Energy Conservation for Certain Industrial Equipment: Alternative Efficiency Determination Methods and Test Procedures for Walk-In Coolers and Walk-In Freezers, 27387-27415 [2014-10721]
Download as PDF
Vol. 79
Tuesday,
No. 92
May 13, 2014
Part II
Department of Energy
tkelley on DSK3SPTVN1PROD with RULES2
10 CFR Parts 429 and 431
Energy Conservation for Certain Industrial Equipment: Alternative Efficiency
Determination Methods and Test Procedures for Walk-In Coolers and
Walk-In Freezers; Final Rule
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
PO 00000
Frm 00001
Fmt 4717
Sfmt 4717
E:\FR\FM\13MYR2.SGM
13MYR2
27388
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[Docket Number EERE–2011–BT–TP–0024]
RIN 1904–AC46
Energy Conservation for Certain
Industrial Equipment: Alternative
Efficiency Determination Methods and
Test Procedures for Walk-In Coolers
and Walk-In Freezers
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
The U.S. Department of
Energy (DOE) is revising its regulations
related to the use of methods for
certifying compliance and reporting
ratings in accordance with energy
conservation standards as they apply to
walk-in coolers and walk-in freezers.
These revisions also include a number
of clarifications to the relevant test
procedure that will serve as the basis for
any applicable alternative efficiency
determination method that may be used
to rate certain walk-in cooler and walkin freezer components.
DATES: The effective date of this final
rule is June 12, 2014. The incorporation
by reference of certain standards in this
rulemaking was approved by the
Director of the Office of the Federal
Register as of March 23, 2009 and April
15, 2011.
ADDRESSES: Docket: The docket is
available for review at
www.regulations.gov, including Federal
Register notices, public meeting
attendee lists and transcripts,
comments, and other supporting
documents/materials. All documents in
the docket are listed in the
www.regulations.gov index. However,
not all documents listed in the index
may be publicly available, such as
information that is exempt from public
disclosure.
A link to the docket Web page can be
found at: https://www.regulations.gov/
#!docketDetail;D=EERE-2011-BT-TP0024. This Web page contains a link to
the docket for this rule on the
www.regulations.gov site. The
www.regulations.gov Web page contains
simple instructions on how to access all
documents, including public comments,
in the docket.
For information on how to review the
docket, contact Ms. Brenda Edwards at
(202) 586–2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Ashley Armstrong, U.S. Department
of Energy, Office of Energy Efficiency
tkelley on DSK3SPTVN1PROD with RULES2
SUMMARY:
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
and Renewable Energy, Building
Technologies Program, EE–5B, 1000
Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–6590. Email:
Ashley.Armstrong@ee.doe.gov.
Mr. Michael Kido, U.S. Department of
Energy, Office of the General Counsel,
GC–71, 1000 Independence Avenue
SW., Washington, DC 20585–0121.
Telephone: (202) 586–8145. Email:
Michael.Kido@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
Table of Contents
I. Authority and Background
A. Authority
B. Background
1. Alternative Efficiency Determination
Method
2. Test Procedures for WICF Refrigeration
Equipment
3. Sampling Plan
4. Test Procedures and Prescriptive
Requirements for WICF Foam Panel RValue
5. Performance-Based Test Procedures for
Energy Consumption of Envelope
Components
II. Summary of the Final Rule
III. Discussion
A. Alternative Efficiency Determination
Method
1. Applicable Equipment
2. Validation
a. Number of Tested Units Required for
Validation
b. Tolerances for Validation
3. Certified Rating
4. Verification
a. Failure To Meet a Certified Rating
b. Action Following Determination of
Noncompliance Based Upon
Enforcement Testing
5. Re-Validation
a. Change in Standards or Test Procedures
b. Re-Validation Using Active Models
c. Time Allowed for Re-Validation
B. Refrigeration Test Procedure
1. Component-Level Ratings for
Refrigeration: Overall
2. Component-Level Ratings for
Refrigeration: Metrics
3. Component-Level Ratings for
Refrigeration: Nominal Calculation
Values
a. On-Cycle Evaporator Fan Power
b. Off-Cycle Evaporator Fan Power
c. Defrost Energy
4. Other Test Procedure Changes
a. Nominal Values for Defrost Energy and
Heat Load Calculations
b. Off-Cycle Evaporator Fan Test
c. Refrigerant Oil Testing
d. Temperature Measurement
e. Test Condition Tolerances
f. Pipe Insulation and Length
g. Composition Analysis
h. Unit Cooler Test Conditions
C. Test Procedure for WICF Panel R-Value
(ASTM C518–04)
1. Test Sample Specifications
2. Removal of Panel Facers
3. 48-Hour Testing Window
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
4. Specimen Conditioning Temperatures
5. Flatness Tolerances on Contact Surfaces
6. Panel Testing Temperature Tolerances
7. Additional Modifications to the Panel
Test Procedure
D. Performance-Based Test Procedures for
Panels and Doors of Walk-In Coolers and
Freezers
1. Panels
2. Doors
E. Sampling Plan
F. Other Issues
G. Compliance with Other EPCA
Requirements
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
V. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III, Part C of the Energy Policy
and Conservation Act of 1975 (‘‘EPCA’’
or ‘‘the Act’’, Pub. L. 94–163) sets forth
a variety of provisions designed to
improve energy efficiency. The National
Energy Conservation Policy Act
(‘‘NECPA’’, Pub. L. 95–619) amended
EPCA and established the energy
conservation program for certain
industrial equipment. (42 U.S.C. 6311–
6317) The Energy Independence and
Security Act of 2007 (‘‘EISA 2007’’)
further amended EPCA to include,
among others, two types of industrial
equipment that are the subject of today’s
notice: Walk-in coolers and walk-in
freezers (collectively, ‘‘walk-ins’’ or
‘‘WICFs’’). (42 U.S.C. 6311(1)(G)) Walkins are enclosed storage spaces of less
than 3,000 square feet that can be
walked into and are refrigerated to
temperatures above and at or below 32
degrees Fahrenheit, respectively. (42
U.S.C. 6311(20)(A)) This term, by
statute, excludes equipment designed
for medical, scientific, or research
purposes. (42 U.S.C. 6311(20)(B))
Under EPCA, the energy conservation
program generally consists of four parts:
(1) Testing; (2) labeling; (3) establishing
Federal energy conservation standards;
and (4) certification and enforcement
procedures. The testing requirements
consist of test procedures that
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
manufacturers of covered equipment
must use as the basis for making
representations about the efficiency of
that equipment, including those
representations made to DOE that the
covered equipment complies with the
applicable energy conservation
standards adopted pursuant to EPCA.
(42 U.S.C. 6314(d)) Similarly, DOE must
use these test requirements to determine
whether the products comply with the
relevant energy conservation standards.
See 42 U.S.C. 6313(a) (applying 42
U.S.C. 6295(s) to walk-ins). For certain
consumer products and commercial and
industrial equipment, DOE’s testing
regulations currently allow
manufacturers to use an alternative
efficiency determination method
(AEDM), in lieu of actual testing, to
simulate the energy consumption or
efficiency of certain basic models of
covered products and equipment under
DOE’s test procedure conditions. As
explained in further detail below, an
AEDM is a computer model or
mathematical tool used to help
determine the energy efficiency of a
particular basic model.
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures that DOE
must follow when prescribing or
amending test procedures for covered
products. Included among these criteria
is that the prescribed procedure be
reasonably designed to produce test
results that measure energy efficiency,
energy use, or estimated annual
operating cost of a covered product
during a representative average use
cycle or period of use, and must not be
unduly burdensome to conduct. (42
U.S.C. 6314(a)(2)) DOE provides the
public with an opportunity to comment
on a proposal made under section 6314.
B. Background
tkelley on DSK3SPTVN1PROD with RULES2
1. Alternative Efficiency Determination
Method
As briefly noted above, AEDMs are
computer modeling or mathematical
tools that predict the performance of
non-tested basic models. They are
derived from mathematical models and
engineering principles that govern the
energy efficiency and energy
consumption characteristics of a type of
covered equipment. These computer
modeling and mathematical tools, when
properly developed, can provide a
relatively straightforward and
reasonably accurate means to predict
the energy usage or efficiency
characteristics of a basic model of a
given covered equipment type. These
tools can be useful in reducing a
manufacturer’s testing burden.
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
Where authorized by regulation,
AEDMs enable manufacturers to rate
and certify their basic models by using
the projected energy use or energy
efficiency results derived from these
simulation models. DOE currently
permits manufacturers of a few, limited
types of expensive or highly customized
equipment to use AEDMs when rating
and certifying their equipment.
DOE believes other similar equipment
that must currently be rated and
certified through testing, such as walkin refrigeration systems, could also be
rated and certified through the use of
computer or mathematical modeling.
Consequently, to examine whether
AEDM usage would be appropriate for
walk-in refrigeration systems, DOE
sought comment on this topic and other
related issues in a Request for
Information (RFI). See 76 FR 21673
(April 18, 2011).
DOE subsequently issued a Notice of
Proposed Rulemaking (NOPR) that
proposed to expand and revise DOE’s
existing AEDM requirements for certain
commercial equipment covered under
EPCA. 77 FR 32038 (May 31, 2012).
Among other things, the May 2012
NOPR proposed to allow manufacturers
of walk-in refrigeration systems to use
AEDMs when certifying the energy use
or energy efficiency of basic models of
equipment in lieu of testing.
Subsequent to the May 2012 NOPR’s
publication, the Appliance Standards
and Rulemaking Federal Advisory
Committee (ASRAC) unanimously
decided to form a working group
(‘‘Working Group’’) to engage in a
negotiated rulemaking effort on the
certification of commercial heating,
ventilating, air conditioning (HVAC),
water heating (WH), and refrigeration
equipment. During the Working Group’s
first meeting on April 30, 2013, Working
Group members voted to expand the
scope of its efforts to include developing
methods of estimating equipment
performance based on AEDM
simulations for commercial HVAC, WH,
and refrigeration equipment. The issues
discussed by the various participants
during the negotiations with DOE were
similar to those raised by the
commenters in response to the May
2012 NOPR, which included AEDM
validation and DOE verification of
ratings derived using an AEDM. As a
result of these negotiations and further
consideration of written comments
submitted in response to DOE’s
supplemental notice of proposed
rulemaking (SNOPR) regarding the
treatment of commercial HVAC, WH,
and refrigeration equipment, see 78 FR
62472 (Oct. 22, 2013), DOE adopted the
Working Group’s AEDM
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
27389
recommendation with respect to this
group of equipment. 78 FR 79579 (Dec.
31, 2013).
To comprehensively address the
specific issues related to walk-ins, DOE
published an SNOPR that proposed to
align DOE’s AEDM regulations by
allowing the use of AEDMs when
certifying the energy efficiency
performance of walk-in refrigeration
equipment in a manner similar to that
which was recently established for
commercial HVAC, refrigeration, and
WH equipment. See 79 FR 9817 (Feb.
20, 2014). This approach, which was
recommended by the Working Group,
would help DOE establish a uniform,
systematic, and fair approach to the use
of these types of modeling techniques
that will enable DOE to ensure that
products in the marketplace are
correctly rated—irrespective of whether
they are subject to actual physical
testing or are rated using modeling—
without unnecessarily burdening
regulated entities. DOE reopened the
comment period for the February 20,
2014 SNOPR to allow interested parties
additional time to provide the
Department with comments, data, and
information. See 79 FR 19844 (April 10,
2014). DOE did not receive any
additional timely submitted comments
in response to the reopened comment
period. Today’s notice is the
culmination of DOE’s efforts regarding
AEDMs for walk-in coolers and freezers
that were initiated with the May 2012
NOPR.
2. Test Procedures for WICF
Refrigeration Equipment
A walk-in’s refrigeration system
performs the mechanical work
necessary to cool the interior space of a
walk-in. The system typically comprises
two separate primary components, a
condenser/compressor (‘‘condensing
unit’’) and an expansion valve/
evaporator (‘‘unit cooler’’). DOE’s
regulations at 10 CFR 431.304, Uniform
test method for the measurement of
energy consumption of walk-in coolers
and walk-in freezers, incorporate by
reference AHRI Standard 1250–2009,
‘‘2009 Standard for Performance Rating
of Walk-in Coolers and Freezers’’ (AHRI
1250–2009) as the testing method for
walk-in refrigeration systems. 10 CFR
431.304(b)(9). AHRI 1250–2009
establishes methods to follow when
testing a complete refrigeration system
(the ‘‘matched system’’ test), as well as
separate methods to use for testing the
unit cooler and condensing unit of a
refrigeration system individually and
then calculating a combined system
rating (the ‘‘mix-match’’ test). AHRI
1250–2009 also contains standard rating
E:\FR\FM\13MYR2.SGM
13MYR2
tkelley on DSK3SPTVN1PROD with RULES2
27390
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
conditions for: Cooler and freezer
systems; systems where the condenser is
located either indoors or outdoors; and
systems with single-speed, two-speed,
or variable-speed compressors. AHRI
1250–2009 also establishes a method for
testing and rating unit coolers that are
connected to a multiplex condensing
system such as those typically found in
a supermarket. The rating produced by
the AHRI 1250–2009 test procedure is
an annual walk-in energy factor
(AWEF), defined as ‘‘a ratio of the total
heat, not including the heat generated
by the operation of refrigeration
systems, removed, in Btu [British
thermal units], from a walk-in box
during one year period of usage for
refrigeration to the total energy input of
refrigeration systems, in watt-hours,
during the same period.’’ AHRI 1250–
2009, at sec. 3.1.
DOE recently proposed energy
conservation standards for walk-ins. See
78 FR 55781 (Sept. 11, 2013) (September
2013 standards NOPR). In that notice,
DOE proposed standards for complete
walk-in refrigeration systems that would
require the ratings for the refrigeration
system to be derived using either the
matched system or mix-match tests
described above. DOE also proposed
standards for unit coolers connected to
a multiplex system, based on the unit
cooler rating method described above.
Responding to the NOPR, several
interested parties discussed the concept
of establishing separate standards for
the unit cooler and condensing unit of
a walk-in as a means to address the
fundamental problem of how one
manufacturer (e.g., unit cooler
manufacturer) would be able to rate its
equipment in the absence of knowing
which equipment (e.g., condensing unit)
would be matched with its own
equipment. Performance characteristics
of both the unit cooler and condensing
unit are needed in order to rate the
refrigeration system’s performance
under the methodology in AHRI 1250–
2009.
In light of that discussion and the fact
that unit coolers and condensing units
are often sold separately or produced by
different manufacturers, DOE proposed
in the February 2014 SNOPR to adopt a
methodology that would account for the
issue noted above by relying on
elements of AHRI 1250–2009, which
includes a method to test both
components separately (i.e., the mixmatch test method). The proposed
method would require the manufacturer
of either the unit cooler or condensing
unit, if sold separately, to test and
certify compliance of a nominal
refrigeration system with DOE’s
standards and make representations of a
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
WICF refrigeration system. Under the
proposal, manufacturers of a complete
WICF refrigeration system could
continue to develop a system rating for
the purposes of certifying compliance
with DOE’s standards and making
energy efficiency representations of the
WICF refrigeration system. Furthermore,
as DOE noted in the February 2014
SNOPR, in reviewing AHRI 1250–2009
and conducting limited testing on a
WICF refrigeration system at a thirdparty laboratory to investigate the
AEDM validation approach, DOE had
discovered several issues in the
refrigeration test procedures that
required clarification and/or created
unnecessary test burden. 79 FR at 9820.
To simplify the procedure and to clarify
certain aspects, DOE proposed alternate
language to certain requirements
contained in AHRI 1250–2009 that
DOE’s test procedure currently
incorporates by reference.
3. Sampling Plan
In order to determine a rating for
certifying compliance or making energy
use representations, DOE requires
manufacturers to test each basic model
in accordance with the applicable DOE
test procedure and apply the
appropriate sampling plan. As part of
the February 2014 SNOPR, DOE
proposed a sampling plan for walk-ins
consistent with other commercial
equipment regulated under EPCA.
4. Test Procedures and Prescriptive
Requirements for WICF Foam Panel RValue
EPCA mandates prescriptive
requirements for the thermal resistance
of walk-in panels: Wall, ceiling, and
doors must have an insulation value of
at least R–25 for coolers and R–32 for
freezers. (42 U.S.C. 6313(f)(1)(C)) EPCA
also requires the use of ASTM C518–04,
Standard Test Method for Thermal
Steady-State Thermal Transmission
Properties by Means of the Heat Flow
Meter Apparatus (‘‘ASTM C518–04’’) to
measure the insulation thermal
resistance of a panel. (42 U.S.C.
6314(a)(9)(A)) The walk-in test
procedure at 10 CFR 431.304
incorporates ASTM C518–04 by
reference. This reference standard is the
method by which thermal conductivity
(the ‘‘K factor’’) of a walk-in panel is
measured; the R-Value of the panel is
then determined by multiplying 1/K
(the reciprocal of K) by the thickness of
the panel. The R-Value of a freezer
panel is determined at a mean
insulation foam temperature of 20
degrees Fahrenheit and the R-Value of a
cooler panel is determined at a mean
insulation foam temperature of 55
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
degrees Fahrenheit. (42 U.S.C.
6314(a)(9)(A)(iii) and (iv)) The
regulations also currently require
manufacturers to use the procedure
detailed in 10 CFR 431.304(b) when
certifying compliance with the panel
energy conservation standards until
January 1, 2015. Manufacturers must
use the procedure in 10 CFR 431.304(c)
when making representations of energy
efficiency currently and when certifying
compliance starting on January 1, 2015.
In the February 2014 SNOPR, DOE
proposed modifications to the test
sample preparation procedures
incorporated from ASTM C518–04 in
both procedures to improve
measurement accuracy.
5. Performance-Based Test Procedures
for Energy Consumption of Envelope
Components
In 10 CFR Part 431, Subpart R,
Appendix A, DOE lays out a method for
measuring performance-based efficiency
metrics for certain WICF envelope
components. This method draws from
several existing industry test methods
by incorporating by reference ASTM
C1363–05 Standard Test Method for
Thermal Performance of Building
Materials and Envelope Assemblies by
Means of a Hot Box Apparatus and
Annex C Determination of the aged
values of thermal resistance and
thermal conductivity from both DIN EN
13164 and DIN EN 13165 (two European
Union-developed testing protocols) for
measuring the energy consumption of
WICF floor and non-floor panels.
Appendix A also incorporates NFRC
100–2010[E0A1] Procedure for
Determining Fenestration Product Ufactors for determining the energy use of
walk-in display and non-display doors.
In the February 2014 SNOPR, DOE
proposed modifying (1) the test
procedures for WICF floor and non-floor
panels to address comments received
from stakeholders during the standards
rulemaking and (2) the WICF display
and non-display door test procedure to
improve the clarity of the test method.
II. Summary of the Final Rule
Today’s final rule comprises six key
elements.
First, the Department will allow WICF
refrigeration manufacturers to use
AEDMs to rate and certify their basic
models by using the projected energy
efficiency derived from these simulation
models in lieu of testing. DOE is
aligning the validation requirements
proposed for WICF refrigeration AEDMs
with those that have already been
adopted for commercial HVAC,
refrigeration, and WH equipment. DOE
is adopting this approach because the
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
cooling and refrigeration systems used
by these equipment types operate under
similar principles as the refrigeration
systems used in walk-ins. This
similarity, along with the practical
considerations discussed elsewhere in
this rule, lend support for applying
similar or identical validation
requirements for walk-ins as well.
Second, today’s final rule adopts an
alternative method for testing and rating
the WICF refrigeration system for unit
coolers and condensing units that are
sold alone. Specifically, unit cooler
manufacturers who distribute a unit
cooler as a separate component must
rate that cooler as though it were to be
connected to a multiplex system and
must comply with any applicable
standard DOE may establish for a unit
cooler connected to a multiplex system.
Similarly, manufacturers who distribute
a condensing unit as a separate
component must use the nominal values
for unit coolers, in lieu of actual unit
cooler test data, when calculating AWEF
using the mix-match rating method in
AHRI 1250. Consistent with this
methodology and pending the outcome
of the standards rulemaking, DOE
would consider modifications to the
certification requirements based on the
following approach:
(1) a manufacturer that only produces
unit coolers would use the test method
(‘‘Walk-in Unit Cooler Match to Parallel
Rack System’’ in AHRI 1250, section
7.9) to establish a WICF refrigeration
system rating for each basic model, and
the unit cooler manufacturer would
certify the compliance of each unit
cooler model as a component of a WICF
refrigeration system basic model;
(2) a manufacturer that only produces
condensing units would test each
condensing unit and combine it with
the unit cooler nominal values adopted
in today’s final rule to establish a WICF
refrigeration system rating for each basic
model, and the condensing unit
manufacturer would certify the
compliance of each condensing unit
model as a component of a WICF
refrigeration system basic model; or
(3) a manufacturer that produces both
unit cooler basic models and
condensing unit basic models that are
marketed and sold as a matched system
would use the test method in AHRI
1250–2009 to test the unit cooler and
the condensing unit as a matched
system to obtain a WICF refrigeration
system rating for each matched system
it produces and then certify compliance,
except where both components have
been previously rated and certified
separately. In this case, the
manufacturer need not test and certify
the matched system unless the
manufacturer wishes to represent the
matched system efficiency as being
higher than the efficiency of either
component.
Third, DOE is adopting the following
modifications to the test procedure for
WICF refrigeration components:
—Clarifying the defrost test procedure;
—Offering an alternative method for
calculating the defrost energy and
heat load of a system with electric
defrost in lieu of a frosted coil test;
—Adding a method for calculating
defrost energy and heat load of a
system with hot gas defrost;
—Changing the minimum fan speed and
duty cycle during the off-cycle
evaporator fan test;
—Removing the refrigerant oil and
refrigerant composition analysis
testing requirements;
—Clarifying and modifying the
temperature measurement
requirements to reduce testing burden
while ensuring accuracy;
—Adding a test condition tolerance for
electrical power frequency and
removing the test condition tolerance
for air temperature leaving the unit;
—Quantifying the requirements for
insulating refrigerant lines;
—Clarifying piping length requirement;
—Bringing consistency between the list
of tests for unit coolers in Tables 15
and 16 of AHRI 1250–2009, and
another similar test method; and
—Clarifying the voltage imbalance for
three-phase power.
Fourth, DOE is modifying the current
test procedure for measuring the
insulation R-Value of WICF panels. (10
CFR 431.304) The current DOE test
procedure allows, but does not require,
panels to be tested with non-foam facers
or protective skins attached. (10 CFR
431.304(b)(5)–(6) and (c)(5)–(6)) Also,
the current DOE test procedure allows
panel test samples to be up to 4 inches
in thickness. (10 CFR 431.304(b)(5) and
(c)(5)) The test procedure requires that
the R-Value be measured at a mean
temperature of 20 degrees Fahrenheit for
freezer panels (10 CFR 431.304(b)(3) and
27391
(c)(3)) and 55 degrees Fahrenheit for
cooler panels (10 CFR 431.304(b)(4) and
(c)(4)); however, no tolerance is
currently specified for these
temperatures. With this final rule, DOE
will require test samples to be 1-inch in
thickness and without non-foam facers,
protective skins, internal non-foam
members or edge regions. DOE is also
adding flatness and parallelism
constraints on the test sample surfaces
that contact the hot and cold plates in
the heat flow meter apparatus. DOE is
also adding a tolerance of ±1 degree
Fahrenheit for the mean temperature
during panel R-Value testing. DOE
believes this clarification will help
ensure that the panel testing is
conducted in a repeatable and
reproducible manner at different
laboratories.
Fifth, to enable walk-in manufacturers
to make energy use representations,
DOE is implementing a sampling plan
for walk-ins consistent with other
commercial equipment regulated under
EPCA.
Finally, in response to manufacturer
comments on the September 2013
standards NOPR, DOE is removing the
existing performance-based test
procedures for WICF floor and non-floor
panels (10 CFR Part 431, Subpart R,
Appendix A, sections 4.2, 4.3, 5.1, and
5.2). DOE recognizes that these
performance-based procedures for WICF
floor and non-floor panels are in
addition to the prescriptive
requirements already established in
EPCA for panel insulation R-Values and,
therefore, may increase the test burden
to manufacturers. This recognition of
the overall burdens faced by
manufacturers is based in part on the
difficulty manufacturers have reportedly
had in locating any testing laboratories
capable of performing the applicable
tests since DOE’s issuance of the test
procedure in April 2011. See 76 FR
21580. Based on market research, DOE
agrees with manufacturers that there are
a limited number of laboratories capable
of conducting the performance-based
procedures for WICF floor and non-floor
panels.
All of the changes noted above, along
with the appropriate sections of the CFR
where these changes appear, are
detailed in the summary table below.
TABLE II.1—SUMMARY OF CFR CHANGES
Change
10 CFR section
Allowing manufacturers to use AEDMs to rate WICF refrigeration systems ......................................
Specific instructions for applying AEDMs to WICF refrigeration systems ..........................................
Changes to test procedures and prescriptive requirements for WICF foam panel R-Value ..............
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
429.53.
429.70(f).
431.304(b)(3)–(6) and 431.304(c)(3)–(6).
E:\FR\FM\13MYR2.SGM
13MYR2
27392
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
TABLE II.1—SUMMARY OF CFR CHANGES—Continued
Change
10 CFR section
Amendments to AHRI 1250–2009 refrigeration system test method, and the panel and door test
methods.
Methods for rating refrigeration components sold separately .............................................................
Amendments to performance-based test procedures for energy consumption of envelope components.
III. Discussion
In response to the February 2014
SNOPR, DOE received written
comments from 9 interested parties,
including manufacturers, trade
associations and energy efficiency
advocacy groups. Table III.1 lists the
entities that commented on that SNOPR
and their affiliation. (DOE also reopened the comment period to allow for
additional comments.) These comments
are discussed in more detail below, and
431.304(c)(8).
431.304(c)(11).
431 Subpart R, Appendix A.
the full set of comments, including the
public meeting transcript, can be found
at: https://www.regulations.gov/#!docket
Detail;dct=FR%252BPR%252BN%252B
O%252BSR%252BPS;rpp=25;po=0;D=
EERE-2011-BT-TP-0024.
TABLE III.1—INTERESTED PARTIES THAT COMMENTED ON THE FEBRUARY 2014 SNOPR
Comment No.
(Docket reference)
Commenter
Acronym
Organization type/affiliation
Air-Conditioning, Heating, and Refrigeration Institute.
American Council for an Energy-Efficient
Economy.
Appliance Standards Awareness Project,
Earthjustice, Natural Resources Defense Council, Alliance to Save Energy, American Council for an Energy
Efficient Economy, Northwest Energy
Efficiency Alliance, and Northwest
Power and Conservation Council.
Bally Refrigerated Boxes, Inc ..................
California Investor-Owned Utilities: Pacific Gas and Electric Company,
Southern California Edison, and San
Diego Gas & Electric.
Heat Transfer Products Group, LLC .......
Lennox International, Inc .........................
National Coil Company ............................
National Refrigeration & Air Conditioning
Canada Corp. (dba KeepRite).
AHRI ........................................................
Industry Trade Group ..............................
100
ACEEE ....................................................
Advocacy Group ......................................
98
ASAP, EJ, NRDC, ASE, ACEEE, NEEA,
NPCC (ASAP, et al.).
Advocacy Group ......................................
99
Bally .........................................................
PG&E, SCE, and SDG&E (CA IOUs) .....
Manufacturer ...........................................
Utility Association ....................................
93
101
HTPG .......................................................
Lennox .....................................................
NCC .........................................................
KeepRite ..................................................
Manufacturer
Manufacturer
Manufacturer
Manufacturer
In response to the initial May 2012
NOPR, DOE received written comments
from 28 interested parties, including
manufacturers, trade associations and
advocacy groups. Seven additional
interested parties commented during the
May 2012 NOPR Public Meeting on June
5, 2012. For reference, Table III.2 lists
the entities that commented on the
NOPR and their affiliation. These
comments were discussed in the
February 2014 SNOPR. The full set of
...........................................
...........................................
...........................................
...........................................
96
97
95
94
comments, including the public meeting
transcript, can be found at: https://
www.regulations.gov/#!docketDetail;dct
=FR%252BPR%252BN%252BO%252
BSR%252BPS;rpp=25;po=0;D=EERE2011-BT-TP-0024.
TABLE III.2—INTERESTED PARTIES THAT COMMENTED ON THE MAY 2012 NOPR
tkelley on DSK3SPTVN1PROD with RULES2
Name
Acronym
AAON, Inc ......................................................................................................................
The ABB Group .............................................................................................................
Air-Conditioning, Heating, and Refrigeration Institute ...................................................
Appliance Standards Awareness Project & American Council for an Energy-Efficient
Economy.
Baldor Electric ................................................................................................................
Bradford White Corporation ...........................................................................................
Burnham Commercial ....................................................................................................
Cooper Power Systems .................................................................................................
Crown Boiler Company ..................................................................................................
CrownTonka/ThermalRite/International Cold Storage ...................................................
Danfoss ..........................................................................................................................
First Co. .........................................................................................................................
Goodman Global, Inc .....................................................................................................
Heatcraft Refrigeration Products LLC ...........................................................................
AAON .................................
ABB ....................................
AHRI ...................................
Joint Comment ...................
Manufacturer.
Manufacturer.
Industry Trade Group.
Advocacy Group.
Baldor Electric ....................
Bradford White ...................
Burnham .............................
Cooper ................................
Crown Boiler .......................
CT/TR/ICS ..........................
Danfoss ..............................
First Co. ..............................
Goodman ............................
Heatcraft Refrigeration .......
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
VerDate Mar<15>2010
19:17 May 12, 2014
Jkt 232001
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
E:\FR\FM\13MYR2.SGM
Organization type/affiliation
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
27393
TABLE III.2—INTERESTED PARTIES THAT COMMENTED ON THE MAY 2012 NOPR—Continued
Name
Acronym
Hillphoenix, Inc ..............................................................................................................
Hussmann Corporation ..................................................................................................
Ingersoll Rand ................................................................................................................
Johnson Controls, Inc ....................................................................................................
Lennox International, Inc ...............................................................................................
Lochinvar, LLC ...............................................................................................................
Mitsubishi Electric ..........................................................................................................
Modine Manufacturing Company ...................................................................................
Mortex Products, Inc ......................................................................................................
National Electrical Manufacturers Association ..............................................................
Nidec Motor Corporation ...............................................................................................
Nordyne, LLC .................................................................................................................
Rheem Manufacturing Company ...................................................................................
Schneider Electric ..........................................................................................................
Southern Store Fixtures, Inc ..........................................................................................
Trane ..............................................................................................................................
True Manufacturing Co. Inc ...........................................................................................
Unico, Inc .......................................................................................................................
United Cool Air ..............................................................................................................
United Technologies Climate, Controls & Security and ITS Carrier .............................
Zero Zone, Inc ...............................................................................................................
Hillphoenix ..........................
Hussmann ..........................
Ingersoll Rand ....................
JCI ......................................
Lennox ................................
Lochinvar ............................
Mitsubishi Electric ...............
Modine ................................
Mortex ................................
NEMA .................................
Nidec ..................................
Nordyne ..............................
Rheem ................................
SE .......................................
Southern Store Fixtures .....
Trane ..................................
True Manufacturing ............
Unico ..................................
United Cool Air ...................
UTC/Carrier ........................
Zero Zone ...........................
In response to the SNOPR on AEDMs
for commercial HVAC, refrigeration and
WH equipment, which was published in
the Federal Register on October 22,
2013, 78 FR 62472, DOE received a
comment relevant to this rulemaking
from Lennox International, Inc., a
manufacturer of HVAC and commercial
refrigeration equipment. This comment
was addressed in the February 2014
SNOPR. See 79 FR at 9824.
The Department also received
relevant comments from 23 interested
parties in response to the September
2013 Standards NOPR and related
NOPR Public Meeting held on October
9, 2013. For reference, Table III.3 lists
the entities that commented on that
Organization type/affiliation
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Industry Trade Group.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer
NOPR and their affiliation. These
comments were also discussed in the
February 2014 SNOPR. See generally 79
FR at 9822–9837. The full set of
comments, including the public meeting
transcript, can be found at: https://
www.regulations.gov/
#!docketDetail;D=EERE-2008-BT-STD0015.
TABLE III.3—INTERESTED PARTIES THAT COMMENTED ON THE SEPTEMBER 2013 STANDARDS NOPR
Acronym
Air Conditioning Contractors of America .......................................................................
Air-Conditioning, Heating, and Refrigeration Institute ...................................................
American Council for an Energy Efficient Economy .....................................................
American Panel Corp ....................................................................................................
Appliance Standards Awareness Project ......................................................................
Architectural Testing Inc ................................................................................................
Bally Refrigerated Boxes, Inc ........................................................................................
CrownTonka Walk-Ins, ThermalRite & International Cold Storage ...............................
Danfoss Group North America ......................................................................................
Heatcraft Refrigeration Products LLC ...........................................................................
Hillphoenix .....................................................................................................................
HussmanCorporation .....................................................................................................
Imperial Brown ...............................................................................................................
KysorWarren ..................................................................................................................
Lennox International Inc ................................................................................................
Louisville Cooler Mfg .....................................................................................................
Manitowoc ......................................................................................................................
National Coil Company ..................................................................................................
Nor-Lake, Inc .................................................................................................................
Northwest Energy Efficiency Alliance & The Northwest Power and Conservation
Council.
Pacific Gas & Electric, Southern California Gas, Southern California Edison, San
Diego Gas & Electric (Ca. State Independently Owned Utilities).
Thermo-Kool ..................................................................................................................
US Cooler Co ................................................................................................................
tkelley on DSK3SPTVN1PROD with RULES2
Name
ACCA .................................
AHRI ...................................
ACEEE ...............................
American Panel ..................
ASAP ..................................
AT .......................................
Bally ....................................
CT/TR/ICS ..........................
Danfoss ..............................
Heatcraft .............................
Hillphoenix ..........................
HussmanCorp ....................
IB ........................................
Kysor ..................................
Lennox ................................
Louisville Cooler .................
Manitowoc ..........................
NCC ....................................
Nor-Lake .............................
NEEA, et al. .......................
Industry Trade Group.
Industry Trade Group.
Advocacy Group.
Manufacturer.
Advocacy Group.
Third Party Laboratory.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Manufacturer.
Advocacy Group.
CA IOU’s ............................
Utility.
Thermo-Kool .......................
US Cooler ...........................
Manufacturer.
Manufacturer.
A. Alternative Efficiency Determination
Method
the use of AEDMs for WICFs and to
establish specific requirements for
18:30 May 12, 2014
Jkt 232001
PO 00000
manufacturer validation 1—i.e., a
1 In the May 2012 NOPR, DOE used the term
‘‘substantiation’’ to refer to the process
In the May 2012 NOPR, DOE
proposed, among other things, to allow
VerDate Mar<15>2010
Organization type/affiliation
Continued
Frm 00007
Fmt 4701
Sfmt 4700
E:\FR\FM\13MYR2.SGM
13MYR2
27394
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
process in which manufacturers
demonstrate the accuracy of an AEDM
model—and DOE verification 2—i.e., a
process followed by DOE when
verifying the accuracy of an AEDM
model—that would apply to this
equipment.
As discussed above, ASRAC formed a
working group in April 2013 to discuss
and negotiate a variety of issues related
to the certification provisions for
commercial heating, ventilation, and air
conditioner (HVAC), refrigeration, and
water heater (WH) equipment. Those
discussions were expanded to include
AEDMs, along with related validation
and verification requirements. These
negotiations eventually led to the
October 2013 SNOPR and the December
2013 final rule that established a series
of requirements related to basic model
definitions and compliance provisions
for commercial HVAC, WH, and
refrigeration equipment. See 78 FR
62472 (SNOPR) and 78 FR 79579 (final
rule). In the February 2014 SNOPR, DOE
proposed to require that the AEDM
validation regulations that apply to
commercial HVAC, refrigeration, and
WH equipment would also apply to
AEDMs designed to simulate testing of
WICF refrigeration systems as a whole
and WICF refrigeration components–
i.e., unit coolers and condenser units.
DOE is retaining this approach in this
final rule and addresses comments on
the SNOPR below.
Generally, AHRI commented that
while it supports AEDMs for walk-ins,
the AEDM provisions for commercial
HVAC, WH, and refrigeration
equipment may not be applicable to
walk-in coolers. AHRI explained that
the Working Group was afforded the
opportunity to amend basic model
definitions and verification procedures
for commercial HVAC, WH, and
refrigeration equipment over the course
of several months of meetings. AHRI
asserted that while most of the AEDM
recommendations could be applied to
walk-ins, this type of equipment is very
unique. To better address this subject,
AHRI requested additional time to
manufacturers used to demonstrate that their
modeling tool, or AEDM, produced accurate results.
See 77 FR at 32040. The Working Group elected to
use the term ‘‘validation,’’ instead of
‘‘substantiation,’’ for this process. DOE clarifies that
‘‘substantiation’’ and ‘‘validation’’ are synonymous
in this context and the Department will use the
term ‘‘validation’’ henceforth.
2 In the May 2012 NOPR, DOE used the term
‘‘DOE validation’’ to refer to the process DOE used
to check that the modeling tool, or AEDM,
produced accurate results. See 77 FR at 32046. The
Working Group elected to use the ‘‘verification,’’,
instead of ‘‘DOE validation,’’, for this process. DOE
clarifies that ‘‘DOE validation’’ and ‘‘verification’’
are synonymous and the Department will use the
term ‘‘verification’’ henceforth.
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
review basic model definitions for
WICFs with respect to AEDMs. (AHRI,
No. 100 at p. 2) DOE provided an
additional comment period. See 79 FR
19844 (April 10, 2014).
In DOE’s view, walk-in refrigeration
equipment is sufficiently similar to
commercial HVAC, WH, and
refrigeration equipment to permit the
AEDM regulatory framework for AEDMs
established by the Working Group to be
effectively applied to walk-in
refrigeration systems. These systems are
similar in operation and design to those
refrigeration systems used in both
commercial HVAC and refrigeration
equipment systems and are commonly
found in both walk-in and commercial
refrigeration equipment applications.
Additionally, similar to commercial
refrigeration equipment, walk-in
refrigeration systems have a high degree
of customization. Permitting the AEDM
regulatory framework to be applied to
walk-ins, would also likely significantly
reduce manufacturer testing burden for
this equipment while maintaining a
reasonable level of accuracy with
respect to energy efficiency.
1. Applicable Equipment
In the February 2014 SNOPR, DOE
proposed to allow WICF refrigeration
system manufacturers to use AEDMs
when rating the performance of this
equipment. DOE did not propose to
extend this allowance to WICF panel or
door manufacturers. WICF panels are
relatively simple pieces of equipment
and the test results from a basic model
of a given panel can be extrapolated to
many other panel basic models under
the provisions of the test procedure. As
for WICF doors, the DOE test procedure
already specifies the use of certain
modeling techniques that are approved
by the National Fenestration Rating
Council (NFRC), which, in DOE’s view,
makes a parallel AEDM provision for
these components unnecessary. 77 FR at
32041. Instead, the Department
proposed other modifications in the
February 2014 SNOPR to the walk-in
panel test procedure to reduce the
burden faced by panel manufacturers
while ensuring the overall accuracy of
the efficiency ratings. The modifications
to the WICF panel test procedure are
outlined in section III.C. DOE did not
receive any comments regarding its
proposal to extend AEDMs to walk-in
refrigeration equipment and therefore is
adopting this proposal in today’s final
rule.
