Petroleum Refinery Sector Risk and Technology Review and New Source Performance Standards, 75177-75354 [2015-26486]
Download as PDF
Vol. 80
Tuesday,
No. 230
December 1, 2015
Part II
Environmental Protection Agency
tkelley on DSK3SPTVN1PROD with RULES2
40 CFR Parts 60 and 63
Petroleum Refinery Sector Risk and Technology Review and New Source
Performance Standards; Final Rule
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00001
Fmt 4717
Sfmt 4717
E:\FR\FM\01DER2.SGM
01DER2
75178
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
ENVIRONMENTAL PROTECTION
AGENCY
40 CFR Parts 60 and 63
[EPA–HQ–OAR–2010–0682; FRL–9935–40–
OAR]
RIN 2060–AQ75
Petroleum Refinery Sector Risk and
Technology Review and New Source
Performance Standards
Environmental Protection
Agency (EPA).
ACTION: Final rule.
AGENCY:
This action finalizes the
residual risk and technology review
conducted for the Petroleum Refinery
source categories regulated under
national emission standards for
hazardous air pollutants (NESHAP)
Refinery MACT 1 and Refinery MACT 2.
It also includes revisions to the Refinery
MACT 1 and MACT 2 rules in
accordance with provisions regarding
establishment of MACT standards. This
action also finalizes technical
corrections and clarifications for the
new source performance standards
(NSPS) for petroleum refineries to
improve consistency and clarity and
address issues related to a 2008 industry
petition for reconsideration.
Implementation of this final rule will
result in projected reductions of 5,200
tons per year (tpy) of hazardous air
pollutants (HAP) which will reduce
cancer risk and chronic health effects.
DATES: This final action is effective on
February 1, 2016. The incorporation by
reference of certain publications for part
63 listed in the rule is approved by the
Director of the Federal Register as of
February 1, 2016. The incorporation by
reference of certain publications for part
60 listed in the rule were approved by
the Director of the Federal Register as of
June 24, 2008.
ADDRESSES: The Environmental
Protection Agency (EPA) has established
a docket for this action under Docket ID
No. EPA–HQ–OAR–2010–0682. All
documents in the docket are listed on
the www.regulations.gov Web site.
Although listed in the index, some
information is not publicly available,
e.g., confidential business information
(CBI) or other information whose
disclosure is restricted by statute.
Certain other material, such as
copyrighted material, is not placed on
the Internet and will be publicly
available only in hard copy form.
Publicly available docket materials are
available either electronically through
https://www.regulations.gov, or in hard
copy at the EPA Docket Center, WJC
tkelley on DSK3SPTVN1PROD with RULES2
SUMMARY:
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
West Building, Room Number 3334,
1301 Constitution Ave. NW.,
Washington, DC. The Public Reading
Room hours of operation are 8:30 a.m.
to 4:30 p.m. Eastern Standard Time
(EST), Monday through Friday. The
telephone number for the Public
Reading Room is (202) 566–1744, and
the telephone number for the Air and
Radiation Docket and Information
Center is (202) 566–1742.
FOR FURTHER INFORMATION CONTACT: For
questions about this final action, contact
Ms. Brenda Shine, Sector Policies and
Programs Division, Refining and
Chemicals Group (E143–01), Office of
Air Quality Planning and Standards,
U.S. Environmental Protection Agency,
Research Triangle Park, North Carolina,
27711; telephone number: (919) 541–
3608; fax number: (919) 541–0246; and
email address: shine.brenda@epa.gov.
For specific information regarding the
risk modeling methodology, contact Mr.
Ted Palma, Health and Environmental
Impacts Division (C539–02), Office of
Air Quality Planning and Standards,
U.S. Environmental Protection Agency,
Research Triangle Park, North Carolina
27711; telephone number: (919) 541–
5470; fax number: (919) 541–0840; and
email address: palma.ted@epa.gov. For
information about the applicability of
the NESHAP to a particular entity,
contact Ms. Maria Malave, Office of
Enforcement and Compliance
Assurance, U.S. Environmental
Protection Agency, William Jefferson
Clinton Building, 1200 Pennsylvania
Ave. NW., Washington, DC 20460;
telephone number: (202) 564–7027; fax
number: (202) 564–0050; and email
address: malave.maria@epa.gov.
SUPPLEMENTARY INFORMATION:
Preamble Acronyms and
Abbreviations. We use multiple
acronyms and terms in this preamble.
While this list may not be exhaustive, to
ease the reading of this preamble and for
reference purposes, the EPA defines the
following terms and acronyms here:
10/25 tpy emissions equal to or greater than
10 tons per year of a single pollutant or 25
tons per year of cumulative pollutants
AEGL acute exposure guideline levels
APCD air pollution control devices
API American Petroleum Institute
BAAQMD Bay Area Air Quality
Management District
BDT best demonstrated technology
BLD bag leak detectors
BSER best system of emission reductions
Btu/ft2 British thermal units per square foot
Btu/scf British thermal units per standard
cubic foot
CAA Clean Air Act
CBI confidential business information
CCU catalytic cracking units
CDX Central Data Exchange
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
CEDRI Compliance and Emissions Data
Reporting Interface
CEMS continuous emission monitoring
system
CFR Code of Federal Regulations
CO carbon monoxide
CO2 carbon dioxide
CO2e carbon dioxide equivalents
COMS continuous opacity monitoring
system
COS carbonyl sulfide
CPMS continuous parameter monitoring
system
CRA Congressional Review Act
CRU catalytic reforming units
CS2 carbon disulfide
DCU delayed coking units
EPA Environmental Protection Agency
ERPG emergency response and planning
guidelines
ERT Electronic Reporting Tool
ESP electrostatic precipitator
FCCU fluid catalytic cracking unit
FGCD fuel gas combustion device
FMP flare management plan
FR Federal Register
FTIR Fourier transform infrared
spectroscopy
GC gas chromatograph
GHG greenhouse gases
H2S hydrogen sulfide
HAP hazardous air pollutants
HCl hydrogen chloride
HCN hydrogen cyanide
HF hydrogen fluoride
HFC highest fenceline concentration
HI hazard index
HQ hazard quotient
ICR information collection request
IRIS Integrated Risk Information System
km kilometers
LAER lowest achievable emission rate
lb/day pounds per day
LDAR leak detection and repair
LEL lower explosive limit
LTD long tons per day
MACT maximum achievable control
technology
MIR maximum individual risk
mph miles per hour
MPV miscellaneous process vent
NAICS North American Industry
Classification System
NESHAP National Emissions Standards for
Hazardous Air Pollutants
NFS near-field interfering source
NHVCZ combustion zone net heating value
Ni nickel
NOX nitrogen oxides
NRDC Natural Resources Defense Council
NSPS new source performance standards
NTTAA National Technology Transfer and
Advancement Act
OAQPS Office of Air Quality Planning and
standards
OECA Office of Enforcement and
Compliance Assurance
OEHHA Office of Environmental Health
Hazard Assessment
OEL open-ended line
OMB Office of Management and Budget
PM particulate matter
PM2.5 particulate matter 2.5 micrometers in
diameter and smaller
ppbv parts per billion by volume
ppm parts per million
E:\FR\FM\01DER2.SGM
01DER2
75179
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
ppmv parts per million by volume
PRA Paperwork Reduction Act
PRD pressure relief device 1
psia pounds per square inch absolute
psig pounds per square inch gauge
REL reference exposure level
REM Model Refinery Emissions Model
RFA Regulatory Flexibility Act
RTC response to comment
RTR Risk and Technology Review
SAB Science Advisory Board
SBA Small Business Administration
SCAQMD South Coast Air Quality
Management District
SCR selective catalytic reduction
SISNOSE significant economic impact on a
substantial number of small entities
SO2 sulfur dioxide
SRP sulfur recovery plant
SRU sulfur recovery unit
SSM startup, shutdown and malfunction
TOSHI target organ-specific hazard index
tpy tons per year
UMRA Unfunded Mandates Reform Act
URE unit risk estimate
UV–DOAS ultraviolet differential optical
absorption spectroscopy
VCS voluntary consensus standards
VOC volatile organic compounds
°F degrees Fahrenheit
DC the concentration difference between
the highest measured concentration and
the lowest measured concentration
mg/m3 micrograms per cubic meter
tkelley on DSK3SPTVN1PROD with RULES2
Background Information. On June 30,
2014, the EPA proposed revisions to
both of the petroleum refinery NESHAP
based on our residual risk and
technology review (RTR). In that action,
we also proposed to revise the NESHAP
pursuant to CAA section 112(d)(2) and
(3), to revise the SSM provisions in the
NESHAP, and to make technical
corrections to the NSPS to address
issues related to reconsideration of the
final NSPS subpart Ja rule in 2008. In
this action, we are finalizing decisions
and revisions for these rules. We
summarize some of the more significant
comments received regarding the
proposed rule and provide our
responses in this preamble. A summary
of all other public comments on the
proposal and the EPA’s responses to
those comments is provided in the
‘‘Response to Comment’’ document,
which is available in Docket ID No.
EPA–HQ–OAR–2010–0682. The ‘‘track
changes’’ version of the regulatory
language that incorporates the changes
in this final action is also available in
the docket for this rulemaking.
Organization of this Document. This
preamble is organized as follows:
I. General Information
A. Does this action apply to me?
B. Where can I get a copy of this document
and other related information?
1 This term is common vernacular to describe the
variety of devices regulated as pressure relief valves
subject to the requirements in 40 CFR part 63
subpart CC.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
C. Judicial Review and Administrative
Reconsideration
II. Background
A. What is the statutory authority for this
action?
B. How do the NESHAP and NSPS regulate
air pollutant emissions from refineries?
C. What changes did we propose for the
Petroleum Refinery NESHAP and NSPS
in our June 30, 2014 RTR proposal?
III. What is included in this final rule?
A. What are the final NESHAP
amendments based on the risk review for
the Petroleum Refinery source
categories?
B. What are the final NESHAP
amendments based on the technology
review for the Petroleum Refinery source
categories?
C. What are the final NESHAP
amendments pursuant to section
112(d)(2) & (3) for the Petroleum
Refinery source categories?
D. What are the final NESHAP
amendments addressing emissions
during periods of SSM?
E. What other revisions to the NESHAP
and NSPS are being promulgated?
F. What are the requirements for
submission of performance test data to
the EPA?
G. What are the effective and compliance
dates of the NESHAP and NSPS?
H. What materials are being incorporated
by reference?
IV. What is the rationale for our final
decisions and amendments to the
Petroleum Refinery NESHAP and NSPS?
A. Residual Risk Review for the Petroleum
Refinery Source Categories
B. Technology Review for the Petroleum
Refinery Source Categories
C. Refinery MACT Amendments Pursuant
to CAA section 112(d)(2) and (d)(3)
D. NESHAP Amendments Addressing
Emissions During Periods of SSM
E. Technical Amendments to Refinery
MACT 1 and 2
F. Technical Amendments to Refinery
NSPS Subparts J and Ja
V. Summary of Cost, Environmental, and
Economic Impacts and Additional
Analyses Conducted
A. What are the affected facilities, the air
quality impacts and cost impacts?
B. What are the economic impacts?
C. What are the benefits?
D. Impacts of This Rulemaking on
Environmental Justice Populations
E. Impacts of This Rulemaking on
Children’s Health
VI. Statutory and Executive Order Reviews
A. Executive Orders 12866: Regulatory
Planning and Review and Executive
Order 13563: Improving Regulation and
Regulatory Review
B. Paperwork Reduction Act (PRA)
C. Regulatory Flexibility Act (RFA)
D. Unfunded Mandates Reform Act
(UMRA)
E. Executive Order 13132: Federalism
F. Executive Order 13175: Consultation
and Coordination With Indian Tribal
Governments
G. Executive Order 13045: Protection of
Children From Environmental Health
Risks and Safety Risks
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
H. Executive Order 13211: Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution or Use
I. National Technology Transfer and
Advancement Act (NTTAA) and 1 CFR
part 51
J. Executive Order 12898: Federal Actions
To Address Environmental Justice in
Minority Populations and Low-Income
Populations
K. Congressional Review Act (CRA)
I. General Information
A. Does this action apply to me?
Regulated Entities. Categories and
entities potentially regulated by this
action are shown in Table 1 of this
preamble.
TABLE 1—INDUSTRIAL SOURCE CATEGORIES AFFECTED BY THIS FINAL
ACTION
NAICS a
Code
NESHAP and source category
Petroleum Refining Industry .........
a North
American
Industry
324110
Classification
System.
Table 1 of this preamble is not
intended to be exhaustive, but rather to
provide a guide for readers regarding
entities likely to be affected by the final
action for the source categories listed.
To determine whether your facility is
affected, you should examine the
applicability criteria in the appropriate
NESHAP or NSPS. If you have any
questions regarding the applicability of
any aspect of these NESHAP or NSPS,
please contact the appropriate person
listed in the preceding FOR FURTHER
INFORMATION CONTACT section of this
preamble.
B. Where can I get a copy of this
document and other related
information?
In addition to being available in the
docket, an electronic copy of this final
action will also be available on the
Internet through the Technology
Transfer Network (TTN) Web site, a
forum for information and technology
exchange in various areas of air
pollution control. Following signature
by the EPA Administrator, the EPA will
post a copy of this final action at:
https://www.epa.gov/ttn/atw/petref.html.
Following publication in the Federal
Register, the EPA will post the Federal
Register version and key technical
documents at this same Web site.
Additional information is available on
the RTR Web site at https://www.epa.
gov/ttn/atw/rrisk/rtrpg.html. This
information includes an overview of the
RTR program, links to project Web sites
E:\FR\FM\01DER2.SGM
01DER2
75180
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
for the RTR source categories, and
detailed emissions and other data we
used as inputs to the risk assessments.
C. Judicial Review and Administrative
Reconsideration
Under CAA section 307(b)(1), judicial
review of this final action is available
only by filing a petition for review in
the United States Court of Appeals for
the District of Columbia Circuit by
February 1, 2016. Under CAA section
307(b)(2), the requirements established
by this final rule may not be challenged
separately in any civil or criminal
proceedings brought by the EPA to
enforce the requirements.
Section 307(d)(7)(B) of the CAA
further provides that ‘‘[o]nly an
objection to a rule or procedure which
was raised with reasonable specificity
during the period for public comment
(including any public hearing) may be
raised during judicial review.’’ This
section also provides a mechanism for
the EPA to reconsider the rule ‘‘[i]f the
person raising an objection can
demonstrate to the Administrator that it
was impracticable to raise such
objection within [the period for public
comment] or if the grounds for such
objection arose after the period for
public comment (but within the time
specified for judicial review) and if such
objection is of central relevance to the
outcome of the rule.’’ Any person
seeking to make such a demonstration
should submit a Petition for
Reconsideration to the Office of the
Administrator, U.S. EPA, Room 3000,
WJC Building, 1200 Pennsylvania Ave.
NW., Washington, DC 20460, with a
copy to both the person(s) listed in the
preceding FOR FURTHER INFORMATION
CONTACT section, and the Associate
General Counsel for the Air and
Radiation Law Office, Office of General
Counsel (Mail Code 2344A), U.S. EPA,
1200 Pennsylvania Ave. NW.,
Washington, DC 20460.
II. Background
tkelley on DSK3SPTVN1PROD with RULES2
A. What is the statutory authority for
this action?
1. NESHAP
Section 112 of the CAA establishes a
two-stage regulatory process to address
emissions of hazardous air pollutants
(HAP) from stationary sources. In the
first stage, we must identify categories
of sources emitting one or more of the
HAP listed in CAA section 112(b) and
then promulgate technology-based
NESHAP for those sources. ‘‘Major
sources’’ are those that emit, or have the
potential to emit, any single HAP at a
rate of 10 tons per year (tpy) or more,
or 25 tpy or more of any combination of
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
HAP. For major sources, these standards
are commonly referred to as maximum
achievable control technology (MACT)
standards and must reflect the
maximum degree of emission reductions
of HAP achievable (after considering
cost, energy requirements, and non-air
quality health and environmental
impacts). In developing MACT
standards, CAA section 112(d)(2) directs
the EPA to consider the application of
measures, processes, methods, systems
or techniques, including but not limited
to those that reduce the volume of or
eliminate HAP emissions through
process changes, substitution of
materials, or other modifications;
enclose systems or processes to
eliminate emissions; collect, capture, or
treat HAP when released from a process,
stack, storage, or fugitive emissions
point; are design, equipment, work
practice, or operational standards; or
any combination of the above.
For these MACT standards, the statute
specifies certain minimum stringency
requirements, which are referred to as
MACT floor requirements, and which
may not be based on cost
considerations. See CAA section
112(d)(3). For new sources, the MACT
floor cannot be less stringent than the
emission control achieved in practice by
the best-controlled similar source. The
MACT standards for existing sources
can be less stringent than floors for new
sources, but they cannot be less
stringent than the average emission
limitation achieved by the bestperforming 12-percent of existing
sources in the category or subcategory
(or the best-performing 5 sources for
categories or subcategories with fewer
than 30 sources). In developing MACT
standards, we must also consider
control options that are more stringent
than the floor, under CAA section
112(d)(2). We may establish standards
more stringent than the floor, based on
the consideration of the cost of
achieving the emissions reductions, any
non-air quality health and
environmental impacts, and energy
requirements.
In the second stage of the regulatory
process, the CAA requires the EPA to
undertake 2 different analyses, which
we refer to as the technology review and
the residual risk review. Under the
technology review, we must review the
technology-based standards and revise
them ‘‘as necessary (taking into account
developments in practices, processes,
and control technologies)’’ no less
frequently than every eight years,
pursuant to CAA section 112(d)(6).
Under the residual risk review, we must
evaluate the risk to public health
remaining after application of the
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
technology-based standards and revise
the standards, if necessary, to provide
an ample margin of safety to protect
public health or to prevent, taking into
consideration costs, energy, safety and
other relevant factors, an adverse
environmental effect. The residual risk
review is required within eight years
after promulgation of the technologybased standards, pursuant to CAA
section 112(f). In conducting the
residual risk review, if the EPA
determines that the current standards
provide an ample margin of safety to
protect public health, it is not necessary
to revise the MACT standards pursuant
to CAA section 112(f).2 For more
information on the statutory authority
for this rule, see 79 FR 36879.
2. NSPS
Section 111 of the CAA establishes
mechanisms for controlling emissions of
air pollutants from stationary sources.
Section 111(b) of the CAA provides
authority for the EPA to promulgate
NSPS that apply only to newly
constructed, reconstructed and modified
sources. Once the EPA has elected to set
NSPS for new and modified sources in
a given source category, CAA section
111(d) calls for regulation of existing
sources, with certain exceptions
explained below.
Specifically, section 111(b) of the
CAA requires the EPA to establish
emission standards for any category of
new and modified stationary sources
that the Administrator, in his or her
judgment, finds ‘‘causes, or contributes
significantly to, air pollution which may
reasonably be anticipated to endanger
public health or welfare.’’ The EPA has
previously made endangerment findings
under this section of the CAA for more
than 60 stationary source categories and
subcategories that are now subject to
NSPS.
Section 111 of the CAA gives the EPA
significant discretion to identify the
affected facilities within a source
category that should be regulated. To
define the affected facilities, the EPA
can use size thresholds for regulation
and create subcategories based on
source type, class or size. Emission
limits also may be established either for
equipment within a facility or for an
entire facility. For listed source
categories, the EPA must establish
‘‘standards of performance’’ that apply
2 The U.S. Court of Appeals has affirmed this
approach of implementing CAA section
112(f)(2)(A): NRDC v. EPA, 529 F.3d 1077, 1083
(D.C. Cir. 2008) (‘‘If EPA determines that the
existing technology-based standards provide an
‘ample margin of safety,’ then the Agency is free to
readopt those standards during the residual risk
rulemaking.’’).
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
to sources that are constructed,
modified or reconstructed after the EPA
proposes the NSPS for the relevant
source category.3
The EPA also has significant
discretion to determine the appropriate
level for the standards. Section 111(a)(1)
of the CAA provides that NSPS are to
reflect the degree of emission limitation
achievable through the application of
the best system of emission reduction
which (taking into account the cost of
achieving such reduction and any nonair quality health and environmental
impact and energy requirements) the
Administrator determines has been
adequately demonstrated. This level of
control is commonly referred to as best
demonstrated technology (BDT) or the
best system of emission reduction
(BSER). The standard that the EPA
develops, based on the BSER achievable
at that source, is commonly a numerical
emission limit, expressed as a
performance level (i.e., a rate-based
standard). Generally, the EPA does not
prescribe a particular technological
system that must be used to comply
with a NSPS. Rather, sources remain
free to elect whatever combination of
measures will achieve equivalent or
greater control of emissions.
Costs are also considered in
evaluating the appropriate standard of
performance for each category or
subcategory. The EPA generally
compares control options and estimated
costs and emission impacts of multiple,
specific emission standard options
under consideration. As part of this
analysis, the EPA considers numerous
factors relating to the potential cost of
the regulation, including industry
organization and market structure,
control options available to reduce
emissions of the regulated pollutant(s)
and costs of these controls.
tkelley on DSK3SPTVN1PROD with RULES2
B. How do the NESHAP and NSPS
regulate air pollutant emissions from
refineries?
The EPA promulgated the petroleum
refinery NESHAP pursuant to CAA
section 112(d)(2) and (3) for refineries
located at major sources in two separate
rules. On August 18, 1995, the first
3 Specific statutory and regulatory provisions
define what constitutes a modification or
reconstruction of a facility. 40 CFR 60.14 provides
that an existing facility is modified and, therefore,
subject to an NSPS, if it undergoes any physical
change in the method of operation which increases
the amount of any air pollutant emitted by such
source or which results in the emission of any air
pollutant not previously emitted. 40 CFR 60.15, in
turn, provides that a facility is reconstructed if
components are replaced at an existing facility to
such an extent that the capital cost of the new
equipment/components exceed 50-percent of what
is believed to be the cost of a completely new
facility.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
petroleum refinery MACT standard was
promulgated in 40 CFR part 63, subpart
CC (60 FR 43620). This rule is known
as ‘‘Refinery MACT 1’’ and covers the
‘‘Sources Not Distinctly Listed,’’
meaning it includes all emissions
sources from petroleum refinery process
units, except those listed separately
under the section 112(c) source category
list and expected to be regulated by
other MACT standards (for example,
boilers and process heaters). Some of
the emission sources regulated in
Refinery MACT 1 include miscellaneous
process vents (MPV), storage vessels,
wastewater, equipment leaks, gasoline
loading racks, marine tank vessel
loading and heat exchange systems.
On April 11, 2002 (67 FR 17762), EPA
promulgated a second MACT standard
regulating certain process vents that
were listed as a separate source category
under CAA section 112(c) and that were
not addressed as part of the Refinery
MACT 1. This standard, which is
referred to as ‘‘Refinery MACT 2’’,
covers process vents on catalytic
cracking units (CCU) (including FCCU),
CRU and SRU and is codified as 40 CFR
part 63, subpart UUU.
Finally, on October 28, 2009, we
revised Refinery MACT 1 by adding
MACT standards for heat exchange
systems, which the EPA had not
addressed in the original 1995 Refinery
MACT 1 rule (74 FR 55686). In this
same 2009 action, we updated the crossreferences to the General Provisions in
40 CFR part 63. On June 20, 2013 (78
FR 37133), we promulgated minor
revisions to the heat exchange
provisions of Refinery MACT 1.
On September 27, 2012, Air Alliance
Houston, California Communities
Against Toxics and other environmental
and public health groups filed a lawsuit
alleging that the EPA missed statutory
deadlines to review and revise Refinery
MACT 1 and 2. The EPA reached an
agreement to settle that litigation and
entered into a Consent Decree. The
Consent Decree provides for the
Administrator to sign a final action no
later than September 30, 2015.
Refinery NSPS subparts J and Ja
regulated criteria pollutant emissions,
including particulate matter (PM), sulfur
dioxide (SO2), nitrogen oxides (NOX)
and carbon monoxide (CO) from FCCU
catalyst regenerators, fuel gas
combustion devices (FGCD) and sulfur
recovery plants. Refinery NSPS subpart
Ja also regulates criteria pollutant
emissions from fluid coking units and
DCU.
The NSPS for petroleum refineries (40
CFR part 60, subpart J) were
promulgated in 1974, amended in 1976
and amended again in 2008, following
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
75181
a review of the standards. As part of the
review that led to the 2008 amendments
to the Refinery NSPS subpart J, the EPA
developed separate standards of
performance for new process units (40
CFR part 60, subpart Ja). However, the
EPA received multiple petitions for
reconsideration on issues related to
those standards. The Administrator
granted the petitions for
reconsideration. The EPA addressed
petition issues related to process heaters
and flares by promulgating amendments
to the Refinery NSPS subparts J and Ja
on September 12, 2012 (77 FR 56422).
In this action, we are finalizing
technical corrections and clarifications
to NSPS subparts J and Ja raised by
American Petroleum Institute (API) in
their 2008 petition for reconsideration
that were not addressed by the final
NSPS amendments of 2012.
The petroleum refining industry
consists of facilities that engage in
converting crude oil into refined
products, including liquefied petroleum
gas, gasoline, kerosene, aviation fuel,
diesel fuel, fuel oils, lubricating oils and
feedstocks for the petrochemical
industry. Currently, 142 facilities have
emission sources regulated by either or
both Refinery MACT 1 and 2.
Petroleum refinery activities start
with the receipt of crude oil for storage
at the refinery, include all the petroleum
handling and refining operations, and
terminate with loading of refined
products into pipelines, tank or rail
cars, tank trucks, or ships or barges that
take products from the refinery to
distribution centers. Petroleum-specific
process units include FCCU and CRU.
Other units and processes found at
petroleum refineries (as well as at many
other types of manufacturing facilities)
include storage vessels and wastewater
treatment plants. HAP emitted by this
industry include organics (e.g.,
acetaldehyde, benzene, formaldehyde,
hexane, phenol, naphthalene, 2methylnaphthalene, dioxins, furans,
ethyl benzene, toluene and xylene);
reduced sulfur compounds (i.e.,
carbonyl sulfide (COS), carbon disulfide
(CS2))); inorganics (e.g., hydrogen
chloride (HCl), hydrogen cyanide
(HCN), chlorine, hydrogen fluoride
(HF)); and metals (e.g., antimony,
arsenic, beryllium, cadmium,
chromium, cobalt, lead, mercury,
manganese and nickel (Ni)). This
industry also emits criteria pollutants
and other non-HAP, including NOX,
PM, SO2, volatile organic compounds
(VOC), CO, greenhouse gases (GHG) and
total reduced sulfur.
E:\FR\FM\01DER2.SGM
01DER2
75182
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
C. What changes did we propose for the
Petroleum Refinery NESHAP and NSPS
in our June 30, 2014, RTR proposal?
On June 30, 2014, the EPA published
a proposed rule in the Federal Register
addressing the RTR for the Petroleum
Refinery NESHAP, 40 CFR part 63,
subparts CC and UUU. The proposal
also included changes pursuant to
section 112(d)(2) and (3) and technical
revisions to the NSPS. Specifically, we
proposed:
(1) Pursuant to CAA sections
112(d)(2) and (3):
a. Refinery MACT 1:
• Adding MACT Standards for DCU
decoking operations.
• Adding operational requirements
for flares used as APCD in Refinery
MACT 1 and 2.
• Adding requirements and
clarifications for vent control bypasses
in Refinery MACT 1.
b. Refinery MACT 2:
• Revising the CRU purge vent
exemption.
(2) Pursuant to CAA sections
112(d)(6) and 112(f)(2):
• Revising Refinery MACT 1 to crossreference the corresponding storage
vessel requirements in the Generic
MACT (40 CFR part 63, subpart WW, as
applicable), and revising the definition
of Group 1 storage vessels to include
smaller capacity storage vessels and to
include storage vessels storing materials
with lower vapor pressures.
(3) Pursuant to CAA section 112(d)(6):
a. Refinery MACT 1:
• Allowing refineries to meet the leak
detection and repair (LDAR)
requirements in Refinery MACT 1 by
monitoring for leaks using optical gas
imaging in place of EPA Method 21,
once the monitoring protocol set forth in
Appendix K is promulgated.
• Amending the Marine Tank Vessel
Loading Operations NESHAP, 40 CFR
part 63, subpart Y, to delete the
exclusion for marine vessel loading
operations at petroleum refineries.
• Establishing a fenceline monitoring
work practice standard to improve the
management of fugitive emissions.
b. Refinery MACT 2:
• Incorporating requirements
consistent with those in Refinery NSPS
subpart Ja for FCCU including:
• Requiring the use of 3-hour
averages rather than daily averages for
parameter operating limits (e.g.,
depending on the type of control device:
Opacity, total power, secondary current,
pressure drop, and/or liquid-to-gas
ratio).
• Removing the Refinery NSPS
subpart J incremental PM emissions
allowance for post combustion devices
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
when burning liquid or solid fuels, and
removing the 30 percent opacity limit
for units complying with NSPS subpart
J.
• Adding requirements for FCCU
controls to include bag leak detectors
(BLD) as an option to continuous
opacity monitoring system (COMS).
• Incorporating total power and the
secondary current operating limits for
electrostatic precipitators (ESP).
• Requiring daily checks of the air or
water pressure to the spray nozzles on
jet ejector-type wet scrubber or other
type of wet scrubber equipped with
atomizing spray nozzles.
• Requiring FCCU periodic
performance testing on a frequency of
once every 5 years, as opposed to the
current rule, which only requires an
initial performance test.
• Including a correlation equation for
the use of oxygen-enriched air for SRU.
• Allowing SRU subject to Refinery
NSPS subpart Ja with a capacity greater
than 20 long tons per day (LTD) to
comply with Refinery NSPS subpart Ja
as a means of complying with Refinery
MACT 2.
(4) Other proposed changes include:
• Removing exemptions from the rule
requirements for periods of SSM in
order to ensure that the NESHAP are
consistent with the court decision in
Sierra Club v. EPA, 551 F. 3d 1019 (D.C.
Cir. 2008).
• Clarifying requirements related to
open-ended valves or lines.
• Adding electronic reporting
requirements.
• Updating the General Provisions
cross-reference tables.
• Making technical corrections and
clarifications to NSPS subparts J and Ja.
subparts J and Ja to address issues raised
in the reconsideration of these rules.
III. What is included in this final rule?
This action finalizes the EPA’s
determinations pursuant to the RTR
provisions of CAA section 112 for the
Petroleum Refinery source categories
and amends the Petroleum Refinery
NESHAP based on those
determinations. This action also
finalizes other changes to the NESHAP
including revising Refinery MACT 1
and 2 pursuant to CAA section 112
(d)(2) and (3), including revising
requirements for flares and pressure
relief devices (PRD). This action
finalizes changes to the SSM provisions
to ensure that the subparts are
consistent with the court decision in
Sierra Club v. EPA, 551 F. 3d 1019 (D.C.
Cir. 2008), adds electronic reporting
requirements in Refinery MACT 1 and
2; and updates the General Provisions
cross-reference tables. Finally, this
action finalizes technical corrections
and clarifications to Refinery NSPS
We determined that there are
developments in practices, processes
and control technologies that warrant
revisions to the MACT standards for this
source category. Therefore, to satisfy the
requirements of CAA section 112(d)(6),
we are revising the MACT standards to
amend 40 CFR part 63, subpart Y to
delete the exclusion for marine vessel
loading operations at petroleum
refineries. Removing this exclusion will
require small marine vessel loading
operations (i.e., operations with HAP
emissions less than 10/25 tpy) and
offshore marine vessel loading
operations to use submerged filling
based on the cargo filling line
requirements in 46 CFR 153.282, as
proposed.
We are also finalizing a fenceline
monitoring work practice standard to
improve the management of fugitive
emissions and finalizing EPA Methods
325A and 325B to support the work
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
A. What are the final NESHAP
amendments based on the risk review
for the Petroleum Refinery source
categories?
The EPA is promulgating final
amendments to the Petroleum Refinery
NESHAP pursuant to CAA section
112(f) that expand the existing Refinery
MACT 1 control requirements and
extend these requirements to smaller
tanks and tanks with lower vapor
pressures. Specifically, consistent with
the proposal, the EPA is amending
Refinery MACT 1 by revising the
definition of Group 1 storage vessels to
include storage vessels with capacities
greater than or equal to 20,000 gallons
but less than 40,000 gallons if the
maximum true vapor pressure is 1.0
psia or greater and to include storage
tanks greater than 40,000 gallons if the
maximum true vapor pressure is 0.75
psia or greater. The EPA is also adding
a cross-reference to the storage vessel
requirements in the Generic MACT (40
CFR part 63, subpart WW and subpart
CC), which include requirements for
guide pole controls and other fittings as
well as inspection requirements. After
considering the public comments, the
final amendments include minor
changes from our proposed
requirements to clarify language and
correct typographical and referencing
errors.
B. What are the final NESHAP
amendments based on the technology
review for the Petroleum Refinery source
categories?
1. Refinery MACT 1
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
practice, with some changes from
proposal to address issues raised by
commenters. Key revisions include:
New provisions for reduced monitoring
for facilities with consistently low
fenceline concentrations; requirements
for alternatives to passive monitoring;
revised placement guidance to allow
perimeter monitoring within a facility’s
property boundary provided all sources
are encompassed within the monitoring
perimeter; reductions in the number of
monitors required for subareas and
segregated areas; clarifications on
monitor placement for internal
roadways or other right-of-ways and
marine docks; and revised timelines for
submitting periodic reports (quarterly
rather than semiannually) and
implementing the work practice
standard (2 years after promulgation
rather than 3 years as proposed). We are
also revising Refinery MACT 1 storage
vessel requirements as described above
under the risk review, as proposed.
2. Refinery MACT 2
We determined that there are
developments in practices, processes
and control technologies that warrant
revisions to the MACT standards for this
source category. Therefore, to satisfy the
requirements of CAA section 112(d)(6),
we are revising the Refinery MACT 2
standard for FCCU subject to Refinery
NSPS subpart J or those electing to
comply with the Refinery NSPS subpart
J requirements. As proposed, we are
removing the incremental PM limit
when burning liquid or solid fuels. We
are finalizing a 20-percent opacity
operating limit evaluated on a 3-hour
average, which differs from the proposal
to eliminate the 30-percent opacity limit
and instead allow only for a site-specific
opacity operating limit or control device
parameter monitoring. As proposed, we
are finalizing requirements to make
Refinery MACT 2 consistent with
Refinery NSPS subpart Ja for FCCU by
including 3-hour averages rather than
daily averages for parameter operating
limits, and by including 3-hour averages
rather than daily averages for the sitespecific opacity operating limit. We are
also finalizing requirements, as
proposed, for FCCU controls to include
adding BLD as an option to COMS,
incorporating total power and the
secondary current operating limits for
ESP and requiring daily checks of the
air or water pressure to the spray
nozzles on jet ejector-type wet scrubbers
or other types of wet scrubbers
equipped with atomizing spray nozzles.
Finally, we are finalizing, as
proposed, requirements for FCCU
periodic performance testing at a
frequency of once every 5 years rather
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
than the current requirements for a onetime initial performance test. However,
for owners or operators complying with
the Refinery NSPS subpart J option
(with the 20-percent opacity operating
limit discussed above), if the PM
emissions are within 80-percent of the
PM limit during any periodic
performance test (i.e., emissions exceed
0.8 lb PM/1,000 lbs of coke burn-off),
the refinery owner or operator must
conduct subsequent performance tests
on an annual basis. Based on comments
received, we are also adding
requirements in the final rule for owners
or operators of FCCU to conduct a onetime test for HCN emissions from the
FCCU concurrent with their first
periodic performance test, which must
be conducted on or before August 1,
2017 for all FCCU subject to Refinery
MACT 2.
For SRU, as proposed, we are
finalizing a correlation equation for the
use of oxygen-enriched air.
Additionally, as proposed, we are
finalizing requirements to allow sulfur
recovery plants subject to Refinery
NSPS subpart Ja with a capacity greater
than 20 LTD to comply with Refinery
NSPS subpart Ja as a means of
complying with Refinery MACT 2.
C. What are the final NESHAP
amendments pursuant to section
112(d)(2) & (3) for the Petroleum
Refinery source categories?
1. Refinery MACT 1
We are finalizing MACT standards for
DCU decoking operations that require
that each coke drum be depressured to
a closed blowdown system until the
coke drum pressure is 2 psig with minor
revisions from proposal. Specifically,
we are finalizing provisions for existing
DCU affected sources to average over a
60-cycle (i.e., 60 batch) basis to comply
with the 2 psig limit, rather than the
proposed requirement to meet the 2 psig
limit on a per venting event basis. In
addition, we are finalizing requirements
for new DCU affected sources to
depressure to 2.0 psig on a per-event,
not-to-exceed basis, adding one
significant digit to the limit for new
DCU affected sources. For both new and
existing DCU affected sources, we are
finalizing specific provisions for DCU
with water overflow design and for
double quenching.
We are finalizing operational
requirements and the associated
monitoring, recordkeeping and
reporting requirements for flares used as
APCD in Refinery MACT 1 and 2 with
revisions to the requirements proposed.
Prior to these amendments, Refinery
MACT 1 and 2 cross-referenced the
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
75183
General Provisions requirements at 40
CFR 63.11(b). As proposed, this final
action replaces the cross reference to the
General Provisions and incorporates
enhanced flare operational requirements
directly into the Refinery MACT
regulations. As proposed, the final rule
amendments require that refinery flares
operate with continuously lit pilot
flames at all times. Consistent with our
proposal, we are finalizing requirements
for flares to operate with no visible
emissions and comply with
consolidated requirements related to
flare tip velocity, but in the final rule
these direct emissions limits apply
when flare vent gas flow is below the
smokeless capacity of the flare rather
than at all times. Above the smokeless
capacity of the flare, we are establishing
a work practice standard related to the
visible emissions and velocity limits;
these work practice standards are
described in more detail in section
III.D.1 of this preamble.
We are finalizing new operational
requirements related to combustion
zone gas properties with revisions from
proposal. In response to comments on
the proposal, we are finalizing
requirements that flares meet a
minimum operating limit of 270 BTU/
scf NHVcz on a 15-minute average, and
are allowing refinery owners or
operators to use a corrected heat content
of 1,212 BTU/scf for hydrogen to
demonstrate compliance with this
operating limit. We had proposed two
separate sets of limits, one being more
stringent if an olefins/hydrogen mixture
was present in the waste gas. For each
set of limits, we proposed three different
alternative combustion zone operating
limits: One based on the combustion
zone net heat content with no correction
for the heat content of hydrogen, one
based on the lower flammability limit
and one based on the combustibles
concentration. We proposed that these
limits be determined on a 15-minute
‘‘feed-forward’’ block average approach
(i.e., compositional data are collected
every 15 minutes, after which
adjustments are made). We have
included an additional option for
refiners to comply where more frequent
data are collected (using direct net
heating value monitoring) to calculate
the combustion limit using net heating
value data from the same 15-minute
block period. We are simplifying the
compliance approach to a single
operating limit based only on the
combustion zone net heating value
(with a hydrogen correction). As
proposed, we are requiring refinery
owners or operators to characterize the
composition of waste gas, assist gas and
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75184
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
fuel to demonstrate compliance with the
operational requirements.
As proposed, we are also finalizing in
this rule a burden reduction option to
use grab sampling every 8 hours rather
than continuous vent gas composition
or heat content monitors. We are also
including, based on public comment,
provisions to conduct limited initial
sampling and process knowledge to
characterize flare gas composition for
flares in ‘‘dedicated’’ service as an
alternative to collecting grab samples
during each specific event. We are
finalizing a requirement for daily visible
emissions observations as proposed,
but, based on public comment, we are
allowing owners or operators to use
video surveillance cameras to
demonstrate compliance with the
visible emissions limit as an alternative
to the daily visible emissions
observations.
For PRD, we are finalizing
requirements for monitoring systems
that are capable of identifying and
recording the time and duration of each
pressure release to the atmosphere, as
proposed. Certain PRD with low set
pressures or low emission potential or
in liquid service would not be subject to
these monitoring requirements. We are
finalizing requirements to minimize or
prevent atmospheric releases of HAP
through PRD. Instead of the proposed
prohibition on such releases, we are
finalizing work practice requirements
that require both preventive measures as
well as root cause analysis and
corrective action that will incentivize
refinery owners or operators to
eliminate the causes of the releases.
We are finalizing requirements for
bypass lines with minor revisions from
those proposed. Specifically, we are not
adopting the proposed requirement to
install quantitative flow monitors and
thus are leaving in place the
requirement to use flow indicators on
bypass lines. In addition, we are
maintaining the requirements to
estimate and report the quantity of
organic HAP released. In response to
public comment, we are also clarifying
changes to remove the proposed
reference to air intrusion and specifying
that reporting of bypasses is only
required when ‘‘regulated material’’ is
discharged to the atmosphere as a result
of a bypass of a control device.
We are also finalizing revisions to the
definition of miscellaneous process
vent, as proposed. These revisions
include deletion of exclusions
associated with episodic releases and
vents from in situ sampling systems. As
proposed, the final amendments require
that these vents must meet the standards
applicable to MPV.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
2. Refinery MACT 2
For CRU vents, we are finalizing the
vessel pressure limit exclusion of 5 psig
to apply only to passive
depressurization, as proposed.
D. What are the final NESHAP
amendments addressing emissions
during periods of SSM?
We are finalizing, as proposed,
changes to Refinery MACT 1 and 2 to
eliminate the SSM exemption.
Consistent with Sierra Club v. EPA, 551
F. 3d 1019 (D.C. Cir. 2008), the EPA has
established standards in this rule that
apply at all times. EPA is revising Table
6 of subpart CC of 40 CFR part 63 and
Table 44 to subpart UUU of 40 CFR part
63 (the General Provisions Applicability
Tables) to change several references
related to requirements that apply
during periods of SSM. We also are
eliminating or revising certain
recordkeeping and reporting
requirements related to the eliminated
SSM exemptions. We also are removing
or modifying inappropriate,
unnecessary or redundant language in
the absence of the SSM exemption.
Further, for certain emission sources in
both MACT 1 and 2, we are establishing
standards to address emissions during
these periods. These are described
below.
1. Refinery MACT 1
We are finalizing a work practice
standard for PRD that requires refinery
owners or operators to establish
prevention measures for each PRD in
organic HAP service. Under the work
practice standard, where a direct release
occurs, the refinery is required to
perform root cause analysis and
implement corrective action. The work
practice standard also limits the number
of events that a PRD may release to the
atmosphere during a 3-year period, as
explained further in the section IV.D. of
this preamble.
We are also finalizing a work practice
standard for emergency flaring events
that requires refinery owners or
operators to establish prevention
measures, including the development of
a flare management plan (FMP), and
perform root cause analysis and
implement corrective action following
flaring events during which the velocity
of waste gas going to the flare or visible
emissions limits (i.e., opacity) at the
flare tip are exceeded, and to limit the
number of these events allowed in a 3year period, as explained further in
section IV.D. of this preamble. Both of
these work practice standards are
consistent with the EPA’s goal to
improve the effectiveness of the rules.
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
These requirements will provide a
strong incentive for facilities, over time,
to better operate their processes to
prevent PRD and flare releases.
We are also finalizing requirements
for opening process equipment to the
atmosphere during maintenance events
after draining and purging to a closed
system, provided the hydrocarbon
content is less than or equal to 10percent of the lower explosive limit
(LEL). For those situations where 10percent LEL cannot be demonstrated,
the equipment may be opened and
vented to the atmosphere if the pressure
is less than or equal to 5 psig, provided
there is no active purging of the
equipment to the atmosphere until the
LEL criterion is met. This 5 psig
allowance is only available during
shutdown. We are also providing
additional allowances for situations
where it is not technically feasible to
depressurize a control system where
there is no more than 72 lbs VOC per
day vented to the atmosphere,
consistent with our Group 1
applicability cutoff for control of
process vents, or for catalyst changeout
activities where hydrotreater pyrophoric
catalyst must be purged. Provisions to
demonstrate that process equipment is
opened only after the LEL, pressure or
mass in the vessel requirement is met
includes documenting the procedures
for equipment openings and procedures
for verifying that the openings meet the
specific, above-discussed requirements
using site-specific procedures used to
de-inventory equipment for safety
purposes (i.e., hot work or vessel entry
procedures).
2. Refinery MACT 2
The Refinery MACT 2 standards
regulate all HAP emissions from the
three refinery process vents subject to
Refinery MACT 2. For FCCU, the
standard specifies a CO limit as a
surrogate for organic HAP and specifies
a PM limit (or Ni limit) as a surrogate
for metal HAP. Compliance with the
organic HAP emissions limit is
demonstrated using a continuous CO
monitor; compliance with the metal
HAP emissions limit is demonstrated
using either COMS or control device
parameter monitoring systems (CPMS).
At proposal, with the removal of the
exemptions in the Refinery MACT 2
rule for periods of startup and
shutdown, we recognized the need for
alternative standards during some
startup and shutdown situations, and
we proposed alternative requirements.
For this final rule, we are including a
1-percent minimum oxygen limit as an
alternative to the 500 ppmv hourly CO
limit during FCCU startup for partial
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
burn FCCU with CO boilers, as
proposed. We are extending that
alternative limit to all FCCU and
extending it to apply during shutdown.
We are not finalizing the proposed
alternative opacity limit for FCCU
during startup. Instead, based on public
comments received, we are finalizing an
alternative minimum cyclone face
velocity limit as a means to demonstrate
compliance with the PM limit during
both startup and shutdown, regardless
of the type of FCCU and its control
device. We are finalizing alternative
standards for sulfur recovery plant
(SRP) incinerator temperature and
excess oxygen limits during SRP
shutdown, as proposed, and we are
extending the proposed alternative
standards to startup as well.
tkelley on DSK3SPTVN1PROD with RULES2
E. What other revisions to the NESHAP
and NSPS are being promulgated?
We are finalizing technical
amendments to NSPS subparts J and Ja
with limited changes from what we
proposed. First, in response to
comments, we are revising the NSPS
requirements that a flow sensor have a
‘‘measurement sensitivity’’ of no more
than 5-percent of the flow rate to an
‘‘accuracy’’ requirement that the flow
sensor have an accuracy of 5-percent of
the flow rate. This change will make the
requirements more clear and consistent
between the flow meter requirements in
the NSPS and the MACT standards
since it is the same flow meter subject
to these requirements. We are also
revising flare flow rate accuracy
requirements in Refinery NSPS subpart
Ja to make them consistent with those
we are finalizing in Refinery MACT 1.
Finally, we are revising 40 CFR
60.101a(b) to begin as ‘‘Except for flares
and delayed coking units . . .’’ to
correct an inadvertent error. We
proposed revisions to this sentence
solely to allow sources subject to
Refinery NSPS subpart J to comply with
the provisions in Refinery NSPS subpart
Ja instead. However, the words ‘‘and
delayed coking units’’ were
inadvertently omitted from the initial
part of the sentence. Thus, as intended,
we are finalizing revisions to this
sentence to allow sources subject to
Refinery NSPS subpart J to comply with
the provisions in Refinery NSPS subpart
Ja.
F. What are the requirements for
submission of performance test data to
the EPA?
As proposed, the EPA is taking a step
to increase the ease and efficiency of
data submittal and data accessibility.
Specifically, the EPA is finalizing the
requirement for owners or operators of
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Petroleum Refinery facilities to submit
electronic copies of certain required
performance test reports through the
EPA’s Central Data Exchange (CDX)
using the Compliance and Emissions
Data Reporting Interface (CEDRI). The
EPA believes that the electronic
submittal of the reports addressed in
this rulemaking will increase the
usefulness of the data contained in
those reports, is in keeping with current
trends in data availability, will further
assist in the protection of public health
and the environment and will
ultimately result in less burden on the
regulated community. Electronic
reporting can also eliminate paperbased, manual processes, thereby saving
time and resources, simplifying data
entry, eliminating redundancies,
minimizing data reporting errors and
providing data quickly and accurately to
the affected facilities, air agencies, the
EPA and the public.
As mentioned in the preamble of the
proposal, the EPA Web site that stores
the submitted electronic data, WebFIRE,
will be easily accessible to everyone and
will provide a user-friendly interface
that any stakeholder could access. By
making the records, data and reports
addressed in this rulemaking readily
available, the EPA, the regulated
community and the public will benefit
when the EPA conducts its CAArequired technology and risk-based
reviews. As a result of having reports
readily accessible, our ability to carry
out comprehensive reviews will be
increased and achieved within a shorter
period of time.
We anticipate fewer or less substantial
information collection requests (ICRs) in
conjunction with prospective CAArequired technology and risk-based
reviews may be needed. We expect this
to result in a decrease in time spent by
industry to respond to data collection
requests. We also expect the ICRs to
contain less extensive stack testing
provisions, as we will already have
stack test data electronically. Reduced
testing requirements would be a cost
savings to industry. The EPA should
also be able to conduct these required
reviews more quickly. While the
regulated community may benefit from
a reduced burden of ICRs, the general
public benefits from the agency’s ability
to provide these required reviews more
quickly, resulting in increased public
health and environmental protection.
Air agencies could benefit from more
streamlined and automated review of
the electronically submitted data.
Having reports and associated data in
electronic format will facilitate review
through the use of software ‘‘search’’
options, as well as the downloading and
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
75185
analyzing of data in spreadsheet format.
The ability to access and review air
emission report information
electronically will assist air agencies to
more quickly and accurately determine
compliance with the applicable
regulations, potentially allowing a faster
response to violations which could
minimize harmful air emissions. This
benefits both air agencies and the
general public.
For a more thorough discussion of
electronic reporting required by this
rule, see the discussion in the preamble
of the proposal. In summary, in addition
to supporting regulation development,
control strategy development, and other
air pollution control activities, having
an electronic database populated with
performance test data will save
industry, air agencies, and the EPA
significant time, money, and effort
while improving the quality of emission
inventories, air quality regulations, and
enhancing the public’s access to this
important information.
G. What are the effective and
compliance dates of the NESHAP and
NSPS?
The final amendments to the NESHAP
and NSPS in this action are effective on
February 1, 2016. As proposed, new
sources must comply with these
requirements by the effective date of the
final rule or upon startup, whichever is
later.
As proposed, existing sources are
required to comply with the final DCU
and CRU requirements no later than 3
years after the effective date of the final
rule. Similarly, as proposed, owners or
operators are required to comply with
the new operating and monitoring
requirements for existing flares no later
than 3 years after the effective date of
the final rule.
We proposed to provide 3 years from
the effective date of the final rule for
refinery owners or operators to install
and begin monitoring (collecting
samples) around the fenceline of their
existing facility. If refinery owners and
operators determined that a site-specific
monitoring plan was needed, they
would also need to submit and receive
approval for such a plan during the 3year compliance period. Based on
information submitted during the
comment period, we are finalizing
requirements that refinery owners or
operators begin collecting samples
around the fenceline within 2 years of
the effective date of the final rule. Based
on information submitted during the
comment period, 1 year is sufficient
time to identify proper monitoring
locations and to install the required
monitoring stations around the facility
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75186
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
fenceline. However, owners or operators
may need additional monitoring
systems to account for near-field
interfering sources (NFS), for which the
development and approval of a sitespecific fenceline monitoring plan is
required. We expect that the sitespecific fenceline monitoring plans can
take an additional year to develop,
submit and obtain approval.
Consequently, we are providing 2 years
from the effective date of the final rule
for refinery owners or operators to
install and begin collecting samples
around the fenceline of their facility.
As proposed, we are requiring that
existing sources comply with the
submerged filling requirement for
marine vessel loading on the effective
date of the final rule.
As proposed, we are providing 18
months after the effective date of the
final rule to conduct required
performance tests and comply with any
revised operating limits for FCCU.
We proposed to require refinery
owners or operators to comply with the
revisions to the SSM provisions of
Refinery MACT 1 and 2 on the effective
date of the final rule. As proposed, this
final rule requires refinery owners or
operators to comply with the limits in
Refinery MACT 2 or the alternative
limits in this final rule during startup
and shutdown for FCCU and SRU on the
effective date of the final rule.
The flare work practice standards for
high-load flaring events (events
exceeding the smokeless capacity of the
flare) require development of FMP (or
revision of an existing plan) to
specifically consider emergency
shutdown and other high load events. In
this FMP, refinery owners or operators
must consider measures that can be
implemented to reduce the frequency
and magnitude of these high-load flaring
events. This may include installation of
a flare gas recovery system.
Additionally, the work practice
standards will require refinery owners
or operators to identify and implement
measures that may involve process
changes. Therefore, we are establishing
a compliance date of 3 years from the
effective date of the final rule for
refinery owners or operators to comply
with the work practice standards for
high load flaring events. We also note
that this compliance period is consistent
with the compliance time provided for
the flare operating limits.
For atmospheric PRD in HAP service
we are establishing a work practice
standard that requires a process hazard
analysis and implementation of a
minimum of three redundant measures
to prevent atmospheric releases.
Alternately, refinery owners or
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
operators may elect to install closed
vent systems to route these PRD to a
flare, drain (for liquid thermal relief
valves) or other control system. We
anticipate that sources will need to
identify the most appropriate preventive
measures or control approach; design,
install and test the system; install
necessary process instrumentation and
safety systems; and may need to time
installations with equipment shutdown
or maintenance outages. Therefore, we
have established a compliance date of 3
years from the effective date of the final
rule for refinery owners or operators to
comply with the work practice
standards for atmospheric PRD.
As proposed, we are requiring
compliance with the electronic
reporting provisions for performance
tests conducted for Refinery MACT 1
and 2 on the effective date of the final
rule.
Finally, we are finalizing additional
requirements for storage vessels under
CAA sections 112(d)(6) and (f)(2) with a
compliance date 90 days after the
effective date of the final rule, as
proposed.
H. What materials are being
incorporated by reference?
In this final rule, the EPA is including
regulatory text that includes
incorporation by reference. In
accordance with requirements of 1 CFR
51.5, the EPA is incorporating by
reference the following documents
described in the amendments to 40 CFR
63.14:
• ASTM D1945–03 (Reapproved
2010), Standard Test Method for
Analysis of Natural Gas by Gas
Chromatography, (Approved January 1,
2010).
• ASTM D1945–14, Standard Test
Method for Analysis of Natural Gas by
Gas Chromatography.
• ASTM D6196–03 (Reapproved
2009), Standard Practice for Selection of
Sorbents, Sampling, and Thermal
Desorption Analysis Procedures for
Volatile Organic Compounds in Air,
(Approved March 1, 2009).
• ASTM D6348–03 (Reapproved
2010), Standard Test Method for
Determination of Gaseous Compounds
by Extractive Direct Interface Fourier
Transform Infrared (FTIR) Spectroscopy,
including Annexes A1 through A8,
(Approved October 1, 2010).
• ASTM D6348–12e1, Standard Test
Method for Determination of Gaseous
Compounds by Extractive Direct
Interface Fourier Transform Infrared
(FTIR) Spectroscopy.
• ASTM D6420–99 (Reapproved
2010), Standard Test Method for
Determination of Gaseous Organic
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
Compounds by Direct Interface Gas
Chromatography-Mass Spectrometry.
• ASTM UOP539–12, Refinery Gas
Analysis by GC.
• BS EN 14662–4:2005, Ambient air
quality—Standard method for the
measurement of benzene
concentrations—Part 4: Diffusive
sampling followed by thermal
desorption and gas chromatography,
June 27, 2005.
• EPA–454/B–08–002, Quality
Assurance Handbook for Air Pollution
Measurement Systems, Volume IV:
Meteorological Measurements, Version
2.0 (Final), March 2008.
• EPA–454/R–99–005, Meteorological
Monitoring Guidance for Regulatory
Modeling Applications, February 2000.
• ISO 16017–2:2003(E): Indoor,
ambient and workplace air—Sampling
and analysis of volatile organic
compounds by sorbent tube/thermal
desorption/capillary gas
chromatography—Part 2: Diffusive
sampling, May 15, 2003.
• Air Stripping Method (Modified El
Paso Method) for Determination of
Volatile Organic Compound Emissions
from Water Sources’’ Revision Number
One, dated January 2003, Sampling
Procedures Manual, Appendix P:
Cooling Tower Monitoring, prepared by
Texas Commission on Environmental
Quality, January 31, 2003.4
The EPA has made, and will continue
to make, these documents available
electronically through
www.regulations.gov and/or in hard
copy at the appropriate EPA office (see
the ADDRESSES section of this preamble
for more information).
IV. What is the rationale for our final
decisions and amendments to the
Petroleum Refinery NESHAP and
NSPS?
A. Residual Risk Review for the
Petroleum Refinery Source Categories
1. What did we propose pursuant to
CAA section 112(f) for the Petroleum
Refinery source categories?
The results of our residual risk review
for the Petroleum Refinery source
categories were published in the June
30, 2014 proposal at (79 FR 36934
through 36942), and included
assessment of chronic and acute
inhalation risk, as well as multipathway
and environmental risk, to inform our
decisions regarding acceptability and
ample margin of safety. The results
indicated that both the actual and
4 The requirements in § 63.655(i)(5)(iii)(G)
associated with this incorporation by reference have
not changed, but are being modified to properly be
incorporated into § 63.14(s).
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
allowable inhalation cancer risks to the
individual most exposed are no greater
than approximately 100-in-1 million,
which is the presumptive limit of
acceptability. In addition, the maximum
chronic non-cancer target organ-specific
hazard index (TOSHI) due to inhalation
exposures was less than 1. The
evaluation of acute non-cancer risks,
which was conservative, showed acute
risks below a level of concern. Based on
the results of the refined site-specific
multipathway analysis, we also
concluded that the ingestion cancer risk
to the individual most exposed through
ingestion is considerably less than 100in-1 million. In determining risk
acceptability, we also evaluated
population impacts because of the large
number of people living near facilities
in the source category. We estimated
that 5-million people are exposed to
increased cancer risks of greater than 1in-1 million and 100,000 people are
exposed to increased cancer risks of
greater than 10-in-1 million, but, as
noted previously, no individual is
exposed to increased cancer risks of
greater than 100-in-1 million.
Considering the above information, we
proposed that the risks remaining after
implementation of the existing NESHAP
for the Refinery MACT 1 and 2 source
categories is acceptable. However, we
noted that the risks based on allowable
emissions are at the presumptive limit
of acceptable risk, and that a large
number of people are exposed to risks
of greater than 1-in-1 million, and we
solicited comment on whether EPA
should conclude that the risk was
unacceptable based on the health
information before the Agency. We also
proposed that the original Refinery
MACT 1 and 2 MACT standards, along
with the proposed requirements for
storage vessels, provide an ample
margin of safety to protect public health.
Finally, we proposed that it is not
necessary to set a more stringent
standard to prevent, taking into
consideration costs, energy, safety, and
other relevant factors, an adverse
environmental effect.
2. How did the risk review change for
the Petroleum Refinery source
categories?
As part of the final risk assessment,
we conducted a screening level analysis
of how the information we received
during the public comment period,
along with the changes we are making
to the proposed rule, would change our
proposed risk estimates (More details
can be found in the ‘‘Final Residual Risk
Assessment for the Petroleum Refining
Source Sector’’, Docket ID No. EPA–
HQ–OAR–2010–0682).
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
First, we received approximately 20
emissions inventory updates for specific
facilities. These updates included
revised emission estimates, revised
release latitude/longitude locations and
other release characteristic revisions.
The updates provided evidence that the
quantity of HAP emitted at these
specific facilities is lower than
considered in the risk modeling for the
proposed rule. Our assessment of the
effects of these changes suggests that the
cancer maximum individual risk (MIR)
based on actual emissions may be closer
to 40-in-1 million, as opposed to 60-in1 million, as projected at proposal. We
did not quantify the reductions in
chronic or acute non-cancer risks from
these updates. We calculated allowable
emissions using the Refinery Emissions
Model (REM), which estimates
emissions based on each refinery’s
capacities and throughputs [See
discussion at 79 FR 36888, June 30,
2014.] The allowable emission estimates
for point and fugitive sources were not
specific to a particular latitude/
longitude location so we assumed them
to release from the centroid of the
facility. Therefore, the predicted cancer
MIR of approximately 100-in-1 million
based on allowable emissions and
reported in the proposal risk
characterization does not change based
on the submitted emissions revisions.
We did not quantify changes to other
actual risk metrics as part of the
screening level analysis (i.e., incidence,
populations in risk bins, multipathway
and ecological analyses), but we would
expect some minor reductions from
those presented in the proposed risk
characterization.
Second, we are establishing work
practice standards in the final rule for
PRD releases and emergency flaring
events, which under the proposed rule
would not have been allowed. Thus,
because we did not consider such nonroutine emissions under our risk
evaluation for the proposed rule, we
performed a screening assessment of
risk associated with these non-routine
events for the final rule. [We provide
further details on the screening
approach in ‘‘Final Residual Risk
Assessment for the Petroleum Refining
Source Sector’’ in Docket ID No. EPA–
HQ–OAR–2010–0682.] We extracted
information on these events from the
2011 Petroleum Refinery ICR data that
included the process unit identification,
mass of emissions, duration of release,
and description of the incident. We
identified the highest HAP mass
releases for both PRDs and flares from
these non-routine events. We assumed
these HAP emission releases could
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
75187
occur at any facility in the source
category. Our analysis suggests that
these HAP emissions could increase the
MIR based on actual emissions by as
much as 2-in-1 million. Because the
PRD and flaring events were the worst
case HAP mass emission release events
reported in the 2011 Refinery ICR for
the source category, we are assuming
that actual and allowable risks are no
different for these events (i.e., a MIR of
2-in-1 million). A MIR increase of 2-in1 million attributable to these events,
added to our previous estimate for
allowable risk at proposal will not
appreciably change our proposed
determination that the MIR based on
allowable emissions are approximately
100-in-1 million. We note that the MIR
estimate attributable to these nonroutine PRD and flaring events was
estimated using a conservative,
screening-level assessment, while the
MIR estimate at proposal was based on
a refined risk assessment. By adding a
screening estimate to a refined risk
estimate, we are merely defining an
upper limit that we expect the
combined risks from both the routine
and non-routine emissions to be.
Similarly, we estimate chronic noncancer hazard index (HI) values
attributable to the additional exposures
resulting from non-routine flaring and
PRD HAP emissions to be well below 1
(HIimmune-system of 0.007) such that there
is no appreciable change in the
maximum chronic non-cancer HI of 0.9
estimated at proposal for routine
emissions, which was based on
neurological effects.
The screening analysis projects that
the maximum predicted acute noncancer risk from non-routine PRD and
flare emissions results in a hazard
quotient (HQ) based on a recommended
reference exposure level limit (REL) of
up to 14 from benzene emissions. While
the analysis shows that there is a
potential for HQs exceeding 1 for
benzene, because of the many
uncertainties and conservative nature of
this screening analysis, the likelihood of
such exposure and risk are low. At
proposal, we projected a HQ based on
the REL for benzene of up to 2 from
routine emissions. If we conservatively
combine the routine and non-routine
emissions analyses, we would expect
the potential for HQs based on the REL
for benzene to have the potential to
increase above 2. However, as projected
at proposal, we estimate that the acute
HQs calculated using acute exposure
guideline levels (AEGL) and emergency
response and planning guidelines
(ERPG) values for all pollutants
including benzene would still be well
E:\FR\FM\01DER2.SGM
01DER2
75188
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
below 1 considering both routine and
non-routine emissions.
Considering all of these factors, we do
not project risks to be significantly
different from what we proposed. Based
on the risk analysis, as informed by the
screening level analysis based on
information obtained during the
comment period, we are finalizing our
determination that the risk remaining
after promulgation of the NESHAP is
acceptable.
3. What key comments did we receive
on the risk review and what are our
responses?
We received numerous comments on
the residual risk assessment analyses
and results. We summarize the key
comments received below, along with
our responses. A complete summary of
all public comments received and our
responses are in the ‘‘Response to
Comment’’ Document in the public
docket (Docket ID No. EPA–HQ–OAR–
2010–0682).
Comment: Several commenters agreed
that the EPA has correctly concluded
that the proposed rule requirements
protect the public with an ample margin
of safety from refinery emissions. Other
commenters noted that EPA found
residual risks remaining after
implementation of the MACT standards
to be acceptable, and in light of the
acceptability determination argued that
the proposed changes to the rule are not
justified. The commenters noted that the
EPA’s detailed emissions inventory
assessment and risk modeling results
demonstrated that, at every U.S.
refinery, category-specific risks are
below the EPA’s presumptive limit of
acceptable risk (i.e., cancer risk of less
than 100-in-1 million).
Other commenters stated the EPA’s
risk estimates are understated and that
the EPA should reduce the benchmark
of what it considers acceptable lifetime
cancer risk instead of the upper limit of
100-in-1 million. One commenter
provided an extensive critique of the
cancer, chronic and acute affects levels
used in the risk assessment and
recommended that the EPA use
California Office of Environmental
Health Hazard Assessment’s (OEHHA)
new toxicity values for several
chemicals. The commenter provided
some references for the approaches used
to derive the California values. The
commenter also asserted that risks
would be unacceptable had these more
protective values been used in the risk
assessment. Some commenters stated
the risks from petroleum refinery
emissions are underestimated because
the EPA did not but should have
included interaction of multiple
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
pollutants, accounted for exposure to
multiple sources, and assessed the
cumulative risks from facility-wide
emissions and multiple nearby sources
impacting an area.
Response: The approximately 100-in1 million benchmark was established in
the Benzene NESHAP (54 FR 38044,
September 14, 1989), which Congress
specifically referenced in CAA section
112(f)(2)(B). While this presumptive
level provides a benchmark for judging
the acceptability of MIR, it is important
to recognize that it does not constitute
a rigid line for making that
determination. The EPA considers the
specific uncertainties of the emissions,
health effects and risk information for
the source category in question when
deciding whether the risk posed by that
source category is acceptable. In
addition, the source category-specific
decision of what constitutes an
acceptable level of risk is a holistic one;
that is, the EPA considers all potential
health impacts—chronic and acute,
cancer and non-cancer, and
multipathway—along with their
uncertainties, when determining
whether the source category presents an
unacceptable risk.
Regarding the comment that in light
of the acceptability determination the
proposed changes to the rule are not
justified, we note that we also are
required to ensure that the standards
provide an ample margin of safety to
protect public health. That analysis is
separate from the acceptability analysis,
and the determination of acceptability
does not automatically lead us to
conclude that the standards provide an
ample margin of safety to protect public
health.
Regarding the comments that the EPA
should use the new California OEHHA
values, we disagree. The EPA’s
chemical-specific toxicity values are
derived using risk assessment
guidelines and approaches that are well
established and vetted through the
scientific community, and follow
rigorous peer review processes.5 The
RTR program gives preference to the
EPA values for use in risk assessments
and uses other values, as appropriate,
when those values are derived with
methods and peer review processes
consistent with those followed by the
EPA. The approach for selecting
appropriate toxicity values for use in the
RTR Program has been endorsed by the
Science Advisory Board (SAB).6
5 Integrated Risk Information System (IRIS). IRIS
Guidance documents available at https://www.epa.
gov/iris/backgrd.html.
6 https://yosemite.epa.gov/sab/sabproduct.nsf/0/
b031ddf79cffded38525734f00649caf!Open
Document&TableRow=2.3#2.
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
The EPA scientists reviewed the
information provided by the commenter
regarding the California values and
concluded that further information is
needed to evaluate the scientific basis
and rationale for the recent changes in
California OEHHA risk assessment
methods. The EPA will work on
gathering the necessary information to
conduct an evaluation of the scientific
merit and the appropriateness of the use
of California OEHHA’s new toxicity
values in the agency decisions. Until the
EPA has completed its evaluation, it is
premature to determine what role these
values might play in the RTR process.
Therefore, the EPA did not use the new
California OEHHA toxicity values as
part of this current action. For more
detailed responses regarding
appropriate reference values for specific
pollutants, see the ‘‘Response to
Comment’’ document in the public
docket (Docket ID No. EPA–HQ–OAR–
2010–0682).
Concerning comments that we should
consider aggregate risks from multiple
pollutants and sources, we note that we
have done this to the extent it is
appropriate to do so. We modeled
whole-facility risks for both chronic
cancer and non-cancer impacts to
understand the risk contribution of the
sources within the Petroleum Refinery
source categories. The individual cancer
risks for the source categories were
aggregated for all carcinogens. In
assessing non-cancer hazard from
chronic exposures to pollutants that
have similar modes of action or (where
this information is absent) that affect the
same target organ, we summed the HQs.
This process creates, for each target
organ, a TOSHI, defined as the sum of
HQs for individual HAP that affect the
same organ or organ system. Wholefacility risks were estimated based on
the 2011 ICR emissions data obtained
from facilities, which included
emissions from all sources at the
refinery, not just Refinery MACT 1 and
2 emission sources (e.g., emissions were
included for combustion units and units
subject to the Hazardous Organic
NESHAP, if present at the refinery). We
disagree with the commenter’s assertion
that additional quantitative assessment
of risks from sources outside the source
category is required under the statute.
The statute requires the EPA to provide
the quantitative risk information
necessary to inform RTR regulatory
decisions, and to this end, the EPA
conducted a comprehensive assessment
of the risks associated with exposure to
the HAP emitted by the source category
and supplemented that with additional
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
information available about other
possible concurrent and relevant risks.
Further, the risk assessment modeling
accounts for the effects of multiple
facilities that may be in close proximity
when estimating concentration and risk
impacts at each block centroid. When
evaluating the risks associated with a
particular source category, we combined
the impacts of all facilities within the
same source category and assessed
chronic exposure and risk for all census
blocks with at least one resident (i.e.,
locations where people may reasonably
be assumed to reside). The MIR
considers the combined impacts of all
sources in the category that may be in
close proximity (i.e., cumulative impact
of all refineries).
Comment: Several commenters stated
that the EPA underestimated exposure
because emissions are underreported
and underestimated. The commenters
noted that for the risk assessment for the
refineries rule, the EPA evaluated (1) the
emissions reported to the agency
pursuant to the 2011 Petroleum Refinery
ICR as sources’ ‘‘actual’’ emissions, and
(2) the emissions the EPA estimates that
the existing standards currently allow
sources to emit using the REM, which
it describes as ‘‘allowable’’ emissions.
According to the commenters, both the
EPA’s ‘‘actual’’ and ‘‘allowable’’
emissions data sets are incomplete and
undercount emissions, causing the EPA
to significantly underestimate the
resulting risk in its risk analysis. For
example, the commenters noted that the
EPA assumed the flare destruction
efficiency to be 98 percent, while the
EPA’s own estimates suggest flare
efficiency is 93.9 percent. The
commenters also noted that the EPA has
further understated risks by ignoring
emissions during unplanned SSM
events and by ignoring HAP for which
no reference values are established. One
commenter cited the TCEQ Emissions
Event Database as evidence that SSM
emissions are a severe public health
problem because data show that nearly
1 million pounds of HAP are reported
from Texas refineries between 2009 and
2013. According to these commenters,
the EPA needs to adopt standards that
provide greater protection, including
protection from the risks of accidents.
Response: We used the best and most
robust facility-specific HAP emissions
inventory available to us, which was the
2011 ICR, in performing the analysis for
the proposed rule. We conducted a
thorough and exhaustive review of the
data submitted through the ICR and we
followed up on source-specific
information on a facility-by-facility
basis, as documented in the ‘‘Emissions
Data Quality Memorandum and
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Development of the Risk Model Input
File’’ (see Docket ID No. EPA–HQ–
OAR–2010–0682–0076). In addition, we
took steps ahead of issuing the 2011 ICR
to make sure that facilities could, as
accurately as practicable, estimate their
HAP emissions for purposes of
responding to the inventory portion of
that ICR. We prepared a Refinery
Protocol to provide guidance to refinery
owners or operators to use the best
available, site-specific data when
developing their emissions inventory, to
ensure all emission sources are included
in the inventory, and to have a
consistent set of emission factors that all
respondents use if no site-specific
emissions data were available. If sitespecific emissions data were available,
sites were to use these data
preferentially over the default factors.
We developed the default factors
provided in the protocol from the best
data available at the time.
The ICR-submitted information for
allowable emissions did not include
emission estimates for all HAP and all
emission sources. Consequently, we
used the REM to estimate allowable
emissions. The REM relies on model
plants that vary based on throughput
capacity. Each model plant contains
process-specific default emission
factors, adjusted for compliance with
the Refinery MACT 1 and 2 emission
standards.
We agree with the commenters that
studies have shown that many refinery
flares are operating less efficiently than
98 percent. Prior to proposing this rule,
we conducted a flare ad hoc peer review
to advise the EPA on factors affecting
flare performance (see discussion in the
June 30, 2014, proposal at 79 FR 36905).
However, we disagree with the
commenters that the risk analysis
should consider this level of
performance since the existing MACT
standard does not allow it. For purposes
of the risk analysis, we evaluate whether
it is necessary to tighten the existing
MACT standard in order to provide an
ample margin of safety. Thus, in
reviewing whether the existing
standards provide an ample margin of
safety, we review the level of emissions
the MACT standards allow. In the
present case, we considered the level of
performance assumed in establishing
the MACT standard for purposes of
determining whether the MACT
standard provides an ample margin of
safety. However, we did recognize that
facilities were experiencing
performance issues with flares and that
many flares were not meeting the
assumed performance level at the time
we promulgated the MACT standard.
Thus, we proposed, and are finalizing,
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
75189
revisions to the flare operating
requirements to ensure that the flares
meet the required performance level.
These provisions are consistent with the
EPA’s goals to improve the effectiveness
of our rules.
Similarly, we do not include startup,
shutdown (including maintenance
events) and malfunction emissions that
are not allowed under the standard as
part of our evaluation of whether the
standards provide an ample margin of
safety. Regarding the HAP emissions
from SSM events that the commenter is
concerned with, we note that our review
of the TCEQ incident database indicates
that many of the large reported release
events were of SO2 emissions and only
a few had significant HAP emissions.
Because in the final rule we are
establishing work practice standards for
PRD and emergency flaring events, we
performed a screening-level risk
analysis to address changes in facility
HAP emission releases due to these
events. Details on this analysis are
presented in the final risk report for the
source category (For more details see
Appendix 13 of the ‘‘Final Residual Risk
Assessment for the Petroleum Refining
Source Sector,’’ Docket ID No. EPA–
HQ–OAR–2010–0682).
As for HAP with no reference value,
the SAB addressed this issue in its May
7, 2010, response to the EPA
Administrator. In that response, the
SAB Panel recommended that, for HAP
that do not have dose-response values
from the EPA’s list, the EPA should
consider and use, as appropriate,
additional sources for such values that
have undergone adequate and rigorous
scientific peer review. The SAB panel
further recommended that the inclusion
of additional sources of dose-response
values into the EPA’s list should be
adequately documented in a transparent
manner in any residual risk assessment
case study. We agree with this approach
and have considered other sources of
dose-response data when conducting
our risk determinations under RTR.
However, in some instances no sources
of information beyond the EPA’s list are
available. Compounds without health
benchmarks are typically those without
significant health effects compared to
compounds with health benchmarks,
and in such cases we assume these
compounds will have a negligible
contribution to the overall health risks
from the source category. A tabular
summary of HAPs that have dose
response values for which an exposure
assessment was conducted is presented
in Table 3.1–1 of the ‘‘Final Residual
Risk Assessment for the Petroleum
Refining Source Sector’’, Docket ID No.
EPA–HQ–OAR–2010–0682.
E:\FR\FM\01DER2.SGM
01DER2
75190
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
Comment: A few commenters asserted
that the EPA should decide that it is
unjust and inconsistent with the CAA’s
health protection purpose to allow the
high health risks caused by refineries to
fall disproportionately on communities
of color and lower income communities
who are least equipped to deal with the
resulting health effects. Because of that
disparity, the commenter stated that the
EPA should recognize that the risks
found are unacceptable and set stronger
national standards for all exposed
Americans.
Response: For this rulemaking, the
EPA conducted both pre- and postcontrol risk-based assessments with
analysis of various socio-economic
factors for populations living near
petroleum refineries (see Docket ID Nos.
EPA–HQ–OAR–2010–0682–0226 and
–0227) and determined that there are
more African-Americans, Other and
multiracial groups, Hispanics, lowincome individuals, and individuals
with less than a high school diploma
compared to national averages. In
determining the need for tighter residual
risk standards, the EPA strives to limit
to no higher than 100-in-1 million the
estimated cancer risk for persons living
near a plant if exposed to the maximum
pollutant concentration for 70 years and
to protect the greatest number of
persons to an individual lifetime risk of
no higher than 1-in-1 million. Although
we consider the risk for all people
regardless of racial or socioeconomic
status, communities near petroleum
refineries will particularly benefit from
the risk reductions associated with this
rule. In particular, as discussed later,
the fenceline monitoring work practice
standard will be a further improvement
in the way fugitive emissions are
managed and will provide an extra
measure of protection for surrounding
communities.
4. What is the rationale for our final
decisions for the risk review?
As described in section IV.A.2 of this
preamble, we performed a screeninglevel analysis to assess the risks
associated with inventory updates we
received for specific facilities and with
emissions events that were previously
not included in the risk assessment
because the proposed rule did not allow
them. Because we are finalizing work
practice standards to regulate emission
events associated with PRD releases and
emergency flaring, we considered the
effect these work practice standards
would have on risks. As discussed in
section IV.A.2 of this preamble, we
project that accounting for these
emergency events in the baseline risks
after implementation of the MACT
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
standards does not appreciably change
the risks, and at most, could increase
the proposed rule estimate of MIR by
approximately 2-in-1 million. Therefore,
we would project that any controls
applied to these emergency events,
including the work practice standards
for PRDs and emergency flaring in this
final rule, would not appreciably change
the proposed post-control risks.
Although we would anticipate minimal
additional risk reductions, we reviewed
more stringent alternatives to the work
practice standards for PRD releases and
emergency flaring events included in
this final rule, and we found that the
costs of increasing flare capacity to
control all PRD releases and to eliminate
all visible emissions during emergency
flaring were too high. We estimate the
capital costs of applying the velocity
and visible emissions limit at all times
would be approximately $3 billion, and
we estimate that the costs of controlling
all PRD releases with flares would be
approximately $300 million. [See the
discussion in the ‘‘Flare Control Option
Impacts for Final Refinery Sector Rule’’,
Docket ID No. EPA–HQ–OAR–2010–
0682 and the PRD work practice
standard discussion in section IV.C of
this preamble.] Further, we did not
receive comments on additional control
technologies that we should have
considered for other emission sources
(e.g., tanks, DCUs) beyond those
considered and described at proposal.
Consequently, as discussed in section
IV.A.2, we conclude that the risks from
the Petroleum Refinery source
categories are acceptable and that, with
the additional requirements for storage
vessels that we are finalizing, as
proposed, the Refinery MACT 1 and 2
rules provide an ample margin of safety
to protect public health. We also
maintain, based on the rationale
presented in the preamble to the
proposed rule, that the current
standards prevent, taking into
consideration costs, energy, safety and
other relevant factors, an adverse
environmental effect.
B. Technology Review for the Petroleum
Refinery Source Categories
1. What did we propose pursuant to
CAA section 112(d)(6) for the Refinery
MACT 1 (40 CFR part 63, subpart CC)
source category?
The results of our technology review
for the Petroleum Refinery source
categories were published in the June
30, 2014, proposal at (79 FR 36913
through 36928). The technology review
was conducted for both MACT source
categories as described below.
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
a. Refinery MACT 1
Refinery MACT 1 sources include
MPV, storage vessels, equipment leaks,
gasoline loading racks, marine vessel
loading operations, cooling towers/heat
exchange systems and wastewater.
Based on technology reviews for the
sources described above, we proposed
that it was not necessary to revise
Refinery MACT 1 requirements for
MPV, gasoline loading racks, cooling
towers/heat exchange systems, and
wastewater. For storage vessels, we
proposed revisions pursuant to the
technology review. Specifically, we
proposed to cross-reference the storage
vessel requirements in the Generic
MACT (40 CFR part 63, subpart WW) to
require controls on floating roof fittings
(e.g., guidepoles, ladder wells and
access hatches) and to revise the
definition of Group 1 storage vessels to
include smaller tanks with lower vapor
pressures. For equipment leaks, we
proposed to allow refineries to meet
LDAR requirements in Refinery MACT
1 by monitoring for leaks via optical gas
imaging in place of the EPA Method 21,
using monitoring requirements to be
specified in a not-yet-proposed
appendix K to 40 CFR part 60. For
marine vessel loading, we proposed to
amend the Marine Tank Vessel Loading
Operations MACT standards (40 CFR
part 63, subpart Y) to require small
marine vessel loading operations (i.e.,
operations with HAP emissions less
than 10/25 tpy) and offshore marine
vessel loading operations at petroleum
refineries to use submerged filling based
on the cargo filling line requirements in
46 CFR 153.282.
We also proposed an additional work
practice standard under the technology
review to manage fugitive emissions
from the entire petroleum refinery
through a fenceline monitoring and
corrective action standard. As part of
the work practice standard, we specified
the monitoring technology and
approach that must be used, and we
developed a fenceline benzene
concentration action level above which
refinery owners or operators would be
required to implement corrective action
to reduce their fenceline concentration
to below this action level. The action
level we proposed was consistent with
the emissions projected from fugitive
sources compliant with the provisions
of the refinery MACT standards as
modified by the additional controls
proposed for storage vessels.
b. Refinery MACT 2
The Refinery MACT 2 source category
regulates HAP emissions from FCCU,
CRU and SRU process vents. We
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
proposed to revise Refinery MACT 2 to
incorporate the developments in
monitoring practices and control
technologies reflected in Refinery NSPS
subpart Ja (73 FR 35838). This included
proposing to incorporate the Refinery
NSPS subpart Ja PM limit for new FCCU
sources and to revise the monitoring
provisions in Refinery MACT 2 to
require all FCCU sources to meet
operating limits consistent with the
requirements in Refinery NSPS subpart
Ja. The existing MACT standard
provided that a refiner could
demonstrate compliance with the PM
limit in the MACT by meeting the 30percent opacity limit requirement of
Refinery NSPS subpart J; we proposed
to eliminate that provision and instead
establish control device operating limits
or site-specific opacity limits similar to
those required in Refinery NSPS subpart
Ja. We also proposed to incorporate the
use of 3-hour averages rather than daily
averages for monitoring data to
demonstrate compliance with the FCCU
site-specific opacity and Ni operating
limits. We proposed additional control
device-specific monitoring alternatives
for various control devices on FCCU,
including BLD monitoring as an option
to COMs for owners or operators of
FCCU using fabric filter-type control
systems, and total power and secondary
current operating limits for owners or
operators of ESPs. We also proposed to
add a requirement to perform daily
checks of the air or water pressure to
atomizing spray nozzles for owners or
operators of FCC wet gas scrubbers.
Finally, we proposed to require a
performance test once every 5 years for
all FCCU in place of the one-time
performance test required by the current
Refinery MACT 2.
At proposal, we did not identify any
developments in practices, processes
and control technologies for CRU
process vents based on our technology
review. For SRU, we proposed to
include the Refinery NSPS subpart Ja
allowance for oxygen-enriched air as a
development in practice and to allow
SRU to comply with Refinery NSPS
subpart Ja as a means of complying with
Refinery MACT 2.
tkelley on DSK3SPTVN1PROD with RULES2
2. How did the technology review
change for the Petroleum Refinery
source categories?
a. Refinery MACT 1
We are finalizing most of our
technology review decisions for
Refinery MACT 1 emissions sources as
proposed; however, as described briefly
below, we are revising certain proposed
requirements.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
We are not taking final action
adopting the use of appendix K to 40
CFR part 60 for optical gas imaging for
refinery equipment subject to the LDAR
requirements in Refinery MACT 1
because we have not yet proposed
appendix K.
After considering the public
comments, we are finalizing the
proposed fenceline monitoring
requirements, with a few revisions.
First, we have made numerous
clarifications in this final rule to the
language for the fenceline monitoring
siting method and analytical method
(i.e., Methods 325 A and B,
respectively). Specific comments on
these methods, along with our responses
and explanations of the revisions to the
regulatory text are discussed in the
‘‘Response to Comment’’ document.
Second, we are finalizing a revised
compliance schedule for fenceline
monitoring, which will require refinery
owners or operators to have the
fenceline monitors in place and
collecting benzene concentration data
no later than 2 years from the effective
date of the final rule, as opposed to 3
years in the proposed rule. Third, we
have removed the requirement for
refinery owners or operators to obtain
the EPA approval for the corrective
action plan. Fourth, we are requiring the
submittal of the fenceline monitoring
data on a quarterly basis, as opposed to
on a semiannual basis as proposed.
Fifth, we are providing guidelines for
operators to use in requesting use of an
alternative fenceline monitoring
technology to the passive sorbent
samplers set forth in Method 325B.
Finally, to reduce the burden of
monitoring, we are finalizing provisions
that would allow refinery owners or
operators to reduce the frequency of
fenceline monitoring for areas that
consistently stay well below the
fenceline benzene concentration action
level. Specifically, we are allowing
refinery owners or operators to monitor
every other two weeks (i.e., skip period
monitoring) if over a two-year period,
each sample collected at a specific
monitoring location is at or below 0.9
mg/m3. If every sample collected from
that sampling location during the
subsequent 2-years is at or below 0.9 mg/
m3, the monitoring frequency may be
reduced from every other two weeks to
quarterly. After an additional two years,
the monitoring can be reduced to
semiannually and finally to annually,
provided the samples continue to be at
or below 0.9 mg/m3 during all sampling
events at that location. If at any time a
sample for a monitoring location that is
monitored at a reduced frequency
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
75191
returns a concentration greater than 0.9
mg/m3, the owner or operator must
return to the original sampling
requirements for one quarter (monitor
every two weeks for the next six
monitoring periods for that location); if
every sample collected from this quarter
is at or below 0.9 ug/m3, then the
sampling frequency reverts back to the
reduced monitoring frequency for that
monitoring location; if not then the
sampling frequency reverts back to the
original biweekly monitoring frequency.
b. Refinery MACT 2
We are finalizing, as proposed, our
determination that it is not necessary to
revise the requirements for CRU
pursuant to the technology review and
we are finalizing our determination that
it is necessary to revise the MACT for
SRU and FCCU. For SRU, we are
finalizing the revisions as proposed. For
FCCU, we are making modifications to
the proposed requirements in light of
public comment.
As discussed previously, we proposed
to remove the alternative in Refinery
MACT 2 for owners or operators to
demonstrate compliance with the PM
limits on FCCU by meeting a 30-percent
opacity standard as provided in
Refinery NSPS subpart J and instead
make the FCCU operating limits in
Refinery MACT 2 consistent with
Refinery NSPS subpart Ja. Based on the
Refinery NSPS subpart J review in 2008,
we determined that a 30-percent opacity
limit does not adequately assure
compliance with the PM emissions limit
(see discussion in the proposed rule at
79 FR 36929, June 30, 2014). Thus, we
included other monitoring approaches
in Refinery NSPS subpart Ja.
Comments received on this proposal,
along with data available to the Agency,
confirmed that the 30-percent opacity
standard is not adequate on its own to
demonstrate compliance with the PM
(or metal HAP) emissions limit in
Refinery MACT 2. We also received
comments that the site-specific opacity
alternative, which is the only
compliance option proposed for FCCU
with tertiary cyclones, would essentially
require owners or operators with these
FCCU configurations to meet an opacity
limit of 10-percent. According to
commenters, opacity increases with
decreasing particle size, so that it is
common to exceed 10-percent opacity
during soot blowing or other similar
events that produce very fine
particulates even though mass
emissions have not changed
appreciably.
Based on the available data, we have
determined that a 20-percent opacity
operating limit is well correlated with
E:\FR\FM\01DER2.SGM
01DER2
75192
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
facilities meeting a limit of 1.0 lb PM/
1,000 lbs coke burn-off. Therefore, we
are retaining the option in Refinery
MACT 2 to comply with Refinery NSPS
subpart J except we are adding a 20percent opacity operating limit in
Refinery MACT 2, evaluated on a 3-hour
basis. To ensure that FCCU owners or
operators complying with the Refinery
NSPS subpart J option can meet the 1.0
lb PM/1,000 lbs emissions limit at all
times, we are finalizing requirements
that owners or operators conduct the
performance test during higher PM
periods, such as soot blowing. Where
the PM emissions are within 80-percent
of the PM limit during any periodic
performance test, we are requiring the
refinery owner or operator to conduct
subsequent performance tests on an
annual basis instead of on a 5-year basis.
We are finalizing our proposed
requirement that compliance with the
control device operating limits in the
other compliance alternatives be
demonstrated on a 3-hour basis, instead
of the 24-hour basis currently allowed
in Refinery MACT 2.
3. What key comments did we receive
on the technology review, and what are
our responses?
a. Refinery MACT 1
The majority of comments received
regarding the proposed amendments to
Refinery MACT 1 pursuant to our
technology review dealt with the
proposed fenceline monitoring
requirements. The primary comments
on the fenceline monitoring
requirements are in this section along
with our responses. Comment
summaries and the EPA’s responses for
additional issues raised regarding the
proposed requirements resulting from
our technology review are in the
‘‘Response to Comment’’ document in
the public docket (Docket ID No. EPA–
HQ–OAR–2010–0682).
tkelley on DSK3SPTVN1PROD with RULES2
i. Legal Authority and Need for
Fenceline Monitoring
Comment: Numerous commenters
claimed that the proposed fenceline
monitoring program would unlawfully
impose what is effectively an ambient
air quality standard for benzene, which
is not authorized by CAA section 112,
which only authorizes the control of
emission sources. The commenters
argued it is an ambient standard because
sources are required to meet the
benzene level set or ‘‘perform injunctive
relief which may or may not address the
source of the benzene.’’ The commenter
quoted language from the proposal as
support that EPA has described the
benzene level as an ambient standard:
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
‘‘We are proposing a HAP concentration
to be measured in the ambient air
around a refinery, that if exceeded,
would trigger corrective action to
minimize fugitive emissions.’’ 79 FR at
36920 (June 30, 2014). The commenter
further noted that this requirement is
not just ‘‘monitoring’’ because it
establishes a ‘‘not-to-be exceeded’’ level.
Therefore, the commenters stated, the
EPA should not finalize this portion of
the proposal.
Response: We disagree with the
comment that the fenceline proposal is
an ambient air standard. First, the
owner or operator must place the
monitors on the facility fenceline to
measure emissions from the facility, i.e.,
on the property of the refiner. While we
recognize that we used the term
‘‘ambient air’’ in the preamble to the
proposal, we note that the placement
requirements for the monitors make
clear that the monitors are not
monitoring ambient air, which EPA has
defined at 40 CFR 50.1(e) as ‘‘that
portion of the atmosphere, external to
buildings, to which the general public
has access.’’ Second, the proposed EPA
Method 325A sets out procedures to
subtract background concentrations and
contributions to the fenceline benzene
concentrations from non-refinery
emission sources, so that the benzene
concentrations measured are
attributable to the refinery. In other
words, the fenceline monitoring work
practice standard uses a benzene
concentration difference, referred to as
the DC (essentially an upwind and
downwind concentration difference) to
isolate the refinery’s emissions
contribution.
Furthermore, we disagree that the fact
that refiners are required to perform
corrective action if the fenceline
benzene concentration action level is
exceeded makes the benzene action
level an ambient standard. As an initial
matter sources are not directly
responsible for demonstrating that an
area is meeting an ambient standard;
rather that burden falls on states. See
e.g., CAA section 110(a)(2). Moreover,
the ‘‘corrective action’’ is simply that
sources must ensure that fugitive
emission sources on the property are not
emitting HAP at levels that will result
in exceedances of the fenceline benzene
concentration action level. In other
words, the purpose of the fenceline
monitoring work practice is to ensure
that sources are limiting HAP emissions
at the fenceline, which are solely
attributable to emissions from sources
within the facility. In fact, the fenceline
benzene concentration action level was
established using emissions inventories
reported by the facilities, assuming
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
compliance with the MACT standards.
Finally, monitoring is conducted as part
of the work practice standard to identify
sources that will require additional
controls to reduce their impact on the
fenceline benzene concentration. In that
sense, the fenceline monitoring work
practice standard is not different than,
for example, our MACT standard for
refinery heat exchangers. If a facility is
exceeding the relevant cooling water
pollutant concentration ‘‘level’’ when it
performs a periodic test, it must
undertake corrective action to bring the
concentration down below the action
level.
Comment: Several commenters noted
that EPA’s authority under section
112(d) is to set ‘‘emissions standards’’
and quoted the CAA definition of that
term: ‘‘A requirement . . . which limits
the quantity, rate, or concentration of
emissions of air pollutants on a
continuous basis, including any
requirement relating to the operation or
maintenance of a source to assure
continuous emission reduction, and any
design, equipment, work practice or
operational standard promulgated under
this Act.’’ 42 U.S.C. 7602(k). The
commenters argued that the proposed
fenceline monitoring standard does not
meet this definition because it would
not ‘‘limit the quantity, rate, or
concentration of emissions’’ from any
given emissions point. Also, the
commenters claimed that the EPA did
not designate fenceline monitoring as a
work practice under CAA section 112(h)
since the EPA did not even mention
CAA section 112(h), nor did it conduct
any analysis to show that fenceline
monitoring meets the CAA section
112(h) factors.
Response: We disagree with the
commenters’ assertion that the proposed
fenceline monitoring work practice
standard is not authorized under CAA
section 112(d)(6). Contrary to the
commenter’s claims, we specifically
proposed the fenceline monitoring
standard under CAA section 112(d)(6) to
be a work practice standard that is
applied broadly to fugitive emissions
sources located at petroleum refineries.
As discussed above, the proposed
standard does more than impose
monitoring as some commenters
suggested; it also will limit emissions
from refineries because it requires the
owner or operator to identify and reduce
HAP emissions through a monitoring
and repair program, as do many work
practice standards authorized under
CAA Section 112(h) and 112(d).
We note that the sources addressed by
the fenceline monitoring standard—
refinery fugitive emissions sources such
as wastewater collection and treatment
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
operations, equipment leaks, heat
exchange systems and storage vessels in
the Refinery MACT 1 rule—are already
subject to work practice standards. Our
review of these requirements indicates
that this fenceline monitoring work
practice standard would be a further
improvement in the way fugitive
emissions are managed and would
provide an extra measure of protection
for surrounding communities. The
commenter claims EPA did not analyze
how the fenceline monitoring
requirement meets the criteria in section
112(h). However, that is a
misinterpretation of how the criteria
apply. The criteria are assessed with
regard to whether it is feasible to
‘‘prescribe or enforce an emission
standard for a source’’, and do not apply
to the work practice standard.
Consistent with the criteria in section
112(h)(2), we determined and
established that work practice standards
are appropriate for these Refinery
MACT fugitive emissions at the time we
established the initial MACT standard.
In the proposal, (79 FR at 36919, June
30, 2014), we reaffirmed that it is
impracticable to directly measure
fugitive emission sources at refineries
but did not consider it necessary to
reiterate these findings as part of this
proposal to revise the existing MACT for
these sources under CAA section
112(d)(6). We note that the commenters
do not provide any grounds to support
a reevaluation of whether these fugitive
emission sources are appropriately
regulated by a work practice standard.
Comment: Several commenters
questioned the EPA’s authority under
the CAA to promulgate a rule that
amounts to an ongoing information
gathering and reporting obligation. The
commenters stated that the EPA has not
demonstrated that the proposed
fenceline monitoring program
represents an actual emission reduction
technology improvement. A commenter
stated that compliance assurance
methods, including monitoring, for
fugitive emissions and other emission
standards are established as part of the
emission standard and EPA’s authority
to gather information that is not directly
required for compliance with a specific
standard but is related to air emissions
is found in CAA section 114. Under
CAA section 114, the requirement must
be related to one of the stated purposes
and must be reasonable. The commenter
did not believe that the EPA has
demonstrated that the costs of fenceline
monitoring are reasonable in light of the
information already available to the EPA
and in light of many other means by
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
which the EPA could obtain such
information.
Response: We disagree with the
commenters’ assertion that the authority
for the fenceline monitoring
requirement falls under CAA section
114 and not CAA section 112(d) because
it is an ‘‘ongoing information gathering
and reporting obligation.’’ The issue
here is not whether EPA could have
required the fenceline monitoring
requirement under CAA section 114, but
rather did EPA support that it was a
development in processes practices or
controls technology under section
112(d)(6).
As an initial matter, we disagree with
the commenters’ characterization of the
fenceline monitoring standard as ‘‘an
information gathering and reporting
obligation.’’ We have repeatedly stated
that we consider the fenceline
monitoring requirement to be a work
practice standard that will ensure
sources take corrective action if
monitored benzene levels (as a surrogate
for HAP emissions from fugitive
emissions sources) exceed the fenceline
benzene concentration action level. The
standard requires refinery owners or
operators to monitor the benzene
concentration at the refinery perimeter,
to evaluate the refinery’s contribution as
estimated by taking the concentration
difference between the highest and
lowest concentrations (DC) in each
period, and to conduct root cause
analysis and take corrective action to
minimize emissions if the concentration
difference is higher (on an annual
average) than the benzene concentration
action level. Thus, the fenceline
monitoring requirement goes well
beyond ‘‘information gathering and
reporting.’’
In addition, the commenters again
read section 112(d)(6) too narrowly by
suggesting that a program considered as
a development must be a ‘‘technology’’
improvement. Section 112(d)(6) of the
CAA requires the EPA to review and
revise the MACT standards, as
necessary, taking into account
developments in ‘‘practices, processes
and control technologies.’’ Consistent
with our long-standing practice for the
technology review of MACT standards,
in section III.C of the proposal (see 79
FR 36900, June 30, 2014), we list five
types of ‘‘developments’’ we consider.
Fenceline monitoring fits squarely
within two of those five types of
developments (emphasis added):
• Any add-on control technology or
other equipment that was not identified
and considered during development of
the original MACT standards.
• Any work practice or operational
procedure that was not identified or
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
75193
considered during development of the
original MACT standards.
As used here, ‘‘other equipment’’ is
clearly separate from and in addition to
‘‘add-on control’’ technology and is
broad enough to include monitoring
equipment. In this case, fenceline
monitoring is a type of equipment that
we did not identify and consider during
development of the original MACT
standards. Additionally, the fenceline
standard is a work practice standard,
involving monitoring, root cause
analysis and corrective action not
identified at the time of the original
MACT standards. Therefore, the
fenceline requirements are a
development in practices that will
improve how facilities manage fugitive
emissions and EPA appropriately relied
on section 112(d)(6) in requiring this
standard.
Comment: Some commenters
contended that because the fenceline
monitoring standard is in essence an
ambient standard, the only justification
that can be used to support it would be
under CAA section 112(f)(2). The
commenters stated that EPA determined
that the MACT standards pose an
acceptable level of risk and protect the
public health with an ample margin of
safety and thus, section 112(f) does not
support imposition of the fenceline
monitoring requirement. Several
commenters stated that the Agency
expressly acknowledges that imposition
of additional emission standards for
fugitive emissions from refinery sources
are not warranted under CAA section
112(f). Some commenters suggested that
because the existing MACT standards
protect public health with an ample
margin of safety, the fenceline
monitoring requirement imposes an
unnecessary burden on industry
because it is not necessary to achieve
acceptable risk or provide an ample
margin of safety.
Response: EPA is not relying on
section 112(f)(2) as the basis for the
fenceline monitoring requirement. As
provided in a previous response to
comment, we disagree with the
commenters that the fenceline
monitoring requirement is an ambient
standard and therefore, we do not need
to consider what authority would be
appropriate for establishing an ambient
standard that would apply to fugitive
sources of emissions at refineries. We
also disagree with the commenters who
suggest that EPA may not require
fenceline monitoring pursuant to
section 112(d)(6) because EPA has not
determined that fenceline monitoring is
necessary to ensure an acceptable level
of risk or the provide an ample margin
of safety. Section 112(d)(6) does not
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75194
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
require EPA to factor in the health
considerations provided in section
112(f)(2) when making a determination
whether it is ‘‘necessary’’ to revise the
MACT.
Comment: Commenters stated that the
pilot studies undertaken by the EPA and
pilot studies undertaken by the refining
industry (see the API Fenceline Study in
the docket for this rulemaking)
demonstrate either that there is no
underestimation of emissions and thus,
no need for the fenceline monitoring
work practice standard, or that fenceline
benzene data cannot be used to validate
emission estimates. Commenters stated
that none of the refineries in the API
study of the proposed refinery fenceline
standard had study-averaged DC
concentrations that exceeded the
proposed action level of 9 mg/m3 and
thus the study provides some evidence
that U.S. refineries are not
underestimating emissions.
Furthermore, the commenter stated that
there is significant ambient air
monitoring performed that further
supports low benzene concentrations in
the vicinities of refineries and cited
ambient monitoring data collected by
the Southeast Texas Regional Planning
Commission Air Quality Group and the
Texas Commission on Environmental
Quality (TCEQ).
Response: We disagree that the API
fenceline study demonstrates that there
is no underestimation of emissions. The
API report referred to by the commenter
actually shows higher DC concentrations
than what we expected, when we
compare the distribution of DC’s
presented in the API fenceline study to
the distribution of benzene
concentrations at the 142 refineries we
modeled (see memorandum ‘‘Fenceline
Ambient Benzene Concentrations
Surrounding Petroleum Refineries’’,
EPA–HQ–OAR–2010–0682–0208). [Note
that API did not identify the facilities in
their study, so we were not able to
perform a one-to-one comparison of the
measured DC concentrations with the
modeled fenceline concentrations.]
Furthermore, the API conducted the
study primarily during the fall and
winter months (October to March) when
the ambient temperatures are lower than
the annual averages. While this may not
impact equipment leak emissions,
temperature can have a significant
impact on emissions from storage
vessels and wastewater treatment
systems, so it is likely that the annual
average DC for the facilities tested could
be higher than the ‘‘winter’’ averages
measured in the API study. Based on
our review of the API study data, we
interpret the results to indicate that
there may be higher concentrations of
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
benzene on the fenceline attributable to
fugitive emissions than anticipated at
some facilities. These studies are an
indication that the standard we are
finalizing will achieve the goal of
ensuring that the owners or operators
manage fugitive emissions within the
refinery.
This regulatory approach also fits
with the EPA’s goals to improve the
effectiveness of rules. Specifically, in
this case, we are improving the
effectiveness of the rule in two ways.
First, we are establishing a fenceline
benzene trigger to manage overall
fugitive HAP emissions, rather than
establishing further requirements on
many individual emission points.
Secondly, the rule incentivizes facilities
to reduce fugitive HAP emissions below
the fenceline benzene trigger by
providing regulatory options for
reduced monitoring.
Regarding ambient monitoring data,
we note that existing ambient monitors
are not located at the fenceline; they are
located away from sources, and
concentrations typically decrease
exponentially with distance from the
emissions source. We are encouraged
that data referenced by the commenter
indicate that ambient levels of benzene
are within levels that are protective of
human health in communities, but note
that analysis of benzene concentrations
in communities does not necessarily
indicate that refineries located near
these communities are adequately
managing their fugitive HAP emissions.
Comment: Several commenters
reiterated that they do not believe the
proposed fenceline monitoring is a
technology development for equipment
leaks, storage vessels or wastewater
sources. However, if the EPA finalizes
the fenceline monitoring requirements,
the commenters suggested that there is
no longer a need or regulatory basis for
imposing both the fenceline monitoring
requirements and the existing MACT
standards for fugitive HAP emission
sources. Thus, the EPA should remove
the current MACT requirements for
LDAR, storage vessels and wastewater
handling and treatment from Refinery
MACT 1 if the EPA promulgates
fenceline monitoring. Addition of
fenceline monitoring on top of the
existing MACT requirements, they
argue, would violate the Executive
Order 12866 mandate to avoid
redundant, costly regulatory
requirements that provide no emission
reductions.
Response: We disagree that the
fenceline monitoring standards we are
finalizing in this rule are redundant to
MACT emissions standards for fugitive
HAP emissions sources. The MACT
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
standards impose requirements on
fugitive HAP emissions sources
consistent with the requirements in
CAA section 112(d)(2) & (3), and the
fenceline monitoring requirement is not
a replacement for those requirements.
Rather, based on our review of these
standards, we concluded that fenceline
monitoring is a development in
practices, processes or control
technologies that would improve
management of fugitive emissions in a
cost-effective manner. In selecting this
development as an across-the-board
means of improving management of
fugitive emissions, we rejected other
more costly developments that would
have applied independently to each
fugitive emissions source. Requiring
refineries to establish a fenceline
monitoring program that identifies HAP
emission sources that cause elevated
benzene concentrations at the fenceline
and correcting high emissions through a
more focused effort augments but does
not replace the existing requirements.
We found that, through early
identification of significant fugitive
HAP releases through fenceline
monitoring, compliance with the
existing MACT standards for these
emissions sources could be improved
and that it was necessary to revise the
existing standards because fenceline
monitoring is a cost-effective
development in processes, practices,
and control technologies.
We note that the existing MACT
requirements are based on the MACT
floor (the best performers), and as such,
provide a significant degree of emission
reductions from the baseline. The action
level for the fenceline work practice
standard, by contrast, is not based on
the best performers but rather on the
highest value expected on the fenceline
from any refinery, based on the
modeling of refinery emission
inventories. As such it is not
representative of the best performers
and could not be justified as meeting the
requirements of section 112(d)(2)and
(3). If we were to remove the existing
standards for fugitive emission sources
at the refinery, we would not be able to
justify that sources are meeting the level
of control we identified as the MACT
floor when we first promulgated the
MACT. Nor could we justify the
fenceline monitoring program we are
promulgating as representing the MACT
floor because we considered cost (and
not the best performers as previously
noted) in identifying the components of
the program. Although the fenceline
monitoring standard on its own cannot
be justified as meeting the MACT floor
requirement for each of the separate
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
types of fugitive emission sources, that
does not mean that it is not an effective
enhancement of those MACT
requirements. To the contrary, it works
in tandem with the existing MACT
requirements to provide improved
management of fugitive emissions and,
in that sense, it is precisely the type of
program that we believe Congress had in
mind when enacting section 112(d)(6).
ii. Rule Should Require Real-Time
Monitoring Technology for Fenceline
Monitoring.
Comment: Numerous commenters
stated that the proposed fenceline
standards, which require monitoring
using 2-week integrated passive
samplers, are flawed and weak for a
number of reasons, including that the
monitoring method does not provide
real-time data, does not provide
adequate spatial coverage of the
fenceline, and does not provide a
mechanism to identify the specific
emission source impacting the fenceline
to manage fugitive emissions. Several
commenters suggested that this
monitoring technology is not state of the
art. They claimed that there are superior
systems in place at refineries that are
technically and economically feasible,
including at Shell Deer Park, Texas; BP
Whiting, Indiana; and Chevron
Richmond, California. Further, they
claimed that these systems more
effectively achieve the objective of
reducing fugitive emissions. They
claimed several systems are superior to
the proposed system, including openpath systems such as ultraviolet
differential optical absorption (UV
DOAS) and Fourier transform infrared
spectroscopy (FTIR), as well as point
monitors such as gas chromatographs. A
number of commenters suggested that
open-path monitors should be required,
stating that this technology is capable of
providing real-time analysis and data on
air pollution, is able to analyze multiple
pollutants simultaneously at low, nearambient concentrations, and is capable
of providing more complete geographic
coverage.
The commenters also stated that the
benefits of real-time monitors are
particularly important in communities
close to refineries, where they believe
refinery emissions are a major source of
toxic pollutants and short-term upset
events that can have significant public
health impacts. In particular, the
commenters stated that open-path
monitors promote an individual’s rightto-know, in real-time, about harmful
pollution events affecting their
communities, and will allow refinery
owners or operators to immediately
identify fugitive emissions and
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
undertake swift corrective action to
reduce these emissions. Some
commenters suggested that, if the EPA
rejects these open-path real-time
monitors, then at a minimum the EPA
should require the use of active daily
monitoring, such as auto-gas
chromatograph (GC) systems.
Finally, a number of commenters
recommended that the EPA provide
sufficient flexibility in its regulations to
allow state and local jurisdictions to
develop, demonstrate, and subsequently
require the use of alternative monitoring
programs, provided these monitoring
programs are at least equivalent to those
in the final rule.
Response: We understand that many
commenters believe real-time
monitoring would not only help refinery
owners or operators in identifying
emission sources, but also would warn
the community of releases in real time.
Both open-path systems and active
sampling systems (such as auto-GCs)
mentioned by the commenters, are
monitoring systems capable of yielding
monitoring data quickly—ranging from
a few minutes to about a day. However,
these ‘‘real-time’’ systems have not been
demonstrated to be able to achieve all of
the goals stated by the commenters—
specifically, able to provide real-time
analysis and data on multiple pollutants
simultaneously at low-, near-ambient
concentrations, with more complete
geographic (or spatial) coverage of the
fenceline.
The real-time open-path systems
suggested by the commenters are all
limited in that they are not sensitive
enough to detect benzene at the levels
needed to ensure that fenceline
monitoring achieves its intended goal.
The fenceline monitoring system needs
to be capable of measuring at sub-ppbv
levels—well below the 9 mg/m3
fenceline benzene concentration action
level in the final rule, in order to
determine the DC. In the proposal, we
discussed two open-path monitoring
technologies, FTIR and UV–DOAS. For
the proposed rule, we analyzed the
feasibility of employing UV–DOAS over
FTIR because the UV–DOAS is more
sensitive to detection of benzene than
FTIR, as we described in the proposal.
We reviewed performance data on
several UV–DOAS systems in support of
the proposed rule, and for this final
rule, we considered information
submitted during the comment period.
We found that the lowest detection limit
reported for any commercially-available
UV–DOAS system is on the order of 3
ppbv over a 200-meter path length,
whereas the fenceline benzene
concentration action level is 2.8 ppbv
(equivalent concentration to 9 mg/m3).
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
75195
This system is being installed at the
Shell Deer Park refinery but has not
been field validated yet. Thus, we do
not yet know the detection capabilities
of the system, as installed. Based on the
lowest reported detection limit, it
cannot achieve the detection levels
needed to demonstrate compliance with
the fenceline standard in this final rule.
This system also will only cover
approximately 5 percent of the fenceline
at Shell Deer Park, instead of the full
fenceline coverage of the passive
diffusive tube monitoring system we
proposed. Facilities would have to
deploy a monitoring system consisting
of many open-path monitors to achieve
the same spatial coverage as the passive
diffusive tube monitoring system.
For the final rule, we also reviewed
other UV–DOAS systems in operation at
refineries that commenters identified.
However, reported detection limits for
these systems are even higher than for
the type of system being installed at
Shell Deer Park. For example, we
reviewed the open-path UV–DOAS
system information from BP Whiting
and found that they were able to verify
a detection limit of 8 ppbv path average
concentration for benzene over a 1,500meter optical path. This is well above
the 2.8 ppbv fenceline benzene
concentration action level, let alone the
sub-ppbv levels necessary to determine
the DC. Moreover, this system, though
commercially available, was optimized
by developing alternative software to
improve the detection limit (see
memorandum ‘‘Meeting Minutes for
April 21, 2015, Meeting Between the
U.S. EPA and BP Whiting’’ in Docket ID
No. EPA–HQ–OAR–2010–0682). Thus,
the system, as installed, would not be
readily available to other refineries. We
reviewed data for the UV–DOAS system
at the Chevron Richmond refinery and
found that this system, with optical path
lengths ranging from 500 to 1,000
meters, has a reported benzene
detection limit of 5 ppbv averaged over
the path length. Again, this is above the
fenceline benzene concentration action
level at the fenceline established in this
final rule. In addition, we could not find
any information to support the reported
detection limit. We note that the public
Web site operated by the City of
Richmond, California indicates that
information provided by the system is
informational only, not quality assured,
and not to be used for emergency
response or health purposes.
We also disagree with the
commenter’s claim that if the EPA does
not finalize requirements for real-time
open-path monitors then, at a minimum,
the EPA should require active daily
monitoring. There are two methods of
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75196
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
active monitoring. One method, which
we will refer to as the ‘‘auto-GC
method,’’ uses a dedicated gas
chromatograph at each monitoring
location and can return ambient air
concentration results multiple times a
day or even hourly. The other method,
which we refer to as ‘‘method 2,’’ uses
an active pump to collect gas in a
sorbent tube or in an evacuated canister
over a 1-day period, for later analysis at
a central location. While active
sampling monitoring networks are
capable of measuring multiple
pollutants and would likely be able to
detect benzene at sub-ppbv levels as
necessary to demonstrate compliance
with the fenceline requirements in this
final rule, they consist of discreet
monitors and would not provide any
better spatial coverage of the refinery
fenceline than a passive diffusive tube
monitoring network. Further, as shown
in Table 9 of the proposed rule (see 79
FR 36923, June 30, 2014), like open-path
systems, an active sampling monitoring
network would cost many times that of
a passive diffusive tube monitoring
network. At proposal, we estimated the
costs of active daily sampling based on
‘‘method 2’’ to be approximately 10
times higher than for the proposed
passive monitoring (see memorandum
‘‘Fenceline Monitoring Technical
Support Document’’, Docket ID No.
EPA–HQ–OAR–2010–0682–0210). We
note that this type of active daily
sampling based on method 2 does not
necessarily yield results within 24 hours
as the sample analysis would be
conducted separately. We did not
specifically estimate the costs of an
auto-GC alternative, but the capital costs
would be at least 20 to 30 times that for
the passive diffusive tube system, would
require shelters and power supplies at
all monitoring locations and would have
operating costs similar to the ‘‘method
2’’ active monitoring option we
considered.
To date, there are no commerciallyavailable, real-time open-path monitors
capable of detecting benzene at the subppbv levels necessary to demonstrate
compliance with the fenceline
requirements in this final rule. Only a
system that can detect such levels will
result in effective action by facilities to
identify and control fugitive emissions
in excess of those contemplated by the
MACT standards. Further, active
monitoring systems, while potentially
capable of detecting benzene at subppbv levels, like open-path systems,
become very costly when enough
monitors are located around the facility
to approach the spatial coverage of the
passive diffusive tubes. However, we
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
believe that the state of technology is
advancing and that the capabilities of
these systems will continue to improve
and that the costs will likely decrease.
If a refinery owner or operator can
demonstrate that a particular technology
would be able to comply with the
fenceline standards, the owner or
operator can request the use of an
alternative test method under the
provisions of 40 CFR 63.7(f). A
discussion of the specific requirements
for these requests can be found in the
first comment and response summary of
Chapter 8.3 of the ‘‘Response to
Comment’’ document.
Comment: One commenter stated that
the required monitoring should include
real-time monitoring of all chemicals
released by refineries that pose risks to
human health. The commenter stated
that the limited scope of monitoring
required by the proposed rule appears to
be guided by the EPA’s judgment that
fugitive, or ‘‘unintended’’ emissions
pose the greatest threat to public health.
On the contrary, communities may well
suffer from the effects of chemicals
released into the air under normal,
permitted emissions. A more expansive
monitoring strategy would account for
both routine and fugitive emissions.
Several commenters noted that
monitoring is limited to benzene as
opposed to multiple HAP. One
commenter noted that ill health
experienced by refinery neighbors is
due in large part to the synergistic
effects of multiple chemicals. Therefore,
the commenter stated that it is essential
that the rule require monitoring of the
full range of chemicals with health
implications. Other commenters
recommended that the fenceline
monitoring requirement be amended to
include additional contaminants, such
as VOC, that may negatively impact
human health and the environment.
Conversely, other commenters stated
that the EPA has appropriately selected
benzene as a target analyte and
surrogate for HAP emissions from
petroleum refineries, as benzene is a
common constituent in refinery
feedstocks and numerous refinery
streams, and is present in most HAPcontaining streams in a refinery.
Response: As part of the CAA section
112(d)(6) technology review, the EPA
identified the fenceline monitoring
standard as a development in practices,
processes or control technologies that
could improve management of fugitive
HAP emissions. Thus, to the extent the
commenter is suggesting that the EPA
require the fenceline monitoring system
to monitor for emissions of non-HAP
pollutants, such request goes beyond the
scope of our action. Furthermore, to the
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
extent that the commenter is raising
health concerns, although we address
residual risk remaining after
implementation of the MACT standards
under CAA section 112(f)(2), we note
that the MACT standards themselves,
including this requirement, are aimed at
protecting public health, especially in
surrounding communities. As we
explained in the proposal, and as we
determine for this final rule, the MACT
standards as modified by additional
requirements for storage vessels,
provide an ample margin of safety to
protect public health. We did not
propose and are not finalizing a
fenceline monitoring requirement as
necessary to provide an ample margin of
safety under CAA section 112(f)(2).
Petroleum refining emissions can
contain hundreds of different
compounds, including many different
HAP, and no single method can detect
every HAP potentially emitted from
refineries. While several HAP are
amenable to quantification via passive
diffusive tube monitoring using the
same adsorbent tubes used for benzene
(e.g., toluene, xylenes and ethyl
benzene, which have uptake rates in
Table 12.1 in Method 325B), we selected
benzene as a surrogate because it is
present in nearly all refinery fugitive
emissions. By selecting a single HAP as
a surrogate for all fugitive HAP, we are
able to establish a clear action level,
which simplifies the determination of
compliance for refinery owners or
operators and simplifies the ability of
regulators and the public to determine
whether sources are complying with the
work practice standard. As described in
the proposal preamble, benzene is
ubiquitous at refineries and present in
nearly all refinery process streams,
including crude oil, gasoline and
wastewater. Additionally, benzene is
primarily emitted from ground level,
fugitive sources that are the focus of the
work practice standard. Thus, we
conclude that monitoring of benzene is
appropriate and sufficient to identify
emission events for which the
monitoring program is targeting.
Consequently, we are not requiring
quantification of other pollutants
although refinery owners or operators
could choose to analyze the diffusive
tube samples for additional HAP in
conducting root cause analysis and
corrective action.
iii. Fenceline Monitoring Action Level
Comment: Several commenters stated
that the action level for fenceline
monitoring (i.e., 9 mg/m3 or 2.8 ppbv),
was set too high. Some of these
commenters noted that the EPA selected
9 mg/m3 as the highest modeled benzene
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
concentration at any refinery fenceline.
One commenter stated that this was
arbitrary and capricious and stated the
action threshold level makes little sense
because only 2 of the 142 modeled
facilities are expected to have fenceline
concentrations above 4 mg/m3. Several
commenters noted that the average
modeled benzene concentration is 0.8
mg/m3, which is more than an order of
magnitude less than the proposed
fenceline benzene concentration action
level.
Two commenters argued for a lower
action level threshold, citing the
proposed California OEHHA rule, which
finalized new and revised benzene
reference exposure levels (REL) that are
more stringent than the ones the EPA
used in the residual risk assessment
supporting the proposed rule.
Two commenters stated that while the
fenceline benzene concentration action
level of 9 mg/m3 is relatively protective
compared to standards adopted by many
states, including Louisiana and Texas, it
is still 80-percent higher than the
European Union’s standard of 5 mg/m3.
The commenter urged the agency to
consider adopting a stricter standard
comparable to what other industrialized
nations use.
Several commenters stated that the
EPA’s 9 mg/m3 action level is
inconsistent with the statutory text and
objectives of CAA sections 112(d) and
(f), which direct the EPA to focus on the
best-performing, lowest-emitting
sources, in order to require the
‘‘maximum achievable’’ emission
reductions. The commenters stated that
the EPA promulgated the 9 mg/m3 limit
without properly following the statutory
requirements for establishing MACT
floor limits, pointing out that the EPA
made no determination of whether or
not these general models were
representative of the emissions levels
actually achieved by the submitting
refinery, and no connection was drawn
between the best performing sources
and the eventual 9 mg/m3 limit.
On the other hand, several
commenters opposed the 9 mg/m3 action
level suggesting that it was not
achievable and that it is arbitrary. Some
commenters noted that emission/
dispersion models are always very sitespecific and do not necessarily yield a
result that is reliable or reproducible.
Several commenters stated that
additional studies are necessary to allow
the agency to account for these variables
and set a more appropriate
concentration corrective action level.
Commenters suggested a 2-year data
gathering effort at all refineries and data
evaluation before determining a specific
threshold to use.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Several commenters recommended
action levels ranging from 15 mg/m3 to
20 mg/m3 of benzene to account for the
variability expected in monitoring data.
The commenters stated that modeling
biases have underestimated the
necessary action level to achieve the
stated goals of the program.
Response: First, it is important to note
that the purpose of the standard has not
changed between proposal and
promulgation, namely that it is a
technology-based standard that is an
advancement in practices to manage
fugitive emissions. It is not intended to
be a separate or new MACT standard
promulgated pursuant to CAA sections
112(d)(2) and (3) for which a ‘‘floor’’
analysis would be required.7 Nor is it a
standard that we are promulgating
pursuant to CAA section 112(f)(2) as
necessary to provide an ample margin of
safety to protect public health or
prevent an adverse environmental
effect.8 Thus, claims that a standard
should reflect European Union healthbased standards or the California
OEHHA rule are misplaced. We also
disagree with the suggestion that the
proposed monitoring requirement will
allow for higher emissions. As noted
elsewhere, we are retaining all of the
source-specific requirements for fugitive
emissions sources that exist in Refinery
MACT 1.
We disagree with the commenters that
suggest that the proposed action level of
9 mg/m3 is too low and may not be
achievable even for well-performing
facilities. As discussed in the preamble
for the proposed rule, we selected the 9
mg/m3 benzene action level because it is
the highest value on the fenceline
predicted by the dispersion modeling
and, thus, is a level that we estimate
that no refinery should exceed when in
full compliance with the MACT
standards, as amended by this final rule.
All of the results of our pilot study, the
API study, and the other ambient
monitoring data near refineries clearly
indicate that this level is achievable.
Furthermore, we expect the fenceline
concentration difference measured
following the procedures in the final
7 To the extent that the commenters are
suggesting that EPA must re-perform the MACT
floor analysis for purposes of setting a standard
pursuant to section 112(d)(6), we note that the D.C.
Circuit has rejected this argument numerous times,
most recently in National Association for Surface
Finishing et al. v. EPA No. 12–1459 in the U.S.
Court of Appeals for the District of Columbia.
8 Although we did not establish this limit to
address residual risk under CAA section 112(f)(2),
the limit was derived from the same inventory used
for our risk modelling. Thus, based on our current
reference concentration for benzene, the 9 mg/m3
action level will also ensure that people living near
the refinery will not be exposed to cancer risks
exceeding 100-in-1 million.
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
75197
rule to be indicative of refinery source
contributions and we have provided
procedures to isolate these
concentrations from outside sources, as
well as background.
We expect that the fenceline
monitoring standard will result in
improved fugitive HAP emissions
management as it will alert the refinery
owners or operators of fugitive sources
releasing high levels of HAPs, such as
large leaks, faulty tank seals, etc.
iv. Fenceline Monitoring Root Cause
Analysis and Corrective Action
Provisions
Comment: A number of commenters
objected to the proposal’s ‘‘open-ended’’
provisions allowing the EPA to direct
refinery owners or operators to change
their operations in order to achieve the
fenceline limit, with no regulatory
limits on costs and without
consideration of the impact to safe
operations or operability of the plant.
Another commenter stated that the EPA
must properly assess the costs
associated with the root cause analysis/
corrective action requirements and
should establish a cost effectiveness
threshold for any required root cause
analysis/corrective action to ensure that
limited resources are effectively and
efficiently applied for the control of
emissions.
One commenter stated the proposed
fenceline benzene concentration action
level is effectively an ambient air
standard, because corrective action to
achieve that level is required and that if
a facility’s initial corrective action is
unsuccessful, the rule provides that
further action is required and the EPA
must approve that further corrective
action plan. Thus, the commenter
argued, the EPA would essentially be
able to dictate corrective actions, with
no bounds on what could be required
and no consideration of whether any
cost-effective actions are available to
assure the action level is met. The
commenter continued that such a
requirement converts a work practice
program to an emission limitation and
such ambient air limits are not
authorized by CAA section 112. Several
commenters noted that LDAR and
current work practice programs have no
similar requirement for the EPA
approval, and the commenters suggested
that the requirement for the EPA
approval of any second corrective action
should not be included in 40 CFR
63.658(h).
Another commenter recommended
that, if after corrective action, a facility
still has an exceedance for the next
sampling episode, then the facility
should be required to do more than it
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75198
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
did after the first root cause analysis, as
the prior corrective action clearly did
not correct the problem. The commenter
stated that one corrective action
measure the EPA should include in all
such instances is higher-quality
monitoring such as UV–DOAS for at
least 1 year to monitor, identify, correct
and assure ongoing compliance after the
exceedance problem is fixed.
Response: The ‘‘on-going’’
requirement to achieve the fenceline
benzene concentration action level is no
different in concept from the LDAR
requirements for equipment or heat
exchange systems in the Refinery MACT
1 rule, which requires the refinery
owner or operator to repair the source
of the emissions regardless of what it
takes until compliance with the
standard is achieved.
We disagree with the claim that the
EPA must assess the costs associated
with the root cause analysis/corrective
action requirements and establish a cost
effectiveness threshold for any required
root cause analysis/corrective action to
ensure that limited resources are
effectively and efficiently applied for
the control of emissions. We did not
attempt to project the costs of the root
cause analysis/corrective action for at
least two reasons. First, based on the
dispersion modeling of the benzene
emissions reported in response to the
inventory section of the 2011 ICR, we
project that no refinery should exceed
that fenceline benzene concentration
action level if in full compliance with
the MACT standards, as amended by
this action. Thus, assuming compliance
with the MACT standards, we would
expect that there are no costs for root
cause analysis/corrective action. To the
extent that there are exceedances of the
action level, the premise of the fenceline
monitoring is to provide the refinery
owners or operators with the flexibility
to identify the most efficient approaches
to reduce the emissions that are
impacting the fenceline level. Since the
choice of control is a very site-specific
decision, we would have no way to
know how to estimate the costs. Thus,
the source is in the best position to
ensure that resources are effectively and
efficiently spent to address any
exceedance.
We intended the proposed
requirement for refinery owners or
operators to submit a corrective action
plan for the EPA approval to provide the
Administrator with information that
they were making a good-faith effort to
reduce emissions below the fenceline
benzene concentration action level, as
expeditiously as practicable. However,
we understand the importance for
refinery owners or operators to begin
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
corrective action as soon as possible,
without having to wait for the EPA
approval. Therefore, we are finalizing
the requirement for refinery owners or
operators to submit such plans but we
are not finalizing the requirement that
the EPA must approve the plan prior to
the corrective action being taken.
We previously responded to
comments regarding UV–DOAS or other
open-path monitoring systems in this
section, explaining that the current
detection limits for these systems
exceeds the action level threshold and,
thus, these systems would not provide
usable data to inform corrective action.
Thus, we disagree that the EPA should
require these systems for all facilities
whose first attempt at corrective action
is ineffective.
v. Fenceline Monitor Siting
Requirements
Comment: Numerous commenters
provided suggestions on, or requested
clarification of, the monitor siting
requirements. Several commenters
stated that proposed Method 325A uses
the terms ‘‘fenceline or property
boundary,’’ while it should consistently
use the term ‘‘property boundary’’ or
even ‘‘property line’’ as the fenceline
location. Several commenters stated that
Sections 8.2.2.1.4 and 8.2.2.3 of Draft
Method 325A specify that samplers be
placed just beyond the intersection
where the measured angle intersects the
property boundary and this could
require placing monitors on other
people’s property, in a road, in a water
body or in a railroad right-of-way. The
commenters suggested that facilities
should be allowed to place monitors at
any vector location that meets other
requirements between the property
boundary and the source nearest the
property boundary. They stated that
facilities need this clarification to avoid
obstructions (e.g., buildings or trees)
that may be at the property line.
Numerous commenters requested that
the rule clarify where monitors need to
be placed in special circumstance, such
as refineries bisected by a road, railroad
or other public right-of-way or a
boundary next to a navigable waterway.
Several commenters stated that refiners
should not need to place monitors on
these property boundaries or other
property boundaries where there are no
residences within 500 feet of the
property line. Commenters also asked if
areas that had non-refinery operations,
but are still inside the property
boundary, would be included for
purposes of determining where to site
monitors.
A few commenters expressed concern
about the approach for determining the
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
number of required monitors at a site
based on the acreage, noting that it is
unfair to small facilities and will leave
gaps in monitoring coverage for very
large facilities. Some commenters
recommended amending the proposed
rule to require the placement of
fenceline monitors at fixed distances
along facilities’ perimeters with no
maximum number of monitors. Some
commenters stated that the rule should
specify an acceptable range on the
2,000-foot spacing requirement or the
radial placement requirement as it may
be necessary to address accessibility or
safety concerns. Several commenters
suggested that a lower minimum
number of sampling monitors should be
required for very small refineries or
small ‘‘subareas.’’ These commenters
noted that refineries often include
disconnected parcels that can be very
small (e.g., 10 acres or less). If each
disconnected parcel must be treated as
a separate subarea, then both sampler
siting options in Draft Method 325A
would result in unnecessarily large
numbers of samplers extremely close
together. Some commenters
recommended that Method 325A
specify that samplers need not be placed
closer than 500 feet (versus the normal
2,000-foot interval specified in Option
2) along the fenceline from an adjoining
sampler, regardless of whether the
radial or linear approach is used and
should waive the minimum number of
samplers specified in Sections 8.2.2.1.1,
8.2.2.2.1, and 8.2.3.1. Another
commenter added that the rule should
waive the requirement for additional
samplers in Sections 8.2.2.1.5 and
8.2.3.5 if the 500-foot minimum spacing
criterion is compromised.
Response: We agree that the Method
325A should provide clear and
consistent language. We have revised
the language to be consistent in referring
to the ‘‘property boundary’’. We have
also revised the Method to allow
placement of monitors at any radial
distance along either a vector location or
linear location (that meets the other
placement requirements) between the
property boundary and the source
nearest the property boundary. That is,
the monitors do not need to be placed
exactly on the property boundary or
outside of the property boundary. They
may be placed within the property
closer to the center of the plant as long
as the monitor is still external to all
potential emission sources. We do note
that if the monitors are placed farther in
from the property boundary, the owner
or operator should take care to ensure,
if possible, that the radial distance from
the sources to the monitors is at least 50
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
meters. If the perimeter line of the
actual placement of the fenceline
monitors is closer than 50 meters to one
or more sources, then the additional
monitor citing requirements will apply.
We have revised subparagraphs of
Section 8.2.2 to provide this allowance.
This clarification should address issues
related to obstructions such as tall walls
located at the facility boundary.
We intended that the fenceline
monitoring would create a monitoring
perimeter capable of detecting
emissions from all fugitive emission
sources at the refinery facility. We have
long established that a road or other
right of way that bisects a plant site does
not make the plant site two separate
facilities, and, thus, would not be
considered part of the property
boundary. As we agree that monitors
need only be placed around the
property boundary of the facility, it
would not be necessary to place
monitors along a road or other right-ofway that bisects a facility. We have
clarified this in the final rule and
Method 325A.
If the facility is bounded by a
waterway on one or more sides, then the
shoreline is the facility boundary and
monitors should be placed along this
boundary. If the waterway bisects the
facility, the waterway would be
considered internal to the facility and
monitors would only be needed at the
facility perimeter.
Regarding the comment that monitors
should not be required where there is no
residence within 500 feet of the
property line, we disagree. We proposed
and are finalizing the fenceline
monitoring standards under CAA
section 112(d)(6) as a means to improve
fugitive HAP emissions management,
regardless of whether there are people
living near a given boundary of the
facility.
Regarding the clarification requested
about monitor placement considering
non-refinery operations, the property
boundary monitors should be placed
outside of all sources at the refinery.
This is because moving the monitoring
line inward to exclude the non-refinery
source could lead to an underestimation
of the DC compared to the monitoring
external of the entire site. If the nonrefinery source is suspected of
contributing significantly to the
maximum concentration measured at
the fenceline, a site-specific monitoring
plan and monitoring location specific
near-field interfering source (NFS)
corrections will be needed to address
this situation.
Section 8.2.3 of Method 325A
includes language to provide some
flexibility when using the linear
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
placement (±10% or ±250 feet). We
consider it reasonable to provide similar
placement allowance criteria for the
radial placement option (±1 degree). We
are not providing requirements that
would allow small area refineries to use
fewer than 12 monitoring sites. We do
not consider that any refinery would be
so small as to warrant fewer than 12
monitors; however, we did not
necessarily consider very small subareas
for irregularly shaped facilities or
segregated operations. When
considering these subareas, we agree
that fewer than 12 monitoring sites
should be appropriate. Therefore, we
have provided that monitors do not
need to be placed closer than 152 meters
(500 feet) (or 76 meters (250 feet) if
known sources are within 50 meters
(162 feet) of the monitoring perimeter,
which is likely for these subareas or
segregated areas) with a stipulation that
a minimum of 3 monitoring locations be
used per subarea or segregated area. We
note, however, that this distance
provision does not obviate the near
source extra monitoring siting
requirements or the requirement to have
a minimum of three monitors per
subarea or segregated area.
If facility owners or operators have
questions regarding the required
locations of monitors for a specific
application, they should contact the
EPA (or designated authority) to resolve
questions about acceptable monitoring
placement.
vi. Compliance Time for Fenceline
Monitoring Requirements
Comment: Some commenters
supported EPA’s proposal to provide 3
years to put a fenceline monitoring
program in place, but the commenters
believe that timing is unclear in the
proposed regulatory language, which
appears in Table 11 to subpart CC, and
requested that the EPA add the initial
compliance date to 40 CFR 63.658(a).
One commenter stated that instituting
this program for all 142 major source
U.S. refineries would require
considerable time. Based on their
experience with their pilot study, one
commenter noted that commercially
available weather guards meeting the
specifications of proposed Method 325A
are not available and would need to be
fabricated. Additionally, a commenter
stated that only a limited number of
laboratories in the U.S. are able to
perform the necessary analyses.
According to the commenter,
considerable time and effort will be
needed to qualify additional laboratories
and to expand the capacity of existing
laboratories to handle the samples from
142 refineries.
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
75199
Other commenters disagreed with the
EPA’s proposed compliance time and
suggested that the EPA shorten the
timeline for implementation at
refineries so that possible corrective
action occurs much sooner than
proposed. The commenters suggested
that deployment of passive samplers can
proceed more promptly than proposed,
especially since the EPA has
simultaneously proposed specific
‘‘monitor siting and sample collection
requirements as EPA method 325A of 40
CFR part 63, Appendix A, and specific
methods analyzing the sorbent tube
samples as EPA Method 325B of 40 CFR
part 63, Appendix A.’’ Moreover, the
commenter noted, a principal reason
that the EPA selected passive monitors
over active monitors was due to the
relative ‘‘ease of deployment.’’ The
commenter claimed this ease of
deployment rationale is undermined by
a 3-year grace period to deploy passive
monitors when the EPA is providing
very specific criteria for their use. The
commenter suggested that the EPA
require full compliance with the passive
monitoring requirement within 1 year of
the effective date of the rule.
Response: While we realize that it
will take some time for the refinery
owners or operators to understand the
final rule and develop a compliant
monitoring program, we agree that in
requiring the passive sampler
monitoring system, we recognized the
ease of implementation and
deployment. Although industry
commenters identified issues they faced
in the API pilot study while trying to
implement the monitoring method, we
note that the 12 facilities that
participated in the API pilot study
installed the fenceline monitors and
began sampling in late 2013 with
relative ease and within months of
obtaining the draft methods. Thus, we
disagree with the suggestion that 3 years
is insufficient and agree with other
commenters that 3 years is in fact too
long. However, we also are aware that
the API pilot facilities used the direct
DC approach proposed and did not
attempt to develop site-specific
monitoring programs to correct for
interfering near-field sources. Although
we expect that facilities could complete
direct implementation of the proposed
fenceline monitoring requirement
within 1 year after the effective date of
the rule, as suggested by some
commenters, facilities that choose to
develop a site-specific monitoring plan
would need a longer period of time.
Therefore, we are finalizing
requirements that specify that facilities
must begin monitoring for the official
E:\FR\FM\01DER2.SGM
01DER2
75200
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
determination of DC values no later than
2 years after the effective date of the
rule.
vii. Fenceline Monitoring
Recordkeeping and Reporting
Requirements
Comment: Some commenters
suggested that facilities should be
required to submit the monitoring data
via the ERT only if they exceed the
fenceline benzene concentration action
level and that all remaining data should
be kept on-site and available for
inspection or upon request of the EPA,
citing that this is consistent with EPA’s
semiannual NESHAP reporting of only
exceptions (i.e., deviations). Other
commenters requested that the EPA
only post the rolling annual average
concentration values and not the 2-week
monitoring data. These commenters
indicated concern that if errors are
present in the raw data that are
submitted semiannually to the EPA, the
data, errors and all, will be released to
the public and correcting them will not
take place or will not take place in a
timely manner. One commenter added
that there is very little useful
information that can be gleaned from
the raw data and posting it simply
invites misunderstandings.
Commenters also stated that the EPA
should adopt reporting requirements to
ensure that facilities report the
monitoring data appropriately.
Specifically, commenters recommended
that 40 CFR 63.655(h)(8)(i) should be
clarified to only require reporting of
valid data and cautioned that data
should be processed to allow accurate
calculations of annual averages to be
used for reporting and evaluation. To
accomplish this, commenters
recommended that the rule provide 75
days from the end of a 6-month
sampling period to report to the EPA,
rather than the proposed 45-day period,
in order to provide adequate time to
obtain quality-assured results for all 2week sampling periods.
One commenter applauded the
proposal’s requirements for electronic
reporting of the fenceline concentration
data and making the resulting
information publicly available.
However, the commenter recommended
that the EPA consider a more truncated
data reporting period that is more
consistent with the associated
milestones of collecting a 14-day
sampling episode. As is, the commenter
claimed, the proposed rule would have
a lag time of up to 7.5 months between
data collection and posting. The
commenter indicated that data reporting
on a more frequent schedule will not
only provide transparency, but will
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
provide states and local agencies with
information about air quality at
refineries at a frequency that could
allow informed activities to address
leaks much more quickly and protect
public health.
Response: We disagree with the
commenters who suggest that facilities
only report the rolling annual average or
only exceedances of the fenceline
benzene concentration action level
because the commenters believe there is
little information to be gleaned from the
raw data. Monitoring data are useful in
understanding emissions, testing
programs, and in determining and
ensuring compliance. We generally
require reporting of all test data, not just
values calculated from test data and/or
where a facility exceeds an emissions or
operating limit. For example, when we
conduct risk and technology reviews for
source categories, we are adding
requirements for facilities to submit
performance test data into the ERT, not
just performance test data that indicates
an exceedance of an applicable
requirement. In the Mercury and Air
Toxics Rule, we require facilities to
report direct measurements made with
CEMS, such as gas concentrations, and
we require hourly reporting of all
measured and calculated emissions
values (see discussion at 77 FR 9374,
February 16, 2012). In particular, for the
fenceline monitoring requirements in
this final rule, we offer facilities options
for delineating background benzene
emissions and benzene emissions not
attributable to the refinery, and we offer
options for reduced monitoring, making
it even more necessary that we have all
of the data to review to ensure that
testing and analyses are being done
correctly and in compliance with the
requirements set out in the regulations,
and that root cause analyses and
corrective actions are being performed
where necessary. Therefore, as
proposed, we are finalizing the
requirements that facilities report the
individual 2-week sampling period
results for each monitor, in addition to
the calculated DC values in their
quarterly reporting.
Regarding commenters’ concerns that
facilities post accurate data and have
sufficient time to perform quality
assurance on the data, in the final rule,
we have established provisions for how
sources are to address outliers and data
corrections. Additionally, as proposed,
we do not require an initial report until
facilities have collected 1 year of data so
that facilities do not report the data
until a rolling annual average value can
be determined. This will allow refinery
staff and analytical laboratories to iron
out any issues that might arise as they
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
implement these methods for the first
time. Once this initial data collection
period is complete, we anticipate that
data quality issues should be infrequent.
Therefore, we are providing a 45-day
period following each quarterly period
before facilities must submit the
monitoring results, which should
provide facilities adequate time to
correct any data errors prior to reporting
the data.
Regarding comments that suggest
reporting each 2-week sample result
soon after its collection, we disagree.
This frequency would put undue
burden on the refinery owners or
operators in trying to collect, review and
quality assure the data prior to
reporting. However, we agree with
commenters that more frequent
reporting of the fenceline monitoring
data would be useful. Therefore, we
have revised the reporting frequency for
the fenceline monitoring data to be
quarterly in the final rule rather than
semiannually as proposed.
Additionally, we understand that there
is a lot of interest in how these data will
be presented to the public, and we plan
to reach out to all stakeholders on
appropriate approaches for presenting
this information in ways that are helpful
and informative.
b. Refinery MACT 2
This section provides comment and
responses for the key comments
received regarding the technology
review amendments proposed for
Refinery MACT 2. Comment summaries
and the EPA’s responses for additional
issues raised regarding the proposed
requirements resulting from our
technology review are in the ‘‘Response
to Comment’’ document in the public
docket (Docket ID No. EPA–HQ–OAR–
2010–0682).
i. FCCU
We received comments on the
consideration of developments in
pollution controls, the averaging time
for FCCU PM limits, and the FCCU
opacity limit, as discussed below.
Comment: One commenter stated that
the EPA failed to consider
developments in pollution controls for
HAP from FCCUs for two reasons. First,
the commenter contended that cost is
not a valid consideration to evaluate if
a ‘‘development’’ in pollution control is
necessary pursuant to section
7412(d)(2), (3), (6), unless the EPA is
setting a ‘‘beyond-the-floor’’
requirement.
Second, the commenter claimed that
the EPA’s review of developments is
nearly 10 years old and misses some
important pollution control
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
improvements in the industry. For
example, the commenter noted that
Valero Benicia installed a combination
of controls in 2012 including a scrubber,
SCR and CO Boiler that combine
exhaust streams from the FCCU and
coking and reportedly eliminate HAP
emissions entirely from these sources.
The commenter also asserted that EPA
consent decrees impose lower effective
limits on PM than the EPA considered
under the technology review. The
commenter identified the BP Whiting
facility as subject to 0.7 lb PM/1,000 lbs
coke burn-off at one FCCU and 0.9 lb
PM/1,000 lbs coke burn-off at another
and claimed these limits are lower than
the 1.0 lb PM/1,000 lbs coke burn-off
limit currently mandated by Refinery
MACT 2.
Response: We disagree that we cannot
consider costs when determining if it is
necessary to revise an existing MACT
standard based on developments in
practices, processes and control
technologies. The commenter suggests
that we cannot consider costs because of
the requirements in CAA section
112(d)(2) and (3) for establishing initial
MACT standards and which do not
allow for consideration of costs until the
second, ‘‘beyond the floor’’ phase of the
analysis. As discussed previously in this
preamble where we respond to
comments on the fenceline monitoring
requirements, to the extent that the
commenters are suggesting that EPA
must re-perform the MACT floor
analysis for purposes of setting a
standard pursuant to section 112(d)(6),
we note that the D.C. Circuit has
rejected this argument numerous times,
most recently in National Association
for Surface Finishing et al. v. EPA No.
12–1459 in the U.S. Court of Appeals for
the District of Columbia.
Regarding the claim that the EPA did
not consider the types of controls at the
Valero and BP facilities, we disagree.
The control measures for both of those
facilities are controls that existed at the
time of the development of the MACT
standard. Thus, we did not identify
these technologies as developments in
control technologies during the
technology review. However, we did
identify developments in processes or
practices that reflect better control by
the existing technology and we
reviewed modified emission limits that
reflect that better level of control. The
commenter suggested that we failed to
consider a level of zero when the Valero
facility was able to achieve zero
emissions through a combined SCR,
boiler and scrubber. However, the
commenter provided no information to
support such a claim and we are
skeptical that such a result could be
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
achieved. We note that the SCR is
designed specifically to reduce NOX
emissions, and would not be capable of
reducing significantly, much less
eliminating completely, HAP emissions.
Similarly, based on our long-standing
understanding of the processes, neither
a boiler nor a scrubber could achieve
such a result. Regarding the level of
emissions achieved at the BP Whiting
facility, we note that we evaluated
control systems that can meet 0.5 lb PM/
1,000 lb coke burn-off, which is a lower
limit than that at BP Whiting. We
determined that these were costeffective to require for new units that
are installing a new control system.
However, we determined that
retrofitting controls designed to meet a
PM limit of 1.0 lb PM/1,000 lbs coke
burn-off to now meet a limit of 0.5 lb
PM/1,000 lbs coke burn-off was not
cost-effective when considering PM and
PM2.5 emissions reductions. We
projected the cost of the 0.5 lb PM/1,000
lbs coke burn-off limit in retrofit cases
to be $23,000 per ton PM emissions
reduced. To meet a limit of 0.7 lb PM/
1,000 lbs coke burn-off or 0.9 lb PM/
1,000 lbs coke burn-off, as is the case for
BP Whiting, the retrofit costs would be
similar to this 0.5 lb PM/1,000 lb coke
burn-off option, but the reductions
would be even less, resulting in costs
over $23,000 per ton. As metal HAP
content of FCCU PM is approximately
0.1 to 0.2-percent of the total PM, the
cost of requiring this lower limit for
existing FCCU is over $10 million per
ton of metal HAP reduced. Therefore,
we determined that it is not necessary
to revise the PM standard for existing
FCCU sources.
Comment: Refinery MACT 2 requires
the owner or operator to demonstrate
compliance with the PM FCCU limits by
complying with the operating limits
established during the performance test
on a daily (i.e., 24-hour) average basis.
Several commenters objected to the
EPA’s proposal to revise this
requirement to a 3-hour averaging time.
Commenters restated EPA’s arguments
for 3-hour averaging time as: (1) Daily
average could allow FCCUs to exceed
limits for short periods while still
complying with the daily average, (2)
consistency with NSPS subpart Ja and
(3) consistency with duration of testing.
The commenters stated that the EPA
had not provided any data that show
that the daily average could allow
FCCUs to exceed limits for short periods
and, therefore, the EPA is using a
hypothetical compliance assurance
argument to change emission limits. The
commenters stated that a change in
emission limits is not authorized by
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
75201
CAA section 112 because the emission
limitations in Refinery MACT 2 for
FCCUs were established as daily
averages following the floor and ample
margin of safety requirements in section
112(d)(2) of the CAA.
The commenters also state that the
EPA’s additional arguments for the
change to a 3-hour average are irrelevant
and legally deficient. The commenters
stated that the combination of a
numerical emission limit and an
averaging period frames the stringency
of a limitation and that a reduction in
either of those factors results in a
significant lowering of the operating
limit. The commenters conclude that
the EPA has proposed to change the
stringency of the requirements without
justification, and the CAA requires that
such a change in stringency be justified
pursuant to CAA section 112(d)(6) or
(f)(2). The commenters stated that
increasing stringency for consistency
with NSPS rules is not a criterion for a
CAA section 112(d)(6) action. Rather
that section requires a change to be due
to ‘‘developments.’’ The only change in
technology since the 2002 promulgation
of Refinery MACT 2 is the availability
of PM continuous emission monitoring
system (CEMS), which is unproven.
One commenter noted that changing
the averaging time is a very significant
modification considering that the
compliance limits would apply for
periods of SSM. This commenter stated
that it is unlikely that existing
operations can consistently be in
compliance with a new 3-hour average
since the current daily averaging was
put in place to recognize that there will
be periods of operating variability that
do not represent the longer term
performance of an FCCU. The
commenters recommended that the EPA
retain the daily averaging requirement.
Response: We disagree with the
commenters’ statement that reducing
the averaging time from a 24-hour basis
to a 3-hour basis for demonstrating
compliance with the FCCU PM emission
limit, using operating limits established
during the performance test, is a change
to the MACT floor. The emission limit
of 1.0 lb PM/1,000 lbs coke burn-off is
the MACT floor, and we are not
changing the PM emissions limit (or
alternate Ni limits) in Table 1 to subpart
UUU (except to remove the incremental
PM limit that did not comport with the
MACT floor emissions limitation).
However, whether or not it is a
change from the MACT floor is not
relevant. Pursuant to CAA section
112(d)(6), the EPA must revise MACT
standards ‘‘as necessary’’ considering
developments in practices, processes
and control technologies. For this
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75202
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
exercise, we considered any of the
following to be a ‘‘development’’:
• Any add-on control technology or
other equipment that was not identified
and considered during development of
the original MACT standards.
• Any improvements in add-on
control technology or other equipment
(that were identified and considered
during development of the original
MACT standards) that could result in
additional emissions reduction.
• Any work practice or operational
procedure that was not identified or
considered during development of the
original MACT standards.
• Any process change or pollution
prevention alternative that could be
broadly applied to the industry and that
was not identified or considered during
development of the original MACT
standards.
• Any significant changes in the cost
(including cost effectiveness) of
applying controls (including controls
the EPA considered during the
development of the original MACT
standards).
In determining whether there are
‘‘developments,’’ we review, among
other things, EPA regulations
promulgated after adoption of the
MACT, such as the NSPS we identified
in this instance. We identified the
enhanced monitoring requirements for
these operating limits as a development
in practices that will help ensure FCCU
owners or operators are properly
operating control devices and, thus, are
meeting the PM emission limit at all
times. We further determined that this
enhanced monitoring was cost effective
and proposed that it was necessary to
revise the existing standard pursuant to
CAA section 112(d)(6).
While we do not have continuous PM
emissions data that show actual
deviations of the PM limit, we do not
need such data in order to conclude that
such deviations could occur when daily
averages are used. The Refinery MACT
2 (i.e., subpart UUU) rule requires
owners or operators to establish
operating limits based on three 1-hour
runs during the performance test. As a
matter of simple mathematics, a source
could demonstrate that it is meeting the
operating limit based on a 24-hour
average but could be exceeding the 1.0
lb PM/1,000 lbs coke burn-off emission
limit based on a 24-hour average or for
one or more individual 3-hour periods
during that 24-hour average. For
example, an owner or operator could
operate with a power input 5-percent
higher than the operating limit for 23
hours, have the ESP off (zero power) for
one hour, and still comply with a 24hour average operating limit. However,
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
it would be difficult for this same unit
to meet the 1.0 lb PM/1,000 lbs coke
burn-off emissions limit over a 24-hour
period, and it certainly would not meet
the limit for every 3-hour period during
that day. As the operating limit can be
established to correspond with 1.0 lb
PM/1,000 lbs coke burn-off, the 5percent higher power input would
likely correspond with a 0.95 lb PM/
1,000 lbs coke burn-off emissions rate
(5-percent lower). Uncontrolled
emissions are typically 6 to 8 lbs/1,000
lbs coke burn-off. Thus, this unit would
have emissions averaging approximately
1.2 lbs PM/1,000 lbs coke burn-off
during this 24-hour period [i.e.,
(0.95*23+7)/24], but would be in
compliance with the 24-hour average
operating limit. The unit would
obviously also be out of compliance
with the 3-hour average over the period
when the power was turned off. We also
have concerns that the operating limits
are not always linear with the
emissions, so that the longer averaging
times do not effectively ensure
compliance with the PM emissions
limit. Therefore, as proposed, we are
finalizing the requirement for owners or
operators to comply with the operating
limits on a 3-hour basis, rather than the
24-hour basis currently in the rule.
Comment: The technology review for
FCCUs resulted in the EPA proposing to
remove the 30-percent opacity
alternative limit for demonstrating
compliance with the PM emissions limit
that is available for refineries complying
with the Refinery NSPS 40 CFR part 63,
subpart J. Two commenters supported
the EPA’s proposed removal of the 30percent opacity limit for FCCUs. Other
commenters stated that current
technology is good enough for a 10- or
20-percent opacity limit. On the other
hand, several commenters stated that
the proposed removal of the 30-percent
opacity limit must meet the criteria
specified in CAA section 112(d)(6) and
(f)(2), which requires analysis of the
statutory basis, environmental impacts,
costs, operational and compliance
feasibility and impacts, that the EPA has
not conducted. The commenters
claimed that had the EPA conducted a
proper analysis, the EPA would have
determined that the proposed change to
remove the 30-percent opacity limit is
not necessary or supportable.
Additionally, these commenters stated
that since the underlying PM emissions
limit is unchanged, there is no emission
reduction justification for this proposed
change, and the change would not meet
the CAA section 112(d)(6) requirement
of being cost effective. The commenters
also noted that processes or practices for
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
existing FCCUs have not changed, as
required for a CAA section 112(d)(6)
revision.
Several commenters urged the EPA to
maintain the 30-percent opacity limit
for these FCCUs. As a practicable and
cost-effective alternative to address the
EPA’s concern as to whether
compliance with a 30-percent opacity
limit ensures compliance with the PM
emissions limit, commenters suggested
annual performance tests to confirm that
the FCCU is meeting the PM emissions
limit, rather than performance tests
every 5 years, as proposed.
One commenter stated that the EPA
never intended for the opacity limit in
Refinery NSPS subpart J to be used to
demonstrate compliance with the PM
emissions limit, but instead to assure
the PM controls operate properly. The
commenter stated that the EPA’s
conclusion that the 30-percent opacity
limit may not be sufficiently stringent to
ensure compliance with the underlying
PM emissions limit is based on a false
premise as to the purpose of the opacity
standard because as the EPA states,
‘‘Opacity of emissions is indicative of
whether control equipment is properly
maintained and operated.’’
Several commenters stated that the
proposed elimination of the 30-percent
opacity limit currently in Refinery
MACT 2 leaves existing FCCUs that use
cyclones with no viable alternative
approach to demonstrate compliance
with the PM emissions limit without
adding or replacing controls. They
stated the other approaches for
demonstrating compliance with the PM
emissions limit in Refinery MACT 2
(such as development of a site-specific
opacity limit) do not work for them. The
commenters stated that although they
believe that more frequent performance
tests would show that the FCCUs are in
fact meeting the PM emissions limit, the
absence of the 30-percent opacity limit
would force FCCUs using cyclones for
PM control to install additional, costly
PM controls (e.g., ESPs or wet gas
scrubbers). They projected that these
additional controls would cost tens of
millions of dollars per FCCU and would
require at least 3 years of compliance
time. Additionally, one commenter
stated that even FCCUs with additional
downstream PM controls would not be
able to achieve a site-specific limit at all
times and needed the availability of the
alternative 30-percent opacity limit. One
commenter estimated that installing an
ESP to meet the proposed 10-percent
opacity limit would cost approximately
$121,000/ton, assuming a 32 tpy PM
emission reduction. The commenter
noted that the ESP would also increase
GHG emissions and require more energy
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
resources from the facility. The
commenter concluded that installing an
ESP is neither cost effective nor
appropriate considering non-air quality
environmental and health impacts and
energy requirements, and recommended
that the EPA maintain the current NSPS
subpart J alternative limits and add
additional alternative limits into
Refinery MACT 2 only as optional limits
for demonstrating compliance with the
PM emissions limit.
Response: In promulgating Refinery
MACT 2, the EPA identified the 1.0 lb
PM/1,000 lbs coke burn-off limit as the
MACT floor but allowed a compliance
option for FCCUs subject to Refinery
NSPS subpart J to comply with an
opacity limit up to 30 percent with one
6-minute allowance to exceed the 30percent opacity in any 1-hour period. As
stated in the proposal, compliance
studies have shown that the 30-percent
opacity limit does not correlate well
with the 1.0 lb PM/1,000 lbs coke burnoff limit, and that an FCCU can comply
with the 30-percent opacity limit while
its emissions exceed the PM emissions
limit.9 Regardless of whether the 30percent opacity limit in Refinery NSPS
subpart J was designed to ‘‘ensure that
the control device was operated
properly,’’ Refinery MACT 2 allows
sources subject to NSPS subpart J to use
the 30-percent opacity limit to
demonstrate continuous compliance
with the PM emissions limit. We have
determined that the 30-percent opacity
limit is inadequate for the purpose of
demonstrating continuous compliance
with the PM emissions limits in
Refinery MACT 2. As such, we
proposed to remove this opacity limit
and require the owner or operator to
either demonstrate compliance with the
PM emissions limit by continuously
monitoring the control device
parameters established during the
performance test or establish and
monitor a site-specific opacity limit. For
clarity, we note that we proposed to
allow a site-specific opacity limit, not a
10-percent opacity limit as some
commenters suggest. The site-specific
opacity limit can be significantly higher
than 10 percent, but it cannot be lower
than 10 percent.
While the compliance study indicates
that a 30-percent opacity limit does not
correlate well with a 1.0 lb PM/1,000 lbs
coke burn-off emissions limit, further
review of this same study indicates that
a 20-percent opacity limit provides a
reasonable correlation with units
9 Compliance Investigations and Enforcement of
Existing Air Emission Regulations at Region 5
Petroleum Refineries. U.S. Environmental
Protection Agency, Region 5—Air and Radiation,
Chicago, Illinois. March 9, 1998.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
meeting the 1.0 lb PM/1,000 lbs coke
burn-off emissions limit. We also
reviewed the data submitted by the
commenters regarding PM emissions
and opacity correlation. While the data
suggest that there is variability and
uncertainty in the PM/opacity
correlation, the data do not support that
a 30-percent opacity limit would ensure
compliance even when considering the
uncertainty associated with the PM/
opacity correlation. Based on the
variability of the 3-run average opacity
limits, we determined that, if the 3-hour
average opacity exceeded 20-percent,
then it was highly likely (98 to 99percent confidence) that the FCCU
emissions from the unit tested would
exceed the PM emissions limit.
After considering the public
comments, reviewing the data submitted
with those comments, and further
review of the compliance study, in this
final rule we are adding a 20-percent
opacity limit, evaluated on a 3-hour
average basis for units subject to NSPS
subpart J. As we noted above, a 20percent opacity limit provides a
reasonable correlation with the PM
emissions limit, and an exceedance of
this 20-percent opacity limit will
provide evidence that the PM emissions
limit is exceeded. However, it is
possible that units could still exceed the
PM emissions limit while complying
with the 20-percent opacity limit, if
those units operate close to the 1 lb PM/
1,000 lbs coke burn-off emissions limit.
To address this concern, we considered
the commenters’ suggestion to require a
performance test annually rather than
once every 5 years. Some commenters
suggested that this option specifically
apply to FCCUs with cyclones, but this
option is applicable to any control
system operating very near the PM
emissions limit and using an opacity
limit to demonstrate continuous
compliance. We have determined that
the Refinery NSPS subpart J compliance
procedures in Refinery MACT 2, in
combination with a 20-percent opacity
limit demonstrated on a 3-hour average
basis and with annual performance tests
when a test indicates PM emissions are
greater than 80-percent of the limit (i.e.,
0.80 lb PM/1,000 lbs coke burn-off), will
ensure continuous compliance with the
PM emissions limit. FCCUs with
measured PM emissions during the
performance test at or below 0.80 lb PM/
1000 lbs of coke burn-off will remain
subject to the requirement to conduct
performance tests once every 5 years,
consistent with the requirements we
proposed.
We do not agree with commenters
that the proposed opacity revision
would add significant cost or
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
75203
compliance burden. The control devicespecific monitoring parameters that
were proposed rely on parameters
commonly used to control the operation
of the control device, so the monitoring
systems should be already available.
Further, since we are merely changing
the opacity limit, we expect these units
will already have opacity monitoring
systems needed to demonstrate
compliance with the PM emissions limit
and would not incur costs for new
equipment.
Comment: Several commenters stated
that they agree with the EPA’s
determination in the proposal that the
current CO limits provide adequate
control of HCN. Two commenters stated
that there are limited HCN emissions
data and that more data are needed
before the Agency can appropriately
determine whether an HCN standard is
necessary and justified. One commenter
noted that the process undertaken by
the EPA to estimate HCN emissions was
flawed, and likely overestimates HCN
emissions significantly. Another
commenter stated that they performed
HCN stack testing at three refineries and
subsequent modeling at two refineries
and concluded that the ambient HCN
emissions were well below the
applicable health limits.
In contrast, some commenters
expressed concerns about high HCN
levels. One commenter stated that the
EPA should consider re-evaluating the
benefit of low NOX emissions from the
FCCU, if that is indeed the cause of
higher HCN emissions, because
exposing people to HCN is not
acceptable. The commenter also noted
that the community now also has the
increased dangers of storing and
transporting aqueous ammonia, which
is used in some cases to achieve low
NOX emissions from the FCCU.
One commenter stated that the EPA
must set stronger HCN standards on
FCCU emissions because of the high
release amounts reported, the fact that
non-cancer risk is driven by emissions
of HCN from FCCU, and the fact that the
EPA has never set standards for HCN
emissions. The commenter provided a
report that they believe shows that the
EPA has not shown that CO is a
reasonable or lawful surrogate to control
HCN and has not shown that the
conditions necessary for a surrogate are
met with regard to CO and HCN, which
is an inorganic nonmetallic HAP.
Further, the report indicates that SCR is
a reasonable and cost effective method
for controlling HCN and that the EPA
failed to review and consider other
viable methods to control HCN and
must do so to satisfy its legal obligations
in this rulemaking.
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75204
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Response: At the time we
promulgated the MACT, we determined
that the control strategy used by the best
performing facilities to reduce organic
HAP emissions was the use of complete
combustion, which occurs when the CO
concentration is reduced to 500 ppmv
(see the proposal for Refinery MACT 2
at 63 FR 48899, September 11, 1998).
We rejected arguments that some
facilities operate at CO levels well
below 500 ppmv and, thus, the MACT
floor should be set at a lower CO
concentration because once CO
concentrations reached 500 ppmv, there
was no longer a correlation between
reduced CO concentrations and reduced
HAP concentrations. And, in fact,
emissions of certain HAP, such as
formaldehyde, tended to increase as CO
concentrations were reduced below 500
ppmv.10
In the current rulemaking action, we
determined at the time of the proposed
rule that this also holds true for HCN
emissions. That is, once CO emissions
are reduced to below 500 ppmv (i.e.,
complete combustion is achieved), we
no longer see a direct correlation
between CO concentrations and HCN
emissions.
All of the HCN emissions data we
have were reported from units operating
at or below the 500 ppmv CO limit (i.e.,
in the complete combustion range), so it
is not surprising that there is not a
strong correlation between CO and HCN
from the FCCU ICR source test data.
However, catalyst vendor data and
combustion kinetic theory support the
fact that, in the partial burn mode (with
CO concentrations of 2 to 6-percent,
which is 20,000 to 60,000 ppmv), HCN
concentrations exiting the FCCU
regenerator are much greater than for
units using complete combustion FCCU
regenerators or the concentration exiting
a post-combustion device used in
conjunction with a partial burn FCCU
regenerator. Therefore, we maintain that
complete combustion is the primary
control needed to achieve controlled
levels of HCN emissions.
We initially thought the higher levels
of HCN emissions that were reported by
sources achieving complete combustion
might be due to a switch away from
platinum-based combustion promoters
to palladium-based combustion
promoters. However, many of the units
that were tested and that had some of
the lowest HCN emissions used
palladium-based oxygen promoters.
Therefore, it appears unlikely that
10 U.S. EPA, 2001. Petroleum Refineries: Catalytic
Cracking Units, Catalytic Reforming Units, and
Sulfur Recovery Units—Background Information for
Promulgated Standards and Response to Comments.
Final Report.EPA–453/R–01–011. June. p. 1–19.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
palladium-based catalyst promoters are
linked to the higher HCN emissions. We
also evaluated one commenter’s
argument that CO is not a good
surrogate for HCN emissions, but that
SCR are a reasonable and cost-effective
control strategy. We are not aware of
any data that suggest that an SCR
removes HCN and the commenter did
not provide any support for that
premise. At proposal, we evaluated
HCN control on units using extra
oxygen or converting back to platinumbased promoters to oxidize any HCN
formed. This would cause more NOX
formation, which would then require
post-combustion NOX control, such as
an SCR. However, if HCN emissions are
not a function of CO concentration
beyond that required to achieve
complete combustion (as noted by the
commenter), then more aggressive
combustion conditions and the use of an
SCR (to remove the NOX formed) may
not be a viable control strategy.
Therefore, considering all of the data
currently available and the comments
received regarding HCN emissions and
controls, we maintain that the only
proven control technique is the use of
complete combustion as defined by a
CO level of 500 ppmv or less. We are
not establishing a more stringent CO
level because, once complete
combustion is achieved, (i.e., CO
concentrations drop below 500 ppmv),
no further reduction in HCN emissions
are achieved.
For the purposes of Refinery MACT 2,
we consider the emission limits and
operating requirements for organic HAP
in Tables 8 through 14 to subpart UUU
of part 63 adequate to also limit HCN
emissions.
Finally, we understand concerns
about the reported HCN emissions being
higher than anticipated and the need for
more data to better determine HCN
emissions levels. To address these
concerns, we are finalizing a
requirement that facility owners or
operators conduct a performance test for
HCN from all FCCU at the same time
they conduct the first PM performance
test on the FCCU following
promulgation of this rule. Facility
owners or operators that conducted a
performance test for HCN from a FCCU
in response to the refinery ICR or
subsequent to the 2011 Petroleum
Refinery ICR following appropriate
methods are not required to retest that
FCCU.
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
4. What is the rationale for our final
approach for the technology review?
a. Refinery MACT 1
We did not receive substantive
comments concerning our proposal that
it was not necessary to revise Refinery
MACT 1 requirements for MPV, gasoline
loading racks and cooling towers/heat
exchange systems. Based on the
rationale provided in the preamble to
the proposed rule, we are taking final
action concluding that it is not
necessary pursuant to CAA section
112(d)(6) to revise the MACT
requirements for MPV, gasoline loading
racks and cooling towers/heat exchange
systems emission sources at refineries.
We proposed that the options for
additional wastewater controls are not
cost effective and thus it was not
necessary to revise the MACT for these
emission sources. We received public
comments suggesting that emissions
from wastewater systems are higher
than modeled and that we should
develop additional technology
standards for wastewater treatment
systems regardless of cost. As we
discussed in the proposal, emissions
from wastewater are difficult to measure
and emission estimates rely on process
data and empirical correlations, which
introduces uncertainty into the
estimates. Although we do not have
evidence, based on the process data we
collected, that emissions are higher than
modeled at proposal, we note that the
fenceline monitoring program
effectively ensures that wastewater
emissions are not significantly greater
than those included in the emissions
inventory and modeled in the risk
assessment. Furthermore, we believe
that cost is a valid consideration in
determining whether it is necessary
within the meaning of section 112(d)(6)
to revise requirements and that we are
not required to establish additional
controls regardless of cost.
Consequently, we conclude that it is not
necessary to revise the Refinery MACT
1 requirements for wastewater systems
pursuant to CAA section 112(d)(6).
For storage vessels, we identified a
number of options, including requiring
tank fitting controls for external and
internal floating roof tanks, controlling
smaller tanks with lower vapor
pressures and requiring additional
monitoring to prevent roof landings,
liquid level overfills and to identify
leaking vents as developments in
practices, processes and control
technology. We proposed to crossreference the storage vessel
requirements in the Generic MACT
(effectively requiring additional control
for tank roof fittings) and to revise the
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
definition of Group 1 storage vessels to
include smaller tanks with lower vapor
pressures. We received comments that
we could have required additional
controls on tanks and monitoring for
landings, overfills and leaking vents
described above. We also received
comments related to clarifications of
specific rule references and overlap
provisions. We addressed these
comments in the ‘‘Response to
Comments’’ document, and we maintain
that the additional control options
described by the commenters (tank roof
landing/degassing requirements or use
of geodesic domes to retrofit external
floating roofs) are not cost-effective.
Consequently, based on the rationale
provided in the preamble to the
proposed rule and our consideration of
public comments, we are finalizing the
requirements as proposed with minor
clarifications of the rule references.
However, as with wastewater systems,
we note that the fenceline monitoring
program will ensure that the owner or
operator is effectively managing fugitive
emissions sources and should detect
landings, overfills, and leaking vents.
For equipment leaks, we identified
specific developments in practices,
processes and control technologies that
included requiring repair of leaking
components at lower leak definitions,
requiring monitoring of connectors, and
allowing the use of the optical imaging
camera as an alternative method of
monitoring for leaks. We proposed to
establish an alternative method for
refineries to meet LDAR requirements in
Refinery MACT 1. This alternative
would allow refineries to monitor for
leaks via optical gas imaging in place of
EPA Method 21, using monitoring
requirements to be specified in a not yet
proposed appendix K to 40 CFR part 60.
However, the development of appendix
K is taking longer than anticipated.
Therefore, we are not finalizing this
alternative monitoring method in
Refinery MACT 1.
We received comments suggesting
that additional requirements be imposed
to further reduce emissions from leaking
equipment components, such as
requiring ‘‘leakless’’ equipment,
reducing the leak threshold, and
eliminating delay of repair provisions.
As provided in the ‘‘Response to
Comments’’ document, we do not agree
that these additional requirements are
cost-effective. Based on the rationale
provided in the preamble to the
proposed rule and our consideration of
public comments, we conclude that it is
not necessary to revise the Refinery
MACT 1 requirements for equipment
leaks. Again, however, the fenceline
monitoring program is intended to
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
ensure that large leaks from fugitive
emissions sources, including equipment
leaks, are more quickly identified and
repaired, thereby helping to reduce
emissions from leaking equipment
components.
For marine vessel loading, we
identified control of marine vessel
loading operations with HAP emissions
of less than 10/25 tpy and the use of
lean oil absorption systems as
developments that we considered in the
technology review. We proposed to
amend 40 CFR part 63, subpart Y to
require small marine vessel loading
operations (i.e., operations with HAP
emissions less than 10/25 tpy) and
offshore marine vessel loading
operations to use submerged filling
based on the cargo filling line
requirements in 46 CFR 153.282. We
received comments that other options
considered during the technology
review of the standard were costeffective for small marine vessel loading
operations and should be required. As
provided in the ‘‘Response to
Comments,’’ we continue to believe
those other controls are not costeffective because of the high costs of
controls for limited additional organic
HAP emission reduction. Therefore, we
are finalizing these amendments as
proposed.
Finally, we proposed that it was
necessary to revise the MACT to require
fenceline monitoring as a means to
manage fugitive emissions from the
entire petroleum refinery, which
includes sources such as wastewater
collection and treatment operations,
equipment leaks and storage vessels. We
received numerous comments regarding
the proposed requirement to conduct
fenceline monitoring, many of which we
address above and the remainder of
which we respond to in the ‘‘Response
to Comments’’ document. After
considering comments, we maintain
that the proposed work practice
standard is authorized under section
112 of the CAA and will improve
fugitive management at the refinery.
Therefore, we are finalizing the key
components of fenceline monitoring
work practice as proposed. These
requirements include the use of passive
diffusive tube samplers (although we are
providing a mechanism to request
approval for alternative monitoring
systems provided certain criteria are
met), the 9 mg/m3 on a rolling annual
average basis action level, and the need
to perform corrective action to comply
with the action level.
Based on public comments received,
we are making numerous revisions to
clarify the fenceline monitor siting
requirements. This includes provisions
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
75205
to allow siting of monitors within the
property boundary as long as all
emissions sources at the refinery are
included within the monitoring
perimeter. We are also clarifying that we
do not consider public roads or public
waterways that bisect a refinery to be
property boundaries, and owners or
operators do not need to place monitors
along the internal public right-of-ways.
We are also providing provisions to
allow fixed placement of monitors at
500 feet intervals (with a minimum of
3 monitors) for subareas or segregated
areas. If an emissions source is near the
monitoring perimeter, an additional
monitor siting requirement would still
apply. The 500 feet provision is
provided to reduce burden for facilities
with irregular shapes or noncontiguous
property areas that we did not fully
consider at proposal.
We also received comments on the
compliance time and reporting
requirements associated with the
fenceline monitoring provisions. Upon
consideration of public comments, we
have revised the compliance period to 2
years after the effective date of the final
rule. Thus, beginning no later than 2
years after the effective date of the rule,
the source must have a fenceline
monitoring system that is collecting
samples such that the first rolling
annual average DC value would be
completed no later than 3 years after the
effective date of the final rule. Facilities
will have 45 days after the completion
of the first year of sampling, as
proposed, to submit the initial data set.
We are reducing the proposed
compliance period from 3 years to 2
years because the passive diffusive tube
monitors are easy to deploy and pilot
study demonstrations indicate that
significant time is not needed to deploy
the monitors. However, the reduced
compliance period still provides time to
resolve site-specific monitor placement
issues and to provide time to develop
and implement a site-specific
monitoring plan, if needed. We are
increasing the fenceline monitoring
reporting frequency (after the first year
of data collection) from semiannually to
quarterly to provide more timely
dissemination of the data collected via
this monitoring program.
b. Refinery MACT 2
We proposed to revise Refinery
MACT 2 to incorporate the
developments in monitoring practices
and control technologies reflected in the
Refinery NSPS subpart Ja limits and
monitoring provisions (73 FR 35838,
June 24, 2008). We are finalizing most
of these provisions as proposed.
Specifically, we are incorporating the
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75206
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Refinery NSPS subpart Ja PM limit for
new FCCU sources. We are also
finalizing compliance options for FCCU
that are not subject to Refinery NSPS
subpart J or Ja. These options would
allow such sources to elect to comply
with the Refinery NSPS subpart Ja
monitoring provisions to demonstrate
compliance with the emissions PM
limit. We are revising the averaging
period for the control device operating
limits or site-specific opacity limits to
be on a 3-hour average basis in order to
more directly link the operating limit to
the duration of the performance test
runs, on which they are based, as
proposed. We are incorporating
additional control device-specific
monitoring alternatives for various
control devices on FCCU, including
BLD monitoring as an option to COMS
for owners or operators of FCCU using
fabric filter-type control systems and
total power and secondary current
operating limits for owners or operators
of ESPs. We are adding an additional
requirement to perform daily checks of
the air or water pressure to atomizing
spray nozzles for owners or operators of
FCCU wet gas scrubbers not subject to
the pressure drop operating limit, as
proposed. Finally, we finalizing
requirements to conduct a performance
test at least once every 5 years for all
FCCU, as proposed. These requirements
are being finalized to ensure that control
devices are continuously operated in a
manner similar to the operating
conditions of the performance test and
to ensure that the emissions limits,
which are assessed based on the results
of three 1-hour test runs, are achieved
at all times.
We also proposed to eliminate the
Refinery NSPS subpart J compliance
option that allows refineries to meet the
30-percent opacity emissions limit
requirement and revise the MACT to
include control device operating limits
or site-specific opacity limits identical
to those required in Refinery NSPS
subpart Ja. We received numerous
comments, particularly from owners or
operators of FCCU that employ tertiary
cyclones to control FCCU PM emissions.
According to the commenters, opacity is
not a direct indicator of PM emissions
because finer particles will increase
opacity readings without a
corresponding mass increase in PM
emissions. Additionally, the
commenters stated that the site-specific
opacity limit generally leads to a sitespecific operating limit of 10-percent
opacity, which is too stringent and does
not adequately account for variability
between PM emissions and opacity
readings. According to the commenters,
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
FCCU with tertiary cyclones would
need to be retrofitted with expensive
and costly controls in order to meet the
10-percent opacity limit, even though
they are meeting the 1 lb/1000 lbs coke
burn PM emissions limit. It was not our
intent to require units to retrofit their
controls simply to meet the site-specific
opacity limit. However, the existing 30percent opacity limit in the subpart J
compliance option is not adequate to
ensure compliance with the PM
emissions limit at all times. After
reviewing the public comments and
available data, we determined that,
rather than removing the subpart J
compliance option altogether, it is
sufficient to add an opacity operating
limit of 20-percent opacity determined
on a 3-hour average basis to the existing
subpart J compliance option and to
require units complying with this
operating limit to conduct annual
performance tests (rather than one every
5 years) when the PM emissions
measured during the source test are
greater than 0.80 lb PM/1,000 lbs coke
burn-off. These provisions improve
assurance that these units are, in fact,
achieving the required PM emissions
limitation without requiring units to
retrofit controls due to variability in the
correlation of PM emissions and
opacity.
We did not propose to revise the
organic HAP emissions limits for FCCU
to further address HCN emissions. We
received numerous comments on this
issue. We continue to believe that
complete combustion is the appropriate
control needed to control HCN
emissions. Consequently, for the
purposes of Refinery MACT 2, we are
not changing the MACT standards to
further reduce emissions of HCN.
However, we understand that there are
uncertainties and high variability in
HCN emissions measured from FCCU.
In order to address the need for more
data to better characterize HCN
emissions levels, we are finalizing a
requirement for refinery owners or
operators to conduct a performance test
for HCN from all FCCU (except those
units that were tested previously using
acceptable methods as outlined in the
2011 Refinery ICR) during the first PM
test required as part of the on-going
compliance requirements for FCCU
metal HAP emissions. These data will
be useful to the EPA in understanding
HCN emissions from FCU and may help
to inform future regulatory reviews for
this source category.
We proposed that there have been no
developments in practices, processes,
and control technologies for CRU based
on our technology review and that
therefore it is not necessary to revise
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
these standards. Based on the rationale
provided in the preamble to the
proposed rule and our consideration of
public comments, we are finalizing our
conclusion.
For SRU, we identified the Refinery
NSPS subpart Ja allowance for oxygenenriched air as a development in
practice and we proposed that it was
necessary to revise the MACT to allow
SRU to comply with Refinery subpart Ja
as a means of complying with Refinery
MACT 2. The key issue identified by
commenters was that Refinery NSPS
subpart Ja includes a flow monitoring
alternative for determining the average
oxygen concentration in the enriched air
stream and that this was not included in
the proposed amendments to Refinery
MACT 2. This was an oversight on our
part. We are, based on the rationale
provided in the preamble to the
proposed rule and our consideration of
public comments, finalizing the SRU
revisions as proposed but with
inclusion of the flow monitoring
alternative provisions that are in
Refinery NSPS subpart Ja for this
source.
C. Refinery MACT Amendments
Pursuant to CAA Section 112(d)(2) and
(d)(3)
1. What did we propose pursuant to
CAA section 112(d)(2) and (d)(3) for the
Petroleum Refinery source categories?
We proposed the following revisions
to the Refinery MACT 1 and 2 standards
pursuant to CAA section 112(d)(2) and
(3) 11: (1) Adding MACT standards for
DCU decoking operations; (2) revising
the CRU purge vent pressure exemption;
(3) adding operational requirements for
flares used as APCD in Refinery MACT
1 and 2; and (4) adding requirements
and clarifications for vent control
bypasses in Refinery MACT 1.
For DCU, we proposed to require that
prior to venting or draining, each coke
drum must be depressured to a closed
blowdown system until the coke drum
vessel pressure is 2 psig or less. As
proposed, the 2 psig limit would apply
to each vessel opening/venting/draining
event at new or existing affected DCU
facilities.
For the CRU, we proposed to require
that any emissions during the active
11 The EPA has authority under CAA section
112(d)(2) and (d)(3) to set MACT standards for
previously unregulated emission points. EPA also
retains the discretion to revise a MACT standard
under the authority of section 112(d)(2) and (3), see
Portland Cement Ass’n v. EPA, 665 F.3d 177, 189
(D.C. Cir. 2011), such as when it identifies an error
in the original standard. See also Medical Waste
Institute v. EPA, 645 F. 3d at 426 (upholding EPA
action establishing MACT floors, based on postcompliance data, when originally-established floors
were improperly established).
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
purging or depressuring of CRU vessels
meet the applicable organic HAP
emission limitations in Tables 15 and 16
to subpart UUU regardless of the vessel
pressure.
For flares, we proposed to remove
cross references to the General
Provisions requirements for flares used
as control devices at 40 CFR 63.11(b)
and to incorporate enhanced flare
operational requirements directly into
the Refinery MACT rules. The proposed
rule amendments included:
• A ban on flaring of halogenated
vent streams.
• A requirement to operate with
continuously lit pilot flames at all times
and to equip the pilot system with an
automated device to relight the pilot if
it is extinguished.
• A requirement to operate with no
visible emissions except for periods not
to exceed a total of 5 minutes during
any 2 consecutive hours and to monitor
for visible emissions daily.
• A requirement to operate with the
flare tip velocity less than 60-feet-persecond or the velocity limit calculated
by an equation provided in the
proposed rule.
• A requirement to meet one of three
combustion zone gas properties
operating limits based on the net
heating value, lower flammability limit,
or combustion concentration. Owners or
operators could elect to comply with
any one of the three limits at any time.
Two separate sets of operating limits
were proposed: One for gas streams not
meeting all three ‘‘hydrogen-olefin
interaction criteria’’ specified in the rule
and a more stringent set of limits for gas
streams meeting all three hydrogenolefin interaction criteria. The
combustion zone net heating value
considered steam assist rates but not
‘‘perimeter air’’ assist rates.
• For air-assisted flares, a
requirement to meet an additional
‘‘dilution parameter’’ operating limit
determined based on the combustion
zone net heating values above, the
diameter of the flare and the perimeter
air assist rates.
The proposed amendments for flares
also included detailed monitoring
requirements to determine these
operating parameters either through
continuous parameter monitoring
systems or grab sampling, detailed
calculation instructions for determining
these parameters on a 15-minute block
average, and detailed recordkeeping and
reporting requirements. We also
proposed provisions to allow owners or
operators to request alternative
emissions limitations that would apply
in place of the proposed operating
limits.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
We proposed to revise the definition
of MPV to remove the current exclusion
for in situ sampling systems (onstream
analyzers). We also proposed to limit
the exclusion for gaseous streams routed
to a fuel gas system to apply only to
those systems for which any flares
receiving gas from the fuel gas system
are in compliance with the proposed
flare monitoring and operating limits.
We note that we also proposed revisions
related to monitoring of bypass lines,
but these revisions were proposed to
address concerns related to SSM
releases and are described in further
detail in section IV.D. of this preamble.
We proposed that emissions of HAP
may not be discharged to the
atmosphere from PRD in organic HAP
service to address concerns related to
SSM releases. To ensure compliance
with this proposed amendment, we
proposed to require that sources
monitor PRD using a system that is
capable of identifying and recording the
time and duration of each pressure
release and of notifying operators that a
pressure release has occurred. This
proposed requirement was addressed in
section IV.A.4. of the preamble for the
proposal.
2. How did the revisions pursuant to
CAA section 112(d)(2) and (3) change
since proposal?
We proposed identical standards for
existing and new DCU decoking
operations, but we are finalizing
standards for new and existing sources
that are not identical. We are finalizing
provisions that will require owners or
operators of existing DCU sources to
comply with a 2 psig limit averaged
over 60 cycles (i.e., 60 venting events),
rather than meet the 2 psig limit on a
per venting event basis, as proposed. We
are finalizing provisions that will
require owners or operators of new DCU
sources to comply with a 2.0 psig limit
on a per event, not-to-exceed basis. We
are adding one significant digit to the
limit for new DCU affected sources
because our re-review of permit
requirements conducted in response to
comments identified that the best
performing DCU source is required to
comply with a 2.0 psig limit on a per
event basis. In response to comments
regarding the proposed prohibition on
draining prior to achieving the pressure
limit, we are finalizing specific
provisions for DCU with water overflow
design and for double quenching.
For flares, we are not finalizing the
ban that we proposed on halogenated
vent streams and we are not finalizing
the proposed requirement to equip the
flare pilot system with an automated
device to relight an extinguished pilot.
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
75207
We are revising the MACT to include
the proposed no visible emissions limit
and the flare tip velocity limit as direct
emissions limits only when the flare
vent gas flow rate is below the
smokeless capacity of the flare. Under
the revised standard, when the flare is
operating above the smokeless capacity,
an exceedance of the no visible
emission limit and/or flare tip velocity
limit is not a violation of the standard
but instead triggers a work practice
standard. Flares operate above the
smokeless capacity only when there is
an emergency release event and thus the
work practice standard is intended to
address emissions during such
emergency release events. (See section
IV.D. of this preamble for more details
regarding this work practice standard).
We are also adding provisions that
would allow sources to use video
surveillance of the flare as an alternative
to daily Method 22 visible emissions
observations.
For flares, we are also simplifying the
combustion zone gas property operating
limits by finalizing a requirement only
for the net heating value of the
combustion zone gas. We are finalizing
requirements that flares meet a
minimum operating limit of 270 BTU/
scf NHVcz on a 15-minute average, as
proposed, and we are allowing refinery
owners or operators to use a corrected
heat content of 1212 BTU/scf for
hydrogen to demonstrate compliance
with this operating limit. We are not
finalizing separate combustion zone
operating limits for gases meeting the
hydrogen-olefin interaction criteria that
were proposed. We are also not
finalizing the alternative combustion
zone operating limits based on lower
flammability limit or combustibles
concentration.
We are finalizing ‘‘dilution
parameter’’ requirements for air-assisted
flares, but we are providing a limit only
for the net heating value dilution
parameter. Similar to the requirements
we are finalizing for the combustion
zone parameters, we are finalizing
requirements that flares meet a
minimum operating limit of 22 BTU/ft2
NHVdil on a 15-minute average, as
proposed, and we are allowing refinery
owners or operators to use a corrected
heat content of 1,212 BTU/scf for
hydrogen to demonstrate compliance
with this operating limit. We are not
finalizing separate dilution parameter
operating limits for gases meeting the
hydrogen-olefin interaction criteria that
were proposed. We are also not
finalizing the alternative dilution
parameter operating limits based on
lower flammability limit or
combustibles concentration.
E:\FR\FM\01DER2.SGM
01DER2
75208
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
We are providing an alternative to use
initial sampling period and process
knowledge for flares in dedicated
service as an alternative to continuous
or on-going grab sample requirements
for determining waste gas net heat
content.
We are finalizing revisions to the
definition of MPV, as proposed.
We are establishing work practice
standards that apply to PRD releases in
place of the proposed prohibition on
PRD releases to the atmosphere. The
work practice standards that we are
finalizing for PRD require refiners to
establish proactive, preventative
measures for each PRD to identify and
correct direct releases of HAP to the
atmosphere as a result of pressure
release events. Over time, these
proactive measures will reduce the
occurrence of releases and the
magnitude of releases when they occur,
while avoiding the environmental
disbenefits of having additional flare
capacity on standby to control these
unpredictable and infrequent events.
Refinery owners or operators will be
required to perform a root cause
analysis/corrective action following
such pressure release events. In
addition, a second release event in a 3year period from the same PRD with the
same root cause on the same equipment
is a deviation of the work practice
standard. A third release event in a
3-year period from the same PRD is a
deviation of the work practice standard
regardless of the root cause. PRD release
events related to force majeure events
are not considered in these hard limits.
3. What key comments did we receive
on the proposed revisions pursuant to
CAA section 112(d)(2) and (3) and what
are our responses?
tkelley on DSK3SPTVN1PROD with RULES2
i. DCU
Comment: Several commenters argued
that the EPA incorrectly set the MACT
floor emission limitation for DCU.
Commenters noted that CAA section
112(d)(3)(A) states that the MACT limit
for existing sources ‘‘shall not be less
stringent, and may be more stringent
than the average emission limitation
achieved by the best performing 12percent of the existing sources’’
excluding those first achieving that level
within 18 months prior to proposal or
30 months prior to promulgation,
whichever is later. According to the
commenters, the EPA failed to follow
this procedure in setting the 2 psig vent
limit as a MACT floor because the EPA
incorrectly considered permit limits and
other non-performance based criteria
instead of basing the MACT floor on the
actual performance of sources.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Commenters stated that the EPA
improperly considered permit limits
that should have been excluded from
consideration, as well as considering
permit limits for closed facilities instead
of using more accurate data from
operating DCUs at sources that
submitted actual emissions data.
Specifically, commenters stated that the
DCU at the non-operational plant
(Hovensa) should not be included. One
commenter noted that they operate one
of the South Coast DCU listed as subject
to a 2 psig limit and asserted that it does
not currently meet that emission
limitation. The commenter claimed that
significant capital investment would be
required in order for the DCU to comply
with the 2 psig limit. According to one
commenter, data for six of the eight
DCU they claim the EPA considered for
the MACT floor should not be counted
in determining the limit that represents
the average emission limitation actually
achieved 18 months prior to the
proposal.
Response: CAA section 112(d)(3)(A)
states that the existing source standard
shall not be less stringent than the
average emission limitation achieved by
the best performing 12-percent of the
existing sources (for which the
Administrator has emissions
information), excluding those sources
that have, within 18 months before the
emission standard is proposed or within
30 months before such standard is
promulgated, whichever is later, first
achieved a level of emission rate or
emission reduction which complies, or
would comply if the source is not
subject to such standard, with the
lowest achievable emission rate (as
defined by section 171) applicable to the
source category and prevailing at the
time, in the category or subcategory for
categories and subcategories with 30 or
more sources. We consider a 2 psig
emissions limitation to be equivalent to
the lowest achievable emission rate
(LAER) emission limits. Thus, we agree
with the commenter that sources that
first meet the 2 psig limit on or after
December 30, 2012, should be excluded
from the MACT floor analysis. We also
agree that under CAA section
112(d)(3)(A), the MACT floor analysis
focuses on those sources that are
achieving the emission limit (i.e., the
emission limitation ‘‘achieved by
. . . ’’). The EPA has previously
determined that the 6th-percentile unit
is a reasonable estimate of the average
emission limitation achieved by the best
performing 12-percent of sources
especially when averaging across units
with and without control requirements.
As noted in our DCU MACT floor
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
analysis memorandum (Docket ID No.
EPA–HQ–OAR–2010–0682–0203), the
6th-percentile is represented by the
fifth-best performing DCU. If we exclude
the two South Coast refineries and the
two Marathon Garyville DCU because
these sources were not implementing
the 2 psig permit limit prior to
December 30, 2012, the fifth-best
performing DCU would be represented
by the Bay Area refineries (4.6 psig).
However, based on the 2011 Petroleum
Refinery ICR responses, 25 out of 75 (33percent) DCU have a ‘‘typical coke drum
pressure when first vented to the
atmosphere’’ of 2 psig or less and 10 out
of 75 (13-percent) DCU have a ‘‘typical
coke drum pressure when first vented to
the atmosphere’’ of 1 psig or less. While
we acknowledge that these data
represent ‘‘typical’’ operations and not
necessarily a never-to-be-exceeded
emissions limitation, we conclude that
this information is sufficient for us to
conclude that the average emission
limitation achieved by the best
performing 12-percent of sources is
consistent with a 2 psig emissions
limitation. This is because facility
owners or operators commonly target to
operate at approximately half the
allowable emissions limit to ensure that
they can comply with the emissions
limit at all times. Therefore, we
maintain that an average venting
pressure of 2 psig is the MACT floor
level for decoking operation at existing
sources based on the ICR responses and
considering the average performance
expected.
Comment: Four commenters
suggested that the 2 psig limit, if
finalized, should be based on a rolling
30-day average per DCU rather than a
never to be exceeded ‘‘instantaneous’’
standard. According to the commenters,
an instantaneous standard is
unnecessary to address HAPs with
chronic health impacts and adds cost
and compliance challenges. According
to the commenters, chronic health
impacts are not materially affected by
short-term variability, but instead
depend on the average concentration of
exposure over a 70-year lifetime;
therefore, there is no health based or
environmental reason for requiring an
instantaneous limit. The commenters
noted that there would be additional
capital costs to comply with a 2 psig
not-to-be-exceeded limit compared to a
30-day average 2 psig limit vent
pressure. One commenter specifically
requested that the EPA also confirm that
a pressure of 2.4 psig is compliant with
the 2 psig limit vent pressure. Another
commenter also requested clarification
that the vent pressure can be rounded to
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
one significant figure when determining
compliance.
Response: For new sources, the
MACT floor emission limit for DCU is
based on the best-performing source.
Based on this and other comments
received, we again reviewed existing
permit conditions. Based on this review,
we found that one of the permit
requirements specified the pressure
limit as 2.0 psig for each coke drum
venting event. Therefore, we are
finalizing the new source MACT floor as
2.0 psig on a per coke drum venting
event basis.
As discussed in response to the
previous comment, we are basing the
MACT floor for existing source DCU on
responses we received from the 2011
Petroleum Refinery ICR. Because the
ICR requested the ‘‘typical coke drum
pressure when first vented to the
atmosphere,’’ we do not consider the
information provided in ICR responses
to reflect a ‘‘never-to-be-exceeded’’
limit. Therefore, we evaluated whether
it is reasonable to allow averaging, and
if so, what averaging period should be
provided.
Health risks are not considered in
establishing MACT requirements, so we
do not consider the argument that
chronic effects are evaluated over a 70year period to be relevant to a
determination of the MACT floor.
However, a primary consideration
regarding averaging periods is how the
averaging period was considered in
setting the floor and whether the
intended reductions will occur under a
different averaging period. According to
the heat balance method for estimating
DCU emissions, DCU decoking
operations emissions are directly
proportional to the average bed
temperature. While the relationship is
not exactly linear, the average bed
temperature is expected to be a function
of the venting pressure. Moreover, the
shape of the pressure-temperature
correlation curve is such that the
emissions at 6 psig are almost exactly
but not quite three times the emissions
at 2 psig. Given the expected linearity
of the emissions with venting pressures,
we are not concerned with an
occasional venting event above 2 psig
because the average emissions from a
facility meeting an average 2 psig
pressure limit would be identical to the
emissions achieved by a facility that
vented each time at 2 psig. That is,
given the expected linearity in the
projected DCU emissions to the venting
pressure, we conclude that it is
reasonable to allow averaging across
events and that the precise averaging
period is not a critical concern.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Most industry commenters requested
a 30-day average. However, different
facilities have different numbers of
DCU, different numbers of drums per
DCU and different cycle times.
Consequently, basing the averaging
period across a given time period would
result in significantly different number
of venting events included in a 30-day
average for different facilities and
generally provide more flexibility to
larger refineries and less flexibility to
smaller refineries. Based on the ICR
responses, almost half of all DCU
operate with two drums and about 90percent of DCU have two to four coke
drums; however, a few DCU have six or
even eight drums. Also, based on the
ICR responses, the average complete
coke drum cycle time is 32 hours, but
can be as short as 18 hours and as long
as 48 hours. Reviewing the ICR
responses, we found that a 30-day
average would include 30 events for
some facilities and more than 250
events at other facilities.
Since the existing source MACT
standards apply ‘‘in combination’’ to
‘‘all releases associated with decoking
operations’’ at a given facility, we
determined that it was reasonable to
consider an averaging period that
applies to the number of venting events
from all coke drums at the facility rather
than to all coke drums for a specific
DCU for a specified period of time. This
provides a more consistent basis for the
averaging period and allows the same
operational flexibility for small
refineries as large refineries. Based on
the ICR responses, the median (typical)
DCU has 60 venting events in a 30-day
period. Providing an averaging period of
60 venting events provides a more
consistent averaging basis for all
facilities, regardless of the number of
DCU at the facility and the number of
drums and cycle times for different
DCU. Additionally, it eliminates issues
with respect to how to handle operating
days versus non-operating days, e.g., in
the event of a turn-around resulting in
a limited number of venting events in a
30-calendar day period. Therefore, we
are establishing a 2 psig limit based on
a 60-event average considering all coke
drum venting events at an existing
source and we are finalizing a 2.0 psig
limit on a per coke drum venting event
for DCU at new sources.
We have consistently maintained our
policy to round to the last digit
provided in the emission limit, a
pressure of 2.4 psig would round to 2
psig and would be compliant with a
requirement to depressure each coke
drum to a closed blowdown system
until the coke drum vessel pressure is
2 psig or less, but it would not be
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
75209
compliant with the revised new source
provision to depressure until the coke
drum vessel pressure is 2.0 psig or less.
A coke drum pressure of 2.04, however,
would be compliant with the revised
new source requirement pressure limit
of 2.0 psig.
ii. Refinery Flares
Comment: Several commenters
suggested that the proposed flare
operating limits were too complex. The
commenters recommended that the EPA
eliminate the dual flare combustion
zone heat content limits related to the
proposed hydrogen-olefin interaction
criteria and instead finalize a single
combustion zone net heating value of
approximately 200 BTU/scf, which
would minimize the unnecessary
burning of supplemental gas but still
ensure good combustion efficiency.
A few commenters suggested that the
EPA based the proposed combustion
zone limits on an invalid data analysis,
that the 1 minute PFTIR data should not
be used to establish combustion
efficiency correlations, and that the
emission limits should be set so as to
provide an equal chance of false
positives and negatives. A few
commenters suggested that the EPA
should assign hydrogen a heating value
of 1,212 BTU/scf to more accurately
reflect its flammability in a NHV basis
and that doing so is consistent with
some recent flare consent decrees and
would help reduce natural gas
supplementation for facilities
complying only with the NHVcz metric.
Several commenters suggested that
neither scientific literature nor the
available flare test data support the
EPA’s claim of an adverse hydrogenolefin interaction on combustion
efficiency and that the EPA should not
finalize the more restrictive combustion
zone operating limits for all flare types.
These commenters suggested that the
EPA did not provide any evidence the
assumed hydrogen-olefin effect actually
exists; that statistical analysis
demonstrates the EPA developed their
limit based on random differences in
data; that the PFTIR data analysis
method of using the individual minuteby-minute data instead of the test
average data is flawed and leads to
invalid conclusions; and that proper
analysis of the data demonstrates the
more stringent operating limits for
hydrogen-olefin conditions cannot be
supported.
Some commenters suggested that
there is evidence to support more
stringent flare combustion zone limits
for a narrowly defined high
concentration propylene-only condition
as outlined in some of the recent flare
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75210
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
consent decrees but that the flare test
data do not support more stringent
operating limits for the proposed
hydrogen-olefins criteria by the EPA.
Additionally, one commenter suggested
that if the EPA decides to proceed with
the more restrictive combustion zone
limits for the hydrogen-olefins
interaction cases then the final rule
should not expand beyond an
interaction between hydrogen and
propylene.
Several commenters suggested that
the proposed 15-minute feed forward
averaging time for flares (e.g.,
combustion zone parameters, air-assist
dilution parameters and associated flow
rates) is arbitrary, unrealistic and
unworkable and that the feed forward
compliance determination should not be
finalized and, if it is finalized, the
averaging time should be extended to
1-hour, 3-hour, or 24-hour. To support
these suggested averaging periods,
commenters claimed that typical
standards for combustion devices are
averaged over these suggested
timeframes, noting as an example,
recent refinery flare consent decrees that
contain a 3-hour average. The
commenters also asserted that both a GC
and calorimeter will be needed to obtain
data rapidly enough to try and maintain
a 15-minute average; that the feed
forward approach requires calculation
artifices to attempt to correct for the fact
that compliance cannot be determined
until the averaging period is over; and
that a longer averaging time is needed
for instrument and control response
time.
Response: In addressing these
comments, we further analyzed the flare
emissions test data. First, to address
concerns that the minute-by-minute
analysis produced flawed results, we recompiled the data into approximate
‘‘15-minute averages’’ to the extent
practical based on the duration of a
given test run (e.g., a 10-minute run was
used as 1 run and a 32-minute run was
divided into 2 runs of 16 minutes each).
We do not find significant differences in
the data or that different conclusions
would be drawn from the data based on
this approach as compared with the
minute-by-minute analysis used for the
proposed rule.
Next, we evaluated the 15-minute run
data using the normal net heating value
for hydrogen of 274 Btu/scf, which is
the value we used in the analysis for the
proposed rule and also evaluated the
data using the 1,212 Btu/scf, the value
recommended by some commenters.
The 1,212 Btu/scf value is based on a
comparison between the lower
flammability limit and net heating value
of hydrogen compared to light organic
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
compounds and has been used in
several consent decrees to which the
EPA is a party. Based on our analysis,
we determined that using a 1,212 Btu/
scf value for hydrogen greatly improves
the correlation between combustion
efficiency and the combustion zone net
heating value over the entire array of
data. Using the net heating value of
1,212 Btu/scf for hydrogen also greatly
reduced the number of ‘‘type 2 failures’’
(instances when the combustion
efficiency is high, but the gas does not
meet the NHVcz limit). One of the
primary motivations for the proposed
approach to provide alternative limits
based on lower flammability limits and
combustibles concentrations was to
reduce these type 2 failures. Therefore,
we proposed all three of these
parameters (i.e., NHVcz, LFL and total
combustibles) and allowed flare owners
or operators to comply with any of the
parameter limits at any time. When
using the net heating value of 1,212 Btu/
scf for hydrogen, the other two
alternatives no longer provide any
improvement in the ability to predict
good flare performance. Consequently,
we are simplifying the operating limits
to use only NHVcz.
Next, we re-evaluated whether to
finalize the proposed dual combustion
zone operating limits for refinery flares
that met certain hydrogen-olefins
interactions or to finalize a single
combustion zone net heating value
limit. The newly re-compiled PFTIR run
average flare dataset suggests that higher
operating limits may be appropriate for
some olefin-hydrogen mixtures.
However, the dataset using 15-minute
test average runs is much smaller than
the set using 1-minute runs and thus
creates a greater level of uncertainty. In
addition, we cannot definitively
conclude that a dual combustion zone
limit for refinery flares meeting certain
hydrogen-olefins interactions is
appropriate given these uncertainties.
Thus, in order to minimize these
uncertainties and streamline the
compliance requirements, we used all of
the 15-minute test run average data
together as a single dataset in an effort
to determine an appropriate, singular
combustion zone net heating value
operational limit.
Finally, we conducted a Monte Carlo
analysis to help assess the impacts of
extending the averaging time on the test
average flare dataset of 15-minute runs
to 1-hour or 3-hour averaging time
alternatives. While we consider it
reasonable to provide a longer averaging
time for logistical reasons, the Monte
Carlo analysis demonstrated, consistent
with concerns described in our
proposal, that short periods of poor
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
performance can dramatically limit the
ability of a flare to achieve the desired
control efficiency. Consequently, we
find it necessary to finalize the
proposed 15-minute averaging period to
ensure that the 98-percent control
efficiency for flares is achieved at all
times. However, we understand that
flare vent gas flow and composition are
variable. While a short averaging time is
needed to ensure adequate control given
this variability, we also understand the
complications that this variability
places on flare process control in efforts
to meet the NHVcz limit. Therefore, we
are clarifying that the 270 Btu/scf
NHVcz value is an operational limit that
must be calculated according to the
requirements in this rule. We also
clarify that compliance with this
operational limit must be evaluated
using the equations and calculation
methods provided in the rule. We
proposed a feed forward calculation
method to allow refinery owners or
operators a means by which to adjust
steam (or air) and, if necessary,
supplemental natural gas flow, in order
to meet the limit. In other words, ‘‘feed
forward’’ refers to the fact that the rule
requires the refinery owners or
operators to use the net heating value of
the vent gas (NHVvg) going into the flare
in one 15-minute period to adjust the
assist media (i.e., steam or air) and/or
the supplemental gas in the next 15minute period, as necessary for the
equation in the rule to calculate an
NHVcz limit of 270 BTU/scf or greater.
We recognize that when a subsequent
measurement value is determined, the
instantaneous NHVcz based on that
compositional analysis and the flow
rates that exist at the time may not be
above 270 Btu/scf. We clarify that this
is not a deviation of the operating limit.
Rather, the owner or operator is only
required to make operational
adjustments based on that information
to achieve, at a minimum, the net
heating value limit for the subsequent
15-minute block average. Failure to
make adjustments to assist media or
supplemental natural gas using the
equation provided for calculating an
NHVcz limit of 270 BTU/scf, using the
NHVvg from the previous period, would
be a deviation of the operating limit.
Alternatively, if the owner or operator
is able to directly measure the NHVvg
on a more frequent basis, such as with
a calorimeter (and optional hydrogen
analyzer), the process control system is
able to adjust more quickly, and the
owner or operator can make adjustments
to assist media or supplemental natural
gas more quickly. In this manner, the
owner or operator is not limited by
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
relying on NHVvg data that may not
represent the current conditions.
Therefore, the owner or operator may
opt to use the NHVvg from the same
period to comply with the operating
limit.
Based on the results of all of our
analyses, the EPA is finalizing a single
minimum NHVcz operating limit for
flares subject to the Petroleum Refinery
MACT standards of 270 BTU/scf during
any 15-minute period. The agency
believes, given the results from the
various data analyses conducted, that
this operating limit is appropriate,
reasonable and will ensure that refinery
flares meet 98-percent destruction
efficiency at all times when operated in
concert with the other suite of
requirements refinery flares need to
achieve (e.g., flare tip velocity
requirements, visible emissions
requirements, and continuously lit pilot
flame requirements). For more detail
regarding our data re-analysis, please
see the memorandum titled ‘‘Flare
Control Option Impacts for Final
Refinery Sector Rule’’ in Docket ID No.
EPA–HQ–OAR–2010–0682.
Comment: Numerous commenters
objected to the proposed requirements
to have the velocity and visible
emissions limits apply at all times for
flares. Commenters suggested that flares
are not designed to meet the visible
emissions and flare tip velocity
requirements when being operated
beyond their smokeless capacity and
suggested several alternative
approaches: remove the visible
emissions and flare tip velocity
requirements from the rule altogether;
exempt flares from these requirements
during emergencies; or add a
requirement to maintain a visible flame
present at all times or include a work
practice standard in the rule when flares
are operated beyond their smokeless
capacity at full hydraulic load. The
commenters identified full hydraulic
load as the maximum flow the flare can
receive based on the piping diameter of
the flare header and operating pressure
of processes connected to the flare
header system. They also specified that
full hydraulic load would only occur if
all sources connected to the flare header
vented at the same time, which might
result from an emergency shutdown due
to a plant-wide power failure.
According to commenters, flares are
typically designed to operate in a
smokeless manner at 20 to 30-percent of
full hydraulic load. Thus, they claimed,
flares have two different design
capacities: A ‘‘smokeless capacity’’ to
handle normal operations and typical
process variations and a ‘‘hydraulic load
capacity’’ to handle very large volumes
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
of gases discharged to the flare as a
result of an emergency shutdown.
According to commenters, this is
inherent in all flare designs and it has
not previously been an issue because
the flare operating limits did not apply
during malfunction events. However, if
flares are required to operate in a
smokeless capacity during emergency
releases, the commenters claimed that
refineries would have to quadruple the
number of flares at each refinery to
control an event that may occur once
every 2 to 5 years.
To support their suggestions,
commenters pointed out that flaring
during emergencies is the optimum way
of handling very large releases and that
the flare test data clearly demonstrate
that visible emissions and/or high flare
tip velocity do not suggest poor
destruction efficiency during such
events. The commenters also argued
that operators should not have
conflicting safety and environmental
considerations to deal with during these
times. The commenters stated that
refiners are still subject to a civil suit
even if the EPA uses its enforcement
discretion where such a release would
violate the limit and in order to avoid
such liability, many new flares would
have to be built. Commenters estimated
that 500 new large flare systems at a
capital cost in excess of $10–20 billion
would need to be built because of the
amount of smokeless design capacity
that would be needed and that this
significant investment would take the
industry at least a decade to install.
Response: At the time of the proposed
rule, we did not have any information
indicating that flares were commonly
operated during emergency releases at
exit velocities greater than 400 ft/sec
(which is 270 miles per hour (mph)).
Similarly, we did not have information
to indicate that flares were commonly
designed to have a smokeless capacity
that is only 20 to 30-percent of their
‘‘hydraulic load capacity.’’ While we are
uncertain that refineries actually would
install additional flares to the degree the
commenters claim, based on the
possibility that there may be an event
every 2 to 5 years that would result in
a deviation of the smokeless limit, we
also recognize that it would be
environmentally detrimental to operate
hundreds of flares on hot standby in an
effort to never have any releases to a
flare that exceed the smokeless capacity
of that flare. This is because operating
hundreds of new flares to prevent
smoking during these rare events will
generate more ongoing emissions from
idling flares than the no visible
emissions limit might prevent during
one of these events. Therefore, we
PO 00000
Frm 00035
Fmt 4701
Sfmt 4700
75211
considered alternative operating limits
or alternative standards that could apply
during these emergency release events.
As an alternative to the proposed
requirement that flares meet the visible
emissions and velocity limits at all
times, we considered a work practice
standard for the limited times when the
flow to the flare exceeds the smokeless
capacity of the flare. Owners or
operators of flares would establish the
smokeless capacity of the flare based on
design specification of the flare. Below
this smokeless capacity, the velocity
and visible emissions standards would
apply as proposed. Above the smokeless
capacity, flares would be required to
perform root cause analysis and take
corrective action to prevent the
recurrence of a similarly caused event.
Multiple events from the same flare in
a given time period would be a
deviation of the work practice standard.
Force majeure events would not be
included in the event count for this
requirement.
Based on industry claims that there is
a hydraulic load flaring event, on
average, every 4.4 years, we assumed
the best performers would have no more
than one event every 6 years, or a
probability of 16.7-percent of having an
event in any given year. We found that,
over a long period of time such as 20
years, half of these best performers
would have 2 events in a 3 year period,
which would still result in over half the
‘‘best performing’’ flares having a
deviation of the work practice standard
if it was limited to 2 events in 3 years.
Conversely, only 6 percent would have
3 events in 3 years over this same time
horizon. Based on this analysis, 3 events
in 3 years would appear to be
‘‘achievable’’ for the average of the best
performing flares.
Pursuant to CAA section 112(d)(2)
and (3), we are finalizing a work
practice standard for flares that is based
on the best practices of the industry,
and considers the rare hydraulic load
events that inevitably occur at even the
best performing facilities.
The best performing facilities have
flare management plans that include
measures to minimize flaring during
events that may cause a significant
release of material to a flare. Therefore,
we are requiring owners or operators of
affected flares to develop a flare
management plan specifically to
identify procedures that will be
followed to limit discharges to the flare
as a result of process upsets or
malfunctions that cause the flare to
exceed its smokeless capacity. We are
specifically requiring refinery owners or
operators to implement appropriate
prevention measures applicable to these
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75212
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
emergency flaring events (similar to the
prevention measures we are requiring in
this final rule to minimize the
likelihood of a PRD release). Refiners
will be required to develop a flare
minimization plan that describes these
proactive measures and reports
smokeless capacity. Refiners will need
to conduct a specific root cause analysis
and take corrective action for any flare
event above smokeless design capacity
that also exceeds the velocity and/or
visible emissions limit. If the root cause
analysis indicates that the exceedance is
caused by operator error or poor
maintenance, the exceedance is a
deviation from the work practice
standard. A second event within a
rolling 3-year period from the same root
cause on the same equipment is a
deviation from the standard. Events
caused by force majeure, which is
defined in this subpart, would be
excluded from a determination of
whether there has been a second event.
Finally, and again excluding force
majeure events, a third opacity or
velocity limit exceedance occurring
from the same flare in a rolling 3-year
period is a deviation of the work
practice standard, regardless of the
cause.
Comment: Several commenters
suggested that the EPA should revise the
combustion efficiency requirements to
apply only to steam-assisted flares used
as Refinery MACT control devices
during periods of time that the flares are
controlling Refinery MACT regulated
streams. One commenter suggested that
the EPA misused the TCEQ data in
proposing the NHVcz metric and that the
proposed limits are overly conservative.
The commenter requested that the EPA
work with stakeholders to conduct
additional testing to determine what, if
any, operating parameters are
appropriate and necessary to achieve an
adequate destruction efficiency for nonsteam-assisted flares.
Response: We disagree with the
commenters that the combustion
efficiency requirements should apply
only to steam-assisted flares. The
available data (for runs where steam
assist is turned off) as well as the
available combustion theories suggest
that the combustion zone net heating
value minimum limit, which is the vent
gas net heating value for unassisted or
perimeter air-assisted flares, is
necessary to ensure proper flare
performance. While we agree that
additional data on air-assisted flares
would allow for a more robust analysis,
the data we do have strongly indicate
that air-assisted flares can be overassisted and that the combustion
efficiency of air-assisted flares that are
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
over-assisted is below 98-percent
control efficiency.
Comment: A few commenters
suggested that the proposed flare
regulations should not apply to part 63,
subpart R (gasoline loading) and subpart
Y (marine vessel loading) facilities, and
to part 61, subpart FF (benzene waste)
facilities. The commenters
recommended that flares associated
with gasoline loading, marine vessel
loading and wastewater treatment
emissions need to comply only with the
General Provisions for flares. Some of
these commenters argued that these
sources are more consistent in flow and
composition than other refinery sources,
so the new requirements are not
necessary to ensure good combustion for
these ‘‘dedicated’’ flares. Some
commenters suggested that operators of
flares with consistent flow and
composition be allowed to use process
knowledge or engineering judgment
rather than be required to install
continuous monitors or be subject to
ongoing grab sampling requirements.
Some commenters noted that the
required control efficiency for some
refinery emissions sources subject to
subpart CC sources is 95-percent. One
commenter also requested that the EPA
provide overlap provisions so flares
used to control sources from different
MACT sources would not have
duplicative requirements.
Response: The regulatory revisions
that we are finalizing apply to
petroleum refinery sources subject to
part 63, subparts CC and UUU. Gasoline
loading, marine vessel loading and
wastewater treatment operations that are
part of the refinery affected source as
defined at 40 CFR 63.640 are subject to
subpart CC. Gasoline loading, marine
vessel loading and wastewater treatment
operations located at non-refinery
source categories are not subject to part
63, subpart CC and, thus, would not be
subject to the revisions to subpart CC
being finalized in this action. To the
extent that the commenters are
requesting that the EPA establish flare
requirements that would apply to flares
that are not part of the refinery affected
source, that request is beyond the scope
of this rulemaking, which only
addresses revisions to Refinery MACT 1
and 2. When we issue rules addressing
requirements for other sources with
flares, we will consider issues similar to
those we considered in this action and
determine at that time whether revisions
to those other flare requirements are
necessary.
The commenters note that some
subpart CC emissions sources have only
a control efficiency requirement of 95percent. While this may be true, where
PO 00000
Frm 00036
Fmt 4701
Sfmt 4700
the owner or operator chooses to control
these sources through the use of a flare,
operation of that flare was subject to
operational requirements in the General
Provisions at 40 CFR 63.11 and the best
performing flares were achieving 98percent control at the time the General
Provisions were promulgated. At the
time the General Provisions were
promulgated, we received no comments
that the EPA should set different
operational limits for flares that are
controlling emissions from sources
where the standard may vary by level of
control efficiency and we see no basis
to do so now. The purpose of the
revisions to the flare operating
requirements is to ensure that flares are
operating consistent with the MACT
floor requirements for any and all
sources that may use flares as a control
device (79 FR 36905, June 30, 2014). As
the MACT floor control requirements of
certain refinery sources that allow the
use of a flare as a control device is 98percent, we established operational
limits to ensure flares used as control
devices meet this MACT requirement.
To the extent that the commenters are
requesting that the EPA establish an
alternative monitoring approach for
flares in dedicated service that have
consistent composition and flow, we
agree that these types of flares, which
have limited flare vent gas streams, do
not need to have the same type of ongoing monitoring requirements as those
with more variable waste streams. Thus,
we are establishing an option that
refinery owners or operators can use to
demonstrate compliance with the
operating requirements for flares that
are in dedicated service to a specific
emission source, such as a wastewater
treatment operation. Refinery owners or
operators will need to submit an
application for the use of this
alternative. The application must
include a description of the system,
characterization of the vent gases that
could be routed to the flare based on a
minimum of 7 grab samples (14 daily
grab samples for continuously operated
flares) and specification of the net
heating value that will be used for all
flaring events (based on the minimum
net heating value of the grab samples).
We are also allowing engineering
estimates to characterize the amount of
gas flared and the amount of assist gas
introduced into the system. For
example, the use of fan curves to
estimate air assist rates is acceptable.
Flare owners or operators would use the
net heating value determined from the
initial sampling phase and measured or
estimated flare vent gas and assist gas
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
flow rates, if applicable, to demonstrate
compliance with the standards.
Comment: A few commenters
suggested that the EPA’s proposed work
practice and monitoring standards for
flares are CAA section 112(d)
‘‘developments’’ required by law and
supported by the evidence, and reflect
best practices at many refineries today.
One commenter suggested that the EPA
must allow companies with consent
decrees to meet their consent decree
requirements as an alternative
compliance approach and in lieu of the
proposed requirements.
Response: We proposed the enhanced
monitoring requirements and operating
limits under authority of CAA sections
112(d)(2) and (d)(3) to ensure that flares
used to control regulated Refinery
MACT 1 or 2 gas streams are meeting
the prescribed control efficiencies
established at the time the MACT
standard was promulgated. And, we
continue to believe that these revisions
are appropriate under CAA sections
112(d)(2) and (d)(3). The commenter has
not suggested, and we do not believe,
that the revisions promulgated would
differ in substance if they were instead
promulgated under CAA section
112(d)(6).
In general, we expect that the NHVcz
monitoring requirements that we are
finalizing for flares will be consistent
with the requirements in various
consent decrees. However, we have not
conducted a rigorous evaluation of
equivalency between various
requirements and therefore we are not at
this time providing an allowance for
flare owners or operators to comply
with the NHVcz operating limits and any
provisions for necessary monitoring
needed in the consent decree in lieu of
the NHVcz limits and monitoring
requirements established in this rule. In
the event that an owner or operator
wishes to continue complying only with
the requirements of a consent decree,
the rule contains provisions by which
owner or operator can seek approval for
alternative limits that are at least
equivalent to the performance achieved
from complying with the operating
limits included in the final rule.
iii. Pressure Relief Devices
Comment: Several commenters
suggested that the EPA develop a work
practice approach for atmospheric PRD
rather than a prohibition on releases.
One commenter recommended that the
EPA establish a work practice standard
for atmospheric PRDs that requires
refiners to implement a base level of
preventative measures including: Basic
process controls, instrumented alarms,
documented and verified routine
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
inspection and maintenance programs,
safety-instrumented systems, disposal
systems, provide redundant equipment,
increase vessel design pressure and
systems that reduce fire exposure on
equipment. Additionally, the
commenter recommended that the EPA
require refiners to perform root cause
analysis and implement corrective
action in the event of a release. The
commenter stated these requirements
would be similar to the root cause
analysis/corrective action requirements
recently promulgated for flares under
NSPS subpart Ja and provided specific
regulatory language for a proposed work
practice approach. (See section 2.4.1.8
in Docket item EPA–HQ–OAR–2010–
0682–0583.) One commenter requested
that the EPA allow a process for
companies to submit an application for
case-by-case limits to be approved by
the agency, either the EPA or a
delegated state similar to the alternate
NOX limits for process heaters provided
in NSPS subpart Ja. This commenter
recommended that the EPA establish
reasonable work practice standards,
specifically suggesting that the EPA
develop work practice standards
consistent with API 521. The
commenter stated that the EPA should
provide an implementation period for
compliance that goes beyond the
timeframe provided under CAA section
112(d). The commenter added that the
EPA should adopt specified changes to
the definition of an atmospheric
pressure relief safety valve and provided
suggested regulatory language for a
proposed work practice standard for
PRDs in EPA–HQ–OAR–2010–0682–
0549.
Another commenter stated that the
EPA should require, as the Bay Area Air
Quality Management District
(BAAQMD) does, that any refinery that
has a reportable PRD event must take
certain steps to prevent such releases in
the future (BAAQMD Rule 8–28–304).
In particular, such a refinery must create
a Process Hazard Analysis, meet the
Prevention Measures Procedures
specified in section 8–28–405, and
conduct a failure analysis of the
incident, to prevent recurrence of
similar incidents (Id. Reg. section 8–28–
304.1). If a second release occurs, then,
within one year, the facility must vent
its PRDs to a vapor recovery or disposal
system that meets certain requirements
(Id. Reg. section 8–28–304.2). The
commenter asserted that the EPA’s
prohibition on releases to the
atmosphere from PRD will ensure that
refineries take the necessary steps to
prevent such releases, or install control
devices so that any releases from PRDs
PO 00000
Frm 00037
Fmt 4701
Sfmt 4700
75213
that must occur are vented through a
control device to reduce the amount of
toxic air pollution they emit. At a
minimum, the commenter stated, the
EPA must prohibit these uncontrolled
emissions and require monitoring and
reporting to assure compliance and
ensure that the emission standards
apply at all times, as required by the
Act. The commenter argued that the
EPA must also, however, consider
requiring the additional developments
that have been put into place in the
BAAQMD and also require control
devices to be used for all PRD, as some
local air districts require. In addition,
the commenter supported the EPA’s
monitoring and reporting requirements
for PRD releases and the proposed
electronic reporting requirements,
which the EPA recognized are needed to
assure compliance and assist with
future rulemakings and as that provision
requires, the EPA also must make all
information reported publicly available
online promptly and in an accessible
and understandable format.
Response: We agree that, under the
proposal, refineries would consider
installing add-on controls to comply
with the prohibition on atmospheric
releases from PRDs. In addition, they
would consider venting these control
devices to existing control devices,
including flares. However, it may not be
feasible to vent some or all of the PRDs
to existing flares if the flares are near
their hydraulic load capacity based on
the processes already connected to the
flares. Flares have negative secondary
impacts when operated at idle
conditions for the vast majority of time,
which could be the case if they were
installed solely to address PRD releases.
These secondary impacts result from
GHG, CO and NOX emissions. Some
PRDs may vent materials that are not
compatible with flare control and would
need to be vented to other controls.
To estimate the impact of the
proposed prohibition on venting PRDs
to the atmosphere, we estimated that at
least one new flare per facility would be
required to handle releases from PRDs,
based on the number of atmospheric
PRDs reported at refineries; that 60percent of the PRDs could be piped to
existing controls at minimal costs and
the other 40-percent would have to be
piped to new flares; and that, on
average, each new flare would service
40 PRDs. Based on these assumptions,
151 new flares would be needed or
approximately one new flare per
refinery. At a capital cost of $2 million
for each new flare, which would not
include long pipe runs, if needed, to
PRD that are dispersed across the plant,
we estimate that the capital cost of the
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75214
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
prohibition on venting to the
atmosphere would exceed $300 million.
