Energy Conservation Program for Consumer Products: Test Procedures for Residential Furnaces and Boilers, 2627-2656 [2016-00040]
Download as PDF
Vol. 81
Friday,
No. 10
January 15, 2016
Part V
Department of Energy
tkelley on DSK3SPTVN1PROD with RULES4
10 CFR Parts 429 and 430
Energy Conservation Program for Consumer Products: Test Procedures for
Residential Furnaces and Boilers; Final Rule
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
PO 00000
Frm 00001
Fmt 4717
Sfmt 4717
E:\FR\FM\15JAR4.SGM
15JAR4
2628
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[Docket No. EERE–2012–BT–TP–0024]
RIN 1904–AC79
Energy Conservation Program for
Consumer Products: Test Procedures
for Residential Furnaces and Boilers
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
The U.S. Department of
Energy (DOE) amends its test procedure
for residential furnaces and boilers
established under the Energy Policy and
Conservation Act. This rulemaking will
fulfill DOE’s obligation to review its test
procedures for covered products at least
once every seven years. The revisions
include: Clarifying the components
included in the burner electrical power
input term (PE); adopting a method for
determining whether a minimum draft
factor can be applied, and how the
conditions are to be verified; allowing
optional measurement of condensate
collection during establishment of
steady state; updating references to the
applicable installation and operating
manual and providing clarifications
when the installation and operation
(I&O) manual does not specify test
setup; clarifying the testing of units
intended to be installed without a return
duct; adopting a provision clarifying the
testing of multi-position units; revising
the required reporting precision for
annual fuel utilization efficiency
(AFUE); and adopting a verification
method for determining whether a
boiler incorporates an automatic means
for adjusting water temperature and
whether this design requirement
functions as required.
DATES: The effective date of this rule is
February 16, 2016. The final rule
changes will be mandatory for
representations made on or after July 13,
2016. The incorporation by reference of
certain material listed in this rule is
approved by the Director of the Federal
Register as of February 16, 2016.
ADDRESSES: The docket, which includes
Federal Register notices, public meeting
attendee lists and transcripts,
comments, and other supporting
documents/materials, is available for
review at www.regulations.gov. All
documents in the docket are listed in
the www.regulations.gov index.
However, not all documents listed in
the index may be publicly available,
such as information that is exempt from
public disclosure.
tkelley on DSK3SPTVN1PROD with RULES4
SUMMARY:
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
A link to the docket Web page can be
found at: https://www.regulations.gov/
#!docketDetail;D=EERE-2012-BT-TP0024. This Web page contains a link to
the docket for this final rule on the
www.regulations.gov site. The
www.regulations.gov Web page contains
simple instructions on how to access all
documents, including public comments,
in the docket.
For further information on how to
review the docket, contact Ms. Brenda
Edwards at (202) 586–2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Ms.
Ashley Armstrong, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Office, EE–5B, 1000
Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–6590. Email:
Ashley.Armstrong@ee.doe.gov.
Mr. Pete Cochran, U.S. Department of
Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue
SW., Washington, DC 20585–0121.
Telephone: (202) 586–9496. Email:
peter.cochran@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final
rule incorporates by reference into part
430 the following industry standard:
ASTM D2156–09 (Reapproved 2013)
(‘‘ASTM D2156R13’’), Standard Test
Method for Smoke Density in Flue Gases
from Burning Distillate Fuels, approved
October 1, 2013.
Copies of ASTM D2156R13 can be
obtained from ASTM. American Society
of Testing and Materials, ASTM
Headquarters, 100 Barr Harbor Drive,
P.O. Box C700, West Conshohocken, PA
19428–2959, (877) 909–2786 or (610)
832–9585, or by going to https://
www.astm.org. See section IV.M for
further discussion of this standard.
Table of Contents
I. Authority and Background
II. Summary of the Final Rule
III. Discussion
A. Products Within Scope of the Final Rule
B. General Comments
1. Statutory Deadline
2. Simultaneous Changes in Test Procedure
and Standards
3. Lack of Data Availability
C. Proposed Incorporation by Reference of
ASHRAE Standard 103–2007
D. Test Procedure Amendments
1. Electrical Power of Components
2. Smoke Stick Test for Determining Use of
Minimum Default Off-Cycle and Power
Burner Draft Factors
3. Condensate Collection During the
Establishment of Steady State Conditions
4. Installation and Operation Manual
Reference
5. Duct Work for Units That Are Installed
Without a Return Duct
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
6. Testing Requirements for Multi-Position
Configurations
7. AFUE Reporting Precision
8. Definitions and Other Changes
E. Other Test Procedure Considerations
1. Room Ambient Air Temperature and
Humidity Ranges
2. Full-Fuel-Cycle Energy Metrics
3. Oversize Factor Value
4. Alternative Methods for Furnace/Boiler
Efficiency Determination
5. Test Method for Combination Appliance
F. Test Burden
G. Measured Energy Use
H. Certification and Enforcement
1. Verification Test for Automatic Means
for Adjusting the Water Temperature in
Boilers
2. Compliance Dates for the Amended Test
Procedure
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Description of Materials Incorporated
by Reference
V. Approval of the Office of the Secretary
I. Authority and Background
Title III, Part B 1 of the Energy Policy
and Conservation Act of 1975 (‘‘EPCA’’
or ‘‘the Act’’), Public Law 94–163 (42
U.S.C. 6291–6309, as codified) sets forth
a variety of provisions designed to
improve energy efficiency and
established the Energy Conservation
Program for Consumer Products Other
Than Automobiles.2 These products
include residential furnaces and boilers,
the subject of this notice.3
Under EPCA, DOE’s energy
conservation program generally consists
of four parts: (1) Testing; (2) labeling; (3)
Federal energy conservation standards;
and (4) certification and enforcement
procedures. The testing requirements
consist of test procedures that
manufacturers of covered products must
1 For editorial reasons, Part B was codified as Part
A in the U.S. Code.
2 All references to EPCA in this document refer
to the statute as amended through the Energy
Efficiency Improvement Act of 2015, Public Law
114–11 (Apr. 30, 2015).
3 Under 42 U.S.C. 6292(a)(5), the statute
establishes ‘‘furnaces’’ as covered products, and 42
U.S.C. 6291(23) defines furnaces as inclusive of
boilers.
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
use as the basis for: (1) Certifying to
DOE that their products comply with
the applicable energy conservation
standards adopted pursuant to EPCA,
and (2) making other representations
about the efficiency of those products.
(42 U.S.C. 6293(c); 42 U.S.C. 6295(s))
Similarly, DOE must use these test
procedures to determine whether the
products comply with any relevant
standards promulgated under EPCA. (42
U.S.C. 6295(s))
EPCA sets forth the criteria and
procedures that DOE must follow when
prescribing or amending test procedures
for covered products. EPCA provides, in
relevant part, that any test procedures
prescribed or amended under this
section shall be reasonably designed to
produce test results which measure
energy efficiency, energy use, or
estimated annual operating cost of a
covered product during a representative
average use cycle or period of use, and
shall not be unduly burdensome to
conduct. (42 U.S.C. 6293(b)(3))
In addition, if DOE determines that a
test procedure amendment is warranted,
it must publish proposed test
procedures and offer the public an
opportunity to present oral and written
comments on them. (42 U.S.C.
6293(b)(2)) Finally, in any rulemaking to
amend a test procedure, DOE must
determine to what extent, if any, the
proposed test procedure would alter the
product’s measured energy efficiency as
determined under the existing test
procedure. (42 U.S.C. 6293(e)(1))
EISA 2007 amended EPCA to require
that, at least once every 7 years, DOE
must review test procedures for all
covered products and either amend the
test procedures (if the Secretary
determines that amended test
procedures would more accurately or
fully comply with the requirements of
42 U.S.C. 6293(b)(3)) or publish a notice
in the Federal Register of any
determination not to amend a test
procedure. (42 U.S.C. 6293(b)(1)(A))
Under this requirement, DOE must
review the test procedure for residential
furnaces and boilers not later than
December 19, 2014 (i.e., 7 years after the
publication of EISA 2007 on December
19, 2007).
DOE’s current energy conservation
standards for residential furnaces and
boilers are expressed as minimum
annual fuel utilization efficiency
(AFUE). AFUE is an annualized fuel
efficiency metric that accounts for fuel
consumption in active, standby, and off
modes. The following discussion
provides a brief history of the
rulemakings underlying the existing test
procedure for residential furnaces and
boilers.
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
The existing DOE test procedure for
determining the AFUE of residential
furnaces and boilers is located at 10 CFR
part 430, subpart B, appendix N,
Uniform Test Method for Measuring the
Energy Consumption of Furnaces and
Boilers. The existing DOE test procedure
for residential furnaces and boilers was
established by a final rule published in
the Federal Register on May 12, 1997,
and it incorporates by reference the
American National Standards Institute/
American Society of Heating,
Refrigerating, and Air-Conditioning
Engineers (ANSI/ASHRAE) Standard
103–1993, Method of Testing for Annual
Fuel Utilization Efficiency of Residential
Central Furnaces and Boilers (ASHRAE
103–1993). 62 FR 26140, 26157
(incorporated by reference at 10 CFR
430.3(f)(10)). On October 14, 1997, DOE
published an interim final rule in the
Federal Register to revise a provision
concerning the insulation of the flue
collector box in order to ensure the
updated test procedure would not affect
the measured AFUE of existing furnaces
and boilers. 62 FR 53508. This interim
final rule was adopted without change
in a final rule published in the Federal
Register on February 24, 1998. 63 FR
9390.
On October 20, 2010, DOE amended
its test procedure for furnaces and
boilers to establish a method for
measuring the electrical energy use in
standby mode and off mode for gasfired and oil-fired furnaces and boilers,
as required by EISA 2007. 75 FR 64621.
These test procedure amendments
incorporated by reference, and were
based primarily on, provisions of the
International Electrotechnical
Commission (IEC) Standard 62301 (First
Edition), Household electrical
appliances—Measurement of standby
power. On December 31, 2012, DOE
published a final rule (December 2012
final rule) in the Federal Register that
updated the incorporation by reference
of the standby mode and off mode test
procedure provisions to refer to the
latest edition of IEC Standard 62301
(Second Edition). 77 FR 76831. On July
10, 2013, DOE published a final rule
(July 2013 final rule) in the Federal
Register that amended its test procedure
for residential furnaces and boilers by
adopting needed equations that allow
manufacturers the option to omit the
heat-up and cool-down tests and still
generate a valid AFUE measurement. 78
FR 41265. On August 30, 2013, DOE
published a correction to the July 2013
final rule that corrected errors in the
redesignations of affected subsections
within section 10 of appendix N. 78 FR
53625.
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
2629
On January 4, 2013, DOE initiated this
rulemaking to examine all aspects of the
DOE test procedure by publishing a
request for information (RFI) (January
2013 RFI) in the Federal Register. 78 FR
675. On March 11, 2015, DOE published
a notice of proposed rulemaking (NOPR)
(March 2015 NOPR) in the Federal
Register to amend the test procedure for
residential furnaces and boilers. 80 FR
12876. In the March 2015 NOPR, DOE
proposed to amend the residential
furnaces and boilers test procedure by
incorporating by reference ANSI/
ASHRAE Standard 103–2007 (ASHRAE
103–2007) in place of ASHRAE 103–
1993, which currently is referenced in
the existing test procedure. In addition,
the March 2015 NOPR proposed to
adopt modifications that would
establish revised test procedures for
two-stage and modulating products, as
well as for boilers with long post-purge
times that would not otherwise be
included in the incorporation by
reference of ASHRAE 103–2007.
DOE also proposed to amend the test
procedure to: (1) Allow the
measurement of condensate during the
establishment of steady-state rather than
require an additional 30 minutes of
testing after steady-state conditions are
established; (2) revise annual electricity
consumption equations to account for
additional electrical components; (3)
revise test procedure references to
‘‘manufacturer recommendations’’ or
‘‘manufacturer’s instructions’’ that do
not explicitly identify the source of the
recommendations or instructions; (4)
include a test protocol for determining
the functionality of the automatic means
for adjusting water temperature; (5)
include a test method to indicate the
absence or presence of air flow to
determine whether the minimum
default draft factor may be used; (6)
revise the required reporting precision
for AFUE; (7) specify testing
requirements for units that are installed
without a return duct; and (8) specify
testing requirements for units with
multi-position configurations. 80 FR
12876.
II. Summary of the Final Rule
The final rule amends the existing
DOE test procedure for residential
furnaces and boilers to improve the
consistency and accuracy of test results
generated using the DOE test procedure
and to reduce test burden. In particular,
these modifications include: (1)
Clarifying the definition of the electrical
power term PE; (2) adopting a smoke
stick test for determining use of
minimum default draft factors; (3)
allowing for the measurement of
condensate under steady-state
E:\FR\FM\15JAR4.SGM
15JAR4
2630
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
conditions; (4) referencing the
manufacturer’s installation and
operation (I&O) manual and providing
clarifications when the I&O manual
does not specify test setup; (5)
specifying ductwork requirements for
units that are installed without a return
duct; (6) specifying testing requirements
for units with multi-position
configurations; and (7) revising the
AFUE reporting precision. DOE has also
revised the definitions of several terms
in the test procedure and added an
enforcement provision to provide a
method of test for DOE to determine
compliance with the automatic means
design requirement mandated by EISA
2007.
DOE has withdrawn or modified all
test procedure amendment proposals in
the March 2015 NOPR for which
stakeholders expressed concern
regarding the effect of the proposed
amendments on the measured energy
efficiency of residential furnaces and
boilers when compared to the current
test procedure. In particular, as
discussed in section III.C, DOE has
withdrawn its proposal to incorporate
by reference ASHRAE 103–2007.
tkelley on DSK3SPTVN1PROD with RULES4
III. Discussion
The following sections discuss the
products within the scope of this
rulemaking, the test procedure
amendments, other test procedure
considerations, test burden, measured
energy use, and changes to certification
and enforcement provisions.
In response to the March 2015 NOPR,
the following twelve interested parties
submitted written comments: The
American Gas Association (AGA); the
Air-Conditioning, Heating and
Refrigeration Institute (AHRI); Burnham
Holdings, Inc. (Burnham); Carrier
Corporation (Carrier); John Cockerill
(Cockerill); Goodman Global, Inc.
(Goodman); Lennox Industries Inc.
(Lennox); Lochinvar, LLC (Lochinvar);
Rheem Manufacturing Company
(Rheem); Ingersoll Rand Residential
Solutions (Ingersoll Rand); Laclede
Group; and Weil-McLain. Interested
parties provided comments on a range
of issues, including those DOE
identified in the March 2015 NOPR, as
well as issues related to the proposed
test procedure changes. The issues on
which DOE received comments, as well
as DOE’s responses to those comments
and the resulting changes to the test
procedure proposals presented in the
NOPR, are discussed in the subsequent
sections. A parenthetical reference at
the end of a comment quotation or
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
paraphrase provides the location of the
item in the public record.4
A. Products Within Scope of the Final
Rule
The test procedure amendments apply
to products that meet the definitions for
residential furnaces and boilers (see
DOE’s regulations at 10 CFR 430.2). A
‘‘furnace’’ is defined as a product that:
(1) Utilizes only single-phase electric
current, or single-phase electric current
or direct current (DC) in conjunction
with natural gas, propane, or home
heating oil; (2) is designed to be the
principal heating source for the living
space of a residence; (3) is not contained
within the same cabinet with a central
air conditioner whose rated cooling
capacity is above 65,000 Btu per hour;
(4) is an electric central furnace, electric
boiler, forced-air central furnace, gravity
central furnace, or low pressure steam
or hot water boiler; and (5) has a heat
input rate of less than 300,000 Btu per
hour for electric boilers and low
pressure steam or hot water boilers and
less than 225,000 Btu per hour for
forced-air central furnaces, gravity
central furnaces, and electric central
furnaces.5
The individual products within the
scope of this test procedure and the
definition of each (see DOE’s regulations
at 10 CFR 430.2) are listed below:
(1) Electric boiler means an
electrically powered furnace designed to
supply low pressure steam or hot water
for space heating application. A low
pressure steam boiler operates at or
below 15 pounds per square inch gauge
(psig) steam pressure; a hot water boiler
operates at or below 160 psig water
pressure and 250 °F water temperature.
(2) Electric central furnace means a
furnace that is designed to supply heat
through a system of ducts with air as the
heating medium, in which heat
generated by one or more electric
resistance heating elements is circulated
by means of a fan or blower.
(3) Forced-air central furnace means a
furnace that burns gas or oil and is
designed to supply heat through a
system of ducts with air as the heating
medium. The heat generated by
4 The parenthetical reference provides a reference
for information located in the docket of DOE’s
rulemaking to amend the test procedures for
residential furnaces and boilers. (Docket No. EERE–
2012–BT–TP–0024, which is maintained at https://
www.regulations.gov/#!docketDetail;D=EERE-2012BT-TP-0024). The references are arranged as
follows: (commenter name, comment docket ID
number, page of that document).
5 The definition of ‘‘furnace’’ currently in the CFR
at 10 CFR 430.2 mistakenly repeats the terms
‘‘gravity central furnaces, and electric central
furnaces’’ at the end of the definition. In this final
rule, DOE is correcting this error to remove the
duplicative language.
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
combustion of gas or oil is transferred to
the air within a casing by conduction
through heat exchange surfaces and is
circulated through the duct system by
means of a fan or blower.
(4) Gravity central furnace means a
gas-fueled furnace which depends
primarily on natural convection for
circulation of heated air and which is
designed to be used in conjunction with
a system of ducts.
(5) Low pressure steam or hot water
boiler is an electric, gas, or oil-burning
furnace designed to supply low pressure
steam or hot water for space heating
applications. A low pressure steam
boiler operates at or below 15 psig steam
pressure; a hot water boiler operates at
or below 160 psig water pressure and
250 °F water temperature.
(6) Mobile home furnace means a
direct vent furnace that is designed for
use only in mobile homes.
(7) Outdoor furnace or boiler is a
furnace or boiler normally intended for
installation out-of-doors or in an
unheated space (such as an attic or a
crawl space).
(8) Weatherized warm air furnace or
boiler means a furnace or boiler
designed for installation outdoors,
approved for resistance to wind, rain,
and snow, and supplied with its own
venting system.
B. General Comments
Stakeholders submitted general
comments regarding the test procedure
and parallel energy conservation
standards rulemaking timeline and the
availability of data related to this
proceeding. DOE discusses and
responds to these comments in the
following subsections.
1. Statutory Deadline
As noted in section I, EISA 2007
requires that DOE must review test
procedures for all covered products and
amend the test procedures or publish a
notice in the Federal Register of any
determination not to amend test
procedures at least once every seven
years. (42 U.S.C. 6293(b)(1)(A)).
AHRI asserted that the start date for
the obligation to review efficiency test
procedures at least once every seven
years has been reset by the July 2013
Final Rule. And, therefore, by its
estimation, DOE has approximately five
more years to review and amend, as
needed, the test procedures for
residential furnaces and boilers. AHRI
added that this would be ample time to
manage DOE’s rulemaking activities
such that proposed revisions to
efficiency standards and test procedures
are not considered concurrently. (AHRI,
No. 36 at p. 2)
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES4
DOE notes that the July 2013 Final
Rule was limited in scope and only
intended to remedy a specific concern
articulated by stakeholders. Specifically,
the July 2013 Final Rule adopted
needed equations to allow
manufacturers the option to omit the
heat up and cool down tests and still
generate a valid AFUE measurement for
certain condensing products. 78 FR
41265, 41266. DOE considers the seven
year look back provision to include a
comprehensive review of the entire test
procedure. (42 U.S.C. 6293(b)(1)(A))
DOE did not conduct a comprehensive
review for the July 2013 Final Rule.
Furthermore, DOE stated in the July
2013 Final Rule that it was initiating a
separate rulemaking that was broader in
scope to examine all aspects of the DOE
test procedure for residential furnaces
and boilers. 78 FR 41265, 41266.
Therefore, DOE maintains that the July
2013 final rule did not meet the
requirements outlined in 42 U.S.C.
6293(b)(1)(A). In contrast, DOE has
conducted a comprehensive review as
part of the current rulemaking, which
satisfies the requirements of 42 U.S.C.
6293(b)(1)(A).
2. Simultaneous Changes in Test
Procedure and Standards
Several stakeholders cited legal and
practical concerns regarding the timing
of proposed revisions to the test
procedures and standards for residential
furnaces and boilers. Stakeholders
requested that DOE delay any further
work on the rulemakings to amend
efficiency standards for these products
until after the finalization of the test
procedure. (AHRI, No. 36 at p. 1; WeilMcLain, No. 31 at p. 2; Ingersoll Rand,
No. 37 at p. 5)
AHRI stated that it believes the nonfinal status of the test procedure inhibits
stakeholders’ fair evaluation of the
standard. AHRI stressed the importance
of having a known efficiency test
procedure. AHRI noted that when a test
procedure is in flux, manufacturers
must spend resources collecting
potentially unusable data which
undermines their ability to provide
input on the proposed efficiency
standards. Similarly, AHRI added that
when a test procedure is not finalized,
a manufacturer has no way of
determining whether the test procedure
will affect its ability to comply with a
proposed revised standard. AHRI noted
that DOE is required to give
stakeholders the opportunity to provide
meaningful comments and asserted that
the joint proposal of test procedures and
standards diminishes that opportunity
(see 42 U.S.C. 6295(p)(2), 6306(a)).
(AHRI, No. 36 at p. 1)
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
In response to AHRI, DOE does not
believe that the timing of the test
procedure and standards rulemakings
has negatively impacted stakeholders’
ability to provide meaningful comment
on this test procedure rulemaking. DOE
allowed four months for public
comment on the test procedure NOPR.
Additionally, DOE’s original proposal
included an update to the latest
industry standard (i.e., ASHARE 103–
2007), which was developed by a
consensus-based ASHRAE process, and
was released in 2007. DOE believes that
industry was involved in developing
that standard and had experience with
the changes in the 2007 version of
ASHRAE Standard 103. Lastly,
stakeholders provided detailed,
insightful comments on all aspects of
the proposal, including submitting
select test data in response to DOE’s
proposal, which shows that industry
was able to carefully consider the
proposed method and how it compared
to the current Federal method of test. In
addition, DOE has taken AHRI’s
concerns regarding the potential impact
of test procedure changes on measured
energy use into account in its
determinations of which test procedure
proposals to finalize in this rulemaking.
AHRI and Goodman stated that by
publishing the March 2015 NOPR
within weeks of the proposed efficiency
standard, DOE has failed to abide by the
procedures located at 10 CFR part 430,
subpart C, appendix A (7)(b). (AHRI, No.
36 at p. 2; Goodman, No. 33 at p. 2)
AHRI stated that the Administrative
Procedure Act (APA) requires agencies
to abide by their policies and
procedures, especially where those rules
have a substantive effect. AHRI asserted
that the non-final test procedure has the
substantive effect of increasing costs to
stakeholders and diminishing their
ability to comment on the efficiency
standards. (AHRI, No. 36 at p. 2; WeilMcLain, No. 31 at p. 7)
In response to the comments from
AHRI and Goodman asserting that DOE
has failed to abide by its procedures at
10 CFR 430, subpart C, appendix A
(7)(b), DOE notes that appendix A
establishes procedures, interpretations,
and policies to guide DOE in the
consideration and promulgation of new
or revised appliance efficiency
standards under EPCA. (See section 1 of
10 CFR part 430, subpart C, appendix A)
Those procedures are a general guide to
the steps DOE typically follows in
promulgating energy conservation
standards. The guidance recognizes that
DOE can and will, on occasion, deviate
from the typical process. Accordingly,
DOE has concluded that there is no
basis to either: (1) Delay the final rules
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
2631
adopting standards for residential
furnaces and boilers; or (2) suspend the
test procedure rulemaking until the
standards rulemaking has been
completed.
Ingersoll Rand and Goodman stated
their concern that two-stage, condensing
furnaces that would meet the March 12,
2015 furnace proposed rule of 92percent AFUE under the current test
procedure would not meet the 92percent AFUE standard under the
proposed DOE test procedure. Ingersoll
Rand noted that the two test procedures
were assumed to be identical in the
March 12, 2015 residential furnace
standard NOPR technical support
document. (Ingersoll Rand, No. 37 at p.
2; Goodman, No. 33 at p. 1) Similarly,
Weil-McLain suggested that the
uncertainty caused by the simultaneous
test procedure rulemaking amplifies
venting issues present in the residential
boiler standards NOPR. (Weil-McLain,
No. 31 at p. 3)
In response to Ingersoll Rand and
Goodman, as discussed in section III.C,
DOE declines to adopt the latest
industry standard of ASHRAE 103–
2007, which is the only amendment
proposed in the March 2015 NOPR that
manufacturers claimed could alter the
AFUE for two-stage and modulating
condensing products. In response to
Weil-McLain, DOE notes that none of
the proposed test procedure provisions
that had the potential to result in a
change in measured AFUE are adopted
in this test procedure final rule, as
discussed in section III.G.
3. Lack of Data Availability
In response the March 2015 NOPR,
interested parties submitted comments
regarding lack of data availability. For
example, the March 2015 NOPR
included several references to a testing
report. 80 FR 12876, 12878. Burnham
stated that in spite of requests from
commenters, the testing report was not
available in the public docket as of July
8, 2015. Burnham added that the lack of
access to the testing report has made it
impossible to properly review the
impact of ambient conditions on AFUE
during the public comment period.
Burnham requested that the comment
period be extended to allow comment
on this document which should be
disclosed immediately. (Burnham, No.
35 at p. 7)
DOE made the test results available
during the test procedure public
meeting.6 The slide deck presented at
6 Test results included in the slide deck for the
public meeting include those for proposed changes
related to AFUE determination for two-stage/
E:\FR\FM\15JAR4.SGM
Continued
15JAR4
2632
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES4
the public meeting was posted to the
docket on March 26, 2015, along with
the transcript of the public meeting.
(Public Meeting Presentation Slides, No.
21) Therefore, stakeholders were
presented with an opportunity to review
and discuss the data with the
Department at the public meeting and to
review the results during the comment
period, which was open until July 10,
2015.
C. Proposed Incorporation by Reference
of ASHRAE Standard 103–2007
In the March 2015 NOPR, DOE
proposed amendments to reduce
variability, eliminate ambiguity, and
address discrepancies between the test
procedure and actual field conditions,
and DOE requested comment on its
proposals. 80 FR 12876, 12902. One of
these proposals was to update its
incorporation by reference of the
industry test standard ASHRAE 103–
1993 to ASHRAE 103–2007.
DOE received several comments in
response to its proposal to update the
incorporation by reference in the DOE
test procedure to ASHRAE 103–2007.
Lochinvar and AGA responded to the
NOPR in favor of adopting ASHRAE
103–2007 provided that DOE make
adequate allowances for the resulting
test burden and the impact that the
change would have on existing
efficiency claims. (Lochinvar, No. 29 at
p. 1; AGA, No. 27 at p. 4) Similarly,
Burnham stated that they are not
opposed to the update provided test
burden is reduced. (Burnham, No. 35 at
p. 3)
Ingersoll Rand and Rheem stated their
support only for certain provisions of
ASHRAE 103–2007. Specifically,
Ingersoll Rand supported requiring only
reduced fire testing (and not high-fire
testing) when the calculated balance
point temperature is less than or equal
to five degrees. (Ingersoll Rand, No. 37
at p. 4) Rheem stated their support for
the elimination of table 8 and the
average design heating requirements in
ASHRAE 103–1993. (Rheem, No. 30 at
p. 2)
Lennox and Weil-McLain suggested
DOE not update to ASHRAE 103–2007
at this time. (Lennox, No. 32 at p. 2;
Weil-McLain, No. 31 at p. 7) AHRI and
Weil-McLain suggested that DOE wait to
modify the test procedure until
ASHRAE 103–2016 is issued. (AHRI,
No. 36 at p. 8; Weil-McLain, No. 31 at
modulating products, measurement of condensate
under steady state conditions, electric consumption
of components, and verification test for automatic
means for adjusting the water temperature in
boilers. DOE did not provide test results for ambient
conditions or other testing for which no changes
were proposed in the NOPR.
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
p. 7) Carrier suggested that DOE not
update to ASHRAE 103–2007, but
change the AFUE metric for forced-air
furnaces to be based on the steady-state
operation, as discussed in section
III.E.4. (Carrier, No. 34 at p. 2)
Several commenters suggested that
that the updating to ASHRAE 103–2007
would result in more significant
changes to AFUE ratings than suggested
by DOE in the March 2015 NOPR.
(Burnham, No. 35 at p. 3; Lennox, No.
32 at p. 2; AGA, No. 27 at p. 4; AHRI,
No. 36 at p. 4; Ingersoll Rand, No. 37 at
p. 2) Of these commenters, only AHRI
provided test data, which indicated
small changes in AFUE as a result of
changes to the cyclical condensate test
for modulating condensing boilers.
(AHRI, No. 36 at p. 17)
Burnham and Ingersoll Rand
suggested that the impact to AFUE
resulting from the changes in cycle
times is still uncertain. Therefore, it is
not possible to conclude that the effect
of this proposed change to the
procedure is insignificant. (Burnham,
No. 35 at p. 3; Ingersoll Rand, No. 37 at
p. 2) Ingersoll Rand noted that as a
result of adopting ASHRAE 103–2007,
two-stage and modulating noncondensing furnaces will have a higher
AFUE rating, and condensing furnaces
will have lower AFUE ratings. Ingersoll
Rand noted that the changes in AFUE
are higher than the uncertainty of the
test procedure reported by DOE and
therefore this change to the test
procedure cannot be considered de
minimis. Ingersoll Rand also noted that
the test results are limited and have
high variability. Ingersoll Rand
suggested that the change not be
adopted until the variability is better
understood. (Ingersoll Rand, No. 37 at p.
2) AGA suggested that the Department
substantially increase the amount of
testing using the modified test
procedure to ensure that the resulting
efficiency rating for both furnaces and
boilers are accurate and repeatable.
(AGA, No. 27 at p. 4)
Similarly, Ingersoll Rand suggested
the calculation to account for post purge
times longer than three minutes not be
adopted without test data indicating the
adjustment to AFUE that would result
from this update. Ingersoll Rand stated
that without test data they cannot
determine if the new readings would be
representative of a unit’s performance.
(Ingersoll Rand, No. 37 at p. 4)
In response to the March 2015 NOPR,
Ingersoll Rand requested that DOE not
adopt the proposed changes to the
calculation of annual auxiliary electrical
energy consumption (EAE) caused by the
update to ASHRAE 103–2007. Ingersoll
Rand stated that the calculation of EAE
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
proposed in the March 2015 NOPR
changes the value of EAE substantially
from ¥8.5 percent to +13.5 percent.
Ingersoll Rand noted that this change,
along with the proposal to include the
electrical consumption of additional
components is significant enough that
all current furnaces would have to be
retested and recertified. Ingersoll Rand
requested that DOE reconsider its
finding that the amended test procedure
would have a ‘‘de minimis impact on
the products’ measured energy use’’ and
instead find that the proposed test
procedure amendment has a significant
impact on measured electricity
consumption. (Ingersoll Rand, No. 37 at
p. 5)
Several commenters stated that the
changes to AFUE caused by updating to
ASHRAE 103–2007 would lead to
additional testing burden. (Burnham,
No. 35 at p. 3; Lennox, No. 32 at p. 2;
AHRI, No. 36 at p. 4) AHRI stated that
the change to use calculated values for
tON and tOFF will at a minimum require
retesting for any step-modulating
models at the reduced input rate and for
many two stage models at both the
maximum and reduced input rates.
(AHRI, No. 36 at p. 4)
Given this expected test burden,
Lochinvar argued that if DOE is to adopt
ASHRAE 103–2007, DOE must declare
in writing that products certified
according to ASHRAE 103–1993 that
were on the market prior to updating the
test procedure are not required to be
retested and recertified unless the
design is changed in a way that affects
efficiency. Lochinvar suggested that
future audit tests of pre-existing
products could still be conducted
according to ASHRAE 103–2007 but
that manufacturers should not be
required to do new tests on existing
models for certification reporting to
DOE’s Compliance Certification
Management System (CCMS).
(Lochinvar, No. 29 at p. 1)
Burnham also commented that their
efforts to explore the impact of adoption
of ASHRAE 103–2007 have been
hampered by the lack of generally
available, National Institute of
Standards and Technology (NIST)
validated software tools for calculating
AFUE (and intermediate values) based
on ASHRAE 103–2007. Burnham argued
that the lack of software is a significant
departure from past practice during
comparable rulemakings. Burnham also
asserted that this constituted a lack of
transparency that would violate basic
administrative law precepts and would
be arbitrary and capricious. (Burnham,
No. 35 at p. 3)
After considering these comments,
DOE agrees that further evaluation is
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES4
needed to determine the impact of
adopting ASHRAE 103–2007 on the
AFUE ratings of residential furnace and
boiler models currently distributed in
commerce. As a result, DOE does not
adopt ASHRAE 103–2007 in this final
rule. Instead, DOE retains the reference
in the existing test procedure to
ASHRAE 103–1993, both related to
AFUE and EAE. However, DOE believes
ASHRAE 103–2007 better accounts for
the operation of two-stage and
modulating equipment and may further
evaluate adoption of ASHRAE 103–
2007, or a successor standard, in future
rulemakings. In addition to retaining the
reference to ASHRAE 103–1993, DOE
revises the list of excluded ASHRAE
103–1993 sections to reflect test
procedure amendments (as discussed in
section III.D) and to more accurately
identify the excluded sections.
DOE does not agree with Burnham’s
assertion that the lack of an automated
software program implementing the
equations presented in DOE’s proposal
hampered stakeholder’s ability to
comment on the practicability and the
impact of the adoption of ASHRAE 103–
2007. DOE does not endorse specific
calculations tools commonly developed
by industry or third-party test
laboratories that automate the equations
provided in DOE’s regulations.
Furthermore, DOE does not need to
provide software for interested parties to
be able to perform the calculations in
proposed test procedure amendments
and believes the simplified equations
provided in the proposed rule can be
easily implemented through a desktopsoftware calculation tool such as a
commonly available spreadsheet
application. Lastly, DOE disagrees with
Burnham’s assertion that the proposed
rule was not sufficiently clear to provide
an opportunity for interested parties to
understand the proposal and provide
meaningful comment because each of
the equations utilized was presented in
the regulatory text within the proposed
rule in a step-by-step fashion.
D. Test Procedure Amendments
In response to the March 2015 NOPR,
DOE received input on a variety of test
procedure issues beyond incorporation
of ASHRAE 103–2007, including: (1)
Electrical power of additional
components; (2) smoke stick test for
determining use of minimum default
draft factors; (3) measurement of
condensate under steady-state
conditions; (4) I&O manual reference
and proposed clarifications when the
I&O manual does not specify test setup;
(5) specifying ductwork requirements
for units that are installed without a
return duct; (6) specifying testing
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
requirements for units with multiposition configurations; (7) AFUE
reporting precision; (8) room ambient
temperature and humidity ranges; (9)
full-fuel-cycle (FFC) energy metrics in
the AFUE test; (10) oversize factor
values; (11) alternative methods for
furnace and boiler efficiency
determination; and (12) test method for
combination appliances. DOE amends
the test procedure for residential
furnaces and boilers regarding issues
(1)–(7), which are addressed in further
detail below. Issues (8)–(12), for which
DOE does not amend the test procedure
in this final rule, are discussed in
section III.E. DOE also received
comments on the verification test for
automatic means for adjusting water
temperature, which are discussed in
section III.H.1.
1. Electrical Power of Components
In the January 2013 RFI and March
2015 NOPR, DOE noted that the specific
method of electrical measurement
prescribed in the existing DOE test
procedure does not explicitly capture
the electrical power associated with all
auxiliary components. The method
identifies PE as the electrical power
used to operate the burner but only
explicitly mentions measurements of
the power supplied to the power burner
motor, the ignition device, and the
circulation water pump, but does not
explicitly identify other devices that use
power during the active mode, such as
the gas valve, safety and operating
controls, and a secondary pump for
boilers (i.e., boiler pump) used to
maintain a minimum flow rate through
the boiler heat exchanger, which is most
typically associated with condensing
boiler designs. 78 FR 675, 678; 80 FR
12876, 12882. In response to the January
2013 RFI, several stakeholders,
including Lennox, Rheem, and AHRI,
stated that manufacturers already
measure all electrical power associated
with the additional components DOE
listed in the January 2013 RFI. (Lennox,
No. 6 at p. 3; Rheem, No. 12 at p. 10;
AHRI, No. 13 at p. 6) Therefore, to
clarify which components are included
in the power measurements, in the
March 2015 NOPR DOE proposed to add
two new terms to the calculations of the
average annual auxiliary electrical
energy consumption (EAE) to capture the
electrical power of the boiler pump
(BES) and the gas valve and controls
(EO), if present. DOE requested comment
on these proposed amendments. 80 FR
12876, 12902.
AHRI expressed the view that the
proposed changes over-complicate this
issue and that the proposed
measurements will change the
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
2633
measurement of EAE. AHRI stated that
the typical gas burner will not operate
unless both the ignition system and gas
control (e.g., automatic valves) are
energized, which DOE acknowledges by
including the power of the energized
electric ignition device in the definition
of PE. AHRI stated that the definition of
PE should be clarified to include all
electrical energy consumption that
relates to the functions of igniting and
operating the burner during the on
cycle. (AHRI, No. 36 at p. 5)
Burnham supported DOE’s proposal
to measure all electrical consumption
associated with operating the burner
(PE), which should include the power
consumption of any additional pump
which is needed to provide adequate
flow through the boiler itself without
also providing significant flow through
the heating system. (Burnham, No. 35 at
p. 4)
Lochinvar stated that, in its
experience, all electrical power
consumption measurements made
during an AFUE test are made at the
power supply connection to the boiler
and account for all auxiliary
components. (Lochinvar, No. 29 at p. 2)
Lochinvar stated that while the
proposed change in the measurement of
electrical consumption seems
unnecessary, it does not object to the
revision.
After reviewing the comments on the
March 2015 NOPR, DOE agrees with the
alternative approach suggested by AHRI
to make explicit that all of the electrical
energy provided to the burner is
captured in the EAE measurement.
Rather than including the additional
terms in the equation for EAE as
proposed in the NOPR, DOE clarifies the
definition of PE to include all of the
electrical power that relates to burner
operation, including energizing the
ignition system, controls, gas valve or
oil control valve, and draft inducer, if
applicable.7 In addition, DOE agrees
with Burnham that the electrical power
of the boiler pump, if present, should be
accounted for in the electrical
measurements for boilers. Therefore,
DOE further amends the definition of PE
for boilers to include the electrical
power of the boiler pump. In cases
where the boiler pump power might not
be captured in the electrical power
measurement because it is not operating
at that time, DOE will require the
nameplate power to be added to PE, and
if nameplate power is not available,
then manufacturers must include a
7 The existing DOE test procedure states in
section 10.4.1 that PE is the ‘‘burner electrical
power input at full load steady-state operation,
including electrical ignition device if energized, as
defined in 9.1.2.2 of ASHRAE 103–1993.’’
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
2634
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
default value of 0.13 kW. This is the
same as the current default value for a
circulating water pump, and DOE
understands that the power of the boiler
pump is similar to that of a typical
circulating water pump. DOE revises
sections 8.1, 8.2, and 10.4 of appendix
N to subpart B of 10 CFR part 430 to
reflect the clarification of the definition
of PE.
The revised section 2 of appendix N
defines the individual components that
are measured as part of PE:
• Control means a device used to
regulate the operation of a piece of
equipment and the supply of fuel,
electricity, air, or water.
• Draft inducer means a fan
incorporated in the furnace or boiler
that either draws or forces air into the
combustion chamber.
• Gas valve means an automatic or
semi-automatic device consisting
essentially of a valve and operator that
controls the gas supply to the burner(s)
during normal operation of an
appliance. The operator may be actuated
by application of gas pressure on a
flexible diaphragm, by electrical means,
by mechanical means or by other means.
• Oil control valve means an
automatically or manually operated
device consisting of an oil valve for
controlling the fuel supply to a burner
to regulate burner input.
• Boiler pump means a pump
installed on a boiler that maintains
adequate water flow through the boiler
heat exchanger and that is separate from
the circulating water pump.
Although these definitions were not
explicitly proposed in the NOPR, they
provide additional clarity about the
definition of PE, consistent with the
proposal in the NOPR to improve the
regulatory text to reflect that PE
includes the electrical power of all
auxiliary components.
Carrier noted that DOE in the past had
held to the policy of not making changes
that will negatively impact present
ratings. The electrically-efficient
furnaces ratio, known as ‘‘e’’, will
increase with the additional
requirement, making some products lose
their ENERGY STAR® qualification.
Carrier stated that including additional
electrical components along with the
blower electrical consumption is
equivalent to changing the ENERGY
STAR qualifying standard without
justifying the value. (Carrier, No. 34 at
p. 4)
In response to Carrier’s concerns, DOE
notes that the definition of PE has
always been the electrical energy input
to the burner and that the amendments
adopted in this rule merely make
explicit additional components that are
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
commonly incorporated into burners.
Further, as noted in many other
stakeholder comments, most
manufacturers already measure the
electrical power of all the auxiliary
components that are listed in the
revised definition of PE. Therefore,
clarifying the additional components in
the definition of PE will not affect
ENERGY STAR ratings for most
furnaces. Furthermore, the clarification
of the definition of PE ensures more
accurate and consistent reporting of
energy consumption in the residential
furnaces and boilers market.
Weil-McLain stated that the new
electrical testing requirements would
not allow the manufacturer to
interpolate results from tests because
the electrical load will not scale in the
same manner as other aspects of a
boiler. This means hundreds of new
tests will need to be run, imposing
substantial cost and burden. (WeilMcLain, No. 31 at p. 6)
In response to Weil-McLain’s
comment, DOE notes that only cast iron
sectional boilers may be certified based
on linear interpolation, as specified in
10 CFR 429.18(b)(3). As stated
previously, the amendment of the
definition of PE will not impose
additional burden because it does not
change the definition but merely
clarifies the components included in
measurement of PE. In addition, DOE’s
understanding is that cast iron sectional
boilers are typically non-condensing
models that do not have boiler pumps.
Burnham recommended that DOE
provide regulatory provisions to ensure
that electrical consumption is measured
with the controls normally shipped with
the boiler. Such provisions are required
because in many cases it is impossible
to perform the AFUE test using controls
having an automatic means of adjusting
water temperature, making replacement
of the standard controls during the
AFUE test mandatory. (Burnham, No. 35
at p. 4) DOE notes that the electrical
power measurement during the steadystate test does not account for electrical
power outside of normal steady-state
operation. Therefore, any controls
operation outside of the steady-state
test, such as automatic means for
adjusting water temperature, are not
included in the electrical power
measurement.
2. Smoke Stick Test for Determining Use
of Minimum Default Off-Cycle and
Power Burner Draft Factors
In the March 2015 NOPR, DOE
proposed to leave the default draft factor
values for furnaces and boilers
unchanged from the existing text
procedure. 80 FR 12876, 12885. DOE
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
did not receive any comments on this
issue, and does not amend the default
draft factor values for this final rule.
In addition, to determine if a unit has
no measureable airflow through the heat
exchanger such that manufacturers may
use the minimum default draft factors,
DOE proposed in the March 2015 NOPR
to incorporate a test based on the use of
a smoke stick to establish the absence of
flow through the heat exchanger. DOE
requested input on whether, in addition
to the proposed smoke stick test, other
options exist for indicating the absence
of flow through the heat exchanger. 80
FR 12876, 12902.
Lochinvar stated that it appreciates
and supports the DOE’s affirmation of
the use of smoke for visual
determination of no-flow conditions in
the vent. (Lochinvar, No. 29 at p. 4)
Similarly, Rheem stated that although
the proposed procedure is not
quantitative, it is more definitive than
‘‘absolutely no chance of airflow
through the combustion chamber and
heat exchanger when the burner is off.’’
(Rheem, No. 30 at p. 3)
Ingersoll Rand and Carrier stated that
the proposed procedure requires a
detailed definition of the ‘‘smoke stick
device’’ and test method to be created
and made available. (Ingersoll Rand, No.
37 at p. 5; Carrier, No. 34 at p. 5)
Ingersoll Rand stated that the test
method and materials to be used need
to be explicitly documented to ensure
that all test labs generate repeatable and
reproducible test results. (Ingersoll
Rand, No. 37 at p. 5) Carrier also
requested additional information as to
where smoke sticks can be obtained
commercially. (Carrier, No. 34 at p. 5)
DOE agrees with Rheem that the test
procedure is not quantitative; however,
the purpose of the test is to provide a
visual assessment of no airflow, not a
quantitative measure of airflow.