DOE is allowing WICF refrigeration
manufacturers to apply an AEDM to a
basic model to determine its efficiency,
provided that the AEDM meets certain
requirements. The AEDM must be
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
derived from a mathematical model that
estimates the energy efficiency or
consumption characteristics of the basic
model as measured by the applicable
DOE test procedure. The AEDM must be
based on engineering or statistical
analysis, computer simulation,
modeling, or other type of analytical
evaluation of performance data. Finally,
the AEDM must be validated according
to DOE requirements, which are
discussed in section III.A.2 of this rule.
2. Validation
a. Number of Tested Units Required for
Validation
In the February 2014 SNOPR, DOE
proposed to apply the Working Group’s
recommendation for AEDM validation
requirements to WICFs. That
recommendation, which DOE adopted
and is applying to those AEDMs used
for commercial HVAC, refrigeration, and
WH equipment, requires a manufacturer
to select a minimum number of models
from each validation class to which the
AEDM will apply. (Validation classes
are groupings of products based on
equipment classes but used for AEDM
validation.) DOE proposed to apply this
same approach to WICF refrigeration
systems using the validation classes
listed in Table III.4. A unit of each basic
model selected would undergo a single
test conducted in accordance with the
DOE test procedure (or, if applicable, a
test procedure waiver issued by DOE) at
a manufacturer’s testing facility or a
third-party testing facility. The test
result should be directly compared to
the result from the AEDM to determine
the AEDM’s validity. A manufacturer
may develop multiple AEDMs per
validation class and each AEDM may
span multiple validation classes;
however, the minimum number of tests
must be maintained per validation class
for every AEDM a manufacturer chooses
to develop. An AEDM may be applied
to any model within the applicable
validation classes at the manufacturer’s
discretion. All documentation of test
results for these models, the AEDM
results, and subsequent comparisons to
the AEDM would be maintained as part
of both the test data underlying the
certified rating and the AEDM
validation package pursuant to 10 CFR
429.71. Specifically, manufacturers
must maintain the AEDM, including the
mathematical model, statistical analysis
or other computer simulations that form
the basis of the AEDM. Additionally,
DOE requires manufacturers to maintain
equipment information, complete test
data, and AEDM calculations for each of
the units that were used to validate the
AEDM. Finally, manufacturers must
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
maintain equipment information and
27395
calculations for each basic model to
which the AEDM was applied.
TABLE III.4—VALIDATION CLASSES PROPOSED IN THE SNOPR
Minimum number of distinct
models that must be tested
Validation class
tkelley on DSK3SPTVN1PROD with RULES2
Dedicated Condensing, Medium Temperature, Indoor System ....................................................................................
Dedicated Condensing, Medium Temperature, Outdoor System .................................................................................
Dedicated Condensing, Low Temperature, Indoor System ..........................................................................................
Dedicated Condensing, Low Temperature, Outdoor System .......................................................................................
Unit Cooler connected to a Multiplex Condensing Unit, Medium Temperature ............................................................
Unit Cooler connected to a Multiplex Condensing Unit, Low Temperature ..................................................................
Medium Temperature, Indoor Condensing Unit ............................................................................................................
Medium Temperature, Outdoor Condensing Unit .........................................................................................................
Low Temperature, Indoor Condensing Unit ..................................................................................................................
Low Temperature, Outdoor Condensing Unit ...............................................................................................................
ACEEE, Bally, KeepRite, NCC, HTPG,
AHRI, and Lennox agreed with DOE’s
proposal to adopt the Working Group’s
AEDM validation requirements for
WICF AEDMs. (ACEEE, No. 98 at p. 1;
Bally, No. 93 at p. 1; KeepRite, No. 94
at p. 1; NCC, No. 95 at p. 1; HTPG, No.
96 at p. 2; AHRI, No. 100 at p. 2;
Lennox, No. 97 at p. 3)
Interested parties also made
additional recommendations regarding
the validation classes. ACEEE suggested
explicitly reserving to the Secretary the
authority to enlarge the validation
sample size if needed. (ACEEE, No. 98
at p. 1) DOE notes that while it is opting
not to adopt ACEEE’s suggestion, it may
revisit and re-evaluate this issue and
adjust the sample size as necessary.
Lennox commented that an AEDM
that has been validated for outdoor
condensing systems should be
considered validated for indoor
condensing units because these
validation classes are very similar
except that outdoor condensing units
are exposed to a wider range of
temperatures. (Lennox, No. 97 at p. 3)
DOE agrees with Lennox. The test
method in AHRI 1250–2009 for outdoor
and indoor condensing units is identical
except for the ambient rating conditions.
Outdoor condensing units are tested at
three ambient temperatures, 35 °F, 59
°F, and 95 °F. The ambient rating
temperature for indoor units is 90 °F.
DOE believes that this condition is
sufficiently similar to the 95 °F outdoor
rating condition such that an AEDM
validated by testing of an outdoor
condensing unit would provide accurate
results for indoor condensing units. For
this reason, DOE is allowing AEDMs
validated for outdoor condensing units
to be extended to indoor condensing
units. However, DOE is not allowing
AEDMs validated with test results from
indoor condensing units only to extend
to outdoor condensing units. DOE is
making this distinction because of
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
concerns that the other two rating
conditions for outdoor units—35 °F and
59 °F—could not be adequately verified
by testing at a single 90 °F rating
condition. Should DOE receive
additional data suggesting that such an
approach would be adequate, it may
consider revisiting this issue in a future
rulemaking effort.
The CA IOUs commented that the
current validation classes do not
account for variation in capacities,
compressor type, refrigerant, fan type,
airflow volume, and heat exchanger coil
materials and configurations. The CA
IOUs expressed concern that AEDMs
that cover all models in a validation
class will be inaccurate and
recommended DOE develop guidelines
for what a single AEDM can cover. (CA
IOUs, No. 101 at pp. 2–3) DOE has
decided to retain in the final rule the
validation classes proposed in the
SNOPR. These validation classes were
developed to minimize the test burden
on manufacturers, and these classes do
not preclude a manufacturer from
conducting additional testing to verify
its AEDM. Similar concerns were raised
during the Commercial Certification
Working Group meetings, and the
parties agreed that the requirements for
validation should be kept to the lowest
possible test burden. The Working
Group agreed that, because
manufacturers are ultimately
responsible for ensuring the compliance
of their products, manufacturers will
ensure that they have sufficient test data
to validate their own AEDMs as
appropriate for the variety of designs to
which they are applying their AEDM.
Additionally, DOE may request test data
used to validate an AEDM from a
manufacturer or conduct verification
testing to ensure models are rated
correctly. See generally, 10 CFR 429.71
(maintenance of records).
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
2
2
2
2
2
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
b. Tolerances for Validation
In the February 2014 SNOPR, DOE
proposed to apply the Working Group’s
recommendation for validation
tolerances to WICF AEDMs. For energy
efficiency metrics, the AEDM results for
a model must be less than or equal to
105 percent of the tested results for that
same model. Additionally, the AEDM’s
predicted efficiency for each model
must meet or exceed applicable federal
energy conservation standards. DOE
adopted these same tolerances for
commercial HVAC, WH, and
refrigeration equipment. See 78 FR
79579 (Dec. 31, 2013).
ACEEE, NCC, HTPG, AHRI, and
Lennox supported the Department’s
proposal to align the validation
tolerances for WICF AEDMs to the
Working Group’s recommended
validation tolerances. (ACEEE, No. 98 at
p. 1, NCC, No. 95 at p. 2; HTPG, No. 96
at p. 2; AHRI, No. 100 at p. 3; Lennox,
No. 97 at p. 3) ACEEE, HTPG, and
Lennox also supported DOE’s proposal
to utilize only one-sided tolerances that
would allow manufacturers to rate
equipment conservatively. (ACEEE No.
98 at p. 1, HTPG, No. 96 at p. 2; Lennox,
No. 97 at p. 3)
Bally and KeepRite commented that
DOE’s proposed tolerances were too
tight. Bally suggested a two-sided
validation tolerance of 8 percent be
adopted to be consistent with other
commercial equipment. KeepRite made
a similar suggestion. (Bally, No. 93 at p.
1; KeepRite, No. 94 at p. 1) In DOE’s
view, a 5 percent one-sided tolerance is
more consistent with the AEDM
validation tolerances for other types of
commercial equipment than the 8
percent two-sided tolerance suggested
by Bally and KeepRite. See 78 FR 79579
(Dec. 31, 2013) (applying a 5 percent,
one-sided tolerance for all commercial
HVAC, WH, and refrigeration
equipment). DOE agrees with ACCEE,
E:\FR\FM\13MYR2.SGM
13MYR2
27396
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
HTPG, and Lennox that a one-sided
tolerance is preferable because it allows
manufacturers to rate equipment
conservatively and account for
manufacturing and testing variability.
3. Certified Rating
DOE’s current regulations provide
manufacturers with some flexibility in
rating each basic model by allowing the
manufacturer the discretion to rate
conservatively relative to tested values.
The Working Group recommended that,
when rating using an AEDM,
manufacturers have the same flexibility.
Accordingly, the Working Group
recommended that, for energy
consumption metrics, each model’s
certified rating must be less than or
equal to the applicable Federal standard
and greater than or equal to the model’s
AEDM result. For energy efficiency
metrics, each model’s certified rating
must be less than or equal to the
model’s AEDM result and greater than
or equal to the applicable Federal
standard. In the February 2014 SNOPR,
DOE proposed to adopt these
requirements for WICF refrigeration
equipment rated an AEDM. The
Department did not receive any
comments on its proposal regarding
certified ratings and is adopting it in
today’s final rule.
tkelley on DSK3SPTVN1PROD with RULES2
4. Verification
DOE may randomly select and test a
single unit of a basic model pursuant to
10 CFR 429.104, which extends to all
DOE covered products, including those
certified using an AEDM. As part of the
AEDM requirements for commercial
HVAC, WH, and refrigeration
equipment, at DOE’s request,
manufacturers must perform
simulations in the presence of a DOE
representative, provide analyses of
previous simulations conducted by the
manufacturer, or conduct certification
tests of basic models selected by the
Department. See 10 CFR 429.74(c)(4). To
maintain consistency, the Department is
extending these requirements to WICF
AEDMs.
a. Failure To Meet a Certified Rating
In the February 2014 SNOPR, DOE
proposed to assess a unit’s performance
through third-party testing. Under this
approach, DOE would begin the
verification process by selecting a single
unit of a given basic model for testing
either from retail or by obtaining a
sample from the manufacturer if none
are available from retail sources. DOE
would then select a third-party testing
laboratory at its discretion to test the
unit selected unless no third-party
laboratory is capable of testing the
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
equipment, in which case DOE may
request testing at a manufacturer’s
facility. The Department would be
responsible for the logistics of arranging
the testing, and the laboratory would
not be allowed to communicate directly
with the manufacturer. Additionally,
the test facility may not discuss DOE
verification testing with the
manufacturer without the Department
present. See 79 FR at 9643–9644.
Further, under DOE’s proposal, if a
unit is tested and the results are
determined to be outside the rating
tolerances described in section
III.A.2.b., DOE would notify the
manufacturer. This approach would also
enable the manufacturer to receive all
documentation related to the test set up,
test conditions, and test results for the
unit if the unit falls outside the rating
tolerances. At that time, a manufacturer
would also be able to present all claims
regarding any issues directly with the
Department. See id. at 9644. If, after
discussions with the manufacturer, DOE
determined that the testing was
conducted appropriately in accordance
with the applicable DOE test procedure,
the rating for the model would be
considered invalid. The Department
notes that 10 CFR 429.13(b) applies to
equipment certified using an AEDM,
and DOE may require a manufacturer to
conduct additional testing if the
manufacturer violates an applicable
standard or certification requirement.
HTPG commented that DOE should
allow the option for a second sample to
be tested to ensure that abnormal
failures unrelated to design or
predictable variations do not adversely
impact an otherwise sound model type.
(HTPG, No. 96 at pp. 2–3) As stated
above, if a unit is determined to be
outside the prescribed rating tolerances,
the Department would provide the
manufacturer with all documentation
related to the test set up, test conditions,
and test results. At that time, the
manufacturer may initiate a discussion
with the Department regarding any
concerns related to the test. For these
reasons, DOE has determined it is not
necessary to automatically allow testing
of a second sample. DOE, at its
discretion, may decide testing an
additional sample is appropriate in
cases where the tested sample has been
found to be defective.
NCC commented that any basic model
that fails to meet its certified rating
should be re-certified based upon test
data. If that model was used to validate
an AEDM, then the AEDM should be revalidated (NCC, No. 95 at p. 2) DOE
understand these suggestions and while
DOE may require a manufacturer to
conduct additional testing if the
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
manufacturer has been found to be in
violation of an applicable standard or
certification requirement, the
Department prefers not to mandate
additional testing and instead evaluate
such a requirement on a case-by-case
basis. The Department is not inclined to
mandate additional testing because of
the burden it imposes. In terms of revalidation, as long as the manufacturer
has sufficient test data underlying the
AEDM to meet the validation
requirements, additional testing for revalidation would not be required by
DOE.
AHRI suggested that DOE apply the
verification requirements adopted for
commercial HVAC, WH, and
refrigeration equipment to walk-ins. It
requested that DOE include the
provisions for witness testing and
engineered-to-order equipment. (AHRI,
No. 100 at p. 3) In this final rule, DOE
has aligned the AEDM verification
methodology for walk-ins to match the
provisions for commercial HVAC, WH,
and refrigeration equipment. However,
the engineered-to-order concept is
outside the scope today’s rulemaking.
DOE will address the engineered-toorder concept and other certification
issues in a future rulemaking.
The CA IOUs commented that DOE’s
verification process is poor and not
easily enforceable. Additionally, the CA
IOUs raised the concern that WICF
manufacturers are not as active in
industry certification programs as other
types of commercial equipment
manufacturers. They assert that these
two factors could undermine both the
potential energy savings that would be
likely to accrue from any standards that
DOE issues and fair competition. The
CA IOUs recommended that DOE work
with AHRI and ASHRAE to develop
calculation tools for WICF
manufacturers. (CA IOUS, No, 101 at p.
2) The Department appreciates the
suggestion from the CA IOUs; however,
DOE finds that manufacturers are better
suited for developing modeling tools for
their own equipment because they have
more intimate knowledge of their own
equipment’s operational and design
characteristics. Thus, a model
developed by the basic model’s
manufacturer is likely to be more
accurate than a general model
developed by the Department. And
since DOE may request any of the
relevant data and documentation a
manufacturer has used to develop a
given AEDM, in DOE’s view, there is
sufficient incentive for a manufacturer
to take appropriate steps to ensure both
the thoroughness and accuracy of its
AEDMs.
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
b. Action Following Determination of
Noncompliance Based Upon
Enforcement Testing
Rather than require the revalidation of
an AEDM if a noncompliant model had
been used to validate that AEDM, DOE
proposed that each AEDM must be
supported by test data obtained from
physical tests of current models.
Because a noncompliant model may not
be distributed in commerce, and so
must be discontinued and can no longer
be considered a current model, the
manufacturer will need to ensure that
the AEDM continues to satisfy the
proposed validation requirements
described in section III.A.2 Additional
testing would only be necessary if the
noncompliant equipment was used as a
sample for validating the AEDM. In that
case, the manufacturer must perform
additional testing of a different model to
ensure the AEDM is valid. Pursuant to
this requirement, should such testing
result in a change in the ratings of
equipment certified using the AEDM,
then those pieces of equipment must be
re-rated and re-certified.
HTPG supported DOE’s approach and
stated that re-validation of an AEDM
should only be required if a noncompliant model was used to validate
the AEDM. (HTPG, No. 96 at pp. 2–3)
It added that DOE should permit the use
of a second sample to address possible
abnormal failures. DOE notes that its
proposed approach, which is based on
the use of physical tests of a sample of
models would not require on the results
of tests from a single model and would
account for abnormal failures that may
occur. No other comments were
received. Consequently, DOE is
adopting the approach detailed in its
proposal.
5. Re-Validation
DOE evaluated different
circumstances that may require a
manufacturer to re-validate an AEDM.
These circumstances are described in
more detail below. In response to this
proposal in the SNOPR, ACEEE made a
general comment that DOE’s proposed
treatment of the revalidation process
appears to assure a good balance
between testing burdens and trusted
certifications. (ACEEE, No. 98 at p. 1)
tkelley on DSK3SPTVN1PROD with RULES2
a. Change in Standards or Test
Procedures
In the February 2014 SNOPR, DOE
proposed not to require re-validation
every time the test procedure or
standard changes. However, should
DOE believe that re-validation is
necessary pursuant to a final rule
standard or test procedure, DOE would
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
raise that issue in the appropriate NOPR
and solicit comment from the public on
the merits of including revalidation.
HTPG and NCC agreed with the
Department’s proposal to evaluate the
necessity to re-validate an AEDM due to
a federal energy conservation standard
or test procedure change on a case-bycase basis. (HTPG, No. 96 at p. 3; NCC,
No. 95 at p. 2) AHRI also commented
that re-validation should only be
required when a change in test
procedure is significant enough to result
in a product having a different rated
value for energy consumption or
efficiency. (AHRI, No. 100 at p. 3)
b. Re-Validation Using Active Models
DOE proposed to require
manufacturers to re-validate their
AEDMs if one of the basic models used
for validation is no longer in production
or if it becomes obsolete. See 79 FR at
9843. DOE did not receive any
comments regarding this proposal and is
adopting it in today’s final rule. DOE is
concerned that an AEDM’s accuracy
may be compromised if the models that
are used to validate it become obsolete.
DOE encourages manufacturers to test
their models beyond the minimum
validation requirements as a means to
affirm an AEDM’s validity. As long as
the manufacturer has sufficient test data
underlying the AEDM to meet the
validation requirements and can readily
produce that documentation on request,
additional testing for re-validation
would not be required by DOE.
c. Time Allowed for Re-Validation
In the February 2014 SNOPR, DOE
declined to propose a time limit to revalidate an AEDM. A manufacturer
would need to ensure that any AEDM it
uses for purposes of certifying its
equipment satisfies the validation
requirements and that the necessary
supporting documentation is available
to DOE on request. AHRI agreed with
DOE that a time limit should not be
imposed because it is consistent with
the AEDM requirements for commercial
HVAC, WH, and refrigeration
equipment. (AHRI, No. 100 at p. 3)
Lennox disagreed with the DOE’s
proposal not to include a time limit and
the Department’s statement that AEDMs
must satisfy the fundamental validation
requirements at all times. Lennox
explained that without setting a time
limit on the validity of a given AEDM,
a change in federal standards, federal
test procedure, basic model status, or a
failure of a basic model could invalidate
all certifications made using an AEDM.
This situation could cause significant
adverse economic impacts on
manufacturers because it would reduce
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
27397
their ability to bring products to market
while performing the additional testing
required for re-validating the AEDM.
Lennox recommended that if revalidation occurs due to an amended
federal test procedure or energy
conservation standard, then revalidation should not be required until
the later of (1) 180 days after the final
rule for the amended federal test
procedure or energy conservation
standards or (2) the effective date of that
amended test procedure or standard. If
re-validation is required due to a basic
model becoming invalid or the failure of
a basic model to meet its certified rating,
DOE should allow a minimum of 120
days for the AEDM to be re-validated.
(Lennox, No. 97 at p. 4) DOE agrees that
in some circumstances a time limit
should be imposed for re-validating
AEDMs, such as in the case where a
federal test procedure or energy
conservation standard is amended.
However, DOE prefers that the revalidation time limit be established on
a case-by-case basis in the course of
each particular rulemaking instead of
mandating a specific time frame.
Applying a more tailored approach
would allow stakeholders of the
particular rulemaking and the
Department to evaluate how substantial
the change may be and how much time
would be required for the affected
manufacturers to address such changes.
The February 2014 SNOPR also
inadvertently included a request for
comment on a 90-day allowance for
manufacturers to re-validate, re-rate,
and recertify an AEDM. DOE received
comments from Bally, KeepRite, NCC,
and HTPG stating that 90 days was
insufficient and that a period of time
around 120–180 days was more
appropriate. (Bally, No. 93 at p. 2;
KeepRite, No. 94 at p. 2; NCC, No. 95
at p. 2; HTPG, No. 96 at p. 3) As DOE
is not establishing a time limit for revalidations in this Final Rule, and will
instead handle this on a case-by-case
basis, DOE is not adopting any of the
suggested time periods offered by these
commenters.
B. Refrigeration Test Procedure
During DOE’s rulemaking to establish
test procedures for WICF equipment,
which resulted in a final rule published
on April 15, 2011 (‘‘April 2011 test
procedure final rule;’’ 76 FR 21580),
interested parties supported DOE’s
approach to use AHRI 1250 (I–P)–2009,
‘‘2009 Standard for Performance Rating
of Walk-In Coolers and Freezers’’
(‘‘AHRI 1250–2009’’), for WICF
refrigeration testing. AHRI 1250–2009 is
an industry-developed testing protocol
used to measure walk-in efficiency. In
E:\FR\FM\13MYR2.SGM
13MYR2
27398
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
the 2014 SNOPR, DOE proposed to add
certain modifications to its procedures
for manufacturers to follow when
applying AHRI 1250–2009. These
proposed changes were designed to
either clarify certain steps in AHRI
1250–2009 or reduce the testing burden
of manufacturers while ensuring that
accurate measurements are obtained.
These modifications are discussed in
the following sections.
1. Component-Level Ratings for
Refrigeration: Overall
Responding to a number of comments
addressing DOE’s proposed energy
conservation standards, DOE’s February
2014 SNOPR proposed an approach to
allow manufacturers to test a separatelysold condensing unit or unit cooler and
generate an AWEF metric consistent
with the existing system-based test
procedure. Under the proposed
approach, a manufacturer who sells a
unit cooler model without a matched
condensing unit must rate and certify
that model as part of a refrigeration
system basic model containing that unit
cooler model by testing according to the
methodology in AHRI 1250–2009 for
unit coolers used with a parallel rack
system (see AHRI 1250–2009, section
7.9). The manufacturer would use a
calculation method to determine the
system AWEF and certify this AWEF to
DOE. Additionally, all unit coolers
tested with this method would need to
comply with any of the applicable
standards that DOE may decide to adopt
for the multiplex equipment classes
addressed in its standards proposal. A
manufacturer who sells a condensing
unit model separately must rate and
certify that model as part of a
refrigeration system basic model
containing that condensing unit model
by conducting the condensing unit
portion of the AHRI 1250–2009 mix/
match test method. The results from the
mix/match test would be combined with
a nominal unit cooler capacity and
power, based on nominal values for
saturated suction temperature and unit
cooler fan and electric defrost energy
use factors (or the hot gas defrost
calculation methodology, as applicable),
in order to calculate an AWEF for the
refrigeration system basic model
containing that condensing unit. 79 FR
at 9830.
All commenters supported DOE’s
proposal to allow rating and
certification for unit coolers and
condensing units separately. (Bally, No.
93 at p. 2; Keeprite, No. 94 at p. 2; NCC,
No. 95 at pp. 2–3; HTPG, No. 96 at p.
3; ACEEE, No. 98 at p. 1; ASAP, et al.,
No. 99 at p. 2; CA IOUs, No. 101 at p.
1; AHRI, No. 100 at p. 4; and Lennox,
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
No. 97 at p. 5) Several commenters,
however, suggested that DOE clarify the
circumstances under which unit coolers
and condensing units may be rated
separately or as a matched system.
Keeprite and AHRI suggested that if a
manufacturer of a unit cooler and
condensing unit rates each component
as a separate basic model, the
manufacturer should not need to re-rate
the components as a combined system
even if they are marketed and sold
together. However, they further
suggested the matched system test
method should be used if the system is
a packaged system or the components
are exclusively marketed and sold as a
matched system. (Keeprite, No. 94 at p.
2; AHRI, No. 100 at pp. 4–5) NCC stated
that, except for packaged systems and
those units paired in marketing
literature, manufacturers should be
permitted to rate all unit coolers and
condensing units separately. (NCC, No.
95 at pp. 2–3) Similarly, Lennox
requested that DOE clarify that only
models exclusively marketed and sold
as a matched system must be rated as a
matched system, and that manufacturers
should be allowed to match components
as a service to the customer without
having to test each combination if the
components were previously rated
separately. (Lennox, No. 97 at pp. 5–6)
The CA IOUs, on the other hand,
recommended that DOE require unit
coolers and condensing units to be rated
separately unless they are part of a
unitary (self-contained) system or a
matched variable refrigerant flow
system. Otherwise, if DOE allows
matched equipment rating for
combinations of ‘‘remote’’ unit coolers
and condensing units (i.e., those
produced as separate pieces of
equipment), then DOE should also
require the manufacturer to calculate
the efficiency ratings of each component
as though it were to be sold separately
and, if they have a lower rating when
rated separately, DOE should require an
annual accounting of shipments to
ensure they are always sold as
combined systems. (CA IOUs, No. 101 at
pp. 1–2) ASAP, et al. agreed that DOE
should ensure that unit coolers and
condensing units rated as ‘‘matched
pairs’’ are only sold as ‘‘matched pairs’’
unless the components are also rated
separately, to prevent the situation
where an inefficient component is rated
with a highly efficient component as a
matched pair, but the inefficient
component is also sold separately,
resulting in lost energy savings. (ASAP,
et al., No. 99 at pp. 1–2) HTPG, on the
other hand, stated that the rating of
matched systems should be allowed in
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
order for the AWEF ratings to reflect
technology advances that require closely
matching unit coolers and condensing
units. (HTPG, No. 96 at p. 3) The CA
IOUs also recommended that the mixmatch approach be dropped from the
standard and that DOE not require
measurement of condensing unit
performance at two different suction
pressures for each ambient temperature
application, which reduces
manufacturer test burden. (CA IOUs,
No. 101 at p. 2)
In this rule, DOE finalizes an
approach that would allow
manufacturers to test a condenser or
unit cooler separately, but rate that
component as part of a refrigeration
system with an AWEF metric consistent
with DOE’s proposed energy
conservation standards for WICF
refrigeration systems. First, DOE agrees
with Keeprite, AHRI, NCC, and Lennox
that, if components are rated separately
for the purposes of certifying and
complying with the DOE standard, they
do not need to be rated as a matched
system if they are later combined and
sold as a matched system, either by their
original manufacturer or an installer. If,
however, a manufacturer wishes to
make a representation of a matched
system’s efficiency that is higher than
the ratings achieved individually by
each component, the manufacturer must
base that representation on the rating
obtained through testing of the matched
system. Second, DOE agrees with the
CA IOUs and ASAP, et al. that a
component must be certified
individually and must individually
comply with DOE’s standards if it is
sold separately by its manufacturer.
However, DOE does not intend to
prevent manufacturers from rating and
certifying matched systems in order to
reflect technological advances
achievable with matched systems, as
pointed out by HTPG. DOE recognizes
that certain refrigeration systems, such
as packaged or unitary systems that
consist of a single piece of equipment,
or systems that implement a multiplecapacity condensing unit, can only be
rated as matched systems under the
current test procedure. DOE recognizes
that, as pointed out by the CA IOUs, the
mix-match procedure is not needed
under this approach, as components
sold separately would be rated using the
separate rating methodology, and
components sold as a matched system
would be rated using the matched
system test procedure. Therefore, DOE
is removing the mix-match suction
temperature conditions from the test
method for clarity and consistency with
E:\FR\FM\13MYR2.SGM
13MYR2
tkelley on DSK3SPTVN1PROD with RULES2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
its overall rating and certification
approach.
Some commenters also urged DOE to
supplement the proposed separatestandards approach with a product
labeling requirement to improve the
enforceability of the standard. ASAP, et
al. stated that the component level
approach could create a loophole
whereby a component manufacturer
could avoid having to meet DOE’s walkin standards by claiming that its
component is not designed for use in
walk-ins or by declining to specify an
application for the equipment. In the
short term, it suggested that DOE should
require all components sold for use in
a walk-in to bear a label indicating that
they are certified for walk-in use, and
issue revised compliance guidance
clarifying that walk-in component
standards apply to equipment that has
the attributes associated with typical
walk-in components in the absence of a
manufacturer’s specific instruction that
the equipment is not for use in walk-ins.
In the long term, DOE should develop
energy conservation standards for
components independent of end-use.
(ASAP, et al., No. 99 at pp. 2–3)
Furthermore, ASAP, et al. stated that
DOE should require unit coolers and
condensing units rated and sold as
matched pairs to bear a label stating that
each is only for sale when matched with
the other component. (ASAP, et al., No.
99 at p. 2) Similarly, the CA IOUs
recommended that DOE develop
compliance and labeling requirements
such that all major walk-in components
would carry a label certifying that they
comply with the walk-in efficiency
regulations. If DOE allows matched
pairs of unit coolers and condensing
units where one of the components does
not comply with the standard
individually, the labeling scheme
should ensure that the deficient
component is only installed with the
matched component that results in the
combined system efficiency that
complies with the DOE standard. (CA
IOUs, No. 101 at p. 6)
DOE agrees with the CA IOUs and
ASAP, et al. and recognizes the
importance of labeling in facilitating
compliance and enforcement
throughout the WICF distribution chain,
and in ensuring that systems rated as
matched systems are only sold in their
matched configuration. Although DOE
is not establishing labeling requirements
at this time, it may consider establishing
labeling requirements in a future
certification, compliance, and
enforcement rulemaking.
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
2. Component-Level Ratings for
Refrigeration: Metrics
Two interested parties commented on
the metrics used to rate individual
components. The CA IOUs
recommended that the performance
metric for condensing units be the
Annual Energy Efficiency Ratio (AEER)
because it is simpler to calculate than
AWEF and can be expanded to a
broader range of condensing units than
those used in walk-in applications. (CA
IOUs, No. 101 at p. 3) AHRI also
suggested that condensing units and
unit coolers sold separately should have
a separate metric than AWEF, as the use
of AWEF implicitly allows for
component ratings to be compared to
system ratings. (AHRI, No. 100 at pp. 5–
6)
In this final rule, DOE is retaining
AWEF as the metric for rating
refrigeration systems and for
refrigeration system components
(condensing units and unit coolers)
rated as part of a refrigeration system, as
this is the metric used in the DOE test
procedure, which is based on the
industry testing protocol AHRI 1250–
2009. If the industry develops a future
revision of this test method with
different metrics, such as AEER or
another, separate metric for component
ratings, then DOE may consider
adopting it in a future rulemaking.
Neither the refrigeration test
procedure nor the proposed energy
conservation standard incorporates
standby or off-mode energy use because
the vast majority of WICFs must operate
at all times to keep their contents cold.
The CA IOUs recommended that the
refrigeration system metric account for
stand-by losses, particularly for
condensing units when the compressor
is off, as condensing unit ancillary loads
such as the crankcase heater,
transformer, and control electronics can
contribute significantly to the energy
consumption. (CA IOUs, No. 101 at p.
4)
DOE agrees that, when considered
individually, condensing units may
experience standby energy use when the
compressor is not running. DOE
carefully considered this issue but is not
currently aware of any recognized or
well-accepted methods for measuring
standby condenser energy use.
However, if the industry develops a test
method to determine this energy usage,
then DOE may consider adopting it in
a future rulemaking.
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
27399
3. Component-Based Ratings for
Refrigeration Systems: Nominal
Calculation Values
In the SNOPR, DOE proposed
nominal values for unit cooler capacity
and power to be used when rating a
condensing unit as an individual
component of a refrigeration system
using an AWEF metric. DOE developed
the nominal values from DOE testing
and modeling of WICF refrigeration
systems and published the test data on
which the nominal values were based.
79 FR at 9830.
In general, stakeholders agreed with
the use of nominal unit cooler values to
rate condensing units. (CA IOUs, No.
101 at p. 3; Bally, No. 93 at p. 2; NCC,
No. 95 at p. 3; HTPG, No. 96 at p. 4;
AHRI, No. 100 at p. 5; and Lennox, No.
97 at p. 2) However, some were
concerned that components rated
separately would not be able to meet
DOE’s energy conservation standards.
AHRI expressed concern about the effect
of the rating strategy on minimum
efficiency levels and recommended that
DOE conduct a thorough and public
analysis to alleviate the concern that the
AWEFs proposed in the energy
conservation standards NOPR would
not be achievable by refrigeration
components rated separately. (AHRI,
No. 100 at pp. 5–6) NCC also suggested
that DOE conduct an evaluation to
ensure the energy efficiency standard
levels are achievable with this
approach. (NCC, No. 95 at p. 3) With
respect to AHRI’s concern that the
AWEF standards are not achievable by
refrigeration components, DOE notes
that it has structured its nominal values
assuming that the condensing units are
paired with unit coolers that would
meet whatever standard, if any, that
DOE may eventually adopt. Thus,
condensing unit manufacturers should
not incur a penalty if they rate their
condensing unit as part of a matched
system or as an individual component.
The following paragraphs address
specific comments or concerns about
the three main nominal values used in
the equations: on-cycle evaporator fan
power, off-cycle evaporator fan power,
and defrost energy.
a. On-Cycle Evaporator Fan Power
In the SNOPR, DOE proposed a
nominal value for on-cycle evaporator
fan power of 0.016 Watts per Btu/h of
gross capacity at the highest ambient
rating condition, based on test and
modeling data. 79 FR at 9831.
Lennox commented that the proposed
nominal value for fan power for unit
coolers is based on test data that only
covered the low end of the full range of
E:\FR\FM\13MYR2.SGM
13MYR2
27400
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
capacities of equipment used in WICF
enclosures. On-cycle fan power is not a
constant value as a function of unit
capacity, but increases as the unit
capacity increases as a result of the long
air throw (that is, the distance the air
must travel after it leaves the fan)
required by this type of equipment.
(Lennox, No. 97 at pp. 2, 5)
In response to Lennox’s comment,
DOE surveyed a wider range of unit
coolers to compare unit cooler fan
wattage to unit capacity. DOE found that
its nominal value of 0.016 for unit
cooler fan wattage per capacity was
valid for low temperature systems even
at capacities up to 250,000 Btu/h;
however, a lower nominal value was
more appropriate for medium
temperature systems. (DOE was not able
to find manufacturer specifications for
larger capacities of unit coolers).
Therefore, DOE is retaining its nominal
value of 0.016 for low temperature unit
cooler on-cycle fan power and
implementing a nominal value of 0.013
for medium temperature unit cooler oncycle fan power. The data and analysis
underlying this finding are included in
the docket at https://
www.regulations.gov/
#!docketDetail;D=EERE-2008-BT-STD0015.
tkelley on DSK3SPTVN1PROD with RULES2
b. Off-Cycle Evaporator Fan Power
In the SNOPR, DOE proposed a
nominal value for off-cycle evaporator
fan power of 0.2 times the on-cycle
evaporator fan power. 79 FR at 9831.
The CA IOUs noted that this default
value is appropriate only if DOE
assumes that unit coolers are using
variable speed evaporator fans and
dropping their fan speed to 50 percent
of flow during the off-cycle periods. (CA
IOUs, No. 101 at pp. 3–4) DOE’s
nominal fan power values are based on
the approach taken in DOE’s proposed
standards. That approach, in turn, is
based on the potential use of unit
coolers that incorporate variable speed
evaporator fans. Variable speed
evaporator fans comprise one of the
technology options on which the
proposed energy conservation standard
is based. Therefore, DOE is including
this assumption to ensure that
condensing unit manufacturers are not
unfairly penalized in comparison to
matched system manufacturers.
c. Defrost Energy
In the SNOPR, DOE proposed a
nominal value for electric defrost energy
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
of 0.12 Watt-hours per defrost cycle, per
Btu/h of gross capacity at the highest
ambient rating condition, and that four
(4) cycles per day should be assumed
unless specified otherwise in the
manufacturer’s installation instructions.
See 79 FR at 9831. This 4-cycle
approach uses the same number of
cycles that DOE built into its walk-in
standards analysis. Under this
approach, the daily electric defrost heat
contribution would be 0.95 times the
daily electric defrost energy use,
converted from Watt-hours to Btu.
These nominal values are only
applicable to low-temperature
refrigeration systems. 79 FR at 9831.
DOE also specified that condensing
units designed to be used with a hot gas
defrost unit cooler, rather than an
electric defrost unit cooler, must use the
nominal values for hot gas defrost heat
load and energy use—that is, the daily
hot gas defrost heat contribution would
be 0.18 btu per defrost cycle, per Btu/
h of gross capacity at the highest
ambient rating condition; and the daily
defrost energy shall be equivalent to half
the calculated daily defrost heat
converted from Btu to watt-hours. 79 FR
at 9830–9832.
The CA IOUs suggested that the
application of the unit cooler nominal
values for defrost are fixed values that
a manufacturer would use. In its view,
the proposed regulatory text seems to
imply that the manufacturer’s
instructions would never contain any
assumed values regarding the number of
applicable cycles that would apply.
Consequently, the CA IOUs suggested
that DOE clarify the final regulatory text
by indicating that the assumed number
of cycles be fixed at 4 cycles per day.
(CA IOUs, No. 101 at pp. 3–4)
In response to the CA IOUs’ comment,
DOE believes there may be some defrost
control mechanisms that reside in the
condensing unit, with associated
manufacturer instructions. To account
for this possibility, DOE is providing
manufacturers with the flexibility to
specify the number of defrost cycles that
may occur. In an effort to avoid limiting
the manufacturers’ ability to reduce the
number of defrosts, DOE is retaining the
option to test according to
manufacturers’ instructions. However,
in investigating this issue, DOE
recognizes that the approach taken in
DOE’s proposed standards is based on
the potential use of defrost controls that
may reside in the unit cooler and not in
the condensing unit. Defrost controls
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
comprise one of the technology options
on which the proposed energy
conservation standard is based.
Therefore, DOE is revising its default
value for the number of defrosts per day
to 2.5 to ensure that condensing unit
manufacturers are not unfairly
penalized in comparison to matched
system manufacturers.
Lennox commented that the test data
used by DOE to establish the nominal
value for defrost energy does not
represent the full range of capacities
used in WICFs. The nominal value for
daily defrost energy use of 0.12 W-h/
cycle per BTU/h of capacity is
representative for smaller capacity units
but not larger capacity units, because
the defrost energy (W-h/cycle per BTU/
h) is not a constant value as a function
of unit capacity. The defrost energy
increases, but not linearly, as the unit
capacity increases due to the larger coil
sizes and corresponding heater wattage
required for larger capacity units.
(Lennox, No. 97 at pp. 6–7)
In response to Lennox’s comment,
DOE surveyed a wider range of unit
coolers (with capacities up to 250,000
Btu/h) to compare defrost wattage and
energy-to-unit capacity. DOE found that
electric defrost wattage increases
linearly with capacity, but, consistent
with the analysis DOE performed for its
energy conservation standards
rulemaking, defrost duration would also
be expected to increase nonlinearly with
capacity. Thus, DOE agrees with
Lennox’s assessment that total defrost
energy increases non-linearly with
capacity. As a result of its analysis, DOE
is expressing the electric defrost energy
as a power function instead of a linear
equation. The data and analysis
underlying the development of this
equation are included in the docket at
https://www.regulations.gov/#!docket
Detail;D=EERE-2008-BT-STD-0015.