Considering the fuel needed
(approximately 50,000 scf/day per flare)
and a natural gas price of $4.50 per
1,000 scf, we estimate the annual
operating cost for these new flares to be
$12 million.
PRDs are unique in that they are
designed for the purpose of releasing or
‘‘popping’’ as a safety measure to
address pressure build-up in various
systems—pipes, tanks, reactors—at a
facility. These pressure build-ups are
typically a sign of a malfunction of the
underlying equipment. While it would
be difficult to regulate most malfunction
events because they are unpredictable
and can vary widely, in the case of
PRDs, they are equipment installed
specifically to release during
malfunctions and as such, we have
information on PRDs in our 2011
Refinery ICR and through the SCAAMD
and BAAQ rules to establish standards
for them. After reviewing these
comments, we thus examined whether it
would be feasible to regulate these
devices under CAA section 112(d)(2)
and (3).
After reviewing the comments, we
agree with the commenters who suggest
that the BAAQMD rule, as well as a
similar South Coast Air Quality
Management District (SCAQMD) rule
that address PRD releases (SCAQMD
Rule 1173), provide work practice
standards that reflect the level of control
that applies to the best performers.
Consequently, we developed a work
practice standard for PRD based on a
detailed MACT analysis considering the
requirements in these rules. Our
rationale for the selected MACT
requirements is provided in section
IV.C.4 of this preamble. The work
practice standards that we are finalizing
for PRDs require refiners to establish
proactive measures for each affected
PRD to prevent direct release of HAP to
the atmosphere as a result of pressure
release events. In the event of an
atmospheric release, we are requiring
refinery owners or operators to conduct
root cause analysis to determine the
cause of a PRD release event. If the root
cause was due to operator error or
negligence, then the release would be a
deviation of the standard. For any other
release (not including those caused by
force majeure events), the owner or
operator would have to implement
corrective action. A second release due
to the same root cause for the same
equipment in a 3-year period would be
a deviation of the work practice
standard. Finally, a third release in a 3year period would be a deviation of the
work practice standard, regardless of the
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
root cause. Force majeure events would
not count in determining whether there
has been a second or third event.
With respect to defining ‘‘atmospheric
pressure relief safety valve’’ as
suggested by the commenter, we note
that the June 30, 2014, proposed
amendments in 40 CFR 63.648(j) used
the term ‘‘relief valve’’ because this was
a defined term in Refinery MACT 1.
However, the proposed amendments
included clauses such as ‘‘if the relief
valve does not consist of or include a
rupture disk.’’ Thus, we specifically
intended to apply the pressure relief
management requirements broadly to
‘‘pressure relief devices’’ and not just
‘‘valves.’’ To clarify this, we have
revised the regulatory language to use
the term ‘‘pressure relief device’’ rather
than ‘‘relief valve’’ to clearly include
rupture disks or similar types of
equipment that may be used for
pressure relief.
4. What is the rationale for our final
approach and final decisions for the
revisions pursuant to CAA section
112(d)(2) and (3)?
We revised the MACT floor
determination for DCU sources. CAA
section 112(d)(3)(A) requires the MACT
floor for existing sources to exclude
‘‘. . . those sources that have, within 18
months before the emission standard is
proposed or within 30 months before
such standard is promulgated,
whichever is later, first achieved a level
of emission rate or emission reduction
which complies, or would comply if the
source is not subject to such standard,
with the lowest achievable emission rate
(as defined by section 171) applicable to
the source category and prevailing at the
time, in the category or subcategory for
categories and subcategories with 30 or
more sources.’’ Because we have
determined that a 2 psig emissions
limitation is equivalent with a LAER
emission limit for DCU, we revised the
MACT floor analysis in order to exclude
sources that first met the 2 psig limit on
or after December 30, 2012. For existing
sources, based on the revised MACT
analysis, we concluded that the MACT
floor is still 2 psig. However, because
the information on which we relied was
submitted in response to the 2011
Petroleum Refinery ICR which
requested ‘‘typical’’ venting pressures
and because providing an allowance to
average across venting periods does not
reduce the emissions reductions
achieved, we are providing a 60-event
averaging period for existing sources in
response to public comments received.
For new DCU sources, our revised
analysis identified one DCU subject to
permit emission limitations of 2.0 psig
PO 00000
Frm 00038
Fmt 4701
Sfmt 4700
pressure limit prior to venting on a per
event basis. Under CAA section
112(d)(3), the MACT standard for new
sources cannot be less stringent than the
emission control achieved in practice by
the best-controlled similar source. Thus,
we are finalizing a limit of 2.0 for new
DCU sources. We note that as 2.0 psig
limit is more stringent than a 2 psig
limit because of the rounding
convention of rounding to the number
of significant digits for which the
standard is expressed. For example, a
2.4 psig venting pressure is compliant
with a 2 psig limit, while it is not
compliant with a 2.0 psig limit.
We evaluated the costs of requiring
existing sources to meet a 2.0 psig limit
as a beyond-the-MACT-floor option. We
determined the incremental cost of
going from a 2 psig limit with an
allowance to average over 60 events to
a 2.0 psig limit on a per event basis was
approximately $70,000 per ton of HAP
reduced considering VOC credits. Based
on this high incremental costeffectiveness, we concluded that the
MACT floor requirement for existing
DCU sources was MACT. As discussed
in detail in the proposal, we do not
consider it technically feasible to meet
a 1 psig pressure limit (effectively a 1.4
psig limit) on a not-to-be-exceeded
basis. Thus, we rejected this beyond the
floor control option for both existing
and new DCU sources. See the
memorandum titled ‘‘Reanalysis of
MACT for Delayed Coking Unit
Decoking Operations’’ in Docket ID No.
EPA–HQ–OAR–2010–0682 for
additional details regarding our reanalysis of MACT for DCU decoking
operations.
In response to comments received on
the prohibition of draining prior to
achieving the proposed pressure limit
(see Section 7.2.1 in the ‘‘National
Emission Standards for Hazardous Air
Pollutants from Petroleum Refineries—
Background Information for Final
Amendments: Summary of Public
Comments and Responses’’ in Docket ID
No. EPA–HQ–OAR–2010–0682), we are
providing specific provisions to allow
for draining under special conditions.
The specific provision and our rationale
for providing them are provided below.
First, we learned that certain DCU are
designed to completely fill the drum
with water and allow the water to
overflow in the overhead line and drain
to a receiving tank in order to more
effectively cool the coke bed. Owners or
operators of this DCU design were
concerned that the water overflow may
be considered a drain and also stated
that overhead temperature rather than
pressure would be a better indicator of
effective bed cooling. In reviewing this
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
type of DCU design, we find that this
design has some unique advantages to
traditional DCU to effect better cooling
of the coke drum, and therefore we do
not want to preclude its use. Based on
saturated steam properties, we
determined that an overhead
temperature of 220 °F would achieve
equivalent or greater emissions
reductions than a 2 psig pressure
limitation and an overhead temperature
of 218 °F would achieve equivalent or
greater emissions reductions than a 2.0
psig pressure limitation. Therefore, we
are including these temperature limits
as alternatives to the 2 or 2.0 psig
pressure limitations for existing and
new DCU affected sources, respectively.
With respect to the overflow ‘‘drain,’’
we remain concerned with emissions
from draining superheated water.
However, if submerged fill is used in the
atmospheric tank receiving the overflow
water, the superheated water will be
cooled by the water within the tank and
emissions that occur during the
conventional draining of water (from the
flashing of superheated water into
steam) can be prevented. Therefore, we
are allowing the use of water overflow
provided the overflow ‘‘drain’’ water is
hard-piped to the receiving tank via a
submerged fill pipe (pipe below the
existing liquid level) whenever the
overflow water exceeds 220 °F.
Second, we received comments that,
for conventional DCU (those not
designed to allow water overflow), there
is a limit to the maximum water level
in the drum, which limits to some
extent how much cooling water can be
added to the coke drum. In rare cases,
the coke drum does not cool sufficiently
using the typical cooling steps. In this
case, the common industry practice is to
partially drain the coke drum and refill
it with additional cooling water. This
‘‘double-quench’’ process is needed for
safety reasons to sufficiently cool the
coke drum contents prior to the
decoking operations. Therefore,
commenters requested provisions to
allow double-quenching of the coke
drum. We recognize the safety issues
associated with coke blow-out during
coke cutting if there is a portion of the
coke bed that is not sufficiently cooled
and we agree that double-quenching is
an effective means to cool the coke
drum in those rare instances that the
typical cooling cycle does not
sufficiently cool the coke drum
contents, so we considered granting the
commenters’ request. As noted
previously, the primary concern with
early draining of the coke drum is the
emissions that are expected to occur as
a result of draining superheated water.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
We recognize, however, that the water
temperature near the bottom of the coke
drum is typically much lower than at
the top of the coke drum. If the
temperature of the water drained from
the bottom of the coke drum remains
below 210 °F, this would minimize
steam flashing and associated HAP
emissions since the water drained
would not be superheated. We conclude
that the use of double quenching is
appropriate for cases when the coke
drum is not sufficiently cooled using the
normal cooling procedures provided the
temperature of the water drained
remains below 210 °F, and it is
consistent with the practices of the best
performing sources. Consequently, we
are finalizing provisions to allow the
use of double-quenching for DCU
provided the temperature of the water
drained remains below 210 °F.
For the CRU, we are finalizing the
proposed revisions to require CRU that
employ active purging to meet the
MACT emissions limitations in Tables
15 and 16 in subpart UUU at all times
regardless of vessel pressure. We
received limited comments regarding
our proposal; these comments generally
concerned the costs associated with the
proposed emissions limitations. As
discussed in our proposal, and based on
data submitted in response to the ICR,
emissions using active purging are
much higher than those not using active
purging. In the original rule, we based
the MACT floor on the best performing
facilities that used sequential
pressurizations and depressurizations
rather than active purging. Thus, in the
proposal, we concluded that allowing
owners or operators to actively purge
while at low pressures was inconsistent
with the MACT floor emissions
limitations achieved by the best
performing 12-percent of sources when
the MACT floor was originally
established. As we are simply requiring
these facilities to meet the same
emission levels determined to be
MACT, we do not consider costs of
potential additional controls to be a
viable rationale to allow these units to
emit several times more HAP than the
units upon which the MACT
requirements were based and the
emissions levels achieved in practice by
the vast majority of other CRU sources.
For flares, we are finalizing proposed
revisions to include detailed flare
monitoring and operating requirements.
We are including the flaring provisions
for refineries in the Refinery MACT
rules and removing the cross-references
to the flaring requirements in the
General Provisions. The final regulatory
requirements differ from the proposed
requirements in several respects. First,
PO 00000
Frm 00039
Fmt 4701
Sfmt 4700
75215
we are not finalizing the ban on
halogenated vent streams because we
did not include sufficient justification
or include cost estimates for this
proposed provision and we did not
include any monitoring requirements to
ensure compliance with this ban on
halogenated vent streams.
We are finalizing the proposed no
visible emissions limit and the flare tip
velocity limit but they will apply only
when the flare vent gas flow rate is
below the smokeless capacity of the
flare. We received a number of
comments stating that the no visible
emissions limit and the flare tip velocity
limit cannot be met during large
malfunctions and emergency shutdown
events. In response to comments, we are
finalizing work practice standards for
emergency flaring events using the
proposed no visible emission limit and
flare tip velocity limit as thresholds in
the final rule to trigger root cause
analysis when the flare vent gas flow
rate is above the smokeless capacity of
the flare. The final work practice
standard includes requirements to
develop a flare management plan, to
implement prevention measures, and to
perform root cause analysis and
implement corrective action following
each flaring event that exceeds the
smokeless capacity of the flare. There is
also a limit on the number of these
flaring events that a given flare may
have in the 3-year period. We are
establishing these provisions because
we now recognize that flares have two
different design capacities: A smokeless
design capacity and a hydraulic load
capacity. We determined that the
proposed visible emissions limit and the
flare tip velocity limit for very large
flow events are not the MACT floor for
such events. The final work practice
standards for flaring events are based on
the best performing facilities and will
result in emission reductions in a
technically feasible manner without any
negative secondary impacts.
We consider it appropriate to
establish a work practice standard for
flares as provided in CAA section
112(h). While it is possible to monitor
gaseous streams going into the flare (as
we have required for the flare operating
requirements) it is not possible to design
and construct a conveyance to capture
the emissions from a flare. While
knowledge of the composition and flow
of gases entering the flare provides a
reasonable basis for establishing
operating requirements for normal
operations, we have no data on flare
performance under conditions in the
hydraulic load range. While smoke in
the flare exhaust is an indication of
incomplete combustion, it is uncertain
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75216
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
how much deterioration of HAP
destruction efficiency occurs during a
smoking event. We also consider that
the application of a measurement
methodology for flare exhaust is not
practicable due to technological and
economic limitations. Passive FTIR has
been used to determine combustion
efficiency in flare exhaust, but these are
essentially manual tests, and the
measurement accuracy is dependent on
how well the monitor is aligned with
the flare exhaust plume. Changes in
wind direction require manual
movement of the monitoring system. It
is also unclear if these systems can
accurately measure combustion
efficiency during high smoking events.
These systems also require very
specialized expertise, and we consider
that it is both technologically and
economically infeasible to measure flare
exhaust emissions, particularly during
high load events. Consequently, for
emergency flare releases, we conclude
that it is appropriate to establish a work
practice standard as provided in CAA
section 112(h).
We also received comments that the
daily visible emissions observations
were burdensome and unnecessary and
some commenters suggested that
facilities be allowed to use video
surveillance cameras. We concluded
that video surveillance cameras would
be at least as effective as the proposed
daily 5-minute visible emissions
observations using Method 22. We are
finalizing the proposed visible
emissions monitoring requirements
Method 22 and the alternative of using
video surveillance cameras.
We are simplifying the combustion
zone gas property operating limits in
response to public comments received.
Specifically, we are finalizing
requirements that all flares meet a
minimum operating limit of 270 BTU/
scf NHVcz on a 15-minute average, and
we are providing that refiners use a
corrected heat content of 1,212 BTU/scf
for hydrogen to demonstrate compliance
with this operating limit. We
determined that a corrected heat content
of 1212 BTU/scf for hydrogen provided
a better indication of flare performance
than without the correction. We also
determined that the other combustion
zone parameters, which were primarily
proposed to provide suitable methods
for flares that had high hydrogen
concentrations, were no longer
necessary when a 1,212 Btu/scf net
heating value is used for hydrogen.
Therefore, we are not finalizing the
alternative combustion zone operating
limits based on lower flammability limit
or combustibles concentration. We are
also not finalizing separate combustion
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
zone operating limits for gases meeting
the proposed hydrogen-olefin
interaction criteria. In our revised
analysis of the data, we analyzed all of
the data together and determined the
270 Btu/scf NHVcz operating limit
provided in the final rule would
adequately ensure that flares achieve the
desired 98-percent control efficiency
regardless of the composition of gas sent
to the flare.
For air-assisted flares, we are
finalizing the additional ‘‘dilution
parameter’’ operating limit only for the
net heating value dilution parameter,
NHVdil. Similar to the requirements we
are finalizing for the combustion zone
parameters, we are finalizing
requirements that flares meet a
minimum operating limit of 22 BTU/ft2
NHVdil on a 15-minute average, and we
are providing that refiners use a
corrected heat content of 1,212 BTU/scf
for hydrogen to demonstrate compliance
with this operating limit. For the
reasons explained above, we are not
finalizing the proposed alternative
dilution parameter operating limits
based on lower flammability limit or
combustibles concentration, and we are
not finalizing separate dilution
parameter operating limits for gases
meeting the proposed hydrogen-olefin
interaction criteria.
For flares in dedicated service, we are
establishing an alternative to continuous
or on-going grab sample requirements
for determining waste gas net heating
content to reduce the burden of
sampling for flare waste gases that have
consistent compositions. Flares in
dedicated service can use initial
sampling period and process knowledge
to determine a fixed net heating value
of the flare vent gas to be used in the
calculations of NHVcz and, if applicable,
NHVdil.
We are revising the definition of MPV
to remove the exemption for in situ
sampling systems for the reasons
provided in the proposed rule.
We received comments
recommending that a work practice
standard be adopted for PRD rather than
the proposed prohibition of atmospheric
PRD releases. Commenters stated that
the prohibition was infeasible due to the
proposed immediate timing of the
requirement and impractical due to cost
considerations. After reviewing these
comments as well as the BAAQMD rule
(Regulation 8, Rule 8–28–304) and the
SCAQMD rule (Rule 1173), we have
determined that the work practice
standards in these rules reflect the level
of control that applies to the best
performers. Therefore, we proceeded to
evaluate appropriate MACT
PO 00000
Frm 00040
Fmt 4701
Sfmt 4700
requirements based on the provisions in
these rules.
The BAAQMD rule requires sources
to implement a minimum of three
prevention measures to limit the
possibility of a release. The BAAQMD
uses a ‘‘release event’’ threshold of 10
lbs/day of organic or inorganic
pollutants; the SCAQMD rule effectively
uses a release event threshold of 500 lbs
VOC/day. When a release event occurs,
both rules require that the refiner
perform a root cause analysis and take
corrective action (including additional
prevention measures). In addition, both
rules require piping the PRD to a flare
if there are more than two release events
(releases above a certain release size
threshold) in a 5-year period. Both rules
include a number of exemptions for
certain types of PRD that are not
expected to release significant amounts
of pollutants to the air or that are not
feasible to control because of pressure
considerations. These include PRD
associated with storage tanks, vacuum
systems and equipment in heavy liquid
service as well as liquid thermal relief
valves that are vented to process drains.
There are five refineries subject to the
BAAQMD rule and seven refineries
subject to the SCAQMD rule, accounting
for 8-percent of refineries nationwide
and representing the industry’s best
performers. We consider the BAAQMD
rule to be the more stringent of the two
because this rule requires sources to
implement a minimum of three
prevention measures to limit the
possibility of a release (the SCAQMD
rule has no similar requirement) and
uses a lower mass threshold for what is
considered a ‘‘release event’’ (10 lbs/day
of organic or inorganic pollutants versus
the 500 lbs VOC release threshold in the
SCAQMD rule). Therefore, the
BAAQMD rule is considered to be the
MACT floor requirement for PRDs
associated with new affected sources
and the SCAQMD rule is considered to
be the MACT floor for PRDs associated
with existing affected sources.
In general, an open PRD is essentially
the same as a miscellaneous process
vent that is vented directly to the
atmosphere. Consistent with our
treatment of miscellaneous process
vents and consistent with the two
California rules, we believe that it is
appropriate to exclude certain types of
PRD that have very low potential to emit
based on their type of service, size and/
or pressure. For example, PRD that have
a potential to emit less than 72 pounds
per day of VOC, considering the size of
the valve opening, design release
pressure, and equipment contents,
would be considered in a similar
manner as Group 2 miscellaneous
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
process vents and would not require
additional control. The two California
rule requirements do not apply to PRD
on storage tanks and vacuum systems.
Most of these PRD have a design release
pressure of 2.5 psig and thus have a very
limited potential to emit. It is
technically infeasible to pipe these
sources to a flare (or other similar
control system) because the back
pressure in the flare header system
generally exceeds 2.5 psig. We note that
some storage tanks can operate at
elevated pressure (i.e., pressure tanks).
Therefore, rather than follow exactly the
requirements in the California rules, we
determined it more practical to exclude
PRD with design release pressure of less
than 2.5 psig.
Any release from a PRD in heavy
liquid service would have a visual
indication of a leak and any repairs to
the valve would have to be further
inspected and, if necessary, repaired
under the existing equipment leak
provisions. Therefore, consistent with
the BAAQMD rule, we are exempting
PRD in heavy liquid service from the
work practice standards we are
establishing in this final rule.
Both the BAAQMD and SCAQMD
rules exempt thermal expansion valves
that are ‘‘vented to process drains or
back to the pipeline.’’ We are unclear
what is meant by ‘‘vented to process
drains’’; however, if a liquid is released
from a PRD via hard-piping to a drain
system that meets the control
requirements specified in Refinery
MACT 1, we consider that these PRD are
controlled and they would not be
subject to the work practice standard
established in this final rule. Similarly,
all PRD in light liquid service that are
hard-piped to a controlled drain system
(or back to the process or pipeline) are
otherwise subject to a MACT
requirement and would not be subject to
the work practice standard.
In considering thermal relief valves
not vented to process drains or back to
the pipeline, we expect that releases
from these thermal relief valves will be
small and generally under the release
event thresholds specified in the
California rules. Therefore, the work
practice standards do not apply to PRD
that are designed solely to release due
to liquid thermal expansion.
The primary goal of the PRD work
practice standard is to reduce the size
and frequency of releases. The
SCAQMD rule is targeted towards fairly
large releases (compared to the direct
PRD releases reported in response to the
Refinery ICR), so it will reduce the
frequency of large releases, but it does
little to reduce the frequency of smaller
releases. To more effectively reduce the
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
size and frequency of all releases, we
consider it important to require the
implementation of prevention measures
(as required in the BAAQMD rule) and
require root cause analysis and
corrective action for PRD releases from
all PRD subject to the work practice
standard. While we recognize that if a
PRD opens for a short period of time,
the release might be below the release
thresholds in the SCAQMD rules, we
believe the release may be indicative of
an important issue or design flaw.
Because the potential for large
emissions exist from the PRD subject to
the work practice standard, we think it
is reasonable to require a root cause
analysis be conducted and appropriate
corrective action implemented to
potentially identify this issue and
prevent a second release which, if the
issue remains uncorrected, could be
significant.
Requiring that prevention measures
be implemented on all PRD subject to
the work practice standard and not
establishing a release threshold for
release events is a variation from the
SCAQMD rule. However, we also
considered the allowable release
frequency. We believe that our adoption
of this approach is balanced by our not
adopting the SCAQMD provisions
requiring that PRD be vented to a flare
or other control system or that refiners
pay a fee if there are multiple releases
of a certain size within a specified
timeframe.12 In place of this system, we
are limiting the number of events from
each PRD that can occur in a 3 year time
period (2, if root causes are different),
and in place of a fine, or routing to
control, stating that the 3rd release in 3
years for any root cause is a deviation
of the standard.
Because we are not including a size
threshold for release events as in the
SCAQMD rule, it is natural to assume
release events would occur more
frequently than release events subject to
the SCAQMD rules. Also, based on our
Monte Carlo analysis of random rare
events, we note that it is quite likely to
have two or three events in a 5-year
period when a long time horizon (e.g.,
20 years) is considered. Therefore,
considering our analysis of emergency
12 The SCAQMD rule requires PRD to be vented
to a flare or other control device if there is a single
release in excess of 2,000 pounds of VOC in a 24hour period or three releases in excess of 500
pounds of VOC in a 5-year period or, alternatively,
pay a $350,000 fee. Thus, the SCAQMD rule would
allow, for example, two releases of over 500 pounds
of VOC each within a 5-year period without any
penalty provided a third event did not occur. If a
third event did occur, the refinery owner or
operator would then have to vent the PRD to a flare
or other control system or pay a fee ($350,000) for
the third release over 500 pounds of VOC.
PO 00000
Frm 00041
Fmt 4701
Sfmt 4700
75217
flaring events and the lack of a 500 lb/
day release threshold, we considered it
reasonable to use a 3-year period rather
than a 5-year period as the basis of a
deviation of the work practice standard.
The SCAQMD work practice
standards do not apply to releases that
are demonstrated to ‘‘result from natural
disasters, acts of war or terrorism, or
external power curtailment beyond the
refinery’s control, excluding power
curtailment due to an interruptible
service agreement.’’ These types of
events, which we are referring to as
‘‘force majeure’’ events, are beyond the
control of the refinery owner or
operator. We are providing that these
events should not be included in the
event count, but that they would be
subject to the root cause analysis in
order to confirm whether the release
was caused by a force majeure event.
Consistent with the requirements in
the SCAQMD rule, we are requiring
refinery owners or operators to conduct
a root cause analysis for a PRD release
event. If the root cause was due to
operator error or negligence, then the
release would be a deviation of the
standard. For any other release (not
including those caused by force majeure
events), the owner or operator would
have to implement corrective action. We
consider that a second release due to the
same root cause for the same equipment
in a 3-year period would be a deviation
of the work practice standard. This
provision will help ensure that root
cause/corrective action are conducted
effectively. Finally, a third release in a
3-year period (not including those
caused by force majeure events) would
be a deviation of the work practice
standard, regardless of the root cause.
While we are using a 3-year interval
rather than the 5-year interval provided
in the SCAQMD, we consider that the
requirements as included in this final
rule (i.e., the inclusion of prevention
measure requirements and no
thresholds for release events) will
achieve equivalent if not greater
emissions reductions than the SCAQMD
rule. We also consider that, given the
prevention measure requirements and a
3-year period, there is less likelihood of
unusual random events that happen
over a short period of time that may
cause refinery owners or operators to
feel compelled to vent the PRD to a flare
to eliminate concerns regarding
potential non-compliance. Thus, we
project that the requirements that we
have included in the final rule will
achieve emissions reductions
commensurate to or exceeding the
requirements in the SCAQMD rule (that
serves as the MACT floor for existing
sources) but will achieve those
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75218
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
reductions in a more cost-effective
manner.
We also considered requiring all PRD
to be vented through a closed vent
system to a control device as an
alternative beyond-the-MACT floor
requirement. While this requirement
would provide additional emission
reductions beyond those we are
establishing as the MACT floor, these
reduction come at significant costs.
Capital costs for requiring control of all
atmospheric PRD is estimated to be
approximately $300 million compared
to $11 million for the requirements
described above. The total annualized
cost for requiring control of all
atmospheric PRD is estimated to be
approximately $41 million/year
compared to $3.3 million/year for the
requirements described above. We
estimate that the incremental costeffectiveness of requiring control of all
atmospheric PRD compared to the
requirements described above exceeds
$1 million per ton of HAP reduced.
Consequently, we conclude that this is
not a cost-effective option for existing
sources.
The final requirements that we have
developed for PRD achieve equal or
greater emission reductions than those
achieved by the SCAQMD rule (MACT
floor). To the extent those requirements
are more stringent that the SCAQMD,
they are cost-effective. We could not
identify an alternative requirement that
provided further emission reductions in
a cost-effective manner. Thus, we
conclude that the work practice
standards described above represent
MACT for existing sources.
The BAAQMD rule, which represents
the requirements applicable to the best
performing sources, is the basis for new
source MACT for PRD. Based on the
specific provisions for PRD in the
BAAQMD rule, we conclude that the
MACT floor requirement is to have all
PRD in HAP service associated with a
new affected source vented through a
closed vent system to a control device.
As with existing sources, the PRD WPS
would also contain the same exclusions
(e.g., heavy liquid service PRDs, thermal
expansion valves, liquid PRDs that are
hard-piped to controlled drains, PRD
with release pressures of less than 2.5
psig, PRD with emission potential of
less than 72 lbs/day, and PRD on mobile
equipment). These provisions are
similar to the applicability provisions of
the BAAQMD rule. Thus, we retain the
same applicability of the work practice
standard for PRDs on new or existing
equipment, but all affected PRD on a
new source would be required to be
controlled. This is essentially equivalent
to the proposed requirement of no
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
atmospheric releases. We could not
identify a control option more stringent
than the BAAQMD rule as applied to
new sources. Therefore, we conclude
that venting all PRD in HAP service
through a closed vent system to a flare
or similar control system is MACT for
PRD associated with new affected
sources.
We consider it appropriate to
establish a work practice standard for
PRD as provided in CAA section 112(h).
While it may be possible to design and
construct a conveyance for PRD
releases, we consider that the
application of a measurement
methodology for PRDs is not practicable
due to technological and economic
limitations. First, it is not practicable to
use a measurement methodology for
PRD releases. The venting time can be
very short and may vary widely in
composition and flow rate. The oftenshort duration of an event makes it
infeasible to collect a grab sample of the
gases when a release occurs, and a
single grab sample would not account
for potential variation in vent gas
composition. It would be economically
prohibitive to construct an appropriate
conveyance and install and operate
continuous monitoring systems for each
individual PRD in order to attempt to
quantitatively measure a release event
that may occur only a few times in a 3year period. Additionally, we have not
identified an available, technically
feasible continuous emission
monitoring systems that can determine
a mass VOC or HAP release quantity
accurately given the flow, composition
and composition variability of potential
PRD releases from refineries.
Consequently, we conclude that it is
appropriate to establish a work practice
standard for PRD releases as provided in
CAA section 112(h).
D. NESHAP Amendments Addressing
Emissions During Periods of SSM
1. What amendments did we propose to
address emissions during periods of
SSM?
We proposed to eliminate the SSM
exemption in 40 CFR part 63, subparts
CC and UUU. Consistent with Sierra
Club v. EPA, we proposed standards in
these rules that apply at all times. We
also proposed several revisions to Table
6 of subpart CC of 40 CFR part 63 and
to Table 44 to subpart UUU of 40 CFR
part 63 (the General Provisions
Applicability tables for each subpart),
including eliminating the incorporation
of the General Provisions’ requirement
that the source develop an SSM plan,
and eliminating and revising certain
recordkeeping and reporting
PO 00000
Frm 00042
Fmt 4701
Sfmt 4700
requirements related to the SSM
exemption.
For Refinery MACT 1, we proposed
that the use of a bypass at any time to
divert a Group 1 miscellaneous process
vent to the atmosphere is a deviation of
the emission standard, and specified
that refiners install, maintain and
operate a continuous parameter
monitoring system (CPMS) for flow that
is capable of recording the volume of
gas that bypasses the APCD.
We also proposed to revise the
definition of MPV to remove the
exclusion for ‘‘Episodic or non-routine
releases such as those associated with
startup, shutdown, malfunction,
maintenance, depressuring and catalyst
transfer operations.’’ We also proposed
that the control requirements for Group
1 MPV apply at all times, including
startup and shutdowns.
For Refinery MACT 2, we proposed
alternate standards for three emission
sources for periods of startup or
shutdown. We proposed PM standards
for startup of FCCU controlled with an
ESP under Refinery MACT 2 because of
safety concerns associated with
operating an ESP during an FCCU
startup. For FCCU controlled by an ESP,
we proposed a 30-percent opacity limit
(on a 6-minute rolling average basis)
during the period that torch oil is used
during FCCU startup. For startup of
FCCU without a post-combustion device
under Refinery MACT 2, we proposed a
CO standard based on an excess oxygen
concentration of 1 volume percent (dry
basis) based on a 1-hour average. For
periods of SRU shutdown, we proposed
to allow diverting the SRU purge gases
to a flare meeting the design and
operating requirements in 40 CFR
63.670 (or, for a limited transitional
time period, 40 CFR 63.11) or to a
thermal oxidizer operated at a minimum
temperature of 1,200 °F and a minimum
outlet oxygen concentration of 2 volume
percent (dry basis). For other emission
sources in Refinery MACT 2, we
proposed that the requirements that
apply during normal operations should
apply during startup and shutdown.
2. How did the SSM provisions change
since proposal?
a. Refinery MACT 1
We proposed that when process
equipment is opened to the atmosphere
(e.g., for maintenance), the existing MPV
emissions limits apply. In this final rule,
we are instead finalizing startup and
shutdown provisions that apply to these
venting events. These startup and
shutdown provisions are work practice
standards that allow refinery owners or
operators to open process equipment
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
during startup and shutdown provided
that the equipment is drained and
purged to a closed system until the
hydrocarbon content is less than or
equal to 10-percent of the LEL. For those
situations where 10-percent LEL cannot
be demonstrated (no direct
measurement location), the equipment
may be opened and vented to the
atmosphere if the pressure is less than
or equal to 5 psig. Active purging of the
equipment is only allowed after the 10percent LEL level is achieved, regardless
of the pressure of the equipment/vessel.
We are establishing a separate
requirement for very small process
equipment, defined as equipment where
it is physically impossible to release
more than 72 lbs VOC per equipment
opening based on the size and contents
of the equipment. This definition is
consistent with the Group 1
applicability cutoff for control of
miscellaneous process vents. We also
developed requirements specific to
catalyst changeout activities where
pyrophoric catalyst (e.g., hydrotreater or
hydrocracker catalysts) must be purged
using recovered hydrogen. These
provisions include: Documenting the
procedures for equipment openings and
procedures for verifying that events
meet the specific conditions above using
site procedures used to de-inventory
equipment for safety purposes (i.e., hot
work or vessel entry procedures) and
documenting any deviations from the
work practice standard requirements.
b. Refinery MACT 2
tkelley on DSK3SPTVN1PROD with RULES2
We are expanding the proposed 1percent minimum oxygen operating
limit alternative for organic HAP to
apply for all FCCU startup and
shutdown events (rather than only
partial burn FCCU with CO boilers
during startup). We are replacing the
proposed opacity limit alternative to the
metal HAP standard with a minimum
cyclone face velocity limit and we are
extending that alternative limit to all
FCCU (regardless of control device) for
both startup and shutdown in this final
rule.
We are extending the proposed
alternative for SRU to monitor
incinerator temperature and excess
oxygen limits during SRU shutdowns to
also apply during periods of startup.
3. What key comments did we receive
on the SSM revisions and what are our
responses?
a. Refinery MACT 1
Comment: Many commenters stated
that the proposed extension of the MPV
definition to episodic maintenance
startup and shutdown vents and
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
elimination of the SSM exception for
storage tanks would create hundreds or
thousands of new vents per refinery per
year and generate massive on-going
burdens. The commenters argued that
the EPA has not included in the record
any analysis of the potential
environmental benefits, costs or
operational and compliance feasibility
and impacts associated with this
requirement and that many of these
requirements will result in delayed and
extended equipment and process
outages. One commenter asserted that
the EPA has articulated no justification
for applying emission standards to these
events, nor any analysis consistent with
CAA section 112 for a determination
that MACT standards are appropriately
applied to these emission events under
the criteria in CAA section 112(d).
Many commenters stated that every
time a vessel is opened for inspection or
maintenance each vent point will have
to be evaluated as a potential MPV or
storage tank vent. If a particular vent
point (e.g., bleeder) used for
maintenance, startup or shutdown
handles material that is initially greater
than 20 ppm HAP, then it is a MPV. If
there is a potential to emit greater than
or equal 72 lbs/day of VOC, then it is
a Group 1 MPV and must be controlled.
If there is a potential of less than 72 lb/
day VOC release, then it is a Group 2
MPV and subject to recordkeeping
requirements. Commenters stated that in
a refinery there would be tens or more
such activities per day associated with
normal maintenance and inspection;
during turnarounds, there could be
hundreds of such MPVs. Commenters
added that these MPVs may then need
to be individually accounted for and
permitted creating an unnecessary
permitting and recordkeeping burden
for these periodic emissions.
Commenters recommended a general
set of work practice requirements for
maintenance, startup and shutdown of
vents, based on state requirements, that
do not impose the permitting, notice
and evaluation requirements associated
with identifying these vents
individually. Commenters explained
that states have dealt with these
episodic vents by establishing them as
a special class of process vent with
limited recordkeeping requirements and
subject to a work practice standard,
rather than the normal MPV
requirements. A key element of these
work practices is clear identification of
the criteria for releasing these vents to
the atmosphere and for routing these
vents to control after hydrocarbon is
reintroduced, which the commenters
asserted the current rule does not
provide. Commenters proposed that a
PO 00000
Frm 00043
Fmt 4701
Sfmt 4700
75219
work practice standard could include
removing process liquids to the extent
practical and depressuring smaller
volume equipment until a pressure of
<5 psig is achieved and/or purging and
depressuring to a control device until
the vent has a hydrocarbon
concentration of less than 10-percent of
the LEL. The commenters suggested that
these standards should provide clear
easily monitored criteria for when this
equipment can be vented to the
atmosphere, and should not impose the
permitting, notice and evaluation
requirements associated with
identifying these vents as individual
MPVs. One commenter provided draft
regulatory language for a work practice
requirement.
Response: We proposed to eliminate
the episodic and non-routine emission
exclusion in order to ensure that the
MACT includes emission limits that
apply at all times consistent with the
holding in Sierra Club. At the time of
the proposal, we expected that
essentially all SSM event emissions
would be routed to flares that are
subject to the MACT standards and,
thus, would serve to control these
emissions. However, we recognize that
maintenance activities that require
equipment openings are a separate class
of startup/shutdown emissions because
there must be a point in time when the
vessel can be opened and any emissions
vented to the atmosphere. We
acknowledge that it would require a
significant effort to identify and
characterize each of these potential
release points for permitting purposes.
In considering these comments and
whether we should establish a separate
limit that would apply to these
equipment openings, we reviewed state
permit requirements and the practices
employed by the best performing
sources. We found that some state or
local agencies required depressuring to
5 psig prior to atmospheric releases
while others required the gases to have
organic concentrations at or below 10percent of LEL prior to atmospheric
venting. In the final rule, we are
establishing a requirement that prior to
opening process equipment to the
atmosphere, the equipment must first be
drained and purged to a closed system
so that the hydrocarbon content is less
than or equal to 10-percent of the LEL.
For those situations where 10-percent
LEL cannot be demonstrated, the
equipment may be opened and vented
to the atmosphere if the pressure is less
than or equal to 5 psig, provided there
is no active purging of the equipment to
the atmosphere until the LEL criterion
is met. For equipment where it is not
technically possible to depressurize to a
E:\FR\FM\01DER2.SGM
01DER2
75220
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
control system, we allow venting to the
atmosphere where there is no more than
72 lbs VOC per day potential, consistent
with our Group 1 applicability cutoff for
control of process vents. For catalyst
changeout activities where hydrotreater
pyrophoric catalyst must be purged we
have provided limited allowances for
direct venting. Provisions to
demonstrate compliance with this work
practice include documenting the
procedures for equipment openings and
procedures for verifying that events
meet the specific conditions above using
site procedures used to de-inventory
equipment for safety purposes (i.e., hot
work or vessel entry procedures).
b. Refinery MACT 2
Comment: Several commenters noted
that there was a proposed specific
alternative metal HAP/PM standard for
startup of an FCCU controlled with an
ESP, but took issue with the fact that no
alternative PM limits were proposed for
startup of FCCU equipped with other
types of PM controls, or for any FCCU
during periods of shutdown or hot
standby. Regarding the proposed
alternative for startup, which would
provide an alternative in the form of an
opacity limit when torch oil is in use,
commenters stated that there are serious
process safety concerns which prevent
most FCCU ESPs from being operated
when torch oil is in the regenerator, that
is, during periods of startup, shutdown
and hot standby. To avoid the
possibility of a fire and explosion, the
commenters claimed ESPs are usually
de-energized and bypassed during these
periods and, consequently, these FCCUs
are generally unable to meet the
proposed 30-percent opacity limit.
Several commenters stated that the
EPA’s limits on FCCU opacity during
SSM are unreasonable and ignore the
technical requirements for transitional
operations of those units. The
commenters indicated that they have
ESPs located downstream of the CO
boiler and claimed that for safety
reasons the CO boiler cannot operate
during startup, shutdown or hot
standby. Further, a commenter
indicated that the ESP cannot operate if
the CO boiler is not operating and thus
both the CO boiler and the ESP must be
bypassed during startup, shutdown, and
hot standby operations.
Another commenter stated that the
EPA offers no data to support the
achievability of this requirement in
practice and discusses information for
26 startup/shutdown events that found
that none complied with a 30-percent
opacity requirement. Several
commenters also noted that experience
has shown that the 30-percent opacity
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
limit is unachievable during these
periods for FCCUs controlled with
tertiary cyclones, when regenerator gas
flow is below cyclone minimum design
flow.
Several commenters suggested that
the EPA establish a standard based on
the operation of FCCU catalyst
regenerators’ internal cyclones that
function to retain the catalyst in the
regenerators and thereby minimize
catalyst and metal HAP emissions from
the regenerators. Additional control to
meet the Refinery MACT 2 emission
limit of not more than 1.0 lb PM/1,000
lbs coke burn-off is provided by a bag
house, wet gas scrubber (WGS), ESP or
tertiary (external) cyclone. The
efficiency of a cyclone is a function of
the inlet gas velocity. Assuring adequate
velocity to the internal cyclones ensures
that the catalyst sent to these additional
controls is minimized and ensures that
they are operating as effectively as
possible. Similarly, even if the FCCU
cannot meet the normal opacity limits
during startup, shutdown or hot standby
(e.g. due to the ESP being off-line for
safety reasons or the tertiary cyclones or
WGS operating at non-routine
conditions), assuring adequate velocity
to the internal regenerator cyclones will
control and minimize particulate
emissions. Several commenters stated
support for another commenter’s
position that all FCCUs should be
allowed the option of complying with a
20 feet/second minimum inlet velocity
to the primary regenerator cyclones
during periods of startup and shutdown,
including hot standby, and these
commenters provided additional
technical explanations in their
comments.
On the other hand, some commenters
seemed to support the proposed opacity
limits, but suggested minor revisions.
One commenter noted that the
SCAQMD has granted Valero’s request
for variances from visible emission
standards during startup of the FCCU of
up to 65-percent opacity for up to five
minutes, in aggregate, during any 1-hour
period, and 30-percent as an hourly
average for the remaining period, during
startup events. The application of this
variance reflects the unavailability and/
or ineffectiveness of the ESP during the
startup condition. Another commenter
recommended that either the opacity
standard should be raised or the time
period for averaging should be extended
so FCCUs can be operated safely during
SSM events and still remain in
compliance.
Response: We have reviewed the data
submitted by the commenters to support
their assertion that the 30-percent
opacity limit (determined on a 6-minute
PO 00000
Frm 00044
Fmt 4701
Sfmt 4700
average basis) is not achievable during
startup and shutdown events. While the
data are limited, and it is unclear if the
data provided are indicative of the
performance achieved by the best
performing sources, we do not have
adequate data to refute the assertion that
the 30-percent opacity limit (determined
on a 6-minute average basis) is not
achievable during startup and shutdown
events. We considered the two options
suggested by the commenters, the
minimum velocity for the internal FCCU
regenerator cyclones and the 30-percent
hourly average opacity limit excluding 5
minutes not exceeding 65-percent
opacity. Again, due to the limited data
available during startup and shutdown
events, we are not able to determine
which requirement would provide
greater HAP emissions reduction.
However, we note that some facilities
may not be required to have an opacity
monitoring system in place and opacity
monitoring is not applicable for FCCU
controlled with wet scrubbers.
Therefore, we find that the minimum
internal cyclone inlet velocity
requirement is more broadly applicable
than the opacity limit. Also, based on
the data provided by the commenters,
the minimum internal cyclone inlet
velocity requirement will provide PM
(and therefore metal HAP) emissions
reductions during startup and shutdown
periods. Therefore, considering the
available data, we conclude that MACT
for FCCU startup and shutdown events
is maintaining the minimum internal
cyclone inlet velocity of 20 feet/second.
Comment: Several commenters stated
that the EPA should provide alternate
standards for startups of FCCU
equipped with CO boilers and for any
FCCU during periods of shutdown and
hot standby. The commenters stated that
the EPA incorrectly assumes that
refiners are able to safely and reliably
start up their FCCU with flue gas boilers
in service and meet the normal
operating limit of 500 ppm CO. They
claimed that most refiners are unable to
reliably start up their FCCU with flue
gas boilers in service due to the design
of the boiler and the fact that many
boilers are not able to safely and reliably
handle the transient FCCU operations
that can occur during startup,
shutdown, and hot standby. One
commenter stated that FCCU built with
CO boilers experience issues with flame
stability due to fluctuating flue gas
compositions and rates when starting up
and shutting down. Accordingly, the
commenter stated, startup and
shutdown activities at FCCU using a
boiler as an APCD are not currently
meeting the Refinery MACT 2 standard
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
of 500 ppm CO on a 1-hour basis, and
this level of control does not qualify as
the MACT floor. The commenter gave
examples of facilities where FCCU,
including those equipped with postcombustion control systems, do not
consistently demonstrate compliance
with a 500 ppm CO concentration
standard during all startup and
shutdown events.
Commenters stated that reliable boiler
operation is critical to the overall
refinery steam system and refineries
must avoid jeopardizing boiler
operation to prevent major upsets of
process operations. A major upset or
site-wide shutdown could result in
flaring and emissions of HAP far in
excess of that emitted while bypassing
the CO boiler.
Commenters stated that combustion of
torch oil in the FCCU regenerator during
startup is one of the primary reasons the
CO limit cannot be met during these
operations. Torch oil is also used during
shutdown to control the cooling rate
(and potential equipment damage) and
during hot standby and, thus, the
normal CO standard cannot be met at
these times either. Hot standby is used
to hold an FCCU regenerator at
operating temperature for outages where
a regenerator shutdown is not needed
and to avoid full FCCU shutdowns. Full
cold shutdown also increases personnel
exposures associated with removing
catalyst and securing equipment.
Additionally, this can produce
additional emissions over maintaining
the unit in hot standby. Commenters
claimed that because of the variability of
CO during torch oil operations, it is not
possible for the EPA to establish a CAA
section 112(d) standard for startup and
shutdown activities at FCCU because
refineries cannot measure a constant
level of emissions reductions.
The commenters recommended
expansion of the proposed standard of
greater than 1-percent hourly average
excess regenerator oxygen to all FCCU,
including units with fired boilers. These
commenters suggested that maintaining
an adequate level of excess oxygen for
the combustion of fuel in the
regenerator is the best way to minimize
CO and organic HAP emissions from
FCCU during these periods.
Response: After reviewing the
comments and discussing CO boiler
operations with facility operators, we
agree that the 1-percent minimum
oxygen limit should be more broadly
applicable to FCCU startup and
shutdown regardless of the control
device configuration and have revised
the final rule accordingly.
Comment: Several commenters stated
that the proposed alternative standards
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
for SRP shutdowns should be extended
to startups as well since the normal SRP
emission limitation cannot always be
achieved during SRP startups. Several
commenters gave examples of startup
activities where this relief is needed,
and noted there may be other startup
activities that also need this relief.
Response: For the control of sulfur
HAP, we determined that incineration
effectively controls these HAP. We were
not aware that there would be unusual
sulfur loads in the SRU tail gas during
startup. We agree that the alternative
standard we proposed for periods of
shutdown is also the MACT floor for
periods of startup because incineration
meeting the limits proposed will
achieve the MACT control requirements
for sulfur HAP during periods of either
startup or shutdown even though sulfur
loadings during these periods may be
elevated. For many SRU configurations,
compliance during normal operations is
demonstrated by monitoring SO2
emissions. However, during startup and
shutdown, high sulfur loadings in the
SRU tail gas entering the incinerator
will cause high SO2 emissions even
though sulfur HAP emissions are well
controlled. Consequently, the proposed
incinerator operating limits provide a
better indication of sulfur HAP control
during startup and shutdown than SO2
emissions. Owners or operators that use
incinerators or thermal oxidizers during
normal operations may meet the sitespecific temperature and excess oxygen
operating limits that were determined
based on their performance test during
periods of startup and shutdown.
4. What is the rationale for our final
approach and final decisions to address
emissions during periods of SSM?
a. Refinery MACT 1
We did not receive comments
regarding the proposed amendments to
Table 6 of subpart CC of 40 CFR part 63;
therefore, for the reasons provided in
the preamble to the proposed rule, we
finalizing these amendments as
proposed.
We determined that it was overly
burdensome and in most cases
technically infeasible to consider every
potential equipment or vessel opening
and classify these ‘‘openings’’ (newly
classified as MPV in the proposal) as
either Group 1 or Group 2 MPV. We also
determined that it is not always
technically feasible, depending on the
opening, to demonstrate compliance
with the MPV emissions limitations.
After considering the public comments,
we determined it was appropriate to
establish separate startup and shutdown
provisions for MPV associated with
PO 00000
Frm 00045
Fmt 4701
Sfmt 4700
75221
process equipment openings. We
reviewed state and local requirements
and based the final rule requirements on
the emissions limitations required to be
followed by the best performing sources.
Therefore, we are finalizing
requirements for refinery owners or
operators to open process equipment
during these startup and shutdown
events without directly permitting these
‘‘vents’’ as Group 1 or Group 2 MPV
provided that the equipment is drained
and purged to a closed system until the
hydrocarbon content is less than or
equal to 10-percent of the LEL. As
described in further detail previously in
this section, we have provided
provisions for special cases where the
10-percent LEL limit cannot be
demonstrated and provisions for less
significant equipment openings,
consistent with the practices used by
the best performing facilities.
b. Refinery MACT 2
We did not receive significant
comments regarding the proposed
amendments to Table 44 to subpart
UUU of 40 CFR part 63; therefore, we
finalizing these amendments as
proposed.
In response to comments, we
determined that the limited provisions
that were provided for startup only or
for shutdown only were too limited and
we have expanded the proposed
provisions to both startup and
shutdown regardless of control device
used. For the FCCU organic HAP
emissions limit, we are finalizing an
alternative limit for periods of startup of
no less than 1-percent oxygen in the
exhaust gas as proposed, but we are
extending that alternative limit to
shutdown and to all FCCU in this final
rule.
For the FCCU metal HAP emissions
limit, we proposed a specific startup
limit for FCCU controlled be an ESP of
30-percent opacity. We received
comments along with limited data
suggesting that this limit was not
achievable. Commenters suggested that
the best performing units maintain a
minimum face velocity of at least 20
feet/second to minimize catalyst PM
losses during startup and shutdowns.
Operators of wet scrubbers also noted
that they cannot maintain pressure
drops and that one cannot meet the PM
emissions limit normalized by coke
burn-off rate when the coke burn-off rate
approaches zero. Consequently,
commenters stated that the alternative
limits should be provided for startup
and shutdown regardless of control
device. Upon consideration of the
comments, we determined that it was
necessary to revise the proposed
E:\FR\FM\01DER2.SGM
01DER2
75222
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
alternative to be based on minimum
inlet face velocity to the FCCU
regenerator internal cyclones and
provide the alternative for both startup
and shutdown. We also expanded this
limit to all FCCU; however, we also
required FCCU with wet scrubbers to
meet only the liquid to gas ratio
operating limit during periods of startup
and shutdown to allow wet scrubbers to
use a consistent compliance method at
all times.
For SRU, we are finalizing an
alternative standard during periods of
startup and shutdown to use a flare that
meets the operating limits included in
the final rule or a thermal oxidizer or
incinerator operated at a minimum
hourly average temperature of 1,200 °F
and a minimum hourly average outlet
oxygen concentration of 2 volume
percent (dry basis). We proposed these
alternatives for periods of shutdown
only, but based on comments received
regarding startup issues, we determined
that high sulfur loadings can occur
during periods of startup and that the
alternative limit proposed was
appropriate for both startup and
shutdown.
E. Technical Amendments to Refinery
MACT 1 and 2
tkelley on DSK3SPTVN1PROD with RULES2
1. What other amendments did we
propose for Refinery MACT 1 and 2?
We proposed a number of
amendments to Refinery MACT 1 and 2
to address technical issues such as rule
language clarifications and reference
corrections. First, we proposed to
amend Refinery MACT 1 to clarify what
is meant by ‘‘seal’’ for open-ended
valves and lines that are ‘‘sealed’’ by the
cap, blind flange, plug, or second valve
by stating that sealed means when there
are no detectable emissions from the
open-ended valve or line at or above an
instrument reading of 500 ppm. Second,
we also proposed electronic reporting
requirements where owners or operators
of petroleum refineries must submit
electronic copies of required
performance test and performance
evaluation reports for compliance with
Refinery MACT 1 and 2 by direct
computer-to-computer electronic
transfer using EPA-provided software.
Third, we proposed to update the
General Provisions Tables 6 (for
Refinery MACT 1) and 44 (for Refinery
MACT 2) to correct cross references and
to incorporate additional sections of the
General Provisions that are necessary to
implement these rules.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
2. How did the other amendments for
Refinery MACT 1 and 2 change since
proposal?
We are not finalizing the definition of
‘‘seal’’ for open-ended lines as
proposed. We are finalizing changes to
update the General Provisions crossreference tables as proposed, with one
minor change to provide an option for
the administrator to issue guidance on
performance test reporting timeframes
in order to address issues relating to
submittal of data to the ERT.
3. What key comments did we receive
on the other amendments for Refinery
MACT 1 and 2 and what are our
responses?
Comment: Numerous commenters
objected to the proposal to clarify the
meaning of ‘‘seal’’ as it relates to openended line (OEL) standards.
Commenters contend that there is no
basis for the EPA to assert that the
proposed definition merely ‘‘clarifies’’
an established interpretation of the term
‘‘seal’’ and stated that the proposed
revision constitutes an illegal change in
the requirements for OELs, and the
clarification should not be finalized.
One commenter stated that none of
the MACT standards in place before this
proposal have stated or suggested that a
‘‘sealed’’ OEL is one with detectable
emissions below 500 ppm. This
commenter added this unique
interpretation of the requirement to
‘‘seal’’ an OEL with a cap or plug is
incompatible with the historical
interpretation of this requirement by
affected facilities and by the EPA, and
the EPA has not issued any sort of
definitive guidance or interpretation
setting out this position. The commenter
detailed numerous references to
considerations the EPA has made
relative to OEL requirements in LDAR
programs. In addition to the examples
cited, the commenter noted that in 2006,
the EPA proposed to add a ‘‘no
detectible emissions’’ limit and
monitoring requirement for OELs to
NSPS VV (71 FR 65317, November 7,
2006). Two commenters noted that the
proposed monitoring was not finalized
in either NSPS VV or VVa (72 FR 64860,
November 16, 2007) because it was not
considered BDT due to the low emission
reductions and the cost effectiveness of
the requirement. Another commenter
agreed that there is no explanation
provided for why this information could
now support the need for a new OEL
seal standard that requires monitoring to
ensure compliance when it was deemed
to be unjustified previously.
In addition, the commenter collected
OEL monitoring data and submitted it to
PO 00000
Frm 00046
Fmt 4701
Sfmt 4700
the EPA (see Docket Item No. EPA–HQ–
OAR–2010–0869–0058). Based on these
data, the commenter asserted that the
existence of leaks from OELs that are
not properly sealed is extremely low.
The commenter noted that the EPA is
claiming this change is only a
clarification of current requirements,
allowing the EPA to bypass the need to
cite a CAA authorization for this change
to the existing CAA section 112(d)(2)
standard or meet the process
requirements associated with such a
change, including providing emission
reduction, cost and burden estimates in
the record and the associated PRA
Information Collection Request (ICR).
Several commenters claimed that this
clarification would result in retroactive
impact and also addressed the
implication of the proposed change on
other fugitive emissions standards. One
commenter stated that the EPA cannot
retroactively reinterpret the OEL
requirements or define the word ‘‘seal’’
and added that the EPA should account
for the thousands of additional
monitoring events per year per refinery
that this new requirement would add to
LDAR programs and provide proper cost
justification under CAA sections
112(d)(6) or 112(f)(2).
Several commenters also stated that
the proposed definition will effectively
change all equipment leak rules in parts
40 CFR parts 60, 61 and 63 and the
change should not be finalized. One
commenter added that by claiming this
change is only a clarification of current
requirements, the EPA would set a
precedent applicable to all OELs in all
industries subject to any similar OEL
equipment leak requirement.
Response: We have decided not to
finalize the proposed clarification of the
term ‘‘seal’’ for OELs at this time. The
fenceline monitoring requirements we
are finalizing will detect any significant
leaks from a cap, blind flange, plug or
second valve that does not properly seal
an OEL, as well as significant leaks from
numerous other types of fugitive
emission sources.
Comment: A few commenters stated
that the proposed use of the ERT is not
appropriate because the costs and
burdens imposed are additive to the
costs of producing and submitting the
written report, and there is no benefit
that justifies the additional cost. One
commenter also stated that the EPA has
not developed or articulated a
reasonable approach to using
information that would be uploaded to
the ERT. The commenters
recommended that the EPA remove this
portion of the proposal until the ERT is
demonstrated to handle all the
information from refinery performance
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tests (rather than only portions), thereby
eliminating the need for both written
and electronic reporting and until the
Agency demonstrates that it is using the
electronic data to develop improved air
quality emission factors.
Other commenters stated that the ERT
requirement does not supersede or
replace any state reporting requirements
and thus the regulated industry will be
subject to dual reporting requirements.
These commenters disagreed with the
preamble claim that eliminating the
recordkeeping requirements for
performance test reports is a burden
savings, and stated that it may duplicate
burdens already borne by the regulated
community.
The commenters expressed further
concern that duplicative reporting
requirements will strain the regulated
industry to comply with deadlines
established by rule for report submittals.
One commenter stated that there is no
mechanism for obtaining extensions for
special circumstances. Under proposed
40 CFR 63.655(h)(9)(i), all reports are
due in 60 days. The commenter claimed
that by not referencing reporting
requirements to the General Provisions
in 40 CFR 63.10(d)(2), there is no
allowance for obtaining additional time
due to unforeseen circumstances or due
to the difficulties involved with
completing particularly complex
reports.
One commenter stated that the
primary performance test method
(Method 18) required for determining
compliance is not currently included in
the list of methods supported by the
ERT. The commenter stated that the
regulated community’s experience with
Method 18 is that it is a very broad
methodology and can be exceptionally
complex to execute and to report. The
commenter stated that the EPA is aware
that Method 18 reporting is complex,
that it may be difficult to incorporate
into the ERT, and that no time schedule
has been defined for development or
implementation for this method.
The commenter also stated that
without formal notice of changes to the
ERT, the regulated community is at risk
of non-compliance. The only way for
the regulated community to know that
changes have occurred in the ERT is to
monitor the Web site directly because
the EPA does not formally announce
changes to the ERT in the Federal
Register. As such, it would be possible
for a regulated entity to be unaware of
changes made such as the incorporation
of Method 18. The commenter
expressed concern that the proposal
language is an open-ended commitment
subject to change without notice. The
commenter stated that the EPA should
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
clearly indicate when facilities would
be required to use the ERT when new
test methods are included in the ERT.
Response: We disagree that use of the
ERT for completing stack test reports is
an added cost and burden. While the
requirement to report the results of stack
tests with the ERT does not supersede
state reporting requirements, we are
aware of several states that already
require the use of the ERT, and we are
aware of more states that are
considering requiring its use. We note
that where states will not accept an
electronic ERT submittal, the ERT
provides an option to print the report,
and the printed report can be mailed to
the state agency. We have no reason to
believe that the time savings in the
ability to reuse data elements within
reports does not, at a minimum, offset
the cost incurred by printing out and
mailing a copy of the report and the
commenters have provided no support
for their cost claims.
Furthermore, based on the analysis
performed for the Electronic Reporting
and Recordkeeping Requirements for
the New Source Performance Standards
Rulemaking (ERRRNSPS) (80 FR 15100),
electronic reporting results in an overall
cost savings to industry when
annualized over a 20-year period. The
cost savings is achieved through means
such as standardization of data,
embedded quality assurance checks,
automatic calculation routines and
reduced data entry through the ability to
reuse data in files instead of starting
from scratch with each test. As outlined
in the ERRRNSPS, there are many
benefits to electronic reporting. These
benefits span all users of the data—the
EPA, state and local regulators, the
regulated entities and the public. We
note that in the preamble to this
proposed rule we provided a number of
reasons why the use of the ERT will
provide benefit going forward and that
most of the benefits we outlined were
longer-term benefits (e.g., reducing
burden of future information collection
requests). Additionally, we note that in
2011, in response to Executive Order
13563, the EPA developed a plan 13 to
periodically review its regulations to
determine if they should be modified,
streamlined, expanded or repealed in an
effort to make regulations more effective
and less burdensome. The plan includes
replacing outdated paper reporting with
electronic reporting. In keeping with
this plan and the White House’s Digital
13 EPA’s
‘‘Final Plan for Periodic Retrospective
Reviews,’’ August 2011. Available at: https://www.
epa.gov/regdarrt/retrospective/documents/
eparetroreviewplan-aug2011.pdf.
PO 00000
Frm 00047
Fmt 4701
Sfmt 4700
75223
Government Strategy, 14 in 2013 the
EPA issued an agency-wide policy
specifying that new regulations will
require reports to be electronic to the
maximum extent possible. By requiring
electronic submission of stack test
reports in this rule, we are taking steps
to implement this policy. We also
disagree that we have not developed or
articulated a reasonable approach to
using information that would be
uploaded to the ERT. To the contrary,
we have discussed at length our plans
for the use of stack test data collected
via the ERT. In 2009, we published an
advanced notice of proposed
rulemaking (74 FR 52723) for the
Emissions Factors Program
Improvements. In that notice, we first
outlined our intended approach for
revising our emissions factors
development procedures. This approach
included using stack test data collected
with the ERT. We reiterated this
position in our ‘‘Recommended
Procedures for the Development of
Emissions Factors and Use of the
WebFIRE Database’’ (https://www.epa.
gov/ttn/chief/efpac/procedures/
procedures81213.pdf), which was
subject to public notice and comment
before being finalized in 2013. Finally,
we discussed uses of these data in the
preamble to the proposed rule and at
length in the preamble to the
ERRRNSPS.
We think that it is a circular argument
to say that the agency should eliminate
the use of the ERT until it demonstrates
that it is using the electronic data. It
would be impossible for the agency to
use data that it does not have. We can
only use electronic data once we have
electronic data. We do note that we are
nearing completion of programming the
WebFIRE database with our new
emissions factor development
procedures and anticipate running the
routines on existing data sets in the near
future.
We continue to improve and upgrade
the ERT on an ongoing basis. The
current version of the ERT supports 41
methods, including EPA Methods 1–4,
5, 5B, 5F, 25A 26, and 26A. We note
that the ERT does not currently support
EPA Method 18, and for performance
tests using Method 18, the source will
still have to produce a paper report.
However, we are aware of the need to
add Method 18 to the ERT, and we are
currently looking at developing this
capability. As noted in the ERRRNSPS,
when new methods are added to the
14 Digital Government: Building a 21st Century
Platform to Better Serve the American People, May
2012. Available at: https://www.whitehouse.gov/
sites/default/files/omb/egov/digital-government/
digital-government-strategy.pdf.
E:\FR\FM\01DER2.SGM
01DER2
75224
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
ERT, we will not only post them to the
Web site; we will also send out a listserv
notice to the Clearinghouse for
Inventories and Emissions Factors
(CHIEF) listserv. Information on joining
the CHIEF listserv can be found at
https://www.epa.gov/ttn/chief/
listserv.html#chief. We are requiring the
use of the ERT if the method is
supported by the ERT, as listed on the
ERT Web site (https://www.epa.gov/ttn/
chief/ert/ert_info.html) at the time of the
test. We do not agree that it is overly
burdensome to check a Web site for
updates prior to conducting a
performance test.
We did revise the MACT 1 and 2
tables referencing reporting
requirements to the general provisions
(Table 6 for Refinery MACT 1 and Table
44 for Refinery MACT 2) to provide
flexibility in the 60-day reporting
timeline to accommodate unforeseen
circumstances or difficulties involved
with completing particularly complex
reports.
4. What is the rationale for our final
approach and final decisions for the
other amendments for Refinery MACT 1
and 2?
We are not finalizing the definition of
seal, as proposed. The fenceline
monitoring work practice standard will
detect any significant leaks from a cap,
blind flange, plug or second valve that
does not properly seal an OEL, as well
as significant leaks from numerous other
types of fugitive emission sources.
We are finalizing requirements for
electronic reporting, as proposed, with a
minor clarification. Specifically, we are
revising Tables 6 in subpart CC and 44
in subpart UUU, which cross-reference
the applicable provisions in the General
Provisions to provide flexibility in the
ERT 60-day reporting timeline. Refiners
can seek approval from the EPA or a
delegated state additional time for
submittal of data due to unforeseen
circumstances or due to the difficulties
involved with completing particularly
complex reports.
F. Technical Amendments to Refinery
NSPS Subparts J and Ja
tkelley on DSK3SPTVN1PROD with RULES2
1. What amendments did we propose for
Refinery NSPS Subparts J and Ja?
We proposed a number of
amendments to Refinery NSPS subparts
J and Ja to address reconsideration
issues and minor technical
clarifications. First, we proposed
revisions to 40 CFR 60.100a(b) to
include a provision that sources subject
to Refinery NSPS subpart J could elect
to comply instead with the provisions of
Refinery NSPS subpart Ja.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Second, we proposed a series of
amendments to the requirements for
SRP in 40 CFR 60.102a, to clarify the
applicable emission limits for different
types of SRP based on whether oxygen
enrichment is used. The amendments
proposed also clarified that emissions
averaging across a group of emission
points within a given SRP is allowed for
each of the different types of SRP, and
that emissions averaging is specific to
the SO2 or reduced sulfur standards
(and not to the 10 ppmv hydrogen
sulfide (H2S) limit). We also proposed a
series of corresponding amendments in
40 CFR 60.106a to clarify the monitoring
requirements, particularly when oxygen
enrichment or emissions averaging is
used. We also proposed clarifications in
40 CFR 60.106a to consistently use the
term ‘‘reduced sulfur compounds’’
when referring to the emission limits
and monitoring devices needed to
comply with the reduced sulfur
compound emission limits for sulfur
recovery plants with reduction control
systems not followed by incineration.
Third, we proposed amendments to
40 CFR 60.102a(g)(1) to clarify that CO
boilers, while part of the FCCU affected
facility, can also be FGCD.
Fourth, we proposed several revisions
to 40 CFR 60.104a to clarify the
performance testing requirements. We
proposed revision to 40 CFR 60.104a(a)
to clarify that an initial compliance
demonstration is needed for the H2S
concentration limit in 40 CFR
60.103a(h). We proposed revisions to
the annual PM testing requirement in 40
CFR 60.104a(b) to clarify that annually
means once per calendar year, with an
interval of at least 8 months but no more
than 16 months between annual tests.
We also proposed to amend 40 CFR
60.104a(f) to clarify that the provisions
of that paragraph are specific to owners
or operators of an FCCU or FCU that use
a cyclone to comply with the PM
emissions limit in 40 CFR 60.102a(b)(1)
and not to facilities electing to comply
with the PM emissions limit using a PM
CEMS. We also proposed to amend 40
CFR 60.104a(j) to delete the
requirements to measure flow for the
H2S concentration limit for fuel gas.
Fifth, we proposed several
amendments to clarify the requirements
for control device operating parameters
in 40 CFR 60.105a. Specifically, we
proposed amendments to 40 CFR
60.105a(b)(1)(ii)(A) to require corrective
action be completed to repair faulty
(leaking or plugged) air or water lines
within 12 hours of identification of an
abnormal pressure reading during the
daily checks. We also proposed
revisions to 40 CFR 60.105a(i) to specify
that periods when abnormal pressure
PO 00000
Frm 00048
Fmt 4701
Sfmt 4700
readings for a jet ejector-type wet
scrubber (or other type of wet scrubber
equipped with atomizing spray nozzles)
are not corrected within 12 hours of
identification and periods when a bag
leak detection system alarm (for a fabric
filter) is not alleviated within the time
period specified in the rule are
considered to be periods of excess
emissions.
We also proposed amendments to 40
CFR 60.105(b)(1)(iv) and
60.107a(b)(1)(iv) to provide flexibility in
span range to accommodate different
manufacturers of the length-of-stain
tubes. We also proposed to delete the
last sentence in 40 CFR 60.105(b)(3)(iii).
Finally, we proposed clarification to
the performance test requirements for
the H2S concentration limit for affected
flares in 40 CFR 60.107a(e)(1)(ii) and
(e)(2)(ii) to remove the distinction
between flares with or without routine
flow.
2. How did the amendments to Refinery
NSPS Subparts J and Ja change since
proposal?
We are making very few changes to
the amendments proposed for Refinery
NSPS subparts J and Ja. In response to
comments, we are revising the NSPS
requirements to replace the
‘‘measurement sensitivity’’ requirements
with accuracy requirements consistent
with those used in Refinery MACT 1
and 2. Specifically, we are revising 40
CFR 60.106a(a)(6)(i)(B) and (7)(i)(B) to
require use of a flow sensor meeting an
accuracy requirement of ±5-percent over
the normal range of flow measured or
10-cubic-feet-per-minute, whichever is
greater. We are also revising the flare
accuracy requirements in 40 CFR
60.107a(f)(1)(ii) to require use of a flow
sensor meeting an accuracy requirement
of ±20-percent of the flow rate at
velocities ranging from 0.1 to 1 feet per
second and an accuracy of ±5-percent of
the flow rate for velocities greater than
1-feet-per-second.
Finally, we are revising 40 CFR
60.101a(b) to correct an inadvertent
error where the phrase ‘‘and delayed
coking units’’ was not included in the
proposed sentence revision.
3. What key comments did we receive
on the amendments to Refinery NSPS
Subparts J and Ja and what are our
responses?
Comment: Two commenters noted
concern with the term ‘‘measurement
sensitivity’’ in proposed 40 CFR
60.106a(a)(6)(i)(B) and (a)(7)(i)(B) for
sulfur recovery unit monitoring
alternatives and in existing regulations
40 CFR 60.107a(f)(1)(ii) for flares
because ‘‘sensitivity’’ is not a term
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
found on typical monitoring system data
sheets. Typical flow meter
characteristics include terms such as
accuracy and resolution and the
commenters requested that the EPA
revise the terminology to match the
wording found in 40 CFR part 63,
subpart CC, Table 13 for flow meters
(i.e., accuracy requirements).
Additionally, several commenters
suggested that the EPA flow monitor
accuracy specifications are inconsistent
with those in the SCAQMD Flare Rule
and many refinery consent decrees. The
commenters recommended revising
both the flare flow meter sensitivity
specification and accuracy specification
in Refinery MACT 1 Table 13 and in
Refinery NSPS subpart Ja to be
consistent with the accuracy
specification from the Shell Deer Park
Consent Decree, Appendix 1.10, which
specifies the required flare flow meter
accuracy as ‘‘±20% of reading over the
velocity range of 0.1–1 feet per second
(ft/s) and ±5% of reading over the
velocity range of 1–250 ft/s.’’
Response: We proposed the term
‘‘measurement sensitivity’’ in proposed
40 CFR 60.106a(a)(6)(i)(B) and
(a)(7)(i)(B) to be internally consistent
within Refinery NSPS subpart Ja [i.e.,
consistent with the existing language in
§ 60.107a(f)(1)(ii)]. However, we agree
with the commenters that this term may
be unclear. This term is not defined in
Refinery NSPS subpart Ja and it is not
commonly used in the flow monitoring
system’s technical specification sheets.
Therefore, to be consistent with the
terminology used by instrument vendors
and used in Refinery MACT 1 and 2, we
are revising these sections to replace the
term ‘‘measurement sensitivity’’ with
‘‘accuracy.’’ We are also revising the
flow rate accuracy provisions specific
for flares to provide an accuracy
requirement of ±20-percent over the
velocity range of 0.1–1 ft/s and ±5% for
velocities exceeding 1 ft/s in 40 CFR
60.107a(f)(1)(ii) and in Table 13 of
subpart CC. We are providing this
provision specifically for flares because
they commonly operate at high
turndown ratios. For other flow
measurements, we are retaining the 10cubic-foot-per-minute accuracy
requirement. We are also clarifying that
the ±5-percent accuracy requirement for
the SRU alternatives apply to the ‘‘the
normal range of flow measured’’
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
consistent with the requirements in
Refinery MACT 1 and 2.
Comment: One commenter stated that
in the proposed revisions to 40 CFR
60.100a, (79 FR 36956), the EPA
proposes to remove the phrase ‘‘and
delayed coker units’’ from 40 CFR
60.100a(b). However, we state the
compliance date for both flares and
delayed coker units separately in the
same paragraph. The commenter
believes the EPA should explain the
reason for and implications of the
removal of this phrase.
Response: The removal of the phrase
‘‘and delayed coking units’’ from the
first sentence in 40 CFR 60.100a(b) was
an inadvertent error. The only revision
that we intended to make in 40 CFR
60.100a was to allow owners or
operators subject to subpart J to elect to
comply with the requirements in
subpart Ja. In the final amendments, we
have included the phrase ‘‘and delayed
coking units’’ in the first sentence in 40
CFR 60.100a(b).
4. What is the rationale for our final
approach and final decisions for the
amendments to Refinery NSPS Subparts
J and Ja?
We are finalizing amendments for
Refinery NSPS subparts J and Ja as
proposed with minor revisions. In
response to comments, we are revising
the ‘‘measurement sensitivity’’
requirements to be an ‘‘accuracy’’
requirement. This change will make the
requirements more clear and consistent
between the flow meter requirements in
the NSPS and the MACT standards
since the same flow meter will be
subject to each of these requirements.
We are also providing a dual accuracy
requirement for flare flow meters. This
accuracy requirement is necessary
because flares, which can have large
diameters to accommodate high flows,
are commonly operated at low flow
rates. Together, this makes it technically
infeasible for many flares to meet the
lower flow 10 cfm accuracy
requirement. Therefore, we are
providing specific accuracy
requirements for flares of ±20-percent
over the velocity range of 0.1–1 ft/s and
±5-percent for velocities exceeding 1 ft/
s, consistent with recent consent
decrees and equipment vendor
specifications.
Finally, we are revising the
introductory phrase in the first sentence
PO 00000
Frm 00049
Fmt 4701
Sfmt 4700
75225
in 40 CFR 60.101a(b) to read ‘‘Except for
flares and delayed coking units . . .’’ to
correct an inadvertent error. We
intended to revise this sentence only to
include the proposed provision to allow
sources subject to Refinery NSPS
subpart J to comply with Refinery NSPS
subpart Ja. The redline text posted on
our Web site showed no revisions to this
introductory phrase, but the amendatory
text did not include the words ‘‘and
delayed coking units’’ in this phrase.
This was an inadvertent error, which we
are correcting in the final rule.
V. Summary of Cost, Environmental
and Economic Impacts and Additional
Analyses Conducted
A. What are the affected facilities, the
air quality impacts and cost impacts?
The sources affected by significant
amendments to the petroleum refinery
standards include flares, storage vessels,
pressure relief devices, fugitive
emissions and DCU. The amendments
for other sources subject to one or more
of the petroleum refinery standards are
expected to have minimal air quality
and cost impacts.
The total capital investment cost of
the final amendments and standards is
estimated at $283 million, $112 million
from the final amendments for storage
vessels, DCU and fenceline monitoring
and $171 million from standards to
ensure compliance. We estimate
annualized costs of the final
amendments for storage vessels, DCU
and fenceline monitoring to be
approximately $13.0 million, which
includes an estimated $11.0 million for
recovery of lost product and the
annualized cost of capital. We also
estimated annualized costs of the final
standards to ensure compliance to be
approximately $50.2 million. The final
amendments for storage vessels, DCU
and fenceline monitoring would achieve
a nationwide HAP emission reduction
of 1,323 tpy, with a concurrent
reduction in VOC emissions of 16,660
tpy and a reduction in methane
emissions of 8,700 metric tonnes per
year. Table 2 of this preamble
summarizes the cost and emission
reduction impacts of the final
amendments, and Table 3 of this
preamble summarizes the costs of the
final standards to ensure compliance.
E:\FR\FM\01DER2.SGM
01DER2
75226
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 2—NATIONWIDE IMPACTS OF FINAL AMENDMENTS (2010$)
Affected source
Total capital
investment
(million $)
Total
annualized
cost without
credit
(million $/yr)
Product
recovery
credit
(million $/yr)
Total
annualized
costs
(million $/yr)
Methane
emission
reductions
(metric tpy)
VOC
emission
reductions
(tpy)
Cost
effectiveness
($/ton VOC)
HAP
emission
reductions
(tpy)
Cost
effectiveness
($/ton HAP)
Storage Vessels ........................
Delayed Coking Units ...............
Fugitive Emissions (Fenceline
Monitoring) .............................
18.5
81
3.13
14.5
(8.16)
(2.80)
(5.03)
11.7
....................
8,700
14,600
2,060
(345)
5,680
910
413
(5,530)
28,330
12.5
6.36
....................
6.36
....................
....................
....................
....................
....................
Total ...................................
112
24.0
(11.0)
13.0
8,700
16,660
780
1,323
9,830
TABLE 3—NATIONWIDE COSTS OF FINAL AMENDMENTS TO ENSURE COMPLIANCE (2010$)
Total
annualized
cost without
credit
(million $/yr)
Product
recovery
credit
(million $/yr)
Total
annualized
costs
(million $/yr)
Affected Source
Total capital
investment
(million $)
Relief Device Monitoring ..................................................................................
Flare Monitoring ...............................................................................................
FCCU Testing ..................................................................................................
11.1
160
........................
3.3
46.5
0.4
........................
........................
........................
3.3
46.5
0.4
Total ..........................................................................................................
171
50.2
........................
50.2
The impacts shown in Table 2 do not
include costs, product recovery credits,
or emissions reductions associated with
any root cause analysis or corrective
action taken in response to the final
amendments for fenceline monitoring.
The impacts shown in Table 3 do not
include (i) the costs or emissions
reductions associated with any root
cause analysis and corrective action
taken in response to the final source
performance testing at the FCCUs, or (ii)
emissions reductions associated with
corrective action taken in response to
pressure relief device or (iii) emissions
reductions associated with the flare
operating and monitoring provisions.
The operational and monitoring
requirements for flares at refineries have
the potential to reduce excess emissions
from flares by up to approximately
3,900 tpy of HAP and 33,000 tpy of
VOC. The operational and monitoring
requirements for flares also have the
potential to reduce methane emissions
by 25,800 metric tonnes per year while
increasing emissions of carbon dioxide
(CO2) and nitrous oxide by 267,000
metric tonnes per year and 2 metric
tonnes per year, respectively, yielding a
net reduction in GHG emissions of
377,000 metric tonnes per year of CO2
equivalents (CO2e).
tkelley on DSK3SPTVN1PROD with RULES2
B. What are the economic impacts?
We performed a national economic
impact analysis for petroleum product
producers. All petroleum product
refiners will incur annual compliance
costs of less than 1-percent of their
sales. For all firms, the minimum costto-sales ratio is <0.01-percent; the
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
maximum cost-to-sales ratio is 0.87percent; and the mean cost-to-sales ratio
is 0.03-percent. Therefore, the overall
economic impact of this proposed rule
should be minimal for the refining
industry and its consumers.
In addition, the EPA performed a
screening analysis for impacts on small
businesses by comparing estimated
annualized engineering compliance
costs at the firm-level to firm sales. The
screening analysis found that the ratio
of compliance cost to firm revenue falls
below 1-percent for the 28 small
companies likely to be affected by the
proposal. For small firms, the minimum
cost-to-sales ratio is <0.01-percent; the
maximum cost-to-sales ratio is 0.62percent; and the mean cost-to-sales ratio
is 0.07-percent.
More information and details of this
analysis is provided in the technical
document ‘‘Economic Impact Analysis
for Petroleum Refineries Proposed
Amendments to the National Emissions
Standards for Hazardous Air
Pollutants’’, which is available in the
docket for this rule (Docket ID No. EPA–
HQ–OAR–2010–0682).
C. What are the benefits?
The final rule is anticipated to result
in a reduction of 1,323 tpy of HAP
(based on allowable emissions under the
MACT standards) and 16,660 tpy of
VOC, not including potential emission
reductions that may occur as a result of
the operating and monitoring
requirements for flares and fugitive
emission sources via fenceline
monitoring. These avoided emissions
will result in improvements in air
PO 00000
Frm 00050
Fmt 4701
Sfmt 4700
quality and reduced negative health
effects associated with exposure to air
pollution of these emissions; however,
we have not quantified or monetized the
benefits of reducing these emissions for
this rulemaking.
D. Impacts of This Rulemaking on
Environmental Justice Populations
To examine the potential impacts on
vulnerable populations (minority, lowincome and indigenous communities)
that might be associated with the
Petroleum Refinery source categories
addressed in this final rule, we
evaluated the percentages of various
social, demographic and economic
groups in the at-risk populations living
near the facilities where these sources
are located and compared them to
national averages. Our analysis of the
demographics of the population with
estimated risks greater than 1-in-1
million indicates potential disparities in
risks between demographic groups
including the African American, Other
and Multiracial, Hispanic, Below the
Poverty Level, and Over 25 without a
High School Diploma when compared
to the nationwide percentages of those
groups. These groups will benefit the
most from the emission reductions
achieved by this final rulemaking,
which is projected to result in 1 million
fewer people exposed to risks greater
than 1-in-1 million.
Additionally, these communities will
benefit from this rulemaking, as this
rulemaking for the first time ever
requires fenceline monitoring, and
reporting of fenceline data. The agency
during the pre-proposal period and
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
during the comment period received
feedback from communities on the
importance of having fenceline
monitoring in their communities and
the importance of communities having
access to this data. The EPA believes
that vulnerable communities will
benefit from this data and the
requirements that EPA has put in place
in this rulemaking to manage fugitive
emissions.
E. Impacts of This Rulemaking on
Children’s Health
Under Executive Order 13045 the EPA
must evaluate the effects of the planned
regulation on children’s health and
safety. This action’s health and risk
assessments are contained in section
IV.A of this preamble. We believe we
have adequately estimated risk for
children, and we do not believe that the
environmental health risks addressed by
this action present a disproportionate
risk to children. When the EPA derives
exposure reference concentrations and
unit risk estimates (URE) for HAP, it
also considers the most sensitive
populations identified (i.e., children) in
the available literature, and importantly,
these are the values used in our risk
assessments. With regard to children’s
potentially greater susceptibility to noncancer toxicants, the assessments rely
on the EPA (or comparable) hazard
identification and dose-response values
which have been developed to be
protective for all subgroups of the
general population, including children.
With respect to cancer, the EPA uses the
age-dependent adjustment factor
approach, and applies these factors to
carcinogenic pollutants that are known
to act via mutagenic mode of action.
Further details are provided in the
‘‘Final Residual Risk Assessment for the
Petroleum Refining Source Sector’’,
Docket ID No. EPA–HQ–OAR–2010–
0682.
tkelley on DSK3SPTVN1PROD with RULES2
VI. Statutory and Executive Order
Reviews
A. Executive Orders 12866: Regulatory
Planning and Review and Executive
Order 13563: Improving Regulation and
Regulatory Review
This action is an economically
significant regulatory action that was
submitted to the Office of Management
and Budget (OMB) for review. Any
changes made in response to OMB
recommendations have been
documented in the docket. The EPA
prepared an analysis of the potential
costs and benefits associated with this
action. This analysis, ‘‘Economic Impact
Analysis: Petroleum Refineries—Final
Amendments to the National Emissions
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Standards for Hazardous Air Pollutants
and New Source Performance
Standards’’ is available in Docket ID
Number EPA–HQ–OAR–2010–0682.
B. Paperwork Reduction Act (PRA)
The information collection
requirements in this rule have been
submitted for approval to the Office of
Management and Budget (OMB) under
the Paperwork Reduction Act, 44 U.S.C.
3501 et se. The information collection
requirements are not enforceable until
OMB approves them.
Adequate recordkeeping and
reporting are necessary to ensure
compliance with these standards as
required by the CAA. The ICR
information collected from
recordkeeping and reporting
requirements is also used for
prioritizing inspections and is of
sufficient quality to be used as evidence
in court.
The ICR document prepared by the
EPA for the amendments to the
Petroleum Refinery MACT standards for
40 CFR part 63, subpart CC has been
assigned the EPA ICR number 1692.08.
Burden changes associated with these
amendments would result from new
monitoring, recordkeeping and
reporting requirements. The estimated
annual increase in recordkeeping and
reporting burden hours is 99,722 hours;
the frequency of response is quarterly
and semiannual for reports for all
respondents that must comply with the
rule’s reporting requirements; and the
estimated average number of likely
respondents per year is 95 (this is the
average in the second year). The cost
burden to respondents resulting from
the collection of information includes
the total capital cost annualized over the
equipment’s expected useful life (about
$18 million, which includes monitoring
equipment for fenceline monitoring,
pressure relief devices, and flares), a
total operation and maintenance
component (about $21 million per year
for fenceline and flare monitoring), and
a labor cost component (about $8.3
million per year, the cost of the
additional 99,722 labor hours). Burden
is defined at 5 CFR 1320.3(b).
The ICR document prepared by the
EPA for the amendments to the
Petroleum Refinery MACT standards for
40 CFR part 63, subpart UUU has been
assigned the EPA ICR number 1844.06.
Burden changes associated with these
amendments would result from new
testing, recordkeeping and reporting
requirements being finalized with this
action. The estimated average burden
per response is 25 hours; the frequency
of response ranges from annually up to
every 5 years for respondents that have
PO 00000
Frm 00051
Fmt 4701
Sfmt 4700
75227
FCCU, and the estimated average
number of likely respondents per year is
67. The cost burden to respondents
resulting from the collection of
information includes the performance
testing costs (approximately $778,000
per year over the first 3 years for the
initial PM and one-time HCN
performance tests and $235,000 per year
starting in the fourth year), and a labor
cost component (approximately
$410,000 per year for 4,940 additional
labor hours). Burden is defined at 5 CFR
1320.3(b).
An agency may not conduct or
sponsor, and a person is not required to
respond to, a collection of information
unless it displays a currently valid OMB
control number. The OMB control
numbers for EPA’s regulations in 40
CFR are listed in 40 CFR part 9. When
this ICR is approved by OMB, the
Agency will publish a technical
amendment to 40 CFR part 9 in the
Federal Register to display the OMB
control number for the approved
information collection requirements
contained in this final rule.
C. Regulatory Flexibility Act (RFA)
I certify that this action will not have
a significant economic impact on a
substantial number of small entities
(SISNOSE) under the RFA. The small
entities subject to the requirements of
this action are small businesses, small
organizations and small governmental
jurisdictions. For purposes of assessing
the impacts of this rule on small
entities, a small entity is defined as: (1)
A small business in the petroleum
refining industry having 1,500 or fewer
employees (Small Business
Administration (SBA), 2011); (2) a small
governmental jurisdiction that is a
government of a city, county, town,
school district or special district with a
population of less than 50,000; and (3)
a small organization that is any not-forprofit enterprise which is independently
owned and operated and is not
dominant in its field. Details of this
analysis are presented in the economic
impact analysis which can be found in
the docket for this rule (Docket ID No.
EPA–HQ–OAR–2010–0682).
D. Unfunded Mandates Reform Act
(UMRA)
This action does not contain an
unfunded mandate of $100 million or
more as described in UMRA, 2 U.S.C.
1531–1538, and does not significantly or
uniquely affect small governments. As
discussed earlier in this preamble, these
amendments result in nationwide costs
of $63.2 million per year for the private
sector. Additionally, the rule contains
no requirements that apply to small
E:\FR\FM\01DER2.SGM
01DER2
75228
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
governments and does not impose
obligations upon them.
E. Executive Order 13132: Federalism
This action does not have federalism
implications. It will not have substantial
direct effects on the states, on the
relationship between the national
government and the states, or on the
distribution of power and
responsibilities among the various
levels of government.
F. Executive Order 13175: Consultation
and Coordination With Indian Tribal
Governments
This action does not have tribal
implications, as specified in Executive
Order 13175. The final amendments
impose no requirements on tribal
governments. Thus, Executive Order
13175 does not apply to this action.
Consistent with the EPA Policy on
Consultation and Coordination with
Indian Tribes, the EPA consulted with
tribal officials during the development
of the proposed rule and specifically
solicited comment on the proposed
amendments from tribal officials.
G. Executive Order 13045: Protection of
Children From Environmental Health
Risks and Safety Risks
This action is not subject to Executive
Order 13045 because the EPA does not
believe the environmental health or
safety risks addressed by this action
present a disproportionate risk to
children. This action’s health and risk
assessments are contained in section
IV.A of this preamble.
tkelley on DSK3SPTVN1PROD with RULES2
H. Executive Order 13211: Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution or Use
This action is not a ‘‘significant
energy action’’ because it is not likely to
have a significant adverse effect on the
supply, distribution or use of energy.
The overall economic impact of this
final rule should be minimal for the
refining industry and its consumers.
I. National Technology Transfer and
Advancement Act (NTTAA) and 1 CFR
Part 51
This rulemaking involves technical
standards. Therefore, the EPA
conducted searches for the Petroleum
Refinery Sector Risk and Technology
Review and New Source Performance
Standards through the Enhanced
National Standards Systems Network
(NSSN) Database managed by the
American National Standards Institute
(ANSI). We also contacted voluntary
consensus standards (VCS)
organizations and accessed and
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
searched their databases. We conducted
searches for EPA Methods 18, 22, 320,
325A, and 325B of 40 CFR parts 60 and
63, appendix A. No applicable VCS
were identified for EPA Method 22.
The following voluntary consensus
standards were identified as acceptable
alternatives to the EPA test methods for
the purpose of this rule.
The voluntary consensus standard
ISO 16017–2:2003(E) ‘‘Air quality—
Sampling and analysis of volatile
organic compounds in ambient air,
indoor air and workplace air by sorbent
tube/thermal desorption/capillary gas
chromatography. Part 2: Diffusive
sampling’’ is an acceptable alternative to
Method 325A, Sections 1.2, 6.1 and 6.5
and Method 325B Sections 1.3, 7.1.2,
7.1.3, 7.1.4, 12.2.4, 13.0, A.1.1, and A.2.
This voluntary consensus standard gives
general guidance for the sampling and
analysis of volatile organic compounds
in air. It is applicable to indoor, ambient
and workplace air. This standard is
available at International Organization
for Standardization, ISO Central
Secretariat, Chemin de Blandonnet 8,
CP 401, 1214 Vernier, Geneva,
Switzerland. See https://www.iso.org.
The voluntary consensus standard BS
EN 14662–4:2005 ‘‘Ambient Air Quality:
Standard Method for the Measurement
of Benzene Concentrations—Part 4:
Diffusive Sampling Followed By
Thermal Desorption and Gas
Chromatography’’ is an acceptable
alternative to Method 325A, Section 1.2
and Method 325B, Sections 1.3, 7.1.3,
7.1.4, 12.2.4, 13.0, A.1.1, and A.2. This
voluntary consensus standard gives
general guidance for the sampling and
analysis of benzene in air by diffusive
sampling, thermal desorption and
capillary gas chromatography. This
standard is available the European
Committee for Standardization, Avenue
Marnix 17—B–1000 Brussels. See
https://www.cen.eu.
The voluntary consensus standard
ASTM D6420–99 (2010) ‘‘Test Method
for Determination of Gaseous Organic
Compounds by Direct Interface Gas
Chromatography/Mass Spectrometry’’ is
an acceptable alternative to EPA Method
18. This voluntary consensus standard
employs a direct interface gas
chromatography/mass spectrometer
(GCMS) to identify and quantify a list of
36 volatile organic compounds (the
compounds are listed in the method).
The voluntary consensus standard
ASTM D6196–03 (Reapproved 2009)
‘‘Standard Practice for Selection of
Sorbents, Sampling, and Thermal
Desorption Analysis Procedures for
Volatile Organic Compounds in Air’’ is
an acceptable alternative to Method
325A, Sections 1.2 and 6.1, and Method
PO 00000
Frm 00052
Fmt 4701
Sfmt 4700
325B, Sections 1.3, 7.1.2, 7.1.3, 7.1.4,
13.0, A.1.1, and A.2. This voluntary
consensus standard is intended to assist
in the selection of sorbents and
procedures for the sampling and
analysis of ambient, indoor, and
workplace atmospheres for a variety of
common volatile organic compounds.
The voluntary consensus standards
ASTM D1945–03 and later revision
ASTM D1945–14 ‘‘Standard Test
Method for Analysis of Natural Gas by
Gas Chromatography’’ are acceptable for
natural gas analysis. This voluntary
consensus standard covers the
determination of the chemical
composition of natural gases and similar
gaseous mixtures. This test method may
be abbreviated for the analysis of lean
natural gases containing negligible
amounts of hexanes and higher
hydrocarbons, or for the determination
of one or more components, as required.
The voluntary consensus standard
ASTM UOP539–12 ‘‘Refinery Gas
Analysis by GC’’ is acceptable for
refinery gas analysis. This voluntary
consensus standard is for determining
the composition of refinery gas streams
or vaporized liquefied petroleum gas
using a preconfigured, commercially
available gas chromatograph.
The voluntary consensus standard
ASTM D6348–03 (Reapproved 2010)
including Annexes A1 through A8,
‘‘Determination of Gaseous Compounds
by Extractive Direct Interface Fourier
Transform (FTIR) Spectroscopy’’ is an
acceptable alternative to EPA Method
320. This voluntary consensus standard
is a field test method that employs an
extractive sampling system to direct
stationary source effluent to an FTIR
spectrometer for the identification and
quantification of gaseous compounds.
This field test method provides near real
time analysis of extracted gas samples
from stationary sources.
The voluntary consensus standard
ASTM D6348–12e1 ‘‘Determination of
Gaseous Compounds by Extractive
Direct Interface Fourier Transform
(FTIR) Spectroscopy’’ is an acceptable
alternative to EPA Method 320 with the
following two caveats: (1) The test plan
preparation and implementation in the
Annexes to ASTM D 6348–03
(Reapproved 2010), Sections A1 through
A8 are mandatory; and (2) In ASTM
D6348–03 (Reapproved 2010) Annex A5
(Analyte Spiking Technique), the
percent (%) R must be determined for
each target analyte (Equation A5.5). In
order for the test data to be acceptable
for a compound, %R must be 70% ≥ R
≤ 130%. If the %R value does not meet
this criterion for a target compound, the
test data is not acceptable for that
compound and the test must be repeated
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
for that analyte (i.e., the sampling and/
or analytical procedure should be
adjusted before a retest). The %R value
for each compound must be reported in
the test report, and all field
measurements must be corrected with
the calculated %R value for that
compound by using the following
equation:
Reported Result = (Measured
Concentration in the Stack × 100)/
% R.
This voluntary consensus standard is
a field test method that employs an
extractive sampling system to direct
stationary source effluent to an FTIR
spectrometer for the identification and
quantification of gaseous compounds.
This field test method provides near real
time analysis of extracted gas samples
from stationary sources.
The EPA solicited comments on VCS
and invited the public to identify
potentially-applicable VCS; however,
we did not receive comments regarding
this aspect of 40 CFR part 60, subparts
J and Ja, and part 63, subparts CC, UUU,
and Y. Under 40 CFR 63.7(f) and 63.8(f),
a source may apply to the EPA for
permission to use alternative test
methods or alternative monitoring
requirements in place of any required
testing methods, performance
specifications, or procedures in this
final rule.
tkelley on DSK3SPTVN1PROD with RULES2
J. Executive Order 12898: Federal
Actions To Address Environmental
Justice in Minority Populations and
Low-Income Populations
Executive Order 12898 (59 FR 7629;
February 16, 1994) establishes federal
executive policy on environmental
justice. Its main provision directs
federal agencies, to the greatest extent
practicable and permitted by law, to
make environmental justice part of their
mission by identifying and addressing,
as appropriate, disproportionately high
and adverse human health or
environmental effects of their programs,
policies and activities on minority
populations and low-income
populations in the U.S. The EPA defines
environmental justice as the fair
treatment and meaningful involvement
of all people regardless of race, color,
national origin or income with respect
to the development, implementation
and enforcement of environmental laws,
regulations and policies. The EPA has
this goal for all communities and
persons by working to ensure that
everyone enjoys the same degree of
protection from environmental and
health hazards and equal access to the
decision-making process to have a
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
healthy environment in which to live,
learn and work.
The EPA believes the human health or
environmental risk addressed by this
action will not have potential
disproportionately high and adverse
human health or environmental effects
on minority, low-income or indigenous
populations. As discussed in section
V.D. of this preamble, the EPA
conducted an analysis of the
characteristics of the population with
greater than 1-in-1 million risk living
within 50 km of the 142 refineries
affected by this rulemaking and
determined that there are more AfricanAmericans, Other and multiracial
groups, Hispanics, low-income
individuals, individuals with less than
a high school diploma compared to
national averages. Therefore, these
populations are expected to experience
the benefits of the risk reductions
associated with this rule. The results of
this evaluation are contained in two
technical reports, ‘‘Risk and Technology
Review—Analysis of Socio-Economic
Factors for Populations Living Near
Petroleum Refineries’’, available in the
docket for this action (See Docket ID
Nos. EPA–HQ–OAR–2010–0682–0226
and -0227). Additionally, a discussion
of the final risk analysis is included in
Sections IV.A and V.D of this preamble.
The EPA has determined that this
final rule will not have
disproportionately high and adverse
human health or environmental effects
on minority, low-income or indigenous
populations because it maintains or
increases the level of environmental
protection for all affected populations
without having any disproportionately
high and adverse human health or
environmental effects on any
population, including any minority,
low-income or indigenous populations.
Further, the EPA believes that
implementation of this rule will provide
an ample margin of safety to protect
public health of all demographic groups.
K. Congressional Review Act (CRA)
This action is subject to the CRA, and
the EPA will submit a rule report to
each House of the Congress and to the
Comptroller General of the United
States. This action is a ‘‘major rule’’ as
defined by 5 U.S.C. 804(2).
List of Subjects
40 CFR Part 60
Environmental protection,
Administrative practice and procedures,
Air pollution control, Hazardous
substances, Incorporation by reference,
Intergovernmental relations, Reporting
and recordkeeping requirements.
PO 00000
Frm 00053
Fmt 4701
Sfmt 4700
75229
40 CFR Part 63
Environmental protection,
Administrative practice and procedures,
Air pollution control, Hazardous
substances, Incorporation by reference,
Intergovernmental relations, Reporting
and recordkeeping requirements.
Dated: September 29, 2015.
Gina McCarthy,
Administrator.
For the reasons stated in the
preamble, title 40, chapter I, of the Code
of Federal Regulations is amended as
follows:
PART 60—STANDARDS OF
PERFORMANCE FOR NEW
STATIONARY SOURCES
1. The authority citation for part 60
continues to read as follows:
■
Authority: 42 U.S.C. 7401 et seq.
Subpart J—Standards of Performance
for Petroleum Refineries
2. Section 60.105 is amended by
revising paragraphs (b)(1)(iv) and
(b)(3)(iii) to read as follows:
■
§ 60.105 Monitoring of emissions and
operations.
*
*
*
*
*
(b) * * *
(1) * * *
(iv) The supporting test results from
sampling the requested fuel gas stream/
system demonstrating that the sulfur
content is less than 5 ppmv. Sampling
data must include, at minimum, 2
weeks of daily monitoring (14 grab
samples) for frequently operated fuel gas
streams/systems; for infrequently
operated fuel gas streams/systems,
seven grab samples must be collected
unless other additional information
would support reduced sampling. The
owner or operator shall use detector
tubes (‘‘length-of-stain tube’’ type
measurement) following the ‘‘Gas
Processors Association Standard 2377–
86 (incorporated by reference—see
§ 60.17), using tubes with a maximum
span between 10 and 40 ppmv inclusive
when 1≤N≤10, where N = number of
pump strokes, to test the applicant fuel
gas stream for H2S; and
*
*
*
*
*
(3) * * *
(iii) If the operation change results in
a sulfur content that is outside the range
of concentrations included in the
original application and the owner or
operator chooses not to submit new
information to support an exemption,
the owner or operator must begin H2S
monitoring using daily stain sampling to
demonstrate compliance using length-of
E:\FR\FM\01DER2.SGM
01DER2
75230
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Subpart Ja—Standards of Performance
for Petroleum Refineries for Which
Construction, Reconstruction, or
Modification Commenced After May 14,
2007
3. Section 60.100a is amended by
revising the first sentence of paragraph
(b) to read as follows:
■
*
*
*
*
*
(b) Except for flares and delayed
coking units, the provisions of this
subpart apply only to affected facilities
under paragraph (a) of this section
which either commence construction,
modification or reconstruction after May
14, 2007, or elect to comply with the
provisions of this subpart in lieu of
complying with the provisions in
subpart J of this part. * * *
*
*
*
*
*
■ 4. Section 60.101a is amended by:
■ a. Revising the definition of
‘‘Corrective action’’; and
■ b. Adding, in alphabetical order, a
definition for ‘‘Sour water’’.
The revision and addition read as
follows:
tkelley on DSK3SPTVN1PROD with RULES2
Definitions.
*
*
*
*
*
Where:
ELS = Emission limit for large sulfur recovery
plant, ppmv (as SO2, dry basis at zero
percent excess air);
k1 = Constant factor for emission limit
conversion: k1 = 1 for converting to the
SO2 limit for a sulfur recovery plant with
an oxidation control system or a
reduction control system followed by
incineration and k1 = 1.2 for converting
to the reduced sulfur compounds limit
for a sulfur recovery plant with a
reduction control system not followed by
incineration; and
%O2 = O2 concentration of the air/oxygen
mixture supplied to the Claus burner,
percent by volume (dry basis). If only
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
§ 60.102a
Emissions limitations.
*
§ 60.100a Applicability, designation of
affected facility, and reconstruction.
§ 60.101a
Corrective action means the design,
operation and maintenance changes that
one takes consistent with good
engineering practice to reduce or
eliminate the likelihood of the
recurrence of the primary cause and any
other contributing cause(s) of an event
identified by a root cause analysis as
having resulted in a discharge of gases
from an affected facility in excess of
specified thresholds.
*
*
*
*
*
Sour water means water that contains
sulfur compounds (usually H2S) at
concentrations of 10 parts per million
by weight or more.
*
*
*
*
*
■ 5. Section 60.102a is amended by
revising paragraphs (b)(1)(i) and (iii), (f),
and (g)(1) introductory text to read as
follows:
*
*
*
*
(b) * * *
(1) * * *
(i) 1.0 gram per kilogram (g/kg) (1
pound (lb) per 1,000 lb) coke burn-off
or, if a PM continuous emission
monitoring system (CEMS) is used,
0.040 grain per dry standard cubic feet
(gr/dscf) corrected to 0 percent excess
air for each modified or reconstructed
FCCU.
*
*
*
*
*
(iii) 1.0 g/kg (1 lb/1,000 lb) coke burnoff or, if a PM CEMS is used, 0.040 grain
per dry standard cubic feet (gr/dscf)
corrected to 0 percent excess air for each
affected FCU.
*
*
*
*
*
(f) Except as provided in paragraph
(f)(3) of this section, each owner or
operator of an affected sulfur recovery
plant shall comply with the applicable
emission limits in paragraph (f)(1) or (2)
of this section.
ambient air is used for the Claus burner
or if the owner or operator elects not to
monitor O2 concentration of the air/
oxygen mixture used in the Claus burner
or for non-Claus sulfur recovery plants,
use 20.9% for %O2.
(ii) For a sulfur recovery plant with a
reduction control system not followed
by incineration, the owner or operator
shall not discharge or cause the
discharge of any gases into the
atmosphere containing reduced sulfur
compounds in excess of the emission
limit calculated using Equation 1 of this
section. For Claus units that use only
PO 00000
Frm 00054
Fmt 4701
Sfmt 4700
(1) For a sulfur recovery plant with a
design production capacity greater than
20 long tons per day (LTD), the owner
or operator shall comply with the
applicable emission limit in paragraph
(f)(1)(i) or (ii) of this section. If the
sulfur recovery plant consists of
multiple process trains or release points,
the owner or operator shall comply with
the applicable emission limit for each
process train or release point
individually or comply with the
applicable emission limit in paragraph
(f)(1)(i) or (ii) as a flow rate weighted
average for a group of release points
from the sulfur recovery plant provided
that flow is monitored as specified in
§ 60.106a(a)(7); if flow is not monitored
as specified in § 60.106a(a)(7), the
owner or operator shall comply with the
applicable emission limit in paragraph
(f)(1)(i) or (ii) for each process train or
release point individually. For a sulfur
recovery plant with a design production
capacity greater than 20 long LTD and
a reduction control system not followed
by incineration, the owner or operator
shall also comply with the H2S emission
limit in paragraph (f)(1)(iii) of this
section for each individual release
point.
(i) For a sulfur recovery plant with an
oxidation control system or a reduction
control system followed by incineration,
the owner or operator shall not
discharge or cause the discharge of any
gases into the atmosphere (SO2) in
excess of the emission limit calculated
using Equation 1 of this section. For
Claus units that use only ambient air in
the Claus burner or that elect not to
monitor O2 concentration of the air/
oxygen mixture used in the Claus
burner or for non-Claus sulfur recovery
plants, this SO2 emissions limit is 250
ppmv (dry basis) at zero percent excess
air.
ambient air in the Claus burner or for
non-Claus sulfur recovery plants, this
reduced sulfur compounds emission
limit is 300 ppmv calculated as ppmv
SO2 (dry basis) at 0-percent excess air.
(iii) For a sulfur recovery plant with
a reduction control system not followed
by incineration, the owner or operator
shall not discharge or cause the
discharge of any gases into the
atmosphere containing hydrogen sulfide
(H2S) in excess of 10 ppmv calculated
as ppmv SO2 (dry basis) at zero percent
excess air.
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.000
stain tubes with a maximum span
between 200 and 400 ppmv inclusive
when 1≤N≤5, where N = number of
pump strokes. The owner or operator
must begin monitoring according to the
requirements in paragraph (a)(1) or (2)
of this section as soon as practicable but
in no case later than 180 days after the
operation change. During daily stain
tube sampling, a daily sample exceeding
162 ppmv is an exceedance of the 3hour H2S concentration limit.
*
*
*
*
*
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75231
control system followed by incineration,
the owner or operator shall not
discharge or cause the discharge of any
gases into the atmosphere containing
SO2 in excess of the emission limit
calculated using Equation 2 of this
section. For Claus units that use only
ambient air in the Claus burner or that
elect not to monitor O2 concentration of
the air/oxygen mixture used in the
Claus burner or for non-Claus sulfur
recovery plants, this SO2 emission limit
is 2,500 ppmv (dry basis) at zero percent
excess air.
the sulfur pit, which shall not exceed
240 hours per year. The owner or
operator must document the time
periods during which the sulfur pit
vents were not controlled and measures
taken to minimize emissions during
these periods. Examples of these
measures include not adding fresh
sulfur or shutting off vent fans.
(g) * * *
(1) Except as provided in (g)(1)(iii) of
this section, for each fuel gas
combustion device, the owner or
operator shall comply with either the
emission limit in paragraph (g)(1)(i) of
this section or the fuel gas concentration
limit in paragraph (g)(1)(ii) of this
section. For CO boilers or furnaces that
are part of a fluid catalytic cracking unit
or fluid coking unit affected facility, the
owner or operator shall comply with the
fuel gas concentration limit in
paragraph (g)(1)(ii) for all fuel gas
streams combusted in these units.
*
*
*
*
*
■ 6. Section 60.104a is amended by:
■ a. Revising the first sentence of
paragraph (a) and paragraphs (b), (f)
introductory text, and (h) introductory
text;
■ b. Adding paragraph (h)(6); and
■ c. Removing and reserving paragraphs
(j)(1) through (3).
The revisions and additions read as
follows:
requirement in § 60.103a(h) according to
the requirements of § 60.8. * * *
(b) The owner or operator of a FCCU
or FCU that elects to monitor control
device operating parameters according
to the requirements in § 60.105a(b), to
use bag leak detectors according to the
requirements in § 60.105a(c), or to use
COMS according to the requirements in
§ 60.105a(e) shall conduct a PM
performance test at least annually (i.e.,
once per calendar year, with an interval
of at least 8 months but no more than
16 months between annual tests) and
furnish the Administrator a written
report of the results of each test.
*
*
*
*
*
(f) The owner or operator of an FCCU
or FCU that uses cyclones to comply
with the PM per coke burn-off emissions
limit in § 60.102a(b)(1) shall establish a
site-specific opacity operating limit
according to the procedures in
paragraphs (f)(1) through (3) of this
section.
*
*
*
*
*
(h) The owner or operator shall
determine compliance with the SO2
emissions limits for sulfur recovery
plants in § 60.102a(f)(1)(i) and (f)(2)(i)
and the reduced sulfur compounds and
H2S emissions limits for sulfur recovery
plants in § 60.102a(f)(1)(ii), (f)(1)(iii),
(f)(2)(ii), and (f)(2)(iii) using the
following methods and procedures:
*
*
*
*
*
(6) If oxygen or oxygen-enriched air is
used in the Claus burner and either
Equation 1 or 2 of this subpart is used
to determine the applicable emissions
limit, determine the average O2
concentration of the air/oxygen mixture
supplied to the Claus burner, in percent
by volume (dry basis), for the
performance test using all hourly
average O2 concentrations determined
(ii) For a sulfur recovery plant with a
reduction control system not followed
by incineration, the owner or operator
shall not discharge or cause the
discharge of any gases into the
atmosphere containing reduced sulfur
compounds in excess of the emission
limit calculated using Equation 2 of this
section. For Claus units that use only
ambient air in the Claus burner or for
non-Claus sulfur recovery plants, this
reduced sulfur compounds emission
limit is 3,000 ppmv calculated as ppmv
SO2 (dry basis) at zero percent excess
air.
(iii) For a sulfur recovery plant with
a reduction control system not followed
by incineration, the owner or operator
shall not discharge or cause the
discharge of any gases into the
atmosphere containing H2S in excess of
100 ppmv calculated as ppmv SO2 (dry
basis) at zero percent excess air.
(3) The emission limits in paragraphs
(f)(1) and (2) of this section shall not
apply during periods of maintenance of
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
§ 60.104a
Performance tests.
(a) The owner or operator shall
conduct a performance test for each
FCCU, FCU, sulfur recovery plant and
fuel gas combustion device to
demonstrate initial compliance with
each applicable emissions limit in
§ 60.102a and conduct a performance
test for each flare to demonstrate initial
compliance with the H2S concentration
PO 00000
Frm 00055
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.001
§ 60.106a(a)(7); if flow is not monitored
as specified in § 60.106a(a)(7), the
owner or operator shall comply with the
applicable emission limit in paragraph
(f)(2)(i) or (ii) for each process train or
release point individually. For a sulfur
recovery plant with a design production
capacity of 20 LTD or less and a
reduction control system not followed
by incineration, the owner or operator
shall also comply with the H2S emission
limit in paragraph (f)(2)(iii) of this
section for each individual release
point.
(i) For a sulfur recovery plant with an
oxidation control system or a reduction
Where:
ESS = Emission limit for small sulfur recovery
plant, ppmv (as SO2, dry basis at zero
percent excess air);
k1 = Constant factor for emission limit
conversion: k1 = 1 for converting to the
SO2 limit for a sulfur recovery plant with
an oxidation control system or a
reduction control system followed by
incineration and k1 = 1.2 for converting
to the reduced sulfur compounds limit
for a sulfur recovery plant with a
reduction control system not followed by
incineration; and
%O2 = O2 concentration of the air/oxygen
mixture supplied to the Claus burner,
percent by volume (dry basis). If only
ambient air is used in the Claus burner
or if the owner or operator elects not to
monitor O2 concentration of the air/
oxygen mixture used in the Claus burner
or for non-Claus sulfur recovery plants,
use 20.9% for %O2.
tkelley on DSK3SPTVN1PROD with RULES2
(2) For a sulfur recovery plant with a
design production capacity of 20 LTD or
less, the owner or operator shall comply
with the applicable emission limit in
paragraph (f)(2)(i) or (ii) of this section.
If the sulfur recovery plant consists of
multiple process trains or release points,
the owner or operator may comply with
the applicable emission limit for each
process train or release point
individually or comply with the
applicable emission limit in paragraph
(f)(2)(i) or (ii) as a flow rate weighted
average for a group of release points
from the sulfur recovery plant provided
that flow is monitored as specified in
75232
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
during the test runs using the
procedures in § 60.106a(a)(5) or (6).
*
*
*
*
*
■ 7. Section 60.105a is amended by:
■ a. Revising paragraphs (b)(1)(i),
(b)(1)(ii)(A), (b)(2), (h)(1), (h)(3)(i), and
(i)(1);
■ b. Redesignating paragraphs (i)(2)
through (6) as (i)(3) through (7);
■ c. Adding paragraph (i)(2); and
■ d. Revising newly redesignated
paragraph (i)(7).
The revisions and additions read as
follows:
§ 60.105a Monitoring of emissions and
operations for fluid catalytic cracking units
(FCCU) and fluid coking units (FCU).
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
(b) * * *
(1) * * *
(i) For units controlled using an
electrostatic precipitator, the owner or
operator shall use CPMS to measure and
record the hourly average total power
input and secondary current to the
entire system.
(ii) * * *
(A) As an alternative to pressure drop,
the owner or operator of a jet ejector
type wet scrubber or other type of wet
scrubber equipped with atomizing spray
nozzles must conduct a daily check of
the air or water pressure to the spray
nozzles and record the results of each
check. Faulty (e.g., leaking or plugged)
air or water lines must be repaired
within 12 hours of identification of an
abnormal pressure reading.
*
*
*
*
*
(2) For use in determining the coke
burn-off rate for an FCCU or FCU, the
owner or operator shall install, operate,
calibrate, and maintain an instrument
for continuously monitoring the
concentrations of CO2, O2 (dry basis),
and if needed, CO in the exhaust gases
prior to any control or energy recovery
system that burns auxiliary fuels. A CO
monitor is not required for determining
coke burn-off rate when no auxiliary
fuel is burned and a continuous CO
monitor is not required in accordance
with paragraph (h)(3) of this section.
(i) The owner or operator shall install,
operate, and maintain each CO2 and O2
monitor according to Performance
Specification 3 of appendix B to this
part.
(ii) The owner or operator shall
conduct performance evaluations of
each CO2 and O2 monitor according to
the requirements in § 60.13(c) and
Performance Specification 3 of
appendix B to this part. The owner or
operator shall use Method 3 of appendix
A–3 to this part for conducting the
relative accuracy evaluations.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(iii) If a CO monitor is required, the
owner or operator shall install, operate,
and maintain each CO monitor
according to Performance Specification
4 or 4A of appendix B to this part. If this
CO monitor also serves to demonstrate
compliance with the CO emissions limit
in § 60.102a(b)(4), the span value for
this instrument is 1,000 ppm; otherwise,
the span value for this instrument
should be set at approximately 2 times
the typical CO concentration expected
in the FCCU of FCU flue gas prior to any
emission control or energy recovery
system that burns auxiliary fuels.
(iv) If a CO monitor is required, the
owner or operator shall conduct
performance evaluations of each CO
monitor according to the requirements
in § 60.13(c) and Performance
Specification 4 of appendix B to this
part. The owner or operator shall use
Method 10, 10A, or 10B of appendix A–
3 to this part for conducting the relative
accuracy evaluations.
(v) The owner or operator shall
comply with the quality assurance
requirements of procedure 1 of
appendix F to this part, including
quarterly accuracy determinations for
CO2 and CO monitors, annual accuracy
determinations for O2 monitors, and
daily calibration drift tests.
*
*
*
*
*
(h) * * *
(1) The owner or operator shall
install, operate, and maintain each CO
monitor according to Performance
Specification 4 or 4A of appendix B to
this part. The span value for this
instrument is 1,000 ppmv CO.
*
*
*
*
*
(3) * * *
(i) The demonstration shall consist of
continuously monitoring CO emissions
for 30 days using an instrument that
meets the requirements of Performance
Specification 4 or 4A of appendix B to
this part. The span value shall be 100
ppmv CO instead of 1,000 ppmv, and
the relative accuracy limit shall be 10
percent of the average CO emissions or
5 ppmv CO, whichever is greater. For
instruments that are identical to Method
10 of appendix A–4 to this part and
employ the sample conditioning system
of Method 10A of appendix A–4 to this
part, the alternative relative accuracy
test procedure in section 10.1 of
Performance Specification 2 of
appendix B to this part may be used in
place of the relative accuracy test.
*
*
*
*
*
(i) * * *
(1) If a CPMS is used according to
paragraph (b)(1) of this section, all 3hour periods during which the average
PM control device operating
PO 00000
Frm 00056
Fmt 4701
Sfmt 4700
characteristics, as measured by the
continuous monitoring systems under
paragraph (b)(1), fall below the levels
established during the performance test.
If the alternative to pressure drop CPMS
is used for the owner or operator of a jet
ejector type wet scrubber or other type
of wet scrubber equipped with
atomizing spray nozzles, each day in
which abnormal pressure readings are
not corrected within 12 hours of
identification.
(2) If a bag leak detection system is
used according to paragraph (c) of this
section, each day in which the cause of
an alarm is not alleviated within the
time period specified in paragraph (c)(3)
of this section.
*
*
*
*
*
(7) All 1-hour periods during which
the average CO concentration as
measured by the CO continuous
monitoring system under paragraph (h)
of this section exceeds 500 ppmv or, if
applicable, all 1-hour periods during
which the average temperature and O2
concentration as measured by the
continuous monitoring systems under
paragraph (h)(4) of this section fall
below the operating limits established
during the performance test.
■ 8. Section 60.106a is amended by:
■ a. Revising paragraph (a)(1)(i);
■ b. Adding paragraphs (a)(1)(iv)
through (vii);
■ c. Revising paragraphs (a)(2)
introductory text, (a)(2)(i) and (ii), and
the first sentence of paragraph (a)(2)(iii);
■ d. Removing paragraphs (a)(2)(iv) and
(v);
■ e. Redesignating paragraphs (a)(2)(vi)
through (ix) as (a)(2)(iv) through (vii);
■ f. Revising the first sentence of
paragraph (a)(3) introductory text and
paragraph (a)(3)(i);
■ g. Adding paragraphs (a)(4) through
(7); and
■ h. Revising paragraphs (b)(2) and (3).
The revisions and additions read as
follows:
§ 60.106a Monitoring of emissions and
operations for sulfur recovery plants.
(a) * * *
(1) * * *
(i) The span value for the SO2 monitor
is two times the applicable SO2
emission limit at the highest O2
concentration in the air/oxygen stream
used in the Claus burner, if applicable.
*
*
*
*
*
(iv) The owner or operator shall
install, operate, and maintain each O2
monitor according to Performance
Specification 3 of appendix B to this
part.
(v) The span value for the O2 monitor
must be selected between 10 and 25
percent, inclusive.
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
(vi) The owner or operator shall
conduct performance evaluations for the
O2 monitor according to the
requirements of § 60.13(c) and
Performance Specification 3 of
appendix B to this part. The owner or
operator shall use Methods 3, 3A, or 3B
of appendix A–2 to this part for
conducting the relative accuracy
evaluations. The method ANSI/ASME
PTC 19.10–1981 (incorporated by
reference—see § 60.17) is an acceptable
alternative to EPA Method 3B of
appendix A–2 to this part.
(vii) The owner or operator shall
comply with the applicable quality
assurance procedures of appendix F to
this part for each monitor, including
annual accuracy determinations for each
O2 monitor, and daily calibration drift
determinations.
(2) For sulfur recovery plants that are
subject to the reduced sulfur
compounds emission limit in
§ 60.102a(f)(1)(ii) or (f)(2)(ii), the owner
or operator shall install, operate,
calibrate, and maintain an instrument
for continuously monitoring and
recording the concentration of reduced
sulfur compounds and O2 emissions
into the atmosphere. The reduced sulfur
compounds emissions shall be
calculated as SO2 (dry basis, zero
percent excess air).
(i) The span value for the reduced
sulfur compounds monitor is two times
the applicable reduced sulfur
compounds emission limit as SO2 at the
highest O2 concentration in the air/
oxygen stream used in the Claus burner,
if applicable.
(ii) The owner or operator shall
install, operate, and maintain each
reduced sulfur compounds CEMS
according to Performance Specification
5 of appendix B to this part.
(iii) The owner or operator shall
conduct performance evaluations of
each reduced sulfur compounds
monitor according to the requirements
in § 60.13(c) and Performance
Specification 5 of appendix B to this
part. * * *
*
*
*
*
*
(3) In place of the reduced sulfur
compounds monitor required in
paragraph (a)(2) of this section, the
owner or operator may install, calibrate,
operate, and maintain an instrument
using an air or O2 dilution and
oxidation system to convert any reduced
sulfur to SO2 for continuously
monitoring and recording the
concentration (dry basis, 0 percent
excess air) of the total resultant SO2.
* * *
(i) The span value for this monitor is
two times the applicable reduced sulfur
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
compounds emission limit as SO2 at the
highest O2 concentration in the air/
oxygen stream used in the Claus burner,
if applicable.
*
*
*
*
*
(4) For sulfur recovery plants that are
subject to the H2S emission limit in
§ 60.102a(f)(1)(iii) or (f)(2)(iii), the
owner or operator shall install, operate,
calibrate, and maintain an instrument
for continuously monitoring and
recording the concentration of H2S, and
O2 emissions into the atmosphere. The
H2S emissions shall be calculated as
SO2 (dry basis, zero percent excess air).
(i) The span value for this monitor is
two times the applicable H2S emission
limit.
(ii) The owner or operator shall
install, operate, and maintain each H2S
CEMS according to Performance
Specification 7 of appendix B to this
part.
(iii) The owner or operator shall
conduct performance evaluations for
each H2S monitor according to the
requirements of § 60.13(c) and
Performance Specification 7 of
appendix B to this part. The owner or
operator shall use Methods 11 or 15 of
appendix A–5 to this part or Method 16
of appendix A–6 to this part for
conducting the relative accuracy
evaluations. The method ANSI/ASME
PTC 19.10–1981 (incorporated by
reference—see § 60.17) is an acceptable
alternative to EPA Method 15A of
appendix A–5 to this part.
(iv) The owner or operator shall
install, operate, and maintain each O2
monitor according to Performance
Specification 3 of appendix B to this
part.
(v) The span value for the O2 monitor
must be selected between 10 and 25
percent, inclusive.
(vi) The owner or operator shall
conduct performance evaluations for the
O2 monitor according to the
requirements of § 60.13(c) and
Performance Specification 3 of
appendix B to this part. The owner or
operator shall use Methods 3, 3A, or 3B
of appendix A–2 to this part for
conducting the relative accuracy
evaluations. The method ANSI/ASME
PTC 19.10–1981 (incorporated by
reference—see § 60.17) is an acceptable
alternative to EPA Method 3B of
appendix A–2 to this part.
(vii) The owner or operator shall
comply with the applicable quality
assurance procedures of appendix F to
this part for each monitor, including
annual accuracy determinations for each
O2 monitor, and daily calibration drift
determinations.
(5) For sulfur recovery plants that use
oxygen or oxygen enriched air in the
PO 00000
Frm 00057
Fmt 4701
Sfmt 4700
75233
Claus burner and that elects to monitor
O2 concentration of the air/oxygen
mixture supplied to the Claus burner,
the owner or operator shall install,
operate, calibrate, and maintain an
instrument for continuously monitoring
and recording the O2 concentration of
the air/oxygen mixture supplied to the
Claus burner in order to determine the
allowable emissions limit.
(i) The owner or operator shall install,
operate, and maintain each O2 monitor
according to Performance Specification
3 of appendix B to this part.
(ii) The span value for the O2 monitor
shall be 100 percent.
(iii) The owner or operator shall
conduct performance evaluations for the
O2 monitor according to the
requirements of § 60.13(c) and
Performance Specification 3 of
appendix B to this part. The owner or
operator shall use Methods 3, 3A, or 3B
of appendix A–2 to this part for
conducting the relative accuracy
evaluations. The method ANSI/ASME
PTC 19.10–1981 (incorporated by
reference—see § 60.17) is an acceptable
alternative to EPA Method 3B of
appendix A–2 to this part.
(iv) The owner or operator shall
comply with the applicable quality
assurance procedures of appendix F to
this part for each monitor, including
annual accuracy determinations for each
O2 monitor, and daily calibration drift
determinations.
(v) The owner or operator shall use
the hourly average O2 concentration
from this monitor for use in Equation 1
or 2 of § 60.102a(f), as applicable, for
each hour and determine the allowable
emission limit as the arithmetic average
of 12 contiguous 1-hour averages (i.e.,
the rolling 12-hour average).
(6) As an alternative to the O2 monitor
required in paragraph (a)(5) of this
section, the owner or operator may
install, calibrate, operate, and maintain
a CPMS to measure and record the
volumetric gas flow rate of ambient air
and oxygen-enriched gas supplied to the
Claus burner and calculate the hourly
average O2 concentration of the air/
oxygen mixture used in the Claus
burner as specified in paragraphs
(a)(6)(i) through (iv) of this section in
order to determine the allowable
emissions limit as specified in
paragraphs (a)(6)(v) of this section.
(i) The owner or operator shall install,
calibrate, operate and maintain each
flow monitor according to the
manufacturer’s procedures and
specifications and the following
requirements.
(A) Locate the monitor in a position
that provides a representative
measurement of the total gas flow rate.
E:\FR\FM\01DER2.SGM
01DER2
75234
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
monitor for physical and operational
integrity and all electrical connections
for oxidation and galvanic corrosion if
the flow monitor is not equipped with
a redundant flow sensor.
(E) Recalibrate the flow monitor in
accordance with the manufacturer’s
procedures and specifications biennially
(every two years) or at the frequency
specified by the manufacturer.
(ii) The owner or operator shall use
20.9 percent as the oxygen content of
the ambient air.
(iii) The owner or operator shall use
product specifications (e.g., as reported
in material safety data sheets) for
percent oxygen for purchased oxygen.
For oxygen produced onsite, the percent
oxygen shall be determined by periodic
measurements or process knowledge.
(iv) The owner or operator shall
calculate the hourly average O2
concentration of the air/oxygen mixture
used in the Claus burner using Equation
10 of this section:
Where:
%O2 = O2 concentration of the air/oxygen
mixture used in the Claus burner,
percent by volume (dry basis);
20.9 = O2 concentration in air, percent dry
basis;
Qair = Volumetric flow rate of ambient air
used in the Claus burner, dscfm;
%O2,oxy = O2 concentration in the enriched
oxygen stream, percent dry basis; and
Qoxy = Volumetric flow rate of enriched
oxygen stream used in the Claus burner,
dscfm.
reduced sulfur compounds emission
limit in § 60.102a(f)(1)(ii) or (f)(2)(ii) as
a flow rate weighted average for a group
of release points from the sulfur
recovery plant rather than for each
process train or release point
individually shall install, calibrate,
operate, and maintain a CPMS to
measure and record the volumetric gas
flow rate of each release point within
the group of release points from the
sulfur recovery plant as specified in
paragraphs (a)(7)(i) through (iv) of this
section.
(i) The owner or operator shall install,
calibrate, operate and maintain each
flow monitor according to the
manufacturer’s procedures and
specifications and the following
requirements.
(A) Locate the monitor in a position
that provides a representative
measurement of the total gas flow rate.
(B) Use a flow sensor meeting an
accuracy requirement of ±5 percent over
the normal range of flow measured or 10
cubic feet per minute, whichever is
greater.
(C) Use a flow monitor that is
maintainable online, is able to
continuously correct for temperature,
pressure, and moisture content, and is
able to record dry flow in standard
conditions (as defined in § 60.2) over
one-minute averages.
(D) At least quarterly, perform a visual
inspection of all components of the
monitor for physical and operational
integrity and all electrical connections
for oxidation and galvanic corrosion if
the flow monitor is not equipped with
a redundant flow sensor.
(E) Recalibrate the flow monitor in
accordance with the manufacturer’s
procedures and specifications biennially
(every two years) or at the frequency
specified by the manufacturer.
(ii) The owner or operator shall
correct the flow to 0 percent excess air
using Equation 11 of this section:
20.9c = 20.9 percent O2¥0.0 percent O2
(defined O2 correction basis), percent;
20.9 = O2 concentration in air, percent; and
%O2 = O2 concentration measured on a dry
basis, percent.
(iii) The owner or operator shall
calculate the flow weighted average SO2
or reduced sulfur compounds
concentration for each hour using
Equation 12 of this section:
(v) The owner or operator shall use
the hourly average O2 concentration
determined using Equation 8 of
§ 60.104a(d)(8) for use in Equation 1 or
2 of § 60.102a(f), as applicable, for each
hour and determine the allowable
emission limit as the arithmetic average
of 12 contiguous 1-hour averages (i.e.,
the rolling 12-hour average).
(7) Owners or operators of a sulfur
recovery plant that elects to comply
with the SO2 emission limit in
§ 60.102a(f)(1)(i) or (f)(2)(i) or the
ER01DE15.003
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00058
Fmt 4701
Sfmt 4725
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.002
tkelley on DSK3SPTVN1PROD with RULES2
Where:
Qadj = Volumetric flow rate adjusted to 0
percent excess air, dry standard cubic
feet per minute (dscfm);
Cmeas = Volumetric flow rate measured by the
flow meter corrected to dry standard
conditions, dscfm;
ER01DE15.004
(B) Use a flow sensor meeting an
accuracy requirement of ±5 percent over
the normal range of flow measured or 10
cubic feet per minute, whichever is
greater.
(C) Use a flow monitor that is
maintainable online, is able to
continuously correct for temperature,
pressure and, for ambient air flow
monitor, moisture content, and is able to
record dry flow in standard conditions
(as defined in § 60.2) over one-minute
averages.
(D) At least quarterly, perform a visual
inspection of all components of the
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
(iv) For sulfur recovery plants that use
oxygen or oxygen enriched air in the
Claus burner, the owner or operator
shall use Equation 10 of this section and
the hourly emission limits determined
in paragraph (a)(5)(v) or (a)(6)(v) of this
section in-place of the pollutant
concentration to determine the flow
weighted average hourly emission limit
for each hour. The allowable emission
limit shall be calculated as the
arithmetic average of 12 contiguous 1hour averages (i.e., the rolling 12-hour
average).
(b) * * *
(2) All 12-hour periods during which
the average concentration of reduced
sulfur compounds (as SO2) as measured
by the reduced sulfur compounds
continuous monitoring system required
under paragraph (a)(2) or (3) of this
section exceeds the applicable emission
limit; or
(3) All 12-hour periods during which
the average concentration of H2S as
measured by the H2S continuous
monitoring system required under
paragraph (a)(4) of this section exceeds
Where:
Fd = F factor on dry basis at 0% excess air,
dscf/MMBtu.
Xi = mole or volume fraction of each
component in the fuel gas.
MEVi = molar exhaust volume, dry
standard cubic feet per mole (dscf/mol).
MHCi = molar heat content, Btu per mole
(Btu/mol).
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
the applicable emission limit (dry basis,
0 percent excess air).
■ 9. Section 60.107a is amended by
revising paragraphs (a)(1)(i) and (ii),
(b)(1)(iv), the first sentence of paragraph
(b)(3)(iii), (d)(3), (e)(1) introductory text,
(e)(1)(ii), (e)(2) introductory text,
(e)(2)(ii), (e)(2)(vi)(C), (e)(3), (f)(1)(ii),
and (h)(5) to read as follows:
§ 60.107a Monitoring of emissions and
operations for fuel gas combustion devices
and flares.
(a) * * *
(1) * * *
(i) The owner or operator shall install,
operate, and maintain each SO2 monitor
according to Performance Specification
2 of appendix B to this part. The span
value for the SO2 monitor is 50 ppmv
SO2.
(ii) The owner or operator shall
conduct performance evaluations for the
SO2 monitor according to the
requirements of § 60.13(c) and
Performance Specification 2 of
appendix B to this part. The owner or
operator shall use Methods 6, 6A, or 6C
of appendix A–4 to this part for
conducting the relative accuracy
evaluations. The method ANSI/ASME
PTC 19.10–1981 (incorporated by
reference—see § 60.17) is an acceptable
alternative to EPA Method 6 or 6A of
appendix A–4 to this part. Samples
taken by Method 6 of appendix A–4 to
this part shall be taken at a flow rate of
approximately 2 liters/min for at least
30 minutes. The relative accuracy limit
shall be 20 percent or 4 ppmv,
whichever is greater, and the calibration
drift limit shall be 5 percent of the
established span value.
*
*
*
*
*
(b) * * *
(1) * * *
(iv) The supporting test results from
sampling the requested fuel gas stream/
system demonstrating that the sulfur
content is less than 5 ppmv H2S.
Sampling data must include, at
1,000,000 = unit conversion, Btu per
MMBtu.
*
*
*
*
*
(e) * * *
(1) Total reduced sulfur monitoring
requirements. The owner or operator
shall install, operate, calibrate and
maintain an instrument or instruments
for continuously monitoring and
recording the concentration of total
PO 00000
Frm 00059
Fmt 4701
Sfmt 4700
minimum, 2 weeks of daily monitoring
(14 grab samples) for frequently
operated fuel gas streams/systems; for
infrequently operated fuel gas streams/
systems, seven grab samples must be
collected unless other additional
information would support reduced
sampling. The owner or operator shall
use detector tubes (‘‘length-of-stain
tube’’ type measurement) following the
‘‘Gas Processors Association Standard
2377–86 (incorporated by reference—
see § 60.17), using tubes with a
maximum span between 10 and 40
ppmv inclusive when 1≤N≤10, where N
= number of pump strokes, to test the
applicant fuel gas stream for H2S; and
*
*
*
*
*
(3) * * *
(iii) If the operation change results in
a sulfur content that is outside the range
of concentrations included in the
original application and the owner or
operator chooses not to submit new
information to support an exemption,
the owner or operator must begin H2S
monitoring using daily stain sampling to
demonstrate compliance using lengthof-stain tubes with a maximum span
between 200 and 400 ppmv inclusive
when 1≤N≤5, where N = number of
pump strokes. * * *
*
*
*
*
*
(d) * * *
(3) As an alternative to the
requirements in paragraph (d)(2) of this
section, the owner or operator of a gasfired process heater shall install, operate
and maintain a gas composition
analyzer and determine the average F
factor of the fuel gas using the factors in
Table 1 of this subpart and Equation 13
of this section. If a single fuel gas system
provides fuel gas to several process
heaters, the F factor may be determined
at a single location in the fuel gas
system provided it is representative of
the fuel gas fed to the affected process
heater(s).
reduced sulfur in gas discharged to the
flare.
*
*
*
*
*
(ii) The owner or operator shall
conduct performance evaluations of
each total reduced sulfur monitor
according to the requirements in
§ 60.13(c) and Performance
Specification 5 of appendix B to this
part. The owner or operator of each total
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.005
Where:
Cave = Flow weighted average concentration
of the pollutant, ppmv (dry basis, zero
percent excess air). The pollutant is
either SO2 (if complying with the SO2
emission limit in § 60.102a(f)(1)(i) or
(f)(2)(i)) or reduced sulfur compounds (if
complying with the reduced sulfur
compounds emission limit in
§ 60.102a(f)(1)(ii) or (f)(2)(ii));
N = Number of release points within the
group of release points from the sulfur
recovery plant for which emissions
averaging is elected;
Cn = Pollutant concentration in the nth release
point within the group of release points
from the sulfur recovery plant for which
emissions averaging is elected, ppmv
(dry basis, zero percent excess air);
Qadj,n = Volumetric flow rate of the nth release
point within the group of release points
from the sulfur recovery plant for which
emissions averaging is elected, dry
standard cubic feet per minute (dscfm,
adjusted to 0 percent excess air).
75235
75236
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
reduced sulfur monitor shall use EPA
Method 15A of appendix A–5 to this
part for conducting the relative accuracy
evaluations. The method ANSI/ASME
PTC 19.10–1981 (incorporated by
reference-see § 60.17) is an acceptable
alternative to EPA Method 15A of
appendix A–5 to this part. The
alternative relative accuracy procedures
described in section 16.0 of Performance
Specification 2 of appendix B to this
part (cylinder gas audits) may be used
for conducting the relative accuracy
evaluations, except that it is not
necessary to include as much of the
sampling probe or sampling line as
practical.
*
*
*
*
*
(2) H2S monitoring requirements. The
owner or operator shall install, operate,
calibrate, and maintain an instrument or
instruments for continuously
monitoring and recording the
concentration of H2S in gas discharged
to the flare according to the
requirements in paragraphs (e)(2)(i)
through (iii) of this section and shall
collect and analyze samples of the gas
and calculate total sulfur concentrations
as specified in paragraphs (e)(2)(iv)
through (ix) of this section.
*
*
*
*
*
(ii) The owner or operator shall
conduct performance evaluations of
each H2S monitor according to the
requirements in § 60.13(c) and
Performance Specification 7 of
appendix B to this part. The owner or
operator shall use EPA Method 11, 15 or
15A of appendix A–5 to this part for
conducting the relative accuracy
evaluations. The method ANSI/ASME
PTC 19.10–1981 (incorporated by
reference—see § 60.17) is an acceptable
alternative to EPA Method 15A of
appendix A–5 to this part. The
alternative relative accuracy procedures
described in section 16.0 of Performance
Specification 2 of appendix B to this
part (cylinder gas audits) may be used
for conducting the relative accuracy
evaluations, except that it is not
necessary to include as much of the
sampling probe or sampling line as
practical.
*
*
*
*
*
(vi) * * *
(C) Determine the acceptable range for
subsequent weekly samples based on
the 95-percent confidence interval for
the distribution of daily ratios based on
the 10 individual daily ratios using
Equation 14 of this section.
Where:
AR = Acceptable range of subsequent ratio
determinations, unitless.
RatioAvg = 10-day average total sulfur-toH2S concentration ratio, unitless.
2.262 = t-distribution statistic for 95percent 2-sided confidence interval for 10
samples (9 degrees of freedom).
SDev = Standard deviation of the 10 daily
average total sulfur-to-H2S concentration
ratios used to develop the 10-day average
total sulfur-to-H2S concentration ratio,
unitless.
requirements in paragraph (a)(1) of this
section, determine the F factor of the
fuel gas at least daily according to the
requirements in paragraphs (d)(2)
through (4) of this section, determine
the higher heating value of the fuel gas
at least daily according to the
requirements in paragraph (d)(7) of this
section, and calculate the total sulfur
content (as SO2) in the fuel gas using
Equation 15 of this section.
*
*
*
*
(f) * * *
(1) * * *
(ii) Use a flow sensor meeting an
accuracy requirement of ±20 percent of
the flow rate at velocities ranging from
0.1 to 1 feet per second and an accuracy
of ±5 percent of the flow rate for
velocities greater than 1 feet per second.
*
*
*
*
*
(h) * * *
(5) Daily O2 limits for fuel gas
combustion devices. Each day during
which the concentration of O2 as
measured by the O2 continuous
monitoring system required under
paragraph (c)(6) or (d)(8) of this section
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
exceeds the O2 operating limit or
operating curve determined during the
most recent biennial performance test.
PART 63—NATIONAL EMISSION
STANDARDS FOR HAZARDOUS AIR
POLLUTANTS FOR SOURCE
CATEGORIES
10. The authority citation for part 63
continues to read as follows:
■
Authority: 42 U.S.C. 7401 et se.
c. Revising newly redesignated
paragraph (h)(78);
■ d. Adding paragraphs (h)(15), (74),
(79), (85), (104) and (j)(2);
■ e. Redesignating paragraph (m)(3)
through (21) as (m)(5) through (23),
respectively, and paragraph (m)(2) as
(m)(3).
■ f. Adding paragraphs (m)(2) and (4)
and (n)(3); and
■ g. Revising paragraph (s)(1).
The revisions and additions read as
follows:
■
Subpart A—General Provisions
§ 63.14
11. Section 63.14 is amended by:
a. Revising paragraph (h)(14);
■ b. Redesignating paragraphs (h)(82)
through (99) as (h)(86) through (103),
paragraphs (h)(77) through (81) as
(h)(80) through (84), paragraphs (h)(73)
through (76) as paragraphs (h)(75)
through (78), and paragraphs (h)(15)
through (72) as (16) through (73),
respectively;
*
■
■
PO 00000
Frm 00060
Fmt 4701
Sfmt 4700
Incorporation by reference.
*
*
*
*
(h) * * *
(14) ASTM D1945–03 (Reapproved
2010), Standard Test Method for
Analysis of Natural Gas by Gas
Chromatography, Approved January 1,
2010, IBR approved for §§ 63.670(j),
63.772(h), and 63.1282(g).
(15) ASTM D1945–14, Standard Test
Method for Analysis of Natural Gas by
Gas Chromatography, Approved
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.007
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
(3) SO2 monitoring requirements. The
owner or operator shall install, operate,
calibrate, and maintain an instrument
for continuously monitoring and
recording the concentration of SO2 from
a process heater or other fuel gas
combustion device that is combusting
gas representative of the fuel gas in the
flare gas line according to the
ER01DE15.006
Where:
TSFG = Total sulfur concentration, as SO2,
in the fuel gas, ppmv.
CSO2 = Concentration of SO2 in the exhaust
gas, ppmv (dry basis at 0-percent excess air).
Fd = F factor gas on dry basis at 0-percent
excess air, dscf/MMBtu.
HHVFG = Higher heating value of the fuel
gas, MMBtu/scf.
*
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
November 1, 2014, IBR approved for
§ 63.670(j).
*
*
*
*
*
(74) ASTM D6196–03 (Reapproved
2009), Standard Practice for Selection of
Sorbents, Sampling, and Thermal
Desorption Analysis Procedures for
Volatile Organic Compounds in Air,
Approved March 1, 2009, IBR approved
for appendix A to this part: Method
325A and Method 325B.
*
*
*
*
*
(78) ASTM D6348–03 (Reapproved
2010), Standard Test Method for
Determination of Gaseous Compounds
by Extractive Direct Interface Fourier
Transform Infrared (FTIR) Spectroscopy,
including Annexes A1 through A8,
Approved October 1, 2010, IBR
approved for § 63.1571(a), tables 4 and
5 to subpart JJJJJ, tables 4 and 6 to
subpart KKKKK, tables 1, 2, and 5 to
subpart UUUUU and appendix B to
subpart UUUUU.
*
*
*
*
*
(79) ASTM D6348–12e1, Standard
Test Method for Determination of
Gaseous Compounds by Extractive
Direct Interface Fourier Transform
Infrared (FTIR) Spectroscopy, Approved
February 1, 2012, IBR approved for
§ 63.1571(a).
*
*
*
*
*
(85) ASTM D6420–99 (Reapproved
2010), Standard Test Method for
Determination of Gaseous Organic
Compounds by Direct Interface Gas
Chromatography-Mass Spectrometry,
Approved October 1, 2010, IBR
approved for § 63.670(j) and appendix A
to this part: Method 325B.
*
*
*
*
*
(104) ASTM UOP539–12, Refinery
Gas Analysis by GC, Copyright 2012 (to
UOP), IBR approved for § 63.670(j).
*
*
*
*
*
(j) * * *
(2) BS EN 14662–4:2005, Ambient air
quality standard method for the
measurement of benzene
concentrations—Part 4: Diffusive
sampling followed by thermal
desorption and gas chromatography,
Published June 27, 2005, IBR approved
for appendix A to this part: Method
325A and Method 325B.
*
*
*
*
*
(m) * * *
(2) EPA–454/B–08–002, Office of Air
Quality Planning and Standards
(OAQPS), Quality Assurance Handbook
for Air Pollution Measurement Systems,
Volume IV: Meteorological
Measurements, Version 2.0 (Final),
March 24, 2008, IBR approved for
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
§ 63.658(d) and appendix A to this part:
Method 325A.
*
*
*
*
*
(4) EPA–454/R–99–005, Office of Air
Quality Planning and Standards
(OAQPS), Meteorological Monitoring
Guidance for Regulatory Modeling
Applications, February 2000, IBR
approved for appendix A to this part:
Method 325A.
*
*
*
*
*
(n) * * *
(3) ISO 16017–2:2003(E): Indoor,
ambient and workplace air—sampling
and analysis of volatile organic
compounds by sorbent tube/thermal
desorption/capillary gas
chromatography—Part 2: Diffusive
sampling, May 15, 2003, IBR approved
for appendix A to this part: Method
325A and Method 325B.
*
*
*
*
*
(s) * * *
(1) ‘‘Air Stripping Method (Modified
El Paso Method) for Determination of
Volatile Organic Compound Emissions
from Water Sources,’’ Revision Number
One, dated January 2003, Sampling
Procedures Manual, Appendix P:
Cooling Tower Monitoring, January 31,
2003, IBR approved for §§ 63.654(c) and
(g), 63.655(i), and 63.11920.
*
*
*
*
*
Subpart Y—National Emission
Standards for Marine Tank Vessel
Loading Operations
12. Section 63.560 is amended by
revising paragraph (a)(4) to read as
follows:
■
§ 63.560 Applicability and designation of
affected source.
(a) * * *
(4) Existing sources with emissions
less than 10 and 25 tons must meet the
submerged fill standards of 46 CFR
153.282.
*
*
*
*
*
Subpart CC—National Emission
Standards for Hazardous Air Pollutants
From Petroleum Refineries
13. Section 63.640 is amended by:
a. Revising paragraphs (a)
introductory text and (c) introductory
text;
■ c. Adding paragraph (c)(9);
■ d. Revising paragraphs (d)(5), (h),
(k)(1), (l) introductory text, (l)(2)
introductory text, (l)(2)(i), (l)(3)
introductory text, (m) introductory text,
(n) introductory text, (n)(1) through (5),
(n)(8) introductory text, and (n)(8)(ii);
■ e. Adding paragraphs (n)(8)(vii) and
(viii);
■ f. Revising paragraph (n)(9)(i);
■
■
PO 00000
Frm 00061
Fmt 4701
Sfmt 4700
75237
g. Adding paragraph (n)(10);
h. Revising paragraph (o)(2)(i)
introductory text;
■ i. Adding paragraph (o)(2)(i)(D);
■ j. Revising paragraph (o)(2)(ii)
introductory text; and
■ k. Adding paragraphs (o)(2)(ii)(C) and
(s).
The revisions and additions read as
follows:
■
■
§ 63.640 Applicability and designation of
affected source.
(a) This subpart applies to petroleum
refining process units and to related
emissions points that are specified in
paragraphs (c)(1) through (9) of this
section that are located at a plant site
and that meet the criteria in paragraphs
(a)(1) and (2) of this section:
*
*
*
*
*
(c) For the purposes of this subpart,
the affected source shall comprise all
emissions points, in combination, listed
in paragraphs (c)(1) through (9) of this
section that are located at a single
refinery plant site.
*
*
*
*
*
(9) All releases associated with the
decoking operations of a delayed coking
unit, as defined in this subpart.
(d) * * *
(5) Emission points routed to a fuel
gas system, as defined in § 63.641,
provided that on and after January 30,
2019, any flares receiving gas from that
fuel gas system are subject to § 63.670.
No other testing, monitoring,
recordkeeping, or reporting is required
for refinery fuel gas systems or emission
points routed to refinery fuel gas
systems.
*
*
*
*
*
(h) Sources subject to this subpart are
required to achieve compliance on or
before the dates specified in table 11 of
this subpart, except as provided in
paragraphs (h)(1) through (3) of this
section.
(1) Marine tank vessels at existing
sources shall be in compliance with this
subpart, except for §§ 63.657 through
63.660, no later than August 18, 1999,
unless the vessels are included in an
emissions average to generate emission
credits. Marine tank vessels used to
generate credits in an emissions average
shall be in compliance with this subpart
no later than August 18, 1998, unless an
extension has been granted by the
Administrator as provided in § 63.6(i).
(2) Existing Group 1 floating roof
storage vessels meeting the applicability
criteria in item 1 of the definition of
Group 1 storage vessel shall be in
compliance with § 63.646 at the first
degassing and cleaning activity after
August 18, 1998, or August 18, 2005,
whichever is first.
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75238
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
(3) An owner or operator may elect to
comply with the provisions of
§ 63.648(c) through (i) as an alternative
to the provisions of § 63.648(a) and (b).
In such cases, the owner or operator
shall comply no later than the dates
specified in paragraphs (h)(3)(i) through
(iii) of this section.
(i) Phase I (see table 2 of this subpart),
beginning on August 18, 1998;
(ii) Phase II (see table 2 of this
subpart), beginning no later than August
18, 1999; and
(iii) Phase III (see table 2 of this
subpart), beginning no later than
February 18, 2001.
*
*
*
*
*
(k) * * *
(1) The reconstructed source,
addition, or change shall be in
compliance with the new source
requirements in item (1), (2), or (3) of
table 11 of this subpart, as applicable,
upon initial startup of the reconstructed
source or by August 18, 1995,
whichever is later; and
*
*
*
*
*
(l) If an additional petroleum refining
process unit is added to a plant site or
if a miscellaneous process vent, storage
vessel, gasoline loading rack, marine
tank vessel loading operation, heat
exchange system, or decoking operation
that meets the criteria in paragraphs
(c)(1) through (9) of this section is added
to an existing petroleum refinery or if
another deliberate operational process
change creating an additional Group 1
emissions point(s) (as defined in
§ 63.641) is made to an existing
petroleum refining process unit, and if
the addition or process change is not
subject to the new source requirements
as determined according to paragraph (i)
or (j) of this section, the requirements in
paragraphs (l)(1) through (4) of this
section shall apply. Examples of process
changes include, but are not limited to,
changes in production capacity, or feed
or raw material where the change
requires construction or physical
alteration of the existing equipment or
catalyst type, or whenever there is
replacement, removal, or addition of
recovery equipment. For purposes of
this paragraph (l) and paragraph (m) of
this section, process changes do not
include: Process upsets, unintentional
temporary process changes, and changes
that are within the equipment
configuration and operating conditions
documented in the Notification of
Compliance Status report required by
§ 63.655(f).
*
*
*
*
*
(2) The added emission point(s) and
any emission point(s) within the added
or changed petroleum refining process
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
unit shall be in compliance with the
applicable requirements in item (4) of
table 11 of this subpart by the dates
specified in paragraph (l)(2)(i) or (ii) of
this section.
(i) If a petroleum refining process unit
is added to a plant site or an emission
point(s) is added to any existing
petroleum refining process unit, the
added emission point(s) shall be in
compliance upon initial startup of any
added petroleum refining process unit
or emission point(s) or by the applicable
compliance date in item (4) of table 11
of this subpart, whichever is later.
*
*
*
*
*
(3) The owner or operator of a
petroleum refining process unit or of a
storage vessel, miscellaneous process
vent, wastewater stream, gasoline
loading rack, marine tank vessel loading
operation, heat exchange system, or
decoking operation meeting the criteria
in paragraphs (c)(1) through (9) of this
section that is added to a plant site and
is subject to the requirements for
existing sources shall comply with the
reporting and recordkeeping
requirements that are applicable to
existing sources including, but not
limited to, the reports listed in
paragraphs (l)(3)(i) through (vii) of this
section. A process change to an existing
petroleum refining process unit shall be
subject to the reporting requirements for
existing sources including, but not
limited to, the reports listed in
paragraphs (l)(3)(i) through (vii) of this
section. The applicable reports include,
but are not limited to:
*
*
*
*
*
(m) If a change that does not meet the
criteria in paragraph (l) of this section
is made to a petroleum refining process
unit subject to this subpart, and the
change causes a Group 2 emission point
to become a Group 1 emission point (as
defined in § 63.641), then the owner or
operator shall comply with the
applicable requirements of this subpart
for existing sources, as specified in item
(4) of table 11 of this subpart, for the
Group 1 emission point as expeditiously
as practicable, but in no event later than
3 years after the emission point becomes
Group 1.
*
*
*
*
*
(n) Overlap of this subpart with other
regulations for storage vessels. As
applicable, paragraphs (n)(1), (3), (4),
(6), and (7) of this section apply for
Group 2 storage vessels and paragraphs
(n)(2) and (5) of this section apply for
Group 1 storage vessels.
(1) After the compliance dates
specified in paragraph (h) of this
section, a Group 2 storage vessel that is
subject to the provisions of 40 CFR part
PO 00000
Frm 00062
Fmt 4701
Sfmt 4700
60, subpart Kb, is required to comply
only with the requirements of 40 CFR
part 60, subpart Kb, except as provided
in paragraph (n)(8) of this section. After
the compliance dates specified in
paragraph (h) of this section, a Group 2
storage vessel that is subject to the
provisions of 40 CFR part 61, subpart Y,
is required to comply only with the
requirements of 40 CFR part 61, subpart
Y, except as provided in paragraph
(n)(10) of this section.
(2) After the compliance dates
specified in paragraph (h) of this
section, a Group 1 storage vessel that is
also subject to 40 CFR part 60, subpart
Kb, is required to comply only with
either 40 CFR part 60, subpart Kb,
except as provided in paragraph (n)(8)
of this section or this subpart. After the
compliance dates specified in paragraph
(h) of this section, a Group 1 storage
vessel that is also subject to 40 CFR part
61, subpart Y, is required to comply
only with either 40 CFR part 61, subpart
Y, except as provided in paragraph
(n)(10) of this section or this subpart.
(3) After the compliance dates
specified in paragraph (h) of this
section, a Group 2 storage vessel that is
part of a new source and is subject to
40 CFR 60.110b, but is not required to
apply controls by 40 CFR 60.110b or
60.112b, is required to comply only
with this subpart.
(4) After the compliance dates
specified in paragraph (h) of this
section, a Group 2 storage vessel that is
part of a new source and is subject to
40 CFR 61.270, but is not required to
apply controls by 40 CFR 61.271, is
required to comply only with this
subpart.
(5) After the compliance dates
specified in paragraph (h) of this
section, a Group 1 storage vessel that is
also subject to the provisions of 40 CFR
part 60, subpart K or Ka, is required to
only comply with the provisions of this
subpart.
*
*
*
*
*
(8) Storage vessels described by
paragraph (n)(1) of this section are to
comply with 40 CFR part 60, subpart
Kb, except as provided in paragraphs
(n)(8)(i) through (vi) of this section.
Storage vessels described by paragraph
(n)(2) electing to comply with part 60,
subpart Kb of this chapter shall comply
with subpart Kb except as provided in
paragraphs (n)(8)(i) through (viii) of this
section.
*
*
*
*
*
(ii) If the owner or operator
determines that it is unsafe to perform
the seal gap measurements required in
§ 60.113b(b) of this chapter or to inspect
the vessel to determine compliance with
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
§ 60.113b(a) of this chapter because the
roof appears to be structurally unsound
and poses an imminent danger to
inspecting personnel, the owner or
operator shall comply with the
requirements in either § 63.120(b)(7)(i)
or (ii) of subpart G (only up to the
compliance date specified in paragraph
(h) of this section for compliance with
§ 63.660, as applicable) or either
§ 63.1063(c)(2)(iv)(A) or (B) of subpart
WW.
*
*
*
*
*
(vii) To be in compliance with
§ 60.112b(a)(1)(iv) or (a)(2)(ii) of this
chapter, guidepoles in floating roof
storage vessels must be equipped with
covers and/or controls (e.g., pole float
system, pole sleeve system, internal
sleeve system or flexible enclosure
system) as appropriate to comply with
the ‘‘no visible gap’’ requirement.
(viii) If a flare is used as a control
device for a storage vessel, on and after
January 30, 2019, the owner or operator
must meet the requirements of § 63.670
instead of the requirements referenced
from part 60, subpart Kb of this chapter
for that flare.
(9) * * *
(i) If the owner or operator determines
that it is unsafe to perform the seal gap
measurements required in
§ 60.113a(a)(1) of this chapter because
the floating roof appears to be
structurally unsound and poses an
imminent danger to inspecting
personnel, the owner or operator shall
comply with the requirements in either
§ 63.120(b)(7)(i) or (ii) of subpart G (only
up to the compliance date specified in
paragraph (h) of this section for
compliance with § 63.660, as applicable)
or either § 63.1063(c)(2)(iv)(A) or (B) of
subpart WW.
*
*
*
*
*
(10) Storage vessels described by
paragraph (n)(1) of this section are to
comply with 40 CFR part 61, subpart Y,
except as provided in paragraphs
(n)(10)(i) through (vi) of this section.
Storage vessels described by paragraph
(n)(2) electing to comply with 40 CFR
part 61, subpart Y, shall comply with
subpart Y except as provided for in
paragraphs (n)(10)(i) through (viii) of
this section.
(i) Storage vessels that are to comply
with § 61.271(b) of this chapter are
exempt from the secondary seal
requirements of § 61.271(b)(2)(ii) of this
chapter during the gap measurements
for the primary seal required by
§ 61.272(b) of this chapter.
(ii) If the owner or operator
determines that it is unsafe to perform
the seal gap measurements required in
§ 61.272(b) of this chapter or to inspect
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
the vessel to determine compliance with
§ 61.272(a) of this chapter because the
roof appears to be structurally unsound
and poses an imminent danger to
inspecting personnel, the owner or
operator shall comply with the
requirements in either § 63.120(b)(7)(i)
or (ii) of subpart G (only up to the
compliance date specified in paragraph
(h) of this section for compliance with
§ 63.660, as applicable) or either
§ 63.1063(c)(2)(iv)(A) or (B) of subpart
WW.
(iii) If a failure is detected during the
inspections required by § 61.272(a)(2) of
this chapter or during the seal gap
measurements required by § 61.272(b)(1)
of this chapter, and the vessel cannot be
repaired within 45 days and the vessel
cannot be emptied within 45 days, the
owner or operator may utilize up to two
extensions of up to 30 additional
calendar days each. The owner or
operator is not required to provide a
request for the extension to the
Administrator.
(iv) If an extension is utilized in
accordance with paragraph (n)(10)(iii) of
this section, the owner or operator shall,
in the next periodic report, identify the
vessel, provide the information listed in
§ 61.272(a)(2) or (b)(4)(iii) of this
chapter, and describe the nature and
date of the repair made or provide the
date the storage vessel was emptied.
(v) Owners and operators of storage
vessels complying with 40 CFR part 61,
subpart Y, may submit the inspection
reports required by § 61.275(a), (b)(1),
and (d) of this chapter as part of the
periodic reports required by this
subpart, rather than within the 60-day
period specified in § 61.275(a), (b)(1),
and (d) of this chapter.
(vi) The reports of rim seal
inspections specified in § 61.275(d) of
this chapter are not required if none of
the measured gaps or calculated gap
areas exceed the limitations specified in
§ 61.272(b)(4) of this chapter.
Documentation of the inspections shall
be recorded as specified in § 61.276(a) of
this chapter.
(vii) To be in compliance with
§ 61.271(a)(6) or (b)(3) of this chapter,
guidepoles in floating roof storage
vessels must be equipped with covers
and/or controls (e.g., pole float system,
pole sleeve system, internal sleeve
system or flexible enclosure system) as
appropriate to comply with the ‘‘no
visible gap’’ requirement.
(viii) If a flare is used as a control
device for a storage vessel, on and after
January 30, 2019, the owner or operator
must meet the requirements of § 63.670
instead of the requirements referenced
from part 61, subpart Y of this chapter
for that flare.
PO 00000
Frm 00063
Fmt 4701
Sfmt 4700
75239
(o) * * *
(2) * * *
(i) Comply with paragraphs
(o)(2)(i)(A) through (D) of this section.
*
*
*
*
*
(D) If a flare is used as a control
device, on and after January 30, 2019,
the flare shall meet the requirements of
§ 63.670. Prior to January 30, 2019, the
flare shall meet the applicable
requirements of 40 CFR part 61, subpart
FF, and subpart G of this part, or the
requirements of § 63.670.
(ii) Comply with paragraphs
(o)(2)(ii)(A) through (C) of this section.
*
*
*
*
*
(C) If a flare is used as a control
device, on and after January 30, 2019,
the flare shall meet the requirements of
§ 63.670. Prior to January 30, 2019, the
flare shall meet the applicable
requirements of 40 CFR part 61, subpart
FF, and subpart G of this part, or the
requirements of § 63.670.
*
*
*
*
*
(s) Overlap of this subpart with other
regulation for flares. On January 30,
2019, flares that are subject to the
provisions of 40 CFR 60.18 or 63.11 and
subject to this subpart are required to
comply only with the provisions
specified in this subpart. Prior to
January 30, 2019, flares that are subject
to the provisions of 40 CFR 60.18 or
63.11 and elect to comply with the
requirements in §§ 63.670 and 63.671
are required to comply only with the
provisions specified in this subpart.
■ 14. Section 63.641 is amended by:
■ a. Adding, in alphabetical order,
definitions of ‘‘Assist air,’’ ‘‘Assist
steam,’’ ‘‘Center steam,’’ ‘‘Closed
blowdown system,’’ ‘‘Combustion
zone,’’ ‘‘Combustion zone gas,’’
‘‘Decoking operations,’’ ‘‘Delayed coking
unit,’’ ‘‘Flare,’’ ‘‘Flare purge gas,’’ ‘‘Flare
supplemental gas,’’ ‘‘Flare sweep gas,’’
‘‘Flare vent gas,’’ ‘‘Flexible enclosure
device,’’ ‘‘Force majeure event,’’ ‘‘Lower
steam,’’ ‘‘Net heating value,’’ ‘‘Perimeter
assist air,’’ ‘‘Pilot gas,’’ ‘‘Premix assist
air,’’ ‘‘Regulated material,’’ ‘‘Thermal
expansion relief valve,’’ ‘‘Total steam,’’
and ‘‘Upper steam’’; and
■ b. Revising the definitions of
‘‘Delayed coker vent,’’ ‘‘Emission
point,’’ ‘‘Group 1 storage vessel,’’
‘‘Miscellaneous process vent,’’
‘‘Periodically discharged,’’ and
‘‘Reference control technology for
storage vessels.’’
The revisions and additions read as
follows:
§ 63.641
Definitions.
*
*
*
*
*
Assist air means all air that
intentionally is introduced prior to or at
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75240
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
a flare tip through nozzles or other
hardware conveyance for the purposes
including, but not limited to, protecting
the design of the flare tip, promoting
turbulence for mixing or inducing air
into the flame. Assist air includes
premix assist air and perimeter assist
air. Assist air does not include the
surrounding ambient air.
Assist steam means all steam that
intentionally is introduced prior to or at
a flare tip through nozzles or other
hardware conveyance for the purposes
including, but not limited to, protecting
the design of the flare tip, promoting
turbulence for mixing or inducing air
into the flame. Assist steam includes,
but is not necessarily limited to, center
steam, lower steam and upper steam.
*
*
*
*
*
Center steam means the portion of
assist steam introduced into the stack of
a flare to reduce burnback.
Closed blowdown system means a
system used for depressuring process
vessels that is not open to the
atmosphere and is configured of piping,
ductwork, connections, accumulators/
knockout drums, and, if necessary, flow
inducing devices that transport gas or
vapor from process vessel to a control
device or back into the process.
*
*
*
*
*
Combustion zone means the area of
the flare flame where the combustion
zone gas combines for combustion.
Combustion zone gas means all gases
and vapors found just after a flare tip.
This gas includes all flare vent gas, total
steam, and premix air.
*
*
*
*
*
Decoking operations means the
sequence of steps conducted at the end
of the delayed coking unit’s cooling
cycle to open the coke drum to the
atmosphere in order to remove coke
from the coke drum. Decoking
operations begin at the end of the
cooling cycle when steam released from
the coke drum is no longer discharged
via the unit’s blowdown system but
instead is vented directly to the
atmosphere. Decoking operations
include atmospheric depressuring
(venting), deheading, draining, and
decoking (coke cutting).
Delayed coker vent means a
miscellaneous process vent that
contains uncondensed vapors from the
delayed coking unit’s blowdown
system. Venting from the delayed coker
vent is typically intermittent in nature,
and occurs primarily during the cooling
cycle of a delayed coking unit coke
drum when vapor from the coke drums
cannot be sent to the fractionator
column for product recovery. The
emissions from the decoking operations,
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
which include direct atmospheric
venting, deheading, draining, or
decoking (coke cutting), are not
considered to be delayed coker vents.
Delayed coking unit means a refinery
process unit in which high molecular
weight petroleum derivatives are
thermally cracked and petroleum coke
is produced in a series of closed, batch
system reactors. A delayed coking unit
includes, but is not limited to, all of the
coke drums associated with a single
fractionator; the fractionator, including
the bottoms receiver and the overhead
condenser; the coke drum cutting water
and quench system, including the jet
pump and coker quench water tank; and
the coke drum blowdown recovery
compressor system.
*
*
*
*
*
Emission point means an individual
miscellaneous process vent, storage
vessel, wastewater stream, equipment
leak, decoking operation or heat
exchange system associated with a
petroleum refining process unit; an
individual storage vessel or equipment
leak associated with a bulk gasoline
terminal or pipeline breakout station
classified under Standard Industrial
Classification code 2911; a gasoline
loading rack classified under Standard
Industrial Classification code 2911; or a
marine tank vessel loading operation
located at a petroleum refinery.
*
*
*
*
*
Flare means a combustion device
lacking an enclosed combustion
chamber that uses an uncontrolled
volume of ambient air to burn gases. For
the purposes of this rule, the definition
of flare includes, but is not necessarily
limited to, air-assisted flares, steamassisted flares and non-assisted flares.
Flare purge gas means gas introduced
between a flare header’s water seal and
the flare tip to prevent oxygen
infiltration (backflow) into the flare tip.
For a flare with no water seal, the
function of flare purge gas is performed
by flare sweep gas and, therefore, by
definition, such a flare has no flare
purge gas.
Flare supplemental gas means all gas
introduced to the flare in order to
improve the combustible characteristics
of combustion zone gas.
Flare sweep gas means, for a flare
with a flare gas recovery system, the gas
intentionally introduced into the flare
header system to maintain a constant
flow of gas through the flare header in
order to prevent oxygen buildup in the
flare header; flare sweep gas in these
flares is introduced prior to and
recovered by the flare gas recovery
system. For a flare without a flare gas
recovery system, flare sweep gas means
PO 00000
Frm 00064
Fmt 4701
Sfmt 4700
the gas intentionally introduced into the
flare header system to maintain a
constant flow of gas through the flare
header and out the flare tip in order to
prevent oxygen buildup in the flare
header and to prevent oxygen
infiltration (backflow) into the flare tip.
Flare vent gas means all gas found just
prior to the flare tip. This gas includes
all flare waste gas (i.e., gas from facility
operations that is directed to a flare for
the purpose of disposing of the gas), that
portion of flare sweep gas that is not
recovered, flare purge gas and flare
supplemental gas, but does not include
pilot gas, total steam or assist air.
Flexible enclosure device means a seal
made of an elastomeric fabric (or other
material) which completely encloses a
slotted guidepole or ladder and
eliminates the vapor emission pathway
from inside the storage vessel through
the guidepole slots or ladder slots to the
outside air.
*
*
*
*
*
Force majeure event means a release
of HAP, either directly to the
atmosphere from a relief valve or
discharged via a flare, that is
demonstrated to the satisfaction of the
Administrator to result from an event
beyond the refinery owner or operator’s
control, such as natural disasters; acts of
war or terrorism; loss of a utility
external to the refinery (e.g., external
power curtailment), excluding power
curtailment due to an interruptible
service agreement; and fire or explosion
originating at a near or adjoining facility
outside of the refinery owner or
operator’s control that impacts the
refinery’s ability to operate.
*
*
*
*
*
Group 1 storage vessel means:
(1) Prior to February 1, 2016:
(i) A storage vessel at an existing
source that has a design capacity greater
than or equal to 177 cubic meters and
stored-liquid maximum true vapor
pressure greater than or equal to 10.4
kilopascals and stored-liquid annual
average true vapor pressure greater than
or equal to 8.3 kilopascals and annual
average HAP liquid concentration
greater than 4 percent by weight total
organic HAP;
(ii) A storage vessel at a new source
that has a design storage capacity greater
than or equal to 151 cubic meters and
stored-liquid maximum true vapor
pressure greater than or equal to 3.4
kilopascals and annual average HAP
liquid concentration greater than 2
percent by weight total organic HAP; or
(iii) A storage vessel at a new source
that has a design storage capacity greater
than or equal to 76 cubic meters and
less than 151 cubic meters and stored-
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
liquid maximum true vapor pressure
greater than or equal to 77 kilopascals
and annual average HAP liquid
concentration greater than 2 percent by
weight total organic HAP.
(2) On and after February 1, 2016:
(i) A storage vessel at an existing
source that has a design capacity greater
than or equal to 151 cubic meters
(40,000 gallons) and stored-liquid
maximum true vapor pressure greater
than or equal to 5.2 kilopascals (0.75
pounds per square inch) and annual
average HAP liquid concentration
greater than 4 percent by weight total
organic HAP;
(ii) A storage vessel at an existing
source that has a design storage capacity
greater than or equal to 76 cubic meters
(20,000 gallons) and less than 151 cubic
meters (40,000 gallons) and storedliquid maximum true vapor pressure
greater than or equal to 13.1 kilopascals
(1.9 pounds per square inch) and annual
average HAP liquid concentration
greater than 4 percent by weight total
organic HAP;
(iii) A storage vessel at a new source
that has a design storage capacity greater
than or equal to 151 cubic meters
(40,000 gallons) and stored-liquid
maximum true vapor pressure greater
than or equal to 3.4 kilopascals (0.5
pounds per square inch) and annual
average HAP liquid concentration
greater than 2 percent by weight total
organic HAP; or
(iv) A storage vessel at a new source
that has a design storage capacity greater
than or equal to 76 cubic meters (20,000
gallons) and less than 151 cubic meters
(40,000 gallons) and stored-liquid
maximum true vapor pressure greater
than or equal to 13.1 kilopascals (1.9
pounds per square inch) and annual
average HAP liquid concentration
greater than 2 percent by weight total
organic HAP.
*
*
*
*
*
Lower steam means the portion of
assist steam piped to an exterior annular
ring near the lower part of a flare tip,
which then flows through tubes to the
flare tip, and ultimately exits the tubes
at the flare tip.
*
*
*
*
*
Miscellaneous process vent means a
gas stream containing greater than 20
parts per million by volume organic
HAP that is continuously or periodically
discharged from a petroleum refining
process unit meeting the criteria
specified in § 63.640(a). Miscellaneous
process vents include gas streams that
are discharged directly to the
atmosphere, gas streams that are routed
to a control device prior to discharge to
the atmosphere, or gas streams that are
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
diverted through a product recovery
device prior to control or discharge to
the atmosphere. Miscellaneous process
vents include vent streams from: Caustic
wash accumulators, distillation tower
condensers/accumulators, flash/
knockout drums, reactor vessels,
scrubber overheads, stripper overheads,
vacuum pumps, steam ejectors, hot
wells, high point bleeds, wash tower
overheads, water wash accumulators,
blowdown condensers/accumulators,
and delayed coker vents. Miscellaneous
process vents do not include:
(1) Gaseous streams routed to a fuel
gas system, provided that on and after
January 30, 2019, any flares receiving
gas from the fuel gas system are in
compliance with § 63.670;
(2) Pressure relief device discharges;
(3) Leaks from equipment regulated
under § 63.648;
(4) [Reserved]
(5) In situ sampling systems (onstream
analyzers) until January 30, 2019. After
this date, these sampling systems will
be included in the definition of
miscellaneous process vents;
(6) Catalytic cracking unit catalyst
regeneration vents;
(7) Catalytic reformer regeneration
vents;
(8) Sulfur plant vents;
(9) Vents from control devices such as
scrubbers, boilers, incinerators, and
electrostatic precipitators applied to
catalytic cracking unit catalyst
regeneration vents, catalytic reformer
regeneration vents, and sulfur plant
vents;
(10) Vents from any stripping
operations applied to comply with the
wastewater provisions of this subpart,
subpart G of this part, or 40 CFR part 61,
subpart FF;
(11) Emissions associated with
delayed coking unit decoking
operations;
(12) Vents from storage vessels;
(13) Emissions from wastewater
collection and conveyance systems
including, but not limited to,
wastewater drains, sewer vents, and
sump drains; and
(14) Hydrogen production plant vents
through which carbon dioxide is
removed from process streams or
through which steam condensate
produced or treated within the
hydrogen plant is degassed or deaerated.
Net heating value means the energy
released as heat when a compound
undergoes complete combustion with
oxygen to form gaseous carbon dioxide
and gaseous water (also referred to as
lower heating value).
*
*
*
*
*
Perimeter assist air means the portion
of assist air introduced at the perimeter
PO 00000
Frm 00065
Fmt 4701
Sfmt 4700
75241
of the flare tip or above the flare tip.
Perimeter assist air includes air
intentionally entrained in lower and
upper steam. Perimeter assist air
includes all assist air except premix
assist air.
Periodically discharged means
discharges that are intermittent and
associated with routine operations,
maintenance activities, startups,
shutdowns, malfunctions, or process
upsets.
*
*
*
*
*
Pilot gas means gas introduced into a
flare tip that provides a flame to ignite
the flare vent gas.
*
*
*
*
*
Premix assist air means the portion of
assist air that is introduced to the flare
vent gas, whether injected or induced,
prior to the flare tip. Premix assist air
also includes any air intentionally
entrained in center steam.
*
*
*
*
*
Reference control technology for
storage vessels means either:
(1) For Group 1 storage vessels
complying with § 63.660:
(i) An internal floating roof, including
an external floating roof converted to an
internal floating roof, meeting the
specifications of § 63.1063(a)(1)(i) and
(b);
(ii) An external floating roof meeting
the specifications of § 63.1063(a)(1)(ii),
(a)(2), and (b); or
(iii) [Reserved]
(iv) A closed-vent system to a control
device that reduces organic HAP
emissions by 95 percent, or to an outlet
concentration of 20 parts per million by
volume (ppmv).
(v) For purposes of emissions
averaging, these four technologies are
considered equivalent.
(2) For all other storage vessels:
(i) An internal floating roof meeting
the specifications of § 63.119(b) of
subpart G except for § 63.119(b)(5) and
(6);
(ii) An external floating roof meeting
the specifications of § 63.119(c) of
subpart G except for § 63.119(c)(2);
(iii) An external floating roof
converted to an internal floating roof
meeting the specifications of § 63.119(d)
of subpart G except for § 63.119(d)(2); or
(iv) A closed-vent system to a control
device that reduces organic HAP
emissions by 95 percent, or to an outlet
concentration of 20 parts per million by
volume.
(v) For purposes of emissions
averaging, these four technologies are
considered equivalent.
*
*
*
*
*
Regulated material means any stream
associated with emission sources listed
E:\FR\FM\01DER2.SGM
01DER2
75242
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
in § 63.640(c) required to meet control
requirements under this subpart as well
as any stream for which this subpart or
a cross-referencing subpart specifies that
the requirements for flare control
devices in § 63.670 must be met.
*
*
*
*
*
Thermal expansion relief valve means
a pressure relief valve designed to
protect equipment from excess pressure
due to thermal expansion of blocked
liquid-filled equipment or piping due to
ambient heating or heat from a heat
tracing system. Pressure relief valves
designed to protect equipment from
excess pressure due to blockage against
a pump or compressor or due to fire
contingency are not thermal expansion
relief valves.
*
*
*
*
*
Total steam means the total of all
steam that is supplied to a flare and
includes, but is not limited to, lower
steam, center steam and upper steam.
Upper steam means the portion of
assist steam introduced via nozzles
located on the exterior perimeter of the
upper end of the flare tip.
*
*
*
*
*
■ 15. Section 63.642 is amended by:
■ a. Adding paragraph (b);
■ b. Revising paragraphs (d)(3), (e), (i),
(k) introductory text, (k)(1), (l)
introductory text, and (l)(2); and
■ c. Adding paragraph (n).
The revisions and additions read as
follows:
§ 63.642
General standards.
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
(b) The emission standards set forth in
this subpart shall apply at all times.
*
*
*
*
*
(d) * * *
(3) Performance tests shall be
conducted according to the provisions
of § 63.7(e) except that performance
tests shall be conducted at maximum
representative operating capacity for the
process. During the performance test, an
owner or operator shall operate the
control device at either maximum or
minimum representative operating
conditions for monitored control device
parameters, whichever results in lower
emission reduction. An owner or
operator shall not conduct a
performance test during startup,
shutdown, periods when the control
device is bypassed or periods when the
process, monitoring equipment or
control device is not operating properly.
The owner/operator may not conduct
performance tests during periods of
malfunction. The owner or operator
must record the process information
that is necessary to document operating
conditions during the test and include
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
in such record an explanation to
support that the test was conducted at
maximum representative operating
capacity. Upon request, the owner or
operator shall make available to the
Administrator such records as may be
necessary to determine the conditions of
performance tests.
*
*
*
*
*
(e) All applicable records shall be
maintained as specified in § 63.655(i).
*
*
*
*
*
(i) The owner or operator of an
existing source shall demonstrate
compliance with the emission standard
in paragraph (g) of this section by
following the procedures specified in
paragraph (k) of this section for all
emission points, or by following the
emissions averaging compliance
approach specified in paragraph (l) of
this section for specified emission
points and the procedures specified in
paragraph (k)(1) of this section.
*
*
*
*
*
(k) The owner or operator of an
existing source may comply, and the
owner or operator of a new source shall
comply, with the applicable provisions
in §§ 63.643 through 63.645, 63.646 or
63.660, 63.647, 63.650, and 63.651, as
specified in § 63.640(h).
(1) The owner or operator using this
compliance approach shall also comply
with the requirements of §§ 63.648 and/
or 63.649, 63.654, 63.655, 63.657,
63.658, 63.670 and 63.671, as
applicable.
*
*
*
*
*
(l) The owner or operator of an
existing source may elect to control
some of the emission points within the
source to different levels than specified
under §§ 63.643 through 63.645, 63.646
or 63.660, 63.647, 63.650, and 63.651, as
applicable according to § 63.640(h), by
using an emissions averaging
compliance approach as long as the
overall emissions for the source do not
exceed the emission level specified in
paragraph (g) of this section. The owner
or operator using emissions averaging
shall meet the requirements in
paragraphs (l)(1) and (2) of this section.
*
*
*
*
*
(2) Comply with the requirements of
§§ 63.648 and/or 63.649, 63.654, 63.652,
63.653, 63.655, 63.657, 63.658, 63.670
and 63.671, as applicable.
*
*
*
*
*
(n) At all times, the owner or operator
must operate and maintain any affected
source, including associated air
pollution control equipment and
monitoring equipment, in a manner
consistent with safety and good air
pollution control practices for
PO 00000
Frm 00066
Fmt 4701
Sfmt 4700
minimizing emissions. The general duty
to minimize emissions does not require
the owner operator to make any further
efforts to reduce emissions if levels
required by the applicable standard
have been achieved. Determination of
whether a source is operating in
compliance with operation and
maintenance requirements will be based
on information available to the
Administrator which may include, but
is not limited to, monitoring results,
review of operation and maintenance
procedures, review of operation and
maintenance records, and inspection of
the source.
■ 16. Section 63.643 is amended by
revising paragraphs (a) introductory text
and (a)(1) and adding paragraph (c) to
read as follows:
§ 63.643 Miscellaneous process vent
provisions.
(a) The owner or operator of a Group
1 miscellaneous process vent as defined
in § 63.641 shall comply with the
requirements of either paragraph (a)(1)
or (2) of this section or, if applicable,
paragraph (c) of this section. The owner
or operator of a miscellaneous process
vent that meets the conditions in
paragraph (c) of this section is only
required to comply with the
requirements of paragraph (c) of this
section and § 63.655(g)(13) and (i)(12)
for that vent.
(1) Reduce emissions of organic
HAP’s using a flare. On and after
January 30, 2019, the flare shall meet
the requirements of § 63.670. Prior to
January 30, 2019, the flare shall meet
the requirements of § 63.11(b) of subpart
A or the requirements of § 63.670.
*
*
*
*
*
(c) An owner or operator may
designate a process vent as a
maintenance vent if the vent is only
used as a result of startup, shutdown,
maintenance, or inspection of
equipment where equipment is emptied,
depressurized, degassed or placed into
service. The owner of operator does not
need to designate a maintenance vent as
a Group 1 or Group 2 miscellaneous
process vent. The owner or operator
must comply with the applicable
requirements in paragraphs (c)(1)
through (3) of this section for each
maintenance vent.
(1) Prior to venting to the atmosphere,
process liquids are removed from the
equipment as much as practical and the
equipment is depressured to a control
device, fuel gas system, or back to the
process until one of the following
conditions, as applicable, is met.
(i) The vapor in the equipment served
by the maintenance vent has a lower
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
explosive limit (LEL) of less than 10
percent.
(ii) If there is no ability to measure the
LEL of the vapor in the equipment based
on the design of the equipment, the
pressure in the equipment served by the
maintenance vent is reduced to 5 psig
or less. Upon opening the maintenance
vent, active purging of the equipment
cannot be used until the LEL of the
vapors in the maintenance vent (or
inside the equipment if the maintenance
is a hatch or similar type of opening)
equipment is less than 10 percent.
(iii) The equipment served by the
maintenance vent contains less than 72
pounds of VOC.
(iv) If the maintenance vent is
associated with equipment containing
pyrophoric catalyst (e.g., hydrotreaters
and hydrocrackers) at refineries that do
not have a pure hydrogen supply, the
LEL of the vapor in the equipment must
be less than 20 percent, except for one
event per year not to exceed 35 percent.
(2) Except for maintenance vents
complying with the alternative in
paragraph (c)(1)(iii) of this section, the
owner or operator must determine the
LEL or, if applicable, equipment
pressure using process instrumentation
or portable measurement devices and
follow procedures for calibration and
maintenance according to
manufacturer’s specifications.
(3) For maintenance vents complying
with the alternative in paragraph
(c)(1)(iii) of this section, the owner or
operator shall determine mass of VOC in
the equipment served by the
maintenance vent based on the
equipment size and contents after
considering any contents drained or
purged from the equipment. Equipment
size may be determined from equipment
design specifications. Equipment
contents may be determined using
process knowledge.
■ 17. Section 63.644 is amended by
revising paragraphs (a) introductory
text, (a)(2), and (c) to read as follows:
tkelley on DSK3SPTVN1PROD with RULES2
§ 63.644 Monitoring provisions for
miscellaneous process vents.
(a) Except as provided in paragraph
(b) of this section, each owner or
operator of a Group 1 miscellaneous
process vent that uses a combustion
device to comply with the requirements
in § 63.643(a) shall install the
monitoring equipment specified in
paragraph (a)(1), (2), (3), or (4) of this
section, depending on the type of
combustion device used. All monitoring
equipment shall be installed, calibrated,
maintained, and operated according to
manufacturer’s specifications or other
written procedures that provide
adequate assurance that the equipment
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
will monitor accurately and, except for
CPMS installed for pilot flame
monitoring, must meet the applicable
minimum accuracy, calibration and
quality control requirements specified
in table 13 of this subpart.
*
*
*
*
*
(2) Where a flare is used prior to
January 30, 2019, a device (including
but not limited to a thermocouple, an
ultraviolet beam sensor, or an infrared
sensor) capable of continuously
detecting the presence of a pilot flame
is required, or the requirements of
§ 63.670 shall be met. Where a flare is
used on and after January 30, 2019, the
requirements of § 63.670 shall be met.
*
*
*
*
*
(c) The owner or operator of a Group
1 miscellaneous process vent using a
vent system that contains bypass lines
that could divert a vent stream away
from the control device used to comply
with paragraph (a) of this section either
directly to the atmosphere or to a
control device that does not comply
with the requirements in § 63.643(a)
shall comply with either paragraph
(c)(1) or (2) of this section. Use of the
bypass at any time to divert a Group 1
miscellaneous process vent stream to
the atmosphere or to a control device
that does not comply with the
requirements in § 63.643(a) is an
emissions standards violation.
Equipment such as low leg drains and
equipment subject to § 63.648 are not
subject to this paragraph (c).
(1) Install, calibrate and maintain a
flow indicator that determines whether
a vent stream flow is present at least
once every hour. A manual block valve
equipped with a valve position
indicator may be used in lieu of a flow
indicator, as long as the valve position
indicator is monitored continuously.
Records shall be generated as specified
in § 63.655(h) and (i). The flow indicator
shall be installed at the entrance to any
bypass line that could divert the vent
stream away from the control device to
the atmosphere; or
(2) Secure the bypass line valve in the
non-diverting position with a car-seal or
a lock-and-key type configuration. A
visual inspection of the seal or closure
mechanism shall be performed at least
once every month to ensure that the
valve is maintained in the non-diverting
position and that the vent stream is not
diverted through the bypass line.
*
*
*
*
*
18. Section 63.645 is amended by
revising paragraphs (e)(1) and (f)(2) to
read as follows:
■
PO 00000
Frm 00067
Fmt 4701
Sfmt 4700
75243
§ 63.645 Test methods and procedures for
miscellaneous process vents.
*
*
*
*
*
(e) * * *
(1) Methods 1 or 1A of 40 CFR part
60, appendix A–1, as appropriate, shall
be used for selection of the sampling
site. For vents smaller than 0.10 meter
in diameter, sample at the center of the
vent.
*
*
*
*
*
(f) * * *
(2) The gas volumetric flow rate shall
be determined using Methods 2, 2A, 2C,
2D, or 2F of 40 CFR part 60, appendix
A–1 or Method 2G of 40 CFR part 60,
appendix A–2, as appropriate.
*
*
*
*
*
■ 19. Section 63.646 is amended by
adding introductory text and revising
paragraph (b)(2) to read as follows:
§ 63.646
Storage vessel provisions.
Upon a demonstration of compliance
with the standards in § 63.660 by the
compliance dates specified in
§ 63.640(h), the standards in this section
shall no longer apply.
*
*
*
*
*
(b) * * *
(2) When an owner or operator and
the Administrator do not agree on
whether the annual average weight
percent organic HAP in the stored liquid
is above or below 4 percent for a storage
vessel at an existing source or above or
below 2 percent for a storage vessel at
a new source, an appropriate method
(based on the type of liquid stored) as
published by EPA or a consensus-based
standards organization shall be used.
Consensus-based standards
organizations include, but are not
limited to, the following: ASTM
International (100 Barr Harbor Drive,
P.O. Box CB700, West Conshohocken,
Pennsylvania 19428–B2959, (800) 262–
1373, https://www.astm.org), the
American National Standards Institute
(ANSI, 1819 L Street NW., 6th floor,
Washington, DC 20036, (202) 293–8020,
https://www.ansi.org), the American Gas
Association (AGA, 400 North Capitol
Street NW., 4th Floor, Washington, DC
20001, (202) 824–7000, https://
www.aga.org), the American Society of
Mechanical Engineers (ASME, Three
Park Avenue, New York, NY 10016–
5990, (800) 843–2763, https://
www.asme.org), the American
Petroleum Institute (API, 1220 L Street
NW., Washington, DC 20005–4070,
(202) 682–8000, https://www.api.org),
and the North American Energy
Standards Board (NAESB, 801 Travis
Street, Suite 1675, Houston, TX 77002,
(713) 356–0060, https://www.naesb.org).
*
*
*
*
*
E:\FR\FM\01DER2.SGM
01DER2
75244
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
20. Section 63.647 is amended by:
a. Revising paragraph (a);
b. Redesignating paragraph (c) as
paragraph (d); and
■ c. Adding paragraph (c).
The revisions and additions read as
follows:
■
■
■
§ 63.647
Wastewater provisions.
(a) Except as provided in paragraphs
(b) and (c) of this section, each owner
or operator of a Group 1 wastewater
stream shall comply with the
requirements of §§ 61.340 through
61.355 of this chapter for each process
wastewater stream that meets the
definition in § 63.641.
*
*
*
*
*
(c) If a flare is used as a control
device, on and after January 30, 2019,
the flare shall meet the requirements of
§ 63.670. Prior to January 30, 2019, the
flare shall meet the applicable
requirements of part 61, subpart FF of
this chapter, or the requirements of
§ 63.670.
*
*
*
*
*
■ 21. Section 63.648 is amended by:
■ a. Adding paragraph (a)(3);
■ b. Revising paragraph (c) introductory
text; and
■ c. Adding paragraphs (c)(11) and (12)
and (j).
The revisions and additions read as
follows:
tkelley on DSK3SPTVN1PROD with RULES2
§ 63.648
Equipment leak standards.
(a) * * *
(3) If a flare is used as a control
device, on and after January 30, 2019,
the flare shall meet the requirements of
§ 63.670. Prior to January 30, 2019, the
flare shall meet the applicable
requirements of part 60, subpart VV of
this chapter, or the requirements of
§ 63.670.
*
*
*
*
*
(c) In lieu of complying with the
existing source provisions of paragraph
(a) in this section, an owner or operator
may elect to comply with the
requirements of §§ 63.161 through
63.169, 63.171, 63.172, 63.175, 63.176,
63.177, 63.179, and 63.180 of subpart H
except as provided in paragraphs (c)(1)
through (12) and (e) through (i) of this
section.
*
*
*
*
*
(11) [Reserved]
(12) If a flare is used as a control
device, on and after January 30, 2019,
the flare shall meet the requirements of
§ 63.670. Prior to January 30, 2019, the
flare shall meet the applicable
requirements of §§ 63.172 and 63.180, or
the requirements of § 63.670.
*
*
*
*
*
(j) Except as specified in paragraph
(j)(4) of this section, the owner or
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
operator must comply with the
requirements specified in paragraphs
(j)(1) and (2) of this section for pressure
relief devices, such as relief valves or
rupture disks, in organic HAP gas or
vapor service instead of the pressure
relief device requirements of § 60.482–4
or § 63.165, as applicable. Except as
specified in paragraphs (j)(4) and (5) of
this section, the owner or operator must
also comply with the requirements
specified in paragraph (j)(3) of this
section for all pressure relief devices.
(1) Operating requirements. Except
during a pressure release, operate each
pressure relief device in organic HAP
gas or vapor service with an instrument
reading of less than 500 ppm above
background as detected by Method 21 of
40 CFR part 60, appendix A–7.
(2) Pressure release requirements. For
pressure relief devices in organic HAP
gas or vapor service, the owner or
operator must comply with the
applicable requirements in paragraphs
(j)(2)(i) through (iii) of this section
following a pressure release.
(i) If the pressure relief device does
not consist of or include a rupture disk,
conduct instrument monitoring, as
specified in § 60.485(b) or § 63.180(c), as
applicable, no later than 5 calendar days
after the pressure relief device returns to
organic HAP gas or vapor service
following a pressure release to verify
that the pressure relief device is
operating with an instrument reading of
less than 500 ppm.
(ii) If the pressure relief device
includes a rupture disk, either comply
with the requirements in paragraph
(j)(2)(i) of this section (not replacing the
rupture disk) or install a replacement
disk as soon as practicable after a
pressure release, but no later than 5
calendar days after the pressure release.
The owner or operator must conduct
instrument monitoring, as specified in
§ 60.485(b) or § 63.180(c), as applicable,
no later than 5 calendar days after the
pressure relief device returns to organic
HAP gas or vapor service following a
pressure release to verify that the
pressure relief device is operating with
an instrument reading of less than 500
ppm.
(iii) If the pressure relief device
consists only of a rupture disk, install a
replacement disk as soon as practicable
after a pressure release, but no later than
5 calendar days after the pressure
release. The owner or operator may not
initiate startup of the equipment served
by the rupture disk until the rupture
disc is replaced. The owner or operator
must conduct instrument monitoring, as
specified in § 60.485(b) or § 63.180(c), as
applicable, no later than 5 calendar days
after the pressure relief device returns to
PO 00000
Frm 00068
Fmt 4701
Sfmt 4700
organic HAP gas or vapor service
following a pressure release to verify
that the pressure relief device is
operating with an instrument reading of
less than 500 ppm.
(3) Pressure release management.
Except as specified in paragraphs (j)(4)
and (5) of this section, the owner or
operator shall comply with the
requirements specified in paragraphs
(j)(3)(i) through (v) of this section for all
pressure relief devices in organic HAP
service no later than January 30, 2019.
(i) The owner or operator must equip
each affected pressure relief device with
a device(s) or use a monitoring system
that is capable of:
(A) Identifying the pressure release;
(B) Recording the time and duration
of each pressure release; and
(C) Notifying operators immediately
that a pressure release is occurring. The
device or monitoring system may be
either specific to the pressure relief
device itself or may be associated with
the process system or piping, sufficient
to indicate a pressure release to the
atmosphere. Examples of these types of
devices and systems include, but are not
limited to, a rupture disk indicator,
magnetic sensor, motion detector on the
pressure relief valve stem, flow monitor,
or pressure monitor.
(ii) The owner or operator must apply
at least three redundant prevention
measures to each affected pressure relief
device and document these measures.
Examples of prevention measures
include:
(A) Flow, temperature, level and
pressure indicators with deadman
switches, monitors, or automatic
actuators.
(B) Documented routine inspection
and maintenance programs and/or
operator training (maintenance
programs and operator training may
count as only one redundant prevention
measure).
(C) Inherently safer designs or safety
instrumentation systems.
(D) Deluge systems.
(E) Staged relief system where initial
pressure relief valve (with lower set
release pressure) discharges to a flare or
other closed vent system and control
device.
(iii) If any affected pressure relief
device releases to atmosphere as a result
of a pressure release event, the owner or
operator must perform root cause
analysis and corrective action analysis
according to the requirement in
paragraph (j)(6) of this section and
implement corrective actions according
to the requirements in paragraph (j)(7) of
this section. The owner or operator must
also calculate the quantity of organic
HAP released during each pressure
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
release event and report this quantity as
required in § 63.655(g)(10)(iii).
Calculations may be based on data from
the pressure relief device monitoring
alone or in combination with process
parameter monitoring data and process
knowledge.
(iv) The owner or operator shall
determine the total number of release
events occurred during the calendar
year for each affected pressure relief
device separately. The owner or
operator shall also determine the total
number of release events for each
pressure relief device for which the root
cause analysis concluded that the root
cause was a force majeureevent, as
defined in this subpart.
(v) Except for pressure relief devices
described in paragraphs (j)(4) and (5) of
this section, the following release events
are a violation of the pressure release
management work practice standards.
(A) Any release event for which the
root cause of the event was determined
to be operator error or poor
maintenance.
(B) A second release event not
including force majeure events from a
single pressure relief device in a 3
calendar year period for the same root
cause for the same equipment.
(C) A third release event not including
force majeure events from a single
pressure relief device in a 3 calendar
year period for any reason.
(4) Pressure relief devices routed to a
control device. If all releases and
potential leaks from a pressure relief
device are routed through a closed vent
system to a control device, back into the
process or to the fuel gas system, the
owner or operator is not required to
comply with paragraph (j)(1), (2), or (3)
(if applicable) of this section. Both the
closed vent system and control device
(if applicable) must meet the
requirements of § 63.644. When
complying with this paragraph (j)(4), all
references to ‘‘Group 1 miscellaneous
process vent’’ in § 63.644 mean
‘‘pressure relief device.’’ If a pressure
relief device complying with this
paragraph (j)(4) is routed to the fuel gas
system, then on and after January 30,
2019, any flares receiving gas from that
fuel gas system must be in compliance
with § 63.670.
(5) Pressure relief devices exempted
from pressure release management
requirements. The following types of
pressure relief devices are not subject to
the pressure release management
requirements in paragraph (j)(3) of this
section.
(i) Pressure relief devices in heavy
liquid service, as defined in § 63.641.
(ii) Pressure relief devices that only
release material that is liquid at
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
standard conditions (1 atmosphere and
68 degrees Fahrenheit) and that are
hard-piped to a controlled drain system
(i.e., a drain system meeting the
requirements for Group 1 wastewater
streams in § 63.647(a)) or piped back to
the process or pipeline.
(iii) Thermal expansion relief valves.
(iv) Pressure relief devices designed
with a set relief pressure of less than 2.5
psig.
(v) Pressure relief devices that do not
have the potential to emit 72 lbs/day or
more of VOC based on the valve
diameter, the set release pressure, and
the equipment contents.
(vi) Pressure relief devices on mobile
equipment.
(6) Root cause analysis and corrective
action analysis. A root cause analysis
and corrective action analysis must be
completed as soon as possible, but no
later than 45 days after a release event.
Special circumstances affecting the
number of root cause analyses and/or
corrective action analyses are provided
in paragraphs (j)(6)(i) through (iv) of this
section.
(i) You may conduct a single root
cause analysis and corrective action
analysis for a single emergency event
that causes two or more pressure relief
devices installed on the same
equipment to release.
(ii) You may conduct a single root
cause analysis and corrective action
analysis for a single emergency event
that causes two or more pressure relief
devices to release, regardless of the
equipment served, if the root cause is
reasonably expected to be a force
majeure event, as defined in this
subpart.
(iii) Except as provided in paragraphs
(j)(6)(i) and (ii) of this section, if more
than one pressure relief device has a
release during the same time period, an
initial root cause analysis shall be
conducted separately for each pressure
relief device that had a release. If the
initial root cause analysis indicates that
the release events have the same root
cause(s), the initially separate root cause
analyses may be recorded as a single
root cause analysis and a single
corrective action analysis may be
conducted.
(7) Corrective action implementation.
Each owner or operator required to
conduct a root cause analysis and
corrective action analysis as specified in
paragraphs (j)(3)(iii) and (j)(6) of this
section shall implement the corrective
action(s) identified in the corrective
action analysis in accordance with the
applicable requirements in paragraphs
(j)(7)(i) through (iii) of this section.
(i) All corrective action(s) must be
implemented within 45 days of the
PO 00000
Frm 00069
Fmt 4701
Sfmt 4700
75245
event for which the root cause and
corrective action analyses were required
or as soon thereafter as practicable. If an
owner or operator concludes that no
corrective action should be
implemented, the owner or operator
shall record and explain the basis for
that conclusion no later than 45 days
following the event.
(ii) For corrective actions that cannot
be fully implemented within 45 days
following the event for which the root
cause and corrective action analyses
were required, the owner or operator
shall develop an implementation
schedule to complete the corrective
action(s) as soon as practicable.
(iii) No later than 45 days following
the event for which a root cause and
corrective action analyses were
required, the owner or operator shall
record the corrective action(s)
completed to date, and, for action(s) not
already completed, a schedule for
implementation, including proposed
commencement and completion dates.
■ 22. Section 63.649 is amended by
revising definition of Cc term in the
equation in paragraph (c)(6)(i) to read as
follows:
§ 63.649 Alternative means of emission
limitation: Connectors in gas/vapor service
and light liquid service.
*
*
(c) * *
(6) * *
(i) * *
*
*
*
*
*
*
Cc = Optional credit for removed connectors
= 0.67 × net number (i.e., the total
number of connectors removed minus
the total added) of connectors in organic
HAP service removed from the process
unit after the applicability date set forth
in § 63.640(h)(3)(iii) for existing process
units, and after the date of start-up for
new process units. If credits are not
taken, then Cc = 0.
*
*
*
*
*
23. Section 63.650 is amended by
revising paragraph (a) and adding
paragraph (d) to read as follows:
■
§ 63.650
Gasoline loading rack provisions.
(a) Except as provided in paragraphs
(b) through (d) of this section, each
owner or operator of a Group 1 gasoline
loading rack classified under Standard
Industrial Classification code 2911
located within a contiguous area and
under common control with a
petroleum refinery shall comply with
subpart R of this part, §§ 63.421,
63.422(a) through (c) and (e), 63.425(a)
through (c) and (e) through (i), 63.427(a)
and (b), and 63.428(b), (c), (g)(1), (h)(1)
through (3), and (k).
*
*
*
*
*
E:\FR\FM\01DER2.SGM
01DER2
75246
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
(d) If a flare is used as a control
device, on and after January 30, 2019,
the flare shall meet the requirements of
§ 63.670. Prior to January 30, 2019, the
flare shall meet the applicable
requirements of subpart R of this part,
or the requirements of § 63.670.
■ 24. Section 63.651 is amended by
revising paragraphs (a) and (d) and
adding paragraph (e) to read as follows:
§ 63.651 Marine tank vessel loading
operation provisions.
(a) Except as provided in paragraphs
(b) through (e) of this section, each
owner or operator of a marine tank
vessel loading operation located at a
petroleum refinery shall comply with
the requirements of §§ 63.560 through
63.568.
*
*
*
*
*
(d) The compliance time of 4 years
after promulgation of 40 CFR part 63,
subpart Y, does not apply. The
compliance time is specified in
§ 63.640(h)(1).
(e) If a flare is used as a control
device, on and after January 30, 2019,
the flare shall meet the requirements of
§ 63.670. Prior to January 30, 2019, the
flare shall meet the applicable
requirements of subpart Y of this part,
or the requirements of § 63.670.
■ 25. Section 63.652 is amended by:
■ a. Revising paragraph (a);
■ b. Removing and reserving paragraph
(f)(2); and
■ c. Revising paragraphs (g)(2)(iii)(B)(1),
(h)(3), (k) introductory text, and (k)(3).
The revisions and additions read as
follows:
tkelley on DSK3SPTVN1PROD with RULES2
§ 63.652
Emissions averaging provisions.
(a) This section applies to owners or
operators of existing sources who seek
to comply with the emission standard in
§ 63.642(g) by using emissions averaging
according to § 63.642(l) rather than
following the provisions of §§ 63.643
through 63.645, 63.646 or 63.660,
63.647, 63.650, and 63.651. Existing
marine tank vessel loading operations
located at the Valdez Marine Terminal
source may not comply with the
standard by using emissions averaging.
*
*
*
*
*
(g) * * *
(2) * * *
(iii) * * *
(B) * * *
(1) The percent reduction shall be
measured according to the procedures
in § 63.116 of subpart G if a combustion
control device is used. For a flare
meeting the criteria in § 63.116(a) of
subpart G or § 63.670, as applicable, or
a boiler or process heater meeting the
criteria in § 63.645(d) or § 63.116(b) of
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
subpart G, the percentage of reduction
shall be 98 percent. If a noncombustion
control device is used, percentage of
reduction shall be demonstrated by a
performance test at the inlet and outlet
of the device, or, if testing is not
feasible, by a control design evaluation
and documented engineering
calculations.
*
*
*
*
*
(h) * * *
(3) Emissions from storage vessels
shall be determined as specified in
§ 63.150(h)(3) of subpart G, except as
follows:
(i) For storage vessels complying with
§ 63.646:
(A) All references to § 63.119(b) in
§ 63.150(h)(3) of subpart G shall be
replaced with: § 63.119(b) or § 63.119(b)
except for § 63.119(b)(5) and (6).
(B) All references to § 63.119(c) in
§ 63.150(h)(3) of subpart G shall be
replaced with: § 63.119(c) or § 63.119(c)
except for § 63.119(c)(2).
(C) All references to § 63.119(d) in
§ 63.150(h)(3) of subpart G shall be
replaced with: § 63.119(d) or § 63.119(d)
except for § 63.119(d)(2).
(ii) For storage vessels complying
with § 63.660:
(A) Section 63.1063(a)(1)(i), (a)(2), and
(b) or § 63.1063(a)(1)(i) and (b) shall
apply instead of § 63.119(b) in
§ 63.150(h)(3) of subpart G.
(B) Section 63.1063(a)(1)(ii), (a)(2),
and (b) shall apply instead of § 63.119(c)
in § 63.150(h)(3) of subpart G.
(C) Section 63.1063(a)(1)(i), (a)(2), and
(b) or § 63.1063(a)(1)(i) and (b) shall
apply instead of § 63.119(d) in
§ 63.150(h)(3) of subpart G.
*
*
*
*
*
(k) The owner or operator shall
demonstrate that the emissions from the
emission points proposed to be
included in the average will not result
in greater hazard or, at the option of the
State or local permitting authority,
greater risk to human health or the
environment than if the emission points
were controlled according to the
provisions in §§ 63.643 through 63.645,
63.646 or 63.660, 63.647, 63.650, and
63.651, as applicable.
*
*
*
*
*
(3) An emissions averaging plan that
does not demonstrate an equivalent or
lower hazard or risk to the satisfaction
of the State or local permitting authority
shall not be approved. The State or local
permitting authority may require such
adjustments to the emissions averaging
plan as are necessary in order to ensure
that the average will not result in greater
hazard or risk to human health or the
environment than would result if the
emission points were controlled
PO 00000
Frm 00070
Fmt 4701
Sfmt 4700
according to §§ 63.643 through 63.645,
63.646 or 63.660, 63.647, 63.650, and
63.651, as applicable.
*
*
*
*
*
■ 26. Section 63.653 is amended by
revising paragraphs (a) introductory
text, (a)(3)(i) and (ii), and (a)(7) to read
as follows:
§ 63.653 Monitoring, recordkeeping, and
implementation plan for emissions
averaging.
(a) For each emission point included
in an emissions average, the owner or
operator shall perform testing,
monitoring, recordkeeping, and
reporting equivalent to that required for
Group 1 emission points complying
with §§ 63.643 through 63.645, 63.646
or 63.660, 63.647, 63.650, and 63.651, as
applicable. The specific requirements
for miscellaneous process vents, storage
vessels, wastewater, gasoline loading
racks, and marine tank vessels are
identified in paragraphs (a)(1) through
(7) of this section.
*
*
*
*
*
(3) * * *
(i) Perform the monitoring or
inspection procedures in § 63.646 and
either § 63.120 of subpart G or § 63.1063
of subpart WW, as applicable; and
(ii) For closed vent systems with
control devices, conduct an initial
design evaluation as specified in
§ 63.646 and either § 63.120(d) of
subpart G or § 63.985(b) of subpart SS,
as applicable.
*
*
*
*
*
(7) If an emission point in an
emissions average is controlled using a
pollution prevention measure or a
device or technique for which no
monitoring parameters or inspection
procedures are specified in §§ 63.643
through 63.645, 63.646 or 63.660,
63.647, 63.650, and 63.651, as
applicable, the owner or operator shall
establish a site-specific monitoring
parameter and shall submit the
information specified in § 63.655(h)(4)
in the Implementation Plan.
*
*
*
*
*
■ 27. Section 63.655 is amended by:
■ a. Revising paragraphs (f) introductory
text, (f)(1) introductory text, (f)(1)(i)(A)
introductory text, (f)(1)(i)(A)(2) and (3),
(f)(1)(i)(B) introductory text,
(f)(1)(i)(B)(2), (f)(1)(i)(D)(2), (f)(1)(iv)
introductory text, and (f)(1)(iv)(A);
■ b. Adding paragraphs (f)(1)(vii) and
(viii);
■ c. Revising paragraphs (f)(2)
introductory text, (f)(3) introductory
text, the first sentence of (f)(6), (g)
introductory text, (g)(1) through (5),
(g)(6)(i)(D), (g)(6)(iii), and (g)(7)(i);
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
d. Adding paragraphs (g)(10) through
(14);
■ e. Removing and reserving paragraph
(h)(1);
■ f. Revising paragraphs (h)(2)
introductory text, (h)(2)(i)(B), (h)(2)(ii),
and (h)(5)(iii);
■ g. Adding paragraphs (h)(8) and (9)
and (i) introductory text;
■ h. Revising paragraph (i)(1)
introductory text and paragraph
(i)(1)(ii);
■ i. Adding paragraphs (i)(1)(v) and (vi);
■ j. Redesignating paragraphs (i)(4) and
(5) as paragraphs (i)(5) and (6),
respectively;
■ k. Adding paragraph (i)(4);
■ l. Revising newly redesignated
paragraph (i)(5) introductory text; and
■ m. Adding paragraphs (i)(7) through
(12).
The revisions and additions read as
follows:
■
§ 63.655 Reporting and recordkeeping
requirements.
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
(f) Each owner or operator of a source
subject to this subpart shall submit a
Notification of Compliance Status report
within 150 days after the compliance
dates specified in § 63.640(h) with the
exception of Notification of Compliance
Status reports submitted to comply with
§ 63.640(l)(3) and for storage vessels
subject to the compliance schedule
specified in § 63.640(h)(2). Notification
of Compliance Status reports required
by § 63.640(l)(3) and for storage vessels
subject to the compliance dates
specified in § 63.640(h)(2) shall be
submitted according to paragraph (f)(6)
of this section. This information may be
submitted in an operating permit
application, in an amendment to an
operating permit application, in a
separate submittal, or in any
combination of the three. If the required
information has been submitted before
the date 150 days after the compliance
date specified in § 63.640(h), a separate
Notification of Compliance Status report
is not required within 150 days after the
compliance dates specified in
§ 63.640(h). If an owner or operator
submits the information specified in
paragraphs (f)(1) through (5) of this
section at different times, and/or in
different submittals, later submittals
may refer to earlier submittals instead of
duplicating and resubmitting the
previously submitted information. Each
owner or operator of a gasoline loading
rack classified under Standard
Industrial Classification Code 2911
located within a contiguous area and
under common control with a
petroleum refinery subject to the
standards of this subpart shall submit
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
the Notification of Compliance Status
report required by subpart R of this part
within 150 days after the compliance
dates specified in § 63.640(h).
(1) The Notification of Compliance
Status report shall include the
information specified in paragraphs
(f)(1)(i) through (viii) of this section.
(i) * * *
(A) Identification of each storage
vessel subject to this subpart, and for
each Group 1 storage vessel subject to
this subpart, the information specified
in paragraphs (f)(1)(i)(A)(1) through (3)
of this section. This information is to be
revised each time a Notification of
Compliance Status report is submitted
for a storage vessel subject to the
compliance schedule specified in
§ 63.640(h)(2) or to comply with
§ 63.640(l)(3).
*
*
*
*
*
(2) For storage vessels subject to the
compliance schedule specified in
§ 63.640(h)(2) that are not complying
with § 63.646, the anticipated
compliance date.
(3) For storage vessels subject to the
compliance schedule specified in
§ 63.640(h)(2) that are complying with
§ 63.646 and the Group 1 storage vessels
described in § 63.640(l), the actual
compliance date.
(B) If a closed vent system and a
control device other than a flare is used
to comply with § 63.646 or § 63.660, the
owner or operator shall submit:
*
*
*
*
*
(2) The design evaluation
documentation specified in
§ 63.120(d)(1)(i) of subpart G or
§ 63.985(b)(1)(i) of subpart SS (as
applicable), if the owner or operator
elects to prepare a design evaluation; or
*
*
*
*
*
(D) * * *
(2) All visible emission readings, heat
content determinations, flow rate
measurements, and exit velocity
determinations made during the
compliance determination required by
§ 63.120(e) of subpart G or § 63.987(b) of
subpart SS or § 63.670(h), as applicable;
and
*
*
*
*
*
(iv) For miscellaneous process vents
controlled by flares, initial compliance
test results including the information in
paragraphs (f)(1)(iv)(A) and (B) of this
section.
(A) All visible emission readings, heat
content determinations, flow rate
measurements, and exit velocity
determinations made during the
compliance determination required by
§§ 63.645 and 63.116(a) of subpart G or
§ 63.670(h), as applicable; and
*
*
*
*
*
PO 00000
Frm 00071
Fmt 4701
Sfmt 4700
75247
(vii) For pressure relief devices in
organic HAP service subject to the
requirements in § 63.648(j)(3)(i) and (ii),
this report shall include the information
specified in paragraphs (f)(1)(vii)(A) and
(B) of this section.
(A) A description of the monitoring
system to be implemented, including
the relief devices and process
parameters to be monitored, and a
description of the alarms or other
methods by which operators will be
notified of a pressure release.
(B) A description of the prevention
measures to be implemented for each
affected pressure relief device.
(viii) For each delayed coking unit,
identification of whether the unit is an
existing affected source or a new
affected source and whether monitoring
will be conducted as specified in
§ 63.657(b) or (c).
(2) If initial performance tests are
required by §§ 63.643 through 63.653,
the Notification of Compliance Status
report shall include one complete test
report for each test method used for a
particular source. On and after February
1, 2016, performance tests shall be
submitted according to paragraph (h)(9)
of this section.
*
*
*
*
*
(3) For each monitored parameter for
which a range is required to be
established under § 63.120(d) of subpart
G or § 63.985(b) of subpart SS for storage
vessels or § 63.644 for miscellaneous
process vents, the Notification of
Compliance Status report shall include
the information in paragraphs (f)(3)(i)
through (iii) of this section.
*
*
*
*
*
(6) Notification of Compliance Status
reports required by § 63.640(l)(3) and for
storage vessels subject to the
compliance dates specified in
§ 63.640(h)(2) shall be submitted no
later than 60 days after the end of the
6-month period during which the
change or addition was made that
resulted in the Group 1 emission point
or the existing Group 1 storage vessel
was brought into compliance, and may
be combined with the periodic
report. * * *
(g) The owner or operator of a source
subject to this subpart shall submit
Periodic Reports no later than 60 days
after the end of each 6-month period
when any of the information specified
in paragraphs (g)(1) through (7) of this
section or paragraphs (g)(9) through (14)
of this section is collected. The first 6month period shall begin on the date the
Notification of Compliance Status report
is required to be submitted. A Periodic
Report is not required if none of the
events identified in paragraphs (g)(1)
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75248
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
through (7) of this section or paragraphs
(g)(9) through (14) of this section
occurred during the 6-month period
unless emissions averaging is utilized.
Quarterly reports must be submitted for
emission points included in emission
averages, as provided in paragraph (g)(8)
of this section. An owner or operator
may submit reports required by other
regulations in place of or as part of the
Periodic Report required by this
paragraph (g) if the reports contain the
information required by paragraphs
(g)(1) through (14) of this section.
(1) For storage vessels, Periodic
Reports shall include the information
specified for Periodic Reports in
paragraphs (g)(2) through (5) of this
section. Information related to gaskets,
slotted membranes, and sleeve seals is
not required for storage vessels that are
part of an existing source complying
with § 63.646.
(2) Internal floating roofs. (i) An
owner or operator who elects to comply
with § 63.646 by using a fixed roof and
an internal floating roof or by using an
external floating roof converted to an
internal floating roof shall submit the
results of each inspection conducted in
accordance with § 63.120(a) of subpart G
in which a failure is detected in the
control equipment.
(A) For vessels for which annual
inspections are required under
§ 63.120(a)(2)(i) or (a)(3)(ii) of subpart G,
the specifications and requirements
listed in paragraphs (g)(2)(i)(A)(1)
through (3) of this section apply.
(1) A failure is defined as any time in
which the internal floating roof is not
resting on the surface of the liquid
inside the storage vessel and is not
resting on the leg supports; or there is
liquid on the floating roof; or the seal is
detached from the internal floating roof;
or there are holes, tears, or other
openings in the seal or seal fabric; or
there are visible gaps between the seal
and the wall of the storage vessel.
(2) Except as provided in paragraph
(g)(2)(i)(A)(3) of this section, each
Periodic Report shall include the date of
the inspection, identification of each
storage vessel in which a failure was
detected, and a description of the
failure. The Periodic Report shall also
describe the nature of and date the
repair was made or the date the storage
vessel was emptied.
(3) If an extension is utilized in
accordance with § 63.120(a)(4) of
subpart G, the owner or operator shall,
in the next Periodic Report, identify the
vessel; include the documentation
specified in § 63.120(a)(4) of subpart G;
and describe the date the storage vessel
was emptied and the nature of and date
the repair was made.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(B) For vessels for which inspections
are required under § 63.120(a)(2)(ii),
(a)(3)(i), or (a)(3)(iii) of subpart G (i.e.,
internal inspections), the specifications
and requirements listed in paragraphs
(g)(2)(i)(B)(1) and (2) of this section
apply.
(1) A failure is defined as any time in
which the internal floating roof has
defects; or the primary seal has holes,
tears, or other openings in the seal or
the seal fabric; or the secondary seal (if
one has been installed) has holes, tears,
or other openings in the seal or the seal
fabric; or, for a storage vessel that is part
of a new source, the gaskets no longer
close off the liquid surface from the
atmosphere; or, for a storage vessel that
is part of a new source, the slotted
membrane has more than a 10 percent
open.
(2) Each Periodic Report shall include
the date of the inspection, identification
of each storage vessel in which a failure
was detected, and a description of the
failure. The Periodic Report shall also
describe the nature of and date the
repair was made.
(ii) An owner or operator who elects
to comply with § 63.660 by using a fixed
roof and an internal floating roof shall
submit the results of each inspection
conducted in accordance with
§ 63.1063(c)(1), (d)(1), and (d)(2) of
subpart WW in which a failure is
detected in the control equipment. For
vessels for which inspections are
required under § 63.1063(c) and (d), the
specifications and requirements listed
in paragraphs (g)(2)(ii)(A) through (C) of
this section apply.
(A) A failure is defined in
§ 63.1063(d)(1) of subpart WW.
(B) Each Periodic Report shall include
a copy of the inspection record required
by § 63.1065(b) of subpart WW when a
failure occurs.
(C) An owner or operator who elects
to use an extension in accordance with
§ 63.1063(e)(2) of subpart WW shall, in
the next Periodic Report, submit the
documentation required by
§ 63.1063(e)(2).
(3) External floating roofs. (i) An
owner or operator who elects to comply
with § 63.646 by using an external
floating roof shall meet the periodic
reporting requirements specified in
paragraphs (g)(3)(i)(A) through (C) of
this section.
(A) The owner or operator shall
submit, as part of the Periodic Report,
documentation of the results of each
seal gap measurement made in
accordance with § 63.120(b) of subpart
G in which the seal and seal gap
requirements of § 63.120(b)(3), (4), (5),
or (6) of subpart G are not met. This
documentation shall include the
PO 00000
Frm 00072
Fmt 4701
Sfmt 4700
information specified in paragraphs
(g)(3)(i)(A)(1) through (4) of this section.
(1) The date of the seal gap
measurement.
(2) The raw data obtained in the seal
gap measurement and the calculations
described in § 63.120(b)(3) and (4) of
subpart G.
(3) A description of any seal condition
specified in § 63.120(b)(5) or (6) of
subpart G that is not met.
(4) A description of the nature of and
date the repair was made, or the date the
storage vessel was emptied.
(B) If an extension is utilized in
accordance with § 63.120(b)(7)(ii) or
(b)(8) of subpart G, the owner or
operator shall, in the next Periodic
Report, identify the vessel; include the
documentation specified in
§ 63.120(b)(7)(ii) or (b)(8) of subpart G,
as applicable; and describe the date the
vessel was emptied and the nature of
and date the repair was made.
(C) The owner or operator shall
submit, as part of the Periodic Report,
documentation of any failures that are
identified during visual inspections
required by § 63.120(b)(10) of subpart G.
This documentation shall meet the
specifications and requirements in
paragraphs (g)(3)(i)(C)(1) and (2) of this
section.
(1) A failure is defined as any time in
which the external floating roof has
defects; or the primary seal has holes or
other openings in the seal or the seal
fabric; or the secondary seal has holes,
tears, or other openings in the seal or
the seal fabric; or, for a storage vessel
that is part of a new source, the gaskets
no longer close off the liquid surface
from the atmosphere; or, for a storage
vessel that is part of a new source, the
slotted membrane has more than 10
percent open area.
(2) Each Periodic Report shall include
the date of the inspection, identification
of each storage vessel in which a failure
was detected, and a description of the
failure. The Periodic Report shall also
describe the nature of and date the
repair was made.
(ii) An owner or operator who elects
to comply with § 63.660 by using an
external floating roof shall meet the
periodic reporting requirements
specified in paragraphs (g)(3)(ii)(A) and
(B) of this section.
(A) For vessels for which inspections
are required under § 63.1063(c)(2),
(d)(1), and (d)(3) of subpart WW, the
owner or operator shall submit, as part
of the Periodic Report, a copy of the
inspection record required by
§ 63.1065(b) of subpart WW when a
failure occurs. A failure is defined in
§ 63.1063(d)(1).
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
(B) An owner or operator who elects
to use an extension in accordance with
§ 63.1063(e)(2) or (c)(2)(iv)(B) of subpart
WW shall, in the next Periodic Report,
submit the documentation required by
those paragraphs.
(4) [Reserved]
(5) An owner or operator who elects
to comply with § 63.646 or § 63.660 by
installing a closed vent system and
control device shall submit, as part of
the next Periodic Report, the
information specified in paragraphs
(g)(5)(i) through (v) of this section, as
applicable.
(i) The Periodic Report shall include
the information specified in paragraphs
(g)(5)(i)(A) and (B) of this section for
those planned routine maintenance
operations that would require the
control device not to meet the
requirements of either § 63.119(e)(1) or
(2) of subpart G, § 63.985(a) and (b) of
subpart SS, or § 63.670, as applicable.
(A) A description of the planned
routine maintenance that is anticipated
to be performed for the control device
during the next 6 months. This
description shall include the type of
maintenance necessary, planned
frequency of maintenance, and lengths
of maintenance periods.
(B) A description of the planned
routine maintenance that was performed
for the control device during the
previous 6 months. This description
shall include the type of maintenance
performed and the total number of
hours during those 6 months that the
control device did not meet the
requirements of either § 63.119(e)(1) or
(2) of subpart G, § 63.985(a) and (b) of
subpart SS, or § 63.670, as applicable,
due to planned routine maintenance.
(ii) If a control device other than a
flare is used, the Periodic Report shall
describe each occurrence when the
monitored parameters were outside of
the parameter ranges documented in the
Notification of Compliance Status
report. The description shall include:
Identification of the control device for
which the measured parameters were
outside of the established ranges, and
causes for the measured parameters to
be outside of the established ranges.
(iii) If a flare is used prior to January
30, 2019 and prior to electing to comply
with the requirements in § 63.670, the
Periodic Report shall describe each
occurrence when the flare does not meet
the general control device requirements
specified in § 63.11(b) of subpart A and
shall include: Identification of the flare
that does not meet the general
requirements specified in § 63.11(b) of
subpart A, and reasons the flare did not
meet the general requirements specified
in § 63.11(b) of subpart A.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(iv) If a flare is used on or after the
date for which compliance with the
requirements in § 63.670 is elected,
which can be no later than January 30,
2019, the Periodic Report shall include
the items specified in paragraph (g)(11)
of this section.
(v) An owner or operator who elects
to comply with § 63.660 by installing an
alternate control device as described in
§ 63.1064 of subpart WW shall submit,
as part of the next Periodic Report, a
written application as described in
§ 63.1066(b)(3) of subpart WW.
(6) * * *
(i) * * *
(D) For data compression systems
under paragraph (h)(5)(iii) of this
section, an operating day when the
monitor operated for less than 75
percent of the operating hours or a day
when less than 18 monitoring values
were recorded.
