Energy Conservation Program: Test Procedure for Commercial Refrigeration Equipment, 22277-22318 [2014-08640]
Download as PDF
Vol. 79
Monday,
No. 76
April 21, 2014
Part IV
Department of Energy
mstockstill on DSK4VPTVN1PROD with RULES2
10 CFR Parts 429 and 431
Energy Conservation Program: Test Procedure for Commercial
Refrigeration Equipment; Final Rule
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
PO 00000
Frm 00001
Fmt 4717
Sfmt 4717
E:\FR\FM\21APR2.SGM
21APR2
22278
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[Docket No. EERE–2013–BT–TP–0025]
RIN 1904–AC99
Energy Conservation Program: Test
Procedure for Commercial
Refrigeration Equipment
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
In this final rule, the U.S.
Department of Energy (DOE) revises and
reorganizes its test procedure for
commercial refrigeration equipment
(CRE) to clarify certain terms,
procedures, and compliance dates to
improve the repeatability and remove
ambiguity from the CRE test procedure.
In this final rule, DOE also addresses a
number of test procedure clarifications
that arose as a result of the negotiated
rulemaking process for certification of
commercial heating, ventilation, air
conditioning, refrigeration, and water
heating equipment.
DATES: The effective date of this rule is
May 21, 2014.
The incorporation by reference of
certain publications listed in this final
rule is approved by the Director of the
Office of the Federal Register as of May
21, 2014.
ADDRESSES: The docket, which includes
Federal Register notices, public meeting
attendee lists and transcripts,
comments, and other supporting
documents/materials, is available for
review at regulations.gov. All
documents in the docket are listed in
the regulations.gov index. However,
some documents listed in the index,
such as those containing information
that is exempt from public disclosure,
may not be publicly available.
A link to the docket Web page can be
found at: https://www1.eere.energy.gov/
buildings/appliance_standards/
rulemaking.aspx?ruleid=80. This Web
page will contain a link to the docket for
this rulemaking on the regulations.gov
site. The regulations.gov Web page will
contain simple instructions on how to
access all documents, including public
comments, in the docket.
For further information on how to
review the docket, contact Ms. Brenda
Edwards at (202) 586–2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Ms.
Ashley Armstrong, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Office, EE–5B, 1000
mstockstill on DSK4VPTVN1PROD with RULES2
SUMMARY:
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–6590. Email:
commercial_refrigeration_equipment@
ee.doe.gov.
Ms. Jennifer Tiedeman, U.S.
Department of Energy, Office of the
General Counsel, GC–71, 1000
Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 287–6111. Email:
mailto:Jennifer.Tiedeman@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final
rule incorporates by reference into 10
CFR part 431 the following industry
standards:
(1) ANSI/ASHRAE 72–2005,
(‘‘ASHRAE 72–2005’’), ‘‘Method of
Testing Commercial Refrigerators and
Freezers,’’ Copyright 2005.
(2) ASTM E 1084–86 (Reapproved
2009), ‘‘Standard Test Method for Solar
Transmittance (Terrestrial) of Sheet
Materials Using Sunlight,’’ approved
April 1, 2009.
Copies of ASHRAE standards may be
purchased from the American Society of
Heating, Refrigerating, and AirConditioning Engineers, Inc., 1971
Tullie Circle NE., Atlanta, GA 30329, or
at www.ashrae.org/.
Copies of ASTM standards may be
purchased from ASTM International,
100 Barr Harbor Drive, P.O. Box C700,
West Conshohocken, PA 19428, (877)
909–2786, or at www.astm.org/.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Summary of the Final Rule
III. Discussion
A. Amendments to the Test Procedure
1. Scope of Coverage
a. Salad Bars, Buffet Tables, and Other
Refrigerated Holding and Serving
Equipment
b. Chef Bases and Griddle Stands
c. Existing Cases Undergoing
Refurbishments or Retrofits
d. Case Doors Shipped as After-Market
Additions
2. Definitions Pertinent to Commercial
Refrigeration Equipment
a. Commercial Refrigeration Equipment
With Drawers
b. Transparent and Solid Doors
c. Hybrid Equipment and Commercial
Refrigerator-Freezers
3. Relationship Among Rating
Temperature, Operating Temperature,
and Integrated Average Temperature
4. Proper Configuration and Use of
Components or Features in the DOE Test
Procedure
a. Energy Management Systems
b. Lighting
c. Test Package Temperatures
5. Treatment of Other Specific Equipment
Features and Accessories During Testing
a. Customer Display Signs/Lights
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
b. Condensate Pan Heaters and Pumps
c. Anti-Sweat Door Heaters
d. Ultraviolet Lights
e. Illuminated Temperature Displays and
Alarms
f. Condenser Filters
g. Refrigeration System Security Covers
h. Night Curtains and Covers
i. Grill Options
j. Coated Coils
k. Internal Secondary Coolant Circuits
l. Wedge Cases
m. Misting or Humidification Systems
n. Air Purifiers
o. General Purpose Outlets
p. Crankcase Heaters
q. Interior/Exterior Liners
r. Other Comments Received From
Interested Parties
6. Rounding of Test Results and Certified
Ratings
7. Testing at the Lowest Application
Product Temperature
a. Definition of Lowest Application
Product Temperature
b. Incorporation by Reference of ASHRAE
72–2005
8. Clarifications in Response to
Interpretations to AHRI 1200–2010
9. Clarification of Methodology for
Measuring Total Display Area
10. Compliance Date of Test Procedure
Amendments
B. Other Notice of Proposed Rulemaking
Comments and DOE Responses
1. Ambient Test Temperatures
2. Burden of Testing
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
V. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III, Part C of the Energy Policy
and Conservation Act of 1975 (EPCA),
Public Law 94–163 (42 U.S.C. 6311–
6317, as codified), added by Public Law
95–619, Title IV, Sec. 441(a), established
the Energy Conservation Program for
Certain Industrial Equipment, a program
covering certain industrial equipment,
which includes the commercial
refrigeration equipment that is the focus
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
of this final rule.1 All references to
EPCA refer to the statute as amended
through the American Energy
Manufacturing Technical Corrections
Act (AEMTCA), Public Law 112–210
(Dec. 18, 2012).
Under EPCA, the energy conservation
program consists essentially of four
parts: (1) Testing, (2) labeling, (3)
Federal energy conservation standards,
and (4) certification and enforcement
procedures. The testing requirements
consist of test procedures that
manufacturers of covered equipment
must use as the basis for (1) certifying
to DOE that their equipment complies
with the applicable energy conservation
standards adopted under EPCA, (42
U.S.C. 6316(e)(1)), and (2) making
representations about the efficiency of
that equipment. (42 U.S.C. 6314(d))
Similarly, DOE must use these test
procedures to determine whether the
equipment complies with relevant
standards promulgated under EPCA. (42
U.S.C. 6316(e)(1))
mstockstill on DSK4VPTVN1PROD with RULES2
General Test Procedure Rulemaking
Process
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered equipment.
EPCA provides, in relevant part, that
any test procedures prescribed or
amended under this section shall be
reasonably designed to produce test
results that reflect energy efficiency,
energy use and estimated annual
operating costs of a covered product
during a representative average use
cycle or period of use and shall not be
unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
In addition, if DOE determines that a
test procedure amendment is warranted,
it must publish proposed test
procedures and offer the public an
opportunity to present oral and written
comments on them. (42 U.S.C.
6314(c)(2)) Finally, in any rulemaking to
amend a test procedure, DOE must
determine to what extent, if any, the
proposed test procedure would alter the
measured energy efficiency of any
covered product or equipment 2 as
determined under the existing test
procedure. If DOE determines that the
amended test procedure would alter the
measured efficiency of a covered
product, DOE must amend the
1 For editorial reasons, upon codification in the
U.S. Code, Part C was re-designated Part A–1.
2 The term ‘‘covered product’’ broadly refers to all
types of appliances and equipment regulated by
DOE regardless of whether they are consumer
products or commercial and industrial equipment.
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
applicable energy conservation standard
accordingly. (42 U.S.C. 6314(a)(6)(D))
Under 42 U.S.C. 6314(c)(1), no later
than 3 years after the date of prescribing
a test procedure pursuant to 42 U.S.C.
6314, and from time to time thereafter,
DOE is required to conduct a
reevaluation and determine whether to
amend the test procedure. If DOE
determines a test procedure should be
amended, it shall promptly publish in
the Federal Register proposed test
procedures, incorporating such
amendments and affording interested
persons an opportunity to present oral
and written data, views, and arguments.
(42 U.S.C. 6314(c)(2))
In February 2012, DOE published a
final rule (2012 test procedure final
rule) prescribing new amendments to
the test procedure for commercial
refrigeration equipment. 77 FR 10291,
10318–21 (Feb. 21, 2012). Pursuant to
EPCA’s requirement in 42 U.S.C.
6314(c), DOE has reevaluated the CRE
test procedure and concluded that it
should be amended to clarify a number
of provisions regarding how aspects of
the test are conducted, to more
explicitly define some terms, and to
more clearly specify the compliance
dates for various provisions. DOE’s
adopted amendments to the test
procedure are presented in this final
rule.
B. Background
EPCA mandates that the American
Society of Heating, Refrigerating, and
Air-Conditioning Engineers (ASHRAE)
Standard 117–2002, ‘‘Method of Testing
Closed Refrigerators,’’ shall be the initial
test procedure for the types of
equipment to which standards are
applicable under 42 U.S.C. 6313(c)(2)–
(3). (42 U.S.C. 6314(a)(6)(A)(ii)) EPCA
requires DOE to address whether to
amend its test procedures if ASHRAE
amends this standard. (42 U.S.C.
6314(a)(6)(E)–(F)) In 2005, ASHRAE
combined Standard 72–1998, ‘‘Method
of Testing Open Refrigerators,’’ and
Standard 117–2002 and published the
test method as ASHRAE Standard 72–
2005 (ASHRAE 72–2005), ‘‘Method of
Testing Commercial Refrigerators and
Freezers,’’ which was approved by the
American National Standards Institute
(ANSI) on July 29, 2005. Consistent with
EPCA’s requirement in 42 U.S.C.
6314(a)(6)(E), DOE reviewed ASHRAE
72–2005, as well as American
Refrigeration Institute (ARI) Standard
1200–2006 (ARI 1200–2006), which was
approved by ANSI on August 28, 2006.
DOE determined that ARI 1200–2006
included by reference the test
procedures in ASHRAE 72–2005 and
the rating temperatures prescribed in
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
22279
EPCA. (42 U.S.C. 6314(a)(6)(B)) As a
result, DOE published a final rule in
December 2006 (2006 test procedure
final rule) that adopted ARI 1200–2006
as the DOE test procedure for
commercial refrigeration equipment. 71
FR 71340, 71357 (Dec. 8, 2006). The
2006 test procedure final rule specified
rating temperatures of 38 °F (±2 °F) for
commercial refrigerators and refrigerator
compartments, 0 °F (±2 °F) for
commercial freezers and freezer
compartments, and ¥15 °F (±2 °F) for
commercial ice-cream freezers. 71 FR at
71370 (Dec. 8, 2006). DOE also adopted
Association of Home Appliance
Manufacturers (AHAM) Standard HRF–
1–2004, ‘‘Energy, Performance and
Capacity of Household Refrigerators,
Refrigerator-Freezers and Freezers,’’ for
measuring compartment volumes for
equipment covered under the 2006 test
procedure final rule. 71 FR at 71358
(Dec. 8, 2006). The test procedure
established in the 2006 final rule
became effective on January 8, 2007 (71
FR at 71340), and its use has been
required to demonstrate compliance
with the current energy conservation
standards.
More recently, on February 21, 2012,
DOE published the aforementioned
2012 test procedure final rule, in which
it adopts several amendments to the
DOE test procedure for commercial
refrigeration equipment. These
amendments include updating the
standard incorporated by reference in
the DOE test procedure in response to
the relevant industry organizations
issuing updated versions. Specifically,
DOE updated the incorporation by
reference of Air-Conditioning, Heating,
and Refrigeration Institute (AHRI)
Standard 1200 (I–P)–2010 (AHRI 1200–
2010), ‘‘Performance Rating of
Commercial Refrigerated Display
Merchandisers and Storage Cabinets,’’
as the DOE test procedure for this
equipment. 77 FR at 10318 (Feb. 21,
2012). The 2012 test procedure final
rule also includes an amendment to
incorporate by reference the updated
ANSI/AHAM Standard HRF–1–2008
(AHAM HRF–1–2008), ‘‘Energy,
Performance, and Capacity of
Household Refrigerators, RefrigeratorFreezers, and Freezers,’’ for determining
compartment volumes for this
equipment. 77 FR at 10318 and 10321
(Feb. 21, 2012). These updates were
primarily editorial in nature and aligned
the AHRI test procedure with the
nomenclature and methodology used in
DOE’s 2009 standards rulemaking on
commercial refrigeration equipment.
The updated AHRI 1200–2010 also
E:\FR\FM\21APR2.SGM
21APR2
22280
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
mstockstill on DSK4VPTVN1PROD with RULES2
references the most recent version of the
AHAM standard, AHAM HRF–1–2008.
In addition, the 2012 test procedure
final rule includes several amendments
designed to address certain energy
efficiency features that were not
accounted for by the previous DOE test
procedure, including provisions for
measuring the impact of night curtains,3
lighting occupancy sensors, and
scheduled controls. 77 FR at 10296–
10298 and 10319–10320 (Feb. 21, 2012).
In the 2012 test procedure final rule,
DOE also adopts amendments to allow
testing of commercial refrigeration
equipment that cannot operate at the
rating temperature specified in the DOE
test procedure. Specifically, the 2012
test procedure final rule allows testing
of commercial refrigeration equipment
at its lowest application product
temperature (LAPT), for equipment that
is physically incapable of reaching the
prescribed rating temperature. 77 FR at
10320 (Feb. 21, 2012). The 2012 test
procedure final rule also allows
manufacturers to test and certify
equipment at the more-stringent rating
temperatures and ambient conditions
required by NSF 4 for food safety testing.
77 FR at 10320–10321 (Feb. 21, 2012).
The test procedure amendments
established in the 2012 test procedure
final rule became effective on March 22,
2012. 77 FR at 10292 (Feb. 21, 2012).
The amendments are required to be
used in conjunction with the amended
standards established in DOE’s recently
published energy conservation
standards final rule (March 2014 energy
conservation standards final rule)
beginning on March 28, 2017. 79 FR
17726, 17727 (Mar. 28, 2014).
Since publication of the 2012 test
procedure final rule, DOE has received
a number of inquiries from interested
parties regarding DOE regulations for
commercial refrigeration equipment,
including how different types of
equipment fit into DOE’s definitions of
commercial refrigeration equipment at
10 CFR 431.62, and questions involving
certain provisions of the DOE test
procedure at 10 CFR 431.64. More
specifically, DOE has received inquiries
and questions regarding the
applicability of DOE’s test procedure
and Federal energy conservation
standards to particular models of
commercial refrigeration equipment, the
3 Night curtains are devices made of an insulating
material, typically insulated aluminum fabric,
designed to be pulled down over the open front of
the case to decrease infiltration and heat transfer
into the case when the merchandizing
establishment is closed.
4 Founded in 1944 as the National Sanitation
Foundation, the organization is now referred to
simply as NSF.
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
proper configuration and use of certain
components and features of commercial
refrigeration equipment for purposes of
testing according to the DOE test
procedure, and the compliance date of
the amendments specified in the 2012
test procedure final rule. On October 28,
2013, the U.S. Department of Energy
(DOE) issued a notice of proposed
rulemaking (hereafter referred to as the
October 2013 test procedure NOPR) to
amend the test procedure for
commercial refrigeration equipment
(CRE) appearing at 10 CFR 431.64. 78
FR 64296 (Oct. 28, 2013). In the October
2013 test procedure NOPR, DOE
presented proposed amendments to
address the questions presented by
interested parties and, where
appropriate, proposed edits to the
regulatory language to clarify DOE’s
existing regulations. 78 FR at 64296
(Oct. 28, 2013).
On February 26, 2013, members of the
Appliance Standards and Rulemaking
Federal Advisory Committee (ASRAC)
unanimously decided to form a working
group to negotiate rulemaking on
certification for commercial heating,
ventilation, and air-conditioning
(HVAC); commercial water heating
(WH); and commercial refrigeration
equipment. A notice of intent to form
the Commercial Certification Working
Group was published in the Federal
Register on March 12, 2013 (Docket No.
EERE–2013–BT–NOC–0023). 78 FR
15653 (Mar. 12, 2013). DOE received 35
nominations for the Working Group. On
April 16, 2013, DOE published a notice
of open meeting that announced the first
meeting and listed the 22 nominees that
were selected to serve as members of the
Working Group, in addition to two
members from ASRAC, and one DOE
representative. 78 FR 22431 (Apr. 16,
2013). The members of the Working
Group were selected to ensure a broad
and balanced array of stakeholder
interests and expertise, and include
efficiency advocates, manufacturers, a
utility representative, and third party
laboratory representatives. As part of
that rulemaking process, DOE
conducted a number of regulatory
negotiation sessions over the course of
the summer of 2013 involving major
stakeholders in the CRE market.5 One
outcome of these meetings was an
agreement on the need to clarify aspects
of the DOE test procedure with respect
to the treatment of specific features of
commercial refrigeration equipment. On
5 All of the details of the negotiation sessions can
be found in the public meeting transcripts that are
posted to the docket for the Working Group
(www.regulations.gov/#!docketDetail;D=EERE-2013BT-NOC-0023).
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
August 30, 2013, the Working Group
submitted a report to ASRAC containing
recommendations on the certification
requirements for HVAC, WH, and
refrigeration equipment (Docket No.
EERE–2013–BT–NOC–0023, No. 51) and
ASRAC voted unanimously to accept
these recommendations (Docket No.
EERE–2013–BT–NOC–0005, No. 13). In
the October 2013 test procedure NOPR,
DOE also proposed clarifications of the
treatment of those features by the DOE
test procedure. 78 FR at 64306–64308
(Oct. 28, 2013).
On December 5, 2013, DOE held a
public meeting (December 2013 NOPR
public meeting) to present the test
procedure amendments proposed in the
October 2013 test procedure NOPR and
accept comments from interested
parties. Interested parties submitted
comments on the ambient test
conditions and the burden of testing and
certification of commercial refrigeration
equipment. DOE analyzed all of the
comments received in response to the
October 2013 test procedure NOPR and
incorporated recommendations, where
appropriate, into this test procedure
final rule.
II. Summary of the Final Rule
In this final rule, DOE adopts
amendments to clarify DOE’s test
procedure provisions, definitions, the
treatment of specific accessories when
testing under the DOE test procedure,
and the applicability of the existing test
procedure and standards to different
types of commercial refrigeration
equipment. Specifically, DOE is
adopting edits to definitions currently
incorporated into the existing DOE test
procedure and including additional
definitions to be incorporated into the
existing test procedure (reorganized into
appendix A to subpart C of 10 CFR part
431). DOE is also adopting edits to
definitions and including additional
definitions to be incorporated into the
test procedure used to determine
compliance with the amended energy
conservation standards adopted for
commercial refrigeration equipment on
March 28, 2014 (reorganized into
appendix B to subpart C of 10 CFR part
431). 79 FR 17726. DOE does not believe
that the test procedure clarifications
adopted in this final rule will affect the
measured energy use of any covered
commercial refrigeration equipment as
they relate to the applicable energy
conservation standards. Rather, the
additional definitions and amendments
to the DOE test procedure for
commercial refrigeration equipment
would serve only to clarify existing
nomenclature, testing provisions,
compliance dates, and requirements for
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
certain features and types of commercial
refrigeration equipment; they would not
establish new requirements with regard
to testing commercial refrigeration
equipment.
DOE notes that certification is not
currently required for commercial
refrigeration equipment. On December
31, 2013, DOE published a final rule
adopting amended regulations
governing alternative energy
determination methods (AEDMs), basic
model definition, and the compliance
dates for certification of commercial
HVAC, refrigeration, and WH (2013
AEDM final rule). 78 FR 79579, 79590.
The 2013 AEDM Final Rule adopted a
certification date of December 31, 2014,
for self-contained, closed solid, and
closed transparent commercial
refrigeration equipment and a
certification date of July 1, 2015, for all
other commercial refrigeration
equipment. Id. DOE also recently
published a NOPR proposing, among
other things, to revise and expand the
certification requirements for
commercial refrigeration equipment. 79
FR 8886, 8899–8900 (Feb. 14, 2014).
The specific proposals discussed in the
NOPR were developed as a result of the
negotiations and recommendations of
the Working Group for commercial
HVAC, WH, and refrigeration
equipment (Docket No. EERE–2013–BT–
NOC–0023).
mstockstill on DSK4VPTVN1PROD with RULES2
III. Discussion
Section III.A presents all of the
revisions to the DOE test procedure
found at 10 CFR part 431, subpart C,
‘‘Uniform test method for measuring the
energy consumption of commercial
refrigerators, freezers, and refrigeratorfreezers,’’ incorporated in this final rule,
and discusses the comments received on
these topics during the December 2013
NOPR public meeting and the
associated comment period. The
changes adopted as a result of this final
rule include revisions addressing the
following:
1. The applicability of the test
procedure and related energy
conservation standards to certain types
of equipment;
2. the definitions of ‘‘hybrid
commercial refrigeration equipment,’’
‘‘commercial refrigeration equipment
with drawers,’’ and ‘‘commercial
refrigeration equipment with solid and/
or transparent doors’’;
3. the relationship among the rating
temperature, operating temperature, and
integrated average temperature (IAT);
4. the proper configuration and use of
energy management systems, lighting
controls, and test packages in the DOE
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
test procedure for commercial
refrigeration equipment;
5. the treatment of various features
and components;
6. the rounding requirements for test
results and certified ratings;
7. the provision adopted in the 2012
test procedure final rule to allow testing
at the LAPT for equipment that cannot
operate at the prescribed rating
temperature for its equipment class;
8. clarifications raised by AHRI’s
Interpretations 1, 2, 3, 4, and 5 of AHRI
1200–2010;
9. the methodology used to determine
total display area (TDA); and
10. the compliance date of certain
amendments established in the 2012 test
procedure final rule.
In response to the October 2013 test
procedure NOPR, DOE received several
comments from stakeholders that did
not pertain to a specific test procedure
amendment. In section III.B, DOE
provides responses to comments
pertaining to (1) the ambient test
temperatures required in the DOE test
procedure and (2) the burden of testing
and certifying equipment as compliant
with DOE’s energy conservation
standards.
A. Amendments to the Test Procedure
This final rule incorporates the
following changes to the test procedure
for commercial refrigeration equipment
in 10 CFR part 431, subpart C.
1. Scope of Coverage
On October 18, 2005, DOE published
a final rule adopting EPCA’s definition
of commercial refrigeration equipment.
This definition includes seven
provisions pertaining to the operational,
functional, and design characteristics of
the equipment that must be met for a
piece of equipment to qualify as
commercial refrigeration equipment. 70
FR 60407, 60414 (Oct. 18, 2005). This
definition forms the basis of the scope
of coverage of DOE’s regulations for
commercial refrigeration equipment.
While the definition of commercial
refrigeration equipment encompasses a
broad cross-section of commercial
refrigeration equipment types, DOE has
only established energy conservation
standards for certain types of covered
commercial refrigeration equipment
specified at 10 CFR 431.66, and these
standards apply to all new equipment
distributed into U.S. commerce. 76 FR
at 12426 and 12437 (March 7, 2011).
There are also several types of
equipment that meet the definition of
commercial refrigeration equipment for
which DOE has not yet set energy
conservation standards. These include,
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
22281
for example, buffet tables, salad bars,
prep tables, and griddle stands.
EPCA and DOE regulations require
manufacturers of commercial
refrigeration equipment to use the DOE
test procedure for commercial
refrigeration equipment to evaluate
compliance with any applicable energy
conservation standards and to support
any representations as to the energy use.
The DOE test procedure for commercial
refrigeration equipment is set forth at 10
CFR 431.64.
In the October 2013 test procedure
NOPR, DOE proposed clarifications
regarding the applicability of the current
DOE energy conservation standards and
test procedure to specific equipment
categories, including the following:
i. Salad bars, buffet tables, and other
refrigerated holding and serving
equipment;
ii. chef bases and griddle stands;
iii. existing cases undergoing
refurbishments or retrofits; and
iv. cases with doors shipped as aftermarket accessories.
78 FR at 64299–64300 (Oct. 28, 2013).
a. Salad Bars, Buffet Tables, and Other
Refrigerated Holding and Serving
Equipment
Salad bars, buffet tables, and other
refrigerated holding and serving
equipment are types of commercial
refrigeration equipment that store and
display perishable items temporarily
during food preparation or service. As
DOE stated in the October 2013 test
procedure NOPR, these units typically
have specific design attributes, such as
easily accessible or open bins that allow
convenient and unimpeded access to
the refrigerated products, which make
them unique from commercial
refrigeration equipment designed for
storage or retailing. 78 FR at 64299–300
(Oct. 28, 2013). In this final rule, DOE
maintains that while salad bars, buffet
tables, and other refrigerated holding
and serving equipment are covered
equipment types because they meet the
definition of commercial refrigeration
equipment in EPCA, the DOE test
procedure and current Federal
standards do not apply due to their
unique operation. Should DOE decide to
consider test procedures or energy
conservation standards for salad bars,
buffet tables, and other refrigerated
holding and serving equipment, it
would do so in a future rulemaking.
b. Chef Bases and Griddle Stands
Chef bases and griddle stands are
designed to be placed directly under
cooking equipment, such as a
commercial grill. Chef bases and griddle
stands are also designed to provide
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
22282
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
food-safe temperatures in extremely hot
environments, and thus are designed
with uniquely robust refrigeration
systems. These refrigeration systems
require larger compressors to provide
more cooling capacity for the storage
volume than equipment with
compressors that are appropriately sized
for more typical ambient temperatures.
As a result, this equipment consumes
more energy than similarly sized,
standard CRE models.
In the October 2013 test procedure
NOPR, DOE stated that chef bases and
griddle stands are considered
commercial refrigeration equipment
according to DOE’s definition at 10 CFR
431.62 and stated that it believes that
chef bases and griddle stands can be
tested using the DOE test procedure for
commercial refrigeration equipment.
DOE also noted that current energy
conservation standards do not apply to
these types of equipment and DOE did
not consider standards for this
equipment in its recent revision of
energy conservation standards for
commercial refrigeration equipment. 79
FR 17726 (Mar. 28, 2014). DOE further
proposed additions to 10 CFR 431.66 to
make clear that the current energy
conservation standards for commercial
refrigeration equipment do not apply to
chef bases and griddle stands. 78 FR at
64300 (Oct. 28, 2013). To clearly
differentiate ‘‘chef bases’’ and ‘‘griddle
stands’’ from conventional types of
commercial refrigeration equipment that
are currently covered by energy
conservation standards, DOE proposed
to establish a definition for ‘‘chef base’’
and/or ‘‘griddle stand’’ based on the
unique operation of chef bases and
griddle stands, which are designed to
provide food-safe temperatures in
extremely warm environments in excess
of 200 °F, and thus are designed with
uniquely robust refrigeration systems.
In response to the October 2013 test
procedure NOPR, interested parties
provided comments on DOE’s proposed
definition and coverage of chef bases
and griddle stands. Continental agreed
with DOE’s proposed definition of ‘‘chef
base or griddle stand,’’ stating that it
corresponds with industry practice
regarding types of units designed and
marketed for harsh applications that
should be given special consideration
for energy consumption limits.
(Continental, No. 14 at p. 1) 6 Traulsen
6 A notation in this form provides a reference for
information that is in the docket of DOE’s
rulemaking to develop test procedures for
commercial refrigeration equipment (Docket No.
EERE–2013–BT–TP–0025, which is maintained at
www.regulations.gov). This particular notation
refers to a comment: (1) Submitted by Continental;
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
suggested that DOE replace the term
‘‘cooking equipment’’ with ‘‘cooking
appliance,’’ but stated that otherwise
found the definition of ‘‘chef base or
griddle stand’’ to be acceptable.
(Traulsen, No. 17 at p. 1)
Hill Phoenix agreed with DOE that
chef bases and griddle stands do not yet
have energy conservation standards
associated with them and requested that
other, similar equipment designed to be
placed or mounted directly under
equipment that is designed to hold food
at an elevated temperature be
considered in this category. (Hill
Phoenix, No. 13 at p. 1) Similarly,
Southern Store Fixtures requested
clarification on the exact definition of
chef bases, specifically, whether this
covered refrigeration units with food
warming equipment on top. (Southern
Store Fixtures, Public Meeting
Transcript, No. 7 at p. 25) True
commented that while some consumers
may place food-warming equipment on
top of a refrigeration unit, a majority of
consumers will place high-temperature
cooking equipment atop the unit, and
manufacturers will almost always
design equipment for the harsh case.
(True, Public Meeting Transcript, No. 7
at p. 26) Hill Phoenix also noted that
NSF Type II equipment is designed to
operate at elevated temperatures and
similarly would use more energy if
tested using the current CRE test
procedure (than Type I equipment) and,
as such, suggested that NSF Type II
equipment also should fall into the
category of equipment for which
standards have not yet been set. (Hill
Phoenix, No. 13 at pp. 1–2)
DOE appreciates the agreement of
interested parties with DOE’s proposed
definition. With regard to replacing the
term ‘‘cooking equipment’’ with
‘‘cooking appliance,’’ as suggested by
interested parties, DOE’s appliance
standards and commercial equipment
program generally refers to equipment
as something designed and primarily
found in commercial applications,
while the term ‘‘appliance’’ refers to a
primarily residential application. DOE
finds that chef bases and griddle stands,
and the associated cooking apparatus
placed above these equipment, are
typically used in commercial kitchens.
As such, DOE believes the term
‘‘cooking equipment’’ is more
appropriate than ‘‘cooking appliance’’
for use in the definition of ‘‘chef bases’’
and ‘‘griddle stands,’’ as it is consistent
with DOE’s designation of equipment as
designed for commercial applications.
(2) appearing in document number 14 of the docket;
and (3) appearing on page 1 of that document.
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
Regarding the inclusion of additional
equipment designed for use directly
under equipment that is designed to
hold food at an elevated temperature as
suggested by several commenters, DOE
believes that this equipment can be
adequately represented in the current
CRE equipment categories and does not
find sufficient justification to exclude
them with the exclusion of ‘‘chef bases’’
and ‘‘griddle stands.’’ The categorization
of griddle stands was meant to
accommodate equipment that
experienced temperatures in excess of
200 °F, which requires significant
modification of the refrigeration system
to maintain cooling in such a high
temperature environment. DOE does not
find that temperatures required for
short-term holding of food are
significantly different from the
temperatures observed in restaurants or
other closed cooking environments in
which conventional commercial
refrigeration equipment is placed. DOE
does not believe that maintenance of
refrigeration performance in these
environments requires significantly
different equipment design, as is the
case of ‘‘chef bases’’ and ‘‘griddle
stands.’’ In addition, DOE has not
observed specific marketing or
identification of commercial
refrigeration equipment designed for use
under food-warming and holding
equipment. Thus, based on DOE’s
assessment, the refrigeration system and
design of this equipment is not
significantly different from other types
of commercial refrigeration equipment,
and DOE believes that the existing DOE
test procedure is sufficiently
representative of field use, and
application of the existing energy
conservation standard appropriate for
this equipment.
In response to Hill Phoenix’s
comment regarding NSF Type II
equipment, DOE believes that NSF Type
II equipment can be effectively
characterized by the existing DOE test
procedure and effectively meet the
existing energy conservation standards.
DOE previously considered NSF Type II
equipment in the 2012 test procedure
final rule and found that the compressor
systems can effectively operate at test
temperatures. In the 2012 test procedure
final rule, DOE agreed with interested
parties that testing cases at an ambient
temperature of 80 °F, rather than the
currently specified 75 °F, will not have
a significant impact on energy
consumption for cases with doors and
recognized that the impact on open
cases may be greater than on closed
cases, but did not believe that
equipment will have operation or
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
performance issues if tested at the
temperatures prescribed by the DOE test
procedure. 77 FR at 10305–10307 (Feb.
21, 2012). DOE maintains that the
energy consumption of a case should
scale with ambient temperature and
does not believe these issues will
prevent units from being tested using
the DOE-prescribed test temperatures or
complying with DOE energy
conservation standards. DOE researched
the equipment available on the market
and requested specific data regarding
the existence of cases that cannot meet
the standard or the characteristics of
their operation. DOE did not encounter
any data arising from this search that
would conflict with its current
treatment of these equipment types, and
no commenters provided any additional
data to support the contention that these
equipment types cannot meet the DOE
standards. In addition, NSF Type II
equipment is typically placed outdoors
and may see a wide variety of
temperatures in the field; thus, DOE
finds the current rating conditions of
75 °F and 45 percent relative humidity
appropriately representative for this
equipment.
mstockstill on DSK4VPTVN1PROD with RULES2
c. Existing Cases Undergoing
Refurbishments or Retrofits
Energy conservation standards apply
only to new equipment manufactured
after the effective date of the applicable
standard, and not to equipment
undergoing retrofits or refurbishments.
DOE stated in its certification,
compliance, and enforcement (CCE)
final rule, published on March 7, 2011,
that manufacturers must certify to DOE
that each basic model of covered
equipment meets the applicable
standard before distributing that
equipment into U.S. commerce. 76 FR at
12426 and 12437. In the October 2013
test procedure NOPR, DOE clarified that
its authority covers only newly
manufactured equipment and does not
extend to rebuilt and refurbished
equipment. 78 FR at 64300 (Oct. 28,
2013).
DOE did not receive any negative
comments in response to this
clarification and continues to maintain
that its energy conservation standards
and test procedures apply to only new
equipment and not existing equipment
undergoing refurbishments or retrofits.
d. Case Doors Shipped as After-Market
Additions
A basic model of commercial
refrigeration equipment is tested, rated,
and subject to specific standards based
on the equipment class(es) to which that
basic model belongs. For commercial
refrigeration equipment, one of the
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
features that distinguishes the current
equipment classes for the purposes of
applying standards is the presence of
doors (i.e., open or closed). In the
October 2013 test procedure NOPR,
DOE proposed that when a model of
commercial refrigeration equipment is
offered for sale with doors as an
optional accessory, regardless of how
the unit is shipped, such unit must be
tested and certified as equivalent to a
basic model shipped with doors preinstalled. DOE also requested comment
on whether, if this same model is
offered for sale as a model without
doors, it should be tested and rated with
no doors installed and meet the
corresponding energy conservation
standards for open case equipment.