DOE also clarifies that condensing
units designed to be used with hot gas
defrost unit coolers may use the
nominal values associated with hot gas
defrost systems. For clarity, DOE has
added these values as nominal values
for unit cooler energy use factors. DOE
is also expressing the values in the form
of equations that incorporate the
capacity variable to emphasize that they
are functions of the given unit’s
capacity.
Table III.5, below, contains DOE’s
revisions to the nominal values for unit
coolers.
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
27401
TABLE III.5—CALCULATIONS FOR UNIT COOLER SATURATED SUCTION TEMPERATURE AND ENERGY USE FACTORS
Medium temperature
Saturated Suction Temperature (°F) ....................................................................
On-cycle evaporator fan power (W) .....................................................................
25 ..............................
0.013 × Q* .................
Low temperature
¥20.
0.016 × Q.
0.2 × on-cycle evaporator fan power.
Off-cycle evaporator fan power (W) .....................................................................
8.5 × 10¥3 × Q1.27
0.95 × electric defrost energy use per
cycle × 3.412.
0.5 × hot gas defrost heat contribution
per cycle/3.412.
0.18 × Q.
Electric defrost energy per cycle (W-h/cycle) ......................................................
Electric defrost heat contribution per cycle (Btu/cycle) ........................................
0 ................................
0 ................................
Hot gas defrost energy per cycle (W-h/cycle) .....................................................
0 ................................
Hot gas defrost heat contribution per cycle (Btu) ................................................
0 ................................
Number of cycles per day ....................................................................................
As specified in installation instructions or, if no instructions, 2.5
* Q represents the gross capacity at the highest ambient rating condition in Btu/h.
4. Other Test Procedure Changes
In the SNOPR, DOE proposed several
other changes to clarify or simplify
elements of the test procedure to reduce
overall test burden. These changes,
discussed below, consist of a variety of
modifications related to both
refrigeration systems and panel
insulation. HTPG generally agreed with
the changes and stated they would
reduce testing burden and improve
manufacturers’ ability to respond to
DOE’s proposed standards. (HTPG, No.
96 at p. 4) Concurrent with this
rulemaking, AHRI formed a committee
to update the AHRI 1250–2009 test
procedure. In its comment, AHRI stated
that its latest updates to AHRI 1250 had
adopted most of DOE’s proposed
changes in the SNOPR, with a few
minor alterations. AHRI included a
courtesy copy of the draft AHRI 1250
update, titled AHRI 1250–2014, with its
comment to DOE. (AHRI, No. 100 at p.
2) DOE has reviewed AHRI’s update to
the test method and has incorporated
many of the changes. (Specific details
on changes and associated comments
are discussed in the following sections.)
DOE intends to begin the process of
incorporating by reference the entirety
of the updated version, which will
require a separate rulemaking.
Meanwhile, DOE is retaining its
approach of amending the current test
procedure (AHRI 1250–2009) in the
regulatory language.
tkelley on DSK3SPTVN1PROD with RULES2
a. Nominal Values for Defrost Energy
and Heat Load Calculations
In the SNOPR, DOE proposed a
calculation methodology that would be
used for calculating some aspects of
electric defrost energy use in lieu of
using certain tests for electric defrost
energy use. Specifically, DOE proposed
that the only required test for electric
defrost energy use of unit coolers is the
test to determine the energy input for
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
the dry coil condition. The nominal
values for frosted coil energy use,
number of defrosts per day in the event
that the unit cooler has an adaptive
defrost system, and daily contribution of
heat load attributed to defrost could
then be calculated using nominal values
rather than having to conduct their
individual respective tests.
Furthermore, as there is currently no
industry-accepted method for
calculating hot gas defrost energy use
and heat load, DOE proposed nominal
values for calculating these quantities
for systems utilizing hot gas defrost. 79
FR at 9831–9832.
Lennox agreed with DOE’s proposal to
make the full defrost tests optional, as
well as a portion of the adaptive defrost
test. (Lennox, No. 97 at p. 6) AHRI
incorporated DOE’s nominal values and
calculation methodology for electric and
hot gas defrost into its update of AHRI
1250. (AHRI, No. 100 at pp. 56–58)
HTPG, however, noted that the
calculation methods for hot gas defrost
do not allow for some of the advanced
methods being utilized in the market or
that may be likely to occur in the near
future. HTPG proposed that DOE work
with industry to develop a test method
to give credit to the energy advantages
of various hot gas defrost methods.
(HTPG, No. 96 at p. 4)
After carefully considering these
comments, DOE has decided to retain
the nominal values for calculating
frosted coil energy use, number of
defrosts per day if the unit has an
adaptive defrost system, and daily
contribution of heat load, as well as
nominal values for calculating hot gas
defrost energy use and heat load. DOE
agrees with HTPG that a test procedure
for hot gas defrost would be beneficial
to capture innovative technologies not
currently accounted for by the
calculation methodology. Should the
industry develop a test method for
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
rating hot gas defrost systems, DOE may
consider adopting it.
b. Off-Cycle Evaporator Fan Test
In the SNOPR, DOE proposed to
amend one aspect of its test procedure
that incorporates AHRI 1250–2009.
Specifically, DOE raised the possibility
of amending that portion of its
procedure that involves AHRI 1250–
2009, section C10 by changing the
currently specified requirement that
when conducting the off-cycle
evaporator fan test, controls shall be
adjusted so that the greater of a 25
percent duty cycle or the manufacturer
default is used for measuring off-cycle
fan energy; and for variable speed
controls, the greater of 25 percent fan
speed or the manufacturer’s default fan
speed shall be used for measuring offcycle fan energy. In the SNOPR, DOE
proposed to amend the maximum offcycle fan cycling or speed reduction to
50 percent of on-cycle duty cycle or 50
percent of on-cycle fan speed. 79 FR at
9832. The CA IOUs supported DOE’s
proposal, citing research that found that
a 50 percent reduction in fan speed did
not have significant impacts on product
temperatures, room temperature
stratification, or infiltration. (CA IOUs,
No. 101 at pp. 4–5) Lennox and AHRI
also agreed with the proposed
modification, and AHRI noted that they
included the modification in their
revised test procedure, AHRI 1250–
2014. (Lennox, No. 97 at p. 7; AHRI, No.
100 at p. 10) In the absence of any
objection to its proposed approach, DOE
is adopting its proposed amendment.
c. Refrigerant Oil Testing
In the SNOPR, DOE proposed to
eliminate from its requirements that
AHRI 1250–2009, section C3.4.6 be
followed when conducting a test of
walk-in refrigeration systems. That
incorporated provision requires that a
measurement be taken of the ratio of oil
E:\FR\FM\13MYR2.SGM
13MYR2
27402
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
to refrigerant in the liquid refrigerant
passing from the condenser to the unit
cooler for all condensing units with onboard oil filters. 79 FR at 9832. Lennox
agreed with DOE’s proposal to eliminate
the requirement for oil circulation test
for units with integrated oil separators
and with the assumption that the
associated oil circulation ratio would be
less than 1 percent. (Lennox, No. 97 at
p. 7) The CA IOUs supported DOE’s
proposed removal of the requirement for
refrigerant oil testing for systems with
oil separators and added their collective
belief that manufacturers do not
anticipate that any new WICF
refrigeration system being tested would
likely have negligible oil in the
refrigerant. They stated that the
proposal to remove the oil testing
requirement should apply to all systems
and not just those with in-line oil
separators. The CA IOUs recommended
DOE investigate this claim and if
correct, remove the requirement for all
systems. (CA IOUs, No. 101 at p. 5) NCC
and AHRI also supported removing the
oil testing requirement for all systems,
not just systems with oil separators, as
single-compressor condensing units do
not generally have oil separators. These
commenters asserted that conducting oil
testing would be time-consuming,
expensive, and unnecessary. (NCC, No.
95 at p. 3; AHRI, No. 100 at p. 6) In light
of these comments, DOE is removing the
oil testing requirement for all systems
due to the test burden involved and its
belief that refrigerant oil is not a
significant factor in new systems. If,
however, DOE finds that refrigerant oil
is affecting the repeatability or accuracy
of the testing, DOE may reinstate this
requirement at a later time.
d. Temperature Measurement
In the SNOPR, DOE proposed that the
required tolerance for test temperature
measurement be maintained at ±0.5 °F
for measurements at the inlet and outlet
of the unit cooler, but be altered to
±1.0 °F for all other temperature
measurements, allowing for the use of
smaller temperature measurement
probes which can more easily be placed
in contact with the refrigerant while not
impeding its flow. Additionally, DOE
proposed to allow the test to be
conducted using sheathed sensors
immersed in the flowing refrigerant for
refrigerant temperature measurements
upstream and downstream of the unit
cooler, in order to reduce test burden.
No refrigerant temperature
measurements other than those
upstream and downstream of the unit
cooler would require a thermometer
well or sheathed sensor immersion. 79
FR at 9832.
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
The CA IOUs supported DOE’s
proposal to allow refrigerant
measurements upstream and
downstream of the unit cooler to be
conducted using either sheathed sensors
or thermocouple wells immersed in
flowing refrigerant. (CA IOUs, No. 101
at p. 5) AHRI noted its update to the test
procedure, AHRI 1250–2014,
incorporates DOE’s proposed approach
for temperature measurement. (AHRI,
No. 100 at p. 10) Keeprite, on the other
hand, believed the type of temperature
sensor should not be specified as there
are other methods or technologies that
exist that could achieve the specified
tolerances. (Keeprite, No. 94 at p. 2)
In light of the comments, DOE is
adopting the modifications to the
temperature measurement approach in
this final rule. In response to Keeprite’s
comment, DOE notes that the approach
being adopted today incorporates
methods that have been established and
accepted by industry for accurate
measurement of temperature. If DOE
becomes aware of other, equally valid
methods or technologies for measuring
temperature, it may consider adopting
them as acceptable methods in the DOE
test procedure.
e. Test Condition Tolerances
In the SNOPR, DOE proposed to
modify the existing test procedure
tolerances to:
• Set a test condition tolerance for the
frequency of electrical power;
• Clarify that the stated maximum
allowable voltage imbalance for threephase power supply refers to the
maximum imbalance for voltages
measured between phases, rather than
phase-to-neutral;
• Delete the requirements related to
the test condition tolerances or
measurements of air leaving the unit;
and
• Remove the tolerances for wet bulb
temperature on the outdoor system
conditions, except for units with
evaporative cooling.
DOE proposed to retain all other
measurement tolerances for air entering
the heat exchangers, including dry bulb
outdoor conditions and dry bulb and
wet bulb indoor conditions (wet bulb
temperature or humidity levels greater
than the required test conditions could
cause excessive frosting of the coil and
affect its rated capacity). 79 FR at 9832–
9833.
The CA IOUs supported DOE’s
proposed changes to the
instrumentation accuracy requirements
and DOE’s recommendation not to
require or set accuracy requirements for
air temperature exiting unit coolers. The
CA IOUs also agreed that air
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
temperature leaving unit coolers need
not be measured and that maintaining
condensing unit entering air wet-bulb
temperatures should only be applicable
to the testing of evaporatively cooled
condensing units, but supported
maintaining both the specified dry-bulb
and relative humidity conditions for air
entering the unit cooler. (CA IOUs, No.
101 at p. 5) AHRI noted that its update
to the test procedure, AHRI 1250–2014,
incorporates DOE’s proposed test
procedure tolerances. (AHRI, No. 100 at
p. 10) In light of the comments, DOE is
adopting its proposed tolerances.
f. Pipe Insulation and Length
In the SNOPR, DOE proposed that
pipe lines between the unit cooler and
condensing unit insulation be
equivalent to a half-inch thick
insulation with a material having an Rvalue of at least 3.7 per inch, and that
flow meters would not need to be
insulated but must not contact the floor.
DOE also proposed to clarify the
requirements on piping length such
that:
• The length of piping between the
condenser and unit cooler does not
include any flow meters;
• The length of piping allowed within
the cooled space shall be a maximum of
15 feet; and
• In the event that there are multiple
branches of piping inside the cooled
space, the 15-foot limit shall apply to
each branch individually instead of the
total piping length. 79 FR at 9833.
Lennox supported DOE’s proposed
clarification of pipe insulation and
length requirements. (Lennox, No. 97 at
p. 7) AHRI noted it has already
incorporated DOE’s proposed
requirements for pipe insulation and
length in its latest revision to the test
method, AHRI 1250–2014. (AHRI, No.
100 at p. 73) In light of the comments,
DOE is adopting its proposed
modifications to piping insulation and
length requirements.
g. Composition Analysis
In the SNOPR, DOE proposed to
remove the current requirement in its
procedure that a refrigerant composition
analysis be conducted for systems with
zeotropic refrigerant mixtures. 79 FR at
9833. Lennox and the CA IOUs
supported the proposal. (Lennox, No. 97
at p. 7; CA IOUs, No. 101 at p. 5) ACEEE
recommended that if changes in the
ratios of the zeotropic blend could
significantly affect capacity or
efficiency, then verification that the
composition meets industry standards
may be needed; however, this could
consist of laboratory certification
documents provided by the
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
manufacturer of the refrigerant blend.
(ACEEE, No. 98 at p. 1) AHRI indicated
that it removed the current requirement
to test a sample of the superheated
vapor refrigerant. (AHRI, No. 100 at p.
10) In light of the comments, DOE is
removing the requirement to conduct a
refrigerant composition analysis. If,
however, DOE finds that refrigerant
composition is affecting the
repeatability or accuracy of the testing,
DOE may reinstate this requirement at a
later time.
specify a lower superheat value in their
installation instructions in order for the
equipment to realize an energy benefit.
Therefore, DOE is requiring that
superheat be set according to the
manufacturer’s specifications in order to
give credit for electronic expansion
valves or advanced controls. In
instances where there are no
specifications for superheat, then the
superheat shall be set to 6.5 °F. In either
case, superheat must be reported as part
of the standard rating.
h. Unit Cooler Test Conditions
In the SNOPR, DOE proposed to
incorporate a modified version of Tables
15 and 16 from AHRI 1250–2009. Those
tables list the unit cooler test
conditions. DOE proposed to include
the inlet saturation temperature and
outlet superheat conditions required in
AHRI 420–2008, ‘‘Performance Rating of
Forced-Circulation Free-Delivery Unit
Coolers for Refrigeration,’’ (‘‘AHRI 420–
2008’’) for testing these types of unit
coolers as part of the tables. 79 FR at
9833.
Lennox and the CA IOUs
recommended that instead of setting the
superheat conditions to 6.5 °F in all
cases, as required by AHRI 420–2008,
the superheat conditions should be set
according to the manufacturer’s
specifications or installation
instructions to ensure that the test
method can credit the energy efficiency
benefits of electronic expansion valves
by allowing manufacturers to set lower
superheat levels. (Lennox, No. 97 at pp.
7–8; CA IOUs, No. 101 at p. 6) Lennox
also noted that the saturated suction
values should reflect the freezer test
conditions of ¥ 20 and ¥ 25 °F.
(Lennox, No. 97 at p. 8) The CA IOUs
supported fixing the liquid inlet
saturation temperature at 105 °F. (CA
IOUs, No. 101 at p. 6) Additionally,
AHRI incorporated the AHRI 420–2008
conditions into the tables with test
conditions for unit coolers, with the
addition of a note instructing that
superheat conditions shall be set
according to the equipment
specification in the equipment or
installation manual. That note specifies
that in instances where no specification
is given, a default superheat value of 6.5
°F shall be used, and the superheat
setting shall be reported as part of the
standard rating. (AHRI, No. 100 at pp.
32–33)
DOE notes that manufacturers can
often incorporate technologies that
allow the superheat to be lowered from
the industry default value to reduce
energy consumption, but installers
typically set the superheat by adjusting
a valve. Manufacturers would need to
C. Test Procedure for WICF Panel RValue (ASTM C518–04)
The DOE test procedure, 10 CFR
431.304 Uniform test method for the
measurement of energy consumption of
walk-in coolers and walk-in freezers,
incorporates by reference ASTM C518–
04, a standard method for determining
thermal transmission properties (i.e.,
thermal conductance or conductivity) of
a material. In the February 2014 SNOPR,
DOE proposed several modifications
and clarifications to the test procedure
to ensure accuracy and reliability. These
proposed revisions would apply to
those testing provisions that
manufacturers must currently use as
well as those provisions that would
need to be followed when evaluating the
efficiency of a panel under any new
standards that DOE may eventually
adopt as part of its parallel standards
rulemaking. The proposed revisions
would require that test samples be no
more than one (1) inch in thickness, be
taken from the center of the panel and
have all protective skins or facers
removed prior to testing. See 79 FR at
9844. DOE received several comments
on its proposed modifications, which
are discussed in the following
subsections.
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
1. Test Sample Specifications
In the SNOPR, DOE proposed that test
samples for R-value measurement
according to ASTM C518–04 be 1 inch
in thickness and cut from the center of
a walk-in cooler or walk-in freezer
panel. AHRI agreed with DOE’s
proposal for test samples to be 1-inch in
thickness and extracted from the center
of a finished panel. (AHRI, No. 100 at
p. 7) Bally also agreed that the
requirement for a 1-inch thick sample
cut from the center of a finished panel
is appropriate. Bally further suggested
the addition of a dimensional tolerance
of +.125 inches and ¥0.0 inches for this
thickness. (Bally, No. 93 at p. 3)
DOE is adopting its proposal that test
samples for R-value measurements
made according to ASTM C518–04 be 1inch in thickness and cut from the
center of a walk-in cooler or walk-in
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
27403
freezer panel. This change should
minimize any inaccuracy that may
result from the differences in thickness
and thermal conductance between the
test sample and the standard reference
material (SRM) used to calibrate the
heat flow meter apparatus. ASTM C518–
04 makes several statements that
indicate that the test sample thickness
and thermal properties should be
comparable to those of the calibration
standard used. (ASTM C518–04 Section
6.1 and 6.5.4) It also states that the
thickness of test samples should be
restricted in order to minimize the
amount of lateral heat losses during
testing. (ASTM C518–04 Section 7.6.1)
The new requirement to use a 1-inch
thick sample is in accordance with these
recommendations of ASTM C518–04.
The test sample will be required to be
extracted from the center of a panel
(rather than near the panel face) since
the insulation foams used in WICF
panels will have experienced the least
amount of aging degradation near the
center of the panel; also, edge regions
are not to be included in testing. DOE
agrees that a tolerance on the 1-inch
requirement is appropriate in order to
clarify this requirement. Using a sample
thickness of precisely 1 inch is not
important to the measurement because
the heat flow meter apparatus adjusts its
measurement for the exact thickness.
The objective of the requirement is that
the sample thickness be close to 1-inch,
as opposed to 2 inches or 0.5 inch, to
improve accuracy, as described above,
and to achieve consistency of test
results obtained in different
laboratories. A tolerance of ±0.1-inch for
the thickness of the test sample will
help achieve these objectives, while
being well within the precision of the
cutting tools typically used to prepare
the sample. (DOE understands that a
high-speed band-saw is often used for
cutting foam panels; moreover, a highspeed band-saw and meat slicer are the
two recommended cutting tools
suggested by ASTM C1303–09a
Standard Test Method for Predicting
Long-Term Thermal Resistance of
Closed-Cell Foam Insulation, Section
6.2.2.3.) Given that these cutting tools
are generally readily available and
capable of the precision required, DOE
believes that a ±0.1-inch tolerance for
the thickness of the test sample is
appropriate and sufficient.
DOE also agrees with Bally’s
statement that care be taken during any
cutting processes so as to not alter the
heat transfer properties of the cut
surface. (Bally, No. 93 at p. 3) Section
6.2.2.4 of ASTM C1303–09a prohibits
the use of hot-wire cutters for cutting
E:\FR\FM\13MYR2.SGM
13MYR2
27404
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
test samples in closed-cell foams to
prevent the formation of a surface skin.
DOE will also adopt as part of this final
rule a provision to prohibit the use of
hot-wire cutters or other heated cutting
instruments in preparing test samples in
order to limit potential altering of the
samples’ heat transfer properties during
the cutting process.
tkelley on DSK3SPTVN1PROD with RULES2
2. Removal of Panel Facers
DOE is also making explicit the
requirement that facers or protective
skins be removed. While these
components make a negligible
contribution to the overall thermal
resistance of WICF panels in the
direction transverse to the panel surface,
DOE recognizes that the inclusion of
metal facers or protective skins during
testing using a heat flow meter
apparatus results in unreliable
measurements. ASTM C518–04 states
that the presence of inhomogeneities or
thermal bridges can produce inaccurate
results. (ASTM C518–04 (4.4))
In its comments on the February 2014
SNOPR, AHRI related that requiring a 1inch thick sample from a finished panel
will already involve removal of the
facers or protective skins. (AHRI, No.
100 at p. 7) DOE recognizes that facers
or skins would be removed when
cutting a 1-inch thick sample from the
center of a thicker panel. DOE also
agrees with AHRI’s assertion that panels
for testing should be supplied as fully
fabricated panels intact prior to testing,
and that the 1-inch thick test sample
should be removed by the test
laboratory at the time of testing. (AHRI,
No. 100 at p. 7) The requirements of 10
CFR 431.304(b)(5) and (c)(5) require that
the insulating foam for testing be
supplied for testing in its final chemical
state. For sprayed foams, the final
chemical form inherently requires facers
or protective skins to form the shape of
the panel. Extruded foam board stock is
typically provided to WICF panel
manufacturers in its final chemical
form; in this case, facers or protective
skins may or may not be attached prior
to testing. Nevertheless, DOE is
explicitly requiring that facers or skins
be removed to ensure that the process of
cutting a sample from a thicker panel
will always achieve this objective.
3. 48-Hour Testing Window
DOE also proposed a 48-hour window
once a test sample has been cut from a
WICF panel to perform ASTM C518–04
testing in order to minimize the effect of
aging of the closed-cell foam that
constitutes the panel insulation.
Thermal resistance of polyurethane
foams that are typical of WICF panels
decreases over time due to the diffusion
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
of air into the foam. DOE proposed the
48-hour window in order to ensure
repeatability and comparability in test
results. The 48-hour window was
developed based on data from Wilkes, et
al. at Oak Ridge National Laboratory.3 In
this study, thermal conductivity of a 0.4
inch thick polyurethane foam insulation
increased between 6.0% and 20.7%
(depending on the blowing agent used)
when aged at 90 °F for 8 days and tested
at 45 °F. Assuming that the rate of
increase of thermal conductivity during
this initial period is linear, the range of
increase covered by these data over a
48-hour period would have been 1.5%
to 5%. DOE understands that the higher
temperature of 90 °F at which these
samples were aged and the smaller
thickness of the sample (0.4 inch
compared to 1-inch as proposed for
WICF panels) would also have played
contributing roles in accelerating the
aging process compared to what is to be
expected in testing WICF panels.
AHRI commented that the 48-hour
period is appropriate and sufficient.
(AHRI, No. 100 at p. 7) Bally agreed that
the time between cutting and testing
should be minimized, but disagreed that
48 hours is an appropriate testing
window for a cut sample. Bally stated
that 48 hours may be appropriate for a
conditioning period for the uncut panel
but once the panel is cut, only one hour
should be allowed before testing is
performed (rather than the 48 hours as
DOE has proposed). (Bally, No. 93 at p.
4) However, Bally provided no evidence
or data suggesting that thermal
conductivity would increase measurably
between 1 and 48 hours after cutting the
test sample. DOE notes that section 7.3
of ASTM C518–04 does not specify a
conditioning period but states that the
conditioning period is typically
indicated by a material specification,
that a typical material specification calls
for conditioning ‘‘at 22°C and 50% R.H.
for a period of time until less than a 1%
mass change is observed over a 24-h
period,’’ and that where the material
specification does not indicate a
conditioning period, materials shall not
be exposed to temperatures that will
irreversibly alter the test specimen.
(ASTM C518–04 Section 7.3) As
mentioned above, DOE expects that the
range of potential increase of thermal
conductivity for a 48-hour period is
small; however, in response to Bally’s
concerns, DOE will reduce the
3 ‘‘Aging of Polyurethane Foam Insulation in
Simulated Refrigerator Panels—Initial Results with
Third-Generation Blowing Agents’’ by Kenneth E.
Wilkes et al., published by Oak Ridge National
Laboratory for presentation at The Earth
Technologies Forum, October 26–28, 1998, Figures
2 and 4(b).
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
allowable window after cutting from 48
hours to a maximum of 24 hours to
remain conservative.
4. Specimen Conditioning Temperatures
Bally suggested that specimens be
conditioned at the mean temperatures at
which they would be tested, namely 20
degrees Fahrenheit for freezers and 55
degrees Fahrenheit for coolers. (Bally,
No. 93 at p. 4) However, it offered no
rationale, evidence or data in support of
this suggestion. DOE understands that
the intent of the conditioning is to
ensure consistency in the moisture level
within the sample during testing. DOE
expects that the closed cell insulation
materials typically used for WICF
panels would not rapidly change their
internal moisture levels, neither
absorbing a significant amount of
moisture in a 24-hour period under
normal ranges of ambient conditions,
nor rejecting a significant amount of
excess moisture in a reasonable time
period, due to the closed-cell structure
of the foam. As indicated in ASTM
C518–04 testing for WICF panels,
section 7.3, conditioning information is
typically provided in the material
specification for the material being
tested, but DOE is not aware of any such
conditioning specifications for
insulation materials typically used for
WICF panels. Further, DOE is concerned
that conditioning at cooled temperatures
could cause condensation when
removed from a cooled conditioning
environment and introduced to a
warmer room temperature in a test
laboratory. Finally, DOE is concerned
that requiring a WICF panel, often 8 feet
by 4 feet in area, to be chilled to 20
degrees Fahrenheit for an extended
period of time may introduce undue test
burden. Therefore, DOE is not requiring
conditioning requirements beyond those
already established by Section 7.3 of
ASTM C518–04.
5. Flatness Tolerances on Contact
Surfaces
Regarding its proposal to add
parallelism and flatness constraints on
the two surfaces that contact the heat
flow meter hot and cold plates, DOE
received two comments. That proposal,
which included a tolerance range of
±0.03 inches, would apply to both
parallelism and flatness. See 79 FR at
9844. AHRI stated that the proposed
tolerances ‘‘are impractical for the
purposes of the proposed test, are
inconsistent with normal WICF panel
manufacturers’ standard processes and
are likely not within the capabilities of
most current panel manufacturing
processes.’’ AHRI recommended that
DOE withdraw this proposal. (AHRI,
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
No. 100 at p. 7) It did not, however,
offer an alternative means for ensuring
sufficient contact between the test
sample surfaces and the surfaces of the
heat flow meter assembly. Contact
between these surfaces is critical to test
accuracy, as air gaps between the heat
flow meter apparatus surfaces and the
test sample surfaces will result in a
higher conductivity and lower thermal
resistance. To address AHRI’s concern,
DOE clarifies that these tolerances will
apply only to the cut faces of the test
sample itself, not the manufactured
panel. DOE also notes that, in support
of this requirement, Bally (a
manufacturer of WICF panels) stated
that the tolerances were acceptable.
(Bally, No. 93 at p. 3) As noted in
section III.C.1, in DOE’s view,
manufacturers should be able to achieve
these tolerances with common cutting
tools and techniques.
6. Panel Testing Temperature
Tolerances
With respect to the appropriate
temperatures for testing panels, DOE
proposed a tolerance of ± 1 degree
Fahrenheit on the average foam
temperature (20 degrees Fahrenheit for
freezers and 55 degrees Fahrenheit for
coolers). DOE proposed these provisions
to help ensure test repeatability. AHRI
and Bally both stated that this provision
is appropriate and sufficient. (AHRI, No.
100 at p. 7 and Bally, No. 93 at p. 3) No
other comments were received.
Accordingly, DOE is adopting its
proposed approach.
tkelley on DSK3SPTVN1PROD with RULES2
7. Additional Modifications to the Panel
Test Procedure
DOE proposed a number of additional
clarifications and modifications to the
panel test procedure. No comments
were received on these issues, which are
listed immediately below.
• Clarify and remove redundancy in
10 CFR 431.304(b)(5) and (c)(5)
regarding foam in its final chemical
form;
• Introduce an equation for WICF
panels consisting of two or more
dissimilar insulating materials other
than facers or protective skins; and
• Remove language in paragraphs (b),
(b)(6), (c) and (c)(6) of 10 CFR 431.304
that referenced manufacturers.
In light of the absence of any
comments regarding these proposals,
DOE is adopting them as part of this
final rule.
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
D. Performance-Based Test Procedures
for Panels and Doors of Walk-In Coolers
and Freezers
1. Panels
As described above, WICF panels
must meet requirements for foam
insulation R-values based on ASTM
C518–04 testing incorporated in 10 CFR
431.304. Additionally, the test
procedure at Appendix A to Subpart R
of Part 431 (Uniform Test Method for
the Measurement of Energy
Consumption of the Components of
Envelopes of Walk-In Coolers and WalkIn Freezers) establishes the method and
metrics by which the energy
consumption (for envelope components)
or efficiency (for refrigeration
components) may be measured; this
includes floor and non-floor panels.
Sections 4.2 and 4.3 of that procedure
establish the calculation procedures that
result in a thermal conductivity, Uvalue, energy use metric for floor and
non-floor panels, and sections 5.1 and
5.2 establish the methods used to make
the measurements. Section 5.1
incorporates by reference ASTM C1363–
05 Standard Test Method for Thermal
Performance of Building Materials and
Envelope Assemblies by Means of a Hot
Box Apparatus; section 5.2 incorporates
by reference Annex C Determination of
the aged values of thermal resistance
and thermal conductivity of DIN EN
13164 and DIN EN 13165.
While ASTM C518–04 testing is
intended to establish the thermal
resistance of the center of a WICF panel,
the required testing under ASTM
C1363–05 is intended to capture the
overall thermal transmittance of a WICF
panel, including thermal bridges and
edge effects. (Thermal transmittance is
the reciprocal of thermal resistance.)
Similar to ASTM C518–04, DIN EN
13164/13165 testing is intended to
measure the thermal resistance of the
center of a WICF panel; however, DIN
EN 13164/13165 also captures the
effects of foam aging on a panel’s
thermal resistance.
In response to the September 2013
standards NOPR, the Department
received a number of comments
regarding the WICF panel test
procedure. The comments largely
presented two concerns: test burden and
the availability of laboratories to
conduct these tests. In these comments,
multiple manufacturers suggested that
no independent laboratories were
capable of conducting DIN EN 13164/
13165 tests, and that only two were
capable of conducting ASTM C1363–05
tests. Several comments suggested that
the cost of these tests could be
excessive, particularly given the limited
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
27405
availability of independent test
laboratories to perform these specific
tests. (See section III.D. of the February
2014 SNOPR for a full comment
summary.)
Responding to these comments, DOE
proposed in the February 2014 SNOPR
to remove the portions of the test
procedure that referenced ASTM
C1363–04 and DIN EN 13164/13165
testing; this would remove sections 4.2,
4.3, 5.1 and 5.2 from 10 CFR 431,
Appendix A of Subpart R. 79 FR at
9837.
DOE received several comments
regarding its proposal to remove these
portions of the WICF test procedure.
Bally supported the proposal to remove
these test portions in order to reduce
testing burden. (Bally, No. 93 at p. 4)
AHRI also supported their removal.
(AHRI, No. 100 at p. 8). AHRI further
recommended that DOE ‘‘translate the
proposed remaining test standard ASTM
C518–04 to prescriptive requirements
which would eliminate testing
requirements.’’ (AHRI, No. 100 p. 8) In
contrast to these industry commenters,
ASAP, et al. suggested that DOE should
not remove the sections that require
ASTM C1363–04 and DIN EN 13164/
13165 testing. (ASAP, et al., No. 99 at
p. 4) ASAP, et al. stated that DOE would
not be able to adopt the performancebased standards based on U-values that
were proposed in the September 2013
standards NOPR and that the estimated
energy savings calculated in the
September 2013 standards NOPR could
therefore not be achieved. (ASAP, et al.,
No. 99 at p. 4) Additionally, ASAP, et
al. believe that the U-value metric
fulfills the requirement that DOE
establish ‘‘performance-based
standards’’ for walk-ins. Finally, ASAP,
et al. suggested that DOE allow use of
an AEDM that can accurately predict the
overall U-value for panels, thereby
reducing test burden. (ASAP, et al., No.
99 at p. 4)
DOE acknowledges that the estimated
savings in the September 2013
standards NOPR were based on Uvalues. DOE also had not been aware of
the considerable difficulties that
affected parties would likely face in
attempting to locate testing laboratories
to assist them in performing the test in
anticipation of any standards with
which manufacturers would need to
comply. Given these difficulties, in
DOE’s view, modifications to the
procedure are necessary to ensure that
some method of measuring panel
efficiency can be readily conducted. The
prescriptive requirements established by
EPCA for WICF panels are effectively
performance-based, as they regulate the
thermal performance of WICF panels
E:\FR\FM\13MYR2.SGM
13MYR2
27406
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
and require a certain minimal level of
performance be met. (DOE refers all
interested parties to the standards
rulemaking for updated estimates of the
energy savings estimates, which will
now be based on the R-value
requirements (and U-factor for doors)).
With respect to ASAP, et al.’s suggestion
to allow use of an AEDM to predict Ufactor, DOE notes that AEDMs must be
validated by testing results and believes
that even this minimal amount of testing
would be burdensome in light of the
lack of testing laboratories who can
perform the testing required to obtain a
U-value. In response to AHRI’s request
to translate the ASTM C518–04 test
standard into prescriptive requirements,
DOE notes that the required minimum
R-value for panels is effectively a
performance standard set forth by EPCA
(42 U.S.C. 6313(f)(1)(C)) and the use of
ASTM C518–04 for measuring the Rvalue is mandated by EPCA. (42 U.S.C.
6314(a)(9)(A))
2. Doors
With respect to the test procedure for
doors, DOE is adopting several minor
changes to section 5.3 for clarification
purposes only. DOE is modifying the
titles of section 5.3(a)(2) from ‘‘Internal
conditions’’ to ‘‘Cold-side conditions’’
and section 5.3(a)(3) from ‘‘External
conditions’’ to ‘‘Warm-side conditions.’’
The terms ‘‘internal’’ and ‘‘external’’ are
irrelevant in the context of the testing
apparatus described in NFRC 100[E0A1]
(incorporated by reference). DOE is also
making explicit the surface convective
heat transfer coefficients referred to in
paragraph (a)(1); these values are 30
Watts per meter-Kelvin (W/m-K) for the
cold side of the hot box apparatus and
7.7 W/m-K for the warm side. This
change only clarifies these terms. These
values are specified in ASTM C1199–09
Standard Test Method for Measuring the
Steady-State Thermal Transmittance of
Fenestration Systems Using Hot Box
Methods which is referred to by NFRC
100[E0A1]. These changes were also
proposed as part of the February 2014
SNOPR.
In response to this SNOPR, AHRI
indicated that they do not object to the
proposed clarifications. (AHRI, No. 100
at p. 8) Bally, however, commented that
they do not agree with evaluating nondisplay doors according to NFRC 100.
(Bally, No. 93 at p. 4) Bally contended
that ‘‘surface convective heat transfer
coefficients, in metric units [are] quite
alien to us since convective heat transfer
is such a small part of heat transfer
except in high heat flow regions like
fenestration.’’ (Bally, No. 93 at p. 4)
Bally also suggested that DOE’s
procedure based on NFRC 100 should
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
be dropped or that, ‘‘at a minimum,
exclude view port windows with a total
window surface area of 340 square
inches or less.’’ (Bally, No. 93 at p. 4)
AHRI also suggested that non-display
doors should have the option of meeting
R-value-based standards. (AHRI, No.
100 at p. 8)
DOE acknowledges that doors are a
type of fenestration; hence, DOE
believes that NFRC 100 is appropriate
for doors. The surface convective
coefficients stipulated in ASTM C1199–
09 (which is referenced by NFRC 100 by
way of NFRC 102) are intended to
ensure testing repeatability by
establishing consistent boundary
conditions. DOE reiterates that the
changes proposed in the February 2014
SNOPR were for clarification purposes
only, and that the substance of the test
method is unchanged. With respect to
Bally’s suggestion that NFRC 100 be
dropped or its application substantially
modified, DOE infers that Bally is
referring to NFRC 100 as a whole, and
not just the convective surface
coefficients specifically. DOE cannot
abandon the use of NFRC 100 for
measuring the performance of WICF
doors without a viable alternative and
Bally has offered none. With regards to
non-display doors that include a small
viewing port window, the presence of
the window means that the information
gained by measuring an overall door Ufactor is all the more valuable given the
thermal bridging the window creates. As
previously stated, capturing the thermal
bridging effects of all components in a
door is critical in accurately reflecting
its energy consumption due to the
nature of fenestration. DOE is also
reluctant to make an exception for nondisplay doors or doors with port
windows, as it could potentially
encourage manufacturers to add small
windows to all of their doors, which
would relieve them from having to meet
performance standards. Should this
occur, there would likely be an increase
in energy consumption due to thermal
bridging. Accordingly, DOE is leaving
the NFRC 100 test in place for doors and
display panels while clarifying the
convective surface coefficients to be
used for testing.
With respect to AHRI’s suggestion
that DOE apply R-value based standards
to non-display doors, DOE notes that the
scope of its proposal addresses only
issues related to AEDMs as they would
apply to walk-ins along with related test
procedure requirements. Comments on
the standards to which non-display
doors should be held fall outside of that
scope. Furthermore, even if DOE were to
consider the possibility of applying an
R-value-based standard—or any other
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
standard—a non-display door includes
more components in its assembly than
a wall panel, which would make the
consideration of potential standards for
these items considerably more complex.
According to the definition for ‘‘door’’
found in 10 CFR 431.302, the door
‘‘includes the door panel, glass, framing
materials, door plug, mullion, and any
other elements that form the door or
part of its connection to the wall.’’ As
such, there are more opportunities for
thermal transmission. DOE believes that
for doors (both display and non-display)
capturing these effects by way of an
overall U-factor through use of the
NFRC 100 test procedure is critical for
accurately reflecting the energy
consumption of these WICF
components. As a result, DOE is
declining to adopt AHRI’s suggestion in
the context of today’s rulemaking.