*
*
*
*
*
(iii) For periods in closed vent
systems when a Group 1 miscellaneous
process vent stream was detected in the
bypass line or diverted from the control
device and either directly to the
atmosphere or to a control device that
does not comply with the requirements
in § 63.643(a), report the date, time,
duration, estimate of the volume of gas,
the concentration of organic HAP in the
gas and the resulting mass emissions of
organic HAP that bypassed the control
device. For periods when the flow
indicator is not operating, report the
date, time, and duration.
(7) * * *
(i) Results of the performance test
shall include the identification of the
source tested, the date of the test, the
percentage of emissions reduction or
outlet pollutant concentration reduction
(whichever is needed to determine
compliance) for each run and for the
average of all runs, and the values of the
monitored operating parameters.
*
*
*
*
*
(10) For pressure relief devices subject
to the requirements § 63.648(j), Periodic
Reports must include the information
specified in paragraphs (g)(10)(i)
through (iii) of this section.
(i) For pressure relief devices in
organic HAP gas or vapor service,
pursuant to § 63.648(j)(1), report any
instrument reading of 500 ppm or
greater.
(ii) For pressure relief devices in
organic HAP gas or vapor service subject
to § 63.648(j)(2), report confirmation
that any monitoring required to be done
during the reporting period to show
compliance was conducted.
(iii) For pressure relief devices in
organic HAP service subject to
PO 00000
Frm 00073
Fmt 4701
Sfmt 4700
75249
§ 63.648(j)(3), report each pressure
release to the atmosphere, including
duration of the pressure release and
estimate of the mass quantity of each
organic HAP released, and the results of
any root cause analysis and corrective
action analysis completed during the
reporting period, including the
corrective actions implemented during
the reporting period and, if applicable,
the implementation schedule for
planned corrective actions to be
implemented subsequent to the
reporting period.
(11) For flares subject to § 63.670,
Periodic Reports must include the
information specified in paragraphs
(g)(11)(i) through (iv) of this section.
(i) Records as specified in paragraph
(i)(9)(i) of this section for each 15minute block during which there was at
least one minute when regulated
material is routed to a flare and no pilot
flame is present.
(ii) Visible emission records as
specified in paragraph (i)(9)(ii)(C) of this
section for each period of 2 consecutive
hours during which visible emissions
exceeded a total of 5 minutes.
(iii) The 15-minute block periods for
which the applicable operating limits
specified in § 63.670(d) through (f) are
not met. Indicate the date and time for
the period, the net heating value
operating parameter(s) determined
following the methods in § 63.670(k)
through (n) as applicable.
(iv) For flaring events meeting the
criteria in § 63.670(o)(3):
(A) The start and stop time and date
of the flaring event.
(B) The length of time for which
emissions were visible from the flare
during the event.
(C) The periods of time that the flare
tip velocity exceeds the maximum flare
tip velocity determined using the
methods in § 63.670(d)(2) and the
maximum 15-minute block average flare
tip velocity recorded during the event.
(D) Results of the root cause and
corrective actions analysis completed
during the reporting period, including
the corrective actions implemented
during the reporting period and, if
applicable, the implementation
schedule for planned corrective actions
to be implemented subsequent to the
reporting period.
(12) For delayed coking units, the
Periodic Report must include the
information specified in paragraphs
(g)(12)(i) through (iv) of this section.
(i) For existing source delayed coking
units, any 60-cycle average exceeding
the applicable limit in § 63.657(a)(1).
(ii) For new source delayed coking
units, any direct venting event
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75250
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
exceeding the applicable limit in
§ 63.657(a)(2).
(iii) The total number of double
quenching events performed during the
reporting period.
(iv) For each double quenching
draining event when the drain water
temperature exceeded 210 °F, report the
drum, date, time, the coke drum vessel
pressure or temperature, as applicable,
when pre-vent draining was initiated,
and the maximum drain water
temperature during the pre-vent
draining period.
(13) For maintenance vents subject to
the requirements in § 63.643(c), Periodic
Reports must include the information
specified in paragraphs (g)(13)(i)
through (iv) of this section for any
release exceeding the applicable limits
in § 63.643(c)(1). For the purposes of
this reporting requirement, owners or
operators complying with
§ 63.643(c)(1)(iv) must report each
venting event for which the lower
explosive limit is 20 percent or greater.
(i) Identification of the maintenance
vent and the equipment served by the
maintenance vent.
(ii) The date and time the
maintenance vent was opened to the
atmosphere.
(iii) The lower explosive limit, vessel
pressure, or mass of VOC in the
equipment, as applicable, at the start of
atmospheric venting. If the 5 psig vessel
pressure option in § 63.643(c)(1)(ii) was
used and active purging was initiated
while the lower explosive limit was 10
percent or greater, also include the
lower explosive limit of the vapors at
the time active purging was initiated.
(iv) An estimate of the mass of organic
HAP released during the entire
atmospheric venting event.
(14) Any changes in the information
provided in a previous Notification of
Compliance Status report.
(h) * * *
(2) For storage vessels, notifications of
inspections as specified in paragraphs
(h)(2)(i) and (ii) of this section.
(i) * * *
(B) Except as provided in paragraph
(h)(2)(i)(C) of this section, if the internal
inspection required by § 63.120(a)(2),
(a)(3), or (b)(10) of subpart G or
§ 63.1063(d)(1) of subpart WW is not
planned and the owner or operator
could not have known about the
inspection 30 calendar days in advance
of refilling the vessel with organic HAP,
the owner or operator shall notify the
Administrator at least 7 calendar days
prior to refilling of the storage vessel.
Notification may be made by telephone
and immediately followed by written
documentation demonstrating why the
inspection was unplanned. This
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
notification, including the written
documentation, may also be made in
writing and sent so that it is received by
the Administrator at least 7 calendar
days prior to the refilling.
*
*
*
*
*
(ii) In order to afford the
Administrator the opportunity to have
an observer present, the owner or
operator of a storage vessel equipped
with an external floating roof shall
notify the Administrator of any seal gap
measurements. The notification shall be
made in writing at least 30 calendar
days in advance of any gap
measurements required by § 63.120(b)(1)
or (2) of subpart G or § 63.1062(d)(3) of
subpart WW. The State or local
permitting authority can waive this
notification requirement for all or some
storage vessels subject to the rule or can
allow less than 30 calendar days’ notice.
*
*
*
*
*
(5) * * *
(iii) An owner or operator may use an
automated data compression recording
system that does not record monitored
operating parameter values at a set
frequency (for example, once every
hour) but records all values that meet
set criteria for variation from previously
recorded values.
(A) The system shall be designed to:
(1) Measure the operating parameter
value at least once every hour.
(2) Record at least 24 values each day
during periods of operation.
(3) Record the date and time when
monitors are turned off or on.
(4) Recognize unchanging data that
may indicate the monitor is not
functioning properly, alert the operator,
and record the incident.
(5) Compute daily average values of
the monitored operating parameter
based on recorded data.
(B) You must maintain a record of the
description of the monitoring system
and data compression recording system
including the criteria used to determine
which monitored values are recorded
and retained, the method for calculating
daily averages, and a demonstrations
that they system meets all criteria of
paragraph (h)(5)(iii)(A) of this section.
*
*
*
*
*
(8) For fenceline monitoring systems
subject to § 63.658, within 45 calendar
days after the end of each quarterly
reporting period covered by the periodic
report, each owner or operator shall
submit the following information to the
EPA’s Compliance and Emissions Data
Reporting Interface (CEDRI). (CEDRI can
be accessed through the EPA’s Central
Data Exchange (CDX) (https://
cdx.epa.gov/). The owner or operator
need not transmit this data prior to
obtaining 12 months of data.
PO 00000
Frm 00074
Fmt 4701
Sfmt 4700
(i) Individual sample results for each
monitor for each sampling period
during the quarterly reporting period.
For the first reporting period and for any
period in which a passive monitor is
added or moved, the owner or operator
shall report the coordinates of all of the
passive monitor locations. The owner or
operator shall determine the coordinates
using an instrument with an accuracy of
at least 3 meters. Coordinates shall be in
decimal degrees with at least five
decimal places.
(ii) The biweekly annual average
concentration difference (Dc) values for
benzene for the quarterly reporting
period.
(iii) Notation for each biweekly value
that indicates whether background
correction was used, all measurements
in the sampling period were below
detection, or whether an outlier was
removed from the sampling period data
set.
(9) On and after February 1, 2016, if
required to submit the results of a
performance test or CEMS performance
evaluation, the owner or operator shall
submit the results according to the
procedures in paragraphs (h)(9)(i) and
(ii) of this section.
(i) Within 60 days after the date of
completing each performance test as
required by this subpart, the owner or
operator shall submit the results of the
performance tests following the
procedure specified in either paragraph
(h)(9)(i)(A) or (B) of this section.
(A) For data collected using test
methods supported by the EPA’s
Electronic Reporting Tool (ERT) as
listed on the EPA’s ERT Web site
(https://www.epa.gov/ttn/chief/ert/
index.html) at the time of the test, the
owner or operator must submit the
results of the performance test to the
EPA via the CEDRI. (CEDRI can be
accessed through the EPA’s CDX.)
Performance test data must be submitted
in a file format generated through the
use of the EPA’s ERT or an alternate
electronic file format consistent with the
extensible markup language (XML)
schema listed on the EPA’s ERT Web
site. If an owner or operator claims that
some of the performance test
information being submitted is
confidential business information (CBI),
the owner or operator must submit a
complete file generated through the use
of the EPA’s ERT or an alternate
electronic file consistent with the XML
schema listed on the EPA’s ERT Web
site, including information claimed to
be CBI, on a compact disc, flash drive
or other commonly used electronic
storage media to the EPA. The electronic
storage media must be clearly marked as
CBI and mailed to U.S. EPA/OAQPS/
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
CORE CBI Office, Attention: Group
Leader, Measurement Policy Group, MD
C404–02, 4930 Old Page Rd., Durham,
NC 27703. The same ERT or alternate
file with the CBI omitted must be
submitted to the EPA via the EPA’s CDX
as described earlier in this paragraph
(h)(9)(i)(A).
(B) For data collected using test
methods that are not supported by the
EPA’s ERT as listed on the EPA’s ERT
Web site at the time of the test, the
owner or operator must submit the
results of the performance test to the
Administrator at the appropriate
address listed in § 63.13.
(ii) Within 60 days after the date of
completing each CEMS performance
evaluation as required by this subpart,
the owner or operator must submit the
results of the performance evaluation
following the procedure specified in
either paragraph (h)(9)(ii)(A) or (B) of
this section.
(A) For performance evaluations of
continuous monitoring systems
measuring relative accuracy test audit
(RATA) pollutants that are supported by
the EPA’s ERT as listed on the EPA’s
ERT Web site at the time of the
evaluation, the owner or operator must
submit the results of the performance
evaluation to the EPA via the CEDRI.
(CEDRI can be accessed through the
EPA’s CDX.) Performance evaluation
data must be submitted in a file format
generated through the use of the EPA’s
ERT or an alternate file format
consistent with the XML schema listed
on the EPA’s ERT Web site. If an owner
or operator claims that some of the
performance evaluation information
being submitted is CBI, the owner or
operator must submit a complete file
generated through the use of the EPA’s
ERT or an alternate electronic file
consistent with the XML schema listed
on the EPA’s ERT Web site, including
information claimed to be CBI, on a
compact disc, flash drive or other
commonly used electronic storage
media to the EPA. The electronic storage
media must be clearly marked as CBI
and mailed to U.S. EPA/OAQPS/CORE
CBI Office, Attention: Group Leader,
Measurement Policy Group, MD C404–
02, 4930 Old Page Rd., Durham, NC
27703. The same ERT or alternate file
with the CBI omitted must be submitted
to the EPA via the EPA’s CDX as
described earlier in this paragraph
(h)(9)(ii)(A).
(B) For any performance evaluations
of continuous monitoring systems
measuring RATA pollutants that are not
supported by the EPA’s ERT as listed on
the EPA’s ERT Web site at the time of
the evaluation, the owner or operator
must submit the results of the
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
performance evaluation to the
Administrator at the appropriate
address listed in § 63.13.
(i) Recordkeeping. Each owner or
operator of a source subject to this
subpart shall keep copies of all
applicable reports and records required
by this subpart for at least 5 years except
as otherwise specified in paragraphs
(i)(1) through (12) of this section. All
applicable records shall be maintained
in such a manner that they can be
readily accessed within 24 hours.
Records may be maintained in hard
copy or computer-readable form
including, but not limited to, on paper,
microfilm, computer, flash drive, floppy
disk, magnetic tape, or microfiche.
(1) Each owner or operator subject to
the storage vessel provisions in § 63.646
shall keep the records specified in
§ 63.123 of subpart G except as specified
in paragraphs (i)(1)(i) through (iv) of this
section. Each owner or operator subject
to the storage vessel provisions in
§ 63.660 shall keep records as specified
in paragraphs (i)(1)(v) and (vi) of this
section.
*
*
*
*
*
(ii) All references to § 63.122 in
§ 63.123 of subpart G shall be replaced
with § 63.655(e).
*
*
*
*
*
(v) Each owner or operator of a Group
1 storage vessel subject to the provisions
in § 63.660 shall keep records as
specified in § 63.1065 or § 63.998, as
applicable.
(vi) Each owner or operator of a Group
2 storage vessel shall keep the records
specified in § 63.1065(a) of subpart WW.
If a storage vessel is determined to be
Group 2 because the weight percent
total organic HAP of the stored liquid is
less than or equal to 4 percent for
existing sources or 2 percent for new
sources, a record of any data,
assumptions, and procedures used to
make this determination shall be
retained.
*
*
*
*
*
(4) For each closed vent system that
contains bypass lines that could divert
a vent stream away from the control
device and either directly to the
atmosphere or to a control device that
does not comply with the requirements
in § 63.643(a), the owner or operator
shall keep a record of the information
specified in either paragraph (i)(4)(i) or
(ii) of this section, as applicable.
(i) The owner or operator shall
maintain records of periods when flow
was detected in the bypass line,
including the date and time and the
duration of the flow in the bypass line.
For each flow event, the owner or
operator shall maintain records
PO 00000
Frm 00075
Fmt 4701
Sfmt 4700
75251
sufficient to determine whether or not
the detected flow included flow of a
Group 1 miscellaneous process vent
stream requiring control. For periods
when the Group 1 miscellaneous
process vent stream requiring control is
diverted from the control device and
released either directly to the
atmosphere or to a control device that
does not comply with the requirements
in § 63.643(a), the owner or operator
shall include an estimate of the volume
of gas, the concentration of organic HAP
in the gas and the resulting emissions of
organic HAP that bypassed the control
device using process knowledge and
engineering estimates.
(ii) Where a seal mechanism is used
to comply with § 63.644(c)(2), hourly
records of flow are not required. In such
cases, the owner or operator shall record
the date that the monthly visual
inspection of the seals or closure
mechanisms is completed. The owner or
operator shall also record the
occurrence of all periods when the seal
or closure mechanism is broken, the
bypass line valve position has changed
or the key for a lock-and-key type lock
has been checked out. The owner or
operator shall include an estimate of the
volume of gas, the concentration of
organic HAP in the gas and the resulting
mass emissions of organic HAP from the
Group 1 miscellaneous process vent
stream requiring control that bypassed
the control device or records sufficient
to demonstrate that there was no flow of
a Group 1 miscellaneous process vent
stream requiring control during the
period.
(5) The owner or operator of a heat
exchange system subject to this subpart
shall comply with the recordkeeping
requirements in paragraphs (i)(5)(i)
through (v) of this section and retain
these records for 5 years.
*
*
*
*
*
(7) Each owner or operator subject to
the delayed coking unit decoking
operations provisions in § 63.657 must
maintain records specified in
paragraphs (i)(7)(i) through (iii) of this
section.
(i) The average pressure or
temperature, as applicable, for the 5minute period prior to venting to the
atmosphere, draining, or deheading the
coke drum for each cooling cycle for
each coke drum.
(ii) If complying with the 60-cycle
rolling average, each 60-cycle rolling
average pressure or temperature, as
applicable, considering all coke drum
venting events in the existing affected
source.
(iii) For double-quench cooling
cycles:
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75252
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
(A) The date, time and duration of
each pre-vent draining event.
(B) The pressure or temperature of the
coke drum vessel, as applicable, for the
15 minute period prior to the pre-vent
draining.
(C) The drain water temperature at 1minute intervals from the start of prevent draining to the complete closure of
the drain valve.
(8) For fenceline monitoring systems
subject to § 63.658, each owner or
operator shall keep the records specified
in paragraphs (i)(8)(i) through (x) of this
section on an ongoing basis.
(i) Coordinates of all passive
monitors, including replicate samplers
and field blanks, and if applicable, the
meteorological station. The owner or
operator shall determine the coordinates
using an instrument with an accuracy of
at least 3 meters. The coordinates shall
be in decimal degrees with at least five
decimal places.
(ii) The start and stop times and dates
for each sample, as well as the tube
identifying information.
(iii) Sampling period average
temperature and barometric pressure
measurements.
(iv) For each outlier determined in
accordance with Section 9.2 of Method
325A of appendix A of this part, the
sampler location of and the
concentration of the outlier and the
evidence used to conclude that the
result is an outlier.
(v) For samples that will be adjusted
for a background, the location of and the
concentration measured simultaneously
by the background sampler, and the
perimeter samplers to which it applies.
(vi) Individual sample results, the
calculated Dc for benzene for each
sampling period and the two samples
used to determine it, whether
background correction was used, and
the annual average Dc calculated after
each sampling period.
(vii) Method detection limit for each
sample, including co-located samples
and blanks.
(viii) Documentation of corrective
action taken each time the action level
was exceeded.
(ix) Other records as required by
Methods 325A and 325B of appendix A
of this part.
(x) If a near-field source correction is
used as provided in § 63.658(i), records
of hourly meteorological data, including
temperature, barometric pressure, wind
speed and wind direction, calculated
daily unit vector wind direction and
daily sigma theta, and other records
specified in the site-specific monitoring
plan.
(9) For each flare subject to § 63.670,
each owner or operator shall keep the
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
records specified in paragraphs (i)(9)(i)
through (xii) of this section up-to-date
and readily accessible, as applicable.
(i) Retain records of the output of the
monitoring device used to detect the
presence of a pilot flame as required in
§ 63.670(b) for a minimum of 2 years.
Retain records of each 15-minute block
during which there was at least one
minute that no pilot flame is present
when regulated material is routed to a
flare for a minimum of 5 years.
(ii) Retain records of daily visible
emissions observations or video
surveillance images required in
§ 63.670(h) as specified in the
paragraphs (i)(9)(ii)(A) through (C), as
applicable, for a minimum of 3 years.
(A) If visible emissions observations
are performed using Method 22 at 40
CFR part 60, appendix A–7, the record
must identify whether the visible
emissions observation was performed,
the results of each observation, total
duration of observed visible emissions,
and whether it was a 5-minute or 2-hour
observation. If the owner or operator
performs visible emissions observations
more than one time during a day, the
record must also identify the date and
time of day each visible emissions
observation was performed.
(B) If video surveillance camera is
used, the record must include all video
surveillance images recorded, with time
and date stamps.
(C) For each 2 hour period for which
visible emissions are observed for more
than 5 minutes in 2 consecutive hours,
the record must include the date and
time of the 2 hour period and an
estimate of the cumulative number of
minutes in the 2 hour period for which
emissions were visible.
(iii) The 15-minute block average
cumulative flows for flare vent gas and,
if applicable, total steam, perimeter
assist air, and premix assist air specified
to be monitored under § 63.670(i), along
with the date and time interval for the
15-minute block. If multiple monitoring
locations are used to determine
cumulative vent gas flow, total steam,
perimeter assist air, and premix assist
air, retain records of the 15-minute
block average flows for each monitoring
location for a minimum of 2 years, and
retain the 15-minute block average
cumulative flows that are used in
subsequent calculations for a minimum
of 5 years. If pressure and temperature
monitoring is used, retain records of the
15-minute block average temperature,
pressure and molecular weight of the
flare vent gas or assist gas stream for
each measurement location used to
determine the 15-minute block average
cumulative flows for a minimum of 2
years, and retain the 15-minute block
PO 00000
Frm 00076
Fmt 4701
Sfmt 4700
average cumulative flows that are used
in subsequent calculations for a
minimum of 5 years.
(iv) The flare vent gas compositions
specified to be monitored under
§ 63.670(j). Retain records of individual
component concentrations from each
compositional analyses for a minimum
of 2 years. If NHVvg analyzer is used,
retain records of the 15-minute block
average values for a minimum of 5
years.
(v) Each 15-minute block average
operating parameter calculated
following the methods specified in
§ 63.670(k) through (n), as applicable.
(vi) [Reserved]
(vii) All periods during which
operating values are outside of the
applicable operating limits specified in
§ 63.670(d) through (f) when regulated
material is being routed to the flare.
(viii) All periods during which the
owner or operator does not perform flare
monitoring according to the procedures
in § 63.670(g) through (j).
(ix) Records of periods when there is
flow of vent gas to the flare, but when
there is no flow of regulated material to
the flare, including the start and stop
time and dates of periods of no
regulated material flow.
(x) Records when the flow of vent gas
exceeds the smokeless capacity of the
flare, including start and stop time and
dates of the flaring event.
(xi) Records of the root cause analysis
and corrective action analysis
conducted as required in § 63.670(o)(3),
including an identification of the
affected facility, the date and duration
of the event, a statement noting whether
the event resulted from the same root
cause(s) identified in a previous
analysis and either a description of the
recommended corrective action(s) or an
explanation of why corrective action is
not necessary under § 63.670(o)(5)(i).
(xii) For any corrective action analysis
for which implementation of corrective
actions are required in § 63.670(o)(5), a
description of the corrective action(s)
completed within the first 45 days
following the discharge and, for
action(s) not already completed, a
schedule for implementation, including
proposed commencement and
completion dates.
(10) [Reserved]
(11) For each pressure relief device
subject to the pressure release
management work practice standards in
§ 63.648(j)(3), the owner or operator
shall keep the records specified in
paragraphs (i)(11)(i) through (iii) of this
section.
(i) Records of the prevention measures
implemented as required in
§ 63.648(j)(3)(ii), if applicable.
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
(ii) Records of the number of releases
during each calendar year and the
number of those releases for which the
root cause was determined to be a force
majeure event. Keep these records for
the current calendar year and the past
five calendar years.
(iii) For each release to the
atmosphere, the owner or operator shall
keep the records specified in paragraphs
(i)(11)(iii)(A) through (D) of this section.
(A) The start and end time and date
of each pressure release to the
atmosphere.
(B) Records of any data, assumptions,
and calculations used to estimate of the
mass quantity of each organic HAP
released during the event.
(C) Records of the root cause analysis
and corrective action analysis
conducted as required in
§ 63.648(j)(3)(iii), including an
identification of the affected facility, the
date and duration of the event, a
statement noting whether the event
resulted from the same root cause(s)
identified in a previous analysis and
either a description of the recommended
corrective action(s) or an explanation of
why corrective action is not necessary
under § 63.648(j)(7)(i).
(D) For any corrective action analysis
for which implementation of corrective
actions are required in § 63.648(j)(7), a
description of the corrective action(s)
completed within the first 45 days
following the discharge and, for
action(s) not already completed, a
schedule for implementation, including
proposed commencement and
completion dates.
(12) For each maintenance vent
opening subject to the requirements in
§ 63.643(c), the owner or operator shall
keep the applicable records specified in
(i)(12)(i) through (v) of this section.
(i) The owner or operator shall
maintain standard site procedures used
to deinventory equipment for safety
purposes (e.g., hot work or vessel entry
procedures) to document the procedures
used to meet the requirements in
§ 63.643(c). The current copy of the
procedures shall be retained and
available on-site at all times. Previous
versions of the standard site procedures,
is applicable, shall be retained for five
years.
(ii) If complying with the
requirements of § 63.643(c)(1)(i) and the
lower explosive limit at the time of the
vessel opening exceeds 10 percent,
identification of the maintenance vent,
the process units or equipment
associated with the maintenance vent,
the date of maintenance vent opening,
and the lower explosive limit at the time
of the vessel opening.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(iii) If complying with the
requirements of § 63.643(c)(1)(ii) and
either the vessel pressure at the time of
the vessel opening exceeds 5 psig or the
lower explosive limit at the time of the
active purging was initiated exceeds 10
percent, identification of the
maintenance vent, the process units or
equipment associated with the
maintenance vent, the date of
maintenance vent opening, the pressure
of the vessel or equipment at the time
of discharge to the atmosphere and, if
applicable, the lower explosive limit of
the vapors in the equipment when
active purging was initiated.
(iv) If complying with the
requirements of § 63.643(c)(1)(iii),
identification of the maintenance vent,
the process units or equipment
associated with the maintenance vent,
the date of maintenance vent opening,
and records used to estimate the total
quantity of VOC in the equipment at the
time the maintenance vent was opened
to the atmosphere for each applicable
maintenance vent opening.
(v) If complying with the
requirements of § 63.643(c)(1)(iv),
identification of the maintenance vent,
the process units or equipment
associated with the maintenance vent,
records documenting the lack of a pure
hydrogen supply, the date of
maintenance vent opening, and the
lower explosive limit of the vapors in
the equipment at the time of discharge
to the atmosphere for each applicable
maintenance vent opening.
28. Section 63.656 is amended by
revising paragraph (c)(1) to read as
follows:
■
§ 63.656
Implementation and enforcement.
*
*
*
*
*
(c) * * *
(1) Approval of alternatives to the
requirements in §§ 63.640, 63.642(g)
through (l), 63.643, 63.646 through
63.652, 63.654, 63.657 through 63.660,
and 63.670. Where these standards
reference another subpart, the cited
provisions will be delegated according
to the delegation provisions of the
referenced subpart. Where these
standards reference another subpart and
modify the requirements, the
requirements shall be modified as
described in this subpart. Delegation of
the modified requirements will also
occur according to the delegation
provisions of the referenced subpart.
*
*
*
*
*
29. Section 63.657 is added to read as
follows:
■
PO 00000
Frm 00077
Fmt 4701
Sfmt 4700
75253
§ 63.657 Delayed coking unit decoking
operation standards.
(a) Except as provided in paragraphs
(e) and (f) of this section, each owner or
operator of a delayed coking unit shall
depressure each coke drum to a closed
blowdown system until the coke drum
vessel pressure or temperature
measured at the top of the coke drum or
in the overhead line of the coke drum
as near as practical to the coke drum
meets the applicable limits specified in
paragraph (a)(1) or (2) of this section
prior to venting to the atmosphere,
draining or deheading the coke drum at
the end of the cooling cycle.
(1) For delayed coking units at an
existing affected source, meet either:
(i) An average vessel pressure of 2
psig determined on a rolling 60-event
average; or
(ii) An average vessel temperature of
220 degrees Fahrenheit determined on a
rolling 60-event average.
(2) For delayed coking units at a new
affected source, meet either:
(i) A vessel pressure of 2.0 psig for
each decoking event; or
(ii) A vessel temperature of 218
degrees Fahrenheit for each decoking
event.
(b) Each owner or operator of a
delayed coking unit complying with the
pressure limits in paragraph (a)(1)(i) or
(a)(2)(i) of this section shall install,
operate, calibrate, and maintain a
monitoring system, as specified in
paragraphs (b)(1) through (5) of this
section, to determine the coke drum
vessel pressure.
(1) The pressure monitoring system
must be in a representative location (at
the top of the coke drum or in the
overhead line as near as practical to the
coke drum) that minimizes or eliminates
pulsating pressure, vibration, and, to the
extent practical, internal and external
corrosion.
(2) The pressure monitoring system
must be capable of measuring a pressure
of 2.0 psig within ±0.5 psig.
(3) The pressure monitoring system
must be verified annually or at the
frequency recommended by the
instrument manufacturer. The pressure
monitoring system must be verified
following any period of more than 24
hours throughout which the pressure
exceeded the maximum rated pressure
of the sensor, or the data recorder was
off scale.
(4) All components of the pressure
monitoring system must be visually
inspected for integrity, oxidation and
galvanic corrosion every 3 months,
unless the system has a redundant
pressure sensor.
(5) The output of the pressure
monitoring system must be reviewed
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75254
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
daily to ensure that the pressure
readings fluctuate as expected between
operating and cooling/decoking cycles
to verify the pressure taps are not
plugged. Plugged pressure taps must be
unplugged or otherwise repaired prior
to the next operating cycle.
(c) Each owner or operator of a
delayed coking unit complying with the
temperature limits in paragraph (a)(1)(ii)
or (a)(2)(ii) of this section shall install,
operate, calibrate, and maintain a
continuous parameter monitoring
system to measure the coke drum vessel
temperature (at the top of the coke drum
or in the overhead line as near as
practical to the coke drum) according to
the requirements specified in table 13 of
this subpart.
(d) The owner or operator of a delayed
coking unit shall determine the coke
drum vessel pressure or temperature, as
applicable, on a 5-minute rolling
average basis while the coke drum is
vented to the closed blowdown system
and shall use the last complete 5-minute
rolling average pressure or temperature
just prior to initiating steps to isolate the
coke drum prior to venting, draining or
deheading to demonstrate compliance
with the requirements in paragraph (a)
of this section. Pressure or temperature
readings after initiating steps to isolate
the coke drum from the closed
blowdown system just prior to
atmospheric venting, draining, or
deheading the coke drum shall not be
used in determining the average coke
drum vessel pressure or temperature for
the purpose of compliance with the
requirements in paragraph (a) of this
section.
(e) The owner or operator of a delayed
coking unit using the ‘‘water overflow’’
method of coke cooling must hardpipe
the overflow water or otherwise prevent
exposure of the overflow water to the
atmosphere when transferring the
overflow water to the overflow water
storage tank whenever the coke drum
vessel temperature exceeds 220 degrees
Fahrenheit. The overflow water storage
tank may be an open or fixed-roof tank
provided that a submerged fill pipe
(pipe outlet below existing liquid level
in the tank) is used to transfer overflow
water to the tank. The owner or operator
of a delayed coking unit using the
‘‘water overflow’’ method of coke
cooling shall determine the coke drum
vessel temperature as specified in
paragraphs (c) and (d) of this section
regardless of the compliance method
used to demonstrate compliance with
the requirements in paragraph (a) of this
section.
(f) The owner or operator of a delayed
coking unit may partially drain a coke
drum prior to achieving the applicable
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
limits in paragraph (a) of this section in
order to double-quench a coke drum
that did not cool adequately using the
normal cooling process steps provided
that the owner or operator meets the
conditions in paragraphs (f)(1) and (2) of
this section.
(1) The owner or operator shall
install, operate, calibrate, and maintain
a continuous parameter monitoring
system to measure the drain water
temperature at the bottom of the coke
drum or in the drain line as near as
practical to the coke drum according to
the requirements specified in table 13 of
this subpart.
(2) The owner or operator must
maintain the drain water temperature
below 210 degrees Fahrenheit during
the partial drain associated with the
double-quench event.
■ 30. Section 63.658 is added to read as
follows:
§ 63.658
Fenceline monitoring provisions.
(a) The owner or operator shall
conduct sampling along the facility
property boundary and analyze the
samples in accordance with Methods
325A and 325B of appendix A of this
part and paragraphs (b) through (k) of
this section.
(b) The target analyte is benzene.
(c) The owner or operator shall
determine passive monitor locations in
accordance with Section 8.2 of Method
325A of appendix A of this part.
(1) As it pertains to this subpart,
known sources of VOCs, as used in
Section 8.2.1.3 in Method 325A of
appendix A of this part for siting
passive monitors means a wastewater
treatment unit, process unit, or any
emission source requiring control
according to the requirements of this
subpart, including marine vessel
loading operations. For marine loading
operations that are located offshore, one
passive monitor should be sited on the
shoreline adjacent to the dock.
(2) The owner or operator may collect
one or more background samples if the
owner or operator believes that an
offsite upwind source or an onsite
source excluded under § 63.640(g) may
influence the sampler measurements. If
the owner or operator elects to collect
one or more background samples, the
owner of operator must develop and
submit a site-specific monitoring plan
for approval according to the
requirements in paragraph (i) of this
section. Upon approval of the sitespecific monitoring plan, the
background sampler(s) should be
operated co-currently with the routine
samplers.
(3) The owner or operator shall collect
at least one co-located duplicate sample
PO 00000
Frm 00078
Fmt 4701
Sfmt 4700
for every 10 field samples per sampling
period and at least two field blanks per
sampling period, as described in Section
9.3 in Method 325A of appendix A of
this part. The co-located duplicates may
be collected at any one of the perimeter
sampling locations.
(4) The owner or operator shall follow
the procedure in Section 9.6 of Method
325B of appendix A of this part to
determine the detection limit of benzene
for each sampler used to collect
samples, background samples (if the
owner or operator elects to do so), colocated samples and blanks.
(d) The owner or operator shall collect
and record meteorological data
according to the applicable
requirements in paragraphs (d)(1)
through (3) of this section.
(1) If a near-field source correction is
used as provided in paragraph (i)(1) of
this section or if an alternative test
method is used that provides timeresolved measurements, the owner or
operator shall:
(i) Use an on-site meteorological
station in accordance with Section 8.3
of Method 325A of appendix A of this
part.
(ii) Collect and record hourly average
meteorological data, including
temperature, barometric pressure, wind
speed and wind direction and calculate
daily unit vector wind direction and
daily sigma theta.
(2) For cases other than those
specified in paragraph (d)(1) of this
section, the owner or operator shall
collect and record sampling period
average temperature and barometric
pressure using either an on-site
meteorological station in accordance
with Section 8.3 of Method 325A of
appendix A of this part or, alternatively,
using data from a United States Weather
Service (USWS) meteorological station
provided the USWS meteorological
station is within 40 kilometers (25
miles) of the refinery.
(3) If an on-site meteorological station
is used, the owner or operator shall
follow the calibration and
standardization procedures for
meteorological measurements in EPA–
454/B–08–002 (incorporated by
reference—see § 63.14).
(e) The owner of operator shall use a
sampling period and sampling
frequency as specified in paragraphs
(e)(1) through (3) of this section.
(1) Sampling period. A 14-day
sampling period shall be used, unless a
shorter sampling period is determined
to be necessary under paragraph (g) or
(i) of this section. A sampling period is
defined as the period during which
sampling tube is deployed at a specific
sampling location with the diffusive
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
sampling end cap in-place and does not
include the time required to analyze the
sample. For the purpose of this subpart,
a 14-day sampling period may be no
shorter than 13 calendar days and no
longer than 15 calendar days, but the
routine sampling period shall be 14
calendar days.
(2) Base sampling frequency. Except
as provided in paragraph (e)(3) of this
section, the frequency of sample
collection shall be once each contiguous
14-day sampling period, such that the
beginning of the next 14-day sampling
period begins immediately upon the
completion of the previous 14-day
sampling period.
(3) Alternative sampling frequency for
burden reduction. When an individual
monitor consistently achieves results at
or below 0.9 mg/m3, the owner or
operator may elect to use the applicable
minimum sampling frequency specified
in paragraphs (e)(3)(i) through (v) of this
section for that monitoring site. When
calculating Dc for the monitoring period
when using this alternative for burden
reduction, zero shall be substituted for
the sample result for the monitoring site
for any period where a sample is not
taken.
(i) If every sample at a monitoring site
is at or below 0.9 mg/m3 for 2 years (52
consecutive samples), every other
sampling period can be skipped for that
monitoring site, i.e., sampling will occur
approximately once per month.
(ii) If every sample at a monitoring
site that is monitored at the frequency
specified in paragraph (e)(3)(i) of this
section is at or below 0.9 mg/m3 for 2
years (i.e., 26 consecutive ‘‘monthly’’
samples), five 14-day sampling periods
can be skipped for that monitoring site
following each period of sampling, i.e.,
sampling will occur approximately once
per quarter.
(iii) If every sample at a monitoring
site that is monitored at the frequency
specified in paragraph (e)(3)(ii) of this
section is at or below 0.9 mg/m3 for 2
years (i.e., 8 consecutive quarterly
samples), twelve 14-day sampling
periods can be skipped for that
monitoring site following each period of
sampling, i.e., sampling will occur twice
a year.
(iv) If every sample at a monitoring
site that is monitored at the frequency
specified in paragraph (e)(3)(iii) of this
section is at or below 0.9 mg/m3 for an
2 years (i.e., 4 consecutive semi-annual
samples), only one sample per year is
required for that monitoring site. For
yearly sampling, samples shall occur at
least 10 months but no more than 14
months apart.
(v) If at any time a sample for a
monitoring site that is monitored at the
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
frequency specified in paragraphs
(e)(3)(i) through (iv) of this section
returns a result that is above 0.9 mg/m3,
the sampling site must return to the
original sampling requirements of
contiguous 14-day sampling periods
with no skip periods for one quarter (six
14-day sampling periods). If every
sample collected during this quarter is
at or below 0.9 mg/m3 , the owner or
operator may revert back to the reduced
monitoring schedule applicable for that
monitoring site prior to the sample
reading exceeding 0.9 mg/m3 If any
sample collected during this quarter is
above 0.9 mg/m3, that monitoring site
must return to the original sampling
requirements of contiguous 14-day
sampling periods with no skip periods
for a minimum of two years. The burden
reduction requirements can be used
again for that monitoring site once the
requirements of paragraph (e)(3)(i) of
this section are met again, i.e., after 52
contiguous 14-day samples with no
results above 0.9 mg/m3 .
(f) Within 45 days of completion of
each sampling period, the owner or
operator shall determine whether the
results are above or below the action
level as follows:
(1) The owner or operator shall
determine the facility impact on the
benzene concentration (Dc) for each 14day sampling period according to either
paragraph (f)(1)(i) or (ii) of this section,
as applicable.
(i) Except when near-field source
correction is used as provided in
paragraph (i) of this section, the owner
or operator shall determine the highest
and lowest sample results for benzene
concentrations from the sample pool
and calculate Dc as the difference in
these concentrations. The owner or
operator shall adhere to the following
procedures when one or more samples
for the sampling period are below the
method detection limit for benzene:
(A) If the lowest detected value of
benzene is below detection, the owner
or operator shall use zero as the lowest
sample result when calculating Dc.
(B) If all sample results are below the
method detection limit, the owner or
operator shall use the method detection
limit as the highest sample result.
(ii) When near-field source correction
is used as provided in paragraph (i) of
this section, the owner or operator shall
determine Dc using the calculation
protocols outlined in the approved sitespecific monitoring plan and in
paragraph (i) of this section.
(2) The owner or operator shall
calculate the annual average Dc based
on the average of the 26 most recent 14day sampling periods. The owner or
operator shall update this annual
PO 00000
Frm 00079
Fmt 4701
Sfmt 4700
75255
average value after receiving the results
of each subsequent 14-day sampling
period.
(3) The action level for benzene is 9
micrograms per cubic meter (mg/m3) on
an annual average basis. If the annual
average Dc value for benzene is less than
or equal to 9 mg/m3, the concentration
is below the action level. If the annual
average Dc value for benzene is greater
than 9 mg/m3, the concentration is above
the action level, and the owner or
operator shall conduct a root cause
analysis and corrective action in
accordance with paragraph (g) of this
section.
(g) Within 5 days of determining that
the action level has been exceeded for
any annual average Dc and no longer
than 50 days after completion of the
sampling period, the owner or operator
shall initiate a root cause analysis to
determine the cause of such exceedance
and to determine appropriate corrective
action, such as those described in
paragraphs (g)(1) through (4) of this
section. The root cause analysis and
initial corrective action analysis shall be
completed and initial corrective actions
taken no later than 45 days after
determining there is an exceedance.
Root cause analysis and corrective
action may include, but is not limited
to:
(1) Leak inspection using Method 21
of part 60, appendix A–7 of this chapter
and repairing any leaks found.
(2) Leak inspection using optical gas
imaging and repairing any leaks found.
(3) Visual inspection to determine the
cause of the high benzene emissions and
implementing repairs to reduce the level
of emissions.
(4) Employing progressively more
frequent sampling, analysis and
meteorology (e.g., using shorter
sampling periods for Methods 325A and
325B of appendix A of this part, or
using active sampling techniques).
(h) If, upon completion of the
corrective action analysis and corrective
actions such as those described in
paragraph (g) of this section, the Dc
value for the next 14-day sampling
period for which the sampling start time
begins after the completion of the
corrective actions is greater than 9 mg/
m3 or if all corrective action measures
identified require more than 45 days to
implement, the owner or operator shall
develop a corrective action plan that
describes the corrective action(s)
completed to date, additional measures
that the owner or operator proposes to
employ to reduce fenceline
concentrations below the action level,
and a schedule for completion of these
measures. The owner or operator shall
submit the corrective action plan to the
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75256
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Administrator within 60 days after
receiving the analytical results
indicating that the Dc value for the 14day sampling period following the
completion of the initial corrective
action is greater than 9 mg/m3 or, if no
initial corrective actions were
identified, no later than 60 days
following the completion of the
corrective action analysis required in
paragraph (g) of this section.
(i) An owner or operator may request
approval from the Administrator for a
site-specific monitoring plan to account
for offsite upwind sources or onsite
sources excluded under § 63.640(g)
according to the requirements in
paragraphs (i)(1) through (4) of this
section.
(1) The owner or operator shall
prepare and submit a site-specific
monitoring plan and receive approval of
the site-specific monitoring plan prior to
using the near-field source alternative
calculation for determining Dc provided
in paragraph (i)(2) of this section. The
site-specific monitoring plan shall
include, at a minimum, the elements
specified in paragraphs (i)(1)(i) through
(v) of this section. The procedures in
Section 12 of Method 325A of appendix
A of this part are not required, but may
be used, if applicable, when
determining near-field source
contributions.
(i) Identification of the near-field
source or sources. For onsite sources,
documentation that the onsite source is
excluded under § 63.640(g) and
identification of the specific provision
in § 63.640(g) that applies to the source.
(ii) Location of the additional
monitoring stations that shall be used to
determine the uniform background
concentration and the near-field source
concentration contribution.
(iii) Identification of the fenceline
monitoring locations impacted by the
near-field source. If more than one nearfield source is present, identify the nearfield source or sources that are expected
to contribute to the concentration at that
monitoring location.
(iv) A description of (including
sample calculations illustrating) the
planned data reduction and calculations
to determine the near-field source
concentration contribution for each
monitoring location.
(v) If more frequent monitoring or a
monitoring station other than a passive
diffusive tube monitoring station is
proposed, provide a detailed description
of the measurement methods,
measurement frequency, and recording
frequency for determining the uniform
background or near-field source
concentration contribution.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(2) When an approved site-specific
monitoring plan is used, the owner or
operator shall determine Dc for
comparison with the 9 mg/m3 action
level using the requirements specified
in paragraphs (i)(2)(i) through (iii) of
this section.
(i) For each monitoring location,
calculate Dci using the following
equation.
Dci = MFCi ¥ NFSi ¥ UB
Where:
Dci = The fenceline concentration, corrected
for background, at measurement location
i, micrograms per cubic meter (mg/m3).
MFCi = The measured fenceline
concentration at measurement location i,
mg/m3.
NFSi = The near-field source contributing
concentration at measurement location i
determined using the additional
measurements and calculation
procedures included in the site-specific
monitoring plan, mg/m3. For monitoring
locations that are not included in the
site-specific monitoring plan as impacted
by a near-field source, use NFSi = 0 mg/
m3.
UB = The uniform background concentration
determined using the additional
measurements included in the sitespecific monitoring plan, mg/m3. If no
additional measurements are specified in
the site-specific monitoring plan for
determining the uniform background
concentration, use UB = 0 mg/m3.
(ii) When one or more samples for the
sampling period are below the method
detection limit for benzene, adhere to
the following procedures:
(A) If the benzene concentration at the
monitoring location used for the
uniform background concentration is
below the method detection limit, the
owner or operator shall use zero for UB
for that monitoring period.
(B) If the benzene concentration at the
monitoring location(s) used to
determine the near-field source
contributing concentration is below the
method detection limit, the owner or
operator shall use zero for the
monitoring location concentration when
calculating NFSi for that monitoring
period.
(C) If a fenceline monitoring location
sample result is below the method
detection limit, the owner or operator
shall use the method detection limit as
the sample result.
(iii) Determine Dc for the monitoring
period as the maximum value of Dci
from all of the fenceline monitoring
locations for that monitoring period.
(3) The site-specific monitoring plan
shall be submitted and approved as
described in paragraphs (i)(3)(i) through
(iv) of this section.
PO 00000
Frm 00080
Fmt 4701
Sfmt 4700
(i) The site-specific monitoring plan
must be submitted to the Administrator
for approval.
(ii) The site-specific monitoring plan
shall also be submitted to the following
address: U.S. Environmental Protection
Agency, Office of Air Quality Planning
and Standards, Sector Policies and
Programs Division, U.S. EPA Mailroom
(E143–01), Attention: Refinery Sector
Lead, 109 T.W. Alexander Drive,
Research Triangle Park, NC 27711.
Electronic copies in lieu of hard copies
may also be submitted to refineryrtr@
epa.gov.
(iii) The Administrator shall approve
or disapprove the plan in 90 days. The
plan shall be considered approved if the
Administrator either approves the plan
in writing, or fails to disapprove the
plan in writing. The 90-day period shall
begin when the Administrator receives
the plan.
(iv) If the Administrator finds any
deficiencies in the site-specific
monitoring plan and disapproves the
plan in writing, the owner or operator
may revise and resubmit the sitespecific monitoring plan following the
requirements in paragraphs (i)(3)(i) and
(ii) of this section. The 90-day period
starts over with the resubmission of the
revised monitoring plan.
(4) The approval by the Administrator
of a site-specific monitoring plan will be
based on the completeness, accuracy
and reasonableness of the request for a
site-specific monitoring plan. Factors
that the Administrator will consider in
reviewing the request for a site-specific
monitoring plan include, but are not
limited to, those described in
paragraphs (i)(4)(i) through (v) of this
section.
(i) The identification of the near-field
source or sources. For onsite sources,
the documentation provided that the
onsite source is excluded under
§ 63.640(g).
(ii) The monitoring location selected
to determine the uniform background
concentration or an indication that no
uniform background concentration
monitor will be used.
(iii) The location(s) selected for
additional monitoring to determine the
near-field source concentration
contribution.
(iv) The identification of the fenceline
monitoring locations impacted by the
near-field source or sources.
(v) The appropriateness of the
planned data reduction and calculations
to determine the near-field source
concentration contribution for each
monitoring location.
(vi) If more frequent monitoring is
proposed, the adequacy of the
description of the measurement and
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
recording frequency proposed and the
adequacy of the rationale for using the
alternative monitoring frequency.
(j) The owner or operator shall
comply with the applicable
recordkeeping and reporting
requirements in § 63.655(h) and (i).
(k) As outlined in § 63.7(f), the owner
or operator may submit a request for an
alternative test method. At a minimum,
the request must follow the
requirements outlined in paragraphs
(k)(1) through (7) of this section.
(1) The alternative method may be
used in lieu of all or a partial number
of passive samplers required in Method
325A of appendix A of this part.
(2) The alternative method must be
validated according to Method 301 in
appendix A of this part or contain
performance based procedures and
indicators to ensure self-validation.
(3) The method detection limit must
nominally be at least an order of
magnitude below the action level, i.e.,
0.9 mg/m3 benzene. The alternate test
method must describe the procedures
used to provide field verification of the
detection limit.
(4) The spatial coverage must be equal
to or better than the spatial coverage
provided in Method 325A of appendix
A of this part.
(i) For path average concentration
open-path instruments, the physical
path length of the measurement shall be
no more than a passive sample footprint
(the spacing that would be provided by
the sorbent traps when following
Method 325A). For example, if Method
325A requires spacing monitors A and
B 610 meters (2000 feet) apart, then the
physical path length limit for the
measurement at that portion of the
fenceline shall be no more than 610
meters (2000 feet).
(ii) For range resolved open-path
instrument or approach, the instrument
or approach must be able to resolve an
average concentration over each passive
sampler footprint within the path length
of the instrument.
(iii) The extra samplers required in
Sections 8.2.1.3 of Method 325A may be
omitted when they fall within the path
length of an open-path instrument.
(5) At a minimum, non-integrating
alternative test methods must provide a
minimum of one cycle of operation
(sampling, analyzing, and data
recording) for each successive 15minute period.
(6) For alternative test methods
capable of real time measurements (less
than a 5 minute sampling and analysis
cycle), the alternative test method may
allow for elimination of data points
corresponding to outside emission
sources for purpose of calculation of the
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
high point for the two week average.
The alternative test method approach
must have wind speed, direction and
stability class of the same time
resolution and within the footprint of
the instrument.
(7) For purposes of averaging data
points to determine the Dc for the 14day average high sample result, all
results measured under the method
detection limit must use the method
detection limit. For purposes of
averaging data points for the 14-day
average low sample result, all results
measured under the method detection
limit must use zero.
■ 31. Section 63.660 is added to read as
follows:
§ 63.660
Storage vessel provisions.
On and after the applicable
compliance date for a Group 1 storage
vessel located at a new or existing
source as specified in § 63.640(h), the
owner or operator of a Group 1 storage
vessel that is part of a new or existing
source shall comply with the
requirements in subpart WW or SS of
this part according to the requirements
in paragraphs (a) through (i) of this
section.
(a) As used in this section, all terms
not defined in § 63.641 shall have the
meaning given them in subpart A, WW,
or SS of this part. The definitions of
‘‘Group 1 storage vessel’’ (paragraph (2))
and ‘‘Storage vessel’’ in § 63.641 shall
apply in lieu of the definition of
‘‘Storage vessel’’ in § 63.1061.
(1) An owner or operator may use
good engineering judgment or test
results to determine the stored liquid
weight percent total organic HAP for
purposes of group determination. Data,
assumptions, and procedures used in
the determination shall be documented.
(2) When an owner or operator and
the Administrator do not agree on
whether the annual average weight
percent organic HAP in the stored liquid
is above or below 4 percent for a storage
vessel at an existing source or above or
below 2 percent for a storage vessel at
a new source, an appropriate method
(based on the type of liquid stored) as
published by EPA or a consensus-based
standards organization shall be used.
Consensus-based standards
organizations include, but are not
limited to, the following: ASTM
International (100 Barr Harbor Drive,
P.O. Box CB700, West Conshohocken,
Pennsylvania 19428–B2959, (800) 262–
1373, https://www.astm.org), the
American National Standards Institute
(ANSI, 1819 L Street NW., 6th Floor,
Washington, DC 20036, (202) 293–8020,
https://www.ansi.org), the American Gas
Association (AGA, 400 North Capitol
PO 00000
Frm 00081
Fmt 4701
Sfmt 4700
75257
Street NW., 4th Floor, Washington, DC
20001, (202) 824–7000, https://
www.aga.org), the American Society of
Mechanical Engineers (ASME, Three
Park Avenue, New York, NY 10016–
5990, (800) 843–2763, https://
www.asme.org), the American
Petroleum Institute (API, 1220 L Street
NW., Washington, DC 20005–4070,
(202) 682–8000, https://www.api.org),
and the North American Energy
Standards Board (NAESB, 801 Travis
Street, Suite 1675, Houston, TX 77002,
(713) 356–0060, https://www.naesb.org).
(b) A floating roof storage vessel
complying with the requirements of
subpart WW of this part may comply
with the control option specified in
paragraph (b)(1) of this section and, if
equipped with a ladder having at least
one slotted leg, shall comply with one
of the control options as described in
paragraph (b)(2) of this section.
(1) In addition to the options
presented in §§ 63.1063(a)(2)(viii)(A)
and (B) and 63.1064, a floating roof
storage vessel may comply with
§ 63.1063(a)(2)(vii) using a flexible
enclosure device and either a gasketed
or welded cap on the top of the
guidepole.
(2) Each opening through a floating
roof for a ladder having at least one
slotted leg shall be equipped with one
of the configurations specified in
paragraphs (b)(2)(i) through (iii) of this
section.
(i) A pole float in the slotted leg and
pole wipers for both legs. The wiper or
seal of the pole float must be at or above
the height of the pole wiper.
(ii) A ladder sleeve and pole wipers
for both legs of the ladder.
(iii) A flexible enclosure device and
either a gasketed or welded cap on the
top of the slotted leg.
(c) For the purposes of this subpart,
references shall apply as specified in
paragraphs (c)(1) through (6) of this
section.
(1) All references to ‘‘the proposal
date for a referencing subpart’’ and ‘‘the
proposal date of the referencing
subpart’’ in subpart WW of this part
mean June 30, 2014.
(2) All references to ‘‘promulgation of
the referencing subpart’’ and ‘‘the
promulgation date of the referencing
subpart’’ in subpart WW of this part
mean February 1, 2016.
(3) All references to ‘‘promulgation
date of standards for an affected source
or affected facility under a referencing
subpart’’ in subpart SS of this part mean
February 1, 2016.
(4) All references to ‘‘the proposal
date of the relevant standard established
pursuant to CAA section 112(f)’’ in
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
subpart SS of this part mean June 30,
2014.
(5) All references to ‘‘the proposal
date of a relevant standard established
pursuant to CAA section 112(d)’’ in
subpart SS of this part mean July 14,
1994.
(6) All references to the ‘‘required
control efficiency’’ in subpart SS of this
part mean reduction of organic HAP
emissions by 95 percent or to an outlet
concentration of 20 ppmv.
(d) For an uncontrolled fixed roof
storage vessel that commenced
construction on or before June 30, 2014,
and that meets the definition of ‘‘Group
1 storage vessel’’, paragraph (2), in
§ 63.641 but not the definition of
‘‘Group 1 storage vessel’’, paragraph (1),
in § 63.641, the requirements of § 63.982
and/or § 63.1062 do not apply until the
next time the storage vessel is
completely emptied and degassed, or
January 30, 2026, whichever occurs
first.
(e) Failure to perform inspections and
monitoring required by this section
shall constitute a violation of the
applicable standard of this subpart.
(f) References in § 63.1066(a) to initial
startup notification requirements do not
apply.
(g) References to the Notification of
Compliance Status in § 63.999(b) mean
the Notification of Compliance Status
required by § 63.655(f).
(h) References to the Periodic Reports
in §§ 63.1066(b) and 63.999(c) mean the
Periodic Report required by § 63.655(g).
(i) Owners or operators electing to
comply with the requirements in
subpart SS of this part for a Group 1
storage vessel must comply with the
requirements in paragraphs (i)(1)
through (3) of this section.
(1) If a flare is used as a control
device, the flare shall meet the
requirements of § 63.670 instead of the
flare requirements in § 63.987.
(2) If a closed vent system contains a
bypass line, the owner or operator shall
comply with the provisions of either
§ 63.983(a)(3)(i) or (ii) for each closed
vent system that contains bypass lines
that could divert a vent stream either
directly to the atmosphere or to a
control device that does not comply
with the requirements in subpart SS of
this part. Except as provided in
paragraphs (i)(2)(i) and (ii) of this
section, use of the bypass at any time to
divert a Group 1 storage vessel to either
directly to the atmosphere or to a
control device that does not comply
with the requirements in subpart SS of
this part is an emissions standards
violation. Equipment such as low leg
drains and equipment subject to
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
§ 63.648 are not subject to this
paragraph (i)(2).
(i) If planned routine maintenance of
the control device cannot be performed
during periods that storage vessel
emissions are vented to the control
device or when the storage vessel is
taken out of service for inspections or
other planned maintenance reasons, the
owner or operator may bypass the
control device.
(ii) Periods for which storage vessel
control device may be bypassed for
planned routine maintenance of the
control device shall not exceed 240
hours per calendar year.
(3) If storage vessel emissions are
routed to a fuel gas system or process,
the fuel gas system or process shall be
operating at all times when regulated
emissions are routed to it. The
exception in § 63.984(a)(1) does not
apply.
■ 32. Section 63.670 is added to read as
follows:
§ 63.670 Requirements for flare control
devices.
On or before January 30, 2019, the
owner or operator of a flare used as a
control device for an emission point
subject to this subpart shall meet the
applicable requirements for flares as
specified in paragraphs (a) through (q)
of this section and the applicable
requirements in § 63.671. The owner or
operator may elect to comply with the
requirements of paragraph (r) of this
section in lieu of the requirements in
paragraphs (d) through (f) of this
section, as applicable.
(a) [Reserved]
(b) Pilot flame presence. The owner or
operator shall operate each flare with a
pilot flame present at all times when
regulated material is routed to the flare.
Each 15-minute block during which
there is at least one minute where no
pilot flame is present when regulated
material is routed to the flare is a
deviation of the standard. Deviations in
different 15-minute blocks from the
same event are considered separate
deviations. The owner or operator shall
monitor for the presence of a pilot flame
as specified in paragraph (g) of this
section.
(c) Visible emissions. The owner or
operator shall specify the smokeless
design capacity of each flare and operate
with no visible emissions, except for
periods not to exceed a total of 5
minutes during any 2 consecutive
hours, when regulated material is routed
to the flare and the flare vent gas flow
rate is less than the smokeless design
capacity of the flare. The owner or
operator shall monitor for visible
PO 00000
Frm 00082
Fmt 4701
Sfmt 4700
emissions from the flare as specified in
paragraph (h) of this section.
(d) Flare tip velocity. For each flare,
the owner or operator shall comply with
either paragraph (d)(1) or (2) of this
section, provided the appropriate
monitoring systems are in-place,
whenever regulated material is routed to
the flare for at least 15-minutes and the
flare vent gas flow rate is less than the
smokeless design capacity of the flare.
(1) Except as provided in paragraph
(d)(2) of this section, the actual flare tip
velocity (Vtip) must be less than 60 feet
per second. The owner or operator shall
monitor Vtipusing the procedures
specified in paragraphs (i) and (k) of this
section.
(2) Vtip must be less than 400 feet per
second and also less than the maximum
allowed flare tip velocity (Vmax) as
calculated according to the following
equation. The owner or operator shall
monitor Vtip using the procedures
specified in paragraphs (i) and (k) of this
section and monitor gas composition
and determine NHVvg using the
procedures specified in paragraphs (j)
and (l) of this section.
Where:
Vmax = Maximum allowed flare tip velocity,
ft/sec.
NHVvg = Net heating value of flare vent gas,
as determined by paragraph (l)(4) of this
section, Btu/scf.
1,212 = Constant.
850 = Constant.
(e) Combustion zone operating limits.
For each flare, the owner or operator
shall operate the flare to maintain the
net heating value of flare combustion
zone gas (NHVcz) at or above 270 British
thermal units per standard cubic feet
(Btu/scf) determined on a 15-minute
block period basis when regulated
material is routed to the flare for at least
15-minutes. The owner or operator shall
monitor and calculate NHVcz as
specified in paragraph (m) of this
section.
(f) Dilution operating limits for flares
with perimeter assist air. For each flare
actively receiving perimeter assist air,
the owner or operator shall operate the
flare to maintain the net heating value
dilution parameter (NHVdil) at or above
22 British thermal units per square foot
(Btu/ft2) determined on a 15-minute
block period basis when regulated
material is being routed to the flare for
at least 15-minutes. The owner or
operator shall monitor and calculate
NHVdil as specified in paragraph (n) of
this section.
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.008
tkelley on DSK3SPTVN1PROD with RULES2
75258
(g) Pilot flame monitoring. The owner
or operator shall continuously monitor
the presence of the pilot flame(s) using
a device (including, but not limited to,
a thermocouple, ultraviolet beam
sensor, or infrared sensor) capable of
detecting that the pilot flame(s) is
present.
(h) Visible emissions monitoring. The
owner or operator shall monitor visible
emissions while regulated materials are
vented to the flare. An initial visible
emissions demonstration must be
conducted using an observation period
of 2 hours using Method 22 at 40 CFR
part 60, appendix A–7. Subsequent
visible emissions observations must be
conducted using either the methods in
paragraph (h)(1) of this section or,
alternatively, the methods in paragraph
(h)(2) of this section. The owner or
operator must record and report any
instances where visible emissions are
observed for more than 5 minutes
during any 2 consecutive hours as
specified in § 63.655(g)(11)(ii).
(1) At least once per day, conduct
visible emissions observations using an
observation period of 5 minutes using
Method 22 at 40 CFR part 60, appendix
A–7. If at any time the owner or
operator sees visible emissions, even if
the minimum required daily visible
emission monitoring has already been
performed, the owner or operator shall
immediately begin an observation
period of 5 minutes using Method 22 at
40 CFR part 60, appendix A–7. If visible
emissions are observed for more than
one continuous minute during any 5minute observation period, the
observation period using Method 22 at
40 CFR part 60, appendix A–7 must be
extended to 2 hours or until 5-minutes
of visible emissions are observed.
(2) Use a video surveillance camera to
continuously record (at least one frame
every 15 seconds with time and date
stamps) images of the flare flame and a
reasonable distance above the flare
flame at an angle suitable for visual
emissions observations. The owner or
operator must provide real-time video
surveillance camera output to the
control room or other continuously
manned location where the camera
images may be viewed at any time.
(i) Flare vent gas, steam assist and air
assist flow rate monitoring. The owner
or operator shall install, operate,
calibrate, and maintain a monitoring
system capable of continuously
measuring, calculating, and recording
the volumetric flow rate in the flare
header or headers that feed the flare as
well as any supplemental natural gas
used. Different flow monitoring
methods may be used to measure
different gaseous streams that make up
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
the flare vent gas provided that the flow
rates of all gas streams that contribute to
the flare vent gas are determined. If
assist air or assist steam is used, the
owner or operator shall install, operate,
calibrate, and maintain a monitoring
system capable of continuously
measuring, calculating, and recording
the volumetric flow rate of assist air
and/or assist steam used with the flare.
If pre-mix assist air and perimeter assist
are both used, the owner or operator
shall install, operate, calibrate, and
maintain a monitoring system capable of
separately measuring, calculating, and
recording the volumetric flow rate of
premix assist air and perimeter assist air
used with the flare. Continuously
monitoring fan speed or power and
using fan curves is an acceptable
method for continuously monitoring
assist air flow rates.
(1) The flow rate monitoring systems
must be able to correct for the
temperature and pressure of the system
and output parameters in standard
conditions (i.e., a temperature of 20 °C
(68 °F) and a pressure of 1 atmosphere).
(2) Mass flow monitors may be used
for determining volumetric flow rate of
flare vent gas provided the molecular
weight of the flare vent gas is
determined using compositional
analysis as specified in paragraph (j) of
this section so that the mass flow rate
can be converted to volumetric flow at
standard conditions using the following
equation.
Where:
Qvol = Volumetric flow rate, standard cubic
feet per second.
Qmass = Mass flow rate, pounds per second.
385.3 = Conversion factor, standard cubic
feet per pound-mole.
MWt = Molecular weight of the gas at the
flow monitoring location, pounds per
pound-mole.
(3) Mass flow monitors may be used
for determining volumetric flow rate of
assist air or assist steam. Use equation
in paragraph (i)(2) of this section to
convert mass flow rates to volumetric
flow rates. Use a molecular weight of 18
pounds per pound-mole for assist steam
and use a molecular weight of 29
pounds per pound-mole for assist air.
(4) Continuous pressure/temperature
monitoring system(s) and appropriate
engineering calculations may be used in
lieu of a continuous volumetric flow
monitoring systems provided the
molecular weight of the gas is known.
For assist steam, use a molecular weight
of 18 pounds per pound-mole. For assist
air, use a molecular weight of 29 pounds
PO 00000
Frm 00083
Fmt 4701
Sfmt 4700
75259
per pound-mole. For flare vent gas,
molecular weight must be determined
using compositional analysis as
specified in paragraph (j) of this section.
(j) Flare vent gas composition
monitoring. The owner or operator shall
determine the concentration of
individual components in the flare vent
gas using either the methods provided
in paragraph (j)(1) or (2) of this section,
to assess compliance with the operating
limits in paragraph (e) of this section
and, if applicable, paragraphs (d) and (f)
of this section. Alternatively, the owner
or operator may elect to directly monitor
the net heating value of the flare vent
gas following the methods provided in
paragraphs (j)(3) of this section and, if
desired, may directly measure the
hydrogen concentration in the flare vent
gas following the methods provided in
paragraphs (j)(4) of this section. The
owner or operator may elect to use
different monitoring methods for
different gaseous streams that make up
the flare vent gas using different
methods provided the composition or
net heating value of all gas streams that
contribute to the flare vent gas are
determined.
(1) Except as provided in paragraphs
(j)(5) and (6) of this section, the owner
or operator shall install, operate,
calibrate, and maintain a monitoring
system capable of continuously
measuring (i.e., at least once every 15minutes), calculating, and recording the
individual component concentrations
present in the flare vent gas.
(2) Except as provided in paragraphs
(j)(5) and (6) of this section, the owner
or operator shall install, operate, and
maintain a grab sampling system
capable of collecting an evacuated
canister sample for subsequent
compositional analysis at least once
every eight hours while there is flow of
regulated material to the flare.
Subsequent compositional analysis of
the samples must be performed
according to Method 18 of 40 CFR part
60, appendix A–6, ASTM D6420–99
(Reapproved 2010), ASTM D1945–03
(Reapproved 2010), ASTM D1945–14 or
ASTM UOP539–12 (all incorporated by
reference—see § 63.14).
(3) Except as provided in paragraphs
(j)(5) and (6) of this section, the owner
or operator shall install, operate,
calibrate, and maintain a calorimeter
capable of continuously measuring,
calculating, and recording NHVvg at
standard conditions.
(4) If the owner or operator uses a
continuous net heating value monitor
according to paragraph (j)(3) of this
section, the owner or operator may, at
their discretion, install, operate,
calibrate, and maintain a monitoring
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.009
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
75260
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
system capable of continuously
measuring, calculating, and recording
the hydrogen concentration in the flare
vent gas.
(5) Direct compositional or net
heating value monitoring is not required
for purchased (‘‘pipeline quality’’)
natural gas streams. The net heating
value of purchased natural gas streams
may be determined using annual or
more frequent grab sampling at any one
representative location. Alternatively,
the net heating value of any purchased
natural gas stream can be assumed to be
920 Btu/scf.
(6) Direct compositional or net
heating value monitoring is not required
for gas streams that have been
demonstrated to have consistent
composition (or a fixed minimum net
heating value) according to the methods
in paragraphs (j)(6)(i) through (v) of this
section.
(i) The owner or operator shall submit
to the Administrator a written
application for an exemption from
monitoring. The application must
contain the following information:
(A) A description of the flare gas
stream/system to be considered,
including submission of a portion of the
appropriate piping diagrams indicating
the boundaries of the flare gas stream/
system and the affected flare(s) to be
considered;
(B) A statement that there are no
crossover or entry points to be
introduced into the flare gas stream/
system (this should be shown in the
piping diagrams) prior to the point
where the flow rate of the gas streams
is measured;
(C) An explanation of the conditions
that ensure that the flare gas net heating
value is consistent and, if flare gas net
heating value is expected to vary (e.g.,
due to product loading of different
material), the conditions expected to
produce the flare gas with the lowest net
heating value;
(D) The supporting test results from
sampling the requested flare gas stream/
system for the net heating value.
Sampling data must include, at
minimum, 2 weeks of daily
measurement values (14 grab samples)
for frequently operated flare gas
streams/systems; for infrequently
operated flare gas streams/systems,
seven grab samples must be collected
unless other additional information
would support reduced sampling. If the
flare gas stream composition can vary,
samples must be taken during those
conditions expected to result in lowest
net heating value identified in
paragraph (j)(6)(i)(C) of this section. The
owner or operator shall determine net
heating value for the gas stream using
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
either gas composition analysis or net
heating value monitor (with optional
hydrogen concentration analyzer)
according to the method provided in
paragraph (l) of this section; and
(E) A description of how the 2 weeks
(or seven samples for infrequently
operated flare gas streams/systems) of
monitoring results compares to the
typical range of net heating values
expected for the flare gas stream/system
going to the affected flare (e.g., ‘‘the
samples are representative of typical
operating conditions of the flare gas
stream going to the loading rack flare’’
or ‘‘the samples are representative of
conditions expected to yield the lowest
net heating value of the flare gas stream
going to the loading rack flare’’).
(F) The net heating value to be used
for all flows of the flare vent gas from
the flare gas stream/system covered in
the application. A single net heating
value must be assigned to the flare vent
gas either by selecting the lowest net
heating value measured in the sampling
program or by determining the 95th
percent confidence interval on the mean
value of all samples collected using the
t-distribution statistic (which is 1.943
for 7 grab samples or 1.771 for 14 grab
samples).
(ii) The effective date of the
exemption is the date of submission of
the information required in paragraph
(j)(6)(i) of this section.
(iii) No further action is required
unless refinery operating conditions
change in such a way that affects the
exempt fuel gas stream/system (e.g., the
stream composition changes). If such a
change occurs, the owner or operator
shall follow the procedures in paragraph
(j)(6)(iii)(A), (B), or (C) of this section.
(A) If the operation change results in
a flare vent gas net heating value that is
still within the range of net heating
values included in the original
application, the owner or operator shall
determine the net heating value on a
grab sample and record the results as
proof that the net heating value assigned
to the vent gas stream in the original
application is still appropriate.
(B) If the operation change results in
a flare vent gas net heating value that is
lower than the net heating value
assigned to the vent gas stream in the
original application, the owner or
operator may submit new information
following the procedures of paragraph
(j)(6)(i) of this section within 60 days (or
within 30 days after the seventh grab
sample is tested for infrequently
operated process units).
(C) If the operation change results in
a flare vent gas net heating value has
greater variability in the flare gas
stream/system such the owner or
PO 00000
Frm 00084
Fmt 4701
Sfmt 4700
operator chooses not to submit new
information to support an exemption,
the owner or operator must begin
monitoring the composition or net heat
content of the flare vent gas stream
using the methods in this section (i.e.,
grab samples every 8 hours until such
time a continuous monitor, if elected, is
installed).
(k) Calculation methods for
cumulative flow rates and determining
compliance with Vtip operating limits.
The owner or operator shall determine
Vtip on a 15-minute block average basis
according to the following requirements.
(1) The owner or operator shall use
design and engineering principles to
determine the unobstructed cross
sectional area of the flare tip. The
unobstructed cross sectional area of the
flare tip is the total tip area that vent gas
can pass through. This area does not
include any stability tabs, stability rings,
and upper steam or air tubes because
flare vent gas does not exit through
them.
(2) The owner or operator shall
determine the cumulative volumetric
flow of flare vent gas for each 15-minute
block average period using the data from
the continuous flow monitoring system
required in paragraph (i) of this section
according to the following requirements,
as applicable. If desired, the cumulative
flow rate for a 15-minute block period
only needs to include flow during those
periods when regulated material is sent
to the flare, but owners or operators may
elect to calculate the cumulative flow
rates across the entire 15-minute block
period for any 15-minute block period
where there is regulated material flow to
the flare.
(i) Use set 15-minute time periods
starting at 12 midnight to 12:15 a.m.,
12:15 a.m. to 12:30 a.m. and so on
concluding at 11:45 p.m. to midnight
when calculating 15-minute block
average flow volumes.
(ii) If continuous pressure/
temperature monitoring system(s) and
engineering calculations are used as
allowed under paragraph (i)(4) of this
section, the owner or operator shall, at
a minimum, determine the 15-minute
block average temperature and pressure
from the monitoring system and use
those values to perform the engineering
calculations to determine the
cumulative flow over the 15-minute
block average period. Alternatively, the
owner or operator may divide the 15minute block average period into equal
duration subperiods (e.g., three 5minute periods) and determine the
average temperature and pressure for
each subperiod, perform engineering
calculations to determine the flow for
each subperiod, then add the volumetric
E:\FR\FM\01DER2.SGM
01DER2
Where:
Vtip = Flare tip velocity, feet per second.
Qcum = Cumulative volumetric flow over 15minute block average period, actual
cubic feet.
Area = Unobstructed area of the flare tip,
square feet.
900 = Conversion factor, seconds per 15minute block average.
tkelley on DSK3SPTVN1PROD with RULES2
(4) If the owner or operator chooses to
comply with paragraph (d)(2) of this
section, the owner or operator shall also
determine the net heating value of the
flare vent gas following the
requirements in paragraphs (j) and (l) of
this section and calculate Vmax using the
equation in paragraph (d)(2) of this
section in order to compare Vtip to Vmax
on a 15-minute block average basis.
(l) Calculation methods for
determining flare vent gas net heating
value. The owner or operator shall
determine the net heating value of the
flare vent gas (NHVvg) based on the
composition monitoring data on a 15minute block average basis according to
the following requirements.
(1) If compositional analysis data are
collected as provided in paragraph (j)(1)
or (2) of this section, the owner or
operator shall determine NHVvg of a
specific sample by using the following
equation.
Where:
NHVvg = Net heating value of flare vent gas,
Btu/scf.
i = Individual component in flare vent gas.
n = Number of components in flare vent gas.
xi = Concentration of component i in flare
vent gas, volume fraction.
NHVi = Net heating value of component i
according to table 12 of this subpart, Btu/
scf. If the component is not specified in
table 12 of this subpart, the heats of
combustion may be determined using
any published values where the net
enthalpy per mole of offgas is based on
combustion at 25 °C and 1 atmosphere
(or constant pressure) with offgas water
in the gaseous state, but the standard
temperature for determining the volume
corresponding to one mole of vent gas is
20 °C.
(2) If direct net heating value
monitoring data are collected as
provided in paragraph (j)(3) of this
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
section but a hydrogen concentration
monitor is not used, the owner or
operator shall use the direct output of
the monitoring system(s) (in Btu/scf) to
determine the NHVvg for the sample.
(3) If direct net heating value
monitoring data are collected as
provided in paragraph (j)(3) of this
section and hydrogen concentration
monitoring data are collected as
provided in paragraph (j)(4) of this
section, the owner or operator shall use
the following equation to determine
NHVvg for each sample measured via the
net heating value monitoring system.
NHVvg = NHVmeasured + 938xH2
Where:
NHVvg = Net heating value of flare vent gas,
Btu/scf.
NHVmeasured = Net heating value of flare vent
gas stream as measured by the
continuous net heating value monitoring
system, Btu/scf.
xH2 = Concentration of hydrogen in flare vent
gas at the time the sample was input into
the net heating value monitoring system,
volume fraction.
938 = Net correction for the measured
heating value of hydrogen (1,212 ¥ 274),
Btu/scf.
(4) Use set 15-minute time periods
starting at 12 midnight to 12:15 a.m.,
12:15 a.m. to 12:30 a.m. and so on
concluding at 11:45 p.m. to midnight
when calculating 15-minute block
averages.
(5) When a continuous monitoring
system is used as provided in paragraph
(j)(1) or (3) of this section and, if
applicable, paragraph (j)(4) of this
section, the owner or operator may elect
to determine the 15-minute block
average NHVvg using either the
calculation methods in paragraph
(l)(5)(i) of this section or the calculation
methods in paragraph (l)(5)(ii) of this
section. The owner or operator may
choose to comply using the calculation
methods in paragraph (l)(5)(i) of this
section for some flares at the petroleum
refinery and comply using the
calculation methods (l)(5)(ii) of this
section for other flares. However, for
each flare, the owner or operator must
elect one calculation method that will
apply at all times, and use that method
for all continuously monitored flare
vent streams associated with that flare.
If the owner or operator intends to
change the calculation method that
applies to a flare, the owner or operator
must notify the Administrator 30 days
in advance of such a change.
(i) Feed-forward calculation method.
When calculating NHVvg for a specific
15-minute block:
(A) Use the results from the first
sample collected during an event, (for
PO 00000
Frm 00085
Fmt 4701
Sfmt 4700
periodic flare vent gas flow events) for
the first 15-minute block associated
with that event.
(B) If the results from the first sample
collected during an event (for periodic
flare vent gas flow events) are not
available until after the second 15minute block starts, use the results from
the first sample collected during an
event for the second 15-minute block
associated with that event.
(C) For all other cases, use the results
that are available from the most recent
sample prior to the 15-minute block
period for that 15-minute block period
for all flare vent gas steams. For the
purpose of this requirement, use the
time that the results become available
rather than the time the sample was
collected. For example, if a sample is
collected at 12:25 a.m. and the analysis
is completed at 12:38 a.m., the results
are available at 12:38 a.m. and these
results would be used to determine
compliance during the 15-minute block
period from 12:45 a.m. to 1:00 a.m.
(ii) Direct calculation method. When
calculating NHVvg for a specific 15minute block:
(A) If the results from the first sample
collected during an event (for periodic
flare vent gas flow events) are not
available until after the second 15minute block starts, use the results from
the first sample collected during an
event for the first 15-minute block
associated with that event.
(B) For all other cases, use the
arithmetic average of all NHVvg
measurement data results that become
available during a 15-minute block to
calculate the 15-minute block average
for that period. For the purpose of this
requirement, use the time that the
results become available rather than the
time the sample was collected. For
example, if a sample is collected at
12:25 a.m. and the analysis is completed
at 12:38 a.m., the results are available at
12:38 a.m. and these results would be
used to determine compliance during
the 15-minute block period from 12:30
a.m. to 12:45 a.m.
(6) When grab samples are used to
determine flare vent gas composition:
(i) Use the analytical results from the
first grab sample collected for an event
for all 15-minute periods from the start
of the event through the 15-minute
block prior to the 15-minute block in
which a subsequent grab sample is
collected.
(ii) Use the results from subsequent
grab sampling events for all 15 minute
periods starting with the 15-minute
block in which the sample was collected
and ending with the 15-minute block
prior to the 15-minute block in which
the next grab sample is collected. For
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.011
flows for the subperiods to determine
the cumulative volumetric flow of vent
gas for the 15-minute block average
period.
(3) The 15-minute block average Vtip
shall be calculated using the following
equation.
75261
ER01DE15.010
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75262
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
(6) of this section and a flow-weighted
average of the gas stream net heating
values shall be used to determine the
15-minute block average net heating
value of the cumulative flare vent gas.
(m) Calculation methods for
determining combustion zone net
heating value. The owner or operator
shall determine the net heating value of
the combustion zone gas (NHVcz) as
specified in paragraph (m)(1) or (2) of
this section, as applicable.
(1) Except as specified in paragraph
(m)(2) of this section, determine the 15minute block average NHVcz based on
the 15-minute block average vent gas
and assist gas flow rates using the
following equation. For periods when
there is no assist steam flow or premix
assist air flow, NHVcz = NHVvg.
Where:
NHVcz = Net heating value of combustion
zone gas, Btu/scf.
NHVvg = Net heating value of flare vent gas
for the 15-minute block period, Btu/scf.
Qvg = Cumulative volumetric flow of flare
vent gas during the 15-minute block
period, scf.
Qs = Cumulative volumetric flow of total
steam during the 15-minute block
period, scf.
Qa,premix = Cumulative volumetric flow of
premix assist air during the 15-minute
block period, scf.
this section and that monitor gas
composition or net heating value in a
location representative of the
cumulative vent gas stream and that
directly monitor supplemental natural
gas flow additions to the flare must
determine the 15-minute block average
NHVcz using the following equation.
Where:
NHVcz = Net heating value of combustion
zone gas, Btu/scf.
NHVvg = Net heating value of flare vent gas
for the 15-minute block period, Btu/scf.
Qvg = Cumulative volumetric flow of flare
vent gas during the 15-minute block
period, scf.
QNG2 = Cumulative volumetric flow of
supplemental natural gas to the flare
during the 15-minute block period, scf.
QNG1 = Cumulative volumetric flow of
supplemental natural gas to the flare
during the previous 15-minute block
period, scf. For the first 15-minute block
period of an event, use the volumetric
flow value for the current 15-minute
block period, i.e., QNG1=QNG2.
NHVNG = Net heating value of supplemental
natural gas to the flare for the 15-minute
block period determined according to the
requirements in paragraph (j)(5) of this
section, Btu/scf.
Qs = Cumulative volumetric flow of total
steam during the 15-minute block
period, scf.
Qa,premix = Cumulative volumetric flow of
premix assist air during the 15-minute
block period, scf.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(2) Owners or operators of flares that
use the feed-forward calculation
PO 00000
Frm 00086
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.015
Qs = Cumulative volumetric flow of total
steam during the 15-minute block
period, scf.
Qa,premix = Cumulative volumetric flow of
premix assist air during the 15-minute
block period, scf.
Qa,perimeter = Cumulative volumetric flow of
perimeter assist air during the 15-minute
block period, scf.
methodology in paragraph (l)(5)(i) of
this section and that monitor gas
composition or net heating value in a
location representative of the
cumulative vent gas stream and that
directly monitor supplemental natural
gas flow additions to the flare must
determine the 15-minute block average
NHVdil using the following equation
only during periods when perimeter
assist air is used. For 15-minute block
periods when there is no cumulative
ER01DE15.014
(n) Calculation methods for
determining the net heating value
dilution parameter. The owner or
operator shall determine the net heating
value dilution parameter (NHVdil) as
specified in paragraph (n)(1) or (2) of
this section, as applicable.
(1) Except as specified in paragraph
(n)(2) of this section, determine the 15minute block average NHVdil based on
the 15-minute block average vent gas
and perimeter assist air flow rates using
the following equation only during
periods when perimeter assist air is
used. For 15-minute block periods when
there is no cumulative volumetric flow
of perimeter assist air, the 15-minute
block average NHVdil parameter does not
need to be calculated.
ER01DE15.013
Where:
NHVdil = Net heating value dilution
parameter, Btu/ft2.
NHVvg = Net heating value of flare vent gas
determined for the 15-minute block
period, Btu/scf.
Qvg = Cumulative volumetric flow of flare
vent gas during the 15-minute block
period, scf.
Diam = Effective diameter of the
unobstructed area of the flare tip for flare
vent gas flow, ft. Use the area as
determined in paragraph (k)(1) of this
section and determine the diameter as
(2) Owners or operators of flares that
use the feed-forward calculation
methodology in paragraph (l)(5)(i) of
ER01DE15.012
tkelley on DSK3SPTVN1PROD with RULES2
the purpose of this requirement, use the
time the sample was collected rather
than the time the analytical results
become available.
(7) If the owner or operator monitors
separate gas streams that combine to
comprise the total flare vent gas flow,
the 15-minute block average net heating
value shall be determined separately for
each measurement location according to
the methods in paragraphs (l)(1) through
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Where:
NHVdil = Net heating value dilution
parameter, Btu/ft2.
NHVvg = Net heating value of flare vent gas
determined for the 15-minute block
period, Btu/scf.
Qvg = Cumulative volumetric flow of flare
vent gas during the 15-minute block
period, scf.
QNG2 = Cumulative volumetric flow of
supplemental natural gas to the flare
during the 15-minute block period, scf.
QNG1 = Cumulative volumetric flow of
supplemental natural gas to the flare
during the previous 15-minute block
period, scf. For the first 15-minute block
period of an event, use the volumetric
flow value for the current 15-minute
block period, i.e., QNG1 =QNG2.
NHVNG = Net heating value of supplemental
natural gas to the flare for the 15-minute
block period determined according to the
requirements in paragraph (j)(5) of this
section, Btu/scf.
Diam = Effective diameter of the
unobstructed area of the flare tip for flare
vent gas flow, ft. Use the area as
determined in paragraph (k)(1) of this
section and determine the diameter as
prevented during periods of startup,
shutdown, or emergency releases. The
flare minimization assessment must (at
a minimum) consider the items in
paragraphs (o)(1)(ii)(A) through (C) of
this section. The assessment must
provide clear rationale in terms of costs
(capital and annual operating), natural
gas offset credits (if applicable),
technical feasibility, secondary
environmental impacts and safety
considerations for the selected
minimization alternative(s) or a
statement, with justifications, that flow
reduction could not be achieved. Based
upon the assessment, each owner or
operator of an affected flare shall
identify the minimization alternatives
that it has implemented by the due date
of the flare management plan and shall
include a schedule for the prompt
implementation of any selected
measures that cannot reasonably be
completed as of that date.
(A) Modification in startup and
shutdown procedures to reduce the
quantity of process gas discharge to the
flare.
(B) Implementation of prevention
measures listed for pressure relief
devices in § 63.648(j)(5) for each
pressure relief valve that can discharge
to the flare.
(C) Installation of a flare gas recovery
system or, for facilities that are fuel gas
rich, a flare gas recovery system and a
co-generation unit or combined heat and
power unit.
(iii) A description of each affected
flare containing the information in
paragraphs (o)(1)(iii)(A) through (G) of
this section.
(A) A general description of the flare,
including whether it is a ground flare or
elevated (including height), the type of
assist system (e.g., air, steam, pressure,
non-assisted), whether the flare is used
on a routine basis or if it is only used
during periods of startup, shutdown or
emergency release, and whether the
flare is equipped with a flare gas
recovery system.
(B) The smokeless capacity of the flare
based on design conditions. Note: A
single value must be provided for the
smokeless capacity of the flare.
(C) The maximum vent gas flow rate
(hydraulic load capacity).
(D) The maximum supplemental gas
flow rate.
tkelley on DSK3SPTVN1PROD with RULES2
Qs = Cumulative volumetric flow of total
steam during the 15-minute block
period, scf.
Qa,premix = Cumulative volumetric flow of
premix assist air during the 15-minute
block period, scf.
Qa,perimeter = Cumulative volumetric flow of
perimeter assist air during the 15-minute
block period, scf.
(o) Emergency flaring provisions. The
owner or operator of a flare that has the
potential to operate above its smokeless
capacity under any circumstance shall
comply with the provisions in
paragraphs (o)(1) through (8) of this
section.
(1) Develop a flare management plan
to minimize flaring during periods of
startup, shutdown, or emergency
releases. The flare management plan
must include the information described
in paragraphs (o)(1)(i) through (vii) of
this section.
(i) A listing of all refinery process
units, ancillary equipment, and fuel gas
systems connected to the flare for each
affected flare.
(ii) An assessment of whether
discharges to affected flares from these
process units, ancillary equipment and
fuel gas systems can be minimized or
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00087
Fmt 4701
Sfmt 4700
(E) For flares that receive assist steam,
the minimum total steam rate and the
maximum total steam rate.
(F) For flares that receive assist air, an
indication of whether the fan/blower is
single speed, multi-fixed speed (e.g.,
high, medium, and low speeds), or
variable speeds. For fans/blowers with
fixed speeds, provide the estimated
assist air flow rate at each fixed speed.
For variable speeds, provide the design
fan curve (e.g., air flow rate as a
function of power input).
(G) Simple process flow diagram
showing the locations of the flare
following components of the flare: Flare
tip (date installed, manufacturer,
nominal and effective tip diameter, tip
drawing); knockout or surge drum(s) or
pot(s) (including dimensions and design
capacities); flare header(s) and
subheader(s); assist system; and ignition
system.
(iv) Description and simple process
flow diagram showing all gas lines
(including flare waste gas, purge or
sweep gas (as applicable), supplemental
gas) that are associated with the flare.
For purge, sweep, supplemental gas,
identify the type of gas used. Designate
which lines are exempt from
composition or net heating value
monitoring and why (e.g., natural gas,
gas streams that have been
demonstrated to have consistent
composition, pilot gas). Designate which
lines are monitored and identify on the
process flow diagram the location and
type of each monitor. Designate the
pressure relief devices that are vented to
the flare.
(v) For each flow rate, gas
composition, net heating value or
hydrogen concentration monitor
identified in paragraph (o)(1)(iv) of this
section, provide a detailed description
of the manufacturer’s specifications,
including, but not limited to, make,
model, type, range, precision, accuracy,
calibration, maintenance and quality
assurance procedures.
(vi) For each pressure relief valve
vented to the flare identified in
paragraph (o)(1)(iv) of this section,
provide a detailed description of each
pressure release valve, including type of
relief device (rupture disc, valve type)
diameter of the relief valve, set pressure
of the relief valve and listing of the
prevention measures implemented. This
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.017
parameter does not need to be
calculated.
ER01DE15.016
volumetric flow of perimeter assist air,
the 15-minute block average NHVdil
75263
tkelley on DSK3SPTVN1PROD with RULES2
75264
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
information may be maintained in an
electronic database on-site and does not
need to be submitted as part of the flare
management plan unless requested to
do so by the Administrator.
(vii) Procedures to minimize or
eliminate discharges to the flare during
the planned startup and shutdown of
the refinery process units and ancillary
equipment that are connected to the
affected flare, together with a schedule
for the prompt implementation of any
procedures that cannot reasonably be
implemented as of the date of the
submission of the flare management
plan.
(2) Each owner or operator required to
develop and implement a written flare
management plan as described in
paragraph (o)(1) of this section must
submit the plan to the Administrator as
described in paragraphs (o)(2)(i) through
(iii) of this section.
(i) The owner or operator must
develop and implement the flare
management plan no later than January
30, 2019 or at startup for a new flare that
commenced construction on or after
February 1, 2016.
(ii) The owner or operator must
comply with the plan as submitted by
the date specified in paragraph (o)(2)(i)
of this section. The plan should be
updated periodically to account for
changes in the operation of the flare,
such as new connections to the flare or
the installation of a flare gas recovery
system, but the plan need be resubmitted to the Administrator only if
the owner or operator alters the design
smokeless capacity of the flare. The
owner or operator must comply with the
updated plan as submitted.
(iii) All versions of the plan submitted
to the Administrator shall also be
submitted to the following address: U.S.
Environmental Protection Agency,
Office of Air Quality Planning and
Standards, Sector Policies and Programs
Division, U.S. EPA Mailroom (E143–01),
Attention: Refinery Sector Lead, 109
T.W. Alexander Drive, Research
Triangle Park, NC 27711. Electronic
copies in lieu of hard copies may also
be submitted to refineryRTR@epa.gov.
(3) The owner or operator of a flare
subject to this subpart shall conduct a
root cause analysis and a corrective
action analysis for each flow event that
contains regulated material and that
meets either the criteria in paragraph
(o)(3)(i) or (ii) of this section.
(i) The vent gas flow rate exceeds the
smokeless capacity of the flare and
visible emissions are present from the
flare for more than 5 minutes during any
2 consecutive hours during the release
event.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(ii) The vent gas flow rate exceeds the
smokeless capacity of the flare and the
15-minute block average flare tip
velocity exceeds the maximum flare tip
velocity determined using the methods
in paragraph (d)(2) of this section.
(4) A root cause analysis and
corrective action analysis must be
completed as soon as possible, but no
later than 45 days after a flare flow
event meeting the criteria in paragraph
(o)(3)(i) or (ii) of this section. Special
circumstances affecting the number of
root cause analyses and/or corrective
action analyses are provided in
paragraphs (o)(4)(i) through (v) of this
section.
(i) You may conduct a single root
cause analysis and corrective action
analysis for a single continuous flare
flow event that meets both of the criteria
in paragraphs (o)(3)(i) and (ii) of this
section.
(ii) You may conduct a single root
cause analysis and corrective action
analysis for a single continuous flare
flow event regardless of the number of
15-minute block periods in which the
flare tip velocity was exceeded or the
number of 2 hour periods that contain
more the 5 minutes of visible emissions.
(iii) You may conduct a single root
cause analysis and corrective action
analysis for a single event that causes
two or more flares that are operated in
series (i.e., cascaded flare systems) to
have a flow event meeting the criteria in
paragraph (o)(3)(i) or (ii) of this section.
(iv) You may conduct a single root
cause analysis and corrective action
analysis for a single event that causes
two or more flares to have a flow event
meeting the criteria in paragraph
(o)(3)(i) or (ii) of this section, regardless
of the configuration of the flares, if the
root cause is reasonably expected to be
a force majeure event, as defined in this
subpart.
(v) Except as provided in paragraphs
(o)(4)(iii) and (iv) of this section, if more
than one flare has a flow event that
meets the criteria in paragraph (o)(3)(i)
or (ii) of this section during the same
time period, an initial root cause
analysis shall be conducted separately
for each flare that has a flow event
meeting the criteria in paragraph
(o)(3)(i) or (ii) of this section. If the
initial root cause analysis indicates that
the flow events have the same root
cause(s), the initially separate root cause
analyses may be recorded as a single
root cause analysis and a single
corrective action analysis may be
conducted.
(5) Each owner or operator of a flare
required to conduct a root cause
analysis and corrective action analysis
as specified in paragraphs (o)(3) and (4)
PO 00000
Frm 00088
Fmt 4701
Sfmt 4700
of this section shall implement the
corrective action(s) identified in the
corrective action analysis in accordance
with the applicable requirements in
paragraphs (o)(5)(i) through (iii) of this
section.
(i) All corrective action(s) must be
implemented within 45 days of the
event for which the root cause and
corrective action analyses were required
or as soon thereafter as practicable. If an
owner or operator concludes that no
corrective action should be
implemented, the owner or operator
shall record and explain the basis for
that conclusion no later than 45 days
following the event.
(ii) For corrective actions that cannot
be fully implemented within 45 days
following the event for which the root
cause and corrective action analyses
were required, the owner or operator
shall develop an implementation
schedule to complete the corrective
action(s) as soon as practicable.
(iii) No later than 45 days following
the event for which a root cause and
corrective action analyses were
required, the owner or operator shall
record the corrective action(s)
completed to date, and, for action(s) not
already completed, a schedule for
implementation, including proposed
commencement and completion dates.
(6) The owner or operator shall
determine the total number of events for
which a root cause and corrective action
analyses was required during the
calendar year for each affected flare
separately for events meeting the criteria
in paragraph (o)(3)(i) of this section and
those meeting the criteria in paragraph
(o)(3)(ii) of this section. For the purpose
of this requirement, a single root cause
analysis conducted for an event that met
both of the criteria in paragraphs
(o)(3)(i) and (ii) of this section would be
counted as an event under each of the
separate criteria counts for that flare.
Additionally, if a single root cause
analysis was conducted for an event that
caused multiple flares to meet the
criteria in paragraph (o)(3)(i) or (ii) of
this section, that event would count as
an event for each of the flares for each
criteria in paragraph (o)(3) of this
section that was met during that event.
The owner or operator shall also
determine the total number of events for
which a root cause and correct action
analyses was required and the analyses
concluded that the root cause was a
force majeure event, as defined in this
subpart.
(7) The following events would be a
violation of this emergency flaring work
practice standard.
(i) Any flow event for which a root
cause analysis was required and the root
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
cause was determined to be operator
error or poor maintenance.
(ii) Two visible emissions exceedance
events meeting the criteria in paragraph
(o)(3)(i) of this section that were not
caused by a force majeure event from a
single flare in a 3 calendar year period
for the same root cause for the same
equipment.
(iii) Two flare tip velocity exceedance
events meeting the criteria in paragraph
(o)(3)(ii) of this section that were not
caused by a force majeure event from a
single flare in a 3 calendar year period
for the same root cause for the same
equipment.
(iv) Three visible emissions
exceedance events meeting the criteria
in paragraph (o)(3)(i) of this section that
were not caused by a force majeure
event from a single flare in a 3 calendar
year period for any reason.
(v) Three flare tip velocity exceedance
events meeting the criteria in paragraph
(o)(3)(ii) of this section that were not
caused by a force majeure event from a
single flare in a 3 calendar year period
for any reason.
(p) Flare monitoring records. The
owner or operator shall keep the records
specified in § 63.655(i)(9).
(q) Reporting. The owner or operator
shall comply with the reporting
requirements specified in
§ 63.655(g)(11).
(r) Alternative means of emissions
limitation. An owner or operator may
request approval from the Administrator
for site-specific operating limits that
shall apply specifically to a selected
flare. Site-specific operating limits
include alternative threshold values for
the parameters specified in paragraphs
(d) through (f) of this section as well as
threshold values for operating
parameters other than those specified in
paragraphs (d) through (f) of this
section. The owner or operator must
demonstrate that the flare achieves 96.5
percent combustion efficiency (or 98
percent destruction efficiency) using the
site-specific operating limits based on a
performance evaluation as described in
paragraph (r)(1) of this section. The
request shall include information as
described in paragraph (r)(2) of this
section. The request shall be submitted
and followed as described in paragraph
(r)(3) of this section.
(1) The owner or operator shall
prepare and submit a site-specific test
plan and receive approval of the sitespecific performance evaluation plan
prior to conducting any flare
performance evaluation test runs
intended for use in developing sitespecific operating limits. The sitespecific performance evaluation plan
shall include, at a minimum, the
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
elements specified in paragraphs (r)(1)(i)
through (ix) of this section. Upon
approval of the site-specific
performance evaluation plan, the owner
or operator shall conduct performance
evaluation test runs for the flare
following the procedures described in
the site-specific performance evaluation
plan.
(i) The design and dimensions of the
flare, flare type (air-assisted only, steamassisted only, air- and steam-assisted,
pressure-assisted, or non-assisted), and
description of gas being flared,
including quantity of gas flared,
frequency of flaring events (if periodic),
expected net heating value of flare vent
gas, minimum total steam assist rate.
(ii) The operating conditions (vent gas
compositions, vent gas flow rates and
assist flow rates, if applicable) likely to
be encountered by the flare during
normal operations and the operating
conditions for the test period.
(iii) A description of (including
sample calculations illustrating) the
planned data reduction and calculations
to determine the flare combustion or
destruction efficiency.
(iv) Site-specific operating parameters
to be monitored continuously during the
flare performance evaluation. These
parameters may include but are not
limited to vent gas flow rate, steam and/
or air assist flow rates, and flare vent gas
composition. If new operating
parameters are proposed for use other
than those specified in paragraphs (d)
through (f) of this section, an
explanation of the relevance of the
proposed operating parameter(s) as an
indicator of flare combustion
performance and why the alternative
operating parameter(s) can adequately
ensure that the flare achieves the
required combustion efficiency.
(v) A detailed description of the
measurement methods, monitored
pollutant(s), measurement locations,
measurement frequency, and recording
frequency proposed for both emission
measurements and flare operating
parameters.
(vi) A description of (including
sample calculations illustrating) the
planned data reduction and calculations
to determine the flare operating
parameters.
(vii) The minimum number and
length of test runs and range of
operating values to be evaluated during
the performance evaluation. A sufficient
number of test runs shall be conducted
to identify the point at which the
combustion/destruction efficiency of the
flare deteriorates.
(viii) [Reserved]
(ix) Test schedule.
PO 00000
Frm 00089
Fmt 4701
Sfmt 4700
75265
(2) The request for flare-specific
operating limits shall include sufficient
and appropriate data, as determined by
the Administrator, to allow the
Administrator to confirm that the
selected site-specific operating limit(s)
adequately ensures that the flare
destruction efficiency is 98 percent or
greater or that the flare combustion
efficiency is 96.5 percent or greater at all
times. At a minimum, the request shall
contain the information described in
paragraphs (r)(2)(i) through (iv) of this
section.
(i) The design and dimensions of the
flare, flare type (air-assisted only, steamassisted only, air- and steam-assisted,
pressure-assisted, or non-assisted), and
description of gas being flared,
including quantity of gas flared,
frequency of flaring events (if periodic),
expected net heating value of flare vent
gas, minimum total steam assist rate.
(ii) Results of each performance
evaluation test run conducted,
including, at a minimum:
(A) The measured combustion/
destruction efficiency.
(B) The measured or calculated
operating parameters for each test run.
If operating parameters are calculated,
the raw data from which the parameters
are calculated must be included in the
test report.
(C) Measurement location
descriptions for both emission
measurements and flare operating
parameters.
(D) Description of sampling and
analysis procedures (including number
and length of test runs) and any
modifications to standard procedures. If
there were deviations from the approved
test plan, a detailed description of the
deviations and rationale why the test
results or calculation procedures used
are appropriate.
(E) Operating conditions (e.g., vent
gas composition, assist rates, etc.) that
occurred during the test.
(F) Quality assurance procedures.
(G) Records of calibrations.
(H) Raw data sheets for field
sampling.
(I) Raw data sheets for field and
laboratory analyses.
(J) Documentation of calculations.
(iii) The selected flare-specific
operating limit values based on the
performance evaluation test results,
including the averaging time for the
operating limit(s), and rationale why the
selected values and averaging times are
sufficiently stringent to ensure proper
flare performance. If new operating
parameters or averaging times are
proposed for use other than those
specified in paragraphs (d) through (f) of
this section, an explanation of why the
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
75266
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
alternative operating parameter(s) or
averaging time(s) adequately ensures the
flare achieves the required combustion
efficiency.
(iv) The means by which the owner or
operator will document on-going,
continuous compliance with the
selected flare-specific operating limit(s),
including the specific measurement
location and frequencies, calculation
procedures, and records to be
maintained.
(3) The request shall be submitted as
described in paragraphs (r)(3)(i) through
(iv) of this section.
(i) The owner or operator may request
approval from the Administrator at any
time upon completion of a performance
evaluation conducted following the
methods in an approved site-specific
performance evaluation plan for an
operating limit(s) that shall apply
specifically to that flare.
(ii) The request must be submitted to
the Administrator for approval. The
owner or operator must continue to
comply with the applicable standards
for flares in this subpart until the
requirements in § 63.6(g)(1) are met and
a notice is published in the Federal
Register allowing use of such an
alternative means of emission
limitation.
(iii) The request shall also be
submitted to the following address: U.S.
Environmental Protection Agency,
Office of Air Quality Planning and
Standards, Sector Policies and Programs
Division, U.S. EPA Mailroom (E143–01),
Attention: Refinery Sector Lead, 109
T.W. Alexander Drive, Research
Triangle Park, NC 27711. Electronic
copies in lieu of hard copies may also
be submitted to refineryrtr@epa.gov.
(iv) If the Administrator finds any
deficiencies in the request, the request
must be revised to address the
deficiencies and be re-submitted for
approval within 45 days of receipt of the
notice of deficiencies. The owner or
operator must comply with the revised
request as submitted until it is
approved.
(4) The approval process for a request
for a flare-specific operating limit(s) is
described in paragraphs (r)(4)(i) through
(iii) of this section.
(i) Approval by the Administrator of
a flare-specific operating limit(s) request
will be based on the completeness,
accuracy and reasonableness of the
request. Factors that the EPA will
consider in reviewing the request for
approval include, but are not limited to,
those described in paragraphs
(r)(4)(i)(A) through (C) of this section.
(A) The description of the flare design
and operating characteristics.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(B) If a new operating parameter(s)
other than those specified in paragraphs
(d) through (f) of this section is
proposed, the explanation of how the
proposed operating parameter(s) serves
a good indicator(s) of flare combustion
performance.
(C) The results of the flare
performance evaluation test runs and
the establishment of operating limits
that ensures that the flare destruction
efficiency is 98 percent or greater or that
the flare combustion efficiency is 96.5
percent or greater at all times.
(D) The completeness of the flare
performance evaluation test report.
(ii) If the request is approved by the
Administrator, a flare-specific operating
limit(s) will be established at the level(s)
demonstrated in the approved request.
(iii) If the Administrator finds any
deficiencies in the request, the request
must be revised to address the
deficiencies and be re-submitted for
approval.
■ 33. Section 63.671 is added to read as
follows:
§ 63.671 Requirements for flare monitoring
systems.
(a) Operation of CPMS. For each
CPMS installed to comply with
applicable provisions in § 63.670, the
owner or operator shall install, operate,
calibrate, and maintain the CPMS as
specified in paragraphs (a)(1) through
(8) of this section.
(1) Except for CPMS installed for pilot
flame monitoring, all monitoring
equipment must meet the applicable
minimum accuracy, calibration and
quality control requirements specified
in table 13 of this subpart.
(2) The owner or operator shall ensure
the readout (that portion of the CPMS
that provides a visual display or record)
or other indication of the monitored
operating parameter from any CPMS
required for compliance is readily
accessible onsite for operational control
or inspection by the operator of the
source.
(3) All CPMS must complete a
minimum of one cycle of operation
(sampling, analyzing and data
recording) for each successive 15minute period.
(4) Except for periods of monitoring
system malfunctions, repairs associated
with monitoring system malfunctions
and required monitoring system quality
assurance or quality control activities
(including, as applicable, calibration
checks and required zero and span
adjustments), the owner or operator
shall operate all CPMS and collect data
continuously at all times when
regulated emissions are routed to the
flare.
PO 00000
Frm 00090
Fmt 4701
Sfmt 4700
(5) The owner or operator shall
operate, maintain, and calibrate each
CPMS according to the CPMS
monitoring plan specified in paragraph
(b) of this section.
(6) For each CPMS except for CPMS
installed for pilot flame monitoring, the
owner or operator shall comply with the
out-of-control procedures described in
paragraph (c) of this section.
(7) The owner or operator shall reduce
data from a CPMS as specified in
paragraph (d) of this section.
(8) The CPMS must be capable of
measuring the appropriate parameter
over the range of values expected for
that measurement location. The data
recording system associated with each
CPMS must have a resolution that is
equal to or better than the required
system accuracy.
(b) CPMS monitoring plan. The owner
or operator shall develop and
implement a CPMS quality control
program documented in a CPMS
monitoring plan that covers each flare
subject to the provisions in § 63.670 and
each CPMS installed to comply with
applicable provisions in § 63.670. The
owner or operator shall have the CPMS
monitoring plan readily available onsite at all times and shall submit a copy
of the CPMS monitoring plan to the
Administrator upon request by the
Administrator. The CPMS monitoring
plan must contain the information listed
in paragraphs (b)(1) through (5) of this
section.
(1) Identification of the specific flare
being monitored and the flare type (airassisted only, steam-assisted only, airand steam-assisted, pressure-assisted, or
non-assisted).
(2) Identification of the parameter to
be monitored by the CPMS and the
expected parameter range, including
worst case and normal operation.
(3) Description of the monitoring
equipment, including the information
specified in paragraphs (b)(3)(i) through
(vii) of this section.
(i) Manufacturer and model number
for all monitoring equipment
components installed to comply with
applicable provisions in § 63.670.
(ii) Performance specifications, as
provided by the manufacturer, and any
differences expected for this installation
and operation.
(iii) The location of the CPMS
sampling probe or other interface and a
justification of how the location meets
the requirements of paragraph (a)(1) of
this section.
(iv) Placement of the CPMS readout,
or other indication of parameter values,
indicating how the location meets the
requirements of paragraph (a)(2) of this
section.
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
(v) Span of the CPMS. The span of the
CPMS sensor and analyzer must
encompass the full range of all expected
values.
(vi) How data outside of the span of
the CPMS will be handled and the
corrective action that will be taken to
reduce and eliminate such occurrences
in the future.
(vii) Identification of the parameter
detected by the parametric signal
analyzer and the algorithm used to
convert these values into the operating
parameter monitored to demonstrate
compliance, if the parameter detected is
different from the operating parameter
monitored.
(4) Description of the data collection
and reduction systems, including the
information specified in paragraphs
(b)(4)(i) through (iii) of this section.
(i) A copy of the data acquisition
system algorithm used to reduce the
measured data into the reportable form
of the standard and to calculate the
applicable averages.
(ii) Identification of whether the
algorithm excludes data collected
during CPMS breakdowns, out-ofcontrol periods, repairs, maintenance
periods, instrument adjustments or
checks to maintain precision and
accuracy, calibration checks, and zero
(low-level), mid-level (if applicable) and
high-level adjustments.
(iii) If the data acquisition algorithm
does not exclude data collected during
CPMS breakdowns, out-of-control
periods, repairs, maintenance periods,
instrument adjustments or checks to
maintain precision and accuracy,
calibration checks, and zero (low-level),
mid-level (if applicable) and high-level
adjustments, a description of the
procedure for excluding this data when
the averages calculated as specified in
paragraph (e) of this section are
determined.
(5) Routine quality control and
assurance procedures, including
descriptions of the procedures listed in
paragraphs (b)(5)(i) through (vi) of this
section and a schedule for conducting
these procedures. The routine
procedures must provide an assessment
of CPMS performance.
(i) Initial and subsequent calibration
of the CPMS and acceptance criteria.
(ii) Determination and adjustment of
the calibration drift of the CPMS.
(iii) Daily checks for indications that
the system is responding. If the CPMS
system includes an internal system
check, the owner or operator may use
the results to verify the system is
responding, as long as the system
provides an alarm to the owner or
operator or the owner or operator checks
the internal system results daily for
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
proper operation and the results are
recorded.
(iv) Preventive maintenance of the
CPMS, including spare parts inventory.
(v) Data recording, calculations and
reporting.
(vi) Program of corrective action for a
CPMS that is not operating properly.
(c) Out-of-control periods. For each
CPMS installed to comply with
applicable provisions in § 63.670 except
for CPMS installed for pilot flame
monitoring, the owner or operator shall
comply with the out-of-control
procedures described in paragraphs
(c)(1) and (2) of this section.
(1) A CPMS is out-of-control if the
zero (low-level), mid-level (if
applicable) or high-level calibration
drift exceeds two times the accuracy
requirement of table 13 of this subpart.
(2) When the CPMS is out of control,
the owner or operator shall take the
necessary corrective action and repeat
all necessary tests that indicate the
system is out of control. The owner or
operator shall take corrective action and
conduct retesting until the performance
requirements are below the applicable
limits. The beginning of the out-ofcontrol period is the hour a performance
check (e.g., calibration drift) that
indicates an exceedance of the
performance requirements established
in this section is conducted. The end of
the out-of-control period is the hour
following the completion of corrective
action and successful demonstration
that the system is within the allowable
limits. The owner or operator shall not
use data recorded during periods the
CPMS is out of control in data averages
and calculations, used to report
emissions or operating levels, as
specified in paragraph (d)(3) of this
section.
(d) CPMS data reduction. The owner
or operator shall reduce data from a
CPMS installed to comply with
applicable provisions in § 63.670 as
specified in paragraphs (d)(1) through
(3) of this section.
(1) The owner or operator may round
the data to the same number of
significant digits used in that operating
limit.
(2) Periods of non-operation of the
process unit (or portion thereof)
resulting in cessation of the emissions to
which the monitoring applies must not
be included in the 15-minute block
averages.
(3) Periods when the CPMS is out of
control must not be included in the 15minute block averages.
(e) Additional requirements for gas
chromatographs. For monitors used to
determine compositional analysis for
net heating value per § 63.670(j)(1), the
PO 00000
Frm 00091
Fmt 4701
Sfmt 4700
75267
gas chromatograph must also meet the
requirements of paragraphs (e)(1)
through (3) of this section.
(1) The quality assurance
requirements are in table 13 of this
subpart.
(2) The calibration gases must meet
one of the following options:
(i) The owner or operator must use a
calibration gas or multiple gases that
include all of compounds listed in
paragraphs (e)(2)(i)(A) through (K) of
this section that may be reasonably
expected to exist in the flare gas stream
and optionally include any of the
compounds listed in paragraphs
(e)(2)(i)(L) through (O) of this section.
All of the calibration gases may be
combined in one cylinder. If multiple
calibration gases are necessary to cover
all compounds, the owner or operator
must calibrate the instrument on all of
the gases.
(A) Hydrogen.
(B) Methane.
(C) Ethane.
(D) Ethylene.
(E) Propane.
(F) Propylene.
(G) n-Butane.
(H) iso-Butane.
(I) Butene (general). It is not necessary
to separately speciate butene isomers,
but the net heating value of trans-butene
must be used for co-eluting butene
isomers.
(J) 1,3-Butadiene. It is not necessary to
separately speciate butadiene isomers,
but you must use the response factor
and net heating value of 1,3-butadiene
for co-eluting butadiene isomers.
(K) n-Pentane. Use the response factor
for n-pentane to quantify all C5+
hydrocarbons.
(L) Acetylene (optional).
(M) Carbon monoxide (optional).
(N) Propadiene (optional).
(O) Hydrogen sulfide (optional).
(ii) The owner or operator must use a
surrogate calibration gas consisting of
hydrogen and C1 through C5 normal
hydrocarbons. All of the calibration
gases may be combined in one cylinder.
If multiple calibration gases are
necessary to cover all compounds, the
owner or operator must calibrate the
instrument on all of the gases.
(3) If the owner or operator chooses to
use a surrogate calibration gas under
paragraph (e)(2)(ii) of this section, the
owner or operator must comply with
paragraphs (e)(3)(i) and (ii) of this
section.
(i) Use the response factor for the
nearest normal hydrocarbon (i.e., nalkane) in the calibration mixture to
quantify unknown components detected
in the analysis.
(ii) Use the response factor for npentane to quantify unknown
E:\FR\FM\01DER2.SGM
01DER2
75268
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
components detected in the analysis
that elute after n-pentane.
■ 34. The appendix to subpart CC is
amended in table 6 by:
■ a. Revising the entries ‘‘63.5(d)(1)(ii)’’
and ‘‘63.5(f)’’;
■ b. Removing the entry ‘‘63.6(e)(1)’’;
■ c. Adding, in numerical order, the
entries ‘‘63.6(e)(1)(i) and (ii)’’ and
‘‘63.6(e)(1)(iii)’’;
■ d. Revising the entries ‘‘63.6(e)(3)(i),’’
‘‘63.6(e)(3)(iii)–63.6(e)(3)(ix),’’ and
‘‘63.6(f)(1)’’;
■ e. Removing the entry ‘‘63.6(f)(2) and
(3)’’;
■ f. Adding, in numerical order, the
entries ‘‘63.6(f)(2)’’ and ‘‘63.6(f)(3)’’;
■ g. Removing the entry ‘‘63.6(h)(1) and
63.6(h)(2)’’;
h. Adding, in numerical order, the
entries ‘‘63.6(h)(1)’’ and ‘‘63.6(h)(2)’’;
■ i. Revising the entries ‘‘63.7(b)’’ and
‘‘63.7(e)(1)’’;
■ j. Removing the entry ‘‘63.8(a)’’;
■ k. Adding, in numerical order, the
entries ‘‘63.8(a)(1) and (2),’’ ‘‘63.8(a)(3),’’
and ‘‘63.8(a)(4)’’;
■ l. Revising the entry ‘‘63.8(c)(1)’’;
■ m. Adding, in numerical order, the
entries ‘‘63.8(c)(1)(i)’’ and
‘‘63.8(c)(1)(iii)’’;
■ n. Revising the entries ‘‘63.8(c)(4),’’
‘‘63.8(c)(5)–63.8(c)(8),’’ ‘‘63.8(d),’’
‘‘63.8(e),’’ ‘‘63.8(g),’’ ‘‘63.10(b)(2)(i),’’
‘‘63.10(b)(2)(ii),’’ ‘‘63.10(b)(2)(iv),’’
‘‘63.10(b)(2)(v),’’ and ‘‘63.10(b)(2)(vii)’’;
■ o. Removing the entry ‘‘63.10(c)(9)–
63.10(c)(15)’’;
■
p. Adding, in numerical order, the
entries ‘‘63.10(c)(9),’’ ‘‘63.10(c)(10)–
63.10(c)(11),’’ and ‘‘63.10(c)(12)–
63.10(c)(15)’’;
■ q. Revising the entry ‘‘63.10(d)(2)’’;
■ r. Removing the entries
‘‘63.10(d)(5)(i)’’ and ‘‘63.10(d)(5)(ii)’’;
■ s. Adding, in numerical order, the
entry ‘‘63.10(d)(5)’’;
■ t. Removing the entry ‘‘63.11–63.16’’;
■ u. Adding, in numerical order, the
entries ‘‘63.11’’ and ‘‘63.12–63.16’’;
■ v. Revising footnote a.
■ w. Removing footnote b.
The revisions and additions read as
follows:
■
Appendix to Subpart CC of Part 63—
Tables
*
*
TABLE 6—GENERAL PROVISIONS APPLICABILITY TO SUBPART
*
*
*
CC a
Applies to
subpart CC
Comment
*
*
63.5(d)(1)(ii) .............................................
*
Yes ...................
*
*
*
*
Except that for affected sources subject to this subpart, emission estimates specified in § 63.5(d)(1)(ii)(H) are not required, and § 63.5(d)(1)(ii)(G) and (I) are Reserved and do not apply.
*
*
63.5(f) .......................................................
*
Yes ...................
*
*
*
*
Except that the cross-reference in § 63.5(f)(2) to § 63.9(b)(2) does not apply.
*
*
63.6(e)(1)(i) and (ii) ..................................
63.6(e)(1)(iii) .............................................
*
No .....................
Yes.
*
*
See § 63.642(n) for general duty requirement.
*
*
63.6(e)(3)(i) ..............................................
*
*
No.
*
*
63.6(e)(3)(iii)–63.6(e)(3)(ix) ......................
63.6(f)(1) ..................................................
63.6(f)(2) ..................................................
*
No.
No.
Yes ...................
*
63.6(f)(3) ..................................................
Yes ...................
*
*
63.6(h)(1) .................................................
63.6(h)(2) .................................................
*
No.
Yes ...................
*
*
63.7(b) ......................................................
*
Yes ...................
*
*
*
*
Except this subpart requires notification of performance test at least 30 days (rather than 60 days) prior to the performance test.
*
*
63.7(e)(1) .................................................
tkelley on DSK3SPTVN1PROD with RULES2
Reference
*
No .....................
*
See § 63.642(d)(3).
*
*
*
*
*
63.8(a)(1) and (2) .....................................
63.8(a)(3) .................................................
63.8(a)(4) .................................................
*
Yes.
No .....................
Yes ...................
*
*
*
*
*
*
63.8(c)(1) ..................................................
63.8(c)(1)(i) ..............................................
63.8(c)(1)(iii) .............................................
*
Yes ...................
No .....................
No.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00092
*
*
*
*
*
*
*
*
Except the phrase ‘‘as specified in § 63.7(c)’’ in § 63.6(f)(2)(iii)(D) does not apply
because this subpart does not require a site-specific test plan.
Except the cross-references to § 63.6(f)(1) and (e)(1)(i) are changed to
§ 63.642(n).
*
*
*
*
Except § 63.6(h)(2)(ii), which is reserved.
Reserved.
Except that for a flare complying with § 63.670, the cross-reference to § 63.11 in
this paragraph does not include § 63.11(b).
*
*
Except § 63.8(c)(1)(i) and (iii).
See § 63.642(n).
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
*
01DER2
*
75269
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 6—GENERAL PROVISIONS APPLICABILITY TO SUBPART CC a—Continued
Reference
Applies to
subpart CC
Comment
*
*
63.8(c)(4) ..................................................
*
Yes ...................
63.8(c)(5)–63.8(c)(8) ................................
63.8(d) ......................................................
No .....................
No .....................
*
*
*
*
Except that for sources other than flares, this subpart specifies the monitoring
cycle frequency specified in § 63.8(c)(4)(ii) is ‘‘once every hour’’ rather than ‘‘for
each successive 15-minute period.’’
This subpart specifies continuous monitoring system requirements.
This subpart specifies quality control procedures for continuous monitoring systems.
63.8(e) ......................................................
Yes.
*
*
63.8(g) ......................................................
*
No .....................
*
*
63.10(b)(2)(i) ............................................
63.10(b)(2)(ii) ...........................................
*
No.
No .....................
*
*
63.10(b)(2)(iv) ..........................................
63.10(b)(2)(v) ...........................................
No.
No.
*
*
63.10(b)(2)(vii) ..........................................
*
No .....................
*
*
*
*
§ 63.655(i) specifies records to be kept for parameters measured with continuous
monitors.
*
*
63.10(c)(9) ................................................
63.10(c)(10)–63.10(c)(11) ........................
63.10(c)(12)–63.10(c)(15) ........................
*
No .....................
No .....................
No.
*
*
*
Reserved.
§ 63.655(i) specifies the records that must be kept.
*
*
63.10(d)(2) ...............................................
*
No .....................
*
*
*
*
Although § 63.655(f) specifies performance test reporting, EPA may approve other
timeframes for submittal of performance test data.
*
*
63.10(d)(5) ...............................................
*
No .....................
*
*
§ 63.655(g) specifies the reporting requirements.
*
*
63.11 ........................................................
*
Yes ...................
*
*
*
*
Except that flares complying with § 63.670 are not subject to the requirements of
§ 63.11(b).
63.12–63.16 .............................................
Yes.
*
*
*
*
This subpart specifies data reduction procedures in §§ 63.655(i)(3) and 63.671(d).
*
*
*
*
*
*
§ 63.655(i) specifies the records that must be kept.
*
*
*
*
*
*
a Wherever
subpart A of this part specifies ‘‘postmark’’ dates, submittals may be sent by methods other than the U.S. Mail (e.g., by fax or courier). Submittals shall be sent by the specified dates, but a postmark is not required.
35. The appendix to subpart CC is
amended in table 10 by:
■ a. Redesignating the entry ‘‘Flare’’ as
‘‘Flare (if meeting the requirements of
§§ 63.643 and 63.644)’’;
■ b. Adding the entry ‘‘Flare (if meeting
the requirements of §§ 63.670 and
■
63.671)’’ after newly redesignated entry
‘‘Flare (if meeting the requirements of
§§ 63.643 and 63.644)’’;
■ c. Revising the entry ‘‘All control
devices’’; and
■ d. Revising footnote i.
The revisions and additions read as
follows:
Appendix to Subpart CC of Part 63—
Tables
*
*
*
*
*
TABLE 10—MISCELLANEOUS PROCESS VENTS—MONITORING, RECORDKEEPING AND REPORTING REQUIREMENTS FOR
COMPLYING WITH 98 WEIGHT-PERCENT REDUCTION OF TOTAL ORGANIC HAP EMISSIONS OR A LIMIT OF 20 PARTS
PER MILLION BY VOLUME
tkelley on DSK3SPTVN1PROD with RULES2
Control device
Parameters to be monitored a
Recordkeeping and reporting requirements for monitored parameters
*
*
Flare (if meeting the requirements
of §§ 63.670 and 63.671).
All control devices ..........................
*
*
The parameters specified in
§ 63.670.
Presence of flow diverted to the atmosphere from the control device (§ 63.644(c)(1)) or
*
*
*
1. Records as specified in § 63.655(i)(9).
2. Report information as specified in § 63.655(g)(11)—PR.g
1. Hourly records of whether the flow indicator was operating and
whether flow was detected at any time during each hour.
Record and report the times and durations of all periods when the
vent stream is diverted through a bypass line or the monitor is not
operating—PR.g
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00093
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75270
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 10—MISCELLANEOUS PROCESS VENTS—MONITORING, RECORDKEEPING AND REPORTING REQUIREMENTS FOR
COMPLYING WITH 98 WEIGHT-PERCENT REDUCTION OF TOTAL ORGANIC HAP EMISSIONS OR A LIMIT OF 20 PARTS
PER MILLION BY VOLUME—Continued
Parameters to be monitored a
Control device
Monthly inspections of
valves (§ 63.644(c)(2)).
sealed
Recordkeeping and reporting requirements for monitored parameters
1. Records that monthly inspections were performed.
2. Record and report all monthly inspections that show the valves are
not closed or the seal has been changed—PR.g
a Regulatory
citations are listed in parentheses.
*
*
*
*
*
*
*
g PR = Periodic Reports described in § 63.655(g).
*
*
*
*
*
*
*
i Process vents that are routed to refinery fuel gas systems are not regulated under this subpart provided that on and after January 30, 2019,
any flares receiving gas from that fuel gas system are in compliance with § 63.670. No monitoring, recordkeeping, or reporting is required for
boilers and process heaters that combust refinery fuel gas.
36. The appendix to subpart CC is
amended by adding table 11 to read as
follows:
■
Appendix to Subpart CC of Part 63—
Tables
*
*
*
*
*
TABLE 11—COMPLIANCE DATES AND REQUIREMENTS
If the construction/reconstruction
date a is . . .
Then the owner or operator must
comply with . . .
And the owner or operator must
achieve compliance . . .
Except as provided in . . .
(1) After June 30, 2014 .................
(i) Requirements for new sources
in §§ 63.640 through 63.642,
63.647, 63.650 through 63.653,
and 63.656 through 63.660.
(ii) The new source requirements
in § 63.654 for heat exchange
systems.
(i) Requirements for new sources
in §§ 63.640 through 63.653
and 63.656 b c.
(ii) Requirements for new sources
in §§ 63.640 through 63.645,
§§ 63.647 through 63.653, and
§§ 63.656 and 63.657 b.
(iii) Requirements for existing
sources in § 63.658.
(iv) Requirements for new sources
in § 63.660 c.
(v) The new source requirements
in § 63.654 for heat exchange
systems.
(i) Requirements for new sources
in §§ 63.640 through 63.653
and 63.656 d e.
(ii) Requirements for new sources
in §§ 63.640 through 63.645,
63.647 through 63.653, and
63.656 and 63.657 d.
(iii) Requirements for existing
sources in § 63.658.
(iv) Requirements for new sources
in § 63.660 e.
(v) The existing source requirements in § 63.654 for heat exchange systems.
(i) Requirements for existing
sources in §§ 63.640 through
63.653 and 63.656 f g.
Upon initial startup or February 1,
2016, whichever is later.
§ 63.640(k), (l) and (m).
Upon initial startup or October 28,
2009, whichever is later.
§ 63.640(k), (l) and (m).
Upon initial startup ........................
§ 63.640(k), (l) and (m).
On or before January 30, 2019 ....
§ 63.640(k), (l) and (m).
On or before January 30, 2018 ....
§ 63.640(k), (l) and (m).
On or before April 29, 2016 .........
§ 63.640(k), (l) and (m).
Upon initial startup or October 28,
2009, whichever is later.
§ 63.640(k), (l) and (m).
Upon initial startup or August 18,
1995, whichever is later.
§ 63.640(k), (l) and (m).
On or before January 30, 2019 ....
§ 63.640(k), (l) and (m).
On or before January 30, 2018 ....
§ 63.640(k), (l) and (m).
On or before April 29, 2016 .........
§ 63.640(k), (l) and (m).
On or before October 29, 2012 ....
§ 63.640(k), (l) and (m).
(a) On or before August 18, 1998
(1) § 63.640(k), (l) and (m).
(2) § 63.6(c)(5) of subpart A of
this part or unless an extension
has been granted by the Administrator as provided in
§ 63.6(i) of subpart A of this
part.
§ 63.640(k), (l) and (m).
(2) After September 4, 2007 but on
or before June 30, 2014.
(3) After July 14, 1994 but on or
before September 4, 2007.
tkelley on DSK3SPTVN1PROD with RULES2
(4) On or before July 14, 1994 ......
(ii) Requirements for existing
sources in §§ 63.640 through
63.645, 63.647 through 63.653,
and 63.656 and 63.657 f.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00094
Fmt 4701
On or before January 30, 2019 ....
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75271
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 11—COMPLIANCE DATES AND REQUIREMENTS—Continued
If the construction/reconstruction
date a is . . .
Then the owner or operator must
comply with . . .
(v) The existing source requirements in § 63.654 for heat exchange systems
And the owner or operator must
achieve compliance . . .
Except as provided in . . .
(iii) Requirements for existing
sources in § 63.658.
(iv) Requirements for existing
sources in § 63.660 g.
On or before October 29, 2012 ....
On or before January 30, 2018 ....
§ 63.640(k), (l) and (m).
On or before April 29, 2016 .........
§ 63.640(k), (l) and (m).
§ 63.640(k), (l) and (m).
a For purposes of this table, the construction/reconstruction date means the date of construction or reconstruction of an entire affected source
or the date of a process unit addition or change meeting the criteria in § 63.640(i) or (j). If a process unit addition or change does not meet the
criteria in § 63.640(i) or (j), the process unit shall comply with the applicable requirements for existing sources.
b Between the compliance dates in items (2)(i) and (2)(ii) of this table, the owner or operator may elect to comply with either the requirements
in item (2)(i) or item (2)(ii) of this table. The requirements in item (2)(i) of this table no longer apply after demonstrated compliance with the requirements in item (2)(ii) of this table.
c Between the compliance dates in items (2)(i) and (2)(iv) of this table, the owner or operator may elect to comply with either the requirements
in item (2)(i) or item (2)(iv) of this table. The requirements in item (2)(i) of this table no longer apply after demonstrated compliance with the requirements in item (2)(iv) of this table.
d Between the compliance dates in items (3)(i) and (3)(ii) of this table, the owner or operator may elect to comply with either the requirements
in item (3)(i) or item (3)(ii) of this table. The requirements in item (3)(i) of this table no longer apply after demonstrated compliance with the requirements in item (3)(ii) of this table.
e Between the compliance dates in items (3)(i) and (3)(iv) of this table, the owner or operator may elect to comply with either the requirements
in item (3)(i) or item (3)(iv) of this table. The requirements in item (3)(i) of this table no longer apply after demonstrated compliance with the requirements in item (3)(iv) of this table.
f Between the compliance dates in items (4)(i) and (4)(ii) of this table, the owner or operator may elect to comply with either the requirements in
item (4)(i) or item (4)(ii) of this table. The requirements in item (4)(i) of this table no longer apply after demonstrated compliance with the requirements in item (4)(ii) of this table.
g Between the compliance dates in items (4)(i) and (4)(iv) of this table, the owner or operator may elect to comply with either the requirements
in item (4)(i) or item (4)(iv) of this table. The requirements in item (4)(i) of this table no longer apply after demonstrated compliance with the requirements in item (4)(iv) of this table.
37. The appendix to subpart CC is
amended by adding table 12 to read as
follows:
■
Appendix to Subpart CC of Part 63—
Tables
*
*
*
*
*
TABLE 12—INDIVIDUAL COMPONENT PROPERTIES
MWi
(pounds per
pound-mole)
tkelley on DSK3SPTVN1PROD with RULES2
Component
Molecular
formula
Acetylene .............................................................................
Benzene ...............................................................................
1,2-Butadiene ......................................................................
1,3-Butadiene ......................................................................
iso-Butane ............................................................................
n-Butane ..............................................................................
cis-Butene ............................................................................
iso-Butene ............................................................................
trans-Butene ........................................................................
Carbon Dioxide ....................................................................
Carbon Monoxide ................................................................
Cyclopropane .......................................................................
Ethane .................................................................................
Ethylene ...............................................................................
Hydrogen .............................................................................
Hydrogen Sulfide .................................................................
Methane ...............................................................................
Methyl-Acetylene .................................................................
Nitrogen ...............................................................................
Oxygen ................................................................................
Pentane+ (C5+) ...................................................................
Propadiene ..........................................................................
Propane ...............................................................................
Propylene .............................................................................
Water ...................................................................................
C2H2 ...............
C6H6 ...............
C4H6 ...............
C4H6 ...............
C4H10 .............
C4H10 .............
C4H8 ...............
C4H8 ...............
C4H8 ...............
CO2 ................
CO .................
C3H6 ...............
C2H6 ...............
C2H4 ...............
H2 ...................
H2S ................
CH4 ................
C3H4 ...............
N2 ...................
O2 ...................
C5H12 .............
C3H4 ...............
C3H8 ...............
C3H6 ...............
H2O ................
NHVi
(British
thermal units
per standard
cubic foot)
CMNi
(mole per
mole)
26.04
78.11
54.09
54.09
58.12
58.12
56.11
56.11
56.11
44.01
28.01
42.08
30.07
28.05
2.02
34.08
16.04
40.06
28.01
32.00
72.15
40.06
44.10
42.08
18.02
2
6
4
4
4
4
4
4
4
1
1
3
2
2
0
0
1
3
0
0
5
3
3
3
0
1,404
3,591
2,794
2,690
2,957
2,968
2,830
2,928
2,826
0
316
2,185
1,595
1,477
1,212a
587
896
2,088
0
0
3,655
2,066
2,281
2,150
0
LFLi
(volume %)
2.5
1.3
2.0
2.0
1.8
1.8
1.6
1.8
1.7
∞
12.5
2.4
3.0
2.7
4.0
4.0
5.0
1.7
∞
∞
1.4
2.16
2.1
2.4
∞
a The theoretical net heating value for hydrogen is 274 Btu/scf, but for the purposes of the flare requirement in this subpart, a net heating value
of 1,212 Btu/scf shall be used.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00095
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75272
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
38. The appendix to subpart CC is
amended by adding table 13 to read as
follows:
■
Appendix to Subpart CC of Part 63—
Tables
*
*
*
*
*
TABLE 13—CALIBRATION AND QUALITY CONTROL REQUIREMENTS FOR CPMS
Parameter
Minimum accuracy requirements
Calibration requirements
Temperature ....................................
±1 percent over the normal range
of temperature measured, expressed in degrees Celsius (C),
or 2.8 degrees C, whichever is
greater.
Flow Rate for All Flows Other Than
Flare Vent Gas.
±5 percent over the normal range
of flow measured or 1.9 liters
per minute (0.5 gallons per
minute), whichever is greater,
for liquid flow.
±5 percent over the normal range
of flow measured or 280 liters
per minute (10 cubic feet per
minute), whichever is greater,
for gas flow.
±5 percent over the normal range
measured for mass flow.
Conduct calibration checks at least annually; conduct calibration
checks following any period of more than 24 hours throughout
which the temperature exceeded the manufacturer’s specified maximum rated temperature or install a new temperature sensor.
At least quarterly, inspect all components for integrity and all electrical connections for continuity, oxidation, and galvanic corrosion,
unless the CPMS has a redundant temperature sensor.
Record the results of each calibration check and inspection.
Locate the temperature sensor in a position that provides a representative temperature; shield the temperature sensor system
from electromagnetic interference and chemical contaminants.
Conduct a flow sensor calibration check at least biennially (every two
years); conduct a calibration check following any period of more
than 24 hours throughout which the flow rate exceeded the manufacturer’s specified maximum rated flow rate or install a new flow
sensor.
At least quarterly, inspect all components for leakage, unless the
CPMS has a redundant flow sensor.
±20 percent of flow rate at velocities ranging from 0.03 to 0.3
meters per second (0.1 to 1 feet
per second).
±5 percent of flow rate at velocities greater than 0.3 meters per
second (1 feet per second).
Pressure ..........................................
±5 percent over the normal operating range or 0.12 kilopascals
(0.5 inches of water column),
whichever is greater.
Net Heating Value by Calorimeter ..
tkelley on DSK3SPTVN1PROD with RULES2
Flare Vent Gas Flow Rate ..............
±2 percent of span ........................
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00096
Fmt 4701
Record the results of each calibration check and inspection.
Locate the flow sensor(s) and other necessary equipment (such as
straightening vanes) in a position that provides representative flow;
reduce swirling flow or abnormal velocity distributions due to upstream and downstream disturbances.
Conduct a flow sensor calibration check at least biennially (every two
years); conduct a calibration check following any period of more
than 24 hours throughout which the flow rate exceeded the manufacturer’s specified maximum rated flow rate or install a new flow
sensor.
At least quarterly, inspect all components for leakage, unless the
CPMS has a redundant flow sensor.
Record the results of each calibration check and inspection.
Locate the flow sensor(s) and other necessary equipment (such as
straightening vanes) in a position that provides representative flow;
reduce swirling flow or abnormal velocity distributions due to upstream and downstream disturbances.
Review pressure sensor readings at least once a week for
straightline (unchanging) pressure and perform corrective action to
ensure proper pressure sensor operation if blockage is indicated.
Using an instrument recommended by the sensor’s manufacturer,
check gauge calibration and transducer calibration annually; conduct calibration checks following any period of more than 24 hours
throughout which the pressure exceeded the manufacturer’s specified maximum rated pressure or install a new pressure sensor.
At least quarterly, inspect all components for integrity, all electrical
connections for continuity, and all mechanical connections for leakage, unless the CPMS has a redundant pressure sensor.
Record the results of each calibration check and inspection.
Locate the pressure sensor(s) in a position that provides a representative measurement of the pressure and minimizes or eliminates
pulsating pressure, vibration, and internal and external corrosion.
Specify calibration requirements in your site specific CPMS monitoring plan. Calibration requirements should follow manufacturer’s
recommendations at a minimum.
Temperature control (heated and/or cooled as necessary) the sampling system to ensure proper year-round operation.
Where feasible, select a sampling location at least two equivalent diameters downstream from and 0.5 equivalent diameters upstream
from the nearest disturbance. Select the sampling location at least
two equivalent duct diameters from the nearest control device,
point of pollutant generation, air in-leakages, or other point at
which a change in the pollutant concentration or emission rate occurs.
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75273
TABLE 13—CALIBRATION AND QUALITY CONTROL REQUIREMENTS FOR CPMS—Continued
Parameter
Minimum accuracy requirements
Calibration requirements
Net Heating Value by Gas Chromatograph.
As specified in Performance Specification 9 of 40 CFR part 60,
appendix B
Hydrogen analyzer ..........................
±2 percent over the concentration
measured or 0.1 volume percent, whichever is greater.
Follow the procedure in Performance Specification 9 of 40 CFR part
60, appendix B, except that a single daily mid-level calibration
check can be used (rather than triplicate analysis), the multi-point
calibration can be conducted quarterly (rather than monthly), and
the sampling line temperature must be maintained at a minimum
temperature of 60 °C (rather than 120 °C).
Specify calibration requirements in your site specific CPMS monitoring plan. Calibration requirements should follow manufacturer’s
recommendations at a minimum.
Select the sampling location at least two equivalent duct diameters
from the nearest control device, point of pollutant generation, air inleakages, or other point at which a change in the pollutant concentration occurs.
39. Section 63.1562 is amended by
revising paragraphs (b)(3) and (f)(5) to
read as follows:
■
§ 63.1562 What parts of my plant are
covered by this subpart?
*
*
*
*
*
(b) * * *
(3) The process vent or group of
process vents on Claus or other types of
sulfur recovery plant units or the tail gas
treatment units serving sulfur recovery
plants that are associated with sulfur
recovery.
*
*
*
*
*
(f) * * *
(5) Gaseous streams routed to a fuel
gas system, provided that on and after
January 30, 2019, any flares receiving
gas from the fuel gas system are subject
to § 63.670.
■ 40. Section 63.1564 is amended by:
■ a. Revising paragraphs (a)(1) and (2);
■ b. Adding paragraph (a)(5);
■ c. Removing the equation following
paragraph (b)(4)(ii) and adding it after
paragraph (b)(4)(iii) introductory text;
■ d. Revising paragraphs (b)(2), (b)(4)(i)
and (ii), and (b)(4)(iv); and
■ e. Adding paragraph (c)(5).
The revisions and additions read as
follows:
§ 63.1564 What are my requirements for
metal HAP emissions from catalytic
cracking units?
tkelley on DSK3SPTVN1PROD with RULES2
(a) * * *
Where:
Rc = Coke burn-off rate, kg/hr (lb/hr);
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(1) Except as provided in paragraph
(a)(5) of this section, meet each emission
limitation in Table 1 of this subpart that
applies to you. If your catalytic cracking
unit is subject to the NSPS for PM in
§ 60.102 of this chapter or is subject to
§ 60.102a(b)(1) of this chapter, you must
meet the emission limitations for NSPS
units. If your catalytic cracking unit is
not subject to the NSPS for PM, you can
choose from the four options in
paragraphs (a)(1)(i) through (vi) of this
section:
(i) You can elect to comply with the
NSPS for PM in § 60.102 of this chapter
(Option 1a);
(ii) You can elect to comply with the
NSPS for PM coke burn-off emission
limit in § 60.102a(b)(1) of this chapter
(Option 1b);
(iii) You can elect to comply with the
NSPS for PM concentration limit in
§ 60.102a(b)(1) of this chapter (Option
1c);
(iv) You can elect to comply with the
PM per coke burn-off emission limit in
§ 60.102a(b)(1) of this chapter (Option
2);
(v) You can elect to comply with the
Nickel (Ni) lb/hr emission limit (Option
3); or
(vi) You can elect to comply with the
Ni per coke burn-off emission limit
(Option 4).
(2) Comply with each operating limit
in Table 2 of this subpart that applies to
you. When a specific control device may
be monitored using more than one
continuous parameter monitoring
system, you may select the parameter
with which you will comply. You must
provide notice to the Administrator (or
Qr = Volumetric flow rate of exhaust gas from
catalyst regenerator before adding air or
PO 00000
Frm 00097
Fmt 4701
Sfmt 4700
other designated authority) if you elect
to change the monitoring option.
*
*
*
*
*
(5) During periods of startup,
shutdown and hot standby, you can
choose from the two options in
paragraphs (a)(5)(i) and (ii) of this
section:
(i) You can elect to comply with the
requirements in paragraphs (a)(1) and
(2) of this section, except catalytic
cracking units controlled using a wet
scrubber must maintain only the liquid
to gas ratio operating limit (the pressure
drop operating limit does not apply); or
(ii) You can elect to maintain the inlet
velocity to the primary internal cyclones
of the catalytic cracking unit catalyst
regenerator at or above 20 feet per
second.
(b) * * *
(2) Conduct a performance test for
each catalytic cracking unit according to
the requirements in § 63.1571 and under
the conditions specified in Table 4 of
this subpart.
*
*
*
*
*
(4) * * *
(i) If you elect Option 1b or Option 2
in paragraph (a)(1)(ii) or (iv) of this
section, compute the PM emission rate
(lb/1,000 lb of coke burn-off) for each
run using Equations 1, 2, and 3 (if
applicable) of this section and the sitespecific opacity limit, if applicable,
using Equation 4 of this section as
follows:
gas streams. Example: You may measure
upstream or downstream of an
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.018
Subpart UUU-—National Emission
Standards for Hazardous Air Pollutants
for Petroleum Refineries: Catalytic
Cracking Units, Catalytic Reforming
Units, and Sulfur Recovery Units
75274
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Qsd = Volumetric flow rate of the catalytic
cracking unit catalyst regenerator flue
gas as measured by Method 2 in
appendix A–1 to part 60 of this chapter,
dscm/hr (dscf/hr);
Rc = Coke burn-off rate, kg coke/hr (1,000 lb
coke/hr); and
K = Conversion factor, 1.0 (kg2/g)/(1,000 kg)
(1,000 lb/(1,000 lb)).
Where:
Es = Emission rate of PM allowed, kg/1,000
kg (1b/1,000 lb) of coke burn-off in
catalyst regenerator;
1.0 = Emission limitation, kg coke/1,000 kg
(lb coke/1,000 lb);
A = Allowable incremental rate of PM
emissions. Before August 1, 2017, A =
0.18 g/million cal (0.10 lb/million Btu).
On or after August 1, 2017, A = 0 g/
million cal (0 lb/million Btu);
H = Heat input rate from solid or liquid fossil
fuel, million cal/hr (million Btu/hr).
Make sure your permitting authority
approves procedures for determining the
heat input rate;
Rc = Coke burn-off rate, kg coke/hr (1,000 lb
coke/hr) determined using Equation 1 of
this section; and
K′ = Conversion factor to units to standard,
1.0 (kg2/g)/(1,000 kg) (103 lb/(1,000 lb)).
Where:
Opacity Limit = Maximum permissible
hourly average opacity, percent, or 10
percent, whichever is greater;
Opacityst = Hourly average opacity measured
during the source test, percent; and
PMEmRst = PM emission rate measured
during the source test, lb/1,000 lb coke
burn.
(ii) If you elect Option 1c in paragraph
(a)(1)(iii) of this section, the PM
concentration emission limit, determine
the average PM concentration from the
initial performance test used to certify
your PM CEMS.
*
*
*
*
*
(iv) If you elect Option 4 in paragraph
(a)(1)(vi) of this section, the Ni per coke
burn-off emission limit, compute your
Ni emission rate using Equations 1 and
8 of this section and your site-specific
Ni operating limit (if you use a
continuous opacity monitoring system)
using Equations 9 and 10 of this section
as follows:
Where:
ENi2 = Normalized mass emission rate of Ni,
mg/kg coke (lb/1,000 lb coke).
ER01DE15.023
Qoxy = Volumetric flow rate of oxygenenriched air stream to regenerator, as
determined from instruments in the
catalytic cracking unit control room,
dscm/min (dscf/min); and
%Oxy = Oxygen concentration in oxygenenriched air stream, percent by volume
(dry basis).
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00098
Fmt 4701
Sfmt 4725
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.019
ER01DE15.020
ER01DE15.021
ER01DE15.022
%CO = Carbon monoxide concentration in
regenerator exhaust, percent by volume
(dry basis);
%O2 = Oxygen concentration in regenerator
exhaust, percent by volume (dry basis);
K1 = Material balance and conversion factor,
0.2982 (kg-min)/(hr-dscm-%) (0.0186 (lbmin)/(hr-dscf-%));
K2 = Material balance and conversion factor,
2.088 (kg-min)/(hr-dscm) (0.1303 (lbmin)/(hr-dscf));
K3 = Material balance and conversion factor,
0.0994 (kg-min)/(hr-dscm-%) (0.0062 (lbmin)/(hr-dscf-%));
Where:
E = Emission rate of PM, kg/1,000 kg (lb/
1,000 lb) of coke burn-off;
Cs = Concentration of PM, g/dscm (lb/dscf);
tkelley on DSK3SPTVN1PROD with RULES2
electrostatic precipitator, but you must
measure upstream of a carbon monoxide
boiler, dscm/min (dscf/min). You may
use the alternative in either
§ 63.1573(a)(1) or (2), as applicable, to
calculate Qr;
Qa = Volumetric flow rate of air to catalytic
cracking unit catalyst regenerator, as
determined from instruments in the
catalytic cracking unit control room,
dscm/min (dscf/min);
%CO2 = Carbon dioxide concentration in
regenerator exhaust, percent by volume
(dry basis);
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
NiEmR2st = Average Ni emission rate
calculated as the arithmetic average Ni
emission rate using Equation 8 of this
Where:
Ni Operating Limit2 = Maximum permissible
hourly average Ni operating limit,
percent-ppmw-acfm-hr/kg coke, i.e.,
your site-specific Ni operating limit; and
Rc,st = Coke burn rate from Equation 1 of this
section, as measured during the initial
performance test, kg coke/hr.
§ 63.1565 What are my requirements for
organic HAP emissions from catalytic
cracking units?
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
(c) * * *
(5) If you elect to comply with the
alternative limit in paragraph (a)(5)(ii) of
this section during periods of startup,
shutdown, and hot standby,
demonstrate continuous compliance by:
(i) Collecting the volumetric flow rate
from the catalyst regenerator (in acfm)
and determining the average flow rate
for each hour. For events lasting less
than one hour, determine the average
flow rate during the event.
(ii) Determining the cumulative crosssectional area of the primary internal
cyclone inlets in square feet (ft2) using
design drawings of the primary (firststage) internal cyclones to determine the
inlet cross-sectional area of each
primary internal cyclone and summing
the cross-sectional areas for all primary
internal cyclones in the catalyst
regenerator or, if primary cyclones. If all
primary internal cyclones are identical,
you may alternatively determine the
inlet cross-sectional area of one primary
internal cyclone using design drawings
and multiply that area by the total
number of primary internal cyclones in
the catalyst regenerator.
(iii) Calculating the inlet velocity to
the primary internal cyclones in square
feet per second (ft2/sec) by dividing the
average volumetric flow rate (acfm) by
the cumulative cross-sectional area of
the primary internal cyclone inlets (ft2)
and by 60 seconds/minute (for unit
conversion).
(iv) Maintaining the inlet velocity to
the primary internal cyclones at or
above 20 feet per second for each hour
during the startup, shutdown, or hot
standby event or, for events lasting less
than 1 hour, for the duration of the
event.
■ 41. Section 63.1565 is amended by
revising paragraph (a)(1) introductory
text and adding paragraph (a)(5) to read
as follows:
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
(a) * * *
(1) Except as provided in paragraph
(a)(5) of this section, meet each emission
limitation in Table 8 of this subpart that
applies to you. If your catalytic cracking
unit is subject to the NSPS for carbon
monoxide (CO) in § 60.103 of this
chapter or is subject to § 60.102a(b)(4) of
this chapter, you must meet the
emission limitations for NSPS units. If
your catalytic cracking unit is not
subject to the NSPS for CO, you can
choose from the two options in
paragraphs (a)(1)(i) through (ii) of this
section:
*
*
*
*
*
(5) During periods of startup,
shutdown and hot standby, you can
choose from the two options in
paragraphs (a)(5)(i) and (ii) of this
section:
(i) You can elect to comply with the
requirements in paragraphs (a)(1) and
(2) of this section; or
(ii) You can elect to maintain the
oxygen (O2) concentration in the
exhaust gas from your catalyst
regenerator at or above 1 volume
percent (dry basis).
*
*
*
*
*
■ 42. Section 63.1566 is amended by
revising paragraphs (a)(1) introductory
text, (a)(1)(i), and (a)(4) to read as
follows:
§ 63.1566 What are my requirements for
organic HAP emissions from catalytic
reforming units?
(a) * * *
(1) Meet each emission limitation in
Table 15 of this subpart that applies to
you. You can choose from the two
options in paragraphs (a)(1)(i) and (ii) of
this section.
(i) You can elect to vent emissions of
total organic compounds (TOC) to a
flare (Option 1). On and after January
30, 2019, the flare must meet the
requirements of § 63.670. Prior to
January 30, 2019, the flare must meet
the control device requirements in
§ 63.11(b) or the requirements of
§ 63.670.
*
*
*
*
*
PO 00000
Frm 00099
Fmt 4701
Sfmt 4700
section for each of the performance test
runs, mg/kg coke.
(4) The emission limitations in Tables
15 and 16 of this subpart do not apply
to emissions from process vents during
passive depressuring when the reactor
vent pressure is 5 pounds per square
inch gauge (psig) or less. The emission
limitations in Tables 15 and 16 of this
subpart do apply to emissions from
process vents during active purging
operations (when nitrogen or other
purge gas is actively introduced to the
reactor vessel) or active depressuring
(using a vacuum pump, ejector system,
or similar device) regardless of the
reactor vent pressure.
*
*
*
*
*
■ 43. Section 63.1568 is amended by
revising paragraphs (a)(1) introductory
text and (a)(1)(i) and adding paragraph
(a)(4) to read as follows:
§ 63.1568 What are my requirements for
HAP emissions from sulfur recovery units?
(a) * * *
(1) Meet each emission limitation in
Table 29 of this subpart that applies to
you. If your sulfur recovery unit is
subject to the NSPS for sulfur oxides in
§ 60.104 or § 60.102a(f)(1) of this
chapter, you must meet the emission
limitations for NSPS units. If your sulfur
recovery unit is not subject to one of
these NSPS for sulfur oxides, you can
choose from the options in paragraphs
(a)(1)(i) through (ii) of this section:
(i) You can elect to meet the NSPS
requirements in § 60.104(a)(2) or
§ 60.102a(f)(1) of this chapter (Option 1);
or
*
*
*
*
*
(4) During periods of startup and
shutdown, you can choose from the
three options in paragraphs (a)(4)(i)
through (iii) of this section.
(i) You can elect to comply with the
requirements in paragraphs (a)(1) and
(2) of this section.
(ii) You can elect to send any startup
or shutdown purge gases to a flare. On
and after January 30, 2019, the flare
must meet the requirements of § 63.670.
Prior to January 30, 2019, the flare must
meet the design and operating
requirements in § 63.11(b) or the
requirements of § 63.670.
(iii) You can elect to send any startup
or shutdown purge gases to a thermal
oxidizer or incinerator operated at a
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.024
Where:
Opacity2 = Opacity value for use in Equation
10 of this section, percent, or 10 percent,
whichever is greater; and
75275
75276
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
minimum hourly average temperature of
1,200 degrees Fahrenheit in the firebox
and a minimum hourly average outlet
oxygen (O2) concentration of 2 volume
percent (dry basis).
*
*
*
*
*
44. Section 63.1570 is amended by
revising paragraphs (a) through (d) and
removing paragraph (g) to read as
follows:
■
§ 63.1570 What are my general
requirements for complying with this
subpart?
(a) You must be in compliance with
all of the non-opacity standards in this
subpart at all times.
(b) You must be in compliance with
the opacity and visible emission limits
in this subpart at all times.
(c) At all times, you must operate and
maintain any affected source, including
associated air pollution control
equipment and monitoring equipment,
in a manner consistent with safety and
good air pollution control practices for
minimizing emissions. The general duty
to minimize emissions does not require
you to make any further efforts to
reduce emissions if levels required by
the applicable standard have been
achieved. Determination of whether a
source is operating in compliance with
operation and maintenance
requirements will be based on
information available to the
Administrator which may include, but
is not limited to, monitoring results,
review of operation and maintenance
procedures, review of operation and
maintenance records, and inspection of
the source.
(d) During the period between the
compliance date specified for your
affected source and the date upon which
continuous monitoring systems have
been installed and validated and any
applicable operating limits have been
set, you must maintain a log that
documents the procedures used to
minimize emissions from process and
emissions control equipment according
to the general duty in paragraph (c) of
this section.
*
*
*
*
*
45. Section 63.1571 is amended by:
a. Adding paragraphs (a)(5) and (6);
■ b. Revising paragraph (b)(1);
■ c. Removing paragraph (b)(4);
■ d. Redesignating paragraph (b)(5) as
paragraph (b)(4); and
■ e. Revising the first sentence of
paragraph (d)(2) and paragraph (d)(4).
The revisions and additions read as
follows:
■
tkelley on DSK3SPTVN1PROD with RULES2
■
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
§ 63.1571 How and when do I conduct a
performance test or other initial compliance
demonstration?
(a) * * *
(5) Periodic performance testing for
PM or Ni. Except as provided in
paragraphs (a)(5)(i) and (ii) of this
section, conduct a periodic performance
test for PM or Ni for each catalytic
cracking unit at least once every 5 years
according to the requirements in Table
4 of this subpart. You must conduct the
first periodic performance test no later
than August 1, 2017.
(i) Catalytic cracking units monitoring
PM concentration with a PM CEMS are
not required to conduct a periodic PM
performance test.
(ii) Conduct a performance test
annually if you comply with the
emission limits in Item 1 (NSPS subpart
J) or Item 4 (Option 1a) in Table 1 of this
subpart and the PM emissions measured
during the most recent performance
source test are greater than 0.80 g/kg
coke burn-off.
(6) One-time performance testing for
HCN. Conduct a performance test for
HCN from each catalytic cracking unit
no later than August 1, 2017 according
to the applicable requirements in
paragraphs (a)(6)(i) and (ii) of this
section.
(i) If you conducted a performance
test for HCN for a specific catalytic
cracking unit between March 31, 2011
and February 1, 2016, you may submit
a request to the Administrator to use the
previously conducted performance test
results to fulfill the one-time
performance test requirement for HCN
for each of the catalytic cracking units
tested according to the requirements in
paragraphs (a)(6)(i)(A) through (D) of
this section.
(A) The request must include a copy
of the complete source test report, the
date(s) of the performance test and the
test methods used. If available, you
must also indicate whether the catalytic
cracking unit catalyst regenerator was
operated in partial or complete
combustion mode during the test, the
control device configuration, including
whether platinum or palladium
combustion promoters were used during
the test, and the CO concentration
(measured using CO CEMS or manual
test method) for each test run.
(B) You must submit a separate
request for each catalytic cracking unit
tested and you must submit each
request to the Administrator no later
than March 30, 2016.
(C) The Administrator will evaluate
each request with respect to the
completeness of the request, the
completeness of the submitted test
report and the appropriateness of the
PO 00000
Frm 00100
Fmt 4701
Sfmt 4700
test methods used. The Administrator
will notify the facility within 60 days of
receipt of the request if it is approved
or denied. If the Administrator fails to
respond to the facility within 60 days of
receipt of the request, the request will
be automatically approved.
(D) If the request is approved, you do
not need to conduct an additional HCN
performance test. If the request is
denied, you must conduct an additional
HCN performance test following the
requirements in (a)(6)(ii) of this section.
(ii) Unless you receive approval to use
a previously conducted performance
test to fulfill the one-time performance
test requirement for HCN for your
catalytic cracking unit as provided in
paragraph (a)(6)(i) of this section,
conduct a performance test for HCN for
each catalytic cracking unit no later
than August 1, 2017 according to
following requirements:
(A) Select sampling port location,
determine volumetric flow rate, conduct
gas molecular weight analysis and
measure moisture content as specified
in either Item 1 of Table 4 of this
subpart or Item 1 of Table 11 of this
subpart.
(B) Measure HCN concentration using
Method 320 of appendix A of this part.
The method ASTM D6348–03
(Reapproved 2010) including Annexes
A1 through A8 (incorporated by
reference—see § 63.14) is an acceptable
alternative to EPA Method 320 of
appendix A of this part. The method
ASTM D6348–12e1 (incorporated by
reference—see § 63.14) is an acceptable
alternative to EPA Method 320 of
appendix A of this part with the
following two caveats:
(1) The test plan preparation and
implementation in the Annexes to
ASTM D6348–03 (Reapproved 2010),
Sections A1 through A8 are mandatory;
and
(2) In ASTM D6348–03 (Reapproved
2010) Annex A5 (Analyte Spiking
Technique), the percent (%) R must be
determined for each target analyte
(Equation A5.5). In order for the test
data to be acceptable for a compound,
%R must be 70% ≥ R ≤ 130%. If the %R
value does not meet this criterion for a
target compound, the test data is not
acceptable for that compound and the
test must be repeated for that analyte
(i.e., the sampling and/or analytical
procedure should be adjusted before a
retest). The %R value for each
compound must be reported in the test
report, and all field measurements must
be corrected with the calculated %R
value for that compound by using the
following equation:
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Reported Result = (Measured
Concentration in the Stack × 100÷/
% R.
(C) Measure CO concentration as
specified in either Item 2 or 3a of Table
11 of this subpart.
(D) Record and include in the test
report an indication of whether the
catalytic cracking unit catalyst
regenerator was operated in partial or
complete combustion mode and the
control device configuration, including
whether platinum or palladium
combustion promoters were used during
the test.
(b) * * *
(1) Performance tests shall be
conducted according to the provisions
of § 63.7(e) except that performance
tests shall be conducted at maximum
representative operating capacity for the
process. During the performance test,
you must operate the control device at
either maximum or minimum
representative operating conditions for
monitored control device parameters,
whichever results in lower emission
reduction. You must not conduct a
performance test during startup,
shutdown, periods when the control
device is bypassed or periods when the
process, monitoring equipment or
control device is not operating properly.
You may not conduct performance tests
during periods of malfunction. You
must record the process information
that is necessary to document operating
conditions during the test and include
in such record an explanation to
support that the test was conducted at
maximum representative operating
capacity. Upon request, you must make
available to the Administrator such
records as may be necessary to
determine the conditions of
performance tests.
*
*
*
*
*
(d) * * *
(2) If you must meet the HAP metal
emission limitations in § 63.1564, you
elect the option in paragraph (a)(1)(iv)
in § 63.1564 (Ni per coke burn-off), and
you use continuous parameter
monitoring systems, you must establish
an operating limit for the equilibrium
catalyst Ni concentration based on the
laboratory analysis of the equilibrium
catalyst Ni concentration from the
initial performance test. * * *
*
*
*
*
*
(4) Except as specified in paragraph
(d)(3) of this section, if you use
continuous parameter monitoring
systems, you may adjust one of your
monitored operating parameters (flow
rate, total power and secondary current,
pressure drop, liquid-to-gas ratio) from
the average of measured values during
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
the performance test to the maximum
value (or minimum value, if applicable)
representative of worst-case operating
conditions, if necessary. This
adjustment of measured values may be
done using control device design
specifications, manufacturer
recommendations, or other applicable
information. You must provide
supporting documentation and rationale
in your Notification of Compliance
Status, demonstrating to the satisfaction
of your permitting authority, that your
affected source complies with the
applicable emission limit at the
operating limit based on adjusted
values.
*
*
*
*
*
■ 46. Section 63.1572 is amended by
revising paragraphs (c) introductory
text, (c)(1), (3), and (4) and (d)(1) and (2)
to read as follows:
§ 63.1572 What are my monitoring
installation, operation, and maintenance
requirements?
*
*
*
*
*
(c) Except for flare monitoring
systems, you must install, operate, and
maintain each continuous parameter
monitoring system according to the
requirements in paragraphs (c)(1)
through (5) of this section. For flares, on
and after January 30, 2019, you must
install, operate, calibrate, and maintain
monitoring systems as specified in
§§ 63.670 and 63.671. Prior to January
30, 2019, you must either meet the
monitoring system requirements in
paragraphs (c)(1) through (5) of this
section or meet the requirements in
§§ 63.670 and 63.671.
(1) You must install, operate, and
maintain each continuous parameter
monitoring system according to the
requirements in Table 41 of this subpart.
You must also meet the equipment
specifications in Table 41 of this subpart
if pH strips or colormetric tube
sampling systems are used. You must
install, operate, and maintain each
continuous parameter monitoring
system according to the requirements in
Table 41 of this subpart. You must meet
the requirements in Table 41 of this
subpart for BLD systems. Alternatively,
before August 1, 2017, you may install,
operate, and maintain each continuous
parameter monitoring system in a
manner consistent with the
manufacturer’s specifications or other
written procedures that provide
adequate assurance that the equipment
will monitor accurately.
*
*
*
*
*
(3) Each continuous parameter
monitoring system must have valid
hourly average data from at least 75
PO 00000
Frm 00101
Fmt 4701
Sfmt 4700
75277
percent of the hours during which the
process operated, except for BLD
systems.
(4) Each continuous parameter
monitoring system must determine and
record the hourly average of all recorded
readings and if applicable, the daily
average of all recorded readings for each
operating day, except for BLD systems.
The daily average must cover a 24-hour
period if operation is continuous or the
number of hours of operation per day if
operation is not continuous, except for
BLD systems.
*
*
*
*
*
(d) * * *
(1) You must conduct all monitoring
in continuous operation (or collect data
at all required intervals) at all times the
affected source is operating.
(2) You may not use data recorded
during required quality assurance or
control activities (including, as
applicable, calibration checks and
required zero and span adjustments) for
purposes of this regulation, including
data averages and calculations, for
fulfilling a minimum data availability
requirement, if applicable. You must
use all the data collected during all
other periods in assessing the operation
of the control device and associated
control system.
■ 47. Section 63.1573 is amended by:
■ a. Redesignating paragraphs (b), (c),
(d), (e), and (f) as paragraphs (c), (d), (e),
(f), and (g);
■ b. Adding paragraph (b); and
■ c. Revising newly redesignated
paragraphs (c) introductory text, (d)
introductory text, (f) introductory text,
and (g)(1) introductory text.
The revisions and additions read as
follows:
§ 63.1573 What are my monitoring
alternatives?
*
*
*
*
*
(b) What is the approved alternative
for monitoring pressure drop? You may
use this alternative to a continuous
parameter monitoring system for
pressure drop if you operate a jet ejector
type wet scrubber or other type of wet
scrubber equipped with atomizing spray
nozzles. You shall:
(1) Conduct a daily check of the air or
water pressure to the spray nozzles;
(2) Maintain records of the results of
each daily check; and
(3) Repair or replace faulty (e.g.,
leaking or plugged) air or water lines
within 12 hours of identification of an
abnormal pressure reading.
(c) What is the approved alternative
for monitoring pH or alkalinity levels?
You may use the alternative in
E:\FR\FM\01DER2.SGM
01DER2
75278
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
paragraph (c)(1) or (2) of this section for
a catalytic reforming unit.
*
*
*
*
*
(d) Can I use another type of
monitoring system? You may use an
automated data compression system. An
automated data compression system
does not record monitored operating
parameter values at a set frequency (e.g.,
once every hour) but records all values
that meet set criteria for variation from
previously recorded values. You must
maintain a record of the description of
the monitoring system and data
recording system, including the criteria
used to determine which monitored
values are recorded and retained, the
method for calculating daily averages,
and a demonstration that the system
meets all of the criteria in paragraphs
(d)(1) through (5) of this section:
*
*
*
*
*
(f) How do I request to monitor
alternative parameters? You must
submit a request for review and
approval or disapproval to the
Administrator. The request must
include the information in paragraphs
(f)(1) through (5) of this section.
*
*
*
*
*
(g) * * *
(1) You may request alternative
monitoring requirements according to
the procedures in this paragraph if you
meet each of the conditions in
paragraphs (g)(1)(i) through (iii) of this
section:
*
*
*
*
*
■ 48. Section 63.1574 is amended by
revising paragraphs (a)(3) introductory
text and (f)(1) to read as follows:
tkelley on DSK3SPTVN1PROD with RULES2
§ 63.1574 What notifications must I submit
and when?
(a) * * *
(3) If you are required to conduct an
initial performance test, performance
evaluation, design evaluation, opacity
observation, visible emission
observation, or other initial compliance
demonstration, you must submit a
notification of compliance status
according to § 63.9(h)(2)(ii). You can
submit this information in an operating
permit application, in an amendment to
an operating permit application, in a
separate submission, or in any
combination. In a State with an
approved operating permit program
where delegation of authority under
section 112(l) of the CAA has not been
requested or approved, you must
provide a duplicate notification to the
applicable Regional Administrator. If
the required information has been
submitted previously, you do not have
to provide a separate notification of
compliance status. Just refer to the
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
earlier submissions instead of
duplicating and resubmitting the
previously submitted information.
*
*
*
*
*
(f) * * *
(1) You must submit the plan to your
permitting authority for review and
approval along with your notification of
compliance status. While you do not
have to include the entire plan in your
permit under part 70 or 71 of this
chapter, you must include the duty to
prepare and implement the plan as an
applicable requirement in your part 70
or 71 operating permit. You must
submit any changes to your permitting
authority for review and approval and
comply with the plan as submitted until
the change is approved.
*
*
*
*
*
■ 49. Section 63.1575 is amended by:
■ a. Revising paragraphs (d)
introductory text and (d)(1) and (2);
■ b. Adding paragraph (d)(4);
■ c. Revising paragraph (e) introductory
text;
■ d. Removing and reserving paragraph
(e)(1);
■ e. Revising paragraphs (e)(4) and (6)
and (f)(1) and (2);
■ f. Removing and reserving paragraph
(h); and
■ g. Adding paragraph (k).
The revisions and additions read as
follows:
§ 63.1575
when?
What reports must I submit and
*
*
*
*
*
(d) For each deviation from an
emission limitation and for each
deviation from the requirements for
work practice standards that occurs at
an affected source where you are not
using a continuous opacity monitoring
system or a continuous emission
monitoring system to comply with the
emission limitation or work practice
standard in this subpart, the semiannual
compliance report must contain the
information in paragraphs (c)(1) through
(3) of this section and the information
in paragraphs (d)(1) through (4) of this
section.
(1) The total operating time of each
affected source during the reporting
period and identification of the sources
for which there was a deviation.
(2) Information on the number, date,
time, duration, and cause of deviations
(including unknown cause, if
applicable).
*
*
*
*
*
(4) The applicable operating limit or
work practice standard from which you
deviated and either the parameter
monitor reading during the deviation or
a description of how you deviated from
the work practice standard.
PO 00000
Frm 00102
Fmt 4701
Sfmt 4700
(e) For each deviation from an
emission limitation occurring at an
affected source where you are using a
continuous opacity monitoring system
or a continuous emission monitoring
system to comply with the emission
limitation, you must include the
information in paragraphs (c)(1) through
(3) of this section, in paragraphs (d)(1)
through (3) of this section, and in
paragraphs (e)(2) through (13) of this
section.
*
*
*
*
*
(4) An estimate of the quantity of each
regulated pollutant emitted over the
emission limit during the deviation, and
a description of the method used to
estimate the emissions.
*
*
*
*
*
(6) A breakdown of the total duration
of the deviations during the reporting
period and into those that are due to
control equipment problems, process
problems, other known causes, and
other unknown causes.
*
*
*
*
*
(f) * * *
(1) You must include the information
in paragraph (f)(1)(i) or (ii) of this
section, if applicable.
(i) If you are complying with
paragraph (k)(1) of this section, a
summary of the results of any
performance test done during the
reporting period on any affected unit.
Results of the performance test include
the identification of the source tested,
the date of the test, the percentage of
emissions reduction or outlet pollutant
concentration reduction (whichever is
needed to determine compliance) for
each run and for the average of all runs,
and the values of the monitored
operating parameters.
(ii) If you are not complying with
paragraph (k)(1) of this section, a copy
of any performance test done during the
reporting period on any affected unit.
The report may be included in the next
semiannual compliance report. The
copy must include a complete report for
each test method used for a particular
kind of emission point tested. For
additional tests performed for a similar
emission point using the same method,
you must submit the results and any
other information required, but a
complete test report is not required. A
complete test report contains a brief
process description; a simplified flow
diagram showing affected processes,
control equipment, and sampling point
locations; sampling site data;
description of sampling and analysis
procedures and any modifications to
standard procedures; quality assurance
procedures; record of operating
conditions during the test; record of
E:\FR\FM\01DER2.SGM
01DER2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
preparation of standards; record of
calibrations; raw data sheets for field
sampling; raw data sheets for field and
laboratory analyses; documentation of
calculations; and any other information
required by the test method.
(2) Any requested change in the
applicability of an emission standard
(e.g., you want to change from the PM
standard to the Ni standard for catalytic
cracking units or from the HCl
concentration standard to percent
reduction for catalytic reforming units)
in your compliance report. You must
include all information and data
necessary to demonstrate compliance
with the new emission standard
selected and any other associated
requirements.
*
*
*
*
*
(k) Electronic submittal of
performance test and CEMS
performance evaluation data. For
performance tests or CEMS performance
evaluations conducted on and after
February 1, 2016, if required to submit
the results of a performance test or
CEMS performance evaluation, you
must submit the results according to the
procedures in paragraphs (k)(1) and (2)
of this section.
(1) Within 60 days after the date of
completing each performance test as
required by this subpart, you must
submit the results of the performance
tests following the procedure specified
in either paragraph (k)(1)(i) or (ii) of this
section.
(i) For data collected using test
methods supported by the EPA’s
Electronic Reporting Tool (ERT) as
listed on the EPA’s ERT Web site
(https://www.epa.gov/ttn/chief/ert/
index.html) at the time of the test, you
must submit the results of the
performance test to the EPA via the
Compliance and Emissions Data
Reporting Interface (CEDRI). (CEDRI can
be accessed through the EPA’s Central
Data Exchange (CDX) (https://
cdx.epa.gov/).) Performance test data
must be submitted in a file format
generated through use of the EPA’s ERT
or an alternate electronic file format
consistent with the extensible markup
language (XML) schema listed on the
EPA’s ERT Web site. If you claim that
some of the performance test
information being submitted is
confidential business information (CBI),
you must submit a complete file
generated through the use of the EPA’s
ERT or an alternate electronic file
consistent with the XML schema listed
on the EPA’s ERT Web site, including
information claimed to be CBI, on a
compact disc, flash drive or other
commonly used electronic storage
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
media to the EPA. The electronic storage
media must be clearly marked as CBI
and mailed to U.S. EPA/OAQPS/CORE
CBI Office, Attention: Group Leader,
Measurement Policy Group, MD C404–
02, 4930 Old Page Rd., Durham, NC
27703. The same ERT or alternate file
with the CBI omitted must be submitted
to the EPA via the EPA’s CDX as
described earlier in this paragraph
(k)(1)(i).
(ii) For data collected using test
methods that are not supported by the
EPA’s ERT as listed on the EPA’s ERT
Web site at the time of the test, you must
submit the results of the performance
test to the Administrator at the
appropriate address listed in § 63.13.
(2) Within 60 days after the date of
completing each CEMS performance
evaluation required by § 63.1571(a) and
(b), you must submit the results of the
performance evaluation following the
procedure specified in either paragraph
(k)(2)(i) or (ii) of this section.
(i) For performance evaluations of
continuous monitoring systems
measuring relative accuracy test audit
(RATA) pollutants that are supported by
the EPA’s ERT as listed on the EPA’s
ERT Web site at the time of the
evaluation, you must submit the results
of the performance evaluation to the
EPA via the CEDRI. (CEDRI is accessed
through the EPA’s CDX.) Performance
evaluation data must be submitted in a
file format generated through the use of
the EPA’s ERT or an alternate file format
consistent with the XML schema listed
on the EPA’s ERT Web site. If you claim
that some of the performance evaluation
information being submitted is CBI, you
must submit a complete file generated
through the use of the EPA’s ERT or an
alternate electronic file consistent with
the XML schema listed on the EPA’s
ERT Web site, including information
claimed to be CBI, on a compact disc,
flash drive or other commonly used
electronic storage media to the EPA. The
electronic storage media must be clearly
marked as CBI and mailed to U.S. EPA/
OAQPS/CORE CBI Office, Attention:
Group Leader, Measurement Policy
Group, MD C404–02, 4930 Old Page Rd.,
Durham, NC 27703. The same ERT or
alternate file with the CBI omitted must
be submitted to the EPA via the EPA’s
CDX as described earlier in this
paragraph (k)(2)(i).
(ii) For any performance evaluations
of continuous monitoring systems
measuring RATA pollutants that are not
supported by the EPA’s ERT as listed on
the EPA’s ERT Web site at the time of
the evaluation, you must submit the
results of the performance evaluation to
the Administrator at the appropriate
address listed in § 63.13.
PO 00000
Frm 00103
Fmt 4701
Sfmt 4700
75279
50. Section 63.1576 is amended by
revising paragraphs (a)(2) and (b)(3) and
(5) to read as follows:
■
§ 63.1576 What records must I keep, in
what form, and for how long?
(a) * * *
(2) The records specified in
paragraphs (a)(2)(i) through (iv) of this
section.
(i) Record the date, time, and duration
of each startup and/or shutdown period,
recording the periods when the affected
source was subject to the standard
applicable to startup and shutdown.
(ii) In the event that an affected unit
fails to meet an applicable standard,
record the number of failures. For each
failure record the date, time and
duration of each failure.
(iii) For each failure to meet an
applicable standard, record and retain a
list of the affected sources or equipment,
an estimate of the volume of each
regulated pollutant emitted over any
emission limit and a description of the
method used to estimate the emissions.
(iv) Record actions taken to minimize
emissions in accordance with
§ 63.1570(c) and any corrective actions
taken to return the affected unit to its
normal or usual manner of operation.
*
*
*
*
*
(b) * * *
(3) The performance evaluation plan
as described in § 63.8(d)(2) for the life
of the affected source or until the
affected source is no longer subject to
the provisions of this part, to be made
available for inspection, upon request,
by the Administrator. If the performance
evaluation plan is revised, you must
keep previous (i.e., superseded) versions
of the performance evaluation plan on
record to be made available for
inspection, upon request, by the
Administrator, for a period of 5 years
after each revision to the plan. The
program of corrective action should be
included in the plan required under
§ 63.8(d)(2).
*
*
*
*
*
(5) Records of the date and time that
each deviation started and stopped.
*
*
*
*
*
■ 51. Section 63.1579 is amended by:
■ a. Revising the introductory text;
■ b. Adding, in alphabetical order, a
new definition of ‘‘Hot standby’’; and
■ c. Revising the definitions of
‘‘Deviation’’ and ‘‘PM’’.
The revisions read as follows:
§ 63.1579
subpart?
What definitions apply to this
Terms used in this subpart are
defined in the Clean Air Act (CAA), in
40 CFR 63.2, the General Provisions of
E:\FR\FM\01DER2.SGM
01DER2
75280
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
this part (§§ 63.1 through 63.15), and in
this section as listed. If the same term
is defined in subpart A of this part and
in this section, it shall have the meaning
given in this section for purposes of this
subpart.
*
*
*
*
*
Deviation means any instance in
which an affected source subject to this
subpart, or an owner or operator of such
a source:
(1) Fails to meet any requirement or
obligation established by this subpart,
including but not limited to any
emission limit, operating limit, or work
practice standard; or
(2) Fails to meet any term or condition
that is adopted to implement an
applicable requirement in this subpart
and that is included in the operating
permit for any affected source required
to obtain such a permit.
*
*
*
*
*
Hot standby means periods when the
catalytic cracking unit is not receiving
fresh or recycled feed oil but the
catalytic cracking unit is maintained at
elevated temperatures, typically using
torch oil in the catalyst regenerator and
recirculating catalyst, to prevent a
complete shutdown and cold restart of
the catalytic cracking unit.
*
*
*
*
*
PM means, for the purposes of this
subpart, emissions of particulate matter
that serve as a surrogate measure of the
total emissions of particulate matter and
metal HAP contained in the particulate
matter, including but not limited to:
Antimony, arsenic, beryllium,
cadmium, chromium, cobalt, lead,
manganese, nickel, and selenium as
measured by Methods 5, 5B or 5F in
appendix A–3 to part 60 of this chapter
or by an approved alternative method.
*
*
*
*
*
52. Table 1 to subpart UUU of part 63
is revised to read as follows:
As stated in § 63.1564(a)(1), you shall
meet each emission limitation in the
following table that applies to you.
■
TABLE 1 TO SUBPART UUU OF PART 63—METAL HAP EMISSION LIMITS FOR CATALYTIC CRACKING UNITS
For each new or existing catalytic cracking unit . . .
You shall meet the following emission limits for
each catalyst regenerator vent . . .
1. Subject to new source performance standard (NSPS) for PM in 40
CFR 60.102 and not electing § 60.100(e).
PM emissions must not exceed 1.0 gram per kilogram (g/kg) (1.0 lb/
1,000 lb) of coke burn-off, and the opacity of emissions must not exceed 30 percent, except for one 6-minute average opacity reading in
any 1-hour period. Before August 1, 2017, if the discharged gases
pass through an incinerator or waste heat boiler in which you burn
auxiliary or in supplemental liquid or solid fossil fuel, the incremental
rate of PM emissions must not exceed 43.0 grams per Gigajoule (g/
GJ) or 0.10 pounds per million British thermal units (lb/million Btu) of
heat input attributable to the liquid or solid fossil fuel; and the opacity
of emissions must not exceed 30 percent, except for one 6-minute
average opacity reading in any 1-hour period.
PM emissions must not exceed 1.0 g/kg (1.0 lb PM/1,000 lb) of coke
burn-off or, if a PM CEMS is used, 0.040 grain per dry standard
cubic feet (gr/dscf) corrected to 0 percent excess air.
PM emissions must not exceed 0.5 g/kg coke burn-off (0.5 lb/1000 lb
coke burn-off) or, if a PM CEMS is used, 0.020 gr/dscf corrected to 0
percent excess air.
PM emissions must not exceed the limits specified in Item 1 of this
table.
2. Subject to NSPS for PM in 40 CFR 60.102a(b)(1)(i); or 40 CFR
60.102 and electing § 60.100(e).
3. Subject to NSPS for PM in 40 CFR 60.102a(b)(1)(ii) ..........................
4. Option 1a: Elect NSPS subpart J requirements for PM per coke burn
limit and 30% opacity, not subject to the NSPS for PM in 40 CFR
60.102 or 60.102a(b)(1).
5. Option 1b: Elect NSPS subpart Ja requirements for PM per coke
burn-off limit, not subject to the NSPS for PM in 40 CFR 60.102 or
60.102a(b)(1).
6. Option 1c: Elect NSPS subpart Ja requirements for PM concentration limit, not subject to the NSPS for PM in 40 CFR 60.102 or
60.102a(b)(1).
7. Option 2: PM per coke burn-off limit, not subject to the NSPS for PM
in 40 CFR 60.102 or 60.102a(b)(1).
8. Option 3: Ni lb/hr limit, not subject to the NSPS for PM in 40 CFR
60.102 or 60.102a(b)(1).
9. Option 4: Ni per coke burn-off limit, not subject to the NSPS for PM
in 40 CFR 60.102 or 60.102a(b)(1).
53. Table 2 to subpart UUU of part 63
is revised to read as follows:
■
PM emissions must not exceed 1.0 g/kg (1.0 lb PM/1000 lb) of coke
burn-off.
PM emissions must not exceed 0.040 gr/dscf corrected to 0 percent
excess air.
PM emissions must not exceed 1.0 g/kg (1.0 lb PM/1000 lb) of coke
burn-off in the catalyst regenerator.
Nickel (Ni) emissions must not exceed 13,000 milligrams per hour (mg/
hr) (0.029 lb/hr).
Ni emissions must not exceed 1.0 mg/kg (0.001 lb/1,000 lb) of coke
burn-off in the catalyst regenerator.
As stated in § 63.1564(a)(2), you shall
meet each operating limit in the
following table that applies to you.
tkelley on DSK3SPTVN1PROD with RULES2
TABLE 2 TO SUBPART UUU OF PART 63—OPERATING LIMITS FOR METAL HAP EMISSIONS FROM CATALYTIC CRACKING
UNITS
For each new or existing catalytic
cracking unit . . .
For this type of continuous
monitoring system . . .
For this type of control
device . . .
You shall meet this operating
limit . . .
1. Subject to the NSPS for PM in
40 CFR 60.102 and not electing
§ 60.100(e).
Continuous
system.
Any ................................................
Maintain the 3-hour rolling average opacity of emissions from
your catalyst regenerator vent
no higher than 20 percent.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
opacity
PO 00000
monitoring
Frm 00104
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75281
TABLE 2 TO SUBPART UUU OF PART 63—OPERATING LIMITS FOR METAL HAP EMISSIONS FROM CATALYTIC CRACKING
UNITS—Continued
For each new or existing catalytic
cracking unit . . .
For this type of continuous
monitoring system . . .
For this type of control
device . . .
You shall meet this operating
limit . . .
2. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(i) or electing
§ 60.100(e).
a. PM CEMS .................................
Any ................................................
Not applicable.
b. Continuous opacity monitoring
system used to comply with a
site-specific opacity limit.
Cyclone or electrostatic precipitator.
c. Continuous parameter monitoring systems.
Electrostatic precipitator ...............
d. Continuous parameter monitoring systems.
Wet scrubber ................................
e. Bag leak detection (BLD) system.
Fabric filter ....................................
Any ................................................
Any ................................................
Any ................................................
Any ................................................
Maintain the 3-hour rolling average opacity of emissions from
your catalyst regenerator vent
no higher than the site-specific
opacity limit established during
the performance test.
i. Maintain the daily average coke
burn-off rate or daily average
flow rate no higher than the
limit established in the performance test.
ii. Maintain the 3-hour rolling average total power and secondary
current above the limit established in the performance test.
i. Maintain the 3-hour rolling average liquid-to-gas ratio above
the limit established in the performance test.
ii. Except for periods of startup,
shutdown, and hot standby,
maintain the 3-hour rolling average pressure drop above the
limit established in the performance test.1
Maintain particulate loading below
the BLD alarm set point established in the initial adjustment
of the BLD system or allowable
seasonal adjustments.
The applicable operating limits in
Item 2 of this table.
See Item 1 of this table.
Any ................................................
Any ................................................
The applicable operating limits in
Item 2.b, 2.c, 2.d, and 2.e of
this table.
PM CEMS .....................................
Any ................................................
Not applicable.
a. Continuous opacity monitoring
system used to comply with a
site-specific opacity limit.
Cyclone, fabric filter, or electrostatic precipitator.
b. Continuous parameter monitoring systems.
i. Electrostatic precipitator ............
See Item 2.b of this table. Alternatively, before August 1, 2017,
you may maintain the hourly
average opacity of emissions
from your catalyst generator
vent no higher than the sitespecific opacity limit established
during the performance test.
(1) See Item 2.c.i of this table.
(2) See item 2.c.ii of this table. Alternatively, before August 1,
2017, you may maintain the
daily average voltage and secondary current above the limit
established in the performance
test.
tkelley on DSK3SPTVN1PROD with RULES2
3. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(ii).
4. Option 1a: Elect NSPS subpart
J requirements for PM per coke
burn limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
5. Option 1b: Elect NSPS subpart
Ja requirements for PM per coke
burn-off limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
6. Option 1c: Elect NSPS subpart
Ja requirements for PM concentration limit, not subject to
the NSPS for PM in 40 CFR
60.102 or 60.102a(b)(1).
7. Option 2: PM per coke burn-off
limit not subject to the NSPS for
PM in 40 CFR 60.102 or
60.102a(b)(1).
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00105
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75282
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 2 TO SUBPART UUU OF PART 63—OPERATING LIMITS FOR METAL HAP EMISSIONS FROM CATALYTIC CRACKING
UNITS—Continued
For each new or existing catalytic
cracking unit . . .
For this type of continuous
monitoring system . . .
For this type of control
device . . .
You shall meet this operating
limit . . .
ii. Wet scrubber ............................
(1) See Item 2.d.i of this table. Alternatively, before August 1,
2017, you may maintain the
daily average liquid-to-gas ratio
above the limit established in
the performance test.
(2) See Item 2.d.ii of the table. Alternatively, before August 1,
2017, you may maintain the
daily average pressure drop
above the limit established in
the performance test (not applicable to a wet scrubber of the
non-venturi jet-ejector design).
See item 2.e of this table.
Fabric filter ....................................
b. Continuous parameter monitoring systems.
8. Option 3: Ni lb/hr limit not subject to the NSPS for PM in 40
CFR 60.102.
c. Bag leak detection (BLD) system.
a. Continuous opacity monitoring
system.
i. Electrostatic precipitator ............
Cyclone, fabric filter, or electrostatic precipitator.
ii. Wet scrubber ............................
tkelley on DSK3SPTVN1PROD with RULES2
c. Bag leak detection (BLD) system.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00106
Fmt 4701
Fabric filter ....................................
Sfmt 4700
E:\FR\FM\01DER2.SGM
Maintain the 3-hour rolling average Ni operating value no higher than the limit established
during the performance test. Alternatively, before August 1,
2017, you may maintain the
daily average Ni operating
value no higher than the limit
established during the performance test.
(1) See Item 2.c.i of this table.
(2) Maintain the monthly rolling
average of the equilibrium catalyst Ni concentration no higher
than the limit established during
the performance test.
(3) See Item 2.c.ii of this table. Alternatively, before August 1,
2017, you may maintain the
daily average voltage and secondary current (or total power
input) above the established
during the performance test.
(1) Maintain the monthly rolling
average of the equilibrium catalyst Ni concentration no higher
than the limit established during
the performance test.
(2) See Item 2.d.i of this table. Alternatively, before August 1,
2017, you may maintain the
daily average liquid-to-gas ratio
above the limit established during the performance test.
(3) See Item 2.d.ii of this table. Alternatively, before August 1,
2017, you may maintain the
daily average pressure drop
above the limit established during the performance test (not
applicable to a non-venturi wet
scrubber of the jet-ejector design).
See item 2.e of this table.
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75283
TABLE 2 TO SUBPART UUU OF PART 63—OPERATING LIMITS FOR METAL HAP EMISSIONS FROM CATALYTIC CRACKING
UNITS—Continued
For each new or existing catalytic
cracking unit . . .
For this type of continuous
monitoring system . . .
For this type of control
device . . .
You shall meet this operating
limit . . .
9. Option 4: Ni per coke burn-off
limit not subject to the NSPS for
PM in 40 CFR 60.102.
a. Continuous opacity monitoring
system.
Cyclone, fabric filter, or electrostatic precipitator.
b. Continuous parameter monitoring systems.
i. Electrostatic precipitator ............
Maintain the 3-hour rolling average Ni operating value no higher than Ni operating limit established during the performance
test. Alternatively, before August 1, 2017, you may elect to
maintain the daily average Ni
operating value no higher than
the Ni operating limit established during the performance
test.
(1) Maintain the monthly rolling
average of the equilibrium catalyst Ni concentration no higher
than the limit established during
the performance test.
(2) See Item 2.c.ii of this table. Alternatively, before August 1,
2017, you may maintain the
daily average voltage and secondary current (or total power
input) above the limit established during the performance
test.
(1) Maintain the monthly rolling
average of the equilibrium catalyst Ni concentration no higher
than the limit established during
the performance test.
(2) See Item 2.d.i of this table. Alternatively, before August 1,
2017, you may maintain the
daily average liquid-to-gas ratio
above the limit established during the performance test.
(3) See Item 2.d.ii of this table. Alternatively, before August 1,
2017, you may maintain the
daily average pressure drop
above the limit established during the performance test (not
applicable to a non-venturi wet
scrubber of the jet-ejector design).
See item 2.e of this table.
ii. Wet scrubber ............................
10. During periods of startup, shutdown, or hot standby.
c. Bag leak detection (BLD) system.
Any ................................................
Fabric filter ....................................
Any ................................................
Meet
the
requirements
§ 63.1564(a)(5).
in
1 If you use a jet ejector type wet scrubber or other type of wet scrubber equipped with atomizing spray nozzles, you can use the alternative in
§ 63.1573(b), and comply with the daily inspections, recordkeeping, and repair provisions, instead of a continuous parameter monitoring system
for pressure drop across the scrubber.
54. Table 3 to subpart UUU of part 63
is revised to read as follows:
■
As stated in § 63.1564(b)(1), you shall
meet each requirement in the following
table that applies to you.
tkelley on DSK3SPTVN1PROD with RULES2
TABLE 3 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR METAL HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS
For each new or existing catalytic
cracking unit . . .
If you use this type of control device for your vent . . .
You shall install, operate, and maintain a . . .
1. Subject to the NSPS for PM in
40 CFR 60.102 and not electing
§ 60.100(e).
Any .................................................
Continuous opacity monitoring system to measure and record the
opacity of emissions from each catalyst regenerator vent.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00107
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75284
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 3 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR METAL HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit . . .
If you use this type of control device for your vent . . .
You shall install, operate, and maintain a . . .
2. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(i); or in
§ 60.102
and
electing
§ 60.100(e); electing to meet the
PM per coke burn-off limit.
a. Cyclone ......................................
b. Electrostatic precipitator ............
Continuous opacity monitoring system to measure and record the
opacity of emissions from each catalyst regenerator vent.
Continuous opacity monitoring system to measure and record the
opacity of emissions from each catalyst regenerator vent; or continuous parameter monitoring systems to measure and record the
coke burn-off rate or the gas flow rate entering or exiting the control device,1 the voltage, current, and secondary current to the control device.
Continuous parameter monitoring system to measure and record the
pressure drop across the scrubber,2 the coke burn-off rate or the
gas flow rate entering or exiting the control device,3 and total liquid
(or scrubbing liquor) flow rate to the control device.
Continuous bag leak detection system to measure and record increases in relative particulate loading from each catalyst regenerator vent.
Continuous emission monitoring system to measure and record the
concentration of PM and oxygen from each catalyst regenerator
vent.
c. Wet scrubber .............................
d. Fabric Filter ...............................
3. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(i); or in
§ 60.102
and
electing
§ 60.100(e); electing to meet the
PM concentration limit.
4. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(ii) electing to
meet the PM per coke burn-off
limit.
5. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(ii) electing to
meet the PM concentration limit.
6. Option 1a: Elect NSPS subpart
J, PM per coke burn-off limit, not
subject to the NSPS for PM in 40
CFR 60.102 or 60.120a(b)(1).
7. Option 1b: Elect NSPS subpart
Ja, PM per coke burn-off limit,
not subject to the NSPS for PM
in
40
CFR
60.102
or
60.120a(b)(1).
8. Option 1c: Elect NSPS subpart
Ja, PM concentration limit not
subject to the NSPS for PM in 40
CFR 60.102 or 60.120a(b)(1).
9. Option 2: PM per coke burn-off
limit, not subject to the NSPS for
PM in 40 CFR 60.102 or
60.120a(b)(1).
10. Option 3: Ni lb/hr limit not subject to the NSPS for PM in 40
CFR 60.102 or 60.102a(b)(1).
Any .................................................
Any .................................................
The applicable continuous monitoring systems in item 2 of this table.
Any .................................................
See item 3 of this table.
Any .................................................
See item 1 of this table.
Any .................................................
The applicable continuous monitoring systems in item 2 of this table.
Any .................................................
See item 3 of this table.
Any .................................................
The applicable continuous monitoring systems in item 2 of this table.
a. Cyclone ......................................
Continuous opacity monitoring system to measure and record the
opacity of emissions from each catalyst regenerator vent and continuous parameter monitoring system to measure and record the
gas flow rate entering or exiting the control device.1
Continuous opacity monitoring system to measure and record the
opacity of emissions from each catalyst regenerator vent and continuous parameter monitoring system to measure and record the
gas flow rate entering or exiting the control device 1; or continuous
parameter monitoring systems to measure and record the coke
burn-off rate or the gas flow rate entering or exiting the control device 1 and the voltage and current (to measure the total power to
the system) and secondary current to the control device.
Continuous parameter monitoring system to measure and record the
pressure drop across the scrubber,2 gas flow rate entering or
exiting the control device,1 and total liquid (or scrubbing liquor) flow
rate to the control device.
Continuous bag leak detection system to measure and record increases in relative particulate loading from each catalyst regenerator vent or the monitoring systems specified in item 10.a of this
table.
Continuous opacity monitoring system to measure and record the
opacity of emissions from each catalyst regenerator vent and continuous parameter monitoring system to measure and record the
coke burn-off rate and the gas flow rate entering or exiting the control device.1
b. Electrostatic precipitator ............
c. Wet scrubber .............................
tkelley on DSK3SPTVN1PROD with RULES2
d. Fabric Filter ...............................
11. Option 4: Ni per coke burn-off
limit not subject to the NSPS for
PM in 40 CFR 60.102 or
60.102a(b)(1).
VerDate Sep<11>2014
23:11 Nov 30, 2015
a. Cyclone ......................................
Jkt 238001
PO 00000
Frm 00108
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75285
TABLE 3 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR METAL HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit . . .
If you use this type of control device for your vent . . .
You shall install, operate, and maintain a . . .
b. Electrostatic precipitator ............
Continuous opacity monitoring system to measure and record the
opacity of emissions from each catalyst regenerator vent and continuous parameter monitoring system to measure and record the
coke burn-off rate and the gas flow rate entering or exiting the control device 1; or continuous parameter monitoring systems to measure and record the coke burn-off rate or the gas flow rate entering
or exiting the control device 1 and voltage and current (to measure
the total power to the system) and secondary current to the control
device.
Continuous parameter monitoring system to measure and record the
pressure drop across the scrubber,2 gas flow rate entering or
exiting the control device,1 and total liquid (or scrubbing liquor) flow
rate to the control device.
Continuous bag leak detection system to measure and record increases in relative particulate loading from each catalyst regenerator vent or the monitoring systems specified in item 11.a of this
table.
Continuous parameter monitoring system to measure and record the
gas flow rate exiting the catalyst regenerator.1
c. Wet scrubber .............................
d. Fabric Filter ...............................
12. Electing to comply with the operating
limits
in
§ 63.1566(a)(5)(iii) during periods
of startup, shutdown, or hot
standby.
Any .................................................
1 If
applicable, you can use the alternative in § 63.1573(a)(1) instead of a continuous parameter monitoring system for gas flow rate.
you use a jet ejector type wet scrubber or other type of wet scrubber equipped with atomizing spray nozzles, you can use the alternative in
§ 63.1573(b) instead of a continuous parameter monitoring system for pressure drop across the scrubber.
2 If
55. Table 4 to subpart UUU of part 63
is revised to read as follows:
■
As stated in §§ 63.1564(b)(2) and
63.1571(a)(5), you shall meet each
requirement in the following table that
applies to you.
TABLE 4 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR METAL HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS
For each new or existing catalytic
cracking unit catalyst regenerator
vent . . .
Using . . .
According to these
requirements . . .
a. Select sampling port’s location
and the number of traverse
ports.
Method 1 or 1A in appendix A–1
to part 60 of this chapter.
Sampling sites must be located at
the outlet of the control device
or the outlet of the regenerator,
as applicable, and prior to any
releases to the atmosphere.
b. Determine velocity and volumetric flow rate.
1. Any .............................................
You must . . .
Method 2, 2A, 2C, 2D, or 2F in
appendix A–1 to part 60 of this
chapter, or Method 2G in appendix A–2 to part 60 of this
chapter, as applicable.
Method 3, 3A, or 3B in appendix
A–2 to part 60 of this chapter,
as applicable.
Method 4 in appendix A–3 to part
60 of this chapter.
tkelley on DSK3SPTVN1PROD with RULES2
c. Conduct gas molecular weight
analysis.
d. Measure moisture content of
the stack gas.
e. If you use an electrostatic precipitator, record the total number of fields in the control system and how many operated
during the applicable performance test.
f. If you use a wet scrubber,
record the total amount (rate) of
water (or scrubbing liquid) and
the amount (rate) of make-up
liquid to the scrubber during
each test run.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00109
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75286
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 4 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR METAL HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit catalyst regenerator
vent . . .
2. Subject to the NSPS for PM in
40 CFR 60.102 and not elect
§ 60.100(e).
You must . . .
Using . . .
According to these
requirements . . .
a. Measure PM emissions ............
Method 5, 5B, or 5F (40 CFR part
60, appendix A–3) to determine
PM emissions and associated
moisture content for units without wet scrubbers. Method 5 or
5B (40 CFR part 60, appendix
A–3) to determine PM emissions and associated moisture
content for unit with wet scrubber.
Equations 1, 2, and 3 of
§ 63.1564 (if applicable).
You must maintain a sampling
rate of at least 0.15 dry standard cubic meters per minute
(dscm/min) (0.53 dry standard
cubic feet per minute (dscf/
min)).
Continuous
system.
You must collect opacity monitoring data every 10 seconds
during the entire period of the
Method 5, 5B, or 5F performance test and reduce the data
to 6-minute averages.
You must maintain a sampling
rate of at least 0.15 dscm/min
(0.53 dscf/min).
b. Compute coke burn-off rate
and PM emission rate (lb/1,000
lb of coke burn-off).
c. Measure opacity of emissions ..
3. Subject to the NSPS for PM in
40 CFR 60.102a(b)(1) or elect
§ 60.100(e), electing the PM for
coke burn-off limit.
a. Measure PM emissions ............
b. Compute coke burn-off rate
and PM emission rate (lb/1,000
lb of coke burn-off).
c. Establish site-specific limit if
you use a COMS.
tkelley on DSK3SPTVN1PROD with RULES2
4. Subject to the NSPS for PM in
40 CFR 60.102a(b)(1) or elect
§ 60.100(e).
a. Measure PM emissions ............
5. Option 1a: Elect NSPS subpart
J requirements for PM per coke
burn-off limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
6. Option 1b: Elect NSPS subpart
Ja requirements for PM per coke
burn-off limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
See item 2 of this table.
VerDate Sep<11>2014
23:11 Nov 30, 2015
opacity
monitoring
Method 5, 5B, or 5F (40 CFR part
60, appendix A–3) to determine
PM emissions and associated
moisture content for units without wet scrubbers. Method 5 or
5B (40 CFR part 60, appendix
A–3) to determine PM emissions and associated moisture
content for unit with wet scrubber.
Equations 1, 2, and 3 of
§ 63.1564 (if applicable).
Continuous
system.
opacity
monitoring
Method 5, 5B, or 5F (40 CFR part
60, appendix A–3) to determine
PM emissions and associated
moisture content for units without wet scrubbers. Method 5 or
5B (40 CFR part 60, appendix
A–3) to determine PM emissions and associated moisture
content for unit with wet scrubber.
.......................................................
If you elect to comply with the
site-specific opacity limit in
§ 63.1564(b)(4)(i), you must collect opacity monitoring data
every 10 seconds during the
entire period of the Method 5,
5B, or 5F performance test. For
site specific opacity monitoring,
reduce the data to 6-minute
averages; determine and record
the average opacity for each
test run; and compute the sitespecific opacity limit using
Equation 4 of § 63.1564.
You must maintain a sampling
rate of at least 0.15 dscm/min
(0.53 dscf/min).
See item 3 of this table.
Jkt 238001
PO 00000
Frm 00110
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75287
TABLE 4 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR METAL HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit catalyst regenerator
vent . . .
7. Option 1c: Elect NSPS requirements for PM concentration, not
subject to the NSPS for PM in
40 CFR 60.102 or 60.102a(b)(1).
8. Option 2: PM per coke burn-off
limit, not subject to the NSPS for
PM in 40 CFR 60.102 or
60.102a(b)(1).
9. Option 3: Ni lb/hr limit, not subject to the NSPS for PM in 40
CFR 60.102 or 60.102a(b)(1).
You must . . .
According to these
requirements . . .
Using . . .
See item 4 of this table.
See item 3 of this table.
a. Measure concentration of Ni ....
b. Compute Ni emission rate (lb/
hr).
c. Determine the equilibrium catalyst Ni concentration.
Method 29 (40 CFR part 60, appendix A–8).
Equation 5 of § 63.1564.
XRF procedure in appendix A to
this subpart1; or EPA Method
6010B or 6020 or EPA Method
7520 or 7521 in SW–8462; or
an alternative to the SW–846
method satisfactory to the Administrator.
d. If you use a continuous opacity
monitoring system, establish
your site-specific Ni operating
limit.
10. Option 4: Ni per coke burn-off
limit, not subject to the NSPS for
PM in 40 CFR 60.102 or
60.102a(b)(1).
i. Equations 6 and 7 of § 63.1564
using data from continuous
opacity monitoring system, gas
flow rate, results of equilibrium
catalyst Ni concentration analysis, and Ni emission rate from
Method 29 test.
a. Measure concentration of Ni.
Method 29 (40 CFR part 60, appendix A–8).
Equations 1 and 8 of § 63.1564.
b. Compute Ni emission rate (lb/
1,000 lb of coke burn-off).
c. Determine the equilibrium catalyst Ni concentration.
tkelley on DSK3SPTVN1PROD with RULES2
d. If you use a continuous opacity
monitoring system, establish
your site-specific Ni operating
limit.
VerDate Sep<11>2014
23:11 Nov 30, 2015
You must obtain 1 sample for
each of the 3 test runs; determine and record the equilibrium
catalyst Ni concentration for
each of the 3 samples; and you
may adjust the laboratory results to the maximum value
using Equation 2 of § 63.1571.
(1) You must collect opacity monitoring data every 10 seconds
during the entire period of the
initial Ni performance test; reduce the data to 6-minute averages; and determine and record
the average opacity from all the
6-minute averages for each test
run.
(2) You must collect gas flow rate
monitoring data every 15 minutes during the entire period of
the initial Ni performance test;
measure the gas flow as near
as practical to the continuous
opacity monitoring system; and
determine and record the hourly
average actual gas flow rate for
each test run.
Jkt 238001
PO 00000
Frm 00111
Fmt 4701
See item 6.c. of this table ............
i.
Equations 9 and 10 of
§ 63.1564 with data from continuous opacity monitoring system, coke burn-off rate, results
of equilibrium catalyst Ni concentration analysis, and Ni
emission rate from Method 29
test.
Sfmt 4700
E:\FR\FM\01DER2.SGM
You must obtain 1 sample for
each of the 3 test runs; determine and record the equilibrium
catalyst Ni concentration for
each of the 3 samples; and you
may adjust the laboratory results to the maximum value
using Equation 2 of § 63.1571.
(1) You must collect opacity monitoring data every 10 seconds
during the entire period of the
initial Ni performance test; reduce the data to 6-minute averages; and determine and record
the average opacity from all the
6-minute averages for each test
run.
01DER2
75288
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 4 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR METAL HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit catalyst regenerator
vent . . .
You must . . .
According to these
requirements . . .
Using . . .
(2) You must collect gas flow rate
monitoring data every 15 minutes during the entire period of
the initial Ni performance test;
measure the gas flow rate as
near as practical to the continuous opacity monitoring system; and determine and record
the hourly average actual gas
flow rate for each test run.
11. If you elect item 5 Option 1b in
Table 1, item 7 Option 2 in
Table 1, item 8 Option 3 in
Table 1, or item 9 Option 4 in
Table 1 of this subpart and you
use continuous parameter monitoring systems.
e. Record the catalyst addition
rate for each test and schedule
for the 10-day period prior to
the test.
a. Establish each operating limit in
Table 2 of this subpart that applies to you.
Data from the continuous parameter monitoring systems and
applicable performance test
methods.
VerDate Sep<11>2014
23:11 Nov 30, 2015
i. Data from the continuous parameter monitoring systems
and applicable performance test
methods.
c. Electrostatic precipitator: Total
power (voltage and current) and
secondary current.
tkelley on DSK3SPTVN1PROD with RULES2
b. Electrostatic precipitator or wet
scrubber: Gas flow rate.
i. Data from the continuous parameter monitoring systems
and applicable performance test
methods.
Jkt 238001
PO 00000
Frm 00112
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
(1) You must collect gas flow rate
monitoring data every 15 minutes during the entire period of
the initial performance test; determine and record the average
gas flow rate for each test run.
(2) You must determine and
record the 3-hr average gas
flow rate from the test runs. Alternatively, before August 1,
2017, you may determine and
record the maximum hourly average gas flow rate from all the
readings.
(1) You must collect voltage, current, and secondary current
monitoring data every 15 minutes during the entire period of
the performance test; and determine and record the average
voltage, current, and secondary
current for each test run. Alternatively, before August 1, 2017,
you may collect voltage and
secondary current (or total
power input) monitoring data
every 15 minutes during the entire period of the initial performance test.
(2) You must determine and
record the 3-hr average total
power to the system for the test
runs and the 3-hr average secondary current from the test
runs. Alternatively, before August 1, 2017, you may determine and record the minimum
hourly average voltage and
secondary current (or total
power input) from all the readings.
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75289
TABLE 4 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR METAL HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit catalyst regenerator
vent . . .
Results of analysis for equilibrium
catalyst Ni concentration.
i. Data from the continuous parameter monitoring systems
and applicable performance test
methods.
f.
Liquid-to-gas
i. Data from the continuous parameter monitoring systems
and applicable performance test
methods.
g. Alternative procedure for gas
flow rate.
tkelley on DSK3SPTVN1PROD with RULES2
According to these
requirements . . .
e. Wet scrubber: Pressure drop
(not applicable to non-venturi
scrubber of jet ejector design).
VerDate Sep<11>2014
Using . . .
d. Electrostatic precipitator or wet
scrubber: Equilibrium catalyst
Ni concentration.
1 Determination
You must . . .
i. Data from the continuous parameter monitoring systems
and applicable performance test
methods.
You must determine and record
the average equilibrium catalyst
Ni concentration for the 3 runs
based on the laboratory results.
You may adjust the value using
Equation 1 or 2 of § 63.1571 as
applicable.
(1) You must collect pressure
drop monitoring data every 15
minutes during the entire period
of the initial performance test;
and determine and record the
average pressure drop for each
test run.
(2) You must determine and
record the 3-hr average pressure drop from the test runs. Alternatively, before August 1,
2017, you may determine and
record the minimum hourly average pressure drop from all
the readings.
(1) You must collect gas flow rate
and total water (or scrubbing
liquid) flow rate monitoring data
every 15 minutes during the entire period of the initial performance test; determine and record
the average gas flow rate for
each test run; and determine
the average total water (or
scrubbing liquid) flow for each
test run.
(2) You must determine and
record the hourly average liquid-to-gas ratio from the test
runs. Alternatively, before August 1, 2017, you may determine and record the hourly average gas flow rate and total
water (or scrubbing liquid) flow
rate from all the readings.
(3) You must determine and
record the 3-hr average liquidto-gas ratio. Alternatively, before August 1, 2017, you may
determine and record the minimum liquid-to-gas ratio.
(1) You must collect air flow rate
monitoring data or determine
the air flow rate using control
room instrumentation every 15
minutes during the entire period
of the initial performance test.
(2) You must determine and
record the 3-hr average rate of
all the readings from the test
runs. Alternatively, before August 1, 2017, you may determine and record the hourly average rate of all the readings.
(3) You must determine and
record the maximum gas flow
rate using Equation 1 of
§ 63.1573.
Wet
ratio.
scrubber:
of Metal Concentration on Catalyst Particles (Instrumental Analyzer Procedure).
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00113
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75290
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
2 EPA Method 6010B, Inductively Coupled Plasma-Atomic Emission Spectrometry, EPA Method 6020, Inductively Coupled Plasma-Mass Spectrometry, EPA Method 7520, Nickel Atomic Absorption, Direct Aspiration, and EPA Method 7521, Nickel Atomic Absorption, Direct Aspiration are
included in ‘‘Test Methods for Evaluating Solid Waste, Physical/Chemical Methods,’’ EPA Publication SW–846, Revision 5 (April 1998). The SW–
846 and Updates (document number 955–001–00000–1) are available for purchase from the Superintendent of Documents, U.S. Government
Publishing Office, Washington, DC 20402, (202) 512–1800; and from the National Technical Information Services (NTIS), 5285 Port Royal Road,
Springfield, VA 22161, (703) 487–4650. Copies may be inspected at the EPA Docket Center, William Jefferson Clinton (WJC) West Building, (Air
Docket), Room 3334, 1301 Constitution Ave. NW., Washington, DC; or at the Office of the Federal Register, 800 North Capitol Street NW., Suite
700, Washington, DC.
56. Table 5 to subpart UUU of part 63
is revised to read as follows:
■
As stated in § 63.1564(b)(5), you shall
meet each requirement in the following
table that applies to you.
TABLE 5 TO SUBPART UUU OF PART 63—INITIAL COMPLIANCE WITH METAL HAP EMISSION LIMITS FOR CATALYTIC
CRACKING UNITS
For each new and existing catalytic
cracking unit catalyst regenerator
vent . . .
For the following emission
limit . . .
You have demonstrated initial compliance if . . .
1. Subject to the NSPS for PM in
40 CFR 60.102 and not electing
§ 60.100(e).
PM emissions must not exceed
1.0 g/kg (1.0 lb/1,000 lb) of coke
burn-off, and the opacity of
emissions must not exceed 30
percent, except for one 6-minute
average opacity reading in any
1-hour period. Before August 1,
2017, if the discharged gases
pass through an incinerator or
waste heat boiler in which you
burn auxiliary or supplemental
liquid or solid fossil fuel, the incremental rate of PM must not
exceed 43.0 g/GJ or 0.10 lb/million Btu of heat input attributable
to the liquid or solid fossil fuel;
and the opacity of emissions
must not exceed 30 percent, except for one 6-minute average
opacity reading in any 1-hour
period.
PM emissions must not exceed
1.0 g/kg (1.0 lb PM/1,000 lb) of
coke burn-off.
You have already conducted a performance test to demonstrate initial
compliance with the NSPS and the measured PM emission rate is
less than or equal to 1.0 g/kg (1.0 lb/1,000 lb) of coke burn-off in
the catalyst regenerator. As part of the Notification of Compliance
Status, you must certify that your vent meets the PM limit. You are
not required to do another performance test to demonstrate initial
compliance. You have already conducted a performance test to
demonstrate initial compliance with the NSPS and the average
hourly opacity is no more than 30 percent, except that one 6minute average in any 1-hour period can exceed 30 percent. As
part of the Notification of Compliance Status, you must certify that
your vent meets the 30 percent opacity limit. As part of your Notification of Compliance Status, you certify that your continuous opacity monitoring system meets the requirements in § 63.1572.
2. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(i); or in
§ 60.102
and
electing
§ 60.100(e); electing to meet the
PM per coke burn-off limit.
PM emissions must not exceed
0.5 g/kg (0.5 lb PM/1,000 lb) of
coke burn-off).
4. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(i), electing to
meet the PM concentration limit.
tkelley on DSK3SPTVN1PROD with RULES2
3. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(i), electing to
meet the PM per coke burn-off
limit.
If a PM CEMS is used, 0.040
grain per dry standard cubic feet
(gr/dscf) corrected to 0 percent
excess air.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00114
Fmt 4701
You have already conducted a performance test to demonstrate initial
compliance with the NSPS and the measured PM emission rate is
less than or equal to 1.0 g/kg (1.0 lb/1,000 lb) of coke burn-off in
the catalyst regenerator. As part of the Notification of Compliance
Status, you must certify that your vent meets the PM limit. You are
not required to do another performance test to demonstrate initial
compliance. As part of your Notification of Compliance Status, you
certify that your BLD; CO2, O2, or CO monitor; or continuous opacity monitoring system meets the requirements in § 63.1572.
You have already conducted a performance test to demonstrate initial
compliance with the NSPS and the measured PM emission rate is
less than or equal to 1.0 g/kg (1.0 lb/1,000 lb) of coke burn-off in
the catalyst regenerator. As part of the Notification of Compliance
Status, you must certify that your vent meets the PM limit. You are
not required to do another performance test to demonstrate initial
compliance. As part of your Notification of Compliance Status, you
certify that your BLD; CO2, O2, or CO monitor; or continuous opacity monitoring system meets the requirements in § 63.1572.
You have already conducted a performance test to demonstrate initial
compliance with the NSPS and the measured PM concentration is
less than or equal to 0.040 grain per dry standard cubic feet (gr/
dscf) corrected to 0 percent excess air. As part of the Notification
of Compliance Status, you must certify that your vent meets the
PM limit. You are not required to do another performance test to
demonstrate initial compliance. As part of your Notification of Compliance Status, you certify that your PM CEMS meets the requirements in § 63.1572.
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75291
TABLE 5 TO SUBPART UUU OF PART 63—INITIAL COMPLIANCE WITH METAL HAP EMISSION LIMITS FOR CATALYTIC
CRACKING UNITS—Continued
For each new and existing catalytic
cracking unit catalyst regenerator
vent . . .
For the following emission
limit . . .
You have demonstrated initial compliance if . . .
5. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(ii), electing to
meet the PM concentration limit.
If a PM CEMS is used, 0.020 gr/
dscf corrected to 0 percent excess air.
6. Option 1a: Elect NSPS subpart J
requirements for PM per coke
burn-off limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
PM emissions must not exceed
1.0 gram per kilogram (g/kg)
(1.0 lb/1,000 lb) of coke burnoff, and the opacity of emissions
must not exceed 30 percent, except for one 6-minute average
opacity reading in any 1-hour
period. Before August 1, 2017,
PM emission must not exceed
1.0 g/kg (1.0 lb/1,000 lb) of coke
burn-off in the catalyst regenerator; if the discharged gases
pass through an incinerator or
waste heat boiler in which you
burn auxiliary or supplemental
liquid or solid fossil fuel, the incremental rate of PM must not
exceed 43.0 g/GJ (0.10 lb/million Btu) of heat input attributable to the liquid or solid fossil
fuel; and the opacity of emissions must not exceed 30 percent, except for one 6-minute
average opacity reading in any
1-hour period.
PM emissions must not exceed
1.0 g/kg (1.0 lb/1,000 lb) of coke
burn-off.
You have already conducted a performance test to demonstrate initial
compliance with the NSPS and the measured PM concentration is
less than or equal to 0.020 gr/dscf corrected to 0 percent excess
air. As part of the Notification of Compliance Status, you must certify that your vent meets the PM limit. You are not required to do
another performance test to demonstrate initial compliance. As part
of your Notification of Compliance Status, you certify that your PM
CEMS meets the requirements in § 63.1572.
The average PM emission rate, measured using EPA Method 5, 5B,
or 5F (for a unit without a wet scrubber) or 5 or 5B (for a unit with
a wet scrubber) (40 CFR part 60, appendix A–3), over the period
of the initial performance test, is no higher than 1.0 g/kg coke burnoff (1.0 lb/1,000 lb) in the catalyst regenerator. The PM emission
rate is calculated using Equations 1, 2, and 3 of § 63.1564. As part
of the Notification of Compliance Status, you must certify that your
vent meets the PM limit. The average hourly opacity is no more
than 30 percent, except that one 6-minute average in any 1-hour
period can exceed 30 percent. As part of the Notification of Compliance Status, you must certify that your vent meets the 30 percent opacity limit. If you use a continuous opacity monitoring system, your performance evaluation shows the system meets the applicable requirements in § 63.1572.
7. Option 1b: Elect NSPS subpart
Ja requirements for PM per coke
burn-off limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
PM emissions must not exceed
0.040 gr/dscf corrected to 0 percent excess air.
9. Option 2: PM per coke burn-off
limit, not subject to the NSPS for
PM in 40 CFR 60.102 or
60.102a(b)(1).
tkelley on DSK3SPTVN1PROD with RULES2
8. Option 1c: Elect NSPS subpart
Ja requirements for PM concentration limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
PM emissions must not exceed
1.0 g/kg (1.0 lb/1,000 lb) of coke
burn-off.
10. Option 3: Ni lb/hr limit, not subject to the NSPS for PM in 40
CFR 60.102 or 60.102a(b)(1).
Nickel (Ni) emissions from your
catalyst regenerator vent must
not exceed 13,000 mg/hr (0.029
lb/hr).
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00115
Fmt 4701
The average PM emission rate, measured using EPA Method 5, 5B,
or 5F (for a unit without a wet scrubber) or 5 or 5B (for a unit with
a wet scrubber) (40 CFR part 60, appendix A–3), over the period
of the initial performance test, is no higher than 1.0 g/kg coke burnoff (1.0 lb/1,000 lb) in the catalyst regenerator. The PM emission
rate is calculated using Equations 1, 2, and 3 of § 63.1564. If you
use a BLD; CO2, O2, CO monitor; or continuous opacity monitoring
system, your performance evaluation shows the system meets the
applicable requirements in § 63.1572.
The average PM concentration, measured using EPA Method 5, 5B,
or 5F (for a unit without a wet scrubber) or Method 5 or 5B (for a
unit with a wet scrubber) (40 CFR part 60, appendix A–3), over the
period of the initial performance test, is less than or equal to 0.040
gr/dscf corrected to 0 percent excess air. Your performance evaluation shows your PM CEMS meets the applicable requirements in
§ 63.1572.
The average PM emission rate, measured using EPA Method 5, 5B,
or 5F (for a unit without a wet scrubber) or 5 or 5B (for a unit with
a wet scrubber) (40 CFR part 60, appendix A–3), over the period
of the initial performance test, is no higher than 1.0 g/kg coke burnoff (1.0 lb/1,000 lb) in the catalyst regenerator. The PM emission
rate is calculated using Equations 1, 2, and 3 of § 63.1564. If you
use a BLD; CO2, O2, CO monitor; or continuous opacity monitoring
system, your performance evaluation shows the system meets the
applicable requirements in § 63.1572.
The average Ni emission rate, measured using Method 29 (40 CFR
part 60, appendix A–8) over the period of the initial performance
test, is not more than 13,000 mg/hr (0.029 lb/hr). The Ni emission
rate is calculated using Equation 5 of § 63.1564; and if you use a
BLD; CO2, O2, or CO monitor; or continuous opacity monitoring
system, your performance evaluation shows the system meets the
applicable requirements in § 63.1572.
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75292
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 5 TO SUBPART UUU OF PART 63—INITIAL COMPLIANCE WITH METAL HAP EMISSION LIMITS FOR CATALYTIC
CRACKING UNITS—Continued
For each new and existing catalytic
cracking unit catalyst regenerator
vent . . .
For the following emission
limit . . .
You have demonstrated initial compliance if . . .
11. Option 4: Ni per coke burn-off
limit not subject to the NSPS for
PM.
Ni emissions from your catalyst regenerator vent must not exceed
1.0 mg/kg (0.001 lb/1,000 lb) of
coke burn-off in the catalyst regenerator.
The average Ni emission rate, measured using Method 29 (40 CFR
part 60, appendix A–8) over the period of the initial performance
test, is not more than 1.0 mg/kg (0.001 lb/1,000 lb) of coke burn-off
in the catalyst regenerator. The Ni emission rate is calculated using
Equation 8 of § 63.1564; and if you use a BLD; CO2, O2, or CO
monitor; or continuous opacity monitoring system, your performance evaluation shows the system meets the applicable requirements in § 63.1572.
57. Table 6 to subpart UUU of part 63
is revised to read as follows:
■
As stated in § 63.1564(c)(1), you shall
meet each requirement in the following
table that applies to you.
TABLE 6 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH METAL HAP EMISSION LIMITS FOR CATALYTIC
CRACKING UNITS
For each new and existing catalytic
cracking unit . . .
Subject to this emission limit for
your catalyst regenerator vent . . .
You shall demonstrate continuous compliance by . . .
1. Subject to the NSPS for PM in
40 CFR 60.102 and not electing
§ 60.100(e).
a. PM emissions must not exceed
1.0 g/kg (1.0 lb/1,000 lb) of coke
burn-off, and the opacity of
emissions must not exceed 30
percent, except for one 6-minute
average opacity reading in any
1-hour period. Before August 1,
2017, if the discharged gases
pass through an incinerator or
waste heat boiler in which you
burn auxiliary or supplemental
liquid or solid fossil fuel, the incremental rate of PM must not
exceed 43.0 g/GJ (0.10 lb/million Btu) of heat input attributable to the liquid or solid fossil
fuel; and the opacity of emissions must not exceed 30 percent, except for one 6-minute
average opacity reading in any
1-hour period.
i. Determining and recording each day the average coke burn-off rate
(thousands of kilograms per hour) using Equation 1 in § 63.1564
and the hours of operation for each catalyst regenerator.
tkelley on DSK3SPTVN1PROD with RULES2
2. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(i), electing to
meet the PM per coke burn-off
limit.
PM emissions must not exceed
1.0 g/kg (1.0 lb PM/1,000 lb) of
coke burn-off.
3. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(ii), electing to
meet the PM per coke burn-off
limit.
PM emissions must not exceed
0.5 g/kg coke burn-off (0.5 lb/
1000 lb coke burn-off).
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00116
Fmt 4701
ii. Conducting a performance test before August 1, 2017 and thereafter following the testing frequency in § 63.1571(a)(5) as applicable to your unit.
iii. Collecting the continuous opacity monitoring data for each catalyst
regenerator vent according to § 63.1572 and maintaining each 6minute average at or below 30 percent, except that one 6-minute
average during a 1-hour period can exceed 30 percent.
iv. Before August 1, 2017, if applicable, determining and recording
each day the rate of combustion of liquid or solid fossil fuels (liters/
hour or kilograms/hour) and the hours of operation during which
liquid or solid fossil-fuels are combusted in the incinerator-waste
heat boiler; if applicable, maintaining the incremental rate of PM at
or below 43 g/GJ (0.10 lb/million Btu) of heat input attributable to
the solid or liquid fossil fuel.
Determining and recording each day the average coke burn-off rate
(thousands of kilograms per hour) using Equation 1 in § 63.1564
and the hours of operation for each catalyst regenerator; maintaining PM emission rate below 1.0 g/kg (1.0 lb PM/1,000 lb) of coke
burn-off; and conducting a performance test once every year.