In response to the October 2013 test
procedure NOPR, the Northwest Energy
Efficiency Alliance (NEEA) commented
that it believed equipment that can
optionally be sold with doors or without
should be tested and certified in each
configuration. (NEEA, No. 16 at p. 1)
DOE did not receive any negative
comments on this proposal.
DOE agrees with NEEA that
commercial refrigeration equipment that
can optionally be sold with doors or
without doors should be treated as
separate basic models in separate
equipment classes and should be tested
both with doors and without doors. This
is consistent with the definition of basic
models, which is based on features that
affect the energy use of a covered piece
of equipment as established in DOE’s
CCE final rule, and requires individual
models that would fall into different
equipment classes to be certified
separately. 76 FR at 12429 (March 7,
2011) (see 10 CFR 431.62).
2. Definitions Pertinent to Commercial
Refrigeration Equipment
DOE currently categorizes commercial
refrigeration equipment by equipment
classes based on several general
characteristics of a given basic model.
10 CFR 431.62 provides definitions that
assist manufacturers in determining
which equipment class and associated
energy conservation standard applies to
a given basic model of commercial
refrigeration equipment. However, 10
CFR 431.62 does not provide explicit
guidance on how to classify commercial
refrigeration equipment with drawers or
how to differentiate between a unit with
transparent doors and a unit with solid
doors. In the October 2013 test
procedure NOPR, DOE proposed
definitions and clarifications regarding
the treatment of commercial
refrigeration equipment with drawers
and commercial refrigeration equipment
with transparent and/or solid doors. 78
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
22283
FR at 64300–03 (Oct. 28, 2013). DOE
also proposed clarification with regard
to the definitions for and categorization
of hybrid equipment and commercial
refrigerator freezers. 78 FR at 64303
(Oct. 28, 2013). These proposals,
comments submitted by interested
parties, and DOE’s response to
submitted comments are presented in
the subsequent sections.
a. Commercial Refrigeration Equipment
With Drawers
DOE’s definition of commercial
refrigerator, freezer, and refrigeratorfreezer specified at 10 CFR 431.62
includes a requirement that the
equipment ‘‘[h]as transparent or solid
doors, sliding or hinged doors, a
combination of hinged, sliding,
transparent, or solid doors, or no
doors.’’ Based on this definition, DOE
interprets the term ‘‘door’’ to mean any
movable component of the CRE unit
that:
1. When closed, separates the interior
refrigerated space from the ambient air;
and
2. when opened, provides access to
the refrigerated products inside the CRE
unit.
Based on this definition, in the
October 2013 test procedure NOPR,
DOE presented its view that drawers are
treated as equivalent to doors for
purposes of DOE’s regulatory program,
including compliance with DOE’s
energy conservation standards.
Likewise, DOE believes drawers are
treated as doors when conducting the
DOE test procedure. 78 FR at 64300–01
(Oct. 28, 2013).
To demonstrate the comparable
operation of models of commercial
refrigeration equipment with drawers as
compared to similar models with
traditional doors, in the October 2013
test procedure NOPR, DOE presented
the test results for several CRE units
with drawers from multiple
manufacturers using the current DOE
test procedure and compared their
performance to nearly identical units
with hinged doors (belonging to the
vertical closed solid, or VCS, equipment
family) from the same manufacturer
product lines. As a result of the testing,
DOE found that the units with drawers
performed similarly to the hinged-door
units to which they were compared.
DOE also presented the effect of draweropening distances for CRE units with
drawers and found minimal variation in
measured total daily energy
consumption (TDEC) at different drawer
opening distances. 78 FR at 64301 (Oct.
28, 2013). DOE believes these test
results confirm that the door-opening
requirements in the DOE test procedure
E:\FR\FM\21APR2.SGM
21APR2
22284
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
mstockstill on DSK4VPTVN1PROD with RULES2
apply to basic models of commercial
refrigeration equipment with drawers,
just as they do for CRE units with other
types of hinged or sliding doors, and
that the current energy conservation
standards prescribed for commercial
refrigeration equipment are equally
applicable to CRE units with drawers.
To clarify how DOE’s regulatory
scheme applies to basic models of CRE
units with drawers, in the October 2013
test procedure NOPR, DOE proposed to
add language to the definition section at
10 CFR 431.62, defining doors as being
inclusive of drawers, and requested
comment on its proposed definition. 78
FR at 64301 (Oct. 28, 2013).
Several interested parties commented
on DOE’s proposed definition of door to
include drawers, the applicability of the
DOE test procedure to units with
drawers, and DOE’s coverage of units
with drawers in general. DOE presents
the comments received by interested
parties and DOE’s response in the
following sections.
Definition of Door
In the October 2013 test procedure
NOPR, DOE defined door at 78 FR
64301 (Oct. 28, 2013).
DOE received several comments and
suggestions from interested parties
regarding its proposed definition for
doors. Continental commented that
DOE’s definition of ‘‘door’’ should not
include drawers. Continental stated that
it is counter-intuitive to define a
‘‘drawer’’ as a subset of a ‘‘door’’ and
this would result in confusion and
misinterpretation and suggested that,
instead, DOE change the usage of the
term ‘‘door’’ in applicable procedures to
‘‘door or drawer.’’ (Continental, No. 14
at p. 1) AHRI did not agree with DOE’s
proposed definition of ‘‘door’’ to be
inclusive of drawers and instead
suggested that DOE create separate
definition for drawers or amending the
current definition for ‘‘doors’’ by
replacing ‘‘door’’ with the term ‘‘door/
drawer.’’ (AHRI, No. 15 at p. 3)
NEEA, AHRI, Southern Store Fixtures,
and True commented that DOE’s
definition of doors would include night
curtains and recommended that DOE
include a specific exclusion of night
curtains in the definition of doors.
(NEEA, No. 16 at p. 2; AHRI, No. 15 at
p. 4; Southern Store Fixtures, Public
Meeting Transcript, No. 7 at p. 32; True,
Public Meeting Transcript, No. 7 at p.
37) Several interested parties, including
NEEA, Traulsen, True, Southern Store
Fixtures, and Unified Brands,
recommended that DOE remove the
‘‘use of tools’’ clause from the
definition, as most drawers and some
doors are intended to be removed
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
without the use of tools. (NEEA, No. 16
at p. 2; Traulsen, No. 17 at p. 2; True,
Public Meeting Transcript, No. 7 at p.
37; Southern Store Fixtures, Public
Meeting Transcript, No. 7 at p. 37;
Unified Brands, No. 9 at p. 1)
DOE appreciates the suggestions of
interested parties regarding changes and
improvements to DOE’s proposed
definition for door. DOE agrees with
interested parties that a night curtain
would have met the definition of ‘‘door’’
proposed in the October 2013 test
procedure NOPR. This was not DOE’s
intent, as night curtains are intended to
be treated as an energy-saving feature
for open cases. DOE also adopted a
specific definition for night curtain in
the 2012 test procedure final rule. 77 FR
at 10318 (Feb. 21, 2012). To clarify that
night curtains are not to be treated as
doors for the purposes of testing using
the DOE test procedure or complying
with DOE’s energy conservation
standards, in this final rule DOE is
adding language to the definition of
‘‘door’’ to exclude night curtains.
DOE also acknowledges comments
submitted by interested parties
regarding the requirement that a door be
‘‘affixed such that it is not removable
without the use of tools.’’ DOE’s intent
with the proposed clause was to exclude
temporary insulating panels or other
devices that are not doors, but may be
placed on open cases periodically to
limit energy consumption when the case
is not in use for merchandizing. DOE
agrees with commenters that some doors
and drawers are intended to be
removable without the use of tools for
the ease of cleaning, product loading, or
other utility features, and that these
cases should still be treated as closed
cases with doors. Therefore, in the
definition of ‘‘door’’ adopted in this
final rule, DOE is removing the ‘‘use of
tools’’ provision. Upon further
consideration, DOE found the statement
to be superfluous. This does not include
night curtains or other panels that are
not in place when the case is being used
for merchandising.
Regarding the inclusion of drawers in
DOE’s definition of ‘‘door,’’ DOE
acknowledges the concerns of interested
parties that referring to drawers as doors
in the test procedure for commercial
refrigeration equipment may be
confusing and non-intuitive. However,
DOE’s test procedure for commercial
refrigeration equipment only addresses
the treatment of ‘‘doors’’ and does not
explicitly reference the treatment of
‘‘drawers.’’ This terminology is
established in ASHRAE Standard 72–
2005, the method of test referenced in
AHRI 1200–2010, the test procedure
incorporated by reference as the
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
foundation of DOE’s test procedure for
commercial refrigeration equipment.
Given that the nomenclature in these
referenced test standards is not the sole
purview of DOE, DOE believes the most
straightforward method for clarifying
that the treatment of drawers should be
identical to the treatment of doors for
the purposes of conducting the DOE test
procedure and compliance with DOE’s
energy conservation standards is to
continue to define door as inclusive of
drawers, as proposed in the October
2013 test procedure NOPR. 78 FR at
64301 (Oct. 28, 2013). However, if the
ASHRAE Standard Project Committee
were to revise ASHRAE Standard 72–
2005 to include drawers specifically,
DOE could review and incorporate the
revised test standard, if appropriate, to
further eliminate confusion. DOE
understands that this may occur in a
forthcoming version of ASHRAE
Standard 72, anticipated to be published
in 2014. Until such a revised test
standard is available, DOE will also
incorporate language into the test
procedure at 10 CFR 431.64 to specify
that drawers are to be treated as
identical to doors when conducting the
DOE test procedure.
Applicability of the DOE Test Procedure
to Commercial Refrigeration Equipment
With Drawers
Several interested parties commented
that the current DOE test procedure for
commercial refrigeration equipment
does not provide sufficient clarity
regarding how to test units with
drawers. Specifically, commenters
identified (1) the type and configuration
of drawer pans, (2) the location and
number of simulators and test packages
in the drawers, (3) how to determine
interior refrigerated volume of a
drawered unit, and (4) how far a drawer
should be opened during testing as areas
of ambiguity when applying the existing
DOE test procedure to CRE models with
drawers. (Unified Brands, No. 9 at p. 2;
Traulsen, No. 17 at p. 2; National,
Public Meeting Transcript, No. 7 at p.
42) Unified Brands and Traulsen
commented that, depending on the
design of the drawer unit, moving the
test simulators in and out of the
refrigerated compartment may cause
variation in the integrated average
temperature (IAT), which could drive
increased energy consumption, and
added that testing of commercial
refrigeration equipment with doors does
not require test simulators to be
removed from the refrigerated
compartment. (Unified Brands, No. 9 at
p. 2; Traulsen, No. 17 at p. 2)
Specifically, National opined that when
calculating total volume of a drawered
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
unit, there should be considerations for
drawer pan capacity. Additionally,
National urged DOE to center the
definition of a unit’s volume on the
amount of product that the unit can
hold. (National, Public Meeting
Transcript, No. 7 at p. 42)
Unified Brands commented that it is
inappropriate for a drawer to be
included as equivalent to a door for the
purposes of testing and compliance with
the DOE test procedure and energy
conservation standards because when a
drawer is opened, the entire contents of
the drawer are removed from the
interior volume of the cabinet and
exposed to the ambient conditions. In
addition, Unified Brands stated that it
manufactures drawer units in which the
drawer is fully insulated refrigerated
space and the cabinet is mostly
structural. Unified Brands further
commented that drawer units are often
designed with additional refrigeration
capacity beyond that of a similarly sized
door unit due to the unique air flow and
refrigeration challenges that drawers
provide. (Unified Brands, No. 9 at pp.
1–2)
Lastly, Unified Brands commented
that current CRE models may require as
many as 12 separate drawer openings,
requiring 12 door-opening apparatus,
the electronic capability to control all of
the openers, and a significant amount of
space. Unified Brands added that testing
equipment with drawers also increases
burden by increasing the complexity of
the test and increasing the risk
associated with managing thermocouple
wires to prevent thermocouple
displacement and breakage. (Unified
Brands, No. 9 at pp. 2–3) Unified Brands
was also concerned that multiple
thermocouple wires may prevent the
drawer gaskets from sealing properly,
resulting in increased energy use.
(Unified Brands, No. 9 at p. 2)
Based on comments received by
interested parties, DOE reviewed its test
procedure for commercial refrigeration
equipment with regards to specific
requirements necessary to accommodate
or clarify the application of the CRE test
procedure to equipment with drawers.
The DOE test procedure for commercial
refrigeration equipment adopts specific
sections of the Association of Home
Appliance Manufacturers Standard for
Energy, Performance and Capacity of
Household Refrigerators, RefrigeratorFreezers and Freezers (AHAM HRF–1–
2004) as the protocol for determining
refrigerated compartment volume for
compliance with the current standards
and specific sections of AHAM HRF–1–
2008 for measuring refrigerated
compartment volume to determine
compliance with the amended standards
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
adopted in the March 2014 energy
conservation standard final rule. 79 FR
17726 (Mar. 28, 2014). DOE reviewed
these methods for determining
refrigerated compartment volume and
finds them sufficient for determining
internal refrigerated volume for
commercial refrigeration equipment
with drawers.
With regard to the comment from
Unified Brands about a model of
commercial refrigeration equipment in
which the drawers are insulated and the
outer case acts more as a support, DOE
researched this type of commercial
refrigeration equipment and reviewed
the applicable methods for calculating
refrigerated or frozen compartment
volume. DOE specifically references
section 3.21, ‘‘Volume,’’ of AHAM HRF
1–2004 and section 3.30, ‘‘Volume,’’ of
AHAM HRF 1–2008. Both of these
sections contain definitions for ‘‘fresh
food compartment volume’’ and ‘‘freezer
compartment volume,’’ which are
defined as the portion of the total
refrigerated volume above or below
32 °F, respectively. The total refrigerated
volume is a combination of these two
compartment volumes. Based on these
definitions, DOE believes that only the
volume that is purposefully refrigerated
for food display or storage is to be
included in the refrigerated volume
calculation. Thus, in the case of a
drawered CRE model in which only the
drawers are insulated and directly
cooled, only the interior volume of the
drawers would be included in the
calculation of refrigerated volume, not
the entire volume of the cabinet
housing. DOE believes that this is clear
in the existing protocol specified in
AHAM HRF 1–2004 and AHAM HRF 1–
2008 and further clarification is not
necessary on this matter.
Regarding test simulator locations,
filler package placement, and pan
configuration for CRE models with
drawers, DOE reviewed the ASHRAE
Standard 72–2005, which is the
industry standard referenced by the
DOE test procedure, to determine the
sufficiency of existing guidance for
placing test simulators and filler
packages in commercial refrigeration
equipment with drawers. ASHRAE
Standard 72–2005 specifically addresses
CRE models with shelves and without
shelves and, in general, specifies that
test simulators shall be placed at the
right end, front and back, and the left
end, front and back. Test simulators are
also to be placed intermittently across
the face of CRE model at shelf standard
breaks or with specific spacing in the
case of CRE models without shelving.
Since CRE models with drawers
typically do not have shelves, these
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
22285
models will be treated as CRE models
without shelves. Therefore, applying the
requirements for CRE models without
shelves to CRE models with drawers, it
is logical that test simulators should be
placed in the front and back corners of
the drawer and, depending on the width
of the drawer, 36- to 48-inch intervals
across the width of the drawer in the
front and back, as is the case for
commercial refrigeration equipment
without shelves. DOE does not see a
problem applying the requirements for a
CRE model without shelves in ASHRAE
Standard 72–2005 to a CRE model with
drawers, which qualifies as a CRE
model without shelves, and believes
placing test simulators in this manner
will accurately and representatively
capture the internal temperature of the
equipment.
With regard to filler package
placement, ASHRAE Standard 72–2005
specifies that the remaining usable
space where test simulators are not
required shall be loaded with filler
packages or filler material so as to
occupy between 70 and 90 percent of
the refrigerated volume and to
uniformly occupy the space from the
front to the rear. Again, DOE does not
anticipate issues in applying these
requirements to CRE models with
drawers just as they are applied to CRE
models with doors. In the case of CRE
models with drawers, each drawer
should be filled with filled packages or
filler material up to the load limit. DOE
acknowledges that it is theoretically
possible that the drawers could hold
less than 70 percent of the net
refrigerated volume if the entire cabinet
was refrigerated. However, DOE notes
that this would be an inefficient design
choice and DOE does not see a
significant utility associated with
having significant amounts of unusable
refrigerated volume. Therefore, DOE
does not believe accommodation is
necessary for such situations. If a
manufacturer produces a case that
cannot meet the requirements of 70
percent packing, that manufacturer must
apply for a test procedure waiver.
As to the pan configuration necessary
for testing CRE models with drawers,
DOE understands that CRE with drawers
often consist of a sliding frame that
accommodates the placement of
standard size pans typically used by the
food service industry for holding food.
DOE acknowledges that theoretically
many configurations of pans could be
placed in a commercial refrigerator or
freezer with drawers. DOE’s test
procedure requires that the model be
configured with a pan configuration that
allows for the maximum packing of
filler packages as specified by the test
E:\FR\FM\21APR2.SGM
21APR2
22286
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
procedure, but not exceeding 90 percent
of the refrigerated volume. To clarify
this requirement, DOE is adopting
language to specify that commercial
refrigeration equipment with drawers
should be configured with the drawer
pans that allow for the maximum
packing of test simulators and filler
packages without exceeding 90 percent
of the refrigerated volume.
In response to the Unified Brands
comment regarding the burden of
conducting the test procedure for
commercial refrigeration equipment on
equipment with drawers, DOE does not
believe that the requirements are
significantly more complex than those
for testing commercial refrigeration
equipment with doors. Numerous dooropening apparatus are also required for
multi-compartment doored cases, and
thermocouples must also be configured
so as to measure test simulators in the
internal refrigerated volume. DOE
acknowledges that incrementally more
thermocouple wire may need to be
attached to thermocouples placed in test
simulators in drawers, to ensure
sufficient slack is available for the
drawer to fully open and fully close
without disturbing the thermocouple
placement within the test simulator.
However, DOE does not believe that
providing this additional length of
thermocouple wire is a significant
additional burden, given many test
simulators may already be equipped
with excess thermocouple wire.
mstockstill on DSK4VPTVN1PROD with RULES2
General Treatment of Drawers as
Equivalent to Doors
In response to the October 2013 test
procedure NOPR, DOE also received
several comments from interested
parties regarding the appropriateness of
treating drawers as equivalent to doors
for the purposes of testing under DOE’s
test procedure for commercial
refrigeration equipment and compliance
with DOE’s energy conservation
standards in general. DOE presents
these comments and DOE’s response in
this section.
Traulsen commented that units with
drawers typically hold less product by
mass and volume than an identical unit
with doors only and questioned how
this will affect the IAT and the
infiltration of air during the door/
drawer opening period. (Traulsen, No.
17 at p. 2) According to Unified Brands,
many drawer units are specifically
designed for drawers and do not have a
door unit of similar construction for
comparison and, prior to assuming
similarity between door and drawer
units, a statistically significant sample
of product designs should be tested and
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
validated. (Unified Brands, No. 9 at pp.
1–2)
DOE’s test data, presented in the
October 2013 test procedure NOPR,
does not suggest that drawers are
significantly different from doors in
terms of applying the DOE test
procedure or the thermodynamic
requirements. 78 FR at 64301 (Oct. 28,
2013). Lacking additional data
contradicting DOE’s test data, DOE is
maintaining its position that drawers are
to be treated as equivalent to doors for
the purposes of conducting the DOE test
procedure and complying with DOE’s
energy conservation standards.
b. Transparent and Solid Doors
In reviewing the CRE test procedure,
DOE identified opportunities for
clarification within the definitions and
classifications of commercial
refrigeration equipment with solid doors
versus those with transparent doors. In
the October 2013 test procedure NOPR,
DOE proposed several new definitions
for transparent, closed solid, and closed
transparent to clarify the test procedure
requirements at 10 CFR 431.64 to ensure
appropriate equipment categorization.
78 FR at 64301–64303 (Oct. 28, 2013).
Definition of Transparent
The DOE test procedure for
commercial refrigeration equipment, as
amended by the 2012 test procedure
final rule, incorporates by reference
AHRI 1200–2010. 77 FR at 10318 (Feb.
21, 2012). AHRI 1200–2010 defines total
display area (TDA) as ‘‘the sum of the
projected area(s) for visible product
expressed in [square feet]’’ and provides
procedures for calculating the TDA of
commercial refrigeration equipment
with panels, end enclosures, doors, or
other envelope components that have
some transparent area(s). Appendix D of
AHRI 1200–2010 provides further
guidance and examples to clarify the
calculation of TDA. The appendix also
defines a transparent material as that
which allows at least 65 percent light
transmittance. Therefore, based on
AHRI 1200–2010, a transparent door
would be one partially or entirely
composed of a material that allows
greater than or equal to 65 percent light
transmittance.
In the October 2013 test procedure
NOPR, DOE proposed a definition for
‘‘transparent’’ based on an unambiguous
measurement of the light transmission
properties of a material in accordance
with ASTM Standard E 1084–86
(Reapproved 2009), ‘‘Standard Test
Method for Solar Transmittance
(Terrestrial) of Sheet Materials Using
Sunlight,’’ at normal incidence. 78 FR at
64301–64302 (Oct. 28, 2013).
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
In response to DOE’s proposed
definition of ‘‘transparent,’’ several
interested parties provided comments
and suggestions for adopting an
appropriate definition for commercial
refrigeration equipment applications.
Continental stated that DOE’s proposed
definition of ‘‘transparent’’ introduces
unnecessary complexity and suggested
that a simple dictionary-type definition
as ‘‘able to [be] seen through’’ would be
sufficient for nearly all applications for
covered commercial refrigeration
equipment. Continental added that DOE
has the right and obligation to challenge
a manufacturer’s claim if DOE believes
it does not meet a basic definition of the
terminology or the intent of the
standard. (Continental, No. 14 at p. 1)
NEEA, True, and Hussmann were
concerned that DOE’s proposed
threshold of 65 percent light
transmittance might inadvertently
exclude some types of Low-E, high
performance glass, which can have
visible transmittance as low as 45
percent. (NEEA, No. 16 at p. 2; True,
Public Meeting Transcript, No. 7 at p.
53; Hussmann, No. 11 at p. 1) NEEA and
Hussmann recommended DOE consider
lowering the threshold for determining
whether a material is transparent or not,
and suggested that DOE possibly refer to
the WINDOWS 5 model, developed by
Lawrence Berkeley National
Laboratory,7 that was used in the
engineering analysis. (NEEA, No. 16 at
p. 2; Hussmann, No. 11 at p. 1)
True and Southern Store Fixtures
noted that self-serve counter display
cases may be fitted with see-through
mirror-finish, or glass reflective panels,
which would affect the transparency of
the doors depending on the
measurement angle and direction.
(Southern Store Fixtures, Public
Meeting Transcript, No. 7 at p. 53; True,
Public Meeting Transcript, No. 7 at p.
55)
True also noted that the majority of
losses through transparent doors were a
result of the difference in insulation
capacities between the glass door and
the solid door, and that only a small
portion of the losses were due to light
entering through transparent doors.
True therefore opined that treating a
glass door as solid, irrespective of its
transparency, was inaccurate. (True,
Public Meeting Transcript, No. 7 at p.
51)
DOE appreciates the suggestions by
commenters. In response to
Continental’s concern regarding the
potential complexity of a quantitative
method for determining a transparent
7 https://windows.lbl.gov/software/window/
window.html.
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
material, rather than a definition based
on the intent or application of the
material, DOE notes that the method to
determine transparency of a material is
not mandatory for equipment
classification or testing. In the October
2013 test procedure NOPR, DOE noted
that determination of the light
transmittance of a transparent material
is not required in all cases to classify a
basic model of commercial refrigeration
equipment as equipment with
transparent doors and clarified that
manufacturers may continue to specify
equipment as belonging to a transparent
equipment class (e.g., vertical closed
transparent or horizontal closed
transparent) or a solid without testing
because, in most cases, it will be
obvious whether a material is
transparent or not; therefore, testing
would not be necessary to verify the
classification of a material as
transparent or not. 78 FR at 64302 (Oct.
28, 2013). Thus, incorporation of a
quantitative test procedure is not
anticipated to add to the complexity and
burden of conducting the DOE test
procedure for most models of
commercial refrigeration equipment.
DOE agrees with Continental that
DOE has the obligation and the right to
challenge the classification of certain
materials as transparent. However, there
may be cases in which the material is
not obviously transparent or solid, such
as basic models with special decals or
opaque glass. DOE prefers to use a
quantitative, objective method to
determine transparency of a material
and subsequent equipment
classification, which will also provide
certainty to the regulated industry.
Therefore, DOE is adopting in this final
rule a definition of ‘‘transparent’’ based
on the evaluation of that material in
accordance with ASTM Standard E
1084–86 (Reapproved 2009).
In response to the comments from
NEEA, True, and Hussmann expressing
concern about the inclusion of Low-E
and high-performance glass as a
‘‘transparent’’ material when such
fenestration products may have visible
transmittance values as low as 45
percent, DOE researched available highperformance glass door products for
commercial refrigeration equipment to
determine an appropriate threshold for
light transmittance. While some Low-E
glass with reflective coatings designed
for extremely sunny environments can
have visible transmittance values as low
as 0.2 (meaning 20 percent transparent),
DOE finds that it is unlikely commercial
refrigeration equipment would
incorporate such material since this
equipment is not typically installed in
extremely sunny environments. In
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
addition, such a low visible
transmittance value would significantly
diminish the ability of consumers to see
through the glass to the contents inside
the unit, which is the intent of
including transparent material in a
given CRE design. Therefore, DOE is
adopting a threshold for determining a
transparent material of 45 percent light
transmittance as determined in
accordance with ASTM Standard E
1084–86 (Reapproved 2009).
Regarding comments by True and
Southern Store Fixtures, DOE
acknowledges that some glass may be
available with a mirrored finish to
prevent viewing or light transmittance
when viewed from one side of the glass,
but not the other. DOE does not intend
to treat such glass as solid, as it provides
the function of transparent material (i.e.,
being able to see through to the internal
contents of the case) when viewed from
one side of the glass. In the equipment
described by commenters, this would be
when viewed at an angle of incidence
normal (90 degrees) to the plane of the
case and from the exterior. DOE believes
that reflective glass would fully meet
the definition of ‘‘transparent’’ when
tested at normal incidence and in the
intended direction of viewing.
Therefore, to clarify the orientation of
glass when testing using ASTM
Standard E 1084–86 (Reapproved 2009),
DOE is incorporating language into the
definition of ‘‘transparent’’ to specify
that the material is to be tested at
normal incidence and in the intended
direction of viewing.
Definition of Equipment With
Transparent Doors Versus Solid Doors
In the energy conservation standards
specified at 10 CFR 431.66, DOE refers
to equipment families using the terms
‘‘closed solid’’ and ‘‘closed transparent’’
(for example, vertical closed solid (VCS)
and vertical closed transparent (VCT)).
In the October 2013 test procedure
NOPR, DOE proposed definitions for
‘‘closed transparent’’ and ‘‘closed solid’’
to clarify what factors differentiate a
CRE basic model as a transparent-door
model or a solid-door model. DOE based
its proposed definitions on a percentage
of outer surface area of all doors that are
transparent. Specifically, DOE proposed
that if 75 percent or more of the outer
surface area of all doors on a CRE unit
is transparent, that unit would be
considered closed transparent.
Conversely, DOE proposed that ‘‘closed
solid’’ would refer to CRE equipment
with doors, and in which more than 75
percent of the outer surface area of all
doors is not transparent. 78 FR at 64318
(Oct. 28, 2013). As DOE presented at the
December 2013 test procedure NOPR
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
22287
public meeting, DOE intended for the
definition of ‘‘closed solid’’ to include
equipment in which more than 25
percent of the outer surface area of all
doors on a unit are not transparent, and
notes that the inclusion of the 75
percent figure in the October 2013 test
procedure NOPR was a typographical
error.
DOE received several comments from
interested parties in response to the
categorization of closed transparent
versus closed solid equipment families
proposed in the October 2013 test
procedure NOPR. Hill Phoenix, AHRI,
and Hussmann commented that a case
that has a transparent door on the front
and a solid door on the side or back,
where approximately 50 percent of the
door surface area is transparent and
approximately 50 percent of the door
surface area is solid, was not adequately
addressed by DOE’s proposed
definitions. Hill Phoenix, AHRI, and
Hussmann further suggested that a CRE
model where 25 percent or more of the
outer surface area of all doors on the
unit are transparent should be treated as
a transparent case and that any case that
has more than 75 percent of the door
area as solid should be subject to the
closed solid energy conservation
standards. (Hill Phoenix, No. 13 at p. 2;
AHRI, No. 15 at p. 4; Hussmann, No. 11
at p. 2)
Continental commented that DOE’s
proposed definitions do not correlate
with the way commercial refrigeration
systems are typically designed for units
with transparent doors. Continental
further commented that if more than 25
percent of the doors on a unit are
transparent, the refrigeration systems
are commonly ‘‘upsized’’ to provide the
increased cooling capacity required.
Thus, Continental suggested that DOE’s
definition should align with industry
practice and adopt a 25 percent
threshold or, at most, a 32 percent level.
(Continental, No. 14 at p. 2)
Traulsen recommended that the
definition of ‘‘closed transparent’’ refer
to CRE models in which 75 percent or
more of the transparent area of the doors
on the customer side of the pass-through
or the operator/customer side of the
reach-in 8 style unit is transparent, and
‘‘closed solid’’ be defined as equipment
in which more than 75 percent of the
outer surface area of all the doors on
each side of the unit is not transparent.
Traulsen added that transparent doors
and the design and operation of closed
transparent equipment carry a higher
8 The comment submitted by Traulsen referenced
‘‘read-in’’ style units. DOE believes Traulsen meant
to reference ‘‘reach-in’’ style units and has amended
the submitted comment to reflect this.
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
22288
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
energy penalty and DOE should be
cautious of creating definitions that
classify equipment with transparent
doors as closed solid equipment.
Traulsen further recommended ignoring
other doors on the backside of the unit
when classifying closed transparent
equipment, similar to the treatment of
pass-through-type equipment in
ASHRAE Standard 72–2005, where only
doors on the one side of the passthrough should be operated during the
test. (Traulsen, No. 17 at p. 2)
Hussmann suggested that DOE further
clarify what ‘‘the outer surface area of
the door’’ is and whether it includes
mullions and door frames. (Hussmann,
No. 11 at p. 2)
Alternatively, Zero Zone offered that
the ENERGY STAR® 9 program uses
definitions that describes a number of
additional details about glass door
equipment and recommended that DOE
should consider these definitions. For
example, Zero Zone stated that it
manufactures a CRE model with
transparent doors on the front and solid
doors on the back, and that the ENERGY
STAR definitions would classify such a
case as a glass door cabinet and DOE’s
proposed definitions would qualify
such as case as a solid door cabinet. In
addition, Zero Zone suggested that DOE
perform an engineering analysis to
assess the impact and feasibility of
reduced energy conservation standard
levels for closed transparent equipment
with a small percent of transparent area.
(Zero Zone, No. 18 at pp. 1–2)
In response to comments regarding
the fraction of transparent surface area
of all outer doors on a given CRE model
that differentiates closed transparent
equipment from closed solid equipment,
DOE acknowledges comments from
interested parties regarding the
increased energy use associated with
closed transparent equipment due to the
increased thermal conductance of glass
as compared to insulated case walls and
other design and operation features. In
determining the fraction of transparent
door surface area to qualify a basic
model of commercial refrigeration
equipment as equipment with
transparent doors, DOE proposed a
transparent surface area higher than 50
percent to ensure that only doors with
a majority of transparent surface area
were considered transparent doors. 78
FR at 64302 (Oct. 28, 2013). However,
DOE finds the suggestions of Traulsen,
9 ENERGY STAR is a joint program of the U.S.
Environmental Protection Agency and DOE that
establishes a voluntary rating, certification, and
labeling program for highly energy efficient
consumer products and commercial equipment.
Information on the program is available at
www.energystar.gov/index.cfm?c=home.index.
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
Hill Phoenix, AHRI, and Hussmann—
that equipment with transparent doors
on one side of the cabinet and solid
doors on another be treated as
transparent equipment—reasonable and
consistent with DOE’s intended
application of closed transparent
equipment. That is, equipment with
only one transparent door and the
remaining sides consisting of solid
insulated case wall and similar
equipment with two doors, one that is
transparent and one on another side that
is solid, should be treated equivalently
for the purposes of testing and
compliance with DOE energy
conservation standards. However, DOE
finds the suggestion of Traulsen to
address only the customer-side of a CRE
model to be inconsistent and
impractical to implement given the
variety of door configurations that could
be present on other sides of the CRE
unit. DOE believes it is most appropriate
to address the outer surface area of all
the doors that may be present on any of
the sides of a CRE model when
determining whether the equipment
belongs in the closed solid or closed
transparent equipment family.
Regarding Hussmann’s request that
DOE provide additional clarity as to the
definition of ‘‘outer surface area,’’ DOE
used the term ‘‘outer surface area’’ to
refer to the surface area on only one side
of a door. DOE acknowledges that solid
and transparent doors installed on
commercial refrigeration equipment are
physically three-dimensional objects,
with surface area measurements on each
of six sides: Four edges and two faces.
DOE used the term ‘‘outer surface area’’
to refer to the side of the door facing out
of, rather than into, the cabinet. In
response to Hussmann’s comment
inquiring whether the outer surface area
of the door included mullions and door
frames, DOE is clarifying that the outer
surface area to be accounted for is that
of the door itself, as defined in section
III.A.2.a, as a unique component of the
CRE model. In this case, the door
consists of the door frame and any
transparent area that represents the
‘‘moveable panel’’ that ‘‘facilitates
access to the refrigerated space.’’ This
would not include mullions, which are
fixed portions of the CRE model’s
envelope on which the doors are
mounted. DOE has specified how to
determine the applicability of
transparent equipment families to a
given model in section 1.2 of each
appendix.