Regarding the Ingersoll Rand and
Carrier request to provide a detailed
definition of the smoke stick device,
DOE notes that smoke sticks are
commercially available and routinely
used for visualization purposes, and
DOE does not endorse a specific type of
smoke stick device. In addition, DOE
believes that the exact amount of smoke
produced by the smoke stick is not
essential to the reproducibility of the
results.
Ingersoll Rand expressed concern
about air flow in the lab and if
manufacturers can fix their venting such
that air does not flow through it.
(Ingersoll Rand, Public Meeting
Transcript, No. 23 at p. 117) Similarly,
Carrier requested DOE to add
clarification to the procedure to ensure
that the smoke stick is not affected by
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES4
the ventilation system when used.
Carrier also expressed concern about the
use of a smoke-generating device in a
lab area that is not appropriately
ventilated. (Carrier, No. 34 at p. 5)
In response to Ingersoll Rand, DOE
already specified that all air currents
and drafts be minimized for the smoke
stick test in the March 2015 NOPR. For
this final rule, DOE explicitly states that
ventilation should be turned off if the
test area is mechanically ventilated, and
to minimize air currents if there is no
mechanical ventilation. To address
Carrier’s safety concerns, DOE clarifies
that the smoke produced by the smoke
stick must be non-toxic to the test
personnel. DOE is confident that the
smoke stick test as proposed in the
NOPR and modified based on the
clarifications recommended by
stakeholders will ensure repeatable and
reproducible test results. Therefore,
DOE adopts the modified optional
smoke stick test to determine the
absence of flow through the heat
exchanger.
In the March 2015 NOPR, DOE also
proposed to include revisions to the
requirements of sections 8.8.3 and 9.10
of ASHRAE 103–2007 to accommodate
the use of the smoke stick test, and, to
reduce redundancy, to eliminate use of
the term ‘‘absolutely’’ from ‘‘absolutely
no chance of airflow’’ in sections 8.8.3
and 9.7.4 of ASHRAE 103–2007. 80 FR
12876, 12902. DOE received no
comment on these proposals. Even
though DOE has decided not to adopt
ASHRAE 103–2007 and instead retain
reference to ASHRAE 103–1993, the
relevant sections do not differ between
the two versions. Therefore, DOE is
adding sections 7.10 and 8.10 to
appendix N and revising sections 10.2
and 10.3 of appendix N to accommodate
the use of the smoke stick test and is
eliminating the use of the term
‘‘absolutely’’ from ‘‘absolutely no
chance of airflow’’ in sections 8.8.3 and
9.7.4 of ASHRAE 103–1993 (included as
sections 7.10 and 8.9 of appendix N) for
determining the use of the minimum
default draft factors.
3. Condensate Collection During the
Establishment of Steady State
Conditions
In the March 2015 NOPR, DOE
proposed to allow for the condensate
mass to be measured during the
establishment of steady-state conditions,
rather than after steady-state has been
achieved. 80 FR 12876, 12881. Section
9.2 of ASHRAE 103–1993 requires that
the measurement of condensate shall be
conducted during the 30-minute period
after steady-state conditions have been
established. For the March 2015 NOPR,
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
DOE investigated the difference in
condensate mass collected and the rate
of condensate production during the
two separate periods (i.e., during the
establishment of steady-state conditions
and after steady-state conditions have
been reached) and determined that there
is no significant difference in the mass
of condensate collected or the rate of
condensate production during the two
separate timeframes.
In response to the March 2015 NOPR,
Lennox, Lochinvar and AHRI stated
their support for the allowance to
measure condensate during the
establishment of steady-state conditions.
(Lochinvar, No. 29 at p. 2; Lennox, No.
32 at p. 3; AHRI, No. 36 at p.5; Ingersoll
Rand, No. 37 at p. 5) However, Lennox,
AHRI and Ingersoll Rand each noted
that to avoid an unintended
consequence of causing manufacturers
to retest existing models, this change
should be clearly identified as an option
to the current procedure. (Lennox, No.
32 at p. 3 Lennox, No. 32 at p. 3; AHRI,
No. 36 at p.5; Ingersoll Rand, No. 37 at
p. 5) Carrier also agreed that the
condensate collection can be done
during the steady state period, so long
as clarification is added to prevent
testing with dry heat exchangers.
(Carrier, No. 34 at p. 4)
On the other hand, Rheem did not
support allowing the measurement of
condensate during the establishment of
steady state conditions. (Rheem, No. 30
at p.1) Rheem argued that condensate
measurements have a significant impact
on the final calculated AFUE value and
that additional variation in the
condensate measurement procedure will
add variation to the test procedure.
Rheem believes that the time spent to
establish steady-state conditions is
worthwhile and should not be
eliminated. (Rheem, No. 30 at p.1)
DOE understands commenters’
concerns regarding the test burden
associated with the need to retest
existing models to the new test
procedure. Therefore, DOE has made the
ability to measure condensate during
the establishment of steady-state
conditions an option, not a requirement.
This change is incorporated in section
8.4 of appendix N.
In response to Rheem, DOE notes that
test data indicate a similar rate of
condensate mass production in both the
establishment of steady-state, and
measurement of condensate test
intervals. Therefore, DOE does not
expect any impact on AFUE to result
from the allowance of this optional
procedure.
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
2635
4. Installation and Operation Manual
Reference
The existing DOE test procedure
language, which refers in some locations
to ‘‘manufacturer recommendations’’ or
‘‘manufacturer instructions’’, can lead to
the use of ad hoc instructions derived
solely for testing purposes. To clarify
the test procedure language, DOE
proposed in the March 2015 NOPR that
testing recommendations should be
drawn from each product’s I&O manual.
DOE also provided alternate
instructions if the I&O manual did not
contain the necessary testing
recommendations. 80 FR 12876, 12883.
Lastly, in the March 2015 NOPR, DOE
proposed to require manufacturers to
request a test procedure waiver from
DOE when the DOE test procedure
provisions and I&O manuals are not
sufficient for testing a furnace or boiler.
Id. These proposals, comments received,
and responses are discussed in the
following sub-sections.
a. Reference to I&O Manual
DOE did not receive any comments
objecting to reference the
manufacturer’s I&O manuals instead of
‘‘manufacturer’s instructions’’ or
‘‘manufacturer’s recommendations.’’
Therefore, DOE replaces all references
to ‘‘manufacturer’s instructions’’ or
‘‘manufacturer’s recommendations’’ in
ASHRAE 103–1993 with ‘‘I&O manual’’
in appendix N.8 However, in response
to the March 2015 NOPR, Burnham
suggested revising the definition of I&O
manual in section 2.7 because many oil
boilers do not carry a safety listing as a
packaged unit; rather, they are
comprised of separately listed
components. (Burnham, No. 35 at p. 5)
DOE agrees with Burnham that some
boilers do not carry safety listings as
packaged units and thus excludes the
reference to the product’s safety listing
in the adopted definition of I&O manual
in section 2 of appendix N.
b. Proposed Specific Instructions for
Adjusting Combustion Airflow
In the NOPR, DOE proposed specific
instructions for adjusting combustion
airflow to achieve an excess air ratio,
flue O2 percentage, or flue CO2
percentage to within the middle 30th
percentile of the acceptable range
specified in the I&O manual. AHRI
stated that the specification of ‘‘the 30th
percentile of the acceptable range’’ is
confusing. The 30th percentile is a
8 DOE replaced references in sections 7.1, 7.2.2.2,
7.2.2.5, 7.2.3.1, 7.8, 8.2.1.3, 8.3.3.1, 8.4.1.1,
8.4.1.1.2, 8.4.1.2, 8.4.2.1.4, 8.4.2.1.6, 8.7.2, and
9.5.1.1 of ASHRAE 103–1993 with sections 6.1, 6.2,
6.3, 6.4, 6.5, 7.1, 7.2, 7.3, 7.4, 7.5, 7.6, 7.7, 7.9, and
8.5 of appendix N, respectively.
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
2636
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
single value so it is not clear what is
meant by ‘‘the middle of the 30th
percentile.’’ (AHRI, No. 36 at p. 3)
Ingersoll Rand stated that the proposed
burner adjustments are more restrictive
than both the current test procedure and
the specifications found in ASHRAE
Standard 103–2007. (Ingersoll Rand, No.
37 at p. 6) Burnham stated that while it
supports DOE’s effort to more closely tie
air fuel ratio used during the test with
what can be expected in the field, DOE
needs to recognize that the industry
practice has been to use the CO2 at the
top end of the range (or in some cases
even higher) in the I&O manual.
(Burnham, No. 35 at p. 4) Lochinvar
objected to the proposed changes,
stating that forcing boiler manufacturers
to test at the maximum input rate and
the middle air-fuel ratio is not typical of
field installations, is inconsistent with
past rating methods, and will force
manufacturers to rerate boilers based on
this test procedure change. Lochinvar
suggested adopting language from
section 5.3 of AHRI Standard 1500,
which uses the CO2 at the top of the
manufacturer’s specified range, to
provide improved clarity and specificity
regarding the air-fuel adjustment and to
be more consistent with current
industry practice, with much less
potential to force manufacturers to retest
and rerate existing products.9
(Lochinvar, No. 29 at pp. 2–3)
Lennox, AHRI, and Burnham noted
that the proposed adjustment of the CO2
percentage on gas- and oil-fired boilers
would significantly affect AFUE.
(Lennox, No. 32 at p. 3; AHRI, No. 36
at pp. 3–4; Burnham, No. 35 at pp. 2, 4)
AHRI stated that the results of the
testing of three residential boilers that it
conducted at Intertek Testing
Laboratories indicate that the proposed
revised burner setup requirements
change AFUE by 0.3 percent for each 1
percent difference in the CO2 values.
(AHRI, No. 36 at pp. 3–4) Burnham
stated that based on test data that it
provided, for an oil-fired hot water
boiler with an 11.5 to 12.5 percent CO2
adjustment range in the I&O manual,
DOE’s proposed adjustment would
reduce AFUE by as much as 1.0 percent
compared to the rating under the
existing test procedure. (Burnham, No.
35 at p. 2) Burnham stated that the
proposed change to the requirements for
adjusting CO2 will have a significant
impact on the existing ratings for many
boilers, and that DOE needs to take this
into account when evaluating the
burden imposed by this rule, as well as
promulgating the parallel residential
boiler standards rulemaking currently
underway. (Burnham, No. 35 at p. 4)
Carrier, Ingersoll Rand, and Rheem
stated that most modern furnaces do not
have the capability to make combustion
air adjustments because the practice of
including primary air shutters is no
longer widely used on modern gas
furnaces with fan-assisted or power
burners. (Carrier, No. 34 at pp. 3–4;
Ingersoll Rand, No. 37 at p. 6; Rheem
No. 30 at p. 3) AHRI and Burnham also
stated that for many gas furnaces and
boilers that use atmospheric burners or
other equipment with no means of
adjusting CO2 in the field, these
adjustments to the excess air ratio
cannot be made. (AHRI, No. 36 at p. 3,
Burnham, No. 35 at p. 4) Carrier,
Ingersoll Rand, and Burnham stated that
DOE needs to exclude from these
requirements burners that have no
capability to make combustion air
adjustments. (Carrier, No. 34 at pp. 3–
4; Ingersoll Rand, No. 37 at p. 6;
Burnham, No. 35 at p. 4)
Burnham stated that some type of
tolerance is needed for adjusting CO2
when the I&O manual provides only a
single or maximum value, as opposed to
a range. To address this issue, Burnham
suggested adopting the language in
section 5.3 of AHRI Standard 1500,
which essentially sets a fixed tolerance
of ±0.1 percent and uses the CO2 at the
top, as opposed to the middle, of the
manufacturer’s specified range.10
(Burnham, No. 35 at p. 4)
After reviewing stakeholders’
comments on the specific instructions
for adjusting combustion airflow, DOE
concurs that further study is needed to
determine the impact on AFUE of the
CO2 percentage proposed in the March
2015 NOPR and the AHRI 1500
requirements suggested by certain
stakeholders. As such, for this final rule,
DOE does not adopt the specific
instructions for adjusting combustion
airflow to achieve an excess air ratio,
flue O2 percentage, or flue CO2
percentage to within the middle 30th
percentile of the acceptable range
specified in the I&O manual. Instead, in
sections 7.3 and 7.5 of appendix N, DOE
retains the instructions in accordance
with ASHRAE 103–1993 section 8.4.1.1
for gas burners to set the primary air
shutters to give a good flame with no
deposit of carbon during the test
procedure, and section 8.4.1.2 for oil
burners to give a CO2 reading as
specified in the I&O manual and an
hourly Btu input within ±2% of the
9 AHRI Standard 1500 is available at https://
ahrinet.org/site/686/Standards/HVACR-IndustryStandards/Search-Standards.
10 AHRI Standard 1500 is available at https://
ahrinet.org/site/686/Standards/HVACR-IndustryStandards/Search-Standards.
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
normal hourly Btu input rating as
specified in the I&O manual. DOE
understands from stakeholder
comments that the instructions in the
existing test procedure to adjust the
primary air shutters for gas units are not
applicable to many modern furnaces
and boilers. However, DOE has
determined that further investigation is
required before amending these test
procedure requirements.
c. Waiver Process for Additional Test
Instructions
In response to DOE’s proposal that
manufacturers request a test procedure
waiver from DOE when the DOE test
procedure provisions and I&O manuals
are not sufficient for testing a furnace or
boiler, Burnham stated that the
proposed waiver process is unduly
burdensome, given the use of
increasingly complex control and
burner systems. To reduce the frequency
with which waivers are required,
Burnham suggested that DOE adopt a
repository for ‘‘special test instructions’’
similar to that which DOE currently has
in place for commercial boilers.
(Burnham, No. 35 at p. 5) Lennox and
AHRI similarly stated that if DOE is
concerned about the situation where the
manufacturer does not provide any
recommended settings in the I&O
manual, DOE should allow
manufacturer to provide information on
unit setup for testing as part of the
certification report as is done for
commercial and industrial equipment.
(Lennox, No. 32 at p. 3; AHRI, No. 36
at pp. 4, 6)
In response to stakeholders’
comments, DOE notes that
manufacturers have control over what
information is specified in the I&O
manual. Furthermore, the test procedure
provides defaults for most requirements
that are based on the I&O manual. As
such, DOE believes the instructions
given in the test procedure and I&O
manuals should be sufficient for testing
in most cases. Therefore, DOE is not
amending its certification provisions to
permit manufacturers to report testspecific instructions as supplemental
information in cases where the I&O
manual does not provide instructions,
and is implementing the requirement to
request a waiver in section 6.1.a of
appendix N. DOE also notes that the
waiver procedure provides a feedback
loop by which DOE learns of issues
manufacturers are encountering with
the test procedure and yields
amendments to the test procedure
through rulemaking to address those
issues.
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES4
5. Duct Work for Units That Are
Installed Without a Return Duct
In the March 2015 NOPR, DOE
proposed to add a provision in the test
procedure clarifying that the return
(inlet) duct is not required during
testing for units that, according to the
I&O manual, are intended to be installed
without a return duct. 80 FR 12876,
12902–12903.
In response, Rheem, Carrier, and
Ingersoll Rand agreed that a unit that is
intended to be installed without a return
duct should be tested without a return
duct. (Rheem, No. 30 at p. 3; Carrier, No.
34 at p. 6; Ingersoll Rand, No. 37 at p.
5) In addition, Carrier recommended
that DOE adopt figure 2 in exhibit 1 of
Carrier’s comment, which clarifies the
use of a return duct for gas furnaces.
(Carrier, No. 34 at p. 6)
DOE agrees with stakeholders and
adopts the amendment clarifying that
units intended to be installed without a
return duct are not required to use the
return (inlet) duct during testing. After
reviewing the figure provided by
Carrier, DOE believes that the language
is sufficient and an additional figure is
unnecessary.
6. Testing Requirements for MultiPosition Configurations
In the March 2015 NOPR, DOE
proposed to require that multi-position
furnaces be tested using the leastefficient position.11 DOE also proposed
to explicitly allow manufacturers to test
multi-position furnaces in other
configurations and report the AFUE
ratings for each position. 80 FR 12876,
12886.
In response, AHRI stated that they
believe that manufacturers already test
in the least-efficient configuration.
(AHRI, Public Meeting Transcript, No.
23 at p. 123)
Carrier stated that in the past, it has
tested and displayed the AFUE by
orientation of installation; however, it
no longer does so because the multiple
ratings by position did not give
customers any benefit. Because the
setup requirements of the DOE test
procedure already cause furnaces to
operate at the lowest efficiency, thus
making AFUE ratings conservative for
the average installation, Carrier
recommended that DOE drop the
requirement to test in all positions and
simplify the testing to be in the most
commonly installed position of the
furnace. If DOE were to require testing
in all positions, Carrier proposed an
11 A multi-position furnace is a furnace that can
be installed in more than one airflow configuration
(e.g., upflow or horizontal; downflow or horizontal;
and upflow, downflow or horizontal).
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
alternative to allow single rating that is
weighted based on percent of
applications by configuration and
installation location to reduce sample
testing burden and not confuse
consumers with excess information.
(Carrier, No. 34 at pp. 6–8)
Lennox disagreed with the testing
requirements in multiple configurations
because of the increased test burden and
lack of improved test accuracy. (Lennox,
No. 32 at pp. 3–4)
In response to Carrier’s and Lennox’s
concerns about increased test burden if
required to test in all configurations,
DOE clarifies that in the March 2015
NOPR, DOE did not propose to require
manufacturers to test in all positions,
but rather to require testing only in the
least efficient configuration while
explicitly allowing manufacturers to test
in multiple configurations if they wish.
DOE notes that, as stated by AHRI, it is
already common industry practice to
test in the least efficient configuration;
accordingly, DOE anticipates that there
will be no additional test burden from
the clarification to require testing in the
least efficient configuration. Regarding
Carrier’s suggestion to test in the
dominant installed position, DOE
believes that testing in the least efficient
position will provide ratings that are
more comparable between different
models because the dominant position
may not be the least efficient
configuration and may vary among
models and among manufacturers. DOE
believes that Carrier’s suggestion of a
weighted rating is not practicable
because DOE is not requiring
manufacturers to test in all
configurations, only the least efficient
one. Therefore, in section 6.1.b of
appendix N and in 10 CFR 429.18, DOE
amends its regulations to require testing
and rating only in the least efficient
configuration, while still allowing
manufacturers the ability to test and rate
in multiple configurations. In addition,
DOE includes a definition for multiposition furnace in section 2 of
appendix N.
In the March 2015 NOPR, DOE also
proposed to allow testing of units
configured for multiple position
installations to use the blower access
door as an option instead of one of the
inlet openings. 80 FR 12876, 12886
(March 11, 2015). In response, Rheem
stated that a furnace should not be
tested in a configuration that is
prohibited by the installation manual.
For example, Rheem stated that its
furnace installation manuals allow only
bottom and side returns. A rear return
and a return in place of the blower
access door are not allowed. (Rheem,
No. 30 at p. 4) Ingersoll Rand stated that
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
2637
testing of multi-position units using the
blower access door may not be feasible
option for some furnaces, and the
manufacturer should state whether this
is an acceptable test method for the
furnace model. (Ingersoll Rand, No. 37
at p. 6)
DOE agrees with Rheem and Ingersoll
Rand that units should not be required
to be tested using the blower access
door if not allowed in the I&O manual
or if not feasible. In an effort to ensure
consistent and appropriate testing, DOE
withdraws its proposal that would have
explicitly allowed the use of the blower
access door for testing of multi-position
furnaces and boilers that are not
shipped with an open inlet.
7. AFUE Reporting Precision
DOE’s existing furnaces and boilers
test procedure specifies that the AFUE
rating be rounded to the nearest whole
percentage point. 10 CFR 430.23(n)(2).
In the March 2015 NOPR, DOE sought
comment on its proposal to report AFUE
to the nearest tenth of a percentage
point. 80 FR 12876, 12902.
AHRI, Lochinvar, Lennox, and
Burnham support reporting of AFUE to
the nearest tenth of a percentage point
and noted that it reflects the current
practice. (AHRI, No. 36 at p. 6;
Lochinvar, No. 29 at p. 4; Lennox, No.
32 at p. 3; Burnham, No. 35 at p. 6)
However, Burnham does not agree with
the proposal to round to the nearest 0.1
percent, stating that it would be a direct
violation of 10 CFR 429.18(a)(2)(i)(B)
requiring any representative value of
AFUE for which consumers would favor
higher values to be less than or equal to
the lower of the mean of the sample or
the lower 97.5 percent confidence limit
(LCL) of the true mean divided by 0.95.
Burnham stated that rounding up would
allow the representative value to
potentially be higher than allowed by
calculation mentioned. Burnham urged
DOE to prescribe the current industry
practice of truncating to 0.1 percent.
(Burnham, No. 35 at pp. 6–7)
In contrast, Rheem stated that rating
furnaces to the nearest tenth of a
percentage point will give consumers
the impression that one furnace is more
efficient than another, while in
actuality, the test procedure tolerances
do not result in the proposed level of
precision that should be required to
support reporting AFUE to the nearest
tenth of a percentage point. (Rheem, No.
30 at p. 3)
Ingersoll Rand stated that while
DOE’s CCMS can accommodate
reporting AFUE to this level, any
manufacturer that reports AFUE to the
whole percentage point will have to
submit new certification reports and
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
2638
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
relabel products. Ingersoll Rand stated
that having to submit new certification
reports and relabel products will cause
an administrative burden and cost to
manufacturers that was not addressed in
the March 2015 NOPR. Ingersoll Rand
requested that DOE consider setting the
effective date of this requirement to
coincide with the effective date of any
amended energy conservation standard
adopted under the March 12, 2015
energy conservation standards NOPR for
residential furnaces. (Ingersoll Rand,
No. 37 at p. 6)
AHRI stated that it reports to the
nearest tenth to DOE for furnaces but
not for boilers due to Environmental
Protection Agency (EPA) and ENERGY
STAR requirements. (AHRI, Public
Meeting Transcript, No. 19 at p. 89)
Burnham urged DOE to work with the
EPA to simultaneously update the
ENERGY STAR requirement of rounding
to the nearest whole percentage point to
avoid conflicting values on the DOE and
ENERGY STAR Web sites. (Burnham,
No. 35 at p. 7)
DOE understands that reporting AFUE
values to the nearest tenth of a
percentage point is currently industry
practice. Based on 10 CFR
429.18(a)(2)(i)(B), DOE agrees with
Burnham that AFUE should be
truncated to the tenth of a percentage
point. In response to Rheem’s comment
about the test procedure tolerances,
DOE notes that in response to the
January 2013 RFI, Rheem stated that this
level of precision has been
demonstrated to be statistically possible.
(Rheem, No. 12 at p. 9). DOE also
observes that Rheem, as well as many
other manufacturers, reports AFUE to
the tenth of a percentage point in DOE’s
Compliance Certification Database and
the AHRI directory for some models. In
response to Ingersoll Rand’s comments,
DOE notes that AHRI’s certification
directories for both furnaces and boilers
as well as DOE’s Compliance
Certification Database already allow
manufacturers to report AFUE to the
nearest tenth of a percentage point.
Therefore, DOE anticipates this
clarification will not require changing
the reported efficiency in manufacturer
literature, nor will it cause significant
manufacturer burden. Furthermore, in
response to AHRI and Burnham, DOE
notes that EPA must use the method of
test, sampling plan, and representation
requirements adopted by DOE. DOE will
work with EPA to make sure the
language in its specification is
harmonized with federal regulations.
Accordingly, DOE updates the existing
requirement for residential furnaces and
boilers in 10 CFR 430.23(n)(2) to
truncate AFUE to the tenth of a
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
percentage point. DOE also clarifies in
10 CFR 429.18 that the represented
value of AFUE based on the tested
sample must be truncated to the tenth
of a percentage point.
8. Definitions and Other Changes
In this final rule, DOE revises the term
‘‘seasonal off switch’’ to ‘‘off switch’’
and revises the definitions of ‘‘off
mode’’ and ‘‘standby mode’’ in section
2 of appendix N to reflect the updated
definitions found in the second edition
of IEC 62301, which was incorporated
by reference in the December 2012 final
rule. DOE also revises sections 8.1, 8.2,
and 8.4 of the existing appendix N
(sections 8.3, 8.5, and 8.7 of the
amended appendix N) to clarify and
improve the test instructions. DOE also
revises sections 10.4, 10.5, 10.6, 10.7.3,
10.9, 10.9.1, and 10.11 of appendix N to
improve grammar and consistency in
formatting throughout the test
procedure, and to include missing
variable definitions. In addition, DOE
incorporates the previously excluded
section 9.7.l of ASHRAE 103–1993 to
include instructions on the setup of the
tracer gas test. DOE updates the
definition of ‘‘isolated combustion
system’’ in section 2.5 of the existing
appendix N (2.8 of the amended
appendix N) to reflect the updated
definition in ASHRAE 103–2007.
Finally, DOE modifies section 8.3 of the
existing appendix N (8.6 of the amended
appendix N) to clarify that the
referenced time delay is the blower
delay t+. DOE did not receive comment
on any of these revisions where
proposed in the NOPR.
E. Other Test Procedure Considerations
1. Room Ambient Air Temperature and
Humidity Ranges
In the March 2015 NOPR, DOE
proposed not to change the test
procedure regarding room ambient
temperature and humidity conditions,
neither by mathematical correction nor
by limiting the existing ambient
condition range, and requested input on
this approach. 80 FR 12876, 12889.
Lochinvar and Lennox stated their
support for DOE’s proposal not to
further restrict the ambient conditions
due to the additional test burden it
would cause. (Lochinvar, No. 29 at p. 4;
Lennox, No. 32 at p. 4) Rheem stated
that they believe that the ambient
conditions range requires further study.
Rheem noted that the room ambient air
temperature and humidity ranges were
developed based on 30-year-old
laboratory conditions and that
laboratory conditions may be more
carefully controlled today compared to
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
the long past. (Rheem, No. 30 at p.1)
AHRI noted that the new edition of
ASHRAE–103–2016 will be issued for
public review and one of the proposed
amendments is to include changes to
the definition of room ambient air
operating conditions. (AHRI, No. 36 at
p. 5)
Burnham stated that they disagree
with DOE’s assertion in the March 2015
NOPR that relative humidity (RH) has a
minimal impact on the AFUE of
condensing boilers and stated that the
issue should be revisited. Burnham
provided test data of a condensing
boiler which shows a swing in AFUE of
approximately 1.3 percent when the RH
was changed from approximately 30
percent to 70 percent. Burnham stated
that they expect the variation in AFUE
as a function of RH to be at least as large
for boilers as it is for furnaces. Burnham
noted that the flue temperature of
boilers is closely linked to the return
water temperature during the test
(120 °F), which is close to the typical
dew point of natural gas flue products.
Changes in RH may therefore have a
large impact on where the temperature
of the flue products falls below the dew
point as they pass through the heat
exchanger. Burnham stated that if
ambient conditions have a significant
impact on AFUE, DOE should tighten
the tolerance for RH to conditions likely
to be seen in the field, even if this
results in an increased burden for
manufacturers in the form of requiring
conditioned lab facilities. (Burnham,
No. 35 at p. 7)
DOE agrees with Rheem and Burnham
that the impact of ambient conditions
on AFUE warrants further study.
However, at this time DOE does not
have adequate data to justify the testing
burden associated with the narrowing of
ambient conditions. Therefore, DOE
maintains the ambient conditions
specified in the current test procedure.
2. Full-Fuel-Cycle Energy Metrics
In the March 2015 NOPR, DOE stated
that the test procedure rulemaking was
not the appropriate vehicle for deriving
an FFC energy descriptor for furnaces
(and other products). Specifically, DOE
noted that if a secondary FFC energy
descriptor were included as part of the
furnace and boiler test procedure, DOE
would need to update the test procedure
annually. DOE indicated its intent to
estimate FFC energy savings in future
energy conservation standards
rulemakings for furnaces, and to take
those savings into account in proposing
and selecting amended standards. 80 FR
12876, 12896.
In response to the NOPR, AGA
expressed their disagreement with
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
DOE’s position, stating that the test
procedure develops the energy
efficiency rating for the product and is
specifically the correct vehicle to be
used for determining the FFC energy
descriptor. AGA added that all that is
needed is a mathematical adjustment to
the site-based energy descriptor now
determined by the test procedure. AGA
requested that the Department
reconsider its decision not to include
provisions for an FFC energy descriptor
and incorporate one in the test
procedures for residential boilers and
furnaces. (AGA, No. 27 at p. 3)
DOE maintains its position outlined
in the NOPR that it does not believe that
a mathematical adjustment to the test
procedure to account for FFC is
appropriate. As noted in the March 2015
NOPR, the mathematical adjustment to
the site-based energy descriptor relies
on information that is updated annually.
If DOE were to include such an
adjustment to the test procedure, DOE
would be required to update the test
procedure annually.
tkelley on DSK3SPTVN1PROD with RULES4
3. Oversize Factor Value
In the March 2015 NOPR, DOE
proposed to maintain the existing
oversize factor of 0.7 and sought
comment on the appropriateness of this
strategy.12 80 FR 12876, 12891.
Rheem stated that replacement
furnaces are more likely to be oversized
than a new construction furnace
because the unit may not be resized
when it is replaced with a more efficient
unit. Rheem also noted that it is more
likely for a furnace to be oversized in a
climate with high variation in outdoor
temperature, or if it is installed in an
area with high airflow requirements for
the cooling load. (Rheem, No. 30 at p.
4)
DOE agrees with Rheem that a variety
of factors, including construction type
and climate, may influence the
magnitude of oversizing that occurs in
a given installation. DOE did not receive
any data supporting a change to the
existing oversize factor of 0.7. DOE has
determined the existing value of 0.7
continues to be representative of the
oversized factor applicable to the
average U.S. household and therefore
maintains that value.
12 The ‘‘oversize factor’’ accounts for the national
average oversizing of equipment that occurs when
a heating product is sized to satisfy more than the
heating load of the household. This is typically
done to size the equipment so that it is able to
satisfy the days in which the house heating
requirements might be exceeded and/or to take into
account uncertainties regarding house heating load.
For example, a 0.7 oversize factor is equivalent to
170-percent oversizing of the heating equipment
(i.e., 70 percent greater input capacity than is
required).
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
4. Alternative Methods for Furnace/
Boiler Efficiency Determination
In response to the March 2015 NOPR,
Carrier questioned the need for a test
method as precise as ASHRAE 103 due
to the advances that have been made in
reducing cyclical losses. Carrier noted
that the difference between steady state
efficiency and cyclical AFUE is less
than 1 percent across all model types.
Carrier suggested that DOE change the
AFUE metric for forced-air furnaces to
be based on the steady-state operation.
(Carrier, No. 34 at p. 2) Carrier stated
that this would simplify the test
procedure and relieve significant
burden from manufacturers. Carrier
stated that the lab setup of gas furnaces
during AFUE testing—including vent
length, isolated combustion system
(ICS) installation, off cycle times, and
blower off delay time—rarely replicates
the actual installation of condensing gas
furnaces. (Carrier, No. 34 at p. 2)
DOE agrees that there have been
significant advances in the
minimization of cyclical losses since the
inception of the AFUE metric. However,
including cyclical losses, which are
captured in the AFUE metric, still
provides market differentiation for
models that would yield the same
steady-state values. Furthermore, DOE
believes that the inclusion of cyclical
losses in the AFUE metric has
contributed to the increases in
efficiency noted by Carrier. For these
reasons, DOE declines to limit the
calculation of AFUE to steady-state
operation. DOE would be willing to
work with industry to investigate this
further to see if moving to a steady-state
methodology has merit and meets the
requirements of the statute.
5. Test Method for Combination
Appliance
In the March 2015 NOPR, DOE
discussed the possibility of creating a
test procedure for determining the
efficiency of combination products.
Ultimately DOE did not propose to
amend the test procedure to include a
method of test for combination
appliances choosing not to complicate
the test procedure rulemaking. 80 FR
12876, 12894.
In response to the NOPR, Ingersoll
Rand believes that EPCA anticipated
products being capable of serving more
than one function and expects DOE to
set separate energy efficiency metrics for
each major function. Ingersoll Rand
noted that EPCA authorizes DOE to ‘‘set
more than 1 energy conservation
standard for each major function.’’ (42
U.S.C. 6295(o)(5)) Ingersoll Rand
suggested that establishing a
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
2639
combination metric and setting a
standard for a combination unit is
contrary to EPCA. (Ingersoll Rand, No.
37 at p. 6)
DOE did not propose a combination
metric in the NOPR, and does not
amend the test procedure to include
such a metric in this final rule.
F. Test Burden
EPCA requires that the test
procedures DOE prescribes or amends
be reasonably designed to produce test
results that measure the energy
efficiency, energy use, water use (in the
case of showerheads, faucets, water
closets, and urinals) or estimated annual
operating cost of a covered product
during a representative average use
cycle or period of use. These procedures
must also not be unduly burdensome to
conduct. (42 U.S.C. 6293(b)(3))
In response to the March 2015 NOPR,
Ingersoll Rand stated that the testing
and reporting burden from the proposals
would be far greater than the average 20
hours per response that DOE estimates.
(Ingersoll Rand, No. 37 at p. 9) WeilMcLain expressed concerns that the cost
of the proposed test is grossly
underestimated and that cost analysis
for all of the testing is fundamentally
flawed and incomplete. Weil-McLain
stated that a more appropriate estimate
for the cost to re-test all models in
DOE’s example of average small boiler
business with 70 basic models would be
more than twenty times the estimate
shown for various reasons, such as the
cost of set up for each test, test re-runs
if parameters are not met, test recording,
and analysis time. In addition, WeilMcLain stated that: (1) Only the
incremental cost related to the changes
in procedure have been captured when
in all likelihood all products will have
to be retested through the entire test
procedure; (2) at least two tests per
model are required for data submittal;
(3) initial certification and annual audits
require an additional witness test by a
third-party lab; (4) engineering, facility,
or other charges were not captured; (5)
third-party test agency fees were not
considered; and (6) the time required to
test the number of models for the
manufacturer and third-party test
agency capacity were not considered.
Weil-McLain also stated that retesting
and re-rating would take substantially
longer than 180 days. (Weil-McLain, No.
31 at pp. 6–7) Ingersoll Rand stated that
to retest all of its current models will
require more than six months of lab
time with a cost of over $400,000.
(Ingersoll Rand, No. 37 at p. 9)
Weil-McLain questioned why DOE
would impose the burden of conducting
all of the new tests on manufacturers
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
2640
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
when DOE stated that the results from
using new test procedures will not
change when compared to current
procedure. (Weil-McLain, No. 31 at p. 2)
Several stakeholders requested more
time to conduct re-testing after the
issuance of the final rule. Weil-McLain
stated that the process of conducting all
the tests, analyzing information, and
conducting re-certification through the
certified labs for hundreds of models
cannot be completed within 180 days of
when the final rule is issued. (WeilMcLain, No. 31 at p. 7) Similarly,
Burnham expressed concern that it has
found it impossible to thoroughly
evaluate the impact of this NOPR, as it
asserted that DOE provided only a short
amount of time and inadequate
information and resources during the
rulemaking process. (Burnham, No. 35
at p. 8) Goodman stated that the
industry needs at least 6 months to
assess the impact of the new test
procedure on existing basic models.
(Goodman, No. 33 at p. 2)
Ingersoll Rand argued that the fact
that many of the current models may be
removed from the market as a result of
the separate energy conservation
standards rulemakings, Fan Energy
Rating (FER) standard effective in 2019
and AFUE proposed standard effective
in 2021, makes this retesting effort even
more burdensome, unnecessary and
wasteful. (Ingersoll Rand, No. 37 at p. 9)
Carrier also stated that recent
rulemakings, such as the standby power
ruling and the recent legislation for
furnace fans, have increased the test
burden for gas furnace compliance
compared to when the complicated
AFUE procedure was formulated and
first implemented. (Carrier, No. 34 at p.
3)
The many comments from
manufacturers regarding re-testing of all
models currently in distribution were
responding to DOE’s proposals to
incorporate by reference ASHRAE 103–
2007 and adjust the CO2 percentage.
Under the amended test procedure, DOE
is not incorporating by reference
ASHRAE 103–2007 or adjusting of the
CO2 percentage, and so manufacturers
will not need to re-test their entire
model line-up, thereby alleviating the
concerns expressed by manufacturers.
DOE has assessed the test burden of the
revisions to the test procedure it is
adopting in this final rule, and has
concluded that manufacturers will
experience no additional burden when
performing the AFUE test.
DOE believes that the clarification of
the electrical power term PE will not
add any additional burden on
manufacturers, since this is what has
been required under the existing test
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
procedure. In terms of the boiler pump,
DOE included a default value in case
manufacturers are not currently
capturing this component, which will
minimize test burden.
Many manufacturers currently
perform the tracer gas test to determine
whether the minimum default draft
factor of 0.05 may be used. DOE expects
that, when establishing the absence of
flow through the heat exchanger, the use
of the smoke stick test will reduce the
test burden to manufacturers by
eliminating, in some cases, the need for
the tracer gas test.
The optional provision allowing for
the measurement of condensate during
the establishment of steady-state
conditions will provide manufacturers
of condensing furnaces and boilers time
and labor savings.
The inclusion of references to the I&O
manual will provide additional
guidance and clarity to the test
procedure. It does not impose additional
test burden since the information is
already available in the manufacturers’
literature.
The amendment of the duct work
setup for units that are installed without
a return duct and the requirement to test
multi-position units in the least efficient
position only clarify the testing
requirements. The duct work setup
change reflect current industry practice
and does not introduce new testing
requirements. With respect to the multiposition unit testing, most
manufacturers indicated that the change
reflects their understanding and current
practice. DOE notes that, although the
test method did not describe the
position for testing as the ‘‘least efficient
position,’’ in practice, if following the
existing method for setup,
manufacturers should have tested the
least efficient position or all testing
configurations. DOE also notes that
AHRI commented that this reflects the
common practice of its members, which
is to test in the least efficient position.
(AHRI, Public Meeting Transcript, No.
23 at p. 123) Therefore, DOE expects
that there would be no additional test
burden associated with these revisions.
The requirement to report AFUE to be
truncated to the tenth of a percentage
point and the requirement to report
whether a boiler uses a burner delay
automatic means control strategy will
not introduce any additional test burden
because they do not require retesting;
however, they may impose a cost on
either boiler manufacturers or
manufacturers who do not currently
report AFUE to a tenth of a percentage
point, who must submit new
certification reports and relabel their
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
products. DOE discusses this burden in
section IV.B.
For these reasons, DOE concludes that
the amended test procedure will not be
unduly burdensome to conduct.
G. Measured Energy Use
When DOE modifies test procedures,
it must determine to what extent, if any,
the new test procedure would alter the
measured energy efficiency or energy
use of any covered product. (42 U.S.C.
6293(e)(1)) In the NOPR, DOE stated
that the one amendment that might alter
the AFUE of covered products is the
incorporation by reference of ASHRAE
103–2007. 80 FR 12876, 12897.
As discussed in section III.C, based on
stakeholder comments, DOE has
declined to incorporate by reference
ASHRAE 103–2007 in this final rule.
Therefore, the amended test procedure
will not alter measured AFUE ratings.
As discussed in section III.D.1, certain
stakeholders commented that the
proposed revision in the NOPR
regarding the method for determining
the electrical power consumption would
change the power measurements. In
response to comments, for the Final
Rule, DOE decided not to change the
method for calculating the electrical
consumption and only clarified the
definition of the PE term. This
clarification will not alter measured
AFUE ratings.
As discussed in section III.D.3, certain
stakeholders expressed concern that
allowing the measurement of
condensate during the establishment of
steady state conditions would have an
impact on the final calculated AFUE
value. In response to comments, DOE
clarified for the final rule that this is an
option rather than a requirement. DOE
has found through its testing as shown
in the test data presented at the NOPR
public meeting indicating both options
produce a similar rate of condensate
mass production and therefore would
have a de minimis impact on measured
AFUE ratings.
As discussed in section III.D.4.b,
certain stakeholders expressed concern
that the proposed adjustment of the CO2
percentage on gas- and oil-fired boilers
would significantly affect AFUE. In
response to comments, DOE has
declined to adopt this proposal for the
final rule.
DOE received no comment regarding
the impact of measured energy use on
the remaining test procedure
amendments, including the smoke stick
test, duct work for units that are
installed without a return duct, and
testing requirements for multi-position
configurations. The smoke stick test
serves to verify a condition and does not
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
impact ratings. The requirements for
units installed without a return duct
and for multi-position configurations
only clarify the testing requirements,
and therefore will not impact measured
energy use or efficiency.
For these reasons, DOE has
determined that none of the adopted test
procedure amendments would alter the
projected measured energy efficiency or
energy use of the covered products that
are the subject of this rulemaking.
tkelley on DSK3SPTVN1PROD with RULES4
H. Certification and Enforcement
1. Verification Test for Automatic
Means for Adjusting the Water
Temperature in Boilers
In 2008, DOE published a technical
amendment to the 2007 energy
conservation standards final rule for
residential furnaces and boilers that
added design requirements for boilers
consistent with the provisions of EISA
2007, including mandating, starting
September 1, 2012, that all gas, oil, and
electric hot water boilers (excluding
those equipped with a tankless domestic
water heating coil) be equipped with
automatic means for adjusting the boiler
water temperature (‘‘automatic means’’)
to ensure that an incremental change in
inferred heat load produces a
corresponding incremental change in
the temperature of water supplied
(codified at 42 U.S.C. 6295(f)(3)).13 73
FR 43611 (July 28, 2008). EISA 2007
further specifies that for single-stage hot
water boilers, the automatic means
requirement may be satisfied by
incorporating controls that allow the
burner or heating element to fire only
when the automatic means has
determined that the inferred heat load
cannot be met by the residual heat of the
water in the system. When there is no
inferred heat load, the automatic means
limits the temperature of the water in
the boiler to not more than 140 °F.
The existing DOE residential furnace
and boiler test procedure does not
include any method of test for
determining compliance with these
design requirements. In the March 2015
NOPR, DOE proposed the introduction
of a new test method for the verification
of the automatic means for adjusting the
water temperature in boilers. DOE
proposed the use of two test methods—
one for single-stage boilers and one for
two-stage/modulating boilers—for
verification of the functionality of the
automatic means for adjusting the water
13 The automatic means requirement excludes
boilers that are manufactured to operate without
any need for electricity. EISA 2007 also prohibited
constant-burning pilot lights for gas-fired hot water
boilers and gas-fired steam boilers. 73 FR 43611,
43613 (July 28, 2008).
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
temperature supplied by a boiler. The
proposed test methods were based on
draft testing methodologies provided by
Natural Resources Canada (NRCan), as
well as the California mechanical codes
section for non-residential boilers.14
The two separate tests were developed
to accommodate various boiler control
strategies, including outdoor reset,
inferred load, and thermal pre-purge
(i.e., burner delay).15 The proposed test
methods, as would be specified in 10
CFR 429.134, would be intended for use
by DOE for assessment and enforcement
testing to determine if a given basic
model complies with the applicable
design requirements. Therefore, boiler
manufacturers would not be required to
conduct this testing. 80 FR 12876,
12902.
Several stakeholders commented on
the lack of compliance criteria for the
automatic means test. Burnham asserted
that it is legally unacceptable for DOE
to not specify any objective criteria for
demonstrating compliance and that DOE
does not have authority to unilaterally
create criteria to determine compliance
with the automatic means test without
notice and comment. (Burnham, No. 35
at p. 6) Weil-McLain stated that it is not
clear what this required test criteria or
procedure would be, but that, once
defined, this test will require more time
and resources to complete. Weil-McLain
also asserted that the new requirement
is arbitrary and capricious because it is
so indefinite. (Weil-McLain, No. 31 p. 8)
DOE’s automatic means design
requirement does not specify how a
manufacturer must implement the
automatic means and does not provide
compliance criteria for the automatic
means testing. DOE interprets the design
requirement established by EISA 2007
as intending to allow manufacturers
flexibility when designing control
strategies to meet the design
requirement. DOE believes that the
requirement of an incremental change in
inferred heat load that produces a
corresponding incremental change in
the temperature of water supplied is a
sufficient metric for evaluation of the
functionality of an automatic means for
adjusting water temperature. DOE
designed the tests, as noted in the
March 2015 NOPR, to confirm whether
the boiler supply water temperature
responds to a change in inferred heat
14 California Energy Commission, ‘‘Reference
Appendices for the 2008 Building Energy Efficiency
Standards for Residential and Non-residential
Buildings’’, p. 332, (Available at: https://
www.energy.ca.gov/2008publications/CEC-4002008-004/CEC-400-2008-004-CMF.PDF) (Last
accessed January 16, 2015).