Determining and recording each day the average coke burn-off rate
(thousands of kilograms per hour) using Equation 1 in § 63.1564
and the hours of operation for each catalyst regenerator; maintaining PM emission rate below 0.5 g/kg (0.5 lb/1,000 lb) of coke burnoff; and conducting a performance test once every year.
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75293
TABLE 6 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH METAL HAP EMISSION LIMITS FOR CATALYTIC
CRACKING UNITS—Continued
For each new and existing catalytic
cracking unit . . .
Subject to this emission limit for
your catalyst regenerator vent . . .
You shall demonstrate continuous compliance by . . .
4. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(i), electing to
meet the PM concentration limit.
If a PM CEMS is used, 0.040
grain per dry standard cubic feet
(gr/dscf) corrected to 0 percent
excess air.
If a PM CEMS is used, 0.020 gr/
dscf corrected to 0 percent excess air.
See item 1 of this table .................
Maintaining PM concentration below 0.040 gr/dscf corrected to 0 percent excess air.
5. Subject to NSPS for PM in 40
CFR 60.102a(b)(1)(ii), electing to
meet the PM concentration limit.
6. Option 1a: Elect NSPS subpart J
requirements for PM per coke
burn-off limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
7. Option 1b: Elect NSPS subpart
Ja requirements for PM per coke
burn-off limit and 30% opacity,
not subject to the NSPS for PM
in
40
CFR
60.102
or
60.102a(b)(1).
8. Option 1c: Elect NSPS subpart
Ja requirements for PM concentration limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
9. Option 2: PM per coke burn-off
limit, not subject to the NSPS for
PM in 40 CFR 60.102 or
60.102a(b)(1).
Maintaining PM concentration below 0.020 gr/dscf corrected to 0 percent excess air.
See item 1 of this table.
PM emissions must not exceed
1.0 g/kg (1.0 lb PM/1,000 lb) of
coke burn-off.
See item 2 of this table.
PM emissions must not exceed
0.040 gr/dscf corrected to 0 percent excess air.
See item 4 of this table.
PM emissions must not exceed
1.0 g/kg (1.0 lb PM/1,000 lb) of
coke burn-off.
Determining and recording each day the average coke burn-off rate
and the hours of operation and the hours of operation for each catalyst regenerator by Equation 1 of § 63.1564 (you can use process
data to determine the volumetric flow rate); maintaining PM emission rate below 1.0 g/kg (1.0 lb PM/1,000 lb) of coke burn-off; and
conducting a performance test before August 1, 2017 and thereafter following the testing frequency in § 63.1571(a)(5) as applicable to your unit.
Maintaining Ni emission rate below 13,000 mg/hr (0.029 lb/hr); and
conducting a performance test before August 1, 2017 and thereafter following the testing frequency in § 63.1571(a)(5) as applicable to your unit.
Determining and recording each day the average coke burn-off rate
(thousands of kilograms per hour) and the hours of operation for
each catalyst regenerator by Equation 1 of § 63.1564 (you can use
process data to determine the volumetric flow rate); and maintaining Ni emission rate below 1.0 mg/kg (0.001 lb/1,000 lb) of coke
burn-off in the catalyst regenerator; and conducting a performance
test before August 1, 2017 and thereafter following the testing frequency in § 63.1571(a)(5) as applicable to your unit.
10. Option 3: Ni lb/hr limit, not subject to the NSPS for PM in 40
CFR 60.102 or 60.102a(b)(1).
Ni emissions must not exceed
13,000 mg/hr (0.029 lb/hr).
11. Option 4: Ni per coke burn-off
limit, not subject to the NSPS for
PM in 40 CFR 60.102 or
60.102a(b)(1).
Ni emissions must not exceed 1.0
mg/kg (0.001 lb/1,000 lb) of
coke burn-off in the catalyst regenerator.
58. Table 7 to subpart UUU of part 63
is revised to read as follows:
■
As stated in § 63.1564(c)(1), you shall
meet each requirement in the following
table that applies to you.
TABLE 7 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR METAL HAP
EMISSIONS FROM CATALYTIC CRACKING UNITS
If you use . . .
1. Subject to NSPS for PM in 40
CFR 60.102 and not electing
§ 60.100(e).
tkelley on DSK3SPTVN1PROD with RULES2
For each new or existing catalytic
cracking unit . . .
Continuous
system.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
For this operating limit . . .
opacity
PO 00000
monitoring
Frm 00117
Fmt 4701
You shall demonstrate continuous
compliance by . . .
The 3-hour average opacity of
emissions from your catalyst regenerator vent must not exceed
20 percent.
Collecting the continuous opacity
monitoring data for each regenerator
vent
according
to
§ 63.1572 and maintain each 3hour rolling average opacity of
emissions no higher than 20
percent.
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75294
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 7 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR METAL HAP
EMISSIONS FROM CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit . . .
If you use . . .
For this operating limit . . .
You shall demonstrate continuous
compliance by . . .
2. Subject to NSPS for PM in 40
CFR 60.102a(b)(1); or 40 CFR
60.102 and elect § 60.100(e),
electing to meet the PM per
coke burn-off limit.
a. Continuous opacity monitoring
system, used for site-specific
opacity limit—Cyclone or electrostatic precipitator.
The average opacity must not exceed the opacity established
during the performance test.
b. Continuous parametric monitoring
systems—electrostatic
precipitator.
i. The average gas flow rate entering or exiting the control device must not exceed the operating limit established during
the performance test.
Collecting the hourly and 3-hr rolling average opacity monitoring
data according to § 63.1572;
maintaining the 3-hr rolling average opacity at or above the
site-specific limit established
during the performance test.
Collecting the hourly and daily average coke burn-off rate or average gas flow rate monitoring
data according to § 63.1572;
and maintaining the daily average coke burn-off rate or average gas flow rate at or below
the limit established during the
performance test.
Collecting the hourly and 3-hr rolling average total power and
secondary current monitoring
data according to § 63.1572;
and maintaining the 3-hr rolling
average total power and secondary current at or above the
limit established during the performance test.
Collecting the hourly and 3-hr rolling average gas flow rate and
scrubber liquid flow rate monitoring
data
according
to
§ 63.1572; determining and recording the 3-hr liquid-to-gas
ratio; and maintaining the 3-hr
rolling average liquid-to-gas
ratio at or above the limit established during the performance
test.
ii. The average total power and
secondary current to the control
device must not fall below the
operating limit established during the performance test.
c. Continuous parametric monitoring systems—wet scrubber.
i. The average liquid-to-gas ratio
must not fall below the operating limit established during
the performance test.
ii. Except for periods of startup,
shutdown and hot standby, the
average pressure drop across
the scrubber must not fall below
the operating limit established
during the performance test.
Increases in relative particulate ....
3. Subject to NSPS for PM in 40
CFR 60.102a(b)(1), electing to
meet the PM concentration limit.
4. Option 1a: Elect NSPS subpart
J requirements for PM per coke
burn-off limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
tkelley on DSK3SPTVN1PROD with RULES2
d. BLD—fabric filter ......................
PM CEMS .....................................
Not applicable ...............................
Continuous
system.
monitoring
The 3-hour average opacity of
emissions from your catalyst regenerator vent must not exceed
20 percent.
5. Option 1b: Elect NSPS subpart
Ja requirements for PM per coke
burn-off limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.102a(b)(1).
a. Continuous opacity monitoring
system.
The opacity of emissions from
your catalyst regenerator vent
must not exceed the site-specific opacity operating limit established during the performance test.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
opacity
PO 00000
Frm 00118
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
Collecting the hourly and 3-hr rolling average pressure drop
monitoring data according to
§ 63.1572; and except for periods of startup, shutdown and
hot standby, maintaining the 3hr rolling average pressure drop
at or above the limit established
during the performance test.
Collecting
and
maintaining
records of BLD system output;
determining the cause of the
alarm within 1 hour of the
alarm; and alleviating the cause
of the alarm within 3 hours by
corrective action.
Complying with Table 6 of this
subpart, item 4 or 5.
Collecting the 3-hr rolling average
continuous opacity monitoring
system data according to
§ 63.1572; and maintaining the
3-hr rolling average opacity no
higher than 20 percent.
Collecting the 3-hr rolling average
continuous opacity monitoring
system data according to
§ 63.1572; maintaining the 3-hr
rolling average opacity at or
below the site-specific limit.
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75295
TABLE 7 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR METAL HAP
EMISSIONS FROM CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit . . .
For this operating limit . . .
You shall demonstrate continuous
compliance by . . .
b. Continuous parametric monitoring
systems—electrostatic
precipitator.
c. Continuous parametric monitoring systems—wet scrubber.
d. BLD—fabric filter ......................
PM CEMS .....................................
See item 2.b of this table .............
See item 2.b of this table.
See item 2.c of this table .............
See item 2.c of this table.
See item 2.d of this table .............
Not applicable ...............................
See item 2.d of this table.
Complying with Table 6 of this
subpart, item 4.
a. Continuous opacity monitoring
system.
The opacity of emissions from
your catalyst regenerator vent
must not exceed the site-specific opacity operating limit established during the performance test.
b. Continuous parameter monitoring
systems—electrostatic
precipitator.
6. Option 1c: Elect NSPS subpart
Ja requirements for PM concentration limit, not subject to
the NSPS for PM in 40 CFR
60.102 or 60.102a(b)(1).
7. Option 2: PM per coke burn-off
limit, not subject to the NSPS for
PM in 40 CFR 60.102 or
60.102a(b)(1).
If you use . . .
i. The average coke burn-off rate
or average gas flow rate entering or exiting the control device
must not exceed the operating
limit established during the performance test.
Collecting the hourly and 3-hr rolling average continuous opacity
monitoring system data according to § 63.1572; and maintaining the 3-hr rolling average
opacity at or below the site-specific limit established during the
performance test. Alternatively,
before August 1, 2017, collecting the hourly average continuous opacity monitoring system
data
according
to
§ 63.1572; and maintaining the
hourly average opacity at or
below the site-specific limit.
Collecting the hourly and daily average coke burn-off rate or gas
flow rate monitoring data according to § 63.1572; and maintaining the daily coke burn-off
rate or average gas flow rate at
or below the limit established
during the performance test.
Collecting the hourly and 3-hr rolling average total power and
secondary current monitoring
data according to § 63.1572;
and maintaining the 3-hr rolling
average total power and secondary current at or above the
limit established during the performance test. Alternatively, before August 1, 2017, collecting
the hourly and daily average
voltage and secondary current
(or total power input) monitoring
data according to § 63.1572;
and maintaining the daily average voltage and secondary current (or total power input) at or
above the limit established during the performance test.
tkelley on DSK3SPTVN1PROD with RULES2
ii. The average total power (voltage and current) and secondary
current to the control device
must not fall below the operating limit established during
the performance test.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00119
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75296
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 7 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR METAL HAP
EMISSIONS FROM CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit . . .
If you use . . .
For this operating limit . . .
You shall demonstrate continuous
compliance by . . .
c. Continuous parameter monitoring systems—wet scrubber.
i. The average liquid-to-gas ratio
must not fall below the operating limit established during
the performance test.
Collecting the hourly and 3-hr rolling average gas flow rate and
scrubber liquid flow rate monitoring
data
according
to
§ 63.1572; determining and recording the 3-hr liquid-to-gas
ratio; and maintaining the 3-hr
rolling average liquid-to-gas
ratio at or above the limit established during the performance
test. Alternatively, before August 1, 2017, collecting the
hourly average gas flow rate
and water (or scrubbing liquid)
flow rate monitoring data according to § 63.1572 1; determining and recording the hourly
average liquid-to-gas ratio; determining and recording the
daily average liquid-to-gas ratio;
and maintaining the daily average liquid-to-gas ratio above
the limit established during the
performance test.
Collecting the hourly and 3-hr rolling average pressure drop
monitoring data according to
§ 63.1572; and except for periods of startup, shutdown and
hot standby, maintaining the 3hr rolling average pressure drop
at or above the limit established
during the performance test. Alternatively, before August 1,
2017, collecting the hourly and
daily average pressure drop
monitoring data according to
§ 63.1572; and maintaining the
daily average pressure drop
above the limit established during the performance test.
See item 2.d of this table.
(1) Collecting the hourly average
continuous opacity monitoring
system data according to
§ 63.1572; determining and recording equilibrium catalyst Ni
concentration at least once a
week 2; collecting the hourly average gas flow rate monitoring
data according to § 63.1572 1;
and determining and recording
the hourly average Ni operating
value using Equation 11 of
§ 63.1564.
ii. Except for periods of startup,
shutdown and hot standby, the
average pressure drop across
the scrubber must not fall below
the operating limit established
during the performance test.
tkelley on DSK3SPTVN1PROD with RULES2
8. Option 3: Ni lb/hr limit not subject to the NSPS for PM in 40
CFR 60.102.
VerDate Sep<11>2014
23:11 Nov 30, 2015
d. BLD—fabric filter ......................
a. Continuous opacity monitoring
system.
Jkt 238001
PO 00000
Frm 00120
Fmt 4701
See item 2.d of this table .............
i. The daily average Ni operating
value must not exceed the sitespecific Ni operating limit established during the performance
test.
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75297
TABLE 7 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR METAL HAP
EMISSIONS FROM CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit . . .
If you use . . .
b. Continuous parameter monitoring
systems—electrostatic
precipitator.
c. Continuous parameter monitoring systems—wet scrubber.
tkelley on DSK3SPTVN1PROD with RULES2
d. BLD—fabric filter ......................
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
You shall demonstrate continuous
compliance by . . .
For this operating limit . . .
Frm 00121
Fmt 4701
i. The average gas flow rate entering or exiting the control device must not exceed the operating limit established during
the performance test.
ii. The average total power (voltage and current) and secondary
current must not fall below the
level established in the performance test.
iii. The monthly rolling average of
the equilibrium catalyst Ni concentration must not exceed the
level established during the performance test.
i. The average liquid-to-gas ratio
must not fall below the operating limit established during
the performance test..
ii. Except for periods of startup,
shutdown and hot standby, the
average pressure drop must not
fall below the operating limit established in the performance
test.
iii. The monthly rolling average
equilibrium catalyst Ni concentration must not exceed the
level established during the performance test.
i. Increases in relative particulate
Sfmt 4700
E:\FR\FM\01DER2.SGM
(2) Determining and recording the
3-hour rolling average Ni operating value and maintaining the
3-hour rolling average Ni operating value below the site-specific Ni operating limit established during the performance
test. Alternatively, before August 1, 2017, determining and
recording the daily average Ni
operating value and maintaining
the daily average Ni operating
value below the site-specific Ni
operating limit established during the performance test.
See item 7.b.i of this table.
See item 7.b.ii of this table.
Determining and recording the
equilibrium catalyst Ni concentration at least once a
week 2; determining and recording the monthly rolling average
of the equilibrium catalyst Ni
concentration once each week
using the weekly or most recent
value; and maintaining the
monthly rolling average below
the limit established in the performance test.
See item 7.c.i of this table.
See item 7.c.ii of this table.
Determining and recording the
equilibrium catalyst Ni concentration at least once a
week 2; determining and recording the monthly rolling average
of equilibrium catalyst Ni concentration once each week
using the weekly or most recent
value; and maintaining the
monthly rolling average below
the limit established in the performance test.
See item 7.d of this table.
01DER2
75298
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 7 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR METAL HAP
EMISSIONS FROM CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit . . .
You shall demonstrate continuous
compliance by . . .
ii. The monthly rolling average of
the equilibrium catalyst Ni concentration must not exceed the
level established during the performance test.
9. Option 4: Ni per coke burn-off
limit not subject to the NSPS for
PM in 40 CFR 60.102.
For this operating limit . . .
If you use . . .
Determining and recording the
equilibrium catalyst Ni concentration at least once a
week 2; determining and recording the monthly rolling average
of the equilibrium catalyst Ni
concentration once each week
using the weekly or most recent
value; and maintaining the
monthly rolling average below
the limit established in the performance test.
(1) Collecting the hourly average
continuous opacity monitoring
system data according to
§ 63.1572; collecting the hourly
average coke burn rate and
hourly average gas flow rate
monitoring data according to
§ 63.15721; determining and recording equilibrium catalyst Ni
concentration at least once a
week 2; and determining and recording the hourly average Ni
operating value using Equation
12 of § 63.1564.
(2) Determining and recording the
3-hour rolling average Ni operating value and maintaining the
3-hour rolling average Ni operating value below the site-specific Ni operating limit established during the performance
test Alternatively, before August
1, 2017, determining and recording the daily average Ni operating value and maintaining
the daily average Ni operating
value below the site-specific Ni
operating limit established during the performance test.
See item 7.b.i of this table.
a. Continuous opacity monitoring
system.
i. The daily average Ni operating
value must not exceed the sitespecific Ni operating limit established during the performance
test.
b. Continuous parameter monitoring
systems—electrostatic
precipitator.
i. The average gas flow rate to
the control device must not exceed the level established in
the performance test.
ii. The average voltage and secondary current (or total power
input) must not fall below the
level established in the performance test.
iii. The monthly rolling average
equilibrium catalyst Ni concentration must not exceed the
level established during the performance test.
i. The average liquid-to-gas ratio
must not fall below the operating limit established during
the performance test.
ii. Except for periods of startup,
shutdown and hot standby, the
daily average pressure drop
must not fall below the operating limit established in the
performance test.
tkelley on DSK3SPTVN1PROD with RULES2
c. Continuous parameter monitoring systems—wet scrubber.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00122
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
See item 7.b.ii of this table.
See item 8.b.iii of this table.
See item 7.c.i of this table.
See item 7.c.ii of this table.
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75299
TABLE 7 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR METAL HAP
EMISSIONS FROM CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic
cracking unit . . .
For this operating limit . . .
You shall demonstrate continuous
compliance by . . .
iii. The monthly rolling average
equilibrium catalyst Ni concentration must not exceed the
level established during the performance test.
i. See item 2.d of this table ..........
ii. The monthly rolling average of
the equilibrium catalyst Ni concentration must not exceed the
level established during the performance test.
See item 8.c.iii of this table.
d. BLD—fabric filter ......................
10. During periods of startup, shutdown, or hot standby.
If you use . . .
Any control device, if elected .......
The inlet velocity limit to the primary internal cyclones of the
catalytic cracking unit catalyst
regenerator
in
§ 63.1564(a)(5)(ii).
See item 2.d of this table.
Determining and recording the
equilibrium catalyst Ni concentration at least once a
week 2; determining and recording the monthly rolling average
of the equilibrium catalyst Ni
concentration once each week
using the weekly or most recent
value; and maintaining the
monthly rolling average below
the limit established in the performance test.
Meeting the requirements in
§ 63.1564(c)(5).
1 If applicable, you can use the alternative in § 63.1573(a)(1) for gas flow rate instead of a continuous parameter monitoring system if you used
the alternative method in the initial performance test.
2 The equilibrium catalyst Ni concentration must be measured by the procedure, Determination of Metal Concentration on Catalyst Particles (Instrumental Analyzer Procedure) in appendix A to this subpart; or by EPA Method 6010B, Inductively Coupled Plasma-Atomic Emission Spectrometry, EPA Method 6020, Inductively Coupled Plasma-Mass Spectrometry, EPA Method 7520, Nickel Atomic Absorption, Direct Aspiration, or
EPA Method 7521, Nickel Atomic Absorption, Direct Aspiration; or by an alternative to EPA Method 6010B, 6020, 7520, or 7521 satisfactory to
the Administrator. The EPA Methods 6010B, 6020, 7520, and 7521 are included in ‘‘Test Methods for Evaluating Solid Waste, Physical/Chemical
Methods,’’ EPA Publication SW–846, Revision 5 (April 1998). The SW–846 and Updates (document number 955–001–00000–1) are available for
purchase from the Superintendent of Documents, U.S. Government Publishing Office, Washington, DC 20402, (202) 512–1800; and from the National Technical Information Services (NTIS), 5285 Port Royal Road, Springfield, VA 22161, (703) 487–4650. Copies may be inspected at the
EPA Docket Center, William Jefferson Clinton (WJC) West Building (Air Docket), Room 3334, 1301 Constitution Ave. NW., Washington, DC; or
at the Office of the Federal Register, 800 North Capitol Street NW., Suite 700, Washington, DC. These methods are also available at https://www.
epa.gov/epaoswer/hazwaste/test/main.htm.
59. Table 8 to subpart UUU of part 63
is revised to read as follows:
■
As stated in § 63.1565(a)(1), you shall
meet each emission limitation in the
following table that applies to you.
TABLE 8 TO SUBPART UUU OF PART 63—ORGANIC HAP EMISSION LIMITS FOR CATALYTIC CRACKING UNITS
For each new and existing catalytic cracking unit . . .
You shall meet the following emission limit for each catalyst
regenerator vent . . .
1. Subject to the NSPS for carbon monoxide (CO) in 40 CFR 60.103 or
60.102a(b)(4).
CO emissions from the catalyst regenerator vent or CO boiler serving
the catalytic cracking unit must not exceed 500 parts per million volume (ppmv) (dry basis).
a. CO emissions from the catalyst regenerator vent or CO boiler serving the catalytic cracking unit must not exceed 500 ppmv (dry basis).
b. If you use a flare to meet the CO limit, then on and after January
30, 2019, the flare must meet the requirements of § 63.670. Prior to
January 30, 2019, the flare must meet the requirements for control
devices in § 63.11(b) and visible emissions must not exceed a total
of 5 minutes during any 2 consecutive hours, or the flare must meet
the requirements of § 63.670.
2. Not subject to the NSPS for CO in 40 CFR 60.103 or 60.102a(b)(4)
60. Table 9 to subpart UUU of part 63
is revised to read as follows:
tkelley on DSK3SPTVN1PROD with RULES2
■
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
As stated in § 63.1565(a)(2), you shall
meet each operating limit in the
following table that applies to you.
PO 00000
Frm 00123
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75300
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 9 TO SUBPART UUU OF PART 63—OPERATING LIMITS FOR ORGANIC HAP EMISSIONS FROM CATALYTIC CRACKING
UNITS
For each new or existing catalytic
cracking unit . . .
For this type of continuous
monitoring system . . .
For this type of control
device . . .
You shall meet this operating
limit . . .
1. Subject to the NSPS for carbon
monoxide (CO) in 40 CFR
60.103 or 60.102a(b)(4).
2. Not subject to the NSPS for CO
in
40
CFR
60.103
or
60.102a(b)(4).
Continuous emission monitoring
system.
Not applicable ...............................
Not applicable.
a.
moni-
Not applicable ...............................
Not applicable.
b. Continuous parameter monitoring systems.
i. Thermal incinerator ....................
Maintain the daily average combustion
zone
temperature
above the limit established during the performance test; and
maintain the daily average oxygen concentration in the vent
stream (percent, dry basis)
above the limit established during the performance test.
Maintain the daily average combustion
zone
temperature
above the limit established in
the performance test.
Continuous emission
toring system.
ii. Boiler or process heater with a
design heat input capacity
under 44 MW or a boiler or
process heater in which all vent
streams are not introduced into
the flame zone.
iii. Flare .........................................
3. During periods of startup, shutdown or hot standby.
Any ................................................
61. Table 10 to subpart UUU of part
63 is revised to read as follows:
Any ................................................
On and after January 30, 2019,
the flare must meet the requirements of § 63.670. Prior to January 30, 2019, the flare pilot
light must be present at all
times and the flare must be operating at all times that emissions may be vented to it, or
the flare must meet the requirements of § 63.670.
Meet
the
requirements
in
§ 63.1565(a)(5).
As stated in § 63.1565(b)(1), you shall
meet each requirement in the following
table that applies to you.
■
TABLE 10 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR ORGANIC HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS
And you use this type of control device for
your vent . . .
You shall install, operate, and maintain this
type of continuous monitoring system . . .
1. Subject to the NSPS for carbon monoxide
(CO) in 40 CFR 60.103 or 60.102a(b)(4).
Not applicable ...................................................
2. Not subject to the NSPS for CO in 40 CFR
60.103 or 60.102a(b)(4).
tkelley on DSK3SPTVN1PROD with RULES2
For each new or existing catalytic cracking
unit . . .
a. Thermal incinerator ......................................
Continuous emission monitoring system to
measure and record the concentration by
volume (dry basis) of CO emissions from
each catalyst regenerator vent.
Continuous emission monitoring system to
measure and record the concentration by
volume (dry basis) of CO emissions from
each catalyst regenerator vent; or continuous parameter monitoring systems to
measure and record the combustion zone
temperature and oxygen content (percent,
dry basis) in the incinerator vent stream.
Continuous emission monitoring system to
measure and record the concentration by
volume (dry basis) of CO emissions from
each catalyst regenerator vent; or continuous parameter monitoring systems to
measure and record the combustion zone
temperature.
b. Process heater or boiler with a design heat
input capacity under 44 MW or process
heater or boiler in which all vent streams
are not introduced into the flame zone.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00124
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75301
TABLE 10 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR ORGANIC HAP EMISSIONS FROM
CATALYTIC CRACKING UNITS—Continued
For each new or existing catalytic cracking
unit . . .
And you use this type of control device for
your vent . . .
You shall install, operate, and maintain this
type of continuous monitoring system . . .
c. Flare .............................................................
On and after January 30, 2019, the monitoring
systems required in §§ 63.670 and 63.671.
Prior to January 30, 2019, monitoring device such as a thermocouple, an ultraviolet
beam sensor, or infrared sensor to continuously detect the presence of a pilot flame,
or the monitoring systems required in
§§ 63.670 and 63.671.
Continuous emission monitoring system to
measure and record the concentration by
volume (dry basis) of CO emissions from
each catalyst regenerator vent.
Continuous parameter monitoring system to
measure and record the concentration by
volume (dry basis) of oxygen from each catalyst regenerator vent.
d. No control device .........................................
3. During periods of startup, shutdown or hot
standby electing to comply with the operating limit in § 63.1565(a)(5)(ii).
Any ...................................................................
62. Table 11 to subpart UUU of part
63 is amended by revising the entry for
item 3 to read as follows:
*
*
*
*
*
■
TABLE 11 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR ORGANIC HAP EMISSIONS
FROM CATALYTIC CRACKING UNITS NOT SUBJECT TO NEW SOURCE PERFORMANCE STANDARD (NSPS) FOR CARBON
MONOXIDE (CO)
According to these
requirements . . .
You must . . .
Using . . .
*
3. Each catalytic cracking unit catalyst regenerator vent if you use
continuous parameter monitoring systems.
*
*
a. Measure the CO concentration
(dry basis) of emissions exiting
the control device.
*
*
Method 10, 10A, or 10B in appendix A–4 to part 60 of this chapter, as applicable.
b. Establish each operating limit in
Table 9 of this subpart that applies to you.
c. Thermal incinerator combustion
zone temperature.
Data from the continuous parameter monitoring systems.
d. Thermal incinerator: oxygen,
content (percent, dry basis) in
the incinerator vent stream.
tkelley on DSK3SPTVN1PROD with RULES2
For . . .
Data from the continuous parameter monitoring systems.
e. If you use a process heater or
boiler with a design heat input
capacity under 44 MW or process heater or boiler in which all
vent streams are not introduced
into the flame zone, establish
operating limit for combustion
zone temperature.
Data from the continuous parameter monitoring systems.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00125
Fmt 4701
Data from the continuous parameter monitoring systems.
Sfmt 4700
E:\FR\FM\01DER2.SGM
*
Collect temperature monitoring
data every 15 minutes during
the entire period of the CO initial performance test; and determine and record the minimum
hourly
average
combustion
zone temperature from all the
readings.
Collect oxygen concentration (percent, dry basis) monitoring data
every 15 minutes during the entire period of the CO initial performance test; and determine
and record the minimum hourly
average percent excess oxygen
concentration from all the readings.
Collect the temperature monitoring
data every 15 minutes during
the entire period of the CO initial performance test; and determine and record the minimum
hourly
average
combustion
zone temperature from all the
readings.
01DER2
75302
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 11 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR ORGANIC HAP EMISSIONS
FROM CATALYTIC CRACKING UNITS NOT SUBJECT TO NEW SOURCE PERFORMANCE STANDARD (NSPS) FOR CARBON
MONOXIDE (CO)—Continued
You must . . .
Using . . .
According to these
requirements . . .
f. If you use a flare, conduct visible emission observations.
Method 22 (40 CFR part 60, appendix A–7).
g. If you use a flare, determine
that the flare meets the requirements for net heating value of
the gas being combusted and
exit velocity.
For . . .
40 CFR 63.11(b)(6) through (8) ....
On and after January 30, 2019,
meet the requirements of
§ 63.670. Prior to January 30,
2019, maintain a 2-hour observation period; and record the
presence of a flame at the pilot
light over the full period of the
test or meet the requirements of
§ 63.670.
On and after January 30, 2019,
the flare must meet the requirements of § 63.670. Prior to January 30, 2019, the flare must
meet the control device requirements in § 63.11(b) or the requirements of § 63.670.
63. Table 12 to subpart UUU of part
63 is revised to read as follows:
■
As stated in § 63.1565(b)(4), you shall
meet each requirement in the following
table that applies to you.
TABLE 12 TO SUBPART UUU OF PART 63—INITIAL COMPLIANCE WITH ORGANIC HAP EMISSION LIMITS FOR CATALYTIC
CRACKING UNITS
For each new and existing catalytic
cracking unit . . .
For the following emission
limit . . .
You have demonstrated initial compliance if . . .
1. Subject to the NSPS for carbon
monoxide (CO) in 40 CFR
60.103,
60.100(e),
or
60.102a(b)(4).
CO emissions from your catalyst
regenerator vent or CO boiler
serving the catalytic cracking
unit must not exceed 500 ppmv
(dry basis).
2. Not subject to the NSPS for CO
in 40 CFR 60.103 60.102a(b)(4).
a. CO emissions from your catalyst regenerator vent or CO boiler serving the catalytic cracking
unit must not exceed 500 ppmv
(dry basis).
You have already conducted a performance test to demonstrate initial
compliance with the NSPS and the measured CO emissions are
less than or equal to 500 ppm (dry basis). As part of the Notification of Compliance Status, you must certify that your vent meets
the CO limit. You are not required to conduct another performance
test to demonstrate initial compliance. You have already conducted
a performance evaluation to demonstrate initial compliance with the
applicable performance specification. As part of your Notification of
Compliance Status, you must certify that your continuous emission
monitoring system meets the applicable requirements in § 63.1572.
You are not required to conduct another performance evaluation to
demonstrate initial compliance.
i. If you use a continuous parameter monitoring system, the average
CO emissions measured by Method 10 over the period of the initial
performance test are less than or equal to 500 ppmv (dry basis).
b. If you use a flare, visible emissions must not exceed a total of
5 minutes during any 2 operating hours.
64. Table 13 to subpart UUU of part
63 is revised to read as follows:
tkelley on DSK3SPTVN1PROD with RULES2
■
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
ii. If you use a continuous emission monitoring system, the hourly average CO emissions over the 24-hour period for the initial performance test are not more than 500 ppmv (dry basis); and your performance evaluation shows your continuous emission monitoring
system meets the applicable requirements in § 63.1572.
On and after January 30, 2019, the flare meets the requirements of
§ 63.670. Prior to January 30, 2019, visible emissions, measured
by Method 22 during the 2-hour observation period during the initial
performance test, are no higher than 5 minutes, or the flare meets
the requirements of § 63.670.
As stated in § 63.1565(c)(1), you shall
meet each requirement in the following
table that applies to you.
PO 00000
Frm 00126
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75303
TABLE 13 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH ORGANIC HAP EMISSION LIMITS FOR
CATALYTIC CRACKING UNITS
For each new and existing
catalytic cracking unit . . .
Subject to this emission limit for
your catalyst regenerator
vent . . .
1. Subject to the NSPS for carbon
monoxide (CO) in 40 CFR
60.103,
60.100(e),
or
60.102a(b)(4).
2. Not subject to the NSPS for CO
in
40
CFR
60.103
or
60.102a(b)(4).
If you must . . .
You shall demonstrate continuous
compliance by . . .
CO emissions from your catalyst
regenerator vent or CO boiler
serving the catalytic cracking
unit must not exceed 500 ppmv
(dry basis).
Continuous emission monitoring
system.
a. CO emissions from your catalyst regenerator vent or CO
boiler serving the catalytic
cracking unit must not exceed
500 ppmv (dry basis).
b. CO emissions from your catalyst regenerator vent or CO
boiler serving the catalytic
cracking unit must not exceed
500 ppmv (dry basis).
c. Visible emissions from a flare
must not exceed a total of 5
minutes during any 2-hour period.
Continuous emission monitoring
system.
Collecting the hourly average CO
monitoring data according to
§ 63.1572; and maintaining the
hourly average CO concentration at or below 500 ppmv (dry
basis).
Same as item 1.
65. Table 14 to subpart UUU of part
63 is revised to read as follows:
■
Continuous parameter monitoring
system.
Maintaining the hourly average
CO concentration below 500
ppmv (dry basis).
Control device-flare ......................
On and after January 30, 2019,
meeting the requirements of
§ 63.670. Prior to January 30,
2019, maintaining visible emissions below a total of 5 minutes
during any 2-hour operating period, or meeting the requirements of § 63.670.
As stated in § 63.1565(c)(1), you shall
meet each requirement in the following
table that applies to you.
TABLE 14 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR ORGANIC HAP
EMISSIONS FROM CATALYTIC CRACKING UNITS
For each new existing catalytic
cracking unit . . .
For this operating limit . . .
If you use . . .
1. Subject to NSPS for carbon Continuous emission monitoring
monoxide (CO) in 40 CFR
system.
60.103, 60.100(e), 60.102a(b)(4).
2. Not subject to the NSPS for CO a. Continuous emission moniin
40
CFR
60.103
or
toring system.
60.102a(b)(4).
b. Continuous parameter monitoring systems—thermal incinerator.
You shall demonstrate continuous
compliance by . . .
Not applicable ...............................
Complying with Table 13 of this
subpart, item 1.
Not applicable ...............................
Complying with Table 13 of this
subpart, item 2.a.
i. The daily average combustion
zone temperature must not fall
below the level established during the performance test.
Collecting the hourly and daily average temperature monitoring
data according to § 63.1572;
and maintaining the daily average combustion zone temperature above the limit established
during the performance test.
Collecting the hourly and daily average oxygen concentration
monitoring data according to
§ 63.1572; and maintaining the
daily average oxygen concentration above the limit established during the performance
test.
Collecting the average hourly and
daily temperature monitoring
data according to § 63.1572;
and maintaining the daily average combustion zone temperature above the limit established
during the performance test.
tkelley on DSK3SPTVN1PROD with RULES2
ii. The daily average oxygen concentration in the vent stream
(percent, dry basis) must not
fall below the level established
during the performance test.
c. Continuous parameter monitoring systems—boiler or process heater with a design heat
input capacity under 44 MW or
boiler or process heater in
which all vent streams are not
introduced into the flame zone.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00127
Fmt 4701
The daily combustion zone temperature must not fall below the
level established in the performance test.
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75304
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 14 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR ORGANIC HAP
EMISSIONS FROM CATALYTIC CRACKING UNITS—Continued
For each new existing catalytic
cracking unit . . .
If you use . . .
You shall demonstrate continuous
compliance by . . .
d. Continuous parameter monitoring system—flare.
3. During periods of startup, shutdown or hot standby electing to
comply with the operating limit in
§ 63.1565(a)(5)(ii).
For this operating limit . . .
The flare pilot light must be
present at all times and the
flare must be operating at all
times that emissions may be
vented to it.
Any control device ........................
The oxygen concentration limit in
§ 63.1565(a)(5)(ii).
On and after January 30, 2019,
meeting the requirements of
§ 63.670. Prior to January 30,
2019, collecting the flare monitoring
data
according
to
§ 63.1572 and recording for
each 1-hour period whether the
monitor was continuously operating and the pilot light was
continuously present during
each 1-hour period, or meeting
the requirements of § 63.670.
Collecting the hourly average oxygen concentration monitoring
data according to § 63.1572
and maintaining the hourly average oxygen concentration at
or above 1 volume percent (dry
basis).
66. Table 15 to subpart UUU of part
63 is amended by revising the entry for
item 1 to read as follows:
*
*
*
*
*
■
TABLE 15 TO SUBPART UUU OF PART 63—ORGANIC HAP EMISSION LIMITS FOR CATALYTIC REFORMING UNITS
For each applicable process vent for a
new or existing catalytic reforming
unit . . .
You shall meet this emission limit during initial catalyst depressuring and catalyst purging
operations . . .
1. Option 1 ................................................
On and after January 30, 2019, vent emissions to a flare that meets the requirements of § 63.670.
Prior to January 30, 2019, vent emissions to a flare that meets the requirements for control devices in § 63.11(b) and visible emissions from a flare must not exceed a total of 5 minutes during
any 2-hour operating period, or vent emissions to a flare that meets the requirements of § 63.670.
*
*
*
*
*
*
*
67. Table 16 to subpart UUU of part
63 is amended by revising the entry for
item 1 to read as follows:
*
*
*
*
*
■
TABLE 16 TO SUBPART UUU OF PART 63—OPERATING LIMITS FOR ORGANIC HAP EMISSIONS FROM CATALYTIC
REFORMING UNITS
For each new or existing catalytic
reforming unit . . .
For this type of control device . . .
You shall meet this operating limit during initial catalyst depressuring
and purging operations. . .
1. Option 1: Vent to flare ...............
Flare ...............................................
On and after January 30, 2019, the flare must meet the requirements
of § 63.670. Prior to January 30, 2019, the flare pilot light must be
present at all times and the flare must be operating at all times that
emissions may be vented to it, or the flare must meet the requirements of § 63.670.
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
*
68. Table 17 to subpart UUU of part
63 is amended by revising the entry for
item 1 to read as follows:
*
*
*
*
*
■
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00128
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
*
75305
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 17 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR ORGANIC HAP EMISSIONS FROM
CATALYTIC REFORMING UNITS
For each applicable process vent
for a new or existing catalytic
reforming unit . . .
If you use this type of control
device . . .
You shall install and operate this type of continuous monitoring
system . . .
1. Option 1: Vent to a flare ............
Flare ...............................................
On and after January 30, 2019, the monitoring systems required in
§§ 63.670 and 63.671. Prior to January 30, 2019, monitoring device
such as a thermocouple, an ultraviolet beam sensor, or infrared
sensor to continuously detect the presence of a pilot flame, or the
monitoring systems required in §§ 63.670 and 63.671.
*
*
*
69. Table 18 to subpart UUU of part
63 is amended by revising the column
*
*
*
*
headings and the entry for item 1 to read
as follows:
*
*
*
*
*
■
TABLE 18 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR ORGANIC HAP EMISSIONS
FROM CATALYTIC REFORMING UNITS
For each new or existing catalytic
reforming unit . . .
You must . . .
Using . . .
According to these
requirements . . .
1. Option 1: Vent to a flare ...........
a. Conduct visible emission observations.
Method 22 (40 CFR part 60, appendix A–7).
b. Determine that the flare meets
the requirements for net heating
value of the gas being combusted and exit velocity.
40 CFR 63.11(b)(6) through (8) ....
On and after January 30, 2019,
the flare must meet the requirements of § 63.670. Prior to January 30, 2019, 2-hour observation period. Record the presence of a flame at the pilot light
over the full period of the test,
or the requirements of § 63.670.
On and after January 30, 2019,
the flare must meet the requirements of § 63.670. Prior to January 30, 2019, the flare must
meet the control device requirements in § 63.11(b) or the requirements of § 63.670.
*
*
*
*
*
*
*
70. Table 19 to subpart UUU of part
63 is amended by revising the entry for
item 1 to read as follows:
*
*
*
*
*
■
TABLE 19 TO SUBPART UUU OF PART 63—INITIAL COMPLIANCE WITH ORGANIC HAP EMISSION LIMITS FOR CATALYTIC
REFORMING UNITS
For each applicable process vent for a new or
existing catalytic reforming unit . . .
For the following emission limit . . .
You have demonstrated initial compliance
if . . .
Option 1 ............................................................
Visible emissions from a flare must not exceed
a total of 5 minutes during any 2 consecutive hours.
On and after January 30, 2019, the flare
meets the requirements of § 63.670. Prior to
January 30, 2019, visible emissions, measured using Method 22 over the 2-hour observation period of the performance test, do
not exceed a total of 5 minutes, or the flare
meets the requirements of § 63.670.
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
*
71. Table 20 to subpart UUU of part
63 is amended by revising the entry for
item 1 to read as follows:
*
*
*
*
*
■
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00129
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
*
75306
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 20 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH ORGANIC HAP EMISSION LIMITS FOR
CATALYTIC REFORMING UNITS
You shall demonstrate continuous compliance
during initial catalyst depressuring and catalyst
purging operations by . . .
For each applicable process vent for a new or
existing catalytic reforming unit . . .
For this emission limit . . .
1. Option 1 ........................................................
Vent emissions from your process vent to a
flare.
*
*
*
*
On and after January 30, 2019, meeting the
requirements of § 63.670. Prior to January
30, 2019, maintaining visible emissions from
a flare below a total of 5 minutes during any
2 consecutive hours, or meeting the requirements of § 63.670.
*
*
*
72. Table 21 to subpart UUU of part
63 is amended by revising the entry for
item 1 to read as follows:
*
*
*
*
*
■
TABLE 21 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR ORGANIC HAP
EMISSIONS FROM CATALYTIC REFORMING UNITS
You shall demonstrate continuous
compliance during initial catalyst
depressuring and purging
operations by . . .
For each applicable process vent
for a new or existing catalytic
reforming unit . . .
If you use . . .
For this operating limit . . .
1. Option 1 ....................................
Flare ..............................................
The flare pilot light must be
present at all times and the
flare must be operating at all
times that emissions may be
vented to it.
*
*
*
*
On and after January 30, 2019,
meeting the requirements of
§ 63.670. Prior to January 30,
2019, collecting flare monitoring
data according to § 63.1572 and
recording for each 1-hour period
whether the monitor was continuously operating and the pilot
light was continuously present
during each 1-hour period, or
meeting the requirements of
§ 63.670.
*
*
*
73. Table 22 to subpart UUU of part
63 is amended by revising the entries for
items 2 and 3 to read as follows:
*
*
*
*
*
■
TABLE 22 TO SUBPART UUU OF PART 63—INORGANIC HAP EMISSION LIMITS FOR CATALYTIC REFORMING UNITS
You shall meet this emission limit for each applicable catalytic
reforming unit process vent during coke burn-off and catalyst
rejuvenation . . .
For . . .
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
*
*
2. Each existing cyclic or continuous catalytic reforming unit .................. Reduce uncontrolled emissions of HCl by 97 percent by weight or to a
concentration of 10 ppmv (dry basis), corrected to 3 percent oxygen.
3. Each new semi-regenerative, cyclic, or continuous catalytic reform- Reduce uncontrolled emissions of HCl by 97 percent by weight or to a
ing unit.
concentration of 10 ppmv (dry basis), corrected to 3 percent oxygen.
74. Table 24 to subpart UUU of part
63 is amended by revising the entries for
■
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
items 2 through 4 and footnote 2 to read
as follows:
*
*
*
*
*
PO 00000
Frm 00130
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75307
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 24 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR INORGANIC HAP EMISSIONS FROM
CATALYTIC REFORMING UNITS
You shall install and operate this type of continuous monitoring
system . . .
If you use this type of control device for your vent . . .
*
*
*
*
*
*
*
2. Internal scrubbing system or no control device (e.g., hot regen sys- Colormetric tube sampling system to measure the HCl concentration in
tem) to meet HCl outlet concentration limit.
the catalyst regenerator exhaust gas during coke burn-off and catalyst rejuvenation. The colormetric tube sampling system must meet
the requirements in Table 41 of this subpart.
3. Internal scrubbing system to meet HCl percent reduction standard ... Continuous parameter monitoring system to measure and record the
gas flow rate entering or exiting the internal scrubbing system during
coke burn-off and catalyst rejuvenation; and continuous parameter
monitoring system to measure and record the total water (or scrubbing liquid) flow rate entering the internal scrubbing system during
coke burn-off and catalyst rejuvenation; and continuous parameter
monitoring system to measure and record the pH or alkalinity of the
water (or scrubbing liquid) exiting the internal scrubbing system during coke burn-off and catalyst rejuvenation.2
4. Fixed-bed gas-solid adsorption system ................................................ Continuous parameter monitoring system to measure and record the
temperature of the gas entering or exiting the adsorption system during coke burn-off and catalyst rejuvenation; and colormetric tube
sampling system to measure the gaseous HCl concentration in the
adsorption system exhaust and at a point within the absorbent bed
not to exceed 90 percent of the total length of the absorbent bed
during coke burn-off and catalyst rejuvenation. The colormetric tube
sampling system must meet the requirements in Table 41 of this
subpart.
*
*
*
*
*
*
*
*
*
*
*
*
*
*
2 If applicable, you can use the alternative in § 63.1573(c)(1) instead of a continuous parameter monitoring system for pH of the water (or
scrubbing liquid) or the alternative in § 63.1573(c)(2) instead of a continuous parameter monitoring system for alkalinity of the water (or scrubbing
liquid).
*
*
*
*
*
75. Table 25 to subpart UUU of part
63 is amended by revising the entries for
■
items 2.a and 4.a and footnote 1 to read
as follows:
*
*
*
*
*
TABLE 25 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR INORGANIC HAP EMISSIONS
FROM CATALYTIC REFORMING UNITS
For each new and existing
catalytic reforming unit
using . . .
You shall . . .
*
*
2. Wet scrubber ............................
*
*
*
a. Establish operating limit for pH i. Data from continuous parameter
level or alkalinity.
monitoring systems.
According to these
requirements . . .
Using . . .
tkelley on DSK3SPTVN1PROD with RULES2
ii. Alternative pH procedure in
§ 63.1573(b)(1).
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00131
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
*
*
Measure and record the pH or alkalinity of the water (or scrubbing liquid) exiting scrubber
every 15 minutes during the entire period of the performance
test. Determine and record the
minimum hourly average pH or
alkalinity level from the recorded values.
Measure and record the pH of the
water (or scrubbing liquid)
exiting the scrubber during coke
burn-off and catalyst rejuvenation using pH strips at least
three times during each test
run. Determine and record the
average pH level for each test
run. Determine and record the
minimum test run average pH
level.
01DER2
75308
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 25 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR INORGANIC HAP EMISSIONS
FROM CATALYTIC REFORMING UNITS—Continued
For each new and existing
catalytic reforming unit
using . . .
According to these
requirements . . .
iii. Alternative alkalinity method in
§ 63.1573(c)(2).
4.
Using . . .
Measure and record the alkalinity
of the water (or scrubbing liquid) exiting the scrubber during
coke burn-off and catalyst rejuvenation using discrete titration
at least three times during each
test run. Determine and record
the average alkalinity level for
each test run. Determine and
record the minimum test run average alkalinity level.
*
*
*
a. Establish operating limit for pH i. Data from continuous parameter
level or alkalinity.
monitoring system.
*
*
Measure and record the pH alkalinity of the water (or scrubbing
liquid) exiting the internal scrubbing system every 15 minutes
during the entire period of the
performance test. Determine
and record the minimum hourly
average pH or alkalinity level
from the recorded values.
Measure and in record pH of the
water (or scrubbing liquid)
exiting the internal scrubbing
system during coke burn-off and
catalyst rejuvenation using pH
strips at least three times during
each test run. Determine and
record the average pH level for
each test run. Determine and
record the minimum test run average pH level.
Measure and record the alkalinity
water (or scrubbing liquid)
exiting the internal scrubbing
system during coke burn-off and
catalyst rejuvenation using discrete titration at least three
times during each test run. Determine and record the average
alkalinity level for each test run.
Determine and record the minimum test run average alkalinity
level.
You shall . . .
*
*
Internal scrubbing system
meeting HCl percent reduction
standard.
ii.
Alternative pH
§ 63.1573(c)(1).
method
in
iii. Alternative alkalinity method in
§ 63.1573(c)(2).
*
*
*
*
*
*
*
1 The
EPA Methods 5050, 9056, 9212 and 9253 are included in ‘‘Test Methods for Evaluating Solid Waste, Physical/Chemical Methods,’’ EPA
Publication SW–846, Revision 5 (April 1998). The SW–846 and Updates (document number 955–001–00000–1) are available for purchase from
the Superintendent of Documents, U.S. Government Printing Office, Washington, DC 20402, (202) 512–1800; and from the National Technical
Information Services (NTIS), 5285 Port Royal Road, Springfield, VA 22161, (703) 487–4650. Copies may be inspected at the EPA Docket Center, William Jefferson Clinton (WJC) West Building (Air Docket), Room 3334, 1301 Constitution Ave. NW., Washington, DC; or at the Office of the
Federal Register, 800 North Capitol Street NW., Suite 700, Washington, DC. These methods are also available at https://www.epa.gov/epaoswer/
hazwaste/test/main.htm.
76. Table 28 to subpart UUU of part
63 is amended by revising the entry for
tkelley on DSK3SPTVN1PROD with RULES2
■
item 5 and footnotes 1 and 3 to read as
follows:
*
*
*
*
*
TABLE 28 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR INORGANIC HAP
EMISSIONS FROM CATALYTIC REFORMING UNITS
For each new and existing catalytic reforming
unit using this type of control device or
system . . .
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
For this operating limit . . .
PO 00000
Frm 00132
Fmt 4701
Sfmt 4700
You shall demonstrate continuous compliance
during coke burn-off and catalyst rejuvenation
by . . .
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75309
TABLE 28 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR INORGANIC HAP
EMISSIONS FROM CATALYTIC REFORMING UNITS—Continued
For each new and existing catalytic reforming
unit using this type of control device or
system . . .
*
*
5. Moving-bed gas-solid adsorption system
(e.g., ChlorsorbTM System).
You shall demonstrate continuous compliance
during coke burn-off and catalyst rejuvenation
by . . .
For this operating limit . . .
*
*
*
a. The daily average temperature of the gas
entering or exiting the adsorption system
must not exceed the limit established during
the performance test.
b. The weekly average chloride level on the
sorbent entering the adsorption system must
not exceed the design or manufacturer’s
recommended limit (1.35 weight percent for
the ChlorsorbTM System).
c. The weekly average chloride level on the
sorbent exiting the adsorption system must
not exceed the design or manufacturer’s
recommended limit (1.8 weight percent for
the ChlorsorbTM System).
*
*
Collecting the hourly and daily average temperature monitoring data according to
§ 63.1572; and maintaining the daily average temperature below the operating limit
established during the performance test.
Collecting samples of the sorbent exiting the
adsorption system three times per week (on
non-consecutive days); and analyzing the
samples for total chloride3; and determining
and recording the weekly average chloride
concentration; and maintaining the chloride
concentration below the design or manufacturer’s recommended limit (1.35 weight percent for the ChlorsorbTM System).
Collecting samples of the sorbent exiting the
adsorption system three times per week (on
non-consecutive days); and analyzing the
samples for total chloride concentration; and
determining and recording the weekly average chloride concentration; and maintaining
the chloride concentration below the design
or manufacturer’s recommended limit (1.8
weight percent ChlorsorbTM System).
1 If applicable, you can use either alternative in § 63.1573(c) instead of a continuous parameter monitoring system for pH or alkalinity if you
used the alternative method in the initial performance test.
*
*
*
*
*
*
*
3 The total chloride concentration of the sorbent material must be measured by the procedure, ‘‘Determination of Metal Concentration on Catalyst Particles (Instrumental Analyzer Procedure)’’ in appendix A to this subpart; or by using EPA Method 5050, Bomb Preparation Method for
Solid Waste, combined either with EPA Method 9056, Determination of Inorganic Anions by Ion Chromatography, or with EPA Method 9253,
Chloride (Titrimetric, Silver Nitrate); or by using EPA Method 9212, Potentiometric Determination of Chloride in Aqueous Samples with Ion-Selective Electrode, and using the soil extraction procedures listed within the method. The EPA Methods 5050, 9056, 9212 and 9253 are included in
‘‘Test Methods for Evaluating Solid Waste, Physical/Chemical Methods,’’ EPA Publication SW–846, Revision 5 (April 1998). The SW–846 and
Updates (document number 955–001–00000–1) are available for purchase from the Superintendent of Documents, U.S. Government Printing Office, Washington, DC 20402, (202) 512–1800; and from the National Technical Information Services (NTIS), 5285 Port Royal Road, Springfield,
VA 22161, (703) 487–4650. Copies may be inspected at the EPA Docket Center, William Jefferson Clinton (WJC) West Building, (Air Docket),
Room 3334, 1301 Constitution Ave. NW., Washington, DC; or at the Office of the Federal Register, 800 North Capitol Street NW., Suite 700,
Washington, DC. These methods are also available at https://www.epa.gov/epaoswer/hazwaste/test/main.htm.
77. Table 29 to subpart UUU of part
63 is revised to read as follows:
■
As stated in § 63.1568(a)(1), you shall
meet each emission limitation in the
following table that applies to you.
TABLE 29 TO SUBPART UUU OF PART 63—HAP EMISSION LIMITS FOR SULFUR RECOVERY UNITS
For . . .
You shall meet this emission limit for each process vent . . .
1. Subject to NSPS. Each new or existing Claus sulfur recovery unit
part of a sulfur recovery plant with design capacity greater than 20
long tons per day (LTD) and subject to the NSPS for sulfur oxides in
40 CFR 60.104(a)(2) or 60.102a(f)(1).
a. 250 ppmv (dry basis) of sulfur dioxide (SO2) at zero percent excess
air, or concentration determined using Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use an oxidation control system or if you use
a reduction control system followed by incineration.
b. 300 ppmv of reduced sulfur compounds calculated as ppmv SO2
(dry basis) at zero percent excess air, or concentration determined
using Equation 1 of 40 CFR 60.102a(f)(1)(i), if you use a reduction
control system without incineration.
a. 250 ppmv (dry basis) of SO2 at zero percent excess air, or concentration determined using Equation 1 of 40 CFR 60.102a(f)(1)(i), if
you use an oxidation control system or if you use a reduction control
system followed by incineration.
b. 300 ppmv of reduced sulfur compounds calculated as ppmv SO2
(dry basis) at zero percent excess air, or concentration determined
using Equation 1 of 40 CFR 60.102a(f)(1)(i), if you use a reduction
control system without incineration.
300 ppmv of total reduced sulfur (TRS) compounds, expressed as an
equivalent SO2 concentration (dry basis) at zero percent oxygen.
tkelley on DSK3SPTVN1PROD with RULES2
2. Option 1: Elect NSPS. Each new or existing sulfur recovery unit
(Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or 60.102a(f)(1).
3. Option 2: TRS limit. Each new or existing sulfur recovery unit (Claus
or other type, regardless of size) not subject to the NSPS for sulfur
oxides in 40 CFR 60.104(a)(2) or 60.102a(f)(1).
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00133
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75310
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
78. Table 30 to subpart UUU of part
63 is revised to read as follows:
As stated in § 63.1568(a)(2), you shall
meet each operating limit in the
following table that applies to you.
■
TABLE 30 TO SUBPART UUU OF PART 63—OPERATING LIMITS FOR HAP EMISSIONS FROM SULFUR RECOVERY UNITS
For . . .
If use this type of control device . . .
You shall meet this operating limit . . .
1. Subject to NSPS. Each new or existing
Claus sulfur recovery unit part of a sulfur recovery plant with design capacity greater
than 20 LTD and subject to the NSPS for sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
2. Option 1: Elect NSPS. Each new or existing
sulfur recovery unit (Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
3. Option 2: TRS limit, if using continuous emissions monitoring systems. Each new or existing sulfur recovery unit (Claus or other type,
regardless of size) not subject to the NSPS
for sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
4. Option 2: TRS limit, if using continuous parameter monitoring systems. Each new or existing sulfur recovery unit (Claus or other
type, regardless of size) not subject to the
NSPS for sulfur oxides in 40 CFR
60.104(a)(2) or 60.102a(f)(1).
Not applicable ..................................................
Not applicable.
Not applicable ..................................................
Not applicable.
Not applicable ..................................................
Not applicable.
Thermal incinerator ..........................................
5. Startup or shutdown option 1: Electing to
comply with § 63.1568(a)(4)(ii). Each new or
existing sulfur recovery unit (Claus or other
type, regardless of size) during periods of
startup or shutdown.
6. Startup or shutdown option 2: Electing to
comply with § 63.1568(a)(4)(iii). Each new or
existing sulfur recovery unit (Claus or other
type, regardless of size) during startup or
shutdown events.
Flare .................................................................
Maintain the daily average combustion zone
temperature above the limit established during the performance test; and maintain the
daily average oxygen concentration in the
vent stream (percent, dry basis) above the
limit established during the performance
test.
On and after January 30, 2019, meet the applicable requirements of § 63.670. Prior to
January 30, 2019, meet the applicable requirements of either § 63.11(b) or § 63.670.
79. Table 31 to subpart UUU is revised
to read as follows:
■
Thermal incinerator or thermal oxidizer ...........
Maintain the hourly average combustion zone
temperature at or above 1,200 degrees
Fahrenheit and maintain the hourly average
oxygen concentration in the exhaust gas
stream at or above 2 volume percent (dry
basis).
As stated in § 63.1568(b)(1), you shall
meet each requirement in the following
table that applies to you.
TABLE 31 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR HAP EMISSIONS FROM SULFUR
RECOVERY UNITS
For this limit . . .
You shall install and operate this continuous
monitoring system . . .
1. Subject to NSPS. Each new or existing
Claus sulfur recovery unit part of a sulfur recovery plant with design capacity greater
than 20 LTD and subject to the NSPS for sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
tkelley on DSK3SPTVN1PROD with RULES2
For . . .
a. 250 ppmv (dry basis) of SO2 at zero percent excess air if you use an oxidation or
reduction control system followed by incineration.
Continuous emission monitoring system to
measure and record the hourly average
concentration of SO2 (dry basis) at zero
percent excess air for each exhaust stack.
This system must include an oxygen monitor for correcting the data for excess air.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00134
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75311
TABLE 31 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR HAP EMISSIONS FROM SULFUR
RECOVERY UNITS—Continued
For this limit . . .
You shall install and operate this continuous
monitoring system . . .
b. 300 ppmv of reduced sulfur compounds
calculated as ppmv SO2 (dry basis) at zero
percent excess air if you use a reduction
control system without incineration.
For . . .
Continuous emission monitoring system to
measure and record the hourly average
concentration of reduced sulfur and oxygen
(O2) emissions. Calculate the reduced sulfur emissions as SO2 (dry basis) at zero
percent excess air. Exception: You can use
an instrument having an air or SO2 dilution
and oxidation system to convert the reduced sulfur to SO2 for continuously monitoring and recording the concentration (dry
basis) at zero percent excess air of the resultant SO2 instead of the reduced sulfur
monitor. The monitor must include an oxygen monitor for correcting the data for excess oxygen.
i. Complete either item 1.a or item 1.b; and
ii. Either a continuous emission monitoring
system to measure and record the O2 concentration for the inlet air/oxygen supplied
to the system or a continuous parameter
monitoring system to measure and record
the volumetric gas flow rate of ambient air
and purchased oxygen-enriched gas.
Continuous emission monitoring system to
measure and record the hourly average
concentration of SO2 (dry basis), at zero
percent excess air for each exhaust stack.
This system must include an oxygen monitor for correcting the data for excess air.
Continuous emission monitoring system to
measure and record the hourly average
concentration of reduced sulfur and O2
emissions for each exhaust stack. Calculate
the reduced sulfur emissions as SO2 (dry
basis), at zero percent excess air. Exception: You can use an instrument having an
air or O2 dilution and oxidation system to
convert the reduced sulfur to SO2 for continuously monitoring and recording the concentration (dry basis) at zero percent excess air of the resultant SO2 instead of the
reduced sulfur monitor. The monitor must
include an oxygen monitor for correcting the
data for excess oxygen.
i. Complete either item 2.a or item 2.b; and
ii. Either a continuous emission monitoring
system to measure and record the O2 concentration for the inlet air/oxygen supplied
to the system, or a continuous parameter
monitoring system to measure and record
the volumetric gas flow rate of ambient air
and purchased oxygen-enriched gas.
i. Continuous emission monitoring system to
measure and record the hourly average
concentration of TRS for each exhaust
stack; this monitor must include an oxygen
monitor for correcting the data for excess
oxygen; or
ii. Continuous parameter monitoring systems
to measure and record the combustion
zone temperature of each thermal incinerator and the oxygen content (percent, dry
basis) in the vent stream of the incinerator.
c. If you use Equation 1 of 40 CFR
60.102a(f)(1)(i) to set your emission limit.
2. Option 1: Elect NSPS. Each new or existing
sulfur recovery unit (Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
a. 250 ppmv (dry basis) of SO2 at zero percent excess air if you use an oxidation or
reduction control system followed by incineration.
b. 300 ppmv of reduced sulfur compounds
calculated as ppmv SO2 (dry basis) at zero
percent excess air if you use a reduction
control system without incineration.
c. If you use Equation 1 of 40 CFR
60.102a(f)(1)(i) to set your emission limit.
tkelley on DSK3SPTVN1PROD with RULES2
3. Option 2: TRS limit. Each new or existing
sulfur recovery unit (Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
a. 300 ppmv of total reduced sulfur (TRS)
compounds, expressed as an equivalent
SO2 concentration (dry basis) at zero percent oxygen.
PO 00000
Frm 00135
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75312
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 31 TO SUBPART UUU OF PART 63—CONTINUOUS MONITORING SYSTEMS FOR HAP EMISSIONS FROM SULFUR
RECOVERY UNITS—Continued
For . . .
For this limit . . .
You shall install and operate this continuous
monitoring system . . .
4. Startup or shutdown option 1: electing to
comply with § 63.1568(a)(4)(ii). Each new or
existing sulfur recovery unit (Claus or other
type, regardless of size) during periods of
startup or shutdown.
Any ...................................................................
5. Startup or shutdown option 2: electing to
comply with § 63.1568(a)(4)(iii). Each new or
existing sulfur recovery unit (Claus or other
type, regardless of size) during periods of
startup or shutdown.
Any ...................................................................
On and after January 30, 2019, monitoring
systems as specified in §§ 63.670 and
63.671. Prior to January 30, 2019, either
continuous parameter monitoring systems
following the requirements in § 63.11 (to detect the presence of a flame; to measure
and record the net heating value of the gas
being combusted; and to measure and
record the volumetric flow of the gas being
combusted) or monitoring systems as specified in §§ 63.670 and 63.671.
Continuous parameter monitoring systems to
measure and record the firebox temperature of each thermal incinerator or oxidizer
and the oxygen content (percent, dry basis)
in the exhaust vent from the incinerator or
oxidizer.
80. Table 32 to subpart UUU of part
63 is revised to read as follows:
■
As stated in § 63.1568(b)(2) and (3),
you shall meet each requirement in the
following table that applies to you.
TABLE 32 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR HAP EMISSIONS FROM
SULFUR RECOVERY UNITS NOT SUBJECT TO THE NEW SOURCE PERFORMANCE STANDARDS FOR SULFUR OXIDES
For . . .
You must . . .
Using . . .
According to these
requirements . . .
1. Option 1: Elect NSPS. Each
new and existing sulfur recovery
unit.
a. Measure SO2 concentration (for
an oxidation or reduction system followed by incineration) or
measure the concentration of
reduced sulfur (or SO2 if you
use an instrument to convert
the reduced sulfur to SO2) for a
reduction control system without incineration.
b. Measure O2 concentration for
the inlet air/oxygen supplied to
the system, if using Equation 1
of 40 CFR 60.102a(f)1)(i) to set
your emission limit. You may
use either an O2 CEMS method
in item 1.b.i of this table or the
flow monitor in item 1.b.ii of this
table.
Data from continuous emission
monitoring system.
Collect SO2 monitoring data every
15 minutes for 24 consecutive
operating hours. Reduce the
data to 1-hour averages computed from four or more data
points equally spaced over
each 1-hour period.
i. Data from continuous emission
monitoring system; or
Collect O2 monitoring data every
15 minutes for 24 consecutive
operating hours. Reduce the
data to 1-hour averages computed from four or more data
points equally spaced over
each 1-hour period; and average over the 24-hour period for
input to Equation 1 of 40 CFR
60.102a(f)(1)(i).
Collect gas flow rate monitoring
data every 15 minutes for 24
consecutive operating hours.
Reduce the data to 1-hour
averages computed from 4 or
more data points equally
spaced over each 1-hour period; calculate the hourly O2
percent using Equation 10 of 40
CFR 60.106a(a)(6)(iv); and average over the 24-hour period
for input to Equation 1 of 40
CFR 60.102a(f)(1)(i).
Collect TRS data every 15 minutes for 24 consecutive operating hours. Reduce the data to
1-hour averages computed from
four or more data points equally
spaced over each 1-hour period.
tkelley on DSK3SPTVN1PROD with RULES2
ii. Data from flow monitor for ambient air and purchased oxygen-enriched gas.
2. Option 2: TRS limit, using
CEMS. Each new and existing
sulfur recovery unit.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Measure the concentration of reduced sulfur (or SO2 if you use
an instrument to convert the reduced sulfur to SO2).
Jkt 238001
PO 00000
Frm 00136
Fmt 4701
Data from continuous emission
monitoring system.
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75313
TABLE 32 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR PERFORMANCE TESTS FOR HAP EMISSIONS FROM SULFUR RECOVERY UNITS NOT SUBJECT TO THE NEW SOURCE PERFORMANCE STANDARDS FOR SULFUR OXIDES—Continued
For . . .
You must . . .
Using . . .
According to these
requirements . . .
3. Option 2: TRS limit, if using
continuous parameter monitoring
systems. Each new and existing
sulfur recovery unit.
a. Select sampling port’s location
and the number of traverse
ports.
Method 1 or 1A in Appendix A–1
to part 60 of this chapter.
Sampling sites must be located at
the outlet of the control device
and prior to any releases to the
atmosphere.
b. Determine velocity and volumetric flow rate.
Method 2, 2A, 2C, 2D, or 2F in
appendix A–1 to part 60 of this
chapter, or Method 2G in appendix A–2 to part 60 of this
chapter, as applicable.
Method 3, 3A, or 3B in appendix
A–2 to part 60 of this chapter,
as applicable.
c. Conduct gas molecular weight
analysis; obtain the oxygen
concentration needed to correct
the emission rate for excess air.
d. Measure moisture content of
the stack gas.
Method 4 in appendix A–3 to part
60 of this chapter.
e. Measure the concentration of
TRS.
Method 15 or 15A in appendix A–
5 to part 60 of this chapter, as
applicable.
f. Calculate the SO2 equivalent for
each run after correcting for
moisture and oxygen.
g. Correct the reduced sulfur
samples to zero percent excess
air.
h. Establish each operating limit in
Table 30 of this subpart that
applies to you.
i. Measure thermal incinerator:
combustion zone temperature.
Data from the continuous parameter monitoring system.
81. Table 33 to subpart UUU of part
63 is revised to read as follows:
tkelley on DSK3SPTVN1PROD with RULES2
■
VerDate Sep<11>2014
23:11 Nov 30, 2015
Make your sampling time for each
Method 4 sample equal to that
for 4 Method 15 samples.
If the cross-sectional area of the
duct is less than 5 square meters (m2) or 54 square feet, you
must use the centroid of the
cross section as the sampling
point. If the cross-sectional area
is 5 m2 or more and the centroid is more than 1 meter (m)
from the wall, your sampling
point may be at a point no closer to the walls than 1 m or 39
inches. Your sampling rate
must be at least 3 liters per
minute or 0.10 cubic feet per
minute to ensure minimum residence time for the sample inside the sample lines.
The arithmetic average of the SO2
equivalent for each sample during the run.
Equation 1 of § 63.1568 ...............
j. Measure thermal incinerator: oxygen concentration (percent,
dry basis) in the vent stream.
Take the samples simultaneously
with reduced sulfur or moisture
samples.
Jkt 238001
Data from the continuous parameter monitoring system.
Data from the continuous parameter monitoring system.
Collect temperature monitoring
data every 15 minutes during
the entire period of the performance test; and determine and
record the minimum hourly average temperature from all the
readings.
Collect oxygen concentration (percent, dry basis) data every 15
minutes during the entire period
of the performance test; and
determine and record the minimum hourly average percent
excess oxygen concentration.
As stated in § 63.1568(b)(5), you shall
meet each requirement in the following
table that applies to you.
PO 00000
Frm 00137
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75314
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 33 TO SUBPART UUU OF PART 63—INITIAL COMPLIANCE WITH HAP EMISSION LIMITS FOR SULFUR RECOVERY
UNITS
For . . .
For the following emission limit . . .
You have demonstrated initial
compliance if . . .
1. Subject to NSPS: Each new or existing
Claus sulfur recovery unit part of a sulfur recovery plant with design capacity greater
than 20 LTD and subject to the NSPS for sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
a. 250 ppmv (dry basis) SO2 at zero percent
excess air, or concentration determined
using
Equation
1
of
40
CFR
60.102a(f)(1)(i), if you use an oxidation or
reduction control system followed by incineration.
You have already conducted a performance
test to demonstrate initial compliance with
the NSPS and each 12-hour rolling average
concentration of SO2 emissions measured
by the continuous emission monitoring system is less than or equal to 250 ppmv (dry
basis) at zero percent excess air, or the
concentration determined using Equation 1
of 40 CFR 60.102a(f)(1)(i). As part of the
Notification of Compliance Status, you must
certify that your vent meets the SO2 limit.
You are not required to do another performance test to demonstrate initial compliance.
You have already conducted a performance
evaluation to demonstrate initial compliance
with the applicable performance specification. As part of your Notification of Compliance Status, you must certify that your continuous emission monitoring system meets
the applicable requirements in § 63.1572.
You are not required to do another performance evaluation to demonstrate initial compliance.
You have already conducted a performance
test to demonstrate initial compliance with
the NSPS and each 12-hour rolling average
concentration of reduced sulfur compounds
measured by your continuous emission
monitoring system is less than or equal to
300 ppmv, calculated as ppmv SO2 (dry
basis) at zero percent excess air, or the
concentration determined using Equation 1
of 40 CFR 60.102a(f)(1)(i). As part of the
Notification of Compliance Status, you must
certify that your vent meets the SO2 limit.
You are not required to do another performance test to demonstrate initial compliance.
You have already conducted a performance
evaluation to demonstrate initial compliance
with the applicable performance specification. As part of your Notification of Compliance Status, you must certify that your continuous emission monitoring system meets
the applicable requirements in § 63.1572.
You are not required to do another performance evaluation to demonstrate initial compliance.
Each 12-hour rolling average concentration of
SO2 emissions measured by the continuous
emission monitoring system during the initial performance test is less than or equal to
250 ppmv (dry basis) at zero percent excess air, or the concentration determined
using
Equation
1
of
40
CFR
60.102a(f)(1)(i); and your performance evaluation shows the monitoring system meets
the applicable requirements in § 63.1572.
Each 12-hour rolling average concentration of
reduced sulfur compounds measured by the
continuous emission monitoring system during the initial performance test is less than
or equal to 300 ppmv, calculated as ppmv
SO2 (dry basis) at zero percent excess air,
or the concentration determined using
Equation 1 of 40 CFR 60.102a(f)(1)(i); and
your performance evaluation shows the
continuous emission monitoring system
meets the applicable requirements in
§ 63.1572.
b. 300 ppmv of reduced sulfur compounds
calculated as ppmv SO2 (dry basis) at zero
percent excess air, or concentration determined using Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use a reduction control system without incineration.
tkelley on DSK3SPTVN1PROD with RULES2
2. Option 1: Elect NSPS. Each new or existing
sulfur recovery unit (Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
a. 250 ppmv (dry basis) of SO2 at zero percent excess air, or concentration determined using Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use an oxidation or
reduction control system followed by incineration.
b. 300 ppmv of reduced sulfur compounds
calculated as ppmv SO2 (dry basis) at zero
percent excess air, or concentration determined using Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use a reduction control system without incineration.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00138
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75315
TABLE 33 TO SUBPART UUU OF PART 63—INITIAL COMPLIANCE WITH HAP EMISSION LIMITS FOR SULFUR RECOVERY
UNITS—Continued
For . . .
For the following emission limit . . .
You have demonstrated initial
compliance if . . .
3. Option 2: TRS limit. Each new or existing
sulfur recovery unit (Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
300 ppmv of TRS compounds expressed as
an equivalent SO2 concentration (dry basis)
at zero percent oxygen.
If you use continuous parameter monitoring
systems, the average concentration of TRS
emissions measured using Method 15 during the initial performance test is less than
or equal to 300 ppmv expressed as equivalent SO2 concentration (dry basis) at zero
percent oxygen. If you use a continuous
emission monitoring system, each 12-hour
rolling average concentration of TRS emissions measured by the continuous emission
monitoring system during the initial performance test is less than or equal to 300 ppmv
expressed as an equivalent SO2 (dry basis)
at zero percent oxygen; and your performance evaluation shows the continuous
emission monitoring system meets the applicable requirements in § 63.1572.
82. Table 34 to subpart UUU of part
63 is revised to read as follows:
As stated in § 63.1568(c)(1), you shall
meet each requirement in the following
table that applies to you.
■
TABLE 34 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH HAP EMISSION LIMITS FOR SULFUR
RECOVERY UNITS
For . . .
For this emission limit . . .
You shall demonstrate continuous compliance
by . . .
1. Subject to NSPS. Each new or existing
Claus sulfur recovery unit part of a sulfur recovery plant with design capacity greater
than 20 LTD and subject to the NSPS for sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
a. 250 ppmv (dry basis) of SO2 at zero percent excess air, or concentration determined using Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use an oxidation or
reduction control system followed by incineration.
Collecting the hourly average SO2 monitoring
data (dry basis, percent excess air) and, if
using
Equation
1
of
40
CFR
60.102a(f)(1)(i), collecting the hourly O2
concentration or flow monitoring data according to § 63.1572; determining and recording each 12-hour rolling average concentration of SO2; maintaining each 12-hour
rolling average concentration of SO2 at or
below the applicable emission limitation;
and reporting any 12-hour rolling average
concentration of SO2 greater than the applicable emission limitation in the semiannual
compliance report required by § 63.1575.
Collecting the hourly average reduced sulfur
(and air or O2 dilution and oxidation) monitoring data and, if using Equation 1 of 40
CFR 60.102a(f)(1)(i), collecting the hourly
O2 concentration or flow monitoring data
according to § 63.1572; determining and recording each 12-hour rolling average concentration of reduced sulfur; maintaining
each 12-hour rolling average concentration
of reduced sulfur at or below the applicable
emission limitation; and reporting any 12hour rolling average concentration of reduced sulfur greater than the applicable
emission limitation in the semiannual compliance report required by § 63.1575.
tkelley on DSK3SPTVN1PROD with RULES2
b. 300 ppmv of reduced sulfur compounds
calculated as ppmv SO2 (dry basis) at zero
percent excess air, or concentration determined using Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use a reduction control system without incineration.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00139
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75316
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 34 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH HAP EMISSION LIMITS FOR SULFUR
RECOVERY UNITS—Continued
For . . .
For this emission limit . . .
You shall demonstrate continuous compliance
by . . .
2. Option 1: Elect NSPS. Each new or existing
sulfur recovery unit (Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
a. 250 ppmv (dry basis) of SO2 at zero percent excess air, or concentration determined using Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use an oxidation or
reduction control system followed by incineration.
Collecting the hourly average SO2 data (dry
basis, percent excess air) and, if using
Equation 1 of 40 CFR 60.102a(f)(1)(i), collecting the hourly O2 concentration or flow
monitoring data according to § 63.1572; determining and recording each 12-hour rolling average concentration of SO2; maintaining each 12-hour rolling average concentration of SO2 at or below the applicable emission limitation; and reporting any 12-hour
rolling average concentration of SO2 greater
than the applicable emission limitation in
the semiannual compliance report required
by § 63.1575.
Collecting the hourly average reduced sulfur
(and air or O2 dilution and oxidation) monitoring data and, if using Equation 1 of 40
CFR 60.102a(f)(1)(i), collecting the hourly
O2 concentration or flow monitoring data
according to § 63.1572; determining and recording each 12-hour rolling average concentration of reduced sulfur; maintaining
each 12-hour rolling average concentration
of reduced sulfur at or below the applicable
emission limitation; and reporting any 12hour rolling average concentration of reduced sulfur greater than the applicable
emission limitation in the semiannual compliance report required by § 63.1575.
i. If you use continuous parameter monitoring
systems, collecting the hourly average TRS
monitoring data according to § 63.1572 and
maintaining each 12-hour average concentration of TRS at or below the applicable
emission limitation; or
ii. If you use a continuous emission monitoring system, collecting the hourly average
TRS
monitoring
data
according
to
§ 63.1572, determining and recording each
12-hour rolling average concentration of
TRS; maintaining each 12-hour rolling average concentration of TRS at or below the
applicable emission limitation; and reporting
any 12-hour rolling average TRS concentration greater than the applicable emission
limitation in the semiannual compliance report required by § 63.1575.
b. 300 ppmv of reduced sulfur compounds
calculated as ppmv SO2 (dry basis) at zero
percent excess air, or concentration determined using Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use a reduction control system without incineration.
3. Option 2: TRS limit. Each new or existing
sulfur recovery unit (Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
83. Table 35 to subpart UUU of part
63 is revised to read as follows:
300 ppmv of TRS compounds, expressed as
an SO2 concentration (dry basis) at zero
percent oxygen or reduced sulfur compounds calculated as ppmv SO2 (dry basis)
at zero percent excess air.
As stated in § 63.1568(c)(1), you shall
meet each requirement in the following
table that applies to you.
■
TABLE 35 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR HAP EMISSIONS
FROM SULFUR RECOVERY UNITS
tkelley on DSK3SPTVN1PROD with RULES2
For . . .
For this operating limit . . .
You shall demonstrate continuous compliance
by . . .
1. Subject to NSPS. Each new or existing
Claus sulfur recovery unit part of a sulfur recovery plant with design capacity greater
than 20 LTD and subject to the NSPS for sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
Not applicable ..................................................
Meeting the requirements of Table 34 of this
subpart.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00140
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75317
TABLE 35 TO SUBPART UUU OF PART 63—CONTINUOUS COMPLIANCE WITH OPERATING LIMITS FOR HAP EMISSIONS
FROM SULFUR RECOVERY UNITS—Continued
For . . .
For this operating limit . . .
You shall demonstrate continuous compliance
by . . .
2. Option 1: Elect NSPS. Each new or existing
sulfur recovery unit (Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
3. Option 2: TRS limit. Each new or existing
sulfur recovery unit (Claus or other type, regardless of size) not subject to the NSPS for
sulfur oxides in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
Not applicable ..................................................
Meeting the requirements of Table 34 of this
subpart.
a. Maintain the daily average combustion
zone temperature above the level established during the performance test.
Collecting the hourly and daily average temperature monitoring data according to
§ 63.1572; and maintaining the daily average combustion zone temperature at or
above the limit established during the performance test
Collecting the hourly and daily average O2
monitoring data according to § 63.1572; and
maintaining the average O2 concentration
above the level established during the performance test.
On and after January 30, 2019, complying
with the applicable requirements of
§ 63.670. Prior to January 30, 2019, complying with the applicable requirements of
either § 63.11(b) or § 63.670.
Collecting continuous (at least once every 15
minutes) and hourly average temperature
monitoring data according to § 63.1572; and
maintaining the daily average firebox temperature at or above 1,200 degrees Fahrenheit.
Collecting continuous (at least once every 15
minutes) and hourly average O2 monitoring
data according to § 63.1572; and maintaining the average O2 concentration at or
above 2 volume percent (dry basis).
b. The daily average oxygen concentration in
the vent stream (percent, dry basis) must
not fall below the level established during
the performance test..
4. Startup or shutdown option 1: Electing to
comply with § 63.1568(a)(4)(ii). Each new or
existing sulfur recovery unit (Claus or other
type, regardless of size) during periods of
startup or shutdown.
5. Startup or shutdown option 2: Electing to
comply with § 63.1568(a)(4)(iii). Each new or
existing sulfur recovery unit (Claus or other
type, regardless of size) during periods of
startup or shutdown.
Using a flare meeting the requirements in
§ 63.11(b) or § 63.670.
a. Minimum hourly average temperature of
1,200 degrees Fahrenheit.
b. Minimum hourly average outlet oxygen
concentration of 2 volume percent (dry
basis).
84. Table 40 to subpart UUU of part
63 is revised to read as follows:
■
As stated in § 63.1572(a)(1) and (b)(1),
you shall meet each requirement in the
following table that applies to you.
TABLE 40 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR INSTALLATION, OPERATION, AND MAINTENANCE OF
CONTINUOUS OPACITY MONITORING SYSTEMS AND CONTINUOUS EMISSION MONITORING SYSTEMS
This type of continuous opacity or emission monitoring system . . .
Must meet these requirements . . .
1. Continuous opacity monitoring system ................................................
2. PM CEMS; this monitor must include an O2 monitor for correcting
the data for excess air.
3. CO continuous emission monitoring system ........................................
Performance specification 1 (40 CFR part 60, appendix B).
The requirements in 40 CFR 60.105a(d).
tkelley on DSK3SPTVN1PROD with RULES2
4. CO continuous emission monitoring system used to demonstrate
emissions average under 50 ppm (dry basis).
5. SO2 continuous emission monitoring system for sulfur recovery unit
with oxidation control system or reduction control system; this monitor must include an O2 monitor for correcting the data for excess air.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00141
Fmt 4701
Performance specification 4 (40 CFR part 60, appendix B); span value
of 1,000 ppm; and procedure 1 (40 CFR part 60, appendix F) except
relative accuracy test audits are required annually instead of quarterly.
Performance specification 4 (40 CFR part 60, appendix B); and span
value of 100 ppm.
Performance specification 2 (40 CFR part 60, appendix B); span value
of 500 ppm SO2, or if using Equation 1 of 40 CFR 60.102a(f)(1)(i),
span value of two times the limit at the highest O2 concentration; use
Methods 6 or 6C (40 CFR part 60, appendix A–4) for certifying the
SO2 monitor and Methods 3A or 3B (40 CFR part 60, appendix A–2)
for certifying the O2 monitor; and procedure 1 (40 CFR part 60, appendix F) except relative accuracy test audits are required annually
instead of quarterly.
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75318
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 40 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR INSTALLATION, OPERATION, AND MAINTENANCE OF
CONTINUOUS OPACITY MONITORING SYSTEMS AND CONTINUOUS EMISSION MONITORING SYSTEMS—Continued
This type of continuous opacity or emission monitoring system . . .
Must meet these requirements . . .
6. Reduced sulfur and O2 continuous emission monitoring system for
sulfur recovery unit with reduction control system not followed by incineration; this monitor must include an O2 monitor for correcting the
data for excess air unless exempted.
Performance specification 5 (40 CFR part 60, appendix B), except calibration drift specification is 2.5 percent of the span value instead of 5
percent; span value is 450 ppm reduced sulfur, or if using Equation
1 of 40 CFR 60.102a(f)(1)(i), span value of two times the limit at the
highest O2 concentration; use Methods 15 or 15A (40 CFR part 60,
appendix A–5) for certifying the reduced sulfur monitor and Methods
3A or 3B (40 CFR part 60, appendix A–2) for certifying the O2 monitor; if Method 3A or 3B yields O2 concentrations below 0.25 percent
during the performance evaluation, the O2 concentration can be assumed to be zero and the O2 monitor is not required; and procedure
1 (40 CFR part 60, appendix F), except relative accuracy test audits,
are required annually instead of quarterly.
Performance specification 5 (40 CFR part 60, appendix B); span value
of 375 ppm SO2 or if using Equation 1 of 40 CFR 60.102a(f)(1)(i),
span value of two times the limit at the highest O2 concentration; use
Methods 15 or 15A (40 CFR part 60, appendix A–5) for certifying the
reduced sulfur monitor and 3A or 3B (40 CFR part 60, appendix A–
2) for certifying the O2 monitor; and procedure 1 (40 CFR part 60,
appendix F), except relative accuracy test audits, are required annually instead of quarterly.
Performance specification 5 (40 CFR part 60, appendix B).
7. Instrument with an air or O2 dilution and oxidation system to convert
reduced sulfur to SO2 for continuously monitoring the concentration
of SO2 instead of reduced sulfur monitor and O2 monitor.
8. TRS continuous emission monitoring system for sulfur recovery unit;
this monitor must include an O2 monitor for correcting the data for
excess air.
9. O2 monitor for oxygen concentration ...................................................
85. Table 41 to subpart UUU of part
63 is revised to read as follows:
■
If necessary due to interferences, locate the oxygen sensor prior to the
introduction of any outside gas stream; performance specification 3
(40 CFR part 60, appendix B; and procedure 1 (40 CFR part 60, appendix F), except relative accuracy test audits, are required annually
instead of quarterly.
As stated in § 63.1572(c)(1), you shall
meet each requirement in the following
table that applies to you.
TABLE 41 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR INSTALLATION, OPERATION, AND MAINTENANCE OF
CONTINUOUS PARAMETER MONITORING SYSTEMS
If you use . . .
You shall . . .
1. pH strips ............
2. pH meter ............
Use pH strips with an accuracy of ±10 percent.
Locate the pH sensor in a position that provides a representative measurement of pH; ensure the sample is properly
mixed and representative of the fluid to be measured.
Use a pH sensor with an accuracy of at least ±0.2 pH units.
Check the pH meter’s calibration on at least one point at least once daily; check the pH meter’s calibration on at least two
points at least once quarterly; at least monthly, inspect all components for integrity and all electrical components for
continuity; record the results of each calibration check and inspection.
Use a colormetric tube sampling system with a printed numerical scale in ppmv, a standard measurement range of 1 to 10
ppmv (or 1 to 30 ppmv if applicable), and a standard deviation for measured values of no more than ±15 percent. System must include a gas detection pump and hot air probe if needed for the measurement range.
a. Locate the concentration sensor so that it provides a representative measurement of the content of the exit gas stream;
ensure the sample is properly mixed and representative of the gas to be measured.
3. Colormetric tube
sampling system.
tkelley on DSK3SPTVN1PROD with RULES2
4. CO2, O2, and CO
monitors for coke
burn-off rate.
5. BLD ....................
6. Voltage, secondary current, or
total power input
sensors.
VerDate Sep<11>2014
Use a sensor with an accuracy of at least ±1 percent of the range of the sensor or to a nominal gas concentration of ±0.5
percent, whichever is greater.
Use a monitor that is able to measure concentration on a dry basis or is able to correct for moisture content and record on
a dry basis.
Conduct calibration checks at least annually; conduct calibration checks following any period of more than 24 hours
throughout which the sensor reading exceeds the manufacturer’s specified maximum operating range or install a new
sensor; at least quarterly, inspect all components for integrity and all electrical connections for continuity; record the results of each calibration and inspection.
b. As an alternative, the requirements in 40 CFR 60.105a(b)(2) may be used.
Follow the requirements in 40 CFR 60.105a(c).
Use meters with an accuracy of at least ±5 percent over the operating range.
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00142
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75319
TABLE 41 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR INSTALLATION, OPERATION, AND MAINTENANCE OF
CONTINUOUS PARAMETER MONITORING SYSTEMS—Continued
If you use . . .
You shall . . .
7. Pressure/Pressure drop1 sensors.
8. Air flow rate, gas
flow rate, or total
water (or scrubbing liquid) flow
rate sensors.
9. Temperature
sensors.
10. Oxygen content
sensors 2.
Each time that the unit is not operating, confirm that the meters read zero. Conduct a calibration check at least annually;
conduct calibration checks following any period of more than 24 hours throughout which the meter reading exceeds the
manufacturer’s specified maximum operating range; at least monthly, inspect all components of the continuous parameter monitoring system for integrity and all electrical connections for continuity; record the results of each calibration
check and inspection.
Locate the pressure sensor(s) in a position that provides a representative measurement of the pressure and minimizes or
eliminates pulsating pressure, vibration, and internal and external corrosion.
Use a gauge with an accuracy of at least ±5 percent over the normal operating range or 0.12 kilopascals (0.5 inches of
water column), whichever is greater.
Review pressure sensor readings at least once a week for straightline (unchanging) pressure and perform corrective action to ensure proper pressure sensor operation if blockage is indicated; using an instrument recommended by the sensor’s manufacturer, check gauge calibration and transducer calibration annually; conduct calibration checks following
any period of more than 24 hours throughout which the pressure exceeded the manufacturer’s specified maximum rated
pressure or install a new pressure sensor; at least quarterly, inspect all components for integrity, all electrical connections for continuity, and all mechanical connections for leakage, unless the CPMS has a redundant pressure sensor;
record the results of each calibration check and inspection.
Locate the flow sensor(s) and other necessary equipment (such as straightening vanes) in a position that provides representative flow; reduce swirling flow or abnormal velocity distributions due to upstream and downstream disturbances.
If you elect to comply with Option 3 (Ni lb/hr) or Option 4 (Ni lb/1,000 lb of coke burn-off) for the HAP metal emission
limitations in § 63.1564, install the continuous parameter monitoring system for gas flow rate as close as practical to the
continuous opacity monitoring system; and if you don’t use a continuous opacity monitoring system, install the continuous parameter monitoring system for gas flow rate as close as practical to the control device.
Use a flow rate sensor with an accuracy of at least ±5 percent over the normal range of flow measured, or 1.9 liter per
minute (0.5 gallons per minute), whichever is greater, for liquid flow.
Use a flow rate sensor with an accuracy of at least ±5 percent over the normal range of flow measured, or 280 liters per
minute (10 cubic feet per minute), whichever is greater, for gas flow.
Conduct a flow sensor calibration check at least biennially (every two years); conduct a calibration check following any period of more than 24 hours throughout which the flow rate exceeded the manufacturer’s specified maximum rated flow
rate or install a new flow sensor; at least quarterly, inspect all components for leakage, unless the CPMS has a redundant flow sensor; record the results of each calibration check and inspection.
Locate the temperature sensor in the combustion zone, or in the ductwork immediately downstream of the combustion
zone before any substantial heat exchange occurs or in the ductwork immediately downstream of the regenerator; locate the temperature sensor in a position that provides a representative temperature; shield the temperature sensor system from electromagnetic interference and chemical contaminants.
Use a temperature sensor with an accuracy of at least ±1 percent over the normal range of temperature measured, expressed in degrees Celsius (C), or 2.8 degrees C, whichever is greater.
Conduct calibration checks at least annually; conduct calibration checks following any period of more than 24 hours
throughout which the temperature exceeded the manufacturer’s specified maximum rated temperature or install a new
temperature sensor; at least quarterly, inspect all components for integrity and all electrical connections for continuity,
oxidation, and galvanic corrosion, unless the CPMS has a redundant temperature sensor; record the results of each
calibration check and inspection.
Locate the oxygen sensor so that it provides a representative measurement of the oxygen content of the exit gas stream;
ensure the sample is properly mixed and representative of the gas to be measured.
Use an oxygen sensor with an accuracy of at least ±1 percent of the range of the sensor or to a nominal gas concentration of ±0.5 percent, whichever is greater.
Conduct calibration checks at least annually; conduct calibration checks following any period of more than 24 hours
throughout which the sensor reading exceeds the manufacturer’s specified maximum operating range or install a new
oxygen sensor; at least quarterly, inspect all components for integrity and all electrical connections for continuity; record
the results of each calibration and inspection.
1 Not
applicable to non-venturi wet scrubbers of the jet-ejector design.
does not replace the requirements for oxygen monitors that are required to use continuous emissions monitoring systems. The requirements in this table apply to oxygen sensors that are continuous parameter monitors, such as those that monitor combustion zone oxygen concentration and regenerator exit oxygen concentration.
2 This
86. Table 43 to subpart UUU is revised
to read as follows:
tkelley on DSK3SPTVN1PROD with RULES2
■
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
As stated in § 63.1575(a), you shall
meet each requirement in the following
table that applies to you.
PO 00000
Frm 00143
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75320
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 43 TO SUBPART UUU OF PART 63—REQUIREMENTS FOR REPORTS
You must submit . . .
The report must contain . . .
You shall submit the report . . .
1. A compliance report ....................
If there are no deviations from any emission limitation or work practice standard that applies to you, a statement that there were no
deviations from the standards during the reporting period and that
no continuous opacity monitoring system or continuous emission
monitoring system was inoperative, inactive, out-of-control, repaired, or adjusted; if you have a deviation from any emission limitation or work practice standard during the reporting period, the report must contain the information in § 63.1575(c) through (e).
On and after January 30, 2019, the information specified in
§ 63.1575(k)(1).
Semiannually according to the requirements in § 63.1575(b).
2. Performance test and CEMS
performance evaluation data.
87. Table 44 to subpart UUU of part
63 is revised to read as follows:
■
Within 60 days after the date of
completing each test according
to
the
requirements
in
§ 63.1575(k).
As stated in § 63.1577, you shall meet
each requirement in the following table
that applies to you.
TABLE 44 TO SUBPART UUU OF PART 63—APPLICABILITY OF NESHAP GENERAL PROVISIONS TO SUBPART UUU
Citation
Subject
Applies to subpart
UUU
§ 63.1(a)(1)–(4) .....................................
§ 63.1(a)(5) ............................................
§ 63.1(a)(6) ............................................
General Applicability ...........................
[Reserved] ..........................................
.............................................................
Yes .............................
Not applicable ............
Yes .............................
§ 63.1(a)(7)–(9) .....................................
§ 63.1(a)(10)–(12) .................................
[Reserved] ..........................................
.............................................................
Not applicable ............
Yes .............................
§ 63.1(b)(1) ............................................
Yes .............................
§ 63.1(c)(2) ............................................
Initial Applicability Determination for
this part.
[Reserved] ..........................................
.............................................................
Applicability of this part after a Relevant Standard has been set under
this part.
.............................................................
No ...............................
§ 63.1(c)(3)–(4) .....................................
§ 63.1(c)(5) ............................................
§ 63.1(d) ................................................
§ 63.1(e) ................................................
§ 63.2 ....................................................
[Reserved] ..........................................
.............................................................
[Reserved] ..........................................
Applicability of Permit Program ..........
Definitions ...........................................
Not applicable ............
Yes .............................
Not applicable ............
Yes .............................
Yes .............................
§ 63.3 ....................................................
§ 63.4(a)(1)–(2) .....................................
§ 63.4(a)(3)–(5) .....................................
§ 63.4(b)–(c) ..........................................
§ 63.5(a) ................................................
§ 63.5(b)(1) ............................................
§ 63.5(b)(2) ............................................
§ 63.5(b)(3)–(4) .....................................
Units and Abbreviations .....................
Prohibited Activities ............................
[Reserved] ..........................................
Circumvention and Fragmentation .....
Construction and Reconstruction .......
.............................................................
[Reserved] ..........................................
.............................................................
Yes .............................
Yes .............................
Not applicable ............
Yes .............................
Yes .............................
Yes .............................
Not applicable ............
Yes .............................
§ 63.5(b)(5) ............................................
§ 63.5(b)(6) ............................................
§ 63.5(c) ................................................
§ 63.5(d)(1)(i) ........................................
[Reserved] ..........................................
.............................................................
[Reserved] ..........................................
Application for Approval of Construction or Reconstruction—General
Application Requirements.
Not applicable ............
Yes .............................
Not applicable ............
Yes .............................
tkelley on DSK3SPTVN1PROD with RULES2
§ 63.1(b)(2) ............................................
§ 63.1(b)(3) ............................................
§ 63.1(c)(1) ............................................
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00144
Fmt 4701
Explanation
Except the correct mail drop (MD)
number is C404–04.
Except that this subpart specifies calendar or operating day.
Not applicable ............
Yes .............................
Yes .............................
Sfmt 4700
E:\FR\FM\01DER2.SGM
Area sources are not subject to this
subpart.
§ 63.1579 specifies that if the same
term is defined in subparts A and
UUU of this part, it shall have the
meaning given in this subpart.
In § 63.5(b)(4), replace the reference
to § 63.9(b) with § 63.9(b)(4) and
(5).
Except this subpart specifies the application is submitted as soon as
practicable before startup but not
later than 90 days after the promulgation date if construction or reconstruction had commenced and initial startup had not occurred before
promulgation.
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75321
TABLE 44 TO SUBPART UUU OF PART 63—APPLICABILITY OF NESHAP GENERAL PROVISIONS TO SUBPART UUU—
Continued
Citation
Subject
Applies to subpart
UUU
Explanation
§ 63.5(d)(1)(ii) ........................................
.............................................................
Yes .............................
§ 63.5(d)(1)(iii) .......................................
.............................................................
No ...............................
Except that emission estimates specified in § 63.5(d)(1)(ii)(H) are not required, and § 63.5(d)(1)(ii)(G) and
(I) are Reserved and do not apply.
This subpart specifies submission of
notification of compliance status.
§ 63.5(d)(2) ............................................
§ 63.5(d)(3) ............................................
§ 63.5(d)(4) ............................................
§ 63.5(e) ................................................
.............................................................
.............................................................
.............................................................
Approval of Construction or Reconstruction.
Approval of Construction or Reconstruction Based on State Review.
.............................................................
Yes
Yes
Yes
Yes
Compliance with Standards and
Maintenance—Applicability.
Compliance Dates for New and Reconstructed Sources.
.............................................................
Yes .............................
[Reserved] ..........................................
Compliance Dates for New and Reconstructed Area Sources That Become Major.
Compliance
Dates
for
Existing
Sources.
Not applicable ............
Yes .............................
[Reserved] ..........................................
Compliance Dates for Existing Area
Sources That Become Major.
[Reserved] ..........................................
General Duty to Minimize Emissions
Not applicable ............
Yes .............................
Requirement to Correct Malfunctions
as Soon as Possible.
Compliance with Standards and
Maintenance Requirements.
[Reserved] ..........................................
Startup, Shutdown, and Malfunction
Plan Requirements.
[Reserved] ..........................................
.............................................................
SSM Exemption ..................................
Compliance with Standards and
Maintenance Requirements.
.............................................................
.............................................................
.............................................................
No ...............................
§ 63.5(f)(1) .............................................
§ 63.5(f)(2) .............................................
§ 63.6(a) ................................................
§ 63.6(b)(1)–(4) .....................................
§ 63.6(b)(5) ............................................
§ 63.6(b)(6) ............................................
§ 63.6(b)(7) ............................................
§ 63.6(c)(1)–(2) .....................................
§ 63.6(c)(3)–(4) .....................................
§ 63.6(c)(5) ............................................
§ 63.6(d) ................................................
§ 63.6(e)(1)(i) ........................................
§ 63.6(e)(1)(ii) ........................................
§ 63.6(e)(1)(iii) .......................................
§ 63.6(e)(2) ............................................
§ 63.6(e)(3)(i) ........................................
§ 63.6(e)(3)(ii) ........................................
§ 63.6(e)(3)(iii)–(ix) ................................
§ 63.6(f)(1) .............................................
§ 63.6(f)(2)(i)–(iii)(C) ..............................
§ 63.6(f)(2)(iii)(D) ...................................
§ 63.6(f)(2)(iv)–(v) .................................
§ 63.6(f)(3) .............................................
§ 63.6(g) ................................................
§ 63.6(h)(1) ............................................
tkelley on DSK3SPTVN1PROD with RULES2
§ 63.6(h)(2)(i) ........................................
§ 63.6(h)(2)(ii) ........................................
§ 63.6(h)(2)(iii) .......................................
§ 63.6(h)(3) ............................................
§ 63.6(h)(4) ............................................
§ 63.6(h)(5) ............................................
§ 63.6(h)(6) ............................................
§ 63.6(h)(7)(i) ........................................
§ 63.6(h)(7)(ii) ........................................
VerDate Sep<11>2014
23:11 Nov 30, 2015
Alternative Standard ...........................
SSM Exemption for Opacity/VE
Standards.
Determining Compliance with Opacity/VE Standards.
[Reserved] ..........................................
.............................................................
[Reserved] ..........................................
Notification of Opacity/VE Observation Date.
Conducting Opacity/VE Observations
Records of Conditions During Opacity/VE Observations.
Report COM Monitoring Data from
Performance Test.
Using COM Instead of Method 9 .......
Jkt 238001
PO 00000
Frm 00145
Fmt 4701
.............................
.............................
.............................
.............................
Yes .............................
Yes .............................
Except that the cross-reference to
§ 63.9(b)(2) does not apply.
Yes .............................
Yes .............................
Yes .............................
Not applicable ............
No ...............................
Except that this subpart specifies different
compliance
dates
for
sources.
Except that this subpart specifies different compliance dates for sources
subject to Tier II gasoline sulfur
control requirements.
See § 63.1570(c) for general duty requirement.
Yes .............................
Not Applicable ............
No ...............................
Not applicable ............
No ...............................
No ...............................
Yes .............................
Yes .............................
Yes .............................
Yes .............................
Except the cross-references to
§ 63.6(f)(1)
and
(e)(1)(i)
are
changed to § 63.1570(c).
Yes .............................
No ...............................
No ...............................
Not applicable ............
Yes .............................
Not applicable ............
Yes .............................
No ...............................
Yes .............................
This subpart specifies methods.
Applies to Method 22 (40 CFR part
60, appendix A–7) tests.
Applies to Method 22 (40 CFR part
60, appendix A–7) observations.
Yes .............................
No ...............................
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75322
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 44 TO SUBPART UUU OF PART 63—APPLICABILITY OF NESHAP GENERAL PROVISIONS TO SUBPART UUU—
Continued
Citation
Subject
Applies to subpart
UUU
§ 63.6(h)(7)(iii) .......................................
Averaging Time for COM during Performance Test.
COM Requirements ............................
COMS Results and Visual Observations.
Determining Compliance with Opacity/VE Standards.
Adjusted Opacity Standard ................
Extension of Compliance ...................
Yes .............................
§ 63.6(h)(7)(iv) .......................................
§ 63.6(h)(7)(v) .......................................
§ 63.6(h)(8) ............................................
§ 63.6(h)(9) ............................................
§ 63.6(i)(1)–(14) ....................................
Yes .............................
Yes .............................
Yes .............................
Yes .............................
Yes .............................
§ 63.6(i)(15) ...........................................
§ 63.6(i)(16) ...........................................
§ 63.6(j) .................................................
§ 63.7(a)(1) ............................................
[Reserved] ..........................................
.............................................................
Presidential Compliance Exemption ..
Performance Test Requirements Applicability.
Not applicable ............
Yes .............................
Yes .............................
Yes .............................
§ 63.7(a)(2) ............................................
Performance Test Dates ....................
Yes .............................
§ 63.7(a)(3) ............................................
§ 63.7(a)(4) ............................................
§ 63.7(b) ................................................
Section 114 Authority .........................
Force Majeure ....................................
Notifications ........................................
Yes .............................
Yes .............................
Yes .............................
§ 63.7(c) ................................................
Quality Assurance Program/Site-Specific Test Plan.
Yes .............................
§ 63.7(d) ................................................
§ 63.7(e)(1) ............................................
§ 63.7(e)(2)–(4) .....................................
§ 63.7(f) .................................................
§ 63.7(g) ................................................
Performance Test Facilities ................
Performance Testing ..........................
Conduct of Tests ................................
Alternative Test Method .....................
Data Analysis, Recordkeeping, Reporting.
Yes .............................
No ...............................
Yes .............................
Yes .............................
Yes .............................
§ 63.7(h) ................................................
§ 63.8(a)(1) ............................................
§ 63.8(a)(2) ............................................
§ 63.8(a)(3) ............................................
§ 63.8(a)(4) ............................................
Waiver of Tests ..................................
Monitoring Requirements-Applicability
Performance Specifications ................
[Reserved] ..........................................
Monitoring with Flares ........................
Yes .............................
Yes .............................
Yes .............................
Not applicable ............
Yes .............................
§ 63.8(b)(1) ............................................
§ 63.8(b)(2)–(3) .....................................
Conduct of Monitoring ........................
Multiple Effluents and Multiple Monitoring Systems.
Monitoring System Operation and
Maintenance.
General Duty to Minimize Emissions
and CMS Operation.
Keep Necessary Parts for CMS .........
Requirement to Develop SSM Plan
for CMS.
Yes .............................
Yes .............................
§ 63.8(c)(1) ............................................
tkelley on DSK3SPTVN1PROD with RULES2
§ 63.8(c)(1)(i) .........................................
§ 63.8(c)(1)(ii) ........................................
§ 63.8(c)(1)(iii) .......................................
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00146
Fmt 4701
Explanation
Extension of compliance under
§ 63.6(i)(4) not applicable to a facility that installs catalytic cracking
feed hydrotreating and receives an
extended compliance date under
§ 63.1563(c).
Except that this subpart specifies the
applicable test and demonstration
procedures.
Except test results must be submitted
in the Notification of Compliance
Status report due 150 days after
the compliance date.
Except that this subpart specifies notification at least 30 days prior to
the scheduled test date rather than
60 days.
Except that when this subpart specifies to use 40 CFR part 60, appendix F, out of control periods are to
be defined as specified in part 60,
appendix F.
See § 63.1571(b)(1).
Except performance test reports must
be submitted with notification of
compliance status due 150 days
after the compliance date, and
§ 63.7(g)(2) is reserved and does
not apply.
Except that for a flare complying with
§ 63.670, the cross-reference to
§ 63.11 in this paragraph does not
include § 63.11(b).
This subpart specifies the required
monitoring locations.
Yes .............................
No ...............................
See § 63.1570(c).
Yes .............................
No ...............................
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75323
TABLE 44 TO SUBPART UUU OF PART 63—APPLICABILITY OF NESHAP GENERAL PROVISIONS TO SUBPART UUU—
Continued
Citation
Subject
Applies to subpart
UUU
Explanation
§ 63.8(c)(2)–(3) .....................................
Monitoring System Installation ...........
Yes .............................
Except that this subpart specifies that
for continuous parameter monitoring systems, operational status
verification includes completion of
manufacturer written specifications
or installation, operation, and calibration of the system or other written procedures that provide adequate assurance that the equipment will monitor accurately.
§ 63.8(c)(4) ............................................
Yes .............................
§ 63.8(c)(5) ............................................
§ 63.8(c)(6) ............................................
§ 63.8(c)(7)–(8) .....................................
§ 63.8(d)(1)–(2) .....................................
§ 63.8(d)(3) ............................................
§ 63.8(e) ................................................
Continuous Monitoring System Requirements.
COMS Minimum Procedures ..............
CMS Requirements ............................
CMS Requirements ............................
Quality Control Program for CMS ......
Written Procedures for CMS ..............
CMS Performance Evaluation ............
Yes .............................
Yes .............................
Yes .............................
Yes .............................
No ...............................
Yes .............................
§ 63.8(f)(1)–(5) ......................................
Alternative Monitoring Methods ..........
Yes .............................
§ 63.8(f)(6) .............................................
Alternative to Relative Accuracy Test
Yes .............................
§ 63.8(g)(1)–(4) .....................................
Reduction of Monitoring Data ............
Yes .............................
§ 63.8(g)(5) ............................................
§ 63.9(a) ................................................
Data Reduction ...................................
Notification Requirements—Applicability.
No ...............................
Yes .............................
§ 63.9(b)(1)–(2) .....................................
Initial Notifications ..............................
Yes .............................
§ 63.9(b)(3) ............................................
§ 63.9(b)(4)–(5) .....................................
[Reserved] ..........................................
Initial Notification Information .............
Not applicable ............
Yes .............................
§ 63.9(c) ................................................
§ 63.9(d) ................................................
Request for Extension of Compliance
New Source Notification for Special
Compliance Requirements.
Notification of Performance Test ........
Yes .............................
Yes .............................
§ 63.9(e) ................................................
§ 63.9(f) .................................................
§ 63.9(g) ................................................
tkelley on DSK3SPTVN1PROD with RULES2
§ 63.9(h) ................................................
§ 63.9(i) .................................................
§ 63.9(j) .................................................
63.10(a) .................................................
§ 63.10(b)(1) ..........................................
VerDate Sep<11>2014
23:11 Nov 30, 2015
Yes .............................
Notification of VE/Opacity Test ..........
Additional Notification Requirements
for Sources with Continuous Monitoring Systems.
Notification of Compliance Status ......
Except § 63.9(b)(4)(ii)–(iv), which are
reserved and do not apply.
Except that notification is required at
least 30 days before test.
Yes .............................
Yes .............................
Adjustment of Deadlines ....................
Change in Previous Information .........
Recordkeeping and Reporting Applicability.
General Recordkeeping Requirements.
Except that results are to be submitted as part of the Notification
Compliance Status due 150 days
after the compliance date.
Except that this subpart specifies procedures for requesting alternative
monitoring systems and alternative
parameters.
Applicable to continuous emission
monitoring systems if performance
specification requires a relative accuracy test audit.
Applies to continuous opacity monitoring system or continuous emission monitoring system.
This subpart specifies requirements.
Duplicate Notification of Compliance
Status report to the Regional Administrator may be required.
Except that notification of construction
or reconstruction is to be submitted
as soon as practicable before startup but no later than 30 days after
the effective date if construction or
reconstruction had commenced but
startup had not occurred before the
effective date.
Yes .............................
Yes .............................
Yes .............................
Jkt 238001
PO 00000
Frm 00147
Fmt 4701
Yes .............................
Except that this subpart specifies the
notification is due no later than 150
days after compliance date, and
except that the reference to
§ 63.5(d)(1)(ii)(H) in § 63.9(h)(5)
does not apply.
Yes .............................
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
75324
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
TABLE 44 TO SUBPART UUU OF PART 63—APPLICABILITY OF NESHAP GENERAL PROVISIONS TO SUBPART UUU—
Continued
Citation
Subject
Applies to subpart
UUU
§ 63.10(b)(2)(i) ......................................
Recordkeeping of Occurrence and
Duration of Startups and Shutdowns.
Recordkeeping of Malfunctions ..........
No ...............................
§ 63.10(b)(2)(ii) ......................................
§ 63.10(b)(2)(iii) .....................................
§ 63.10(b)(2)(iv)–(v) ..............................
§ 63.10(b)(2)(vi) .....................................
§ 63.10(b)(2)(vii)–(xiv) ...........................
§ 63.10(b)(3) ..........................................
§ 63.10(c)(1)–(6) ...................................
§ 63.10(c)(7)–(8) ...................................
§ 63.10(c)(9) ..........................................
§ 63.10(c)(10) ........................................
§ 63.10(c)(11) ........................................
§ 63.10(c)(12)–(14) ...............................
Maintenance Records ........................
Actions Taken to Minimize Emissions
During SSM.
Recordkeeping for CMS Malfunctions
Other CMS Requirements ..................
Recordkeeping for Applicability Determinations..
Additional Records for Continuous
Monitoring Systems.
Additional Recordkeeping Requirements
for
CMS—Identifying
Exceedances and Excess Emissions.
[Reserved] ..........................................
Recording Nature and Cause of Malfunctions.
Recording Corrective Actions .............
No ...............................
Yes .............................
Yes .............................
Yes .............................
Yes .............................
Not applicable ............
No ...............................
No ...............................
No ...............................
Yes .............................
No ...............................
§ 63.10(d)(3) ..........................................
§ 63.10(d)(4) ..........................................
§ 63.10(d)(5) ..........................................
Opacity or VE Observations ...............
Progress Reports ...............................
SSM Reports ......................................
Yes .............................
Yes .............................
No ...............................
§ 63.10(e)(1)–(2) ...................................
Additional CMS Reports .....................
Yes .............................
§ 63.10(e)(3) ..........................................
Excess Emissions/CMS Performance
Reports.
COMS Data Reports ..........................
Recordkeeping/Reporting Waiver ......
Control Device and Work Practice
Requirements Applicability.
Flares ..................................................
No ...............................
tkelley on DSK3SPTVN1PROD with RULES2
§ 63.11(c)–(e) ........................................
§ 63.12
§ 63.13
§ 63.14
§ 63.15
..................................................
..................................................
..................................................
..................................................
§ 63.16 ..................................................
VerDate Sep<11>2014
23:11 Nov 30, 2015
Alternative Work Practice for Monitoring Equipment for Leaks.
State Authority and Delegations ........
Addresses ...........................................
Incorporation by Reference ................
Availability of Information and Confidentiality.
Performance Track Provisions ...........
Jkt 238001
PO 00000
Frm 00148
Fmt 4701
Except § 63.10(c)(2)–(4), which are
Reserved and do not apply.
Yes .............................
§ 63.10(c)(15) ........................................
§ 63.10(d)(1) ..........................................
§ 63.10(d)(2) ..........................................
§ 63.11(b) ..............................................
See § 63.1576(a)(2) for recordkeeping
of (1) date, time and duration; (2)
listing of affected source or equipment, and an estimate of the volume of each regulated pollutant
emitted over the standard; and (3)
actions taken to minimize emissions and correct the failure.
Yes .............................
No ...............................
Additional CMS Recordkeeping Requirements.
Use of SSM Plan ................................
General Reporting Requirements ......
Performance Test Results ..................
§ 63.10(e)(4) ..........................................
§ 63.10(f) ...............................................
§ 63.11(a) ..............................................
Explanation
See § 63.1576(a)(2) for malfunctions
recordkeeping requirements.
See § 63.1576(a)(2) for malfunctions
recordkeeping requirements.
Yes .............................
This subpart requires performance
test results to be reported as part
of the Notification of Compliance
Status due 150 days after the compliance date.
See § 63.1575(d) for CPMS malfunction reporting and § 63.1575(e) for
COMS and CEMS malfunction reporting.
Except that reports of performance
evaluations must be submitted in
Notification of Compliance Status.
This subpart specifies the applicable
requirements.
Yes .............................
Yes .............................
Yes .............................
Yes .............................
Except that flares complying with
§ 63.670 are not subject to the requirements of § 63.11(b).
Yes .............................
Yes
Yes
Yes
Yes
.............................
.............................
.............................
.............................
Yes .............................
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
88. Appendix A to subpart UUU of
part 63 is amended by revising the first
sentence of section 2.1 and section 7.1.3
to read as follows:
■
Appendix A to Subpart UUU of Part
63—Determination of Metal
Concentration on Catalyst Particles
(Instrumental Analyzer Procedure)
*
*
*
*
*
2.1 A representative sample of catalyst
particles is collected, prepared, and analyzed
for analyte concentration using either energy
or wavelength dispersive X-ray fluorescent
(XRF) spectrometry instrumental analyzers.
* * *
*
*
*
*
*
7.1.3 Low-Range Calibration Standard.
Concentration equivalent to 1 to 20 percent
of the span. The concentration of the lowrange calibration standard should be selected
so that it is less than either one-fourth of the
applicable concentration limit or of the
lowest concentration anticipated in the
catalyst samples.
*
*
*
*
*
89. Appendix A to part 63 is amended
by adding Method 325A and Method
325B in numerical order to read as
follows:
■
Appendix A to Part 63—Test Methods
Pollutant Measurement Methods From
Various Waste Media
*
*
*
*
*
tkelley on DSK3SPTVN1PROD with RULES2
Method 325A—Volatile Organic
Compounds from Fugitive and Area Sources:
Sampler Deployment and VOC Sample
Collection
1.0 Scope and Application
1.1 This method describes collection of
volatile organic compounds (VOCs) at or
inside a facility property boundary or from
fugitive and area emission sources using
passive (diffusive) tube samplers (PS). The
concentration of airborne VOCs at or near
these potential fugitive- or area-emission
sources may be determined using this
method in combination with Method 325B.
Companion Method 325B (Sampler
Preparation and Analysis) describes
preparation of sampling tubes, shipment and
storage of exposed sampling tubes, and
analysis of sampling tubes collected using
either this passive sampling procedure or
alternative active (pumped) sampling
methods.
1.2 This method may be used to
determine the average concentration of the
select VOCs using the corresponding uptake
rates listed in Method 325B, Table 12.1.
Additional compounds or alternative
sorbents must be evaluated as described in
Addendum A of Method 325B or by one of
the following national/international standard
methods: ISO 16017–2:2003(E), ASTM
D6196–03 (Reapproved 2009), or BS EN
14662–4:2005 (all incorporated by
reference—see § 63.14), or reported in the
peer-reviewed open literature.
1.3 Methods 325A and 325B are valid for
the measurement of benzene. Supporting
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
literature (References 1–8) indicates that
benzene can be measured by flame ionization
detection or mass spectrometry over a
concentration range of approximately 0.5
micrograms per cubic meter (mg/m3) to at
least 500 mg/m3 when industry standard (3.5
inch long × 0.25 inch outside diameter (o.d.)
× 5 mm inner diameter (i.d.)) inert-coated
stainless steel sorbent tubes packed with
CarbographTM 1 TD, CarbopackTM B, or
CarbopackTM X or equivalent are used and
when samples are accumulated over a period
of 14 days.
1.4 This method may be applied to
screening average airborne VOC
concentrations at facility property boundaries
or monitoring perimeters over an extended
period of time using multiple sampling
periods (e.g., 26 × 14-day sampling periods).
The duration of each sampling period is
normally 14 days.
1.5 This method requires the collection of
local meteorological data (wind speed and
direction, temperature, and barometric
pressure). Although local meteorology is a
component of this method, non-regulatory
applications of this method may use regional
meteorological data. Such applications risk
that the results may not identify the precise
source of the emissions.
2.0
Summary of the Method
2.1 Principle of the Method
The diffusive passive sampler collects VOC
from air for a measured time period at a rate
that is proportional to the concentration of
vapor in the air at that location.
2.1.1 This method describes the
deployment of prepared passive samplers,
including determination of the number of
passive samplers needed for each survey and
placement of samplers along or inside the
facility property boundary depending on the
size and shape of the site or linear length of
the boundary.
2.1.2 The rate of sampling is specific to
each compound and depends on the
diffusion constants of that VOC and the
sampler dimensions/characteristics as
determined by prior calibration in a standard
atmosphere (Reference 1).
2.1.3 The gaseous VOC target compounds
migrate through a constant diffusion barrier
(e.g., an air gap of fixed dimensions) at the
sampling end of the diffusion sampling tube
and adsorb onto the sorbent.
2.1.4 Heat and a flow of inert carrier gas
are then used to extract (desorb) the retained
VOCs back from the sampling end of the tube
and transport/transfer them to a gas
chromatograph (GC) equipped with a
chromatographic column to separate the
VOCs and a detector to determine the
quantity of target VOCs.
2.1.5 Gaseous or liquid calibration
standards loaded onto the sampling ends of
clean sorbent tubes must be used to calibrate
the analytical equipment.
2.1.6 This method requires the use of
field blanks to ensure sample integrity
associated with shipment, collection, and
storage of the passive samples. It also
requires the use of field duplicates to validate
the sampling process.
2.1.7 At the end of each sampling period,
the passive samples are collected, sealed, and
PO 00000
Frm 00149
Fmt 4701
Sfmt 4700
75325
shipped to a laboratory for analysis of target
VOCs by thermal desorption gas
chromatography, as described in Method
325B.
2.2 Application of Diffusive Sampling
2.2.1 This method requires deployment of
passive sampling tubes on a monitoring
perimeter encompassing all known emission
sources at a facility and collection of local
meteorological data. It may be used to
determine average concentration of VOC at a
facility’s ‘‘fenceline’’ using time integrated
passive sampling (Reference 2).
2.2.2 Collecting samples and
meteorological data at progressively higher
frequencies may be employed to resolve
shorter term concentration fluctuations and
wind conditions that could introduce
interfering emissions from other sources.
2.2.3 This passive sampling method
provides a low cost approach to screening of
fugitive or area emissions compared to active
sampling methods that are based on pumped
sorbent tubes or time weighted average
canister sampling.
2.2.3.1 Additional passive sampling tubes
may be deployed at different distances from
the facility property boundary or from the
geometric center of the fugitive emission
source.
2.2.3.2 Additional meteorological
measurements may also be collected as
needed to perform preliminary gradientbased assessment of the extent of the
pollution plume at ground level and the
effect of ‘‘background’’ sources contributing
to airborne VOC concentrations at the
location.
2.2.4 Time-resolved concentration
measurements coupled with time-resolved
meteorological monitoring may be used to
generate data needed for source
apportionment procedures and mass flux
calculations.
3.0 Definitions
(See also Section 3.0 of Method 325B.)
3.1 Fenceline means the property
boundary of a facility or internal monitoring
perimeter established in accordance with the
requirements in Section 8.2 of this method.
3.2 Passive sampler (PS) means a specific
type of sorbent tube (defined in this method)
that has a fixed dimension air (diffusion) gap
at the sampling end and is sealed at the other
end.
3.3 Passive sampling refers to the activity
of quantitatively collecting VOC on sorbent
tubes using the process of diffusion.
3.4 PSi is the annual average for all PS
concentration results from location i.
3.5 PSi3 is the set of annual average
concentration results for PSi and two sorbent
tubes nearest to the PS location i.
3.6 PSip is the concentration from the
sorbent tube at location i for the test period
or episode p.
3.7 Sampling period is the length of time
each passive sampler is exposed during field
monitoring. The sampling period for this
method is 14 days.
3.8 Sorbent tube (Also referred to as tube,
PS tube, adsorbent tube, and sampling tube)
is an inert coated stainless steel tube.
Standard PS tube dimensions for this method
E:\FR\FM\01DER2.SGM
01DER2
75326
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
are 3.5-inch (89 mm) long × 0.25-inch (6.4
mm) o.d. with an i.d. of 5 mm, a crosssectional area of 19.6 mm2 and an air gap of
15 mm. The central portion of the tube is
packed with solid adsorbent material
contained between 2 × 100-mesh stainless
steel gauzes and terminated with a diffusion
cap at the sampling end of the tube. These
axial passive samplers are installed under a
protective hood during field deployment.
Note: Glass and glass- (or fused silica-)
lined stainless steel sorbent tubes (typically
4 mm i.d.) are also available in various
lengths to suit different makes of thermal
desorption equipment, but these are rarely
used for passive sampling because it is more
difficult to adequately define the diffusive air
gap in glass or glass-line tubing. Such tubes
are not recommended for this method.
4.0
Sampling Interferences
4.1 General Interferences
Passive tube samplers should be sited at a
distance beyond the influence of possible
obstructions such as trees, walls, or buildings
at the monitoring site. Complex topography
and physical site obstructions, such as bodies
of water, hills, buildings, and other structures
that may prevent access to a planned PS
location must be taken into consideration.
You must document and report siting
interference with the results of this method.
4.2 Background Interference
Nearby or upwind sources of target
emissions outside the facility being tested
can contribute to background concentrations.
Moreover, because passive samplers measure
continuously, changes in wind direction can
cause variation in the level of background
concentrations from interfering sources
during the monitoring period. This is why
local meteorological information, particularly
wind direction and speed, is required to be
collected throughout the monitoring period.
Interfering sources can include neighboring
industrial facilities, transportation facilities,
fueling operations, combustion sources,
short-term transient sources, residential
sources, and nearby highways or roads. As
PS data are evaluated, the location of
potential interferences with respect to PS
locations and local wind conditions should
be considered, especially when high PS
concentration values are observed.
tkelley on DSK3SPTVN1PROD with RULES2
4.3 Tube Handling
You must protect the PS tubes from gross
external contamination during field
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
sampling. Analytical thermal desorption
equipment used to analyze PS tubes must
desorb organic compounds from the interior
of PS tubes and exclude contamination from
external sampler surfaces in the analytical/
sample flow path. If the analytical equipment
does not comply with this requirement, you
must wear clean, white, cotton or powderfree nitrile gloves to handle sampling tubes
to prevent contamination of the external
sampler surfaces. Sampling tubes must be
capped with two-piece, brass, 0.25 inch,
long-term storage caps fitted with combined
polytetrafluoroethylene ferrules (see Section
6.1 and Method 325B) to prevent ingress of
airborne contaminants outside the sampling
period. When not being used for field
monitoring, the capped tubes must be stored
in a clean, air-tight, shipping container to
prevent the collection of VOCs (see Section
6.4.2 of Method 325B).
4.4 Local Weather Conditions and
Airborne Particulates
Although air speeds are a constraint for
many forms of passive samplers, axial tube
PS devices have such a slow inherent uptake
rate that they are largely immune to these
effects (References 4,5). Passive samplers
must nevertheless be deployed under nonemitting weatherproof hoods to moderate the
effect of local weather conditions such as
solar heating and rain. The cover must not
impede the ingress of ambient air. Sampling
tubes should also be orientated vertically and
pointing downwards, to minimize
accumulation of particulates.
4.5 Temperature
The normal working range for field
sampling for sorbent packing is 0–40 °C
(References 6,7). Note that most published
passive uptake rate data for sorbent tubes is
quoted at 20 °C. Note also that, as a rough
guide, an increase in temperature of 10 °C
will reduce the collection capacity for a given
analyte on a given sorbent packing by a factor
of 2, but the uptake rate will not change
significantly (Reference 4).
5.0 Safety
This method does not purport to include
all safety issues or procedures needed when
deploying or collecting passive sampling
tubes. Precautions typical of field air
sampling projects are required. Tripping,
falling, electrical, and weather safety
considerations must all be included in plans
to deploy and collect passive sampling tubes.
PO 00000
Frm 00150
Fmt 4701
Sfmt 4700
6.0 Sampling Equipment and Supplies, and
Pre-Deployment Planning
This section describes the equipment and
supplies needed to deploy passive sampling
monitoring equipment at a facility property
boundary. Details of the passive sampling
tubes themselves and equipment required for
subsequent analysis are described in Method
325B.
6.1
Passive Sampling Tubes
The industry standard PS tubes used in
this method must meet the specific
configuration and preparation requirements
described in Section 3.0 of this method and
Section 6.1 of Method 325B.
Note: The use of PS tubes packed with
various sorbent materials for monitoring a
wide variety of organic compounds in
ambient air has been documented in the
literature (References 4–10). Other sorbents
may be used in standard passive sampling
tubes for monitoring additional target
compound(s) once their uptake rate and
performance has been demonstrated
following procedures in Addendum A to
Method 325B. Guidance on sorbent selection
can also be obtained from relevant national
and international standard methods such as
ASTM D6196–03 (Reapproved 2009)
(Reference 14) and ISO 16017–2:2003(E)
(Reference 13) (both incorporated by
reference—see § 63.14).
6.2
Passive or Diffusive Sampling Cap
One diffusive sampling cap is required per
PS tube. The cap fits onto the sampling end
of the tube during air monitoring. The other
end of the tube remains sealed with the longterm storage cap. Each diffusive sampling cap
is fitted with a stainless steel gauze, which
defines the outer limit of the diffusion air
gap.
6.3
Sorbent Tube Protection Cover
A simple weatherproof hood, suitable for
protecting passive sampling tubes from the
worst of the weather (see Section 4.4)
consists of an inverted cone/funnel
constructed of an inert, non-outgassing
material that fits over the diffusive tube, with
the open (sampling) end of the tube
projecting just below the cone opening. An
example is shown in Figure 6.1 (Adapted
from Reference 13).
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Thermal Desorption Apparatus
If the analytical thermal desorber that will
subsequently be used to analyze the passive
sampling tubes does not meet the
requirement to exclude outer surface
contaminants from the sample flow path (see
Section 6.6 of Method 325B), then clean,
white, cotton or powder-free nitrile gloves
must be used for handling the passive
sampling tubes during field deployment.
6.5
Sorbent Selection
Sorbent tube configurations, sorbents or
other VOC not listed in this method must be
evaluated according to Method 325B,
Addendum A or ISO 16017–2:2003(E)
(Reference 13) (incorporated by reference—
see § 63.14). The supporting evaluation and
verification data described in Method 325B,
Addendum A for configurations or
compounds different from the ones described
in this method must meet the performance
requirements of Method 325A/B and must be
submitted with the test plan for your
measurement program.
7.0
Reagents and Standards
No reagents or standards are needed for the
field deployment and collection of passive
sampling tubes. Specifications for sorbents,
gas and liquid phase standards, preloaded
standard tubes, and carrier gases are covered
in Section 7 of Method 325B.
tkelley on DSK3SPTVN1PROD with RULES2
8.0 Sample Deployment, Recovery, and
Storage
Pre-deployment and planning steps are
required before field deployment of passive
sampling tubes. These activities include but
are not limited to conducting a site visit,
determining suitable and required
monitoring locations, and determining the
monitoring frequency to be used.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
8.1 Conducting the Site Visit
8.1.1 Determine the size and shape of the
facility footprint in order to determine the
required number of monitoring locations.
8.1.2 Identify obstacles or obstructions
(buildings, roads, fences), hills and other
terrain issues (e.g., bodies of water or swamp
land) that could interfere with air parcel flow
to the sampler or that prevent reasonable
access to the location. You may use the
general guidance in Section 4.1 of this
method during the site visit to identify
sampling locations. You must evaluate the
placement of each passive sampler to
determine if the conditions in this section are
met.
8.1.3 Identify to the extent possible and
record potential off-site source interferences
(e.g., neighboring industrial facilities,
transportation facilities, fueling operations,
combustion sources, short-term transient
sources, residential sources, nearby
highways).
8.1.4 Identify the closest available
meteorological station. Identify potential
locations for one or more on-site or near-site
meteorological station(s) following the
guidance in EPA–454/B–08–002 (Reference
11) (incorporated by reference—see § 63.14).
8.2 Determining Sampling Locations
(References 2, 3)
8.2.1 The number and placement of the
passive samplers depends on the size, the
shape of the facility footprint or the linear
distance around the facility, and the
proximity of emission sources near the
property boundaries. Aerial photographs or
site maps may be used to determine the size
(acreage) and shape of the facility or the
length of the monitoring perimeter. Place
passive samplers on an internal monitoring
perimeter on or inside the facility boundary
encompassing all emission sources at the
facility at different angles circling the
PO 00000
Frm 00151
Fmt 4701
Sfmt 4700
geometric center of the facility or at different
distances based on the monitoring perimeter
length of the facility.
Note: In some instances, permanent air
monitoring stations may already be located in
close proximity to the facility. These stations
may be operated and maintained by the site,
or local or state regulatory agencies. If access
to the station is possible, a PS may be
deployed adjacent to other air monitoring
instrumentation. A comparison of the
pollutant concentrations measured with the
PS to concentrations measured by site
instrumentation may be used as an optional
data quality indicator to assess the accuracy
of PS results.
8.2.1.1 The monitoring perimeter may be
located between the property boundary and
any potential emission source near the
property boundary, as long as the distance
from the source to the monitoring perimeter
is at least 50 meters (162 feet). If a potential
emissions source is within 50 meters (162
feet) of the property boundary, the property
boundary shall be used as the monitoring
perimeter near that source.
8.2.1.2 Samplers need only be placed
around the monitoring perimeter and not
along internal roads or other right of ways
that may bisect the facility.
8.2.1.3 Extra samplers must be placed
near known sources of VOCs if the potential
emission source is within 50 meters (162
feet) of the boundary and the source location
is between two monitors. Measure the
distance (x) between the two monitors and
place another monitor halfway between (x/2)
the two monitors. For example, in Figure 8.1,
the facility added three additional monitors
(i.e., light shaded sampler locations) and in
Figure 8.2, the facility added two additional
monitors to provide sufficient coverage of all
area sources.
BILLING CODE 6560–50–P
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.025
6.4
75327
75328
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
~
0
:!::
c
0
E
ro
c
0
:-e
"'0
"'0
<(
Refinery (20% Angle)
Note: Shaded sources are within 50 meters of the property boundary
and are located between two monitors. Additional coverage required
by this method was accomplished by placing the monitors halfway
between two existing monitors.
Figure 8.1. Facility with a Regular Shape Between 750 and 1,500
Acres in Area
(f)
(f)
(f)
(f)
(f)
Refinery (24,000 Feet Perimeter)
Figure 8.2. Facility with a Boundary Length of 24,000 feet
8.2.2 Option 1 for Determining Sampling
Locations.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
8.2.2.1 For facilities with a regular
(circular, triangular, rectangular, or square)
PO 00000
Frm 00152
Fmt 4701
Sfmt 4700
shape, determine the geographic center of the
facility.
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.026
tkelley on DSK3SPTVN1PROD with RULES2
Note: Shaded sources are within 50 meters of the property boundary
and are located between two monitors. Additional coverqe required
by this method was accomplished by placing the monitors halfway
between two existing monitors.
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75329
determine sampling locations. The subareas
must be defined such that a circle can
reasonably encompass the subarea. Then
determine the geometric center point of each
of the subareas.
8.2.2.2.1 If a subarea is less than or equal
to 750 acres (e.g., Figure 8.3), measure angles
of 30 degrees from the center point for a total
of twelve 30 degree measurements (±1
degree).
center for a total of twenty-four 15 degree
measurements (±1 degree).
8.2.2.2.4 Locate each sampling point
where the measured angle intersects the
outer monitoring perimeter. Sampling points
need not be placed closer than 152 meters
(500 feet) apart (or 76 meters (250 feet) if
known sources are within 50 meters (162
feet) of the monitoring perimeter), as long as
a minimum of 3 monitoring locations are
used for each subarea.
8.2.2.2.5 Sampling sites are not needed at
the intersection of an inner boundary with an
adjacent subarea. The sampling location must
be sited where the measured angle intersects
the subarea’s outer monitoring perimeter.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00153
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.027
acres. Monitor placements are represented
with black dots along the property boundary.
8.2.2.1.3 For facilities covering an area
greater than 1,500 acres, measure angles of 15
degrees from the center point for a total of
twenty-four 15 degree measurements evenly
spaced (±1 degree).
8.2.2.1.4 Locate each sampling point
where the measured angle intersects the
outer monitoring perimeter.
8.2.2.2 For irregularly shaped facilities,
divide the area into a set of connecting
subarea circles, triangles or rectangles to
8.2.2.2.2 If a subarea is greater than 750
acres but less than or equal to 1,500 acres
(e.g., Figure 8.4), measure angles of 20
degrees from the center point for a total of
eighteen 20 degree measurements (±1
degree).
8.2.2.2.3 If a subarea is greater than 1,500
acres, measure angles of 15 degrees from the
tkelley on DSK3SPTVN1PROD with RULES2
8.2.2.1.1 For facilities with an area of less
than or equal to 750 acres, measure angles of
30 degrees from the center point for a total
of twelve 30 degree measurements evenly
spaced (±1 degree).
8.2.2.1.2 For facilities covering an area
greater than 750 acres but less than or equal
to 1,500 acres, measure angles of 20 degrees
from the center point for a total of eighteen
20 degree measurements evenly spaced (±1
degree). Figure 8.1 shows the monitor
placement around the property boundary of
a facility with an area between 750 and 1,500
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
8.2.3 Option 2 for Determining Sampling
Locations.
8.2.3.1 For facilities with a monitoring
perimeter length of less than 7,315 meters
(24,000 feet), a minimum of twelve sampling
locations evenly spaced ±10 percent of the
location interval is required.
8.2.3.2 For facilities with a monitoring
perimeter length greater than 7,315 meters
(24,000 feet), sampling locations are spaced
610 ±76 meters (2,000 ± 250 feet) apart.
8.3 Siting a Meteorological Station
A meteorological station is required at or
near the facility you are monitoring. A
number of commercially available
meteorological stations can be used.
Information on meteorological instruments
can be found in EPA–454/R–99–005
(Reference 11) (incorporated by reference—
see § 63.14). Some important considerations
for siting of meteorological stations are
detailed below.
8.3.1 Place meteorological stations in
locations that represent conditions affecting
the transport and dispersion of pollutants in
the area of interest. Complex terrain may
require the use of more than one
meteorological station.
8.3.2 Deploy wind instruments over level,
open terrain at a height of 10 meters (33 feet).
If possible, locate wind instruments at a
distance away from nearby structures that is
equal to at least 10 times the height of the
structure.
8.3.3 Protect meteorological instruments
from thermal radiation and adequately
ventilate them using aspirated shields. The
temperature sensor must be located at a
distance away from any nearby structures
that is equal to at least four times the height
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
of the structure. Temperature sensors must be
located at least 30 meters (98 feet) from large
paved areas.
8.3.4 Collect and record meteorological
data, including wind speed, wind direction,
temperature and barometric pressure on an
hourly basis. Calculate average unit vector
wind direction, sigma theta, temperature and
barometric pressure per sampling period to
enable calculation of concentrations at
standard conditions. Supply this information
to the laboratory.
8.3.5 Identify and record the location of
the meteorological station by its GPS
coordinate.
8.4 Monitoring Frequency
8.4.1 Sample collection may be
performed for periods up to 14 days.
8.4.2 A site screening protocol that meets
method requirements may be performed by
collecting samples for a year where each PS
accumulates VOC for a 14-day sampling
period. Study results are accumulated for the
sampling periods (typically 26) over the
course of one calendar year. To the extent
practical, sampling tubes should be changed
at approximately the same time of day at
each of the monitoring sites.
8.5 Passive Sampler Deployment
8.5.1 Clean (conditioned) sorbent tubes
must be prepared and packaged by the
laboratory as described in Method 325B and
must be deployed for sampling within 30
days of conditioning.
8.5.2 Allow the tubes to equilibrate with
ambient temperature (approximately 30
minutes to 1 hour) at the monitoring location
before removing them from their storage/
shipping container for sample collection.
PO 00000
Frm 00154
Fmt 4701
Sfmt 4700
8.5.3 If there is any risk that the
analytical equipment will not meet the
requirement to exclude contamination on
outer tube surfaces from the sample flow
path (see Section 6.6 of Method 325B),
sample handlers must wear clean, white,
cotton or powder-free nitrile gloves during
PS deployment and collection and
throughout any other tube handling
operations.
8.5.4 Inspect the sampling tubes
immediately prior to deployment. Ensure
that they are intact, securely capped, and in
good condition. Any suspect tubes (e.g.,
tubes that appear to have leaked sorbent)
should be removed from the sampling set.
8.5.5 Secure passive samplers so the
bottom of the diffusive sampling cap is 1.5
to 3 meters (4.9 to 9.8 feet) above ground
using a pole or other secure structure at each
sampling location. Orient the PS vertically
and with the sampling end pointing
downward to avoid ingress of particulates.
Note: Duplicate sampling assemblies must
be deployed in at least one monitoring
location for every 10 monitoring locations
during each field monitoring period.
8.5.6 Protect the PS from rain and
excessive wind velocity by placing them
under the type of protective hood described
in Section 6.1.3 or equivalent.
8.5.7 Remove the storage cap on the
sampling end of the tube and replace it with
a diffusive sampling cap at the start of the
sampling period. Make sure the diffusion cap
is properly seated and store the removed
storage caps in the empty tube shipping
container.
8.5.8 Record the start time and location
details for each sampler on the field sample
data sheet (see example in Section 17.0.).
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.028
75330
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
8.6 Sorbent Tube Recovery and
Meteorological Data Collection
Recover deployed sampling tubes and field
blanks as follows:
8.6.1 After the sampling period is
complete, immediately replace the diffusion
end cap on each sampled tube with a longterm storage end cap. Tighten the seal
securely by hand and then tighten an
additional quarter turn with an appropriate
tool. Record the stop date and time and any
additional relevant information on the
sample data sheet.
8.6.2 Place the sampled tubes, together
with the field blanks, in the storage/shipping
container. Label the storage container, but do
not use paints, markers, or adhesive labels to
identify the tubes. TD-compatible electronic
(radio frequency identification (RFID)) tube
labels are available commercially and are
compatible with some brands of thermal
desorber. If used, these may be programmed
with relevant tube and sample information,
which can be read and automatically
transcribed into the sequence report by the
TD system.
Note: Sampled tubes must not be placed in
the same shipping container as clean
conditioned sampling tubes.
8.6.3 Sampled tubes may be shipped at
ambient temperature to a laboratory for
sample analysis.
8.6.4 Specify whether the tubes are field
blanks or were used for sampling and
document relevant information for each tube
using a Chain of Custody form (see example
in Section 17.0) that accompanies the
samples from preparation of the tubes
through receipt for analysis, including the
tkelley on DSK3SPTVN1PROD with RULES2
Where:
PSi = Annual average for location i.
PSip = Sampling period specific
concentration from Method 325B.
i = Location of passive sampler (0 to 360°).
p = The sampling period.
N = The number of sampling periods in the
year (e.g., for 14-day sampling periods,
from 1 to 26).
Note: PSip is a function of sampling
location-specific factors such as the
contribution from facility sources, unusual
localized meteorological conditions,
contribution from nearby interfering sources,
the background caused by integrated far-field
sources and measurement error due to
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
following information: Unique tube
identification numbers for each sampled
tube; the date, time, and location code for
each PS placement; the date, time, and
location code for each PS recovery; the GPS
reference for each sampling location; the
unique identification number of the
duplicate sample (if applicable); and
problems or anomalies encountered.
8.6.5 If the sorbent tubes are supplied
with electronic (e.g., RFID) tags, it is also
possible to allocate a sample identifier to
each PS tube. In this case, the recommended
format for the identification number of each
sampled tube is AA–BB–CC–DD–VOC,
where:
AA = Sequence number of placement on
route (01, 02, 03 . . .)
BB = Sampling location code (01, 02,
03 . . .)
CC = 14-day sample period number (01 to 26)
DD = Sample code (SA = sample, DU =
duplicate, FB = field blank)
VOC = 3-letter code for target compound(s)
(e.g., BNZ for benzene or BTX for
benzene, toluene, and xylenes)
Note: Sampling start and end times/dates
can also be logged using RFID tube tags.
9.0 Quality Control
9.1 Most quality control checks are
carried out by the laboratory and associated
requirements are in Section 9.0 of Method
325B, including requirements for laboratory
blanks, field blanks, and duplicate samples.
9.2 Evaluate for potential outliers the
laboratory results for neighboring sampling
tubes collected over the same time period. A
potential outlier is a result for which one or
more PS tube does not agree with the trend
in results shown by neighboring PS tubes—
particularly when data from those locations
have been more consistent during previous
sampling periods. Accidental contamination
by the sample handler must be documented
before any result can be eliminated as an
outlier. Rare but possible examples of
contamination include loose or missing
storage caps or contaminated storage/
shipping containers. Review data from the
same and neighboring monitoring locations
deployment, handling, siting, or analytical
errors.
12.2 Identify Sampling Locations of
Interest
If data from neighboring sampling
locations are significantly different, then you
may add extra sampling points to isolate
background contributions or identify facilityspecific ‘‘hot spots.’’
12.3
Evaluate Trends
You may evaluate trends and patterns in
the PS data over multiple sampling periods
to determine if elevated concentrations of
target compounds are due to operations on
PO 00000
Frm 00155
Fmt 4701
Sfmt 4700
for the subsequent sampling periods. If the
anomalous result is not repeated for that
monitoring location, the episode can be
ascribed to transient contamination and the
data in question must be flagged for potential
elimination from the dataset.
9.3
Duplicates and Field Blanks
9.3.1 Collect at least one co-located/
duplicate sample for every 10 field samples
to determine precision of the measurements.
9.3.2 Collect at least two field blanks
sorbent samples per sampling period to
ensure sample integrity associated with
shipment, collection, and storage. You must
use the entire sampling apparatus for field
blanks including unopened sorbent tubes
mounted in protective sampling hoods. The
tube closures must not be removed. Field
blanks must be placed in two different
quadrants (e.g., 90° and 270°) and remain at
the sampling location for the sampling
period.
10.0
Calibration and Standardization
Follow the calibration and standardization
procedures for meteorological measurements
in EPA–454/B–08–002 March 2008
(Reference 11) (incorporated by reference—
see § 63.14). Refer to Method 325B for
calibration and standardization procedures
for analysis of the passive sampling tubes.
11.0
Analytical Procedures
Refer to Method 325B, which provides
details for the preparation and analysis of
sampled passive monitoring tubes
(preparation of sampling tubes, shipment and
storage of exposed sampling tubes, and
analysis of sampling tubes).
12.0 Data Analysis, Calculations and
Documentation
12.1 Calculate Annual Average Fenceline
Concentration.
After a year’s worth of sampling at the
facility fenceline (for example, 26 14-day
samples), the average (PSi) may be calculated
for any specified period at each PS location
using Equation 12.1.
the facility or if contributions from
background sources are significant.
12.3.1 Obtain meteorological data
including wind speed and wind direction or
unit vector wind data from the on-site
meteorological station. Use this
meteorological data to determine the
prevailing wind direction and speed during
the periods of elevated concentrations.
12.3.2 As an option you may perform
preliminary back trajectory calculations
(https://ready.arl.noaa.gov/HYSPLIT.php) to
aid in identifying the source of the
background contribution to elevated target
compound concentrations.
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.029
8.5.9 Expose the sampling tubes for the
required sampling period-normally 14-days.
8.5.10 Field blank tubes (see Section 9.3
of Method 325B) are stored outside the
shipping container at representative
sampling locations around the site, but with
both long-term storage caps kept in place
throughout the monitoring exercise. Collect
at least two field blanks sorbent samples per
sampling period to ensure sample integrity
associated with shipment, collection, and
storage.
75331
75332
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
12.3.3 Information on published or
documented events on- and off-site may also
be included in the associated sampling
period report to explain elevated
concentrations if relevant. For example, you
would describe if there was a chemical spill
on site, or an accident on an adjacent road.
12.3.4 Additional monitoring for shorter
periods (See section 8.4) may be necessary to
allow better discrimination/resolution of
contributing emission sources if the
measured trends and associated meteorology
do not provide a clear assessment of facility
contribution to the measured fenceline
concentration.
12.3.5 Additional records necessary to
calculate sampling period average target
compound concentration can be found in
Section 12.1 of Method 325B.
13.0 Method Performance
Method performance requirements are
described in Method 325B.
14.0 Pollution Prevention
[Reserved]
15.0 Waste Management
[Reserved]
tkelley on DSK3SPTVN1PROD with RULES2
16.0 References
1. Ambient air quality—Standard method for
measurement of benzene
concentrations—Part 4: Diffusive
sampling followed by thermal desorption
and gas chromatography, BS EN 14662–
4:2005.
2. Thoma, E.D., Miller, C.M., Chung, K.C.,
Parsons, N.L. and Shine, B.C. Facility
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Fence Line Monitoring using Passive
Samplers, J. Air & Waste Mange. Assoc.
2011, 61:834–842.
3. Quality Assurance Handbook for Air
Pollution C Systems, Volume II: Ambient
Air Quality Monitoring Program, EPA–
454/B–13–003, May 2013. Available at
https://www.epa.gov/ttnamti1/files/
ambient/pm25/qa/QA-Handbook-VolII.pdf.
4. Brown, R.H., Charlton, J. and Saunders,
K.J.: The development of an improved
diffusive sampler. Am. Ind. Hyg. Assoc.
J. 1981, 42(12): 865–869.
5. Brown, R. H. Environmental use of
diffusive samplers: evaluation of reliable
diffusive uptake rates for benzene,
toluene and xylene. J. Environ. Monit.
1999, 1 (1), 115–116.
6. Ballach, J.; Greuter, B.; Schultz, E.;
Jaeschke, W. Variations of uptake rates in
benzene diffusive sampling as a function
of ambient conditions. Sci. Total
Environ. 1999, 244, 203–217.
7. Brown, R. H. Monitoring the ambient
environment with diffusive samplers:
theory and practical considerations. J
Environ. Monit. 2000, 2 (1), 1–9.
8. Buzica, D.; Gerboles, M.; Plaisance, H. The
equivalence of diffusive samplers to
reference methods for monitoring O3,
benzene and NO2 in ambient air. J.
Environ. Monit. 2008, 10 (9), 1052–1059.
9. Woolfenden, E. Sorbent-based sampling
methods for volatile and semi-volatile
organic compounds in air. Part 2.
Sorbent selection and other aspects of
optimizing air monitoring methods. J.
PO 00000
Frm 00156
Fmt 4701
Sfmt 4700
Chromatogr. A 2010, 1217, (16), 2685–
94.
10. Pfeffer, H. U.; Breuer, L. BTX
measurements with diffusive samplers in
the vicinity of a cokery: Comparison
between ORSA-type samplers and
pumped sampling. J. Environ. Monit.
2000, 2 (5), 483–486.
11. US EPA. 2000. Meteorological Monitoring
Guidance for Regulatory Modeling
Applications. EPA–454/R–99–005. Office
of Air Quality Planning and Standards,
Research Triangle Park, NC. February
2000. Available at https://www.epa.gov/
scram001/guidance/met/mmgrma.pdf.
12. Quality Assurance Handbook for Air
Pollution Measurement Systems. Volume
IV: Meteorological Measurements
Version 2.0 Final, EPA–454/B–08–002
March 2008. Available at https://www.
epa.gov/ttnamti1/files/ambient/met/
Volume%20IV_Meteorological_
Measurements.pdf.
13. ISO 16017–2:2003(E), Indoor, ambient
and workplace air—Sampling and
analysis of volatile organic compounds
by sorbent tube/thermal desorption/
capillary gas chromatography. Part 2:
Diffusive sampling.
14. ASTM D6196–03 (Reapproved 2009):
Standard practice for selection of
sorbents, sampling, and thermal
desorption analysis procedures for
volatile organic compounds in air.
17.0 Tables, Diagrams, Flowcharts and
Validation Data
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75333
Method 325 A/B
EXAMPLE FIELD TEST DATA SHEET (FTDS)
AND
CHAIN OF CUSTODY
I. GENERAL INFORMATION
SITE NAME:
SITE LOCATION ADDRESS:
CITY:
STATE:
ZIP:
II. SAMPLING DATA
Sample
ID
(Tube)
#
Sorbent
Sample
or
blank
Start
Date
Start
Time
Stop
Date
Stop
Time
Location
(gps)
Ambient
Temp.
(oF)
Barometric
Pressure
(in. Hg)
III. CUSTODY INFORMATION
COLLECTED BY:
Relinquished to Shipper Name:
Date:
Received by Laboratory Date:
Name
Sample condition upon receipt:
Time
Time
Analysis Required:
Figure 17.1. Example Field Data Form and Chain of Custody
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00157
Fmt 4701
Sfmt 4725
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.030
tkelley on DSK3SPTVN1PROD with RULES2
Comments:
75334
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Method 325B—Volatile Organic Compounds
from Fugitive and Area Sources:
tkelley on DSK3SPTVN1PROD with RULES2
Sampler Preparation and Analysis
1.0 Scope and Application
1.1 This method describes thermal
desorption/gas chromatography (TD/GC)
analysis of volatile organic compounds
(VOCs) from fugitive and area emission
sources collected onto sorbent tubes using
passive sampling. It could also be applied to
the TD/GC analysis of VOCs collected using
active (pumped) sampling onto sorbent tubes.
The concentration of airborne VOCs at or
near potential fugitive- or area-emission
sources may be determined using this
method in combination with Method 325A.
Companion Method 325A (Sampler
Deployment and VOC Sample Collection)
describes procedures for deploying the
sorbent tubes and passively collecting VOCs.
1.2 The preferred GC detector for this
method is a mass spectrometer (MS), but
flame ionization detectors (FID) may also be
used. Other conventional GC detectors such
as electron capture (ECD), photoionization
(PID), or flame photometric (FPD) may also
be used if they are selective and sensitive to
the target compound(s) and if they meet the
method performance criteria provided in this
method.
1.3 There are 97 VOCs listed as
hazardous air pollutants in Title III of the
Clean Air Act Amendments of 1990. Many of
these VOC are candidate compounds for this
method. Compounds with known uptake
rates for CarbographTM 1 TD, CarbopackTM B,
or CarbopackTM X are listed in Table 12.1.
This method provides performance criteria to
demonstrate acceptable performance of the
method (or modifications of the method) for
monitoring one or more of the compounds
listed Table 12.1. If standard passive
sampling tubes are packed with other
sorbents or used for other analytes than those
listed in Table 12.1, then method
performance and relevant uptake rates
should be verified according to Addendum A
to this method or by one of the following
national/international standard methods: ISO
16017–2:2003(E), ASTM D6196–03
(Reapproved 2009), or BS EN 14662–4:2005
(all incorporated by reference—see § 63.14),
or reported in the peer-reviewed open
literature.
1.4 The analytical approach using TD/
GC/MS is based on previously published
EPA guidance in Compendium Method TO–
17 (https://www.epa.gov/ttnamti1/airtox.
html#compendium) (Reference 1), which
describes active (pumped) sampling of VOCs
from ambient air onto tubes packed with
thermally stable adsorbents.
1.5 Inorganic gases not suitable for
analysis by this method include oxides of
carbon, nitrogen and sulfur, ozone (O3), and
other diatomic permanent gases. Other
pollutants not suitable for this analysis
method include particulate pollutants, (i.e.,
fumes, aerosols, and dusts), compounds too
labile (reactive) for conventional GC analysis,
and VOCs that are more volatile than
propane.
2.0 Summary of Method
2.1 This method provides procedures for
the preparation, conditioning, blanking, and
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
shipping of sorbent tubes prior to sample
collection.
2.2 Laboratory and field personnel must
have experience of sampling trace-level
VOCs using sorbent tubes (References 2,5)
and must have experience operating thermal
desorption/GC/multi-detector
instrumentation.
2.3 Key steps of this method as
implemented for each sample tube include:
Stringent leak testing under stop flow,
recording ambient temperature conditions,
adding internal standards, purging the tube,
thermally desorbing the sampling tube,
refocusing on a focusing trap, desorbing and
transferring/injecting the VOCs from the
secondary trap into the capillary GC column
for separation and analysis.
2.4 Water management steps incorporated
into this method include: (a) Selection of
hydrophobic sorbents in the sampling tube;
(b) optional dry purging of sample tubes prior
to analysis; and (c) additional selective
elimination of water during primary (tube)
desorption (if required) by selecting trapping
sorbents and temperatures such that target
compounds are quantitatively retained while
water is purged to vent.
3.0 Definitions
(See also Section 3.0 of Method 325A).
3.1 Blanking is the desorption and
confirmatory analysis of conditioned sorbent
tubes before they are sent for field sampling.
3.2 Breakthrough volume and associated
relation to passive sampling. Breakthrough
volumes, as applied to active sorbent tube
sampling, equate to the volume of air
containing a constant concentration of
analyte that may be passed through a sorbent
tube at a given temperature before a
detectable level (5 percent) of the input
analyte concentration elutes from the tube.
Although breakthrough volumes are directly
related to active rather than passive
sampling, they provide a measure of the
strength of the sorbent-sorbate interaction
and therefore also relate to the efficiency of
the passive sampling process. The best direct
measure of passive sampling efficiency is the
stability of the uptake rate. Quantitative
passive sampling is compromised when the
sorbent no longer acts as a perfect sink—i.e.,
when the concentration of a target analyte
immediately above the sorbent sampling
surface no longer approximates to zero. This
causes a reduction in the uptake rate over
time. If the uptake rate for a given analyte on
a given sorbent tube remains relatively
constant —i.e., if the uptake rate determined
for 48 hours is similar to that determined for
7 or 14 days—the user can be confident that
passive sampling is occurring at a constant
rate. As a general rule of thumb, such ideal
passive sampling conditions typically exist
for analyte:sorbent combinations where the
breakthrough volume exceeds 100 L
(Reference 4).
3.3 Continuing calibration verification
sample (CCV). Single level calibration
samples run periodically to confirm that the
analytical system continues to generate
sample results within acceptable agreement
to the current calibration curve.
3.4 Focusing trap is a cooled, secondary
sorbent trap integrated into the analytical
PO 00000
Frm 00158
Fmt 4701
Sfmt 4700
thermal desorber. It typically has a smaller
i.d. and lower thermal mass than the original
sample tube allowing it to effectively refocus
desorbed analytes and then heat rapidly to
ensure efficient transfer/injection into the
capillary GC analytical column.
3.5 High Resolution Capillary Column
Chromatography uses fused silica capillary
columns with an inner diameter of 320 mm
or less and with a stationary phase film
thickness of 5 mm or less.
3.6 h is time in hours.
3.7 i.d. is inner diameter.
3.8 min is time in minutes.
3.9 Method Detection Limit is the lowest
level of analyte that can be detected in the
sample matrix with 99% confidence.
3.10 MS–SCAN is the mode of operation
of a GC quadrupole mass spectrometer
detector that measures all ions over a given
mass range over a given period of time.
3.11 MS–SIM is the mode of operation of
a GC quadrupole mass spectrometer detector
that measures only a single ion or a selected
number of discrete ions for each analyte.
3.12 o.d. is outer diameter.
3.13 ppbv is parts per billion by volume.
3.14 Thermal desorption is the use of
heat and a flow of inert (carrier) gas to extract
volatiles from a solid matrix. No solvent is
required.
3.15 Total ion chromatogram is the
chromatogram produced from a mass
spectrometer detector collecting full spectral
information.
3.16 Two-stage thermal desorption is the
process of thermally desorbing analytes from
a sorbent tube, reconcentrating them on a
focusing trap (see Section 3.4), which is then
itself rapidly heated to ‘‘inject’’ the
concentrated compounds into the GC
analyzer.
3.17 VOC is volatile organic compound.
4.0 Analytical Interferences
4.1 Interference from Sorbent Artifacts.
Artifacts may include target analytes as well
as other VOC that co-elute
chromatographically with the compounds of
interest or otherwise interfere with the
identification or quantitation of target
analytes.
4.1.1 Sorbent decomposition artifacts are
VOCs that form when sorbents degenerate,
e.g., when exposed to reactive species during
sampling. For example, benzaldehyde,
phenol, and acetophenone artifacts are
reported to be formed via oxidation of the
polymeric sorbent Tenax® when sampling
high concentration (100–500 ppb) ozone
atmospheres (Reference 5).
4.1.2 Preparation and storage artifacts are
VOCs that were not completely cleaned from
the sorbent tube during conditioning or that
are an inherent feature of that sorbent at a
given temperature.
4.2 Humidity. Moisture captured during
sampling can interfere with VOC analysis.
Passive sampling using tubes packed with
hydrophobic sorbents, like those described in
this method, minimizes water retention.
However, if water interference is found to be
an issue under extreme conditions, one or
more of the water management steps
described in Section 2.4 can be applied.
4.3 Contamination from Sample
Handling. The type of analytical thermal
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
6.0 Equipment and Supplies
6.1 Tube Dimensions and Materials. The
sampling tubes for this method are 3.5-inches
(89 mm) long, 1⁄4 inch (6.4 mm) o.d., and 5
6.2 Tube Conditioning Apparatus
6.2.1 Freshly packed or newly purchased
tubes must be conditioned as described in
Section 9 using an appropriate dedicated
tube conditioning unit or the thermal
desorber. Note that the analytical TD system
should be used for tube conditioning if it
supports a dedicated tube conditioning mode
in which effluent from contaminated tubes is
directed to vent without passing through key
parts of the sample flow path such as the
focusing trap.
6.2.2 Dedicated tube conditioning units
must be leak-tight to prevent air ingress,
allow precise and reproducible temperature
selection (±5 °C), offer a temperature range at
least as great as that of the thermal desorber,
and support inert gas flows in the range up
to 100 mL/min.
Note: For safety and to avoid laboratory
contamination, effluent gases from freshly
packed or highly contaminated tubes should
be passed through a charcoal filter during the
conditioning process to prevent desorbed
VOCs from polluting the laboratory
atmosphere.
with relevant tube and sample information,
which can be read and automatically
transcribed into the sequence report by the
TD system (see Section 8.6 of Method 325A).
6.3 Tube Labeling
6.3.1 Label the sample tubes with a
unique permanent identification number and
an indication of the sampling end of the tube.
Labeling options include etching and TDcompatible electronic (radio frequency
identification (RFID)) tube labels.
6.3.2 To avoid contamination, do not
make ink markings of any kind on clean
sorbent tubes or apply adhesive labels.
Note: TD-compatible electronic (RFID) tube
labels are available commercially and are
compatible with some brands of thermal
desorber. If used, these may be programmed
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
6.4 Blank and Sampled Tube Storage
Apparatus
6.4.1 Long-term storage caps. Seal clean,
blank and sampled sorbent tubes using inert,
long-term tube storage caps comprising nongreased, 2-piece, 0.25-inch, metal
SwageLok®-type screw caps fitted with
combined polytetrafluoroethylene ferrules.
6.4.2 Storage and transportation
containers. Use clean glass jars, metal cans or
rigid, non-emitting polymer boxes.
Note: You may add a small packet of new
activated charcoal or charcoal/silica gel to
the shipping container for storage and
transportation of batches of conditioned
sorbent tubes prior to use. Coolers without
ice packs make suitable shipping boxes for
containers of tubes because the coolers help
to insulate the samples from extreme
temperatures (e.g., if left in a parked vehicle).
6.5 Unheated GC Injection Unit for Loading
Standards Onto Blank Tubes
A suitable device has a simple push fit or
finger-tightening connector for attaching the
sampling end of blank sorbent tubes without
damaging the tube. It also has a means of
controlling carrier gas flow through the
injector and attached sorbent tube at 50–100
mL/min and includes a low emission septum
cap that allows the introduction of gas or
liquid standards via appropriate syringes.
Reproducible and quantitative transfer of
higher boiling compounds in liquid
standards is facilitated if the injection unit
PO 00000
Frm 00159
Fmt 4701
Sfmt 4700
mm i.d. passive sampling tubes (see Figure
6.1). The tubes are made of inert-coated
stainless steel with the central section (up to
60 mm) packed with sorbent, typically
supported between two 100 mesh stainless
steel gauze. The tubes have a cross sectional
area of 19.6 square mm (5 mm i.d.). When
used for passive sampling, these tubes have
an internal diffusion (air) gap (DG) of 1.5 cm
between the sorbent retaining gauze at the
sampling end of the tube, and the gauze in
the diffusion cap.
allows the tip of the syringe to just touch the
sorbent retaining gauze inside the tube.
6.6 Thermal Desorption Apparatus
The manual or automated thermal
desorption system must heat sorbent tubes
while a controlled flow of inert (carrier) gas
passes through the tube and out of the
sampling end. The apparatus must also
incorporate a focusing trap to quantitatively
refocus compounds desorbed from the tube.
Secondary desorption of the focusing trap
should be fast/efficient enough to transfer the
compounds into the high resolution capillary
GC column without band broadening and
without any need for further pre- or oncolumn focusing. Typical TD focusing traps
comprise small sorbent traps (Reference 16)
that are electrically-cooled using multistage
Peltier cells (References 17, 18). The
direction of gas flow during trap desorption
should be the reverse of that used for
focusing to extend the compatible analyte
volatility range. Closed cycle coolers offer
another cryogen-free trap cooling option.
Other TD system requirements and
operational stages are described in Section 11
and in Figures 17–2 through 17–4.
6.7 Thermal Desorber—GC Interface
6.7.1 The interface between the thermal
desorber and the GC must be heated
uniformly and the connection between the
transfer line insert and the capillary GC
analytical column itself must be leak tight.
6.7.2 A portion of capillary column can
alternatively be threaded through the heated
transfer line/TD interface and connected
directly to the thermal desorber.
Note: Use of a metal syringe-type needle or
unheated length of fused silica pushed
through the septum of a conventional GC
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.031
standard to establish appropriate field and
laboratory safety and health practices prior to
use.
5.2 Laboratory analysts must exercise
extreme care in working with high-pressure
gas cylinders.
5.3 Due to the high temperatures
involved, operators must use caution when
conditioning and analyzing tubes.
5.0 Safety
5.1 This method does not address all of
the safety concerns associated with its use. It
is the responsibility of the user of this
tkelley on DSK3SPTVN1PROD with RULES2
desorption equipment selected should
exclude the possibility of outer tube surface
contamination entering the sample flow path
(see Section 6.6). If the available system does
not meet this requirement, sampling tubes
and caps must be handled only while
wearing clean, white cotton or powder free
nitrile gloves to prevent contamination with
body oils, hand lotions, perfumes, etc.
75335
75336
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
injector is not permitted as a means of
interfacing the thermal desorber to the
chromatograph. Such connections result in
cold spots, cause band broadening and are
prone to leaks.
6.8 GC/MS Analytical Components
6.8.1 The GC system must be capable of
temperature programming and operation of a
high resolution capillary column. Depending
on the choice of column (e.g., film thickness)
and the volatility of the target compounds, it
may be necessary to cool the GC oven to
subambient temperatures (e.g., ¥50 °C) at the
start of the run to allow resolution of very
volatile organic compounds.
6.8.2 All carrier gas lines supplying the
GC must be constructed from clean stainless
steel or copper tubing. Nonpolytetrafluoroethylene thread sealants. Flow
controllers, cylinder regulators, or other
pneumatic components fitted with rubber
components are not suitable.
6.9 Chromatographic Columns
High-resolution, fused silica or equivalent
capillary columns that provide adequate
separation of sample components to permit
identification and quantitation of target
compounds must be used.
Note: 100-percent methyl silicone or 5percent phenyl, 95-percent methyl silicone
fused silica capillary columns of 0.25- to
0.32-mm i.d. of varying lengths and with
varying thicknesses of stationary phase have
been used successfully for non-polar and
moderately polar compounds. However,
given the diversity of potential target lists,
GC column choice is left to the operator,
subject to the performance criteria of this
method.
6.10 Mass Spectrometer
Linear quadrupole, magnetic sector, ion
trap or time-of-flight mass spectrometers may
be used provided they meet specified
performance criteria. The mass detector must
be capable of collecting data from 35 to 300
atomic mass units (amu) every 1 second or
less, utilizing 70 volts (nominal) electron
energy in the electron ionization mode, and
producing a mass spectrum that meets all the
instrument performance acceptance criteria
in Section 9 when 50 hg or less of pbromofluorobenzene is analyzed.
tkelley on DSK3SPTVN1PROD with RULES2
7.0
Reagents and Standards
7.1 Sorbent Selection
7.1.1 Use commercially packed tubes
meeting the requirements of this method or
prepare tubes in the laboratory using sieved
sorbents of particle size in the range 20 to 80
mesh that meet the retention and quality
control requirements of this method.
7.1.2 This passive air monitoring method
can be used without the evaluation specified
in Addendum A if the type of tubes
described in Section 6.1 are packed with 4–
6 cm (typically 400–650 mg) of the sorbents
listed in Table 12.1 and used for the
respective target analytes.
Note: Although CarbopackTM X is the
optimum sorbent choice for passive sampling
of 1,3-butadiene, recovery of compounds
with vapor pressure lower than benzene may
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
be difficult to achieve without exceeding
sorbent maximum temperature limitations
(see Table 8.1). See ISO 16017–2:2003(E) or
ASTM D6196–03 (Reapproved 2009) (both
incorporated by reference—see § 63.14) for
more details on sorbent choice for air
monitoring using passive sampling tubes.
7.1.3 If standard passive sampling tubes
are packed with other sorbents or used for
analytes other than those tabulated in Section
12.0, method performance and relevant
uptake rates should be verified according to
Addendum A to this method or by following
the techniques described in one of the
following national/international standard
methods: ISO 16017–2:2003(E), ASTM
D6196–03 (Reapproved 2009), or BS EN
14662–4:2005 (all incorporated by
reference—see § 63.14)—or reported in the
peer-reviewed open literature. A summary
table and the supporting evaluation data
demonstrating the selected sorbent meets the
requirements in Addendum A to this method
must be submitted to the regulatory authority
as part of a request to use an alternative
sorbent.
7.1.4 Passive (diffusive) sampling and
thermal desorption methods that have been
evaluated at relatively high atmospheric
concentrations (i.e., mid-ppb to ppm) and
published for use in workplace air and
industrial/mobile source emissions testing
(References 9–20) may be applied to this
procedure. However, the validity of any
shorter term uptake rates must be verified
and adjusted if necessary for the longer
monitoring periods required by this method
by following procedures described in
Addendum A to this method or those
presented in national/international standard
methods: ISO 16017–2:2003(E), ASTM
D6196–03 (Reapproved 2009), or BS EN
14662–4:2005 (all incorporated by referencesee § 63.14).
7.1.5 Suitable sorbents for passive
sampling must have breakthrough volumes of
at least 20 L (preferably >100 L) for the
compounds of interest and must
quantitatively release the analytes during
desorption without exceeding maximum
temperatures for the sorbent or
instrumentation.
7.1.6 Repack/replace the sorbent tubes or
demonstrate tube performance following the
requirements in Addendum A to this method
at least every 2 years or every 50 uses,
whichever occurs first.
7.2 Gas Phase Standards
7.2.1 Static or dynamic standard
atmospheres may be used to prepare
calibration tubes and/or to validate passive
sampling uptake rates and can be generated
from pure chemicals or by diluting
concentrated gas standards. The standard
atmosphere must be stable at ambient
pressure and accurate to ±10 percent of the
target gas concentration. It must be possible
to maintain standard atmosphere
concentrations at the same or lower levels
than the target compound concentration
objectives of the test. Test atmospheres used
for validation of uptake rates must also
contain at least 35 percent relative humidity.
Note: Accurate, low-(ppb-) level gas-phase
VOC standards are difficult to generate from
PO 00000
Frm 00160
Fmt 4701
Sfmt 4700
pure materials and may be unstable
depending on analyte polarity and volatility.
Parallel monitoring of vapor concentrations
with alternative methods, such as pumped
sorbent tubes or sensitive/selective on-line
detectors, may be necessary to minimize
uncertainty. For these reasons, standard
atmospheres are rarely used for routine
calibration.
7.2.2 Concentrated, pressurized gas phase
standards. Accurate (±5 percent or better),
concentrated gas phase standards supplied in
pressurized cylinders may also be used for
calibration. The concentration of the
standard should be such that a 0.5–5.0 mL
volume contains approximately the same
mass of analytes as will be collected from a
typical air sample.
7.2.3 Follow manufacturer’s guidelines
concerning storage conditions and
recertification of the concentrated gas phase
standard. Gas standards must be recertified a
minimum of once every 12 months.
7.3 Liquid Standards
Target analytes can also be introduced to
the sampling end of sorbent tubes in the form
of liquid calibration standards.
7.3.1 The concentration of liquid
standards must be such that an injection of
0.5–2 ml of the solution introduces the same
mass of target analyte that is expected to be
collected during the passive air sampling
period.
7.3.2 Solvent Selection. The solvent
selected for the liquid standard must be pure
(contaminants <10 percent of minimum
analyte levels) and must not interfere
chromatographically with the compounds of
interest.
7.3.3 If liquid standards are sourced
commercially, follow manufacturer’s
guidelines concerning storage conditions and
shelf life of unopened and opened liquid
stock standards.
Note: Commercial VOC standards are
typically supplied in volatile or noninterfering solvents such as methanol.
7.3.4 Working standards must be stored at
6 °C or less and used or discarded within two
weeks of preparation.
7.4 Gas Phase Internal Standards
7.4.1 Gas-phase deuterated or fluorinated
organic compounds may be used as internal
standards for MS-based systems.
7.4.2 Typical compounds include
deuterated toluene, perfluorobenzene and
perfluorotoluene.
7.4.3 Use multiple internal standards to
cover the volatility range of the target
analytes.
7.4.4 Gas-phase standards must be
obtained in pressurized cylinders and
containing vendor certified gas
concentrations accurate to ±5 percent. The
concentration should be such that the mass
of internal standard components introduced
is similar to those of the target analytes
collected during field monitoring.
7.5 Preloaded Standard Tubes
Certified, preloaded standard tubes,
accurate within ±5 percent for each analyte
at the microgram level and ±10 percent at the
nanogram level, are available commercially
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
and may be used for auditing and quality
control purposes. (See Section 9.5 for audit
accuracy evaluation criteria.) Certified
preloaded tubes may also be used for routine
calibration.
Note: Proficiency testing schemes are also
available for TD/GC/MS analysis of sorbent
tubes preloaded with common analytes such
as benzene, toluene, and xylene.
filters must be installed in the carrier gas
lines supplying the analytical system
according to the manufacturer’s instructions.
Keep records of filter and oxygen scrubber
replacement.
7.6 Carrier Gases
Use inert, 99.999-percent or higher purity
helium as carrier gas. Oxygen and organic
75337
8.1.2 New tubes should be conditioned for
2 hours to supplement the vendor’s
conditioning procedure. Recommended
temperatures for tube conditioning are given
in Table 8.1.
8.1.3 After conditioning, the blank must
be verified on each new sorbent tube and on
10 percent of each batch of reconditioned
tubes. See Section 9.0 for acceptance criteria.
8.1.1 Sampling tubes must be
conditioned using the apparatus described in
Section 6.2.
8.0 Sorbent Tube Handling (Before and
After Sampling)
8.1
Sample Tube Conditioning
TABLE 8.1—EXAMPLE SORBENT TUBE CONDITIONING PARAMETERS
Maximum
temperature
(°C)
Sampling sorbent
Carbotrap® C ...............................................................................................................................
CarbopackTM C
Anasorb® GCB2
CarbographTM 1 TD
Carbotrap®
CarbopackTM B
Anasorb® GCB1
Tenax® TA
CarbopackTM X ............................................................................................................................
8.2 Capping, Storage and Shipment of
Conditioned Tubes
tkelley on DSK3SPTVN1PROD with RULES2
8.2.1 Conditioned tubes must be sealed
using long-term storage caps (see Section 6.4)
pushed fully down onto both ends of the PS
sorbent tube, tightened by hand and then
tighten an additional quarter turn using an
appropriate tool.
8.2.2 The capped tubes must be kept in
appropriate containers for storage and
transportation (see Section 6.4.2). Containers
of sorbent tubes may be stored and shipped
at ambient temperature and must be kept in
a clean environment.
8.2.3 You must keep batches of capped
tubes in their shipping boxes or wrap them
in uncoated aluminum foil before placing
them in their storage container, especially
before air freight, because the packaging
helps hold caps in position if the tubes get
very cold.
8.3 Calculating the Number of Tubes
Required for a Monitoring Exercise
8.3.1 Follow guidance given in Method
325A to determine the number of tubes
required for site monitoring.
8.3.2 The following additional samples
will also be required: Laboratory blanks as
specified in Section 9.1.2 (one per analytical
sequence minimum), field blanks as specified
in Section 9.3.2 (two per sampling period
minimum), CCV tubes as specified in Section
10.9.4. (at least one per analysis sequence or
every 24 hours), and duplicate samples as
specified in Section 9.4 (at least one
duplicate sample is required for every 10
sampling locations during each monitoring
period).
8.4 Sample Collection
8.4.1 Allow the tubes to equilibrate with
ambient temperature (approximately 30
minutes to 1 hour) at the monitoring location
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
before removing them from their storage/
shipping container for sample collection.
8.4.2 Tubes must be used for sampling
within 30 days of conditioning (Reference 4).
8.4.3 During field monitoring, the longterm storage cap at the sampling end of the
tube is replaced with a diffusion cap and the
whole assembly is arranged vertically, with
the sampling end pointing downward, under
a protective hood or shield—See Section 6.1
of Method 325A for more details.
8.5
Sample Storage
8.5.1 After sampling, tubes must be
immediately resealed with long-term storage
caps and placed back inside the type of
storage container described in Section 6.4.2.
8.5.2 Exposed tubes may not be placed in
the same container as clean tubes. They
should not be taken back out of the container
until ready for analysis and after they have
had time to equilibrate with ambient
temperature in the laboratory.
8.5.3 Sampled tubes must be inspected
before analysis to identify problems such as
loose or missing caps, damaged tubes, tubes
that appear to be leaking sorbent or container
contamination. Any and all such problems
must be documented together with the
unique identification number of the tube or
tubes concerned. Affected tubes must not be
analyzed but must be set aside.
8.5.4 Intact tubes must be analyzed
within 30 days of the end of sample
collection (within one week for limonene,
carene, bis-chloromethyl ether, labile sulfur
or nitrogen-containing compounds, and other
reactive VOCs).
Note: Ensure ambient temperatures stay
below 23 °C during transportation and
storage. Refrigeration is not normally
required unless the samples contain reactive
compounds or cannot be analyzed within 30
days. If refrigeration is used, the atmosphere
PO 00000
Frm 00161
Fmt 4701
Sfmt 4700
Conditioning
temperature
(°C)
Carrier gas
flow rate
>400
350
100 mL/min
350
330
100 mL/min
inside the refrigerator must be clean and free
of organic solvents.
9.0
Quality Control
9.1
Laboratory Blank
The analytical system must be
demonstrated to be contaminant free by
performing a blank analysis at the beginning
of each analytical sequence to demonstrate
that the secondary trap and TD/GC/MS
analytical equipment are free of any
significant interferents.
9.1.1 Laboratory blank tubes must be
prepared from tubes that are identical to
those used for field sampling.
9.1.2 Analysis of at least one laboratory
blank is required per analytical sequence.
The laboratory blank must be stored in the
laboratory under clean, controlled ambient
temperature conditions.
9.1.3 Laboratory blank/artifact levels
must meet the requirements of Section 9.2.2
(see also Table 17.1). If the laboratory blank
does not meet requirements, stop and
perform corrective actions and then reanalyze laboratory blank to ensure it meets
requirements.
9.2
Tube Conditioning
9.2.1 Conditioned tubes must be
demonstrated to be free of contaminants and
interference by running 10 percent of the
blank tubes selected at random from each
conditioned batch under standard sample
analysis conditions (see Section 8.1).
9.2.2 Confirm that artifacts and
background contamination are ≤ 0.2 ppbv or
less than three times the detection limit of
the procedure or less than 10 percent of the
target compound(s) mass that would be
collected if airborne concentrations were at
the regulated limit value, whichever is larger.
Only tubes that meet these criteria can be
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
9.4 Duplicate Samples
Duplicate (co-located) samples collected
must be analyzed and reported as part of
method quality control. They are used to
evaluate sampling and analysis precision.
Relevant performance criteria are given in
Section 9.9.
9.5 Method Performance Criteria
Unless otherwise noted, monitoring
method performance specifications must be
demonstrated for the target compounds using
the procedures described in Addendum A to
this method and the statistical approach
presented in Method 301.
9.6 Method Detection Limit
Determine the method detection limit
under the analytical conditions selected (see
9.8
Where:
A1 = A measurement value taken from one
spiked tube.
A2 = A measurement value taken from a
second spiked tube.
A = The average of A1 and A2.
tkelley on DSK3SPTVN1PROD with RULES2
Where:
Spiked Value = A known mass of VOCs
added to the tube.
Measured Value = Mass determined from
analysis of the tube.
9.9
Where:
F1 = A measurement value (mass) taken from
one of the two field replicate tubes used
in sampling.
F2 = A measurement value (mass) taken from
the second of two field replicate tubes
used in sampling.
F = The average of F1 and F2.
9.10.1 Quantitative (>95 percent)
compound recovery must be demonstrated by
repeat analyses on a same standard tube.
9.10.2 Compound recovery through the
TD system can also be demonstrated by
comparing the calibration check sample
response factor obtained from direct GC
injection of liquid standards with that
obtained from thermal desorption analysis
response factor using the same column under
identical conditions.
9.10.3 If the relative response factors
obtained for one or more target compounds
introduced to the column via thermal
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Field Replicate Precision
Use Equation 9.3 to determine and
report replicate precision for duplicate
field samples (see Section 9.4). The
level of agreement between duplicate
9.10 Desorption Efficiency and Compound
Recovery
The efficiency of the thermal desorption
method must be determined.
Analytical Precision
Demonstrate an analytical precision within
±20 percent using Equation 9.2. Analytical
precision must be demonstrated during
PO 00000
Frm 00162
Fmt 4701
Sfmt 4700
Section 11.3) using the procedure in Section
15 of Method 301. The method detection
limit is defined for each system by making
seven replicate measurements of a
concentration of the compound of interest
within a factor of five of the detection limit.
Compute the standard deviation for the seven
replicate concentrations, and multiply this
value by three. The results should
demonstrate that the method is able to detect
analytes such as benzene at concentrations as
low as 50 ppt or 1/3rd (preferably 1/10th) of
the lowest concentration of interest,
whichever is larger.
Note: Determining the detection limit may
be an iterative process as described in 40 CFR
part 136, Appendix B.
9.7
Analytical Bias
Analytical bias must be demonstrated to be
within ±30 percent using Equation 9.1.
Analytical bias must be demonstrated during
initial setup of this method and as part of the
CCV carried out with every sequence of 10
samples or less (see Section 9.14). Calibration
standard tubes (see Section 10.0) may be
used for this purpose.
initial setup of this method and at least once
per year. Calibration standard tubes may be
used (see Section 10.0) and data from CCV
may also be applied for this purpose.
field samples is a measure of the
precision achievable for the entire
sampling and analysis procedure. Flag
data sets for which the duplicate
samples do not agree within 30 percent.
desorption fail to meet the criteria in Section
9.10.1, you must adjust the TD parameters to
meet the criteria and repeat the experiment.
Once the thermal desorption conditions have
been optimized, you must repeat this test
each time the analytical system is
recalibrated to demonstrate continued
method performance.
9.11
Audit Samples
Certified reference standard samples must
be used to audit this procedure (if available).
Accuracy within 30 percent must be
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.034
9.3 Field Blanks
9.3.1 Field blank tubes must be prepared
from tubes that are identical to those used for
field sampling—i.e., they should be from the
same batch, have a similar history, and be
conditioned at the same time.
9.3.2 Field blanks must be shipped to the
monitoring site with the sampling tubes and
must be stored at the sampling location
throughout the monitoring exercise. The field
blanks must be installed under a protective
hood/cover at the sampling location, but the
long-term storage caps must remain in place
throughout the monitoring period (see
Method 325A). The field blanks are then
shipped back to the laboratory in the same
container as the sampled tubes. One field
blank tube is required for every 10 sampled
tubes on a monitoring exercise and no less
than two field blanks should be collected,
regardless of the size of the monitoring study.
9.3.3 Field blanks must contain no greater
than one-third of the measured target analyte
or compliance limit for field samples (see
Table 17.1). If either field blank fails, flag all
data that do not meet this criterion with a
note that the associated results are estimated
and likely to be biased high due to field
blank background.
ER01DE15.033
used for field monitoring, field or laboratory
blanks, or for system calibration.
9.2.3 If unacceptable levels of VOCs are
observed in the tube blanks, then the
processes of tube conditioning and checking
the blanks must be repeated.
ER01DE15.032
75338
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
demonstrated for relevant ambient air
concentrations (0.5 to 25 ppb).
Verify the instrument performance by
analyzing a 50 hg injection of
bromofluorobenzene. Prior to the beginning
of each analytical sequence or every 24 hours
during continuous GC/MS operation for this
9.12 Mass Spectrometer Tuning Criteria
Tune the mass spectrometer (if used)
according to manufacturer’s specifications.
75339
method demonstrate that the
bromofluorobenzene tuning performance
criteria in Table 9.1 have been met.
TABLE 9.1—GC/MS TUNING CRITERIA 1
Target mass
Rel. to mass
50 .................................................................................................................................................
75 .................................................................................................................................................
95 .................................................................................................................................................
96 .................................................................................................................................................
173 ...............................................................................................................................................
174 ...............................................................................................................................................
175 ...............................................................................................................................................
176 ...............................................................................................................................................
177 ...............................................................................................................................................
95
95
95
95
174
95
174
174
176
Lower limit %
Upper limit %
8
30
100
5
0
50
4
93
5
40
66
100
9
2
120
9
101
9
1 All ion abundances must be normalized to m/z 95, the nominal base peak, even though the ion abundance of m/z 174 may be up to 120 percent that of m/z 95.
9.13 Routine CCV at the Start of a
Sequence
Run CCV before each sequence of analyses
and after every tenth sample to ensure that
the previous multi-level calibration (see
Section 10.6.3) is still valid.
9.13.1 The sample concentration used for
the CCV should be near the mid-point of the
multi-level calibration range.
9.13.2 Quantitation software must be
updated with response factors determined
from the CCV standard. The percent
deviation between the initial calibration and
the CCV for all compounds must be within
30 percent.
9.14 CCV at the End of a Sequence
Run another CCV after running each
sequence of samples. The initial CCV for a
subsequent set of samples may be used as the
final CCV for a previous analytical sequence,
provided the same analytical method is used
and the subsequent set of samples is
analyzed immediately (within 4 hours) after
the last CCV.
9.15 Additional Verification
Use a calibration check standard from a
second, separate source to verify the original
calibration at least once every three months.
9.16 Integration Method
Document the procedure used for
integration of analytical data including field
samples, calibration standards and blanks.
tkelley on DSK3SPTVN1PROD with RULES2
9.17 QC Records
Maintain all QC reports/records for each
TD/GC/MS analytical system used for
application of this method. Routine quality
control requirements for this method are
listed below and summarized in Table 17.1.
10.0 Calibration and Standardization
10.1 Calibrate the analytical system using
standards covering the range of analyte
masses expected from field samples.
10.2 Analytical results for field samples
must fall within the calibrated range of the
analytical system to be valid.
10.3 Calibration standard preparation
must be fully traceable to primary standards
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
of mass and/or volume, and/or be confirmed
using an independent certified reference
method.
10.3.1 Preparation of calibration standard
tubes from standard atmospheres.
10.3.1.1 Subject to the requirements in
Section 7.2.1, low-level standard
atmospheres may be introduced to clean,
conditioned sorbent tubes in order to
produce calibration standards.
10.3.1.2 The standard atmosphere
generator or system must be capable of
producing sufficient flow at a constant rate
to allow the required analyte mass to be
introduced within a reasonable time frame
and without affecting the concentration of
the standard atmosphere itself.
10.3.1.3 The sampling manifold may be
heated to minimize risk of condensation but
the temperature of the gas delivered to the
sorbent tubes may not exceed 100 °F.
10.3.1.4 The flow rates passed through
the tube should be in the order of 50–100
mL/min and the volume of standard
atmosphere sampled from the manifold or
chamber must not exceed the breakthrough
volume of the sorbent at the given
temperature.
10.4 Preparation of calibration standard
tubes from concentrated gas standards.
10.4.1 If a suitable concentrated gas
standard (see Section 7.2.2) can be obtained,
follow the manufacturer’s recommendations
relating to suitable storage conditions and
product lifetime.
10.4.2 Introduce precise 0.5 to 500.0 mL
aliquots of the standard to the sampling end
of conditioned sorbent tubes in a 50–100 mL/
min flow of pure carrier gas.
Note: This can be achieved by connecting
the sampling end of the tube to an unheated
GC injector (see Section 6.6) and introducing
the aliquot of gas using a suitable gas syringe.
Gas sample valves could alternatively be
used to meter the standard gas volume.
10.4.3 Each sorbent tube should be left
connected to the flow of gas for 2 minutes
after standard introduction. As soon as each
spiked tube is removed from the injection
unit, seal it with long-term storage caps and
place it in an appropriate tube storage/
PO 00000
Frm 00163
Fmt 4701
Sfmt 4700
transportation container if it is not to be
analyzed within 24 hours.
10.5 Preparation of calibration standard
tubes from liquid standards.
10.5.1 Suitable standards are described in
Section 7.3.
10.5.2 Introduce precise 0.5 to 2 ml
aliquots of liquid standards to the sampling
end of sorbent tubes in a flow (50–100 mL/
min) of carrier gas using a precision syringe
and an unheated injector (Section 6.5). The
flow of gas should be sufficient to completely
vaporize the liquid standard.
Note: If the analytes of interest are higher
boiling than n-decane, reproducible analyte
transfer to the sorbent bed is optimized by
allowing the tip of the syringe to gently touch
the sorbent retaining gauze at the sampling
end of the tube.
10.5.3 Each sorbent tube is left connected
to the flow of gas for 5 minutes after liquid
standard introduction.
10.5.3.1 As soon as each spiked tube is
removed from the injection unit, seal it with
long-term storage caps and place it in an
appropriate tube storage container if it is not
to be analyzed within 24 hours.
Note: In cases where it is possible to
selectively purge the solvent from the tube
while all target analytes are quantitatively
retained, a larger 2 mL injection may be made
for optimum accuracy. However, if the
solvent cannot be selectively purged and will
be present during analysis, the injection
volume should be as small as possible (e.g.,
0.5 mL) to minimize solvent interference.
Note: This standard preparation technique
requires the entire liquid plug including the
tip volume be brought into the syringe barrel.
The volume in the barrel is recorded, the
syringe is inserted into the septum of the
spiking apparatus. The liquid is then quickly
injected. Any remaining liquid in the syringe
tip is brought back into the syringe barrel.
The volume in the barrel is recorded and the
amount spiked onto the tube is the difference
between the before spiking volume and the
after spiking volume. A bias occurs with this
method when sample is drawn continuously
up into the syringe to the specified volume
E:\FR\FM\01DER2.SGM
01DER2
75340
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
and the calibration solution in the syringe tip
is ignored.
10.6 Preparation of calibration standard
tubes from multiple standards.
10.6.1 If it is not possible to prepare one
standard containing all the compounds of
interest (e.g., because of chemical reactivity
or the breadth of the volatility range),
standard tubes can be prepared from multiple
gas or liquid standards.
10.6.2 Follow the procedures described
in Sections 10.4 and 10.5, respectively, for
introducing each gas and/or liquid standard
to the tube and load those containing the
highest boiling compounds of interest first
and the lightest species last.
10.7 Additional requirements for
preparation of calibration tubes.
10.7.1 Storage of Calibration Standard
Tubes
10.7.1.1 Seal tubes with long-term storage
caps immediately after they have been
disconnected from the standard loading
manifold or injection apparatus.
10.7.1.2 Calibration standard tubes may
be stored for no longer than 30 days and
should be refrigerated if there is any risk of
chemical interaction or degradation. Audit
standards (see section 9.11) are exempt from
this criteria and may be stored for the shelflife specified on their certificates.
10.8 Keep records for calibration standard
tubes to include the following:
10.8.1 The stock number of any
commercial liquid or gas standards used.
10.8.2 A chromatogram of the most recent
blank for each tube used as a calibration
standard together with the associated
analytical conditions and date of cleaning.
10.8.3 Date of standard loading.
10.8.4 List of standard components,
approximate masses and associated
confidence levels.
10.8.5 Example analysis of an identical
standard with associated analytical
conditions.
10.8.6 A brief description of the method
used for standard preparation.
10.8.7 The standard’s expiration date.
10.9 TD/GC/MS using standard tubes to
calibrate system response.
10.9.1 Verify that the TD/GC/MS
analytical system meets the instrument
performance criteria given in Section 9.1.
10.9.2 The prepared calibration standard
tubes must be analyzed using the analytical
conditions applied to field samples (see
Section 11.0) and must be selected to ensure
quantitative transfer and adequate
chromatographic resolution of target
compounds, surrogates, and internal
standards in order to enable reliable
identification and quantitation of compounds
of interest. The analytical conditions should
also be sufficiently stringent to prevent
buildup of higher boiling, non-target
contaminants that may be collected on the
tubes during field monitoring.
10.9.3 Calibration range. Each TD/GC/MS
system must be calibrated at five
concentrations that span the monitoring
range of interest before being used for sample
analysis. This initial multi-level calibration
determines instrument sensitivity under the
analytical conditions selected and the
linearity of GC/MS response for the target
compounds. One of the calibration points
must be within a factor of five of the
detection limit for the compounds of interest.
10.9.4 One of the calibration points from
the initial calibration curve must be at the
same concentration as the daily CCV
standard (e.g., the mass collected when
sampling air at typical concentrations).
10.9.5 Calibration frequency. Each GC/
MS system must be recalibrated with a full
5-point calibration curve following corrective
action (e.g., ion source cleaning or repair,
column replacement) or if the instrument
fails the daily calibration acceptance criteria.
10.9.5.1 CCV checks must be carried out
on a regular routine basis as described in
Section 9.14.
10.9.5.2 Quantitation ions for the target
compounds are shown in Table 10.1. Use the
primary ion unless interferences are present,
in which case you should use a secondary
ion.
TABLE 10.1—CLEAN AIR ACT VOLATILE ORGANIC COMPOUNDS FOR PASSIVE SORBENT SAMPLING
Compound
Vapor
pressure
(mmHg) a
BP
(°C)
CAS No.
Characteristic ion(s)
MW b
Primary
Secondary
1,1-Dichloroethene .............................
3-Chloropropene ................................
1,1,2-Trichloro-1,2,2-trifluoroethane1,1-Dichloroethane .........................
75–35–4
107–05–1
32
44.5
500
340
96.9
76.5
61
76
96
41, 39, 78
75–34–3
57.0
230
99
63
1,2-Dichloroethane .............................
1,1,1-Trichloroethane .........................
Benzene .............................................
Carbon tetrachloride ..........................
1,2-Dichloropropane ...........................
Trichloroethene ..................................
1,1,2-Trichloroethane .........................
Toluene ..............................................
Tetrachloroethene ..............................
Chlorobenzene ...................................
Ethylbenzene .....................................
m,p-Xylene .........................................
107–06–2
71–55–6
71–43–2
56–23–5
78–87–5
79–01–6
79–00–5
108–88–3
127–18–4
108–90–7
100–41–4
108–38–3,
106–42–3
100–42–5
95–47–6
106–46–7
83.5
74.1
80.1
76.7
97.0
87.0
114
111
121
132
136
138
61.5
100
76.0
90.0
42.0
20.0
19.0
22.0
14.0
8.8
7.0
6.5
99
133.4
78
153.8
113
131.4
133.4
92
165.8
112.6
106
106.2
62
97
78
117
63
95
83
92
164
112
91
106
65, 83, 85, 98,
100
98
99, 61
..............................
119
112
97, 130, 132
97, 85
91
129, 131, 166
77, 114
106
91
145
144
173
6.6
5.0
0.60
104
106.2
147
104
106
146
78
91
111, 148
Styrene ...............................................
o-Xylene .............................................
p-Dichlorobenzene .............................
a Pressure
b Molecular
tkelley on DSK3SPTVN1PROD with RULES2
11.0
in millimeters of mercury.
weight.
Analytical Procedure
11.1 Preparation for Sample Analysis
11.1.1 Each sequence of analyses must be
ordered as follows:
11.1.1.1 CCV.
11.1.1.2 A laboratory blank.
11.1.1.3 Field blank.
11.1.1.4 Sample(s).
11.1.1.5 Field blank.
11.1.1.6 CCV after 10 field samples.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
11.1.1.7
batch.
CCV at the end of the sample
11.2 Pre-desorption System Checks and
Procedures
11.2.1 Ensure all sample tubes and field
blanks are at ambient temperature before
removing them from the storage container.
11.2.2 If using an automated TD/GC/MS
analyzer, remove the long-term storage caps
from the tubes, replace them with
PO 00000
Frm 00164
Fmt 4701
Sfmt 4700
appropriate analytical caps, and load them
into the system in the sequence described in
Section 11.1. Alternatively, if using a manual
system, uncap and analyze each tube, one at
a time, in the sequence described in Section
11.1.
11.2.3 The following thermal desorption
system integrity checks and procedures are
required before each tube is analyzed.
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Note: Commercial thermal desorbers
should implement these steps automatically.
11.2.3.1 Tube leak test: Each tube must be
leak tested as soon as it is loaded into the
carrier gas flow path before analysis to ensure
data integrity.
11.2.3.2 Conduct the leak test at the GC
carrier gas pressure, without heat or gas flow
applied. Tubes that fail the leak test should
not be analyzed, but should be resealed and
stored intact. On automated systems, the
instrument should continue to leak test and
analyze subsequent tubes after a given tube
has failed. Automated systems must also
store and record which tubes in a sequence
have failed the leak test. Information on
failed tubes should be downloaded with the
batch of sequence information from the
analytical system.
11.2.3.3 Leak test the sample flow path.
Leak check the sample flow path of the
thermal desorber before each analysis
without heat or gas flow applied to the
sample tube. Stop the automatic sequence of
tube desorption and GC analysis if any leak
is detected in the main sample flow path.
This process may be carried out as a separate
step or as part of Section 11.2.3.2.
11.2.4 Optional Dry Purge
11.2.4.1 Tubes may be dry purged with a
flow of pure dry gas passing into the tube
from the sampling end, to remove water
vapor and other very volatile interferents if
required.
11.2.5 Internal Standard (IS) Addition
11.2.5.1 Use the internal standard
addition function of the automated thermal
desorber (if available) to introduce a precise
aliquot of the internal standard to the
sampling end of each tube after the leak test
and shortly before primary (tube)
desorption).
Note: This step can be combined with dry
purging the tube (Section 11.2.4) if required.
11.2.5.2 If the analyzer does not have a
facility for automatic IS addition, gas or
liquid internal standard can be manually
introduced to the sampling end of tubes in
a flow of carrier gas using the types of
procedure described in Sections 10.3 and
10.4, respectively.
11.2.6 Pre-purge. Each tube should be
purged to vent with carrier gas flowing in the
desorption direction (i.e., flowing into the
tube from the non-sampling end) to remove
oxygen before heat is applied. This is to
prevent analyte and sorbent oxidation and to
prevent deterioration of key analyzer
components such as the GC column and mass
spectrometer (if applicable). A series of
schematics illustrating these steps is
presented in Figures 17.2 and 17.3.
tkelley on DSK3SPTVN1PROD with RULES2
11.3
Analytical Procedure
11.3.1 Steps Required for Thermal
Desorption
11.3.1.1 Ensure that the pressure and
purity of purge and carrier gases supplying
the TD/GC/MS system, meet manufacturer
specifications and the requirements of this
method.
11.3.1.2 Ensure also that the analytical
method selected meets the QC requirements
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
of this method (Section 9) and that all the
analytical parameters are at set point.
11.3.1.3 Conduct predesorption system
checks (see Section 11.2).
11.3.1.4 Desorb the sorbent tube under
conditions demonstrated to achieve >95
percent recovery of target compounds (see
Section 9.5.2).
Note: Typical tube desorption conditions
range from 280–350 °C for 5–15 minutes with
a carrier gas flow of 30–100 mL/min passing
through the tube from the non-sampling end
such that analytes are flushed out of the tube
from the sampling end. Desorbed VOCs are
concentrated (refocused) on a secondary,
cooled sorbent trap integrated into the
analytical equipment (see Figure 17.4). The
focusing trap is typically maintained at a
temperature between ¥30 and +30 °C during
focusing. Selection of hydrophobic sorbents
for focusing and setting a trapping
temperature of +25 to 27 °C aid analysis of
humid samples because these settings allow
selective elimination of any residual water
from the system, prior to GC/MS analysis.
Note: The transfer of analytes from the tube
to the focusing trap during primary (tube)
desorption can be carried out splitless or
under controlled split conditions (see Figure
17.4) depending on the masses of target
compounds sampled and the requirements of
the system—sensitivity, required calibration
range, column overload limitations, etc.
Instrument controlled sample splits must be
demonstrated by showing the reproducibility
using calibration standards. Field and
laboratory blank samples must be analyzed at
the same split as the lowest calibration
standard. During secondary (trap) desorption
the focusing trap is heated rapidly (typically
at rates >40 °C/s) with inert (carrier) gas
flowing through the trap (3–100 mL/min) in
the reverse direction to that used during
focusing.
11.3.1.5 The split conditions selected for
optimum field sample analysis must also be
demonstrated on representative standards.
Note: Typical trap desorption temperatures
are in the range 250–360 °C, with a ‘‘hold’’
time of 1–3 minutes at the highest
temperature. Trap desorption automatically
triggers the start of GC analysis. The trap
desorption can also be carried out under
splitless conditions (i.e., with everything
desorbed from the trap being transferred to
the analytical column and GC detector) or,
more commonly, under controlled split
conditions (see Figure 17.4). The selected
split ratio depends on the masses of target
compounds sampled and the requirements of
the system—sensitivity, required calibration
range, column overload limitations, etc. If a
split is selected during both primary (trap)
desorption and secondary (trap) desorption,
the overall split ratio is the product of the
two. Such ‘double’ split capability gives
optimum flexibility for accommodating
concentrated samples as well as trace-level
samples on the TD/GC/MS analytical system.
High resolution capillary columns and most
GC/MS detectors tend to work best with
approximately 20–200 ng per compound per
tube to avoid saturation. The overall split
ratio must be adjusted such that, when it is
applied to the sample mass that is expected
PO 00000
Frm 00165
Fmt 4701
Sfmt 4700
75341
to be collected during field monitoring, the
amount reaching the column will be
attenuated to fall within this range. As a rule
of thumb this means that ∼20 ng samples will
require splitless or very low split analysis, ∼2
mg samples will require a split ratio in the
order of ∼50:1 and 200 mg samples will
require a double split method with an overall
split ratio in the order of 2,000:1.
11.3.1.6 Analyzed tubes must be resealed
with long-term storage caps immediately
after analysis (manual systems) or after
completion of a sequence (automated
systems). This prevents contamination,
minimizing the extent of tube reconditioning
required before subsequent reuse.
11.3.2 GC/MS Analytical Procedure
11.3.2.1 Heat/cool the GC oven to its
starting set point.
11.3.2.2 If using a GC/MS system, it can
be operated in either MS-Scan or MS–SIM
mode (depending on required sensitivity
levels and the type of mass spectrometer
selected). As soon as trap desorption and
transfer of analytes into the GC column
triggers the start of the GC/MS analysis,
collect mass spectral data over a range of
masses from 35 to 300 amu. Collect at least
10 data points per eluting chromatographic
peak in order to adequately integrate and
quantify target compounds.
11.3.2.3 Use secondary ion quantitation
only when there are sample matrix
interferences with the primary ion. If
secondary ion quantitation is performed, flag
the data and document the reasons for the
alternative quantitation procedure.
11.3.2.4 Data reduction is performed by
the instruments post processing program that
is automatically accessed after data
acquisition is completed at the end of the GC
run. The concentration of each target
compound is calculated using the previously
established response factors for the CCV
analyzed in Section 11.1.1.6.
11.3.2.5 Whenever the thermal
desorption—GC/MS analytical method is
changed or major equipment maintenance is
performed, you must conduct a new fivelevel calibration (see Section 10.6.3). System
calibration remains valid as long as results
from subsequent CCV are within 30 percent
of the most recent 5-point calibration (see
Section 10.9.5). Include relevant CCV data in
the supporting information in the data report
for each set of samples.
11.3.2.6 Document, flag and explain all
sample results that exceed the calibration
range. Report flags and provide
documentation in the analytical results for
the affected sample(s).
12.0 Data Analysis, Calculations, and
Reporting
12.1 Recordkeeping Procedures for Sorbent
Tubes
12.1.1 Label sample tubes with a unique
identification number as described in Section
6.3.
12.1.2 Keep records of the tube numbers
and sorbent lots used for each sampling
period.
12.1.3 Keep records of sorbent tube
packing if tubes are manually prepared in the
E:\FR\FM\01DER2.SGM
01DER2
75342
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
laboratory and not supplied commercially.
These records must include the masses and/
or bed lengths of sorbent(s) contained in each
tube, the maximum allowable temperature
for that tube and the date each tube was
packed. If a tube is repacked at any stage,
record the date of tube repacking and any
other relevant information required in
Section 12.1.
12.1.4 Keep records of the conditioning
and blanking of tubes. These records must
include, but are not limited to, the unique
identification number and measured
background resulting from the tube
conditioning.
12.1.5 Record the location, dates, tube
identification and times associated with each
sample collection. Record this information
on a Chain of Custody form that is sent to the
analytical laboratory.
12.1.6 Field sampling personnel must
complete and send a Chain of Custody to the
analysis laboratory (see Section 8.6.4 of
Method 325A for what information to
include and Section 17.0 of this method for
an example form). Duplicate copies of the
Chain of Custody must be included with the
sample report and stored with the field test
data archive.
12.1.7 Field sampling personnel must
also keep records of the unit vector wind
direction, sigma theta, temperature and
barometric pressure averages for the
sampling period. See Section 8.3.4 of Method
325A.
12.1.8 Laboratory personnel must record
the sample receipt date, and analysis date.
12.1.9 Laboratory personnel must
maintain records of the analytical method
and sample results in electronic or hardcopy
in sufficient detail to reconstruct the
calibration, sample, and quality control
results from each sampling period.
Where:
As = Peak area for the characteristic ion of the
analyte.
Ais = Peak area for the characteristic ion of
the internal standard.
Ms = Mass of the analyte.
Mis = Mass of the internal standard.
12.2.1.2 Standard deviation of the
response factors (SDRF). Calculate the SDRF
using Equation 12.2:
Where:
RFi = RF for each of the calibration
compounds.
RF = Mean RF for each compound from the
initial calibration.
n = Number of calibration standards.
12.2.1.3 Percent deviation (%DEV).
Calculate the %DEV using Equation 12.3:
Where:
SDRF = Standard deviation.
RF = Mean RF for each compound from the
initial calibration.
12.2.1.4 Relative percent difference
(RPD). Calculate the RPD using Equation
12.4:
Where:
R1, R2 = Values that are being compared (i.e.,
response factors in CCV).
12.2.2 Determine the equivalent
concentration of compounds in atmospheres
as follows.
12.2.3 Correct target concentrations
determined at the sampling site temperature
and atmospheric pressure to standard
conditions (25 °C and 760 mm mercury)
using Equation 12.5 (Reference 21).
Where:
tss = The average temperature during the
collection period at the sampling site (K).
Pss = The average pressure at the sampling
site during the collection period (mm
Hg).
U = The diffusive uptake rate (sampling rate)
(mL/min).
12.2
Calculations
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00166
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.038
ER01DE15.036
ER01DE15.037
VerDate Sep<11>2014
ER01DE15.035
tkelley on DSK3SPTVN1PROD with RULES2
ER01DE15.039
12.2.1 Complete the calculations in this
section to determine compliance with
calibration quality control criteria (see also
Table 17.1).
12.2.1.1 Response factor (RF). Calculate
the RF using Equation 12.1:
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
12.2.4 For passive sorbent tube samples,
calculate the concentration of the target
compound(s) in the sampled air, in mg/m3 by
using Equation 12.6 (Reference 22).
Where:
Cm = The concentration of target compound
in the air sampled (mg/m3).
mmeas = The mass of the compound as
measured in the sorbent tube (mg).
UNTP = The diffusive uptake rate corrected for
local conditions (sampling rate) (mL/
min).
t = The exposure time (minutes).
Note: Diffusive uptake rates for common
VOCs, using carbon sorbents packed into
sorbent tubes of the dimensions specified in
Section 6.1, are listed in Table 12.1. Adjust
analytical conditions to keep expected
sampled masses within range (see Sections
11.3.1.3 to 11.3.1.5). Best possible method
75343
detection limits are typically in the order of
0.1 ppb for 1,3-butadiene and 0.05 ppb for
volatile aromatics such as benzene for 14-day
monitoring. However, actual detection limits
will depend upon the analytical conditions
selected.
TABLE 12.1—VALIDATED SORBENTS AND UPTAKE RATES (ML/MIN) FOR SELECTED CLEAN AIR ACT COMPOUNDS
1,1-Dichloroethene ..............................................................................................
3-Chloropropene .................................................................................................
1,1-Dichloroethane ..............................................................................................
1,2-Dichloroethane ..............................................................................................
1,1,1-Trichloroethane ..........................................................................................
Benzene ..............................................................................................................
Carbon tetrachloride ...........................................................................................
1,2-Dichloropropane ...........................................................................................
Trichloroethene ...................................................................................................
1,1,2-Trichloroethane ..........................................................................................
Toluene ...............................................................................................................
Tetrachloroethene ...............................................................................................
Chlorobenzene ....................................................................................................
Ethylbenzene ......................................................................................................
m,p-Xylene ..........................................................................................................
Styrene ................................................................................................................
o-Xylene ..............................................................................................................
p-Dichlorobenzene ..............................................................................................
b Reference
c Reference
tkelley on DSK3SPTVN1PROD with RULES2
13.0
not available
not available
not available
not available
not available
0.63 ± 0.07b
not available
not available
not available
not available
0.56 ± 0.06c
not available
not available
not available
0.47 ± 0.04c
not available
0.47 ± 0.04c
not available
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
not available.
not available.
not available.
not available.
not available.
0.63 ± 0.07b.
not available.
not available.
not available.
not available.
0.56 ± 0.06c.
not available.
not available.
0.50c.
0.47 ± 0.04c.
not available.
0.47 ± 0.04c.
not available.
3, McClenny, J. Environ. Monit. 7:248–256. Based on 24-hour duration.
24, BS EN 14662–4:2005 (incorporated by reference—see § 63.14). Based on 14-day duration.
25, ISO 16017–2:2003(E) (incorporated by reference—see § 63.14). Based on 14-day duration.
Method Performance
The performance of this procedure for VOC
not listed in Table 12.1 is determined using
the procedure in Addendum A of this
Method or by one of the following national/
international standard methods: ISO 16017–
2:2003(E), ASTM D6196–03 (Reapproved
2009), or BS EN 14662–4:2005 (all
incorporated by reference—see § 63.14).
13.1 The valid range for measurement of
VOC is approximately 0.5 mg/m3 to 5 mg/m3
in air, collected over a 14-day sampling
period. The upper limit of the useful range
depends on the split ratio selected (Section
11.3.1) and the dynamic range of the
analytical system. The lower limit of the
useful range depends on the noise from the
analytical instrument detector and on the
blank level of target compounds or
interfering compounds on the sorbent tube
(see Section 13.3).
13.2 Diffusive sorbent tubes compatible
with passive sampling and thermal
desorption methods have been evaluated at
relatively high atmospheric concentrations
(i.e., mid-ppb to ppm) and published for use
in workplace air and industrial/mobile
source emissions (References 15–16, 21–22).
VerDate Sep<11>2014
0.57 ± 0.14
0.51 ± 0.3
0.57 ± 0.1
0.57 ± 0.08
0.51 ± 0.1
0.67 ± 0.06
0.51 ± 0.06
0.52 ± 0.1
0.5 ± 0.05
0.49 ± 0.13
0.52 ± 0.14
0.48 ± 0.05
0.51 ± 0.06
0.46 ± 0.07
0.46 ± 0.09
0.5 ± 0.14
0.46 ± 0.12
0.45 ± 0.05
CarbopackTM
B
23:11 Nov 30, 2015
Jkt 238001
13.3 Best possible detection limits and
maximum quantifiable concentrations of air
pollutants range from sub-part-per-trillion
(sub-ppt) for halogenated species such as
CCl4 and the freons using an electron capture
detector (ECD), SIM Mode GC/MS, triple
quad MS or GC/TOF MS to sub-ppb for
volatile hydrocarbons collected over 72 hours
followed by analysis using GC with
quadrupole MS operated in the full SCAN
mode.
13.3.1 Actual detection limits for
atmospheric monitoring vary depending on
several key factors. These factors are:
• Minimum artifact levels.
• GC detector selection.
• Time of exposure for passive sorbent
tubes.
• Selected analytical conditions,
particularly column resolution and split
ratio.
14.0
Pollution Prevention
This method involves the use of ambient
concentrations of gaseous compounds that
post little or no danger of pollution to the
environment.
PO 00000
Frm 00167
Fmt 4701
Sfmt 4700
15.0
Waste Management
Dispose of expired calibration solutions as
hazardous materials. Exercise standard
laboratory environmental practices to
minimize the use and disposal of laboratory
solvents.
16.0
References
1. Winberry, W. T. Jr., et al., Determination
of Volatile Organic Compounds in
Ambient Air Using Active Sampling onto
Sorbent Tubes: Method TO–17r, Second
Edition, U.S. Environmental Protection
Agency, Research Triangle Park, NC
27711, January 1999. https://www.epa.
gov/ttnamti1/airtox.html#compendium
2. Ciccioli, P., Brancaleoni, E., Cecinato, A.,
Sparapini, R., and Frattoni, M.,
‘‘Identification and Determination of
Biogenic and Anthropogenic VOCs in
Forest Areas of Northern and Southern
Europe and a Remote Site of the
Himalaya Region by High-resolution GC–
MS,’’ J. of Chrom., 643, pp 55–69, 1993.
3. McClenny, W.A., K.D. Oliver, H.H.
Jacumin, Jr., E.H. Daughtrey, Jr., D.A.
Whitaker. 2005. 24 h diffusive sampling
of toxic VOCs in air onto CarbopackTM
X solid adsorbent followed by thermal
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.040
a Reference
CarbographTM1
TD
CarbopackTM
Xa
Compound
75344
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
desorption/GC/MS analysis—laboratory
studies. J. Environ. Monit. 7:248–256.
4. Markes International (www.markes.com/
publications): Thermal desorption
Technical Support Note 2: Prediction of
uptake rates for diffusive tubes.
5. Ciccioli, P., Brancaleoni, E., Cecinato, A.,
DiPalo, C., Brachetti, A., and Liberti, A.,
‘‘GC Evaluation of the Organic
Components Present in the Atmosphere
at Trace Levels with the Aid of
CarbopackTM B for Preconcentration of
the Sample,’’ J. of Chrom., 351, pp 433–
449, 1986.
6. Broadway, G. M., and Trewern, T., ‘‘Design
Considerations for the Optimization of a
Packed Thermal Desorption Cold Trap
for Capillary Gas Chromatography,’’
Proc. 13th Int’l Symposium on Capil.
Chrom., Baltimore, MD, pp 310–320,
1991.
7. Broadway, G. M., ‘‘An Automated System
for use Without Liquid Cryogen for the
Determination of VOC’s in Ambient
Air,’’ Proc. 14th Int’l. Symposium on
Capil. Chrom., Baltimore, MD, 1992.
8. Gibitch, J., Ogle, L., and Radenheimer, P.,
‘‘Analysis of Ozone Precursor
Compounds in Houston, Texas Using
Automated Continuous GCs,’’ in
Proceedings of the Air and Waste
Management Association Conference:
Measurement of Toxic and Related Air
Pollutants, Air and Waste Management
Association, Pittsburgh, PA, May 1995.
9. Vandendriessche, S., and Griepink, B.,
‘‘The Certification of Benzene, Toluene
and m-Xylene Sorbed on Tenax® TA in
Tubes,’’ CRM–112 CEC, BCR, EUR12308
EN, 1989.
10. MDHS 2 (Acrylonitrile in Air),
‘‘Laboratory Method Using Porous
Polymer Adsorption Tubes, and Thermal
Desorption with Gas Chromatographic
Analysis,’’ Methods for the
Determination of Hazardous Substances
(MDHS), UK Health and Safety
Executive, Sheffield, UK.
11. MDHS 22 (Benzene in Air), ‘‘Laboratory
Method Using Porous Polymer
Adsorbent Tubes, Thermal Desorption
and Gas Chromatography,’’ Method for
the Determination of Hazardous
Substances (MDHS), UK Health and
Safety Executive, Sheffield, UK.
12. MDHS 23 (Glycol Ether and Glycol
Acetate Vapors in Air), ‘‘Laboratory
Method Using Tenax® Sorbent Tubes,
Thermal Desorption and Gas
Chromatography,’’ Method for the
Determination of Hazardous Substances
(MDHS), UK Health and Safety
Executive, Sheffield, UK.
13. MDHS 40 (Toluene in air), ‘‘Laboratory
Method Using Pumped Porous Polymer
Adsorbent Tubes, Thermal Desorption
and Gas Chromatography,’’ Method for
the Determination of Hazardous
Substances (MDHS), UK Health and
Safety Executive, Sheffield, UK.
14. MDHS 60 (Mixed Hydrocarbons (C to C)
in Air), ‘‘Laboratory Method Using
Pumped Porous Polymer 3 10 and
Carbon Sorbent Tubes, Thermal
Desorption and Gas Chromatography,’’
Method for the Determination of
Hazardous Substances (MDHS), UK
Health and Safety Executive, Sheffield,
UK.
15. Price, J. A., and Saunders, K. J.,
‘‘Determination of Airborne Methyl tertButyl Ether in Gasoline Atmospheres,’’
Analyst, Vol. 109, pp. 829–834, July
1984.
16. Coker, D. T., van den Hoed, N., Saunders,
K. J., and Tindle, P. E., ‘‘A Monitoring
Method for Gasoline Vapour Giving
Detailed Composition,’’ Ann. Occup,
Hyg., Vol 33, No. 11, pp 15–26, 1989.
17. DFG, ‘‘Analytische Methoden zur prufing
gesundheitsschadlicher Arbeistsstoffe,’’
Deutsche Forschungsgemeinschaft,
Verlag Chemie, Weinheim FRG, 1985.
18. NNI, ‘‘Methods in NVN Series
(Luchtkwaliteit; Werkplekatmasfeer),’’
Nederlands Normailsatie—Institut, Delft,
The Netherlands, 1986–88.
19. ‘‘Sampling by Solid Adsorption
Techniques,’’ Standards Association of
Australia Organic Vapours, Australian
Standard 2976, 1987.
20. Woolfenden, E. A., ‘‘Monitoring VOCs in
Air Using Pumped Sampling onto
Sorbent Tubes Followed by Thermal
Desorption-capillary GC Analysis:
Summary of Reported Data and Practical
Guidelines for Successful Application,’’
J. Air & Waste Manage. Assoc., Vol. 47,
1997, pp. 20–36.
21. Validation Guidelines for Air Sampling
Methods Utilizing Chromatographic
Analysis, OSHA T–005, Version 3.0, May
2010, https://www.osha.gov/dts/sltc/
methods/chromguide/chromguide.pdf.
22. ASTM D4597–10, Standard Practice for
Sampling Workplace Atmospheres to
collect Gases or Vapors with Solid
Sorbent Diffusive Samplers.
23. Martin, https://www.hsl.gov.uk/media/
1619/issue14.pdf.
24. BS EN 14662–4:2005, Ambient air
quality—Standard method for the
measurement of benzene
concentrations—Part 4: Diffusive
sampling followed by thermal desorption
and gas chromatography.
25. ISO 16017–2:2003(E): Indoor, ambient
and workplace air—Sampling and
analysis of volatile organic compounds
by sorbent tube/thermal desorption/
capillary gas chromatography—Part 2:
Diffusive sampling.
17.0 Tables, Diagrams, Flowcharts and
Validation Data
TABLE 17.1—SUMMARY OF GC/MS ANALYSIS QUALITY CONTROL PROCEDURES
Frequency
Acceptance criteria
Corrective action
Bromofluorobenzene
Instrument
Tune Performance Check.
Five point calibration bracketing
the expected sample concentration.
Dailya prior to sample analysis .....
Evaluation criteria presented in
Section 9.5 and Table 9.2.
(1) Percent Deviation (%DEV) of
response factors ±30%.
(2) Relative Retention Times
(RRTs) for target peaks ±0.06
units from mean RRT.
Calibration Verification (CCV Second
source
calibration
verification check).
Laboratory Blank Analysis .............
tkelley on DSK3SPTVN1PROD with RULES2
Parameter
Following the calibration curve .....
(1) Retune and or
(2) Perform Maintenance.
(1) Repeat calibration sample
analysis.
(2) Repeat linearity check.
(3) Prepare new calibration standards as necessary and repeat
analysis.
(1) Repeat calibration check.
(2) Repeat calibration curve.
Blank Sorbent Tube Certification ...
Samples—Internal Standards ........
a Every
Following any major change, repair or maintenance or if daily
CCV does not meet method requirements. Recalibration not to
exceed three months.
Daily a following bromofluoro- benzene and calibration check;
prior to sample analysis.
One tube analyzed for each batch
of tubes cleaned or 10 percent
of tubes whichever is greater.
All samples ...................................
The response factor ±30% DEV
from calibration curve average
response factor.
(1) ≤0.2 ppbv per analyte or ≤3
times the LOD, whichever is
greater.
(2) Internal Standard (IS) area response ±40% and IS Retention
Time (RT) ±0.33 min. of most
recent calibration check.
<0.2 ppbv per VOC targeted compound or 3 times the LOD,
whichever is greater.
IS area response ±40% and IS
RT ±0.33 min. of most recent
calibration validation.
(1) Repeat analysis with new
blank tube.
(2) Check system for leaks, contamination.
3) Analyze additional blank.
Reclean all tubes in batch and reanalyze.
Flag Data for possible invalidation.
24 hours.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00168
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75345
BILLING CODE 6560–50–P
Method 325 A/B
EXAMPLE FIELD TEST DATA SHEET (FTDS)
AND
CHAIN OF CUSTODY
I. GENERAL INFORMATION
SITE NAME:
SITE LOCATION ADDRESS:
CITY:
STATE:
ZIP:
II. SAMPLING DATA
Sample
ID
(Tube)
#
Sorbent
Sample
or
blank
Start
Date
Start
Time
Stop
Date
Stop
Time
Location
(gps)
Ambient
Temp.
(oF)
Barometric
Pressure
(in. Hg)
III. CUSTODY INFORMATION
COLLECTED BY:
Relinquished to Shipper Date:
Name:
Received by Laboratory Name
Date:
Sample condition upon receipt:
Time
Time
Analysis Required:
Figure 17.1. Example Field Data From and Chain of Custody
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00169
Fmt 4701
Sfmt 4725
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.041
tkelley on DSK3SPTVN1PROD with RULES2
Comments:
75346
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
GCAoalytical
Column
To Detector
T
•••\
l···························r·················~······
.