In response to Zero Zone’s suggestion
that DOE consider the ENERGY STAR®
definitions for solid door cabinet, glass
door cabinet, and mixed solid/glass
door cabinet, DOE reviewed the
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
definitions in the ENERGY STAR
‘‘Version 2.1 Program Requirements for
Commercial Refrigerators and
Freezers’’ 10 (Version 2.1 Program
Requirements), as well as associated
stakeholder comments received during
the development of the ENERGY STAR
Version 2.1 Program Requirements in
developing the proposed definitions for
closed solid and closed transparent.11
The primary difference between the
ENERGY STAR classification scheme
and that proposed by DOE is the
treatment of CRE models with mixed
solid and transparent doors on at least
one side of the unit. In DOE’s proposal,
cases with mixed solid and transparent
doors would be treated as either solid or
transparent cases, based on the outer
surface area of the doors, whereas
ENERGY STAR treats this equipment in
a separate equipment category.
DOE believes the definitions proposed
in the October 2013 test procedure
NOPR are straightforward and would
unambiguously address equipment
categorization. 78 FR at 64318 (Oct. 28,
2013). In addition, setting the threshold
for transparent surface area of all outer
doors at greater than 25 percent makes
it unlikely that equipment with
substantial amounts of transparent area
will be categorized in the closed solid
equipment family. For example,
equipment that has one door that is halftransparent and half-solid would be
treated as ‘‘closed transparent’’ and
would have to meet the energy
conservation standard for the
appropriate equipment class based on
its volume or TDA. As a result, DOE
10 U.S. Environmental Protection Agency.
ENERGY STAR® Program Requirements for
Commercial Refrigerators and Freezers: Eligibility
Criteria; Version 2.1. Effective January 1, 2010. (Last
accessed August 15, 2013.) https://www.energystar.
gov/ia/partners/product_specs/program_reqs/
Commercial_Refrigerator_and_Freezer_Program_
Requirements.pdf?dae6-ef7c.
11 See Continental Refrigerator, Comments on
Specification for Commercial Refrigerators and
Freezers, Version 2.0 Draft 3. Dated January 7, 2009.
Available at: https://www.energystar.gov/ia/
partners/prod_development/revisions/downloads/
refrig/Continental_Comments.pdf?f45c-2369.
Beverage-Air Corporation, Beverage-Air Comments
re: ENERGY VERSION 2.0—DRAFT 3, Dated
January 8, 2009. Available at: https://www.
energystar.gov/ia/partners/prod_development/
revisions/downloads/refrig/Beverage-Air_
Comments.pdf?f45c-2369. Anonymous, Comments
on Draft 2. Dated September 15, 2008. Available at:
https://www.energystar.gov/ia/partners/prod_
development/revisions/downloads/refrig/
Anonymous_Comments.pdf?f45c-2369. True
Manufacturing, Comments on Draft 2. Dated
September 17, 2008. Available at: https://www.
energystar.gov/ia/partners/prod_development/
revisions/downloads/refrig/True_Comments.pdf
?f45c-2369. Traulsen, Comments on Draft 1. Dated
April 18, 2008. Available at: https://www.
energystar.gov/ia/partners/prod_development/
revisions/downloads/refrig/Traulsen_Comments.
pdf?f45c-2369.
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
mstockstill on DSK4VPTVN1PROD with RULES2
does not anticipate issues associated
with equipment with small transparent
areas that cannot meet the applicable
energy conservation standard. Also,
these definitions are consistent with the
equipment categorization methodology
DOE uses to establish standards for
covered equipment. As such, DOE
believes defining terms that are used
directly in the description and
determination of equipment classes for
commercial refrigeration equipment is
the most clear, unambiguous method for
defining and categorizing equipment as
closed transparent or closed solid, and
DOE does not see a need to establish a
unique equipment category for mixed
solid/transparent equipment.
c. Hybrid Equipment and Commercial
Refrigerator-Freezers
At 10 CFR 431.62, DOE defines a
commercial hybrid refrigerator, freezer,
or refrigerator-freezer as having two or
more chilled and/or frozen
compartments that are in two or more
different equipment families, contained
in one cabinet, and sold as a single unit.
In the October 2013 test procedure
NOPR, DOE proposed to replace the
definition of ‘‘commercial hybrid
refrigerator, freezer, and refrigeratorfreezer’’ with a definition of
‘‘commercial hybrid,’’ and introduce a
new definition of ‘‘commercial
refrigerator-freezer’’ to clarify DOE’s
definitions and equipment categories.
78 FR at 64303–64304, 64318 (Oct. 28,
2013).
In response to the definitions
proposed in the October 2013 test
procedure NOPR, DOE received
comments from interested parties
regarding DOE’s definition for
commercial hybrid and the applicability
of the definition of commercial hybrid
to certain equipment. Continental
commented that the proposed definition
of ‘‘commercial hybrid’’ should specify
that the ‘‘two compartments’’ are
separated by an insulated partition to
isolate them for different storage
applications, as this would limit
confusion with multiple section
cabinets, which may have non-insulated
partitions or ducting between them
purely for air distribution, shared
throughout the entire unit. (Continental,
No. 14 at p. 2)
True noted that DOE’s definition did
not explicitly state that dual
temperature units were separated by a
vertical partition, and therefore might
include solid-shelf units. (True, Public
Meeting Transcript, No. 7 at p. 71)
Similarly, National expressed confusion
over the application of the DOE rule in
cases where two sections of a unit were
at different temperatures, but potentially
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
use the same evaporator coil or share air
between the two spaces. (National,
Public Meeting Transcript, No. 7 at p.
75) National commented that some twodoor units are built with airflow down
the middle and panels with louvers to
distribute air. (National, Public Meeting
Transcript, No. 7 at p. 79)
Hussmann agreed with DOE’s
proposed definitions of commercial
hybrid and commercial refrigeratorfreezer, but requested clarification on
how to classify or handle a piece of
equipment that contains at least one
section or compartment that is not
covered by the DOE test procedure (e.g.,
salad bars and buffet tables).
(Hussmann, No. 11 at p. 2) Royston
noted that in many hybrid units such as
salad bars, it was unclear what
percentage of the unit would be
considered refrigerated. (Royston,
Public Meeting Transcript, No. 7 at p.
82)
In response to Continental’s
suggestion that DOE consider specifying
that the compartments in a commercial
hybrid refrigerator, freezer, or
refrigerator freezer be separated by an
insulated partition or be thermally
isolated from one another, DOE agrees
that the intent of the commercial hybrid
equipment provisions is to address
equipment with thermally distinct
compartments from different equipment
families (e.g., vertical closed transparent
and vertically closed solid). As such,
DOE is adopting language to specify that
commercial hybrid equipment is
equipment consisting of two or more
thermally separated refrigerated
compartments that are in two or more
different equipment families that is sold
as a single unit.
In regard to clarification on how to
classify or handle a piece of equipment
that contains at least one section or
compartment that is not covered by the
DOE test procedure (e.g., salad bars and
buffet tables), DOE clarifies that this
type of equipment is not hybrid
equipment because it does not consist of
two or more different equipment
families. Only the compartment(s) of the
piece of commercial refrigeration
equipment that is covered by one of
DOE’s existing equipment classes is
included in DOE’s equipment family
definitions. The compartment that is not
covered by DOE’s existing standards for
commercial refrigeration equipment is
not included in DOE’s equipment family
definitions and, thus, such a unit would
not meet the definition of commercial
hybrid. Using the example presented in
Hussmann’s comment, consider a
commercial refrigerator that contains
one compartment that falls into the
vertical closed solid equipment family
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
22289
and a thermally separate compartment
that offers accessible refrigerated bins
for the purposes of preparing
sandwiches or holding buffet items. As
presented in section III.A.1.a, sandwich
prep tables and buffet tables are not
currently regulated under DOE’s
existing energy conservation standards
or subject to DOE’s test procedure for
commercial refrigeration equipment. As
such, this CRE model would be covered
under DOE’s existing energy
conservation standards as a commercial
refrigerator in the vertical closed solid
equipment family based on the
refrigerated volume of only the
refrigerated compartment comprising
the vertical closed solid commercial
refrigerator. This CRE model would be
tested under the DOE test procedure for
commercial refrigeration equipment as a
commercial refrigerator, and the
compartment containing the sandwich
prep or buffet table bins would be
disabled and not included in the
determination of energy consumption
for that equipment. If the same
refrigeration system serves both
compartments and the refrigeration of
the sandwich/buffet compartment
cannot be disabled, manufacturers may
apply for a test procedure waiver for
such equipment if the measured energy
use would not be representative of the
commercial refrigerator, freezer, or
refrigerator-freezer portion of the CRE
basic model.
3. Relationship Among Rating
Temperature, Operating Temperature,
and Integrated Average Temperature
Currently, the table at 10 CFR
431.66(d)(1) describing the energy
conservation standards for equipment
other than hybrid equipment,
refrigerator-freezers, and wedge cases
refers to the ‘‘rating temperature’’ and
‘‘operating temperature’’ of equipment,
and the table describing the applicable
test procedure for covered equipment at
10 CFR 431.64(b)(3) refers to the term
‘‘integrated average temperature.’’ DOE
defines ‘‘integrated average
temperature’’ as ‘‘the average
temperature of all the test package
measurements taken during the test.’’ 10
CFR 431.62.
In the October 2013 test procedure
NOPR, DOE proposed explicit
definitions for ‘‘rating temperature’’ as
the IAT at which a model of commercial
refrigeration equipment should be
evaluated in accordance with the DOE
test procedure, and ‘‘operating
temperature’’ as the range of IATs at
which the unit of commercial
refrigeration equipment is capable of
operating. In addition, DOE noted that
while the operating temperature range
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
22290
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
of equipment is used to establish the
appropriate equipment class for CRE
basic models based on the standards
table at 10 CFR 431.66(d)(1), only the
definition of ‘‘ice-cream freezer’’
explicitly identifies the appropriate
operating range (i.e., at or below ¥5 °F).
10 CFR 431.62 Therefore, DOE also
proposed definitions of ‘‘commercial
refrigerator’’ and ‘‘commercial freezer’’
that reference the operating temperature
range of each category of equipment. 78
FR at 64303–64304, 64318 (Oct. 28,
2013).
In response to DOE’s proposed
definitions for commercial refrigerator,
commercial freezer, and commercial
refrigerator-freezer, Continental
commented that the use of the term
‘‘capable of’’ introduced confusion and
does not accurately reflect industry
practices. Continental offered the
example of a piece of equipment that is
designed and marketed as a refrigerator,
but includes an oversized refrigeration
system that may be necessary to hold
products at temperatures near 32 °F that
would allow the refrigerator to be
capable of operating below 32 °F in
some applications, although it is not
intended to be operated that way. As
such, Continental suggested that DOE
define the commercial refrigerator
operating range as ‘‘all refrigerated
compartments in the unit are designed,
marketed or intended for operating at or
above 32 °F.’’ (Continental, No. 14 at p.
2) Similarly, Hussmann suggested DOE
replace ‘‘capable of operating’’ with
‘‘designed, marketed, or intended to be
operated by the manufacturer.’’
(Hussmann, No. 11 at p. 2)
DOE acknowledges comments from
interested parties, but notes that DOE
prefers to have an objective method for
determining coverage of equipment
under DOE’s equipment classes. DOE
believes that relying on how a piece of
equipment is ‘‘designed, marketed, or
intended to be used’’ provides too much
flexibility for manufacturers to specify
how a CRE basic model is ‘‘intended to
be used,’’ without consideration of how
the equipment actually can be used. As
such, DOE maintains that, for selfcontained equipment and remote
equipment with thermostats, DOE will
establish the operating range of
equipment based on the operating
temperatures the commercial
refrigeration equipment is capable of
maintaining. DOE will determine the
operating range of covered equipment
based on the maximum and minimum
thermostat set points. However, DOE
acknowledges that, for equipment with
an operating temperature range that is
primarily in, for example, the
commercial refrigerator operating
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
temperature range (i.e., at or above
32 °F), but has a minimum operating
temperature in the commercial freezer
range slightly below 32 °F (e.g., 30 °F), it
may not be appropriate to require such
equipment to be certified as both a
commercial refrigerator and a
commercial freezer. DOE believes that
equipment should be categorized in the
equipment class most representative of
the operating temperature range of that
equipment. As such, DOE is adopting a
tolerance on the minimum and
maximum IAT that categorizes
equipment as a commercial refrigerator,
commercial freezer, or commercial ice
cream freezer. DOE believes a tolerance
of ±2 °F would allow sufficient
flexibility that equipment with an
operating temperature range that is
substantially representative of one
equipment class, but with a minimum
or maximum operating temperature that
extends slightly into the operating
temperature range of another equipment
class, is not required to be certified in
both equipment classes. This tolerance
is also consistent with the tolerance on
the rating temperatures for the relevant
equipment classes. Therefore, in this
final rule, DOE will establish in 10 CFR
431.66 operating temperature ranges of
greater than or equal to 32 °F (±2 °F) for
commercial refrigerators, less than 32 °F
(±2 °F) for commercial freezers, and less
than or equal to ¥5 °F (±2 °F) for ice
cream freezers.
DOE acknowledges that for remote
equipment the operating range of
equipment could be much broader, as it
is based on the operating parameters of
the compressor system much more than
the case design. Manufacturers may
design a case that could optimize
performance for operation as a freezer,
but customers would be able to adjust
the compressor operating characteristics
to operate the case at refrigerator
temperatures, even though it is not
intended to be used that way. As such,
in this test procedure final rule DOE
adopts additional language to clarify
that for remote condensing equipment,
the operating temperature range is based
on the range of IATs at which a piece
of commercial refrigeration equipment
is marketed, designed, or intended to be
used. DOE does not see the need to
establish such a definition for selfcontained equipment with thermostats
and will maintain the definition of
‘‘operating temperature’’ proposed in
the NOPR based on the IATs at which
a piece of commercial refrigeration
equipment is capable of operating.
Traulsen recommended changing all
referenced temperature thresholds from
32 °F to 25 °F, since some equipment,
including meat refrigerators, is intended
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
to be operated as low as 25 °F.
(Traulsen, No. 17 at p. 3)
In response to Traulsen’s
recommendation regarding establishing
equipment categories based on
operating ranges of greater than or equal
to 25 °F for commercial refrigerators,
below 25 °F for commercial freezers, and
a combination of the two for commercial
refrigerator-freezers, DOE believes that
32 °F is a more appropriate temperature
threshold for differentiating chilled
from frozen food storage equipment.
Equipment that can operate at 25 °F is
functionally a freezer, since food is
primarily composed of liquid water and
water freezes at 32 °F. In addition, an
operating temperature threshold of 32 °F
was determined in the 2009 CRE energy
conservation standards final rule and
has been in place historically for the
purposes of compliance with those
standards since January 1, 2012. 74 FR
1092, 1099–1100 (Jan. 9, 2009). DOE
notes that the equipment mentioned by
Traulsen, which operates both at or
above 32 °F and below 32 °F, would
qualify as both a commercial refrigerator
and a commercial freezer and would
have to be certified in both equipment
categories. To the extent that the
equipment was not able to reach the
rating temperature for commercial
freezers of 0 °F, the equipment would be
tested at its LAPT for certification as a
freezer.
In the October 2013 test procedure
NOPR, DOE recognized that some basic
models may have operating
characteristics that include an operating
temperature range that spans multiple
equipment classes, and proposed
language to clarify that equipment
meeting the definition of multiple
equipment classes when operated as
intended by the manufacturer would
have to be tested and certified as each
of these equipment classes to
demonstrate compliance with DOE’s
energy conservation standards. 78 FR at
64304 (Oct. 28, 2013).
Zero Zone and AHRI disagreed with
DOE’s proposal that the equipment
capable of operating in two or more
operating temperature ranges be tested
and certified as complying with both
equipment classes. Zero Zone and AHRI
suggested that these cases be tested and
certified at their lowest published
operating temperature, which would be
reflective of the highest energy use
mode. (Zero Zone, No. 18 at p. 2; AHRI,
No. 15 at p. 4) Zero Zone added that if
DOE requires equipment to be tested at
all the published operating temperature
ranges, more-complex controls may be
required to reduce energy so the
equipment can meet the energy
conservation standards for both
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
equipment categories, and suggested
that DOE consider the increased cost of
these controls compared to the benefits
to consumers. Zero Zone added that, in
general, remote freezers can be operated
inefficiently as a refrigerator by
customer settings on the remote
condensing unit, but added that it does
not condone such operation. As such,
Zero Zone suggested DOE use the term
‘‘marketed operating temperature’’ to
avoid having equipment potentially
tested at two different temperature
classes because it can be operated at two
or more temperature class operating
ranges even though it is not designed for
use in these operating temperature
ranges. (Zero Zone, No. 18 at p. 2)
In contrast, NEEA supported DOE’s
proposal that equipment intended to
operate in multiple equipment classes
be tested and certified in each
equipment class to demonstrate
compliance with DOE’s energy
conservation standards because NEEA
believed it will allow a level playing
field for manufacturers to produce
energy compliant refrigeration
equipment. (NEEA, No. 16 at p. 2)
DOE considered comments submitted
by interested parties regarding the
potential for commercial refrigeration
equipment classified into two
equipment categories. Zero Zone and
AHRI both suggested that equipment
instead be deemed compliant based on
testing and certification in the morestringent configuration or most energyconsuming mode. Zero Zone also
discussed the example of a dual
temperature unit that can operate as a
commercial refrigerator or a commercial
freezer. DOE notes that, while the
freezer configuration would represent
the most energy-consuming mode,
determining the more-stringent standard
level is less straightforward. Although
the freezer configuration may use more
energy, the energy conservation
standard level for the refrigerator
configuration may in fact be more
stringent. This would especially be true
if the operating range of the case was
such that the CRE model could not be
tested at the rating temperature of 0 °F
for freezers. For example, in the case of
a piece of commercial refrigeration
equipment that has an operating
temperature range of 10 to 50 °F, the
unit can operate as a refrigerator, at or
above 32 °F, or be converted to operate
as a freezer, but only down to 10 °F.
Thus, the unit cannot operate at the
rating temperature for freezers of 0 °F
and would be certified at the
equipment’s LAPT of 10 °F. However,
the equipment, when tested at the
LAPT, would still be subject to the same
energy conservation standard and, as
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
such, the freezer energy conservation
standard would be much easier to meet.
In addition, rating the equipment as a
freezer may or may not accurately
represent the use of the equipment in
the field. That is, dual temperature
equipment may spend considerable
operating hours as a refrigerator and less
significant operating hours as a freezer.
This may be the case in a commercial
kitchen, for example, where freezer
space is necessary at the beginning of
the week when new product arrives, but
is converted to refrigerator space over
the course of the week as food is
prepared and stored for more immediate
use. DOE does not find it tenable that
dual temperature equipment operating
inefficiently as a refrigerator most of the
time could be compliant with DOE’s
energy conservation standards due to its
certification as a commercial freezer
only.
DOE acknowledges Zero Zone’s
concern that equipment that can operate
as a refrigerator or a freezer may require
more-complex controls to meet DOE’s
energy conservation standards as both a
refrigerator and a freezer. However,
based on the difficulty in determining
the ‘‘more-stringent’’ standard and the
potential for certification of otherwise
non-compliant equipment, DOE believes
that this incremental burden is justified
to ensure compliance with DOE’s energy
conservation standards. Further, DOE
notes that equipment that can operate as
both a refrigerator and a freezer
competes directly with equipment in
both categories and, as such, must be
certified to meet the energy
conservation standard for both
equipment categories to provide a fair
and level playing field when selling this
equipment in the market.
In this test procedure final rule, DOE
continues to require that self-contained
equipment or remote condensing
equipment with thermostats capable of
operating at IATs that span multiple
equipment categories be certified and
comply with DOE’s regulations for each
applicable equipment category.
Similarly, DOE adopts requirements for
remote condensing equipment without a
thermostat that specify that if a given
basic model of CRE is marketed,
designed, or intended to operate at IATs
spanning multiple equipment
categories, the CRE basic model must be
certified and comply with the relevant
energy conservation standards for all
applicable equipment categories.
4. Proper Configuration and Use of
Components or Features in the DOE
Test Procedure
In response to several inquiries from
interested parties regarding the proper
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
22291
configuration and use of certain
components or features specified in the
DOE test procedure, DOE proposed
specific provisions in the October 2013
test procedure NOPR for the treatment
of energy management systems and case
lighting when conducting the DOE test
procedure. 78 FR at 64304–64306 (Oct.
28, 2013). In addition, DOE also
addressed and clarified the appropriate
temperatures of test packages when
loaded into the test unit. 78 FR at 64306
(Oct. 28, 2013). These proposals,
comments received by interested
parties, and DOE’s responses are
summarized in the subsequent sections.
a. Energy Management Systems
The DOE test procedure specifies that
all devices that would normally be used
in the field must be installed and
operated in the same manner during the
test unless such installation and
operation is inconsistent with any
requirement of the test procedure.12
Such devices include energy
management systems. In the October
2013 test procedure NOPR, DOE
presented its interpretation of energy
management systems as electronic
devices that control specific systems in
commercial refrigeration equipment to
save energy, for example, automatic
controls that are capable of turning off
cabinet lights on a predetermined
schedule or in response to an external
variable, increasing the temperature
setting of the thermostat (in refrigerators
that store non-perishable items) during
non-merchandizing hours, or activating
and deactivating anti-sweat heaters, pan
heaters, or defrost heaters. 78 FR at
64304 (Oct. 28, 2013).
In the October 2013 test procedure
NOPR, DOE further proposed that, if
normal field installation or operation of
any device would be inconsistent with
any test procedure requirement, then
the specific function of that device that
causes inconsistency with the DOE test
procedure provisions must be disabled
for the duration of the test. In addition,
if the device is designed for multiple
functions, only those functions of the
device that cause inconsistency with the
DOE test procedure requirements must
be disabled. 78 FR at 64321 (Oct. 28,
2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of energy
management systems during the DOE
test procedure and, as such, is adopting
the proposal presented in the October
12 ASHRAE 72–2005, section 6.1.1,
‘‘Accessories,’’ as incorporated by reference into the
DOE test procedure at 10 CFR 431.64.
E:\FR\FM\21APR2.SGM
21APR2
22292
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
mstockstill on DSK4VPTVN1PROD with RULES2
2013 test procedure NOPR with no
modifications.
b. Lighting
The DOE test procedure specifies that
all devices that would normally be used
in the field must be installed and
operated in the same manner during the
test. 10 CFR 431.64. Specifically, due to
language and provisions in ARI 1200–
2006 (as incorporated by reference in
the 2006 test procedure final rule) and
AHRI 1200–2010 (as incorporated by
reference in the 2012 test procedure
final rule and this test procedure
update) regarding case lighting, DOE
believes that the energy consumption
associated with lights installed on a
model of commercial refrigeration
equipment are intended to be captured
during testing. In addition, the DOE test
procedure requires that all standard
components, such as shelves, end
enclosures, lights, anti-condensate
heaters, racks, and similar items that
would normally be used during
shopping or working periods, shall be
installed and used as recommended by
the manufacturer, which DOE interprets
to mean that if lighting is installed on
the case, the lighting should be operated
as intended to be used in the field.
However, due to the variety of types of
lighting controls and schemes available
on the market, the existing provisions
for ‘‘accessories’’ may prove insufficient
to yield consistent results during
testing. Therefore, in the 2012 test
procedure final rule, DOE established
specific periods in the test during which
these variable lights may be turned off
or dimmed to account for energy savings
due to installed occupancy sensors or
scheduled lighting controls. 77 FR at
10319–10320 (Feb. 21, 2012).
In the October 2013 test procedure
NOPR, to clarify the treatment of
lighting under DOE’s test procedure,
DOE proposed to specify in Appendix A
to Subpart C that all lighting must be
energized to the maximum illumination
level for the duration of testing for
commercial refrigeration equipment
except for closed solid models of
commercial refrigeration equipment that
include automatic controls that disable
case lighting when the door is closed,
the use of which is specified by the
manufacturer instructions. DOE also
proposed to specify in Appendix B to
Subpart C, which will be required for
equipment testing on or after the
compliance date of any amended energy
conservation standards, that case
lighting shall be energized to its
maximum illumination level except for
when a model of commercial
refrigeration equipment is equipped
with lighting occupancy sensors and/or
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
scheduled controls, or when the a
model is outfitted with other
permanently installed, automatic energy
management systems that control case
lighting. 78 FR at 64305–64306 (Oct. 28,
2013).
Zero Zone commented that they agree
with DOE’s proposed exception for solid
door models that utilize an automatic
control to disable case lighting when the
door is closed. However, Zero Zone did
not believe DOE’s treatment of manual
case lighting adjustment, such as light
switches, is consistent with its
treatment of manually deployable night
curtains for open cases. (Zero Zone, No.
18 at p. 3) In addition, Zero Zone was
concerned that an open case model with
several lighting options would be tested
with all lights installed for the test
procedure, but the customer may choose
to have a select amount of the lights on
in the operation of the installed case.
Zero Zone inquired if each lighting
scheme in the open case model would
be considered a base model and tested
separately. (Zero Zone, Public Meeting
Transcript, No. 7 at pp. 153–154) True
commented that certain occupancy
sensors with a learning curve built into
them would not be able to be accurately
tested since there is no activity near the
unit during testing. True added that
they can be programmed to override the
sensor if needed. (True, Public Meeting
Transcript, No. 7 at pp. 155–156)
DOE acknowledges Zero Zone’s
comment regarding the consistency of
the DOE test procedure as it relates to
the treatment of manual lighting
controls and manual night curtains.
DOE addressed this issue in the 2012
test procedure final rule, in which DOE
stated that night curtains represent an
incremental cost and explicit energy
management feature that must be
uniquely specified on commercial
refrigeration equipment, making it
unlikely that customers would purchase
a case with night curtains and not
employ them. By contrast, manual light
switches may be installed for a variety
of energy- or utility-related reasons and
typically come standard on a baseline
unit of commercial refrigeration
equipment. As such, DOE finds it less
likely that customers will employ
manual light switches to adjust case
lighting during unoccupied periods
with any regularity. 77 FR at 10299–
10300 (Feb. 21, 2012). DOE continues to
maintain that the incremental cost of
night curtains and dedicated use as an
energy-efficiency feature make them
unique from manual light switches and
justify different treatment in the DOE
test procedure.
In response to Zero Zone’s comment
regarding the variety of lighting options
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
available for installation on a given
model of commercial refrigeration
equipment, DOE notes that these
different lighting schemes will have an
impact on the measured daily energy
consumption of the case. As such, each
light option could be treated as an
individual basic model and be tested
and certified as such. However, to the
extent that manufacturers do not wish to
account for the reduced energy
consumption associated with reduced
lighting configurations, all lighting
configurations may be grouped into a
CRE basic model. In this case, the CRE
basic model would be tested and
certified based on the lighting
configuration with the maximum
lighting energy usage and all individual
models certified under that basic model
would receive that rating.
In response to True’s comment
regarding lighting controls that are
triggered by occupancy sensors, these
lighting controls should currently be
tested with all the controlled lighting
turned on to the maximum illumination
level and the occupancy sensor disabled
to determine whether the model
complies with existing energy
conservation standards, as reflected in
Appendix A. Beginning on the
compliance date of any amended energy
conservation standards for commercial
refrigeration equipment, manufacturers
shall use the prescribed test provisions
for cases with lighting occupancy
sensors included in Appendix B.
c. Test Package Temperatures
The ASHRAE 72–2005 method of test,
as referenced by ARI 1200–2006 and
AHRI 1200–2010, and thus incorporated
by the DOE test procedure at 10 CFR
431.64, provides specific instruction at
section 6.2 as to the loading of test
simulators and filler packages. ASHRAE
72–2005 also requires temperature
stabilization before the formal test
period begins, as detailed in section 7.4.
After steady-state operation is reached,
the unit must then operate for another
period of 12 hours without any
adjustment to the controls before it is
deemed to be stabilized and the testing
can begin. These established
stabilization requirements are designed
to ensure that the product simulators
and test packages are cooled to the test
temperature prior to initiation of the test
period and data collection, and the unit
of commercial refrigeration equipment
under test is not operating in a pulldown application during any part of the
DOE test procedure.
In response to inquiries received by
interested parties, DOE presented
clarification of these stabilization
requirements in the October 2013 test
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
procedure NOPR, but did not find that
the test procedure required more
explicit clarification. 78 FR at 64306
(Oct. 28, 2013). DOE did not receive any
comments from interested parties on its
proposal regarding treatment of test
package temperatures during the DOE
test procedure and, as such, is adopting
the proposal presented in the October
2013 test procedure NOPR with no
modifications.
5. Treatment of Other Specific
Equipment Features and Accessories
During Testing
During the negotiated rulemaking for
certification of commercial heating,
ventilation, air conditioning,
refrigeration, and water heating
equipment, stakeholders raised a
number of issues regarding the
treatment during the DOE test procedure
of specific features, components, and
accessories that may be in place on
certain basic models of commercial
refrigeration equipment. In the October
2013 test procedure NOPR, DOE
presented proposals that resulted from
the negotiations regarding the treatment
of specific features, components, and
accessories. 78 FR at 64306–64308 (Oct.
28, 2013). The specific proposals and
the resultant amendments adopted in
this final rule are discussed in the
following sections.
mstockstill on DSK4VPTVN1PROD with RULES2
a. Customer Display Signs/Lights
Manufacturers stated that some
customers, when ordering commercial
refrigeration equipment, may wish to
add additional exterior signage, outside
of the body of the refrigerated cabinet,
to certain units of a given model to
advertise the product inside. This
lighting and signage is optional and is
not integral to the cabinet. Further, this
auxiliary signage does not illuminate
product inside the body of the cabinet.
During the negotiations, stakeholders
inquired regarding how this lighting or
signage should be treated during testing.
In the October 2013 test procedure
NOPR, DOE proposed that under the
DOE test procedure, all lighting that is
integral to the refrigerated cabinet or
illuminates the product contained
within must be operational during the
test, and DOE proposed to add clarifying
language in the regulatory text to
address customer display signs/lights.
Under DOE’s proposal, supplemental
lighting that exists solely for the
purposes of advertising or drawing
attention to the case and is not integral
to the case would not be operated
during testing under the DOE test
procedure. 78 FR at 64306 (Oct. 28,
2013).
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of customer display
signs/lights during the DOE test
procedure and, as such, is adopting the
proposal presented in the October 2013
test procedure NOPR with no
modifications.
b. Condensate Pan Heaters and Pumps
Commercial refrigeration equipment
captures water from the air entering the
cabinet during operation by causing the
water to condense and then freeze on
the evaporator coil of the equipment.
During a defrost cycle, this frost is
melted and the meltwater produced
must be removed from the unit. In many
types of equipment, this meltwater is
collected in a pan beneath the unit.
Some models of commercial
refrigeration equipment come equipped
with electric resistance heaters that
evaporate this water out of the pan and
into the ambient air. Other models may
come equipped with pumps that send
meltwater to an external drain.
In the October 2013 test procedure
NOPR, DOE proposed that, during the
DOE test procedure, these electric
resistance heaters and condensate
pumps must be installed and
operational during the entire test (as per
section 6.1.1, ‘‘Accessories,’’ of
ASHRAE 72–2005) and clarified that the
‘‘entire test’’ includes stabilization
(including pull-down), steady-state, and
performance testing periods. Prior to the
start of the stabilization period, as
defined by ASHRAE 72–2005, the
condensate pan should be dry, and
during the entire test following the start
of the stabilization period, any
condensate moisture generated should
be allowed to accumulate in the pan as
it would during normal operation, with
no manual removal of water at any time
during the entire test. DOE proposed
that if a manufacturer offers a given
basic model for sale with an available
condensate pan heater or pump, the
manufacturer must make
representations of the performance of
the basic model as tested with the
feature in place, and DOE proposed
clarifying language in the regulatory text
to address condensate pan heaters and
pumps. 78 FR at 64306 (Oct. 28, 2013).
In response to DOE’s proposal in the
October 2013 test procedure NOPR,
AHRI, Hussmann, and Zero Zone
commented that condensate pan heaters
should not be required to be tested for
remote equipment, since they are not
accounted for in the energy
conservation standard engineering
analysis. (AHRI, No. 15 at p. 3;
Hussmann, No. 11 at p. 4; Zero Zone,
No. 18 at p. 2) AHRI commented that
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
22293
condensate pan heaters or pumps are
usually added in the field to fulfill
specific needs of commercial customers
and are typically installed on less than
5 percent of the total remote cases sold
within the U.S. AHRI further
commented that it is unreasonable to
require manufacturers to test potentially
all remote equipment with condensate
pan heaters to certify its basic models to
DOE, if those models may be sold with
condensate pan heaters in some specific
applications. (AHRI, No. 15 at p. 3)
Hussmann corroborated that remote
equipment shipped with condensate
pan heaters represents less than 1
percent of case volume for Hussmann
and stated its belief that the discussions
during the negotiated rulemaking
(Docket No. EERE–2013–BT–NOC–
0023) were primarily surrounding selfcontained equipment. (Hussmann, No.
11 at p. 4)
Zero Zone added that if case
manufacturers are deterred from
supplying condensate pan heaters, end
users will work around this by buying
condensate pans from third parties that
typically are not Underwriters
Laboratories (UL) Recognized or UL
Listed and do not come with protective
covers. (Zero Zone, No. 18 at pp. 2–3)
DOE acknowledges the opinions of
interested parties and agrees that
condensate pan heaters and pumps are
not common on remote equipment. As
such, DOE agrees that determination of
daily energy consumption for remote
cases with condensate pan heaters may
not be the most representative
configuration. Thus, DOE is adopting
language in this final rule applying the
requirements for testing with
condensate pan heaters and pumps in
place for self-contained equipment only.
DOE notes that whether or not
condensate pan heaters were included
in DOE’s engineering analysis and
energy modeling to support standard
development is not dispositive as to
what features are included and
accounted for when testing a given basic
model of commercial refrigeration
equipment. DOE models a
representative model for each
equipment class, but manufacturers may
deviate from that assumed
representative model in any number of
ways, including the addition of features
and accessories that improve the utility
of cases in specific applications, such as
condensate pan heaters and pumps.
c. Anti-Sweat Door Heaters
Many transparent-door cases come
equipped with anti-sweat electric
resistance heaters that serve to
evaporate any water that condenses on
the transparent surface of the door
E:\FR\FM\21APR2.SGM
21APR2
22294
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
during operation. In some instances,
manufacturers may equip their cases
with higher-powered anti-sweat heaters
in anticipation of potential adverse
operating conditions.
