Approval and Promulgation of Implementation Plans; State of Colorado; Regional Haze State Implementation Plan, 29953-29959 [2015-12491]
Download as PDF
wreier-aviles on DSK5TPTVN1PROD with RULES
Federal Register / Vol. 80, No. 100 / Tuesday, May 26, 2015 / Rules and Regulations
During the enforcement period, persons
and vessels are prohibited from entering
into, transiting through, or anchoring
within this regulated area unless
authorized by the Captain of the Port, or
his designated representative.
DATES: The regulations for the safety
zone listed in 33 CFR 165.1123, Table
1, Item 7, will be enforced from 8:30
p.m. to 10:30 p.m. on several dates
between May 23, 2015, and September
6, 2015.
FOR FURTHER INFORMATION CONTACT: If
you have questions on this publication,
call or email Petty Officer Nick
Bateman, Waterways Management, U.S.
Coast Guard Sector San Diego, CA;
telephone (619) 278–7656, email D11PF-MarineEventsSanDiego@uscg.mil.
SUPPLEMENTARY INFORMATION: The Coast
Guard will enforce the safety zone in
Mission Bay, California, for the annual
2015 Sea World San Diego Fireworks
Display (Item 7 on Table 1 of 33 CFR
165.1123), on May 23 through May 25,
June 13 through June 30, July 1 through
July 31, August 1 through August 9,
August 15, August 22, August 29,
September 5, and September 6, 2015.
The safety zone is located off of the
south side of Fiesta Island adjacent to
Sea World.
Under the provisions of 33 CFR
165.1123, persons and vessels are
prohibited during the fireworks display
times from entering into, transiting
through, or anchoring within the 800
foot regulated area safety zone around
the fireworks barge, located in
approximate position 32°46′03″ N.,
117°13′11″ W., unless authorized by the
Captain of the Port, or his designated
representative. Persons or vessels
desiring to enter into or pass through
the safety zone may request permission
from the Captain of the Port or a
designated representative. The Coast
Guard Captain of the Port or designated
representative can be reached via VHF
CH 16 or at (619) 278–7033. If
permission is granted, all persons and
vessels shall comply with the
instructions of the Captain of the Port or
designated representative. Spectator
vessels may safely transit outside the
regulated area, but may not anchor,
block, loiter, or impede the transit of
official fireworks support, event vessels
or enforcement patrol vessels. The Coast
Guard may be assisted by other Federal,
State, or local law enforcement agencies
in enforcing this regulation.
This notice is issued under authority
of 5 U.S.C. 552(a) and 33 CFR 165.1123.
In addition to this notice in the Federal
Register, the Coast Guard will provide
the maritime community with advance
notification of this enforcement period
VerDate Sep<11>2014
14:03 May 22, 2015
Jkt 235001
via the Local Notice to Mariners,
Broadcast Notice to Mariners, and local
advertising by the event sponsor.
If the Coast Guard determines that the
regulated area need not be enforced for
the full duration stated on this notice,
then a Broadcast Notice to Mariners or
other communications coordinated with
the event sponsor will grant general
permission to enter the regulated area.
Dated: May 8, 2015.
J.A. Janszen,
Captain, U.S. Coast Guard, Acting, Captain
of the Port San Diego.
[FR Doc. 2015–12555 Filed 5–22–15; 8:45 am]
BILLING CODE 9110–04–P
DEPARTMENT OF HOMELAND
SECURITY
29953
Federal, State, or local law enforcement
agencies in enforcing this regulation.
This notice of enforcement is issued
under authority of 33 CFR 165.118 and
5 U.S.C. 552 (a). In addition to this
notification in the Federal Register, the
Coast Guard will provide mariners with
advanced notification of enforcement
periods via the Local Notice to Mariners
and Broadcast Notice to Mariners. If the
COTP determines that the regulated area
need not be enforced for the full
duration stated in this notice of
enforcement, a Broadcast Notice to
Mariners may be used to grant general
permission to enter the regulated area.
Dated: April 22, 2015.
J.C. O’Connor, III,
Captain, U.S. Coast Guard, Captain of the
Port Boston.
[FR Doc. 2015–11814 Filed 5–22–15; 8:45 am]
Coast Guard
BILLING CODE 9110–04–P
33 CFR Part 165
ENVIRONMENTAL PROTECTION
AGENCY
[Docket No. USCG–2015–0224]
Safety Zones; Recurring Events in
Captain of the Port Boston Zone;
Charles River 1-Mile Swim
Coast Guard, DHS.
Notice of enforcement of
regulation.
40 CFR Part 52
[EPA–R08–OAR–2011–0770; FRL–9928–16–
Region 8]
AGENCY:
ACTION:
The Coast Guard will enforce
the subject safety zone in the Captain of
the Port Boston Zone on the specified
date and time listed below. This action
is necessary to ensure the protection of
the maritime public and event
participants from the hazards associated
with this annual recurring event.
DATES: The subject safety zone will be
enforced on June 6, 2015 from 7:30 a.m.
to 9:30 a.m., instead of from 8:00 a.m.
to 9:00 a.m. on the usual second Sunday
in July.
FOR FURTHER INFORMATION CONTACT: If
you have questions on this notice of
enforcement, call or email Mr. Mark
Cutter, Coast Guard Sector Boston
Waterways Management Division,
telephone 617–223–4000, email
Mark.E.Cutter@uscg.mil.
SUPPLEMENTARY INFORMATION: The
subject event is listed in Table 1 of 33
CFR 165.118 as enforced annually on
the second Sunday in July, from 8:00
a.m. to 9:00 p.m. In 2015, it will be
enforced on June 6, 2015.
Under the provisions of 33 CFR
165.118, no person or vessel, except for
the safety vessels assisting with the
event may enter the safety zone unless
given permission from the COTP or the
designated on-scene representative. The
Coast Guard may be assisted by other
SUMMARY:
PO 00000
Frm 00017
Fmt 4700
Sfmt 4700
Approval and Promulgation of
Implementation Plans; State of
Colorado; Regional Haze State
Implementation Plan
Environmental Protection
Agency.
ACTION: Final rule.
AGENCY:
The Environmental Protection
Agency (EPA) is reissuing its final
approval of the Colorado regional haze
State Implementation Plan (SIP)
revision submitted on May 25, 2011
with respect to the State’s best available
retrofit technology (BART)
determination for the Comanche
Generating Station (Comanche) near
Pueblo, Colorado. EPA originally
finalized its approval of the Colorado
regional haze SIP on December 31, 2012.
In response to a petition for review of
that final action in the United States
Court of Appeals for the Tenth Circuit,
EPA successfully moved for a voluntary
remand, without vacatur, to more
adequately respond to public comments
concerning Comanche. EPA is providing
new responses to those comments in
this rulemaking notice.
DATES: This final rule is effective on
June 25, 2015.
ADDRESSES: EPA has established a
docket for this action under Docket ID
No. EPA–R08– OAR–2011–0770. All
documents in the docket are listed on
the www.regulations.gov index.
SUMMARY:
E:\FR\FM\26MYR1.SGM
26MYR1
29954
Federal Register / Vol. 80, No. 100 / Tuesday, May 26, 2015 / Rules and Regulations
Although listed in the index, some
information is not publicly available,
e.g., Confidential Business Information
(CBI) or other information whose
disclosure is restricted by statute.
Certain other material, such as
copyrighted material, is not placed on
the Internet and will be publicly
available only in hard copy form.
Publicly available docket materials are
available either electronically through
www.regulations.gov or in hard copy at
the Air Program, Environmental
Protection Agency (EPA), Region 8,
1595 Wynkoop Street, Denver, Colorado
80202–1129. EPA requests that if at all
possible, you contact the person listed
in the FOR FURTHER INFORMATION
CONTACT section to view the hard copy
of the docket. You may view the hard
copy of the docket Monday through
Friday, 8:00 a.m. to 4:00 p.m., excluding
Federal holidays.
FOR FURTHER INFORMATION CONTACT: Gail
Fallon, Air Program, U.S.
Environmental Protection Agency,
Region 8, Mailcode 8P–AR, 1595
Wynkoop Street, Denver, Colorado
80202–1129, (303) 312–6281,
fallon.gail@epa.gov.
SUPPLEMENTARY INFORMATION:
Table of Contents
wreier-aviles on DSK5TPTVN1PROD with RULES
I. Background
II. Public Comments and Revised EPA
Responses
III. Final Action
IV. Incorporation by Reference
V. Statutory and Executive Order Reviews
I. Background
On March 26, 2012, EPA proposed to
approve the Colorado regional haze SIP
as meeting the applicable requirements
of Sections 169A and 169B of the Clean
Air Act (CAA) and EPA’s implementing
regulations at 40 CFR 51.308–309
(Regional Haze Rule) and 40 CFR part
51, Appendix Y (Best Available Retrofit
Technology (BART) Guidelines).1
Among the components of the SIP was
a nitrogen oxides (NOX) BART
determination for Units 1 and 2 at
Comanche. As with several other
facilities, the State submitted a BART
analysis for Comanche that took into
account the five factors required by
section 169A(g)(2) of the CAA. The State
determined that the existing emission
controls at Comanche Units 1 and 2,
low-NOX burners with over-fire air
(LNB/OFA), are BART. EPA proposed to
approve the State’s NOX BART
determination for Comanche.
EPA received several adverse
comments on its proposed approval,
including comments from WildEarth
1 77
FR 18052.
VerDate Sep<11>2014
14:03 May 22, 2015
Jkt 235001
Guardians (Guardians) and the National
Parks Conservation Association (NPCA).
On December 31, 2012, EPA published
a notice of its final approval of the
Colorado regional haze SIP.2 That final
action included an approval of the
Comanche NOX BART determination.
On February 25, 2013, NPCA and
Guardians filed petitions seeking the
Tenth Circuit’s review of EPA’s final
approval of the Colorado regional haze
SIP.3 Guardians challenged EPA’s
approval of Colorado’s BART
determinations for Units 1 and 2 of the
Craig Station; Units 1 and 2 of the
Comanche Station; and Boilers 4 and 5
of the Colorado Energy Nations
Company (CENC), LLP facility at the
Coors Brewery. Guardians also
challenged EPA’s approval of Colorado’s
reasonable progress determination for
Craig Unit 3, and the deadlines for
compliance with emission limits for the
units at all three facilities. NPCA
challenged only EPA’s approval of
Colorado’s BART and reasonable
progress determinations for Craig Units
1, 2, and 3. After the court consolidated
the cases for review, EPA reached a
settlement with NPCA and Guardians
concerning their claims related to the
Craig Station,4 and Guardians elected
not to pursue its claims regarding
CENC/Coors. Guardians’ claims
concerning the Comanche Station are
still active. In response to these claims,
EPA moved the court for a partial
voluntary remand of its 2012 final
approval without vacatur so as to
provide a more detailed and complete
response to some of the adverse
comments on the proposed approval.5
The court granted EPA’s motion.6
II. Public Comments and Revised EPA
Responses
We received adverse comments on
our proposed approval of the Colorado
regional haze SIP, including comments
from Guardians related to our proposed
approval of Colorado’s BART
determinations for Units 1 and 2 at the
Comanche Station. We are reissuing our
final approval of the Colorado regional
haze SIP with respect to Comanche to
provide more detailed and clearer
responses to the Comanche-related
2 77
FR 76871.
WildEarth Guardians v. EPA, No. 13–9520
(10th Cir.) and National Parks Conservation
Association v. EPA, No. 13–9525 (10th Cir.).
4 See Proposed Settlement Agreement, 79 FR
47636 (Aug. 14, 2014).
5 See Respondents’ Motion for Partial Voluntary
Remand Without Vacatur and to Stay Briefing
Schedule Pending Resolution of This Motion, filed
Sep. 19, 2014 in WildEarth Guardians v. EPA, No.
13–9520 (10th Cir.).
6 See Order filed Oct. 6, 2014 in WildEarth
Guardians v. EPA, No. 13–9520 (10th Cir.).
3 See
PO 00000
Frm 00018
Fmt 4700
Sfmt 4700
adverse comments. The responses below
contain our complete, updated, and
clarified responses to comments related
to the Comanche NOX BART
determination.