E. Sampling Plan
In order to determine a rating for
certifying compliance and making
energy use representations, DOE
requires manufacturers to test each basic
model in accordance with the
applicable DOE test procedure and
apply the sampling plan. DOE proposed
a sampling plan for walk-ins consistent
with other commercial equipment
regulated under EPCA that would be
included a proposed § 429.53 of Subpart
B of 10 CFR Part 429. For consistency
with other commercial equipment
regulated under EPCA, DOE proposed
that manufacturers test a sample of
sufficient size of a WICF component
basic model to ensure a representative
rating—but not less than two units as
prescribed in 10 CFR 429.11. DOE
proposed that any represented energy
consumption values of a walk-in basic
model component shall be greater than
or equal to the higher of the mean of the
sample or the 95 percent upper
confidence limit (UCL) of the true mean
divided by 1.05. Additionally, DOE
proposed that any represented energy
efficiency values of a walk-in basic
model component shall be the less than
or equal to the lower of the mean of the
sample or the 95 percent lower
confidence limit (LCL) of the true mean
divided by 0.95. DOE did not receive
any comments on this proposal and so
is adopting the proposed sampling
requirements.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Order 12866
The Office of Management and Budget
has determined that test procedure
rulemakings do not constitute
‘‘significant regulatory actions’’ under
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
section 3(f) of Executive Order 12866,
‘‘Regulatory Planning and Review,’’ 58
FR 51735 (Oct. 4, 1993). Accordingly,
this regulatory action was not subject to
review under the Executive Order by the
Office of Information and Regulatory
Affairs (OIRA) in the Office of
Management and Budget (OMB).
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601, et seq.) requires the
preparation of a final regulatory
flexibility analysis (FRFA) for any rule
that by law must be proposed for public
comment, unless the agency certifies
that the rule, if promulgated, will not
have a significant economic impact on
a substantial number of small entities.
As required by Executive Order 13272,
‘‘Proper Consideration of Small Entities
in Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s Web site: www.gc.doe.gov.
DOE reviewed the test procedures
promulgated in today’s final rule under
the provisions of the Regulatory
Flexibility Act (RFA) and the policies
and procedures published on February
19, 2003.
As discussed in more detail below,
DOE found that the provisions of this
rule will not result in increased testing
and/or reporting burden for
manufacturers and permit additional
manufacturers to use an AEDM for the
purposes of rating and certifying their
equipment, which would reduce
manufacturer testing burden.
Accordingly, based on DOE’s review,
manufacturers are unlikely to
experience an increased financial
burden because of the provisions
established in today’s final rule.
First, DOE is allowing manufacturers
walk-in refrigeration systems to use an
AEDM to determine the energy
consumption of their products.
Previously, no walk-in manufacturers
were eligible to use an AEDM. Today’s
rule adopts voluntary methods for
determining compliance in lieu of
conducting actual physical testing—
which, in turn, are expected to reduce
the testing burden of walk-in
manufacturers who elect to use an
AEDM. Furthermore, the validation
requirements for an AEDM do not
require more testing than that which is
already required under DOE’s
regulations at 10 CFR 429.12. While the
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
Department believes that permitting
greater use of AEDMs will reduce the
affected manufacturer’s test burden,
their use is at the manufacturer’s
discretion. If, as a result of any of the
regulations herein, a manufacturer
believes that use of an AEDM would
increase rather than decrease their
financial burden compared to
performing actual testing, the
manufacturer may choose not to employ
the method. Should a manufacturer
choose to abstain from using an AEDM,
this provision would not apply and the
manufacturer would continue to remain
subject to the requirements of the
applicable DOE test procedures for
walk-ins, which would result in no
change in burden from that which was
already required.
DOE is also codifying alternate
methods for determining the
compliance of individual walk-in
refrigeration system components, which
should further decrease the burden of
the future test procedure for walk-in
refrigeration systems. DOE is currently
undertaking an energy conservation
standards rulemaking to set
performance standards for walk-in
components, including panels, doors,
and refrigeration systems. Under the
provisions of the March 2011 Final Rule
(76 FR 12422 (March 7, 2011)), the
‘‘component’’ manufacturer would be
required to certify compliance with
these standards once any applicable
compliance date is reached—however,
there were no provisions for
manufacturers of individual
refrigeration components (i.e., unit
coolers and condensing units) to ensure
the compliance of their components
with an energy conservation standard
because the proposed refrigeration
system standard would apply to the
whole refrigeration system. These
manufacturers could potentially have
incurred a large burden by having to test
all combinations of the components
they wished to distribute. Additionally,
manufacturers of only one type of
component could have been
inadvertently prevented from selling
their equipment because there would
have been no available compliance
mechanism. This rule establishes an
alternate testing methodology by which
manufacturers of either component of a
walk-in refrigeration system—the
condensing unit or the unit cooler—may
determine compliance with the
applicable standard without having to
test every combination of components
that they produce. DOE believes this
approach will significantly reduce the
testing burden for all manufacturers,
including small businesses.
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
27407
Finally, DOE is adopting several
clarifications and modifications to the
existing test procedures that are
intended to further reduce testing
burden. For example, DOE is not
requiring the use of long-term thermal
resistance testing of foam and is
allowing manufacturers to test their
panels based only on testing to ASTM
C518, a simpler test method that is
already in use in the industry. For a
complete list of test procedure
modifications, see section III.
For the reasons enumerated above,
DOE is certifying that this final rule will
not have a significant impact on a
substantial number of small entities.
C. Review Under the Paperwork
Reduction Act of 1995
A walk-in manufacturer must certify
to DOE that its equipment complies
with all applicable energy conservation
standards. To certify compliance,
manufacturers must test their products
according to the DOE test procedures for
walk-in equipment, including any
amendments adopted for those test
procedures. DOE has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including walkin coolers and freezers. 76 FR 12422
(March 7, 2011). The collection-ofinformation requirement for
certification and recordkeeping is
subject to review and approval by OMB
under the Paperwork Reduction Act
(PRA). This requirement has been
approved by OMB under OMB control
number 1910–1400. Public reporting
burden for the certification is estimated
to average 20 hours per response,
including the time for reviewing
instructions, searching existing data
sources, gathering and maintaining the
data needed, and completing and
reviewing the collection of information.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
DOE is amending its test procedures
and related provisions for walk-ins.
DOE has determined that this rule falls
into a class of actions that are
categorically excluded from review
under the National Environmental
Policy Act of 1969 (42 U.S.C. 4321 et
seq.) and DOE’s implementing
regulations at 10 CFR part 1021. This
E:\FR\FM\13MYR2.SGM
13MYR2
27408
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
rule amends the existing test procedures
without affecting the amount, quality, or
distribution of energy usage, and,
therefore, will not result in any
environmental impacts. Thus, this
rulemaking is covered by Categorical
Exclusion A5 under 10 CFR part 1021,
subpart D, which applies to any
rulemaking that interprets or amends an
existing rule without changing the
environmental effect of that rule.
Accordingly, neither an environmental
assessment nor an environmental
impact statement is required.
tkelley on DSK3SPTVN1PROD with RULES2
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 10, 1999), imposes
certain requirements on Federal
agencies formulating and implementing
policies or regulations that preempt
State law or that have federalism
implications. The Executive Order
requires agencies to examine the
constitutional and statutory authority
supporting any action that would limit
the policymaking discretion of the
States, and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have federalism implications. On March
14, 2000, DOE published a statement of
policy describing the intergovernmental
consultation process it will follow in the
development of such regulations. (65 FR
13735) DOE has examined this rule and
has tentatively determined that it would
not have a substantial direct effect on
the States, on the relationship between
the national government and the States,
or on the distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of
today’s rule. States can petition DOE for
exemption from such preemption to the
extent, and based on criteria, set forth in
EPCA. (42 U.S.C. 6297) No further
action is required by Executive Order
13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Regarding the
review required by section 3(a), section
3(b) of Executive Order 12988
specifically requires that Executive
agencies make every reasonable effort to
ensure that the regulation: (1) Clearly
specifies the preemptive effect, if any;
(2) clearly specifies any effect on
existing Federal law or regulation; (3)
provides a clear legal standard for
affected conduct while promoting
simplification and burden reduction; (4)
specifies the retroactive effect, if any; (5)
adequately defines key terms; and (6)
addresses other important issues
affecting clarity and general
draftsmanship under any guidelines
issued by the Attorney General. Section
3(c) of Executive Order 12988 requires
Executive agencies to review regulations
in light of applicable standards in
sections 3(a) and 3(b) to determine
whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, the rule meets
the relevant standards of Executive
Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. (Pub. L. 104–4, sec. 201,
codified at 2 U.S.C. 1531) For regulatory
actions likely to result in a rule that may
cause the expenditure by State, local,
and Tribal governments, in the
aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a)–(b)) UMRA
also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect them. On
March 18, 1997, DOE published a
statement of policy on its process for
intergovernmental consultation under
UMRA. (62 FR 12820) (This policy is
also available at https://www.energy.gov/
gc.) DOE examined today’s rule
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
according to UMRA and its statement of
policy and has determined that the rule
contains neither an intergovernmental
mandate, nor a mandate that may result
in the expenditure by State, local, and
Tribal governments, in the aggregate, or
by the private sector, of $100 million or
more in any year. Accordingly, no
further assessment or analysis is
required under UMRA.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
rule would not have any impact on the
autonomy or integrity of the family as
an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
Pursuant to Executive Order 12630,
‘‘Governmental Actions and Interference
with Constitutionally Protected Property
Rights,’’ 53 FR 8859 (March 18, 1988),
DOE has determined that this rule
would not result in any takings that
might require compensation under the
Fifth Amendment to the U.S.
Constitution.
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516, note)
provides for Federal agencies to review
most disseminations of information to
the public under information quality
guidelines established by each agency
pursuant to general guidelines issued by
OMB. OMB’s guidelines were published
at 67 FR 8452 (Feb. 22, 2002), and
DOE’s guidelines were published at 67
FR 62446 (Oct. 7, 2002). DOE has
reviewed today’s rule under the OMB
and DOE guidelines and has concluded
that it is consistent with applicable
policies in those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OIRA at OMB, a
Statement of Energy Effects for any
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgates or is
expected to lead to promulgation of a
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of today’s final rule.
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Reporting and recordkeeping
requirements.
10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Incorporation by reference, Reporting
and recordkeeping requirements.
Issued in Washington, DC, on May 5, 2014.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
For the reasons stated in the
preamble, DOE is amending parts 429
and 431 of Chapter II, Subchapter D of
Title 10, Code of Federal Regulations, as
set forth below:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
2. Section 429.53 is revised to read as
follows:
■
§ 429.53 Walk-in coolers and walk-in
freezers.
(a) Determination of represented
value—(1) Refrigeration equipment:
Manufacturers must determine the
represented value, which includes the
certified rating, for each basic model of
walk-in cooler or freezer refrigeration
equipment, either by testing, in
conjunction with the applicable
sampling provisions, or by applying an
AEDM satisfying the criteria provided at
§ 429.70(f)(1).
(i) Units to be tested. (A) If the
represented value for a given basic
model is determined through testing,
the general requirements of § 429.11
apply; and
(B) For each basic model selected for
testing, a sample of sufficient size shall
be randomly selected and tested to
ensure that—
(1) Any represented value of energy
consumption or other measure of energy
use of a basic model for which
consumers would favor lower values
shall be greater than or equal to the
higher of:
(i) The mean of the sample, where:
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
¯
and, x is the sample mean; n is the
number of samples; and xi is the ith
sample; or,
(ii) The upper 95 percent confidence
limit (UCL) of the true mean divided by
1.05, where:
¯
And x is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.95 is the t
statistic for a 95% one-tailed confidence
interval with n¥1 degrees of freedom
(from Appendix A to subpart B). And,
(2) Any represented value of energy
efficiency or other measure of energy
consumption of a basic model for which
consumers would favor higher values
shall be less than or equal to the lower
of:
(i) The mean of the sample, where:
¯
And, x is the sample mean; n is the
number of samples; and xi is the ith
sample; or,
(ii) The lower 95 percent confidence
limit (LCL) of the true mean divided by
0.95, where:
¯
And x is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.95 is the t
statistic for a 95% one-tailed confidence
interval with n¥1 degrees of freedom
(from Appendix A to subpart B).
(ii) Alternative efficiency
determination methods. In lieu of
testing, a represented value of efficiency
or consumption for a basic model of a
walk-in cooler or freezer refrigeration
system must be determined through the
application of an AEDM pursuant to the
requirements of § 429.70 and the
provisions of this section, where:
(A) Any represented value of energy
consumption or other measure of energy
use of a basic model for which
consumers would favor lower values
shall be greater than or equal to the
output of the AEDM and less than or
equal to the Federal standard for that
basic model; and
(B) Any represented value of energy
efficiency or other measure of energy
consumption of a basic model for which
consumers would favor higher values
shall be less than or equal to the output
E:\FR\FM\13MYR2.SGM
13MYR2
ER13MY14.003
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101, et seq.), DOE must
comply with all laws applicable to the
former Federal Energy Administration,
including section 32 of the Federal
Energy Administration Act of 1974
(Pub. L. 93–275), as amended by the
Federal Energy Administration
Authorization Act of 1977 (Pub. L. 95–
70). (15 U.S.C. 788; FEAA) Section 32
provides in relevant part that, where a
rule authorizes or requires use of
commercial standards, the notice of the
final rule must inform the public of the
use and background of such standards.
In addition, section 32(c) requires DOE
to consult with the Attorney General
and the Chairman of the Federal Trade
Commission (FTC) concerning the
impact of the commercial or industry
standards on competition. Today’s rule
does not incorporate any commercial
standards. The commercial standards
discussed in today’s rulemaking were
already adopted in the Test Procedures
for Walk-In Coolers and Walk-In
Freezers, which was published in the
Federal Register on April 15, 2011. 76
FR 21580. DOE conducted a review
under Section 32 of the Federal Energy
Administration Act of 1974 in the April
2011 test procedure final rule. 76 FR
21580, 21604.
10 CFR Part 429
ER13MY14.001 ER13MY14.002
tkelley on DSK3SPTVN1PROD with RULES2
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
List of Subjects
ER13MY14.000
final rule, and that: (1) Is a significant
regulatory action under Executive Order
12866, or any successor order; and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy; or (3) is designated by the
Administrator of OIRA as a significant
energy action. For any significant energy
action, the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use
should the rule be implemented, and of
reasonable alternatives to the action and
their expected benefits on energy
supply, distribution, and use.
DOE has reviewed today’s rule and
determined, it would not have a
significant adverse effect on the supply,
distribution, or use of energy, nor has it
been designated as a significant energy
action by the Administrator of OIRA.
Therefore, it is not a significant energy
action, and, accordingly, DOE has not
prepared a Statement of Energy Effects
for this rulemaking.
27409
¯
and, x is the sample mean; n is the
number of samples; and xi is the ith
sample; or,
(ii) The upper 95 percent confidence
limit (UCL) of the true mean divided by
1.05, where:
¯
And, x is the sample mean; n is the
number of samples; and xi is the ith
sample; or,
(ii) The lower 95 percent confidence
limit (LCL) of the true mean divided by
0.95, where:
¯
And x is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.95 is the t
statistic for a 95% one-tailed confidence
interval with n¥1 degrees of freedom
(from Appendix A to subpart B).
(b) Certification reports. (1) The
requirements of § 429.12 are applicable
to manufacturers of the components of
walk-in coolers and freezers (WICFs)
listed in paragraph (b)(2) of this section,
and;
(2) Pursuant to § 429.12(b)(13), a
certification report shall include the
following public product-specific
information:
(i) For WICF doors: The door type, Rvalue of the door insulation, and a
declaration that the manufacturer has
incorporated the applicable design
requirements. In addition, for those
WICFs with transparent reach-in doors
and windows: The glass type of the
doors and windows (e.g., double-pane
with heat reflective treatment, triplepane glass with gas fill), and the power
draw of the antisweat heater in watts
per square foot of door opening.
(ii) For WICF panels: The R-value of
the insulation (except for glazed
portions of the doors or structural
members).
(iii) For WICF refrigeration systems:
The motor’s purpose (i.e., evaporator fan
motor or condenser fan motor), the
horsepower, and a declaration that the
manufacturer has incorporated the
applicable design requirements.
3. Section 429.70 is amended by
adding paragraph (f) to read as follows:
tkelley on DSK3SPTVN1PROD with RULES2
■
¯
And x is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.95 is the t
statistic for a 95% one-tailed confidence
interval with n¥1 degrees of freedom
(from Appendix A to subpart B). And,
(2) Any represented value of energy
efficiency or other measure of energy
consumption of a basic model for which
consumers would favor higher values
shall be less than or equal to the lower
of:
(i) The mean of the sample, where:
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
§ 429.70 Alternative methods for
determining energy efficiency or energy
use.
*
*
*
*
*
(f) Alternative efficiency
determination method (AEDM) for walkin refrigeration equipment—
(1) Criteria an AEDM must satisfy. A
manufacturer may not apply an AEDM
to a basic model to determine its
efficiency pursuant to this section
unless:
(i) The AEDM is derived from a
mathematical model that estimates the
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
energy efficiency or energy
consumption characteristics of the basic
model as measured by the applicable
DOE test procedure;
(ii) The AEDM is based on
engineering or statistical analysis,
computer simulation or modeling, or
other analytical evaluation of
performance data; and
(iii) The manufacturer has validated
the AEDM, in accordance with
paragraph (f)(2) of this section.
(2) Validation of an AEDM. Before
using an AEDM, the manufacturer must
validate the AEDM’s accuracy and
reliability as follows:
(i) The manufacturer must select at
least the minimum number of basic
models for each validation class
specified in paragraph (f)(2)(iv) of this
section to which the particular AEDM
applies. Test a single unit of each basic
model in accordance with paragraph
(f)(2)(iii) of this section. Using the
AEDM, calculate the energy use or
energy efficiency for each of the selected
basic models. Compare the results from
the single unit test and the AEDM
output according to paragraph (f)(2)(ii)
of this section. The manufacturer is
responsible for ensuring the accuracy
and repeatability of the AEDM.
(ii) Individual model tolerances. (A)
The predicted efficiency for each model
calculated by applying the AEDM may
not be more than five percent greater
than the efficiency determined from the
corresponding test of the model.
(B) The predicted energy efficiency
for each model calculated by applying
the AEDM must meet or exceed the
applicable federal energy conservation
standard.
(iii) Additional test unit requirements.
(A) Each AEDM must be supported by
test data obtained from physical tests of
current models; and
(B) Test results used to validate the
AEDM must meet or exceed current,
applicable Federal standards as
specified in part 431 of this chapter;
(C) Each test must have been
performed in accordance with the
applicable DOE test procedure with
which compliance is required at the
time the basic model is distributed in
commerce; and
(D) For rating WICF refrigeration
system components, an AEDM may not
simulate or model portions of the
system that are not required to be tested
by the DOE test procedure. That is, if
the test results used to validate the
AEDM are for either a unit cooler only
or a condensing unit only, the AEDM
must estimate the system rating using
the nominal values specified in the DOE
test procedure for the other part of the
refrigeration system.
E:\FR\FM\13MYR2.SGM
13MYR2
ER13MY14.005 ER13MY14.006
of the AEDM and greater than or equal
to the Federal standard for that basic
model.
(iii) If the represented value of a
refrigeration system was determined
using the unit cooler testing provisions
at 10 CFR 431.304(c)(12), that
represented value may be used for all
refrigeration systems containing that
unit cooler irrespective of whether such
equipment is sold separately or as part
of a matched refrigeration system.
However, for any representations of
matched-system efficiency that exceed
the refrigeration system rating as
determined by the unit cooler testing
provisions at 10 CFR 431.304(c)(12) and
for which a manufacturer wishes to
make representations of the moreefficient rating, then the matched
refrigeration system must be tested
separately in accordance with the DOE
test procedure for matched systems and
applicable sampling plan.
(2) WICF components other than
those specified in (a)(1) of this section—
(i) Units to be tested.
(A) The general requirements of
§ 429.11 apply; and
(B) For each basic model selected for
testing, a sample of sufficient size shall
be randomly selected and tested to
ensure that—
(1) Any represented value of energy
consumption or other measure of energy
use of a basic model for which
consumers would favor lower values
shall be greater than or equal to the
higher of:
(i) The mean of the sample, where:
ER13MY14.007
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
ER13MY14.004
27410
27411
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
(iv) WICF refrigeration validation
classes.
Minimum number
of distinct models
that must be tested
Validation class
Dedicated Condensing, Medium Temperature, Indoor System .....................................................................................................
Dedicated Condensing, Medium Temperature, Outdoor System 1 ................................................................................................
Dedicated Condensing, Low Temperature, Indoor System ...........................................................................................................
Dedicated Condensing, Low Temperature, Outdoor System 2 ......................................................................................................
Unit Cooler connected to a Multiplex Condensing Unit, Medium Temperature .............................................................................
Unit Cooler connected to a Multiplex Condensing Unit, Low Temperature ...................................................................................
Medium Temperature, Indoor Condensing Unit .............................................................................................................................
Medium Temperature, Outdoor Condensing Unit 3 ........................................................................................................................
Low Temperature, Indoor Condensing Unit ...................................................................................................................................
Low Temperature, Outdoor Condensing Unit 4 ..............................................................................................................................
2
2
2
2
2
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
tkelley on DSK3SPTVN1PROD with RULES2
1 AEDMs validated for dedicated condensing, medium temperature, outdoor systems may be used to determine representative values for dedicated condensing, medium temperature, indoor systems, and additional validation testing is not required. AEDMs validated for only dedicated
condensing, medium temperature, indoor systems may not be used to determine representative values for dedicated condensing, medium temperature, outdoor systems.
2 AEDMs validated for dedicated condensing, low temperature, outdoor systems may be used to determine representative values for dedicated
condensing, low temperature, indoor systems, and additional validation testing is not required. AEDMs validated for only dedicated condensing,
low temperature, indoor systems may not be used to determine representative values for dedicated condensing, low temperature, outdoor systems.
3 AEDMs validated for medium temperature, outdoor condensing units may be used to determine representative values for medium temperature, indoor condensing units, and additional validation testing is not required. AEDMs validated for only medium temperature, indoor condensing
units may not be used to determine representative values for medium temperature, outdoor condensing units.
4 AEDMs validated for low temperature, outdoor condensing units may be used to determine representative values for low temperature, indoor
condensing units, and additional validation testing is not required. AEDMs validated for only low temperature, indoor condensing units may not
be used to determine representative values for low temperature, outdoor condensing units.
(3) AEDM records retention
requirements. If a manufacturer has
used an AEDM to determine
representative values pursuant to this
section, the manufacturer must have
available upon request for inspection by
the Department records showing:
(i) The AEDM, including the
mathematical model, the engineering or
statistical analysis, and/or computer
simulation or modeling that is the basis
of the AEDM;
(ii) Equipment information, complete
test data, AEDM calculations, and the
statistical comparisons from the units
tested that were used to validate the
AEDM pursuant to paragraph (f)(2) of
this section; and
(iii) Equipment information and
AEDM calculations for each basic model
to which the AEDM has been applied.
(4) Additional AEDM requirements. If
requested by the Department the
manufacturer must perform at least one
of the following:
(i) Conduct simulations before
representatives of the Department to
predict the performance of particular
basic models of the product to which
the AEDM was applied;
(ii) Provide analyses of previous
simulations conducted by the
manufacturer; or
(iii) Conduct certification testing of
basic models selected by the
Department.
(5) AEDM verification testing. DOE
may use the test data for a given
individual model generated pursuant to
§ 429.104 to verify the certified rating
determined by an AEDM as long as the
following process is followed:
(i) Selection of units. DOE will obtain
units for test from retail, where
available. If units cannot be obtained
from retail, DOE will request that a unit
be provided by the manufacturer.
(ii) Lab requirements. DOE will
conduct testing at an independent,
third-party testing facility of its
choosing. In cases where no third-party
laboratory is capable of testing the
equipment, it may be tested at a
manufacturer’s facility upon DOE’s
request.
(iii) Manufacturer participation.
Testing will be performed without
manufacturer representatives on-site.
(iv) Testing. All verification testing
will be conducted in accordance with
the applicable DOE test procedure, as
well as each of the following to the
extent that they apply:
(A) Any active test procedure waivers
that have been granted for the basic
model;
(B) Any test procedure guidance that
has been issued by DOE;
(C) If during test set-up or testing, the
lab indicates to DOE that it needs
additional information regarding a given
basic model in order to test in
accordance with the applicable DOE test
procedure, DOE may organize a meeting
between DOE, the manufacturer and the
lab to provide such information.
(D) At no time during the process may
the lab communicate directly with the
manufacturer without DOE present.
(v) Failure to meet certified rating. If
a model tests worse than its certified
rating by an amount exceeding the
tolerance prescribed in paragraph
(f)(5)(vi) of this section, DOE will notify
the manufacturer. DOE will provide the
manufacturer with all documentation
related to the test set up, test conditions,
and test results for the unit. Within the
timeframe allotted by DOE, the
manufacturer may then present all
claims regarding testing validity.
(vi) Tolerances. for efficiency metrics,
the result from a DOE verification test
must be greater than or equal to the
certified rating × (1 ¥ the applicable
tolerance).
Equipment
Metric
Applicable
tolerance
Refrigeration systems (including components) ...............................................................................
AWEF ....................................
5%
VerDate Mar<15>2010
19:17 May 12, 2014
Jkt 232001
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
E:\FR\FM\13MYR2.SGM
13MYR2
27412
(vii) Invalid rating. If, following
discussions with the manufacturer and
a retest where applicable, DOE
determines that the testing was
conducted appropriately in accordance
with the DOE test procedure, the rating
for the model will be considered
invalid. Pursuant to 10 CFR 429.13(b),
DOE may require a manufacturer to
conduct additional testing as a remedial
measure.
PART 431—ENERGY CONSERVATION
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
4. The authority citation for part 431
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
§ 431.303
[Amended]
5. Section 431.303 is amended by:
a. Removing and reserving paragraph
(c)(2);
■ b. Removing paragraph (d); and
■ c. Redesignating paragraph (e) as (d).
■
■
6. Section 431.304 is amended by:
a. Revising paragraphs (b)
introductory text, and (b)(3) through (6);
■ b. Adding paragraph (b)(7);
■ c. Revising paragraphs (c)
introductory text, and (c)(3) through (6);
■ d. Redesignating paragraphs (c)(7)
through (c)(10) as paragraphs (c)(8)
through (c)(11), respectively;
■ e. Adding new paragraph (c)(7);
■ f. Revising redesignated paragraph
(c)(8), (c)(9) and (c)(10); and,
■ g. Adding paragraph (c)(12).
The revisions and additions read as
follows:
■
■
§ 431.304 Uniform test method for the
measurement of energy consumption of
walk-in coolers and walk-in freezers.
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
(b) This paragraph (b) shall be used
for the purposes of certifying
compliance with the applicable R-value
energy conservation standards for
panels until compliance with amended
standards is required.
*
*
*
*
*
(3) When calculating the R value for
freezers, the K factor of the foam at 20
± 1 degrees Fahrenheit (average foam
temperature) shall be used. Test results
from a test sample 1 ± 0.1-inches in
thickness may be used to determine the
R value of panels with various foam
thickness as long as the foam is of the
same final chemical form.
(4) When calculating the R value for
coolers, the K factor of the foam at 55
± 1 degrees Fahrenheit (average foam
temperature) shall be used. Test results
from a test sample 1 ± 0.1-inches in
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
thickness may be used to determine the
R value of panels with various foam
thickness as long as the foam is of the
same final chemical form.
(5) Foam shall be tested after it is
produced in its final chemical form.
(For foam produced inside of a panel
(‘‘foam-in-place’’), ‘‘final chemical
form’’ means the foam is cured as
intended and ready for use as a finished
panel. For foam produced as board stock
(typically polystyrene), ‘‘final chemical
form’’ means after extrusion and ready
for assembly into a panel or after
assembly into a panel.) Foam from
foam-in-place panels must not include
any structural members or non-foam
materials. Foam produced as board
stock may be tested prior to its
incorporation into a final panel. A test
sample 1 ± 0.1-inches in thickness must
be taken from the center of a panel and
any protective skins or facers must be
removed. A high-speed band-saw and a
meat slicer are two types of
recommended cutting tools. Hot wire
cutters or other heated tools must not be
used for cutting foam test samples. The
two surfaces of the test sample that will
contact the hot plate assemblies (as
defined in ASTM C518 (incorporated by
reference, see § 431.303)) must both
maintain ±0.03 inches flatness tolerance
and also maintain parallelism with
respect to one another within ±0.03
inches. Testing must be completed
within 24 hours of samples being cut for
testing.
(6) Internal non-foam member and/or
edge regions shall not be considered in
ASTM C518 testing.
(7) For panels consisting of two or
more layers of dissimilar insulating
materials (excluding facers or protective
skins), test each material as described in
paragraphs (c)(1) through (6) of this
section. For a panel with N layers of
insulating material, the overall R-Value
shall be calculated as follows:
Where:
ki is the k factor of the ith material as
measured by ASTM C518,
ti is the thickness of the ith material
that appears in the panel, and
N is the total number of material
layers that appears in the panel.
(c) This paragraph (c) shall be used for
any representations of energy efficiency
or energy use starting on October 12,
2011, and to certify compliance to the
energy conservation standards of the Rvalue of panels on or after the
compliance date of amended energy
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
conservation standards for walk-in
cooler and freezers.
*
*
*
*
*
(3) For calculating the R value for
freezers, the K factor of the foam at 20
± 1 degrees Fahrenheit (average foam
temperature) shall be used. Test results
from a test sample 1 ± 0.1-inches in
thickness may be used to determine the
R value of panels with various foam
thickness as long as the foam is of the
same final chemical form.
(4) For calculating the R value for
coolers, the K factor of the foam at 55
± 1 degrees Fahrenheit (average foam
temperature) shall be used. Test results
from a test sample 1 ± 0.1-inches in
thickness may be used to determine the
R value of panels with various foam
thickness as long as the foam is of the
same final chemical form.
(5) Foam shall be tested after it is
produced in its final chemical form.
(For foam produced inside of a panel
(‘‘foam-in-place’’), ‘‘final chemical
form’’ means the foam is cured as
intended and ready for use as a finished
panel. For foam produced as board stock
(typically polystyrene), ‘‘final chemical
form’’ means after extrusion and ready
for assembly into a panel or after
assembly into a panel.) Foam from
foam-in-place panels must not include
any structural members or non-foam
materials. Foam produced as board
stock may be tested prior to its
incorporation into a final panel. A test
sample 1 ± 0.1-inches in thickness must
be taken from the center of a panel and
any protective skins or facers must be
removed. A high-speed band-saw and a
meat slicer are two types of
recommended cutting tools. Hot wire
cutters or other heated tools must not be
used for cutting foam test samples. The
two surfaces of the test sample that will
contact the hot plate assemblies (as
defined in ASTM C518 (incorporated by
reference, see § 431.303)) must both
maintain ±0.03 inches flatness tolerance
and also maintain parallelism with
respect to one another within ±0.03
inches. Testing must be completed
within 24 hours of samples being cut for
testing.
(6) Internal non-foam member and/or
edge regions shall not be considered in
ASTM C518 testing.
(7) For panels consisting of two or
more layers of dissimilar insulating
materials (excluding facers or protective
skins), test each material as described in
paragraphs (c)(1) through (6) of this
section. For a panel with N layers of
insulating material, the overall R-Value
shall be calculated as follows:
E:\FR\FM\13MYR2.SGM
13MYR2
ER13MY14.008
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
27413
Where:
DFd = the defrost energy, in W-h, at the
dry coil condition
DFf = the defrost energy, in W-h, at the
frosted coil condition
NDF = the number of defrosts per day
(xii) In section C11, if the unit utilizes
hot gas defrost, QDF and DF shall be
calculated as follows:
QDF = 0.18 Btu/defrost per Btu/h
capacity × Qref × NDF
Where:
Qref = Gross refrigeration capacity in
Btu/h as measured at the high
ambient condition (90 °F for indoor
systems and 95 °F for outdoor
systems)
NDF = Number of defrosts per day; this
value shall be set to the number
recommended in the installation
instructions for the unit (or if no
instructions, shall be set to 4) for units
without adaptive defrost and 2.5 for
units with adaptive defrost
For unit coolers connected to a
multiplex system: The defrost energy,
DF, in W-h = 0
For dedicated condensing systems or
condensing units tested separately:
DF = 0.5 × QDF/3.412 Btu/W-h
(xiii) Delete section C3.4.6.
(xiv) Off-cycle evaporator fan test. In
lieu of section C10, follow the following
procedures: Upon the completion of the
steady state test for walk-in systems, the
compressors of the walk-in systems
shall be turned off. The unit cooler’s
fans’ power consumption shall be
measured in accordance with the
requirements in Section C3.5. Off-cycle
fan power shall be equal to on-cycle fan
power unless evaporator fans are
controlled by a qualifying control.
Qualifying evaporator fan controls shall
have a user adjustable method of
destratifying air during the off-cycle
including but not limited to: adjustable
fan speed control or periodic ‘‘stir
cycles.’’ Qualifying evaporator fan
controls shall be adjusted so that the
greater of a 50% duty cycle or the
manufacturer default is used for
measuring off-cycle fan energy. For
variable speed controls, the greater of
50% fan speed or the manufacturer’s
default fan speed shall be used for
measuring off-cycle fan energy. When a
cyclic control is used at least three full
‘‘stir cycles’’ are measured.
(xv) In lieu of Table 15 and Table 16,
use the following Tables:
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
E:\FR\FM\13MYR2.SGM
13MYR2
ER13MY14.010
(vii) In section C3.4.5, for verification
of sub-cooling downstream of mass flow
meters, only the sight glass and a
temperature sensor located on the tube
surface under the insulation are
required.
(viii) Delete section C3.3.6.
(ix) In section C11.1, to determine
frost load defrost conditions, the Frost
Load Conditions Defrost Test (C11.1.1)
is optional. If the frost load test is not
performed, the frost load defrost DFf
shall be equal to 1.05 multiplied by the
dry coil energy consumption DFd
measured using the dry coil condition
test in section C11.1 and the number of
defrosts per day NDF shall be set to 4.
(x) In section C11.2, if the system has
an adaptive or demand defrost system,
the optional test may be run as specified
to establish the number of defrosts per
day under dry coil conditions and this
number shall be averaged with the
number of defrosts per day calculated
under the frost load conditions. If the
system has an adaptive or demand
defrost system and the optional test is
not run, the number of defrosts per day
NDF shall be set to the average of 1 and
the number of defrosts per day
calculated under the frost load
conditions (paragraph (c)(8)(ix) of this
section).
(xi) In section C11.3, if the frost load
test is not performed, the daily
contribution of the load attributed to
defrost QDF in Btu shall be calculated as
follows:
ER13MY14.009
tkelley on DSK3SPTVN1PROD with RULES2
Where:
ki is the k factor of the ith material as
measured by ASTM C518, and
ti is the thickness of the ith material
that appears in the panel.
N is the total number of material
layers that appears in the panel.
(8) Determine the U-factor,
conduction load, and energy use of
walk-in cooler and walk-in freezer
display panels by conducting the test
procedure set forth in appendix A to
this subpart section 4.1.
(9) Determine the energy use of walkin cooler and walk-in freezer display
doors and non-display doors by
conducting the test procedure set forth
in appendix A to this subpart, sections
4.4 and 4.5, respectively.
(10) Determine the Annual Walk-in
Energy Factor of walk-in cooler and
walk-in freezer refrigeration systems by
conducting the test procedure set forth
in AHRI 1250–2009 (incorporated by
reference; see § 431.303), with the
following modifications:
(i) In Table 2, Test Operating and Test
Condition Tolerances for Steady-State
Test, electrical power frequency shall
have a Test Condition Tolerance of 1
percent. Also, refrigerant temperature
measurements shall have a tolerance of
± 0.5 F for unit cooler in/out, ± 1.0 F for
all other temperature measurements.
(ii) In Table 2, the Test Operating
Tolerances and Test Condition
Tolerances for Air Leaving
Temperatures shall be deleted.
(iii) In Tables 2 through 14, The Test
Condition Outdoor Wet Bulb
Temperature requirement and its
associated tolerance apply only to units
with evaporative cooling.
(iv) In section C3.1.6, refrigerant
temperature measurements upstream
and downstream of the unit cooler may
use sheathed sensors immersed in the
flowing refrigerant instead of
thermometer wells.
(v) In section C3.5, for a given motor
winding configuration, the total power
input shall be measured at the highest
nameplate voltage. For three-phase
power, voltage imbalances shall be no
more than 2 percent from phase to
phase.
(vi) In the test setup (section C8.3),
the condenser and unit cooler shall be
connected by pipes of the manufacturerspecified size. The pipe lines shall be
insulated with a minimum total thermal
resistance equivalent to 1⁄2″ thick
insulation having a flat-surface R-Value
of 3.7 ft2-°F-hr/Btu per inch or greater.
Flow meters need not be insulated but
must not be in contact with the floor.
The lengths of the connected liquid line
and suction line shall be 25 feet, not
including the requisite flow meters,
each. Of this length, no more than 15
feet shall be in the conditioned space.
In the case where there are multiple
branches of piping, the maximum length
of piping applies to each branch
individually as opposed to the total
length of the piping.
27414
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
TABLE 15—REFRIGERATOR UNIT COOLER
Unit cooler air
entering drybulb, °F
Unit cooler air
entering relative humidity,
%
Saturated suction temp, °F
Off Cycle Fan
Power.
35
<50
—
—
Refrigeration
Capacity Suction A.
Refrigeration
Capacity Suction B.
35
<50
25
35
<50
20
Test description
Liquid inlet
saturation
temp, °F
Liquid inlet
subcooling
temp, °F
Compressor
capacity
Test objective
—
Compressor
Off.
105
9
Compressor
On.
105
9
Compressor
On.
Measure fan input
power during compressor off cycle.
Determine Net Refrigeration Capacity of
Unit Cooler.
Determine Net Refrigeration Capacity of
Unit Cooler.
Note: Superheat to be set according to equipment specification in equipment or installation manual. If no superheat specification is given, a default superheat value of 6.5 °F shall be used. The superheat setting used in the test shall be reported as part of the standard rating.
TABLE 16—FREEZER UNIT COOLER
Unit cooler air
entering drybulb, °F
Unit cooler air
entering relative humidity,
%
Saturated suction temp, °F
Off Cycle Fan
Power.
¥10
<50
—
—
Refrigeration
Capacity Suction A.
Refrigeration
Capacity Suction B.
Defrost ..............
¥10
<50
25
¥10
<50
¥10
Various
Test Description
Liquid inlet
saturation
temp, °F
Liquid inlet
subcooling
temp, °F
Compressor
capacity
Test objective
—
Compressor
Off.
105
9
Compressor
On.
20
105
9
Compressor
On.
—
—
—
Compressor
Off.
Measure fan input
power during compressor off cycle.
Determine Net Refrigeration Capacity of
Unit Cooler.
Determine Net Refrigeration Capacity of
Unit Cooler.
Test according to Appendix C Section
C11.
Note: Superheat to be set according to equipment specification in equipment or installation manual. If no superheat specification is given, a default superheat value of 6.5 °F shall be used. The superheat setting used in the test shall be reported as part of the standard rating.
tkelley on DSK3SPTVN1PROD with RULES2
*
*
*
*
*
(12) Calculation of AWEF for a walkin cooler and freezer refrigeration
system component distributed
individually. This section only applies
to fixed capacity condensing units.
Multiple-capacity condensing units
must be tested as part of a matched
system.
(i) Calculate the AWEF for a
refrigeration system containing a unit
cooler that is distributed individually
using the method for testing a unit
cooler connected to a multiplex
condensing system.