In the October 2013 test procedure
NOPR, DOE proposed that anti-sweat
heaters should be operational during
testing under the DOE test procedure
and proposed adding clarifying
language in the regulatory text to
address anti-sweat door heaters. Models
with a user-selectable setting must be
tested with the anti-sweat heaters
turned on and set to the maximum
usage position and models featuring an
automatic, non-user adjustable
controller that turns on or off based on
environmental conditions must be
tested with the controller operating in
the automatic state. Additionally, DOE
proposed that, if a unit is not shipped
with a controller from the point of
manufacture, and is intended to be used
with a controller, the manufacturer must
make representations of the basic model
based on the rated performance of that
basic model as tested when equipped
with a controller intended by the
manufacturer for use with the unit. 78
FR at 64306–64307 (Oct. 28, 2013).
NEEA stated that it supports DOE’s
proposal that anti-sweat heaters be in
operation during testing unless controls
are shipped with the unit and can be
turned off by these controls during
testing. (NEEA, No. 16 at pp. 2–3) DOE
did not receive any negative comments
from interested parties on its proposal
regarding treatment anti-sweat door
heater in the DOE test procedure and, as
such, is adopting the proposal presented
in the October 2013 test procedure
NOPR with no modifications.
mstockstill on DSK4VPTVN1PROD with RULES2
d. Ultraviolet Lights
Some manufacturers equip certain
models of commercial refrigeration
equipment with ultraviolet lights, which
can be operated by end users to
neutralize pathogens and ensure case
cleanliness. Manufacturers inquired as
to how these will be addressed by the
DOE test procedure. In the October 2013
test procedure NOPR, DOE proposed
that ultraviolet lights should not be
turned on during the test procedure and
proposed adding regulatory text to
clarify this position. 78 FR at 64307
(Oct. 28, 2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of ultraviolet lights
during the DOE test procedure and, as
such, is adopting the proposal presented
in the October 2013 test procedure
NOPR with no modifications.
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
e. Illuminated Temperature Displays
and Alarms
Manufacturers may equip some
commercial refrigeration equipment
models with illuminated displays that
provide visual information to the
equipment operator regarding, for
example, the temperature inside the
refrigerated case or if the case
temperature falls outside of a specified
range. DOE understands these items to
be features integral to the design of the
given model and proposed that they
should be enabled during the test as
they would be during normal field
operation. In the October 2013 test
procedure NOPR, DOE proposed to add
clarifying language in the regulatory text
to address illuminated temperature
displays and alarms. 78 FR at 64307
(Oct. 28, 2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of illuminated
temperature displays and alarms during
the DOE test procedure and, as such, is
adopting the proposal presented in the
October 2013 test procedure NOPR with
no modifications.
f. Condenser Filters
Manufacturers may offer models
equipped with non-permanent filters
over a model’s condenser coil to prevent
particulates such as flour from blocking
the condenser coil and reducing airflow.
In the October 2013 test procedure
NOPR, DOE proposed that these filters
should be removed during the DOE test
procedure and proposed to add
clarifying language as part of the
regulatory text. 78 FR at 64307 (Oct. 28,
2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of condensate filters
during the DOE test procedure and, as
such, is adopting the proposal presented
in the October 2013 test procedure
NOPR with no modifications.
g. Refrigeration System Security Covers
Manufacturers may offer for sale with
a basic model an option to include
straps or other devices to secure the
condensing unit and prevent theft or
tampering. In the October 2013 test
procedure NOPR, DOE proposed that
these security devices should be
removed during testing under the DOE
test procedure and proposed to add
clarifying language as part of the
regulatory text to clarify this provision.
78 FR 64307 (Oct. 28, 2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of refrigeration
system security covers during the DOE
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
test procedure and, as such, is adopting
the proposal presented in the October
2013 test procedure NOPR with no
modifications.
h. Night Curtains and Covers
Night curtains and night covers are
defined at 10 CFR 431.62 as a device
that is deployed temporarily to decrease
air exchange and heat transfer between
the refrigerated case and the
surrounding environment. In the
October 2013 test procedure NOPR,
DOE stated that the proper treatment of
these components during the DOE test
procedure is discussed in the current
text of the DOE test procedure, 10 CFR
431.64, as amended by the 2012 DOE
test procedure final rule. DOE also
added these provisions at section 1.2.10
in Appendix B and proposed adding
language to clarify that night curtains
may not be used when testing under
Appendix A. 78 FR at 64307 (Oct. 28,
2013).
DOE did not receive any comments
from interested parties regarding
treatment of night curtains and covers
during the DOE test procedure and, as
such, is adopting the proposal presented
in the October 2013 test procedure
NOPR with no modifications.
i. Grill Options
Manufacturers may offer for sale with
a basic model optional grills that are
used to direct airflow in unique
applications, such as when a unit is
mounted close to a rear wall and the
airflow needs to be directed upwards. In
the October 2013 test procedure NOPR,
DOE proposed that, if present, nonstandard grills should be removed
during testing under the DOE test
procedure and proposed to add
clarifying language as part of the
regulatory text. 78 FR at 64307 (Oct. 28,
2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of grill options
during the DOE test procedure and, as
such, is adopting the proposal presented
in the October 2013 test procedure
NOPR with no modifications.
j. Coated Coils
Coated coils, generally specified for
use in units that will be subjected to
environments in which acids or
oxidizers are present, are treated with
an additional coating (such as a layer of
epoxy or polymer) as a barrier to protect
the bare metal of the coil from
deterioration through environmental
contact. In the October 2013 test
procedure NOPR, DOE presented its
belief that the existing DOE test
procedure accurately accounts for the
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
performance of all types of coils,
including those with coatings, and that
no additional accommodations or
clarifications are needed in the test
procedure. Commercial refrigeration
equipment with coated coils shall be
tested in accordance with the DOE test
procedure, as specified at appendices A
and B to subpart C of 10 CFR part 431.
78 FR at 64307 (Oct. 28, 2013).
DOE did not receive any comments
from interested parties regarding
treatment of coated coils during the
DOE test procedure and, as such, is
adopting the proposal presented in the
October 2013 test procedure NOPR with
no modifications.
mstockstill on DSK4VPTVN1PROD with RULES2
k. Internal Secondary Coolant Circuits
The use of internal, secondary,
working fluid that is cooled by a remote
condensing unit is a proprietary design
that purportedly allows for greater
control of unit temperature, and may
present other attributes desirable to a
customer. In the October 2013 test
procedure NOPR, DOE stated that it
found no evidence indicating that this
design could not be tested using the
DOE test procedure as written, as the
operation of equipment with internal
secondary coolant circuits would be
effectively the same as that of a standard
remote condensing case from the
perspective of the test procedure. 78 FR
at 64307 (Oct. 28, 2013).
DOE did not receive any comments
from interested parties regarding
treatment of internal secondary coolant
circuits during the DOE test procedure
and, as such, is adopting the proposal
presented in the October 2013 test
procedure NOPR with no modifications.
l. Wedge Cases
Wedge cases are models of
commercial refrigeration equipment that
fit between two other cases to fill a gap
(such as in a corner) in a continuous
case lineup. They may require air
spillover from adjacent cases to meet the
manufacturer’s design temperatures.
During the negotiation proceedings,
manufacturers inquired as to how
wedge cases should be treated under the
DOE test procedure.
DOE considered the coverage and
testing of wedge cases in the 2009
energy conservation standards final
rule. 74 FR 1092, 1102–1103 (Dec. 9,
2009). Based on that assessment, DOE
understands that wedge cases meet the
definition of commercial refrigeration
equipment and fall into existing CRE
equipment classes. In the October 2013
test procedure NOPR, DOE stated that it
is unaware of any technical attributes
that prevent wedge cases from being
tested using the DOE test procedure, or
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
that the DOE test procedure is not
representative of the energy use of a
given basic model of wedge case. 78 FR
at 64307 (Oct. 28, 2013).
DOE did not receive any comments
from interested parties regarding
treatment of wedge cases during the
DOE test procedure and, as such, is
adopting the proposal presented in the
October 2013 test procedure NOPR with
no modifications.
m. Misting or Humidification Systems
Manufacturers may offer for sale with
a basic model optional misting or
humidification systems, which dispense
a water mist used to maintain the
optimal quality of products. These are
commonly used with cases containing,
for example, fresh produce, meat, or
seafood. In the October 2013 test
procedure NOPR, DOE proposed that, if
present, these systems should be
inactive during testing under the DOE
test procedure and proposed to add
clarifying language as part of the
regulatory text. 78 FR at 64307–64308
(Oct. 28, 2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of misting or
humidification systems during the DOE
test procedure and, as such, is adopting
the proposal presented in the October
2013 test procedure NOPR with no
modifications.
n. Air Purifiers
Manufacturers may offer for sale
purifying systems to remove
contaminants from air recirculated
within the interior of a refrigerated case.
In the October 2013 test procedure
NOPR, DOE proposed that air purifiers
should be inactive during testing under
the DOE test procedure and proposed to
add clarifying language as part of the
regulatory text. 78 FR at 64308 (Oct. 28,
2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of air purifiers
during the DOE test procedure and, as
such, is adopting the proposal presented
in the October 2013 test procedure
NOPR with no modifications.
o. General Purpose Outlets
Some commercial refrigeration
equipment may be offered for sale with
integrated general purpose electrical
outlets, which may be used to power
additional equipment such as scales or
slicers. In the October 2013 test
procedure NOPR, DOE proposed that,
during testing under the DOE test
procedure, no external load should be
connected to the general purpose outlets
contained within a unit and proposed to
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
22295
add clarifying language as part of the
regulatory text. 78 FR at 64308 (Oct. 28,
2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of general purpose
outlets during the DOE test procedure
and, as such, is adopting the proposal
presented in the October 2013 test
procedure NOPR with no modifications.
p. Crankcase Heaters
Some models of self-contained
commercial refrigeration equipment
feature electric resistance heaters
designed to keep the compressor warm
in order to maintain the refrigerant
contained within at optimal conditions
when the unit is operating at low
ambient temperatures. In the October
2013 test procedure NOPR, DOE
proposed that, if present, crankcase
heaters should be operational during the
test. Under this proposal, if a control
system, such as a thermostat or
electronic controller, is used to
modulate the operation of the crankcase
heater, it should be used as intended per
the manufacturer’s instructions. DOE
proposed to add clarifying language
regarding testing units with crankcase
heaters. 78 FR at 64308 (Oct. 28, 2013).
DOE did not receive any comments
from interested parties on its proposal
regarding treatment of crankcase heaters
during the DOE test procedure and, as
such, is adopting the proposal presented
in the October 2013 test procedure
NOPR with no modifications.
q. Interior/Exterior Liners
Manufacturers may offer for sale a
variety of different interior or exterior
liner materials with a given CRE basic
model. These liners, by virtue of
differences in thickness, composition,
and other physical attributes, could
change the insulative properties of the
case walls and thus alter the energy
consumption of the case. The test
procedure estimates the heat loss from
the refrigerated space to the
surroundings by measuring the amount
of energy needed to maintain the
refrigerated space at the given rating
temperature. In the October 2013 test
procedure NOPR, DOE presented its
belief that the DOE test procedure
adequately accounts for variability in
the energy consumption of models with
different liner types just as it accounts
for the energy performance of models
with varying levels of insulation.
Therefore, DOE did not propose any
additional measures to accommodate
these equipment features. 78 FR at
64308 (Oct. 28, 2013).
DOE did not receive any comments
from interested parties on its proposal
E:\FR\FM\21APR2.SGM
21APR2
22296
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
regarding treatment of interior/exterior
liners during the DOE test procedure
and, as such, is adopting the proposal
presented in the October 2013 test
procedure NOPR with no modifications.
mstockstill on DSK4VPTVN1PROD with RULES2
r. Crankcase Pressure Regulators
During the 2013 Working Group
meetings, stakeholders mentioned that
they sometimes equip the compressors
of self-contained commercial
refrigeration units with devices called
crankcase pressure regulators. The
function of these devices is to maintain
optimal gas pressure within the
compressor crankcase in instances
where the voltage input to the
compressor may not be uniform. This
often is the case, for example, in rural
locations where the transmission system
may experience interruptions or
fluctuations resulting in line voltage
drops. Working Group members agreed
unanimously that manufacturers should
offer an identical model without this
feature for the purposes of testing. DOE
plans to address this through guidance.
s. Other Comments Received From
Interested Parties
In response to the October 2013 test
procedure NOPR, DOE received several
additional comments pertaining to its
treatment of accessories generally. Zero
Zone agreed with DOE’s
accommodations of some specific
accessories and features proposed in the
October 2013 test procedure NOPR.
However, Zero Zone questioned why
DOE did not make allowances for
customers with high ambient humidities
and allow the use of higher anti-sweat
heat for those applications. Zero Zone
recommended that, to be consistent,
DOE should require testing with the
options it plans to exclude in this
rulemaking, and if the equipment can’t
pass the energy standard with these
options installed, customers need to
modify their stores to avoid the need for
the equipment modifications. (Zero
Zone, No. 18 at p. 3)
The government of the People’s
Republic of China (China)
recommended that all non-core energyconsuming accessories, such as lighting
associated with short-term opening and
closing of the refrigerator door,
networking and standby, or operation of
the deodorizing system, should be left
out and not included in the
measurement of daily energy
consumption. (China, No. 10 at p. 2) In
addition, China recommended that, if a
manufacturer included in their product
literature information that the operation
of some functions was auxiliary to the
effective operation of the refrigeration
equipment, their energy consumption
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
would account for a small proportion of
total energy consumption and could be
excluded from the calculation of total or
combined daily energy consumption.
(China, No. 10 at p. 4)
In response to Zero Zone’s comment
regarding accounting for the use of antisweat heaters at high humidities in the
DOE test procedure, DOE notes that its
test procedure is meant to represent an
average cycle of use. The ambient
temperatures required in the DOE test
procedure are 75 °F and 45 percent
relative humidity. These ambient
conditions apply to all equipment and
are meant to be representative of the
typical installation conditions for most
commercial refrigeration equipment.
DOE does not believe that the additional
complexity and burden associated with
testing at additional or different ambient
temperature conditions for some
equipment is justified to capture
additional use of anti-sweat heaters.
DOE notes that, as presented in section
III.A.5.c, this final rule establishes
provisions that anti-sweat door heaters
that do not have automatic controls
should be energized when testing in
accordance with the DOE test procedure
and that energy use due to anti-sweat
door heaters that have automatic
controls will be captured based on the
control algorithm associated with the
automatic control scheme.
In response to China’s comment
regarding the treatment of non-core or
auxiliary accessories, DOE believes that,
to a large extent, the provisions adopted
in this section address the appropriate
treatment of specific non-core and
auxiliary accessories. DOE notes that, to
ensure consistent and repeatable testing,
it is beneficial to adopt specific test
provisions for the treatment of specific
accessories. The proposals adopted in
this test procedure final rule address
specific accessories agreed upon as a
result of negotiations between DOE and
interested parties. DOE does not believe
adopting more-general provisions for
the treatment of ‘‘non-core’’ accessories,
as suggested by China, is necessary. In
addition, DOE believes such ambiguous
provisions may result in
misinterpretation and lack of
consistency in implementation of the
test procedure. Therefore, DOE is not
adopting provisions for testing of
accessories other than those proposed in
the October 2013 test procedure NOPR.
78 FR at 64306–08 (Oct. 28, 2013).
6. Rounding of Test Results and
Certified Ratings
The current DOE test procedure,
which incorporates by reference
provisions from ARI 1200–2006 and
AHRI 1200–2010, requires that the
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
calculated daily energy consumption
(CDEC), for remote condensing
equipment, and the total daily energy
consumption (TDEC), for self-contained
refrigeration equipment, be expressed in
terms of kilowatt-hours (kWh) per day
and must be stated in increments of 0.01
kWh per day. This is consistent with the
number of significant figures expressed
in the energy conservation standards
listed at 10 CFR 431.66.
DOE’s requirements for calculating
test results and certified ratings for
covered commercial refrigeration
equipment are found at 10 CFR 431.64
and 10 CFR 429.42, respectively. The
DOE test procedure currently requires
that results for CDEC or TDEC resulting
from testing a single unit be rounded to
0.01 kWh per day. In the case where the
reported value is derived from testing, at
least two or more units should be tested
pursuant to 429.42 and the appropriate
sampling statistics must be applied in
order to develop the represented value.
DOE is adopting in this final rule
provisions to clarify that the represented
value should also be rounded to the
nearest 0.01 kWh per day after
application of the sampling statistics.
For commercial refrigeration equipment
rated using an AEDM, the certified
rating must be derived pursuant to
429.70 and rounded to 0.01 kWh per
day.
In the October 2013 test procedure
NOPR, DOE proposed to clarify 10 CFR
431.64 by specifying that all
calculations in the DOE test procedure
must be carried out using raw, measured
values, and the results from the testing
of a single unit of a given basic model
should be expressed in 0.01 kWh per
day. DOE also proposed to update the
language at 10 CFR 429.42 to reflect the
same rounding requirements, namely
that certified ratings be expressed in
0.01 kWh per day increments. 78 FR at
64308 (Oct. 28, 2013).
In response to this proposal, Traulsen
suggested that, in lieu of leaving an
ambiguous rounding factor that may
result in inconsistencies between
manufacturers or reporting entities, DOE
require all calculations to be carried out
to the third decimal point and rounding
to the second decimal point for the
purposes of certification and
compliance with DOE’s energy
conservation standards. (Traulsen, No.
17 at p. 3) Southern Store Fixtures
commented that the rounding of test
results and the raw data, per ASHRAE
Standard 72, is carried to one decimal
point and should be consistent with this
test procedure. (Southern Store Fixtures,
Public Meeting Transcript, No. 7 at p.
165)
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
mstockstill on DSK4VPTVN1PROD with RULES2
In response to Southern Store
Fixtures’ comment regarding values in
ASHRAE 72–2005 that are carried to the
first decimal point, DOE notes that
pressure and temperature measurements
are specified to the first decimal point
and reporting these values to the third
decimal point may be inappropriate.
However, these values are not used
directly in the calculation of TDEC or
CDEC, and the number of significant
digits past the decimal is not relevant.
For these quantities, the number of
significant digits to be carried through
calculations is dictated by the number
of significant digits in the value as a
whole, and at least three significant
digits are expected for all these
quantities.
In this final rule, DOE is not
modifying the proposal presented in the
October 2013 test procedure NOPR, and
is adopting in this test procedure final
rule language that all calculations in the
DOE test procedure must be carried out
using raw, measured values and the
results from the testing of a single unit
of a given basic model should be
expressed in 0.01 kWh per day.
7. Testing at the Lowest Application
Product Temperature
In the 2012 test procedure final rule,
DOE establishes provisions for testing
equipment that is not capable of
achieving the prescribed rating
temperature for its respective equipment
class: 38 °F (±2 °F) for commercial
refrigerators, 0 °F (±2 °F) for commercial
freezers, and ¥15 °F (±2 °F) for icecream freezers. 77 FR at 10320 (Feb. 21,
2012). This equipment includes, for
example, floral cases and ice storage
cases, which do not have operating
temperatures that are low enough to
meet their respective rating temperature
requirements. The 2012 test procedure
amendments specify that such
equipment must be tested at its LAPT,
instead of the specified rating
temperature for its given equipment
class. 77 FR at 10320 (Feb. 21, 2012).
DOE regulations at 10 CFR 431.62
define LAPT as the integrated average
temperature closest to the specified
rating temperature for a given piece of
equipment achievable and repeatable
such that the IAT of a given unit is
within ±2 °F of the average of all IAT
values for that basic model. For cases
with thermostats, this will be the lowest
thermostat set point.
a. Definition of Lowest Application
Product Temperature
In the October 2013 test procedure
NOPR, DOE clarified the definition and
intent of the LAPT for equipment that
cannot maintain the prescribed rating
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
temperature. 78 FR at 64308–09 (Oct.
28, 2013). That is, DOE specified the
LAPT is the lowest temperature at
which a given basic model is capable of
operating, and equipment rated under
the LAPT provisions must be tested in
accordance with all the requirements of
the DOE test procedure, except that the
rating temperature for this equipment
will be the LAPT and the IAT measured
during the test will be within ±2 °F of
the LAPT instead of within ±2 °F of the
prescribed rating temperature for that
equipment class. DOE acknowledged
that the lowest operating temperature
for a given unit may vary slightly for
specific units tested under a given basic
model due to manufacturing tolerances,
refrigerant charge, or other minor
differences among units of a given CRE
basic model. However, the LAPT should
be specified such that, if DOE were to
select a representative unit of this model
randomly to test for compliance
purposes, DOE would be able to test the
unit by setting the unit to operate as
cold as possible and achieve an
integrated average temperature that is
±2 °F of the LAPT. 78 FR 64308–09 (Oct.
28, 2013).
In response to DOE’s proposed
clarification of LAPT in the October
2013 NOPR, interested parties had
several suggestions regarding the
definition of LAPT. Traulsen
recommended the following
clarification to the LAPT definition: The
term ‘‘LAPT’’ is attained by adjusting
the unit thermostat to the lowest
operating temperature where the ‘‘IAT’’
is maintained at a condition of ±2 °F
over the duration of the test procedure.
The LAPT value is equal to or greater
than the rating temperature based on
refrigeration system capacity or lowest
possible thermostat set point. (Traulsen,
No. 15 at p. 3) Hussmann recommended
that DOE change the definition of LAPT
for remote equipment without a
thermostat from ‘‘adjusted dew point’’
to ‘‘dew point,’’ since that is what is
controlled in a test environment.
Hussmann also stated that it believed
the LAPT should not be below the
manufacturer’s lowest specified
operating temperature and that testing
of the LAPT as the ‘‘temperature
achieved with the adjusted dew point
temperature (as defined in AHRI
Standard 1200 (I–P)-2010) set to 5
degrees colder than that required to
maintain the manufacturers lowest
specified operating temperature’’ will
only result in an unsuccessful,
unrepeatable, non-steady state test due
to excessive ice build-up on the
evaporator coil. (Hussmann, No. 11 at p.
3)
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
22297
DOE appreciates the
recommendations submitted by
interested parties regarding the
definition and specification of LAPT.
Specifically, DOE believes that
Traulsen’s recommended language is
generally incorporated into the existing
definition and procedure proposed in
the October 2013 test procedure NOPR.
Further, DOE notes that the term
‘‘LAPT’’ should be defined so as to
describe the characteristics and
specification of the lowest IAT a CRE
basic model is capable of achieving,
rather than the procedure for
determining LAPT, which is described
in the relevant section of 10 CFR 431.64.
DOE also notes that the LAPT for a
given CRE basic model does not have to
be ‘‘maintained’’ throughout the test
procedure, but rather the IAT resulting
from conducting the test procedure
should be within ±2 °F of the specified
LAPT.
In addition, in response to
Hussmann’s recommendation regarding
the LAPT provisions for remote
equipment that does not have a
thermostat, DOE agrees with Hussmann
that it may be more appropriate to
specify the dew point, as opposed to the
adjusted dew point for remote
equipment. AHRI 1200–2010 defines the
dew point as the refrigerant vapor
saturation temperature at a specified
pressure. This corresponds typically to
the temperature in the evaporator.
Conversely, the adjusted dew point is
defined in AHRI 1200–2010 as a
temperature lower than the actual dew
point to account for suction line
pressure losses and represents the
saturated suction temperature at the
compressor. This is more representative
of the refrigerant temperature entering
the compressor and is the value used to
specify compressor performance for the
purposes of determining the CDEC for
remote cases in AHRI 1200–2010. AHRI
1200–2010 further specifies the adjusted
dew point as 2 °F lower than the
evaporator dew point for commercial
refrigerators and 3 °F lower than the
evaporator dew point for commercial
freezers, when applying standardized
assumptions regarding condensing rack
performance (see Table 1 in section 5,
‘‘Rating Requirements for Remote
Commercial Refrigerated Display
Merchandisers and Storage Cabinets,’’ of
AHRI 1200–2010). While the dew point
and the adjusted dew point are
dependent on one another, DOE
acknowledges that the dew point
controls the internal refrigerated
temperature directly and is what is
directly controlled in a test
environment. DOE notes that specifying
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
22298
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
the dew point, rather than the adjusted
dew point, as 5 degrees below that
required to maintain the manufacturer’s
lowest specified operating temperature
will not change the resultant LAPT
value for remote equipment, as the two
values are dependent on one another.
Specifically, the adjusted dew point is
specified as 3 °F lower than the dew
point for commercial freezers and icecream freezers and 2 °F lower than the
dew point for commercial refrigerators.
In response to Hussmann’s comment
that specifying the adjusted dew point
as 5 degrees colder than that required to
maintain the manufacturer’s lowest
specified operating temperature will
result in internal refrigerated
temperatures that may be lower than the
manufacturer’s lowest specified
operating temperature, which could
lead to ice buildup on the evaporator
coil, DOE acknowledges that this may
be a concern but notes that this may be
an issue for only a small number of
basic models. If a model is not able to
operate consistently at a temperature 5
degrees below the dew point required to
maintain the manufacturer’s lowest
specified operating temperature, a
manufacturer must request a test
procedure waiver.
DOE notes that it adopted such
language in the 2012 test procedure
final rule to ensure that the achieved
LAPT represented a conservative rating
for remote equipment. DOE believed
this was necessary because the internal
refrigerated temperature for remote
equipment is so variable and dependent
on the remote condensing rack capacity
and operation. 77 FR at 10305 (Feb. 21,
2012). DOE is reluctant to revise the
LAPT for remote equipment without a
thermostat as the dew point required to
achieve the necessary integrated average
temperature inside the case for that
basic model. As recommended by
Hussmann, this approach would allow
manufacturers to specify virtually any
temperature as the LAPT for a given
CRE basic model, including a
temperature not representative of the
lowest temperature the CRE model can
achieve. As such, DOE is adopting
language that continues to establish the
LAPT for remote equipment without a
thermostat based on specifying the dew
point as 5 degrees below the
temperature required to maintain the
lowest specified operating temperature
of that equipment.
b. Incorporation by Reference of
ASHRAE 72–2005
Although ASHRAE 72–2005 is
currently evoked as the DOE method of
test through DOE’s incorporation by
reference of ARI 1200–2006 and AHRI
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
1200–2010 as the test procedure for
commercial refrigeration equipment,
DOE has never specifically incorporated
by reference ASHRAE 72–2005. Due to
the explicit reference of ASHRAE 72–
2005 in the proposed definition of LAPT
in the October 2013 test procedure
NOPR, DOE proposed to incorporate by
reference ASHRAE 72–2005 at 10 CFR
431.63. 78 FR at 64309 (Oct. 28, 2013).
In response to DOE’s proposal to
incorporate by reference ASHRAE 72–
2005, ASHRAE recommended that DOE
update the reference of ANSI/ASHRAE
72–2005 to the 2013 edition of this
standard. (ASHRAE, No. 8 at p. 1) DOE
notes that, at this time, a new edition of
ASHRAE 72 is not available. DOE is
aware that ASHRAE 72 is intended to be
published soon, but DOE is not electing
to delay publication of this final rule to
accommodate ASHRAE’s publication
timeline. When a new edition of
ASHRAE 72 is available, DOE will
review the revised test protocol and
consider amending DOE’s test
procedure to reference the updated
ASHRAE 72 version, as appropriate.
8. Clarifications in Response to
Interpretations to AHRI 1200–2010
The 2012 test procedure final rule
amends the DOE test procedure for
commercial refrigeration equipment to
reference AHRI 1200–2010 as the
method of test to be used as of the
compliance date of the amended
standards established published in the
March 2014 energy conservation
standards final rule. 77 FR at 10295–
10296 (Feb. 21, 2012); 79 FR 17726,
17734 (Mar. 28, 2014).
In the October 2013 test procedure
NOPR, DOE discussed five
interpretations to AHRI 1200–2010 that
AHRI had recently published. AHRI
issued interpretations 1 through 4 to
AHRI 1200–2010 to clarify the method
for calculation of TDA. Interpretation 5
to AHRI 1200–2010 clarifies the
approach for testing commercial
refrigeration equipment with two
independent refrigeration sections. 78
FR at 64309–64310 (Oct. 28, 2013). In
the October 2013 test procedure NOPR,
DOE presented its belief that the TDA
should be measured as the ‘‘projected
visible area’’ and discussed how
Interpretations 1, 3, and 4 were
consistent with this method.
Specifically, Interpretation 1 specifies
that TDA should not include any
transparent areas where the view is
blocked by solid features, Interpretation
3 describes how to treat silk screens and
other semi-transparent coverings on
transparent doors or panels, and
Interpretation 4 provides guidance to
determine the area and length of
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
commercial refrigeration equipment
with curved fronts. DOE did not
propose further clarification of the DOE
test procedure beyond the definition of
‘‘transparent’’ proposed in section
III.B.2.a of the October 2013 test
procedure NOPR, believing that the
existing test instructions contained in
ARI 1200–2006, AHRI 1200–2010, and
the DOE test procedure were sufficient
to specify clearly how to calculate TDA
for cases with solid features covering
portions of projected area or for cases
with non-rectangular geometries. 78 FR
at 64310 (Oct. 28, 2013). However, DOE
found Interpretation 2, which includes
solid features in the calculation of TDA
such as door frames and mullions, to be
inconsistent with DOE’s method of
calculating TDA. DOE’s proposed
method, comments received by
interested parties, and DOE’s responses
are laid out in more detail in section
III.A.9.
DOE also reviewed Interpretation 5,
which clarifies the method for
evaluating commercial refrigeration
equipment with more than one
refrigerated section, and found that
AHRI’s Interpretation 5 is consistent
with the DOE test procedure for these
systems, as specified at 10 CFR
431.66(d)(2)(i), which explains how to
test commercial refrigeration equipment
with more than one refrigerated
compartment or section. 78 FR at 64310
(Oct. 28, 2013).
In response to DOE’s discussion of the
AHRI interpretations in the October
2013 test procedure NOPR, China
recommended adding clarifying
language to specify how to calculate the
TDA for curved front cases and
suggested that the TDA for these cases
be based on the effective projected area.
(China, No. 10 at p. 3)
DOE acknowledges China’s suggestion
that the DOE test procedure provide
more-explicit guidance for how to
calculate TDA for cases with unique,
non-rectangular geometries. DOE notes
that AHRI Interpretation 4 lays out
clearly the approach for doing so. DOE
discussed this approach in the October
2013 test procedure NOPR and
determined that it was consistent with
the DOE test procedure and did not
need clarification. 78 FR at 64310 (Oct.
28, 2013). However, based on China’s
request, DOE notes that some interested
parties may find additional clarification
useful. As such, DOE is adopting
additional clarification in the DOE test
procedure for cases with curved front
geometries.
DOE notes that, on October 1, 2013,
ANSI approved a revised edition of the
AHRI 1200 test procedure, AHRI 1200–
2013, which incorporates a new graphic
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
mstockstill on DSK4VPTVN1PROD with RULES2
to Appendix D describing the
measurement of TDA for cases with
curved-fronts and adds language
clarifying the calculation of the height
dimension (Dh). Specifically, AHRI
1200–2013 specifies that the dimension
L shall be taken as the arc length of the
curves section of visible product area.
AHRI 1200–2013 also adopted language
to Appendix D that reads ‘‘when
measuring Dh, only the visible
dimension shall be considered. Opaque
door frames, light shades, nontransparent silk screens, and the like
that impede visibility shall be excluded
from the measurement.’’ AHRI 1200–
2013 did not make any other changes to
the methods, nomenclature, or layout of
AHRI 1200, and is otherwise consistent
with ARI 1200–2006 and AHRI 1200–
2010, the test procedures currently
incorporated by reference into the DOE
test procedure.
In the 2012 test procedure final rule,
DOE incorporated by reference AHRI
1200–2010 as the test procedure for
commercial refrigeration equipment
manufactured on or after the
compliance date of the amended energy
conservation standards adopted in the
March 2014 energy conservation
standards final rule.13 77 FR at 10295,
10308–09, 10318–21 (Feb. 21, 2012); 79
FR 17726, 17734 (Mar. 28, 2014). DOE
also maintained the incorporation by
reference of ARI 1200–2006 for
equipment certified prior to March 28,
2017. 77 FR at 10318–10320 (Feb. 21,
2012). In the 2012 test procedure final
rule, DOE discussed the changes made
between ARI 1200–2006 and AHRI
1200–2010 as including both editorial
and technical changes to (1) the
equipment class nomenclature used
within the test procedure; (2) the
integrated average rating temperature for
ice-cream freezers; and (3) the method
of normalizing and reporting units for
equipment energy consumption. 77 FR
at 10296 (Feb. 21, 2012). AHRI 1200–
2013 differs from AHRI 1200–2010 in
adopting (1) a new definition of
‘‘transparent surface,’’ which is a
surface with a minimum of 65 percent
light transmission or 65 percent clear
surface; (2) a new statement in
Appendix D specifying that when
13 In the 2012 test procedure final rule, DOE
adopted a specific date (January 1, 2016), which
was the anticipated compliance date for any
standards amended as a result of the ongoing CRE
energy conservation standards rulemaking (Docket
No. EERE–2010–BT–STD–0003). However, DOE
discussed in the preamble to the 2012 test
procedure final rule that the intent was to require
compliance with the test procedure amendments
adopted in that final rule consistent with the
compliance of any new or amended standards. 77
FR 10292, 10295, 10308–9, 10318–21 (Feb. 21,
2012).
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
calculating Dh only the visible
dimension shall be considered; and (3)
an additional figure, Figure D18,
providing clarification regarding the
calculation of TDA for radius cases with
transparent sides.
DOE finds the amendments adopted
in AHRI 1200–2013 to be generally
consistent with the DOE test procedure
for commercial refrigeration equipment,
except DOE finds the need for
additional clarity surrounding the
description of how TDA is to be
calculated for radius cases the definition
of ‘‘transparent surface.’’ For radius
cases, DOE maintains that TDA shall be
calculated as the projection of visible
product, as described in section III.A.9.
To clarify the method for calculating
TDA for equipment with curved-front
geometries, DOE is adopting a new
figure specifying the dimensions Dh, L,
and area Ae are to be determined as
planar projections of the area of visible
product when viewed at an angle
normal to the transparent area for radius
cases. Regarding the definition of
‘‘transparent surface,’’ as discussed in
section III.A.2.b, DOE adopts a
definition of ‘‘transparent’’ based on a
light transmittance of 45 percent when
measured in accordance with ASTM
Standard E 1084–86 (Reapproved 2009).
9. Clarification of Methodology for
Measuring Total Display Area
DOE uses TDA to determine the
applicable performance standard for
remote condensing commercial
refrigeration equipment with
transparent doors or no doors.