Comment: The commenter argues that
Comanche Units 1 and 2 are currently
meeting lower NOX emission rates than
the State’s BART emission limits that
EPA proposed to approve. The
commenter cited the State’s BART
analysis, noting that currently Unit 1 is
emitting at an average annual rate of
0.124 lb/MMBtu and Unit 2 is emitting
at an average annual rate of 0.165 lb/
MMBtu, and compares those rates to the
Colorado BART limits: a 30-day
emission rate of 0.20 lb/mmBtu, and a
combined annual average emission rate
of 0.15 lb/mmBtu. According to the
commenter, allowing these units to emit
more pollution than they currently emit
does not represent BART and would not
lead to visibility improvements, and
nothing in the CAA or EPA’s regulations
suggests that it is appropriate for BART
limits to include any such cushion.
Further, the commenter alleges that that
under the annual BART limits, NOX
emissions will be allowed to increase by
at least 14 tons per year (tpy), and that
the 30-day rolling average limits would
allow Unit 1 to emit at least 40% more
NOX than the baseline 30-day rolling
average peak and Unit 2 to emit 12%
more NOX. The commenter claims that
the data demonstrates that Unit 1 could
meet a 30-day rolling average NOX
emission limit of 0.15 lb/MMBtu and
Unit 2 could meet a limit of 0.18 lb/
MMBtu without any trouble, and that
the BART limits should reflect what is
achievable. Accordingly, the commenter
asserts that EPA must disapprove
Colorado’s NOX BART determinations
for Comanche Unit 1 and Unit 2 and
adopt a FIP that establishes BART limits
that represent actual emission
reductions.7
Response: We disagree with this
comment. The State set NOX BART
emission limits for Comanche Units 1
and 2 individually at a 30-day rolling
average emission rate of 0.20 lb/MMBtu
and a combined annual average
emission rate of 0.15 lb/MMBtu. As EPA
requested in our October 26, 2010
comment letter during the state public
comment process, the State considered
tightening the 30-day limits, but
ultimately chose not to do so. In EPA’s
judgment, the State could have better
explained the basis for the margin for
compliance, but a more robust analysis
7 Comments submitted by WildEarth Guardians
(hereinafter referred to as ‘‘Guardians’ Comments’’)
at 5–6, EPA–R08–OAR–2011–0770–0040
Attachment 2 (May 25, 2012).
E:\FR\FM\26MYR1.SGM
26MYR1
Federal Register / Vol. 80, No. 100 / Tuesday, May 26, 2015 / Rules and Regulations
wreier-aviles on DSK5TPTVN1PROD with RULES
would not have led it to reach a
different conclusion as to the Comanche
NOX BART limits. Further, if we were
to disapprove the SIP and promulgate a
FIP with lower emission limits, the
actual emissions from Comanche would
unlikely be significantly lower. We
therefore decline to disapprove the NOX
BART determination for Comanche.
In our October 26, 2010 comment
letter to the State, we asked Colorado to
evaluate tightening Comanche’s NOX
limits. The State conducted that
evaluation.8 Based on its experience,
and after reviewing other state BART
proposals, Colorado found that 30-day
rolling average NOX emission rates
could be expected to be up to
approximately 15% higher than annual
average emission rates. With this in
mind, and also considering uncertainty
regarding load fluctuations, coldweather operating, startup, and
increased cycling to back up renewable
energy generation, the State concluded
that a 0.20 lb/MMBtu 30-day rolling
average emission limit was appropriate
for both units.
As a general matter, EPA finds it
appropriate and reasonable to allow a
margin for compliance in setting 30-day
rolling average BART limits, and we
have approved other state BART
determinations that included such
margins. The shorter 30-day averaging
period results in higher variability in
emissions because of load variation,
startup, shutdown, and other factors.
Accordingly, we have not generally
required that 30-day rolling average
emission limits be equal to the annual
emission rates used for calculating costeffectiveness. We find the State’s
application of a margin for compliance
here consistent with that approach.
The compliance margin included for
the Comanche units is larger than we
would generally expect. But we find
that with respect to Comanche, the
compliance margin is unlikely to lead to
significant actual NOX emissions
increases. After all, the lower Comanche
emissions cited by the commenter
occurred under permit limits identical
to those the State selected as BART, and
the commenter has provided no
evidence that the facility will change its
operations just because the State has
adopted the permit limits as BART
8 See Colorado Regional Haze Submittal,
Appendix C (Technical Support Documents for
BART Determination), BART Analysis of Control
Options For Public Service Company—Comanche
Station, Units 1 and 2, at 17–19 (EPA–R08–OAR–
2011–0770–0013, PDF pages 312–14); see also
Appendix C—Technical Support Documents for
BART Determination (EPA–R08–OAR–2011–0770–
0017), Attachment 5: Public Service Company—
Comanche Station Units 1 and 2 Technical
Analysis.
VerDate Sep<11>2014
14:03 May 22, 2015
Jkt 235001
limits. Instead, emission rates are likely
to remain near the baseline figures cited
by the commenter, which as the
commenter notes are below the BART
limits. An occasional rise is possible in
light of the uncertainties referred to
above, which is the purpose of allowing
a margin for compliance above the
actual 30-day rolling average emissions
levels. The commenter appeared to at
least partly acknowledge this reality,
stating that ‘‘[w]e do not suggest that the
State was required to set the emission
limits exactly at the levels emitted.’’ 9
But none of these uncertainties suggests
that there will be a consistent increase
in emissions over the long term.
As for annual average emission rates,
Colorado found that in 2009, the annual
average rate for both units combined
was about 0.15 lb/MMBtu. Colorado did
not propose applying a margin of
compliance to the 2009 annual average
rate, and set a limit at 0.15 lb/MMBtu.
Because short-term emissions increases
and decreases should average out over
the course of any single year, we believe
that setting the BART annual emission
limit at about the annual emission rate
from 2009 is reasonable, unless there is
evidence that the source was not
properly operated in 2009 or that annual
average source operating conditions in
2009 were unrepresentative of future
operations. The commenter has not
alleged that there is any such evidence.
The commenter does assert that the 0.15
lb/MMBtu annual limit would allow an
increase in actual emissions if both
units operate at the BART limit. The
potential emissions increase calculated
by the commenter, however, would only
be 14 tons of NOX per year. A 14-ton
increase is not significant when
compared to the annual NOX emissions
of approximately 3,860 tons from
Comanche Units 1 and 2; it does not
warrant disapproval and a subsequent
FIP.10
The commenter alleges, but does not
support or quantify, a ‘‘likely’’ further
increase (beyond the claimed 14-ton
increase) based on the potential for one
unit to exceed 0.15 lb/MMBtu while the
combined rate remains below that limit.
This comment appears to be referring to
a scenario in which the unit operating
above 0.15 lb/MMBtu would have a
higher heat input than the unit
9 Guardians’
Comments at 8.
state flexibility to exempt de
minimis emission levels from a BART analysis, the
BART Guidelines make a similar point: ‘‘If a State
were to undertake a BART analysis for emissions
of less than 40 tons of SO2 or NOX . . . from a
source, it is unlikely to result in anything but a
trivial improvement in visibility. This is because
reducing emissions at these levels would have little
effect on regional emissions loadings or visibility
impairment.’’ 70 FR at 39117.
10 Discussing
PO 00000
Frm 00019
Fmt 4700
Sfmt 4700
29955
operating below 0.15 lb/MMBtu, so that
together they would still comply with
the SIP’s 0.15 lb/MMBtu average
emission rate limit while having higher
emissions than if each unit were held to
a limit of 0.15 lb/MMBtu. With the
existing LNB/OFA controls, though,
neither unit can be operated at an
emission rate much below its current
emission rate, and so there is unlikely
to be ‘‘room’’ for the other unit to
operate much higher while still meeting
the combined emission limit. Also, the
two units are subject to very similar
physical limits on heat input.11 We
therefore find that any additional
emissions consistent with a 0.15 lb/
MMBtu combined limit would be
insignificant from a visibility
standpoint. Further, we note that the
annual NOX BART limit of 0.15 lb/
MMBtu is below the average actual
emissions of 0.16 lb/MMBtu for Units 1
and 2 between January and October
2010.12 Therefore, Colorado imposed an
annual emission limit that was lower
than the then most recent partial-year
figures for Units 1 and 2.
The commenter also argues that the
30-day rolling average limits of 0.20 lb/
MMBtu would allow emission increases
because the actual 30-day rolling
average rates have consistently been
below this number. Annual emissions
are controlled by the SIP’s limit of 0.15
lb/MMBtu for the average of the two
unit’s annual average emission rates,
and would be so controlled even if there
were no 30-day limits at all. The issue
of whether the State and EPA correctly
assessed how well the annual limit will
control annual emissions was addressed
above. Therefore, EPA understands that
this comment regarding the 30-day
limits of 0.20 lb/MMBtu is meant to
address the possibility that the emission
rate of one or both units in 30-day
periods may be higher than 0.15 lb/
MMBtu, while the source could still
comply with respect to the annual
average limit by having lower emissions
in other 30-day periods. EPA agrees that
this is possible, but the State modeled
the baseline visibility impact of the
source assuming a constant emission
rate of 0.20 lb/MMBtu, so the possibility
has been fully considered.
11 See Colorado Regional Haze Submittal,
Appendix C (Technical Support Documents for
BART Determination), BART Analysis of Control
Options For Public Service Company—Comanche
Station, Units 1 and 2, at 2, Table 1: Comanche
Units 1 and 2 Technical Information (EPA–R08–
OAR–2011–0770–0013, PDF page 297 (citing boiler
ratings of 3,531 MMBtu/hr for Unit 1 and 3,482
MMBtu/hr for Unit 2).
12 January–October 2010 is the most recent annual
average emission rate period discussed by Colorado
in the regional haze SIP. See id. at 18 (PDF page
313).
E:\FR\FM\26MYR1.SGM
26MYR1
wreier-aviles on DSK5TPTVN1PROD with RULES
29956
Federal Register / Vol. 80, No. 100 / Tuesday, May 26, 2015 / Rules and Regulations
For these reasons, we have
determined that while the State could
have better explained the basis for the
margin for compliance it allowed, a
more robust analysis would not have led
it to reach a different conclusion as to
the NOX emission limits for Comanche
Units 1 and 2. In its next regional haze
SIP, the State can review the longer
history of emissions from Comanche
that will be available then, and consider
whether a downward adjustment in the
emission limit is appropriate to ensure
the best possible operation of the
emission controls.
Comment: The commenter asserts that
the State failed to appropriately assess
the cost of SCR, by assuming that SCR
would achieve an emission rate of 0.07
lb/MMBtu on an annual average basis.
But, according to the commenter, EPA
has noted that SCR can achieve
emission rates as low as 0.04 lb/MMBtu
on an annual basis, and a 0.05 lb/
MMBtu emission rate on an annual
average basis is a more appropriate
benchmark from which to assess the
cost-effectiveness of SCR. The
commenter claims that because the State
did not assess the cost-effectiveness of
SCR based on a rate of 0.05 lb/MMBtu,
the State did not reasonably take into
account the cost of compliance with
SCR in accordance with the CAA. The
commenter adds that although EPA and
the State may claim that SCR would not
be cost-effective in any case, there is no
support for such an assertion, and
without an adequate case-specific cost
analysis, there is no support for
concluding that SCR is unreasonable,
particularly for Unit 2.13
Response: We disagree with this
comment. We have reviewed the
information in the administrative record
for this action again, and we find that
our previous conclusion is still correct.
We agree that SCR can achieve annual
NOX emission rates of 0.05 lb/MMBtu,
and that ideally Colorado would have
used this value when assessing the SCR
control option.14 But if the State had
done so, the marginally lower emissions
would not have caused the State to
reach a different conclusion as to what
technology is BART.
First, we note that the comment
misstates the rate that Colorado actually
used for the purpose of calculating costeffectiveness. In the Comanche NOX
BART analysis, the State assumed an
annual emissions rate for SCR of 0.061
13 Guardians’
Comments at 9.
this notice, our references to the
use of SCR at Comanche incorporate the effects of
LNB/OFA. Thus, when we discuss comparing the
effects of SCR against the baseline, we are
comparing SCR operating with LNB/OFA against
the post-2009 baseline of LNB/OFA alone.
