percent of the BEP flow rate.
E.1. Determine the driver power input at
100 percent of the measured BEP flow rate
of the tested pump by employing a least
squares regression to determine a linear
relationship between the measured driver
power input at the nominal speed of rotation
of the pump and the measured flow rate,
using the following load points: 60, 75, 90,
100, 110, and 120 percent of the expected
BEP flow rate. Use the linear relationship to
determine the driver power input at the
nominal speed of rotation for the load point
of 100 percent of the measured BEP flow rate
of the tested pump.
E.2 Determine the driver power input at
25, 50, and 75 percent of the BEP flow rate
by measuring the driver power input at the
load points defined by:
(1) Those flow rates, and
(2) The associated head points calculated
according to the following reference system
curve equation:
Where:
Hi = pump total head at load point i (ft),
H100% = pump total head at 100 percent of
the BEP flow rate and nominal speed of
rotation (ft),
Qi = flow rate at load point i (gpm),
Q100% = flow rate at 100 percent of the BEP
flow rate and nominal speed of rotation
(gpm), and
i = load point corresponding to 25, 50, or 75
percent of the measured BEP flow rate of
the tested pump.
E.2.1. For pumps sold with motors and
continuous controls, the specific head and
flow points must be achieved within 10
percent of the calculated values and the
measured driver power input must be
corrected to the exact intended head and
flow conditions using the following equation:
tkelley on DSK3SPTVN1PROD with RULES2
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00071
Fmt 4701
Sfmt 4700
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.050 ER25JA16.051
D.1. Adjust the flow by throttling the pump
without changing the speed of rotation of the
pump to a minimum of seven flow points: 40,
60, 75, 90, 100, 110, and 120 percent of the
expected BEP flow rate of the pump at the
nominal speed of rotation, as specified in HI
40.6–2014, except section 40.6.5.3, section
A.7, and appendix B (incorporated by
reference, see § 431.463).
D.2. Determine the BEP flow rate as the
flow rate at the operating point of maximum
overall efficiency on the pump efficiency
curve, as determined in accordance with
section 40.6.6.3 of HI 40.6–2014
(incorporated by reference, see § 431.463),
where overall efficiency is the ratio of the
pump power output divided by the driver
power input, as specified in Table 40.6.2.1 of
HI 40.6–2014 and the calculations provided
in section 40.6.6.2 are to be disregarded.
E. Calculating the Variable Load Pump
Energy Rating. Determine the PERVL of each
tested pump using the following equation:
ER25JA16.049
VI. Testing-Based Approach for Pumps Sold
with Motors and Controls
A. Scope. This section VI applies only to
pumps sold with electric motors, including
single-phase induction motors, and
continuous or non-continuous controls. For
the purposes of this section VI, all references
to ‘‘driver input power’’ in this section VI or
HI 40.6–2014 (incorporated by reference, see
§ 431.463) refer to the input power to the
continuous or non-continuous controls.
B. Measurement Equipment. The
requirements regarding measurement
equipment presented in section I.B of this
appendix apply to this section VI, and in
addition electrical measurement equipment
must:
(1) Be capable of measuring true RMS
current, true RMS voltage, and real power up
to the 40th harmonic of fundamental supply
source frequency, and
(2) For all instruments used to measure a
given parameter, have a combined accuracy
of ±2.0 percent of the measured value at the
fundamental supply source frequency, where
combined accuracy is the root sum of squares
of individual instrument accuracies.
C. Test Conditions. The requirements
regarding test conditions presented in section
I.C of this appendix apply to this section VI.
The following conditions also apply to the
mains power supplied to the continuous or
non-continuous control:
(1) Maintain the voltage within ±5 percent
of the rated value of the motor,
(2) Maintain the frequency within ±1
percent of the rated value of the motor,
(3) Maintain the voltage unbalance of the
power supply within ±3 percent of the rated
values of the motor, and
(4) Maintain total harmonic distortion
below 12 percent throughout the test.
D. Testing BEP for the Pump. Determine
the BEP of the pump as follows:
in the equation in this section V.E.1.2.2. of
this appendix to calculate the part load loss
factor at each load point
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
Where:
Pi = pump power input at load point i (hp);
P100≠ = pump power input at 100 percent of
the BEP flow rate and nominal speed of
rotation (hp);
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
E. Calculating the Variable Load Pump
Energy Rating. Determine the PERVL of each
tested pump using the following equation:
Qi = flow rate at load point i (gpm);
Q100≠ = flow rate at 100 percent of the BEP
flow rate and nominal speed of rotation
(gpm); and
i = load point corresponding to 25, 50, or 75
percent of the measured BEP flow rate of
the tested pump.
E.1.2 Calculate the motor and control part
load losses at each load point corresponding
PO 00000
Frm 00072
Fmt 4701
Sfmt 4700
Where:
PERVL = the pump energy rating for a
variable load (hp);
wi = 0.25;
Piin,c = the calculated driver power input to
the continuous or non-continuous
controls at load point i for the tested
pump as determined in accordance with
section VII.E.1 of this appendix; and
i = load point corresponding to 25, 50, 75,
or 100 percent of the BEP flow rate.
E.1 Determine the driver power input at
each load point corresponding to 25, 50, 75,
or 100 percent of the BEP flow rate as
follows:
Where:
Piin,c = driver power input at to the
continuous or non-continuous controls
at load point i (hp),
Pi = pump power input to the bare pump at
load point i as determined in accordance
with section VII.E.1.1 of this appendix
(hp),
Li = the part load motor and control losses
at load point i as determined in
accordance with section VII.E.1.2 of this
appendix (hp), and
i = load point corresponding to 25, 50, 75,
or 100 percent of the BEP flow rate.
E.1.1 Determine the pump power input at
100 percent of the measured BEP flow rate
of the tested pump by employing a least
squares regression to determine a linear
relationship between the measured pump
power input at the nominal speed of rotation
and the measured flow rate at the following
load points: 60, 75, 90, 100, 110, and 120
percent of the expected BEP flow rate. Use
the linear relationship to determine the
pump power input at the nominal speed of
rotation for the load point of 100 percent of
the BEP flow rate.
E.1.1.1 Determine the pump power input
at 25, 50, and 75 percent of the BEP flow rate
based on the measured pump power input at
100 percent of the BEP flow rate and using
with the following equation:
E:\FR\FM\25JAR2.SGM
25JAR2
ER25JA16.055
VII. Calculation-Based Approach for Pumps
Sold With Motors and Controls
A. Scope. This section VII can only be used
in lieu of the test method in section VI of this
appendix to calculate the index for pumps
listed in section VII.A.1 or VII.A.2 of this
appendix.
A.1. Pumps sold with motors regulated by
DOE’s energy conservation standards for
polyphase NEMA Design B electric motors at
§ 431.25(g) and continuous controls, and
A.2. Pumps sold with submersible motors
and continuous controls.
A.3. Pumps sold with motors not listed in
VII.A.1 or VII.A.2 of this appendix and
pumps sold without continuous controls,
including pumps sold with non-continuous
controls, cannot use this section and must
apply the test method in section VI of this
appendix.
B. Measurement Equipment. The
requirements regarding measurement
equipment presented in section I.B of this
appendix apply to this section VII, and in
addition, when testing pumps using a
calibrated motor electrical measurement
equipment must:
(1) Be capable of measuring true RMS
current, true RMS voltage, and real power up
to the 40th harmonic of fundamental supply
source frequency, and
(2) For all instruments used to measure a
given parameter, have a combined accuracy
of ±2.0 percent of the measured value at the
fundamental supply source frequency, where
combined accuracy is the root sum of squares
of individual instrument accuracies.
C. Test Conditions. The requirements
regarding test conditions presented in section
I.C of this appendix apply to this section VII.
When testing pumps using a calibrated motor
the following conditions also apply to the
mains power supplied to the motor:
(1) Maintain the voltage within ±5 percent
of the rated value of the motor,
(2) Maintain the frequency within ±1
percent of the rated value of the motor,
(3) Maintain the voltage unbalance of the
power supply within ±3 percent of the rated
values of the motor, and
(4) Maintain total harmonic distortion
below 12 percent throughout the test.
D. Testing BEP for the Bare Pump.
Determine the BEP of the pump as follows:
D.1. Adjust the flow by throttling the pump
without changing the speed of rotation of the
pump to a minimum of seven flow points: 40,
60, 75, 90, 100, 110, and 120 percent of the
expected BEP flow rate of the pump at the
nominal speed of rotation, as specified in HI
40.6–2014, except section 40.6.5.3, section
A.7, and appendix B (incorporated by
reference, see § 431.463).
D.2. Determine the BEP flow rate as the
flow rate at the operating point of maximum
pump efficiency on the pump efficiency
curve, as determined in accordance with
section 40.6.6.3 of HI 40.6–2014
(incorporated by reference, see § 431.463),
where pump efficiency is the ratio of the
pump power output divided by the pump
power input, as specified in Table 40.6.2.1 of
HI 40.6–2014 and the calculations provided
in section 40.6.6.2 are to be disregarded.
ER25JA16.053 ER25JA16.054
Where:
Piin,c = the corrected driver power input to
the continuous or non-continuous
controls at load point i (hp),
Hsp,i = the specified total system head at load
point i based on the reference system
curve (ft),
HM,j = the measured total system head at load
point j (ft),
Qsp,i = the specified total system flow rate at
load point i based on the reference
system curve (gpm),
QM,j = the measured total system flow rate at
load point j (gpm),
PM,jin,c = the measured normalized driver
power input to the continuous or noncontinuous controls at load point j (hp),
i = specified load point at 25, 50, 75, or 100
percent of BEP flow, and
j = measured load point corresponding to
specified load point i.
E.2.2. For pumps sold with motors and
non-continuous controls, the head associated
with each of the specified flow points shall
be no lower than 10 percent below that
defined by the reference system curve
equation in section VI.E.2 of this appendix.
Only the measured flow points must be
achieved within 10 percent of the calculated
values. Correct for flow and head as
described in section VI.E.2.1, except do not
correct measured head values that are higher
than the reference system curve at the same
flow rate; only correct flow rate and head
values lower than the reference system curve
at the same flow rate. For head values higher
than the system curve, use the measured
head points directly to calculate PEIVL.
ER25JA16.052
4156
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
to 25, 50, 75, and 100 percent of the BEP flow
rate as follows:
4157
Lfull = motor losses at full load as determined
in accordance with section VII.E.1.2.1 of
this appendix (hp),
zi = part load loss factor at load point i as
determined in accordance with section
VII.E.1.2.2 of this appendix, and
i = load point corresponding to 25, 50, 75,
or 100 percent of the BEP flow rate.
E.1.2.1 Determine the full load motor
losses using the appropriate motor efficiency
value and horsepower as shown in the
following equation:
Where:
Lfull = motor losses at full load (hp),
MotorHP = the horsepower of the motor with
which the pump model is being tested
(hp), and
hmotor,full = the represented nominal full load
motor efficiency (i.e., nameplate/DOEcertified value) or default nominal full
load submersible motor efficiency as
determined in accordance with section
VII.E.1.2.1.1 of this appendix (%).
E.1.2.1.1 For pumps sold with motors
other than submersible motors, determine the
represented nominal full load motor
efficiency as described in section
VII.E.1.2.1.1.1 of this appendix. For pumps
sold with submersible motors, determine the
default nominal full load submersible motor
efficiency as described in section
VII.E.1.2.1.1.2 of this appendix.
E.1.2.1.1.1 For pumps sold with motors
other than submersible motors, the
represented nominal full load motor
efficiency is that of the motor with which the
given pump model is being tested, as
determined in accordance with the DOE test
procedure for electric motors at § 431.16 and
applicable representation procedures in parts
429 and 430.
E.1.2.1.1.2 For pumps sold with
submersible motors, the default nominal full
load submersible motor efficiency is that
listed in Table 2 of this appendix, with the
number of poles relevant to the speed at
which the pump is being tested (see section
I.C.1 of this appendix) and the motor
horsepower of the pump being tested.
E.1.2.2 For load points corresponding to
25, 50, 75, and 100 percent of the BEP flow
rate, determine the part load loss factor at
each load point as follows:
Where:
zi = the motor and control part load loss
factor at load point i,
a,b,c = coefficients listed in Table 4 of this
appendix based on the horsepower of the
motor with which the pump is being
tested,
Pi = the pump power input to the bare pump
at load point i, as determined in
accordance with section VII.E.1.1 of this
appendix (hp),
MotorHP = the horsepower of the motor with
which the pump is being tested (hp),
Li = Lfull × zi
Where:
Li = motor and control losses at load point
i (hp),
TABLE 2—DEFAULT NOMINAL FULL LOAD SUBMERSIBLE MOTOR EFFICIENCY BY MOTOR HORSEPOWER AND POLE
Default nominal full load
submersible motor efficiency
1 ...............................................................................................................................................................................
1.5 ............................................................................................................................................................................
2 ...............................................................................................................................................................................
3 ...............................................................................................................................................................................
5 ...............................................................................................................................................................................
7.5 ............................................................................................................................................................................
10 .............................................................................................................................................................................
15 .............................................................................................................................................................................
20 .............................................................................................................................................................................
25 .............................................................................................................................................................................
30 .............................................................................................................................................................................
40 .............................................................................................................................................................................
50 .............................................................................................................................................................................
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00073
Fmt 4701
Sfmt 4700
E:\FR\FM\25JAR2.SGM
25JAR2
55
66
68
70
74
68
70
72
72
74
77
78.5
80
4 poles
68
70
70
75.5
75.5
74
74
75.5
77
78.5
80
81.5
82.5
ER25JA16.057 ER25JA16.058
tkelley on DSK3SPTVN1PROD with RULES2
2 poles
ER25JA16.056
Motor horsepower
(hp)
4158
Federal Register / Vol. 81, No. 15 / Monday, January 25, 2016 / Rules and Regulations
TABLE 2—DEFAULT NOMINAL FULL LOAD SUBMERSIBLE MOTOR EFFICIENCY BY MOTOR HORSEPOWER AND POLE—
Continued
Default nominal full load
submersible motor efficiency
Motor horsepower
(hp)
2 poles
60 .............................................................................................................................................................................
75 .............................................................................................................................................................................
100 ...........................................................................................................................................................................
125 ...........................................................................................................................................................................
150 ...........................................................................................................................................................................
200 ...........................................................................................................................................................................
250 ...........................................................................................................................................................................
TABLE 3—NOMINAL FULL LOAD
MOTOR EFFICIENCY VALUES
TABLE 3—NOMINAL FULL LOAD
MOTOR EFFICIENCY VALUES—Continued
Nominal full load motor efficiency*
4 poles
81.5
81.5
81.5
84
84
85.5
86.5
84
85.5
84
84
85.5
86.5
86.5
TABLE 3—NOMINAL FULL LOAD
MOTOR EFFICIENCY VALUES—Continued
Nominal full load motor efficiency*
Nominal full load motor efficiency*
85.5
86.5
87.5
88.5
89.5
90.2
91.0
91.7
92.4
93.0
93.6
94.1
94.5
95.0
95.4
95.8
96.2
96.5
50.5
52.5
55.0
57.5
59.5
62.0
64.0
66.0
68.0
70.0
72.0
74.0
75.5
77.0
78.5
80.0
81.5
82.5
84.0
96.8
97.1
97.4
97.6
97.8
98.0
98.2
98.4
98.5
98.6
98.7
98.8
98.9
99.0
* Note: Each consecutive incremental value
of nominal efficiency represents one band.
TABLE 4—MOTOR AND CONTROL PART LOAD LOSS FACTOR EQUATION COEFFICIENTS FOR SECTION VII.E.1.2.2 OF THIS
APPENDIX A
Coefficients for Motor and Control Part Load Loss
Factor (zi)
Motor horsepower
(hp)
a
≤5 .....................................................................................................................................
>5 and ≤20 .......................................................................................................................
>20 and ≤50 .....................................................................................................................
>50 ...................................................................................................................................
¥
¥
¥
¥
b
0.4658
1.3198
1.5122
0.8914
[FR Doc. 2016–00039 Filed 1–22–16; 8:45 am]
tkelley on DSK3SPTVN1PROD with RULES2
BILLING CODE 6450–01–P
VerDate Sep<11>2014
13:56 Jan 22, 2016
Jkt 238001
PO 00000
Frm 00074
Fmt 4701
Sfmt 9990
E:\FR\FM\25JAR2.SGM
25JAR2
c
1.4965
2.9551
3.0777
2.8846
0.5303
0.1052
0.1847
0.2625
Agencies
[Federal Register Volume 81, Number 15 (Monday, January 25, 2016)]
[Rules and Regulations]
[Pages 4085-4158]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2016-00039]
[[Page 4085]]
Vol. 81
Monday,
No. 15
January 25, 2016
Part II
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 431
Energy Conservation Program: Test Procedure for Pumps; Final Rule
Federal Register / Vol. 81 , No. 15 / Monday, January 25, 2016 /
Rules and Regulations
[[Page 4086]]
=======================================================================
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[Docket No. EERE-2013-BT-TP-0055]
RIN 1905-AD50
Energy Conservation Program: Test Procedure for Pumps
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: On April 1, 2015, the U.S. Department of Energy (DOE) issued a
notice of proposed rulemaking (NOPR) to establish new definitions and a
new test procedure for pumps. That proposed rulemaking serves as the
basis for this final rule. This final rule establishes a new test
procedure for pumps, as well as associated definitions and parameters
that establish the scope of applicability of the test procedure.
Specifically, the pumps test procedure adopted in this final rule
incorporates by reference the test procedure from the Hydraulic
Institute (HI)--standard 40.6-2014, ``Methods for Rotodynamic Pump
Efficiency Testing''--with several clarifications and modifications,
related to measuring the hydraulic power, shaft power, and electric
input power of pumps, inclusive of electric motors and any continuous
or non-continuous controls. The new pumps test procedure will be used
to determine the constant load pump energy index (PEICL) for
pumps sold without continuous or non-continuous controls and the
variable load pump energy index (PEIVL) for pumps sold with
continuous or non-continuous controls. The final rule incorporates
certain recommendations made by the commercial and industrial pumps
(CIP) Working Group, which was established under the Appliance
Standards Rulemaking Federal Advisory Committee (ASRAC), as well as
comments submitted by interested parties in response to the April 2015
pumps test procedure NOPR.
DATES: The effective date of this rule is February 24, 2016. Compliance
with the final rule will be mandatory for representations of
PEICL, PEIVL, the constant load pump energy
rating (PERCL), and the variable load pump energy rating
(PERVL) made on or after July 25, 2016. The incorporation by
reference of certain publications listed in this rule is approved by
the Director of the Federal Register as of February 24, 2016.
ADDRESSES: The docket, which includes Federal Register notices, public
meeting attendee lists and transcripts, comments, and other supporting
documents/materials, is available for review at regulations.gov. All
documents in the docket are listed in the www.regulations.gov index.
However, some documents listed in the index, such as those containing
information that is exempt from public disclosure, may not be publicly
available.
A link to the docket Web page can be found at: https://www1.eere.energy.gov/buildings/appliance_standards/product.aspx/productid/44. This Web page contains a link to the docket for this
document on the regulations.gov site. The www.regulations.gov Web page
contains simple instructions on how to access all documents, including
public comments, in the docket.
For further information on how to review the docket, contact Ms.
Brenda Edwards at (202) 586-2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Ashley Armstrong, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Office, EE-5B,
1000 Independence Avenue SW., Washington, DC 20585-0121. Telephone:
(202) 586-6590. Email: pumps@ee.doe.gov.
Jennifer Tiedeman, U.S. Department of Energy, Office of the General
Counsel, GC-33, 1000 Independence Avenue SW., Washington DC 20585-0121.
Telephone: (202) 287-6111. Email: Jennifer.Tiedeman@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final rule incorporates by reference
into 10 CFR part 431 the following industry standards:
(1) FM Class Number 1319, ``Approval Standard for Centrifugal Fire
Pumps (Horizontal, End Suction Type),'' approved January 2015.
Copies of FM Class Number 1319 can be obtained from: FM Global,
1151 Boston-Providence Turnpike, P.O. Box 9102, Norwood, MA 02062,
(781) 762-4300, or by visiting www.fmglobal.com.
(2) American National Standards Institute (ANSI)/HI 1.1-1.2-2014
(``ANSI/HI 1.1-1.2-2014''), ``American National Standard for
Rotodynamic Centrifugal Pumps for Nomenclature and Definitions;''
approved October 30, 2014, sections 1.1, ``Types and nomenclature,''
and 1.2.9, ``Rotodynamic pump icons.''
(3) ANSI/HI 2.1-2.2-2014 (``ANSI/HI 2.1-2.2-2014 ''), ``American
National Standard for Rotodynamic Vertical Pumps of Radial, Mixed, and
Axial Flow Types for Nomenclature and Definitions,'' approved April 8,
2014, section 2.1, ``Types and nomenclature.''
(4) HI 40.6-2014, (``HI 40.6-2014'') ``Methods for Rotodynamic Pump
Efficiency Testing,'' (except for section 40.6.5.3, ``Test report;''
Appendix A, section A.7, ``Testing at temperatures exceeding 30 [deg]C
(86[emsp14][deg]F);'' and Appendix B, ``Reporting of test results
(normative);'') copyright 2014.
Copies of ANSI/HI 1.1-1.2-2014, ANSI/HI 2.1-2.2-2014, and HI 40.6-
2014 can be obtained from: the Hydraulic Institute at 6 Campus Drive,
First Floor North, Parsippany, NJ 07054-4406, (973) 267-9700, or by
visiting www.pumps.org.
(5) National Fire Protection Association (NFPA) 20-2016, ``Standard
for the Installation of Stationary Pumps for Fire Protection,'' 2016
Edition, approved June 15, 2015.
Copies of NFPA 20-2016 can be obtained from: the National Fire
Protection Association, 1 Batterymarch Park, Quincy, MA 02169, (617)
770-3000, or by visiting www.nfpa.org.
(6) UL 488, (``ANSI/UL 448-2013''), ``Standard for Safety
Centrifugal Stationary Pumps for Fire-Protection Service,'' 10th
Edition, June 8, 2007, including revisions through July 12, 2013.
Copies of ANSI/UL448-2013 can be obtained from: UL, 333 Pfingsten
Road, Northbrook, IL 60062, (847) 272-8800, or by visiting https://ul.com.
This material is also available for inspection at U.S. Department
of Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Program, Sixth Floor, 950 L'Enfant Plaza SW., Washington,
DC 20024, (202) 586-2945, or at https://energy.gov/eere/buildings/appliance-and-equipment-standards-program.
See section IV.N. for additional information about these standards.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Summary of the Final Rule
III. Discussion
A. Scope
1. Definitions Related to the Scope of Covered Pumps
2. Equipment Categories
3. Scope Exclusions Based on Application
4. Parameters for Establishing the Scope of Pumps in This
Rulemaking
5. Drivers Other Than Electric Motors
6. Pumps Sold With Single-Phase Induction Motors
B. Rating Metric: Constant and Variable Load Pump Energy Index
1. Determination of the Pump Energy Rating
2. PERSTD: Minimally Compliant Pump
C. Determination of Pump Performance
1. Incorporation by Reference of HI 40.6-2014
[[Page 4087]]
2. Minor Modifications and Additions to HI 40.6-2014
D. Determination of Motor Efficiency
1. Default Nominal Full Load Motor Efficiency
2. Represented Nominal Full Load Motor Efficiency for Pumps Sold
With Motors
3. Determining Part Load Motor Losses
E. Test Methods for Different Pump Configurations
1. Calculation-Based Test Methods
2. Testing-Based Methods
F. Representations of Energy Use and Energy Efficiency
G. Sampling Plans for Pumps
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
1. The Need for, and Objectives of, Today's Rule
2. Significant Issues From Interested Parties in Response to
IRFA
3. Revised Assessment of Burden Associated With This Test
Procedure Final Rule
4. Calculator Comments
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by Reference
V. Approval of the Office of the Secretary
I. Authority and Background
Pumps are included in the list of ``covered equipment'' for which
the U.S. Department of Energy (DOE) is authorized to establish and
amend energy conservation standards and test procedures. (42 U.S.C.
6311(1)(A)) However, there are not currently any Federal energy
conservation standards or test procedures for pumps. The following
sections discuss DOE's authority to establish test procedures for pumps
and relevant background information regarding DOE's consideration of
test procedures for this equipment.
A. Authority
The Energy Policy and Conservation Act of 1975 (EPCA), Public Law
94-163, as amended by Public Law 95-619, Title IV, Sec. 441(a),
established the Energy Conservation Program for Certain Industrial
Equipment under Title III, Part C (42 U.S.C. 6311-6317, as codified)
\1\ \2\ Included among the various types of industrial equipment
addressed by EPCA are pumps, the subject of this document. (42 U.S.C.
6311(1)(A))
---------------------------------------------------------------------------
\1\ For editorial reasons, Part C was codified as Part A-1 in
the U.S. Code.
\2\ All references to EPCA in this document refer to the statute
as amended through the Energy Efficiency Improvement Act of 2015,
Public Law 114-11 (April 30, 2015).
---------------------------------------------------------------------------
Under EPCA, the energy conservation program consists essentially of
four parts: (1) Testing, (2) labeling, (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. The
testing requirements consist of test procedures that manufacturers of
covered products must use as the basis for (1) certifying to DOE that
their products comply with the applicable energy conservation standards
adopted under EPCA, (42 U.S.C. 6295(s) and 6316(a)(1)), and (2) making
representations about the efficiency of that equipment. (42 U.S.C.
6314(d)) Similarly, DOE must use these test procedures to determine
whether the products comply with any relevant standards promulgated
under EPCA.
DOE is authorized to prescribe energy conservation standards and
corresponding test procedures for statutorily covered equipment such as
pumps. While DOE is currently evaluating whether to establish energy
conservation standards for pumps (Docket No. EERE-2011-BT-STD-0031),
DOE must first establish a test procedure that measures the energy use,
energy efficiency, or estimated operating costs of such equipment. See,
generally, 42 U.S.C. 6295(r) and 6316(a).
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered equipment. EPCA provides that any test procedures prescribed or
amended under this section shall be reasonably designed to produce test
results that measure energy efficiency, energy use or estimated annual
operating cost of a covered product during a representative average use
cycle or period of use, and shall not be unduly burdensome to conduct.
(42 U.S.C. 6314(a)(2))
In addition, before prescribing any final test procedures, DOE must
publish proposed test procedures and offer the public an opportunity to
present oral and written comments on them. (42 U.S.C. 6314(b)(1)-(2))
In this final rule, DOE is establishing a test procedure for pumps
concurrent with its ongoing energy conservation standards rulemaking
for this equipment (See Docket No. EERE-2011-BT-STD-0031). As discussed
further in section I.B, DOE published a notice of proposed rulemaking
(NOPR) on April 1, 2015 presenting and requesting public comment on
DOE's proposals related to pumps definitions, metric, and test
procedure requirements (April 2015 pump test procedure NOPR). 80 FR
17586.
The pumps test procedure adopted in this final rule includes
methods required to (1) measure the performance of the covered
equipment and (2) use the measured results to calculate a pump energy
index (PEICL for pumps sold without continuous or non-
continuous controls or PEIVL for pumps sold with continuous
or non-continuous controls) to represent the power consumption of the
pump, inclusive of a motor and any continuous or non-continuous
controls, normalized with respect to the performance of a minimally
compliant pump. In this final rule, DOE is also establishing the
specific styles and characteristics of pumps to which the test
procedure applies.
Manufacturers will be required to make all representations of pump
efficiency, overall (wire-to-water) efficiency, bowl efficiency, driver
power input, pump power input (brake or shaft horsepower), and/or pump
power output (hydraulic horsepower) using methods that will generate
values consistent with the DOE test procedure beginning 180 days after
the publication date of this final rule in the Federal Register.
Manufacturers also will be required to use the new test procedure and
metric when making representations regarding the PEICL,
PEIVL, PERCL, or PERVL of covered
equipment 180 days after the publication date of any applicable energy
conservation standards final rule in the Federal Register. However, DOE
notes that certification of compliance with any energy conservation
standards for pumps would not be required until the compliance date of
any final rule establishing such energy conservation standards. See 42
U.S.C. 6314(d) and Docket No. EERE-2011-BT-STD-0031.
B. Background
DOE does not currently regulate pumps. In 2011, DOE issued a
Request for Information (RFI) to gather data and information related to
pumps in anticipation of initiating rulemakings to formally consider
test procedures and energy conservation standards for this equipment.
76 FR 34192 (June 13, 2011). In February 2013, DOE published a Notice
of Public Meeting and Availability of the Framework document to
initiate an energy conservation standard rulemaking for pumps (78 FR
7304 Feb. 1, 2013) and
[[Page 4088]]
held a public meeting to discuss the Framework document (the ``pumps
Framework public meeting'').
Following the pumps Framework public meeting, DOE convened a
Commercial and Industrial Pumps Working Group (``CIP Working Group''
or, in context, ``Working Group'') through the Appliance Standards
Rulemaking Federal Advisory Committee (ASRAC) to negotiate standards
and test procedures for pumps as an alternative to the traditional
notice and comment rulemaking process that DOE had already begun.
(Docket No. EERE-2013-BT-NOC-0039) \3\ The CIP Working Group commenced
negotiations at an open meeting on December 18 and 19, 2013, and held
six additional meetings and two webinars to discuss definitions,
metrics, test procedures, and standard levels for pumps.\4\ The CIP
Working Group concluded its negotiations on June 19, 2014, with a
consensus vote to approve a term sheet containing recommendations to
DOE on appropriate standard levels for pumps as well as recommendations
addressing issues related to the metric and test procedure for pumps
(``Working Group recommendations'').\5\ Subsequently, ASRAC voted
unanimously to approve the Working Group recommendations during a July
7, 2014 webinar.
---------------------------------------------------------------------------
\3\ Information on the ASRAC, the CIP Working Group, and meeting
dates is available at https://energy.gov/eere/buildings/appliance-standards-and-rulemaking-federal-advisory-committee.
\4\ Details of the negotiation sessions can be found in the
public meeting transcripts that are posted to the docket for the
Working Group (https://www.regulations.gov/#!docketDetail;D=EERE-
2013-BT-NOC-0039).
\5\ The term sheet containing the Working Group recommendations
is available in the CIP Working Group's docket. (Docket No. EERE-
2013-BT-NOC-0039, No. 92) The ground rules of the CIP Working Group
define consensus as no more than two negative votes. (Docket No.
EERE-2013-BT-NOC-0039, No. 18 at p. 2) Concurrence was assumed if a
voting member was absent, and overt dissent was only evidenced by a
negative vote. Abstention was not construed as a negative vote.
---------------------------------------------------------------------------
Following approval of the Working Group recommendations, DOE
published a NOPR implementing the recommendations of the CIP Working
Group \6\ and proposing a new test procedure for pumps, as well as
associated definitions and parameters to establish the applicability of
the test procedure (April 2015 pump test procedure NOPR). 80 FR 17586
(April 1, 2015). On April 29, 2015, DOE held a public meeting to
discuss and request public comment on the April 2015 pumps test
procedure NOPR (April 2015 NOPR public meeting).
---------------------------------------------------------------------------
\6\ DOE's proposals in the April 2015 pumps test procedure NOPR
reflect the intent of the CIP Working Group recommendations.
However, DOE proposed some slight modifications and significant
additional detail to ensure the technical integrity, accuracy,
repeatability, and enforceability of the pumps test procedure and
scope.
---------------------------------------------------------------------------
DOE's test procedure for pumps, adopted in this final rule,
reflects certain recommendations of the CIP Working Group, as well as
input from interested parties received in response to the April 2015
pumps test procedure NOPR. Provisions of this final rule that are
directly pertinent to any of the 14 approved Working Group
recommendations will be specified with a citation to the specific
recommendation number (for example: Docket No. EERE-2013-BT-NOC-0039,
No. 92, Recommendation #X at p. Y). Additionally, in developing the
provisions of this final rule, DOE also has referenced discussions from
the CIP Working Group meetings regarding potential actions or comments
that may not have been formally approved as part of the Working Group
recommendations. These references to discussions or suggestions of the
CIP Working Group not found in the Working Group recommendations will
have a citation to meeting transcripts (for example: Docket No. EERE-
2013-BT-NOC-0039, No. X at p. Y).
Finally, in this final rule, DOE responds to all comments received
from interested parties in response to the proposals presented in the
April 2015 pumps test procedure NOPR, either during the April 2015 NOPR
public meeting or in subsequent written comments. In response to the
April 2015 pumps test procedure NOPR, DOE received eight written
comments in addition to the verbal comments made by interested parties
during the April 2015 NOPR public meeting. The commenters included:
Wilo USA, LLC (Wilo); the Hydraulic Institute (HI); the National
Electrical Manufacturers Association (NEMA); the Appliance Standards
Awareness Project (ASAP), Natural Resources Defense Council (NRDC),
Northwest Energy Efficiency Alliance (NEEA), and Northwest Power and
Conservation Council (NPCC), collectively referred to herein as the
energy efficiency advocates (EEAs); the Air-Conditioning, Heating, &
Refrigeration Institute (AHRI); the Association of Pool & Spa
Professionals (APSP); Pacific Gas and Electric Company (PG&E), Southern
California Gas Company (SCG), Southern California Edison (SCE), and San
Diego Gas and Electric Company (SDG&E), collectively referred to herein
as the CA IOUs. DOE will identify comments received in response to the
April 2015 pumps test procedure NOPR by the commenter, the number of
document as listed in the docket maintained at www.regulations.gov
(Docket No. EERE-2013-BT-TP-0055), and the page number of that document
where the comment appears (for example: HI, No. 8 at p. 4). If a
comment was made verbally during the NOPR public meeting, DOE will also
specifically identify those as being located in the NOPR public meeting
transcript (for example: HI, NOPR public meeting transcript, No. 7 at
p. 235). This final rule also contains comments submitted in response
to the pumps energy conservation standards rulemaking (Docket No. EERE-
2011-BT-STD-0031) and such comments will be identified with that docket
number.
II. Summary of the Final Rule
In this final rule, DOE is establishing a new subpart Y to part 431
of Title 10 of the Code of Federal Regulations that contains
definitions and a test procedure applicable to pumps. This final rule
also contains sampling plans for pumps for the purposes of making
representations regarding the energy consumption of applicable pumps
and demonstrating compliance with any energy conservation standards
that DOE adopts.
DOE notes that equipment meeting the pump definition is already
covered equipment. In this final rule, DOE is establishing definitions
for the term pump, certain pump components, and several categories and
configurations of pumps. While the range of equipment included in DOE's
definition of pump is broad, the test procedure established by this
rulemaking is limited to a specific scope of pumps, as described in
section III.A of this final rule; specifically certain kinds of
rotodynamic pumps \7\ for which standards are being considered in DOE's
energy conservation standards rulemaking. (Docket No. EERE-2011-BT-STD-
0031)
---------------------------------------------------------------------------
\7\ A rotodynamic (or centrifugal) pump is a kinetic machine
that continuously imparts energy to the pumped fluid by means of a
rotating impeller, propeller, or rotor. This kind of pump is in
contrast to positive-displacement pumps, which have an expanding
cavity on the suction side and a decreasing cavity on the discharge
side that move a constant volume of fluid for each cycle of
operation.
---------------------------------------------------------------------------
DOE's approach adopted in this final rule establishes a new metric,
the pump energy index (PEI), to rate the energy performance of pumps
subject to this test procedure. The test procedure contains methods for
determining constant load pump energy index (PEICL) for
pumps sold without continuous or non-continuous controls and the
variable load pump energy index (PEIVL) for pumps sold with
either
[[Page 4089]]
continuous or non-continuous controls. Both PEICL and
PEIVL describe the weighted average performance of the rated
pump at specific load points, normalized with respect to the
performance of a minimally compliant pump without controls.
The test procedure contains methods to determine the appropriate
index for all equipment for which this test procedure applies using
either calculation-based methods and/or testing-based methods. While
both methods include some amount of testing and some amount of
calculation, the terms ``calculation-based'' and ``testing-based'' are
used to distinguish between methods in which the input power to the
pump is determined either by (a) measuring the bare pump shaft input
power \8\ and calculating efficiency, or losses, of the motor and any
continuous control \9\ (i.e., calculation-based method) or (b)
measuring the input power to the driver,\10\ or motor, and any
continuous or non-continuous controls \11\ for a given pump directly
(i.e., testing-based method). For both the testing-based and
calculation-based approaches, the test procedure for pumps established
in this final rule is based on the test methods contained in HI
Standard 40.6-2014, ``Methods for Rotodynamic Pump Efficiency
Testing,'' (``HI 40.6-2014''), with slight modifications as noted in
section III.C.2.
---------------------------------------------------------------------------
\8\ The term ``pump shaft input power'' is referred to as ``pump
power input'' in HI 40.6-2014. The term ``pump shaft input power''
is used synonymously with that term in this document.
\9\ DOE notes that for non-continuous controls, as defined in
section III.E.1.c, PEIVL can only be determined using a
``testing-based'' method. If a calculation-based method is desired,
the pump would instead be rated as a pump sold with a motor and
without speed controls using the PEICL metric. See
section III.E.1.c for further discussion.
\10\ The input power to the driver is referred to as ``driver
power input'' in HI 40.6-2014. The term ``input power to the
driver'' is used synonymously with that term in this document.
\11\ In the case wherein a pump is sold with a motor equipped
with either continuous or non-continuous controls and is rated using
the testing-based method, the input power to the pump would be
determined as the input power to the continuous or non-continuous
control. See section III.E.2.c.
---------------------------------------------------------------------------
The test procedure also prescribes the specific categories and
configurations of pumps to which the calculation-based and testing-
based methods are applicable. As discussed further in section III.E.2,
the testing-based methods are applicable to all pumps that are subject
to the test procedure, while the calculation-based methods are only
applicable to (1) pumps sold with neither a motor nor controls (i.e.,
``bare pump,'' discussed later in section III.A.1.a), (2) pumps sold
with motors that are subject to DOE's energy conservation standards for
electric motors \12\ (with or without continuous controls), and (3)
pumps sold with submersible motors (with or without continuous
controls).
---------------------------------------------------------------------------
\12\ All references to ``motors that are subject to the DOE's
energy conservation standards for electric motors'' refer to those
motors that are subject to the energy conservation standards for
electric motors at 431.25(g) (as established in the May 2014 medium
electric motor energy conservation standard final rule. 79 FR 30933
(May 29, 2014)). See section III.D.1 and III.E.1 for more
discussion.
---------------------------------------------------------------------------
Regardless of the metric (i.e., PEICL versus
PEIVL) or test method (i.e., calculation-based versus
testing-based), the results for the given pump are divided by the
calculated input power to the motor for a hypothetical pump that serves
an identical hydraulic load and minimally complies with any energy
conservation standards that DOE may set as a result of the ongoing
standards rulemaking. (Docket No. EERE-2011-BT-STD-0031) This
normalized metric results in a value that is indexed to the standard
(i.e., a value of 1.0 for a pump that is minimally compliant, and a
value less than 1.0 for a pump that is less consumptive than the
maximum the standard allows).
This final rule also establishes requirements regarding the
sampling plan and representations for covered pumps at subpart B of
part 429 of Title 10 of the Code of Federal Regulations. The sampling
plan requirements are similar to those for several other types of
commercial equipment and are appropriate for pumps based on the
expected range of measurement uncertainty and manufacturing tolerances
for this equipment. For those pumps addressed by this test procedure,
DOE is also specifying the energy consumption or energy efficiency
representations that may be made, in addition to the regulated metric
(PEICL or PEIVL).
Beginning on the compliance date for any energy conservation
standards that DOE may set, all pumps within the scope of those energy
conservation standards would be required to be tested in accordance
with subpart Y of part 431 and must have their testing performed in a
manner consistent with the applicable sampling requirements.
Manufacturers must make all representations of pump efficiency, overall
(wire-to-water) efficiency, bowl efficiency, driver power input, pump
power input (brake or shaft horsepower), and/or pump power output
(hydraulic horsepower) using methods that will generate values
consistent with the DOE test procedure beginning 180 days after the
publication date of this final rule in the Federal Register. Similarly,
all representations regarding PEICL, PEIVL,
PERCL, or PERVL would be required to be made
based on values consistent with the adopted pump test procedure 180
days after the publication date of any final rule establishing energy
conservation standards for those pumps that are addressed by the test
procedure. See 42 U.S.C. 6314(d). DOE understands that manufacturers of
pumps likely have historical test data (e.g., existing pump curves)
which were developed with methods consistent with the DOE test
procedure being adopted in this final rule. DOE notes that it does not
expect manufacturers to regenerate all of the historical test data
unless the rating resulting from the historical methods, which is based
on the same methodology being adopted in this final rule, would no
longer be valid.
III. Discussion
This final rule places a new test procedure for pumps and related
definitions in a new subpart Y of part 431, and adds new sampling plans
and reporting requirements for this equipment in a new section 429.59
of 10 CFR part 429. Subpart Y contains definitions, materials
incorporated by reference, and the test procedure for certain
categories and configurations of pumps established as a result of this
rulemaking, as well as any energy conservation standards for pumps
resulting from the ongoing energy conservation standard rulemaking, as
shown in Table III.1. (Docket No. EERE-2011-BT-STD-0031)
Table III.1--Summary of Relevant Provisions Addressed in This Final Rule, Their Location Within the Code of
Federal Regulations, and the Applicable Preamble Discussion
----------------------------------------------------------------------------------------------------------------
Applicable preamble
Location Proposal Summary of additions discussion
----------------------------------------------------------------------------------------------------------------
10 CFR 429.59 *.................... Sampling Plan......... Number of pumps to be Section III.G.
tested to rate a pump
basic model and
calculation of rating.
[[Page 4090]]
10 CFR 431.461..................... Purpose and Scope..... Scope of pump regulations, Section III.A.
as well as the proposed
test procedure and
associated energy
conservation standards.
10 CFR 431.462..................... Definitions........... Definitions pertinent to Section III.A.
establishing equipment
classes and testing
applicable classes of
pumps.
10 CFR 431.463..................... Incorporation by Description of industry Sections III.A and
Reference. standards incorporated by III.C.
reference in the DOE test
procedure or related
definitions.
10 CFR 431.464 and Appendix A to Test Procedure........ Instructions for Sections III.B, III.C,
Subpart Y of Part 431. determining the PEICL or III.D, and III.E.
PEIVL for applicable
classes of pumps.
10 CFR 431.466..................... Energy Conservation Energy conservation Section III.A and
Standards. standard for applicable Docket EERE-2011-BT-
classes of pumps, in terms STD-0031.
of PEI and associated C-
Value.
----------------------------------------------------------------------------------------------------------------
* Note: DOE is also making minor modifications to 10 CFR 429.2; 429.11(a) and (b); 429.12(b)(13); 429.70;
429.72; 429.102; and 429.134 to apply the general sampling requirements established in these sections to the
equipment-specific sampling requirements for pumps at 10 CFR 429.59.
The following sections discuss DOE's new provisions regarding
testing and sampling requirements for pumps, including:
(1) Scope,
(2) rating metric,
(3) determination of pump performance,
(4) determination of motor efficiency,
(5) test methods for different combinations of bare pumps, drivers
and controls,
(6) representations, and
(7) sampling plans.
These sections also present any pertinent comments DOE received in
response to the April 2015 pumps test procedure NOPR or the parallel
pumps energy conservation standards rulemaking (Docket No. EERE-2011-
BT-STD-0031), as well as DOE's responses to those comments and the
resulting changes to the test procedure as proposed in the NOPR.
A. Scope
The term ``pump'' is listed as a type of covered equipment under
EPCA; however, that term is undefined. See 42 U.S.C. 6311(1)(A). In the
April 2015 pumps test procedure NOPR, consistent with recommendations
from the CIP Working Group (Docket No. EERE-2013-BT-NOC-0039, No. 92,
Recommendations #4 and 6-8 at pp. 2-4), DOE proposed definitions for
the term pump, as covered equipment, and related components of pumps.
80 FR 17586, 17591 (April 1, 2015). In addition, DOE proposed to define
which pumps would need to be tested using the test procedure
established in this rulemaking by applying three criteria: (1) The
equipment category; (2) the application; and (3) applicable performance
specifications--i.e., horsepower (hp), flow rate, head, design
temperature, and speed restrictions. Id.
In response to DOE's proposed definitions and scope of the test
procedure for pumps, HI commented that it detected no inconsistencies
with the scope of the pump test procedure and energy conservation
standard rulemakings. (HI, No. 8 at p. 4)
DOE's criteria for establishing which pumps will be subject to the
test procedure, including any additional comments received by
interested parties on those particular topics, are discussed in
sections III.A.1 through III.A.6, respectively.
1. Definitions Related to the Scope of Covered Pumps
To help explain the scope for this rule and the manner in which
both the procedure and related standards will be applied to different
pump configurations and categories of pumps, the aforementioned
definitions for pump, certain pump components, and other specific pump
characteristics, are discussed in the following subsections.
a. Pumps and Related Components
As part of its collective efforts to help DOE craft an appropriate
regulatory approach to pumps, the CIP Working Group made a series of
recommendations regarding a variety of potential definitions that would
define ``pump,'' the covered equipment. In particular, the Working
Group offered a definition for ``pump'' along with the related terms
``bare pump,'' ``mechanical equipment,'' ``driver,'' and ``controls.''
(Docket No. EERE-2013-BT-NOC-0039, No. 92, Recommendations #1 and 2 at
pp. 1-2) Accordingly, in the April 2015 pumps test procedure NOPR, DOE
proposed adopting these recommended definitions with slight
modification. 80 FR 17586, 17591 (April 1, 2015). Specifically, in the
April 2015 pumps test procedure NOPR, DOE proposed the following terms:
Pump means equipment that is designed to move liquids
(which may include entrained gases, free solids, and totally dissolved
solids) by physical or mechanical action and includes at least a bare
pump and, if included by the manufacturer at the time of sale,
mechanical equipment, driver, and controls.
Bare pump means a pump excluding mechanical equipment,
driver, and controls.
Mechanical equipment means any component of a pump that
transfers energy from a driver to the bare pump.
Driver means the machine providing mechanical input to
drive a bare pump directly or through the use of mechanical equipment.
Examples include, but are not limited to, an electric motor, internal
combustion engine, or gas/steam turbine.
Control means any device that can be used to operate the
driver. Examples include, but are not limited to, continuous or non-
continuous controls, schedule-based controls, on/off switches, and
float switches.
80 FR 17586, 17591-92 (April 1, 2015).
HI expressed agreement with the proposed definitions, except for
the text ``entrained gases'' in the proposed definition for pump. HI
indicated that the text ``entrained gasses'' should be changed to
``dissolved gasses'' because pumps within scope are not designed to
pump entrained gas, and small amounts
[[Page 4091]]
of entrained gas would result in a loss of performance and efficiency.
(HI, No. 8 at p. 4)
DOE understands that, whereas dissolved gases are in solution and
would not appear as bubbles in the pumped liquid, entrained gases are
not in solution and would appear as bubbles in the pumped liquid. In
addition, DOE agrees that pumps within the scope of this rulemaking are
not designed to pump entrained gas. This has been acknowledged through
the definition of ``clean water pump,'' as described in section III.A.3
of this final rule, which specifies that the total gas content of the
water must not exceed the saturation volume.\13\ However, the
definition for ``pump'' applies in general to all pumps, which are
covered under EPCA (see 42 U.S.C. 6311(1)(A)), and is broader than the
scope of this rulemaking. Changing the language in the definition of
``pump'' from ``dissolved gasses'' to ``entrained gasses'' would
suggest that DOE's coverage of pumps was limited. In addition, such a
change would limit DOE's coverage to a subset of the pumps intended by
the Working Group and proposed in the NOPR. Therefore, DOE declines to
make the requested change.
---------------------------------------------------------------------------
\13\ In general, entrained gasses, or gas bubbles, will only
form when the total gas content of the water is above the saturation
volume of the liquid. Otherwise, gases are more likely to stay
dissolved in the liquid and not generate gas bubbles.
---------------------------------------------------------------------------
DOE did not receive comments on other aspects of the ``pump''
definition or on the other terms discussed in this section. As such,
DOE is adopting definitions for the terms ``pump,'' ``bare pump,''
``mechanical equipment,'' ``driver,'' and ``control'' as proposed in
the April 2015 pumps test procedure NOPR without further changes.
b. Definition of Categories of Controls
The definition of ``control'' established in this final rule is
broad. DOE acknowledges the definition may include many different kinds
of electronic or mechanical devices that can ``control the driver'' of
a pump (e.g., continuous or non-continuous controls, timers, and on/off
switches). These various controls may use a variety of mechanisms to
control the pump for operational reasons, which may or may not result
in reduced energy consumption.
In the April 2015 pumps test procedure NOPR, DOE proposed specific
test methods for pumps that are sold with motors that are paired with
controls that adjust the speed of the driver, as DOE determined that
these were the most common type of controls that reduced energy
consumption in the field. Similarly, DOE proposed that such pumps
equipped with speed controls could apply the PEIVL metric.
80 FR 17586, 17592-93 (April 1, 2015). Additionally, DOE proposed that
pumps sold with motors and controls other than speed controls \14\
would be subject to the appropriate bare pump and motor test procedures
and rated using PEICL. Id.
---------------------------------------------------------------------------
\14\ Here and throughout this final rule, DOE uses the term
``speed controls'' to refer to continuous and non-continuous
controls, as defined in section III.A.1.b of this document.
---------------------------------------------------------------------------
To explicitly establish the kinds of controls that may apply the
PEIVL metric under the test procedure, DOE proposed to
define the terms ``continuous control'' and ``non-continuous control''
(see sections III.B and III.E for further discussion of the
PEIVL rating metric and its applicability to pumps with
controls, respectively):
Continuous control means a control that adjusts the speed
of the pump driver continuously over the driver operating speed range
in response to incremental changes in the required pump flow, head, or
power output.\15\ As an example, variable speed drives (VSDs),
including variable frequency drives and electronically commutated
motors (ECMs), meet the definition for continuous controls.
---------------------------------------------------------------------------
\15\ HI-40.6, as incorporated by reference, defines pump power
output as ``the mechanical power transferred to the liquid as it
passes through the pump, also known as pump hydraulic power.''
---------------------------------------------------------------------------
Non-continuous control means a control that adjusts the
speed of a driver to one of a discrete number of non-continuous preset
operating speeds, and does not respond to incremental reductions in the
required pump flow, head, or power output. As an example, multi-speed
motors such as two-speed motors meet the definition for non-continuous
controls.
80 FR 17586, 17592-93 (April 1, 2015).
DOE requested comment on the proposed definitions of ``continuous
control'' and ``non-continuous control.'' DOE also requested comment on
the likelihood of a pump with continuous or non-continuous controls
being distributed in commerce, but never being paired with any sensor
or feedback mechanisms that would enable energy savings. In response,
HI commented that it agrees with the proposed definitions for
continuous control and non-continuous control, and that it does not
have data on pumps with speed controls being distributed in commerce
without any sensor or feedback mechanisms. (HI, No. 8 at p. 4)
During the public meeting, Regal Beloit requested a clarification
related to DOE's definitions of continuous control and non-continuous
control. Specifically, Regal Beloit requested clarification regarding
whether pumps sold with multi-pole motors and ``single-speed controls,
which would be considered multi-speed,'' would be classified as pumps
sold with non-continuous controls. (Regal Beloit, NOPR public meeting
transcript, No. 7 at p. 98). With respect to Regal Beloit's use of the
term ``single-speed controls,'' DOE believes that Regal Beloit is
referring to ``multi-speed'' permanent split capacitor (PSC) motors,
which are PSC motors that are offered with two or more discrete speed
options. Depending on the specific model, speeds may be adjusted
manually with a switch or automatically with a type of control logic.
Similarly, multi-pole motors are induction motors that are offered with
two or more discrete speed options. Again, speeds may be adjusted
manually with a switch or automatically with a type of control logic.
In this final rule, DOE clarifies that, to the extent multi-pole
motors and multi-speed PSC motors control the driver speed discretely
(via manual switch or control logic) in response to incremental
reductions in the required flow, head, or pump power output, such
motors would meet the definition of non-continuous controls and would
be tested in accordance with the applicable test procedure for pumps
sold with motors and non-continuous controls (see section III.E). DOE
also clarifies in this final rule that any control that can achieve the
specified load points on the reference system curve (see section
III.E.2.c) meets DOE's definition of continuous control, as it can
achieve the specific flow rate and head values specified by the
reference system curve in the test procedure.
CA IOUs asked during the April 2015 NOPR public meeting whether DOE
would consider differentiating between two-speed and multi-speed
motors, and stated that if more discrete speeds are available there is
more opportunity to match the pump and motor to the load. (CA IOUs,
NOPR public meeting transcript, No. 7 at pp. 98-99) DOE believes that
in this context, CA IOUs is referring to ``multi-speed motors'' as
motors with more than two discrete speeds.