15 See the March 2015 NOPR for further
description of the different control strategies.
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
2641
load without specifying to what degree
the temperature must change or for how
long that change is present because such
detail is not required for meeting the
design requirement. DOE also designed
the test methods to accommodate
technological advancements in controls
and designs. For these reasons, DOE
does not agree with Burnham and WeilMcLain that establishing further criteria
or thresholds is required beyond the
general requirements set forth in the
2008 technical amendment to the
furnace and boiler final rule.
Lochinvar stated that while it
supports the use of automatic means as
an effective method of energy
conservation, it opposes testing controls
for compliance for the following
reasons: (1) The lack of compliance
threshold; (2) no guarantee of
repeatability or consistency in test
method or results; (3) difficulty in
reasonably measuring the effectiveness
of different designs; (4) test method may
be biased for or against certain control
methods; and (5) a published
simulation-type test will lead to
manufacturers designing automatic
means for the test compliance.
(Lochinvar, No. 29 at p. 3) AHRI stated
that the criterion to confirm the
functioning of the means is too vague to
be meaningful, and that DOE should not
finalize this proposed procedure and
not pursue further the concept of adding
a test to verify the functioning of the
automatic means. (AHRI, No. 36 at p. 6)
Several stakeholders commented on
technical issues regarding the proposed
test method. Lochinvar and Burnham
stated that single-stage products may
use options other than ‘‘thermal purge.’’
(Lochinvar, No. 29 at p. 3; Burnham, No.
35 at p. 6) Lochinvar stated that if DOE
chooses to require automatic means
testing, single-stage boilers must be
allowed to comply by meeting either the
proposed test method in § 429.134(e)(1)
or (e)(2). (Lochinvar, No. 29 at p. 3)
Lochinvar also stated that DOE
incorrectly states that the automatic
means will change the heat output of a
boiler in response to the inferred heat
load. Responding to DOE’s proposal in
the March 31, 2015 notice of proposed
rulemaking for energy conservation
standards for boilers (‘‘March 2015 ECS
Boiler NOPR’’), Lochinvar asserted that
the automatic means would change the
temperature of the water supplied, not
necessarily the heat output. (Lochinvar,
No. 29 at p. 4)
Burnham argued that the water
temperatures specified are too low to
necessarily cause a burner delay. Also
responding to the March 2015 ECS
Boiler NOPR, Burnham suggested that
the proposed 10 CFR
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
2642
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
429.134(e)(1)(iii)(C) seems to imply that
a delay will always be present.
However, Burnham asserted that EISA
only requires that the automatic means
delay ignition above 140 °F until it has
determined that the inferred heat load
cannot be met by the residual heat in
the boiler. (Burnham, No. 35 at p. 6)
Burnham stated that the proposed 10
CFR 429.134(e)(2)(ii)(B)(1) specifies that
the supply water temperature be
maintained at ‘‘the lowest supply water
temperature (±4 °F),’’ which may not be
possible if the boiler’s minimum input
is greater than the corresponding load,
resulting in burner cycling. Burnham
stated that a similar problem is possible
in the proposed 10 CFR
429.134(e)(2)(ii)(C)(2), where a ‘‘boost
function’’ (a control strategy commonly
used that shifts the y-intercept of the
reset curve upward during extended
calls for heat) might make it impossible
to hold the required ±3 °F tolerance for
the boiler supply water temperature.
(Burnham, No. 35 at p. 6)
Burnham stated that some of the
control strategies currently in use
require multiple burner cycles to
determine the inferred heat load, which
does not seem to be taken into account
by DOE’s proposed verification method.
(Burnham, No. 35 at p. 6)
DOE makes several changes to the
proposed verification of automatic
means tests to address the technical
comments received from Lochinvar and
Burnham. DOE revised the two tests for
the verification of automatic means
presented in the NOPR such that the test
previously identified as the two-stage/
modulating boilers test will apply to all
boilers, with the exception of singlestage boilers that employ a burner delay
control strategy. The test for all boiler
products monitors water temperature
settings from the inferential load
controller and/or monitors supply water
temperature to determine whether the
supply water temperature changes in
response to changes in the inferred load.
This test method allows for establishing
the necessary conditions that may lead
to a change in inferred load, for
example, a change in outdoor air
temperature, a change in thermostat
patterns, and/or a change in boiler
cycling.
DOE is adopting the test previously
identified as the single-stage boilers test
as the test method for single-stage
boilers that employ a burner delay
control strategy to fulfill the automatic
means design requirement as specified
in 42 U.S.C. 6295(f)(3)(B)(ii). The test for
single-stage boilers that employ a burner
delay control strategy captures the
delayed burner reaction following a call
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
for heating when residual heat is
present within the boiler.
DOE agrees with Burnham and
Lochinvar’s comments that help to
clarify the test method and allow for
accommodating variations in the control
strategies. Therefore, DOE adopts
revisions that include removing the
minimum supply water temperature
tolerance requirement to allow
variations in temperature when burner
cycling occurs; increasing the inlet
water temperature from 120 °F (±2 °F)
to 140 °F (±2 °F) for the test method for
single-stage boilers that employ a burner
delay control strategy so that it is high
enough to cause burner delay; and
making terminology related to inlet
water consistent throughout the test
method. However, DOE disagrees with
Burnham’s comment that the tolerance
range for determining a stabilized
supply water temperature could not be
met under a specific control strategy,
such as the boost mode where an
extended call for heating occurs until
the heat demand is satisfied. In such a
case, DOE’s test method would be
implemented when either the heat
demand is satisfied or the high boiler
water temperature limit is reached.
As discussed in the March 2015
NOPR, DOE also adds a definition for
‘‘controlling parameter.’’ DOE has
placed this definition in 10 CFR 430.2
rather than appendix N as it applies to
DOE enforcement regulations rather
than manufacturer testing. Controlling
parameter is defined as a measurable
quantity for a residential boiler (such as
temperature or usage pattern) used for
inferring heating load, which would
then result in incremental changes in
supply water temperature.
2. Compliance Dates for the Amended
Test Procedure
This document amends 10 CFR
429.18, 10 CFR 429.134, 10 CFR 430.2,
10 CFR 430.3, 10 CFR 430.23, and 10
CFR part 430, subpart B, appendix N.
When DOE modifies test procedures, it
must determine to what extent, if any,
the new test procedure would alter the
measured energy efficiency or energy
use of any covered product. (42 U.S.C.
6293(e)(1)) For the reasons described
previously, DOE has determined that
none of the test procedure amendments
would alter the measured energy
efficiency or energy use of the covered
products that are the subject of this
rulemaking. The changes made to
appendix N through this final rule, as
listed in section III.D, clarify the manner
in which the test is conducted, or
otherwise represent minor changes or
additions to the test or reporting
requirements that do not affect
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
measured energy use. Therefore, these
amendments become effective 30 days
after publication of this final rule in the
Federal Register. Pursuant to 42 U.S.C.
6293(c)(2), 180 days after DOE
prescribes or establishes a new or
amended test procedure, manufacturers
must make representations of energy
efficiency, including certifications of
compliance, using that new or amended
test procedure.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Order 12866
The Office of Management and Budget
(OMB) has determined that test
procedure rulemakings do not constitute
‘‘significant regulatory actions’’ under
section 3(f) of Executive Order 12866,
‘‘Regulatory Planning and Review,’’ 58
FR 51735 (Oct. 4, 1993). Accordingly,
this action was not subject to review
under the Executive Order by the Office
of Information and Regulatory Affairs
(OIRA) in OMB.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq., as amended by the
Small Business Regulatory Fairness Act
of 1996) requires preparation of an
initial regulatory flexibility analysis
(IRFA) for any rule that by law must be
proposed for public comment, unless
the agency certifies that the rule, if
promulgated, will not have a significant
economic impact on a substantial
number of small entities. As required by
Executive Order 13272, ‘‘Proper
Consideration of Small Entities in
Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s Web site: https://energy.gov/
gc/office-general-counsel.
DOE reviewed this final rule under
the provisions of the Regulatory
Flexibility Act and the procedures and
policies published on February 19,
2003. 68 FR 7990. This final rule
amends DOE’s test procedure by
providing clarifications regarding
relevant test procedure provisions and
revising the definitions of some terms.
DOE has concluded that this final rule
will not have a significant impact on a
substantial number of small entities.
The factual basis for this certification is
as follows:
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES4
The Small Business Administration
(SBA) considers a business entity to be
a small business if, together with its
affiliates, it employs less than a
threshold number of workers specified
in 13 CFR part 121. These size standards
and codes are established by the North
American Industry Classification
System (NAICS) and are available at
https://www.sba.gov/sites/default/files/
files/Size_Standards_Table.pdf.
Residential boiler manufacturing is
classified under NAICS 333414,
‘‘Heating Equipment (Except Warm Air
Furnaces) Manufacturing,’’ for which
the maximum size threshold is 500
employees or fewer. Residential furnace
manufacturing is classified under
NAICS 333415, ‘‘Air-conditioning and
warm air heating equipment and
commercial and industrial refrigeration
equipment manufacturing’’ for which
the maximum size threshold is 750
employees or fewer. To estimate the
number of companies that could be
small business manufacturers of
products covered by this rulemaking,
DOE conducted a market survey using
available public information to identify
potential small manufacturers. DOE’s
research involved reviewing several
industry trade association membership
directories (e.g., AHRI 16), SBA
databases,17 individual company Web
sites, and marketing research tools (e.g.,
Hoovers 18 reports) to create a list of all
domestic small business manufacturers
of residential furnaces and boilers
covered by this rulemaking.
After DOE identified manufacturers of
residential furnaces and consumer
boilers, DOE then consulted publicallyavailable data and contacted companies,
as necessary, to determine if they both
meet the SBA’s definition of a ‘‘small
business’’ manufacturer and have their
manufacturing facilities located within
the United States. DOE screened out
companies that did not offer products
covered by this rulemaking, did not
meet the definition of a ‘‘small
business,’’ or are foreign-owned and
operated. Based on this analysis, DOE
identified 9 small businesses that
manufacture residential furnaces and 9
small businesses that manufacture
residential boilers (two of which also
manufacture residential furnaces), for a
total of 16 small businesses potentially
impacted by this rulemaking.
This document amends DOE’s test
procedure by incorporating several
16 For more information on the boiler and furnace
directories, see https://www.ahridirectory.org/
ahridirectory/pages/home.aspx.
17 For more information see: https://dsbs.sba.gov/
dsbs/search/dsp_dsbs.cfm.
18 For more information see: https://
www.hoovers.com/.
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
changes that modify the existing test
procedure or reporting requirements for
furnaces and boilers. This includes the
following changes that could potentially
impact manufacturers: (1) Clarified
definition of electrical power term PE;
(2) a smoke stick method for
determining whether the minimum
default draft factor may be used; (3) a
provision to allow for the measurement
of condensate under steady-state
conditions; (4) reference to
manufacturers’ I&O manuals; (5)
specification of ductwork for units that
are installed without a return duct; (6)
specification of testing requirements for
multi-position units; (7) revised
reporting precision for AFUE to the
nearest tenth of a percentage point; and
(8) requirement to report the use of a
burner delay automatic means control
strategy in certification reports. The
estimated costs of testing/rating and
potential impact to manufacturer
burden resulting from use of the
amended test procedure are discussed
subsequently. The estimated costs and
potential impacts apply to all
manufacturers, including the
manufacturers identified as small
businesses.
DOE believes that explicitly listing
the components encompassed in the
definition of PE does not change the
definition of the electrical power term
PE but rather only clarifies it, and will
not impose any additional test burden.
The adoption of the smoke stick
method for determining whether the
minimum default draft factor may be
used is intended to reduce the test
burden to manufacturers. DOE
estimated that the smoke stick method
for determining the minimum default
draft factor would reduce the overall
duration of the test by about 15 minutes
for units designed to have no flow
through the heat exchanger. However,
DOE does not have sufficient
information to support estimating the
fraction of units that have been designed
such that there is no flow through the
heat exchanger. Therefore, DOE has not
included the cost savings associated
with the smoke stick.
The addition of the optional provision
to allow for the measurement of
condensate prior to the establishment of
steady state conditions will result in a
lowering of test burden for
manufacturers of condensing furnaces
and boilers. Manufacturers of
condensing furnaces and boilers will
benefit from the time and labor savings
attributed to the measurement of
condensate during the establishment of
steady-state conditions. However, DOE
does not have sufficient information to
support estimating the fraction of units
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
2643
that would be tested under the optional
provision. Therefore, DOE has not
included the cost savings associated
with the optional provision to allow for
the measurement of condensate prior to
the establishment of steady state
conditions.
The clarification of duct work
requirements for units that are installed
without a return duct and clarification
of the test requirements for multiposition units do not present any
additional test burden to manufacturers,
as the two amendments do not change
the existing testing requirements or
conflict with current industry practice.
Revision of AFUE reporting precision
and the requirement to report the use of
a burner delay automatic means control
strategy in the certification report do not
present any additional test burden to
manufacturers, as the two amendments
do not change testing requirements.
However, both amendments may require
some manufacturers to submit new
certification reports and relabel their
products. DOE estimates that for
affected parties, submitting new
certification reports and relabeling
products will take 30 minutes per unit.
At an assumed cost of $40 per hour, the
cost to recertify and relabel is $20 per
unit.
To determine the potential cost of the
test procedure amendments on small
furnace and boiler manufacturers, DOE
estimated the cost of recertifying and
relabeling per basic model and the
savings from the optional provision to
measure condensate during the
establishment of steady state conditions,
as described above. DOE estimated that
on average, each furnace small business
would have 51 basic models, and each
boiler small business would have 70
basic models. Based on residential
furnace and boiler model data, DOE
assumed that approximately 70 percent
of all furnace and 60 percent of all
boiler manufacturers will need to
recertify and relabel due to the revision
of the AFUE reporting precision. Based
on residential boiler model data, DOE
assumed that about 75 percent of boilers
are single-stage boilers; furthermore,
DOE assumed that about two-thirds of
single-stage boilers employ a burner
delay automatic means control strategy.
Thus, DOE assumed that half of all
boiler models will employ a burner
delay automatic means control strategy.
The additional recertification and
relabeling cost associated with the test
procedure amendments was multiplied
by the estimated fraction of affected
basic models produced by a small
manufacturer. DOE has estimated a total
added cost from the test procedure
amendments of $714 per furnace
E:\FR\FM\15JAR4.SGM
15JAR4
2644
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
manufacturer and a total added cost of
about $1,120 per boiler manufacturer for
manufacturers that currently do not
report AFUE to the nearest tenth of a
percentage point or for manufacturers of
single-stage boilers that employ a burner
delay automatic means control strategy.
For the reasons stated previously,
DOE certifies that this rule will not have
a significant economic impact on a
substantial number of small entities.
tkelley on DSK3SPTVN1PROD with RULES4
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of residential furnaces
and boilers must certify to DOE that
their products comply with all
applicable energy conservation
standards. In certifying compliance with
applicable performance standards,
manufacturers must test their products
according to the DOE test procedures for
residential furnaces and boilers,
including any amendments adopted for
those test procedures. Manufacturers
must also ensure their products comply
with applicable design standards. DOE
has established regulations for the
certification and recordkeeping
requirements for all covered consumer
products and commercial equipment,
including residential furnaces and
boilers. See generally 10 CFR part 429.
The collection-of-information
requirement for certification and
recordkeeping is subject to review and
approval by OMB under the Paperwork
Reduction Act (PRA). This requirement
has been approved by OMB under OMB
control number 1910–1400. Public
reporting burden for the certification is
estimated to average 30 hours per
response, including the time for
reviewing instructions, searching
existing data sources, gathering and
maintaining the data needed, and
completing and reviewing the collection
of information.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE amends its test
procedure for residential furnaces and
boilers. DOE has determined that this
rule falls into a class of actions that are
categorically excluded from review
under the National Environmental
Policy Act of 1969 (42 U.S.C. 4321 et
seq.) and DOE’s implementing
regulations at 10 CFR part 1021.
Specifically, this rule amends an
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
existing rule without affecting the
amount, quality or distribution of
energy usage, and, therefore, will not
result in any environmental impacts.
Thus, this rulemaking is covered by
Categorical Exclusion A5 under 10 CFR
part 1021, subpart D, which applies to
any rulemaking that interprets or
amends an existing rule without
changing the environmental effect of
that rule. Accordingly, neither an
environmental assessment nor an
environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 10, 1999) imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have Federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States, and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have Federalism implications. On
March 14, 2000, DOE published a
statement of policy describing the
intergovernmental consultation process
it will follow in the development of
such regulations. 65 FR 13735. DOE
examined this final rule and determined
that it will not have a substantial direct
effect on the States, on the relationship
between the national government and
the States, or on the distribution of
power and responsibilities among the
various levels of government. EPCA
governs and prescribes Federal
preemption of State regulations as to
energy conservation for the products
that are the subject of this final rule.
States can petition DOE for exemption
from such preemption to the extent, and
based on criteria, set forth in EPCA. (42
U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, this final rule
meets the relevant standards of
Executive Order 12988.
G. Review under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
regulatory action resulting in a rule that
may cause the expenditure by State,
local, and Tribal governments, in the
aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR
12820. (This policy is also available at
https://energy.gov/gc/office-generalcounsel). DOE examined this final rule
according to UMRA and its statement of
policy and determined that the rule
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
contains neither an intergovernmental
mandate, nor a mandate that may result
in the expenditure of $100 million or
more in any year, so these requirements
do not apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
rule will not have any impact on the
autonomy or integrity of the family as
an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
Pursuant to Executive Order 12630,
‘‘Governmental Actions and Interference
with Constitutionally Protected Property
Rights,’’ 53 FR 8859 (March 18, 1988),
DOE has determined that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
tkelley on DSK3SPTVN1PROD with RULES4
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). DOE has reviewed
this final rule under the OMB and DOE
guidelines and has concluded that it is
consistent with applicable policies in
those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB, a
Statement of Energy Effects for any
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgated or is
expected to lead to promulgation of a
final rule, and that: (1) Is a significant
regulatory action under Executive Order
12866, or any successor order; and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy; or (3) is designated by the
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
2645
Administrator of OIRA as a significant
energy action. For any significant energy
action, the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use if the
regulation is implemented, and of
reasonable alternatives to the action and
their expected benefits on energy
supply, distribution, and use.
This regulatory action is not a
significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
‘‘Standard Test Method for Smoke
Density in Flue Gases from Burning
Distillate Fuels,’’ ASTM D2156–09
(Reapproved 2013). ASTM D2156 is an
industry accepted test procedure that
establishes uniform test methods for the
evaluation of smoke density in the flue
gases from burning distillate fuels. The
test procedure established in this final
rule references ASTM D2156 in its
entirety, which includes terminology,
methods of testing, materials, apparatus,
procedures, reporting, and precision
and bias, to determine the allowable
smoke in the flue of oil furnaces and
boilers. ASTM D2156–09 is available on
ASTM’s Web site at https://
www.astm.org/Standards/D2156.htm.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977 (Pub. L. 95–
70). (15 U.S.C. 788; FEAA) Section 32
essentially provides in relevant part
that, where a proposed rule authorizes
or requires use of commercial standards,
the notice of proposed rulemaking must
inform the public of the use and
background of such standards. In
addition, section 32(c) requires DOE to
consult with the Attorney General and
the Chairman of the Federal Trade
Commission (FTC) concerning the
impact of the commercial or industry
standards on competition.
This final rule incorporates testing
methods contained in the following
commercial standard: ASTM D2156–09
(Reapproved 2013). While this test
procedure is not exclusively based on
this standard, the DOE test procedure
adopts several provisions from this
standard without amendment. DOE has
evaluated this standard and is unable to
conclude whether it fully complies with
the requirements of section 32(b) of the
FEAA (i.e., that it was developed in a
manner that fully provides for public
participation, comment, and review).
DOE has consulted with the Attorney
General and the Chairwoman of the FTC
concerning the impact of these test
procedures on competition and has
received no comments objecting to their
use.
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of this rule prior to its effective date.
The report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
M. Description of Materials
Incorporated by Reference
In this final rule, DOE incorporates by
reference the ASTM test standard
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
N. Congressional Notification
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
List of Subjects
10 CFR Part 429
Confidential business information,
Energy conservation, Household
appliances, Imports, Reporting and
recordkeeping requirements.
10 CFR Part 430
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Small
businesses.
Issued in Washington, DC, on December
29, 2015.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
For the reasons stated in the
preamble, DOE amends parts 429 and
430 of chapter II, subchapter D of title
10, Code of Federal Regulations, as set
forth below:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
E:\FR\FM\15JAR4.SGM
15JAR4
2646
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
2. Amend § 429.18 by adding
paragraphs (a)(2)(vii) and (b)(4) to read
as follows:
■
§ 429.18
Residential furnaces.
(a) * * *
(2) * * *
(vii) Reported values. The represented
value of annual fuel utilization
efficiency must be truncated to the onetenth of a percentage point.
(b) * * *
(4) For multi-position furnaces, the
annual fuel utilization efficiency
(AFUE) reported for each basic model
must be based on testing in the least
efficient configuration. Manufacturers
may also report and make
representations of additional AFUE
values based on testing in other
configurations.
■ 3. Amend § 429.134 by adding
paragraph (h) to read as follows:
§ 429.134 Product-specific enforcement
provisions
tkelley on DSK3SPTVN1PROD with RULES4
*
*
*
*
*
(h) Residential boilers—test protocols
for functional verification of automatic
means for adjusting water temperature.
These tests are intended to verify the
functionality of the design requirement
that a boiler has an automatic means for
adjusting water temperature for singlestage, two-stage, and modulating boilers.
These test methods are intended to
permit the functional testing of a range
of control strategies used to fulfill this
design requirement. Section 2,
Definitions, and paragraph 6.1.a of
appendix N to subpart B of part 430 of
this chapter apply for the purposes of
this paragraph (h).
(1) Test protocol for all products other
than single-stage products employing
burner delay. This test is intended to
verify whether an automatic means for
adjusting water temperature other than
burner delay produces an incremental
change in water supply temperature in
response to an incremental change in
inferred heat load.
(i) Boiler setup—(A) Boiler
installation. Boiler installation in the
test room shall be in accordance with
the setup and apparatus requirements of
section 6 of appendix N to subpart B of
10 CFR part 430.
(B) Establishing flow rate and
temperature rise. Start the boiler
without enabling the means for
adjusting water temperature. Establish a
water flow rate that allows for a water
temperature rise of greater than or equal
to 20 °F at maximum input rate.
(C) Temperature stabilization.
Temperature stabilization is deemed to
be obtained when the boiler supply
water temperature does not vary by
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
more than ±3 °F over a period of five
minutes.
(D) Adjust the inferential load
controller. (1) Adjust the boiler controls
(in accordance with the I&O manual) to
the default setting that allows for
activation of the means for adjusting
water temperature. For boiler controls
that do not allow for control adjustment
during active mode operation, terminate
call for heat and adjust the inferential
load controller in accordance with the
I&O manual and then reinitiate call for
heat.
(2) If the means for adjusting water
temperature uses outdoor temperature
reset, the maximum outdoor
temperature setting (if equipped) should
be set to a temperature high enough that
the boiler operates continuously during
the duration of this test (i.e., if the
conditions in paragraph (h)(1)(ii)(A) of
this section equal room ambient
temperature, then the maximum
outdoor temperature should be set at a
temperature greater than the ambient air
temperature during the test).
(ii) Establish low inferred load
conditions at minimum boiler supply
water temperature—(A) Establish low
inferred load conditions. (1) Establish
the inferred load conditions (simulated
using a controlling parameter, such as
outdoor temperature, thermostat
patterns, or boiler cycling) so that the
supply water temperature is maintained
at the minimum supply water
temperature prescribed by the boiler
manufacturer’s temperature reset
control strategy found in the I&O
manual.
(2) The minimum supply water
temperature of the default temperature
reset curve is usually provided in the
I&O manual. If there is no recommended
minimum supply water temperature, set
the minimum supply water temperature
equal to 20 °F less than the high supply
water temperature specified in
paragraph (h)(1)(iii)(A) of this section.
(B) Supply water temperature
stabilization at low inferred load. (1)
Maintain the call for heat until the
boiler supply water temperature has
stabilized. Temperature stabilization is
deemed to be obtained when the boiler
supply water temperature does not vary
by more than ±3 °F over a period of five
minutes. The duration of time required
to stabilize the supply water, following
the procedure in paragraph (h)(1)(ii)(A)
of this section, is dependent on the reset
strategy and may vary from model to
model.
(2) Record the boiler supply water
temperature while the temperature is
stabilized.
(iii) Establish high inferred load
conditions at maximum boiler supply
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
water temperature—(A) Establish high
inferred load conditions. Establish the
inferred load conditions so that the
supply water temperature is set to the
maximum allowable supply water
temperature as prescribed in the I&O
manual, or if there is no
recommendation, set to a temperature
greater than 170 °F.
(B) Supply water temperature
stabilization at high inferred load. (1)
Maintain the call for heat until the
boiler supply water temperature has
stabilized. Temperature stabilization is
deemed to be obtained when the boiler
supply water temperature does not vary
by more than ±3 °F over a period of five
minutes. The duration of time required
to stabilize the supply water, following
the procedure in paragraph (h)(1)(iii)(A)
of this section, is dependent on the reset
strategy and may vary from model to
model.
(2) Record the boiler supply water
temperature while the temperature is
stabilized.
(3) Terminate the call for heat.
(iv) [Reserved]
(2) Test protocol for single-stage
products employing burner delay. This
test will be used in place of paragraph
(h)(1) of this section for products
manufacturers have certified to DOE
under § 429.18(b)(3) as employing a
burner delay automatic means strategy.
This test verifies whether the automatic
means in single-stage boiler products
establishes a burner delay upon a call
for heat until the means has determined
that the inferred heat load cannot be met
by the residual heat of the water in the
system.
(i) Boiler setup—(A) Boiler
installation. Boiler installation in the
test room shall be in accordance with
the setup and apparatus requirements
by section 6.0 of appendix N to subpart
B of 10 CFR part 430.
(B) Activation of controls. Adjust the
boiler controls in accordance with the
I&O manual at the default setting that
allows for activation of the means for
adjusting water temperature.
(C) Adjustment of water flow and
temperature. The flow and temperature
of inlet water to the boiler shall be
capable of being adjusted manually.
(ii) Boiler heat-up—(A) Boiler startup. Power up the boiler and initiate a
call for heat.
(B) Adjustment of firing rate. Adjust
the boiler’s firing rate to within ±5% of
its maximum rated input.
(C) Establishing flow rate and
temperature rise. Adjust the water flow
through the boiler to achieve a DT of
20 °F (±2 °F) or greater with an inlet
water temperature equal to 140 °F
(±2 °F).
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
(D) Terminate the call for heating.
Terminate the call for heat, stop the
flow of water through the boiler, and
record the time at termination.
(iii) Verify burner delay—(A)
Reinitiate call for heat. Within three (3)
minutes of termination (paragraph
(h)(2)(ii)(D) of this section) and without
adjusting the inlet water flow rate or
temperature as specified in paragraph
(h)(2)(ii)(C) of this section, reinitiate the
call for heat and water flow and record
the time.
(B) Verify burner ignition. At 15second intervals, record time and
supply water temperature until the main
burner ignites.
(C) Terminate the call for heat.
(iv) [Reserved]
PART 430—ENERGY CONSERVATION
PROGRAM FOR CONSUMER
PRODUCTS
4. The authority citation for part 430
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6309; 28 U.S.C.
2461 note.
5. Amend § 430.2 by adding in
alphabetical order a definition of
‘‘Controlling parameter’’ and revising
the definition of ‘‘Furnace’’ to read as
follows:
■
§ 430.2
Definitions.
tkelley on DSK3SPTVN1PROD with RULES4
*
*
*
*
*
Controlling parameter means a
measurable quantity or an algorithm
(such as temperature or usage pattern)
used for inferring heating load to a
residential boiler, which would then
result in incremental changes in boiler
supply water temperature.
*
*
*
*
*
Furnace means a product which
utilizes only single-phase electric
current, or single-phase electric current
or DC current in conjunction with
natural gas, propane, or home heating
oil, and which—
(1) Is designed to be the principal
heating source for the living space of a
residence;
(2) Is not contained within the same
cabinet with a central air conditioner
whose rated cooling capacity is above
65,000 Btu per hour;
(3) Is an electric central furnace,
electric boiler, forced-air central
furnace, gravity central furnace, or lowpressure steam or hot water boiler; and
(4) Has a heat input rate of less than
300,000 Btu per hour for electric boilers
and low-pressure steam or hot water
boilers and less than 225,000 Btu per
hour for forced-air central furnaces,
gravity central furnaces, and electric
central furnaces.
*
*
*
*
*
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
6. Amend § 430.3 by revising
paragraph (g)(11) and adding paragraph
(j)(2) to read as follows:
■
§ 430.3 Materials incorporated by
reference.
*
*
*
*
*
(g) * * *
(11) ANSI/ASHRAE Standard 103–
1993, (‘‘ASHRAE 103–1993’’), Methods
of Testing for Annual Fuel Utilization
Efficiency of Residential Central
Furnaces and Boilers, (with Errata of
October 24, 1996), except for sections
7.1, 7.2.2.2, 7.2.2.5, 7.2.3.1, 7.8, 8.2.1.3,
8.3.3.1, 8.4.1.1, 8.4.1.1.2, 8.4.1.2,
8.4.2.1.4, 8.4.2.1.6, 8.6.1.1, 8.7.2, 8.8.3,
9.1.2.2.1, 9.1.2.2.2, 9.5.1.1, 9.5.1.2.1,
9.5.1.2.2, 9.5.2.1, 9.7.1, 9.7.4, 9.7.6, 9.10,
11.5.11.1, 11.5.11.2 and appendices B
and C, approved October 4, 1993, IBR
approved for § 430.23 and appendix N
to subpart B.
*
*
*
*
*
(j) * * *
(2) ASTM D2156–09 (Reapproved
2013) (‘‘ASTM D2156R13’’), Standard
Test Method for Smoke Density in Flue
Gases from Burning Distillate Fuels,
approved October 1, 2013, IBR approved
for appendix N to subpart B.
*
*
*
*
*
■ 7. Amend § 430.23 by revising
paragraph (n)(2) to read as follows:
§ 430.23 Test procedures for the
measurement of energy and water
consumption.
*
*
*
*
*
(n) * * *
(2) The annual fuel utilization
efficiency for furnaces, expressed in
percent, is the ratio of the annual fuel
output of useful energy delivered to the
heated space to the annual fuel energy
input to the furnace determined
according to section 10.1 of appendix N
of this subpart for gas and oil furnaces
and determined in accordance with
section 11.1 of the American National
Standards Institute/American Society of
Heating, Refrigerating, and AirConditioning Engineers (ANSI/
ASHRAE) Standard 103–1993
(incorporated by reference, see § 430.3)
for electric furnaces. Truncate the
annual fuel utilization efficiency to onetenth of a percentage point.
*
*
*
*
*
■ 8. Revise appendix N to subpart B to
read as follows:
Appendix N to Subpart B of Part 430—
Uniform Test Method for Measuring the
Energy Consumption of Furnaces and
Boilers
Note: Prior to July 13, 2016,
representations with respect to the energy
use or efficiency of residential furnaces and
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
2647
boilers, including compliance certifications,
must be based on testing conducted in
accordance with either this appendix as it
now appears or appendix N as it appeared at
10 CFR part 430, subpart B revised as of
January 1, 2016.
After July 13, 2016, representations with
respect to energy use or efficiency of
residential furnaces and boilers, including
compliance certifications, must be based on
testing conducted in accordance with this
appendix.
1.0 Scope. The scope of this appendix is
as specified in section 2 of ASHRAE 103–
1993 (incorporated by reference, see § 430.3).
For purposes of this appendix, the
Department of Energy incorporates by
reference several industry standards, either
in whole or in part, as listed in § 430.3. In
cases where there is a conflict, the language
of the test procedure in this appendix takes
precedence over the incorporated standards.
2.0 Definitions. Definitions include those
specified in section 3 of ASHRAE 103–1993
(incorporated by reference, see § 430.3) and
the following additional and modified
definitions.
2.1 Active mode means the condition in
which the furnace or boiler is connected to
the power source, and at least one of the
burner, electric resistance elements, or any
electrical auxiliaries such as blowers or
pumps, are activated.
2.2 Boiler pump means a pump installed
on a boiler and that is separate from the
circulating water pump.
2.3 Control means a device used to
regulate the operation of a piece of
equipment and the supply of fuel, electricity,
air, or water.
2.4 Draft inducer means a fan
incorporated in the furnace or boiler that
either draws or forces air into the combustion
chamber.
2.5 Gas valve means an automatic or
semi-automatic device consisting essentially
of a valve and operator that controls the gas
supply to the burner(s) during normal
operation of an appliance. The operator may
be actuated by application of gas pressure on
a flexible diaphragm, by electrical means, by
mechanical means or by other means.
2.6 Installation and operation (I&O)
manual means instructions for installing,
commissioning, and operating the furnace or
boiler, which are supplied with the product
when shipped by the manufacturer.
2.7 Isolated combustion system means a
system where a unit is installed within the
structure, but isolated from the heated space.
A portion of the jacket heat from the unit is
lost, and air for ventilation, combustion and
draft control comes from outside the heated
space.
2.8 Multi-position furnace means a
furnace that can be installed in more than
one airflow configuration (i.e., upflow or
horizontal; downflow or horizontal; upflow
or downflow; and upflow, or downflow, or
horizontal).
2.9 Off mode means a mode in which the
furnace or boiler is connected to a mains
power source and is not providing any active
mode or standby mode function, and where
the mode may persist for an indefinite time.
The existence of an off switch in off position
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
2648
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
(a disconnected circuit) is included within
the classification of off mode.
2.10 Off switch means the switch on the
furnace or boiler that, when activated, results
in a measurable change in energy
consumption between the standby and off
modes.
2.11 Oil control valve means an
automatically or manually operated device
consisting of an oil valve for controlling the
fuel supply to a burner to regulate burner
input.
2.12 Standby mode means any mode in
which the furnace or boiler is connected to
a mains power source and offers one or more
of the following space heating functions that
may persist:
a. To facilitate the activation of other
modes (including activation or deactivation
of active mode) by remote switch (including
thermostat or remote control), internal or
external sensors, or timer;
b. Continuous functions, including
information or status displays or sensor
based functions.
2.13 Thermal stack damper means a type
of stack damper that relies exclusively upon
the changes in temperature in the stack gases
to open or close the damper.
3.0 Classifications. Classifications are as
specified in section 4 of ASHRAE 103–1993
(incorporated by reference, see § 430.3).
4.0 Requirements. Requirements are as
specified in section 5 of ASHRAE 103–1993
(incorporated by reference, see § 430.3).
5.0 Instruments. Instruments must be as
specified in section 6 of ASHRAE 103–1993
(incorporated by reference, see § 430.3).
6.0 Apparatus. The apparatus used in
conjunction with the furnace or boiler during
the testing must be as specified in section 7
of ASHRAE 103–1993 (incorporated by
reference, see § 430.3) except for sections 7.1,
7.2.2.2, 7.2.2.5, 7.2.3.1, and 7.8; and as
specified in sections 6.1 through 6.5 of this
appendix.
6.1 General.
a. Install the furnace or boiler in the test
room in accordance with the I&O manual, as
defined in section 2.6 of this appendix,
except that if provisions within this
appendix are specified, then the provisions
herein drafted and prescribed by DOE
govern. If the I&O manual and any additional
provisions of this appendix are not sufficient
for testing a furnace or boiler, the
manufacturer must request a waiver from the
test procedure pursuant to 10 CFR 430.27.
b. If the I&O manual indicates the unit
should not be installed with a return duct,
then the return (inlet) duct specified in
section 7.2.1 of ASHRAE 103–1993
(incorporated by reference, see § 430.3) is not
required.
c. Test multi-position furnaces in the least
efficient configuration. Testing of multiposition furnaces in other configurations is
permitted if energy use or efficiency is
represented pursuant to the requirements in
10 CFR part 429.
d. The apparatuses described in section 6
of this appendix are used in conjunction with
the furnace or boiler during testing. Each
piece of apparatus shall conform to material
and construction specifications listed in this
appendix and in ASHRAE 103–1993
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
(incorporated by reference, see § 430.3), and
the reference standards cited in this
appendix and in ASHRAE 103–1993.
e. Test rooms containing equipment must
have suitable facilities for providing the
utilities (including but not limited to
environmental controls, sufficient fluid
source(s), applicable measurement
equipment, and any other technology or
tools) necessary for performance of the test
and must be able to maintain conditions
within the limits specified in section 6 of this
appendix.
6.2 Forced-air central furnaces (direct
vent and direct exhaust).
a. Units not equipped with a draft hood or
draft diverter must be provided with the
minimum-length vent configuration
recommended in the I&O manual or a 5-ft
flue pipe if there is no recommendation
provided in the I&O manual (see Figure 4 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3)). For a direct exhaust
system, insulate the minimum-length vent
configuration or the 5-ft flue pipe with
insulation having an R-value not less than 7
and an outer layer of aluminum foil. For a
direct vent system, see section 7.5 of
ASHRAE 103–1993 for insulation
requirements.
b. For units with power burners, cover the
flue collection box with insulation having an
R-value of not less than 7 and an outer layer
of aluminum foil before the cool-down and
heat-up tests described in sections 9.5 and
9.6 of ASHRAE 103–1993 (incorporated by
reference, see § 430.3), respectively.
However, do not apply the insulation for the
jacket loss test (if conducted) described in
section 8.6 of ASHRAE 103–1993 or the
steady-state test described in section 9.1 of
ASHRAE 103–1993.
c. For power-vented units, insulate the
shroud surrounding the blower impeller with
insulation having an R-value of not less than
7 and an outer layer of aluminum foil before
the cool-down and heat-up tests described in
sections 9.5 and 9.6, respectively, of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3). Do not apply the
insulation for the jacket loss test (if
conducted) described in section 8.6 of
ASHRAE 103–1993 or the steady-state test
described in section 9.1 of ASHRAE 103–
1993. Do not insulate the blower motor or
block the airflow openings that facilitate the
cooling of the combustion blower motor or
bearings.
6.3 Downflow furnaces. Install an internal
section of vent pipe the same size as the flue
collar for connecting the flue collar to the top
of the unit, if not supplied by the
manufacturer. Do not insulate the internal
vent pipe during the jacket loss test (if
conducted) described in section 8.6 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3) or the steady-state test
described in section 9.1 of ASHRAE 103–
1993. Do not insulate the internal vent pipe
before the cool-down and heat-up tests
described in sections 9.5 and 9.6,
respectively, of ASHRAE 103–1993. If the
vent pipe is surrounded by a metal jacket, do
not insulate the metal jacket. Install a 5-ft test
stack of the same cross-sectional area or
perimeter as the vent pipe above the top of
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
the furnace. Tape or seal around the junction
connecting the vent pipe and the 5-ft test
stack. Insulate the 5-ft test stack with
insulation having an R-value not less than 7
and an outer layer of aluminum foil. (See
Figure 3–E of ASHRAE 103–1993.)
6.4 Units with draft hoods or draft
diverters. Install the stack damper in
accordance with the I&O manual. Install 5
feet of stack above the damper.
a. For units with an integral draft diverter,
cover the 5-ft stack with insulation having an
R-value of not less than 7 and an outer layer
of aluminum foil.
b. For units with draft hoods, insulate the
flue pipe between the outlet of the furnace
and the draft hood with insulation having an
R-value of not less than 7 and an outer layer
of aluminum foil.
c. For units with integral draft diverters
that are mounted in an exposed position (not
inside the overall unit cabinet), cover the
diverter boxes (excluding any openings
through which draft relief air flows) before
the beginning of any test (including jacket
loss test) with insulation having an R-value
of not less than 7 and an outer layer of
aluminum foil.
d. For units equipped with integral draft
diverters that are enclosed within the overall
unit cabinet, insulate the draft diverter box
with insulation as described in section 6.4.c
before the cool-down and heat-up tests
described in sections 9.5 and 9.6,
respectively, of ASHRAE 103–1993
(incorporated by reference, see § 430.3). Do
not apply the insulation for the jacket loss
test (if conducted) described in section 8.6 of
ASHRAE 103–1993 or the steady-state test
described in section 9.1 of ASHRAE 103–
1993.
6.5 Condensate collection. Attach
condensate drain lines to the unit as
specified in the I&O manual. Maintain a
continuous downward slope of drain lines
from the unit. Additional precautions (such
as eliminating any line configuration or
position that would otherwise restrict or
block the flow of condensate or checking to
ensure a proper connection with condensate
drain spout that allows for unobstructed
flow) must be taken to facilitate
uninterrupted flow of condensate during the
test. Collection containers must be glass or
polished stainless steel to facilitate removal
of interior deposits. The collection container
must have a vent opening to the atmosphere.
7.0 Testing conditions. The testing
conditions must be as specified in section 8
of ASHRAE 103–1993 (incorporated by
reference, see § 430.3), except for section
8.2.1.3, 8.3.3.1, 8.4.1.1, 8.4.1.1.2, 8.4.1.2,
8.4.2.1.4, 8.4.2.1.6, 8.6.1.1, 8.7.2, and 8.8.3;
and as specified in sections 7.1 to 7.10 of this
appendix, respectively.
7.1 Fuel supply, gas. In conducting the
tests specified herein, gases with
characteristics as shown in Table 1 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3) shall be used.
Maintain the gas supply, ahead of all controls
for a furnace, at a test pressure between the
normal and increased values shown in Table
1 of ASHRAE 103–1993. Maintain the
regulator outlet pressure at a level
approximating that recommended in the I&O
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
manual, as defined in section 2.6 of this
appendix, or, in the absence of such
recommendation, to the nominal regulator
settings used when the product is shipped by
the manufacturer. Use a gas having a specific
gravity as shown in Table 1 of ASHRAE 103–
1993 and with a higher heating value within
±5% of the higher heating value shown in
Table 1 of ASHRAE 103–1993. Determine the
actual higher heating value in Btu per
standard cubic foot for the gas to be used in
the test within an error no greater than 1%.
7.2 Installation of piping. Install piping
equipment in accordance with the I&O
manual. In the absence of such specification,
install piping in accordance with section
8.3.1.1 of ASHRAE 103–1993 (incorporated
by reference, see § 430.3).
7.3 Gas burner. Adjust the burners of gasfired furnaces and boilers to their maximum
Btu input ratings at the normal test pressure
specified by section 7.1 of this appendix.
Correct the burner input rate to reflect gas
characteristics at a temperature of 60 °F and
atmospheric pressure of 30 in of Hg and
adjust down to within ±2 percent of the
hourly Btu nameplate input rating specified
by the manufacturer as measured during the
steady-state performance test in section 8 of
this appendix. Set the primary air shutters in
accordance with the I&O manual to give a
good flame at this condition. If, however, the
setting results in the deposit of carbon on the
burners during any test specified herein, the
tester shall adjust the shutters and burners
until no more carbon is deposited and shall
perform the tests again with the new settings
(see Figure 9 of ASHRAE 103–1993
(incorporated by reference, see § 430.3)).
After the steady-state performance test has
been started, do not make additional
adjustments to the burners during the
required series of performance tests specified
in section 9 of ASHRAE 103–1993. If a ventlimiting means is provided on a gas pressure
regulator, keep it in place during all tests.
7.4 Modulating gas burner adjustment at
reduced input rate. For gas-fired furnaces
and boilers equipped with modulating-type
controls, adjust the controls to operate the
unit at the nameplate minimum input rate. If
the modulating control is of a non-automatic
type, adjust the control to the setting
recommended in the I&O manual. In the
absence of such recommendation, the
midpoint setting of the non-automatic control
shall be used as the setting for determining
the reduced fuel input rate. Start the furnace
or boiler by turning the safety control valve
to the ‘‘ON’’ position. For boilers, use a
supply water temperature that will allow for
continuous operation without shutoff by the
control. If necessary to achieve such
continuous operation, supply water may be
increased above 120 °F; in such cases,
gradually increase the supply water
temperature to determine what minimum
supply water temperature, with a 20 °F
temperature rise across the boiler, will be
needed to adjust for the minimum input rate
at the reduced input rate control setting.