14 Throughout
VerDate Sep<11>2014
14:03 May 22, 2015
Jkt 235001
lb/MMBtu—not 0.07 lb/MMBtu.15 (The
latter figure was the 30-day rolling
average rate, not the annual average as
the commenter contends.16) Therefore,
the relevant comparison for the
commenter’s purpose would be between
the 0.061 lb/MMBtu annual average rate
that the State used and the 0.05 lb/
MMBtu annual average emission rate
that the commenter prefers.
Using the 0.061 lb/MMBtu annual
average emission rate, Colorado
estimated emissions of 740 tpy for Unit
1 and 869 tpy for Unit 2 with SCR.17
Based on those estimated emissions, the
State calculated emission reductions of
770.4 tpy for Unit 1 and 1,480 tpy for
Unit 2, compared to a baseline level of
emissions measured in 2009 that
reflected the installation of LNB/OFA
controls.18 Based on these reductions,
the State derived cost-effectiveness
values for SCR of $15,920 per ton and
$9,900 per ton for Units 1 and 2,
respectively.19 It is a simple exercise to
insert the annual average emission rate
of 0.05 lb/MMBtu into the State’s
technical analysis spreadsheet.20 Doing
so, we can see that using the figure the
commenter recommends would have
produced estimated emission levels of
about 609 tpy for Unit 1 and 713 tpy for
Unit 2 with SCR, which in turn give
emission reductions of 897 tpy (Unit 1)
15 See Colorado Regional Haze Submittal,
Appendix C (Technical Support Documents for
BART Determination), BART Analysis of Control
Options For Public Service Company—Comanche
Station, Units 1 and 2, Tables 10 and 11, at 20–21
(R08–OAR–2011–0770–0013, PDF pages 315–16;
see also Technical Support Documents for BART
Determination (EPA–R08–OAR–2011–0770–0017),
Attachment: Public Service Company—Cmanche
Station, Units 1 and 2 Technical Analysis (.xls
format spreadsheet file, tabs ‘‘Comanche 1 NOX’’
and ‘‘Comanche 2 NOX’’). There is an
inconsequential (approx. 0.33%) difference between
the Unit 1 baseline numbers in these two parts of
the record; the discussion in this rule uses the 1506
tpy figure from the State’s technical analysis
spreadsheet.
16 Id.
17 Id.
18 ‘‘[T]he Division used years 2009 (annual
averages and 30-day rolling) for baseline emissions
for reduction and cost calculations.’’ Colorado
Regional Haze Submittal, Appendix C (Technical
Support Documents for BART Determination),
BART Analysis of Control Options For Public
Service Company—Comanche Station, Units 1 and
2, at 3 (R08–OAR–2011–0770–0013, PDF page 298);
see also id., Table 2 (‘‘PSCo Comanche Units 1 &
2 Baseline Emissions’’).
19 See Colorado Regional Haze Submittal,
Appendix C (Technical Support Documents for
BART Determination), BART Analysis of Control
Options For Public Service Company—Comanche
Station, Units 1 and 2, Tables 10–13, at 20–21 (R08–
OAR–2011–0770–0013, PDF pages 315–16).
20 See Technical Support Documents for BART
Determination (EPA–R08–OAR–2011–0770–0017),
Attachment: Public Service Company—Comanche
Station, Units 1 and 2 Technical Analysis (Excel
spreadsheet file, tabs ‘‘Comanche 1 NOX’’and
‘‘Comanche 2 NOX’’).
PO 00000
Frm 00020
Fmt 4700
Sfmt 4700
and 1,636 tpy (Unit 2) compared to a
2009 baseline level and costeffectiveness values of $13,670 and
$8,956 per ton for Units 1 and 2,
respectively.21 Considering that these
adjusted cost-effectiveness values
remain high and (as discussed below)
the extent of the benefits associated
with SCR remains low, we do not
believe that the impact on the BART
analysis would have led to a different
conclusion if Colorado had used the
more stringent emission rate. Therefore,
we conclude that the State’s use of 0.061
lb/MMBtu to evaluate the costeffectiveness of SCR at Comanche is not
grounds for disapproval.
Comment: The commenter states that
Colorado appears to have overestimated
the capital cost of SCR, in that the
State’s reliance on the CUECost model
led to artificially inflated capital costs.
According to the commenter, both EPA
and the National Park Service (NPS)
previously commented to the State that
the State should have used EPA’s
Control Cost Manual, and both noted
that the CUECost model relied upon by
the State is not appropriate. The
commenter argues that the State does
not explain in the record why its use of
CUECost was reasonable, particularly in
light of the concerns expressed by EPA
and the NPS.22
Response: We agree that there were
flaws in Colorado’s approach to
estimating the costs of SCR for the
Comanche BART units, and that the
CUECost model likely yielded an
inflated cost estimate. In the referenced
correspondence, EPA stated that ‘‘the
CUECost model yields high capital costs
for the Comanche facility,’’ and
suggested that the capital costs
calculated would have been
approximately 50% lower if the CCM
had been followed.23 But even if we
reduce the capital cost estimates by that
percentage, and also adjust the emission
rate as discussed in the previous
comment, we believe that the cost of
SCR at Comanche would still be high
compared to the visibility benefits, and
21 For Unit 1, the State also calculated an
incremental value to assess the cost-effectiveness of
SCR over SNCR. Even after making the correction
to an assumed annual average rate of 0.05 lb/
MMBtu as described above, this value remains very
high: $23,497 per ton.
22 Guardians’ Comments at 9.
23 Letter from Callie Videtich, EPA, to Paul
Tourangeau, CDPHE (Oct. 26, 2010), at 8–9 (EPA–
R08–OAR–2011–0770–0043, Attachment 19). EPA
stated that using the CCM to assess SCR capital
costs for the Comanche BART units yielded an
estimate of approximately $120/kW, as opposed to
the $247/kW (Unit 1) and $248/kW (Unit 2) derived
from the CUECost model. Id. This ratio of dollars
per kW results in a 51.6% lower estimate.
E:\FR\FM\26MYR1.SGM
26MYR1
Federal Register / Vol. 80, No. 100 / Tuesday, May 26, 2015 / Rules and Regulations
wreier-aviles on DSK5TPTVN1PROD with RULES
that Colorado’s decision not to require
SCR would still be reasonable.
Specifically, cutting the capital cost
estimate by 51.6%, and using the more
stringent 0.05 lb/MMBtu emission rate
discussed in the previous comment,
produces cost-effectiveness values of
$9,319 and $6,481 per ton for employing
SCR at Units 1 and 2, respectively.24
Thus, even after addressing both of the
cost issues raised by the commenter, the
cost-effectiveness values remain high.
Also, as discussed below in response to
another comment, we have concluded
that the visibility benefits that would
result from SCR are insufficient to
justify these high costs. Accordingly, we
do not believe that Colorado would have
reached a different NOX BART
conclusion if it had used the CCM in its
analysis (as well as the more stringent
emission rate discussed previously).
In its SIP, the State explained that, in
its view, SCR for NOX control would
generally be reasonable if costs did not
exceed $5,000 per ton of pollutant
reduced, and if the controls provided a
modeled visibility benefit of 0.50
deciviews (dv) or greater at the primary
Class I Area affected.25 Considering the
State’s guidance, it is clear that making
the adjustments that the commenter
requests would not lead to a different
outcome. Therefore, considering all the
BART factors, we do not see a basis to
conclude that using a lower capital cost
estimate, combined with a 0.05 lb/
MMBtu emission rate for SCR, would
have led the State to reach a different
conclusion or should lead us to
disapprove the State’s BART
determination.
Comment: The commenter states that
Colorado and EPA may claim that, even
if the costs were accurately assessed, the
visibility benefits of SCR would not be
significant, but that there is no support
for this assertion. According to the
commenter, it appears that Colorado’s
assessment of visibility improvements is
based on an assumption that the
proposed BART limits, which the
commenter refers to as the ‘‘do nothing’’
BART limits, would actually improve
visibility. But, the commenter claims,
the proposed BART limits would allow
24 The 51.6% adjustment to capital cost can be
made by multiplying the ‘‘total capital costs’’
figures on the State’s technical analysis spreadsheet
by 0.484. See Technical Support Documents for
BART Determination (EPA–R08–OAR–2011–0770–
0017), Attachment: Public Service Company—
Comanche Station, Units 1 and 2 Technical
Analysis (.xls format spreadsheet file, tabs
‘‘Comanche 1 NOX’’ and ‘‘Comanche 2 NOX’’). In
addition to capital costs, the cost-effectiveness
calculations incorporate operating and maintenance
costs, which the commenter did not challenge.
25 See Colorado Regional Haze Submittal at 52
(R08–OAR–2011–0770–0013, PDF page 53).
VerDate Sep<11>2014
14:03 May 22, 2015
Jkt 235001
increased emissions, and therefore
would not improve visibility. On the
other hand, states the commenter, SCR
would appear to provide significant
visibility improvements. The
commenter argues that for Unit 2 this is
especially significant because SCR was
the only available technology analyzed
for BART.26
Response: We disagree with this
comment. In relation to the high costs,
the visibility benefits of SCR at
Comanche are not sufficiently large to
warrant disapproval of the State’s BART
determination. We would come to this
conclusion regardless of whether the
cost component of the BART analysis
involved the State’s original figures or
the adjusted figures discussed above in
response to previous comments. The
State estimated that SCR would produce
visibility improvements of 0.14 dv (Unit
1) and 0.17 dv (Unit 2) as compared to
the 2009 post-LNB/OFA baseline.27 This
level of expected visibility improvement
from SCR is insufficient to cause us to
conclude that the State’s BART
determination is unreasonable.
As discussed above in response to a
previous comment, we recognize that
the State did not use the 0.05 lb/MMBtu
emission rate that accurately represents
the performance capabilities of SCR.
Accordingly, it is reasonable to expect
that the State would have estimated
slightly greater visibility benefits from
SCR if it had used the 0.05 lb/MMBtu
rate. In EPA’s judgment, however, the
visibility benefits compared to the 2009
baseline would have remained modest.
We note, for instance, that in the State’s
analysis of Comanche Unit 1, the
difference in visibility benefit between
selective non-catalytic reduction (SNCR)
(with a NOX emission rate of 0.10 lb/
MMBtu) and SCR (with a NOX emission
rate of 0.07 lb/MMBtu) is only 0.03 dv.28
We conclude that the impact of a further
26 Guardians’
Comments at 9–10.
Colorado Regional Haze Submittal,
Appendix C (Technical Support Documents for
BART Determination), BART Analysis of Control
Options For Public Service Company—Comanche
Station, Units 1 and 2, Table 15, at 24 (R08–OAR–
2011–0770–0013, PDF page 319). As discussed
below, the table also includes information on
improvements over the pre-control baseline; this
information is illustrative and was not the basis for
the BART determination or for our approval of the
State’s action.
28 What are labeled by the State as ‘‘NO emission
X
rates’’ (e.g., Table 15 of their analysis) are actually
the 30-day emission limits. See Colorado Regional
Haze Submittal, Appendix C (Technical Support
Documents for BART Determination), BART
Analysis of Control Options For Public Service
Company—Comanche Station, Units 1 and 2, Table
15, at 24 (R08–OAR–2011–0770–0013, PDF page
319). Actual 30-day emission rates have been lower.
See id. at 18 (PDF page 313).
27 See
PO 00000
Frm 00021
Fmt 4700
Sfmt 4700
29957
reduction in emission rate to 0.05 lb/
MMBtu would be similarly small.29
As mentioned previously, the State
explained that, in its view, SCR for NOX
control will generally be reasonable
when costs do not exceed $5,000 per ton
of pollutant reduced, and when the
controls provide a modeled visibility
benefit of 0.50 dv or greater at the
primary Class I Area affected.30 While
we agree with the State that these
guidance criteria should not be used as
absolute determinants of BART
outcomes, they are in general consistent
with the decisions that other states and
EPA have made when considering
whether to require SCR as NOX BART,
and generally reflect a reasonable
balancing of the BART factors. In this
case, we expect that even using the SCR
emission rate requested by the
commenter, the visibility improvement
from SCR would fall well below the
State’s criteria. Judging these visibility
improvements against the fairly high
cost of SCR (again, even after
adjustment to reflect the comments), we
find that the State’s decision not to
impose SCR was reasonable.