(ii) Calculate the AWEF for a
refrigeration system containing a
condensing unit that is distributed
individually using the following
nominal values:
Saturated suction temperature at the
evaporator coil exit Tevap (°F) = 25 for
coolers and ¥20 for freezers
For medium temperature (cooler)
condensing units: On-cycle
evaporator fan power EFcomp, on (W) =
0.013 W-h/Btu × qmix, cd (Btu/h);
where qmix, cd is the gross cooling
capacity at the highest ambient rating
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
condition (90 °F for indoor units and
95 °F for outdoor units)
For low temperature (freezer)
condensing units: On-cycle
evaporator fan power EFcomp, on (W) =
0.016 W-h/Btu × qmix, cd (Btu/h);
where qmix, cd is the gross cooling
capacity at the highest ambient rating
condition (90 °F for indoor units and
95 °F for outdoor units)
Off-cycle evaporator fan power EFcomp,
off (W) = 0.2 × EFcomp, on (W)
For medium temperature (cooler)
condensing units: Daily defrost energy
use DF (W-h) = 0 and daily defrost
heat load contribution QDF (Btu) = 0
For low temperature (freezer)
condensing units without hot gas
defrost capability:
Daily defrost energy use DF (W-h) = 8.5
× 10¥3 × (qmix, cd (Btu/h))1.27 × NDF for
freezers
Defrost heat load contribution QDF (Btu)
= 0.95 × DF (W-h)/3.412 Btu/W-h
For low temperature (freezer)
condensing units with hot gas defrost
capability, DF and QDF shall be
calculated using the method in
paragraph (c)(10)(xii) of this section.
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
The number of defrost cycles per day
(NDF) shall be set to the number
recommended in the installation
instructions for the unit (or if no
instructions, shall be set to 2.5).
7. Appendix A to Subpart R of Part
431 is amended by:
■ a. Removing and reserving sections
4.2, 4.3, 5.1, and 5.2;
■ b. Revising paragraph 5.3(a)(1);
■ c. Removing in paragraph 5.3(a)(2)
introductory text ‘‘Internal’’ and adding
‘‘Cold-side’’ in its place; and
■ d. Removing in paragraph 5.3(a)(3)
introductory text ‘‘External’’ and adding
‘‘Warm-side’’ in its place.
The revision reads as follows:
■
Appendix A to Subpart R of Part 431—
Uniform Test Method for the
Measurement of Energy Consumption of
the Components of Envelopes of WalkIn Coolers and Walk-In Freezers
*
*
*
*
*
*
*
4.2 [Reserved]
4.3 [Reserved]
*
*
*
5.1 [Reserved]
E:\FR\FM\13MYR2.SGM
13MYR2
Federal Register / Vol. 79, No. 92 / Tuesday, May 13, 2014 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES2
5.2 [Reserved]
5.3 * * *
(a) * * *
(1) The average surface heat transfer
coefficient on the cold-side of the apparatus
VerDate Mar<15>2010
18:30 May 12, 2014
Jkt 232001
shall be 30 Watts per square-meter-Kelvin
(W/m2*K) ± 5%. The average surface heat
transfer coefficient on the warm-side of the
PO 00000
27415
apparatus shall be 7.7 Watts per squaremeter-Kelvin (W/m2*K) ± 5%.
*
*
*
*
*
[FR Doc. 2014–10721 Filed 5–12–14; 8:45 am]
BILLING CODE 6450–01–P
Frm 00029
Fmt 4701
Sfmt 9990
E:\FR\FM\13MYR2.SGM
13MYR2
Agencies
[Federal Register Volume 79, Number 92 (Tuesday, May 13, 2014)]
[Rules and Regulations]
[Pages 27387-27415]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2014-10721]
[[Page 27387]]
Vol. 79
Tuesday,
No. 92
May 13, 2014
Part II
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 431
Energy Conservation for Certain Industrial Equipment: Alternative
Efficiency Determination Methods and Test Procedures for Walk-In
Coolers and Walk-In Freezers; Final Rule
Federal Register / Vol. 79 , No. 92 / Tuesday, May 13, 2014 / Rules
and Regulations
[[Page 27388]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[Docket Number EERE-2011-BT-TP-0024]
RIN 1904-AC46
Energy Conservation for Certain Industrial Equipment: Alternative
Efficiency Determination Methods and Test Procedures for Walk-In
Coolers and Walk-In Freezers
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (DOE) is revising its
regulations related to the use of methods for certifying compliance and
reporting ratings in accordance with energy conservation standards as
they apply to walk-in coolers and walk-in freezers. These revisions
also include a number of clarifications to the relevant test procedure
that will serve as the basis for any applicable alternative efficiency
determination method that may be used to rate certain walk-in cooler
and walk-in freezer components.
DATES: The effective date of this final rule is June 12, 2014. The
incorporation by reference of certain standards in this rulemaking was
approved by the Director of the Office of the Federal Register as of
March 23, 2009 and April 15, 2011.
ADDRESSES: Docket: The docket is available for review at
www.regulations.gov, including Federal Register notices, public meeting
attendee lists and transcripts, comments, and other supporting
documents/materials. All documents in the docket are listed in the
www.regulations.gov index. However, not all documents listed in the
index may be publicly available, such as information that is exempt
from public disclosure.
A link to the docket Web page can be found at: https://www.regulations.gov/#!docketDetail;D=EERE-2011-BT-TP-0024. This Web
page contains a link to the docket for this rule on the
www.regulations.gov site. The www.regulations.gov Web page contains
simple instructions on how to access all documents, including public
comments, in the docket.
For information on how to review the docket, contact Ms. Brenda
Edwards at (202) 586-2945 or by email: Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Ashley Armstrong, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Program, EE-5B,
1000 Independence Avenue SW., Washington, DC 20585-0121. Telephone:
(202) 586-6590. Email: Ashley.Armstrong@ee.doe.gov.
Mr. Michael Kido, U.S. Department of Energy, Office of the General
Counsel, GC-71, 1000 Independence Avenue SW., Washington, DC 20585-
0121. Telephone: (202) 586-8145. Email: Michael.Kido@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
Table of Contents
I. Authority and Background
A. Authority
B. Background
1. Alternative Efficiency Determination Method
2. Test Procedures for WICF Refrigeration Equipment
3. Sampling Plan
4. Test Procedures and Prescriptive Requirements for WICF Foam
Panel R-Value
5. Performance-Based Test Procedures for Energy Consumption of
Envelope Components
II. Summary of the Final Rule
III. Discussion
A. Alternative Efficiency Determination Method
1. Applicable Equipment
2. Validation
a. Number of Tested Units Required for Validation
b. Tolerances for Validation
3. Certified Rating
4. Verification
a. Failure To Meet a Certified Rating
b. Action Following Determination of Noncompliance Based Upon
Enforcement Testing
5. Re-Validation
a. Change in Standards or Test Procedures
b. Re-Validation Using Active Models
c. Time Allowed for Re-Validation
B. Refrigeration Test Procedure
1. Component-Level Ratings for Refrigeration: Overall
2. Component-Level Ratings for Refrigeration: Metrics
3. Component-Level Ratings for Refrigeration: Nominal
Calculation Values
a. On-Cycle Evaporator Fan Power
b. Off-Cycle Evaporator Fan Power
c. Defrost Energy
4. Other Test Procedure Changes
a. Nominal Values for Defrost Energy and Heat Load Calculations
b. Off-Cycle Evaporator Fan Test
c. Refrigerant Oil Testing
d. Temperature Measurement
e. Test Condition Tolerances
f. Pipe Insulation and Length
g. Composition Analysis
h. Unit Cooler Test Conditions
C. Test Procedure for WICF Panel R-Value (ASTM C518-04)
1. Test Sample Specifications
2. Removal of Panel Facers
3. 48-Hour Testing Window
4. Specimen Conditioning Temperatures
5. Flatness Tolerances on Contact Surfaces
6. Panel Testing Temperature Tolerances
7. Additional Modifications to the Panel Test Procedure
D. Performance-Based Test Procedures for Panels and Doors of
Walk-In Coolers and Freezers
1. Panels
2. Doors
E. Sampling Plan
F. Other Issues
G. Compliance with Other EPCA Requirements
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
V. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III, Part C of the Energy Policy and Conservation Act of 1975
(``EPCA'' or ``the Act'', Pub. L. 94-163) sets forth a variety of
provisions designed to improve energy efficiency. The National Energy
Conservation Policy Act (``NECPA'', Pub. L. 95-619) amended EPCA and
established the energy conservation program for certain industrial
equipment. (42 U.S.C. 6311-6317) The Energy Independence and Security
Act of 2007 (``EISA 2007'') further amended EPCA to include, among
others, two types of industrial equipment that are the subject of
today's notice: Walk-in coolers and walk-in freezers (collectively,
``walk-ins'' or ``WICFs''). (42 U.S.C. 6311(1)(G)) Walk-ins are
enclosed storage spaces of less than 3,000 square feet that can be
walked into and are refrigerated to temperatures above and at or below
32 degrees Fahrenheit, respectively. (42 U.S.C. 6311(20)(A)) This term,
by statute, excludes equipment designed for medical, scientific, or
research purposes. (42 U.S.C. 6311(20)(B))
Under EPCA, the energy conservation program generally consists of
four parts: (1) Testing; (2) labeling; (3) establishing Federal energy
conservation standards; and (4) certification and enforcement
procedures. The testing requirements consist of test procedures that
[[Page 27389]]
manufacturers of covered equipment must use as the basis for making
representations about the efficiency of that equipment, including those
representations made to DOE that the covered equipment complies with
the applicable energy conservation standards adopted pursuant to EPCA.
(42 U.S.C. 6314(d)) Similarly, DOE must use these test requirements to
determine whether the products comply with the relevant energy
conservation standards. See 42 U.S.C. 6313(a) (applying 42 U.S.C.
6295(s) to walk-ins). For certain consumer products and commercial and
industrial equipment, DOE's testing regulations currently allow
manufacturers to use an alternative efficiency determination method
(AEDM), in lieu of actual testing, to simulate the energy consumption
or efficiency of certain basic models of covered products and equipment
under DOE's test procedure conditions. As explained in further detail
below, an AEDM is a computer model or mathematical tool used to help
determine the energy efficiency of a particular basic model.
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
that DOE must follow when prescribing or amending test procedures for
covered products. Included among these criteria is that the prescribed
procedure be reasonably designed to produce test results that measure
energy efficiency, energy use, or estimated annual operating cost of a
covered product during a representative average use cycle or period of
use, and must not be unduly burdensome to conduct. (42 U.S.C.
6314(a)(2)) DOE provides the public with an opportunity to comment on a
proposal made under section 6314.
B. Background
1. Alternative Efficiency Determination Method
As briefly noted above, AEDMs are computer modeling or mathematical
tools that predict the performance of non-tested basic models. They are
derived from mathematical models and engineering principles that govern
the energy efficiency and energy consumption characteristics of a type
of covered equipment. These computer modeling and mathematical tools,
when properly developed, can provide a relatively straightforward and
reasonably accurate means to predict the energy usage or efficiency
characteristics of a basic model of a given covered equipment type.
These tools can be useful in reducing a manufacturer's testing burden.
Where authorized by regulation, AEDMs enable manufacturers to rate
and certify their basic models by using the projected energy use or
energy efficiency results derived from these simulation models. DOE
currently permits manufacturers of a few, limited types of expensive or
highly customized equipment to use AEDMs when rating and certifying
their equipment.
DOE believes other similar equipment that must currently be rated
and certified through testing, such as walk-in refrigeration systems,
could also be rated and certified through the use of computer or
mathematical modeling. Consequently, to examine whether AEDM usage
would be appropriate for walk-in refrigeration systems, DOE sought
comment on this topic and other related issues in a Request for
Information (RFI). See 76 FR 21673 (April 18, 2011).
DOE subsequently issued a Notice of Proposed Rulemaking (NOPR) that
proposed to expand and revise DOE's existing AEDM requirements for
certain commercial equipment covered under EPCA. 77 FR 32038 (May 31,
2012). Among other things, the May 2012 NOPR proposed to allow
manufacturers of walk-in refrigeration systems to use AEDMs when
certifying the energy use or energy efficiency of basic models of
equipment in lieu of testing.
Subsequent to the May 2012 NOPR's publication, the Appliance
Standards and Rulemaking Federal Advisory Committee (ASRAC) unanimously
decided to form a working group (``Working Group'') to engage in a
negotiated rulemaking effort on the certification of commercial
heating, ventilating, air conditioning (HVAC), water heating (WH), and
refrigeration equipment. During the Working Group's first meeting on
April 30, 2013, Working Group members voted to expand the scope of its
efforts to include developing methods of estimating equipment
performance based on AEDM simulations for commercial HVAC, WH, and
refrigeration equipment. The issues discussed by the various
participants during the negotiations with DOE were similar to those
raised by the commenters in response to the May 2012 NOPR, which
included AEDM validation and DOE verification of ratings derived using
an AEDM. As a result of these negotiations and further consideration of
written comments submitted in response to DOE's supplemental notice of
proposed rulemaking (SNOPR) regarding the treatment of commercial HVAC,
WH, and refrigeration equipment, see 78 FR 62472 (Oct. 22, 2013), DOE
adopted the Working Group's AEDM recommendation with respect to this
group of equipment. 78 FR 79579 (Dec. 31, 2013).
To comprehensively address the specific issues related to walk-ins,
DOE published an SNOPR that proposed to align DOE's AEDM regulations by
allowing the use of AEDMs when certifying the energy efficiency
performance of walk-in refrigeration equipment in a manner similar to
that which was recently established for commercial HVAC, refrigeration,
and WH equipment. See 79 FR 9817 (Feb. 20, 2014). This approach, which
was recommended by the Working Group, would help DOE establish a
uniform, systematic, and fair approach to the use of these types of
modeling techniques that will enable DOE to ensure that products in the
marketplace are correctly rated--irrespective of whether they are
subject to actual physical testing or are rated using modeling--without
unnecessarily burdening regulated entities. DOE reopened the comment
period for the February 20, 2014 SNOPR to allow interested parties
additional time to provide the Department with comments, data, and
information. See 79 FR 19844 (April 10, 2014). DOE did not receive any
additional timely submitted comments in response to the reopened
comment period. Today's notice is the culmination of DOE's efforts
regarding AEDMs for walk-in coolers and freezers that were initiated
with the May 2012 NOPR.
2. Test Procedures for WICF Refrigeration Equipment
A walk-in's refrigeration system performs the mechanical work
necessary to cool the interior space of a walk-in. The system typically
comprises two separate primary components, a condenser/compressor
(``condensing unit'') and an expansion valve/evaporator (``unit
cooler''). DOE's regulations at 10 CFR 431.304, Uniform test method for
the measurement of energy consumption of walk-in coolers and walk-in
freezers, incorporate by reference AHRI Standard 1250-2009, ``2009
Standard for Performance Rating of Walk-in Coolers and Freezers'' (AHRI
1250-2009) as the testing method for walk-in refrigeration systems. 10
CFR 431.304(b)(9). AHRI 1250-2009 establishes methods to follow when
testing a complete refrigeration system (the ``matched system'' test),
as well as separate methods to use for testing the unit cooler and
condensing unit of a refrigeration system individually and then
calculating a combined system rating (the ``mix-match'' test). AHRI
1250-2009 also contains standard rating
[[Page 27390]]
conditions for: Cooler and freezer systems; systems where the condenser
is located either indoors or outdoors; and systems with single-speed,
two-speed, or variable-speed compressors. AHRI 1250-2009 also
establishes a method for testing and rating unit coolers that are
connected to a multiplex condensing system such as those typically
found in a supermarket. The rating produced by the AHRI 1250-2009 test
procedure is an annual walk-in energy factor (AWEF), defined as ``a
ratio of the total heat, not including the heat generated by the
operation of refrigeration systems, removed, in Btu [British thermal
units], from a walk-in box during one year period of usage for
refrigeration to the total energy input of refrigeration systems, in
watt-hours, during the same period.'' AHRI 1250-2009, at sec. 3.1.
DOE recently proposed energy conservation standards for walk-ins.
See 78 FR 55781 (Sept. 11, 2013) (September 2013 standards NOPR). In
that notice, DOE proposed standards for complete walk-in refrigeration
systems that would require the ratings for the refrigeration system to
be derived using either the matched system or mix-match tests described
above. DOE also proposed standards for unit coolers connected to a
multiplex system, based on the unit cooler rating method described
above. Responding to the NOPR, several interested parties discussed the
concept of establishing separate standards for the unit cooler and
condensing unit of a walk-in as a means to address the fundamental
problem of how one manufacturer (e.g., unit cooler manufacturer) would
be able to rate its equipment in the absence of knowing which equipment
(e.g., condensing unit) would be matched with its own equipment.
Performance characteristics of both the unit cooler and condensing unit
are needed in order to rate the refrigeration system's performance
under the methodology in AHRI 1250-2009.
In light of that discussion and the fact that unit coolers and
condensing units are often sold separately or produced by different
manufacturers, DOE proposed in the February 2014 SNOPR to adopt a
methodology that would account for the issue noted above by relying on
elements of AHRI 1250-2009, which includes a method to test both
components separately (i.e., the mix-match test method). The proposed
method would require the manufacturer of either the unit cooler or
condensing unit, if sold separately, to test and certify compliance of
a nominal refrigeration system with DOE's standards and make
representations of a WICF refrigeration system. Under the proposal,
manufacturers of a complete WICF refrigeration system could continue to
develop a system rating for the purposes of certifying compliance with
DOE's standards and making energy efficiency representations of the
WICF refrigeration system. Furthermore, as DOE noted in the February
2014 SNOPR, in reviewing AHRI 1250-2009 and conducting limited testing
on a WICF refrigeration system at a third-party laboratory to
investigate the AEDM validation approach, DOE had discovered several
issues in the refrigeration test procedures that required clarification
and/or created unnecessary test burden. 79 FR at 9820. To simplify the
procedure and to clarify certain aspects, DOE proposed alternate
language to certain requirements contained in AHRI 1250-2009 that DOE's
test procedure currently incorporates by reference.
3. Sampling Plan
In order to determine a rating for certifying compliance or making
energy use representations, DOE requires manufacturers to test each
basic model in accordance with the applicable DOE test procedure and
apply the appropriate sampling plan. As part of the February 2014
SNOPR, DOE proposed a sampling plan for walk-ins consistent with other
commercial equipment regulated under EPCA.
4. Test Procedures and Prescriptive Requirements for WICF Foam Panel R-
Value
EPCA mandates prescriptive requirements for the thermal resistance
of walk-in panels: Wall, ceiling, and doors must have an insulation
value of at least R-25 for coolers and R-32 for freezers. (42 U.S.C.
6313(f)(1)(C)) EPCA also requires the use of ASTM C518-04, Standard
Test Method for Thermal Steady-State Thermal Transmission Properties by
Means of the Heat Flow Meter Apparatus (``ASTM C518-04'') to measure
the insulation thermal resistance of a panel. (42 U.S.C. 6314(a)(9)(A))
The walk-in test procedure at 10 CFR 431.304 incorporates ASTM C518-04
by reference. This reference standard is the method by which thermal
conductivity (the ``K factor'') of a walk-in panel is measured; the R-
Value of the panel is then determined by multiplying 1/K (the
reciprocal of K) by the thickness of the panel. The R-Value of a
freezer panel is determined at a mean insulation foam temperature of 20
degrees Fahrenheit and the R-Value of a cooler panel is determined at a
mean insulation foam temperature of 55 degrees Fahrenheit. (42 U.S.C.
6314(a)(9)(A)(iii) and (iv)) The regulations also currently require
manufacturers to use the procedure detailed in 10 CFR 431.304(b) when
certifying compliance with the panel energy conservation standards
until January 1, 2015. Manufacturers must use the procedure in 10 CFR
431.304(c) when making representations of energy efficiency currently
and when certifying compliance starting on January 1, 2015. In the
February 2014 SNOPR, DOE proposed modifications to the test sample
preparation procedures incorporated from ASTM C518-04 in both
procedures to improve measurement accuracy.
5. Performance-Based Test Procedures for Energy Consumption of Envelope
Components
In 10 CFR Part 431, Subpart R, Appendix A, DOE lays out a method
for measuring performance-based efficiency metrics for certain WICF
envelope components. This method draws from several existing industry
test methods by incorporating by reference ASTM C1363-05 Standard Test
Method for Thermal Performance of Building Materials and Envelope
Assemblies by Means of a Hot Box Apparatus and Annex C Determination of
the aged values of thermal resistance and thermal conductivity from
both DIN EN 13164 and DIN EN 13165 (two European Union-developed
testing protocols) for measuring the energy consumption of WICF floor
and non-floor panels. Appendix A also incorporates NFRC 100-2010[E0A1]
Procedure for Determining Fenestration Product U-factors for
determining the energy use of walk-in display and non-display doors. In
the February 2014 SNOPR, DOE proposed modifying (1) the test procedures
for WICF floor and non-floor panels to address comments received from
stakeholders during the standards rulemaking and (2) the WICF display
and non-display door test procedure to improve the clarity of the test
method.
II. Summary of the Final Rule
Today's final rule comprises six key elements.
First, the Department will allow WICF refrigeration manufacturers
to use AEDMs to rate and certify their basic models by using the
projected energy efficiency derived from these simulation models in
lieu of testing. DOE is aligning the validation requirements proposed
for WICF refrigeration AEDMs with those that have already been adopted
for commercial HVAC, refrigeration, and WH equipment. DOE is adopting
this approach because the
[[Page 27391]]
cooling and refrigeration systems used by these equipment types operate
under similar principles as the refrigeration systems used in walk-ins.
This similarity, along with the practical considerations discussed
elsewhere in this rule, lend support for applying similar or identical
validation requirements for walk-ins as well.
Second, today's final rule adopts an alternative method for testing
and rating the WICF refrigeration system for unit coolers and
condensing units that are sold alone. Specifically, unit cooler
manufacturers who distribute a unit cooler as a separate component must
rate that cooler as though it were to be connected to a multiplex
system and must comply with any applicable standard DOE may establish
for a unit cooler connected to a multiplex system. Similarly,
manufacturers who distribute a condensing unit as a separate component
must use the nominal values for unit coolers, in lieu of actual unit
cooler test data, when calculating AWEF using the mix-match rating
method in AHRI 1250. Consistent with this methodology and pending the
outcome of the standards rulemaking, DOE would consider modifications
to the certification requirements based on the following approach:
(1) a manufacturer that only produces unit coolers would use the
test method (``Walk-in Unit Cooler Match to Parallel Rack System'' in
AHRI 1250, section 7.9) to establish a WICF refrigeration system rating
for each basic model, and the unit cooler manufacturer would certify
the compliance of each unit cooler model as a component of a WICF
refrigeration system basic model;
(2) a manufacturer that only produces condensing units would test
each condensing unit and combine it with the unit cooler nominal values
adopted in today's final rule to establish a WICF refrigeration system
rating for each basic model, and the condensing unit manufacturer would
certify the compliance of each condensing unit model as a component of
a WICF refrigeration system basic model; or
(3) a manufacturer that produces both unit cooler basic models and
condensing unit basic models that are marketed and sold as a matched
system would use the test method in AHRI 1250-2009 to test the unit
cooler and the condensing unit as a matched system to obtain a WICF
refrigeration system rating for each matched system it produces and
then certify compliance, except where both components have been
previously rated and certified separately. In this case, the
manufacturer need not test and certify the matched system unless the
manufacturer wishes to represent the matched system efficiency as being
higher than the efficiency of either component.
Third, DOE is adopting the following modifications to the test
procedure for WICF refrigeration components:
--Clarifying the defrost test procedure;
--Offering an alternative method for calculating the defrost energy and
heat load of a system with electric defrost in lieu of a frosted coil
test;
--Adding a method for calculating defrost energy and heat load of a
system with hot gas defrost;
--Changing the minimum fan speed and duty cycle during the off-cycle
evaporator fan test;
--Removing the refrigerant oil and refrigerant composition analysis
testing requirements;
--Clarifying and modifying the temperature measurement requirements to
reduce testing burden while ensuring accuracy;
--Adding a test condition tolerance for electrical power frequency and
removing the test condition tolerance for air temperature leaving the
unit;
--Quantifying the requirements for insulating refrigerant lines;
--Clarifying piping length requirement;
--Bringing consistency between the list of tests for unit coolers in
Tables 15 and 16 of AHRI 1250-2009, and another similar test method;
and
--Clarifying the voltage imbalance for three-phase power.
Fourth, DOE is modifying the current test procedure for measuring
the insulation R-Value of WICF panels. (10 CFR 431.304) The current DOE
test procedure allows, but does not require, panels to be tested with
non-foam facers or protective skins attached. (10 CFR 431.304(b)(5)-(6)
and (c)(5)-(6)) Also, the current DOE test procedure allows panel test
samples to be up to 4 inches in thickness. (10 CFR 431.304(b)(5) and
(c)(5)) The test procedure requires that the R-Value be measured at a
mean temperature of 20 degrees Fahrenheit for freezer panels (10 CFR
431.304(b)(3) and (c)(3)) and 55 degrees Fahrenheit for cooler panels
(10 CFR 431.304(b)(4) and (c)(4)); however, no tolerance is currently
specified for these temperatures. With this final rule, DOE will
require test samples to be 1-inch in thickness and without non-foam
facers, protective skins, internal non-foam members or edge regions.
DOE is also adding flatness and parallelism constraints on the test
sample surfaces that contact the hot and cold plates in the heat flow
meter apparatus. DOE is also adding a tolerance of 1 degree
Fahrenheit for the mean temperature during panel R-Value testing. DOE
believes this clarification will help ensure that the panel testing is
conducted in a repeatable and reproducible manner at different
laboratories.
Fifth, to enable walk-in manufacturers to make energy use
representations, DOE is implementing a sampling plan for walk-ins
consistent with other commercial equipment regulated under EPCA.
Finally, in response to manufacturer comments on the September 2013
standards NOPR, DOE is removing the existing performance-based test
procedures for WICF floor and non-floor panels (10 CFR Part 431,
Subpart R, Appendix A, sections 4.2, 4.3, 5.1, and 5.2). DOE recognizes
that these performance-based procedures for WICF floor and non-floor
panels are in addition to the prescriptive requirements already
established in EPCA for panel insulation R-Values and, therefore, may
increase the test burden to manufacturers. This recognition of the
overall burdens faced by manufacturers is based in part on the
difficulty manufacturers have reportedly had in locating any testing
laboratories capable of performing the applicable tests since DOE's
issuance of the test procedure in April 2011. See 76 FR 21580. Based on
market research, DOE agrees with manufacturers that there are a limited
number of laboratories capable of conducting the performance-based
procedures for WICF floor and non-floor panels.
All of the changes noted above, along with the appropriate sections
of the CFR where these changes appear, are detailed in the summary
table below.
Table II.1--Summary of CFR Changes
----------------------------------------------------------------------------------------------------------------
Change 10 CFR section
----------------------------------------------------------------------------------------------------------------
Allowing manufacturers to use AEDMs to rate 429.53.
WICF refrigeration systems.
Specific instructions for applying AEDMs to 429.70(f).
WICF refrigeration systems.
Changes to test procedures and prescriptive 431.304(b)(3)-(6) and 431.304(c)(3)-(6).
requirements for WICF foam panel R-Value.
[[Page 27392]]
Amendments to AHRI 1250-2009 refrigeration 431.304(c)(8).
system test method, and the panel and door
test methods.
Methods for rating refrigeration components 431.304(c)(11).
sold separately.
Amendments to performance-based test 431 Subpart R, Appendix A.
procedures for energy consumption of
envelope components.
----------------------------------------------------------------------------------------------------------------
III. Discussion
In response to the February 2014 SNOPR, DOE received written
comments from 9 interested parties, including manufacturers, trade
associations and energy efficiency advocacy groups. Table III.1 lists
the entities that commented on that SNOPR and their affiliation. (DOE
also re-opened the comment period to allow for additional comments.)
These comments are discussed in more detail below, and the full set of
comments, including the public meeting transcript, can be found at:
https://www.regulations.gov/#!docketDetail;dct=FR%252BPR%252BN%252BO%252BSR%252BPS;rpp=25;po=0;D=EER
E-2011-BT-TP-0024.
Table III.1--Interested Parties That Commented on the February 2014 SNOPR
----------------------------------------------------------------------------------------------------------------
Comment No.
Commenter Acronym Organization type/ (Docket
affiliation reference)
----------------------------------------------------------------------------------------------------------------
Air-Conditioning, Heating, and AHRI...................... Industry Trade Group...... 100
Refrigeration Institute.
American Council for an Energy-Efficient ACEEE..................... Advocacy Group............ 98
Economy.
Appliance Standards Awareness Project, ASAP, EJ, NRDC, ASE, Advocacy Group............ 99
Earthjustice, Natural Resources Defense ACEEE, NEEA, NPCC (ASAP,
Council, Alliance to Save Energy, et al.).
American Council for an Energy
Efficient Economy, Northwest Energy
Efficiency Alliance, and Northwest
Power and Conservation Council.
Bally Refrigerated Boxes, Inc........... Bally..................... Manufacturer.............. 93
California Investor-Owned Utilities: PG&E, SCE, and SDG&E (CA Utility Association....... 101
Pacific Gas and Electric Company, IOUs).
Southern California Edison, and San
Diego Gas & Electric.
Heat Transfer Products Group, LLC....... HTPG...................... Manufacturer.............. 96
Lennox International, Inc............... Lennox.................... Manufacturer.............. 97
National Coil Company................... NCC....................... Manufacturer.............. 95
National Refrigeration & Air KeepRite.................. Manufacturer.............. 94
Conditioning Canada Corp. (dba
KeepRite).
----------------------------------------------------------------------------------------------------------------
In response to the initial May 2012 NOPR, DOE received written
comments from 28 interested parties, including manufacturers, trade
associations and advocacy groups. Seven additional interested parties
commented during the May 2012 NOPR Public Meeting on June 5, 2012. For
reference, Table III.2 lists the entities that commented on the NOPR
and their affiliation. These comments were discussed in the February
2014 SNOPR. The full set of comments, including the public meeting
transcript, can be found at: https://www.regulations.gov/#!docketDetail;dct=FR%252BPR%252BN%252BO%252BSR%252BPS;rpp=25;po=0;D=EER
E-2011-BT-TP-0024.
Table III.2--Interested Parties That Commented on the May 2012 NOPR
------------------------------------------------------------------------
Organization type/
Name Acronym affiliation
------------------------------------------------------------------------
AAON, Inc........................ AAON.............. Manufacturer.
The ABB Group.................... ABB............... Manufacturer.
Air-Conditioning, Heating, and AHRI.............. Industry Trade
Refrigeration Institute. Group.
Appliance Standards Awareness Joint Comment..... Advocacy Group.
Project & American Council for
an Energy-Efficient Economy.
Baldor Electric.................. Baldor Electric... Manufacturer.
Bradford White Corporation....... Bradford White.... Manufacturer.
Burnham Commercial............... Burnham........... Manufacturer.
Cooper Power Systems............. Cooper............ Manufacturer.
Crown Boiler Company............. Crown Boiler...... Manufacturer.
CrownTonka/ThermalRite/ CT/TR/ICS......... Manufacturer.
International Cold Storage.
Danfoss.......................... Danfoss........... Manufacturer.
First Co......................... First Co.......... Manufacturer.
Goodman Global, Inc.............. Goodman........... Manufacturer.
Heatcraft Refrigeration Products Heatcraft Manufacturer.
LLC. Refrigeration.
[[Page 27393]]
Hillphoenix, Inc................. Hillphoenix....... Manufacturer.
Hussmann Corporation............. Hussmann.......... Manufacturer.
Ingersoll Rand................... Ingersoll Rand.... Manufacturer.
Johnson Controls, Inc............ JCI............... Manufacturer.
Lennox International, Inc........ Lennox............ Manufacturer.
Lochinvar, LLC................... Lochinvar......... Manufacturer.
Mitsubishi Electric.............. Mitsubishi Manufacturer.
Electric.
Modine Manufacturing Company..... Modine............ Manufacturer.
Mortex Products, Inc............. Mortex............ Manufacturer.
National Electrical Manufacturers NEMA.............. Industry Trade
Association. Group.
Nidec Motor Corporation.......... Nidec............. Manufacturer.
Nordyne, LLC..................... Nordyne........... Manufacturer.
Rheem Manufacturing Company...... Rheem............. Manufacturer.
Schneider Electric............... SE................ Manufacturer.
Southern Store Fixtures, Inc..... Southern Store Manufacturer.
Fixtures.
Trane............................ Trane............. Manufacturer.
True Manufacturing Co. Inc....... True Manufacturing Manufacturer.
Unico, Inc....................... Unico............. Manufacturer.
United Cool Air.................. United Cool Air... Manufacturer.
United Technologies Climate, UTC/Carrier....... Manufacturer.
Controls & Security and ITS
Carrier.
Zero Zone, Inc................... Zero Zone......... Manufacturer
------------------------------------------------------------------------
In response to the SNOPR on AEDMs for commercial HVAC,
refrigeration and WH equipment, which was published in the Federal
Register on October 22, 2013, 78 FR 62472, DOE received a comment
relevant to this rulemaking from Lennox International, Inc., a
manufacturer of HVAC and commercial refrigeration equipment. This
comment was addressed in the February 2014 SNOPR. See 79 FR at 9824.
The Department also received relevant comments from 23 interested
parties in response to the September 2013 Standards NOPR and related
NOPR Public Meeting held on October 9, 2013. For reference, Table III.3
lists the entities that commented on that NOPR and their affiliation.
These comments were also discussed in the February 2014 SNOPR. See
generally 79 FR at 9822-9837. The full set of comments, including the
public meeting transcript, can be found at: https://www.regulations.gov/#!docketDetail;D=EERE-2008-BT-STD-0015.
Table III.3--Interested Parties That Commented on the September 2013
Standards NOPR
------------------------------------------------------------------------
Organization type/
Name Acronym affiliation
------------------------------------------------------------------------
Air Conditioning Contractors of ACCA.............. Industry Trade
America. Group.
Air-Conditioning, Heating, and AHRI.............. Industry Trade
Refrigeration Institute. Group.
American Council for an Energy ACEEE............. Advocacy Group.
Efficient Economy.
American Panel Corp.............. American Panel.... Manufacturer.
Appliance Standards Awareness ASAP.............. Advocacy Group.
Project.
Architectural Testing Inc........ AT................ Third Party
Laboratory.
Bally Refrigerated Boxes, Inc.... Bally............. Manufacturer.
CrownTonka Walk-Ins, ThermalRite CT/TR/ICS......... Manufacturer.
& International Cold Storage.
Danfoss Group North America...... Danfoss........... Manufacturer.
Heatcraft Refrigeration Products Heatcraft......... Manufacturer.
LLC.
Hillphoenix...................... Hillphoenix....... Manufacturer.
HussmanCorporation............... HussmanCorp....... Manufacturer.
Imperial Brown................... IB................ Manufacturer.
KysorWarren...................... Kysor............. Manufacturer.
Lennox International Inc......... Lennox............ Manufacturer.
Louisville Cooler Mfg............ Louisville Cooler. Manufacturer.
Manitowoc........................ Manitowoc......... Manufacturer.
National Coil Company............ NCC............... Manufacturer.
Nor-Lake, Inc.................... Nor-Lake.......... Manufacturer.
Northwest Energy Efficiency NEEA, et al....... Advocacy Group.
Alliance & The Northwest Power
and Conservation Council.
Pacific Gas & Electric, Southern CA IOU's.......... Utility.
California Gas, Southern
California Edison, San Diego Gas
& Electric (Ca. State
Independently Owned Utilities).
Thermo-Kool...................... Thermo-Kool....... Manufacturer.
US Cooler Co..................... US Cooler......... Manufacturer.
------------------------------------------------------------------------
A. Alternative Efficiency Determination Method
In the May 2012 NOPR, DOE proposed, among other things, to allow
the use of AEDMs for WICFs and to establish specific requirements for
manufacturer validation \1\--i.e., a
[[Page 27394]]
process in which manufacturers demonstrate the accuracy of an AEDM
model--and DOE verification \2\--i.e., a process followed by DOE when
verifying the accuracy of an AEDM model--that would apply to this
equipment.
---------------------------------------------------------------------------
\1\ In the May 2012 NOPR, DOE used the term ``substantiation''
to refer to the process manufacturers used to demonstrate that their
modeling tool, or AEDM, produced accurate results. See 77 FR at
32040. The Working Group elected to use the term ``validation,''
instead of ``substantiation,'' for this process. DOE clarifies that
``substantiation'' and ``validation'' are synonymous in this context
and the Department will use the term ``validation'' henceforth.
\2\ In the May 2012 NOPR, DOE used the term ``DOE validation''
to refer to the process DOE used to check that the modeling tool, or
AEDM, produced accurate results. See 77 FR at 32046. The Working
Group elected to use the ``verification,'', instead of ``DOE
validation,'', for this process. DOE clarifies that ``DOE
validation'' and ``verification'' are synonymous and the Department
will use the term ``verification'' henceforth.
---------------------------------------------------------------------------
As discussed above, ASRAC formed a working group in April 2013 to
discuss and negotiate a variety of issues related to the certification
provisions for commercial heating, ventilation, and air conditioner
(HVAC), refrigeration, and water heater (WH) equipment. Those
discussions were expanded to include AEDMs, along with related
validation and verification requirements. These negotiations eventually
led to the October 2013 SNOPR and the December 2013 final rule that
established a series of requirements related to basic model definitions
and compliance provisions for commercial HVAC, WH, and refrigeration
equipment. See 78 FR 62472 (SNOPR) and 78 FR 79579 (final rule). In the
February 2014 SNOPR, DOE proposed to require that the AEDM validation
regulations that apply to commercial HVAC, refrigeration, and WH
equipment would also apply to AEDMs designed to simulate testing of
WICF refrigeration systems as a whole and WICF refrigeration
components- i.e., unit coolers and condenser units. DOE is retaining
this approach in this final rule and addresses comments on the SNOPR
below.
Generally, AHRI commented that while it supports AEDMs for walk-
ins, the AEDM provisions for commercial HVAC, WH, and refrigeration
equipment may not be applicable to walk-in coolers. AHRI explained that
the Working Group was afforded the opportunity to amend basic model
definitions and verification procedures for commercial HVAC, WH, and
refrigeration equipment over the course of several months of meetings.
AHRI asserted that while most of the AEDM recommendations could be
applied to walk-ins, this type of equipment is very unique. To better
address this subject, AHRI requested additional time to review basic
model definitions for WICFs with respect to AEDMs. (AHRI, No. 100 at p.
2) DOE provided an additional comment period. See 79 FR 19844 (April
10, 2014).
In DOE's view, walk-in refrigeration equipment is sufficiently
similar to commercial HVAC, WH, and refrigeration equipment to permit
the AEDM regulatory framework for AEDMs established by the Working
Group to be effectively applied to walk-in refrigeration systems. These
systems are similar in operation and design to those refrigeration
systems used in both commercial HVAC and refrigeration equipment
systems and are commonly found in both walk-in and commercial
refrigeration equipment applications. Additionally, similar to
commercial refrigeration equipment, walk-in refrigeration systems have
a high degree of customization. Permitting the AEDM regulatory
framework to be applied to walk-ins, would also likely significantly
reduce manufacturer testing burden for this equipment while maintaining
a reasonable level of accuracy with respect to energy efficiency.