Monitor regulated gas pressure out of the
modulating control valve (or entering the
burner) to determine when no further
reduction of gas pressure results. The flow
rate of water through the boiler shall be
adjusted to achieve a 20 °F temperature rise.
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
7.5 Oil burner. Adjust the burners of oilfired furnaces or boilers to give a CO2 reading
specified in the I&O manual and an hourly
Btu input during the steady-state
performance test described in section 8 of
this appendix. Ensure the hourly BTU input
is within ±2% of the normal hourly Btu input
rating as specified in the I&O manual. Smoke
in the flue may not exceed a No. 1 smoke
during the steady-state performance test as
measured by the procedure in ASTM
D2156R13 (incorporated by reference, see
§ 430.3). Maintain the average draft over the
fire and in the flue during the steady-state
performance test at the value specified in the
I&O manual. Do not allow draft fluctuations
exceeding 0.005 in. water. Do not make
additional adjustments to the burner during
the required series of performance tests. The
instruments and measuring apparatus for this
test are described in section 6 of this
appendix and shown in Figure 8 of ASHRAE
103–1993 (incorporated by reference, see
§ 430.3).
7.6 Adjust air throughputs to achieve a
temperature rise that is the higher of a and
b, below, unless c applies. A tolerance of ±2
°F is permitted.
a. 15 °F less than the nameplate maximum
temperature rise or
b. 15 °F higher than the minimum
temperature rise specified in the I&O manual.
c. A furnace with a non-adjustable air
temperature rise range and an automatically
controlled airflow that does not permit a
temperature rise range of 30°F or more must
be tested at the midpoint of the rise range.
7.7 Establish the temperature rise
specified in section 7.6 of this appendix by
adjusting the circulating airflow. This
adjustment must be accomplished by
symmetrically restricting the outlet air duct
and varying blower speed selection to obtain
the desired temperature rise and minimum
external static pressure, as specified in Table
4 of ASHRAE 103–1993 (incorporated by
reference, see § 430.3). If the required
temperature rise cannot be obtained at the
minimum specified external static pressure
by adjusting blower speed selection and duct
outlet restriction, then the following applies.
a. If the resultant temperature rise is less
than the required temperature rise, vary the
blower speed by gradually adjusting the
blower voltage so as to maintain the
minimum external static pressure listed in
Table 4 of ASHRAE 103–1993 (incorporated
by reference, see § 430.3). The airflow
restrictions shall then remain unchanged. If
static pressure must be varied to prevent
unstable blower operation, then increase the
static pressure until blower operation is
stabilized, except that the static pressure
must not exceed the maximum external static
pressure as specified by the manufacturer in
the I&O manual.
b. If the resultant temperature rise is
greater than the required temperature rise,
then the unit can be tested at a higher
temperature rise value, but one not greater
than nameplate maximum temperature rise.
In order not to exceed the maximum
temperature rise, the speed of a direct-driven
blower may be increased by increasing the
circulating air blower motor voltage.
7.8 Measurement of jacket surface
temperature. Divide the jacket of the furnace
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
2649
or boiler into 6-inch squares when practical,
and otherwise into 36-square-inch regions
comprising 4 inch by 9 inch or 3 inch by 12
inch sections, and determine the surface
temperature at the center of each square or
section with a surface thermocouple. Record
the surface temperature of the 36-square-inch
areas in groups where the temperature
differential of the 36-square-inch areas is less
than 10 °F for temperature up to 100 °F above
room temperature, and less than 20 °F for
temperatures more than 100 °F above room
temperature. For forced-air central furnaces,
the circulating air blower compartment is
considered as part of the duct system, and no
surface temperature measurement of the
blower compartment needs to be recorded for
the purpose of this test. For downflow
furnaces, measure all cabinet surface
temperatures of the heat exchanger and
combustion section, including the bottom
around the outlet duct and the burner door,
using the 36-square-inch thermocouple grid.
The cabinet surface temperatures around the
blower section do not need to be measured
(See Figure 3–E of ASHRAE 103–1993
(incorporated by reference, see § 430.3)).
7.9 Installation of vent system. Keep the
vent or air intake system supplied by the
manufacturer in place during all tests. Test
units intended for installation with a variety
of vent pipe lengths with the minimum vent
length as specified in the I&O manual, or a
5-ft. flue pipe if there are no
recommendations in the I&O manual. Do not
connect a furnace or boiler employing a
direct vent system to a chimney or induceddraft source. Vent combustion products
solely by using the venting incorporated in
the furnace or boiler and the vent or air
intake system supplied by the manufacturer.
For units that are not designed to
significantly preheat the incoming air, see
section 7.5 of this appendix and Figure 4a or
4b of ASHRAE 103–1993 (incorporated by
reference, see § 430.3). For units that do
significantly preheat the incoming air, see
Figure 4c or 4d of ASHRAE 103–1993.
7.10 Additional optional method of
testing for determining DP and DF for
furnaces and boilers. On units whose design
is such that there is no measurable airflow
through the combustion chamber and heat
exchanger when the burner(s) is (are) off as
determined by the optional test procedure in
section 7.10.1 of this appendix, DF and DP
may be set equal to 0.05.
7.10.1 Optional test method for
indicating the absence of flow through the
heat exchanger. Manufacturers may use the
following test protocol to determine whether
air flows through the combustion chamber
and heat exchanger when the burner(s) is
(are) off. The minimum default draft factor
(as allowed per sections 8.8.3 and 9.10 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3)) may be used only for
units determined pursuant to this protocol to
have no airflow through the combustion
chamber and heat exchanger.
7.10.1.1 Test apparatus. Use a smoke
stick that produces smoke that is easily
visible and has a density less than or
approximately equal to air. Use a smoke stick
that produces smoke that is non-toxic to the
test personnel and produces gas that is
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
2650
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
unreactive with the environment in the test
chamber.
7.10.1.2 Test conditions. Minimize all air
currents and drafts in the test chamber,
including turning off ventilation if the test
chamber is mechanically ventilated. Wait at
least two minutes following the termination
of the furnace or boiler on-cycle before
beginning the optional test method for
indicating the absence of flow through the
heat exchanger.
7.10.1.3 Location of the test apparatus.
After all air currents and drafts in the test
chamber have been eliminated or minimized,
position the smoke stick based on the
following equipment configuration: (a) For
horizontal combustion air intakes,
approximately 4 inches from the vertical
plane at the termination of the intake vent
and 4 inches below the bottom edge of the
combustion air intake; or (b) for vertical
combustion air intakes, approximately 4
inches horizontal from vent perimeter at the
termination of the intake vent and 4 inches
down (parallel to the vertical axis of the
vent). In the instance where the boiler
combustion air intake is closer than 4 inches
to the floor, place the smoke device directly
on the floor without impeding the flow of
smoke.
7.10.1.4 Duration of test. Establish the
presence of smoke from the smoke stick and
then monitor the direction of the smoke flow
for no less than 30 seconds.
7.10.1.5 Test results. During visual
assessment, determine whether there is any
draw of smoke into the combustion air intake
vent.
If absolutely no smoke is drawn into the
combustion air intake, the furnace or boiler
meets the requirements to allow use of the
minimum default draft factor pursuant to
section 8.8.3 and/or section 9.10 of ASHRAE
103–1993 (incorporated by reference, see
§ 430.3).
If there is any smoke drawn into the intake,
proceed with the methods of testing as
prescribed in section 8.8 of ASHRAE 103–
1993.
8.0 Test procedure. Conduct testing and
measurements as specified in section 9 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3) except for sections
9.1.2.2.1, 9.1.2.2.2, 9.5.1.1, 9.5.1.2.1,
9.5.1.2.2, 9.5.2.1, 9.7.4, and 9.10; and as
specified in sections 8.1 through 8.11 of this
appendix. Section 8.4 of this appendix may
be used in lieu of section 9.2 of ASHRAE
103–1993.
8.1 Fuel input. For gas units, measure and
record the steady-state gas input rate in Btu/
hr, including pilot gas, corrected to standard
conditions of 60 °F and 30 in. Hg. Use
measured values of gas temperature and
pressure at the meter and barometric pressure
to correct the metered gas flow rate to the
above standard conditions. For oil units,
measure and record the steady-state fuel
input rate.
8.2 Electrical input. For furnaces and
boilers, during the steady-state test, perform
a single measurement of all of the electrical
power involved in burner operation (PE),
including energizing the ignition system,
controls, gas valve or oil control valve, and
draft inducer, if applicable. For boilers, the
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
measurement of PE must include the boiler
pump if so equipped. If the boiler pump does
not operate during the measurement of PE,
add the boiler pump nameplate power to the
measurement of PE. If the boiler pump
nameplate power is not available, use 0.13
kW.
For furnaces, during the steady-state test,
perform a single measurement of the
electrical power to the circulating air blower
(BE). For hot water boilers, use the
circulating water pump nameplate power for
BE, or if the pump nameplate power is not
available, use 0.13 kW.
8.3 Input to interrupted ignition device.
For burners equipped with an interrupted
ignition device, record the nameplate electric
power used by the ignition device, PEIG, or
record that PEIG = 0.4 kW if no nameplate
power input is provided. Record the
nameplate ignition device on-time interval,
tIG, or, if the nameplate does not provide the
ignition device on-time interval, measure the
on-time interval with a stopwatch at the
beginning of the test, starting when the
burner is turned on. Set tIG = 0 and PEIG =
0 if the device on-time interval is less than
or equal to 5 seconds after the burner is on.
8.4 Optional test procedures for
condensing furnaces and boilers,
measurement of condensate during the
establishment of steady-state conditions. For
units with step-modulating or two-stage
controls, conduct the test at both the
maximum and reduced inputs. In lieu of
collecting the condensate immediately after
the steady state conditions have been reached
as required by section 9.2 of ASHRAE 103–
1993 (incorporated by reference, see § 430.3),
condensate may be collected during the
establishment of steady state conditions as
defined by section 9.1.2.1 of ASHRAE 103–
1993. Perform condensate collection for at
least 30 minutes. Measure condensate mass
immediately at the end of the collection
period to prevent evaporation loss from the
sample. Record fuel input for the 30-minute
condensate collection test period. Observe
and record fuel higher heating value (HHV),
temperature, and pressures necessary for
determining fuel energy input (Qc,ss).
Measure the fuel quantity and HHV with
errors no greater than 1%. The humidity for
the room air shall at no time exceed 80%.
Determine the mass of condensate for the
establishment of steady state conditions
(Mc,ss) in pounds by subtracting the tare
container weight from the total container and
condensate weight measured at the end of the
30-minute condensate collection test period.
8.5 Cool-down test for gas- and oil-fueled
gravity and forced-air central furnaces
without stack dampers. Turn off the main
burner after completing steady-state testing,
and measure the flue gas temperature by
means of the thermocouple grid described in
section 7.6 of ASHRAE 103–1993
(incorporated by reference, see § 430.3) at 1.5
minutes (TF,OFF(t3)) and 9 minutes (TF,OFF(t4))
after shutting off the burner. When taking
these temperature readings, the integral draft
diverter must remain blocked and insulated,
and the stack restriction must remain in
place. On atmospheric systems with an
integral draft diverter or draft hood and
equipped with either an electromechanical
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
inlet damper or an electromechanical flue
damper that closes within 10 seconds after
the burner shuts off to restrict the flow
through the heat exchanger in the off-cycle,
bypass or adjust the control for the
electromechanical damper so that the damper
remains open during the cool-down test.
For furnaces that employ post-purge,
measure the length of the post-purge period
with a stopwatch. Record the time from
burner ‘‘OFF’’ to combustion blower ‘‘OFF’’
(electrically de-energized) as tP. If the
measured tP is less than or equal to 30
seconds, set tP at 0 and conduct the cooldown test as if there is no post-purge. If tP
is prescribed by the I&O manual or measured
to be greater than 180 seconds, stop the
combustion blower at 180 seconds and use
that value for tP. Measure the flue gas
temperature by means of the thermocouple
grid described in section 7.6 of ASHRAE
103–1993 at the end of the post-purge period,
tP(TF,OFF (tP)), and at the time (1.5 + tP)
minutes (TF,OFF(t3)) and (9.0 + tP) minutes
(TF,OFF(t4)) after the main burner shuts off.
8.6 Cool-down test for gas- and oil-fueled
gravity and forced-air central furnaces
without stack dampers and with adjustable
fan control. For a furnace with adjustable fan
control, measure the time delay between
burner shutdown and blower shutdown, t+.
This time delay, t+, will be 3.0 minutes for
non-condensing furnaces or 1.5 minutes for
condensing furnaces or until the supply air
temperature drops to a value of 40 °F above
the inlet air temperature, whichever results
in the longest fan on-time. For a furnace
without adjustable fan control or with the
type of adjustable fan control whose range of
adjustment does not allow for the time delay,
t+, specified above, bypass the fan control
and manually control the fan to allow for the
appropriate delay time as specified in section
9.5.1.2 of ASHRAE 103–1993 (incorporated
by reference, see § 430.3). For a furnace that
employs a single motor to drive both the
power burner and the indoor air circulating
blower, the power burner and indoor air
circulating blower must be stopped at the
same time
8.7 Cool-down test for gas- and oil-fueled
boilers without stack dampers. After steadystate testing has been completed, turn the
main burner(s) ‘‘OFF’’ and measure the flue
gas temperature at 3.75 minutes (temperature
designated as TF,OFF(t3)) and 22.5 minutes
(temperature designated as TF,OFF(t4)) after
the burner shut-off using the thermocouple
grid described in section 7.6 of ASHRAE
103–1993 (incorporated by reference, see
§ 430.3).
a. During this off-period, for units that do
not have pump delay after shut-off, do not
allow any water to circulate through the hot
water boilers.
b. For units that have pump delay on shutoff, except those having pump controls
sensing water temperature, the unit control
must stop the pump. Measure and record the
time between burner shut-off and pump shutoff (t+) to the nearest second.
c. For units having pump delay controls
that sense water temperature, operate the
pump for 15 minutes and record t+ as 15
minutes. While the pump is operating,
maintain the inlet water temperature and
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
provision of section 8.2.1.4, Electrical
Supply, of ASHRAE 103–1993 shall apply in
lieu of the corresponding provisions of IEC
62301 at section 4.2, Test room, and the
voltage specification of section 4.3, Power
supply. Frequency shall be 60Hz. Clarifying
further, IEC 62301 section 4.4, Power
measurement instruments, and section 5,
Measurements, apply in lieu of ASHRAE
103–1993 section 6.10, Energy Flow Rate.
Measure the wattage so that all possible
standby mode wattage for the entire
appliance is recorded, not just the standby
mode wattage of a single auxiliary. Round the
recorded standby power (PW,SB) to the second
decimal place, except for loads greater than
or equal to 10W, which must be recorded to
at least three significant figures.
8.11.2 Off mode power measurement. If
the unit is equipped with an off switch or
there is an expected difference between off
mode power and standby mode power,
measure off mode power (PW,OFF) in
accordance with the standby power
procedures in IEC 62301 (incorporated by
reference, see § 430.3), except that section
8.5, Room Ambient Temperature, of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3) and the voltage
provision of section 8.2.1.4, Electrical
Supply, of ASHRAE 103–1993 shall apply in
lieu of the corresponding provisions of IEC
62301 at section 4.2, Test room, and the
voltage specification of section 4.3, Power
supply. Frequency shall be 60Hz. Clarifying
further, IEC 62301 section 4.4, Power
measurement instruments, and section 5,
Measurements, apply for this measurement
in lieu of ASHRAE 103–1993 section 6.10,
Energy Flow Rate. Measure the wattage so
that all possible off mode wattage for the
entire appliance is recorded, not just the off
mode wattage of a single auxiliary. If there
is no expected difference in off mode power
and standby mode power, let PW,OFF = PW,SB,
in which case no separate measurement of off
mode power is necessary. Round the
recorded off mode power (PW,OFF) to the
second decimal place, except for loads
greater than or equal to 10W, in which case
round the recorded value to at least three
significant figures.
9.0 Nomenclature. Nomenclature
includes the nomenclature specified in
section 10 of ASHRAE 103–1993
(incorporated by reference, see § 430.3) and
the following additional variables:
Effmotor = Efficiency of power burner motor
PEIG = Electrical power to the interrupted
ignition device, kW
RT,a = RT,F if flue gas is measured
= RT,S if stack gas is measured
RT,F = Ratio of combustion air mass flow rate
to stoichiometric air mass flow rate
PO 00000
Frm 00025
Fmt 4701
Sfmt 4725
RT,S = Ratio of the sum of combustion air and
relief air mass flow rate to stoichiometric
air mass flow rate
tIG = Electrical interrupted ignition device
on-time, min.
Ta,SS,X = TF,SS,X if flue gas temperature is
measured, °F
= TS,SS,X if stack gas temperature is
measured, °F
yIG = Ratio of electrical interrupted ignition
device on-time to average burner on-time
yP = Ratio of power burner combustion
blower on-time to average burner ontime
ESO = Average annual electric standby mode
and off mode energy consumption, in
kilowatt-hours
PW,OFF = Furnace or boiler off mode power,
in watts
PW,SB = Furnace or boiler standby mode
power, in watts
10.0 Calculation of derived results from
test measurements. Perform calculations as
specified in section 11 of ASHRAE 103–1993
(incorporated by reference, see § 430.3),
except for sections 11.5.11.1, 11.5.11.2, and
appendices B and C; and as specified in
sections 10.1 through 10.11 and Figure 1 of
this appendix.
10.1 Annual fuel utilization efficiency.
The annual fuel utilization efficiency (AFUE)
is as defined in sections 11.2.12 (noncondensing systems), 11.3.12 (condensing
systems), 11.4.12 (non-condensing
modulating systems) and 11.5.12 (condensing
modulating systems) of ASHRAE 103–1993
(incorporated by reference, see § 430.3),
except for the definition for the term EffyHS
in the defining equation for AFUE. EffyHS is
defined as:
EffyHS = heating seasonal efficiency as
defined in sections 11.2.11 (noncondensing systems), 11.3.11
(condensing systems), 11.4.11 (noncondensing modulating systems) and
11.5.11 (condensing modulating systems)
of ASHRAE 103–1993, except that for
condensing modulating systems sections
11.5.11.1 and 11.5.11.2 are replaced by
sections 10.2 and 10.3 of this appendix.
EffyHS is based on the assumptions that
all weatherized warm air furnaces or
boilers are located outdoors, that nonweatherized warm air furnaces are
installed as isolated combustion systems,
and that non-weatherized boilers are
installed indoors.
10.2 Part-load efficiency at reduced fuel
input rate. If the option in section 8.10 of this
appendix is not employed, calculate the partload efficiency at the reduced fuel input rate,
EffyU,R, for condensing furnaces and boilers
equipped with either step-modulating or twostage controls, expressed as a percent and
defined as:
E:\FR\FM\15JAR4.SGM
15JAR4
ER15JA16.016
tkelley on DSK3SPTVN1PROD with RULES4
flow rate at the same values as used during
the steady-state test, as specified in sections
9.1 and 8.4.2.3 of ASHRAE 103–1993
(incorporated by reference, see § 430.3).
d. For boilers that employ post-purge,
measure the length of the post-purge period
with a stopwatch. Record the time from
burner ‘‘OFF’’ to combustion blower ‘‘OFF’’
(electrically de-energized) as tP. If tP is
prescribed by the I&O manual or measured to
be greater than 180 seconds, stop the
combustion blower at 180 seconds and use
that value for tP. Measure the flue gas
temperature by means of the thermocouple
grid described in section 7.6 of ASHRAE
103–1993 at the end of the post-purge period
tP (TF,OFF(tP)) and at (3.75 + tP) minutes
(TF,OFF(t3)) and (22.5 + tP) minutes (TF,OFF(t4))
after the main burner shuts off. If the
measured tP is less than or equal to 30
seconds, record tP as 0 and conduct the cooldown test as if there is no post-purge.
8.8 Direct measurement of off-cycle losses
testing method. [Reserved.]
8.9 Calculation options. The rate of the
flue gas mass flow through the furnace and
the factors DP, DF, and DS are calculated by
the equations in sections 11.6.1, 11.6.2,
11.6.3, 11.6.4, 11.7.1, and 11.7.2 of ASHRAE
103–1993 (incorporated by reference, see
§ 430.3). On units whose design is such that
there is no measurable airflow through the
combustion chamber and heat exchanger
when the burner(s) is (are) off (as determined
by the optional test procedure in section 7.10
of this appendix), DF and DP may be set equal
to 0.05.
8.10 Optional test procedures for
condensing furnaces and boilers that have no
off-period flue losses. For units that have
applied the test method in section 7.10 of
this appendix to determine that no
measurable airflow exists through the
combustion chamber and heat exchanger
during the burner off-period and having postpurge periods of less than 5 seconds, the
cool-down and heat-up tests specified in
sections 9.5 and 9.6 of ASHRAE 103–1993
(incorporated by reference, see § 430.3) may
be omitted. In lieu of conducting the cooldown and heat-up tests, the tester may use
the losses determined during the steady-state
test described in section 9.1 of ASHRAE 103–
1993 when calculating heating seasonal
efficiency, EffyHS.
8.11 Measurement of electrical standby
and off mode power.
8.11.1 Standby power measurement. With
all electrical auxiliaries of the furnace or
boiler not activated, measure the standby
power (PW,SB) in accordance with the
procedures in IEC 62301 (incorporated by
reference, see § 430.3), except that section
8.5, Room Ambient Temperature, of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3) and the voltage
2651
2652
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
If the option in section 8.10 of this
appendix is employed, calculate EffyU,R as
follows:
Where:
LL,A = value as defined in section 11.2.7 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3)
LG = value as defined in section 11.3.11.1 of
ASHRAE 103–1993, at reduced input
rate,
LC = value as defined in section 11.3.11.2 of
ASHRAE 103–1993 at reduced input
rate,
LJ = value as defined in section 11.4.8.1.1 of
ASHRAE 103–1993 at maximum input
rate,
tON = value as defined in section 11.4.9.11 of
ASHRAE 103–1993,
QP = pilot fuel input rate determined in
accordance with section 9.2 of ASHRAE
103–1993 in Btu/h,
QIN = value as defined in section 11.4.8.1.1
of ASHRAE 103–1993,
tOFF = value as defined in section 11.4.9.12
of ASHRAE 103–1993 at reduced input
rate,
LS,ON = value as defined in section 11.4.10.5
of ASHRAE 103–1993 at reduced input
rate,
LS,OFF = value as defined in section 11.4.10.6
of ASHRAE 103–1993 at reduced input
rate,
LI,ON = value as defined in section 11.4.10.7
of ASHRAE 103–1993 at reduced input
rate,
LI,OFF = value as defined in section 11.4.10.8
of ASHRAE 103–1993 at reduced input
rate,
CJ = jacket loss factor and equal to:
= 0.0 for furnaces or boilers intended to be
installed indoors
= 1.7 for furnaces intended to be installed
as isolated combustion systems
= 2.4 for boilers (other than finned-tube
boilers) intended to be installed as
isolated combustion systems
= 3.3 for furnaces intended to be installed
outdoors
= 4.7 for boilers (other than finned-tube
boilers) intended to be installed outdoors
= 1.0 for finned-tube boilers intended to be
installed outdoors
= 0.5 for finned-tube boilers intended to be
installed in isolated combustion system
applications
LS,SS = value as defined in section 11.4.6 of
ASHRAE 103–1993 at reduced input
rate,
CS = value as defined in section 11.3.10.1 of
ASHRAE 103–1993 at reduced input
rate.
10.3 Part-Load Efficiency at Maximum
Fuel Input Rate. If the option in section 8.10
of this appendix is not employed, calculate
the part-load efficiency at maximum fuel
input rate, EffyU,H, for condensing furnaces
and boilers equipped with two-stage controls,
expressed as a percent and defined as:
QIN = value as defined in section 11.4.8.1.1
of ASHRAE 103–1993,
tOFF = value as defined in section 11.4.9.12
of ASHRAE 103–1993 at maximum input
rate,
LS,ON = value as defined in section 11.4.10.5
of ASHRAE 103–1993 at maximum input
rate,
LS,OFF = value as defined in section 11.4.10.6
of ASHRAE 103–1993 at maximum input
rate,
LI,ON = value as defined in section 11.4.10.7
of ASHRAE 103–1993 at maximum input
rate,
LI,OFF = value as defined in section 11.4.10.8
of ASHRAE 103–1993 at maximum input
rate,
CJ = value as defined in section 10.2 of this
appendix,
LS,SS = value as defined in section 11.4.6 of
ASHRAE 103–1993 at maximum input
rate,
CS = value as defined in section 11.4.10.1 of
ASHRAE 103–1993 at maximum input
rate.
10.4 National average burner operating
hours, average annual fuel energy
consumption, and average annual auxiliary
electrical energy consumption for gas or oil
furnaces and boilers.
10.4.1 National average number of burner
operating hours. For furnaces and boilers
equipped with single-stage controls, the
national average number of burner operating
hours is defined as:
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
E:\FR\FM\15JAR4.SGM
15JAR4
ER15JA16.014 ER15JA16.015
Where:
LL,A = value as defined in section 11.2.7 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3),
LG = value as defined in section 11.3.11.1 of
ASHRAE 103–1 at maximum input rate,
LC = value as defined in section 11.3.11.2 of
ASHRAE 103–1993 at maximum input
rate,
LJ = value as defined in section 11.4.8.1.1 of
ASHRAE 103–1993 at maximum input
rate,
tON = value as defined in section 11.4.9.11 of
ASHRAE 103–1993,
QP = pilot fuel input rate determined in
accordance with section 9.2 of ASHRAE
103–1993 in Btu/h,
ER15JA16.017
tkelley on DSK3SPTVN1PROD with RULES4
If the option in section 8.10 of this
appendix is employed, calculate EffyU,H as
follows:
tkelley on DSK3SPTVN1PROD with RULES4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
BOHSS = 2,080 (0.77) (A) DHR ¥ 2,080 (B)
Where:
2,080 = national average heating load hours
0.77 = adjustment factor to adjust the
calculated design heating requirement
and heating load hours to the actual
heating load experienced by the heating
system
A = 100,000/[341,300 (yP PE + yIG PEIG + y
BE) + (QIN ¥ QP) EffyHS], for forced draft
unit, indoors
= 100,000/[341,300 (yP PE Effmotor + yIG
PEIG + y BE) + (QIN ¥ QP) EffyHS], for
forced draft unit, isolated combustion
system,
= 100,000/[341,300 (yP PE (1 ¥ Effmotor) +
yIG PEIG + y BE) + (QIN ¥ QP) EffyHS],
for induced draft unit, indoors, and
= 100,000/[341,300 (yIG PEIG + y BE) + (QIN
¥ QP) EffyHS], for induced draft unit,
isolated combustion system.
DHR = typical design heating requirements as
listed in Table 8 (in kBtu/h) of ASHRAE
103–1993 (incorporated by reference, see
§ 430.3), using the proper value of QOUT
defined in 11.2.8.1 of ASHRAE 103–
1993.
B = 2 QP (EffyHS) (A)/100,000
Where:
Effmotor = nameplate power burner motor
efficiency provided by the manufacturer,
= 0.50, an assumed default power burner
efficiency if not provided by the
manufacturer.
100,000 = factor that accounts for percent
and kBtu
yP = ratio of induced or forced draft blower
on-time to average burner on-time, as
follows:
1 for units without post-purge;
1 + (tP/3.87) for single stage furnaces with
post purge;
1 + (tP/10) for two-stage and step
modulating furnaces with post purge;
1 + (tP/9.68) for single stage boilers with
post purge; or
1 + (tP/15) for two stage and step
modulating boilers with post purge.
PE = all electrical power related to burner
operation at full load steady-state
operation, including electrical ignition
device if energized, controls, gas valve or
oil control valve, draft inducer, and
boiler pump, as determined in section
8.2 of this appendix.
yIG = ratio of burner interrupted ignition
device on-time to average burner ontime, as follows:
0 for burners not equipped with
interrupted ignition device;
(tIG/3.87) for single-stage furnaces or
boilers;
(tIG/10) for two-stage and step modulating
furnaces;
(tIG/9.68) for single stage boilers; or
(tIG/15) for two stage and step modulating
boilers.
PEIG = electrical input rate to the interrupted
ignition device on burner (if employed),
as defined in section 8.3 of this appendix
y = ratio of blower or pump on-time to
average burner on-time, as follows:
1 for furnaces without fan delay or boilers
without a pump delay;
1 + (t+ ¥ t¥)/3.87 for single-stage furnaces
with fan delay;
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
1 + (t+ ¥ t¥)/10 for two-stage and step
modulating furnaces with fan delay;
1 + (t+/9.68) for single-stage boilers with
pump delay;
1 + (t+/1.5) for two-stage and step
modulating boilers with pump delay.
BE = circulating air fan or water pump
electrical energy input rate at full-load
steady-state operation as defined in
section 8.2 of this appendix.
tP = post-purge time as defined in section 8.5
(furnace) or section 8.7 (boiler) of this
appendix
= 0 if tP is equal to or less than 30 second
tIG = on-time of the burner interrupted
ignition device, as defined in section 8.3
of this appendix
QIN = as defined in section 11.2.8.1 of
ASHRAE 103–1993
QP = as defined in section 11.2.11 of
ASHRAE 103–1993
EffyHS = as defined in section 11.2.11 (noncondensing systems) or section 11.3.11.3
(condensing systems) of ASHRAE 103–
1993, percent, and calculated on the
basis of:
isolated combustion system installation,
for non-weatherized warm air furnaces;
indoor installation, for non-weatherized
boilers; or
outdoor installation, for furnaces and
boilers that are weatherized.
2 = ratio of the average length of the heating
season in hours to the average heating
load hours
t+ = delay time between burner shutoff and
the blower or pump shutoff measured as
defined in section 9.5.1.2 of ASHRAE
103–1993 (furnace) or section 8.7 of this
appendix (boiler).
t¥ = as defined in section 9.6.1 of ASHRAE
103–1993
10.4.1.1 For furnaces and boilers
equipped with two stage or step modulating
controls the average annual energy used
during the heating season, EM, is defined as:
EM = (QIN ¥ QP) BOHSS + (8,760 ¥ 4,600)
QP
Where:
QIN = as defined in 11.4.8.1.1 of ASHRAE
103–1993 (incorporated by reference, see
§ 430.3)
QP = as defined in 11.4.12 of ASHRAE 103–
1993
BOHSS = as defined in section 10.4.1 of this
appendix, in which the weighted EffyHS
as defined in 11.4.11.3 or 11.5.11.3 of
ASHRAE 103–1993 is used for
calculating the values of A and B, the
term DHR is based on the value of QOUT
defined in 11.4.8.1.1 or 11.5.8.1.1 of
ASHRAE 103–1993, and the term (yPPE
+ yIGPEIG + yBE) in the factor A is
increased by the factor R, which is
defined as:
R = 2.3 for two stage controls
= 2.3 for step modulating controls when
the ratio of minimum-to-maximum
output is greater than or equal to 0.5
= 3.0 for step modulating controls when
the ratio of minimum-to-maximum
output is less than 0.5
A = 100,000/[341,300 (yP PE + yIG PEIG + y
BE) R + (QIN ¥ QP) EffyHS], for forced
draft unit, indoors
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
2653
= 100,000/[341,300 (yP PE Effmotor + yIG
PEIG + y BE) R + (QIN ¥ QP) EffyHS], for
forced draft unit, isolated combustion
system,
= 100,000/[341,300 (yP PE (1 ¥ Effmotor) +
yIG PEIG + y BE) R + (QIN ¥ QP) EffyHS],
for induced draft unit, indoors, and
= 100,000/[341,300 (yIG PEIG + y BE) R +
(QIN ¥ QP) EffyHS], for induced draft
unit, isolated combustion system.
Where:
Effmotor = nameplate power burner motor
efficiency provided by the manufacturer,
= 0.50, an assumed default power burner
efficiency if not provided by the
manufacturer.
EffyHS = as defined in 11.4.11.3 or 11.5.11.3
of ASHRAE 103–1993, and calculated on
the basis of:
isolated combustion system installation,
for non-weatherized warm air furnaces;
indoor installation, for non-weatherized
boilers; or
outdoor installation, for furnaces and
boilers that are weatherized.
8,760 = total number of hours per year
4,600 = as defined in 11.4.12 of ASHRAE
103–1993
10.4.1.2 For furnaces and boilers
equipped with two-stage or step-modulating
controls, the national average number of
burner operating hours at the reduced
operating mode (BOHR) is defined as:
BOHR = XR EM/QIN,R
Where:
XR = as defined in 11.4.8.7 of ASHRAE 103–
1993 (incorporated by reference, see
§ 430.3)
EM = as defined in section 10.4.1.1 of this
appendix
QIN,R = as defined in 11.4.8.1.2 of ASHRAE
103–1993
10.4.1.3 For furnaces and boilers
equipped with two-stage controls, the
national average number of burner operating
hours at the maximum operating mode
(BOHH) is defined as:
BOHH = XH EM/QIN
Where:
XH = as defined in 11.4.8.6 of ASHRAE 103–
1993 (incorporated by reference, see
§ 430.3)
EM = as defined in section 10.4.1.1 of this
appendix
QIN = as defined in section 11.4.8.1.1 of
ASHRAE 103–1993
10.4.1.4 For furnaces and boilers
equipped with step-modulating controls, the
national average number of burner operating
hours at the modulating operating mode
(BOHM) is defined as:
BOHM = XH EM/QIN,M
Where:
XH = as defined in 11.4.8.6 of ASHRAE 103–
1993 (incorporated by reference, see
§ 430.3)
EM = as defined in section 10.4.1.1 of this
appendix
QIN,M = QOUT,M/(EffySS,M/100)
QOUT,M = as defined in 11.4.8.10 or 11.5.8.10
of ASHRAE 103–1993, as appropriate
EffySS,M = as defined in 11.4.8.8 or 11.5.8.8
of ASHRAE 103–1993, as appropriate, in
percent
E:\FR\FM\15JAR4.SGM
15JAR4
tkelley on DSK3SPTVN1PROD with RULES4
2654
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
100 = factor that accounts for percent
10.4.2 Average annual fuel energy
consumption for gas or oil fueled furnaces or
boilers. For furnaces or boilers equipped with
single-stage controls, the average annual fuel
energy consumption (EF) is expressed in Btu
per year and defined as:
EF = BOHSS (QIN ¥ QP) + 8,760 QP
Where:
BOHSS = as defined in section 10.4.1 of this
appendix
QIN = as defined in section 11.2.8.1 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3)
QP = as defined in section 11.2.11 of
ASHRAE 103–1993
8,760 = as defined in section 10.4.1.1 of this
appendix
10.4.2.1 For furnaces or boilers equipped
with either two-stage or step modulating
controls, EF is defined as:
EF = EM + 4,600 QP
Where:
EM = as defined in section 10.4.1.1 of this
appendix
4,600 = as defined in section 11.4.12 of
ASHRAE 103–1993
QP = as defined in section 11.2.11 of
ASHRAE 103–1993
10.4.3 Average annual auxiliary electrical
energy consumption for gas or oil-fueled
furnaces or boilers. For furnaces and boilers
equipped with single-stage controls, the
average annual auxiliary electrical
consumption (EAE) is expressed in kilowatthours and defined as:
EAE = BOHSS (yP PE + yIG PEIG + yBE) + ESO
Where:
BOHSS = as defined in section 10.4.1 of this
appendix
yP = as defined in section 10.4.1 of this
appendix
PE = as defined in section 10.4.1 of this
appendix
yIG = as defined in section 10.4.1 of this
appendix
PEIG = as defined in section 10.4.1 of this
appendix
y = as defined in section 10.4.1 of this
appendix
BE = as defined in section 10.4.1 of this
appendix
ESO = as defined in section 10.11 of this
appendix
10.4.3.1 For furnaces or boilers equipped
with two-stage controls, EAE is defined as:
EAE = BOHR (yP PER + yIG PEIG + yBER) +
BOHH (yP PEH + yIG PEIG + y BEH) + ESO
Where:
BOHR = as defined in section 10.4.1.2 of this
appendix
yP = as defined in section 10.4.1 of this
appendix
PER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
yIG = as defined in section 10.4.1 of this
appendix
PEIG = as defined in section 10.4.1 of this
appendix
y = as defined in section 10.4.1 of this
appendix
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
BER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
BOHH = as defined in section 10.4.1.3 of this
appendix
PEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
BEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
ESO = as defined in section 10.11 of this
appendix
10.4.3.2 For furnaces or boilers equipped
with step-modulating controls, EAE is defined
as:
EAE = BOHR (yP PER + yIG PEIG + y BER) +
BOHM (yP PEH + yIG PEIG + y BEH) + ESO
Where:
BOHR = as defined in section 10.4.1.2 of this
appendix
yP = as defined in section 10.4.1 of this
appendix
PER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
yIG = as defined in section 10.4.1 of this
appendix
PEIG = as defined in section 10.4.1 of this
appendix
y = as defined in section 10.4.1 of this
appendix
BER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
BOHM = as defined in 10.4.1.4 of this
appendix
PEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
BEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
ESO = as defined in section 10.11 of this
appendix
10.5 Average annual electric energy
consumption for electric furnaces or boilers.
For electric furnaces and boilers, the average
annual electrical energy consumption (EE) is
expressed in kilowatt-hours and defined as:
EE = 100 (2,080) (0.77) DHR/(3.412 AFUE) +
ESO
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.4.1 of this
appendix
0.77 = as defined in section 10.4.1 of this
appendix
DHR = as defined in section 10.4.1 of this
appendix
3.412 = conversion factor from watt-hours to
Btu
AFUE = as defined in section 11.1 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3), in percent, and
calculated on the basis of:
isolated combustion system installation,
for non-weatherized warm air furnaces;
indoor installation, for non-weatherized
boilers; or
outdoor installation, for furnaces and
boilers that are weatherized.
ESO = as defined in section 10.11 of this
appendix.
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
10.6 Energy factor.
10.6.1 Energy factor for gas or oil
furnaces and boilers. Calculate the energy
factor, EF, for gas or oil furnaces and boilers
defined as, in percent:
EF = (EF ¥ 4,600 (QP))(EffyHS)/(EF + 3,412
(EAE))
Where:
EF = average annual fuel consumption as
defined in section 10.4.2 of this
appendix
4,600 = as defined in section 11.4.12 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3)
QP = pilot fuel input rate determined in
accordance with section 9.2 of ASHRAE
103–1993 in Btu/h
EffyHS = annual fuel utilization efficiency as
defined in sections 11.2.11, 11.3.11,
11.4.11 or 11.5.11 of ASHRAE 103–1993,
in percent, and calculated on the basis
of:
isolated combustion system installation,
for non-weatherized warm air furnaces;
indoor installation, for non-weatherized
boilers; or
outdoor installation, for furnaces and
boilers that are weatherized.
3,412 = conversion factor from kW to Btu/h
EAE = as defined in section 10.4.3 of this
appendix
10.6.2 Energy factor for electric furnaces
and boilers. The energy factor, EF, for electric
furnaces and boilers is defined as:
EF = AFUE
Where:
AFUE = annual fuel utilization efficiency as
defined in section 10.4.3 of this
appendix, in percent
10.7 Average annual energy consumption
for furnaces and boilers located in a different
geographic region of the United States and in
buildings with different design heating
requirements.
10.7.1 Average annual fuel energy
consumption for gas or oil-fueled furnaces
and boilers located in a different geographic
region of the United States and in buildings
with different design heating requirements.
For gas or oil-fueled furnaces and boilers, the
average annual fuel energy consumption for
a specific geographic region and a specific
typical design heating requirement (EFR) is
expressed in Btu per year and defined as:
EFR = (EF ¥ 8,760 QP) (HLH/2,080) + 8,760
QP
Where:
EF = as defined in section 10.4.2 of this
appendix
8,760 = as defined in section 10.4.1.1 of this
appendix
QP = as defined in section 11.2.11 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3)
HLH = heating load hours for a specific
geographic region determined from the
heating load hour map in Figure 1 of this
appendix
2,080 = as defined in section 10.4.1 of this
appendix
10.7.2 Average annual auxiliary electrical
energy consumption for gas or oil-fueled
furnaces and boilers located in a different
geographic region of the United States and in
E:\FR\FM\15JAR4.SGM
15JAR4
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES4
buildings with different design heating
requirements. For gas or oil-fueled furnaces
and boilers, the average annual auxiliary
electrical energy consumption for a specific
geographic region and a specific typical
design heating requirement (EAER) is
expressed in kilowatt-hours and defined as:
EAER = (EAE ¥ ESO) (HLH/2080) + ESOR
Where:
EAE = as defined in section 10.4.3 of this
appendix
ESO = as defined in section 10.11 of this
appendix
HLH = as defined in section 10.7.1 of this
appendix
2,080 = as defined in section 10.4.1 of this
appendix
ESOR = as defined in section 10.7.3 of this
appendix.
10.7.3 Average annual electric energy
consumption for electric furnaces and boilers
located in a different geographic region of the
United States and in buildings with different
design heating requirements. For electric
furnaces and boilers, the average annual
electric energy consumption for a specific
geographic region and a specific typical
design heating requirement (EER) is expressed
in kilowatt-hours and defined as:
EER = 100 (0.77) DHR HLH/(3.412 AFUE) +
ESOR
Where:
100 = as defined in section 10.4.3 of this
appendix
0.77 = as defined in section 10.4.1 of this
appendix
DHR = as defined in section 10.4.1 of this
appendix
HLH = as defined in section 10.7.1 of this
appendix
3.412 = as defined in section 10.4.3 of this
appendix
AFUE = as defined in section 10.4.3 of this
appendix
ESOR = ESO as defined in section 10.11 of this
appendix, except that in the equation for
ESO, the term BOH is multiplied by the
expression (HLH/2080) to get the
appropriate regional accounting of
standby mode and off mode loss.
10.8 Annual energy consumption for
mobile home furnaces
10.8.1 National average number of burner
operating hours for mobile home furnaces
(BOHSS). BOHSS is the same as in section
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
10.4.1 of this appendix, except that the value
of EffyHS in the calculation of the burner
operating hours, BOHSS, is calculated on the
basis of a direct vent unit with system
number 9 or 10.
10.8.2 Average annual fuel energy for
mobile home furnaces (EF). EF is same as in
section 10.4.2 of this appendix except that
the burner operating hours, BOHSS, is
calculated as specified in section 10.8.1 of
this appendix.
10.8.3 Average annual auxiliary electrical
energy consumption for mobile home
furnaces (EAE). EAE is the same as in section
10.4.3 of this appendix, except that the
burner operating hours, BOHSS, is calculated
as specified in section 10.8.1 of this
appendix.
10.9 Calculation of sales weighted
average annual energy consumption for
mobile home furnaces. To reflect the
distribution of mobile homes to geographical
regions with average HLHMHF values different
from 2,080, adjust the annual fossil fuel and
auxiliary electrical energy consumption
values for mobile home furnaces using the
following adjustment calculations.
10.9.1 For mobile home furnaces, the
sales weighted average annual fossil fuel
energy consumption is expressed in Btu per
year and defined as:
EF,MHF = (EF ¥ 8,760 QP) HLHMHF/2,080 +
8,760 QP
Where:
EF = as defined in section 10.8.2 of this
appendix
8,760 = as defined in section 10.4.1.1 of this
appendix
QP = as defined in section 10.2 of this
appendix
HLHMHF = 1880, sales weighted average
heating load hours for mobile home
furnaces
2,080 = as defined in section 10.4.1 of this
appendix
10.9.2 For mobile home furnaces, the
sales-weighted-average annual auxiliary
electrical energy consumption is expressed in
kilowatt-hours and defined as:
EAE,MHF = EAE HLHMHF/2,080
Where:
EAE = as defined in section 10.8.3 of this
appendix
HLHMHF = as defined in section 10.9.1 of this
appendix
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
2655
2,080 = as defined in section 10.4.1 of this
appendix
10.10 Direct determination of off-cycle
losses for furnaces and boilers equipped with
thermal stack dampers. [Reserved.]
10.11 Average annual electrical standby
mode and off mode energy consumption.