The commenter incorrectly asserted
that the State’s BART determination was
based on the assumption that existing
controls would improve visibility
compared to current levels. Colorado
did not claim that its BART emission
limits would result in visibility benefits
compared to current levels (that is,
compared to the 2009 post-LNB/OFA
emissions baseline). The State did note
that the existing level of control
provided benefits when compared to the
2004 baseline, which is true. But while
Colorado referred to both a pre-LNB/
OFA baseline and a 2009 baseline when
discussing visibility benefits, the State
actually used only the 2009 baseline in
calculating cost-effectiveness, and
likewise relied on visibility benefits
based on the 2009 baseline in making
the BART determination for
29 Thus, comparing the SNCR and SCR numbers,
we see that a NOX emissions rate reduction from
0.10 to 0.07 lb/MMBtu is reflected in a visibility
improvement from 0.11 to 0.14 dv. If we assume,
for the purpose of conservatively estimating
visibility improvements, that there is a linear
relationship between emission reductions and
visibility improvement, then further reducing the
NOX emission rate from 0.07 to 0.05 lb/MMBtu
might cause visibility improvements at Units 1 and
2 to increase from 0.14 and 0.178 dv to
approximately 0.16 and 0.198 dv. See Approval and
Promulgation of Air Quality Implementation Plans;
State of Florida; Regional Haze State
Implementation Plan, 78 FR 53250, 53267 (Aug. 29,
2013) (‘‘[A]n assumption of a linear response to
changes in emissions is a reasonable estimation and
the simplified methodology used for these BART
determinations likely provides conservative
overestimates of visibility impact reductions.’’).
30 See Colorado Regional Haze Submittal at 52
(R08–OAR–2011–0770–0013, PDF page 53).
E:\FR\FM\26MYR1.SGM
26MYR1
29958
Federal Register / Vol. 80, No. 100 / Tuesday, May 26, 2015 / Rules and Regulations
wreier-aviles on DSK5TPTVN1PROD with RULES
Comanche.31 We have reviewed the
visibility estimates and cost calculations
that the State relied on when making its
BART determination for Comanche and
have confirmed that they were based on
comparisons to the 2009 baseline.32
It was correct for the State to use the
2009 baseline for NOX emissions from
Units 1 and 2 in the BART
determination. The CAA requires that,
in making BART determinations, states
and EPA take into consideration ‘‘any
existing pollution control technology in
use at the source.’’ 33 As we explained
in detail in our final action on the
Wyoming regional haze SIP, this
consideration should generally
incorporate controls into baseline
emissions if the controls were installed
to comply with CAA requirements other
than the BART requirement.34 That is
exactly what happened with respect to
Comanche Units 1 and 2. The controls
in question had been placed on these
units to ‘‘net out’’ of Prevention of
Significant Deterioration (PSD) review
requirements for NOX and SO2
emissions from the new Unit 3.35
31 Colorado stated in the SIP that ‘‘the Division
used year[ ] 2009 (annual averages and 30-day
rolling) for baseline emissions for reduction and
cost calculations.’’ See Colorado Regional Haze
Submittal, Appendix C (Technical Support
Documents for BART Determination), BART
Analysis of Control Options For Public Service
Company—Comanche Station, Units 1 and 2, at 20–
21, 24 (R08–OAR–2011–0770–0013, PDF pages
315–16, 319); see also Appendix C—Technical
Support Documents for BART Determination (EPA–
R08–OAR–2011–0770–0017), Attachment 5: Public
Service Company—Comanche Station Units 1 and
2 Technical Analysis. Likewise, the State’s BART
determination cites only the 0.14 dv and 0.17dv
visibility improvement numbers derived from
comparison to the 2009 baseline. See Colorado
Regional Haze Submittal at 66 (R08–OAR–2011–
0770–0013, PDF page 67).
32 In replying to this comment and one other
comment in the December 2012 final approval, we
inadvertently made a confusing statement
concerning the applicable baselines. In that notice,
we stated that Colorado had ‘‘assessed the benefit
of control options relative to both the subject-toBART baseline and to the installation of new lowNOX burners (LNB) [with over-fire air] in 2007 and
2008.’’ Further, we noted that ‘‘relative to the
subject-to-BART baseline, Colorado’s BART
selection (combustion controls), does in fact show
visibility improvement.’’ These statements
appeared to suggest that it was appropriate for
Colorado to use a 2009 baseline when evaluating
the benefits of SNCR and SCR, but a 2004 (pre-LNB/
OFA) baseline to evaluate the State’s proposed
BART option. That was not our intention. Our
reference to the 2004 subject-to-BART baseline—
that is, to the emissions level before the installation
of the LNB/OFA, which were required to comply
with non-BART CAA requirements—was merely an
observation, by which we intended to show that the
installation of those controls had produced real air
quality improvements over previous levels. That
illustration was not, however, intended to be part
of our evaluation of the State’s cost or visibility
analyses.
33 42 U.S.C. 7491(g)(2).
34 79 FR 5032, 5104–05 (Jan. 30, 2014).
35 See Colorado Regional Haze Submittal,
Appendix C (Technical Support Documents for
VerDate Sep<11>2014
14:03 May 22, 2015
Jkt 235001
Therefore, it was appropriate for the
State to use the 2009 emissions baseline,
which reflected the reductions achieved
by LNB/OFA, in its BART analysis for
Comanche.
Finally, we addressed the assertion
that the State’s BART limits would lead
to increased emissions in our response
to a previous comment. The commenter
has failed to offer any support for this
claim, and we do not find any basis to
conclude that increased emissions will
result from the State’s BART limits.
For the above reasons, while we agree
that SCR at Comanche Units 1 and 2
would result in visibility improvements,
we find that the State reasonably
concluded that those visibility
improvements would not be sufficient
to justify the cost involved.
Comment: The commenter states that
it is unclear why Colorado rejected
SNCR for Comanche Unit 1, particularly
because the proposed BART limit for
Unit 1 is less stringent than Unit 1’s
current actual emissions. Citing EPA
figures, the commenter asserts that Unit
1 would meet a 30-day rolling average
emission rate of 0.10 lb/MMBtu under
an SNCR scenario. The commenter
notes that the State found that the cost
of $3,644 per ton of NOX reduced and
the perceived ‘‘low visibility
improvement’’ warranted a
determination that SNCR was not
reasonable for Unit 1. The commenter
asserts, however, that this cost is
squarely within the range of what
Colorado considers to be costeffective.36
Response: We find that the State’s
rejection of SNCR was reasonable based
on its weighing of the BART factors. The
State concluded that the cost of SNCR
was not warranted given the relatively
modest 0.11 dv visibility improvement
that would result. Even if a control
technology is cost-effective on a dollar
per ton basis, a state may conclude that
the control technology is not warranted
based on a reasonable consideration of
all five BART factors.
Comment: The commenter states that
Colorado’s analysis indicates that SNCR
would achieve greater emission
BART Determination), BART Analysis of Control
Options For Public Service Company—Comanche
Station, Units 1 and 2, at 1 (R08–OAR–2011–0770–
0013, PDF page 1) (‘‘As part of that [2004
construction] project, PSCo proposed to install
control devices on the existing units.’’); see also
Colorado Operating Permit # 96OPPB133
(Comanche Station) (‘‘. . . PSCo proposed to install
NOX controls (low NOX burners with over-fire air)
on both Units 1 and 2 . . . to ‘net-out’ of Prevention
of Significant Deterioration (PSD) review
requirements for NOX and SO2’’), posted at https://
www.colorado.gov/pacific/cdphe/operatingpermits-company-index.
36 Guardians’ Comments at 10.
PO 00000
Frm 00022
Fmt 4700
Sfmt 4700
reductions than an emission rate of 0.20
lb/MMBtu on a 30-day rolling average.
According to the commenter, although
the State asserts that the visibility
improvement from SNCR would amount
to 0.11 dv, it is unclear why such
improvements are not reasonable or are
insignificant, particularly given that the
purpose of BART is to reduce or
eliminate visibility impairment. The
commenter argues that there is no
explanation in the record supporting the
State’s assertion. Further, the
commenter argues that it appears as if
the State’s assessment of visibility
improvements is based on an incorrect
assumption that the proposed BART
limit would actually improve visibility.
The commenter states that when
compared to the real impacts of the
State’s proposed BART limit for
Comanche Unit 1, SNCR appears to
provide significant visibility
improvements, because, as opposed to
the proposed BART limit, SNCR would
actually achieve improvements.
Therefore, the commenter concludes,
EPA must promulgate a FIP that
establishes an appropriate NOX BART
limit for Comanche Unit 1.37
Response: The commenter is correct
that the State predicted that SNCR
would result in additional improvement
in visibility over the control technology
that the State selected as BART.
However, this does not mean that the
CAA or our regulations required the
State to select SNCR as BART. For the
reasons stated above, we find that it was
reasonable for the State to reject SNCR
based on consideration of all five BART
factors. We agree that SNCR would
result in visibility improvements, but as
with SCR, we agree with the State’s
assessment that the visibility
improvements were insufficient to
justify the cost involved.
Regarding the commenter’s claim that
the State’s selected limits will lead to an
increase in emissions, as discussed
above in detail, the commenter has
presented no evidence that any
emissions increase will occur.
III. Final Action
With respect to the Comanche Station,
EPA is re-finalizing its approval of the
Colorado regional haze SIP submitted
on May 25, 2011. Because this refinalization merely gives additional
explanation in response to comments
and does not alter any previous
determinations, it does not affect any
applicable SIP compliance deadlines.
Our action is based on an evaluation of
Colorado’s regional haze SIP submittal
for Comanche against the regional haze
37 Guardians’
E:\FR\FM\26MYR1.SGM
Comments at 10.
26MYR1
Federal Register / Vol. 80, No. 100 / Tuesday, May 26, 2015 / Rules and Regulations
requirements at 40 CFR 51.300–51.309
and CAA sections 169A and 169B. All
general SIP requirements contained in
CAA section 110, other provisions of the
CAA, and our regulations applicable to
this action were also evaluated. The
purpose of this action is to ensure
compliance with these requirements
and to provide additional rationale to
support our conclusions.
IV. Incorporation by Reference
In this rule, the EPA is finalizing
regulatory text that includes
incorporation by reference. In
accordance with requirements of 1 CFR
51.5, the EPA is finalizing the
incorporation by reference of Colorado
revisions to its SIP to address the
requirements of EPA’s regional haze
rule discussed in section III, Final
Action, of this preamble. The EPA has
made, and will continue to make, these
documents generally available
electronically through
www.regulations.gov and/or in hard
copy at the appropriate EPA office (see
the ADDRESSES section of this preamble
for more information).
wreier-aviles on DSK5TPTVN1PROD with RULES
V. Statutory and Executive Order
Reviews
Under the Clean Air Act, the
Administrator is required to approve a
SIP submission that complies with the
provisions of the Act and applicable
federal regulations. 42 U.S.C. 7410(k);
40 CFR 52.02(a). Thus, in reviewing SIP
submissions, EPA’s role is to approve
state choices, provided that they meet
the criteria of the Clean Air Act.
Accordingly, this action merely
approves state law as meeting federal
requirements and does not impose
additional requirements beyond those
imposed by state law. For that reason,
this action:
• Is not a ‘‘significant regulatory
action’’ subject to review by the Office
of Management and Budget under
Executive Order 12866 (58 FR 51735,
October 4, 1993);
• Does not impose an information
collection burden under the provisions
of the Paperwork Reduction Act (44
U.S.C. 3501 et seq.);
• Is certified as not having a
significant economic impact on a
substantial number of small entities
under the Regulatory Flexibility Act (5
U.S.C. 601 et seq.);
• Does not contain any unfunded
mandate or significantly or uniquely
affect small governments, as described
in the Unfunded Mandates Reform Act
of 1995 (Pub. L. 104–4);
• Does not have federalism
implications as specified in Executive
VerDate Sep<11>2014
14:03 May 22, 2015
Jkt 235001
Order 13132 (64 FR 43255, August 10,
1999);
• Is not an economically significant
regulatory action based on health or
safety risks subject to Executive Order
13045 (62 FR 19885, April 23, 1997);
• Is not a significant regulatory action
subject to Executive Order 13211 (66 FR
28355, May 22, 2001);
• Is not subject to requirements of
Section 12(d) of the National
Technology Transfer and Advancement
Act of 1995 (15 U.S.C. 272 note) because
this action does not involve the use of
measurement or other standards; and
• Does not provide EPA with the
discretionary authority to address, as
appropriate, disproportionate human
health or environmental effects, using
practicable and legally permissible
methods, under Executive Order 12898
(59 FR 7629, February 16, 1994).