Appendix D of ARI 1200–2006 and
AHRI 1200–2010, as incorporated by
reference by DOE at 10 CFR 431.63,
provides a definition and instructions
on determining TDA. AHRI 1200–2013
provides the same definition and
instructions, and specifies that when
calculating Dh, only the visible
dimension shall be considered, an
additional figure, Figure D18, provides
clarification regarding the calculation of
TDA for radius cases with transparent
sides. Appendix D of ARI 1200–2006,
AHRI 1200–2010, and AHRI 1200–2013
defines TDA as follows:
‘‘Total Display Area (TDA) is the sum of
the projected area(s) for visible product.’’
Moreover, Appendix D provides a
general equation for calculating the
‘‘projected area(s),’’ in the form of:
TDA = Dh*L + Ae,
Where:
Ae = Projected area from visible product
through end walls
Dh = Dimension of projected visible product
L = Length of Commercial Refrigerated
Display Merchandiser
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
22299
Figures D1 through D16 of Appendix
D of ARI 1200–2006, AHRI 1200–2010,
and AHRI 1200–2013 provide
instructions on the measurement of Dh,
L, and Ae for various geometries of
commercial refrigerated display
merchandisers. These figures show that
TDA includes only those areas through
which displayed product is visible for
the Ae and Dh dimension, irrespective of
the presence of other transparent areas
through which product cannot be
viewed. As Interpretations 1, 3, and 4 of
AHRI 1200–2010 and the amendments
adopted in AHRI 1200–2013 make clear,
the converse is also true—areas of the
product zone that cannot be viewed as
part of a direct projection through a
transparent area are not to be included
in any measurement of Dh. The term
‘‘direct projection’’ refers to the view at
an angle perpendicular to the plane of
product presentation (facing area). ARI
1200–2006, AHRI 1200–2010, and AHRI
1200–2013 all define the third variable,
‘‘L’’, as the ‘‘length of commercial
refrigerated display merchandiser.’’
However, Appendix D contains no
figures or illustrations instructing a user
how to perform this measurement.
In the October 2013 test procedure
NOPR, DOE discussed the calculation of
TDA for various CRE models and, at the
public meeting presented figures, to
illustrate the concept that the
measurement of TDA in practice should
be consistent with its definition as the
‘‘dimension of projected visible
product.’’ (DOE, No. 3 at pp. 68–71)
DOE clarified that this included the
dimension L, which corresponds to the
total length of the transparent area of the
merchandiser through which product
can be seen; areas of opaque material
that overhang the product zone and well
as areas of transparent material that do
not project upon a zone occupied by
product, should not be included in this
length. To clarify the calculation of
TDA, DOE proposed to add clarifying
text and figures to the test procedure
explaining that the measurement of
TDA should be representative of the
‘‘dimension of projected visible
product’’ and that no opaque materials
or areas of transparent material through
which product cannot be viewed should
be included in the calculation of TDA.
78 FR at 64310–64312 (Oct. 28, 2013).
In response to DOE’s proposal to
clarify the method of calculating TDA,
DOE received several comments from
interested parties objecting to DOE’s
interpretation and offering suggestions
for other methods of calculating the
dimension L when determining TDA of
a CRE basic model with transparent
doors or no doors. AHRI, Hill Phoenix,
Hussmann, and Zero Zone disagreed
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
22300
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
with DOE’s definition of the length of a
commercial refrigerated display
merchandiser and stated that industry
has always treated the length ‘‘L’’ as the
‘‘length of the commercial refrigerated
display merchandiser’’ from inside wall
to inside wall, disregarding the presence
of non-transparent mullions and door
frames. AHRI, Hill Phoenix, Hussmann,
and Zero Zone further believed, and
provided quantitative justification to
support, that DOE must have used case
length in the engineering analysis for
the 2009 and the current rulemaking.
(Docket No. EERE–2012–BT–STD–0003)
The commenters stated it is impossible
to have a typical 30-inch by 67-inch
door have 13 square feet of TDA without
including the mullions and door frames
and provided analysis to support this
viewpoint. The commenters added that
using TDA as DOE described in the
October 2013 test procedure NOPR
instead of case length would reduce the
standard level by 10 to 12.5 percent.
(AHRI, No. 15 at pp. 1–3; Hill Phoenix,
No. 13 at pp. 2–6; Hussmann, No. 11 at
pp. 3–4; Zero Zone, No. 18 at pp. 3–4)
Hussmann expressed concern that
changing the method for calculating
TDA without changing the standards
would unfairly penalize manufacturers.
(Hussmann, Public Meeting Transcript,
No. 7 at p. 190)
Arneg and Zero Zone commented that
the TDA is dependent on the distance
the observer is located from the door
and their orientation of viewing. (Arneg,
Public Meeting Transcript, No. 7 at p.
196; Zero Zone, Public Meeting
Transcript, No. 7 at pp. 196–198)
To be consistent with current industry
practice and DOE’s energy conservation
standard rulemaking analysis (Docket
No. EERE–2010–BT–STD–0003), AHRI,
Hill Phoenix, and Hussmann suggested
that DOE use the interior refrigerated
length, calculated from inside wall to
inside wall, except for when a case has
greater than 5 inches of non-transparent
area. For CRE models with more than 5
inches of non-transparent length in the
dimension L, the commenters
recommended that DOE use total length
of transparent area plus 5 inches. (AHRI,
No. 15 at pp. 1–3; Hill Phoenix, No. 13
at pp. 2–6; Hussmann, No. 11 at p. 4)
Zero Zone recommended that DOE
adjust the energy conservation standard
to account for the reduction in TDA
associated with not including the door
frames and mullions in the calculation
of TDA. If DOE elects not to adjust the
energy conservation standard
commensurate with the change in
calculation of TDA, Zero Zone
recommended that DOE not alter the
calculation of TDA from that assumed
in the engineering analysis for the
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
ongoing energy conservation standard
rulemaking (Docket No. EERE–2010–
BT–STD–0003) and noted that the
market place will sort out the value and
utility of equipment that has more or
less visible product. (Zero Zone, No. 18
at p. 4) Zero Zone suggested that DOE
incorporate a TDA-dependent
component in the formula for energy,
and another component considering
non-TDA space or volume, noting that
this is a unique design, although
something similar has been done for ice
cases. (Zero Zone, Public Meeting
Transcript, No. 7 at pp. 206–207)
Traulsen suggested using volume to
calculate energy consumption for glass
door remotes, effectively bypassing the
TDA discussion, or suggested leaving
TDA as a square-footage calculated wallto-wall, top to bottom while ignoring the
depth dimension. (Traulsen, Public
Meeting Transcript, No. 7 at pp. 209–
211)
Southern Store Fixtures expressed
concern that setting the precedent of
eliminating mullions could result in the
elimination from the calculation of TDA
of other components in the refrigerated
space that occupy space not containing
merchandise. Southern Store Fixtures
asserted that this could eventually cause
the calculation to become complicated
and burdensome for manufacturers.
(Southern Store Fixtures, Public
Meeting Transcript, No. 7 at pp. 207–
208)
Hussmann, True, and Zero Zone
agreed that, for the majority of cases
observed in the field, calculating L
using the length of the interior
refrigerated volume or the continuous
length of the transparent doors
(including mullions and doorframes)
would be the same. (Hussmann, Public
Meeting Transcript, No. 7 at pp. 217–
218; True, Public Meeting Transcript,
No. 7 at p. 218; Zero Zone, Public
Meeting Transcript, No. 7 at pp. 219–
220)
In response to the suggestions offered
by interested parties, DOE finds that
calculating TDA to include portions of
non-transparent area is inconsistent
with the stated definition of TDA.
However, DOE acknowledges that
defining TDA as strictly the total length
of transparent area may be inconsistent
with the method used by industry to
calculate TDA today. As a compromise,
DOE is adopting in this final rule, a
method for calculating the TDA of CRE
basic models that is representative of
the dimension through which product
can be viewed, but which
accommodates small non-transparent
areas that are part of the doors
themselves and are typically included
in the calculation of TDA by
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
manufacturers today. With regards to
the calculation of TDA for the vertical
closed transparent case modeled in
DOE’s engineering analysis supporting
the March 2014 energy conservation
standards final rule, DOE notes that the
case modeled represents a typical multideck refrigerated merchandiser with five
doors of 13 square feet each, for a TDA
of 65 square feet (see appendix 5A of the
technical support document for March
2014 energy conservation standards
rulemaking final rule, Docket No. EERE–
2010–BT–STD–0003). DOE based its
calculation of representative door TDA
upon the continuous length of
transparent area of the CRE model,
which included mullions and door
frames, but excluded any additional
case wall present on the front face of the
unit. In other words, DOE included the
entire length of the transparent doors,
including minor non-transparent areas,
in its calculation of case TDA. DOE
notes that, for the case modeled, the
interior length of the refrigerated
volume would be the same as the
continuous length of transparent area
when measured from door edge to door
edge. DOE emphasizes that the model is
meant to be representative of the energy
use of a given type of commercial
refrigeration equipment, and not to
represent all the different design options
available for any given model within an
equipment category.
DOE agrees with interested parties
that if the dimension L were determined
strictly as the length of transparent area,
not including any non-transparent
mullions or door frames, the difference
may be on the order of 10 percent.
However, to respond to the concerns of
interested parties, DOE is not adopting
such a strict definition of L, but rather
a ‘‘continuous’’ length of transparent
area to be consistent with the
continuous dimension of Dh. DOE
believes that, to be consistent with the
definition and intent of TDA, the
dimension L should represent the
continuous length of transparent area, as
proposed in the October 2013 test
procedure NOPR. 78 FR at 64321 (Oct.
28, 2013). However, DOE acknowledges
that some unique case designs may
feature large sections of case wall or
other non-transparent area between
sections of transparent area and agrees
with interested parties that some
threshold is necessary to ensure only
materials with a significant majority of
transparent area are included in the
dimension L (e.g., transparent doors
with thin door mullions or other nontransparent hardware). DOE has
reviewed the suggestion, submitted by
interested parties that 5-inches or less of
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
non-transparent length be allowed in
the measurement of L. DOE finds that a
threshold of 5-inches or less is not
sufficient to accommodate the nontransparent lengths for a large number of
transparent-door CRE models with more
than 3 doors. In addition, DOE notes
that a fixed threshold of 5-inches for
cases, regardless of the size of the case
and the length of the dimension ‘‘L’’
does not treat all cases equivalently.
However, DOE acknowledges that the
concept of a threshold for nontransparent area, as suggested by
interested parties, prevents cases with
significant portions of non-transparent
area between transparent doors or cases
with transparent doors significantly
inset from the case end walls from
calculating an unrepresentatively high
TDA, as would be the case if only
interior refrigerated case length was
used. As such, DOE believes a more
consistent approach would be to apply
a threshold of non-transparent area that
may be included in the dimension ‘‘L’’
based on a percentage of the interior
refrigerated case length that is not
transparent. DOE is adopting in this
final rule a threshold of 10 percent of
non-transparent area that may be
included in the dimension L. DOE
believes this will more equitably treat
the variety of case designs available on
the market. DOE also notes that the 10
percent threshold is less stringent than
the 5-inch threshold recommended by
manufacturers. That is, a threshold of 10
percent accommodates greater amounts
of non-transparent area in the
dimension ‘‘L’’ for a majority of CRE
models. In addition, a threshold of 10
percent is consistent with the modeling
performed in the CRE energy
conservation standard rulemaking
(Docket No. EERE–2010–BT–STD–
0003).
For those cases with greater than 10
percent of non-transparent area in the
interior refrigerated length of the CRE
model, DOE agrees with the general
approach recommended by interested
parties that the dimension L should be
determined as the total length, along the
axis of the merchandiser, of portions
through which product can be viewed
from an angle normal to the transparent
area (i.e., the projected linear
dimension(s) of visible product) plus 10
percent, to provide equitable treatment
of cases with different door
configurations.
Therefore, in this final rule, DOE
adopts instructions for calculating TDA
that define L as the interior length of the
CRE model, provided no more than 10
percent of that length consists of nontransparent material. For those cases
with greater than 10 percent of non-
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
transparent area, L shall be determined
as the projected linear dimension(s) of
visible product plus 10 percent of nontransparent area.
DOE believes this instruction is
consistent with and clarifies current
industry practice and the existing
provisions of the DOE test procedure
and, as such, believes that this
amendment should not change the
measured energy consumption of
covered equipment. Therefore, DOE is
adopting these amendments in both
Appendix A, which is the test
procedure required for equipment
testing to demonstrate compliance with
current energy conservation standards,
and Appendix B, which will be required
for testing on March 28, 2017, consistent
with the compliance date of the
amended energy conservation standards
established in the March 2014 energy
conservation standards final rule. 79 FR
17726, 17727 (Mar. 28, 2014).
10. Compliance Date of Test Procedure
Amendments
In this final rule, DOE also
reorganizes the test procedure
requirements at 10 CFR 431.64 so that
they are easier to understand, and
updates the compliance date to be
consistent with the compliance date of
the amended standards established in
the March 2014 energy conservation
standards final rule. 79 FR 17726, 17727
(Mar. 28, 2014).
EPCA prescribes that if any
rulemaking amends a test procedure,
DOE must determine to what extent, if
any, the proposed test procedure would
alter the measured energy efficiency of
any covered equipment as determined
under the existing test procedure. (42
U.S.C. 6314(a)(6)) Further, if DOE
determines that the amended test
procedure would alter the measured
efficiency of covered equipment, DOE
must amend the applicable energy
conservation standard accordingly. (42
U.S.C. 6314(a)(6))
In the 2012 test procedure final rule,
DOE stated that some test procedure
amendments will change the measured
energy consumption of some covered
equipment. 77 FR at 10295 and 10309
(Feb. 21, 2012). Specifically, DOE
determined the provisions to
accommodate testing of night curtains
and lighting occupancy sensors and
controls altered the measured energy
consumption of covered equipment. 77
FR at 10309 (Feb. 21, 2012). As such,
DOE established in the 2012 test
procedure final rule that use of the
amended test procedure for compliance
with DOE energy conservation
standards or representations with
respect to energy consumption of
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
22301
commercial refrigeration equipment
would be required on the compliance
date of the revised energy conservation
standards established in the March 2014
energy conservation standards final
rule. 77 FR at 10309 (Feb. 21, 2012); 79
FR 17726, 17727 (Mar. 28, 2014).
To improve clarity, in the October
2013 test procedure NOPR, DOE
proposed to reorganize the language at
10 CFR 431.64 into Appendices A and
B. In the October 2013 test procedure
NOPR, Appendix A contained the test
procedure for commercial refrigeration
equipment established in the 2006 test
procedure final rule and Appendix B
included the amended test procedure
established in the 2012 test procedure
final rule that will be required to be
used on March 28, 2014, consistent with
the compliance date of the amended
standards established in the March 2014
energy conservation standards final
rule. 78 FR at 64318–64325 (Oct. 28,
2013); 79 FR 17726, 17727 (Mar. 28,
2014).
In response to DOE’s proposal,
Hussmann stated that is does not
understand why DOE cannot allow
energy-saving features adopted in the
2012 test procedure final rule to
demonstrate compliance with current
energy conservation standards.
(Hussmann, No. 11 at p. 3) Hussmann
further stated that it believes that the
provision allowing manufacturers to
rate equipment conservatively that were
tested at a temperature lower than the
required 38 ± 2 °F provided the basic
model still meets the applicable energy
conservation standard should be
included in Appendix A (effective 30
days after publication of a final rule in
the Federal Register) as well as
Appendix B. Hussmann added that this
will reduce testing burden for
manufacturers without sacrificing
efficiency. (Hussmann, No. 11 at p. 3)
Zero Zone commented that it agreed
with DOE’s proposed approach to test
remote cases under the LAPT and
suggested that the test method should be
included as part of Appendix A and
immediately become part of DOE’s test
procedure. (Zero Zone, No. 18 at p. 3)
With regard to permitting early use of
the test procedure amendments
established in the 2012 test procedure
final rule, DOE acknowledges
Hussmann’s request and notes that DOE
has published guidance establishing
that, while manufacturers need not
comply with a new or amended test
procedure prior to the compliance date
established for that test procedure,
manufacturers may voluntarily use
amended test procedures to rate and
certify their products prior to the
compliance date if they also comply
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
22302
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
with energy conservation standards
based on that test procedure. See
https://www1.eere.energy.gov/buildings/
appliance_standards/pdfs/tp_faq_201206-29.pdf. DOE cannot permit amended
test procedure provisions that affect the
measured energy consumption to be
used to demonstrate compliance with
energy conservation standards that were
not set based on that test procedure.
Specifically, the provisions adopted in
Appendix B in this final rule may be
used prior to the compliance date
established in this final rule as long as
the equipment also demonstrates
compliance with the amended standards
established in the March 2014 energy
conservation standards final rule, which
used that test procedure as a basis. 79
FR 17726, 17734 (Mar. 28, 2014).
Manufacturers may not use the test
procedure established in Appendix B to
demonstrate compliance with existing
energy conservation standards.
In response to Hussmann’s request to
include allowances for conservatively
rating commercial refrigerators at
temperatures lower than the specified
rating temperature of 38 ± 2 °F in
Appendix A as well as Appendix B,
DOE acknowledges that, in addition to
testing and certification to comply with
DOE’s energy conservation standards,
commercial refrigeration equipment that
is marketed to hold perishable food
items must also be classified and
certified by NSF/ANSI–7, ‘‘Commercial
Refrigerators and Freezers’’ (hereafter
referred to as NSF–7), a food safety
standard issued by NSF.14 NSF–7
establishes two classes for commercial
display cases: Type I, which is tested at
ASHRAE Standard 72 standard ambient
conditions (75 °F dry bulb and 64 °F wet
bulb temperature), and Type II, which is
tested at higher ambient conditions
(80 °F dry bulb and 68 °F wet bulb
temperature). These two test conditions
are also reported in terms of dry bulb
temperature and percentage relative
humidity. Type I corresponds to 75 °F
and 55 percent relative humidity, and
Type II corresponds to 80 °F and 60
percent relative humidity. NSF–7 also
requires Type I and Type II equipment
to be tested such that the average
temperature of each test package
containing an individual temperature
sensor does not exceed 41 °F and no
single temperature sensor exceeds a
reading of 43 °F at any time during the
test. NSF–7 does not specify a required
average temperature for all test sensors
or the measurement of energy
14 NSF International. ‘‘NSF/ASNI 7—2009:
Commercial Refrigerators and Freezers.’’ Ann
Arbor, MI. https://www.nsf.org/business/food_
equipment/standards.asp.
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
consumption during the test. On the
other hand, DOE does require an
integrated average test temperature of
38 °F ± 2 °F. However, manufacturers
have reported that they test cases at
lower IATs than that specified by DOE
to ensure the NSF–7 requirements are
met. In the 2012 test procedure final
rule, DOE establishes provisions that
allow manufacturers to optionally test
equipment at internal or ambient
conditions more stringent than the
prescribed DOE rating temperatures and
conditions for that equipment class, to
reduce the repetitive test burden of
testing at both DOE and NSF–7
conditions. 77 FR at 10305–07 (Feb. 21,
2012).
DOE believes that accommodating
Hussmann’s request and including the
provisions regarding certification of
equipment at conservative IATs in both
Appendix A and Appendix B won’t
affect the measured energy consumption
of covered equipment or the stringency
of the applicable energy conservation
standard, as the provision is voluntary
and thus is not required for equipment
testing. In addition, DOE believes that
allowing manufacturers to implement
this conservative rating approach as of
30 days after publication of a final rule
in the Federal Register will significantly
reduce the burden associated with
testing equipment that must be certified
to both DOE’s energy conservation
standards and NSF’s food safety
standard. Therefore, DOE is adopting
optional provisions to allow
manufacturers to conservatively rate
equipment at internal or ambient
temperatures more stringent than the
rating temperature or ambient
conditions prescribed for their
equipment class, provided the basic
model still meets the applicable energy
conservation standard, in both
Appendix A and Appendix B. DOE
notes that all other test procedure
requirements must be satisfied to ensure
a valid test; only the IAT and rating
conditions may be adjusted.
In response to Zero Zone’s
recommendation that DOE include the
provisions for testing equipment that
cannot be tested at the specified rating
temperature at the LAPT in Appendix A
in addition to Appendix B, DOE is
incorporating the LAPT provisions into
both Appendix A and Appendix B as
part of this final rule.
B. Other Notice of Proposed Rulemaking
Comments and DOE Responses
In response to the October 2013 test
procedure NOPR, DOE received
comments from interested parties
regarding several issues that pertain to
the CRE test procedure, but not to
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
specific provisions or amendments.
Specifically, DOE received comments
on the ambient temperatures used for
testing commercial refrigeration
equipment at standard rating conditions
and the burden of testing.
1. Ambient Test Temperatures
DOE’s test procedure for commercial
refrigeration equipment establishes
standard rating conditions for testing
covered equipment of 75 °F and 55
percent relative humidity. Commercial
refrigeration equipment that is marketed
to hold perishable food items is
classified and certified by NSF/ANSI–7,
‘‘Commercial Refrigerators and
Freezers’’ (hereafter referred to as NSF–
7), a food safety standard issued by NSF.
NSF–7 establishes two classes for
commercial display cases: Type I, which
is tested at ASHRAE Standard 72
standard ambient conditions (75 °F dry
bulb and 64 °F wet bulb temperature),
and Type II, which is tested at higher
ambient conditions (80 °F dry bulb and
68 °F wet bulb temperature). These two
test conditions are also reported in
terms of dry bulb temperature and
percentage relative humidity. Type I
corresponds to 75 °F and 55 percent
relative humidity, and Type II
corresponds to 80 °F and 60 percent
relative humidity. NSF–7 also requires
Type I and Type II equipment to be
tested such that the average temperature
of each test package containing an
individual temperature sensor does not
exceed 41 °F and no single temperature
sensor exceeds a reading of 43 °F at any
time during the test. NSF–7 does not
specify a required average temperature
for all test sensors or the measurement
of energy consumption during the test.
On the other hand, DOE does require an
integrated average test temperature of
38 °F ± 2 °F. However, manufacturers
have reported that they test cases at
lower IATs than that specified by DOE
to ensure the NSF–7 requirements are
met.
Continental commented that
commercial refrigeration equipment is
designed primarily to keep food safe in
harsh conditions and added that most
commercial kitchens have multiple
pieces of heat-generating cooking
equipment near the refrigeration
equipment and ambient temperatures
much higher than 75 °F. Continental
suggested that DOE utilize ambient test
temperatures and allowable energy
consumption levels cognizant of public
health and safety. (Continental, No. 14
at p. 2)
In response to the comment from
Continental, DOE believes that the
existing test conditions specified within
the ASHRAE 72 test procedure and
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
accepted by industry are generally
representative of field conditions. With
respect to equipment designed to
operate in harsher ambient conditions,
DOE previously considered NSF Type II
equipment in the 2012 test procedure
final rule and found that the compressor
systems can effectively operate at test
temperatures. In the 2012 test procedure
final rule, DOE agreed with interested
parties that testing cases at an ambient
temperature of 80 °F, rather than the
currently specified 75 °F, will not have
a significant impact on energy
consumption for cases with doors and
recognized that the impact on open
cases may be greater than on closed
cases, but did not believe that
equipment will have operation or
performance issues if tested at a the
temperatures prescribed by the DOE test
procedure. 77 FR at 10305–10307 (Feb.
21, 2012). DOE maintains that the
energy consumption of a case should
scale with ambient temperature and
does not believe these issues will
prevent units from being tested using
the DOE-prescribed test temperatures or
complying with any existing or
amended DOE energy conservation
standards.
mstockstill on DSK4VPTVN1PROD with RULES2
2. Burden of Testing
Felix Storch, Inc. (FSI) expressed
concern that there would be an undue
burden on small business to conduct the
proposed test procedures. FSI’s opinion
was that DOE has not calculated the full
extent to which the proposed test
procedures revisions will affect small
manufacturers. FSI further commented
that small businesses have limited R&D
budgets and expertise to understand and
carry out the proposed test procedures
effectively. (FSI, No. 12 at p. 1)
FSI recommended, to limit burden on
small business, that: (1) Small
businesses be allowed to use a single
test for each basic model; (2) DOE
provide free consulting help to small
businesses to interpret test procedures
and be bound in enforcement cases by
the interpretations it provides; (3) DOE,
upon issuance of notices or rulemaking
documents, be required to notify
affected small businesses of new or
revised regulations, and no enforcement
be permitted against small business
absent such notification; and (4) CCMS
submission be optional, not required,
for small businesses as this represents a
large burden with little benefit to the
consumer community. (FSI, No. 12 at p.
3) Finally, FSI stated that small
businesses, such as FSI, serve small
niche markets and increase customer
choice by providing customizable
solutions. (FSI, No. 12 at p. 3)
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
DOE understands that amending test
procedures or including additional
provisions in those test procedures
could increase the burden on
manufacturers to quantify the
performance of their equipment. EPCA
requires that the test procedures
promulgated by DOE be reasonably
designed to produce test results that
reflect energy efficiency, energy use,
and estimated operating costs of the
covered equipment during a
representative average use cycle. EPCA
also requires that the test procedure not
be unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
DOE has analyzed the expected
incremental cost of the test procedure
amendments adopted in this final rule
and its impact on manufacturers. All
commercial refrigeration equipment
covered by this rule is currently
required to be tested using the DOE test
procedure to show compliance with
applicable energy conservation
standards. The DOE test procedure, as
amended by the 2012 test procedure
final rule, consists of one 24-hour test at
standard rating conditions to determine
daily energy consumption.
In addition, the 2012 test procedure
final rule amends the test procedure for
commercial refrigeration equipment to
update the referenced industry test
procedures to their most current
versions (AHRI 1200–2010 and AHAM
HRF–1–2008); incorporates provisions
for testing certain energy efficiency
features, including night curtains and
lighting occupancy sensor and
scheduled controls; and provides a test
procedure for specialty equipment that
cannot be tested at the prescribed rating
temperature. As part of that rulemaking,
DOE considered the burden associated
with the test procedure amendments
and certified that the rule would not
have a ‘‘significant economic impact on
a substantial number of small entities,’’
and the preparation of a regulatory
flexibility analysis was not warranted.
77 FR at 10314–10316 (Feb. 21, 2012).
The test procedure amendments
adopted in this final rule only
reorganize and clarify the existing
requirements in the DOE test procedure,
both those established in the 2006 test
procedure final rule and those
established in the 2012 test procedure
final rule; they do not alter or affect any
of the test procedure requirements or
technical provisions in any way. DOE
does not believe that the proposed test
procedure amendments would affect the
way in which any covered commercial
refrigeration equipment is tested, nor
would they impact the burden of
conducting such a test.
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
22303
In this test procedure final rule, DOE
is also allowing manufacturers to test at
the internal temperatures and/or
ambient conditions required for NSF–7
testing within 30 days of publication of
this final rule in the Federal Register.
This will dramatically reduce the
burden for manufacturers that produce
equipment for food storage, as under the
amended test procedure these two 24hour tests can be combined. The NSF–
7 test is similar in length and burden to
the DOE test, but is performed at
slightly different internal and external
temperatures. Certification of equipment
tested at NSF–7 test temperatures for the
purposes of compliance with DOE
energy conservation standards will only
be possible for equipment that is able to
meet the DOE energy conservation
standard at the more stringent NSF–7
test conditions. However, DOE believes
this provision can still potentially
decrease the burden of test for some
manufacturers.
The amendments to the test procedure
for commercial refrigeration equipment
were chosen to help minimize the
impact of additional testing while
clarifying and reorganizing the DOE test
procedure to provide more accurate and
repeatable test methods. Because none
of these amendments significantly
increase the burden of a test, DOE
believes that the test procedure finalized
here will not be unduly burdensome to
conduct.
In response to FSI’s comments
regarding this impact of DOE’s test
procedure for commercial refrigeration
equipment on small businesses, DOE
notes that the bulk of FSI’s
recommendations address CCE
provisions that were established in a
previous rulemaking (76 FR at 12446–
12449 (March 7, 2011)) and are not
addressed in this final rule. DOE
provided a robust analysis of the
estimated burden of the test procedure
clarifications and amendments adopted
in this final rule and determined that
these changes would not cause an
undue burden on small manufacturers.
This analysis is presented in section
IV.B of this final rule.
With regard to burden on small
manufacturers associated with
previously promulgated rulemakings,
DOE is only analyzing the incremental
burden associated with the amendments
and provisions adopted as a result of
this final rule. However, DOE notes that
previous rulemakings, such as those that
accounted for the impact of CCE
requirements on CRE manufacturers,
including small businesses, have
accounted for the incremental burden
associated with these requirements and,
in each case, found the burden to not
E:\FR\FM\21APR2.SGM
21APR2
22304
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
have a significant impact on a
substantial number of small entities.
Specifically, with regard to an
allowance for small businesses to use a
single test for each basic model, DOE
established a sample size of not less
than two in the CCE final rule for all
manufacturers regardless of size to
ensure a suitable representation of
model variability. 76 FR at 12453
(March 7, 2011). Regarding the
availability of free consulting help for
small businesses to interpret test
procedures, DOE has established a
guidance process whereby interested
parties may submit questions to DOE at
any time regarding proper conduct of
the DOE test procedure or compliance
with relevant certification requirements.
DOE also maintains a database of issues
on which DOE has issued guidance for
reference.15 When DOE issues notices or
rulemaking documents, these
documents are immediately available on
DOE’s Web site for Appliance and
Commercial Equipment Standards 16
and are publicly available via the
Federal Register. DOE seeks to be as
open as possible in conducting
rulemakings and invites interested
parties to participate openly. Regarding
CCMS submission of certified ratings for
small businesses, DOE has the same
requirements for small businesses as for
large entities and is under the same
requirements to verify compliance with
applicable energy conservation
standards. Without certification reports,
DOE has no record of compliance for
applicable covered products. Further,
DOE has attempted to design the CCMS
templates to be as simple and
straightforward as possible to minimize
burden on manufacturers required to
use these templates. Therefore, DOE
continues to require certification of the
TDEC or CDEC of covered basic models
of commercial refrigeration equipment
based on the testing of at least two
unique units and the submittal of
certification reports using DOE’s CCMS
templates.
IV. Procedural Issues and Regulatory
Review
mstockstill on DSK4VPTVN1PROD with RULES2
A. Review Under Executive Order 12866
The Office of Management and Budget
(OMB) has determined that test
procedure rulemakings do not constitute
‘‘significant regulatory actions’’ under
section 3(f) of Executive Order 12866,
15 U.S. Department of Energy Appliance &
Commercial Equipment Standards Program
Guidance and Frequently Asked Questions,
available at: https://www1.eere.energy.gov/guidance/
default.aspx?pid=2&spid=1.
16 https://energy.gov/node/773531/about_
appliance_and_equipment.html.
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
‘‘Regulatory Planning and Review,’’ 58
FR 51735 (Oct. 4, 1993). Accordingly,
this action was not subject to review
under the Executive Order by the Office
of Information and Regulatory Affairs
(OIRA) in the OMB.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility act
analysis (IRFA) whenever an agency is
required to publish a general notice of
proposed rulemaking. When an agency
promulgates a final rule after being
required to publish a general notice of
proposed rulemaking, the agency must
prepare a final regulatory flexibility
analysis. The requirement to prepare
these analyses does not apply to any
proposed or final rule if the agency
certifies that the rule will not, if
promulgated, have a significant
economic impact on a substantial
number of small entities. If the agency
makes such a certification, the agency
must publish the certification in the
Federal Register along with the factual
basis for such certification.
As required by Executive Order
13272, ‘‘Proper Consideration of Small
Entities in Agency Rulemaking,’’ 67 FR
53461 (Aug. 16, 2002), DOE published
procedures and policies on February 19,
2003, so that the potential impacts of its
rules on small entities are properly
considered during the rulemaking
process. 68 FR 7990 (Feb. 12, 2003).
DOE has made its procedures and
policies available on the Office of the
General Counsel’s Web site at https://
energy.gov/gc/office-general-counsel.
In the October 2013 test procedure
NOPR, DOE reviewed the proposed rule
to amend the test procedure for
commercial refrigeration equipment,
under the provisions of the Regulatory
Flexibility Act and the procedures and
policies published on February 19,
2003. DOE certified that the proposed
rule, if adopted, would not result in a
significant impact on a substantial
number of small entities. 78 FR at 64313
(October 28, 2013). DOE received
comments on its certification and the
economic impacts of the test procedure,
and has responded to these comments
in section III.B.2. After consideration of
these comments, DOE certifies that the
test procedure amendments set forth in
this final rule will not have a significant
impact on a substantial number of small
entities. The factual basis for this
certification is set forth below.
For the commercial refrigeration
industry, the Small Business
Association (SBA) has set a size
threshold, which defines those entities
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
classified as ‘‘small businesses’’ for the
purpose of the statute. DOE used the
SBA’s size standards to determine
whether any small entities would be
required to comply with the rule. The
size standards are codified at 13 CFR
Part 121. The standards are listed by
North American Industry Classification
System (NAICS) code and industry
description and are available at https://
www.sba.gov/sites/default/files/files/
Size_Standards_Table.pdf. Commercial
refrigeration equipment manufacturing
is classified under NAICS 333415, ‘‘AirConditioning and Warm Air Heating
Equipment and Commercial and
Industrial Refrigeration Equipment
Manufacturing.’’ Small entities within
this industry description are those with
750 employees or fewer.
DOE conducted a market survey to
determine whether any small business
manufacturers of equipment would be
covered by this rulemaking. During its
market survey, DOE used all available
public information to identify potential
small manufacturers. DOE’s research
involved the review of industry trade
association membership directories
(including AHRI), equipment databases
(e.g., Federal Trade Commission (FTC),
the Thomas Register, California Energy
Commission (CEC), and ENERGY STAR
databases), individual company Web
sites, and marketing research tools (e.g.,
Dunn and Bradstreet reports, Manta) to
create a list of companies that
manufacture or sell commercial
refrigeration equipment covered by this
rulemaking. DOE also referred to a list
of small businesses that manufacture
commercial refrigeration equipment,
supplied by Traulsen in a written
comment provided in response to the
NOPR proposing amendments to the
DOE test procedure for commercial
refrigeration equipment published
November 24, 2010 (Docket No. EERE–
2010–BT–TP–0034, Traulsen, No. 9 at
pp. 4–5). Using these sources, DOE
identified 61 manufacturers of
commercial refrigeration equipment.