Calculate the annual electrical standby mode
and off mode energy consumption (ESO) in
kilowatt-hours, defined as:
ESO = (PW,SB (4160 ¥ BOH) + 4600 PW,OFF)
K
Where:
PW,SB = furnace or boiler standby mode
power, in watts, as measured in section
8.11.1 of this appendix
4,160 = average heating season hours per year
BOH = total burner operating hours as
calculated in section 10.4 of this
appendix for gas or oil-fueled furnaces or
boilers. Where for gas or oil-fueled
furnaces and boilers equipped with
single-stage controls, BOH = BOHSS; for
gas or oil-fueled furnaces and boilers
equipped with two-stage controls, BOH =
(BOHR + BOHH); and for gas or oil-fueled
furnaces and boilers equipped with stepmodulating controls, BOH = (BOHR +
BOHM). For electric furnaces and boilers,
BOH = 100(2080)(0.77)DHR/(Ein
3.412(AFUE))
4,600 = as defined in section 11.4.12 of
ASHRAE 103–1993 (incorporated by
reference, see § 430.3)
PW,OFF = furnace or boiler off mode power,
in watts, as measured in section 8.11.2
of this appendix
K = 0.001 kWh/Wh, conversion factor from
watt-hours to kilowatt-hours
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.4.1 of this
appendix
0.77 = as defined in section 10.4.1 of this
appendix
DHR = as defined in section 10.4.1 of this
appendix
Ein = steady-state electric rated power, in
kilowatts, from section 9.3 of ASHRAE
103–1993
3.412 = as defined in section 10.4.3 of this
appendix
AFUE = as defined in section 11.1 of
ASHRAE 103–1993 in percent
E:\FR\FM\15JAR4.SGM
15JAR4
2656
Federal Register / Vol. 81, No. 10 / Friday, January 15, 2016 / Rules and Regulations
[FR Doc. 2016–00040 Filed 1–14–16; 8:45 am]
VerDate Sep<11>2014
21:45 Jan 14, 2016
Jkt 238001
PO 00000
Frm 00030
Fmt 4701
Sfmt 9990
E:\FR\FM\15JAR4.SGM
15JAR4
ER15JA16.018
tkelley on DSK3SPTVN1PROD with RULES4
BILLING CODE 6450–01–P
Agencies
[Federal Register Volume 81, Number 10 (Friday, January 15, 2016)]
[Rules and Regulations]
[Pages 2627-2656]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2016-00040]
[[Page 2627]]
Vol. 81
Friday,
No. 10
January 15, 2016
Part V
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 430
Energy Conservation Program for Consumer Products: Test Procedures for
Residential Furnaces and Boilers; Final Rule
Federal Register / Vol. 81 , No. 10 / Friday, January 15, 2016 /
Rules and Regulations
[[Page 2628]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[Docket No. EERE-2012-BT-TP-0024]
RIN 1904-AC79
Energy Conservation Program for Consumer Products: Test
Procedures for Residential Furnaces and Boilers
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (DOE) amends its test procedure
for residential furnaces and boilers established under the Energy
Policy and Conservation Act. This rulemaking will fulfill DOE's
obligation to review its test procedures for covered products at least
once every seven years. The revisions include: Clarifying the
components included in the burner electrical power input term (PE);
adopting a method for determining whether a minimum draft factor can be
applied, and how the conditions are to be verified; allowing optional
measurement of condensate collection during establishment of steady
state; updating references to the applicable installation and operating
manual and providing clarifications when the installation and operation
(I&O) manual does not specify test setup; clarifying the testing of
units intended to be installed without a return duct; adopting a
provision clarifying the testing of multi-position units; revising the
required reporting precision for annual fuel utilization efficiency
(AFUE); and adopting a verification method for determining whether a
boiler incorporates an automatic means for adjusting water temperature
and whether this design requirement functions as required.
DATES: The effective date of this rule is February 16, 2016. The final
rule changes will be mandatory for representations made on or after
July 13, 2016. The incorporation by reference of certain material
listed in this rule is approved by the Director of the Federal Register
as of February 16, 2016.
ADDRESSES: The docket, which includes Federal Register notices, public
meeting attendee lists and transcripts, comments, and other supporting
documents/materials, is available for review at www.regulations.gov.
All documents in the docket are listed in the www.regulations.gov
index. However, not all documents listed in the index may be publicly
available, such as information that is exempt from public disclosure.
A link to the docket Web page can be found at: https://www.regulations.gov/#!docketDetail;D=EERE-2012-BT-TP-0024. This Web
page contains a link to the docket for this final rule on the
www.regulations.gov site. The www.regulations.gov Web page contains
simple instructions on how to access all documents, including public
comments, in the docket.
For further information on how to review the docket, contact Ms.
Brenda Edwards at (202) 586-2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Ms. Ashley Armstrong, U.S. Department
of Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Office, EE-5B, 1000 Independence Avenue SW., Washington,
DC 20585-0121. Telephone: (202) 586-6590. Email:
Ashley.Armstrong@ee.doe.gov.
Mr. Pete Cochran, U.S. Department of Energy, Office of the General
Counsel, GC-33, 1000 Independence Avenue SW., Washington, DC 20585-
0121. Telephone: (202) 586-9496. Email: peter.cochran@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final rule incorporates by reference
into part 430 the following industry standard:
ASTM D2156-09 (Reapproved 2013) (``ASTM D2156R13''), Standard Test
Method for Smoke Density in Flue Gases from Burning Distillate Fuels,
approved October 1, 2013.
Copies of ASTM D2156R13 can be obtained from ASTM. American Society
of Testing and Materials, ASTM Headquarters, 100 Barr Harbor Drive,
P.O. Box C700, West Conshohocken, PA 19428-2959, (877) 909-2786 or
(610) 832-9585, or by going to https://www.astm.org. See section IV.M
for further discussion of this standard.
Table of Contents
I. Authority and Background
II. Summary of the Final Rule
III. Discussion
A. Products Within Scope of the Final Rule
B. General Comments
1. Statutory Deadline
2. Simultaneous Changes in Test Procedure and Standards
3. Lack of Data Availability
C. Proposed Incorporation by Reference of ASHRAE Standard 103-
2007
D. Test Procedure Amendments
1. Electrical Power of Components
2. Smoke Stick Test for Determining Use of Minimum Default Off-
Cycle and Power Burner Draft Factors
3. Condensate Collection During the Establishment of Steady
State Conditions
4. Installation and Operation Manual Reference
5. Duct Work for Units That Are Installed Without a Return Duct
6. Testing Requirements for Multi-Position Configurations
7. AFUE Reporting Precision
8. Definitions and Other Changes
E. Other Test Procedure Considerations
1. Room Ambient Air Temperature and Humidity Ranges
2. Full-Fuel-Cycle Energy Metrics
3. Oversize Factor Value
4. Alternative Methods for Furnace/Boiler Efficiency
Determination
5. Test Method for Combination Appliance
F. Test Burden
G. Measured Energy Use
H. Certification and Enforcement
1. Verification Test for Automatic Means for Adjusting the Water
Temperature in Boilers
2. Compliance Dates for the Amended Test Procedure
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Description of Materials Incorporated by Reference
V. Approval of the Office of the Secretary
I. Authority and Background
Title III, Part B \1\ of the Energy Policy and Conservation Act of
1975 (``EPCA'' or ``the Act''), Public Law 94-163 (42 U.S.C. 6291-6309,
as codified) sets forth a variety of provisions designed to improve
energy efficiency and established the Energy Conservation Program for
Consumer Products Other Than Automobiles.\2\ These products include
residential furnaces and boilers, the subject of this notice.\3\
---------------------------------------------------------------------------
\1\ For editorial reasons, Part B was codified as Part A in the
U.S. Code.
\2\ All references to EPCA in this document refer to the statute
as amended through the Energy Efficiency Improvement Act of 2015,
Public Law 114-11 (Apr. 30, 2015).
\3\ Under 42 U.S.C. 6292(a)(5), the statute establishes
``furnaces'' as covered products, and 42 U.S.C. 6291(23) defines
furnaces as inclusive of boilers.
---------------------------------------------------------------------------
Under EPCA, DOE's energy conservation program generally consists of
four parts: (1) Testing; (2) labeling; (3) Federal energy conservation
standards; and (4) certification and enforcement procedures. The
testing requirements consist of test procedures that manufacturers of
covered products must
[[Page 2629]]
use as the basis for: (1) Certifying to DOE that their products comply
with the applicable energy conservation standards adopted pursuant to
EPCA, and (2) making other representations about the efficiency of
those products. (42 U.S.C. 6293(c); 42 U.S.C. 6295(s)) Similarly, DOE
must use these test procedures to determine whether the products comply
with any relevant standards promulgated under EPCA. (42 U.S.C. 6295(s))
EPCA sets forth the criteria and procedures that DOE must follow
when prescribing or amending test procedures for covered products. EPCA
provides, in relevant part, that any test procedures prescribed or
amended under this section shall be reasonably designed to produce test
results which measure energy efficiency, energy use, or estimated
annual operating cost of a covered product during a representative
average use cycle or period of use, and shall not be unduly burdensome
to conduct. (42 U.S.C. 6293(b)(3))
In addition, if DOE determines that a test procedure amendment is
warranted, it must publish proposed test procedures and offer the
public an opportunity to present oral and written comments on them. (42
U.S.C. 6293(b)(2)) Finally, in any rulemaking to amend a test
procedure, DOE must determine to what extent, if any, the proposed test
procedure would alter the product's measured energy efficiency as
determined under the existing test procedure. (42 U.S.C. 6293(e)(1))
EISA 2007 amended EPCA to require that, at least once every 7
years, DOE must review test procedures for all covered products and
either amend the test procedures (if the Secretary determines that
amended test procedures would more accurately or fully comply with the
requirements of 42 U.S.C. 6293(b)(3)) or publish a notice in the
Federal Register of any determination not to amend a test procedure.
(42 U.S.C. 6293(b)(1)(A)) Under this requirement, DOE must review the
test procedure for residential furnaces and boilers not later than
December 19, 2014 (i.e., 7 years after the publication of EISA 2007 on
December 19, 2007).
DOE's current energy conservation standards for residential
furnaces and boilers are expressed as minimum annual fuel utilization
efficiency (AFUE). AFUE is an annualized fuel efficiency metric that
accounts for fuel consumption in active, standby, and off modes. The
following discussion provides a brief history of the rulemakings
underlying the existing test procedure for residential furnaces and
boilers.
The existing DOE test procedure for determining the AFUE of
residential furnaces and boilers is located at 10 CFR part 430, subpart
B, appendix N, Uniform Test Method for Measuring the Energy Consumption
of Furnaces and Boilers. The existing DOE test procedure for
residential furnaces and boilers was established by a final rule
published in the Federal Register on May 12, 1997, and it incorporates
by reference the American National Standards Institute/American Society
of Heating, Refrigerating, and Air-Conditioning Engineers (ANSI/ASHRAE)
Standard 103-1993, Method of Testing for Annual Fuel Utilization
Efficiency of Residential Central Furnaces and Boilers (ASHRAE 103-
1993). 62 FR 26140, 26157 (incorporated by reference at 10 CFR
430.3(f)(10)). On October 14, 1997, DOE published an interim final rule
in the Federal Register to revise a provision concerning the insulation
of the flue collector box in order to ensure the updated test procedure
would not affect the measured AFUE of existing furnaces and boilers. 62
FR 53508. This interim final rule was adopted without change in a final
rule published in the Federal Register on February 24, 1998. 63 FR
9390.
On October 20, 2010, DOE amended its test procedure for furnaces
and boilers to establish a method for measuring the electrical energy
use in standby mode and off mode for gas- fired and oil-fired furnaces
and boilers, as required by EISA 2007. 75 FR 64621. These test
procedure amendments incorporated by reference, and were based
primarily on, provisions of the International Electrotechnical
Commission (IEC) Standard 62301 (First Edition), Household electrical
appliances--Measurement of standby power. On December 31, 2012, DOE
published a final rule (December 2012 final rule) in the Federal
Register that updated the incorporation by reference of the standby
mode and off mode test procedure provisions to refer to the latest
edition of IEC Standard 62301 (Second Edition). 77 FR 76831. On July
10, 2013, DOE published a final rule (July 2013 final rule) in the
Federal Register that amended its test procedure for residential
furnaces and boilers by adopting needed equations that allow
manufacturers the option to omit the heat-up and cool-down tests and
still generate a valid AFUE measurement. 78 FR 41265. On August 30,
2013, DOE published a correction to the July 2013 final rule that
corrected errors in the redesignations of affected subsections within
section 10 of appendix N. 78 FR 53625.
On January 4, 2013, DOE initiated this rulemaking to examine all
aspects of the DOE test procedure by publishing a request for
information (RFI) (January 2013 RFI) in the Federal Register. 78 FR
675. On March 11, 2015, DOE published a notice of proposed rulemaking
(NOPR) (March 2015 NOPR) in the Federal Register to amend the test
procedure for residential furnaces and boilers. 80 FR 12876. In the
March 2015 NOPR, DOE proposed to amend the residential furnaces and
boilers test procedure by incorporating by reference ANSI/ASHRAE
Standard 103-2007 (ASHRAE 103-2007) in place of ASHRAE 103-1993, which
currently is referenced in the existing test procedure. In addition,
the March 2015 NOPR proposed to adopt modifications that would
establish revised test procedures for two-stage and modulating
products, as well as for boilers with long post-purge times that would
not otherwise be included in the incorporation by reference of ASHRAE
103-2007.
DOE also proposed to amend the test procedure to: (1) Allow the
measurement of condensate during the establishment of steady-state
rather than require an additional 30 minutes of testing after steady-
state conditions are established; (2) revise annual electricity
consumption equations to account for additional electrical components;
(3) revise test procedure references to ``manufacturer
recommendations'' or ``manufacturer's instructions'' that do not
explicitly identify the source of the recommendations or instructions;
(4) include a test protocol for determining the functionality of the
automatic means for adjusting water temperature; (5) include a test
method to indicate the absence or presence of air flow to determine
whether the minimum default draft factor may be used; (6) revise the
required reporting precision for AFUE; (7) specify testing requirements
for units that are installed without a return duct; and (8) specify
testing requirements for units with multi-position configurations. 80
FR 12876.
II. Summary of the Final Rule
The final rule amends the existing DOE test procedure for
residential furnaces and boilers to improve the consistency and
accuracy of test results generated using the DOE test procedure and to
reduce test burden. In particular, these modifications include: (1)
Clarifying the definition of the electrical power term PE; (2) adopting
a smoke stick test for determining use of minimum default draft
factors; (3) allowing for the measurement of condensate under steady-
state
[[Page 2630]]
conditions; (4) referencing the manufacturer's installation and
operation (I&O) manual and providing clarifications when the I&O manual
does not specify test setup; (5) specifying ductwork requirements for
units that are installed without a return duct; (6) specifying testing
requirements for units with multi-position configurations; and (7)
revising the AFUE reporting precision. DOE has also revised the
definitions of several terms in the test procedure and added an
enforcement provision to provide a method of test for DOE to determine
compliance with the automatic means design requirement mandated by EISA
2007.
DOE has withdrawn or modified all test procedure amendment
proposals in the March 2015 NOPR for which stakeholders expressed
concern regarding the effect of the proposed amendments on the measured
energy efficiency of residential furnaces and boilers when compared to
the current test procedure. In particular, as discussed in section
III.C, DOE has withdrawn its proposal to incorporate by reference
ASHRAE 103-2007.
III. Discussion
The following sections discuss the products within the scope of
this rulemaking, the test procedure amendments, other test procedure
considerations, test burden, measured energy use, and changes to
certification and enforcement provisions.
In response to the March 2015 NOPR, the following twelve interested
parties submitted written comments: The American Gas Association (AGA);
the Air-Conditioning, Heating and Refrigeration Institute (AHRI);
Burnham Holdings, Inc. (Burnham); Carrier Corporation (Carrier); John
Cockerill (Cockerill); Goodman Global, Inc. (Goodman); Lennox
Industries Inc. (Lennox); Lochinvar, LLC (Lochinvar); Rheem
Manufacturing Company (Rheem); Ingersoll Rand Residential Solutions
(Ingersoll Rand); Laclede Group; and Weil-McLain. Interested parties
provided comments on a range of issues, including those DOE identified
in the March 2015 NOPR, as well as issues related to the proposed test
procedure changes. The issues on which DOE received comments, as well
as DOE's responses to those comments and the resulting changes to the
test procedure proposals presented in the NOPR, are discussed in the
subsequent sections. A parenthetical reference at the end of a comment
quotation or paraphrase provides the location of the item in the public
record.\4\
---------------------------------------------------------------------------
\4\ The parenthetical reference provides a reference for
information located in the docket of DOE's rulemaking to amend the
test procedures for residential furnaces and boilers. (Docket No.
EERE-2012-BT-TP-0024, which is maintained at https://www.regulations.gov/#!docketDetail;D=EERE-2012-BT-TP-0024). The
references are arranged as follows: (commenter name, comment docket
ID number, page of that document).
---------------------------------------------------------------------------
A. Products Within Scope of the Final Rule
The test procedure amendments apply to products that meet the
definitions for residential furnaces and boilers (see DOE's regulations
at 10 CFR 430.2). A ``furnace'' is defined as a product that: (1)
Utilizes only single-phase electric current, or single-phase electric
current or direct current (DC) in conjunction with natural gas,
propane, or home heating oil; (2) is designed to be the principal
heating source for the living space of a residence; (3) is not
contained within the same cabinet with a central air conditioner whose
rated cooling capacity is above 65,000 Btu per hour; (4) is an electric
central furnace, electric boiler, forced-air central furnace, gravity
central furnace, or low pressure steam or hot water boiler; and (5) has
a heat input rate of less than 300,000 Btu per hour for electric
boilers and low pressure steam or hot water boilers and less than
225,000 Btu per hour for forced-air central furnaces, gravity central
furnaces, and electric central furnaces.\5\
---------------------------------------------------------------------------
\5\ The definition of ``furnace'' currently in the CFR at 10 CFR
430.2 mistakenly repeats the terms ``gravity central furnaces, and
electric central furnaces'' at the end of the definition. In this
final rule, DOE is correcting this error to remove the duplicative
language.
---------------------------------------------------------------------------
The individual products within the scope of this test procedure and
the definition of each (see DOE's regulations at 10 CFR 430.2) are
listed below:
(1) Electric boiler means an electrically powered furnace designed
to supply low pressure steam or hot water for space heating
application. A low pressure steam boiler operates at or below 15 pounds
per square inch gauge (psig) steam pressure; a hot water boiler
operates at or below 160 psig water pressure and 250 [deg]F water
temperature.
(2) Electric central furnace means a furnace that is designed to
supply heat through a system of ducts with air as the heating medium,
in which heat generated by one or more electric resistance heating
elements is circulated by means of a fan or blower.
(3) Forced-air central furnace means a furnace that burns gas or
oil and is designed to supply heat through a system of ducts with air
as the heating medium. The heat generated by combustion of gas or oil
is transferred to the air within a casing by conduction through heat
exchange surfaces and is circulated through the duct system by means of
a fan or blower.
(4) Gravity central furnace means a gas-fueled furnace which
depends primarily on natural convection for circulation of heated air
and which is designed to be used in conjunction with a system of ducts.
(5) Low pressure steam or hot water boiler is an electric, gas, or
oil-burning furnace designed to supply low pressure steam or hot water
for space heating applications. A low pressure steam boiler operates at
or below 15 psig steam pressure; a hot water boiler operates at or
below 160 psig water pressure and 250 [deg]F water temperature.
(6) Mobile home furnace means a direct vent furnace that is
designed for use only in mobile homes.
(7) Outdoor furnace or boiler is a furnace or boiler normally
intended for installation out-of-doors or in an unheated space (such as
an attic or a crawl space).
(8) Weatherized warm air furnace or boiler means a furnace or
boiler designed for installation outdoors, approved for resistance to
wind, rain, and snow, and supplied with its own venting system.
B. General Comments
Stakeholders submitted general comments regarding the test
procedure and parallel energy conservation standards rulemaking
timeline and the availability of data related to this proceeding. DOE
discusses and responds to these comments in the following subsections.
1. Statutory Deadline
As noted in section I, EISA 2007 requires that DOE must review test
procedures for all covered products and amend the test procedures or
publish a notice in the Federal Register of any determination not to
amend test procedures at least once every seven years. (42 U.S.C.
6293(b)(1)(A)).
AHRI asserted that the start date for the obligation to review
efficiency test procedures at least once every seven years has been
reset by the July 2013 Final Rule. And, therefore, by its estimation,
DOE has approximately five more years to review and amend, as needed,
the test procedures for residential furnaces and boilers. AHRI added
that this would be ample time to manage DOE's rulemaking activities
such that proposed revisions to efficiency standards and test
procedures are not considered concurrently. (AHRI, No. 36 at p. 2)
[[Page 2631]]
DOE notes that the July 2013 Final Rule was limited in scope and
only intended to remedy a specific concern articulated by stakeholders.
Specifically, the July 2013 Final Rule adopted needed equations to
allow manufacturers the option to omit the heat up and cool down tests
and still generate a valid AFUE measurement for certain condensing
products. 78 FR 41265, 41266. DOE considers the seven year look back
provision to include a comprehensive review of the entire test
procedure. (42 U.S.C. 6293(b)(1)(A)) DOE did not conduct a
comprehensive review for the July 2013 Final Rule. Furthermore, DOE
stated in the July 2013 Final Rule that it was initiating a separate
rulemaking that was broader in scope to examine all aspects of the DOE
test procedure for residential furnaces and boilers. 78 FR 41265,
41266. Therefore, DOE maintains that the July 2013 final rule did not
meet the requirements outlined in 42 U.S.C. 6293(b)(1)(A). In contrast,
DOE has conducted a comprehensive review as part of the current
rulemaking, which satisfies the requirements of 42 U.S.C.
6293(b)(1)(A).
2. Simultaneous Changes in Test Procedure and Standards
Several stakeholders cited legal and practical concerns regarding
the timing of proposed revisions to the test procedures and standards
for residential furnaces and boilers. Stakeholders requested that DOE
delay any further work on the rulemakings to amend efficiency standards
for these products until after the finalization of the test procedure.
(AHRI, No. 36 at p. 1; Weil-McLain, No. 31 at p. 2; Ingersoll Rand, No.
37 at p. 5)
AHRI stated that it believes the non-final status of the test
procedure inhibits stakeholders' fair evaluation of the standard. AHRI
stressed the importance of having a known efficiency test procedure.
AHRI noted that when a test procedure is in flux, manufacturers must
spend resources collecting potentially unusable data which undermines
their ability to provide input on the proposed efficiency standards.
Similarly, AHRI added that when a test procedure is not finalized, a
manufacturer has no way of determining whether the test procedure will
affect its ability to comply with a proposed revised standard. AHRI
noted that DOE is required to give stakeholders the opportunity to
provide meaningful comments and asserted that the joint proposal of
test procedures and standards diminishes that opportunity (see 42
U.S.C. 6295(p)(2), 6306(a)). (AHRI, No. 36 at p. 1)
In response to AHRI, DOE does not believe that the timing of the
test procedure and standards rulemakings has negatively impacted
stakeholders' ability to provide meaningful comment on this test
procedure rulemaking. DOE allowed four months for public comment on the
test procedure NOPR. Additionally, DOE's original proposal included an
update to the latest industry standard (i.e., ASHARE 103-2007), which
was developed by a consensus-based ASHRAE process, and was released in
2007. DOE believes that industry was involved in developing that
standard and had experience with the changes in the 2007 version of
ASHRAE Standard 103. Lastly, stakeholders provided detailed, insightful
comments on all aspects of the proposal, including submitting select
test data in response to DOE's proposal, which shows that industry was
able to carefully consider the proposed method and how it compared to
the current Federal method of test. In addition, DOE has taken AHRI's
concerns regarding the potential impact of test procedure changes on
measured energy use into account in its determinations of which test
procedure proposals to finalize in this rulemaking.
AHRI and Goodman stated that by publishing the March 2015 NOPR
within weeks of the proposed efficiency standard, DOE has failed to
abide by the procedures located at 10 CFR part 430, subpart C, appendix
A (7)(b). (AHRI, No. 36 at p. 2; Goodman, No. 33 at p. 2) AHRI stated
that the Administrative Procedure Act (APA) requires agencies to abide
by their policies and procedures, especially where those rules have a
substantive effect. AHRI asserted that the non-final test procedure has
the substantive effect of increasing costs to stakeholders and
diminishing their ability to comment on the efficiency standards.
(AHRI, No. 36 at p. 2; Weil-McLain, No. 31 at p. 7)
In response to the comments from AHRI and Goodman asserting that
DOE has failed to abide by its procedures at 10 CFR 430, subpart C,
appendix A (7)(b), DOE notes that appendix A establishes procedures,
interpretations, and policies to guide DOE in the consideration and
promulgation of new or revised appliance efficiency standards under
EPCA. (See section 1 of 10 CFR part 430, subpart C, appendix A) Those
procedures are a general guide to the steps DOE typically follows in
promulgating energy conservation standards. The guidance recognizes
that DOE can and will, on occasion, deviate from the typical process.
Accordingly, DOE has concluded that there is no basis to either: (1)
Delay the final rules adopting standards for residential furnaces and
boilers; or (2) suspend the test procedure rulemaking until the
standards rulemaking has been completed.
Ingersoll Rand and Goodman stated their concern that two-stage,
condensing furnaces that would meet the March 12, 2015 furnace proposed
rule of 92-percent AFUE under the current test procedure would not meet
the 92-percent AFUE standard under the proposed DOE test procedure.
Ingersoll Rand noted that the two test procedures were assumed to be
identical in the March 12, 2015 residential furnace standard NOPR
technical support document. (Ingersoll Rand, No. 37 at p. 2; Goodman,
No. 33 at p. 1) Similarly, Weil-McLain suggested that the uncertainty
caused by the simultaneous test procedure rulemaking amplifies venting
issues present in the residential boiler standards NOPR. (Weil-McLain,
No. 31 at p. 3)
In response to Ingersoll Rand and Goodman, as discussed in section
III.C, DOE declines to adopt the latest industry standard of ASHRAE
103-2007, which is the only amendment proposed in the March 2015 NOPR
that manufacturers claimed could alter the AFUE for two-stage and
modulating condensing products. In response to Weil-McLain, DOE notes
that none of the proposed test procedure provisions that had the
potential to result in a change in measured AFUE are adopted in this
test procedure final rule, as discussed in section III.G.
3. Lack of Data Availability
In response the March 2015 NOPR, interested parties submitted
comments regarding lack of data availability. For example, the March
2015 NOPR included several references to a testing report. 80 FR 12876,
12878. Burnham stated that in spite of requests from commenters, the
testing report was not available in the public docket as of July 8,
2015. Burnham added that the lack of access to the testing report has
made it impossible to properly review the impact of ambient conditions
on AFUE during the public comment period. Burnham requested that the
comment period be extended to allow comment on this document which
should be disclosed immediately. (Burnham, No. 35 at p. 7)
DOE made the test results available during the test procedure
public meeting.\6\ The slide deck presented at
[[Page 2632]]
the public meeting was posted to the docket on March 26, 2015, along
with the transcript of the public meeting. (Public Meeting Presentation
Slides, No. 21) Therefore, stakeholders were presented with an
opportunity to review and discuss the data with the Department at the
public meeting and to review the results during the comment period,
which was open until July 10, 2015.
---------------------------------------------------------------------------
\6\ Test results included in the slide deck for the public
meeting include those for proposed changes related to AFUE
determination for two-stage/modulating products, measurement of
condensate under steady state conditions, electric consumption of
components, and verification test for automatic means for adjusting
the water temperature in boilers. DOE did not provide test results
for ambient conditions or other testing for which no changes were
proposed in the NOPR.
---------------------------------------------------------------------------
C. Proposed Incorporation by Reference of ASHRAE Standard 103-2007
In the March 2015 NOPR, DOE proposed amendments to reduce
variability, eliminate ambiguity, and address discrepancies between the
test procedure and actual field conditions, and DOE requested comment
on its proposals. 80 FR 12876, 12902. One of these proposals was to
update its incorporation by reference of the industry test standard
ASHRAE 103-1993 to ASHRAE 103-2007.
DOE received several comments in response to its proposal to update
the incorporation by reference in the DOE test procedure to ASHRAE 103-
2007. Lochinvar and AGA responded to the NOPR in favor of adopting
ASHRAE 103-2007 provided that DOE make adequate allowances for the
resulting test burden and the impact that the change would have on
existing efficiency claims. (Lochinvar, No. 29 at p. 1; AGA, No. 27 at
p. 4) Similarly, Burnham stated that they are not opposed to the update
provided test burden is reduced. (Burnham, No. 35 at p. 3)
Ingersoll Rand and Rheem stated their support only for certain
provisions of ASHRAE 103-2007. Specifically, Ingersoll Rand supported
requiring only reduced fire testing (and not high-fire testing) when
the calculated balance point temperature is less than or equal to five
degrees. (Ingersoll Rand, No. 37 at p. 4) Rheem stated their support
for the elimination of table 8 and the average design heating
requirements in ASHRAE 103-1993. (Rheem, No. 30 at p. 2)
Lennox and Weil-McLain suggested DOE not update to ASHRAE 103-2007
at this time. (Lennox, No. 32 at p. 2; Weil-McLain, No. 31 at p. 7)
AHRI and Weil-McLain suggested that DOE wait to modify the test
procedure until ASHRAE 103-2016 is issued. (AHRI, No. 36 at p. 8; Weil-
McLain, No. 31 at p. 7) Carrier suggested that DOE not update to ASHRAE
103-2007, but change the AFUE metric for forced-air furnaces to be
based on the steady-state operation, as discussed in section III.E.4.
(Carrier, No. 34 at p. 2)
Several commenters suggested that that the updating to ASHRAE 103-
2007 would result in more significant changes to AFUE ratings than
suggested by DOE in the March 2015 NOPR. (Burnham, No. 35 at p. 3;
Lennox, No. 32 at p. 2; AGA, No. 27 at p. 4; AHRI, No. 36 at p. 4;
Ingersoll Rand, No. 37 at p. 2) Of these commenters, only AHRI provided
test data, which indicated small changes in AFUE as a result of changes
to the cyclical condensate test for modulating condensing boilers.
(AHRI, No. 36 at p. 17)
Burnham and Ingersoll Rand suggested that the impact to AFUE
resulting from the changes in cycle times is still uncertain.
Therefore, it is not possible to conclude that the effect of this
proposed change to the procedure is insignificant. (Burnham, No. 35 at
p. 3; Ingersoll Rand, No. 37 at p. 2) Ingersoll Rand noted that as a
result of adopting ASHRAE 103-2007, two-stage and modulating non-
condensing furnaces will have a higher AFUE rating, and condensing
furnaces will have lower AFUE ratings. Ingersoll Rand noted that the
changes in AFUE are higher than the uncertainty of the test procedure
reported by DOE and therefore this change to the test procedure cannot
be considered de minimis. Ingersoll Rand also noted that the test
results are limited and have high variability. Ingersoll Rand suggested
that the change not be adopted until the variability is better
understood. (Ingersoll Rand, No. 37 at p. 2) AGA suggested that the
Department substantially increase the amount of testing using the
modified test procedure to ensure that the resulting efficiency rating
for both furnaces and boilers are accurate and repeatable. (AGA, No. 27
at p. 4)
Similarly, Ingersoll Rand suggested the calculation to account for
post purge times longer than three minutes not be adopted without test
data indicating the adjustment to AFUE that would result from this
update. Ingersoll Rand stated that without test data they cannot
determine if the new readings would be representative of a unit's
performance. (Ingersoll Rand, No. 37 at p. 4)
In response to the March 2015 NOPR, Ingersoll Rand requested that
DOE not adopt the proposed changes to the calculation of annual
auxiliary electrical energy consumption (EAE) caused by the
update to ASHRAE 103-2007. Ingersoll Rand stated that the calculation
of EAE proposed in the March 2015 NOPR changes the value of
EAE substantially from -8.5 percent to +13.5 percent.
Ingersoll Rand noted that this change, along with the proposal to
include the electrical consumption of additional components is
significant enough that all current furnaces would have to be retested
and recertified. Ingersoll Rand requested that DOE reconsider its
finding that the amended test procedure would have a ``de minimis
impact on the products' measured energy use'' and instead find that the
proposed test procedure amendment has a significant impact on measured
electricity consumption. (Ingersoll Rand, No. 37 at p. 5)
Several commenters stated that the changes to AFUE caused by
updating to ASHRAE 103-2007 would lead to additional testing burden.
(Burnham, No. 35 at p. 3; Lennox, No. 32 at p. 2; AHRI, No. 36 at p. 4)
AHRI stated that the change to use calculated values for tON
and tOFF will at a minimum require retesting for any step-
modulating models at the reduced input rate and for many two stage
models at both the maximum and reduced input rates. (AHRI, No. 36 at p.
4)
Given this expected test burden, Lochinvar argued that if DOE is to
adopt ASHRAE 103-2007, DOE must declare in writing that products
certified according to ASHRAE 103-1993 that were on the market prior to
updating the test procedure are not required to be retested and
recertified unless the design is changed in a way that affects
efficiency. Lochinvar suggested that future audit tests of pre-existing
products could still be conducted according to ASHRAE 103-2007 but that
manufacturers should not be required to do new tests on existing models
for certification reporting to DOE's Compliance Certification
Management System (CCMS). (Lochinvar, No. 29 at p. 1)
Burnham also commented that their efforts to explore the impact of
adoption of ASHRAE 103-2007 have been hampered by the lack of generally
available, National Institute of Standards and Technology (NIST)
validated software tools for calculating AFUE (and intermediate values)
based on ASHRAE 103-2007. Burnham argued that the lack of software is a
significant departure from past practice during comparable rulemakings.
Burnham also asserted that this constituted a lack of transparency that
would violate basic administrative law precepts and would be arbitrary
and capricious. (Burnham, No. 35 at p. 3)
After considering these comments, DOE agrees that further
evaluation is
[[Page 2633]]
needed to determine the impact of adopting ASHRAE 103-2007 on the AFUE
ratings of residential furnace and boiler models currently distributed
in commerce. As a result, DOE does not adopt ASHRAE 103-2007 in this
final rule. Instead, DOE retains the reference in the existing test
procedure to ASHRAE 103-1993, both related to AFUE and EAE.
However, DOE believes ASHRAE 103-2007 better accounts for the operation
of two-stage and modulating equipment and may further evaluate adoption
of ASHRAE 103-2007, or a successor standard, in future rulemakings. In
addition to retaining the reference to ASHRAE 103-1993, DOE revises the
list of excluded ASHRAE 103-1993 sections to reflect test procedure
amendments (as discussed in section III.D) and to more accurately
identify the excluded sections.
DOE does not agree with Burnham's assertion that the lack of an
automated software program implementing the equations presented in
DOE's proposal hampered stakeholder's ability to comment on the
practicability and the impact of the adoption of ASHRAE 103-2007. DOE
does not endorse specific calculations tools commonly developed by
industry or third-party test laboratories that automate the equations
provided in DOE's regulations. Furthermore, DOE does not need to
provide software for interested parties to be able to perform the
calculations in proposed test procedure amendments and believes the
simplified equations provided in the proposed rule can be easily
implemented through a desktop-software calculation tool such as a
commonly available spreadsheet application. Lastly, DOE disagrees with
Burnham's assertion that the proposed rule was not sufficiently clear
to provide an opportunity for interested parties to understand the
proposal and provide meaningful comment because each of the equations
utilized was presented in the regulatory text within the proposed rule
in a step-by-step fashion.
D. Test Procedure Amendments
In response to the March 2015 NOPR, DOE received input on a variety
of test procedure issues beyond incorporation of ASHRAE 103-2007,
including: (1) Electrical power of additional components; (2) smoke
stick test for determining use of minimum default draft factors; (3)
measurement of condensate under steady-state conditions; (4) I&O manual
reference and proposed clarifications when the I&O manual does not
specify test setup; (5) specifying ductwork requirements for units that
are installed without a return duct; (6) specifying testing
requirements for units with multi-position configurations; (7) AFUE
reporting precision; (8) room ambient temperature and humidity ranges;
(9) full-fuel-cycle (FFC) energy metrics in the AFUE test; (10)
oversize factor values; (11) alternative methods for furnace and boiler
efficiency determination; and (12) test method for combination
appliances. DOE amends the test procedure for residential furnaces and
boilers regarding issues (1)-(7), which are addressed in further detail
below. Issues (8)-(12), for which DOE does not amend the test procedure
in this final rule, are discussed in section III.E. DOE also received
comments on the verification test for automatic means for adjusting
water temperature, which are discussed in section III.H.1.
1. Electrical Power of Components
In the January 2013 RFI and March 2015 NOPR, DOE noted that the
specific method of electrical measurement prescribed in the existing
DOE test procedure does not explicitly capture the electrical power
associated with all auxiliary components. The method identifies PE as
the electrical power used to operate the burner but only explicitly
mentions measurements of the power supplied to the power burner motor,
the ignition device, and the circulation water pump, but does not
explicitly identify other devices that use power during the active
mode, such as the gas valve, safety and operating controls, and a
secondary pump for boilers (i.e., boiler pump) used to maintain a
minimum flow rate through the boiler heat exchanger, which is most
typically associated with condensing boiler designs. 78 FR 675, 678; 80
FR 12876, 12882. In response to the January 2013 RFI, several
stakeholders, including Lennox, Rheem, and AHRI, stated that
manufacturers already measure all electrical power associated with the
additional components DOE listed in the January 2013 RFI. (Lennox, No.
6 at p. 3; Rheem, No. 12 at p. 10; AHRI, No. 13 at p. 6) Therefore, to
clarify which components are included in the power measurements, in the
March 2015 NOPR DOE proposed to add two new terms to the calculations
of the average annual auxiliary electrical energy consumption
(EAE) to capture the electrical power of the boiler pump
(BES) and the gas valve and controls (EO), if
present. DOE requested comment on these proposed amendments. 80 FR
12876, 12902.
AHRI expressed the view that the proposed changes over-complicate
this issue and that the proposed measurements will change the
measurement of EAE. AHRI stated that the typical gas burner
will not operate unless both the ignition system and gas control (e.g.,
automatic valves) are energized, which DOE acknowledges by including
the power of the energized electric ignition device in the definition
of PE. AHRI stated that the definition of PE should be clarified to
include all electrical energy consumption that relates to the functions
of igniting and operating the burner during the on cycle. (AHRI, No. 36
at p. 5)
Burnham supported DOE's proposal to measure all electrical
consumption associated with operating the burner (PE), which should
include the power consumption of any additional pump which is needed to
provide adequate flow through the boiler itself without also providing
significant flow through the heating system. (Burnham, No. 35 at p. 4)
Lochinvar stated that, in its experience, all electrical power
consumption measurements made during an AFUE test are made at the power
supply connection to the boiler and account for all auxiliary
components. (Lochinvar, No. 29 at p. 2) Lochinvar stated that while the
proposed change in the measurement of electrical consumption seems
unnecessary, it does not object to the revision.
After reviewing the comments on the March 2015 NOPR, DOE agrees
with the alternative approach suggested by AHRI to make explicit that
all of the electrical energy provided to the burner is captured in the
EAE measurement. Rather than including the additional terms
in the equation for EAE as proposed in the NOPR, DOE
clarifies the definition of PE to include all of the electrical power
that relates to burner operation, including energizing the ignition
system, controls, gas valve or oil control valve, and draft inducer, if
applicable.\7\ In addition, DOE agrees with Burnham that the electrical
power of the boiler pump, if present, should be accounted for in the
electrical measurements for boilers. Therefore, DOE further amends the
definition of PE for boilers to include the electrical power of the
boiler pump. In cases where the boiler pump power might not be captured
in the electrical power measurement because it is not operating at that
time, DOE will require the nameplate power to be added to PE, and if
nameplate power is not available, then manufacturers must include a
[[Page 2634]]
default value of 0.13 kW. This is the same as the current default value
for a circulating water pump, and DOE understands that the power of the
boiler pump is similar to that of a typical circulating water pump. DOE
revises sections 8.1, 8.2, and 10.4 of appendix N to subpart B of 10
CFR part 430 to reflect the clarification of the definition of PE.
---------------------------------------------------------------------------
\7\ The existing DOE test procedure states in section 10.4.1
that PE is the ``burner electrical power input at full load steady-
state operation, including electrical ignition device if energized,
as defined in 9.1.2.2 of ASHRAE 103-1993.''
---------------------------------------------------------------------------
The revised section 2 of appendix N defines the individual
components that are measured as part of PE:
Control means a device used to regulate the operation of a
piece of equipment and the supply of fuel, electricity, air, or water.
Draft inducer means a fan incorporated in the furnace or
boiler that either draws or forces air into the combustion chamber.
Gas valve means an automatic or semi-automatic device
consisting essentially of a valve and operator that controls the gas
supply to the burner(s) during normal operation of an appliance. The
operator may be actuated by application of gas pressure on a flexible
diaphragm, by electrical means, by mechanical means or by other means.
Oil control valve means an automatically or manually
operated device consisting of an oil valve for controlling the fuel
supply to a burner to regulate burner input.
Boiler pump means a pump installed on a boiler that
maintains adequate water flow through the boiler heat exchanger and
that is separate from the circulating water pump.
Although these definitions were not explicitly proposed in the
NOPR, they provide additional clarity about the definition of PE,
consistent with the proposal in the NOPR to improve the regulatory text
to reflect that PE includes the electrical power of all auxiliary
components.
Carrier noted that DOE in the past had held to the policy of not
making changes that will negatively impact present ratings. The
electrically-efficient furnaces ratio, known as ``e'', will increase
with the additional requirement, making some products lose their ENERGY
STAR[supreg] qualification. Carrier stated that including additional
electrical components along with the blower electrical consumption is
equivalent to changing the ENERGY STAR qualifying standard without
justifying the value. (Carrier, No. 34 at p. 4)
In response to Carrier's concerns, DOE notes that the definition of
PE has always been the electrical energy input to the burner and that
the amendments adopted in this rule merely make explicit additional
components that are commonly incorporated into burners. Further, as
noted in many other stakeholder comments, most manufacturers already
measure the electrical power of all the auxiliary components that are
listed in the revised definition of PE. Therefore, clarifying the
additional components in the definition of PE will not affect ENERGY
STAR ratings for most furnaces. Furthermore, the clarification of the
definition of PE ensures more accurate and consistent reporting of
energy consumption in the residential furnaces and boilers market.
Weil-McLain stated that the new electrical testing requirements
would not allow the manufacturer to interpolate results from tests
because the electrical load will not scale in the same manner as other
aspects of a boiler. This means hundreds of new tests will need to be
run, imposing substantial cost and burden. (Weil-McLain, No. 31 at p.
6)
In response to Weil-McLain's comment, DOE notes that only cast iron
sectional boilers may be certified based on linear interpolation, as
specified in 10 CFR 429.18(b)(3). As stated previously, the amendment
of the definition of PE will not impose additional burden because it
does not change the definition but merely clarifies the components
included in measurement of PE. In addition, DOE's understanding is that
cast iron sectional boilers are typically non-condensing models that do
not have boiler pumps.
Burnham recommended that DOE provide regulatory provisions to
ensure that electrical consumption is measured with the controls
normally shipped with the boiler. Such provisions are required because
in many cases it is impossible to perform the AFUE test using controls
having an automatic means of adjusting water temperature, making
replacement of the standard controls during the AFUE test mandatory.
(Burnham, No. 35 at p. 4) DOE notes that the electrical power
measurement during the steady-state test does not account for
electrical power outside of normal steady-state operation. Therefore,
any controls operation outside of the steady-state test, such as
automatic means for adjusting water temperature, are not included in
the electrical power measurement.
2. Smoke Stick Test for Determining Use of Minimum Default Off-Cycle
and Power Burner Draft Factors
In the March 2015 NOPR, DOE proposed to leave the default draft
factor values for furnaces and boilers unchanged from the existing text
procedure. 80 FR 12876, 12885. DOE did not receive any comments on this
issue, and does not amend the default draft factor values for this
final rule.
In addition, to determine if a unit has no measureable airflow
through the heat exchanger such that manufacturers may use the minimum
default draft factors, DOE proposed in the March 2015 NOPR to
incorporate a test based on the use of a smoke stick to establish the
absence of flow through the heat exchanger. DOE requested input on
whether, in addition to the proposed smoke stick test, other options
exist for indicating the absence of flow through the heat exchanger. 80
FR 12876, 12902.