• The SIP is not approved to apply on
any Indian reservation land or in any
other area where EPA or an Indian tribe
has demonstrated that a tribe has
jurisdiction. In those areas of Indian
country, the rule does not have tribal
implications and will not impose
substantial direct costs on tribal
governments or preempt tribal law as
specified by Executive Order 13175 (65
FR 67249, November 9, 2000).
The Congressional Review Act, 5
U.S.C. 801 et seq., as added by the Small
Business Regulatory Enforcement
Fairness Act of 1996, generally provides
that before a rule may take effect, the
agency promulgating the rule must
submit a rule report, which includes a
copy of the rule, to each House of the
Congress and to the Comptroller General
of the United States. EPA will submit a
report containing this action and other
required information to the U.S. Senate,
the U.S. House of Representatives, and
the Comptroller General of the United
States prior to publication of the rule in
the Federal Register. A major rule
cannot take effect until 60 days after it
is published in the Federal Register.
This action is not a ‘‘major rule’’ as
defined by 5 U.S.C. 804(2).
Under section 307(b)(1) of the Clean
Air Act, petitions for judicial review of
this action must be filed in the United
States Court of Appeals for the
appropriate circuit by July 27, 2015.
Filing a petition for reconsideration by
the Administrator of this final rule does
not affect the finality of this action for
the purposes of judicial review nor does
it extend the time within which a
petition for judicial review may be filed,
and shall not postpone the effectiveness
of such rule or action. This action may
not be challenged later in proceedings to
enforce its requirements. See section
307(b)(2).
PO 00000
Frm 00023
Fmt 4700
Sfmt 4700
29959
List of Subjects in 40 CFR Part 52
Environmental protection, Air
pollution control, Incorporation by
reference, Intergovernmental relations,
Nitrogen dioxide, Particulate matter,
Sulfur oxides.
Dated: May 8, 2015.
Debra H. Thomas,
Acting Regional Administrator Region 8.
40 CFR part 52 is amended as follows:
PART 52—APPROVAL AND
PROMULGATION OF
IMPLEMENTATION PLANS
1. The authority citation for Part 52
continues to read as follows:
■
Authority: 42 U.S.C. 7401 et seq.
Subpart G—Colorado
2. Section 52.320 is amended by
revising paragraph (c)(124) introductory
text to read as follows:
■
§ 52.320
Identification of plan.
*
*
*
*
*
(c) * * *
(124) On May 25, 2011 the State of
Colorado submitted revisions to its State
Implementation Plan to address the
requirements of EPA’s regional haze
rule. On December 31, 2012, EPA issued
a final rule approving this submittal and
responding to public comments. On
May 26, 2015 EPA reissued the final
rule with respect to the nitrogen oxides
(NOX) best available retrofit technology
(BART) determination for the Comanche
Generating Station to provide additional
responses to public comments.
*
*
*
*
*
[FR Doc. 2015–12491 Filed 5–22–15; 8:45 am]
BILLING CODE 6560–50–P
ENVIRONMENTAL PROTECTION
AGENCY
40 CFR Part 52
[EPA–R03–OAR–2014–0422; FRL–9927–90–
Region 3]
Approval and Promulgation of Air
Quality Implementation Plans; Virginia;
Revisions to the Attainment Plans for
the Commonwealth of Virginia Portion
of the Washington, DC–MD–VA 1990 1Hour and 1997 8-Hour Ozone
Nonattainment Areas and the
Maintenance Plan for the
Fredericksburg 1997 8-Hour Ozone
Maintenance Area To Remove the
Stage II Vapor Recovery Program
Environmental Protection
Agency (EPA).
ACTION: Direct final rule.
AGENCY:
E:\FR\FM\26MYR1.SGM
26MYR1
Agencies
[Federal Register Volume 80, Number 100 (Tuesday, May 26, 2015)]
[Rules and Regulations]
[Pages 29953-29959]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2015-12491]
=======================================================================
-----------------------------------------------------------------------
ENVIRONMENTAL PROTECTION AGENCY
40 CFR Part 52
[EPA-R08-OAR-2011-0770; FRL-9928-16-Region 8]
Approval and Promulgation of Implementation Plans; State of
Colorado; Regional Haze State Implementation Plan
AGENCY: Environmental Protection Agency.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: The Environmental Protection Agency (EPA) is reissuing its
final approval of the Colorado regional haze State Implementation Plan
(SIP) revision submitted on May 25, 2011 with respect to the State's
best available retrofit technology (BART) determination for the
Comanche Generating Station (Comanche) near Pueblo, Colorado. EPA
originally finalized its approval of the Colorado regional haze SIP on
December 31, 2012. In response to a petition for review of that final
action in the United States Court of Appeals for the Tenth Circuit, EPA
successfully moved for a voluntary remand, without vacatur, to more
adequately respond to public comments concerning Comanche. EPA is
providing new responses to those comments in this rulemaking notice.
DATES: This final rule is effective on June 25, 2015.
ADDRESSES: EPA has established a docket for this action under Docket ID
No. EPA-R08- OAR-2011-0770. All documents in the docket are listed on
the www.regulations.gov index.
[[Page 29954]]
Although listed in the index, some information is not publicly
available, e.g., Confidential Business Information (CBI) or other
information whose disclosure is restricted by statute. Certain other
material, such as copyrighted material, is not placed on the Internet
and will be publicly available only in hard copy form. Publicly
available docket materials are available either electronically through
www.regulations.gov or in hard copy at the Air Program, Environmental
Protection Agency (EPA), Region 8, 1595 Wynkoop Street, Denver,
Colorado 80202-1129. EPA requests that if at all possible, you contact
the person listed in the FOR FURTHER INFORMATION CONTACT section to
view the hard copy of the docket. You may view the hard copy of the
docket Monday through Friday, 8:00 a.m. to 4:00 p.m., excluding Federal
holidays.
FOR FURTHER INFORMATION CONTACT: Gail Fallon, Air Program, U.S.
Environmental Protection Agency, Region 8, Mailcode 8P-AR, 1595 Wynkoop
Street, Denver, Colorado 80202-1129, (303) 312-6281,
fallon.gail@epa.gov.
SUPPLEMENTARY INFORMATION:
Table of Contents
I. Background
II. Public Comments and Revised EPA Responses
III. Final Action
IV. Incorporation by Reference
V. Statutory and Executive Order Reviews
I. Background
On March 26, 2012, EPA proposed to approve the Colorado regional
haze SIP as meeting the applicable requirements of Sections 169A and
169B of the Clean Air Act (CAA) and EPA's implementing regulations at
40 CFR 51.308-309 (Regional Haze Rule) and 40 CFR part 51, Appendix Y
(Best Available Retrofit Technology (BART) Guidelines).\1\ Among the
components of the SIP was a nitrogen oxides (NOX) BART
determination for Units 1 and 2 at Comanche. As with several other
facilities, the State submitted a BART analysis for Comanche that took
into account the five factors required by section 169A(g)(2) of the
CAA. The State determined that the existing emission controls at
Comanche Units 1 and 2, low-NOX burners with over-fire air
(LNB/OFA), are BART. EPA proposed to approve the State's NOX
BART determination for Comanche.
---------------------------------------------------------------------------
\1\ 77 FR 18052.
---------------------------------------------------------------------------
EPA received several adverse comments on its proposed approval,
including comments from WildEarth Guardians (Guardians) and the
National Parks Conservation Association (NPCA). On December 31, 2012,
EPA published a notice of its final approval of the Colorado regional
haze SIP.\2\ That final action included an approval of the Comanche
NOX BART determination.
---------------------------------------------------------------------------
\2\ 77 FR 76871.
---------------------------------------------------------------------------
On February 25, 2013, NPCA and Guardians filed petitions seeking
the Tenth Circuit's review of EPA's final approval of the Colorado
regional haze SIP.\3\ Guardians challenged EPA's approval of Colorado's
BART determinations for Units 1 and 2 of the Craig Station; Units 1 and
2 of the Comanche Station; and Boilers 4 and 5 of the Colorado Energy
Nations Company (CENC), LLP facility at the Coors Brewery. Guardians
also challenged EPA's approval of Colorado's reasonable progress
determination for Craig Unit 3, and the deadlines for compliance with
emission limits for the units at all three facilities. NPCA challenged
only EPA's approval of Colorado's BART and reasonable progress
determinations for Craig Units 1, 2, and 3. After the court
consolidated the cases for review, EPA reached a settlement with NPCA
and Guardians concerning their claims related to the Craig Station,\4\
and Guardians elected not to pursue its claims regarding CENC/Coors.
Guardians' claims concerning the Comanche Station are still active. In
response to these claims, EPA moved the court for a partial voluntary
remand of its 2012 final approval without vacatur so as to provide a
more detailed and complete response to some of the adverse comments on
the proposed approval.\5\ The court granted EPA's motion.\6\
---------------------------------------------------------------------------
\3\ See WildEarth Guardians v. EPA, No. 13-9520 (10th Cir.) and
National Parks Conservation Association v. EPA, No. 13-9525 (10th
Cir.).
\4\ See Proposed Settlement Agreement, 79 FR 47636 (Aug. 14,
2014).
\5\ See Respondents' Motion for Partial Voluntary Remand Without
Vacatur and to Stay Briefing Schedule Pending Resolution of This
Motion, filed Sep. 19, 2014 in WildEarth Guardians v. EPA, No. 13-
9520 (10th Cir.).
\6\ See Order filed Oct. 6, 2014 in WildEarth Guardians v. EPA,
No. 13-9520 (10th Cir.).
---------------------------------------------------------------------------
II. Public Comments and Revised EPA Responses
We received adverse comments on our proposed approval of the
Colorado regional haze SIP, including comments from Guardians related
to our proposed approval of Colorado's BART determinations for Units 1
and 2 at the Comanche Station. We are reissuing our final approval of
the Colorado regional haze SIP with respect to Comanche to provide more
detailed and clearer responses to the Comanche-related adverse
comments. The responses below contain our complete, updated, and
clarified responses to comments related to the Comanche NOX
BART determination.
Comment: The commenter argues that Comanche Units 1 and 2 are
currently meeting lower NOX emission rates than the State's
BART emission limits that EPA proposed to approve. The commenter cited
the State's BART analysis, noting that currently Unit 1 is emitting at
an average annual rate of 0.124 lb/MMBtu and Unit 2 is emitting at an
average annual rate of 0.165 lb/MMBtu, and compares those rates to the
Colorado BART limits: a 30-day emission rate of 0.20 lb/mmBtu, and a
combined annual average emission rate of 0.15 lb/mmBtu. According to
the commenter, allowing these units to emit more pollution than they
currently emit does not represent BART and would not lead to visibility
improvements, and nothing in the CAA or EPA's regulations suggests that
it is appropriate for BART limits to include any such cushion. Further,
the commenter alleges that that under the annual BART limits,
NOX emissions will be allowed to increase by at least 14
tons per year (tpy), and that the 30-day rolling average limits would
allow Unit 1 to emit at least 40% more NOX than the baseline
30-day rolling average peak and Unit 2 to emit 12% more NOX.
The commenter claims that the data demonstrates that Unit 1 could meet
a 30-day rolling average NOX emission limit of 0.15 lb/MMBtu
and Unit 2 could meet a limit of 0.18 lb/MMBtu without any trouble, and
that the BART limits should reflect what is achievable. Accordingly,
the commenter asserts that EPA must disapprove Colorado's
NOX BART determinations for Comanche Unit 1 and Unit 2 and
adopt a FIP that establishes BART limits that represent actual emission
reductions.\7\
---------------------------------------------------------------------------
\7\ Comments submitted by WildEarth Guardians (hereinafter
referred to as ``Guardians' Comments'') at 5-6, EPA-R08-OAR-2011-
0770-0040 Attachment 2 (May 25, 2012).