DOE then reviewed this data to
determine whether the entities met the
SBA’s definition of a small business
manufacturer of commercial
refrigeration equipment and screened
out companies that do not offer
equipment covered by this rulemaking,
do not meet the definition of a ‘‘small
business,’’ or are foreign owned and
operated. Based on this review, DOE has
identified 26 companies that would be
considered small manufacturers and
will be directly regulated by this rule,
which represents 43 percent of national
CRE manufacturers. Although 43
percent would be considered a
substantial number of small entities,
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
further analysis of incremental costs
associated with this rulemaking
determined no significant impact on
these manufacturers. Specifically, the
changes to the test procedure adopted in
this final rule consist only of
clarifications regarding:
1. The applicability of the test
procedure and related energy
conservation standards to certain types
of equipment;
2. the definitions of ‘‘hybrid
commercial refrigeration equipment,’’
‘‘commercial refrigeration equipment
with drawers,’’ and ‘‘commercial
refrigeration equipment with solid and/
or transparent doors’’;
3. the relationship among the rating
temperature, operating temperature, and
integrated average temperature;
4. the proper configuration and use of
energy management systems, lighting
controls, and test packages in the DOE
test procedure for commercial
refrigeration equipment;
5. the treatment of various features,
components, and accessories under the
DOE test procedure;
6. the rounding requirements for test
results and certified ratings;
7. the provision adopted in the 2012
test procedure final rule to allow testing
at the lowest application product
temperature for equipment that cannot
operate at the prescribed rating
temperature for its equipment class;
8. clarifications raised by
Interpretations 1, 2, 3, 4, and 5 of AHRI
1200–2010;
9. the methodology used to determine
total display area; and
10. the compliance date of certain
amendments established in the 2012 test
procedure final rule.
All commercial refrigeration
equipment covered by this rule is
currently required to be tested using the
DOE test procedure to show compliance
with established energy conservation
standards. The DOE test procedure
manufacturers must use to demonstrate
compliance with existing standards is
that established in the 2006 test
procedure final rule, which references
ARI 1200–2006 and AHAM HRF–1–
2004. This test procedure consists of
one 24-hour test at standard rating
conditions to determine daily energy
consumption.
The 2012 test procedure final rule
amends the test procedure for
commercial refrigeration equipment to
update the referenced industry test
procedures to their most current
versions (AHRI 1200–2010 and AHAM
HRF–1–2008); incorporates provisions
for testing certain energy efficiency
features, including night curtains and
lighting occupancy sensor and
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
scheduled controls; and provides a test
procedure for specialty equipment that
cannot be tested at the prescribed rating
temperature. As part of that rulemaking,
DOE considered the burden associated
with the test procedure amendments
and certified that the rule would not
have a ‘‘significant economic impact on
a substantial number of small entities,’’
and the preparation of a regulatory
flexibility analysis was not warranted.
77 FR at 10314–10316 (Feb. 21, 2012).
The test procedure amendments
adopted in this final rule only
reorganize and clarify the existing
requirements in the DOE test procedure,
both those established in the 2006 test
procedure final rule and those
established in the 2012 test procedure
final rule; they do not alter or affect any
of the test procedure requirements or
provisions in any way. DOE does not
believe that the proposed test procedure
amendments would affect the way in
which any covered commercial
refrigeration equipment is tested, nor
would they increase the burden of
conducting such a test.
Rather, some of the provisions
adopted in this final rule will reduce the
burden associated with testing and
certifying commercial refrigeration
equipment. Specifically, this final rule
allows manufacturers to reduce burden
by testing and certifying equipment and
internal and ambient test conditions
that satisfy both the DOE test procedure
and the NSF–7 test procedure effective
30 days after publication of this final
rule in the Federal Register. This may
significantly decrease the amount of
testing manufacturers must do to
demonstrate compliance with both
programs.
DOE also notes that the amendments
regarding the treatment of various
features, components, and accessories
under the DOE test procedure were the
result of a series of negotiations that
occurred between DOE, manufacturers,
and energy efficiency advocates and,
thus, represent a mutually agreed upon
approach for each of these features. DOE
believes adoption of these clarifications
will streamline testing and make DOE’s
test procedure easier and more
straightforward to implement.
The negotiations also resulted in a
recently published final rule adopting
amended regulations governing AEDMs,
basic model definition, and compliance
for commercial HVAC, refrigeration, and
WH equipment. The AEDM provisions
allow an alternative method for
determining compliance in lieu of
conducting actual physical testing. 78
FR 79579, 79590. Commercial
refrigeration equipment previously were
required to test two units of each basic
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
22305
model, so the addition of an AEDM
option reduces the number of units for
which manufacturers will need to
conduct this test procedure. The 2013
AEDM final rule also clarified its basic
model definitions, which give
manufacturers the flexibility to group
individual models based on certain
characteristics into an individual basic
model for the purposes of demonstrating
compliance with DOE’s energy
conservation standards. DOE notes that
the AEDM and basic model provisions
adopted in the 2013 AEDM final rule
will reduce the burden of demonstrating
compliance with DOE’s energy
conservation standards in general, such
that the burden estimates for testing
discussed here represent a worse case.
The specific reductions in burden
accomplished in the 2013 AEDM final
rule are discussed in more detail in that
rule. 78 FR 79590–79591 (Dec. 31,
2013).
Based on this factual basis, DOE
continues to certify that this rule will
not have a ‘‘significant economic impact
on a substantial number of small
entities,’’ and the preparation of a
regulatory flexibility analysis is not
warranted. DOE has transmitted the
certification and supporting statement
of factual basis to the Chief Counsel for
Advocacy of the Small Business
Administration for review under 5
U.S.C. 605(b).
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of commercial
refrigeration equipment must certify to
DOE that their products comply with
any applicable energy conservation
standards. In certifying compliance,
manufacturers must test their products
according to the DOE test procedure for
commercial refrigeration equipment,
including any amendments adopted for
that test procedure. DOE has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including
commercial refrigeration equipment. 76
FR 12422 (March 7, 2011). The
collection-of-information requirement
for the certification and recordkeeping
is subject to review and approval by
OMB under the Paperwork Reduction
Act (PRA). This requirement has been
approved by OMB under OMB Control
Number 1910–1400. Public reporting
burden for the certification is estimated
to average 20 hours per response,
including the time for reviewing
instructions, searching existing data
sources, gathering and maintaining the
data needed, and completing and
reviewing the collection of information.
E:\FR\FM\21APR2.SGM
21APR2
22306
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
mstockstill on DSK4VPTVN1PROD with RULES2
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE amends its test
procedure for commercial refrigeration
equipment. DOE has determined that
this rule falls into a class of actions that
are categorically excluded from review
under the National Environmental
Policy Act of 1969 (NEPA; 42 U.S.C.
4321 et seq.). The rule is covered by
Categorical Exclusion A5, for
rulemakings that interpret or amend an
existing rule without changing the
environmental effect, as set forth in
DOE’s NEPA regulations in appendix A
to subpart D, 10 CFR part 1021. This
rule will not affect the quality or
distribution of energy usage and
therefore will not result in any
environmental impacts. Accordingly,
neither an environmental assessment
nor an environmental impact statement
is required.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (Aug. 4, 1999), imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have Federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have Federalism implications. On
March 14, 2000, DOE published a
statement of policy describing the
intergovernmental consultation process
it will follow in the development of
such regulations. 65 FR at 13735 (March
14, 2000). DOE has examined this final
rule and has determined that it would
not have a substantial direct effect on
the States, on the relationship between
the national government and the States,
or on the distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of this
final rule. States can petition DOE for
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
exemption from such preemption to the
extent, and based on criteria, set forth in
EPCA. (42 U.S.C. 6297(d)) No further
action is required by Executive Order
13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, the final rule
meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA; Pub. 104–
4 sec. 201 (codified at 2 U.S.C. 1531)
requires each Federal agency to assess
the effects of Federal regulatory actions
on State, local, and Tribal governments
and the private sector. For proposed
regulatory actions likely to result in a
rule that may cause expenditures by
State, local, and Tribal governments in
the aggregate or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish estimates of the resulting
costs, benefits, and other effects on the
national economy. (2 U.S.C. 1532(a), (b))
The UMRA also requires a Federal
agency to develop an effective process
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
to permit timely input by elected
officers of State, local, and Tribal
governments on a proposed ‘‘significant
intergovernmental mandate’’ and
requires an agency plan for giving notice
and opportunity for timely input to
potentially affected small governments
before establishing any requirements
that might significantly or uniquely
affect small governments. On March 18,
1997, DOE published a statement of
policy on its process for
intergovernmental consultation under
UMRA. 62 FR 12820. (This policy is
also available at https://energy.gov/gc/
office-general-counsel.) DOE reviewed
this final rule pursuant to UMRA and its
policy and determined that the rule
contains neither an intergovernmental
mandate nor a mandate that may result
in the expenditure of $100 million or
more in any year, so these requirements
do not apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
final rule would not have any impact on
the autonomy or integrity of the family
as an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 15, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516, note)
provides for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. The OMB’s
guidelines were published in 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published in 67 FR
62446 (Oct. 7, 2002). DOE has reviewed
this final rule under the OMB and DOE
guidelines and has concluded that it is
consistent with applicable policies in
those guidelines.
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OIRA, Office of
Management and Budget, a Statement of
Energy Effects for any proposed
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgated or is
expected to lead to promulgation of a
final rule, and that (1) is a significant
regulatory action under Executive Order
12866, or any successor order; and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy; or (3) is designated by the
Administrator of OIRA as a significant
energy action. For any proposed
significant energy action, the agency
must give a detailed statement of any
adverse effects on energy supply,
distribution, or use should the proposal
be implemented, and of reasonable
alternatives to the action and their
expected benefits on energy supply,
distribution, and use. This regulatory
action would not have a significant
adverse effect on the supply,
distribution, or use of energy and
therefore it is not a significant energy
action. Accordingly, DOE has not
prepared a Statement of Energy Effects.
mstockstill on DSK4VPTVN1PROD with RULES2
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91), DOE must comply with section 32
of the Federal Energy Administration
Act of 1974 (Pub. L. 93–275), as
amended by the Federal Energy
Administration Authorization Act of
1977. When a proposed rule contains or
involves use of commercial standards,
the rulemaking must inform the public
of the use and background of such
standards. (15 U.S.C. 788 Section 32)
This final rule incorporates testing
methods contained in ASTM Standard E
1084–86 (Reapproved 2009), ‘‘Standard
Test Method for Solar Transmittance
(Terrestrial) of Sheet Materials Using
Sunlight,’’ and ASHRAE 72–2005,
‘‘Method of Testing Commercial
Refrigerators and Freezers.’’ DOE has
evaluated these standards and is unable
to conclude whether they fully comply
with the requirements of section 323(b)
of the Federal Energy Administration
Act (i.e., whether they were developed
in a manner that fully provides for
public participation, comment, and
review).
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
As required by section 32(c) of the
Federal Energy Administration Act of
1974 as amended, DOE has consulted
with the Attorney General and the
Chairman of the Federal Trade
Commission about the impact on
competition of using the methods
contained in these standards before
prescribing a final rule.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of this rule before its effective date. The
report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
List of Subjects
10 CFR Part 429
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Reporting and
recordkeeping requirements.
10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Small
businesses.
Issued in Washington, DC, on April 10,
2014.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
For the reasons set forth in the
preamble, DOE amends parts 429 and
431 of chapter II of title 10, of the Code
of Federal Regulations, as set forth
below:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
§ 429.42
[Amended]
2. Section 429.42 is amended by
adding in paragraphs (b)(2)(i), (ii), and
(iii), the words ‘‘increments of 0.01’’
before the phrase ‘‘kilowatt hours per
day (kWh/day).’’
■
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
22307
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
3. The authority citation for part 431
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
4. Section 431.62 is amended by:
a. Removing the definition for
‘‘commercial hybrid refrigerator, freezer,
and refrigerator-freezer’’;
■ b. Adding in alphabetical order the
definitions for ‘‘chef base or griddle
stand,’’ ‘‘closed solid,’’ ‘‘closed
transparent,’’ ‘‘commercial freezer,’’
‘‘commercial hybrid,’’ ‘‘commercial
refrigerator,’’ ‘‘commercial refrigeratorfreezer,’’ ‘‘door,’’ ‘‘operating
temperature,’’ ‘‘rating temperature,’’ and
’’transparent’’; and
■ c. Revising the definitions for ‘‘icecream freezer’’ and ‘‘lowest application
product temperature.’’
The additions and revision read as
follows:
■
■
§ 431.62 Definitions concerning
commercial refrigerators, freezers and
refrigerator-freezers.
*
*
*
*
*
Chef base or griddle stand means
commercial refrigeration equipment that
is designed and marketed for the
express purpose of having a griddle or
other cooking appliance placed on top
of it that is capable of reaching
temperatures hot enough to cook food.
Closed solid means equipment with
doors, and in which more than 75
percent of the outer surface area of all
doors on a unit are not transparent.
Closed transparent means equipment
with doors, and in which 25 percent or
more of the outer surface area of all
doors on the unit are transparent.
Commercial freezer means a unit of
commercial refrigeration equipment in
which all refrigerated compartments in
the unit are capable of operating below
32 °F (±2 °F).
Commercial hybrid means a unit of
commercial refrigeration equipment:
(1) That consists of two or more
thermally separated refrigerated
compartments that are in two or more
different equipment families, and
(2) That is sold as a single unit.
Commercial refrigerator means a unit
of commercial refrigeration equipment
in which all refrigerated compartments
in the unit are capable of operating at or
above 32 °F (±2 °F).
Commercial refrigerator-freezer means
a unit of commercial refrigeration
equipment consisting of two or more
refrigerated compartments where at
least one refrigerated compartment is
E:\FR\FM\21APR2.SGM
21APR2
mstockstill on DSK4VPTVN1PROD with RULES2
22308
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
capable of operating at or above 32 °F
(±2 °F) and at least one refrigerated
compartment is capable of operating
below 32 °F (±2 °F).
*
*
*
*
*
Door means a movable panel that
separates the interior volume of a unit
of commercial refrigeration equipment
from the ambient environment and is
designed to facilitate access to the
refrigerated space for the purpose of
loading and unloading product. This
includes hinged doors, sliding doors,
and drawers. This does not include
night curtains.
*
*
*
*
*
Ice-cream freezer means a commercial
freezer that is designed to operate at or
below ¥5 °F (±2 °F) (¥21 °C ± 1.1 °C)
and that the manufacturer designs,
markets, or intends for the storing,
displaying, or dispensing of ice cream.
*
*
*
*
*
Lowest application product
temperature means the lowest
integrated average temperature at which
a given basic model is capable of
consistently operating (i.e., maintaining
so as to comply with the steady-state
stabilization requirements specified in
ASHRAE 72–2005 (incorporated by
reference, see § 431.63) for the purposes
of testing under the DOE test
procedure).
*
*
*
*
*
Operating temperature means the
range of integrated average temperatures
at which a self-contained commercial
refrigeration unit or remote-condensing
commercial refrigeration unit with a
thermostat is capable of operating or, in
the case of a remote-condensing
commercial refrigeration unit without a
thermostat, the range of integrated
average temperatures at which the unit
is marketed, designed, or intended to
operate.
*
*
*
*
*
Rating temperature means the
integrated average temperature a unit
must maintain during testing (i.e., either
as listed in the table at § 431.66(d)(1) or
the lowest application product
temperature).
*
*
*
*
*
Transparent means greater than or
equal to 45 percent light transmittance,
as determined in accordance with the
ASTM Standard E 1084–86 (Reapproved
2009), (incorporated by reference, see
§ 431.63) at normal incidence and in the
intended direction of viewing.
*
*
*
*
*
■ 5. Section 431.63 is amended by:
■ a. Removing ‘‘for § 431.64’’ in
paragraphs (b)(1) and (b)(2) and adding
in its place, ‘‘for § 431.64 and
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
appendices A and B to subpart C to part
431’’;
■ b. Removing ‘‘and 431.66’’ in
paragraphs (c)(1) and (2) and adding in
its place, ‘‘431.66, and appendices A
and B to subpart C of part 431’’; and
■ c. Adding paragraphs (d) and (e) to
read as follows:
§ 431.63 Materials incorporated by
reference.
*
*
*
*
*
(d) ASHRAE. The American Society of
Heating, Refrigerating, and AirConditioning Engineers, Inc., 1971
Tullie Circle NE., Atlanta, GA 30329, or
https://www.ashrae.org/.
(1) ANSI/ASHRAE Standard 72–2005,
(ASHRAE 72–2005), ‘‘Method of Testing
Commercial Refrigerators and Freezers,’’
Copyright 2005, IBR approved for
§ 431.62, and appendices A and B to
subpart C of part 431.
(2) [Reserved]
(e) ASTM. ASTM International, 100
Barr Harbor Drive, P.O. Box C700, West
Conshohocken, PA 19428, (877) 909–
2786, or go to https://www.astm.org/.
(1) ASTM E 1084 (Reapproved 2009),
‘‘Standard Test Method for Solar
Transmittance (Terrestrial) of Sheet
Materials Using Sunlight,’’ approved
April 1, 2009, IBR approved for
§ 431.62.
(2) [Reserved]
■ 6. Section 431.64 is amended by
revising paragraph (b) to read as follows:
§ 431.64 Uniform test method for the
measurement of energy consumption of
commercial refrigerators, freezers, and
refrigerator-freezers.
*
*
*
*
*
(b) Testing and calculations.
Determine the daily energy
consumption of each covered
commercial refrigerator, freezer, or
refrigerator-freezer by conducting the
appropriate test procedure set forth
below, in appendix A or B to this
subpart. The daily energy consumption
of commercial refrigeration equipment
shall be calculated using raw measured
values and the final test results shall be
reported in increments of 0.01 kWh/day.
■ 7. Section 431.66 is amended by:
■ a. In the table in paragraph (d)(1)
removing every instance of ‘‘≥32’’ and
adding in its place ‘‘≥32 ±2’’, removing
every instance of ‘‘<32’’ and adding in
its place ‘‘<32 ±2’’, and removing
‘‘≤¥5**’’ and adding in its place ‘‘≤¥5
±2**’’
■ b. Adding paragraph (f) to read as
follows:
§ 431.66 Energy conservation standards
and their effective dates.
*
PO 00000
*
*
Frm 00032
*
Fmt 4701
*
Sfmt 4700
(f) Exclusions. The energy
conservation standards in paragraphs (b)
through (e) of this section do not apply
to salad bars, buffet tables, and chef
bases or griddle stands.
■ 8. Add appendices A and B to subpart
C of part 431 to read as follows:
Appendix A to Subpart C of Part 431—
Uniform Test Method for the Measurement
of Energy Consumption of Commercial
Refrigerators, Freezers, and RefrigeratorFreezers
Note: After October 20, 2014 but before
March 28, 2017, any representations made
with respect to the energy use or efficiency
of commercial refrigeration equipment must
be made in accordance with the results of
testing pursuant to this appendix.
Manufacturers conducting tests of
commercial refrigeration equipment after
May 21, 2014 and prior to October 20, 2014,
must conduct such test in accordance with
either this appendix or § 431.64 as it
appeared at 10 CFR part 430, subpart B, in
the 10 CFR parts 200 to 499 edition revised
as of January 1, 2014. Any representations
made with respect to the energy use or
efficiency of such commercial refrigeration
equipment must be in accordance with
whichever version is selected. Given that
after October 20, 2014 representations with
respect to the energy use or efficiency of
commercial refrigeration equipment must be
made in accordance with tests conducted
pursuant to this appendix, manufacturers
may wish to begin using this test procedure
as soon as possible.
1. Test Procedure
1.1. Determination of Daily Energy
Consumption. Determine the daily energy
consumption of each covered commercial
refrigerator, freezer, refrigerator-freezer or
ice-cream freezer by conducting the test
procedure set forth in the Air-Conditioning
and Refrigeration Institute (ARI) Standard
1200–2006, ‘‘Performance Rating of
Commercial Refrigerated Display
Merchandisers and Storage Cabinets,’’
section 3, ‘‘Definitions,’’ section 4, ‘‘Test
Requirements,’’ and section 7, ‘‘Symbols and
Subscripts’’ (incorporated by reference, see
§ 431.63). For each commercial refrigerator,
freezer, or refrigerator-freezer with a selfcontained condensing unit, also use ARI
Standard 1200–2006, section 6, ‘‘Rating
Requirements for Self-contained Commercial
Refrigerated Display Merchandisers and
Storage Cabinets.’’ For each commercial
refrigerator, freezer, or refrigerator-freezer
with a remote condensing unit, also use ARI
Standard 1200–2006, section 5, ‘‘Rating
Requirements for Remote Commercial
Refrigerated Display Merchandisers and
Storage Cabinets.’’
1.2. Methodology for Determining
Applicability of Transparent Door Equipment
Families. To determine if a door for a given
model of commercial refrigeration equipment
is transparent: (1) Calculate the outer door
surface area including frames and mullions;
(2) calculate the transparent surface area
within the outer door surface area excluding
frames and mullions; (3) calculate the ratio
E:\FR\FM\21APR2.SGM
21APR2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
of (2) to (1) for each of the outer doors; and
(4) the ratio for the transparent surface area
of all outer doors must be greater than 0.25
to qualify as a transparent equipment family.
1.3. Additional Specifications for Testing
of Components and Accessories. Subject to
the provisions regarding specific components
and accessories listed below, all standard
components that would be used during
normal operation of the basic model in the
field shall be installed and in operation
during testing as recommended by the
manufacturer and representative of their
typical operation in the field unless such
installation and operation is inconsistent
with any requirement of the test procedure.
The specific components and accessories
listed in the subsequent sections shall be
operated as stated during the test.
1.3.1. Energy Management Systems.
Applicable energy management systems may
be activated during the test procedure
provided they are permanently installed on
the case, configured as sold and in such a
manner so as to operate automatically
without the intervention of the operator, and
do not conflict with any of other
requirements for a valid test as specified in
this appendix.
1.3.2. Lighting. Energize all lighting, except
customer display signs/lights as described in
section 1.3.3 and UV lighting as described in
section 1.3.6 of this appendix, to the
maximum illumination level for the duration
of testing. However, if a closed solid unit of
commercial refrigeration equipment includes
an automatic lighting control system that can
turn off internal case lighting when the door
is closed, and the manufacturer recommends
the use of this system in writing in the
product literature delivered with the unit,
then the lighting control should be operated
in the automatic setting, even if the model
has a manual switch that disables the
automatic lighting control.
1.3.3. Customer display signs/lights. Do not
energize supplemental lighting that exists
solely for the purposes of advertising or
drawing attention to the case and is not
integral to the operation of the case.
1.3.4. Condensate pan heaters and pumps.
For self-contained equipment only, all
electric resistance condensate heaters and
condensate pumps must be installed and
operational during the test. This includes the
stabilization period (including pull-down),
steady-state, and performance testing
periods. Prior to the start of the stabilization
period as defined by ASHRAE 72–2005
(incorporated by reference, see § 431.63), the
condensate pan must be dry. Following the
start of the stabilization period, allow any
condensate moisture generated to accumulate
in the pan. Do not manually add or remove
water from the condensate pan at any time
during the test.
1.3.5. Anti-sweat door heaters. Anti-sweat
door heaters must be in operation during the
entirety of the test procedure. Models with a
user-selectable setting must have the heaters
energized and set to the maximum usage
position. Models featuring an automatic, nonuser-adjustable controller that turns on or off
based on environmental conditions must be
operating in the automatic state. If a unit is
not shipped with a controller from the point
of manufacture and is intended to be used
with an automatic, non-user-adjustable
controller, test the unit with a manufacturerrecommended controller that turns on or off
based on environmental conditions.
1.3.6. Ultraviolet lights. Do not energize
ultraviolet lights during the test.
1.3.7. Illuminated temperature displays
and alarms. All illuminated temperature
displays and alarms shall be energized and
operated during the test as they would be
during normal field operation.
1.3.8. Condenser filters. Remove any
nonpermanent filters that are provided to
prevent particulates from blocking a model’s
condenser coil.
Category
1.3.9. Refrigeration system security covers.
Remove any devices used to secure the
condensing unit against unwanted removal.
1.3.10. Night curtains and covers. Do not
deploy night curtains or covers.
1.3.11. Grill options. Remove any optional,
non-standard grills used to direct airflow.
1.3.12. Misting or humidification systems.
Misting or humidification systems must be
inactive during the test.
1.3.13. Air purifiers. Air purifiers must be
inactive during the test.
1.3.14. General purpose outlets. During the
test, do not connect any external load to any
general purpose outlets contained within a
unit.
1.3.15. Crankcase heaters. Crankcase
heaters must be operational during the test.
If a control system, such as a thermostat or
electronic controller, is used to modulate the
operation of the crankcase heater, it must be
activated during the test.
1.3.16. Drawers. Drawers are to be treated
as identical to doors when conducting the
DOE test procedure. Commercial refrigeration
equipment with drawers should be
configured with the drawer pans that allow
for the maximum packing of test simulators
and filler packages without the filler
packages and test simulators exceeding 90
percent of the refrigerated volume. Packing of
test simulators and filler packages shall be in
accordance with the requirements for
commercial refrigerators without shelves, as
specified in section 6.2.3 of ASHRAE 72–
2005 (incorporated by reference, see
§ 431.63).
2. Test Conditions
2.1. Integrated Average Temperatures.
Conduct the testing required in section 1 and
2 of this appendix A, and determine the daily
energy consumption at the applicable
integrated average temperature as found in
the following table.
Test procedure
(i) Refrigerator with Solid Door(s) ...............................................................................
(ii) Refrigerator with Transparent Door(s) ..................................................................
(iii) Freezer with Solid Door(s) ....................................................................................
(iv) Freezer with Transparent Door(s) ........................................................................
(v) Refrigerator-Freezer with Solid Door(s) ................................................................
ARI Standard
1200–2006 1
ARI Standard
1200–2006 1
ARI Standard
1200–2006 1
ARI Standard
1200–2006 1
ARI Standard
1200–2006 1
38 °F (±2 °F).
....
38 °F (±2 °F).
....
0 °F (±2 °F).
....
0 °F (±2 °F).
....
38 °F (±2 °F) for refrigerator compartment. 0 °F (±2 °F) for freezer compartment.
38 °F (±2 °F).
ARI Standard ....
1200–2006 1
ARI Standard ....
1200–2006 1
ARI Standard ....
1200–2006 1
(ix) Commercial Refrigerator, Freezer, and Refrigerator-Freezer with a Remote
Condensing Unit.
ARI Standard ....
1200–2006 1
1 Incorporated
VerDate Mar<15>2010
Integrated average temperature
....
(viii) Commercial Refrigerator, Freezer, and Refrigerator-Freezer with a Self-Contained Condensing Unit and without Doors.
mstockstill on DSK4VPTVN1PROD with RULES2
(vi) Commercial Refrigerator with a Self-Contained Condensing Unit Designed for
Pull-Down Temperature Applications and Transparent Doors.
(vii) Ice-Cream Freezer ...............................................................................................
¥15.0 °F (±2 °F).
(A) 0 °F (±2 °F) for low temperature applications.
(B) 38 °F (±2 °F) for medium temperature applications.
(A) 0 °F (±2 °F) for low temperature applications.
(B) 38 °F (±2 °F) for medium temperature applications.
by reference, see § 431.63.
18:57 Apr 18, 2014
Jkt 232001
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
22309
E:\FR\FM\21APR2.SGM
21APR2
22310
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
mstockstill on DSK4VPTVN1PROD with RULES2
2.2. Lowest Application Product
Temperature. If a unit of commercial
refrigeration equipment is not able to be
operated at the integrated average
temperature specified in the table in
paragraph 2.1, test the unit at the lowest
application product temperature (LAPT), as
defined in § 431.62. For units equipped with
a thermostat, LAPT is the lowest thermostat
setting. For remote condensing equipment
without a thermostat or other means of
controlling temperature at the case, the
lowest application product temperature is the
temperature achieved with the dew point
temperature (as defined in AHRI Standard
1200 (I–P)-2010 (incorporated by reference
see § 431.63)) set to 5 degrees colder than that
required to maintain the manufacturer’s
lowest specified operating temperature.
2.3. Testing at NSF Test Conditions. For
commercial refrigeration equipment that is
also tested in accordance with NSF test
procedures (Type I and Type II), integrated
average temperatures and ambient conditions
used for NSF testing may be used in place
of the DOE-prescribed integrated average
temperatures and ambient conditions
provided they result in a more stringent test.
That is, the measured daily energy
consumption of the same unit, when tested
at the rating temperatures and/or ambient
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
conditions specified in the DOE test
procedure, must be lower than or equal to the
measured daily energy consumption of the
unit when tested with the rating
temperatures or ambient conditions used for
NSF testing. The integrated average
temperature measured during the test may be
lower than the range specified by the DOE
applicable temperature specification
provided in paragraph 2.1 of this appendix,
but may not exceed the upper value of the
specified range. Ambient temperatures and/
or humidity values may be higher than those
specified in the DOE test procedure.
3. Volume and Total Display Area
3.1. Determination of Volume. Determine
the volume of a commercial refrigerator,
freezer, refrigerator-freezer, or ice-cream
freezer using the method set forth in the
ANSI/AHAM HRF–1–2004, ‘‘Energy,
Performance and Capacity of Household
Refrigerators, Refrigerator-Freezers and
Freezers’’ (incorporated by reference, see
§ 431.63), section 3.21, ‘‘Volume,’’ sections
4.1 through 4.3, ‘‘Method for Computing
Total Refrigerated Volume and Total Shelf
Area of Household Refrigerators and
Household Wine Chillers,’’ and sections 5.1
through 5.3, ‘‘Method for Computing Total
Refrigerated Volume and Total Shelf Area of
Household Freezers.’’
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
3.2. Determination of Total Display Area.
Determine the total display area of a
commercial refrigerator, freezer, refrigeratorfreezer, or ice-cream freezer using the method
set forth in ARI Standard 1200–2006
(incorporated by reference, see § 431.63), but
disregarding the specification that
‘‘transparent material (≥65% light
transmittance) in Appendix D. Specifically,
total display area shall be the sum of the
projected area(s) of visible product,
expressed in ft 2 (i.e., portions through which
product can be viewed from an angle normal,
or perpendicular, to the transparent area).
Determine L as the interior length of the CRE
model, provided no more than 10 percent of
that length consists of non-transparent
material. For those cases with greater than 10
percent of non-transparent area, L shall be
determined as the projected linear
dimension(s) of visible product plus 10
percent of non-transparent area.
See Figures A3.1, A3.2, A3.3, A3.4, and
A3.5 as examples of how to calculate the
dimensions associated with calculation of
total display area. In the diagrams, Dh and L
represent the dimensions of the projected
visible product.
BILLING CODE 6450–01–P
E:\FR\FM\21APR2.SGM
21APR2
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
PO 00000
Frm 00035
Fmt 4701
Sfmt 4725
E:\FR\FM\21APR2.SGM
21APR2
22311
ER21AP14.000
mstockstill on DSK4VPTVN1PROD with RULES2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
VerDate Mar<15>2010
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
18:57 Apr 18, 2014
Jkt 232001
PO 00000
Frm 00036
Fmt 4701
Sfmt 4725
E:\FR\FM\21APR2.SGM
21APR2
ER21AP14.001
mstockstill on DSK4VPTVN1PROD with RULES2
22312
BILLING CODE 6450–01–C
Appendix B to Subpart C of Part 431—
Amended Uniform Test Method for the
Measurement of Energy Consumption of
Commercial Refrigerators, Freezers, and
Refrigerator-Freezers
Note: Any representations made on or after
March 28, 2017, with respect to the energy
use or efficiency of commercial refrigeration
equipment must be made in accordance with
the results of testing pursuant to this
appendix.
mstockstill on DSK4VPTVN1PROD with RULES2
1. Test Procedure
1.1. Determination of Daily Energy
Consumption. Determine the daily energy
consumption of each covered commercial
refrigerator, freezer, refrigerator-freezer or
ice-cream freezer by conducting the test
procedure set forth in the AHRI Standard
1200 (I–P)–2010, section 3, ‘‘Definitions,’’
section 4, ‘‘Test Requirements,’’ and section
7, ‘‘Symbols and Subscripts’’ (incorporated
by reference, see § 431.63). For each
commercial refrigerator, freezer, or
refrigerator-freezer with a self-contained
condensing unit, also use AHRI Standard
1200 (I–P)–2010, section 6, ‘‘Rating
Requirements for Self-contained Commercial
Refrigerated Display Merchandisers and
Storage Cabinets.’’ For each commercial
refrigerator, freezer, or refrigerator-freezer
with a remote condensing unit, also use
AHRI Standard 1200 (I–P)-2010, section 5,
‘‘Rating Requirements for Remote
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
Commercial Refrigerated Display
Merchandisers and Storage Cabinets.’’
1.2. Methodology for Determining
Applicability of Transparent Door Equipment
Families
To determine if a door for a given model
of commercial refrigeration equipment is
transparent: (1) Calculate the outer door
surface area including frames and mullions;
(2) calculate the transparent surface area
within the outer door surface area excluding
frames and mullions; (3) calculate the ratio
of (2) to (1) for each of the outer doors; and
(4) the ratio for the transparent surface area
of all outer doors must be greater than 0.25
to qualify as a transparent equipment family.
1.3. Additional Specifications for Testing
of Components and Accessories. All standard
components that would be used during
normal operation of the basic model in the
field shall be installed and used during
testing as recommended by the manufacturer
and representative of their typical operation
in the field unless such installation and
operation is inconsistent with any
requirement of the test procedure. The
specific components and accessories listed in
the subsequent sections shall be operated as
stated during the test.
1.3.1. Energy Management Systems.
Applicable energy management systems may
be activated during the test procedure
provided they are permanently installed on
the case, configured and sold in such a
manner so as to operate automatically
without the intervention of the operator, and
PO 00000
Frm 00037
Fmt 4701
Sfmt 4700
22313
do not conflict with any of other
requirements for a valid test as specified in
this appendix.
1.3.2. Lighting. All lighting except for
customer display signs/lights as described in
section 1.3.3 and UV lighting as described in
section 1.3.6 of this appendix shall be
energized to the maximum illumination level
for the duration of testing for commercial
refrigeration equipment with lighting except
when the unit is equipped with lighting
occupancy sensors and controls. If the unit
includes an automatic lighting control
system, it should be enabled during test. If
the unit is equipped with lighting occupancy
sensors and controls in should be tested in
accordance with section 1.3.2.1 of this
appendix.