DOE believes the definition of non-continuous control adequately
covers all motors with two or more discrete speeds that are sold with
any control mechanism that controls the motor speed discretely (e.g.,
manual switch or control logic). Furthermore, the test procedure for
pumps sold with motors and non-continuous controls, as proposed in the
April 2015 pumps test procedure NOPR, contains provisions
[[Page 4092]]
that will typically allow motors with three or more speeds to achieve a
lower (less consumptive) PEIVL rating than motors with only
two speeds. This procedure is outlined in detail in section III.E.2.c.
Consequently, DOE believes that motors with differing numbers of
discrete speed options are already differentiated in the proposed test
procedure and has determined that it is not necessary to further
differentiate between two-speed and multi-speed motors.
After considering HI's agreement with the proposed definitions and
the questions raised by Regal Beloit and CA IOUs, DOE is adopting, in
this final rule, the definitions for continuous and non-continuous
controls, as proposed in the April 2015 pumps test procedure NOPR.
c. Definition of Basic Model
In the course of regulating consumer products and commercial and
industrial equipment, DOE has developed the concept of a ``basic
model'' to determine the specific product or equipment configuration(s)
to which the regulations would apply. For the purposes of applying
pumps regulations, DOE proposed to define what constitutes a basic
model of pump.
In the April 2015 pumps test procedure NOPR, DOE defined a basic
model in a manner similar to the definitions used for other commercial
and industrial equipment, with the exception of two pump-specific
issues. Specifically, DOE proposed to define basic model as it applies
to pumps to include all units of a given covered equipment type (or
class thereof) manufactured by one manufacturer, having the same
primary energy source, and having essentially identical electrical,
physical, and functional (or hydraulic) characteristics that affect
energy consumption, energy efficiency, water consumption, or water
efficiency; except that:
(1) Variation in the number of stages particular radially split,
multi-sage vertical in-line casing diffuser (RSV) \16\ and vertical
turbine submersible (VTS) pump units are sold with would not result in
different basic models; and
---------------------------------------------------------------------------
\16\ The acronym RSV abbreviates ``radially split vertical,''
which is a key characteristic of the radially split, multi-stage
vertical in-line casing diffuser equipment category.
---------------------------------------------------------------------------
(2) pump models for which the bare pump differs in impeller
diameter, or impeller trim, may be considered a single basic model.
80 FR 17586, 17593 and 17641 (April 1, 2015).
The first modification to the basic model definition applies to
variation in the number of stages for multi-stage bare pumps,\17\ which
DOE believes will significantly reduce testing burden and is consistent
with DOE's proposed test procedure provision that such pumps be tested
with a specific number of stages, as discussed in section III.C.2.c.
DOE did not receive any comments on the exception to the general basic
model definition that different stage versions of multi-stage pumps
would be treated as the same basic model and, as such, is adopting this
pump-specific provision as proposed, with minor wording revisions for
clarity.
---------------------------------------------------------------------------
\17\ The implications of the resulting variation in motor
selection for pumps sold with motors or motors and controls is
discussed in section III.A.1.d.
---------------------------------------------------------------------------
The second modification to the typical basic model definition
proposed in the April 2015 pumps test procedure NOPR was that a trimmed
impeller, though it may impact efficiency, would not be a basis for
requiring different bare pump models to be rated as unique basic
models.\18\ DOE also proposed to base the certified rating for a given
pump basic model on that model's full impeller diameter--specifically,
all PEI and PER representations for the members of a basic model would
be based upon the full impeller model. 80 FR 17586, 17593-94 (April 1,
2015). This proposal is consistent with the Working Group
recommendation that the rating of a given pump basic model should be
based on testing at full impeller diameter only and that DOE not
require testing at reduced impeller diameters. (Docket No. EERE-2013-
BT-NOC-0039, No. 92, Recommendation #7 at p. 3)
---------------------------------------------------------------------------
\18\ The implications of the resulting variation in motor
selection for pumps sold with motors or motors and controls is
discussed in section III.A.1.d.
---------------------------------------------------------------------------
Relevant to this proposed requirement, DOE proposed to define the
term ``full impeller'' as it pertains to the rating of pump models in
accordance with the test procedure. Specifically, DOE proposed to
define full impeller as the maximum diameter impeller with which the
pump is distributed in commerce in the United States or the maximum
impeller diameter represented in the manufacturer's literature,
whichever is larger. For pumps that may only be sold with a trimmed
impeller due to a custom application, DOE proposed to define the full
impeller as the maximum diameter impeller with which the pump is
distributed in commerce. 80 FR 17586, 17593-94 (April 1, 2015)
Under DOE's proposed definition of ``full impeller,'' manufacturers
would also be able to represent a model with a trimmed impeller as less
consumptive than one with a full impeller. To do so, they would treat
that trimmed impeller model as a different basic model and test a
representative number of units at the maximum diameter distributed in
commerce of that trimmed basic model listing. In such a case, the
impeller trim with which the pump is rated would become the ``full
impeller diameter.'' In these cases, manufacturers could elect to (1)
group individual pump units with bare pumps that vary only in impeller
diameter into a single basic model or (2) establish separate basic
models (with unique ratings) for any number of unique impeller trims,
provided that the PEI rating associated with any individual model were
based on the maximum diameter impeller for that basic model and that
basic model is compliant with any energy conservation standards
established as part of the parallel pumps energy conservation standards
rulemaking. (Docket No. EERE-2011-BT-STD-0031; 80 FR 17586, 17593-94
(April 1, 2015)).
DOE noted that, while manufacturers would be able to group pump
models with various impeller trims under one basic model with the same
certified PEI rating based on the full impeller diameter, all
representations of PEI and PER for any individual model would be (1)
based on testing of the model with the full impeller diameter in the
basic model and (2) rated using method A.1, ``bare pump with default
motor efficiency and default motor part load loss curve'' (explained
further in section III.E), regardless of the actual impeller size used
with a given pump. Id.
At the April 2015 NOPR public meeting, interested parties
representing HI \19\ expressed concern regarding the option to consider
pumps with trimmed impellers as separate basic models. Specifically,
one HI representative from Patterson Pump Company noted that the
premise was contrary to the Working Group's agreement that all
representations for PEI would be done using full impeller diameter, not
trimmed impeller diameter. Another HI representative from Xylem (Mark
Handzel) stated that reporting is greatly simplified if only reported
for full impeller diameter. (HI, NOPR public meeting transcript, No. 7
at pp. 29, 32). The CA IOUs responded that the Working Group had only
agreed to what was going to be required for reporting on a mandatory
basis, and that its
[[Page 4093]]
preference was to maintain the flexibility for manufacturers to
voluntarily report the information for pumps with trimmed impellers.
(CA IOUs, NOPR public meeting transcript, No. 7 at pp. 34, 36)
Furthermore, in its written comments, HI agreed with the proposed
definition of the term ``basic model,'' which allows manufacturers the
option of rating pumps with trimmed impellers as a single basic model
or separate basic models. (HI, No. 8 at p. 4) HI also agreed with DOE's
proposed definition of full impeller and the proposal that all pump
models be rated in a full impeller configuration only. (HI, No. 8 at p.
5)
---------------------------------------------------------------------------
\19\ Several interested parties identified themselves as
representing HI at the April 2015 NOPR public meeting, including Bob
Barbour from TACO, Inc.; HI representatives from Xylem (Mark Handzel
and Raul Ruzicka), and Al Huber from Patterson Pump Company.
---------------------------------------------------------------------------
In response, DOE reaffirms that only reporting PEI at full impeller
diameter will be mandatory. Given that some interested parties stated
that they prefer maintaining the option of rating pumps with trimmed
impellers as separate basic models, and HI did not indicate concern
with this option in the written comments, DOE is maintaining the option
to rate pumps with trimmed impellers as separate basic models in this
final rule. Furthermore, DOE notes that in the case a manufacturer
chooses to rate pumps with trimmed impellers as separate basic models,
the full impeller definition is still applicable and all
representations regarding the PEI and PER must be based on the ``full
impeller'' diameter for that basic model.
Upon further review of the proposed definition for ``full
impeller,'' DOE has determined that the language within the definition
is duplicative, and therefore, potentially confusing. Specifically, in
the proposed definition, DOE referred to both distribution in commerce
and representations in manufacturer literature. However, DOE notes that
42 U.S.C. 4291(16) defines distribution in commerce as meaning ``to
sell in commerce, to import, to introduce or deliver for introduction
into commerce, or to hold for sale or distribution after introduction
into commerce.'' This definition encompasses making advertising
materials such as representations in manufacturer literature.
Accordingly, DOE has revised the definition for full impeller diameter
as set forth in the regulatory text of this rule (10 CFR 431.62).
d. Basic Models of Pumps Sold With Motors or Motors and Speed Controls
In the April 2015 pumps test procedure NOPR, DOE noted that, for
pumps sold with motors and pumps sold with motors and continuous or
non-continuous controls, pump manufacturers may pair a given pump with
several different motors that have different performance
characteristics. 80 FR 17586, 17594 (April 1, 2015). Under the
definition of basic model proposed in the April 2015 pumps test
procedure NOPR and discussed in section III.A.1.c, each unique pump and
motor pairing represents a unique basic model. However, DOE noted that,
consistent with DOE's practice with other products and equipment, pump
manufacturers may elect to group similar individual pump models within
the same equipment class into the same basic model to reduce testing
burden, provided all representations regarding the energy use of pumps
within that basic model are identical and based on the most consumptive
unit. See 76 FR 12422, 12423 (March 7, 2011). In addition, consistent
with DOE's treatment of variation in the number of stages for multi-
stage RSV and VTS pumps and impeller trim, in the April 2015 pump test
procedure NOPR, DOE proposed that variation in motor sizing as a result
of different impeller trims or different number of stages for multi-
stage pumps would not serve as a basis for differentiating basic
models. 80 FR 17586, 17593 (April 1, 2015)
In response, HI recommended that DOE clarify the definition of
``basic model,'' stating that ``pump manufacturers may pair a given
pump with several different motors with different performance
characteristics, and can include all combinations under one basic model
as long as the representations regarding the energy use is based on the
most consumptive unit for each given pole speed, given clean water with
a specific gravity of 1.0 . . . [A]s variation in impeller trim of the
bare pump does not constitute a characteristic that would differentiate
basic models, variation in motor sizing as a result of different
impeller trims would also not serve as a basis for differentiating
basic models.'' (HI, No. 8 at p. 5)
In general, DOE agrees with HI's interpretation. DOE agrees with HI
that pump manufacturers may pair a given pump with several different
motors with different performance characteristics, and can include all
combinations under one basic model if the certification of energy use
and all representations made by the manufacturer, are based on the most
consumptive bare pump/motor combination for each basic model and are
determined in accordance with the DOE test procedure and applicable
sampling plans. Furthermore, because variation in impeller trim of the
bare pump is not a basis for requiring models to be rated as unique
basic models, DOE agrees that variation in the horsepower rating of the
paired motor as a result of different impeller trims within a basic
model would also not necessarily be a basis for requiring units to be
rated as unique basic models. Similarly since RSV and VTS pumps may be
sold with varying numbers of stages, the horsepower rating of the
paired motor may also vary correspondingly. DOE notes that this
variation in motor horsepower does not necessarily constitute a
characteristic that will define separate basic models.
However, variation in motor sizing (i.e., horsepower rating) may
also be associated with variation in motor efficiency, which is a
performance characteristic; typically larger motors are more efficient
than smaller motors. For this reason, in response to HI, DOE clarifies
that in order to group pumps sold with motors (or motors and controls)
into a single basic model (in contrast to grouping bare pumps with
variations in impeller trim into a single basic model, as discussed in
the previous section), each motor offered in a pump included in that
basic model must have motor efficiency rated at the Federal minimum
(see the appropriate table for NEMA Design B motors at 10 CFR 431.25)
\20\ or the same number of bands above the Federal minimum for each
respective motor horsepower (see Table 3 of Appendix A to Subpart Y of
Part 431).) \21\ For example, the Federal minimum for a NEMA Design B 5
HP, 2-pole, enclosed motor in 10 CFR 431.25 is 88.5. A manufacturer is
rating the pump and motor combination with a 90.2 percent efficient
motor. In Table 3 of Appendix A to Subpart Y of Part 431, 90.2 is two
bands above 88.5. Therefore, for a NEMA Design B 3 HP, 2-pole enclosed
motor, in order to be considered as the same basic model, the
manufacturer cannot distribute it with a motor with an efficiency less
than 88.5 percent, which in Table 3 is two bands above the Federal
minimum. If the manufacturer wishes to rate it with a less efficient
motor, it must be rated as a separate basic model. This approach will
ensure that the PEI and PER representations for the entire basic model
will be representative of the performance across various impeller trims
and motor horsepower. DOE has added this clarification to the
definition of basic model.
---------------------------------------------------------------------------
\20\ For submersible motors, refer to the default motor
efficiency values in this test procedure, shown in Table 2 of
Appendix A to Subpart Y of Part 431, with further discussion in
section III.D.1.b.
\21\ See section III.D.1.b for further discussion of Table 3.
---------------------------------------------------------------------------
DOE did not receive any other comments from interested parties
regarding basic models for pumps sold
[[Page 4094]]
with motors or motors and speed controls.
2. Equipment Categories
In the April 2015 pumps test procedure NOPR, DOE proposed that the
test procedure be applicable to the following pump equipment
categories: end suction close-coupled (ESCC), end suction frame mounted
(ESFM), in-line (IL), RSV, and VTS pumps. 80 FR 17586, 17594-95 (April
1, 2015). DOE also proposed that the test procedure would not be
applicable to certain categories of pumps, including circulators,
dedicated purpose pool pumps, axial/mixed flow pumps, and positive
displacement pumps. Id. at 17597. These proposals were based on the
recommendation of the Working Group. (Docket No. EERE-2013-BT-NOC-0039,
No. 92, Recommendation #4, 5A, 5B, and 6 at p. 2) DOE also noted that,
while intended to be consistent with this test procedure, the scope of
any energy conservation standards proposed for pumps would be discussed
as part of a separate rulemaking. Id.
DOE requested comment on the proposed applicability of the test
procedure to the five pump equipment categories noted above, namely
ESCC, ESFM, IL, RSV, and VTS pumps. HI commented that it agrees that
the proposed test procedure was applicable to the five pump equipment
categories noted. (HI, No. 8 at p. 5) HI also agreed that circulators
and pool pumps should be handled under two separate rulemakings. (HI,
No. 8 at p. 7) No other interested parties provided comments on the
scope of applicability of the proposed test procedure. As the
amendments DOE is making to the proposed test procedure provisions do
not significantly change the test methods or approach specified in the
pump test procedure, and receiving no dissenting comments, DOE adopts
its proposal that the test procedure provisions established in this
final rule are applicable to the same scope of pumps discussed in the
April 2015 pumps test procedure NOPR. 80 FR 17586, 17591-17601 (April
1, 2015).
The specific definitions and specifications DOE proposed to
establish the scope of the test procedure, and any comments DOE
received on those definitions, are discussed in the subsequent sections
III.A.2.a, III.A.2.b, III.A.2.c, and III.A.2.d. The final equipment
category definitions DOE is adopting in this final rule are presented
in section III.A.2.e.
a. Definitions of Pump Equipment Categories
As noted, in the April 2015 pumps test procedure NOPR, DOE proposed
specific definitions for the five categories of pumps (i.e., ESCC,
ESFM, IL, RSV, and VTS) to establish the pumps to which the proposed
test procedure is applicable. 80 FR 17586, 17595-96 and 17641-42 (April
1, 2015). To assist in defining these five pump categories, DOE also
proposed the following definitions for several specific characteristics
of the five pumps categories for which the test procedure is
applicable--namely rotodynamic pump, single-axis flow pump, and end
suction pump:
Rotodynamic pump means a pump in which energy is
continuously imparted to the pumped fluid by means of a rotating
impeller, propeller, or rotor.
Single axis flow pump means a pump in which the liquid
inlet of the bare pump is on the same axis as the liquid discharge of
the bare pump.
End suction pump means a rotodynamic pump that is single-
stage and in which the liquid enters the bare pump in a direction
parallel to the impeller shaft and on the end opposite the bare pump's
driver-end.
Id.
Based on these three definitions involving general pump
characteristics, DOE proposed to define the following five pump
equipment categories to which the test procedure applies as follows:
(1) End suction frame mounted (ESFM) pump means an end suction pump
wherein:
(a) the bare pump has its own impeller shaft and bearings and so
does not rely on the motor shaft to serve as the impeller shaft;
(b) the pump requires attachment to a rigid foundation to function
as designed and cannot function as designed when supported only by the
supply and discharge piping to which it is connected; and
(c) the pump does not include a basket strainer.
Examples include, but are not limited to, pumps complying with
ANSI/HI nomenclature OH0 and OH1, as described in ANSI/HI 1.1-1.2-2014.
(2) End suction close-coupled (ESCC) pump means an end suction pump
in which:
(a) the motor shaft also serves as the impeller shaft for the bare
pump;
(b) the pump requires attachment to a rigid foundation to function
as designed and cannot function as designed when supported only by the
supply and discharge piping to which it is connected; and
(c) the pump does not include a basket strainer.
Examples include, but are not limited to, pumps complying with
ANSI/HI nomenclature OH7, as described in ANSI/HI 1.1-1.2-2014.
(3) In-line (IL) pump means a single-stage, single axis flow,
rotodynamic pump in which:
(a) liquid is discharged through a volute in a plane perpendicular
to the impeller shaft; and
(b) the pump requires attachment to a rigid foundation to function
as designed and cannot function as designed when supported only by the
supply and discharge piping to which it is connected.
Examples include, but are not limited to, pumps complying with
ANSI/HI nomenclature OH3, OH4, or OH5, as described in ANSI/HI 1.1-1.2-
2014.
(4) Radially split, multi-stage, vertical, in-line, diffuser casing
(RSV) pump means a vertically suspended, multi-stage, single axis flow,
rotodynamic pump in which:
(a) liquid is discharged in a plane perpendicular to the impeller
shaft;
(b) each stage (or bowl) consists of an impeller and diffuser; and.
(c) no external part of such a pump is designed to be submerged in
the pumped liquid.
Examples include, but are not limited to, pumps complying with
ANSI/HI nomenclature VS8, as described in the ANSI/HI 2.1-2.2-2008).
(5) Vertical turbine submersible (VTS) pump means a single-stage or
multi-stage rotodynamic pump that is designed to be operated with the
motor and stage(s) (or bowl(s)) fully submerged in the pumped liquid,
and in which:
(a) each stage of this pump consists of an impeller and diffuser
and
(b) liquid enters and exits each stage of the bare pump in a
direction parallel to the impeller shaft.
Examples include, but are not limited to, pumps complying with
ANSI/HI nomenclature VS0, as described in ANSI/HI 2.1-2.2-2008.
Id.
In the April 2015 pumps test procedure NOPR, DOE requested comment
on the proposed equipment category definitions and related terminology.
Comments DOE received on these definitions and DOE's responses to those
comments are discussed in the following subsections. DOE notes that
comments regarding the exclusion of circulators and dedicated-purpose
pool pumps, which are addressed in sections III.A.2.b and
[[Page 4095]]
III.A.2.c of this final rule, are also pertinent to the definitions of
the ESCC, ESFM, IL, RSV, and VTS equipment categories and are also
discussed in this section.
HI Nomenclature
DOE noted that any references to HI nomenclature in ANSI/HI 1.1-
1.2-2014 or ANSI/HI 2.1-2.2-2008 were incorporated into the definitions
of the aforementioned pump equipment categories as examples only and
clarified that, in cases where there is a conflict between the
description provided in ANSI/HI 1.1-1.2-2014 or ANSI/HI 2.1-2.2-2008,
as applicable, and DOE's definitions established at 10 CFR 431.462, the
language in the regulatory text would prevail. Id.
DOE requested comment on whether the references to ANSI/HI
nomenclature are necessary as part of the equipment definitions in the
regulatory text; whether such references would be likely to cause
confusion due to inconsistencies; and whether discussing the ANSI/HI
nomenclature in this preamble would provide sufficient reference
material for manufacturers when determining the appropriate equipment
category for their pump models. At the April 2015 NOPR public meeting,
an HI representative from Xylem (Mark Handzel) advocated the use of
ANSI/HI nomenclature without new DOE nomenclature. (HI, NOPR public
meeting transcript, No. 7 at p. 63) In written comments, HI indicated
that it affirms the importance of any pump rulemaking using ANSI/HI
designations and nomenclature, citing common usage by U.S. pump
manufacturers, distributors, engineering consulting firms, and pump
users. (HI, No. 8 at p. 6) HI also commented that all references to
ANSI/HI 2.1-2.2-2008 should be changed to ANSI/HI 2.1-2.2-2014 because
the latter is the current version. (HI, No. 8 at p. 13) The EEAs
commented that they support the proposed definitions for the pump types
to which the proposed test procedures would be applicable; they also
indicated that they believe this approach would both limit the risk
that a manufacturer could make a small change to a pump design in order
to avoid having to meet the pump efficiency standards and help to
provide clarity to manufacturers. (EEAs, No. 10 at p. 1)
After reviewing the comments, DOE is maintaining its definitions
for the pump equipment categories presented in the April 2015 pumps
test procedure NOPR, which references the ANSI/HI nomenclature as
illustrative only. DOE believes that this approach strikes the best
balance between the needs of the industry and the ability of DOE to
enforce its regulations for pumps appropriately. DOE reiterates that
the scope of the rulemaking is not limited to pumps meeting the ANSI/HI
nomenclature referenced in the definitions and that any pump model
meeting one of the DOE equipment category definitions is considered to
be part of that equipment category, whether or not the pump is
considered by the industry to be part of one of the referenced ANSI/HI
nomenclature subgroups or a different subgroup.
Further, in preparing this final rule, DOE reviewed the ANSI/HI
nomenclature to ensure that all applicable categories of pumps that
would meet DOE's proposed equipment definitions were listed. Upon
review, DOE noticed that the styles of pumps identified as OH2, OH3A,
OH5A, and OH6 in ANSI/HI 1.1-1.2-2014 may be considered by some parties
to meet ESCC, ESFM, or IL pump definitions because they share some
similar characteristics with those categories of pumps. DOE wishes to
clarify that the styles of pumps generally considered to be OH2, OH3A,
OH5A, and OH6 are covered equipment in that they meet the definition of
``pump,'' but are not subject to the test procedure established in this
final rule, since they do not fall within the specific scope of pumps
to which the test procedure is applicable. Specifically, DOE determined
that OH3A and OH5A are not within the scope of this rule because they
do not meet the definition of end-suction pump (i.e., liquid does not
enter pump in a direction parallel to the impeller shaft due to inlet
adapter) and do not meet the definition of IL pump (i.e., the flow
inlet and outlet are on the same plane but not on the same axis). In
addition, DOE believes that the majority of these OH3A and OH5A pumps
are non-clogging and thus would also be excluded because they do not
meet DOE's definition of clean water pump, as discussed further in
section III.A.3.
Regarding OH6 pumps, DOE notes that such pumps include a high speed
integral gear such that the impeller shaft will rotate faster than the
driver. While these pumps meet the definition of IL pumps, they are
excluded from the scope of pumps subject to this test procedure because
they operate at impeller speeds greater than the nominal speed
limitations discussed in section III.A.4 and III.C.2.c. In addition,
the impellers and drivers of OH6 pumps rotate at different speeds and,
thus, would be excluded based on DOE's revised specifications regarding
the impeller and driver rotating speeds of pumps addressed by this test
procedure (see section III.A.4). Similarly, DOE notes that OH2 pumps
would meet the definition of an ESFM pump, but would be excluded
because such pumps are designed specifically for pumping hydrocarbon
fluids, as noted by the American Petroleum Institute Standard 610
certification and, as such, are not clean water pumps. For these
reasons, DOE is not referencing OH2, OH3A, OH5A, or OH6 nomenclature in
the definitions of ESCC, ESFM, IL, RSV, and VTS established in this
rulemaking.
Finally, DOE notes that in April 2014, HI released an updated
version of ANSI/HI 2.1-2.2, ANSI/HI 2.1-2.2-2014. DOE reviewed ANSI/HI
2.1-2.2-2014 and found the documents to be substantially the same as
ANSI/HI 2.1-2.2-2008, with the exception of the addition of a new
definition and description for pipe length, more detailed
characteristics identified on some of the figures, and slight
reorganization of the sections to improve document flow. DOE notes that
none of these minor changes affect the content pertinent to the
references to ANSI/HI 2.1-2.2-2008 nomenclature proposed in the April
2015 pumps test procedure NOPR. As such, DOE believes that it is
appropriate to reference the most up-to-date industry standard and is
updating all references in the RSV and VTS equipment category
definitions from ANSI/HI 2.1-2.2-2008 to ANSI/HI 2.1-2.2-2014 in this
final rule.
Specific Styles of IL Pumps
In response to DOE's request for comment on all proposed pump
definitions in general, HI commented that twin head pumps, which
combine two impeller assemblies into a common single axis flow casing
with a single inlet and discharge, were not included in DOE's
definitions and should be added to the rulemaking scope. (HI, No. 8 at
p. 3) DOE notes that such pumps are a style of IL pump and, thus
subject to the test procedure and standards as an IL pump, but DOE
understands that this inclusion was not explicitly laid out in the
NOPR. As such, twin head pumps meet the definition of IL pumps as
proposed in the April 2015 pumps test procedure NOPR. Specifically,
twin head pumps are single-axis flow, rotodynamic pumps with single-
stage impellers and in which liquid is discharged through a volute in a
plane perpendicular to the impeller shaft. However, to clarify the
applicability of the IL pump definition and DOE's pump test procedure
to twin head pumps, DOE is adopting in this final rule a definition of
twin head pump as set forth in the regulatory text of this rule (10 CFR
431.62).
[[Page 4096]]
In this final rule, DOE is also clarifying the testing and
certification requirements for such pumps. For the purposes of applying
the DOE test procedure to and certifying twin head pumps, DOE is
clarifying that such pumps should be tested configured with a single
impeller assembly, as discussed further in section III.C.2.c.
RSV Pump Definition
DOE also requested specific comment on whether it needed to clarify
the flow direction to distinguish RSV pumps from other similar pumps
when determining test procedure and standards applicability and on
whether any additional language would be necessary in the proposed RSV
definition in the April 2015 pumps test procedure NOPR to make the
exclusion of immersible pumps clearer. HI commented that it believes
the icons shown and the definition found in ANSI/HI 2.1-2.2-2014
provide sufficient clarity to the flow direction, and that it does not
believe any additional language is necessary. (HI, No. 8 at pp. 6-7)
DOE reviewed the figures in ANSI/HI 2.1-2.2-2014 and believes that the
figure is illustrative of the general equipment characteristics for RSV
pumps. The description accompanying the figure also describes the
manner in which liquid enters and exits the pump. Specifically, section
2.1.3.6 of ANSI/HI 2.1-2.2-2014 states that, for RSV pumps, ``fluid
enters one nozzle of the in-line casing and is directed to the inlet of
an internal multi-stage diffuser pump. After traveling through multiple
stages, the liquid exits at the top stage of the pump where the flow is
redirected via the outer sleeve to the opposing nozzle of the in-line
casing.'' As DOE's definition of RSV pump references the figures and
description in ANSI/HI 2.1-2.2-2014, and this description of flow path
through the pump is not inconsistent or conflicting with DOE's
definition of RSV pump, DOE does not believe that further clarification
is necessary in this regard.
Regarding the exclusion of immersible pumps, HI commented that it
did not believe any additional clarification was necessary. (HI, No. 8
at pp. 6-7) Therefore, in this final rule, DOE has determined that the
adopted language is sufficient to exclude any immersible pumps from
treatment as an RSV pump for purposes of DOE's regulations.
VTS Equipment Terminology
Upon review of CIP Working Group transcripts and slides, DOE also
determined that interested parties had requested the equipment category
``vertical turbine submersible'' be termed ``submersible turbine,''
given that some of these pumps are installed horizontally. (CIP Working
Group transcript, No. 14 at p. 263) DOE notes that the definition
proposed for vertical turbine submersible is silent as to installation
orientation and, as a result, would include horizontally installed
pumps. DOE believes that referring to submersible turbine pumps as
``vertical turbine submersible,'' when horizontally mounted submersible
turbine pumps are also included in the equipment category, as defined,
could lead to confusion among manufacturers and in the market place. As
such, and given that changing the defined term from vertical turbine
submersible to submersible turbine would not change the scope of the
definition, DOE is revising the nomenclature in this final rule to
match that used in the CIP Working Group, which more accurately
describes the subject equipment. In the preamble to this final rule,
DOE has retained the VTS abbreviation for the submersible turbine
equipment category for consistency with the April 2015 pump test
procedure NOPR, pumps energy conservation standards rulemaking (Docket
No. EERE-2011-BT-STD-0031), and all Working Group discussions and
recommendations to date (Docket No. EERE-2013-BT-NOC-0039). However,
DOE is adopting the acronym ``ST'' for the regulatory text for long-
term consistency with the defined term.
ESFM Equipment Terminology
Similarly, the ``end suction frame mounted'' category proposed in
the NOPR had been referred to as ``end suction frame mounted/own
bearings'' in the CIP Working Group documentation. (See for example,
EERE-2013-BT-NOC-0039-0092 at p. 2 and EERE-2013-BT-NOC-0039-0031 at p.
4) The proposed end suction frame mounted definition would be inclusive
of own bearings pumps, or any end-suction pump that ``does not rely on
the motor shaft to serve as the impeller shaft.'' 80 FR 17586, 17641
(April 1, 2015). DOE intended the ESFM and ESCC equipment category
definitions proposed in the April 2015 pumps test procedure NOPR to be
mutually exclusive, whereby pumps that are close coupled to the motor
and share a single impeller and motor shaft would be part of the ESCC
equipment category, and all other end suction pumps that are
mechanically-coupled to the motor and for which the bare pump and motor
have separate shafts would be part of the ESFM equipment category.
DOE understands that there are several coupling and mounting
methods for pairing a bare pump and motor, in addition to frame
mounting, and that referring to the ESFM equipment category based only
on that criteria may be misleading. To clarify the applicability of the
previously defined end suction frame mounted equipment category to own
bearing pumps, and given that changing the term itself would not change
the scope of the definition, DOE is revising the nomenclature in this
final rule to match that used in the CIP Working Group. Therefore, in
this final rule, DOE is defining this equipment category as end-suction
frame mounted/own bearing and adding to the definition the term
``mechanically-coupled'' to clarify that the ESFM equipment is, in
fact, inclusive of many coupling methods. DOE is further adopting a
specific definition for ``mechanically-coupled,'' as mutually exclusive
with ``close-coupled,'' to explicitly establish the coupling methods to
which the ESFM equipment category applies. The definition of
mechanically-coupled consists of text that was in the proposed
definition for ESFM and does not change the scope of ESFM from the
proposal.
b. Circulators
Circulators, which are a specific kind of rotodynamic pump, are
small, low-head pumps similar to the IL configuration pumps that are
generally used to circulate water in hydronic space conditioning or
potable water systems in buildings.
The CIP Working Group recommended that circulators be addressed as
part of a separate rulemaking process that would involve informal
negotiation between interested parties followed by an ASRAC-approved
negotiation. (Docket No. EERE-2013-BT-NOC-0039, No. 92, Recommendation
#5A at p. 2)
In the April 2015 test procedure NOPR, DOE also proposed to exclude
circulators from the rulemaking, and proposed a definition that would
be mutually exclusive from the other pumps in the rulemaking.
Specifically, DOE proposed definitions for circulators, ESCC, ESFM, and
IL pumps that were mutually exclusive, based on the assumption that
circulators require only the support of the supply and discharge piping
to function as designed, whereas ESCC, ESFM, and IL pumps require
attachment to a rigid foundation to function as designed. In response
to the proposed circulator definition, DOE received comments from
several interested parties,
[[Page 4097]]
addressed below. However, DOE has not yet received any formal proposals
or requests for negotiation from the interested parties.
The EEAs and CA IOUs expressed concern that the portion of the
proposed circulator definition that describes circulators as
``requir[ing] only the support of the supply and discharge piping to
which it is connected to function as designed,'' may lead to the design
of circulators with alternative mounting intended to circumvent
regulation. (EEAs, No. 10 at p. 1; CA IOUs, No. 13 at pp. 4-5) HI
agreed that no pump definition should be associated with a rigid
foundation, as in the industry rigid foundation has a different
connotation than DOE is using. (HI, No. 8 at pp. 5-6, 10). HI also
disagreed with the proposed circulator definition, commenting that
there are many end suction and close-coupled IL pumps that would meet
the proposed circulator definition but that are not considered
circulators. Instead, HI stated its belief that such pumps should be
included in the scope of pumps considered in this rulemaking. As a
result, HI recommended revising the definitions of circulator, ESFM,
ESCC, and IL pumps, as well as other related definitions. (HI, No. 8 at
pp. 7-8) Following the close of the comment period, the HI circulator
pump committee resubmitted revised definitions for circulator and IL
pumps, and other related definitions. (HI, No. 15 at pp. 1-3)
DOE reviewed both sets of HI's recommended definitions and found
them to be essentially the same. Specifically, HI's circulator pump
committee offered the following revised definitions of IL pumps and
circulator pumps, which were also included in HI's comments submitted
in response to the April 2015 pumps test procedure NOPR:
``In-line pump means a single-stage, single-axis flow, dry rotor,
rotodynamic pump that has a shaft input power greater than or equal to
one horsepower and less than or equal to two hundred horsepower at BEP
and full impeller diameter, in which liquid is discharged through a
volute in a plane perpendicular to the shaft, except for: Those that
are short-coupled or close-coupled, have a maximum hydraulic power that
is less than or equal to five horsepower at the full impeller diameter
and over the full range of operation, and are distributed in commerce
with a horizontal motor. Examples include, but are not limited to,
pumps complying with ANSI/HI nomenclature OH3, OH4, or OH5, as
described in ANSI/HI 1.1-1.2-2014, within the specified horsepower
range. Pumps complying with ANSI/HI nomenclature CP1, CP2, and CP3, as
described in ANSI/HI 1.1-1.2-2014, would not meet the definition of in-
line pump.'' (HI, No. 8 at pp. 5-6; HI, No. 15 at p. 1)
``Circulator pump means a single stage, in-line, rotodynamic pump
that meets one of the following descriptions:
i. [Wet Rotor Circulator] A single-axis flow, close-coupled, wet
rotor pump that: (1) Has a maximum hydraulic power greater than or
equal to 1/40 hp and less than or equal to 5 hp at full impeller
diameter and over the full range of operation, (2) is distributed in
commerce with a horizontal motor, and (3) discharges the pumped liquid
through a volute in a plane perpendicular to the shaft. Examples
include, but are not limited to, pumps complying with ANSI/HI 1.1-1.2-
2014 nomenclature CP1; or
ii. [Dry Rotor Two-Piece Circulator] A single-axis flow, close-
coupled, dry rotor pump that: (1) Has a maximum hydraulic power greater
than or equal to 1/40 hp and less than or equal to 5 hp at full
impeller diameter and over the full range of operation, (2) is
distributed in commerce with a horizontal motor, and (3) discharges the
pumped liquid through a volute in a plane perpendicular to the shaft.
Examples include, but are not limited to, pumps complying with ANSI/HI
1.1-1.2-2014 nomenclature CP2; or
iii. [Dry Rotor Three-Piece Circulator] A single-axis flow, short-
coupled, dry rotor pump, either flexibly or rigidly coupled that: (1)
Has a maximum hydraulic power greater than or equal to 1/40 hp and less
than or equal to 5 hp at full impeller diameter and over the full range
of operation, (2) is distributed in commerce with a horizontal motor,
and (3) discharges the pumped liquid through a volute in a place
perpendicular to the shaft. Examples include, but are not limited to,
pumps complying with ANSI/HI 1.1-1.2-2014 nomenclature CP3.''
(HI, No. 8 at pp. 8-9; HI, No. 15 at p. 1)
HI also recommended several supporting definitions, including
definitions for single-axis flow pump, close-coupled pump, short-
coupled pump, rigid-coupled pump, flexibly-coupled pump, hydraulic
power, wet rotor pump, dry rotor pump, horizontal motor, and non-
horizontal motor. (HI, No. 8 at pp. 9-10; HI, No. 15 at pp. 2-3)
The EEAs and CA IOUs also stated that they are collectively
discussing an improved definition of circulators with HI. (EEAs, No. 10
at p. 1; CA IOUs, No. 13 at pp. 4-5)
In light of the continued discussions among these interested
parties regarding future definitions, test procedures, and energy
conservation standards for circulators, DOE has decided to refrain from
defining the term ``circulator'' in this rulemaking. Rather than
explicitly define the term circulator in this rule, DOE has modified
the definitions of ESCC, ESFM, IL, VTS, and RSV to specifically exclude
certain categories of pumps that are widely considered circulators by
the industry, using many of the criteria and characteristics of
circulators indicated by HI in its comments and proposed in the April
2015 pumps test procedure NOPR.
In particular, in its definition of IL pump, DOE excluded pumps
that are commonly marketed and sold as circulators in the pump industry
by utilizing the design features of a horizontal motor, as well as a
hydraulic power less than or equal to 5 hp. This is consistent with
HI's suggested definition of IL pump as well as circulator pump, which
includes reference to a horizontal motor and a horsepower range of 1/40
to 5 hydraulic hp. DOE agrees that a horizontal motor, which is a motor
that is required to be oriented with the motor shaft in a horizontal
position in order to operate as designed, is a distinguishing feature
of a circulator. To clearly establish this characteristic, DOE is also
defining the term horizontal motor in this rulemaking based on the
definition HI suggested in its comments. Specifically, HI's proposed
definition and the definition DOE is adopting in this final rule are as
follows:
Horizontal motor means a motor that requires the motor shaft to be
in a horizontal position to function as designed, as specified in the
manufacturer literature.
DOE notes that it is maintaining a lower shaft limit of 1 hp for
the IL pump equipment category and only specifically excluding those
pumps that have both: (1) A hydraulic output of less than 5 hp and (2)
a horizontal motor. As such, any IL pumps that have a shaft horsepower
greater than or equal to 1 hp and hydraulic output less than 5 hp and
are not sold with a horizontal motor, as well as IL pumps that have a
hydraulic output greater than or equal to 5 hp and shaft horsepower
less than or equal to 200 hp and are sold with a horizontal or non-
horizontal motor, would continue to be included in the IL pump
definition and subject to the test procedure established in this final
rule. DOE notes that the majority of pumps that are commonly referred
to as
[[Page 4098]]
circulators have a shaft input power less than 1 hp. Such pumps may
operate with or without horizontal motors. As such, the lower shaft
power limit in the IL pump definition excludes these pumps from the
scope of this rulemaking.
DOE also acknowledges that HI recommended establishing the
hydraulic horsepower threshold over the full range of operation of the
pump. (HI, No. 8 at pp. 5-6 and 8-9; HI, No. 15 at p. 1) However, DOE
notes that the other horsepower thresholds referenced in this final
rule reference pump shaft input power as measured at BEP. DOE also
notes that the test procedure established in this final rule contains a
specific and repeatable methodology for determining BEP of a tested
pump. Conversely, in the proposed test procedure, DOE did not define
the ``full range of operation'' of a pump or propose a method for how
to determine it. Since it is important that DOE's test procedures be as
precise and unambiguous as possible, DOE believes that it is important
that the hydraulic horsepower of a pump be determined in a consistent
manner when determining whether or not the pump meets the definition of
an IL pump and, thus, is subject to DOE's pumps test procedure
establish in this final rule. Therefore, in this final rule, DOE is
establishing the hydraulic horsepower threshold for circulator pumps as
determined at BEP. That is, DOE will exclude from the definition of IL
pump, IL pumps with a hydraulic horsepower less than 5 hp, as
determined at full impeller diameter and BEP, and that are distributed
in commerce with a horizontal motor, as those pumps are considered to
be circulator pumps.
Consistent with the changes to the IL definition, DOE is also
incorporating horsepower limits into the ESCC, ESFM, RSV, and VTS
equipment category definitions. DOE notes that, in the April 2015 pumps
test procedure NOPR, DOE proposed to establish the scope of the test
procedure using a horsepower range of greater than or equal to 1 hp and
less than 200 hp that was applicable to all ESCC, ESFM, IL, RSV, and
VTS pumps. 80 FR 17586, 17600 (April 1, 2015). However, to maintain
consistent format among the five defined equipment categories, DOE is
including this established horsepower range in each of the equipment
category definitions explicitly rather than in a separate scope
limitation. DOE discusses the horsepower range and other parameters
used to establish the scope of the test procedure in section III.A.4.
Additionally, DOE has added the design feature of a ``dry rotor''
to the definition of an IL pump \22\ and added a definition of dry
rotor pump, as suggested by HI. This feature excludes pumps that comply
with ANSI/HI nomenclature CP1, also referred to as wet rotor
circulators, as described in ANSI/HI 1.1-1.2-2014. This definition is
also consistent with HI's proposed IL and circulator pump definitions.
DOE notes that wet rotor pumps were proposed to be excluded from the
scope of the test procedure in the April 2015 pumps test procedure NOPR
under the definition of ``sealless pump.'' Specifically, DOE proposed a
definition of sealless pump to include both: (1) A pump that transmits
torque from the motor to the bare pump using a magnetic coupling and
(2) a pump in which the motor shaft also serves as the impeller shaft
for the bare pump and the motor rotor is immersed in the pumped fluid.
80 FR at 17641-42. HI's proposed definition of wet rotor is identical
to the second clause of DOE's proposed sealless pump definition. As
such, in this final rule, DOE defines dry rotor pump, consistent with
the definition proposed by HI, and to incorporate the term dry rotor
into the ESFM, ESCC, IL, RSV, and VTS equipment category definitions.
Given the mutually exclusive relationship between wet and dry rotor
pumps, the definitions of ESCC, ESFM, IL, RSV, and VTS pumps, as
established in section III.A.2.a, now implicitly exclude wet rotor
pumps from the scope of this test procedure. This implicit exclusion of
wet rotor pumps alleviates the need to explicitly exclude wet rotor
pumps using the definition of sealless pump as proposed in the NOPR.
Further discussion of modifications to the definition of sealless pump
are found in section III.A.2.b.
---------------------------------------------------------------------------
\22\ In the NOPR, DOE had excluded sealless pumps, including wet
rotor pumps, from the scope of the rulemaking in addition to
explicitly limiting the defined pump categories to dry rotor pumps.
80 FR 17586, 17598-99 (April 1, 2015) See section III.A.3.b.
---------------------------------------------------------------------------
DOE also acknowledges the concern from interested parties regarding
the potential issues associated with referencing attachment to a rigid
foundation. As noted in the NOPR, DOE initially proposed such a design
feature to clearly differentiate and exclude circulators from other,
similar categories of pumps that would be subject to the proposed test
procedure. However, DOE has, based on comments received from interested
parties, revised its approach to the exclusion of circulators and,
consequently, this design feature is no longer needed in the
definitions of IL, ESCC, and ESFM. Instead, DOE has made other
modifications to the applicable definitions to continue to exclude
circulators from the equipment categories addressed in this rulemaking,
as discussed above.
In addition to the parameters necessary to exclude circulators from
the scope of pumps for which the test procedure is applicable, the CA
IOUs commented that certain multi-stage pumps should be included in the
definition of a circulator, as proposed by DOE. CA IOUs also provided
an example of a commercially available style of pump that they believe
to be a multi-stage circulator. (CA IOUs, No. 13 at pp. 4-5) DOE
reviewed the example style of pump provided by the CA IOUs and found
that this specific style of pump is available in sizes from 0.5 to 75
motor hp, depending on impeller diameter and number of stages. DOE also
concluded that specific models within this general pump family, namely
those with shaft horsepower greater than or equal to 1 hp, meet the
definition of an RSV pump and therefore are included in the scope of
this rulemaking. Conversely, other models within the same pump family
with shaft horsepower less than 1 hp do not meet the definition of an
RSV pump and are not subject to the test procedure established in this
rulemaking. Consequently, given that DOE has withdrawn its proposal to
define circulators at this time, DOE has determined that it does not
need to define or address these small RSV pumps in this rulemaking.
c. Pool Pumps
The CIP Working Group formally recommended that DOE initiate a
separate rulemaking for dedicated-purpose pool pumps (DPPPs) by
December 2014. (Docket No. EERE-2013-BT-NOC-0039, No. 92,
Recommendation #5A at p. 2) In the April 2015 pumps test procedure
NOPR, DOE proposed defining a ``dedicated-purpose pool pump'' as an end
suction pump designed specifically to circulate water in a pool and
that includes an integrated basket strainer. 80 FR 17586, 17641 (April
1, 2015). DOE developed this proposed definition to help distinguish a
DPPP from other categories of pumps under consideration in this
rulemaking (Docket No. EERE-2013-BT-TP-0055).
In response, APSP requested that DOE continue to keep pool pumps
separate from the scope of pumps considered in this rulemaking (APSP,
No. 12 at p.1), and the CA IOUs encouraged ASRAC to establish a new
working group for DPPP. (CA IOUs, No. 13 at pp. 1-2) In July 2015, DOE
issued a RFI on DPPPs requesting data and information from
[[Page 4099]]
interested parties on this equipment (July 2015 DPPP RFI). 80 FR 38032
(July 3, 2015). On August 25, 2015, DOE also published a notice of
intent to establish a working group for DPPPs. 80 FR 51483. See https://www1.eere.energy.gov/buildings/appliance_standards/rulemaking.aspx/ruleid/14 for more updates and information on the DPPP rulemaking.
DOE also received several comments regarding its proposed
definition. During the April 2015 NOPR public meeting, CA IOUs
expressed that the defining characteristic of a pool pump may not be
the strainer basket, as not all pool pumps have them. (CA IOUs, NOPR
public meeting transcript, No. 7 at pp. 57-58, 68) An HI representative
from Xylem (Mark Handzel) responded that commercial pool pumps without
basket strainers would be considered under one of the equipment
categories addressed in this rulemaking. (HI, NOPR public meeting
transcript, No. 7 at pp. 58-59) An HI representative from Xylem (Paul
Ruzicka) also suggested that, on the residential side, pool pumps are
double insulated products. (HI, NOPR public meeting transcript, No. 7
at pp. 69-70)
In written comments, the EEAs and the CA IOUs noted that many pool
pumps, including booster pumps, do not include an integrated basket
strainer, and that not all pool pumps are designed specifically to
circulate water (EEAs, No. 10 at p. 2; CA IOUs, No. 13 at p. 2-3). The
CA IOUs noted that 40 percent of California residential in-ground pools
have booster pumps that are operated 2.5 hours per day. The size is
typically \3/4\ nameplate horsepower with a service factor of 1.5. The
CA IOUs recommended that these be considered pool pumps and excluded
from this rulemaking, further noting that these manufacturers were not
involved in the CIP Working Group deliberations. The CA IOUs also
stated that mass market commodity pool pumps are unique because either
the pump is secured directly to the motor; or the pump and motor are
each factory secured to a common frame. (CA IOUs, No. 13 at pp. 2-4)
In separate written comments, APSP and the CA IOUs recommended the
following definition:
``A `pool pump' is a pump with the following characteristics:
An integral end suction pump and motor combination
specifically designed for pool and spa applications.
The impeller is attached to a motor (or motor and
controller) served by single-phase power five total horsepower or less.
The pump is secured directly to the motor, or the pump and
motor are factory secured to a common frame.'' (APSP, No. 12 at p. 1;
CA IOUs, No. 13 at p. 3-4)
DOE's original intent in proposing a definition for DPPP in the
April 2015 pumps test procedure NOPR was to properly exclude them from
this rulemaking. Upon review, DOE agrees with certain of the submitted
comments on the proposed definition, such as that all pumps associated
with pools may not include an integrated basket strainer. For example,
DOE is aware that booster pumps are not typically sold with integrated
basket strainers and some filter pumps may be sold separately from the
strainer, as discussed in the July 2015 DPPP RFI. 80 FR 26475, 26481
(May 8, 2015).
Therefore, after reviewing the comments submitted by interested
parties, DOE has decided to refrain from adopting a definition for DPPP
in this final rule. Instead, in this final rule, DOE is excluding DPPP
from the definitions for ESCC and ESFM pumps, and DOE will define DPPP
in the separate DPPP rulemaking that was initiated with the RFI.
d. Axial/Mixed Flow and Positive Displacement Pumps
``Axial/mixed flow pump'' is a term used by the pump industry to
describe a rotodynamic pump that is used to move large volumes of
liquid at high flow rates and low heads. These pumps are typically
custom-designed and used in applications such as dewatering, flood
control, and storm water management.
Positive displacement (PD) pumps are a style of pump that operates
by first opening an increasing volume to suction; this volume is then
filled, closed, moved to discharge, and displaced. PD pumps operate at
near-constant flow over their range of operational pressures and can
often produce higher pressure than a centrifugal pump, at a given flow
rate. PD pumps also excel at maintaining flow and efficiency for
liquids more viscous than water. When used in clean water applications,
PD pumps are typically chosen for high pressure, constant flow
applications such as high pressure power washing, oil field water
injection, and low-flow metering processes.
The CIP Working Group recommended excluding both of these types of
pumps from prospective energy conservation standards. (Docket No. EERE-
2013-BT-NOC-0039, No. 92, Recommendation #6 at p. 2) The primary reason
for excluding these pumps from this test procedure rulemaking is their
low market share in the considered horsepower range and low potential
for energy savings. (Docket No. EERE-2013-BT-NOC-0039, No. 14 at pp.
114 and 372-73) In addition, the CIP Working Group acknowledged that PD
pumps are more commonly used in non-clean water applications and
provide a different utility than the categories of pumps addressed in
this rulemaking. (Docket No. EERE-2013-BT-NOC-0039, No. 14 at p. 114)
Therefore, in the April 2015 pumps test procedure NOPR, DOE proposed to
exclude these pumps from the scope of this rulemaking and the parallel
energy conservation standards rulemaking, but determined that both
axial/mixed flow and PD pumps were implicitly excluded based on the
proposed equipment category definitions and scope parameters, so that
explicit exclusions were not necessary. 80 FR 17586, 17597-98 (April 1,
2015). In the April 2015 pumps test procedure NOPR, DOE requested
comment on the proposed exclusion and the assertion that such pumps
were explicitly excluded based on the existing definitions and scope
parameters. Id.
HI commented that both positive displacement and axial/mixed flow
pumps should be added to the list of equipment excluded from the scope
of pumps in this final rule. HI noted that PD pumps represent a small
percentage of the overall pump market and are generally used for niche
applications, such as viscous or shear-sensitive liquids. As a result,
such pumps have a distinct difference in design compared with
rotodynamic pumps. HI also suggested differentiating and excluding
axial/mixed flow pumps using a specific speed limit of 4,500,\23\ where
pumps with a specific speed greater than 4,500 would be considered
axial/mixed flow. (HI, No. 8 at p. 11)
---------------------------------------------------------------------------
\23\ Specific speed is a quasi-dimensionless quantity used to
describe relative pump geometry and flow characteristics.
---------------------------------------------------------------------------
In response to HI, DOE notes that the April 2015 pumps test
procedure NOPR does not include PD pumps within its scope of
applicability. All equipment to which the April 2015 pumps test
procedure NOPR and this final rule applies is explicitly defined as
types of rotodynamic pumps. Further, rotodynamic pumps are explicitly
defined in the April 2015 pumps test procedure NOPR and this final rule
as continuously imparting energy to the pumped fluid by means of a
rotating impeller, propeller, or rotor. Such definition necessarily
does not include
[[Page 4100]]
PD pumps, which do not continuously impart energy to the pumped fluid
and do not contain an impeller, propeller, or rotor. As such, no PD
pumps meet the definition of any equipment within the scope of this
test procedure, as discussed in section III.A.2.a. Therefore, DOE does
not believe it is necessary to explicitly exclude PD pumps, which is
consistent with the comments submitted by HI.
Regarding axial/mixed flow pumps, DOE agrees with HI that axial/
mixed flow pumps, which are designed to accommodate high flow-to-head-
ratio applications, should not be subject to the test procedure
established in this final rule. DOE notes that the definitions of IL,
RSV, and VTS implicitly exclude axial/mixed flow pumps through specific
design features. Specifically, the definitions of IL and RSV pumps
exclude axial/mixed flow pumps by specifying single axis flow and a
liquid inlet in a plane perpendicular to the impeller shaft. In
contrast, the liquid intake in axial/mixed flow pumps is typically
parallel to the impeller shaft; as such, these pumps do not meet the
definition of an RSV or IL pump. DOE understands that less typical
piping configurations could allow an axial/mixed flow pump to be built
with the liquid inlet in a plane perpendicular to the impeller shaft.
However, such a configuration would not satisfy the definition of
single axis flow and, as such, these pumps would not meet the
definition of an RSV or IL pump. Additionally, the definition of VTS
pump excludes axial/mixed flow pumps by specifying that the pump must
be designed to operate with the motor and stage(s) fully submerged in
the pumped liquid. Axial/mixed flow pumps are not designed to be
completely submerged in the pumped liquid and, therefore do not meet
the definition of a VTS pump.