---------------------------------------------------------------------------
Response: We disagree with this comment. The State set
NOX BART emission limits for Comanche Units 1 and 2
individually at a 30-day rolling average emission rate of 0.20 lb/MMBtu
and a combined annual average emission rate of 0.15 lb/MMBtu. As EPA
requested in our October 26, 2010 comment letter during the state
public comment process, the State considered tightening the 30-day
limits, but ultimately chose not to do so. In EPA's judgment, the State
could have better explained the basis for the margin for compliance,
but a more robust analysis
[[Page 29955]]
would not have led it to reach a different conclusion as to the
Comanche NOX BART limits. Further, if we were to disapprove
the SIP and promulgate a FIP with lower emission limits, the actual
emissions from Comanche would unlikely be significantly lower. We
therefore decline to disapprove the NOX BART determination
for Comanche.
In our October 26, 2010 comment letter to the State, we asked
Colorado to evaluate tightening Comanche's NOX limits. The
State conducted that evaluation.\8\ Based on its experience, and after
reviewing other state BART proposals, Colorado found that 30-day
rolling average NOX emission rates could be expected to be
up to approximately 15% higher than annual average emission rates. With
this in mind, and also considering uncertainty regarding load
fluctuations, cold-weather operating, startup, and increased cycling to
back up renewable energy generation, the State concluded that a 0.20
lb/MMBtu 30-day rolling average emission limit was appropriate for both
units.
---------------------------------------------------------------------------
\8\ See Colorado Regional Haze Submittal, Appendix C (Technical
Support Documents for BART Determination), BART Analysis of Control
Options For Public Service Company--Comanche Station, Units 1 and 2,
at 17-19 (EPA-R08-OAR-2011-0770-0013, PDF pages 312-14); see also
Appendix C--Technical Support Documents for BART Determination (EPA-
R08-OAR-2011-0770-0017), Attachment 5: Public Service Company--
Comanche Station Units 1 and 2 Technical Analysis.
---------------------------------------------------------------------------
As a general matter, EPA finds it appropriate and reasonable to
allow a margin for compliance in setting 30-day rolling average BART
limits, and we have approved other state BART determinations that
included such margins. The shorter 30-day averaging period results in
higher variability in emissions because of load variation, startup,
shutdown, and other factors. Accordingly, we have not generally
required that 30-day rolling average emission limits be equal to the
annual emission rates used for calculating cost-effectiveness. We find
the State's application of a margin for compliance here consistent with
that approach.
The compliance margin included for the Comanche units is larger
than we would generally expect. But we find that with respect to
Comanche, the compliance margin is unlikely to lead to significant
actual NOX emissions increases. After all, the lower
Comanche emissions cited by the commenter occurred under permit limits
identical to those the State selected as BART, and the commenter has
provided no evidence that the facility will change its operations just
because the State has adopted the permit limits as BART limits.
Instead, emission rates are likely to remain near the baseline figures
cited by the commenter, which as the commenter notes are below the BART
limits. An occasional rise is possible in light of the uncertainties
referred to above, which is the purpose of allowing a margin for
compliance above the actual 30-day rolling average emissions levels.
The commenter appeared to at least partly acknowledge this reality,
stating that ``[w]e do not suggest that the State was required to set
the emission limits exactly at the levels emitted.'' \9\ But none of
these uncertainties suggests that there will be a consistent increase
in emissions over the long term.
---------------------------------------------------------------------------
\9\ Guardians' Comments at 8.
---------------------------------------------------------------------------
As for annual average emission rates, Colorado found that in 2009,
the annual average rate for both units combined was about 0.15 lb/
MMBtu. Colorado did not propose applying a margin of compliance to the
2009 annual average rate, and set a limit at 0.15 lb/MMBtu. Because
short-term emissions increases and decreases should average out over
the course of any single year, we believe that setting the BART annual
emission limit at about the annual emission rate from 2009 is
reasonable, unless there is evidence that the source was not properly
operated in 2009 or that annual average source operating conditions in
2009 were unrepresentative of future operations. The commenter has not
alleged that there is any such evidence. The commenter does assert that
the 0.15 lb/MMBtu annual limit would allow an increase in actual
emissions if both units operate at the BART limit. The potential
emissions increase calculated by the commenter, however, would only be
14 tons of NOX per year. A 14-ton increase is not
significant when compared to the annual NOX emissions of
approximately 3,860 tons from Comanche Units 1 and 2; it does not
warrant disapproval and a subsequent FIP.\10\
---------------------------------------------------------------------------
\10\ Discussing state flexibility to exempt de minimis emission
levels from a BART analysis, the BART Guidelines make a similar
point: ``If a State were to undertake a BART analysis for emissions
of less than 40 tons of SO2 or NOX . . . from
a source, it is unlikely to result in anything but a trivial
improvement in visibility. This is because reducing emissions at
these levels would have little effect on regional emissions loadings
or visibility impairment.'' 70 FR at 39117.
---------------------------------------------------------------------------
The commenter alleges, but does not support or quantify, a
``likely'' further increase (beyond the claimed 14-ton increase) based
on the potential for one unit to exceed 0.15 lb/MMBtu while the
combined rate remains below that limit. This comment appears to be
referring to a scenario in which the unit operating above 0.15 lb/MMBtu
would have a higher heat input than the unit operating below 0.15 lb/
MMBtu, so that together they would still comply with the SIP's 0.15 lb/
MMBtu average emission rate limit while having higher emissions than if
each unit were held to a limit of 0.15 lb/MMBtu. With the existing LNB/
OFA controls, though, neither unit can be operated at an emission rate
much below its current emission rate, and so there is unlikely to be
``room'' for the other unit to operate much higher while still meeting
the combined emission limit. Also, the two units are subject to very
similar physical limits on heat input.\11\ We therefore find that any
additional emissions consistent with a 0.15 lb/MMBtu combined limit
would be insignificant from a visibility standpoint. Further, we note
that the annual NOX BART limit of 0.15 lb/MMBtu is below the
average actual emissions of 0.16 lb/MMBtu for Units 1 and 2 between
January and October 2010.\12\ Therefore, Colorado imposed an annual
emission limit that was lower than the then most recent partial-year
figures for Units 1 and 2.
---------------------------------------------------------------------------
\11\ See Colorado Regional Haze Submittal, Appendix C (Technical
Support Documents for BART Determination), BART Analysis of Control
Options For Public Service Company--Comanche Station, Units 1 and 2,
at 2, Table 1: Comanche Units 1 and 2 Technical Information (EPA-
R08-OAR-2011-0770-0013, PDF page 297 (citing boiler ratings of 3,531
MMBtu/hr for Unit 1 and 3,482 MMBtu/hr for Unit 2).
\12\ January-October 2010 is the most recent annual average
emission rate period discussed by Colorado in the regional haze SIP.
See id. at 18 (PDF page 313).
---------------------------------------------------------------------------
The commenter also argues that the 30-day rolling average limits of
0.20 lb/MMBtu would allow emission increases because the actual 30-day
rolling average rates have consistently been below this number. Annual
emissions are controlled by the SIP's limit of 0.15 lb/MMBtu for the
average of the two unit's annual average emission rates, and would be
so controlled even if there were no 30-day limits at all. The issue of
whether the State and EPA correctly assessed how well the annual limit
will control annual emissions was addressed above. Therefore, EPA
understands that this comment regarding the 30-day limits of 0.20 lb/
MMBtu is meant to address the possibility that the emission rate of one
or both units in 30-day periods may be higher than 0.15 lb/MMBtu, while
the source could still comply with respect to the annual average limit
by having lower emissions in other 30-day periods. EPA agrees that this
is possible, but the State modeled the baseline visibility impact of
the source assuming a constant emission rate of 0.20 lb/MMBtu, so the
possibility has been fully considered.
[[Page 29956]]
For these reasons, we have determined that while the State could
have better explained the basis for the margin for compliance it
allowed, a more robust analysis would not have led it to reach a
different conclusion as to the NOX emission limits for
Comanche Units 1 and 2. In its next regional haze SIP, the State can
review the longer history of emissions from Comanche that will be
available then, and consider whether a downward adjustment in the
emission limit is appropriate to ensure the best possible operation of
the emission controls.
Comment: The commenter asserts that the State failed to
appropriately assess the cost of SCR, by assuming that SCR would
achieve an emission rate of 0.07 lb/MMBtu on an annual average basis.
But, according to the commenter, EPA has noted that SCR can achieve
emission rates as low as 0.04 lb/MMBtu on an annual basis, and a 0.05
lb/MMBtu emission rate on an annual average basis is a more appropriate
benchmark from which to assess the cost-effectiveness of SCR. The
commenter claims that because the State did not assess the cost-
effectiveness of SCR based on a rate of 0.05 lb/MMBtu, the State did
not reasonably take into account the cost of compliance with SCR in
accordance with the CAA. The commenter adds that although EPA and the
State may claim that SCR would not be cost-effective in any case, there
is no support for such an assertion, and without an adequate case-
specific cost analysis, there is no support for concluding that SCR is
unreasonable, particularly for Unit 2.\13\
---------------------------------------------------------------------------
\13\ Guardians' Comments at 9.
---------------------------------------------------------------------------
Response: We disagree with this comment. We have reviewed the
information in the administrative record for this action again, and we
find that our previous conclusion is still correct. We agree that SCR
can achieve annual NOX emission rates of 0.05 lb/MMBtu, and
that ideally Colorado would have used this value when assessing the SCR
control option.\14\ But if the State had done so, the marginally lower
emissions would not have caused the State to reach a different
conclusion as to what technology is BART.
---------------------------------------------------------------------------
\14\ Throughout this notice, our references to the use of SCR at
Comanche incorporate the effects of LNB/OFA. Thus, when we discuss
comparing the effects of SCR against the baseline, we are comparing
SCR operating with LNB/OFA against the post-2009 baseline of LNB/OFA
alone.
---------------------------------------------------------------------------
First, we note that the comment misstates the rate that Colorado
actually used for the purpose of calculating cost-effectiveness. In the
Comanche NOX BART analysis, the State assumed an annual
emissions rate for SCR of 0.061 lb/MMBtu--not 0.07 lb/MMBtu.\15\ (The
latter figure was the 30-day rolling average rate, not the annual
average as the commenter contends.\16\) Therefore, the relevant
comparison for the commenter's purpose would be between the 0.061 lb/
MMBtu annual average rate that the State used and the 0.05 lb/MMBtu
annual average emission rate that the commenter prefers.
---------------------------------------------------------------------------
\15\ See Colorado Regional Haze Submittal, Appendix C (Technical
Support Documents for BART Determination), BART Analysis of Control
Options For Public Service Company--Comanche Station, Units 1 and 2,
Tables 10 and 11, at 20-21 (R08-OAR-2011-0770-0013, PDF pages 315-
16; see also Technical Support Documents for BART Determination
(EPA-R08-OAR-2011-0770-0017), Attachment: Public Service Company--
Cmanche Station, Units 1 and 2 Technical Analysis (.xls format
spreadsheet file, tabs ``Comanche 1 NOX'' and ``Comanche
2 NOX''). There is an inconsequential (approx. 0.33%)
difference between the Unit 1 baseline numbers in these two parts of
the record; the discussion in this rule uses the 1506 tpy figure
from the State's technical analysis spreadsheet.
\16\ Id.
---------------------------------------------------------------------------
Using the 0.061 lb/MMBtu annual average emission rate, Colorado
estimated emissions of 740 tpy for Unit 1 and 869 tpy for Unit 2 with
SCR.\17\ Based on those estimated emissions, the State calculated
emission reductions of 770.4 tpy for Unit 1 and 1,480 tpy for Unit 2,
compared to a baseline level of emissions measured in 2009 that
reflected the installation of LNB/OFA controls.\18\ Based on these
reductions, the State derived cost-effectiveness values for SCR of
$15,920 per ton and $9,900 per ton for Units 1 and 2, respectively.\19\
It is a simple exercise to insert the annual average emission rate of
0.05 lb/MMBtu into the State's technical analysis spreadsheet.\20\
Doing so, we can see that using the figure the commenter recommends
would have produced estimated emission levels of about 609 tpy for Unit
1 and 713 tpy for Unit 2 with SCR, which in turn give emission
reductions of 897 tpy (Unit 1) and 1,636 tpy (Unit 2) compared to a
2009 baseline level and cost-effectiveness values of $13,670 and $8,956
per ton for Units 1 and 2, respectively.\21\ Considering that these
adjusted cost-effectiveness values remain high and (as discussed below)
the extent of the benefits associated with SCR remains low, we do not
believe that the impact on the BART analysis would have led to a
different conclusion if Colorado had used the more stringent emission
rate. Therefore, we conclude that the State's use of 0.061 lb/MMBtu to
evaluate the cost-effectiveness of SCR at Comanche is not grounds for
disapproval.