I
'
:
l
:
:
:
:
:
M 1M
JiiC
*
••
••
•*
•
••
SOrbentTube
at Ambient
Temperature
Cold
Sorbeot
Focusing
Trap
I
I·····®
I
Pressure
Transducer
Split Flow Vent
Closed
•*
--Flow
•··••··· Pressure, No Flow
Desorb Flow Vent Closed
CarrierGas - - - . . . - Supplyln
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00170
Fmt 4701
Sfmt 4725
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.042
tkelley on DSK3SPTVN1PROD with RULES2
Figure 17.2. Schematic of Ther.mal Desorption Flow Path During
Leak Testing
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
75347
GC Analytical
Column
lQOetectcir
Cold
Sorbent
Focusing
Pressure
·····® Transducer
Trap
SorbentTube
at Ambient
Temperature
Split Flow Vent
Open (optional)
liiE
liiE
••
--Flow
•••••••• Pressure, No Flow
Desorb Flow Vent Closed
(optional)
Carrier Gas
Supply In
CarrierGas;.__ _ _,
Supply In
Pressurised Internal
Standard (IS) Gas In
GCAnalvtlcal
Column
To Detector
Cold
Sorbent
* Focu~il'lll
·····@
Ill(
Pressure
Tran•duCIIr
*Trap
SorbentTube
at Ambient
Ill
Temperature
•
Split Flow Vent
•
•
•
--Flow
•••••••• Pressure, No Flow
Vent
Desorb flow Vent Closlild
Clrriet Gas
Sopplyln - - - - '
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00171
Fmt 4701
Sfmt 4725
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.043
tkelley on DSK3SPTVN1PROD with RULES2
Figure 17.3. Schematic of Thermal Desorption Flow During Purge
of Air (Top) and Addition of IS Gas to the Sorbent Tube (Bottom)
75348
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
&Analytical
Column
To l:letector
I
j
I'::\
r···\!:!1
Pressure
Transducer
!
1
Sorbent TUbe
at Elevated
Temperature
Split Row Vent
(Optional for Inlet
Split)
-Flow
•••···•· Pressure, No Flow
Carrier Gas
Desorb Aow Vent Open
Supply in
Carder Gas._ _ __.
Supply In
GCAnalytlcal
Column
To l:letector
( .........................
i
I'::\ Pressure
SQrbent
FocuslngTrap
at Elevated
Temperature
SorbentTube
••••v:.:.~
Transducer
Coolin&
Split Aow Vent
(Optional for
Outlet Split)
--Flow
J
Carrier Gas
•·•···•· Pressure, No Flow
!--··"
Supply in
BILLING CODE 6560–50–C
A.1
ADDENDUM A to Method 325B—Method
325 Performance Evaluation
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
Scope and Application
A.1.1 To be measured by Methods 325A
and 325B, each new target volatile organic
compound (VOC) or sorbent that is not listed
in Table 12.1 must be evaluated by exposing
PO 00000
Frm 00172
Fmt 4701
Sfmt 4700
the selected sorbent tube to a known
concentration of the target compound(s) in an
exposure chamber following the procedure in
this Addendum or by following the
procedures in the national/international
standard methods: ISO 16017–2:2003(E),
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.044
tkelley on DSK3SPTVN1PROD with RULES2
Figure 17.4. Schematic of Ther.mal Desorption Flow Path During
Primary (Tube) Desorption (Top) and Secondary (Trap) Desorption
and Transfer to the GC (Bottom)
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
ASTM D6196–03 (Reapproved 2009), or BS
EN 14662–4:2005 (all incorporated by
reference—see § 63.14), or reported in peerreviewed open literature.
A.1.2 You must determine the uptake rate
and the relative standard deviation compared
to the theoretical concentration of volatile
material in the exposure chamber for each of
the tests required in this method. If data that
meet the requirement of this Addendum are
available in the peer reviewed open literature
for VOCs of interest collected on your passive
sorbent tube configuration, then such data
may be submitted in lieu of the testing
required in this Addendum.
A.1.3 You must expose sorbent tubes in
a test chamber to parts per trillion by volume
(pptv) and low parts per billion by volume
(ppbv) concentrations of VOCs in humid
atmospheres to determine the sorbent tube
uptake rate and to confirm compound
capture and recovery.
A.2
Summary of Method
tkelley on DSK3SPTVN1PROD with RULES2
Note: The technique described here is one
approach for determining uptake rates for
new sorbent/sorbate pairs. It is equally valid
to follow the techniques described in any one
of the following national/international
standards methods: ISO 16017–2:2003(E),
ASTM D6196–03 (Reapproved 2009), or BS
EN 14662–4:2005 (all incorporated by
reference—see § 63.14).
A.2.1 Known concentrations of VOC are
metered into an exposure chamber
containing sorbent tubes filled with media
selected to capture the volatile organic
compounds of interest (see Figure A.1 and
A.2 for an example of the exposure chamber
and sorbent tube retaining rack). VOC are
diluted with humid air and the chamber is
allowed to equilibrate for 6 hours. Clean
passive sampling devices are placed into the
chamber and exposed for a measured period
of time. The passive uptake rate of the
passive sampling devices is determined using
the standard and dilution gas flow rates.
Chamber concentrations are confirmed with
whole gas sample collection and analysis or
direct interface volatile organic compound
measurement methods.
A.2.2 An exposure chamber and known
gas concentrations must be used to challenge
and evaluate the collection and recovery of
target compounds from the sorbent and tube
selected to perform passive measurements of
VOC in atmospheres.
A.3 Definitions
A.3.1 cc is cubic centimeter.
A.3.2 ECD is electron capture detector.
A.3.3 FID is flame ionization detector.
A.3.4 LED is light-emitting diode.
A.3.5 MFC is mass flow controller.
A.3.6 MFM is mass flow meter.
A.3.7 min is minute.
A.3.8 ppbv is parts per billion by volume.
A.3.9 ppmv is parts per million by
volume.
A.3.10 PSD is passive sampling device.
A.3.11 psig is pounds per square inch
gauge.
A.3.12 RH is relative humidity.
A.3.13 VOC is volatile organic
compound.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
A.4 Interferences
A.4.1 VOC contaminants in water can
contribute interference or bias results high.
Use only distilled, organic-free water for
dilution gas humidification.
A.4.2 Solvents and other VOC-containing
liquids can contaminate the exposure
chamber. Store and use solvents and other
VOC-containing liquids in the exhaust hood
when exposure experiments are in progress
to prevent the possibility of contamination of
VOCs into the chamber through the
chamber’s exhaust vent.
Note: Whenever possible, passive sorbent
evaluation should be performed in a VOC
free laboratory.
A.4.3 PSDs should be handled by
personnel wearing only clean, white cotton
or powder free nitrile gloves to prevent
contamination of the PSDs with oils from the
hands.
A.4.4 This performance evaluation
procedure is applicable to only volatile
materials that can be measured accurately
with direct interface gas chromatography or
whole gas sample collection, concentration
and analysis. Alternative methods to confirm
the concentration of volatile materials in
exposure chambers are subject to
Administrator approval.
A.5 Safety
A.5.1 This procedure does not address all
of the safety concerns associated with its use.
It is the responsibility of the user of this
standard to establish appropriate field and
laboratory safety and health practices and
determine the applicability of regulatory
limitations prior to use.
A.5.2 Laboratory analysts must exercise
appropriate care in working with highpressure gas cylinders.
A.6 Equipment and Supplies
A.6.1 You must use an exposure chamber
of sufficient size to simultaneously expose a
minimum of eight sorbent tubes.
A.6.2 Your exposure chamber must not
contain VOC that interfere with the
compound under evaluation. Chambers made
of glass and/or stainless steel have been used
successfully for measurement of known
concentration of selected VOC compounds.
A.6.3 The following equipment and
supplies are needed:
• Clean, white cotton or nitrile gloves;
• Conditioned passive sampling device
tubes and diffusion caps; and
• NIST traceable high resolution digital gas
mass flow meters (MFMs) or flow controllers
(MFCs).
A.7 Reagents and Standards
A.7.1 You must generate an exposure gas
that contains between 35 and 75 percent
relative humidity and a concentration of
target compound(s) within 2 to 5 times the
concentration to be measured in the field.
A.7.2 Target gas concentrations must be
generated with certified gas standards and
diluted with humid clean air. Dilution to
reach the desired concentration must be done
with zero grade air or better.
A.7.3 The following reagents and
standards are needed:
• Distilled water for the humidification;
PO 00000
Frm 00173
Fmt 4701
Sfmt 4700
75349
• VOC standards mixtures in high-pressure
cylinder certified by the supplier (Note: The
accuracy of the certified standards has a
direct bearing on the accuracy of the
measurement results. Typical vendor
accuracy is ±5 percent accuracy but some
VOC may only be available at lower accuracy
(e.g., acrolein at 10 percent)); and
• Purified dilution air containing less than
0.2 ppbv of the target VOC.
A.8 Sample Collection, Preservation and
Storage
A.8.1 You must use certified gas
standards diluted with humid air. Generate
humidified air by adding distilled organic
free water to purified or zero grade air.
Humidification may be accomplished by
quantitative addition of water to the air
dilution gas stream in a heated chamber or
by passing purified air through a humidifying
bubbler. You must control the relative
humidity in the test gas throughout the
period of passive sampler exposure.
Note: The RH in the exposure chamber is
directly proportional to the fraction of the
purified air that passes through the water in
the bubbler before entering the exposure
chamber. Achieving uniform humidification
in the proper range is a trial-and-error
process with a humidifying bubbler. You
may need to heat the bubbler to achieve
sufficient humidity. An equilibration period
of approximately 15 minutes is required
following each adjustment of the air flow
through the humidifier. Several adjustments
or equilibration cycles may be required to
achieve the desired RH level.
Note: You will need to determine both the
dilution rate and the humidification rate for
your design of the exposure chamber by trial
and error before performing method
evaluation tests.
A.8.2 Prepare and condition sorbent
tubes following the procedures in Method
325B Section 7.0.
A.8.3 You must verify that the exposure
chamber does not leak.
A.8.4 You must complete two evaluation
tests using a minimum of eight passive
sampling tubes in each test with less than 5percent depletion of test analyte by the
samplers.
A.8.4.1 Perform at least one evaluation at
two to five times the estimated analytical
detection limit or less.
A.8.4.2 Perform second evaluation at a
concentration equivalent to the middle of the
analysis calibration range.
A.8.5 You must evaluate the samplers in
the test chamber operating between 35
percent and 75 percent RH, and at 25 ± 5 °C.
Allow the exposure chamber to equilibrate
for 6 hours before starting an evaluation.
A.8.6 The flow rate through the chamber
must be ≤0.5 meter per second face velocity
across the sampler face.
A.8.7 Place clean, ready to use sorbent
tubes into the exposure chamber for
predetermined amounts of time to evaluate
collection and recovery from the tubes. The
exposure time depends on the concentration
of volatile test material in the chamber and
the detection limit required for the sorbent
tube sampling application. Exposure time
E:\FR\FM\01DER2.SGM
01DER2
75350
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
should match sample collection time. The
sorbent tube exposure chamber time may not
be less than 24 hours and should not be
longer than 2 weeks.
A.8.7.1 To start the exposure, place the
clean PSDs equipped with diffusion caps on
the tube inlet into a retaining rack.
A.8.7.2 Place the entire retaining rack
inside the exposure chamber with the
diffusive sampling end of the tubes facing
into the chamber flow. Seal the chamber and
record the exposure start time, chamber RH,
chamber temperature, PSD types and
numbers, orientation of PSDs, and volatile
material mixture composition (see Figure
A.2).
A.8.7.3 Diluted, humidified target gas
must be continuously fed into the exposure
chamber during cartridge exposure. Measure
the flow rate of target compound standard gas
and dilution air to an accuracy of 5 percent.
A.8.7.4 Record the time, temperature, and
RH at the beginning, middle, and end of the
exposure time.
A.8.7.5 At the end of the exposure time,
remove the PSDs from the exposure chamber.
Record the exposure end time, chamber RH,
and temperature.
BILLING CODE 6560–50–P
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00174
Fmt 4701
Sfmt 4725
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.045
tkelley on DSK3SPTVN1PROD with RULES2
Figure A.l. Example Sorbent Tube Exposure Chamber
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00175
Fmt 4701
Sfmt 4725
E:\FR\FM\01DER2.SGM
01DER2
75351
ER01DE15.046
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
BILLING CODE 6560–50–C
tkelley on DSK3SPTVN1PROD with RULES2
A.9
Quality Control
A.9.1 Monitor and record the exposure
chamber temperature and RH during PSD
exposures.
A.9.2 Measure the flow rates of standards
and purified humified air immediately
following PSD exposures.
A.10
Calibration and Standardization
A.10.1 Follow the procedures described
in Method 325B Section 10.0 for calibration.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
A.10.2 Verify chamber concentration by
direct injection into a gas chromatograph
calibrated for the target compound(s) or by
collection of an integrated SUMMA canister
followed by analysis using a
preconcentration gas chromatographic
method such as EPA Compendium Method
TO–15, Determination of VOCs in Air
Collected in Specially-Prepared Canisters
and Analyzed By GC/MS.
A.10.2.1 To use direct injection gas
chromatography to verify the exposure
chamber concentration, follow the
procedures in Method 18 of 40 CFR part 60,
PO 00000
Frm 00176
Fmt 4701
Sfmt 4700
Appendix A–6. The method ASTM D6420–
99 (Reapproved 2010) (incorporated by
reference—see § 63.14) is an acceptable
alternative to EPA Method 18 of 40 CFR part
60).
Note: Direct injection gas chromatography
may not be sufficiently sensitive for all
compounds. Therefore, the whole gas
preconcentration sample and analysis
method may be required to measure at low
concentrations.
A.10.2.2 To verify exposure chamber
concentrations using SUMMA canisters,
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.047
75352
75353
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
prepare clean canister(s) and measure the
concentration of VOC collected in an
integrated SUMMA canister over the period
used for the evaluation (minimum 24 hours).
Analyze the TO–15 canister sample following
EPA Compendium Method TO–15.
A.10.2.3 Compare the theoretical
concentration of volatile material added to
the test chamber to the measured
concentration to confirm the chamber
operation. Theoretical concentration must
agree with the measured concentration
within 30 percent.
A.11
Analysis Procedure
Analyze the sorbent tubes following the
procedures described in Section 11.0 of
Method 325B.
A.12 Recordkeeping Procedures for
Sorbent Tube Evaluation
Keep records for the sorbent tube
evaluation to include at a minimum the
following information:
A.12.1 Sorbent tube description and
specifications.
A.12.2 Sorbent material description and
specifications.
A.12.3 Volatile analytes used in the
sampler test.
A.12.4 Chamber conditions including
flow rate, temperature, and relative humidity.
A.12.5 Relative standard deviation of the
sampler results at the conditions tested.
A.12.6 95 percent confidence limit on the
sampler overall accuracy.
A.12.7 The relative accuracy of the
sorbent tube results compared to the direct
chamber measurement by direct gas
chromatography or SUMMA canister
analysis.
A.13
Method Performance
A.13.1 Sorbent tube performance is
acceptable if the relative accuracy of the
passive sorbent sampler agrees with the
active measurement method by ±10 percent
at the 95 percent confidence limit and the
uptake ratio is equal to greater than 0.5 mL/
min (1 ng/ppm-min).
Note: For example, there is a maximum
deviation comparing Perkin-Elmer passive
type sorbent tubes packed with CarbopackTM
X of 1.3 to 10 percent compared to active
sampling using the following uptake rates.
1,3-butadiene
uptake rate
mL/min
CarbopackTM X (2 week) .........................................................
Estimated
detection limit
(2 week)
Benzene
uptake rates
mL/min
Estimated
detection limit
(2 week)
0.61 ± 0.11 a
0.1 ppbv
0.67 a
0.05 ppbv
a McClenny,
CarbopackTM
W.A., K.D. Oliver, H.H. Jacumin, Jr., E.H. Daughtrey, Jr., D.A. Whitaker. 2005. 24 h diffusive sampling of toxic VOCs in air onto
X solid adsorbent followed by thermal desorption/GC/MS analysis—laboratory studies. J. Environ. Monit. 7:248–256.
Cs = The concentration of target compound
in the standard cylinder (parts per
million by volume).
A.13.2.3 Determine the uptake rate of the
target gas being evaluated using Equation
A.2.
Tt = The exposure time (minutes).
A.13.2.4 Estimate the variance (relative
standard deviation (RSD)) of the intersampler results at each condition tested using
Equation A.3. RSD for the sampler is
estimated by pooling the variance estimates
from each test run.
Where:
Xi = The measured mass of analyte found on
sorbent tube i.
Xi = The mean value of all Xi.
n = The number of measurements of the
analyte.
A.13.2.4 Determine the percent relative
standard deviation of the inter-sampler
results using Equation A.4.
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00177
Fmt 4701
Sfmt 4700
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.049
Where:
Mx = The mass of analyte measured on the
sampling tube (hg).
Ce = The theoretical exposure chamber
concentration (hg/mL).
ER01DE15.048
FRt = The flow rate of all target compounds
from separate if multiple cylinders are
used (mL/min).
FRa = The flow rate of dilution air plus
moisture (mL/min).
ER01DE15.050
A.13.2.1 Calculate the theoretical
concentration of VOC standards using
Equation A.1.
Where:
Cf = The final concentration of standard in
the exposure chamber (ppbv).
FRi = The flow rate of the target compound
I (mL/min).
tkelley on DSK3SPTVN1PROD with RULES2
A13.2 Data Analysis and Calculations for
Method Evaluation
75354
Federal Register / Vol. 80, No. 230 / Tuesday, December 1, 2015 / Rules and Regulations
is determined based on the number of test
runs performed to evaluate the sorbent tube
and sorbent combination. For the minimum
test requirement of eight samplers tested at
two concentrations, the number of tests is 16
and the degrees of freedom are 15.
Where:
D95% = 95 percent confidence interval.
%RSD = percent relative standard deviation.
t0.95 = The Students t statistic for f degrees
of freedom at 95 percent confidence.
f = The number of degrees of freedom.
n = Number of samples.
A.13.2.6 Determine the relative accuracy
of the sorbent tube combination compared to
the active sampling results using Equation
A.6.
Where:
RA = Relative accuracy.
Xi = The mean value of all Xi.
Xi = The average concentration of analyte
measured by the active measurement
method.
D95% = 95 percent confidence interval.
A.14 Pollution Prevention
This method involves the use of ambient
concentrations of gaseous compounds that
post little or no pollution to the environment.
A.16
A.15 Waste Management
Expired calibration solutions should be
disposed of as hazardous materials.
[FR Doc. 2015–26486 Filed 11–30–15; 8:45 am]
References
1. ISO TC 146/SC 02 N 361 Workplace
atmospheres—Protocol for evaluating the
performance of diffusive samplers.
ER01DE15.052
ER01DE15.053
BILLING CODE 6560–50–P
VerDate Sep<11>2014
23:11 Nov 30, 2015
Jkt 238001
PO 00000
Frm 00178
Fmt 4701
Sfmt 9990
E:\FR\FM\01DER2.SGM
01DER2
ER01DE15.051
tkelley on DSK3SPTVN1PROD with RULES2
A.13.2.5 Determine the 95 percent
confidence interval for the sampler results
using Equation A.5. The confidence interval
Agencies
[Federal Register Volume 80, Number 230 (Tuesday, December 1, 2015)]
[Rules and Regulations]
[Pages 75177-75354]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2015-26486]
[[Page 75177]]
Vol. 80
Tuesday,
No. 230
December 1, 2015
Part II
Environmental Protection Agency
-----------------------------------------------------------------------
40 CFR Parts 60 and 63
Petroleum Refinery Sector Risk and Technology Review and New Source
Performance Standards; Final Rule
Federal Register / Vol. 80 , No. 230 / Tuesday, December 1, 2015 /
Rules and Regulations
[[Page 75178]]
-----------------------------------------------------------------------
ENVIRONMENTAL PROTECTION AGENCY
40 CFR Parts 60 and 63
[EPA-HQ-OAR-2010-0682; FRL-9935-40-OAR]
RIN 2060-AQ75
Petroleum Refinery Sector Risk and Technology Review and New
Source Performance Standards
AGENCY: Environmental Protection Agency (EPA).
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: This action finalizes the residual risk and technology review
conducted for the Petroleum Refinery source categories regulated under
national emission standards for hazardous air pollutants (NESHAP)
Refinery MACT 1 and Refinery MACT 2. It also includes revisions to the
Refinery MACT 1 and MACT 2 rules in accordance with provisions
regarding establishment of MACT standards. This action also finalizes
technical corrections and clarifications for the new source performance
standards (NSPS) for petroleum refineries to improve consistency and
clarity and address issues related to a 2008 industry petition for
reconsideration. Implementation of this final rule will result in
projected reductions of 5,200 tons per year (tpy) of hazardous air
pollutants (HAP) which will reduce cancer risk and chronic health
effects.
DATES: This final action is effective on February 1, 2016. The
incorporation by reference of certain publications for part 63 listed
in the rule is approved by the Director of the Federal Register as of
February 1, 2016. The incorporation by reference of certain
publications for part 60 listed in the rule were approved by the
Director of the Federal Register as of June 24, 2008.
ADDRESSES: The Environmental Protection Agency (EPA) has established a
docket for this action under Docket ID No. EPA-HQ-OAR-2010-0682. All
documents in the docket are listed on the www.regulations.gov Web site.
Although listed in the index, some information is not publicly
available, e.g., confidential business information (CBI) or other
information whose disclosure is restricted by statute. Certain other
material, such as copyrighted material, is not placed on the Internet
and will be publicly available only in hard copy form. Publicly
available docket materials are available either electronically through
https://www.regulations.gov, or in hard copy at the EPA Docket Center,
WJC West Building, Room Number 3334, 1301 Constitution Ave. NW.,
Washington, DC. The Public Reading Room hours of operation are 8:30
a.m. to 4:30 p.m. Eastern Standard Time (EST), Monday through Friday.
The telephone number for the Public Reading Room is (202) 566-1744, and
the telephone number for the Air and Radiation Docket and Information
Center is (202) 566-1742.
FOR FURTHER INFORMATION CONTACT: For questions about this final action,
contact Ms. Brenda Shine, Sector Policies and Programs Division,
Refining and Chemicals Group (E143-01), Office of Air Quality Planning
and Standards, U.S. Environmental Protection Agency, Research Triangle
Park, North Carolina, 27711; telephone number: (919) 541-3608; fax
number: (919) 541-0246; and email address: shine.brenda@epa.gov. For
specific information regarding the risk modeling methodology, contact
Mr. Ted Palma, Health and Environmental Impacts Division (C539-02),
Office of Air Quality Planning and Standards, U.S. Environmental
Protection Agency, Research Triangle Park, North Carolina 27711;
telephone number: (919) 541-5470; fax number: (919) 541-0840; and email
address: palma.ted@epa.gov. For information about the applicability of
the NESHAP to a particular entity, contact Ms. Maria Malave, Office of
Enforcement and Compliance Assurance, U.S. Environmental Protection
Agency, William Jefferson Clinton Building, 1200 Pennsylvania Ave. NW.,
Washington, DC 20460; telephone number: (202) 564-7027; fax number:
(202) 564-0050; and email address: malave.maria@epa.gov.
SUPPLEMENTARY INFORMATION:
Preamble Acronyms and Abbreviations. We use multiple acronyms and
terms in this preamble. While this list may not be exhaustive, to ease
the reading of this preamble and for reference purposes, the EPA
defines the following terms and acronyms here:
10/25 tpy emissions equal to or greater than 10 tons per year of a
single pollutant or 25 tons per year of cumulative pollutants
AEGL acute exposure guideline levels
APCD air pollution control devices
API American Petroleum Institute
BAAQMD Bay Area Air Quality Management District
BDT best demonstrated technology
BLD bag leak detectors
BSER best system of emission reductions
Btu/ft2 British thermal units per square foot
Btu/scf British thermal units per standard cubic foot
CAA Clean Air Act
CBI confidential business information
CCU catalytic cracking units
CDX Central Data Exchange
CEDRI Compliance and Emissions Data Reporting Interface
CEMS continuous emission monitoring system
CFR Code of Federal Regulations
CO carbon monoxide
CO2 carbon dioxide
CO2e carbon dioxide equivalents
COMS continuous opacity monitoring system
COS carbonyl sulfide
CPMS continuous parameter monitoring system
CRA Congressional Review Act
CRU catalytic reforming units
CS2 carbon disulfide
DCU delayed coking units
EPA Environmental Protection Agency
ERPG emergency response and planning guidelines
ERT Electronic Reporting Tool
ESP electrostatic precipitator
FCCU fluid catalytic cracking unit
FGCD fuel gas combustion device
FMP flare management plan
FR Federal Register
FTIR Fourier transform infrared spectroscopy
GC gas chromatograph
GHG greenhouse gases
H2S hydrogen sulfide
HAP hazardous air pollutants
HCl hydrogen chloride
HCN hydrogen cyanide
HF hydrogen fluoride
HFC highest fenceline concentration
HI hazard index
HQ hazard quotient
ICR information collection request
IRIS Integrated Risk Information System
km kilometers
LAER lowest achievable emission rate
lb/day pounds per day
LDAR leak detection and repair
LEL lower explosive limit
LTD long tons per day
MACT maximum achievable control technology
MIR maximum individual risk
mph miles per hour
MPV miscellaneous process vent
NAICS North American Industry Classification System
NESHAP National Emissions Standards for Hazardous Air Pollutants
NFS near-field interfering source
NHVCZ combustion zone net heating value
Ni nickel
NOX nitrogen oxides
NRDC Natural Resources Defense Council
NSPS new source performance standards
NTTAA National Technology Transfer and Advancement Act
OAQPS Office of Air Quality Planning and standards
OECA Office of Enforcement and Compliance Assurance
OEHHA Office of Environmental Health Hazard Assessment
OEL open-ended line
OMB Office of Management and Budget
PM particulate matter
PM2.5 particulate matter 2.5 micrometers in diameter and
smaller
ppbv parts per billion by volume
ppm parts per million
[[Page 75179]]
ppmv parts per million by volume
PRA Paperwork Reduction Act
PRD pressure relief device \1\
---------------------------------------------------------------------------
\1\ This term is common vernacular to describe the variety of
devices regulated as pressure relief valves subject to the
requirements in 40 CFR part 63 subpart CC.
---------------------------------------------------------------------------
psia pounds per square inch absolute
psig pounds per square inch gauge
REL reference exposure level
REM Model Refinery Emissions Model
RFA Regulatory Flexibility Act
RTC response to comment
RTR Risk and Technology Review
SAB Science Advisory Board
SBA Small Business Administration
SCAQMD South Coast Air Quality Management District
SCR selective catalytic reduction
SISNOSE significant economic impact on a substantial number of small
entities
SO2 sulfur dioxide
SRP sulfur recovery plant
SRU sulfur recovery unit
SSM startup, shutdown and malfunction
TOSHI target organ-specific hazard index
tpy tons per year
UMRA Unfunded Mandates Reform Act
URE unit risk estimate
UV-DOAS ultraviolet differential optical absorption spectroscopy
VCS voluntary consensus standards
VOC volatile organic compounds
[deg]F degrees Fahrenheit
[Delta]C the concentration difference between the highest measured
concentration and the lowest measured concentration
[mu]g/m\3\ micrograms per cubic meter
Background Information. On June 30, 2014, the EPA proposed
revisions to both of the petroleum refinery NESHAP based on our
residual risk and technology review (RTR). In that action, we also
proposed to revise the NESHAP pursuant to CAA section 112(d)(2) and
(3), to revise the SSM provisions in the NESHAP, and to make technical
corrections to the NSPS to address issues related to reconsideration of
the final NSPS subpart Ja rule in 2008. In this action, we are
finalizing decisions and revisions for these rules. We summarize some
of the more significant comments received regarding the proposed rule
and provide our responses in this preamble. A summary of all other
public comments on the proposal and the EPA's responses to those
comments is provided in the ``Response to Comment'' document, which is
available in Docket ID No. EPA-HQ-OAR-2010-0682. The ``track changes''
version of the regulatory language that incorporates the changes in
this final action is also available in the docket for this rulemaking.
Organization of this Document. This preamble is organized as
follows:
I. General Information
A. Does this action apply to me?
B. Where can I get a copy of this document and other related
information?
C. Judicial Review and Administrative Reconsideration
II. Background
A. What is the statutory authority for this action?
B. How do the NESHAP and NSPS regulate air pollutant emissions
from refineries?
C. What changes did we propose for the Petroleum Refinery NESHAP
and NSPS in our June 30, 2014 RTR proposal?
III. What is included in this final rule?
A. What are the final NESHAP amendments based on the risk review
for the Petroleum Refinery source categories?
B. What are the final NESHAP amendments based on the technology
review for the Petroleum Refinery source categories?
C. What are the final NESHAP amendments pursuant to section
112(d)(2) & (3) for the Petroleum Refinery source categories?
D. What are the final NESHAP amendments addressing emissions
during periods of SSM?
E. What other revisions to the NESHAP and NSPS are being
promulgated?
F. What are the requirements for submission of performance test
data to the EPA?
G. What are the effective and compliance dates of the NESHAP and
NSPS?
H. What materials are being incorporated by reference?
IV. What is the rationale for our final decisions and amendments to
the Petroleum Refinery NESHAP and NSPS?
A. Residual Risk Review for the Petroleum Refinery Source
Categories
B. Technology Review for the Petroleum Refinery Source
Categories
C. Refinery MACT Amendments Pursuant to CAA section 112(d)(2)
and (d)(3)
D. NESHAP Amendments Addressing Emissions During Periods of SSM
E. Technical Amendments to Refinery MACT 1 and 2
F. Technical Amendments to Refinery NSPS Subparts J and Ja
V. Summary of Cost, Environmental, and Economic Impacts and
Additional Analyses Conducted
A. What are the affected facilities, the air quality impacts and
cost impacts?
B. What are the economic impacts?
C. What are the benefits?
D. Impacts of This Rulemaking on Environmental Justice
Populations
E. Impacts of This Rulemaking on Children's Health
VI. Statutory and Executive Order Reviews
A. Executive Orders 12866: Regulatory Planning and Review and
Executive Order 13563: Improving Regulation and Regulatory Review
B. Paperwork Reduction Act (PRA)
C. Regulatory Flexibility Act (RFA)
D. Unfunded Mandates Reform Act (UMRA)
E. Executive Order 13132: Federalism
F. Executive Order 13175: Consultation and Coordination With
Indian Tribal Governments
G. Executive Order 13045: Protection of Children From
Environmental Health Risks and Safety Risks
H. Executive Order 13211: Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution or Use
I. National Technology Transfer and Advancement Act (NTTAA) and
1 CFR part 51
J. Executive Order 12898: Federal Actions To Address
Environmental Justice in Minority Populations and Low-Income
Populations
K. Congressional Review Act (CRA)
I. General Information
A. Does this action apply to me?
Regulated Entities. Categories and entities potentially regulated
by this action are shown in Table 1 of this preamble.
Table 1--Industrial Source Categories Affected by This Final Action
------------------------------------------------------------------------
NAICS \a\
NESHAP and source category Code
------------------------------------------------------------------------
Petroleum Refining Industry................................. 324110
------------------------------------------------------------------------
\a\ North American Industry Classification System.
Table 1 of this preamble is not intended to be exhaustive, but
rather to provide a guide for readers regarding entities likely to be
affected by the final action for the source categories listed. To
determine whether your facility is affected, you should examine the
applicability criteria in the appropriate NESHAP or NSPS. If you have
any questions regarding the applicability of any aspect of these NESHAP
or NSPS, please contact the appropriate person listed in the preceding
FOR FURTHER INFORMATION CONTACT section of this preamble.
B. Where can I get a copy of this document and other related
information?
In addition to being available in the docket, an electronic copy of
this final action will also be available on the Internet through the
Technology Transfer Network (TTN) Web site, a forum for information and
technology exchange in various areas of air pollution control.
Following signature by the EPA Administrator, the EPA will post a copy
of this final action at: https://www.epa.gov/ttn/atw/petref.html.
Following publication in the Federal Register, the EPA will post the
Federal Register version and key technical documents at this same Web
site.
Additional information is available on the RTR Web site at https://www.epa.gov/ttn/atw/rrisk/rtrpg.html. This information includes an
overview of the RTR program, links to project Web sites
[[Page 75180]]
for the RTR source categories, and detailed emissions and other data we
used as inputs to the risk assessments.
C. Judicial Review and Administrative Reconsideration
Under CAA section 307(b)(1), judicial review of this final action
is available only by filing a petition for review in the United States
Court of Appeals for the District of Columbia Circuit by February 1,
2016. Under CAA section 307(b)(2), the requirements established by this
final rule may not be challenged separately in any civil or criminal
proceedings brought by the EPA to enforce the requirements.
Section 307(d)(7)(B) of the CAA further provides that ``[o]nly an
objection to a rule or procedure which was raised with reasonable
specificity during the period for public comment (including any public
hearing) may be raised during judicial review.'' This section also
provides a mechanism for the EPA to reconsider the rule ``[i]f the
person raising an objection can demonstrate to the Administrator that
it was impracticable to raise such objection within [the period for
public comment] or if the grounds for such objection arose after the
period for public comment (but within the time specified for judicial
review) and if such objection is of central relevance to the outcome of
the rule.'' Any person seeking to make such a demonstration should
submit a Petition for Reconsideration to the Office of the
Administrator, U.S. EPA, Room 3000, WJC Building, 1200 Pennsylvania
Ave. NW., Washington, DC 20460, with a copy to both the person(s)
listed in the preceding FOR FURTHER INFORMATION CONTACT section, and
the Associate General Counsel for the Air and Radiation Law Office,
Office of General Counsel (Mail Code 2344A), U.S. EPA, 1200
Pennsylvania Ave. NW., Washington, DC 20460.
II. Background
A. What is the statutory authority for this action?
1. NESHAP
Section 112 of the CAA establishes a two-stage regulatory process
to address emissions of hazardous air pollutants (HAP) from stationary
sources. In the first stage, we must identify categories of sources
emitting one or more of the HAP listed in CAA section 112(b) and then
promulgate technology-based NESHAP for those sources. ``Major sources''
are those that emit, or have the potential to emit, any single HAP at a
rate of 10 tons per year (tpy) or more, or 25 tpy or more of any
combination of HAP. For major sources, these standards are commonly
referred to as maximum achievable control technology (MACT) standards
and must reflect the maximum degree of emission reductions of HAP
achievable (after considering cost, energy requirements, and non-air
quality health and environmental impacts). In developing MACT
standards, CAA section 112(d)(2) directs the EPA to consider the
application of measures, processes, methods, systems or techniques,
including but not limited to those that reduce the volume of or
eliminate HAP emissions through process changes, substitution of
materials, or other modifications; enclose systems or processes to
eliminate emissions; collect, capture, or treat HAP when released from
a process, stack, storage, or fugitive emissions point; are design,
equipment, work practice, or operational standards; or any combination
of the above.
For these MACT standards, the statute specifies certain minimum
stringency requirements, which are referred to as MACT floor
requirements, and which may not be based on cost considerations. See
CAA section 112(d)(3). For new sources, the MACT floor cannot be less
stringent than the emission control achieved in practice by the best-
controlled similar source. The MACT standards for existing sources can
be less stringent than floors for new sources, but they cannot be less
stringent than the average emission limitation achieved by the best-
performing 12-percent of existing sources in the category or
subcategory (or the best-performing 5 sources for categories or
subcategories with fewer than 30 sources). In developing MACT
standards, we must also consider control options that are more
stringent than the floor, under CAA section 112(d)(2). We may establish
standards more stringent than the floor, based on the consideration of
the cost of achieving the emissions reductions, any non-air quality
health and environmental impacts, and energy requirements.
In the second stage of the regulatory process, the CAA requires the
EPA to undertake 2 different analyses, which we refer to as the
technology review and the residual risk review. Under the technology
review, we must review the technology-based standards and revise them
``as necessary (taking into account developments in practices,
processes, and control technologies)'' no less frequently than every
eight years, pursuant to CAA section 112(d)(6). Under the residual risk
review, we must evaluate the risk to public health remaining after
application of the technology-based standards and revise the standards,
if necessary, to provide an ample margin of safety to protect public
health or to prevent, taking into consideration costs, energy, safety
and other relevant factors, an adverse environmental effect. The
residual risk review is required within eight years after promulgation
of the technology-based standards, pursuant to CAA section 112(f). In
conducting the residual risk review, if the EPA determines that the
current standards provide an ample margin of safety to protect public
health, it is not necessary to revise the MACT standards pursuant to
CAA section 112(f).\2\ For more information on the statutory authority
for this rule, see 79 FR 36879.
---------------------------------------------------------------------------
\2\ The U.S. Court of Appeals has affirmed this approach of
implementing CAA section 112(f)(2)(A): NRDC v. EPA, 529 F.3d 1077,
1083 (D.C. Cir. 2008) (``If EPA determines that the existing
technology-based standards provide an `ample margin of safety,' then
the Agency is free to readopt those standards during the residual
risk rulemaking.'').
---------------------------------------------------------------------------
2. NSPS
Section 111 of the CAA establishes mechanisms for controlling
emissions of air pollutants from stationary sources. Section 111(b) of
the CAA provides authority for the EPA to promulgate NSPS that apply
only to newly constructed, reconstructed and modified sources. Once the
EPA has elected to set NSPS for new and modified sources in a given
source category, CAA section 111(d) calls for regulation of existing
sources, with certain exceptions explained below.
Specifically, section 111(b) of the CAA requires the EPA to
establish emission standards for any category of new and modified
stationary sources that the Administrator, in his or her judgment,
finds ``causes, or contributes significantly to, air pollution which
may reasonably be anticipated to endanger public health or welfare.''
The EPA has previously made endangerment findings under this section of
the CAA for more than 60 stationary source categories and subcategories
that are now subject to NSPS.
Section 111 of the CAA gives the EPA significant discretion to
identify the affected facilities within a source category that should
be regulated. To define the affected facilities, the EPA can use size
thresholds for regulation and create subcategories based on source
type, class or size. Emission limits also may be established either for
equipment within a facility or for an entire facility. For listed
source categories, the EPA must establish ``standards of performance''
that apply
[[Page 75181]]
to sources that are constructed, modified or reconstructed after the
EPA proposes the NSPS for the relevant source category.\3\
---------------------------------------------------------------------------
\3\ Specific statutory and regulatory provisions define what
constitutes a modification or reconstruction of a facility. 40 CFR
60.14 provides that an existing facility is modified and, therefore,
subject to an NSPS, if it undergoes any physical change in the
method of operation which increases the amount of any air pollutant
emitted by such source or which results in the emission of any air
pollutant not previously emitted. 40 CFR 60.15, in turn, provides
that a facility is reconstructed if components are replaced at an
existing facility to such an extent that the capital cost of the new
equipment/components exceed 50-percent of what is believed to be the
cost of a completely new facility.
---------------------------------------------------------------------------
The EPA also has significant discretion to determine the
appropriate level for the standards. Section 111(a)(1) of the CAA
provides that NSPS are to reflect the degree of emission limitation
achievable through the application of the best system of emission
reduction which (taking into account the cost of achieving such
reduction and any non-air quality health and environmental impact and
energy requirements) the Administrator determines has been adequately
demonstrated. This level of control is commonly referred to as best
demonstrated technology (BDT) or the best system of emission reduction
(BSER). The standard that the EPA develops, based on the BSER
achievable at that source, is commonly a numerical emission limit,
expressed as a performance level (i.e., a rate-based standard).
Generally, the EPA does not prescribe a particular technological system
that must be used to comply with a NSPS. Rather, sources remain free to
elect whatever combination of measures will achieve equivalent or
greater control of emissions.
Costs are also considered in evaluating the appropriate standard of
performance for each category or subcategory. The EPA generally
compares control options and estimated costs and emission impacts of
multiple, specific emission standard options under consideration. As
part of this analysis, the EPA considers numerous factors relating to
the potential cost of the regulation, including industry organization
and market structure, control options available to reduce emissions of
the regulated pollutant(s) and costs of these controls.
B. How do the NESHAP and NSPS regulate air pollutant emissions from
refineries?
The EPA promulgated the petroleum refinery NESHAP pursuant to CAA
section 112(d)(2) and (3) for refineries located at major sources in
two separate rules. On August 18, 1995, the first petroleum refinery
MACT standard was promulgated in 40 CFR part 63, subpart CC (60 FR
43620). This rule is known as ``Refinery MACT 1'' and covers the
``Sources Not Distinctly Listed,'' meaning it includes all emissions
sources from petroleum refinery process units, except those listed
separately under the section 112(c) source category list and expected
to be regulated by other MACT standards (for example, boilers and
process heaters). Some of the emission sources regulated in Refinery
MACT 1 include miscellaneous process vents (MPV), storage vessels,
wastewater, equipment leaks, gasoline loading racks, marine tank vessel
loading and heat exchange systems.
On April 11, 2002 (67 FR 17762), EPA promulgated a second MACT
standard regulating certain process vents that were listed as a
separate source category under CAA section 112(c) and that were not
addressed as part of the Refinery MACT 1. This standard, which is
referred to as ``Refinery MACT 2'', covers process vents on catalytic
cracking units (CCU) (including FCCU), CRU and SRU and is codified as
40 CFR part 63, subpart UUU.
Finally, on October 28, 2009, we revised Refinery MACT 1 by adding
MACT standards for heat exchange systems, which the EPA had not
addressed in the original 1995 Refinery MACT 1 rule (74 FR 55686). In
this same 2009 action, we updated the cross-references to the General
Provisions in 40 CFR part 63. On June 20, 2013 (78 FR 37133), we
promulgated minor revisions to the heat exchange provisions of Refinery
MACT 1.
On September 27, 2012, Air Alliance Houston, California Communities
Against Toxics and other environmental and public health groups filed a
lawsuit alleging that the EPA missed statutory deadlines to review and
revise Refinery MACT 1 and 2. The EPA reached an agreement to settle
that litigation and entered into a Consent Decree. The Consent Decree
provides for the Administrator to sign a final action no later than
September 30, 2015.
Refinery NSPS subparts J and Ja regulated criteria pollutant
emissions, including particulate matter (PM), sulfur dioxide
(SO2), nitrogen oxides (NOX) and carbon monoxide
(CO) from FCCU catalyst regenerators, fuel gas combustion devices
(FGCD) and sulfur recovery plants. Refinery NSPS subpart Ja also
regulates criteria pollutant emissions from fluid coking units and DCU.
The NSPS for petroleum refineries (40 CFR part 60, subpart J) were
promulgated in 1974, amended in 1976 and amended again in 2008,
following a review of the standards. As part of the review that led to
the 2008 amendments to the Refinery NSPS subpart J, the EPA developed
separate standards of performance for new process units (40 CFR part
60, subpart Ja). However, the EPA received multiple petitions for
reconsideration on issues related to those standards. The Administrator
granted the petitions for reconsideration. The EPA addressed petition
issues related to process heaters and flares by promulgating amendments
to the Refinery NSPS subparts J and Ja on September 12, 2012 (77 FR
56422). In this action, we are finalizing technical corrections and
clarifications to NSPS subparts J and Ja raised by American Petroleum
Institute (API) in their 2008 petition for reconsideration that were
not addressed by the final NSPS amendments of 2012.
The petroleum refining industry consists of facilities that engage
in converting crude oil into refined products, including liquefied
petroleum gas, gasoline, kerosene, aviation fuel, diesel fuel, fuel
oils, lubricating oils and feedstocks for the petrochemical industry.
Currently, 142 facilities have emission sources regulated by either or
both Refinery MACT 1 and 2.
Petroleum refinery activities start with the receipt of crude oil
for storage at the refinery, include all the petroleum handling and
refining operations, and terminate with loading of refined products
into pipelines, tank or rail cars, tank trucks, or ships or barges that
take products from the refinery to distribution centers. Petroleum-
specific process units include FCCU and CRU. Other units and processes
found at petroleum refineries (as well as at many other types of
manufacturing facilities) include storage vessels and wastewater
treatment plants. HAP emitted by this industry include organics (e.g.,
acetaldehyde, benzene, formaldehyde, hexane, phenol, naphthalene, 2-
methylnaphthalene, dioxins, furans, ethyl benzene, toluene and xylene);
reduced sulfur compounds (i.e., carbonyl sulfide (COS), carbon
disulfide (CS2))); inorganics (e.g., hydrogen chloride (HCl), hydrogen
cyanide (HCN), chlorine, hydrogen fluoride (HF)); and metals (e.g.,
antimony, arsenic, beryllium, cadmium, chromium, cobalt, lead, mercury,
manganese and nickel (Ni)). This industry also emits criteria
pollutants and other non-HAP, including NOX, PM,
SO2, volatile organic compounds (VOC), CO, greenhouse gases
(GHG) and total reduced sulfur.
[[Page 75182]]
C. What changes did we propose for the Petroleum Refinery NESHAP and
NSPS in our June 30, 2014, RTR proposal?
On June 30, 2014, the EPA published a proposed rule in the Federal
Register addressing the RTR for the Petroleum Refinery NESHAP, 40 CFR
part 63, subparts CC and UUU. The proposal also included changes
pursuant to section 112(d)(2) and (3) and technical revisions to the
NSPS. Specifically, we proposed:
(1) Pursuant to CAA sections 112(d)(2) and (3):
a. Refinery MACT 1:
Adding MACT Standards for DCU decoking operations.
Adding operational requirements for flares used as APCD in
Refinery MACT 1 and 2.
Adding requirements and clarifications for vent control
bypasses in Refinery MACT 1.
b. Refinery MACT 2:
Revising the CRU purge vent exemption.
(2) Pursuant to CAA sections 112(d)(6) and 112(f)(2):
Revising Refinery MACT 1 to cross-reference the
corresponding storage vessel requirements in the Generic MACT (40 CFR
part 63, subpart WW, as applicable), and revising the definition of
Group 1 storage vessels to include smaller capacity storage vessels and
to include storage vessels storing materials with lower vapor
pressures.
(3) Pursuant to CAA section 112(d)(6):
a. Refinery MACT 1:
Allowing refineries to meet the leak detection and repair
(LDAR) requirements in Refinery MACT 1 by monitoring for leaks using
optical gas imaging in place of EPA Method 21, once the monitoring
protocol set forth in Appendix K is promulgated.
Amending the Marine Tank Vessel Loading Operations NESHAP,
40 CFR part 63, subpart Y, to delete the exclusion for marine vessel
loading operations at petroleum refineries.
Establishing a fenceline monitoring work practice standard
to improve the management of fugitive emissions.
b. Refinery MACT 2:
Incorporating requirements consistent with those in
Refinery NSPS subpart Ja for FCCU including:
Requiring the use of 3-hour averages rather than daily
averages for parameter operating limits (e.g., depending on the type of
control device: Opacity, total power, secondary current, pressure drop,
and/or liquid-to-gas ratio).
Removing the Refinery NSPS subpart J incremental PM
emissions allowance for post combustion devices when burning liquid or
solid fuels, and removing the 30 percent opacity limit for units
complying with NSPS subpart J.
Adding requirements for FCCU controls to include bag leak
detectors (BLD) as an option to continuous opacity monitoring system
(COMS).
Incorporating total power and the secondary current
operating limits for electrostatic precipitators (ESP).
Requiring daily checks of the air or water pressure to the
spray nozzles on jet ejector-type wet scrubber or other type of wet
scrubber equipped with atomizing spray nozzles.
Requiring FCCU periodic performance testing on a frequency
of once every 5 years, as opposed to the current rule, which only
requires an initial performance test.
Including a correlation equation for the use of oxygen-
enriched air for SRU.
Allowing SRU subject to Refinery NSPS subpart Ja with a
capacity greater than 20 long tons per day (LTD) to comply with
Refinery NSPS subpart Ja as a means of complying with Refinery MACT 2.
(4) Other proposed changes include:
Removing exemptions from the rule requirements for periods
of SSM in order to ensure that the NESHAP are consistent with the court
decision in Sierra Club v. EPA, 551 F. 3d 1019 (D.C. Cir. 2008).
Clarifying requirements related to open-ended valves or
lines.
Adding electronic reporting requirements.
Updating the General Provisions cross-reference tables.
Making technical corrections and clarifications to NSPS
subparts J and Ja.
III. What is included in this final rule?
This action finalizes the EPA's determinations pursuant to the RTR
provisions of CAA section 112 for the Petroleum Refinery source
categories and amends the Petroleum Refinery NESHAP based on those
determinations. This action also finalizes other changes to the NESHAP
including revising Refinery MACT 1 and 2 pursuant to CAA section 112
(d)(2) and (3), including revising requirements for flares and pressure
relief devices (PRD). This action finalizes changes to the SSM
provisions to ensure that the subparts are consistent with the court
decision in Sierra Club v. EPA, 551 F. 3d 1019 (D.C. Cir. 2008), adds
electronic reporting requirements in Refinery MACT 1 and 2; and updates
the General Provisions cross-reference tables. Finally, this action
finalizes technical corrections and clarifications to Refinery NSPS
subparts J and Ja to address issues raised in the reconsideration of
these rules.
A. What are the final NESHAP amendments based on the risk review for
the Petroleum Refinery source categories?
The EPA is promulgating final amendments to the Petroleum Refinery
NESHAP pursuant to CAA section 112(f) that expand the existing Refinery
MACT 1 control requirements and extend these requirements to smaller
tanks and tanks with lower vapor pressures. Specifically, consistent
with the proposal, the EPA is amending Refinery MACT 1 by revising the
definition of Group 1 storage vessels to include storage vessels with
capacities greater than or equal to 20,000 gallons but less than 40,000
gallons if the maximum true vapor pressure is 1.0 psia or greater and
to include storage tanks greater than 40,000 gallons if the maximum
true vapor pressure is 0.75 psia or greater. The EPA is also adding a
cross-reference to the storage vessel requirements in the Generic MACT
(40 CFR part 63, subpart WW and subpart CC), which include requirements
for guide pole controls and other fittings as well as inspection
requirements. After considering the public comments, the final
amendments include minor changes from our proposed requirements to
clarify language and correct typographical and referencing errors.
B. What are the final NESHAP amendments based on the technology review
for the Petroleum Refinery source categories?
1. Refinery MACT 1
We determined that there are developments in practices, processes
and control technologies that warrant revisions to the MACT standards
for this source category. Therefore, to satisfy the requirements of CAA
section 112(d)(6), we are revising the MACT standards to amend 40 CFR
part 63, subpart Y to delete the exclusion for marine vessel loading
operations at petroleum refineries. Removing this exclusion will
require small marine vessel loading operations (i.e., operations with
HAP emissions less than 10/25 tpy) and offshore marine vessel loading
operations to use submerged filling based on the cargo filling line
requirements in 46 CFR 153.282, as proposed.
We are also finalizing a fenceline monitoring work practice
standard to improve the management of fugitive emissions and finalizing
EPA Methods 325A and 325B to support the work
[[Page 75183]]
practice, with some changes from proposal to address issues raised by
commenters. Key revisions include: New provisions for reduced
monitoring for facilities with consistently low fenceline
concentrations; requirements for alternatives to passive monitoring;
revised placement guidance to allow perimeter monitoring within a
facility's property boundary provided all sources are encompassed
within the monitoring perimeter; reductions in the number of monitors
required for subareas and segregated areas; clarifications on monitor
placement for internal roadways or other right-of-ways and marine
docks; and revised timelines for submitting periodic reports (quarterly
rather than semiannually) and implementing the work practice standard
(2 years after promulgation rather than 3 years as proposed). We are
also revising Refinery MACT 1 storage vessel requirements as described
above under the risk review, as proposed.
2. Refinery MACT 2
We determined that there are developments in practices, processes
and control technologies that warrant revisions to the MACT standards
for this source category. Therefore, to satisfy the requirements of CAA
section 112(d)(6), we are revising the Refinery MACT 2 standard for
FCCU subject to Refinery NSPS subpart J or those electing to comply
with the Refinery NSPS subpart J requirements. As proposed, we are
removing the incremental PM limit when burning liquid or solid fuels.
We are finalizing a 20-percent opacity operating limit evaluated on a
3-hour average, which differs from the proposal to eliminate the 30-
percent opacity limit and instead allow only for a site-specific
opacity operating limit or control device parameter monitoring. As
proposed, we are finalizing requirements to make Refinery MACT 2
consistent with Refinery NSPS subpart Ja for FCCU by including 3-hour
averages rather than daily averages for parameter operating limits, and
by including 3-hour averages rather than daily averages for the site-
specific opacity operating limit. We are also finalizing requirements,
as proposed, for FCCU controls to include adding BLD as an option to
COMS, incorporating total power and the secondary current operating
limits for ESP and requiring daily checks of the air or water pressure
to the spray nozzles on jet ejector-type wet scrubbers or other types
of wet scrubbers equipped with atomizing spray nozzles.
Finally, we are finalizing, as proposed, requirements for FCCU
periodic performance testing at a frequency of once every 5 years
rather than the current requirements for a one-time initial performance
test. However, for owners or operators complying with the Refinery NSPS
subpart J option (with the 20-percent opacity operating limit discussed
above), if the PM emissions are within 80-percent of the PM limit
during any periodic performance test (i.e., emissions exceed 0.8 lb PM/
1,000 lbs of coke burn-off), the refinery owner or operator must
conduct subsequent performance tests on an annual basis. Based on
comments received, we are also adding requirements in the final rule
for owners or operators of FCCU to conduct a one-time test for HCN
emissions from the FCCU concurrent with their first periodic
performance test, which must be conducted on or before August 1, 2017
for all FCCU subject to Refinery MACT 2.
For SRU, as proposed, we are finalizing a correlation equation for
the use of oxygen-enriched air. Additionally, as proposed, we are
finalizing requirements to allow sulfur recovery plants subject to
Refinery NSPS subpart Ja with a capacity greater than 20 LTD to comply
with Refinery NSPS subpart Ja as a means of complying with Refinery
MACT 2.
C. What are the final NESHAP amendments pursuant to section 112(d)(2) &
(3) for the Petroleum Refinery source categories?
1. Refinery MACT 1
We are finalizing MACT standards for DCU decoking operations that
require that each coke drum be depressured to a closed blowdown system
until the coke drum pressure is 2 psig with minor revisions from
proposal. Specifically, we are finalizing provisions for existing DCU
affected sources to average over a 60-cycle (i.e., 60 batch) basis to
comply with the 2 psig limit, rather than the proposed requirement to
meet the 2 psig limit on a per venting event basis. In addition, we are
finalizing requirements for new DCU affected sources to depressure to
2.0 psig on a per-event, not-to-exceed basis, adding one significant
digit to the limit for new DCU affected sources. For both new and
existing DCU affected sources, we are finalizing specific provisions
for DCU with water overflow design and for double quenching.
We are finalizing operational requirements and the associated
monitoring, recordkeeping and reporting requirements for flares used as
APCD in Refinery MACT 1 and 2 with revisions to the requirements
proposed. Prior to these amendments, Refinery MACT 1 and 2 cross-
referenced the General Provisions requirements at 40 CFR 63.11(b). As
proposed, this final action replaces the cross reference to the General
Provisions and incorporates enhanced flare operational requirements
directly into the Refinery MACT regulations. As proposed, the final
rule amendments require that refinery flares operate with continuously
lit pilot flames at all times. Consistent with our proposal, we are
finalizing requirements for flares to operate with no visible emissions
and comply with consolidated requirements related to flare tip
velocity, but in the final rule these direct emissions limits apply
when flare vent gas flow is below the smokeless capacity of the flare
rather than at all times. Above the smokeless capacity of the flare, we
are establishing a work practice standard related to the visible
emissions and velocity limits; these work practice standards are
described in more detail in section III.D.1 of this preamble.
We are finalizing new operational requirements related to
combustion zone gas properties with revisions from proposal. In
response to comments on the proposal, we are finalizing requirements
that flares meet a minimum operating limit of 270 BTU/scf NHVcz on a
15-minute average, and are allowing refinery owners or operators to use
a corrected heat content of 1,212 BTU/scf for hydrogen to demonstrate
compliance with this operating limit. We had proposed two separate sets
of limits, one being more stringent if an olefins/hydrogen mixture was
present in the waste gas. For each set of limits, we proposed three
different alternative combustion zone operating limits: One based on
the combustion zone net heat content with no correction for the heat
content of hydrogen, one based on the lower flammability limit and one
based on the combustibles concentration. We proposed that these limits
be determined on a 15-minute ``feed-forward'' block average approach
(i.e., compositional data are collected every 15 minutes, after which
adjustments are made). We have included an additional option for
refiners to comply where more frequent data are collected (using direct
net heating value monitoring) to calculate the combustion limit using
net heating value data from the same 15-minute block period. We are
simplifying the compliance approach to a single operating limit based
only on the combustion zone net heating value (with a hydrogen
correction). As proposed, we are requiring refinery owners or operators
to characterize the composition of waste gas, assist gas and
[[Page 75184]]
fuel to demonstrate compliance with the operational requirements.
As proposed, we are also finalizing in this rule a burden reduction
option to use grab sampling every 8 hours rather than continuous vent
gas composition or heat content monitors. We are also including, based
on public comment, provisions to conduct limited initial sampling and
process knowledge to characterize flare gas composition for flares in
``dedicated'' service as an alternative to collecting grab samples
during each specific event. We are finalizing a requirement for daily
visible emissions observations as proposed, but, based on public
comment, we are allowing owners or operators to use video surveillance
cameras to demonstrate compliance with the visible emissions limit as
an alternative to the daily visible emissions observations.
For PRD, we are finalizing requirements for monitoring systems that
are capable of identifying and recording the time and duration of each
pressure release to the atmosphere, as proposed. Certain PRD with low
set pressures or low emission potential or in liquid service would not
be subject to these monitoring requirements. We are finalizing
requirements to minimize or prevent atmospheric releases of HAP through
PRD. Instead of the proposed prohibition on such releases, we are
finalizing work practice requirements that require both preventive
measures as well as root cause analysis and corrective action that will
incentivize refinery owners or operators to eliminate the causes of the
releases.
We are finalizing requirements for bypass lines with minor
revisions from those proposed. Specifically, we are not adopting the
proposed requirement to install quantitative flow monitors and thus are
leaving in place the requirement to use flow indicators on bypass
lines. In addition, we are maintaining the requirements to estimate and
report the quantity of organic HAP released. In response to public
comment, we are also clarifying changes to remove the proposed
reference to air intrusion and specifying that reporting of bypasses is
only required when ``regulated material'' is discharged to the
atmosphere as a result of a bypass of a control device.
We are also finalizing revisions to the definition of miscellaneous
process vent, as proposed. These revisions include deletion of
exclusions associated with episodic releases and vents from in situ
sampling systems. As proposed, the final amendments require that these
vents must meet the standards applicable to MPV.
2. Refinery MACT 2
For CRU vents, we are finalizing the vessel pressure limit
exclusion of 5 psig to apply only to passive depressurization, as
proposed.
D. What are the final NESHAP amendments addressing emissions during
periods of SSM?
We are finalizing, as proposed, changes to Refinery MACT 1 and 2 to
eliminate the SSM exemption. Consistent with Sierra Club v. EPA, 551 F.
3d 1019 (D.C. Cir. 2008), the EPA has established standards in this
rule that apply at all times. EPA is revising Table 6 of subpart CC of
40 CFR part 63 and Table 44 to subpart UUU of 40 CFR part 63 (the
General Provisions Applicability Tables) to change several references
related to requirements that apply during periods of SSM. We also are
eliminating or revising certain recordkeeping and reporting
requirements related to the eliminated SSM exemptions. We also are
removing or modifying inappropriate, unnecessary or redundant language
in the absence of the SSM exemption. Further, for certain emission
sources in both MACT 1 and 2, we are establishing standards to address
emissions during these periods. These are described below.
1. Refinery MACT 1
We are finalizing a work practice standard for PRD that requires
refinery owners or operators to establish prevention measures for each
PRD in organic HAP service. Under the work practice standard, where a
direct release occurs, the refinery is required to perform root cause
analysis and implement corrective action. The work practice standard
also limits the number of events that a PRD may release to the
atmosphere during a 3-year period, as explained further in the section
IV.D. of this preamble.
We are also finalizing a work practice standard for emergency
flaring events that requires refinery owners or operators to establish
prevention measures, including the development of a flare management
plan (FMP), and perform root cause analysis and implement corrective
action following flaring events during which the velocity of waste gas
going to the flare or visible emissions limits (i.e., opacity) at the
flare tip are exceeded, and to limit the number of these events allowed
in a 3-year period, as explained further in section IV.D. of this
preamble. Both of these work practice standards are consistent with the
EPA's goal to improve the effectiveness of the rules. These
requirements will provide a strong incentive for facilities, over time,
to better operate their processes to prevent PRD and flare releases.
We are also finalizing requirements for opening process equipment
to the atmosphere during maintenance events after draining and purging
to a closed system, provided the hydrocarbon content is less than or
equal to 10-percent of the lower explosive limit (LEL). For those
situations where 10-percent LEL cannot be demonstrated, the equipment
may be opened and vented to the atmosphere if the pressure is less than
or equal to 5 psig, provided there is no active purging of the
equipment to the atmosphere until the LEL criterion is met. This 5 psig
allowance is only available during shutdown. We are also providing
additional allowances for situations where it is not technically
feasible to depressurize a control system where there is no more than
72 lbs VOC per day vented to the atmosphere, consistent with our Group
1 applicability cutoff for control of process vents, or for catalyst
changeout activities where hydrotreater pyrophoric catalyst must be
purged. Provisions to demonstrate that process equipment is opened only
after the LEL, pressure or mass in the vessel requirement is met
includes documenting the procedures for equipment openings and
procedures for verifying that the openings meet the specific, above-
discussed requirements using site-specific procedures used to de-
inventory equipment for safety purposes (i.e., hot work or vessel entry
procedures).
2. Refinery MACT 2
The Refinery MACT 2 standards regulate all HAP emissions from the
three refinery process vents subject to Refinery MACT 2. For FCCU, the
standard specifies a CO limit as a surrogate for organic HAP and
specifies a PM limit (or Ni limit) as a surrogate for metal HAP.
Compliance with the organic HAP emissions limit is demonstrated using a
continuous CO monitor; compliance with the metal HAP emissions limit is
demonstrated using either COMS or control device parameter monitoring
systems (CPMS). At proposal, with the removal of the exemptions in the
Refinery MACT 2 rule for periods of startup and shutdown, we recognized
the need for alternative standards during some startup and shutdown
situations, and we proposed alternative requirements.
For this final rule, we are including a 1-percent minimum oxygen
limit as an alternative to the 500 ppmv hourly CO limit during FCCU
startup for partial
[[Page 75185]]
burn FCCU with CO boilers, as proposed. We are extending that
alternative limit to all FCCU and extending it to apply during
shutdown.
We are not finalizing the proposed alternative opacity limit for
FCCU during startup. Instead, based on public comments received, we are
finalizing an alternative minimum cyclone face velocity limit as a
means to demonstrate compliance with the PM limit during both startup
and shutdown, regardless of the type of FCCU and its control device. We
are finalizing alternative standards for sulfur recovery plant (SRP)
incinerator temperature and excess oxygen limits during SRP shutdown,
as proposed, and we are extending the proposed alternative standards to
startup as well.
E. What other revisions to the NESHAP and NSPS are being promulgated?
We are finalizing technical amendments to NSPS subparts J and Ja
with limited changes from what we proposed. First, in response to
comments, we are revising the NSPS requirements that a flow sensor have
a ``measurement sensitivity'' of no more than 5-percent of the flow
rate to an ``accuracy'' requirement that the flow sensor have an
accuracy of 5-percent of the flow rate. This change will make the
requirements more clear and consistent between the flow meter
requirements in the NSPS and the MACT standards since it is the same
flow meter subject to these requirements. We are also revising flare
flow rate accuracy requirements in Refinery NSPS subpart Ja to make
them consistent with those we are finalizing in Refinery MACT 1.
Finally, we are revising 40 CFR 60.101a(b) to begin as ``Except for
flares and delayed coking units . . .'' to correct an inadvertent
error. We proposed revisions to this sentence solely to allow sources
subject to Refinery NSPS subpart J to comply with the provisions in
Refinery NSPS subpart Ja instead. However, the words ``and delayed
coking units'' were inadvertently omitted from the initial part of the
sentence. Thus, as intended, we are finalizing revisions to this
sentence to allow sources subject to Refinery NSPS subpart J to comply
with the provisions in Refinery NSPS subpart Ja.
F. What are the requirements for submission of performance test data to
the EPA?
As proposed, the EPA is taking a step to increase the ease and
efficiency of data submittal and data accessibility. Specifically, the
EPA is finalizing the requirement for owners or operators of Petroleum
Refinery facilities to submit electronic copies of certain required
performance test reports through the EPA's Central Data Exchange (CDX)
using the Compliance and Emissions Data Reporting Interface (CEDRI).
The EPA believes that the electronic submittal of the reports addressed
in this rulemaking will increase the usefulness of the data contained
in those reports, is in keeping with current trends in data
availability, will further assist in the protection of public health
and the environment and will ultimately result in less burden on the
regulated community. Electronic reporting can also eliminate paper-
based, manual processes, thereby saving time and resources, simplifying
data entry, eliminating redundancies, minimizing data reporting errors
and providing data quickly and accurately to the affected facilities,
air agencies, the EPA and the public.
As mentioned in the preamble of the proposal, the EPA Web site that
stores the submitted electronic data, WebFIRE, will be easily
accessible to everyone and will provide a user-friendly interface that
any stakeholder could access. By making the records, data and reports
addressed in this rulemaking readily available, the EPA, the regulated
community and the public will benefit when the EPA conducts its CAA-
required technology and risk-based reviews. As a result of having
reports readily accessible, our ability to carry out comprehensive
reviews will be increased and achieved within a shorter period of time.
We anticipate fewer or less substantial information collection
requests (ICRs) in conjunction with prospective CAA-required technology
and risk-based reviews may be needed. We expect this to result in a
decrease in time spent by industry to respond to data collection
requests. We also expect the ICRs to contain less extensive stack
testing provisions, as we will already have stack test data
electronically. Reduced testing requirements would be a cost savings to
industry. The EPA should also be able to conduct these required reviews
more quickly. While the regulated community may benefit from a reduced
burden of ICRs, the general public benefits from the agency's ability
to provide these required reviews more quickly, resulting in increased
public health and environmental protection.
Air agencies could benefit from more streamlined and automated
review of the electronically submitted data. Having reports and
associated data in electronic format will facilitate review through the
use of software ``search'' options, as well as the downloading and
analyzing of data in spreadsheet format. The ability to access and
review air emission report information electronically will assist air
agencies to more quickly and accurately determine compliance with the
applicable regulations, potentially allowing a faster response to
violations which could minimize harmful air emissions. This benefits
both air agencies and the general public.
For a more thorough discussion of electronic reporting required by
this rule, see the discussion in the preamble of the proposal. In
summary, in addition to supporting regulation development, control
strategy development, and other air pollution control activities,
having an electronic database populated with performance test data will
save industry, air agencies, and the EPA significant time, money, and
effort while improving the quality of emission inventories, air quality
regulations, and enhancing the public's access to this important
information.
G. What are the effective and compliance dates of the NESHAP and NSPS?
The final amendments to the NESHAP and NSPS in this action are
effective on February 1, 2016. As proposed, new sources must comply
with these requirements by the effective date of the final rule or upon
startup, whichever is later.
As proposed, existing sources are required to comply with the final
DCU and CRU requirements no later than 3 years after the effective date
of the final rule. Similarly, as proposed, owners or operators are
required to comply with the new operating and monitoring requirements
for existing flares no later than 3 years after the effective date of
the final rule.
We proposed to provide 3 years from the effective date of the final
rule for refinery owners or operators to install and begin monitoring
(collecting samples) around the fenceline of their existing facility.
If refinery owners and operators determined that a site-specific
monitoring plan was needed, they would also need to submit and receive
approval for such a plan during the 3-year compliance period. Based on
information submitted during the comment period, we are finalizing
requirements that refinery owners or operators begin collecting samples
around the fenceline within 2 years of the effective date of the final
rule. Based on information submitted during the comment period, 1 year
is sufficient time to identify proper monitoring locations and to
install the required monitoring stations around the facility
[[Page 75186]]
fenceline. However, owners or operators may need additional monitoring
systems to account for near-field interfering sources (NFS), for which
the development and approval of a site-specific fenceline monitoring
plan is required. We expect that the site-specific fenceline monitoring
plans can take an additional year to develop, submit and obtain
approval. Consequently, we are providing 2 years from the effective
date of the final rule for refinery owners or operators to install and
begin collecting samples around the fenceline of their facility.
As proposed, we are requiring that existing sources comply with the
submerged filling requirement for marine vessel loading on the
effective date of the final rule.
As proposed, we are providing 18 months after the effective date of
the final rule to conduct required performance tests and comply with
any revised operating limits for FCCU.
We proposed to require refinery owners or operators to comply with
the revisions to the SSM provisions of Refinery MACT 1 and 2 on the
effective date of the final rule. As proposed, this final rule requires
refinery owners or operators to comply with the limits in Refinery MACT
2 or the alternative limits in this final rule during startup and
shutdown for FCCU and SRU on the effective date of the final rule.
The flare work practice standards for high-load flaring events
(events exceeding the smokeless capacity of the flare) require
development of FMP (or revision of an existing plan) to specifically
consider emergency shutdown and other high load events. In this FMP,
refinery owners or operators must consider measures that can be
implemented to reduce the frequency and magnitude of these high-load
flaring events. This may include installation of a flare gas recovery
system. Additionally, the work practice standards will require refinery
owners or operators to identify and implement measures that may involve
process changes. Therefore, we are establishing a compliance date of 3
years from the effective date of the final rule for refinery owners or
operators to comply with the work practice standards for high load
flaring events. We also note that this compliance period is consistent
with the compliance time provided for the flare operating limits.
For atmospheric PRD in HAP service we are establishing a work
practice standard that requires a process hazard analysis and
implementation of a minimum of three redundant measures to prevent
atmospheric releases. Alternately, refinery owners or operators may
elect to install closed vent systems to route these PRD to a flare,
drain (for liquid thermal relief valves) or other control system. We
anticipate that sources will need to identify the most appropriate
preventive measures or control approach; design, install and test the
system; install necessary process instrumentation and safety systems;
and may need to time installations with equipment shutdown or
maintenance outages. Therefore, we have established a compliance date
of 3 years from the effective date of the final rule for refinery
owners or operators to comply with the work practice standards for
atmospheric PRD.
As proposed, we are requiring compliance with the electronic
reporting provisions for performance tests conducted for Refinery MACT
1 and 2 on the effective date of the final rule.
Finally, we are finalizing additional requirements for storage
vessels under CAA sections 112(d)(6) and (f)(2) with a compliance date
90 days after the effective date of the final rule, as proposed.
H. What materials are being incorporated by reference?
In this final rule, the EPA is including regulatory text that
includes incorporation by reference. In accordance with requirements of
1 CFR 51.5, the EPA is incorporating by reference the following
documents described in the amendments to 40 CFR 63.14:
ASTM D1945-03 (Reapproved 2010), Standard Test Method for
Analysis of Natural Gas by Gas Chromatography, (Approved January 1,
2010).
ASTM D1945-14, Standard Test Method for Analysis of
Natural Gas by Gas Chromatography.
ASTM D6196-03 (Reapproved 2009), Standard Practice for
Selection of Sorbents, Sampling, and Thermal Desorption Analysis
Procedures for Volatile Organic Compounds in Air, (Approved March 1,
2009).
ASTM D6348-03 (Reapproved 2010), Standard Test Method for
Determination of Gaseous Compounds by Extractive Direct Interface
Fourier Transform Infrared (FTIR) Spectroscopy, including Annexes A1
through A8, (Approved October 1, 2010).
ASTM D6348-12e1, Standard Test Method for Determination of
Gaseous Compounds by Extractive Direct Interface Fourier Transform
Infrared (FTIR) Spectroscopy.
ASTM D6420-99 (Reapproved 2010), Standard Test Method for
Determination of Gaseous Organic Compounds by Direct Interface Gas
Chromatography-Mass Spectrometry.
ASTM UOP539-12, Refinery Gas Analysis by GC.
BS EN 14662-4:2005, Ambient air quality--Standard method
for the measurement of benzene concentrations--Part 4: Diffusive
sampling followed by thermal desorption and gas chromatography, June
27, 2005.
EPA-454/B-08-002, Quality Assurance Handbook for Air
Pollution Measurement Systems, Volume IV: Meteorological Measurements,
Version 2.0 (Final), March 2008.
EPA-454/R-99-005, Meteorological Monitoring Guidance for
Regulatory Modeling Applications, February 2000.
ISO 16017-2:2003(E): Indoor, ambient and workplace air--
Sampling and analysis of volatile organic compounds by sorbent tube/
thermal desorption/capillary gas chromatography--Part 2: Diffusive
sampling, May 15, 2003.
Air Stripping Method (Modified El Paso Method) for
Determination of Volatile Organic Compound Emissions from Water
Sources'' Revision Number One, dated January 2003, Sampling Procedures
Manual, Appendix P: Cooling Tower Monitoring, prepared by Texas
Commission on Environmental Quality, January 31, 2003.\4\
---------------------------------------------------------------------------
\4\ The requirements in Sec. 63.655(i)(5)(iii)(G) associated
with this incorporation by reference have not changed, but are being
modified to properly be incorporated into Sec. 63.14(s).
---------------------------------------------------------------------------
The EPA has made, and will continue to make, these documents
available electronically through www.regulations.gov and/or in hard
copy at the appropriate EPA office (see the ADDRESSES section of this
preamble for more information).
IV. What is the rationale for our final decisions and amendments to the
Petroleum Refinery NESHAP and NSPS?
A. Residual Risk Review for the Petroleum Refinery Source Categories
1. What did we propose pursuant to CAA section 112(f) for the Petroleum
Refinery source categories?
The results of our residual risk review for the Petroleum Refinery
source categories were published in the June 30, 2014 proposal at (79
FR 36934 through 36942), and included assessment of chronic and acute
inhalation risk, as well as multipathway and environmental risk, to
inform our decisions regarding acceptability and ample margin of
safety. The results indicated that both the actual and
[[Page 75187]]
allowable inhalation cancer risks to the individual most exposed are no
greater than approximately 100-in-1 million, which is the presumptive
limit of acceptability. In addition, the maximum chronic non-cancer
target organ-specific hazard index (TOSHI) due to inhalation exposures
was less than 1. The evaluation of acute non-cancer risks, which was
conservative, showed acute risks below a level of concern. Based on the
results of the refined site-specific multipathway analysis, we also
concluded that the ingestion cancer risk to the individual most exposed
through ingestion is considerably less than 100-in-1 million. In
determining risk acceptability, we also evaluated population impacts
because of the large number of people living near facilities in the
source category. We estimated that 5-million people are exposed to
increased cancer risks of greater than 1-in-1 million and 100,000
people are exposed to increased cancer risks of greater than 10-in-1
million, but, as noted previously, no individual is exposed to
increased cancer risks of greater than 100-in-1 million. Considering
the above information, we proposed that the risks remaining after
implementation of the existing NESHAP for the Refinery MACT 1 and 2
source categories is acceptable. However, we noted that the risks based
on allowable emissions are at the presumptive limit of acceptable risk,
and that a large number of people are exposed to risks of greater than
1-in-1 million, and we solicited comment on whether EPA should conclude
that the risk was unacceptable based on the health information before
the Agency. We also proposed that the original Refinery MACT 1 and 2
MACT standards, along with the proposed requirements for storage
vessels, provide an ample margin of safety to protect public health.
Finally, we proposed that it is not necessary to set a more stringent
standard to prevent, taking into consideration costs, energy, safety,
and other relevant factors, an adverse environmental effect.
2. How did the risk review change for the Petroleum Refinery source
categories?
As part of the final risk assessment, we conducted a screening
level analysis of how the information we received during the public
comment period, along with the changes we are making to the proposed
rule, would change our proposed risk estimates (More details can be
found in the ``Final Residual Risk Assessment for the Petroleum
Refining Source Sector'', Docket ID No. EPA-HQ-OAR-2010-0682).
First, we received approximately 20 emissions inventory updates for
specific facilities. These updates included revised emission estimates,
revised release latitude/longitude locations and other release
characteristic revisions. The updates provided evidence that the
quantity of HAP emitted at these specific facilities is lower than
considered in the risk modeling for the proposed rule. Our assessment
of the effects of these changes suggests that the cancer maximum
individual risk (MIR) based on actual emissions may be closer to 40-in-
1 million, as opposed to 60-in-1 million, as projected at proposal. We
did not quantify the reductions in chronic or acute non-cancer risks
from these updates. We calculated allowable emissions using the
Refinery Emissions Model (REM), which estimates emissions based on each
refinery's capacities and throughputs [See discussion at 79 FR 36888,
June 30, 2014.] The allowable emission estimates for point and fugitive
sources were not specific to a particular latitude/longitude location
so we assumed them to release from the centroid of the facility.
Therefore, the predicted cancer MIR of approximately 100-in-1 million
based on allowable emissions and reported in the proposal risk
characterization does not change based on the submitted emissions
revisions. We did not quantify changes to other actual risk metrics as
part of the screening level analysis (i.e., incidence, populations in
risk bins, multipathway and ecological analyses), but we would expect
some minor reductions from those presented in the proposed risk
characterization.
Second, we are establishing work practice standards in the final
rule for PRD releases and emergency flaring events, which under the
proposed rule would not have been allowed. Thus, because we did not
consider such non-routine emissions under our risk evaluation for the
proposed rule, we performed a screening assessment of risk associated
with these non-routine events for the final rule. [We provide further
details on the screening approach in ``Final Residual Risk Assessment
for the Petroleum Refining Source Sector'' in Docket ID No. EPA-HQ-OAR-
2010-0682.] We extracted information on these events from the 2011
Petroleum Refinery ICR data that included the process unit
identification, mass of emissions, duration of release, and description
of the incident. We identified the highest HAP mass releases for both
PRDs and flares from these non-routine events. We assumed these HAP
emission releases could occur at any facility in the source category.
Our analysis suggests that these HAP emissions could increase the MIR
based on actual emissions by as much as 2-in-1 million. Because the PRD
and flaring events were the worst case HAP mass emission release events
reported in the 2011 Refinery ICR for the source category, we are
assuming that actual and allowable risks are no different for these
events (i.e., a MIR of 2-in-1 million). A MIR increase of 2-in-1
million attributable to these events, added to our previous estimate
for allowable risk at proposal will not appreciably change our proposed
determination that the MIR based on allowable emissions are
approximately 100-in-1 million. We note that the MIR estimate
attributable to these non-routine PRD and flaring events was estimated
using a conservative, screening-level assessment, while the MIR
estimate at proposal was based on a refined risk assessment. By adding
a screening estimate to a refined risk estimate, we are merely defining
an upper limit that we expect the combined risks from both the routine
and non-routine emissions to be. Similarly, we estimate chronic non-
cancer hazard index (HI) values attributable to the additional
exposures resulting from non-routine flaring and PRD HAP emissions to
be well below 1 (HIimmune-system of 0.007) such that there
is no appreciable change in the maximum chronic non-cancer HI of 0.9
estimated at proposal for routine emissions, which was based on
neurological effects.
The screening analysis projects that the maximum predicted acute
non-cancer risk from non-routine PRD and flare emissions results in a
hazard quotient (HQ) based on a recommended reference exposure level
limit (REL) of up to 14 from benzene emissions. While the analysis
shows that there is a potential for HQs exceeding 1 for benzene,
because of the many uncertainties and conservative nature of this
screening analysis, the likelihood of such exposure and risk are low.
At proposal, we projected a HQ based on the REL for benzene of up to 2
from routine emissions. If we conservatively combine the routine and
non-routine emissions analyses, we would expect the potential for HQs
based on the REL for benzene to have the potential to increase above 2.
However, as projected at proposal, we estimate that the acute HQs
calculated using acute exposure guideline levels (AEGL) and emergency
response and planning guidelines (ERPG) values for all pollutants
including benzene would still be well
[[Page 75188]]
below 1 considering both routine and non-routine emissions.
Considering all of these factors, we do not project risks to be
significantly different from what we proposed. Based on the risk
analysis, as informed by the screening level analysis based on
information obtained during the comment period, we are finalizing our
determination that the risk remaining after promulgation of the NESHAP
is acceptable.
3. What key comments did we receive on the risk review and what are our
responses?
We received numerous comments on the residual risk assessment
analyses and results. We summarize the key comments received below,
along with our responses. A complete summary of all public comments
received and our responses are in the ``Response to Comment'' Document
in the public docket (Docket ID No. EPA-HQ-OAR-2010-0682).
Comment: Several commenters agreed that the EPA has correctly
concluded that the proposed rule requirements protect the public with
an ample margin of safety from refinery emissions. Other commenters
noted that EPA found residual risks remaining after implementation of
the MACT standards to be acceptable, and in light of the acceptability
determination argued that the proposed changes to the rule are not
justified. The commenters noted that the EPA's detailed emissions
inventory assessment and risk modeling results demonstrated that, at
every U.S. refinery, category-specific risks are below the EPA's
presumptive limit of acceptable risk (i.e., cancer risk of less than
100-in-1 million).
Other commenters stated the EPA's risk estimates are understated
and that the EPA should reduce the benchmark of what it considers
acceptable lifetime cancer risk instead of the upper limit of 100-in-1
million. One commenter provided an extensive critique of the cancer,
chronic and acute affects levels used in the risk assessment and
recommended that the EPA use California Office of Environmental Health
Hazard Assessment's (OEHHA) new toxicity values for several chemicals.
The commenter provided some references for the approaches used to
derive the California values. The commenter also asserted that risks
would be unacceptable had these more protective values been used in the
risk assessment. Some commenters stated the risks from petroleum
refinery emissions are underestimated because the EPA did not but
should have included interaction of multiple pollutants, accounted for
exposure to multiple sources, and assessed the cumulative risks from
facility-wide emissions and multiple nearby sources impacting an area.
Response: The approximately 100-in-1 million benchmark was
established in the Benzene NESHAP (54 FR 38044, September 14, 1989),
which Congress specifically referenced in CAA section 112(f)(2)(B).
While this presumptive level provides a benchmark for judging the
acceptability of MIR, it is important to recognize that it does not
constitute a rigid line for making that determination. The EPA
considers the specific uncertainties of the emissions, health effects
and risk information for the source category in question when deciding
whether the risk posed by that source category is acceptable. In
addition, the source category-specific decision of what constitutes an
acceptable level of risk is a holistic one; that is, the EPA considers
all potential health impacts--chronic and acute, cancer and non-cancer,
and multipathway--along with their uncertainties, when determining
whether the source category presents an unacceptable risk.
Regarding the comment that in light of the acceptability
determination the proposed changes to the rule are not justified, we
note that we also are required to ensure that the standards provide an
ample margin of safety to protect public health. That analysis is
separate from the acceptability analysis, and the determination of
acceptability does not automatically lead us to conclude that the
standards provide an ample margin of safety to protect public health.
Regarding the comments that the EPA should use the new California
OEHHA values, we disagree. The EPA's chemical-specific toxicity values
are derived using risk assessment guidelines and approaches that are
well established and vetted through the scientific community, and
follow rigorous peer review processes.\5\ The RTR program gives
preference to the EPA values for use in risk assessments and uses other
values, as appropriate, when those values are derived with methods and
peer review processes consistent with those followed by the EPA. The
approach for selecting appropriate toxicity values for use in the RTR
Program has been endorsed by the Science Advisory Board (SAB).\6\
---------------------------------------------------------------------------
\5\ Integrated Risk Information System (IRIS). IRIS Guidance
documents available at https://www.epa.gov/iris/backgrd.html.
\6\ https://yosemite.epa.gov/sab/sabproduct.nsf/0/b031ddf79cffded38525734f00649caf!OpenDocument&TableRow=2.3#2.
---------------------------------------------------------------------------
The EPA scientists reviewed the information provided by the
commenter regarding the California values and concluded that further
information is needed to evaluate the scientific basis and rationale
for the recent changes in California OEHHA risk assessment methods. The
EPA will work on gathering the necessary information to conduct an
evaluation of the scientific merit and the appropriateness of the use
of California OEHHA's new toxicity values in the agency decisions.
Until the EPA has completed its evaluation, it is premature to
determine what role these values might play in the RTR process.
Therefore, the EPA did not use the new California OEHHA toxicity values
as part of this current action. For more detailed responses regarding
appropriate reference values for specific pollutants, see the
``Response to Comment'' document in the public docket (Docket ID No.
EPA-HQ-OAR-2010-0682).
Concerning comments that we should consider aggregate risks from
multiple pollutants and sources, we note that we have done this to the
extent it is appropriate to do so. We modeled whole-facility risks for
both chronic cancer and non-cancer impacts to understand the risk
contribution of the sources within the Petroleum Refinery source
categories. The individual cancer risks for the source categories were
aggregated for all carcinogens. In assessing non-cancer hazard from
chronic exposures to pollutants that have similar modes of action or
(where this information is absent) that affect the same target organ,
we summed the HQs. This process creates, for each target organ, a
TOSHI, defined as the sum of HQs for individual HAP that affect the
same organ or organ system. Whole-facility risks were estimated based
on the 2011 ICR emissions data obtained from facilities, which included
emissions from all sources at the refinery, not just Refinery MACT 1
and 2 emission sources (e.g., emissions were included for combustion
units and units subject to the Hazardous Organic NESHAP, if present at
the refinery). We disagree with the commenter's assertion that
additional quantitative assessment of risks from sources outside the
source category is required under the statute. The statute requires the
EPA to provide the quantitative risk information necessary to inform
RTR regulatory decisions, and to this end, the EPA conducted a
comprehensive assessment of the risks associated with exposure to the
HAP emitted by the source category and supplemented that with
additional
[[Page 75189]]
information available about other possible concurrent and relevant
risks.
Further, the risk assessment modeling accounts for the effects of
multiple facilities that may be in close proximity when estimating
concentration and risk impacts at each block centroid. When evaluating
the risks associated with a particular source category, we combined the
impacts of all facilities within the same source category and assessed
chronic exposure and risk for all census blocks with at least one
resident (i.e., locations where people may reasonably be assumed to
reside). The MIR considers the combined impacts of all sources in the
category that may be in close proximity (i.e., cumulative impact of all
refineries).
Comment: Several commenters stated that the EPA underestimated
exposure because emissions are underreported and underestimated. The
commenters noted that for the risk assessment for the refineries rule,
the EPA evaluated (1) the emissions reported to the agency pursuant to
the 2011 Petroleum Refinery ICR as sources' ``actual'' emissions, and
(2) the emissions the EPA estimates that the existing standards
currently allow sources to emit using the REM, which it describes as
``allowable'' emissions. According to the commenters, both the EPA's
``actual'' and ``allowable'' emissions data sets are incomplete and
undercount emissions, causing the EPA to significantly underestimate
the resulting risk in its risk analysis. For example, the commenters
noted that the EPA assumed the flare destruction efficiency to be 98
percent, while the EPA's own estimates suggest flare efficiency is 93.9
percent. The commenters also noted that the EPA has further understated
risks by ignoring emissions during unplanned SSM events and by ignoring
HAP for which no reference values are established. One commenter cited
the TCEQ Emissions Event Database as evidence that SSM emissions are a
severe public health problem because data show that nearly 1 million
pounds of HAP are reported from Texas refineries between 2009 and 2013.
According to these commenters, the EPA needs to adopt standards that
provide greater protection, including protection from the risks of
accidents.
Response: We used the best and most robust facility-specific HAP
emissions inventory available to us, which was the 2011 ICR, in
performing the analysis for the proposed rule. We conducted a thorough
and exhaustive review of the data submitted through the ICR and we
followed up on source-specific information on a facility-by-facility
basis, as documented in the ``Emissions Data Quality Memorandum and
Development of the Risk Model Input File'' (see Docket ID No. EPA-HQ-
OAR-2010-0682-0076). In addition, we took steps ahead of issuing the
2011 ICR to make sure that facilities could, as accurately as
practicable, estimate their HAP emissions for purposes of responding to
the inventory portion of that ICR. We prepared a Refinery Protocol to
provide guidance to refinery owners or operators to use the best
available, site-specific data when developing their emissions
inventory, to ensure all emission sources are included in the
inventory, and to have a consistent set of emission factors that all
respondents use if no site-specific emissions data were available. If
site-specific emissions data were available, sites were to use these
data preferentially over the default factors. We developed the default
factors provided in the protocol from the best data available at the
time.
The ICR-submitted information for allowable emissions did not
include emission estimates for all HAP and all emission sources.
Consequently, we used the REM to estimate allowable emissions. The REM
relies on model plants that vary based on throughput capacity. Each
model plant contains process-specific default emission factors,
adjusted for compliance with the Refinery MACT 1 and 2 emission
standards.
We agree with the commenters that studies have shown that many
refinery flares are operating less efficiently than 98 percent. Prior
to proposing this rule, we conducted a flare ad hoc peer review to
advise the EPA on factors affecting flare performance (see discussion
in the June 30, 2014, proposal at 79 FR 36905). However, we disagree
with the commenters that the risk analysis should consider this level
of performance since the existing MACT standard does not allow it. For
purposes of the risk analysis, we evaluate whether it is necessary to
tighten the existing MACT standard in order to provide an ample margin
of safety. Thus, in reviewing whether the existing standards provide an
ample margin of safety, we review the level of emissions the MACT
standards allow. In the present case, we considered the level of
performance assumed in establishing the MACT standard for purposes of
determining whether the MACT standard provides an ample margin of
safety. However, we did recognize that facilities were experiencing
performance issues with flares and that many flares were not meeting
the assumed performance level at the time we promulgated the MACT
standard. Thus, we proposed, and are finalizing, revisions to the flare
operating requirements to ensure that the flares meet the required
performance level. These provisions are consistent with the EPA's goals
to improve the effectiveness of our rules.
Similarly, we do not include startup, shutdown (including
maintenance events) and malfunction emissions that are not allowed
under the standard as part of our evaluation of whether the standards
provide an ample margin of safety. Regarding the HAP emissions from SSM
events that the commenter is concerned with, we note that our review of
the TCEQ incident database indicates that many of the large reported
release events were of SO2 emissions and only a few had
significant HAP emissions.
Because in the final rule we are establishing work practice
standards for PRD and emergency flaring events, we performed a
screening-level risk analysis to address changes in facility HAP
emission releases due to these events. Details on this analysis are
presented in the final risk report for the source category (For more
details see Appendix 13 of the ``Final Residual Risk Assessment for the
Petroleum Refining Source Sector,'' Docket ID No. EPA-HQ-OAR-2010-
0682).
As for HAP with no reference value, the SAB addressed this issue in
its May 7, 2010, response to the EPA Administrator. In that response,
the SAB Panel recommended that, for HAP that do not have dose-response
values from the EPA's list, the EPA should consider and use, as
appropriate, additional sources for such values that have undergone
adequate and rigorous scientific peer review. The SAB panel further
recommended that the inclusion of additional sources of dose-response
values into the EPA's list should be adequately documented in a
transparent manner in any residual risk assessment case study. We agree
with this approach and have considered other sources of dose-response
data when conducting our risk determinations under RTR. However, in
some instances no sources of information beyond the EPA's list are
available. Compounds without health benchmarks are typically those
without significant health effects compared to compounds with health
benchmarks, and in such cases we assume these compounds will have a
negligible contribution to the overall health risks from the source
category. A tabular summary of HAPs that have dose response values for
which an exposure assessment was conducted is presented in Table 3.1-1
of the ``Final Residual Risk Assessment for the Petroleum Refining
Source Sector'', Docket ID No. EPA-HQ-OAR-2010-0682.
[[Page 75190]]
Comment: A few commenters asserted that the EPA should decide that
it is unjust and inconsistent with the CAA's health protection purpose
to allow the high health risks caused by refineries to fall
disproportionately on communities of color and lower income communities
who are least equipped to deal with the resulting health effects.
Because of that disparity, the commenter stated that the EPA should
recognize that the risks found are unacceptable and set stronger
national standards for all exposed Americans.
Response: For this rulemaking, the EPA conducted both pre- and
post-control risk-based assessments with analysis of various socio-
economic factors for populations living near petroleum refineries (see
Docket ID Nos. EPA-HQ-OAR-2010-0682-0226 and -0227) and determined that
there are more African-Americans, Other and multiracial groups,
Hispanics, low-income individuals, and individuals with less than a
high school diploma compared to national averages. In determining the
need for tighter residual risk standards, the EPA strives to limit to
no higher than 100-in-1 million the estimated cancer risk for persons
living near a plant if exposed to the maximum pollutant concentration
for 70 years and to protect the greatest number of persons to an
individual lifetime risk of no higher than 1-in-1 million. Although we
consider the risk for all people regardless of racial or socioeconomic
status, communities near petroleum refineries will particularly benefit
from the risk reductions associated with this rule. In particular, as
discussed later, the fenceline monitoring work practice standard will
be a further improvement in the way fugitive emissions are managed and
will provide an extra measure of protection for surrounding
communities.
4. What is the rationale for our final decisions for the risk review?
As described in section IV.A.2 of this preamble, we performed a
screening-level analysis to assess the risks associated with inventory
updates we received for specific facilities and with emissions events
that were previously not included in the risk assessment because the
proposed rule did not allow them. Because we are finalizing work
practice standards to regulate emission events associated with PRD
releases and emergency flaring, we considered the effect these work
practice standards would have on risks. As discussed in section IV.A.2
of this preamble, we project that accounting for these emergency events
in the baseline risks after implementation of the MACT standards does
not appreciably change the risks, and at most, could increase the
proposed rule estimate of MIR by approximately 2-in-1 million.
Therefore, we would project that any controls applied to these
emergency events, including the work practice standards for PRDs and
emergency flaring in this final rule, would not appreciably change the
proposed post-control risks. Although we would anticipate minimal
additional risk reductions, we reviewed more stringent alternatives to
the work practice standards for PRD releases and emergency flaring
events included in this final rule, and we found that the costs of
increasing flare capacity to control all PRD releases and to eliminate
all visible emissions during emergency flaring were too high. We
estimate the capital costs of applying the velocity and visible
emissions limit at all times would be approximately $3 billion, and we
estimate that the costs of controlling all PRD releases with flares
would be approximately $300 million. [See the discussion in the ``Flare
Control Option Impacts for Final Refinery Sector Rule'', Docket ID No.
EPA-HQ-OAR-2010-0682 and the PRD work practice standard discussion in
section IV.C of this preamble.] Further, we did not receive comments on
additional control technologies that we should have considered for
other emission sources (e.g., tanks, DCUs) beyond those considered and
described at proposal. Consequently, as discussed in section IV.A.2, we
conclude that the risks from the Petroleum Refinery source categories
are acceptable and that, with the additional requirements for storage
vessels that we are finalizing, as proposed, the Refinery MACT 1 and 2
rules provide an ample margin of safety to protect public health. We
also maintain, based on the rationale presented in the preamble to the
proposed rule, that the current standards prevent, taking into
consideration costs, energy, safety and other relevant factors, an
adverse environmental effect.
B. Technology Review for the Petroleum Refinery Source Categories
1. What did we propose pursuant to CAA section 112(d)(6) for the
Refinery MACT 1 (40 CFR part 63, subpart CC) source category?
The results of our technology review for the Petroleum Refinery
source categories were published in the June 30, 2014, proposal at (79
FR 36913 through 36928). The technology review was conducted for both
MACT source categories as described below.
a. Refinery MACT 1
Refinery MACT 1 sources include MPV, storage vessels, equipment
leaks, gasoline loading racks, marine vessel loading operations,
cooling towers/heat exchange systems and wastewater. Based on
technology reviews for the sources described above, we proposed that it
was not necessary to revise Refinery MACT 1 requirements for MPV,
gasoline loading racks, cooling towers/heat exchange systems, and
wastewater. For storage vessels, we proposed revisions pursuant to the
technology review. Specifically, we proposed to cross-reference the
storage vessel requirements in the Generic MACT (40 CFR part 63,
subpart WW) to require controls on floating roof fittings (e.g.,
guidepoles, ladder wells and access hatches) and to revise the
definition of Group 1 storage vessels to include smaller tanks with
lower vapor pressures. For equipment leaks, we proposed to allow
refineries to meet LDAR requirements in Refinery MACT 1 by monitoring
for leaks via optical gas imaging in place of the EPA Method 21, using
monitoring requirements to be specified in a not-yet-proposed appendix
K to 40 CFR part 60. For marine vessel loading, we proposed to amend
the Marine Tank Vessel Loading Operations MACT standards (40 CFR part
63, subpart Y) to require small marine vessel loading operations (i.e.,
operations with HAP emissions less than 10/25 tpy) and offshore marine
vessel loading operations at petroleum refineries to use submerged
filling based on the cargo filling line requirements in 46 CFR 153.282.
We also proposed an additional work practice standard under the
technology review to manage fugitive emissions from the entire
petroleum refinery through a fenceline monitoring and corrective action
standard. As part of the work practice standard, we specified the
monitoring technology and approach that must be used, and we developed
a fenceline benzene concentration action level above which refinery
owners or operators would be required to implement corrective action to
reduce their fenceline concentration to below this action level. The
action level we proposed was consistent with the emissions projected
from fugitive sources compliant with the provisions of the refinery
MACT standards as modified by the additional controls proposed for
storage vessels.
b. Refinery MACT 2
The Refinery MACT 2 source category regulates HAP emissions from
FCCU, CRU and SRU process vents. We
[[Page 75191]]
proposed to revise Refinery MACT 2 to incorporate the developments in
monitoring practices and control technologies reflected in Refinery
NSPS subpart Ja (73 FR 35838). This included proposing to incorporate
the Refinery NSPS subpart Ja PM limit for new FCCU sources and to
revise the monitoring provisions in Refinery MACT 2 to require all FCCU
sources to meet operating limits consistent with the requirements in
Refinery NSPS subpart Ja. The existing MACT standard provided that a
refiner could demonstrate compliance with the PM limit in the MACT by
meeting the 30-percent opacity limit requirement of Refinery NSPS
subpart J; we proposed to eliminate that provision and instead
establish control device operating limits or site-specific opacity
limits similar to those required in Refinery NSPS subpart Ja. We also
proposed to incorporate the use of 3-hour averages rather than daily
averages for monitoring data to demonstrate compliance with the FCCU
site-specific opacity and Ni operating limits. We proposed additional
control device-specific monitoring alternatives for various control
devices on FCCU, including BLD monitoring as an option to COMs for
owners or operators of FCCU using fabric filter-type control systems,
and total power and secondary current operating limits for owners or
operators of ESPs. We also proposed to add a requirement to perform
daily checks of the air or water pressure to atomizing spray nozzles
for owners or operators of FCC wet gas scrubbers. Finally, we proposed
to require a performance test once every 5 years for all FCCU in place
of the one-time performance test required by the current Refinery MACT
2.
At proposal, we did not identify any developments in practices,
processes and control technologies for CRU process vents based on our
technology review. For SRU, we proposed to include the Refinery NSPS
subpart Ja allowance for oxygen-enriched air as a development in
practice and to allow SRU to comply with Refinery NSPS subpart Ja as a
means of complying with Refinery MACT 2.
2. How did the technology review change for the Petroleum Refinery
source categories?
a. Refinery MACT 1
We are finalizing most of our technology review decisions for
Refinery MACT 1 emissions sources as proposed; however, as described
briefly below, we are revising certain proposed requirements.
We are not taking final action adopting the use of appendix K to 40
CFR part 60 for optical gas imaging for refinery equipment subject to
the LDAR requirements in Refinery MACT 1 because we have not yet
proposed appendix K.
After considering the public comments, we are finalizing the
proposed fenceline monitoring requirements, with a few revisions.
First, we have made numerous clarifications in this final rule to the
language for the fenceline monitoring siting method and analytical
method (i.e., Methods 325 A and B, respectively). Specific comments on
these methods, along with our responses and explanations of the
revisions to the regulatory text are discussed in the ``Response to
Comment'' document. Second, we are finalizing a revised compliance
schedule for fenceline monitoring, which will require refinery owners
or operators to have the fenceline monitors in place and collecting
benzene concentration data no later than 2 years from the effective
date of the final rule, as opposed to 3 years in the proposed rule.
Third, we have removed the requirement for refinery owners or operators
to obtain the EPA approval for the corrective action plan. Fourth, we
are requiring the submittal of the fenceline monitoring data on a
quarterly basis, as opposed to on a semiannual basis as proposed.
Fifth, we are providing guidelines for operators to use in requesting
use of an alternative fenceline monitoring technology to the passive
sorbent samplers set forth in Method 325B. Finally, to reduce the
burden of monitoring, we are finalizing provisions that would allow
refinery owners or operators to reduce the frequency of fenceline
monitoring for areas that consistently stay well below the fenceline
benzene concentration action level. Specifically, we are allowing
refinery owners or operators to monitor every other two weeks (i.e.,
skip period monitoring) if over a two-year period, each sample
collected at a specific monitoring location is at or below 0.9 [mu]g/
m\3\. If every sample collected from that sampling location during the
subsequent 2-years is at or below 0.9 [mu]g/m\3\, the monitoring
frequency may be reduced from every other two weeks to quarterly. After
an additional two years, the monitoring can be reduced to semiannually
and finally to annually, provided the samples continue to be at or
below 0.9 [mu]g/m\3\ during all sampling events at that location. If at
any time a sample for a monitoring location that is monitored at a
reduced frequency returns a concentration greater than 0.9 [mu]g/m\3\,
the owner or operator must return to the original sampling requirements
for one quarter (monitor every two weeks for the next six monitoring
periods for that location); if every sample collected from this quarter
is at or below 0.9 ug/m\3\, then the sampling frequency reverts back to
the reduced monitoring frequency for that monitoring location; if not
then the sampling frequency reverts back to the original biweekly
monitoring frequency.
b. Refinery MACT 2
We are finalizing, as proposed, our determination that it is not
necessary to revise the requirements for CRU pursuant to the technology
review and we are finalizing our determination that it is necessary to
revise the MACT for SRU and FCCU. For SRU, we are finalizing the
revisions as proposed. For FCCU, we are making modifications to the
proposed requirements in light of public comment.
As discussed previously, we proposed to remove the alternative in
Refinery MACT 2 for owners or operators to demonstrate compliance with
the PM limits on FCCU by meeting a 30-percent opacity standard as
provided in Refinery NSPS subpart J and instead make the FCCU operating
limits in Refinery MACT 2 consistent with Refinery NSPS subpart Ja.
Based on the Refinery NSPS subpart J review in 2008, we determined that
a 30-percent opacity limit does not adequately assure compliance with
the PM emissions limit (see discussion in the proposed rule at 79 FR
36929, June 30, 2014). Thus, we included other monitoring approaches in
Refinery NSPS subpart Ja.
Comments received on this proposal, along with data available to
the Agency, confirmed that the 30-percent opacity standard is not
adequate on its own to demonstrate compliance with the PM (or metal
HAP) emissions limit in Refinery MACT 2. We also received comments that
the site-specific opacity alternative, which is the only compliance
option proposed for FCCU with tertiary cyclones, would essentially
require owners or operators with these FCCU configurations to meet an
opacity limit of 10-percent. According to commenters, opacity increases
with decreasing particle size, so that it is common to exceed 10-
percent opacity during soot blowing or other similar events that
produce very fine particulates even though mass emissions have not
changed appreciably.
Based on the available data, we have determined that a 20-percent
opacity operating limit is well correlated with
[[Page 75192]]
facilities meeting a limit of 1.0 lb PM/1,000 lbs coke burn-off.
Therefore, we are retaining the option in Refinery MACT 2 to comply
with Refinery NSPS subpart J except we are adding a 20-percent opacity
operating limit in Refinery MACT 2, evaluated on a 3-hour basis. To
ensure that FCCU owners or operators complying with the Refinery NSPS
subpart J option can meet the 1.0 lb PM/1,000 lbs emissions limit at
all times, we are finalizing requirements that owners or operators
conduct the performance test during higher PM periods, such as soot
blowing. Where the PM emissions are within 80-percent of the PM limit
during any periodic performance test, we are requiring the refinery
owner or operator to conduct subsequent performance tests on an annual
basis instead of on a 5-year basis.
We are finalizing our proposed requirement that compliance with the
control device operating limits in the other compliance alternatives be
demonstrated on a 3-hour basis, instead of the 24-hour basis currently
allowed in Refinery MACT 2.
3. What key comments did we receive on the technology review, and what
are our responses?
a. Refinery MACT 1
The majority of comments received regarding the proposed amendments
to Refinery MACT 1 pursuant to our technology review dealt with the
proposed fenceline monitoring requirements. The primary comments on the
fenceline monitoring requirements are in this section along with our
responses. Comment summaries and the EPA's responses for additional
issues raised regarding the proposed requirements resulting from our
technology review are in the ``Response to Comment'' document in the
public docket (Docket ID No. EPA-HQ-OAR-2010-0682).
i. Legal Authority and Need for Fenceline Monitoring
Comment: Numerous commenters claimed that the proposed fenceline
monitoring program would unlawfully impose what is effectively an
ambient air quality standard for benzene, which is not authorized by
CAA section 112, which only authorizes the control of emission sources.
The commenters argued it is an ambient standard because sources are
required to meet the benzene level set or ``perform injunctive relief
which may or may not address the source of the benzene.'' The commenter
quoted language from the proposal as support that EPA has described the
benzene level as an ambient standard: ``We are proposing a HAP
concentration to be measured in the ambient air around a refinery, that
if exceeded, would trigger corrective action to minimize fugitive
emissions.'' 79 FR at 36920 (June 30, 2014). The commenter further
noted that this requirement is not just ``monitoring'' because it
establishes a ``not-to-be exceeded'' level. Therefore, the commenters
stated, the EPA should not finalize this portion of the proposal.
Response: We disagree with the comment that the fenceline proposal
is an ambient air standard. First, the owner or operator must place the
monitors on the facility fenceline to measure emissions from the
facility, i.e., on the property of the refiner. While we recognize that
we used the term ``ambient air'' in the preamble to the proposal, we
note that the placement requirements for the monitors make clear that
the monitors are not monitoring ambient air, which EPA has defined at
40 CFR 50.1(e) as ``that portion of the atmosphere, external to
buildings, to which the general public has access.'' Second, the
proposed EPA Method 325A sets out procedures to subtract background
concentrations and contributions to the fenceline benzene
concentrations from non-refinery emission sources, so that the benzene
concentrations measured are attributable to the refinery. In other
words, the fenceline monitoring work practice standard uses a benzene
concentration difference, referred to as the [Delta]C (essentially an
upwind and downwind concentration difference) to isolate the refinery's
emissions contribution.
Furthermore, we disagree that the fact that refiners are required
to perform corrective action if the fenceline benzene concentration
action level is exceeded makes the benzene action level an ambient
standard. As an initial matter sources are not directly responsible for
demonstrating that an area is meeting an ambient standard; rather that
burden falls on states. See e.g., CAA section 110(a)(2). Moreover, the
``corrective action'' is simply that sources must ensure that fugitive
emission sources on the property are not emitting HAP at levels that
will result in exceedances of the fenceline benzene concentration
action level. In other words, the purpose of the fenceline monitoring
work practice is to ensure that sources are limiting HAP emissions at
the fenceline, which are solely attributable to emissions from sources
within the facility. In fact, the fenceline benzene concentration
action level was established using emissions inventories reported by
the facilities, assuming compliance with the MACT standards. Finally,
monitoring is conducted as part of the work practice standard to
identify sources that will require additional controls to reduce their
impact on the fenceline benzene concentration. In that sense, the
fenceline monitoring work practice standard is not different than, for
example, our MACT standard for refinery heat exchangers. If a facility
is exceeding the relevant cooling water pollutant concentration
``level'' when it performs a periodic test, it must undertake
corrective action to bring the concentration down below the action
level.
Comment: Several commenters noted that EPA's authority under
section 112(d) is to set ``emissions standards'' and quoted the CAA
definition of that term: ``A requirement . . . which limits the
quantity, rate, or concentration of emissions of air pollutants on a
continuous basis, including any requirement relating to the operation
or maintenance of a source to assure continuous emission reduction, and
any design, equipment, work practice or operational standard
promulgated under this Act.'' 42 U.S.C. 7602(k). The commenters argued
that the proposed fenceline monitoring standard does not meet this
definition because it would not ``limit the quantity, rate, or
concentration of emissions'' from any given emissions point. Also, the
commenters claimed that the EPA did not designate fenceline monitoring
as a work practice under CAA section 112(h) since the EPA did not even
mention CAA section 112(h), nor did it conduct any analysis to show
that fenceline monitoring meets the CAA section 112(h) factors.
Response: We disagree with the commenters' assertion that the
proposed fenceline monitoring work practice standard is not authorized
under CAA section 112(d)(6). Contrary to the commenter's claims, we
specifically proposed the fenceline monitoring standard under CAA
section 112(d)(6) to be a work practice standard that is applied
broadly to fugitive emissions sources located at petroleum refineries.
As discussed above, the proposed standard does more than impose
monitoring as some commenters suggested; it also will limit emissions
from refineries because it requires the owner or operator to identify
and reduce HAP emissions through a monitoring and repair program, as do
many work practice standards authorized under CAA Section 112(h) and
112(d).
We note that the sources addressed by the fenceline monitoring
standard--refinery fugitive emissions sources such as wastewater
collection and treatment
[[Page 75193]]
operations, equipment leaks, heat exchange systems and storage vessels
in the Refinery MACT 1 rule--are already subject to work practice
standards. Our review of these requirements indicates that this
fenceline monitoring work practice standard would be a further
improvement in the way fugitive emissions are managed and would provide
an extra measure of protection for surrounding communities. The
commenter claims EPA did not analyze how the fenceline monitoring
requirement meets the criteria in section 112(h). However, that is a
misinterpretation of how the criteria apply. The criteria are assessed
with regard to whether it is feasible to ``prescribe or enforce an
emission standard for a source'', and do not apply to the work practice
standard. Consistent with the criteria in section 112(h)(2), we
determined and established that work practice standards are appropriate
for these Refinery MACT fugitive emissions at the time we established
the initial MACT standard. In the proposal, (79 FR at 36919, June 30,
2014), we reaffirmed that it is impracticable to directly measure
fugitive emission sources at refineries but did not consider it
necessary to reiterate these findings as part of this proposal to
revise the existing MACT for these sources under CAA section 112(d)(6).
We note that the commenters do not provide any grounds to support a
reevaluation of whether these fugitive emission sources are
appropriately regulated by a work practice standard.
Comment: Several commenters questioned the EPA's authority under
the CAA to promulgate a rule that amounts to an ongoing information
gathering and reporting obligation. The commenters stated that the EPA
has not demonstrated that the proposed fenceline monitoring program
represents an actual emission reduction technology improvement. A
commenter stated that compliance assurance methods, including
monitoring, for fugitive emissions and other emission standards are
established as part of the emission standard and EPA's authority to
gather information that is not directly required for compliance with a
specific standard but is related to air emissions is found in CAA
section 114. Under CAA section 114, the requirement must be related to
one of the stated purposes and must be reasonable. The commenter did
not believe that the EPA has demonstrated that the costs of fenceline
monitoring are reasonable in light of the information already available
to the EPA and in light of many other means by which the EPA could
obtain such information.
Response: We disagree with the commenters' assertion that the
authority for the fenceline monitoring requirement falls under CAA
section 114 and not CAA section 112(d) because it is an ``ongoing
information gathering and reporting obligation.'' The issue here is not
whether EPA could have required the fenceline monitoring requirement
under CAA section 114, but rather did EPA support that it was a
development in processes practices or controls technology under section
112(d)(6).
As an initial matter, we disagree with the commenters'
characterization of the fenceline monitoring standard as ``an
information gathering and reporting obligation.'' We have repeatedly
stated that we consider the fenceline monitoring requirement to be a
work practice standard that will ensure sources take corrective action
if monitored benzene levels (as a surrogate for HAP emissions from
fugitive emissions sources) exceed the fenceline benzene concentration
action level. The standard requires refinery owners or operators to
monitor the benzene concentration at the refinery perimeter, to
evaluate the refinery's contribution as estimated by taking the
concentration difference between the highest and lowest concentrations
([Delta]C) in each period, and to conduct root cause analysis and take
corrective action to minimize emissions if the concentration difference
is higher (on an annual average) than the benzene concentration action
level. Thus, the fenceline monitoring requirement goes well beyond
``information gathering and reporting.''
In addition, the commenters again read section 112(d)(6) too
narrowly by suggesting that a program considered as a development must
be a ``technology'' improvement. Section 112(d)(6) of the CAA requires
the EPA to review and revise the MACT standards, as necessary, taking
into account developments in ``practices, processes and control
technologies.'' Consistent with our long-standing practice for the
technology review of MACT standards, in section III.C of the proposal
(see 79 FR 36900, June 30, 2014), we list five types of
``developments'' we consider. Fenceline monitoring fits squarely within
two of those five types of developments (emphasis added):
Any add-on control technology or other equipment that was
not identified and considered during development of the original MACT
standards.
Any work practice or operational procedure that was not
identified or considered during development of the original MACT
standards.
As used here, ``other equipment'' is clearly separate from and in
addition to ``add-on control'' technology and is broad enough to
include monitoring equipment. In this case, fenceline monitoring is a
type of equipment that we did not identify and consider during
development of the original MACT standards. Additionally, the fenceline
standard is a work practice standard, involving monitoring, root cause
analysis and corrective action not identified at the time of the
original MACT standards. Therefore, the fenceline requirements are a
development in practices that will improve how facilities manage
fugitive emissions and EPA appropriately relied on section 112(d)(6) in
requiring this standard.
Comment: Some commenters contended that because the fenceline
monitoring standard is in essence an ambient standard, the only
justification that can be used to support it would be under CAA section
112(f)(2). The commenters stated that EPA determined that the MACT
standards pose an acceptable level of risk and protect the public
health with an ample margin of safety and thus, section 112(f) does not
support imposition of the fenceline monitoring requirement. Several
commenters stated that the Agency expressly acknowledges that
imposition of additional emission standards for fugitive emissions from
refinery sources are not warranted under CAA section 112(f). Some
commenters suggested that because the existing MACT standards protect
public health with an ample margin of safety, the fenceline monitoring
requirement imposes an unnecessary burden on industry because it is not
necessary to achieve acceptable risk or provide an ample margin of
safety.
Response: EPA is not relying on section 112(f)(2) as the basis for
the fenceline monitoring requirement. As provided in a previous
response to comment, we disagree with the commenters that the fenceline
monitoring requirement is an ambient standard and therefore, we do not
need to consider what authority would be appropriate for establishing
an ambient standard that would apply to fugitive sources of emissions
at refineries. We also disagree with the commenters who suggest that
EPA may not require fenceline monitoring pursuant to section 112(d)(6)
because EPA has not determined that fenceline monitoring is necessary
to ensure an acceptable level of risk or the provide an ample margin of
safety. Section 112(d)(6) does not
[[Page 75194]]
require EPA to factor in the health considerations provided in section
112(f)(2) when making a determination whether it is ``necessary'' to
revise the MACT.
Comment: Commenters stated that the pilot studies undertaken by the
EPA and pilot studies undertaken by the refining industry (see the API
Fenceline Study in the docket for this rulemaking) demonstrate either
that there is no underestimation of emissions and thus, no need for the
fenceline monitoring work practice standard, or that fenceline benzene
data cannot be used to validate emission estimates. Commenters stated
that none of the refineries in the API study of the proposed refinery
fenceline standard had study-averaged [Delta]C concentrations that
exceeded the proposed action level of 9 [micro]g/m\3\ and thus the
study provides some evidence that U.S. refineries are not
underestimating emissions. Furthermore, the commenter stated that there
is significant ambient air monitoring performed that further supports
low benzene concentrations in the vicinities of refineries and cited
ambient monitoring data collected by the Southeast Texas Regional
Planning Commission Air Quality Group and the Texas Commission on
Environmental Quality (TCEQ).
Response: We disagree that the API fenceline study demonstrates
that there is no underestimation of emissions. The API report referred
to by the commenter actually shows higher [Delta]C concentrations than
what we expected, when we compare the distribution of [Delta]C's
presented in the API fenceline study to the distribution of benzene
concentrations at the 142 refineries we modeled (see memorandum
``Fenceline Ambient Benzene Concentrations Surrounding Petroleum
Refineries'', EPA-HQ-OAR-2010-0682-0208). [Note that API did not
identify the facilities in their study, so we were not able to perform
a one-to-one comparison of the measured [Delta]C concentrations with
the modeled fenceline concentrations.] Furthermore, the API conducted
the study primarily during the fall and winter months (October to
March) when the ambient temperatures are lower than the annual
averages. While this may not impact equipment leak emissions,
temperature can have a significant impact on emissions from storage
vessels and wastewater treatment systems, so it is likely that the
annual average [Delta]C for the facilities tested could be higher than
the ``winter'' averages measured in the API study. Based on our review
of the API study data, we interpret the results to indicate that there
may be higher concentrations of benzene on the fenceline attributable
to fugitive emissions than anticipated at some facilities. These
studies are an indication that the standard we are finalizing will
achieve the goal of ensuring that the owners or operators manage
fugitive emissions within the refinery.
This regulatory approach also fits with the EPA's goals to improve
the effectiveness of rules. Specifically, in this case, we are
improving the effectiveness of the rule in two ways. First, we are
establishing a fenceline benzene trigger to manage overall fugitive HAP
emissions, rather than establishing further requirements on many
individual emission points. Secondly, the rule incentivizes facilities
to reduce fugitive HAP emissions below the fenceline benzene trigger by
providing regulatory options for reduced monitoring.
Regarding ambient monitoring data, we note that existing ambient
monitors are not located at the fenceline; they are located away from
sources, and concentrations typically decrease exponentially with
distance from the emissions source. We are encouraged that data
referenced by the commenter indicate that ambient levels of benzene are
within levels that are protective of human health in communities, but
note that analysis of benzene concentrations in communities does not
necessarily indicate that refineries located near these communities are
adequately managing their fugitive HAP emissions.
Comment: Several commenters reiterated that they do not believe the
proposed fenceline monitoring is a technology development for equipment
leaks, storage vessels or wastewater sources. However, if the EPA
finalizes the fenceline monitoring requirements, the commenters
suggested that there is no longer a need or regulatory basis for
imposing both the fenceline monitoring requirements and the existing
MACT standards for fugitive HAP emission sources. Thus, the EPA should
remove the current MACT requirements for LDAR, storage vessels and
wastewater handling and treatment from Refinery MACT 1 if the EPA
promulgates fenceline monitoring. Addition of fenceline monitoring on
top of the existing MACT requirements, they argue, would violate the
Executive Order 12866 mandate to avoid redundant, costly regulatory
requirements that provide no emission reductions.
Response: We disagree that the fenceline monitoring standards we
are finalizing in this rule are redundant to MACT emissions standards
for fugitive HAP emissions sources. The MACT standards impose
requirements on fugitive HAP emissions sources consistent with the
requirements in CAA section 112(d)(2) & (3), and the fenceline
monitoring requirement is not a replacement for those requirements.
Rather, based on our review of these standards, we concluded that
fenceline monitoring is a development in practices, processes or
control technologies that would improve management of fugitive
emissions in a cost-effective manner. In selecting this development as
an across-the-board means of improving management of fugitive
emissions, we rejected other more costly developments that would have
applied independently to each fugitive emissions source. Requiring
refineries to establish a fenceline monitoring program that identifies
HAP emission sources that cause elevated benzene concentrations at the
fenceline and correcting high emissions through a more focused effort
augments but does not replace the existing requirements. We found that,
through early identification of significant fugitive HAP releases
through fenceline monitoring, compliance with the existing MACT
standards for these emissions sources could be improved and that it was
necessary to revise the existing standards because fenceline monitoring
is a cost-effective development in processes, practices, and control
technologies.
We note that the existing MACT requirements are based on the MACT
floor (the best performers), and as such, provide a significant degree
of emission reductions from the baseline. The action level for the
fenceline work practice standard, by contrast, is not based on the best
performers but rather on the highest value expected on the fenceline
from any refinery, based on the modeling of refinery emission
inventories. As such it is not representative of the best performers
and could not be justified as meeting the requirements of section
112(d)(2)and (3). If we were to remove the existing standards for
fugitive emission sources at the refinery, we would not be able to
justify that sources are meeting the level of control we identified as
the MACT floor when we first promulgated the MACT. Nor could we justify
the fenceline monitoring program we are promulgating as representing
the MACT floor because we considered cost (and not the best performers
as previously noted) in identifying the components of the program.
Although the fenceline monitoring standard on its own cannot be
justified as meeting the MACT floor requirement for each of the
separate
[[Page 75195]]
types of fugitive emission sources, that does not mean that it is not
an effective enhancement of those MACT requirements. To the contrary,
it works in tandem with the existing MACT requirements to provide
improved management of fugitive emissions and, in that sense, it is
precisely the type of program that we believe Congress had in mind when
enacting section 112(d)(6).
ii. Rule Should Require Real-Time Monitoring Technology for Fenceline
Monitoring.
Comment: Numerous commenters stated that the proposed fenceline
standards, which require monitoring using 2-week integrated passive
samplers, are flawed and weak for a number of reasons, including that
the monitoring method does not provide real-time data, does not provide
adequate spatial coverage of the fenceline, and does not provide a
mechanism to identify the specific emission source impacting the
fenceline to manage fugitive emissions. Several commenters suggested
that this monitoring technology is not state of the art. They claimed
that there are superior systems in place at refineries that are
technically and economically feasible, including at Shell Deer Park,
Texas; BP Whiting, Indiana; and Chevron Richmond, California. Further,
they claimed that these systems more effectively achieve the objective
of reducing fugitive emissions. They claimed several systems are
superior to the proposed system, including open-path systems such as
ultraviolet differential optical absorption (UV DOAS) and Fourier
transform infrared spectroscopy (FTIR), as well as point monitors such
as gas chromatographs. A number of commenters suggested that open-path
monitors should be required, stating that this technology is capable of
providing real-time analysis and data on air pollution, is able to
analyze multiple pollutants simultaneously at low, near-ambient
concentrations, and is capable of providing more complete geographic
coverage.
The commenters also stated that the benefits of real-time monitors
are particularly important in communities close to refineries, where
they believe refinery emissions are a major source of toxic pollutants
and short-term upset events that can have significant public health
impacts. In particular, the commenters stated that open-path monitors
promote an individual's right-to-know, in real-time, about harmful
pollution events affecting their communities, and will allow refinery
owners or operators to immediately identify fugitive emissions and
undertake swift corrective action to reduce these emissions. Some
commenters suggested that, if the EPA rejects these open-path real-time
monitors, then at a minimum the EPA should require the use of active
daily monitoring, such as auto-gas chromatograph (GC) systems.
Finally, a number of commenters recommended that the EPA provide
sufficient flexibility in its regulations to allow state and local
jurisdictions to develop, demonstrate, and subsequently require the use
of alternative monitoring programs, provided these monitoring programs
are at least equivalent to those in the final rule.
Response: We understand that many commenters believe real-time
monitoring would not only help refinery owners or operators in
identifying emission sources, but also would warn the community of
releases in real time.
Both open-path systems and active sampling systems (such as auto-
GCs) mentioned by the commenters, are monitoring systems capable of
yielding monitoring data quickly--ranging from a few minutes to about a
day. However, these ``real-time'' systems have not been demonstrated to
be able to achieve all of the goals stated by the commenters--
specifically, able to provide real-time analysis and data on multiple
pollutants simultaneously at low-, near-ambient concentrations, with
more complete geographic (or spatial) coverage of the fenceline.
The real-time open-path systems suggested by the commenters are all
limited in that they are not sensitive enough to detect benzene at the
levels needed to ensure that fenceline monitoring achieves its intended
goal. The fenceline monitoring system needs to be capable of measuring
at sub-ppbv levels--well below the 9 [mu]g/m\3\ fenceline benzene
concentration action level in the final rule, in order to determine the
[Delta]C. In the proposal, we discussed two open-path monitoring
technologies, FTIR and UV-DOAS. For the proposed rule, we analyzed the
feasibility of employing UV-DOAS over FTIR because the UV-DOAS is more
sensitive to detection of benzene than FTIR, as we described in the
proposal. We reviewed performance data on several UV-DOAS systems in
support of the proposed rule, and for this final rule, we considered
information submitted during the comment period. We found that the
lowest detection limit reported for any commercially-available UV-DOAS
system is on the order of 3 ppbv over a 200-meter path length, whereas
the fenceline benzene concentration action level is 2.8 ppbv
(equivalent concentration to 9 [mu]g/m\3\). This system is being
installed at the Shell Deer Park refinery but has not been field
validated yet. Thus, we do not yet know the detection capabilities of
the system, as installed. Based on the lowest reported detection limit,
it cannot achieve the detection levels needed to demonstrate compliance
with the fenceline standard in this final rule. This system also will
only cover approximately 5 percent of the fenceline at Shell Deer Park,
instead of the full fenceline coverage of the passive diffusive tube
monitoring system we proposed. Facilities would have to deploy a
monitoring system consisting of many open-path monitors to achieve the
same spatial coverage as the passive diffusive tube monitoring system.
For the final rule, we also reviewed other UV-DOAS systems in
operation at refineries that commenters identified. However, reported
detection limits for these systems are even higher than for the type of
system being installed at Shell Deer Park. For example, we reviewed the
open-path UV-DOAS system information from BP Whiting and found that
they were able to verify a detection limit of 8 ppbv path average
concentration for benzene over a 1,500-meter optical path. This is well
above the 2.8 ppbv fenceline benzene concentration action level, let
alone the sub-ppbv levels necessary to determine the [Delta]C.
Moreover, this system, though commercially available, was optimized by
developing alternative software to improve the detection limit (see
memorandum ``Meeting Minutes for April 21, 2015, Meeting Between the
U.S. EPA and BP Whiting'' in Docket ID No. EPA-HQ-OAR-2010-0682). Thus,
the system, as installed, would not be readily available to other
refineries. We reviewed data for the UV-DOAS system at the Chevron
Richmond refinery and found that this system, with optical path lengths
ranging from 500 to 1,000 meters, has a reported benzene detection
limit of 5 ppbv averaged over the path length. Again, this is above the
fenceline benzene concentration action level at the fenceline
established in this final rule. In addition, we could not find any
information to support the reported detection limit. We note that the
public Web site operated by the City of Richmond, California indicates
that information provided by the system is informational only, not
quality assured, and not to be used for emergency response or health
purposes.
We also disagree with the commenter's claim that if the EPA does
not finalize requirements for real-time open-path monitors then, at a
minimum, the EPA should require active daily monitoring. There are two
methods of
[[Page 75196]]
active monitoring. One method, which we will refer to as the ``auto-GC
method,'' uses a dedicated gas chromatograph at each monitoring
location and can return ambient air concentration results multiple
times a day or even hourly. The other method, which we refer to as
``method 2,'' uses an active pump to collect gas in a sorbent tube or
in an evacuated canister over a 1-day period, for later analysis at a
central location. While active sampling monitoring networks are capable
of measuring multiple pollutants and would likely be able to detect
benzene at sub-ppbv levels as necessary to demonstrate compliance with
the fenceline requirements in this final rule, they consist of discreet
monitors and would not provide any better spatial coverage of the
refinery fenceline than a passive diffusive tube monitoring network.
Further, as shown in Table 9 of the proposed rule (see 79 FR 36923,
June 30, 2014), like open-path systems, an active sampling monitoring
network would cost many times that of a passive diffusive tube
monitoring network. At proposal, we estimated the costs of active daily
sampling based on ``method 2'' to be approximately 10 times higher than
for the proposed passive monitoring (see memorandum ``Fenceline
Monitoring Technical Support Document'', Docket ID No. EPA-HQ-OAR-2010-
0682-0210). We note that this type of active daily sampling based on
method 2 does not necessarily yield results within 24 hours as the
sample analysis would be conducted separately. We did not specifically
estimate the costs of an auto-GC alternative, but the capital costs
would be at least 20 to 30 times that for the passive diffusive tube
system, would require shelters and power supplies at all monitoring
locations and would have operating costs similar to the ``method 2''
active monitoring option we considered.
To date, there are no commercially-available, real-time open-path
monitors capable of detecting benzene at the sub-ppbv levels necessary
to demonstrate compliance with the fenceline requirements in this final
rule. Only a system that can detect such levels will result in
effective action by facilities to identify and control fugitive
emissions in excess of those contemplated by the MACT standards.
Further, active monitoring systems, while potentially capable of
detecting benzene at sub-ppbv levels, like open-path systems, become
very costly when enough monitors are located around the facility to
approach the spatial coverage of the passive diffusive tubes. However,
we believe that the state of technology is advancing and that the
capabilities of these systems will continue to improve and that the
costs will likely decrease. If a refinery owner or operator can
demonstrate that a particular technology would be able to comply with
the fenceline standards, the owner or operator can request the use of
an alternative test method under the provisions of 40 CFR 63.7(f). A
discussion of the specific requirements for these requests can be found
in the first comment and response summary of Chapter 8.3 of the
``Response to Comment'' document.
Comment: One commenter stated that the required monitoring should
include real-time monitoring of all chemicals released by refineries
that pose risks to human health. The commenter stated that the limited
scope of monitoring required by the proposed rule appears to be guided
by the EPA's judgment that fugitive, or ``unintended'' emissions pose
the greatest threat to public health. On the contrary, communities may
well suffer from the effects of chemicals released into the air under
normal, permitted emissions. A more expansive monitoring strategy would
account for both routine and fugitive emissions.
Several commenters noted that monitoring is limited to benzene as
opposed to multiple HAP. One commenter noted that ill health
experienced by refinery neighbors is due in large part to the
synergistic effects of multiple chemicals. Therefore, the commenter
stated that it is essential that the rule require monitoring of the
full range of chemicals with health implications. Other commenters
recommended that the fenceline monitoring requirement be amended to
include additional contaminants, such as VOC, that may negatively
impact human health and the environment. Conversely, other commenters
stated that the EPA has appropriately selected benzene as a target
analyte and surrogate for HAP emissions from petroleum refineries, as
benzene is a common constituent in refinery feedstocks and numerous
refinery streams, and is present in most HAP-containing streams in a
refinery.
Response: As part of the CAA section 112(d)(6) technology review,
the EPA identified the fenceline monitoring standard as a development
in practices, processes or control technologies that could improve
management of fugitive HAP emissions. Thus, to the extent the commenter
is suggesting that the EPA require the fenceline monitoring system to
monitor for emissions of non-HAP pollutants, such request goes beyond
the scope of our action. Furthermore, to the extent that the commenter
is raising health concerns, although we address residual risk remaining
after implementation of the MACT standards under CAA section 112(f)(2),
we note that the MACT standards themselves, including this requirement,
are aimed at protecting public health, especially in surrounding
communities. As we explained in the proposal, and as we determine for
this final rule, the MACT standards as modified by additional
requirements for storage vessels, provide an ample margin of safety to
protect public health. We did not propose and are not finalizing a
fenceline monitoring requirement as necessary to provide an ample
margin of safety under CAA section 112(f)(2).
Petroleum refining emissions can contain hundreds of different
compounds, including many different HAP, and no single method can
detect every HAP potentially emitted from refineries. While several HAP
are amenable to quantification via passive diffusive tube monitoring
using the same adsorbent tubes used for benzene (e.g., toluene, xylenes
and ethyl benzene, which have uptake rates in Table 12.1 in Method
325B), we selected benzene as a surrogate because it is present in
nearly all refinery fugitive emissions. By selecting a single HAP as a
surrogate for all fugitive HAP, we are able to establish a clear action
level, which simplifies the determination of compliance for refinery
owners or operators and simplifies the ability of regulators and the
public to determine whether sources are complying with the work
practice standard. As described in the proposal preamble, benzene is
ubiquitous at refineries and present in nearly all refinery process
streams, including crude oil, gasoline and wastewater. Additionally,
benzene is primarily emitted from ground level, fugitive sources that
are the focus of the work practice standard. Thus, we conclude that
monitoring of benzene is appropriate and sufficient to identify
emission events for which the monitoring program is targeting.
Consequently, we are not requiring quantification of other pollutants
although refinery owners or operators could choose to analyze the
diffusive tube samples for additional HAP in conducting root cause
analysis and corrective action.
iii. Fenceline Monitoring Action Level
Comment: Several commenters stated that the action level for
fenceline monitoring (i.e., 9 [mu]g/m\3\ or 2.8 ppbv), was set too
high. Some of these commenters noted that the EPA selected 9 [mu]g/m\3\
as the highest modeled benzene
[[Page 75197]]
concentration at any refinery fenceline. One commenter stated that this
was arbitrary and capricious and stated the action threshold level
makes little sense because only 2 of the 142 modeled facilities are
expected to have fenceline concentrations above 4 [mu]g/m\3\. Several
commenters noted that the average modeled benzene concentration is 0.8
[mu]g/m\3\, which is more than an order of magnitude less than the
proposed fenceline benzene concentration action level.
Two commenters argued for a lower action level threshold, citing
the proposed California OEHHA rule, which finalized new and revised
benzene reference exposure levels (REL) that are more stringent than
the ones the EPA used in the residual risk assessment supporting the
proposed rule.
Two commenters stated that while the fenceline benzene
concentration action level of 9 [mu]g/m\3\ is relatively protective
compared to standards adopted by many states, including Louisiana and
Texas, it is still 80-percent higher than the European Union's standard
of 5 [mu]g/m\3\. The commenter urged the agency to consider adopting a
stricter standard comparable to what other industrialized nations use.
Several commenters stated that the EPA's 9 [mu]g/m\3\ action level
is inconsistent with the statutory text and objectives of CAA sections
112(d) and (f), which direct the EPA to focus on the best-performing,
lowest-emitting sources, in order to require the ``maximum achievable''
emission reductions. The commenters stated that the EPA promulgated the
9 [mu]g/m\3\ limit without properly following the statutory
requirements for establishing MACT floor limits, pointing out that the
EPA made no determination of whether or not these general models were
representative of the emissions levels actually achieved by the
submitting refinery, and no connection was drawn between the best
performing sources and the eventual 9 [mu]g/m\3\ limit.
On the other hand, several commenters opposed the 9 [mu]g/m\3\
action level suggesting that it was not achievable and that it is
arbitrary. Some commenters noted that emission/dispersion models are
always very site-specific and do not necessarily yield a result that is
reliable or reproducible. Several commenters stated that additional
studies are necessary to allow the agency to account for these
variables and set a more appropriate concentration corrective action
level. Commenters suggested a 2-year data gathering effort at all
refineries and data evaluation before determining a specific threshold
to use.
Several commenters recommended action levels ranging from 15 [mu]g/
m\3\ to 20 [mu]g/m\3\ of benzene to account for the variability
expected in monitoring data. The commenters stated that modeling biases
have underestimated the necessary action level to achieve the stated
goals of the program.
Response: First, it is important to note that the purpose of the
standard has not changed between proposal and promulgation, namely that
it is a technology-based standard that is an advancement in practices
to manage fugitive emissions. It is not intended to be a separate or
new MACT standard promulgated pursuant to CAA sections 112(d)(2) and
(3) for which a ``floor'' analysis would be required.\7\ Nor is it a
standard that we are promulgating pursuant to CAA section 112(f)(2) as
necessary to provide an ample margin of safety to protect public health
or prevent an adverse environmental effect.\8\ Thus, claims that a
standard should reflect European Union health-based standards or the
California OEHHA rule are misplaced. We also disagree with the
suggestion that the proposed monitoring requirement will allow for
higher emissions. As noted elsewhere, we are retaining all of the
source-specific requirements for fugitive emissions sources that exist
in Refinery MACT 1.
---------------------------------------------------------------------------
\7\ To the extent that the commenters are suggesting that EPA
must re-perform the MACT floor analysis for purposes of setting a
standard pursuant to section 112(d)(6), we note that the D.C.
Circuit has rejected this argument numerous times, most recently in
National Association for Surface Finishing et al. v. EPA No. 12-1459
in the U.S. Court of Appeals for the District of Columbia.
\8\ Although we did not establish this limit to address residual
risk under CAA section 112(f)(2), the limit was derived from the
same inventory used for our risk modelling. Thus, based on our
current reference concentration for benzene, the 9 [mu]g/m\3\ action
level will also ensure that people living near the refinery will not
be exposed to cancer risks exceeding 100-in-1 million.
---------------------------------------------------------------------------
We disagree with the commenters that suggest that the proposed
action level of 9 [mu]g/m\3\ is too low and may not be achievable even
for well-performing facilities. As discussed in the preamble for the
proposed rule, we selected the 9 [mu]g/m\3\ benzene action level
because it is the highest value on the fenceline predicted by the
dispersion modeling and, thus, is a level that we estimate that no
refinery should exceed when in full compliance with the MACT standards,
as amended by this final rule. All of the results of our pilot study,
the API study, and the other ambient monitoring data near refineries
clearly indicate that this level is achievable. Furthermore, we expect
the fenceline concentration difference measured following the
procedures in the final rule to be indicative of refinery source
contributions and we have provided procedures to isolate these
concentrations from outside sources, as well as background.
We expect that the fenceline monitoring standard will result in
improved fugitive HAP emissions management as it will alert the
refinery owners or operators of fugitive sources releasing high levels
of HAPs, such as large leaks, faulty tank seals, etc.
iv. Fenceline Monitoring Root Cause Analysis and Corrective Action
Provisions
Comment: A number of commenters objected to the proposal's ``open-
ended'' provisions allowing the EPA to direct refinery owners or
operators to change their operations in order to achieve the fenceline
limit, with no regulatory limits on costs and without consideration of
the impact to safe operations or operability of the plant. Another
commenter stated that the EPA must properly assess the costs associated
with the root cause analysis/corrective action requirements and should
establish a cost effectiveness threshold for any required root cause
analysis/corrective action to ensure that limited resources are
effectively and efficiently applied for the control of emissions.
One commenter stated the proposed fenceline benzene concentration
action level is effectively an ambient air standard, because corrective
action to achieve that level is required and that if a facility's
initial corrective action is unsuccessful, the rule provides that
further action is required and the EPA must approve that further
corrective action plan. Thus, the commenter argued, the EPA would
essentially be able to dictate corrective actions, with no bounds on
what could be required and no consideration of whether any cost-
effective actions are available to assure the action level is met. The
commenter continued that such a requirement converts a work practice
program to an emission limitation and such ambient air limits are not
authorized by CAA section 112. Several commenters noted that LDAR and
current work practice programs have no similar requirement for the EPA
approval, and the commenters suggested that the requirement for the EPA
approval of any second corrective action should not be included in 40
CFR 63.658(h).
Another commenter recommended that, if after corrective action, a
facility still has an exceedance for the next sampling episode, then
the facility should be required to do more than it
[[Page 75198]]
did after the first root cause analysis, as the prior corrective action
clearly did not correct the problem. The commenter stated that one
corrective action measure the EPA should include in all such instances
is higher-quality monitoring such as UV-DOAS for at least 1 year to
monitor, identify, correct and assure ongoing compliance after the
exceedance problem is fixed.
Response: The ``on-going'' requirement to achieve the fenceline
benzene concentration action level is no different in concept from the
LDAR requirements for equipment or heat exchange systems in the
Refinery MACT 1 rule, which requires the refinery owner or operator to
repair the source of the emissions regardless of what it takes until
compliance with the standard is achieved.
We disagree with the claim that the EPA must assess the costs
associated with the root cause analysis/corrective action requirements
and establish a cost effectiveness threshold for any required root
cause analysis/corrective action to ensure that limited resources are
effectively and efficiently applied for the control of emissions. We
did not attempt to project the costs of the root cause analysis/
corrective action for at least two reasons. First, based on the
dispersion modeling of the benzene emissions reported in response to
the inventory section of the 2011 ICR, we project that no refinery
should exceed that fenceline benzene concentration action level if in
full compliance with the MACT standards, as amended by this action.
Thus, assuming compliance with the MACT standards, we would expect that
there are no costs for root cause analysis/corrective action. To the
extent that there are exceedances of the action level, the premise of
the fenceline monitoring is to provide the refinery owners or operators
with the flexibility to identify the most efficient approaches to
reduce the emissions that are impacting the fenceline level. Since the
choice of control is a very site-specific decision, we would have no
way to know how to estimate the costs. Thus, the source is in the best
position to ensure that resources are effectively and efficiently spent
to address any exceedance.
We intended the proposed requirement for refinery owners or
operators to submit a corrective action plan for the EPA approval to
provide the Administrator with information that they were making a
good-faith effort to reduce emissions below the fenceline benzene
concentration action level, as expeditiously as practicable. However,
we understand the importance for refinery owners or operators to begin
corrective action as soon as possible, without having to wait for the
EPA approval. Therefore, we are finalizing the requirement for refinery
owners or operators to submit such plans but we are not finalizing the
requirement that the EPA must approve the plan prior to the corrective
action being taken.
We previously responded to comments regarding UV-DOAS or other
open-path monitoring systems in this section, explaining that the
current detection limits for these systems exceeds the action level
threshold and, thus, these systems would not provide usable data to
inform corrective action. Thus, we disagree that the EPA should require
these systems for all facilities whose first attempt at corrective
action is ineffective.
v. Fenceline Monitor Siting Requirements
Comment: Numerous commenters provided suggestions on, or requested
clarification of, the monitor siting requirements. Several commenters
stated that proposed Method 325A uses the terms ``fenceline or property
boundary,'' while it should consistently use the term ``property
boundary'' or even ``property line'' as the fenceline location. Several
commenters stated that Sections 8.2.2.1.4 and 8.2.2.3 of Draft Method
325A specify that samplers be placed just beyond the intersection where
the measured angle intersects the property boundary and this could
require placing monitors on other people's property, in a road, in a
water body or in a railroad right-of-way. The commenters suggested that
facilities should be allowed to place monitors at any vector location
that meets other requirements between the property boundary and the
source nearest the property boundary. They stated that facilities need
this clarification to avoid obstructions (e.g., buildings or trees)
that may be at the property line.
Numerous commenters requested that the rule clarify where monitors
need to be placed in special circumstance, such as refineries bisected
by a road, railroad or other public right-of-way or a boundary next to
a navigable waterway. Several commenters stated that refiners should
not need to place monitors on these property boundaries or other
property boundaries where there are no residences within 500 feet of
the property line. Commenters also asked if areas that had non-refinery
operations, but are still inside the property boundary, would be
included for purposes of determining where to site monitors.
A few commenters expressed concern about the approach for
determining the number of required monitors at a site based on the
acreage, noting that it is unfair to small facilities and will leave
gaps in monitoring coverage for very large facilities. Some commenters
recommended amending the proposed rule to require the placement of
fenceline monitors at fixed distances along facilities' perimeters with
no maximum number of monitors. Some commenters stated that the rule
should specify an acceptable range on the 2,000-foot spacing
requirement or the radial placement requirement as it may be necessary
to address accessibility or safety concerns. Several commenters
suggested that a lower minimum number of sampling monitors should be
required for very small refineries or small ``subareas.'' These
commenters noted that refineries often include disconnected parcels
that can be very small (e.g., 10 acres or less). If each disconnected
parcel must be treated as a separate subarea, then both sampler siting
options in Draft Method 325A would result in unnecessarily large
numbers of samplers extremely close together. Some commenters
recommended that Method 325A specify that samplers need not be placed
closer than 500 feet (versus the normal 2,000-foot interval specified
in Option 2) along the fenceline from an adjoining sampler, regardless
of whether the radial or linear approach is used and should waive the
minimum number of samplers specified in Sections 8.2.2.1.1, 8.2.2.2.1,
and 8.2.3.1. Another commenter added that the rule should waive the
requirement for additional samplers in Sections 8.2.2.1.5 and 8.2.3.5
if the 500-foot minimum spacing criterion is compromised.
Response: We agree that the Method 325A should provide clear and
consistent language. We have revised the language to be consistent in
referring to the ``property boundary''. We have also revised the Method
to allow placement of monitors at any radial distance along either a
vector location or linear location (that meets the other placement
requirements) between the property boundary and the source nearest the
property boundary. That is, the monitors do not need to be placed
exactly on the property boundary or outside of the property boundary.
They may be placed within the property closer to the center of the
plant as long as the monitor is still external to all potential
emission sources. We do note that if the monitors are placed farther in
from the property boundary, the owner or operator should take care to
ensure, if possible, that the radial distance from the sources to the
monitors is at least 50
[[Page 75199]]
meters. If the perimeter line of the actual placement of the fenceline
monitors is closer than 50 meters to one or more sources, then the
additional monitor citing requirements will apply. We have revised
subparagraphs of Section 8.2.2 to provide this allowance. This
clarification should address issues related to obstructions such as
tall walls located at the facility boundary.
We intended that the fenceline monitoring would create a monitoring
perimeter capable of detecting emissions from all fugitive emission
sources at the refinery facility. We have long established that a road
or other right of way that bisects a plant site does not make the plant
site two separate facilities, and, thus, would not be considered part
of the property boundary. As we agree that monitors need only be placed
around the property boundary of the facility, it would not be necessary
to place monitors along a road or other right-of-way that bisects a
facility. We have clarified this in the final rule and Method 325A.
If the facility is bounded by a waterway on one or more sides, then
the shoreline is the facility boundary and monitors should be placed
along this boundary. If the waterway bisects the facility, the waterway
would be considered internal to the facility and monitors would only be
needed at the facility perimeter.
Regarding the comment that monitors should not be required where
there is no residence within 500 feet of the property line, we
disagree. We proposed and are finalizing the fenceline monitoring
standards under CAA section 112(d)(6) as a means to improve fugitive
HAP emissions management, regardless of whether there are people living
near a given boundary of the facility.
Regarding the clarification requested about monitor placement
considering non-refinery operations, the property boundary monitors
should be placed outside of all sources at the refinery. This is
because moving the monitoring line inward to exclude the non-refinery
source could lead to an underestimation of the [Delta]C compared to the
monitoring external of the entire site. If the non-refinery source is
suspected of contributing significantly to the maximum concentration
measured at the fenceline, a site-specific monitoring plan and
monitoring location specific near-field interfering source (NFS)
corrections will be needed to address this situation.
Section 8.2.3 of Method 325A includes language to provide some
flexibility when using the linear placement (10% or 250 feet). We consider it reasonable to provide similar placement
allowance criteria for the radial placement option (1
degree). We are not providing requirements that would allow small area
refineries to use fewer than 12 monitoring sites. We do not consider
that any refinery would be so small as to warrant fewer than 12
monitors; however, we did not necessarily consider very small subareas
for irregularly shaped facilities or segregated operations. When
considering these subareas, we agree that fewer than 12 monitoring
sites should be appropriate. Therefore, we have provided that monitors
do not need to be placed closer than 152 meters (500 feet) (or 76
meters (250 feet) if known sources are within 50 meters (162 feet) of
the monitoring perimeter, which is likely for these subareas or
segregated areas) with a stipulation that a minimum of 3 monitoring
locations be used per subarea or segregated area. We note, however,
that this distance provision does not obviate the near source extra
monitoring siting requirements or the requirement to have a minimum of
three monitors per subarea or segregated area.
If facility owners or operators have questions regarding the
required locations of monitors for a specific application, they should
contact the EPA (or designated authority) to resolve questions about
acceptable monitoring placement.
vi. Compliance Time for Fenceline Monitoring Requirements
Comment: Some commenters supported EPA's proposal to provide 3
years to put a fenceline monitoring program in place, but the
commenters believe that timing is unclear in the proposed regulatory
language, which appears in Table 11 to subpart CC, and requested that
the EPA add the initial compliance date to 40 CFR 63.658(a). One
commenter stated that instituting this program for all 142 major source
U.S. refineries would require considerable time. Based on their
experience with their pilot study, one commenter noted that
commercially available weather guards meeting the specifications of
proposed Method 325A are not available and would need to be fabricated.
Additionally, a commenter stated that only a limited number of
laboratories in the U.S. are able to perform the necessary analyses.
According to the commenter, considerable time and effort will be needed
to qualify additional laboratories and to expand the capacity of
existing laboratories to handle the samples from 142 refineries.
Other commenters disagreed with the EPA's proposed compliance time
and suggested that the EPA shorten the timeline for implementation at
refineries so that possible corrective action occurs much sooner than
proposed. The commenters suggested that deployment of passive samplers
can proceed more promptly than proposed, especially since the EPA has
simultaneously proposed specific ``monitor siting and sample collection
requirements as EPA method 325A of 40 CFR part 63, Appendix A, and
specific methods analyzing the sorbent tube samples as EPA Method 325B
of 40 CFR part 63, Appendix A.'' Moreover, the commenter noted, a
principal reason that the EPA selected passive monitors over active
monitors was due to the relative ``ease of deployment.'' The commenter
claimed this ease of deployment rationale is undermined by a 3-year
grace period to deploy passive monitors when the EPA is providing very
specific criteria for their use. The commenter suggested that the EPA
require full compliance with the passive monitoring requirement within
1 year of the effective date of the rule.
Response: While we realize that it will take some time for the
refinery owners or operators to understand the final rule and develop a
compliant monitoring program, we agree that in requiring the passive
sampler monitoring system, we recognized the ease of implementation and
deployment. Although industry commenters identified issues they faced
in the API pilot study while trying to implement the monitoring method,
we note that the 12 facilities that participated in the API pilot study
installed the fenceline monitors and began sampling in late 2013 with
relative ease and within months of obtaining the draft methods. Thus,
we disagree with the suggestion that 3 years is insufficient and agree
with other commenters that 3 years is in fact too long. However, we
also are aware that the API pilot facilities used the direct [Delta]C
approach proposed and did not attempt to develop site-specific
monitoring programs to correct for interfering near-field sources.
Although we expect that facilities could complete direct implementation
of the proposed fenceline monitoring requirement within 1 year after
the effective date of the rule, as suggested by some commenters,
facilities that choose to develop a site-specific monitoring plan would
need a longer period of time. Therefore, we are finalizing requirements
that specify that facilities must begin monitoring for the official
[[Page 75200]]
determination of [Delta]C values no later than 2 years after the
effective date of the rule.
vii. Fenceline Monitoring Recordkeeping and Reporting Requirements
Comment: Some commenters suggested that facilities should be
required to submit the monitoring data via the ERT only if they exceed
the fenceline benzene concentration action level and that all remaining
data should be kept on-site and available for inspection or upon
request of the EPA, citing that this is consistent with EPA's
semiannual NESHAP reporting of only exceptions (i.e., deviations).
Other commenters requested that the EPA only post the rolling annual
average concentration values and not the 2-week monitoring data. These
commenters indicated concern that if errors are present in the raw data
that are submitted semiannually to the EPA, the data, errors and all,
will be released to the public and correcting them will not take place
or will not take place in a timely manner. One commenter added that
there is very little useful information that can be gleaned from the
raw data and posting it simply invites misunderstandings.
Commenters also stated that the EPA should adopt reporting
requirements to ensure that facilities report the monitoring data
appropriately. Specifically, commenters recommended that 40 CFR
63.655(h)(8)(i) should be clarified to only require reporting of valid
data and cautioned that data should be processed to allow accurate
calculations of annual averages to be used for reporting and
evaluation. To accomplish this, commenters recommended that the rule
provide 75 days from the end of a 6-month sampling period to report to
the EPA, rather than the proposed 45-day period, in order to provide
adequate time to obtain quality-assured results for all 2-week sampling
periods.
One commenter applauded the proposal's requirements for electronic
reporting of the fenceline concentration data and making the resulting
information publicly available. However, the commenter recommended that
the EPA consider a more truncated data reporting period that is more
consistent with the associated milestones of collecting a 14-day
sampling episode. As is, the commenter claimed, the proposed rule would
have a lag time of up to 7.5 months between data collection and
posting. The commenter indicated that data reporting on a more frequent
schedule will not only provide transparency, but will provide states
and local agencies with information about air quality at refineries at
a frequency that could allow informed activities to address leaks much
more quickly and protect public health.
Response: We disagree with the commenters who suggest that
facilities only report the rolling annual average or only exceedances
of the fenceline benzene concentration action level because the
commenters believe there is little information to be gleaned from the
raw data. Monitoring data are useful in understanding emissions,
testing programs, and in determining and ensuring compliance. We
generally require reporting of all test data, not just values
calculated from test data and/or where a facility exceeds an emissions
or operating limit. For example, when we conduct risk and technology
reviews for source categories, we are adding requirements for
facilities to submit performance test data into the ERT, not just
performance test data that indicates an exceedance of an applicable
requirement. In the Mercury and Air Toxics Rule, we require facilities
to report direct measurements made with CEMS, such as gas
concentrations, and we require hourly reporting of all measured and
calculated emissions values (see discussion at 77 FR 9374, February 16,
2012). In particular, for the fenceline monitoring requirements in this
final rule, we offer facilities options for delineating background
benzene emissions and benzene emissions not attributable to the
refinery, and we offer options for reduced monitoring, making it even
more necessary that we have all of the data to review to ensure that
testing and analyses are being done correctly and in compliance with
the requirements set out in the regulations, and that root cause
analyses and corrective actions are being performed where necessary.
Therefore, as proposed, we are finalizing the requirements that
facilities report the individual 2-week sampling period results for
each monitor, in addition to the calculated [Delta]C values in their
quarterly reporting.
Regarding commenters' concerns that facilities post accurate data
and have sufficient time to perform quality assurance on the data, in
the final rule, we have established provisions for how sources are to
address outliers and data corrections. Additionally, as proposed, we do
not require an initial report until facilities have collected 1 year of
data so that facilities do not report the data until a rolling annual
average value can be determined. This will allow refinery staff and
analytical laboratories to iron out any issues that might arise as they
implement these methods for the first time. Once this initial data
collection period is complete, we anticipate that data quality issues
should be infrequent. Therefore, we are providing a 45-day period
following each quarterly period before facilities must submit the
monitoring results, which should provide facilities adequate time to
correct any data errors prior to reporting the data.
Regarding comments that suggest reporting each 2-week sample result
soon after its collection, we disagree. This frequency would put undue
burden on the refinery owners or operators in trying to collect, review
and quality assure the data prior to reporting. However, we agree with
commenters that more frequent reporting of the fenceline monitoring
data would be useful. Therefore, we have revised the reporting
frequency for the fenceline monitoring data to be quarterly in the
final rule rather than semiannually as proposed. Additionally, we
understand that there is a lot of interest in how these data will be
presented to the public, and we plan to reach out to all stakeholders
on appropriate approaches for presenting this information in ways that
are helpful and informative.
b. Refinery MACT 2
This section provides comment and responses for the key comments
received regarding the technology review amendments proposed for
Refinery MACT 2. Comment summaries and the EPA's responses for
additional issues raised regarding the proposed requirements resulting
from our technology review are in the ``Response to Comment'' document
in the public docket (Docket ID No. EPA-HQ-OAR-2010-0682).
i. FCCU
We received comments on the consideration of developments in
pollution controls, the averaging time for FCCU PM limits, and the FCCU
opacity limit, as discussed below.
Comment: One commenter stated that the EPA failed to consider
developments in pollution controls for HAP from FCCUs for two reasons.
First, the commenter contended that cost is not a valid consideration
to evaluate if a ``development'' in pollution control is necessary
pursuant to section 7412(d)(2), (3), (6), unless the EPA is setting a
``beyond-the-floor'' requirement.
Second, the commenter claimed that the EPA's review of developments
is nearly 10 years old and misses some important pollution control
[[Page 75201]]
improvements in the industry. For example, the commenter noted that
Valero Benicia installed a combination of controls in 2012 including a
scrubber, SCR and CO Boiler that combine exhaust streams from the FCCU
and coking and reportedly eliminate HAP emissions entirely from these
sources.
The commenter also asserted that EPA consent decrees impose lower
effective limits on PM than the EPA considered under the technology
review. The commenter identified the BP Whiting facility as subject to
0.7 lb PM/1,000 lbs coke burn-off at one FCCU and 0.9 lb PM/1,000 lbs
coke burn-off at another and claimed these limits are lower than the
1.0 lb PM/1,000 lbs coke burn-off limit currently mandated by Refinery
MACT 2.
Response: We disagree that we cannot consider costs when
determining if it is necessary to revise an existing MACT standard
based on developments in practices, processes and control technologies.
The commenter suggests that we cannot consider costs because of the
requirements in CAA section 112(d)(2) and (3) for establishing initial
MACT standards and which do not allow for consideration of costs until
the second, ``beyond the floor'' phase of the analysis. As discussed
previously in this preamble where we respond to comments on the
fenceline monitoring requirements, to the extent that the commenters
are suggesting that EPA must re-perform the MACT floor analysis for
purposes of setting a standard pursuant to section 112(d)(6), we note
that the D.C. Circuit has rejected this argument numerous times, most
recently in National Association for Surface Finishing et al. v. EPA
No. 12-1459 in the U.S. Court of Appeals for the District of Columbia.
Regarding the claim that the EPA did not consider the types of
controls at the Valero and BP facilities, we disagree. The control
measures for both of those facilities are controls that existed at the
time of the development of the MACT standard. Thus, we did not identify
these technologies as developments in control technologies during the
technology review. However, we did identify developments in processes
or practices that reflect better control by the existing technology and
we reviewed modified emission limits that reflect that better level of
control. The commenter suggested that we failed to consider a level of
zero when the Valero facility was able to achieve zero emissions
through a combined SCR, boiler and scrubber. However, the commenter
provided no information to support such a claim and we are skeptical
that such a result could be achieved. We note that the SCR is designed
specifically to reduce NOX emissions, and would not be
capable of reducing significantly, much less eliminating completely,
HAP emissions. Similarly, based on our long-standing understanding of
the processes, neither a boiler nor a scrubber could achieve such a
result. Regarding the level of emissions achieved at the BP Whiting
facility, we note that we evaluated control systems that can meet 0.5
lb PM/1,000 lb coke burn-off, which is a lower limit than that at BP
Whiting. We determined that these were cost-effective to require for
new units that are installing a new control system. However, we
determined that retrofitting controls designed to meet a PM limit of
1.0 lb PM/1,000 lbs coke burn-off to now meet a limit of 0.5 lb PM/
1,000 lbs coke burn-off was not cost-effective when considering PM and
PM2.5 emissions reductions. We projected the cost of the 0.5
lb PM/1,000 lbs coke burn-off limit in retrofit cases to be $23,000 per
ton PM emissions reduced. To meet a limit of 0.7 lb PM/1,000 lbs coke
burn-off or 0.9 lb PM/1,000 lbs coke burn-off, as is the case for BP
Whiting, the retrofit costs would be similar to this 0.5 lb PM/1,000 lb
coke burn-off option, but the reductions would be even less, resulting
in costs over $23,000 per ton. As metal HAP content of FCCU PM is
approximately 0.1 to 0.2-percent of the total PM, the cost of requiring
this lower limit for existing FCCU is over $10 million per ton of metal
HAP reduced. Therefore, we determined that it is not necessary to
revise the PM standard for existing FCCU sources.
Comment: Refinery MACT 2 requires the owner or operator to
demonstrate compliance with the PM FCCU limits by complying with the
operating limits established during the performance test on a daily
(i.e., 24-hour) average basis. Several commenters objected to the EPA's
proposal to revise this requirement to a 3-hour averaging time.
Commenters restated EPA's arguments for 3-hour averaging time as: (1)
Daily average could allow FCCUs to exceed limits for short periods
while still complying with the daily average, (2) consistency with NSPS
subpart Ja and (3) consistency with duration of testing. The commenters
stated that the EPA had not provided any data that show that the daily
average could allow FCCUs to exceed limits for short periods and,
therefore, the EPA is using a hypothetical compliance assurance
argument to change emission limits. The commenters stated that a change
in emission limits is not authorized by CAA section 112 because the
emission limitations in Refinery MACT 2 for FCCUs were established as
daily averages following the floor and ample margin of safety
requirements in section 112(d)(2) of the CAA.
The commenters also state that the EPA's additional arguments for
the change to a 3-hour average are irrelevant and legally deficient.
The commenters stated that the combination of a numerical emission
limit and an averaging period frames the stringency of a limitation and
that a reduction in either of those factors results in a significant
lowering of the operating limit. The commenters conclude that the EPA
has proposed to change the stringency of the requirements without
justification, and the CAA requires that such a change in stringency be
justified pursuant to CAA section 112(d)(6) or (f)(2). The commenters
stated that increasing stringency for consistency with NSPS rules is
not a criterion for a CAA section 112(d)(6) action. Rather that section
requires a change to be due to ``developments.'' The only change in
technology since the 2002 promulgation of Refinery MACT 2 is the
availability of PM continuous emission monitoring system (CEMS), which
is unproven.
One commenter noted that changing the averaging time is a very
significant modification considering that the compliance limits would
apply for periods of SSM. This commenter stated that it is unlikely
that existing operations can consistently be in compliance with a new
3-hour average since the current daily averaging was put in place to
recognize that there will be periods of operating variability that do
not represent the longer term performance of an FCCU. The commenters
recommended that the EPA retain the daily averaging requirement.
Response: We disagree with the commenters' statement that reducing
the averaging time from a 24-hour basis to a 3-hour basis for
demonstrating compliance with the FCCU PM emission limit, using
operating limits established during the performance test, is a change
to the MACT floor. The emission limit of 1.0 lb PM/1,000 lbs coke burn-
off is the MACT floor, and we are not changing the PM emissions limit
(or alternate Ni limits) in Table 1 to subpart UUU (except to remove
the incremental PM limit that did not comport with the MACT floor
emissions limitation).
However, whether or not it is a change from the MACT floor is not
relevant. Pursuant to CAA section 112(d)(6), the EPA must revise MACT
standards ``as necessary'' considering developments in practices,
processes and control technologies. For this
[[Page 75202]]
exercise, we considered any of the following to be a ``development'':
Any add-on control technology or other equipment that was
not identified and considered during development of the original MACT
standards.
Any improvements in add-on control technology or other
equipment (that were identified and considered during development of
the original MACT standards) that could result in additional emissions
reduction.
Any work practice or operational procedure that was not
identified or considered during development of the original MACT
standards.
Any process change or pollution prevention alternative
that could be broadly applied to the industry and that was not
identified or considered during development of the original MACT
standards.
Any significant changes in the cost (including cost
effectiveness) of applying controls (including controls the EPA
considered during the development of the original MACT standards).
In determining whether there are ``developments,'' we review, among
other things, EPA regulations promulgated after adoption of the MACT,
such as the NSPS we identified in this instance. We identified the
enhanced monitoring requirements for these operating limits as a
development in practices that will help ensure FCCU owners or operators
are properly operating control devices and, thus, are meeting the PM
emission limit at all times. We further determined that this enhanced
monitoring was cost effective and proposed that it was necessary to
revise the existing standard pursuant to CAA section 112(d)(6).
While we do not have continuous PM emissions data that show actual
deviations of the PM limit, we do not need such data in order to
conclude that such deviations could occur when daily averages are used.
The Refinery MACT 2 (i.e., subpart UUU) rule requires owners or
operators to establish operating limits based on three 1-hour runs
during the performance test. As a matter of simple mathematics, a
source could demonstrate that it is meeting the operating limit based
on a 24-hour average but could be exceeding the 1.0 lb PM/1,000 lbs
coke burn-off emission limit based on a 24-hour average or for one or
more individual 3-hour periods during that 24-hour average. For
example, an owner or operator could operate with a power input 5-
percent higher than the operating limit for 23 hours, have the ESP off
(zero power) for one hour, and still comply with a 24-hour average
operating limit. However, it would be difficult for this same unit to
meet the 1.0 lb PM/1,000 lbs coke burn-off emissions limit over a 24-
hour period, and it certainly would not meet the limit for every 3-hour
period during that day. As the operating limit can be established to
correspond with 1.0 lb PM/1,000 lbs coke burn-off, the 5-percent higher
power input would likely correspond with a 0.95 lb PM/1,000 lbs coke
burn-off emissions rate (5-percent lower). Uncontrolled emissions are
typically 6 to 8 lbs/1,000 lbs coke burn-off. Thus, this unit would
have emissions averaging approximately 1.2 lbs PM/1,000 lbs coke burn-
off during this 24-hour period [i.e., (0.95*23+7)/24], but would be in
compliance with the 24-hour average operating limit. The unit would
obviously also be out of compliance with the 3-hour average over the
period when the power was turned off. We also have concerns that the
operating limits are not always linear with the emissions, so that the
longer averaging times do not effectively ensure compliance with the PM
emissions limit. Therefore, as proposed, we are finalizing the
requirement for owners or operators to comply with the operating limits
on a 3-hour basis, rather than the 24-hour basis currently in the rule.
Comment: The technology review for FCCUs resulted in the EPA
proposing to remove the 30-percent opacity alternative limit for
demonstrating compliance with the PM emissions limit that is available
for refineries complying with the Refinery NSPS 40 CFR part 63, subpart
J. Two commenters supported the EPA's proposed removal of the 30-
percent opacity limit for FCCUs. Other commenters stated that current
technology is good enough for a 10- or 20-percent opacity limit. On the
other hand, several commenters stated that the proposed removal of the
30-percent opacity limit must meet the criteria specified in CAA
section 112(d)(6) and (f)(2), which requires analysis of the statutory
basis, environmental impacts, costs, operational and compliance
feasibility and impacts, that the EPA has not conducted. The commenters
claimed that had the EPA conducted a proper analysis, the EPA would
have determined that the proposed change to remove the 30-percent
opacity limit is not necessary or supportable. Additionally, these
commenters stated that since the underlying PM emissions limit is
unchanged, there is no emission reduction justification for this
proposed change, and the change would not meet the CAA section
112(d)(6) requirement of being cost effective. The commenters also
noted that processes or practices for existing FCCUs have not changed,
as required for a CAA section 112(d)(6) revision.
Several commenters urged the EPA to maintain the 30-percent opacity
limit for these FCCUs. As a practicable and cost-effective alternative
to address the EPA's concern as to whether compliance with a 30-percent
opacity limit ensures compliance with the PM emissions limit,
commenters suggested annual performance tests to confirm that the FCCU
is meeting the PM emissions limit, rather than performance tests every
5 years, as proposed.
One commenter stated that the EPA never intended for the opacity
limit in Refinery NSPS subpart J to be used to demonstrate compliance
with the PM emissions limit, but instead to assure the PM controls
operate properly. The commenter stated that the EPA's conclusion that
the 30-percent opacity limit may not be sufficiently stringent to
ensure compliance with the underlying PM emissions limit is based on a
false premise as to the purpose of the opacity standard because as the
EPA states, ``Opacity of emissions is indicative of whether control
equipment is properly maintained and operated.''
Several commenters stated that the proposed elimination of the 30-
percent opacity limit currently in Refinery MACT 2 leaves existing
FCCUs that use cyclones with no viable alternative approach to
demonstrate compliance with the PM emissions limit without adding or
replacing controls. They stated the other approaches for demonstrating
compliance with the PM emissions limit in Refinery MACT 2 (such as
development of a site-specific opacity limit) do not work for them. The
commenters stated that although they believe that more frequent
performance tests would show that the FCCUs are in fact meeting the PM
emissions limit, the absence of the 30-percent opacity limit would
force FCCUs using cyclones for PM control to install additional, costly
PM controls (e.g., ESPs or wet gas scrubbers). They projected that
these additional controls would cost tens of millions of dollars per
FCCU and would require at least 3 years of compliance time.
Additionally, one commenter stated that even FCCUs with additional
downstream PM controls would not be able to achieve a site-specific
limit at all times and needed the availability of the alternative 30-
percent opacity limit. One commenter estimated that installing an ESP
to meet the proposed 10-percent opacity limit would cost approximately
$121,000/ton, assuming a 32 tpy PM emission reduction. The commenter
noted that the ESP would also increase GHG emissions and require more
energy
[[Page 75203]]
resources from the facility. The commenter concluded that installing an
ESP is neither cost effective nor appropriate considering non-air
quality environmental and health impacts and energy requirements, and
recommended that the EPA maintain the current NSPS subpart J
alternative limits and add additional alternative limits into Refinery
MACT 2 only as optional limits for demonstrating compliance with the PM
emissions limit.
Response: In promulgating Refinery MACT 2, the EPA identified the
1.0 lb PM/1,000 lbs coke burn-off limit as the MACT floor but allowed a
compliance option for FCCUs subject to Refinery NSPS subpart J to
comply with an opacity limit up to 30 percent with one 6-minute
allowance to exceed the 30-percent opacity in any 1-hour period. As
stated in the proposal, compliance studies have shown that the 30-
percent opacity limit does not correlate well with the 1.0 lb PM/1,000
lbs coke burn-off limit, and that an FCCU can comply with the 30-
percent opacity limit while its emissions exceed the PM emissions
limit.\9\ Regardless of whether the 30-percent opacity limit in
Refinery NSPS subpart J was designed to ``ensure that the control
device was operated properly,'' Refinery MACT 2 allows sources subject
to NSPS subpart J to use the 30-percent opacity limit to demonstrate
continuous compliance with the PM emissions limit. We have determined
that the 30-percent opacity limit is inadequate for the purpose of
demonstrating continuous compliance with the PM emissions limits in
Refinery MACT 2. As such, we proposed to remove this opacity limit and
require the owner or operator to either demonstrate compliance with the
PM emissions limit by continuously monitoring the control device
parameters established during the performance test or establish and
monitor a site-specific opacity limit. For clarity, we note that we
proposed to allow a site-specific opacity limit, not a 10-percent
opacity limit as some commenters suggest. The site-specific opacity
limit can be significantly higher than 10 percent, but it cannot be
lower than 10 percent.
---------------------------------------------------------------------------
\9\ Compliance Investigations and Enforcement of Existing Air
Emission Regulations at Region 5 Petroleum Refineries. U.S.
Environmental Protection Agency, Region 5--Air and Radiation,
Chicago, Illinois. March 9, 1998.
---------------------------------------------------------------------------
While the compliance study indicates that a 30-percent opacity
limit does not correlate well with a 1.0 lb PM/1,000 lbs coke burn-off
emissions limit, further review of this same study indicates that a 20-
percent opacity limit provides a reasonable correlation with units
meeting the 1.0 lb PM/1,000 lbs coke burn-off emissions limit. We also
reviewed the data submitted by the commenters regarding PM emissions
and opacity correlation. While the data suggest that there is
variability and uncertainty in the PM/opacity correlation, the data do
not support that a 30-percent opacity limit would ensure compliance
even when considering the uncertainty associated with the PM/opacity
correlation. Based on the variability of the 3-run average opacity
limits, we determined that, if the 3-hour average opacity exceeded 20-
percent, then it was highly likely (98 to 99-percent confidence) that
the FCCU emissions from the unit tested would exceed the PM emissions
limit.
After considering the public comments, reviewing the data submitted
with those comments, and further review of the compliance study, in
this final rule we are adding a 20-percent opacity limit, evaluated on
a 3-hour average basis for units subject to NSPS subpart J. As we noted
above, a 20-percent opacity limit provides a reasonable correlation
with the PM emissions limit, and an exceedance of this 20-percent
opacity limit will provide evidence that the PM emissions limit is
exceeded. However, it is possible that units could still exceed the PM
emissions limit while complying with the 20-percent opacity limit, if
those units operate close to the 1 lb PM/1,000 lbs coke burn-off
emissions limit. To address this concern, we considered the commenters'
suggestion to require a performance test annually rather than once
every 5 years. Some commenters suggested that this option specifically
apply to FCCUs with cyclones, but this option is applicable to any
control system operating very near the PM emissions limit and using an
opacity limit to demonstrate continuous compliance. We have determined
that the Refinery NSPS subpart J compliance procedures in Refinery MACT
2, in combination with a 20-percent opacity limit demonstrated on a 3-
hour average basis and with annual performance tests when a test
indicates PM emissions are greater than 80-percent of the limit (i.e.,
0.80 lb PM/1,000 lbs coke burn-off), will ensure continuous compliance
with the PM emissions limit. FCCUs with measured PM emissions during
the performance test at or below 0.80 lb PM/1000 lbs of coke burn-off
will remain subject to the requirement to conduct performance tests
once every 5 years, consistent with the requirements we proposed.
We do not agree with commenters that the proposed opacity revision
would add significant cost or compliance burden. The control device-
specific monitoring parameters that were proposed rely on parameters
commonly used to control the operation of the control device, so the
monitoring systems should be already available. Further, since we are
merely changing the opacity limit, we expect these units will already
have opacity monitoring systems needed to demonstrate compliance with
the PM emissions limit and would not incur costs for new equipment.
Comment: Several commenters stated that they agree with the EPA's
determination in the proposal that the current CO limits provide
adequate control of HCN. Two commenters stated that there are limited
HCN emissions data and that more data are needed before the Agency can
appropriately determine whether an HCN standard is necessary and
justified. One commenter noted that the process undertaken by the EPA
to estimate HCN emissions was flawed, and likely overestimates HCN
emissions significantly. Another commenter stated that they performed
HCN stack testing at three refineries and subsequent modeling at two
refineries and concluded that the ambient HCN emissions were well below
the applicable health limits.
In contrast, some commenters expressed concerns about high HCN
levels. One commenter stated that the EPA should consider re-evaluating
the benefit of low NOX emissions from the FCCU, if that is
indeed the cause of higher HCN emissions, because exposing people to
HCN is not acceptable. The commenter also noted that the community now
also has the increased dangers of storing and transporting aqueous
ammonia, which is used in some cases to achieve low NOX
emissions from the FCCU.
One commenter stated that the EPA must set stronger HCN standards
on FCCU emissions because of the high release amounts reported, the
fact that non-cancer risk is driven by emissions of HCN from FCCU, and
the fact that the EPA has never set standards for HCN emissions. The
commenter provided a report that they believe shows that the EPA has
not shown that CO is a reasonable or lawful surrogate to control HCN
and has not shown that the conditions necessary for a surrogate are met
with regard to CO and HCN, which is an inorganic nonmetallic HAP.
Further, the report indicates that SCR is a reasonable and cost
effective method for controlling HCN and that the EPA failed to review
and consider other viable methods to control HCN and must do so to
satisfy its legal obligations in this rulemaking.
[[Page 75204]]
Response: At the time we promulgated the MACT, we determined that
the control strategy used by the best performing facilities to reduce
organic HAP emissions was the use of complete combustion, which occurs
when the CO concentration is reduced to 500 ppmv (see the proposal for
Refinery MACT 2 at 63 FR 48899, September 11, 1998). We rejected
arguments that some facilities operate at CO levels well below 500 ppmv
and, thus, the MACT floor should be set at a lower CO concentration
because once CO concentrations reached 500 ppmv, there was no longer a
correlation between reduced CO concentrations and reduced HAP
concentrations. And, in fact, emissions of certain HAP, such as
formaldehyde, tended to increase as CO concentrations were reduced
below 500 ppmv.\10\
---------------------------------------------------------------------------
\10\ U.S. EPA, 2001. Petroleum Refineries: Catalytic Cracking
Units, Catalytic Reforming Units, and Sulfur Recovery Units--
Background Information for Promulgated Standards and Response to
Comments. Final Report.EPA-453/R-01-011. June. p. 1-19.
---------------------------------------------------------------------------
In the current rulemaking action, we determined at the time of the
proposed rule that this also holds true for HCN emissions. That is,
once CO emissions are reduced to below 500 ppmv (i.e., complete
combustion is achieved), we no longer see a direct correlation between
CO concentrations and HCN emissions.
All of the HCN emissions data we have were reported from units
operating at or below the 500 ppmv CO limit (i.e., in the complete
combustion range), so it is not surprising that there is not a strong
correlation between CO and HCN from the FCCU ICR source test data.
However, catalyst vendor data and combustion kinetic theory support the
fact that, in the partial burn mode (with CO concentrations of 2 to 6-
percent, which is 20,000 to 60,000 ppmv), HCN concentrations exiting
the FCCU regenerator are much greater than for units using complete
combustion FCCU regenerators or the concentration exiting a post-
combustion device used in conjunction with a partial burn FCCU
regenerator. Therefore, we maintain that complete combustion is the
primary control needed to achieve controlled levels of HCN emissions.
We initially thought the higher levels of HCN emissions that were
reported by sources achieving complete combustion might be due to a
switch away from platinum-based combustion promoters to palladium-based
combustion promoters. However, many of the units that were tested and
that had some of the lowest HCN emissions used palladium-based oxygen
promoters. Therefore, it appears unlikely that palladium-based catalyst
promoters are linked to the higher HCN emissions. We also evaluated one
commenter's argument that CO is not a good surrogate for HCN emissions,
but that SCR are a reasonable and cost-effective control strategy. We
are not aware of any data that suggest that an SCR removes HCN and the
commenter did not provide any support for that premise. At proposal, we
evaluated HCN control on units using extra oxygen or converting back to
platinum-based promoters to oxidize any HCN formed. This would cause
more NOX formation, which would then require post-combustion
NOX control, such as an SCR. However, if HCN emissions are
not a function of CO concentration beyond that required to achieve
complete combustion (as noted by the commenter), then more aggressive
combustion conditions and the use of an SCR (to remove the
NOX formed) may not be a viable control strategy. Therefore,
considering all of the data currently available and the comments
received regarding HCN emissions and controls, we maintain that the
only proven control technique is the use of complete combustion as
defined by a CO level of 500 ppmv or less. We are not establishing a
more stringent CO level because, once complete combustion is achieved,
(i.e., CO concentrations drop below 500 ppmv), no further reduction in
HCN emissions are achieved.
For the purposes of Refinery MACT 2, we consider the emission
limits and operating requirements for organic HAP in Tables 8 through
14 to subpart UUU of part 63 adequate to also limit HCN emissions.
Finally, we understand concerns about the reported HCN emissions
being higher than anticipated and the need for more data to better
determine HCN emissions levels. To address these concerns, we are
finalizing a requirement that facility owners or operators conduct a
performance test for HCN from all FCCU at the same time they conduct
the first PM performance test on the FCCU following promulgation of
this rule. Facility owners or operators that conducted a performance
test for HCN from a FCCU in response to the refinery ICR or subsequent
to the 2011 Petroleum Refinery ICR following appropriate methods are
not required to retest that FCCU.
4. What is the rationale for our final approach for the technology
review?
a. Refinery MACT 1
We did not receive substantive comments concerning our proposal
that it was not necessary to revise Refinery MACT 1 requirements for
MPV, gasoline loading racks and cooling towers/heat exchange systems.
Based on the rationale provided in the preamble to the proposed rule,
we are taking final action concluding that it is not necessary pursuant
to CAA section 112(d)(6) to revise the MACT requirements for MPV,
gasoline loading racks and cooling towers/heat exchange systems
emission sources at refineries.
We proposed that the options for additional wastewater controls are
not cost effective and thus it was not necessary to revise the MACT for
these emission sources. We received public comments suggesting that
emissions from wastewater systems are higher than modeled and that we
should develop additional technology standards for wastewater treatment
systems regardless of cost. As we discussed in the proposal, emissions
from wastewater are difficult to measure and emission estimates rely on
process data and empirical correlations, which introduces uncertainty
into the estimates. Although we do not have evidence, based on the
process data we collected, that emissions are higher than modeled at
proposal, we note that the fenceline monitoring program effectively
ensures that wastewater emissions are not significantly greater than
those included in the emissions inventory and modeled in the risk
assessment. Furthermore, we believe that cost is a valid consideration
in determining whether it is necessary within the meaning of section
112(d)(6) to revise requirements and that we are not required to
establish additional controls regardless of cost. Consequently, we
conclude that it is not necessary to revise the Refinery MACT 1
requirements for wastewater systems pursuant to CAA section 112(d)(6).
For storage vessels, we identified a number of options, including
requiring tank fitting controls for external and internal floating roof
tanks, controlling smaller tanks with lower vapor pressures and
requiring additional monitoring to prevent roof landings, liquid level
overfills and to identify leaking vents as developments in practices,
processes and control technology. We proposed to cross-reference the
storage vessel requirements in the Generic MACT (effectively requiring
additional control for tank roof fittings) and to revise the
[[Page 75205]]
definition of Group 1 storage vessels to include smaller tanks with
lower vapor pressures. We received comments that we could have required
additional controls on tanks and monitoring for landings, overfills and
leaking vents described above. We also received comments related to
clarifications of specific rule references and overlap provisions. We
addressed these comments in the ``Response to Comments'' document, and
we maintain that the additional control options described by the
commenters (tank roof landing/degassing requirements or use of geodesic
domes to retrofit external floating roofs) are not cost-effective.
Consequently, based on the rationale provided in the preamble to the
proposed rule and our consideration of public comments, we are
finalizing the requirements as proposed with minor clarifications of
the rule references. However, as with wastewater systems, we note that
the fenceline monitoring program will ensure that the owner or operator
is effectively managing fugitive emissions sources and should detect
landings, overfills, and leaking vents.
For equipment leaks, we identified specific developments in
practices, processes and control technologies that included requiring
repair of leaking components at lower leak definitions, requiring
monitoring of connectors, and allowing the use of the optical imaging
camera as an alternative method of monitoring for leaks. We proposed to
establish an alternative method for refineries to meet LDAR
requirements in Refinery MACT 1. This alternative would allow
refineries to monitor for leaks via optical gas imaging in place of EPA
Method 21, using monitoring requirements to be specified in a not yet
proposed appendix K to 40 CFR part 60. However, the development of
appendix K is taking longer than anticipated. Therefore, we are not
finalizing this alternative monitoring method in Refinery MACT 1.
We received comments suggesting that additional requirements be
imposed to further reduce emissions from leaking equipment components,
such as requiring ``leakless'' equipment, reducing the leak threshold,
and eliminating delay of repair provisions. As provided in the
``Response to Comments'' document, we do not agree that these
additional requirements are cost-effective. Based on the rationale
provided in the preamble to the proposed rule and our consideration of
public comments, we conclude that it is not necessary to revise the
Refinery MACT 1 requirements for equipment leaks. Again, however, the
fenceline monitoring program is intended to ensure that large leaks
from fugitive emissions sources, including equipment leaks, are more
quickly identified and repaired, thereby helping to reduce emissions
from leaking equipment components.
For marine vessel loading, we identified control of marine vessel
loading operations with HAP emissions of less than 10/25 tpy and the
use of lean oil absorption systems as developments that we considered
in the technology review. We proposed to amend 40 CFR part 63, subpart
Y to require small marine vessel loading operations (i.e., operations
with HAP emissions less than 10/25 tpy) and offshore marine vessel
loading operations to use submerged filling based on the cargo filling
line requirements in 46 CFR 153.282. We received comments that other
options considered during the technology review of the standard were
cost-effective for small marine vessel loading operations and should be
required. As provided in the ``Response to Comments,'' we continue to
believe those other controls are not cost-effective because of the high
costs of controls for limited additional organic HAP emission
reduction. Therefore, we are finalizing these amendments as proposed.
Finally, we proposed that it was necessary to revise the MACT to
require fenceline monitoring as a means to manage fugitive emissions
from the entire petroleum refinery, which includes sources such as
wastewater collection and treatment operations, equipment leaks and
storage vessels. We received numerous comments regarding the proposed
requirement to conduct fenceline monitoring, many of which we address
above and the remainder of which we respond to in the ``Response to
Comments'' document. After considering comments, we maintain that the
proposed work practice standard is authorized under section 112 of the
CAA and will improve fugitive management at the refinery. Therefore, we
are finalizing the key components of fenceline monitoring work practice
as proposed. These requirements include the use of passive diffusive
tube samplers (although we are providing a mechanism to request
approval for alternative monitoring systems provided certain criteria
are met), the 9 [mu]g/m3 on a rolling annual average basis
action level, and the need to perform corrective action to comply with
the action level.
Based on public comments received, we are making numerous revisions
to clarify the fenceline monitor siting requirements. This includes
provisions to allow siting of monitors within the property boundary as
long as all emissions sources at the refinery are included within the
monitoring perimeter. We are also clarifying that we do not consider
public roads or public waterways that bisect a refinery to be property
boundaries, and owners or operators do not need to place monitors along
the internal public right-of-ways. We are also providing provisions to
allow fixed placement of monitors at 500 feet intervals (with a minimum
of 3 monitors) for subareas or segregated areas. If an emissions source
is near the monitoring perimeter, an additional monitor siting
requirement would still apply. The 500 feet provision is provided to
reduce burden for facilities with irregular shapes or noncontiguous
property areas that we did not fully consider at proposal.
We also received comments on the compliance time and reporting
requirements associated with the fenceline monitoring provisions. Upon
consideration of public comments, we have revised the compliance period
to 2 years after the effective date of the final rule. Thus, beginning
no later than 2 years after the effective date of the rule, the source
must have a fenceline monitoring system that is collecting samples such
that the first rolling annual average [Delta]C value would be completed
no later than 3 years after the effective date of the final rule.
Facilities will have 45 days after the completion of the first year of
sampling, as proposed, to submit the initial data set. We are reducing
the proposed compliance period from 3 years to 2 years because the
passive diffusive tube monitors are easy to deploy and pilot study
demonstrations indicate that significant time is not needed to deploy
the monitors. However, the reduced compliance period still provides
time to resolve site-specific monitor placement issues and to provide
time to develop and implement a site-specific monitoring plan, if
needed. We are increasing the fenceline monitoring reporting frequency
(after the first year of data collection) from semiannually to
quarterly to provide more timely dissemination of the data collected
via this monitoring program.
b. Refinery MACT 2
We proposed to revise Refinery MACT 2 to incorporate the
developments in monitoring practices and control technologies reflected
in the Refinery NSPS subpart Ja limits and monitoring provisions (73 FR
35838, June 24, 2008). We are finalizing most of these provisions as
proposed. Specifically, we are incorporating the
[[Page 75206]]
Refinery NSPS subpart Ja PM limit for new FCCU sources. We are also
finalizing compliance options for FCCU that are not subject to Refinery
NSPS subpart J or Ja. These options would allow such sources to elect
to comply with the Refinery NSPS subpart Ja monitoring provisions to
demonstrate compliance with the emissions PM limit. We are revising the
averaging period for the control device operating limits or site-
specific opacity limits to be on a 3-hour average basis in order to
more directly link the operating limit to the duration of the
performance test runs, on which they are based, as proposed. We are
incorporating additional control device-specific monitoring
alternatives for various control devices on FCCU, including BLD
monitoring as an option to COMS for owners or operators of FCCU using
fabric filter-type control systems and total power and secondary
current operating limits for owners or operators of ESPs. We are adding
an additional requirement to perform daily checks of the air or water
pressure to atomizing spray nozzles for owners or operators of FCCU wet
gas scrubbers not subject to the pressure drop operating limit, as
proposed. Finally, we finalizing requirements to conduct a performance
test at least once every 5 years for all FCCU, as proposed. These
requirements are being finalized to ensure that control devices are
continuously operated in a manner similar to the operating conditions
of the performance test and to ensure that the emissions limits, which
are assessed based on the results of three 1-hour test runs, are
achieved at all times.
We also proposed to eliminate the Refinery NSPS subpart J
compliance option that allows refineries to meet the 30-percent opacity
emissions limit requirement and revise the MACT to include control
device operating limits or site-specific opacity limits identical to
those required in Refinery NSPS subpart Ja. We received numerous
comments, particularly from owners or operators of FCCU that employ
tertiary cyclones to control FCCU PM emissions. According to the
commenters, opacity is not a direct indicator of PM emissions because
finer particles will increase opacity readings without a corresponding
mass increase in PM emissions. Additionally, the commenters stated that
the site-specific opacity limit generally leads to a site-specific
operating limit of 10-percent opacity, which is too stringent and does
not adequately account for variability between PM emissions and opacity
readings. According to the commenters, FCCU with tertiary cyclones
would need to be retrofitted with expensive and costly controls in
order to meet the 10-percent opacity limit, even though they are
meeting the 1 lb/1000 lbs coke burn PM emissions limit. It was not our
intent to require units to retrofit their controls simply to meet the
site-specific opacity limit. However, the existing 30-percent opacity
limit in the subpart J compliance option is not adequate to ensure
compliance with the PM emissions limit at all times. After reviewing
the public comments and available data, we determined that, rather than
removing the subpart J compliance option altogether, it is sufficient
to add an opacity operating limit of 20-percent opacity determined on a
3-hour average basis to the existing subpart J compliance option and to
require units complying with this operating limit to conduct annual
performance tests (rather than one every 5 years) when the PM emissions
measured during the source test are greater than 0.80 lb PM/1,000 lbs
coke burn-off. These provisions improve assurance that these units are,
in fact, achieving the required PM emissions limitation without
requiring units to retrofit controls due to variability in the
correlation of PM emissions and opacity.
We did not propose to revise the organic HAP emissions limits for
FCCU to further address HCN emissions. We received numerous comments on
this issue. We continue to believe that complete combustion is the
appropriate control needed to control HCN emissions. Consequently, for
the purposes of Refinery MACT 2, we are not changing the MACT standards
to further reduce emissions of HCN. However, we understand that there
are uncertainties and high variability in HCN emissions measured from
FCCU. In order to address the need for more data to better characterize
HCN emissions levels, we are finalizing a requirement for refinery
owners or operators to conduct a performance test for HCN from all FCCU
(except those units that were tested previously using acceptable
methods as outlined in the 2011 Refinery ICR) during the first PM test
required as part of the on-going compliance requirements for FCCU metal
HAP emissions. These data will be useful to the EPA in understanding
HCN emissions from FCU and may help to inform future regulatory reviews
for this source category.
We proposed that there have been no developments in practices,
processes, and control technologies for CRU based on our technology
review and that therefore it is not necessary to revise these
standards. Based on the rationale provided in the preamble to the
proposed rule and our consideration of public comments, we are
finalizing our conclusion.
For SRU, we identified the Refinery NSPS subpart Ja allowance for
oxygen-enriched air as a development in practice and we proposed that
it was necessary to revise the MACT to allow SRU to comply with
Refinery subpart Ja as a means of complying with Refinery MACT 2. The
key issue identified by commenters was that Refinery NSPS subpart Ja
includes a flow monitoring alternative for determining the average
oxygen concentration in the enriched air stream and that this was not
included in the proposed amendments to Refinery MACT 2. This was an
oversight on our part. We are, based on the rationale provided in the
preamble to the proposed rule and our consideration of public comments,
finalizing the SRU revisions as proposed but with inclusion of the flow
monitoring alternative provisions that are in Refinery NSPS subpart Ja
for this source.
C. Refinery MACT Amendments Pursuant to CAA Section 112(d)(2) and
(d)(3)
1. What did we propose pursuant to CAA section 112(d)(2) and (d)(3) for
the Petroleum Refinery source categories?
We proposed the following revisions to the Refinery MACT 1 and 2
standards pursuant to CAA section 112(d)(2) and (3) \11\: (1) Adding
MACT standards for DCU decoking operations; (2) revising the CRU purge
vent pressure exemption; (3) adding operational requirements for flares
used as APCD in Refinery MACT 1 and 2; and (4) adding requirements and
clarifications for vent control bypasses in Refinery MACT 1.
---------------------------------------------------------------------------
\11\ The EPA has authority under CAA section 112(d)(2) and
(d)(3) to set MACT standards for previously unregulated emission
points. EPA also retains the discretion to revise a MACT standard
under the authority of section 112(d)(2) and (3), see Portland
Cement Ass'n v. EPA, 665 F.3d 177, 189 (D.C. Cir. 2011), such as
when it identifies an error in the original standard. See also
Medical Waste Institute v. EPA, 645 F. 3d at 426 (upholding EPA
action establishing MACT floors, based on post-compliance data, when
originally-established floors were improperly established).
---------------------------------------------------------------------------
For DCU, we proposed to require that prior to venting or draining,
each coke drum must be depressured to a closed blowdown system until
the coke drum vessel pressure is 2 psig or less. As proposed, the 2
psig limit would apply to each vessel opening/venting/draining event at
new or existing affected DCU facilities.
For the CRU, we proposed to require that any emissions during the
active
[[Page 75207]]
purging or depressuring of CRU vessels meet the applicable organic HAP
emission limitations in Tables 15 and 16 to subpart UUU regardless of
the vessel pressure.
For flares, we proposed to remove cross references to the General
Provisions requirements for flares used as control devices at 40 CFR
63.11(b) and to incorporate enhanced flare operational requirements
directly into the Refinery MACT rules. The proposed rule amendments
included:
A ban on flaring of halogenated vent streams.
A requirement to operate with continuously lit pilot
flames at all times and to equip the pilot system with an automated
device to relight the pilot if it is extinguished.
A requirement to operate with no visible emissions except
for periods not to exceed a total of 5 minutes during any 2 consecutive
hours and to monitor for visible emissions daily.
A requirement to operate with the flare tip velocity less
than 60-feet-per-second or the velocity limit calculated by an equation
provided in the proposed rule.
A requirement to meet one of three combustion zone gas
properties operating limits based on the net heating value, lower
flammability limit, or combustion concentration. Owners or operators
could elect to comply with any one of the three limits at any time. Two
separate sets of operating limits were proposed: One for gas streams
not meeting all three ``hydrogen-olefin interaction criteria''
specified in the rule and a more stringent set of limits for gas
streams meeting all three hydrogen-olefin interaction criteria. The
combustion zone net heating value considered steam assist rates but not
``perimeter air'' assist rates.
For air-assisted flares, a requirement to meet an
additional ``dilution parameter'' operating limit determined based on
the combustion zone net heating values above, the diameter of the flare
and the perimeter air assist rates.
The proposed amendments for flares also included detailed
monitoring requirements to determine these operating parameters either
through continuous parameter monitoring systems or grab sampling,
detailed calculation instructions for determining these parameters on a
15-minute block average, and detailed recordkeeping and reporting
requirements. We also proposed provisions to allow owners or operators
to request alternative emissions limitations that would apply in place
of the proposed operating limits.
We proposed to revise the definition of MPV to remove the current
exclusion for in situ sampling systems (onstream analyzers). We also
proposed to limit the exclusion for gaseous streams routed to a fuel
gas system to apply only to those systems for which any flares
receiving gas from the fuel gas system are in compliance with the
proposed flare monitoring and operating limits. We note that we also
proposed revisions related to monitoring of bypass lines, but these
revisions were proposed to address concerns related to SSM releases and
are described in further detail in section IV.D. of this preamble.
We proposed that emissions of HAP may not be discharged to the
atmosphere from PRD in organic HAP service to address concerns related
to SSM releases. To ensure compliance with this proposed amendment, we
proposed to require that sources monitor PRD using a system that is
capable of identifying and recording the time and duration of each
pressure release and of notifying operators that a pressure release has
occurred. This proposed requirement was addressed in section IV.A.4. of
the preamble for the proposal.
2. How did the revisions pursuant to CAA section 112(d)(2) and (3)
change since proposal?
We proposed identical standards for existing and new DCU decoking
operations, but we are finalizing standards for new and existing
sources that are not identical. We are finalizing provisions that will
require owners or operators of existing DCU sources to comply with a 2
psig limit averaged over 60 cycles (i.e., 60 venting events), rather
than meet the 2 psig limit on a per venting event basis, as proposed.
We are finalizing provisions that will require owners or operators of
new DCU sources to comply with a 2.0 psig limit on a per event, not-to-
exceed basis. We are adding one significant digit to the limit for new
DCU affected sources because our re-review of permit requirements
conducted in response to comments identified that the best performing
DCU source is required to comply with a 2.0 psig limit on a per event
basis. In response to comments regarding the proposed prohibition on
draining prior to achieving the pressure limit, we are finalizing
specific provisions for DCU with water overflow design and for double
quenching.
For flares, we are not finalizing the ban that we proposed on
halogenated vent streams and we are not finalizing the proposed
requirement to equip the flare pilot system with an automated device to
relight an extinguished pilot.
We are revising the MACT to include the proposed no visible
emissions limit and the flare tip velocity limit as direct emissions
limits only when the flare vent gas flow rate is below the smokeless
capacity of the flare. Under the revised standard, when the flare is
operating above the smokeless capacity, an exceedance of the no visible
emission limit and/or flare tip velocity limit is not a violation of
the standard but instead triggers a work practice standard. Flares
operate above the smokeless capacity only when there is an emergency
release event and thus the work practice standard is intended to
address emissions during such emergency release events. (See section
IV.D. of this preamble for more details regarding this work practice
standard). We are also adding provisions that would allow sources to
use video surveillance of the flare as an alternative to daily Method
22 visible emissions observations.
For flares, we are also simplifying the combustion zone gas
property operating limits by finalizing a requirement only for the net
heating value of the combustion zone gas. We are finalizing
requirements that flares meet a minimum operating limit of 270 BTU/scf
NHVcz on a 15-minute average, as proposed, and we are allowing refinery
owners or operators to use a corrected heat content of 1212 BTU/scf for
hydrogen to demonstrate compliance with this operating limit. We are
not finalizing separate combustion zone operating limits for gases
meeting the hydrogen-olefin interaction criteria that were proposed. We
are also not finalizing the alternative combustion zone operating
limits based on lower flammability limit or combustibles concentration.
We are finalizing ``dilution parameter'' requirements for air-
assisted flares, but we are providing a limit only for the net heating
value dilution parameter. Similar to the requirements we are finalizing
for the combustion zone parameters, we are finalizing requirements that
flares meet a minimum operating limit of 22 BTU/ft2
NHVdil on a 15-minute average, as proposed, and we are
allowing refinery owners or operators to use a corrected heat content
of 1,212 BTU/scf for hydrogen to demonstrate compliance with this
operating limit. We are not finalizing separate dilution parameter
operating limits for gases meeting the hydrogen-olefin interaction
criteria that were proposed. We are also not finalizing the alternative
dilution parameter operating limits based on lower flammability limit
or combustibles concentration.
[[Page 75208]]
We are providing an alternative to use initial sampling period and
process knowledge for flares in dedicated service as an alternative to
continuous or on-going grab sample requirements for determining waste
gas net heat content.
We are finalizing revisions to the definition of MPV, as proposed.
We are establishing work practice standards that apply to PRD
releases in place of the proposed prohibition on PRD releases to the
atmosphere. The work practice standards that we are finalizing for PRD
require refiners to establish proactive, preventative measures for each
PRD to identify and correct direct releases of HAP to the atmosphere as
a result of pressure release events. Over time, these proactive
measures will reduce the occurrence of releases and the magnitude of
releases when they occur, while avoiding the environmental disbenefits
of having additional flare capacity on standby to control these
unpredictable and infrequent events. Refinery owners or operators will
be required to perform a root cause analysis/corrective action
following such pressure release events. In addition, a second release
event in a 3-year period from the same PRD with the same root cause on
the same equipment is a deviation of the work practice standard. A
third release event in a 3-year period from the same PRD is a deviation
of the work practice standard regardless of the root cause. PRD release
events related to force majeure events are not considered in these hard
limits.
3. What key comments did we receive on the proposed revisions pursuant
to CAA section 112(d)(2) and (3) and what are our responses?
i. DCU
Comment: Several commenters argued that the EPA incorrectly set the
MACT floor emission limitation for DCU. Commenters noted that CAA
section 112(d)(3)(A) states that the MACT limit for existing sources
``shall not be less stringent, and may be more stringent than the
average emission limitation achieved by the best performing 12-percent
of the existing sources'' excluding those first achieving that level
within 18 months prior to proposal or 30 months prior to promulgation,
whichever is later. According to the commenters, the EPA failed to
follow this procedure in setting the 2 psig vent limit as a MACT floor
because the EPA incorrectly considered permit limits and other non-
performance based criteria instead of basing the MACT floor on the
actual performance of sources. Commenters stated that the EPA
improperly considered permit limits that should have been excluded from
consideration, as well as considering permit limits for closed
facilities instead of using more accurate data from operating DCUs at
sources that submitted actual emissions data. Specifically, commenters
stated that the DCU at the non-operational plant (Hovensa) should not
be included. One commenter noted that they operate one of the South
Coast DCU listed as subject to a 2 psig limit and asserted that it does
not currently meet that emission limitation. The commenter claimed that
significant capital investment would be required in order for the DCU
to comply with the 2 psig limit. According to one commenter, data for
six of the eight DCU they claim the EPA considered for the MACT floor
should not be counted in determining the limit that represents the
average emission limitation actually achieved 18 months prior to the
proposal.
Response: CAA section 112(d)(3)(A) states that the existing source
standard shall not be less stringent than the average emission
limitation achieved by the best performing 12-percent of the existing
sources (for which the Administrator has emissions information),
excluding those sources that have, within 18 months before the emission
standard is proposed or within 30 months before such standard is
promulgated, whichever is later, first achieved a level of emission
rate or emission reduction which complies, or would comply if the
source is not subject to such standard, with the lowest achievable
emission rate (as defined by section 171) applicable to the source
category and prevailing at the time, in the category or subcategory for
categories and subcategories with 30 or more sources. We consider a 2
psig emissions limitation to be equivalent to the lowest achievable
emission rate (LAER) emission limits. Thus, we agree with the commenter
that sources that first meet the 2 psig limit on or after December 30,
2012, should be excluded from the MACT floor analysis. We also agree
that under CAA section 112(d)(3)(A), the MACT floor analysis focuses on
those sources that are achieving the emission limit (i.e., the emission
limitation ``achieved by . . . ''). The EPA has previously determined
that the 6th-percentile unit is a reasonable estimate of the average
emission limitation achieved by the best performing 12-percent of
sources especially when averaging across units with and without control
requirements. As noted in our DCU MACT floor analysis memorandum
(Docket ID No. EPA-HQ-OAR-2010-0682-0203), the 6th-percentile is
represented by the fifth-best performing DCU. If we exclude the two
South Coast refineries and the two Marathon Garyville DCU because these
sources were not implementing the 2 psig permit limit prior to December
30, 2012, the fifth-best performing DCU would be represented by the Bay
Area refineries (4.6 psig). However, based on the 2011 Petroleum
Refinery ICR responses, 25 out of 75 (33-percent) DCU have a ``typical
coke drum pressure when first vented to the atmosphere'' of 2 psig or
less and 10 out of 75 (13-percent) DCU have a ``typical coke drum
pressure when first vented to the atmosphere'' of 1 psig or less. While
we acknowledge that these data represent ``typical'' operations and not
necessarily a never-to-be-exceeded emissions limitation, we conclude
that this information is sufficient for us to conclude that the average
emission limitation achieved by the best performing 12-percent of
sources is consistent with a 2 psig emissions limitation. This is
because facility owners or operators commonly target to operate at
approximately half the allowable emissions limit to ensure that they
can comply with the emissions limit at all times. Therefore, we
maintain that an average venting pressure of 2 psig is the MACT floor
level for decoking operation at existing sources based on the ICR
responses and considering the average performance expected.
Comment: Four commenters suggested that the 2 psig limit, if
finalized, should be based on a rolling 30-day average per DCU rather
than a never to be exceeded ``instantaneous'' standard. According to
the commenters, an instantaneous standard is unnecessary to address
HAPs with chronic health impacts and adds cost and compliance
challenges. According to the commenters, chronic health impacts are not
materially affected by short-term variability, but instead depend on
the average concentration of exposure over a 70-year lifetime;
therefore, there is no health based or environmental reason for
requiring an instantaneous limit. The commenters noted that there would
be additional capital costs to comply with a 2 psig not-to-be-exceeded
limit compared to a 30-day average 2 psig limit vent pressure. One
commenter specifically requested that the EPA also confirm that a
pressure of 2.4 psig is compliant with the 2 psig limit vent pressure.
Another commenter also requested clarification that the vent pressure
can be rounded to
[[Page 75209]]
one significant figure when determining compliance.
Response: For new sources, the MACT floor emission limit for DCU is
based on the best-performing source. Based on this and other comments
received, we again reviewed existing permit conditions. Based on this
review, we found that one of the permit requirements specified the
pressure limit as 2.0 psig for each coke drum venting event. Therefore,
we are finalizing the new source MACT floor as 2.0 psig on a per coke
drum venting event basis.
As discussed in response to the previous comment, we are basing the
MACT floor for existing source DCU on responses we received from the
2011 Petroleum Refinery ICR. Because the ICR requested the ``typical
coke drum pressure when first vented to the atmosphere,'' we do not
consider the information provided in ICR responses to reflect a
``never-to-be-exceeded'' limit. Therefore, we evaluated whether it is
reasonable to allow averaging, and if so, what averaging period should
be provided.
Health risks are not considered in establishing MACT requirements,
so we do not consider the argument that chronic effects are evaluated
over a 70-year period to be relevant to a determination of the MACT
floor. However, a primary consideration regarding averaging periods is
how the averaging period was considered in setting the floor and
whether the intended reductions will occur under a different averaging
period. According to the heat balance method for estimating DCU
emissions, DCU decoking operations emissions are directly proportional
to the average bed temperature. While the relationship is not exactly
linear, the average bed temperature is expected to be a function of the
venting pressure. Moreover, the shape of the pressure-temperature
correlation curve is such that the emissions at 6 psig are almost
exactly but not quite three times the emissions at 2 psig. Given the
expected linearity of the emissions with venting pressures, we are not
concerned with an occasional venting event above 2 psig because the
average emissions from a facility meeting an average 2 psig pressure
limit would be identical to the emissions achieved by a facility that
vented each time at 2 psig. That is, given the expected linearity in
the projected DCU emissions to the venting pressure, we conclude that
it is reasonable to allow averaging across events and that the precise
averaging period is not a critical concern.
Most industry commenters requested a 30-day average. However,
different facilities have different numbers of DCU, different numbers
of drums per DCU and different cycle times. Consequently, basing the
averaging period across a given time period would result in
significantly different number of venting events included in a 30-day
average for different facilities and generally provide more flexibility
to larger refineries and less flexibility to smaller refineries. Based
on the ICR responses, almost half of all DCU operate with two drums and
about 90-percent of DCU have two to four coke drums; however, a few DCU
have six or even eight drums. Also, based on the ICR responses, the
average complete coke drum cycle time is 32 hours, but can be as short
as 18 hours and as long as 48 hours. Reviewing the ICR responses, we
found that a 30-day average would include 30 events for some facilities
and more than 250 events at other facilities.
Since the existing source MACT standards apply ``in combination''
to ``all releases associated with decoking operations'' at a given
facility, we determined that it was reasonable to consider an averaging
period that applies to the number of venting events from all coke drums
at the facility rather than to all coke drums for a specific DCU for a
specified period of time. This provides a more consistent basis for the
averaging period and allows the same operational flexibility for small
refineries as large refineries. Based on the ICR responses, the median
(typical) DCU has 60 venting events in a 30-day period. Providing an
averaging period of 60 venting events provides a more consistent
averaging basis for all facilities, regardless of the number of DCU at
the facility and the number of drums and cycle times for different DCU.
Additionally, it eliminates issues with respect to how to handle
operating days versus non-operating days, e.g., in the event of a turn-
around resulting in a limited number of venting events in a 30-calendar
day period. Therefore, we are establishing a 2 psig limit based on a
60-event average considering all coke drum venting events at an
existing source and we are finalizing a 2.0 psig limit on a per coke
drum venting event for DCU at new sources.
We have consistently maintained our policy to round to the last
digit provided in the emission limit, a pressure of 2.4 psig would
round to 2 psig and would be compliant with a requirement to depressure
each coke drum to a closed blowdown system until the coke drum vessel
pressure is 2 psig or less, but it would not be compliant with the
revised new source provision to depressure until the coke drum vessel
pressure is 2.0 psig or less. A coke drum pressure of 2.04, however,
would be compliant with the revised new source requirement pressure
limit of 2.0 psig.
ii. Refinery Flares
Comment: Several commenters suggested that the proposed flare
operating limits were too complex. The commenters recommended that the
EPA eliminate the dual flare combustion zone heat content limits
related to the proposed hydrogen-olefin interaction criteria and
instead finalize a single combustion zone net heating value of
approximately 200 BTU/scf, which would minimize the unnecessary burning
of supplemental gas but still ensure good combustion efficiency.
A few commenters suggested that the EPA based the proposed
combustion zone limits on an invalid data analysis, that the 1 minute
PFTIR data should not be used to establish combustion efficiency
correlations, and that the emission limits should be set so as to
provide an equal chance of false positives and negatives. A few
commenters suggested that the EPA should assign hydrogen a heating
value of 1,212 BTU/scf to more accurately reflect its flammability in a
NHV basis and that doing so is consistent with some recent flare
consent decrees and would help reduce natural gas supplementation for
facilities complying only with the NHVcz metric.
Several commenters suggested that neither scientific literature nor
the available flare test data support the EPA's claim of an adverse
hydrogen-olefin interaction on combustion efficiency and that the EPA
should not finalize the more restrictive combustion zone operating
limits for all flare types. These commenters suggested that the EPA did
not provide any evidence the assumed hydrogen-olefin effect actually
exists; that statistical analysis demonstrates the EPA developed their
limit based on random differences in data; that the PFTIR data analysis
method of using the individual minute-by-minute data instead of the
test average data is flawed and leads to invalid conclusions; and that
proper analysis of the data demonstrates the more stringent operating
limits for hydrogen-olefin conditions cannot be supported.
Some commenters suggested that there is evidence to support more
stringent flare combustion zone limits for a narrowly defined high
concentration propylene-only condition as outlined in some of the
recent flare
[[Page 75210]]
consent decrees but that the flare test data do not support more
stringent operating limits for the proposed hydrogen-olefins criteria
by the EPA. Additionally, one commenter suggested that if the EPA
decides to proceed with the more restrictive combustion zone limits for
the hydrogen-olefins interaction cases then the final rule should not
expand beyond an interaction between hydrogen and propylene.
Several commenters suggested that the proposed 15-minute feed
forward averaging time for flares (e.g., combustion zone parameters,
air-assist dilution parameters and associated flow rates) is arbitrary,
unrealistic and unworkable and that the feed forward compliance
determination should not be finalized and, if it is finalized, the
averaging time should be extended to 1-hour, 3-hour, or 24-hour. To
support these suggested averaging periods, commenters claimed that
typical standards for combustion devices are averaged over these
suggested timeframes, noting as an example, recent refinery flare
consent decrees that contain a 3-hour average. The commenters also
asserted that both a GC and calorimeter will be needed to obtain data
rapidly enough to try and maintain a 15-minute average; that the feed
forward approach requires calculation artifices to attempt to correct
for the fact that compliance cannot be determined until the averaging
period is over; and that a longer averaging time is needed for
instrument and control response time.
Response: In addressing these comments, we further analyzed the
flare emissions test data. First, to address concerns that the minute-
by-minute analysis produced flawed results, we re-compiled the data
into approximate ``15-minute averages'' to the extent practical based
on the duration of a given test run (e.g., a 10-minute run was used as
1 run and a 32-minute run was divided into 2 runs of 16 minutes each).
We do not find significant differences in the data or that different
conclusions would be drawn from the data based on this approach as
compared with the minute-by-minute analysis used for the proposed rule.
Next, we evaluated the 15-minute run data using the normal net
heating value for hydrogen of 274 Btu/scf, which is the value we used
in the analysis for the proposed rule and also evaluated the data using
the 1,212 Btu/scf, the value recommended by some commenters. The 1,212
Btu/scf value is based on a comparison between the lower flammability
limit and net heating value of hydrogen compared to light organic
compounds and has been used in several consent decrees to which the EPA
is a party. Based on our analysis, we determined that using a 1,212
Btu/scf value for hydrogen greatly improves the correlation between
combustion efficiency and the combustion zone net heating value over
the entire array of data. Using the net heating value of 1,212 Btu/scf
for hydrogen also greatly reduced the number of ``type 2 failures''
(instances when the combustion efficiency is high, but the gas does not
meet the NHVcz limit). One of the primary motivations for the proposed
approach to provide alternative limits based on lower flammability
limits and combustibles concentrations was to reduce these type 2
failures. Therefore, we proposed all three of these parameters (i.e.,
NHVcz, LFL and total combustibles) and allowed flare owners or
operators to comply with any of the parameter limits at any time. When
using the net heating value of 1,212 Btu/scf for hydrogen, the other
two alternatives no longer provide any improvement in the ability to
predict good flare performance. Consequently, we are simplifying the
operating limits to use only NHVcz.
Next, we re-evaluated whether to finalize the proposed dual
combustion zone operating limits for refinery flares that met certain
hydrogen-olefins interactions or to finalize a single combustion zone
net heating value limit. The newly re-compiled PFTIR run average flare
dataset suggests that higher operating limits may be appropriate for
some olefin-hydrogen mixtures. However, the dataset using 15-minute
test average runs is much smaller than the set using 1-minute runs and
thus creates a greater level of uncertainty. In addition, we cannot
definitively conclude that a dual combustion zone limit for refinery
flares meeting certain hydrogen-olefins interactions is appropriate
given these uncertainties. Thus, in order to minimize these
uncertainties and streamline the compliance requirements, we used all
of the 15-minute test run average data together as a single dataset in
an effort to determine an appropriate, singular combustion zone net
heating value operational limit.
Finally, we conducted a Monte Carlo analysis to help assess the
impacts of extending the averaging time on the test average flare
dataset of 15-minute runs to 1-hour or 3-hour averaging time
alternatives. While we consider it reasonable to provide a longer
averaging time for logistical reasons, the Monte Carlo analysis
demonstrated, consistent with concerns described in our proposal, that
short periods of poor performance can dramatically limit the ability of
a flare to achieve the desired control efficiency. Consequently, we
find it necessary to finalize the proposed 15-minute averaging period
to ensure that the 98-percent control efficiency for flares is achieved
at all times. However, we understand that flare vent gas flow and
composition are variable. While a short averaging time is needed to
ensure adequate control given this variability, we also understand the
complications that this variability places on flare process control in
efforts to meet the NHVcz limit. Therefore, we are clarifying that the
270 Btu/scf NHVcz value is an operational limit that must be calculated
according to the requirements in this rule. We also clarify that
compliance with this operational limit must be evaluated using the
equations and calculation methods provided in the rule. We proposed a
feed forward calculation method to allow refinery owners or operators a
means by which to adjust steam (or air) and, if necessary, supplemental
natural gas flow, in order to meet the limit. In other words, ``feed
forward'' refers to the fact that the rule requires the refinery owners
or operators to use the net heating value of the vent gas (NHVvg) going
into the flare in one 15-minute period to adjust the assist media
(i.e., steam or air) and/or the supplemental gas in the next 15-minute
period, as necessary for the equation in the rule to calculate an NHVcz
limit of 270 BTU/scf or greater. We recognize that when a subsequent
measurement value is determined, the instantaneous NHVcz based on that
compositional analysis and the flow rates that exist at the time may
not be above 270 Btu/scf. We clarify that this is not a deviation of
the operating limit. Rather, the owner or operator is only required to
make operational adjustments based on that information to achieve, at a
minimum, the net heating value limit for the subsequent 15-minute block
average. Failure to make adjustments to assist media or supplemental
natural gas using the equation provided for calculating an NHVcz limit
of 270 BTU/scf, using the NHVvg from the previous period, would be a
deviation of the operating limit.
Alternatively, if the owner or operator is able to directly measure
the NHVvg on a more frequent basis, such as with a calorimeter (and
optional hydrogen analyzer), the process control system is able to
adjust more quickly, and the owner or operator can make adjustments to
assist media or supplemental natural gas more quickly. In this manner,
the owner or operator is not limited by
[[Page 75211]]
relying on NHVvg data that may not represent the current conditions.
Therefore, the owner or operator may opt to use the NHVvg from the same
period to comply with the operating limit.
Based on the results of all of our analyses, the EPA is finalizing
a single minimum NHVcz operating limit for flares subject to the
Petroleum Refinery MACT standards of 270 BTU/scf during any 15-minute
period. The agency believes, given the results from the various data
analyses conducted, that this operating limit is appropriate,
reasonable and will ensure that refinery flares meet 98-percent
destruction efficiency at all times when operated in concert with the
other suite of requirements refinery flares need to achieve (e.g.,
flare tip velocity requirements, visible emissions requirements, and
continuously lit pilot flame requirements). For more detail regarding
our data re-analysis, please see the memorandum titled ``Flare Control
Option Impacts for Final Refinery Sector Rule'' in Docket ID No. EPA-
HQ-OAR-2010-0682.
Comment: Numerous commenters objected to the proposed requirements
to have the velocity and visible emissions limits apply at all times
for flares. Commenters suggested that flares are not designed to meet
the visible emissions and flare tip velocity requirements when being
operated beyond their smokeless capacity and suggested several
alternative approaches: remove the visible emissions and flare tip
velocity requirements from the rule altogether; exempt flares from
these requirements during emergencies; or add a requirement to maintain
a visible flame present at all times or include a work practice
standard in the rule when flares are operated beyond their smokeless
capacity at full hydraulic load. The commenters identified full
hydraulic load as the maximum flow the flare can receive based on the
piping diameter of the flare header and operating pressure of processes
connected to the flare header system. They also specified that full
hydraulic load would only occur if all sources connected to the flare
header vented at the same time, which might result from an emergency
shutdown due to a plant-wide power failure. According to commenters,
flares are typically designed to operate in a smokeless manner at 20 to
30-percent of full hydraulic load. Thus, they claimed, flares have two
different design capacities: A ``smokeless capacity'' to handle normal
operations and typical process variations and a ``hydraulic load
capacity'' to handle very large volumes of gases discharged to the
flare as a result of an emergency shutdown. According to commenters,
this is inherent in all flare designs and it has not previously been an
issue because the flare operating limits did not apply during
malfunction events. However, if flares are required to operate in a
smokeless capacity during emergency releases, the commenters claimed
that refineries would have to quadruple the number of flares at each
refinery to control an event that may occur once every 2 to 5 years.
To support their suggestions, commenters pointed out that flaring
during emergencies is the optimum way of handling very large releases
and that the flare test data clearly demonstrate that visible emissions
and/or high flare tip velocity do not suggest poor destruction
efficiency during such events. The commenters also argued that
operators should not have conflicting safety and environmental
considerations to deal with during these times. The commenters stated
that refiners are still subject to a civil suit even if the EPA uses
its enforcement discretion where such a release would violate the limit
and in order to avoid such liability, many new flares would have to be
built. Commenters estimated that 500 new large flare systems at a
capital cost in excess of $10-20 billion would need to be built because
of the amount of smokeless design capacity that would be needed and
that this significant investment would take the industry at least a
decade to install.
Response: At the time of the proposed rule, we did not have any
information indicating that flares were commonly operated during
emergency releases at exit velocities greater than 400 ft/sec (which is
270 miles per hour (mph)). Similarly, we did not have information to
indicate that flares were commonly designed to have a smokeless
capacity that is only 20 to 30-percent of their ``hydraulic load
capacity.'' While we are uncertain that refineries actually would
install additional flares to the degree the commenters claim, based on
the possibility that there may be an event every 2 to 5 years that
would result in a deviation of the smokeless limit, we also recognize
that it would be environmentally detrimental to operate hundreds of
flares on hot standby in an effort to never have any releases to a
flare that exceed the smokeless capacity of that flare. This is because
operating hundreds of new flares to prevent smoking during these rare
events will generate more ongoing emissions from idling flares than the
no visible emissions limit might prevent during one of these events.
Therefore, we considered alternative operating limits or alternative
standards that could apply during these emergency release events.
As an alternative to the proposed requirement that flares meet the
visible emissions and velocity limits at all times, we considered a
work practice standard for the limited times when the flow to the flare
exceeds the smokeless capacity of the flare. Owners or operators of
flares would establish the smokeless capacity of the flare based on
design specification of the flare. Below this smokeless capacity, the
velocity and visible emissions standards would apply as proposed. Above
the smokeless capacity, flares would be required to perform root cause
analysis and take corrective action to prevent the recurrence of a
similarly caused event. Multiple events from the same flare in a given
time period would be a deviation of the work practice standard. Force
majeure events would not be included in the event count for this
requirement.
Based on industry claims that there is a hydraulic load flaring
event, on average, every 4.4 years, we assumed the best performers
would have no more than one event every 6 years, or a probability of
16.7-percent of having an event in any given year. We found that, over
a long period of time such as 20 years, half of these best performers
would have 2 events in a 3 year period, which would still result in
over half the ``best performing'' flares having a deviation of the work
practice standard if it was limited to 2 events in 3 years. Conversely,
only 6 percent would have 3 events in 3 years over this same time
horizon. Based on this analysis, 3 events in 3 years would appear to be
``achievable'' for the average of the best performing flares.
Pursuant to CAA section 112(d)(2) and (3), we are finalizing a work
practice standard for flares that is based on the best practices of the
industry, and considers the rare hydraulic load events that inevitably
occur at even the best performing facilities.
The best performing facilities have flare management plans that
include measures to minimize flaring during events that may cause a
significant release of material to a flare. Therefore, we are requiring
owners or operators of affected flares to develop a flare management
plan specifically to identify procedures that will be followed to limit
discharges to the flare as a result of process upsets or malfunctions
that cause the flare to exceed its smokeless capacity. We are
specifically requiring refinery owners or operators to implement
appropriate prevention measures applicable to these
[[Page 75212]]
emergency flaring events (similar to the prevention measures we are
requiring in this final rule to minimize the likelihood of a PRD
release). Refiners will be required to develop a flare minimization
plan that describes these proactive measures and reports smokeless
capacity. Refiners will need to conduct a specific root cause analysis
and take corrective action for any flare event above smokeless design
capacity that also exceeds the velocity and/or visible emissions limit.
If the root cause analysis indicates that the exceedance is caused by
operator error or poor maintenance, the exceedance is a deviation from
the work practice standard. A second event within a rolling 3-year
period from the same root cause on the same equipment is a deviation
from the standard. Events caused by force majeure, which is defined in
this subpart, would be excluded from a determination of whether there
has been a second event. Finally, and again excluding force majeure
events, a third opacity or velocity limit exceedance occurring from the
same flare in a rolling 3-year period is a deviation of the work
practice standard, regardless of the cause.
Comment: Several commenters suggested that the EPA should revise
the combustion efficiency requirements to apply only to steam-assisted
flares used as Refinery MACT control devices during periods of time
that the flares are controlling Refinery MACT regulated streams. One
commenter suggested that the EPA misused the TCEQ data in proposing the
NHVcz metric and that the proposed limits are overly
conservative. The commenter requested that the EPA work with
stakeholders to conduct additional testing to determine what, if any,
operating parameters are appropriate and necessary to achieve an
adequate destruction efficiency for non-steam-assisted flares.