1. Applicable Equipment
In the February 2014 SNOPR, DOE proposed to allow WICF
refrigeration system manufacturers to use AEDMs when rating the
performance of this equipment. DOE did not propose to extend this
allowance to WICF panel or door manufacturers. WICF panels are
relatively simple pieces of equipment and the test results from a basic
model of a given panel can be extrapolated to many other panel basic
models under the provisions of the test procedure. As for WICF doors,
the DOE test procedure already specifies the use of certain modeling
techniques that are approved by the National Fenestration Rating
Council (NFRC), which, in DOE's view, makes a parallel AEDM provision
for these components unnecessary. 77 FR at 32041. Instead, the
Department proposed other modifications in the February 2014 SNOPR to
the walk-in panel test procedure to reduce the burden faced by panel
manufacturers while ensuring the overall accuracy of the efficiency
ratings. The modifications to the WICF panel test procedure are
outlined in section III.C. DOE did not receive any comments regarding
its proposal to extend AEDMs to walk-in refrigeration equipment and
therefore is adopting this proposal in today's final rule.
DOE is allowing WICF refrigeration manufacturers to apply an AEDM
to a basic model to determine its efficiency, provided that the AEDM
meets certain requirements. The AEDM must be derived from a
mathematical model that estimates the energy efficiency or consumption
characteristics of the basic model as measured by the applicable DOE
test procedure. The AEDM must be based on engineering or statistical
analysis, computer simulation, modeling, or other type of analytical
evaluation of performance data. Finally, the AEDM must be validated
according to DOE requirements, which are discussed in section III.A.2
of this rule.
2. Validation
a. Number of Tested Units Required for Validation
In the February 2014 SNOPR, DOE proposed to apply the Working
Group's recommendation for AEDM validation requirements to WICFs. That
recommendation, which DOE adopted and is applying to those AEDMs used
for commercial HVAC, refrigeration, and WH equipment, requires a
manufacturer to select a minimum number of models from each validation
class to which the AEDM will apply. (Validation classes are groupings
of products based on equipment classes but used for AEDM validation.)
DOE proposed to apply this same approach to WICF refrigeration systems
using the validation classes listed in Table III.4. A unit of each
basic model selected would undergo a single test conducted in
accordance with the DOE test procedure (or, if applicable, a test
procedure waiver issued by DOE) at a manufacturer's testing facility or
a third-party testing facility. The test result should be directly
compared to the result from the AEDM to determine the AEDM's validity.
A manufacturer may develop multiple AEDMs per validation class and each
AEDM may span multiple validation classes; however, the minimum number
of tests must be maintained per validation class for every AEDM a
manufacturer chooses to develop. An AEDM may be applied to any model
within the applicable validation classes at the manufacturer's
discretion. All documentation of test results for these models, the
AEDM results, and subsequent comparisons to the AEDM would be
maintained as part of both the test data underlying the certified
rating and the AEDM validation package pursuant to 10 CFR 429.71.
Specifically, manufacturers must maintain the AEDM, including the
mathematical model, statistical analysis or other computer simulations
that form the basis of the AEDM. Additionally, DOE requires
manufacturers to maintain equipment information, complete test data,
and AEDM calculations for each of the units that were used to validate
the AEDM. Finally, manufacturers must
[[Page 27395]]
maintain equipment information and calculations for each basic model to
which the AEDM was applied.
Table III.4--Validation Classes Proposed in the SNOPR
------------------------------------------------------------------------
Minimum number of
Validation class distinct models that
must be tested
------------------------------------------------------------------------
Dedicated Condensing, Medium Temperature, Indoor 2 Basic Models.
System.
Dedicated Condensing, Medium Temperature, 2 Basic Models.
Outdoor System.
Dedicated Condensing, Low Temperature, Indoor 2 Basic Models.
System.
Dedicated Condensing, Low Temperature, Outdoor 2 Basic Models.
System.
Unit Cooler connected to a Multiplex Condensing 2 Basic Models.
Unit, Medium Temperature.
Unit Cooler connected to a Multiplex Condensing 2 Basic Models.
Unit, Low Temperature.
Medium Temperature, Indoor Condensing Unit...... 2 Basic Models.
Medium Temperature, Outdoor Condensing Unit..... 2 Basic Models.
Low Temperature, Indoor Condensing Unit......... 2 Basic Models.
Low Temperature, Outdoor Condensing Unit........ 2 Basic Models.
------------------------------------------------------------------------
ACEEE, Bally, KeepRite, NCC, HTPG, AHRI, and Lennox agreed with
DOE's proposal to adopt the Working Group's AEDM validation
requirements for WICF AEDMs. (ACEEE, No. 98 at p. 1; Bally, No. 93 at
p. 1; KeepRite, No. 94 at p. 1; NCC, No. 95 at p. 1; HTPG, No. 96 at p.
2; AHRI, No. 100 at p. 2; Lennox, No. 97 at p. 3)
Interested parties also made additional recommendations regarding
the validation classes. ACEEE suggested explicitly reserving to the
Secretary the authority to enlarge the validation sample size if
needed. (ACEEE, No. 98 at p. 1) DOE notes that while it is opting not
to adopt ACEEE's suggestion, it may revisit and re-evaluate this issue
and adjust the sample size as necessary.
Lennox commented that an AEDM that has been validated for outdoor
condensing systems should be considered validated for indoor condensing
units because these validation classes are very similar except that
outdoor condensing units are exposed to a wider range of temperatures.
(Lennox, No. 97 at p. 3) DOE agrees with Lennox. The test method in
AHRI 1250-2009 for outdoor and indoor condensing units is identical
except for the ambient rating conditions. Outdoor condensing units are
tested at three ambient temperatures, 35 [deg]F, 59 [deg]F, and 95
[deg]F. The ambient rating temperature for indoor units is 90 [deg]F.
DOE believes that this condition is sufficiently similar to the 95
[deg]F outdoor rating condition such that an AEDM validated by testing
of an outdoor condensing unit would provide accurate results for indoor
condensing units. For this reason, DOE is allowing AEDMs validated for
outdoor condensing units to be extended to indoor condensing units.
However, DOE is not allowing AEDMs validated with test results from
indoor condensing units only to extend to outdoor condensing units. DOE
is making this distinction because of concerns that the other two
rating conditions for outdoor units--35 [deg]F and 59 [deg]F--could not
be adequately verified by testing at a single 90 [deg]F rating
condition. Should DOE receive additional data suggesting that such an
approach would be adequate, it may consider revisiting this issue in a
future rulemaking effort.
The CA IOUs commented that the current validation classes do not
account for variation in capacities, compressor type, refrigerant, fan
type, airflow volume, and heat exchanger coil materials and
configurations. The CA IOUs expressed concern that AEDMs that cover all
models in a validation class will be inaccurate and recommended DOE
develop guidelines for what a single AEDM can cover. (CA IOUs, No. 101
at pp. 2-3) DOE has decided to retain in the final rule the validation
classes proposed in the SNOPR. These validation classes were developed
to minimize the test burden on manufacturers, and these classes do not
preclude a manufacturer from conducting additional testing to verify
its AEDM. Similar concerns were raised during the Commercial
Certification Working Group meetings, and the parties agreed that the
requirements for validation should be kept to the lowest possible test
burden. The Working Group agreed that, because manufacturers are
ultimately responsible for ensuring the compliance of their products,
manufacturers will ensure that they have sufficient test data to
validate their own AEDMs as appropriate for the variety of designs to
which they are applying their AEDM. Additionally, DOE may request test
data used to validate an AEDM from a manufacturer or conduct
verification testing to ensure models are rated correctly. See
generally, 10 CFR 429.71 (maintenance of records).
b. Tolerances for Validation
In the February 2014 SNOPR, DOE proposed to apply the Working
Group's recommendation for validation tolerances to WICF AEDMs. For
energy efficiency metrics, the AEDM results for a model must be less
than or equal to 105 percent of the tested results for that same model.
Additionally, the AEDM's predicted efficiency for each model must meet
or exceed applicable federal energy conservation standards. DOE adopted
these same tolerances for commercial HVAC, WH, and refrigeration
equipment. See 78 FR 79579 (Dec. 31, 2013).
ACEEE, NCC, HTPG, AHRI, and Lennox supported the Department's
proposal to align the validation tolerances for WICF AEDMs to the
Working Group's recommended validation tolerances. (ACEEE, No. 98 at p.
1, NCC, No. 95 at p. 2; HTPG, No. 96 at p. 2; AHRI, No. 100 at p. 3;
Lennox, No. 97 at p. 3) ACEEE, HTPG, and Lennox also supported DOE's
proposal to utilize only one-sided tolerances that would allow
manufacturers to rate equipment conservatively. (ACEEE No. 98 at p. 1,
HTPG, No. 96 at p. 2; Lennox, No. 97 at p. 3)
Bally and KeepRite commented that DOE's proposed tolerances were
too tight. Bally suggested a two-sided validation tolerance of 8
percent be adopted to be consistent with other commercial equipment.
KeepRite made a similar suggestion. (Bally, No. 93 at p. 1; KeepRite,
No. 94 at p. 1) In DOE's view, a 5 percent one-sided tolerance is more
consistent with the AEDM validation tolerances for other types of
commercial equipment than the 8 percent two-sided tolerance suggested
by Bally and KeepRite. See 78 FR 79579 (Dec. 31, 2013) (applying a 5
percent, one-sided tolerance for all commercial HVAC, WH, and
refrigeration equipment). DOE agrees with ACCEE,
[[Page 27396]]
HTPG, and Lennox that a one-sided tolerance is preferable because it
allows manufacturers to rate equipment conservatively and account for
manufacturing and testing variability.
3. Certified Rating
DOE's current regulations provide manufacturers with some
flexibility in rating each basic model by allowing the manufacturer the
discretion to rate conservatively relative to tested values. The
Working Group recommended that, when rating using an AEDM,
manufacturers have the same flexibility. Accordingly, the Working Group
recommended that, for energy consumption metrics, each model's
certified rating must be less than or equal to the applicable Federal
standard and greater than or equal to the model's AEDM result. For
energy efficiency metrics, each model's certified rating must be less
than or equal to the model's AEDM result and greater than or equal to
the applicable Federal standard. In the February 2014 SNOPR, DOE
proposed to adopt these requirements for WICF refrigeration equipment
rated an AEDM. The Department did not receive any comments on its
proposal regarding certified ratings and is adopting it in today's
final rule.
4. Verification
DOE may randomly select and test a single unit of a basic model
pursuant to 10 CFR 429.104, which extends to all DOE covered products,
including those certified using an AEDM. As part of the AEDM
requirements for commercial HVAC, WH, and refrigeration equipment, at
DOE's request, manufacturers must perform simulations in the presence
of a DOE representative, provide analyses of previous simulations
conducted by the manufacturer, or conduct certification tests of basic
models selected by the Department. See 10 CFR 429.74(c)(4). To maintain
consistency, the Department is extending these requirements to WICF
AEDMs.
a. Failure To Meet a Certified Rating
In the February 2014 SNOPR, DOE proposed to assess a unit's
performance through third-party testing. Under this approach, DOE would
begin the verification process by selecting a single unit of a given
basic model for testing either from retail or by obtaining a sample
from the manufacturer if none are available from retail sources. DOE
would then select a third-party testing laboratory at its discretion to
test the unit selected unless no third-party laboratory is capable of
testing the equipment, in which case DOE may request testing at a
manufacturer's facility. The Department would be responsible for the
logistics of arranging the testing, and the laboratory would not be
allowed to communicate directly with the manufacturer. Additionally,
the test facility may not discuss DOE verification testing with the
manufacturer without the Department present. See 79 FR at 9643-9644.
Further, under DOE's proposal, if a unit is tested and the results
are determined to be outside the rating tolerances described in section
III.A.2.b., DOE would notify the manufacturer. This approach would also
enable the manufacturer to receive all documentation related to the
test set up, test conditions, and test results for the unit if the unit
falls outside the rating tolerances. At that time, a manufacturer would
also be able to present all claims regarding any issues directly with
the Department. See id. at 9644. If, after discussions with the
manufacturer, DOE determined that the testing was conducted
appropriately in accordance with the applicable DOE test procedure, the
rating for the model would be considered invalid. The Department notes
that 10 CFR 429.13(b) applies to equipment certified using an AEDM, and
DOE may require a manufacturer to conduct additional testing if the
manufacturer violates an applicable standard or certification
requirement.
HTPG commented that DOE should allow the option for a second sample
to be tested to ensure that abnormal failures unrelated to design or
predictable variations do not adversely impact an otherwise sound model
type. (HTPG, No. 96 at pp. 2-3) As stated above, if a unit is
determined to be outside the prescribed rating tolerances, the
Department would provide the manufacturer with all documentation
related to the test set up, test conditions, and test results. At that
time, the manufacturer may initiate a discussion with the Department
regarding any concerns related to the test. For these reasons, DOE has
determined it is not necessary to automatically allow testing of a
second sample. DOE, at its discretion, may decide testing an additional
sample is appropriate in cases where the tested sample has been found
to be defective.
NCC commented that any basic model that fails to meet its certified
rating should be re-certified based upon test data. If that model was
used to validate an AEDM, then the AEDM should be re-validated (NCC,
No. 95 at p. 2) DOE understand these suggestions and while DOE may
require a manufacturer to conduct additional testing if the
manufacturer has been found to be in violation of an applicable
standard or certification requirement, the Department prefers not to
mandate additional testing and instead evaluate such a requirement on a
case-by-case basis. The Department is not inclined to mandate
additional testing because of the burden it imposes. In terms of re-
validation, as long as the manufacturer has sufficient test data
underlying the AEDM to meet the validation requirements, additional
testing for re-validation would not be required by DOE.
AHRI suggested that DOE apply the verification requirements adopted
for commercial HVAC, WH, and refrigeration equipment to walk-ins. It
requested that DOE include the provisions for witness testing and
engineered-to-order equipment. (AHRI, No. 100 at p. 3) In this final
rule, DOE has aligned the AEDM verification methodology for walk-ins to
match the provisions for commercial HVAC, WH, and refrigeration
equipment. However, the engineered-to-order concept is outside the
scope today's rulemaking. DOE will address the engineered-to-order
concept and other certification issues in a future rulemaking.
The CA IOUs commented that DOE's verification process is poor and
not easily enforceable. Additionally, the CA IOUs raised the concern
that WICF manufacturers are not as active in industry certification
programs as other types of commercial equipment manufacturers. They
assert that these two factors could undermine both the potential energy
savings that would be likely to accrue from any standards that DOE
issues and fair competition. The CA IOUs recommended that DOE work with
AHRI and ASHRAE to develop calculation tools for WICF manufacturers.
(CA IOUS, No, 101 at p. 2) The Department appreciates the suggestion
from the CA IOUs; however, DOE finds that manufacturers are better
suited for developing modeling tools for their own equipment because
they have more intimate knowledge of their own equipment's operational
and design characteristics. Thus, a model developed by the basic
model's manufacturer is likely to be more accurate than a general model
developed by the Department. And since DOE may request any of the
relevant data and documentation a manufacturer has used to develop a
given AEDM, in DOE's view, there is sufficient incentive for a
manufacturer to take appropriate steps to ensure both the thoroughness
and accuracy of its AEDMs.
[[Page 27397]]
b. Action Following Determination of Noncompliance Based Upon
Enforcement Testing
Rather than require the revalidation of an AEDM if a noncompliant
model had been used to validate that AEDM, DOE proposed that each AEDM
must be supported by test data obtained from physical tests of current
models. Because a noncompliant model may not be distributed in
commerce, and so must be discontinued and can no longer be considered a
current model, the manufacturer will need to ensure that the AEDM
continues to satisfy the proposed validation requirements described in
section III.A.2 Additional testing would only be necessary if the
noncompliant equipment was used as a sample for validating the AEDM. In
that case, the manufacturer must perform additional testing of a
different model to ensure the AEDM is valid. Pursuant to this
requirement, should such testing result in a change in the ratings of
equipment certified using the AEDM, then those pieces of equipment must
be re-rated and re-certified.
HTPG supported DOE's approach and stated that re-validation of an
AEDM should only be required if a non-compliant model was used to
validate the AEDM. (HTPG, No. 96 at pp. 2-3) It added that DOE should
permit the use of a second sample to address possible abnormal
failures. DOE notes that its proposed approach, which is based on the
use of physical tests of a sample of models would not require on the
results of tests from a single model and would account for abnormal
failures that may occur. No other comments were received. Consequently,
DOE is adopting the approach detailed in its proposal.
5. Re-Validation
DOE evaluated different circumstances that may require a
manufacturer to re-validate an AEDM. These circumstances are described
in more detail below. In response to this proposal in the SNOPR, ACEEE
made a general comment that DOE's proposed treatment of the
revalidation process appears to assure a good balance between testing
burdens and trusted certifications. (ACEEE, No. 98 at p. 1)
a. Change in Standards or Test Procedures
In the February 2014 SNOPR, DOE proposed not to require re-
validation every time the test procedure or standard changes. However,
should DOE believe that re-validation is necessary pursuant to a final
rule standard or test procedure, DOE would raise that issue in the
appropriate NOPR and solicit comment from the public on the merits of
including revalidation.
HTPG and NCC agreed with the Department's proposal to evaluate the
necessity to re-validate an AEDM due to a federal energy conservation
standard or test procedure change on a case-by-case basis. (HTPG, No.
96 at p. 3; NCC, No. 95 at p. 2) AHRI also commented that re-validation
should only be required when a change in test procedure is significant
enough to result in a product having a different rated value for energy
consumption or efficiency. (AHRI, No. 100 at p. 3)
b. Re-Validation Using Active Models
DOE proposed to require manufacturers to re-validate their AEDMs if
one of the basic models used for validation is no longer in production
or if it becomes obsolete. See 79 FR at 9843. DOE did not receive any
comments regarding this proposal and is adopting it in today's final
rule. DOE is concerned that an AEDM's accuracy may be compromised if
the models that are used to validate it become obsolete. DOE encourages
manufacturers to test their models beyond the minimum validation
requirements as a means to affirm an AEDM's validity. As long as the
manufacturer has sufficient test data underlying the AEDM to meet the
validation requirements and can readily produce that documentation on
request, additional testing for re-validation would not be required by
DOE.
c. Time Allowed for Re-Validation
In the February 2014 SNOPR, DOE declined to propose a time limit to
re-validate an AEDM. A manufacturer would need to ensure that any AEDM
it uses for purposes of certifying its equipment satisfies the
validation requirements and that the necessary supporting documentation
is available to DOE on request. AHRI agreed with DOE that a time limit
should not be imposed because it is consistent with the AEDM
requirements for commercial HVAC, WH, and refrigeration equipment.
(AHRI, No. 100 at p. 3)
Lennox disagreed with the DOE's proposal not to include a time
limit and the Department's statement that AEDMs must satisfy the
fundamental validation requirements at all times. Lennox explained that
without setting a time limit on the validity of a given AEDM, a change
in federal standards, federal test procedure, basic model status, or a
failure of a basic model could invalidate all certifications made using
an AEDM. This situation could cause significant adverse economic
impacts on manufacturers because it would reduce their ability to bring
products to market while performing the additional testing required for
re-validating the AEDM. Lennox recommended that if re-validation occurs
due to an amended federal test procedure or energy conservation
standard, then re-validation should not be required until the later of
(1) 180 days after the final rule for the amended federal test
procedure or energy conservation standards or (2) the effective date of
that amended test procedure or standard. If re-validation is required
due to a basic model becoming invalid or the failure of a basic model
to meet its certified rating, DOE should allow a minimum of 120 days
for the AEDM to be re-validated. (Lennox, No. 97 at p. 4) DOE agrees
that in some circumstances a time limit should be imposed for re-
validating AEDMs, such as in the case where a federal test procedure or
energy conservation standard is amended. However, DOE prefers that the
re-validation time limit be established on a case-by-case basis in the
course of each particular rulemaking instead of mandating a specific
time frame. Applying a more tailored approach would allow stakeholders
of the particular rulemaking and the Department to evaluate how
substantial the change may be and how much time would be required for
the affected manufacturers to address such changes.
The February 2014 SNOPR also inadvertently included a request for
comment on a 90-day allowance for manufacturers to re-validate, re-
rate, and recertify an AEDM. DOE received comments from Bally,
KeepRite, NCC, and HTPG stating that 90 days was insufficient and that
a period of time around 120-180 days was more appropriate. (Bally, No.
93 at p. 2; KeepRite, No. 94 at p. 2; NCC, No. 95 at p. 2; HTPG, No. 96
at p. 3) As DOE is not establishing a time limit for re-validations in
this Final Rule, and will instead handle this on a case-by-case basis,
DOE is not adopting any of the suggested time periods offered by these
commenters.
B. Refrigeration Test Procedure
During DOE's rulemaking to establish test procedures for WICF
equipment, which resulted in a final rule published on April 15, 2011
(``April 2011 test procedure final rule;'' 76 FR 21580), interested
parties supported DOE's approach to use AHRI 1250 (I-P)-2009, ``2009
Standard for Performance Rating of Walk-In Coolers and Freezers''
(``AHRI 1250-2009''), for WICF refrigeration testing. AHRI 1250-2009 is
an industry-developed testing protocol used to measure walk-in
efficiency. In
[[Page 27398]]
the 2014 SNOPR, DOE proposed to add certain modifications to its
procedures for manufacturers to follow when applying AHRI 1250-2009.
These proposed changes were designed to either clarify certain steps in
AHRI 1250-2009 or reduce the testing burden of manufacturers while
ensuring that accurate measurements are obtained. These modifications
are discussed in the following sections.
1. Component-Level Ratings for Refrigeration: Overall
Responding to a number of comments addressing DOE's proposed energy
conservation standards, DOE's February 2014 SNOPR proposed an approach
to allow manufacturers to test a separately-sold condensing unit or
unit cooler and generate an AWEF metric consistent with the existing
system-based test procedure. Under the proposed approach, a
manufacturer who sells a unit cooler model without a matched condensing
unit must rate and certify that model as part of a refrigeration system
basic model containing that unit cooler model by testing according to
the methodology in AHRI 1250-2009 for unit coolers used with a parallel
rack system (see AHRI 1250-2009, section 7.9). The manufacturer would
use a calculation method to determine the system AWEF and certify this
AWEF to DOE. Additionally, all unit coolers tested with this method
would need to comply with any of the applicable standards that DOE may
decide to adopt for the multiplex equipment classes addressed in its
standards proposal. A manufacturer who sells a condensing unit model
separately must rate and certify that model as part of a refrigeration
system basic model containing that condensing unit model by conducting
the condensing unit portion of the AHRI 1250-2009 mix/match test
method. The results from the mix/match test would be combined with a
nominal unit cooler capacity and power, based on nominal values for
saturated suction temperature and unit cooler fan and electric defrost
energy use factors (or the hot gas defrost calculation methodology, as
applicable), in order to calculate an AWEF for the refrigeration system
basic model containing that condensing unit. 79 FR at 9830.
All commenters supported DOE's proposal to allow rating and
certification for unit coolers and condensing units separately. (Bally,
No. 93 at p. 2; Keeprite, No. 94 at p. 2; NCC, No. 95 at pp. 2-3; HTPG,
No. 96 at p. 3; ACEEE, No. 98 at p. 1; ASAP, et al., No. 99 at p. 2; CA
IOUs, No. 101 at p. 1; AHRI, No. 100 at p. 4; and Lennox, No. 97 at p.
5) Several commenters, however, suggested that DOE clarify the
circumstances under which unit coolers and condensing units may be
rated separately or as a matched system. Keeprite and AHRI suggested
that if a manufacturer of a unit cooler and condensing unit rates each
component as a separate basic model, the manufacturer should not need
to re-rate the components as a combined system even if they are
marketed and sold together. However, they further suggested the matched
system test method should be used if the system is a packaged system or
the components are exclusively marketed and sold as a matched system.
(Keeprite, No. 94 at p. 2; AHRI, No. 100 at pp. 4-5) NCC stated that,
except for packaged systems and those units paired in marketing
literature, manufacturers should be permitted to rate all unit coolers
and condensing units separately. (NCC, No. 95 at pp. 2-3) Similarly,
Lennox requested that DOE clarify that only models exclusively marketed
and sold as a matched system must be rated as a matched system, and
that manufacturers should be allowed to match components as a service
to the customer without having to test each combination if the
components were previously rated separately. (Lennox, No. 97 at pp. 5-
6)
The CA IOUs, on the other hand, recommended that DOE require unit
coolers and condensing units to be rated separately unless they are
part of a unitary (self-contained) system or a matched variable
refrigerant flow system. Otherwise, if DOE allows matched equipment
rating for combinations of ``remote'' unit coolers and condensing units
(i.e., those produced as separate pieces of equipment), then DOE should
also require the manufacturer to calculate the efficiency ratings of
each component as though it were to be sold separately and, if they
have a lower rating when rated separately, DOE should require an annual
accounting of shipments to ensure they are always sold as combined
systems. (CA IOUs, No. 101 at pp. 1-2) ASAP, et al. agreed that DOE
should ensure that unit coolers and condensing units rated as ``matched
pairs'' are only sold as ``matched pairs'' unless the components are
also rated separately, to prevent the situation where an inefficient
component is rated with a highly efficient component as a matched pair,
but the inefficient component is also sold separately, resulting in
lost energy savings. (ASAP, et al., No. 99 at pp. 1-2) HTPG, on the
other hand, stated that the rating of matched systems should be allowed
in order for the AWEF ratings to reflect technology advances that
require closely matching unit coolers and condensing units. (HTPG, No.
96 at p. 3) The CA IOUs also recommended that the mix-match approach be
dropped from the standard and that DOE not require measurement of
condensing unit performance at two different suction pressures for each
ambient temperature application, which reduces manufacturer test
burden. (CA IOUs, No. 101 at p. 2)
In this rule, DOE finalizes an approach that would allow
manufacturers to test a condenser or unit cooler separately, but rate
that component as part of a refrigeration system with an AWEF metric
consistent with DOE's proposed energy conservation standards for WICF
refrigeration systems. First, DOE agrees with Keeprite, AHRI, NCC, and
Lennox that, if components are rated separately for the purposes of
certifying and complying with the DOE standard, they do not need to be
rated as a matched system if they are later combined and sold as a
matched system, either by their original manufacturer or an installer.
If, however, a manufacturer wishes to make a representation of a
matched system's efficiency that is higher than the ratings achieved
individually by each component, the manufacturer must base that
representation on the rating obtained through testing of the matched
system. Second, DOE agrees with the CA IOUs and ASAP, et al. that a
component must be certified individually and must individually comply
with DOE's standards if it is sold separately by its manufacturer.
However, DOE does not intend to prevent manufacturers from rating and
certifying matched systems in order to reflect technological advances
achievable with matched systems, as pointed out by HTPG. DOE recognizes
that certain refrigeration systems, such as packaged or unitary systems
that consist of a single piece of equipment, or systems that implement
a multiple-capacity condensing unit, can only be rated as matched
systems under the current test procedure. DOE recognizes that, as
pointed out by the CA IOUs, the mix-match procedure is not needed under
this approach, as components sold separately would be rated using the
separate rating methodology, and components sold as a matched system
would be rated using the matched system test procedure. Therefore, DOE
is removing the mix-match suction temperature conditions from the test
method for clarity and consistency with
[[Page 27399]]
its overall rating and certification approach.
Some commenters also urged DOE to supplement the proposed separate-
standards approach with a product labeling requirement to improve the
enforceability of the standard. ASAP, et al. stated that the component
level approach could create a loophole whereby a component manufacturer
could avoid having to meet DOE's walk-in standards by claiming that its
component is not designed for use in walk-ins or by declining to
specify an application for the equipment. In the short term, it
suggested that DOE should require all components sold for use in a
walk-in to bear a label indicating that they are certified for walk-in
use, and issue revised compliance guidance clarifying that walk-in
component standards apply to equipment that has the attributes
associated with typical walk-in components in the absence of a
manufacturer's specific instruction that the equipment is not for use
in walk-ins. In the long term, DOE should develop energy conservation
standards for components independent of end-use. (ASAP, et al., No. 99
at pp. 2-3) Furthermore, ASAP, et al. stated that DOE should require
unit coolers and condensing units rated and sold as matched pairs to
bear a label stating that each is only for sale when matched with the
other component. (ASAP, et al., No. 99 at p. 2) Similarly, the CA IOUs
recommended that DOE develop compliance and labeling requirements such
that all major walk-in components would carry a label certifying that
they comply with the walk-in efficiency regulations. If DOE allows
matched pairs of unit coolers and condensing units where one of the
components does not comply with the standard individually, the labeling
scheme should ensure that the deficient component is only installed
with the matched component that results in the combined system
efficiency that complies with the DOE standard. (CA IOUs, No. 101 at p.
6)
DOE agrees with the CA IOUs and ASAP, et al. and recognizes the
importance of labeling in facilitating compliance and enforcement
throughout the WICF distribution chain, and in ensuring that systems
rated as matched systems are only sold in their matched configuration.
Although DOE is not establishing labeling requirements at this time, it
may consider establishing labeling requirements in a future
certification, compliance, and enforcement rulemaking.
2. Component-Level Ratings for Refrigeration: Metrics
Two interested parties commented on the metrics used to rate
individual components. The CA IOUs recommended that the performance
metric for condensing units be the Annual Energy Efficiency Ratio
(AEER) because it is simpler to calculate than AWEF and can be expanded
to a broader range of condensing units than those used in walk-in
applications. (CA IOUs, No. 101 at p. 3) AHRI also suggested that
condensing units and unit coolers sold separately should have a
separate metric than AWEF, as the use of AWEF implicitly allows for
component ratings to be compared to system ratings. (AHRI, No. 100 at
pp. 5-6)
In this final rule, DOE is retaining AWEF as the metric for rating
refrigeration systems and for refrigeration system components
(condensing units and unit coolers) rated as part of a refrigeration
system, as this is the metric used in the DOE test procedure, which is
based on the industry testing protocol AHRI 1250-2009. If the industry
develops a future revision of this test method with different metrics,
such as AEER or another, separate metric for component ratings, then
DOE may consider adopting it in a future rulemaking.
Neither the refrigeration test procedure nor the proposed energy
conservation standard incorporates standby or off-mode energy use
because the vast majority of WICFs must operate at all times to keep
their contents cold. The CA IOUs recommended that the refrigeration
system metric account for stand-by losses, particularly for condensing
units when the compressor is off, as condensing unit ancillary loads
such as the crankcase heater, transformer, and control electronics can
contribute significantly to the energy consumption. (CA IOUs, No. 101
at p. 4)
DOE agrees that, when considered individually, condensing units may
experience standby energy use when the compressor is not running. DOE
carefully considered this issue but is not currently aware of any
recognized or well-accepted methods for measuring standby condenser
energy use. However, if the industry develops a test method to
determine this energy usage, then DOE may consider adopting it in a
future rulemaking.
3. Component-Based Ratings for Refrigeration Systems: Nominal
Calculation Values
In the SNOPR, DOE proposed nominal values for unit cooler capacity
and power to be used when rating a condensing unit as an individual
component of a refrigeration system using an AWEF metric. DOE developed
the nominal values from DOE testing and modeling of WICF refrigeration
systems and published the test data on which the nominal values were
based. 79 FR at 9830.
In general, stakeholders agreed with the use of nominal unit cooler
values to rate condensing units. (CA IOUs, No. 101 at p. 3; Bally, No.
93 at p. 2; NCC, No. 95 at p. 3; HTPG, No. 96 at p. 4; AHRI, No. 100 at
p. 5; and Lennox, No. 97 at p. 2) However, some were concerned that
components rated separately would not be able to meet DOE's energy
conservation standards. AHRI expressed concern about the effect of the
rating strategy on minimum efficiency levels and recommended that DOE
conduct a thorough and public analysis to alleviate the concern that
the AWEFs proposed in the energy conservation standards NOPR would not
be achievable by refrigeration components rated separately. (AHRI, No.
100 at pp. 5-6) NCC also suggested that DOE conduct an evaluation to
ensure the energy efficiency standard levels are achievable with this
approach. (NCC, No. 95 at p. 3) With respect to AHRI's concern that the
AWEF standards are not achievable by refrigeration components, DOE
notes that it has structured its nominal values assuming that the
condensing units are paired with unit coolers that would meet whatever
standard, if any, that DOE may eventually adopt. Thus, condensing unit
manufacturers should not incur a penalty if they rate their condensing
unit as part of a matched system or as an individual component. The
following paragraphs address specific comments or concerns about the
three main nominal values used in the equations: on-cycle evaporator
fan power, off-cycle evaporator fan power, and defrost energy.
a. On-Cycle Evaporator Fan Power
In the SNOPR, DOE proposed a nominal value for on-cycle evaporator
fan power of 0.016 Watts per Btu/h of gross capacity at the highest
ambient rating condition, based on test and modeling data. 79 FR at
9831.
Lennox commented that the proposed nominal value for fan power for
unit coolers is based on test data that only covered the low end of the
full range of
[[Page 27400]]
capacities of equipment used in WICF enclosures. On-cycle fan power is
not a constant value as a function of unit capacity, but increases as
the unit capacity increases as a result of the long air throw (that is,
the distance the air must travel after it leaves the fan) required by
this type of equipment. (Lennox, No. 97 at pp. 2, 5)
In response to Lennox's comment, DOE surveyed a wider range of unit
coolers to compare unit cooler fan wattage to unit capacity. DOE found
that its nominal value of 0.016 for unit cooler fan wattage per
capacity was valid for low temperature systems even at capacities up to
250,000 Btu/h; however, a lower nominal value was more appropriate for
medium temperature systems. (DOE was not able to find manufacturer
specifications for larger capacities of unit coolers). Therefore, DOE
is retaining its nominal value of 0.016 for low temperature unit cooler
on-cycle fan power and implementing a nominal value of 0.013 for medium
temperature unit cooler on-cycle fan power. The data and analysis
underlying this finding are included in the docket at https://www.regulations.gov/#!docketDetail;D=EERE-2008-BT-STD-0015.
b. Off-Cycle Evaporator Fan Power
In the SNOPR, DOE proposed a nominal value for off-cycle evaporator
fan power of 0.2 times the on-cycle evaporator fan power. 79 FR at
9831. The CA IOUs noted that this default value is appropriate only if
DOE assumes that unit coolers are using variable speed evaporator fans
and dropping their fan speed to 50 percent of flow during the off-cycle
periods. (CA IOUs, No. 101 at pp. 3-4) DOE's nominal fan power values
are based on the approach taken in DOE's proposed standards. That
approach, in turn, is based on the potential use of unit coolers that
incorporate variable speed evaporator fans. Variable speed evaporator
fans comprise one of the technology options on which the proposed
energy conservation standard is based. Therefore, DOE is including this
assumption to ensure that condensing unit manufacturers are not
unfairly penalized in comparison to matched system manufacturers.
c. Defrost Energy
In the SNOPR, DOE proposed a nominal value for electric defrost
energy of 0.12 Watt-hours per defrost cycle, per Btu/h of gross
capacity at the highest ambient rating condition, and that four (4)
cycles per day should be assumed unless specified otherwise in the
manufacturer's installation instructions. See 79 FR at 9831. This 4-
cycle approach uses the same number of cycles that DOE built into its
walk-in standards analysis. Under this approach, the daily electric
defrost heat contribution would be 0.95 times the daily electric
defrost energy use, converted from Watt-hours to Btu. These nominal
values are only applicable to low-temperature refrigeration systems. 79
FR at 9831. DOE also specified that condensing units designed to be
used with a hot gas defrost unit cooler, rather than an electric
defrost unit cooler, must use the nominal values for hot gas defrost
heat load and energy use--that is, the daily hot gas defrost heat
contribution would be 0.18 btu per defrost cycle, per Btu/h of gross
capacity at the highest ambient rating condition; and the daily defrost
energy shall be equivalent to half the calculated daily defrost heat
converted from Btu to watt-hours. 79 FR at 9830-9832.
The CA IOUs suggested that the application of the unit cooler
nominal values for defrost are fixed values that a manufacturer would
use. In its view, the proposed regulatory text seems to imply that the
manufacturer's instructions would never contain any assumed values
regarding the number of applicable cycles that would apply.
Consequently, the CA IOUs suggested that DOE clarify the final
regulatory text by indicating that the assumed number of cycles be
fixed at 4 cycles per day. (CA IOUs, No. 101 at pp. 3-4)
In response to the CA IOUs' comment, DOE believes there may be some
defrost control mechanisms that reside in the condensing unit, with
associated manufacturer instructions. To account for this possibility,
DOE is providing manufacturers with the flexibility to specify the
number of defrost cycles that may occur. In an effort to avoid limiting
the manufacturers' ability to reduce the number of defrosts, DOE is
retaining the option to test according to manufacturers' instructions.
However, in investigating this issue, DOE recognizes that the approach
taken in DOE's proposed standards is based on the potential use of
defrost controls that may reside in the unit cooler and not in the
condensing unit. Defrost controls comprise one of the technology
options on which the proposed energy conservation standard is based.
Therefore, DOE is revising its default value for the number of defrosts
per day to 2.5 to ensure that condensing unit manufacturers are not
unfairly penalized in comparison to matched system manufacturers.
Lennox commented that the test data used by DOE to establish the
nominal value for defrost energy does not represent the full range of
capacities used in WICFs. The nominal value for daily defrost energy
use of 0.12 W-h/cycle per BTU/h of capacity is representative for
smaller capacity units but not larger capacity units, because the
defrost energy (W-h/cycle per BTU/h) is not a constant value as a
function of unit capacity. The defrost energy increases, but not
linearly, as the unit capacity increases due to the larger coil sizes
and corresponding heater wattage required for larger capacity units.
(Lennox, No. 97 at pp. 6-7)
In response to Lennox's comment, DOE surveyed a wider range of unit
coolers (with capacities up to 250,000 Btu/h) to compare defrost
wattage and energy-to-unit capacity. DOE found that electric defrost
wattage increases linearly with capacity, but, consistent with the
analysis DOE performed for its energy conservation standards
rulemaking, defrost duration would also be expected to increase
nonlinearly with capacity. Thus, DOE agrees with Lennox's assessment
that total defrost energy increases non-linearly with capacity. As a
result of its analysis, DOE is expressing the electric defrost energy
as a power function instead of a linear equation. The data and analysis
underlying the development of this equation are included in the docket
at https://www.regulations.gov/#!docketDetail;D=EERE-2008-BT-STD-0015.
DOE also clarifies that condensing units designed to be used with
hot gas defrost unit coolers may use the nominal values associated with
hot gas defrost systems. For clarity, DOE has added these values as
nominal values for unit cooler energy use factors. DOE is also
expressing the values in the form of equations that incorporate the
capacity variable to emphasize that they are functions of the given
unit's capacity.
Table III.5, below, contains DOE's revisions to the nominal values
for unit coolers.
[[Page 27401]]
Table III.5--Calculations for Unit Cooler Saturated Suction Temperature and Energy Use Factors
----------------------------------------------------------------------------------------------------------------
Medium temperature Low temperature
----------------------------------------------------------------------------------------------------------------
Saturated Suction Temperature ([deg]F)... 25..................................... -20.
On-cycle evaporator fan power (W)........ 0.013 x Q*............................. 0.016 x Q.