In summary, DOE believes that the definitions of IL, RSV, and VTS
equipment categories are sufficient to exclude pumps that are referred
to as axial/mixed flow. As a result, DOE maintains that a specific
speed limitation or other criteria for these categories is unnecessary,
and DOE has not included a specific speed range for these pumps in the
parameters for establishing the scope of this rulemaking described in
section III.A.4.
With respect to the end suction pumps defined in this final rule,
DOE agrees that additional scope parameters are necessary to limit the
scope of this rulemaking to end suction pumps and not inadvertently
include axial/mixed flow pumps. DOE agrees with HI's suggestion of a
specific speed limit to accomplish the exclusion of axial/mixed flow
pumps. However, DOE reviewed the specific speeds of all end suction
pumps submitted by manufacturers during the energy conservation
standards rulemaking and identified multiple end suction pumps with
specific speeds in the range of 4,500 to 5,000.\24\ DOE notes these
data were voluntarily submitted by manufacturers who self-classified
their pumps into equipment types with the understanding that the
rulemaking was not intended to include axial/mixed flow pumps. DOE
reviewed literature for the specific pumps end suction pumps with
specific speeds in the range of 4,500 to 5,000 and found them to be
marketed as end suction pumps. Furthermore, DOE notes that the
performance data for these pumps were included in the energy
conservation standards rulemaking analysis. Consequently, DOE finds it
appropriate to explicitly include within the scope of this rule, as
established in Sec. 431.464(a)(1)(ii), all end suction pumps with
specific speeds up to and including 5,000 and exclude pumps with
specific speeds greater than 5,000.
---------------------------------------------------------------------------
\24\ All values for specific speed in this final rule pertain to
calculations using U.S. customary units.
---------------------------------------------------------------------------
e. Final Equipment Category Definitions
After consideration of all comments, definitions for pump equipment
categories subject to this test procedure are as set forth in the
regulatory text of this rule (10 CFR 431.62).
DOE received no comments on DOE's other supporting definitions
proposed in the April 2015 pumps test procedure NOPR, namely
rotodynamic pump, single axis flow pump, and end suction pump.
Therefore, DOE is adopting those definitions as proposed.
3. Scope Exclusions Based on Application
In an effort to meet the intent and recommendations of the CIP
Working Group to include only those pumps intended to pump clean water
in the scope of this test procedure rulemaking (Docket No. EERE-2013-
BT-NOC-0039, No. 92, Recommendation #8 at pp. 3-4), DOE proposed to
define ``clean water pump'' in the April 2015 pumps test procedure
NOPR. 80 FR 17586, 17598 (April 1, 2015). DOE also proposed defining
several kinds of clean water pumps that are designed for specific
applications and that the CIP Working Group had indicated should be
excluded from the scope of this test procedure and DOE's standards
rulemaking efforts that are being considered in a separate rulemaking.
(Docket No. EERE-2011-BT-STD-0031) These proposed definitions, comments
DOE received regarding the proposed definitions, and DOE's responses to
those comments are discussed in the subsequent sections III.A.3.a and
III.A.3.b.
a. Definition of Clean Water Pump
In the NOPR, DOE proposed defining ``clean water pump'' as a pump
that is designed for use in pumping water with a maximum non-absorbent
free solid content of 0.25 kilograms per cubic meter, and with a
maximum dissolved solid content of 50 kilograms per cubic meter,
provided that the total gas content of the water does not exceed the
saturation volume, and disregarding any additives necessary to prevent
the water from freezing at a minimum of -10 [deg]C. DOE also noted that
several common pumps would not meet the definition of clean water
pumps, as they are not designed for pumping clean water, including
wastewater, sump, slurry, or solids handling pumps; pumps designed for
pumping hydrocarbon product fluids; chemical process pumps; and
sanitary pumps. DOE also proposed to incorporate by reference the
definition for ``clear water'' established in HI 40.6-2014 to describe
the characteristics of the fluid to be used when testing pumps in
accordance with the DOE test procedure. 80 FR 17586, 17598 (April 1,
2015).
DOE requested comment on the definition of ``clean water pump''
proposed in the April 2015 pumps test procedure NOPR and its proposal
to incorporate by reference the definition of ``clear water'' in HI
40.6-2014 to describe the testing fluid to be used when testing pumps
in accordance with the DOE test procedure. In response to these
proposals, HI commented that it agrees with the definition of ``clean
water pump'' as set forth in the NOPR, and that it agrees with
incorporating by reference the definition of ``clear water'' in HI
40.6-2014. (HI, No. 8 at p. 11) DOE received no other comments on these
terms and has determined that the definitions proposed in the NOPR are
sufficient for the purposes of applying DOE's test procedure. However,
for consistency, DOE is making the minor modification of translating
the definition to use all U.S. customary units. As such, DOE is
adopting the definition of clean water pump and incorporating by
reference the definition of ``clear water'' in HI 40.6-2014 as proposed
in the April 2015 pumps test procedure NOPR, with only the minor
modification regarding units noted previously.
[[Page 4101]]
b. Exclusion of Specific Kinds of Clean Water Pumps
In the April 2015 pumps test procedure NOPR, DOE also proposed
defining several kinds of pumps that meet the definition of clean water
pumps discussed in section III.A.3.a, but that the CIP Working Group
recommended be excluded from this pumps test procedure rulemaking.
Specifically, in the April 2015 pump test procedure NOPR, DOE proposed
that the test procedure would not apply to the following:
Fire pumps;
self-priming pumps;
prime-assist pumps;
sealless pumps;
pumps designed to be used in a nuclear facility subject to
10 CFR part 50--Domestic Licensing of Production and Utilization
Facilities; and
a pump meeting the design and construction requirements
set forth in Military Specification MIL-P-17639F, ``Pumps, Centrifugal,
Miscellaneous Service, Naval Shipboard Use'' (as amended).
80 FR 17586, 17598-17600 (April 1, 2015).
Accordingly, DOE proposed the following definitions of fire pump,
self-priming pump, prime-assist pump, and sealless pump:
Fire pump means a pump that is compliant with National
Fire Protection Association (NFPA) 20-2016,\25\ ``Standard for the
Installation of Stationary Pumps for Fire Protection,'' and either (1)
American National Standards Institute (ANSI)/UL listed under ANSI/UL
448-2013, ``Standard for Safety Centrifugal Stationary Pumps for Fire-
Protection Service,'' or (2) FM approved under the January 2015 edition
\26\ of FM Class Number 1319, ``Approval Standard for Centrifugal Fire
Pumps (Horizontal, End Suction Type).''
---------------------------------------------------------------------------
\25\ DOE notes that in the April 2015 pumps test procedure NOPR,
DOE proposed to reference NFPA 20-2013. However, on May 26, 2015,
NFPA released a revised version of NFPA 20. DOE reviewed the new
NFPA 20-2016 and finds it to be consistent with NFPA 20-2013 for the
purposes of defining the characteristics of a ``fire pump'' in the
context of DOE's regulations for pumps. DOE finds it most
appropriate to reference the most up-to-date version of the NFPA
Standard, as that version would be the version currently in use for
specifying the necessary characteristics of fire pumps in the
industry. Therefore, in this final rule, DOE is updating the
definition of fire pump to reference NFPA 20-2016.
\26\ Similar to NFPA 20-2016, DOE notes that, in January 2015,
FM Global released an updated version of the FM Class Number 1319
standard. DOE reviewed the new January 2015 edition and notes that
it contains only editorial changes as compared to the October 2008
edition proposed in the NOPR. DOE believes that it is most
appropriate to reference the most up-to-date version of the FM
standard, as that version is the version currently in use for
specifying the necessary characteristics of fire pumps in the
industry. Therefore, in this final rule, DOE is updating the
definition of fire pump to reference the January 2015 edition of FM
Class Number 1319.
---------------------------------------------------------------------------
Self-priming pump means a pump designed to lift liquid
that originates below the center line of the pump impeller. Such a pump
requires initial manual priming from a dry start condition, but
requires no subsequent manual re-priming.
Prime-assist pump means a pump designed to lift liquid
that originates below the center line of the pump impeller. Such a pump
requires no manual intervention to prime or re-prime from a dry-start
condition. Such a pump includes a vacuum pump or air compressor to
remove air from the suction line to automatically perform the prime or
re-prime function.
Sealless pump means either:
[cir] A pump that transmits torque from the motor to the bare pump
using a magnetic coupling; or
[cir] A pump in which the motor shaft also serves as the impeller
shaft for the bare pump, and the motor rotor is immersed in the pumped
fluid.
Id. at 17641-42.
HI commented that it agrees with the definition of ``fire pump''
and recommended alternate definitions for ``self-priming pump,''
``prime-assist pump,'' and ``sealless pump'' as follows:
Self-priming pump means a pump designed to lift liquid
that originates below the centerline of the pump inlet. Further, such a
pump must contain at least one internal recirculation passage and
requires a manual filling of the pump casing prior to initial start-up.
Such a pump must then be able to re-prime after the initial start-up
without the use of external vacuum sources, manual filling, or a foot
valve.
Prime-assist pump means a pump designed to lift liquid
that originates below the centerline of the pump inlet. Such a pump
requires no manual intervention to prime or re-prime from a dry-start
condition without the use of a foot valve. Such a pump includes a
vacuum pump or air compressor and venture/educator to remove air from
the suction line to automatically perform the prime or re-prime
function at any point during the pump's operating cycle.
A sealless pump means either:
[cir] A hermetically sealed pump that transmits torque from the
motor to an inner impeller rotor via magnetic force through a
containment shell;
[cir] Or, a type of pump that has a common shaft to link the pump
and motor in a single hermetically sealed unit. The pumped liquid is
circulated through the motor but is isolated from the motor components
by a stator liner.
(HI, No. 55 at pp. 11-12)
DOE considered these recommendations and revised the definitions of
these excluded clean water pumps in this final rule, incorporating the
key components of HI's proposals. Specifically, DOE agrees with HI's
revised definitions for prime-assist pump and self-priming pump and is
adopting them in this final rule with some minor modifications for
clarity. DOE finds HI's suggested definitions to be consistent with
DOE's proposed definitions but more precise, using industry-specific
language.
Regarding HI's suggested definition of sealless pump, DOE agrees
with the content of the definition. However, DOE notes that, based on
the modifications to equipment category definitions described in
section III.A.2.a, DOE has determined that it is no longer necessary to
explicitly exclude wet rotor pumps (the second clause of HI's sealless
pump definition) from the scope of this rulemaking. Specifically, as
explained in section III.A.2.a, DOE is specifying in its revised
definitions that all ESCC, ESFM, IL, RSV, and VTS pumps are types of
dry rotor pumps. Dry rotor pump means a pump in which the motor rotor
is not immersed in the pumped fluid. Conversely, a wet rotor pump is
one in which the motor rotor is immersed in the pumped liquid.
Given the mutually exclusive relationship between wet and dry rotor
pumps, the definitions of ESCC, ESFM, IL, RSV, and VTS pumps, as
established in section III.A.2.a, now implicitly exclude wet rotor
pumps from the scope of this test procedure. As a result, DOE has
simplified the sealless pump exclusion in this final rule to exclude
magnet driven pumps only. Accordingly, DOE is also modifying the term
``sealless pump'' to ``magnet driven pump,'' as DOE believes this term
more accurately describes the excluded equipment. In addition, DOE is
modifying the definition of magnet driven pump to be consistent with
the suggestions from HI, which DOE believes is consistent with the
portion of the sealless pump definition proposed in the April 2015
pumps test procedure NOPR addressing magnet driven pumps, but which
uses more precise and industry-specific terminology.
HI also commented that no pumps designed to the Federal defense
specification MIL-P-17639 should be included in this rulemaking. (HI,
No. 8 at p. 12) HI stated that the specifications included in the CIP
Working Group
[[Page 4102]]
term sheet also should be excluded, specifically MIL-P-17881, MIL-P-
17840, MIL-P-18682, and MIL-P-18472 (commonly referred to as ``MIL-
SPEC''). DOE has therefore reviewed these additional specifications in
determining exclusions in this final rule.
Pumps designed to these military specifications must meet very
specific physical and/or operational characteristics and comply with
complex and rigid reporting requirements.\27\ These specifications
require that significant amounts of design and test data be submitted
to various military design review agencies to ensure that the pump can
be operated and maintained in harsh naval environments. DOE believes
there is sufficient justification to exclude all of the MIL-SPEC pumps
identified by HI from the scope of this rulemaking without a risk of
clean water pumps being marketed or sold as MIL-SPEC for actual use in
other applications due to the rigorous and burdensome requirements
associated with complying with those regulations. DOE notes that, as
mentioned in the April 2015 pumps test procedure NOPR, when considering
if a pump is designed and constructed to the requirements set forth in
any of these specifications, DOE may request that a manufacturer
provide DOE with copies of the original design and test data that were
submitted to appropriate design review agencies, as required by each of
these specifications. 80 FR 17586, 17599 (April 1, 2015).
---------------------------------------------------------------------------
\27\ United States General Accounting Office, Report to
Congressional Committees, Acquisition Reform: DOD Begins Program To
Reform Specifications and Standards, GAO/NSIAD-95-14. October 11,
1994. Washington, DC. pp. 2-3. https://www.gao.gov/archive/1995/ns95014.pdf.
---------------------------------------------------------------------------
After reviewing and considering comments, DOE is adopting in this
final rule that the following specific types of clean water pumps are
excluded from the scope of this test procedure final rule:
Fire pumps;
self-priming pumps;
prime-assist pumps;
magnet driven pumps;
pumps designed to be used in a nuclear facility subject to
10 CFR part 50--Domestic Licensing of Production and Utilization
Facilities; and
pumps meeting the design and construction requirements set
forth in Military Specification MIL-P-17639F, ``Pumps, Centrifugal,
Miscellaneous Service, Naval Shipboard Use'' (as amended); MIL-P-
17881D, ``Pumps, Centrifugal, Boiler Feed, (Multi-Stage)'' (as
amended); MIL-P-17840C, ``Pumps, Centrifugal, Close-Coupled, Navy
Standard (For Surface Ship Application)'' (as amended); MIL-P-18682D,
``Pump, Centrifugal, Main Condenser Circulating, Naval Shipboard'' (as
amended); and MIL-P-18472G, ``Pumps, Centrifugal, Condensate, Feed
Booster, Waste Heat Boiler, And Distilling Plant'' (as amended).
Accordingly, DOE provides the revised definitions of fire pump,
self-priming pump, prime-assist pump, and magnet driven pump set forth
in the regulatory text of this rule (10 CFR 431.62).
4. Parameters for Establishing the Scope of Pumps in This Rulemaking
In addition to limiting the types of pumps that DOE will regulate
at this time through pump definitions and their applications, DOE
proposed in the April 2015 pumps test procedure NOPR to further limit
the scope of the pumps test procedure considered in this rulemaking by
applying the following performance and design characteristics:
1-200 hp (shaft power at the BEP at full impeller diameter
for the number of stages \28\ required for testing to the standard);
\29\
---------------------------------------------------------------------------
\28\ The number of ``stages'' in a multi-stage pump refers to
the number of bowl assemblies included in that pump.
\29\ The CIP Working Group also recommended that testing be
required with three stages for RSV pumps and nine stages for VTS
pumps, unless a model is not available with that specific number of
stages, in which case the pump would be tested with the next closest
number of stages. This recommendation is discussed in more detail in
section III.C.2.c.
---------------------------------------------------------------------------
25 gallons per minute (gpm) and greater (at BEP at full
impeller diameter);
459 feet of head maximum (at BEP at full impeller
diameter);
design temperature range from -10 to 120 [deg]C;
pumps designed for nominal 3,600 or 1,800 revolutions per
minute (rpm) driver speeds; and
6-inch or smaller bowl diameter for VTS pumps (HI VS0).
(Docket No. EERE-2013-BT-NOC-0039, No. 92, Recommendation #7 at p. 3);
80 FR 17586, 17600 (April 1, 2015).
Wilo commented that lower thresholds for horsepower and BEP flow
rate should not be included as limiting parameters on the scope of
pumps considered in the rule, citing unspecified gains in energy
savings that could be realized by regulating smaller models. (Wilo,
Docket No. EERE-2011-BT-STD-0031, No. 44 at pp. 1-2) \30\ In response
to Wilo's suggestion that DOE apply the test procedure to pumps with
flow rates below 25 gpm or shaft input power below 1 hp, DOE believes
that such a recommendation is inconsistent with the scope of pumps the
CIP Working Group recommended for this rulemaking. Given that such
small horsepower pumps were not considered in the CIP Working Group
discussions, any data or information submitted to DOE throughout those
negotiations did not consider small horsepower pumps. As such, DOE is
electing to maintain the lower thresholds for horsepower and BEP flow
rate as proposed in the April 2015 pumps test procedure NOPR.
---------------------------------------------------------------------------
\30\ A notation in this form provides a reference for
information that is in the docket of DOE's rulemaking to develop
energy conservation standards for commercial and industrial pumps
(Docket No. EERE-2011-BT-STD-0031, which is maintained at
www.regulations.gov). This particular notation refers to a comment:
(1) Submitted by Wilo; (2) appearing in document number 44 of the
docket; and (3) appearing on pages 1-2 of that document.
---------------------------------------------------------------------------
HI recommended in the April 2015 NOPR public meeting and written
comments that DOE establish scope related to ``driver and impeller''
speed rather than just driver speed. HI noted that pumps do not all
have 1:1 motor rotating speed to impeller-rotating speed, such as a
gear pump. (HI, NOPR public meeting transcript, No. 7 at p. 85; HI, No.
8 at p. 13) HI further specified as an example that a geared pump
designed to use a 2-pole motor could be in scope but could not be
tested according to section I.C.1 of the test procedure. (HI, No. 8 at
p. 13)
DOE notes that the list shown in the preamble of the April 2015
pump test procedure NOPR, based on the CIP Working Group
recommendations, included a limitation for pumps designed for nominal
driver speeds of 3,600 or 1,800 revolutions per minute (rpm) driver.
(Docket No. EERE-2013-BT-NOC-0039, No. 92, Recommendation #7 at p. 3);
80 FR 17586, 17600 (April 1, 2015). However, in the regulatory text of
the April 2015 pumps test procedure NOPR, DOE modified this
recommendation to acknowledge that the pumps within the scope of the
proposed test procedure include pumps paired with non-induction motors,
which have wide range of operating speeds. Specifically, DOE proposed
to limit the scope of the proposed test procedure to pumps designed to
operate with either: (1) A 2- or 4-pole induction motor, or (2) a non-
induction motor with a speed of rotation operating range that includes
speeds of rotation between 2,880 and 4,320 rpm and/or 1,440 and 2,160
rpm. Id. at 17642. DOE proposed the speed ranges of 2,880 to 4,320 and
1,440 to 2,160 based on the nominal rotating speeds of 3,600 and 1,800
for 2- and 4-pole motors, respectively, and the allowed 20
[[Page 4103]]
percent tolerance on rotating speed proposed in the NOPR. Id. at 17609.
DOE notes that geared pumps were never explicitly addressed by the
CIP Working Group; were not included in the pump data which are the
basis of this final rule and the associated energy conservation
standard rulemaking; and were not intended to be included in the scope
of the April 2015 pumps test procedure NOPR. In addition, as mentioned
in section III.A.2.a, geared pumps typically operate at impeller speeds
higher than the 1,800 and 3,600 nominal rotating speeds DOE referenced
in CIP Working Group discussions and the April 2015 pumps test
procedure NOPR. In light of HI's comment, DOE agrees that it is worth
clarifying that such pumps are not subject to or addressed by the test
procedure established in this final rule. To clarify that pumps with
higher impeller or lower driver rotating speeds (i.e., geared pumps)
are not within the scope of this rulemaking, DOE is modifying the
language establishing the rotating speeds within the scope of the test
procedure adopted in this final rule to note that the driver and
impeller must operate at the same speed.
During the April 2015 NOPR public meeting, the CA IOUs expressed
concern regarding whether it was the CIP Working Group's intention to
address VTS pumps that operate at high speed. Specifically, the CA IOUs
mentioned that it may not have been the intent of HI to exclude a
product operating at a higher rpm and recommended that HI consider the
language proposed in the April 2015 pumps test procedure NOPR to ensure
they support the scope of pumps addressed by the proposed test
procedure. (CA IOUs, NOPR public meeting transcript, No. 7 at pp. 86-
88) However, in its written comments, HI did not recommend any changes
to the parameters other than the discussion on impeller speed versus
driver speed. (HI, No. 8 at p. 13)
Wilo commented that manufacturers may redesign to nominal speeds
excluded from the DOE regulation. (Wilo, Docket No. EERE-2011-BT-STD-
0031, No. 44 at p. 2) Wilo indicated that, for example, a pump could be
designed for use with 6-pole motors at 1,200 rpm, or for use with
controls at 2,650 rpm. Wilo recommended to instead apply the minimum
efficiency required per equipment class (e.g., C-values at 1,800 rpm)
to pumps of any speed and specific speed, thereby eliminating
exceptions for speed and allowing for enforcement across all motor
speeds. (Id.)
DOE's data and analysis are based solely on pumps with nominal
rotating speeds corresponding to those speed ranges proposed in the
2015 pumps test procedure NOPR. DOE notes that, during the initial data
request underlying the parallel pumps test procedure and energy
conservation standards rulemakings, DOE requested data on six-pole
pumps from manufacturers. However, manufacturers declined to provide
such on the basis that, while some pumps may be sold for use with 6-
pole motors, they are all designed for use with 4- or 2-pole motors.
(Docket No. EERE-2013-BT-NOC-0039, No. 46 at p. 198) As such,
manufacturers posited that these pumps would already be captured in the
provided data for 4- and 2-pole, and any efficiency improvements made
to meet the energy conservation standards for those equipment classes
would also result in energy savings when the pump was operated with a
6-pole motor. Additionally, DOE finds it unlikely that, for those pumps
that can operate with 2-, 4-, or 6-pole motors, a manufacturer would
begin specifying that their pump was inappropriate for operation in the
nominal speed ranges of 2,880 and 4,320 rpm and/or 1,440 and 2,160 rpm
to avoid regulation.
After considering these comments, DOE maintains its position set
forth in the NOPR, and limits the test procedure applicability to pumps
designed for the given motors or speeds. DOE notes that pumps with
lower or higher operating speeds are covered as ``pumps'' and, should
DOE deem it necessary, DOE could evaluate the need for a test procedure
or standards for pumps at other rotating speeds in a future rulemaking.
In summary, DOE is establishing in this final rule the following
scope parameters:
25 gpm and greater (at BEP at full impeller diameter);
459 feet of head maximum (at BEP at full impeller diameter
and the number of stages specified for testing);
design temperature range from 14 to 248 [deg]F;
designed to operate with either (1) a 2- or 4-pole
induction motor, or (2) a non-induction motor with a speed of rotation
operating range that includes speeds of rotation between 2,880 and
4,320 rpm and/or 1,440 and 2,160 rpm, and in either case, the driver
and impeller must rotate at the same speed; and
6-inch or smaller bowl diameter for VTS pumps (HI VS0).
As discussed further in section III.B.2, DOE is clarifying that the
limitation on pump total head of 459 feet must be ascertained based on
the pump operating at BEP, at full impeller diameter, and with the
number of stages specified for testing.
Additionally, to exclude axial/mixed flow pumps, DOE is applying a
seventh scope parameter for ESCC and ESFM pumps, namely:
For ESCC and ESFM pumps, specific speed less than or equal
to 5,000 when calculated using U.S. customary units in accordance with
the DOE test procedure.
As discussed in section III.A.2.d, DOE is setting this limit on
specific speed based on HI's suggestion and data submitted by
manufacturers for end suction pumps. DOE believes that a specific speed
limit for the remaining equipment categories, namely IL, RSV, and VTS,
are unnecessary, as the definitions for these categories include design
features that implicitly exclude axial/mixed flow pumps.
In the April 2015 pumps test procedure NOPR, DOE proposed defining
bowl diameter to specify clearly and unambiguously the limiting
criterion for VTS pumps (i.e., bowl diameter). 80 FR 17586, 17600
(April 1, 2015). Specifically, DOE proposed defining ``bowl diameter''
as it applies to VTS pumps as follows:
Bowl diameter means the maximum dimension of an imaginary straight
line passing through and in the plane of the circular shape of the
intermediate bowl or chamber of the bare pump that is perpendicular to
the pump shaft and that intersects the circular shape of the
intermediate bowl or chamber of the bare pump at both of its ends,
where the intermediate bowl or chamber is as defined in ANSI/HI 2.1-
2.2-2008.
With this definition, only those VTS pumps with bowl diameters of 6
inches or less would be required to be tested under the test procedure.
Id.
In response to DOE's request for comment on the proposed definition
for ``bowl diameter'' as it would apply to VTS pumps, HI commented that
the definition should reference the updated 2014 version of ANSI/HI
2.1-2.2-2008, and recommended that the word ``outermost'' should be
inserted before the text ``circular shape of the intermediate bowl.''
(HI, No. 8 at p. 13) Based on previously submitted HI comments
regarding the energy conservation standards rulemaking for pumps, DOE
understands that VTS (e.g., VS0) pumps are considered equivalent to a
style of pump referred to as ``submersible multi-stage water pump''
[[Page 4104]]
(MSS) in EU regulation 547.\31\ (HI, Docket No. EERE-2011-BT-STD-0031,
No. 25 at p. 3) DOE also understands that, according to EU 547, MSS
pumps are designed to be operated in a borehole and have a nominal
outer diameter of either 4 or 6 inches.
---------------------------------------------------------------------------
\31\ Council of the European Union. 2012. Commission Regulation
(EU) No 547/2012 of 25 June 2012 implementing Directive 2009/125/EC
of the European Parliament and of the Council with regard to
ecodesign requirements for water pumps. Official Journal of the
European Union. L 165, 26 June 2012.
---------------------------------------------------------------------------
DOE agrees with HI that including the word ``outermost'' in the
proposed bowl diameter definition would improve the clarity of the
critical dimension and ensure the definition is aligned with how the
pumps are treated in EU 547. Therefore, in this final rule, DOE is
including the term outer diameter before the text ``circular shape of
the intermediate bowl'' in the definition of ``bowl diameter'' proposed
in the April 2015 pumps test procedure NOPR. DOE has also determined
that in order to avoid confusion with the ANSI/HI 2.1-2.2-2014 term
``seal chamber,'' the text ``or chamber'' should be removed from the
bowl diameter definition. The revised definition reads as set forth in
the regulatory text of this rule (10 CFR 431.62).
5. Drivers Other Than Electric Motors
DOE recognizes that some pumps, particularly in the agricultural
sector, may be sold and operated with drivers other than electric
motors (i.e., non-electric drivers), such as engines, steam turbines,
or generators. In the April 2015 pump test procedure NOPR, in
accordance with the recommendations of the CIP Working Group (Docket
No. EERE-2013-BT-NOC-0039, No. 92, Recommendation #3 at p. 2), DOE
proposed that pumps sold with non-electric drivers be rated as bare
pumps only. Specifically, based on DOE's proposed test procedure for
bare pumps discussed in detail in section III.E.1.a, pumps sold with
non-electric drivers would determine the PEICL for the pump
based on the calculated performance of the bare pump combined with a
default motor that is minimally compliant with DOE's energy
conservation standards for electric motors \32\ listed at 10 CFR
431.25. 80 FR 17586, 17600 (April 1, 2015). DOE noted that by requiring
testing and certification in this manner, any hydraulic improvements
made to the bare pump to comply with any applicable energy conservation
standards that may apply to the bare pump would also result in energy
savings when the pump was used with a non-electric driver. Id.
---------------------------------------------------------------------------
\32\ In context, the terms ``electric motor'' and ``motor'' are
used interchangeably.
---------------------------------------------------------------------------
DOE requested comment on its proposal to test pumps sold with non-
electric drivers as bare pumps. HI commented that it agrees that pumps
sold with non-electric drivers should be tested as bare pumps, as
recommended by the CIP Working Group. (HI, No. 8 at p. 13) DOE received
no other comments on the proposal and is adopting provisions for
testing pumps paired with non-electric drivers as bare pumps in this
final rule, as proposed in the April 2015 pumps test procedure NOPR.
6. Pumps Sold With Single-Phase Induction Motors
In the April 2015 pumps test procedure NOPR, DOE acknowledged that
some pumps within the scope of this rulemaking may be distributed in
commerce with single-phase motors. However, DOE determined that the
majority of pumps in the scope of this test procedure rulemaking are
sold with polyphase induction motors. Moreover, DOE noted that, to the
extent that pumps within the scope of the proposed test procedure are
distributed in commerce with single-phase motors, most of these pumps
are offered for sale with either single-phase or polyphase induction
motors of similar size, depending on the power requirements of
customers.
Given that single-phase induction motors are, in general, less
efficient than polyphase induction motors and, thus, will result in
different energy consumption characteristics when paired with the same
bare pump, DOE proposed that pumps sold with single-phase induction
motors be tested and rated in the bare pump configuration, using the
calculation-based method (see section III.E.1.a for a more detailed
description of this method). DOE believed that such an approach would
more equitably rate pumps sold with single-phase motors and prevent
pumps sold with single-phase motors from being penalized by the reduced
energy efficiency of the paired single-phase motor, as compared to
similarly-sized polyphase motors. 80 FR 17586, 17600-01 (April 1,
2015).
In response to DOE's proposed method for testing pumps sold with
single-phase induction motors, HI agreed that it is appropriate to
apply the calculation-based test procedure to bare pumps to determine
the PEICL for such pumps. However, HI also requested the
option of using single-phase motor wire-to-water test data (that is,
applying the testing-based method for pumps sold with motors, discussed
in section III.E.2.b) to determine the PEICL for such pumps.
(HI, No. 8 at p. 13) Given that single-phase induction motors are, in
general, less efficient than polyphase induction motors, determining
the PEICL for pumps sold with single-phase induction motors
based on the testing-based method for pumps sold with motors will
generally result in PEICL ratings that are equivalent to or
lower than those determined by rating the pump as a bare pump (as
proposed in the April 2015 pumps test procedure NOPR). Therefore, use
of the testing-based method will make it harder, rather than easier,
for pumps sold with single-phase induction motors, to meet the
established standards. For these reasons, DOE sees no reason why
manufactures could not be allowed to employ the testing-based method
for pumps sold with motors to determine the PEICL if they
chose to. As such, DOE is adopting provisions in this final rule that
allow manufacturers the option of rating pumps sold with single-phase
motors as bare pumps (using a calculation-based method) or as pumps
with motors using the testing-based methods. DOE notes that if
manufacturers choose to employ the testing-based methods for pumps sold
with motors, the denominator must still be calculated based on the
default motor efficiency values for polyphase NEMA Design B motor, as
discussed in section III.B.2. DOE also notes that, as for all pumps
subject to this test procedure final rule, manufacturers must report
which test method was employed in determining the certified
PEICL rating for the given basic model in the certification
report submitted to DOE. These requirements are discussed in more
detail in the pumps energy conservation standards rulemaking. (Docket
No. EERE-2011-BT-STD-0031)
B. Rating Metric: Constant and Variable Load Pump Energy Index
After significant discussion in the CIP Working Group open meeting,
the Working Group recommended that DOE use a wire-to-water, power-based
metric for all pumps, regardless of how they are sold. (Docket No.
EERE-2013-BT-NOC-0039, No. 92, Recommendation #11 at p. 5)
Specifically, the CIP Working Group recommended that DOE use the PEI
metric to measure pump energy performance, which is calculated as a
ratio of the PER (PERCL or PERVL) of the tested
pump divided by the PERCL of a pump that would minimally
comply with any DOE energy conservation standard for that pump type
(PERSTD). In both cases, PER represents a pump's power
consumption at a weighted average of
[[Page 4105]]
three or four load points. The CIP Working Group recommended a similar
metric for all pump configurations (i.e., bare pumps, pumps sold with a
motor, and pumps sold with a motor and continuous or non-continuous
controls) to allow for better comparability and more consistent
application of the rating metric for all pumps within the recommended
scope. This way, the benefit of speed control, as compared to a similar
pump without speed control, can be reflected in the measurement of
energy use or energy efficiency.
Accordingly, in the April 2015 pumps test procedure NOPR, DOE
proposed to establish a test procedure to determine the
PEICL for pumps sold without continuous or non-continuous
controls and PEIVL for pumps sold with continuous or non-
continuous controls. 80 FR 17586, 17601-02 (April 1, 2015). As
recommended by the CIP Working Group, DOE proposed to determine the
PEICL or PEIVL as the ratio of a PERCL
or PERVL scaled with respect to a ``standard pump energy
rating'' (PERSTD) that represents the performance of a bare
pump of the same equipment class that serves the same hydraulic load,
has the same flow and specific speed characteristics, and is minimally
compliant with DOE's energy conservation standards. Id.
Specifically, for pumps sold without continuous or non-continuous
controls, DOE proposed using the PEICL metric, which would
be evaluated as shown in equation (1):
[GRAPHIC] [TIFF OMITTED] TR25JA16.000
Where:
PERCL = the weighted average input power to the motor at
load points of 75, 100, and 110 percent of BEP flow (hp) and
PERSTD = the PERCL for a pump of the same
equipment class with the same flow and specific speed
characteristics that is minimally compliant with DOE's energy
conservation standards serving the same hydraulic load (hp). A more
detailed discussion of the PERSTD value is provided in
section III.B.2.
Similarly, for pumps sold with a motor and continuous or non-
continuous controls, DOE proposed to use PEIVL, which would
be evaluated as shown in equation (2):
[GRAPHIC] [TIFF OMITTED] TR25JA16.001
Where:
PERVL = the average input power to the motor and
continuous or non-continuous controls at load points of 25, 50, 75,
and 100 percent of BEP flow (hp) and
PERSTD = the PERCL for a pump of the same
equipment class with the same flow and specific speed
characteristics that is minimally compliant with DOE's energy
conservation standards serving the same hydraulic load (hp).
DOE noted in the April 2015 pumps test procedure NOPR that, under
the proposed approach, the performance of bare pumps or pumps paired
with motors (but without continuous or non-continuous controls) would
be determined for the appropriate load points along the single-speed
pump curve by increasing head (i.e., throttling) as flow is decreased
from the maximum flow rate of the pump, while pumps sold with
continuous or non-continuous controls, by contrast, would follow a
system curve and achieve the desired flow points by reducing the pump's
speed of rotation rather than controlling flow by throttling. By
reducing speed, power is reduced in proportion to the cube of speed,
resulting in lower power requirements for any part load flow points. As
such, the PEIVL for a pump sold with continuous or non-
continuous controls would be lower than the PEICL for the
same pump sold without continuous or non-continuous controls. In
essence, consistent with the recommendation of the CIP Working Group,
adopting the PEICL and PEIVL metrics as proposed
would illustrate the inherent performance differences that can occur
when coupling a given pump with continuous or non-continuous controls.
Id.
1. Determination of the Pump Energy Rating
As mentioned above, PERCL and PERVL represent
the weighted average input power to the pump determined at three or
four discrete load points for PERCL or PERVL,
respectively. In order to determine the representative performance of a
given pump unit, DOE must define a load profile and establish specific
load points at which to test a given pump for pumps sold with speed
controls and pumps sold without such speed controls (i.e., pumps sold
as bare pumps and pumps sold with motors). Based on DOE's research and
recommendations provided by the CIP Working Group, DOE proposed
adopting two distinct load profiles to represent constant speed and
variable speed pump operation, as shown in Table III.2.
Table III.2--Load Profiles Based on Pump Configuration
------------------------------------------------------------------------
Pump configuration Load profile Load points
------------------------------------------------------------------------
Pumps Sold without Continuous or Constant Load 75%, 100%, and
Non-Continuous Controls (i.e., Profile. 110% of BEP flow.
bare pumps and pumps sold with
motors).
Pumps Sold with Continuous or Variable Load 25%, 50%, 75%, and
Non-Continuous Controls. Profile. 100% of BEP flow.
------------------------------------------------------------------------
Lack of field data on load profiles and the wide variation in
system operation also make it difficult to select appropriate weights
for the load profiles. For these reasons, the CIP Working Group members
concluded that equal weighting would at least create a level playing
field across manufacturers (see, e.g., Docket No. EERE-2013-BT-NOC-
0039, No. 63 at p. 125), and DOE proposed to adopt this recommendation
in the April 2015 pumps test procedure NOPR. 80 FR 17586, 17604 (April
1, 2015).
[[Page 4106]]
In response to DOE's proposed metrics, load points, and weights, HI
commented that it agrees with the PEICL and PEIVL
metric architecture (HI, No. 8 at p. 14), and the CA IOUs also
indicated their support of DOE's proposed approach (CA IOUs, NOPR
public meeting transcript, No. 7 at p. 110). Therefore, DOE is
adopting, in this final rule, a metric of PEICL for pumps
sold as bare pumps or pumps sold with motors, but without continuous or
non-continuous controls, as proposed in the April 2015 pumps test
procedure NOPR, where the PERCL would be evaluated as the
weighted average input power to the motor at load points corresponding
to 75, 100, and 110 percent of BEP flow, as shown in equation (3):
[GRAPHIC] [TIFF OMITTED] TR25JA16.002
Where:
[omega]i = weighting at load point i (equal weighting or
0.3333 in this case),
Pi\in,m\ = measured or calculated driver power input to
the motor at load point i (hp), and
i = load point corresponding to 75, 100, or 110 percent of BEP flow
as determined in accordance with the DOE test procedure.
Id. at 17602.
Similarly, DOE is adopting a metric of PEIVL for pumps
sold with motors and continuous or non-continuous controls, where
PERVL is calculated as shown in equation (4):
[GRAPHIC] [TIFF OMITTED] TR25JA16.003
Where:
[omega]i = weighting at load point i (equal weighting or
0.25 in this case),
Pi\in,c\ = measured or calculated driver power input to
the continuous or non-continuous controls at load point i (hp), and
i = load point corresponding to 25, 50, 75, or 100 percent of BEP
flow as determined in accordance with the DOE test procedure.
Id. at 17603.
.DOE notes that, in the April 2015 pumps test procedure NOPR, DOE
proposed to refer to the driver power input using the variable
Pi\in\ regardless of whether it applied to pumps sold with
motors, where the driver input power is measured at the input to the
motor, or pumps sold with motors and continuous or non-continuous
controls, where the driver power input is measured at the input to the
controls. In this final rule, DOE is clarifying the terminology by
referring to driver power input to the motor as Pi\in,m\ and
driver power input to the controls as Pi\in,c\. DOE notes
that HI 40.6-2014 uses the variable Pgr to refer to driver
input power and, for the purposes of applying HI 40.6-2014 and the DOE
test procedure, DOE's defined variable (i.e., Pi\in,m\ and
Pi\in,c\) should be treated as equivalent to Pgr.
2. PERSTD: Minimally Compliant Pump
DOE proposed in the April 2015 pumps test procedure NOPR that the
PERCL or PERVL of the pump being rated in the
numerator of these equations would be scaled based on PERCL
of a pump that would minimally comply with the applicable standard for
the same class of pump to provide a rating for each pump model that is
indexed to a standardized value. DOE noted that scaling the
PEICL and PEIVL metrics based on a normalizing
factor would help compare values across and among various pump types
and sizes. 80 FR 17586, 17604 (April 1, 2015). DOE noted that such an
approach would be consistent with the CIP Working Group's
recommendations (Docket No. EERE-2013-BT-NOC-0039, No. 92,
Recommendation #11 at pg. 5) and is similar to the approach suggested
by Europump, a trade association of European pump manufacturers.\33\
Id.
---------------------------------------------------------------------------
\33\ Europump. Extended Product Approach for Pumps: A Europump
Guide. April 8, 2013.
---------------------------------------------------------------------------
In the April 2015 pumps test procedure NOPR, DOE proposed to
determine PERSTD as a baseline, minimally compliant pump,
inclusive of a minimally compliant default motor, defined as a function
of flow and specific speed. To do this, DOE proposed to use an equation
to determine the efficiency of a minimally compliant pump, shown in
equation (5): \34\
---------------------------------------------------------------------------
\34\ This equation reflects that shown in the April 2015 NOPR
public meeting (Docket No. EERE-2013-BT-TP-0055, No. 6 at p.49) and
represents a correction from that published in the April 2015 pumps
test procedure NOPR. 80 FR 17586, 17604 (April 1, 2015).
---------------------------------------------------------------------------
[[Page 4107]]
[GRAPHIC] [TIFF OMITTED] TR25JA16.004
Where:
Q100% = BEP flow rate (gpm),
Ns = specific speed at 60 Hz and calculated using U.S. customary
units, and
C = a constant that is set for the two-dimensional surface described
by equation (5), which is set based on the speed of rotation and
equipment type of the pump model. The values of this constant, or
``C-values,'' are used to establish the minimum, mandatory pump
efficiency with a minimally compliant pump and will be established
in the pump energy conservation standard rulemaking.
DOE developed this equation based on the equation used in the EU to
develop its regulations for clean water pumps, translated to 60 Hz
electrical input power and U.S. customary units.\35\ Id. HI commented
that it agrees with the corrected version of the equation for minimum
pump efficiency equation ([eta]pump,STD) presented during
the public meeting, except that the 555.6 value should be changed to
555.60 and a full significant digit analysis should be conducted to
ensure that two decimal places can be carried for efficiency. (HI, No.
8 at pp. 14-15) HI also indicated that because all data in the equation
are supposed to be normalized to 1,800 or 3,600 rpm,
Q100% should be clarified as the flow at BEP in
gallons per minute normalized to synchronous speed at 60 Hz. In
response to HI's suggested clarifications to the pump efficiency
equipment presented in the April 2015 pump test procedure NOPR and the
slide deck presented at the NOPR public meeting (see Docket No. EERE-
2013-BT-TP-0055, No. 6 at p.49), DOE is clarifying in this final rule
that Q100% in the minimum pump efficiency
equation ([eta]pump,STD) is the BEP flow rate (gpm) measured
at 60 Hz and full impeller diameter and normalized to nominal speed of
rotation of the pump (1,800 or 3,600 rpm). DOE has also revised the
equation for minimum pump efficiency equation
([eta]pump,STD) to match the equation shared during the
public meeting, as suggested by HI.
---------------------------------------------------------------------------
\35\ The equation to define the minimally compliant pump in the
EU is of the same form, but employs different coefficients to
reflect the fact that the flow will be reported in m3/h
at 50 Hz and the specific speed will also be reported in metric
units. Specific speed is a dimensionless quantity, but has a
different magnitude when calculated using metric versus U.S.
customary units. DOE notes that an exact translation from metric to
U.S. customary units is not possible due to the logarithmic
relationship of the terms.
---------------------------------------------------------------------------
Regarding the significance of the 555.6 value in equation (5) and
its impact on the number of significant digits in the resultant
minimally compliant pump efficiency ([eta],pump,STD) or
final determination of PEICL or PEIVL, DOE notes
that all coefficients in the listed equations in DOE's pump test
procedure, including the equation for the minimally compliant pump
efficiency, should be treated as infinitely significant and should not
limit the number of significant digits reported in the resultant value.
As noted in the April 2015 pumps test procedure NOPR and discussed in
more detail in section III.C.2.f, all calculations should be performed
with raw measured values and rounded only when determining
PERCL or PERVL and PEICL or
PEIVL. 80 FR 17586, 17612 (April 1, 2015) However,
considering HI's comment, DOE acknowledges that testing personnel or
manufacturers may inadvertently interpret equation coefficients to be
reflective of a given degree of resolution, precision, or significance.
Therefore, to ensure that, even if the coefficients are incorrectly
treated as carrying an indication of measurement resolution or
precision such rounding does not impact the significance of the
reported PERCL and PEICL or PERVL and
PEIVL values, DOE is adding values (zeros in most cases)
after the decimal to some of the coefficients in the minimally
compliant pump efficiency equation, as shown in equation (6):
[GRAPHIC] [TIFF OMITTED] TR25JA16.005
Where:
Q100% = BEP flow rate measured at full
impeller diameter and normalized to the nominal speed of rotation
for the tested pump (gpm),
Ns = specific speed at 60 Hz and calculated using U.S. customary
units, and
C = a constant that is set for the two-dimensional surface described
by equation (6) based on the speed of rotation and equipment type of
the pump model. This constant, or ``C-value,'' is used to establish
the minimum, mandatory pump efficiency with a minimally compliant
pump and will be established in the pump energy conservation
standard rulemaking.
DOE added sufficient significant digits to ensure efficiency can be
reported to 4 significant digits (i.e., the hundredths place for
efficiencies greater than 10 percent). DOE is also adding zeros to the
equations for calculating the reference system curve (described in
section III.E.1.c) to similarly ensure sufficient significance is
maintained throughout DOE's test procedure calculations.
In equation (6), the specific speed (Ns) is a quasi-non-
dimensional number used to classify pumps based on their relative
geometry and hydraulic characteristics. It is calculated as a function
of the rotational speed, flow rate, head of the pump, and number of
stages as shown in equation (7) below:
[GRAPHIC] [TIFF OMITTED] TR25JA16.006
Where:
Ns = specific speed,
nsp = nominal speed of rotation (rpm),
[[Page 4108]]
Q100% = BEP flow rate at full impeller and
nominal speed (gpm),
H100% = pump total head at BEP flow at full
impeller and nominal speed (ft), and
S = number of stages.
DOE notes that, in the April 2015 pumps test procedure NOPR, the
definition of specific speed did not indicate that the
H100% term should be normalized by the number of
stages. 80 FR 17586, 17604 (April 1, 2015). However, doing so is
consistent with the theoretical calculation of specific speed for
multi-stage pumps used in the pump industry,\36\ as well as the CIP
Working Group discussions and analysis \37\ and treatment in the EU 547
regulations.\38\ DOE also noted this in the second footnote to Table
1.2 in the Framework document. (Docket No. EERE-2011-BT-STD-0031, No.
13 at p. 7) To clarify that, for multi-stage RSV and VTS pumps the
specific speed should be calculated for a single stage only, DOE is
modifying equation (7) to clearly specify that the head at BEP should
be divided by the number of stages with which the pump is being tested.
Further, DOE also proposed using the capital letter ``N'' to define
nominal speed of rotation. DOE notes that HI 40.6-2014 defines the
``specified speed of rotation'' using the nomenclature
``nsp.'' While DOE believes that the phrase ``nominal speed
of rotation'' is clearer and more consistent with DOE's regulatory
approach, DOE believes referencing the same nomenclature as HI 40.6-
2014 will reduce confusion when conducting the pumps test procedure. As
such, in this final rule, DOE is updating the variable used for nominal
speed of rotation to be consistent with HI 40.6-2014.
---------------------------------------------------------------------------
\36\ Wilson, S. Specific Speed. Grundfos White Paper. Available
at: https://www.grundfos.com/content/dam/CBS/global/whitepapers/Specific-Speed.pdf.
\37\ DOE's PEI Calculator that was used to support Working Group
negotiations and analysis divided the pump total head at 100 percent
of BEP flow by the number of stages for multi-stage pumps (See, for
example, Docket No. EERE-2013-BT-NOC-0039, No. 95).
\38\ Council of the European Union. 2012. Commission Regulation
(EU) No 547/2012 of 25 June 2012 implementing Directive 2009/125/EC
of the European Parliament and of the Council with regard to
ecodesign requirements for water pumps. Official Journal of the
European Union. L 165, 26 June 2012.
---------------------------------------------------------------------------
As proposed in the April 2015 pumps test procedure NOPR, the
calculated efficiency of the minimally compliant pump reflects the pump
efficiency at BEP. To calculate PERSTD as the weighted
average input power to a minimally compliant bare pump at the same load
points as PERCL, DOE determined a method to translate the
default efficiency of a minimally compliant pump at BEP to the load
points corresponding to 75 and 110 percent of BEP flow, as shown in
equation (8):
[GRAPHIC] [TIFF OMITTED] TR25JA16.007
Where:
[omega]i = weighting at load point i (equal weighting or
0.3333 in this case);
Pu,i = the measured hydraulic output power at load point
i of the tested pump (hp); \39\
---------------------------------------------------------------------------
\39\ In the April 2015 pumps test procedure NOPR, DOE proposed
to define pump hydraulic output power using the variable
nomenclature PHydro. However, HI 40.6-2014 uses the
nomenclature Pu to refer to pump hydraulic output power.
Therefore, for consistency, DOE is adopting the nomenclature
Pu for hydraulic output power in this final rule.
---------------------------------------------------------------------------
[alpha]i = 0.947 for 75 percent of the BEP flow rate,
1.000 for 100 percent of the BEP flow rate, and 0.985 for 110
percent of the BEP flow rate;
[eta]pump,STD = the minimally compliant pump efficiency,
as determined in accordance with equation (6);
Li = the motor losses at load point i, as determined in
accordance with the procedure specified for bare pumps in sections
III.D.1 and III.D.2; and
i = load point corresponding to 75, 100, or 110 percent of BEP flow,
as determined in accordance with the DOE test procedure.
80 FR 17586, 17605 (April 1, 2015).
DOE also proposed in the April 2015 pumps test procedure NOPR that
the quotient of the hydraulic output power divided by the minimally
compliant pump efficiency for the rated pump would be used to determine
the input power to a minimally compliant pump at each load point, and
that the pump hydraulic output power for the minimally compliant pump
would be the same as that for the particular pump being evaluated.
Specifically, DOE proposed that the hydraulic power in equation (8) at
75, 100, and 110 percent of BEP flow would be calculated using the
following equation (9):
[GRAPHIC] [TIFF OMITTED] TR25JA16.008
Where:
Pu,i = the measured hydraulic output power at load point
i of the tested pump (hp);
Qi = the measured flow rate at load point i of the tested
pump (gpm);
Hi = pump total head at load point i of the tested pump
(ft);
i = load point corresponding to 75, 100, or 110 percent of BEP flow,
as determined in accordance with the DOE test procedure; and
SG = the specific gravity of water at specified test conditions.\40\
\40\ DOE notes that the specific gravity of the test liquid
specified in the DOE test procedure, which is clear water as defined
by section 40.6.5.5 of HI 40.6-2014, requires that the liquid be
between 50-86[emsp14][deg]F, with a maximum kinematic viscosity of
1.6 x 10-\5\ft\2\/s and a maximum density of 62.4 lb/
ft\3\. Based on these parameters, the specific gravity of the test
liquid will be between 1.000 and 0.995 and, therefore, can be
treated as unity when testing in accordance with the DOE test
procedure.
---------------------------------------------------------------------------
[[Page 4109]]
Id.
As indicated in equation (8), the calculated shaft input power for
the minimally compliant pump at each load point is then combined with a
minimally compliant motor for that default motor type and appropriate
size, as described in section III.D.1, and the default part load loss
curve, as described in section III.D.2, to determine the input power to
the motor at each load point. Id.
As noted previously, HI and CA IOUs expressed their support of
DOE's proposed approach. (HI, No. 8 at p. 7; CA IOUs, NOPR public
meeting transcript, No. 7 at p. 110) HI also pointed out in its written
comments that [eta]pump,STD incorrectly appeared twice in
the middle term in the denominator in equation (10) of the April 2015
pumps test procedure NOPR. (HI, No. 8 at p. 15) DOE acknowledges the
correction and has implemented the equation correctly in this final
rule document. Having received no other comments, DOE is adopting the
calculation procedure for PERSTD as proposed in the April
2015 pumps test procedure NOPR, with the minor clarifications regarding
the number of digits reported for certain equation coefficients and
calculation of specific speed for multi-stage pumps as noted above and
correcting the erroneous terms that occurred in the April 2015 pump
test procedure NOPR.
Regarding the calculation of pump hydraulic output power presented
in equation (9), DOE notes that the equation presented in the April
2015 pumps test procedure NOPR specifies a denominator of 3956. 80 FR
17586, 17605 (April 1, 2015). DOE notes that this value represents the
unit conversion from the product of flow (Q) in gpm, head in ft, and
specific gravity (which is dimensionless), to horsepower. Conversely,
DOE observes that HI 40.6-2014 specifies a value of 3960 in section
40.6.6.2 in regards to calculating pump efficiency. HI 40.6-2014 does
not specify a specific unit conversion factor for the purposes of
calculating pump hydraulic output power. Instead HI 40.6-2014 provides
the following equation (10) for determining pump power output:
[GRAPHIC] [TIFF OMITTED] TR25JA16.065
Where:
Pu = the measured hydraulic output power of the tested
pump,\41\
---------------------------------------------------------------------------
\41\ For each of the quantities listed, HI 40.6-2014 provides
multiple metric and U.S. customary units. Appendix E also provides
unit conversions.
---------------------------------------------------------------------------
[rho] = density,
Q = the volume rate of flow,
H = pump total head, and
g = acceleration due to gravity.