Response: We disagree with the commenters that the combustion
efficiency requirements should apply only to steam-assisted flares. The
available data (for runs where steam assist is turned off) as well as
the available combustion theories suggest that the combustion zone net
heating value minimum limit, which is the vent gas net heating value
for unassisted or perimeter air-assisted flares, is necessary to ensure
proper flare performance. While we agree that additional data on air-
assisted flares would allow for a more robust analysis, the data we do
have strongly indicate that air-assisted flares can be over-assisted
and that the combustion efficiency of air-assisted flares that are
over-assisted is below 98-percent control efficiency.
Comment: A few commenters suggested that the proposed flare
regulations should not apply to part 63, subpart R (gasoline loading)
and subpart Y (marine vessel loading) facilities, and to part 61,
subpart FF (benzene waste) facilities. The commenters recommended that
flares associated with gasoline loading, marine vessel loading and
wastewater treatment emissions need to comply only with the General
Provisions for flares. Some of these commenters argued that these
sources are more consistent in flow and composition than other refinery
sources, so the new requirements are not necessary to ensure good
combustion for these ``dedicated'' flares. Some commenters suggested
that operators of flares with consistent flow and composition be
allowed to use process knowledge or engineering judgment rather than be
required to install continuous monitors or be subject to ongoing grab
sampling requirements.
Some commenters noted that the required control efficiency for some
refinery emissions sources subject to subpart CC sources is 95-percent.
One commenter also requested that the EPA provide overlap provisions so
flares used to control sources from different MACT sources would not
have duplicative requirements.
Response: The regulatory revisions that we are finalizing apply to
petroleum refinery sources subject to part 63, subparts CC and UUU.
Gasoline loading, marine vessel loading and wastewater treatment
operations that are part of the refinery affected source as defined at
40 CFR 63.640 are subject to subpart CC. Gasoline loading, marine
vessel loading and wastewater treatment operations located at non-
refinery source categories are not subject to part 63, subpart CC and,
thus, would not be subject to the revisions to subpart CC being
finalized in this action. To the extent that the commenters are
requesting that the EPA establish flare requirements that would apply
to flares that are not part of the refinery affected source, that
request is beyond the scope of this rulemaking, which only addresses
revisions to Refinery MACT 1 and 2. When we issue rules addressing
requirements for other sources with flares, we will consider issues
similar to those we considered in this action and determine at that
time whether revisions to those other flare requirements are necessary.
The commenters note that some subpart CC emissions sources have
only a control efficiency requirement of 95-percent. While this may be
true, where the owner or operator chooses to control these sources
through the use of a flare, operation of that flare was subject to
operational requirements in the General Provisions at 40 CFR 63.11 and
the best performing flares were achieving 98-percent control at the
time the General Provisions were promulgated. At the time the General
Provisions were promulgated, we received no comments that the EPA
should set different operational limits for flares that are controlling
emissions from sources where the standard may vary by level of control
efficiency and we see no basis to do so now. The purpose of the
revisions to the flare operating requirements is to ensure that flares
are operating consistent with the MACT floor requirements for any and
all sources that may use flares as a control device (79 FR 36905, June
30, 2014). As the MACT floor control requirements of certain refinery
sources that allow the use of a flare as a control device is 98-
percent, we established operational limits to ensure flares used as
control devices meet this MACT requirement.
To the extent that the commenters are requesting that the EPA
establish an alternative monitoring approach for flares in dedicated
service that have consistent composition and flow, we agree that these
types of flares, which have limited flare vent gas streams, do not need
to have the same type of on-going monitoring requirements as those with
more variable waste streams. Thus, we are establishing an option that
refinery owners or operators can use to demonstrate compliance with the
operating requirements for flares that are in dedicated service to a
specific emission source, such as a wastewater treatment operation.
Refinery owners or operators will need to submit an application for the
use of this alternative. The application must include a description of
the system, characterization of the vent gases that could be routed to
the flare based on a minimum of 7 grab samples (14 daily grab samples
for continuously operated flares) and specification of the net heating
value that will be used for all flaring events (based on the minimum
net heating value of the grab samples). We are also allowing
engineering estimates to characterize the amount of gas flared and the
amount of assist gas introduced into the system. For example, the use
of fan curves to estimate air assist rates is acceptable. Flare owners
or operators would use the net heating value determined from the
initial sampling phase and measured or estimated flare vent gas and
assist gas
[[Page 75213]]
flow rates, if applicable, to demonstrate compliance with the
standards.
Comment: A few commenters suggested that the EPA's proposed work
practice and monitoring standards for flares are CAA section 112(d)
``developments'' required by law and supported by the evidence, and
reflect best practices at many refineries today. One commenter
suggested that the EPA must allow companies with consent decrees to
meet their consent decree requirements as an alternative compliance
approach and in lieu of the proposed requirements.
Response: We proposed the enhanced monitoring requirements and
operating limits under authority of CAA sections 112(d)(2) and (d)(3)
to ensure that flares used to control regulated Refinery MACT 1 or 2
gas streams are meeting the prescribed control efficiencies established
at the time the MACT standard was promulgated. And, we continue to
believe that these revisions are appropriate under CAA sections
112(d)(2) and (d)(3). The commenter has not suggested, and we do not
believe, that the revisions promulgated would differ in substance if
they were instead promulgated under CAA section 112(d)(6).
In general, we expect that the NHVcz monitoring
requirements that we are finalizing for flares will be consistent with
the requirements in various consent decrees. However, we have not
conducted a rigorous evaluation of equivalency between various
requirements and therefore we are not at this time providing an
allowance for flare owners or operators to comply with the
NHVcz operating limits and any provisions for necessary
monitoring needed in the consent decree in lieu of the NHVcz
limits and monitoring requirements established in this rule. In the
event that an owner or operator wishes to continue complying only with
the requirements of a consent decree, the rule contains provisions by
which owner or operator can seek approval for alternative limits that
are at least equivalent to the performance achieved from complying with
the operating limits included in the final rule.
iii. Pressure Relief Devices
Comment: Several commenters suggested that the EPA develop a work
practice approach for atmospheric PRD rather than a prohibition on
releases. One commenter recommended that the EPA establish a work
practice standard for atmospheric PRDs that requires refiners to
implement a base level of preventative measures including: Basic
process controls, instrumented alarms, documented and verified routine
inspection and maintenance programs, safety-instrumented systems,
disposal systems, provide redundant equipment, increase vessel design
pressure and systems that reduce fire exposure on equipment.
Additionally, the commenter recommended that the EPA require refiners
to perform root cause analysis and implement corrective action in the
event of a release. The commenter stated these requirements would be
similar to the root cause analysis/corrective action requirements
recently promulgated for flares under NSPS subpart Ja and provided
specific regulatory language for a proposed work practice approach.
(See section 2.4.1.8 in Docket item EPA-HQ-OAR-2010-0682-0583.) One
commenter requested that the EPA allow a process for companies to
submit an application for case-by-case limits to be approved by the
agency, either the EPA or a delegated state similar to the alternate
NOX limits for process heaters provided in NSPS subpart Ja.
This commenter recommended that the EPA establish reasonable work
practice standards, specifically suggesting that the EPA develop work
practice standards consistent with API 521. The commenter stated that
the EPA should provide an implementation period for compliance that
goes beyond the timeframe provided under CAA section 112(d). The
commenter added that the EPA should adopt specified changes to the
definition of an atmospheric pressure relief safety valve and provided
suggested regulatory language for a proposed work practice standard for
PRDs in EPA-HQ-OAR-2010-0682-0549.
Another commenter stated that the EPA should require, as the Bay
Area Air Quality Management District (BAAQMD) does, that any refinery
that has a reportable PRD event must take certain steps to prevent such
releases in the future (BAAQMD Rule 8-28-304). In particular, such a
refinery must create a Process Hazard Analysis, meet the Prevention
Measures Procedures specified in section 8-28-405, and conduct a
failure analysis of the incident, to prevent recurrence of similar
incidents (Id. Reg. section 8-28-304.1). If a second release occurs,
then, within one year, the facility must vent its PRDs to a vapor
recovery or disposal system that meets certain requirements (Id. Reg.
section 8-28-304.2). The commenter asserted that the EPA's prohibition
on releases to the atmosphere from PRD will ensure that refineries take
the necessary steps to prevent such releases, or install control
devices so that any releases from PRDs that must occur are vented
through a control device to reduce the amount of toxic air pollution
they emit. At a minimum, the commenter stated, the EPA must prohibit
these uncontrolled emissions and require monitoring and reporting to
assure compliance and ensure that the emission standards apply at all
times, as required by the Act. The commenter argued that the EPA must
also, however, consider requiring the additional developments that have
been put into place in the BAAQMD and also require control devices to
be used for all PRD, as some local air districts require. In addition,
the commenter supported the EPA's monitoring and reporting requirements
for PRD releases and the proposed electronic reporting requirements,
which the EPA recognized are needed to assure compliance and assist
with future rulemakings and as that provision requires, the EPA also
must make all information reported publicly available online promptly
and in an accessible and understandable format.
Response: We agree that, under the proposal, refineries would
consider installing add-on controls to comply with the prohibition on
atmospheric releases from PRDs. In addition, they would consider
venting these control devices to existing control devices, including
flares. However, it may not be feasible to vent some or all of the PRDs
to existing flares if the flares are near their hydraulic load capacity
based on the processes already connected to the flares. Flares have
negative secondary impacts when operated at idle conditions for the
vast majority of time, which could be the case if they were installed
solely to address PRD releases. These secondary impacts result from
GHG, CO and NOX emissions. Some PRDs may vent materials that
are not compatible with flare control and would need to be vented to
other controls.
To estimate the impact of the proposed prohibition on venting PRDs
to the atmosphere, we estimated that at least one new flare per
facility would be required to handle releases from PRDs, based on the
number of atmospheric PRDs reported at refineries; that 60-percent of
the PRDs could be piped to existing controls at minimal costs and the
other 40-percent would have to be piped to new flares; and that, on
average, each new flare would service 40 PRDs. Based on these
assumptions, 151 new flares would be needed or approximately one new
flare per refinery. At a capital cost of $2 million for each new flare,
which would not include long pipe runs, if needed, to PRD that are
dispersed across the plant, we estimate that the capital cost of the
[[Page 75214]]
prohibition on venting to the atmosphere would exceed $300 million.
Considering the fuel needed (approximately 50,000 scf/day per flare)
and a natural gas price of $4.50 per 1,000 scf, we estimate the annual
operating cost for these new flares to be $12 million.
PRDs are unique in that they are designed for the purpose of
releasing or ``popping'' as a safety measure to address pressure build-
up in various systems--pipes, tanks, reactors--at a facility. These
pressure build-ups are typically a sign of a malfunction of the
underlying equipment. While it would be difficult to regulate most
malfunction events because they are unpredictable and can vary widely,
in the case of PRDs, they are equipment installed specifically to
release during malfunctions and as such, we have information on PRDs in
our 2011 Refinery ICR and through the SCAAMD and BAAQ rules to
establish standards for them. After reviewing these comments, we thus
examined whether it would be feasible to regulate these devices under
CAA section 112(d)(2) and (3).
After reviewing the comments, we agree with the commenters who
suggest that the BAAQMD rule, as well as a similar South Coast Air
Quality Management District (SCAQMD) rule that address PRD releases
(SCAQMD Rule 1173), provide work practice standards that reflect the
level of control that applies to the best performers. Consequently, we
developed a work practice standard for PRD based on a detailed MACT
analysis considering the requirements in these rules. Our rationale for
the selected MACT requirements is provided in section IV.C.4 of this
preamble. The work practice standards that we are finalizing for PRDs
require refiners to establish proactive measures for each affected PRD
to prevent direct release of HAP to the atmosphere as a result of
pressure release events. In the event of an atmospheric release, we are
requiring refinery owners or operators to conduct root cause analysis
to determine the cause of a PRD release event. If the root cause was
due to operator error or negligence, then the release would be a
deviation of the standard. For any other release (not including those
caused by force majeure events), the owner or operator would have to
implement corrective action. A second release due to the same root
cause for the same equipment in a 3-year period would be a deviation of
the work practice standard. Finally, a third release in a 3-year period
would be a deviation of the work practice standard, regardless of the
root cause. Force majeure events would not count in determining whether
there has been a second or third event.
With respect to defining ``atmospheric pressure relief safety
valve'' as suggested by the commenter, we note that the June 30, 2014,
proposed amendments in 40 CFR 63.648(j) used the term ``relief valve''
because this was a defined term in Refinery MACT 1. However, the
proposed amendments included clauses such as ``if the relief valve does
not consist of or include a rupture disk.'' Thus, we specifically
intended to apply the pressure relief management requirements broadly
to ``pressure relief devices'' and not just ``valves.'' To clarify
this, we have revised the regulatory language to use the term
``pressure relief device'' rather than ``relief valve'' to clearly
include rupture disks or similar types of equipment that may be used
for pressure relief.
4. What is the rationale for our final approach and final decisions for
the revisions pursuant to CAA section 112(d)(2) and (3)?
We revised the MACT floor determination for DCU sources. CAA
section 112(d)(3)(A) requires the MACT floor for existing sources to
exclude ``. . . those sources that have, within 18 months before the
emission standard is proposed or within 30 months before such standard
is promulgated, whichever is later, first achieved a level of emission
rate or emission reduction which complies, or would comply if the
source is not subject to such standard, with the lowest achievable
emission rate (as defined by section 171) applicable to the source
category and prevailing at the time, in the category or subcategory for
categories and subcategories with 30 or more sources.'' Because we have
determined that a 2 psig emissions limitation is equivalent with a LAER
emission limit for DCU, we revised the MACT floor analysis in order to
exclude sources that first met the 2 psig limit on or after December
30, 2012. For existing sources, based on the revised MACT analysis, we
concluded that the MACT floor is still 2 psig. However, because the
information on which we relied was submitted in response to the 2011
Petroleum Refinery ICR which requested ``typical'' venting pressures
and because providing an allowance to average across venting periods
does not reduce the emissions reductions achieved, we are providing a
60-event averaging period for existing sources in response to public
comments received.
For new DCU sources, our revised analysis identified one DCU
subject to permit emission limitations of 2.0 psig pressure limit prior
to venting on a per event basis. Under CAA section 112(d)(3), the MACT
standard for new sources cannot be less stringent than the emission
control achieved in practice by the best-controlled similar source.
Thus, we are finalizing a limit of 2.0 for new DCU sources. We note
that as 2.0 psig limit is more stringent than a 2 psig limit because of
the rounding convention of rounding to the number of significant digits
for which the standard is expressed. For example, a 2.4 psig venting
pressure is compliant with a 2 psig limit, while it is not compliant
with a 2.0 psig limit.
We evaluated the costs of requiring existing sources to meet a 2.0
psig limit as a beyond-the-MACT-floor option. We determined the
incremental cost of going from a 2 psig limit with an allowance to
average over 60 events to a 2.0 psig limit on a per event basis was
approximately $70,000 per ton of HAP reduced considering VOC credits.
Based on this high incremental cost-effectiveness, we concluded that
the MACT floor requirement for existing DCU sources was MACT. As
discussed in detail in the proposal, we do not consider it technically
feasible to meet a 1 psig pressure limit (effectively a 1.4 psig limit)
on a not-to-be-exceeded basis. Thus, we rejected this beyond the floor
control option for both existing and new DCU sources. See the
memorandum titled ``Reanalysis of MACT for Delayed Coking Unit Decoking
Operations'' in Docket ID No. EPA-HQ-OAR-2010-0682 for additional
details regarding our re-analysis of MACT for DCU decoking operations.
In response to comments received on the prohibition of draining
prior to achieving the proposed pressure limit (see Section 7.2.1 in
the ``National Emission Standards for Hazardous Air Pollutants from
Petroleum Refineries--Background Information for Final Amendments:
Summary of Public Comments and Responses'' in Docket ID No. EPA-HQ-OAR-
2010-0682), we are providing specific provisions to allow for draining
under special conditions. The specific provision and our rationale for
providing them are provided below.
First, we learned that certain DCU are designed to completely fill
the drum with water and allow the water to overflow in the overhead
line and drain to a receiving tank in order to more effectively cool
the coke bed. Owners or operators of this DCU design were concerned
that the water overflow may be considered a drain and also stated that
overhead temperature rather than pressure would be a better indicator
of effective bed cooling. In reviewing this
[[Page 75215]]
type of DCU design, we find that this design has some unique advantages
to traditional DCU to effect better cooling of the coke drum, and
therefore we do not want to preclude its use. Based on saturated steam
properties, we determined that an overhead temperature of 220 [deg]F
would achieve equivalent or greater emissions reductions than a 2 psig
pressure limitation and an overhead temperature of 218 [deg]F would
achieve equivalent or greater emissions reductions than a 2.0 psig
pressure limitation. Therefore, we are including these temperature
limits as alternatives to the 2 or 2.0 psig pressure limitations for
existing and new DCU affected sources, respectively. With respect to
the overflow ``drain,'' we remain concerned with emissions from
draining superheated water. However, if submerged fill is used in the
atmospheric tank receiving the overflow water, the superheated water
will be cooled by the water within the tank and emissions that occur
during the conventional draining of water (from the flashing of
superheated water into steam) can be prevented. Therefore, we are
allowing the use of water overflow provided the overflow ``drain''
water is hard-piped to the receiving tank via a submerged fill pipe
(pipe below the existing liquid level) whenever the overflow water
exceeds 220 [deg]F.
Second, we received comments that, for conventional DCU (those not
designed to allow water overflow), there is a limit to the maximum
water level in the drum, which limits to some extent how much cooling
water can be added to the coke drum. In rare cases, the coke drum does
not cool sufficiently using the typical cooling steps. In this case,
the common industry practice is to partially drain the coke drum and
refill it with additional cooling water. This ``double-quench'' process
is needed for safety reasons to sufficiently cool the coke drum
contents prior to the decoking operations. Therefore, commenters
requested provisions to allow double-quenching of the coke drum. We
recognize the safety issues associated with coke blow-out during coke
cutting if there is a portion of the coke bed that is not sufficiently
cooled and we agree that double-quenching is an effective means to cool
the coke drum in those rare instances that the typical cooling cycle
does not sufficiently cool the coke drum contents, so we considered
granting the commenters' request. As noted previously, the primary
concern with early draining of the coke drum is the emissions that are
expected to occur as a result of draining superheated water. We
recognize, however, that the water temperature near the bottom of the
coke drum is typically much lower than at the top of the coke drum. If
the temperature of the water drained from the bottom of the coke drum
remains below 210 [deg]F, this would minimize steam flashing and
associated HAP emissions since the water drained would not be
superheated. We conclude that the use of double quenching is
appropriate for cases when the coke drum is not sufficiently cooled
using the normal cooling procedures provided the temperature of the
water drained remains below 210 [deg]F, and it is consistent with the
practices of the best performing sources. Consequently, we are
finalizing provisions to allow the use of double-quenching for DCU
provided the temperature of the water drained remains below 210 [deg]F.
For the CRU, we are finalizing the proposed revisions to require
CRU that employ active purging to meet the MACT emissions limitations
in Tables 15 and 16 in subpart UUU at all times regardless of vessel
pressure. We received limited comments regarding our proposal; these
comments generally concerned the costs associated with the proposed
emissions limitations. As discussed in our proposal, and based on data
submitted in response to the ICR, emissions using active purging are
much higher than those not using active purging. In the original rule,
we based the MACT floor on the best performing facilities that used
sequential pressurizations and depressurizations rather than active
purging. Thus, in the proposal, we concluded that allowing owners or
operators to actively purge while at low pressures was inconsistent
with the MACT floor emissions limitations achieved by the best
performing 12-percent of sources when the MACT floor was originally
established. As we are simply requiring these facilities to meet the
same emission levels determined to be MACT, we do not consider costs of
potential additional controls to be a viable rationale to allow these
units to emit several times more HAP than the units upon which the MACT
requirements were based and the emissions levels achieved in practice
by the vast majority of other CRU sources.
For flares, we are finalizing proposed revisions to include
detailed flare monitoring and operating requirements. We are including
the flaring provisions for refineries in the Refinery MACT rules and
removing the cross-references to the flaring requirements in the
General Provisions. The final regulatory requirements differ from the
proposed requirements in several respects. First, we are not finalizing
the ban on halogenated vent streams because we did not include
sufficient justification or include cost estimates for this proposed
provision and we did not include any monitoring requirements to ensure
compliance with this ban on halogenated vent streams.
We are finalizing the proposed no visible emissions limit and the
flare tip velocity limit but they will apply only when the flare vent
gas flow rate is below the smokeless capacity of the flare. We received
a number of comments stating that the no visible emissions limit and
the flare tip velocity limit cannot be met during large malfunctions
and emergency shutdown events. In response to comments, we are
finalizing work practice standards for emergency flaring events using
the proposed no visible emission limit and flare tip velocity limit as
thresholds in the final rule to trigger root cause analysis when the
flare vent gas flow rate is above the smokeless capacity of the flare.
The final work practice standard includes requirements to develop a
flare management plan, to implement prevention measures, and to perform
root cause analysis and implement corrective action following each
flaring event that exceeds the smokeless capacity of the flare. There
is also a limit on the number of these flaring events that a given
flare may have in the 3-year period. We are establishing these
provisions because we now recognize that flares have two different
design capacities: A smokeless design capacity and a hydraulic load
capacity. We determined that the proposed visible emissions limit and
the flare tip velocity limit for very large flow events are not the
MACT floor for such events. The final work practice standards for
flaring events are based on the best performing facilities and will
result in emission reductions in a technically feasible manner without
any negative secondary impacts.
We consider it appropriate to establish a work practice standard
for flares as provided in CAA section 112(h). While it is possible to
monitor gaseous streams going into the flare (as we have required for
the flare operating requirements) it is not possible to design and
construct a conveyance to capture the emissions from a flare. While
knowledge of the composition and flow of gases entering the flare
provides a reasonable basis for establishing operating requirements for
normal operations, we have no data on flare performance under
conditions in the hydraulic load range. While smoke in the flare
exhaust is an indication of incomplete combustion, it is uncertain
[[Page 75216]]
how much deterioration of HAP destruction efficiency occurs during a
smoking event. We also consider that the application of a measurement
methodology for flare exhaust is not practicable due to technological
and economic limitations. Passive FTIR has been used to determine
combustion efficiency in flare exhaust, but these are essentially
manual tests, and the measurement accuracy is dependent on how well the
monitor is aligned with the flare exhaust plume. Changes in wind
direction require manual movement of the monitoring system. It is also
unclear if these systems can accurately measure combustion efficiency
during high smoking events. These systems also require very specialized
expertise, and we consider that it is both technologically and
economically infeasible to measure flare exhaust emissions,
particularly during high load events. Consequently, for emergency flare
releases, we conclude that it is appropriate to establish a work
practice standard as provided in CAA section 112(h).
We also received comments that the daily visible emissions
observations were burdensome and unnecessary and some commenters
suggested that facilities be allowed to use video surveillance cameras.
We concluded that video surveillance cameras would be at least as
effective as the proposed daily 5-minute visible emissions observations
using Method 22. We are finalizing the proposed visible emissions
monitoring requirements Method 22 and the alternative of using video
surveillance cameras.
We are simplifying the combustion zone gas property operating
limits in response to public comments received. Specifically, we are
finalizing requirements that all flares meet a minimum operating limit
of 270 BTU/scf NHVcz on a 15-minute average, and we are
providing that refiners use a corrected heat content of 1,212 BTU/scf
for hydrogen to demonstrate compliance with this operating limit. We
determined that a corrected heat content of 1212 BTU/scf for hydrogen
provided a better indication of flare performance than without the
correction. We also determined that the other combustion zone
parameters, which were primarily proposed to provide suitable methods
for flares that had high hydrogen concentrations, were no longer
necessary when a 1,212 Btu/scf net heating value is used for hydrogen.
Therefore, we are not finalizing the alternative combustion zone
operating limits based on lower flammability limit or combustibles
concentration. We are also not finalizing separate combustion zone
operating limits for gases meeting the proposed hydrogen-olefin
interaction criteria. In our revised analysis of the data, we analyzed
all of the data together and determined the 270 Btu/scf
NHVcz operating limit provided in the final rule would
adequately ensure that flares achieve the desired 98-percent control
efficiency regardless of the composition of gas sent to the flare.
For air-assisted flares, we are finalizing the additional
``dilution parameter'' operating limit only for the net heating value
dilution parameter, NHVdil. Similar to the requirements we
are finalizing for the combustion zone parameters, we are finalizing
requirements that flares meet a minimum operating limit of 22 BTU/
ft2 NHVdil on a 15-minute average, and we are
providing that refiners use a corrected heat content of 1,212 BTU/scf
for hydrogen to demonstrate compliance with this operating limit. For
the reasons explained above, we are not finalizing the proposed
alternative dilution parameter operating limits based on lower
flammability limit or combustibles concentration, and we are not
finalizing separate dilution parameter operating limits for gases
meeting the proposed hydrogen-olefin interaction criteria.
For flares in dedicated service, we are establishing an alternative
to continuous or on-going grab sample requirements for determining
waste gas net heating content to reduce the burden of sampling for
flare waste gases that have consistent compositions. Flares in
dedicated service can use initial sampling period and process knowledge
to determine a fixed net heating value of the flare vent gas to be used
in the calculations of NHVcz and, if applicable,
NHVdil.
We are revising the definition of MPV to remove the exemption for
in situ sampling systems for the reasons provided in the proposed rule.
We received comments recommending that a work practice standard be
adopted for PRD rather than the proposed prohibition of atmospheric PRD
releases. Commenters stated that the prohibition was infeasible due to
the proposed immediate timing of the requirement and impractical due to
cost considerations. After reviewing these comments as well as the
BAAQMD rule (Regulation 8, Rule 8-28-304) and the SCAQMD rule (Rule
1173), we have determined that the work practice standards in these
rules reflect the level of control that applies to the best performers.
Therefore, we proceeded to evaluate appropriate MACT requirements based
on the provisions in these rules.
The BAAQMD rule requires sources to implement a minimum of three
prevention measures to limit the possibility of a release. The BAAQMD
uses a ``release event'' threshold of 10 lbs/day of organic or
inorganic pollutants; the SCAQMD rule effectively uses a release event
threshold of 500 lbs VOC/day. When a release event occurs, both rules
require that the refiner perform a root cause analysis and take
corrective action (including additional prevention measures). In
addition, both rules require piping the PRD to a flare if there are
more than two release events (releases above a certain release size
threshold) in a 5-year period. Both rules include a number of
exemptions for certain types of PRD that are not expected to release
significant amounts of pollutants to the air or that are not feasible
to control because of pressure considerations. These include PRD
associated with storage tanks, vacuum systems and equipment in heavy
liquid service as well as liquid thermal relief valves that are vented
to process drains.
There are five refineries subject to the BAAQMD rule and seven
refineries subject to the SCAQMD rule, accounting for 8-percent of
refineries nationwide and representing the industry's best performers.
We consider the BAAQMD rule to be the more stringent of the two because
this rule requires sources to implement a minimum of three prevention
measures to limit the possibility of a release (the SCAQMD rule has no
similar requirement) and uses a lower mass threshold for what is
considered a ``release event'' (10 lbs/day of organic or inorganic
pollutants versus the 500 lbs VOC release threshold in the SCAQMD
rule). Therefore, the BAAQMD rule is considered to be the MACT floor
requirement for PRDs associated with new affected sources and the
SCAQMD rule is considered to be the MACT floor for PRDs associated with
existing affected sources.
In general, an open PRD is essentially the same as a miscellaneous
process vent that is vented directly to the atmosphere. Consistent with
our treatment of miscellaneous process vents and consistent with the
two California rules, we believe that it is appropriate to exclude
certain types of PRD that have very low potential to emit based on
their type of service, size and/or pressure. For example, PRD that have
a potential to emit less than 72 pounds per day of VOC, considering the
size of the valve opening, design release pressure, and equipment
contents, would be considered in a similar manner as Group 2
miscellaneous
[[Page 75217]]
process vents and would not require additional control. The two
California rule requirements do not apply to PRD on storage tanks and
vacuum systems. Most of these PRD have a design release pressure of 2.5
psig and thus have a very limited potential to emit. It is technically
infeasible to pipe these sources to a flare (or other similar control
system) because the back pressure in the flare header system generally
exceeds 2.5 psig. We note that some storage tanks can operate at
elevated pressure (i.e., pressure tanks). Therefore, rather than follow
exactly the requirements in the California rules, we determined it more
practical to exclude PRD with design release pressure of less than 2.5
psig.
Any release from a PRD in heavy liquid service would have a visual
indication of a leak and any repairs to the valve would have to be
further inspected and, if necessary, repaired under the existing
equipment leak provisions. Therefore, consistent with the BAAQMD rule,
we are exempting PRD in heavy liquid service from the work practice
standards we are establishing in this final rule.
Both the BAAQMD and SCAQMD rules exempt thermal expansion valves
that are ``vented to process drains or back to the pipeline.'' We are
unclear what is meant by ``vented to process drains''; however, if a
liquid is released from a PRD via hard-piping to a drain system that
meets the control requirements specified in Refinery MACT 1, we
consider that these PRD are controlled and they would not be subject to
the work practice standard established in this final rule. Similarly,
all PRD in light liquid service that are hard-piped to a controlled
drain system (or back to the process or pipeline) are otherwise subject
to a MACT requirement and would not be subject to the work practice
standard.
In considering thermal relief valves not vented to process drains
or back to the pipeline, we expect that releases from these thermal
relief valves will be small and generally under the release event
thresholds specified in the California rules. Therefore, the work
practice standards do not apply to PRD that are designed solely to
release due to liquid thermal expansion.
The primary goal of the PRD work practice standard is to reduce the
size and frequency of releases. The SCAQMD rule is targeted towards
fairly large releases (compared to the direct PRD releases reported in
response to the Refinery ICR), so it will reduce the frequency of large
releases, but it does little to reduce the frequency of smaller
releases. To more effectively reduce the size and frequency of all
releases, we consider it important to require the implementation of
prevention measures (as required in the BAAQMD rule) and require root
cause analysis and corrective action for PRD releases from all PRD
subject to the work practice standard. While we recognize that if a PRD
opens for a short period of time, the release might be below the
release thresholds in the SCAQMD rules, we believe the release may be
indicative of an important issue or design flaw. Because the potential
for large emissions exist from the PRD subject to the work practice
standard, we think it is reasonable to require a root cause analysis be
conducted and appropriate corrective action implemented to potentially
identify this issue and prevent a second release which, if the issue
remains uncorrected, could be significant.
Requiring that prevention measures be implemented on all PRD
subject to the work practice standard and not establishing a release
threshold for release events is a variation from the SCAQMD rule.
However, we also considered the allowable release frequency. We believe
that our adoption of this approach is balanced by our not adopting the
SCAQMD provisions requiring that PRD be vented to a flare or other
control system or that refiners pay a fee if there are multiple
releases of a certain size within a specified timeframe.\12\ In place
of this system, we are limiting the number of events from each PRD that
can occur in a 3 year time period (2, if root causes are different),
and in place of a fine, or routing to control, stating that the 3rd
release in 3 years for any root cause is a deviation of the standard.
---------------------------------------------------------------------------
\12\ The SCAQMD rule requires PRD to be vented to a flare or
other control device if there is a single release in excess of 2,000
pounds of VOC in a 24-hour period or three releases in excess of 500
pounds of VOC in a 5-year period or, alternatively, pay a $350,000
fee. Thus, the SCAQMD rule would allow, for example, two releases of
over 500 pounds of VOC each within a 5-year period without any
penalty provided a third event did not occur. If a third event did
occur, the refinery owner or operator would then have to vent the
PRD to a flare or other control system or pay a fee ($350,000) for
the third release over 500 pounds of VOC.
---------------------------------------------------------------------------
Because we are not including a size threshold for release events as
in the SCAQMD rule, it is natural to assume release events would occur
more frequently than release events subject to the SCAQMD rules. Also,
based on our Monte Carlo analysis of random rare events, we note that
it is quite likely to have two or three events in a 5-year period when
a long time horizon (e.g., 20 years) is considered. Therefore,
considering our analysis of emergency flaring events and the lack of a
500 lb/day release threshold, we considered it reasonable to use a 3-
year period rather than a 5-year period as the basis of a deviation of
the work practice standard.
The SCAQMD work practice standards do not apply to releases that
are demonstrated to ``result from natural disasters, acts of war or
terrorism, or external power curtailment beyond the refinery's control,
excluding power curtailment due to an interruptible service
agreement.'' These types of events, which we are referring to as
``force majeure'' events, are beyond the control of the refinery owner
or operator. We are providing that these events should not be included
in the event count, but that they would be subject to the root cause
analysis in order to confirm whether the release was caused by a force
majeure event.
Consistent with the requirements in the SCAQMD rule, we are
requiring refinery owners or operators to conduct a root cause analysis
for a PRD release event. If the root cause was due to operator error or
negligence, then the release would be a deviation of the standard. For
any other release (not including those caused by force majeure events),
the owner or operator would have to implement corrective action. We
consider that a second release due to the same root cause for the same
equipment in a 3-year period would be a deviation of the work practice
standard. This provision will help ensure that root cause/corrective
action are conducted effectively. Finally, a third release in a 3-year
period (not including those caused by force majeure events) would be a
deviation of the work practice standard, regardless of the root cause.
While we are using a 3-year interval rather than the 5-year interval
provided in the SCAQMD, we consider that the requirements as included
in this final rule (i.e., the inclusion of prevention measure
requirements and no thresholds for release events) will achieve
equivalent if not greater emissions reductions than the SCAQMD rule. We
also consider that, given the prevention measure requirements and a 3-
year period, there is less likelihood of unusual random events that
happen over a short period of time that may cause refinery owners or
operators to feel compelled to vent the PRD to a flare to eliminate
concerns regarding potential non-compliance. Thus, we project that the
requirements that we have included in the final rule will achieve
emissions reductions commensurate to or exceeding the requirements in
the SCAQMD rule (that serves as the MACT floor for existing sources)
but will achieve those
[[Page 75218]]
reductions in a more cost-effective manner.
We also considered requiring all PRD to be vented through a closed
vent system to a control device as an alternative beyond-the-MACT floor
requirement. While this requirement would provide additional emission
reductions beyond those we are establishing as the MACT floor, these
reduction come at significant costs. Capital costs for requiring
control of all atmospheric PRD is estimated to be approximately $300
million compared to $11 million for the requirements described above.
The total annualized cost for requiring control of all atmospheric PRD
is estimated to be approximately $41 million/year compared to $3.3
million/year for the requirements described above. We estimate that the
incremental cost-effectiveness of requiring control of all atmospheric
PRD compared to the requirements described above exceeds $1 million per
ton of HAP reduced. Consequently, we conclude that this is not a cost-
effective option for existing sources.
The final requirements that we have developed for PRD achieve equal
or greater emission reductions than those achieved by the SCAQMD rule
(MACT floor). To the extent those requirements are more stringent that
the SCAQMD, they are cost-effective. We could not identify an
alternative requirement that provided further emission reductions in a
cost-effective manner. Thus, we conclude that the work practice
standards described above represent MACT for existing sources.
The BAAQMD rule, which represents the requirements applicable to
the best performing sources, is the basis for new source MACT for PRD.
Based on the specific provisions for PRD in the BAAQMD rule, we
conclude that the MACT floor requirement is to have all PRD in HAP
service associated with a new affected source vented through a closed
vent system to a control device. As with existing sources, the PRD WPS
would also contain the same exclusions (e.g., heavy liquid service
PRDs, thermal expansion valves, liquid PRDs that are hard-piped to
controlled drains, PRD with release pressures of less than 2.5 psig,
PRD with emission potential of less than 72 lbs/day, and PRD on mobile
equipment). These provisions are similar to the applicability
provisions of the BAAQMD rule. Thus, we retain the same applicability
of the work practice standard for PRDs on new or existing equipment,
but all affected PRD on a new source would be required to be
controlled. This is essentially equivalent to the proposed requirement
of no atmospheric releases. We could not identify a control option more
stringent than the BAAQMD rule as applied to new sources. Therefore, we
conclude that venting all PRD in HAP service through a closed vent
system to a flare or similar control system is MACT for PRD associated
with new affected sources.
We consider it appropriate to establish a work practice standard
for PRD as provided in CAA section 112(h). While it may be possible to
design and construct a conveyance for PRD releases, we consider that
the application of a measurement methodology for PRDs is not
practicable due to technological and economic limitations. First, it is
not practicable to use a measurement methodology for PRD releases. The
venting time can be very short and may vary widely in composition and
flow rate. The often-short duration of an event makes it infeasible to
collect a grab sample of the gases when a release occurs, and a single
grab sample would not account for potential variation in vent gas
composition. It would be economically prohibitive to construct an
appropriate conveyance and install and operate continuous monitoring
systems for each individual PRD in order to attempt to quantitatively
measure a release event that may occur only a few times in a 3-year
period. Additionally, we have not identified an available, technically
feasible continuous emission monitoring systems that can determine a
mass VOC or HAP release quantity accurately given the flow, composition
and composition variability of potential PRD releases from refineries.
Consequently, we conclude that it is appropriate to establish a work
practice standard for PRD releases as provided in CAA section 112(h).
D. NESHAP Amendments Addressing Emissions During Periods of SSM
1. What amendments did we propose to address emissions during periods
of SSM?
We proposed to eliminate the SSM exemption in 40 CFR part 63,
subparts CC and UUU. Consistent with Sierra Club v. EPA, we proposed
standards in these rules that apply at all times. We also proposed
several revisions to Table 6 of subpart CC of 40 CFR part 63 and to
Table 44 to subpart UUU of 40 CFR part 63 (the General Provisions
Applicability tables for each subpart), including eliminating the
incorporation of the General Provisions' requirement that the source
develop an SSM plan, and eliminating and revising certain recordkeeping
and reporting requirements related to the SSM exemption.
For Refinery MACT 1, we proposed that the use of a bypass at any
time to divert a Group 1 miscellaneous process vent to the atmosphere
is a deviation of the emission standard, and specified that refiners
install, maintain and operate a continuous parameter monitoring system
(CPMS) for flow that is capable of recording the volume of gas that
bypasses the APCD.
We also proposed to revise the definition of MPV to remove the
exclusion for ``Episodic or non-routine releases such as those
associated with startup, shutdown, malfunction, maintenance,
depressuring and catalyst transfer operations.'' We also proposed that
the control requirements for Group 1 MPV apply at all times, including
startup and shutdowns.
For Refinery MACT 2, we proposed alternate standards for three
emission sources for periods of startup or shutdown. We proposed PM
standards for startup of FCCU controlled with an ESP under Refinery
MACT 2 because of safety concerns associated with operating an ESP
during an FCCU startup. For FCCU controlled by an ESP, we proposed a
30-percent opacity limit (on a 6-minute rolling average basis) during
the period that torch oil is used during FCCU startup. For startup of
FCCU without a post-combustion device under Refinery MACT 2, we
proposed a CO standard based on an excess oxygen concentration of 1
volume percent (dry basis) based on a 1-hour average. For periods of
SRU shutdown, we proposed to allow diverting the SRU purge gases to a
flare meeting the design and operating requirements in 40 CFR 63.670
(or, for a limited transitional time period, 40 CFR 63.11) or to a
thermal oxidizer operated at a minimum temperature of
1,200[emsp14][deg]F and a minimum outlet oxygen concentration of 2
volume percent (dry basis). For other emission sources in Refinery MACT
2, we proposed that the requirements that apply during normal
operations should apply during startup and shutdown.
2. How did the SSM provisions change since proposal?
a. Refinery MACT 1
We proposed that when process equipment is opened to the atmosphere
(e.g., for maintenance), the existing MPV emissions limits apply. In
this final rule, we are instead finalizing startup and shutdown
provisions that apply to these venting events. These startup and
shutdown provisions are work practice standards that allow refinery
owners or operators to open process equipment
[[Page 75219]]
during startup and shutdown provided that the equipment is drained and
purged to a closed system until the hydrocarbon content is less than or
equal to 10-percent of the LEL. For those situations where 10-percent
LEL cannot be demonstrated (no direct measurement location), the
equipment may be opened and vented to the atmosphere if the pressure is
less than or equal to 5 psig. Active purging of the equipment is only
allowed after the 10-percent LEL level is achieved, regardless of the
pressure of the equipment/vessel. We are establishing a separate
requirement for very small process equipment, defined as equipment
where it is physically impossible to release more than 72 lbs VOC per
equipment opening based on the size and contents of the equipment. This
definition is consistent with the Group 1 applicability cutoff for
control of miscellaneous process vents. We also developed requirements
specific to catalyst changeout activities where pyrophoric catalyst
(e.g., hydrotreater or hydrocracker catalysts) must be purged using
recovered hydrogen. These provisions include: Documenting the
procedures for equipment openings and procedures for verifying that
events meet the specific conditions above using site procedures used to
de-inventory equipment for safety purposes (i.e., hot work or vessel
entry procedures) and documenting any deviations from the work practice
standard requirements.
b. Refinery MACT 2
We are expanding the proposed 1-percent minimum oxygen operating
limit alternative for organic HAP to apply for all FCCU startup and
shutdown events (rather than only partial burn FCCU with CO boilers
during startup). We are replacing the proposed opacity limit
alternative to the metal HAP standard with a minimum cyclone face
velocity limit and we are extending that alternative limit to all FCCU
(regardless of control device) for both startup and shutdown in this
final rule.
We are extending the proposed alternative for SRU to monitor
incinerator temperature and excess oxygen limits during SRU shutdowns
to also apply during periods of startup.
3. What key comments did we receive on the SSM revisions and what are
our responses?
a. Refinery MACT 1
Comment: Many commenters stated that the proposed extension of the
MPV definition to episodic maintenance startup and shutdown vents and
elimination of the SSM exception for storage tanks would create
hundreds or thousands of new vents per refinery per year and generate
massive on-going burdens. The commenters argued that the EPA has not
included in the record any analysis of the potential environmental
benefits, costs or operational and compliance feasibility and impacts
associated with this requirement and that many of these requirements
will result in delayed and extended equipment and process outages. One
commenter asserted that the EPA has articulated no justification for
applying emission standards to these events, nor any analysis
consistent with CAA section 112 for a determination that MACT standards
are appropriately applied to these emission events under the criteria
in CAA section 112(d).
Many commenters stated that every time a vessel is opened for
inspection or maintenance each vent point will have to be evaluated as
a potential MPV or storage tank vent. If a particular vent point (e.g.,
bleeder) used for maintenance, startup or shutdown handles material
that is initially greater than 20 ppm HAP, then it is a MPV. If there
is a potential to emit greater than or equal 72 lbs/day of VOC, then it
is a Group 1 MPV and must be controlled. If there is a potential of
less than 72 lb/day VOC release, then it is a Group 2 MPV and subject
to recordkeeping requirements. Commenters stated that in a refinery
there would be tens or more such activities per day associated with
normal maintenance and inspection; during turnarounds, there could be
hundreds of such MPVs. Commenters added that these MPVs may then need
to be individually accounted for and permitted creating an unnecessary
permitting and recordkeeping burden for these periodic emissions.
Commenters recommended a general set of work practice requirements
for maintenance, startup and shutdown of vents, based on state
requirements, that do not impose the permitting, notice and evaluation
requirements associated with identifying these vents individually.
Commenters explained that states have dealt with these episodic vents
by establishing them as a special class of process vent with limited
recordkeeping requirements and subject to a work practice standard,
rather than the normal MPV requirements. A key element of these work
practices is clear identification of the criteria for releasing these
vents to the atmosphere and for routing these vents to control after
hydrocarbon is reintroduced, which the commenters asserted the current
rule does not provide. Commenters proposed that a work practice
standard could include removing process liquids to the extent practical
and depressuring smaller volume equipment until a pressure of <5 psig
is achieved and/or purging and depressuring to a control device until
the vent has a hydrocarbon concentration of less than 10-percent of the
LEL. The commenters suggested that these standards should provide clear
easily monitored criteria for when this equipment can be vented to the
atmosphere, and should not impose the permitting, notice and evaluation
requirements associated with identifying these vents as individual
MPVs. One commenter provided draft regulatory language for a work
practice requirement.
Response: We proposed to eliminate the episodic and non-routine
emission exclusion in order to ensure that the MACT includes emission
limits that apply at all times consistent with the holding in Sierra
Club. At the time of the proposal, we expected that essentially all SSM
event emissions would be routed to flares that are subject to the MACT
standards and, thus, would serve to control these emissions. However,
we recognize that maintenance activities that require equipment
openings are a separate class of startup/shutdown emissions because
there must be a point in time when the vessel can be opened and any
emissions vented to the atmosphere. We acknowledge that it would
require a significant effort to identify and characterize each of these
potential release points for permitting purposes.
In considering these comments and whether we should establish a
separate limit that would apply to these equipment openings, we
reviewed state permit requirements and the practices employed by the
best performing sources. We found that some state or local agencies
required depressuring to 5 psig prior to atmospheric releases while
others required the gases to have organic concentrations at or below
10-percent of LEL prior to atmospheric venting. In the final rule, we
are establishing a requirement that prior to opening process equipment
to the atmosphere, the equipment must first be drained and purged to a
closed system so that the hydrocarbon content is less than or equal to
10-percent of the LEL. For those situations where 10-percent LEL cannot
be demonstrated, the equipment may be opened and vented to the
atmosphere if the pressure is less than or equal to 5 psig, provided
there is no active purging of the equipment to the atmosphere until the
LEL criterion is met. For equipment where it is not technically
possible to depressurize to a
[[Page 75220]]
control system, we allow venting to the atmosphere where there is no
more than 72 lbs VOC per day potential, consistent with our Group 1
applicability cutoff for control of process vents. For catalyst
changeout activities where hydrotreater pyrophoric catalyst must be
purged we have provided limited allowances for direct venting.
Provisions to demonstrate compliance with this work practice include
documenting the procedures for equipment openings and procedures for
verifying that events meet the specific conditions above using site
procedures used to de-inventory equipment for safety purposes (i.e.,
hot work or vessel entry procedures).
b. Refinery MACT 2
Comment: Several commenters noted that there was a proposed
specific alternative metal HAP/PM standard for startup of an FCCU
controlled with an ESP, but took issue with the fact that no
alternative PM limits were proposed for startup of FCCU equipped with
other types of PM controls, or for any FCCU during periods of shutdown
or hot standby. Regarding the proposed alternative for startup, which
would provide an alternative in the form of an opacity limit when torch
oil is in use, commenters stated that there are serious process safety
concerns which prevent most FCCU ESPs from being operated when torch
oil is in the regenerator, that is, during periods of startup, shutdown
and hot standby. To avoid the possibility of a fire and explosion, the
commenters claimed ESPs are usually de-energized and bypassed during
these periods and, consequently, these FCCUs are generally unable to
meet the proposed 30-percent opacity limit.
Several commenters stated that the EPA's limits on FCCU opacity
during SSM are unreasonable and ignore the technical requirements for
transitional operations of those units. The commenters indicated that
they have ESPs located downstream of the CO boiler and claimed that for
safety reasons the CO boiler cannot operate during startup, shutdown or
hot standby. Further, a commenter indicated that the ESP cannot operate
if the CO boiler is not operating and thus both the CO boiler and the
ESP must be bypassed during startup, shutdown, and hot standby
operations.
Another commenter stated that the EPA offers no data to support the
achievability of this requirement in practice and discusses information
for 26 startup/shutdown events that found that none complied with a 30-
percent opacity requirement. Several commenters also noted that
experience has shown that the 30-percent opacity limit is unachievable
during these periods for FCCUs controlled with tertiary cyclones, when
regenerator gas flow is below cyclone minimum design flow.
Several commenters suggested that the EPA establish a standard
based on the operation of FCCU catalyst regenerators' internal cyclones
that function to retain the catalyst in the regenerators and thereby
minimize catalyst and metal HAP emissions from the regenerators.
Additional control to meet the Refinery MACT 2 emission limit of not
more than 1.0 lb PM/1,000 lbs coke burn-off is provided by a bag house,
wet gas scrubber (WGS), ESP or tertiary (external) cyclone. The
efficiency of a cyclone is a function of the inlet gas velocity.
Assuring adequate velocity to the internal cyclones ensures that the
catalyst sent to these additional controls is minimized and ensures
that they are operating as effectively as possible. Similarly, even if
the FCCU cannot meet the normal opacity limits during startup, shutdown
or hot standby (e.g. due to the ESP being off-line for safety reasons
or the tertiary cyclones or WGS operating at non-routine conditions),
assuring adequate velocity to the internal regenerator cyclones will
control and minimize particulate emissions. Several commenters stated
support for another commenter's position that all FCCUs should be
allowed the option of complying with a 20 feet/second minimum inlet
velocity to the primary regenerator cyclones during periods of startup
and shutdown, including hot standby, and these commenters provided
additional technical explanations in their comments.
On the other hand, some commenters seemed to support the proposed
opacity limits, but suggested minor revisions. One commenter noted that
the SCAQMD has granted Valero's request for variances from visible
emission standards during startup of the FCCU of up to 65-percent
opacity for up to five minutes, in aggregate, during any 1-hour period,
and 30-percent as an hourly average for the remaining period, during
startup events. The application of this variance reflects the
unavailability and/or ineffectiveness of the ESP during the startup
condition. Another commenter recommended that either the opacity
standard should be raised or the time period for averaging should be
extended so FCCUs can be operated safely during SSM events and still
remain in compliance.
Response: We have reviewed the data submitted by the commenters to
support their assertion that the 30-percent opacity limit (determined
on a 6-minute average basis) is not achievable during startup and
shutdown events. While the data are limited, and it is unclear if the
data provided are indicative of the performance achieved by the best
performing sources, we do not have adequate data to refute the
assertion that the 30-percent opacity limit (determined on a 6-minute
average basis) is not achievable during startup and shutdown events. We
considered the two options suggested by the commenters, the minimum
velocity for the internal FCCU regenerator cyclones and the 30-percent
hourly average opacity limit excluding 5 minutes not exceeding 65-
percent opacity. Again, due to the limited data available during
startup and shutdown events, we are not able to determine which
requirement would provide greater HAP emissions reduction. However, we
note that some facilities may not be required to have an opacity
monitoring system in place and opacity monitoring is not applicable for
FCCU controlled with wet scrubbers. Therefore, we find that the minimum
internal cyclone inlet velocity requirement is more broadly applicable
than the opacity limit. Also, based on the data provided by the
commenters, the minimum internal cyclone inlet velocity requirement
will provide PM (and therefore metal HAP) emissions reductions during
startup and shutdown periods. Therefore, considering the available
data, we conclude that MACT for FCCU startup and shutdown events is
maintaining the minimum internal cyclone inlet velocity of 20 feet/
second.
Comment: Several commenters stated that the EPA should provide
alternate standards for startups of FCCU equipped with CO boilers and
for any FCCU during periods of shutdown and hot standby. The commenters
stated that the EPA incorrectly assumes that refiners are able to
safely and reliably start up their FCCU with flue gas boilers in
service and meet the normal operating limit of 500 ppm CO. They claimed
that most refiners are unable to reliably start up their FCCU with flue
gas boilers in service due to the design of the boiler and the fact
that many boilers are not able to safely and reliably handle the
transient FCCU operations that can occur during startup, shutdown, and
hot standby. One commenter stated that FCCU built with CO boilers
experience issues with flame stability due to fluctuating flue gas
compositions and rates when starting up and shutting down. Accordingly,
the commenter stated, startup and shutdown activities at FCCU using a
boiler as an APCD are not currently meeting the Refinery MACT 2
standard
[[Page 75221]]
of 500 ppm CO on a 1-hour basis, and this level of control does not
qualify as the MACT floor. The commenter gave examples of facilities
where FCCU, including those equipped with post-combustion control
systems, do not consistently demonstrate compliance with a 500 ppm CO
concentration standard during all startup and shutdown events.
Commenters stated that reliable boiler operation is critical to the
overall refinery steam system and refineries must avoid jeopardizing
boiler operation to prevent major upsets of process operations. A major
upset or site-wide shutdown could result in flaring and emissions of
HAP far in excess of that emitted while bypassing the CO boiler.
Commenters stated that combustion of torch oil in the FCCU
regenerator during startup is one of the primary reasons the CO limit
cannot be met during these operations. Torch oil is also used during
shutdown to control the cooling rate (and potential equipment damage)
and during hot standby and, thus, the normal CO standard cannot be met
at these times either. Hot standby is used to hold an FCCU regenerator
at operating temperature for outages where a regenerator shutdown is
not needed and to avoid full FCCU shutdowns. Full cold shutdown also
increases personnel exposures associated with removing catalyst and
securing equipment. Additionally, this can produce additional emissions
over maintaining the unit in hot standby. Commenters claimed that
because of the variability of CO during torch oil operations, it is not
possible for the EPA to establish a CAA section 112(d) standard for
startup and shutdown activities at FCCU because refineries cannot
measure a constant level of emissions reductions.
The commenters recommended expansion of the proposed standard of
greater than 1-percent hourly average excess regenerator oxygen to all
FCCU, including units with fired boilers. These commenters suggested
that maintaining an adequate level of excess oxygen for the combustion
of fuel in the regenerator is the best way to minimize CO and organic
HAP emissions from FCCU during these periods.
Response: After reviewing the comments and discussing CO boiler
operations with facility operators, we agree that the 1-percent minimum
oxygen limit should be more broadly applicable to FCCU startup and
shutdown regardless of the control device configuration and have
revised the final rule accordingly.
Comment: Several commenters stated that the proposed alternative
standards for SRP shutdowns should be extended to startups as well
since the normal SRP emission limitation cannot always be achieved
during SRP startups. Several commenters gave examples of startup
activities where this relief is needed, and noted there may be other
startup activities that also need this relief.
Response: For the control of sulfur HAP, we determined that
incineration effectively controls these HAP. We were not aware that
there would be unusual sulfur loads in the SRU tail gas during startup.
We agree that the alternative standard we proposed for periods of
shutdown is also the MACT floor for periods of startup because
incineration meeting the limits proposed will achieve the MACT control
requirements for sulfur HAP during periods of either startup or
shutdown even though sulfur loadings during these periods may be
elevated. For many SRU configurations, compliance during normal
operations is demonstrated by monitoring SO2 emissions.
However, during startup and shutdown, high sulfur loadings in the SRU
tail gas entering the incinerator will cause high SO2
emissions even though sulfur HAP emissions are well controlled.
Consequently, the proposed incinerator operating limits provide a
better indication of sulfur HAP control during startup and shutdown
than SO2 emissions. Owners or operators that use
incinerators or thermal oxidizers during normal operations may meet the
site-specific temperature and excess oxygen operating limits that were
determined based on their performance test during periods of startup
and shutdown.
4. What is the rationale for our final approach and final decisions to
address emissions during periods of SSM?
a. Refinery MACT 1
We did not receive comments regarding the proposed amendments to
Table 6 of subpart CC of 40 CFR part 63; therefore, for the reasons
provided in the preamble to the proposed rule, we finalizing these
amendments as proposed.
We determined that it was overly burdensome and in most cases
technically infeasible to consider every potential equipment or vessel
opening and classify these ``openings'' (newly classified as MPV in the
proposal) as either Group 1 or Group 2 MPV. We also determined that it
is not always technically feasible, depending on the opening, to
demonstrate compliance with the MPV emissions limitations. After
considering the public comments, we determined it was appropriate to
establish separate startup and shutdown provisions for MPV associated
with process equipment openings. We reviewed state and local
requirements and based the final rule requirements on the emissions
limitations required to be followed by the best performing sources.
Therefore, we are finalizing requirements for refinery owners or
operators to open process equipment during these startup and shutdown
events without directly permitting these ``vents'' as Group 1 or Group
2 MPV provided that the equipment is drained and purged to a closed
system until the hydrocarbon content is less than or equal to 10-
percent of the LEL. As described in further detail previously in this
section, we have provided provisions for special cases where the 10-
percent LEL limit cannot be demonstrated and provisions for less
significant equipment openings, consistent with the practices used by
the best performing facilities.
b. Refinery MACT 2
We did not receive significant comments regarding the proposed
amendments to Table 44 to subpart UUU of 40 CFR part 63; therefore, we
finalizing these amendments as proposed.
In response to comments, we determined that the limited provisions
that were provided for startup only or for shutdown only were too
limited and we have expanded the proposed provisions to both startup
and shutdown regardless of control device used. For the FCCU organic
HAP emissions limit, we are finalizing an alternative limit for periods
of startup of no less than 1-percent oxygen in the exhaust gas as
proposed, but we are extending that alternative limit to shutdown and
to all FCCU in this final rule.
For the FCCU metal HAP emissions limit, we proposed a specific
startup limit for FCCU controlled be an ESP of 30-percent opacity. We
received comments along with limited data suggesting that this limit
was not achievable. Commenters suggested that the best performing units
maintain a minimum face velocity of at least 20 feet/second to minimize
catalyst PM losses during startup and shutdowns. Operators of wet
scrubbers also noted that they cannot maintain pressure drops and that
one cannot meet the PM emissions limit normalized by coke burn-off rate
when the coke burn-off rate approaches zero. Consequently, commenters
stated that the alternative limits should be provided for startup and
shutdown regardless of control device. Upon consideration of the
comments, we determined that it was necessary to revise the proposed
[[Page 75222]]
alternative to be based on minimum inlet face velocity to the FCCU
regenerator internal cyclones and provide the alternative for both
startup and shutdown. We also expanded this limit to all FCCU; however,
we also required FCCU with wet scrubbers to meet only the liquid to gas
ratio operating limit during periods of startup and shutdown to allow
wet scrubbers to use a consistent compliance method at all times.
For SRU, we are finalizing an alternative standard during periods
of startup and shutdown to use a flare that meets the operating limits
included in the final rule or a thermal oxidizer or incinerator
operated at a minimum hourly average temperature of 1,200 [deg]F and a
minimum hourly average outlet oxygen concentration of 2 volume percent
(dry basis). We proposed these alternatives for periods of shutdown
only, but based on comments received regarding startup issues, we
determined that high sulfur loadings can occur during periods of
startup and that the alternative limit proposed was appropriate for
both startup and shutdown.
E. Technical Amendments to Refinery MACT 1 and 2
1. What other amendments did we propose for Refinery MACT 1 and 2?
We proposed a number of amendments to Refinery MACT 1 and 2 to
address technical issues such as rule language clarifications and
reference corrections. First, we proposed to amend Refinery MACT 1 to
clarify what is meant by ``seal'' for open-ended valves and lines that
are ``sealed'' by the cap, blind flange, plug, or second valve by
stating that sealed means when there are no detectable emissions from
the open-ended valve or line at or above an instrument reading of 500
ppm. Second, we also proposed electronic reporting requirements where
owners or operators of petroleum refineries must submit electronic
copies of required performance test and performance evaluation reports
for compliance with Refinery MACT 1 and 2 by direct computer-to-
computer electronic transfer using EPA-provided software. Third, we
proposed to update the General Provisions Tables 6 (for Refinery MACT
1) and 44 (for Refinery MACT 2) to correct cross references and to
incorporate additional sections of the General Provisions that are
necessary to implement these rules.
2. How did the other amendments for Refinery MACT 1 and 2 change since
proposal?
We are not finalizing the definition of ``seal'' for open-ended
lines as proposed. We are finalizing changes to update the General
Provisions cross-reference tables as proposed, with one minor change to
provide an option for the administrator to issue guidance on
performance test reporting timeframes in order to address issues
relating to submittal of data to the ERT.
3. What key comments did we receive on the other amendments for
Refinery MACT 1 and 2 and what are our responses?
Comment: Numerous commenters objected to the proposal to clarify
the meaning of ``seal'' as it relates to open-ended line (OEL)
standards. Commenters contend that there is no basis for the EPA to
assert that the proposed definition merely ``clarifies'' an established
interpretation of the term ``seal'' and stated that the proposed
revision constitutes an illegal change in the requirements for OELs,
and the clarification should not be finalized.
One commenter stated that none of the MACT standards in place
before this proposal have stated or suggested that a ``sealed'' OEL is
one with detectable emissions below 500 ppm. This commenter added this
unique interpretation of the requirement to ``seal'' an OEL with a cap
or plug is incompatible with the historical interpretation of this
requirement by affected facilities and by the EPA, and the EPA has not
issued any sort of definitive guidance or interpretation setting out
this position. The commenter detailed numerous references to
considerations the EPA has made relative to OEL requirements in LDAR
programs. In addition to the examples cited, the commenter noted that
in 2006, the EPA proposed to add a ``no detectible emissions'' limit
and monitoring requirement for OELs to NSPS VV (71 FR 65317, November
7, 2006). Two commenters noted that the proposed monitoring was not
finalized in either NSPS VV or VVa (72 FR 64860, November 16, 2007)
because it was not considered BDT due to the low emission reductions
and the cost effectiveness of the requirement. Another commenter agreed
that there is no explanation provided for why this information could
now support the need for a new OEL seal standard that requires
monitoring to ensure compliance when it was deemed to be unjustified
previously.
In addition, the commenter collected OEL monitoring data and
submitted it to the EPA (see Docket Item No. EPA-HQ-OAR-2010-0869-
0058). Based on these data, the commenter asserted that the existence
of leaks from OELs that are not properly sealed is extremely low.
The commenter noted that the EPA is claiming this change is only a
clarification of current requirements, allowing the EPA to bypass the
need to cite a CAA authorization for this change to the existing CAA
section 112(d)(2) standard or meet the process requirements associated
with such a change, including providing emission reduction, cost and
burden estimates in the record and the associated PRA Information
Collection Request (ICR).
Several commenters claimed that this clarification would result in
retroactive impact and also addressed the implication of the proposed
change on other fugitive emissions standards. One commenter stated that
the EPA cannot retroactively reinterpret the OEL requirements or define
the word ``seal'' and added that the EPA should account for the
thousands of additional monitoring events per year per refinery that
this new requirement would add to LDAR programs and provide proper cost
justification under CAA sections 112(d)(6) or 112(f)(2).
Several commenters also stated that the proposed definition will
effectively change all equipment leak rules in parts 40 CFR parts 60,
61 and 63 and the change should not be finalized. One commenter added
that by claiming this change is only a clarification of current
requirements, the EPA would set a precedent applicable to all OELs in
all industries subject to any similar OEL equipment leak requirement.
Response: We have decided not to finalize the proposed
clarification of the term ``seal'' for OELs at this time. The fenceline
monitoring requirements we are finalizing will detect any significant
leaks from a cap, blind flange, plug or second valve that does not
properly seal an OEL, as well as significant leaks from numerous other
types of fugitive emission sources.
Comment: A few commenters stated that the proposed use of the ERT
is not appropriate because the costs and burdens imposed are additive
to the costs of producing and submitting the written report, and there
is no benefit that justifies the additional cost. One commenter also
stated that the EPA has not developed or articulated a reasonable
approach to using information that would be uploaded to the ERT. The
commenters recommended that the EPA remove this portion of the proposal
until the ERT is demonstrated to handle all the information from
refinery performance
[[Page 75223]]
tests (rather than only portions), thereby eliminating the need for
both written and electronic reporting and until the Agency demonstrates
that it is using the electronic data to develop improved air quality
emission factors.
Other commenters stated that the ERT requirement does not supersede
or replace any state reporting requirements and thus the regulated
industry will be subject to dual reporting requirements. These
commenters disagreed with the preamble claim that eliminating the
recordkeeping requirements for performance test reports is a burden
savings, and stated that it may duplicate burdens already borne by the
regulated community.
The commenters expressed further concern that duplicative reporting
requirements will strain the regulated industry to comply with
deadlines established by rule for report submittals. One commenter
stated that there is no mechanism for obtaining extensions for special
circumstances. Under proposed 40 CFR 63.655(h)(9)(i), all reports are
due in 60 days. The commenter claimed that by not referencing reporting
requirements to the General Provisions in 40 CFR 63.10(d)(2), there is
no allowance for obtaining additional time due to unforeseen
circumstances or due to the difficulties involved with completing
particularly complex reports.
One commenter stated that the primary performance test method
(Method 18) required for determining compliance is not currently
included in the list of methods supported by the ERT. The commenter
stated that the regulated community's experience with Method 18 is that
it is a very broad methodology and can be exceptionally complex to
execute and to report. The commenter stated that the EPA is aware that
Method 18 reporting is complex, that it may be difficult to incorporate
into the ERT, and that no time schedule has been defined for
development or implementation for this method.
The commenter also stated that without formal notice of changes to
the ERT, the regulated community is at risk of non-compliance. The only
way for the regulated community to know that changes have occurred in
the ERT is to monitor the Web site directly because the EPA does not
formally announce changes to the ERT in the Federal Register. As such,
it would be possible for a regulated entity to be unaware of changes
made such as the incorporation of Method 18. The commenter expressed
concern that the proposal language is an open-ended commitment subject
to change without notice. The commenter stated that the EPA should
clearly indicate when facilities would be required to use the ERT when
new test methods are included in the ERT.
Response: We disagree that use of the ERT for completing stack test
reports is an added cost and burden. While the requirement to report
the results of stack tests with the ERT does not supersede state
reporting requirements, we are aware of several states that already
require the use of the ERT, and we are aware of more states that are
considering requiring its use. We note that where states will not
accept an electronic ERT submittal, the ERT provides an option to print
the report, and the printed report can be mailed to the state agency.
We have no reason to believe that the time savings in the ability to
reuse data elements within reports does not, at a minimum, offset the
cost incurred by printing out and mailing a copy of the report and the
commenters have provided no support for their cost claims.
Furthermore, based on the analysis performed for the Electronic
Reporting and Recordkeeping Requirements for the New Source Performance
Standards Rulemaking (ERRRNSPS) (80 FR 15100), electronic reporting
results in an overall cost savings to industry when annualized over a
20-year period. The cost savings is achieved through means such as
standardization of data, embedded quality assurance checks, automatic
calculation routines and reduced data entry through the ability to
reuse data in files instead of starting from scratch with each test. As
outlined in the ERRRNSPS, there are many benefits to electronic
reporting. These benefits span all users of the data--the EPA, state
and local regulators, the regulated entities and the public. We note
that in the preamble to this proposed rule we provided a number of
reasons why the use of the ERT will provide benefit going forward and
that most of the benefits we outlined were longer-term benefits (e.g.,
reducing burden of future information collection requests).
Additionally, we note that in 2011, in response to Executive Order
13563, the EPA developed a plan \13\ to periodically review its
regulations to determine if they should be modified, streamlined,
expanded or repealed in an effort to make regulations more effective
and less burdensome. The plan includes replacing outdated paper
reporting with electronic reporting. In keeping with this plan and the
White House's Digital Government Strategy, \14\ in 2013 the EPA issued
an agency-wide policy specifying that new regulations will require
reports to be electronic to the maximum extent possible. By requiring
electronic submission of stack test reports in this rule, we are taking
steps to implement this policy. We also disagree that we have not
developed or articulated a reasonable approach to using information
that would be uploaded to the ERT. To the contrary, we have discussed
at length our plans for the use of stack test data collected via the
ERT. In 2009, we published an advanced notice of proposed rulemaking
(74 FR 52723) for the Emissions Factors Program Improvements. In that
notice, we first outlined our intended approach for revising our
emissions factors development procedures. This approach included using
stack test data collected with the ERT. We reiterated this position in
our ``Recommended Procedures for the Development of Emissions Factors
and Use of the WebFIRE Database'' (https://www.epa.gov/ttn/chief/efpac/procedures/procedures81213.pdf), which was subject to public notice and
comment before being finalized in 2013. Finally, we discussed uses of
these data in the preamble to the proposed rule and at length in the
preamble to the ERRRNSPS.
---------------------------------------------------------------------------
\13\ EPA's ``Final Plan for Periodic Retrospective Reviews,''
August 2011. Available at: https://www.epa.gov/regdarrt/retrospective/documents/eparetroreviewplan-aug2011.pdf.
\14\ Digital Government: Building a 21st Century Platform to
Better Serve the American People, May 2012. Available at: https://www.whitehouse.gov/sites/default/files/omb/egov/digital-government/digital-government-strategy.pdf.
---------------------------------------------------------------------------
We think that it is a circular argument to say that the agency
should eliminate the use of the ERT until it demonstrates that it is
using the electronic data. It would be impossible for the agency to use
data that it does not have. We can only use electronic data once we
have electronic data. We do note that we are nearing completion of
programming the WebFIRE database with our new emissions factor
development procedures and anticipate running the routines on existing
data sets in the near future.
We continue to improve and upgrade the ERT on an ongoing basis. The
current version of the ERT supports 41 methods, including EPA Methods
1-4, 5, 5B, 5F, 25A 26, and 26A. We note that the ERT does not
currently support EPA Method 18, and for performance tests using Method
18, the source will still have to produce a paper report. However, we
are aware of the need to add Method 18 to the ERT, and we are currently
looking at developing this capability. As noted in the ERRRNSPS, when
new methods are added to the
[[Page 75224]]
ERT, we will not only post them to the Web site; we will also send out
a listserv notice to the Clearinghouse for Inventories and Emissions
Factors (CHIEF) listserv. Information on joining the CHIEF listserv can
be found at https://www.epa.gov/ttn/chief/listserv.html#chief. We are
requiring the use of the ERT if the method is supported by the ERT, as
listed on the ERT Web site (https://www.epa.gov/ttn/chief/ert/ert_info.html) at the time of the test. We do not agree that it is
overly burdensome to check a Web site for updates prior to conducting a
performance test.
We did revise the MACT 1 and 2 tables referencing reporting
requirements to the general provisions (Table 6 for Refinery MACT 1 and
Table 44 for Refinery MACT 2) to provide flexibility in the 60-day
reporting timeline to accommodate unforeseen circumstances or
difficulties involved with completing particularly complex reports.
4. What is the rationale for our final approach and final decisions for
the other amendments for Refinery MACT 1 and 2?
We are not finalizing the definition of seal, as proposed. The
fenceline monitoring work practice standard will detect any significant
leaks from a cap, blind flange, plug or second valve that does not
properly seal an OEL, as well as significant leaks from numerous other
types of fugitive emission sources.
We are finalizing requirements for electronic reporting, as
proposed, with a minor clarification. Specifically, we are revising
Tables 6 in subpart CC and 44 in subpart UUU, which cross-reference the
applicable provisions in the General Provisions to provide flexibility
in the ERT 60-day reporting timeline. Refiners can seek approval from
the EPA or a delegated state additional time for submittal of data due
to unforeseen circumstances or due to the difficulties involved with
completing particularly complex reports.
F. Technical Amendments to Refinery NSPS Subparts J and Ja
1. What amendments did we propose for Refinery NSPS Subparts J and Ja?
We proposed a number of amendments to Refinery NSPS subparts J and
Ja to address reconsideration issues and minor technical
clarifications. First, we proposed revisions to 40 CFR 60.100a(b) to
include a provision that sources subject to Refinery NSPS subpart J
could elect to comply instead with the provisions of Refinery NSPS
subpart Ja.
Second, we proposed a series of amendments to the requirements for
SRP in 40 CFR 60.102a, to clarify the applicable emission limits for
different types of SRP based on whether oxygen enrichment is used. The
amendments proposed also clarified that emissions averaging across a
group of emission points within a given SRP is allowed for each of the
different types of SRP, and that emissions averaging is specific to the
SO2 or reduced sulfur standards (and not to the 10 ppmv
hydrogen sulfide (H2S) limit). We also proposed a series of
corresponding amendments in 40 CFR 60.106a to clarify the monitoring
requirements, particularly when oxygen enrichment or emissions
averaging is used. We also proposed clarifications in 40 CFR 60.106a to
consistently use the term ``reduced sulfur compounds'' when referring
to the emission limits and monitoring devices needed to comply with the
reduced sulfur compound emission limits for sulfur recovery plants with
reduction control systems not followed by incineration.
Third, we proposed amendments to 40 CFR 60.102a(g)(1) to clarify
that CO boilers, while part of the FCCU affected facility, can also be
FGCD.
Fourth, we proposed several revisions to 40 CFR 60.104a to clarify
the performance testing requirements. We proposed revision to 40 CFR
60.104a(a) to clarify that an initial compliance demonstration is
needed for the H2S concentration limit in 40 CFR 60.103a(h).
We proposed revisions to the annual PM testing requirement in 40 CFR
60.104a(b) to clarify that annually means once per calendar year, with
an interval of at least 8 months but no more than 16 months between
annual tests. We also proposed to amend 40 CFR 60.104a(f) to clarify
that the provisions of that paragraph are specific to owners or
operators of an FCCU or FCU that use a cyclone to comply with the PM
emissions limit in 40 CFR 60.102a(b)(1) and not to facilities electing
to comply with the PM emissions limit using a PM CEMS. We also proposed
to amend 40 CFR 60.104a(j) to delete the requirements to measure flow
for the H2S concentration limit for fuel gas.
Fifth, we proposed several amendments to clarify the requirements
for control device operating parameters in 40 CFR 60.105a.
Specifically, we proposed amendments to 40 CFR 60.105a(b)(1)(ii)(A) to
require corrective action be completed to repair faulty (leaking or
plugged) air or water lines within 12 hours of identification of an
abnormal pressure reading during the daily checks. We also proposed
revisions to 40 CFR 60.105a(i) to specify that periods when abnormal
pressure readings for a jet ejector-type wet scrubber (or other type of
wet scrubber equipped with atomizing spray nozzles) are not corrected
within 12 hours of identification and periods when a bag leak detection
system alarm (for a fabric filter) is not alleviated within the time
period specified in the rule are considered to be periods of excess
emissions.
We also proposed amendments to 40 CFR 60.105(b)(1)(iv) and
60.107a(b)(1)(iv) to provide flexibility in span range to accommodate
different manufacturers of the length-of-stain tubes. We also proposed
to delete the last sentence in 40 CFR 60.105(b)(3)(iii).
Finally, we proposed clarification to the performance test
requirements for the H2S concentration limit for affected
flares in 40 CFR 60.107a(e)(1)(ii) and (e)(2)(ii) to remove the
distinction between flares with or without routine flow.
2. How did the amendments to Refinery NSPS Subparts J and Ja change
since proposal?
We are making very few changes to the amendments proposed for
Refinery NSPS subparts J and Ja. In response to comments, we are
revising the NSPS requirements to replace the ``measurement
sensitivity'' requirements with accuracy requirements consistent with
those used in Refinery MACT 1 and 2. Specifically, we are revising 40
CFR 60.106a(a)(6)(i)(B) and (7)(i)(B) to require use of a flow sensor
meeting an accuracy requirement of 5-percent over the
normal range of flow measured or 10-cubic-feet-per-minute, whichever is
greater. We are also revising the flare accuracy requirements in 40 CFR
60.107a(f)(1)(ii) to require use of a flow sensor meeting an accuracy
requirement of 20-percent of the flow rate at velocities
ranging from 0.1 to 1 feet per second and an accuracy of 5-
percent of the flow rate for velocities greater than 1-feet-per-second.
Finally, we are revising 40 CFR 60.101a(b) to correct an
inadvertent error where the phrase ``and delayed coking units'' was not
included in the proposed sentence revision.
3. What key comments did we receive on the amendments to Refinery NSPS
Subparts J and Ja and what are our responses?
Comment: Two commenters noted concern with the term ``measurement
sensitivity'' in proposed 40 CFR 60.106a(a)(6)(i)(B) and (a)(7)(i)(B)
for sulfur recovery unit monitoring alternatives and in existing
regulations 40 CFR 60.107a(f)(1)(ii) for flares because ``sensitivity''
is not a term
[[Page 75225]]
found on typical monitoring system data sheets. Typical flow meter
characteristics include terms such as accuracy and resolution and the
commenters requested that the EPA revise the terminology to match the
wording found in 40 CFR part 63, subpart CC, Table 13 for flow meters
(i.e., accuracy requirements). Additionally, several commenters
suggested that the EPA flow monitor accuracy specifications are
inconsistent with those in the SCAQMD Flare Rule and many refinery
consent decrees. The commenters recommended revising both the flare
flow meter sensitivity specification and accuracy specification in
Refinery MACT 1 Table 13 and in Refinery NSPS subpart Ja to be
consistent with the accuracy specification from the Shell Deer Park
Consent Decree, Appendix 1.10, which specifies the required flare flow
meter accuracy as ``20% of reading over the velocity range
of 0.1-1 feet per second (ft/s) and 5% of reading over the
velocity range of 1-250 ft/s.''
Response: We proposed the term ``measurement sensitivity'' in
proposed 40 CFR 60.106a(a)(6)(i)(B) and (a)(7)(i)(B) to be internally
consistent within Refinery NSPS subpart Ja [i.e., consistent with the
existing language in Sec. 60.107a(f)(1)(ii)]. However, we agree with
the commenters that this term may be unclear. This term is not defined
in Refinery NSPS subpart Ja and it is not commonly used in the flow
monitoring system's technical specification sheets. Therefore, to be
consistent with the terminology used by instrument vendors and used in
Refinery MACT 1 and 2, we are revising these sections to replace the
term ``measurement sensitivity'' with ``accuracy.'' We are also
revising the flow rate accuracy provisions specific for flares to
provide an accuracy requirement of 20-percent over the
velocity range of 0.1-1 ft/s and 5% for velocities
exceeding 1 ft/s in 40 CFR 60.107a(f)(1)(ii) and in Table 13 of subpart
CC. We are providing this provision specifically for flares because
they commonly operate at high turndown ratios. For other flow
measurements, we are retaining the 10-cubic-foot-per-minute accuracy
requirement. We are also clarifying that the 5-percent
accuracy requirement for the SRU alternatives apply to the ``the normal
range of flow measured'' consistent with the requirements in Refinery
MACT 1 and 2.
Comment: One commenter stated that in the proposed revisions to 40
CFR 60.100a, (79 FR 36956), the EPA proposes to remove the phrase ``and
delayed coker units'' from 40 CFR 60.100a(b). However, we state the
compliance date for both flares and delayed coker units separately in
the same paragraph. The commenter believes the EPA should explain the
reason for and implications of the removal of this phrase.
Response: The removal of the phrase ``and delayed coking units''
from the first sentence in 40 CFR 60.100a(b) was an inadvertent error.
The only revision that we intended to make in 40 CFR 60.100a was to
allow owners or operators subject to subpart J to elect to comply with
the requirements in subpart Ja. In the final amendments, we have
included the phrase ``and delayed coking units'' in the first sentence
in 40 CFR 60.100a(b).
4. What is the rationale for our final approach and final decisions for
the amendments to Refinery NSPS Subparts J and Ja?
We are finalizing amendments for Refinery NSPS subparts J and Ja as
proposed with minor revisions. In response to comments, we are revising
the ``measurement sensitivity'' requirements to be an ``accuracy''
requirement. This change will make the requirements more clear and
consistent between the flow meter requirements in the NSPS and the MACT
standards since the same flow meter will be subject to each of these
requirements. We are also providing a dual accuracy requirement for
flare flow meters. This accuracy requirement is necessary because
flares, which can have large diameters to accommodate high flows, are
commonly operated at low flow rates. Together, this makes it
technically infeasible for many flares to meet the lower flow 10 cfm
accuracy requirement. Therefore, we are providing specific accuracy
requirements for flares of 20-percent over the velocity
range of 0.1-1 ft/s and 5-percent for velocities exceeding
1 ft/s, consistent with recent consent decrees and equipment vendor
specifications.
Finally, we are revising the introductory phrase in the first
sentence in 40 CFR 60.101a(b) to read ``Except for flares and delayed
coking units . . .'' to correct an inadvertent error. We intended to
revise this sentence only to include the proposed provision to allow
sources subject to Refinery NSPS subpart J to comply with Refinery NSPS
subpart Ja. The redline text posted on our Web site showed no revisions
to this introductory phrase, but the amendatory text did not include
the words ``and delayed coking units'' in this phrase. This was an
inadvertent error, which we are correcting in the final rule.
V. Summary of Cost, Environmental and Economic Impacts and Additional
Analyses Conducted
A. What are the affected facilities, the air quality impacts and cost
impacts?
The sources affected by significant amendments to the petroleum
refinery standards include flares, storage vessels, pressure relief
devices, fugitive emissions and DCU. The amendments for other sources
subject to one or more of the petroleum refinery standards are expected
to have minimal air quality and cost impacts.
The total capital investment cost of the final amendments and
standards is estimated at $283 million, $112 million from the final
amendments for storage vessels, DCU and fenceline monitoring and $171
million from standards to ensure compliance. We estimate annualized
costs of the final amendments for storage vessels, DCU and fenceline
monitoring to be approximately $13.0 million, which includes an
estimated $11.0 million for recovery of lost product and the annualized
cost of capital. We also estimated annualized costs of the final
standards to ensure compliance to be approximately $50.2 million. The
final amendments for storage vessels, DCU and fenceline monitoring
would achieve a nationwide HAP emission reduction of 1,323 tpy, with a
concurrent reduction in VOC emissions of 16,660 tpy and a reduction in
methane emissions of 8,700 metric tonnes per year. Table 2 of this
preamble summarizes the cost and emission reduction impacts of the
final amendments, and Table 3 of this preamble summarizes the costs of
the final standards to ensure compliance.
[[Page 75226]]
Table 2--Nationwide Impacts of Final Amendments (2010$)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Total
annualized Product Total Methane
Total cost recovery annualized emission VOC Cost HAP Cost
Affected source capital without credit costs reductions emission effectiveness emission effectiveness
investment credit (million $/ (million $/ (metric reductions ($/ton VOC) reductions ($/ton HAP)
(million $) (million $/ yr) yr) tpy) (tpy) (tpy)
yr)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Storage Vessels................ 18.5 3.13 (8.16) (5.03) ........... 14,600 (345) 910 (5,530)
Delayed Coking Units........... 81 14.5 (2.80) 11.7 8,700 2,060 5,680 413 28,330
Fugitive Emissions (Fenceline 12.5 6.36 ........... 6.36 ........... ........... ............. ........... .............
Monitoring)...................
------------------------------------------------------------------------------------------------------------------------
Total...................... 112 24.0 (11.0) 13.0 8,700 16,660 780 1,323 9,830
--------------------------------------------------------------------------------------------------------------------------------------------------------
Table 3--Nationwide Costs of Final Amendments To Ensure Compliance (2010$)
----------------------------------------------------------------------------------------------------------------
Total
Total capital annualized Product Total
Affected Source investment cost without recovery annualized
(million $) credit credit costs (million
(million $/yr) (million $/yr) $/yr)
----------------------------------------------------------------------------------------------------------------
Relief Device Monitoring........................ 11.1 3.3 .............. 3.3
Flare Monitoring................................ 160 46.5 .............. 46.5
FCCU Testing.................................... .............. 0.4 .............. 0.4
---------------------------------------------------------------
Total....................................... 171 50.2 .............. 50.2
----------------------------------------------------------------------------------------------------------------
The impacts shown in Table 2 do not include costs, product recovery
credits, or emissions reductions associated with any root cause
analysis or corrective action taken in response to the final amendments
for fenceline monitoring. The impacts shown in Table 3 do not include
(i) the costs or emissions reductions associated with any root cause
analysis and corrective action taken in response to the final source
performance testing at the FCCUs, or (ii) emissions reductions
associated with corrective action taken in response to pressure relief
device or (iii) emissions reductions associated with the flare
operating and monitoring provisions. The operational and monitoring
requirements for flares at refineries have the potential to reduce
excess emissions from flares by up to approximately 3,900 tpy of HAP
and 33,000 tpy of VOC. The operational and monitoring requirements for
flares also have the potential to reduce methane emissions by 25,800
metric tonnes per year while increasing emissions of carbon dioxide
(CO2) and nitrous oxide by 267,000 metric tonnes per year and 2 metric
tonnes per year, respectively, yielding a net reduction in GHG
emissions of 377,000 metric tonnes per year of CO2 equivalents
(CO2e).
B. What are the economic impacts?
We performed a national economic impact analysis for petroleum
product producers. All petroleum product refiners will incur annual
compliance costs of less than 1-percent of their sales. For all firms,
the minimum cost-to-sales ratio is <0.01-percent; the maximum cost-to-
sales ratio is 0.87-percent; and the mean cost-to-sales ratio is 0.03-
percent. Therefore, the overall economic impact of this proposed rule
should be minimal for the refining industry and its consumers.
In addition, the EPA performed a screening analysis for impacts on
small businesses by comparing estimated annualized engineering
compliance costs at the firm-level to firm sales. The screening
analysis found that the ratio of compliance cost to firm revenue falls
below 1-percent for the 28 small companies likely to be affected by the
proposal. For small firms, the minimum cost-to-sales ratio is <0.01-
percent; the maximum cost-to-sales ratio is 0.62-percent; and the mean
cost-to-sales ratio is 0.07-percent.
More information and details of this analysis is provided in the
technical document ``Economic Impact Analysis for Petroleum Refineries
Proposed Amendments to the National Emissions Standards for Hazardous
Air Pollutants'', which is available in the docket for this rule
(Docket ID No. EPA-HQ-OAR-2010-0682).
C. What are the benefits?
The final rule is anticipated to result in a reduction of 1,323 tpy
of HAP (based on allowable emissions under the MACT standards) and
16,660 tpy of VOC, not including potential emission reductions that may
occur as a result of the operating and monitoring requirements for
flares and fugitive emission sources via fenceline monitoring. These
avoided emissions will result in improvements in air quality and
reduced negative health effects associated with exposure to air
pollution of these emissions; however, we have not quantified or
monetized the benefits of reducing these emissions for this rulemaking.
D. Impacts of This Rulemaking on Environmental Justice Populations
To examine the potential impacts on vulnerable populations
(minority, low-income and indigenous communities) that might be
associated with the Petroleum Refinery source categories addressed in
this final rule, we evaluated the percentages of various social,
demographic and economic groups in the at-risk populations living near
the facilities where these sources are located and compared them to
national averages. Our analysis of the demographics of the population
with estimated risks greater than 1-in-1 million indicates potential
disparities in risks between demographic groups including the African
American, Other and Multiracial, Hispanic, Below the Poverty Level, and
Over 25 without a High School Diploma when compared to the nationwide
percentages of those groups. These groups will benefit the most from
the emission reductions achieved by this final rulemaking, which is
projected to result in 1 million fewer people exposed to risks greater
than 1-in-1 million.
Additionally, these communities will benefit from this rulemaking,
as this rulemaking for the first time ever requires fenceline
monitoring, and reporting of fenceline data. The agency during the pre-
proposal period and
[[Page 75227]]
during the comment period received feedback from communities on the
importance of having fenceline monitoring in their communities and the
importance of communities having access to this data. The EPA believes
that vulnerable communities will benefit from this data and the
requirements that EPA has put in place in this rulemaking to manage
fugitive emissions.
E. Impacts of This Rulemaking on Children's Health
Under Executive Order 13045 the EPA must evaluate the effects of
the planned regulation on children's health and safety. This action's
health and risk assessments are contained in section IV.A of this
preamble. We believe we have adequately estimated risk for children,
and we do not believe that the environmental health risks addressed by
this action present a disproportionate risk to children. When the EPA
derives exposure reference concentrations and unit risk estimates (URE)
for HAP, it also considers the most sensitive populations identified
(i.e., children) in the available literature, and importantly, these
are the values used in our risk assessments. With regard to children's
potentially greater susceptibility to non-cancer toxicants, the
assessments rely on the EPA (or comparable) hazard identification and
dose-response values which have been developed to be protective for all
subgroups of the general population, including children. With respect
to cancer, the EPA uses the age-dependent adjustment factor approach,
and applies these factors to carcinogenic pollutants that are known to
act via mutagenic mode of action. Further details are provided in the
``Final Residual Risk Assessment for the Petroleum Refining Source
Sector'', Docket ID No. EPA-HQ-OAR-2010-0682.
VI. Statutory and Executive Order Reviews
A. Executive Orders 12866: Regulatory Planning and Review and Executive
Order 13563: Improving Regulation and Regulatory Review
This action is an economically significant regulatory action that
was submitted to the Office of Management and Budget (OMB) for review.
Any changes made in response to OMB recommendations have been
documented in the docket. The EPA prepared an analysis of the potential
costs and benefits associated with this action. This analysis,
``Economic Impact Analysis: Petroleum Refineries--Final Amendments to
the National Emissions Standards for Hazardous Air Pollutants and New
Source Performance Standards'' is available in Docket ID Number EPA-HQ-
OAR-2010-0682.
B. Paperwork Reduction Act (PRA)
The information collection requirements in this rule have been
submitted for approval to the Office of Management and Budget (OMB)
under the Paperwork Reduction Act, 44 U.S.C. 3501 et se. The
information collection requirements are not enforceable until OMB
approves them.
Adequate recordkeeping and reporting are necessary to ensure
compliance with these standards as required by the CAA. The ICR
information collected from recordkeeping and reporting requirements is
also used for prioritizing inspections and is of sufficient quality to
be used as evidence in court.
The ICR document prepared by the EPA for the amendments to the
Petroleum Refinery MACT standards for 40 CFR part 63, subpart CC has
been assigned the EPA ICR number 1692.08. Burden changes associated
with these amendments would result from new monitoring, recordkeeping
and reporting requirements. The estimated annual increase in
recordkeeping and reporting burden hours is 99,722 hours; the frequency
of response is quarterly and semiannual for reports for all respondents
that must comply with the rule's reporting requirements; and the
estimated average number of likely respondents per year is 95 (this is
the average in the second year). The cost burden to respondents
resulting from the collection of information includes the total capital
cost annualized over the equipment's expected useful life (about $18
million, which includes monitoring equipment for fenceline monitoring,
pressure relief devices, and flares), a total operation and maintenance
component (about $21 million per year for fenceline and flare
monitoring), and a labor cost component (about $8.3 million per year,
the cost of the additional 99,722 labor hours). Burden is defined at 5
CFR 1320.3(b).
The ICR document prepared by the EPA for the amendments to the
Petroleum Refinery MACT standards for 40 CFR part 63, subpart UUU has
been assigned the EPA ICR number 1844.06. Burden changes associated
with these amendments would result from new testing, recordkeeping and
reporting requirements being finalized with this action. The estimated
average burden per response is 25 hours; the frequency of response
ranges from annually up to every 5 years for respondents that have
FCCU, and the estimated average number of likely respondents per year
is 67. The cost burden to respondents resulting from the collection of
information includes the performance testing costs (approximately
$778,000 per year over the first 3 years for the initial PM and one-
time HCN performance tests and $235,000 per year starting in the fourth
year), and a labor cost component (approximately $410,000 per year for
4,940 additional labor hours). Burden is defined at 5 CFR 1320.3(b).
An agency may not conduct or sponsor, and a person is not required
to respond to, a collection of information unless it displays a
currently valid OMB control number. The OMB control numbers for EPA's
regulations in 40 CFR are listed in 40 CFR part 9. When this ICR is
approved by OMB, the Agency will publish a technical amendment to 40
CFR part 9 in the Federal Register to display the OMB control number
for the approved information collection requirements contained in this
final rule.
C. Regulatory Flexibility Act (RFA)
I certify that this action will not have a significant economic
impact on a substantial number of small entities (SISNOSE) under the
RFA. The small entities subject to the requirements of this action are
small businesses, small organizations and small governmental
jurisdictions. For purposes of assessing the impacts of this rule on
small entities, a small entity is defined as: (1) A small business in
the petroleum refining industry having 1,500 or fewer employees (Small
Business Administration (SBA), 2011); (2) a small governmental
jurisdiction that is a government of a city, county, town, school
district or special district with a population of less than 50,000; and
(3) a small organization that is any not-for-profit enterprise which is
independently owned and operated and is not dominant in its field.
Details of this analysis are presented in the economic impact analysis
which can be found in the docket for this rule (Docket ID No. EPA-HQ-
OAR-2010-0682).
D. Unfunded Mandates Reform Act (UMRA)
This action does not contain an unfunded mandate of $100 million or
more as described in UMRA, 2 U.S.C. 1531-1538, and does not
significantly or uniquely affect small governments. As discussed
earlier in this preamble, these amendments result in nationwide costs
of $63.2 million per year for the private sector. Additionally, the
rule contains no requirements that apply to small
[[Page 75228]]
governments and does not impose obligations upon them.
E. Executive Order 13132: Federalism
This action does not have federalism implications. It will not have
substantial direct effects on the states, on the relationship between
the national government and the states, or on the distribution of power
and responsibilities among the various levels of government.
F. Executive Order 13175: Consultation and Coordination With Indian
Tribal Governments
This action does not have tribal implications, as specified in
Executive Order 13175. The final amendments impose no requirements on
tribal governments. Thus, Executive Order 13175 does not apply to this
action. Consistent with the EPA Policy on Consultation and Coordination
with Indian Tribes, the EPA consulted with tribal officials during the
development of the proposed rule and specifically solicited comment on
the proposed amendments from tribal officials.
G. Executive Order 13045: Protection of Children From Environmental
Health Risks and Safety Risks
This action is not subject to Executive Order 13045 because the EPA
does not believe the environmental health or safety risks addressed by
this action present a disproportionate risk to children. This action's
health and risk assessments are contained in section IV.A of this
preamble.
H. Executive Order 13211: Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution or Use
This action is not a ``significant energy action'' because it is
not likely to have a significant adverse effect on the supply,
distribution or use of energy. The overall economic impact of this
final rule should be minimal for the refining industry and its
consumers.
I. National Technology Transfer and Advancement Act (NTTAA) and 1 CFR
Part 51
This rulemaking involves technical standards. Therefore, the EPA
conducted searches for the Petroleum Refinery Sector Risk and
Technology Review and New Source Performance Standards through the
Enhanced National Standards Systems Network (NSSN) Database managed by
the American National Standards Institute (ANSI). We also contacted
voluntary consensus standards (VCS) organizations and accessed and
searched their databases. We conducted searches for EPA Methods 18, 22,
320, 325A, and 325B of 40 CFR parts 60 and 63, appendix A. No
applicable VCS were identified for EPA Method 22.
The following voluntary consensus standards were identified as
acceptable alternatives to the EPA test methods for the purpose of this
rule.
The voluntary consensus standard ISO 16017-2:2003(E) ``Air
quality--Sampling and analysis of volatile organic compounds in ambient
air, indoor air and workplace air by sorbent tube/thermal desorption/
capillary gas chromatography. Part 2: Diffusive sampling'' is an
acceptable alternative to Method 325A, Sections 1.2, 6.1 and 6.5 and
Method 325B Sections 1.3, 7.1.2, 7.1.3, 7.1.4, 12.2.4, 13.0, A.1.1, and
A.2. This voluntary consensus standard gives general guidance for the
sampling and analysis of volatile organic compounds in air. It is
applicable to indoor, ambient and workplace air. This standard is
available at International Organization for Standardization, ISO
Central Secretariat, Chemin de Blandonnet 8, CP 401, 1214 Vernier,
Geneva, Switzerland. See https://www.iso.org.
The voluntary consensus standard BS EN 14662-4:2005 ``Ambient Air
Quality: Standard Method for the Measurement of Benzene
Concentrations--Part 4: Diffusive Sampling Followed By Thermal
Desorption and Gas Chromatography'' is an acceptable alternative to
Method 325A, Section 1.2 and Method 325B, Sections 1.3, 7.1.3, 7.1.4,
12.2.4, 13.0, A.1.1, and A.2. This voluntary consensus standard gives
general guidance for the sampling and analysis of benzene in air by
diffusive sampling, thermal desorption and capillary gas
chromatography. This standard is available the European Committee for
Standardization, Avenue Marnix 17--B-1000 Brussels. See https://www.cen.eu.
The voluntary consensus standard ASTM D6420-99 (2010) ``Test Method
for Determination of Gaseous Organic Compounds by Direct Interface Gas
Chromatography/Mass Spectrometry'' is an acceptable alternative to EPA
Method 18. This voluntary consensus standard employs a direct interface
gas chromatography/mass spectrometer (GCMS) to identify and quantify a
list of 36 volatile organic compounds (the compounds are listed in the
method).
The voluntary consensus standard ASTM D6196-03 (Reapproved 2009)
``Standard Practice for Selection of Sorbents, Sampling, and Thermal
Desorption Analysis Procedures for Volatile Organic Compounds in Air''
is an acceptable alternative to Method 325A, Sections 1.2 and 6.1, and
Method 325B, Sections 1.3, 7.1.2, 7.1.3, 7.1.4, 13.0, A.1.1, and A.2.
This voluntary consensus standard is intended to assist in the
selection of sorbents and procedures for the sampling and analysis of
ambient, indoor, and workplace atmospheres for a variety of common
volatile organic compounds.
The voluntary consensus standards ASTM D1945-03 and later revision
ASTM D1945-14 ``Standard Test Method for Analysis of Natural Gas by Gas
Chromatography'' are acceptable for natural gas analysis. This
voluntary consensus standard covers the determination of the chemical
composition of natural gases and similar gaseous mixtures. This test
method may be abbreviated for the analysis of lean natural gases
containing negligible amounts of hexanes and higher hydrocarbons, or
for the determination of one or more components, as required.
The voluntary consensus standard ASTM UOP539-12 ``Refinery Gas
Analysis by GC'' is acceptable for refinery gas analysis. This
voluntary consensus standard is for determining the composition of
refinery gas streams or vaporized liquefied petroleum gas using a
preconfigured, commercially available gas chromatograph.
The voluntary consensus standard ASTM D6348-03 (Reapproved 2010)
including Annexes A1 through A8, ``Determination of Gaseous Compounds
by Extractive Direct Interface Fourier Transform (FTIR) Spectroscopy''
is an acceptable alternative to EPA Method 320. This voluntary
consensus standard is a field test method that employs an extractive
sampling system to direct stationary source effluent to an FTIR
spectrometer for the identification and quantification of gaseous
compounds. This field test method provides near real time analysis of
extracted gas samples from stationary sources.
The voluntary consensus standard ASTM D6348-12e1 ``Determination of
Gaseous Compounds by Extractive Direct Interface Fourier Transform
(FTIR) Spectroscopy'' is an acceptable alternative to EPA Method 320
with the following two caveats: (1) The test plan preparation and
implementation in the Annexes to ASTM D 6348-03 (Reapproved 2010),
Sections A1 through A8 are mandatory; and (2) In ASTM D6348-03
(Reapproved 2010) Annex A5 (Analyte Spiking Technique), the percent (%)
R must be determined for each target analyte (Equation A5.5). In order
for the test data to be acceptable for a compound, %R must be 70% >= R
<= 130%. If the %R value does not meet this criterion for a target
compound, the test data is not acceptable for that compound and the
test must be repeated
[[Page 75229]]
for that analyte (i.e., the sampling and/or analytical procedure should
be adjusted before a retest). The %R value for each compound must be
reported in the test report, and all field measurements must be
corrected with the calculated %R value for that compound by using the
following equation:
Reported Result = (Measured Concentration in the Stack x 100)/% R.
This voluntary consensus standard is a field test method that
employs an extractive sampling system to direct stationary source
effluent to an FTIR spectrometer for the identification and
quantification of gaseous compounds. This field test method provides
near real time analysis of extracted gas samples from stationary
sources.
The EPA solicited comments on VCS and invited the public to
identify potentially-applicable VCS; however, we did not receive
comments regarding this aspect of 40 CFR part 60, subparts J and Ja,
and part 63, subparts CC, UUU, and Y. Under 40 CFR 63.7(f) and 63.8(f),
a source may apply to the EPA for permission to use alternative test
methods or alternative monitoring requirements in place of any required
testing methods, performance specifications, or procedures in this
final rule.
J. Executive Order 12898: Federal Actions To Address Environmental
Justice in Minority Populations and Low-Income Populations
Executive Order 12898 (59 FR 7629; February 16, 1994) establishes
federal executive policy on environmental justice. Its main provision
directs federal agencies, to the greatest extent practicable and
permitted by law, to make environmental justice part of their mission
by identifying and addressing, as appropriate, disproportionately high
and adverse human health or environmental effects of their programs,
policies and activities on minority populations and low-income
populations in the U.S. The EPA defines environmental justice as the
fair treatment and meaningful involvement of all people regardless of
race, color, national origin or income with respect to the development,
implementation and enforcement of environmental laws, regulations and
policies. The EPA has this goal for all communities and persons by
working to ensure that everyone enjoys the same degree of protection
from environmental and health hazards and equal access to the decision-
making process to have a healthy environment in which to live, learn
and work.
The EPA believes the human health or environmental risk addressed
by this action will not have potential disproportionately high and
adverse human health or environmental effects on minority, low-income
or indigenous populations. As discussed in section V.D. of this
preamble, the EPA conducted an analysis of the characteristics of the
population with greater than 1-in-1 million risk living within 50 km of
the 142 refineries affected by this rulemaking and determined that
there are more African-Americans, Other and multiracial groups,
Hispanics, low-income individuals, individuals with less than a high
school diploma compared to national averages. Therefore, these
populations are expected to experience the benefits of the risk
reductions associated with this rule. The results of this evaluation
are contained in two technical reports, ``Risk and Technology Review--
Analysis of Socio-Economic Factors for Populations Living Near
Petroleum Refineries'', available in the docket for this action (See
Docket ID Nos. EPA-HQ-OAR-2010-0682-0226 and -0227). Additionally, a
discussion of the final risk analysis is included in Sections IV.A and
V.D of this preamble.
The EPA has determined that this final rule will not have
disproportionately high and adverse human health or environmental
effects on minority, low-income or indigenous populations because it
maintains or increases the level of environmental protection for all
affected populations without having any disproportionately high and
adverse human health or environmental effects on any population,
including any minority, low-income or indigenous populations. Further,
the EPA believes that implementation of this rule will provide an ample
margin of safety to protect public health of all demographic groups.
K. Congressional Review Act (CRA)
This action is subject to the CRA, and the EPA will submit a rule
report to each House of the Congress and to the Comptroller General of
the United States. This action is a ``major rule'' as defined by 5
U.S.C. 804(2).
List of Subjects
40 CFR Part 60
Environmental protection, Administrative practice and procedures,
Air pollution control, Hazardous substances, Incorporation by
reference, Intergovernmental relations, Reporting and recordkeeping
requirements.
40 CFR Part 63
Environmental protection, Administrative practice and procedures,
Air pollution control, Hazardous substances, Incorporation by
reference, Intergovernmental relations, Reporting and recordkeeping
requirements.
Dated: September 29, 2015.
Gina McCarthy,
Administrator.
For the reasons stated in the preamble, title 40, chapter I, of the
Code of Federal Regulations is amended as follows:
PART 60--STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES
0
1. The authority citation for part 60 continues to read as follows:
Authority: 42 U.S.C. 7401 et seq.
Subpart J--Standards of Performance for Petroleum Refineries
0
2. Section 60.105 is amended by revising paragraphs (b)(1)(iv) and
(b)(3)(iii) to read as follows:
Sec. 60.105 Monitoring of emissions and operations.
* * * * *
(b) * * *
(1) * * *
(iv) The supporting test results from sampling the requested fuel
gas stream/system demonstrating that the sulfur content is less than 5
ppmv. Sampling data must include, at minimum, 2 weeks of daily
monitoring (14 grab samples) for frequently operated fuel gas streams/
systems; for infrequently operated fuel gas streams/systems, seven grab
samples must be collected unless other additional information would
support reduced sampling. The owner or operator shall use detector
tubes (``length-of-stain tube'' type measurement) following the ``Gas
Processors Association Standard 2377-86 (incorporated by reference--see
Sec. 60.17), using tubes with a maximum span between 10 and 40 ppmv
inclusive when 1<=N<=10, where N = number of pump strokes, to test the
applicant fuel gas stream for H2S; and
* * * * *
(3) * * *
(iii) If the operation change results in a sulfur content that is
outside the range of concentrations included in the original
application and the owner or operator chooses not to submit new
information to support an exemption, the owner or operator must begin
H2S monitoring using daily stain sampling to demonstrate
compliance using length-of
[[Page 75230]]
stain tubes with a maximum span between 200 and 400 ppmv inclusive when
1<=N<=5, where N = number of pump strokes. The owner or operator must
begin monitoring according to the requirements in paragraph (a)(1) or
(2) of this section as soon as practicable but in no case later than
180 days after the operation change. During daily stain tube sampling,
a daily sample exceeding 162 ppmv is an exceedance of the 3-hour
H2S concentration limit.
* * * * *
Subpart Ja--Standards of Performance for Petroleum Refineries for
Which Construction, Reconstruction, or Modification Commenced After
May 14, 2007
0
3. Section 60.100a is amended by revising the first sentence of
paragraph (b) to read as follows:
Sec. 60.100a Applicability, designation of affected facility, and
reconstruction.
* * * * *
(b) Except for flares and delayed coking units, the provisions of
this subpart apply only to affected facilities under paragraph (a) of
this section which either commence construction, modification or
reconstruction after May 14, 2007, or elect to comply with the
provisions of this subpart in lieu of complying with the provisions in
subpart J of this part. * * *
* * * * *
0
4. Section 60.101a is amended by:
0
a. Revising the definition of ``Corrective action''; and
0
b. Adding, in alphabetical order, a definition for ``Sour water''.
The revision and addition read as follows:
Sec. 60.101a Definitions.
* * * * *
Corrective action means the design, operation and maintenance
changes that one takes consistent with good engineering practice to
reduce or eliminate the likelihood of the recurrence of the primary
cause and any other contributing cause(s) of an event identified by a
root cause analysis as having resulted in a discharge of gases from an
affected facility in excess of specified thresholds.
* * * * *
Sour water means water that contains sulfur compounds (usually
H2S) at concentrations of 10 parts per million by weight or
more.
* * * * *
0
5. Section 60.102a is amended by revising paragraphs (b)(1)(i) and
(iii), (f), and (g)(1) introductory text to read as follows:
Sec. 60.102a Emissions limitations.
* * * * *
(b) * * *
(1) * * *
(i) 1.0 gram per kilogram (g/kg) (1 pound (lb) per 1,000 lb) coke
burn-off or, if a PM continuous emission monitoring system (CEMS) is
used, 0.040 grain per dry standard cubic feet (gr/dscf) corrected to 0
percent excess air for each modified or reconstructed FCCU.
* * * * *
(iii) 1.0 g/kg (1 lb/1,000 lb) coke burn-off or, if a PM CEMS is
used, 0.040 grain per dry standard cubic feet (gr/dscf) corrected to 0
percent excess air for each affected FCU.
* * * * *
(f) Except as provided in paragraph (f)(3) of this section, each
owner or operator of an affected sulfur recovery plant shall comply
with the applicable emission limits in paragraph (f)(1) or (2) of this
section.
(1) For a sulfur recovery plant with a design production capacity
greater than 20 long tons per day (LTD), the owner or operator shall
comply with the applicable emission limit in paragraph (f)(1)(i) or
(ii) of this section. If the sulfur recovery plant consists of multiple
process trains or release points, the owner or operator shall comply
with the applicable emission limit for each process train or release
point individually or comply with the applicable emission limit in
paragraph (f)(1)(i) or (ii) as a flow rate weighted average for a group
of release points from the sulfur recovery plant provided that flow is
monitored as specified in Sec. 60.106a(a)(7); if flow is not monitored
as specified in Sec. 60.106a(a)(7), the owner or operator shall comply
with the applicable emission limit in paragraph (f)(1)(i) or (ii) for
each process train or release point individually. For a sulfur recovery
plant with a design production capacity greater than 20 long LTD and a
reduction control system not followed by incineration, the owner or
operator shall also comply with the H2S emission limit in
paragraph (f)(1)(iii) of this section for each individual release
point.
(i) For a sulfur recovery plant with an oxidation control system or
a reduction control system followed by incineration, the owner or
operator shall not discharge or cause the discharge of any gases into
the atmosphere (SO2) in excess of the emission limit
calculated using Equation 1 of this section. For Claus units that use
only ambient air in the Claus burner or that elect not to monitor
O2 concentration of the air/oxygen mixture used in the Claus
burner or for non-Claus sulfur recovery plants, this SO2
emissions limit is 250 ppmv (dry basis) at zero percent excess air.
[GRAPHIC] [TIFF OMITTED] TR01DE15.000
Where:
ELS = Emission limit for large sulfur recovery plant,
ppmv (as SO2, dry basis at zero percent excess air);
k1 = Constant factor for emission limit conversion:
k1 = 1 for converting to the SO2 limit for a
sulfur recovery plant with an oxidation control system or a
reduction control system followed by incineration and k1
= 1.2 for converting to the reduced sulfur compounds limit for a
sulfur recovery plant with a reduction control system not followed
by incineration; and
%O2 = O2 concentration of the air/oxygen
mixture supplied to the Claus burner, percent by volume (dry basis).
If only ambient air is used for the Claus burner or if the owner or
operator elects not to monitor O2 concentration of the
air/oxygen mixture used in the Claus burner or for non-Claus sulfur
recovery plants, use 20.9% for %O2.
(ii) For a sulfur recovery plant with a reduction control system
not followed by incineration, the owner or operator shall not discharge
or cause the discharge of any gases into the atmosphere containing
reduced sulfur compounds in excess of the emission limit calculated
using Equation 1 of this section. For Claus units that use only ambient
air in the Claus burner or for non-Claus sulfur recovery plants, this
reduced sulfur compounds emission limit is 300 ppmv calculated as ppmv
SO2 (dry basis) at 0-percent excess air.
(iii) For a sulfur recovery plant with a reduction control system
not followed by incineration, the owner or operator shall not discharge
or cause the discharge of any gases into the atmosphere containing
hydrogen sulfide (H2S) in excess of 10 ppmv calculated as
ppmv SO2 (dry basis) at zero percent excess air.
[[Page 75231]]
(2) For a sulfur recovery plant with a design production capacity
of 20 LTD or less, the owner or operator shall comply with the
applicable emission limit in paragraph (f)(2)(i) or (ii) of this
section. If the sulfur recovery plant consists of multiple process
trains or release points, the owner or operator may comply with the
applicable emission limit for each process train or release point
individually or comply with the applicable emission limit in paragraph
(f)(2)(i) or (ii) as a flow rate weighted average for a group of
release points from the sulfur recovery plant provided that flow is
monitored as specified in Sec. 60.106a(a)(7); if flow is not monitored
as specified in Sec. 60.106a(a)(7), the owner or operator shall comply
with the applicable emission limit in paragraph (f)(2)(i) or (ii) for
each process train or release point individually. For a sulfur recovery
plant with a design production capacity of 20 LTD or less and a
reduction control system not followed by incineration, the owner or
operator shall also comply with the H2S emission limit in
paragraph (f)(2)(iii) of this section for each individual release
point.
(i) For a sulfur recovery plant with an oxidation control system or
a reduction control system followed by incineration, the owner or
operator shall not discharge or cause the discharge of any gases into
the atmosphere containing SO2 in excess of the emission
limit calculated using Equation 2 of this section. For Claus units that
use only ambient air in the Claus burner or that elect not to monitor
O2 concentration of the air/oxygen mixture used in the Claus
burner or for non-Claus sulfur recovery plants, this SO2
emission limit is 2,500 ppmv (dry basis) at zero percent excess air.
[GRAPHIC] [TIFF OMITTED] TR01DE15.001
Where:
ESS = Emission limit for small sulfur recovery plant,
ppmv (as SO2, dry basis at zero percent excess air);
k1 = Constant factor for emission limit conversion:
k1 = 1 for converting to the SO2 limit for a
sulfur recovery plant with an oxidation control system or a
reduction control system followed by incineration and k1
= 1.2 for converting to the reduced sulfur compounds limit for a
sulfur recovery plant with a reduction control system not followed
by incineration; and
%O2 = O2 concentration of the air/oxygen
mixture supplied to the Claus burner, percent by volume (dry basis).
If only ambient air is used in the Claus burner or if the owner or
operator elects not to monitor O2 concentration of the
air/oxygen mixture used in the Claus burner or for non-Claus sulfur
recovery plants, use 20.9% for %O2.
(ii) For a sulfur recovery plant with a reduction control system
not followed by incineration, the owner or operator shall not discharge
or cause the discharge of any gases into the atmosphere containing
reduced sulfur compounds in excess of the emission limit calculated
using Equation 2 of this section. For Claus units that use only ambient
air in the Claus burner or for non-Claus sulfur recovery plants, this
reduced sulfur compounds emission limit is 3,000 ppmv calculated as
ppmv SO2 (dry basis) at zero percent excess air.
(iii) For a sulfur recovery plant with a reduction control system
not followed by incineration, the owner or operator shall not discharge
or cause the discharge of any gases into the atmosphere containing
H2S in excess of 100 ppmv calculated as ppmv SO2
(dry basis) at zero percent excess air.
(3) The emission limits in paragraphs (f)(1) and (2) of this
section shall not apply during periods of maintenance of the sulfur
pit, which shall not exceed 240 hours per year. The owner or operator
must document the time periods during which the sulfur pit vents were
not controlled and measures taken to minimize emissions during these
periods. Examples of these measures include not adding fresh sulfur or
shutting off vent fans.
(g) * * *
(1) Except as provided in (g)(1)(iii) of this section, for each
fuel gas combustion device, the owner or operator shall comply with
either the emission limit in paragraph (g)(1)(i) of this section or the
fuel gas concentration limit in paragraph (g)(1)(ii) of this section.
For CO boilers or furnaces that are part of a fluid catalytic cracking
unit or fluid coking unit affected facility, the owner or operator
shall comply with the fuel gas concentration limit in paragraph
(g)(1)(ii) for all fuel gas streams combusted in these units.
* * * * *
0
6. Section 60.104a is amended by:
0
a. Revising the first sentence of paragraph (a) and paragraphs (b), (f)
introductory text, and (h) introductory text;
0
b. Adding paragraph (h)(6); and
0
c. Removing and reserving paragraphs (j)(1) through (3).
The revisions and additions read as follows:
Sec. 60.104a Performance tests.
(a) The owner or operator shall conduct a performance test for each
FCCU, FCU, sulfur recovery plant and fuel gas combustion device to
demonstrate initial compliance with each applicable emissions limit in
Sec. 60.102a and conduct a performance test for each flare to
demonstrate initial compliance with the H2S concentration
requirement in Sec. 60.103a(h) according to the requirements of Sec.
60.8. * * *
(b) The owner or operator of a FCCU or FCU that elects to monitor
control device operating parameters according to the requirements in
Sec. 60.105a(b), to use bag leak detectors according to the
requirements in Sec. 60.105a(c), or to use COMS according to the
requirements in Sec. 60.105a(e) shall conduct a PM performance test at
least annually (i.e., once per calendar year, with an interval of at
least 8 months but no more than 16 months between annual tests) and
furnish the Administrator a written report of the results of each test.
* * * * *
(f) The owner or operator of an FCCU or FCU that uses cyclones to
comply with the PM per coke burn-off emissions limit in Sec.
60.102a(b)(1) shall establish a site-specific opacity operating limit
according to the procedures in paragraphs (f)(1) through (3) of this
section.
* * * * *
(h) The owner or operator shall determine compliance with the
SO2 emissions limits for sulfur recovery plants in Sec.
60.102a(f)(1)(i) and (f)(2)(i) and the reduced sulfur compounds and
H2S emissions limits for sulfur recovery plants in Sec.
60.102a(f)(1)(ii), (f)(1)(iii), (f)(2)(ii), and (f)(2)(iii) using the
following methods and procedures:
* * * * *
(6) If oxygen or oxygen-enriched air is used in the Claus burner
and either Equation 1 or 2 of this subpart is used to determine the
applicable emissions limit, determine the average O2
concentration of the air/oxygen mixture supplied to the Claus burner,
in percent by volume (dry basis), for the performance test using all
hourly average O2 concentrations determined
[[Page 75232]]
during the test runs using the procedures in Sec. 60.106a(a)(5) or
(6).
* * * * *
0
7. Section 60.105a is amended by:
0
a. Revising paragraphs (b)(1)(i), (b)(1)(ii)(A), (b)(2), (h)(1),
(h)(3)(i), and (i)(1);
0
b. Redesignating paragraphs (i)(2) through (6) as (i)(3) through (7);
0
c. Adding paragraph (i)(2); and
0
d. Revising newly redesignated paragraph (i)(7).
The revisions and additions read as follows:
Sec. 60.105a Monitoring of emissions and operations for fluid
catalytic cracking units (FCCU) and fluid coking units (FCU).
* * * * *
(b) * * *
(1) * * *
(i) For units controlled using an electrostatic precipitator, the
owner or operator shall use CPMS to measure and record the hourly
average total power input and secondary current to the entire system.
(ii) * * *
(A) As an alternative to pressure drop, the owner or operator of a
jet ejector type wet scrubber or other type of wet scrubber equipped
with atomizing spray nozzles must conduct a daily check of the air or
water pressure to the spray nozzles and record the results of each
check. Faulty (e.g., leaking or plugged) air or water lines must be
repaired within 12 hours of identification of an abnormal pressure
reading.
* * * * *
(2) For use in determining the coke burn-off rate for an FCCU or
FCU, the owner or operator shall install, operate, calibrate, and
maintain an instrument for continuously monitoring the concentrations
of CO2, O2 (dry basis), and if needed, CO in the
exhaust gases prior to any control or energy recovery system that burns
auxiliary fuels. A CO monitor is not required for determining coke
burn-off rate when no auxiliary fuel is burned and a continuous CO
monitor is not required in accordance with paragraph (h)(3) of this
section.
(i) The owner or operator shall install, operate, and maintain each
CO2 and O2 monitor according to Performance
Specification 3 of appendix B to this part.
(ii) The owner or operator shall conduct performance evaluations of
each CO2 and O2 monitor according to the
requirements in Sec. 60.13(c) and Performance Specification 3 of
appendix B to this part. The owner or operator shall use Method 3 of
appendix A-3 to this part for conducting the relative accuracy
evaluations.
(iii) If a CO monitor is required, the owner or operator shall
install, operate, and maintain each CO monitor according to Performance
Specification 4 or 4A of appendix B to this part. If this CO monitor
also serves to demonstrate compliance with the CO emissions limit in
Sec. 60.102a(b)(4), the span value for this instrument is 1,000 ppm;
otherwise, the span value for this instrument should be set at
approximately 2 times the typical CO concentration expected in the FCCU
of FCU flue gas prior to any emission control or energy recovery system
that burns auxiliary fuels.
(iv) If a CO monitor is required, the owner or operator shall
conduct performance evaluations of each CO monitor according to the
requirements in Sec. 60.13(c) and Performance Specification 4 of
appendix B to this part. The owner or operator shall use Method 10,
10A, or 10B of appendix A-3 to this part for conducting the relative
accuracy evaluations.
(v) The owner or operator shall comply with the quality assurance
requirements of procedure 1 of appendix F to this part, including
quarterly accuracy determinations for CO2 and CO monitors,
annual accuracy determinations for O2 monitors, and daily
calibration drift tests.
* * * * *
(h) * * *
(1) The owner or operator shall install, operate, and maintain each
CO monitor according to Performance Specification 4 or 4A of appendix B
to this part. The span value for this instrument is 1,000 ppmv CO.
* * * * *
(3) * * *
(i) The demonstration shall consist of continuously monitoring CO
emissions for 30 days using an instrument that meets the requirements
of Performance Specification 4 or 4A of appendix B to this part. The
span value shall be 100 ppmv CO instead of 1,000 ppmv, and the relative
accuracy limit shall be 10 percent of the average CO emissions or 5
ppmv CO, whichever is greater. For instruments that are identical to
Method 10 of appendix A-4 to this part and employ the sample
conditioning system of Method 10A of appendix A-4 to this part, the
alternative relative accuracy test procedure in section 10.1 of
Performance Specification 2 of appendix B to this part may be used in
place of the relative accuracy test.
* * * * *
(i) * * *
(1) If a CPMS is used according to paragraph (b)(1) of this
section, all 3-hour periods during which the average PM control device
operating characteristics, as measured by the continuous monitoring
systems under paragraph (b)(1), fall below the levels established
during the performance test. If the alternative to pressure drop CPMS
is used for the owner or operator of a jet ejector type wet scrubber or
other type of wet scrubber equipped with atomizing spray nozzles, each
day in which abnormal pressure readings are not corrected within 12
hours of identification.
(2) If a bag leak detection system is used according to paragraph
(c) of this section, each day in which the cause of an alarm is not
alleviated within the time period specified in paragraph (c)(3) of this
section.
* * * * *
(7) All 1-hour periods during which the average CO concentration as
measured by the CO continuous monitoring system under paragraph (h) of
this section exceeds 500 ppmv or, if applicable, all 1-hour periods
during which the average temperature and O2 concentration as
measured by the continuous monitoring systems under paragraph (h)(4) of
this section fall below the operating limits established during the
performance test.
0
8. Section 60.106a is amended by:
0
a. Revising paragraph (a)(1)(i);
0
b. Adding paragraphs (a)(1)(iv) through (vii);
0
c. Revising paragraphs (a)(2) introductory text, (a)(2)(i) and (ii),
and the first sentence of paragraph (a)(2)(iii);
0
d. Removing paragraphs (a)(2)(iv) and (v);
0
e. Redesignating paragraphs (a)(2)(vi) through (ix) as (a)(2)(iv)
through (vii);
0
f. Revising the first sentence of paragraph (a)(3) introductory text
and paragraph (a)(3)(i);
0
g. Adding paragraphs (a)(4) through (7); and
0
h. Revising paragraphs (b)(2) and (3).
The revisions and additions read as follows:
Sec. 60.106a Monitoring of emissions and operations for sulfur
recovery plants.
(a) * * *
(1) * * *
(i) The span value for the SO2 monitor is two times the
applicable SO2 emission limit at the highest O2
concentration in the air/oxygen stream used in the Claus burner, if
applicable.
* * * * *
(iv) The owner or operator shall install, operate, and maintain
each O2 monitor according to Performance Specification 3 of
appendix B to this part.
(v) The span value for the O2 monitor must be selected
between 10 and 25 percent, inclusive.
[[Page 75233]]
(vi) The owner or operator shall conduct performance evaluations
for the O2 monitor according to the requirements of Sec.
60.13(c) and Performance Specification 3 of appendix B to this part.
The owner or operator shall use Methods 3, 3A, or 3B of appendix A-2 to
this part for conducting the relative accuracy evaluations. The method
ANSI/ASME PTC 19.10-1981 (incorporated by reference--see Sec. 60.17)
is an acceptable alternative to EPA Method 3B of appendix A-2 to this
part.
(vii) The owner or operator shall comply with the applicable
quality assurance procedures of appendix F to this part for each
monitor, including annual accuracy determinations for each
O2 monitor, and daily calibration drift determinations.
(2) For sulfur recovery plants that are subject to the reduced
sulfur compounds emission limit in Sec. 60.102a(f)(1)(ii) or
(f)(2)(ii), the owner or operator shall install, operate, calibrate,
and maintain an instrument for continuously monitoring and recording
the concentration of reduced sulfur compounds and O2
emissions into the atmosphere. The reduced sulfur compounds emissions
shall be calculated as SO2 (dry basis, zero percent excess
air).
(i) The span value for the reduced sulfur compounds monitor is two
times the applicable reduced sulfur compounds emission limit as
SO2 at the highest O2 concentration in the air/
oxygen stream used in the Claus burner, if applicable.
(ii) The owner or operator shall install, operate, and maintain
each reduced sulfur compounds CEMS according to Performance
Specification 5 of appendix B to this part.
(iii) The owner or operator shall conduct performance evaluations
of each reduced sulfur compounds monitor according to the requirements
in Sec. 60.13(c) and Performance Specification 5 of appendix B to this
part. * * *
* * * * *
(3) In place of the reduced sulfur compounds monitor required in
paragraph (a)(2) of this section, the owner or operator may install,
calibrate, operate, and maintain an instrument using an air or
O2 dilution and oxidation system to convert any reduced
sulfur to SO2 for continuously monitoring and recording the
concentration (dry basis, 0 percent excess air) of the total resultant
SO2. * * *
(i) The span value for this monitor is two times the applicable
reduced sulfur compounds emission limit as SO2 at the
highest O2 concentration in the air/oxygen stream used in
the Claus burner, if applicable.
* * * * *
(4) For sulfur recovery plants that are subject to the
H2S emission limit in Sec. 60.102a(f)(1)(iii) or
(f)(2)(iii), the owner or operator shall install, operate, calibrate,
and maintain an instrument for continuously monitoring and recording
the concentration of H2S, and O2 emissions into
the atmosphere. The H2S emissions shall be calculated as
SO2 (dry basis, zero percent excess air).
(i) The span value for this monitor is two times the applicable
H2S emission limit.
(ii) The owner or operator shall install, operate, and maintain
each H2S CEMS according to Performance Specification 7 of
appendix B to this part.
(iii) The owner or operator shall conduct performance evaluations
for each H2S monitor according to the requirements of Sec.
60.13(c) and Performance Specification 7 of appendix B to this part.
The owner or operator shall use Methods 11 or 15 of appendix A-5 to
this part or Method 16 of appendix A-6 to this part for conducting the
relative accuracy evaluations. The method ANSI/ASME PTC 19.10-1981
(incorporated by reference--see Sec. 60.17) is an acceptable
alternative to EPA Method 15A of appendix A-5 to this part.
(iv) The owner or operator shall install, operate, and maintain
each O2 monitor according to Performance Specification 3 of
appendix B to this part.
(v) The span value for the O2 monitor must be selected
between 10 and 25 percent, inclusive.
(vi) The owner or operator shall conduct performance evaluations
for the O2 monitor according to the requirements of Sec.
60.13(c) and Performance Specification 3 of appendix B to this part.
The owner or operator shall use Methods 3, 3A, or 3B of appendix A-2 to
this part for conducting the relative accuracy evaluations. The method
ANSI/ASME PTC 19.10-1981 (incorporated by reference--see Sec. 60.17)
is an acceptable alternative to EPA Method 3B of appendix A-2 to this
part.
(vii) The owner or operator shall comply with the applicable
quality assurance procedures of appendix F to this part for each
monitor, including annual accuracy determinations for each
O2 monitor, and daily calibration drift determinations.
(5) For sulfur recovery plants that use oxygen or oxygen enriched
air in the Claus burner and that elects to monitor O2
concentration of the air/oxygen mixture supplied to the Claus burner,
the owner or operator shall install, operate, calibrate, and maintain
an instrument for continuously monitoring and recording the
O2 concentration of the air/oxygen mixture supplied to the
Claus burner in order to determine the allowable emissions limit.
(i) The owner or operator shall install, operate, and maintain each
O2 monitor according to Performance Specification 3 of
appendix B to this part.
(ii) The span value for the O2 monitor shall be 100
percent.
(iii) The owner or operator shall conduct performance evaluations
for the O2 monitor according to the requirements of Sec.
60.13(c) and Performance Specification 3 of appendix B to this part.
The owner or operator shall use Methods 3, 3A, or 3B of appendix A-2 to
this part for conducting the relative accuracy evaluations. The method
ANSI/ASME PTC 19.10-1981 (incorporated by reference--see Sec. 60.17)
is an acceptable alternative to EPA Method 3B of appendix A-2 to this
part.
(iv) The owner or operator shall comply with the applicable quality
assurance procedures of appendix F to this part for each monitor,
including annual accuracy determinations for each O2
monitor, and daily calibration drift determinations.
(v) The owner or operator shall use the hourly average
O2 concentration from this monitor for use in Equation 1 or
2 of Sec. 60.102a(f), as applicable, for each hour and determine the
allowable emission limit as the arithmetic average of 12 contiguous 1-
hour averages (i.e., the rolling 12-hour average).
(6) As an alternative to the O2 monitor required in
paragraph (a)(5) of this section, the owner or operator may install,
calibrate, operate, and maintain a CPMS to measure and record the
volumetric gas flow rate of ambient air and oxygen-enriched gas
supplied to the Claus burner and calculate the hourly average
O2 concentration of the air/oxygen mixture used in the Claus
burner as specified in paragraphs (a)(6)(i) through (iv) of this
section in order to determine the allowable emissions limit as
specified in paragraphs (a)(6)(v) of this section.
(i) The owner or operator shall install, calibrate, operate and
maintain each flow monitor according to the manufacturer's procedures
and specifications and the following requirements.
(A) Locate the monitor in a position that provides a representative
measurement of the total gas flow rate.
[[Page 75234]]
(B) Use a flow sensor meeting an accuracy requirement of 5 percent over the normal range of flow measured or 10 cubic feet
per minute, whichever is greater.
(C) Use a flow monitor that is maintainable online, is able to
continuously correct for temperature, pressure and, for ambient air
flow monitor, moisture content, and is able to record dry flow in
standard conditions (as defined in Sec. 60.2) over one-minute
averages.
(D) At least quarterly, perform a visual inspection of all
components of the monitor for physical and operational integrity and
all electrical connections for oxidation and galvanic corrosion if the
flow monitor is not equipped with a redundant flow sensor.
(E) Recalibrate the flow monitor in accordance with the
manufacturer's procedures and specifications biennially (every two
years) or at the frequency specified by the manufacturer.
(ii) The owner or operator shall use 20.9 percent as the oxygen
content of the ambient air.
(iii) The owner or operator shall use product specifications (e.g.,
as reported in material safety data sheets) for percent oxygen for
purchased oxygen. For oxygen produced onsite, the percent oxygen shall
be determined by periodic measurements or process knowledge.
(iv) The owner or operator shall calculate the hourly average
O2 concentration of the air/oxygen mixture used in the Claus
burner using Equation 10 of this section:
[GRAPHIC] [TIFF OMITTED] TR01DE15.002
Where:
%O2 = O2 concentration of the air/oxygen
mixture used in the Claus burner, percent by volume (dry basis);
20.9 = O2 concentration in air, percent dry basis;
Qair = Volumetric flow rate of ambient air used in the
Claus burner, dscfm;
%O2,oxy = O2 concentration in the enriched
oxygen stream, percent dry basis; and
Qoxy = Volumetric flow rate of enriched oxygen stream
used in the Claus burner, dscfm.
(v) The owner or operator shall use the hourly average
O2 concentration determined using Equation 8 of Sec.
60.104a(d)(8) for use in Equation 1 or 2 of Sec. 60.102a(f), as
applicable, for each hour and determine the allowable emission limit as
the arithmetic average of 12 contiguous 1-hour averages (i.e., the
rolling 12-hour average).
(7) Owners or operators of a sulfur recovery plant that elects to
comply with the SO2 emission limit in Sec. 60.102a(f)(1)(i)
or (f)(2)(i) or the reduced sulfur compounds emission limit in Sec.
60.102a(f)(1)(ii) or (f)(2)(ii) as a flow rate weighted average for a
group of release points from the sulfur recovery plant rather than for
each process train or release point individually shall install,
calibrate, operate, and maintain a CPMS to measure and record the
volumetric gas flow rate of each release point within the group of
release points from the sulfur recovery plant as specified in
paragraphs (a)(7)(i) through (iv) of this section.
(i) The owner or operator shall install, calibrate, operate and
maintain each flow monitor according to the manufacturer's procedures
and specifications and the following requirements.
(A) Locate the monitor in a position that provides a representative
measurement of the total gas flow rate.
(B) Use a flow sensor meeting an accuracy requirement of 5 percent over the normal range of flow measured or 10 cubic feet
per minute, whichever is greater.
(C) Use a flow monitor that is maintainable online, is able to
continuously correct for temperature, pressure, and moisture content,
and is able to record dry flow in standard conditions (as defined in
Sec. 60.2) over one-minute averages.
(D) At least quarterly, perform a visual inspection of all
components of the monitor for physical and operational integrity and
all electrical connections for oxidation and galvanic corrosion if the
flow monitor is not equipped with a redundant flow sensor.
(E) Recalibrate the flow monitor in accordance with the
manufacturer's procedures and specifications biennially (every two
years) or at the frequency specified by the manufacturer.
(ii) The owner or operator shall correct the flow to 0 percent
excess air using Equation 11 of this section:
[GRAPHIC] [TIFF OMITTED] TR01DE15.003
Where:
Qadj = Volumetric flow rate adjusted to 0 percent excess
air, dry standard cubic feet per minute (dscfm);
Cmeas = Volumetric flow rate measured by the flow meter
corrected to dry standard conditions, dscfm;
20.9c = 20.9 percent O2-0.0 percent
O2 (defined O2 correction basis), percent;
20.9 = O2 concentration in air, percent; and
%O2 = O2 concentration measured on a dry
basis, percent.
(iii) The owner or operator shall calculate the flow weighted
average SO2 or reduced sulfur compounds concentration for
each hour using Equation 12 of this section:
[GRAPHIC] [TIFF OMITTED] TR01DE15.004
[[Page 75235]]
Where:
Cave = Flow weighted average concentration of the
pollutant, ppmv (dry basis, zero percent excess air). The pollutant
is either SO2 (if complying with the SO2
emission limit in Sec. 60.102a(f)(1)(i) or (f)(2)(i)) or reduced
sulfur compounds (if complying with the reduced sulfur compounds
emission limit in Sec. 60.102a(f)(1)(ii) or (f)(2)(ii));
N = Number of release points within the group of release points from
the sulfur recovery plant for which emissions averaging is elected;
Cn = Pollutant concentration in the nth
release point within the group of release points from the sulfur
recovery plant for which emissions averaging is elected, ppmv (dry
basis, zero percent excess air);
Qadj,n = Volumetric flow rate of the nth
release point within the group of release points from the sulfur
recovery plant for which emissions averaging is elected, dry
standard cubic feet per minute (dscfm, adjusted to 0 percent excess
air).
(iv) For sulfur recovery plants that use oxygen or oxygen enriched
air in the Claus burner, the owner or operator shall use Equation 10 of
this section and the hourly emission limits determined in paragraph
(a)(5)(v) or (a)(6)(v) of this section in-place of the pollutant
concentration to determine the flow weighted average hourly emission
limit for each hour. The allowable emission limit shall be calculated
as the arithmetic average of 12 contiguous 1-hour averages (i.e., the
rolling 12-hour average).
(b) * * *
(2) All 12-hour periods during which the average concentration of
reduced sulfur compounds (as SO2) as measured by the reduced
sulfur compounds continuous monitoring system required under paragraph
(a)(2) or (3) of this section exceeds the applicable emission limit; or
(3) All 12-hour periods during which the average concentration of
H2S as measured by the H2S continuous monitoring
system required under paragraph (a)(4) of this section exceeds the
applicable emission limit (dry basis, 0 percent excess air).
0
9. Section 60.107a is amended by revising paragraphs (a)(1)(i) and
(ii), (b)(1)(iv), the first sentence of paragraph (b)(3)(iii), (d)(3),
(e)(1) introductory text, (e)(1)(ii), (e)(2) introductory text,
(e)(2)(ii), (e)(2)(vi)(C), (e)(3), (f)(1)(ii), and (h)(5) to read as
follows:
Sec. 60.107a Monitoring of emissions and operations for fuel gas
combustion devices and flares.
(a) * * *
(1) * * *
(i) The owner or operator shall install, operate, and maintain each
SO2 monitor according to Performance Specification 2 of
appendix B to this part. The span value for the SO2 monitor
is 50 ppmv SO2.
(ii) The owner or operator shall conduct performance evaluations
for the SO2 monitor according to the requirements of Sec.
60.13(c) and Performance Specification 2 of appendix B to this part.
The owner or operator shall use Methods 6, 6A, or 6C of appendix A-4 to
this part for conducting the relative accuracy evaluations. The method
ANSI/ASME PTC 19.10-1981 (incorporated by reference--see Sec. 60.17)
is an acceptable alternative to EPA Method 6 or 6A of appendix A-4 to
this part. Samples taken by Method 6 of appendix A-4 to this part shall
be taken at a flow rate of approximately 2 liters/min for at least 30
minutes. The relative accuracy limit shall be 20 percent or 4 ppmv,
whichever is greater, and the calibration drift limit shall be 5
percent of the established span value.
* * * * *
(b) * * *
(1) * * *
(iv) The supporting test results from sampling the requested fuel
gas stream/system demonstrating that the sulfur content is less than 5
ppmv H2S. Sampling data must include, at minimum, 2 weeks of
daily monitoring (14 grab samples) for frequently operated fuel gas
streams/systems; for infrequently operated fuel gas streams/systems,
seven grab samples must be collected unless other additional
information would support reduced sampling. The owner or operator shall
use detector tubes (``length-of-stain tube'' type measurement)
following the ``Gas Processors Association Standard 2377-86
(incorporated by reference--see Sec. 60.17), using tubes with a
maximum span between 10 and 40 ppmv inclusive when 1<=N<=10, where N =
number of pump strokes, to test the applicant fuel gas stream for
H2S; and
* * * * *
(3) * * *
(iii) If the operation change results in a sulfur content that is
outside the range of concentrations included in the original
application and the owner or operator chooses not to submit new
information to support an exemption, the owner or operator must begin
H2S monitoring using daily stain sampling to demonstrate
compliance using length-of-stain tubes with a maximum span between 200
and 400 ppmv inclusive when 1<=N<=5, where N = number of pump strokes.
* * *
* * * * *
(d) * * *
(3) As an alternative to the requirements in paragraph (d)(2) of
this section, the owner or operator of a gas-fired process heater shall
install, operate and maintain a gas composition analyzer and determine
the average F factor of the fuel gas using the factors in Table 1 of
this subpart and Equation 13 of this section. If a single fuel gas
system provides fuel gas to several process heaters, the F factor may
be determined at a single location in the fuel gas system provided it
is representative of the fuel gas fed to the affected process
heater(s).
[GRAPHIC] [TIFF OMITTED] TR01DE15.005
Where:
Fd = F factor on dry basis at 0% excess air, dscf/MMBtu.
Xi = mole or volume fraction of each component in the
fuel gas.
MEVi = molar exhaust volume, dry standard cubic feet
per mole (dscf/mol).
MHCi = molar heat content, Btu per mole (Btu/mol).
1,000,000 = unit conversion, Btu per MMBtu.
* * * * *
(e) * * *
(1) Total reduced sulfur monitoring requirements. The owner or
operator shall install, operate, calibrate and maintain an instrument
or instruments for continuously monitoring and recording the
concentration of total reduced sulfur in gas discharged to the flare.
* * * * *
(ii) The owner or operator shall conduct performance evaluations of
each total reduced sulfur monitor according to the requirements in
Sec. 60.13(c) and Performance Specification 5 of appendix B to this
part. The owner or operator of each total
[[Page 75236]]
reduced sulfur monitor shall use EPA Method 15A of appendix A-5 to this
part for conducting the relative accuracy evaluations. The method ANSI/
ASME PTC 19.10-1981 (incorporated by reference-see Sec. 60.17) is an
acceptable alternative to EPA Method 15A of appendix A-5 to this part.
The alternative relative accuracy procedures described in section 16.0
of Performance Specification 2 of appendix B to this part (cylinder gas
audits) may be used for conducting the relative accuracy evaluations,
except that it is not necessary to include as much of the sampling
probe or sampling line as practical.
* * * * *
(2) H2S monitoring requirements. The owner or operator shall
install, operate, calibrate, and maintain an instrument or instruments
for continuously monitoring and recording the concentration of
H2S in gas discharged to the flare according to the
requirements in paragraphs (e)(2)(i) through (iii) of this section and
shall collect and analyze samples of the gas and calculate total sulfur
concentrations as specified in paragraphs (e)(2)(iv) through (ix) of
this section.
* * * * *
(ii) The owner or operator shall conduct performance evaluations of
each H2S monitor according to the requirements in Sec.
60.13(c) and Performance Specification 7 of appendix B to this part.
The owner or operator shall use EPA Method 11, 15 or 15A of appendix A-
5 to this part for conducting the relative accuracy evaluations. The
method ANSI/ASME PTC 19.10-1981 (incorporated by reference--see Sec.
60.17) is an acceptable alternative to EPA Method 15A of appendix A-5
to this part. The alternative relative accuracy procedures described in
section 16.0 of Performance Specification 2 of appendix B to this part
(cylinder gas audits) may be used for conducting the relative accuracy
evaluations, except that it is not necessary to include as much of the
sampling probe or sampling line as practical.
* * * * *
(vi) * * *
(C) Determine the acceptable range for subsequent weekly samples
based on the 95-percent confidence interval for the distribution of
daily ratios based on the 10 individual daily ratios using Equation 14
of this section.
[GRAPHIC] [TIFF OMITTED] TR01DE15.006
Where:
AR = Acceptable range of subsequent ratio determinations,
unitless.
RatioAvg = 10-day average total sulfur-to-
H2S concentration ratio, unitless.
2.262 = t-distribution statistic for 95-percent 2-sided
confidence interval for 10 samples (9 degrees of freedom).
SDev = Standard deviation of the 10 daily average total sulfur-
to-H2S concentration ratios used to develop the 10-day
average total sulfur-to-H2S concentration ratio,
unitless.
* * * * *
(3) SO2 monitoring requirements. The owner or operator shall
install, operate, calibrate, and maintain an instrument for
continuously monitoring and recording the concentration of
SO2 from a process heater or other fuel gas combustion
device that is combusting gas representative of the fuel gas in the
flare gas line according to the requirements in paragraph (a)(1) of
this section, determine the F factor of the fuel gas at least daily
according to the requirements in paragraphs (d)(2) through (4) of this
section, determine the higher heating value of the fuel gas at least
daily according to the requirements in paragraph (d)(7) of this
section, and calculate the total sulfur content (as SO2) in
the fuel gas using Equation 15 of this section.
[GRAPHIC] [TIFF OMITTED] TR01DE15.007
Where:
TSFG = Total sulfur concentration, as SO2,
in the fuel gas, ppmv.
CSO2 = Concentration of SO2 in the exhaust
gas, ppmv (dry basis at 0-percent excess air).
Fd = F factor gas on dry basis at 0-percent excess
air, dscf/MMBtu.
HHVFG = Higher heating value of the fuel gas, MMBtu/
scf.
* * * * *
(f) * * *
(1) * * *
(ii) Use a flow sensor meeting an accuracy requirement of 20 percent of the flow rate at velocities ranging from 0.1 to 1
feet per second and an accuracy of 5 percent of the flow
rate for velocities greater than 1 feet per second.
* * * * *
(h) * * *
(5) Daily O2 limits for fuel gas combustion devices. Each day
during which the concentration of O2 as measured by the
O2 continuous monitoring system required under paragraph
(c)(6) or (d)(8) of this section exceeds the O2 operating
limit or operating curve determined during the most recent biennial
performance test.
PART 63--NATIONAL EMISSION STANDARDS FOR HAZARDOUS AIR POLLUTANTS
FOR SOURCE CATEGORIES
0
10. The authority citation for part 63 continues to read as follows:
Authority: 42 U.S.C. 7401 et se.
Subpart A--General Provisions
0
11. Section 63.14 is amended by:
0
a. Revising paragraph (h)(14);
0
b. Redesignating paragraphs (h)(82) through (99) as (h)(86) through
(103), paragraphs (h)(77) through (81) as (h)(80) through (84),
paragraphs (h)(73) through (76) as paragraphs (h)(75) through (78), and
paragraphs (h)(15) through (72) as (16) through (73), respectively;
0
c. Revising newly redesignated paragraph (h)(78);
0
d. Adding paragraphs (h)(15), (74), (79), (85), (104) and (j)(2);
0
e. Redesignating paragraph (m)(3) through (21) as (m)(5) through (23),
respectively, and paragraph (m)(2) as (m)(3).
0
f. Adding paragraphs (m)(2) and (4) and (n)(3); and
0
g. Revising paragraph (s)(1).
The revisions and additions read as follows:
Sec. 63.14 Incorporation by reference.
* * * * *
(h) * * *
(14) ASTM D1945-03 (Reapproved 2010), Standard Test Method for
Analysis of Natural Gas by Gas Chromatography, Approved January 1,
2010, IBR approved for Sec. Sec. 63.670(j), 63.772(h), and 63.1282(g).
(15) ASTM D1945-14, Standard Test Method for Analysis of Natural
Gas by Gas Chromatography, Approved
[[Page 75237]]
November 1, 2014, IBR approved for Sec. 63.670(j).
* * * * *
(74) ASTM D6196-03 (Reapproved 2009), Standard Practice for
Selection of Sorbents, Sampling, and Thermal Desorption Analysis
Procedures for Volatile Organic Compounds in Air, Approved March 1,
2009, IBR approved for appendix A to this part: Method 325A and Method
325B.
* * * * *
(78) ASTM D6348-03 (Reapproved 2010), Standard Test Method for
Determination of Gaseous Compounds by Extractive Direct Interface
Fourier Transform Infrared (FTIR) Spectroscopy, including Annexes A1
through A8, Approved October 1, 2010, IBR approved for Sec.
63.1571(a), tables 4 and 5 to subpart JJJJJ, tables 4 and 6 to subpart
KKKKK, tables 1, 2, and 5 to subpart UUUUU and appendix B to subpart
UUUUU.
* * * * *
(79) ASTM D6348-12e1, Standard Test Method for Determination of
Gaseous Compounds by Extractive Direct Interface Fourier Transform
Infrared (FTIR) Spectroscopy, Approved February 1, 2012, IBR approved
for Sec. 63.1571(a).
* * * * *
(85) ASTM D6420-99 (Reapproved 2010), Standard Test Method for
Determination of Gaseous Organic Compounds by Direct Interface Gas
Chromatography-Mass Spectrometry, Approved October 1, 2010, IBR
approved for Sec. 63.670(j) and appendix A to this part: Method 325B.
* * * * *
(104) ASTM UOP539-12, Refinery Gas Analysis by GC, Copyright 2012
(to UOP), IBR approved for Sec. 63.670(j).
* * * * *
(j) * * *
(2) BS EN 14662-4:2005, Ambient air quality standard method for the
measurement of benzene concentrations--Part 4: Diffusive sampling
followed by thermal desorption and gas chromatography, Published June
27, 2005, IBR approved for appendix A to this part: Method 325A and
Method 325B.
* * * * *
(m) * * *
(2) EPA-454/B-08-002, Office of Air Quality Planning and Standards
(OAQPS), Quality Assurance Handbook for Air Pollution Measurement
Systems, Volume IV: Meteorological Measurements, Version 2.0 (Final),
March 24, 2008, IBR approved for Sec. 63.658(d) and appendix A to this
part: Method 325A.
* * * * *
(4) EPA-454/R-99-005, Office of Air Quality Planning and Standards
(OAQPS), Meteorological Monitoring Guidance for Regulatory Modeling
Applications, February 2000, IBR approved for appendix A to this part:
Method 325A.
* * * * *
(n) * * *
(3) ISO 16017-2:2003(E): Indoor, ambient and workplace air--
sampling and analysis of volatile organic compounds by sorbent tube/
thermal desorption/capillary gas chromatography--Part 2: Diffusive
sampling, May 15, 2003, IBR approved for appendix A to this part:
Method 325A and Method 325B.
* * * * *
(s) * * *
(1) ``Air Stripping Method (Modified El Paso Method) for
Determination of Volatile Organic Compound Emissions from Water
Sources,'' Revision Number One, dated January 2003, Sampling Procedures
Manual, Appendix P: Cooling Tower Monitoring, January 31, 2003, IBR
approved for Sec. Sec. 63.654(c) and (g), 63.655(i), and 63.11920.
* * * * *
Subpart Y--National Emission Standards for Marine Tank Vessel
Loading Operations
0
12. Section 63.560 is amended by revising paragraph (a)(4) to read as
follows:
Sec. 63.560 Applicability and designation of affected source.
(a) * * *
(4) Existing sources with emissions less than 10 and 25 tons must
meet the submerged fill standards of 46 CFR 153.282.
* * * * *
Subpart CC--National Emission Standards for Hazardous Air
Pollutants From Petroleum Refineries
0
13. Section 63.640 is amended by:
0
a. Revising paragraphs (a) introductory text and (c) introductory text;
0
c. Adding paragraph (c)(9);
0
d. Revising paragraphs (d)(5), (h), (k)(1), (l) introductory text,
(l)(2) introductory text, (l)(2)(i), (l)(3) introductory text, (m)
introductory text, (n) introductory text, (n)(1) through (5), (n)(8)
introductory text, and (n)(8)(ii);
0
e. Adding paragraphs (n)(8)(vii) and (viii);
0
f. Revising paragraph (n)(9)(i);
0
g. Adding paragraph (n)(10);
0
h. Revising paragraph (o)(2)(i) introductory text;
0
i. Adding paragraph (o)(2)(i)(D);
0
j. Revising paragraph (o)(2)(ii) introductory text; and
0
k. Adding paragraphs (o)(2)(ii)(C) and (s).
The revisions and additions read as follows:
Sec. 63.640 Applicability and designation of affected source.
(a) This subpart applies to petroleum refining process units and to
related emissions points that are specified in paragraphs (c)(1)
through (9) of this section that are located at a plant site and that
meet the criteria in paragraphs (a)(1) and (2) of this section:
* * * * *
(c) For the purposes of this subpart, the affected source shall
comprise all emissions points, in combination, listed in paragraphs
(c)(1) through (9) of this section that are located at a single
refinery plant site.
* * * * *
(9) All releases associated with the decoking operations of a
delayed coking unit, as defined in this subpart.
(d) * * *
(5) Emission points routed to a fuel gas system, as defined in
Sec. 63.641, provided that on and after January 30, 2019, any flares
receiving gas from that fuel gas system are subject to Sec. 63.670. No
other testing, monitoring, recordkeeping, or reporting is required for
refinery fuel gas systems or emission points routed to refinery fuel
gas systems.
* * * * *
(h) Sources subject to this subpart are required to achieve
compliance on or before the dates specified in table 11 of this
subpart, except as provided in paragraphs (h)(1) through (3) of this
section.
(1) Marine tank vessels at existing sources shall be in compliance
with this subpart, except for Sec. Sec. 63.657 through 63.660, no
later than August 18, 1999, unless the vessels are included in an
emissions average to generate emission credits. Marine tank vessels
used to generate credits in an emissions average shall be in compliance
with this subpart no later than August 18, 1998, unless an extension
has been granted by the Administrator as provided in Sec. 63.6(i).
(2) Existing Group 1 floating roof storage vessels meeting the
applicability criteria in item 1 of the definition of Group 1 storage
vessel shall be in compliance with Sec. 63.646 at the first degassing
and cleaning activity after August 18, 1998, or August 18, 2005,
whichever is first.
[[Page 75238]]
(3) An owner or operator may elect to comply with the provisions of
Sec. 63.648(c) through (i) as an alternative to the provisions of
Sec. 63.648(a) and (b). In such cases, the owner or operator shall
comply no later than the dates specified in paragraphs (h)(3)(i)
through (iii) of this section.
(i) Phase I (see table 2 of this subpart), beginning on August 18,
1998;
(ii) Phase II (see table 2 of this subpart), beginning no later
than August 18, 1999; and
(iii) Phase III (see table 2 of this subpart), beginning no later
than February 18, 2001.
* * * * *
(k) * * *
(1) The reconstructed source, addition, or change shall be in
compliance with the new source requirements in item (1), (2), or (3) of
table 11 of this subpart, as applicable, upon initial startup of the
reconstructed source or by August 18, 1995, whichever is later; and
* * * * *
(l) If an additional petroleum refining process unit is added to a
plant site or if a miscellaneous process vent, storage vessel, gasoline
loading rack, marine tank vessel loading operation, heat exchange
system, or decoking operation that meets the criteria in paragraphs
(c)(1) through (9) of this section is added to an existing petroleum
refinery or if another deliberate operational process change creating
an additional Group 1 emissions point(s) (as defined in Sec. 63.641)
is made to an existing petroleum refining process unit, and if the
addition or process change is not subject to the new source
requirements as determined according to paragraph (i) or (j) of this
section, the requirements in paragraphs (l)(1) through (4) of this
section shall apply. Examples of process changes include, but are not
limited to, changes in production capacity, or feed or raw material
where the change requires construction or physical alteration of the
existing equipment or catalyst type, or whenever there is replacement,
removal, or addition of recovery equipment. For purposes of this
paragraph (l) and paragraph (m) of this section, process changes do not
include: Process upsets, unintentional temporary process changes, and
changes that are within the equipment configuration and operating
conditions documented in the Notification of Compliance Status report
required by Sec. 63.655(f).
* * * * *
(2) The added emission point(s) and any emission point(s) within
the added or changed petroleum refining process unit shall be in
compliance with the applicable requirements in item (4) of table 11 of
this subpart by the dates specified in paragraph (l)(2)(i) or (ii) of
this section.
(i) If a petroleum refining process unit is added to a plant site
or an emission point(s) is added to any existing petroleum refining
process unit, the added emission point(s) shall be in compliance upon
initial startup of any added petroleum refining process unit or
emission point(s) or by the applicable compliance date in item (4) of
table 11 of this subpart, whichever is later.
* * * * *
(3) The owner or operator of a petroleum refining process unit or
of a storage vessel, miscellaneous process vent, wastewater stream,
gasoline loading rack, marine tank vessel loading operation, heat
exchange system, or decoking operation meeting the criteria in
paragraphs (c)(1) through (9) of this section that is added to a plant
site and is subject to the requirements for existing sources shall
comply with the reporting and recordkeeping requirements that are
applicable to existing sources including, but not limited to, the
reports listed in paragraphs (l)(3)(i) through (vii) of this section. A
process change to an existing petroleum refining process unit shall be
subject to the reporting requirements for existing sources including,
but not limited to, the reports listed in paragraphs (l)(3)(i) through
(vii) of this section. The applicable reports include, but are not
limited to:
* * * * *
(m) If a change that does not meet the criteria in paragraph (l) of
this section is made to a petroleum refining process unit subject to
this subpart, and the change causes a Group 2 emission point to become
a Group 1 emission point (as defined in Sec. 63.641), then the owner
or operator shall comply with the applicable requirements of this
subpart for existing sources, as specified in item (4) of table 11 of
this subpart, for the Group 1 emission point as expeditiously as
practicable, but in no event later than 3 years after the emission
point becomes Group 1.
* * * * *
(n) Overlap of this subpart with other regulations for storage
vessels. As applicable, paragraphs (n)(1), (3), (4), (6), and (7) of
this section apply for Group 2 storage vessels and paragraphs (n)(2)
and (5) of this section apply for Group 1 storage vessels.
(1) After the compliance dates specified in paragraph (h) of this
section, a Group 2 storage vessel that is subject to the provisions of
40 CFR part 60, subpart Kb, is required to comply only with the
requirements of 40 CFR part 60, subpart Kb, except as provided in
paragraph (n)(8) of this section. After the compliance dates specified
in paragraph (h) of this section, a Group 2 storage vessel that is
subject to the provisions of 40 CFR part 61, subpart Y, is required to
comply only with the requirements of 40 CFR part 61, subpart Y, except
as provided in paragraph (n)(10) of this section.
(2) After the compliance dates specified in paragraph (h) of this
section, a Group 1 storage vessel that is also subject to 40 CFR part
60, subpart Kb, is required to comply only with either 40 CFR part 60,
subpart Kb, except as provided in paragraph (n)(8) of this section or
this subpart. After the compliance dates specified in paragraph (h) of
this section, a Group 1 storage vessel that is also subject to 40 CFR
part 61, subpart Y, is required to comply only with either 40 CFR part
61, subpart Y, except as provided in paragraph (n)(10) of this section
or this subpart.
(3) After the compliance dates specified in paragraph (h) of this
section, a Group 2 storage vessel that is part of a new source and is
subject to 40 CFR 60.110b, but is not required to apply controls by 40
CFR 60.110b or 60.112b, is required to comply only with this subpart.
(4) After the compliance dates specified in paragraph (h) of this
section, a Group 2 storage vessel that is part of a new source and is
subject to 40 CFR 61.270, but is not required to apply controls by 40
CFR 61.271, is required to comply only with this subpart.
(5) After the compliance dates specified in paragraph (h) of this
section, a Group 1 storage vessel that is also subject to the
provisions of 40 CFR part 60, subpart K or Ka, is required to only
comply with the provisions of this subpart.
* * * * *
(8) Storage vessels described by paragraph (n)(1) of this section
are to comply with 40 CFR part 60, subpart Kb, except as provided in
paragraphs (n)(8)(i) through (vi) of this section. Storage vessels
described by paragraph (n)(2) electing to comply with part 60, subpart
Kb of this chapter shall comply with subpart Kb except as provided in
paragraphs (n)(8)(i) through (viii) of this section.
* * * * *
(ii) If the owner or operator determines that it is unsafe to
perform the seal gap measurements required in Sec. 60.113b(b) of this
chapter or to inspect the vessel to determine compliance with
[[Page 75239]]
Sec. 60.113b(a) of this chapter because the roof appears to be
structurally unsound and poses an imminent danger to inspecting
personnel, the owner or operator shall comply with the requirements in
either Sec. 63.120(b)(7)(i) or (ii) of subpart G (only up to the
compliance date specified in paragraph (h) of this section for
compliance with Sec. 63.660, as applicable) or either Sec.
63.1063(c)(2)(iv)(A) or (B) of subpart WW.
* * * * *
(vii) To be in compliance with Sec. 60.112b(a)(1)(iv) or
(a)(2)(ii) of this chapter, guidepoles in floating roof storage vessels
must be equipped with covers and/or controls (e.g., pole float system,
pole sleeve system, internal sleeve system or flexible enclosure
system) as appropriate to comply with the ``no visible gap''
requirement.
(viii) If a flare is used as a control device for a storage vessel,
on and after January 30, 2019, the owner or operator must meet the
requirements of Sec. 63.670 instead of the requirements referenced
from part 60, subpart Kb of this chapter for that flare.
(9) * * *
(i) If the owner or operator determines that it is unsafe to
perform the seal gap measurements required in Sec. 60.113a(a)(1) of
this chapter because the floating roof appears to be structurally
unsound and poses an imminent danger to inspecting personnel, the owner
or operator shall comply with the requirements in either Sec.
63.120(b)(7)(i) or (ii) of subpart G (only up to the compliance date
specified in paragraph (h) of this section for compliance with Sec.
63.660, as applicable) or either Sec. 63.1063(c)(2)(iv)(A) or (B) of
subpart WW.
* * * * *
(10) Storage vessels described by paragraph (n)(1) of this section
are to comply with 40 CFR part 61, subpart Y, except as provided in
paragraphs (n)(10)(i) through (vi) of this section. Storage vessels
described by paragraph (n)(2) electing to comply with 40 CFR part 61,
subpart Y, shall comply with subpart Y except as provided for in
paragraphs (n)(10)(i) through (viii) of this section.
(i) Storage vessels that are to comply with Sec. 61.271(b) of this
chapter are exempt from the secondary seal requirements of Sec.
61.271(b)(2)(ii) of this chapter during the gap measurements for the
primary seal required by Sec. 61.272(b) of this chapter.
(ii) If the owner or operator determines that it is unsafe to
perform the seal gap measurements required in Sec. 61.272(b) of this
chapter or to inspect the vessel to determine compliance with Sec.
61.272(a) of this chapter because the roof appears to be structurally
unsound and poses an imminent danger to inspecting personnel, the owner
or operator shall comply with the requirements in either Sec.
63.120(b)(7)(i) or (ii) of subpart G (only up to the compliance date
specified in paragraph (h) of this section for compliance with Sec.
63.660, as applicable) or either Sec. 63.1063(c)(2)(iv)(A) or (B) of
subpart WW.
(iii) If a failure is detected during the inspections required by
Sec. 61.272(a)(2) of this chapter or during the seal gap measurements
required by Sec. 61.272(b)(1) of this chapter, and the vessel cannot
be repaired within 45 days and the vessel cannot be emptied within 45
days, the owner or operator may utilize up to two extensions of up to
30 additional calendar days each. The owner or operator is not required
to provide a request for the extension to the Administrator.
(iv) If an extension is utilized in accordance with paragraph
(n)(10)(iii) of this section, the owner or operator shall, in the next
periodic report, identify the vessel, provide the information listed in
Sec. 61.272(a)(2) or (b)(4)(iii) of this chapter, and describe the
nature and date of the repair made or provide the date the storage
vessel was emptied.
(v) Owners and operators of storage vessels complying with 40 CFR
part 61, subpart Y, may submit the inspection reports required by Sec.
61.275(a), (b)(1), and (d) of this chapter as part of the periodic
reports required by this subpart, rather than within the 60-day period
specified in Sec. 61.275(a), (b)(1), and (d) of this chapter.
(vi) The reports of rim seal inspections specified in Sec.
61.275(d) of this chapter are not required if none of the measured gaps
or calculated gap areas exceed the limitations specified in Sec.
61.272(b)(4) of this chapter. Documentation of the inspections shall be
recorded as specified in Sec. 61.276(a) of this chapter.
(vii) To be in compliance with Sec. 61.271(a)(6) or (b)(3) of this
chapter, guidepoles in floating roof storage vessels must be equipped
with covers and/or controls (e.g., pole float system, pole sleeve
system, internal sleeve system or flexible enclosure system) as
appropriate to comply with the ``no visible gap'' requirement.
(viii) If a flare is used as a control device for a storage vessel,
on and after January 30, 2019, the owner or operator must meet the
requirements of Sec. 63.670 instead of the requirements referenced
from part 61, subpart Y of this chapter for that flare.
(o) * * *
(2) * * *
(i) Comply with paragraphs (o)(2)(i)(A) through (D) of this
section.
* * * * *
(D) If a flare is used as a control device, on and after January
30, 2019, the flare shall meet the requirements of Sec. 63.670. Prior
to January 30, 2019, the flare shall meet the applicable requirements
of 40 CFR part 61, subpart FF, and subpart G of this part, or the
requirements of Sec. 63.670.
(ii) Comply with paragraphs (o)(2)(ii)(A) through (C) of this
section.
* * * * *
(C) If a flare is used as a control device, on and after January
30, 2019, the flare shall meet the requirements of Sec. 63.670. Prior
to January 30, 2019, the flare shall meet the applicable requirements
of 40 CFR part 61, subpart FF, and subpart G of this part, or the
requirements of Sec. 63.670.
* * * * *
(s) Overlap of this subpart with other regulation for flares. On
January 30, 2019, flares that are subject to the provisions of 40 CFR
60.18 or 63.11 and subject to this subpart are required to comply only
with the provisions specified in this subpart. Prior to January 30,
2019, flares that are subject to the provisions of 40 CFR 60.18 or
63.11 and elect to comply with the requirements in Sec. Sec. 63.670
and 63.671 are required to comply only with the provisions specified in
this subpart.
0
14. Section 63.641 is amended by:
0
a. Adding, in alphabetical order, definitions of ``Assist air,''
``Assist steam,'' ``Center steam,'' ``Closed blowdown system,''
``Combustion zone,'' ``Combustion zone gas,'' ``Decoking operations,''
``Delayed coking unit,'' ``Flare,'' ``Flare purge gas,'' ``Flare
supplemental gas,'' ``Flare sweep gas,'' ``Flare vent gas,'' ``Flexible
enclosure device,'' ``Force majeure event,'' ``Lower steam,'' ``Net
heating value,'' ``Perimeter assist air,'' ``Pilot gas,'' ``Premix
assist air,'' ``Regulated material,'' ``Thermal expansion relief
valve,'' ``Total steam,'' and ``Upper steam''; and
0
b. Revising the definitions of ``Delayed coker vent,'' ``Emission
point,'' ``Group 1 storage vessel,'' ``Miscellaneous process vent,''
``Periodically discharged,'' and ``Reference control technology for
storage vessels.''
The revisions and additions read as follows:
Sec. 63.641 Definitions.
* * * * *
Assist air means all air that intentionally is introduced prior to
or at
[[Page 75240]]
a flare tip through nozzles or other hardware conveyance for the
purposes including, but not limited to, protecting the design of the
flare tip, promoting turbulence for mixing or inducing air into the
flame. Assist air includes premix assist air and perimeter assist air.
Assist air does not include the surrounding ambient air.
Assist steam means all steam that intentionally is introduced prior
to or at a flare tip through nozzles or other hardware conveyance for
the purposes including, but not limited to, protecting the design of
the flare tip, promoting turbulence for mixing or inducing air into the
flame. Assist steam includes, but is not necessarily limited to, center
steam, lower steam and upper steam.
* * * * *
Center steam means the portion of assist steam introduced into the
stack of a flare to reduce burnback.
Closed blowdown system means a system used for depressuring process
vessels that is not open to the atmosphere and is configured of piping,
ductwork, connections, accumulators/knockout drums, and, if necessary,
flow inducing devices that transport gas or vapor from process vessel
to a control device or back into the process.
* * * * *
Combustion zone means the area of the flare flame where the
combustion zone gas combines for combustion.
Combustion zone gas means all gases and vapors found just after a
flare tip. This gas includes all flare vent gas, total steam, and
premix air.
* * * * *
Decoking operations means the sequence of steps conducted at the
end of the delayed coking unit's cooling cycle to open the coke drum to
the atmosphere in order to remove coke from the coke drum. Decoking
operations begin at the end of the cooling cycle when steam released
from the coke drum is no longer discharged via the unit's blowdown
system but instead is vented directly to the atmosphere. Decoking
operations include atmospheric depressuring (venting), deheading,
draining, and decoking (coke cutting).
Delayed coker vent means a miscellaneous process vent that contains
uncondensed vapors from the delayed coking unit's blowdown system.
Venting from the delayed coker vent is typically intermittent in
nature, and occurs primarily during the cooling cycle of a delayed
coking unit coke drum when vapor from the coke drums cannot be sent to
the fractionator column for product recovery. The emissions from the
decoking operations, which include direct atmospheric venting,
deheading, draining, or decoking (coke cutting), are not considered to
be delayed coker vents.
Delayed coking unit means a refinery process unit in which high
molecular weight petroleum derivatives are thermally cracked and
petroleum coke is produced in a series of closed, batch system
reactors. A delayed coking unit includes, but is not limited to, all of
the coke drums associated with a single fractionator; the fractionator,
including the bottoms receiver and the overhead condenser; the coke
drum cutting water and quench system, including the jet pump and coker
quench water tank; and the coke drum blowdown recovery compressor
system.
* * * * *
Emission point means an individual miscellaneous process vent,
storage vessel, wastewater stream, equipment leak, decoking operation
or heat exchange system associated with a petroleum refining process
unit; an individual storage vessel or equipment leak associated with a
bulk gasoline terminal or pipeline breakout station classified under
Standard Industrial Classification code 2911; a gasoline loading rack
classified under Standard Industrial Classification code 2911; or a
marine tank vessel loading operation located at a petroleum refinery.
* * * * *
Flare means a combustion device lacking an enclosed combustion
chamber that uses an uncontrolled volume of ambient air to burn gases.
For the purposes of this rule, the definition of flare includes, but is
not necessarily limited to, air-assisted flares, steam-assisted flares
and non-assisted flares.
Flare purge gas means gas introduced between a flare header's water
seal and the flare tip to prevent oxygen infiltration (backflow) into
the flare tip. For a flare with no water seal, the function of flare
purge gas is performed by flare sweep gas and, therefore, by
definition, such a flare has no flare purge gas.
Flare supplemental gas means all gas introduced to the flare in
order to improve the combustible characteristics of combustion zone
gas.
Flare sweep gas means, for a flare with a flare gas recovery
system, the gas intentionally introduced into the flare header system
to maintain a constant flow of gas through the flare header in order to
prevent oxygen buildup in the flare header; flare sweep gas in these
flares is introduced prior to and recovered by the flare gas recovery
system. For a flare without a flare gas recovery system, flare sweep
gas means the gas intentionally introduced into the flare header system
to maintain a constant flow of gas through the flare header and out the
flare tip in order to prevent oxygen buildup in the flare header and to
prevent oxygen infiltration (backflow) into the flare tip.
Flare vent gas means all gas found just prior to the flare tip.
This gas includes all flare waste gas (i.e., gas from facility
operations that is directed to a flare for the purpose of disposing of
the gas), that portion of flare sweep gas that is not recovered, flare
purge gas and flare supplemental gas, but does not include pilot gas,
total steam or assist air.
Flexible enclosure device means a seal made of an elastomeric
fabric (or other material) which completely encloses a slotted
guidepole or ladder and eliminates the vapor emission pathway from
inside the storage vessel through the guidepole slots or ladder slots
to the outside air.
* * * * *
Force majeure event means a release of HAP, either directly to the
atmosphere from a relief valve or discharged via a flare, that is
demonstrated to the satisfaction of the Administrator to result from an
event beyond the refinery owner or operator's control, such as natural
disasters; acts of war or terrorism; loss of a utility external to the
refinery (e.g., external power curtailment), excluding power
curtailment due to an interruptible service agreement; and fire or
explosion originating at a near or adjoining facility outside of the
refinery owner or operator's control that impacts the refinery's
ability to operate.
* * * * *
Group 1 storage vessel means:
(1) Prior to February 1, 2016:
(i) A storage vessel at an existing source that has a design
capacity greater than or equal to 177 cubic meters and stored-liquid
maximum true vapor pressure greater than or equal to 10.4 kilopascals
and stored-liquid annual average true vapor pressure greater than or
equal to 8.3 kilopascals and annual average HAP liquid concentration
greater than 4 percent by weight total organic HAP;
(ii) A storage vessel at a new source that has a design storage
capacity greater than or equal to 151 cubic meters and stored-liquid
maximum true vapor pressure greater than or equal to 3.4 kilopascals
and annual average HAP liquid concentration greater than 2 percent by
weight total organic HAP; or
(iii) A storage vessel at a new source that has a design storage
capacity greater than or equal to 76 cubic meters and less than 151
cubic meters and stored-
[[Page 75241]]
liquid maximum true vapor pressure greater than or equal to 77
kilopascals and annual average HAP liquid concentration greater than 2
percent by weight total organic HAP.
(2) On and after February 1, 2016:
(i) A storage vessel at an existing source that has a design
capacity greater than or equal to 151 cubic meters (40,000 gallons) and
stored-liquid maximum true vapor pressure greater than or equal to 5.2
kilopascals (0.75 pounds per square inch) and annual average HAP liquid
concentration greater than 4 percent by weight total organic HAP;
(ii) A storage vessel at an existing source that has a design
storage capacity greater than or equal to 76 cubic meters (20,000
gallons) and less than 151 cubic meters (40,000 gallons) and stored-
liquid maximum true vapor pressure greater than or equal to 13.1
kilopascals (1.9 pounds per square inch) and annual average HAP liquid
concentration greater than 4 percent by weight total organic HAP;
(iii) A storage vessel at a new source that has a design storage
capacity greater than or equal to 151 cubic meters (40,000 gallons) and
stored-liquid maximum true vapor pressure greater than or equal to 3.4
kilopascals (0.5 pounds per square inch) and annual average HAP liquid
concentration greater than 2 percent by weight total organic HAP; or
(iv) A storage vessel at a new source that has a design storage
capacity greater than or equal to 76 cubic meters (20,000 gallons) and
less than 151 cubic meters (40,000 gallons) and stored-liquid maximum
true vapor pressure greater than or equal to 13.1 kilopascals (1.9
pounds per square inch) and annual average HAP liquid concentration
greater than 2 percent by weight total organic HAP.
* * * * *
Lower steam means the portion of assist steam piped to an exterior
annular ring near the lower part of a flare tip, which then flows
through tubes to the flare tip, and ultimately exits the tubes at the
flare tip.
* * * * *
Miscellaneous process vent means a gas stream containing greater
than 20 parts per million by volume organic HAP that is continuously or
periodically discharged from a petroleum refining process unit meeting
the criteria specified in Sec. 63.640(a). Miscellaneous process vents
include gas streams that are discharged directly to the atmosphere, gas
streams that are routed to a control device prior to discharge to the
atmosphere, or gas streams that are diverted through a product recovery
device prior to control or discharge to the atmosphere. Miscellaneous
process vents include vent streams from: Caustic wash accumulators,
distillation tower condensers/accumulators, flash/knockout drums,
reactor vessels, scrubber overheads, stripper overheads, vacuum pumps,
steam ejectors, hot wells, high point bleeds, wash tower overheads,
water wash accumulators, blowdown condensers/accumulators, and delayed
coker vents. Miscellaneous process vents do not include:
(1) Gaseous streams routed to a fuel gas system, provided that on
and after January 30, 2019, any flares receiving gas from the fuel gas
system are in compliance with Sec. 63.670;
(2) Pressure relief device discharges;
(3) Leaks from equipment regulated under Sec. 63.648;
(4) [Reserved]
(5) In situ sampling systems (onstream analyzers) until January 30,
2019. After this date, these sampling systems will be included in the
definition of miscellaneous process vents;
(6) Catalytic cracking unit catalyst regeneration vents;
(7) Catalytic reformer regeneration vents;
(8) Sulfur plant vents;
(9) Vents from control devices such as scrubbers, boilers,
incinerators, and electrostatic precipitators applied to catalytic
cracking unit catalyst regeneration vents, catalytic reformer
regeneration vents, and sulfur plant vents;
(10) Vents from any stripping operations applied to comply with the
wastewater provisions of this subpart, subpart G of this part, or 40
CFR part 61, subpart FF;
(11) Emissions associated with delayed coking unit decoking
operations;
(12) Vents from storage vessels;
(13) Emissions from wastewater collection and conveyance systems
including, but not limited to, wastewater drains, sewer vents, and sump
drains; and
(14) Hydrogen production plant vents through which carbon dioxide
is removed from process streams or through which steam condensate
produced or treated within the hydrogen plant is degassed or deaerated.
Net heating value means the energy released as heat when a compound
undergoes complete combustion with oxygen to form gaseous carbon
dioxide and gaseous water (also referred to as lower heating value).
* * * * *
Perimeter assist air means the portion of assist air introduced at
the perimeter of the flare tip or above the flare tip. Perimeter assist
air includes air intentionally entrained in lower and upper steam.
Perimeter assist air includes all assist air except premix assist air.
Periodically discharged means discharges that are intermittent and
associated with routine operations, maintenance activities, startups,
shutdowns, malfunctions, or process upsets.
* * * * *
Pilot gas means gas introduced into a flare tip that provides a
flame to ignite the flare vent gas.
* * * * *
Premix assist air means the portion of assist air that is
introduced to the flare vent gas, whether injected or induced, prior to
the flare tip. Premix assist air also includes any air intentionally
entrained in center steam.
* * * * *
Reference control technology for storage vessels means either:
(1) For Group 1 storage vessels complying with Sec. 63.660:
(i) An internal floating roof, including an external floating roof
converted to an internal floating roof, meeting the specifications of
Sec. 63.1063(a)(1)(i) and (b);
(ii) An external floating roof meeting the specifications of Sec.
63.1063(a)(1)(ii), (a)(2), and (b); or
(iii) [Reserved]
(iv) A closed-vent system to a control device that reduces organic
HAP emissions by 95 percent, or to an outlet concentration of 20 parts
per million by volume (ppmv).
(v) For purposes of emissions averaging, these four technologies
are considered equivalent.
(2) For all other storage vessels:
(i) An internal floating roof meeting the specifications of Sec.
63.119(b) of subpart G except for Sec. 63.119(b)(5) and (6);
(ii) An external floating roof meeting the specifications of Sec.
63.119(c) of subpart G except for Sec. 63.119(c)(2);
(iii) An external floating roof converted to an internal floating
roof meeting the specifications of Sec. 63.119(d) of subpart G except
for Sec. 63.119(d)(2); or
(iv) A closed-vent system to a control device that reduces organic
HAP emissions by 95 percent, or to an outlet concentration of 20 parts
per million by volume.
(v) For purposes of emissions averaging, these four technologies
are considered equivalent.
* * * * *
Regulated material means any stream associated with emission
sources listed
[[Page 75242]]
in Sec. 63.640(c) required to meet control requirements under this
subpart as well as any stream for which this subpart or a cross-
referencing subpart specifies that the requirements for flare control
devices in Sec. 63.670 must be met.
* * * * *
Thermal expansion relief valve means a pressure relief valve
designed to protect equipment from excess pressure due to thermal
expansion of blocked liquid-filled equipment or piping due to ambient
heating or heat from a heat tracing system. Pressure relief valves
designed to protect equipment from excess pressure due to blockage
against a pump or compressor or due to fire contingency are not thermal
expansion relief valves.
* * * * *
Total steam means the total of all steam that is supplied to a
flare and includes, but is not limited to, lower steam, center steam
and upper steam.
Upper steam means the portion of assist steam introduced via
nozzles located on the exterior perimeter of the upper end of the flare
tip.
* * * * *
0
15. Section 63.642 is amended by:
0
a. Adding paragraph (b);
0
b. Revising paragraphs (d)(3), (e), (i), (k) introductory text, (k)(1),
(l) introductory text, and (l)(2); and
0
c. Adding paragraph (n).
The revisions and additions read as follows:
Sec. 63.642 General standards.
* * * * *
(b) The emission standards set forth in this subpart shall apply at
all times.
* * * * *
(d) * * *
(3) Performance tests shall be conducted according to the
provisions of Sec. 63.7(e) except that performance tests shall be
conducted at maximum representative operating capacity for the process.
During the performance test, an owner or operator shall operate the
control device at either maximum or minimum representative operating
conditions for monitored control device parameters, whichever results
in lower emission reduction. An owner or operator shall not conduct a
performance test during startup, shutdown, periods when the control
device is bypassed or periods when the process, monitoring equipment or
control device is not operating properly. The owner/operator may not
conduct performance tests during periods of malfunction. The owner or
operator must record the process information that is necessary to
document operating conditions during the test and include in such
record an explanation to support that the test was conducted at maximum
representative operating capacity. Upon request, the owner or operator
shall make available to the Administrator such records as may be
necessary to determine the conditions of performance tests.
* * * * *
(e) All applicable records shall be maintained as specified in
Sec. 63.655(i).
* * * * *
(i) The owner or operator of an existing source shall demonstrate
compliance with the emission standard in paragraph (g) of this section
by following the procedures specified in paragraph (k) of this section
for all emission points, or by following the emissions averaging
compliance approach specified in paragraph (l) of this section for
specified emission points and the procedures specified in paragraph
(k)(1) of this section.
* * * * *
(k) The owner or operator of an existing source may comply, and the
owner or operator of a new source shall comply, with the applicable
provisions in Sec. Sec. 63.643 through 63.645, 63.646 or 63.660,
63.647, 63.650, and 63.651, as specified in Sec. 63.640(h).
(1) The owner or operator using this compliance approach shall also
comply with the requirements of Sec. Sec. 63.648 and/or 63.649,
63.654, 63.655, 63.657, 63.658, 63.670 and 63.671, as applicable.
* * * * *
(l) The owner or operator of an existing source may elect to
control some of the emission points within the source to different
levels than specified under Sec. Sec. 63.643 through 63.645, 63.646 or
63.660, 63.647, 63.650, and 63.651, as applicable according to Sec.
63.640(h), by using an emissions averaging compliance approach as long
as the overall emissions for the source do not exceed the emission
level specified in paragraph (g) of this section. The owner or operator
using emissions averaging shall meet the requirements in paragraphs
(l)(1) and (2) of this section.
* * * * *
(2) Comply with the requirements of Sec. Sec. 63.648 and/or
63.649, 63.654, 63.652, 63.653, 63.655, 63.657, 63.658, 63.670 and
63.671, as applicable.
* * * * *
(n) At all times, the owner or operator must operate and maintain
any affected source, including associated air pollution control
equipment and monitoring equipment, in a manner consistent with safety
and good air pollution control practices for minimizing emissions. The
general duty to minimize emissions does not require the owner operator
to make any further efforts to reduce emissions if levels required by
the applicable standard have been achieved. Determination of whether a
source is operating in compliance with operation and maintenance
requirements will be based on information available to the
Administrator which may include, but is not limited to, monitoring
results, review of operation and maintenance procedures, review of
operation and maintenance records, and inspection of the source.
0
16. Section 63.643 is amended by revising paragraphs (a) introductory
text and (a)(1) and adding paragraph (c) to read as follows:
Sec. 63.643 Miscellaneous process vent provisions.
(a) The owner or operator of a Group 1 miscellaneous process vent
as defined in Sec. 63.641 shall comply with the requirements of either
paragraph (a)(1) or (2) of this section or, if applicable, paragraph
(c) of this section. The owner or operator of a miscellaneous process
vent that meets the conditions in paragraph (c) of this section is only
required to comply with the requirements of paragraph (c) of this
section and Sec. 63.655(g)(13) and (i)(12) for that vent.
(1) Reduce emissions of organic HAP's using a flare. On and after
January 30, 2019, the flare shall meet the requirements of Sec.
63.670. Prior to January 30, 2019, the flare shall meet the
requirements of Sec. 63.11(b) of subpart A or the requirements of
Sec. 63.670.
* * * * *
(c) An owner or operator may designate a process vent as a
maintenance vent if the vent is only used as a result of startup,
shutdown, maintenance, or inspection of equipment where equipment is
emptied, depressurized, degassed or placed into service. The owner of
operator does not need to designate a maintenance vent as a Group 1 or
Group 2 miscellaneous process vent. The owner or operator must comply
with the applicable requirements in paragraphs (c)(1) through (3) of
this section for each maintenance vent.
(1) Prior to venting to the atmosphere, process liquids are removed
from the equipment as much as practical and the equipment is
depressured to a control device, fuel gas system, or back to the
process until one of the following conditions, as applicable, is met.
(i) The vapor in the equipment served by the maintenance vent has a
lower
[[Page 75243]]
explosive limit (LEL) of less than 10 percent.
(ii) If there is no ability to measure the LEL of the vapor in the
equipment based on the design of the equipment, the pressure in the
equipment served by the maintenance vent is reduced to 5 psig or less.
Upon opening the maintenance vent, active purging of the equipment
cannot be used until the LEL of the vapors in the maintenance vent (or
inside the equipment if the maintenance is a hatch or similar type of
opening) equipment is less than 10 percent.
(iii) The equipment served by the maintenance vent contains less
than 72 pounds of VOC.
(iv) If the maintenance vent is associated with equipment
containing pyrophoric catalyst (e.g., hydrotreaters and hydrocrackers)
at refineries that do not have a pure hydrogen supply, the LEL of the
vapor in the equipment must be less than 20 percent, except for one
event per year not to exceed 35 percent.
(2) Except for maintenance vents complying with the alternative in
paragraph (c)(1)(iii) of this section, the owner or operator must
determine the LEL or, if applicable, equipment pressure using process
instrumentation or portable measurement devices and follow procedures
for calibration and maintenance according to manufacturer's
specifications.
(3) For maintenance vents complying with the alternative in
paragraph (c)(1)(iii) of this section, the owner or operator shall
determine mass of VOC in the equipment served by the maintenance vent
based on the equipment size and contents after considering any contents
drained or purged from the equipment. Equipment size may be determined
from equipment design specifications. Equipment contents may be
determined using process knowledge.
0
17. Section 63.644 is amended by revising paragraphs (a) introductory
text, (a)(2), and (c) to read as follows:
Sec. 63.644 Monitoring provisions for miscellaneous process vents.
(a) Except as provided in paragraph (b) of this section, each owner
or operator of a Group 1 miscellaneous process vent that uses a
combustion device to comply with the requirements in Sec. 63.643(a)
shall install the monitoring equipment specified in paragraph (a)(1),
(2), (3), or (4) of this section, depending on the type of combustion
device used. All monitoring equipment shall be installed, calibrated,
maintained, and operated according to manufacturer's specifications or
other written procedures that provide adequate assurance that the
equipment will monitor accurately and, except for CPMS installed for
pilot flame monitoring, must meet the applicable minimum accuracy,
calibration and quality control requirements specified in table 13 of
this subpart.
* * * * *
(2) Where a flare is used prior to January 30, 2019, a device
(including but not limited to a thermocouple, an ultraviolet beam
sensor, or an infrared sensor) capable of continuously detecting the
presence of a pilot flame is required, or the requirements of Sec.
63.670 shall be met. Where a flare is used on and after January 30,
2019, the requirements of Sec. 63.670 shall be met.
* * * * *
(c) The owner or operator of a Group 1 miscellaneous process vent
using a vent system that contains bypass lines that could divert a vent
stream away from the control device used to comply with paragraph (a)
of this section either directly to the atmosphere or to a control
device that does not comply with the requirements in Sec. 63.643(a)
shall comply with either paragraph (c)(1) or (2) of this section. Use
of the bypass at any time to divert a Group 1 miscellaneous process
vent stream to the atmosphere or to a control device that does not
comply with the requirements in Sec. 63.643(a) is an emissions
standards violation. Equipment such as low leg drains and equipment
subject to Sec. 63.648 are not subject to this paragraph (c).
(1) Install, calibrate and maintain a flow indicator that
determines whether a vent stream flow is present at least once every
hour. A manual block valve equipped with a valve position indicator may
be used in lieu of a flow indicator, as long as the valve position
indicator is monitored continuously. Records shall be generated as
specified in Sec. 63.655(h) and (i). The flow indicator shall be
installed at the entrance to any bypass line that could divert the vent
stream away from the control device to the atmosphere; or
(2) Secure the bypass line valve in the non-diverting position with
a car-seal or a lock-and-key type configuration. A visual inspection of
the seal or closure mechanism shall be performed at least once every
month to ensure that the valve is maintained in the non-diverting
position and that the vent stream is not diverted through the bypass
line.
* * * * *
0
18. Section 63.645 is amended by revising paragraphs (e)(1) and (f)(2)
to read as follows:
Sec. 63.645 Test methods and procedures for miscellaneous process
vents.
* * * * *
(e) * * *
(1) Methods 1 or 1A of 40 CFR part 60, appendix A-1, as
appropriate, shall be used for selection of the sampling site. For
vents smaller than 0.10 meter in diameter, sample at the center of the
vent.
* * * * *
(f) * * *
(2) The gas volumetric flow rate shall be determined using Methods
2, 2A, 2C, 2D, or 2F of 40 CFR part 60, appendix A-1 or Method 2G of 40
CFR part 60, appendix A-2, as appropriate.
* * * * *
0
19. Section 63.646 is amended by adding introductory text and revising
paragraph (b)(2) to read as follows:
Sec. 63.646 Storage vessel provisions.
Upon a demonstration of compliance with the standards in Sec.
63.660 by the compliance dates specified in Sec. 63.640(h), the
standards in this section shall no longer apply.
* * * * *
(b) * * *
(2) When an owner or operator and the Administrator do not agree on
whether the annual average weight percent organic HAP in the stored
liquid is above or below 4 percent for a storage vessel at an existing
source or above or below 2 percent for a storage vessel at a new
source, an appropriate method (based on the type of liquid stored) as
published by EPA or a consensus-based standards organization shall be
used. Consensus-based standards organizations include, but are not
limited to, the following: ASTM International (100 Barr Harbor Drive,
P.O. Box CB700, West Conshohocken, Pennsylvania 19428-B2959, (800) 262-
1373, https://www.astm.org), the American National Standards Institute
(ANSI, 1819 L Street NW., 6th floor, Washington, DC 20036, (202) 293-
8020, https://www.ansi.org), the American Gas Association (AGA, 400
North Capitol Street NW., 4th Floor, Washington, DC 20001, (202) 824-
7000, https://www.aga.org), the American Society of Mechanical Engineers
(ASME, Three Park Avenue, New York, NY 10016-5990, (800) 843-2763,
https://www.asme.org), the American Petroleum Institute (API, 1220 L
Street NW., Washington, DC 20005-4070, (202) 682-8000, https://www.api.org), and the North American Energy Standards Board (NAESB, 801
Travis Street, Suite 1675, Houston, TX 77002, (713) 356-0060, https://www.naesb.org).
* * * * *
[[Page 75244]]
0
20. Section 63.647 is amended by:
0
a. Revising paragraph (a);
0
b. Redesignating paragraph (c) as paragraph (d); and
0
c. Adding paragraph (c).
The revisions and additions read as follows:
Sec. 63.647 Wastewater provisions.
(a) Except as provided in paragraphs (b) and (c) of this section,
each owner or operator of a Group 1 wastewater stream shall comply with
the requirements of Sec. Sec. 61.340 through 61.355 of this chapter
for each process wastewater stream that meets the definition in Sec.
63.641.
* * * * *
(c) If a flare is used as a control device, on and after January
30, 2019, the flare shall meet the requirements of Sec. 63.670. Prior
to January 30, 2019, the flare shall meet the applicable requirements
of part 61, subpart FF of this chapter, or the requirements of Sec.
63.670.
* * * * *
0
21. Section 63.648 is amended by:
0
a. Adding paragraph (a)(3);
0
b. Revising paragraph (c) introductory text; and
0
c. Adding paragraphs (c)(11) and (12) and (j).
The revisions and additions read as follows:
Sec. 63.648 Equipment leak standards.
(a) * * *
(3) If a flare is used as a control device, on and after January
30, 2019, the flare shall meet the requirements of Sec. 63.670. Prior
to January 30, 2019, the flare shall meet the applicable requirements
of part 60, subpart VV of this chapter, or the requirements of Sec.
63.670.
* * * * *
(c) In lieu of complying with the existing source provisions of
paragraph (a) in this section, an owner or operator may elect to comply
with the requirements of Sec. Sec. 63.161 through 63.169, 63.171,
63.172, 63.175, 63.176, 63.177, 63.179, and 63.180 of subpart H except
as provided in paragraphs (c)(1) through (12) and (e) through (i) of
this section.
* * * * *
(11) [Reserved]
(12) If a flare is used as a control device, on and after January
30, 2019, the flare shall meet the requirements of Sec. 63.670. Prior
to January 30, 2019, the flare shall meet the applicable requirements
of Sec. Sec. 63.172 and 63.180, or the requirements of Sec. 63.670.
* * * * *
(j) Except as specified in paragraph (j)(4) of this section, the
owner or operator must comply with the requirements specified in
paragraphs (j)(1) and (2) of this section for pressure relief devices,
such as relief valves or rupture disks, in organic HAP gas or vapor
service instead of the pressure relief device requirements of Sec.
60.482-4 or Sec. 63.165, as applicable. Except as specified in
paragraphs (j)(4) and (5) of this section, the owner or operator must
also comply with the requirements specified in paragraph (j)(3) of this
section for all pressure relief devices.
(1) Operating requirements. Except during a pressure release,
operate each pressure relief device in organic HAP gas or vapor service
with an instrument reading of less than 500 ppm above background as
detected by Method 21 of 40 CFR part 60, appendix A-7.
(2) Pressure release requirements. For pressure relief devices in
organic HAP gas or vapor service, the owner or operator must comply
with the applicable requirements in paragraphs (j)(2)(i) through (iii)
of this section following a pressure release.
(i) If the pressure relief device does not consist of or include a
rupture disk, conduct instrument monitoring, as specified in Sec.
60.485(b) or Sec. 63.180(c), as applicable, no later than 5 calendar
days after the pressure relief device returns to organic HAP gas or
vapor service following a pressure release to verify that the pressure
relief device is operating with an instrument reading of less than 500
ppm.
(ii) If the pressure relief device includes a rupture disk, either
comply with the requirements in paragraph (j)(2)(i) of this section
(not replacing the rupture disk) or install a replacement disk as soon
as practicable after a pressure release, but no later than 5 calendar
days after the pressure release. The owner or operator must conduct
instrument monitoring, as specified in Sec. 60.485(b) or Sec.
63.180(c), as applicable, no later than 5 calendar days after the
pressure relief device returns to organic HAP gas or vapor service
following a pressure release to verify that the pressure relief device
is operating with an instrument reading of less than 500 ppm.
(iii) If the pressure relief device consists only of a rupture
disk, install a replacement disk as soon as practicable after a
pressure release, but no later than 5 calendar days after the pressure
release. The owner or operator may not initiate startup of the
equipment served by the rupture disk until the rupture disc is
replaced. The owner or operator must conduct instrument monitoring, as
specified in Sec. 60.485(b) or Sec. 63.180(c), as applicable, no
later than 5 calendar days after the pressure relief device returns to
organic HAP gas or vapor service following a pressure release to verify
that the pressure relief device is operating with an instrument reading
of less than 500 ppm.
(3) Pressure release management. Except as specified in paragraphs
(j)(4) and (5) of this section, the owner or operator shall comply with
the requirements specified in paragraphs (j)(3)(i) through (v) of this
section for all pressure relief devices in organic HAP service no later
than January 30, 2019.
(i) The owner or operator must equip each affected pressure relief
device with a device(s) or use a monitoring system that is capable of:
(A) Identifying the pressure release;
(B) Recording the time and duration of each pressure release; and
(C) Notifying operators immediately that a pressure release is
occurring. The device or monitoring system may be either specific to
the pressure relief device itself or may be associated with the process
system or piping, sufficient to indicate a pressure release to the
atmosphere. Examples of these types of devices and systems include, but
are not limited to, a rupture disk indicator, magnetic sensor, motion
detector on the pressure relief valve stem, flow monitor, or pressure
monitor.
(ii) The owner or operator must apply at least three redundant
prevention measures to each affected pressure relief device and
document these measures. Examples of prevention measures include:
(A) Flow, temperature, level and pressure indicators with deadman
switches, monitors, or automatic actuators.
(B) Documented routine inspection and maintenance programs and/or
operator training (maintenance programs and operator training may count
as only one redundant prevention measure).
(C) Inherently safer designs or safety instrumentation systems.
(D) Deluge systems.
(E) Staged relief system where initial pressure relief valve (with
lower set release pressure) discharges to a flare or other closed vent
system and control device.
(iii) If any affected pressure relief device releases to atmosphere
as a result of a pressure release event, the owner or operator must
perform root cause analysis and corrective action analysis according to
the requirement in paragraph (j)(6) of this section and implement
corrective actions according to the requirements in paragraph (j)(7) of
this section. The owner or operator must also calculate the quantity of
organic HAP released during each pressure
[[Page 75245]]
release event and report this quantity as required in Sec.
63.655(g)(10)(iii). Calculations may be based on data from the pressure
relief device monitoring alone or in combination with process parameter
monitoring data and process knowledge.
(iv) The owner or operator shall determine the total number of
release events occurred during the calendar year for each affected
pressure relief device separately. The owner or operator shall also
determine the total number of release events for each pressure relief
device for which the root cause analysis concluded that the root cause
was a force majeureevent, as defined in this subpart.
(v) Except for pressure relief devices described in paragraphs
(j)(4) and (5) of this section, the following release events are a
violation of the pressure release management work practice standards.
(A) Any release event for which the root cause of the event was
determined to be operator error or poor maintenance.
(B) A second release event not including force majeure events from
a single pressure relief device in a 3 calendar year period for the
same root cause for the same equipment.
(C) A third release event not including force majeure events from a
single pressure relief device in a 3 calendar year period for any
reason.
(4) Pressure relief devices routed to a control device. If all
releases and potential leaks from a pressure relief device are routed
through a closed vent system to a control device, back into the process
or to the fuel gas system, the owner or operator is not required to
comply with paragraph (j)(1), (2), or (3) (if applicable) of this
section. Both the closed vent system and control device (if applicable)
must meet the requirements of Sec. 63.644. When complying with this
paragraph (j)(4), all references to ``Group 1 miscellaneous process
vent'' in Sec. 63.644 mean ``pressure relief device.'' If a pressure
relief device complying with this paragraph (j)(4) is routed to the
fuel gas system, then on and after January 30, 2019, any flares
receiving gas from that fuel gas system must be in compliance with
Sec. 63.670.
(5) Pressure relief devices exempted from pressure release
management requirements. The following types of pressure relief devices
are not subject to the pressure release management requirements in
paragraph (j)(3) of this section.
(i) Pressure relief devices in heavy liquid service, as defined in
Sec. 63.641.
(ii) Pressure relief devices that only release material that is
liquid at standard conditions (1 atmosphere and 68 degrees Fahrenheit)
and that are hard-piped to a controlled drain system (i.e., a drain
system meeting the requirements for Group 1 wastewater streams in Sec.
63.647(a)) or piped back to the process or pipeline.
(iii) Thermal expansion relief valves.
(iv) Pressure relief devices designed with a set relief pressure of
less than 2.5 psig.
(v) Pressure relief devices that do not have the potential to emit
72 lbs/day or more of VOC based on the valve diameter, the set release
pressure, and the equipment contents.
(vi) Pressure relief devices on mobile equipment.
(6) Root cause analysis and corrective action analysis. A root
cause analysis and corrective action analysis must be completed as soon
as possible, but no later than 45 days after a release event. Special
circumstances affecting the number of root cause analyses and/or
corrective action analyses are provided in paragraphs (j)(6)(i) through
(iv) of this section.
(i) You may conduct a single root cause analysis and corrective
action analysis for a single emergency event that causes two or more
pressure relief devices installed on the same equipment to release.
(ii) You may conduct a single root cause analysis and corrective
action analysis for a single emergency event that causes two or more
pressure relief devices to release, regardless of the equipment served,
if the root cause is reasonably expected to be a force majeure event,
as defined in this subpart.
(iii) Except as provided in paragraphs (j)(6)(i) and (ii) of this
section, if more than one pressure relief device has a release during
the same time period, an initial root cause analysis shall be conducted
separately for each pressure relief device that had a release. If the
initial root cause analysis indicates that the release events have the
same root cause(s), the initially separate root cause analyses may be
recorded as a single root cause analysis and a single corrective action
analysis may be conducted.
(7) Corrective action implementation. Each owner or operator
required to conduct a root cause analysis and corrective action
analysis as specified in paragraphs (j)(3)(iii) and (j)(6) of this
section shall implement the corrective action(s) identified in the
corrective action analysis in accordance with the applicable
requirements in paragraphs (j)(7)(i) through (iii) of this section.
(i) All corrective action(s) must be implemented within 45 days of
the event for which the root cause and corrective action analyses were
required or as soon thereafter as practicable. If an owner or operator
concludes that no corrective action should be implemented, the owner or
operator shall record and explain the basis for that conclusion no
later than 45 days following the event.
(ii) For corrective actions that cannot be fully implemented within
45 days following the event for which the root cause and corrective
action analyses were required, the owner or operator shall develop an
implementation schedule to complete the corrective action(s) as soon as
practicable.
(iii) No later than 45 days following the event for which a root
cause and corrective action analyses were required, the owner or
operator shall record the corrective action(s) completed to date, and,
for action(s) not already completed, a schedule for implementation,
including proposed commencement and completion dates.
0
22. Section 63.649 is amended by revising definition of Cc
term in the equation in paragraph (c)(6)(i) to read as follows:
Sec. 63.649 Alternative means of emission limitation: Connectors in
gas/vapor service and light liquid service.
* * * * *
(c) * * *
(6) * * *
(i) * * *
Cc = Optional credit for removed connectors = 0.67 x net
number (i.e., the total number of connectors removed minus the total
added) of connectors in organic HAP service removed from the process
unit after the applicability date set forth in Sec.
63.640(h)(3)(iii) for existing process units, and after the date of
start-up for new process units. If credits are not taken, then
Cc = 0.
* * * * *
0
23. Section 63.650 is amended by revising paragraph (a) and adding
paragraph (d) to read as follows:
Sec. 63.650 Gasoline loading rack provisions.
(a) Except as provided in paragraphs (b) through (d) of this
section, each owner or operator of a Group 1 gasoline loading rack
classified under Standard Industrial Classification code 2911 located
within a contiguous area and under common control with a petroleum
refinery shall comply with subpart R of this part, Sec. Sec. 63.421,
63.422(a) through (c) and (e), 63.425(a) through (c) and (e) through
(i), 63.427(a) and (b), and 63.428(b), (c), (g)(1), (h)(1) through (3),
and (k).
* * * * *
[[Page 75246]]
(d) If a flare is used as a control device, on and after January
30, 2019, the flare shall meet the requirements of Sec. 63.670. Prior
to January 30, 2019, the flare shall meet the applicable requirements
of subpart R of this part, or the requirements of Sec. 63.670.
0
24. Section 63.651 is amended by revising paragraphs (a) and (d) and
adding paragraph (e) to read as follows:
Sec. 63.651 Marine tank vessel loading operation provisions.
(a) Except as provided in paragraphs (b) through (e) of this
section, each owner or operator of a marine tank vessel loading
operation located at a petroleum refinery shall comply with the
requirements of Sec. Sec. 63.560 through 63.568.
* * * * *
(d) The compliance time of 4 years after promulgation of 40 CFR
part 63, subpart Y, does not apply. The compliance time is specified in
Sec. 63.640(h)(1).
(e) If a flare is used as a control device, on and after January
30, 2019, the flare shall meet the requirements of Sec. 63.670. Prior
to January 30, 2019, the flare shall meet the applicable requirements
of subpart Y of this part, or the requirements of Sec. 63.670.
0
25. Section 63.652 is amended by:
0
a. Revising paragraph (a);
0
b. Removing and reserving paragraph (f)(2); and
0
c. Revising paragraphs (g)(2)(iii)(B)(1), (h)(3), (k) introductory
text, and (k)(3).
The revisions and additions read as follows:
Sec. 63.652 Emissions averaging provisions.
(a) This section applies to owners or operators of existing sources
who seek to comply with the emission standard in Sec. 63.642(g) by
using emissions averaging according to Sec. 63.642(l) rather than
following the provisions of Sec. Sec. 63.643 through 63.645, 63.646 or
63.660, 63.647, 63.650, and 63.651. Existing marine tank vessel loading
operations located at the Valdez Marine Terminal source may not comply
with the standard by using emissions averaging.
* * * * *
(g) * * *
(2) * * *
(iii) * * *
(B) * * *
(1) The percent reduction shall be measured according to the
procedures in Sec. 63.116 of subpart G if a combustion control device
is used. For a flare meeting the criteria in Sec. 63.116(a) of subpart
G or Sec. 63.670, as applicable, or a boiler or process heater meeting
the criteria in Sec. 63.645(d) or Sec. 63.116(b) of subpart G, the
percentage of reduction shall be 98 percent. If a noncombustion control
device is used, percentage of reduction shall be demonstrated by a
performance test at the inlet and outlet of the device, or, if testing
is not feasible, by a control design evaluation and documented
engineering calculations.
* * * * *
(h) * * *
(3) Emissions from storage vessels shall be determined as specified
in Sec. 63.150(h)(3) of subpart G, except as follows:
(i) For storage vessels complying with Sec. 63.646:
(A) All references to Sec. 63.119(b) in Sec. 63.150(h)(3) of
subpart G shall be replaced with: Sec. 63.119(b) or Sec. 63.119(b)
except for Sec. 63.119(b)(5) and (6).
(B) All references to Sec. 63.119(c) in Sec. 63.150(h)(3) of
subpart G shall be replaced with: Sec. 63.119(c) or Sec. 63.119(c)
except for Sec. 63.119(c)(2).
(C) All references to Sec. 63.119(d) in Sec. 63.150(h)(3) of
subpart G shall be replaced with: Sec. 63.119(d) or Sec. 63.119(d)
except for Sec. 63.119(d)(2).
(ii) For storage vessels complying with Sec. 63.660:
(A) Section 63.1063(a)(1)(i), (a)(2), and (b) or Sec.
63.1063(a)(1)(i) and (b) shall apply instead of Sec. 63.119(b) in
Sec. 63.150(h)(3) of subpart G.
(B) Section 63.1063(a)(1)(ii), (a)(2), and (b) shall apply instead
of Sec. 63.119(c) in Sec. 63.150(h)(3) of subpart G.
(C) Section 63.1063(a)(1)(i), (a)(2), and (b) or Sec.
63.1063(a)(1)(i) and (b) shall apply instead of Sec. 63.119(d) in
Sec. 63.150(h)(3) of subpart G.
* * * * *
(k) The owner or operator shall demonstrate that the emissions from
the emission points proposed to be included in the average will not
result in greater hazard or, at the option of the State or local
permitting authority, greater risk to human health or the environment
than if the emission points were controlled according to the provisions
in Sec. Sec. 63.643 through 63.645, 63.646 or 63.660, 63.647, 63.650,
and 63.651, as applicable.
* * * * *
(3) An emissions averaging plan that does not demonstrate an
equivalent or lower hazard or risk to the satisfaction of the State or
local permitting authority shall not be approved. The State or local
permitting authority may require such adjustments to the emissions
averaging plan as are necessary in order to ensure that the average
will not result in greater hazard or risk to human health or the
environment than would result if the emission points were controlled
according to Sec. Sec. 63.643 through 63.645, 63.646 or 63.660,
63.647, 63.650, and 63.651, as applicable.
* * * * *
0
26. Section 63.653 is amended by revising paragraphs (a) introductory
text, (a)(3)(i) and (ii), and (a)(7) to read as follows:
Sec. 63.653 Monitoring, recordkeeping, and implementation plan for
emissions averaging.
(a) For each emission point included in an emissions average, the
owner or operator shall perform testing, monitoring, recordkeeping, and
reporting equivalent to that required for Group 1 emission points
complying with Sec. Sec. 63.643 through 63.645, 63.646 or 63.660,
63.647, 63.650, and 63.651, as applicable. The specific requirements
for miscellaneous process vents, storage vessels, wastewater, gasoline
loading racks, and marine tank vessels are identified in paragraphs
(a)(1) through (7) of this section.
* * * * *
(3) * * *
(i) Perform the monitoring or inspection procedures in Sec. 63.646
and either Sec. 63.120 of subpart G or Sec. 63.1063 of subpart WW, as
applicable; and
(ii) For closed vent systems with control devices, conduct an
initial design evaluation as specified in Sec. 63.646 and either Sec.
63.120(d) of subpart G or Sec. 63.985(b) of subpart SS, as applicable.
* * * * *
(7) If an emission point in an emissions average is controlled
using a pollution prevention measure or a device or technique for which
no monitoring parameters or inspection procedures are specified in
Sec. Sec. 63.643 through 63.645, 63.646 or 63.660, 63.647, 63.650, and
63.651, as applicable, the owner or operator shall establish a site-
specific monitoring parameter and shall submit the information
specified in Sec. 63.655(h)(4) in the Implementation Plan.
* * * * *
0
27. Section 63.655 is amended by:
0
a. Revising paragraphs (f) introductory text, (f)(1) introductory text,
(f)(1)(i)(A) introductory text, (f)(1)(i)(A)(2) and (3), (f)(1)(i)(B)
introductory text, (f)(1)(i)(B)(2), (f)(1)(i)(D)(2), (f)(1)(iv)
introductory text, and (f)(1)(iv)(A);
0
b. Adding paragraphs (f)(1)(vii) and (viii);
0
c. Revising paragraphs (f)(2) introductory text, (f)(3) introductory
text, the first sentence of (f)(6), (g) introductory text, (g)(1)
through (5), (g)(6)(i)(D), (g)(6)(iii), and (g)(7)(i);
[[Page 75247]]
0
d. Adding paragraphs (g)(10) through (14);
0
e. Removing and reserving paragraph (h)(1);
0
f. Revising paragraphs (h)(2) introductory text, (h)(2)(i)(B),
(h)(2)(ii), and (h)(5)(iii);
0
g. Adding paragraphs (h)(8) and (9) and (i) introductory text;
0
h. Revising paragraph (i)(1) introductory text and paragraph
(i)(1)(ii);
0
i. Adding paragraphs (i)(1)(v) and (vi);
0
j. Redesignating paragraphs (i)(4) and (5) as paragraphs (i)(5) and
(6), respectively;
0
k. Adding paragraph (i)(4);
0
l. Revising newly redesignated paragraph (i)(5) introductory text; and
0
m. Adding paragraphs (i)(7) through (12).
The revisions and additions read as follows:
Sec. 63.655 Reporting and recordkeeping requirements.
* * * * *
(f) Each owner or operator of a source subject to this subpart
shall submit a Notification of Compliance Status report within 150 days
after the compliance dates specified in Sec. 63.640(h) with the
exception of Notification of Compliance Status reports submitted to
comply with Sec. 63.640(l)(3) and for storage vessels subject to the
compliance schedule specified in Sec. 63.640(h)(2). Notification of
Compliance Status reports required by Sec. 63.640(l)(3) and for
storage vessels subject to the compliance dates specified in Sec.
63.640(h)(2) shall be submitted according to paragraph (f)(6) of this
section. This information may be submitted in an operating permit
application, in an amendment to an operating permit application, in a
separate submittal, or in any combination of the three. If the required
information has been submitted before the date 150 days after the
compliance date specified in Sec. 63.640(h), a separate Notification
of Compliance Status report is not required within 150 days after the
compliance dates specified in Sec. 63.640(h). If an owner or operator
submits the information specified in paragraphs (f)(1) through (5) of
this section at different times, and/or in different submittals, later
submittals may refer to earlier submittals instead of duplicating and
resubmitting the previously submitted information. Each owner or
operator of a gasoline loading rack classified under Standard
Industrial Classification Code 2911 located within a contiguous area
and under common control with a petroleum refinery subject to the
standards of this subpart shall submit the Notification of Compliance
Status report required by subpart R of this part within 150 days after
the compliance dates specified in Sec. 63.640(h).
(1) The Notification of Compliance Status report shall include the
information specified in paragraphs (f)(1)(i) through (viii) of this
section.
(i) * * *
(A) Identification of each storage vessel subject to this subpart,
and for each Group 1 storage vessel subject to this subpart, the
information specified in paragraphs (f)(1)(i)(A)(1) through (3) of this
section. This information is to be revised each time a Notification of
Compliance Status report is submitted for a storage vessel subject to
the compliance schedule specified in Sec. 63.640(h)(2) or to comply
with Sec. 63.640(l)(3).
* * * * *
(2) For storage vessels subject to the compliance schedule
specified in Sec. 63.640(h)(2) that are not complying with Sec.
63.646, the anticipated compliance date.
(3) For storage vessels subject to the compliance schedule
specified in Sec. 63.640(h)(2) that are complying with Sec. 63.646
and the Group 1 storage vessels described in Sec. 63.640(l), the
actual compliance date.
(B) If a closed vent system and a control device other than a flare
is used to comply with Sec. 63.646 or Sec. 63.660, the owner or
operator shall submit:
* * * * *
(2) The design evaluation documentation specified in Sec.
63.120(d)(1)(i) of subpart G or Sec. 63.985(b)(1)(i) of subpart SS (as
applicable), if the owner or operator elects to prepare a design
evaluation; or
* * * * *
(D) * * *
(2) All visible emission readings, heat content determinations,
flow rate measurements, and exit velocity determinations made during
the compliance determination required by Sec. 63.120(e) of subpart G
or Sec. 63.987(b) of subpart SS or Sec. 63.670(h), as applicable; and
* * * * *
(iv) For miscellaneous process vents controlled by flares, initial
compliance test results including the information in paragraphs
(f)(1)(iv)(A) and (B) of this section.
(A) All visible emission readings, heat content determinations,
flow rate measurements, and exit velocity determinations made during
the compliance determination required by Sec. Sec. 63.645 and
63.116(a) of subpart G or Sec. 63.670(h), as applicable; and
* * * * *
(vii) For pressure relief devices in organic HAP service subject to
the requirements in Sec. 63.648(j)(3)(i) and (ii), this report shall
include the information specified in paragraphs (f)(1)(vii)(A) and (B)
of this section.
(A) A description of the monitoring system to be implemented,
including the relief devices and process parameters to be monitored,
and a description of the alarms or other methods by which operators
will be notified of a pressure release.
(B) A description of the prevention measures to be implemented for
each affected pressure relief device.
(viii) For each delayed coking unit, identification of whether the
unit is an existing affected source or a new affected source and
whether monitoring will be conducted as specified in Sec. 63.657(b) or
(c).
(2) If initial performance tests are required by Sec. Sec. 63.643
through 63.653, the Notification of Compliance Status report shall
include one complete test report for each test method used for a
particular source. On and after February 1, 2016, performance tests
shall be submitted according to paragraph (h)(9) of this section.
* * * * *
(3) For each monitored parameter for which a range is required to
be established under Sec. 63.120(d) of subpart G or Sec. 63.985(b) of
subpart SS for storage vessels or Sec. 63.644 for miscellaneous
process vents, the Notification of Compliance Status report shall
include the information in paragraphs (f)(3)(i) through (iii) of this
section.
* * * * *
(6) Notification of Compliance Status reports required by Sec.
63.640(l)(3) and for storage vessels subject to the compliance dates
specified in Sec. 63.640(h)(2) shall be submitted no later than 60
days after the end of the 6-month period during which the change or
addition was made that resulted in the Group 1 emission point or the
existing Group 1 storage vessel was brought into compliance, and may be
combined with the periodic report. * * *
(g) The owner or operator of a source subject to this subpart shall
submit Periodic Reports no later than 60 days after the end of each 6-
month period when any of the information specified in paragraphs (g)(1)
through (7) of this section or paragraphs (g)(9) through (14) of this
section is collected. The first 6-month period shall begin on the date
the Notification of Compliance Status report is required to be
submitted. A Periodic Report is not required if none of the events
identified in paragraphs (g)(1)
[[Page 75248]]
through (7) of this section or paragraphs (g)(9) through (14) of this
section occurred during the 6-month period unless emissions averaging
is utilized. Quarterly reports must be submitted for emission points
included in emission averages, as provided in paragraph (g)(8) of this
section. An owner or operator may submit reports required by other
regulations in place of or as part of the Periodic Report required by
this paragraph (g) if the reports contain the information required by
paragraphs (g)(1) through (14) of this section.
(1) For storage vessels, Periodic Reports shall include the
information specified for Periodic Reports in paragraphs (g)(2) through
(5) of this section. Information related to gaskets, slotted membranes,
and sleeve seals is not required for storage vessels that are part of
an existing source complying with Sec. 63.646.
(2) Internal floating roofs. (i) An owner or operator who elects to
comply with Sec. 63.646 by using a fixed roof and an internal floating
roof or by using an external floating roof converted to an internal
floating roof shall submit the results of each inspection conducted in
accordance with Sec. 63.120(a) of subpart G in which a failure is
detected in the control equipment.
(A) For vessels for which annual inspections are required under
Sec. 63.120(a)(2)(i) or (a)(3)(ii) of subpart G, the specifications
and requirements listed in paragraphs (g)(2)(i)(A)(1) through (3) of
this section apply.
(1) A failure is defined as any time in which the internal floating
roof is not resting on the surface of the liquid inside the storage
vessel and is not resting on the leg supports; or there is liquid on
the floating roof; or the seal is detached from the internal floating
roof; or there are holes, tears, or other openings in the seal or seal
fabric; or there are visible gaps between the seal and the wall of the
storage vessel.
(2) Except as provided in paragraph (g)(2)(i)(A)(3) of this
section, each Periodic Report shall include the date of the inspection,
identification of each storage vessel in which a failure was detected,
and a description of the failure. The Periodic Report shall also
describe the nature of and date the repair was made or the date the
storage vessel was emptied.
(3) If an extension is utilized in accordance with Sec.
63.120(a)(4) of subpart G, the owner or operator shall, in the next
Periodic Report, identify the vessel; include the documentation
specified in Sec. 63.120(a)(4) of subpart G; and describe the date the
storage vessel was emptied and the nature of and date the repair was
made.
(B) For vessels for which inspections are required under Sec.
63.120(a)(2)(ii), (a)(3)(i), or (a)(3)(iii) of subpart G (i.e.,
internal inspections), the specifications and requirements listed in
paragraphs (g)(2)(i)(B)(1) and (2) of this section apply.
(1) A failure is defined as any time in which the internal floating
roof has defects; or the primary seal has holes, tears, or other
openings in the seal or the seal fabric; or the secondary seal (if one
has been installed) has holes, tears, or other openings in the seal or
the seal fabric; or, for a storage vessel that is part of a new source,
the gaskets no longer close off the liquid surface from the atmosphere;
or, for a storage vessel that is part of a new source, the slotted
membrane has more than a 10 percent open.
(2) Each Periodic Report shall include the date of the inspection,
identification of each storage vessel in which a failure was detected,
and a description of the failure. The Periodic Report shall also
describe the nature of and date the repair was made.
(ii) An owner or operator who elects to comply with Sec. 63.660 by
using a fixed roof and an internal floating roof shall submit the
results of each inspection conducted in accordance with Sec.
63.1063(c)(1), (d)(1), and (d)(2) of subpart WW in which a failure is
detected in the control equipment. For vessels for which inspections
are required under Sec. 63.1063(c) and (d), the specifications and
requirements listed in paragraphs (g)(2)(ii)(A) through (C) of this
section apply.
(A) A failure is defined in Sec. 63.1063(d)(1) of subpart WW.
(B) Each Periodic Report shall include a copy of the inspection
record required by Sec. 63.1065(b) of subpart WW when a failure
occurs.
(C) An owner or operator who elects to use an extension in
accordance with Sec. 63.1063(e)(2) of subpart WW shall, in the next
Periodic Report, submit the documentation required by Sec.
63.1063(e)(2).
(3) External floating roofs. (i) An owner or operator who elects to
comply with Sec. 63.646 by using an external floating roof shall meet
the periodic reporting requirements specified in paragraphs
(g)(3)(i)(A) through (C) of this section.
(A) The owner or operator shall submit, as part of the Periodic
Report, documentation of the results of each seal gap measurement made
in accordance with Sec. 63.120(b) of subpart G in which the seal and
seal gap requirements of Sec. 63.120(b)(3), (4), (5), or (6) of
subpart G are not met. This documentation shall include the information
specified in paragraphs (g)(3)(i)(A)(1) through (4) of this section.
(1) The date of the seal gap measurement.
(2) The raw data obtained in the seal gap measurement and the
calculations described in Sec. 63.120(b)(3) and (4) of subpart G.
(3) A description of any seal condition specified in Sec.
63.120(b)(5) or (6) of subpart G that is not met.
(4) A description of the nature of and date the repair was made, or
the date the storage vessel was emptied.
(B) If an extension is utilized in accordance with Sec.
63.120(b)(7)(ii) or (b)(8) of subpart G, the owner or operator shall,
in the next Periodic Report, identify the vessel; include the
documentation specified in Sec. 63.120(b)(7)(ii) or (b)(8) of subpart
G, as applicable; and describe the date the vessel was emptied and the
nature of and date the repair was made.
(C) The owner or operator shall submit, as part of the Periodic
Report, documentation of any failures that are identified during visual
inspections required by Sec. 63.120(b)(10) of subpart G. This
documentation shall meet the specifications and requirements in
paragraphs (g)(3)(i)(C)(1) and (2) of this section.
(1) A failure is defined as any time in which the external floating
roof has defects; or the primary seal has holes or other openings in
the seal or the seal fabric; or the secondary seal has holes, tears, or
other openings in the seal or the seal fabric; or, for a storage vessel
that is part of a new source, the gaskets no longer close off the
liquid surface from the atmosphere; or, for a storage vessel that is
part of a new source, the slotted membrane has more than 10 percent
open area.
(2) Each Periodic Report shall include the date of the inspection,
identification of each storage vessel in which a failure was detected,
and a description of the failure. The Periodic Report shall also
describe the nature of and date the repair was made.
(ii) An owner or operator who elects to comply with Sec. 63.660 by
using an external floating roof shall meet the periodic reporting
requirements specified in paragraphs (g)(3)(ii)(A) and (B) of this
section.
(A) For vessels for which inspections are required under Sec.
63.1063(c)(2), (d)(1), and (d)(3) of subpart WW, the owner or operator
shall submit, as part of the Periodic Report, a copy of the inspection
record required by Sec. 63.1065(b) of subpart WW when a failure
occurs. A failure is defined in Sec. 63.1063(d)(1).
[[Page 75249]]
(B) An owner or operator who elects to use an extension in
accordance with Sec. 63.1063(e)(2) or (c)(2)(iv)(B) of subpart WW
shall, in the next Periodic Report, submit the documentation required
by those paragraphs.
(4) [Reserved]
(5) An owner or operator who elects to comply with Sec. 63.646 or
Sec. 63.660 by installing a closed vent system and control device
shall submit, as part of the next Periodic Report, the information
specified in paragraphs (g)(5)(i) through (v) of this section, as
applicable.
(i) The Periodic Report shall include the information specified in
paragraphs (g)(5)(i)(A) and (B) of this section for those planned
routine maintenance operations that would require the control device
not to meet the requirements of either Sec. 63.119(e)(1) or (2) of
subpart G, Sec. 63.985(a) and (b) of subpart SS, or Sec. 63.670, as
applicable.
(A) A description of the planned routine maintenance that is
anticipated to be performed for the control device during the next 6
months. This description shall include the type of maintenance
necessary, planned frequency of maintenance, and lengths of maintenance
periods.
(B) A description of the planned routine maintenance that was
performed for the control device during the previous 6 months. This
description shall include the type of maintenance performed and the
total number of hours during those 6 months that the control device did
not meet the requirements of either Sec. 63.119(e)(1) or (2) of
subpart G, Sec. 63.985(a) and (b) of subpart SS, or Sec. 63.670, as
applicable, due to planned routine maintenance.
(ii) If a control device other than a flare is used, the Periodic
Report shall describe each occurrence when the monitored parameters
were outside of the parameter ranges documented in the Notification of
Compliance Status report. The description shall include: Identification
of the control device for which the measured parameters were outside of
the established ranges, and causes for the measured parameters to be
outside of the established ranges.
(iii) If a flare is used prior to January 30, 2019 and prior to
electing to comply with the requirements in Sec. 63.670, the Periodic
Report shall describe each occurrence when the flare does not meet the
general control device requirements specified in Sec. 63.11(b) of
subpart A and shall include: Identification of the flare that does not
meet the general requirements specified in Sec. 63.11(b) of subpart A,
and reasons the flare did not meet the general requirements specified
in Sec. 63.11(b) of subpart A.
(iv) If a flare is used on or after the date for which compliance
with the requirements in Sec. 63.670 is elected, which can be no later
than January 30, 2019, the Periodic Report shall include the items
specified in paragraph (g)(11) of this section.
(v) An owner or operator who elects to comply with Sec. 63.660 by
installing an alternate control device as described in Sec. 63.1064 of
subpart WW shall submit, as part of the next Periodic Report, a written
application as described in Sec. 63.1066(b)(3) of subpart WW.