----------------------------------------------------------------------
Off-cycle evaporator fan power (W)....... 0.2 x on-cycle evaporator fan power.
----------------------------------------------------------------------
Electric defrost energy per cycle (W-h/ 0...................................... 8.5 x 10-3 x Q\1.27\
cycle).
Electric defrost heat contribution per 0...................................... 0.95 x electric defrost
cycle (Btu/cycle). energy use per cycle x
3.412.
Hot gas defrost energy per cycle (W-h/ 0...................................... 0.5 x hot gas defrost heat
cycle). contribution per cycle/
3.412.
Hot gas defrost heat contribution per 0...................................... 0.18 x Q.
cycle (Btu).
----------------------------------------------------------------------
Number of cycles per day................. As specified in installation instructions or, if no instructions, 2.5
----------------------------------------------------------------------------------------------------------------
* Q represents the gross capacity at the highest ambient rating condition in Btu/h.
4. Other Test Procedure Changes
In the SNOPR, DOE proposed several other changes to clarify or
simplify elements of the test procedure to reduce overall test burden.
These changes, discussed below, consist of a variety of modifications
related to both refrigeration systems and panel insulation. HTPG
generally agreed with the changes and stated they would reduce testing
burden and improve manufacturers' ability to respond to DOE's proposed
standards. (HTPG, No. 96 at p. 4) Concurrent with this rulemaking, AHRI
formed a committee to update the AHRI 1250-2009 test procedure. In its
comment, AHRI stated that its latest updates to AHRI 1250 had adopted
most of DOE's proposed changes in the SNOPR, with a few minor
alterations. AHRI included a courtesy copy of the draft AHRI 1250
update, titled AHRI 1250-2014, with its comment to DOE. (AHRI, No. 100
at p. 2) DOE has reviewed AHRI's update to the test method and has
incorporated many of the changes. (Specific details on changes and
associated comments are discussed in the following sections.) DOE
intends to begin the process of incorporating by reference the entirety
of the updated version, which will require a separate rulemaking.
Meanwhile, DOE is retaining its approach of amending the current test
procedure (AHRI 1250-2009) in the regulatory language.
a. Nominal Values for Defrost Energy and Heat Load Calculations
In the SNOPR, DOE proposed a calculation methodology that would be
used for calculating some aspects of electric defrost energy use in
lieu of using certain tests for electric defrost energy use.
Specifically, DOE proposed that the only required test for electric
defrost energy use of unit coolers is the test to determine the energy
input for the dry coil condition. The nominal values for frosted coil
energy use, number of defrosts per day in the event that the unit
cooler has an adaptive defrost system, and daily contribution of heat
load attributed to defrost could then be calculated using nominal
values rather than having to conduct their individual respective tests.
Furthermore, as there is currently no industry-accepted method for
calculating hot gas defrost energy use and heat load, DOE proposed
nominal values for calculating these quantities for systems utilizing
hot gas defrost. 79 FR at 9831-9832.
Lennox agreed with DOE's proposal to make the full defrost tests
optional, as well as a portion of the adaptive defrost test. (Lennox,
No. 97 at p. 6) AHRI incorporated DOE's nominal values and calculation
methodology for electric and hot gas defrost into its update of AHRI
1250. (AHRI, No. 100 at pp. 56-58) HTPG, however, noted that the
calculation methods for hot gas defrost do not allow for some of the
advanced methods being utilized in the market or that may be likely to
occur in the near future. HTPG proposed that DOE work with industry to
develop a test method to give credit to the energy advantages of
various hot gas defrost methods. (HTPG, No. 96 at p. 4)
After carefully considering these comments, DOE has decided to
retain the nominal values for calculating frosted coil energy use,
number of defrosts per day if the unit has an adaptive defrost system,
and daily contribution of heat load, as well as nominal values for
calculating hot gas defrost energy use and heat load. DOE agrees with
HTPG that a test procedure for hot gas defrost would be beneficial to
capture innovative technologies not currently accounted for by the
calculation methodology. Should the industry develop a test method for
rating hot gas defrost systems, DOE may consider adopting it.
b. Off-Cycle Evaporator Fan Test
In the SNOPR, DOE proposed to amend one aspect of its test
procedure that incorporates AHRI 1250-2009. Specifically, DOE raised
the possibility of amending that portion of its procedure that involves
AHRI 1250-2009, section C10 by changing the currently specified
requirement that when conducting the off-cycle evaporator fan test,
controls shall be adjusted so that the greater of a 25 percent duty
cycle or the manufacturer default is used for measuring off-cycle fan
energy; and for variable speed controls, the greater of 25 percent fan
speed or the manufacturer's default fan speed shall be used for
measuring off-cycle fan energy. In the SNOPR, DOE proposed to amend the
maximum off-cycle fan cycling or speed reduction to 50 percent of on-
cycle duty cycle or 50 percent of on-cycle fan speed. 79 FR at 9832.
The CA IOUs supported DOE's proposal, citing research that found that a
50 percent reduction in fan speed did not have significant impacts on
product temperatures, room temperature stratification, or infiltration.
(CA IOUs, No. 101 at pp. 4-5) Lennox and AHRI also agreed with the
proposed modification, and AHRI noted that they included the
modification in their revised test procedure, AHRI 1250-2014. (Lennox,
No. 97 at p. 7; AHRI, No. 100 at p. 10) In the absence of any objection
to its proposed approach, DOE is adopting its proposed amendment.
c. Refrigerant Oil Testing
In the SNOPR, DOE proposed to eliminate from its requirements that
AHRI 1250-2009, section C3.4.6 be followed when conducting a test of
walk-in refrigeration systems. That incorporated provision requires
that a measurement be taken of the ratio of oil
[[Page 27402]]
to refrigerant in the liquid refrigerant passing from the condenser to
the unit cooler for all condensing units with on-board oil filters. 79
FR at 9832. Lennox agreed with DOE's proposal to eliminate the
requirement for oil circulation test for units with integrated oil
separators and with the assumption that the associated oil circulation
ratio would be less than 1 percent. (Lennox, No. 97 at p. 7) The CA
IOUs supported DOE's proposed removal of the requirement for
refrigerant oil testing for systems with oil separators and added their
collective belief that manufacturers do not anticipate that any new
WICF refrigeration system being tested would likely have negligible oil
in the refrigerant. They stated that the proposal to remove the oil
testing requirement should apply to all systems and not just those with
in-line oil separators. The CA IOUs recommended DOE investigate this
claim and if correct, remove the requirement for all systems. (CA IOUs,
No. 101 at p. 5) NCC and AHRI also supported removing the oil testing
requirement for all systems, not just systems with oil separators, as
single-compressor condensing units do not generally have oil
separators. These commenters asserted that conducting oil testing would
be time-consuming, expensive, and unnecessary. (NCC, No. 95 at p. 3;
AHRI, No. 100 at p. 6) In light of these comments, DOE is removing the
oil testing requirement for all systems due to the test burden involved
and its belief that refrigerant oil is not a significant factor in new
systems. If, however, DOE finds that refrigerant oil is affecting the
repeatability or accuracy of the testing, DOE may reinstate this
requirement at a later time.
d. Temperature Measurement
In the SNOPR, DOE proposed that the required tolerance for test
temperature measurement be maintained at 0.5[emsp14][deg]F
for measurements at the inlet and outlet of the unit cooler, but be
altered to 1.0[emsp14][deg]F for all other temperature
measurements, allowing for the use of smaller temperature measurement
probes which can more easily be placed in contact with the refrigerant
while not impeding its flow. Additionally, DOE proposed to allow the
test to be conducted using sheathed sensors immersed in the flowing
refrigerant for refrigerant temperature measurements upstream and
downstream of the unit cooler, in order to reduce test burden. No
refrigerant temperature measurements other than those upstream and
downstream of the unit cooler would require a thermometer well or
sheathed sensor immersion. 79 FR at 9832.
The CA IOUs supported DOE's proposal to allow refrigerant
measurements upstream and downstream of the unit cooler to be conducted
using either sheathed sensors or thermocouple wells immersed in flowing
refrigerant. (CA IOUs, No. 101 at p. 5) AHRI noted its update to the
test procedure, AHRI 1250-2014, incorporates DOE's proposed approach
for temperature measurement. (AHRI, No. 100 at p. 10) Keeprite, on the
other hand, believed the type of temperature sensor should not be
specified as there are other methods or technologies that exist that
could achieve the specified tolerances. (Keeprite, No. 94 at p. 2)
In light of the comments, DOE is adopting the modifications to the
temperature measurement approach in this final rule. In response to
Keeprite's comment, DOE notes that the approach being adopted today
incorporates methods that have been established and accepted by
industry for accurate measurement of temperature. If DOE becomes aware
of other, equally valid methods or technologies for measuring
temperature, it may consider adopting them as acceptable methods in the
DOE test procedure.
e. Test Condition Tolerances
In the SNOPR, DOE proposed to modify the existing test procedure
tolerances to:
Set a test condition tolerance for the frequency of
electrical power;
Clarify that the stated maximum allowable voltage
imbalance for three-phase power supply refers to the maximum imbalance
for voltages measured between phases, rather than phase-to-neutral;
Delete the requirements related to the test condition
tolerances or measurements of air leaving the unit; and
Remove the tolerances for wet bulb temperature on the
outdoor system conditions, except for units with evaporative cooling.
DOE proposed to retain all other measurement tolerances for air
entering the heat exchangers, including dry bulb outdoor conditions and
dry bulb and wet bulb indoor conditions (wet bulb temperature or
humidity levels greater than the required test conditions could cause
excessive frosting of the coil and affect its rated capacity). 79 FR at
9832-9833.
The CA IOUs supported DOE's proposed changes to the instrumentation
accuracy requirements and DOE's recommendation not to require or set
accuracy requirements for air temperature exiting unit coolers. The CA
IOUs also agreed that air temperature leaving unit coolers need not be
measured and that maintaining condensing unit entering air wet-bulb
temperatures should only be applicable to the testing of evaporatively
cooled condensing units, but supported maintaining both the specified
dry-bulb and relative humidity conditions for air entering the unit
cooler. (CA IOUs, No. 101 at p. 5) AHRI noted that its update to the
test procedure, AHRI 1250-2014, incorporates DOE's proposed test
procedure tolerances. (AHRI, No. 100 at p. 10) In light of the
comments, DOE is adopting its proposed tolerances.
f. Pipe Insulation and Length
In the SNOPR, DOE proposed that pipe lines between the unit cooler
and condensing unit insulation be equivalent to a half-inch thick
insulation with a material having an R-value of at least 3.7 per inch,
and that flow meters would not need to be insulated but must not
contact the floor. DOE also proposed to clarify the requirements on
piping length such that:
The length of piping between the condenser and unit cooler
does not include any flow meters;
The length of piping allowed within the cooled space shall
be a maximum of 15 feet; and
In the event that there are multiple branches of piping
inside the cooled space, the 15-foot limit shall apply to each branch
individually instead of the total piping length. 79 FR at 9833.
Lennox supported DOE's proposed clarification of pipe insulation
and length requirements. (Lennox, No. 97 at p. 7) AHRI noted it has
already incorporated DOE's proposed requirements for pipe insulation
and length in its latest revision to the test method, AHRI 1250-2014.
(AHRI, No. 100 at p. 73) In light of the comments, DOE is adopting its
proposed modifications to piping insulation and length requirements.
g. Composition Analysis
In the SNOPR, DOE proposed to remove the current requirement in its
procedure that a refrigerant composition analysis be conducted for
systems with zeotropic refrigerant mixtures. 79 FR at 9833. Lennox and
the CA IOUs supported the proposal. (Lennox, No. 97 at p. 7; CA IOUs,
No. 101 at p. 5) ACEEE recommended that if changes in the ratios of the
zeotropic blend could significantly affect capacity or efficiency, then
verification that the composition meets industry standards may be
needed; however, this could consist of laboratory certification
documents provided by the
[[Page 27403]]
manufacturer of the refrigerant blend. (ACEEE, No. 98 at p. 1) AHRI
indicated that it removed the current requirement to test a sample of
the superheated vapor refrigerant. (AHRI, No. 100 at p. 10) In light of
the comments, DOE is removing the requirement to conduct a refrigerant
composition analysis. If, however, DOE finds that refrigerant
composition is affecting the repeatability or accuracy of the testing,
DOE may reinstate this requirement at a later time.
h. Unit Cooler Test Conditions
In the SNOPR, DOE proposed to incorporate a modified version of
Tables 15 and 16 from AHRI 1250-2009. Those tables list the unit cooler
test conditions. DOE proposed to include the inlet saturation
temperature and outlet superheat conditions required in AHRI 420-2008,
``Performance Rating of Forced-Circulation Free-Delivery Unit Coolers
for Refrigeration,'' (``AHRI 420-2008'') for testing these types of
unit coolers as part of the tables. 79 FR at 9833.
Lennox and the CA IOUs recommended that instead of setting the
superheat conditions to 6.5 [deg]F in all cases, as required by AHRI
420-2008, the superheat conditions should be set according to the
manufacturer's specifications or installation instructions to ensure
that the test method can credit the energy efficiency benefits of
electronic expansion valves by allowing manufacturers to set lower
superheat levels. (Lennox, No. 97 at pp. 7-8; CA IOUs, No. 101 at p. 6)
Lennox also noted that the saturated suction values should reflect the
freezer test conditions of - 20 and - 25 [deg]F. (Lennox, No. 97 at p.
8) The CA IOUs supported fixing the liquid inlet saturation temperature
at 105 [deg]F. (CA IOUs, No. 101 at p. 6) Additionally, AHRI
incorporated the AHRI 420-2008 conditions into the tables with test
conditions for unit coolers, with the addition of a note instructing
that superheat conditions shall be set according to the equipment
specification in the equipment or installation manual. That note
specifies that in instances where no specification is given, a default
superheat value of 6.5 [deg]F shall be used, and the superheat setting
shall be reported as part of the standard rating. (AHRI, No. 100 at pp.
32-33)
DOE notes that manufacturers can often incorporate technologies
that allow the superheat to be lowered from the industry default value
to reduce energy consumption, but installers typically set the
superheat by adjusting a valve. Manufacturers would need to specify a
lower superheat value in their installation instructions in order for
the equipment to realize an energy benefit. Therefore, DOE is requiring
that superheat be set according to the manufacturer's specifications in
order to give credit for electronic expansion valves or advanced
controls. In instances where there are no specifications for superheat,
then the superheat shall be set to 6.5 [deg]F. In either case,
superheat must be reported as part of the standard rating.
C. Test Procedure for WICF Panel R-Value (ASTM C518-04)
The DOE test procedure, 10 CFR 431.304 Uniform test method for the
measurement of energy consumption of walk-in coolers and walk-in
freezers, incorporates by reference ASTM C518-04, a standard method for
determining thermal transmission properties (i.e., thermal conductance
or conductivity) of a material. In the February 2014 SNOPR, DOE
proposed several modifications and clarifications to the test procedure
to ensure accuracy and reliability. These proposed revisions would
apply to those testing provisions that manufacturers must currently use
as well as those provisions that would need to be followed when
evaluating the efficiency of a panel under any new standards that DOE
may eventually adopt as part of its parallel standards rulemaking. The
proposed revisions would require that test samples be no more than one
(1) inch in thickness, be taken from the center of the panel and have
all protective skins or facers removed prior to testing. See 79 FR at
9844. DOE received several comments on its proposed modifications,
which are discussed in the following subsections.
1. Test Sample Specifications
In the SNOPR, DOE proposed that test samples for R-value
measurement according to ASTM C518-04 be 1 inch in thickness and cut
from the center of a walk-in cooler or walk-in freezer panel. AHRI
agreed with DOE's proposal for test samples to be 1-inch in thickness
and extracted from the center of a finished panel. (AHRI, No. 100 at p.
7) Bally also agreed that the requirement for a 1-inch thick sample cut
from the center of a finished panel is appropriate. Bally further
suggested the addition of a dimensional tolerance of +.125 inches and -
0.0 inches for this thickness. (Bally, No. 93 at p. 3)
DOE is adopting its proposal that test samples for R-value
measurements made according to ASTM C518-04 be 1-inch in thickness and
cut from the center of a walk-in cooler or walk-in freezer panel. This
change should minimize any inaccuracy that may result from the
differences in thickness and thermal conductance between the test
sample and the standard reference material (SRM) used to calibrate the
heat flow meter apparatus. ASTM C518-04 makes several statements that
indicate that the test sample thickness and thermal properties should
be comparable to those of the calibration standard used. (ASTM C518-04
Section 6.1 and 6.5.4) It also states that the thickness of test
samples should be restricted in order to minimize the amount of lateral
heat losses during testing. (ASTM C518-04 Section 7.6.1) The new
requirement to use a 1-inch thick sample is in accordance with these
recommendations of ASTM C518-04. The test sample will be required to be
extracted from the center of a panel (rather than near the panel face)
since the insulation foams used in WICF panels will have experienced
the least amount of aging degradation near the center of the panel;
also, edge regions are not to be included in testing. DOE agrees that a
tolerance on the 1-inch requirement is appropriate in order to clarify
this requirement. Using a sample thickness of precisely 1 inch is not
important to the measurement because the heat flow meter apparatus
adjusts its measurement for the exact thickness. The objective of the
requirement is that the sample thickness be close to 1-inch, as opposed
to 2 inches or 0.5 inch, to improve accuracy, as described above, and
to achieve consistency of test results obtained in different
laboratories. A tolerance of 0.1-inch for the thickness of
the test sample will help achieve these objectives, while being well
within the precision of the cutting tools typically used to prepare the
sample. (DOE understands that a high-speed band-saw is often used for
cutting foam panels; moreover, a high-speed band-saw and meat slicer
are the two recommended cutting tools suggested by ASTM C1303-09a
Standard Test Method for Predicting Long-Term Thermal Resistance of
Closed-Cell Foam Insulation, Section 6.2.2.3.) Given that these cutting
tools are generally readily available and capable of the precision
required, DOE believes that a 0.1-inch tolerance for the
thickness of the test sample is appropriate and sufficient.
DOE also agrees with Bally's statement that care be taken during
any cutting processes so as to not alter the heat transfer properties
of the cut surface. (Bally, No. 93 at p. 3) Section 6.2.2.4 of ASTM
C1303-09a prohibits the use of hot-wire cutters for cutting
[[Page 27404]]
test samples in closed-cell foams to prevent the formation of a surface
skin. DOE will also adopt as part of this final rule a provision to
prohibit the use of hot-wire cutters or other heated cutting
instruments in preparing test samples in order to limit potential
altering of the samples' heat transfer properties during the cutting
process.
2. Removal of Panel Facers
DOE is also making explicit the requirement that facers or
protective skins be removed. While these components make a negligible
contribution to the overall thermal resistance of WICF panels in the
direction transverse to the panel surface, DOE recognizes that the
inclusion of metal facers or protective skins during testing using a
heat flow meter apparatus results in unreliable measurements. ASTM
C518-04 states that the presence of inhomogeneities or thermal bridges
can produce inaccurate results. (ASTM C518-04 (4.4))
In its comments on the February 2014 SNOPR, AHRI related that
requiring a 1-inch thick sample from a finished panel will already
involve removal of the facers or protective skins. (AHRI, No. 100 at p.
7) DOE recognizes that facers or skins would be removed when cutting a
1-inch thick sample from the center of a thicker panel. DOE also agrees
with AHRI's assertion that panels for testing should be supplied as
fully fabricated panels intact prior to testing, and that the 1-inch
thick test sample should be removed by the test laboratory at the time
of testing. (AHRI, No. 100 at p. 7) The requirements of 10 CFR
431.304(b)(5) and (c)(5) require that the insulating foam for testing
be supplied for testing in its final chemical state. For sprayed foams,
the final chemical form inherently requires facers or protective skins
to form the shape of the panel. Extruded foam board stock is typically
provided to WICF panel manufacturers in its final chemical form; in
this case, facers or protective skins may or may not be attached prior
to testing. Nevertheless, DOE is explicitly requiring that facers or
skins be removed to ensure that the process of cutting a sample from a
thicker panel will always achieve this objective.
3. 48-Hour Testing Window
DOE also proposed a 48-hour window once a test sample has been cut
from a WICF panel to perform ASTM C518-04 testing in order to minimize
the effect of aging of the closed-cell foam that constitutes the panel
insulation. Thermal resistance of polyurethane foams that are typical
of WICF panels decreases over time due to the diffusion of air into the
foam. DOE proposed the 48-hour window in order to ensure repeatability
and comparability in test results. The 48-hour window was developed
based on data from Wilkes, et al. at Oak Ridge National Laboratory.\3\
In this study, thermal conductivity of a 0.4 inch thick polyurethane
foam insulation increased between 6.0% and 20.7% (depending on the
blowing agent used) when aged at 90[emsp14][deg]F for 8 days and tested
at 45[emsp14][deg]F. Assuming that the rate of increase of thermal
conductivity during this initial period is linear, the range of
increase covered by these data over a 48-hour period would have been
1.5% to 5%. DOE understands that the higher temperature of
90[emsp14][deg]F at which these samples were aged and the smaller
thickness of the sample (0.4 inch compared to 1-inch as proposed for
WICF panels) would also have played contributing roles in accelerating
the aging process compared to what is to be expected in testing WICF
panels.
---------------------------------------------------------------------------
\3\ ``Aging of Polyurethane Foam Insulation in Simulated
Refrigerator Panels--Initial Results with Third-Generation Blowing
Agents'' by Kenneth E. Wilkes et al., published by Oak Ridge
National Laboratory for presentation at The Earth Technologies
Forum, October 26-28, 1998, Figures 2 and 4(b).
---------------------------------------------------------------------------
AHRI commented that the 48-hour period is appropriate and
sufficient. (AHRI, No. 100 at p. 7) Bally agreed that the time between
cutting and testing should be minimized, but disagreed that 48 hours is
an appropriate testing window for a cut sample. Bally stated that 48
hours may be appropriate for a conditioning period for the uncut panel
but once the panel is cut, only one hour should be allowed before
testing is performed (rather than the 48 hours as DOE has proposed).
(Bally, No. 93 at p. 4) However, Bally provided no evidence or data
suggesting that thermal conductivity would increase measurably between
1 and 48 hours after cutting the test sample. DOE notes that section
7.3 of ASTM C518-04 does not specify a conditioning period but states
that the conditioning period is typically indicated by a material
specification, that a typical material specification calls for
conditioning ``at 22[deg]C and 50% R.H. for a period of time until less
than a 1% mass change is observed over a 24-h period,'' and that where
the material specification does not indicate a conditioning period,
materials shall not be exposed to temperatures that will irreversibly
alter the test specimen. (ASTM C518-04 Section 7.3) As mentioned above,
DOE expects that the range of potential increase of thermal
conductivity for a 48-hour period is small; however, in response to
Bally's concerns, DOE will reduce the allowable window after cutting
from 48 hours to a maximum of 24 hours to remain conservative.
4. Specimen Conditioning Temperatures
Bally suggested that specimens be conditioned at the mean
temperatures at which they would be tested, namely 20 degrees
Fahrenheit for freezers and 55 degrees Fahrenheit for coolers. (Bally,
No. 93 at p. 4) However, it offered no rationale, evidence or data in
support of this suggestion. DOE understands that the intent of the
conditioning is to ensure consistency in the moisture level within the
sample during testing. DOE expects that the closed cell insulation
materials typically used for WICF panels would not rapidly change their
internal moisture levels, neither absorbing a significant amount of
moisture in a 24-hour period under normal ranges of ambient conditions,
nor rejecting a significant amount of excess moisture in a reasonable
time period, due to the closed-cell structure of the foam. As indicated
in ASTM C518-04 testing for WICF panels, section 7.3, conditioning
information is typically provided in the material specification for the
material being tested, but DOE is not aware of any such conditioning
specifications for insulation materials typically used for WICF panels.
Further, DOE is concerned that conditioning at cooled temperatures
could cause condensation when removed from a cooled conditioning
environment and introduced to a warmer room temperature in a test
laboratory. Finally, DOE is concerned that requiring a WICF panel,
often 8 feet by 4 feet in area, to be chilled to 20 degrees Fahrenheit
for an extended period of time may introduce undue test burden.
Therefore, DOE is not requiring conditioning requirements beyond those
already established by Section 7.3 of ASTM C518-04.
5. Flatness Tolerances on Contact Surfaces
Regarding its proposal to add parallelism and flatness constraints
on the two surfaces that contact the heat flow meter hot and cold
plates, DOE received two comments. That proposal, which included a
tolerance range of 0.03 inches, would apply to both
parallelism and flatness. See 79 FR at 9844. AHRI stated that the
proposed tolerances ``are impractical for the purposes of the proposed
test, are inconsistent with normal WICF panel manufacturers' standard
processes and are likely not within the capabilities of most current
panel manufacturing processes.'' AHRI recommended that DOE withdraw
this proposal. (AHRI,
[[Page 27405]]
No. 100 at p. 7) It did not, however, offer an alternative means for
ensuring sufficient contact between the test sample surfaces and the
surfaces of the heat flow meter assembly. Contact between these
surfaces is critical to test accuracy, as air gaps between the heat
flow meter apparatus surfaces and the test sample surfaces will result
in a higher conductivity and lower thermal resistance. To address
AHRI's concern, DOE clarifies that these tolerances will apply only to
the cut faces of the test sample itself, not the manufactured panel.
DOE also notes that, in support of this requirement, Bally (a
manufacturer of WICF panels) stated that the tolerances were
acceptable. (Bally, No. 93 at p. 3) As noted in section III.C.1, in
DOE's view, manufacturers should be able to achieve these tolerances
with common cutting tools and techniques.
6. Panel Testing Temperature Tolerances
With respect to the appropriate temperatures for testing panels,
DOE proposed a tolerance of 1 degree Fahrenheit on the
average foam temperature (20 degrees Fahrenheit for freezers and 55
degrees Fahrenheit for coolers). DOE proposed these provisions to help
ensure test repeatability. AHRI and Bally both stated that this
provision is appropriate and sufficient. (AHRI, No. 100 at p. 7 and
Bally, No. 93 at p. 3) No other comments were received. Accordingly,
DOE is adopting its proposed approach.
7. Additional Modifications to the Panel Test Procedure
DOE proposed a number of additional clarifications and
modifications to the panel test procedure. No comments were received on
these issues, which are listed immediately below.
Clarify and remove redundancy in 10 CFR 431.304(b)(5) and
(c)(5) regarding foam in its final chemical form;
Introduce an equation for WICF panels consisting of two or
more dissimilar insulating materials other than facers or protective
skins; and
Remove language in paragraphs (b), (b)(6), (c) and (c)(6)
of 10 CFR 431.304 that referenced manufacturers.
In light of the absence of any comments regarding these proposals,
DOE is adopting them as part of this final rule.
D. Performance-Based Test Procedures for Panels and Doors of Walk-In
Coolers and Freezers
1. Panels
As described above, WICF panels must meet requirements for foam
insulation R-values based on ASTM C518-04 testing incorporated in 10
CFR 431.304. Additionally, the test procedure at Appendix A to Subpart
R of Part 431 (Uniform Test Method for the Measurement of Energy
Consumption of the Components of Envelopes of Walk-In Coolers and Walk-
In Freezers) establishes the method and metrics by which the energy
consumption (for envelope components) or efficiency (for refrigeration
components) may be measured; this includes floor and non-floor panels.
Sections 4.2 and 4.3 of that procedure establish the calculation
procedures that result in a thermal conductivity, U-value, energy use
metric for floor and non-floor panels, and sections 5.1 and 5.2
establish the methods used to make the measurements. Section 5.1
incorporates by reference ASTM C1363-05 Standard Test Method for
Thermal Performance of Building Materials and Envelope Assemblies by
Means of a Hot Box Apparatus; section 5.2 incorporates by reference
Annex C Determination of the aged values of thermal resistance and
thermal conductivity of DIN EN 13164 and DIN EN 13165.
While ASTM C518-04 testing is intended to establish the thermal
resistance of the center of a WICF panel, the required testing under
ASTM C1363-05 is intended to capture the overall thermal transmittance
of a WICF panel, including thermal bridges and edge effects. (Thermal
transmittance is the reciprocal of thermal resistance.) Similar to ASTM
C518-04, DIN EN 13164/13165 testing is intended to measure the thermal
resistance of the center of a WICF panel; however, DIN EN 13164/13165
also captures the effects of foam aging on a panel's thermal
resistance.
In response to the September 2013 standards NOPR, the Department
received a number of comments regarding the WICF panel test procedure.
The comments largely presented two concerns: test burden and the
availability of laboratories to conduct these tests. In these comments,
multiple manufacturers suggested that no independent laboratories were
capable of conducting DIN EN 13164/13165 tests, and that only two were
capable of conducting ASTM C1363-05 tests. Several comments suggested
that the cost of these tests could be excessive, particularly given the
limited availability of independent test laboratories to perform these
specific tests. (See section III.D. of the February 2014 SNOPR for a
full comment summary.)
Responding to these comments, DOE proposed in the February 2014
SNOPR to remove the portions of the test procedure that referenced ASTM
C1363-04 and DIN EN 13164/13165 testing; this would remove sections
4.2, 4.3, 5.1 and 5.2 from 10 CFR 431, Appendix A of Subpart R. 79 FR
at 9837.
DOE received several comments regarding its proposal to remove
these portions of the WICF test procedure. Bally supported the proposal
to remove these test portions in order to reduce testing burden.
(Bally, No. 93 at p. 4) AHRI also supported their removal. (AHRI, No.
100 at p. 8). AHRI further recommended that DOE ``translate the
proposed remaining test standard ASTM C518-04 to prescriptive
requirements which would eliminate testing requirements.'' (AHRI, No.
100 p. 8) In contrast to these industry commenters, ASAP, et al.
suggested that DOE should not remove the sections that require ASTM
C1363-04 and DIN EN 13164/13165 testing. (ASAP, et al., No. 99 at p. 4)
ASAP, et al. stated that DOE would not be able to adopt the
performance-based standards based on U-values that were proposed in the
September 2013 standards NOPR and that the estimated energy savings
calculated in the September 2013 standards NOPR could therefore not be
achieved. (ASAP, et al., No. 99 at p. 4) Additionally, ASAP, et al.
believe that the U-value metric fulfills the requirement that DOE
establish ``performance-based standards'' for walk-ins. Finally, ASAP,
et al. suggested that DOE allow use of an AEDM that can accurately
predict the overall U-value for panels, thereby reducing test burden.
(ASAP, et al., No. 99 at p. 4)
DOE acknowledges that the estimated savings in the September 2013
standards NOPR were based on U-values. DOE also had not been aware of
the considerable difficulties that affected parties would likely face
in attempting to locate testing laboratories to assist them in
performing the test in anticipation of any standards with which
manufacturers would need to comply. Given these difficulties, in DOE's
view, modifications to the procedure are necessary to ensure that some
method of measuring panel efficiency can be readily conducted. The
prescriptive requirements established by EPCA for WICF panels are
effectively performance-based, as they regulate the thermal performance
of WICF panels
[[Page 27406]]
and require a certain minimal level of performance be met. (DOE refers
all interested parties to the standards rulemaking for updated
estimates of the energy savings estimates, which will now be based on
the R-value requirements (and U-factor for doors)). With respect to
ASAP, et al.'s suggestion to allow use of an AEDM to predict U-factor,
DOE notes that AEDMs must be validated by testing results and believes
that even this minimal amount of testing would be burdensome in light
of the lack of testing laboratories who can perform the testing
required to obtain a U-value. In response to AHRI's request to
translate the ASTM C518-04 test standard into prescriptive
requirements, DOE notes that the required minimum R-value for panels is
effectively a performance standard set forth by EPCA (42 U.S.C.
6313(f)(1)(C)) and the use of ASTM C518-04 for measuring the R-value is
mandated by EPCA. (42 U.S.C. 6314(a)(9)(A))
2. Doors
With respect to the test procedure for doors, DOE is adopting
several minor changes to section 5.3 for clarification purposes only.
DOE is modifying the titles of section 5.3(a)(2) from ``Internal
conditions'' to ``Cold-side conditions'' and section 5.3(a)(3) from
``External conditions'' to ``Warm-side conditions.'' The terms
``internal'' and ``external'' are irrelevant in the context of the
testing apparatus described in NFRC 100[E0A1] (incorporated by
reference). DOE is also making explicit the surface convective heat
transfer coefficients referred to in paragraph (a)(1); these values are
30 Watts per meter-Kelvin (W/m-K) for the cold side of the hot box
apparatus and 7.7 W/m-K for the warm side. This change only clarifies
these terms. These values are specified in ASTM C1199-09 Standard Test
Method for Measuring the Steady-State Thermal Transmittance of
Fenestration Systems Using Hot Box Methods which is referred to by NFRC
100[E0A1]. These changes were also proposed as part of the February
2014 SNOPR.
In response to this SNOPR, AHRI indicated that they do not object
to the proposed clarifications. (AHRI, No. 100 at p. 8) Bally, however,
commented that they do not agree with evaluating non-display doors
according to NFRC 100. (Bally, No. 93 at p. 4) Bally contended that
``surface convective heat transfer coefficients, in metric units [are]
quite alien to us since convective heat transfer is such a small part
of heat transfer except in high heat flow regions like fenestration.''
(Bally, No. 93 at p. 4) Bally also suggested that DOE's procedure based
on NFRC 100 should be dropped or that, ``at a minimum, exclude view
port windows with a total window surface area of 340 square inches or
less.'' (Bally, No. 93 at p. 4) AHRI also suggested that non-display
doors should have the option of meeting R-value-based standards. (AHRI,
No. 100 at p. 8)
DOE acknowledges that doors are a type of fenestration; hence, DOE
believes that NFRC 100 is appropriate for doors. The surface convective
coefficients stipulated in ASTM C1199-09 (which is referenced by NFRC
100 by way of NFRC 102) are intended to ensure testing repeatability by
establishing consistent boundary conditions. DOE reiterates that the
changes proposed in the February 2014 SNOPR were for clarification
purposes only, and that the substance of the test method is unchanged.
With respect to Bally's suggestion that NFRC 100 be dropped or its
application substantially modified, DOE infers that Bally is referring
to NFRC 100 as a whole, and not just the convective surface
coefficients specifically. DOE cannot abandon the use of NFRC 100 for
measuring the performance of WICF doors without a viable alternative
and Bally has offered none. With regards to non-display doors that
include a small viewing port window, the presence of the window means
that the information gained by measuring an overall door U-factor is
all the more valuable given the thermal bridging the window creates. As
previously stated, capturing the thermal bridging effects of all
components in a door is critical in accurately reflecting its energy
consumption due to the nature of fenestration. DOE is also reluctant to
make an exception for non-display doors or doors with port windows, as
it could potentially encourage manufacturers to add small windows to
all of their doors, which would relieve them from having to meet
performance standards. Should this occur, there would likely be an
increase in energy consumption due to thermal bridging. Accordingly,
DOE is leaving the NFRC 100 test in place for doors and display panels
while clarifying the convective surface coefficients to be used for
testing.
With respect to AHRI's suggestion that DOE apply R-value based
standards to non-display doors, DOE notes that the scope of its
proposal addresses only issues related to AEDMs as they would apply to
walk-ins along with related test procedure requirements. Comments on
the standards to which non-display doors should be held fall outside of
that scope. Furthermore, even if DOE were to consider the possibility
of applying an R-value-based standard--or any other standard--a non-
display door includes more components in its assembly than a wall
panel, which would make the consideration of potential standards for
these items considerably more complex. According to the definition for
``door'' found in 10 CFR 431.302, the door ``includes the door panel,
glass, framing materials, door plug, mullion, and any other elements
that form the door or part of its connection to the wall.'' As such,
there are more opportunities for thermal transmission. DOE believes
that for doors (both display and non-display) capturing these effects
by way of an overall U-factor through use of the NFRC 100 test
procedure is critical for accurately reflecting the energy consumption
of these WICF components. As a result, DOE is declining to adopt AHRI's
suggestion in the context of today's rulemaking.
E. Sampling Plan
In order to determine a rating for certifying compliance and making
energy use representations, DOE requires manufacturers to test each
basic model in accordance with the applicable DOE test procedure and
apply the sampling plan. DOE proposed a sampling plan for walk-ins
consistent with other commercial equipment regulated under EPCA that
would be included a proposed Sec. 429.53 of Subpart B of 10 CFR Part
429. For consistency with other commercial equipment regulated under
EPCA, DOE proposed that manufacturers test a sample of sufficient size
of a WICF component basic model to ensure a representative rating--but
not less than two units as prescribed in 10 CFR 429.11. DOE proposed
that any represented energy consumption values of a walk-in basic model
component shall be greater than or equal to the higher of the mean of
the sample or the 95 percent upper confidence limit (UCL) of the true
mean divided by 1.05. Additionally, DOE proposed that any represented
energy efficiency values of a walk-in basic model component shall be
the less than or equal to the lower of the mean of the sample or the 95
percent lower confidence limit (LCL) of the true mean divided by 0.95.
DOE did not receive any comments on this proposal and so is adopting
the proposed sampling requirements.
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget has determined that test
procedure rulemakings do not constitute ``significant regulatory
actions'' under
[[Page 27407]]
section 3(f) of Executive Order 12866, ``Regulatory Planning and
Review,'' 58 FR 51735 (Oct. 4, 1993). Accordingly, this regulatory
action was not subject to review under the Executive Order by the
Office of Information and Regulatory Affairs (OIRA) in the Office of
Management and Budget (OMB).
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601, et seq.) requires the
preparation of a final regulatory flexibility analysis (FRFA) for any
rule that by law must be proposed for public comment, unless the agency
certifies that the rule, if promulgated, will not have a significant
economic impact on a substantial number of small entities. As required
by Executive Order 13272, ``Proper Consideration of Small Entities in
Agency Rulemaking,'' 67 FR 53461 (August 16, 2002), DOE published
procedures and policies on February 19, 2003, to ensure that the
potential impacts of its rules on small entities are properly
considered during the DOE rulemaking process. 68 FR 7990. DOE has made
its procedures and policies available on the Office of the General
Counsel's Web site: www.gc.doe.gov. DOE reviewed the test procedures
promulgated in today's final rule under the provisions of the
Regulatory Flexibility Act (RFA) and the policies and procedures
published on February 19, 2003.
As discussed in more detail below, DOE found that the provisions of
this rule will not result in increased testing and/or reporting burden
for manufacturers and permit additional manufacturers to use an AEDM
for the purposes of rating and certifying their equipment, which would
reduce manufacturer testing burden. Accordingly, based on DOE's review,
manufacturers are unlikely to experience an increased financial burden
because of the provisions established in today's final rule.
First, DOE is allowing manufacturers walk-in refrigeration systems
to use an AEDM to determine the energy consumption of their products.
Previously, no walk-in manufacturers were eligible to use an AEDM.