As shown in equation (10), the unit conversion factor can be
derived from the product of density and acceleration due to gravity. An
analysis was performed to convert from the metric units for density and
acceleration due to gravity specified in HI 40.6-2014 to the
appropriate units. This analysis found the value of 3956 to be more
accurate and have a greater amount of precision than the 3960 value
specified in HI 40.6-2014. DOE notes that, in its submitted comments,
HI suggested a definition for hydraulic power as ``the mechanical power
transferred to the liquid as it passes through the pump, also known as
pump output power. (Refer to HI 40.6-2014)'' and provided the following
equation (11):
[GRAPHIC] [TIFF OMITTED] TR25JA16.009
Where:
Pu = measured hydraulic output power (hp),
Q = measured flow rate (gpm),
H = measured pump total head (ft), and
SG = the specific gravity of the test fluid.
(HI, No. 8 at p. 10; HI, No. 15 at p. 3)
However, as noted above, DOE believes a unit conversion of 3956 is
more accurate. Therefore, to ensure consistent calculations and results
in the DOE test procedure, in this final rule DOE is maintaining a unit
conversion factor of 3956 instead of the 3960 value specified in HI
40.6-2014 and clarifying that the 3960 calculation in section 40.6.6.2
of HI 40.6-2014 should not be used. The calculation and rounding
requirements for the pumps test procedure are described further in
section III.C.2.f.
C. Determination of Pump Performance
To determine PEICL or PEIVL for applicable
pumps, DOE proposed that the test procedure would require physically
measuring the performance of either: (1) The bare pump, under the
calculation-based methods (see section III.E.1), or (2) the entire
pump, inclusive of any motor, continuous control, or non-continuous
control, under the testing-based methods (see section III.E.2).
Specifically, the input power to the pump at 75, 100, and 110 percent
of BEP flow for PEICL, or at 25, 50, 75, and 100 percent of
BEP flow for PEIVL, would be required for input into the
PEICL or PEIVL equations, respectively. DOE
proposed that, depending on whether the calculation-based method or
testing-based method were applied, a slightly different test method
would apply for measuring pump performance. In the case of the
calculation-based method, only the bare pump performance is physically
measured--the performance of the motor and any continuous or non-
continuous controls would be addressed through a series of
calculations. In the case of the testing-based method, the input power
to the pump at the motor or at the continuous or non-continuous
control, if any, is directly measured and used to calculate
PEICL or PEIVL. 80 FR 17586, 17606-07 (April 1,
2015).
1. Incorporation by Reference of HI 40.6-2014
Regarding the determination of bare pump performance, the CIP
Working Group recommended that whatever procedure DOE adopts, it should
be consistent with HI 40.6-2014 for determining bare pump performance.
(Docket No. EERE-2013-BT-NOC-0039, No. 92, Recommendation #10 at pg. 4)
In preparation of the April 2015 pump test procedure NOPR, DOE reviewed
HI 40.6-2014 and determined that it contains the relevant test methods
needed to accurately characterize the performance of the pumps that
would be addressed by this rulemaking, with a few minor modifications
noted in section III.C.2. Specifically, HI 40.6-2014 defines and
explains how to calculate pump power input,\42\ driver power input (for
testing-based methods),\43\ pump power output,\44\
[[Page 4110]]
pump efficiency,\45\ bowl efficiency,\46\ overall efficiency,\47\ and
other relevant quantities at the specified load points necessary to
determine PEICL and PEIVL. HI 40.6-2014 also
contains appropriate specifications regarding the scope of pumps
covered by the test methods, test methodology, standard rating
conditions, equipment specifications, uncertainty calculations, and
tolerances.
---------------------------------------------------------------------------
\42\ The term ``pump power input'' in HI 40.6-2014 is defined as
``the power transmitted to the pump by its driver'' and is
synonymous with the term ``pump shaft input power,'' as used in this
document.
\43\ The term ``driver power input'' in HI 40.6-2014 is defined
as ``the power absorbed by the pump driver'' and is synonymous with
the term ``pump input power to the driver,'' as used in this
document.
\44\ The term ``pump power output'' in HI-40.6 is defined as
``the mechanical power transferred to the liquid as it passes
through the pump, also known as pump hydraulic power.'' It is used
synonymously with ``pump hydraulic power'' in this document.
\45\ The term ``pump efficiency'' is defined in HI 40.6-2014 as
a ratio of pump power output to pump power input.
\46\ The term ``bowl efficiency'' is defined in HI 40.6-2014 as
a ratio of pump power output to bowl assembly power input and is
applicable only to VTS and RSV pumps.
\47\ The term ``overall efficiency'' is defined in HI 40.6-2014
as a ratio of pump power output to driver power input and describes
the combined efficiency of a pump and driver.
---------------------------------------------------------------------------
Accordingly, in the April 2015 pumps test procedure NOPR, DOE
proposed to incorporate by reference HI 40.6-2014 as part of DOE's test
procedure for measuring the energy consumption of pumps, with the minor
modifications and exceptions listed in III.C.2.a through III.C.2.f of
the NOPR document and discussed in more detail in section III.C.2 of
this final rule. 80 FR 17586, 17607-12 (April 1, 2015).
HI commented that it agrees with using HI 40.6-2014 as the basis of
DOE test procedure for pumps. (HI, No. 8 at p. 15) DOE received no
other comments on this proposal in the April 2015 pumps test procedure
NOPR and, therefore, is incorporating by reference HI 40.6-2014 as the
basis for the DOE pumps test procedure, with the minor modifications
and exceptions listed in section III.C.2 of this final rule.
2. Minor Modifications and Additions to HI 40.6-2014
In general, DOE finds the test methods contained within HI 40.6-
2014 are sufficiently specific and reasonably designed to produce test
results that accurately measure the energy efficiency and energy use of
applicable pumps. However, as proposed in the April 2015 pumps test
procedure NOPR, DOE believes a few minor modifications are necessary to
ensure repeatable and reproducible test results and to provide
measurement methods and equipment specifications for the entire scope
of pumps that DOE is addressing as part of this final rule. DOE's
proposed modifications and clarifications to HI 40.6-2014, comments
received on those topics, DOE's responses to those comments, and any
changes to the April 2015 pumps test procedure NOPR proposals that DOE
is making as a result are addressed in the subsequent sections
III.C.2.a through III.C.2.f.
a. Sections Excluded From DOE's Incorporation by Reference
While DOE is referencing HI 40.6-2014 as the basis for its test
procedure, in the April 2015 pumps test procedure NOPR, DOE noted that
some sections of the standard are not applicable to DOE's regulatory
framework. Specifically, DOE noted that section 40.6.5.3 provides
requirements regarding the generation of a test report and appendix
``B'' provides guidance on test report formatting, both of which are
not required for testing and rating pumps in accordance with DOE's
procedure. In addition, DOE noted that section A.7 of appendix A,
``Testing at temperatures exceeding 30 [deg]C (86 [deg]F),'' HI 40.6-
2014 addresses testing at temperatures above 30 [deg]C (86 [deg]F),
which is inconsistent with DOE's proposal to only test with liquids
meeting the definition of ``clear water'' established in section
40.6.5.5 of HI 40.6-2014. As such, DOE proposed not incorporating by
reference section 40.6.5.3, section A.7, and appendix B of HI 40.6-
2014. 80 FR 17586, 17608 (April 1, 2015).
HI commented that it agrees with the proposal to not incorporate by
reference section 40.6.5.3, section A.7, and appendix B of HI 40.6-2014
as part of the DOE test procedure. (HI, No. 8 at 15) DOE received no
other comments on this proposal in the April 2015 pumps test procedure
NOPR and, as such, is adopting the proposal in the April 2015 pumps
test procedure NOPR to incorporate by reference HI 40.6-2014 except for
section 40.6.5.3, section A.7, and appendix B in this final rule.
In reviewing the relevant sections of HI 40.6-2014, DOE also noted
that section 40.6.4.1, ``Vertically suspended pumps,'' which contains
specific testing instructions for vertically suspended VS1 and VS3
pumps, mentions VS0 pumps. Specifically, section 40.6.4.1 states ``A
variation to this is pump type VS0 . . . [a] VS0 [pump] is evaluated as
a pump end only similar to the bowl performance and efficiency
described for the line-shafted product.'' DOE notes that this language
in HI 40.6-2014 is intended to exclude VS0 pumps from the
specifications in section 40.6.4.1 and specify that testing for VS0, as
a type of vertical turbine pump, must consider only bowl assembly total
head and, for VTS bare pumps, only the bowl assembly power input, as
defined in section 40.6.2 of HI 40.6-2014. However, DOE believes that
the language of section 40.6.4.1 is somewhat confusing and may lead to
misinterpretation by some not familiar with all the varieties of
vertical turbine and vertically suspended pumps and their specific
testing considerations. Therefore, in this final rule, DOE is
clarifying that the specifications of section 40.6.4.1 of HI 40.6-2014
do not apply to VTS pumps and that the performance of VTS bare pumps
considers the bowl performance only. For VTS pumps sold with motors
evaluated using the testing-based approaches discussed in section
III.E.2, the bowl assembly total head and driver power input are to be
used to determine the pump performance.
b. Data Collection and Determination of Stabilization
In order to ensure the repeatability of test data and results, the
DOE pump test procedure must provide instructions regarding how to
sample and collect data at each load point such that the collected data
are taken at stabilized conditions that accurately and precisely
represent the performance of the pump at that load point. Section
40.6.5.5.1 of HI 40.6-2014 provides that all measurements shall be made
under steady state conditions, which are described as follows: (1) No
vortexing, (2) margins as specified in ANSI/HI 9.6.1 Rotodynamic Pumps
Guideline for NPSH Margin, and (3) when the mean value of all measured
quantities required for the test data point remains constant within the
permissible amplitudes of fluctuations defined in Table 40.6.3.2.2 over
a minimum period of 10 seconds before performance data are collected.
HI 40.6-2014 does not specify the measurement interval for
determination of steady state operation. However, DOE understands that
a minimum of two stabilization measurements are required to calculate
an average. DOE proposed in the April 2015 pumps test procedure NOPR
that the stabilization measurement interval should not be greater than
5 seconds, thereby allowing for no fewer than two separate measurements
that each have an integration time of no more than 5 seconds. 80 FR
17586, 17606 (April 1, 2015).
Section 40.6.3.2.2 of HI 40.6-2014, ``Permissible fluctuations,''
also provides that permissible damping devices may be used to minimize
noise and large fluctuations in the data in order to achieve the
specifications noted in Table 40.6.3.2.2. In the April 2015 pumps test
procedure NOPR, DOE proposed to specify that damping devices would only
be permitted to integrate up to the measurement interval to ensure that
each stabilization data point is reflective of a separate measurement.
80 FR 17586, 17606 (April 1, 2015).
DOE requested comment on its proposal to require that data be
[[Page 4111]]
collected at least every 5 seconds for all measured quantities. HI
commented that collecting stabilization data every 5 seconds is not
standard industry practice, and that this practice would require
manufacturers to obtain automated data acquisition systems, posing
additional and unnecessary burden not agreed to by the CIP Working
Group. (HI, No. 8 at pp. 15-16) HI recommended that steady-state
operation be verified by recording flow at the beginning and end of the
data acquisition and checking that the difference in flow is within the
allowable fluctuation identified in HI 40.6-2014 (Table 40.6.3.2.2). HI
also stated that the two flow readings should be separated by a minimum
of 5 seconds.
DOE also requested comment on its proposal to allow damping
devices, as described in section 40.6.3.2.2, but with integration
limited to the data collection interval and HI commented that it agrees
with this proposal except with respect to the interval used for data
collection. (HI, No. 8 at p. 16)
After reviewing HI's comments and considering the proposal in the
April 2015 pump test procedure NOPR, DOE maintains that at least two
unique measurements, at a minimum, are necessary to determine
stabilization prior to recording a measurement at a given load point.
DOE also agrees with HI that it is appropriate to continue to reference
the requirements for permissible fluctuations and minimum duration of
stabilization testing, as detailed in HI 40.6-2014 sections 40.6.3.2.2
and 40.6.5.5.1. However, in light of HI's concern regarding automated
data collection requirements if the interval of data collection is
specified as 5 seconds, DOE has determined that a threshold for the
data collection interval does not need to be specified to determine
steady state operation provided the other requirements for
stabilization are satisfied. That is, provided that at least two unique
measurements are recorded, their mean computed, and that the two unique
measurements are not farther away from the mean than the tolerance
specified in the ``permissible amplitude of fluctuation'' table (Table
40.6.3.2.2) in HI 40.6-2014, the pump can be determined to be
stabilized and data recorded for the purposes of conducting the DOE
test procedure. DOE notes that section 40.6.5.5.1 requires that steady
state be determined for a minimum of 10 seconds, but that a longer time
can be used if necessary, in which case the two unique measurements
could be recorded more than 5 seconds apart. For example, if a facility
were not equipped with a data acquisition system, stabilization could
be determined over 1 minute and data taken every 30 seconds to
determine stabilized operation at each flow point.
Regarding the use of damping devices, DOE is maintaining the
requirements that the integration time for each measurement cannot be
greater than the measurement interval. This is necessary to ensure that
the measurements used to determine stabilization are, in fact, unique.
Therefore, in this test procedure final rule, DOE is adopting
stabilization requirements consistent with HI section 40.6.3.2.2 and
section 40.6.5.5.1, except that at least two unique measurements must
be used to determine stabilization and any damping devices are only
permitted to integrate up to the data collection interval. DOE notes
that, for physical dampening devices, the pressure indicator/signal
must register 99 percent of a sudden change in pressure over the
measurement interval to satisfy the requirement for unique
measurements, consistent with annex D of ISO 3966:2008(E),
``Measurement of fluid flow in closed conduits--Velocity area method
using Pitot static tubes,'' which is referenced in HI 40.6-2014 for
measuring flow with pitot tubes.
c. Modifications Regarding Test Consistency and Repeatability
Sections 40.6.5.6 and 40.6.5.7 of HI 40.6-2014 specify test
arrangements and test conditions. However, DOE finds that the
standardized test conditions described in these sections are not
sufficient to produce accurate and repeatable test results. To address
these potential sources of variability or ambiguity, in the April 2015
pumps test procedure NOPR, DOE proposed to adopt several additional
requirements regarding the nominal pump speed, the input power
characteristics, and the number of stages to test for multi-stage pumps
to further specify the procedures for testing pumps in a standardized
and repeatable manner. 80 FR 17586, 17608 (April 1, 2015).
Pump Speed
The rotating speed of a pump affects the efficiency and
PEICL or PEIVL of that pump. To limit variability
and increase repeatability within the test procedure, DOE proposed in
the April 2015 pumps test procedure NOPR to require all test data to be
normalized to one of two nominal speeds--1,800 or 3,600 rpm at 60 Hz.
Specifically, pumps designed to operate at any speed of rotation
between 2,880 and 4,320 rpm would be rated at 3,600 rpm, and pumps
designed to operate at any speed of rotation between 1,440 and 2,160
rpm would be rated at 1,800 rpm, as noted in Table III.3. 80 FR 17586,
17609 (April 1, 2015).
Table III.3--Nominal Speed of Rotation for Different Configurations of Pumps
----------------------------------------------------------------------------------------------------------------
Pump design speed of Nominal speed of
Pump configuration rotation Style of motor rotation for rating
----------------------------------------------------------------------------------------------------------------
Bare Pump............................ 2,880 and 4,320 rpm.... N/A.................... 3,600 rpm.
1,440 and 2,160 rpm.... 1,800 rpm.
N/A.................... 2-pole Induction Motor. 3,600 rpm.
N/A.................... 4-pole Induction Motor. 1,800 rpm.
Pump + Motor OR...................... N/A.................... Non-Induction Motor 3,600 rpm.
Pump + Motor + Control............... Designed to Operate
between 2,880 and
4,320 rpm.
N/A.................... Non-Induction Motor 1,800 rpm.
Designed to Operate
between 1,440 and
2,160 rpm.
----------------------------------------------------------------------------------------------------------------
DOE proposed that, for pumps sold without motors, the nominal speed
would be selected based on the speed of rotation for which the pump is
designed to be operated, while for pumps sold with motors, the nominal
speed of rotation would be selected based on the speed(s) for which the
motor is designed to operate. DOE also clarified that pumps designed to
operate at speeds that include both ranges would be rated at both
nominal speeds of rotations since each nominal speed rating represents
a different basic model of pump. Finally, DOE noted that these speed
ranges are not exclusive. That is, if a pump were to be designed to
operate from 2,600 to 4,000 rpm, such a pump
[[Page 4112]]
would have a nominal speed of rotation of 3,600 rpm for the purposes of
testing and rating the pump, even though part of the operating range of
the pump (i.e., 2,600 to 2,880 rpm) falls outside DOE's specified speed
ranges.
In DOE's April 2015 pumps test procedure NOPR proposal, DOE
acknowledged that it may not be feasible to operate pumps during the
test at exactly the nominal speeds of 3,600 or 1,800 rpm and noted that
section 40.6.5.5.2 of HI 40.6-2014 allows for tested speeds up to 20
percent off of the nominal speed, provided the tested speed does not
vary more than 1 percent at each load point as required by
section 40.6.3.2.2 of HI 40.6-2014. However, to ensure consistent and
comparable test results, DOE proposed that all data collected during
the test procedure at the speed measured during the test should be
adjusted to the nominal speed prior to use in subsequent calculations
and the PEICL or PEIVL of a given pump should be
based on the nominal speed. Id. For pumps sold with motors and
continuous or non-continuous controls and that are tested using the
testing-based method described in section III.E.2.c, DOE proposed that
this adjustment to the nominal speed only apply at the 100 percent of
BEP flow load point and that subsequent part load points be measured at
reduced speed and used in subsequent calculations without adjustment.
DOE also proposed to use the methods in HI 40.6-2014 section
40.6.6.1.1, ``Translation of the test results into data based on the
specified speed of rotation (for frequency) and density'' to adjust any
data from the tested speed to the nominal speed. Id.
DOE requested comment on its proposal to require data collected at
the pump speed measured during testing to be normalized to the nominal
speeds of 1,800 and 3,600 rpm. HI commented that it agrees with the
proposal. (HI, No. 8 at p. 16)
Therefore, in this test procedure final rule, DOE is opting to
adopt the operating speed limits proposed in the April 2015 pumps test
procedure NOPR and discussed in section III.A.4 for the purposes of
applying this test procedure final rule.
DOE also requested comment on its proposal to adopt the
requirements in HI 40.6-2014 regarding the deviation of tested speed
from nominal speed and the variation of speed during the test,
specifically regarding whether maintaining tested speed within 1 percent of the nominal speed is feasible and whether this
approach would produce more accurate and repeatable test results. HI
commented that it does not believe it is feasible to maintain tested
speed within 1 percent of the specified nominal speed
because typical motor speed-load curves do not meet this criterion.
(HI, No. 8 at p. 16) However, HI also noted that data could be
collected and rotating speed maintained at 1 percent for a
particular data collection point. DOE believes that HI may have
misinterpreted the proposal in the April 2015 pumps test procedure
NOPR. In the NOPR, DOE proposed maintaining the speed of rotation at
each test point within the 1 percent speed tolerance, but
that the speed of rotation at each test point could vary from the
nominal speed of rotation 20 percent, consistent with HI
40.6-2014. DOE agrees that the 1 percent speed tolerance is
applicable to determining stabilization at each data collection point
only and is not determined relative to nominal speed and, therefore, is
adopting the April 2015 pump test procedure NOPR proposal to adopt the
nominal speed tolerances listed in section 40.6.5.5.2 of HI 40.6-2014,
as well as the stabilization requirements provided in section
40.6.3.2.2 of HI 40.6-2014 in this test procedure final rule.
Additionally, DOE is adopting the provisions that all measured data be
translated to the nominal rating speed.
Power Supply Characteristics
Because pump power consumption is a component of the proposed
metric, inclusive of any motor and continuous or non-continuous
controls, measuring power consumption is an important element of the
test. The characteristics of the power supplied to the pump affect the
accuracy and repeatability of the measured power consumption of the
pump. As such, to ensure accurate and repeatable measurement of power
consumption, in the April 2015 pumps test procedure NOPR, DOE specified
nominal values for voltage, frequency, voltage unbalance, total
harmonic distortion (THD), and impedance levels, as well as tolerances
about each of these quantities, that must be maintained at the input
terminals to the motor, continuous control, or non-continuous control,
as applicable when performing the testing-based methods or when using a
calibrated motor to determine bare pump performance. 80 FR 17586, 17610
(April 1, 2015).
To determine the appropriate power supply characteristics for
testing pumps with motors (but without continuous or non-continuous
controls) and pumps with both motors and continuous or non-continuous
controls, DOE examined applicable test methods for electric motors and
VSD systems. DOE determined that the Institute of Electrical and
Electronics Engineers (IEEE) Standard 112-2004, ``IEEE Standard Test
Procedure for Polyphase Induction Motors and Generators,'' (IEEE 112-
2004) and the Canadian Standards Association (CSA) C390-10, ``Test
methods, marking requirements, and energy efficiency levels for three-
phase induction motors,'' (CSA C390-10) are the most relevant test
methods for measuring input power to electric motors, as they are the
test methods incorporated by reference as the DOE test procedure for
electric motors. Other widely referenced industry standard test methods
for motors include: IEC 60034-1 Edition 12.0 2010-02, ``Rotating
electrical machines--Part 1: Rating and performance'' (IEC 60034-
1:2010) and NEMA MG 1-2014, ``Motors and Generators'' (NEMA MG 1-2014).
DOE also identified both AHRI 1210-2011, ``2011 Standard for
Performance Rating of Variable Frequency Drives,'' (AHRI 1210-2011) and
the 2013 version of CSA Standard C838, ``Energy efficiency test methods
for three-phase variable frequency drive systems,'' (CSA C838-13) as
applicable methods for measuring the performance of VSD control
systems. A summary of DOE's proposed power supply characteristics and
the requirements of the industry standards DOE referenced in developing
such a proposal are summarized in Table III.4.
Table III.4--Summary of Tolerances Proposed by DOE in the April 2015 Pumps Test Procedure NOPR and Referenced in Relevant Industry Standards
--------------------------------------------------------------------------------------------------------------------------------------------------------
Voltage Voltage waveform
Reference document Section unbalance Voltage tolerance Frequency tolerance distortion Source impedance
--------------------------------------------------------------------------------------------------------------------------------------------------------
April 2015 Pumps Test III.C.2.c..... 0.5%..... 0.5%..... THD <=5%.............
Procedure NOPR Proposal. minus>0.5%.
HI 40.6-2014 (calibrated C.4.1......... ............. 5%....... 1%.......
motors).
[[Page 4113]]
CSA C390-10 (motors)......... 5.2........... 0.5%..... 0.5%..... THD <=5% (to 20th)...
minus>0.5%.
IEC 60034-1:2010 (motors).... 7.3........... ............. 5% * 2% *
(zone A). (zone A).
9.11.......... ............. ..................... ..................... THD <=5% (to 100th).. .....................
IEEE 112-2004 (motors)....... 3.1........... <=0.5%....... ..................... 0.5%..... THD <=5%.............
NEMA MG 1-2014 (motors)...... 7.7.3.2....... <=1%......... ..................... 0.5%..... deviation factor .....................
<=10%.
12.44.1....... ............. 10% **... 5% **....
12.45......... <=1% [dagger]
AHRI 1210-2011 (VFDs)........ 5.1.2......... <=0.5%....... 0.5%..... 0.5%..... ..................... <=1%.
CSA C838-13 (VFDs)........... 5.3........... 0.5%..... 0.5%..... THD <=5% (to 20th)... 1% < value <=3% of
minus>0.5%. VFD.
--------------------------------------------------------------------------------------------------------------------------------------------------------
* Values are for the overall bounds of the hexagonal surface in IEC Figure 12.
** NEMA states that performance within these voltage and frequency variations will not necessarily be in accordance with the standards established for
operation at rated voltage and frequency.
[dagger] NEMA states that performance will not necessarily be the same as when the motor is operating with a balanced voltage at the motor terminals.
HI commented that it disagrees with the power conditioning
requirements proposed in the April 2015 pumps test procedure NOPR;
knows of no pump test labs that meet them; and views them as a
significant and unnecessary burden to manufacturers that were not
agreed to by the CIP Working Group. HI specifically cited costs
associated with the proposed limitation on voltage unbalance, and noted
that the nominal motor efficiency values used for the calculation
method have a less stringent tolerance of 2 percent. HI also indicated
that testing with unconditioned power will result in a lower efficiency
value and a higher PEI value than when testing with conditioned power.
HI proposed that whereas conditioned power, as proposed in the April
2015 pumps test procedure NOPR, should be used for DOE enforcement
testing and motor calibration, manufacturer test labs should only be
held to the 3 percent limit for driver input power fluctuation
specified in HI 40.6-2014. (HI, No. 8 at pp. 16-18)
Regal Beloit stated during the April 2015 NOPR public meeting that
motor manufacturers faced similar challenges when motor standards were
introduced, and third-party test labs adapted to help meet the power
conditioning requirements. Regal Beloit also indicated that AHRI 1210
was not developed for pumps, and CSA C838 would be preferred. In
addition, Regal Beloit expressed concern that any loosening of the
power conditioning requirements could hinder differentiation between
lower and higher performing products. (Regal Beloit, NOPR public
meeting transcript, No. 7 at pp. 137-46)
As noted in the April 2015 pumps test procedure NOPR, DOE
recognizes that driver efficiency can vary: (a) When the input voltage
level is not exactly at the nameplate voltage, (b) when the fundamental
frequency of the input voltage waveform is not exactly 60 Hz, (c) when
input voltage phases are unbalanced, and/or (d) when the input voltage
waveform is not strictly sinusoidal. However, DOE acknowledges the
concerns of HI regarding the burden of providing power meeting strict
voltage, frequency, voltage unbalance, and THD limits. As EPCA requires
DOE test procedures to not be unduly burdensome to conduct (42 U.S.C.
6314(a)(2)), DOE, in this final rule, is reconsidering the proposed
requirements regarding the power supply characteristics to find a
compromise among repeatability, accuracy, and test burden.
DOE notes that HI's proposal of a 3 percent tolerance
on power is not feasible without some parameters around power supply
characteristics, as variation in voltage unbalance, harmonics, voltage,
and frequency will affect the variability in the measurement of input
power to the pump insofar as it will affect the performance and
efficiency of the motor. That is, for example, increased voltage
unbalance will affect motor performance such that testing the same pump
sold with a motor under differing voltage unbalance conditions will
result in different measured pump performance. This can be viewed
either as: (1) Different (typically lower) hydraulic output for the
same input power to the motor or (2) different (typically increased)
input power to the motor to deliver the same hydraulic output power.
Under the latter scenario, DOE has developed an approach to
correlate variability in power supply characteristics with variability
in the measured input power to the motor. Similarly, DOE separately
considered how variability in power supply characteristics would impact
input power to the continuous or non-continuous controls. Specifically,
DOE determined, for each power supply characteristic (i.e., voltage,
frequency, voltage unbalance, and voltage THD) the level of variability
that was associated with HI's proposed acceptable tolerance of 3 percent on driver input power. As such, DOE considered each of
the power supply variables individually to determine if alternative,
less burdensome requirements were feasible.
Regarding the impact of variation in voltage, section 12.44.1 of
NEMA MG 1-2014 specifies that AC motors shall operate successfully
under running conditions at rated load with a variation in the voltage
up to 10 percent of rated (nameplate) voltage with rated
frequency for induction motors. Similarly, according to Figure 5-1 in
the DOE Advanced Manufacturing Office (AMO) ``Premium Efficiency Motor
Selection and Application Guide'' (AMO motor handbook), the efficiency
of a ``pre-EPAct'' \48\ standard efficiency motor varies by less than
3 percent when operated at 10 percent of
nameplate voltage. Section 2.2.2 of ANSI C84.1-2011 states that the
nominal voltage of a system is near the voltage level at which the
system
[[Page 4114]]
normally operates, and that systems generally operate at voltage levels
about 5 to 10 percent below the maximum system voltage for which system
components are designed. DOE also notes that section C.4.1 of HI 40.6-
2014 indicates that when a calibrated motor is used to determine the
pump input power, the voltage shall be the same as used during the
calibration of the motor with a tolerance of 5 percent;
this specification is consistent with the 5 percent
outermost limits in Figure 12 of IEC 60034-1:2010 for zone A
(continuous operation). In consideration of these standards, DOE has
determined that, within reasonable limits, motor performance does not
appear to be strongly affected by variation in voltage. However, DOE
believes that it is important to ensure voltage is maintained within
those reasonable limits. Therefore, in this final rule, DOE is adopting
a tolerance on voltage consistent with the requirements in HI 40.6-2014
of 5.0 percent of the nominal rated voltage. DOE believes
such a proposal provides representative measurements without imposing
undue test burden on manufacturers.
---------------------------------------------------------------------------
\48\ Energy Policy Act of 2005, Public Law 109-58, 119 Stat. 594
---------------------------------------------------------------------------
Considering the impact of frequency on the rated performance of
pumps and motors, the AMO motor handbook states that a premium
efficiency motor is usually 0.5 to 2.0 percent more efficient when
operating at 60 Hz than when the same motor is driven by a 50-Hz power
supply, suggesting that motor performance is not strongly dependent on
frequency. However, section C.4.1 of HI 40.6-2014 indicates that when a
calibrated motor is used to determine the pump input power, the
frequency shall be the same as used during the calibration of the motor
with a tolerance of 1 percent. DOE believes that the HI
requirement would be equally applicable to determining the performance
of pumps sold with motors and pumps sold with motors and continuous or
non-continuous controls under the testing-based methods to ensure
repeatable and accurate measurements. Therefore, in this final rule,
DOE is relaxing the proposal in the April 2015 pumps test procedure
NOPR to instead limit frequency variation of 1.0 percent of
nameplate frequency, consistent with HI 40.6-2014. DOE also notes that
the U.S. electric grid typically provides power at a frequency within
these bounds and, as such, DOE believe such a tolerance will not impose
undue test burden. Further, DOE believes that maintaining tolerances
consistent with the typical U.S. electric power supply is necessary to
ensure repeatability of the test and ensure that the test is
representative of the energy consumption of the equipment.
Specifically, a specification of 1 percent is consistent
with the 1 percent tolerance for continuous operation
across all durations of off-nominal frequency specified in the North
American Electric Reliability Corporation (NERC) Standard PRC-024-1,
``Generator Frequency and Voltage Protective Relay Settings.''
Regarding voltage unbalance, DOE notes that motor performance will
vary as a function of voltage unbalance. Specifically, NEMA MG 1-2014
includes a horsepower derating curve for up to 5 percent voltage
unbalance and recommends limiting voltage unbalance to 1 percent,
noting that motor performance will not necessarily be the same as when
the motor is operating with a balanced voltage at the motor terminals.
Similarly, Table 5-3 in the AMO motor handbook relates a voltage
unbalance of 3 percent to a decrease in motor efficiency of 2 to 3
percent, compared with a decrease of 5 percent or more for a voltage
unbalance of 5 percent.\49\ DOE notes that a variation of 3 percent in
motor efficiency equates to a 3 percent variability in measured input
power to the motor.
---------------------------------------------------------------------------
\49\ DOE Office of Energy Efficiency and Renewable Energy
(EERE), Premium Efficiency Motor Selection and Application Guide--A
Handbook for Industry (February 2014, www.energy.gov/eere/amo/motor-systems).
---------------------------------------------------------------------------
Given the dependence of motor, and thus pump, performance on
voltage unbalance, DOE then evaluated the relative burden associated
with providing different levels of voltage unbalance in the test
facility, in an effort to determine a level of voltage unbalance that
would not be unduly burdensome to specify in the test procedure. DOE
researched typical levels of voltage unbalance available on the
national electric grid, based on utility standards and specifications
for generation and distribution of power. NEMA MG 1-2014 states that if
a motor is subjected to more than 1 percent voltage unbalance the
manufacturer should be consulted regarding this unusual service
condition, and the AMO motor handbook states that unbalances exceeding
1 percent will void most manufacturers' warranties. DOE also found that
PG&E Electric Rule No. 2 states that the voltage balance between phases
for service delivery voltages will be maintained by PG&E as close as
practicable to 2.5 percent.\50\ Similarly, Annex C of ANSI C84.1-2011
indicates that approximately 98 percent of the electric supply systems
surveyed were found to be below 3.0 percent voltage unbalance, and 66
percent were found to be below 1.0 percent; the standard states that
electric supply systems should be designed and operated to limit the
maximum voltage unbalance to 3 percent when measured at the electric-
utility revenue meter under no-load conditions.\51\ Therefore, DOE
determines 3.0 percent voltage unbalance provides a reasonable
tolerance, would be generally available to most testing facilities
using grid-supplied power and would limit the impact on input power to
less than 3 percent, consistent with HI's recommendation.
---------------------------------------------------------------------------
\50\ Accessed on August 21, 2015, at www.pge.com/tariffs/tm2/pdf/ELEC_RULES_2.pdf.
\51\ American National Standard For Electric Power Systems and
Equipment--Voltage Ratings (60 Hertz).
---------------------------------------------------------------------------
Regarding limitations on harmonic distortion on the power supply,
the AMO publication, ``Improving Motor and Drive System Performance''
(AMO motor sourcebook) states that electrical equipment is often rated
to handle 5 percent THD (as defined in IEEE Std 519), and notes that
motors are typically much less sensitive to harmonics than computers or
communication systems.\52\ Similarly, IEC 60034-1:2010 specifies a
limit of 5 percent voltage THD, measured to the 100th harmonic. In
addition, for bus voltage of 1.0 kV or less at the point of common
coupling (PCC), section 5.1 of IEEE Std 519-2014 recommends line-to-
neutral harmonic voltage limits of 5.0 percent individual harmonic
distortion and 8.0 percent voltage THD for weekly 95th percentile short
time (10 min) values, measured to the 50th harmonic. The IEEE standard
also indicates that daily 99th percentile very short time (3 second)
values should be less than 1.5 times these values. NEMA MG 1-2014 uses
different metrics (voltage waveform deviation factor and harmonic
voltage factor or HVF) to establish harmonic voltage limits and
horsepower derating factors for motors. However, the NEMA metrics are
not directly comparable to voltage THD, and the HVF derating curve was
developed under the assumption that any voltage unbalance or even
harmonics are negligible.\53\ In
[[Page 4115]]
consideration of these recommendations regarding voltage THD limits and
potentially significant impacts on motor performance, in this final
rule, DOE is limiting voltage THD to <=12.0 percent (corresponding to
the IEEE 3-second limit but measured to the 40th harmonic) in this
final rule to ensure representative and repeatable measurements. DOE
also notes that a limit of <=12.0 percent voltage THD is not unduly
burdensome for test labs as it is within the bounds of standardized
voltage THD limits placed on grid operators and, thus, is generally
available on the national electric power grid.
---------------------------------------------------------------------------
\52\ DOE EERE, Improving Motor and Drive System Performance--A
Sourcebook for Industry (February 2014, www.energy.gov/eere/amo/motor-systems).
\53\ NEMA's voltage deviation factor is calculated as the
maximum difference between corresponding ordinates of the voltage
waveform and of the equivalent sine wave, divided by the maximum
ordinate of the equivalent sine wave when the waves are superimposed
such that the maximum difference is minimized. Harmonic voltage
factor (HVF) is calculated by squaring the ratio of harmonic voltage
to rated voltage for each odd harmonic not divisible by three (up to
some specified order, e.g., the 13th harmonic in IEC 60034-1:2010),
dividing each result by the order of the corresponding harmonic, and
then taking the square root of the sum of these quotients. Voltage
THD is calculated by taking the square root of the sum of squares of
each RMS harmonic voltage (up to some specified order, e.g., the
50th harmonic in IEEE 519-2014), and then dividing by the RMS
fundamental voltage.
---------------------------------------------------------------------------
DOE also discussed source impedance in the NOPR and considered
adopting specifications in AHRI 1210-2011 (source impedance <=1
percent) or CSA C838-13 (source impedance > 1.0 percent of VFD and <=
3.0 percent of VFD) for motors and speed controls. 80 FR 17586, 17611-
12 (April 1, 2015). DOE understands that a nonlinear load can distort
the voltage waveform, depending on the magnitudes of the source
impedance and current distortion.\54\ However, DOE also understands
that motors are not a significant source of harmonics in the current
waveform if the steel core is not magnetically saturated,\55\ and that
motor efficiency is not greatly affected by harmonics in the voltage
waveform if voltage THD is sufficiently limited. Therefore, in this
final rule, DOE is not specifying source impedance requirements. DOE
believes that the adopted requirements for the preceding four power
supply characteristics (i.e., voltage unbalance, voltage, frequency,
and voltage THD) will sufficiently limit variability in motor
performance resulting from variations in the characteristics of the
mains power supplied to the motor.
---------------------------------------------------------------------------
\54\ IEEE Std 1560-2005, ``IEEE Standard for Methods of
Measurement of Radio-Frequency Power-Line Interference Filter in the
Range of 100 Hz to 10 GHz'' (February 2006).
\55\ Fire Protection Research Foundation, ``Evaluation of the
Impact on Non-Linear Power On Wiring Requirements for Commercial
Buildings'' (June 2011, www.nfpa.org/research/fire-protection-research-foundation/projects-reports-and-proceedings/electrical-safety/new-technologies-and-electrical-safety/evaluation-of-the-impact-on-non-linear-power).
---------------------------------------------------------------------------
Regarding the impact of variation in power supply characteristics
on continuous and non-continuous controls, DOE understands that motors,
continuous controls, and non-continuous controls all have similar power
conditioning requirements because they will be subjected to similar
electrical conditions in the field. That is, based on DOE's research,
manufacturers appear to have designed motors to be reasonably tolerant
of variability in power supply characteristics (or power quality) that
are characteristic of typical grid operation, but their performance is
significantly impacted at levels outside the bounds of that commonly
experienced in their field. While less information is available of the
response of continuous and non-continuous controls to these power
supply variables, DOE expects this relationship to be true for such
controls as well. For example, NEMA guidance published in 2007 states
that adjustable frequency controls can operate on power systems with a
voltage unbalance not exceeding 3 percent.\56\ In addition, guidance
published by the Electric Power Research Institute (EPRI) in 2001
indicates that VSDs should be specified to operate without any problem
for a voltage unbalance of 2 percent.\57\ Consequently, DOE is
applying, in this final rule, the same power conditioning requirements
to pumps tested with motors and pumps tested with motors and continuous
or non-continuous controls.
---------------------------------------------------------------------------
\56\ NEMA Application Guide for AC Adjustable Speed Drive
Systems (December 2007, www.nema.org/Standards/Pages/Application-Guide-for-AC-Adjustable-Speed-Drive-Systems.aspx).
\57\ EPRI Guide to the Industrial Application of Motors and
Variable-Speed Drives (September 2001, www.epri.com/abstracts/Pages/ProductAbstract.aspx?ProductId=000000000001005983).
---------------------------------------------------------------------------
DOE notes that these requirements are applicable to pumps sold with
motors and pumps sold with motors and continuous or non-continuous
controls rated using the testing-based method, as such methods require
measurement of electrical input power to the motor or control.
Commensurately, these requirements are applicable to any pumps rated
using a calculation-based method, including bare pumps, pumps sold with
applicable electric motors, and pumps sold with applicable electric
motors and continuous controls, when the bare pump is tested using a
calibrated motor to determine pump shaft input power. Pumps evaluated
based on the calculation method where the input power to the motor is
determined using equipment other than a calibrated motor would not have
to meet these requirements, as variations in voltage, frequency,
voltage unbalance, and voltage THD are not expected to significantly
affect the tested pump's energy performance.
Number of Stages for Multi-Stage Pumps
RSV and VTS pumps are typically multi-stage pumps that may be
offered in a variety of stages.\58\ The energy consumption
characteristics of such multi-stage pumps vary, approximately linearly,
as a function of the number of stages. However, to simplify
certification requirements and limit testing burden, DOE proposed in
the April 2015 pumps test procedure NOPR that certification of RSV and
VTS pumps be based on testing with the following number of stages:
---------------------------------------------------------------------------
\58\ The stages of VTS pumps are also commonly referred to as
``bowls.'' See section 2.1.3.1 and Figure 2.1.3.1 of ANSI/HI 2.1-
2.2-2014.
---------------------------------------------------------------------------
RSV: 3 stages; and
VTS: 9 stages.
If a model is not available with that specific number of stages,
the model would be tested with the next closest number of stages
distributed in commerce by the manufacturer, or the next higher number
of stages if both the next lower and next higher number of stages are
equivalently close to the required number of stages. This is consistent
with DOE's proposal, discussed previously in section III.A.1.c, that
variation in number of stages for RSV and VTS pumps would not be a
characteristic that constitutes different basic models. 80 FR 17586,
17610 (April 1, 2015).
In response to DOE's proposal regarding testing of multi-stage RSV
and VTS pumps, HI commented that it agrees with this proposal. (HI, No.
8 at p. 18) DOE received no other comments on this proposal and has,
therefore, adopted the provisions for testing multi-stage RSV and VTS
pumps proposed in the April 2015 pumps test procedure NOPR with no
modifications.
Twin Head Pumps
A twin head pump is a type of IL pump that contains two impeller
assemblies, mounted in two volutes that share a single inlet and
discharge in a common casing. In response to the April 2015 pumps test
procedure NOPR, DOE received comment from HI recommending that DOE
include twin head pumps in this rulemaking and align their test
procedure with Europump guidelines.\59\ (HI, No. 8 at p. 3) These
guidelines recommend testing a twin head pump by incorporating one
[[Page 4116]]
of the impeller assemblies into an adequate IL type pump casing.
---------------------------------------------------------------------------
\59\ Guideline on the application of COMMISSION REGULATION (EU)
No 547/2012 implementing Directive 2009/125/EC of the European
Parliament and of the Council with regard to ecodesign requirements
for water pumps (12th of September 2012)).
---------------------------------------------------------------------------
DOE agrees with HI's recommendation and, as discussed in section
III.A.2.a, originally intended to include these pumps as a category of
IL pumps. To clarify DOE's original intent in this final rule, DOE is
adopting a definition of twin head pump, specifying that twin head
pumps are a subset of the IL pump equipment category, and modifying the
test procedure in this final rule to be consistent with the EU
guidelines. DOE's definition for twin head pump and the modified IL
definition are presented in section III.A.2.a. However, DOE also
acknowledges that clarifications to the test procedure proposed in the
April 2015 pumps test procedure NOPR are necessary to explicitly
specify the procedures for testing twin head pumps in accordance with
the DOE test procedure. As such, DOE is establishing explicit
instructions for configuring twin head pumps in this final rule.
In general, twin head pumps, as a subset of IL pumps, are tested in
accordance with the test procedure for IL pumps. Specifically, twin
head pumps, which are essentially two IL pumps packaged together in a
single casing, are to be tested using an equivalent single-head IL
configuration. That is, to test a twin head pump, one of the two
impeller assemblies is to be incorporated into an adequate, IL style,
single impeller volute and casing. An adequate, IL style, single
impeller volute and casing means a volute and casing for which any
physical and functional characteristics that affect energy consumption
and energy efficiency are essentially identical to their corresponding
characteristics for a single impeller in the twin head pump volute and
casing.
d. Determination of Pump Shaft Input Power at Specified Flow Rates
HI 40.6-2014 provides a specific procedure for determining BEP for
a given pump based on seven load points at 40, 60, 75, 90, 100, 110 and
120 percent of the expected BEP flow of the pump. The test protocol in
section 40.6.6.2 of HI 40.6-2014 requires that the hydraulic power and
the pump shaft input power, or input power to the motor for pumps
tested using the testing-based methods, be measured at each of the
seven load points. HI 40.6-2014 further specifies that the pump
efficiency be determined as the hydraulic power divided by the shaft
input power, or as the hydraulic power divided by the product of the
measured input power to the motor and the known efficiency of a
calibrated motor, depending on how the pump is tested. The equations
for calculating pump efficiency are shown in equation (12):
[GRAPHIC] [TIFF OMITTED] TR25JA16.064
Where:
[eta]pump,i = pump efficiency at load point i (%);
Pu,i = pump hydraulic output power at load point i (hp);
Pi = pump shaft input power at load point i (hp);
Pi\in,m\ = measured driver power input to the calibrated
motor at load point i (hp);
[eta]motor,i = the calibrated motor efficiency \60\ at
load point i (%); and
---------------------------------------------------------------------------
\60\ Note: to determine pump shaft input power based on the
measured driver input power, a calibrated motor and the calibrated
motor efficiencies at each load point i must be used where they are
known with ``sufficient accuracy,'' meaning that the efficiency of
the motor combined with the power measurement device uncertainty
must not exceed 2.5 percent, as required by Table
40.6.3.2.3 in HI 40.6-2014.
---------------------------------------------------------------------------
i = load point corresponding to 40, 60, 75, 90, 100, 110 or 120
percent of expected BEP flow.
The pump efficiency at each of these load points is then used to
determine the tested BEP for a given pump and, in particular, the flow
rate associated with the BEP of the pump (i.e., BEP flow). Then, based
on the determined BEP flow, the pump shaft input power or input power
to the motor is determined at each of the specified load points, as
discussed in section III.B.
In the April 2015 pumps test procedure NOPR, DOE observed that the
specific load points measured in the test protocol may not be exactly
at 75, 100, or 110 percent of the BEP flow load points specified in the
test procedure and, thus, the relevant power input measurements--
specifically, pump shaft input power, input power to the pump at the
driver, or input power to the continuous or non-continuous controls--
must be adjusted to reflect the power input at the specific load points
specified in the test procedure. To adjust the measured power input
values, DOE proposed that the measured input power and flow data
corresponding to the load point from 60 percent of expected BEP flow to
120 percent of expected BEP flow be linearly regressed and the input
power at the specific load point of 75, 100, and 110 percent of BEP
flow be determined from that regression equation. 80 FR 17586, 17610-11
(April 1, 2015).
In response to the April 2015 pumps test procedure NOPR, HI
commented that it agrees with DOE's proposal to use a linear regression
of the pump input power with respect to flow rate at all the tested
load points greater than or equal to 60 percent of expected BEP flow to
determine the pump shaft input power at the specified load points of
75, 100, and 110 percent of BEP flow. (HI, No. 8 at p. 18) DOE received
no other comments on the proposal and, as such, is adopting it as
proposed in the April 2015 pump test procedure NOPR with no revisions
or modifications.
Determination of Pump Shaft Input Power for Pumps With BEP at the
Maximum Allowable Flow
HI 40.6-2014 contains a method for determining the BEP of tested
pumps based on the flow rate at which the maximum pump efficiency
occurs. DOE recognizes that there may be some unique pump models that
do not exhibit the typical parabolic relationship of pump efficiency to
flow rate. Instead, for some pumps, pump efficiency will continue to
increase as a function of flow until reaching the maximum allowable
flow that can be developed without damaging the pump, also referred to
as ``pump run-out.'' Similarly, the expected BEP of some pumps may be
only slightly below the maximum allowable flow. For such pumps, it may
not be possible to use the procedure described in HI 40.6-2014 to
determine the BEP, since the pump cannot safely operate at flows of 110
and/or 120 percent of the expected BEP of the pump. In such cases, DOE
proposed in the April 2015 pumps test procedure NOPR that the seven
flow points for determination of BEP should be 40, 50, 60, 70, 80, 90,
and 100 percent of the expected maximum allowable flow rate of the pump
instead of the seven flow points described in section 40.6.5.5.1 of HI
40.6-2014. In addition, in such cases, DOE proposed that the specified
constant load flow points should be 100, 90, and 65 percent
[[Page 4117]]
of the BEP flow rate. 80 FR 17586, 17611 (April 1, 2015).
In response, HI commented that it disagreed with this proposal
because in order to determine the location of the BEP, testing must
occur at rates of flow greater than 100 percent of expected BEP flow.
(HI, No. 8, p. 18) DOE notes that the proposal in the April 2015 pumps
test procedure NOPR is specified with respect to the expected maximum
allowable flow rate, or the expected BEP, of the pump, not the measured
BEP flow. That is, under the NOPR proposal, pumps with the expected BEP
occurring at the maximum allowable flow, as defined in ANSI/HI 1.1-1.2-
2014, would be tested at the alternative load points specified in test
procedure for pumps with BEP at run-out.
DOE acknowledges that pump manufacturers must have some knowledge
of the expected operational characteristics of their pump, including
the expected BEP and expected maximum allowable flow, in order to
determine the appropriate load points for determining BEP. However, DOE
notes that this is the case for all pumps, not just pumps with BEP at
run-out. That is, the specific load points used to determine BEP for
all pumps are specified with respect to the expected operating
characteristics of the pump (i.e., BEP flow rate, as specified in
section 40.6.5.5.1 of HI 40.6-2014, or maximum allowable flow for pumps
with BEP at run-out). DOE believes this is necessary since the BEP and
flow characteristics of different load points could vary widely and it
is important that the data captured during the test procedure
effectively and fully characterize the performance of the pump over the
pump's operating ranges. DOE also understands that significant design,
engineering, and modeling are involved with creating pump models for
specific applications and design parameters and, as such, DOE finds it
unlikely that the BEP of a pump will occur at or near a pump's maximum
allowable flow without the pump manufacturer having some expectation
that this will occur based on the inherent design characteristics of
the pump. As such, DOE believes that the proposed test procedure for
pumps with BEP at or near run-out is consistent with the HI 40.6-2014
industry test protocols and appropriate for determining the performance
of such pumps and no additional changes are necessary. DOE also notes
that the maximum efficiency point (or BEP), in the case of pumps with
BEP at the maximum allowable flow rate will occur at the maximum flow
rate tested and will not be a parabolic maxima, as is the case for most
pumps.
DOE notes that, in the April 2015 NOPR, DOE referred to pumps with
BEP at run-out as corresponding to those with their expected BEP at the
expected maximum allowable flow. DOE recognizes that pumps with their
maximum allowable flow occurring between 100 and 120 percent of BEP
flow would also not be able to be tested in accordance with the
proposed test procedure, as not all of the load points specified in the
procedure could be measured in accordance with the test procedure. As
such, DOE is adopting, in this final rule, the proposal described in
the April 2015 pumps test procedure NOPR, except that DOE is clarifying
that pumps with maximum allowable flow occurring between 100 and 120 of
BEP flow also qualify as pumps with BEP at run-out and must apply the
appropriate test procedure. To ensure that the DOE test procedure is
consistent and adequately captures the range of flow rates with which
the pump is expected to operate, DOE is maintaining in this final rule
that load points for determination of BEP are specified with respect to
the expected maximum allowable flow of the pump, for pumps with the
expected BEP within 20 percent of the expected maximum allowable flow.
In the final rule, DOE is also clarifying the specific load points that
must be used in determining pump or driver input power in accordance
with the procedure described in section III.C.2.d.
e. Measurement Equipment for Testing-Based Methods
In the April 2015 pumps test procedure NOPR, DOE noted that HI
40.6-2014 does not contain all the necessary methods and calculations
to determine pump power consumption for the range of equipment that
will be addressed by this final rule (i.e., pumps inclusive of motors
and continuous or non-continuous controls). For the purposes of
determining most quantities relevant to the determination of
PEICL or PEIVL for pumps rated using the
calculation-based methods, DOE proposed to incorporate by reference HI
40.6-2014, appendix C, which specifies the required instrumentation to
measure head, speed, flow rate, torque, temperature, and electrical
input power to the motor. However, DOE noted that, for the purposes of
measuring input power to the driver for pumps sold with a motor and
continuous or non-continuous controls rated using the testing-based
method, the equipment specified in section C.4.3.1, ``electric power
input to the motor,'' of HI 40.6-2014 may not be sufficient. Based on
the specifications in CSA C838-13 and AHRI 1210-2011, since these test
standards are the most relevant references for measuring input power to
such controls, DOE proposed that electrical measurements for
determining VSD efficiency be taken using equipment capable of
measuring current, voltage, and real power up to at least the 40th
harmonic of fundamental supply source frequency \61\ and have an
accuracy level of 0.2 percent of full scale when measured
at the fundamental supply source frequency. 80 FR 17586, 17611-12
(April 1, 2015).
---------------------------------------------------------------------------
\61\ CSA C838-13 requires measurement up to the 50th harmonic.
However, DOE believes that measurement up to the 40th harmonic is
sufficient, and the difference between the two types of frequency
measurement equipment will not be appreciable.
---------------------------------------------------------------------------
DOE requested comment on the type and accuracy of required
measurement equipment, especially the equipment required for electrical
power measurements for pumps sold with motors having continuous or non-
continuous controls. AHRI commented that AHRI 1210-2011 specifies
appropriate power supply tolerances so that both pump manufacturers and
DOE enforcement testing can be confident with the establishment and
verification of ratings of VFDs sold with pumps. (AHRI, No. 11 at pp.
1-2) AHRI also indicated that any harmonics in the power system can
affect the measured performance of the pump when tested with a motor or
motor and continuous or non-continuous control. In addition, AHRI
notified DOE that VFD manufacturers are working to expand the scope of
AHRI 1210-2011 to include a higher horsepower upper limit and to
include additional load points.