---------------------------------------------------------------------------
\17\ Id.
\18\ ``[T]he Division used years 2009 (annual averages and 30-
day rolling) for baseline emissions for reduction and cost
calculations.'' Colorado Regional Haze Submittal, Appendix C
(Technical Support Documents for BART Determination), BART Analysis
of Control Options For Public Service Company--Comanche Station,
Units 1 and 2, at 3 (R08-OAR-2011-0770-0013, PDF page 298); see also
id., Table 2 (``PSCo Comanche Units 1 & 2 Baseline Emissions'').
\19\ See Colorado Regional Haze Submittal, Appendix C (Technical
Support Documents for BART Determination), BART Analysis of Control
Options For Public Service Company--Comanche Station, Units 1 and 2,
Tables 10-13, at 20-21 (R08-OAR-2011-0770-0013, PDF pages 315-16).
\20\ See Technical Support Documents for BART Determination
(EPA-R08-OAR-2011-0770-0017), Attachment: Public Service Company--
Comanche Station, Units 1 and 2 Technical Analysis (Excel
spreadsheet file, tabs ``Comanche 1 NOX''and ``Comanche 2
NOX'').
\21\ For Unit 1, the State also calculated an incremental value
to assess the cost-effectiveness of SCR over SNCR. Even after making
the correction to an assumed annual average rate of 0.05 lb/MMBtu as
described above, this value remains very high: $23,497 per ton.
---------------------------------------------------------------------------
Comment: The commenter states that Colorado appears to have
overestimated the capital cost of SCR, in that the State's reliance on
the CUECost model led to artificially inflated capital costs. According
to the commenter, both EPA and the National Park Service (NPS)
previously commented to the State that the State should have used EPA's
Control Cost Manual, and both noted that the CUECost model relied upon
by the State is not appropriate. The commenter argues that the State
does not explain in the record why its use of CUECost was reasonable,
particularly in light of the concerns expressed by EPA and the NPS.\22\
---------------------------------------------------------------------------
\22\ Guardians' Comments at 9.
---------------------------------------------------------------------------
Response: We agree that there were flaws in Colorado's approach to
estimating the costs of SCR for the Comanche BART units, and that the
CUECost model likely yielded an inflated cost estimate. In the
referenced correspondence, EPA stated that ``the CUECost model yields
high capital costs for the Comanche facility,'' and suggested that the
capital costs calculated would have been approximately 50% lower if the
CCM had been followed.\23\ But even if we reduce the capital cost
estimates by that percentage, and also adjust the emission rate as
discussed in the previous comment, we believe that the cost of SCR at
Comanche would still be high compared to the visibility benefits, and
[[Page 29957]]
that Colorado's decision not to require SCR would still be reasonable.
---------------------------------------------------------------------------
\23\ Letter from Callie Videtich, EPA, to Paul Tourangeau, CDPHE
(Oct. 26, 2010), at 8-9 (EPA-R08-OAR-2011-0770-0043, Attachment 19).
EPA stated that using the CCM to assess SCR capital costs for the
Comanche BART units yielded an estimate of approximately $120/kW, as
opposed to the $247/kW (Unit 1) and $248/kW (Unit 2) derived from
the CUECost model. Id. This ratio of dollars per kW results in a
51.6% lower estimate.
---------------------------------------------------------------------------
Specifically, cutting the capital cost estimate by 51.6%, and using
the more stringent 0.05 lb/MMBtu emission rate discussed in the
previous comment, produces cost-effectiveness values of $9,319 and
$6,481 per ton for employing SCR at Units 1 and 2, respectively.\24\
Thus, even after addressing both of the cost issues raised by the
commenter, the cost-effectiveness values remain high. Also, as
discussed below in response to another comment, we have concluded that
the visibility benefits that would result from SCR are insufficient to
justify these high costs. Accordingly, we do not believe that Colorado
would have reached a different NOX BART conclusion if it had
used the CCM in its analysis (as well as the more stringent emission
rate discussed previously).
---------------------------------------------------------------------------
\24\ The 51.6% adjustment to capital cost can be made by
multiplying the ``total capital costs'' figures on the State's
technical analysis spreadsheet by 0.484. See Technical Support
Documents for BART Determination (EPA-R08-OAR-2011-0770-0017),
Attachment: Public Service Company--Comanche Station, Units 1 and 2
Technical Analysis (.xls format spreadsheet file, tabs ``Comanche 1
NOX'' and ``Comanche 2 NOX''). In addition to
capital costs, the cost-effectiveness calculations incorporate
operating and maintenance costs, which the commenter did not
challenge.
---------------------------------------------------------------------------
In its SIP, the State explained that, in its view, SCR for
NOX control would generally be reasonable if costs did not
exceed $5,000 per ton of pollutant reduced, and if the controls
provided a modeled visibility benefit of 0.50 deciviews (dv) or greater
at the primary Class I Area affected.\25\ Considering the State's
guidance, it is clear that making the adjustments that the commenter
requests would not lead to a different outcome. Therefore, considering
all the BART factors, we do not see a basis to conclude that using a
lower capital cost estimate, combined with a 0.05 lb/MMBtu emission
rate for SCR, would have led the State to reach a different conclusion
or should lead us to disapprove the State's BART determination.
---------------------------------------------------------------------------
\25\ See Colorado Regional Haze Submittal at 52 (R08-OAR-2011-
0770-0013, PDF page 53).
---------------------------------------------------------------------------
Comment: The commenter states that Colorado and EPA may claim that,
even if the costs were accurately assessed, the visibility benefits of
SCR would not be significant, but that there is no support for this
assertion. According to the commenter, it appears that Colorado's
assessment of visibility improvements is based on an assumption that
the proposed BART limits, which the commenter refers to as the ``do
nothing'' BART limits, would actually improve visibility. But, the
commenter claims, the proposed BART limits would allow increased
emissions, and therefore would not improve visibility. On the other
hand, states the commenter, SCR would appear to provide significant
visibility improvements. The commenter argues that for Unit 2 this is
especially significant because SCR was the only available technology
analyzed for BART.\26\
---------------------------------------------------------------------------
\26\ Guardians' Comments at 9-10.
---------------------------------------------------------------------------
Response: We disagree with this comment. In relation to the high
costs, the visibility benefits of SCR at Comanche are not sufficiently
large to warrant disapproval of the State's BART determination. We
would come to this conclusion regardless of whether the cost component
of the BART analysis involved the State's original figures or the
adjusted figures discussed above in response to previous comments. The
State estimated that SCR would produce visibility improvements of 0.14
dv (Unit 1) and 0.17 dv (Unit 2) as compared to the 2009 post-LNB/OFA
baseline.\27\ This level of expected visibility improvement from SCR is
insufficient to cause us to conclude that the State's BART
determination is unreasonable.
---------------------------------------------------------------------------
\27\ See Colorado Regional Haze Submittal, Appendix C (Technical
Support Documents for BART Determination), BART Analysis of Control
Options For Public Service Company--Comanche Station, Units 1 and 2,
Table 15, at 24 (R08-OAR-2011-0770-0013, PDF page 319). As discussed
below, the table also includes information on improvements over the
pre-control baseline; this information is illustrative and was not
the basis for the BART determination or for our approval of the
State's action.
---------------------------------------------------------------------------
As discussed above in response to a previous comment, we recognize
that the State did not use the 0.05 lb/MMBtu emission rate that
accurately represents the performance capabilities of SCR. Accordingly,
it is reasonable to expect that the State would have estimated slightly
greater visibility benefits from SCR if it had used the 0.05 lb/MMBtu
rate. In EPA's judgment, however, the visibility benefits compared to
the 2009 baseline would have remained modest. We note, for instance,
that in the State's analysis of Comanche Unit 1, the difference in
visibility benefit between selective non-catalytic reduction (SNCR)
(with a NOX emission rate of 0.10 lb/MMBtu) and SCR (with a
NOX emission rate of 0.07 lb/MMBtu) is only 0.03 dv.\28\ We
conclude that the impact of a further reduction in emission rate to
0.05 lb/MMBtu would be similarly small.\29\
---------------------------------------------------------------------------
\28\ What are labeled by the State as ``NOX emission
rates'' (e.g., Table 15 of their analysis) are actually the 30-day
emission limits. See Colorado Regional Haze Submittal, Appendix C
(Technical Support Documents for BART Determination), BART Analysis
of Control Options For Public Service Company--Comanche Station,
Units 1 and 2, Table 15, at 24 (R08-OAR-2011-0770-0013, PDF page
319). Actual 30-day emission rates have been lower. See id. at 18
(PDF page 313).
\29\ Thus, comparing the SNCR and SCR numbers, we see that a
NOX emissions rate reduction from 0.10 to 0.07 lb/MMBtu
is reflected in a visibility improvement from 0.11 to 0.14 dv. If we
assume, for the purpose of conservatively estimating visibility
improvements, that there is a linear relationship between emission
reductions and visibility improvement, then further reducing the
NOX emission rate from 0.07 to 0.05 lb/MMBtu might cause
visibility improvements at Units 1 and 2 to increase from 0.14 and
0.178 dv to approximately 0.16 and 0.198 dv. See Approval and
Promulgation of Air Quality Implementation Plans; State of Florida;
Regional Haze State Implementation Plan, 78 FR 53250, 53267 (Aug.
29, 2013) (``[A]n assumption of a linear response to changes in
emissions is a reasonable estimation and the simplified methodology
used for these BART determinations likely provides conservative
overestimates of visibility impact reductions.'').
---------------------------------------------------------------------------
As mentioned previously, the State explained that, in its view, SCR
for NOX control will generally be reasonable when costs do
not exceed $5,000 per ton of pollutant reduced, and when the controls
provide a modeled visibility benefit of 0.50 dv or greater at the
primary Class I Area affected.\30\ While we agree with the State that
these guidance criteria should not be used as absolute determinants of
BART outcomes, they are in general consistent with the decisions that
other states and EPA have made when considering whether to require SCR
as NOX BART, and generally reflect a reasonable balancing of
the BART factors. In this case, we expect that even using the SCR
emission rate requested by the commenter, the visibility improvement
from SCR would fall well below the State's criteria. Judging these
visibility improvements against the fairly high cost of SCR (again,
even after adjustment to reflect the comments), we find that the
State's decision not to impose SCR was reasonable.
---------------------------------------------------------------------------
\30\ See Colorado Regional Haze Submittal at 52 (R08-OAR-2011-
0770-0013, PDF page 53).
---------------------------------------------------------------------------
The commenter incorrectly asserted that the State's BART
determination was based on the assumption that existing controls would
improve visibility compared to current levels. Colorado did not claim
that its BART emission limits would result in visibility benefits
compared to current levels (that is, compared to the 2009 post-LNB/OFA
emissions baseline). The State did note that the existing level of
control provided benefits when compared to the 2004 baseline, which is
true. But while Colorado referred to both a pre-LNB/OFA baseline and a
2009 baseline when discussing visibility benefits, the State actually
used only the 2009 baseline in calculating cost-effectiveness, and
likewise relied on visibility benefits based on the 2009 baseline in
making the BART determination for
[[Page 29958]]
Comanche.\31\ We have reviewed the visibility estimates and cost
calculations that the State relied on when making its BART
determination for Comanche and have confirmed that they were based on
comparisons to the 2009 baseline.\32\
---------------------------------------------------------------------------
\31\ Colorado stated in the SIP that ``the Division used year[ ]
2009 (annual averages and 30-day rolling) for baseline emissions for
reduction and cost calculations.'' See Colorado Regional Haze
Submittal, Appendix C (Technical Support Documents for BART
Determination), BART Analysis of Control Options For Public Service
Company--Comanche Station, Units 1 and 2, at 20-21, 24 (R08-OAR-
2011-0770-0013, PDF pages 315-16, 319); see also Appendix C--
Technical Support Documents for BART Determination (EPA-R08-OAR-
2011-0770-0017), Attachment 5: Public Service Company--Comanche
Station Units 1 and 2 Technical Analysis. Likewise, the State's BART
determination cites only the 0.14 dv and 0.17dv visibility
improvement numbers derived from comparison to the 2009 baseline.