(6) * * *
(i) * * *
(D) For data compression systems under paragraph (h)(5)(iii) of
this section, an operating day when the monitor operated for less than
75 percent of the operating hours or a day when less than 18 monitoring
values were recorded.
* * * * *
(iii) For periods in closed vent systems when a Group 1
miscellaneous process vent stream was detected in the bypass line or
diverted from the control device and either directly to the atmosphere
or to a control device that does not comply with the requirements in
Sec. 63.643(a), report the date, time, duration, estimate of the
volume of gas, the concentration of organic HAP in the gas and the
resulting mass emissions of organic HAP that bypassed the control
device. For periods when the flow indicator is not operating, report
the date, time, and duration.
(7) * * *
(i) Results of the performance test shall include the
identification of the source tested, the date of the test, the
percentage of emissions reduction or outlet pollutant concentration
reduction (whichever is needed to determine compliance) for each run
and for the average of all runs, and the values of the monitored
operating parameters.
* * * * *
(10) For pressure relief devices subject to the requirements Sec.
63.648(j), Periodic Reports must include the information specified in
paragraphs (g)(10)(i) through (iii) of this section.
(i) For pressure relief devices in organic HAP gas or vapor
service, pursuant to Sec. 63.648(j)(1), report any instrument reading
of 500 ppm or greater.
(ii) For pressure relief devices in organic HAP gas or vapor
service subject to Sec. 63.648(j)(2), report confirmation that any
monitoring required to be done during the reporting period to show
compliance was conducted.
(iii) For pressure relief devices in organic HAP service subject to
Sec. 63.648(j)(3), report each pressure release to the atmosphere,
including duration of the pressure release and estimate of the mass
quantity of each organic HAP released, and the results of any root
cause analysis and corrective action analysis completed during the
reporting period, including the corrective actions implemented during
the reporting period and, if applicable, the implementation schedule
for planned corrective actions to be implemented subsequent to the
reporting period.
(11) For flares subject to Sec. 63.670, Periodic Reports must
include the information specified in paragraphs (g)(11)(i) through (iv)
of this section.
(i) Records as specified in paragraph (i)(9)(i) of this section for
each 15-minute block during which there was at least one minute when
regulated material is routed to a flare and no pilot flame is present.
(ii) Visible emission records as specified in paragraph
(i)(9)(ii)(C) of this section for each period of 2 consecutive hours
during which visible emissions exceeded a total of 5 minutes.
(iii) The 15-minute block periods for which the applicable
operating limits specified in Sec. 63.670(d) through (f) are not met.
Indicate the date and time for the period, the net heating value
operating parameter(s) determined following the methods in Sec.
63.670(k) through (n) as applicable.
(iv) For flaring events meeting the criteria in Sec. 63.670(o)(3):
(A) The start and stop time and date of the flaring event.
(B) The length of time for which emissions were visible from the
flare during the event.
(C) The periods of time that the flare tip velocity exceeds the
maximum flare tip velocity determined using the methods in Sec.
63.670(d)(2) and the maximum 15-minute block average flare tip velocity
recorded during the event.
(D) Results of the root cause and corrective actions analysis
completed during the reporting period, including the corrective actions
implemented during the reporting period and, if applicable, the
implementation schedule for planned corrective actions to be
implemented subsequent to the reporting period.
(12) For delayed coking units, the Periodic Report must include the
information specified in paragraphs (g)(12)(i) through (iv) of this
section.
(i) For existing source delayed coking units, any 60-cycle average
exceeding the applicable limit in Sec. 63.657(a)(1).
(ii) For new source delayed coking units, any direct venting event
[[Page 75250]]
exceeding the applicable limit in Sec. 63.657(a)(2).
(iii) The total number of double quenching events performed during
the reporting period.
(iv) For each double quenching draining event when the drain water
temperature exceeded 210 [deg]F, report the drum, date, time, the coke
drum vessel pressure or temperature, as applicable, when pre-vent
draining was initiated, and the maximum drain water temperature during
the pre-vent draining period.
(13) For maintenance vents subject to the requirements in Sec.
63.643(c), Periodic Reports must include the information specified in
paragraphs (g)(13)(i) through (iv) of this section for any release
exceeding the applicable limits in Sec. 63.643(c)(1). For the purposes
of this reporting requirement, owners or operators complying with Sec.
63.643(c)(1)(iv) must report each venting event for which the lower
explosive limit is 20 percent or greater.
(i) Identification of the maintenance vent and the equipment served
by the maintenance vent.
(ii) The date and time the maintenance vent was opened to the
atmosphere.
(iii) The lower explosive limit, vessel pressure, or mass of VOC in
the equipment, as applicable, at the start of atmospheric venting. If
the 5 psig vessel pressure option in Sec. 63.643(c)(1)(ii) was used
and active purging was initiated while the lower explosive limit was 10
percent or greater, also include the lower explosive limit of the
vapors at the time active purging was initiated.
(iv) An estimate of the mass of organic HAP released during the
entire atmospheric venting event.
(14) Any changes in the information provided in a previous
Notification of Compliance Status report.
(h) * * *
(2) For storage vessels, notifications of inspections as specified
in paragraphs (h)(2)(i) and (ii) of this section.
(i) * * *
(B) Except as provided in paragraph (h)(2)(i)(C) of this section,
if the internal inspection required by Sec. 63.120(a)(2), (a)(3), or
(b)(10) of subpart G or Sec. 63.1063(d)(1) of subpart WW is not
planned and the owner or operator could not have known about the
inspection 30 calendar days in advance of refilling the vessel with
organic HAP, the owner or operator shall notify the Administrator at
least 7 calendar days prior to refilling of the storage vessel.
Notification may be made by telephone and immediately followed by
written documentation demonstrating why the inspection was unplanned.
This notification, including the written documentation, may also be
made in writing and sent so that it is received by the Administrator at
least 7 calendar days prior to the refilling.
* * * * *
(ii) In order to afford the Administrator the opportunity to have
an observer present, the owner or operator of a storage vessel equipped
with an external floating roof shall notify the Administrator of any
seal gap measurements. The notification shall be made in writing at
least 30 calendar days in advance of any gap measurements required by
Sec. 63.120(b)(1) or (2) of subpart G or Sec. 63.1062(d)(3) of
subpart WW. The State or local permitting authority can waive this
notification requirement for all or some storage vessels subject to the
rule or can allow less than 30 calendar days' notice.
* * * * *
(5) * * *
(iii) An owner or operator may use an automated data compression
recording system that does not record monitored operating parameter
values at a set frequency (for example, once every hour) but records
all values that meet set criteria for variation from previously
recorded values.
(A) The system shall be designed to:
(1) Measure the operating parameter value at least once every hour.
(2) Record at least 24 values each day during periods of operation.
(3) Record the date and time when monitors are turned off or on.
(4) Recognize unchanging data that may indicate the monitor is not
functioning properly, alert the operator, and record the incident.
(5) Compute daily average values of the monitored operating
parameter based on recorded data.
(B) You must maintain a record of the description of the monitoring
system and data compression recording system including the criteria
used to determine which monitored values are recorded and retained, the
method for calculating daily averages, and a demonstrations that they
system meets all criteria of paragraph (h)(5)(iii)(A) of this section.
* * * * *
(8) For fenceline monitoring systems subject to Sec. 63.658,
within 45 calendar days after the end of each quarterly reporting
period covered by the periodic report, each owner or operator shall
submit the following information to the EPA's Compliance and Emissions
Data Reporting Interface (CEDRI). (CEDRI can be accessed through the
EPA's Central Data Exchange (CDX) (https://cdx.epa.gov/). The owner or
operator need not transmit this data prior to obtaining 12 months of
data.
(i) Individual sample results for each monitor for each sampling
period during the quarterly reporting period. For the first reporting
period and for any period in which a passive monitor is added or moved,
the owner or operator shall report the coordinates of all of the
passive monitor locations. The owner or operator shall determine the
coordinates using an instrument with an accuracy of at least 3 meters.
Coordinates shall be in decimal degrees with at least five decimal
places.
(ii) The biweekly annual average concentration difference
([Delta]c) values for benzene for the quarterly reporting period.
(iii) Notation for each biweekly value that indicates whether
background correction was used, all measurements in the sampling period
were below detection, or whether an outlier was removed from the
sampling period data set.
(9) On and after February 1, 2016, if required to submit the
results of a performance test or CEMS performance evaluation, the owner
or operator shall submit the results according to the procedures in
paragraphs (h)(9)(i) and (ii) of this section.
(i) Within 60 days after the date of completing each performance
test as required by this subpart, the owner or operator shall submit
the results of the performance tests following the procedure specified
in either paragraph (h)(9)(i)(A) or (B) of this section.
(A) For data collected using test methods supported by the EPA's
Electronic Reporting Tool (ERT) as listed on the EPA's ERT Web site
(https://www.epa.gov/ttn/chief/ert/) at the time of the test,
the owner or operator must submit the results of the performance test
to the EPA via the CEDRI. (CEDRI can be accessed through the EPA's
CDX.) Performance test data must be submitted in a file format
generated through the use of the EPA's ERT or an alternate electronic
file format consistent with the extensible markup language (XML) schema
listed on the EPA's ERT Web site. If an owner or operator claims that
some of the performance test information being submitted is
confidential business information (CBI), the owner or operator must
submit a complete file generated through the use of the EPA's ERT or an
alternate electronic file consistent with the XML schema listed on the
EPA's ERT Web site, including information claimed to be CBI, on a
compact disc, flash drive or other commonly used electronic storage
media to the EPA. The electronic storage media must be clearly marked
as CBI and mailed to U.S. EPA/OAQPS/
[[Page 75251]]
CORE CBI Office, Attention: Group Leader, Measurement Policy Group, MD
C404-02, 4930 Old Page Rd., Durham, NC 27703. The same ERT or alternate
file with the CBI omitted must be submitted to the EPA via the EPA's
CDX as described earlier in this paragraph (h)(9)(i)(A).
(B) For data collected using test methods that are not supported by
the EPA's ERT as listed on the EPA's ERT Web site at the time of the
test, the owner or operator must submit the results of the performance
test to the Administrator at the appropriate address listed in Sec.
63.13.
(ii) Within 60 days after the date of completing each CEMS
performance evaluation as required by this subpart, the owner or
operator must submit the results of the performance evaluation
following the procedure specified in either paragraph (h)(9)(ii)(A) or
(B) of this section.
(A) For performance evaluations of continuous monitoring systems
measuring relative accuracy test audit (RATA) pollutants that are
supported by the EPA's ERT as listed on the EPA's ERT Web site at the
time of the evaluation, the owner or operator must submit the results
of the performance evaluation to the EPA via the CEDRI. (CEDRI can be
accessed through the EPA's CDX.) Performance evaluation data must be
submitted in a file format generated through the use of the EPA's ERT
or an alternate file format consistent with the XML schema listed on
the EPA's ERT Web site. If an owner or operator claims that some of the
performance evaluation information being submitted is CBI, the owner or
operator must submit a complete file generated through the use of the
EPA's ERT or an alternate electronic file consistent with the XML
schema listed on the EPA's ERT Web site, including information claimed
to be CBI, on a compact disc, flash drive or other commonly used
electronic storage media to the EPA. The electronic storage media must
be clearly marked as CBI and mailed to U.S. EPA/OAQPS/CORE CBI Office,
Attention: Group Leader, Measurement Policy Group, MD C404-02, 4930 Old
Page Rd., Durham, NC 27703. The same ERT or alternate file with the CBI
omitted must be submitted to the EPA via the EPA's CDX as described
earlier in this paragraph (h)(9)(ii)(A).
(B) For any performance evaluations of continuous monitoring
systems measuring RATA pollutants that are not supported by the EPA's
ERT as listed on the EPA's ERT Web site at the time of the evaluation,
the owner or operator must submit the results of the performance
evaluation to the Administrator at the appropriate address listed in
Sec. 63.13.
(i) Recordkeeping. Each owner or operator of a source subject to
this subpart shall keep copies of all applicable reports and records
required by this subpart for at least 5 years except as otherwise
specified in paragraphs (i)(1) through (12) of this section. All
applicable records shall be maintained in such a manner that they can
be readily accessed within 24 hours. Records may be maintained in hard
copy or computer-readable form including, but not limited to, on paper,
microfilm, computer, flash drive, floppy disk, magnetic tape, or
microfiche.
(1) Each owner or operator subject to the storage vessel provisions
in Sec. 63.646 shall keep the records specified in Sec. 63.123 of
subpart G except as specified in paragraphs (i)(1)(i) through (iv) of
this section. Each owner or operator subject to the storage vessel
provisions in Sec. 63.660 shall keep records as specified in
paragraphs (i)(1)(v) and (vi) of this section.
* * * * *
(ii) All references to Sec. 63.122 in Sec. 63.123 of subpart G
shall be replaced with Sec. 63.655(e).
* * * * *
(v) Each owner or operator of a Group 1 storage vessel subject to
the provisions in Sec. 63.660 shall keep records as specified in Sec.
63.1065 or Sec. 63.998, as applicable.
(vi) Each owner or operator of a Group 2 storage vessel shall keep
the records specified in Sec. 63.1065(a) of subpart WW. If a storage
vessel is determined to be Group 2 because the weight percent total
organic HAP of the stored liquid is less than or equal to 4 percent for
existing sources or 2 percent for new sources, a record of any data,
assumptions, and procedures used to make this determination shall be
retained.
* * * * *
(4) For each closed vent system that contains bypass lines that
could divert a vent stream away from the control device and either
directly to the atmosphere or to a control device that does not comply
with the requirements in Sec. 63.643(a), the owner or operator shall
keep a record of the information specified in either paragraph
(i)(4)(i) or (ii) of this section, as applicable.
(i) The owner or operator shall maintain records of periods when
flow was detected in the bypass line, including the date and time and
the duration of the flow in the bypass line. For each flow event, the
owner or operator shall maintain records sufficient to determine
whether or not the detected flow included flow of a Group 1
miscellaneous process vent stream requiring control. For periods when
the Group 1 miscellaneous process vent stream requiring control is
diverted from the control device and released either directly to the
atmosphere or to a control device that does not comply with the
requirements in Sec. 63.643(a), the owner or operator shall include an
estimate of the volume of gas, the concentration of organic HAP in the
gas and the resulting emissions of organic HAP that bypassed the
control device using process knowledge and engineering estimates.
(ii) Where a seal mechanism is used to comply with Sec.
63.644(c)(2), hourly records of flow are not required. In such cases,
the owner or operator shall record the date that the monthly visual
inspection of the seals or closure mechanisms is completed. The owner
or operator shall also record the occurrence of all periods when the
seal or closure mechanism is broken, the bypass line valve position has
changed or the key for a lock-and-key type lock has been checked out.
The owner or operator shall include an estimate of the volume of gas,
the concentration of organic HAP in the gas and the resulting mass
emissions of organic HAP from the Group 1 miscellaneous process vent
stream requiring control that bypassed the control device or records
sufficient to demonstrate that there was no flow of a Group 1
miscellaneous process vent stream requiring control during the period.
(5) The owner or operator of a heat exchange system subject to this
subpart shall comply with the recordkeeping requirements in paragraphs
(i)(5)(i) through (v) of this section and retain these records for 5
years.
* * * * *
(7) Each owner or operator subject to the delayed coking unit
decoking operations provisions in Sec. 63.657 must maintain records
specified in paragraphs (i)(7)(i) through (iii) of this section.
(i) The average pressure or temperature, as applicable, for the 5-
minute period prior to venting to the atmosphere, draining, or
deheading the coke drum for each cooling cycle for each coke drum.
(ii) If complying with the 60-cycle rolling average, each 60-cycle
rolling average pressure or temperature, as applicable, considering all
coke drum venting events in the existing affected source.
(iii) For double-quench cooling cycles:
[[Page 75252]]
(A) The date, time and duration of each pre-vent draining event.
(B) The pressure or temperature of the coke drum vessel, as
applicable, for the 15 minute period prior to the pre-vent draining.
(C) The drain water temperature at 1-minute intervals from the
start of pre-vent draining to the complete closure of the drain valve.
(8) For fenceline monitoring systems subject to Sec. 63.658, each
owner or operator shall keep the records specified in paragraphs
(i)(8)(i) through (x) of this section on an ongoing basis.
(i) Coordinates of all passive monitors, including replicate
samplers and field blanks, and if applicable, the meteorological
station. The owner or operator shall determine the coordinates using an
instrument with an accuracy of at least 3 meters. The coordinates shall
be in decimal degrees with at least five decimal places.
(ii) The start and stop times and dates for each sample, as well as
the tube identifying information.
(iii) Sampling period average temperature and barometric pressure
measurements.
(iv) For each outlier determined in accordance with Section 9.2 of
Method 325A of appendix A of this part, the sampler location of and the
concentration of the outlier and the evidence used to conclude that the
result is an outlier.
(v) For samples that will be adjusted for a background, the
location of and the concentration measured simultaneously by the
background sampler, and the perimeter samplers to which it applies.
(vi) Individual sample results, the calculated [Delta]c for benzene
for each sampling period and the two samples used to determine it,
whether background correction was used, and the annual average [Delta]c
calculated after each sampling period.
(vii) Method detection limit for each sample, including co-located
samples and blanks.
(viii) Documentation of corrective action taken each time the
action level was exceeded.
(ix) Other records as required by Methods 325A and 325B of appendix
A of this part.
(x) If a near-field source correction is used as provided in Sec.
63.658(i), records of hourly meteorological data, including
temperature, barometric pressure, wind speed and wind direction,
calculated daily unit vector wind direction and daily sigma theta, and
other records specified in the site-specific monitoring plan.
(9) For each flare subject to Sec. 63.670, each owner or operator
shall keep the records specified in paragraphs (i)(9)(i) through (xii)
of this section up-to-date and readily accessible, as applicable.
(i) Retain records of the output of the monitoring device used to
detect the presence of a pilot flame as required in Sec. 63.670(b) for
a minimum of 2 years. Retain records of each 15-minute block during
which there was at least one minute that no pilot flame is present when
regulated material is routed to a flare for a minimum of 5 years.
(ii) Retain records of daily visible emissions observations or
video surveillance images required in Sec. 63.670(h) as specified in
the paragraphs (i)(9)(ii)(A) through (C), as applicable, for a minimum
of 3 years.
(A) If visible emissions observations are performed using Method 22
at 40 CFR part 60, appendix A-7, the record must identify whether the
visible emissions observation was performed, the results of each
observation, total duration of observed visible emissions, and whether
it was a 5-minute or 2-hour observation. If the owner or operator
performs visible emissions observations more than one time during a
day, the record must also identify the date and time of day each
visible emissions observation was performed.
(B) If video surveillance camera is used, the record must include
all video surveillance images recorded, with time and date stamps.
(C) For each 2 hour period for which visible emissions are observed
for more than 5 minutes in 2 consecutive hours, the record must include
the date and time of the 2 hour period and an estimate of the
cumulative number of minutes in the 2 hour period for which emissions
were visible.
(iii) The 15-minute block average cumulative flows for flare vent
gas and, if applicable, total steam, perimeter assist air, and premix
assist air specified to be monitored under Sec. 63.670(i), along with
the date and time interval for the 15-minute block. If multiple
monitoring locations are used to determine cumulative vent gas flow,
total steam, perimeter assist air, and premix assist air, retain
records of the 15-minute block average flows for each monitoring
location for a minimum of 2 years, and retain the 15-minute block
average cumulative flows that are used in subsequent calculations for a
minimum of 5 years. If pressure and temperature monitoring is used,
retain records of the 15-minute block average temperature, pressure and
molecular weight of the flare vent gas or assist gas stream for each
measurement location used to determine the 15-minute block average
cumulative flows for a minimum of 2 years, and retain the 15-minute
block average cumulative flows that are used in subsequent calculations
for a minimum of 5 years.
(iv) The flare vent gas compositions specified to be monitored
under Sec. 63.670(j). Retain records of individual component
concentrations from each compositional analyses for a minimum of 2
years. If NHVvg analyzer is used, retain records of the 15-minute block
average values for a minimum of 5 years.
(v) Each 15-minute block average operating parameter calculated
following the methods specified in Sec. 63.670(k) through (n), as
applicable.
(vi) [Reserved]
(vii) All periods during which operating values are outside of the
applicable operating limits specified in Sec. 63.670(d) through (f)
when regulated material is being routed to the flare.
(viii) All periods during which the owner or operator does not
perform flare monitoring according to the procedures in Sec. 63.670(g)
through (j).
(ix) Records of periods when there is flow of vent gas to the
flare, but when there is no flow of regulated material to the flare,
including the start and stop time and dates of periods of no regulated
material flow.
(x) Records when the flow of vent gas exceeds the smokeless
capacity of the flare, including start and stop time and dates of the
flaring event.
(xi) Records of the root cause analysis and corrective action
analysis conducted as required in Sec. 63.670(o)(3), including an
identification of the affected facility, the date and duration of the
event, a statement noting whether the event resulted from the same root
cause(s) identified in a previous analysis and either a description of
the recommended corrective action(s) or an explanation of why
corrective action is not necessary under Sec. 63.670(o)(5)(i).
(xii) For any corrective action analysis for which implementation
of corrective actions are required in Sec. 63.670(o)(5), a description
of the corrective action(s) completed within the first 45 days
following the discharge and, for action(s) not already completed, a
schedule for implementation, including proposed commencement and
completion dates.
(10) [Reserved]
(11) For each pressure relief device subject to the pressure
release management work practice standards in Sec. 63.648(j)(3), the
owner or operator shall keep the records specified in paragraphs
(i)(11)(i) through (iii) of this section.
(i) Records of the prevention measures implemented as required in
Sec. 63.648(j)(3)(ii), if applicable.
[[Page 75253]]
(ii) Records of the number of releases during each calendar year
and the number of those releases for which the root cause was
determined to be a force majeure event. Keep these records for the
current calendar year and the past five calendar years.
(iii) For each release to the atmosphere, the owner or operator
shall keep the records specified in paragraphs (i)(11)(iii)(A) through
(D) of this section.
(A) The start and end time and date of each pressure release to the
atmosphere.
(B) Records of any data, assumptions, and calculations used to
estimate of the mass quantity of each organic HAP released during the
event.
(C) Records of the root cause analysis and corrective action
analysis conducted as required in Sec. 63.648(j)(3)(iii), including an
identification of the affected facility, the date and duration of the
event, a statement noting whether the event resulted from the same root
cause(s) identified in a previous analysis and either a description of
the recommended corrective action(s) or an explanation of why
corrective action is not necessary under Sec. 63.648(j)(7)(i).
(D) For any corrective action analysis for which implementation of
corrective actions are required in Sec. 63.648(j)(7), a description of
the corrective action(s) completed within the first 45 days following
the discharge and, for action(s) not already completed, a schedule for
implementation, including proposed commencement and completion dates.
(12) For each maintenance vent opening subject to the requirements
in Sec. 63.643(c), the owner or operator shall keep the applicable
records specified in (i)(12)(i) through (v) of this section.
(i) The owner or operator shall maintain standard site procedures
used to deinventory equipment for safety purposes (e.g., hot work or
vessel entry procedures) to document the procedures used to meet the
requirements in Sec. 63.643(c). The current copy of the procedures
shall be retained and available on-site at all times. Previous versions
of the standard site procedures, is applicable, shall be retained for
five years.
(ii) If complying with the requirements of Sec. 63.643(c)(1)(i)
and the lower explosive limit at the time of the vessel opening exceeds
10 percent, identification of the maintenance vent, the process units
or equipment associated with the maintenance vent, the date of
maintenance vent opening, and the lower explosive limit at the time of
the vessel opening.
(iii) If complying with the requirements of Sec. 63.643(c)(1)(ii)
and either the vessel pressure at the time of the vessel opening
exceeds 5 psig or the lower explosive limit at the time of the active
purging was initiated exceeds 10 percent, identification of the
maintenance vent, the process units or equipment associated with the
maintenance vent, the date of maintenance vent opening, the pressure of
the vessel or equipment at the time of discharge to the atmosphere and,
if applicable, the lower explosive limit of the vapors in the equipment
when active purging was initiated.
(iv) If complying with the requirements of Sec. 63.643(c)(1)(iii),
identification of the maintenance vent, the process units or equipment
associated with the maintenance vent, the date of maintenance vent
opening, and records used to estimate the total quantity of VOC in the
equipment at the time the maintenance vent was opened to the atmosphere
for each applicable maintenance vent opening.
(v) If complying with the requirements of Sec. 63.643(c)(1)(iv),
identification of the maintenance vent, the process units or equipment
associated with the maintenance vent, records documenting the lack of a
pure hydrogen supply, the date of maintenance vent opening, and the
lower explosive limit of the vapors in the equipment at the time of
discharge to the atmosphere for each applicable maintenance vent
opening.
0
28. Section 63.656 is amended by revising paragraph (c)(1) to read as
follows:
Sec. 63.656 Implementation and enforcement.
* * * * *
(c) * * *
(1) Approval of alternatives to the requirements in Sec. Sec.
63.640, 63.642(g) through (l), 63.643, 63.646 through 63.652, 63.654,
63.657 through 63.660, and 63.670. Where these standards reference
another subpart, the cited provisions will be delegated according to
the delegation provisions of the referenced subpart. Where these
standards reference another subpart and modify the requirements, the
requirements shall be modified as described in this subpart. Delegation
of the modified requirements will also occur according to the
delegation provisions of the referenced subpart.
* * * * *
0
29. Section 63.657 is added to read as follows:
Sec. 63.657 Delayed coking unit decoking operation standards.
(a) Except as provided in paragraphs (e) and (f) of this section,
each owner or operator of a delayed coking unit shall depressure each
coke drum to a closed blowdown system until the coke drum vessel
pressure or temperature measured at the top of the coke drum or in the
overhead line of the coke drum as near as practical to the coke drum
meets the applicable limits specified in paragraph (a)(1) or (2) of
this section prior to venting to the atmosphere, draining or deheading
the coke drum at the end of the cooling cycle.
(1) For delayed coking units at an existing affected source, meet
either:
(i) An average vessel pressure of 2 psig determined on a rolling
60-event average; or
(ii) An average vessel temperature of 220 degrees Fahrenheit
determined on a rolling 60-event average.
(2) For delayed coking units at a new affected source, meet either:
(i) A vessel pressure of 2.0 psig for each decoking event; or
(ii) A vessel temperature of 218 degrees Fahrenheit for each
decoking event.
(b) Each owner or operator of a delayed coking unit complying with
the pressure limits in paragraph (a)(1)(i) or (a)(2)(i) of this section
shall install, operate, calibrate, and maintain a monitoring system, as
specified in paragraphs (b)(1) through (5) of this section, to
determine the coke drum vessel pressure.
(1) The pressure monitoring system must be in a representative
location (at the top of the coke drum or in the overhead line as near
as practical to the coke drum) that minimizes or eliminates pulsating
pressure, vibration, and, to the extent practical, internal and
external corrosion.
(2) The pressure monitoring system must be capable of measuring a
pressure of 2.0 psig within 0.5 psig.
(3) The pressure monitoring system must be verified annually or at
the frequency recommended by the instrument manufacturer. The pressure
monitoring system must be verified following any period of more than 24
hours throughout which the pressure exceeded the maximum rated pressure
of the sensor, or the data recorder was off scale.
(4) All components of the pressure monitoring system must be
visually inspected for integrity, oxidation and galvanic corrosion
every 3 months, unless the system has a redundant pressure sensor.
(5) The output of the pressure monitoring system must be reviewed
[[Page 75254]]
daily to ensure that the pressure readings fluctuate as expected
between operating and cooling/decoking cycles to verify the pressure
taps are not plugged. Plugged pressure taps must be unplugged or
otherwise repaired prior to the next operating cycle.
(c) Each owner or operator of a delayed coking unit complying with
the temperature limits in paragraph (a)(1)(ii) or (a)(2)(ii) of this
section shall install, operate, calibrate, and maintain a continuous
parameter monitoring system to measure the coke drum vessel temperature
(at the top of the coke drum or in the overhead line as near as
practical to the coke drum) according to the requirements specified in
table 13 of this subpart.
(d) The owner or operator of a delayed coking unit shall determine
the coke drum vessel pressure or temperature, as applicable, on a 5-
minute rolling average basis while the coke drum is vented to the
closed blowdown system and shall use the last complete 5-minute rolling
average pressure or temperature just prior to initiating steps to
isolate the coke drum prior to venting, draining or deheading to
demonstrate compliance with the requirements in paragraph (a) of this
section. Pressure or temperature readings after initiating steps to
isolate the coke drum from the closed blowdown system just prior to
atmospheric venting, draining, or deheading the coke drum shall not be
used in determining the average coke drum vessel pressure or
temperature for the purpose of compliance with the requirements in
paragraph (a) of this section.
(e) The owner or operator of a delayed coking unit using the
``water overflow'' method of coke cooling must hardpipe the overflow
water or otherwise prevent exposure of the overflow water to the
atmosphere when transferring the overflow water to the overflow water
storage tank whenever the coke drum vessel temperature exceeds 220
degrees Fahrenheit. The overflow water storage tank may be an open or
fixed-roof tank provided that a submerged fill pipe (pipe outlet below
existing liquid level in the tank) is used to transfer overflow water
to the tank. The owner or operator of a delayed coking unit using the
``water overflow'' method of coke cooling shall determine the coke drum
vessel temperature as specified in paragraphs (c) and (d) of this
section regardless of the compliance method used to demonstrate
compliance with the requirements in paragraph (a) of this section.
(f) The owner or operator of a delayed coking unit may partially
drain a coke drum prior to achieving the applicable limits in paragraph
(a) of this section in order to double-quench a coke drum that did not
cool adequately using the normal cooling process steps provided that
the owner or operator meets the conditions in paragraphs (f)(1) and (2)
of this section.
(1) The owner or operator shall install, operate, calibrate, and
maintain a continuous parameter monitoring system to measure the drain
water temperature at the bottom of the coke drum or in the drain line
as near as practical to the coke drum according to the requirements
specified in table 13 of this subpart.
(2) The owner or operator must maintain the drain water temperature
below 210 degrees Fahrenheit during the partial drain associated with
the double-quench event.
0
30. Section 63.658 is added to read as follows:
Sec. 63.658 Fenceline monitoring provisions.
(a) The owner or operator shall conduct sampling along the facility
property boundary and analyze the samples in accordance with Methods
325A and 325B of appendix A of this part and paragraphs (b) through (k)
of this section.
(b) The target analyte is benzene.
(c) The owner or operator shall determine passive monitor locations
in accordance with Section 8.2 of Method 325A of appendix A of this
part.
(1) As it pertains to this subpart, known sources of VOCs, as used
in Section 8.2.1.3 in Method 325A of appendix A of this part for siting
passive monitors means a wastewater treatment unit, process unit, or
any emission source requiring control according to the requirements of
this subpart, including marine vessel loading operations. For marine
loading operations that are located offshore, one passive monitor
should be sited on the shoreline adjacent to the dock.
(2) The owner or operator may collect one or more background
samples if the owner or operator believes that an offsite upwind source
or an onsite source excluded under Sec. 63.640(g) may influence the
sampler measurements. If the owner or operator elects to collect one or
more background samples, the owner of operator must develop and submit
a site-specific monitoring plan for approval according to the
requirements in paragraph (i) of this section. Upon approval of the
site-specific monitoring plan, the background sampler(s) should be
operated co-currently with the routine samplers.
(3) The owner or operator shall collect at least one co-located
duplicate sample for every 10 field samples per sampling period and at
least two field blanks per sampling period, as described in Section 9.3
in Method 325A of appendix A of this part. The co-located duplicates
may be collected at any one of the perimeter sampling locations.
(4) The owner or operator shall follow the procedure in Section 9.6
of Method 325B of appendix A of this part to determine the detection
limit of benzene for each sampler used to collect samples, background
samples (if the owner or operator elects to do so), co-located samples
and blanks.
(d) The owner or operator shall collect and record meteorological
data according to the applicable requirements in paragraphs (d)(1)
through (3) of this section.
(1) If a near-field source correction is used as provided in
paragraph (i)(1) of this section or if an alternative test method is
used that provides time-resolved measurements, the owner or operator
shall:
(i) Use an on-site meteorological station in accordance with
Section 8.3 of Method 325A of appendix A of this part.
(ii) Collect and record hourly average meteorological data,
including temperature, barometric pressure, wind speed and wind
direction and calculate daily unit vector wind direction and daily
sigma theta.
(2) For cases other than those specified in paragraph (d)(1) of
this section, the owner or operator shall collect and record sampling
period average temperature and barometric pressure using either an on-
site meteorological station in accordance with Section 8.3 of Method
325A of appendix A of this part or, alternatively, using data from a
United States Weather Service (USWS) meteorological station provided
the USWS meteorological station is within 40 kilometers (25 miles) of
the refinery.
(3) If an on-site meteorological station is used, the owner or
operator shall follow the calibration and standardization procedures
for meteorological measurements in EPA-454/B-08-002 (incorporated by
reference--see Sec. 63.14).
(e) The owner of operator shall use a sampling period and sampling
frequency as specified in paragraphs (e)(1) through (3) of this
section.
(1) Sampling period. A 14-day sampling period shall be used, unless
a shorter sampling period is determined to be necessary under paragraph
(g) or (i) of this section. A sampling period is defined as the period
during which sampling tube is deployed at a specific sampling location
with the diffusive
[[Page 75255]]
sampling end cap in-place and does not include the time required to
analyze the sample. For the purpose of this subpart, a 14-day sampling
period may be no shorter than 13 calendar days and no longer than 15
calendar days, but the routine sampling period shall be 14 calendar
days.
(2) Base sampling frequency. Except as provided in paragraph (e)(3)
of this section, the frequency of sample collection shall be once each
contiguous 14-day sampling period, such that the beginning of the next
14-day sampling period begins immediately upon the completion of the
previous 14-day sampling period.
(3) Alternative sampling frequency for burden reduction. When an
individual monitor consistently achieves results at or below 0.9 [mu]g/
m\3\, the owner or operator may elect to use the applicable minimum
sampling frequency specified in paragraphs (e)(3)(i) through (v) of
this section for that monitoring site. When calculating [Delta]c for
the monitoring period when using this alternative for burden reduction,
zero shall be substituted for the sample result for the monitoring site
for any period where a sample is not taken.
(i) If every sample at a monitoring site is at or below 0.9 [mu]g/
m3 for 2 years (52 consecutive samples), every other
sampling period can be skipped for that monitoring site, i.e., sampling
will occur approximately once per month.
(ii) If every sample at a monitoring site that is monitored at the
frequency specified in paragraph (e)(3)(i) of this section is at or
below 0.9 [mu]g/m3 for 2 years (i.e., 26 consecutive
``monthly'' samples), five 14-day sampling periods can be skipped for
that monitoring site following each period of sampling, i.e., sampling
will occur approximately once per quarter.
(iii) If every sample at a monitoring site that is monitored at the
frequency specified in paragraph (e)(3)(ii) of this section is at or
below 0.9 [mu]g/m3 for 2 years (i.e., 8 consecutive
quarterly samples), twelve 14-day sampling periods can be skipped for
that monitoring site following each period of sampling, i.e., sampling
will occur twice a year.
(iv) If every sample at a monitoring site that is monitored at the
frequency specified in paragraph (e)(3)(iii) of this section is at or
below 0.9 [mu]g/m3 for an 2 years (i.e., 4 consecutive semi-
annual samples), only one sample per year is required for that
monitoring site. For yearly sampling, samples shall occur at least 10
months but no more than 14 months apart.
(v) If at any time a sample for a monitoring site that is monitored
at the frequency specified in paragraphs (e)(3)(i) through (iv) of this
section returns a result that is above 0.9 [mu]g/m\3\, the sampling
site must return to the original sampling requirements of contiguous
14-day sampling periods with no skip periods for one quarter (six 14-
day sampling periods). If every sample collected during this quarter is
at or below 0.9 [mu]g/m3 , the owner or operator may revert
back to the reduced monitoring schedule applicable for that monitoring
site prior to the sample reading exceeding 0.9 [mu]g/m3 If
any sample collected during this quarter is above 0.9 [mu]g/m\3\, that
monitoring site must return to the original sampling requirements of
contiguous 14-day sampling periods with no skip periods for a minimum
of two years. The burden reduction requirements can be used again for
that monitoring site once the requirements of paragraph (e)(3)(i) of
this section are met again, i.e., after 52 contiguous 14-day samples
with no results above 0.9 [mu]g/m3 .
(f) Within 45 days of completion of each sampling period, the owner
or operator shall determine whether the results are above or below the
action level as follows:
(1) The owner or operator shall determine the facility impact on
the benzene concentration ([Delta]c) for each 14-day sampling period
according to either paragraph (f)(1)(i) or (ii) of this section, as
applicable.
(i) Except when near-field source correction is used as provided in
paragraph (i) of this section, the owner or operator shall determine
the highest and lowest sample results for benzene concentrations from
the sample pool and calculate [Delta]c as the difference in these
concentrations. The owner or operator shall adhere to the following
procedures when one or more samples for the sampling period are below
the method detection limit for benzene:
(A) If the lowest detected value of benzene is below detection, the
owner or operator shall use zero as the lowest sample result when
calculating [Delta]c.
(B) If all sample results are below the method detection limit, the
owner or operator shall use the method detection limit as the highest
sample result.
(ii) When near-field source correction is used as provided in
paragraph (i) of this section, the owner or operator shall determine
[Delta]c using the calculation protocols outlined in the approved site-
specific monitoring plan and in paragraph (i) of this section.
(2) The owner or operator shall calculate the annual average
[Delta]c based on the average of the 26 most recent 14-day sampling
periods. The owner or operator shall update this annual average value
after receiving the results of each subsequent 14-day sampling period.
(3) The action level for benzene is 9 micrograms per cubic meter
([mu]g/m3) on an annual average basis. If the annual average [Delta]c
value for benzene is less than or equal to 9 [mu]g/m\3\, the
concentration is below the action level. If the annual average [Delta]c
value for benzene is greater than 9 [mu]g/m\3\, the concentration is
above the action level, and the owner or operator shall conduct a root
cause analysis and corrective action in accordance with paragraph (g)
of this section.
(g) Within 5 days of determining that the action level has been
exceeded for any annual average [Delta]c and no longer than 50 days
after completion of the sampling period, the owner or operator shall
initiate a root cause analysis to determine the cause of such
exceedance and to determine appropriate corrective action, such as
those described in paragraphs (g)(1) through (4) of this section. The
root cause analysis and initial corrective action analysis shall be
completed and initial corrective actions taken no later than 45 days
after determining there is an exceedance. Root cause analysis and
corrective action may include, but is not limited to:
(1) Leak inspection using Method 21 of part 60, appendix A-7 of
this chapter and repairing any leaks found.
(2) Leak inspection using optical gas imaging and repairing any
leaks found.
(3) Visual inspection to determine the cause of the high benzene
emissions and implementing repairs to reduce the level of emissions.
(4) Employing progressively more frequent sampling, analysis and
meteorology (e.g., using shorter sampling periods for Methods 325A and
325B of appendix A of this part, or using active sampling techniques).
(h) If, upon completion of the corrective action analysis and
corrective actions such as those described in paragraph (g) of this
section, the [Delta]c value for the next 14-day sampling period for
which the sampling start time begins after the completion of the
corrective actions is greater than 9 [mu]g/m\3\ or if all corrective
action measures identified require more than 45 days to implement, the
owner or operator shall develop a corrective action plan that describes
the corrective action(s) completed to date, additional measures that
the owner or operator proposes to employ to reduce fenceline
concentrations below the action level, and a schedule for completion of
these measures. The owner or operator shall submit the corrective
action plan to the
[[Page 75256]]
Administrator within 60 days after receiving the analytical results
indicating that the [Delta]c value for the 14-day sampling period
following the completion of the initial corrective action is greater
than 9 [mu]g/m\3\ or, if no initial corrective actions were identified,
no later than 60 days following the completion of the corrective action
analysis required in paragraph (g) of this section.
(i) An owner or operator may request approval from the
Administrator for a site-specific monitoring plan to account for
offsite upwind sources or onsite sources excluded under Sec. 63.640(g)
according to the requirements in paragraphs (i)(1) through (4) of this
section.
(1) The owner or operator shall prepare and submit a site-specific
monitoring plan and receive approval of the site-specific monitoring
plan prior to using the near-field source alternative calculation for
determining [Delta]c provided in paragraph (i)(2) of this section. The
site-specific monitoring plan shall include, at a minimum, the elements
specified in paragraphs (i)(1)(i) through (v) of this section. The
procedures in Section 12 of Method 325A of appendix A of this part are
not required, but may be used, if applicable, when determining near-
field source contributions.
(i) Identification of the near-field source or sources. For onsite
sources, documentation that the onsite source is excluded under Sec.
63.640(g) and identification of the specific provision in Sec.
63.640(g) that applies to the source.
(ii) Location of the additional monitoring stations that shall be
used to determine the uniform background concentration and the near-
field source concentration contribution.
(iii) Identification of the fenceline monitoring locations impacted
by the near-field source. If more than one near-field source is
present, identify the near-field source or sources that are expected to
contribute to the concentration at that monitoring location.
(iv) A description of (including sample calculations illustrating)
the planned data reduction and calculations to determine the near-field
source concentration contribution for each monitoring location.
(v) If more frequent monitoring or a monitoring station other than
a passive diffusive tube monitoring station is proposed, provide a
detailed description of the measurement methods, measurement frequency,
and recording frequency for determining the uniform background or near-
field source concentration contribution.
(2) When an approved site-specific monitoring plan is used, the
owner or operator shall determine [Delta]c for comparison with the 9
[mu]g/m\3\ action level using the requirements specified in paragraphs
(i)(2)(i) through (iii) of this section.
(i) For each monitoring location, calculate [Delta]ci
using the following equation.
[Delta]ci = MFCi - NFSi - UB
Where:
[Delta]ci = The fenceline concentration, corrected for
background, at measurement location i, micrograms per cubic meter
([mu]g/m\3\).
MFCi = The measured fenceline concentration at
measurement location i, [mu]g/m\3\.
NFSi = The near-field source contributing concentration
at measurement location i determined using the additional
measurements and calculation procedures included in the site-
specific monitoring plan, [mu]g/m\3\. For monitoring locations that
are not included in the site-specific monitoring plan as impacted by
a near-field source, use NFSi = 0 [mu]g/m\3\.
UB = The uniform background concentration determined using the
additional measurements included in the site-specific monitoring
plan, [mu]g/m\3\. If no additional measurements are specified in the
site-specific monitoring plan for determining the uniform background
concentration, use UB = 0 [mu]g/m\3\.
(ii) When one or more samples for the sampling period are below the
method detection limit for benzene, adhere to the following procedures:
(A) If the benzene concentration at the monitoring location used
for the uniform background concentration is below the method detection
limit, the owner or operator shall use zero for UB for that monitoring
period.
(B) If the benzene concentration at the monitoring location(s) used
to determine the near-field source contributing concentration is below
the method detection limit, the owner or operator shall use zero for
the monitoring location concentration when calculating NFSi
for that monitoring period.
(C) If a fenceline monitoring location sample result is below the
method detection limit, the owner or operator shall use the method
detection limit as the sample result.
(iii) Determine [Delta]c for the monitoring period as the maximum
value of [Delta]ci from all of the fenceline monitoring
locations for that monitoring period.
(3) The site-specific monitoring plan shall be submitted and
approved as described in paragraphs (i)(3)(i) through (iv) of this
section.
(i) The site-specific monitoring plan must be submitted to the
Administrator for approval.
(ii) The site-specific monitoring plan shall also be submitted to
the following address: U.S. Environmental Protection Agency, Office of
Air Quality Planning and Standards, Sector Policies and Programs
Division, U.S. EPA Mailroom (E143-01), Attention: Refinery Sector Lead,
109 T.W. Alexander Drive, Research Triangle Park, NC 27711. Electronic
copies in lieu of hard copies may also be submitted to
refineryrtr@epa.gov.
(iii) The Administrator shall approve or disapprove the plan in 90
days. The plan shall be considered approved if the Administrator either
approves the plan in writing, or fails to disapprove the plan in
writing. The 90-day period shall begin when the Administrator receives
the plan.
(iv) If the Administrator finds any deficiencies in the site-
specific monitoring plan and disapproves the plan in writing, the owner
or operator may revise and resubmit the site-specific monitoring plan
following the requirements in paragraphs (i)(3)(i) and (ii) of this
section. The 90-day period starts over with the resubmission of the
revised monitoring plan.
(4) The approval by the Administrator of a site-specific monitoring
plan will be based on the completeness, accuracy and reasonableness of
the request for a site-specific monitoring plan. Factors that the
Administrator will consider in reviewing the request for a site-
specific monitoring plan include, but are not limited to, those
described in paragraphs (i)(4)(i) through (v) of this section.
(i) The identification of the near-field source or sources. For
onsite sources, the documentation provided that the onsite source is
excluded under Sec. 63.640(g).
(ii) The monitoring location selected to determine the uniform
background concentration or an indication that no uniform background
concentration monitor will be used.
(iii) The location(s) selected for additional monitoring to
determine the near-field source concentration contribution.
(iv) The identification of the fenceline monitoring locations
impacted by the near-field source or sources.
(v) The appropriateness of the planned data reduction and
calculations to determine the near-field source concentration
contribution for each monitoring location.
(vi) If more frequent monitoring is proposed, the adequacy of the
description of the measurement and
[[Page 75257]]
recording frequency proposed and the adequacy of the rationale for
using the alternative monitoring frequency.
(j) The owner or operator shall comply with the applicable
recordkeeping and reporting requirements in Sec. 63.655(h) and (i).
(k) As outlined in Sec. 63.7(f), the owner or operator may submit
a request for an alternative test method. At a minimum, the request
must follow the requirements outlined in paragraphs (k)(1) through (7)
of this section.
(1) The alternative method may be used in lieu of all or a partial
number of passive samplers required in Method 325A of appendix A of
this part.
(2) The alternative method must be validated according to Method
301 in appendix A of this part or contain performance based procedures
and indicators to ensure self-validation.
(3) The method detection limit must nominally be at least an order
of magnitude below the action level, i.e., 0.9 [micro]g/m3
benzene. The alternate test method must describe the procedures used to
provide field verification of the detection limit.
(4) The spatial coverage must be equal to or better than the
spatial coverage provided in Method 325A of appendix A of this part.
(i) For path average concentration open-path instruments, the
physical path length of the measurement shall be no more than a passive
sample footprint (the spacing that would be provided by the sorbent
traps when following Method 325A). For example, if Method 325A requires
spacing monitors A and B 610 meters (2000 feet) apart, then the
physical path length limit for the measurement at that portion of the
fenceline shall be no more than 610 meters (2000 feet).
(ii) For range resolved open-path instrument or approach, the
instrument or approach must be able to resolve an average concentration
over each passive sampler footprint within the path length of the
instrument.
(iii) The extra samplers required in Sections 8.2.1.3 of Method
325A may be omitted when they fall within the path length of an open-
path instrument.
(5) At a minimum, non-integrating alternative test methods must
provide a minimum of one cycle of operation (sampling, analyzing, and
data recording) for each successive 15-minute period.
(6) For alternative test methods capable of real time measurements
(less than a 5 minute sampling and analysis cycle), the alternative
test method may allow for elimination of data points corresponding to
outside emission sources for purpose of calculation of the high point
for the two week average. The alternative test method approach must
have wind speed, direction and stability class of the same time
resolution and within the footprint of the instrument.
(7) For purposes of averaging data points to determine the [Delta]c
for the 14-day average high sample result, all results measured under
the method detection limit must use the method detection limit. For
purposes of averaging data points for the 14-day average low sample
result, all results measured under the method detection limit must use
zero.
0
31. Section 63.660 is added to read as follows:
Sec. 63.660 Storage vessel provisions.
On and after the applicable compliance date for a Group 1 storage
vessel located at a new or existing source as specified in Sec.
63.640(h), the owner or operator of a Group 1 storage vessel that is
part of a new or existing source shall comply with the requirements in
subpart WW or SS of this part according to the requirements in
paragraphs (a) through (i) of this section.
(a) As used in this section, all terms not defined in Sec. 63.641
shall have the meaning given them in subpart A, WW, or SS of this part.
The definitions of ``Group 1 storage vessel'' (paragraph (2)) and
``Storage vessel'' in Sec. 63.641 shall apply in lieu of the
definition of ``Storage vessel'' in Sec. 63.1061.
(1) An owner or operator may use good engineering judgment or test
results to determine the stored liquid weight percent total organic HAP
for purposes of group determination. Data, assumptions, and procedures
used in the determination shall be documented.
(2) When an owner or operator and the Administrator do not agree on
whether the annual average weight percent organic HAP in the stored
liquid is above or below 4 percent for a storage vessel at an existing
source or above or below 2 percent for a storage vessel at a new
source, an appropriate method (based on the type of liquid stored) as
published by EPA or a consensus-based standards organization shall be
used. Consensus-based standards organizations include, but are not
limited to, the following: ASTM International (100 Barr Harbor Drive,
P.O. Box CB700, West Conshohocken, Pennsylvania 19428-B2959, (800) 262-
1373, https://www.astm.org), the American National Standards Institute
(ANSI, 1819 L Street NW., 6th Floor, Washington, DC 20036, (202) 293-
8020, https://www.ansi.org), the American Gas Association (AGA, 400
North Capitol Street NW., 4th Floor, Washington, DC 20001, (202) 824-
7000, https://www.aga.org), the American Society of Mechanical Engineers
(ASME, Three Park Avenue, New York, NY 10016-5990, (800) 843-2763,
https://www.asme.org), the American Petroleum Institute (API, 1220 L
Street NW., Washington, DC 20005-4070, (202) 682-8000, https://www.api.org), and the North American Energy Standards Board (NAESB, 801
Travis Street, Suite 1675, Houston, TX 77002, (713) 356-0060, https://www.naesb.org).
(b) A floating roof storage vessel complying with the requirements
of subpart WW of this part may comply with the control option specified
in paragraph (b)(1) of this section and, if equipped with a ladder
having at least one slotted leg, shall comply with one of the control
options as described in paragraph (b)(2) of this section.
(1) In addition to the options presented in Sec. Sec.
63.1063(a)(2)(viii)(A) and (B) and 63.1064, a floating roof storage
vessel may comply with Sec. 63.1063(a)(2)(vii) using a flexible
enclosure device and either a gasketed or welded cap on the top of the
guidepole.
(2) Each opening through a floating roof for a ladder having at
least one slotted leg shall be equipped with one of the configurations
specified in paragraphs (b)(2)(i) through (iii) of this section.
(i) A pole float in the slotted leg and pole wipers for both legs.
The wiper or seal of the pole float must be at or above the height of
the pole wiper.
(ii) A ladder sleeve and pole wipers for both legs of the ladder.
(iii) A flexible enclosure device and either a gasketed or welded
cap on the top of the slotted leg.
(c) For the purposes of this subpart, references shall apply as
specified in paragraphs (c)(1) through (6) of this section.
(1) All references to ``the proposal date for a referencing
subpart'' and ``the proposal date of the referencing subpart'' in
subpart WW of this part mean June 30, 2014.
(2) All references to ``promulgation of the referencing subpart''
and ``the promulgation date of the referencing subpart'' in subpart WW
of this part mean February 1, 2016.
(3) All references to ``promulgation date of standards for an
affected source or affected facility under a referencing subpart'' in
subpart SS of this part mean February 1, 2016.
(4) All references to ``the proposal date of the relevant standard
established pursuant to CAA section 112(f)'' in
[[Page 75258]]
subpart SS of this part mean June 30, 2014.
(5) All references to ``the proposal date of a relevant standard
established pursuant to CAA section 112(d)'' in subpart SS of this part
mean July 14, 1994.
(6) All references to the ``required control efficiency'' in
subpart SS of this part mean reduction of organic HAP emissions by 95
percent or to an outlet concentration of 20 ppmv.
(d) For an uncontrolled fixed roof storage vessel that commenced
construction on or before June 30, 2014, and that meets the definition
of ``Group 1 storage vessel'', paragraph (2), in Sec. 63.641 but not
the definition of ``Group 1 storage vessel'', paragraph (1), in Sec.
63.641, the requirements of Sec. 63.982 and/or Sec. 63.1062 do not
apply until the next time the storage vessel is completely emptied and
degassed, or January 30, 2026, whichever occurs first.
(e) Failure to perform inspections and monitoring required by this
section shall constitute a violation of the applicable standard of this
subpart.
(f) References in Sec. 63.1066(a) to initial startup notification
requirements do not apply.
(g) References to the Notification of Compliance Status in Sec.
63.999(b) mean the Notification of Compliance Status required by Sec.
63.655(f).
(h) References to the Periodic Reports in Sec. Sec. 63.1066(b) and
63.999(c) mean the Periodic Report required by Sec. 63.655(g).
(i) Owners or operators electing to comply with the requirements in
subpart SS of this part for a Group 1 storage vessel must comply with
the requirements in paragraphs (i)(1) through (3) of this section.
(1) If a flare is used as a control device, the flare shall meet
the requirements of Sec. 63.670 instead of the flare requirements in
Sec. 63.987.
(2) If a closed vent system contains a bypass line, the owner or
operator shall comply with the provisions of either Sec.
63.983(a)(3)(i) or (ii) for each closed vent system that contains
bypass lines that could divert a vent stream either directly to the
atmosphere or to a control device that does not comply with the
requirements in subpart SS of this part. Except as provided in
paragraphs (i)(2)(i) and (ii) of this section, use of the bypass at any
time to divert a Group 1 storage vessel to either directly to the
atmosphere or to a control device that does not comply with the
requirements in subpart SS of this part is an emissions standards
violation. Equipment such as low leg drains and equipment subject to
Sec. 63.648 are not subject to this paragraph (i)(2).
(i) If planned routine maintenance of the control device cannot be
performed during periods that storage vessel emissions are vented to
the control device or when the storage vessel is taken out of service
for inspections or other planned maintenance reasons, the owner or
operator may bypass the control device.
(ii) Periods for which storage vessel control device may be
bypassed for planned routine maintenance of the control device shall
not exceed 240 hours per calendar year.
(3) If storage vessel emissions are routed to a fuel gas system or
process, the fuel gas system or process shall be operating at all times
when regulated emissions are routed to it. The exception in Sec.
63.984(a)(1) does not apply.
0
32. Section 63.670 is added to read as follows:
Sec. 63.670 Requirements for flare control devices.
On or before January 30, 2019, the owner or operator of a flare
used as a control device for an emission point subject to this subpart
shall meet the applicable requirements for flares as specified in
paragraphs (a) through (q) of this section and the applicable
requirements in Sec. 63.671. The owner or operator may elect to comply
with the requirements of paragraph (r) of this section in lieu of the
requirements in paragraphs (d) through (f) of this section, as
applicable.
(a) [Reserved]
(b) Pilot flame presence. The owner or operator shall operate each
flare with a pilot flame present at all times when regulated material
is routed to the flare. Each 15-minute block during which there is at
least one minute where no pilot flame is present when regulated
material is routed to the flare is a deviation of the standard.
Deviations in different 15-minute blocks from the same event are
considered separate deviations. The owner or operator shall monitor for
the presence of a pilot flame as specified in paragraph (g) of this
section.
(c) Visible emissions. The owner or operator shall specify the
smokeless design capacity of each flare and operate with no visible
emissions, except for periods not to exceed a total of 5 minutes during
any 2 consecutive hours, when regulated material is routed to the flare
and the flare vent gas flow rate is less than the smokeless design
capacity of the flare. The owner or operator shall monitor for visible
emissions from the flare as specified in paragraph (h) of this section.
(d) Flare tip velocity. For each flare, the owner or operator shall
comply with either paragraph (d)(1) or (2) of this section, provided
the appropriate monitoring systems are in-place, whenever regulated
material is routed to the flare for at least 15-minutes and the flare
vent gas flow rate is less than the smokeless design capacity of the
flare.
(1) Except as provided in paragraph (d)(2) of this section, the
actual flare tip velocity (Vtip) must be less than 60 feet
per second. The owner or operator shall monitor Vtipusing
the procedures specified in paragraphs (i) and (k) of this section.
(2) Vtip must be less than 400 feet per second and also
less than the maximum allowed flare tip velocity (Vmax) as
calculated according to the following equation. The owner or operator
shall monitor Vtip using the procedures specified in paragraphs (i) and
(k) of this section and monitor gas composition and determine
NHVvg using the procedures specified in paragraphs (j) and
(l) of this section.
[GRAPHIC] [TIFF OMITTED] TR01DE15.008
Where:
Vmax = Maximum allowed flare tip velocity, ft/sec.
NHVvg = Net heating value of flare vent gas, as
determined by paragraph (l)(4) of this section, Btu/scf.
1,212 = Constant.
850 = Constant.
(e) Combustion zone operating limits. For each flare, the owner or
operator shall operate the flare to maintain the net heating value of
flare combustion zone gas (NHVcz) at or above 270 British
thermal units per standard cubic feet (Btu/scf) determined on a 15-
minute block period basis when regulated material is routed to the
flare for at least 15-minutes. The owner or operator shall monitor and
calculate NHVcz as specified in paragraph (m) of this
section.
(f) Dilution operating limits for flares with perimeter assist air.
For each flare actively receiving perimeter assist air, the owner or
operator shall operate the flare to maintain the net heating value
dilution parameter (NHVdil) at or above 22 British thermal units per
square foot (Btu/ft2) determined on a 15-minute block period
basis when regulated material is being routed to the flare for at least
15-minutes. The owner or operator shall monitor and calculate
NHVdil as specified in paragraph (n) of this section.
[[Page 75259]]
(g) Pilot flame monitoring. The owner or operator shall
continuously monitor the presence of the pilot flame(s) using a device
(including, but not limited to, a thermocouple, ultraviolet beam
sensor, or infrared sensor) capable of detecting that the pilot
flame(s) is present.
(h) Visible emissions monitoring. The owner or operator shall
monitor visible emissions while regulated materials are vented to the
flare. An initial visible emissions demonstration must be conducted
using an observation period of 2 hours using Method 22 at 40 CFR part
60, appendix A-7. Subsequent visible emissions observations must be
conducted using either the methods in paragraph (h)(1) of this section
or, alternatively, the methods in paragraph (h)(2) of this section. The
owner or operator must record and report any instances where visible
emissions are observed for more than 5 minutes during any 2 consecutive
hours as specified in Sec. 63.655(g)(11)(ii).
(1) At least once per day, conduct visible emissions observations
using an observation period of 5 minutes using Method 22 at 40 CFR part
60, appendix A-7. If at any time the owner or operator sees visible
emissions, even if the minimum required daily visible emission
monitoring has already been performed, the owner or operator shall
immediately begin an observation period of 5 minutes using Method 22 at
40 CFR part 60, appendix A-7. If visible emissions are observed for
more than one continuous minute during any 5-minute observation period,
the observation period using Method 22 at 40 CFR part 60, appendix A-7
must be extended to 2 hours or until 5-minutes of visible emissions are
observed.
(2) Use a video surveillance camera to continuously record (at
least one frame every 15 seconds with time and date stamps) images of
the flare flame and a reasonable distance above the flare flame at an
angle suitable for visual emissions observations. The owner or operator
must provide real-time video surveillance camera output to the control
room or other continuously manned location where the camera images may
be viewed at any time.
(i) Flare vent gas, steam assist and air assist flow rate
monitoring. The owner or operator shall install, operate, calibrate,
and maintain a monitoring system capable of continuously measuring,
calculating, and recording the volumetric flow rate in the flare header
or headers that feed the flare as well as any supplemental natural gas
used. Different flow monitoring methods may be used to measure
different gaseous streams that make up the flare vent gas provided that
the flow rates of all gas streams that contribute to the flare vent gas
are determined. If assist air or assist steam is used, the owner or
operator shall install, operate, calibrate, and maintain a monitoring
system capable of continuously measuring, calculating, and recording
the volumetric flow rate of assist air and/or assist steam used with
the flare. If pre-mix assist air and perimeter assist are both used,
the owner or operator shall install, operate, calibrate, and maintain a
monitoring system capable of separately measuring, calculating, and
recording the volumetric flow rate of premix assist air and perimeter
assist air used with the flare. Continuously monitoring fan speed or
power and using fan curves is an acceptable method for continuously
monitoring assist air flow rates.
(1) The flow rate monitoring systems must be able to correct for
the temperature and pressure of the system and output parameters in
standard conditions (i.e., a temperature of 20 [deg]C
(68[emsp14][deg]F) and a pressure of 1 atmosphere).
(2) Mass flow monitors may be used for determining volumetric flow
rate of flare vent gas provided the molecular weight of the flare vent
gas is determined using compositional analysis as specified in
paragraph (j) of this section so that the mass flow rate can be
converted to volumetric flow at standard conditions using the following
equation.
[GRAPHIC] [TIFF OMITTED] TR01DE15.009
Where:
Qvol = Volumetric flow rate, standard cubic feet per
second.
Qmass = Mass flow rate, pounds per second.
385.3 = Conversion factor, standard cubic feet per pound-mole.
MWt = Molecular weight of the gas at the flow monitoring location,
pounds per pound-mole.
(3) Mass flow monitors may be used for determining volumetric flow
rate of assist air or assist steam. Use equation in paragraph (i)(2) of
this section to convert mass flow rates to volumetric flow rates. Use a
molecular weight of 18 pounds per pound-mole for assist steam and use a
molecular weight of 29 pounds per pound-mole for assist air.
(4) Continuous pressure/temperature monitoring system(s) and
appropriate engineering calculations may be used in lieu of a
continuous volumetric flow monitoring systems provided the molecular
weight of the gas is known. For assist steam, use a molecular weight of
18 pounds per pound-mole. For assist air, use a molecular weight of 29
pounds per pound-mole. For flare vent gas, molecular weight must be
determined using compositional analysis as specified in paragraph (j)
of this section.
(j) Flare vent gas composition monitoring. The owner or operator
shall determine the concentration of individual components in the flare
vent gas using either the methods provided in paragraph (j)(1) or (2)
of this section, to assess compliance with the operating limits in
paragraph (e) of this section and, if applicable, paragraphs (d) and
(f) of this section. Alternatively, the owner or operator may elect to
directly monitor the net heating value of the flare vent gas following
the methods provided in paragraphs (j)(3) of this section and, if
desired, may directly measure the hydrogen concentration in the flare
vent gas following the methods provided in paragraphs (j)(4) of this
section. The owner or operator may elect to use different monitoring
methods for different gaseous streams that make up the flare vent gas
using different methods provided the composition or net heating value
of all gas streams that contribute to the flare vent gas are
determined.
(1) Except as provided in paragraphs (j)(5) and (6) of this
section, the owner or operator shall install, operate, calibrate, and
maintain a monitoring system capable of continuously measuring (i.e.,
at least once every 15-minutes), calculating, and recording the
individual component concentrations present in the flare vent gas.
(2) Except as provided in paragraphs (j)(5) and (6) of this
section, the owner or operator shall install, operate, and maintain a
grab sampling system capable of collecting an evacuated canister sample
for subsequent compositional analysis at least once every eight hours
while there is flow of regulated material to the flare. Subsequent
compositional analysis of the samples must be performed according to
Method 18 of 40 CFR part 60, appendix A-6, ASTM D6420-99 (Reapproved
2010), ASTM D1945-03 (Reapproved 2010), ASTM D1945-14 or ASTM UOP539-12
(all incorporated by reference--see Sec. 63.14).
(3) Except as provided in paragraphs (j)(5) and (6) of this
section, the owner or operator shall install, operate, calibrate, and
maintain a calorimeter capable of continuously measuring, calculating,
and recording NHVvg at standard conditions.
(4) If the owner or operator uses a continuous net heating value
monitor according to paragraph (j)(3) of this section, the owner or
operator may, at their discretion, install, operate, calibrate, and
maintain a monitoring
[[Page 75260]]
system capable of continuously measuring, calculating, and recording
the hydrogen concentration in the flare vent gas.
(5) Direct compositional or net heating value monitoring is not
required for purchased (``pipeline quality'') natural gas streams. The
net heating value of purchased natural gas streams may be determined
using annual or more frequent grab sampling at any one representative
location. Alternatively, the net heating value of any purchased natural
gas stream can be assumed to be 920 Btu/scf.
(6) Direct compositional or net heating value monitoring is not
required for gas streams that have been demonstrated to have consistent
composition (or a fixed minimum net heating value) according to the
methods in paragraphs (j)(6)(i) through (v) of this section.
(i) The owner or operator shall submit to the Administrator a
written application for an exemption from monitoring. The application
must contain the following information:
(A) A description of the flare gas stream/system to be considered,
including submission of a portion of the appropriate piping diagrams
indicating the boundaries of the flare gas stream/system and the
affected flare(s) to be considered;
(B) A statement that there are no crossover or entry points to be
introduced into the flare gas stream/system (this should be shown in
the piping diagrams) prior to the point where the flow rate of the gas
streams is measured;
(C) An explanation of the conditions that ensure that the flare gas
net heating value is consistent and, if flare gas net heating value is
expected to vary (e.g., due to product loading of different material),
the conditions expected to produce the flare gas with the lowest net
heating value;
(D) The supporting test results from sampling the requested flare
gas stream/system for the net heating value. Sampling data must
include, at minimum, 2 weeks of daily measurement values (14 grab
samples) for frequently operated flare gas streams/systems; for
infrequently operated flare gas streams/systems, seven grab samples
must be collected unless other additional information would support
reduced sampling. If the flare gas stream composition can vary, samples
must be taken during those conditions expected to result in lowest net
heating value identified in paragraph (j)(6)(i)(C) of this section. The
owner or operator shall determine net heating value for the gas stream
using either gas composition analysis or net heating value monitor
(with optional hydrogen concentration analyzer) according to the method
provided in paragraph (l) of this section; and
(E) A description of how the 2 weeks (or seven samples for
infrequently operated flare gas streams/systems) of monitoring results
compares to the typical range of net heating values expected for the
flare gas stream/system going to the affected flare (e.g., ``the
samples are representative of typical operating conditions of the flare
gas stream going to the loading rack flare'' or ``the samples are
representative of conditions expected to yield the lowest net heating
value of the flare gas stream going to the loading rack flare'').
(F) The net heating value to be used for all flows of the flare
vent gas from the flare gas stream/system covered in the application. A
single net heating value must be assigned to the flare vent gas either
by selecting the lowest net heating value measured in the sampling
program or by determining the 95th percent confidence interval on the
mean value of all samples collected using the t-distribution statistic
(which is 1.943 for 7 grab samples or 1.771 for 14 grab samples).
(ii) The effective date of the exemption is the date of submission
of the information required in paragraph (j)(6)(i) of this section.
(iii) No further action is required unless refinery operating
conditions change in such a way that affects the exempt fuel gas
stream/system (e.g., the stream composition changes). If such a change
occurs, the owner or operator shall follow the procedures in paragraph
(j)(6)(iii)(A), (B), or (C) of this section.
(A) If the operation change results in a flare vent gas net heating
value that is still within the range of net heating values included in
the original application, the owner or operator shall determine the net
heating value on a grab sample and record the results as proof that the
net heating value assigned to the vent gas stream in the original
application is still appropriate.
(B) If the operation change results in a flare vent gas net heating
value that is lower than the net heating value assigned to the vent gas
stream in the original application, the owner or operator may submit
new information following the procedures of paragraph (j)(6)(i) of this
section within 60 days (or within 30 days after the seventh grab sample
is tested for infrequently operated process units).
(C) If the operation change results in a flare vent gas net heating
value has greater variability in the flare gas stream/system such the
owner or operator chooses not to submit new information to support an
exemption, the owner or operator must begin monitoring the composition
or net heat content of the flare vent gas stream using the methods in
this section (i.e., grab samples every 8 hours until such time a
continuous monitor, if elected, is installed).
(k) Calculation methods for cumulative flow rates and determining
compliance with Vtip operating limits. The owner or operator shall
determine Vtip on a 15-minute block average basis according
to the following requirements.
(1) The owner or operator shall use design and engineering
principles to determine the unobstructed cross sectional area of the
flare tip. The unobstructed cross sectional area of the flare tip is
the total tip area that vent gas can pass through. This area does not
include any stability tabs, stability rings, and upper steam or air
tubes because flare vent gas does not exit through them.
(2) The owner or operator shall determine the cumulative volumetric
flow of flare vent gas for each 15-minute block average period using
the data from the continuous flow monitoring system required in
paragraph (i) of this section according to the following requirements,
as applicable. If desired, the cumulative flow rate for a 15-minute
block period only needs to include flow during those periods when
regulated material is sent to the flare, but owners or operators may
elect to calculate the cumulative flow rates across the entire 15-
minute block period for any 15-minute block period where there is
regulated material flow to the flare.
(i) Use set 15-minute time periods starting at 12 midnight to 12:15
a.m., 12:15 a.m. to 12:30 a.m. and so on concluding at 11:45 p.m. to
midnight when calculating 15-minute block average flow volumes.
(ii) If continuous pressure/temperature monitoring system(s) and
engineering calculations are used as allowed under paragraph (i)(4) of
this section, the owner or operator shall, at a minimum, determine the
15-minute block average temperature and pressure from the monitoring
system and use those values to perform the engineering calculations to
determine the cumulative flow over the 15-minute block average period.
Alternatively, the owner or operator may divide the 15-minute block
average period into equal duration subperiods (e.g., three 5-minute
periods) and determine the average temperature and pressure for each
subperiod, perform engineering calculations to determine the flow for
each subperiod, then add the volumetric
[[Page 75261]]
flows for the subperiods to determine the cumulative volumetric flow of
vent gas for the 15-minute block average period.
(3) The 15-minute block average Vtip shall be calculated
using the following equation.
[GRAPHIC] [TIFF OMITTED] TR01DE15.010
Where:
Vtip = Flare tip velocity, feet per second.
Qcum = Cumulative volumetric flow over 15-minute block
average period, actual cubic feet.
Area = Unobstructed area of the flare tip, square feet.
900 = Conversion factor, seconds per 15-minute block average.
(4) If the owner or operator chooses to comply with paragraph
(d)(2) of this section, the owner or operator shall also determine the
net heating value of the flare vent gas following the requirements in
paragraphs (j) and (l) of this section and calculate Vmax
using the equation in paragraph (d)(2) of this section in order to
compare Vtip to Vmax on a 15-minute block average
basis.
(l) Calculation methods for determining flare vent gas net heating
value. The owner or operator shall determine the net heating value of
the flare vent gas (NHVvg) based on the composition
monitoring data on a 15-minute block average basis according to the
following requirements.
(1) If compositional analysis data are collected as provided in
paragraph (j)(1) or (2) of this section, the owner or operator shall
determine NHVvg of a specific sample by using the following
equation.
[GRAPHIC] [TIFF OMITTED] TR01DE15.011
Where:
NHVvg = Net heating value of flare vent gas, Btu/scf.
i = Individual component in flare vent gas.
n = Number of components in flare vent gas.
xi = Concentration of component i in flare vent gas,
volume fraction.
NHVi = Net heating value of component i according to
table 12 of this subpart, Btu/scf. If the component is not specified
in table 12 of this subpart, the heats of combustion may be
determined using any published values where the net enthalpy per
mole of offgas is based on combustion at 25 [deg]C and 1 atmosphere
(or constant pressure) with offgas water in the gaseous state, but
the standard temperature for determining the volume corresponding to
one mole of vent gas is 20 [deg]C.
(2) If direct net heating value monitoring data are collected as
provided in paragraph (j)(3) of this section but a hydrogen
concentration monitor is not used, the owner or operator shall use the
direct output of the monitoring system(s) (in Btu/scf) to determine the
NHVvg for the sample.
(3) If direct net heating value monitoring data are collected as
provided in paragraph (j)(3) of this section and hydrogen concentration
monitoring data are collected as provided in paragraph (j)(4) of this
section, the owner or operator shall use the following equation to
determine NHVvg for each sample measured via the net heating
value monitoring system.
NHVvg = NHVmeasured + 938xH2
Where:
NHVvg = Net heating value of flare vent gas, Btu/scf.
NHVmeasured = Net heating value of flare vent gas stream
as measured by the continuous net heating value monitoring system,
Btu/scf.
xH2 = Concentration of hydrogen in flare vent gas at the time the
sample was input into the net heating value monitoring system,
volume fraction.
938 = Net correction for the measured heating value of hydrogen
(1,212 - 274), Btu/scf.
(4) Use set 15-minute time periods starting at 12 midnight to 12:15
a.m., 12:15 a.m. to 12:30 a.m. and so on concluding at 11:45 p.m. to
midnight when calculating 15-minute block averages.
(5) When a continuous monitoring system is used as provided in
paragraph (j)(1) or (3) of this section and, if applicable, paragraph
(j)(4) of this section, the owner or operator may elect to determine
the 15-minute block average NHVvg using either the
calculation methods in paragraph (l)(5)(i) of this section or the
calculation methods in paragraph (l)(5)(ii) of this section. The owner
or operator may choose to comply using the calculation methods in
paragraph (l)(5)(i) of this section for some flares at the petroleum
refinery and comply using the calculation methods (l)(5)(ii) of this
section for other flares. However, for each flare, the owner or
operator must elect one calculation method that will apply at all
times, and use that method for all continuously monitored flare vent
streams associated with that flare. If the owner or operator intends to
change the calculation method that applies to a flare, the owner or
operator must notify the Administrator 30 days in advance of such a
change.
(i) Feed-forward calculation method. When calculating
NHVvg for a specific 15-minute block:
(A) Use the results from the first sample collected during an
event, (for periodic flare vent gas flow events) for the first 15-
minute block associated with that event.
(B) If the results from the first sample collected during an event
(for periodic flare vent gas flow events) are not available until after
the second 15-minute block starts, use the results from the first
sample collected during an event for the second 15-minute block
associated with that event.
(C) For all other cases, use the results that are available from
the most recent sample prior to the 15-minute block period for that 15-
minute block period for all flare vent gas steams. For the purpose of
this requirement, use the time that the results become available rather
than the time the sample was collected. For example, if a sample is
collected at 12:25 a.m. and the analysis is completed at 12:38 a.m.,
the results are available at 12:38 a.m. and these results would be used
to determine compliance during the 15-minute block period from 12:45
a.m. to 1:00 a.m.
(ii) Direct calculation method. When calculating NHVvg
for a specific 15-minute block:
(A) If the results from the first sample collected during an event
(for periodic flare vent gas flow events) are not available until after
the second 15-minute block starts, use the results from the first
sample collected during an event for the first 15-minute block
associated with that event.
(B) For all other cases, use the arithmetic average of all
NHVvg measurement data results that become available during
a 15-minute block to calculate the 15-minute block average for that
period. For the purpose of this requirement, use the time that the
results become available rather than the time the sample was collected.
For example, if a sample is collected at 12:25 a.m. and the analysis is
completed at 12:38 a.m., the results are available at 12:38 a.m. and
these results would be used to determine compliance during the 15-
minute block period from 12:30 a.m. to 12:45 a.m.
(6) When grab samples are used to determine flare vent gas
composition:
(i) Use the analytical results from the first grab sample collected
for an event for all 15-minute periods from the start of the event
through the 15-minute block prior to the 15-minute block in which a
subsequent grab sample is collected.
(ii) Use the results from subsequent grab sampling events for all
15 minute periods starting with the 15-minute block in which the sample
was collected and ending with the 15-minute block prior to the 15-
minute block in which the next grab sample is collected. For
[[Page 75262]]
the purpose of this requirement, use the time the sample was collected
rather than the time the analytical results become available.
(7) If the owner or operator monitors separate gas streams that
combine to comprise the total flare vent gas flow, the 15-minute block
average net heating value shall be determined separately for each
measurement location according to the methods in paragraphs (l)(1)
through (6) of this section and a flow-weighted average of the gas
stream net heating values shall be used to determine the 15-minute
block average net heating value of the cumulative flare vent gas.
(m) Calculation methods for determining combustion zone net heating
value. The owner or operator shall determine the net heating value of
the combustion zone gas (NHVcz) as specified in paragraph
(m)(1) or (2) of this section, as applicable.
(1) Except as specified in paragraph (m)(2) of this section,
determine the 15-minute block average NHVcz based on the 15-
minute block average vent gas and assist gas flow rates using the
following equation. For periods when there is no assist steam flow or
premix assist air flow, NHVcz = NHVvg.
[GRAPHIC] [TIFF OMITTED] TR01DE15.012
Where:
NHVcz = Net heating value of combustion zone gas, Btu/
scf.
NHVvg = Net heating value of flare vent gas for the 15-
minute block period, Btu/scf.
Qvg = Cumulative volumetric flow of flare vent gas during
the 15-minute block period, scf.
Qs = Cumulative volumetric flow of total steam during the
15-minute block period, scf.
Qa,premix = Cumulative volumetric flow of premix assist
air during the 15-minute block period, scf.
(2) Owners or operators of flares that use the feed-forward
calculation methodology in paragraph (l)(5)(i) of this section and that
monitor gas composition or net heating value in a location
representative of the cumulative vent gas stream and that directly
monitor supplemental natural gas flow additions to the flare must
determine the 15-minute block average NHVcz using the
following equation.
[GRAPHIC] [TIFF OMITTED] TR01DE15.013
Where:
NHVcz = Net heating value of combustion zone gas, Btu/
scf.
NHVvg = Net heating value of flare vent gas for the 15-
minute block period, Btu/scf.
Qvg = Cumulative volumetric flow of flare vent gas during
the 15-minute block period, scf.
QNG2 = Cumulative volumetric flow of supplemental natural
gas to the flare during the 15-minute block period, scf.
QNG1 = Cumulative volumetric flow of supplemental natural
gas to the flare during the previous 15-minute block period, scf.
For the first 15-minute block period of an event, use the volumetric
flow value for the current 15-minute block period, i.e.,
QNG1=QNG2.
NHVNG = Net heating value of supplemental natural gas to
the flare for the 15-minute block period determined according to the
requirements in paragraph (j)(5) of this section, Btu/scf.
Qs = Cumulative volumetric flow of total steam during the
15-minute block period, scf.
Qa,premix = Cumulative volumetric flow of premix assist
air during the 15-minute block period, scf.
(n) Calculation methods for determining the net heating value
dilution parameter. The owner or operator shall determine the net
heating value dilution parameter (NHVdil) as specified in
paragraph (n)(1) or (2) of this section, as applicable.
(1) Except as specified in paragraph (n)(2) of this section,
determine the 15-minute block average NHVdil based on the
15-minute block average vent gas and perimeter assist air flow rates
using the following equation only during periods when perimeter assist
air is used. For 15-minute block periods when there is no cumulative
volumetric flow of perimeter assist air, the 15-minute block average
NHVdil parameter does not need to be calculated.
[GRAPHIC] [TIFF OMITTED] TR01DE15.014
Where:
NHVdil = Net heating value dilution parameter, Btu/
ft2.
NHVvg = Net heating value of flare vent gas determined
for the 15-minute block period, Btu/scf.
Qvg = Cumulative volumetric flow of flare vent gas during
the 15-minute block period, scf.
Diam = Effective diameter of the unobstructed area of the flare tip
for flare vent gas flow, ft. Use the area as determined in paragraph
(k)(1) of this section and determine the diameter as
[GRAPHIC] [TIFF OMITTED] TR01DE15.015
Qs = Cumulative volumetric flow of total steam during the
15-minute block period, scf.
Qa,premix = Cumulative volumetric flow of premix assist
air during the 15-minute block period, scf.
Qa,perimeter = Cumulative volumetric flow of perimeter
assist air during the 15-minute block period, scf.
(2) Owners or operators of flares that use the feed-forward
calculation methodology in paragraph (l)(5)(i) of this section and that
monitor gas composition or net heating value in a location
representative of the cumulative vent gas stream and that directly
monitor supplemental natural gas flow additions to the flare must
determine the 15-minute block average NHVdil using the
following equation only during periods when perimeter assist air is
used. For 15-minute block periods when there is no cumulative
[[Page 75263]]
volumetric flow of perimeter assist air, the 15-minute block average
NHVdil parameter does not need to be calculated.
[GRAPHIC] [TIFF OMITTED] TR01DE15.016
Where:
NHVdil = Net heating value dilution parameter, Btu/
ft2.
NHVvg = Net heating value of flare vent gas determined
for the 15-minute block period, Btu/scf.
Qvg = Cumulative volumetric flow of flare vent gas during
the 15-minute block period, scf.
QNG2 = Cumulative volumetric flow of supplemental natural
gas to the flare during the 15-minute block period, scf.
QNG1 = Cumulative volumetric flow of supplemental natural
gas to the flare during the previous 15-minute block period, scf.
For the first 15-minute block period of an event, use the volumetric
flow value for the current 15-minute block period, i.e.,
QNG1 =QNG2.
NHVNG = Net heating value of supplemental natural gas to
the flare for the 15-minute block period determined according to the
requirements in paragraph (j)(5) of this section, Btu/scf.
Diam = Effective diameter of the unobstructed area of the flare tip
for flare vent gas flow, ft. Use the area as determined in paragraph
(k)(1) of this section and determine the diameter as
[GRAPHIC] [TIFF OMITTED] TR01DE15.017
Qs = Cumulative volumetric flow of total steam during the
15-minute block period, scf.
Qa,premix = Cumulative volumetric flow of premix assist
air during the 15-minute block period, scf.
Qa,perimeter = Cumulative volumetric flow of perimeter
assist air during the 15-minute block period, scf.
(o) Emergency flaring provisions. The owner or operator of a flare
that has the potential to operate above its smokeless capacity under
any circumstance shall comply with the provisions in paragraphs (o)(1)
through (8) of this section.
(1) Develop a flare management plan to minimize flaring during
periods of startup, shutdown, or emergency releases. The flare
management plan must include the information described in paragraphs
(o)(1)(i) through (vii) of this section.
(i) A listing of all refinery process units, ancillary equipment,
and fuel gas systems connected to the flare for each affected flare.
(ii) An assessment of whether discharges to affected flares from
these process units, ancillary equipment and fuel gas systems can be
minimized or prevented during periods of startup, shutdown, or
emergency releases. The flare minimization assessment must (at a
minimum) consider the items in paragraphs (o)(1)(ii)(A) through (C) of
this section. The assessment must provide clear rationale in terms of
costs (capital and annual operating), natural gas offset credits (if
applicable), technical feasibility, secondary environmental impacts and
safety considerations for the selected minimization alternative(s) or a
statement, with justifications, that flow reduction could not be
achieved. Based upon the assessment, each owner or operator of an
affected flare shall identify the minimization alternatives that it has
implemented by the due date of the flare management plan and shall
include a schedule for the prompt implementation of any selected
measures that cannot reasonably be completed as of that date.
(A) Modification in startup and shutdown procedures to reduce the
quantity of process gas discharge to the flare.
(B) Implementation of prevention measures listed for pressure
relief devices in Sec. 63.648(j)(5) for each pressure relief valve
that can discharge to the flare.
(C) Installation of a flare gas recovery system or, for facilities
that are fuel gas rich, a flare gas recovery system and a co-generation
unit or combined heat and power unit.
(iii) A description of each affected flare containing the
information in paragraphs (o)(1)(iii)(A) through (G) of this section.
(A) A general description of the flare, including whether it is a
ground flare or elevated (including height), the type of assist system
(e.g., air, steam, pressure, non-assisted), whether the flare is used
on a routine basis or if it is only used during periods of startup,
shutdown or emergency release, and whether the flare is equipped with a
flare gas recovery system.
(B) The smokeless capacity of the flare based on design conditions.
Note: A single value must be provided for the smokeless capacity of the
flare.
(C) The maximum vent gas flow rate (hydraulic load capacity).
(D) The maximum supplemental gas flow rate.
(E) For flares that receive assist steam, the minimum total steam
rate and the maximum total steam rate.
(F) For flares that receive assist air, an indication of whether
the fan/blower is single speed, multi-fixed speed (e.g., high, medium,
and low speeds), or variable speeds. For fans/blowers with fixed
speeds, provide the estimated assist air flow rate at each fixed speed.
For variable speeds, provide the design fan curve (e.g., air flow rate
as a function of power input).
(G) Simple process flow diagram showing the locations of the flare
following components of the flare: Flare tip (date installed,
manufacturer, nominal and effective tip diameter, tip drawing);
knockout or surge drum(s) or pot(s) (including dimensions and design
capacities); flare header(s) and subheader(s); assist system; and
ignition system.
(iv) Description and simple process flow diagram showing all gas
lines (including flare waste gas, purge or sweep gas (as applicable),
supplemental gas) that are associated with the flare. For purge, sweep,
supplemental gas, identify the type of gas used. Designate which lines
are exempt from composition or net heating value monitoring and why
(e.g., natural gas, gas streams that have been demonstrated to have
consistent composition, pilot gas). Designate which lines are monitored
and identify on the process flow diagram the location and type of each
monitor. Designate the pressure relief devices that are vented to the
flare.
(v) For each flow rate, gas composition, net heating value or
hydrogen concentration monitor identified in paragraph (o)(1)(iv) of
this section, provide a detailed description of the manufacturer's
specifications, including, but not limited to, make, model, type,
range, precision, accuracy, calibration, maintenance and quality
assurance procedures.
(vi) For each pressure relief valve vented to the flare identified
in paragraph (o)(1)(iv) of this section, provide a detailed description
of each pressure release valve, including type of relief device
(rupture disc, valve type) diameter of the relief valve, set pressure
of the relief valve and listing of the prevention measures implemented.
This
[[Page 75264]]
information may be maintained in an electronic database on-site and
does not need to be submitted as part of the flare management plan
unless requested to do so by the Administrator.
(vii) Procedures to minimize or eliminate discharges to the flare
during the planned startup and shutdown of the refinery process units
and ancillary equipment that are connected to the affected flare,
together with a schedule for the prompt implementation of any
procedures that cannot reasonably be implemented as of the date of the
submission of the flare management plan.
(2) Each owner or operator required to develop and implement a
written flare management plan as described in paragraph (o)(1) of this
section must submit the plan to the Administrator as described in
paragraphs (o)(2)(i) through (iii) of this section.
(i) The owner or operator must develop and implement the flare
management plan no later than January 30, 2019 or at startup for a new
flare that commenced construction on or after February 1, 2016.
(ii) The owner or operator must comply with the plan as submitted
by the date specified in paragraph (o)(2)(i) of this section. The plan
should be updated periodically to account for changes in the operation
of the flare, such as new connections to the flare or the installation
of a flare gas recovery system, but the plan need be re-submitted to
the Administrator only if the owner or operator alters the design
smokeless capacity of the flare. The owner or operator must comply with
the updated plan as submitted.
(iii) All versions of the plan submitted to the Administrator shall
also be submitted to the following address: U.S. Environmental
Protection Agency, Office of Air Quality Planning and Standards, Sector
Policies and Programs Division, U.S. EPA Mailroom (E143-01), Attention:
Refinery Sector Lead, 109 T.W. Alexander Drive, Research Triangle Park,
NC 27711. Electronic copies in lieu of hard copies may also be
submitted to refineryRTR@epa.gov.
(3) The owner or operator of a flare subject to this subpart shall
conduct a root cause analysis and a corrective action analysis for each
flow event that contains regulated material and that meets either the
criteria in paragraph (o)(3)(i) or (ii) of this section.
(i) The vent gas flow rate exceeds the smokeless capacity of the
flare and visible emissions are present from the flare for more than 5
minutes during any 2 consecutive hours during the release event.
(ii) The vent gas flow rate exceeds the smokeless capacity of the
flare and the 15-minute block average flare tip velocity exceeds the
maximum flare tip velocity determined using the methods in paragraph
(d)(2) of this section.
(4) A root cause analysis and corrective action analysis must be
completed as soon as possible, but no later than 45 days after a flare
flow event meeting the criteria in paragraph (o)(3)(i) or (ii) of this
section. Special circumstances affecting the number of root cause
analyses and/or corrective action analyses are provided in paragraphs
(o)(4)(i) through (v) of this section.
(i) You may conduct a single root cause analysis and corrective
action analysis for a single continuous flare flow event that meets
both of the criteria in paragraphs (o)(3)(i) and (ii) of this section.
(ii) You may conduct a single root cause analysis and corrective
action analysis for a single continuous flare flow event regardless of
the number of 15-minute block periods in which the flare tip velocity
was exceeded or the number of 2 hour periods that contain more the 5
minutes of visible emissions.
(iii) You may conduct a single root cause analysis and corrective
action analysis for a single event that causes two or more flares that
are operated in series (i.e., cascaded flare systems) to have a flow
event meeting the criteria in paragraph (o)(3)(i) or (ii) of this
section.
(iv) You may conduct a single root cause analysis and corrective
action analysis for a single event that causes two or more flares to
have a flow event meeting the criteria in paragraph (o)(3)(i) or (ii)
of this section, regardless of the configuration of the flares, if the
root cause is reasonably expected to be a force majeure event, as
defined in this subpart.
(v) Except as provided in paragraphs (o)(4)(iii) and (iv) of this
section, if more than one flare has a flow event that meets the
criteria in paragraph (o)(3)(i) or (ii) of this section during the same
time period, an initial root cause analysis shall be conducted
separately for each flare that has a flow event meeting the criteria in
paragraph (o)(3)(i) or (ii) of this section. If the initial root cause
analysis indicates that the flow events have the same root cause(s),
the initially separate root cause analyses may be recorded as a single
root cause analysis and a single corrective action analysis may be
conducted.
(5) Each owner or operator of a flare required to conduct a root
cause analysis and corrective action analysis as specified in
paragraphs (o)(3) and (4) of this section shall implement the
corrective action(s) identified in the corrective action analysis in
accordance with the applicable requirements in paragraphs (o)(5)(i)
through (iii) of this section.
(i) All corrective action(s) must be implemented within 45 days of
the event for which the root cause and corrective action analyses were
required or as soon thereafter as practicable. If an owner or operator
concludes that no corrective action should be implemented, the owner or
operator shall record and explain the basis for that conclusion no
later than 45 days following the event.
(ii) For corrective actions that cannot be fully implemented within
45 days following the event for which the root cause and corrective
action analyses were required, the owner or operator shall develop an
implementation schedule to complete the corrective action(s) as soon as
practicable.
(iii) No later than 45 days following the event for which a root
cause and corrective action analyses were required, the owner or
operator shall record the corrective action(s) completed to date, and,
for action(s) not already completed, a schedule for implementation,
including proposed commencement and completion dates.
(6) The owner or operator shall determine the total number of
events for which a root cause and corrective action analyses was
required during the calendar year for each affected flare separately
for events meeting the criteria in paragraph (o)(3)(i) of this section
and those meeting the criteria in paragraph (o)(3)(ii) of this section.
For the purpose of this requirement, a single root cause analysis
conducted for an event that met both of the criteria in paragraphs
(o)(3)(i) and (ii) of this section would be counted as an event under
each of the separate criteria counts for that flare. Additionally, if a
single root cause analysis was conducted for an event that caused
multiple flares to meet the criteria in paragraph (o)(3)(i) or (ii) of
this section, that event would count as an event for each of the flares
for each criteria in paragraph (o)(3) of this section that was met
during that event. The owner or operator shall also determine the total
number of events for which a root cause and correct action analyses was
required and the analyses concluded that the root cause was a force
majeure event, as defined in this subpart.
(7) The following events would be a violation of this emergency
flaring work practice standard.
(i) Any flow event for which a root cause analysis was required and
the root
[[Page 75265]]
cause was determined to be operator error or poor maintenance.
(ii) Two visible emissions exceedance events meeting the criteria
in paragraph (o)(3)(i) of this section that were not caused by a force
majeure event from a single flare in a 3 calendar year period for the
same root cause for the same equipment.
(iii) Two flare tip velocity exceedance events meeting the criteria
in paragraph (o)(3)(ii) of this section that were not caused by a force
majeure event from a single flare in a 3 calendar year period for the
same root cause for the same equipment.
(iv) Three visible emissions exceedance events meeting the criteria
in paragraph (o)(3)(i) of this section that were not caused by a force
majeure event from a single flare in a 3 calendar year period for any
reason.
(v) Three flare tip velocity exceedance events meeting the criteria
in paragraph (o)(3)(ii) of this section that were not caused by a force
majeure event from a single flare in a 3 calendar year period for any
reason.
(p) Flare monitoring records. The owner or operator shall keep the
records specified in Sec. 63.655(i)(9).
(q) Reporting. The owner or operator shall comply with the
reporting requirements specified in Sec. 63.655(g)(11).
(r) Alternative means of emissions limitation. An owner or operator
may request approval from the Administrator for site-specific operating
limits that shall apply specifically to a selected flare. Site-specific
operating limits include alternative threshold values for the
parameters specified in paragraphs (d) through (f) of this section as
well as threshold values for operating parameters other than those
specified in paragraphs (d) through (f) of this section. The owner or
operator must demonstrate that the flare achieves 96.5 percent
combustion efficiency (or 98 percent destruction efficiency) using the
site-specific operating limits based on a performance evaluation as
described in paragraph (r)(1) of this section. The request shall
include information as described in paragraph (r)(2) of this section.
The request shall be submitted and followed as described in paragraph
(r)(3) of this section.
(1) The owner or operator shall prepare and submit a site-specific
test plan and receive approval of the site-specific performance
evaluation plan prior to conducting any flare performance evaluation
test runs intended for use in developing site-specific operating
limits. The site-specific performance evaluation plan shall include, at
a minimum, the elements specified in paragraphs (r)(1)(i) through (ix)
of this section. Upon approval of the site-specific performance
evaluation plan, the owner or operator shall conduct performance
evaluation test runs for the flare following the procedures described
in the site-specific performance evaluation plan.
(i) The design and dimensions of the flare, flare type (air-
assisted only, steam-assisted only, air- and steam-assisted, pressure-
assisted, or non-assisted), and description of gas being flared,
including quantity of gas flared, frequency of flaring events (if
periodic), expected net heating value of flare vent gas, minimum total
steam assist rate.
(ii) The operating conditions (vent gas compositions, vent gas flow
rates and assist flow rates, if applicable) likely to be encountered by
the flare during normal operations and the operating conditions for the
test period.
(iii) A description of (including sample calculations illustrating)
the planned data reduction and calculations to determine the flare
combustion or destruction efficiency.
(iv) Site-specific operating parameters to be monitored
continuously during the flare performance evaluation. These parameters
may include but are not limited to vent gas flow rate, steam and/or air
assist flow rates, and flare vent gas composition. If new operating
parameters are proposed for use other than those specified in
paragraphs (d) through (f) of this section, an explanation of the
relevance of the proposed operating parameter(s) as an indicator of
flare combustion performance and why the alternative operating
parameter(s) can adequately ensure that the flare achieves the required
combustion efficiency.
(v) A detailed description of the measurement methods, monitored
pollutant(s), measurement locations, measurement frequency, and
recording frequency proposed for both emission measurements and flare
operating parameters.
(vi) A description of (including sample calculations illustrating)
the planned data reduction and calculations to determine the flare
operating parameters.
(vii) The minimum number and length of test runs and range of
operating values to be evaluated during the performance evaluation. A
sufficient number of test runs shall be conducted to identify the point
at which the combustion/destruction efficiency of the flare
deteriorates.
(viii) [Reserved]
(ix) Test schedule.
(2) The request for flare-specific operating limits shall include
sufficient and appropriate data, as determined by the Administrator, to
allow the Administrator to confirm that the selected site-specific
operating limit(s) adequately ensures that the flare destruction
efficiency is 98 percent or greater or that the flare combustion
efficiency is 96.5 percent or greater at all times. At a minimum, the
request shall contain the information described in paragraphs (r)(2)(i)
through (iv) of this section.
(i) The design and dimensions of the flare, flare type (air-
assisted only, steam-assisted only, air- and steam-assisted, pressure-
assisted, or non-assisted), and description of gas being flared,
including quantity of gas flared, frequency of flaring events (if
periodic), expected net heating value of flare vent gas, minimum total
steam assist rate.
(ii) Results of each performance evaluation test run conducted,
including, at a minimum:
(A) The measured combustion/destruction efficiency.
(B) The measured or calculated operating parameters for each test
run. If operating parameters are calculated, the raw data from which
the parameters are calculated must be included in the test report.
(C) Measurement location descriptions for both emission
measurements and flare operating parameters.
(D) Description of sampling and analysis procedures (including
number and length of test runs) and any modifications to standard
procedures. If there were deviations from the approved test plan, a
detailed description of the deviations and rationale why the test
results or calculation procedures used are appropriate.
(E) Operating conditions (e.g., vent gas composition, assist rates,
etc.) that occurred during the test.
(F) Quality assurance procedures.
(G) Records of calibrations.
(H) Raw data sheets for field sampling.
(I) Raw data sheets for field and laboratory analyses.
(J) Documentation of calculations.
(iii) The selected flare-specific operating limit values based on
the performance evaluation test results, including the averaging time
for the operating limit(s), and rationale why the selected values and
averaging times are sufficiently stringent to ensure proper flare
performance. If new operating parameters or averaging times are
proposed for use other than those specified in paragraphs (d) through
(f) of this section, an explanation of why the
[[Page 75266]]
alternative operating parameter(s) or averaging time(s) adequately
ensures the flare achieves the required combustion efficiency.
(iv) The means by which the owner or operator will document on-
going, continuous compliance with the selected flare-specific operating
limit(s), including the specific measurement location and frequencies,
calculation procedures, and records to be maintained.
(3) The request shall be submitted as described in paragraphs
(r)(3)(i) through (iv) of this section.
(i) The owner or operator may request approval from the
Administrator at any time upon completion of a performance evaluation
conducted following the methods in an approved site-specific
performance evaluation plan for an operating limit(s) that shall apply
specifically to that flare.
(ii) The request must be submitted to the Administrator for
approval. The owner or operator must continue to comply with the
applicable standards for flares in this subpart until the requirements
in Sec. 63.6(g)(1) are met and a notice is published in the Federal
Register allowing use of such an alternative means of emission
limitation.
(iii) The request shall also be submitted to the following address:
U.S. Environmental Protection Agency, Office of Air Quality Planning
and Standards, Sector Policies and Programs Division, U.S. EPA Mailroom
(E143-01), Attention: Refinery Sector Lead, 109 T.W. Alexander Drive,
Research Triangle Park, NC 27711. Electronic copies in lieu of hard
copies may also be submitted to refineryrtr@epa.gov.
(iv) If the Administrator finds any deficiencies in the request,
the request must be revised to address the deficiencies and be re-
submitted for approval within 45 days of receipt of the notice of
deficiencies. The owner or operator must comply with the revised
request as submitted until it is approved.
(4) The approval process for a request for a flare-specific
operating limit(s) is described in paragraphs (r)(4)(i) through (iii)
of this section.
(i) Approval by the Administrator of a flare-specific operating
limit(s) request will be based on the completeness, accuracy and
reasonableness of the request. Factors that the EPA will consider in
reviewing the request for approval include, but are not limited to,
those described in paragraphs (r)(4)(i)(A) through (C) of this section.
(A) The description of the flare design and operating
characteristics.
(B) If a new operating parameter(s) other than those specified in
paragraphs (d) through (f) of this section is proposed, the explanation
of how the proposed operating parameter(s) serves a good indicator(s)
of flare combustion performance.
(C) The results of the flare performance evaluation test runs and
the establishment of operating limits that ensures that the flare
destruction efficiency is 98 percent or greater or that the flare
combustion efficiency is 96.5 percent or greater at all times.
(D) The completeness of the flare performance evaluation test
report.
(ii) If the request is approved by the Administrator, a flare-
specific operating limit(s) will be established at the level(s)
demonstrated in the approved request.
(iii) If the Administrator finds any deficiencies in the request,
the request must be revised to address the deficiencies and be re-
submitted for approval.
0
33. Section 63.671 is added to read as follows:
Sec. 63.671 Requirements for flare monitoring systems.
(a) Operation of CPMS. For each CPMS installed to comply with
applicable provisions in Sec. 63.670, the owner or operator shall
install, operate, calibrate, and maintain the CPMS as specified in
paragraphs (a)(1) through (8) of this section.
(1) Except for CPMS installed for pilot flame monitoring, all
monitoring equipment must meet the applicable minimum accuracy,
calibration and quality control requirements specified in table 13 of
this subpart.
(2) The owner or operator shall ensure the readout (that portion of
the CPMS that provides a visual display or record) or other indication
of the monitored operating parameter from any CPMS required for
compliance is readily accessible onsite for operational control or
inspection by the operator of the source.
(3) All CPMS must complete a minimum of one cycle of operation
(sampling, analyzing and data recording) for each successive 15-minute
period.
(4) Except for periods of monitoring system malfunctions, repairs
associated with monitoring system malfunctions and required monitoring
system quality assurance or quality control activities (including, as
applicable, calibration checks and required zero and span adjustments),
the owner or operator shall operate all CPMS and collect data
continuously at all times when regulated emissions are routed to the
flare.
(5) The owner or operator shall operate, maintain, and calibrate
each CPMS according to the CPMS monitoring plan specified in paragraph
(b) of this section.
(6) For each CPMS except for CPMS installed for pilot flame
monitoring, the owner or operator shall comply with the out-of-control
procedures described in paragraph (c) of this section.
(7) The owner or operator shall reduce data from a CPMS as
specified in paragraph (d) of this section.
(8) The CPMS must be capable of measuring the appropriate parameter
over the range of values expected for that measurement location. The
data recording system associated with each CPMS must have a resolution
that is equal to or better than the required system accuracy.
(b) CPMS monitoring plan. The owner or operator shall develop and
implement a CPMS quality control program documented in a CPMS
monitoring plan that covers each flare subject to the provisions in
Sec. 63.670 and each CPMS installed to comply with applicable
provisions in Sec. 63.670. The owner or operator shall have the CPMS
monitoring plan readily available on-site at all times and shall submit
a copy of the CPMS monitoring plan to the Administrator upon request by
the Administrator. The CPMS monitoring plan must contain the
information listed in paragraphs (b)(1) through (5) of this section.
(1) Identification of the specific flare being monitored and the
flare type (air-assisted only, steam-assisted only, air- and steam-
assisted, pressure-assisted, or non-assisted).
(2) Identification of the parameter to be monitored by the CPMS and
the expected parameter range, including worst case and normal
operation.
(3) Description of the monitoring equipment, including the
information specified in paragraphs (b)(3)(i) through (vii) of this
section.
(i) Manufacturer and model number for all monitoring equipment
components installed to comply with applicable provisions in Sec.
63.670.
(ii) Performance specifications, as provided by the manufacturer,
and any differences expected for this installation and operation.
(iii) The location of the CPMS sampling probe or other interface
and a justification of how the location meets the requirements of
paragraph (a)(1) of this section.
(iv) Placement of the CPMS readout, or other indication of
parameter values, indicating how the location meets the requirements of
paragraph (a)(2) of this section.
[[Page 75267]]
(v) Span of the CPMS. The span of the CPMS sensor and analyzer must
encompass the full range of all expected values.
(vi) How data outside of the span of the CPMS will be handled and
the corrective action that will be taken to reduce and eliminate such
occurrences in the future.
(vii) Identification of the parameter detected by the parametric
signal analyzer and the algorithm used to convert these values into the
operating parameter monitored to demonstrate compliance, if the
parameter detected is different from the operating parameter monitored.
(4) Description of the data collection and reduction systems,
including the information specified in paragraphs (b)(4)(i) through
(iii) of this section.
(i) A copy of the data acquisition system algorithm used to reduce
the measured data into the reportable form of the standard and to
calculate the applicable averages.
(ii) Identification of whether the algorithm excludes data
collected during CPMS breakdowns, out-of-control periods, repairs,
maintenance periods, instrument adjustments or checks to maintain
precision and accuracy, calibration checks, and zero (low-level), mid-
level (if applicable) and high-level adjustments.
(iii) If the data acquisition algorithm does not exclude data
collected during CPMS breakdowns, out-of-control periods, repairs,
maintenance periods, instrument adjustments or checks to maintain
precision and accuracy, calibration checks, and zero (low-level), mid-
level (if applicable) and high-level adjustments, a description of the
procedure for excluding this data when the averages calculated as
specified in paragraph (e) of this section are determined.
(5) Routine quality control and assurance procedures, including
descriptions of the procedures listed in paragraphs (b)(5)(i) through
(vi) of this section and a schedule for conducting these procedures.
The routine procedures must provide an assessment of CPMS performance.
(i) Initial and subsequent calibration of the CPMS and acceptance
criteria.
(ii) Determination and adjustment of the calibration drift of the
CPMS.
(iii) Daily checks for indications that the system is responding.
If the CPMS system includes an internal system check, the owner or
operator may use the results to verify the system is responding, as
long as the system provides an alarm to the owner or operator or the
owner or operator checks the internal system results daily for proper
operation and the results are recorded.
(iv) Preventive maintenance of the CPMS, including spare parts
inventory.
(v) Data recording, calculations and reporting.
(vi) Program of corrective action for a CPMS that is not operating
properly.
(c) Out-of-control periods. For each CPMS installed to comply with
applicable provisions in Sec. 63.670 except for CPMS installed for
pilot flame monitoring, the owner or operator shall comply with the
out-of-control procedures described in paragraphs (c)(1) and (2) of
this section.
(1) A CPMS is out-of-control if the zero (low-level), mid-level (if
applicable) or high-level calibration drift exceeds two times the
accuracy requirement of table 13 of this subpart.
(2) When the CPMS is out of control, the owner or operator shall
take the necessary corrective action and repeat all necessary tests
that indicate the system is out of control. The owner or operator shall
take corrective action and conduct retesting until the performance
requirements are below the applicable limits. The beginning of the out-
of-control period is the hour a performance check (e.g., calibration
drift) that indicates an exceedance of the performance requirements
established in this section is conducted. The end of the out-of-control
period is the hour following the completion of corrective action and
successful demonstration that the system is within the allowable
limits. The owner or operator shall not use data recorded during
periods the CPMS is out of control in data averages and calculations,
used to report emissions or operating levels, as specified in paragraph
(d)(3) of this section.
(d) CPMS data reduction. The owner or operator shall reduce data
from a CPMS installed to comply with applicable provisions in Sec.
63.670 as specified in paragraphs (d)(1) through (3) of this section.
(1) The owner or operator may round the data to the same number of
significant digits used in that operating limit.
(2) Periods of non-operation of the process unit (or portion
thereof) resulting in cessation of the emissions to which the
monitoring applies must not be included in the 15-minute block
averages.
(3) Periods when the CPMS is out of control must not be included in
the 15-minute block averages.
(e) Additional requirements for gas chromatographs. For monitors
used to determine compositional analysis for net heating value per
Sec. 63.670(j)(1), the gas chromatograph must also meet the
requirements of paragraphs (e)(1) through (3) of this section.
(1) The quality assurance requirements are in table 13 of this
subpart.
(2) The calibration gases must meet one of the following options:
(i) The owner or operator must use a calibration gas or multiple
gases that include all of compounds listed in paragraphs (e)(2)(i)(A)
through (K) of this section that may be reasonably expected to exist in
the flare gas stream and optionally include any of the compounds listed
in paragraphs (e)(2)(i)(L) through (O) of this section. All of the
calibration gases may be combined in one cylinder. If multiple
calibration gases are necessary to cover all compounds, the owner or
operator must calibrate the instrument on all of the gases.
(A) Hydrogen.
(B) Methane.
(C) Ethane.
(D) Ethylene.
(E) Propane.
(F) Propylene.
(G) n-Butane.
(H) iso-Butane.
(I) Butene (general). It is not necessary to separately speciate
butene isomers, but the net heating value of trans-butene must be used
for co-eluting butene isomers.
(J) 1,3-Butadiene. It is not necessary to separately speciate
butadiene isomers, but you must use the response factor and net heating
value of 1,3-butadiene for co-eluting butadiene isomers.
(K) n-Pentane. Use the response factor for n-pentane to quantify
all C5+ hydrocarbons.
(L) Acetylene (optional).
(M) Carbon monoxide (optional).
(N) Propadiene (optional).
(O) Hydrogen sulfide (optional).
(ii) The owner or operator must use a surrogate calibration gas
consisting of hydrogen and C1 through C5 normal hydrocarbons. All of
the calibration gases may be combined in one cylinder. If multiple
calibration gases are necessary to cover all compounds, the owner or
operator must calibrate the instrument on all of the gases.
(3) If the owner or operator chooses to use a surrogate calibration
gas under paragraph (e)(2)(ii) of this section, the owner or operator
must comply with paragraphs (e)(3)(i) and (ii) of this section.
(i) Use the response factor for the nearest normal hydrocarbon
(i.e., n-alkane) in the calibration mixture to quantify unknown
components detected in the analysis.
(ii) Use the response factor for n-pentane to quantify unknown
[[Page 75268]]
components detected in the analysis that elute after n-pentane.
0
34. The appendix to subpart CC is amended in table 6 by:
0
a. Revising the entries ``63.5(d)(1)(ii)'' and ``63.5(f)'';
0
b. Removing the entry ``63.6(e)(1)'';
0
c. Adding, in numerical order, the entries ``63.6(e)(1)(i) and (ii)''
and ``63.6(e)(1)(iii)'';
0
d. Revising the entries ``63.6(e)(3)(i),'' ``63.6(e)(3)(iii)-
63.6(e)(3)(ix),'' and ``63.6(f)(1)'';
0
e. Removing the entry ``63.6(f)(2) and (3)'';
0
f. Adding, in numerical order, the entries ``63.6(f)(2)'' and
``63.6(f)(3)'';
0
g. Removing the entry ``63.6(h)(1) and 63.6(h)(2)'';
0
h. Adding, in numerical order, the entries ``63.6(h)(1)'' and
``63.6(h)(2)'';
0
i. Revising the entries ``63.7(b)'' and ``63.7(e)(1)'';
0
j. Removing the entry ``63.8(a)'';
0
k. Adding, in numerical order, the entries ``63.8(a)(1) and (2),''
``63.8(a)(3),'' and ``63.8(a)(4)'';
0
l. Revising the entry ``63.8(c)(1)'';
0
m. Adding, in numerical order, the entries ``63.8(c)(1)(i)'' and
``63.8(c)(1)(iii)'';
0
n. Revising the entries ``63.8(c)(4),'' ``63.8(c)(5)-63.8(c)(8),''
``63.8(d),'' ``63.8(e),'' ``63.8(g),'' ``63.10(b)(2)(i),''
``63.10(b)(2)(ii),'' ``63.10(b)(2)(iv),'' ``63.10(b)(2)(v),'' and
``63.10(b)(2)(vii)'';
0
o. Removing the entry ``63.10(c)(9)-63.10(c)(15)'';
0
p. Adding, in numerical order, the entries ``63.10(c)(9),''
``63.10(c)(10)-63.10(c)(11),'' and ``63.10(c)(12)-63.10(c)(15)'';
0
q. Revising the entry ``63.10(d)(2)'';
0
r. Removing the entries ``63.10(d)(5)(i)'' and ``63.10(d)(5)(ii)'';
0
s. Adding, in numerical order, the entry ``63.10(d)(5)'';
0
t. Removing the entry ``63.11-63.16'';
0
u. Adding, in numerical order, the entries ``63.11'' and ``63.12-
63.16'';
0
v. Revising footnote a.
0
w. Removing footnote b.
The revisions and additions read as follows:
Appendix to Subpart CC of Part 63--Tables
* * * * *
Table 6--General Provisions Applicability to Subpart CC \a\
------------------------------------------------------------------------
Applies to subpart
Reference CC Comment
------------------------------------------------------------------------
* * * * * * *
63.5(d)(1)(ii).............. Yes................. Except that for
affected sources
subject to this
subpart, emission
estimates specified
in Sec.
63.5(d)(1)(ii)(H)
are not required,
and Sec.
63.5(d)(1)(ii)(G)
and (I) are
Reserved and do not
apply.
* * * * * * *
63.5(f)..................... Yes................. Except that the
cross-reference in
Sec. 63.5(f)(2)
to Sec.
63.9(b)(2) does not
apply.
* * * * * * *
63.6(e)(1)(i) and (ii)...... No.................. See Sec. 63.642(n)
for general duty
requirement.
63.6(e)(1)(iii)............. Yes. ....................
* * * * * * *
63.6(e)(3)(i)............... No. ....................
* * * * * * *
63.6(e)(3)(iii)-63.6(e)(3)(i No. ....................
x).
63.6(f)(1).................. No. ....................
63.6(f)(2).................. Yes................. Except the phrase
``as specified in
Sec. 63.7(c)'' in
Sec.
63.6(f)(2)(iii)(D)
does not apply
because this
subpart does not
require a site-
specific test plan.
63.6(f)(3).................. Yes................. Except the cross-
references to Sec.
63.6(f)(1) and
(e)(1)(i) are
changed to Sec.
63.642(n).
* * * * * * *
63.6(h)(1).................. No. ....................
63.6(h)(2).................. Yes................. Except Sec.
63.6(h)(2)(ii),
which is reserved.
* * * * * * *
63.7(b)..................... Yes................. Except this subpart
requires
notification of
performance test at
least 30 days
(rather than 60
days) prior to the
performance test.
* * * * * * *
63.7(e)(1).................. No.................. See Sec.
63.642(d)(3).
* * * * * * *
63.8(a)(1) and (2).......... Yes. ....................
63.8(a)(3).................. No.................. Reserved.
63.8(a)(4).................. Yes................. Except that for a
flare complying
with Sec. 63.670,
the cross-reference
to Sec. 63.11 in
this paragraph does
not include Sec.
63.11(b).
* * * * * * *
63.8(c)(1).................. Yes................. Except Sec.
63.8(c)(1)(i) and
(iii).
63.8(c)(1)(i)............... No.................. See Sec.
63.642(n).
63.8(c)(1)(iii)............. No. ....................
[[Page 75269]]
* * * * * * *
63.8(c)(4).................. Yes................. Except that for
sources other than
flares, this
subpart specifies
the monitoring
cycle frequency
specified in Sec.
63.8(c)(4)(ii) is
``once every hour''
rather than ``for
each successive 15-
minute period.''
63.8(c)(5)-63.8(c)(8)....... No.................. This subpart
specifies
continuous
monitoring system
requirements.
63.8(d)..................... No.................. This subpart
specifies quality
control procedures
for continuous
monitoring systems.
63.8(e)..................... Yes. ....................
* * * * * * *
63.8(g)..................... No.................. This subpart
specifies data
reduction
procedures in Sec.
Sec. 63.655(i)(3)
and 63.671(d).
* * * * * * *
63.10(b)(2)(i).............. No. ....................
63.10(b)(2)(ii)............. No.................. Sec. 63.655(i)
specifies the
records that must
be kept.
* * * * * * *
63.10(b)(2)(iv)............. No. ....................
63.10(b)(2)(v).............. No. ....................
* * * * * * *
63.10(b)(2)(vii)............ No.................. Sec. 63.655(i)
specifies records
to be kept for
parameters measured
with continuous
monitors.
* * * * * * *
63.10(c)(9)................. No.................. Reserved.
63.10(c)(10)-63.10(c)(11)... No.................. Sec. 63.655(i)
specifies the
records that must
be kept.
63.10(c)(12)-63.10(c)(15)... No. ....................
* * * * * * *
63.10(d)(2)................. No.................. Although Sec.
63.655(f) specifies
performance test
reporting, EPA may
approve other
timeframes for
submittal of
performance test
data.
* * * * * * *
63.10(d)(5)................. No.................. Sec. 63.655(g)
specifies the
reporting
requirements.
* * * * * * *
63.11....................... Yes................. Except that flares
complying with Sec.
63.670 are not
subject to the
requirements of
Sec. 63.11(b).
63.12-63.16................. Yes.
------------------------------------------------------------------------
\a\ Wherever subpart A of this part specifies ``postmark'' dates,
submittals may be sent by methods other than the U.S. Mail (e.g., by
fax or courier). Submittals shall be sent by the specified dates, but
a postmark is not required.
0
35. The appendix to subpart CC is amended in table 10 by:
0
a. Redesignating the entry ``Flare'' as ``Flare (if meeting the
requirements of Sec. Sec. 63.643 and 63.644)'';
0
b. Adding the entry ``Flare (if meeting the requirements of Sec. Sec.
63.670 and 63.671)'' after newly redesignated entry ``Flare (if meeting
the requirements of Sec. Sec. 63.643 and 63.644)'';
0
c. Revising the entry ``All control devices''; and
0
d. Revising footnote i.
The revisions and additions read as follows:
Appendix to Subpart CC of Part 63--Tables
* * * * *
Table 10--Miscellaneous Process Vents--Monitoring, Recordkeeping and
Reporting Requirements for Complying With 98 Weight-Percent Reduction of
Total Organic HAP Emissions or a Limit of 20 Parts per Million by Volume
------------------------------------------------------------------------
Recordkeeping and
Parameters to be reporting
Control device monitored \a\ requirements for
monitored parameters
------------------------------------------------------------------------
* * * * * * *
Flare (if meeting the The parameters 1. Records as
requirements of Sec. Sec. specified in specified in Sec.
63.670 and 63.671). Sec. 63.670. 63.655(i)(9).
2. Report information
as specified in Sec.
63.655(g)(11)--
PR.\g\
All control devices........... Presence of flow 1. Hourly records of
diverted to the whether the flow
atmosphere from indicator was
the control operating and
device (Sec. whether flow was
63.644(c)(1)) or detected at any time
during each hour.
Record and report
the times and
durations of all
periods when the
vent stream is
diverted through a
bypass line or the
monitor is not
operating--PR.\g\
[[Page 75270]]
Monthly 1. Records that
inspections of monthly inspections
sealed valves were performed.
(Sec. 2. Record and report
63.644(c)(2)). all monthly
inspections that
show the valves are
not closed or the
seal has been
changed--PR.\g\
------------------------------------------------------------------------
\a\ Regulatory citations are listed in parentheses.
* * * * * * *
\g\ PR = Periodic Reports described in Sec. 63.655(g).
* * * * * * *
\i\ Process vents that are routed to refinery fuel gas systems are not
regulated under this subpart provided that on and after January 30,
2019, any flares receiving gas from that fuel gas system are in
compliance with Sec. 63.670. No monitoring, recordkeeping, or
reporting is required for boilers and process heaters that combust
refinery fuel gas.
0
36. The appendix to subpart CC is amended by adding table 11 to read as
follows:
Appendix to Subpart CC of Part 63--Tables
* * * * *
Table 11--Compliance Dates and Requirements
----------------------------------------------------------------------------------------------------------------
Then the owner or And the owner or
If the construction/reconstruction operator must comply operator must achieve Except as provided in .
date \a\ is . . . with . . . compliance . . . . .
----------------------------------------------------------------------------------------------------------------
(1) After June 30, 2014.............. (i) Requirements for Upon initial startup or Sec. 63.640(k), (l)
new sources in Sec. February 1, 2016, and (m).
Sec. 63.640 through whichever is later.
63.642, 63.647, 63.650
through 63.653, and
63.656 through 63.660.
(ii) The new source Upon initial startup or Sec. 63.640(k), (l)
requirements in Sec. October 28, 2009, and (m).
63.654 for heat whichever is later.
exchange systems.
(2) After September 4, 2007 but on or (i) Requirements for Upon initial startup... Sec. 63.640(k), (l)
before June 30, 2014. new sources in Sec. and (m).
Sec. 63.640 through
63.653 and 63.656 \b\
\c\.
(ii) Requirements for On or before January Sec. 63.640(k), (l)
new sources in Sec. 30, 2019. and (m).
Sec. 63.640 through
63.645, Sec. Sec.
63.647 through 63.653,
and Sec. Sec.
63.656 and 63.657 \b\.
(iii) Requirements for On or before January Sec. 63.640(k), (l)
existing sources in 30, 2018. and (m).
Sec. 63.658.
(iv) Requirements for On or before April 29, Sec. 63.640(k), (l)
new sources in Sec. 2016. and (m).
63.660 \c\.
(v) The new source Upon initial startup or Sec. 63.640(k), (l)
requirements in Sec. October 28, 2009, and (m).
63.654 for heat whichever is later.
exchange systems.
(3) After July 14, 1994 but on or (i) Requirements for Upon initial startup or Sec. 63.640(k), (l)
before September 4, 2007. new sources in Sec. August 18, 1995, and (m).
Sec. 63.640 through whichever is later.
63.653 and 63.656 \d\
\e\.
(ii) Requirements for On or before January Sec. 63.640(k), (l)
new sources in Sec. 30, 2019. and (m).
Sec. 63.640 through
63.645, 63.647 through
63.653, and 63.656 and
63.657 \d\.
(iii) Requirements for On or before January Sec. 63.640(k), (l)
existing sources in 30, 2018. and (m).
Sec. 63.658.
(iv) Requirements for On or before April 29, Sec. 63.640(k), (l)
new sources in Sec. 2016. and (m).
63.660 \e\.
(v) The existing source On or before October Sec. 63.640(k), (l)
requirements in Sec. 29, 2012. and (m).
63.654 for heat
exchange systems.
(4) On or before July 14, 1994....... (i) Requirements for (a) On or before August (1) Sec. 63.640(k),
existing sources in 18, 1998. (l) and (m).
Sec. Sec. 63.640 (2) Sec. 63.6(c)(5)
through 63.653 and of subpart A of this
63.656 \f\ \g\. part or unless an
extension has been
granted by the
Administrator as
provided in Sec.
63.6(i) of subpart A
of this part.
(ii) Requirements for On or before January Sec. 63.640(k), (l)
existing sources in 30, 2019. and (m).
Sec. Sec. 63.640
through 63.645, 63.647
through 63.653, and
63.656 and 63.657 \f\.
[[Page 75271]]
(iii) Requirements for On or before January Sec. 63.640(k), (l)
existing sources in 30, 2018. and (m).
Sec. 63.658.
(iv) Requirements for On or before April 29, Sec. 63.640(k), (l)
existing sources in 2016. and (m).
Sec. 63.660 \g\.
(v) The existing source requirements On or before October Sec. 63.640(k), (l)
in Sec. 63.654 for heat exchange 29, 2012. and (m).
systems
----------------------------------------------------------------------------------------------------------------
\a\ For purposes of this table, the construction/reconstruction date means the date of construction or
reconstruction of an entire affected source or the date of a process unit addition or change meeting the
criteria in Sec. 63.640(i) or (j). If a process unit addition or change does not meet the criteria in Sec.
63.640(i) or (j), the process unit shall comply with the applicable requirements for existing sources.
\b\ Between the compliance dates in items (2)(i) and (2)(ii) of this table, the owner or operator may elect to
comply with either the requirements in item (2)(i) or item (2)(ii) of this table. The requirements in item
(2)(i) of this table no longer apply after demonstrated compliance with the requirements in item (2)(ii) of
this table.
\c\ Between the compliance dates in items (2)(i) and (2)(iv) of this table, the owner or operator may elect to
comply with either the requirements in item (2)(i) or item (2)(iv) of this table. The requirements in item
(2)(i) of this table no longer apply after demonstrated compliance with the requirements in item (2)(iv) of
this table.
\d\ Between the compliance dates in items (3)(i) and (3)(ii) of this table, the owner or operator may elect to
comply with either the requirements in item (3)(i) or item (3)(ii) of this table. The requirements in item
(3)(i) of this table no longer apply after demonstrated compliance with the requirements in item (3)(ii) of
this table.
\e\ Between the compliance dates in items (3)(i) and (3)(iv) of this table, the owner or operator may elect to
comply with either the requirements in item (3)(i) or item (3)(iv) of this table. The requirements in item
(3)(i) of this table no longer apply after demonstrated compliance with the requirements in item (3)(iv) of
this table.
\f\ Between the compliance dates in items (4)(i) and (4)(ii) of this table, the owner or operator may elect to
comply with either the requirements in item (4)(i) or item (4)(ii) of this table. The requirements in item
(4)(i) of this table no longer apply after demonstrated compliance with the requirements in item (4)(ii) of
this table.
\g\ Between the compliance dates in items (4)(i) and (4)(iv) of this table, the owner or operator may elect to
comply with either the requirements in item (4)(i) or item (4)(iv) of this table. The requirements in item
(4)(i) of this table no longer apply after demonstrated compliance with the requirements in item (4)(iv) of
this table.
0
37. The appendix to subpart CC is amended by adding table 12 to read as
follows:
Appendix to Subpart CC of Part 63--Tables
* * * * *
Table 12--Individual Component Properties
----------------------------------------------------------------------------------------------------------------
NHVi (British
MWi (pounds CMNi (mole thermal units LFLi (volume
Component Molecular formula per pound- per mole) per standard %)
mole) cubic foot)
----------------------------------------------------------------------------------------------------------------
Acetylene................... C2H2.............. 26.04 2 1,404 2.5
Benzene..................... C6H6.............. 78.11 6 3,591 1.3
1,2-Butadiene............... C4H6.............. 54.09 4 2,794 2.0
1,3-Butadiene............... C4H6.............. 54.09 4 2,690 2.0
iso-Butane.................. C4H10............. 58.12 4 2,957 1.8
n-Butane.................... C4H10............. 58.12 4 2,968 1.8
cis-Butene.................. C4H8.............. 56.11 4 2,830 1.6
iso-Butene.................. C4H8.............. 56.11 4 2,928 1.8
trans-Butene................ C4H8.............. 56.11 4 2,826 1.7
Carbon Dioxide.............. CO2............... 44.01 1 0 [infin]
Carbon Monoxide............. CO................ 28.01 1 316 12.5
Cyclopropane................ C3H6.............. 42.08 3 2,185 2.4
Ethane...................... C2H6.............. 30.07 2 1,595 3.0
Ethylene.................... C2H4.............. 28.05 2 1,477 2.7
Hydrogen.................... H2................ 2.02 0 1,212\a\ 4.0
Hydrogen Sulfide............ H2S............... 34.08 0 587 4.0
Methane..................... CH4............... 16.04 1 896 5.0
Methyl-Acetylene............ C3H4.............. 40.06 3 2,088 1.7
Nitrogen.................... N2................ 28.01 0 0 [infin]
Oxygen...................... O2................ 32.00 0 0 [infin]
Pentane+ (C5+).............. C5H12............. 72.15 5 3,655 1.4
Propadiene.................. C3H4.............. 40.06 3 2,066 2.16
Propane..................... C3H8.............. 44.10 3 2,281 2.1
Propylene................... C3H6.............. 42.08 3 2,150 2.4
Water....................... H2O............... 18.02 0 0 [infin]
----------------------------------------------------------------------------------------------------------------
\a\ The theoretical net heating value for hydrogen is 274 Btu/scf, but for the purposes of the flare requirement
in this subpart, a net heating value of 1,212 Btu/scf shall be used.
[[Page 75272]]
0
38. The appendix to subpart CC is amended by adding table 13 to read as
follows:
Appendix to Subpart CC of Part 63--Tables
* * * * *
Table 13--Calibration and Quality Control Requirements for CPMS
------------------------------------------------------------------------
Minimum accuracy Calibration
Parameter requirements requirements
------------------------------------------------------------------------
Temperature................... 1 Conduct calibration
percent over the checks at least
normal range of annually; conduct
temperature calibration checks
measured, following any period
expressed in of more than 24
degrees Celsius hours throughout
(C), or 2.8 which the
degrees C, temperature exceeded
whichever is the manufacturer's
greater. specified maximum
rated temperature or
install a new
temperature sensor.
At least quarterly,
inspect all
components for
integrity and all
electrical
connections for
continuity,
oxidation, and
galvanic corrosion,
unless the CPMS has
a redundant
temperature sensor.
Record the results of
each calibration
check and
inspection.
Locate the
temperature sensor
in a position that
provides a
representative
temperature; shield
the temperature
sensor system from
electromagnetic
interference and
chemical
contaminants.
Flow Rate for All Flows Other 5 Conduct a flow sensor
Than Flare Vent Gas. percent over the calibration check at
normal range of least biennially
flow measured or (every two years);
1.9 liters per conduct a
minute (0.5 calibration check
gallons per following any period
minute), of more than 24
whichever is hours throughout
greater, for which the flow rate
liquid flow. exceeded the
manufacturer's
specified maximum
rated flow rate or
install a new flow
sensor.
5 At least quarterly,
percent over the inspect all
normal range of components for
flow measured or leakage, unless the
280 liters per CPMS has a redundant
minute (10 cubic flow sensor.
feet per
minute),
whichever is
greater, for gas
flow.
5 Record the results of
percent over the each calibration
normal range check and
measured for inspection.
mass flow. Locate the flow
sensor(s) and other
necessary equipment
(such as
straightening vanes)
in a position that
provides
representative flow;
reduce swirling flow
or abnormal velocity
distributions due to
upstream and
downstream
disturbances.
Flare Vent Gas Flow Rate...... 20 Conduct a flow sensor
percent of flow calibration check at
rate at least biennially
velocities (every two years);
ranging from conduct a
0.03 to 0.3 calibration check
meters per following any period
second (0.1 to 1 of more than 24
feet per second). hours throughout
5 which the flow rate
percent of flow exceeded the
rate at manufacturer's
velocities specified maximum
greater than 0.3 rated flow rate or
meters per install a new flow
second (1 feet sensor.
per second). At least quarterly,
inspect all
components for
leakage, unless the
CPMS has a redundant
flow sensor.
Record the results of
each calibration
check and
inspection.
Locate the flow
sensor(s) and other
necessary equipment
(such as
straightening vanes)
in a position that
provides
representative flow;
reduce swirling flow
or abnormal velocity
distributions due to
upstream and
downstream
disturbances.
Pressure...................... 5 Review pressure
percent over the sensor readings at
normal operating least once a week
range or 0.12 for straightline
kilopascals (0.5 (unchanging)
inches of water pressure and perform
column), corrective action to
whichever is ensure proper
greater. pressure sensor
operation if
blockage is
indicated.
Using an instrument
recommended by the
sensor's
manufacturer, check
gauge calibration
and transducer
calibration
annually; conduct
calibration checks
following any period
of more than 24
hours throughout
which the pressure
exceeded the
manufacturer's
specified maximum
rated pressure or
install a new
pressure sensor.
At least quarterly,
inspect all
components for
integrity, all
electrical
connections for
continuity, and all
mechanical
connections for
leakage, unless the
CPMS has a redundant
pressure sensor.
Record the results of
each calibration
check and
inspection.
Locate the pressure
sensor(s) in a
position that
provides a
representative
measurement of the
pressure and
minimizes or
eliminates pulsating
pressure, vibration,
and internal and
external corrosion.
Net Heating Value by 2 Specify calibration
Calorimeter. percent of span. requirements in your
site specific CPMS
monitoring plan.
Calibration
requirements should
follow
manufacturer's
recommendations at a
minimum.
Temperature control
(heated and/or
cooled as necessary)
the sampling system
to ensure proper
year-round
operation.
Where feasible,
select a sampling
location at least
two equivalent
diameters downstream
from and 0.5
equivalent diameters
upstream from the
nearest disturbance.
Select the sampling
location at least
two equivalent duct
diameters from the
nearest control
device, point of
pollutant
generation, air in-
leakages, or other
point at which a
change in the
pollutant
concentration or
emission rate
occurs.
[[Page 75273]]
Net Heating Value by Gas As specified in Follow the procedure
Chromatograph. Performance in Performance
Specification 9 Specification 9 of
of 40 CFR part 40 CFR part 60,
60, appendix B appendix B, except
that a single daily
mid-level
calibration check
can be used (rather
than triplicate
analysis), the multi-
point calibration
can be conducted
quarterly (rather
than monthly), and
the sampling line
temperature must be
maintained at a
minimum temperature
of 60 [deg]C (rather
than 120 [deg]C).
Hydrogen analyzer............. 2 Specify calibration
percent over the requirements in your
concentration site specific CPMS
measured or 0.1 monitoring plan.
volume percent, Calibration
whichever is requirements should
greater. follow
manufacturer's
recommendations at a
minimum.
Select the sampling
location at least
two equivalent duct
diameters from the
nearest control
device, point of
pollutant
generation, air in-
leakages, or other
point at which a
change in the
pollutant
concentration
occurs.
------------------------------------------------------------------------
Subpart UUU---National Emission Standards for Hazardous Air
Pollutants for Petroleum Refineries: Catalytic Cracking Units,
Catalytic Reforming Units, and Sulfur Recovery Units
0
39. Section 63.1562 is amended by revising paragraphs (b)(3) and (f)(5)
to read as follows:
Sec. 63.1562 What parts of my plant are covered by this subpart?
* * * * *
(b) * * *
(3) The process vent or group of process vents on Claus or other
types of sulfur recovery plant units or the tail gas treatment units
serving sulfur recovery plants that are associated with sulfur
recovery.
* * * * *
(f) * * *
(5) Gaseous streams routed to a fuel gas system, provided that on
and after January 30, 2019, any flares receiving gas from the fuel gas
system are subject to Sec. 63.670.
0
40. Section 63.1564 is amended by:
0
a. Revising paragraphs (a)(1) and (2);
0
b. Adding paragraph (a)(5);
0
c. Removing the equation following paragraph (b)(4)(ii) and adding it
after paragraph (b)(4)(iii) introductory text;
0
d. Revising paragraphs (b)(2), (b)(4)(i) and (ii), and (b)(4)(iv); and
0
e. Adding paragraph (c)(5).
The revisions and additions read as follows:
Sec. 63.1564 What are my requirements for metal HAP emissions from
catalytic cracking units?
(a) * * *
(1) Except as provided in paragraph (a)(5) of this section, meet
each emission limitation in Table 1 of this subpart that applies to
you. If your catalytic cracking unit is subject to the NSPS for PM in
Sec. 60.102 of this chapter or is subject to Sec. 60.102a(b)(1) of
this chapter, you must meet the emission limitations for NSPS units. If
your catalytic cracking unit is not subject to the NSPS for PM, you can
choose from the four options in paragraphs (a)(1)(i) through (vi) of
this section:
(i) You can elect to comply with the NSPS for PM in Sec. 60.102 of
this chapter (Option 1a);
(ii) You can elect to comply with the NSPS for PM coke burn-off
emission limit in Sec. 60.102a(b)(1) of this chapter (Option 1b);
(iii) You can elect to comply with the NSPS for PM concentration
limit in Sec. 60.102a(b)(1) of this chapter (Option 1c);
(iv) You can elect to comply with the PM per coke burn-off emission
limit in Sec. 60.102a(b)(1) of this chapter (Option 2);
(v) You can elect to comply with the Nickel (Ni) lb/hr emission
limit (Option 3); or
(vi) You can elect to comply with the Ni per coke burn-off emission
limit (Option 4).
(2) Comply with each operating limit in Table 2 of this subpart
that applies to you. When a specific control device may be monitored
using more than one continuous parameter monitoring system, you may
select the parameter with which you will comply. You must provide
notice to the Administrator (or other designated authority) if you
elect to change the monitoring option.
* * * * *
(5) During periods of startup, shutdown and hot standby, you can
choose from the two options in paragraphs (a)(5)(i) and (ii) of this
section:
(i) You can elect to comply with the requirements in paragraphs
(a)(1) and (2) of this section, except catalytic cracking units
controlled using a wet scrubber must maintain only the liquid to gas
ratio operating limit (the pressure drop operating limit does not
apply); or
(ii) You can elect to maintain the inlet velocity to the primary
internal cyclones of the catalytic cracking unit catalyst regenerator
at or above 20 feet per second.
(b) * * *
(2) Conduct a performance test for each catalytic cracking unit
according to the requirements in Sec. 63.1571 and under the conditions
specified in Table 4 of this subpart.
* * * * *
(4) * * *
(i) If you elect Option 1b or Option 2 in paragraph (a)(1)(ii) or
(iv) of this section, compute the PM emission rate (lb/1,000 lb of coke
burn-off) for each run using Equations 1, 2, and 3 (if applicable) of
this section and the site-specific opacity limit, if applicable, using
Equation 4 of this section as follows:
[GRAPHIC] [TIFF OMITTED] TR01DE15.018
Where:
Rc = Coke burn-off rate, kg/hr (lb/hr);
Qr = Volumetric flow rate of exhaust gas from catalyst
regenerator before adding air or gas streams. Example: You may
measure upstream or downstream of an
[[Page 75274]]
electrostatic precipitator, but you must measure upstream of a
carbon monoxide boiler, dscm/min (dscf/min). You may use the
alternative in either Sec. 63.1573(a)(1) or (2), as applicable, to
calculate Qr;
Qa = Volumetric flow rate of air to catalytic cracking
unit catalyst regenerator, as determined from instruments in the
catalytic cracking unit control room, dscm/min (dscf/min);
%CO2 = Carbon dioxide concentration in regenerator
exhaust, percent by volume (dry basis);
%CO = Carbon monoxide concentration in regenerator exhaust, percent
by volume (dry basis);
%O2 = Oxygen concentration in regenerator exhaust,
percent by volume (dry basis);
K1 = Material balance and conversion factor, 0.2982 (kg-
min)/(hr-dscm-%) (0.0186 (lb-min)/(hr-dscf-%));
K2 = Material balance and conversion factor, 2.088 (kg-
min)/(hr-dscm) (0.1303 (lb-min)/(hr-dscf));
K3 = Material balance and conversion factor, 0.0994 (kg-
min)/(hr-dscm-%) (0.0062 (lb-min)/(hr-dscf-%));
Qoxy = Volumetric flow rate of oxygen-enriched air stream
to regenerator, as determined from instruments in the catalytic
cracking unit control room, dscm/min (dscf/min); and
%Oxy = Oxygen concentration in oxygen-enriched air
stream, percent by volume (dry basis).
[GRAPHIC] [TIFF OMITTED] TR01DE15.019
Where:
E = Emission rate of PM, kg/1,000 kg (lb/1,000 lb) of coke burn-off;
Cs = Concentration of PM, g/dscm (lb/dscf);
Qsd = Volumetric flow rate of the catalytic cracking unit
catalyst regenerator flue gas as measured by Method 2 in appendix A-
1 to part 60 of this chapter, dscm/hr (dscf/hr);
Rc = Coke burn-off rate, kg coke/hr (1,000 lb coke/hr);
and
K = Conversion factor, 1.0 (kg2/g)/(1,000 kg) (1,000 lb/
(1,000 lb)).
[GRAPHIC] [TIFF OMITTED] TR01DE15.020
Where:
Es = Emission rate of PM allowed, kg/1,000 kg (1b/1,000
lb) of coke burn-off in catalyst regenerator;
1.0 = Emission limitation, kg coke/1,000 kg (lb coke/1,000 lb);
A = Allowable incremental rate of PM emissions. Before August 1,
2017, A = 0.18 g/million cal (0.10 lb/million Btu). On or after
August 1, 2017, A = 0 g/million cal (0 lb/million Btu);
H = Heat input rate from solid or liquid fossil fuel, million cal/hr
(million Btu/hr). Make sure your permitting authority approves
procedures for determining the heat input rate;
Rc = Coke burn-off rate, kg coke/hr (1,000 lb coke/hr)
determined using Equation 1 of this section; and
K' = Conversion factor to units to standard, 1.0 (kg2/g)/
(1,000 kg) (103 lb/(1,000 lb)).
[GRAPHIC] [TIFF OMITTED] TR01DE15.021
Where:
Opacity Limit = Maximum permissible hourly average opacity, percent,
or 10 percent, whichever is greater;
Opacityst = Hourly average opacity measured during the
source test, percent; and
PMEmRst = PM emission rate measured during the source
test, lb/1,000 lb coke burn.
(ii) If you elect Option 1c in paragraph (a)(1)(iii) of this
section, the PM concentration emission limit, determine the average PM
concentration from the initial performance test used to certify your PM
CEMS.
* * * * *
(iv) If you elect Option 4 in paragraph (a)(1)(vi) of this section,
the Ni per coke burn-off emission limit, compute your Ni emission rate
using Equations 1 and 8 of this section and your site-specific Ni
operating limit (if you use a continuous opacity monitoring system)
using Equations 9 and 10 of this section as follows:
[GRAPHIC] [TIFF OMITTED] TR01DE15.022
Where:
ENi2 = Normalized mass emission rate of Ni, mg/kg coke
(lb/1,000 lb coke).
[GRAPHIC] [TIFF OMITTED] TR01DE15.023
[[Page 75275]]
Where:
Opacity2 = Opacity value for use in Equation 10 of this
section, percent, or 10 percent, whichever is greater; and
NiEmR2st = Average Ni emission rate calculated as the
arithmetic average Ni emission rate using Equation 8 of this section
for each of the performance test runs, mg/kg coke.
[GRAPHIC] [TIFF OMITTED] TR01DE15.024
Where:
Ni Operating Limit2 = Maximum permissible hourly average
Ni operating limit, percent-ppmw-acfm-hr/kg coke, i.e., your site-
specific Ni operating limit; and
Rc,st = Coke burn rate from Equation 1 of this section,
as measured during the initial performance test, kg coke/hr.
* * * * *
(c) * * *
(5) If you elect to comply with the alternative limit in paragraph
(a)(5)(ii) of this section during periods of startup, shutdown, and hot
standby, demonstrate continuous compliance by:
(i) Collecting the volumetric flow rate from the catalyst
regenerator (in acfm) and determining the average flow rate for each
hour. For events lasting less than one hour, determine the average flow
rate during the event.
(ii) Determining the cumulative cross-sectional area of the primary
internal cyclone inlets in square feet (ft2) using design
drawings of the primary (first-stage) internal cyclones to determine
the inlet cross-sectional area of each primary internal cyclone and
summing the cross-sectional areas for all primary internal cyclones in
the catalyst regenerator or, if primary cyclones. If all primary
internal cyclones are identical, you may alternatively determine the
inlet cross-sectional area of one primary internal cyclone using design
drawings and multiply that area by the total number of primary internal
cyclones in the catalyst regenerator.
(iii) Calculating the inlet velocity to the primary internal
cyclones in square feet per second (ft2/sec) by dividing the
average volumetric flow rate (acfm) by the cumulative cross-sectional
area of the primary internal cyclone inlets (ft2) and by 60
seconds/minute (for unit conversion).
(iv) Maintaining the inlet velocity to the primary internal
cyclones at or above 20 feet per second for each hour during the
startup, shutdown, or hot standby event or, for events lasting less
than 1 hour, for the duration of the event.
0
41. Section 63.1565 is amended by revising paragraph (a)(1)
introductory text and adding paragraph (a)(5) to read as follows:
Sec. 63.1565 What are my requirements for organic HAP emissions from
catalytic cracking units?
(a) * * *
(1) Except as provided in paragraph (a)(5) of this section, meet
each emission limitation in Table 8 of this subpart that applies to
you. If your catalytic cracking unit is subject to the NSPS for carbon
monoxide (CO) in Sec. 60.103 of this chapter or is subject to Sec.
60.102a(b)(4) of this chapter, you must meet the emission limitations
for NSPS units. If your catalytic cracking unit is not subject to the
NSPS for CO, you can choose from the two options in paragraphs
(a)(1)(i) through (ii) of this section:
* * * * *
(5) During periods of startup, shutdown and hot standby, you can
choose from the two options in paragraphs (a)(5)(i) and (ii) of this
section:
(i) You can elect to comply with the requirements in paragraphs
(a)(1) and (2) of this section; or
(ii) You can elect to maintain the oxygen (O2)
concentration in the exhaust gas from your catalyst regenerator at or
above 1 volume percent (dry basis).
* * * * *
0
42. Section 63.1566 is amended by revising paragraphs (a)(1)
introductory text, (a)(1)(i), and (a)(4) to read as follows:
Sec. 63.1566 What are my requirements for organic HAP emissions from
catalytic reforming units?
(a) * * *
(1) Meet each emission limitation in Table 15 of this subpart that
applies to you. You can choose from the two options in paragraphs
(a)(1)(i) and (ii) of this section.
(i) You can elect to vent emissions of total organic compounds
(TOC) to a flare (Option 1). On and after January 30, 2019, the flare
must meet the requirements of Sec. 63.670. Prior to January 30, 2019,
the flare must meet the control device requirements in Sec. 63.11(b)
or the requirements of Sec. 63.670.
* * * * *
(4) The emission limitations in Tables 15 and 16 of this subpart do
not apply to emissions from process vents during passive depressuring
when the reactor vent pressure is 5 pounds per square inch gauge (psig)
or less. The emission limitations in Tables 15 and 16 of this subpart
do apply to emissions from process vents during active purging
operations (when nitrogen or other purge gas is actively introduced to
the reactor vessel) or active depressuring (using a vacuum pump,
ejector system, or similar device) regardless of the reactor vent
pressure.
* * * * *
0
43. Section 63.1568 is amended by revising paragraphs (a)(1)
introductory text and (a)(1)(i) and adding paragraph (a)(4) to read as
follows:
Sec. 63.1568 What are my requirements for HAP emissions from sulfur
recovery units?
(a) * * *
(1) Meet each emission limitation in Table 29 of this subpart that
applies to you. If your sulfur recovery unit is subject to the NSPS for
sulfur oxides in Sec. 60.104 or Sec. 60.102a(f)(1) of this chapter,
you must meet the emission limitations for NSPS units. If your sulfur
recovery unit is not subject to one of these NSPS for sulfur oxides,
you can choose from the options in paragraphs (a)(1)(i) through (ii) of
this section:
(i) You can elect to meet the NSPS requirements in Sec.
60.104(a)(2) or Sec. 60.102a(f)(1) of this chapter (Option 1); or
* * * * *
(4) During periods of startup and shutdown, you can choose from the
three options in paragraphs (a)(4)(i) through (iii) of this section.
(i) You can elect to comply with the requirements in paragraphs
(a)(1) and (2) of this section.
(ii) You can elect to send any startup or shutdown purge gases to a
flare. On and after January 30, 2019, the flare must meet the
requirements of Sec. 63.670. Prior to January 30, 2019, the flare must
meet the design and operating requirements in Sec. 63.11(b) or the
requirements of Sec. 63.670.
(iii) You can elect to send any startup or shutdown purge gases to
a thermal oxidizer or incinerator operated at a
[[Page 75276]]
minimum hourly average temperature of 1,200 degrees Fahrenheit in the
firebox and a minimum hourly average outlet oxygen (O2)
concentration of 2 volume percent (dry basis).
* * * * *
0
44. Section 63.1570 is amended by revising paragraphs (a) through (d)
and removing paragraph (g) to read as follows:
Sec. 63.1570 What are my general requirements for complying with this
subpart?
(a) You must be in compliance with all of the non-opacity standards
in this subpart at all times.
(b) You must be in compliance with the opacity and visible emission
limits in this subpart at all times.
(c) At all times, you must operate and maintain any affected
source, including associated air pollution control equipment and
monitoring equipment, in a manner consistent with safety and good air
pollution control practices for minimizing emissions. The general duty
to minimize emissions does not require you to make any further efforts
to reduce emissions if levels required by the applicable standard have
been achieved. Determination of whether a source is operating in
compliance with operation and maintenance requirements will be based on
information available to the Administrator which may include, but is
not limited to, monitoring results, review of operation and maintenance
procedures, review of operation and maintenance records, and inspection
of the source.
(d) During the period between the compliance date specified for
your affected source and the date upon which continuous monitoring
systems have been installed and validated and any applicable operating
limits have been set, you must maintain a log that documents the
procedures used to minimize emissions from process and emissions
control equipment according to the general duty in paragraph (c) of
this section.
* * * * *
0
45. Section 63.1571 is amended by:
0
a. Adding paragraphs (a)(5) and (6);
0
b. Revising paragraph (b)(1);
0
c. Removing paragraph (b)(4);
0
d. Redesignating paragraph (b)(5) as paragraph (b)(4); and
0
e. Revising the first sentence of paragraph (d)(2) and paragraph
(d)(4).
The revisions and additions read as follows:
Sec. 63.1571 How and when do I conduct a performance test or other
initial compliance demonstration?
(a) * * *
(5) Periodic performance testing for PM or Ni. Except as provided
in paragraphs (a)(5)(i) and (ii) of this section, conduct a periodic
performance test for PM or Ni for each catalytic cracking unit at least
once every 5 years according to the requirements in Table 4 of this
subpart. You must conduct the first periodic performance test no later
than August 1, 2017.
(i) Catalytic cracking units monitoring PM concentration with a PM
CEMS are not required to conduct a periodic PM performance test.
(ii) Conduct a performance test annually if you comply with the
emission limits in Item 1 (NSPS subpart J) or Item 4 (Option 1a) in
Table 1 of this subpart and the PM emissions measured during the most
recent performance source test are greater than 0.80 g/kg coke burn-
off.
(6) One-time performance testing for HCN. Conduct a performance
test for HCN from each catalytic cracking unit no later than August 1,
2017 according to the applicable requirements in paragraphs (a)(6)(i)
and (ii) of this section.
(i) If you conducted a performance test for HCN for a specific
catalytic cracking unit between March 31, 2011 and February 1, 2016,
you may submit a request to the Administrator to use the previously
conducted performance test results to fulfill the one-time performance
test requirement for HCN for each of the catalytic cracking units
tested according to the requirements in paragraphs (a)(6)(i)(A) through
(D) of this section.
(A) The request must include a copy of the complete source test
report, the date(s) of the performance test and the test methods used.
If available, you must also indicate whether the catalytic cracking
unit catalyst regenerator was operated in partial or complete
combustion mode during the test, the control device configuration,
including whether platinum or palladium combustion promoters were used
during the test, and the CO concentration (measured using CO CEMS or
manual test method) for each test run.
(B) You must submit a separate request for each catalytic cracking
unit tested and you must submit each request to the Administrator no
later than March 30, 2016.
(C) The Administrator will evaluate each request with respect to
the completeness of the request, the completeness of the submitted test
report and the appropriateness of the test methods used. The
Administrator will notify the facility within 60 days of receipt of the
request if it is approved or denied. If the Administrator fails to
respond to the facility within 60 days of receipt of the request, the
request will be automatically approved.
(D) If the request is approved, you do not need to conduct an
additional HCN performance test. If the request is denied, you must
conduct an additional HCN performance test following the requirements
in (a)(6)(ii) of this section.
(ii) Unless you receive approval to use a previously conducted
performance test to fulfill the one-time performance test requirement
for HCN for your catalytic cracking unit as provided in paragraph
(a)(6)(i) of this section, conduct a performance test for HCN for each
catalytic cracking unit no later than August 1, 2017 according to
following requirements:
(A) Select sampling port location, determine volumetric flow rate,
conduct gas molecular weight analysis and measure moisture content as
specified in either Item 1 of Table 4 of this subpart or Item 1 of
Table 11 of this subpart.
(B) Measure HCN concentration using Method 320 of appendix A of
this part. The method ASTM D6348-03 (Reapproved 2010) including Annexes
A1 through A8 (incorporated by reference--see Sec. 63.14) is an
acceptable alternative to EPA Method 320 of appendix A of this part.
The method ASTM D6348-12e1 (incorporated by reference--see Sec. 63.14)
is an acceptable alternative to EPA Method 320 of appendix A of this
part with the following two caveats:
(1) The test plan preparation and implementation in the Annexes to
ASTM D6348-03 (Reapproved 2010), Sections A1 through A8 are mandatory;
and
(2) In ASTM D6348-03 (Reapproved 2010) Annex A5 (Analyte Spiking
Technique), the percent (%) R must be determined for each target
analyte (Equation A5.5). In order for the test data to be acceptable
for a compound, %R must be 70% >= R <= 130%. If the %R value does not
meet this criterion for a target compound, the test data is not
acceptable for that compound and the test must be repeated for that
analyte (i.e., the sampling and/or analytical procedure should be
adjusted before a retest). The %R value for each compound must be
reported in the test report, and all field measurements must be
corrected with the calculated %R value for that compound by using the
following equation:
[[Page 75277]]
Reported Result = (Measured Concentration in the Stack x 100//% R.
(C) Measure CO concentration as specified in either Item 2 or 3a of
Table 11 of this subpart.
(D) Record and include in the test report an indication of whether
the catalytic cracking unit catalyst regenerator was operated in
partial or complete combustion mode and the control device
configuration, including whether platinum or palladium combustion
promoters were used during the test.
(b) * * *
(1) Performance tests shall be conducted according to the
provisions of Sec. 63.7(e) except that performance tests shall be
conducted at maximum representative operating capacity for the process.
During the performance test, you must operate the control device at
either maximum or minimum representative operating conditions for
monitored control device parameters, whichever results in lower
emission reduction. You must not conduct a performance test during
startup, shutdown, periods when the control device is bypassed or
periods when the process, monitoring equipment or control device is not
operating properly. You may not conduct performance tests during
periods of malfunction. You must record the process information that is
necessary to document operating conditions during the test and include
in such record an explanation to support that the test was conducted at
maximum representative operating capacity. Upon request, you must make
available to the Administrator such records as may be necessary to
determine the conditions of performance tests.
* * * * *
(d) * * *
(2) If you must meet the HAP metal emission limitations in Sec.
63.1564, you elect the option in paragraph (a)(1)(iv) in Sec. 63.1564
(Ni per coke burn-off), and you use continuous parameter monitoring
systems, you must establish an operating limit for the equilibrium
catalyst Ni concentration based on the laboratory analysis of the
equilibrium catalyst Ni concentration from the initial performance
test. * * *
* * * * *
(4) Except as specified in paragraph (d)(3) of this section, if you
use continuous parameter monitoring systems, you may adjust one of your
monitored operating parameters (flow rate, total power and secondary
current, pressure drop, liquid-to-gas ratio) from the average of
measured values during the performance test to the maximum value (or
minimum value, if applicable) representative of worst-case operating
conditions, if necessary. This adjustment of measured values may be
done using control device design specifications, manufacturer
recommendations, or other applicable information. You must provide
supporting documentation and rationale in your Notification of
Compliance Status, demonstrating to the satisfaction of your permitting
authority, that your affected source complies with the applicable
emission limit at the operating limit based on adjusted values.
* * * * *
0
46. Section 63.1572 is amended by revising paragraphs (c) introductory
text, (c)(1), (3), and (4) and (d)(1) and (2) to read as follows:
Sec. 63.1572 What are my monitoring installation, operation, and
maintenance requirements?
* * * * *
(c) Except for flare monitoring systems, you must install, operate,
and maintain each continuous parameter monitoring system according to
the requirements in paragraphs (c)(1) through (5) of this section. For
flares, on and after January 30, 2019, you must install, operate,
calibrate, and maintain monitoring systems as specified in Sec. Sec.
63.670 and 63.671. Prior to January 30, 2019, you must either meet the
monitoring system requirements in paragraphs (c)(1) through (5) of this
section or meet the requirements in Sec. Sec. 63.670 and 63.671.
(1) You must install, operate, and maintain each continuous
parameter monitoring system according to the requirements in Table 41
of this subpart. You must also meet the equipment specifications in
Table 41 of this subpart if pH strips or colormetric tube sampling
systems are used. You must install, operate, and maintain each
continuous parameter monitoring system according to the requirements in
Table 41 of this subpart. You must meet the requirements in Table 41 of
this subpart for BLD systems. Alternatively, before August 1, 2017, you
may install, operate, and maintain each continuous parameter monitoring
system in a manner consistent with the manufacturer's specifications or
other written procedures that provide adequate assurance that the
equipment will monitor accurately.
* * * * *
(3) Each continuous parameter monitoring system must have valid
hourly average data from at least 75 percent of the hours during which
the process operated, except for BLD systems.
(4) Each continuous parameter monitoring system must determine and
record the hourly average of all recorded readings and if applicable,
the daily average of all recorded readings for each operating day,
except for BLD systems. The daily average must cover a 24-hour period
if operation is continuous or the number of hours of operation per day
if operation is not continuous, except for BLD systems.
* * * * *
(d) * * *
(1) You must conduct all monitoring in continuous operation (or
collect data at all required intervals) at all times the affected
source is operating.
(2) You may not use data recorded during required quality assurance
or control activities (including, as applicable, calibration checks and
required zero and span adjustments) for purposes of this regulation,
including data averages and calculations, for fulfilling a minimum data
availability requirement, if applicable. You must use all the data
collected during all other periods in assessing the operation of the
control device and associated control system.
0
47. Section 63.1573 is amended by:
0
a. Redesignating paragraphs (b), (c), (d), (e), and (f) as paragraphs
(c), (d), (e), (f), and (g);
0
b. Adding paragraph (b); and
0
c. Revising newly redesignated paragraphs (c) introductory text, (d)
introductory text, (f) introductory text, and (g)(1) introductory text.
The revisions and additions read as follows:
Sec. 63.1573 What are my monitoring alternatives?
* * * * *
(b) What is the approved alternative for monitoring pressure drop?
You may use this alternative to a continuous parameter monitoring
system for pressure drop if you operate a jet ejector type wet scrubber
or other type of wet scrubber equipped with atomizing spray nozzles.
You shall:
(1) Conduct a daily check of the air or water pressure to the spray
nozzles;
(2) Maintain records of the results of each daily check; and
(3) Repair or replace faulty (e.g., leaking or plugged) air or
water lines within 12 hours of identification of an abnormal pressure
reading.
(c) What is the approved alternative for monitoring pH or
alkalinity levels? You may use the alternative in
[[Page 75278]]
paragraph (c)(1) or (2) of this section for a catalytic reforming unit.
* * * * *
(d) Can I use another type of monitoring system? You may use an
automated data compression system. An automated data compression system
does not record monitored operating parameter values at a set frequency
(e.g., once every hour) but records all values that meet set criteria
for variation from previously recorded values. You must maintain a
record of the description of the monitoring system and data recording
system, including the criteria used to determine which monitored values
are recorded and retained, the method for calculating daily averages,
and a demonstration that the system meets all of the criteria in
paragraphs (d)(1) through (5) of this section:
* * * * *
(f) How do I request to monitor alternative parameters? You must
submit a request for review and approval or disapproval to the
Administrator. The request must include the information in paragraphs
(f)(1) through (5) of this section.
* * * * *
(g) * * *
(1) You may request alternative monitoring requirements according
to the procedures in this paragraph if you meet each of the conditions
in paragraphs (g)(1)(i) through (iii) of this section:
* * * * *
0
48. Section 63.1574 is amended by revising paragraphs (a)(3)
introductory text and (f)(1) to read as follows:
Sec. 63.1574 What notifications must I submit and when?
(a) * * *
(3) If you are required to conduct an initial performance test,
performance evaluation, design evaluation, opacity observation, visible
emission observation, or other initial compliance demonstration, you
must submit a notification of compliance status according to Sec.
63.9(h)(2)(ii). You can submit this information in an operating permit
application, in an amendment to an operating permit application, in a
separate submission, or in any combination. In a State with an approved
operating permit program where delegation of authority under section
112(l) of the CAA has not been requested or approved, you must provide
a duplicate notification to the applicable Regional Administrator. If
the required information has been submitted previously, you do not have
to provide a separate notification of compliance status. Just refer to
the earlier submissions instead of duplicating and resubmitting the
previously submitted information.
* * * * *
(f) * * *
(1) You must submit the plan to your permitting authority for
review and approval along with your notification of compliance status.
While you do not have to include the entire plan in your permit under
part 70 or 71 of this chapter, you must include the duty to prepare and
implement the plan as an applicable requirement in your part 70 or 71
operating permit. You must submit any changes to your permitting
authority for review and approval and comply with the plan as submitted
until the change is approved.
* * * * *
0
49. Section 63.1575 is amended by:
0
a. Revising paragraphs (d) introductory text and (d)(1) and (2);
0
b. Adding paragraph (d)(4);
0
c. Revising paragraph (e) introductory text;
0
d. Removing and reserving paragraph (e)(1);
0
e. Revising paragraphs (e)(4) and (6) and (f)(1) and (2);
0
f. Removing and reserving paragraph (h); and
0
g. Adding paragraph (k).
The revisions and additions read as follows:
Sec. 63.1575 What reports must I submit and when?
* * * * *
(d) For each deviation from an emission limitation and for each
deviation from the requirements for work practice standards that occurs
at an affected source where you are not using a continuous opacity
monitoring system or a continuous emission monitoring system to comply
with the emission limitation or work practice standard in this subpart,
the semiannual compliance report must contain the information in
paragraphs (c)(1) through (3) of this section and the information in
paragraphs (d)(1) through (4) of this section.
(1) The total operating time of each affected source during the
reporting period and identification of the sources for which there was
a deviation.
(2) Information on the number, date, time, duration, and cause of
deviations (including unknown cause, if applicable).
* * * * *
(4) The applicable operating limit or work practice standard from
which you deviated and either the parameter monitor reading during the
deviation or a description of how you deviated from the work practice
standard.
(e) For each deviation from an emission limitation occurring at an
affected source where you are using a continuous opacity monitoring
system or a continuous emission monitoring system to comply with the
emission limitation, you must include the information in paragraphs
(c)(1) through (3) of this section, in paragraphs (d)(1) through (3) of
this section, and in paragraphs (e)(2) through (13) of this section.
* * * * *
(4) An estimate of the quantity of each regulated pollutant emitted
over the emission limit during the deviation, and a description of the
method used to estimate the emissions.
* * * * *
(6) A breakdown of the total duration of the deviations during the
reporting period and into those that are due to control equipment
problems, process problems, other known causes, and other unknown
causes.
* * * * *
(f) * * *
(1) You must include the information in paragraph (f)(1)(i) or (ii)
of this section, if applicable.
(i) If you are complying with paragraph (k)(1) of this section, a
summary of the results of any performance test done during the
reporting period on any affected unit. Results of the performance test
include the identification of the source tested, the date of the test,
the percentage of emissions reduction or outlet pollutant concentration
reduction (whichever is needed to determine compliance) for each run
and for the average of all runs, and the values of the monitored
operating parameters.
(ii) If you are not complying with paragraph (k)(1) of this
section, a copy of any performance test done during the reporting
period on any affected unit. The report may be included in the next
semiannual compliance report. The copy must include a complete report
for each test method used for a particular kind of emission point
tested. For additional tests performed for a similar emission point
using the same method, you must submit the results and any other
information required, but a complete test report is not required. A
complete test report contains a brief process description; a simplified
flow diagram showing affected processes, control equipment, and
sampling point locations; sampling site data; description of sampling
and analysis procedures and any modifications to standard procedures;
quality assurance procedures; record of operating conditions during the
test; record of
[[Page 75279]]
preparation of standards; record of calibrations; raw data sheets for
field sampling; raw data sheets for field and laboratory analyses;
documentation of calculations; and any other information required by
the test method.
(2) Any requested change in the applicability of an emission
standard (e.g., you want to change from the PM standard to the Ni
standard for catalytic cracking units or from the HCl concentration
standard to percent reduction for catalytic reforming units) in your
compliance report. You must include all information and data necessary
to demonstrate compliance with the new emission standard selected and
any other associated requirements.
* * * * *
(k) Electronic submittal of performance test and CEMS performance
evaluation data. For performance tests or CEMS performance evaluations
conducted on and after February 1, 2016, if required to submit the
results of a performance test or CEMS performance evaluation, you must
submit the results according to the procedures in paragraphs (k)(1) and
(2) of this section.
(1) Within 60 days after the date of completing each performance
test as required by this subpart, you must submit the results of the
performance tests following the procedure specified in either paragraph
(k)(1)(i) or (ii) of this section.
(i) For data collected using test methods supported by the EPA's
Electronic Reporting Tool (ERT) as listed on the EPA's ERT Web site
(https://www.epa.gov/ttn/chief/ert/) at the time of the test,
you must submit the results of the performance test to the EPA via the
Compliance and Emissions Data Reporting Interface (CEDRI). (CEDRI can
be accessed through the EPA's Central Data Exchange (CDX) (https://cdx.epa.gov/).) Performance test data must be submitted in a file
format generated through use of the EPA's ERT or an alternate
electronic file format consistent with the extensible markup language
(XML) schema listed on the EPA's ERT Web site. If you claim that some
of the performance test information being submitted is confidential
business information (CBI), you must submit a complete file generated
through the use of the EPA's ERT or an alternate electronic file
consistent with the XML schema listed on the EPA's ERT Web site,
including information claimed to be CBI, on a compact disc, flash drive
or other commonly used electronic storage media to the EPA. The
electronic storage media must be clearly marked as CBI and mailed to
U.S. EPA/OAQPS/CORE CBI Office, Attention: Group Leader, Measurement
Policy Group, MD C404-02, 4930 Old Page Rd., Durham, NC 27703. The same
ERT or alternate file with the CBI omitted must be submitted to the EPA
via the EPA's CDX as described earlier in this paragraph (k)(1)(i).
(ii) For data collected using test methods that are not supported
by the EPA's ERT as listed on the EPA's ERT Web site at the time of the
test, you must submit the results of the performance test to the
Administrator at the appropriate address listed in Sec. 63.13.
(2) Within 60 days after the date of completing each CEMS
performance evaluation required by Sec. 63.1571(a) and (b), you must
submit the results of the performance evaluation following the
procedure specified in either paragraph (k)(2)(i) or (ii) of this
section.
(i) For performance evaluations of continuous monitoring systems
measuring relative accuracy test audit (RATA) pollutants that are
supported by the EPA's ERT as listed on the EPA's ERT Web site at the
time of the evaluation, you must submit the results of the performance
evaluation to the EPA via the CEDRI. (CEDRI is accessed through the
EPA's CDX.) Performance evaluation data must be submitted in a file
format generated through the use of the EPA's ERT or an alternate file
format consistent with the XML schema listed on the EPA's ERT Web site.
If you claim that some of the performance evaluation information being
submitted is CBI, you must submit a complete file generated through the
use of the EPA's ERT or an alternate electronic file consistent with
the XML schema listed on the EPA's ERT Web site, including information
claimed to be CBI, on a compact disc, flash drive or other commonly
used electronic storage media to the EPA. The electronic storage media
must be clearly marked as CBI and mailed to U.S. EPA/OAQPS/CORE CBI
Office, Attention: Group Leader, Measurement Policy Group, MD C404-02,
4930 Old Page Rd., Durham, NC 27703. The same ERT or alternate file
with the CBI omitted must be submitted to the EPA via the EPA's CDX as
described earlier in this paragraph (k)(2)(i).
(ii) For any performance evaluations of continuous monitoring
systems measuring RATA pollutants that are not supported by the EPA's
ERT as listed on the EPA's ERT Web site at the time of the evaluation,
you must submit the results of the performance evaluation to the
Administrator at the appropriate address listed in Sec. 63.13.
0
50. Section 63.1576 is amended by revising paragraphs (a)(2) and (b)(3)
and (5) to read as follows:
Sec. 63.1576 What records must I keep, in what form, and for how
long?
(a) * * *
(2) The records specified in paragraphs (a)(2)(i) through (iv) of
this section.
(i) Record the date, time, and duration of each startup and/or
shutdown period, recording the periods when the affected source was
subject to the standard applicable to startup and shutdown.
(ii) In the event that an affected unit fails to meet an applicable
standard, record the number of failures. For each failure record the
date, time and duration of each failure.
(iii) For each failure to meet an applicable standard, record and
retain a list of the affected sources or equipment, an estimate of the
volume of each regulated pollutant emitted over any emission limit and
a description of the method used to estimate the emissions.
(iv) Record actions taken to minimize emissions in accordance with
Sec. 63.1570(c) and any corrective actions taken to return the
affected unit to its normal or usual manner of operation.
* * * * *
(b) * * *
(3) The performance evaluation plan as described in Sec.
63.8(d)(2) for the life of the affected source or until the affected
source is no longer subject to the provisions of this part, to be made
available for inspection, upon request, by the Administrator. If the
performance evaluation plan is revised, you must keep previous (i.e.,
superseded) versions of the performance evaluation plan on record to be
made available for inspection, upon request, by the Administrator, for
a period of 5 years after each revision to the plan. The program of
corrective action should be included in the plan required under Sec.
63.8(d)(2).
* * * * *
(5) Records of the date and time that each deviation started and
stopped.
* * * * *
0
51. Section 63.1579 is amended by:
0
a. Revising the introductory text;
0
b. Adding, in alphabetical order, a new definition of ``Hot standby'';
and
0
c. Revising the definitions of ``Deviation'' and ``PM''.
The revisions read as follows:
Sec. 63.1579 What definitions apply to this subpart?
Terms used in this subpart are defined in the Clean Air Act (CAA),
in 40 CFR 63.2, the General Provisions of
[[Page 75280]]
this part (Sec. Sec. 63.1 through 63.15), and in this section as
listed. If the same term is defined in subpart A of this part and in
this section, it shall have the meaning given in this section for
purposes of this subpart.
* * * * *
Deviation means any instance in which an affected source subject to
this subpart, or an owner or operator of such a source:
(1) Fails to meet any requirement or obligation established by this
subpart, including but not limited to any emission limit, operating
limit, or work practice standard; or
(2) Fails to meet any term or condition that is adopted to
implement an applicable requirement in this subpart and that is
included in the operating permit for any affected source required to
obtain such a permit.
* * * * *
Hot standby means periods when the catalytic cracking unit is not
receiving fresh or recycled feed oil but the catalytic cracking unit is
maintained at elevated temperatures, typically using torch oil in the
catalyst regenerator and recirculating catalyst, to prevent a complete
shutdown and cold restart of the catalytic cracking unit.
* * * * *
PM means, for the purposes of this subpart, emissions of
particulate matter that serve as a surrogate measure of the total
emissions of particulate matter and metal HAP contained in the
particulate matter, including but not limited to: Antimony, arsenic,
beryllium, cadmium, chromium, cobalt, lead, manganese, nickel, and
selenium as measured by Methods 5, 5B or 5F in appendix A-3 to part 60
of this chapter or by an approved alternative method.
* * * * *
0
52. Table 1 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1564(a)(1), you shall meet each emission
limitation in the following table that applies to you.
Table 1 to Subpart UUU of Part 63--Metal HAP Emission Limits for
Catalytic Cracking Units
------------------------------------------------------------------------
You shall meet the following
For each new or existing catalytic emission limits for each
cracking unit . . . catalyst regenerator vent . . .
------------------------------------------------------------------------
1. Subject to new source performance PM emissions must not exceed
standard (NSPS) for PM in 40 CFR 1.0 gram per kilogram (g/kg)
60.102 and not electing Sec. (1.0 lb/1,000 lb) of coke burn-
60.100(e). off, and the opacity of
emissions must not exceed 30
percent, except for one 6-
minute average opacity reading
in any 1-hour period. Before
August 1, 2017, if the
discharged gases pass through
an incinerator or waste heat
boiler in which you burn
auxiliary or in supplemental
liquid or solid fossil fuel,
the incremental rate of PM
emissions must not exceed 43.0
grams per Gigajoule (g/GJ) or
0.10 pounds per million
British thermal units (lb/
million Btu) of heat input
attributable to the liquid or
solid fossil fuel; and the
opacity of emissions must not
exceed 30 percent, except for
one 6-minute average opacity
reading in any 1-hour period.
2. Subject to NSPS for PM in 40 CFR PM emissions must not exceed
60.102a(b)(1)(i); or 40 CFR 60.102 and 1.0 g/kg (1.0 lb PM/1,000 lb)
electing Sec. 60.100(e). of coke burn-off or, if a PM
CEMS is used, 0.040 grain per
dry standard cubic feet (gr/
dscf) corrected to 0 percent
excess air.
3. Subject to NSPS for PM in 40 CFR PM emissions must not exceed
60.102a(b)(1)(ii). 0.5 g/kg coke burn-off (0.5 lb/
1000 lb coke burn-off) or, if
a PM CEMS is used, 0.020 gr/
dscf corrected to 0 percent
excess air.
4. Option 1a: Elect NSPS subpart J PM emissions must not exceed
requirements for PM per coke burn the limits specified in Item 1
limit and 30% opacity, not subject to of this table.
the NSPS for PM in 40 CFR 60.102 or
60.102a(b)(1).
5. Option 1b: Elect NSPS subpart Ja PM emissions must not exceed
requirements for PM per coke burn-off 1.0 g/kg (1.0 lb PM/1000 lb)
limit, not subject to the NSPS for PM of coke burn-off.
in 40 CFR 60.102 or 60.102a(b)(1).
6. Option 1c: Elect NSPS subpart Ja PM emissions must not exceed
requirements for PM concentration 0.040 gr/dscf corrected to 0
limit, not subject to the NSPS for PM percent excess air.
in 40 CFR 60.102 or 60.102a(b)(1).
7. Option 2: PM per coke burn-off PM emissions must not exceed
limit, not subject to the NSPS for PM 1.0 g/kg (1.0 lb PM/1000 lb)
in 40 CFR 60.102 or 60.102a(b)(1). of coke burn-off in the
catalyst regenerator.
8. Option 3: Ni lb/hr limit, not Nickel (Ni) emissions must not
subject to the NSPS for PM in 40 CFR exceed 13,000 milligrams per
60.102 or 60.102a(b)(1). hour (mg/hr) (0.029 lb/hr).
9. Option 4: Ni per coke burn-off Ni emissions must not exceed
limit, not subject to the NSPS for PM 1.0 mg/kg (0.001 lb/1,000 lb)
in 40 CFR 60.102 or 60.102a(b)(1). of coke burn-off in the
catalyst regenerator.
------------------------------------------------------------------------
0
53. Table 2 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1564(a)(2), you shall meet each operating
limit in the following table that applies to you.
Table 2 to Subpart UUU of Part 63--Operating Limits for Metal HAP Emissions From Catalytic Cracking Units
----------------------------------------------------------------------------------------------------------------
For this type of
For each new or existing catalytic continuous monitoring For this type of You shall meet this
cracking unit . . . system . . . control device . . . operating limit . . .
----------------------------------------------------------------------------------------------------------------
1. Subject to the NSPS for PM in 40 Continuous opacity Any.................... Maintain the 3-hour
CFR 60.102 and not electing Sec. monitoring system. rolling average
60.100(e). opacity of emissions
from your catalyst
regenerator vent no
higher than 20
percent.
[[Page 75281]]
2. Subject to NSPS for PM in 40 CFR a. PM CEMS............. Any.................... Not applicable.
60.102a(b)(1)(i) or electing Sec.
60.100(e).
b. Continuous opacity Cyclone or Maintain the 3-hour
monitoring system used electrostatic rolling average
to comply with a site- precipitator. opacity of emissions
specific opacity limit. from your catalyst
regenerator vent no
higher than the site-
specific opacity limit
established during the
performance test.
c. Continuous parameter Electrostatic i. Maintain the daily
monitoring systems. precipitator. average coke burn-off
rate or daily average
flow rate no higher
than the limit
established in the
performance test.
ii. Maintain the 3-hour
rolling average total
power and secondary
current above the
limit established in
the performance test.
d. Continuous parameter Wet scrubber........... i. Maintain the 3-hour
monitoring systems. rolling average liquid-
to-gas ratio above the
limit established in
the performance test.
ii. Except for periods
of startup, shutdown,
and hot standby,
maintain the 3-hour
rolling average
pressure drop above
the limit established
in the performance
test.\1\
e. Bag leak detection Fabric filter.......... Maintain particulate
(BLD) system. loading below the BLD
alarm set point
established in the
initial adjustment of
the BLD system or
allowable seasonal
adjustments.
3. Subject to NSPS for PM in 40 CFR Any.................... Any.................... The applicable
60.102a(b)(1)(ii). operating limits in
Item 2 of this table.
4. Option 1a: Elect NSPS subpart J Any.................... Any.................... See Item 1 of this
requirements for PM per coke burn table.
limit, not subject to the NSPS for
PM in 40 CFR 60.102 or 60.102a(b)(1).
5. Option 1b: Elect NSPS subpart Ja Any.................... Any.................... The applicable
requirements for PM per coke burn- operating limits in
off limit, not subject to the NSPS Item 2.b, 2.c, 2.d,
for PM in 40 CFR 60.102 or and 2.e of this table.
60.102a(b)(1).
6. Option 1c: Elect NSPS subpart Ja PM CEMS................ Any.................... Not applicable.
requirements for PM concentration
limit, not subject to the NSPS for
PM in 40 CFR 60.102 or 60.102a(b)(1).
7. Option 2: PM per coke burn-off a. Continuous opacity Cyclone, fabric filter, See Item 2.b of this
limit not subject to the NSPS for PM monitoring system used or electrostatic table. Alternatively,
in 40 CFR 60.102 or 60.102a(b)(1). to comply with a site- precipitator. before August 1, 2017,
specific opacity limit. you may maintain the
hourly average opacity
of emissions from your
catalyst generator
vent no higher than
the site-specific
opacity limit
established during the
performance test.
b. Continuous parameter i. Electrostatic (1) See Item 2.c.i of
monitoring systems. precipitator. this table.
(2) See item 2.c.ii of
this table.
Alternatively, before
August 1, 2017, you
may maintain the daily
average voltage and
secondary current
above the limit
established in the
performance test.
[[Page 75282]]
ii. Wet scrubber....... (1) See Item 2.d.i of
this table.
Alternatively, before
August 1, 2017, you
may maintain the daily
average liquid-to-gas
ratio above the limit
established in the
performance test.
(2) See Item 2.d.ii of
the table.
Alternatively, before
August 1, 2017, you
may maintain the daily
average pressure drop
above the limit
established in the
performance test (not
applicable to a wet
scrubber of the non-
venturi jet-ejector
design).
c. Bag leak detection Fabric filter.......... See item 2.e of this
(BLD) system. table.
8. Option 3: Ni lb/hr limit not a. Continuous opacity Cyclone, fabric filter, Maintain the 3-hour
subject to the NSPS for PM in 40 CFR monitoring system. or electrostatic rolling average Ni
60.102. precipitator. operating value no
higher than the limit
established during the
performance test.
Alternatively, before
August 1, 2017, you
may maintain the daily
average Ni operating
value no higher than
the limit established
during the performance
test.
b. Continuous parameter i. Electrostatic (1) See Item 2.c.i of
monitoring systems. precipitator. this table.
(2) Maintain the
monthly rolling
average of the
equilibrium catalyst
Ni concentration no
higher than the limit
established during the
performance test.
(3) See Item 2.c.ii of
this table.
Alternatively, before
August 1, 2017, you
may maintain the daily
average voltage and
secondary current (or
total power input)
above the established
during the performance
test.
ii. Wet scrubber....... (1) Maintain the
monthly rolling
average of the
equilibrium catalyst
Ni concentration no
higher than the limit
established during the
performance test.
(2) See Item 2.d.i of
this table.
Alternatively, before
August 1, 2017, you
may maintain the daily
average liquid-to-gas
ratio above the limit
established during the
performance test.
(3) See Item 2.d.ii of
this table.
Alternatively, before
August 1, 2017, you
may maintain the daily
average pressure drop
above the limit
established during the
performance test (not
applicable to a non-
venturi wet scrubber
of the jet-ejector
design).
c. Bag leak detection Fabric filter.......... See item 2.e of this
(BLD) system. table.
[[Page 75283]]
9. Option 4: Ni per coke burn-off a. Continuous opacity Cyclone, fabric filter, Maintain the 3-hour
limit not subject to the NSPS for PM monitoring system. or electrostatic rolling average Ni
in 40 CFR 60.102. precipitator. operating value no
higher than Ni
operating limit
established during the
performance test.
Alternatively, before
August 1, 2017, you
may elect to maintain
the daily average Ni
operating value no
higher than the Ni
operating limit
established during the
performance test.
b. Continuous parameter i. Electrostatic (1) Maintain the
monitoring systems. precipitator. monthly rolling
average of the
equilibrium catalyst
Ni concentration no
higher than the limit
established during the
performance test.
(2) See Item 2.c.ii of
this table.
Alternatively, before
August 1, 2017, you
may maintain the daily
average voltage and
secondary current (or
total power input)
above the limit
established during the
performance test.
ii. Wet scrubber....... (1) Maintain the
monthly rolling
average of the
equilibrium catalyst
Ni concentration no
higher than the limit
established during the
performance test.
(2) See Item 2.d.i of
this table.
Alternatively, before
August 1, 2017, you
may maintain the daily
average liquid-to-gas
ratio above the limit
established during the
performance test.
(3) See Item 2.d.ii of
this table.
Alternatively, before
August 1, 2017, you
may maintain the daily
average pressure drop
above the limit
established during the
performance test (not
applicable to a non-
venturi wet scrubber
of the jet-ejector
design).
c. Bag leak detection Fabric filter.......... See item 2.e of this
(BLD) system. table.
10. During periods of startup, Any.................... Any.................... Meet the requirements
shutdown, or hot standby. in Sec.
63.1564(a)(5).
----------------------------------------------------------------------------------------------------------------
\1\ If you use a jet ejector type wet scrubber or other type of wet scrubber equipped with atomizing spray
nozzles, you can use the alternative in Sec. 63.1573(b), and comply with the daily inspections,
recordkeeping, and repair provisions, instead of a continuous parameter monitoring system for pressure drop
across the scrubber.
0
54. Table 3 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1564(b)(1), you shall meet each requirement
in the following table that applies to you.
Table 3 to Subpart UUU of Part 63--Continuous Monitoring Systems for
Metal HAP Emissions From Catalytic Cracking Units
------------------------------------------------------------------------
If you use this
For each new or existing type of control You shall install,
catalytic cracking unit . . . device for your operate, and maintain
vent . . . a . . .
------------------------------------------------------------------------
1. Subject to the NSPS for PM Any.............. Continuous opacity
in 40 CFR 60.102 and not monitoring system to
electing Sec. 60.100(e). measure and record
the opacity of
emissions from each
catalyst regenerator
vent.
[[Page 75284]]
2. Subject to NSPS for PM in a. Cyclone....... Continuous opacity
40 CFR 60.102a(b)(1)(i); or b. Electrostatic monitoring system to
in Sec. 60.102 and electing precipitator. measure and record
Sec. 60.100(e); electing to the opacity of
meet the PM per coke burn-off emissions from each
limit. catalyst regenerator
vent.
Continuous opacity
monitoring system to
measure and record
the opacity of
emissions from each
catalyst regenerator
vent; or continuous
parameter monitoring
systems to measure
and record the coke
burn-off rate or the
gas flow rate
entering or exiting
the control
device,\1\ the
voltage, current,
and secondary
current to the
control device.
c. Wet scrubber.. Continuous parameter
monitoring system to
measure and record
the pressure drop
across the
scrubber,\2\ the
coke burn-off rate
or the gas flow rate
entering or exiting
the control
device,\3\ and total
liquid (or scrubbing
liquor) flow rate to
the control device.
d. Fabric Filter. Continuous bag leak
detection system to
measure and record
increases in
relative particulate
loading from each
catalyst regenerator
vent.
3. Subject to NSPS for PM in Any.............. Continuous emission
40 CFR 60.102a(b)(1)(i); or monitoring system to
in Sec. 60.102 and electing measure and record
Sec. 60.100(e); electing to the concentration of
meet the PM concentration PM and oxygen from
limit. each catalyst
regenerator vent.
4. Subject to NSPS for PM in Any.............. The applicable
40 CFR 60.102a(b)(1)(ii) continuous
electing to meet the PM per monitoring systems
coke burn-off limit. in item 2 of this
table.
5. Subject to NSPS for PM in Any.............. See item 3 of this
40 CFR 60.102a(b)(1)(ii) table.
electing to meet the PM
concentration limit.
6. Option 1a: Elect NSPS Any.............. See item 1 of this
subpart J, PM per coke burn- table.
off limit, not subject to the
NSPS for PM in 40 CFR 60.102
or 60.120a(b)(1).
7. Option 1b: Elect NSPS Any.............. The applicable
subpart Ja, PM per coke burn- continuous
off limit, not subject to the monitoring systems
NSPS for PM in 40 CFR 60.102 in item 2 of this
or 60.120a(b)(1). table.
8. Option 1c: Elect NSPS Any.............. See item 3 of this
subpart Ja, PM concentration table.
limit not subject to the NSPS
for PM in 40 CFR 60.102 or
60.120a(b)(1).
9. Option 2: PM per coke burn- Any.............. The applicable
off limit, not subject to the continuous
NSPS for PM in 40 CFR 60.102 monitoring systems
or 60.120a(b)(1). in item 2 of this
table.
10. Option 3: Ni lb/hr limit a. Cyclone....... Continuous opacity
not subject to the NSPS for monitoring system to
PM in 40 CFR 60.102 or measure and record
60.102a(b)(1). the opacity of
emissions from each
catalyst regenerator
vent and continuous
parameter monitoring
system to measure
and record the gas
flow rate entering
or exiting the
control device.\1\
b. Electrostatic Continuous opacity
precipitator. monitoring system to
measure and record
the opacity of
emissions from each
catalyst regenerator
vent and continuous
parameter monitoring
system to measure
and record the gas
flow rate entering
or exiting the
control device \1\;
or continuous
parameter monitoring
systems to measure
and record the coke
burn-off rate or the
gas flow rate
entering or exiting
the control device
\1\ and the voltage
and current (to
measure the total
power to the system)
and secondary
current to the
control device.
c. Wet scrubber.. Continuous parameter
monitoring system to
measure and record
the pressure drop
across the
scrubber,\2\ gas
flow rate entering
or exiting the
control device,\1\
and total liquid (or
scrubbing liquor)
flow rate to the
control device.
d. Fabric Filter. Continuous bag leak
detection system to
measure and record
increases in
relative particulate
loading from each
catalyst regenerator
vent or the
monitoring systems
specified in item
10.a of this table.
11. Option 4: Ni per coke burn- a. Cyclone....... Continuous opacity
off limit not subject to the monitoring system to
NSPS for PM in 40 CFR 60.102 measure and record
or 60.102a(b)(1). the opacity of
emissions from each
catalyst regenerator
vent and continuous
parameter monitoring
system to measure
and record the coke
burn-off rate and
the gas flow rate
entering or exiting
the control
device.\1\
[[Page 75285]]
b. Electrostatic Continuous opacity
precipitator. monitoring system to
measure and record
the opacity of
emissions from each
catalyst regenerator
vent and continuous
parameter monitoring
system to measure
and record the coke
burn-off rate and
the gas flow rate
entering or exiting
the control device
\1\; or continuous
parameter monitoring
systems to measure
and record the coke
burn-off rate or the
gas flow rate
entering or exiting
the control device
\1\ and voltage and
current (to measure
the total power to
the system) and
secondary current to
the control device.
c. Wet scrubber.. Continuous parameter
monitoring system to
measure and record
the pressure drop
across the
scrubber,\2\ gas
flow rate entering
or exiting the
control device,\1\
and total liquid (or
scrubbing liquor)
flow rate to the
control device.
d. Fabric Filter. Continuous bag leak
detection system to
measure and record
increases in
relative particulate
loading from each
catalyst regenerator
vent or the
monitoring systems
specified in item
11.a of this table.
12. Electing to comply with Any.............. Continuous parameter
the operating limits in Sec. monitoring system to
63.1566(a)(5)(iii) during measure and record
periods of startup, shutdown, the gas flow rate
or hot standby. exiting the catalyst
regenerator.\1\
------------------------------------------------------------------------
\1\ If applicable, you can use the alternative in Sec. 63.1573(a)(1)
instead of a continuous parameter monitoring system for gas flow rate.
\2\ If you use a jet ejector type wet scrubber or other type of wet
scrubber equipped with atomizing spray nozzles, you can use the
alternative in Sec. 63.1573(b) instead of a continuous parameter
monitoring system for pressure drop across the scrubber.
0
55. Table 4 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. Sec. 63.1564(b)(2) and 63.1571(a)(5), you shall
meet each requirement in the following table that applies to you.
Table 4 to Subpart UUU of Part 63--Requirements for Performance Tests for Metal HAP Emissions From Catalytic
Cracking Units
----------------------------------------------------------------------------------------------------------------
For each new or existing catalytic
cracking unit catalyst regenerator You must . . . Using . . . According to these
vent . . . requirements . . .
----------------------------------------------------------------------------------------------------------------
1. Any............................... a. Select sampling Method 1 or 1A in Sampling sites must be
port's location and appendix A-1 to part located at the outlet
the number of traverse 60 of this chapter. of the control device
ports. or the outlet of the
regenerator, as
applicable, and prior
to any releases to the
atmosphere.
b. Determine velocity Method 2, 2A, 2C, 2D, .......................
and volumetric flow or 2F in appendix A-1
rate. to part 60 of this
chapter, or Method 2G
in appendix A-2 to
part 60 of this
chapter, as applicable.
c. Conduct gas Method 3, 3A, or 3B in .......................
molecular weight appendix A-2 to part
analysis. 60 of this chapter, as
applicable.
d. Measure moisture Method 4 in appendix A- .......................
content of the stack 3 to part 60 of this
gas. chapter.
e. If you use an .......................
electrostatic
precipitator, record
the total number of
fields in the control
system and how many
operated during the
applicable performance
test.
f. If you use a wet .......................
scrubber, record the
total amount (rate) of
water (or scrubbing
liquid) and the amount
(rate) of make-up
liquid to the scrubber
during each test run.
[[Page 75286]]
2. Subject to the NSPS for PM in 40 a. Measure PM emissions Method 5, 5B, or 5F (40 You must maintain a
CFR 60.102 and not elect Sec. CFR part 60, appendix sampling rate of at
60.100(e). A-3) to determine PM least 0.15 dry
emissions and standard cubic meters
associated moisture per minute (dscm/min)
content for units (0.53 dry standard
without wet scrubbers. cubic feet per minute
Method 5 or 5B (40 CFR (dscf/min)).
part 60, appendix A-3)
to determine PM
emissions and
associated moisture
content for unit with
wet scrubber.
b. Compute coke burn- Equations 1, 2, and 3 .......................
off rate and PM of Sec. 63.1564 (if
emission rate (lb/ applicable).
1,000 lb of coke burn-
off).
c. Measure opacity of Continuous opacity You must collect
emissions. monitoring system. opacity monitoring
data every 10 seconds
during the entire
period of the Method
5, 5B, or 5F
performance test and
reduce the data to 6-
minute averages.
3. Subject to the NSPS for PM in 40 a. Measure PM emissions Method 5, 5B, or 5F (40 You must maintain a
CFR 60.102a(b)(1) or elect Sec. CFR part 60, appendix sampling rate of at
60.100(e), electing the PM for coke A-3) to determine PM least 0.15 dscm/min
burn-off limit. emissions and (0.53 dscf/min).
associated moisture
content for units
without wet scrubbers.
Method 5 or 5B (40 CFR
part 60, appendix A-3)
to determine PM
emissions and
associated moisture
content for unit with
wet scrubber.
b. Compute coke burn- Equations 1, 2, and 3 .......................
off rate and PM of Sec. 63.1564 (if
emission rate (lb/ applicable).
1,000 lb of coke burn-
off).
c. Establish site- Continuous opacity If you elect to comply
specific limit if you monitoring system. with the site-specific
use a COMS. opacity limit in Sec.
63.1564(b)(4)(i), you
must collect opacity
monitoring data every
10 seconds during the
entire period of the
Method 5, 5B, or 5F
performance test. For
site specific opacity
monitoring, reduce the
data to 6-minute
averages; determine
and record the average
opacity for each test
run; and compute the
site-specific opacity
limit using Equation 4
of Sec. 63.1564.
4. Subject to the NSPS for PM in 40 a. Measure PM emissions Method 5, 5B, or 5F (40 You must maintain a
CFR 60.102a(b)(1) or elect Sec. CFR part 60, appendix sampling rate of at
60.100(e). A-3) to determine PM least 0.15 dscm/min
emissions and (0.53 dscf/min).
associated moisture
content for units
without wet scrubbers.
Method 5 or 5B (40 CFR
part 60, appendix A-3)
to determine PM
emissions and
associated moisture
content for unit with
wet scrubber.
5. Option 1a: Elect NSPS subpart J See item 2 of this ....................... .......................
requirements for PM per coke burn- table.
off limit, not subject to the NSPS
for PM in 40 CFR 60.102 or
60.102a(b)(1).
6. Option 1b: Elect NSPS subpart Ja See item 3 of this
requirements for PM per coke burn- table.
off limit, not subject to the NSPS
for PM in 40 CFR 60.102 or
60.102a(b)(1).
[[Page 75287]]
7. Option 1c: Elect NSPS requirements See item 4 of this
for PM concentration, not subject to table.
the NSPS for PM in 40 CFR 60.102 or
60.102a(b)(1).
8. Option 2: PM per coke burn-off See item 3 of this
limit, not subject to the NSPS for table.
PM in 40 CFR 60.102 or 60.102a(b)(1).
9. Option 3: Ni lb/hr limit, not a. Measure Method 29 (40 CFR part
subject to the NSPS for PM in 40 CFR concentration of Ni. 60, appendix A-8).
60.102 or 60.102a(b)(1). ....................... Equation 5 of Sec.
b. Compute Ni emission 63.1564.
rate (lb/hr).
c. Determine the XRF procedure in You must obtain 1
equilibrium catalyst appendix A to this sample for each of the
Ni concentration. subpart1; or EPA 3 test runs; determine
Method 6010B or 6020 and record the
or EPA Method 7520 or equilibrium catalyst
7521 in SW-8462; or an Ni concentration for
alternative to the SW- each of the 3 samples;
846 method and you may adjust the
satisfactory to the laboratory results to
Administrator. the maximum value
using Equation 2 of
Sec. 63.1571.
d. If you use a i. Equations 6 and 7 of (1) You must collect
continuous opacity Sec. 63.1564 using opacity monitoring
monitoring system, data from continuous data every 10 seconds
establish your site- opacity monitoring during the entire
specific Ni operating system, gas flow rate, period of the initial
limit. results of equilibrium Ni performance test;
catalyst Ni reduce the data to 6-
concentration minute averages; and
analysis, and Ni determine and record
emission rate from the average opacity
Method 29 test. from all the 6-minute
averages for each test
run.
(2) You must collect
gas flow rate
monitoring data every
15 minutes during the
entire period of the
initial Ni performance
test; measure the gas
flow as near as
practical to the
continuous opacity
monitoring system; and
determine and record
the hourly average
actual gas flow rate
for each test run.
10. Option 4: Ni per coke burn-off a. Measure Method 29 (40 CFR part
limit, not subject to the NSPS for concentration of Ni. 60, appendix A-8).
PM in 40 CFR 60.102 or 60.102a(b)(1). ....................... Equations 1 and 8 of
b. Compute Ni emission Sec. 63.1564.
rate (lb/1,000 lb of
coke burn-off).
c. Determine the See item 6.c. of this You must obtain 1
equilibrium catalyst table. sample for each of the
Ni concentration. 3 test runs; determine
and record the
equilibrium catalyst
Ni concentration for
each of the 3 samples;
and you may adjust the
laboratory results to
the maximum value
using Equation 2 of
Sec. 63.1571.
d. If you use a i. Equations 9 and 10 (1) You must collect
continuous opacity of Sec. 63.1564 with opacity monitoring
monitoring system, data from continuous data every 10 seconds
establish your site- opacity monitoring during the entire
specific Ni operating system, coke burn-off period of the initial
limit. rate, results of Ni performance test;
equilibrium catalyst reduce the data to 6-
Ni concentration minute averages; and
analysis, and Ni determine and record
emission rate from the average opacity
Method 29 test. from all the 6-minute
averages for each test
run.
[[Page 75288]]
(2) You must collect
gas flow rate
monitoring data every
15 minutes during the
entire period of the
initial Ni performance
test; measure the gas
flow rate as near as
practical to the
continuous opacity
monitoring system; and
determine and record
the hourly average
actual gas flow rate
for each test run.
e. Record the catalyst .......................
addition rate for each
test and schedule for
the 10-day period
prior to the test.
11. If you elect item 5 Option 1b in a. Establish each Data from the .......................
Table 1, item 7 Option 2 in Table 1, operating limit in continuous parameter
item 8 Option 3 in Table 1, or item Table 2 of this monitoring systems and
9 Option 4 in Table 1 of this subpart that applies applicable performance
subpart and you use continuous to you. test methods.
parameter monitoring systems.
b. Electrostatic i. Data from the (1) You must collect
precipitator or wet continuous parameter gas flow rate
scrubber: Gas flow monitoring systems and monitoring data every
rate. applicable performance 15 minutes during the
test methods. entire period of the
initial performance
test; determine and
record the average gas
flow rate for each
test run.
(2) You must determine
and record the 3-hr
average gas flow rate
from the test runs.
Alternatively, before
August 1, 2017, you
may determine and
record the maximum
hourly average gas
flow rate from all the
readings.
c. Electrostatic i. Data from the (1) You must collect
precipitator: Total continuous parameter voltage, current, and
power (voltage and monitoring systems and secondary current
current) and secondary applicable performance monitoring data every
current. test methods. 15 minutes during the
entire period of the
performance test; and
determine and record
the average voltage,
current, and secondary
current for each test
run. Alternatively,
before August 1, 2017,
you may collect
voltage and secondary
current (or total
power input)
monitoring data every
15 minutes during the
entire period of the
initial performance
test.
(2) You must determine
and record the 3-hr
average total power to
the system for the
test runs and the 3-hr
average secondary
current from the test
runs. Alternatively,
before August 1, 2017,
you may determine and
record the minimum
hourly average voltage
and secondary current
(or total power input)
from all the readings.
[[Page 75289]]
d. Electrostatic Results of analysis for You must determine and
precipitator or wet equilibrium catalyst record the average
scrubber: Equilibrium Ni concentration. equilibrium catalyst
catalyst Ni Ni concentration for
concentration. the 3 runs based on
the laboratory
results. You may
adjust the value using
Equation 1 or 2 of
Sec. 63.1571 as
applicable.
e. Wet scrubber: i. Data from the (1) You must collect
Pressure drop (not continuous parameter pressure drop
applicable to non- monitoring systems and monitoring data every
venturi scrubber of applicable performance 15 minutes during the
jet ejector design). test methods. entire period of the
initial performance
test; and determine
and record the average
pressure drop for each
test run.
(2) You must determine
and record the 3-hr
average pressure drop
from the test runs.
Alternatively, before
August 1, 2017, you
may determine and
record the minimum
hourly average
pressure drop from all
the readings.
f. Wet scrubber: Liquid- i. Data from the (1) You must collect
to-gas ratio. continuous parameter gas flow rate and
monitoring systems and total water (or
applicable performance scrubbing liquid) flow
test methods. rate monitoring data
every 15 minutes
during the entire
period of the initial
performance test;
determine and record
the average gas flow
rate for each test
run; and determine the
average total water
(or scrubbing liquid)
flow for each test
run.
(2) You must determine
and record the hourly
average liquid-to-gas
ratio from the test
runs. Alternatively,
before August 1, 2017,
you may determine and
record the hourly
average gas flow rate
and total water (or
scrubbing liquid) flow
rate from all the
readings.
(3) You must determine
and record the 3-hr
average liquid-to-gas
ratio. Alternatively,
before August 1, 2017,
you may determine and
record the minimum
liquid-to-gas ratio.
g. Alternative i. Data from the (1) You must collect
procedure for gas flow continuous parameter air flow rate
rate. monitoring systems and monitoring data or
applicable performance determine the air flow
test methods. rate using control
room instrumentation
every 15 minutes
during the entire
period of the initial
performance test.
(2) You must determine
and record the 3-hr
average rate of all
the readings from the
test runs.
Alternatively, before
August 1, 2017, you
may determine and
record the hourly
average rate of all
the readings.
(3) You must determine
and record the maximum
gas flow rate using
Equation 1 of Sec.
63.1573.
----------------------------------------------------------------------------------------------------------------
\1\ Determination of Metal Concentration on Catalyst Particles (Instrumental Analyzer Procedure).
[[Page 75290]]
\2\ EPA Method 6010B, Inductively Coupled Plasma-Atomic Emission Spectrometry, EPA Method 6020, Inductively
Coupled Plasma-Mass Spectrometry, EPA Method 7520, Nickel Atomic Absorption, Direct Aspiration, and EPA Method
7521, Nickel Atomic Absorption, Direct Aspiration are included in ``Test Methods for Evaluating Solid Waste,
Physical/Chemical Methods,'' EPA Publication SW-846, Revision 5 (April 1998). The SW-846 and Updates (document
number 955-001-00000-1) are available for purchase from the Superintendent of Documents, U.S. Government
Publishing Office, Washington, DC 20402, (202) 512-1800; and from the National Technical Information Services
(NTIS), 5285 Port Royal Road, Springfield, VA 22161, (703) 487-4650. Copies may be inspected at the EPA Docket
Center, William Jefferson Clinton (WJC) West Building, (Air Docket), Room 3334, 1301 Constitution Ave. NW.,
Washington, DC; or at the Office of the Federal Register, 800 North Capitol Street NW., Suite 700, Washington,
DC.
0
56. Table 5 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1564(b)(5), you shall meet each requirement
in the following table that applies to you.
Table 5 to Subpart UUU of Part 63--Initial Compliance With Metal HAP
Emission Limits for Catalytic Cracking Units
------------------------------------------------------------------------
For each new and existing For the following
catalytic cracking unit emission limit . You have demonstrated
catalyst regenerator vent . . . . initial compliance if
. . . .
------------------------------------------------------------------------
1. Subject to the NSPS for PM PM emissions must You have already
in 40 CFR 60.102 and not not exceed 1.0 g/ conducted a
electing Sec. 60.100(e). kg (1.0 lb/1,000 performance test to
lb) of coke burn- demonstrate initial
off, and the compliance with the
opacity of NSPS and the
emissions must measured PM emission
not exceed 30 rate is less than or
percent, except equal to 1.0 g/kg
for one 6-minute (1.0 lb/1,000 lb) of
average opacity coke burn-off in the
reading in any 1- catalyst
hour period. regenerator. As part
Before August 1, of the Notification
2017, if the of Compliance
discharged gases Status, you must
pass through an certify that your
incinerator or vent meets the PM
waste heat limit. You are not
boiler in which required to do
you burn another performance
auxiliary or test to demonstrate
supplemental initial compliance.
liquid or solid You have already
fossil fuel, the conducted a
incremental rate performance test to
of PM must not demonstrate initial
exceed 43.0 g/GJ compliance with the
or 0.10 lb/ NSPS and the average
million Btu of hourly opacity is no
heat input more than 30
attributable to percent, except that
the liquid or one 6-minute average
solid fossil in any 1-hour period
fuel; and the can exceed 30
opacity of percent. As part of
emissions must the Notification of
not exceed 30 Compliance Status,
percent, except you must certify
for one 6-minute that your vent meets
average opacity the 30 percent
reading in any 1- opacity limit. As
hour period. part of your
Notification of
Compliance Status,
you certify that
your continuous
opacity monitoring
system meets the
requirements in Sec.
63.1572.
2. Subject to NSPS for PM in PM emissions must You have already
40 CFR 60.102a(b)(1)(i); or not exceed 1.0 g/ conducted a
in Sec. 60.102 and electing kg (1.0 lb PM/ performance test to
Sec. 60.100(e); electing to 1,000 lb) of demonstrate initial
meet the PM per coke burn-off coke burn-off. compliance with the
limit. NSPS and the
measured PM emission
rate is less than or
equal to 1.0 g/kg
(1.0 lb/1,000 lb) of
coke burn-off in the
catalyst
regenerator. As part
of the Notification
of Compliance
Status, you must
certify that your
vent meets the PM
limit. You are not
required to do
another performance
test to demonstrate
initial compliance.
As part of your
Notification of
Compliance Status,
you certify that
your BLD; CO2, O2,
or CO monitor; or
continuous opacity
monitoring system
meets the
requirements in Sec.
63.1572.
3. Subject to NSPS for PM in PM emissions must You have already
40 CFR 60.102a(b)(1)(i), not exceed 0.5 g/ conducted a
electing to meet the PM per kg (0.5 lb PM/ performance test to
coke burn-off limit. 1,000 lb) of demonstrate initial
coke burn-off). compliance with the
NSPS and the
measured PM emission
rate is less than or
equal to 1.0 g/kg
(1.0 lb/1,000 lb) of
coke burn-off in the
catalyst
regenerator. As part
of the Notification
of Compliance
Status, you must
certify that your
vent meets the PM
limit. You are not
required to do
another performance
test to demonstrate
initial compliance.
As part of your
Notification of
Compliance Status,
you certify that
your BLD; CO2, O2,
or CO monitor; or
continuous opacity
monitoring system
meets the
requirements in Sec.
63.1572.
4. Subject to NSPS for PM in If a PM CEMS is You have already
40 CFR 60.102a(b)(1)(i), used, 0.040 conducted a
electing to meet the PM grain per dry performance test to
concentration limit. standard cubic demonstrate initial
feet (gr/dscf) compliance with the
corrected to 0 NSPS and the
percent excess measured PM
air. concentration is
less than or equal
to 0.040 grain per
dry standard cubic
feet (gr/dscf)
corrected to 0
percent excess air.
As part of the
Notification of
Compliance Status,
you must certify
that your vent meets
the PM limit. You
are not required to
do another
performance test to
demonstrate initial
compliance. As part
of your Notification
of Compliance
Status, you certify
that your PM CEMS
meets the
requirements in Sec.
63.1572.
[[Page 75291]]
5. Subject to NSPS for PM in If a PM CEMS is You have already
40 CFR 60.102a(b)(1)(ii), used, 0.020 gr/ conducted a
electing to meet the PM dscf corrected performance test to
concentration limit. to 0 percent demonstrate initial
excess air. compliance with the
NSPS and the
measured PM
concentration is
less than or equal
to 0.020 gr/dscf
corrected to 0
percent excess air.
As part of the
Notification of
Compliance Status,
you must certify
that your vent meets
the PM limit. You
are not required to
do another
performance test to
demonstrate initial
compliance. As part
of your Notification
of Compliance
Status, you certify
that your PM CEMS
meets the
requirements in Sec.
63.1572.
6. Option 1a: Elect NSPS PM emissions must The average PM
subpart J requirements for PM not exceed 1.0 emission rate,
per coke burn-off limit, not gram per measured using EPA
subject to the NSPS for PM in kilogram (g/kg) Method 5, 5B, or 5F
40 CFR 60.102 or (1.0 lb/1,000 (for a unit without
60.102a(b)(1). lb) of coke burn- a wet scrubber) or 5
off, and the or 5B (for a unit
opacity of with a wet scrubber)
emissions must (40 CFR part 60,
not exceed 30 appendix A-3), over
percent, except the period of the
for one 6-minute initial performance
average opacity test, is no higher
reading in any 1- than 1.0 g/kg coke
hour period. burn-off (1.0 lb/
Before August 1, 1,000 lb) in the
2017, PM catalyst
emission must regenerator. The PM
not exceed 1.0 g/ emission rate is
kg (1.0 lb/1,000 calculated using
lb) of coke burn- Equations 1, 2, and
off in the 3 of Sec. 63.1564.
catalyst As part of the
regenerator; if Notification of
the discharged Compliance Status,
gases pass you must certify
through an that your vent meets
incinerator or the PM limit. The
waste heat average hourly
boiler in which opacity is no more
you burn than 30 percent,
auxiliary or except that one 6-
supplemental minute average in
liquid or solid any 1-hour period
fossil fuel, the can exceed 30
incremental rate percent. As part of
of PM must not the Notification of
exceed 43.0 g/GJ Compliance Status,
(0.10 lb/million you must certify
Btu) of heat that your vent meets
input the 30 percent
attributable to opacity limit. If
the liquid or you use a continuous
solid fossil opacity monitoring
fuel; and the system, your
opacity of performance
emissions must evaluation shows the
not exceed 30 system meets the
percent, except applicable
for one 6-minute requirements in Sec.
average opacity 63.1572.
reading in any 1-
hour period.
7. Option 1b: Elect NSPS PM emissions must The average PM
subpart Ja requirements for not exceed 1.0 g/ emission rate,
PM per coke burn-off limit, kg (1.0 lb/1,000 measured using EPA
not subject to the NSPS for lb) of coke burn- Method 5, 5B, or 5F
PM in 40 CFR 60.102 or off. (for a unit without
60.102a(b)(1). a wet scrubber) or 5
or 5B (for a unit
with a wet scrubber)
(40 CFR part 60,
appendix A-3), over
the period of the
initial performance
test, is no higher
than 1.0 g/kg coke
burn-off (1.0 lb/
1,000 lb) in the
catalyst
regenerator. The PM
emission rate is
calculated using
Equations 1, 2, and
3 of Sec. 63.1564.
If you use a BLD;
CO2, O2, CO monitor;
or continuous
opacity monitoring
system, your
performance
evaluation shows the
system meets the
applicable
requirements in Sec.
63.1572.
8. Option 1c: Elect NSPS PM emissions must The average PM
subpart Ja requirements for not exceed 0.040 concentration,
PM concentration limit, not gr/dscf measured using EPA
subject to the NSPS for PM in corrected to 0 Method 5, 5B, or 5F
40 CFR 60.102 or percent excess (for a unit without
60.102a(b)(1). air. a wet scrubber) or
Method 5 or 5B (for
a unit with a wet
scrubber) (40 CFR
part 60, appendix A-
3), over the period
of the initial
performance test, is
less than or equal
to 0.040 gr/dscf
corrected to 0
percent excess air.
Your performance
evaluation shows
your PM CEMS meets
the applicable
requirements in Sec.
63.1572.
9. Option 2: PM per coke burn- PM emissions must The average PM
off limit, not subject to the not exceed 1.0 g/ emission rate,
NSPS for PM in 40 CFR 60.102 kg (1.0 lb/1,000 measured using EPA
or 60.102a(b)(1). lb) of coke burn- Method 5, 5B, or 5F
off. (for a unit without
a wet scrubber) or 5
or 5B (for a unit
with a wet scrubber)
(40 CFR part 60,
appendix A-3), over
the period of the
initial performance
test, is no higher
than 1.0 g/kg coke
burn-off (1.0 lb/
1,000 lb) in the
catalyst
regenerator. The PM
emission rate is
calculated using
Equations 1, 2, and
3 of Sec. 63.1564.
If you use a BLD;
CO2, O2, CO monitor;
or continuous
opacity monitoring
system, your
performance
evaluation shows the
system meets the
applicable
requirements in Sec.
63.1572.
10. Option 3: Ni lb/hr limit, Nickel (Ni) The average Ni
not subject to the NSPS for emissions from emission rate,
PM in 40 CFR 60.102 or your catalyst measured using
60.102a(b)(1). regenerator vent Method 29 (40 CFR
must not exceed part 60, appendix A-
13,000 mg/hr 8) over the period
(0.029 lb/hr). of the initial
performance test, is
not more than 13,000
mg/hr (0.029 lb/hr).
The Ni emission rate
is calculated using
Equation 5 of Sec.
63.1564; and if you
use a BLD; CO2, O2,
or CO monitor; or
continuous opacity
monitoring system,
your performance
evaluation shows the
system meets the
applicable
requirements in Sec.
63.1572.
[[Page 75292]]
11. Option 4: Ni per coke burn- Ni emissions from The average Ni
off limit not subject to the your catalyst emission rate,
NSPS for PM. regenerator vent measured using
must not exceed Method 29 (40 CFR
1.0 mg/kg (0.001 part 60, appendix A-
lb/1,000 lb) of 8) over the period
coke burn-off in of the initial
the catalyst performance test, is
regenerator. not more than 1.0 mg/
kg (0.001 lb/1,000
lb) of coke burn-off
in the catalyst
regenerator. The Ni
emission rate is
calculated using
Equation 8 of Sec.
63.1564; and if you
use a BLD; CO2, O2,
or CO monitor; or
continuous opacity
monitoring system,
your performance
evaluation shows the
system meets the
applicable
requirements in Sec.
63.1572.
------------------------------------------------------------------------
0
57. Table 6 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1564(c)(1), you shall meet each requirement
in the following table that applies to you.
Table 6 to Subpart UUU of Part 63--Continuous Compliance With Metal HAP
Emission Limits for Catalytic Cracking Units
------------------------------------------------------------------------
Subject to this
emission limit You shall demonstrate
For each new and existing for your catalyst continuous compliance
catalytic cracking unit . . . regenerator vent by . . .
. . .
------------------------------------------------------------------------
1. Subject to the NSPS for PM a. PM emissions i. Determining and
in 40 CFR 60.102 and not must not exceed recording each day
electing Sec. 60.100(e). 1.0 g/kg (1.0 lb/ the average coke
1,000 lb) of burn-off rate
coke burn-off, (thousands of
and the opacity kilograms per hour)
of emissions using Equation 1 in
must not exceed Sec. 63.1564 and
30 percent, the hours of
except for one 6- operation for each
minute average catalyst
opacity reading regenerator.
in any 1-hour
period. Before
August 1, 2017,
if the
discharged gases
pass through an
incinerator or
waste heat
boiler in which
you burn
auxiliary or
supplemental
liquid or solid
fossil fuel, the
incremental rate
of PM must not
exceed 43.0 g/GJ
(0.10 lb/million
Btu) of heat
input
attributable to
the liquid or
solid fossil
fuel; and the
opacity of
emissions must
not exceed 30
percent, except
for one 6-minute
average opacity
reading in any 1-
hour period.
ii. Conducting a
performance test
before August 1,
2017 and thereafter
following the
testing frequency in
Sec. 63.1571(a)(5)
as applicable to
your unit.
iii. Collecting the
continuous opacity
monitoring data for
each catalyst
regenerator vent
according to Sec.
63.1572 and
maintaining each 6-
minute average at or
below 30 percent,
except that one 6-
minute average
during a 1-hour
period can exceed 30
percent.
iv. Before August 1,
2017, if applicable,
determining and
recording each day
the rate of
combustion of liquid
or solid fossil
fuels (liters/hour
or kilograms/hour)
and the hours of
operation during
which liquid or
solid fossil-fuels
are combusted in the
incinerator-waste
heat boiler; if
applicable,
maintaining the
incremental rate of
PM at or below 43 g/
GJ (0.10 lb/million
Btu) of heat input
attributable to the
solid or liquid
fossil fuel.
2. Subject to NSPS for PM in PM emissions must Determining and
40 CFR 60.102a(b)(1)(i), not exceed 1.0 g/ recording each day
electing to meet the PM per kg (1.0 lb PM/ the average coke
coke burn-off limit. 1,000 lb) of burn-off rate
coke burn-off. (thousands of
kilograms per hour)
using Equation 1 in
Sec. 63.1564 and
the hours of
operation for each
catalyst
regenerator;
maintaining PM
emission rate below
1.0 g/kg (1.0 lb PM/
1,000 lb) of coke
burn-off; and
conducting a
performance test
once every year.
3. Subject to NSPS for PM in PM emissions must Determining and
40 CFR 60.102a(b)(1)(ii), not exceed 0.5 g/ recording each day
electing to meet the PM per kg coke burn-off the average coke
coke burn-off limit. (0.5 lb/1000 lb burn-off rate
coke burn-off). (thousands of
kilograms per hour)
using Equation 1 in
Sec. 63.1564 and
the hours of
operation for each
catalyst
regenerator;
maintaining PM
emission rate below
0.5 g/kg (0.5 lb/
1,000 lb) of coke
burn-off; and
conducting a
performance test
once every year.
[[Page 75293]]
4. Subject to NSPS for PM in If a PM CEMS is Maintaining PM
40 CFR 60.102a(b)(1)(i), used, 0.040 concentration below
electing to meet the PM grain per dry 0.040 gr/dscf
concentration limit. standard cubic corrected to 0
feet (gr/dscf) percent excess air.
corrected to 0
percent excess
air.
5. Subject to NSPS for PM in If a PM CEMS is Maintaining PM
40 CFR 60.102a(b)(1)(ii), used, 0.020 gr/ concentration below
electing to meet the PM dscf corrected 0.020 gr/dscf
concentration limit. to 0 percent corrected to 0
excess air. percent excess air.
6. Option 1a: Elect NSPS See item 1 of See item 1 of this
subpart J requirements for PM this table. table.
per coke burn-off limit, not
subject to the NSPS for PM in
40 CFR 60.102 or
60.102a(b)(1).
7. Option 1b: Elect NSPS PM emissions must See item 2 of this
subpart Ja requirements for not exceed 1.0 g/ table.
PM per coke burn-off limit kg (1.0 lb PM/
and 30% opacity, not subject 1,000 lb) of
to the NSPS for PM in 40 CFR coke burn-off.
60.102 or 60.102a(b)(1).
8. Option 1c: Elect NSPS PM emissions must See item 4 of this
subpart Ja requirements for not exceed 0.040 table.
PM concentration limit, not gr/dscf
subject to the NSPS for PM in corrected to 0
40 CFR 60.102 or percent excess
60.102a(b)(1). air.
9. Option 2: PM per coke burn- PM emissions must Determining and
off limit, not subject to the not exceed 1.0 g/ recording each day
NSPS for PM in 40 CFR 60.102 kg (1.0 lb PM/ the average coke
or 60.102a(b)(1). 1,000 lb) of burn-off rate and
coke burn-off. the hours of
operation and the
hours of operation
for each catalyst
regenerator by
Equation 1 of Sec.
63.1564 (you can use
process data to
determine the
volumetric flow
rate); maintaining
PM emission rate
below 1.0 g/kg (1.0
lb PM/1,000 lb) of
coke burn-off; and
conducting a
performance test
before August 1,
2017 and thereafter
following the
testing frequency in
Sec. 63.1571(a)(5)
as applicable to
your unit.
10. Option 3: Ni lb/hr limit, Ni emissions must Maintaining Ni
not subject to the NSPS for not exceed emission rate below
PM in 40 CFR 60.102 or 13,000 mg/hr 13,000 mg/hr (0.029
60.102a(b)(1). (0.029 lb/hr). lb/hr); and
conducting a
performance test
before August 1,
2017 and thereafter
following the
testing frequency in
Sec. 63.1571(a)(5)
as applicable to
your unit.
11. Option 4: Ni per coke burn- Ni emissions must Determining and
off limit, not subject to the not exceed 1.0 recording each day
NSPS for PM in 40 CFR 60.102 mg/kg (0.001 lb/ the average coke
or 60.102a(b)(1). 1,000 lb) of burn-off rate
coke burn-off in (thousands of
the catalyst kilograms per hour)
regenerator. and the hours of
operation for each
catalyst regenerator
by Equation 1 of
Sec. 63.1564 (you
can use process data
to determine the
volumetric flow
rate); and
maintaining Ni
emission rate below
1.0 mg/kg (0.001 lb/
1,000 lb) of coke
burn-off in the
catalyst
regenerator; and
conducting a
performance test
before August 1,
2017 and thereafter
following the
testing frequency in
Sec. 63.1571(a)(5)
as applicable to
your unit.
------------------------------------------------------------------------
0
58. Table 7 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1564(c)(1), you shall meet each requirement
in the following table that applies to you.
Table 7 to Subpart UUU of Part 63--Continuous Compliance With Operating Limits for Metal HAP Emissions From
Catalytic Cracking Units
----------------------------------------------------------------------------------------------------------------
You shall demonstrate
For each new or existing catalytic If you use . . . For this operating continuous compliance
cracking unit . . . limit . . . by . . .
----------------------------------------------------------------------------------------------------------------
1. Subject to NSPS for PM in 40 CFR Continuous opacity The 3-hour average Collecting the
60.102 and not electing Sec. monitoring system. opacity of emissions continuous opacity
60.100(e). from your catalyst monitoring data for
regenerator vent must each regenerator vent
not exceed 20 percent. according to Sec.
63.1572 and maintain
each 3-hour rolling
average opacity of
emissions no higher
than 20 percent.
[[Page 75294]]
2. Subject to NSPS for PM in 40 CFR a. Continuous opacity The average opacity Collecting the hourly
60.102a(b)(1); or 40 CFR 60.102 and monitoring system, must not exceed the and 3-hr rolling
elect Sec. 60.100(e), electing to used for site-specific opacity established average opacity
meet the PM per coke burn-off limit. opacity limit--Cyclone during the performance monitoring data
or electrostatic test. according to Sec.
precipitator. 63.1572; maintaining
the 3-hr rolling
average opacity at or
above the site-
specific limit
established during the
performance test.
b. Continuous i. The average gas flow Collecting the hourly
parametric monitoring rate entering or and daily average coke
systems--electrostatic exiting the control burn-off rate or
precipitator. device must not exceed average gas flow rate
the operating limit monitoring data
established during the according to Sec.
performance test. 63.1572; and
maintaining the daily
average coke burn-off
rate or average gas
flow rate at or below
the limit established
during the performance
test.
ii. The average total Collecting the hourly
power and secondary and 3-hr rolling
current to the control average total power
device must not fall and secondary current
below the operating monitoring data
limit established according to Sec.
during the performance 63.1572; and
test. maintaining the 3-hr
rolling average total
power and secondary
current at or above
the limit established
during the performance
test.
c. Continuous i. The average liquid- Collecting the hourly
parametric monitoring to-gas ratio must not and 3-hr rolling
systems--wet scrubber. fall below the average gas flow rate
operating limit and scrubber liquid
established during the flow rate monitoring
performance test. data according to Sec.
63.1572; determining
and recording the 3-hr
liquid-to-gas ratio;
and maintaining the 3-
hr rolling average
liquid-to-gas ratio at
or above the limit
established during the
performance test.
ii. Except for periods Collecting the hourly
of startup, shutdown and 3-hr rolling
and hot standby, the average pressure drop
average pressure drop monitoring data
across the scrubber according to Sec.
must not fall below 63.1572; and except
the operating limit for periods of
established during the startup, shutdown and
performance test. hot standby,
maintaining the 3-hr
rolling average
pressure drop at or
above the limit
established during the
performance test.
d. BLD--fabric filter.. Increases in relative Collecting and
particulate. maintaining records of
BLD system output;
determining the cause
of the alarm within 1
hour of the alarm; and
alleviating the cause
of the alarm within 3
hours by corrective
action.
3. Subject to NSPS for PM in 40 CFR PM CEMS................ Not applicable......... Complying with Table 6
60.102a(b)(1), electing to meet the of this subpart, item
PM concentration limit. 4 or 5.