HI commented that it disagrees with the requirements in AHRI 1210-
2011 and CSA C838-13, asserting that they were not agreed to by the CIP
Working Group and would be excessively burdensome. (HI, No. 8 at pp.
18-19) HI also indicated that pump manufacturers do not have the same
equipment as motor and drive test laboratories and should not be
expected to have the same level of instrumentation. HI recommended that
DOE instead require the 2.0 percent maximum permissible
measurement device uncertainty specified in Table 40.6.3.2.3 of HI
40.6-2014 for driver input power.
In response to HI's concerns regarding the burden of such
additional instrumentation, DOE notes that, in the April 2015 pumps
test procedure NOPR proposal, such sophisticated electric measurement
equipment was only proposed to be required for the
[[Page 4118]]
measurement of input power to the continuous or non-continuous control
when rating the pump under the testing-based methods. For other pump
configurations and when testing a pump using the calculation-based
methods, the electrical measurement equipment specified in HI 40.6-2014
section C.4.3.1 of appendix C would apply. DOE also notes that several
interested parties, including HI, previously commented that such
measurement equipment was necessary due to the potential impact of the
continuous control on line harmonics and other equipment on the
circuit. (Docket No. EERE-2011-BT-STD-0031, CA IOUs, Framework public
meeting transcript No. 19 at p. 236; Docket No. EERE-2011-BT-STD-0031,
HI, No. 25 at p. 35) HI also previously noted that this additional
instrumentation is manageable and within the capabilities of what most
of the HI members are doing today. (Docket No. EERE-2011-BT-STD-0031;
HI, public meeting transcript, No. 19 at p. 235)
In addition, given the power conditioning requirements adopted in
section III.C.2.c, DOE believes that the more sophisticated electrical
measurement equipment capable of measuring true root mean square (RMS)
voltage, true RMS current, and real power for distorted waveforms is
required to ensure that the incoming power is within the specifications
for those pump configurations where it is required and that the power
measurement is accurate. Specifically, DOE is requiring, as discussed
at length in section III.C.2.c, certain voltage, frequency, voltage
unbalance, and voltage THD levels be maintained when testing: (1) Bare
pumps using a calibrated motor, (2) pumps sold with motors using the
testing-based methods, and (3) pumps sold with motors and continuous or
non-continuous controls using the testing-based method. In order to
verify that these requirements are met, measurement equipment must be
capable of accurately measuring real power, true RMS voltage,
frequency, voltage unbalance, and voltage THD. DOE notes that, in
section C.4.3, HI 40.6 specifies that driver input power to the motor
should be calculated as the product of (1) line volts, (2) line amps,
and (3) power factor. As HI 40.6-2014 specifies the measurement of
power factor, DOE believes that the electric equipment capable of
measuring at least real power, true RMS voltage, and true RMS current
is already required by HI 40.6-2014, as such measurements are necessary
for determining power factor.
Some watt meters and watt-hour meters would not be sufficient for
accurate measurement of real power for distorted voltage waveforms or
distorted current waveforms; this is because such instruments
incorrectly assume that the waveforms are perfectly sinusoidal (i.e.,
free of the harmonics that are introduced by non-linear loads).\62\ DOE
is therefore requiring the use of instruments that accurately measure
true RMS current, true RMS voltage, and real power for distorted
waveforms with harmonic frequencies ranging from the fundamental
frequency (60 Hz) up to and including the 40th harmonic (2400 Hz).
---------------------------------------------------------------------------
\62\ PG&E, ``Voltage and Current Measurement of Non-Sinusoidal
AC Power'' (October 2004, https://www.pge.com/includes/docs/pdfs/mybusiness/customerservice/energystatus/powerquality/nonsinusoidal_power.pdf, accessed September 8, 2015).
---------------------------------------------------------------------------
However, with respect to the required accuracy of any electrical
measurement equipment, DOE acknowledges the concern from HI regarding
the additional burden associated with acquiring instrumentation
consistent with the specifications provided in the NOPR. As such, DOE
reviewed available and applicable test methods for motors and controls,
including AHRI 1210-2011 and CSA C838-13. DOE notes that AHRI 1210-2011
in turn references IEC 61000-4-7, ``Testing and measurement
techniques--General guide on harmonics and interharmonics measurements
and instrumentation, for power supply systems and equipment connected
thereto,'' regarding the necessary characteristics for electric
measurement equipment. IEC 61000-4-7 provides requirements for Class I
instruments and recommends their use where precise measurements are
necessary, such as for verifying compliance with standards. The maximum
error on power for IEC Class I instruments is 1 percent of
measured value for readings greater than or equal to 150 W (0.2 hp).
However, IEC 61000-4-7 states that the error limits refer to single-
frequency (i.e., sinusoidal) steady-state waveforms, in the operating
frequency range, applied to the instrument under rated operating
conditions to be indicated by the manufacturer.
The requirements in IEC 61000-4-7 generally align with those in
section 5.7.3 of CSA C390-10, which specifies that motor input power
measurements shall have a maximum uncertainty of 1.0
percent of the reading (including all errors from the power meter,
current transformers, and potential/voltage transformers). However, CSA
also states that the specified uncertainties shall apply only at the
rated full load (i.e., near rated power factor) of the motor under
test. While both IEC 61000-4-7 and CSA C390-10 recommend instrument
tolerances of 1.0 percent, DOE notes that their application
of that tolerance is not the same as the tolerance DOE is adopting in
this final rule, which applies to the measured power at each test point
and with the power supply characteristics experienced during the test.
DOE recognizes that the accuracy of input power measurements can be
compromised to some extent when voltage and/or current waveforms are
displaced and/or distorted. In addition, DOE recognizes that motors
will not always be fully loaded during pump testing, that motors may be
operated somewhat above nameplate voltage (as allowed in this final
rule), and that some distortion of the voltage waveform is permitted in
this final rule. Therefore, DOE believes it is appropriate to allow
electrical equipment accuracy of 2.0 percent of measured
value, consistent with the tolerance specified in section 40.6.3.2.3 of
HI 40.6-2014 and HI's request. DOE is adopting such a requirement in
this final rule.
DOE also recognizes that current and voltage instrument
transformers can be used in conjunction with electrical measurement
equipment to measure current and voltage. Usage of instrument
transformers can introduce additional losses and errors to the
measurement system. DOE is clarifying in this final rule that the
combined accuracy of all instruments used to measure a parameter must
meet the prescribed accuracy requirements for electrical measurement
equipment. Section C.4.1 of AHRI 1210-2011 indicates that combined
accuracy should be calculated by multiplying the accuracies of
individual instruments. In contrast, section 5.7.2 of CSA C838-2013
indicates that if all components of the power measuring system cannot
be calibrated together as a system, the total error shall be calculated
from the square root of the sum of the squares of all the errors. DOE
understands that it is more accurate to combine independent accuracies
(i.e., uncertainties or errors) by summing them in quadrature.\63\ DOE
is therefore using the root sum of squares to calculate the combined
accuracy of multiple instruments used in a single measurement,
consistent with conventional error propagation methods.
---------------------------------------------------------------------------
\63\ National Institute of Standards and Technology (NIST)
Guidelines for Evaluating and Expressing the Uncertainty of NIST
Measurement Results (https://physics.nist.gov/Pubs/guidelines/sec5.html, accessed September 8, 2015).
---------------------------------------------------------------------------
Therefore, in this final rule, DOE is specifying the
characteristics of the
[[Page 4119]]
electrical measurement equipment that must be used when measuring input
power to the motor, continuous controls, or non-continuous controls.
Specifically, the electrical measurement equipment in such cases must
be capable of measuring true RMS current, true RMS voltage, and real
power up to at least the 40th harmonic of fundamental supply source
frequency and have an accuracy level of 2.0 percent of the
measured value when measured at the fundamental supply source
frequency. DOE notes that standard electrical measurement equipment
meeting the requirements of HI 40.6-2014 section C.4.3.1 may still be
used when testing any pumps under the calculation-based methods (i.e.,
bare pumps, pump sold with motors, and pumps sold with motors and
continuous or non-continuous controls), provided a calibrated motor is
not used to determine the pump shaft input power. The electrical
measurement equipment requirements being adopted in this pumps test
procedure final rule are summarized in Table III.5.
Table III.5--Electrical Measurement Requirements for Different
Configurations of Pumps for the Calculation Based and Testing Based
Approaches
------------------------------------------------------------------------
Electrical measurement requirements
-------------------------------------------
Testing-based test
Pump configuration Calculation-based method or
test method without Calculation-based
a calibrated motor test method with a
calibrated motor
------------------------------------------------------------------------
Bare Pump................... HI 40.6-2014, Not Applicable.
section C.4.3.1,
unless testing with
a calibrated motor.
Pump + Motor or Pump + Motor HI 40.6-2014, Equipment capable of
+ Continuous or Non- section C.4.3.1, measuring true RMS
Continuous Controls. unless testing with current, true RMS
a calibrated motor. voltage, and real
power up to at
least the 40th
harmonic of
fundamental supply
source frequency
and have an
accuracy level of
2.0
percent of the
measured value when
measured at the
fundamental supply
source frequency.
------------------------------------------------------------------------
While DOE acknowledges that these requirements may represent a
burden for some manufacturers and test labs who do not already have
such equipment, DOE has minimized the additional burden associated with
this requirement, to the extent possible, by only requiring more
sophisticated power measurement equipment in those cases where it is
necessary to verify that the test procedure power conditioning
requirements are being met. DOE also notes that, for many pumps, the
testing-based approaches are optional and a manufacturer could elect to
determine the PEI using the calculation-based approach and avoid having
to purchase and use the more accurate and expensive electrical
measurement equipment necessary for conducting testing under the
testing-based approach. The burden associated with this test procedure,
and in particular the required test equipment, is discussed further in
section IV.B.
f. Calculations and Rounding
DOE notes HI 40.6-2014 does not specify how to round values for
calculation and reporting purposes. DOE recognizes that the manner in
which values are rounded can affect the resulting PER or PEI, and all
PER or PEI values should be reported with the same number of
significant digits. In the April 2015 pumps test procedure NOPR, DOE
proposed to require that all calculations be performed with the raw
measured data, to ensure accuracy, and that the PERCL and
PEICL or PERVL and PEIVL be reported
to the nearest 0.01. 80 FR 17586, 17612 (April 1, 2015).
DOE requested comment on its proposal to conduct all calculations
using raw measured values and that the PERCL and
PEICL or PERVL and PEIVL, as
applicable, be reported to the nearest 0.01. In response, HI commented
that it understands and agrees that the requirement is to normalize raw
data to nominal speed, and the PERCL, PEICL,
PERVL and PEIVL would be reported to the nearest
0.01. (HI, No. 8 at p. 19) In the April 2015 NOPR public meeting, a
representative of HI (Paul Ruzicka) suggested that DOE clarify that
calculations be performed with ``raw normalized data,'' since all data
are to be corrected to nominal speed. (HI, NOPR public meeting
transcript, No. 7 at pp. 165-66)
DOE appreciates HI's confirmation of the proposed approach. In
response to HI's suggestion that DOE clarify that all calculations are
to be performed with ``raw normalized data,'' DOE notes that the
normalization to nominal speed is also a calculation and that such
calculation is also to be performed with raw measured data. Also, some
collected data do not need to be normalized to nominal speed. As such,
DOE finds it clearer to continue to specify that all calculations be
performed with raw measured data, including the normalization to
nominal speed.
In addition, in preparing the final rule test procedure provisions,
DOE reviewed the calculations, uncertainty, and significance of
measured values used to determine the PERCL and
PEICL or PERVL and PEIVL, as
applicable. Based on this analysis, DOE determined that while
PEICL and PEIVL are to be reported to 0.01, the
precision of the measurement equipment specified in the NOPR is not
sufficient to determine PERCL and PERVL to 0.01,
especially for large pumps. As such, in this final rule, DOE is
continuing to specify that all calculations be performed with the raw
measured data, to ensure accuracy, and that the PEICL and
PEIVL be reported to the nearest 0.01. However, DOE is
specifying, in this final rule, that PERCL and
PERVL need only be specified to three significant digits,
which is equivalent to or better than the level of significance
specified for PEICL and PEIVL. DOE also agrees
with HI that all data should be corrected to nominal speed prior to
performing subsequent calculations, as described in section III.C.2.c.
D. Determination of Motor Efficiency
The PEICL and PEIVL metrics both describe the
performance of a pump and an accompanying motor, including continuous
or non-continuous controls, if applicable. As such, the performance of
the applicable motor must be determined to calculate the
PEICL or PEIVL of a given pump model.
[[Page 4120]]
In the April 2015 pumps test procedure NOPR, DOE proposed that the
motor efficiency would be determined based on the configuration in
which the pump was sold. For determining the default motor efficiency
of a minimally compliant pump (PERSTD) and for determining
the default motor efficiency used to calculate PERCL for
bare pumps, DOE proposed to specify the nominal full load motor
efficiency that corresponds to the applicable Federal minimum standard.
For determining PERCL or PERVL for pumps sold
with motors or with motors and continuous or non-continuous controls,
DOE proposed to use either (1) the physically tested performance of the
motor paired with that pump when using testing-based methods, or (2)
the represented nominal full load motor efficiency (i.e., the nameplate
and certified rating) of the motor (other than submersible) distributed
in commerce with that pump model when using the calculation-based test
method. 80 FR 17586, 17612-13 (April 1, 2015). The specific procedures
for determining the applicable Federal minimum and represented nominal
full load motor efficiency values are described in section III.D.1 and
III.D.2, respectively.
Based on DOE's proposed test procedure, the applicable Federal
minimum or the represented nominal full load motor efficiency would
then be used to determine the full load losses, in horsepower,
associated with that motor. The full load losses would then be adjusted
using an algorithm to reflect the motor performance at partial loads,
corresponding to the load points specified in the DOE test. These
losses would then be combined with the measured pump shaft input power
at each load point to determine the PERCL or
PERVL for that pump, as described in section III.B. Id.
Section III.E.1 describes how the Federal minimum or represented
nominal full load motor efficiency is used in the calculation-based
method when calculating overall pump power consumption.
1. Default Nominal Full Load Motor Efficiency
For determining the default motor efficiency of a minimally
compliant pump (PERSTD) and for determining the default
motor efficiency used to calculate PERCL for bare pumps, DOE
proposed to specify the nominal full load motor efficiency that
corresponds to the applicable Federal minimum standard. In the April
2015 pumps test procedure NOPR, DOE proposed that the ``default''
nominal full load motor efficiency values be based on the minimum
nominal full load motor efficiency standards for polyphase, NEMA Design
B motors from 1 to 500 hp, defined in 10 CFR part 431, subpart B for
medium and large electric motors, except for submersible motors.
Specifically, at the time of the proposal, the values in Table 5 of 10
CFR 431.25(h) defined the nominal full load motor efficiency standards,
by number of poles and horsepower for the applicable motors. 80 FR
17586, 17612-13 (April 1, 2015). DOE is using the term ``default
nominal full load efficiency'' throughout this document to refer to the
default values used in this test procedure for determining
PERSTD and for bare pumps, PERCL corresponding to
the applicable Federal minimum energy conservation standards. See
section III.D.1.a for a discussion regarding electric motors covered by
DOE's energy conservation standards at 10 CFR 431.25 and section
III.D.1.b for a discussion regarding submersible motors.
a. Covered Electric Motors
For the determination of PERSTD for all pumps (except ST
pumps) and PERCL for bare pumps (see section III.E.1.a),
default nominal full load motor efficiency values are required. As
mentioned previously, DOE believes the nominal full load motor
efficiency standards specified for NEMA Design B motors are appropriate
for the pumps (except ST pumps) to which this test procedure is
applicable. In the April 2015 pumps test procedure NOPR, DOE also
proposed to specify the selection of the default motor characteristics
used for calculating PERCL and PERSTD based on
the configuration in which the pump is being sold. Specifically, for
bare pumps, DOE proposed that the default nominal full load motor
efficiency for determining PERCL and PERSTD would
be based on the following criteria:
The number of poles selected for the default motor would
be equivalent to the nominal speed of the rated pump (i.e., 2 poles
correspond to 3,600 rpm and 4 poles correspond to 1,800 rpm);
the motor horsepower selected for a given pump would be
required to be either equivalent to, or the next highest horsepower-
rated level greater than, the measured pump shaft input power at 120
percent of BEP flow, as determined based on an extrapolation of the
linear regression of pump input power (discussed in section III.C.2.d);
and
the lower standard (i.e., less stringent) of either the
open or enclosed construction at the appropriate motor horsepower and
number of poles. 80 FR 17586, 17612-13 (April 1, 2015).
As mentioned previously, the appropriate table at 10 CFR 431.25 is
the table of nominal full load motor efficiency standards that is
currently required for compliance of NEMA Design B polyphase motors.
For pumps sold either with motors or with motors and continuous or
non-continuous controls, selection of a default nominal full load motor
efficiency for calculation of PERSTD is also required. This
default nominal full load motor efficiency is also based on the
applicable Federal minimum standards. In this case, DOE proposed that
the motor horsepower and number of poles selected for determining the
default nominal full load motor efficiency for use in the calculation
of PERSTD should be equivalent to the horsepower and poles
of the motor with which the pump model is distributed in commerce.
Similar to the case for bare pumps, DOE also proposed that the default
nominal full load motor efficiency corresponding to the minimally
compliant motor in PERSTD would still be the minimum of the
open and enclosed standards for the appropriate motor horsepower and
number of poles. That is, regardless of the motor construction (i.e.,
open or enclosed) of the motor with which the pump is being rated, the
minimum nominal full load motor efficiency standard listed in the
applicable table for polyphase NEMA Design B motors at 10 CFR 431.25
for the given motor horsepower and number of poles would be used. Id.
DOE requested comment on its proposal to determine the default
motor horsepower for rating bare pumps based on the pump shaft input
power at 120 percent of BEP flow and, in response, HI commented that it
agrees with this proposal. (HI, No. 8 at p. 19) DOE also requested
comment on its proposal to specify the default nominal full load motor
efficiency based on the applicable minimally allowed nominal full load
motor efficiency specified in DOE's energy conservation standards for
NEMA Design B motors at 10 CFR 431.25 for all pumps except pumps sold
with submersible motors. HI commented that each NEMA MG 1 nominal
efficiency value is the average efficiency of a large population of
motors of the same design, so for any given nominal efficiency value,
half of the corresponding population would be lower. (HI, No. 8 at p.
19) HI indicated that the NEMA MG 1 minimum efficiency values should be
used instead so that the test method for determining PEICL
and PEIVL are not disadvantaged. Wilo similarly commented
that the use of NEMA nominal efficiencies would cause 50 percent of
borderline pumps to
[[Page 4121]]
fail. (Wilo, Docket No. EERE-2011-BT-STD-0031, No. 44 at p. 2)
DOE acknowledges the comments from HI and Wilo regarding the use of
nominal full load motor efficiency values from 10 CFR 431.25. DOE notes
that these values represent the minimum Federal efficiency standard for
applicable covered motors and, as such, believes that referencing an
alternative, lower efficiency value would be inappropriate and
inconsistent with DOE's regulatory framework. However, in response to
the specific concern voiced regarding a potential disadvantage when
using the testing-based method, DOE will follow the method the
manufacturer used to determine the representative value when conducting
enforcement testing. In other words, if a pump manufacturer has used
the calculation-based rating method to determine the representative
value for a pump basic model, then DOE would also use the calculation-
based approach, which relies on the nominal full load motor efficiency
values from the table and not the actual motor tested performance.
Conversely, if a manufacturer elected to use the testing-based
approach, DOE would also assess compliance using the testing-based
approach which would account for the actual tested efficiency of the
motor incorporated into the pump. Thus, a manufacturer need not be
concerned that the actual efficiency of an individual motor would have
a disparate effect on the measured efficiency during assessment or
enforcement testing.
In this final rule, DOE is adopting the default nominal full load
motor efficiency values for bare pumps and the method for determining
PERSTD proposed in the April 2015 pumps test procedure NOPR.
That is, the default nominal full load motor efficiency for bare pumps
and for determining PERSTD for all pumps (besides VTS pumps)
is determined by referencing the applicable energy conservation
standards found at 10 CFR 431.25 for NEMA Design B motors that are
required at the time the pump model is being certified. At the time of
publication of this document, the appropriate motor Federal energy
conservation standards for NEMA Design B polyphase motors can be found
at 10 CFR 431.25(h).
DOE notes that, if DOE were to amend the energy conservation
standards for NEMA Design B polyphase motors, the represented values
for pump PEI would no longer remain valid, and manufacturers would need
to revise their represented values to reflect the amended nominal full
load motor efficiency standards and recertify at the first annual
certification date after the compliance date for the amended motor
Federal energy conservation standards. As a result of the methodology
being adopted today, which will result in changes to represented values
for pumps when the Federal energy conservation standards for NEMA
Design B polyphase motors changes, DOE does not believe that any actual
design or manufacturing changes will be required from the pump
manufacturer since the bare pump will remain the same and is unaffected
by the motor standard. Instead, DOE is ensuring that pump ratings still
reflect differential representations depending on the efficiency of the
motor that is being sold with the pump. DOE understands that certain
motors that were minimally compliant with the previous motor standard
may no longer be able to be sold once manufacturers are required to
comply with amended standards for motors (if adopted) and thus, DOE
believes a methodology which reflects this reality is best. Because the
PEI is an indexed value that is meant to compare the performance of the
pump being tested to that of a theoretical ``minimally-compliant''
pump, the default nominal full load motor efficiency for that
``minimally-compliant pump'' must reflect any changes in the motor
standard and available products in the market. If DOE did not adopt a
methodology that acknowledges potential changes to the energy
conservation standards for NEMA Design B motors, then pump represented
values could be artificially inflated when compliance with amended
energy conservation standards for motors is required and could result
in a situation where a compliant pump could be less efficient due to
the credit being given from the amended energy conservation standards
for motors.
For these reasons, DOE is specifying in the pumps test procedure
adopted in this final rule that when determining PERSTD for
all pumps (except VTS pumps) and PERCL for bare pumps, the
default nominal full load motor efficiency value that is used must be
the energy conservation standard for NEMA Design B polyphase motors
that is required at the time the pump model is being certified and must
be updated with an annual certification. As this amended default
nominal full load motor efficiency will occur in both the numerator and
the denominator of the PEI metric, such a test procedure provision will
not lead to changes in the relative ratings of bare pump models using
the calculation-based approach.
b. Submersible Motors
DOE notes that submersible motors are not currently subject to the
DOE energy conservation standards for electric motors specified at 10
CFR 431.25. Therefore, for the purposes of calculating PEICL
for bare VTS pumps or PERSTD for any pumps sold with
submersible motors, DOE requires a default assumption regarding full
load efficiency for submersible motors. In the April 2015 pumps test
procedure NOPR, DOE constructed a table of motor full load efficiencies
by motor horsepower, similar to the table of energy conservation
standards for electric motors at 10 CFR 431.25(h), as shown in Table
III.6. 80 FR 17586, 17614-15 (April 1, 2015).
As it was not DOE's intent to impact the rated efficiency of
submersible motors through this rulemaking, DOE deflated the minimum
submersible motor efficiency that DOE observed by using the maximum
number of ``bands'' across a horsepower range to ensure that the value
represented a worst-case value. Where no data were available, DOE
applied the same number of NEMA bands across the range of motor
horsepower and numbers of poles.
Table III.6--Two-Pole Motor Submersible Motor Full Load Efficiency by Motor Horsepower Relative to the Full Load
Efficiency in in Table 5 of 10 CFR 431.25(h)
----------------------------------------------------------------------------------------------------------------
Observed number Default number
Minimum observed of ``bands'' of ``bands''
full load below the full below the full
Motor horsepower (hp) efficiency (2- load efficiency load efficiency
poles) (%) in Table 5 of 10 in Table 5 of 10
CFR 431.25(h) CFR 431.25(h)
----------------------------------------------------------------------------------------------------------------
1...................................................... 67 6 11
1.5.................................................... 67 11 .................
[[Page 4122]]
2...................................................... 73 9 .................
3...................................................... 75 9 .................
5...................................................... 76 10 .................
7.5.................................................... 77 10 15
10..................................................... 75 13 .................
15..................................................... 72.2 15 .................
20..................................................... 76.4 13 .................
25..................................................... 79 12 .................
30..................................................... 79.9 12 12
40..................................................... 83 10 .................
50..................................................... 83 11 .................
60..................................................... 84 11 .................
75..................................................... 83.8 12 .................
100.................................................... 87 10 14
125.................................................... 86 13 .................
150.................................................... 86 13 .................
175.................................................... 88 12 .................
200.................................................... 87 14 .................
250.................................................... 87 14 .................
----------------------------------------------------------------------------------------------------------------
Id.
In response to the April 2015 pumps test procedure NOPR proposal,
HI commented in the public meeting that several of the minimum motor
efficiency values are higher than what is being published. (HI, NOPR
public meeting transcript, No. 7 at pp. 159-60). In written comments,
HI provided corrected efficiencies for several values. (HI, No. 8 at
pp. 19-20)
DOE thanks HI for submitting data to assist in constructing a
submersible motor efficiency table that is representative of minimally
efficient submersible motors. DOE has revised its proposed submersible
efficiency values to accommodate the lower values provided by HI, as
shown in Table III.7.
Table III.7--Revised Submersible Motor Full Load Efficiency by Motor Horsepower
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Minimum observed full load Observed number of ``bands'' Binned number of ``bands'' Resulting default nominal full
efficiency (%) below the full load efficiency below the full load efficiency load submersible motor
-------------------------------- in Table 5 of 10 CFR 431.25(h) for NEMA design B motors in efficiency
Motor horsepower (hp) -------------------------------- CFR 431.25 -------------------------------
2 poles 4 poles --------------------------------
2 poles 4 poles 2 poles 4 poles 2 poles 4 poles
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
1............................................................... 67 .............. 6 .............. 11 11 55 68
1.5............................................................. 67 .............. 11 .............. .............. .............. 66 70
2............................................................... 73 .............. 9 .............. .............. .............. 68 70
3............................................................... 75 .............. 9 .............. .............. .............. 70 75.5
5............................................................... 76 .............. 10 .............. .............. .............. 74 75.5
7.5............................................................. 77 .............. 10 .............. 15 15 68 74
10.............................................................. 75 .............. 13 .............. .............. .............. 70 74
15.............................................................. 72.2 .............. 15 .............. .............. .............. 72 75.5
20.............................................................. 76.4 .............. 13 .............. .............. .............. 72 77
25.............................................................. 79 .............. 12 .............. .............. .............. 74 78.5
30.............................................................. 79.9 81.8 12 13 13 14 77 80
40.............................................................. 83 .............. 10 .............. .............. .............. 78.5 81.5
50.............................................................. 83 85.1 11 13 .............. .............. 80 82.5
60.............................................................. 82.4 85.4 13 14 .............. .............. 81.5 84
75.............................................................. 83.8 86.2 12 14 .............. .............. 81.5 85.5
100............................................................. 87 .............. 10 .............. 14 15 81.5 84
125............................................................. 86 .............. 13 .............. .............. .............. 84 84
150............................................................. 86 86.1 13 .............. .............. .............. 84 85.5
200............................................................. 87 .............. 13 15 .............. .............. 85.5 86.5
250............................................................. 87 .............. 14 .............. .............. .............. 86.5 86.5
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
During the April 2015 NOPR public meeting, Nidec Corporation
(Nidec) expressed that the levels of submersible motors should be
consistent with the requirements for vertical motors. Nidec also stated
that there be two sets of default efficiency values: one for a dry
rotor and one for a wet rotor. (Nidec, NOPR public meeting transcript,
No. 7 at pp. 160-61) Nidec added that the type with air could use Table
12-12 from NEMA MG 1. (Nidec, NOPR public meeting transcript, No. 7 at
p. 163)
In response to Nidec's comment, DOE notes that all equipment
categories that are subject to the test procedure, including VTS pumps
that are most commonly paired with submersible motors, are defined as
dry rotor pumps. As such, wet rotor submersible motors
[[Page 4123]]
and wet rotor submersible pumps are not subject to the test procedure,
and a table of minimum efficiency values for them is not necessary. DOE
notes that, in response to Nidec's comment regarding ``the type [of
motor] with air,'' DOE believes Nidec is referring to non-hermitically
sealed units (i.e., non-submersible motors) and confirming that Table
12-12 in NEMA MG-1 (which is consistent with DOE's minimum efficiency
standards for electric motors at 10 CFR 431.25) is appropriate for such
non-submersible motors. While DOE's application of the minimum
efficiency standards for electric motors in this final rule is limited
to NEMA Design B motors, DOE notes that NEMA's comment is consistent
with the approach being taken in this final rule.
HI stated that DOE needs to emphasize that single-phase motors are
not part of the minimum efficiency tables. (HI, No. 8 at pp. 19-21) DOE
notes that in this test procedure, as described in section III.A.6, all
pumps sold with single-phase motors, including single-phase submersible
motors, may be rated as bare pumps in order to not be penalized for the
inherently lower efficiencies of single-phase equipment. In the bare
pump approach, the default submersible motor efficiency values
presented in Table III.7 are used in calculating both the numerator
(PERCL or PERVL) and denominator
(PERSTD) of PEI; the lower efficiency of a single-phase
motor is not taken into account. DOE notes that, as described in
section III.A.6, pumps sold with single-phase submersible motors may
also apply the testing-based approach, if desired by the manufacturer.
However, in such a case, the default motor efficiency used to determine
PERSTD would continue to be the default nominal submersible
motor efficiency presented in Table III.7.
In regard to selection of default motor size for submersible
motors, in the April 2015 pumps test procedure NOPR, DOE proposed to
apply the same sizing method proposed for other categories of pumps,
described in section III.D.1 of this NOPR. At the April 2015 NOPR
public meeting, HI stated that submersible motors are sold utilizing
full NEMA motor service factors and recommended amending the
submersible motor sizing to account for this sizing approach. (HI, NOPR
public meeting transcript, No. 7 at p. 150) In its written comments, HI
noted that DOE needs to emphasize that submersible pumps are typically
loaded to the fully utilized service factor of the motor. (HI, No. 8 at
pp. 19-20)
In response to HI's suggestion, DOE has reviewed the typical
service factors of submersible motors offered for sale with pumps
within the scope of this test procedure. DOE determined that the
majority of submersible motors exhibited service factors of 1.15. DOE
notes that this value is also consistent with the service factor
prescribed in table 12-4 of NEMA MG-1 2009 for Design A, B, and C
polyphase, squirrel cage, general-purpose, alternating-current motors
of the open type with a motor horsepower greater than 1 hp. In light of
this, DOE is revising its requirements for the default motor sizing of
submersible motors in this final rule to reflect the service factors
observed in the industry. That is, DOE is specifying that, for VTS bare
pumps, the default submersible motor horsepower be determined as the
motor horsepower that is equal to or the next highest motor horsepower
greater than the pump shaft input power (in horsepower) at 120 percent
of BEP flow divided by the service factor, or 1.15. DOE notes that some
motors less than 3 horsepower may have a higher service factor, but by
using the same value for all pumps, DOE is simplifying the procedure
and does not expect this simplification to significantly impact the PEI
for VTS bare pumps. This is because the same service factor (1.15) is
used for the given pump's PERCL and for PERSTD,
so the two efficiency values essentially cancel out and do not
significantly impact the rating.
DOE reiterates that this default service factor is only necessary
for determining the default motor efficiency for submersible motors.
For pumps sold with submersible motors and pumps sold with submersible
motors and continuous or non-continuous controls, the actual
submersible motor size with which the pump is distributed in commerce
is used when determining motor efficiency for use in calculating
PERCL, PERVL, and PERSTD.
In summary, in this final rule, DOE will allow the use of default
nominal full load submersible motor efficiency values presented in
Table III.7 to rate (1) VTS bare pumps, (2) pumps sold with submersible
motors, and (3) pumps sold with submersible motors and continuous or
non-continuous controls as an option instead of using the testing-based
approach. DOE believes that allowing the calculation-based method to be
used for pumps sold with submersible motors may also reduce the testing
burden for some manufacturers. However, if manufacturers wish to
account for the use of submersible motors with a higher efficiency than
the default nominal full load submersible motor efficiency, they may
choose to rate the pump model using the testing-based, wire-to-water
method described in section III.E.2.
2. Represented Nominal Full Load Motor Efficiency for Pumps Sold With
Motors
For pumps sold with motors or motors and continuous or non-
continuous controls that are rated using the calculation-based
approach, DOE proposed in the April 2015 pumps test procedure NOPR that
the nominal full load motor efficiency used in determining the
PERCL or PERVL will be the value that is
certified to DOE as the nominal full load motor efficiency in
accordance with the standards and test procedures for electric motors
at 10 CFR 431, subpart B. 80 FR 17586, 17613-14 (April 1, 2015). As
noted in the April 2015 pumps test procedure NOPR and described in
greater detail in section III.E.1.b and III.E.2, this verifiable and
standardized represented nominal full load motor efficiency is only
available for motors that are subject to DOE's test procedure for
electric motors and, as such, DOE proposed in the April 2015 pump test
procedure NOPR, that only pumps sold with motors subject to DOE's
electric motor test procedure and energy conservation standards would
be able to conduct the proposed calculation-based approach. Id. at
17618, 17626-28. DOE notes that these represented nominal full load
efficiency values correspond to the certified value submitted on the
motor manufacturer's certification report and on the nameplate of the
motor itself. Therefore, if the motor manufacturer elects to certify
conservatively at the Federal energy conservation standard level, this
is the value the pump manufacturer must use in its calculations for
pumps sold with motors subject to DOE's Federal energy conservation
standards.
For pumps sold with submersible motors and rated using the
calculation-based approach, DOE also proposed that the nominal full
load motor efficiency values would be the same as the default nominal
full load submersible motor efficiency values used to determine the
PERCL for bare pumps and PERSTD. Id. at 17614.
These values are representative of minimally efficient submersible
motors and are discussed further in section III.D.1.b. As noted
previously, if manufacturers wish to represent the efficiency of pumps
sold with submersible motors that are more efficient than the assumed
value, then they may perform the testing-based method described in
section III.E.2.b in section.
[[Page 4124]]
DOE received no comments on these proposals and is adopting the
provisions for specifying the represented nominal full load motor
efficiency for motors subject to DOE's electric motor test procedure
and the default nominal full load submersible motor efficiency for
submersible motors, as proposed. DOE notes that, for pumps sold with
motors not addressed by DOE's electric motor test procedure (except
submersible motors), the calculation-based methods described in section
III.E.1.b would not apply, and no assumption regarding nominal
efficiency of the motor paired with the pump is permitted when
determining PERCL or PERVL. However, an
assumption regarding the default efficiency of the minimally compliant
motor that can be paired with a given pump would still be required to
calculate PERSTD. See Section III.D.1; 80 FR 17586, 17613-14
(April 1, 2015).
3. Determining Part Load Motor Losses
As described in section III.B.2, default nominal full load motor
efficiency is converted to motor losses, in horsepower, at each load
point to determine the input power to the motor when determining
PERSTD. This same approach is used to determine
PERCL under the calculation-based approach, which is
described in greater detail in section III.E.2.b. In the April 2015
pumps test procedure NOPR, DOE proposed to determine the part load
losses of the motor at each load point by applying an algorithm to the
full load losses of the motor. 80 FR 17615. Specifically, DOE proposed
to determine a part load loss factor (yi) at each load point
based on the following equation (13):
[GRAPHIC] [TIFF OMITTED] TR25JA16.010
Where:
yi = the part load loss factor at load point i,
Pi = the shaft input power to the bare pump at load point
i (hp),
MotorHP = the motor horsepower (hp), and
i = load point corresponding to 75, 100, or 110 percent of BEP flow
for uncontrolled pumps or 25, 50, 75, or 100 percent of BEP flow for
pumps sold with a motor and continuous or non-continuous controls.
Id.
In the proposal, the full load losses of the motor would be
determined based on the full load motor efficiency, which would be the
default nominal full load motor efficiency described in section III.D.1
for bare pumps and when determining PERSTD, or the
represented nominal full load motor efficiency described in section
III.D.2 for pumps sold with applicable motors. Specifically, DOE
proposed that the full load motor losses would be calculated as shown
in equation (14):
[GRAPHIC] [TIFF OMITTED] TR25JA16.011
Where:
Lfull\64\ = motor losses at full load (hp),
---------------------------------------------------------------------------
\64\ DOE notes that, in the April 2015 pumps test procedure
NOPR, DOE proposed to define this term using the nomenclature
Lfull,default and described it as equivalent to ``default
motor losses at full load.'' However, upon further review, DOE finds
this terminology confusing because this equation applies both to
pumps rated as bare pumps, for which a default nominal full load
motor efficiency applies, as well as pumps rated with motors and
pumps rated with motors and controls, for with the nominal full load
motor efficiency with which the pump is rated applies (not a default
value), depending on the context. Therefore, in this final rule, DOE
is updating the terminology to use the nomenclature Lfull
and describe the term as equivalent to ``motor losses at full
load,'' referencing the relevant procedure for determining full load
motor losses based on the pump configuration.
---------------------------------------------------------------------------
MotorHP = the motor horsepower (hp), and
[eta]motor,full = the default or rated nominal full load
motor efficiency as determined in accordance with section III.D.1 or
III.D.2, respectively (%).
Id.
Finally, DOE proposed that the part load losses at each specified
load point would be determined based on the product of the full load
losses and the part load loss factor at that load point, as shown in
equation (15):
[GRAPHIC] [TIFF OMITTED] TR25JA16.012
Where:
Li = motor losses at load point i (hp),
Lfull = motor losses at full load (hp),
yi = part load loss factor at load point i, and
i = load point corresponding to 75, 100, or 110 percent of BEP flow
for uncontrolled pumps or 25, 50, 75, or 100 percent of BEP flow for
pumps sold with a motor and continuous or non-continuous controls.
These calculated part load motor losses at each of the specified
load points would then be combined with the measured pump shaft input
power and weighted equally to calculate PERCL or
PERVL via the calculation-based approach and
PERSTD, as described in section III.E.1.b and III.B.2,
respectively. Id. at 17615-16.
DOE requested comment on the development and use of the motor part
load loss factor curves to describe part load performance of covered
motors and submersible motors, including the default motor specified in
section III.D.1 for bare pumps and calculation of PERSTD.
DOE received no comments on the proposal and, as such, is adopting the
proposed methodology presented in the April 2015 pumps test procedure
NOPR with no modification for pumps, except those sold with submersible
motors. DOE notes that, in making the change requested by interested
parties to account for service factor in sizing submersible motors (see
section III.D.1.b), DOE is making a slight modification to the part
load loss factors for VTS pumps to specify that where
[GRAPHIC] [TIFF OMITTED] TR25JA16.013
a value of 1.000 should be used as the part load loss factor.
This change is needed because the proposed part load loss curves
were not developed to be representative of
[[Page 4125]]
performance above the full load of the motor. This modification
implicitly assumes that the motor efficiency curve is flat between full
load and the service factor (i.e., 1.15). DOE expects the full load
losses of the motor to be more representative of the performance of
motors beyond full load operation than extending the curve, which would
assume that losses would decrease (efficiency would increase) above
full load. DOE has not made any other revisions to the part load loss
factors. DOE also notes that such is the case for all pumps; that is,
the ratio of pump shaft input power to motor horsepower should not
exceed a value of 1 for any pump. As such, to ensure that the part load
loss factor equation is not applied inappropriately, DOE is adding this
clarification as applicable to all pumps tested under the test
procedure.
E. Test Methods for Different Pump Configurations
As previously discussed, the PEICL and PEIVL
for a given pump is determined by first calculating the
PERCL or PERVL, as applicable, for the given
pump. For all pumps, the PERCL or PERVL is then
scaled based on a calculated PERSTD (i.e., the
PERCL of a pump that would minimally comply with the
applicable standard). (Docket No. EERE-2011-BT-STD-0031) The process
for determining the PERSTD is described in section III.B.2.
In the April 2015 pumps test procedure NOPR, DOE proposed that
different test methods for determining the PERCL and
PERVL of applicable pumps would apply based on the
configuration of the pump model and the characteristics of the motor
and controls it may be sold with. 80 FR 17586, 17616 (April 1, 2015).
For example, the available test method(s) for pumps sold alone (i.e.,
bare pumps) would be different than those for pumps sold with motors or
pumps sold with motors and continuous or non-continuous controls.
Further, the available test methods for pumps sold with motors that are
covered by DOE's energy conservation standards for electric motors at
10 CFR 431.25(g) (as established by the energy conservation standards
established in the May 2014 medium electric motor energy conservation
standard final rule (79 FR 30933 (May 29, 2014)) \65\ would be
different than the available test methods for pumps sold with motors
that are not covered by DOE's test procedure for electric motors.
Specifically, DOE proposed defining the applicability of the proposed
test methods based on the following:
---------------------------------------------------------------------------
\65\ DOE recognizes that the scope of the electric motor
standards at 10 CFR 431.25 may change in the future as a result of
potential future rulemakings. Since the scope of such future motors
standards is unknown, DOE wishes to clearly and unambiguously
establish the specific motors which, when sold with an applicable
bare pump, would be eligible to apply the calculation-based test
methods described in this section.
---------------------------------------------------------------------------
Two potential approaches: (1) Testing-based versus (2)
calculation-based;
three potential configurations: (1) Bare pumps, (2) pumps
sold with motors, and (3) pumps sold with motors and controls; and
two different sub-configuration criteria:
(1) Whether the pump was sold with: (a) a motor covered by DOE's
electric motor energy conservation standards, (b) a submersible motor,
(c) a motor that is not covered by DOE's electric motor energy
conservation standards and is not a submersible motor, or (d) no motor;
and
(2) whether the pump was sold with: (a) continuous controls, (b)
non-continuous controls, or (c) neither continuous or non-continuous
controls.
The applicability of DOE's proposed test methods to different
configurations of pumps is summarized in Table III.8. Id. at 17627.
Table III.8--Applicability of Calculation-Based and Testing-Based Test Procedure Options Based on Pump
Configuration
----------------------------------------------------------------------------------------------------------------
Calculation-based test Testing-based test
Pump configuration Pump sub-configuration method method
----------------------------------------------------------------------------------------------------------------
Bare Pump......................... Bare Pump................. A.1: Tested Pump Not Applicable.
Efficiency of Bare Pump +
Default Nominal Full Load
Motor Efficiency +
Default Motor Part Load
Loss Curve.
Pump + Motor...................... Pump + Motor Covered by B.1: Tested Pump B.2: Tested Wire-to-
DOE's Electric Motor Efficiency of Bare Pump + Water Performance.
Energy Conservation Represented Nominal Full
Standards OR Pump + Load Motor Efficiency for
Submersible Motor. Actual Motor Paired with
Pump + Default Motor Part
Load Loss Curve.
Pump + Motor Not Covered Not Applicable............ B.2: Tested Wire-to-
by DOE's Electric Motor Water Performance.
Energy Conservation
Standards (Except
Submersible Motors).
Pump + Motor + Speed Controls..... Pump + Motor Covered by C.1: Tested Pump C.2: Tested Wire-to-
DOE's Electric Motor Efficiency of Bare Pump + Water Performance.
Energy Conservation Represented Nominal Full
Standards + Continuous Load Motor Efficiency for
Control OR Pump + Actual Motor Paired with
Submersible Motor + Pump + Default Motor/
Continuous Control. Control Part Load Loss
Curve + Assumed System
Curve.
Pump + Motor Covered by Not Applicable............ C.2: Tested Wire-to-
DOE's Electric Motor Water Performance.
Energy Conservation
Standards + Non-
Continuous Control OR
Pump + Submersible Motor
+ Non-Continuous Control.
Pump + Motor Not Covered Not Applicable............ C.2: Tested Wire-to-
by DOE's Electric Motor Water Performance.
Energy Conservation
Standards (Except
Submersible Motors) +
Continuous or Non-
Continuous Controls.
----------------------------------------------------------------------------------------------------------------
[[Page 4126]]
DOE's proposed applicability of testing-based and calculation-based
test methods, as shown in Table III.8, was designed to maximize the
number of pumps that can be rated using the less burdensome
calculation-based methods A.1, B.1, and C.1. DOE also proposed the
applicability of the various test methods to maximize flexibility in
rating equipment. That is, where possible, DOE proposed to allow either
the calculation-based or the testing-based method to be used to
determine the PEI of applicable pump models. 80 FR 17627-28. In this
case, if a manufacturer wished to represent the improved performance of
a given pump, for example from a motor with improved part load
efficiency performance, and believed that the assumptions made in the
calculation method would not adequately represent the improved
performance of that pump, the manufacturer would be able to use the
testing-based methods to rate the PEICL or PEIVL
of that pump model to capture the improved performance of the pump as
tested.
DOE also noted that, since the measured performance of individual
units can vary from the average performance of the population or from
DOE's assumed values used in the calculation-based approach, it is
theoretically possible for the calculation-based approach to generate
ratings that are better or worse than the testing-based approach. To
address this possibility, DOE proposed that manufacturers report the
test method (i.e., calculation-based or testing-based) used to
determine the PEI for each model and that DOE would use the same method
used by the manufacturer to generate the rating when performing
assessment or enforcement testing. Id. at 17628.
DOE requested comment on its proposal to establish calculation-
based test methods as the required test method for bare pumps and
testing-based methods as the required test method for pumps sold with
motors that are not regulated by DOE's electric motor energy
conservation standards, except for submersible motors, or for pumps
sold with any motors and with non-continuous controls. DOE also
requested comment on the proposal to allow either testing-based methods
or calculation-based methods to be used to rate pumps sold with
continuous control-equipped motors that are either (1) regulated by
DOE's electric motor standards or (2) submersible motors. In addition,
DOE requested comment on the level of burden associated with reporting
the test method used by a manufacturer to certify a given pump basic
model as compliant with any energy conservation standards DOE may set.
HI commented that it agrees with these proposals, and that it is
not too burdensome to note the test method in the certification report,
as proposed in the April 2015 pumps test procedure NOPR. (HI, No. 8 at
p. 23) Wilo commented that the calculation-based test methods should be
eliminated entirely. Wilo indicated that one problem is that DOE is not
responsible for providing tools to determine compliance, so each
manufacturer will be responsible for creating its own potentially
erroneous evaluation tool. Wilo also indicated that a second problem is
that there are no standard efficiencies for VFDs, so a manufacturer
could use a minimally performing VFD to create a better performing PEI
value for a given pump sold with motor and controls. (Wilo, Docket No.
EERE-2011-BT-STD-0031, No. 44 at pp. 3-4)
In response to Wilo's comment regarding the calculation-based
approach, DOE notes that DOE developed the calculation-based approach
with extensive feedback and input from the CIP Working Group and
believes that it is appropriate for the categories and configurations
of pumps for which DOE proposed it would be applicable. DOE also notes
that, as described in the April 2015 pumps test procedure NOPR, the
calculation-based approach is significantly less burdensome than the
testing-based approach since a manufacturer may elect to determine the
PEI rating for several pump models sold with different combinations of
motors and/or continuous controls based on the physical test of the
bare pump only. That is, manufacturers may test a representative sample
of bare pumps (see section III.G for a description of DOE's sampling
provisions for pumps) and all subsequent ratings of that bare pump sold
with any combination of motors that are covered by DOE's energy
conservation standards, submersible motors, and continuous controls may
be calculated using the calculation-based approach with no additional
physical testing. Due to the potentially large burden associated with
requiring physical testing of each potential combination of a bare
pump, motor, and continuous control, as well as the existing concerns
of manufacturers and other interested parties regarding the proposed
test procedure (see section IV.B), DOE is electing to maintain the
calculation-based procedure as an option for applicable pumps.
DOE also notes that the calculation-based procedure is required for
bare pumps, as testing-based methods do not apply to bare pumps because
a PEI rating (which includes the efficiency of the motor) cannot be
determined based on a test of the bare pump alone. For all other pump
configurations, the calculation-based method is only offered as an
option, should manufacturers choose to employ it. Therefore, if Wilo
prefers to use the testing-based approach to certify their equipment,
it may do so for all configurations of pumps except bare pumps.
Regarding the accuracy or validity of any evaluation tools to
implement any calculations associated with either the calculation-based
or testing-based approach, DOE notes that manufacturers must rate pumps
in accordance with the test procedure. The calculation-based approach
required by the regulations provides sufficient detail for
manufacturers to develop reliable tools. Nonetheless, manufacturers are
responsible for ensuring that any calculations are performed correctly,
whether performed using an evaluation tool or by hand, for both the
calculation-based and the testing-based approaches.
In response to Wilo's comment regarding the potential for a
manufacturer to improve the PEI rating of a given pump model sold with
a motor, but without continuous controls, by pairing the pump with
continuous controls, DOE acknowledges that the PEI for pumps sold with
continuous controls tested using either the calculation-based or
testing-based approach will be better (i.e., lower) than that of the
same pump sold and tested with a motor only. However, consistent with
the feedback provided by the CIP Working Group, DOE believes that
decreased PEI is reflective and representative of the improved energy
performance customers are likely to observe in the field. That is, the
load points and, in the case of controlled-motors, the system curve,
assumed for these pumps (discussed in section III.B and III.E.2.c,
respectively) are representative of the operation of such pumps in the
field. DOE also notes that, as mentioned in the April 2015 pumps test
procedure NOPR, the testing-based method is intended to allow for more
granular differentiation of equipment performance, including
differentiation of the performance of different models or styles of
continuous controls. In particular, DOE noted in the April 2015 pumps
test procedure NOPR that the ability of the testing-based method to
differentiate among the performance of various continuous controls was
particularly important for pumps sold with motors and continuous
controls, since DOE is only assuming a single
[[Page 4127]]
system performance curve to represent all applicable continuous
controls, as described in section III.E.1.c, and the testing-based
method may provide an opportunity for manufacturers to differentiate
among the performance of different continuous control technologies. Id.
at 17627-28.
In this test procedure final rule, DOE is adopting the test method
applicability proposed in the April 2015 pumps test procedure NOPR and
shown in Table III.8 with no modifications. As proposed in the NOPR,
DOE is also adopting requirements that manufacturers report the test
method used to determine the ratings for applicable pump models and
provisions that when conducting assessment and enforcement testing DOE
will use the same method reported by manufacturers.
The specific test methods, any comments DOE received on the
proposed methods and applicability, and the final test methods DOE is
adopting in this final rule are discussed in the following sections:
Section III.E.1.a: The calculation-based approach for bare
pumps (method A.1),
section III.E.1.b: The calculation-based approach for
pumps sold with applicable motors,
section III.E.1.c: The calculation-based approach for
pumps sold with applicable motors and continuous controls,
section III.E.2.b: The testing-based approach for pumps
sold with motors, and
section III.E.2.c: The testing-based approach for pumps
sold with motors and continuous or non-continuous controls.
1. Calculation-Based Test Methods
In the April 2015 pumps test procedure NOPR, DOE proposed that the
following calculation-based test methods would be used to rate (1)
pumps sold as bare pumps (method A.1); (2) pumps sold either with (a)
motors that are regulated by DOE's electric motor standards or (b)
submersible motors (method B.1); and (3) pumps sold with motors that
are either (a) regulated by DOE's electric motor standards or (b)
submersible motors, and that are equipped with continuous controls
66 67 (method C.1). 80 FR 17586, 17616 (April 1, 2015).
---------------------------------------------------------------------------
\66\ The calculation-based test method was designed to capture
the dynamic response of a control that can continuously respond to
changes in load and reduce power consumption at all load points
below BEP. Therefore, pumps sold with non-continuous controls would
instead use the testing-based method described in section III.E.2.c,
which captures some reduction in power consumption at some reduced
flow rates. DOE discussed this approach with the CIP Working Group,
which generally agreed with it, although such a recommendation was
not specifically included in the CIP Working Group recommendations.
(Docket No. EERE-2013-BT-NOC-0039, No. 107 at pp. 49-50)
\67\ DOE notes that some pumps sold with continuous controls,
such as pumps sold with ECMs, may not be eligible to apply the
calculation-based method based on the fact that ECMs are not: (1) A
type of motor covered by DOE's energy conservation standards for
covered motors or (2) a submersible motor (see section III.E). These
pumps would instead apply a testing-based method.
---------------------------------------------------------------------------
Regardless of the pump configuration or characteristics, the
calculation-based test method for the applicable pump types includes
the following steps:
(1) Physical testing of the bare pump, in accordance with HI 40.6-
2014, to determine the pump BEP and pump shaft input power at 75, 100,
and 110 of actual BEP flow, adjusted to nominal speed;
(2) Determining the part load losses of the motor (or default
motor) and any continuous or non-continuous controls applicable to the
rated pump model at each load point;
(3) Taking the sum of the pump shaft input power at nominal speed
and the calculated part load motor losses at each load point in the
constant load or variable load profiles, as applicable, to determine
the input power to the pump at each load point;
(4) Determining the PERCL or PERVL, as
applicable, for the given pump as the weighted average of the input
power to the pump at the applicable load points;
(5) Determining the PERSTD for the minimally compliant
pump, as described in section III.B.2; and
(6) Dividing the PERCL or PERVL from step 4
by the PERSTD for that pump model to determine
PEICL or PEIVL, respectively.