See Colorado Regional Haze Submittal at 66 (R08-OAR-2011-0770-0013,
PDF page 67).
\32\ In replying to this comment and one other comment in the
December 2012 final approval, we inadvertently made a confusing
statement concerning the applicable baselines. In that notice, we
stated that Colorado had ``assessed the benefit of control options
relative to both the subject-to-BART baseline and to the
installation of new low- NOX burners (LNB) [with over-
fire air] in 2007 and 2008.'' Further, we noted that ``relative to
the subject-to-BART baseline, Colorado's BART selection (combustion
controls), does in fact show visibility improvement.'' These
statements appeared to suggest that it was appropriate for Colorado
to use a 2009 baseline when evaluating the benefits of SNCR and SCR,
but a 2004 (pre-LNB/OFA) baseline to evaluate the State's proposed
BART option. That was not our intention. Our reference to the 2004
subject-to-BART baseline--that is, to the emissions level before the
installation of the LNB/OFA, which were required to comply with non-
BART CAA requirements--was merely an observation, by which we
intended to show that the installation of those controls had
produced real air quality improvements over previous levels. That
illustration was not, however, intended to be part of our evaluation
of the State's cost or visibility analyses.
---------------------------------------------------------------------------
It was correct for the State to use the 2009 baseline for
NOX emissions from Units 1 and 2 in the BART determination.
The CAA requires that, in making BART determinations, states and EPA
take into consideration ``any existing pollution control technology in
use at the source.'' \33\ As we explained in detail in our final action
on the Wyoming regional haze SIP, this consideration should generally
incorporate controls into baseline emissions if the controls were
installed to comply with CAA requirements other than the BART
requirement.\34\ That is exactly what happened with respect to Comanche
Units 1 and 2. The controls in question had been placed on these units
to ``net out'' of Prevention of Significant Deterioration (PSD) review
requirements for NOX and SO2 emissions from the
new Unit 3.\35\ Therefore, it was appropriate for the State to use the
2009 emissions baseline, which reflected the reductions achieved by
LNB/OFA, in its BART analysis for Comanche.
---------------------------------------------------------------------------
\33\ 42 U.S.C. 7491(g)(2).
\34\ 79 FR 5032, 5104-05 (Jan. 30, 2014).
\35\ See Colorado Regional Haze Submittal, Appendix C (Technical
Support Documents for BART Determination), BART Analysis of Control
Options For Public Service Company--Comanche Station, Units 1 and 2,
at 1 (R08-OAR-2011-0770-0013, PDF page 1) (``As part of that [2004
construction] project, PSCo proposed to install control devices on
the existing units.''); see also Colorado Operating Permit #
96OPPB133 (Comanche Station) (``. . . PSCo proposed to install
NOX controls (low NOX burners with over-fire
air) on both Units 1 and 2 . . . to `net-out' of Prevention of
Significant Deterioration (PSD) review requirements for
NOX and SO2''), posted at https://www.colorado.gov/pacific/cdphe/operating-permits-company-index.
---------------------------------------------------------------------------
Finally, we addressed the assertion that the State's BART limits
would lead to increased emissions in our response to a previous
comment. The commenter has failed to offer any support for this claim,
and we do not find any basis to conclude that increased emissions will
result from the State's BART limits.
For the above reasons, while we agree that SCR at Comanche Units 1
and 2 would result in visibility improvements, we find that the State
reasonably concluded that those visibility improvements would not be
sufficient to justify the cost involved.
Comment: The commenter states that it is unclear why Colorado
rejected SNCR for Comanche Unit 1, particularly because the proposed
BART limit for Unit 1 is less stringent than Unit 1's current actual
emissions. Citing EPA figures, the commenter asserts that Unit 1 would
meet a 30-day rolling average emission rate of 0.10 lb/MMBtu under an
SNCR scenario. The commenter notes that the State found that the cost
of $3,644 per ton of NOX reduced and the perceived ``low
visibility improvement'' warranted a determination that SNCR was not
reasonable for Unit 1. The commenter asserts, however, that this cost
is squarely within the range of what Colorado considers to be cost-
effective.\36\
---------------------------------------------------------------------------
\36\ Guardians' Comments at 10.
---------------------------------------------------------------------------
Response: We find that the State's rejection of SNCR was reasonable
based on its weighing of the BART factors. The State concluded that the
cost of SNCR was not warranted given the relatively modest 0.11 dv
visibility improvement that would result. Even if a control technology
is cost-effective on a dollar per ton basis, a state may conclude that
the control technology is not warranted based on a reasonable
consideration of all five BART factors.
Comment: The commenter states that Colorado's analysis indicates
that SNCR would achieve greater emission reductions than an emission
rate of 0.20 lb/MMBtu on a 30-day rolling average. According to the
commenter, although the State asserts that the visibility improvement
from SNCR would amount to 0.11 dv, it is unclear why such improvements
are not reasonable or are insignificant, particularly given that the
purpose of BART is to reduce or eliminate visibility impairment. The
commenter argues that there is no explanation in the record supporting
the State's assertion. Further, the commenter argues that it appears as
if the State's assessment of visibility improvements is based on an
incorrect assumption that the proposed BART limit would actually
improve visibility. The commenter states that when compared to the real
impacts of the State's proposed BART limit for Comanche Unit 1, SNCR
appears to provide significant visibility improvements, because, as
opposed to the proposed BART limit, SNCR would actually achieve
improvements. Therefore, the commenter concludes, EPA must promulgate a
FIP that establishes an appropriate NOX BART limit for
Comanche Unit 1.\37\
---------------------------------------------------------------------------
\37\ Guardians' Comments at 10.
---------------------------------------------------------------------------
Response: The commenter is correct that the State predicted that
SNCR would result in additional improvement in visibility over the
control technology that the State selected as BART. However, this does
not mean that the CAA or our regulations required the State to select
SNCR as BART. For the reasons stated above, we find that it was
reasonable for the State to reject SNCR based on consideration of all
five BART factors. We agree that SNCR would result in visibility
improvements, but as with SCR, we agree with the State's assessment
that the visibility improvements were insufficient to justify the cost
involved.
Regarding the commenter's claim that the State's selected limits
will lead to an increase in emissions, as discussed above in detail,
the commenter has presented no evidence that any emissions increase
will occur.
III. Final Action
With respect to the Comanche Station, EPA is re-finalizing its
approval of the Colorado regional haze SIP submitted on May 25, 2011.
Because this re-finalization merely gives additional explanation in
response to comments and does not alter any previous determinations, it
does not affect any applicable SIP compliance deadlines. Our action is
based on an evaluation of Colorado's regional haze SIP submittal for
Comanche against the regional haze
[[Page 29959]]
requirements at 40 CFR 51.300-51.309 and CAA sections 169A and 169B.
All general SIP requirements contained in CAA section 110, other
provisions of the CAA, and our regulations applicable to this action
were also evaluated. The purpose of this action is to ensure compliance
with these requirements and to provide additional rationale to support
our conclusions.
IV. Incorporation by Reference
In this rule, the EPA is finalizing regulatory text that includes
incorporation by reference. In accordance with requirements of 1 CFR
51.5, the EPA is finalizing the incorporation by reference of Colorado
revisions to its SIP to address the requirements of EPA's regional haze
rule discussed in section III, Final Action, of this preamble. The EPA
has made, and will continue to make, these documents generally
available electronically through www.regulations.gov and/or in hard
copy at the appropriate EPA office (see the ADDRESSES section of this
preamble for more information).
V. Statutory and Executive Order Reviews
Under the Clean Air Act, the Administrator is required to approve a
SIP submission that complies with the provisions of the Act and
applicable federal regulations. 42 U.S.C. 7410(k); 40 CFR 52.02(a).
Thus, in reviewing SIP submissions, EPA's role is to approve state
choices, provided that they meet the criteria of the Clean Air Act.
Accordingly, this action merely approves state law as meeting federal
requirements and does not impose additional requirements beyond those
imposed by state law. For that reason, this action:
Is not a ``significant regulatory action'' subject to
review by the Office of Management and Budget under Executive Order
12866 (58 FR 51735, October 4, 1993);
Does not impose an information collection burden under the
provisions of the Paperwork Reduction Act (44 U.S.C. 3501 et seq.);
Is certified as not having a significant economic impact
on a substantial number of small entities under the Regulatory
Flexibility Act (5 U.S.C. 601 et seq.);
Does not contain any unfunded mandate or significantly or
uniquely affect small governments, as described in the Unfunded
Mandates Reform Act of 1995 (Pub. L. 104-4);
Does not have federalism implications as specified in
Executive Order 13132 (64 FR 43255, August 10, 1999);
Is not an economically significant regulatory action based
on health or safety risks subject to Executive Order 13045 (62 FR
19885, April 23, 1997);
Is not a significant regulatory action subject to
Executive Order 13211 (66 FR 28355, May 22, 2001);
Is not subject to requirements of Section 12(d) of the
National Technology Transfer and Advancement Act of 1995 (15 U.S.C. 272
note) because this action does not involve the use of measurement or
other standards; and
Does not provide EPA with the discretionary authority to
address, as appropriate, disproportionate human health or environmental
effects, using practicable and legally permissible methods, under
Executive Order 12898 (59 FR 7629, February 16, 1994).
The SIP is not approved to apply on any Indian reservation
land or in any other area where EPA or an Indian tribe has demonstrated
that a tribe has jurisdiction. In those areas of Indian country, the
rule does not have tribal implications and will not impose substantial
direct costs on tribal governments or preempt tribal law as specified
by Executive Order 13175 (65 FR 67249, November 9, 2000).
The Congressional Review Act, 5 U.S.C. 801 et seq., as added by the
Small Business Regulatory Enforcement Fairness Act of 1996, generally
provides that before a rule may take effect, the agency promulgating
the rule must submit a rule report, which includes a copy of the rule,
to each House of the Congress and to the Comptroller General of the
United States. EPA will submit a report containing this action and
other required information to the U.S. Senate, the U.S. House of
Representatives, and the Comptroller General of the United States prior
to publication of the rule in the Federal Register. A major rule cannot
take effect until 60 days after it is published in the Federal
Register. This action is not a ``major rule'' as defined by 5 U.S.C.
804(2).
Under section 307(b)(1) of the Clean Air Act, petitions for
judicial review of this action must be filed in the United States Court
of Appeals for the appropriate circuit by July 27, 2015. Filing a
petition for reconsideration by the Administrator of this final rule
does not affect the finality of this action for the purposes of
judicial review nor does it extend the time within which a petition for
judicial review may be filed, and shall not postpone the effectiveness
of such rule or action. This action may not be challenged later in
proceedings to enforce its requirements. See section 307(b)(2).
List of Subjects in 40 CFR Part 52
Environmental protection, Air pollution control, Incorporation by
reference, Intergovernmental relations, Nitrogen dioxide, Particulate
matter, Sulfur oxides.
Dated: May 8, 2015.
Debra H. Thomas,
Acting Regional Administrator Region 8.
40 CFR part 52 is amended as follows:
PART 52--APPROVAL AND PROMULGATION OF IMPLEMENTATION PLANS
0
1. The authority citation for Part 52 continues to read as follows:
Authority: 42 U.S.C. 7401 et seq.
Subpart G--Colorado
0
2. Section 52.320 is amended by revising paragraph (c)(124)
introductory text to read as follows:
Sec. 52.320 Identification of plan.
* * * * *
(c) * * *
(124) On May 25, 2011 the State of Colorado submitted revisions to
its State Implementation Plan to address the requirements of EPA's
regional haze rule. On December 31, 2012, EPA issued a final rule
approving this submittal and responding to public comments. On May 26,
2015 EPA reissued the final rule with respect to the nitrogen oxides
(NOX) best available retrofit technology (BART)
determination for the Comanche Generating Station to provide additional
responses to public comments.
* * * * *
[FR Doc. 2015-12491 Filed 5-22-15; 8:45 am]
BILLING CODE 6560-50-P