Today's rule adopts voluntary methods for determining compliance in
lieu of conducting actual physical testing--which, in turn, are
expected to reduce the testing burden of walk-in manufacturers who
elect to use an AEDM. Furthermore, the validation requirements for an
AEDM do not require more testing than that which is already required
under DOE's regulations at 10 CFR 429.12. While the Department believes
that permitting greater use of AEDMs will reduce the affected
manufacturer's test burden, their use is at the manufacturer's
discretion. If, as a result of any of the regulations herein, a
manufacturer believes that use of an AEDM would increase rather than
decrease their financial burden compared to performing actual testing,
the manufacturer may choose not to employ the method. Should a
manufacturer choose to abstain from using an AEDM, this provision would
not apply and the manufacturer would continue to remain subject to the
requirements of the applicable DOE test procedures for walk-ins, which
would result in no change in burden from that which was already
required.
DOE is also codifying alternate methods for determining the
compliance of individual walk-in refrigeration system components, which
should further decrease the burden of the future test procedure for
walk-in refrigeration systems. DOE is currently undertaking an energy
conservation standards rulemaking to set performance standards for
walk-in components, including panels, doors, and refrigeration systems.
Under the provisions of the March 2011 Final Rule (76 FR 12422 (March
7, 2011)), the ``component'' manufacturer would be required to certify
compliance with these standards once any applicable compliance date is
reached--however, there were no provisions for manufacturers of
individual refrigeration components (i.e., unit coolers and condensing
units) to ensure the compliance of their components with an energy
conservation standard because the proposed refrigeration system
standard would apply to the whole refrigeration system. These
manufacturers could potentially have incurred a large burden by having
to test all combinations of the components they wished to distribute.
Additionally, manufacturers of only one type of component could have
been inadvertently prevented from selling their equipment because there
would have been no available compliance mechanism. This rule
establishes an alternate testing methodology by which manufacturers of
either component of a walk-in refrigeration system--the condensing unit
or the unit cooler--may determine compliance with the applicable
standard without having to test every combination of components that
they produce. DOE believes this approach will significantly reduce the
testing burden for all manufacturers, including small businesses.
Finally, DOE is adopting several clarifications and modifications
to the existing test procedures that are intended to further reduce
testing burden. For example, DOE is not requiring the use of long-term
thermal resistance testing of foam and is allowing manufacturers to
test their panels based only on testing to ASTM C518, a simpler test
method that is already in use in the industry. For a complete list of
test procedure modifications, see section III.
For the reasons enumerated above, DOE is certifying that this final
rule will not have a significant impact on a substantial number of
small entities.
C. Review Under the Paperwork Reduction Act of 1995
A walk-in manufacturer must certify to DOE that its equipment
complies with all applicable energy conservation standards. To certify
compliance, manufacturers must test their products according to the DOE
test procedures for walk-in equipment, including any amendments adopted
for those test procedures. DOE has established regulations for the
certification and recordkeeping requirements for all covered consumer
products and commercial equipment, including walk-in coolers and
freezers. 76 FR 12422 (March 7, 2011). The collection-of-information
requirement for certification and recordkeeping is subject to review
and approval by OMB under the Paperwork Reduction Act (PRA). This
requirement has been approved by OMB under OMB control number 1910-
1400. Public reporting burden for the certification is estimated to
average 20 hours per response, including the time for reviewing
instructions, searching existing data sources, gathering and
maintaining the data needed, and completing and reviewing the
collection of information.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
DOE is amending its test procedures and related provisions for
walk-ins. DOE has determined that this rule falls into a class of
actions that are categorically excluded from review under the National
Environmental Policy Act of 1969 (42 U.S.C. 4321 et seq.) and DOE's
implementing regulations at 10 CFR part 1021. This
[[Page 27408]]
rule amends the existing test procedures without affecting the amount,
quality, or distribution of energy usage, and, therefore, will not
result in any environmental impacts. Thus, this rulemaking is covered
by Categorical Exclusion A5 under 10 CFR part 1021, subpart D, which
applies to any rulemaking that interprets or amends an existing rule
without changing the environmental effect of that rule. Accordingly,
neither an environmental assessment nor an environmental impact
statement is required.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 10,
1999), imposes certain requirements on Federal agencies formulating and
implementing policies or regulations that preempt State law or that
have federalism implications. The Executive Order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States, and
to carefully assess the necessity for such actions. The Executive Order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. (65 FR 13735) DOE has examined this
rule and has tentatively determined that it would not have a
substantial direct effect on the States, on the relationship between
the national government and the States, or on the distribution of power
and responsibilities among the various levels of government. EPCA
governs and prescribes Federal preemption of State regulations as to
energy conservation for the products that are the subject of today's
rule. States can petition DOE for exemption from such preemption to the
extent, and based on criteria, set forth in EPCA. (42 U.S.C. 6297) No
further action is required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
Eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Regarding the review required by section 3(a),
section 3(b) of Executive Order 12988 specifically requires that
Executive agencies make every reasonable effort to ensure that the
regulation: (1) Clearly specifies the preemptive effect, if any; (2)
clearly specifies any effect on existing Federal law or regulation; (3)
provides a clear legal standard for affected conduct while promoting
simplification and burden reduction; (4) specifies the retroactive
effect, if any; (5) adequately defines key terms; and (6) addresses
other important issues affecting clarity and general draftsmanship
under any guidelines issued by the Attorney General. Section 3(c) of
Executive Order 12988 requires Executive agencies to review regulations
in light of applicable standards in sections 3(a) and 3(b) to determine
whether they are met or it is unreasonable to meet one or more of them.
DOE has completed the required review and determined that, to the
extent permitted by law, the rule meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (UMRA)
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. (Pub. L. 104-4, sec. 201, codified at 2 U.S.C. 1531)
For regulatory actions likely to result in a rule that may cause the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector of $100 million or more in any one year
(adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a)-(b)) UMRA also requires a Federal agency to develop
an effective process to permit timely input by elected officers of
State, local, and Tribal governments on a ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect them. On March 18, 1997, DOE published
a statement of policy on its process for intergovernmental consultation
under UMRA. (62 FR 12820) (This policy is also available at https://www.energy.gov/gc.) DOE examined today's rule according to UMRA and its
statement of policy and has determined that the rule contains neither
an intergovernmental mandate, nor a mandate that may result in the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector, of $100 million or more in any year.
Accordingly, no further assessment or analysis is required under UMRA.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This rule would not have any impact on the autonomy or integrity of the
family as an institution. Accordingly, DOE has concluded that it is not
necessary to prepare a Family Policymaking Assessment.
I. Review Under Executive Order 12630
Pursuant to Executive Order 12630, ``Governmental Actions and
Interference with Constitutionally Protected Property Rights,'' 53 FR
8859 (March 18, 1988), DOE has determined that this rule would not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516, note) provides for Federal agencies to
review most disseminations of information to the public under
information quality guidelines established by each agency pursuant to
general guidelines issued by OMB. OMB's guidelines were published at 67
FR 8452 (Feb. 22, 2002), and DOE's guidelines were published at 67 FR
62446 (Oct. 7, 2002). DOE has reviewed today's rule under the OMB and
DOE guidelines and has concluded that it is consistent with applicable
policies in those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OIRA
at OMB, a Statement of Energy Effects for any significant energy
action. A ``significant energy action'' is defined as any action by an
agency that promulgates or is expected to lead to promulgation of a
[[Page 27409]]
final rule, and that: (1) Is a significant regulatory action under
Executive Order 12866, or any successor order; and (2) is likely to
have a significant adverse effect on the supply, distribution, or use
of energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any significant energy action, the
agency must give a detailed statement of any adverse effects on energy
supply, distribution, or use should the rule be implemented, and of
reasonable alternatives to the action and their expected benefits on
energy supply, distribution, and use.
DOE has reviewed today's rule and determined, it would not have a
significant adverse effect on the supply, distribution, or use of
energy, nor has it been designated as a significant energy action by
the Administrator of OIRA. Therefore, it is not a significant energy
action, and, accordingly, DOE has not prepared a Statement of Energy
Effects for this rulemaking.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101, et seq.), DOE must comply with all laws
applicable to the former Federal Energy Administration, including
section 32 of the Federal Energy Administration Act of 1974 (Pub. L.
93-275), as amended by the Federal Energy Administration Authorization
Act of 1977 (Pub. L. 95-70). (15 U.S.C. 788; FEAA) Section 32 provides
in relevant part that, where a rule authorizes or requires use of
commercial standards, the notice of the final rule must inform the
public of the use and background of such standards. In addition,
section 32(c) requires DOE to consult with the Attorney General and the
Chairman of the Federal Trade Commission (FTC) concerning the impact of
the commercial or industry standards on competition. Today's rule does
not incorporate any commercial standards. The commercial standards
discussed in today's rulemaking were already adopted in the Test
Procedures for Walk-In Coolers and Walk-In Freezers, which was
published in the Federal Register on April 15, 2011. 76 FR 21580. DOE
conducted a review under Section 32 of the Federal Energy
Administration Act of 1974 in the April 2011 test procedure final rule.
76 FR 21580, 21604.
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of today's final
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Reporting and recordkeeping
requirements.
10 CFR Part 431
Administrative practice and procedure, Confidential business
information, Energy conservation, Incorporation by reference, Reporting
and recordkeeping requirements.
Issued in Washington, DC, on May 5, 2014.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
For the reasons stated in the preamble, DOE is amending parts 429
and 431 of Chapter II, Subchapter D of Title 10, Code of Federal
Regulations, as set forth below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317.
0
2. Section 429.53 is revised to read as follows:
Sec. 429.53 Walk-in coolers and walk-in freezers.
(a) Determination of represented value--(1) Refrigeration
equipment: Manufacturers must determine the represented value, which
includes the certified rating, for each basic model of walk-in cooler
or freezer refrigeration equipment, either by testing, in conjunction
with the applicable sampling provisions, or by applying an AEDM
satisfying the criteria provided at Sec. 429.70(f)(1).
(i) Units to be tested. (A) If the represented value for a given
basic model is determined through testing, the general requirements of
Sec. 429.11 apply; and
(B) For each basic model selected for testing, a sample of
sufficient size shall be randomly selected and tested to ensure that--
(1) Any represented value of energy consumption or other measure of
energy use of a basic model for which consumers would favor lower
values shall be greater than or equal to the higher of:
(i) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TR13MY14.000
and, x is the sample mean; n is the number of samples; and
xi is the ith sample; or,
(ii) The upper 95 percent confidence limit (UCL) of the true mean
divided by 1.05, where:
[GRAPHIC] [TIFF OMITTED] TR13MY14.001
And x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.95 is the t statistic for a
95% one-tailed confidence interval with n-1 degrees of freedom (from
Appendix A to subpart B). And,
(2) Any represented value of energy efficiency or other measure of
energy consumption of a basic model for which consumers would favor
higher values shall be less than or equal to the lower of:
(i) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TR13MY14.002
And, x is the sample mean; n is the number of samples; and
xi is the ith sample; or,
(ii) The lower 95 percent confidence limit (LCL) of the true mean
divided by 0.95, where:
[GRAPHIC] [TIFF OMITTED] TR13MY14.003
And x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.95 is the t statistic for a
95% one-tailed confidence interval with n-1 degrees of freedom (from
Appendix A to subpart B).
(ii) Alternative efficiency determination methods. In lieu of
testing, a represented value of efficiency or consumption for a basic
model of a walk-in cooler or freezer refrigeration system must be
determined through the application of an AEDM pursuant to the
requirements of Sec. 429.70 and the provisions of this section, where:
(A) Any represented value of energy consumption or other measure of
energy use of a basic model for which consumers would favor lower
values shall be greater than or equal to the output of the AEDM and
less than or equal to the Federal standard for that basic model; and
(B) Any represented value of energy efficiency or other measure of
energy consumption of a basic model for which consumers would favor
higher values shall be less than or equal to the output
[[Page 27410]]
of the AEDM and greater than or equal to the Federal standard for that
basic model.
(iii) If the represented value of a refrigeration system was
determined using the unit cooler testing provisions at 10 CFR
431.304(c)(12), that represented value may be used for all
refrigeration systems containing that unit cooler irrespective of
whether such equipment is sold separately or as part of a matched
refrigeration system. However, for any representations of matched-
system efficiency that exceed the refrigeration system rating as
determined by the unit cooler testing provisions at 10 CFR
431.304(c)(12) and for which a manufacturer wishes to make
representations of the more-efficient rating, then the matched
refrigeration system must be tested separately in accordance with the
DOE test procedure for matched systems and applicable sampling plan.
(2) WICF components other than those specified in (a)(1) of this
section--(i) Units to be tested.
(A) The general requirements of Sec. 429.11 apply; and
(B) For each basic model selected for testing, a sample of
sufficient size shall be randomly selected and tested to ensure that--
(1) Any represented value of energy consumption or other measure of
energy use of a basic model for which consumers would favor lower
values shall be greater than or equal to the higher of:
(i) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TR13MY14.004
and, x is the sample mean; n is the number of samples; and
xi is the ith sample; or,
(ii) The upper 95 percent confidence limit (UCL) of the true mean
divided by 1.05, where:
[GRAPHIC] [TIFF OMITTED] TR13MY14.005
And x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.95 is the t statistic for a
95% one-tailed confidence interval with n-1 degrees of freedom (from
Appendix A to subpart B). And,
(2) Any represented value of energy efficiency or other measure of
energy consumption of a basic model for which consumers would favor
higher values shall be less than or equal to the lower of:
(i) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TR13MY14.006
And, x is the sample mean; n is the number of samples; and
xi is the i\th\ sample; or,
(ii) The lower 95 percent confidence limit (LCL) of the true mean
divided by 0.95, where:
[GRAPHIC] [TIFF OMITTED] TR13MY14.007
And x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.95 is the t statistic for a
95% one-tailed confidence interval with n-1 degrees of freedom (from
Appendix A to subpart B).
(b) Certification reports. (1) The requirements of Sec. 429.12 are
applicable to manufacturers of the components of walk-in coolers and
freezers (WICFs) listed in paragraph (b)(2) of this section, and;
(2) Pursuant to Sec. 429.12(b)(13), a certification report shall
include the following public product-specific information:
(i) For WICF doors: The door type, R-value of the door insulation,
and a declaration that the manufacturer has incorporated the applicable
design requirements. In addition, for those WICFs with transparent
reach-in doors and windows: The glass type of the doors and windows
(e.g., double-pane with heat reflective treatment, triple-pane glass
with gas fill), and the power draw of the antisweat heater in watts per
square foot of door opening.
(ii) For WICF panels: The R-value of the insulation (except for
glazed portions of the doors or structural members).
(iii) For WICF refrigeration systems: The motor's purpose (i.e.,
evaporator fan motor or condenser fan motor), the horsepower, and a
declaration that the manufacturer has incorporated the applicable
design requirements.
0
3. Section 429.70 is amended by adding paragraph (f) to read as
follows:
Sec. 429.70 Alternative methods for determining energy efficiency or
energy use.
* * * * *
(f) Alternative efficiency determination method (AEDM) for walk-in
refrigeration equipment--
(1) Criteria an AEDM must satisfy. A manufacturer may not apply an
AEDM to a basic model to determine its efficiency pursuant to this
section unless:
(i) The AEDM is derived from a mathematical model that estimates
the energy efficiency or energy consumption characteristics of the
basic model as measured by the applicable DOE test procedure;
(ii) The AEDM is based on engineering or statistical analysis,
computer simulation or modeling, or other analytical evaluation of
performance data; and
(iii) The manufacturer has validated the AEDM, in accordance with
paragraph (f)(2) of this section.
(2) Validation of an AEDM. Before using an AEDM, the manufacturer
must validate the AEDM's accuracy and reliability as follows:
(i) The manufacturer must select at least the minimum number of
basic models for each validation class specified in paragraph
(f)(2)(iv) of this section to which the particular AEDM applies. Test a
single unit of each basic model in accordance with paragraph
(f)(2)(iii) of this section. Using the AEDM, calculate the energy use
or energy efficiency for each of the selected basic models. Compare the
results from the single unit test and the AEDM output according to
paragraph (f)(2)(ii) of this section. The manufacturer is responsible
for ensuring the accuracy and repeatability of the AEDM.
(ii) Individual model tolerances. (A) The predicted efficiency for
each model calculated by applying the AEDM may not be more than five
percent greater than the efficiency determined from the corresponding
test of the model.
(B) The predicted energy efficiency for each model calculated by
applying the AEDM must meet or exceed the applicable federal energy
conservation standard.
(iii) Additional test unit requirements. (A) Each AEDM must be
supported by test data obtained from physical tests of current models;
and
(B) Test results used to validate the AEDM must meet or exceed
current, applicable Federal standards as specified in part 431 of this
chapter;
(C) Each test must have been performed in accordance with the
applicable DOE test procedure with which compliance is required at the
time the basic model is distributed in commerce; and
(D) For rating WICF refrigeration system components, an AEDM may
not simulate or model portions of the system that are not required to
be tested by the DOE test procedure. That is, if the test results used
to validate the AEDM are for either a unit cooler only or a condensing
unit only, the AEDM must estimate the system rating using the nominal
values specified in the DOE test procedure for the other part of the
refrigeration system.
[[Page 27411]]
(iv) WICF refrigeration validation classes.
------------------------------------------------------------------------
Minimum number of distinct
Validation class models that must be tested
------------------------------------------------------------------------
Dedicated Condensing, Medium 2 Basic Models.
Temperature, Indoor System.
Dedicated Condensing, Medium 2 Basic Models.
Temperature, Outdoor System \1\.
Dedicated Condensing, Low Temperature, 2 Basic Models.
Indoor System.
Dedicated Condensing, Low Temperature, 2 Basic Models.
Outdoor System \2\.
Unit Cooler connected to a Multiplex 2 Basic Models.
Condensing Unit, Medium Temperature.
Unit Cooler connected to a Multiplex 2 Basic Models.
Condensing Unit, Low Temperature.
Medium Temperature, Indoor Condensing 2 Basic Models.
Unit.
Medium Temperature, Outdoor Condensing 2 Basic Models.
Unit \3\.
Low Temperature, Indoor Condensing Unit 2 Basic Models.
Low Temperature, Outdoor Condensing 2 Basic Models.
Unit \4\.
------------------------------------------------------------------------
\1\ AEDMs validated for dedicated condensing, medium temperature,
outdoor systems may be used to determine representative values for
dedicated condensing, medium temperature, indoor systems, and
additional validation testing is not required. AEDMs validated for
only dedicated condensing, medium temperature, indoor systems may not
be used to determine representative values for dedicated condensing,
medium temperature, outdoor systems.
\2\ AEDMs validated for dedicated condensing, low temperature, outdoor
systems may be used to determine representative values for dedicated
condensing, low temperature, indoor systems, and additional validation
testing is not required. AEDMs validated for only dedicated
condensing, low temperature, indoor systems may not be used to
determine representative values for dedicated condensing, low
temperature, outdoor systems.
\3\ AEDMs validated for medium temperature, outdoor condensing units may
be used to determine representative values for medium temperature,
indoor condensing units, and additional validation testing is not
required. AEDMs validated for only medium temperature, indoor
condensing units may not be used to determine representative values
for medium temperature, outdoor condensing units.
\4\ AEDMs validated for low temperature, outdoor condensing units may be
used to determine representative values for low temperature, indoor
condensing units, and additional validation testing is not required.
AEDMs validated for only low temperature, indoor condensing units may
not be used to determine representative values for low temperature,
outdoor condensing units.
(3) AEDM records retention requirements. If a manufacturer has used
an AEDM to determine representative values pursuant to this section,
the manufacturer must have available upon request for inspection by the
Department records showing:
(i) The AEDM, including the mathematical model, the engineering or
statistical analysis, and/or computer simulation or modeling that is
the basis of the AEDM;
(ii) Equipment information, complete test data, AEDM calculations,
and the statistical comparisons from the units tested that were used to
validate the AEDM pursuant to paragraph (f)(2) of this section; and
(iii) Equipment information and AEDM calculations for each basic
model to which the AEDM has been applied.
(4) Additional AEDM requirements. If requested by the Department
the manufacturer must perform at least one of the following:
(i) Conduct simulations before representatives of the Department to
predict the performance of particular basic models of the product to
which the AEDM was applied;
(ii) Provide analyses of previous simulations conducted by the
manufacturer; or
(iii) Conduct certification testing of basic models selected by the
Department.
(5) AEDM verification testing. DOE may use the test data for a
given individual model generated pursuant to Sec. 429.104 to verify
the certified rating determined by an AEDM as long as the following
process is followed:
(i) Selection of units. DOE will obtain units for test from retail,
where available. If units cannot be obtained from retail, DOE will
request that a unit be provided by the manufacturer.
(ii) Lab requirements. DOE will conduct testing at an independent,
third-party testing facility of its choosing. In cases where no third-
party laboratory is capable of testing the equipment, it may be tested
at a manufacturer's facility upon DOE's request.
(iii) Manufacturer participation. Testing will be performed without
manufacturer representatives on-site.
(iv) Testing. All verification testing will be conducted in
accordance with the applicable DOE test procedure, as well as each of
the following to the extent that they apply:
(A) Any active test procedure waivers that have been granted for
the basic model;
(B) Any test procedure guidance that has been issued by DOE;
(C) If during test set-up or testing, the lab indicates to DOE that
it needs additional information regarding a given basic model in order
to test in accordance with the applicable DOE test procedure, DOE may
organize a meeting between DOE, the manufacturer and the lab to provide
such information.
(D) At no time during the process may the lab communicate directly
with the manufacturer without DOE present.
(v) Failure to meet certified rating. If a model tests worse than
its certified rating by an amount exceeding the tolerance prescribed in
paragraph (f)(5)(vi) of this section, DOE will notify the manufacturer.
DOE will provide the manufacturer with all documentation related to the
test set up, test conditions, and test results for the unit. Within the
timeframe allotted by DOE, the manufacturer may then present all claims
regarding testing validity.
(vi) Tolerances. for efficiency metrics, the result from a DOE
verification test must be greater than or equal to the certified rating
x (1 - the applicable tolerance).
------------------------------------------------------------------------
Applicable
Equipment Metric tolerance
------------------------------------------------------------------------
Refrigeration systems (including AWEF................ 5%
components).
------------------------------------------------------------------------
[[Page 27412]]
(vii) Invalid rating. If, following discussions with the
manufacturer and a retest where applicable, DOE determines that the
testing was conducted appropriately in accordance with the DOE test
procedure, the rating for the model will be considered invalid.
Pursuant to 10 CFR 429.13(b), DOE may require a manufacturer to conduct
additional testing as a remedial measure.
PART 431--ENERGY CONSERVATION PROGRAM FOR CERTAIN COMMERCIAL AND
INDUSTRIAL EQUIPMENT
0
4. The authority citation for part 431 continues to read as follows:
Authority: 42 U.S.C. 6291-6317.
Sec. 431.303 [Amended]
0
5. Section 431.303 is amended by:
0
a. Removing and reserving paragraph (c)(2);
0
b. Removing paragraph (d); and
0
c. Redesignating paragraph (e) as (d).
0
6. Section 431.304 is amended by:
0
a. Revising paragraphs (b) introductory text, and (b)(3) through (6);
0
b. Adding paragraph (b)(7);
0
c. Revising paragraphs (c) introductory text, and (c)(3) through (6);
0
d. Redesignating paragraphs (c)(7) through (c)(10) as paragraphs (c)(8)
through (c)(11), respectively;
0
e. Adding new paragraph (c)(7);
0
f. Revising redesignated paragraph (c)(8), (c)(9) and (c)(10); and,
0
g. Adding paragraph (c)(12).
The revisions and additions read as follows:
Sec. 431.304 Uniform test method for the measurement of energy
consumption of walk-in coolers and walk-in freezers.
* * * * *
(b) This paragraph (b) shall be used for the purposes of certifying
compliance with the applicable R-value energy conservation standards
for panels until compliance with amended standards is required.
* * * * *
(3) When calculating the R value for freezers, the K factor of the
foam at 20 1 degrees Fahrenheit (average foam temperature)
shall be used. Test results from a test sample 1 0.1-
inches in thickness may be used to determine the R value of panels with
various foam thickness as long as the foam is of the same final
chemical form.
(4) When calculating the R value for coolers, the K factor of the
foam at 55 1 degrees Fahrenheit (average foam temperature)
shall be used. Test results from a test sample 1 0.1-
inches in thickness may be used to determine the R value of panels with
various foam thickness as long as the foam is of the same final
chemical form.
(5) Foam shall be tested after it is produced in its final chemical
form. (For foam produced inside of a panel (``foam-in-place''), ``final
chemical form'' means the foam is cured as intended and ready for use
as a finished panel. For foam produced as board stock (typically
polystyrene), ``final chemical form'' means after extrusion and ready
for assembly into a panel or after assembly into a panel.) Foam from
foam-in-place panels must not include any structural members or non-
foam materials. Foam produced as board stock may be tested prior to its
incorporation into a final panel. A test sample 1 0.1-
inches in thickness must be taken from the center of a panel and any
protective skins or facers must be removed. A high-speed band-saw and a
meat slicer are two types of recommended cutting tools. Hot wire
cutters or other heated tools must not be used for cutting foam test
samples. The two surfaces of the test sample that will contact the hot
plate assemblies (as defined in ASTM C518 (incorporated by reference,
see Sec. 431.303)) must both maintain 0.03 inches flatness
tolerance and also maintain parallelism with respect to one another
within 0.03 inches. Testing must be completed within 24
hours of samples being cut for testing.
(6) Internal non-foam member and/or edge regions shall not be
considered in ASTM C518 testing.
(7) For panels consisting of two or more layers of dissimilar
insulating materials (excluding facers or protective skins), test each
material as described in paragraphs (c)(1) through (6) of this section.
For a panel with N layers of insulating material, the overall R-Value
shall be calculated as follows:
[GRAPHIC] [TIFF OMITTED] TR13MY14.008
Where:
ki is the k factor of the ith material as measured by
ASTM C518,
ti is the thickness of the ith material that appears in
the panel, and
N is the total number of material layers that appears in the panel.
(c) This paragraph (c) shall be used for any representations of
energy efficiency or energy use starting on October 12, 2011, and to
certify compliance to the energy conservation standards of the R-value
of panels on or after the compliance date of amended energy
conservation standards for walk-in cooler and freezers.
* * * * *
(3) For calculating the R value for freezers, the K factor of the
foam at 20 1 degrees Fahrenheit (average foam temperature)
shall be used. Test results from a test sample 1 0.1-
inches in thickness may be used to determine the R value of panels with
various foam thickness as long as the foam is of the same final
chemical form.
(4) For calculating the R value for coolers, the K factor of the
foam at 55 1 degrees Fahrenheit (average foam temperature)
shall be used. Test results from a test sample 1 0.1-
inches in thickness may be used to determine the R value of panels with
various foam thickness as long as the foam is of the same final
chemical form.
(5) Foam shall be tested after it is produced in its final chemical
form. (For foam produced inside of a panel (``foam-in-place''), ``final
chemical form'' means the foam is cured as intended and ready for use
as a finished panel. For foam produced as board stock (typically
polystyrene), ``final chemical form'' means after extrusion and ready
for assembly into a panel or after assembly into a panel.) Foam from
foam-in-place panels must not include any structural members or non-
foam materials. Foam produced as board stock may be tested prior to its
incorporation into a final panel. A test sample 1 0.1-
inches in thickness must be taken from the center of a panel and any
protective skins or facers must be removed. A high-speed band-saw and a
meat slicer are two types of recommended cutting tools. Hot wire
cutters or other heated tools must not be used for cutting foam test
samples. The two surfaces of the test sample that will contact the hot
plate assemblies (as defined in ASTM C518 (incorporated by reference,
see Sec. 431.303)) must both maintain 0.03 inches flatness
tolerance and also maintain parallelism with respect to one another
within 0.03 inches. Testing must be completed within 24
hours of samples being cut for testing.
(6) Internal non-foam member and/or edge regions shall not be
considered in ASTM C518 testing.
(7) For panels consisting of two or more layers of dissimilar
insulating materials (excluding facers or protective skins), test each
material as described in paragraphs (c)(1) through (6) of this section.
For a panel with N layers of insulating material, the overall R-Value
shall be calculated as follows:
[[Page 27413]]
[GRAPHIC] [TIFF OMITTED] TR13MY14.009
Where:
ki is the k factor of the ith material as measured by
ASTM C518, and
ti is the thickness of the ith material that appears in
the panel.
N is the total number of material layers that appears in the panel.
(8) Determine the U-factor, conduction load, and energy use of
walk-in cooler and walk-in freezer display panels by conducting the
test procedure set forth in appendix A to this subpart section 4.1.
(9) Determine the energy use of walk-in cooler and walk-in freezer
display doors and non-display doors by conducting the test procedure
set forth in appendix A to this subpart, sections 4.4 and 4.5,
respectively.
(10) Determine the Annual Walk-in Energy Factor of walk-in cooler
and walk-in freezer refrigeration systems by conducting the test
procedure set forth in AHRI 1250-2009 (incorporated by reference; see
Sec. 431.303), with the following modifications:
(i) In Table 2, Test Operating and Test Condition Tolerances for
Steady-State Test, electrical power frequency shall have a Test
Condition Tolerance of 1 percent. Also, refrigerant temperature
measurements shall have a tolerance of 0.5 F for unit
cooler in/out, 1.0 F for all other temperature
measurements.
(ii) In Table 2, the Test Operating Tolerances and Test Condition
Tolerances for Air Leaving Temperatures shall be deleted.
(iii) In Tables 2 through 14, The Test Condition Outdoor Wet Bulb
Temperature requirement and its associated tolerance apply only to
units with evaporative cooling.
(iv) In section C3.1.6, refrigerant temperature measurements
upstream and downstream of the unit cooler may use sheathed sensors
immersed in the flowing refrigerant instead of thermometer wells.
(v) In section C3.5, for a given motor winding configuration, the
total power input shall be measured at the highest nameplate voltage.
For three-phase power, voltage imbalances shall be no more than 2
percent from phase to phase.
(vi) In the test setup (section C8.3), the condenser and unit
cooler shall be connected by pipes of the manufacturer-specified size.
The pipe lines shall be insulated with a minimum total thermal
resistance equivalent to \1/2\'' thick insulation having a flat-surface
R-Value of 3.7 ft\2\-[deg]F-hr/Btu per inch or greater. Flow meters
need not be insulated but must not be in contact with the floor. The
lengths of the connected liquid line and suction line shall be 25 feet,
not including the requisite flow meters, each. Of this length, no more
than 15 feet shall be in the conditioned space. In the case where there
are multiple branches of piping, the maximum length of piping applies
to each branch individually as opposed to the total length of the
piping.
(vii) In section C3.4.5, for verification of sub-cooling downstream
of mass flow meters, only the sight glass and a temperature sensor
located on the tube surface under the insulation are required.
(viii) Delete section C3.3.6.
(ix) In section C11.1, to determine frost load defrost conditions,
the Frost Load Conditions Defrost Test (C11.1.1) is optional. If the
frost load test is not performed, the frost load defrost DFf
shall be equal to 1.05 multiplied by the dry coil energy consumption
DFd measured using the dry coil condition test in section
C11.1 and the number of defrosts per day NDF shall be set to
4.
(x) In section C11.2, if the system has an adaptive or demand
defrost system, the optional test may be run as specified to establish
the number of defrosts per day under dry coil conditions and this
number shall be averaged with the number of defrosts per day calculated
under the frost load conditions. If the system has an adaptive or
demand defrost system and the optional test is not run, the number of
defrosts per day NDF shall be set to the average of 1 and
the number of defrosts per day calculated under the frost load
conditions (paragraph (c)(8)(ix) of this section).
(xi) In section C11.3, if the frost load test is not performed, the
daily contribution of the load attributed to defrost QDF in
Btu shall be calculated as follows:
[GRAPHIC] [TIFF OMITTED] TR13MY14.010
Where:
DFd = the defrost energy, in W-h, at the dry coil condition
DFf = the defrost energy, in W-h, at the frosted coil
condition
NDF = the number of defrosts per day
(xii) In section C11, if the unit utilizes hot gas defrost,
QDF and DF shall be calculated as follows:
QDF = 0.18 Btu/defrost per Btu/h capacity x Qref x NDF
Where:
Qref = Gross refrigeration capacity in Btu/h as measured at
the high ambient condition (90 [deg]F for indoor systems and 95 [deg]F
for outdoor systems)
NDF = Number of defrosts per day; this value shall be set to
the number recommended in the installation instructions for the unit
(or if no instructions, shall be set to 4) for units without adaptive
defrost and 2.5 for units with adaptive defrost
For unit coolers connected to a multiplex system: The defrost energy,
DF, in W-h = 0
For dedicated condensing systems or condensing units tested
separately:
DF = 0.5 x QDF/3.412 Btu/W-h
(xiii) Delete section C3.4.6.
(xiv) Off-cycle evaporator fan test. In lieu of section C10, follow
the following procedures: Upon the completion of the steady state test
for walk-in systems, the compressors of the walk-in systems shall be
turned off. The unit cooler's fans' power consumption shall be measured
in accordance with the requirements in Section C3.5. Off-cycle fan
power shall be equal to on-cycle fan power unless evaporator fans are
controlled by a qualifying control. Qualifying evaporator fan controls
shall have a user adjustable method of destratifying air during the
off-cycle including but not limited to: adjustable fan speed control or
periodic ``stir cycles.'' Qualifying evaporator fan controls shall be
adjusted so that the greater of a 50% duty cycle or the manufacturer
default is used for measuring off-cycle fan energy. For variable speed
controls, the greater of 50% fan speed or the manufacturer's default
fan speed shall be used for measuring off-cycle fan energy. When a
cyclic control is used at least three full ``stir cycles'' are
measured.
(xv) In lieu of Table 15 and Table 16, use the following Tables:
[[Page 27414]]
Table 15--Refrigerator Unit Cooler
--------------------------------------------------------------------------------------------------------------------------------------------------------
Unit cooler Unit cooler
air entering air entering Saturated Liquid inlet Liquid inlet Compressor
Test description dry-bulb, relative suction temp, saturation subcooling capacity Test objective
[deg]F humidity, % [deg]F temp, [deg]F temp, [deg]F
--------------------------------------------------------------------------------------------------------------------------------------------------------
Off Cycle Fan Power............. 35 <50 -- -- -- Compressor Off.... Measure fan input
power during
compressor off
cycle.
Refrigeration Capacity Suction A 35 <50 25 105 9 Compressor On..... Determine Net
Refrigeration
Capacity of Unit
Cooler.
Refrigeration Capacity Suction B 35 <50 20 105 9 Compressor On..... Determine Net
Refrigeration
Capacity of Unit
Cooler.
--------------------------------------------------------------------------------------------------------------------------------------------------------
Note: Superheat to be set according to equipment specification in equipment or installation manual. If no superheat specification is given, a default
superheat value of 6.5 [deg]F shall be used. The superheat setting used in the test shall be reported as part of the standard rating.
Table 16--Freezer Unit Cooler
--------------------------------------------------------------------------------------------------------------------------------------------------------
Unit cooler Unit cooler
air entering air entering Saturated Liquid inlet Liquid inlet Compressor
Test Description dry-bulb, relative suction temp, saturation subcooling capacity Test objective
[deg]F humidity, % [deg]F temp, [deg]F temp, [deg]F
--------------------------------------------------------------------------------------------------------------------------------------------------------
Off Cycle Fan Power............. -10 <50 -- -- -- Compressor Off.... Measure fan input
power during
compressor off
cycle.
Refrigeration Capacity Suction A -10 <50 25 105 9 Compressor On..... Determine Net
Refrigeration
Capacity of Unit
Cooler.
Refrigeration Capacity Suction B -10 <50 20 105 9 Compressor On..... Determine Net
Refrigeration
Capacity of Unit
Cooler.
Defrost......................... -10 Various -- -- -- Compressor Off.... Test according to
Appendix C
Section C11.
--------------------------------------------------------------------------------------------------------------------------------------------------------
Note: Superheat to be set according to equipment specification in equipment or installation manual. If no superheat specification is given, a default
superheat value of 6.5 [deg]F shall be used. The superheat setting used in the test shall be reported as part of the standard rating.
* * * * *
(12) Calculation of AWEF for a walk-in cooler and freezer
refrigeration system component distributed individually. This section
only applies to fixed capacity condensing units. Multiple-capacity
condensing units must be tested as part of a matched system.
(i) Calculate the AWEF for a refrigeration system containing a unit
cooler that is distributed individually using the method for testing a
unit cooler connected to a multiplex condensing system.
(ii) Calculate the AWEF for a refrigeration system containing a
condensing unit that is distributed individually using the following
nominal values:
Saturated suction temperature at the evaporator coil exit
Tevap ([deg]F) = 25 for coolers and -20 for freezers
For medium temperature (cooler) condensing units: On-cycle evaporator
fan power EFcomp, on (W) = 0.013 W-h/Btu x
qmix, cd (Btu/h); where qmix, cd is the gross
cooling capacity at the highest ambient rating condition
(90[emsp14][deg]F for indoor units and 95[emsp14][deg]F for outdoor
units)
For low temperature (freezer) condensing units: On-cycle evaporator fan
power EFcomp, on (W) = 0.016 W-h/Btu x qmix, cd
(Btu/h); where qmix, cd is the gross cooling capacity at the
highest ambient rating condition (90[emsp14][deg]F for indoor units and
95[emsp14][deg]F for outdoor units)
Off-cycle evaporator fan power EFcomp, off (W) = 0.2 x
EFcomp, on (W)
For medium temperature (cooler) condensing units: Daily defrost energy
use DF (W-h) = 0 and daily defrost heat load contribution
QDF (Btu) = 0
For low temperature (freezer) condensing units without hot gas
defrost capability:
Daily defrost energy use DF (W-h) = 8.5 x 10-3 x
(qmix, cd (Btu/h))\1.27\ x NDF for freezers
Defrost heat load contribution QDF (Btu) = 0.95 x DF (W-h)/
3.412 Btu/W-h
For low temperature (freezer) condensing units with hot gas defrost
capability, DF and QDF shall be calculated using the method
in paragraph (c)(10)(xii) of this section.
The number of defrost cycles per day (NDF) shall be set
to the number recommended in the installation instructions for the unit
(or if no instructions, shall be set to 2.5).
0
7. Appendix A to Subpart R of Part 431 is amended by:
0
a. Removing and reserving sections 4.2, 4.3, 5.1, and 5.2;
0
b. Revising paragraph 5.3(a)(1);
0
c. Removing in paragraph 5.3(a)(2) introductory text ``Internal'' and
adding ``Cold-side'' in its place; and
0
d. Removing in paragraph 5.3(a)(3) introductory text ``External'' and
adding ``Warm-side'' in its place.
The revision reads as follows:
Appendix A to Subpart R of Part 431--Uniform Test Method for the
Measurement of Energy Consumption of the Components of Envelopes of
Walk-In Coolers and Walk-In Freezers
* * * * *
4.2 [Reserved]
4.3 [Reserved]
* * * * *
5.1 [Reserved]
[[Page 27415]]
5.2 [Reserved]
5.3 * * *
(a) * * *
(1) The average surface heat transfer coefficient on the cold-
side of the apparatus shall be 30 Watts per square-meter-Kelvin (W/
m\2\*K) 5%. The average surface heat transfer
coefficient on the warm-side of the apparatus shall be 7.7 Watts per
square-meter-Kelvin (W/m\2\*K) 5%.
* * * * *
[FR Doc. 2014-10721 Filed 5-12-14; 8:45 am]
BILLING CODE 6450-01-P