The specific test methods for bare pumps, pumps sold with motors,
and pumps sold with motors and continuous controls are described in
more detail in the following sections III.E.1.a, III.E.1.b, and
III.E.1.c, respectively.
a. Calculation-Based Test Method A.1: Bare Pump
As described previously, DOE proposed in the April 2015 pumps test
procedure NOPR that the bare pump PERCL would be determined
based on the measured pump shaft input power at 75, 100, and 110
percent of BEP flow. 80 FR 17586, 17616-17 (April 1, 2015). Section
III.C of this final rule describes the test method for determining pump
shaft input power at the specified load points, which is based on HI
40.6-2014. DOE proposed that the measured pump shaft input power at the
three constant-load flow points would then be combined with the part
load motor losses at each load point and equally weighted to determine
PERCL for that bare pump, as shown in equation (16):
[GRAPHIC] [TIFF OMITTED] TR25JA16.014
Where:
[omega]i = weighting at load point i (equal weighting or
\1/3\ in this case),
Pi\in,m\ = calculated input power to the motor at load
point i (hp),
Pi = the shaft input power to the bare pump at load point
i (hp),
Li = default motor losses at load point i (hp), and
i = load point corresponding to 75, 100, or 110 percent of BEP flow
as determined in accordance with the DOE test procedure.
Id.
The part load motor losses for the bare pump would be determined
for the bare pump based on a default nominal full load motor
efficiency, representative of a motor that is minimally compliant with
DOE's electric motor energy conservation standards (or the default
minimum motor efficiency for submersible motors), as described in
section III.D.1, and the default motor loss curve, as described in
section III.D.2. Id.
As presented in section III.B, the PEICL for a bare pump
can then be calculated as the PERCL for a given pump divided
by the PERSTD for a pump that is minimally compliant with
DOE's pump standards sold without controls, as shown in equation (17):
[[Page 4128]]
[GRAPHIC] [TIFF OMITTED] TR25JA16.015
Where:
PERSTD = the PERCL for a pump of the same
equipment class with the same flow and specific speed
characteristics that is minimally compliant with DOE's energy
conservation standards serving the same hydraulic load (hp). The
procedure for determining PERSTD is described in detail
in section III.B.2.
For bare pumps, DOE proposed establishing the calculation-based
approach (method A.1) as the only applicable test procedure, as
testing-based methods do not apply to bare pumps because a PEI rating
(which includes the efficiency of the motor) cannot be determined based
on a test of the bare pump alone.
DOE received no specific comments on the proposed test procedure
for bare pumps and is adopting the calculation-based test procedure, as
proposed.
b. Calculation-Based Test Method B.1: Pump Sold With a Motor
For pumps sold with motors that either are regulated by DOE's
electric motor standards or are submersible motors, DOE proposed to
allow the use of the applicable calculation-based method (method B.1),
in addition to the testing-based method (method B.2, discussed in
section III.E.2.b). In these cases, DOE proposed that the calculation-
based test procedure would be similar to that for pumps sold alone
(method A.1) except that the represented nominal full load motor
efficiency, or losses, would be that of the motor with which the pump
is sold when determining PERCL, as opposed to the default
nominal full load motor efficiency assumed in the bare pump case. For
motors covered by DOE's electric motor standards, DOE proposed that the
represented nominal full load motor efficiency be determined in
accordance with the DOE electric motor test procedure specified at 10
CFR 431.16 and appendix B to subpart B of part 431 (see section
III.D.2) and applicable procedures for determining the represented
value (also specified in 10 CFR part 429 and 431). For pumps sold with
submersible motors rated using the calculation-based method, the
default nominal full load submersible motor efficiency would be
determined from Table III.6 (see section III.D.1.b). DOE also
reiterated that this calculation-based method would not apply to pumps
sold with motors that are not subject to DOE's electric motor standards
(except for submersible motors). 80 FR 17586, 17618 (April 1, 2015).
The PEICL for pumps sold with motors would then be
calculated using a similar approach that would be applied to bare pumps
shown in equations (16) and (17), above, except that the default part
load losses of the motor at each load point would be determined based
on the represented nominal full load motor efficiency, as described in
section III.D.2. Id.
As previously discussed in section III.B.2, in determining
PERSTD, DOE proposed to use the electric motor efficiency
standards listed at 10 CFR 431.25 for polyphase NEMA Design B motors as
the default nominal full load motor efficiency of the minimally
compliant pump for pumps sold with motors other than submersible
motors. Similarly, for pumps sold with submersible motors, the default
nominal full load motor efficiency would be that specified in Table
III.6 in section III.D.1.b for both the rated pump model and
PERSTD. Id.
In the April 2015 pump test procedure NOPR, DOE requested comment
on several specific items related to the proposed calculation-based
test procedure for pumps sold with applicable motors. Specifically, DOE
requested comment on its proposal to determine the part load losses of
motors covered by DOE's electric motor energy conservation standards
using the represented nominal full load motor efficiency, as determined
in accordance with DOE's electric motor test procedure, and the same
default motor part load loss curve used in test method A.1. In
response, HI commented that it could not comment on this issue. (HI,
No. 8 at p. 21) DOE received no additional comments on this proposal.
DOE requested comment on its proposal that pumps sold with motors
that are not addressed by DOE's electric motors test procedure (except
submersible motors) would be rated based on the testing-based approach,
and HI commented that it agrees with this proposal. (HI, No. 8 at p.
21) DOE received no additional comments on this proposal and has
determined that no revisions are necessary.
DOE also requested comment on its proposal to determine the
PERCL of pumps sold with submersible motors using the
proposed default nominal full load efficiency values for submersible
motors and to apply the same default motor part load loss curve to the
default motor in test method A.1 to the bare pump. HI commented that it
agrees with the proposal as long its concerns regarding submersible
motor efficiency, as detailed in section III.D.1.b of this final rule,
are addressed. (HI, No. 8 at p. 21) DOE received no other comments on
this proposal.
Based on the comments received from interested parties, DOE is
adopting the proposed test method B.1 for pumps sold with motors
covered by DOE's electric motor test procedure. For pumps sold with
submersible motors, the default nominal full load submersible motor
efficiency values used in the calculation of PERCL and
PERSTD are the values shown in Table III.7, which are
revised based on the input from HI.
c. Calculation-Based Test Method C.1: Pump Sold With a Motor and
Continuous Controls
For pumps sold with continuous controls and motors that are either
(a) regulated by DOE's electric motor standards for electric motors or
(b) submersible motors, DOE proposed, in the April 2015 pumps test
procedure NOPR, to allow use of either the applicable calculation-based
method (method C.1, discussed in this section III.E.1.c) or the
testing-based method (method C.2, discussed in section III.E.2.c). 80
FR 17618-19. The proposed calculation-based approach for pumps sold
with motors and continuous controls determines the PEIVL
metric, which accounts for the power reduction resulting from reducing
speed to achieve a given flow rate, as opposed to throttling. In this
case, DOE proposed that the PEIVL would be determined as the
PERVL of the given pump divided by the PERSTD,
where the PERSTD would be determined in accordance with the
procedures in section III.B.2, and the PERVL would be
determined as the weighted average input power to the pump at 25, 50,
75, and 100 percent of BEP flow, as shown in equation (18):
[[Page 4129]]
[GRAPHIC] [TIFF OMITTED] TR25JA16.016
Where:
[omega]i = weighting at load point i (equal weighting or
\1/4\ in this case),
Piin,c = measured or calculated driver power
input to the continuous or non-continuous controls at load point i
(hp), and
i = 25, 50, 75, and 100 percent of BEP flow, as determined in
accordance with the DOE test procedure.
Id.
Similar to the calculation-based approaches for bare pumps and
pumps sold with motors, the input power to the pump when sold with
motors and continuous controls would be determined by adding together
the pump shaft input power and the combined losses from the motor and
continuous controls at each of the load points. However, in the case of
determining PERVL for pumps sold with motors and continuous
controls, DOE proposed that only the input power at the 100 percent of
BEP flow load point would be determined through testing, and the
remaining 25, 50, and 75 percent of BEP flow load points would be
calculated based on an assumed system curve. In particular, consistent
with CIP Working Group discussions (Docket No. EERE-2013-BT-NOC-0039,
No. 107 at pp. 49-50), DOE proposed to use a quadratic reference system
curve, which goes through the BEP and an offset on the y-axis,
representative of a static head component to the system curve. The
reference system curve equation is shown in equation (19) and depicted
in Figure III.1:
[GRAPHIC] [TIFF OMITTED] TR25JA16.017
Where:
H = the total system head (ft),
Q = the flow rate (gpm),
Q100% = flow rate at 100 percent of BEP flow
(gpm), and
H100% = total pump head at 100 percent of BEP
flow (ft).
[GRAPHIC] [TIFF OMITTED] TR25JA16.018
DOE's approach for developing the proposed system curve is
discussed in detail in the April 2015 pump test procedure NOPR. Id. at
17619-20.
To determine the pump shaft input power at 25, 50, and 75 percent
of BEP flow, DOE proposed to apply the reference system curve discussed
in section III.E.1.c and assume that continuous speed reduction is
applied to achieve the reduced load points. Specifically, the reduction
in pump shaft input power at part loadings was assumed to be equivalent
to the relative reduction in pump hydraulic output power assumed by the
system curve, as shown in equation (20):
[[Page 4130]]
[GRAPHIC] [TIFF OMITTED] TR25JA16.019
Where:
Pi = shaft input power to the bare pump at load point i
(hp),
P100% = shaft input power to the bare pump at
100 percent of BEP flow (hp),
Qi = flow rate at load point i (gpm),
Q100% = flow rate at 100 percent of BEP flow
(gpm), and
i = 25, 50, and 75 percent of BEP flow as determined in accordance
with the DOE test procedure.
Id. at 17620-21.
Finally, to calculate the PERVL for pumps sold with
applicable motors and continuous controls, DOE proposed to apply a
separate algorithm for determining the part load losses of the motor
and continuous controls together, to account for the additional losses
as a result of inefficiencies from the continuous control and increased
inefficiencies in the speed-controlled motor due to harmonic
distortion. Based on data DOE collected regarding VFD performance, DOE
determined that four part load loss equations would be the most
appropriate way to represent the combined efficiency of the motor and
continuous control as a function of the output power of the motor and,
therefore, proposed to use the polynomial expression shown in equation
(21) to estimate the aggregate part load losses of motors and
continuous controls at each load point:
[GRAPHIC] [TIFF OMITTED] TR25JA16.020
Where:
zi = the part load loss factor for the motor and
continuous controls at load point i;
a,b,c = coefficients based on motor horsepower, see Table III.9;
Pi = the shaft input power to the bare pump at load point
i (hp);
MotorHP = the horsepower of the motor with which the pump is being
rated (hp); and
i = 25, 50, 75, and 100 percent of BEP flow as determined in
accordance with the DOE test procedure.
Table III.9--Motor and Continuous Control Part Load Loss Factor Equation Coefficients for Equation (21)
----------------------------------------------------------------------------------------------------------------
Coefficients for equation (21)
Motor horsepower (hp) -----------------------------------------------------
a b c
----------------------------------------------------------------------------------------------------------------
<=5....................................................... -0.4658 1.4965 0.5303
>5 and <=20............................................... -1.3198 2.9551 0.1052
>20 and <=50.............................................. -1.5122 3.0777 0.1847
>50....................................................... -0.8914 2.8846 0.2625
----------------------------------------------------------------------------------------------------------------
The development of DOE's part load loss factor equations for motors
and continuous controls are also described in detail in the April 2015
pumps test procedure NOPR. 80 FR 17586, 17621 (April 1, 2015).
To determine the resultant PEIVL rating for pumps sold
with applicable motors and continuous controls and rated based on the
calculation-based approach, the PERVL determined based on
the reference system curve and default motor and control losses would
be divided by the PERSTD, determined in accordance with the
procedure described in section III.B.2. DOE notes that, although the
PERVL of the tested pump only requires the 100 percent of
BEP flow load point to be determined experimentally, the full HI 40.6-
2014 test would still be required, and the pump hydraulic output power
at 75, 100, and 110 percent of BEP flow would still be necessary for
determining the PERSTD of the given pump. Id. at 17621-22.
In response to DOE's proposed calculation-based approach for pumps
sold with application motors and continuous controls, HI commented that
it is in agreement with the calculation-based test method for pumps
sold with motors and continuous controls, provided that the corrected
version of NOPR equation (6) presented at the April 2015 NOPR public
meeting is used. (HI, No. 8 at pp. 21-22) HI also specifically
indicated that it agrees with the proposed system curve shape, and that
it agrees that the curve should go through the statically loaded
offset.
Regal Beloit commented that it accepts the structure of the pump
energy conservation standards NOPR and the April 2015 pumps test
procedure NOPR as presented with respect to motor-drive efficiency
testing and evaluation, and encouraged the use of the forthcoming
industry standard IEC 61800-9-2 once it is published and at such time
as the DOE seeks to revise the pumps test procedure. (Regal Beloit, No.
9 at p. 1) DOE understands that the IEC standard will serve as a 60 Hz
version of the 50 Hz European industry standard BS EN 50598. DOE will
review the IEC standard once it is available, and may consider it for
future rulemaking activity.
DOE received no other comments on this test method, and confirms
that the final rule uses the corrected equation for determining the
minimum standard pump efficiency presented at the April 2015 NOPR
public meeting.
d. Other Calculation Methods for Determination of Pump Performance
In the April 2015 pumps test procedure NOPR, DOE proposed that each
bare pump model be physically tested in accordance with the test
procedure and that calculations alone could not be used to determine
bare pump performance. DOE noted that the calculation-based test
procedure for certain applicable pumps already contains provisions for
tested bare pump performance to be combined with default or tested
performance data regarding the motor or motor with continuous or non-
continuous controls to calculate the PER of multiple pump basic models.
Therefore, DOE proposed that, beyond the calculations proposed in the
April 2015 pumps test procedure
[[Page 4131]]
NOPR, DOE would not permit use of other algorithms or alternative
efficiency determination methods to determine the rated performance of
covered pumps or pump components (i.e., motors or controls). 80 FR
17586, 17622-23 (April 1, 2015).
DOE requested comment on its proposal to require testing of each
individual bare pump as the basis for a certified PEICL or
PEIVL rating for one or more pump basic models. DOE also
requested comment on its proposal to limit the use of calculations and
algorithms in the determination of pump performance to the calculation-
based methods proposed in the NOPR. HI commented that it agrees with
these proposals. (HI, No. 8 at p. 22) DOE received no additional
comments on these proposals and, consistent with the comments submitted
by HI, is adopting such calculation methods as discussed in this
section III.E.1 in this final rule.
2. Testing-Based Methods
Testing-based methods directly measure the input power to the
motor, continuous control, or non-continuous control at the load points
of interest (i.e., 75, 100, and 110 percent of BEP flow for
uncontrolled pumps and 25, 50, 75, and 100 percent of BEP flow for
pumps sold with a motor and speed controls). As such, as discussed
previously, these methods cannot be applied to bare pumps. In addition,
these test methods are the only test methods applicable to pumps sold
with motors that are not addressed by DOE's electric motor test
procedure (except submersible motors) or that are sold with non-
continuous controls and are an optional procedure for all pumps sold
with motors or motors with continuous controls.
The following sections describe DOE's proposals, any comments
received from interested parties, and the final test provisions DOE is
adopting in this final rule on the following topics:
How to determine BEP for pumps rated using the testing-
based method (section III.E.2.a),
the testing-based approach for pumps sold with motors
(method B.2; described in section III.E.2.b), and
the testing-based approach for pumps sold with motors and
continuous or non-continuous controls (method B.3; described in section
III.E.2.c).
a. The Best Efficiency Point for Pumps Testing Using Testing-Based
Methods
In the April 2015 pumps test procedure NOPR, DOE noted that when
testing some pumps using testing-based methods, it is not possible to
determine BEP as a ratio of pump input power over pump hydraulic power
unless additional measurements are made of bare pump performance or
pump shaft input power, in addition to input power to the motor. See
section III.C.2.d. Specifically, in the case of pumps sold with motors
or motors with continuous or non-continuous controls measured using
testing-based methods, DOE noted that input power to the pump shaft is
not measured directly in the proposed test procedure. As such, DOE
proposed that the BEP for such pumps be determined using a similar
procedure to that discussed in section III.C.2.d for calculation-based
methods; however, BEP would be determined using the maxima of what is
typically known as overall efficiency (i.e., the input power to the
driver or continuous control, if any, divided by the pump hydraulic
output power at the nominal speed), rather than pump efficiency. 80 FR
17586, 17623 (April 1, 2015).
DOE requested comment on its proposal to require manufacturers to
determine BEP for pumps rated with a testing-based method by using the
ratio of input power to the driver or continuous control, if any, over
pump hydraulic output. DOE also requested input on the degree to which
this method may yield significantly different BEPs from the case in
which BEP is determined based on pump efficiency. HI commented that BEP
can only be determined when testing the bare pump. HI also indicated
that determining BEP through a wire-to-water (i.e., testing-based)
method will cause the manufacturers to have to test each motor
configuration sold with the bare pump, increasing the burden. HI
recommended that the manufacturer be given the option to determine BEP
by testing as a bare pump or by testing using a wire to water test. HI
also recommended that BEP be instead defined as the pump hydraulic
power operating point consisting of both flow and head conditions that
result in the maximum efficiency of the certified unit. (HI, No. 8 at
pp. 22-23).
After review, DOE has determined that the HI proposal would yield
different efficiency ratings for the same pump. In response to HI's
comment, DOE notes that DOE initially proposed that the BEP when
applying the testing-based methods would be based on the overall
efficiency in order to reduce burden when conducting testing. That is,
when testing a pump in accordance with the testing-based method, DOE
proposed that the overall efficiency would be used to determine pump
efficiency so that the pump shaft input power would not have to be
separately determined, since measurements of pump shaft input power are
not otherwise needed when conducting the test procedure. If DOE were
instead to specify that BEP be determined based on the pump efficiency
only, pumps tested using the testing-based approaches would either need
to have additional instrumentation installed (e.g., a torque sensor) to
measure pump shaft input power or, in some cases, would require
duplicative testing of the pump with a calibrated motor if a torque
sensor could not be inserted between the bare pump and motor based on
the pump design. For example, ESCC and VTS pumps would not be able to
be tested using the testing-based methods to determine BEP based on
pump efficiency in the same test, unless a calibrated motor with the
same characteristics as the motor with which the pump model was to be
distributed in commerce was used.
In response to HI's concern regarding the increased burden of
determining the BEP based on overall efficiency, DOE finds this
statement to be erroneous, since the determination of BEP based on
overall efficiency would only be required for the testing-based
approaches and the testing-based approaches already require each basic
model to be tested. Under the proposed approach, no incremental testing
would be necessary. To the extent that manufacturers wish to use the
calculation-based methods to determine the PEI of applicable pumps, the
BEP of the bare pump, based on pump efficiency, must be used. However,
these data are irrelevant to determining the PEI of pumps under the
testing-based approach, since the two methods are mutually exclusive.
That is, the PEI of a given pump cannot be determined via both
calculation-based and testing-based approaches. DOE has ensured that
this is clear in the regulatory text included in this final rule.
Regarding HI's proposal to optionally allow manufacturers to use
either pump efficiency or overall efficiency, DOE believes that such an
approach could potentially result in variability in the BEP, and thus
PEI, for the same pump model. This is unacceptable since each pump
model can have only one certified PEI value associated with it and that
value must be repeatable and consistent among test facilities.
DOE believes that the approach proposed in the April 2015 pumps
test procedure NOPR will result in representations that are more
straightforward and consistent, as well as less burdensome, for those
pumps rated using the testing-based approach. As such, DOE is adopting,
in this final rule, the approach proposed in the April 2015 pump test
procedure NOPR to
[[Page 4132]]
determine the BEP of pumps rated using the testing-based approach based
on overall efficiency, as opposed to pump efficiency.
Regarding HI's comment that BEP should be determined as the load
point associated with maximum efficiency, which consists of both head
and flow points, DOE acknowledges HI's comments and agrees that the BEP
for each pump represents the flow and head points representing maximum
efficiency at full impeller diameter. In particular, DOE notes that
DOE's definition of BEP, as adopted in this final rule, specifies BEP
with respect to a load point, consisting of both flow and head
conditions. However, in this test procedure final rule, DOE in general
refers to BEP flow, since DOE's specified load points are characterized
with respect to BEP flow only. DOE understands that the head and flow
of a given pump, at full impeller diameter and without throttling, are
inextricably linked, so it is not necessary to independently account
for and specify both parameters. That is, for example, by specifying
the flow at 100 percent of BEP, the power calculated at that load point
will, necessarily, also be reflective of head at 100 percent of BEP
flow, since the data are all based on the same curve. It is not
possible to determine the power input at, for example, 50 percent of
BEP flow and 100 percent of BEP head without throttling the pump,
trimming the impeller, or otherwise physically altering the tested
equipment or test set-up such that the data generated would no longer
be reflective of the pump model being tested. As such, DOE does not
believe that any additional specifications or clarifications regarding
the BEP load point are necessary in the pumps test procedure.
b. Testing-Based Test Method B.2: Pump Sold With a Motor
For pumps sold with motors that are not regulated by DOE's electric
motor standards (except for submersible motors), DOE proposed that use
of the testing-based method B.2, discussed in this section III.E.2.b,
would be required because the nominal full load efficiency of the
motor, as determined using a specific standardized procedure, is not
available for those motors. For pumps sold with motors subject to DOE's
electric motor standards or submersible motors, the testing-based
approach discussed in this section III.E.2.b would be optional.
In the April 2015 pumps test procedure NOPR, DOE also proposed
that, for pumps sold with motors, the PEICL could be
determined by wire-to-water testing, as specified in HI 40.6-2014,
section 40.6.4.4. In this case, the PERCL would become an
average of the measured power input to the motor at the three specified
load points, as shown in equation (22):
[GRAPHIC] [TIFF OMITTED] TR25JA16.021
Where:
[omega]i = weighting at load point i (equal weighting or
\1/3\ in this case),
Pi\in,m\ = measured or calculated driver power input to
the motor at load point i (hp), and
i = load point at 75, 100, or 110 percent of BEP flow as determined
in accordance with the DOE test procedure.
80 FR 17586, 17623 (April 1, 2015).
DOE received no comments on the proposed testing-based approach for
pumps sold with motors and, as such, is adopting the provisions
discussed in the April 2015 pumps test procedure NOPR with no changes.
c. Testing-Based Test Method C.2: Pump Sold With a Motor and Speed
Controls
For pumps sold with non-continuous control-equipped motors that are
either (1) regulated by DOE's electric motor standards for electric
motors or (2) submersible motors, as defined in section III.E.1.c, DOE
proposed in the April 2015 pumps test procedure NOPR that the
calculation-based method C.1 would not be applicable because these
controls are not able to follow the reference system curve described in
section III.E.1.c. Instead, pumps sold with non-continuous controls
would have to be tested using the testing-based method C.2. For pumps
sold with motors not regulated by DOE's electric motor standards
(excluding submersible motors) that are equipped with either continuous
or non-continuous controls, DOE also noted that only these testing-
based methods (method C.2) would apply, as is the case for pumps sold
with motors not regulated by DOE's electric motor standards (excluding
submersible motors) without controls (discussed in section III.E.2.b).
80 FR 17586, 17627 (April 1, 2015).
For pumps sold with continuous controls and motors that are (1)
regulated by DOE's electric motor standards for electric motors or (2)
submersible motors, the testing-based approach discussed herein (method
C.2) would be optional, and such pumps may also be tested under the
calculation-based approach, as discussed in section III.E.1.c. Id.
Regarding the specific procedures contained in the testing-based
approach for pumps sold with motors and continuous or non-continuous
controls, DOE proposed that the PEIVL may be determined by
wire-to-water testing, based on the procedure specified in HI 40.6,
section 40.6.4.4, except that the input power:
Is the ``driver input power'' defined in table 40.6.2.1 of
HI 40.6-2014 and referenced in table 40.6.3.2.3, section 40.6.4.4, and
section 40.6.6.2,
refers to the input power to the continuous or non-
continuous control, and
is determined in accordance with the tolerances and
requirements for measuring electrical power described in section
III.C.2.e.
80 FR 17623-24.
DOE clarified that, with the proposed approach, pump manufacturers
would determine the BEP of the pump, inclusive of motor and continuous
or non-continuous controls, as described in section III.E.2.a, and then
adjust the operating speed of the motor and the head until the
specified head and flow conditions are reached (i.e., 25, 50, and 75
percent of BEP flow and the associated head pressures determined by the
reference system curve in section III.E.1.c). To ensure this method C.2
results in consistent and repeatable ratings, DOE also proposed
tolerances around each load point of 10 percent about (i.e., above and
below) the target flow and head load points defined on the reference
system curve for each pump. Similarly, DOE also proposed that the
measured data would be
[[Page 4133]]
extrapolated to the exact load points specified by the reference system
curve using the following equation (23):
[GRAPHIC] [TIFF OMITTED] TR25JA16.022
Where:
Pi = the corrected driver power input to the continuous
or non-continuous controls at load point i (hp),
Hsp,i = the specified total system head at load point i
based on the reference system curve (ft),\68\
---------------------------------------------------------------------------
\68\ DOE notes that in the April 2015 pumps test procedure NOPR,
DOE proposed to define the tested and ``reference'' head and flow
values using the subscript ``T'' for tested and ``R'' for rated
(e.g., HR, HT, QR, QT).
DOE notes that Table 40.6.2.2b of HI 40.6-2014 provides a list of
subscripts for use in applying the HI 40.6-2014 test method.
Specifically, Table 40.6.2.2b defines the subscript ``sp'' as
denoting ``specified'' values and the subscript ``M'' as denoting
measured values. For the sake of clarity and continuity, in this
final rule, DOE is adopting subscripts consistent with the defined
HI nomenclature.
---------------------------------------------------------------------------
HM,j = the measured total system head at load point j
(ft),
Qsp,i = the specified total system flow rate at load
point i based on the reference system curve (gpm),
QM,j = the measured total system flow rate at load point
j (gpm),
PM,j = the measured shaft input power to the bare pump at
load point j,
i = specified load point at 25, 50, 75, or 100 percent of BEP flow
as determined in accordance with the DOE test procedure, and
j = measured load point corresponding to specified load point i.
Id. at 17624-25.
Under DOE's proposed approach, the PER would become the mean of the
measured power input to the continuous or non-continuous control at the
four specified load points based on the assumed system curve (as in
method C.1), as shown in equation (24):
[GRAPHIC] [TIFF OMITTED] TR25JA16.023
Where:
[omega]i = weighting at load point i (equal weighting or
\1/4\ in this case),
Pi\in,c\ = measured or calculated driver power input to
the continuous or non-continuous controls at load point i (hp), and
i = load point at 25, 50, 75, or 100 percent of BEP flow, as
determined in accordance with the DOE test procedure.
Id. at 17625.
In the April 2015 pumps test procedure NOPR proposal, DOE also
noted that some pumps are sold with non-continuous controls, such as
multi-speed motors, that are not able to follow the reference system
curve directly at all load points. For example, in the case of a pump
sold with a two-speed motor, the pump will operate at full speed (i.e.,
the nominal speed) for some of the load points and reduced speed at the
other load points, as shown in Figure III.2.
[[Page 4134]]
[GRAPHIC] [TIFF OMITTED] TR25JA16.024
For pumps sold with non-continuous controls, DOE proposed to modify
this testing-based method C.2 for pumps sold with motors and continuous
or non-continuous controls to specify that the head measurements
associated with each of the specified flow points would not have to be
achieved within 10 percent of the specified head, as described by the
reference system curve--only the flow rate would need to be achieved
within 10 percent of the specified value. Id. at 17626. Instead, DOE
proposed to require that the measured pump total head corresponding to
the 25, 50, 75 and 100 percent of BEP flow points could not be lower
than 10 percent below that defined by referenced system curve. DOE also
proposed that, in this case, the measured head and flow rate would not
be corrected to the reference system curve. Instead, the tested load
points would be used directly in further calculations of
PEIVL. Id.
DOE requested comment on the proposed testing-based method for
pumps sold with motors and continuous or non-continuous controls, as
well as the proposed testing-based method for determining the input
power to the pump for pumps sold with motors and non-continuous
controls. In addition, DOE requested comment on any other type of non-
continuous control that may be sold with a pump and for which the
proposed test procedure would not apply.
HI commented that it agrees with the optional testing-based
methods, but also indicated that any pump sold with an ON/OFF control
should be tested or calculated using a PEICL method. (HI,
No. 8 at p. 23) DOE agrees with HI that ON/OFF switches do not
constitute a type of continuous or non-continuous control for which the
calculation-based or testing-based methods (C.1 and C.2, respectively)
or the PEIVL metric, would be applicable. Consistent with
the April 2015 pumps test procedure NOPR section III.A.1.a and public
meeting slide 45, DOE has revised Table 1 in appendix A accordingly to
clarify that (1) the calculation-based and testing-based methods to
determine PEIVL apply to pumps sold with motors and
continuous or non-continuous controls only; whereas, (2) the test
methods for pumps sold with motors (methods B.1 and B.2) apply to pumps
sold with motors and controls other than continuous and non-continuous
controls.
F. Representations of Energy Use and Energy Efficiency
As noted previously, manufacturers of any pumps within the scope of
the pump test procedure will be required to use the test procedure
established in this rulemaking when making representations about the
energy efficiency or energy use of their equipment. Specifically, 42
U.S.C. 6314(d) provides that ``[n]o manufacturer . . . may make any
representation . . . respecting the energy consumption of such
equipment or cost of energy consumed by such equipment, unless such
equipment has been tested in accordance with such test procedure and
such representation fairly discloses the results of such testing.''
In the April 2015 pumps test procedure NOPR, DOE noted that
performing the proposed test procedure for pumps requires a key
component (C-value) that is being addressed through the parallel
standards rulemaking for pumps (Docket No. EERE-2011-BT-STD-0031). 80
FR 17586, 17628 (April 1, 2015). Because of this dependency, DOE
clarified that manufacturers of equipment that are addressed by this
test procedure and any applicable standards that DOE may set would have
180 days after the promulgation of those standards to begin using the
DOE procedure.
With respect to representations, generally, DOE stated its
understanding that manufacturers often make representations
(graphically or in numerical form) of energy use metrics, including
pump efficiency, overall (wire-to-water) efficiency, bowl efficiency,
driver power input, pump power input (brake or shaft horsepower), and/
or pump power output (hydraulic horsepower) and may
[[Page 4135]]
make these representations at multiple impeller trims, operating
speeds, and number of stages for a given pump. DOE proposed in the
April 2015 pumps test procedure NOPR to allow manufacturers to continue
making these representations. Id.
DOE also proposed that any representations of PEI and PER must be
made in accordance with the DOE test procedure, and there may only be
one PEI or PER representation for each basic model. In other words,
representations of PEI and PER that differ from the full impeller PEI
and PER cannot be made at alternate speeds, stages, or impeller trims.
Additionally, if the PEI and PER for a basic model is rated using any
method other than method A.1, ``bare pump with default motor efficiency
and default motor part load loss curve,'' such a basic model may not
include individual models with alternate stages or impeller trims.
If a manufacturer wishes to make unique representations of PEI or
PER based on a trimmed impeller, the manufacturer must certify the
trimmed impeller as a separate basic model. In such a case, the
``trimmed impeller'' being rated would become the ``full impeller'' for
the new basic model (i.e., the maximum diameter impeller distributed in
commerce for that pump model) (see section III.A.1.c). 80 FR 17586,
17628 (April 1, 2015).
In response to DOE's language regarding representations in the
April 2015 pumps test procedure NOPR, HI stated its concern with the
somewhat vague language used around 42 U.S.C. 6314(d) prohibited
representation. HI emphasized that it is imperative that pump
manufacturers be allowed to continue using pre-existing efficiency
curves and sizing software that is used directly by end users and
distributors to purchase pumps. HI noted its interpretation that the
following text: ``Manufacturers often make these representations at
multiple impeller trims, operating speeds, and number of stages for a
given pump. DOE proposes to allow manufacturers to continue making
these representations.'' indicates that existing performance and
efficiency data can continue to be used and that only representations
of PER and PEI fall under [the requirements of] 42 U.S.C. 6314(d)
``Prohibited Representation.'' HI requested that DOE clearly articulate
in the final rule that prohibited representation under 42 U.S.C.
6314(d) applies only to PER and PEI representations. (HI, No. 8 at p.
1)
In response to HI's comment regarding the nature of representations
manufacturers are allowed to make regarding the performance of their
equipment under 42 U.S.C. 6314(d), DOE reiterates that, beginning 180
days after publication of this final rule in the Federal Register, all
representations regarding PERCL and PERVL must be
made in accordance with the DOE test procedure. Similarly, all
representations regarding PEICL and PEIVL must be
made in accordance with the DOE test procedure beginning 180 days after
publication of a final rule in the Federal Register that sets C-values
(i.e., a final rule in the parallel energy conservation standards
rulemaking). However, regarding other measures of energy use, energy
efficiency, or related performance metrics for pumps, DOE clarifies
that such representations must be made using methods that will generate
values consistent with the DOE test procedure, as finalized in this
final rule. DOE acknowledges that manufacturers have large amounts of
pre-existing data that they currently use to market and make
representations about the performance of their equipment and that
regenerating all of this data within the 180 day timeframe would be
burdensome. As such, manufacturers may continue to use such data to
make representations about the performance of applicable pump models
after the 180 day timeframe, provided manufacturers are confident that
the values are consistent with those that would be generated under the
adopted test procedure.
In the April 2015 NOPR public meeting, the EEAs noted that it would
be helpful if DOE could have its certification materials available
prior to the compliance date so that manufacturers can make early
representations of PEI. (EEAs, NOPR public meeting transcript, No. 7 at
pp. 191-192) The EEAs also noted that it would be helpful for all the
fields in the certification report to show up in the database, or that
they would determine which items the utility programs would need.
(EEAs, NOPR public meeting transcript, No. 7 at pp. 206-207) DOE
discusses compliance certification reporting in the parallel energy
conservation standards rulemaking, and has considered the stakeholder
comments in that rule.
G. Sampling Plans for Pumps
DOE provides in subpart B to 10 CFR part 429 sampling plans for all
covered equipment. The purpose of these sampling plans is to provide
uniform statistical methods for determining compliance with prescribed
energy conservation standards and for making representations of energy
consumption and energy efficiency on labels and in other locations such
as marketing materials. In the April 2015 pumps test procedure NOPR,
DOE proposed that, for pumps, the same statistical sampling plans used
for other commercial and industrial equipment would be applicable and
proposed to add the sampling plan to 10 CFR 429.59. 80 FR 17586, 17628-
29 (April 1, 2015).
Under the proposal, DOE proposed that a sample of sufficient size
must be randomly selected and tested to ensure compliance and that a
minimum of two units must be tested to certify a basic model as
compliant. DOE also proposed to apply the same statistical sampling
procedures, including the confidence limit and derating factor, that
are applicable to many other types of commercial and industrial
equipment, as DOE believes equipment variability and measurement
repeatability associated with the measurements proposed for rating
pumps are similar to the variability and measurement repeatability
associated with energy efficiency or consumption measurement required
for other commercial equipment. Id.
Finally, DOE proposed that DOE would determine compliance in an
enforcement matter based on the arithmetic mean of a sample not to
exceed four units. Id.
DOE received no comments on this proposal. However, upon reviewing
the April 2015 pump test procedure NOPR proposals, DOE identified
several provisions that require clarification to ensure that DOE's
certification and enforcement provisions are clear and consistent.
First, in the April 2015 pumps test procedure NOPR, the equations
for the upper confidence limit (UCL) and lower confidence limit (LCL)
in section 429.60 both referenced a confidence limit of 0.95. 80 FR
17586, 17640 (April 1, 2015). However, the UCL and LCL were proposed to
be divided by a de-rating factor of 1.01 and 0.99, respectively. Id.
DOE notes that the confidence limit of the t-statistic and the de-
rating factor in the denominator, collectively, are intended to capture
the likely variability in pump testing resulting from the allowable
test tolerances and instrument accuracy (discussed in sections III.C),
lab-to-lab variability, and manufacturing tolerances contained within
each model. In the April 2015 pumps test procedure NOPR, DOE had
proposed a confidence limit of 99 percent, expecting a 95 percent
confidence limit would exceed the amount of variability in PEI that
would occur in pump ratings. Specifically, because PEI is an indexed
value, with values that range from zero to one, this decreases the
amount of
[[Page 4136]]
variability that may occur in each individual measurement.
DOE received no comments from interested parties in response to the
proposal in the April 2015 pumps test procedure NOPR. However, DOE
reevaluated the April 2015 pumps test procedure NOPR proposal and
determined that the resultant values may yield overly conservative
results that would effectively require such pumps to meet a more
stringent standard than that considered in the associated pumps energy
conservation standards rule (Docket No. EERE-2011-BT-STD-0031).
Therefore, in this final rule, DOE is correcting the confidence limit
and derating factor adopted in this final rule to better reflect the
likely variability in test results expected to result from the pumps
test procedure, lab-to-lab variability, and manufacturing tolerances.
Specifically, for the purpose of regulating pumps, a confidence limit
of 0.95 and de-rating factor of 1.05 or 0.95 is required due to the
combined impacts of test tolerances, experimental variability in
conducting the test procedure, and manufacturing variability for this
equipment. That is, given the likely variation of measured PEIs within
a sample of pump units of the same model, a confidence limit of 0.95 is
necessary to ensure that the statistical requirements in the sampling
plan for pumps are consistent with the magnitude of the variance
between tested units within a sample resulting from manufacturing
tolerances and experimental uncertainty inherent in the test procedure.
Therefore, DOE is adopting a confidence limit of 0.95 and de-rating
factors of 1.05 and 0.95 as applicable to pumps in this test procedure
final rule.
Also, regarding testing pumps for enforcement purposes, DOE is
clarifying, in this final rule, the procedure for determining BEP when
the ``expected BEP'' may not be known to DOE. As discussed in section
III.C.2.d, the procedure for determining BEP described in section
40.6.5.5.1 of HI 40.6-2014 requires that the flow points are to be 40,
60, 75, 90, 100, 110, and 120 percent of the expected BEP of the pump
model and that if the BEP rate of flow is displaced by more than 5
percent, the test must be repeated. In the case of enforcement testing,
DOE will follow the same procedure as manufacturers in determining the
BEP of the pump. In this final rule, DOE is clarifying that DOE will
use the volume rate of flow (flow rate) at BEP and nominal speed
certified by the manufacturer for that pump model as the expected BEP
when performing the BEP test. In the case that the BEP rate of flow is
more than 5 percent displaced from the certified value, DOE will also
retest the pump as required by the test procedure. However, if the
retested BEP rate of flow is still more than 5 percent displaced from
the manufacturer's certified value, DOE will use the mean of the tested
values as the volume rate of flow (flow rate) at BEP and nominal speed
in subsequent calculations when determining the PEI for that model.
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget (OMB) has determined that test
procedure rulemakings do not constitute ``significant regulatory
actions'' under section 3(f) of Executive Order 12866, Regulatory
Planning and Review, 58 FR 51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under the Executive Order by the
Office of Information and Regulatory Affairs (OIRA) in OMB.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601, et seq.) requires
preparation of a regulatory flexibility analysis for any rule that by
law must be proposed for public comment, unless the agency certifies
that the rule, if promulgated, will not have a significant economic
impact on a substantial number of small entities. As required by
Executive Order 13272, ``Proper Consideration of Small Entities in
Agency Rulemaking,'' 67 FR 53461 (August 16, 2002), DOE published
procedures and policies on February 19, 2003, to ensure that the
potential impacts of its rules on small entities are properly
considered during the DOE rulemaking process. 68 FR 7990. DOE has made
its procedures and policies available on the Office of the General
Counsel's Web site: https://energy.gov/gc/office-general-counsel.
DOE reviewed today's final rule, which establishes new test
procedures for pumps, under the provisions of the Regulatory
Flexibility Act and the procedures and policies published on February
19, 2003. DOE concludes that the final rule DOE is adopting will not
result in a significant impact on a substantial number of small
entities. The factual basis set forth in the following sections.
1. The Need for, and Objectives of, Today's Rule
While DOE is currently evaluating whether to establish energy
conservation standards for pumps, DOE must first establish a test
procedure that measures the energy use, energy efficiency, or estimated
operating costs of a given type of covered equipment before
establishing any new energy conservation standards for that equipment.
See, generally, 42 U.S.C. 6295(r) and 6316(a). To fulfill these
requirements, DOE is establishing the test procedure for pumps,
described in this final rule, concurrent with its ongoing energy
conservation standards rulemaking for this equipment. See Docket No.
EERE-2011-BT-STD-0031.
In this test procedure, DOE prescribes test methods for measuring
the energy consumption of certain pumps, inclusive of motors and
controls (continuous or non-continuous), if they are included with the
pump when distributed in commerce. In addition, this final rule
establishes a new subpart Y to part 431 of Title 10 of the Code of
Federal Regulations that contains DOE's new test procedure for pumps,
as well as definitions pertinent to establishing the scope of pumps to
which the adopted test procedure is applicable. This final rule also
contains sampling plans for pumps for the purposes of demonstrating
compliance with any energy conservation standards that DOE adopts.
DOE's test procedure contains methods to determine the energy
consumption for all equipment for which this test procedure applies
using either calculation-based methods and/or testing-based methods.
While both methods include some amount of testing and some amount of
calculation, the terms ``calculation-based'' and ``testing-based'' are
used to distinguish between methods in which the input power to the
pump is determined either by (a) measuring the bare pump shaft input
power \69\ and calculating efficiency, or losses, of the motor and any
continuous control \70\ (i.e., calculation-based method) or (b)
measuring the input power to the driver,\71\ or motor, and any
continuous or non-continuous controls \72\ for a given pump directly
[[Page 4137]]
(i.e., testing-based method). As such, the test procedure includes
measurements and calculations of the produced hydraulic power, pump
shaft input power, electric input power to the motor, and electrical
input power to the continuous or non-continuous controls, as
applicable, which are substantially based on the test methods contained
in the industry test standard HI Standard 40.6-2014, ``Methods for
Rotodynamic Pump Efficiency Testing,'' (``HI 40.6-2014''), with slight
modifications as noted in section III.C.2.
---------------------------------------------------------------------------
\69\ The term ``pump shaft input power'' is referred to as
``pump power input'' in HI 40.6-2014. The term ``pump shaft input
power'' is used synonymously with that term in this document.
\70\ DOE notes that for non-continuous controls, as defined in
section III.E.1.c, PEIVL can only be determined using a
``testing-based'' method. If a calculation-based method is desired,
the pump would instead be rated as a pump sold with a motor and
without speed controls using the PEICL metric. See
section III.E.1.c for further discussion.
\71\ The input power to the driver is referred to as ``driver
power input'' in HI 40.6-2014. The term ``input power to the
driver'' is used synonymously with that term in this document.
\72\ In the case that a pump is sold with a motor equipped with
either continuous or non-continuous controls and is rated using the
testing-based method, the input power to the pump would be
determined as the input power to the continuous or non-continuous
control. See section III.E.2.c.
---------------------------------------------------------------------------
This test procedure final rule also contains requirements regarding
(1) the characteristics, categories, and configurations of pumps to
which the adopted test procedure is applicable; (2) the specific manner
in which pumps must be tested to determine any applicable
representations regarding the performance of pumps subject to the test
procedure; and (3) the number of pump units that must be tested to
determine the representative value for each basic model. As noted in
the April 2015 pump test procedure NOPR and further elaborated in
section III.F, DOE's new pumps test procedure requires a key component
(C-value) that is being addressed through the parallel standards
rulemaking for pumps (Docket No. EERE-2011-BT-STD-0031). 80 FR 17586,
17628 (April 1, 2015). As such, the use of this test procedure as the
basis for any representations regarding the energy efficiency or energy
use of pumps would not be required until 180 days after the publication
of any energy conservation standards final rule in the Federal
Register, Therefore, DOE notes that the test methods, definitions, and
sampling plans contained in this final rule do not introduce any
incremental burden to any manufacturers, since the use of such test
methods is not required by this test procedure final rule by itself.
That is, any burden associated with testing pumps in accordance with
the requirements of this test procedure final rule is not be required
until the promulgation of any energy conservation standards final rule
for pumps. On this basis, DOE maintains that this final rule has no
incremental burden associated with it and a final regulatory
flexibility analysis is not required.
While DOE maintains that this final rule has no incremental burden
associated with it when viewed as a stand-alone rulemaking, DOE
recognizes that pump energy conservation standards are currently being
considered in an associated rulemaking (Docket No. EERE-2011-BT-STD-
0031) and may be proposed or promulgated in the near future. Therefore,
to consider the aggregate impacts of developing certified ratings for
applicable pump models for the purposes of making representations
regarding the energy use of such equipment or certifying compliance to
DOE under any future energy conservation standards, DOE is also
estimating the full burden of conducting the testing required by this
test procedure final rule for each pump model. Therefore, while such is
not required yet, DOE is presenting the results from conducting the
regulatory flexibility analysis to develop estimates of the costs
associated with testing equipment consistent with the requirements of
this test procedure final rule, as would be required to certify
compliance with the potential energy conservation standard. DOE
presents the results of such analysis in the following sections.
However, DOE is not determining the significance of that burden
with respect to manufacturers' financial situation or status as a small
entity. As the use of the testing requirements contained in this final
rule is contingent upon the energy conservation standards rulemaking,
DOE is analyzing the effect of the combined burden associated with both
the test procedure and energy conservation standard rulemakings in the
manufacturer impact analysis performed as part of the energy
conservation standard rulemaking (see docket EERE-2011-BT-STD-0031).
The costs described in the following subsections are referenced in the
manufacturer impact analysis in the pumps energy conservation standard
rulemaking to estimate the burden associated with testing. However, DOE
reiterates that the estimates provided in this test procedure
regulatory flexibility analysis serve only to provide information about
the possible burden manufacturers may incur while testing pumps using
this DOE test procedure; they do not represent actual burden incurred
by the industry as there is no incremental burden associated with this
test procedure final rule until and unless the associated pumps energy
conservation standard final rule is published.
2. Significant Issues From Interested Parties in Response to IRFA
Within the April 2015 pumps test procedure NOPR, DOE conducted an
initial regulatory flexibility analysis (IRFA). 80 FR 17586, 17629-33
(April 1, 2015). In response to DOE's April 2015 pumps test procedure
NOPR estimate of testing burden, DOE received written and verbal
comments at the April 2015 NOPR public meeting, as well as throughout
the comment period. Comments related to the potential burden include
comments related to potential anticompetitive effects of the proposed
test procedure; cost of test facility(s); labor costs; quantity of
manufacturers potentially affected; and manufacturer sales to assess
burden. In this final rule, DOE addresses these comments and presents a
revised assessment of potential burden related to test procedure final
rule.
Anticompetitive Effects of Burden and Expense
Consistent with DOE's requirements to comply with section 32(c) of
the Federal Energy Administration Act of 1974, as amended by the
Federal Energy Administration Authorization Act of 1977 (15 U.S.C. 788;
see section IV.L), DOE is required to consult with the Attorney General
and the Chairman of the Federal Trade Commission (FTC) concerning the
impact of the proposed test procedure on competition in the pumps
industry. The U.S. Department of Justice (DOJ) reviewed the April 2015
pumps test procedure NOPR, attended the April 2015 NOPR public meeting,
and consulted with members of the industry in preparing their comments
and conclusions regarding any anticompetitive effects of the pumps test
procedure. In response to the proposed test procedure, DOJ commented
that it is not able to determine whether or not the proposed test
procedure (or associated energy conservation standard) will lessen
competition within the industry. However, DOJ noted that it is
concerned about the possibility of anticompetitive effects resulting
from the burden and expense of compliance. (DOJ, No. 14 at p. 2)
In this final rule, DOE reviews the potential burden and expense
related to testing, but does not analyze the potential effects on
competition. However, DOE notes that it has taken steps, in the test
procedure adopted in this final rule to minimize burden on
manufacturers related to testing and rating equipment in accordance
with such procedures.
Burden of Test Facility(s)
In the April 2015 pumps test procedure NOPR, DOE estimated the
burden to manufacturers associated with performing testing in
accordance with the proposed test procedure. 80 FR 17586, 17629-33
(April 1, 2015). DOE estimated that in order to determine the
performance of any covered pump models for the purposes of making
[[Page 4138]]
representations or certifying compliance under any future energy
conservation standards for pumps, each manufacturer would have to
either (a) have the units tested in-house or (b) have the units tested
at a third party testing facility. In addition, if the manufacturer
elected to test pumps in-house, each manufacturer would have to
undertake the following burden-inducing activities:
(1) Construct and maintain a test facility that is capable of
testing pumps in compliance with the test procedure, including
acquisition and calibration of any necessary measurement equipment, and
(2) conduct the DOE test procedure on two units of each covered
pump model. Id.
Because pumps are newly regulated equipment and there are no
existing testing requirements for pumps, the capabilities of existing
testing facilities may vary widely from one manufacturer to another. In
the April 2015 pumps test procedure NOPR, DOE based it's assessment of
testing burden on the conservative assumption that pump manufacturers
would have no existing testing infrastructure and would have to bear
the full cost of constructing a new testing facility generally capable
of conducting testing in accordance with the proposed test procedure.
DOE estimated the capital cost of constructing the two types of
facilities: A facility equipped to perform the calculation-based test
methods (described in section, III.E.1), which varied between $91,000
and $277,000, and a facility equipped to perform the testing-based test
methods (described in section, III.E.2), which varied between $72,000
and $213,000. DOE amortized these capital costs to determine an annual
payment amount over an estimated 7-year loan period because DOE's
research indicated this was the typical loan period for pump
manufacturers. DOE's final calculations regarding the cost of
constructing a test lab assumed that the majority of pump models would
be certified based on the bare pump configuration and subsequent
ratings for the same bare pump sold with any number of applicable
motors and continuous controls could be generated using the
calculation-based approach. In addition, DOE estimated the ongoing cost
of testing between $161.61 and $430.96 per unit, plus calibration
activities of $1,241.67 per year. 80 FR 17586, 17632 (April 1, 2015)
Based on these assumptions, DOE estimated the amortized total burden
associated with the test procedure ranged between $61,000 and $221,000
annually for small manufacturers affected by this rule. Id.
DOE requested specific comments and feedback on a number of
assumptions made in the April 2015 pumps test procedure NOPR regulatory
flexibility analysis. Regarding the cost of constructing a test
facility capable of performing the test procedure presented in the
April 2015 pumps test procedure NOPR, HI stated that the estimates of
materials and costs to build a pump testing facility as presented are
greatly underestimated and would be in excess of $1 million. HI
indicated that DOE's facility description leaves out many expensive
machines and other equipment that would be required for this testing.
(HI, No. 0008 at pp. 24-25)
DOE disagrees with the comments from HI regarding the cost of the
testing facility and the effect of burden on manufacturers and the
industry. DOE notes that, in the April 2015 pumps test procedure NOPR
initial regulatory flexibility analysis (IRFA), DOE used the most
burdensome assumptions to estimate the burden associated with complying
with the test procedure, resulting in estimates lower than the $1
million HI suggested. DOE notes that the estimated costs in the IRFA
were based on the construction of a facility capable of conducting the
DOE test procedure for pumps within the scope of the rulemaking.
Because of a lack of information on existing testing facilities in the
industry, as well as the potential variability in the capabilities of
these existing facilities, DOE assumed that no manufacturers would have
existing test capabilities and all manufacturers would have to
construct new test laboratories in order to comply with the test
procedure. DOE also assumed in the IRFA that no third party
laboratories were available to conduct testing in accordance with the
DOE test procedure. 80 FR 17586, 17631 (April 1, 2015).
DOE recognizes that many pump manufacturers already have pump test
facilities and conduct pump testing as part of an existing
manufacturing quality control process, to develop pump performance
information for new and existing products, and to demonstrate the
performance of specific pump units for customers. As such, for the
purposes of estimating testing burden associated with this test
procedure final rule, DOE has revised the baseline assumptions
regarding the existing test lab capabilities of manufacturers and has
estimated the incremental burden associated with just those test
procedure requirements that would not typically exist in current
manufacturer facilities. DOE describes these updated assumptions and
analysis in section IV.B.3.
Regarding the capabilities of existing test laboratories, HI
commented that it disagrees with DOE's assumption in the NOPR that the
use of a non-calibrated test motor and VFD with a torque meter would be
the most common and least costly approach for testing bare pumps in
accordance with the proposed DOE test procedure. (HI, No. 0008 at p.