1.3.2.1. Lighting Occupancy Sensors and
Controls. For units with lighting occupancy
sensors and/or scheduled lighting controls
installed on the unit, determine the effect of
the controls/sensors on daily energy
consumption by either a physical test or a
calculation method and using the variables
that are defined as:
CECA is the alternate compressor energy
consumption (kilowatt-hours);
LECsc is the lighting energy consumption of
internal case lights with lighting occupancy
sensors and controls deployed (kilowatthours);
Pli is the rated power of lights when they
are fully on (watts);
Pli(off) is the power of lights when they are
off (watts);
E:\FR\FM\21APR2.SGM
21APR2
ER21AP14.002
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
NETS
Operating temperature class
EER
Btu/W
mstockstill on DSK4VPTVN1PROD with RULES2
Medium .....................................
Low ...........................................
11
7
1.3.3. Customer display signs/lights. Do not
energize supplemental lighting that exists
solely for the purposes of advertising or
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
EER FOR SELF-CONTAINED COMMERCIAL REFRIGERATED DISPLAY MERCHANDISERS AND STORAGE CABINETS—Continued
Operating temperature class
EER
Btu/W
Ice Cream .................................
5
1.3.2.1.iii.C. For remote condensing units,
calculate the revised compressor energy
consumption (CECR) by adding the CECA to
the compressor energy consumption (CEC)
measured in AHRI Standard 1200 (I–P)–2010
(incorporated by reference, see § 431.63). The
CDEC for the entire case is the sum of the
drawing attention to the case and is not
integral to the operation of the case.
PO 00000
Frm 00038
Fmt 4701
Sfmt 4700
CECR and LECsc (as calculated above) and the
fan energy consumption (FEC), anticondensate energy consumption (AEC),
defrost energy consumption (DEC), and
condensate evaporator pan energy
consumption (PEC) (as measured in AHRI
Standard 1200 (I–P)–2010).
1.3.2.1.iii.D. For self-contained units, the
TDEC for the entire case is the sum of total
daily energy consumption as measured by
the AHRI Standard 1200 (I–P)–2010
(incorporated by reference, see § 431.63) test
with the lights fully on (TDECo) and CECA,
less the decrease in lighting energy use due
to lighting occupancy sensors and scheduled
lighting controls, as shown in following
equation.
1.3.4. Condensate pan heaters and pumps.
For self-contained equipment only, all
electric resistance condensate heaters and
E:\FR\FM\21APR2.SGM
21APR2
ER21AP14.006
EER FOR SELF-CONTAINED COMMERCIAL REFRIGERATED DISPLAY MERCHANDISERS AND STORAGE CABI-
The sum of tsc, toff, and tdim should equal
24 hours and the total time period during
which the lights are off or dimmed shall not
exceed 10.8 hours. For cases with scheduled
lighting controls, the time the case lighting is
off and/or dimmed due to scheduled lighting
controls (toff,controls and/or tdim,controls, as
applicable) shall not exceed 8 hours. For
cases with lighting occupancy sensors
installed, the time the case lighting is off
and/or dimmed due to lighting occupancy
sensors (toff,sensors and/or tdim,sensors, as
applicable) shall not exceed 10.8 hours. For
cases with lighting occupancy sensors and
scheduled lighting controls installed, the
time the case lighting is off and/or dimmed
due to lighting occupancy sensors (toff,sensors
and/or tdim,sensors, as applicable) shall not
exceed 2.8 hours and the time the case
lighting is off and/or dimmed due to
scheduled lighting controls (toff,controls and/or
tdim,controls, as applicable) shall not exceed 8
hours.
1.3.2.1.ii. If using a physical test to
determine the daily energy consumption,
turn off the lights for a time period
equivalent to toff and dim the lights for a time
period equal to tdim. If night curtains are also
being tested on the case, the period of lights
off and/or dimmed shall begin at the same
time that the night curtain is being deployed
and shall continue consecutively, in that
order, for the appropriate number of hours.
1.3.2.1.iii. If using a calculation method to
determine the daily energy consumption—
ER21AP14.005
Where EER represents the energy efficiency
ratio from Table 1 in AHRI Standard 1200 (I–
P)–2010 (incorporated by reference, see
§ 431.63) for remote condensing equipment
or the values shown in the following table for
self-contained equipment:
toff,sensors is the time case lighting is off due
to the use of lighting occupancy sensors
(hours); and
tsc is the time period when lighting is fully
on with lighting occupancy sensors and
scheduled lighting controls enabled (hours).
1.3.2.1.i. For both a physical test and a
calculation method, determine the estimated
time off or dimmed, toff or tdim, as the sum
of contributions from lighting occupancy
sensors and scheduled lighting controls that
dim or turn off lighting, respectively, as
shown in the following equation:
ER21AP14.004
Pli(dim) is the power of lights when they are
dimmed (watts);
TDECo is the total daily energy
consumption with lights fully on, as
measured by AHRI Standard 1200 (I–P)–2010
(kilowatt-hours);
tdim is the time period during which the
lights are dimmed due to the use of lighting
occupancy sensors or scheduled lighting
controls (hours);
tdim,controls is the time case lighting is
dimmed due to the use of lighting controls
(hours);
tdim,sensors is the time case lighting is
dimmed due to the use of lighting occupancy
sensors (hours);
tl is the time period when lights would be
on without lighting occupancy sensors and/
or scheduled lighting controls (24 hours);
toff is the time period during which the
lights are off due to the use of lighting
occupancy sensors and/or scheduled lighting
controls (hours);
toff,controls is the time case lighting is off due
to the use of scheduled lighting controls
(hours);
ER21AP14.003
22314
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
condensate pumps must be installed and in
operation during the test. This includes the
stabilization period (including pull-down),
steady-state, and performance testing
periods. Prior to the start of the stabilization
period as defined by ASHRAE 72–2005
(incorporated by reference, see § 431.63), the
condensate pan must be dry. Following the
start of the stabilization period, allow any
condensate moisture generated to accumulate
in the pan. Do not manually add or remove
water to or from the condensate pan at any
time during the test.
1.3.5. Anti-sweat door heaters. Anti-sweat
door heaters must be operational during the
entirety of the test procedure. Models with a
user-selectable setting must have the heaters
energized and set to the maximum usage
position. Models featuring an automatic, nonuser-adjustable controller that turns on or off
based on environmental conditions must be
operating in the automatic state. If a unit is
not shipped with a controller from the point
of manufacture and is intended to be used
with an automatic, non-user-adjustable
controller, test the unit with a manufacturerrecommended controller that turns on or off
based on environmental conditions.
1.3.6. Ultraviolet lights. Do not energize
ultraviolet lights during the test.
1.3.7. Illuminated temperature displays
and alarms. All illuminated temperature
displays and alarms shall be energized and
operated during the test as they would be
during normal field operation.
1.3.8. Condenser filters. Remove any
nonpermanent filters that are provided to
prevent particulates from blocking a model’s
condenser coil.
1.3.9. Refrigeration system security covers.
Remove any devices used to secure the
condensing unit against unwanted removal.
1.3.10. Night curtains and covers. For
display cases sold with night curtains
installed, the night curtain shall be employed
for 6 hours; beginning 3 hours after the start
of the first defrost period. Upon the
completion of the 6-hour period, the night
curtain shall be raised until the completion
of the 24-hour test period.
1.3.11. Grill options. Remove any optional
non-standard grills used to direct airflow.
1.3.12. Misting or humidification systems.
Misting or humidification systems must be
inactive during the test.
1.3.13. Air purifiers. Air purifiers must be
inactive during the test.
1.3.14. General purpose outlets. During the
test, do not connect any external load to any
general purpose outlets contained within a
unit.
1.3.15. Crankcase heaters. Crankcase
heaters must be operational during the test.
If a control system, such as a thermostat or
electronic controller, is used to modulate the
operation of the crankcase heater, it must be
utilized during the test.
1.3.16. Drawers. Drawers are to be treated
as identical to doors when conducting the
DOE test procedure. Commercial refrigeration
equipment with drawers should be
configured with the drawer pans that allow
for the maximum packing of test simulators
and filler packages without the filler
packages and test simulators exceeding 90
percent of the refrigerated volume. Packing of
test simulators and filler packages shall be in
accordance with the requirements for
commercial refrigerators without shelves, as
specified in section 6.2.3 of ASHRAE 72–
2005 (incorporated by reference, see
§ 431.63).
2. Test Conditions
2.1. Integrated Average Temperatures.
Conduct the testing required in section 1 of
this appendix B, and determine the daily
energy consumption at the applicable
integrated average temperature in the
following table.
Category
Test procedure
(i) Refrigerator with Solid Door(s) ...........................................................................................................
(ii) Refrigerator with Transparent Door(s) ...............................................................................................
(iii) Freezer with Solid Door(s) ................................................................................................................
(iv) Freezer with Transparent Door(s) .....................................................................................................
(v) Refrigerator-Freezer with Solid Door(s) .............................................................................................
(vi) Commercial Refrigerator with a Self-Contained Condensing Unit Designed for Pull-Down Temperature Applications and Transparent Doors.
(vii) Ice-Cream Freezer ...........................................................................................................................
(viii) Commercial Refrigerator, Freezer, and Refrigerator-Freezer with a Self-Contained Condensing
Unit and without Doors.
mstockstill on DSK4VPTVN1PROD with RULES2
(ix) Commercial Refrigerator, Freezer, and Refrigerator-Freezer with a Remote Condensing Unit ......
1 Incorporated
VerDate Mar<15>2010
AHRI Standard
1200 (I–P)–
2010 1.
AHRI Standard
1200 (I–P)–
2010 1.
AHRI Standard
1200 (I–P)–
2010 1.
AHRI Standard
1200 (I–P)–
2010 1.
AHRI Standard
1200 (I–P)–
2010 1.
AHRI Standard
1200 (I–P)–
2010 1.
AHRI Standard
1200 (I–P)–
2010 1.
AHRI Standard
1200 (I–P)–
2010 1.
AHRI Standard
1200 (I–P)–
2010 1.
by reference, see § 431.63.
18:57 Apr 18, 2014
Jkt 232001
PO 00000
Frm 00039
Fmt 4701
Sfmt 4700
22315
E:\FR\FM\21APR2.SGM
21APR2
Integrated average
temperature
38 °F (±2 °F).
38 °F (±2 °F).
0 °F (±2 °F).
0 °F (±2 °F).
38 °F (±2 °F) for refrigerator compartment.
0 °F (±2 °F) for
freezer compartment.
38 °F (±2 °F).
¥15.0 °F (±2 °F).
(A) 0 °F (±2 °F) for
low temperature
applications.
(B) 38.0 °F (±2 °F)
for medium temperature applications.
(A) 0 °F (±2 °F) for
low temperature
applications.
(B) 38.0 °F (±2 °F)
for medium temperature applications.
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
mstockstill on DSK4VPTVN1PROD with RULES2
2.2. Lowest Application Product
Temperature. If a unit of commercial
refrigeration equipment is not able to be
operated at the integrated average
temperature specified in the table in
paragraph 2.1 of this appendix, test the unit
at the lowest application product
temperature (LAPT), as defined in § 431.62.
For units equipped with a thermostat, LAPT
is the lowest thermostat setting. For remote
condensing equipment without a thermostat
or other means of controlling temperature at
the case, the lowest application product
temperature is the temperature achieved with
the dew point temperature (as defined in
AHRI Standard 1200 (I–P)–2010
(incorporated by reference, see § 431.63)) set
to 5 degrees colder than that required to
maintain the manufacturer’s lowest specified
application temperature.
2.3. Testing at NSF Test Conditions. For
commercial refrigeration equipment that is
also tested in accordance with NSF test
procedures (Type I and Type II), integrated
average temperatures and ambient conditions
used for NSF testing may be used in place
of the DOE-prescribed integrated average
temperatures and ambient conditions
provided they result in a more stringent test.
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
That is, the measured daily energy
consumption of the same unit, when tested
at the rating temperatures and/or ambient
conditions specified in the DOE test
procedure, must be lower than or equal to the
measured daily energy consumption of the
unit when tested with the rating
temperatures or ambient conditions used for
NSF testing. The integrated average
temperature measured during the test may be
lower than the range specified by the DOE
applicable temperature specification
provided in paragraph 2.1 of this appendix,
but may not exceed the upper value of the
specified range. Ambient temperatures and/
or humidity values may be higher than those
specified in the DOE test procedure.
3. Volume and Total Display Area
3.1. Determination of Volume. Determine
the volume of a commercial refrigerator,
freezer, refrigerator-freezer, or ice-cream
freezer using the method set forth in the
HRF–1–2008 (incorporated by reference, see
§ 431.63), section 3.30, ‘‘Volume,’’ and
sections 4.1 through 4.3, ‘‘Method for
Computing Refrigerated Volume of
Refrigerators, Refrigerator-Freezers, Wine
Chillers and Freezers.’’
PO 00000
Frm 00040
Fmt 4701
Sfmt 4725
3.2. Determination of Total Display Area.
Determine the total display area of a
commercial refrigerator, freezer, refrigeratorfreezer, or ice-cream freezer using the method
set forth in ARI Standard 1200–2006
(incorporated by reference, see § 431.63), but
disregarding the specification that
‘‘transparent material (≥65% light
transmittance) in Appendix D. Specifically,
total display area shall be the sum of the
projected area(s) of visible product,
expressed in ft2 (i.e., portions through which
product can be viewed from an angle normal,
or perpendicular, to the transparent area).
Determine L as the interior length of the CRE
model, provided no more than 5 inches of
that length consists of non-transparent
material. For those cases with greater than 5
inches of non-transparent area, L shall be
determined as the projected linear
dimension(s) of visible product plus 5 inches
of non-transparent area.
See Figures A3.1, A3.2, and A3.3 as
examples of how to calculate the dimensions
associated with calculation of total display
area. In the diagrams, Dh and L represent the
dimensions of the projected visible product.
BILLING CODE 4500–01–P
E:\FR\FM\21APR2.SGM
21APR2
ER21AP14.007
22316
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
PO 00000
Frm 00041
Fmt 4701
Sfmt 4725
E:\FR\FM\21APR2.SGM
21APR2
22317
ER21AP14.008
mstockstill on DSK4VPTVN1PROD with RULES2
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
Federal Register / Vol. 79, No. 76 / Monday, April 21, 2014 / Rules and Regulations
[FR Doc. 2014–08640 Filed 4–18–14; 8:45 am]
BILLING CODE 6450–01–C
VerDate Mar<15>2010
18:57 Apr 18, 2014
Jkt 232001
PO 00000
Frm 00042
Fmt 4701
Sfmt 9990
E:\FR\FM\21APR2.SGM
21APR2
ER21AP14.009
mstockstill on DSK4VPTVN1PROD with RULES2
22318
Agencies
[Federal Register Volume 79, Number 76 (Monday, April 21, 2014)]
[Rules and Regulations]
[Pages 22277-22318]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2014-08640]
[[Page 22277]]
Vol. 79
Monday,
No. 76
April 21, 2014
Part IV
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 431
Energy Conservation Program: Test Procedure for Commercial
Refrigeration Equipment; Final Rule
Federal Register / Vol. 79 , No. 76 / Monday, April 21, 2014 / Rules
and Regulations
[[Page 22278]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[Docket No. EERE-2013-BT-TP-0025]
RIN 1904-AC99
Energy Conservation Program: Test Procedure for Commercial
Refrigeration Equipment
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: In this final rule, the U.S. Department of Energy (DOE)
revises and reorganizes its test procedure for commercial refrigeration
equipment (CRE) to clarify certain terms, procedures, and compliance
dates to improve the repeatability and remove ambiguity from the CRE
test procedure. In this final rule, DOE also addresses a number of test
procedure clarifications that arose as a result of the negotiated
rulemaking process for certification of commercial heating,
ventilation, air conditioning, refrigeration, and water heating
equipment.
DATES: The effective date of this rule is May 21, 2014.
The incorporation by reference of certain publications listed in
this final rule is approved by the Director of the Office of the
Federal Register as of May 21, 2014.
ADDRESSES: The docket, which includes Federal Register notices, public
meeting attendee lists and transcripts, comments, and other supporting
documents/materials, is available for review at regulations.gov. All
documents in the docket are listed in the regulations.gov index.
However, some documents listed in the index, such as those containing
information that is exempt from public disclosure, may not be publicly
available.
A link to the docket Web page can be found at: https://www1.eere.energy.gov/buildings/appliance_standards/rulemaking.aspx?ruleid=80. This Web page will contain a link to the
docket for this rulemaking on the regulations.gov site. The
regulations.gov Web page will contain simple instructions on how to
access all documents, including public comments, in the docket.
For further information on how to review the docket, contact Ms.
Brenda Edwards at (202) 586-2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Ms. Ashley Armstrong, U.S. Department
of Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Office, EE-5B, 1000 Independence Avenue SW., Washington,
DC 20585-0121. Telephone: (202) 586-6590. Email: commercial_refrigeration_equipment@ee.doe.gov.
Ms. Jennifer Tiedeman, U.S. Department of Energy, Office of the
General Counsel, GC-71, 1000 Independence Avenue SW., Washington, DC
20585-0121. Telephone: (202) 287-6111. Email:
mailto:Jennifer.Tiedeman@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final rule incorporates by reference
into 10 CFR part 431 the following industry standards:
(1) ANSI/ASHRAE 72-2005, (``ASHRAE 72-2005''), ``Method of Testing
Commercial Refrigerators and Freezers,'' Copyright 2005.
(2) ASTM E 1084-86 (Reapproved 2009), ``Standard Test Method for
Solar Transmittance (Terrestrial) of Sheet Materials Using Sunlight,''
approved April 1, 2009.
Copies of ASHRAE standards may be purchased from the American
Society of Heating, Refrigerating, and Air-Conditioning Engineers,
Inc., 1971 Tullie Circle NE., Atlanta, GA 30329, or at www.ashrae.org/.
Copies of ASTM standards may be purchased from ASTM International,
100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428,
(877) 909-2786, or at www.astm.org/.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Summary of the Final Rule
III. Discussion
A. Amendments to the Test Procedure
1. Scope of Coverage
a. Salad Bars, Buffet Tables, and Other Refrigerated Holding and
Serving Equipment
b. Chef Bases and Griddle Stands
c. Existing Cases Undergoing Refurbishments or Retrofits
d. Case Doors Shipped as After-Market Additions
2. Definitions Pertinent to Commercial Refrigeration Equipment
a. Commercial Refrigeration Equipment With Drawers
b. Transparent and Solid Doors
c. Hybrid Equipment and Commercial Refrigerator-Freezers
3. Relationship Among Rating Temperature, Operating Temperature,
and Integrated Average Temperature
4. Proper Configuration and Use of Components or Features in the
DOE Test Procedure
a. Energy Management Systems
b. Lighting
c. Test Package Temperatures
5. Treatment of Other Specific Equipment Features and
Accessories During Testing
a. Customer Display Signs/Lights
b. Condensate Pan Heaters and Pumps
c. Anti-Sweat Door Heaters
d. Ultraviolet Lights
e. Illuminated Temperature Displays and Alarms
f. Condenser Filters
g. Refrigeration System Security Covers
h. Night Curtains and Covers
i. Grill Options
j. Coated Coils
k. Internal Secondary Coolant Circuits
l. Wedge Cases
m. Misting or Humidification Systems
n. Air Purifiers
o. General Purpose Outlets
p. Crankcase Heaters
q. Interior/Exterior Liners
r. Other Comments Received From Interested Parties
6. Rounding of Test Results and Certified Ratings
7. Testing at the Lowest Application Product Temperature
a. Definition of Lowest Application Product Temperature
b. Incorporation by Reference of ASHRAE 72-2005
8. Clarifications in Response to Interpretations to AHRI 1200-
2010
9. Clarification of Methodology for Measuring Total Display Area
10. Compliance Date of Test Procedure Amendments
B. Other Notice of Proposed Rulemaking Comments and DOE
Responses
1. Ambient Test Temperatures
2. Burden of Testing
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
V. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III, Part C of the Energy Policy and Conservation Act of 1975
(EPCA), Public Law 94-163 (42 U.S.C. 6311-6317, as codified), added by
Public Law 95-619, Title IV, Sec. 441(a), established the Energy
Conservation Program for Certain Industrial Equipment, a program
covering certain industrial equipment, which includes the commercial
refrigeration equipment that is the focus
[[Page 22279]]
of this final rule.\1\ All references to EPCA refer to the statute as
amended through the American Energy Manufacturing Technical Corrections
Act (AEMTCA), Public Law 112-210 (Dec. 18, 2012).
---------------------------------------------------------------------------
\1\ For editorial reasons, upon codification in the U.S. Code,
Part C was re-designated Part A-1.
---------------------------------------------------------------------------
Under EPCA, the energy conservation program consists essentially of
four parts: (1) Testing, (2) labeling, (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. The
testing requirements consist of test procedures that manufacturers of
covered equipment must use as the basis for (1) certifying to DOE that
their equipment complies with the applicable energy conservation
standards adopted under EPCA, (42 U.S.C. 6316(e)(1)), and (2) making
representations about the efficiency of that equipment. (42 U.S.C.
6314(d)) Similarly, DOE must use these test procedures to determine
whether the equipment complies with relevant standards promulgated
under EPCA. (42 U.S.C. 6316(e)(1))
General Test Procedure Rulemaking Process
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered equipment. EPCA provides, in relevant part, that any test
procedures prescribed or amended under this section shall be reasonably
designed to produce test results that reflect energy efficiency, energy
use and estimated annual operating costs of a covered product during a
representative average use cycle or period of use and shall not be
unduly burdensome to conduct. (42 U.S.C. 6314(a)(2))
In addition, if DOE determines that a test procedure amendment is
warranted, it must publish proposed test procedures and offer the
public an opportunity to present oral and written comments on them. (42
U.S.C. 6314(c)(2)) Finally, in any rulemaking to amend a test
procedure, DOE must determine to what extent, if any, the proposed test
procedure would alter the measured energy efficiency of any covered
product or equipment \2\ as determined under the existing test
procedure. If DOE determines that the amended test procedure would
alter the measured efficiency of a covered product, DOE must amend the
applicable energy conservation standard accordingly. (42 U.S.C.
6314(a)(6)(D))
---------------------------------------------------------------------------
\2\ The term ``covered product'' broadly refers to all types of
appliances and equipment regulated by DOE regardless of whether they
are consumer products or commercial and industrial equipment.
---------------------------------------------------------------------------
Under 42 U.S.C. 6314(c)(1), no later than 3 years after the date of
prescribing a test procedure pursuant to 42 U.S.C. 6314, and from time
to time thereafter, DOE is required to conduct a reevaluation and
determine whether to amend the test procedure. If DOE determines a test
procedure should be amended, it shall promptly publish in the Federal
Register proposed test procedures, incorporating such amendments and
affording interested persons an opportunity to present oral and written
data, views, and arguments. (42 U.S.C. 6314(c)(2))
In February 2012, DOE published a final rule (2012 test procedure
final rule) prescribing new amendments to the test procedure for
commercial refrigeration equipment. 77 FR 10291, 10318-21 (Feb. 21,
2012). Pursuant to EPCA's requirement in 42 U.S.C. 6314(c), DOE has
reevaluated the CRE test procedure and concluded that it should be
amended to clarify a number of provisions regarding how aspects of the
test are conducted, to more explicitly define some terms, and to more
clearly specify the compliance dates for various provisions. DOE's
adopted amendments to the test procedure are presented in this final
rule.
B. Background
EPCA mandates that the American Society of Heating, Refrigerating,
and Air-Conditioning Engineers (ASHRAE) Standard 117-2002, ``Method of
Testing Closed Refrigerators,'' shall be the initial test procedure for
the types of equipment to which standards are applicable under 42
U.S.C. 6313(c)(2)-(3). (42 U.S.C. 6314(a)(6)(A)(ii)) EPCA requires DOE
to address whether to amend its test procedures if ASHRAE amends this
standard. (42 U.S.C. 6314(a)(6)(E)-(F)) In 2005, ASHRAE combined
Standard 72-1998, ``Method of Testing Open Refrigerators,'' and
Standard 117-2002 and published the test method as ASHRAE Standard 72-
2005 (ASHRAE 72-2005), ``Method of Testing Commercial Refrigerators and
Freezers,'' which was approved by the American National Standards
Institute (ANSI) on July 29, 2005. Consistent with EPCA's requirement
in 42 U.S.C. 6314(a)(6)(E), DOE reviewed ASHRAE 72-2005, as well as
American Refrigeration Institute (ARI) Standard 1200-2006 (ARI 1200-
2006), which was approved by ANSI on August 28, 2006. DOE determined
that ARI 1200-2006 included by reference the test procedures in ASHRAE
72-2005 and the rating temperatures prescribed in EPCA. (42 U.S.C.
6314(a)(6)(B)) As a result, DOE published a final rule in December 2006
(2006 test procedure final rule) that adopted ARI 1200-2006 as the DOE
test procedure for commercial refrigeration equipment. 71 FR 71340,
71357 (Dec. 8, 2006). The 2006 test procedure final rule specified
rating temperatures of 38 [deg]F (2 [deg]F) for commercial
refrigerators and refrigerator compartments, 0 [deg]F (2
[deg]F) for commercial freezers and freezer compartments, and -15
[deg]F (2 [deg]F) for commercial ice-cream freezers. 71 FR
at 71370 (Dec. 8, 2006). DOE also adopted Association of Home Appliance
Manufacturers (AHAM) Standard HRF-1-2004, ``Energy, Performance and
Capacity of Household Refrigerators, Refrigerator-Freezers and
Freezers,'' for measuring compartment volumes for equipment covered
under the 2006 test procedure final rule. 71 FR at 71358 (Dec. 8,
2006). The test procedure established in the 2006 final rule became
effective on January 8, 2007 (71 FR at 71340), and its use has been
required to demonstrate compliance with the current energy conservation
standards.
More recently, on February 21, 2012, DOE published the
aforementioned 2012 test procedure final rule, in which it adopts
several amendments to the DOE test procedure for commercial
refrigeration equipment. These amendments include updating the standard
incorporated by reference in the DOE test procedure in response to the
relevant industry organizations issuing updated versions. Specifically,
DOE updated the incorporation by reference of Air-Conditioning,
Heating, and Refrigeration Institute (AHRI) Standard 1200 (I-P)-2010
(AHRI 1200-2010), ``Performance Rating of Commercial Refrigerated
Display Merchandisers and Storage Cabinets,'' as the DOE test procedure
for this equipment. 77 FR at 10318 (Feb. 21, 2012). The 2012 test
procedure final rule also includes an amendment to incorporate by
reference the updated ANSI/AHAM Standard HRF-1-2008 (AHAM HRF-1-2008),
``Energy, Performance, and Capacity of Household Refrigerators,
Refrigerator-Freezers, and Freezers,'' for determining compartment
volumes for this equipment. 77 FR at 10318 and 10321 (Feb. 21, 2012).
These updates were primarily editorial in nature and aligned the AHRI
test procedure with the nomenclature and methodology used in DOE's 2009
standards rulemaking on commercial refrigeration equipment. The updated
AHRI 1200-2010 also
[[Page 22280]]
references the most recent version of the AHAM standard, AHAM HRF-1-
2008.
In addition, the 2012 test procedure final rule includes several
amendments designed to address certain energy efficiency features that
were not accounted for by the previous DOE test procedure, including
provisions for measuring the impact of night curtains,\3\ lighting
occupancy sensors, and scheduled controls. 77 FR at 10296-10298 and
10319-10320 (Feb. 21, 2012). In the 2012 test procedure final rule, DOE
also adopts amendments to allow testing of commercial refrigeration
equipment that cannot operate at the rating temperature specified in
the DOE test procedure. Specifically, the 2012 test procedure final
rule allows testing of commercial refrigeration equipment at its lowest
application product temperature (LAPT), for equipment that is
physically incapable of reaching the prescribed rating temperature. 77
FR at 10320 (Feb. 21, 2012). The 2012 test procedure final rule also
allows manufacturers to test and certify equipment at the more-
stringent rating temperatures and ambient conditions required by NSF
\4\ for food safety testing. 77 FR at 10320-10321 (Feb. 21, 2012).
---------------------------------------------------------------------------
\3\ Night curtains are devices made of an insulating material,
typically insulated aluminum fabric, designed to be pulled down over
the open front of the case to decrease infiltration and heat
transfer into the case when the merchandizing establishment is
closed.
\4\ Founded in 1944 as the National Sanitation Foundation, the
organization is now referred to simply as NSF.
---------------------------------------------------------------------------
The test procedure amendments established in the 2012 test
procedure final rule became effective on March 22, 2012. 77 FR at 10292
(Feb. 21, 2012). The amendments are required to be used in conjunction
with the amended standards established in DOE's recently published
energy conservation standards final rule (March 2014 energy
conservation standards final rule) beginning on March 28, 2017. 79 FR
17726, 17727 (Mar. 28, 2014).
Since publication of the 2012 test procedure final rule, DOE has
received a number of inquiries from interested parties regarding DOE
regulations for commercial refrigeration equipment, including how
different types of equipment fit into DOE's definitions of commercial
refrigeration equipment at 10 CFR 431.62, and questions involving
certain provisions of the DOE test procedure at 10 CFR 431.64. More
specifically, DOE has received inquiries and questions regarding the
applicability of DOE's test procedure and Federal energy conservation
standards to particular models of commercial refrigeration equipment,
the proper configuration and use of certain components and features of
commercial refrigeration equipment for purposes of testing according to
the DOE test procedure, and the compliance date of the amendments
specified in the 2012 test procedure final rule. On October 28, 2013,
the U.S. Department of Energy (DOE) issued a notice of proposed
rulemaking (hereafter referred to as the October 2013 test procedure
NOPR) to amend the test procedure for commercial refrigeration
equipment (CRE) appearing at 10 CFR 431.64. 78 FR 64296 (Oct. 28,
2013). In the October 2013 test procedure NOPR, DOE presented proposed
amendments to address the questions presented by interested parties
and, where appropriate, proposed edits to the regulatory language to
clarify DOE's existing regulations. 78 FR at 64296 (Oct. 28, 2013).
On February 26, 2013, members of the Appliance Standards and
Rulemaking Federal Advisory Committee (ASRAC) unanimously decided to
form a working group to negotiate rulemaking on certification for
commercial heating, ventilation, and air-conditioning (HVAC);
commercial water heating (WH); and commercial refrigeration equipment.
A notice of intent to form the Commercial Certification Working Group
was published in the Federal Register on March 12, 2013 (Docket No.
EERE-2013-BT-NOC-0023). 78 FR 15653 (Mar. 12, 2013). DOE received 35
nominations for the Working Group. On April 16, 2013, DOE published a
notice of open meeting that announced the first meeting and listed the
22 nominees that were selected to serve as members of the Working
Group, in addition to two members from ASRAC, and one DOE
representative. 78 FR 22431 (Apr. 16, 2013). The members of the Working
Group were selected to ensure a broad and balanced array of stakeholder
interests and expertise, and include efficiency advocates,
manufacturers, a utility representative, and third party laboratory
representatives. As part of that rulemaking process, DOE conducted a
number of regulatory negotiation sessions over the course of the summer
of 2013 involving major stakeholders in the CRE market.\5\ One outcome
of these meetings was an agreement on the need to clarify aspects of
the DOE test procedure with respect to the treatment of specific
features of commercial refrigeration equipment. On August 30, 2013, the
Working Group submitted a report to ASRAC containing recommendations on
the certification requirements for HVAC, WH, and refrigeration
equipment (Docket No. EERE-2013-BT-NOC-0023, No. 51) and ASRAC voted
unanimously to accept these recommendations (Docket No. EERE-2013-BT-
NOC-0005, No. 13). In the October 2013 test procedure NOPR, DOE also
proposed clarifications of the treatment of those features by the DOE
test procedure. 78 FR at 64306-64308 (Oct. 28, 2013).
---------------------------------------------------------------------------
\5\ All of the details of the negotiation sessions can be found
in the public meeting transcripts that are posted to the docket for
the Working Group (www.regulations.gov/#!docketDetail;D=EERE-2013-
BT-NOC-0023).
---------------------------------------------------------------------------
On December 5, 2013, DOE held a public meeting (December 2013 NOPR
public meeting) to present the test procedure amendments proposed in
the October 2013 test procedure NOPR and accept comments from
interested parties. Interested parties submitted comments on the
ambient test conditions and the burden of testing and certification of
commercial refrigeration equipment. DOE analyzed all of the comments
received in response to the October 2013 test procedure NOPR and
incorporated recommendations, where appropriate, into this test
procedure final rule.
II. Summary of the Final Rule
In this final rule, DOE adopts amendments to clarify DOE's test
procedure provisions, definitions, the treatment of specific
accessories when testing under the DOE test procedure, and the
applicability of the existing test procedure and standards to different
types of commercial refrigeration equipment. Specifically, DOE is
adopting edits to definitions currently incorporated into the existing
DOE test procedure and including additional definitions to be
incorporated into the existing test procedure (reorganized into
appendix A to subpart C of 10 CFR part 431). DOE is also adopting edits
to definitions and including additional definitions to be incorporated
into the test procedure used to determine compliance with the amended
energy conservation standards adopted for commercial refrigeration
equipment on March 28, 2014 (reorganized into appendix B to subpart C
of 10 CFR part 431). 79 FR 17726. DOE does not believe that the test
procedure clarifications adopted in this final rule will affect the
measured energy use of any covered commercial refrigeration equipment
as they relate to the applicable energy conservation standards. Rather,
the additional definitions and amendments to the DOE test procedure for
commercial refrigeration equipment would serve only to clarify existing
nomenclature, testing provisions, compliance dates, and requirements
for
[[Page 22281]]
certain features and types of commercial refrigeration equipment; they
would not establish new requirements with regard to testing commercial
refrigeration equipment.
DOE notes that certification is not currently required for
commercial refrigeration equipment. On December 31, 2013, DOE published
a final rule adopting amended regulations governing alternative energy
determination methods (AEDMs), basic model definition, and the
compliance dates for certification of commercial HVAC, refrigeration,
and WH (2013 AEDM final rule). 78 FR 79579, 79590. The 2013 AEDM Final
Rule adopted a certification date of December 31, 2014, for self-
contained, closed solid, and closed transparent commercial
refrigeration equipment and a certification date of July 1, 2015, for
all other commercial refrigeration equipment. Id. DOE also recently
published a NOPR proposing, among other things, to revise and expand
the certification requirements for commercial refrigeration equipment.
79 FR 8886, 8899-8900 (Feb. 14, 2014). The specific proposals discussed
in the NOPR were developed as a result of the negotiations and
recommendations of the Working Group for commercial HVAC, WH, and
refrigeration equipment (Docket No. EERE-2013-BT-NOC-0023).