Lochinvar stated that it appreciates and supports the DOE's
affirmation of the use of smoke for visual determination of no-flow
conditions in the vent. (Lochinvar, No. 29 at p. 4) Similarly, Rheem
stated that although the proposed procedure is not quantitative, it is
more definitive than ``absolutely no chance of airflow through the
combustion chamber and heat exchanger when the burner is off.'' (Rheem,
No. 30 at p. 3)
Ingersoll Rand and Carrier stated that the proposed procedure
requires a detailed definition of the ``smoke stick device'' and test
method to be created and made available. (Ingersoll Rand, No. 37 at p.
5; Carrier, No. 34 at p. 5) Ingersoll Rand stated that the test method
and materials to be used need to be explicitly documented to ensure
that all test labs generate repeatable and reproducible test results.
(Ingersoll Rand, No. 37 at p. 5) Carrier also requested additional
information as to where smoke sticks can be obtained commercially.
(Carrier, No. 34 at p. 5)
DOE agrees with Rheem that the test procedure is not quantitative;
however, the purpose of the test is to provide a visual assessment of
no airflow, not a quantitative measure of airflow. Regarding the
Ingersoll Rand and Carrier request to provide a detailed definition of
the smoke stick device, DOE notes that smoke sticks are commercially
available and routinely used for visualization purposes, and DOE does
not endorse a specific type of smoke stick device. In addition, DOE
believes that the exact amount of smoke produced by the smoke stick is
not essential to the reproducibility of the results.
Ingersoll Rand expressed concern about air flow in the lab and if
manufacturers can fix their venting such that air does not flow through
it. (Ingersoll Rand, Public Meeting Transcript, No. 23 at p. 117)
Similarly, Carrier requested DOE to add clarification to the procedure
to ensure that the smoke stick is not affected by
[[Page 2635]]
the ventilation system when used. Carrier also expressed concern about
the use of a smoke-generating device in a lab area that is not
appropriately ventilated. (Carrier, No. 34 at p. 5)
In response to Ingersoll Rand, DOE already specified that all air
currents and drafts be minimized for the smoke stick test in the March
2015 NOPR. For this final rule, DOE explicitly states that ventilation
should be turned off if the test area is mechanically ventilated, and
to minimize air currents if there is no mechanical ventilation. To
address Carrier's safety concerns, DOE clarifies that the smoke
produced by the smoke stick must be non-toxic to the test personnel.
DOE is confident that the smoke stick test as proposed in the NOPR and
modified based on the clarifications recommended by stakeholders will
ensure repeatable and reproducible test results. Therefore, DOE adopts
the modified optional smoke stick test to determine the absence of flow
through the heat exchanger.
In the March 2015 NOPR, DOE also proposed to include revisions to
the requirements of sections 8.8.3 and 9.10 of ASHRAE 103-2007 to
accommodate the use of the smoke stick test, and, to reduce redundancy,
to eliminate use of the term ``absolutely'' from ``absolutely no chance
of airflow'' in sections 8.8.3 and 9.7.4 of ASHRAE 103-2007. 80 FR
12876, 12902. DOE received no comment on these proposals. Even though
DOE has decided not to adopt ASHRAE 103-2007 and instead retain
reference to ASHRAE 103-1993, the relevant sections do not differ
between the two versions. Therefore, DOE is adding sections 7.10 and
8.10 to appendix N and revising sections 10.2 and 10.3 of appendix N to
accommodate the use of the smoke stick test and is eliminating the use
of the term ``absolutely'' from ``absolutely no chance of airflow'' in
sections 8.8.3 and 9.7.4 of ASHRAE 103-1993 (included as sections 7.10
and 8.9 of appendix N) for determining the use of the minimum default
draft factors.
3. Condensate Collection During the Establishment of Steady State
Conditions
In the March 2015 NOPR, DOE proposed to allow for the condensate
mass to be measured during the establishment of steady-state
conditions, rather than after steady-state has been achieved. 80 FR
12876, 12881. Section 9.2 of ASHRAE 103-1993 requires that the
measurement of condensate shall be conducted during the 30-minute
period after steady-state conditions have been established. For the
March 2015 NOPR, DOE investigated the difference in condensate mass
collected and the rate of condensate production during the two separate
periods (i.e., during the establishment of steady-state conditions and
after steady-state conditions have been reached) and determined that
there is no significant difference in the mass of condensate collected
or the rate of condensate production during the two separate
timeframes.
In response to the March 2015 NOPR, Lennox, Lochinvar and AHRI
stated their support for the allowance to measure condensate during the
establishment of steady[hyphen]state conditions. (Lochinvar, No. 29 at
p. 2; Lennox, No. 32 at p. 3; AHRI, No. 36 at p.5; Ingersoll Rand, No.
37 at p. 5) However, Lennox, AHRI and Ingersoll Rand each noted that to
avoid an unintended consequence of causing manufacturers to retest
existing models, this change should be clearly identified as an option
to the current procedure. (Lennox, No. 32 at p. 3 Lennox, No. 32 at p.
3; AHRI, No. 36 at p.5; Ingersoll Rand, No. 37 at p. 5) Carrier also
agreed that the condensate collection can be done during the steady
state period, so long as clarification is added to prevent testing with
dry heat exchangers. (Carrier, No. 34 at p. 4)
On the other hand, Rheem did not support allowing the measurement
of condensate during the establishment of steady state conditions.
(Rheem, No. 30 at p.1) Rheem argued that condensate measurements have a
significant impact on the final calculated AFUE value and that
additional variation in the condensate measurement procedure will add
variation to the test procedure. Rheem believes that the time spent to
establish steady-state conditions is worthwhile and should not be
eliminated. (Rheem, No. 30 at p.1)
DOE understands commenters' concerns regarding the test burden
associated with the need to retest existing models to the new test
procedure. Therefore, DOE has made the ability to measure condensate
during the establishment of steady-state conditions an option, not a
requirement. This change is incorporated in section 8.4 of appendix N.
In response to Rheem, DOE notes that test data indicate a similar
rate of condensate mass production in both the establishment of steady-
state, and measurement of condensate test intervals. Therefore, DOE
does not expect any impact on AFUE to result from the allowance of this
optional procedure.
4. Installation and Operation Manual Reference
The existing DOE test procedure language, which refers in some
locations to ``manufacturer recommendations'' or ``manufacturer
instructions'', can lead to the use of ad hoc instructions derived
solely for testing purposes. To clarify the test procedure language,
DOE proposed in the March 2015 NOPR that testing recommendations should
be drawn from each product's I&O manual. DOE also provided alternate
instructions if the I&O manual did not contain the necessary testing
recommendations. 80 FR 12876, 12883. Lastly, in the March 2015 NOPR,
DOE proposed to require manufacturers to request a test procedure
waiver from DOE when the DOE test procedure provisions and I&O manuals
are not sufficient for testing a furnace or boiler. Id. These
proposals, comments received, and responses are discussed in the
following sub-sections.
a. Reference to I&O Manual
DOE did not receive any comments objecting to reference the
manufacturer's I&O manuals instead of ``manufacturer's instructions''
or ``manufacturer's recommendations.'' Therefore, DOE replaces all
references to ``manufacturer's instructions'' or ``manufacturer's
recommendations'' in ASHRAE 103-1993 with ``I&O manual'' in appendix
N.\8\ However, in response to the March 2015 NOPR, Burnham suggested
revising the definition of I&O manual in section 2.7 because many oil
boilers do not carry a safety listing as a packaged unit; rather, they
are comprised of separately listed components. (Burnham, No. 35 at p.
5) DOE agrees with Burnham that some boilers do not carry safety
listings as packaged units and thus excludes the reference to the
product's safety listing in the adopted definition of I&O manual in
section 2 of appendix N.
---------------------------------------------------------------------------
\8\ DOE replaced references in sections 7.1, 7.2.2.2, 7.2.2.5,
7.2.3.1, 7.8, 8.2.1.3, 8.3.3.1, 8.4.1.1, 8.4.1.1.2, 8.4.1.2,
8.4.2.1.4, 8.4.2.1.6, 8.7.2, and 9.5.1.1 of ASHRAE 103-1993 with
sections 6.1, 6.2, 6.3, 6.4, 6.5, 7.1, 7.2, 7.3, 7.4, 7.5, 7.6, 7.7,
7.9, and 8.5 of appendix N, respectively.
---------------------------------------------------------------------------
b. Proposed Specific Instructions for Adjusting Combustion Airflow
In the NOPR, DOE proposed specific instructions for adjusting
combustion airflow to achieve an excess air ratio, flue O2
percentage, or flue CO2 percentage to within the middle 30th
percentile of the acceptable range specified in the I&O manual. AHRI
stated that the specification of ``the 30th percentile of the
acceptable range'' is confusing. The 30th percentile is a
[[Page 2636]]
single value so it is not clear what is meant by ``the middle of the
30th percentile.'' (AHRI, No. 36 at p. 3) Ingersoll Rand stated that
the proposed burner adjustments are more restrictive than both the
current test procedure and the specifications found in ASHRAE Standard
103-2007. (Ingersoll Rand, No. 37 at p. 6) Burnham stated that while it
supports DOE's effort to more closely tie air fuel ratio used during
the test with what can be expected in the field, DOE needs to recognize
that the industry practice has been to use the CO2 at the
top end of the range (or in some cases even higher) in the I&O manual.
(Burnham, No. 35 at p. 4) Lochinvar objected to the proposed changes,
stating that forcing boiler manufacturers to test at the maximum input
rate and the middle air-fuel ratio is not typical of field
installations, is inconsistent with past rating methods, and will force
manufacturers to rerate boilers based on this test procedure change.
Lochinvar suggested adopting language from section 5.3 of AHRI Standard
1500, which uses the CO2 at the top of the manufacturer's
specified range, to provide improved clarity and specificity regarding
the air-fuel adjustment and to be more consistent with current industry
practice, with much less potential to force manufacturers to retest and
rerate existing products.\9\ (Lochinvar, No. 29 at pp. 2-3)
---------------------------------------------------------------------------
\9\ AHRI Standard 1500 is available at https://ahrinet.org/site/686/Standards/HVACR-Industry-Standards/Search-Standards.
---------------------------------------------------------------------------
Lennox, AHRI, and Burnham noted that the proposed adjustment of the
CO2 percentage on gas- and oil-fired boilers would
significantly affect AFUE. (Lennox, No. 32 at p. 3; AHRI, No. 36 at pp.
3-4; Burnham, No. 35 at pp. 2, 4) AHRI stated that the results of the
testing of three residential boilers that it conducted at Intertek
Testing Laboratories indicate that the proposed revised burner setup
requirements change AFUE by 0.3 percent for each 1 percent difference
in the CO2 values. (AHRI, No. 36 at pp. 3-4) Burnham stated
that based on test data that it provided, for an oil-fired hot water
boiler with an 11.5 to 12.5 percent CO2 adjustment range in
the I&O manual, DOE's proposed adjustment would reduce AFUE by as much
as 1.0 percent compared to the rating under the existing test
procedure. (Burnham, No. 35 at p. 2) Burnham stated that the proposed
change to the requirements for adjusting CO2 will have a
significant impact on the existing ratings for many boilers, and that
DOE needs to take this into account when evaluating the burden imposed
by this rule, as well as promulgating the parallel residential boiler
standards rulemaking currently underway. (Burnham, No. 35 at p. 4)
Carrier, Ingersoll Rand, and Rheem stated that most modern furnaces
do not have the capability to make combustion air adjustments because
the practice of including primary air shutters is no longer widely used
on modern gas furnaces with fan-assisted or power burners. (Carrier,
No. 34 at pp. 3-4; Ingersoll Rand, No. 37 at p. 6; Rheem No. 30 at p.
3) AHRI and Burnham also stated that for many gas furnaces and boilers
that use atmospheric burners or other equipment with no means of
adjusting CO2 in the field, these adjustments to the excess
air ratio cannot be made. (AHRI, No. 36 at p. 3, Burnham, No. 35 at p.
4) Carrier, Ingersoll Rand, and Burnham stated that DOE needs to
exclude from these requirements burners that have no capability to make
combustion air adjustments. (Carrier, No. 34 at pp. 3-4; Ingersoll
Rand, No. 37 at p. 6; Burnham, No. 35 at p. 4)
Burnham stated that some type of tolerance is needed for adjusting
CO2 when the I&O manual provides only a single or maximum
value, as opposed to a range. To address this issue, Burnham suggested
adopting the language in section 5.3 of AHRI Standard 1500, which
essentially sets a fixed tolerance of 0.1 percent and uses
the CO2 at the top, as opposed to the middle, of the
manufacturer's specified range.\10\ (Burnham, No. 35 at p. 4)
---------------------------------------------------------------------------
\10\ AHRI Standard 1500 is available at https://ahrinet.org/site/686/Standards/HVACR-Industry-Standards/Search-Standards.
---------------------------------------------------------------------------
After reviewing stakeholders' comments on the specific instructions
for adjusting combustion airflow, DOE concurs that further study is
needed to determine the impact on AFUE of the CO2 percentage
proposed in the March 2015 NOPR and the AHRI 1500 requirements
suggested by certain stakeholders. As such, for this final rule, DOE
does not adopt the specific instructions for adjusting combustion
airflow to achieve an excess air ratio, flue O2 percentage,
or flue CO2 percentage to within the middle 30th percentile
of the acceptable range specified in the I&O manual. Instead, in
sections 7.3 and 7.5 of appendix N, DOE retains the instructions in
accordance with ASHRAE 103-1993 section 8.4.1.1 for gas burners to set
the primary air shutters to give a good flame with no deposit of carbon
during the test procedure, and section 8.4.1.2 for oil burners to give
a CO2 reading as specified in the I&O manual and an hourly
Btu input within 2% of the normal hourly Btu input rating
as specified in the I&O manual. DOE understands from stakeholder
comments that the instructions in the existing test procedure to adjust
the primary air shutters for gas units are not applicable to many
modern furnaces and boilers. However, DOE has determined that further
investigation is required before amending these test procedure
requirements.
c. Waiver Process for Additional Test Instructions
In response to DOE's proposal that manufacturers request a test
procedure waiver from DOE when the DOE test procedure provisions and
I&O manuals are not sufficient for testing a furnace or boiler, Burnham
stated that the proposed waiver process is unduly burdensome, given the
use of increasingly complex control and burner systems. To reduce the
frequency with which waivers are required, Burnham suggested that DOE
adopt a repository for ``special test instructions'' similar to that
which DOE currently has in place for commercial boilers. (Burnham, No.
35 at p. 5) Lennox and AHRI similarly stated that if DOE is concerned
about the situation where the manufacturer does not provide any
recommended settings in the I&O manual, DOE should allow manufacturer
to provide information on unit setup for testing as part of the
certification report as is done for commercial and industrial
equipment. (Lennox, No. 32 at p. 3; AHRI, No. 36 at pp. 4, 6)
In response to stakeholders' comments, DOE notes that manufacturers
have control over what information is specified in the I&O manual.
Furthermore, the test procedure provides defaults for most requirements
that are based on the I&O manual. As such, DOE believes the
instructions given in the test procedure and I&O manuals should be
sufficient for testing in most cases. Therefore, DOE is not amending
its certification provisions to permit manufacturers to report test-
specific instructions as supplemental information in cases where the
I&O manual does not provide instructions, and is implementing the
requirement to request a waiver in section 6.1.a of appendix N. DOE
also notes that the waiver procedure provides a feedback loop by which
DOE learns of issues manufacturers are encountering with the test
procedure and yields amendments to the test procedure through
rulemaking to address those issues.
[[Page 2637]]
5. Duct Work for Units That Are Installed Without a Return Duct
In the March 2015 NOPR, DOE proposed to add a provision in the test
procedure clarifying that the return (inlet) duct is not required
during testing for units that, according to the I&O manual, are
intended to be installed without a return duct. 80 FR 12876, 12902-
12903.
In response, Rheem, Carrier, and Ingersoll Rand agreed that a unit
that is intended to be installed without a return duct should be tested
without a return duct. (Rheem, No. 30 at p. 3; Carrier, No. 34 at p. 6;
Ingersoll Rand, No. 37 at p. 5) In addition, Carrier recommended that
DOE adopt figure 2 in exhibit 1 of Carrier's comment, which clarifies
the use of a return duct for gas furnaces. (Carrier, No. 34 at p. 6)
DOE agrees with stakeholders and adopts the amendment clarifying
that units intended to be installed without a return duct are not
required to use the return (inlet) duct during testing. After reviewing
the figure provided by Carrier, DOE believes that the language is
sufficient and an additional figure is unnecessary.
6. Testing Requirements for Multi-Position Configurations
In the March 2015 NOPR, DOE proposed to require that multi-position
furnaces be tested using the least-efficient position.\11\ DOE also
proposed to explicitly allow manufacturers to test multi-position
furnaces in other configurations and report the AFUE ratings for each
position. 80 FR 12876, 12886.
---------------------------------------------------------------------------
\11\ A multi-position furnace is a furnace that can be installed
in more than one airflow configuration (e.g., upflow or horizontal;
downflow or horizontal; and upflow, downflow or horizontal).
---------------------------------------------------------------------------
In response, AHRI stated that they believe that manufacturers
already test in the least-efficient configuration. (AHRI, Public
Meeting Transcript, No. 23 at p. 123)
Carrier stated that in the past, it has tested and displayed the
AFUE by orientation of installation; however, it no longer does so
because the multiple ratings by position did not give customers any
benefit. Because the setup requirements of the DOE test procedure
already cause furnaces to operate at the lowest efficiency, thus making
AFUE ratings conservative for the average installation, Carrier
recommended that DOE drop the requirement to test in all positions and
simplify the testing to be in the most commonly installed position of
the furnace. If DOE were to require testing in all positions, Carrier
proposed an alternative to allow single rating that is weighted based
on percent of applications by configuration and installation location
to reduce sample testing burden and not confuse consumers with excess
information. (Carrier, No. 34 at pp. 6-8)
Lennox disagreed with the testing requirements in multiple
configurations because of the increased test burden and lack of
improved test accuracy. (Lennox, No. 32 at pp. 3-4)
In response to Carrier's and Lennox's concerns about increased test
burden if required to test in all configurations, DOE clarifies that in
the March 2015 NOPR, DOE did not propose to require manufacturers to
test in all positions, but rather to require testing only in the least
efficient configuration while explicitly allowing manufacturers to test
in multiple configurations if they wish. DOE notes that, as stated by
AHRI, it is already common industry practice to test in the least
efficient configuration; accordingly, DOE anticipates that there will
be no additional test burden from the clarification to require testing
in the least efficient configuration. Regarding Carrier's suggestion to
test in the dominant installed position, DOE believes that testing in
the least efficient position will provide ratings that are more
comparable between different models because the dominant position may
not be the least efficient configuration and may vary among models and
among manufacturers. DOE believes that Carrier's suggestion of a
weighted rating is not practicable because DOE is not requiring
manufacturers to test in all configurations, only the least efficient
one. Therefore, in section 6.1.b of appendix N and in 10 CFR 429.18,
DOE amends its regulations to require testing and rating only in the
least efficient configuration, while still allowing manufacturers the
ability to test and rate in multiple configurations. In addition, DOE
includes a definition for multi-position furnace in section 2 of
appendix N.
In the March 2015 NOPR, DOE also proposed to allow testing of units
configured for multiple position installations to use the blower access
door as an option instead of one of the inlet openings. 80 FR 12876,
12886 (March 11, 2015). In response, Rheem stated that a furnace should
not be tested in a configuration that is prohibited by the installation
manual. For example, Rheem stated that its furnace installation manuals
allow only bottom and side returns. A rear return and a return in place
of the blower access door are not allowed. (Rheem, No. 30 at p. 4)
Ingersoll Rand stated that testing of multi-position units using the
blower access door may not be feasible option for some furnaces, and
the manufacturer should state whether this is an acceptable test method
for the furnace model. (Ingersoll Rand, No. 37 at p. 6)
DOE agrees with Rheem and Ingersoll Rand that units should not be
required to be tested using the blower access door if not allowed in
the I&O manual or if not feasible. In an effort to ensure consistent
and appropriate testing, DOE withdraws its proposal that would have
explicitly allowed the use of the blower access door for testing of
multi-position furnaces and boilers that are not shipped with an open
inlet.
7. AFUE Reporting Precision
DOE's existing furnaces and boilers test procedure specifies that
the AFUE rating be rounded to the nearest whole percentage point. 10
CFR 430.23(n)(2). In the March 2015 NOPR, DOE sought comment on its
proposal to report AFUE to the nearest tenth of a percentage point. 80
FR 12876, 12902.
AHRI, Lochinvar, Lennox, and Burnham support reporting of AFUE to
the nearest tenth of a percentage point and noted that it reflects the
current practice. (AHRI, No. 36 at p. 6; Lochinvar, No. 29 at p. 4;
Lennox, No. 32 at p. 3; Burnham, No. 35 at p. 6) However, Burnham does
not agree with the proposal to round to the nearest 0.1 percent,
stating that it would be a direct violation of 10 CFR
429.18(a)(2)(i)(B) requiring any representative value of AFUE for which
consumers would favor higher values to be less than or equal to the
lower of the mean of the sample or the lower 97.5 percent confidence
limit (LCL) of the true mean divided by 0.95. Burnham stated that
rounding up would allow the representative value to potentially be
higher than allowed by calculation mentioned. Burnham urged DOE to
prescribe the current industry practice of truncating to 0.1 percent.
(Burnham, No. 35 at pp. 6-7)
In contrast, Rheem stated that rating furnaces to the nearest tenth
of a percentage point will give consumers the impression that one
furnace is more efficient than another, while in actuality, the test
procedure tolerances do not result in the proposed level of precision
that should be required to support reporting AFUE to the nearest tenth
of a percentage point. (Rheem, No. 30 at p. 3)
Ingersoll Rand stated that while DOE's CCMS can accommodate
reporting AFUE to this level, any manufacturer that reports AFUE to the
whole percentage point will have to submit new certification reports
and
[[Page 2638]]
relabel products. Ingersoll Rand stated that having to submit new
certification reports and relabel products will cause an administrative
burden and cost to manufacturers that was not addressed in the March
2015 NOPR. Ingersoll Rand requested that DOE consider setting the
effective date of this requirement to coincide with the effective date
of any amended energy conservation standard adopted under the March 12,
2015 energy conservation standards NOPR for residential furnaces.
(Ingersoll Rand, No. 37 at p. 6)
AHRI stated that it reports to the nearest tenth to DOE for
furnaces but not for boilers due to Environmental Protection Agency
(EPA) and ENERGY STAR requirements. (AHRI, Public Meeting Transcript,
No. 19 at p. 89) Burnham urged DOE to work with the EPA to
simultaneously update the ENERGY STAR requirement of rounding to the
nearest whole percentage point to avoid conflicting values on the DOE
and ENERGY STAR Web sites. (Burnham, No. 35 at p. 7)
DOE understands that reporting AFUE values to the nearest tenth of
a percentage point is currently industry practice. Based on 10 CFR
429.18(a)(2)(i)(B), DOE agrees with Burnham that AFUE should be
truncated to the tenth of a percentage point. In response to Rheem's
comment about the test procedure tolerances, DOE notes that in response
to the January 2013 RFI, Rheem stated that this level of precision has
been demonstrated to be statistically possible. (Rheem, No. 12 at p.
9). DOE also observes that Rheem, as well as many other manufacturers,
reports AFUE to the tenth of a percentage point in DOE's Compliance
Certification Database and the AHRI directory for some models. In
response to Ingersoll Rand's comments, DOE notes that AHRI's
certification directories for both furnaces and boilers as well as
DOE's Compliance Certification Database already allow manufacturers to
report AFUE to the nearest tenth of a percentage point. Therefore, DOE
anticipates this clarification will not require changing the reported
efficiency in manufacturer literature, nor will it cause significant
manufacturer burden. Furthermore, in response to AHRI and Burnham, DOE
notes that EPA must use the method of test, sampling plan, and
representation requirements adopted by DOE. DOE will work with EPA to
make sure the language in its specification is harmonized with federal
regulations. Accordingly, DOE updates the existing requirement for
residential furnaces and boilers in 10 CFR 430.23(n)(2) to truncate
AFUE to the tenth of a percentage point. DOE also clarifies in 10 CFR
429.18 that the represented value of AFUE based on the tested sample
must be truncated to the tenth of a percentage point.
8. Definitions and Other Changes
In this final rule, DOE revises the term ``seasonal off switch'' to
``off switch'' and revises the definitions of ``off mode'' and
``standby mode'' in section 2 of appendix N to reflect the updated
definitions found in the second edition of IEC 62301, which was
incorporated by reference in the December 2012 final rule. DOE also
revises sections 8.1, 8.2, and 8.4 of the existing appendix N (sections
8.3, 8.5, and 8.7 of the amended appendix N) to clarify and improve the
test instructions. DOE also revises sections 10.4, 10.5, 10.6, 10.7.3,
10.9, 10.9.1, and 10.11 of appendix N to improve grammar and
consistency in formatting throughout the test procedure, and to include
missing variable definitions. In addition, DOE incorporates the
previously excluded section 9.7.l of ASHRAE 103-1993 to include
instructions on the setup of the tracer gas test. DOE updates the
definition of ``isolated combustion system'' in section 2.5 of the
existing appendix N (2.8 of the amended appendix N) to reflect the
updated definition in ASHRAE 103-2007. Finally, DOE modifies section
8.3 of the existing appendix N (8.6 of the amended appendix N) to
clarify that the referenced time delay is the blower delay t\+\. DOE
did not receive comment on any of these revisions where proposed in the
NOPR.
E. Other Test Procedure Considerations
1. Room Ambient Air Temperature and Humidity Ranges
In the March 2015 NOPR, DOE proposed not to change the test
procedure regarding room ambient temperature and humidity conditions,
neither by mathematical correction nor by limiting the existing ambient
condition range, and requested input on this approach. 80 FR 12876,
12889.
Lochinvar and Lennox stated their support for DOE's proposal not to
further restrict the ambient conditions due to the additional test
burden it would cause. (Lochinvar, No. 29 at p. 4; Lennox, No. 32 at p.
4) Rheem stated that they believe that the ambient conditions range
requires further study. Rheem noted that the room ambient air
temperature and humidity ranges were developed based on 30-year-old
laboratory conditions and that laboratory conditions may be more
carefully controlled today compared to the long past. (Rheem, No. 30 at
p.1) AHRI noted that the new edition of ASHRAE-103-2016 will be issued
for public review and one of the proposed amendments is to include
changes to the definition of room ambient air operating conditions.
(AHRI, No. 36 at p. 5)
Burnham stated that they disagree with DOE's assertion in the March
2015 NOPR that relative humidity (RH) has a minimal impact on the AFUE
of condensing boilers and stated that the issue should be revisited.
Burnham provided test data of a condensing boiler which shows a swing
in AFUE of approximately 1.3 percent when the RH was changed from
approximately 30 percent to 70 percent. Burnham stated that they expect
the variation in AFUE as a function of RH to be at least as large for
boilers as it is for furnaces. Burnham noted that the flue temperature
of boilers is closely linked to the return water temperature during the
test (120[emsp14][deg]F), which is close to the typical dew point of
natural gas flue products. Changes in RH may therefore have a large
impact on where the temperature of the flue products falls below the
dew point as they pass through the heat exchanger. Burnham stated that
if ambient conditions have a significant impact on AFUE, DOE should
tighten the tolerance for RH to conditions likely to be seen in the
field, even if this results in an increased burden for manufacturers in
the form of requiring conditioned lab facilities. (Burnham, No. 35 at
p. 7)
DOE agrees with Rheem and Burnham that the impact of ambient
conditions on AFUE warrants further study. However, at this time DOE
does not have adequate data to justify the testing burden associated
with the narrowing of ambient conditions. Therefore, DOE maintains the
ambient conditions specified in the current test procedure.
2. Full-Fuel-Cycle Energy Metrics
In the March 2015 NOPR, DOE stated that the test procedure
rulemaking was not the appropriate vehicle for deriving an FFC energy
descriptor for furnaces (and other products). Specifically, DOE noted
that if a secondary FFC energy descriptor were included as part of the
furnace and boiler test procedure, DOE would need to update the test
procedure annually. DOE indicated its intent to estimate FFC energy
savings in future energy conservation standards rulemakings for
furnaces, and to take those savings into account in proposing and
selecting amended standards. 80 FR 12876, 12896.
In response to the NOPR, AGA expressed their disagreement with
[[Page 2639]]
DOE's position, stating that the test procedure develops the energy
efficiency rating for the product and is specifically the correct
vehicle to be used for determining the FFC energy descriptor. AGA added
that all that is needed is a mathematical adjustment to the site-based
energy descriptor now determined by the test procedure. AGA requested
that the Department reconsider its decision not to include provisions
for an FFC energy descriptor and incorporate one in the test procedures
for residential boilers and furnaces. (AGA, No. 27 at p. 3)
DOE maintains its position outlined in the NOPR that it does not
believe that a mathematical adjustment to the test procedure to account
for FFC is appropriate. As noted in the March 2015 NOPR, the
mathematical adjustment to the site-based energy descriptor relies on
information that is updated annually. If DOE were to include such an
adjustment to the test procedure, DOE would be required to update the
test procedure annually.
3. Oversize Factor Value
In the March 2015 NOPR, DOE proposed to maintain the existing
oversize factor of 0.7 and sought comment on the appropriateness of
this strategy.\12\ 80 FR 12876, 12891.
---------------------------------------------------------------------------
\12\ The ``oversize factor'' accounts for the national average
oversizing of equipment that occurs when a heating product is sized
to satisfy more than the heating load of the household. This is
typically done to size the equipment so that it is able to satisfy
the days in which the house heating requirements might be exceeded
and/or to take into account uncertainties regarding house heating
load. For example, a 0.7 oversize factor is equivalent to 170-
percent oversizing of the heating equipment (i.e., 70 percent
greater input capacity than is required).
---------------------------------------------------------------------------
Rheem stated that replacement furnaces are more likely to be
oversized than a new construction furnace because the unit may not be
resized when it is replaced with a more efficient unit. Rheem also
noted that it is more likely for a furnace to be oversized in a climate
with high variation in outdoor temperature, or if it is installed in an
area with high airflow requirements for the cooling load. (Rheem, No.
30 at p. 4)
DOE agrees with Rheem that a variety of factors, including
construction type and climate, may influence the magnitude of
oversizing that occurs in a given installation. DOE did not receive any
data supporting a change to the existing oversize factor of 0.7. DOE
has determined the existing value of 0.7 continues to be representative
of the oversized factor applicable to the average U.S. household and
therefore maintains that value.
4. Alternative Methods for Furnace/Boiler Efficiency Determination
In response to the March 2015 NOPR, Carrier questioned the need for
a test method as precise as ASHRAE 103 due to the advances that have
been made in reducing cyclical losses. Carrier noted that the
difference between steady state efficiency and cyclical AFUE is less
than 1 percent across all model types. Carrier suggested that DOE
change the AFUE metric for forced-air furnaces to be based on the
steady-state operation. (Carrier, No. 34 at p. 2) Carrier stated that
this would simplify the test procedure and relieve significant burden
from manufacturers. Carrier stated that the lab setup of gas furnaces
during AFUE testing--including vent length, isolated combustion system
(ICS) installation, off cycle times, and blower off delay time--rarely
replicates the actual installation of condensing gas furnaces.
(Carrier, No. 34 at p. 2)
DOE agrees that there have been significant advances in the
minimization of cyclical losses since the inception of the AFUE metric.
However, including cyclical losses, which are captured in the AFUE
metric, still provides market differentiation for models that would
yield the same steady-state values. Furthermore, DOE believes that the
inclusion of cyclical losses in the AFUE metric has contributed to the
increases in efficiency noted by Carrier. For these reasons, DOE
declines to limit the calculation of AFUE to steady-state operation.
DOE would be willing to work with industry to investigate this further
to see if moving to a steady-state methodology has merit and meets the
requirements of the statute.
5. Test Method for Combination Appliance
In the March 2015 NOPR, DOE discussed the possibility of creating a
test procedure for determining the efficiency of combination products.
Ultimately DOE did not propose to amend the test procedure to include a
method of test for combination appliances choosing not to complicate
the test procedure rulemaking. 80 FR 12876, 12894.
In response to the NOPR, Ingersoll Rand believes that EPCA
anticipated products being capable of serving more than one function
and expects DOE to set separate energy efficiency metrics for each
major function. Ingersoll Rand noted that EPCA authorizes DOE to ``set
more than 1 energy conservation standard for each major function.'' (42
U.S.C. 6295(o)(5)) Ingersoll Rand suggested that establishing a
combination metric and setting a standard for a combination unit is
contrary to EPCA. (Ingersoll Rand, No. 37 at p. 6)
DOE did not propose a combination metric in the NOPR, and does not
amend the test procedure to include such a metric in this final rule.
F. Test Burden
EPCA requires that the test procedures DOE prescribes or amends be
reasonably designed to produce test results that measure the energy
efficiency, energy use, water use (in the case of showerheads, faucets,
water closets, and urinals) or estimated annual operating cost of a
covered product during a representative average use cycle or period of
use. These procedures must also not be unduly burdensome to conduct.
(42 U.S.C. 6293(b)(3))
In response to the March 2015 NOPR, Ingersoll Rand stated that the
testing and reporting burden from the proposals would be far greater
than the average 20 hours per response that DOE estimates. (Ingersoll
Rand, No. 37 at p. 9) Weil-McLain expressed concerns that the cost of
the proposed test is grossly underestimated and that cost analysis for
all of the testing is fundamentally flawed and incomplete. Weil-McLain
stated that a more appropriate estimate for the cost to re-test all
models in DOE's example of average small boiler business with 70 basic
models would be more than twenty times the estimate shown for various
reasons, such as the cost of set up for each test, test re-runs if
parameters are not met, test recording, and analysis time. In addition,
Weil-McLain stated that: (1) Only the incremental cost related to the
changes in procedure have been captured when in all likelihood all
products will have to be retested through the entire test procedure;
(2) at least two tests per model are required for data submittal; (3)
initial certification and annual audits require an additional witness
test by a third-party lab; (4) engineering, facility, or other charges
were not captured; (5) third-party test agency fees were not
considered; and (6) the time required to test the number of models for
the manufacturer and third-party test agency capacity were not
considered. Weil-McLain also stated that retesting and re-rating would
take substantially longer than 180 days. (Weil-McLain, No. 31 at pp. 6-
7) Ingersoll Rand stated that to retest all of its current models will
require more than six months of lab time with a cost of over $400,000.
(Ingersoll Rand, No. 37 at p. 9)
Weil-McLain questioned why DOE would impose the burden of
conducting all of the new tests on manufacturers
[[Page 2640]]
when DOE stated that the results from using new test procedures will
not change when compared to current procedure. (Weil-McLain, No. 31 at
p. 2)
Several stakeholders requested more time to conduct re-testing
after the issuance of the final rule. Weil-McLain stated that the
process of conducting all the tests, analyzing information, and
conducting re-certification through the certified labs for hundreds of
models cannot be completed within 180 days of when the final rule is
issued. (Weil-McLain, No. 31 at p. 7) Similarly, Burnham expressed
concern that it has found it impossible to thoroughly evaluate the
impact of this NOPR, as it asserted that DOE provided only a short
amount of time and inadequate information and resources during the
rulemaking process. (Burnham, No. 35 at p. 8) Goodman stated that the
industry needs at least 6 months to assess the impact of the new test
procedure on existing basic models. (Goodman, No. 33 at p. 2)
Ingersoll Rand argued that the fact that many of the current models
may be removed from the market as a result of the separate energy
conservation standards rulemakings, Fan Energy Rating (FER) standard
effective in 2019 and AFUE proposed standard effective in 2021, makes
this retesting effort even more burdensome, unnecessary and wasteful.
(Ingersoll Rand, No. 37 at p. 9) Carrier also stated that recent
rulemakings, such as the standby power ruling and the recent
legislation for furnace fans, have increased the test burden for gas
furnace compliance compared to when the complicated AFUE procedure was
formulated and first implemented. (Carrier, No. 34 at p. 3)
The many comments from manufacturers regarding re-testing of all
models currently in distribution were responding to DOE's proposals to
incorporate by reference ASHRAE 103-2007 and adjust the CO2
percentage. Under the amended test procedure, DOE is not incorporating
by reference ASHRAE 103-2007 or adjusting of the CO2
percentage, and so manufacturers will not need to re-test their entire
model line-up, thereby alleviating the concerns expressed by
manufacturers. DOE has assessed the test burden of the revisions to the
test procedure it is adopting in this final rule, and has concluded
that manufacturers will experience no additional burden when performing
the AFUE test.
DOE believes that the clarification of the electrical power term PE
will not add any additional burden on manufacturers, since this is what
has been required under the existing test procedure. In terms of the
boiler pump, DOE included a default value in case manufacturers are not
currently capturing this component, which will minimize test burden.
Many manufacturers currently perform the tracer gas test to
determine whether the minimum default draft factor of 0.05 may be used.
DOE expects that, when establishing the absence of flow through the
heat exchanger, the use of the smoke stick test will reduce the test
burden to manufacturers by eliminating, in some cases, the need for the
tracer gas test.
The optional provision allowing for the measurement of condensate
during the establishment of steady-state conditions will provide
manufacturers of condensing furnaces and boilers time and labor
savings.
The inclusion of references to the I&O manual will provide
additional guidance and clarity to the test procedure. It does not
impose additional test burden since the information is already
available in the manufacturers' literature.
The amendment of the duct work setup for units that are installed
without a return duct and the requirement to test multi-position units
in the least efficient position only clarify the testing requirements.
The duct work setup change reflect current industry practice and does
not introduce new testing requirements. With respect to the multi-
position unit testing, most manufacturers indicated that the change
reflects their understanding and current practice. DOE notes that,
although the test method did not describe the position for testing as
the ``least efficient position,'' in practice, if following the
existing method for setup, manufacturers should have tested the least
efficient position or all testing configurations. DOE also notes that
AHRI commented that this reflects the common practice of its members,
which is to test in the least efficient position. (AHRI, Public Meeting
Transcript, No. 23 at p. 123) Therefore, DOE expects that there would
be no additional test burden associated with these revisions.
The requirement to report AFUE to be truncated to the tenth of a
percentage point and the requirement to report whether a boiler uses a
burner delay automatic means control strategy will not introduce any
additional test burden because they do not require retesting; however,
they may impose a cost on either boiler manufacturers or manufacturers
who do not currently report AFUE to a tenth of a percentage point, who
must submit new certification reports and relabel their products. DOE
discusses this burden in section IV.B.
For these reasons, DOE concludes that the amended test procedure
will not be unduly burdensome to conduct.
G. Measured Energy Use
When DOE modifies test procedures, it must determine to what
extent, if any, the new test procedure would alter the measured energy
efficiency or energy use of any covered product. (42 U.S.C. 6293(e)(1))
In the NOPR, DOE stated that the one amendment that might alter the
AFUE of covered products is the incorporation by reference of ASHRAE
103-2007. 80 FR 12876, 12897.
As discussed in section III.C, based on stakeholder comments, DOE
has declined to incorporate by reference ASHRAE 103-2007 in this final
rule. Therefore, the amended test procedure will not alter measured
AFUE ratings.
As discussed in section III.D.1, certain stakeholders commented
that the proposed revision in the NOPR regarding the method for
determining the electrical power consumption would change the power
measurements. In response to comments, for the Final Rule, DOE decided
not to change the method for calculating the electrical consumption and
only clarified the definition of the PE term. This clarification will
not alter measured AFUE ratings.
As discussed in section III.D.3, certain stakeholders expressed
concern that allowing the measurement of condensate during the
establishment of steady state conditions would have an impact on the
final calculated AFUE value. In response to comments, DOE clarified for
the final rule that this is an option rather than a requirement. DOE
has found through its testing as shown in the test data presented at
the NOPR public meeting indicating both options produce a similar rate
of condensate mass production and therefore would have a de minimis
impact on measured AFUE ratings.
As discussed in section III.D.4.b, certain stakeholders expressed
concern that the proposed adjustment of the CO2 percentage
on gas- and oil-fired boilers would significantly affect AFUE. In
response to comments, DOE has declined to adopt this proposal for the
final rule.
DOE received no comment regarding the impact of measured energy use
on the remaining test procedure amendments, including the smoke stick
test, duct work for units that are installed without a return duct, and
testing requirements for multi-position configurations. The smoke stick
test serves to verify a condition and does not
[[Page 2641]]
impact ratings. The requirements for units installed without a return
duct and for multi-position configurations only clarify the testing
requirements, and therefore will not impact measured energy use or
efficiency.
For these reasons, DOE has determined that none of the adopted test
procedure amendments would alter the projected measured energy
efficiency or energy use of the covered products that are the subject
of this rulemaking.
H. Certification and Enforcement
1. Verification Test for Automatic Means for Adjusting the Water
Temperature in Boilers
In 2008, DOE published a technical amendment to the 2007 energy
conservation standards final rule for residential furnaces and boilers
that added design requirements for boilers consistent with the
provisions of EISA 2007, including mandating, starting September 1,
2012, that all gas, oil, and electric hot water boilers (excluding
those equipped with a tankless domestic water heating coil) be equipped
with automatic means for adjusting the boiler water temperature
(``automatic means'') to ensure that an incremental change in inferred
heat load produces a corresponding incremental change in the
temperature of water supplied (codified at 42 U.S.C. 6295(f)(3)).\13\
73 FR 43611 (July 28, 2008). EISA 2007 further specifies that for
single-stage hot water boilers, the automatic means requirement may be
satisfied by incorporating controls that allow the burner or heating
element to fire only when the automatic means has determined that the
inferred heat load cannot be met by the residual heat of the water in
the system. When there is no inferred heat load, the automatic means
limits the temperature of the water in the boiler to not more than 140
[deg]F.
---------------------------------------------------------------------------
\13\ The automatic means requirement excludes boilers that are
manufactured to operate without any need for electricity. EISA 2007
also prohibited constant-burning pilot lights for gas-fired hot
water boilers and gas-fired steam boilers. 73 FR 43611, 43613 (July
28, 2008).
---------------------------------------------------------------------------
The existing DOE residential furnace and boiler test procedure does
not include any method of test for determining compliance with these
design requirements. In the March 2015 NOPR, DOE proposed the
introduction of a new test method for the verification of the automatic
means for adjusting the water temperature in boilers. DOE proposed the
use of two test methods--one for single-stage boilers and one for two-
stage/modulating boilers--for verification of the functionality of the
automatic means for adjusting the water temperature supplied by a
boiler. The proposed test methods were based on draft testing
methodologies provided by Natural Resources Canada (NRCan), as well as
the California mechanical codes section for non-residential
boilers.\14\ The two separate tests were developed to accommodate
various boiler control strategies, including outdoor reset, inferred
load, and thermal pre-purge (i.e., burner delay).\15\ The proposed test
methods, as would be specified in 10 CFR 429.134, would be intended for
use by DOE for assessment and enforcement testing to determine if a
given basic model complies with the applicable design requirements.
Therefore, boiler manufacturers would not be required to conduct this
testing. 80 FR 12876, 12902.
---------------------------------------------------------------------------
\14\ California Energy Commission, ``Reference Appendices for
the 2008 Building Energy Efficiency Standards for Residential and
Non-residential Buildings'', p. 332, (Available at: https://www.energy.ca.gov/2008publications/CEC-400-2008-004/CEC-400-2008-004-CMF.PDF) (Last accessed January 16, 2015).
\15\ See the March 2015 NOPR for further description of the
different control strategies.
---------------------------------------------------------------------------
Several stakeholders commented on the lack of compliance criteria
for the automatic means test. Burnham asserted that it is legally
unacceptable for DOE to not specify any objective criteria for
demonstrating compliance and that DOE does not have authority to
unilaterally create criteria to determine compliance with the automatic
means test without notice and comment. (Burnham, No. 35 at p. 6) Weil-
McLain stated that it is not clear what this required test criteria or
procedure would be, but that, once defined, this test will require more
time and resources to complete. Weil-McLain also asserted that the new
requirement is arbitrary and capricious because it is so indefinite.
(Weil-McLain, No. 31 p. 8)
DOE's automatic means design requirement does not specify how a
manufacturer must implement the automatic means and does not provide
compliance criteria for the automatic means testing. DOE interprets the
design requirement established by EISA 2007 as intending to allow
manufacturers flexibility when designing control strategies to meet the
design requirement. DOE believes that the requirement of an incremental
change in inferred heat load that produces a corresponding incremental
change in the temperature of water supplied is a sufficient metric for
evaluation of the functionality of an automatic means for adjusting
water temperature. DOE designed the tests, as noted in the March 2015
NOPR, to confirm whether the boiler supply water temperature responds
to a change in inferred heat load without specifying to what degree the
temperature must change or for how long that change is present because
such detail is not required for meeting the design requirement. DOE
also designed the test methods to accommodate technological
advancements in controls and designs. For these reasons, DOE does not
agree with Burnham and Weil-McLain that establishing further criteria
or thresholds is required beyond the general requirements set forth in
the 2008 technical amendment to the furnace and boiler final rule.