24) Additionally, HI noted that it did not find anything in the NOPR
preamble that mentions recertification requirements. (HI, No. 0008 at
p. 25)
DOE acknowledges comments from HI on the underestimated cost
estimates to build a pump testing facility and suggestions of
components. DOE disagrees with HI that a VFD control would not be the
most common approach for testing pumps in accordance with the DOE test
procedure. DOE conducted a literature search for pump configurations
and determined that almost all controls available to be paired with
pumps are VFD controls. DOE also reiterates that the estimates used in
the IRFA were not meant to be the least costly for manufacturers. The
cost estimates for constructing a test facility were meant to be the
most burdensome on manufacturers to show the most costly approach to
building a test facility. DOE acknowledges the comment from HI
regarding recertification requirements and clarifies that the estimates
for recertification requirements in the April 2015 pumps test procedure
NOPR IRFA are for pumps which have been redesigned to capture market
preferences or other customer requirements. DOE estimates that 10
percent of basic models per manufacturer will be redesigned and tested
each year, and the Department has included the costs of testing newly
redesigned pumps in this DOE test procedure final rule regulatory
flexibility analysis (see section IV.B.3). To further clarify these
costs, DOE has removed the terminology used in the April 2015 pumps
test procedure NOPR IRFA regarding recertification that was unclear.
Instead, in this final rule, DOE uses redesigned and tested to refer to
pumps that would require new certifications each year, as their energy
performance will have changed as a result of the equipment redesign.
DOE notes that only those pump models for which the energy consumption
characteristics have changed necessitate a new basic model
certification and that pump models whose energy consumption
characteristics have not changed do not need to be recertified.
[[Page 4139]]
HI agreed that, for most pump models, only physical testing of the
underlying bare pump model is required, and subsequent rating for that
bare pump sold with a motor or motor and continuous control can be
based on calculations only. (HI, No. 0008 at p. 24) HI also stated that
all pumps listed within the scope as outlined in the term sheet can be
evaluated in accordance with the methodology described in the April
2015 pumps test procedure NOPR if the corrected equation presented by
DOE at the April 29, 2015 public meeting is used. (HI, No. 0008 at p.
24) HI stated that it could not comment on the number of pump models
per manufacturer that would be required to use the test (wire-to-water)
method to certify pump performance based on a lack of data, but stated
that 100 percent of pumps would need to be tested to certify because of
the new testing requirements and sampling provisions. (HI, No. 0008 at
p. 25)
DOE appreciates the comment from HI that only physical testing of
the underlying bare pump is required and that subsequent configurations
can be based on calculations. DOE agrees with HI that 100 percent of
pumps would need to be tested to certify compliance with a proposed PEI
standard, if adopted in a standards final rule. This is true for
PEICL and PEIVL because these values cannot be
calculated without the finalized C-Values from the energy conservation
standards rulemaking. In addition, the PERCL and
PERVL metrics contain specific assumptions regarding the
representative performance of pumps and pump components that are not
part of the industry's current test methods. However, as noted in
section III.F, DOE recognizes that manufacturers already make some
representations regarding the performance of relevant pumps (e.g., pump
efficiency, BEP efficiency, and pump total head or volume rate of flow
(flow rate) at BEP and full impeller) based on testing using test
standards consistent with or similar to HI 40.6-2014, which DOE is
incorporating by reference as the basis for the DOE test procedure. As
such, DOE notes that, while all PEICL, PEIVL,
PERCL, and PERVL ratings must be newly-generated,
some existing test data that were collected consistent with the methods
DOE is incorporating by reference into the DOE test procedure may be
used, provided manufacturers are confident any such values are
equivalent to those that would be generated using the new DOE test
procedure.
Quantity of Manufacturers Potentially Affected
To calculate the burden associated with testing pumps on aper
manufacturer or per model basis, DOE collected information on the
number of manufacturers in the pumps industry, and the numbers of
models per manufacturer. DOE then focused this analysis on the small
entities as part of the regulatory flexibility analysis. To determine
which pump manufacturers were small entities, DOE referenced the Small
Business Administration (SBA) size threshold for ``Pump and Pumping
Equipment Manufacturing'' (North American Industry Classification
System code 333911).\73\ The SBA sets a threshold of 500 employees or
less for an entity to be considered as a small business for this
category, as established at 13 CFR 121.201.
---------------------------------------------------------------------------
\73\ See https://www.sba.gov/sites/default/files/files/Size_Standards_Table.pdf.
---------------------------------------------------------------------------
In the April 2015 pumps test procedure NOPR, DOE conducted a
focused inquiry into small business manufacturers of equipment covered
by this rulemaking. DOE identified 68 distinct manufacturers of covered
pump products sold in the U.S. DOE then analyzed those 68 to determine
which would be considered a small business. After removing entities
that are foreign owned or operated, DOE determined that there were 25
small businesses in the analysis. These 25 companies represent 29
percent of pump manufacturers with facilities in the United States. 80
FR 17586, 17629 (April 1, 2015).
In response to DOE's assessment of the number of small
manufacturers subject to the pumps test procedure rule, HI commented
that the HI organization currently has 106 member companies (pump
manufacturers and associate members) and is aware of more entities
within the market. HI believes that the identification of 68 distinct
pump manufacturers in the U.S. is low. (HI, No. at pp. 23-24)
DOE appreciates the comment from HI that there are more
manufacturers in the pump manufacturing industry that are not included
in this analysis. DOE notes that although HI might have associate
members, if the member does not manufacture a pump, the associate
member is not part of the analysis. During its market survey, DOE used
available public information to identify potential small manufacturers.
DOE's research involved the review of individual company Web sites and
marketing research tools (e.g., Dun and Bradstreet reports, Manta,
Hoovers) to create a list of companies that manufacture pumps covered
by this rulemaking. DOE also contacted HI to obtain information about
pump manufacturing companies that participate in the national
association. DOE identified 86 potential businesses of covered pump
products sold in the U.S., but reduced that number to 68 by determining
which businesses were located in the United States. From these
manufacturers, DOE eliminated 29 from the analysis because they had
more than 500 employees. DOE removed an additional 16 manufacturers
because they either had foreign parent companies or had domestic parent
companies with 500 or more employees. After removing entities that are
foreign owned or operated, DOE determined that there were 25 small
businesses to investigate for this analysis. The regulatory flexibility
analysis investigated manufacturers who manufacture pumps within the
scope of this rulemaking, are considered a small business according to
SBA standards, and are not foreign-owned or operated. Thus, there are
fewer manufacturers analyzed in the regulatory flexibility analysis
than are present in the industry.
In summary, DOE agrees with HI that 68 distinct manufacturers is
low on an industry-wide basis, but that is because the number was
reduced by other criteria before being presented in the April 2015
pumps test procedure NOPR. DOE notes that HI is not disagreeing with
DOE's assessment of the quantity of small businesses, but rather the
potential size of total pump manufacturers in the U.S. Following the
April 2015 pumps test procedure NOPR, DOE has not identified any more
(or different) manufacturers that meet the criteria (domestic
headquarters, not owned by another entity, meets the SBA threshold of
500 employees or fewer) to be considered a small business. Therefore,
in this final rule, DOE maintains the quantity of 25 small businesses
for purposes of analyzing the potential burden. Within the 25 small
businesses, DOE has, however, identified an additional manufacturer
that produces pumps that are within the scope of this rulemaking and
have included this manufacturer in this DOE pumps test procedure final
rule regulatory flexibility analysis (raising the total from 15 to 16).
Manufacturer Sales To Assess Burden
In the April 2015 pumps test procedure NOPR, DOE used average sales
to assist in assessing the potential burden. 80 FR 17586, 17629 (April
1, 2015). HI commented that it has no alternative to offer other than
using the
[[Page 4140]]
average sales, but noted that it does not understand what DOE is
presenting in Table IV.2 [of the April 2015 pumps test procedure NOPR].
(HI, No. 0008 at p. 25)
DOE agrees with HI that there is no better alternative to using
average sales as the financial indicator for assessing the burden on
manufacturers. DOE notes that Table IV.2 in the April 2015 pumps test
procedure NOPR displays the results of the initial regulatory
flexibility analysis. 80 FR 17586, 17633 (April 1, 2015). The columns
indicate the range of number of employees in each row; the number of
small businesses within each employee size range; the average number of
basic models produced by manufacturers in each employee size range; and
the average sales of the manufacturers in each employee size range as
determined from available data sources. Using the estimated potential
testing burden, number of basic models, and the average annual sales,
DOE determined the potential burden as a percentage of sales of each
group of small businesses (as defined by ranges of numbers of
employees). Because DOE maintains that this final rule has no
incremental burden associated with it when viewed as a stand-alone
rulemaking, DOE is only presenting the estimates of the costs
associated with testing equipment consistent with the requirements of
this test procedure final rule, as would be required to certify
compliance with potential energy conservation standards. As such, this
table of impacts on manufacturers as a result of conducting this test
procedure is no longer included in this regulatory flexibility
analysis.
HI commented that there will be a significant burden on both small
and large entities and believes that this estimated value would vary
depending on the size of the pump manufacturer. (HI, No. 0008 at pp.
25-26)
DOE agrees that the estimated burden may vary based on the size of
the manufacturers if energy conservation standards are promulgated. DOE
only considered the aggregate effects on small manufacturers of
developing certified ratings for applicable pump models for the
purposes of making representations regarding the energy use of such
equipment or certifying compliance to DOE under any future energy
conservation standards. The estimated burden of conducting the DOE test
procedure presented in the April 2015 pumps test procedure NOPR showed
that, as the number of employees increased, so did the number of basic
models and average sales. As a result, as the number of employees
increased, the average estimated burden, as a percentage of average
annual sales, decreased. Based on this analysis, it is likely that the
burden may vary based on the size of manufacturer.
DOE cannot confirm HI's comment that there will be a significant
burden on large manufacturers because the regulatory flexibility
analysis aims to assess whether there is a significant economic impact
on a substantial number of small entities. DOE did not assess the
impact of the rule on large entities. However, DOE notes that the
parallel energy conservation standards rulemaking includes a full
manufacturer impact analysis (Docket No. EERE-2011-BT-STD-0031).
3. Revised Assessment of Burden Associated With This Test Procedure
Final Rule
In the initial regulatory flexibility analysis portion of the April
2015 pumps test procedure NOPR, DOE estimated the most burdensome costs
for manufacturers to conduct the DOE test procedure. In the initial
regulatory flexibility analysis DOE recognized that, because testing is
not currently required or standardized, testing facilities may vary
widely from one pump manufacturer to another. For the purposes of
estimating testing burden in the initial regulatory flexibility
analysis, DOE estimated the burden associated with a situation where a
given pump manufacturer did not have existing test facilities at all
and would be required to construct such facilities to test equipment in
accordance with the test procedure. In light of comments received
regarding the burden associated with testing, DOE revised the analysis
and gathered additional information to better characterize the expected
burden associated with testing basic models in accordance with the DOE
test procedure.
DOE is analyzing the effect of the combined burden associated with
both the test procedure and energy conservation standards rulemakings
in the manufacturer impact analysis performed as part of the energy
conservation standards rulemaking (see docket EERE-2011-BT-STD-0031).
The costs described in the following subsection are referenced in the
manufacturer impact analysis in the pumps energy conservation standards
rulemaking to estimate the burden associated with testing. However, DOE
reiterates that the estimates provided serve only to provide
information about the possible burden manufacturers may incur while
testing pumps using this DOE test procedure; they do not represent
actual burden incurred by the industry as there is no incremental
burden associated with this test procedure final rule until and unless
the associated pumps energy conservation standards final rule is
published.
The DOE test procedure will require pump manufacturers to conduct
the calculation-based method or the testing-based method, depending on
the type and configuration of the pump(s) being tested. DOE is adopting
the less burdensome calculation-based test method as the required test
method for bare pumps, and as optional test methods for pumps other
than bare pumps. This includes pumps sold with motors that are covered
by DOE's electric motor energy conservation standards or submersible
motors and pumps sold with either of these two motor styles that are
also sold with continuous controls (see section III.E for a more
thorough description of the applicability of the calculation-based
approach to different pump configurations). DOE is also requiring that
manufacturers use a testing-based method where pumps are sold either
with motors that are not covered by DOE's electric motor energy
conservation standards (except submersible motors) or with non-
continuous controls.
Both the calculation-based method and the testing-based method
require physical testing of pumps at some level and, as such, utilize a
similar basic testing facility. DOE recognizes that all manufacturers,
regardless of HI membership, have access to test facilities to be able
to produce pump curves that characterize the performance of their
equipment. As such, DOE estimated that all manufacturers would be able
to conduct the DOE test procedure in an available test facility.
Sixteen of 25 small manufacturers identified in DOE's survey of
manufacturers produce pumps that fall within the scope of this
rulemaking and would be required to perform testing; the other 9
produce pump types that are not within the scope of pumps for which
this test procedure is applicable. Of the 16 manufacturers that produce
pumps within the scope of this rulemaking, 8 are members of HI
according to their listing on HI's Web site.\74\
---------------------------------------------------------------------------
\74\ See https://www.pumps.org/member_companies.aspx.
---------------------------------------------------------------------------
As member companies of HI, DOE assumes that manufacturers with
pumps within the scope of this test procedure would test pumps in
accordance with HI's most current industry testing standards. That is,
DOE assumes that manufacturers that are HI members already conduct
testing in accordance
[[Page 4141]]
with HI 40.6-2014. In HI 40.6-2014, manufacturers are required to test
their pumps in an ISO 9906 Grade 2B test facility, which is the same
grade test facility prescribed in HI 14.6-2011. Because the
calculation-based method described in this test procedure is equivalent
to HI 40.6-2014, as recommended by the Working Group, manufacturers who
are members of HI would already be capable of testing pumps in
accordance to the testing-based method in this test procedure. There is
no incremental cost to calibrate measurement instrumentation for these
manufacturers because HI 40.6-2014 prescribes calibration intervals for
all instruments in the test facility. The testing-based method in this
test procedure requires electrical measurement equipment capable of
measuring true RMS current, true RMS voltage, and real power up to at
least the 40th harmonic of fundamental supply source frequency with an
accuracy level of 2.0 percent of full scale when measured
at the fundamental supply source frequency, as discussed in section
III.C.2.e. Electrical equipment accuracy of 2.0 percent of
reading is consistent with the value specified in section 40.6.3.2.3 of
HI 40.6-2014. Therefore, the is no incremental cost to conduct testing
for HI member companies when testing pumps pursuant to the testing-
based method or the calculation-based method.
Manufacturers who are not members of HI need to purchase electrical
measurement equipment with 2.0 percent accuracy to conduct
the testing-based method of the DOE test procedure. DOE determined that
the average cost of such equipment is approximately $5,218.42 based on
a review of available products on the market. Unlike the manufacturers
who are HI members, the non-HI manufacturers may not perform regular
equipment calibration and, as such, will incur an additional cost to
calibrate the instruments in the test facility. DOE assumed that each
testing facility would need to calibrate the instrumentation used in
the test loop as specified in HI 40.6-2014 appendix D. The flowmeter,
torque sensor, and power quality meter all should be calibrated once a
year. The pressure transducer should be calibrated every 4 months and a
laser tachometer should be calibrated every 3 years. These
calibrations, together, cost a manufacturer about $1,241.67 per year.
DOE analyzed the estimated burden for 7 years for the 16 small
manufacturers that produce pumps within the scope of the DOE test
procedure. DOE used an analysis period of 7 years based on the
assumption that the machinery qualifies for a 7-year depreciation
schedule under the Modified Accelerated Cost Recovery System
(MACRS).\75\ The average, and representative, of the likely burden to
manufacturers is $6,334 for the capital costs associated with
constructing a test facility capable of conducting the DOE test
procedure. This burden ranges between $0 and $12,668.
---------------------------------------------------------------------------
\75\ Department of the Treasury, Internal Revenue Service. How
to Depreciate Property. IRS Pub. 926.
---------------------------------------------------------------------------
Both methods of the test procedure require test personnel to set
up, conduct, and remove each pump in accordance with that procedure.
DOE estimated the cost of labor using the median hourly wage of $41.44
for the overall category of an engineer.\76\ Including fringe benefits,
which are estimated to be nominally 30 percent of total compensation,
the total hourly cost to an employer is estimated to be $53.87.\77\
---------------------------------------------------------------------------
\76\ U.S. Department of Labor, Bureau of Labor Statistics. 2012.
National Occupational Employment and Wage Estimates. Washington, DC
Available at https://www.bls.gov/oes/2012/may/oes_nat.htm#17-0000.
\77\ U.S. Department of Labor, Bureau of Labor Statistics. 2014.
Employer Costs for Employee Compensation--Management, Professional,
and Related Employees. Washington, DC Available at: https://www.bls.gov/news.release/pdf/ecec.pdf.
---------------------------------------------------------------------------
Based on conversations with test engineers, DOE estimates it would
take between 1 and 2 hours of an engineer's time to complete the test
procedure per unit tested, which would result in a cost of $53.87 to
$107.74 per unit based on an engineer's labor rate of $53.87 per hour.
DOE estimates that setting up and removing the pumps from the test
stand would require 2 to 6 hours of the engineer's time depending on
the size of the pump and any other fittings that need to be configured
to enable testing, resulting in a cost between $107.74 to $323.22 per
unit based on the labor rate of $53.87 per hour for an engineer. The
total cost of testing a pump, including setup, tests, and takedown
ranges between $161.61 and $430.96 per unit. DOE estimates that the
time required to conduct the calculation-based method of test would be
the same as the time required to conduct the test-based method (wire-
to-water test).
DOE also estimates that pump manufacturers would redesign covered
pump models or introduce new pump models each year. As such, DOE
estimates that a certain portion of the pump models that a given pump
manufacturer offers for sale would need to be tested each year. DOE
estimates that approximately 10 percent of manufacturers' unique pump
models would need to be tested each year.
DOE amortized the capital costs against the recurring burden of
testing pumps described in this analysis for each small manufacturer
identified to produce pumps covered under the scope of the DOE test
procedure. DOE notes that the labor component represents the majority
of the overall cost associated with testing, while the much more
variable capital costs are only 23 percent of the total test cost. The
representative amortized burden for testing each unit of a basic model
is $561.16. As discussed in the sampling provisions in section III.G,
this test procedure will require manufacturers to test at least two
units of each pump basic model to develop a certified rating. This
results in an average cost of $1,122.32 to test two units of each basic
model.
While analyzing the potential burdens of testing pumps in-house,
DOE recognized that the price per basic model was higher for some
manufacturers than for others. For manufacturers with higher costs of
testing per basic model may elect to send their pumps to a third-party
test facility to mitigate these costs. DOE anticipates that third party
testing facilities will update their test facilities to be able to
provide testing for pump manufacturers in accordance with the DOE test
procedure. Based on market research and discussions with third party
test lab personnel, DOE estimates that testing pumps in a third party
test facility according to the DOE test procedure will cost
approximately $2,500 per unit.
4. Calculator Comments
Wilo indicated that one problem is that DOE is not responsible for
providing tools to determine compliance, so each manufacturer would be
responsible for creating its own potentially erroneous evaluation tool.
(Wilo, No. 0044 at p. 3-4) HI requested that DOE share the latest
version of the PEI calculator with the pump industry as an easy means
of determining whether their products fall within or outside the scope
of the efficiency levels specified in the rulemaking. (HI, No. 0002 at
p. 1) HI also requested that DOE provide a PEI calculator so that all
calculations for PEI are performed exactly the same way by all members
of the pump industry, government agencies and interested parties. (HI,
No. 0007 at p. 2) HI commented that the calculator could be used to
report data to interested utilities. (HI, No. 0007 at p. 10) HI also
commented that the complexity of the rating systems will cause a
significant burden on all manufacturers to develop
[[Page 4142]]
a tool which quickly evaluates product. This is even more important for
small and medium-sized companies that may not have the resources to
develop such an analytic tool on their own. (HI, No. 0008 at p. 2)
In response to the comments submitted by Wilo and HI, DOE made the
PEI calculator available on the pumps test procedure rulemaking Web
site.\78\ Under the provisions in this pumps test procedure final rule,
the PEI calculations must be performed using measured values--that is,
using results from testing actual pumps in accordance with the proposed
test method and sampling plan. The PEI calculator provided to the
public is not considered an Alternative Efficiency Determination Method
(AEDM) by the Department and is not to be used to simulate or estimate
the efficiency of a pump. DOE has provided this ``calculator'' as a
convenience at the request of interested parties. DOE notes that
manufacturers should consult section III.B of this final rule and the
adopted regulatory text at 10 CFR 431.464 and appendix A of subpart Y
for the formulas for calculating PEI and should not rely on this
spreadsheet. DOE also notes that while this calculator is an excel-
based version of the calculations in the test procedure proposal, DOE
did not rely on this document to develop the proposal itself.
---------------------------------------------------------------------------
\78\ https://www1.eere.energy.gov/buildings/appliance_standards/product.aspx/productid/44#testprocedures.
---------------------------------------------------------------------------
Based on the estimates presented, DOE believes that the test
procedure amendments will not have a significant economic impact on a
substantial number of small entities, and the preparation of a final
regulatory flexibility analysis is not required. DOE will transmit the
certification and supporting statement of factual basis to the Chief
Counsel for Advocacy of the Small Business Administration for review
under 5 U.S.C. 605(b).
C. Review Under the Paperwork Reduction Act of 1995
All collections of information from the public by a Federal agency
must receive prior approval from OMB. DOE has established regulations
for the certification and recordkeeping requirements for covered
consumer products and industrial equipment. 10 CFR part 429, subpart B.
DOE published a NOPR proposing energy conservation standards for pumps
on April 24, 2015. 80 FR 22938. In an application to renew the OMB
information collection approval for DOE's certification and
recordkeeping requirements, DOE included an estimated burden for
manufacturers of pumps in case DOE ultimately sets energy conservation
standards for this equipment. OMB has approved the revised information
collection for DOE's certification and recordkeeping requirements. 80
FR 5099 (January 30, 2015). In the April 2015 pumps test procedure
NOPR, DOE estimated that it will take each respondent approximately 30
hours total per company per year to comply with the certification and
recordkeeping requirements based on 20 hours of technician/technical
work and 10 hours clerical work to actually submit the Compliance and
Certification Management System templates. 80 FR 17586, 17633 (April
15, 2015).
In response to DOE's April 2015 pump test procedure NOPR, HI
commented that the hours shown are low and will vary by the number of
basic models covered. (HI, No. at p. 26)
DOE appreciates the comment submitted by HI regarding the burden
estimate to comply with the proposed recordkeeping requirements. DOE
recognizes that recordkeeping burden may vary substantially based on
company preferences and practices as well as the number of basic models
each manufacturer will test. However, DOE maintains that, on average,
it will take manufacturers approximately 30 hours to comply with the
certification and recordkeeping requirements. In addition, DOE notes
that, while this test procedure rulemaking includes recordkeeping
requirements that are associated with executing and maintaining the
test data for this equipment, the certification requirements would be
established in a final rule establishing energy conservation standards
for pumps.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
In this final rule, DOE amends its test procedure for pumps. DOE
has determined that this rule falls into a class of actions that are
categorically excluded from review under the National Environmental
Policy Act of 1969 (42 U.S.C. 4321 et seq.) and DOE's implementing
regulations at 10 CFR part 1021. Specifically, this rule amends an
existing rule without affecting the amount, quality or distribution of
energy usage, and, therefore, will not result in any environmental
impacts. Thus, this rulemaking is covered by Categorical Exclusion A5
under 10 CFR part 1021, subpart D, which applies to any rulemaking that
interprets or amends an existing rule without changing the
environmental effect of that rule. Accordingly, neither an
environmental assessment nor an environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 4,
1999), imposes certain requirements on agencies formulating and
implementing policies or regulations that preempt State law or that
have Federalism implications. The Executive Order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States and
to carefully assess the necessity for such actions. The Executive Order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have Federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. 65 FR 13735. DOE examined this final
rule and determined that it will not have a substantial direct effect
on the States, on the relationship between the national government and
the States, or on the distribution of power and responsibilities among
the various levels of government. EPCA governs and prescribes Federal
preemption of State regulations as to energy conservation for the
products that are the subject of this final rule. States can petition
DOE for exemption from such preemption to the extent, and based on
criteria, set forth in EPCA. (42 U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
Eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically
[[Page 4143]]
requires that Executive agencies make every reasonable effort to ensure
that the regulation: (1) Clearly specifies the preemptive effect, if
any; (2) clearly specifies any effect on existing Federal law or
regulation; (3) provides a clear legal standard for affected conduct
while promoting simplification and burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately defines key terms; and (6)
addresses other important issues affecting clarity and general
draftsmanship under any guidelines issued by the Attorney General.
Section 3(c) of Executive Order 12988 requires Executive agencies to
review regulations in light of applicable standards in sections 3(a)
and 3(b) to determine whether they are met or it is unreasonable to
meet one or more of them. DOE has completed the required review and
determined that, to the extent permitted by law, this final rule meets
the relevant standards of Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (UMRA)
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. Public Law 104-4, sec. 201 (codified at 2 U.S.C. 1531).
For a regulatory action resulting in a rule that may cause the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector of $100 million or more in any one year
(adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The UMRA also requires a Federal agency to
develop an effective process to permit timely input by elected officers
of State, local, and Tribal governments on a proposed ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect small governments. On March 18, 1997,
DOE published a statement of policy on its process for
intergovernmental consultation under UMRA. 62 FR 12820; also available
at https://energy.gov/gc/office-general-counsel. DOE examined this final
rule according to UMRA and its statement of policy and determined that
the rule contains neither an intergovernmental mandate nor a mandate
that may result in the expenditure of $100 million or more in any year,
so these requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This final rule will not have any impact on the autonomy or integrity
of the family as an institution. Accordingly, DOE has concluded that it
is not necessary to prepare a Family Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights'' 53 FR 8859 (March 18, 1988), that this regulation will not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (Feb. 22, 2002), and
DOE's guidelines were published at 67 FR 62446 (Oct. 7, 2002). DOE has
reviewed this final rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OMB
a Statement of Energy Effects for any significant energy action. A
``significant energy action'' is defined as any action by an agency
that promulgated or is expected to lead to promulgation of a final
rule, and that: (1) Is a significant regulatory action under Executive
Order 12866, or any successor order; and (2) is likely to have a
significant adverse effect on the supply, distribution, or use of
energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any significant energy action, the
agency must give a detailed statement of any adverse effects on energy
supply, distribution, or use if the regulation is implemented, and of
reasonable alternatives to the action and their expected benefits on
energy supply, distribution, and use.
This regulatory action is not a significant regulatory action under
Executive Order 12866. Moreover, it would not have a significant
adverse effect on the supply, distribution, or use of energy, nor has
it been designated as a significant energy action by the Administrator
of OIRA. Therefore, it is not a significant energy action, and,
accordingly, DOE has not prepared a Statement of Energy Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of the
Federal Energy Administration Act of 1974, as amended by the Federal
Energy Administration Authorization Act of 1977. (15 U.S.C. 788; FEAA)
Section 32 essentially provides in relevant part that, where a proposed
rule authorizes or requires use of commercial standards, the notice of
proposed rulemaking must inform the public of the use and background of
such standards. In addition, section 32(c) requires DOE to consult with
the Attorney General and the Chairman of the Federal Trade Commission
(FTC) concerning the impact of the commercial or industry standards on
competition.
The final rule incorporates by reference the testing methods
contained in HI 40.6-2014, ``Methods for Rotodynamic Pump Efficiency
Testing,'' except section 40.6.5.3, ``Test report;'' section A.7,
``Testing at temperatures exceeding 30 [deg]C (86 14;[deg]F);'' and
appendix B, ``Reporting of test results.'' In addition, the final
rule's definitions incorporate by reference the following standards:
(1) Sections 1.1, ``types and nomenclature,'' and 1.2.9,
``rotodynamic pump icons,'' of the 2014 version of ANSI/HI 1.1-1.2-
2014, ``American National Standard for Rotodynamic Centrifugal Pumps
for Nomenclature and Definitions;''
(2) section 2.1, ``types and nomenclature,'' of the 2014 version of
ANSI/HI 2.1-2.2, ``American National Standard for Rotodynamic Vertical
Pumps of Radial, Mixed, and Axial Flow Types for Nomenclature and
Definitions.''
(3) FM Class Number 1319, ``Approval Standard for Centrifugal Fire
Pumps
[[Page 4144]]
(Horizontal, End Suction Type),'' approved January 2015.
(4) NFPA 20-2016, ``Standard for the Installation of Stationary
Pumps for Fire Protection,'' approved 2016.
(5) ANSI/UL 448-2013, ``Standard for Safety Centrifugal Stationary
Pumps for Fire-Protection Service,'' approved 2013.
While this test procedure is not exclusively based on these
industry testing standards, some components of the DOE test procedure
adopt definitions, test parameters, measurement techniques, and
additional calculations from them without amendment. The Department has
evaluated these industry testing standards and is unable to conclude
whether they would fully comply with the requirements of section 32(b)
of the FEAA, (i.e., that they were developed in a manner that fully
provides for public participation, comment, and review). DOE has
consulted with both the Attorney General and the Chairman of the FTC
about the impact on competition of using the methods contained in this
standard, as well as the effects of the rule in general, if
promulgated. Regarding any impact on competition that the adopted test
procedure may have, the DOJ reviewed the April 2015 pumps test
procedure NOPR, attended the April 2015 NOPR public meeting, and
consulted with members of the industry in preparing their comments and
conclusions regarding any anticompetitive effects of the pumps test
procedure. In response to the proposed test procedure, DOJ commented
that it is not able to determine whether or not the proposed test
procedure (or associated energy conservation standard) will lessen
competition within the industry. However, DOJ noted that it is
concerned about the possibility of anticompetitive effects resulting
from the burden and expense of compliance. (DOJ, No. 14 at p. 2) In
response to DOJ's concern regarding the burden of conducting the test
procedure, DOE has revised several of the requirements, which DOE
believes will mitigate DOJ's (and manufacturers') concerns. DOE
addresses these concerns regarding the burden related to testing pumps
in accordance with the test procedure in section IV.B.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will report to Congress on the
promulgation of this rule before its effective date. The report will
state that it has been determined that the rule is not a ``major rule''
as defined by 5 U.S.C. 804(2).
N. Description of Materials Incorporated by Reference
In this final rule, DOE is incorporating by reference specific
sections from a method of test published by HI, titled ``Methods for
Rotodynamic Pump Efficiency Testing.'' Specifically, the test procedure
codified by this final rule references HI 40.6-2014, except section
40.6.5.3, ``Test report;'' section A.7, ``Testing at temperatures
exceeding 30 [deg]C (86[emsp14][deg]F);'' and appendix B, ``Reporting
of test results.'' HI 40.6-2014 is an industry-accepted standard used
to specify methods of testing for determining the head, flow rate, pump
power input, driver power input, pump power output, and other relevant
parameters necessary to determine the PEICL or
PEIVL of applicable pumps, as described in this final rule.
In addition, the final rule's definitions incorporate by reference
the following sections of the following standards:
(1) Sections 1.1, ``types and nomenclature,'' and 1.2.9,
``rotodynamic pump icons,'' of the 2014 version of ANSI/HI 1.1-1.2-
2014, ``American National Standard for Rotodynamic Centrifugal Pumps
for Nomenclature and Definitions;'' and
(2) section 2.1, ``types and nomenclature,'' of the 2014 version of
ANSI/HI 2.1-2.2, ``American National Standard for Rotodynamic Vertical
Pumps of Radial, Mixed, and Axial Flow Types for Nomenclature and
Definitions.''
(3) FM Class Number 1319, ``Approval Standard for Centrifugal Fire
Pumps (Horizontal, End Suction Type),'' approved January 2015.
(4) NFPA 20-2016, ``Standard for the Installation of Stationary
Pumps for Fire Protection,'' approved 2015.
(5) ANSI/UL 448-2013, ``Standard for Safety Centrifugal Stationary
Pumps for Fire-Protection Service,'' ANSI approved 2013.
ANSI/HI 1.1-1.2-2014 and ANSI/HI 2.1-2.2-2014 describe and define
specific pump characteristics relevant to the differentiation of pump
categories and configurations when applying the DOE test procedure. The
FM, NFPA, and ANSI/UL standards describe the relevant technical
characteristics and testing requirements to certify certain pumps as
fire pumps.
Copies of all HI standards may be purchased from the Hydraulic
Institute at 6 Campus Drive, First Floor North, Parsippany, NJ, 07054-
4406, or by going to www.pumps.org.
Copies of FM Class Number 1319 can be obtained from: FM Global,
1151 Boston-Providence Turnpike, P.O. Box 9102, Norwood, MA 02062,
(781) 762-4300. www.fmglobal.com.
Copies of NFPA 20-2016 can be obtained from: the National Fire
Protection Association, 1 Batterymarch Park, Quincy, MA 02169, (617)
770-3000. www.nfpa.org.
Copies of ANSI/UL 448-2013 can be obtained from: UL, 333 Pfingsten
Road, Northbrook, IL 60062, (847) 272-8800. https://ul.com.
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this final
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Imports, Intergovernmental relations,
Small businesses.
10 CFR Part 431
Administrative practice and procedure, Confidential business
information, Energy conservation, Imports, Incorporation by reference,
Intergovernmental relations, Small businesses.
Issued in Washington, DC, on December 30, 2015.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
For the reasons stated in the preamble, DOE amends parts 429 and
431 of Chapter II, subchapter D of Title 10, Code of Federal
Regulations as set forth below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317.
0
2. In Sec. 429.2 revise paragraph (a) to read as follows:
Sec. 429.2 Definitions.
(a) The definitions found in Sec. Sec. 430.2, 431.2, 431.62,
431.72, 431.82, 431.92, 431.102, 431.132, 431.152, 431.172, 431.192,
431.202, 431.222, 431.242, 431.262, 431.282, 431.292, 431.302, 431.322,
431.442 and 431.462 of this chapter apply for purposes of this part.
* * * * *
Sec. 429.11 [Amended]
0
3. In paragraphs (a) and (b) remove ``429.54'' and add ``429.62'' in
its place.
0
4. Add Sec. 429.59 to read as follows:
[[Page 4145]]
Sec. 429.59 Pumps.
(a) Determination of represented value. Manufacturers must
determine the represented value, which includes the certified rating,
for each basic model by testing (which includes the calculation-based
methods in the test procedure), in conjunction with the following
sampling provisions. Manufacturers must update represented values to
account for any change in the applicable motor standards in Sec.
431.25 of this chapter and certify amended values as of the next annual
certification.
(1) Units to be tested. The requirements of Sec. 429.11 are
applicable to pumps; and for each basic model, a sample of sufficient
size shall be randomly selected and tested to ensure that--
(i) Any value of the constant or variable load pump energy index or
other measure of energy consumption must be greater than or equal to
the higher of:
(A) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TR25JA16.025
and x is the sample mean; n is the number of samples; and
xi is the maximum of the ith sample;
Or,
(B) The upper 95 percent confidence limit (UCL) of the true mean
divided by 1.05, where:
[GRAPHIC] [TIFF OMITTED] TR25JA16.026
and x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.95 is the t statistic for a 95
percent one-tailed confidence interval with n-1 degrees of freedom
(from appendix A to subpart B of part 429);
and
(ii) Any measure of energy efficiency of a basic model must be less
than or equal to the lower of:
(A) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TR25JA16.027
and x is the sample mean; n is the number of samples; and
xi is the maximum of the ith sample;
Or,
(B) The lower 95 percent confidence limit (LCL) of the true mean
divided by 0.95, where:
[GRAPHIC] [TIFF OMITTED] TR25JA16.028
and x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.95 is the t statistic for a 95
percent one-tailed confidence interval with n-1 degrees of freedom
(from appendix A of subpart B).
(b) [Reserved]
Sec. 429.70 [Amended]
0
5. Amend Sec. 429.70(a) by removing ``429.54'' and adding ``429.62''
in its place.
0
6. In Sec. 429.71, add paragraph (d) to read as follows:
Sec. 429.71 Maintenance of records.
* * * * *
(d) When considering if a pump is subject to energy conservation
standards under part 431 of this chapter, DOE may need to determine if
a pump was designed and constructed to the requirements set forth in
Military Specifications: MIL-P-17639F, MIL-P-17881D, MIL-P-17840C, MIL-
P-18682D, or MIL-P-18472G. In this case, a manufacturer must provide
DOE with copies of the original design and test data that were
submitted to appropriate design review agencies, as required by MIL-P-
17639F, MIL-P-17881D, MIL-P-17840C, MIL-P-18682D, or MIL-P-18472G.
Military specifications and standards are available for review at
https://everyspec.com/MIL-SPECS.
Sec. 429.72 [Amended]
0
7. Amend Sec. 429.72(a) by removing ``429.54'' and adding in its place
``429.62''.
Sec. 429.102 [Amended]
0
8. Amend Sec. 429.102(a)(1) by removing ``429.54'' and adding in its
place ``429.62''.
0
9. Section 429.110 is amended by:
0
a. Redesignating paragraphs (e)(1)(iv) through (vi) as (e)(1)(v)
through (vii), respectively; and
0
b. Adding a new paragraph (e)(1)(iv).
The addition reads as follows:
Sec. 429.110 Enforcement testing.
* * * * *
(e) * * *
(1) * * *
(iv) For pumps, DOE will use an initial sample size of not more
than four units and will determine compliance based on the arithmetic
mean of the sample.
* * * * *
0
10. Section 429.134 is amended by adding paragraph (h) to read as
follows:
Sec. 429.134 Product-specific enforcement provisions.
* * * * *
(h) Pumps. (1) The volume rate of flow (flow rate) at BEP and
nominal speed of rotation of each tested unit of the basic model will
be measured pursuant to the test requirements of Sec. 431.464 of this
chapter, where the value of volume rate of flow (flow rate) at BEP and
nominal speed of rotation certified by the manufacturer will be treated
as the expected BEP flow rate. The results of the measurement(s) will
be compared to the value of volume rate of flow (flow rate) at BEP and
nominal speed of rotation certified by the manufacturer. The certified
volume rate of flow (flow rate) at BEP and nominal speed of rotation
will be considered valid only if the measurement(s) (either the
measured volume rate of flow (flow rate) at BEP and nominal speed of
rotation for a single unit sample or the average of the measured flow
rates for a multiple unit sample) is within five percent of the
certified volume rate of flow (flow rate) at BEP and nominal speed of
rotation.
(i) If the representative value of volume rate of flow (flow rate)
at BEP and nominal speed of rotation is found to be valid, the measured
volume rate of flow (flow rate) at BEP and nominal speed of rotation
will be used in subsequent calculations of constant load pump energy
rating (PERCL) and constant load pump energy index
(PEICL) or variable load pump energy rating
(PERVL) and variable load pump energy index
(PEIVL) for that basic model.
(ii) If the representative value of volume rate of flow (flow rate)
at BEP and nominal speed of rotation is found to be invalid, the mean
of all the measured volume rate of flow (flow rate) at BEP and nominal
speed of rotation values determined from the tested unit(s) will serve
as the new expected BEP flow rate and the unit(s) will be retested
until such time as the measured volume rate of flow (flow rate) at BEP
and nominal speed of rotation is within 5 percent of the expected BEP
flow rate.
(2) DOE will test each pump unit according to the test method
specified by the manufacturer in the certification report submitted
pursuant to Sec. 429.59(b).
PART 431--ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND
INDUSTRIAL EQUIPMENT
0
11. The authority citation for part 431 continues to read as follows:
Authority: 42 U.S.C. 6291-6317.
0
12. Add subpart Y to part 431 to read as follows:
Subpart Y--Pumps
Sec.
[[Page 4146]]
431.461 Purpose and scope.
431.462 Definitions.
431.463 Materials incorporated by reference.
431.464 Test procedure for measuring and determining energy
consumption of pumps.
Appendix A to Subpart Y of Part 431--Uniform Test Method for the
Measurement of Energy Consumption of Pumps
Subpart Y--Pumps
Sec. 431.461 Purpose and scope.
This subpart contains definitions, test procedures, and energy
conservation requirements for pumps, pursuant to Part A-1 of Title III
of the Energy Policy and Conservation Act, as amended, 42 U.S.C. 6311-
6317.
Sec. 431.462 Definitions.
The following definitions are applicable to this subpart, including
appendix A. In cases where there is a conflict, the language of the
definitions adopted in this section takes precedence over any
descriptions or definitions found in the 2014 version of ANSI/HI 1.1-
1.2, ``American National Standard for Rotodynamic Centrifugal Pumps for
Nomenclature and Definitions'' (ANSI/HI 1.1-1.2-2014) (incorporated by
reference, see Sec. 431.463), or the 2014 version of ANSI/HI 2.1-2.2,
``American National Standard for Rotodynamic Vertical Pumps of Radial,
Mixed, and Axial Flow Types for Nomenclature and Definitions'' (ANSI/HI
2.1-2.2-2014) (incorporated by reference, see Sec. 431.463). In cases
where definitions reference design intent, DOE will consider marketing
materials, labels and certifications, and equipment design to determine
design intent.
Bare pump means a pump excluding mechanical equipment, driver, and
controls.
Basic model means all units of a given class of pump manufactured
by one manufacturer, having the same primary energy source, and having
essentially identical electrical, physical, and functional (or
hydraulic) characteristics that affect energy consumption, energy
efficiency, water consumption, or water efficiency; except that:
(1) For RSV and ST pumps, all variations in numbers of stages of
the bare pump must be considered a single basic model;
(2) Pump models for which the bare pump differs in impeller
diameter, or impeller trim, may be considered a single basic model; and
(3) Pump models for which the bare pump differs in number of stages
or impeller diameter and which are sold with motors (or motors and
controls) of varying horsepower may only be considered a single basic
model if:
(i) for ESCC, ESFM, IL, and RSV pumps, each motor offered in the
basic model has a nominal full load motor efficiency rated at the
Federal minimum (see the current table for NEMA Design B motors at 10
CFR 431.25) or the same number of bands above the Federal minimum for
each respective motor horsepower (see Table 3 of Appendix A to Subpart
Y of Part 431); or
(ii) for ST pumps, each motor offered in the basic model has a full
load motor efficiency at the default nominal full load submersible
motor efficiency shown in Table 2 of appendix A to subpart Y of part
431 or the same number of bands above the default nominal full load
submersible motor efficiency for each respective motor horsepower (see
Table 3 of Appendix A to Subpart Y of Part 431).
Best efficiency point (BEP) means the pump hydraulic power
operating point (consisting of both flow and head conditions) that
results in the maximum efficiency.
Bowl diameter means the maximum dimension of an imaginary straight
line passing through and in the plane of the circular shape of the
intermediate bowl of the bare pump that is perpendicular to the pump
shaft and that intersects the outermost circular shape of the
intermediate bowl of the bare pump at both of its ends, where the
intermediate bowl is as defined in ANSI/HI 2.1-2.2-2014.
Clean water pump means a pump that is designed for use in pumping
water with a maximum non-absorbent free solid content of 0.016 pounds
per cubic foot, and with a maximum dissolved solid content of 3.1
pounds per cubic foot, provided that the total gas content of the water
does not exceed the saturation volume, and disregarding any additives
necessary to prevent the water from freezing at a minimum of
14[emsp14][deg]F.
Close-coupled pump means a pump in which the motor shaft also
serves as the impeller shaft for the bare pump.
Continuous control means a control that adjusts the speed of the
pump driver continuously over the driver operating speed range in
response to incremental changes in the required pump flow, head, or
power output.
Control means any device that can be used to operate the driver.
Examples include, but are not limited to, continuous or non-continuous
controls, schedule-based controls, on/off switches, and float switches.
Driver means the machine providing mechanical input to drive a bare
pump directly or through the use of mechanical equipment. Examples
include, but are not limited to, an electric motor, internal combustion
engine, or gas/steam turbine.
Dry rotor pump means a pump in which the motor rotor is not
immersed in the pumped fluid.
End suction close-coupled (ESCC) pump means a close-coupled, dry
rotor, end suction pump that has a shaft input power greater than or
equal to 1 hp and less than or equal to 200 hp at BEP and full impeller
diameter and that is not a dedicated-purpose pool pump. Examples
include, but are not limited to, pumps within the specified horsepower
range that comply with ANSI/HI nomenclature OH7, as described in ANSI/
HI 1.1-1.2-2014.
End suction frame mounted/own bearings (ESFM) pump means a
mechanically-coupled, dry rotor, end suction pump that has a shaft
input power greater than or equal to 1 hp and less than or equal to 200
hp at BEP and full impeller diameter and that is not a dedicated-
purpose pool pump. Examples include, but are not limited to, pumps
within the specified horsepower range that comply with ANSI/HI
nomenclature OH0 and OH1, as described in ANSI/HI 1.1-1.2-2014.
End suction pump means a single-stage, rotodynamic pump in which
the liquid enters the bare pump in a direction parallel to the impeller
shaft and on the side opposite the bare pump's driver-end. The liquid
is discharged through a volute in a plane perpendicular to the shaft.
Fire pump means a pump that is compliant with NFPA 20-2016
(incorporated by reference, see Sec. 431.463), ``Standard for the
Installation of Stationary Pumps for Fire Protection,'' and is either:
(1) UL listed under ANSI/UL 448-2013 (incorporated by reference,
see Sec. 431.463), ``Standard for Safety Centrifugal Stationary Pumps
for Fire-Protection Service,'' or
(2) FM Global (FM) approved under the January 2015 edition of FM
Class Number 1319, ``Approval Standard for Centrifugal Fire Pumps
(Horizontal, End Suction Type),'' (incorporated by reference, see Sec.
431.463).
Full impeller diameter means the maximum diameter impeller with
which a given pump basic model is distributed in commerce.
Horizontal motor means a motor that requires the motor shaft to be
in a horizontal position to function as designed, as specified in the
manufacturer literature.
In-line (IL) pump means a pump that is either a twin-head pump or a
single-stage, single-axis flow, dry rotor, rotodynamic pump that has a
shaft
[[Page 4147]]
input power greater than or equal to 1 hp and less than or equal to 200
hp at BEP and full impeller diameter, in which liquid is discharged
through a volute in a plane perpendicular to the shaft. Such pumps do
not include pumps that are mechanically coupled or close-coupled, have
a pump power output that is less than or equal to 5 hp at BEP at full
impeller diameter, and are distributed in commerce with a horizontal
motor. Examples of in-line pumps include, but are not limited to, pumps
within the specified horsepower range that comply with ANSI/HI
nomenclature OH3, OH4, or OH5, as described in ANSI/HI 1.1-1.2-2014.
Magnet driven pump means a pump in which the bare pump is isolated
from the motor via a containment shell and torque is transmitted from
the motor to the bare pump via magnetic force. The motor shaft is not
physically coupled to the impeller or impeller shaft.
Mechanical equipment means any component of a pump that transfers
energy from the driver to the bare pump.
Mechanically-coupled pump means a pump in which the bare pump has
its own impeller shaft and bearings and so does not rely on the motor
shaft to serve as the impeller shaft.
Non-continuous control means a control that adjusts the speed of a
driver to one of a discrete number of non-continuous preset operating
speeds, and does not respond to incremental reductions in the required
pump flow, head, or power output.
Prime-assist pump means a pump that:
(1) Is designed to lift liquid that originates below the centerline
of the pump inlet;
(2) Requires no manual intervention to prime or re-prime from a
dry-start condition; and
(3) Includes a device, such as a vacuum pump or air compressor and
venturi eductor, to remove air from the suction line in order to
automatically perform the prime or re-prime function at any point
during the pump's operating cycle.
Pump means equipment designed to move liquids (which may include
entrained gases, free solids, and totally dissolved solids) by physical
or mechanical action and includes a bare pump and, if included by the
manufacturer at the time of sale, mechanical equipment, driver, and
controls.
Radially split, multi-stage, vertical, in-line diffuser casing
(RSV) pump means a vertically suspended, multi-stage, single axis flow,
dry rotor, rotodynamic pump:
(1) That has a shaft input power greater than or equal to 1 hp and
less than or equal to 200 hp at BEP and full impeller diameter and at
the number of stages required for testing and
(2) In which liquid is discharged in a place perpendicular to the
impeller shaft; and
(3) For which each stage (or bowl) consists of an impeller and
diffuser;
(4) For which no external part of such a pump is designed to be
submerged in the pumped liquid; and
(5) Examples include, but are not limited to, pumps complying with
ANSI/HI nomenclature VS8, as described in ANSI/HI 2.1-2.2-2014.
Rotodynamic pump means a pump in which energy is continuously
imparted to the pumped fluid by means of a rotating impeller,
propeller, or rotor.
Self-priming pump means a pump that:
(1) Is designed to lift liquid that originates below the centerline
of the pump inlet;
(2) Contains at least one internal recirculation passage; and
(3) Requires a manual filling of the pump casing prior to initial
start-up, but is able to re-prime after the initial start-up without
the use of external vacuum sources, manual filling, or a foot valve.
Single axis flow pump means a pump in which the liquid inlet of the
bare pump is on the same axis as the liquid discharge of the bare pump.
Submersible turbine (ST) pump means a single-stage or multi-stage,
dry rotor, rotodynamic pump that is designed to be operated with the
motor and stage(s) fully submerged in the pumped liquid; that has a
shaft input power greater than or equal to 1 hp and less than or equal
to 200 hp at BEP and full impeller diameter and at the number of stages
required for testing; and in which each stage of this pump consists of
an impeller and diffuser, and liquid enters and exits each stage of the
bare pump in a direction parallel to the impeller shaft. Examples
include, but are not limited to, pumps within the specified horsepower
range that comply with ANSI/HI nomenclature VS0, as described in ANSI/
HI 2.1-2.2-2014.
Twin head pump means a dry rotor, single-axis flow, rotodynamic
pump that contains two impeller assemblies, which both share a common
casing, inlet, and discharge, and each of which
(1) Contains an impeller, impeller shaft (or motor shaft in the
case of close-coupled pumps), shaft seal or packing, driver (if
present), and mechanical equipment (if present);
(2) Has a shaft input power that is greater than or equal to 1 hp
and less than or equal to 200 hp at best efficiency point (BEP) and
full impeller diameter;
(3) Has the same primary energy source (if sold with a driver) and
the same electrical, physical, and functional characteristics that
affect energy consumption or energy efficiency;
(4) Is mounted in its own volute; and
(5) Discharges liquid through its volute and the common discharge
in a plane perpendicular to the impeller shaft.
Sec. 431.463 Materials incorporated by reference.
(a) General. DOE incorporates by reference the following standards
into subpart Y of part 431. The material listed has been approved for
incorporation by reference by the Director of the Federal Register in
accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Any subsequent
amendment to a standard by the standard-setting organization will not
affect the DOE test procedures unless and until amended by DOE.
Material is incorporated as it exists on the date of the approval and a
notice of any change in the material will be published in the Federal
Register. All approved material is available for inspection at the
National Archives and Records Administration (NARA). For information on
the availability of this material at NARA, call 202-741-6030, or go to:
www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. Also, this material is available for inspection at
U.S. Department of Energy, Office of Energy Efficiency and Renewable
Energy, Building Technologies Program, Sixth Floor, 950 L'Enfant Plaza
SW., Washington, DC 20024, (202) 586-2945, or go to: https://www1.eere.energy.gov/buildings/appliance_standards. These standards can
be obtained from the sources below.
(b) FM. FM Global, 1151 Boston-Providence Turnpike, P.O. Box 9102,
Norwood, MA 02062, (781) 762-4300. www.fmglobal.com.
(1) FM Class Number 1319, ``Approval Standard for Centrifugal Fire
Pumps (Horizontal, End Suction Type),'' January 2015, IBR approved for
Sec. 431.462.
(2) [Reserved]
(c) HI. Hydraulic Institute, 6 Campus Drive, First Floor North,
Parsippany, NJ 07054-4406, 973-267-9700. www.Pumps.org.
(1) ANSI/HI 1.1-1.2-2014, (``ANSI/HI 1.1-1.2-2014''), ``American
National Standard for Rotodynamic Centrifugal Pumps for Nomenclature
and Definitions,'' approved October 30, 2014, section 1.1, ``Types and
[[Page 4148]]
nomenclature,'' and section 1.2.9, ``Rotodynamic pump icons,'' IBR
approved for Sec. 431.462.
(2) ANSI/HI 2.1-2.2-2014, (``ANSI/HI 2.1-2.2-2014''), ``American
National Standard for Rotodynamic Vertical Pumps of Radial, Mixed, and
Axial Flow Types for Nomenclature and Definitions,'' approved April 8,
2014, section 2.1, ``Types and nomenclature,'' IBR approved for Sec.
431.462.
(3) HI 40.6-2014, (``HI 40.6-2014''), ``Methods for Rotodynamic
Pump Efficiency Testing,'' (except section 40.6.5.3, ``Test report;''
Appendix A, section A.7, ``Testing at temperatures exceeding 30 [deg]C
(86[emsp14][deg]F);'' and Appendix B, ``Reporting of test results
(normative);'') copyright 2014, IBR approved for appendix A to subpart
Y of part 431.