4. Option 1a: Elect NSPS subpart J Continuous opacity The 3-hour average Collecting the 3-hr
requirements for PM per coke burn- monitoring system. opacity of emissions rolling average
off limit, not subject to the NSPS from your catalyst continuous opacity
for PM in 40 CFR 60.102 or regenerator vent must monitoring system data
60.102a(b)(1). not exceed 20 percent. according to Sec.
63.1572; and
maintaining the 3-hr
rolling average
opacity no higher than
20 percent.
5. Option 1b: Elect NSPS subpart Ja a. Continuous opacity The opacity of Collecting the 3-hr
requirements for PM per coke burn- monitoring system. emissions from your rolling average
off limit, not subject to the NSPS catalyst regenerator continuous opacity
for PM in 40 CFR 60.102 or vent must not exceed monitoring system data
60.102a(b)(1). the site-specific according to Sec.
opacity operating 63.1572; maintaining
limit established the 3-hr rolling
during the performance average opacity at or
test. below the site-
specific limit.
[[Page 75295]]
b. Continuous See item 2.b of this See item 2.b of this
parametric monitoring table. table.
systems--electrostatic
precipitator.
c. Continuous See item 2.c of this See item 2.c of this
parametric monitoring table. table.
systems--wet scrubber.
d. BLD--fabric filter.. See item 2.d of this See item 2.d of this
table. table.
6. Option 1c: Elect NSPS subpart Ja PM CEMS................ Not applicable......... Complying with Table 6
requirements for PM concentration of this subpart, item
limit, not subject to the NSPS for 4.
PM in 40 CFR 60.102 or 60.102a(b)(1).
7. Option 2: PM per coke burn-off a. Continuous opacity The opacity of Collecting the hourly
limit, not subject to the NSPS for monitoring system. emissions from your and 3-hr rolling
PM in 40 CFR 60.102 or 60.102a(b)(1). catalyst regenerator average continuous
vent must not exceed opacity monitoring
the site-specific system data according
opacity operating to Sec. 63.1572; and
limit established maintaining the 3-hr
during the performance rolling average
test. opacity at or below
the site-specific
limit established
during the performance
test. Alternatively,
before August 1, 2017,
collecting the hourly
average continuous
opacity monitoring
system data according
to Sec. 63.1572; and
maintaining the hourly
average opacity at or
below the site-
specific limit.
b. Continuous parameter i. The average coke Collecting the hourly
monitoring systems-- burn-off rate or and daily average coke
electrostatic average gas flow rate burn-off rate or gas
precipitator. entering or exiting flow rate monitoring
the control device data according to Sec.
must not exceed the 63.1572; and
operating limit maintaining the daily
established during the coke burn-off rate or
performance test. average gas flow rate
at or below the limit
established during the
performance test.
ii. The average total Collecting the hourly
power (voltage and and 3-hr rolling
current) and secondary average total power
current to the control and secondary current
device must not fall monitoring data
below the operating according to Sec.
limit established 63.1572; and
during the performance maintaining the 3-hr
test. rolling average total
power and secondary
current at or above
the limit established
during the performance
test. Alternatively,
before August 1, 2017,
collecting the hourly
and daily average
voltage and secondary
current (or total
power input)
monitoring data
according to Sec.
63.1572; and
maintaining the daily
average voltage and
secondary current (or
total power input) at
or above the limit
established during the
performance test.
[[Page 75296]]
c. Continuous parameter i. The average liquid- Collecting the hourly
monitoring systems-- to-gas ratio must not and 3-hr rolling
wet scrubber. fall below the average gas flow rate
operating limit and scrubber liquid
established during the flow rate monitoring
performance test. data according to Sec.
63.1572; determining
and recording the 3-hr
liquid-to-gas ratio;
and maintaining the 3-
hr rolling average
liquid-to-gas ratio at
or above the limit
established during the
performance test.
Alternatively, before
August 1, 2017,
collecting the hourly
average gas flow rate
and water (or
scrubbing liquid) flow
rate monitoring data
according to Sec.
63.1572 \1\;
determining and
recording the hourly
average liquid-to-gas
ratio; determining and
recording the daily
average liquid-to-gas
ratio; and maintaining
the daily average
liquid-to-gas ratio
above the limit
established during the
performance test.
ii. Except for periods Collecting the hourly
of startup, shutdown and 3-hr rolling
and hot standby, the average pressure drop
average pressure drop monitoring data
across the scrubber according to Sec.
must not fall below 63.1572; and except
the operating limit for periods of
established during the startup, shutdown and
performance test. hot standby,
maintaining the 3-hr
rolling average
pressure drop at or
above the limit
established during the
performance test.
Alternatively, before
August 1, 2017,
collecting the hourly
and daily average
pressure drop
monitoring data
according to Sec.
63.1572; and
maintaining the daily
average pressure drop
above the limit
established during the
performance test.
d. BLD--fabric filter.. See item 2.d of this See item 2.d of this
table. table.
8. Option 3: Ni lb/hr limit not a. Continuous opacity i. The daily average Ni (1) Collecting the
subject to the NSPS for PM in 40 CFR monitoring system. operating value must hourly average
60.102. not exceed the site- continuous opacity
specific Ni operating monitoring system data
limit established according to Sec.
during the performance 63.1572; determining
test. and recording
equilibrium catalyst
Ni concentration at
least once a week \2\;
collecting the hourly
average gas flow rate
monitoring data
according to Sec.
63.1572 \1\; and
determining and
recording the hourly
average Ni operating
value using Equation
11 of Sec. 63.1564.
[[Page 75297]]
(2) Determining and
recording the 3-hour
rolling average Ni
operating value and
maintaining the 3-hour
rolling average Ni
operating value below
the site-specific Ni
operating limit
established during the
performance test.
Alternatively, before
August 1, 2017,
determining and
recording the daily
average Ni operating
value and maintaining
the daily average Ni
operating value below
the site-specific Ni
operating limit
established during the
performance test.
b. Continuous parameter i. The average gas flow See item 7.b.i of this
monitoring systems-- rate entering or table.
electrostatic exiting the control
precipitator. device must not exceed
the operating limit
established during the
performance test.
ii. The average total See item 7.b.ii of this
power (voltage and table.
current) and secondary
current must not fall
below the level
established in the
performance test.
iii. The monthly Determining and
rolling average of the recording the
equilibrium catalyst equilibrium catalyst
Ni concentration must Ni concentration at
not exceed the level least once a week \2\;
established during the determining and
performance test. recording the monthly
rolling average of the
equilibrium catalyst
Ni concentration once
each week using the
weekly or most recent
value; and maintaining
the monthly rolling
average below the
limit established in
the performance test.
c. Continuous parameter i. The average liquid- See item 7.c.i of this
monitoring systems-- to-gas ratio must not table.
wet scrubber. fall below the
operating limit
established during the
performance test..
ii. Except for periods See item 7.c.ii of this
of startup, shutdown table.
and hot standby, the
average pressure drop
must not fall below
the operating limit
established in the
performance test.
iii. The monthly Determining and
rolling average recording the
equilibrium catalyst equilibrium catalyst
Ni concentration must Ni concentration at
not exceed the level least once a week \2\;
established during the determining and
performance test. recording the monthly
rolling average of
equilibrium catalyst
Ni concentration once
each week using the
weekly or most recent
value; and maintaining
the monthly rolling
average below the
limit established in
the performance test.
d. BLD--fabric filter.. i. Increases in See item 7.d of this
relative particulate. table.
[[Page 75298]]
ii. The monthly rolling Determining and
average of the recording the
equilibrium catalyst equilibrium catalyst
Ni concentration must Ni concentration at
not exceed the level least once a week \2\;
established during the determining and
performance test. recording the monthly
rolling average of the
equilibrium catalyst
Ni concentration once
each week using the
weekly or most recent
value; and maintaining
the monthly rolling
average below the
limit established in
the performance test.
9. Option 4: Ni per coke burn-off a. Continuous opacity i. The daily average Ni (1) Collecting the
limit not subject to the NSPS for PM monitoring system. operating value must hourly average
in 40 CFR 60.102. not exceed the site- continuous opacity
specific Ni operating monitoring system data
limit established according to Sec.
during the performance 63.1572; collecting
test. the hourly average
coke burn rate and
hourly average gas
flow rate monitoring
data according to Sec.
63.15721;
determining and
recording equilibrium
catalyst Ni
concentration at least
once a week \2\; and
determining and
recording the hourly
average Ni operating
value using Equation
12 of Sec. 63.1564.
(2) Determining and
recording the 3-hour
rolling average Ni
operating value and
maintaining the 3-hour
rolling average Ni
operating value below
the site-specific Ni
operating limit
established during the
performance test
Alternatively, before
August 1, 2017,
determining and
recording the daily
average Ni operating
value and maintaining
the daily average Ni
operating value below
the site-specific Ni
operating limit
established during the
performance test.
b. Continuous parameter i. The average gas flow See item 7.b.i of this
monitoring systems-- rate to the control table.
electrostatic device must not exceed
precipitator. the level established
in the performance
test.
ii. The average voltage See item 7.b.ii of this
and secondary current table.
(or total power input)
must not fall below
the level established
in the performance
test.
iii. The monthly See item 8.b.iii of
rolling average this table.
equilibrium catalyst
Ni concentration must
not exceed the level
established during the
performance test.
c. Continuous parameter i. The average liquid- See item 7.c.i of this
monitoring systems-- to-gas ratio must not table.
wet scrubber. fall below the
operating limit
established during the
performance test.
ii. Except for periods See item 7.c.ii of this
of startup, shutdown table.
and hot standby, the
daily average pressure
drop must not fall
below the operating
limit established in
the performance test.
[[Page 75299]]
iii. The monthly See item 8.c.iii of
rolling average this table.
equilibrium catalyst
Ni concentration must
not exceed the level
established during the
performance test.
d. BLD--fabric filter.. i. See item 2.d of this See item 2.d of this
table. table.
ii. The monthly rolling Determining and
average of the recording the
equilibrium catalyst equilibrium catalyst
Ni concentration must Ni concentration at
not exceed the level least once a week \2\;
established during the determining and
performance test. recording the monthly
rolling average of the
equilibrium catalyst
Ni concentration once
each week using the
weekly or most recent
value; and maintaining
the monthly rolling
average below the
limit established in
the performance test.
10. During periods of startup, Any control device, if The inlet velocity Meeting the
shutdown, or hot standby. elected. limit to the primary requirements in Sec.
internal cyclones of 63.1564(c)(5).
the catalytic cracking
unit catalyst
regenerator in Sec.
63.1564(a)(5)(ii).
----------------------------------------------------------------------------------------------------------------
\1\ If applicable, you can use the alternative in Sec. 63.1573(a)(1) for gas flow rate instead of a continuous
parameter monitoring system if you used the alternative method in the initial performance test.
\2\ The equilibrium catalyst Ni concentration must be measured by the procedure, Determination of Metal
Concentration on Catalyst Particles (Instrumental Analyzer Procedure) in appendix A to this subpart; or by EPA
Method 6010B, Inductively Coupled Plasma-Atomic Emission Spectrometry, EPA Method 6020, Inductively Coupled
Plasma-Mass Spectrometry, EPA Method 7520, Nickel Atomic Absorption, Direct Aspiration, or EPA Method 7521,
Nickel Atomic Absorption, Direct Aspiration; or by an alternative to EPA Method 6010B, 6020, 7520, or 7521
satisfactory to the Administrator. The EPA Methods 6010B, 6020, 7520, and 7521 are included in ``Test Methods
for Evaluating Solid Waste, Physical/Chemical Methods,'' EPA Publication SW-846, Revision 5 (April 1998). The
SW-846 and Updates (document number 955-001-00000-1) are available for purchase from the Superintendent of
Documents, U.S. Government Publishing Office, Washington, DC 20402, (202) 512-1800; and from the National
Technical Information Services (NTIS), 5285 Port Royal Road, Springfield, VA 22161, (703) 487-4650. Copies may
be inspected at the EPA Docket Center, William Jefferson Clinton (WJC) West Building (Air Docket), Room 3334,
1301 Constitution Ave. NW., Washington, DC; or at the Office of the Federal Register, 800 North Capitol Street
NW., Suite 700, Washington, DC. These methods are also available at https://www.epa.gov/epaoswer/hazwaste/test/main.htm.
0
59. Table 8 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1565(a)(1), you shall meet each emission
limitation in the following table that applies to you.
Table 8 to Subpart UUU of Part 63--Organic HAP Emission Limits for
Catalytic Cracking Units
------------------------------------------------------------------------
You shall meet the following
For each new and existing catalytic emission limit for each
cracking unit . . . catalyst regenerator vent . .
.
------------------------------------------------------------------------
1. Subject to the NSPS for carbon CO emissions from the catalyst
monoxide (CO) in 40 CFR 60.103 or regenerator vent or CO boiler
60.102a(b)(4). serving the catalytic cracking
unit must not exceed 500 parts
per million volume (ppmv) (dry
basis).
2. Not subject to the NSPS for CO in 40 a. CO emissions from the
CFR 60.103 or 60.102a(b)(4). catalyst regenerator vent or
CO boiler serving the
catalytic cracking unit must
not exceed 500 ppmv (dry
basis).
b. If you use a flare to meet
the CO limit, then on and
after January 30, 2019, the
flare must meet the
requirements of Sec. 63.670.
Prior to January 30, 2019, the
flare must meet the
requirements for control
devices in Sec. 63.11(b) and
visible emissions must not
exceed a total of 5 minutes
during any 2 consecutive
hours, or the flare must meet
the requirements of Sec.
63.670.
------------------------------------------------------------------------
0
60. Table 9 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1565(a)(2), you shall meet each operating
limit in the following table that applies to you.
[[Page 75300]]
Table 9 to Subpart UUU of Part 63--Operating Limits for Organic HAP Emissions From Catalytic Cracking Units
----------------------------------------------------------------------------------------------------------------
For this type of
For each new or existing catalytic continuous monitoring For this type of You shall meet this
cracking unit . . . system . . . control device . . . operating limit . . .
----------------------------------------------------------------------------------------------------------------
1. Subject to the NSPS for carbon Continuous emission Not applicable......... Not applicable.
monoxide (CO) in 40 CFR 60.103 or monitoring system.
60.102a(b)(4).
2. Not subject to the NSPS for CO in a. Continuous emission Not applicable......... Not applicable.
40 CFR 60.103 or 60.102a(b)(4). monitoring system.
b. Continuous parameter i. Thermal incinerator. Maintain the daily
monitoring systems. average combustion
zone temperature above
the limit established
during the performance
test; and maintain the
daily average oxygen
concentration in the
vent stream (percent,
dry basis) above the
limit established
during the performance
test.
ii. Boiler or process Maintain the daily
heater with a design average combustion
heat input capacity zone temperature above
under 44 MW or a the limit established
boiler or process in the performance
heater in which all test.
vent streams are not
introduced into the
flame zone.
iii. Flare............. On and after January
30, 2019, the flare
must meet the
requirements of Sec.
63.670. Prior to
January 30, 2019, the
flare pilot light must
be present at all
times and the flare
must be operating at
all times that
emissions may be
vented to it, or the
flare must meet the
requirements of Sec.
63.670.
3. During periods of startup, Any.................... Any.................... Meet the requirements
shutdown or hot standby. in Sec.
63.1565(a)(5).
----------------------------------------------------------------------------------------------------------------
0
61. Table 10 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1565(b)(1), you shall meet each requirement
in the following table that applies to you.
Table 10 to Subpart UUU of Part 63--Continuous Monitoring Systems for
Organic HAP Emissions From Catalytic Cracking Units
------------------------------------------------------------------------
You shall install,
And you use this operate, and
For each new or existing type of control maintain this type
catalytic cracking unit . . . device for your of continuous
vent . . . monitoring system
. . .
------------------------------------------------------------------------
1. Subject to the NSPS for Not applicable.... Continuous
carbon monoxide (CO) in 40 CFR emission
60.103 or 60.102a(b)(4). monitoring system
to measure and
record the
concentration by
volume (dry
basis) of CO
emissions from
each catalyst
regenerator vent.
2. Not subject to the NSPS for a. Thermal Continuous
CO in 40 CFR 60.103 or incinerator. emission
60.102a(b)(4). monitoring system
to measure and
record the
concentration by
volume (dry
basis) of CO
emissions from
each catalyst
regenerator vent;
or continuous
parameter
monitoring
systems to
measure and
record the
combustion zone
temperature and
oxygen content
(percent, dry
basis) in the
incinerator vent
stream.
b. Process heater Continuous
or boiler with a emission
design heat input monitoring system
capacity under 44 to measure and
MW or process record the
heater or boiler concentration by
in which all vent volume (dry
streams are not basis) of CO
introduced into emissions from
the flame zone. each catalyst
regenerator vent;
or continuous
parameter
monitoring
systems to
measure and
record the
combustion zone
temperature.
[[Page 75301]]
c. Flare.......... On and after
January 30, 2019,
the monitoring
systems required
in Sec. Sec.
63.670 and
63.671. Prior to
January 30, 2019,
monitoring device
such as a
thermocouple, an
ultraviolet beam
sensor, or
infrared sensor
to continuously
detect the
presence of a
pilot flame, or
the monitoring
systems required
in Sec. Sec.
63.670 and
63.671.
d. No control Continuous
device. emission
monitoring system
to measure and
record the
concentration by
volume (dry
basis) of CO
emissions from
each catalyst
regenerator vent.
3. During periods of startup, Any............... Continuous
shutdown or hot standby parameter
electing to comply with the monitoring system
operating limit in Sec. to measure and
63.1565(a)(5)(ii). record the
concentration by
volume (dry
basis) of oxygen
from each
catalyst
regenerator vent.
------------------------------------------------------------------------
0
62. Table 11 to subpart UUU of part 63 is amended by revising the entry
for item 3 to read as follows:
* * * * *
Table 11 to Subpart UUU of Part 63--Requirements for Performance Tests for Organic HAP Emissions From Catalytic
Cracking Units Not Subject to New Source Performance Standard (NSPS) for Carbon Monoxide (CO)
----------------------------------------------------------------------------------------------------------------
According to these
For . . . You must . . . Using . . . requirements . . .
----------------------------------------------------------------------------------------------------------------
* * * * * *
3. Each catalytic cracking unit a. Measure the CO Method 10, 10A, or 10B .......................
catalyst regenerator vent if you use concentration (dry in appendix A-4 to
continuous parameter monitoring basis) of emissions part 60 of this
systems. exiting the control chapter, as applicable.
device.
b. Establish each Data from the .......................
operating limit in continuous parameter
Table 9 of this monitoring systems.
subpart that applies
to you.
c. Thermal incinerator Data from the Collect temperature
combustion zone continuous parameter monitoring data every
temperature. monitoring systems. 15 minutes during the
entire period of the
CO initial performance
test; and determine
and record the minimum
hourly average
combustion zone
temperature from all
the readings.
d. Thermal incinerator: Data from the Collect oxygen
oxygen, content continuous parameter concentration
(percent, dry basis) monitoring systems. (percent, dry basis)
in the incinerator monitoring data every
vent stream. 15 minutes during the
entire period of the
CO initial performance
test; and determine
and record the minimum
hourly average percent
excess oxygen
concentration from all
the readings.
e. If you use a process Data from the Collect the temperature
heater or boiler with continuous parameter monitoring data every
a design heat input monitoring systems. 15 minutes during the
capacity under 44 MW entire period of the
or process heater or CO initial performance
boiler in which all test; and determine
vent streams are not and record the minimum
introduced into the hourly average
flame zone, establish combustion zone
operating limit for temperature from all
combustion zone the readings.
temperature.
[[Page 75302]]
f. If you use a flare, Method 22 (40 CFR part On and after January
conduct visible 60, appendix A-7). 30, 2019, meet the
emission observations. requirements of Sec.
63.670. Prior to
January 30, 2019,
maintain a 2-hour
observation period;
and record the
presence of a flame at
the pilot light over
the full period of the
test or meet the
requirements of Sec.
63.670.
g. If you use a flare, 40 CFR 63.11(b)(6) On and after January
determine that the through (8). 30, 2019, the flare
flare meets the must meet the
requirements for net requirements of Sec.
heating value of the 63.670. Prior to
gas being combusted January 30, 2019, the
and exit velocity. flare must meet the
control device
requirements in Sec.
63.11(b) or the
requirements of Sec.
63.670.
----------------------------------------------------------------------------------------------------------------
0
63. Table 12 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1565(b)(4), you shall meet each requirement
in the following table that applies to you.
Table 12 to Subpart UUU of Part 63--Initial Compliance With Organic HAP
Emission Limits for Catalytic Cracking Units
------------------------------------------------------------------------
For the following
For each new and existing emission limit . You have demonstrated
catalytic cracking unit . . . . . initial compliance if
. . .
------------------------------------------------------------------------
1. Subject to the NSPS for CO emissions from You have already
carbon monoxide (CO) in 40 your catalyst conducted a
CFR 60.103, 60.100(e), or regenerator vent performance test to
60.102a(b)(4). or CO boiler demonstrate initial
serving the compliance with the
catalytic NSPS and the
cracking unit measured CO
must not exceed emissions are less
500 ppmv (dry than or equal to 500
basis). ppm (dry basis). As
part of the
Notification of
Compliance Status,
you must certify
that your vent meets
the CO limit. You
are not required to
conduct another
performance test to
demonstrate initial
compliance. You have
already conducted a
performance
evaluation to
demonstrate initial
compliance with the
applicable
performance
specification. As
part of your
Notification of
Compliance Status,
you must certify
that your continuous
emission monitoring
system meets the
applicable
requirements in Sec.
63.1572. You are
not required to
conduct another
performance
evaluation to
demonstrate initial
compliance.
2. Not subject to the NSPS for a. CO emissions i. If you use a
CO in 40 CFR 60.103 from your continuous parameter
60.102a(b)(4). catalyst monitoring system,
regenerator vent the average CO
or CO boiler emissions measured
serving the by Method 10 over
catalytic the period of the
cracking unit initial performance
must not exceed test are less than
500 ppmv (dry or equal to 500 ppmv
basis). (dry basis).
ii. If you use a
continuous emission
monitoring system,
the hourly average
CO emissions over
the 24-hour period
for the initial
performance test are
not more than 500
ppmv (dry basis);
and your performance
evaluation shows
your continuous
emission monitoring
system meets the
applicable
requirements in Sec.
63.1572.
b. If you use a On and after January
flare, visible 30, 2019, the flare
emissions must meets the
not exceed a requirements of Sec.
total of 5 63.670. Prior to
minutes during January 30, 2019,
any 2 operating visible emissions,
hours. measured by Method
22 during the 2-hour
observation period
during the initial
performance test,
are no higher than 5
minutes, or the
flare meets the
requirements of Sec.
63.670.
------------------------------------------------------------------------
0
64. Table 13 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1565(c)(1), you shall meet each requirement
in the following table that applies to you.
[[Page 75303]]
Table 13 to Subpart UUU of Part 63--Continuous Compliance With Organic HAP Emission Limits for Catalytic
Cracking Units
----------------------------------------------------------------------------------------------------------------
Subject to this
For each new and existing catalytic emission limit for your You shall demonstrate
cracking unit . . . catalyst regenerator If you must . . . continuous compliance
vent . . . by . . .
----------------------------------------------------------------------------------------------------------------
1. Subject to the NSPS for carbon CO emissions from your Continuous emission Collecting the hourly
monoxide (CO) in 40 CFR 60.103, catalyst regenerator monitoring system. average CO monitoring
60.100(e), or 60.102a(b)(4). vent or CO boiler data according to Sec.
serving the catalytic 63.1572; and
cracking unit must not maintaining the hourly
exceed 500 ppmv (dry average CO
basis). concentration at or
below 500 ppmv (dry
basis).
2. Not subject to the NSPS for CO in a. CO emissions from Continuous emission Same as item 1.
40 CFR 60.103 or 60.102a(b)(4). your catalyst monitoring system.
regenerator vent or CO
boiler serving the
catalytic cracking
unit must not exceed
500 ppmv (dry basis).
b. CO emissions from Continuous parameter Maintaining the hourly
your catalyst monitoring system. average CO
regenerator vent or CO concentration below
boiler serving the 500 ppmv (dry basis).
catalytic cracking
unit must not exceed
500 ppmv (dry basis).
c. Visible emissions Control device-flare... On and after January
from a flare must not 30, 2019, meeting the
exceed a total of 5 requirements of Sec.
minutes during any 2- 63.670. Prior to
hour period. January 30, 2019,
maintaining visible
emissions below a
total of 5 minutes
during any 2-hour
operating period, or
meeting the
requirements of Sec.
63.670.
----------------------------------------------------------------------------------------------------------------
0
65. Table 14 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1565(c)(1), you shall meet each requirement
in the following table that applies to you.
Table 14 to Subpart UUU of Part 63--Continuous Compliance With Operating Limits for Organic HAP Emissions From
Catalytic Cracking Units
----------------------------------------------------------------------------------------------------------------
You shall demonstrate
For each new existing catalytic If you use . . . For this operating continuous compliance
cracking unit . . . limit . . . by . . .
----------------------------------------------------------------------------------------------------------------
1. Subject to NSPS for carbon Continuous emission Not applicable......... Complying with Table 13
monoxide (CO) in 40 CFR 60.103, monitoring system. of this subpart, item
60.100(e), 60.102a(b)(4). 1.
2. Not subject to the NSPS for CO in a. Continuous emission Not applicable......... Complying with Table 13
40 CFR 60.103 or 60.102a(b)(4). monitoring system. of this subpart, item
2.a.
b. Continuous parameter i. The daily average Collecting the hourly
monitoring systems-- combustion zone and daily average
thermal incinerator. temperature must not temperature monitoring
fall below the level data according to Sec.
established during the 63.1572; and
performance test. maintaining the daily
average combustion
zone temperature above
the limit established
during the performance
test.
ii. The daily average Collecting the hourly
oxygen concentration and daily average
in the vent stream oxygen concentration
(percent, dry basis) monitoring data
must not fall below according to Sec.
the level established 63.1572; and
during the performance maintaining the daily
test. average oxygen
concentration above
the limit established
during the performance
test.
c. Continuous parameter The daily combustion Collecting the average
monitoring systems-- zone temperature must hourly and daily
boiler or process not fall below the temperature monitoring
heater with a design level established in data according to Sec.
heat input capacity the performance test. 63.1572; and
under 44 MW or boiler maintaining the daily
or process heater in average combustion
which all vent streams zone temperature above
are not introduced the limit established
into the flame zone. during the performance
test.
[[Page 75304]]
d. Continuous parameter The flare pilot light On and after January
monitoring system-- must be present at all 30, 2019, meeting the
flare. times and the flare requirements of Sec.
must be operating at 63.670. Prior to
all times that January 30, 2019,
emissions may be collecting the flare
vented to it. monitoring data
according to Sec.
63.1572 and recording
for each 1-hour period
whether the monitor
was continuously
operating and the
pilot light was
continuously present
during each 1-hour
period, or meeting the
requirements of Sec.
63.670.
3. During periods of startup, Any control device..... The oxygen Collecting the hourly
shutdown or hot standby electing to concentration limit in average oxygen
comply with the operating limit in Sec. concentration
Sec. 63.1565(a)(5)(ii). 63.1565(a)(5)(ii). monitoring data
according to Sec.
63.1572 and
maintaining the hourly
average oxygen
concentration at or
above 1 volume percent
(dry basis).
----------------------------------------------------------------------------------------------------------------
0
66. Table 15 to subpart UUU of part 63 is amended by revising the entry
for item 1 to read as follows:
* * * * *
Table 15 to Subpart UUU of Part 63--Organic HAP Emission Limits for
Catalytic Reforming Units
------------------------------------------------------------------------
You shall meet this
emission limit
during initial
For each applicable process vent for a new or catalyst
existing catalytic reforming unit . . . depressuring and
catalyst purging
operations . . .
------------------------------------------------------------------------
1. Option 1....................................... On and after January
30, 2019, vent
emissions to a
flare that meets
the requirements of
Sec. 63.670.
Prior to January
30, 2019, vent
emissions to a
flare that meets
the requirements
for control devices
in Sec. 63.11(b)
and visible
emissions from a
flare must not
exceed a total of 5
minutes during any
2-hour operating
period, or vent
emissions to a
flare that meets
the requirements of
Sec. 63.670.
* * * * * * *
------------------------------------------------------------------------
0
67. Table 16 to subpart UUU of part 63 is amended by revising the entry
for item 1 to read as follows:
* * * * *
Table 16 to Subpart UUU of Part 63--Operating Limits for Organic HAP
Emissions From Catalytic Reforming Units
------------------------------------------------------------------------
You shall meet this
operating limit
For each new or existing For this type of during initial
catalytic reforming unit . . . control device . catalyst depressuring
. . and purging
operations. . .
------------------------------------------------------------------------
1. Option 1: Vent to flare.... Flare............ On and after January
30, 2019, the flare
must meet the
requirements of Sec.
63.670. Prior to
January 30, 2019,
the flare pilot
light must be
present at all times
and the flare must
be operating at all
times that emissions
may be vented to it,
or the flare must
meet the
requirements of Sec.
63.670.
* * * * * * *
------------------------------------------------------------------------
0
68. Table 17 to subpart UUU of part 63 is amended by revising the entry
for item 1 to read as follows:
* * * * *
[[Page 75305]]
Table 17 to Subpart UUU of Part 63--Continuous Monitoring Systems for
Organic HAP Emissions From Catalytic Reforming Units
------------------------------------------------------------------------
You shall install and
For each applicable process If you use this operate this type of
vent for a new or existing type of control continuous monitoring
catalytic reforming unit . . device . . . system . . .
.
------------------------------------------------------------------------
1. Option 1: Vent to a flare.. Flare............ On and after January
30, 2019, the
monitoring systems
required in Sec.
Sec. 63.670 and
63.671. Prior to
January 30, 2019,
monitoring device
such as a
thermocouple, an
ultraviolet beam
sensor, or infrared
sensor to
continuously detect
the presence of a
pilot flame, or the
monitoring systems
required in Sec.
Sec. 63.670 and
63.671.
* * * * * * *
------------------------------------------------------------------------
0
69. Table 18 to subpart UUU of part 63 is amended by revising the
column headings and the entry for item 1 to read as follows:
* * * * *
Table 18 to Subpart UUU of Part 63--Requirements for Performance Tests for Organic HAP Emissions From Catalytic
Reforming Units
----------------------------------------------------------------------------------------------------------------
For each new or existing catalytic According to these
reforming unit . . . You must . . . Using . . . requirements . . .
----------------------------------------------------------------------------------------------------------------
1. Option 1: Vent to a flare......... a. Conduct visible Method 22 (40 CFR part On and after January
emission observations. 60, appendix A-7). 30, 2019, the flare
must meet the
requirements of Sec.
63.670. Prior to
January 30, 2019, 2-
hour observation
period. Record the
presence of a flame at
the pilot light over
the full period of the
test, or the
requirements of Sec.
63.670.
b. Determine that the 40 CFR 63.11(b)(6) On and after January
flare meets the through (8). 30, 2019, the flare
requirements for net must meet the
heating value of the requirements of Sec.
gas being combusted 63.670. Prior to
and exit velocity. January 30, 2019, the
flare must meet the
control device
requirements in Sec.
63.11(b) or the
requirements of Sec.
63.670.
* * * * * * *
----------------------------------------------------------------------------------------------------------------
0
70. Table 19 to subpart UUU of part 63 is amended by revising the entry
for item 1 to read as follows:
* * * * *
Table 19 to Subpart UUU of Part 63--Initial Compliance With Organic HAP
Emission Limits for Catalytic Reforming Units
------------------------------------------------------------------------
For each applicable process
vent for a new or existing For the following You have
catalytic reforming unit . . emission limit . . . demonstrated initial
. compliance if . . .
------------------------------------------------------------------------
Option 1.................... Visible emissions On and after January
from a flare must 30, 2019, the flare
not exceed a total meets the
of 5 minutes during requirements of
any 2 consecutive Sec. 63.670.
hours. Prior to January
30, 2019, visible
emissions, measured
using Method 22
over the 2-hour
observation period
of the performance
test, do not exceed
a total of 5
minutes, or the
flare meets the
requirements of
Sec. 63.670.
* * * * * * *
------------------------------------------------------------------------
0
71. Table 20 to subpart UUU of part 63 is amended by revising the entry
for item 1 to read as follows:
* * * * *
[[Page 75306]]
Table 20 to Subpart UUU of Part 63--Continuous Compliance With Organic
HAP Emission Limits for Catalytic Reforming Units
------------------------------------------------------------------------
You shall
demonstrate
For each applicable process continuous
vent for a new or existing For this emission compliance during
catalytic reforming unit . . limit . . . initial catalyst
. depressuring and
catalyst purging
operations by . . .
------------------------------------------------------------------------
1. Option 1................. Vent emissions from On and after January
your process vent 30, 2019, meeting
to a flare. the requirements of
Sec. 63.670.
Prior to January
30, 2019,
maintaining visible
emissions from a
flare below a total
of 5 minutes during
any 2 consecutive
hours, or meeting
the requirements of
Sec. 63.670.
* * * * * * *
------------------------------------------------------------------------
0
72. Table 21 to subpart UUU of part 63 is amended by revising the entry
for item 1 to read as follows:
* * * * *
Table 21 to Subpart UUU of Part 63--Continuous Compliance With Operating Limits for Organic HAP Emissions From
Catalytic Reforming Units
----------------------------------------------------------------------------------------------------------------
You shall demonstrate
continuous compliance
For each applicable process vent for For this operating during initial catalyst
a new or existing catalytic reforming If you use . . . limit . . . depressuring and
unit . . . purging operations by
. . .
----------------------------------------------------------------------------------------------------------------
1. Option 1.......................... Flare.................. The flare pilot light On and after January
must be present at all 30, 2019, meeting the
times and the flare requirements of Sec.
must be operating at 63.670. Prior to
all times that January 30, 2019,
emissions may be collecting flare
vented to it. monitoring data
according to Sec.
63.1572 and recording
for each 1-hour period
whether the monitor
was continuously
operating and the
pilot light was
continuously present
during each 1-hour
period, or meeting the
requirements of Sec.
63.670.
* * * * * * *
----------------------------------------------------------------------------------------------------------------
0
73. Table 22 to subpart UUU of part 63 is amended by revising the
entries for items 2 and 3 to read as follows:
* * * * *
Table 22 to Subpart UUU of Part 63--Inorganic HAP Emission Limits for
Catalytic Reforming Units
------------------------------------------------------------------------
You shall meet this emission
limit for each applicable
catalytic reforming unit
For . . . process vent during coke burn-
off and catalyst rejuvenation
. . .
------------------------------------------------------------------------
* * * * * * *
2. Each existing cyclic or continuous Reduce uncontrolled emissions
catalytic reforming unit. of HCl by 97 percent by weight
or to a concentration of 10
ppmv (dry basis), corrected to
3 percent oxygen.
3. Each new semi-regenerative, cyclic, Reduce uncontrolled emissions
or continuous catalytic reforming unit. of HCl by 97 percent by weight
or to a concentration of 10
ppmv (dry basis), corrected to
3 percent oxygen.
------------------------------------------------------------------------
0
74. Table 24 to subpart UUU of part 63 is amended by revising the
entries for items 2 through 4 and footnote 2 to read as follows:
* * * * *
[[Page 75307]]
Table 24 to Subpart UUU of Part 63--Continuous Monitoring Systems for
Inorganic HAP Emissions From Catalytic Reforming Units
------------------------------------------------------------------------
You shall install and operate
If you use this type of control device this type of continuous
for your vent . . . monitoring system . . .
------------------------------------------------------------------------
* * * * * * *
2. Internal scrubbing system or no Colormetric tube sampling
control device (e.g., hot regen system to measure the HCl
system) to meet HCl outlet concentration in the catalyst
concentration limit. regenerator exhaust gas during
coke burn-off and catalyst
rejuvenation. The colormetric
tube sampling system must meet
the requirements in Table 41
of this subpart.
3. Internal scrubbing system to meet Continuous parameter monitoring
HCl percent reduction standard. system to measure and record
the gas flow rate entering or
exiting the internal scrubbing
system during coke burn-off
and catalyst rejuvenation; and
continuous parameter
monitoring system to measure
and record the total water (or
scrubbing liquid) flow rate
entering the internal
scrubbing system during coke
burn-off and catalyst
rejuvenation; and continuous
parameter monitoring system to
measure and record the pH or
alkalinity of the water (or
scrubbing liquid) exiting the
internal scrubbing system
during coke burn-off and
catalyst rejuvenation.\2\
4. Fixed-bed gas-solid adsorption Continuous parameter monitoring
system. system to measure and record
the temperature of the gas
entering or exiting the
adsorption system during coke
burn-off and catalyst
rejuvenation; and colormetric
tube sampling system to
measure the gaseous HCl
concentration in the
adsorption system exhaust and
at a point within the
absorbent bed not to exceed 90
percent of the total length of
the absorbent bed during coke
burn-off and catalyst
rejuvenation. The colormetric
tube sampling system must meet
the requirements in Table 41
of this subpart.
* * * * * * *
------------------------------------------------------------------------
* * * * * * *
\2\ If applicable, you can use the alternative in Sec. 63.1573(c)(1)
instead of a continuous parameter monitoring system for pH of the
water (or scrubbing liquid) or the alternative in Sec. 63.1573(c)(2)
instead of a continuous parameter monitoring system for alkalinity of
the water (or scrubbing liquid).
* * * * *
0
75. Table 25 to subpart UUU of part 63 is amended by revising the
entries for items 2.a and 4.a and footnote 1 to read as follows:
* * * * *
Table 25 to Subpart UUU of Part 63--Requirements for Performance Tests for Inorganic HAP Emissions From
Catalytic Reforming Units
----------------------------------------------------------------------------------------------------------------
For each new and existing catalytic According to these
reforming unit using . . . You shall . . . Using . . . requirements . . .
----------------------------------------------------------------------------------------------------------------
* * * * * * *
2. Wet scrubber...................... a. Establish operating i. Data from continuous Measure and record the
limit for pH level or parameter monitoring pH or alkalinity of
alkalinity. systems. the water (or
scrubbing liquid)
exiting scrubber every
15 minutes during the
entire period of the
performance test.
Determine and record
the minimum hourly
average pH or
alkalinity level from
the recorded values.
ii. Alternative pH Measure and record the
procedure in Sec. pH of the water (or
63.1573(b)(1). scrubbing liquid)
exiting the scrubber
during coke burn-off
and catalyst
rejuvenation using pH
strips at least three
times during each test
run. Determine and
record the average pH
level for each test
run. Determine and
record the minimum
test run average pH
level.
[[Page 75308]]
iii. Alternative Measure and record the
alkalinity method in alkalinity of the
Sec. 63.1573(c)(2). water (or scrubbing
liquid) exiting the
scrubber during coke
burn-off and catalyst
rejuvenation using
discrete titration at
least three times
during each test run.
Determine and record
the average alkalinity
level for each test
run. Determine and
record the minimum
test run average
alkalinity level.
* * * * * * *
4. Internal scrubbing system meeting a. Establish operating i. Data from continuous Measure and record the
HCl percent reduction standard. limit for pH level or parameter monitoring pH alkalinity of the
alkalinity. system. water (or scrubbing
liquid) exiting the
internal scrubbing
system every 15
minutes during the
entire period of the
performance test.
Determine and record
the minimum hourly
average pH or
alkalinity level from
the recorded values.
ii. Alternative pH Measure and in record
method in Sec. pH of the water (or
63.1573(c)(1). scrubbing liquid)
exiting the internal
scrubbing system
during coke burn-off
and catalyst
rejuvenation using pH
strips at least three
times during each test
run. Determine and
record the average pH
level for each test
run. Determine and
record the minimum
test run average pH
level.
iii. Alternative Measure and record the
alkalinity method in alkalinity water (or
Sec. 63.1573(c)(2). scrubbing liquid)
exiting the internal
scrubbing system
during coke burn-off
and catalyst
rejuvenation using
discrete titration at
least three times
during each test run.
Determine and record
the average alkalinity
level for each test
run. Determine and
record the minimum
test run average
alkalinity level.
* * * * * * *
----------------------------------------------------------------------------------------------------------------
\1\ The EPA Methods 5050, 9056, 9212 and 9253 are included in ``Test Methods for Evaluating Solid Waste,
Physical/Chemical Methods,'' EPA Publication SW-846, Revision 5 (April 1998). The SW-846 and Updates (document
number 955-001-00000-1) are available for purchase from the Superintendent of Documents, U.S. Government
Printing Office, Washington, DC 20402, (202) 512-1800; and from the National Technical Information Services
(NTIS), 5285 Port Royal Road, Springfield, VA 22161, (703) 487-4650. Copies may be inspected at the EPA Docket
Center, William Jefferson Clinton (WJC) West Building (Air Docket), Room 3334, 1301 Constitution Ave. NW.,
Washington, DC; or at the Office of the Federal Register, 800 North Capitol Street NW., Suite 700, Washington,
DC. These methods are also available at https://www.epa.gov/epaoswer/hazwaste/test/main.htm.
0
76. Table 28 to subpart UUU of part 63 is amended by revising the entry
for item 5 and footnotes 1 and 3 to read as follows:
* * * * *
Table 28 to Subpart UUU of Part 63--Continuous Compliance With Operating
Limits for Inorganic HAP Emissions From Catalytic Reforming Units
------------------------------------------------------------------------
You shall
demonstrate
For each new and existing continuous
catalytic reforming unit For this operating compliance during
using this type of control limit . . . coke burn-off and
device or system . . . catalyst
rejuvenation by . .
.
------------------------------------------------------------------------
[[Page 75309]]
* * * * * * *
5. Moving-bed gas-solid a. The daily average Collecting the
adsorption system (e.g., temperature of the hourly and daily
ChlorsorbTM System). gas entering or average temperature
exiting the monitoring data
adsorption system according to Sec.
must not exceed the 63.1572; and
limit established maintaining the
during the daily average
performance test. temperature below
the operating limit
established during
the performance
test.
b. The weekly Collecting samples
average chloride of the sorbent
level on the exiting the
sorbent entering adsorption system
the adsorption three times per
system must not week (on non-
exceed the design consecutive days);
or manufacturer's and analyzing the
recommended limit samples for total
(1.35 weight chloride\3\; and
percent for the determining and
Chlorsorb\TM\ recording the
System). weekly average
chloride
concentration; and
maintaining the
chloride
concentration below
the design or
manufacturer's
recommended limit
(1.35 weight
percent for the
Chlorsorb\TM\
System).
c. The weekly Collecting samples
average chloride of the sorbent
level on the exiting the
sorbent exiting the adsorption system
adsorption system three times per
must not exceed the week (on non-
design or consecutive days);
manufacturer's and analyzing the
recommended limit samples for total
(1.8 weight percent chloride
for the concentration; and
Chlorsorb\TM\ determining and
System). recording the
weekly average
chloride
concentration; and
maintaining the
chloride
concentration below
the design or
manufacturer's
recommended limit
(1.8 weight percent
Chlorsorb\TM\
System).
------------------------------------------------------------------------
\1\ If applicable, you can use either alternative in Sec. 63.1573(c)
instead of a continuous parameter monitoring system for pH or
alkalinity if you used the alternative method in the initial
performance test.
* * * * * * *
\3\ The total chloride concentration of the sorbent material must be
measured by the procedure, ``Determination of Metal Concentration on
Catalyst Particles (Instrumental Analyzer Procedure)'' in appendix A
to this subpart; or by using EPA Method 5050, Bomb Preparation Method
for Solid Waste, combined either with EPA Method 9056, Determination
of Inorganic Anions by Ion Chromatography, or with EPA Method 9253,
Chloride (Titrimetric, Silver Nitrate); or by using EPA Method 9212,
Potentiometric Determination of Chloride in Aqueous Samples with Ion-
Selective Electrode, and using the soil extraction procedures listed
within the method. The EPA Methods 5050, 9056, 9212 and 9253 are
included in ``Test Methods for Evaluating Solid Waste, Physical/
Chemical Methods,'' EPA Publication SW-846, Revision 5 (April 1998).
The SW-846 and Updates (document number 955-001-00000-1) are available
for purchase from the Superintendent of Documents, U.S. Government
Printing Office, Washington, DC 20402, (202) 512-1800; and from the
National Technical Information Services (NTIS), 5285 Port Royal Road,
Springfield, VA 22161, (703) 487-4650. Copies may be inspected at the
EPA Docket Center, William Jefferson Clinton (WJC) West Building, (Air
Docket), Room 3334, 1301 Constitution Ave. NW., Washington, DC; or at
the Office of the Federal Register, 800 North Capitol Street NW.,
Suite 700, Washington, DC. These methods are also available at https://www.epa.gov/epaoswer/hazwaste/test/main.htm.
0
77. Table 29 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1568(a)(1), you shall meet each emission
limitation in the following table that applies to you.
Table 29 to Subpart UUU of Part 63--HAP Emission Limits for Sulfur
Recovery Units
------------------------------------------------------------------------
You shall meet this emission
For . . . limit for each process vent . .
.
------------------------------------------------------------------------
1. Subject to NSPS. Each new or a. 250 ppmv (dry basis) of
existing Claus sulfur recovery unit sulfur dioxide (SO2) at zero
part of a sulfur recovery plant with percent excess air, or
design capacity greater than 20 long concentration determined using
tons per day (LTD) and subject to the Equation 1 of 40 CFR
NSPS for sulfur oxides in 40 CFR 60.102a(f)(1)(i), if you use
60.104(a)(2) or 60.102a(f)(1). an oxidation control system or
if you use a reduction control
system followed by
incineration.
b. 300 ppmv of reduced sulfur
compounds calculated as ppmv
SO2 (dry basis) at zero
percent excess air, or
concentration determined using
Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use a
reduction control system
without incineration.
2. Option 1: Elect NSPS. Each new or a. 250 ppmv (dry basis) of SO2
existing sulfur recovery unit (Claus at zero percent excess air, or
or other type, regardless of size) not concentration determined using
subject to the NSPS for sulfur oxides Equation 1 of 40 CFR
in 40 CFR 60.104(a)(2) or 60.102a(f)(1)(i), if you use
60.102a(f)(1). an oxidation control system or
if you use a reduction control
system followed by
incineration.
b. 300 ppmv of reduced sulfur
compounds calculated as ppmv
SO2 (dry basis) at zero
percent excess air, or
concentration determined using
Equation 1 of 40 CFR
60.102a(f)(1)(i), if you use a
reduction control system
without incineration.
3. Option 2: TRS limit. Each new or 300 ppmv of total reduced
existing sulfur recovery unit (Claus sulfur (TRS) compounds,
or other type, regardless of size) not expressed as an equivalent SO2
subject to the NSPS for sulfur oxides concentration (dry basis) at
in 40 CFR 60.104(a)(2) or zero percent oxygen.
60.102a(f)(1).
------------------------------------------------------------------------
[[Page 75310]]
0
78. Table 30 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1568(a)(2), you shall meet each operating
limit in the following table that applies to you.
Table 30 to Subpart UUU of Part 63--Operating Limits for HAP Emissions
From Sulfur Recovery Units
------------------------------------------------------------------------
You shall meet this
For . . . If use this type of operating limit . .
control device . . . .
------------------------------------------------------------------------
1. Subject to NSPS. Each new Not applicable...... Not applicable.
or existing Claus sulfur
recovery unit part of a
sulfur recovery plant with
design capacity greater
than 20 LTD and subject to
the NSPS for sulfur oxides
in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
2. Option 1: Elect NSPS. Not applicable...... Not applicable.
Each new or existing sulfur
recovery unit (Claus or
other type, regardless of
size) not subject to the
NSPS for sulfur oxides in
40 CFR 60.104(a)(2) or
60.102a(f)(1).
3. Option 2: TRS limit, if Not applicable...... Not applicable.
using continuous emissions
monitoring systems. Each
new or existing sulfur
recovery unit (Claus or
other type, regardless of
size) not subject to the
NSPS for sulfur oxides in
40 CFR 60.104(a)(2) or
60.102a(f)(1).
4. Option 2: TRS limit, if Thermal incinerator. Maintain the daily
using continuous parameter average combustion
monitoring systems. Each zone temperature
new or existing sulfur above the limit
recovery unit (Claus or established during
other type, regardless of the performance
size) not subject to the test; and maintain
NSPS for sulfur oxides in the daily average
40 CFR 60.104(a)(2) or oxygen
60.102a(f)(1). concentration in
the vent stream
(percent, dry
basis) above the
limit established
during the
performance test.
5. Startup or shutdown Flare............... On and after January
option 1: Electing to 30, 2019, meet the
comply with Sec. applicable
63.1568(a)(4)(ii). Each new requirements of
or existing sulfur recovery Sec. 63.670.
unit (Claus or other type, Prior to January
regardless of size) during 30, 2019, meet the
periods of startup or applicable
shutdown. requirements of
either Sec.
63.11(b) or Sec.
63.670.
6. Startup or shutdown Thermal incinerator Maintain the hourly
option 2: Electing to or thermal oxidizer. average combustion
comply with Sec. zone temperature at
63.1568(a)(4)(iii). Each or above 1,200
new or existing sulfur degrees Fahrenheit
recovery unit (Claus or and maintain the
other type, regardless of hourly average
size) during startup or oxygen
shutdown events. concentration in
the exhaust gas
stream at or above
2 volume percent
(dry basis).
------------------------------------------------------------------------
0
79. Table 31 to subpart UUU is revised to read as follows:
As stated in Sec. 63.1568(b)(1), you shall meet each requirement
in the following table that applies to you.
Table 31 to Subpart UUU of Part 63--Continuous Monitoring Systems for
HAP Emissions From Sulfur Recovery Units
------------------------------------------------------------------------
You shall install
and operate this
For . . . For this limit . . . continuous
monitoring system .
. .
------------------------------------------------------------------------
1. Subject to NSPS. Each new a. 250 ppmv (dry Continuous emission
or existing Claus sulfur basis) of SO2 at monitoring system
recovery unit part of a zero percent excess to measure and
sulfur recovery plant with air if you use an record the hourly
design capacity greater oxidation or average
than 20 LTD and subject to reduction control concentration of
the NSPS for sulfur oxides system followed by SO2 (dry basis) at
in 40 CFR 60.104(a)(2) or incineration. zero percent excess
60.102a(f)(1). air for each
exhaust stack. This
system must include
an oxygen monitor
for correcting the
data for excess
air.
[[Page 75311]]
b. 300 ppmv of Continuous emission
reduced sulfur monitoring system
compounds to measure and
calculated as ppmv record the hourly
SO2 (dry basis) at average
zero percent excess concentration of
air if you use a reduced sulfur and
reduction control oxygen (O2)
system without emissions.
incineration. Calculate the
reduced sulfur
emissions as SO2
(dry basis) at zero
percent excess air.
Exception: You can
use an instrument
having an air or
SO2 dilution and
oxidation system to
convert the reduced
sulfur to SO2 for
continuously
monitoring and
recording the
concentration (dry
basis) at zero
percent excess air
of the resultant
SO2 instead of the
reduced sulfur
monitor. The
monitor must
include an oxygen
monitor for
correcting the data
for excess oxygen.
c. If you use i. Complete either
Equation 1 of 40 item 1.a or item
CFR 1.b; and
60.102a(f)(1)(i) to ii. Either a
set your emission continuous emission
limit. monitoring system
to measure and
record the O2
concentration for
the inlet air/
oxygen supplied to
the system or a
continuous
parameter
monitoring system
to measure and
record the
volumetric gas flow
rate of ambient air
and purchased
oxygen-enriched
gas.
2. Option 1: Elect NSPS. a. 250 ppmv (dry Continuous emission
Each new or existing sulfur basis) of SO2 at monitoring system
recovery unit (Claus or zero percent excess to measure and
other type, regardless of air if you use an record the hourly
size) not subject to the oxidation or average
NSPS for sulfur oxides in reduction control concentration of
40 CFR 60.104(a)(2) or system followed by SO2 (dry basis), at
60.102a(f)(1). incineration. zero percent excess
air for each
exhaust stack. This
system must include
an oxygen monitor
for correcting the
data for excess
air.
b. 300 ppmv of Continuous emission
reduced sulfur monitoring system
compounds to measure and
calculated as ppmv record the hourly
SO2 (dry basis) at average
zero percent excess concentration of
air if you use a reduced sulfur and
reduction control O2 emissions for
system without each exhaust stack.
incineration. Calculate the
reduced sulfur
emissions as SO2
(dry basis), at
zero percent excess
air. Exception: You
can use an
instrument having
an air or O2
dilution and
oxidation system to
convert the reduced
sulfur to SO2 for
continuously
monitoring and
recording the
concentration (dry
basis) at zero
percent excess air
of the resultant
SO2 instead of the
reduced sulfur
monitor. The
monitor must
include an oxygen
monitor for
correcting the data
for excess oxygen.
c. If you use i. Complete either
Equation 1 of 40 item 2.a or item
CFR 2.b; and
60.102a(f)(1)(i) to ii. Either a
set your emission continuous emission
limit. monitoring system
to measure and
record the O2
concentration for
the inlet air/
oxygen supplied to
the system, or a
continuous
parameter
monitoring system
to measure and
record the
volumetric gas flow
rate of ambient air
and purchased
oxygen-enriched
gas.
3. Option 2: TRS limit. Each a. 300 ppmv of total i. Continuous
new or existing sulfur reduced sulfur emission monitoring
recovery unit (Claus or (TRS) compounds, system to measure
other type, regardless of expressed as an and record the
size) not subject to the equivalent SO2 hourly average
NSPS for sulfur oxides in concentration (dry concentration of
40 CFR 60.104(a)(2) or basis) at zero TRS for each
60.102a(f)(1). percent oxygen. exhaust stack; this
monitor must
include an oxygen
monitor for
correcting the data
for excess oxygen;
or
ii. Continuous
parameter
monitoring systems
to measure and
record the
combustion zone
temperature of each
thermal incinerator
and the oxygen
content (percent,
dry basis) in the
vent stream of the
incinerator.
[[Page 75312]]
4. Startup or shutdown Any................. On and after January
option 1: electing to 30, 2019,
comply with Sec. monitoring systems
63.1568(a)(4)(ii). Each new as specified in
or existing sulfur recovery Sec. Sec. 63.670
unit (Claus or other type, and 63.671. Prior
regardless of size) during to January 30,
periods of startup or 2019, either
shutdown. continuous
parameter
monitoring systems
following the
requirements in
Sec. 63.11 (to
detect the presence
of a flame; to
measure and record
the net heating
value of the gas
being combusted;
and to measure and
record the
volumetric flow of
the gas being
combusted) or
monitoring systems
as specified in
Sec. Sec. 63.670
and 63.671.
5. Startup or shutdown Any................. Continuous parameter
option 2: electing to monitoring systems
comply with Sec. to measure and
63.1568(a)(4)(iii). Each record the firebox
new or existing sulfur temperature of each
recovery unit (Claus or thermal incinerator
other type, regardless of or oxidizer and the
size) during periods of oxygen content
startup or shutdown. (percent, dry
basis) in the
exhaust vent from
the incinerator or
oxidizer.
------------------------------------------------------------------------
0
80. Table 32 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1568(b)(2) and (3), you shall meet each
requirement in the following table that applies to you.
Table 32 to Subpart UUU of Part 63--Requirements for Performance Tests for HAP Emissions From Sulfur Recovery
Units Not Subject to the New Source Performance Standards for Sulfur Oxides
----------------------------------------------------------------------------------------------------------------
According to these
For . . . You must . . . Using . . . requirements . . .
----------------------------------------------------------------------------------------------------------------
1. Option 1: Elect NSPS. Each new and a. Measure SO2 Data from continuous Collect SO2 monitoring
existing sulfur recovery unit. concentration (for an emission monitoring data every 15 minutes
oxidation or reduction system. for 24 consecutive
system followed by operating hours.
incineration) or Reduce the data to 1-
measure the hour averages computed
concentration of from four or more data
reduced sulfur (or SO2 points equally spaced
if you use an over each 1-hour
instrument to convert period.
the reduced sulfur to
SO2) for a reduction
control system without
incineration.
b. Measure O2 i. Data from continuous Collect O2 monitoring
concentration for the emission monitoring data every 15 minutes
inlet air/oxygen system; or for 24 consecutive
supplied to the operating hours.
system, if using Reduce the data to 1-
Equation 1 of 40 CFR hour averages computed
60.102a(f)1)(i) to set from four or more data
your emission limit. points equally spaced
You may use either an over each 1-hour
O2 CEMS method in item period; and average
1.b.i of this table or over the 24-hour
the flow monitor in period for input to
item 1.b.ii of this Equation 1 of 40 CFR
table. 60.102a(f)(1)(i).
ii. Data from flow Collect gas flow rate
monitor for ambient monitoring data every
air and purchased 15 minutes for 24
oxygen-enriched gas. consecutive operating
hours. Reduce the data
to 1-hour averages
computed from 4 or
more data points
equally spaced over
each 1-hour period;
calculate the hourly
O2 percent using
Equation 10 of 40 CFR
60.106a(a)(6)(iv); and
average over the 24-
hour period for input
to Equation 1 of 40
CFR 60.102a(f)(1)(i).
2. Option 2: TRS limit, using CEMS. Measure the Data from continuous Collect TRS data every
Each new and existing sulfur concentration of emission monitoring 15 minutes for 24
recovery unit. reduced sulfur (or SO2 system. consecutive operating
if you use an hours. Reduce the data
instrument to convert to 1-hour averages
the reduced sulfur to computed from four or
SO2). more data points
equally spaced over
each 1-hour period.
[[Page 75313]]
3. Option 2: TRS limit, if using a. Select sampling Method 1 or 1A in Sampling sites must be
continuous parameter monitoring port's location and Appendix A-1 to part located at the outlet
systems. Each new and existing the number of traverse 60 of this chapter. of the control device
sulfur recovery unit. ports. and prior to any
releases to the
atmosphere.
b. Determine velocity Method 2, 2A, 2C, 2D, .......................
and volumetric flow or 2F in appendix A-1
rate. to part 60 of this
chapter, or Method 2G
in appendix A-2 to
part 60 of this
chapter, as applicable.
c. Conduct gas Method 3, 3A, or 3B in Take the samples
molecular weight appendix A-2 to part simultaneously with
analysis; obtain the 60 of this chapter, as reduced sulfur or
oxygen concentration applicable. moisture samples.
needed to correct the
emission rate for
excess air.
d. Measure moisture Method 4 in appendix A- Make your sampling time
content of the stack 3 to part 60 of this for each Method 4
gas. chapter. sample equal to that
for 4 Method 15
samples.
e. Measure the Method 15 or 15A in If the cross-sectional
concentration of TRS. appendix A-5 to part area of the duct is
60 of this chapter, as less than 5 square
applicable. meters (m2) or 54
square feet, you must
use the centroid of
the cross section as
the sampling point. If
the cross-sectional
area is 5 m2 or more
and the centroid is
more than 1 meter (m)
from the wall, your
sampling point may be
at a point no closer
to the walls than 1 m
or 39 inches. Your
sampling rate must be
at least 3 liters per
minute or 0.10 cubic
feet per minute to
ensure minimum
residence time for the
sample inside the
sample lines.
f. Calculate the SO2 The arithmetic average .......................
equivalent for each of the SO2 equivalent
run after correcting for each sample during
for moisture and the run.
oxygen.
g. Correct the reduced Equation 1 of Sec. .......................
sulfur samples to zero 63.1568.
percent excess air.
h. Establish each Data from the .......................
operating limit in continuous parameter
Table 30 of this monitoring system.
subpart that applies
to you.
i. Measure thermal Data from the Collect temperature
incinerator: continuous parameter monitoring data every
combustion zone monitoring system. 15 minutes during the
temperature. entire period of the
performance test; and
determine and record
the minimum hourly
average temperature
from all the readings.
j. Measure thermal Data from the Collect oxygen
incinerator: oxygen continuous parameter concentration
concentration monitoring system. (percent, dry basis)
(percent, dry basis) data every 15 minutes
in the vent stream. during the entire
period of the
performance test; and
determine and record
the minimum hourly
average percent excess
oxygen concentration.
----------------------------------------------------------------------------------------------------------------
0
81. Table 33 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1568(b)(5), you shall meet each requirement
in the following table that applies to you.
[[Page 75314]]
Table 33 to Subpart UUU of Part 63--Initial Compliance With HAP Emission
Limits for Sulfur Recovery Units
------------------------------------------------------------------------
You have
For . . . For the following demonstrated initial
emission limit . . . compliance if . . .
------------------------------------------------------------------------
1. Subject to NSPS: Each new a. 250 ppmv (dry You have already
or existing Claus sulfur basis) SO2 at zero conducted a
recovery unit part of a percent excess air, performance test to
sulfur recovery plant with or concentration demonstrate initial
design capacity greater determined using compliance with the
than 20 LTD and subject to Equation 1 of 40 NSPS and each 12-
the NSPS for sulfur oxides CFR hour rolling
in 40 CFR 60.104(a)(2) or 60.102a(f)(1)(i), average
60.102a(f)(1). if you use an concentration of
oxidation or SO2 emissions
reduction control measured by the
system followed by continuous emission
incineration. monitoring system
is less than or
equal to 250 ppmv
(dry basis) at zero
percent excess air,
or the
concentration
determined using
Equation 1 of 40
CFR
60.102a(f)(1)(i).
As part of the
Notification of
Compliance Status,
you must certify
that your vent
meets the SO2
limit. You are not
required to do
another performance
test to demonstrate
initial compliance.
You have already
conducted a
performance
evaluation to
demonstrate initial
compliance with the
applicable
performance
specification. As
part of your
Notification of
Compliance Status,
you must certify
that your
continuous emission
monitoring system
meets the
applicable
requirements in
Sec. 63.1572. You
are not required to
do another
performance
evaluation to
demonstrate initial
compliance.
b. 300 ppmv of You have already
reduced sulfur conducted a
compounds performance test to
calculated as ppmv demonstrate initial
SO2 (dry basis) at compliance with the
zero percent excess NSPS and each 12-
air, or hour rolling
concentration average
determined using concentration of
Equation 1 of 40 reduced sulfur
CFR compounds measured
60.102a(f)(1)(i), by your continuous
if you use a emission monitoring
reduction control system is less than
system without or equal to 300
incineration. ppmv, calculated as
ppmv SO2 (dry
basis) at zero
percent excess air,
or the
concentration
determined using
Equation 1 of 40
CFR
60.102a(f)(1)(i).
As part of the
Notification of
Compliance Status,
you must certify
that your vent
meets the SO2
limit. You are not
required to do
another performance
test to demonstrate
initial compliance.
You have already
conducted a
performance
evaluation to
demonstrate initial
compliance with the
applicable
performance
specification. As
part of your
Notification of
Compliance Status,
you must certify
that your
continuous emission
monitoring system
meets the
applicable
requirements in
Sec. 63.1572. You
are not required to
do another
performance
evaluation to
demonstrate initial
compliance.
2. Option 1: Elect NSPS. a. 250 ppmv (dry Each 12-hour rolling
Each new or existing sulfur basis) of SO2 at average
recovery unit (Claus or zero percent excess concentration of
other type, regardless of air, or SO2 emissions
size) not subject to the concentration measured by the
NSPS for sulfur oxides in determined using continuous emission
40 CFR 60.104(a)(2) or Equation 1 of 40 monitoring system
60.102a(f)(1). CFR during the initial
60.102a(f)(1)(i), performance test is
if you use an less than or equal
oxidation or to 250 ppmv (dry
reduction control basis) at zero
system followed by percent excess air,
incineration. or the
concentration
determined using
Equation 1 of 40
CFR
60.102a(f)(1)(i);
and your
performance
evaluation shows
the monitoring
system meets the
applicable
requirements in
Sec. 63.1572.
b. 300 ppmv of Each 12-hour rolling
reduced sulfur average
compounds concentration of
calculated as ppmv reduced sulfur
SO2 (dry basis) at compounds measured
zero percent excess by the continuous
air, or emission monitoring
concentration system during the
determined using initial performance
Equation 1 of 40 test is less than
CFR or equal to 300
60.102a(f)(1)(i), ppmv, calculated as
if you use a ppmv SO2 (dry
reduction control basis) at zero
system without percent excess air,
incineration. or the
concentration
determined using
Equation 1 of 40
CFR
60.102a(f)(1)(i);
and your
performance
evaluation shows
the continuous
emission monitoring
system meets the
applicable
requirements in
Sec. 63.1572.
[[Page 75315]]
3. Option 2: TRS limit. Each 300 ppmv of TRS If you use
new or existing sulfur compounds expressed continuous
recovery unit (Claus or as an equivalent parameter
other type, regardless of SO2 concentration monitoring systems,
size) not subject to the (dry basis) at zero the average
NSPS for sulfur oxides in percent oxygen. concentration of
40 CFR 60.104(a)(2) or TRS emissions
60.102a(f)(1). measured using
Method 15 during
the initial
performance test is
less than or equal
to 300 ppmv
expressed as
equivalent SO2
concentration (dry
basis) at zero
percent oxygen. If
you use a
continuous emission
monitoring system,
each 12-hour
rolling average
concentration of
TRS emissions
measured by the
continuous emission
monitoring system
during the initial
performance test is
less than or equal
to 300 ppmv
expressed as an
equivalent SO2 (dry
basis) at zero
percent oxygen; and
your performance
evaluation shows
the continuous
emission monitoring
system meets the
applicable
requirements in
Sec. 63.1572.
------------------------------------------------------------------------
0
82. Table 34 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1568(c)(1), you shall meet each requirement
in the following table that applies to you.
Table 34 to Subpart UUU of Part 63--Continuous Compliance With HAP
Emission Limits for Sulfur Recovery Units
------------------------------------------------------------------------
You shall
For this emission demonstrate
For . . . limit . . . continuous
compliance by . . .
------------------------------------------------------------------------
1. Subject to NSPS. Each new a. 250 ppmv (dry Collecting the
or existing Claus sulfur basis) of SO2 at hourly average SO2
recovery unit part of a zero percent excess monitoring data
sulfur recovery plant with air, or (dry basis, percent
design capacity greater concentration excess air) and, if
than 20 LTD and subject to determined using using Equation 1 of
the NSPS for sulfur oxides Equation 1 of 40 40 CFR
in 40 CFR 60.104(a)(2) or CFR 60.102a(f)(1)(i),
60.102a(f)(1). 60.102a(f)(1)(i), collecting the
if you use an hourly O2
oxidation or concentration or
reduction control flow monitoring
system followed by data according to
incineration. Sec. 63.1572;
determining and
recording each 12-
hour rolling
average
concentration of
SO2; maintaining
each 12-hour
rolling average
concentration of
SO2 at or below the
applicable emission
limitation; and
reporting any 12-
hour rolling
average
concentration of
SO2 greater than
the applicable
emission limitation
in the semiannual
compliance report
required by Sec.
63.1575.
b. 300 ppmv of Collecting the
reduced sulfur hourly average
compounds reduced sulfur (and
calculated as ppmv air or O2 dilution
SO2 (dry basis) at and oxidation)
zero percent excess monitoring data
air, or and, if using
concentration Equation 1 of 40
determined using CFR
Equation 1 of 40 60.102a(f)(1)(i),
CFR collecting the
60.102a(f)(1)(i), hourly O2
if you use a concentration or
reduction control flow monitoring
system without data according to
incineration. Sec. 63.1572;
determining and
recording each 12-
hour rolling
average
concentration of
reduced sulfur;
maintaining each 12-
hour rolling
average
concentration of
reduced sulfur at
or below the
applicable emission
limitation; and
reporting any 12-
hour rolling
average
concentration of
reduced sulfur
greater than the
applicable emission
limitation in the
semiannual
compliance report
required by Sec.
63.1575.
[[Page 75316]]
2. Option 1: Elect NSPS. a. 250 ppmv (dry Collecting the
Each new or existing sulfur basis) of SO2 at hourly average SO2
recovery unit (Claus or zero percent excess data (dry basis,
other type, regardless of air, or percent excess air)
size) not subject to the concentration and, if using
NSPS for sulfur oxides in determined using Equation 1 of 40
40 CFR 60.104(a)(2) or Equation 1 of 40 CFR
60.102a(f)(1). CFR 60.102a(f)(1)(i),
60.102a(f)(1)(i), collecting the
if you use an hourly O2
oxidation or concentration or
reduction control flow monitoring
system followed by data according to
incineration. Sec. 63.1572;
determining and
recording each 12-
hour rolling
average
concentration of
SO2; maintaining
each 12-hour
rolling average
concentration of
SO2 at or below the
applicable emission
limitation; and
reporting any 12-
hour rolling
average
concentration of
SO2 greater than
the applicable
emission limitation
in the semiannual
compliance report
required by Sec.
63.1575.
b. 300 ppmv of Collecting the
reduced sulfur hourly average
compounds reduced sulfur (and
calculated as ppmv air or O2 dilution
SO2 (dry basis) at and oxidation)
zero percent excess monitoring data
air, or and, if using
concentration Equation 1 of 40
determined using CFR
Equation 1 of 40 60.102a(f)(1)(i),
CFR collecting the
60.102a(f)(1)(i), hourly O2
if you use a concentration or
reduction control flow monitoring
system without data according to
incineration. Sec. 63.1572;
determining and
recording each 12-
hour rolling
average
concentration of
reduced sulfur;
maintaining each 12-
hour rolling
average
concentration of
reduced sulfur at
or below the
applicable emission
limitation; and
reporting any 12-
hour rolling
average
concentration of
reduced sulfur
greater than the
applicable emission
limitation in the
semiannual
compliance report
required by Sec.
63.1575.
3. Option 2: TRS limit. Each 300 ppmv of TRS i. If you use
new or existing sulfur compounds, continuous
recovery unit (Claus or expressed as an SO2 parameter
other type, regardless of concentration (dry monitoring systems,
size) not subject to the basis) at zero collecting the
NSPS for sulfur oxides in percent oxygen or hourly average TRS
40 CFR 60.104(a)(2) or reduced sulfur monitoring data
60.102a(f)(1). compounds according to Sec.
calculated as ppmv 63.1572 and
SO2 (dry basis) at maintaining each 12-
zero percent excess hour average
air. concentration of
TRS at or below the
applicable emission
limitation; or
ii. If you use a
continuous emission
monitoring system,
collecting the
hourly average TRS
monitoring data
according to Sec.
63.1572,
determining and
recording each 12-
hour rolling
average
concentration of
TRS; maintaining
each 12-hour
rolling average
concentration of
TRS at or below the
applicable emission
limitation; and
reporting any 12-
hour rolling
average TRS
concentration
greater than the
applicable emission
limitation in the
semiannual
compliance report
required by Sec.
63.1575.
------------------------------------------------------------------------
0
83. Table 35 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1568(c)(1), you shall meet each requirement
in the following table that applies to you.
Table 35 to Subpart UUU of Part 63--Continuous Compliance With Operating
Limits for HAP Emissions From Sulfur Recovery Units
------------------------------------------------------------------------
You shall
For this operating demonstrate
For . . . limit . . . continuous
compliance by . . .
------------------------------------------------------------------------
1. Subject to NSPS. Each new Not applicable...... Meeting the
or existing Claus sulfur requirements of
recovery unit part of a Table 34 of this
sulfur recovery plant with subpart.
design capacity greater
than 20 LTD and subject to
the NSPS for sulfur oxides
in 40 CFR 60.104(a)(2) or
60.102a(f)(1).
[[Page 75317]]
2. Option 1: Elect NSPS. Not applicable...... Meeting the
Each new or existing sulfur requirements of
recovery unit (Claus or Table 34 of this
other type, regardless of subpart.
size) not subject to the
NSPS for sulfur oxides in
40 CFR 60.104(a)(2) or
60.102a(f)(1).
3. Option 2: TRS limit. Each a. Maintain the Collecting the
new or existing sulfur daily average hourly and daily
recovery unit (Claus or combustion zone average temperature
other type, regardless of temperature above monitoring data
size) not subject to the the level according to Sec.
NSPS for sulfur oxides in established during 63.1572; and
40 CFR 60.104(a)(2) or the performance maintaining the
60.102a(f)(1). test. daily average
combustion zone
temperature at or
above the limit
established during
the performance
test
b. The daily average Collecting the
oxygen hourly and daily
concentration in average O2
the vent stream monitoring data
(percent, dry according to Sec.
basis) must not 63.1572; and
fall below the maintaining the
level established average O2
during the concentration above
performance test.. the level
established during
the performance
test.
4. Startup or shutdown Using a flare On and after January
option 1: Electing to meeting the 30, 2019, complying
comply with Sec. requirements in with the applicable
63.1568(a)(4)(ii). Each new Sec. 63.11(b) or requirements of
or existing sulfur recovery Sec. 63.670. Sec. 63.670.
unit (Claus or other type, Prior to January
regardless of size) during 30, 2019, complying
periods of startup or with the applicable
shutdown. requirements of
either Sec.
63.11(b) or Sec.
63.670.
5. Startup or shutdown a. Minimum hourly Collecting
option 2: Electing to average temperature continuous (at
comply with Sec. of 1,200 degrees least once every 15
63.1568(a)(4)(iii). Each Fahrenheit. minutes) and hourly
new or existing sulfur average temperature
recovery unit (Claus or monitoring data
other type, regardless of according to Sec.
size) during periods of 63.1572; and
startup or shutdown. maintaining the
daily average
firebox temperature
at or above 1,200
degrees Fahrenheit.
b. Minimum hourly Collecting
average outlet continuous (at
oxygen least once every 15
concentration of 2 minutes) and hourly
volume percent (dry average O2
basis). monitoring data
according to Sec.
63.1572; and
maintaining the
average O2
concentration at or
above 2 volume
percent (dry
basis).
------------------------------------------------------------------------
0
84. Table 40 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1572(a)(1) and (b)(1), you shall meet each
requirement in the following table that applies to you.
Table 40 to Subpart UUU of Part 63--Requirements for Installation,
Operation, and Maintenance of Continuous Opacity Monitoring Systems and
Continuous Emission Monitoring Systems
------------------------------------------------------------------------
This type of continuous opacity or Must meet these requirements .
emission monitoring system . . . . .
------------------------------------------------------------------------
1. Continuous opacity monitoring system Performance specification 1 (40
CFR part 60, appendix B).
2. PM CEMS; this monitor must include The requirements in 40 CFR
an O2 monitor for correcting the data 60.105a(d).
for excess air.
3. CO continuous emission monitoring Performance specification 4 (40
system. CFR part 60, appendix B); span
value of 1,000 ppm; and
procedure 1 (40 CFR part 60,
appendix F) except relative
accuracy test audits are
required annually instead of
quarterly.
4. CO continuous emission monitoring Performance specification 4 (40
system used to demonstrate emissions CFR part 60, appendix B); and
average under 50 ppm (dry basis). span value of 100 ppm.
5. SO2 continuous emission monitoring Performance specification 2 (40
system for sulfur recovery unit with CFR part 60, appendix B); span
oxidation control system or reduction value of 500 ppm SO2, or if
control system; this monitor must using Equation 1 of 40 CFR
include an O2 monitor for correcting 60.102a(f)(1)(i), span value
the data for excess air. of two times the limit at the
highest O2 concentration; use
Methods 6 or 6C (40 CFR part
60, appendix A-4) for
certifying the SO2 monitor and
Methods 3A or 3B (40 CFR part
60, appendix A-2) for
certifying the O2 monitor; and
procedure 1 (40 CFR part 60,
appendix F) except relative
accuracy test audits are
required annually instead of
quarterly.
[[Page 75318]]
6. Reduced sulfur and O2 continuous Performance specification 5 (40
emission monitoring system for sulfur CFR part 60, appendix B),
recovery unit with reduction control except calibration drift
system not followed by incineration; specification is 2.5 percent
this monitor must include an O2 of the span value instead of 5
monitor for correcting the data for percent; span value is 450 ppm
excess air unless exempted. reduced sulfur, or if using
Equation 1 of 40 CFR
60.102a(f)(1)(i), span value
of two times the limit at the
highest O2 concentration; use
Methods 15 or 15A (40 CFR part
60, appendix A-5) for
certifying the reduced sulfur
monitor and Methods 3A or 3B
(40 CFR part 60, appendix A-2)
for certifying the O2 monitor;
if Method 3A or 3B yields O2
concentrations below 0.25
percent during the performance
evaluation, the O2
concentration can be assumed
to be zero and the O2 monitor
is not required; and procedure
1 (40 CFR part 60, appendix
F), except relative accuracy
test audits, are required
annually instead of quarterly.
7. Instrument with an air or O2 Performance specification 5 (40
dilution and oxidation system to CFR part 60, appendix B); span
convert reduced sulfur to SO2 for value of 375 ppm SO2 or if
continuously monitoring the using Equation 1 of 40 CFR
concentration of SO2 instead of 60.102a(f)(1)(i), span value
reduced sulfur monitor and O2 monitor. of two times the limit at the
highest O2 concentration; use
Methods 15 or 15A (40 CFR part
60, appendix A-5) for
certifying the reduced sulfur
monitor and 3A or 3B (40 CFR
part 60, appendix A-2) for
certifying the O2 monitor; and
procedure 1 (40 CFR part 60,
appendix F), except relative
accuracy test audits, are
required annually instead of
quarterly.
8. TRS continuous emission monitoring Performance specification 5 (40
system for sulfur recovery unit; this CFR part 60, appendix B).
monitor must include an O2 monitor for
correcting the data for excess air.
9. O2 monitor for oxygen concentration. If necessary due to
interferences, locate the
oxygen sensor prior to the
introduction of any outside
gas stream; performance
specification 3 (40 CFR part
60, appendix B; and procedure
1 (40 CFR part 60, appendix
F), except relative accuracy
test audits, are required
annually instead of quarterly.
------------------------------------------------------------------------
0
85. Table 41 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1572(c)(1), you shall meet each requirement
in the following table that applies to you.
Table 41 to Subpart UUU of Part 63--Requirements for Installation,
Operation, and Maintenance of Continuous Parameter Monitoring Systems
------------------------------------------------------------------------
If you use . . . You shall . . .
------------------------------------------------------------------------
1. pH strips............... Use pH strips with an accuracy of 10 percent.
2. pH meter................ Locate the pH sensor in a position that
provides a representative measurement of
pH; ensure the sample is properly mixed
and representative of the fluid to be
measured.
Use a pH sensor with an accuracy of at
least 0.2 pH units.
Check the pH meter's calibration on at
least one point at least once daily; check
the pH meter's calibration on at least two
points at least once quarterly; at least
monthly, inspect all components for
integrity and all electrical components
for continuity; record the results of each
calibration check and inspection.
3. Colormetric tube Use a colormetric tube sampling system with
sampling system. a printed numerical scale in ppmv, a
standard measurement range of 1 to 10 ppmv
(or 1 to 30 ppmv if applicable), and a
standard deviation for measured values of
no more than 15 percent.
System must include a gas detection pump
and hot air probe if needed for the
measurement range.
4. CO2, O2, and CO monitors a. Locate the concentration sensor so that
for coke burn-off rate. it provides a representative measurement
of the content of the exit gas stream;
ensure the sample is properly mixed and
representative of the gas to be measured.
Use a sensor with an accuracy of at least
1 percent of the range of the
sensor or to a nominal gas concentration
of 0.5 percent, whichever is
greater.
Use a monitor that is able to measure
concentration on a dry basis or is able to
correct for moisture content and record on
a dry basis.
Conduct calibration checks at least
annually; conduct calibration checks
following any period of more than 24 hours
throughout which the sensor reading
exceeds the manufacturer's specified
maximum operating range or install a new
sensor; at least quarterly, inspect all
components for integrity and all
electrical connections for continuity;
record the results of each calibration and
inspection.
b. As an alternative, the requirements in
40 CFR 60.105a(b)(2) may be used.
5. BLD..................... Follow the requirements in 40 CFR
60.105a(c).
6. Voltage, secondary Use meters with an accuracy of at least
current, or total power 5 percent over the operating
input sensors. range.
[[Page 75319]]
Each time that the unit is not operating,
confirm that the meters read zero. Conduct
a calibration check at least annually;
conduct calibration checks following any
period of more than 24 hours throughout
which the meter reading exceeds the
manufacturer's specified maximum operating
range; at least monthly, inspect all
components of the continuous parameter
monitoring system for integrity and all
electrical connections for continuity;
record the results of each calibration
check and inspection.
7. Pressure/Pressure Locate the pressure sensor(s) in a position
drop\1\ sensors. that provides a representative measurement
of the pressure and minimizes or
eliminates pulsating pressure, vibration,
and internal and external corrosion.
Use a gauge with an accuracy of at least
5 percent over the normal
operating range or 0.12 kilopascals (0.5
inches of water column), whichever is
greater.
Review pressure sensor readings at least
once a week for straightline (unchanging)
pressure and perform corrective action to
ensure proper pressure sensor operation if
blockage is indicated; using an instrument
recommended by the sensor's manufacturer,
check gauge calibration and transducer
calibration annually; conduct calibration
checks following any period of more than
24 hours throughout which the pressure
exceeded the manufacturer's specified
maximum rated pressure or install a new
pressure sensor; at least quarterly,
inspect all components for integrity, all
electrical connections for continuity, and
all mechanical connections for leakage,
unless the CPMS has a redundant pressure
sensor; record the results of each
calibration check and inspection.
8. Air flow rate, gas flow Locate the flow sensor(s) and other
rate, or total water (or necessary equipment (such as straightening
scrubbing liquid) flow vanes) in a position that provides
rate sensors. representative flow; reduce swirling flow
or abnormal velocity distributions due to
upstream and downstream disturbances. If
you elect to comply with Option 3 (Ni lb/
hr) or Option 4 (Ni lb/1,000 lb of coke
burn-off) for the HAP metal emission
limitations in Sec. 63.1564, install the
continuous parameter monitoring system for
gas flow rate as close as practical to the
continuous opacity monitoring system; and
if you don't use a continuous opacity
monitoring system, install the continuous
parameter monitoring system for gas flow
rate as close as practical to the control
device.
Use a flow rate sensor with an accuracy of
at least 5 percent over the
normal range of flow measured, or 1.9
liter per minute (0.5 gallons per minute),
whichever is greater, for liquid flow.
Use a flow rate sensor with an accuracy of
at least 5 percent over the
normal range of flow measured, or 280
liters per minute (10 cubic feet per
minute), whichever is greater, for gas
flow.
Conduct a flow sensor calibration check at
least biennially (every two years);
conduct a calibration check following any
period of more than 24 hours throughout
which the flow rate exceeded the
manufacturer's specified maximum rated
flow rate or install a new flow sensor; at
least quarterly, inspect all components
for leakage, unless the CPMS has a
redundant flow sensor; record the results
of each calibration check and inspection.
9. Temperature sensors..... Locate the temperature sensor in the
combustion zone, or in the ductwork
immediately downstream of the combustion
zone before any substantial heat exchange
occurs or in the ductwork immediately
downstream of the regenerator; locate the
temperature sensor in a position that
provides a representative temperature;
shield the temperature sensor system from
electromagnetic interference and chemical
contaminants.
Use a temperature sensor with an accuracy
of at least 1 percent over the
normal range of temperature measured,
expressed in degrees Celsius (C), or 2.8
degrees C, whichever is greater.
Conduct calibration checks at least
annually; conduct calibration checks
following any period of more than 24 hours
throughout which the temperature exceeded
the manufacturer's specified maximum rated
temperature or install a new temperature
sensor; at least quarterly, inspect all
components for integrity and all
electrical connections for continuity,
oxidation, and galvanic corrosion, unless
the CPMS has a redundant temperature
sensor; record the results of each
calibration check and inspection.
10. Oxygen content sensors Locate the oxygen sensor so that it
\2\. provides a representative measurement of
the oxygen content of the exit gas stream;
ensure the sample is properly mixed and
representative of the gas to be measured.
Use an oxygen sensor with an accuracy of at
least 1 percent of the range
of the sensor or to a nominal gas
concentration of 0.5 percent,
whichever is greater.
Conduct calibration checks at least
annually; conduct calibration checks
following any period of more than 24 hours
throughout which the sensor reading
exceeds the manufacturer's specified
maximum operating range or install a new
oxygen sensor; at least quarterly, inspect
all components for integrity and all
electrical connections for continuity;
record the results of each calibration and
inspection.
------------------------------------------------------------------------
\1\ Not applicable to non-venturi wet scrubbers of the jet-ejector
design.
\2\ This does not replace the requirements for oxygen monitors that are
required to use continuous emissions monitoring systems. The
requirements in this table apply to oxygen sensors that are continuous
parameter monitors, such as those that monitor combustion zone oxygen
concentration and regenerator exit oxygen concentration.
0
86. Table 43 to subpart UUU is revised to read as follows:
As stated in Sec. 63.1575(a), you shall meet each requirement in
the following table that applies to you.
[[Page 75320]]
Table 43 to Subpart UUU of Part 63--Requirements for Reports
------------------------------------------------------------------------
You shall submit
You must submit . . . The report must the report . . .
contain . . .
------------------------------------------------------------------------
1. A compliance report........ If there are no Semiannually
deviations from any according to
emission limitation the
or work practice requirements in
standard that applies Sec.
to you, a statement 63.1575(b).
that there were no
deviations from the
standards during the
reporting period and
that no continuous
opacity monitoring
system or continuous
emission monitoring
system was
inoperative,
inactive, out-of-
control, repaired, or
adjusted; if you have
a deviation from any
emission limitation
or work practice
standard during the
reporting period, the
report must contain
the information in
Sec. 63.1575(c)
through (e).
2. Performance test and CEMS On and after January Within 60 days
performance evaluation data. 30, 2019, the after the date
information specified of completing
in Sec. each test
63.1575(k)(1). according to
the
requirements in
Sec.
63.1575(k).
------------------------------------------------------------------------
0
87. Table 44 to subpart UUU of part 63 is revised to read as follows:
As stated in Sec. 63.1577, you shall meet each requirement in the
following table that applies to you.
Table 44 to Subpart UUU of Part 63--Applicability of NESHAP General Provisions to Subpart UUU
----------------------------------------------------------------------------------------------------------------
Applies to subpart
Citation Subject UUU Explanation
----------------------------------------------------------------------------------------------------------------
Sec. 63.1(a)(1)-(4)............. General Applicability..... Yes.................. .........................
Sec. 63.1(a)(5)................. [Reserved]................ Not applicable....... .........................
Sec. 63.1(a)(6)................. .......................... Yes.................. Except the correct mail
drop (MD) number is C404-
04.
Sec. 63.1(a)(7)-(9)............. [Reserved]................ Not applicable....... .........................
Sec. 63.1(a)(10)-(12)........... .......................... Yes.................. Except that this subpart
specifies calendar or
operating day.
Sec. 63.1(b)(1)................. Initial Applicability Yes.................. .........................
Determination for this
part.
Sec. 63.1(b)(2)................. [Reserved]................ Not applicable....... .........................
Sec. 63.1(b)(3)................. .......................... Yes.................. .........................
Sec. 63.1(c)(1)................. Applicability of this part Yes.................. .........................
after a Relevant Standard
has been set under this
part.
Sec. 63.1(c)(2)................. .......................... No................... Area sources are not
subject to this subpart.
Sec. 63.1(c)(3)-(4)............. [Reserved]................ Not applicable....... .........................
Sec. 63.1(c)(5)................. .......................... Yes.................. .........................
Sec. 63.1(d).................... [Reserved]................ Not applicable....... .........................
Sec. 63.1(e).................... Applicability of Permit Yes.................. .........................
Program.
Sec. 63.2....................... Definitions............... Yes.................. Sec. 63.1579 specifies
that if the same term is
defined in subparts A
and UUU of this part, it
shall have the meaning
given in this subpart.
Sec. 63.3....................... Units and Abbreviations... Yes.................. .........................
Sec. 63.4(a)(1)-(2)............. Prohibited Activities..... Yes.................. .........................
Sec. 63.4(a)(3)-(5)............. [Reserved]................ Not applicable....... .........................
Sec. 63.4(b)-(c)................ Circumvention and Yes.................. .........................
Fragmentation.
Sec. 63.5(a).................... Construction and Yes.................. .........................
Reconstruction.
Sec. 63.5(b)(1)................. .......................... Yes.................. .........................
Sec. 63.5(b)(2)................. [Reserved]................ Not applicable....... .........................
Sec. 63.5(b)(3)-(4)............. .......................... Yes.................. In Sec. 63.5(b)(4),
replace the reference to
Sec. 63.9(b) with Sec.
63.9(b)(4) and (5).
Sec. 63.5(b)(5)................. [Reserved]................ Not applicable....... .........................
Sec. 63.5(b)(6)................. .......................... Yes.................. .........................
Sec. 63.5(c).................... [Reserved]................ Not applicable....... .........................
Sec. 63.5(d)(1)(i).............. Application for Approval Yes.................. Except this subpart
of Construction or specifies the
Reconstruction--General application is submitted
Application Requirements. as soon as practicable
before startup but not
later than 90 days after
the promulgation date if
construction or
reconstruction had
commenced and initial
startup had not occurred
before promulgation.
[[Page 75321]]
Sec. 63.5(d)(1)(ii)............. .......................... Yes.................. Except that emission
estimates specified in
Sec. 63.5(d)(1)(ii)(H)
are not required, and
Sec. 63.5(d)(1)(ii)(G)
and (I) are Reserved and
do not apply.
Sec. 63.5(d)(1)(iii)............ .......................... No................... This subpart specifies
submission of
notification of
compliance status.
Sec. 63.5(d)(2)................. .......................... Yes.................. .........................
Sec. 63.5(d)(3)................. .......................... Yes.................. .........................
Sec. 63.5(d)(4)................. .......................... Yes.................. .........................
Sec. 63.5(e).................... Approval of Construction Yes.................. .........................
or Reconstruction.
Sec. 63.5(f)(1)................. Approval of Construction Yes.................. .........................
or Reconstruction Based
on State Review.
Sec. 63.5(f)(2)................. .......................... Yes.................. Except that the cross-
reference to Sec.
63.9(b)(2) does not
apply.
Sec. 63.6(a).................... Compliance with Standards Yes.................. .........................
and Maintenance--
Applicability.
Sec. 63.6(b)(1)-(4)............. Compliance Dates for New Yes.................. .........................
and Reconstructed Sources.
Sec. 63.6(b)(5)................. .......................... Yes.................. Except that this subpart
specifies different
compliance dates for
sources.
Sec. 63.6(b)(6)................. [Reserved]................ Not applicable....... .........................
Sec. 63.6(b)(7)................. Compliance Dates for New Yes.................. .........................
and Reconstructed Area
Sources That Become Major.
Sec. 63.6(c)(1)-(2)............. Compliance Dates for Yes.................. Except that this subpart
Existing Sources. specifies different
compliance dates for
sources subject to Tier
II gasoline sulfur
control requirements.
Sec. 63.6(c)(3)-(4)............. [Reserved]................ Not applicable....... .........................
Sec. 63.6(c)(5)................. Compliance Dates for Yes.................. .........................
Existing Area Sources
That Become Major.
Sec. 63.6(d).................... [Reserved]................ Not applicable....... .........................
Sec. 63.6(e)(1)(i).............. General Duty to Minimize No................... See Sec. 63.1570(c) for
Emissions. general duty
requirement.
Sec. 63.6(e)(1)(ii)............. Requirement to Correct No................... .........................
Malfunctions as Soon as
Possible.
Sec. 63.6(e)(1)(iii)............ Compliance with Standards Yes.................. .........................
and Maintenance
Requirements.
Sec. 63.6(e)(2)................. [Reserved]................ Not Applicable....... .........................
Sec. 63.6(e)(3)(i).............. Startup, Shutdown, and No................... .........................
Malfunction Plan
Requirements.
Sec. 63.6(e)(3)(ii)............. [Reserved]................ Not applicable....... .........................
Sec. 63.6(e)(3)(iii)-(ix)....... .......................... No................... .........................
Sec. 63.6(f)(1)................. SSM Exemption............. No................... .........................
Sec. 63.6(f)(2)(i)-(iii)(C)..... Compliance with Standards Yes.................. .........................
and Maintenance
Requirements.
Sec. 63.6(f)(2)(iii)(D)......... .......................... Yes.................. .........................
Sec. 63.6(f)(2)(iv)-(v)......... .......................... Yes.................. .........................
Sec. 63.6(f)(3)................. .......................... Yes.................. Except the cross-
references to Sec.
63.6(f)(1) and (e)(1)(i)
are changed to Sec.
63.1570(c).
Sec. 63.6(g).................... Alternative Standard...... Yes.................. .........................
Sec. 63.6(h)(1)................. SSM Exemption for Opacity/ No................... .........................
VE Standards.
Sec. 63.6(h)(2)(i).............. Determining Compliance No................... This subpart specifies
with Opacity/VE Standards. methods.
Sec. 63.6(h)(2)(ii)............. [Reserved]................ Not applicable....... .........................
Sec. 63.6(h)(2)(iii)............ .......................... Yes.................. .........................
Sec. 63.6(h)(3)................. [Reserved]................ Not applicable....... .........................
Sec. 63.6(h)(4)................. Notification of Opacity/VE Yes.................. Applies to Method 22 (40
Observation Date. CFR part 60, appendix A-
7) tests.
Sec. 63.6(h)(5)................. Conducting Opacity/VE No................... .........................
Observations.
Sec. 63.6(h)(6)................. Records of Conditions Yes.................. Applies to Method 22 (40
During Opacity/VE CFR part 60, appendix A-
Observations. 7) observations.
Sec. 63.6(h)(7)(i).............. Report COM Monitoring Data Yes.................. .........................
from Performance Test.
Sec. 63.6(h)(7)(ii)............. Using COM Instead of No................... .........................
Method 9.
[[Page 75322]]
Sec. 63.6(h)(7)(iii)............ Averaging Time for COM Yes.................. .........................
during Performance Test.
Sec. 63.6(h)(7)(iv)............. COM Requirements.......... Yes.................. .........................
Sec. 63.6(h)(7)(v).............. COMS Results and Visual Yes.................. .........................
Observations.
Sec. 63.6(h)(8)................. Determining Compliance Yes.................. .........................
with Opacity/VE Standards.
Sec. 63.6(h)(9)................. Adjusted Opacity Standard. Yes.................. .........................
Sec. 63.6(i)(1)-(14)............ Extension of Compliance... Yes.................. Extension of compliance
under Sec. 63.6(i)(4)
not applicable to a
facility that installs
catalytic cracking feed
hydrotreating and
receives an extended
compliance date under
Sec. 63.1563(c).
Sec. 63.6(i)(15)................ [Reserved]................ Not applicable....... .........................
Sec. 63.6(i)(16)................ .......................... Yes.................. .........................
Sec. 63.6(j).................... Presidential Compliance Yes.................. .........................
Exemption.
Sec. 63.7(a)(1)................. Performance Test Yes.................. Except that this subpart
Requirements specifies the applicable
Applicability. test and demonstration
procedures.
Sec. 63.7(a)(2)................. Performance Test Dates.... Yes.................. Except test results must
be submitted in the
Notification of
Compliance Status report
due 150 days after the
compliance date.
Sec. 63.7(a)(3)................. Section 114 Authority..... Yes.................. .........................
Sec. 63.7(a)(4)................. Force Majeure............. Yes.................. .........................
Sec. 63.7(b).................... Notifications............. Yes.................. Except that this subpart
specifies notification
at least 30 days prior
to the scheduled test
date rather than 60
days.
Sec. 63.7(c).................... Quality Assurance Program/ Yes.................. Except that when this
Site-Specific Test Plan. subpart specifies to use
40 CFR part 60, appendix
F, out of control
periods are to be
defined as specified in
part 60, appendix F.
Sec. 63.7(d).................... Performance Test Yes.................. .........................
Facilities.
Sec. 63.7(e)(1)................. Performance Testing....... No................... See Sec. 63.1571(b)(1).
Sec. 63.7(e)(2)-(4)............. Conduct of Tests.......... Yes.................. .........................
Sec. 63.7(f).................... Alternative Test Method... Yes.................. .........................
Sec. 63.7(g).................... Data Analysis, Yes.................. Except performance test
Recordkeeping, Reporting. reports must be
submitted with
notification of
compliance status due
150 days after the
compliance date, and
Sec. 63.7(g)(2) is
reserved and does not
apply.
Sec. 63.7(h).................... Waiver of Tests........... Yes.................. .........................
Sec. 63.8(a)(1)................. Monitoring Requirements- Yes.................. .........................
Applicability.
Sec. 63.8(a)(2)................. Performance Specifications Yes.................. .........................
Sec. 63.8(a)(3)................. [Reserved]................ Not applicable....... .........................
Sec. 63.8(a)(4)................. Monitoring with Flares.... Yes.................. Except that for a flare
complying with Sec.
63.670, the cross-
reference to Sec.
63.11 in this paragraph
does not include Sec.
63.11(b).
Sec. 63.8(b)(1)................. Conduct of Monitoring..... Yes.................. .........................
Sec. 63.8(b)(2)-(3)............. Multiple Effluents and Yes.................. This subpart specifies
Multiple Monitoring the required monitoring
Systems. locations.
Sec. 63.8(c)(1)................. Monitoring System Yes.................. .........................
Operation and Maintenance.
Sec. 63.8(c)(1)(i).............. General Duty to Minimize No................... See Sec. 63.1570(c).
Emissions and CMS
Operation.
Sec. 63.8(c)(1)(ii)............. Keep Necessary Parts for Yes.................. .........................
CMS.
Sec. 63.8(c)(1)(iii)............ Requirement to Develop SSM No................... .........................
Plan for CMS.
[[Page 75323]]
Sec. 63.8(c)(2)-(3)............. Monitoring System Yes.................. Except that this subpart
Installation. specifies that for
continuous parameter
monitoring systems,
operational status
verification includes
completion of
manufacturer written
specifications or
installation, operation,
and calibration of the
system or other written
procedures that provide
adequate assurance that
the equipment will
monitor accurately.
Sec. 63.8(c)(4)................. Continuous Monitoring Yes.................. .........................
System Requirements.
Sec. 63.8(c)(5)................. COMS Minimum Procedures... Yes.................. .........................
Sec. 63.8(c)(6)................. CMS Requirements.......... Yes.................. .........................
Sec. 63.8(c)(7)-(8)............. CMS Requirements.......... Yes.................. .........................
Sec. 63.8(d)(1)-(2)............. Quality Control Program Yes.................. .........................
for CMS.
Sec. 63.8(d)(3)................. Written Procedures for CMS No................... .........................
Sec. 63.8(e).................... CMS Performance Evaluation Yes.................. Except that results are
to be submitted as part
of the Notification
Compliance Status due
150 days after the
compliance date.
Sec. 63.8(f)(1)-(5)............. Alternative Monitoring Yes.................. Except that this subpart
Methods. specifies procedures for
requesting alternative
monitoring systems and
alternative parameters.
Sec. 63.8(f)(6)................. Alternative to Relative Yes.................. Applicable to continuous
Accuracy Test. emission monitoring
systems if performance
specification requires a
relative accuracy test
audit.
Sec. 63.8(g)(1)-(4)............. Reduction of Monitoring Yes.................. Applies to continuous
Data. opacity monitoring
system or continuous
emission monitoring
system.
Sec. 63.8(g)(5)................. Data Reduction............ No................... This subpart specifies
requirements.
Sec. 63.9(a).................... Notification Requirements-- Yes.................. Duplicate Notification of
Applicability. Compliance Status report
to the Regional
Administrator may be
required.
Sec. 63.9(b)(1)-(2)............. Initial Notifications..... Yes.................. Except that notification
of construction or
reconstruction is to be
submitted as soon as
practicable before
startup but no later
than 30 days after the
effective date if
construction or
reconstruction had
commenced but startup
had not occurred before
the effective date.
Sec. 63.9(b)(3)................. [Reserved]................ Not applicable....... .........................
Sec. 63.9(b)(4)-(5)............. Initial Notification Yes.................. Except Sec.
Information. 63.9(b)(4)(ii)-(iv),
which are reserved and
do not apply.
Sec. 63.9(c).................... Request for Extension of Yes.................. .........................
Compliance.
Sec. 63.9(d).................... New Source Notification Yes.................. .........................
for Special Compliance
Requirements.
Sec. 63.9(e).................... Notification of Yes.................. Except that notification
Performance Test. is required at least 30
days before test.
Sec. 63.9(f).................... Notification of VE/Opacity Yes.................. .........................
Test.
Sec. 63.9(g).................... Additional Notification Yes.................. .........................
Requirements for Sources
with Continuous
Monitoring Systems.
Sec. 63.9(h).................... Notification of Compliance Yes.................. Except that this subpart
Status. specifies the
notification is due no
later than 150 days
after compliance date,
and except that the
reference to Sec.
63.5(d)(1)(ii)(H) in
Sec. 63.9(h)(5) does
not apply.
Sec. 63.9(i).................... Adjustment of Deadlines... Yes.................. .........................
Sec. 63.9(j).................... Change in Previous Yes.................. .........................
Information.
63.10(a).......................... Recordkeeping and Yes.................. .........................
Reporting Applicability.
Sec. 63.10(b)(1)................ General Recordkeeping Yes.................. .........................
Requirements.
[[Page 75324]]
Sec. 63.10(b)(2)(i)............. Recordkeeping of No................... .........................
Occurrence and Duration
of Startups and Shutdowns.
Sec. 63.10(b)(2)(ii)............ Recordkeeping of No................... See Sec. 63.1576(a)(2)
Malfunctions. for recordkeeping of (1)
date, time and duration;
(2) listing of affected
source or equipment, and
an estimate of the
volume of each regulated
pollutant emitted over
the standard; and (3)
actions taken to
minimize emissions and
correct the failure.
Sec. 63.10(b)(2)(iii)........... Maintenance Records....... Yes.................. .........................
Sec. 63.10(b)(2)(iv)-(v)........ Actions Taken to Minimize No................... .........................
Emissions During SSM.
Sec. 63.10(b)(2)(vi)............ Recordkeeping for CMS Yes.................. .........................
Malfunctions.
Sec. 63.10(b)(2)(vii)-(xiv)..... Other CMS Requirements.... Yes.................. .........................
Sec. 63.10(b)(3)................ Recordkeeping for Yes.................. .........................
Applicability
Determinations..
Sec. 63.10(c)(1)-(6)............ Additional Records for Yes.................. Except Sec. 63.10(c)(2)-
Continuous Monitoring (4), which are Reserved
Systems. and do not apply.
Sec. 63.10(c)(7)-(8)............ Additional Recordkeeping Yes.................. .........................
Requirements for CMS--
Identifying Exceedances
and Excess Emissions.
Sec. 63.10(c)(9)................ [Reserved]................ Not applicable....... .........................
Sec. 63.10(c)(10)............... Recording Nature and Cause No................... See Sec. 63.1576(a)(2)
of Malfunctions. for malfunctions
recordkeeping
requirements.
Sec. 63.10(c)(11)............... Recording Corrective No................... See Sec. 63.1576(a)(2)
Actions. for malfunctions
recordkeeping
requirements.
Sec. 63.10(c)(12)-(14).......... Additional CMS Yes.................. .........................
Recordkeeping
Requirements.
Sec. 63.10(c)(15)............... Use of SSM Plan........... No................... .........................
Sec. 63.10(d)(1)................ General Reporting Yes.................. .........................
Requirements.
Sec. 63.10(d)(2)................ Performance Test Results.. No................... This subpart requires
performance test results
to be reported as part
of the Notification of
Compliance Status due
150 days after the
compliance date.
Sec. 63.10(d)(3)................ Opacity or VE Observations Yes.................. .........................
Sec. 63.10(d)(4)................ Progress Reports.......... Yes.................. .........................
Sec. 63.10(d)(5)................ SSM Reports............... No................... See Sec. 63.1575(d) for
CPMS malfunction
reporting and Sec.
63.1575(e) for COMS and
CEMS malfunction
reporting.
Sec. 63.10(e)(1)-(2)............ Additional CMS Reports.... Yes.................. Except that reports of
performance evaluations
must be submitted in
Notification of
Compliance Status.
Sec. 63.10(e)(3)................ Excess Emissions/CMS No................... This subpart specifies
Performance Reports. the applicable
requirements.
Sec. 63.10(e)(4)................ COMS Data Reports......... Yes.................. .........................
Sec. 63.10(f)................... Recordkeeping/Reporting Yes.................. .........................
Waiver.
Sec. 63.11(a)................... Control Device and Work Yes.................. .........................
Practice Requirements
Applicability.
Sec. 63.11(b)................... Flares.................... Yes.................. Except that flares
complying with Sec.
63.670 are not subject
to the requirements of
Sec. 63.11(b).
Sec. 63.11(c)-(e)............... Alternative Work Practice Yes.................. .........................
for Monitoring Equipment
for Leaks.
Sec. 63.12...................... State Authority and Yes.................. .........................
Delegations.
Sec. 63.13...................... Addresses................. Yes.................. .........................
Sec. 63.14...................... Incorporation by Reference Yes.................. .........................
Sec. 63.15...................... Availability of Yes.................. .........................
Information and
Confidentiality.
Sec. 63.16...................... Performance Track Yes.................. .........................
Provisions.
----------------------------------------------------------------------------------------------------------------
[[Page 75325]]
0
88. Appendix A to subpart UUU of part 63 is amended by revising the
first sentence of section 2.1 and section 7.1.3 to read as follows:
Appendix A to Subpart UUU of Part 63--Determination of Metal
Concentration on Catalyst Particles (Instrumental Analyzer Procedure)
* * * * *
2.1 A representative sample of catalyst particles is collected,
prepared, and analyzed for analyte concentration using either energy
or wavelength dispersive X-ray fluorescent (XRF) spectrometry
instrumental analyzers. * * *
* * * * *
7.1.3 Low-Range Calibration Standard. Concentration equivalent
to 1 to 20 percent of the span. The concentration of the low-range
calibration standard should be selected so that it is less than
either one-fourth of the applicable concentration limit or of the
lowest concentration anticipated in the catalyst samples.
* * * * *
0
89. Appendix A to part 63 is amended by adding Method 325A and Method
325B in numerical order to read as follows:
Appendix A to Part 63--Test Methods Pollutant Measurement Methods From
Various Waste Media
* * * * *
Method 325A--Volatile Organic Compounds from Fugitive and Area
Sources:
Sampler Deployment and VOC Sample Collection
1.0 Scope and Application
1.1 This method describes collection of volatile organic
compounds (VOCs) at or inside a facility property boundary or from
fugitive and area emission sources using passive (diffusive) tube
samplers (PS). The concentration of airborne VOCs at or near these
potential fugitive- or area-emission sources may be determined using
this method in combination with Method 325B. Companion Method 325B
(Sampler Preparation and Analysis) describes preparation of sampling
tubes, shipment and storage of exposed sampling tubes, and analysis
of sampling tubes collected using either this passive sampling
procedure or alternative active (pumped) sampling methods.
1.2 This method may be used to determine the average
concentration of the select VOCs using the corresponding uptake
rates listed in Method 325B, Table 12.1. Additional compounds or
alternative sorbents must be evaluated as described in Addendum A of
Method 325B or by one of the following national/international
standard methods: ISO 16017-2:2003(E), ASTM D6196-03 (Reapproved
2009), or BS EN 14662-4:2005 (all incorporated by reference--see
Sec. 63.14), or reported in the peer-reviewed open literature.
1.3 Methods 325A and 325B are valid for the measurement of
benzene. Supporting literature (References 1-8) indicates that
benzene can be measured by flame ionization detection or mass
spectrometry over a concentration range of approximately 0.5
micrograms per cubic meter ([micro]g/m3) to at least 500
[micro]g/m\3\ when industry standard (3.5 inch long x 0.25 inch
outside diameter (o.d.) x 5 mm inner diameter (i.d.)) inert-coated
stainless steel sorbent tubes packed with CarbographTM 1
TD, CarbopackTM B, or CarbopackTM X or
equivalent are used and when samples are accumulated over a period
of 14 days.
1.4 This method may be applied to screening average airborne VOC
concentrations at facility property boundaries or monitoring
perimeters over an extended period of time using multiple sampling
periods (e.g., 26 x 14-day sampling periods). The duration of each
sampling period is normally 14 days.
1.5 This method requires the collection of local meteorological
data (wind speed and direction, temperature, and barometric
pressure). Although local meteorology is a component of this method,
non-regulatory applications of this method may use regional
meteorological data. Such applications risk that the results may not
identify the precise source of the emissions.
2.0 Summary of the Method
2.1 Principle of the Method
The diffusive passive sampler collects VOC from air for a
measured time period at a rate that is proportional to the
concentration of vapor in the air at that location.
2.1.1 This method describes the deployment of prepared passive
samplers, including determination of the number of passive samplers
needed for each survey and placement of samplers along or inside the
facility property boundary depending on the size and shape of the
site or linear length of the boundary.
2.1.2 The rate of sampling is specific to each compound and
depends on the diffusion constants of that VOC and the sampler
dimensions/characteristics as determined by prior calibration in a
standard atmosphere (Reference 1).
2.1.3 The gaseous VOC target compounds migrate through a
constant diffusion barrier (e.g., an air gap of fixed dimensions) at
the sampling end of the diffusion sampling tube and adsorb onto the
sorbent.
2.1.4 Heat and a flow of inert carrier gas are then used to
extract (desorb) the retained VOCs back from the sampling end of the
tube and transport/transfer them to a gas chromatograph (GC)
equipped with a chromatographic column to separate the VOCs and a
detector to determine the quantity of target VOCs.
2.1.5 Gaseous or liquid calibration standards loaded onto the
sampling ends of clean sorbent tubes must be used to calibrate the
analytical equipment.
2.1.6 This method requires the use of field blanks to ensure
sample integrity associated with shipment, collection, and storage
of the passive samples. It also requires the use of field duplicates
to validate the sampling process.
2.1.7 At the end of each sampling period, the passive samples
are collected, sealed, and shipped to a laboratory for analysis of
target VOCs by thermal desorption gas chromatography, as described
in Method 325B.
2.2 Application of Diffusive Sampling
2.2.1 This method requires deployment of passive sampling tubes
on a monitoring perimeter encompassing all known emission sources at
a facility and collection of local meteorological data. It may be
used to determine average concentration of VOC at a facility's
``fenceline'' using time integrated passive sampling (Reference 2).
2.2.2 Collecting samples and meteorological data at
progressively higher frequencies may be employed to resolve shorter
term concentration fluctuations and wind conditions that could
introduce interfering emissions from other sources.
2.2.3 This passive sampling method provides a low cost approach
to screening of fugitive or area emissions compared to active
sampling methods that are based on pumped sorbent tubes or time
weighted average canister sampling.
2.2.3.1 Additional passive sampling tubes may be deployed at
different distances from the facility property boundary or from the
geometric center of the fugitive emission source.
2.2.3.2 Additional meteorological measurements may also be
collected as needed to perform preliminary gradient-based assessment
of the extent of the pollution plume at ground level and the effect
of ``background'' sources contributing to airborne VOC
concentrations at the location.
2.2.4 Time-resolved concentration measurements coupled with
time-resolved meteorological monitoring may be used to generate data
needed for source apportionment procedures and mass flux
calculations.
3.0 Definitions
(See also Section 3.0 of Method 325B.)
3.1 Fenceline means the property boundary of a facility or
internal monitoring perimeter established in accordance with the
requirements in Section 8.2 of this method.
3.2 Passive sampler (PS) means a specific type of sorbent tube
(defined in this method) that has a fixed dimension air (diffusion)
gap at the sampling end and is sealed at the other end.
3.3 Passive sampling refers to the activity of quantitatively
collecting VOC on sorbent tubes using the process of diffusion.
3.4 PSi is the annual average for all PS concentration results
from location i.
3.5 PSi3 is the set of annual average concentration results for
PSi and two sorbent tubes nearest to the PS location i.
3.6 PSip is the concentration from the sorbent tube at location
i for the test period or episode p.
3.7 Sampling period is the length of time each passive sampler
is exposed during field monitoring. The sampling period for this
method is 14 days.
3.8 Sorbent tube (Also referred to as tube, PS tube, adsorbent
tube, and sampling tube) is an inert coated stainless steel tube.
Standard PS tube dimensions for this method
[[Page 75326]]
are 3.5-inch (89 mm) long x 0.25-inch (6.4 mm) o.d. with an i.d. of
5 mm, a cross-sectional area of 19.6 mm2 and an air gap
of 15 mm. The central portion of the tube is packed with solid
adsorbent material contained between 2 x 100-mesh stainless steel
gauzes and terminated with a diffusion cap at the sampling end of
the tube. These axial passive samplers are installed under a
protective hood during field deployment.
Note: Glass and glass- (or fused silica-) lined stainless steel
sorbent tubes (typically 4 mm i.d.) are also available in various
lengths to suit different makes of thermal desorption equipment, but
these are rarely used for passive sampling because it is more
difficult to adequately define the diffusive air gap in glass or
glass-line tubing. Such tubes are not recommended for this method.
4.0 Sampling Interferences
4.1 General Interferences
Passive tube samplers should be sited at a distance beyond the
influence of possible obstructions such as trees, walls, or
buildings at the monitoring site. Complex topography and physical
site obstructions, such as bodies of water, hills, buildings, and
other structures that may prevent access to a planned PS location
must be taken into consideration. You must document and report
siting interference with the results of this method.
4.2 Background Interference
Nearby or upwind sources of target emissions outside the
facility being tested can contribute to background concentrations.
Moreover, because passive samplers measure continuously, changes in
wind direction can cause variation in the level of background
concentrations from interfering sources during the monitoring
period. This is why local meteorological information, particularly
wind direction and speed, is required to be collected throughout the
monitoring period. Interfering sources can include neighboring
industrial facilities, transportation facilities, fueling
operations, combustion sources, short-term transient sources,
residential sources, and nearby highways or roads. As PS data are
evaluated, the location of potential interferences with respect to
PS locations and local wind conditions should be considered,
especially when high PS concentration values are observed.
4.3 Tube Handling
You must protect the PS tubes from gross external contamination
during field sampling. Analytical thermal desorption equipment used
to analyze PS tubes must desorb organic compounds from the interior
of PS tubes and exclude contamination from external sampler surfaces
in the analytical/sample flow path. If the analytical equipment does
not comply with this requirement, you must wear clean, white, cotton
or powder-free nitrile gloves to handle sampling tubes to prevent
contamination of the external sampler surfaces. Sampling tubes must
be capped with two-piece, brass, 0.25 inch, long-term storage caps
fitted with combined polytetrafluoroethylene ferrules (see Section
6.1 and Method 325B) to prevent ingress of airborne contaminants
outside the sampling period. When not being used for field
monitoring, the capped tubes must be stored in a clean, air-tight,
shipping container to prevent the collection of VOCs (see Section
6.4.2 of Method 325B).
4.4 Local Weather Conditions and Airborne Particulates
Although air speeds are a constraint for many forms of passive
samplers, axial tube PS devices have such a slow inherent uptake
rate that they are largely immune to these effects (References 4,5).
Passive samplers must nevertheless be deployed under non-emitting
weatherproof hoods to moderate the effect of local weather
conditions such as solar heating and rain. The cover must not impede
the ingress of ambient air. Sampling tubes should also be orientated
vertically and pointing downwards, to minimize accumulation of
particulates.
4.5 Temperature
The normal working range for field sampling for sorbent packing
is 0-40 [deg]C (References 6,7). Note that most published passive
uptake rate data for sorbent tubes is quoted at 20 [deg]C. Note also
that, as a rough guide, an increase in temperature of 10 [deg]C will
reduce the collection capacity for a given analyte on a given
sorbent packing by a factor of 2, but the uptake rate will not
change significantly (Reference 4).
5.0 Safety
This method does not purport to include all safety issues or
procedures needed when deploying or collecting passive sampling
tubes. Precautions typical of field air sampling projects are
required. Tripping, falling, electrical, and weather safety
considerations must all be included in plans to deploy and collect
passive sampling tubes.
6.0 Sampling Equipment and Supplies, and Pre-Deployment Planning
This section describes the equipment and supplies needed to
deploy passive sampling monitoring equipment at a facility property
boundary. Details of the passive sampling tubes themselves and
equipment required for subsequent analysis are described in Method
325B.
6.1 Passive Sampling Tubes
The industry standard PS tubes used in this method must meet the
specific configuration and preparation requirements described in
Section 3.0 of this method and Section 6.1 of Method 325B.
Note: The use of PS tubes packed with various sorbent materials
for monitoring a wide variety of organic compounds in ambient air
has been documented in the literature (References 4-10). Other
sorbents may be used in standard passive sampling tubes for
monitoring additional target compound(s) once their uptake rate and
performance has been demonstrated following procedures in Addendum A
to Method 325B. Guidance on sorbent selection can also be obtained
from relevant national and international standard methods such as
ASTM D6196-03 (Reapproved 2009) (Reference 14) and ISO 16017-
2:2003(E) (Reference 13) (both incorporated by reference--see Sec.
63.14).
6.2 Passive or Diffusive Sampling Cap
One diffusive sampling cap is required per PS tube. The cap fits
onto the sampling end of the tube during air monitoring. The other
end of the tube remains sealed with the long-term storage cap. Each
diffusive sampling cap is fitted with a stainless steel gauze, which
defines the outer limit of the diffusion air gap.
6.3 Sorbent Tube Protection Cover
A simple weatherproof hood, suitable for protecting passive
sampling tubes from the worst of the weather (see Section 4.4)
consists of an inverted cone/funnel constructed of an inert, non-
outgassing material that fits over the diffusive tube, with the open
(sampling) end of the tube projecting just below the cone opening.
An example is shown in Figure 6.1 (Adapted from Reference 13).
[[Page 75327]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.025
6.4 Thermal Desorption Apparatus
If the analytical thermal desorber that will subsequently be
used to analyze the passive sampling tubes does not meet the
requirement to exclude outer surface contaminants from the sample
flow path (see Section 6.6 of Method 325B), then clean, white,
cotton or powder-free nitrile gloves must be used for handling the
passive sampling tubes during field deployment.
6.5 Sorbent Selection
Sorbent tube configurations, sorbents or other VOC not listed in
this method must be evaluated according to Method 325B, Addendum A
or ISO 16017-2:2003(E) (Reference 13) (incorporated by reference--
see Sec. 63.14). The supporting evaluation and verification data
described in Method 325B, Addendum A for configurations or compounds
different from the ones described in this method must meet the
performance requirements of Method 325A/B and must be submitted with
the test plan for your measurement program.
7.0 Reagents and Standards
No reagents or standards are needed for the field deployment and
collection of passive sampling tubes. Specifications for sorbents,
gas and liquid phase standards, preloaded standard tubes, and
carrier gases are covered in Section 7 of Method 325B.
8.0 Sample Deployment, Recovery, and Storage
Pre-deployment and planning steps are required before field
deployment of passive sampling tubes. These activities include but
are not limited to conducting a site visit, determining suitable and
required monitoring locations, and determining the monitoring
frequency to be used.
8.1 Conducting the Site Visit
8.1.1 Determine the size and shape of the facility footprint in
order to determine the required number of monitoring locations.
8.1.2 Identify obstacles or obstructions (buildings, roads,
fences), hills and other terrain issues (e.g., bodies of water or
swamp land) that could interfere with air parcel flow to the sampler
or that prevent reasonable access to the location. You may use the
general guidance in Section 4.1 of this method during the site visit
to identify sampling locations. You must evaluate the placement of
each passive sampler to determine if the conditions in this section
are met.
8.1.3 Identify to the extent possible and record potential off-
site source interferences (e.g., neighboring industrial facilities,
transportation facilities, fueling operations, combustion sources,
short-term transient sources, residential sources, nearby highways).
8.1.4 Identify the closest available meteorological station.
Identify potential locations for one or more on-site or near-site
meteorological station(s) following the guidance in EPA-454/B-08-002
(Reference 11) (incorporated by reference--see Sec. 63.14).
8.2 Determining Sampling Locations (References 2, 3)
8.2.1 The number and placement of the passive samplers depends
on the size, the shape of the facility footprint or the linear
distance around the facility, and the proximity of emission sources
near the property boundaries. Aerial photographs or site maps may be
used to determine the size (acreage) and shape of the facility or
the length of the monitoring perimeter. Place passive samplers on an
internal monitoring perimeter on or inside the facility boundary
encompassing all emission sources at the facility at different
angles circling the geometric center of the facility or at different
distances based on the monitoring perimeter length of the facility.
Note: In some instances, permanent air monitoring stations may
already be located in close proximity to the facility. These
stations may be operated and maintained by the site, or local or
state regulatory agencies. If access to the station is possible, a
PS may be deployed adjacent to other air monitoring instrumentation.
A comparison of the pollutant concentrations measured with the PS to
concentrations measured by site instrumentation may be used as an
optional data quality indicator to assess the accuracy of PS
results.
8.2.1.1 The monitoring perimeter may be located between the
property boundary and any potential emission source near the
property boundary, as long as the distance from the source to the
monitoring perimeter is at least 50 meters (162 feet). If a
potential emissions source is within 50 meters (162 feet) of the
property boundary, the property boundary shall be used as the
monitoring perimeter near that source.
8.2.1.2 Samplers need only be placed around the monitoring
perimeter and not along internal roads or other right of ways that
may bisect the facility.
8.2.1.3 Extra samplers must be placed near known sources of VOCs
if the potential emission source is within 50 meters (162 feet) of
the boundary and the source location is between two monitors.
Measure the distance (x) between the two monitors and place another
monitor halfway between (x/2) the two monitors. For example, in
Figure 8.1, the facility added three additional monitors (i.e.,
light shaded sampler locations) and in Figure 8.2, the facility
added two additional monitors to provide sufficient coverage of all
area sources.
BILLING CODE 6560-50-P
[[Page 75328]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.026
8.2.2 Option 1 for Determining Sampling Locations.
8.2.2.1 For facilities with a regular (circular, triangular,
rectangular, or square) shape, determine the geographic center of
the facility.
[[Page 75329]]
8.2.2.1.1 For facilities with an area of less than or equal to
750 acres, measure angles of 30 degrees from the center point for a
total of twelve 30 degree measurements evenly spaced (1
degree).
8.2.2.1.2 For facilities covering an area greater than 750 acres
but less than or equal to 1,500 acres, measure angles of 20 degrees
from the center point for a total of eighteen 20 degree measurements
evenly spaced (1 degree). Figure 8.1 shows the monitor
placement around the property boundary of a facility with an area
between 750 and 1,500 acres. Monitor placements are represented with
black dots along the property boundary.
8.2.2.1.3 For facilities covering an area greater than 1,500
acres, measure angles of 15 degrees from the center point for a
total of twenty-four 15 degree measurements evenly spaced (1 degree).
8.2.2.1.4 Locate each sampling point where the measured angle
intersects the outer monitoring perimeter.
8.2.2.2 For irregularly shaped facilities, divide the area into
a set of connecting subarea circles, triangles or rectangles to
determine sampling locations. The subareas must be defined such that
a circle can reasonably encompass the subarea. Then determine the
geometric center point of each of the subareas.
8.2.2.2.1 If a subarea is less than or equal to 750 acres (e.g.,
Figure 8.3), measure angles of 30 degrees from the center point for
a total of twelve 30 degree measurements (1 degree).
[GRAPHIC] [TIFF OMITTED] TR01DE15.027
8.2.2.2.2 If a subarea is greater than 750 acres but less than
or equal to 1,500 acres (e.g., Figure 8.4), measure angles of 20
degrees from the center point for a total of eighteen 20 degree
measurements (1 degree).
8.2.2.2.3 If a subarea is greater than 1,500 acres, measure
angles of 15 degrees from the center for a total of twenty-four 15
degree measurements (1 degree).
8.2.2.2.4 Locate each sampling point where the measured angle
intersects the outer monitoring perimeter. Sampling points need not
be placed closer than 152 meters (500 feet) apart (or 76 meters (250
feet) if known sources are within 50 meters (162 feet) of the
monitoring perimeter), as long as a minimum of 3 monitoring
locations are used for each subarea.
8.2.2.2.5 Sampling sites are not needed at the intersection of
an inner boundary with an adjacent subarea. The sampling location
must be sited where the measured angle intersects the subarea's
outer monitoring perimeter.
[[Page 75330]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.028
8.2.3 Option 2 for Determining Sampling Locations.
8.2.3.1 For facilities with a monitoring perimeter length of
less than 7,315 meters (24,000 feet), a minimum of twelve sampling
locations evenly spaced 10 percent of the location
interval is required.
8.2.3.2 For facilities with a monitoring perimeter length
greater than 7,315 meters (24,000 feet), sampling locations are
spaced 610 76 meters (2,000 250 feet)
apart.
8.3 Siting a Meteorological Station
A meteorological station is required at or near the facility you
are monitoring. A number of commercially available meteorological
stations can be used. Information on meteorological instruments can
be found in EPA-454/R-99-005 (Reference 11) (incorporated by
reference--see Sec. 63.14). Some important considerations for
siting of meteorological stations are detailed below.
8.3.1 Place meteorological stations in locations that represent
conditions affecting the transport and dispersion of pollutants in
the area of interest. Complex terrain may require the use of more
than one meteorological station.
8.3.2 Deploy wind instruments over level, open terrain at a
height of 10 meters (33 feet). If possible, locate wind instruments
at a distance away from nearby structures that is equal to at least
10 times the height of the structure.
8.3.3 Protect meteorological instruments from thermal radiation
and adequately ventilate them using aspirated shields. The
temperature sensor must be located at a distance away from any
nearby structures that is equal to at least four times the height of
the structure. Temperature sensors must be located at least 30
meters (98 feet) from large paved areas.
8.3.4 Collect and record meteorological data, including wind
speed, wind direction, temperature and barometric pressure on an
hourly basis. Calculate average unit vector wind direction, sigma
theta, temperature and barometric pressure per sampling period to
enable calculation of concentrations at standard conditions. Supply
this information to the laboratory.
8.3.5 Identify and record the location of the meteorological
station by its GPS coordinate.
8.4 Monitoring Frequency
8.4.1 Sample collection may be performed for periods up to 14
days.
8.4.2 A site screening protocol that meets method requirements
may be performed by collecting samples for a year where each PS
accumulates VOC for a 14-day sampling period. Study results are
accumulated for the sampling periods (typically 26) over the course
of one calendar year. To the extent practical, sampling tubes should
be changed at approximately the same time of day at each of the
monitoring sites.
8.5 Passive Sampler Deployment
8.5.1 Clean (conditioned) sorbent tubes must be prepared and
packaged by the laboratory as described in Method 325B and must be
deployed for sampling within 30 days of conditioning.
8.5.2 Allow the tubes to equilibrate with ambient temperature
(approximately 30 minutes to 1 hour) at the monitoring location
before removing them from their storage/shipping container for
sample collection.
8.5.3 If there is any risk that the analytical equipment will
not meet the requirement to exclude contamination on outer tube
surfaces from the sample flow path (see Section 6.6 of Method 325B),
sample handlers must wear clean, white, cotton or powder-free
nitrile gloves during PS deployment and collection and throughout
any other tube handling operations.
8.5.4 Inspect the sampling tubes immediately prior to
deployment. Ensure that they are intact, securely capped, and in
good condition. Any suspect tubes (e.g., tubes that appear to have
leaked sorbent) should be removed from the sampling set.
8.5.5 Secure passive samplers so the bottom of the diffusive
sampling cap is 1.5 to 3 meters (4.9 to 9.8 feet) above ground using
a pole or other secure structure at each sampling location. Orient
the PS vertically and with the sampling end pointing downward to
avoid ingress of particulates.
Note: Duplicate sampling assemblies must be deployed in at
least one monitoring location for every 10 monitoring locations
during each field monitoring period.
8.5.6 Protect the PS from rain and excessive wind velocity by
placing them under the type of protective hood described in Section
6.1.3 or equivalent.
8.5.7 Remove the storage cap on the sampling end of the tube and
replace it with a diffusive sampling cap at the start of the
sampling period. Make sure the diffusion cap is properly seated and
store the removed storage caps in the empty tube shipping container.
8.5.8 Record the start time and location details for each
sampler on the field sample data sheet (see example in Section
17.0.).
[[Page 75331]]
8.5.9 Expose the sampling tubes for the required sampling
period-normally 14-days.
8.5.10 Field blank tubes (see Section 9.3 of Method 325B) are
stored outside the shipping container at representative sampling
locations around the site, but with both long-term storage caps kept
in place throughout the monitoring exercise. Collect at least two
field blanks sorbent samples per sampling period to ensure sample
integrity associated with shipment, collection, and storage.
8.6 Sorbent Tube Recovery and Meteorological Data Collection
Recover deployed sampling tubes and field blanks as follows:
8.6.1 After the sampling period is complete, immediately replace
the diffusion end cap on each sampled tube with a long-term storage
end cap. Tighten the seal securely by hand and then tighten an
additional quarter turn with an appropriate tool. Record the stop
date and time and any additional relevant information on the sample
data sheet.
8.6.2 Place the sampled tubes, together with the field blanks,
in the storage/shipping container. Label the storage container, but
do not use paints, markers, or adhesive labels to identify the
tubes. TD-compatible electronic (radio frequency identification
(RFID)) tube labels are available commercially and are compatible
with some brands of thermal desorber. If used, these may be
programmed with relevant tube and sample information, which can be
read and automatically transcribed into the sequence report by the
TD system.
Note: Sampled tubes must not be placed in the same shipping
container as clean conditioned sampling tubes.
8.6.3 Sampled tubes may be shipped at ambient temperature to a
laboratory for sample analysis.
8.6.4 Specify whether the tubes are field blanks or were used
for sampling and document relevant information for each tube using a
Chain of Custody form (see example in Section 17.0) that accompanies
the samples from preparation of the tubes through receipt for
analysis, including the following information: Unique tube
identification numbers for each sampled tube; the date, time, and
location code for each PS placement; the date, time, and location
code for each PS recovery; the GPS reference for each sampling
location; the unique identification number of the duplicate sample
(if applicable); and problems or anomalies encountered.
8.6.5 If the sorbent tubes are supplied with electronic (e.g.,
RFID) tags, it is also possible to allocate a sample identifier to
each PS tube. In this case, the recommended format for the
identification number of each sampled tube is AA-BB-CC-DD-VOC,
where:
AA = Sequence number of placement on route (01, 02, 03 . . .)
BB = Sampling location code (01, 02, 03 . . .)
CC = 14-day sample period number (01 to 26)
DD = Sample code (SA = sample, DU = duplicate, FB = field blank)
VOC = 3-letter code for target compound(s) (e.g., BNZ for benzene or
BTX for benzene, toluene, and xylenes)
Note: Sampling start and end times/dates can also be logged
using RFID tube tags.
9.0 Quality Control
9.1 Most quality control checks are carried out by the
laboratory and associated requirements are in Section 9.0 of Method
325B, including requirements for laboratory blanks, field blanks,
and duplicate samples.
9.2 Evaluate for potential outliers the laboratory results for
neighboring sampling tubes collected over the same time period. A
potential outlier is a result for which one or more PS tube does not
agree with the trend in results shown by neighboring PS tubes--
particularly when data from those locations have been more
consistent during previous sampling periods. Accidental
contamination by the sample handler must be documented before any
result can be eliminated as an outlier. Rare but possible examples
of contamination include loose or missing storage caps or
contaminated storage/shipping containers. Review data from the same
and neighboring monitoring locations for the subsequent sampling
periods. If the anomalous result is not repeated for that monitoring
location, the episode can be ascribed to transient contamination and
the data in question must be flagged for potential elimination from
the dataset.
9.3 Duplicates and Field Blanks
9.3.1 Collect at least one co-located/duplicate sample for every
10 field samples to determine precision of the measurements.
9.3.2 Collect at least two field blanks sorbent samples per
sampling period to ensure sample integrity associated with shipment,
collection, and storage. You must use the entire sampling apparatus
for field blanks including unopened sorbent tubes mounted in
protective sampling hoods. The tube closures must not be removed.
Field blanks must be placed in two different quadrants (e.g.,
90[deg] and 270[deg]) and remain at the sampling location for the
sampling period.
10.0 Calibration and Standardization
Follow the calibration and standardization procedures for
meteorological measurements in EPA-454/B-08-002 March 2008
(Reference 11) (incorporated by reference--see Sec. 63.14). Refer
to Method 325B for calibration and standardization procedures for
analysis of the passive sampling tubes.
11.0 Analytical Procedures
Refer to Method 325B, which provides details for the preparation
and analysis of sampled passive monitoring tubes (preparation of
sampling tubes, shipment and storage of exposed sampling tubes, and
analysis of sampling tubes).
12.0 Data Analysis, Calculations and Documentation
12.1 Calculate Annual Average Fenceline Concentration.
After a year's worth of sampling at the facility fenceline (for
example, 26 14-day samples), the average (PSi) may be
calculated for any specified period at each PS location using
Equation 12.1.
[GRAPHIC] [TIFF OMITTED] TR01DE15.029
Where:
PSi = Annual average for location i.
PSip = Sampling period specific concentration from Method
325B.
i = Location of passive sampler (0 to 360[deg]).
p = The sampling period.
N = The number of sampling periods in the year (e.g., for 14-day
sampling periods, from 1 to 26).
Note: PSip is a function of sampling location-
specific factors such as the contribution from facility sources,
unusual localized meteorological conditions, contribution from
nearby interfering sources, the background caused by integrated far-
field sources and measurement error due to deployment, handling,
siting, or analytical errors.
12.2 Identify Sampling Locations of Interest
If data from neighboring sampling locations are significantly
different, then you may add extra sampling points to isolate
background contributions or identify facility-specific ``hot
spots.''
12.3 Evaluate Trends
You may evaluate trends and patterns in the PS data over
multiple sampling periods to determine if elevated concentrations of
target compounds are due to operations on the facility or if
contributions from background sources are significant.
12.3.1 Obtain meteorological data including wind speed and wind
direction or unit vector wind data from the on-site meteorological
station. Use this meteorological data to determine the prevailing
wind direction and speed during the periods of elevated
concentrations.
12.3.2 As an option you may perform preliminary back trajectory
calculations (https://ready.arl.noaa.gov/HYSPLIT.php) to aid in
identifying the source of the background contribution to elevated
target compound concentrations.
[[Page 75332]]
12.3.3 Information on published or documented events on- and
off-site may also be included in the associated sampling period
report to explain elevated concentrations if relevant. For example,
you would describe if there was a chemical spill on site, or an
accident on an adjacent road.
12.3.4 Additional monitoring for shorter periods (See section
8.4) may be necessary to allow better discrimination/resolution of
contributing emission sources if the measured trends and associated
meteorology do not provide a clear assessment of facility
contribution to the measured fenceline concentration.
12.3.5 Additional records necessary to calculate sampling period
average target compound concentration can be found in Section 12.1
of Method 325B.
13.0 Method Performance
Method performance requirements are described in Method 325B.
14.0 Pollution Prevention
[Reserved]
15.0 Waste Management
[Reserved]
16.0 References
1. Ambient air quality--Standard method for measurement of benzene
concentrations--Part 4: Diffusive sampling followed by thermal
desorption and gas chromatography, BS EN 14662-4:2005.
2. Thoma, E.D., Miller, C.M., Chung, K.C., Parsons, N.L. and Shine,
B.C. Facility Fence Line Monitoring using Passive Samplers, J. Air &
Waste Mange. Assoc. 2011, 61:834-842.
3. Quality Assurance Handbook for Air Pollution C Systems, Volume
II: Ambient Air Quality Monitoring Program, EPA-454/B-13-003, May
2013. Available at https://www.epa.gov/ttnamti1/files/ambient/pm25/qa/QA-Handbook-Vol-II.pdf.
4. Brown, R.H., Charlton, J. and Saunders, K.J.: The development of
an improved diffusive sampler. Am. Ind. Hyg. Assoc. J. 1981, 42(12):
865-869.
5. Brown, R. H. Environmental use of diffusive samplers: evaluation
of reliable diffusive uptake rates for benzene, toluene and xylene.
J. Environ. Monit. 1999, 1 (1), 115-116.
6. Ballach, J.; Greuter, B.; Schultz, E.; Jaeschke, W. Variations of
uptake rates in benzene diffusive sampling as a function of ambient
conditions. Sci. Total Environ. 1999, 244, 203-217.
7. Brown, R. H. Monitoring the ambient environment with diffusive
samplers: theory and practical considerations. J Environ. Monit.
2000, 2 (1), 1-9.
8. Buzica, D.; Gerboles, M.; Plaisance, H. The equivalence of
diffusive samplers to reference methods for monitoring
O3, benzene and NO2 in ambient air. J.
Environ. Monit. 2008, 10 (9), 1052-1059.
9. Woolfenden, E. Sorbent-based sampling methods for volatile and
semi-volatile organic compounds in air. Part 2. Sorbent selection
and other aspects of optimizing air monitoring methods. J.
Chromatogr. A 2010, 1217, (16), 2685-94.
10. Pfeffer, H. U.; Breuer, L. BTX measurements with diffusive
samplers in the vicinity of a cokery: Comparison between ORSA-type
samplers and pumped sampling. J. Environ. Monit. 2000, 2 (5), 483-
486.
11. US EPA. 2000. Meteorological Monitoring Guidance for Regulatory
Modeling Applications. EPA-454/R-99-005. Office of Air Quality
Planning and Standards, Research Triangle Park, NC. February 2000.
Available at https://www.epa.gov/scram001/guidance/met/mmgrma.pdf.
12. Quality Assurance Handbook for Air Pollution Measurement
Systems. Volume IV: Meteorological Measurements Version 2.0 Final,
EPA-454/B-08-002 March 2008. Available at https://www.epa.gov/ttnamti1/files/ambient/met/Volume%20IV_Meteorological_Measurements.pdf.
13. ISO 16017-2:2003(E), Indoor, ambient and workplace air--Sampling
and analysis of volatile organic compounds by sorbent tube/thermal
desorption/capillary gas chromatography. Part 2: Diffusive sampling.
14. ASTM D6196-03 (Reapproved 2009): Standard practice for selection
of sorbents, sampling, and thermal desorption analysis procedures
for volatile organic compounds in air.
17.0 Tables, Diagrams, Flowcharts and Validation Data
[[Page 75333]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.030
[[Page 75334]]
Method 325B--Volatile Organic Compounds from Fugitive and Area Sources:
Sampler Preparation and Analysis
1.0 Scope and Application
1.1 This method describes thermal desorption/gas chromatography
(TD/GC) analysis of volatile organic compounds (VOCs) from fugitive
and area emission sources collected onto sorbent tubes using passive
sampling. It could also be applied to the TD/GC analysis of VOCs
collected using active (pumped) sampling onto sorbent tubes. The
concentration of airborne VOCs at or near potential fugitive- or
area-emission sources may be determined using this method in
combination with Method 325A. Companion Method 325A (Sampler
Deployment and VOC Sample Collection) describes procedures for
deploying the sorbent tubes and passively collecting VOCs.
1.2 The preferred GC detector for this method is a mass
spectrometer (MS), but flame ionization detectors (FID) may also be
used. Other conventional GC detectors such as electron capture
(ECD), photoionization (PID), or flame photometric (FPD) may also be
used if they are selective and sensitive to the target compound(s)
and if they meet the method performance criteria provided in this
method.
1.3 There are 97 VOCs listed as hazardous air pollutants in
Title III of the Clean Air Act Amendments of 1990. Many of these VOC
are candidate compounds for this method. Compounds with known uptake
rates for CarbographTM 1 TD, CarbopackTM B, or
CarbopackTM X are listed in Table 12.1. This method
provides performance criteria to demonstrate acceptable performance
of the method (or modifications of the method) for monitoring one or
more of the compounds listed Table 12.1. If standard passive
sampling tubes are packed with other sorbents or used for other
analytes than those listed in Table 12.1, then method performance
and relevant uptake rates should be verified according to Addendum A
to this method or by one of the following national/international
standard methods: ISO 16017-2:2003(E), ASTM D6196-03 (Reapproved
2009), or BS EN 14662-4:2005 (all incorporated by reference--see
Sec. 63.14), or reported in the peer-reviewed open literature.
1.4 The analytical approach using TD/GC/MS is based on
previously published EPA guidance in Compendium Method TO-17 (https://www.epa.gov/ttnamti1/airtox.html#compendium) (Reference 1), which
describes active (pumped) sampling of VOCs from ambient air onto
tubes packed with thermally stable adsorbents.
1.5 Inorganic gases not suitable for analysis by this method
include oxides of carbon, nitrogen and sulfur, ozone
(O3), and other diatomic permanent gases. Other
pollutants not suitable for this analysis method include particulate
pollutants, (i.e., fumes, aerosols, and dusts), compounds too labile
(reactive) for conventional GC analysis, and VOCs that are more
volatile than propane.
2.0 Summary of Method
2.1 This method provides procedures for the preparation,
conditioning, blanking, and shipping of sorbent tubes prior to
sample collection.
2.2 Laboratory and field personnel must have experience of
sampling trace-level VOCs using sorbent tubes (References 2,5) and
must have experience operating thermal desorption/GC/multi-detector
instrumentation.
2.3 Key steps of this method as implemented for each sample tube
include: Stringent leak testing under stop flow, recording ambient
temperature conditions, adding internal standards, purging the tube,
thermally desorbing the sampling tube, refocusing on a focusing
trap, desorbing and transferring/injecting the VOCs from the
secondary trap into the capillary GC column for separation and
analysis.
2.4 Water management steps incorporated into this method
include: (a) Selection of hydrophobic sorbents in the sampling tube;
(b) optional dry purging of sample tubes prior to analysis; and (c)
additional selective elimination of water during primary (tube)
desorption (if required) by selecting trapping sorbents and
temperatures such that target compounds are quantitatively retained
while water is purged to vent.
3.0 Definitions
(See also Section 3.0 of Method 325A).
3.1 Blanking is the desorption and confirmatory analysis of
conditioned sorbent tubes before they are sent for field sampling.
3.2 Breakthrough volume and associated relation to passive
sampling. Breakthrough volumes, as applied to active sorbent tube
sampling, equate to the volume of air containing a constant
concentration of analyte that may be passed through a sorbent tube
at a given temperature before a detectable level (5 percent) of the
input analyte concentration elutes from the tube. Although
breakthrough volumes are directly related to active rather than
passive sampling, they provide a measure of the strength of the
sorbent-sorbate interaction and therefore also relate to the
efficiency of the passive sampling process. The best direct measure
of passive sampling efficiency is the stability of the uptake rate.
Quantitative passive sampling is compromised when the sorbent no
longer acts as a perfect sink--i.e., when the concentration of a
target analyte immediately above the sorbent sampling surface no
longer approximates to zero. This causes a reduction in the uptake
rate over time. If the uptake rate for a given analyte on a given
sorbent tube remains relatively constant --i.e., if the uptake rate
determined for 48 hours is similar to that determined for 7 or 14
days--the user can be confident that passive sampling is occurring
at a constant rate. As a general rule of thumb, such ideal passive
sampling conditions typically exist for analyte:sorbent combinations
where the breakthrough volume exceeds 100 L (Reference 4).
3.3 Continuing calibration verification sample (CCV). Single
level calibration samples run periodically to confirm that the
analytical system continues to generate sample results within
acceptable agreement to the current calibration curve.
3.4 Focusing trap is a cooled, secondary sorbent trap integrated
into the analytical thermal desorber. It typically has a smaller
i.d. and lower thermal mass than the original sample tube allowing
it to effectively refocus desorbed analytes and then heat rapidly to
ensure efficient transfer/injection into the capillary GC analytical
column.
3.5 High Resolution Capillary Column Chromatography uses fused
silica capillary columns with an inner diameter of 320 [mu]m or less
and with a stationary phase film thickness of 5 [mu]m or less.
3.6 h is time in hours.
3.7 i.d. is inner diameter.
3.8 min is time in minutes.
3.9 Method Detection Limit is the lowest level of analyte that
can be detected in the sample matrix with 99% confidence.
3.10 MS-SCAN is the mode of operation of a GC quadrupole mass
spectrometer detector that measures all ions over a given mass range
over a given period of time.
3.11 MS-SIM is the mode of operation of a GC quadrupole mass
spectrometer detector that measures only a single ion or a selected
number of discrete ions for each analyte.
3.12 o.d. is outer diameter.
3.13 ppbv is parts per billion by volume.
3.14 Thermal desorption is the use of heat and a flow of inert
(carrier) gas to extract volatiles from a solid matrix. No solvent
is required.
3.15 Total ion chromatogram is the chromatogram produced from a
mass spectrometer detector collecting full spectral information.
3.16 Two-stage thermal desorption is the process of thermally
desorbing analytes from a sorbent tube, reconcentrating them on a
focusing trap (see Section 3.4), which is then itself rapidly heated
to ``inject'' the concentrated compounds into the GC analyzer.
3.17 VOC is volatile organic compound.
4.0 Analytical Interferences
4.1 Interference from Sorbent Artifacts. Artifacts may include
target analytes as well as other VOC that co-elute
chromatographically with the compounds of interest or otherwise
interfere with the identification or quantitation of target
analytes.
4.1.1 Sorbent decomposition artifacts are VOCs that form when
sorbents degenerate, e.g., when exposed to reactive species during
sampling. For example, benzaldehyde, phenol, and acetophenone
artifacts are reported to be formed via oxidation of the polymeric
sorbent Tenax[supreg] when sampling high concentration (100-500 ppb)
ozone atmospheres (Reference 5).
4.1.2 Preparation and storage artifacts are VOCs that were not
completely cleaned from the sorbent tube during conditioning or that
are an inherent feature of that sorbent at a given temperature.
4.2 Humidity. Moisture captured during sampling can interfere
with VOC analysis. Passive sampling using tubes packed with
hydrophobic sorbents, like those described in this method, minimizes
water retention. However, if water interference is found to be an
issue under extreme conditions, one or more of the water management
steps described in Section 2.4 can be applied.
4.3 Contamination from Sample Handling. The type of analytical
thermal
[[Page 75335]]
desorption equipment selected should exclude the possibility of
outer tube surface contamination entering the sample flow path (see
Section 6.6). If the available system does not meet this
requirement, sampling tubes and caps must be handled only while
wearing clean, white cotton or powder free nitrile gloves to prevent
contamination with body oils, hand lotions, perfumes, etc.
5.0 Safety
5.1 This method does not address all of the safety concerns
associated with its use. It is the responsibility of the user of
this standard to establish appropriate field and laboratory safety
and health practices prior to use.
5.2 Laboratory analysts must exercise extreme care in working
with high-pressure gas cylinders.
5.3 Due to the high temperatures involved, operators must use
caution when conditioning and analyzing tubes.
6.0 Equipment and Supplies
6.1 Tube Dimensions and Materials. The sampling tubes for this
method are 3.5-inches (89 mm) long, \1/4\ inch (6.4 mm) o.d., and 5
mm i.d. passive sampling tubes (see Figure 6.1). The tubes are made
of inert-coated stainless steel with the central section (up to 60
mm) packed with sorbent, typically supported between two 100 mesh
stainless steel gauze. The tubes have a cross sectional area of 19.6
square mm (5 mm i.d.). When used for passive sampling, these tubes
have an internal diffusion (air) gap (DG) of 1.5 cm between the
sorbent retaining gauze at the sampling end of the tube, and the
gauze in the diffusion cap.
[GRAPHIC] [TIFF OMITTED] TR01DE15.031
6.2 Tube Conditioning Apparatus
6.2.1 Freshly packed or newly purchased tubes must be
conditioned as described in Section 9 using an appropriate dedicated
tube conditioning unit or the thermal desorber. Note that the
analytical TD system should be used for tube conditioning if it
supports a dedicated tube conditioning mode in which effluent from
contaminated tubes is directed to vent without passing through key
parts of the sample flow path such as the focusing trap.
6.2.2 Dedicated tube conditioning units must be leak-tight to
prevent air ingress, allow precise and reproducible temperature
selection (5 [deg]C), offer a temperature range at least
as great as that of the thermal desorber, and support inert gas
flows in the range up to 100 mL/min.
Note: For safety and to avoid laboratory contamination, effluent
gases from freshly packed or highly contaminated tubes should be
passed through a charcoal filter during the conditioning process to
prevent desorbed VOCs from polluting the laboratory atmosphere.
6.3 Tube Labeling
6.3.1 Label the sample tubes with a unique permanent
identification number and an indication of the sampling end of the
tube. Labeling options include etching and TD-compatible electronic
(radio frequency identification (RFID)) tube labels.
6.3.2 To avoid contamination, do not make ink markings of any
kind on clean sorbent tubes or apply adhesive labels.
Note: TD-compatible electronic (RFID) tube labels are available
commercially and are compatible with some brands of thermal
desorber. If used, these may be programmed with relevant tube and
sample information, which can be read and automatically transcribed
into the sequence report by the TD system (see Section 8.6 of Method
325A).
6.4 Blank and Sampled Tube Storage Apparatus
6.4.1 Long-term storage caps. Seal clean, blank and sampled
sorbent tubes using inert, long-term tube storage caps comprising
non-greased, 2-piece, 0.25-inch, metal SwageLok[supreg]-type screw
caps fitted with combined polytetrafluoroethylene ferrules.
6.4.2 Storage and transportation containers. Use clean glass
jars, metal cans or rigid, non-emitting polymer boxes.
Note: You may add a small packet of new activated charcoal or
charcoal/silica gel to the shipping container for storage and
transportation of batches of conditioned sorbent tubes prior to use.
Coolers without ice packs make suitable shipping boxes for
containers of tubes because the coolers help to insulate the samples
from extreme temperatures (e.g., if left in a parked vehicle).
6.5 Unheated GC Injection Unit for Loading Standards Onto Blank Tubes
A suitable device has a simple push fit or finger-tightening
connector for attaching the sampling end of blank sorbent tubes
without damaging the tube. It also has a means of controlling
carrier gas flow through the injector and attached sorbent tube at
50-100 mL/min and includes a low emission septum cap that allows the
introduction of gas or liquid standards via appropriate syringes.
Reproducible and quantitative transfer of higher boiling compounds
in liquid standards is facilitated if the injection unit allows the
tip of the syringe to just touch the sorbent retaining gauze inside
the tube.
6.6 Thermal Desorption Apparatus
The manual or automated thermal desorption system must heat
sorbent tubes while a controlled flow of inert (carrier) gas passes
through the tube and out of the sampling end. The apparatus must
also incorporate a focusing trap to quantitatively refocus compounds
desorbed from the tube. Secondary desorption of the focusing trap
should be fast/efficient enough to transfer the compounds into the
high resolution capillary GC column without band broadening and
without any need for further pre- or on-column focusing. Typical TD
focusing traps comprise small sorbent traps (Reference 16) that are
electrically-cooled using multistage Peltier cells (References 17,
18). The direction of gas flow during trap desorption should be the
reverse of that used for focusing to extend the compatible analyte
volatility range. Closed cycle coolers offer another cryogen-free
trap cooling option. Other TD system requirements and operational
stages are described in Section 11 and in Figures 17-2 through 17-4.
6.7 Thermal Desorber--GC Interface
6.7.1 The interface between the thermal desorber and the GC must
be heated uniformly and the connection between the transfer line
insert and the capillary GC analytical column itself must be leak
tight.
6.7.2 A portion of capillary column can alternatively be
threaded through the heated transfer line/TD interface and connected
directly to the thermal desorber.
Note: Use of a metal syringe-type needle or unheated length of
fused silica pushed through the septum of a conventional GC
[[Page 75336]]
injector is not permitted as a means of interfacing the thermal
desorber to the chromatograph. Such connections result in cold
spots, cause band broadening and are prone to leaks.
6.8 GC/MS Analytical Components
6.8.1 The GC system must be capable of temperature programming
and operation of a high resolution capillary column. Depending on
the choice of column (e.g., film thickness) and the volatility of
the target compounds, it may be necessary to cool the GC oven to
subambient temperatures (e.g., -50 [deg]C) at the start of the run
to allow resolution of very volatile organic compounds.
6.8.2 All carrier gas lines supplying the GC must be constructed
from clean stainless steel or copper tubing. Non-
polytetrafluoroethylene thread sealants. Flow controllers, cylinder
regulators, or other pneumatic components fitted with rubber
components are not suitable.
6.9 Chromatographic Columns
High-resolution, fused silica or equivalent capillary columns
that provide adequate separation of sample components to permit
identification and quantitation of target compounds must be used.
Note: 100-percent methyl silicone or 5-percent phenyl, 95-
percent methyl silicone fused silica capillary columns of 0.25- to
0.32-mm i.d. of varying lengths and with varying thicknesses of
stationary phase have been used successfully for non-polar and
moderately polar compounds. However, given the diversity of
potential target lists, GC column choice is left to the operator,
subject to the performance criteria of this method.
6.10 Mass Spectrometer
Linear quadrupole, magnetic sector, ion trap or time-of-flight
mass spectrometers may be used provided they meet specified
performance criteria. The mass detector must be capable of
collecting data from 35 to 300 atomic mass units (amu) every 1
second or less, utilizing 70 volts (nominal) electron energy in the
electron ionization mode, and producing a mass spectrum that meets
all the instrument performance acceptance criteria in Section 9 when
50 [eta]g or less of p-bromofluorobenzene is analyzed.
7.0 Reagents and Standards
7.1 Sorbent Selection
7.1.1 Use commercially packed tubes meeting the requirements of
this method or prepare tubes in the laboratory using sieved sorbents
of particle size in the range 20 to 80 mesh that meet the retention
and quality control requirements of this method.
7.1.2 This passive air monitoring method can be used without the
evaluation specified in Addendum A if the type of tubes described in
Section 6.1 are packed with 4-6 cm (typically 400-650 mg) of the
sorbents listed in Table 12.1 and used for the respective target
analytes.
Note: Although CarbopackTM X is the optimum sorbent
choice for passive sampling of 1,3-butadiene, recovery of compounds
with vapor pressure lower than benzene may be difficult to achieve
without exceeding sorbent maximum temperature limitations (see Table
8.1). See ISO 16017-2:2003(E) or ASTM D6196-03 (Reapproved 2009)
(both incorporated by reference--see Sec. 63.14) for more details
on sorbent choice for air monitoring using passive sampling tubes.
7.1.3 If standard passive sampling tubes are packed with other
sorbents or used for analytes other than those tabulated in Section
12.0, method performance and relevant uptake rates should be
verified according to Addendum A to this method or by following the
techniques described in one of the following national/international
standard methods: ISO 16017-2:2003(E), ASTM D6196-03 (Reapproved
2009), or BS EN 14662-4:2005 (all incorporated by reference--see
Sec. 63.14)--or reported in the peer-reviewed open literature. A
summary table and the supporting evaluation data demonstrating the
selected sorbent meets the requirements in Addendum A to this method
must be submitted to the regulatory authority as part of a request
to use an alternative sorbent.
7.1.4 Passive (diffusive) sampling and thermal desorption
methods that have been evaluated at relatively high atmospheric
concentrations (i.e., mid-ppb to ppm) and published for use in
workplace air and industrial/mobile source emissions testing
(References 9-20) may be applied to this procedure. However, the
validity of any shorter term uptake rates must be verified and
adjusted if necessary for the longer monitoring periods required by
this method by following procedures described in Addendum A to this
method or those presented in national/international standard
methods: ISO 16017-2:2003(E), ASTM D6196-03 (Reapproved 2009), or BS
EN 14662-4:2005 (all incorporated by reference-see Sec. 63.14).
7.1.5 Suitable sorbents for passive sampling must have
breakthrough volumes of at least 20 L (preferably >100 L) for the
compounds of interest and must quantitatively release the analytes
during desorption without exceeding maximum temperatures for the
sorbent or instrumentation.
7.1.6 Repack/replace the sorbent tubes or demonstrate tube
performance following the requirements in Addendum A to this method
at least every 2 years or every 50 uses, whichever occurs first.
7.2 Gas Phase Standards
7.2.1 Static or dynamic standard atmospheres may be used to
prepare calibration tubes and/or to validate passive sampling uptake
rates and can be generated from pure chemicals or by diluting
concentrated gas standards. The standard atmosphere must be stable
at ambient pressure and accurate to 10 percent of the
target gas concentration. It must be possible to maintain standard
atmosphere concentrations at the same or lower levels than the
target compound concentration objectives of the test. Test
atmospheres used for validation of uptake rates must also contain at
least 35 percent relative humidity.
Note: Accurate, low-(ppb-) level gas-phase VOC standards are
difficult to generate from pure materials and may be unstable
depending on analyte polarity and volatility. Parallel monitoring of
vapor concentrations with alternative methods, such as pumped
sorbent tubes or sensitive/selective on-line detectors, may be
necessary to minimize uncertainty. For these reasons, standard
atmospheres are rarely used for routine calibration.
7.2.2 Concentrated, pressurized gas phase standards. Accurate
(5 percent or better), concentrated gas phase standards
supplied in pressurized cylinders may also be used for calibration.
The concentration of the standard should be such that a 0.5-5.0 mL
volume contains approximately the same mass of analytes as will be
collected from a typical air sample.
7.2.3 Follow manufacturer's guidelines concerning storage
conditions and recertification of the concentrated gas phase
standard. Gas standards must be recertified a minimum of once every
12 months.
7.3 Liquid Standards
Target analytes can also be introduced to the sampling end of
sorbent tubes in the form of liquid calibration standards.
7.3.1 The concentration of liquid standards must be such that an
injection of 0.5-2 [micro]l of the solution introduces the same mass
of target analyte that is expected to be collected during the
passive air sampling period.
7.3.2 Solvent Selection. The solvent selected for the liquid
standard must be pure (contaminants <10 percent of minimum analyte
levels) and must not interfere chromatographically with the
compounds of interest.
7.3.3 If liquid standards are sourced commercially, follow
manufacturer's guidelines concerning storage conditions and shelf
life of unopened and opened liquid stock standards.
Note: Commercial VOC standards are typically supplied in
volatile or non-interfering solvents such as methanol.
7.3.4 Working standards must be stored at 6 [deg]C or less and
used or discarded within two weeks of preparation.
7.4 Gas Phase Internal Standards
7.4.1 Gas-phase deuterated or fluorinated organic compounds may
be used as internal standards for MS-based systems.
7.4.2 Typical compounds include deuterated toluene,
perfluorobenzene and perfluorotoluene.
7.4.3 Use multiple internal standards to cover the volatility
range of the target analytes.
7.4.4 Gas-phase standards must be obtained in pressurized
cylinders and containing vendor certified gas concentrations
accurate to 5 percent. The concentration should be such
that the mass of internal standard components introduced is similar
to those of the target analytes collected during field monitoring.
7.5 Preloaded Standard Tubes
Certified, preloaded standard tubes, accurate within 5 percent for each analyte at the microgram level and 10 percent at the nanogram level, are available commercially
[[Page 75337]]
and may be used for auditing and quality control purposes. (See
Section 9.5 for audit accuracy evaluation criteria.) Certified
preloaded tubes may also be used for routine calibration.
Note: Proficiency testing schemes are also available for TD/GC/
MS analysis of sorbent tubes preloaded with common analytes such as
benzene, toluene, and xylene.
7.6 Carrier Gases
Use inert, 99.999-percent or higher purity helium as carrier
gas. Oxygen and organic filters must be installed in the carrier gas
lines supplying the analytical system according to the
manufacturer's instructions. Keep records of filter and oxygen
scrubber replacement.
8.0 Sorbent Tube Handling (Before and After Sampling)
8.1 Sample Tube Conditioning
8.1.1 Sampling tubes must be conditioned using the apparatus
described in Section 6.2.
8.1.2 New tubes should be conditioned for 2 hours to supplement
the vendor's conditioning procedure. Recommended temperatures for
tube conditioning are given in Table 8.1.
8.1.3 After conditioning, the blank must be verified on each new
sorbent tube and on 10 percent of each batch of reconditioned tubes.
See Section 9.0 for acceptance criteria.
Table 8.1--Example Sorbent Tube Conditioning Parameters
----------------------------------------------------------------------------------------------------------------
Maximum Conditioning
Sampling sorbent temperature temperature Carrier gas
([deg]C) ([deg]C) flow rate
----------------------------------------------------------------------------------------------------------------
Carbotrap[supreg] C............................................. >400 350 100 mL/min
CarbopackTM C
Anasorb[supreg] GCB2
CarbographTM 1 TD
Carbotrap[supreg]
CarbopackTM B
Anasorb[supreg] GCB1
Tenax[supreg] TA 350 330 100 mL/min
CarbopackTM X...................................................
----------------------------------------------------------------------------------------------------------------
8.2 Capping, Storage and Shipment of Conditioned Tubes
8.2.1 Conditioned tubes must be sealed using long-term storage
caps (see Section 6.4) pushed fully down onto both ends of the PS
sorbent tube, tightened by hand and then tighten an additional
quarter turn using an appropriate tool.
8.2.2 The capped tubes must be kept in appropriate containers
for storage and transportation (see Section 6.4.2). Containers of
sorbent tubes may be stored and shipped at ambient temperature and
must be kept in a clean environment.
8.2.3 You must keep batches of capped tubes in their shipping
boxes or wrap them in uncoated aluminum foil before placing them in
their storage container, especially before air freight, because the
packaging helps hold caps in position if the tubes get very cold.
8.3 Calculating the Number of Tubes Required for a Monitoring Exercise
8.3.1 Follow guidance given in Method 325A to determine the
number of tubes required for site monitoring.
8.3.2 The following additional samples will also be required:
Laboratory blanks as specified in Section 9.1.2 (one per analytical
sequence minimum), field blanks as specified in Section 9.3.2 (two
per sampling period minimum), CCV tubes as specified in Section
10.9.4. (at least one per analysis sequence or every 24 hours), and
duplicate samples as specified in Section 9.4 (at least one
duplicate sample is required for every 10 sampling locations during
each monitoring period).
8.4 Sample Collection
8.4.1 Allow the tubes to equilibrate with ambient temperature
(approximately 30 minutes to 1 hour) at the monitoring location
before removing them from their storage/shipping container for
sample collection.
8.4.2 Tubes must be used for sampling within 30 days of
conditioning (Reference 4).
8.4.3 During field monitoring, the long-term storage cap at the
sampling end of the tube is replaced with a diffusion cap and the
whole assembly is arranged vertically, with the sampling end
pointing downward, under a protective hood or shield--See Section
6.1 of Method 325A for more details.
8.5 Sample Storage
8.5.1 After sampling, tubes must be immediately resealed with
long-term storage caps and placed back inside the type of storage
container described in Section 6.4.2.
8.5.2 Exposed tubes may not be placed in the same container as
clean tubes. They should not be taken back out of the container
until ready for analysis and after they have had time to equilibrate
with ambient temperature in the laboratory.
8.5.3 Sampled tubes must be inspected before analysis to
identify problems such as loose or missing caps, damaged tubes,
tubes that appear to be leaking sorbent or container contamination.
Any and all such problems must be documented together with the
unique identification number of the tube or tubes concerned.
Affected tubes must not be analyzed but must be set aside.
8.5.4 Intact tubes must be analyzed within 30 days of the end of
sample collection (within one week for limonene, carene, bis-
chloromethyl ether, labile sulfur or nitrogen-containing compounds,
and other reactive VOCs).
Note: Ensure ambient temperatures stay below 23 [deg]C during
transportation and storage. Refrigeration is not normally required
unless the samples contain reactive compounds or cannot be analyzed
within 30 days. If refrigeration is used, the atmosphere inside the
refrigerator must be clean and free of organic solvents.
9.0 Quality Control
9.1 Laboratory Blank
The analytical system must be demonstrated to be contaminant
free by performing a blank analysis at the beginning of each
analytical sequence to demonstrate that the secondary trap and TD/
GC/MS analytical equipment are free of any significant interferents.
9.1.1 Laboratory blank tubes must be prepared from tubes that
are identical to those used for field sampling.
9.1.2 Analysis of at least one laboratory blank is required per
analytical sequence. The laboratory blank must be stored in the
laboratory under clean, controlled ambient temperature conditions.
9.1.3 Laboratory blank/artifact levels must meet the
requirements of Section 9.2.2 (see also Table 17.1). If the
laboratory blank does not meet requirements, stop and perform
corrective actions and then re-analyze laboratory blank to ensure it
meets requirements.
9.2 Tube Conditioning
9.2.1 Conditioned tubes must be demonstrated to be free of
contaminants and interference by running 10 percent of the blank
tubes selected at random from each conditioned batch under standard
sample analysis conditions (see Section 8.1).
9.2.2 Confirm that artifacts and background contamination are <=
0.2 ppbv or less than three times the detection limit of the
procedure or less than 10 percent of the target compound(s) mass
that would be collected if airborne concentrations were at the
regulated limit value, whichever is larger. Only tubes that meet
these criteria can be
[[Page 75338]]
used for field monitoring, field or laboratory blanks, or for system
calibration.
9.2.3 If unacceptable levels of VOCs are observed in the tube
blanks, then the processes of tube conditioning and checking the
blanks must be repeated.
9.3 Field Blanks
9.3.1 Field blank tubes must be prepared from tubes that are
identical to those used for field sampling--i.e., they should be
from the same batch, have a similar history, and be conditioned at
the same time.
9.3.2 Field blanks must be shipped to the monitoring site with
the sampling tubes and must be stored at the sampling location
throughout the monitoring exercise. The field blanks must be
installed under a protective hood/cover at the sampling location,
but the long-term storage caps must remain in place throughout the
monitoring period (see Method 325A). The field blanks are then
shipped back to the laboratory in the same container as the sampled
tubes. One field blank tube is required for every 10 sampled tubes
on a monitoring exercise and no less than two field blanks should be
collected, regardless of the size of the monitoring study.
9.3.3 Field blanks must contain no greater than one-third of the
measured target analyte or compliance limit for field samples (see
Table 17.1). If either field blank fails, flag all data that do not
meet this criterion with a note that the associated results are
estimated and likely to be biased high due to field blank
background.
9.4 Duplicate Samples
Duplicate (co-located) samples collected must be analyzed and
reported as part of method quality control. They are used to
evaluate sampling and analysis precision. Relevant performance
criteria are given in Section 9.9.
9.5 Method Performance Criteria
Unless otherwise noted, monitoring method performance
specifications must be demonstrated for the target compounds using
the procedures described in Addendum A to this method and the
statistical approach presented in Method 301.
9.6 Method Detection Limit
Determine the method detection limit under the analytical
conditions selected (see Section 11.3) using the procedure in
Section 15 of Method 301. The method detection limit is defined for
each system by making seven replicate measurements of a
concentration of the compound of interest within a factor of five of
the detection limit. Compute the standard deviation for the seven
replicate concentrations, and multiply this value by three. The
results should demonstrate that the method is able to detect
analytes such as benzene at concentrations as low as 50 ppt or 1/3rd
(preferably 1/10th) of the lowest concentration of interest,
whichever is larger.
Note: Determining the detection limit may be an iterative
process as described in 40 CFR part 136, Appendix B.
9.7 Analytical Bias
Analytical bias must be demonstrated to be within 30 percent using Equation 9.1. Analytical bias must be
demonstrated during initial setup of this method and as part of the
CCV carried out with every sequence of 10 samples or less (see
Section 9.14). Calibration standard tubes (see Section 10.0) may be
used for this purpose.
[GRAPHIC] [TIFF OMITTED] TR01DE15.032
Eq. 9.1Where:
Spiked Value = A known mass of VOCs added to the tube.
Measured Value = Mass determined from analysis of the tube.
9.8 Analytical Precision
Demonstrate an analytical precision within 20
percent using Equation 9.2. Analytical precision must be
demonstrated during initial setup of this method and at least once
per year. Calibration standard tubes may be used (see Section 10.0)
and data from CCV may also be applied for this purpose.
[GRAPHIC] [TIFF OMITTED] TR01DE15.033
Eq. 9.2Where:
A1 = A measurement value taken from one spiked tube.
A2 = A measurement value taken from a second spiked tube.
A = The average of A1 and A2.
9.9 Field Replicate Precision
Use Equation 9.3 to determine and report replicate precision for
duplicate field samples (see Section 9.4). The level of agreement
between duplicate field samples is a measure of the precision
achievable for the entire sampling and analysis procedure. Flag data
sets for which the duplicate samples do not agree within 30 percent.
[GRAPHIC] [TIFF OMITTED] TR01DE15.034
Eq. 9.3Where:
F1 = A measurement value (mass) taken from one of the two field
replicate tubes used in sampling.
F2 = A measurement value (mass) taken from the second of two field
replicate tubes used in sampling.
F = The average of F1 and F2.
9.10 Desorption Efficiency and Compound Recovery
The efficiency of the thermal desorption method must be
determined.
9.10.1 Quantitative (>95 percent) compound recovery must be
demonstrated by repeat analyses on a same standard tube.
9.10.2 Compound recovery through the TD system can also be
demonstrated by comparing the calibration check sample response
factor obtained from direct GC injection of liquid standards with
that obtained from thermal desorption analysis response factor using
the same column under identical conditions.
9.10.3 If the relative response factors obtained for one or more
target compounds introduced to the column via thermal desorption
fail to meet the criteria in Section 9.10.1, you must adjust the TD
parameters to meet the criteria and repeat the experiment. Once the
thermal desorption conditions have been optimized, you must repeat
this test each time the analytical system is recalibrated to
demonstrate continued method performance.
9.11 Audit Samples
Certified reference standard samples must be used to audit this
procedure (if available). Accuracy within 30 percent must be
[[Page 75339]]
demonstrated for relevant ambient air concentrations (0.5 to 25
ppb).
9.12 Mass Spectrometer Tuning Criteria
Tune the mass spectrometer (if used) according to manufacturer's
specifications. Verify the instrument performance by analyzing a 50
[eta]g injection of bromofluorobenzene. Prior to the beginning of
each analytical sequence or every 24 hours during continuous GC/MS
operation for this method demonstrate that the bromofluorobenzene
tuning performance criteria in Table 9.1 have been met.
Table 9.1--GC/MS Tuning Criteria \1\
----------------------------------------------------------------------------------------------------------------
Target mass Rel. to mass Lower limit % Upper limit %
----------------------------------------------------------------------------------------------------------------
50.............................................................. 95 8 40
75.............................................................. 95 30 66
95.............................................................. 95 100 100
96.............................................................. 95 5 9
173............................................................. 174 0 2
174............................................................. 95 50 120
175............................................................. 174 4 9
176............................................................. 174 93 101
177............................................................. 176 5 9
----------------------------------------------------------------------------------------------------------------
\1\ All ion abundances must be normalized to m/z 95, the nominal base peak, even though the ion abundance of m/z
174 may be up to 120 percent that of m/z 95.
9.13 Routine CCV at the Start of a Sequence
Run CCV before each sequence of analyses and after every tenth
sample to ensure that the previous multi-level calibration (see
Section 10.6.3) is still valid.
9.13.1 The sample concentration used for the CCV should be near
the mid-point of the multi-level calibration range.
9.13.2 Quantitation software must be updated with response
factors determined from the CCV standard. The percent deviation
between the initial calibration and the CCV for all compounds must
be within 30 percent.
9.14 CCV at the End of a Sequence
Run another CCV after running each sequence of samples. The
initial CCV for a subsequent set of samples may be used as the final
CCV for a previous analytical sequence, provided the same analytical
method is used and the subsequent set of samples is analyzed
immediately (within 4 hours) after the last CCV.
9.15 Additional Verification
Use a calibration check standard from a second, separate source
to verify the original calibration at least once every three months.
9.16 Integration Method
Document the procedure used for integration of analytical data
including field samples, calibration standards and blanks.
9.17 QC Records
Maintain all QC reports/records for each TD/GC/MS analytical
system used for application of this method. Routine quality control
requirements for this method are listed below and summarized in
Table 17.1.
10.0 Calibration and Standardization
10.1 Calibrate the analytical system using standards covering
the range of analyte masses expected from field samples.
10.2 Analytical results for field samples must fall within the
calibrated range of the analytical system to be valid.
10.3 Calibration standard preparation must be fully traceable to
primary standards of mass and/or volume, and/or be confirmed using
an independent certified reference method.
10.3.1 Preparation of calibration standard tubes from standard
atmospheres.
10.3.1.1 Subject to the requirements in Section 7.2.1, low-level
standard atmospheres may be introduced to clean, conditioned sorbent
tubes in order to produce calibration standards.
10.3.1.2 The standard atmosphere generator or system must be
capable of producing sufficient flow at a constant rate to allow the
required analyte mass to be introduced within a reasonable time
frame and without affecting the concentration of the standard
atmosphere itself.
10.3.1.3 The sampling manifold may be heated to minimize risk of
condensation but the temperature of the gas delivered to the sorbent
tubes may not exceed 100[emsp14][deg]F.
10.3.1.4 The flow rates passed through the tube should be in the
order of 50-100 mL/min and the volume of standard atmosphere sampled
from the manifold or chamber must not exceed the breakthrough volume
of the sorbent at the given temperature.
10.4 Preparation of calibration standard tubes from concentrated
gas standards.
10.4.1 If a suitable concentrated gas standard (see Section
7.2.2) can be obtained, follow the manufacturer's recommendations
relating to suitable storage conditions and product lifetime.
10.4.2 Introduce precise 0.5 to 500.0 mL aliquots of the
standard to the sampling end of conditioned sorbent tubes in a 50-
100 mL/min flow of pure carrier gas.
Note: This can be achieved by connecting the sampling end of the
tube to an unheated GC injector (see Section 6.6) and introducing
the aliquot of gas using a suitable gas syringe. Gas sample valves
could alternatively be used to meter the standard gas volume.
10.4.3 Each sorbent tube should be left connected to the flow of
gas for 2 minutes after standard introduction. As soon as each
spiked tube is removed from the injection unit, seal it with long-
term storage caps and place it in an appropriate tube storage/
transportation container if it is not to be analyzed within 24
hours.
10.5 Preparation of calibration standard tubes from liquid
standards.
10.5.1 Suitable standards are described in Section 7.3.
10.5.2 Introduce precise 0.5 to 2 [micro]l aliquots of liquid
standards to the sampling end of sorbent tubes in a flow (50-100 mL/
min) of carrier gas using a precision syringe and an unheated
injector (Section 6.5). The flow of gas should be sufficient to
completely vaporize the liquid standard.
Note: If the analytes of interest are higher boiling than n-
decane, reproducible analyte transfer to the sorbent bed is
optimized by allowing the tip of the syringe to gently touch the
sorbent retaining gauze at the sampling end of the tube.
10.5.3 Each sorbent tube is left connected to the flow of gas
for 5 minutes after liquid standard introduction.
10.5.3.1 As soon as each spiked tube is removed from the
injection unit, seal it with long-term storage caps and place it in
an appropriate tube storage container if it is not to be analyzed
within 24 hours.
Note: In cases where it is possible to selectively purge the
solvent from the tube while all target analytes are quantitatively
retained, a larger 2 [micro]L injection may be made for optimum
accuracy. However, if the solvent cannot be selectively purged and
will be present during analysis, the injection volume should be as
small as possible (e.g., 0.5 [micro]L) to minimize solvent
interference.
Note: This standard preparation technique requires the entire
liquid plug including the tip volume be brought into the syringe
barrel. The volume in the barrel is recorded, the syringe is
inserted into the septum of the spiking apparatus. The liquid is
then quickly injected. Any remaining liquid in the syringe tip is
brought back into the syringe barrel. The volume in the barrel is
recorded and the amount spiked onto the tube is the difference
between the before spiking volume and the after spiking volume. A
bias occurs with this method when sample is drawn continuously up
into the syringe to the specified volume
[[Page 75340]]
and the calibration solution in the syringe tip is ignored.
10.6 Preparation of calibration standard tubes from multiple
standards.
10.6.1 If it is not possible to prepare one standard containing
all the compounds of interest (e.g., because of chemical reactivity
or the breadth of the volatility range), standard tubes can be
prepared from multiple gas or liquid standards.
10.6.2 Follow the procedures described in Sections 10.4 and
10.5, respectively, for introducing each gas and/or liquid standard
to the tube and load those containing the highest boiling compounds
of interest first and the lightest species last.
10.7 Additional requirements for preparation of calibration
tubes.
10.7.1 Storage of Calibration Standard Tubes
10.7.1.1 Seal tubes with long-term storage caps immediately
after they have been disconnected from the standard loading manifold
or injection apparatus.
10.7.1.2 Calibration standard tubes may be stored for no longer
than 30 days and should be refrigerated if there is any risk of
chemical interaction or degradation. Audit standards (see section
9.11) are exempt from this criteria and may be stored for the shelf-
life specified on their certificates.
10.8 Keep records for calibration standard tubes to include the
following:
10.8.1 The stock number of any commercial liquid or gas
standards used.
10.8.2 A chromatogram of the most recent blank for each tube
used as a calibration standard together with the associated
analytical conditions and date of cleaning.
10.8.3 Date of standard loading.
10.8.4 List of standard components, approximate masses and
associated confidence levels.
10.8.5 Example analysis of an identical standard with associated
analytical conditions.
10.8.6 A brief description of the method used for standard
preparation.
10.8.7 The standard's expiration date.
10.9 TD/GC/MS using standard tubes to calibrate system response.
10.9.1 Verify that the TD/GC/MS analytical system meets the
instrument performance criteria given in Section 9.1.
10.9.2 The prepared calibration standard tubes must be analyzed
using the analytical conditions applied to field samples (see
Section 11.0) and must be selected to ensure quantitative transfer
and adequate chromatographic resolution of target compounds,
surrogates, and internal standards in order to enable reliable
identification and quantitation of compounds of interest. The
analytical conditions should also be sufficiently stringent to
prevent buildup of higher boiling, non-target contaminants that may
be collected on the tubes during field monitoring.
10.9.3 Calibration range. Each TD/GC/MS system must be
calibrated at five concentrations that span the monitoring range of
interest before being used for sample analysis. This initial multi-
level calibration determines instrument sensitivity under the
analytical conditions selected and the linearity of GC/MS response
for the target compounds. One of the calibration points must be
within a factor of five of the detection limit for the compounds of
interest.
10.9.4 One of the calibration points from the initial
calibration curve must be at the same concentration as the daily CCV
standard (e.g., the mass collected when sampling air at typical
concentrations).
10.9.5 Calibration frequency. Each GC/MS system must be
recalibrated with a full 5-point calibration curve following
corrective action (e.g., ion source cleaning or repair, column
replacement) or if the instrument fails the daily calibration
acceptance criteria.
10.9.5.1 CCV checks must be carried out on a regular routine
basis as described in Section 9.14.
10.9.5.2 Quantitation ions for the target compounds are shown in
Table 10.1. Use the primary ion unless interferences are present, in
which case you should use a secondary ion.
Table 10.1--Clean Air Act Volatile Organic Compounds for Passive Sorbent Sampling
--------------------------------------------------------------------------------------------------------------------------------------------------------
Vapor Characteristic ion(s)
Compound CAS No. BP ([deg]C) pressure MW \b\ ----------------------------------
(mmHg) \a\ Primary Secondary
--------------------------------------------------------------------------------------------------------------------------------------------------------
1,1-Dichloroethene................................... 75-35-4 32 500 96.9 61 96
3-Chloropropene...................................... 107-05-1 44.5 340 76.5 76 41, 39, 78
1,1,2-Trichloro-1,2,2-trifluoroethane-1,1- 75-34-3 57.0 230 99 63 65, 83, 85, 98,
Dichloroethane...................................... 100
1,2-Dichloroethane................................... 107-06-2 83.5 61.5 99 62 98
1,1,1-Trichloroethane................................ 71-55-6 74.1 100 133.4 97 99, 61
Benzene.............................................. 71-43-2 80.1 76.0 78 78 .................
Carbon tetrachloride................................. 56-23-5 76.7 90.0 153.8 117 119
1,2-Dichloropropane.................................. 78-87-5 97.0 42.0 113 63 112
Trichloroethene...................................... 79-01-6 87.0 20.0 131.4 95 97, 130, 132
1,1,2-Trichloroethane................................ 79-00-5 114 19.0 133.4 83 97, 85
Toluene.............................................. 108-88-3 111 22.0 92 92 91
Tetrachloroethene.................................... 127-18-4 121 14.0 165.8 164 129, 131, 166
Chlorobenzene........................................ 108-90-7 132 8.8 112.6 112 77, 114
Ethylbenzene......................................... 100-41-4 136 7.0 106 91 106
m,p-Xylene........................................... 108-38-3, 106- 138 6.5 106.2 106 91
42-3
Styrene.............................................. 100-42-5 145 6.6 104 104 78
o-Xylene............................................. 95-47-6 144 5.0 106.2 106 91
p-Dichlorobenzene.................................... 106-46-7 173 0.60 147 146 111, 148
--------------------------------------------------------------------------------------------------------------------------------------------------------
\a\ Pressure in millimeters of mercury.
\b\ Molecular weight.
11.0 Analytical Procedure
11.1 Preparation for Sample Analysis
11.1.1 Each sequence of analyses must be ordered as follows:
11.1.1.1 CCV.
11.1.1.2 A laboratory blank.
11.1.1.3 Field blank.
11.1.1.4 Sample(s).
11.1.1.5 Field blank.
11.1.1.6 CCV after 10 field samples.
11.1.1.7 CCV at the end of the sample batch.
11.2 Pre-desorption System Checks and Procedures
11.2.1 Ensure all sample tubes and field blanks are at ambient
temperature before removing them from the storage container.
11.2.2 If using an automated TD/GC/MS analyzer, remove the long-
term storage caps from the tubes, replace them with appropriate
analytical caps, and load them into the system in the sequence
described in Section 11.1. Alternatively, if using a manual system,
uncap and analyze each tube, one at a time, in the sequence
described in Section 11.1.
11.2.3 The following thermal desorption system integrity checks
and procedures are required before each tube is analyzed.
[[Page 75341]]
Note: Commercial thermal desorbers should implement these steps
automatically.
11.2.3.1 Tube leak test: Each tube must be leak tested as soon
as it is loaded into the carrier gas flow path before analysis to
ensure data integrity.
11.2.3.2 Conduct the leak test at the GC carrier gas pressure,
without heat or gas flow applied. Tubes that fail the leak test
should not be analyzed, but should be resealed and stored intact. On
automated systems, the instrument should continue to leak test and
analyze subsequent tubes after a given tube has failed. Automated
systems must also store and record which tubes in a sequence have
failed the leak test. Information on failed tubes should be
downloaded with the batch of sequence information from the
analytical system.
11.2.3.3 Leak test the sample flow path. Leak check the sample
flow path of the thermal desorber before each analysis without heat
or gas flow applied to the sample tube. Stop the automatic sequence
of tube desorption and GC analysis if any leak is detected in the
main sample flow path. This process may be carried out as a separate
step or as part of Section 11.2.3.2.
11.2.4 Optional Dry Purge
11.2.4.1 Tubes may be dry purged with a flow of pure dry gas
passing into the tube from the sampling end, to remove water vapor
and other very volatile interferents if required.
11.2.5 Internal Standard (IS) Addition
11.2.5.1 Use the internal standard addition function of the
automated thermal desorber (if available) to introduce a precise
aliquot of the internal standard to the sampling end of each tube
after the leak test and shortly before primary (tube) desorption).
Note: This step can be combined with dry purging the tube
(Section 11.2.4) if required.
11.2.5.2 If the analyzer does not have a facility for automatic
IS addition, gas or liquid internal standard can be manually
introduced to the sampling end of tubes in a flow of carrier gas
using the types of procedure described in Sections 10.3 and 10.4,
respectively.
11.2.6 Pre-purge. Each tube should be purged to vent with
carrier gas flowing in the desorption direction (i.e., flowing into
the tube from the non-sampling end) to remove oxygen before heat is
applied. This is to prevent analyte and sorbent oxidation and to
prevent deterioration of key analyzer components such as the GC
column and mass spectrometer (if applicable). A series of schematics
illustrating these steps is presented in Figures 17.2 and 17.3.
11.3 Analytical Procedure
11.3.1 Steps Required for Thermal Desorption
11.3.1.1 Ensure that the pressure and purity of purge and
carrier gases supplying the TD/GC/MS system, meet manufacturer
specifications and the requirements of this method.
11.3.1.2 Ensure also that the analytical method selected meets
the QC requirements of this method (Section 9) and that all the
analytical parameters are at set point.
11.3.1.3 Conduct predesorption system checks (see Section 11.2).
11.3.1.4 Desorb the sorbent tube under conditions demonstrated
to achieve >95 percent recovery of target compounds (see Section
9.5.2).
Note: Typical tube desorption conditions range from 280-350
[deg]C for 5-15 minutes with a carrier gas flow of 30-100 mL/min
passing through the tube from the non-sampling end such that
analytes are flushed out of the tube from the sampling end. Desorbed
VOCs are concentrated (refocused) on a secondary, cooled sorbent
trap integrated into the analytical equipment (see Figure 17.4). The
focusing trap is typically maintained at a temperature between -30
and +30 [deg]C during focusing. Selection of hydrophobic sorbents
for focusing and setting a trapping temperature of +25 to 27 [deg]C
aid analysis of humid samples because these settings allow selective
elimination of any residual water from the system, prior to GC/MS
analysis.
Note: The transfer of analytes from the tube to the focusing
trap during primary (tube) desorption can be carried out splitless
or under controlled split conditions (see Figure 17.4) depending on
the masses of target compounds sampled and the requirements of the
system--sensitivity, required calibration range, column overload
limitations, etc. Instrument controlled sample splits must be
demonstrated by showing the reproducibility using calibration
standards. Field and laboratory blank samples must be analyzed at
the same split as the lowest calibration standard. During secondary
(trap) desorption the focusing trap is heated rapidly (typically at
rates >40 [deg]C/s) with inert (carrier) gas flowing through the
trap (3-100 mL/min) in the reverse direction to that used during
focusing.
11.3.1.5 The split conditions selected for optimum field sample
analysis must also be demonstrated on representative standards.
Note: Typical trap desorption temperatures are in the range
250-360 [deg]C, with a ``hold'' time of 1-3 minutes at the highest
temperature. Trap desorption automatically triggers the start of GC
analysis. The trap desorption can also be carried out under
splitless conditions (i.e., with everything desorbed from the trap
being transferred to the analytical column and GC detector) or, more
commonly, under controlled split conditions (see Figure 17.4). The
selected split ratio depends on the masses of target compounds
sampled and the requirements of the system--sensitivity, required
calibration range, column overload limitations, etc. If a split is
selected during both primary (trap) desorption and secondary (trap)
desorption, the overall split ratio is the product of the two. Such
`double' split capability gives optimum flexibility for
accommodating concentrated samples as well as trace-level samples on
the TD/GC/MS analytical system. High resolution capillary columns
and most GC/MS detectors tend to work best with approximately 20-200
ng per compound per tube to avoid saturation. The overall split
ratio must be adjusted such that, when it is applied to the sample
mass that is expected to be collected during field monitoring, the
amount reaching the column will be attenuated to fall within this
range. As a rule of thumb this means that ~20 ng samples will
require splitless or very low split analysis, ~2 [micro]g samples
will require a split ratio in the order of ~50:1 and 200 [micro]g
samples will require a double split method with an overall split
ratio in the order of 2,000:1.
11.3.1.6 Analyzed tubes must be resealed with long-term storage
caps immediately after analysis (manual systems) or after completion
of a sequence (automated systems). This prevents contamination,
minimizing the extent of tube reconditioning required before
subsequent reuse.
11.3.2 GC/MS Analytical Procedure
11.3.2.1 Heat/cool the GC oven to its starting set point.
11.3.2.2 If using a GC/MS system, it can be operated in either
MS-Scan or MS-SIM mode (depending on required sensitivity levels and
the type of mass spectrometer selected). As soon as trap desorption
and transfer of analytes into the GC column triggers the start of
the GC/MS analysis, collect mass spectral data over a range of
masses from 35 to 300 amu. Collect at least 10 data points per
eluting chromatographic peak in order to adequately integrate and
quantify target compounds.
11.3.2.3 Use secondary ion quantitation only when there are
sample matrix interferences with the primary ion. If secondary ion
quantitation is performed, flag the data and document the reasons
for the alternative quantitation procedure.
11.3.2.4 Data reduction is performed by the instruments post
processing program that is automatically accessed after data
acquisition is completed at the end of the GC run. The concentration
of each target compound is calculated using the previously
established response factors for the CCV analyzed in Section
11.1.1.6.
11.3.2.5 Whenever the thermal desorption--GC/MS analytical
method is changed or major equipment maintenance is performed, you
must conduct a new five-level calibration (see Section 10.6.3).
System calibration remains valid as long as results from subsequent
CCV are within 30 percent of the most recent 5-point calibration
(see Section 10.9.5). Include relevant CCV data in the supporting
information in the data report for each set of samples.
11.3.2.6 Document, flag and explain all sample results that
exceed the calibration range. Report flags and provide documentation
in the analytical results for the affected sample(s).
12.0 Data Analysis, Calculations, and Reporting
12.1 Recordkeeping Procedures for Sorbent Tubes
12.1.1 Label sample tubes with a unique identification number as
described in Section 6.3.
12.1.2 Keep records of the tube numbers and sorbent lots used
for each sampling period.
12.1.3 Keep records of sorbent tube packing if tubes are
manually prepared in the
[[Page 75342]]
laboratory and not supplied commercially. These records must include
the masses and/or bed lengths of sorbent(s) contained in each tube,
the maximum allowable temperature for that tube and the date each
tube was packed. If a tube is repacked at any stage, record the date
of tube repacking and any other relevant information required in
Section 12.1.
12.1.4 Keep records of the conditioning and blanking of tubes.
These records must include, but are not limited to, the unique
identification number and measured background resulting from the
tube conditioning.
12.1.5 Record the location, dates, tube identification and times
associated with each sample collection. Record this information on a
Chain of Custody form that is sent to the analytical laboratory.
12.1.6 Field sampling personnel must complete and send a Chain
of Custody to the analysis laboratory (see Section 8.6.4 of Method
325A for what information to include and Section 17.0 of this method
for an example form). Duplicate copies of the Chain of Custody must
be included with the sample report and stored with the field test
data archive.
12.1.7 Field sampling personnel must also keep records of the
unit vector wind direction, sigma theta, temperature and barometric
pressure averages for the sampling period. See Section 8.3.4 of
Method 325A.
12.1.8 Laboratory personnel must record the sample receipt date,
and analysis date.
12.1.9 Laboratory personnel must maintain records of the
analytical method and sample results in electronic or hardcopy in
sufficient detail to reconstruct the calibration, sample, and
quality control results from each sampling period.
12.2 Calculations
12.2.1 Complete the calculations in this section to determine
compliance with calibration quality control criteria (see also Table
17.1).
12.2.1.1 Response factor (RF). Calculate the RF using Equation
12.1:
[GRAPHIC] [TIFF OMITTED] TR01DE15.035
Where:
As = Peak area for the characteristic ion of the analyte.
Ais = Peak area for the characteristic ion of the
internal standard.
Ms = Mass of the analyte.
Mis = Mass of the internal standard.
12.2.1.2 Standard deviation of the response factors
(SDRF). Calculate the SDRF using Equation 12.2:
[GRAPHIC] [TIFF OMITTED] TR01DE15.036
Where:
RFi = RF for each of the calibration compounds.
RF = Mean RF for each compound from the initial calibration.
n = Number of calibration standards.
12.2.1.3 Percent deviation (%DEV). Calculate the %DEV using
Equation 12.3:
[GRAPHIC] [TIFF OMITTED] TR01DE15.037
Where:
SDRF = Standard deviation.
RF = Mean RF for each compound from the initial calibration.
12.2.1.4 Relative percent difference (RPD). Calculate the RPD
using Equation 12.4:
[GRAPHIC] [TIFF OMITTED] TR01DE15.038
Where:
R1, R2 = Values that are being compared (i.e., response factors in
CCV).
12.2.2 Determine the equivalent concentration of compounds in
atmospheres as follows.
12.2.3 Correct target concentrations determined at the sampling
site temperature and atmospheric pressure to standard conditions (25
[deg]C and 760 mm mercury) using Equation 12.5 (Reference 21).
[GRAPHIC] [TIFF OMITTED] TR01DE15.039
Where:
tss = The average temperature during the collection
period at the sampling site (K).
Pss = The average pressure at the sampling site during
the collection period (mm Hg).
U = The diffusive uptake rate (sampling rate) (mL/min).
[[Page 75343]]
12.2.4 For passive sorbent tube samples, calculate the
concentration of the target compound(s) in the sampled air, in
[mu]g/m3 by using Equation 12.6 (Reference 22).
[GRAPHIC] [TIFF OMITTED] TR01DE15.040
Where:
Cm = The concentration of target compound in the air
sampled ([mu]g/m3).
mmeas = The mass of the compound as measured in the
sorbent tube ([mu]g).
UNTP = The diffusive uptake rate corrected for local
conditions (sampling rate) (mL/min).
t = The exposure time (minutes).
Note: Diffusive uptake rates for common VOCs, using carbon
sorbents packed into sorbent tubes of the dimensions specified in
Section 6.1, are listed in Table 12.1. Adjust analytical conditions
to keep expected sampled masses within range (see Sections 11.3.1.3
to 11.3.1.5). Best possible method detection limits are typically in
the order of 0.1 ppb for 1,3-butadiene and 0.05 ppb for volatile
aromatics such as benzene for 14-day monitoring. However, actual
detection limits will depend upon the analytical conditions
selected.
Table 12.1--Validated Sorbents and Uptake Rates (mL/min) for Selected Clean Air Act Compounds
----------------------------------------------------------------------------------------------------------------
Compound Carbopack\TM\ X\a\ Carbograph\TM\ 1 TD Carbopack\TM\ B
----------------------------------------------------------------------------------------------------------------
1,1-Dichloroethene............... 0.57 not available.............. not available.
0.14
3-Chloropropene.................. 0.51 not available.............. not available.
0.3
1,1-Dichloroethane............... 0.57 not available.............. not available.
0.1
1,2-Dichloroethane............... 0.57 not available.............. not available.
0.08
1,1,1-Trichloroethane............ 0.51 not available.............. not available.
0.1
Benzene.......................... 0.67 0.63 0.07\b\.. 0.63 0.07\b\.
0.06
Carbon tetrachloride............. 0.51 not available.............. not available.
0.06
1,2-Dichloropropane.............. 0.52 not available.............. not available.
0.1
Trichloroethene.................. 0.5 not available.............. not available.
0.05
1,1,2-Trichloroethane............ 0.49 not available.............. not available.
0.13
Toluene.......................... 0.52 0.56 0.06\c\.. 0.56 0.06\c\.
0.14
Tetrachloroethene................ 0.48 not available.............. not available.
0.05
Chlorobenzene.................... 0.51 not available.............. not available.
0.06
Ethylbenzene..................... 0.46 not available.............. 0.50\c\.
0.07
m,p-Xylene....................... 0.46 0.47 0.04\c\.. 0.47 0.04\c\.
0.09
Styrene.......................... 0.5 not available.............. not available.
0.14
o-Xylene......................... 0.46 0.47 0.04\c\.. 0.47 0.04\c\.
0.12
p-Dichlorobenzene................ 0.45 not available.............. not available.
0.05
----------------------------------------------------------------------------------------------------------------
\a\ Reference 3, McClenny, J. Environ. Monit. 7:248-256. Based on 24-hour duration.
\b\ Reference 24, BS EN 14662-4:2005 (incorporated by reference--see Sec. 63.14). Based on 14-day duration.
\c\ Reference 25, ISO 16017-2:2003(E) (incorporated by reference--see Sec. 63.14). Based on 14-day duration.
13.0 Method Performance
The performance of this procedure for VOC not listed in Table
12.1 is determined using the procedure in Addendum A of this Method
or by one of the following national/international standard methods:
ISO 16017-2:2003(E), ASTM D6196-03 (Reapproved 2009), or BS EN
14662-4:2005 (all incorporated by reference--see Sec. 63.14).
13.1 The valid range for measurement of VOC is approximately 0.5
[micro]g/m\3\ to 5 mg/m\3\ in air, collected over a 14-day sampling
period. The upper limit of the useful range depends on the split
ratio selected (Section 11.3.1) and the dynamic range of the
analytical system. The lower limit of the useful range depends on
the noise from the analytical instrument detector and on the blank
level of target compounds or interfering compounds on the sorbent
tube (see Section 13.3).
13.2 Diffusive sorbent tubes compatible with passive sampling
and thermal desorption methods have been evaluated at relatively
high atmospheric concentrations (i.e., mid-ppb to ppm) and published
for use in workplace air and industrial/mobile source emissions
(References 15-16, 21-22).
13.3 Best possible detection limits and maximum quantifiable
concentrations of air pollutants range from sub-part-per-trillion
(sub-ppt) for halogenated species such as CCl4 and the freons using
an electron capture detector (ECD), SIM Mode GC/MS, triple quad MS
or GC/TOF MS to sub-ppb for volatile hydrocarbons collected over 72
hours followed by analysis using GC with quadrupole MS operated in
the full SCAN mode.
13.3.1 Actual detection limits for atmospheric monitoring vary
depending on several key factors. These factors are:
Minimum artifact levels.
GC detector selection.
Time of exposure for passive sorbent tubes.
Selected analytical conditions, particularly column
resolution and split ratio.
14.0 Pollution Prevention
This method involves the use of ambient concentrations of
gaseous compounds that post little or no danger of pollution to the
environment.
15.0 Waste Management
Dispose of expired calibration solutions as hazardous materials.
Exercise standard laboratory environmental practices to minimize the
use and disposal of laboratory solvents.
16.0 References
1. Winberry, W. T. Jr., et al., Determination of Volatile Organic
Compounds in Ambient Air Using Active Sampling onto Sorbent Tubes:
Method TO-17r, Second Edition, U.S. Environmental Protection Agency,
Research Triangle Park, NC 27711, January 1999. https://www.epa.gov/ttnamti1/airtox.html#compendium
2. Ciccioli, P., Brancaleoni, E., Cecinato, A., Sparapini, R., and
Frattoni, M., ``Identification and Determination of Biogenic and
Anthropogenic VOCs in Forest Areas of Northern and Southern Europe
and a Remote Site of the Himalaya Region by High-resolution GC-MS,''
J. of Chrom., 643, pp 55-69, 1993.
3. McClenny, W.A., K.D. Oliver, H.H. Jacumin, Jr., E.H. Daughtrey,
Jr., D.A. Whitaker. 2005. 24 h diffusive sampling of toxic VOCs in
air onto Carbopack\TM\ X solid adsorbent followed by thermal
[[Page 75344]]
desorption/GC/MS analysis--laboratory studies. J. Environ. Monit.
7:248-256.
4. Markes International (www.markes.com/publications): Thermal
desorption Technical Support Note 2: Prediction of uptake rates for
diffusive tubes.
5. Ciccioli, P., Brancaleoni, E., Cecinato, A., DiPalo, C.,
Brachetti, A., and Liberti, A., ``GC Evaluation of the Organic
Components Present in the Atmosphere at Trace Levels with the Aid of
CarbopackTM B for Preconcentration of the Sample,'' J. of
Chrom., 351, pp 433-449, 1986.
6. Broadway, G. M., and Trewern, T., ``Design Considerations for the
Optimization of a Packed Thermal Desorption Cold Trap for Capillary
Gas Chromatography,'' Proc. 13th Int'l Symposium on Capil. Chrom.,
Baltimore, MD, pp 310-320, 1991.
7. Broadway, G. M., ``An Automated System for use Without Liquid
Cryogen for the Determination of VOC's in Ambient Air,'' Proc. 14th
Int'l. Symposium on Capil. Chrom., Baltimore, MD, 1992.
8. Gibitch, J., Ogle, L., and Radenheimer, P., ``Analysis of Ozone
Precursor Compounds in Houston, Texas Using Automated Continuous
GCs,'' in Proceedings of the Air and Waste Management Association
Conference: Measurement of Toxic and Related Air Pollutants, Air and
Waste Management Association, Pittsburgh, PA, May 1995.
9. Vandendriessche, S., and Griepink, B., ``The Certification of
Benzene, Toluene and m-Xylene Sorbed on Tenax[supreg] TA in Tubes,''
CRM-112 CEC, BCR, EUR12308 EN, 1989.
10. MDHS 2 (Acrylonitrile in Air), ``Laboratory Method Using Porous
Polymer Adsorption Tubes, and Thermal Desorption with Gas
Chromatographic Analysis,'' Methods for the Determination of
Hazardous Substances (MDHS), UK Health and Safety Executive,
Sheffield, UK.
11. MDHS 22 (Benzene in Air), ``Laboratory Method Using Porous
Polymer Adsorbent Tubes, Thermal Desorption and Gas
Chromatography,'' Method for the Determination of Hazardous
Substances (MDHS), UK Health and Safety Executive, Sheffield, UK.
12. MDHS 23 (Glycol Ether and Glycol Acetate Vapors in Air),
``Laboratory Method Using Tenax[supreg] Sorbent Tubes, Thermal
Desorption and Gas Chromatography,'' Method for the Determination of
Hazardous Substances (MDHS), UK Health and Safety Executive,
Sheffield, UK.
13. MDHS 40 (Toluene in air), ``Laboratory Method Using Pumped
Porous Polymer Adsorbent Tubes, Thermal Desorption and Gas
Chromatography,'' Method for the Determination of Hazardous
Substances (MDHS), UK Health and Safety Executive, Sheffield, UK.
14. MDHS 60 (Mixed Hydrocarbons (C to C) in Air), ``Laboratory
Method Using Pumped Porous Polymer 3 10 and Carbon Sorbent Tubes,
Thermal Desorption and Gas Chromatography,'' Method for the
Determination of Hazardous Substances (MDHS), UK Health and Safety
Executive, Sheffield, UK.
15. Price, J. A., and Saunders, K. J., ``Determination of Airborne
Methyl tert-Butyl Ether in Gasoline Atmospheres,'' Analyst, Vol.
109, pp. 829-834, July 1984.
16. Coker, D. T., van den Hoed, N., Saunders, K. J., and Tindle, P.
E., ``A Monitoring Method for Gasoline Vapour Giving Detailed
Composition,'' Ann. Occup, Hyg., Vol 33, No. 11, pp 15-26, 1989.
17. DFG, ``Analytische Methoden zur prufing gesundheitsschadlicher
Arbeistsstoffe,'' Deutsche Forschungsgemeinschaft, Verlag Chemie,
Weinheim FRG, 1985.
18. NNI, ``Methods in NVN Series (Luchtkwaliteit;
Werkplekatmasfeer),'' Nederlands Normailsatie--Institut, Delft, The
Netherlands, 1986-88.
19. ``Sampling by Solid Adsorption Techniques,'' Standards
Association of Australia Organic Vapours, Australian Standard 2976,
1987.
20. Woolfenden, E. A., ``Monitoring VOCs in Air Using Pumped
Sampling onto Sorbent Tubes Followed by Thermal Desorption-capillary
GC Analysis: Summary of Reported Data and Practical Guidelines for
Successful Application,'' J. Air & Waste Manage. Assoc., Vol. 47,
1997, pp. 20-36.
21. Validation Guidelines for Air Sampling Methods Utilizing
Chromatographic Analysis, OSHA T-005, Version 3.0, May 2010, https://www.osha.gov/dts/sltc/methods/chromguide/chromguide.pdf.
22. ASTM D4597-10, Standard Practice for Sampling Workplace
Atmospheres to collect Gases or Vapors with Solid Sorbent Diffusive
Samplers.
23. Martin, https://www.hsl.gov.uk/media/1619/issue14.pdf.
24. BS EN 14662-4:2005, Ambient air quality--Standard method for the
measurement of benzene concentrations--Part 4: Diffusive sampling
followed by thermal desorption and gas chromatography.
25. ISO 16017-2:2003(E): Indoor, ambient and workplace air--Sampling
and analysis of volatile organic compounds by sorbent tube/thermal
desorption/capillary gas chromatography--Part 2: Diffusive sampling.
17.0 Tables, Diagrams, Flowcharts and Validation Data
Table 17.1--Summary of GC/MS Analysis Quality Control Procedures
----------------------------------------------------------------------------------------------------------------
Parameter Frequency Acceptance criteria Corrective action
----------------------------------------------------------------------------------------------------------------
Bromofluorobenzene Instrument Tune Daily\a\ prior to Evaluation criteria (1) Retune and or
Performance Check. sample analysis. presented in Section (2) Perform
9.5 and Table 9.2. Maintenance.
Five point calibration bracketing the Following any major (1) Percent Deviation (1) Repeat calibration
expected sample concentration. change, repair or (%DEV) of response sample analysis.
maintenance or if factors 30%. check.
meet method (2) Relative Retention (3) Prepare new
requirements. Times (RRTs) for calibration standards
Recalibration not to target peaks 0.06 units from repeat analysis.
mean RRT.
Calibration Verification (CCV Second Following the The response factor (1) Repeat calibration
source calibration verification calibration curve. 30% DEV check.
check). from calibration curve (2) Repeat calibration
average response curve.
factor.
Laboratory Blank Analysis............ Daily \a\ following (1) <=0.2 ppbv per (1) Repeat analysis
bromofluoro- benzene analyte or <=3 times with new blank tube.
and calibration check; the LOD, whichever is (2) Check system for
prior to sample greater. leaks, contamination.
analysis. (2) Internal Standard 3) Analyze additional
(IS) area response blank.
40% and IS
Retention Time (RT)
0.33 min.
of most recent
calibration check.
Blank Sorbent Tube Certification..... One tube analyzed for <0.2 ppbv per VOC Reclean all tubes in
each batch of tubes targeted compound or 3 batch and reanalyze.
cleaned or 10 percent times the LOD,
of tubes whichever is whichever is greater.
greater.
Samples--Internal Standards.......... All samples............ IS area response 40% and IS RT invalidation.
0.33 min.
of most recent
calibration validation.
----------------------------------------------------------------------------------------------------------------
\a\ Every 24 hours.
[[Page 75345]]
BILLING CODE 6560-50-P
[GRAPHIC] [TIFF OMITTED] TR01DE15.041
[[Page 75346]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.042
[[Page 75347]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.043
[[Page 75348]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.044
BILLING CODE 6560-50-C
ADDENDUM A to Method 325B--Method 325 Performance Evaluation
A.1 Scope and Application
A.1.1 To be measured by Methods 325A and 325B, each new target
volatile organic compound (VOC) or sorbent that is not listed in
Table 12.1 must be evaluated by exposing the selected sorbent tube
to a known concentration of the target compound(s) in an exposure
chamber following the procedure in this Addendum or by following the
procedures in the national/international standard methods: ISO
16017-2:2003(E),
[[Page 75349]]
ASTM D6196-03 (Reapproved 2009), or BS EN 14662-4:2005 (all
incorporated by reference--see Sec. 63.14), or reported in peer-
reviewed open literature.
A.1.2 You must determine the uptake rate and the relative
standard deviation compared to the theoretical concentration of
volatile material in the exposure chamber for each of the tests
required in this method. If data that meet the requirement of this
Addendum are available in the peer reviewed open literature for VOCs
of interest collected on your passive sorbent tube configuration,
then such data may be submitted in lieu of the testing required in
this Addendum.
A.1.3 You must expose sorbent tubes in a test chamber to parts
per trillion by volume (pptv) and low parts per billion by volume
(ppbv) concentrations of VOCs in humid atmospheres to determine the
sorbent tube uptake rate and to confirm compound capture and
recovery.
A.2 Summary of Method
Note: The technique described here is one approach for
determining uptake rates for new sorbent/sorbate pairs. It is
equally valid to follow the techniques described in any one of the
following national/international standards methods: ISO 16017-
2:2003(E), ASTM D6196-03 (Reapproved 2009), or BS EN 14662-4:2005
(all incorporated by reference--see Sec. 63.14).
A.2.1 Known concentrations of VOC are metered into an exposure
chamber containing sorbent tubes filled with media selected to
capture the volatile organic compounds of interest (see Figure A.1
and A.2 for an example of the exposure chamber and sorbent tube
retaining rack). VOC are diluted with humid air and the chamber is
allowed to equilibrate for 6 hours. Clean passive sampling devices
are placed into the chamber and exposed for a measured period of
time. The passive uptake rate of the passive sampling devices is
determined using the standard and dilution gas flow rates. Chamber
concentrations are confirmed with whole gas sample collection and
analysis or direct interface volatile organic compound measurement
methods.
A.2.2 An exposure chamber and known gas concentrations must be
used to challenge and evaluate the collection and recovery of target
compounds from the sorbent and tube selected to perform passive
measurements of VOC in atmospheres.
A.3 Definitions
A.3.1 cc is cubic centimeter.
A.3.2 ECD is electron capture detector.
A.3.3 FID is flame ionization detector.
A.3.4 LED is light-emitting diode.
A.3.5 MFC is mass flow controller.
A.3.6 MFM is mass flow meter.
A.3.7 min is minute.
A.3.8 ppbv is parts per billion by volume.
A.3.9 ppmv is parts per million by volume.
A.3.10 PSD is passive sampling device.
A.3.11 psig is pounds per square inch gauge.
A.3.12 RH is relative humidity.
A.3.13 VOC is volatile organic compound.
A.4 Interferences
A.4.1 VOC contaminants in water can contribute interference or
bias results high. Use only distilled, organic-free water for
dilution gas humidification.
A.4.2 Solvents and other VOC-containing liquids can contaminate
the exposure chamber. Store and use solvents and other VOC-
containing liquids in the exhaust hood when exposure experiments are
in progress to prevent the possibility of contamination of VOCs into
the chamber through the chamber's exhaust vent.
Note: Whenever possible, passive sorbent evaluation should be
performed in a VOC free laboratory.
A.4.3 PSDs should be handled by personnel wearing only clean,
white cotton or powder free nitrile gloves to prevent contamination
of the PSDs with oils from the hands.
A.4.4 This performance evaluation procedure is applicable to
only volatile materials that can be measured accurately with direct
interface gas chromatography or whole gas sample collection,
concentration and analysis. Alternative methods to confirm the
concentration of volatile materials in exposure chambers are subject
to Administrator approval.
A.5 Safety
A.5.1 This procedure does not address all of the safety concerns
associated with its use. It is the responsibility of the user of
this standard to establish appropriate field and laboratory safety
and health practices and determine the applicability of regulatory
limitations prior to use.
A.5.2 Laboratory analysts must exercise appropriate care in
working with high-pressure gas cylinders.
A.6 Equipment and Supplies
A.6.1 You must use an exposure chamber of sufficient size to
simultaneously expose a minimum of eight sorbent tubes.
A.6.2 Your exposure chamber must not contain VOC that interfere
with the compound under evaluation. Chambers made of glass and/or
stainless steel have been used successfully for measurement of known
concentration of selected VOC compounds.
A.6.3 The following equipment and supplies are needed:
Clean, white cotton or nitrile gloves;
Conditioned passive sampling device tubes and diffusion
caps; and
NIST traceable high resolution digital gas mass flow
meters (MFMs) or flow controllers (MFCs).
A.7 Reagents and Standards
A.7.1 You must generate an exposure gas that contains between 35
and 75 percent relative humidity and a concentration of target
compound(s) within 2 to 5 times the concentration to be measured in
the field.
A.7.2 Target gas concentrations must be generated with certified
gas standards and diluted with humid clean air. Dilution to reach
the desired concentration must be done with zero grade air or
better.
A.7.3 The following reagents and standards are needed:
Distilled water for the humidification;
VOC standards mixtures in high-pressure cylinder
certified by the supplier (Note: The accuracy of the certified
standards has a direct bearing on the accuracy of the measurement
results. Typical vendor accuracy is 5 percent accuracy
but some VOC may only be available at lower accuracy (e.g., acrolein
at 10 percent)); and
Purified dilution air containing less than 0.2 ppbv of
the target VOC.
A.8 Sample Collection, Preservation and Storage
A.8.1 You must use certified gas standards diluted with humid
air. Generate humidified air by adding distilled organic free water
to purified or zero grade air. Humidification may be accomplished by
quantitative addition of water to the air dilution gas stream in a
heated chamber or by passing purified air through a humidifying
bubbler. You must control the relative humidity in the test gas
throughout the period of passive sampler exposure.
Note: The RH in the exposure chamber is directly proportional
to the fraction of the purified air that passes through the water in
the bubbler before entering the exposure chamber. Achieving uniform
humidification in the proper range is a trial-and-error process with
a humidifying bubbler. You may need to heat the bubbler to achieve
sufficient humidity. An equilibration period of approximately 15
minutes is required following each adjustment of the air flow
through the humidifier. Several adjustments or equilibration cycles
may be required to achieve the desired RH level.
Note: You will need to determine both the dilution rate and the
humidification rate for your design of the exposure chamber by trial
and error before performing method evaluation tests.
A.8.2 Prepare and condition sorbent tubes following the
procedures in Method 325B Section 7.0.
A.8.3 You must verify that the exposure chamber does not leak.
A.8.4 You must complete two evaluation tests using a minimum of
eight passive sampling tubes in each test with less than 5-percent
depletion of test analyte by the samplers.
A.8.4.1 Perform at least one evaluation at two to five times the
estimated analytical detection limit or less.
A.8.4.2 Perform second evaluation at a concentration equivalent
to the middle of the analysis calibration range.
A.8.5 You must evaluate the samplers in the test chamber
operating between 35 percent and 75 percent RH, and at 25 5 [deg]C. Allow the exposure chamber to equilibrate for 6
hours before starting an evaluation.
A.8.6 The flow rate through the chamber must be <=0.5 meter per
second face velocity across the sampler face.
A.8.7 Place clean, ready to use sorbent tubes into the exposure
chamber for predetermined amounts of time to evaluate collection and
recovery from the tubes. The exposure time depends on the
concentration of volatile test material in the chamber and the
detection limit required for the sorbent tube sampling application.
Exposure time
[[Page 75350]]
should match sample collection time. The sorbent tube exposure
chamber time may not be less than 24 hours and should not be longer
than 2 weeks.
A.8.7.1 To start the exposure, place the clean PSDs equipped
with diffusion caps on the tube inlet into a retaining rack.
A.8.7.2 Place the entire retaining rack inside the exposure
chamber with the diffusive sampling end of the tubes facing into the
chamber flow. Seal the chamber and record the exposure start time,
chamber RH, chamber temperature, PSD types and numbers, orientation
of PSDs, and volatile material mixture composition (see Figure A.2).
A.8.7.3 Diluted, humidified target gas must be continuously fed
into the exposure chamber during cartridge exposure. Measure the
flow rate of target compound standard gas and dilution air to an
accuracy of 5 percent.
A.8.7.4 Record the time, temperature, and RH at the beginning,
middle, and end of the exposure time.
A.8.7.5 At the end of the exposure time, remove the PSDs from
the exposure chamber. Record the exposure end time, chamber RH, and
temperature.
BILLING CODE 6560-50-P
[GRAPHIC] [TIFF OMITTED] TR01DE15.045
[[Page 75351]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.046
[[Page 75352]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.047
BILLING CODE 6560-50-C
A.9 Quality Control
A.9.1 Monitor and record the exposure chamber temperature and RH
during PSD exposures.
A.9.2 Measure the flow rates of standards and purified humified
air immediately following PSD exposures.
A.10 Calibration and Standardization
A.10.1 Follow the procedures described in Method 325B Section
10.0 for calibration.
A.10.2 Verify chamber concentration by direct injection into a
gas chromatograph calibrated for the target compound(s) or by
collection of an integrated SUMMA canister followed by analysis
using a preconcentration gas chromatographic method such as EPA
Compendium Method TO-15, Determination of VOCs in Air Collected in
Specially-Prepared Canisters and Analyzed By GC/MS.
A.10.2.1 To use direct injection gas chromatography to verify
the exposure chamber concentration, follow the procedures in Method
18 of 40 CFR part 60, Appendix A-6. The method ASTM D6420-99
(Reapproved 2010) (incorporated by reference--see Sec. 63.14) is an
acceptable alternative to EPA Method 18 of 40 CFR part 60).
Note: Direct injection gas chromatography may not be
sufficiently sensitive for all compounds. Therefore, the whole gas
preconcentration sample and analysis method may be required to
measure at low concentrations.
A.10.2.2 To verify exposure chamber concentrations using SUMMA
canisters,
[[Page 75353]]
prepare clean canister(s) and measure the concentration of VOC
collected in an integrated SUMMA canister over the period used for
the evaluation (minimum 24 hours). Analyze the TO-15 canister sample
following EPA Compendium Method TO-15.
A.10.2.3 Compare the theoretical concentration of volatile
material added to the test chamber to the measured concentration to
confirm the chamber operation. Theoretical concentration must agree
with the measured concentration within 30 percent.
A.11 Analysis Procedure
Analyze the sorbent tubes following the procedures described in
Section 11.0 of Method 325B.
A.12 Recordkeeping Procedures for Sorbent Tube Evaluation
Keep records for the sorbent tube evaluation to include at a
minimum the following information:
A.12.1 Sorbent tube description and specifications.
A.12.2 Sorbent material description and specifications.
A.12.3 Volatile analytes used in the sampler test.
A.12.4 Chamber conditions including flow rate, temperature, and
relative humidity.
A.12.5 Relative standard deviation of the sampler results at the
conditions tested.
A.12.6 95 percent confidence limit on the sampler overall
accuracy.
A.12.7 The relative accuracy of the sorbent tube results
compared to the direct chamber measurement by direct gas
chromatography or SUMMA canister analysis.
A.13 Method Performance
A.13.1 Sorbent tube performance is acceptable if the relative
accuracy of the passive sorbent sampler agrees with the active
measurement method by 10 percent at the 95 percent
confidence limit and the uptake ratio is equal to greater than 0.5
mL/min (1 ng/ppm-min).
Note: For example, there is a maximum deviation comparing
Perkin-Elmer passive type sorbent tubes packed with Carbopack\TM\ X
of 1.3 to 10 percent compared to active sampling using the following
uptake rates.
----------------------------------------------------------------------------------------------------------------
1,3-butadiene Estimated Estimated
uptake rate mL/ detection limit Benzene uptake detection limit (2
min (2 week) rates mL/min week)
----------------------------------------------------------------------------------------------------------------
Carbopack\TM\ X (2 week)........ 0.61 0.1 ppbv 0.67 \a\ 0.05 ppbv
0.11 \a\
----------------------------------------------------------------------------------------------------------------
\a\ McClenny, W.A., K.D. Oliver, H.H. Jacumin, Jr., E.H. Daughtrey, Jr., D.A. Whitaker. 2005. 24 h diffusive
sampling of toxic VOCs in air onto Carbopack\TM\ X solid adsorbent followed by thermal desorption/GC/MS
analysis--laboratory studies. J. Environ. Monit. 7:248-256.
A13.2 Data Analysis and Calculations for Method Evaluation
A.13.2.1 Calculate the theoretical concentration of VOC
standards using Equation A.1.
[GRAPHIC] [TIFF OMITTED] TR01DE15.048
Where:
Cf = The final concentration of standard in the exposure
chamber (ppbv).
FRi = The flow rate of the target compound I (mL/min).
FRt = The flow rate of all target compounds from separate
if multiple cylinders are used (mL/min).
FRa = The flow rate of dilution air plus moisture (mL/
min).
Cs = The concentration of target compound in the standard
cylinder (parts per million by volume).
A.13.2.3 Determine the uptake rate of the target gas being
evaluated using Equation A.2.
[GRAPHIC] [TIFF OMITTED] TR01DE15.049
Where:
Mx = The mass of analyte measured on the sampling tube
([eta]g).
Ce = The theoretical exposure chamber concentration
([eta]g/mL).
Tt = The exposure time (minutes).
A.13.2.4 Estimate the variance (relative standard deviation
(RSD)) of the inter-sampler results at each condition tested using
Equation A.3. RSD for the sampler is estimated by pooling the
variance estimates from each test run.
[GRAPHIC] [TIFF OMITTED] TR01DE15.050
Where:
Xi = The measured mass of analyte found on sorbent tube
i.
Xi = The mean value of all Xi.
n = The number of measurements of the analyte.
A.13.2.4 Determine the percent relative standard deviation of
the inter-sampler results using Equation A.4.
[[Page 75354]]
[GRAPHIC] [TIFF OMITTED] TR01DE15.051
A.13.2.5 Determine the 95 percent confidence interval for the
sampler results using Equation A.5. The confidence interval is
determined based on the number of test runs performed to evaluate
the sorbent tube and sorbent combination. For the minimum test
requirement of eight samplers tested at two concentrations, the
number of tests is 16 and the degrees of freedom are 15.
[GRAPHIC] [TIFF OMITTED] TR01DE15.052
Where:
[Delta]95% = 95 percent confidence interval.
%RSD = percent relative standard deviation.
t0.95 = The Students t statistic for f degrees of freedom
at 95 percent confidence.
f = The number of degrees of freedom.
n = Number of samples.
A.13.2.6 Determine the relative accuracy of the sorbent tube
combination compared to the active sampling results using Equation
A.6.
[GRAPHIC] [TIFF OMITTED] TR01DE15.053
Where:
RA = Relative accuracy.
Xi = The mean value of all Xi.
Xi = The average concentration of analyte measured by the
active measurement method.
[Delta]95% = 95 percent confidence interval.
A.14 Pollution Prevention
This method involves the use of ambient concentrations of
gaseous compounds that post little or no pollution to the
environment.
A.15 Waste Management
Expired calibration solutions should be disposed of as hazardous
materials.
A.16 References
1. ISO TC 146/SC 02 N 361 Workplace atmospheres--Protocol for
evaluating the performance of diffusive samplers.
[FR Doc. 2015-26486 Filed 11-30-15; 8:45 am]
BILLING CODE 6560-50-P