Lochinvar stated that while it supports the use of automatic means
as an effective method of energy conservation, it opposes testing
controls for compliance for the following reasons: (1) The lack of
compliance threshold; (2) no guarantee of repeatability or consistency
in test method or results; (3) difficulty in reasonably measuring the
effectiveness of different designs; (4) test method may be biased for
or against certain control methods; and (5) a published simulation-type
test will lead to manufacturers designing automatic means for the test
compliance. (Lochinvar, No. 29 at p. 3) AHRI stated that the criterion
to confirm the functioning of the means is too vague to be meaningful,
and that DOE should not finalize this proposed procedure and not pursue
further the concept of adding a test to verify the functioning of the
automatic means. (AHRI, No. 36 at p. 6)
Several stakeholders commented on technical issues regarding the
proposed test method. Lochinvar and Burnham stated that single-stage
products may use options other than ``thermal purge.'' (Lochinvar, No.
29 at p. 3; Burnham, No. 35 at p. 6) Lochinvar stated that if DOE
chooses to require automatic means testing, single-stage boilers must
be allowed to comply by meeting either the proposed test method in
Sec. 429.134(e)(1) or (e)(2). (Lochinvar, No. 29 at p. 3)
Lochinvar also stated that DOE incorrectly states that the
automatic means will change the heat output of a boiler in response to
the inferred heat load. Responding to DOE's proposal in the March 31,
2015 notice of proposed rulemaking for energy conservation standards
for boilers (``March 2015 ECS Boiler NOPR''), Lochinvar asserted that
the automatic means would change the temperature of the water supplied,
not necessarily the heat output. (Lochinvar, No. 29 at p. 4)
Burnham argued that the water temperatures specified are too low to
necessarily cause a burner delay. Also responding to the March 2015 ECS
Boiler NOPR, Burnham suggested that the proposed 10 CFR
[[Page 2642]]
429.134(e)(1)(iii)(C) seems to imply that a delay will always be
present. However, Burnham asserted that EISA only requires that the
automatic means delay ignition above 140 [deg]F until it has determined
that the inferred heat load cannot be met by the residual heat in the
boiler. (Burnham, No. 35 at p. 6)
Burnham stated that the proposed 10 CFR 429.134(e)(2)(ii)(B)(1)
specifies that the supply water temperature be maintained at ``the
lowest supply water temperature (4 [deg]F),'' which may not
be possible if the boiler's minimum input is greater than the
corresponding load, resulting in burner cycling. Burnham stated that a
similar problem is possible in the proposed 10 CFR
429.134(e)(2)(ii)(C)(2), where a ``boost function'' (a control strategy
commonly used that shifts the y-intercept of the reset curve upward
during extended calls for heat) might make it impossible to hold the
required 3 [deg]F tolerance for the boiler supply water
temperature. (Burnham, No. 35 at p. 6)
Burnham stated that some of the control strategies currently in use
require multiple burner cycles to determine the inferred heat load,
which does not seem to be taken into account by DOE's proposed
verification method. (Burnham, No. 35 at p. 6)
DOE makes several changes to the proposed verification of automatic
means tests to address the technical comments received from Lochinvar
and Burnham. DOE revised the two tests for the verification of
automatic means presented in the NOPR such that the test previously
identified as the two-stage/modulating boilers test will apply to all
boilers, with the exception of single-stage boilers that employ a
burner delay control strategy. The test for all boiler products
monitors water temperature settings from the inferential load
controller and/or monitors supply water temperature to determine
whether the supply water temperature changes in response to changes in
the inferred load. This test method allows for establishing the
necessary conditions that may lead to a change in inferred load, for
example, a change in outdoor air temperature, a change in thermostat
patterns, and/or a change in boiler cycling.
DOE is adopting the test previously identified as the single-stage
boilers test as the test method for single-stage boilers that employ a
burner delay control strategy to fulfill the automatic means design
requirement as specified in 42 U.S.C. 6295(f)(3)(B)(ii). The test for
single-stage boilers that employ a burner delay control strategy
captures the delayed burner reaction following a call for heating when
residual heat is present within the boiler.
DOE agrees with Burnham and Lochinvar's comments that help to
clarify the test method and allow for accommodating variations in the
control strategies. Therefore, DOE adopts revisions that include
removing the minimum supply water temperature tolerance requirement to
allow variations in temperature when burner cycling occurs; increasing
the inlet water temperature from 120 [deg]F (2 [deg]F) to
140 [deg]F (2 [deg]F) for the test method for single-stage
boilers that employ a burner delay control strategy so that it is high
enough to cause burner delay; and making terminology related to inlet
water consistent throughout the test method. However, DOE disagrees
with Burnham's comment that the tolerance range for determining a
stabilized supply water temperature could not be met under a specific
control strategy, such as the boost mode where an extended call for
heating occurs until the heat demand is satisfied. In such a case,
DOE's test method would be implemented when either the heat demand is
satisfied or the high boiler water temperature limit is reached.
As discussed in the March 2015 NOPR, DOE also adds a definition for
``controlling parameter.'' DOE has placed this definition in 10 CFR
430.2 rather than appendix N as it applies to DOE enforcement
regulations rather than manufacturer testing. Controlling parameter is
defined as a measurable quantity for a residential boiler (such as
temperature or usage pattern) used for inferring heating load, which
would then result in incremental changes in supply water temperature.
2. Compliance Dates for the Amended Test Procedure
This document amends 10 CFR 429.18, 10 CFR 429.134, 10 CFR 430.2,
10 CFR 430.3, 10 CFR 430.23, and 10 CFR part 430, subpart B, appendix
N. When DOE modifies test procedures, it must determine to what extent,
if any, the new test procedure would alter the measured energy
efficiency or energy use of any covered product. (42 U.S.C. 6293(e)(1))
For the reasons described previously, DOE has determined that none of
the test procedure amendments would alter the measured energy
efficiency or energy use of the covered products that are the subject
of this rulemaking. The changes made to appendix N through this final
rule, as listed in section III.D, clarify the manner in which the test
is conducted, or otherwise represent minor changes or additions to the
test or reporting requirements that do not affect measured energy use.
Therefore, these amendments become effective 30 days after publication
of this final rule in the Federal Register. Pursuant to 42 U.S.C.
6293(c)(2), 180 days after DOE prescribes or establishes a new or
amended test procedure, manufacturers must make representations of
energy efficiency, including certifications of compliance, using that
new or amended test procedure.
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget (OMB) has determined that test
procedure rulemakings do not constitute ``significant regulatory
actions'' under section 3(f) of Executive Order 12866, ``Regulatory
Planning and Review,'' 58 FR 51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under the Executive Order by the
Office of Information and Regulatory Affairs (OIRA) in OMB.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq., as amended by
the Small Business Regulatory Fairness Act of 1996) requires
preparation of an initial regulatory flexibility analysis (IRFA) for
any rule that by law must be proposed for public comment, unless the
agency certifies that the rule, if promulgated, will not have a
significant economic impact on a substantial number of small entities.
As required by Executive Order 13272, ``Proper Consideration of Small
Entities in Agency Rulemaking,'' 67 FR 53461 (August 16, 2002), DOE
published procedures and policies on February 19, 2003, to ensure that
the potential impacts of its rules on small entities are properly
considered during the DOE rulemaking process. 68 FR 7990. DOE has made
its procedures and policies available on the Office of the General
Counsel's Web site: https://energy.gov/gc/office-general-counsel.
DOE reviewed this final rule under the provisions of the Regulatory
Flexibility Act and the procedures and policies published on February
19, 2003. 68 FR 7990. This final rule amends DOE's test procedure by
providing clarifications regarding relevant test procedure provisions
and revising the definitions of some terms. DOE has concluded that this
final rule will not have a significant impact on a substantial number
of small entities. The factual basis for this certification is as
follows:
[[Page 2643]]
The Small Business Administration (SBA) considers a business entity
to be a small business if, together with its affiliates, it employs
less than a threshold number of workers specified in 13 CFR part 121.
These size standards and codes are established by the North American
Industry Classification System (NAICS) and are available at https://www.sba.gov/sites/default/files/files/Size_Standards_Table.pdf.
Residential boiler manufacturing is classified under NAICS 333414,
``Heating Equipment (Except Warm Air Furnaces) Manufacturing,'' for
which the maximum size threshold is 500 employees or fewer. Residential
furnace manufacturing is classified under NAICS 333415, ``Air-
conditioning and warm air heating equipment and commercial and
industrial refrigeration equipment manufacturing'' for which the
maximum size threshold is 750 employees or fewer. To estimate the
number of companies that could be small business manufacturers of
products covered by this rulemaking, DOE conducted a market survey
using available public information to identify potential small
manufacturers. DOE's research involved reviewing several industry trade
association membership directories (e.g., AHRI \16\), SBA
databases,\17\ individual company Web sites, and marketing research
tools (e.g., Hoovers \18\ reports) to create a list of all domestic
small business manufacturers of residential furnaces and boilers
covered by this rulemaking.
---------------------------------------------------------------------------
\16\ For more information on the boiler and furnace directories,
see https://www.ahridirectory.org/ahridirectory/pages/home.aspx.
\17\ For more information see: https://dsbs.sba.gov/dsbs/search/dsp_dsbs.cfm.
\18\ For more information see: https://www.hoovers.com/.
---------------------------------------------------------------------------
After DOE identified manufacturers of residential furnaces and
consumer boilers, DOE then consulted publically-available data and
contacted companies, as necessary, to determine if they both meet the
SBA's definition of a ``small business'' manufacturer and have their
manufacturing facilities located within the United States. DOE screened
out companies that did not offer products covered by this rulemaking,
did not meet the definition of a ``small business,'' or are foreign-
owned and operated. Based on this analysis, DOE identified 9 small
businesses that manufacture residential furnaces and 9 small businesses
that manufacture residential boilers (two of which also manufacture
residential furnaces), for a total of 16 small businesses potentially
impacted by this rulemaking.
This document amends DOE's test procedure by incorporating several
changes that modify the existing test procedure or reporting
requirements for furnaces and boilers. This includes the following
changes that could potentially impact manufacturers: (1) Clarified
definition of electrical power term PE; (2) a smoke stick method for
determining whether the minimum default draft factor may be used; (3) a
provision to allow for the measurement of condensate under steady-state
conditions; (4) reference to manufacturers' I&O manuals; (5)
specification of ductwork for units that are installed without a return
duct; (6) specification of testing requirements for multi-position
units; (7) revised reporting precision for AFUE to the nearest tenth of
a percentage point; and (8) requirement to report the use of a burner
delay automatic means control strategy in certification reports. The
estimated costs of testing/rating and potential impact to manufacturer
burden resulting from use of the amended test procedure are discussed
subsequently. The estimated costs and potential impacts apply to all
manufacturers, including the manufacturers identified as small
businesses.
DOE believes that explicitly listing the components encompassed in
the definition of PE does not change the definition of the electrical
power term PE but rather only clarifies it, and will not impose any
additional test burden.
The adoption of the smoke stick method for determining whether the
minimum default draft factor may be used is intended to reduce the test
burden to manufacturers. DOE estimated that the smoke stick method for
determining the minimum default draft factor would reduce the overall
duration of the test by about 15 minutes for units designed to have no
flow through the heat exchanger. However, DOE does not have sufficient
information to support estimating the fraction of units that have been
designed such that there is no flow through the heat exchanger.
Therefore, DOE has not included the cost savings associated with the
smoke stick.
The addition of the optional provision to allow for the measurement
of condensate prior to the establishment of steady state conditions
will result in a lowering of test burden for manufacturers of
condensing furnaces and boilers. Manufacturers of condensing furnaces
and boilers will benefit from the time and labor savings attributed to
the measurement of condensate during the establishment of steady-state
conditions. However, DOE does not have sufficient information to
support estimating the fraction of units that would be tested under the
optional provision. Therefore, DOE has not included the cost savings
associated with the optional provision to allow for the measurement of
condensate prior to the establishment of steady state conditions.
The clarification of duct work requirements for units that are
installed without a return duct and clarification of the test
requirements for multi-position units do not present any additional
test burden to manufacturers, as the two amendments do not change the
existing testing requirements or conflict with current industry
practice.
Revision of AFUE reporting precision and the requirement to report
the use of a burner delay automatic means control strategy in the
certification report do not present any additional test burden to
manufacturers, as the two amendments do not change testing
requirements. However, both amendments may require some manufacturers
to submit new certification reports and relabel their products. DOE
estimates that for affected parties, submitting new certification
reports and relabeling products will take 30 minutes per unit. At an
assumed cost of $40 per hour, the cost to recertify and relabel is $20
per unit.
To determine the potential cost of the test procedure amendments on
small furnace and boiler manufacturers, DOE estimated the cost of
recertifying and relabeling per basic model and the savings from the
optional provision to measure condensate during the establishment of
steady state conditions, as described above. DOE estimated that on
average, each furnace small business would have 51 basic models, and
each boiler small business would have 70 basic models. Based on
residential furnace and boiler model data, DOE assumed that
approximately 70 percent of all furnace and 60 percent of all boiler
manufacturers will need to recertify and relabel due to the revision of
the AFUE reporting precision. Based on residential boiler model data,
DOE assumed that about 75 percent of boilers are single-stage boilers;
furthermore, DOE assumed that about two-thirds of single-stage boilers
employ a burner delay automatic means control strategy. Thus, DOE
assumed that half of all boiler models will employ a burner delay
automatic means control strategy. The additional recertification and
relabeling cost associated with the test procedure amendments was
multiplied by the estimated fraction of affected basic models produced
by a small manufacturer. DOE has estimated a total added cost from the
test procedure amendments of $714 per furnace
[[Page 2644]]
manufacturer and a total added cost of about $1,120 per boiler
manufacturer for manufacturers that currently do not report AFUE to the
nearest tenth of a percentage point or for manufacturers of single-
stage boilers that employ a burner delay automatic means control
strategy.
For the reasons stated previously, DOE certifies that this rule
will not have a significant economic impact on a substantial number of
small entities.
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of residential furnaces and boilers must certify to
DOE that their products comply with all applicable energy conservation
standards. In certifying compliance with applicable performance
standards, manufacturers must test their products according to the DOE
test procedures for residential furnaces and boilers, including any
amendments adopted for those test procedures. Manufacturers must also
ensure their products comply with applicable design standards. DOE has
established regulations for the certification and recordkeeping
requirements for all covered consumer products and commercial
equipment, including residential furnaces and boilers. See generally 10
CFR part 429. The collection-of-information requirement for
certification and recordkeeping is subject to review and approval by
OMB under the Paperwork Reduction Act (PRA). This requirement has been
approved by OMB under OMB control number 1910-1400. Public reporting
burden for the certification is estimated to average 30 hours per
response, including the time for reviewing instructions, searching
existing data sources, gathering and maintaining the data needed, and
completing and reviewing the collection of information.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
In this final rule, DOE amends its test procedure for residential
furnaces and boilers. DOE has determined that this rule falls into a
class of actions that are categorically excluded from review under the
National Environmental Policy Act of 1969 (42 U.S.C. 4321 et seq.) and
DOE's implementing regulations at 10 CFR part 1021. Specifically, this
rule amends an existing rule without affecting the amount, quality or
distribution of energy usage, and, therefore, will not result in any
environmental impacts. Thus, this rulemaking is covered by Categorical
Exclusion A5 under 10 CFR part 1021, subpart D, which applies to any
rulemaking that interprets or amends an existing rule without changing
the environmental effect of that rule. Accordingly, neither an
environmental assessment nor an environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 10,
1999) imposes certain requirements on agencies formulating and
implementing policies or regulations that preempt State law or that
have Federalism implications. The Executive Order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States, and
to carefully assess the necessity for such actions. The Executive Order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have Federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. 65 FR 13735. DOE examined this final
rule and determined that it will not have a substantial direct effect
on the States, on the relationship between the national government and
the States, or on the distribution of power and responsibilities among
the various levels of government. EPCA governs and prescribes Federal
preemption of State regulations as to energy conservation for the
products that are the subject of this final rule. States can petition
DOE for exemption from such preemption to the extent, and based on
criteria, set forth in EPCA. (42 U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
Eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically requires that Executive agencies make every reasonable
effort to ensure that the regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly specifies any effect on existing
Federal law or regulation; (3) provides a clear legal standard for
affected conduct while promoting simplification and burden reduction;
(4) specifies the retroactive effect, if any; (5) adequately defines
key terms; and (6) addresses other important issues affecting clarity
and general draftsmanship under any guidelines issued by the Attorney
General. Section 3(c) of Executive Order 12988 requires Executive
agencies to review regulations in light of applicable standards in
sections 3(a) and 3(b) to determine whether they are met or it is
unreasonable to meet one or more of them. DOE has completed the
required review and determined that, to the extent permitted by law,
this final rule meets the relevant standards of Executive Order 12988.
G. Review under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (UMRA)
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. Public Law 104-4, sec. 201 (codified at 2 U.S.C. 1531).
For a regulatory action resulting in a rule that may cause the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector of $100 million or more in any one year
(adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The UMRA also requires a Federal agency to
develop an effective process to permit timely input by elected officers
of State, local, and Tribal governments on a proposed ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect small governments. On March 18, 1997,
DOE published a statement of policy on its process for
intergovernmental consultation under UMRA. 62 FR 12820. (This policy is
also available at https://energy.gov/gc/office-general-counsel). DOE
examined this final rule according to UMRA and its statement of policy
and determined that the rule
[[Page 2645]]
contains neither an intergovernmental mandate, nor a mandate that may
result in the expenditure of $100 million or more in any year, so these
requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This rule will not have any impact on the autonomy or integrity of the
family as an institution. Accordingly, DOE has concluded that it is not
necessary to prepare a Family Policymaking Assessment.
I. Review Under Executive Order 12630
Pursuant to Executive Order 12630, ``Governmental Actions and
Interference with Constitutionally Protected Property Rights,'' 53 FR
8859 (March 18, 1988), DOE has determined that this regulation will not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (Feb. 22, 2002), and
DOE's guidelines were published at 67 FR 62446 (Oct. 7, 2002). DOE has
reviewed this final rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OMB,
a Statement of Energy Effects for any significant energy action. A
``significant energy action'' is defined as any action by an agency
that promulgated or is expected to lead to promulgation of a final
rule, and that: (1) Is a significant regulatory action under Executive
Order 12866, or any successor order; and (2) is likely to have a
significant adverse effect on the supply, distribution, or use of
energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any significant energy action, the
agency must give a detailed statement of any adverse effects on energy
supply, distribution, or use if the regulation is implemented, and of
reasonable alternatives to the action and their expected benefits on
energy supply, distribution, and use.
This regulatory action is not a significant regulatory action under
Executive Order 12866. Moreover, it would not have a significant
adverse effect on the supply, distribution, or use of energy, nor has
it been designated as a significant energy action by the Administrator
of OIRA. Therefore, it is not a significant energy action, and,
accordingly, DOE has not prepared a Statement of Energy Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of the
Federal Energy Administration Act of 1974, as amended by the Federal
Energy Administration Authorization Act of 1977 (Pub. L. 95-70). (15
U.S.C. 788; FEAA) Section 32 essentially provides in relevant part
that, where a proposed rule authorizes or requires use of commercial
standards, the notice of proposed rulemaking must inform the public of
the use and background of such standards. In addition, section 32(c)
requires DOE to consult with the Attorney General and the Chairman of
the Federal Trade Commission (FTC) concerning the impact of the
commercial or industry standards on competition.
This final rule incorporates testing methods contained in the
following commercial standard: ASTM D2156-09 (Reapproved 2013). While
this test procedure is not exclusively based on this standard, the DOE
test procedure adopts several provisions from this standard without
amendment. DOE has evaluated this standard and is unable to conclude
whether it fully complies with the requirements of section 32(b) of the
FEAA (i.e., that it was developed in a manner that fully provides for
public participation, comment, and review). DOE has consulted with the
Attorney General and the Chairwoman of the FTC concerning the impact of
these test procedures on competition and has received no comments
objecting to their use.
M. Description of Materials Incorporated by Reference
In this final rule, DOE incorporates by reference the ASTM test
standard ``Standard Test Method for Smoke Density in Flue Gases from
Burning Distillate Fuels,'' ASTM D2156-09 (Reapproved 2013). ASTM D2156
is an industry accepted test procedure that establishes uniform test
methods for the evaluation of smoke density in the flue gases from
burning distillate fuels. The test procedure established in this final
rule references ASTM D2156 in its entirety, which includes terminology,
methods of testing, materials, apparatus, procedures, reporting, and
precision and bias, to determine the allowable smoke in the flue of oil
furnaces and boilers. ASTM D2156-09 is available on ASTM's Web site at
https://www.astm.org/Standards/D2156.htm.
N. Congressional Notification
As required by 5 U.S.C. 801, DOE will report to Congress on the
promulgation of this rule prior to its effective date. The report will
state that it has been determined that the rule is not a ``major rule''
as defined by 5 U.S.C. 804(2).
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this final
rule.
List of Subjects
10 CFR Part 429
Confidential business information, Energy conservation, Household
appliances, Imports, Reporting and recordkeeping requirements.
10 CFR Part 430
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Incorporation by reference, Intergovernmental relations, Small
businesses.
Issued in Washington, DC, on December 29, 2015.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
For the reasons stated in the preamble, DOE amends parts 429 and
430 of chapter II, subchapter D of title 10, Code of Federal
Regulations, as set forth below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317.
[[Page 2646]]
0
2. Amend Sec. 429.18 by adding paragraphs (a)(2)(vii) and (b)(4) to
read as follows:
Sec. 429.18 Residential furnaces.
(a) * * *
(2) * * *
(vii) Reported values. The represented value of annual fuel
utilization efficiency must be truncated to the one-tenth of a
percentage point.
(b) * * *
(4) For multi-position furnaces, the annual fuel utilization
efficiency (AFUE) reported for each basic model must be based on
testing in the least efficient configuration. Manufacturers may also
report and make representations of additional AFUE values based on
testing in other configurations.
0
3. Amend Sec. 429.134 by adding paragraph (h) to read as follows:
Sec. 429.134 Product-specific enforcement provisions
* * * * *
(h) Residential boilers--test protocols for functional verification
of automatic means for adjusting water temperature. These tests are
intended to verify the functionality of the design requirement that a
boiler has an automatic means for adjusting water temperature for
single-stage, two-stage, and modulating boilers. These test methods are
intended to permit the functional testing of a range of control
strategies used to fulfill this design requirement. Section 2,
Definitions, and paragraph 6.1.a of appendix N to subpart B of part 430
of this chapter apply for the purposes of this paragraph (h).
(1) Test protocol for all products other than single-stage products
employing burner delay. This test is intended to verify whether an
automatic means for adjusting water temperature other than burner delay
produces an incremental change in water supply temperature in response
to an incremental change in inferred heat load.
(i) Boiler setup--(A) Boiler installation. Boiler installation in
the test room shall be in accordance with the setup and apparatus
requirements of section 6 of appendix N to subpart B of 10 CFR part
430.
(B) Establishing flow rate and temperature rise. Start the boiler
without enabling the means for adjusting water temperature. Establish a
water flow rate that allows for a water temperature rise of greater
than or equal to 20[emsp14][deg]F at maximum input rate.
(C) Temperature stabilization. Temperature stabilization is deemed
to be obtained when the boiler supply water temperature does not vary
by more than 3[emsp14][deg]F over a period of five minutes.
(D) Adjust the inferential load controller. (1) Adjust the boiler
controls (in accordance with the I&O manual) to the default setting
that allows for activation of the means for adjusting water
temperature. For boiler controls that do not allow for control
adjustment during active mode operation, terminate call for heat and
adjust the inferential load controller in accordance with the I&O
manual and then reinitiate call for heat.
(2) If the means for adjusting water temperature uses outdoor
temperature reset, the maximum outdoor temperature setting (if
equipped) should be set to a temperature high enough that the boiler
operates continuously during the duration of this test (i.e., if the
conditions in paragraph (h)(1)(ii)(A) of this section equal room
ambient temperature, then the maximum outdoor temperature should be set
at a temperature greater than the ambient air temperature during the
test).
(ii) Establish low inferred load conditions at minimum boiler
supply water temperature--(A) Establish low inferred load conditions.
(1) Establish the inferred load conditions (simulated using a
controlling parameter, such as outdoor temperature, thermostat
patterns, or boiler cycling) so that the supply water temperature is
maintained at the minimum supply water temperature prescribed by the
boiler manufacturer's temperature reset control strategy found in the
I&O manual.
(2) The minimum supply water temperature of the default temperature
reset curve is usually provided in the I&O manual. If there is no
recommended minimum supply water temperature, set the minimum supply
water temperature equal to 20 [deg]F less than the high supply water
temperature specified in paragraph (h)(1)(iii)(A) of this section.
(B) Supply water temperature stabilization at low inferred load.
(1) Maintain the call for heat until the boiler supply water
temperature has stabilized. Temperature stabilization is deemed to be
obtained when the boiler supply water temperature does not vary by more
than 3 [deg]F over a period of five minutes. The duration
of time required to stabilize the supply water, following the procedure
in paragraph (h)(1)(ii)(A) of this section, is dependent on the reset
strategy and may vary from model to model.
(2) Record the boiler supply water temperature while the
temperature is stabilized.
(iii) Establish high inferred load conditions at maximum boiler
supply water temperature--(A) Establish high inferred load conditions.
Establish the inferred load conditions so that the supply water
temperature is set to the maximum allowable supply water temperature as
prescribed in the I&O manual, or if there is no recommendation, set to
a temperature greater than 170 [deg]F.
(B) Supply water temperature stabilization at high inferred load.
(1) Maintain the call for heat until the boiler supply water
temperature has stabilized. Temperature stabilization is deemed to be
obtained when the boiler supply water temperature does not vary by more
than 3[emsp14][deg]F over a period of five minutes. The
duration of time required to stabilize the supply water, following the
procedure in paragraph (h)(1)(iii)(A) of this section, is dependent on
the reset strategy and may vary from model to model.
(2) Record the boiler supply water temperature while the
temperature is stabilized.
(3) Terminate the call for heat.
(iv) [Reserved]
(2) Test protocol for single-stage products employing burner delay.
This test will be used in place of paragraph (h)(1) of this section for
products manufacturers have certified to DOE under Sec. 429.18(b)(3)
as employing a burner delay automatic means strategy. This test
verifies whether the automatic means in single-stage boiler products
establishes a burner delay upon a call for heat until the means has
determined that the inferred heat load cannot be met by the residual
heat of the water in the system.
(i) Boiler setup--(A) Boiler installation. Boiler installation in
the test room shall be in accordance with the setup and apparatus
requirements by section 6.0 of appendix N to subpart B of 10 CFR part
430.
(B) Activation of controls. Adjust the boiler controls in
accordance with the I&O manual at the default setting that allows for
activation of the means for adjusting water temperature.
(C) Adjustment of water flow and temperature. The flow and
temperature of inlet water to the boiler shall be capable of being
adjusted manually.
(ii) Boiler heat-up--(A) Boiler start-up. Power up the boiler and
initiate a call for heat.
(B) Adjustment of firing rate. Adjust the boiler's firing rate to
within 5% of its maximum rated input.
(C) Establishing flow rate and temperature rise. Adjust the water
flow through the boiler to achieve a [Delta]T of 20[emsp14][deg]F
(2 [deg]F) or greater with an inlet water temperature equal
to 140[emsp14][deg]F (2[emsp14][deg]F).
[[Page 2647]]
(D) Terminate the call for heating. Terminate the call for heat,
stop the flow of water through the boiler, and record the time at
termination.
(iii) Verify burner delay--(A) Reinitiate call for heat. Within
three (3) minutes of termination (paragraph (h)(2)(ii)(D) of this
section) and without adjusting the inlet water flow rate or temperature
as specified in paragraph (h)(2)(ii)(C) of this section, reinitiate the
call for heat and water flow and record the time.
(B) Verify burner ignition. At 15-second intervals, record time and
supply water temperature until the main burner ignites.
(C) Terminate the call for heat.
(iv) [Reserved]
PART 430--ENERGY CONSERVATION PROGRAM FOR CONSUMER PRODUCTS
0
4. The authority citation for part 430 continues to read as follows:
Authority: 42 U.S.C. 6291-6309; 28 U.S.C. 2461 note.
0
5. Amend Sec. 430.2 by adding in alphabetical order a definition of
``Controlling parameter'' and revising the definition of ``Furnace'' to
read as follows:
Sec. 430.2 Definitions.
* * * * *
Controlling parameter means a measurable quantity or an algorithm
(such as temperature or usage pattern) used for inferring heating load
to a residential boiler, which would then result in incremental changes
in boiler supply water temperature.
* * * * *
Furnace means a product which utilizes only single-phase electric
current, or single-phase electric current or DC current in conjunction
with natural gas, propane, or home heating oil, and which--
(1) Is designed to be the principal heating source for the living
space of a residence;
(2) Is not contained within the same cabinet with a central air
conditioner whose rated cooling capacity is above 65,000 Btu per hour;
(3) Is an electric central furnace, electric boiler, forced-air
central furnace, gravity central furnace, or low-pressure steam or hot
water boiler; and
(4) Has a heat input rate of less than 300,000 Btu per hour for
electric boilers and low-pressure steam or hot water boilers and less
than 225,000 Btu per hour for forced-air central furnaces, gravity
central furnaces, and electric central furnaces.
* * * * *
0
6. Amend Sec. 430.3 by revising paragraph (g)(11) and adding paragraph
(j)(2) to read as follows:
Sec. 430.3 Materials incorporated by reference.
* * * * *
(g) * * *
(11) ANSI/ASHRAE Standard 103-1993, (``ASHRAE 103-1993''), Methods
of Testing for Annual Fuel Utilization Efficiency of Residential
Central Furnaces and Boilers, (with Errata of October 24, 1996), except
for sections 7.1, 7.2.2.2, 7.2.2.5, 7.2.3.1, 7.8, 8.2.1.3, 8.3.3.1,
8.4.1.1, 8.4.1.1.2, 8.4.1.2, 8.4.2.1.4, 8.4.2.1.6, 8.6.1.1, 8.7.2,
8.8.3, 9.1.2.2.1, 9.1.2.2.2, 9.5.1.1, 9.5.1.2.1, 9.5.1.2.2, 9.5.2.1,
9.7.1, 9.7.4, 9.7.6, 9.10, 11.5.11.1, 11.5.11.2 and appendices B and C,
approved October 4, 1993, IBR approved for Sec. 430.23 and appendix N
to subpart B.
* * * * *
(j) * * *
(2) ASTM D2156-09 (Reapproved 2013) (``ASTM D2156R13''), Standard
Test Method for Smoke Density in Flue Gases from Burning Distillate
Fuels, approved October 1, 2013, IBR approved for appendix N to subpart
B.
* * * * *
0
7. Amend Sec. 430.23 by revising paragraph (n)(2) to read as follows:
Sec. 430.23 Test procedures for the measurement of energy and water
consumption.
* * * * *
(n) * * *
(2) The annual fuel utilization efficiency for furnaces, expressed
in percent, is the ratio of the annual fuel output of useful energy
delivered to the heated space to the annual fuel energy input to the
furnace determined according to section 10.1 of appendix N of this
subpart for gas and oil furnaces and determined in accordance with
section 11.1 of the American National Standards Institute/American
Society of Heating, Refrigerating, and Air-Conditioning Engineers
(ANSI/ASHRAE) Standard 103-1993 (incorporated by reference, see Sec.
430.3) for electric furnaces. Truncate the annual fuel utilization
efficiency to one-tenth of a percentage point.
* * * * *
0
8. Revise appendix N to subpart B to read as follows:
Appendix N to Subpart B of Part 430--Uniform Test Method for Measuring
the Energy Consumption of Furnaces and Boilers
Note: Prior to July 13, 2016, representations with respect to
the energy use or efficiency of residential furnaces and boilers,
including compliance certifications, must be based on testing
conducted in accordance with either this appendix as it now appears
or appendix N as it appeared at 10 CFR part 430, subpart B revised
as of January 1, 2016.
After July 13, 2016, representations with respect to energy use
or efficiency of residential furnaces and boilers, including
compliance certifications, must be based on testing conducted in
accordance with this appendix.
1.0 Scope. The scope of this appendix is as specified in section
2 of ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3).
For purposes of this appendix, the Department of Energy
incorporates by reference several industry standards, either in
whole or in part, as listed in Sec. 430.3. In cases where there is
a conflict, the language of the test procedure in this appendix
takes precedence over the incorporated standards.
2.0 Definitions. Definitions include those specified in section
3 of ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3)
and the following additional and modified definitions.
2.1 Active mode means the condition in which the furnace or
boiler is connected to the power source, and at least one of the
burner, electric resistance elements, or any electrical auxiliaries
such as blowers or pumps, are activated.
2.2 Boiler pump means a pump installed on a boiler and that is
separate from the circulating water pump.
2.3 Control means a device used to regulate the operation of a
piece of equipment and the supply of fuel, electricity, air, or
water.
2.4 Draft inducer means a fan incorporated in the furnace or
boiler that either draws or forces air into the combustion chamber.
2.5 Gas valve means an automatic or semi-automatic device
consisting essentially of a valve and operator that controls the gas
supply to the burner(s) during normal operation of an appliance. The
operator may be actuated by application of gas pressure on a
flexible diaphragm, by electrical means, by mechanical means or by
other means.
2.6 Installation and operation (I&O) manual means instructions
for installing, commissioning, and operating the furnace or boiler,
which are supplied with the product when shipped by the
manufacturer.
2.7 Isolated combustion system means a system where a unit is
installed within the structure, but isolated from the heated space.
A portion of the jacket heat from the unit is lost, and air for
ventilation, combustion and draft control comes from outside the
heated space.
2.8 Multi-position furnace means a furnace that can be installed
in more than one airflow configuration (i.e., upflow or horizontal;
downflow or horizontal; upflow or downflow; and upflow, or downflow,
or horizontal).
2.9 Off mode means a mode in which the furnace or boiler is
connected to a mains power source and is not providing any active
mode or standby mode function, and where the mode may persist for an
indefinite time. The existence of an off switch in off position
[[Page 2648]]
(a disconnected circuit) is included within the classification of
off mode.
2.10 Off switch means the switch on the furnace or boiler that,
when activated, results in a measurable change in energy consumption
between the standby and off modes.
2.11 Oil control valve means an automatically or manually
operated device consisting of an oil valve for controlling the fuel
supply to a burner to regulate burner input.
2.12 Standby mode means any mode in which the furnace or boiler
is connected to a mains power source and offers one or more of the
following space heating functions that may persist:
a. To facilitate the activation of other modes (including
activation or deactivation of active mode) by remote switch
(including thermostat or remote control), internal or external
sensors, or timer;
b. Continuous functions, including information or status
displays or sensor based functions.
2.13 Thermal stack damper means a type of stack damper that
relies exclusively upon the changes in temperature in the stack
gases to open or close the damper.
3.0 Classifications. Classifications are as specified in section
4 of ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3).
4.0 Requirements. Requirements are as specified in section 5 of
ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3).
5.0 Instruments. Instruments must be as specified in section 6
of ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3).
6.0 Apparatus. The apparatus used in conjunction with the
furnace or boiler during the testing must be as specified in section
7 of ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3)
except for sections 7.1, 7.2.2.2, 7.2.2.5, 7.2.3.1, and 7.8; and as
specified in sections 6.1 through 6.5 of this appendix.
6.1 General.
a. Install the furnace or boiler in the test room in accordance
with the I&O manual, as defined in section 2.6 of this appendix,
except that if provisions within this appendix are specified, then
the provisions herein drafted and prescribed by DOE govern. If the
I&O manual and any additional provisions of this appendix are not
sufficient for testing a furnace or boiler, the manufacturer must
request a waiver from the test procedure pursuant to 10 CFR 430.27.
b. If the I&O manual indicates the unit should not be installed
with a return duct, then the return (inlet) duct specified in
section 7.2.1 of ASHRAE 103-1993 (incorporated by reference, see
Sec. 430.3) is not required.
c. Test multi-position furnaces in the least efficient
configuration. Testing of multi-position furnaces in other
configurations is permitted if energy use or efficiency is
represented pursuant to the requirements in 10 CFR part 429.
d. The apparatuses described in section 6 of this appendix are
used in conjunction with the furnace or boiler during testing. Each
piece of apparatus shall conform to material and construction
specifications listed in this appendix and in ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3), and the reference
standards cited in this appendix and in ASHRAE 103-1993.
e. Test rooms containing equipment must have suitable facilities
for providing the utilities (including but not limited to
environmental controls, sufficient fluid source(s), applicable
measurement equipment, and any other technology or tools) necessary
for performance of the test and must be able to maintain conditions
within the limits specified in section 6 of this appendix.
6.2 Forced-air central furnaces (direct vent and direct
exhaust).
a. Units not equipped with a draft hood or draft diverter must
be provided with the minimum-length vent configuration recommended
in the I&O manual or a 5-ft flue pipe if there is no recommendation
provided in the I&O manual (see Figure 4 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3)). For a direct exhaust
system, insulate the minimum-length vent configuration or the 5-ft
flue pipe with insulation having an R-value not less than 7 and an
outer layer of aluminum foil. For a direct vent system, see section
7.5 of ASHRAE 103-1993 for insulation requirements.
b. For units with power burners, cover the flue collection box
with insulation having an R-value of not less than 7 and an outer
layer of aluminum foil before the cool-down and heat-up tests
described in sections 9.5 and 9.6 of ASHRAE 103-1993 (incorporated
by reference, see Sec. 430.3), respectively. However, do not apply
the insulation for the jacket loss test (if conducted) described in
section 8.6 of ASHRAE 103-1993 or the steady-state test described in
section 9.1 of ASHRAE 103-1993.
c. For power-vented units, insulate the shroud surrounding the
blower impeller with insulation having an R-value of not less than 7
and an outer layer of aluminum foil before the cool-down and heat-up
tests described in sections 9.5 and 9.6, respectively, of ASHRAE
103-1993 (incorporated by reference, see Sec. 430.3). Do not apply
the insulation for the jacket loss test (if conducted) described in
section 8.6 of ASHRAE 103-1993 or the steady-state test described in
section 9.1 of ASHRAE 103-1993. Do not insulate the blower motor or
block the airflow openings that facilitate the cooling of the
combustion blower motor or bearings.
6.3 Downflow furnaces. Install an internal section of vent pipe
the same size as the flue collar for connecting the flue collar to
the top of the unit, if not supplied by the manufacturer. Do not
insulate the internal vent pipe during the jacket loss test (if
conducted) described in section 8.6 of ASHRAE 103-1993 (incorporated
by reference, see Sec. 430.3) or the steady-state test described in
section 9.1 of ASHRAE 103-1993. Do not insulate the internal vent
pipe before the cool-down and heat-up tests described in sections
9.5 and 9.6, respectively, of ASHRAE 103-1993. If the vent pipe is
surrounded by a metal jacket, do not insulate the metal jacket.
Install a 5-ft test stack of the same cross-sectional area or
perimeter as the vent pipe above the top of the furnace. Tape or
seal around the junction connecting the vent pipe and the 5-ft test
stack. Insulate the 5-ft test stack with insulation having an R-
value not less than 7 and an outer layer of aluminum foil. (See
Figure 3-E of ASHRAE 103-1993.)
6.4 Units with draft hoods or draft diverters. Install the stack
damper in accordance with the I&O manual. Install 5 feet of stack
above the damper.
a. For units with an integral draft diverter, cover the 5-ft
stack with insulation having an R-value of not less than 7 and an
outer layer of aluminum foil.
b. For units with draft hoods, insulate the flue pipe between
the outlet of the furnace and the draft hood with insulation having
an R-value of not less than 7 and an outer layer of aluminum foil.
c. For units with integral draft diverters that are mounted in
an exposed position (not inside the overall unit cabinet), cover the
diverter boxes (excluding any openings through which draft relief
air flows) before the beginning of any test (including jacket loss
test) with insulation having an R-value of not less than 7 and an
outer layer of aluminum foil.
d. For units equipped with integral draft diverters that are
enclosed within the overall unit cabinet, insulate the draft
diverter box with insulation as described in section 6.4.c before
the cool-down and heat-up tests described in sections 9.5 and 9.6,
respectively, of ASHRAE 103-1993 (incorporated by reference, see
Sec. 430.3). Do not apply the insulation for the jacket loss test
(if conducted) described in section 8.6 of ASHRAE 103-1993 or the
steady-state test described in section 9.1 of ASHRAE 103-1993.
6.5 Condensate collection. Attach condensate drain lines to the
unit as specified in the I&O manual. Maintain a continuous downward
slope of drain lines from the unit. Additional precautions (such as
eliminating any line configuration or position that would otherwise
restrict or block the flow of condensate or checking to ensure a
proper connection with condensate drain spout that allows for
unobstructed flow) must be taken to facilitate uninterrupted flow of
condensate during the test. Collection containers must be glass or
polished stainless steel to facilitate removal of interior deposits.
The collection container must have a vent opening to the atmosphere.
7.0 Testing conditions. The testing conditions must be as
specified in section 8 of ASHRAE 103-1993 (incorporated by
reference, see Sec. 430.3), except for section 8.2.1.3, 8.3.3.1,
8.4.1.1, 8.4.1.1.2, 8.4.1.2, 8.4.2.1.4, 8.4.2.1.6, 8.6.1.1, 8.7.2,
and 8.8.3; and as specified in sections 7.1 to 7.10 of this
appendix, respectively.
7.1 Fuel supply, gas. In conducting the tests specified herein,
gases with characteristics as shown in Table 1 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3) shall be used. Maintain
the gas supply, ahead of all controls for a furnace, at a test
pressure between the normal and increased values shown in Table 1 of
ASHRAE 103-1993. Maintain the regulator outlet pressure at a level
approximating that recommended in the I&O
[[Page 2649]]
manual, as defined in section 2.6 of this appendix, or, in the
absence of such recommendation, to the nominal regulator settings
used when the product is shipped by the manufacturer. Use a gas
having a specific gravity as shown in Table 1 of ASHRAE 103-1993 and
with a higher heating value within 5% of the higher
heating value shown in Table 1 of ASHRAE 103-1993. Determine the
actual higher heating value in Btu per standard cubic foot for the
gas to be used in the test within an error no greater than 1%.
7.2 Installation of piping. Install piping equipment in
accordance with the I&O manual. In the absence of such
specification, install piping in accordance with section 8.3.1.1 of
ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3).
7.3 Gas burner. Adjust the burners of gas-fired furnaces and
boilers to their maximum Btu input ratings at the normal test
pressure specified by section 7.1 of this appendix. Correct the
burner input rate to reflect gas characteristics at a temperature of
60 [deg]F and atmospheric pressure of 30 in of Hg and adjust down to
within 2 percent of the hourly Btu nameplate input
rating specified by the manufacturer as measured during the steady-
state performance test in section 8 of this appendix. Set the
primary air shutters in accordance with the I&O manual to give a
good flame at this condition. If, however, the setting results in
the deposit of carbon on the burners during any test specified
herein, the tester shall adjust the shutters and burners until no
more carbon is deposited and shall perform the tests again with the
new settings (see Figure 9 of ASHRAE 103-1993 (incorporated by
reference, see Sec. 430.3)). After the steady-state performance
test has been started, do not make additional adjustments to the
burners during the required series of performance tests specified in
section 9 of ASHRAE 103-1993. If a vent-limiting means is provided
on a gas pressure regulator, keep it in place during all tests.
7.4 Modulating gas burner adjustment at reduced input rate. For
gas-fired furnaces and boilers equipped with modulating-type
controls, adjust the controls to operate the unit at the nameplate
minimum input rate. If the modulating control is of a non-automatic
type, adjust the control to the setting recommended in the I&O
manual. In the absence of such recommendation, the midpoint setting
of the non-automatic control shall be used as the setting for
determining the reduced fuel input rate. Start the furnace or boiler
by turning the safety control valve to the ``ON'' position. For
boilers, use a supply water temperature that will allow for
continuous operation without shutoff by the control. If necessary to
achieve such continuous operation, supply water may be increased
above 120 [deg]F; in such cases, gradually increase the supply water
temperature to determine what minimum supply water temperature, with
a 20 [deg]F temperature rise across the boiler, will be needed to
adjust for the minimum input rate at the reduced input rate control
setting. Monitor regulated gas pressure out of the modulating
control valve (or entering the burner) to determine when no further
reduction of gas pressure results. The flow rate of water through
the boiler shall be adjusted to achieve a 20 [deg]F temperature
rise.