(d) NFPA. National Fire Protection Association, 1 Batterymarch
Park, Quincy, MA 02169-7471, (617) 770-3000. www.nfpa.org.
(1) NFPA 20, (``NFPA 20-2016''), ``Standard for the Installation of
Stationary Pumps for Fire Protection,'' 2016 Edition, approved June 15,
2015, IBR approved for Sec. 431.462.
(2) [Reserved]
(e) UL. UL, 333 Pfingsten Road, Northbrook, IL 60062, (847) 272-
8800. ul.com.
(1) UL 448, (``ANSI/UL 448-2013''), ``Standard for Safety
Centrifugal Stationary Pumps for Fire-Protection Service,'' 10th
Edition, June 8, 2007, including revisions through July 12, 2013, IBR
approved for Sec. 431.462.
(2) [Reserved]
Sec. 431.464 Test procedure for measuring and determining energy
consumption of pumps
(a) Scope. This section provides the test procedures for
determining the constant and variable load pump energy index for:
(1) The following categories of clean water pumps:
(i) End suction close-coupled (ESCC);
(ii) End suction frame mounted/own bearings (ESFM);
(iii) In-line (IL);
(iv) Radially split, multi-stage, vertical, in-line casing diffuser
(RSV); and
(v) Submersible turbine (ST) pumps
(2) With the following characteristics:
(i) Flow rate of 25 gpm or greater at BEP and full impeller
diameter;
(ii) Maximum head of 459 feet at BEP and full impeller diameter and
the number of stages required for testing (see section 1.2.2 of
appendix A of this subpart);
(iii) Design temperature range from 14 to 248[emsp14][deg]F;
(iv) Designed to operate with either: (1) a 2- or 4-pole induction
motor, or (2) a non-induction motor with a speed of rotation operating
range that includes speeds of rotation between 2,880 and 4,320
revolutions per minute and/or 1,440 and 2,160 revolutions per minute,
and in either case, the driver and impeller must rotate at the same
speed;
(v) For ST pumps, a 6-inch or smaller bowl diameter; and
(vi) For ESCC and ESFM pumps, a specific speed less than or equal
to 5000 when calculated using U.S. customary units.
(3) Except for the following pumps:
(i) Fire pumps;
(ii) Self-priming pumps;
(iii) Prime-assist pumps;
(iv) Magnet driven pumps;
(v) Pumps designed to be used in a nuclear facility subject to 10
CFR part 50, ``Domestic Licensing of Production and Utilization
Facilities;'' and
(vi) Pumps meeting the design and construction requirements set
forth in Military Specifications: MIL-P-17639F, ``Pumps, Centrifugal,
Miscellaneous Service, Naval Shipboard Use'' (as amended); MIL-P-
17881D, ``Pumps, Centrifugal, Boiler Feed, (Multi-Stage)'' (as
amended); MIL-P-17840C, ``Pumps, Centrifugal, Close-Coupled, Navy
Standard (For Surface Ship Application)'' (as amended); MIL-P-18682D,
``Pump, Centrifugal, Main Condenser Circulating, Naval Shipboard'' (as
amended); and MIL-P-18472G, ``Pumps, Centrifugal, Condensate, Feed
Booster, Waste Heat Boiler, And Distilling Plant'' (as amended).
Military specifications and standards are available for review at
https://everyspec.com/MIL-SPECS.
(b) Testing and calculations. Determine the applicable constant
load pump energy index (PEICL) or variable load pump energy
index (PEIVL) using the test procedure set forth in appendix
A of this subpart Y.
Appendix A to Subpart Y of Part 431--Uniform Test Method for the
Measurement of Energy Consumption of Pumps
Note: Starting on July 25, 2016, any representations made with
respect to the energy use or efficiency of pumps subject to testing
pursuant to 10 CFR 431.464 must be made in accordance with the
results of testing pursuant to this appendix.
I. Test Procedure for Pumps
A. General. To determine the constant load pump energy index
(PEICL) for bare pumps and pumps sold with electric
motors or the variable load pump energy index (PEIVL) for
pumps sold with electric motors and continuous or non-continuous
controls, perform testing in accordance with HI 40.6-2014, except
section 40.6.5.3, ``Test report;'' section A.7, ``Testing at
temperatures exceeding 30 [deg]C (86[emsp14][deg]F);'' and appendix
B, ``Reporting of test results;'' (incorporated by reference, see
Sec. 431.463) with the modifications and additions as noted
throughout the provisions below. Where HI 40.6-2014 refers to
``pump,'' the term refers to the ``bare pump,'' as defined in Sec.
431.462. Also, for the purposes of applying this appendix, the term
``volume per unit time,'' as defined in section 40.6.2, ``Terms and
definitions,'' of HI 40.6-2014 shall be deemed to be synonymous with
the term ``flow rate'' used throughout that standard and this
appendix. In addition, the specifications of section 40.6.4.1 of HI
40.6-2014 do not apply to ST pumps and the performance of ST bare
pumps considers the bowl performance only.
A.1 Scope. Section II of this appendix is applicable to all
pumps and describes how to calculate the pump energy index (section
II.A) based on the pump energy rating for the minimally compliant
reference pump (PERSTD; section II.B) and the constant
load pump energy rating (PERCL) or variable load pump
energy rating (PERVL) determined in accordance with one
of sections III through VII of this appendix, based on the
configuration in which the pump is distributed in commerce and the
applicable testing method specified in sections III through VII and
as described in Table 1 of this appendix.
Table 1--Applicability of Calculation-Based and Testing-Based Test
Procedure Options Based on Pump Configuration
------------------------------------------------------------------------
Pump sub- Applicable test
Pump configuration configuration methods
------------------------------------------------------------------------
Bare Pump................... Bare Pump........... Section III: Test
OR.................. Procedure for Bare
Pump + Single-Phase Pumps.
Induction Motor.
OR..................
Pump + Driver Other
Than Electric Motor.
[[Page 4149]]
Pump + Motor *.............. Pump + Polyphase Section IV: Testing-
Motor Covered by Based Approach for
DOE's Electric Pumps Sold with
Motor Energy Motors
Conservation OR
Standards **. Section V:
OR.................. Calculation-Based
Pump + Submersible Approach for Pumps
Motor. Sold with Motors.
Pump + Motor Not Section IV: Testing-
Covered by DOE's Based Approach for
Electric Motor Pumps Sold with
Energy Conservation Motors.
Standards (Except
Submersible Motors)
** ***.
Pump + Motor + Continuous Pump + Polyphase Section VI: Testing-
Controls. Motor Covered by Based Approach for
OR.......................... DOE's Electric Pumps Sold with
Pump + Motor + Non- Motor Energy Motors and Controls
Continuous Controls. Conservation OR
Standards** + Section VII:
Continuous Control. Calculation-Based
OR.................. Approach for Pumps
Pump + Submersible Sold with Motors
Motor + Continuous Controls.
Control.
Pump + Polyphase Section VI: Testing-
Motor Covered by Based Approach for
DOE's Electric Pumps Sold with
Motor Energy Motors and
Conservation Controls.
Standards** + Non-
Continuous Control.
OR..................
Pump + Submersible
Motor + Non-
Continuous Control.
Pump + Motor Not Section VI: Testing-
Covered by DOE's Based Approach for
Electric Motor Pumps Sold with
Energy Conservation Motors and
Standards (Except Controls.
Submersible Motors)
** *** + Continuous
or Non-Continuous
Controls.
------------------------------------------------------------------------
* Also applies if unit is sold with controls other than continuous or
non-continuous controls (e.g., ON/OFF switches).
** All references to ``Motors Covered by DOE's Electric Motor Energy
Conservation Standards'' refer to those listed at Sec. 431.25(g) of
this chapter.
*** Includes pumps sold with single-phase induction motors.
A.2 Section III of this appendix addresses the test procedure
applicable to bare pumps. This test procedure also applies to pumps
sold with drivers other than motors and pumps sold with single-phase
induction motors.
A.3 Section IV of this appendix addresses the testing-based
approach for pumps sold with motors, which is applicable to all
pumps sold with electric motors, including single-phase induction
motors. This test procedure also applies to pumps sold with controls
other than continuous or non-continuous controls (e.g., on/off
switches).
A.4 Section V of this appendix addresses the calculation-based
approach for pumps sold with motors, which applies to:
(1) Pumps sold with polyphase electric motors regulated by DOE's
energy conservation standards for electric motors at Sec.
431.25(g), and
(2) Pumps sold with submersible motors.
A.5 Section VI of this appendix addresses the testing-based
approach for pumps sold with motors and controls, which is
applicable to all pumps sold with electric motors (including single-
phase induction motors) and continuous or non-continuous controls.
A.6 Section VII of this appendix discusses the calculation-based
approach for pumps sold with motors and controls, which applies to:
(1) Pumps sold with polyphase electric motors regulated by DOE's
energy conservation standards for electric motors at Sec. 431.25(g)
and continuous controls and
(2) Pumps sold with submersible motors and continuous controls.
B. Measurement Equipment. For the purposes of measuring pump
power input, driver power input to the motor or controls, and pump
power output, the equipment specified in HI 40.6-2014 Appendix C
(incorporated by reference, see Sec. 431.463) necessary to measure
head, speed of rotation, flow rate, temperature, torque, and
electrical power must be used and must comply with the stated
accuracy requirements in HI 40.6-2014 Table 40.6.3.2.3 except as
noted in sections III.B, IV.B, V.B, VI.B, and VII.B of this
appendix. When more than one instrument is used to measure a given
parameter, the combined accuracy, calculated as the root sum of
squares of individual instrument accuracies, must meet the specified
accuracy requirements.
C. Test Conditions. Conduct testing at full impeller diameter in
accordance with the test conditions, stabilization requirements, and
specifications of HI 40.6-2014 (incorporated by reference, see Sec.
431.463) section 40.6.3, ``Pump efficiency testing;'' section
40.6.4, ``Considerations when determining the efficiency of a
pump;'' section 40.6.5.4 (including appendix A), ``Test
arrangements;'' and section 40.6.5.5, ``Test conditions.''. For ST
pumps, head measurements must be based on the bowl assembly total
head as described in section A.5 of 40.6-2014 and the pump power
input or driver power input, as applicable, must be based on the
measured input power to the driver or bare pump, respectively;
section 40.6.4.1, ``vertically suspended pumps,'' does not apply to
ST pumps.
C.1 Nominal Speed of Rotation. Determine the nominal speed of
rotation based on the range of speeds of rotation at which the pump
is designed to operate, in accordance with sections I.C.1.1,
I.C.1.2, I.C.1.3, I.C.1.4, or I.C.1.5 of this appendix, as
applicable. When determining the range of speeds at which the pump
is designed to operate, DOE will refer to published data, marketing
literature, and other publically-available information about the
pump model and motor, as applicable.
C.1.1 For pumps sold without motors, select the nominal speed of
rotation based on the speed for which the pump is designed. For bare
pumps designed for speeds of rotation including 2,880 to 4,320
revolutions per minute (rpm), the nominal speed of rotation shall be
3,600 rpm. For bare pumps designed for speeds of rotation including
1,440 to 2,160 rpm, the nominal speed of rotation shall be 1,800
rpm.
C.1.2 For pumps sold with 4-pole induction motors, the nominal
speed of rotation shall be 1,800 rpm.
C.1.3 For pumps sold with 2-pole induction motors, the nominal
speed of rotation shall be 3,600 rpm.
C.1.4 For pumps sold with non-induction motors where the
operating range of the pump and motor includes speeds of rotation
between 2,880 and 4,320 rpm, the nominal speed of rotation shall be
3,600 rpm.
C.1.5 For pumps sold with non-induction motors where the
operating range of the pump and motor includes speeds of rotation
between 1,440 and 2,160 rpm, the nominal speed of rotation shall be
1,800 rpm.
C.2 Multi-stage Pumps. For RSV and ST pumps, perform testing on
the pump with three stages for RSV pumps and nine stages for ST
pumps. If the basic model of pump being tested is only available
with fewer than the required number of stages, test the pump with
the maximum number of stages with which the basic model is
distributed in commerce in the United States. If the basic model of
pump being tested is only available with greater than the required
number of stages, test the pump with the lowest number
[[Page 4150]]
of stages with which the basic model is distributed in commerce in
the United States. If the basic model of pump being tested is
available with both fewer and greater than the required number of
stages, but not the required number of stages, test the pump with
the number of stages closest to the required number of stages. If
both the next lower and next higher number of stages are
equivalently close to the required number of stages, test the pump
with the next higher number of stages.
C.3 Twin Head Pumps. For twin head pumps, perform testing on an
equivalent single impeller IL pump, constructed by incorporating one
of the driver and impeller assemblies of the twin head pump being
rated into an adequate, IL style, single impeller volute and casing.
An adequate, IL style, single impeller volute and casing means a
volute and casing for which any physical and functional
characteristics that affect energy consumption and energy efficiency
are the same to their corresponding characteristics for a single
impeller in the twin head pump volute and casing.
D. Data Collection and Analysis
D.1 Damping Devices. Use of damping devices, as described in
section 40.6.3.2.2 of HI 40.6-2014 (incorporated by reference, see
Sec. 431.463), are only permitted to integrate up to the data
collection interval used during testing.
D.2 Stabilization. Record data at any tested load point only
under stabilized conditions, as defined in HI 40.6-2014 section
40.6.5.5.1 (incorporated by reference, see Sec. 431.463), where a
minimum of two measurements are used to determine stabilization.
D.3 Calculations and Rounding. Normalize all measured data to
the nominal speed of rotation of 3,600 or 1,800 rpm based on the
nominal speed of rotation selected for the pump in section I.C.1 of
this appendix, in accordance with the procedures specified in
section 40.6.6.1.1 of HI 40.6-2014 (incorporated by reference, see
Sec. 431.463). Except for the ``expected BEP flow rate,'' all terms
and quantities refer to values determined in accordance with the
procedures set forth in this appendix for the rated pump. Perform
all calculations using raw measured values without rounding. Round
PERCL and PERVL to three significant digits,
and round PEICL, and PEIVL values, as
applicable, to the hundredths place (i.e., 0.01).
D.4 Pumps with BEP at Run Out.
Test pumps for which the expected BEP corresponds to a volume
rate of flow that is within 20 percent of the expected maximum flow
rate at which the pump is designed to operate continuously or safely
(i.e., pumps with BEP at run-out) in accordance with the test
procedure specified in this appendix, but with the following
exceptions:
(1) Use the following seven flow points for determination of BEP
in sections III.D, IV.D, V.D, VI.D, and VII.D of this appendix
instead of those specified in those sections: 40, 50, 60, 70, 80,
90, and 100 percent of the expected.
(2) Use flow points of 60, 70, 80, 90, and 100 percent of the
expected maximum flow rate of the pump to determine pump power input
or driver power input at the specified load points in section
III.E.1.1, IV.E.1, V.E.1.1, VI.E.1, and VII.E.1.1 of this appendix
instead of those specified in those sections.
(3) To determine of PERCL and PERSTD, use
load points of 65, 90, and 100 percent of the BEP flow rate
determined with the modified flow points specified in this section
I.D.4 of this appendix instead of 75, 100, and 110 percent of BEP
flow.
II. Calculation of the Pump Energy Index
A. Determine the PEI of each tested pump based on the
configuration in which it is sold, as follows:
A.1. For pumps rated as bare pumps or pumps sold with motors,
determine the PEICL using the following equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.029
Where:
PEICL = the pump energy index for a constant load (hp),
PERCL = the pump energy rating for a constant load (hp),
determined in accordance with either section III (for bare pumps,
pumps sold with single-phase induction motors, and pumps sold with
drivers other than electric motors), section IV (for pumps sold with
motors and rated using the testing-based approach), or section V
(for pumps sold with motors and rated using the calculation-based
approach) of this appendix, and
PERSTD = the PERCL for a pump that is
minimally compliant with DOE's energy conservation standards with
the same flow and specific speed characteristics as the tested pump
(hp), as determined in accordance with section II.B of this
appendix.
A.2 For pumps rated as pumps sold with motors and continuous
controls or non-continuous controls, determine the PEIVL
using the following equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.030
Where:
PEIVL = the pump energy index for a variable load,
PERVL = the pump energy rating for a variable load (hp)
determined in accordance with section VI (for pumps sold with motors
and continuous or non-continuous controls rated using the testing-
based approach) or section VII of this appendix (for pumps sold with
motors and continuous controls rated using the calculation-based
approach), and
PERSTD = the PERCL for a pump that is
minimally compliant with DOE's energy conservation standards with
the same flow and specific speed characteristics as the tested pump
(hp), as determined in accordance with section II.B of this
appendix.
B. Determine the pump energy rating for the minimally compliant
reference pump (PERSTD), according to the following
equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.031
Where:
PERSTD = the PERCL for a pump that is
minimally compliant with DOE's energy conservation standards with
the same flow and specific speed characteristics as the tested pump
(hp),
[omega]i = 0.3333,
Pi\in,m\ = calculated driver power input to the motor at
load point i for the minimally compliant pump (hp), calculated in
accordance with section II.B.1of this appendix, and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
B.1. Determine the driver power input at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate as
follows:
[GRAPHIC] [TIFF OMITTED] TR25JA16.032
Where:
Pi\in,m\ = driver power input to the motor at load point
i (hp),
Pi = pump power input to the bare pump at load point i
(hp), calculated in accordance with section II.B.1.1 of this
appendix,
Li = the part load motor losses at load point i (hp),
calculated in accordance with section II.B.1.2 of this appendix, and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
B.1.1. Determine the pump power input to the minimally compliant
pump at each load point corresponding to 75, 100, or 110 percent of
the BEP flow rate as follows:
[GRAPHIC] [TIFF OMITTED] TR25JA16.033
Where:
Pi = pump power input to the bare pump at load point i
(hp),
[[Page 4151]]
[alpha]i = 0.947 for 75 percent of the BEP flow rate,
1.000 for 100 percent of the BEP flow rate, and 0.985 for 110
percent of the BEP flow rate;
Pu,i = the pump power output at load point i of the
tested pump (hp), as determined in accordance with section
II.B.1.1.2 of this appendix;
[eta]pump,STD = the minimally compliant pump efficiency
(%), calculated in accordance with section II.B.1.1.1 of this
appendix; and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
B.1.1.1 Calculate the minimally compliant pump efficiency based
on the following equation:
[eta]pump,STD = -0.8500 x
ln(Q100[percnt])\2\ -0.3800 x ln(Ns) x
ln(Q100[percnt]) - 11.480 x ln(Ns)\2\ + 17.800
x ln(Q100[percnt]) + 179.80 x ln(Ns) - (C +
555.60
Where:
[eta]pump,STD = minimally compliant pump efficiency (%),
Q100[percnt] = the BEP flow rate of the tested
pump at full impeller and nominal speed of rotation (gpm),
Ns = specific speed of the tested pump determined in accordance with
section II.B.1.1.1.1 of this appendix, and
C = the appropriate C-value for the category and nominal speed of
rotation of the tested pump, as listed at Sec. 431.466.
B.1.1.1.1 Determine the specific speed of the rated pump using
the following equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.034
Where:
Ns = specific speed,
nsp = the nominal speed of rotation (rpm),
Q100[percnt] = the measured BEP flow rate of
the tested pump at full impeller and nominal speed of rotation
(gpm),
H100[percnt] = pump total head at 100 percent
of the BEP flow rate of the tested pump at full impeller and nominal
speed of rotation (ft), and
S = the number of stages with which the pump is being rated.
B.1.1.2 Determine the pump power output at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate using
the following equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.035
Where:
Pu,i = the measured pump power output at load point i of
the tested pump (hp),
Qi = the measured flow rate at load point i of the tested
pump (gpm),
Hi = pump total head at load point i of the tested pump
(ft),
SG = the specific gravity of water at specified test conditions,
which is equivalent to 1.00, and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
B.1.2 Determine the motor part load losses at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate as
follows:
Li = Lfull x yi
Where:
Li = part load motor losses at load point i (hp),
Lfull = motor losses at full load (hp), as determined in
accordance with section II.B.1.2.1 of this appendix,
yi = part load loss factor at load point i determined in
accordance with section II.B.1.2.2 of this appendix, and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
B.1.2.1 Determine the full load motor losses using the
appropriate motor efficiency value and horsepower as shown in the
following equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.036
Where:
Lfull = motor losses at full load (hp),
MotorHP = the motor horsepower as determined in accordance with
section II.B.1.2.1.1 of this appendix (hp), and
[eta]motor,full = the default nominal full load motor
efficiency as determined in accordance with section II.B.1.2.1.2 of
this appendix (%).
B.1.2.1.1 Determine the motor horsepower as follows:
For bare pumps other than ST pumps, the motor
horsepower is determined as the horsepower rating listed in Table 2
of this appendix that is either equivalent to, or the next highest
horsepower greater than, the pump power input to the bare pump at
120 percent of the BEP flow rate of the tested pump.
For ST bare pumps, the motor horsepower is determined
as the horsepower rating listed in Table 2 of this appendix that, is
either equivalent to, or the next highest horsepower greater than,
the pump power input to the bare pump at 120 percent of the BEP flow
rate of the tested pump divided by a service factor of 1.15.
For pumps sold with motors, pumps sold with motors and
continuous controls, or pumps sold with motors and non-continuous
controls, the motor horsepower is the rated horsepower of the motor
with which the pump is being tested.
B.1.2.1.2 Determine the default nominal full load motor
efficiency as described in section II.B.1.2.1.2.1 of this appendix
for pumps other than ST pumps or II.B.1.2.1.2.2 of this appendix for
ST pumps.
B.1.2.1.2.1. For pumps other than ST pumps, the default nominal
full load motor efficiency is the minimum of the nominal full load
motor efficiency standards (open or enclosed) from the table
containing the current energy conservation standards for NEMA Design
B motors at Sec. 431.25, with the number of poles relevant to the
speed at which the pump is being tested (see section I.C.1 of this
appendix) and the motor horsepower determined in section
II.B.1.2.1.1 of this appendix.
B.1.2.1.2.2. For ST pumps, the default nominal full load motor
efficiency is the default nominal full load submersible motor
efficiency listed in Table 2 of this appendix, with the number of
poles relevant to the speed at which the pump is being tested (see
section I.C.1 of this appendix) and the motor horsepower determined
in section II.B.1.2.1.1 of this appendix.
B.1.2.2 Determine the part load loss factor at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate as
follows:
[GRAPHIC] [TIFF OMITTED] TR25JA16.037
Where:
yi = the part load loss factor at load point i,
Pi = pump power input to the bare pump at load point i
(hp),
MotorHP = the motor horsepower (hp), as determined in accordance
with section II.B.1.2.1.1 of this appendix,
[[Page 4152]]
[GRAPHIC] [TIFF OMITTED] TR25JA16.038
III. Test Procedure for Bare Pumps
A. Scope. This section III applies only to:
(1) Bare pumps,
(2) Pumps sold with drivers other than electric motors, and
(3) Pumps sold with single-phase induction motors.
B. Measurement Equipment. The requirements regarding measurement
equipment presented in section I.B of this appendix apply to this
section III, and in addition, when testing pumps using a calibrated
motor:
(1) Electrical measurement equipment must be capable of
measuring true RMS current, true RMS voltage, and real power up to
the 40th harmonic of fundamental supply source frequency, and
(2) Any instruments used to measure a particular parameter
specified in paragraph (1) must have a combined accuracy of 2.0 percent of the measured value at the fundamental supply
source frequency, where combined accuracy is the root sum of squares
of individual instrument accuracies.
C. Test Conditions. The requirements regarding test conditions
presented in section I.C of this appendix apply to this section III.
When testing pumps using a calibrated motor the following conditions
also apply to the mains power supplied to the motor:
(1) Maintain the voltage within 5 percent of the
rated value of the motor,
(2) Maintain the frequency within 1 percent of the
rated value of the motor,
(3) Maintain the voltage unbalance of the power supply within
3 percent of the rated values of the motor, and
(2) Maintain total harmonic distortion below 12 percent
throughout the test.
D. Testing BEP for the Pump. Determine the best efficiency point
(BEP) of the pump as follows:
D.1. Adjust the flow by throttling the pump without changing the
speed of rotation of the pump and conduct the test at a minimum of
the following seven flow points: 40, 60, 75, 90, 100, 110, and 120
percent of the expected BEP flow rate of the pump at the nominal
speed of rotation, as specified in HI 40.6-2014, except section
40.6.5.3, section A.7, and appendix B (incorporated by reference,
see Sec. 431.463).
D.2. Determine the BEP flow rate as the flow rate at the
operating point of maximum pump efficiency on the pump efficiency
curve, as determined in accordance with section 40.6.6.3 of HI 40.6-
2014 (incorporated by reference, see Sec. 431.463), where the pump
efficiency is the ratio of the pump power output divided by the pump
power input, as specified in Table 40.6.2.1 of HI 40.6-2014,
disregarding the calculations provided in section 40.6.6.2.
E. Calculating the Constant Load Pump Energy Rating. Determine
the PERCL of each tested pump using the following
equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.039
Where:
PERCL = the pump energy rating for a constant load (hp),
[omega]i = 0.3333,
Piin,m = calculated driver power input to the
motor at load point i (hp), as determined in accordance with section
III.E.1 of this appendix, and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
E.1 Determine the driver power input at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate as
follows:
[GRAPHIC] [TIFF OMITTED] TR25JA16.040
Where:
Pi\in,m\ = driver power input to the motor at load point
i (hp),
Pi = pump power input to the bare pump at load point i
(hp), as determined in section III.E.1.1 of this appendix,
Li = the part load motor losses at load point i (hp), as
determined in accordance with section III.E.1.2 of this appendix,
and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
E.1.1 Determine the pump power input at 75, 100, 110, and 120
percent of the BEP flow rate by employing a least squares regression
to determine a linear relationship between the pump power input at
the nominal speed of rotation of the pump and the measured flow rate
at the following load points: 60, 75, 90, 100, 110, and 120 percent
of the expected BEP flow rate. Use the linear relationship to
determine the pump power input at the nominal speed of rotation for
the load points of 75, 100, 110, and 120 percent of the BEP flow
rate.
E.1.2 Determine the motor part load losses at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate as
follows:
Li = Lfull x yi
Where:
Li = motor losses at load point i (hp),
Lfull = motor losses at full load (hp), as determined in
accordance with section III.E.1.2.1 of this appendix,
yi = loss factor at load point i as determined in
accordance with section III.E.1.2.2 of this appendix, and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
E.1.2.1 Determine the full load motor losses using the
appropriate motor efficiency value and horsepower as shown in the
following equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.041
Where:
Lfull = motor losses at full load (hp);
MotorHP = the motor horsepower (hp), as determined in accordance
with section II.E.1.2.1.1 of this appendix, and
[eta]motor,full = the default nominal full load motor
efficiency (%), as determined in accordance with section
III.E.1.2.1.2 of this appendix.
E.1.2.1.1 Determine the motor horsepower as follows:
For bare pumps other than ST pumps, determine the motor
horsepower by selecting the horsepower rating listed in Table 2 of
this appendix that is either equivalent to, or the next highest
horsepower greater than, the pump power input to the bare pump at
120 percent of the BEP flow rate of the tested pump.
For ST bare pumps, determine the motor horsepower by
selecting the horsepower rating listed in Table 2 of this appendix
that, is either equivalent to, or the next highest horsepower
greater than, the pump power input to the bare pump at 120 percent
of the BEP flow rate of the tested pump divided by a service factor
of 1.15.
For pumps sold with motors, pumps sold with motors and
continuous controls, or
[[Page 4153]]
pumps sold with motors and non-continuous controls, the motor
horsepower is the rated horsepower of the motor with which the pump
is being tested.
E.1.2.1.2 Determine the default nominal full load motor
efficiency as described in section III.E.1.2.1.2.1 of this appendix
for pumps other than ST pumps or III.E.1.2.1.2.2. of this appendix
for ST pumps.
E.1.2.1.2.1. For pumps other than ST pumps, the default nominal
full load motor efficiency is the minimum of the nominal full load
motor efficiency standards (open or enclosed) from the table
containing the current energy conservation standards for NEMA Design
B motors at Sec. 431.25, with the number of poles relevant to the
speed at which the pump is being tested (see section I.C.1 of this
appendix) and the motor horsepower determined in section
III.E.1.2.1.1 of this appendix.
E.1.2.1.2.2. For ST pumps, the default nominal full load motor
efficiency is the default nominal full load submersible motor
efficiency listed in Table 2 of this appendix, with the number of
poles relevant to the speed at which the pump is being tested (see
section I.C.1 of this appendix) and the motor horsepower determined
in section III.E.1.2.1.1 of this appendix;
E.1.2.2 Determine the loss factor at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate as
follows:
[GRAPHIC] [TIFF OMITTED] TR25JA16.042
Where:
yi = the part load loss factor at load point i,
Pi = pump power input to the bare pump at load point i
(hp), as determined in accordance with section III.E.1.1 of this
appendix,
MotorHP = as determined in accordance with section III.E.1.2.1 of
this appendix (hp),
[GRAPHIC] [TIFF OMITTED] TR25JA16.043
IV. Testing-Based Approach for Pumps Sold With Motors
A. Scope. This section IV applies only to pumps sold with
electric motors, including single-phase induction motors.
B. Measurement Equipment. The requirements regarding measurement
equipment presented in section I.B of this appendix apply to this
section IV, and in addition, the electrical measurement equipment
must:
(1) Be capable of measuring true RMS current, true RMS voltage,
and real power up to the 40th harmonic of fundamental supply source
frequency, and
(2) For all instruments used to measure a given parameter, have
a combined accuracy of 2.0 percent of the measured value
at the fundamental supply source frequency, where combined accuracy
is the root sum of squares of individual instrument accuracies.
C. Test Conditions. The requirements regarding test conditions
presented in section I.C of this appendix apply to this section IV.
The following conditions also apply to the mains power supplied to
the motor:
(1) Maintain the voltage within 5 percent of the
rated value of the motor,
(2) Maintain the frequency within 1 percent of the
rated value of the motor,
(3) Maintain the voltage unbalance of the power supply within
3 percent of the rated values of the motor, and
(4) Maintain total harmonic distortion below 12 percent
throughout the test.
D. Testing BEP for the Pump. Determine the BEP of the pump as
follows:
D.1 Adjust the flow by throttling the pump without changing the
speed of rotation of the pump to a minimum of seven flow points: 40,
60, 75, 90, 100, 110, and 120 percent of the expected BEP flow rate
of the pump at the nominal speed of rotation, as specified in HI
40.6-2014, except section 40.6.5.3, section A.7, and appendix B
(incorporated by reference, see Sec. 431.463).
D.2. Determine the BEP flow rate as the flow rate at the
operating point of maximum overall efficiency on the pump efficiency
curve, as determined in accordance with section 40.6.6.3 of HI 40.6-
2014 (incorporated by reference, see Sec. 431.463), where the
overall efficiency is the ratio of the pump power output divided by
the driver power input, as specified in Table 40.6.2.1 of HI 40.6-
2014, disregarding the calculations provided in section 40.6.6.2.
E. Calculating the Constant Load Pump Energy Rating. Determine
the PERCL of each tested pump using the following
equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.044
Where:
PERCL = the pump energy rating for a constant load (hp),
[omega]i = 0.3333,
Piin = measured driver power input to the
motor at load point i (hp) for the tested pump as determined in
accordance with section IV.E.1 of this appendix, and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
E.1 Determine the driver power input at 75, 100, and 110 percent
of the BEP flow rate by employing a least squares regression to
determine a linear relationship between the driver power input at
the nominal speed of rotation of the pump and the measured flow rate
at the following load points: 60, 75, 90, 100, 110, and 120 percent
of the expected BEP flow rate. Use the linear relationship to
determine the driver power input at the nominal speed of rotation
for the load points of 75, 100, and 110 percent of the BEP flow
rate.
V. Calculation-Based Approach for Pumps Sold With Motors
A. Scope. This section V can only be used in lieu of the test
method in section IV of this appendix to calculate the index for
pumps sold with motors listed in section V.A.1 or V.A.2 of this
appendix.
A.1 Pumps sold with motors subject to DOE's energy conservation
standards for polyphase electric motors at Sec. 431.25(g), and
A.2. Pumps sold with submersible motors.
A.3. Pumps sold with motors not listed in sections V.A.1 or
V.A.2 of this appendix cannot use this section V and must apply the
test method in section IV of this appendix.
B. Measurement Equipment. The requirements regarding measurement
equipment presented in section I.B of this appendix apply to this
section V, and in addition, when testing pumps using a calibrated
motor electrical measurement equipment must:
(1) Be capable of measuring true RMS current, true RMS voltage,
and real power up
[[Page 4154]]
to the 40th harmonic of fundamental supply source frequency, and
(2) For all instruments used to measure a given parameter, have
a combined accuracy of 2.0 percent of the measured value
at the fundamental supply source frequency, where combined accuracy
is the root sum of squares of individual instrument accuracies.
C. Test Conditions. The requirements regarding test conditions
presented in section I.C of this appendix apply to this section V.
When testing pumps using a calibrated motor the following conditions
also apply to the mains power supplied to the motor:
(1) Maintain the voltage within 5 percent of the
rated value of the motor,
(2) Maintain the frequency within 1 percent of the
rated value of the motor,
(3) Maintain the voltage unbalance of the power supply within
3 percent of the rated values of the motor, and
(4) Maintain total harmonic distortion below 12 percent
throughout the test.
D. Testing BEP for the Bare Pump. Determine the best efficiency
point (BEP) of the pump as follows:
D.1 Adjust the flow by throttling the pump without changing the
speed of rotation of the pump to a minimum of seven flow points: 40,
60, 75, 90, 100, 110, and 120 percent of the expected BEP flow rate
of the pump at the nominal speed of rotation, as specified in HI
40.6-2014, except section 40.6.5.3, section A.7, and appendix B
(incorporated by reference, see Sec. 431.463).
D.2. Determine the BEP flow rate as the flow rate at the
operating point of maximum pump efficiency on the pump efficiency
curve, as determined in accordance with section 40.6.6.3 of HI 40.6-
2014 (incorporated by reference, see Sec. 431.463), where pump
efficiency is the ratio of the pump power output divided by the pump
power input, as specified in Table 40.6.2.1 of HI 40.6-2014 and the
calculations provided in section 40.6.6.2 are to be disregarded.
E. Calculating the Constant Load Pump Energy Rating. Determine
the PERCL of each tested pump using the following
equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.045
Where:
PERCL = the pump energy rating for a constant load (hp),
[omega]i = 0.3333,
Piin,m = calculated driver power input to the
motor at load point i for the tested pump as determined in
accordance with section V.E.1 of this appendix (hp), and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
E.1 Determine the driver power input at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate as
follows:
[GRAPHIC] [TIFF OMITTED] TR25JA16.046
Where:
Pi\in,m\ = driver power input to the motor at load point
i (hp),
Pi = pump power input to the bare pump at load point i,
as determined in section V.E.1.1 of this appendix (hp),
Li = the part load motor losses at load point i as
determined in accordance with section V.E.1.2 of this appendix (hp),
and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
E.1.1 Determine the pump power input at 75, 100, 110, and 120
percent of the BEP flow rate by employing a least squares regression
to determine a linear relationship between the pump power input at
the nominal speed of rotation of the pump and the measured flow rate
at the following load points: 60, 75, 90, 100, 110, and 120 percent
of the expected BEP flow rate. Use the linear relationship to
determine the pump power input at the nominal speed of rotation for
the load points of 75, 100, 110, and 120 percent of the BEP flow
rate.
E.1.2 Determine the motor part load losses at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate as
follows:
Li = Lfull x Yi
Where:
Li = motor losses at load point i (hp),
Lfull = motor losses at full load as determined in
accordance with section V.E.1.2.1 of this appendix (hp),
yi = part load loss factor at load point i as determined
in accordance with section V.E.1.2.2 of this appendix, and
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate.
E.1.2.1 Determine the full load motor losses using the
appropriate motor efficiency value and horsepower as shown in the
following equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.047
Where:
Lfull = motor losses at full load (hp),
MotorHP = the horsepower of the motor with which the pump model is
being tested (hp), and
[eta]motor,full = the represented nominal full load motor
efficiency (i.e., nameplate/DOE-certified value) or default nominal
full load submersible motor efficiency as determined in accordance
with section V.E.1.2.1.1 of this appendix (%).
E.1.2.1.1 For pumps sold with motors other than submersible
motors, determine the represented nominal full load motor efficiency
as described in section V.E.1.2.1.1.1 of this appendix. For pumps
sold with submersible motors determine the default nominal full load
submersible motor efficiency as described in section V.E.1.2.1.1.2
of this appendix.
E.1.2.1.1.1. For pumps sold with motors other than submersible
motors, the represented nominal full load motor efficiency is that
of the motor with which the given pump model is being tested, as
determined in accordance with the DOE test procedure for electric
motors at Sec. 431.16 and applicable representation procedures in
parts 429 and 430.
E.1.2.1.1.2. For pumps sold with submersible motors, the default
nominal full load submersible motor efficiency is that listed in
Table 2 of this appendix, with the number of poles relevant to the
speed at which the pump is being tested (see section I.C.1 of this
appendix) and the motor horsepower of the pump being tested.
E.1.2.2 Determine the loss factor at each load point
corresponding to 75, 100, or 110 percent of the BEP flow rate as
follows:
[GRAPHIC] [TIFF OMITTED] TR25JA16.048
Where:
yi = the part load loss factor at load point i,
Pi = the pump power input to the bare pump at load point
i as determined in accordance with section V.E.1.1 of this appendix
(hp),
MotorHP = the horsepower of the motor with which the pump model is
being tested (hp),
i = load point corresponding to 75, 100, or 110 percent of the BEP
flow rate, and
[[Page 4155]]
[GRAPHIC] [TIFF OMITTED] TR25JA16.049
in the equation in this section V.E.1.2.2. of this appendix to
calculate the part load loss factor at each load point
VI. Testing-Based Approach for Pumps Sold with Motors and Controls
A. Scope. This section VI applies only to pumps sold with
electric motors, including single-phase induction motors, and
continuous or non-continuous controls. For the purposes of this
section VI, all references to ``driver input power'' in this section
VI or HI 40.6-2014 (incorporated by reference, see Sec. 431.463)
refer to the input power to the continuous or non-continuous
controls.
B. Measurement Equipment. The requirements regarding measurement
equipment presented in section I.B of this appendix apply to this
section VI, and in addition electrical measurement equipment must:
(1) Be capable of measuring true RMS current, true RMS voltage,
and real power up to the 40th harmonic of fundamental supply source
frequency, and
(2) For all instruments used to measure a given parameter, have
a combined accuracy of 2.0 percent of the measured value
at the fundamental supply source frequency, where combined accuracy
is the root sum of squares of individual instrument accuracies.
C. Test Conditions. The requirements regarding test conditions
presented in section I.C of this appendix apply to this section VI.
The following conditions also apply to the mains power supplied to
the continuous or non-continuous control:
(1) Maintain the voltage within 5 percent of the
rated value of the motor,
(2) Maintain the frequency within 1 percent of the
rated value of the motor,
(3) Maintain the voltage unbalance of the power supply within
3 percent of the rated values of the motor, and
(4) Maintain total harmonic distortion below 12 percent
throughout the test.
D. Testing BEP for the Pump. Determine the BEP of the pump as
follows:
D.1. Adjust the flow by throttling the pump without changing the
speed of rotation of the pump to a minimum of seven flow points: 40,
60, 75, 90, 100, 110, and 120 percent of the expected BEP flow rate
of the pump at the nominal speed of rotation, as specified in HI
40.6-2014, except section 40.6.5.3, section A.7, and appendix B
(incorporated by reference, see Sec. 431.463).
D.2. Determine the BEP flow rate as the flow rate at the
operating point of maximum overall efficiency on the pump efficiency
curve, as determined in accordance with section 40.6.6.3 of HI 40.6-
2014 (incorporated by reference, see Sec. 431.463), where overall
efficiency is the ratio of the pump power output divided by the
driver power input, as specified in Table 40.6.2.1 of HI 40.6-2014
and the calculations provided in section 40.6.6.2 are to be
disregarded.
E. Calculating the Variable Load Pump Energy Rating. Determine
the PERVL of each tested pump using the following
equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.050
Where:
PERVL = the pump energy rating for a variable load (hp);
[omega]i = 0.25;
Piin,c = the normalized driver power input to
continuous or non-continuous controls at load point i for the tested
pump as determined in accordance with section VI.E.1 of this
appendix; and
i = load point corresponding 25, 50, 75, or 100 percent of the BEP
flow rate.
E.1. Determine the driver power input at 100 percent of the
measured BEP flow rate of the tested pump by employing a least
squares regression to determine a linear relationship between the
measured driver power input at the nominal speed of rotation of the
pump and the measured flow rate, using the following load points:
60, 75, 90, 100, 110, and 120 percent of the expected BEP flow rate.
Use the linear relationship to determine the driver power input at
the nominal speed of rotation for the load point of 100 percent of
the measured BEP flow rate of the tested pump.
E.2 Determine the driver power input at 25, 50, and 75 percent
of the BEP flow rate by measuring the driver power input at the load
points defined by:
(1) Those flow rates, and
(2) The associated head points calculated according to the
following reference system curve equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.051
Where:
Hi = pump total head at load point i (ft),
H100[percnt] = pump total head at 100 percent
of the BEP flow rate and nominal speed of rotation (ft),
Qi = flow rate at load point i (gpm),
Q100[percnt] = flow rate at 100 percent of the
BEP flow rate and nominal speed of rotation (gpm), and
i = load point corresponding to 25, 50, or 75 percent of the
measured BEP flow rate of the tested pump.
E.2.1. For pumps sold with motors and continuous controls, the
specific head and flow points must be achieved within 10 percent of
the calculated values and the measured driver power input must be
corrected to the exact intended head and flow conditions using the
following equation:
[[Page 4156]]
[GRAPHIC] [TIFF OMITTED] TR25JA16.052
Where:
Pi\in,c\ = the corrected driver power input to the
continuous or non-continuous controls at load point i (hp),
Hsp,i = the specified total system head at load point i
based on the reference system curve (ft),
HM,j = the measured total system head at load point j
(ft),
Qsp,i = the specified total system flow rate at load
point i based on the reference system curve (gpm),
QM,j = the measured total system flow rate at load point
j (gpm),
PM,j\in,c\ = the measured normalized driver power input
to the continuous or non-continuous controls at load point j (hp),
i = specified load point at 25, 50, 75, or 100 percent of BEP flow,
and
j = measured load point corresponding to specified load point i.
E.2.2. For pumps sold with motors and non-continuous controls,
the head associated with each of the specified flow points shall be
no lower than 10 percent below that defined by the reference system
curve equation in section VI.E.2 of this appendix. Only the measured
flow points must be achieved within 10 percent of the calculated
values. Correct for flow and head as described in section VI.E.2.1,
except do not correct measured head values that are higher than the
reference system curve at the same flow rate; only correct flow rate
and head values lower than the reference system curve at the same
flow rate. For head values higher than the system curve, use the
measured head points directly to calculate PEIVL.
VII. Calculation-Based Approach for Pumps Sold With Motors and Controls
A. Scope. This section VII can only be used in lieu of the test
method in section VI of this appendix to calculate the index for
pumps listed in section VII.A.1 or VII.A.2 of this appendix.
A.1. Pumps sold with motors regulated by DOE's energy
conservation standards for polyphase NEMA Design B electric motors
at Sec. 431.25(g) and continuous controls, and
A.2. Pumps sold with submersible motors and continuous controls.
A.3. Pumps sold with motors not listed in VII.A.1 or VII.A.2 of
this appendix and pumps sold without continuous controls, including
pumps sold with non-continuous controls, cannot use this section and
must apply the test method in section VI of this appendix.
B. Measurement Equipment. The requirements regarding measurement
equipment presented in section I.B of this appendix apply to this
section VII, and in addition, when testing pumps using a calibrated
motor electrical measurement equipment must:
(1) Be capable of measuring true RMS current, true RMS voltage,
and real power up to the 40th harmonic of fundamental supply source
frequency, and
(2) For all instruments used to measure a given parameter, have
a combined accuracy of 2.0 percent of the measured value
at the fundamental supply source frequency, where combined accuracy
is the root sum of squares of individual instrument accuracies.
C. Test Conditions. The requirements regarding test conditions
presented in section I.C of this appendix apply to this section VII.
When testing pumps using a calibrated motor the following conditions
also apply to the mains power supplied to the motor:
(1) Maintain the voltage within 5 percent of the
rated value of the motor,
(2) Maintain the frequency within 1 percent of the
rated value of the motor,
(3) Maintain the voltage unbalance of the power supply within
3 percent of the rated values of the motor, and
(4) Maintain total harmonic distortion below 12 percent
throughout the test.
D. Testing BEP for the Bare Pump. Determine the BEP of the pump
as follows:
D.1. Adjust the flow by throttling the pump without changing the
speed of rotation of the pump to a minimum of seven flow points: 40,
60, 75, 90, 100, 110, and 120 percent of the expected BEP flow rate
of the pump at the nominal speed of rotation, as specified in HI
40.6-2014, except section 40.6.5.3, section A.7, and appendix B
(incorporated by reference, see Sec. 431.463).
D.2. Determine the BEP flow rate as the flow rate at the
operating point of maximum pump efficiency on the pump efficiency
curve, as determined in accordance with section 40.6.6.3 of HI 40.6-
2014 (incorporated by reference, see Sec. 431.463), where pump
efficiency is the ratio of the pump power output divided by the pump
power input, as specified in Table 40.6.2.1 of HI 40.6-2014 and the
calculations provided in section 40.6.6.2 are to be disregarded.
E. Calculating the Variable Load Pump Energy Rating. Determine
the PERVL of each tested pump using the following
equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.053
Where:
PERVL = the pump energy rating for a variable load (hp);
[omega]i = 0.25;
Piin,c = the calculated driver power input to
the continuous or non-continuous controls at load point i for the
tested pump as determined in accordance with section VII.E.1 of this
appendix; and
i = load point corresponding to 25, 50, 75, or 100 percent of the
BEP flow rate.
E.1 Determine the driver power input at each load point
corresponding to 25, 50, 75, or 100 percent of the BEP flow rate as
follows:
[GRAPHIC] [TIFF OMITTED] TR25JA16.054
Where:
Pi\in,c\ = driver power input at to the continuous or
non-continuous controls at load point i (hp),
Pi = pump power input to the bare pump at load point i as
determined in accordance with section VII.E.1.1 of this appendix
(hp),
Li = the part load motor and control losses at load point
i as determined in accordance with section VII.E.1.2 of this
appendix (hp), and
i = load point corresponding to 25, 50, 75, or 100 percent of the
BEP flow rate.
E.1.1 Determine the pump power input at 100 percent of the
measured BEP flow rate of the tested pump by employing a least
squares regression to determine a linear relationship between the
measured pump power input at the nominal speed of rotation and the
measured flow rate at the following load points: 60, 75, 90, 100,
110, and 120 percent of the expected BEP flow rate. Use the linear
relationship to determine the pump power input at the nominal speed
of rotation for the load point of 100 percent of the BEP flow rate.
E.1.1.1 Determine the pump power input at 25, 50, and 75 percent
of the BEP flow rate based on the measured pump power input at 100
percent of the BEP flow rate and using with the following equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.055
Where:
Pi = pump power input at load point i (hp);
P100% = pump power input at 100 percent of the BEP flow
rate and nominal speed of rotation (hp);
Qi = flow rate at load point i (gpm);
Q100% = flow rate at 100 percent of the BEP flow rate and
nominal speed of rotation (gpm); and
i = load point corresponding to 25, 50, or 75 percent of the
measured BEP flow rate of the tested pump.
E.1.2 Calculate the motor and control part load losses at each
load point corresponding
[[Page 4157]]
to 25, 50, 75, and 100 percent of the BEP flow rate as follows:
Li = Lfull x zi
Where:
Li = motor and control losses at load point i (hp),
Lfull = motor losses at full load as determined in
accordance with section VII.E.1.2.1 of this appendix (hp),
zi = part load loss factor at load point i as determined
in accordance with section VII.E.1.2.2 of this appendix, and
i = load point corresponding to 25, 50, 75, or 100 percent of the
BEP flow rate.
E.1.2.1 Determine the full load motor losses using the
appropriate motor efficiency value and horsepower as shown in the
following equation:
[GRAPHIC] [TIFF OMITTED] TR25JA16.056
Where:
Lfull = motor losses at full load (hp),
MotorHP = the horsepower of the motor with which the pump model is
being tested (hp), and
[eta]motor,full = the represented nominal full load motor
efficiency (i.e., nameplate/DOE-certified value) or default nominal
full load submersible motor efficiency as determined in accordance
with section VII.E.1.2.1.1 of this appendix (%).
E.1.2.1.1 For pumps sold with motors other than submersible
motors, determine the represented nominal full load motor efficiency
as described in section VII.E.1.2.1.1.1 of this appendix. For pumps
sold with submersible motors, determine the default nominal full
load submersible motor efficiency as described in section
VII.E.1.2.1.1.2 of this appendix.
E.1.2.1.1.1 For pumps sold with motors other than submersible
motors, the represented nominal full load motor efficiency is that
of the motor with which the given pump model is being tested, as
determined in accordance with the DOE test procedure for electric
motors at Sec. 431.16 and applicable representation procedures in
parts 429 and 430.
E.1.2.1.1.2 For pumps sold with submersible motors, the default
nominal full load submersible motor efficiency is that listed in
Table 2 of this appendix, with the number of poles relevant to the
speed at which the pump is being tested (see section I.C.1 of this
appendix) and the motor horsepower of the pump being tested.
E.1.2.2 For load points corresponding to 25, 50, 75, and 100
percent of the BEP flow rate, determine the part load loss factor at
each load point as follows:
[GRAPHIC] [TIFF OMITTED] TR25JA16.057
Where:
zi = the motor and control part load loss factor at load
point i,
a,b,c = coefficients listed in Table 4 of this appendix based on the
horsepower of the motor with which the pump is being tested,
Pi = the pump power input to the bare pump at load point
i, as determined in accordance with section VII.E.1.1 of this
appendix (hp),
MotorHP = the horsepower of the motor with which the pump is being
tested (hp),
[GRAPHIC] [TIFF OMITTED] TR25JA16.058
Table 2--Default Nominal Full Load Submersible Motor Efficiency by Motor
Horsepower and Pole
------------------------------------------------------------------------
Default nominal full load
submersible motor efficiency
Motor horsepower (hp) -------------------------------
2 poles 4 poles
------------------------------------------------------------------------
1....................................... 55 68
1.5..................................... 66 70
2....................................... 68 70
3....................................... 70 75.5
5....................................... 74 75.5
7.5..................................... 68 74
10...................................... 70 74
15...................................... 72 75.5
20...................................... 72 77
25...................................... 74 78.5
30...................................... 77 80
40...................................... 78.5 81.5
50...................................... 80 82.5
[[Page 4158]]
60...................................... 81.5 84
75...................................... 81.5 85.5
100..................................... 81.5 84
125..................................... 84 84
150..................................... 84 85.5
200..................................... 85.5 86.5
250..................................... 86.5 86.5
------------------------------------------------------------------------
Table 3--Nominal Full Load Motor Efficiency Values
------------------------------------------------------------------------
Nominal full load motor efficiency*
-------------------------------------------------------------------------
50.5
52.5
55.0
57.5
59.5
62.0
64.0
66.0
68.0
70.0
72.0
74.0
75.5
77.0
78.5
80.0
81.5
82.5
84.0
85.5
86.5
87.5
88.5
89.5
90.2
91.0
91.7
92.4
93.0
93.6
94.1
94.5
95.0
95.4
95.8
96.2
96.5
96.8
97.1
97.4
97.6
97.8
98.0
98.2
98.4
98.5
98.6
98.7
98.8
98.9
99.0
------------------------------------------------------------------------
* Note: Each consecutive incremental value of nominal efficiency
represents one band.
Table 4--Motor and Control Part Load Loss Factor Equation Coefficients for Section VII.E.1.2.2 of This Appendix
A
----------------------------------------------------------------------------------------------------------------
Coefficients for Motor and Control Part Load Loss
Factor (zi)
Motor horsepower (hp) -----------------------------------------------------
a b c
----------------------------------------------------------------------------------------------------------------
<=5....................................................... - 0.4658 1.4965 0.5303
>5 and <=20............................................... - 1.3198 2.9551 0.1052
>20 and <=50.............................................. - 1.5122 3.0777 0.1847
>50....................................................... - 0.8914 2.8846 0.2625
----------------------------------------------------------------------------------------------------------------
[FR Doc. 2016-00039 Filed 1-22-16; 8:45 am]
BILLING CODE 6450-01-P