7.5 Oil burner. Adjust the burners of oil-fired furnaces or
boilers to give a CO2 reading specified in the I&O manual
and an hourly Btu input during the steady-state performance test
described in section 8 of this appendix. Ensure the hourly BTU input
is within 2% of the normal hourly Btu input rating as
specified in the I&O manual. Smoke in the flue may not exceed a No.
1 smoke during the steady-state performance test as measured by the
procedure in ASTM D2156R13 (incorporated by reference, see Sec.
430.3). Maintain the average draft over the fire and in the flue
during the steady-state performance test at the value specified in
the I&O manual. Do not allow draft fluctuations exceeding 0.005 in.
water. Do not make additional adjustments to the burner during the
required series of performance tests. The instruments and measuring
apparatus for this test are described in section 6 of this appendix
and shown in Figure 8 of ASHRAE 103-1993 (incorporated by reference,
see Sec. 430.3).
7.6 Adjust air throughputs to achieve a temperature rise that is
the higher of a and b, below, unless c applies. A tolerance of
2 [deg]F is permitted.
a. 15 [deg]F less than the nameplate maximum temperature rise or
b. 15 [deg]F higher than the minimum temperature rise specified
in the I&O manual.
c. A furnace with a non-adjustable air temperature rise range
and an automatically controlled airflow that does not permit a
temperature rise range of 30[deg]F or more must be tested at the
midpoint of the rise range.
7.7 Establish the temperature rise specified in section 7.6 of
this appendix by adjusting the circulating airflow. This adjustment
must be accomplished by symmetrically restricting the outlet air
duct and varying blower speed selection to obtain the desired
temperature rise and minimum external static pressure, as specified
in Table 4 of ASHRAE 103-1993 (incorporated by reference, see Sec.
430.3). If the required temperature rise cannot be obtained at the
minimum specified external static pressure by adjusting blower speed
selection and duct outlet restriction, then the following applies.
a. If the resultant temperature rise is less than the required
temperature rise, vary the blower speed by gradually adjusting the
blower voltage so as to maintain the minimum external static
pressure listed in Table 4 of ASHRAE 103-1993 (incorporated by
reference, see Sec. 430.3). The airflow restrictions shall then
remain unchanged. If static pressure must be varied to prevent
unstable blower operation, then increase the static pressure until
blower operation is stabilized, except that the static pressure must
not exceed the maximum external static pressure as specified by the
manufacturer in the I&O manual.
b. If the resultant temperature rise is greater than the
required temperature rise, then the unit can be tested at a higher
temperature rise value, but one not greater than nameplate maximum
temperature rise. In order not to exceed the maximum temperature
rise, the speed of a direct-driven blower may be increased by
increasing the circulating air blower motor voltage.
7.8 Measurement of jacket surface temperature. Divide the jacket
of the furnace or boiler into 6-inch squares when practical, and
otherwise into 36-square-inch regions comprising 4 inch by 9 inch or
3 inch by 12 inch sections, and determine the surface temperature at
the center of each square or section with a surface thermocouple.
Record the surface temperature of the 36-square-inch areas in groups
where the temperature differential of the 36-square-inch areas is
less than 10 [deg]F for temperature up to 100 [deg]F above room
temperature, and less than 20 [deg]F for temperatures more than 100
[deg]F above room temperature. For forced-air central furnaces, the
circulating air blower compartment is considered as part of the duct
system, and no surface temperature measurement of the blower
compartment needs to be recorded for the purpose of this test. For
downflow furnaces, measure all cabinet surface temperatures of the
heat exchanger and combustion section, including the bottom around
the outlet duct and the burner door, using the 36-square-inch
thermocouple grid. The cabinet surface temperatures around the
blower section do not need to be measured (See Figure 3-E of ASHRAE
103-1993 (incorporated by reference, see Sec. 430.3)).
7.9 Installation of vent system. Keep the vent or air intake
system supplied by the manufacturer in place during all tests. Test
units intended for installation with a variety of vent pipe lengths
with the minimum vent length as specified in the I&O manual, or a 5-
ft. flue pipe if there are no recommendations in the I&O manual. Do
not connect a furnace or boiler employing a direct vent system to a
chimney or induced-draft source. Vent combustion products solely by
using the venting incorporated in the furnace or boiler and the vent
or air intake system supplied by the manufacturer. For units that
are not designed to significantly preheat the incoming air, see
section 7.5 of this appendix and Figure 4a or 4b of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3). For units that do
significantly preheat the incoming air, see Figure 4c or 4d of
ASHRAE 103-1993.
7.10 Additional optional method of testing for determining DP
and DF for furnaces and boilers. On units whose design is such that
there is no measurable airflow through the combustion chamber and
heat exchanger when the burner(s) is (are) off as determined by the
optional test procedure in section 7.10.1 of this appendix,
DF and DP may be set equal to 0.05.
7.10.1 Optional test method for indicating the absence of flow
through the heat exchanger. Manufacturers may use the following test
protocol to determine whether air flows through the combustion
chamber and heat exchanger when the burner(s) is (are) off. The
minimum default draft factor (as allowed per sections 8.8.3 and 9.10
of ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3)) may
be used only for units determined pursuant to this protocol to have
no airflow through the combustion chamber and heat exchanger.
7.10.1.1 Test apparatus. Use a smoke stick that produces smoke
that is easily visible and has a density less than or approximately
equal to air. Use a smoke stick that produces smoke that is non-
toxic to the test personnel and produces gas that is
[[Page 2650]]
unreactive with the environment in the test chamber.
7.10.1.2 Test conditions. Minimize all air currents and drafts
in the test chamber, including turning off ventilation if the test
chamber is mechanically ventilated. Wait at least two minutes
following the termination of the furnace or boiler on-cycle before
beginning the optional test method for indicating the absence of
flow through the heat exchanger.
7.10.1.3 Location of the test apparatus. After all air currents
and drafts in the test chamber have been eliminated or minimized,
position the smoke stick based on the following equipment
configuration: (a) For horizontal combustion air intakes,
approximately 4 inches from the vertical plane at the termination of
the intake vent and 4 inches below the bottom edge of the combustion
air intake; or (b) for vertical combustion air intakes,
approximately 4 inches horizontal from vent perimeter at the
termination of the intake vent and 4 inches down (parallel to the
vertical axis of the vent). In the instance where the boiler
combustion air intake is closer than 4 inches to the floor, place
the smoke device directly on the floor without impeding the flow of
smoke.
7.10.1.4 Duration of test. Establish the presence of smoke from
the smoke stick and then monitor the direction of the smoke flow for
no less than 30 seconds.
7.10.1.5 Test results. During visual assessment, determine
whether there is any draw of smoke into the combustion air intake
vent.
If absolutely no smoke is drawn into the combustion air intake,
the furnace or boiler meets the requirements to allow use of the
minimum default draft factor pursuant to section 8.8.3 and/or
section 9.10 of ASHRAE 103-1993 (incorporated by reference, see
Sec. 430.3).
If there is any smoke drawn into the intake, proceed with the
methods of testing as prescribed in section 8.8 of ASHRAE 103-1993.
8.0 Test procedure. Conduct testing and measurements as
specified in section 9 of ASHRAE 103-1993 (incorporated by
reference, see Sec. 430.3) except for sections 9.1.2.2.1,
9.1.2.2.2, 9.5.1.1, 9.5.1.2.1, 9.5.1.2.2, 9.5.2.1, 9.7.4, and 9.10;
and as specified in sections 8.1 through 8.11 of this appendix.
Section 8.4 of this appendix may be used in lieu of section 9.2 of
ASHRAE 103-1993.
8.1 Fuel input. For gas units, measure and record the steady-
state gas input rate in Btu/hr, including pilot gas, corrected to
standard conditions of 60 [deg]F and 30 in. Hg. Use measured values
of gas temperature and pressure at the meter and barometric pressure
to correct the metered gas flow rate to the above standard
conditions. For oil units, measure and record the steady-state fuel
input rate.
8.2 Electrical input. For furnaces and boilers, during the
steady-state test, perform a single measurement of all of the
electrical power involved in burner operation (PE), including
energizing the ignition system, controls, gas valve or oil control
valve, and draft inducer, if applicable. For boilers, the
measurement of PE must include the boiler pump if so equipped. If
the boiler pump does not operate during the measurement of PE, add
the boiler pump nameplate power to the measurement of PE. If the
boiler pump nameplate power is not available, use 0.13 kW.
For furnaces, during the steady-state test, perform a single
measurement of the electrical power to the circulating air blower
(BE). For hot water boilers, use the circulating water pump
nameplate power for BE, or if the pump nameplate power is not
available, use 0.13 kW.
8.3 Input to interrupted ignition device. For burners equipped
with an interrupted ignition device, record the nameplate electric
power used by the ignition device, PEIG, or record that
PEIG = 0.4 kW if no nameplate power input is provided.
Record the nameplate ignition device on-time interval,
tIG, or, if the nameplate does not provide the ignition
device on-time interval, measure the on-time interval with a
stopwatch at the beginning of the test, starting when the burner is
turned on. Set tIG = 0 and PEIG = 0 if the
device on-time interval is less than or equal to 5 seconds after the
burner is on.
8.4 Optional test procedures for condensing furnaces and
boilers, measurement of condensate during the establishment of
steady-state conditions. For units with step-modulating or two-stage
controls, conduct the test at both the maximum and reduced inputs.
In lieu of collecting the condensate immediately after the steady
state conditions have been reached as required by section 9.2 of
ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3),
condensate may be collected during the establishment of steady state
conditions as defined by section 9.1.2.1 of ASHRAE 103-1993. Perform
condensate collection for at least 30 minutes. Measure condensate
mass immediately at the end of the collection period to prevent
evaporation loss from the sample. Record fuel input for the 30-
minute condensate collection test period. Observe and record fuel
higher heating value (HHV), temperature, and pressures necessary for
determining fuel energy input (Qc,ss). Measure the fuel quantity and
HHV with errors no greater than 1%. The humidity for the room air
shall at no time exceed 80%. Determine the mass of condensate for
the establishment of steady state conditions (Mc,ss) in pounds by
subtracting the tare container weight from the total container and
condensate weight measured at the end of the 30-minute condensate
collection test period.
8.5 Cool-down test for gas- and oil-fueled gravity and forced-
air central furnaces without stack dampers. Turn off the main burner
after completing steady-state testing, and measure the flue gas
temperature by means of the thermocouple grid described in section
7.6 of ASHRAE 103-1993 (incorporated by reference, see Sec. 430.3)
at 1.5 minutes (TF,OFF(t3)) and 9 minutes
(TF,OFF(t4)) after shutting off the burner.
When taking these temperature readings, the integral draft diverter
must remain blocked and insulated, and the stack restriction must
remain in place. On atmospheric systems with an integral draft
diverter or draft hood and equipped with either an electromechanical
inlet damper or an electromechanical flue damper that closes within
10 seconds after the burner shuts off to restrict the flow through
the heat exchanger in the off-cycle, bypass or adjust the control
for the electromechanical damper so that the damper remains open
during the cool-down test.
For furnaces that employ post-purge, measure the length of the
post-purge period with a stopwatch. Record the time from burner
``OFF'' to combustion blower ``OFF'' (electrically de-energized) as
tP. If the measured tP is less than or equal
to 30 seconds, set tP at 0 and conduct the cool-down test
as if there is no post-purge. If tP is prescribed by the
I&O manual or measured to be greater than 180 seconds, stop the
combustion blower at 180 seconds and use that value for
tP. Measure the flue gas temperature by means of the
thermocouple grid described in section 7.6 of ASHRAE 103-1993 at the
end of the post-purge period, tP(TF,OFF
(tP)), and at the time (1.5 + tP) minutes
(TF,OFF(t3)) and (9.0 + tP) minutes
(TF,OFF(t4)) after the main burner shuts off.
8.6 Cool-down test for gas- and oil-fueled gravity and forced-
air central furnaces without stack dampers and with adjustable fan
control. For a furnace with adjustable fan control, measure the time
delay between burner shutdown and blower shutdown, t\+\. This time
delay, t\+\, will be 3.0 minutes for non-condensing furnaces or 1.5
minutes for condensing furnaces or until the supply air temperature
drops to a value of 40[emsp14][deg]F above the inlet air
temperature, whichever results in the longest fan on-time. For a
furnace without adjustable fan control or with the type of
adjustable fan control whose range of adjustment does not allow for
the time delay, t\+\, specified above, bypass the fan control and
manually control the fan to allow for the appropriate delay time as
specified in section 9.5.1.2 of ASHRAE 103-1993 (incorporated by
reference, see Sec. 430.3). For a furnace that employs a single
motor to drive both the power burner and the indoor air circulating
blower, the power burner and indoor air circulating blower must be
stopped at the same time
8.7 Cool-down test for gas- and oil-fueled boilers without stack
dampers. After steady-state testing has been completed, turn the
main burner(s) ``OFF'' and measure the flue gas temperature at 3.75
minutes (temperature designated as TF,OFF(t3))
and 22.5 minutes (temperature designated as
TF,OFF(t4)) after the burner shut-off using
the thermocouple grid described in section 7.6 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3).
a. During this off-period, for units that do not have pump delay
after shut-off, do not allow any water to circulate through the hot
water boilers.
b. For units that have pump delay on shut-off, except those
having pump controls sensing water temperature, the unit control
must stop the pump. Measure and record the time between burner shut-
off and pump shut-off (t\+\) to the nearest second.
c. For units having pump delay controls that sense water
temperature, operate the pump for 15 minutes and record t\+\ as 15
minutes. While the pump is operating, maintain the inlet water
temperature and
[[Page 2651]]
flow rate at the same values as used during the steady-state test,
as specified in sections 9.1 and 8.4.2.3 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3).
d. For boilers that employ post-purge, measure the length of the
post-purge period with a stopwatch. Record the time from burner
``OFF'' to combustion blower ``OFF'' (electrically de-energized) as
tP. If tP is prescribed by the I&O manual or
measured to be greater than 180 seconds, stop the combustion blower
at 180 seconds and use that value for tP. Measure the
flue gas temperature by means of the thermocouple grid described in
section 7.6 of ASHRAE 103-1993 at the end of the post-purge period
tP (TF,OFF(tP)) and at (3.75 +
tP) minutes (TF,OFF(t3)) and (22.5
+ tP) minutes (TF,OFF(t4)) after
the main burner shuts off. If the measured tP is less
than or equal to 30 seconds, record tP as 0 and conduct
the cool-down test as if there is no post-purge.
8.8 Direct measurement of off-cycle losses testing method.
[Reserved.]
8.9 Calculation options. The rate of the flue gas mass flow
through the furnace and the factors DP, DF,
and DS are calculated by the equations in sections
11.6.1, 11.6.2, 11.6.3, 11.6.4, 11.7.1, and 11.7.2 of ASHRAE 103-
1993 (incorporated by reference, see Sec. 430.3). On units whose
design is such that there is no measurable airflow through the
combustion chamber and heat exchanger when the burner(s) is (are)
off (as determined by the optional test procedure in section 7.10 of
this appendix), DF and DP may be set equal to
0.05.
8.10 Optional test procedures for condensing furnaces and
boilers that have no off-period flue losses. For units that have
applied the test method in section 7.10 of this appendix to
determine that no measurable airflow exists through the combustion
chamber and heat exchanger during the burner off-period and having
post-purge periods of less than 5 seconds, the cool-down and heat-up
tests specified in sections 9.5 and 9.6 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3) may be omitted. In lieu
of conducting the cool-down and heat-up tests, the tester may use
the losses determined during the steady-state test described in
section 9.1 of ASHRAE 103-1993 when calculating heating seasonal
efficiency, EffyHS.
8.11 Measurement of electrical standby and off mode power.
8.11.1 Standby power measurement. With all electrical
auxiliaries of the furnace or boiler not activated, measure the
standby power (PW,SB) in accordance with the procedures
in IEC 62301 (incorporated by reference, see Sec. 430.3), except
that section 8.5, Room Ambient Temperature, of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3) and the voltage
provision of section 8.2.1.4, Electrical Supply, of ASHRAE 103-1993
shall apply in lieu of the corresponding provisions of IEC 62301 at
section 4.2, Test room, and the voltage specification of section
4.3, Power supply. Frequency shall be 60Hz. Clarifying further, IEC
62301 section 4.4, Power measurement instruments, and section 5,
Measurements, apply in lieu of ASHRAE 103-1993 section 6.10, Energy
Flow Rate. Measure the wattage so that all possible standby mode
wattage for the entire appliance is recorded, not just the standby
mode wattage of a single auxiliary. Round the recorded standby power
(PW,SB) to the second decimal place, except for loads
greater than or equal to 10W, which must be recorded to at least
three significant figures.
8.11.2 Off mode power measurement. If the unit is equipped with
an off switch or there is an expected difference between off mode
power and standby mode power, measure off mode power
(PW,OFF) in accordance with the standby power
procedures in IEC 62301 (incorporated by reference, see Sec.
430.3), except that section 8.5, Room Ambient Temperature, of ASHRAE
103-1993 (incorporated by reference, see Sec. 430.3) and the
voltage provision of section 8.2.1.4, Electrical Supply, of ASHRAE
103-1993 shall apply in lieu of the corresponding provisions of IEC
62301 at section 4.2, Test room, and the voltage specification of
section 4.3, Power supply. Frequency shall be 60Hz. Clarifying
further, IEC 62301 section 4.4, Power measurement instruments, and
section 5, Measurements, apply for this measurement in lieu of
ASHRAE 103-1993 section 6.10, Energy Flow Rate. Measure the wattage
so that all possible off mode wattage for the entire appliance is
recorded, not just the off mode wattage of a single auxiliary. If
there is no expected difference in off mode power and standby mode
power, let PW,OFF = PW,SB, in which case no
separate measurement of off mode power is necessary. Round the
recorded off mode power (PW,OFF) to the second decimal
place, except for loads greater than or equal to 10W, in which case
round the recorded value to at least three significant figures.
9.0 Nomenclature. Nomenclature includes the nomenclature
specified in section 10 of ASHRAE 103-1993 (incorporated by
reference, see Sec. 430.3) and the following additional variables:
Effmotor = Efficiency of power burner motor
PEIG = Electrical power to the interrupted ignition
device, kW
RT,a = RT,F if flue gas is measured
= RT,S if stack gas is measured
RT,F = Ratio of combustion air mass flow rate to
stoichiometric air mass flow rate
RT,S = Ratio of the sum of combustion air and relief air
mass flow rate to stoichiometric air mass flow rate
tIG = Electrical interrupted ignition device on-time,
min.
Ta,SS,X = TF,SS,X if flue gas temperature is
measured, [deg]F
= TS,SS,X if stack gas temperature is measured,
[deg]F
yIG = Ratio of electrical interrupted ignition device on-
time to average burner on-time
yP = Ratio of power burner combustion blower on-time to
average burner on-time
ESO = Average annual electric standby mode and off mode
energy consumption, in kilowatt-hours
PW,OFF = Furnace or boiler off mode power, in watts
PW,SB = Furnace or boiler standby mode power, in watts
10.0 Calculation of derived results from test measurements.
Perform calculations as specified in section 11 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3), except for sections
11.5.11.1, 11.5.11.2, and appendices B and C; and as specified in
sections 10.1 through 10.11 and Figure 1 of this appendix.
10.1 Annual fuel utilization efficiency. The annual fuel
utilization efficiency (AFUE) is as defined in sections 11.2.12
(non-condensing systems), 11.3.12 (condensing systems), 11.4.12
(non-condensing modulating systems) and 11.5.12 (condensing
modulating systems) of ASHRAE 103-1993 (incorporated by reference,
see Sec. 430.3), except for the definition for the term
EffyHS in the defining equation for AFUE.
EffyHS is defined as:
EffyHS = heating seasonal efficiency as defined in
sections 11.2.11 (non-condensing systems), 11.3.11 (condensing
systems), 11.4.11 (non-condensing modulating systems) and 11.5.11
(condensing modulating systems) of ASHRAE 103-1993, except that for
condensing modulating systems sections 11.5.11.1 and 11.5.11.2 are
replaced by sections 10.2 and 10.3 of this appendix.
EffyHS is based on the assumptions that all weatherized
warm air furnaces or boilers are located outdoors, that non-
weatherized warm air furnaces are installed as isolated combustion
systems, and that non-weatherized boilers are installed indoors.
10.2 Part-load efficiency at reduced fuel input rate. If the
option in section 8.10 of this appendix is not employed, calculate
the part-load efficiency at the reduced fuel input rate,
EffyU,R, for condensing furnaces and boilers equipped
with either step-modulating or two-stage controls, expressed as a
percent and defined as:
[GRAPHIC] [TIFF OMITTED] TR15JA16.016
[[Page 2652]]
If the option in section 8.10 of this appendix is employed,
calculate EffyU,R as follows:
[GRAPHIC] [TIFF OMITTED] TR15JA16.017
Where:
LL,A = value as defined in section 11.2.7 of ASHRAE 103-
1993 (incorporated by reference, see Sec. 430.3)
LG = value as defined in section 11.3.11.1 of ASHRAE 103-
1993, at reduced input rate,
LC = value as defined in section 11.3.11.2 of ASHRAE 103-
1993 at reduced input rate,
LJ = value as defined in section 11.4.8.1.1 of ASHRAE
103-1993 at maximum input rate,
tON = value as defined in section 11.4.9.11 of ASHRAE
103-1993,
QP = pilot fuel input rate determined in accordance with
section 9.2 of ASHRAE 103-1993 in Btu/h,
QIN = value as defined in section 11.4.8.1.1 of ASHRAE
103-1993,
tOFF = value as defined in section 11.4.9.12 of ASHRAE
103-1993 at reduced input rate,
LS,ON = value as defined in section 11.4.10.5 of ASHRAE
103-1993 at reduced input rate,
LS,OFF = value as defined in section 11.4.10.6 of ASHRAE
103-1993 at reduced input rate,
LI,ON = value as defined in section 11.4.10.7 of ASHRAE
103-1993 at reduced input rate,
LI,OFF = value as defined in section 11.4.10.8 of ASHRAE
103-1993 at reduced input rate,
CJ = jacket loss factor and equal to:
= 0.0 for furnaces or boilers intended to be installed indoors
= 1.7 for furnaces intended to be installed as isolated
combustion systems
= 2.4 for boilers (other than finned-tube boilers) intended to
be installed as isolated combustion systems
= 3.3 for furnaces intended to be installed outdoors
= 4.7 for boilers (other than finned-tube boilers) intended to
be installed outdoors
= 1.0 for finned-tube boilers intended to be installed outdoors
= 0.5 for finned-tube boilers intended to be installed in
isolated combustion system applications
LS,SS = value as defined in section 11.4.6 of ASHRAE 103-
1993 at reduced input rate,
CS = value as defined in section 11.3.10.1 of ASHRAE 103-
1993 at reduced input rate.
10.3 Part-Load Efficiency at Maximum Fuel Input Rate. If the
option in section 8.10 of this appendix is not employed, calculate
the part-load efficiency at maximum fuel input rate,
EffyU,H, for condensing furnaces and boilers equipped
with two-stage controls, expressed as a percent and defined as:
[GRAPHIC] [TIFF OMITTED] TR15JA16.014
If the option in section 8.10 of this appendix is employed,
calculate EffyU,H as follows:
[GRAPHIC] [TIFF OMITTED] TR15JA16.015
Where:
LL,A = value as defined in section 11.2.7 of ASHRAE 103-
1993 (incorporated by reference, see Sec. 430.3),
LG = value as defined in section 11.3.11.1 of ASHRAE 103-
1 at maximum input rate,
LC = value as defined in section 11.3.11.2 of ASHRAE 103-
1993 at maximum input rate,
LJ = value as defined in section 11.4.8.1.1 of ASHRAE
103-1993 at maximum input rate,
tON = value as defined in section 11.4.9.11 of ASHRAE
103-1993,
QP = pilot fuel input rate determined in accordance with
section 9.2 of ASHRAE 103-1993 in Btu/h,
QIN = value as defined in section 11.4.8.1.1 of ASHRAE
103-1993,
tOFF = value as defined in section 11.4.9.12 of ASHRAE
103-1993 at maximum input rate,
LS,ON = value as defined in section 11.4.10.5 of ASHRAE
103-1993 at maximum input rate,
LS,OFF = value as defined in section 11.4.10.6 of ASHRAE
103-1993 at maximum input rate,
LI,ON = value as defined in section 11.4.10.7 of ASHRAE
103-1993 at maximum input rate,
LI,OFF = value as defined in section 11.4.10.8 of ASHRAE
103-1993 at maximum input rate,
CJ = value as defined in section 10.2 of this appendix,
LS,SS = value as defined in section 11.4.6 of ASHRAE 103-
1993 at maximum input rate,
CS = value as defined in section 11.4.10.1 of ASHRAE 103-
1993 at maximum input rate.
10.4 National average burner operating hours, average annual
fuel energy consumption, and average annual auxiliary electrical
energy consumption for gas or oil furnaces and boilers.
10.4.1 National average number of burner operating hours. For
furnaces and boilers equipped with single-stage controls, the
national average number of burner operating hours is defined as:
[[Page 2653]]
BOHSS = 2,080 (0.77) (A) DHR - 2,080 (B)
Where:
2,080 = national average heating load hours
0.77 = adjustment factor to adjust the calculated design heating
requirement and heating load hours to the actual heating load
experienced by the heating system
A = 100,000/[341,300 (yP PE + yIG
PEIG + y BE) + (QIN - QP)
EffyHS], for forced draft unit, indoors
= 100,000/[341,300 (yP PE Effmotor +
yIG PEIG + y BE) + (QIN -
QP) EffyHS], for forced draft unit, isolated
combustion system,
= 100,000/[341,300 (yP PE (1 - Effmotor) +
yIG PEIG + y BE) + (QIN -
QP) EffyHS], for induced draft unit, indoors,
and
= 100,000/[341,300 (yIG PEIG + y BE) +
(QIN - QP) EffyHS], for induced
draft unit, isolated combustion system.
DHR = typical design heating requirements as listed in Table 8 (in
kBtu/h) of ASHRAE 103-1993 (incorporated by reference, see Sec.
430.3), using the proper value of QOUT defined in
11.2.8.1 of ASHRAE 103-1993.
B = 2 QP (EffyHS) (A)/100,000
Where:
Effmotor = nameplate power burner motor efficiency
provided by the manufacturer,
= 0.50, an assumed default power burner efficiency if not
provided by the manufacturer.
100,000 = factor that accounts for percent and kBtu
yP = ratio of induced or forced draft blower on-time to
average burner on-time, as follows:
1 for units without post-purge;
1 + (tP/3.87) for single stage furnaces with post
purge;
1 + (tP/10) for two-stage and step modulating
furnaces with post purge;
1 + (tP/9.68) for single stage boilers with post
purge; or
1 + (tP/15) for two stage and step modulating boilers
with post purge.
PE = all electrical power related to burner operation at full load
steady-state operation, including electrical ignition device if
energized, controls, gas valve or oil control valve, draft inducer,
and boiler pump, as determined in section 8.2 of this appendix.
yIG = ratio of burner interrupted ignition device on-time
to average burner on-time, as follows:
0 for burners not equipped with interrupted ignition device;
(tIG/3.87) for single-stage furnaces or boilers;
(tIG/10) for two-stage and step modulating furnaces;
(tIG/9.68) for single stage boilers; or
(tIG/15) for two stage and step modulating boilers.
PEIG = electrical input rate to the interrupted ignition
device on burner (if employed), as defined in section 8.3 of this
appendix
y = ratio of blower or pump on-time to average burner on-time, as
follows:
1 for furnaces without fan delay or boilers without a pump
delay;
1 + (t\+\ - t-)/3.87 for single-stage furnaces with
fan delay;
1 + (t\+\ - t-)/10 for two-stage and step modulating
furnaces with fan delay;
1 + (t\+\/9.68) for single-stage boilers with pump delay;
1 + (t\+\/1.5) for two-stage and step modulating boilers with
pump delay.
BE = circulating air fan or water pump electrical energy input rate
at full-load steady-state operation as defined in section 8.2 of
this appendix.
tP = post-purge time as defined in section 8.5 (furnace)
or section 8.7 (boiler) of this appendix
= 0 if tP is equal to or less than 30 second
tIG = on-time of the burner interrupted ignition device,
as defined in section 8.3 of this appendix
QIN = as defined in section 11.2.8.1 of ASHRAE 103-1993
QP = as defined in section 11.2.11 of ASHRAE 103-1993
EffyHS = as defined in section 11.2.11 (non-condensing
systems) or section 11.3.11.3 (condensing systems) of ASHRAE 103-
1993, percent, and calculated on the basis of:
isolated combustion system installation, for non-weatherized
warm air furnaces;
indoor installation, for non-weatherized boilers; or
outdoor installation, for furnaces and boilers that are
weatherized.
2 = ratio of the average length of the heating season in hours to
the average heating load hours
t\+\ = delay time between burner shutoff and the blower or pump
shutoff measured as defined in section 9.5.1.2 of ASHRAE 103-1993
(furnace) or section 8.7 of this appendix (boiler).
t- = as defined in section 9.6.1 of ASHRAE 103-1993
10.4.1.1 For furnaces and boilers equipped with two stage or
step modulating controls the average annual energy used during the
heating season, EM, is defined as:
EM = (QIN - QP) BOHSS +
(8,760 - 4,600) QP
Where:
QIN = as defined in 11.4.8.1.1 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3)
QP = as defined in 11.4.12 of ASHRAE 103-1993
BOHSS = as defined in section 10.4.1 of this appendix, in
which the weighted EffyHS as defined in 11.4.11.3 or
11.5.11.3 of ASHRAE 103-1993 is used for calculating the values of A
and B, the term DHR is based on the value of QOUT defined
in 11.4.8.1.1 or 11.5.8.1.1 of ASHRAE 103-1993, and the term
(yPPE + yIGPEIG + yBE) in the
factor A is increased by the factor R, which is defined as:
R = 2.3 for two stage controls
= 2.3 for step modulating controls when the ratio of minimum-to-
maximum output is greater than or equal to 0.5
= 3.0 for step modulating controls when the ratio of minimum-to-
maximum output is less than 0.5
A = 100,000/[341,300 (yP PE + yIG
PEIG + y BE) R + (QIN - QP)
EffyHS], for forced draft unit, indoors
= 100,000/[341,300 (yP PE Effmotor +
yIG PEIG + y BE) R + (QIN -
QP) EffyHS], for forced draft unit, isolated
combustion system,
= 100,000/[341,300 (yP PE (1 - Effmotor) +
yIG PEIG + y BE) R + (QIN -
QP) EffyHS], for induced draft unit, indoors,
and
= 100,000/[341,300 (yIG PEIG + y BE) R +
(QIN - QP) EffyHS], for induced
draft unit, isolated combustion system.
Where:
Effmotor = nameplate power burner motor efficiency
provided by the manufacturer,
= 0.50, an assumed default power burner efficiency if not
provided by the manufacturer.
EffyHS = as defined in 11.4.11.3 or 11.5.11.3 of ASHRAE
103-1993, and calculated on the basis of:
isolated combustion system installation, for non-weatherized
warm air furnaces;
indoor installation, for non-weatherized boilers; or
outdoor installation, for furnaces and boilers that are
weatherized.
8,760 = total number of hours per year
4,600 = as defined in 11.4.12 of ASHRAE 103-1993
10.4.1.2 For furnaces and boilers equipped with two-stage or
step-modulating controls, the national average number of burner
operating hours at the reduced operating mode (BOHR) is
defined as:
BOHR = XR EM/QIN,R
Where:
XR = as defined in 11.4.8.7 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3)
EM = as defined in section 10.4.1.1 of this appendix
QIN,R = as defined in 11.4.8.1.2 of ASHRAE 103-1993
10.4.1.3 For furnaces and boilers equipped with two-stage
controls, the national average number of burner operating hours at
the maximum operating mode (BOHH) is defined as:
BOHH = XH EM/QIN
Where:
XH = as defined in 11.4.8.6 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3)
EM = as defined in section 10.4.1.1 of this appendix
QIN = as defined in section 11.4.8.1.1 of ASHRAE 103-1993
10.4.1.4 For furnaces and boilers equipped with step-modulating
controls, the national average number of burner operating hours at
the modulating operating mode (BOHM) is defined as:
BOHM = XH EM/QIN,M
Where:
XH = as defined in 11.4.8.6 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3)
EM = as defined in section 10.4.1.1 of this appendix
QIN,M = QOUT,M/(EffySS,M/100)
QOUT,M = as defined in 11.4.8.10 or 11.5.8.10 of ASHRAE
103-1993, as appropriate
EffySS,M = as defined in 11.4.8.8 or 11.5.8.8 of ASHRAE
103-1993, as appropriate, in percent
[[Page 2654]]
100 = factor that accounts for percent
10.4.2 Average annual fuel energy consumption for gas or oil
fueled furnaces or boilers. For furnaces or boilers equipped with
single-stage controls, the average annual fuel energy consumption
(EF) is expressed in Btu per year and defined as:
EF = BOHSS (QIN - QP) +
8,760 QP
Where:
BOHSS = as defined in section 10.4.1 of this appendix
QIN = as defined in section 11.2.8.1 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3)
QP = as defined in section 11.2.11 of ASHRAE 103-1993
8,760 = as defined in section 10.4.1.1 of this appendix
10.4.2.1 For furnaces or boilers equipped with either two-stage
or step modulating controls, EF is defined as:
EF = EM + 4,600 QP
Where:
EM = as defined in section 10.4.1.1 of this appendix
4,600 = as defined in section 11.4.12 of ASHRAE 103-1993
QP = as defined in section 11.2.11 of ASHRAE 103-1993
10.4.3 Average annual auxiliary electrical energy consumption
for gas or oil-fueled furnaces or boilers. For furnaces and boilers
equipped with single-stage controls, the average annual auxiliary
electrical consumption (EAE) is expressed in kilowatt-
hours and defined as:
EAE = BOHSS (yP PE + yIG
PEIG + yBE) + ESO
Where:
BOHSS = as defined in section 10.4.1 of this appendix
yP = as defined in section 10.4.1 of this appendix
PE = as defined in section 10.4.1 of this appendix
yIG = as defined in section 10.4.1 of this appendix
PEIG = as defined in section 10.4.1 of this appendix
y = as defined in section 10.4.1 of this appendix
BE = as defined in section 10.4.1 of this appendix
ESO = as defined in section 10.11 of this appendix
10.4.3.1 For furnaces or boilers equipped with two-stage
controls, EAE is defined as:
EAE = BOHR (yP PER +
yIG PEIG + yBER) + BOHH
(yP PEH + yIG PEIG + y
BEH) + ESO
Where:
BOHR = as defined in section 10.4.1.2 of this appendix
yP = as defined in section 10.4.1 of this appendix
PER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
yIG = as defined in section 10.4.1 of this appendix
PEIG = as defined in section 10.4.1 of this appendix
y = as defined in section 10.4.1 of this appendix
BER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
BOHH = as defined in section 10.4.1.3 of this appendix
PEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
BEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
ESO = as defined in section 10.11 of this appendix
10.4.3.2 For furnaces or boilers equipped with step-modulating
controls, EAE is defined as:
EAE = BOHR (yP PER +
yIG PEIG + y BER) + BOHM
(yP PEH + yIG PEIG + y
BEH) + ESO
Where:
BOHR = as defined in section 10.4.1.2 of this appendix
yP = as defined in section 10.4.1 of this appendix
PER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
yIG = as defined in section 10.4.1 of this appendix
PEIG = as defined in section 10.4.1 of this appendix
y = as defined in section 10.4.1 of this appendix
BER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
BOHM = as defined in 10.4.1.4 of this appendix
PEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
BEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
ESO = as defined in section 10.11 of this appendix
10.5 Average annual electric energy consumption for electric
furnaces or boilers. For electric furnaces and boilers, the average
annual electrical energy consumption (EE) is expressed in
kilowatt-hours and defined as:
EE = 100 (2,080) (0.77) DHR/(3.412 AFUE) + ESO
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.4.1 of this appendix
0.77 = as defined in section 10.4.1 of this appendix
DHR = as defined in section 10.4.1 of this appendix
3.412 = conversion factor from watt-hours to Btu
AFUE = as defined in section 11.1 of ASHRAE 103-1993 (incorporated
by reference, see Sec. 430.3), in percent, and calculated on the
basis of:
isolated combustion system installation, for non-weatherized
warm air furnaces;
indoor installation, for non-weatherized boilers; or
outdoor installation, for furnaces and boilers that are
weatherized.
ESO = as defined in section 10.11 of this appendix.
10.6 Energy factor.
10.6.1 Energy factor for gas or oil furnaces and boilers.
Calculate the energy factor, EF, for gas or oil furnaces and boilers
defined as, in percent:
EF = (EF - 4,600 (QP))(EffyHS)/
(EF + 3,412 (EAE))
Where:
EF = average annual fuel consumption as defined in
section 10.4.2 of this appendix
4,600 = as defined in section 11.4.12 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3)
QP = pilot fuel input rate determined in accordance with
section 9.2 of ASHRAE 103-1993 in Btu/h
EffyHS = annual fuel utilization efficiency as defined in
sections 11.2.11, 11.3.11, 11.4.11 or 11.5.11 of ASHRAE 103-1993, in
percent, and calculated on the basis of:
isolated combustion system installation, for non-weatherized
warm air furnaces;
indoor installation, for non-weatherized boilers; or
outdoor installation, for furnaces and boilers that are
weatherized.
3,412 = conversion factor from kW to Btu/h
EAE = as defined in section 10.4.3 of this appendix
10.6.2 Energy factor for electric furnaces and boilers. The
energy factor, EF, for electric furnaces and boilers is defined as:
EF = AFUE
Where:
AFUE = annual fuel utilization efficiency as defined in section
10.4.3 of this appendix, in percent
10.7 Average annual energy consumption for furnaces and boilers
located in a different geographic region of the United States and in
buildings with different design heating requirements.
10.7.1 Average annual fuel energy consumption for gas or oil-
fueled furnaces and boilers located in a different geographic region
of the United States and in buildings with different design heating
requirements. For gas or oil-fueled furnaces and boilers, the
average annual fuel energy consumption for a specific geographic
region and a specific typical design heating requirement
(EFR) is expressed in Btu per year and defined as:
EFR = (EF - 8,760 QP) (HLH/2,080) +
8,760 QP
Where:
EF = as defined in section 10.4.2 of this appendix
8,760 = as defined in section 10.4.1.1 of this appendix
QP = as defined in section 11.2.11 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3)
HLH = heating load hours for a specific geographic region determined
from the heating load hour map in Figure 1 of this appendix
2,080 = as defined in section 10.4.1 of this appendix
10.7.2 Average annual auxiliary electrical energy consumption
for gas or oil-fueled furnaces and boilers located in a different
geographic region of the United States and in
[[Page 2655]]
buildings with different design heating requirements. For gas or
oil-fueled furnaces and boilers, the average annual auxiliary
electrical energy consumption for a specific geographic region and a
specific typical design heating requirement (EAER) is
expressed in kilowatt-hours and defined as:
EAER = (EAE - ESO) (HLH/2080) +
ESOR
Where:
EAE = as defined in section 10.4.3 of this appendix
ESO = as defined in section 10.11 of this appendix
HLH = as defined in section 10.7.1 of this appendix
2,080 = as defined in section 10.4.1 of this appendix
ESOR = as defined in section 10.7.3 of this appendix.
10.7.3 Average annual electric energy consumption for electric
furnaces and boilers located in a different geographic region of the
United States and in buildings with different design heating
requirements. For electric furnaces and boilers, the average annual
electric energy consumption for a specific geographic region and a
specific typical design heating requirement (EER) is
expressed in kilowatt-hours and defined as:
EER = 100 (0.77) DHR HLH/(3.412 AFUE) + ESOR
Where:
100 = as defined in section 10.4.3 of this appendix
0.77 = as defined in section 10.4.1 of this appendix
DHR = as defined in section 10.4.1 of this appendix
HLH = as defined in section 10.7.1 of this appendix
3.412 = as defined in section 10.4.3 of this appendix
AFUE = as defined in section 10.4.3 of this appendix
ESOR = ESO as defined in section 10.11 of this
appendix, except that in the equation for ESO, the term
BOH is multiplied by the expression (HLH/2080) to get the
appropriate regional accounting of standby mode and off mode loss.
10.8 Annual energy consumption for mobile home furnaces
10.8.1 National average number of burner operating hours for
mobile home furnaces (BOHSS). BOHSS is the same as in
section 10.4.1 of this appendix, except that the value of
EffyHS in the calculation of the burner operating hours,
BOHSS, is calculated on the basis of a direct vent unit
with system number 9 or 10.
10.8.2 Average annual fuel energy for mobile home furnaces (EF).
EF is same as in section 10.4.2 of this appendix except
that the burner operating hours, BOHSS, is calculated as
specified in section 10.8.1 of this appendix.
10.8.3 Average annual auxiliary electrical energy consumption
for mobile home furnaces (EAE). EAE is the same as in
section 10.4.3 of this appendix, except that the burner operating
hours, BOHSS, is calculated as specified in section
10.8.1 of this appendix.
10.9 Calculation of sales weighted average annual energy
consumption for mobile home furnaces. To reflect the distribution of
mobile homes to geographical regions with average HLHMHF
values different from 2,080, adjust the annual fossil fuel and
auxiliary electrical energy consumption values for mobile home
furnaces using the following adjustment calculations.
10.9.1 For mobile home furnaces, the sales weighted average
annual fossil fuel energy consumption is expressed in Btu per year
and defined as:
EF,MHF = (EF - 8,760 QP)
HLHMHF/2,080 + 8,760 QP
Where:
EF = as defined in section 10.8.2 of this appendix
8,760 = as defined in section 10.4.1.1 of this appendix
QP = as defined in section 10.2 of this appendix
HLHMHF = 1880, sales weighted average heating load hours
for mobile home furnaces
2,080 = as defined in section 10.4.1 of this appendix
10.9.2 For mobile home furnaces, the sales-weighted-average
annual auxiliary electrical energy consumption is expressed in
kilowatt-hours and defined as:
EAE,MHF = EAE HLHMHF/2,080
Where:
EAE = as defined in section 10.8.3 of this appendix
HLHMHF = as defined in section 10.9.1 of this appendix
2,080 = as defined in section 10.4.1 of this appendix
10.10 Direct determination of off-cycle losses for furnaces and
boilers equipped with thermal stack dampers. [Reserved.]
10.11 Average annual electrical standby mode and off mode energy
consumption. Calculate the annual electrical standby mode and off
mode energy consumption (ESO) in kilowatt-hours, defined
as:
ESO = (PW,SB (4160 - BOH) + 4600
PW,OFF) K
Where:
PW,SB = furnace or boiler standby mode power, in watts,
as measured in section 8.11.1 of this appendix
4,160 = average heating season hours per year
BOH = total burner operating hours as calculated in section 10.4 of
this appendix for gas or oil-fueled furnaces or boilers. Where for
gas or oil-fueled furnaces and boilers equipped with single-stage
controls, BOH = BOHSS; for gas or oil-fueled furnaces and
boilers equipped with two-stage controls, BOH = (BOHR +
BOHH); and for gas or oil-fueled furnaces and boilers
equipped with step-modulating controls, BOH = (BOHR +
BOHM). For electric furnaces and boilers, BOH =
100(2080)(0.77)DHR/(Ein 3.412(AFUE))
4,600 = as defined in section 11.4.12 of ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3)
PW,OFF = furnace or boiler off mode power, in watts, as
measured in section 8.11.2 of this appendix
K = 0.001 kWh/Wh, conversion factor from watt-hours to kilowatt-
hours
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.4.1 of this appendix
0.77 = as defined in section 10.4.1 of this appendix
DHR = as defined in section 10.4.1 of this appendix
Ein = steady-state electric rated power, in kilowatts,
from section 9.3 of ASHRAE 103-1993
3.412 = as defined in section 10.4.3 of this appendix
AFUE = as defined in section 11.1 of ASHRAE 103-1993 in percent
[[Page 2656]]
[GRAPHIC] [TIFF OMITTED] TR15JA16.018
[FR Doc. 2016-00040 Filed 1-14-16; 8:45 am]
BILLING CODE 6450-01-P