III. Discussion
Section III.A presents all of the revisions to the DOE test
procedure found at 10 CFR part 431, subpart C, ``Uniform test method
for measuring the energy consumption of commercial refrigerators,
freezers, and refrigerator-freezers,'' incorporated in this final rule,
and discusses the comments received on these topics during the December
2013 NOPR public meeting and the associated comment period. The changes
adopted as a result of this final rule include revisions addressing the
following:
1. The applicability of the test procedure and related energy
conservation standards to certain types of equipment;
2. the definitions of ``hybrid commercial refrigeration
equipment,'' ``commercial refrigeration equipment with drawers,'' and
``commercial refrigeration equipment with solid and/or transparent
doors'';
3. the relationship among the rating temperature, operating
temperature, and integrated average temperature (IAT);
4. the proper configuration and use of energy management systems,
lighting controls, and test packages in the DOE test procedure for
commercial refrigeration equipment;
5. the treatment of various features and components;
6. the rounding requirements for test results and certified
ratings;
7. the provision adopted in the 2012 test procedure final rule to
allow testing at the LAPT for equipment that cannot operate at the
prescribed rating temperature for its equipment class;
8. clarifications raised by AHRI's Interpretations 1, 2, 3, 4, and
5 of AHRI 1200-2010;
9. the methodology used to determine total display area (TDA); and
10. the compliance date of certain amendments established in the
2012 test procedure final rule.
In response to the October 2013 test procedure NOPR, DOE received
several comments from stakeholders that did not pertain to a specific
test procedure amendment. In section III.B, DOE provides responses to
comments pertaining to (1) the ambient test temperatures required in
the DOE test procedure and (2) the burden of testing and certifying
equipment as compliant with DOE's energy conservation standards.
A. Amendments to the Test Procedure
This final rule incorporates the following changes to the test
procedure for commercial refrigeration equipment in 10 CFR part 431,
subpart C.
1. Scope of Coverage
On October 18, 2005, DOE published a final rule adopting EPCA's
definition of commercial refrigeration equipment. This definition
includes seven provisions pertaining to the operational, functional,
and design characteristics of the equipment that must be met for a
piece of equipment to qualify as commercial refrigeration equipment. 70
FR 60407, 60414 (Oct. 18, 2005). This definition forms the basis of the
scope of coverage of DOE's regulations for commercial refrigeration
equipment. While the definition of commercial refrigeration equipment
encompasses a broad cross-section of commercial refrigeration equipment
types, DOE has only established energy conservation standards for
certain types of covered commercial refrigeration equipment specified
at 10 CFR 431.66, and these standards apply to all new equipment
distributed into U.S. commerce. 76 FR at 12426 and 12437 (March 7,
2011). There are also several types of equipment that meet the
definition of commercial refrigeration equipment for which DOE has not
yet set energy conservation standards. These include, for example,
buffet tables, salad bars, prep tables, and griddle stands.
EPCA and DOE regulations require manufacturers of commercial
refrigeration equipment to use the DOE test procedure for commercial
refrigeration equipment to evaluate compliance with any applicable
energy conservation standards and to support any representations as to
the energy use. The DOE test procedure for commercial refrigeration
equipment is set forth at 10 CFR 431.64.
In the October 2013 test procedure NOPR, DOE proposed
clarifications regarding the applicability of the current DOE energy
conservation standards and test procedure to specific equipment
categories, including the following:
i. Salad bars, buffet tables, and other refrigerated holding and
serving equipment;
ii. chef bases and griddle stands;
iii. existing cases undergoing refurbishments or retrofits; and
iv. cases with doors shipped as after-market accessories.
78 FR at 64299-64300 (Oct. 28, 2013).
a. Salad Bars, Buffet Tables, and Other Refrigerated Holding and
Serving Equipment
Salad bars, buffet tables, and other refrigerated holding and
serving equipment are types of commercial refrigeration equipment that
store and display perishable items temporarily during food preparation
or service. As DOE stated in the October 2013 test procedure NOPR,
these units typically have specific design attributes, such as easily
accessible or open bins that allow convenient and unimpeded access to
the refrigerated products, which make them unique from commercial
refrigeration equipment designed for storage or retailing. 78 FR at
64299-300 (Oct. 28, 2013). In this final rule, DOE maintains that while
salad bars, buffet tables, and other refrigerated holding and serving
equipment are covered equipment types because they meet the definition
of commercial refrigeration equipment in EPCA, the DOE test procedure
and current Federal standards do not apply due to their unique
operation. Should DOE decide to consider test procedures or energy
conservation standards for salad bars, buffet tables, and other
refrigerated holding and serving equipment, it would do so in a future
rulemaking.
b. Chef Bases and Griddle Stands
Chef bases and griddle stands are designed to be placed directly
under cooking equipment, such as a commercial grill. Chef bases and
griddle stands are also designed to provide
[[Page 22282]]
food-safe temperatures in extremely hot environments, and thus are
designed with uniquely robust refrigeration systems. These
refrigeration systems require larger compressors to provide more
cooling capacity for the storage volume than equipment with compressors
that are appropriately sized for more typical ambient temperatures. As
a result, this equipment consumes more energy than similarly sized,
standard CRE models.
In the October 2013 test procedure NOPR, DOE stated that chef bases
and griddle stands are considered commercial refrigeration equipment
according to DOE's definition at 10 CFR 431.62 and stated that it
believes that chef bases and griddle stands can be tested using the DOE
test procedure for commercial refrigeration equipment. DOE also noted
that current energy conservation standards do not apply to these types
of equipment and DOE did not consider standards for this equipment in
its recent revision of energy conservation standards for commercial
refrigeration equipment. 79 FR 17726 (Mar. 28, 2014). DOE further
proposed additions to 10 CFR 431.66 to make clear that the current
energy conservation standards for commercial refrigeration equipment do
not apply to chef bases and griddle stands. 78 FR at 64300 (Oct. 28,
2013). To clearly differentiate ``chef bases'' and ``griddle stands''
from conventional types of commercial refrigeration equipment that are
currently covered by energy conservation standards, DOE proposed to
establish a definition for ``chef base'' and/or ``griddle stand'' based
on the unique operation of chef bases and griddle stands, which are
designed to provide food-safe temperatures in extremely warm
environments in excess of 200 [deg]F, and thus are designed with
uniquely robust refrigeration systems.
In response to the October 2013 test procedure NOPR, interested
parties provided comments on DOE's proposed definition and coverage of
chef bases and griddle stands. Continental agreed with DOE's proposed
definition of ``chef base or griddle stand,'' stating that it
corresponds with industry practice regarding types of units designed
and marketed for harsh applications that should be given special
consideration for energy consumption limits. (Continental, No. 14 at p.
1) \6\ Traulsen suggested that DOE replace the term ``cooking
equipment'' with ``cooking appliance,'' but stated that otherwise found
the definition of ``chef base or griddle stand'' to be acceptable.
(Traulsen, No. 17 at p. 1)
---------------------------------------------------------------------------
\6\ A notation in this form provides a reference for information
that is in the docket of DOE's rulemaking to develop test procedures
for commercial refrigeration equipment (Docket No. EERE-2013-BT-TP-
0025, which is maintained at www.regulations.gov). This particular
notation refers to a comment: (1) Submitted by Continental; (2)
appearing in document number 14 of the docket; and (3) appearing on
page 1 of that document.
---------------------------------------------------------------------------
Hill Phoenix agreed with DOE that chef bases and griddle stands do
not yet have energy conservation standards associated with them and
requested that other, similar equipment designed to be placed or
mounted directly under equipment that is designed to hold food at an
elevated temperature be considered in this category. (Hill Phoenix, No.
13 at p. 1) Similarly, Southern Store Fixtures requested clarification
on the exact definition of chef bases, specifically, whether this
covered refrigeration units with food warming equipment on top.
(Southern Store Fixtures, Public Meeting Transcript, No. 7 at p. 25)
True commented that while some consumers may place food-warming
equipment on top of a refrigeration unit, a majority of consumers will
place high-temperature cooking equipment atop the unit, and
manufacturers will almost always design equipment for the harsh case.
(True, Public Meeting Transcript, No. 7 at p. 26) Hill Phoenix also
noted that NSF Type II equipment is designed to operate at elevated
temperatures and similarly would use more energy if tested using the
current CRE test procedure (than Type I equipment) and, as such,
suggested that NSF Type II equipment also should fall into the category
of equipment for which standards have not yet been set. (Hill Phoenix,
No. 13 at pp. 1-2)
DOE appreciates the agreement of interested parties with DOE's
proposed definition. With regard to replacing the term ``cooking
equipment'' with ``cooking appliance,'' as suggested by interested
parties, DOE's appliance standards and commercial equipment program
generally refers to equipment as something designed and primarily found
in commercial applications, while the term ``appliance'' refers to a
primarily residential application. DOE finds that chef bases and
griddle stands, and the associated cooking apparatus placed above these
equipment, are typically used in commercial kitchens. As such, DOE
believes the term ``cooking equipment'' is more appropriate than
``cooking appliance'' for use in the definition of ``chef bases'' and
``griddle stands,'' as it is consistent with DOE's designation of
equipment as designed for commercial applications.
Regarding the inclusion of additional equipment designed for use
directly under equipment that is designed to hold food at an elevated
temperature as suggested by several commenters, DOE believes that this
equipment can be adequately represented in the current CRE equipment
categories and does not find sufficient justification to exclude them
with the exclusion of ``chef bases'' and ``griddle stands.'' The
categorization of griddle stands was meant to accommodate equipment
that experienced temperatures in excess of 200 [deg]F, which requires
significant modification of the refrigeration system to maintain
cooling in such a high temperature environment. DOE does not find that
temperatures required for short-term holding of food are significantly
different from the temperatures observed in restaurants or other closed
cooking environments in which conventional commercial refrigeration
equipment is placed. DOE does not believe that maintenance of
refrigeration performance in these environments requires significantly
different equipment design, as is the case of ``chef bases'' and
``griddle stands.'' In addition, DOE has not observed specific
marketing or identification of commercial refrigeration equipment
designed for use under food-warming and holding equipment. Thus, based
on DOE's assessment, the refrigeration system and design of this
equipment is not significantly different from other types of commercial
refrigeration equipment, and DOE believes that the existing DOE test
procedure is sufficiently representative of field use, and application
of the existing energy conservation standard appropriate for this
equipment.
In response to Hill Phoenix's comment regarding NSF Type II
equipment, DOE believes that NSF Type II equipment can be effectively
characterized by the existing DOE test procedure and effectively meet
the existing energy conservation standards. DOE previously considered
NSF Type II equipment in the 2012 test procedure final rule and found
that the compressor systems can effectively operate at test
temperatures. In the 2012 test procedure final rule, DOE agreed with
interested parties that testing cases at an ambient temperature of 80
[deg]F, rather than the currently specified 75 [deg]F, will not have a
significant impact on energy consumption for cases with doors and
recognized that the impact on open cases may be greater than on closed
cases, but did not believe that equipment will have operation or
[[Page 22283]]
performance issues if tested at the temperatures prescribed by the DOE
test procedure. 77 FR at 10305-10307 (Feb. 21, 2012). DOE maintains
that the energy consumption of a case should scale with ambient
temperature and does not believe these issues will prevent units from
being tested using the DOE-prescribed test temperatures or complying
with DOE energy conservation standards. DOE researched the equipment
available on the market and requested specific data regarding the
existence of cases that cannot meet the standard or the characteristics
of their operation. DOE did not encounter any data arising from this
search that would conflict with its current treatment of these
equipment types, and no commenters provided any additional data to
support the contention that these equipment types cannot meet the DOE
standards. In addition, NSF Type II equipment is typically placed
outdoors and may see a wide variety of temperatures in the field; thus,
DOE finds the current rating conditions of 75 [deg]F and 45 percent
relative humidity appropriately representative for this equipment.
c. Existing Cases Undergoing Refurbishments or Retrofits
Energy conservation standards apply only to new equipment
manufactured after the effective date of the applicable standard, and
not to equipment undergoing retrofits or refurbishments. DOE stated in
its certification, compliance, and enforcement (CCE) final rule,
published on March 7, 2011, that manufacturers must certify to DOE that
each basic model of covered equipment meets the applicable standard
before distributing that equipment into U.S. commerce. 76 FR at 12426
and 12437. In the October 2013 test procedure NOPR, DOE clarified that
its authority covers only newly manufactured equipment and does not
extend to rebuilt and refurbished equipment. 78 FR at 64300 (Oct. 28,
2013).
DOE did not receive any negative comments in response to this
clarification and continues to maintain that its energy conservation
standards and test procedures apply to only new equipment and not
existing equipment undergoing refurbishments or retrofits.
d. Case Doors Shipped as After-Market Additions
A basic model of commercial refrigeration equipment is tested,
rated, and subject to specific standards based on the equipment
class(es) to which that basic model belongs. For commercial
refrigeration equipment, one of the features that distinguishes the
current equipment classes for the purposes of applying standards is the
presence of doors (i.e., open or closed). In the October 2013 test
procedure NOPR, DOE proposed that when a model of commercial
refrigeration equipment is offered for sale with doors as an optional
accessory, regardless of how the unit is shipped, such unit must be
tested and certified as equivalent to a basic model shipped with doors
pre-installed. DOE also requested comment on whether, if this same
model is offered for sale as a model without doors, it should be tested
and rated with no doors installed and meet the corresponding energy
conservation standards for open case equipment.
In response to the October 2013 test procedure NOPR, the Northwest
Energy Efficiency Alliance (NEEA) commented that it believed equipment
that can optionally be sold with doors or without should be tested and
certified in each configuration. (NEEA, No. 16 at p. 1) DOE did not
receive any negative comments on this proposal.
DOE agrees with NEEA that commercial refrigeration equipment that
can optionally be sold with doors or without doors should be treated as
separate basic models in separate equipment classes and should be
tested both with doors and without doors. This is consistent with the
definition of basic models, which is based on features that affect the
energy use of a covered piece of equipment as established in DOE's CCE
final rule, and requires individual models that would fall into
different equipment classes to be certified separately. 76 FR at 12429
(March 7, 2011) (see 10 CFR 431.62).
2. Definitions Pertinent to Commercial Refrigeration Equipment
DOE currently categorizes commercial refrigeration equipment by
equipment classes based on several general characteristics of a given
basic model. 10 CFR 431.62 provides definitions that assist
manufacturers in determining which equipment class and associated
energy conservation standard applies to a given basic model of
commercial refrigeration equipment. However, 10 CFR 431.62 does not
provide explicit guidance on how to classify commercial refrigeration
equipment with drawers or how to differentiate between a unit with
transparent doors and a unit with solid doors. In the October 2013 test
procedure NOPR, DOE proposed definitions and clarifications regarding
the treatment of commercial refrigeration equipment with drawers and
commercial refrigeration equipment with transparent and/or solid doors.
78 FR at 64300-03 (Oct. 28, 2013). DOE also proposed clarification with
regard to the definitions for and categorization of hybrid equipment
and commercial refrigerator freezers. 78 FR at 64303 (Oct. 28, 2013).
These proposals, comments submitted by interested parties, and DOE's
response to submitted comments are presented in the subsequent
sections.
a. Commercial Refrigeration Equipment With Drawers
DOE's definition of commercial refrigerator, freezer, and
refrigerator-freezer specified at 10 CFR 431.62 includes a requirement
that the equipment ``[h]as transparent or solid doors, sliding or
hinged doors, a combination of hinged, sliding, transparent, or solid
doors, or no doors.'' Based on this definition, DOE interprets the term
``door'' to mean any movable component of the CRE unit that:
1. When closed, separates the interior refrigerated space from the
ambient air; and
2. when opened, provides access to the refrigerated products inside
the CRE unit.
Based on this definition, in the October 2013 test procedure NOPR,
DOE presented its view that drawers are treated as equivalent to doors
for purposes of DOE's regulatory program, including compliance with
DOE's energy conservation standards. Likewise, DOE believes drawers are
treated as doors when conducting the DOE test procedure. 78 FR at
64300-01 (Oct. 28, 2013).
To demonstrate the comparable operation of models of commercial
refrigeration equipment with drawers as compared to similar models with
traditional doors, in the October 2013 test procedure NOPR, DOE
presented the test results for several CRE units with drawers from
multiple manufacturers using the current DOE test procedure and
compared their performance to nearly identical units with hinged doors
(belonging to the vertical closed solid, or VCS, equipment family) from
the same manufacturer product lines. As a result of the testing, DOE
found that the units with drawers performed similarly to the hinged-
door units to which they were compared. DOE also presented the effect
of drawer-opening distances for CRE units with drawers and found
minimal variation in measured total daily energy consumption (TDEC) at
different drawer opening distances. 78 FR at 64301 (Oct. 28, 2013). DOE
believes these test results confirm that the door-opening requirements
in the DOE test procedure
[[Page 22284]]
apply to basic models of commercial refrigeration equipment with
drawers, just as they do for CRE units with other types of hinged or
sliding doors, and that the current energy conservation standards
prescribed for commercial refrigeration equipment are equally
applicable to CRE units with drawers.
To clarify how DOE's regulatory scheme applies to basic models of
CRE units with drawers, in the October 2013 test procedure NOPR, DOE
proposed to add language to the definition section at 10 CFR 431.62,
defining doors as being inclusive of drawers, and requested comment on
its proposed definition. 78 FR at 64301 (Oct. 28, 2013).
Several interested parties commented on DOE's proposed definition
of door to include drawers, the applicability of the DOE test procedure
to units with drawers, and DOE's coverage of units with drawers in
general. DOE presents the comments received by interested parties and
DOE's response in the following sections.
Definition of Door
In the October 2013 test procedure NOPR, DOE defined door at 78 FR
64301 (Oct. 28, 2013).
DOE received several comments and suggestions from interested
parties regarding its proposed definition for doors. Continental
commented that DOE's definition of ``door'' should not include drawers.
Continental stated that it is counter-intuitive to define a ``drawer''
as a subset of a ``door'' and this would result in confusion and
misinterpretation and suggested that, instead, DOE change the usage of
the term ``door'' in applicable procedures to ``door or drawer.''
(Continental, No. 14 at p. 1) AHRI did not agree with DOE's proposed
definition of ``door'' to be inclusive of drawers and instead suggested
that DOE create separate definition for drawers or amending the current
definition for ``doors'' by replacing ``door'' with the term ``door/
drawer.'' (AHRI, No. 15 at p. 3)
NEEA, AHRI, Southern Store Fixtures, and True commented that DOE's
definition of doors would include night curtains and recommended that
DOE include a specific exclusion of night curtains in the definition of
doors. (NEEA, No. 16 at p. 2; AHRI, No. 15 at p. 4; Southern Store
Fixtures, Public Meeting Transcript, No. 7 at p. 32; True, Public
Meeting Transcript, No. 7 at p. 37) Several interested parties,
including NEEA, Traulsen, True, Southern Store Fixtures, and Unified
Brands, recommended that DOE remove the ``use of tools'' clause from
the definition, as most drawers and some doors are intended to be
removed without the use of tools. (NEEA, No. 16 at p. 2; Traulsen, No.
17 at p. 2; True, Public Meeting Transcript, No. 7 at p. 37; Southern
Store Fixtures, Public Meeting Transcript, No. 7 at p. 37; Unified
Brands, No. 9 at p. 1)
DOE appreciates the suggestions of interested parties regarding
changes and improvements to DOE's proposed definition for door. DOE
agrees with interested parties that a night curtain would have met the
definition of ``door'' proposed in the October 2013 test procedure
NOPR. This was not DOE's intent, as night curtains are intended to be
treated as an energy-saving feature for open cases. DOE also adopted a
specific definition for night curtain in the 2012 test procedure final
rule. 77 FR at 10318 (Feb. 21, 2012). To clarify that night curtains
are not to be treated as doors for the purposes of testing using the
DOE test procedure or complying with DOE's energy conservation
standards, in this final rule DOE is adding language to the definition
of ``door'' to exclude night curtains.
DOE also acknowledges comments submitted by interested parties
regarding the requirement that a door be ``affixed such that it is not
removable without the use of tools.'' DOE's intent with the proposed
clause was to exclude temporary insulating panels or other devices that
are not doors, but may be placed on open cases periodically to limit
energy consumption when the case is not in use for merchandizing. DOE
agrees with commenters that some doors and drawers are intended to be
removable without the use of tools for the ease of cleaning, product
loading, or other utility features, and that these cases should still
be treated as closed cases with doors. Therefore, in the definition of
``door'' adopted in this final rule, DOE is removing the ``use of
tools'' provision. Upon further consideration, DOE found the statement
to be superfluous. This does not include night curtains or other panels
that are not in place when the case is being used for merchandising.
Regarding the inclusion of drawers in DOE's definition of ``door,''
DOE acknowledges the concerns of interested parties that referring to
drawers as doors in the test procedure for commercial refrigeration
equipment may be confusing and non-intuitive. However, DOE's test
procedure for commercial refrigeration equipment only addresses the
treatment of ``doors'' and does not explicitly reference the treatment
of ``drawers.'' This terminology is established in ASHRAE Standard 72-
2005, the method of test referenced in AHRI 1200-2010, the test
procedure incorporated by reference as the foundation of DOE's test
procedure for commercial refrigeration equipment. Given that the
nomenclature in these referenced test standards is not the sole purview
of DOE, DOE believes the most straightforward method for clarifying
that the treatment of drawers should be identical to the treatment of
doors for the purposes of conducting the DOE test procedure and
compliance with DOE's energy conservation standards is to continue to
define door as inclusive of drawers, as proposed in the October 2013
test procedure NOPR. 78 FR at 64301 (Oct. 28, 2013). However, if the
ASHRAE Standard Project Committee were to revise ASHRAE Standard 72-
2005 to include drawers specifically, DOE could review and incorporate
the revised test standard, if appropriate, to further eliminate
confusion. DOE understands that this may occur in a forthcoming version
of ASHRAE Standard 72, anticipated to be published in 2014. Until such
a revised test standard is available, DOE will also incorporate
language into the test procedure at 10 CFR 431.64 to specify that
drawers are to be treated as identical to doors when conducting the DOE
test procedure.
Applicability of the DOE Test Procedure to Commercial Refrigeration
Equipment With Drawers
Several interested parties commented that the current DOE test
procedure for commercial refrigeration equipment does not provide
sufficient clarity regarding how to test units with drawers.
Specifically, commenters identified (1) the type and configuration of
drawer pans, (2) the location and number of simulators and test
packages in the drawers, (3) how to determine interior refrigerated
volume of a drawered unit, and (4) how far a drawer should be opened
during testing as areas of ambiguity when applying the existing DOE
test procedure to CRE models with drawers. (Unified Brands, No. 9 at p.
2; Traulsen, No. 17 at p. 2; National, Public Meeting Transcript, No. 7
at p. 42) Unified Brands and Traulsen commented that, depending on the
design of the drawer unit, moving the test simulators in and out of the
refrigerated compartment may cause variation in the integrated average
temperature (IAT), which could drive increased energy consumption, and
added that testing of commercial refrigeration equipment with doors
does not require test simulators to be removed from the refrigerated
compartment. (Unified Brands, No. 9 at p. 2; Traulsen, No. 17 at p. 2)
Specifically, National opined that when calculating total volume of a
drawered
[[Page 22285]]
unit, there should be considerations for drawer pan capacity.
Additionally, National urged DOE to center the definition of a unit's
volume on the amount of product that the unit can hold. (National,
Public Meeting Transcript, No. 7 at p. 42)
Unified Brands commented that it is inappropriate for a drawer to
be included as equivalent to a door for the purposes of testing and
compliance with the DOE test procedure and energy conservation
standards because when a drawer is opened, the entire contents of the
drawer are removed from the interior volume of the cabinet and exposed
to the ambient conditions. In addition, Unified Brands stated that it
manufactures drawer units in which the drawer is fully insulated
refrigerated space and the cabinet is mostly structural. Unified Brands
further commented that drawer units are often designed with additional
refrigeration capacity beyond that of a similarly sized door unit due
to the unique air flow and refrigeration challenges that drawers
provide. (Unified Brands, No. 9 at pp. 1-2)
Lastly, Unified Brands commented that current CRE models may
require as many as 12 separate drawer openings, requiring 12 door-
opening apparatus, the electronic capability to control all of the
openers, and a significant amount of space. Unified Brands added that
testing equipment with drawers also increases burden by increasing the
complexity of the test and increasing the risk associated with managing
thermocouple wires to prevent thermocouple displacement and breakage.
(Unified Brands, No. 9 at pp. 2-3) Unified Brands was also concerned
that multiple thermocouple wires may prevent the drawer gaskets from
sealing properly, resulting in increased energy use. (Unified Brands,
No. 9 at p. 2)
Based on comments received by interested parties, DOE reviewed its
test procedure for commercial refrigeration equipment with regards to
specific requirements necessary to accommodate or clarify the
application of the CRE test procedure to equipment with drawers. The
DOE test procedure for commercial refrigeration equipment adopts
specific sections of the Association of Home Appliance Manufacturers
Standard for Energy, Performance and Capacity of Household
Refrigerators, Refrigerator-Freezers and Freezers (AHAM HRF-1-2004) as
the protocol for determining refrigerated compartment volume for
compliance with the current standards and specific sections of AHAM
HRF-1-2008 for measuring refrigerated compartment volume to determine
compliance with the amended standards adopted in the March 2014 energy
conservation standard final rule. 79 FR 17726 (Mar. 28, 2014). DOE
reviewed these methods for determining refrigerated compartment volume
and finds them sufficient for determining internal refrigerated volume
for commercial refrigeration equipment with drawers.
With regard to the comment from Unified Brands about a model of
commercial refrigeration equipment in which the drawers are insulated
and the outer case acts more as a support, DOE researched this type of
commercial refrigeration equipment and reviewed the applicable methods
for calculating refrigerated or frozen compartment volume. DOE
specifically references section 3.21, ``Volume,'' of AHAM HRF 1-2004
and section 3.30, ``Volume,'' of AHAM HRF 1-2008. Both of these
sections contain definitions for ``fresh food compartment volume'' and
``freezer compartment volume,'' which are defined as the portion of the
total refrigerated volume above or below 32 [deg]F, respectively. The
total refrigerated volume is a combination of these two compartment
volumes. Based on these definitions, DOE believes that only the volume
that is purposefully refrigerated for food display or storage is to be
included in the refrigerated volume calculation. Thus, in the case of a
drawered CRE model in which only the drawers are insulated and directly
cooled, only the interior volume of the drawers would be included in
the calculation of refrigerated volume, not the entire volume of the
cabinet housing. DOE believes that this is clear in the existing
protocol specified in AHAM HRF 1-2004 and AHAM HRF 1-2008 and further
clarification is not necessary on this matter.
Regarding test simulator locations, filler package placement, and
pan configuration for CRE models with drawers, DOE reviewed the ASHRAE
Standard 72-2005, which is the industry standard referenced by the DOE
test procedure, to determine the sufficiency of existing guidance for
placing test simulators and filler packages in commercial refrigeration
equipment with drawers. ASHRAE Standard 72-2005 specifically addresses
CRE models with shelves and without shelves and, in general, specifies
that test simulators shall be placed at the right end, front and back,
and the left end, front and back. Test simulators are also to be placed
intermittently across the face of CRE model at shelf standard breaks or
with specific spacing in the case of CRE models without shelving. Since
CRE models with drawers typically do not have shelves, these models
will be treated as CRE models without shelves. Therefore, applying the
requirements for CRE models without shelves to CRE models with drawers,
it is logical that test simulators should be placed in the front and
back corners of the drawer and, depending on the width of the drawer,
36- to 48-inch intervals across the width of the drawer in the front
and back, as is the case for commercial refrigeration equipment without
shelves. DOE does not see a problem applying the requirements for a CRE
model without shelves in ASHRAE Standard 72-2005 to a CRE model with
drawers, which qualifies as a CRE model without shelves, and believes
placing test simulators in this manner will accurately and
representatively capture the internal temperature of the equipment.
With regard to filler package placement, ASHRAE Standard 72-2005
specifies that the remaining usable space where test simulators are not
required shall be loaded with filler packages or filler material so as
to occupy between 70 and 90 percent of the refrigerated volume and to
uniformly occupy the space from the front to the rear. Again, DOE does
not anticipate issues in applying these requirements to CRE models with
drawers just as they are applied to CRE models with doors. In the case
of CRE models with drawers, each drawer should be filled with filled
packages or filler material up to the load limit. DOE acknowledges that
it is theoretically possible that the drawers could hold less than 70
percent of the net refrigerated volume if the entire cabinet was
refrigerated. However, DOE notes that this would be an inefficient
design choice and DOE does not see a significant utility associated
with having significant amounts of unusable refrigerated volume.
Therefore, DOE does not believe accommodation is necessary for such
situations. If a manufacturer produces a case that cannot meet the
requirements of 70 percent packing, that manufacturer must apply for a
test procedure waiver.
As to the pan configuration necessary for testing CRE models with
drawers, DOE understands that CRE with drawers often consist of a
sliding frame that accommodates the placement of standard size pans
typically used by the food service industry for holding food. DOE
acknowledges that theoretically many configurations of pans could be
placed in a commercial refrigerator or freezer with drawers. DOE's test
procedure requires that the model be configured with a pan
configuration that allows for the maximum packing of filler packages as
specified by the test
[[Page 22286]]
procedure, but not exceeding 90 percent of the refrigerated volume. To
clarify this requirement, DOE is adopting language to specify that
commercial refrigeration equipment with drawers should be configured
with the drawer pans that allow for the maximum packing of test
simulators and filler packages without exceeding 90 percent of the
refrigerated volume.
In response to the Unified Brands comment regarding the burden of
conducting the test procedure for commercial refrigeration equipment on
equipment with drawers, DOE does not believe that the requirements are
significantly more complex than those for testing commercial
refrigeration equipment with doors. Numerous door-opening apparatus are
also required for multi-compartment doored cases, and thermocouples
must also be configured so as to measure test simulators in the
internal refrigerated volume. DOE acknowledges that incrementally more
thermocouple wire may need to be attached to thermocouples placed in
test simulators in drawers, to ensure sufficient slack is available for
the drawer to fully open and fully close without disturbing the
thermocouple placement within the test simulator. However, DOE does not
believe that providing this additional length of thermocouple wire is a
significant additional burden, given many test simulators may already
be equipped with excess thermocouple wire.
General Treatment of Drawers as Equivalent to Doors
In response to the October 2013 test procedure NOPR, DOE also
received several comments from interested parties regarding the
appropriateness of treating drawers as equivalent to doors for the
purposes of testing under DOE's test procedure for commercial
refrigeration equipment and compliance with DOE's energy conservation
standards in general. DOE presents these comments and DOE's response in
this section.
Traulsen commented that units with drawers typically hold less
product by mass and volume than an identical unit with doors only and
questioned how this will affect the IAT and the infiltration of air
during the door/drawer opening period. (Traulsen, No. 17 at p. 2)
According to Unified Brands, many drawer units are specifically
designed for drawers and do not have a door unit of similar
construction for comparison and, prior to assuming similarity between
door and drawer units, a statistically significant sample of product
designs should be tested and validated. (Unified Brands, No. 9 at pp.
1-2)
DOE's test data, presented in the October 2013 test procedure NOPR,
does not suggest that drawers are significantly different from doors in
terms of applying the DOE test procedure or the thermodynamic
requirements. 78 FR at 64301 (Oct. 28, 2013). Lacking additional data
contradicting DOE's test data, DOE is maintaining its position that
drawers are to be treated as equivalent to doors for the purposes of
conducting the DOE test procedure and complying with DOE's energy
conservation standards.
b. Transparent and Solid Doors
In reviewing the CRE test procedure, DOE identified opportunities
for clarification within the definitions and classifications of
commercial refrigeration equipment with solid doors versus those with
transparent doors. In the October 2013 test procedure NOPR, DOE
proposed several new definitions for transparent, closed solid, and
closed transparent to clarify the test procedure requirements at 10 CFR
431.64 to ensure appropriate equipment categorization. 78 FR at 64301-
64303 (Oct. 28, 2013).
Definition of Transparent
The DOE test procedure for commercial refrigeration equipment, as
amended by the 2012 test procedure final rule, incorporates by
reference AHRI 1200-2010. 77 FR at 10318 (Feb. 21, 2012). AHRI 1200-
2010 defines total display area (TDA) as ``the sum of the projected
area(s) for visible product expressed in [square feet]'' and provides
procedures for calculating the TDA of commercial refrigeration
equipment with panels, end enclosures, doors, or other envelope
components that have some transparent area(s). Appendix D of AHRI 1200-
2010 provides further guidance and examples to clarify the calculation
of TDA. The appendix also defines a transparent material as that which
allows at least 65 percent light transmittance. Therefore, based on
AHRI 1200-2010, a transparent door would be one partially or entirely
composed of a material that allows greater than or equal to 65 percent
light transmittance.
In the October 2013 test procedure NOPR, DOE proposed a definition
for ``transparent'' based on an unambiguous measurement of the light
transmission properties of a material in accordance with ASTM Standard
E 1084-86 (Reapproved 2009), ``Standard Test Method for Solar
Transmittance (Terrestrial) of Sheet Materials Using Sunlight,'' at
normal incidence. 78 FR at 64301-64302 (Oct. 28, 2013).
In response to DOE's proposed definition of ``transparent,''
several interested parties provided comments and suggestions for
adopting an appropriate definition for commercial refrigeration
equipment applications. Continental stated that DOE's proposed
definition of ``transparent'' introduces unnecessary complexity and
suggested that a simple dictionary-type definition as ``able to [be]
seen through'' would be sufficient for nearly all applications for
covered commercial refrigeration equipment. Continental added that DOE
has the right and obligation to challenge a manufacturer's claim if DOE
believes it does not meet a basic definition of the terminology or the
intent of the standard. (Continental, No. 14 at p. 1) NEEA, True, and
Hussmann were concerned that DOE's proposed threshold of 65 percent
light transmittance might inadvertently exclude some types of Low-E,
high performance glass, which can have visible transmittance as low as
45 percent. (NEEA, No. 16 at p. 2; True, Public Meeting Transcript, No.
7 at p. 53; Hussmann, No. 11 at p. 1) NEEA and Hussmann recommended DOE
consider lowering the threshold for determining whether a material is
transparent or not, and suggested that DOE possibly refer to the
WINDOWS 5 model, developed by Lawrence Berkeley National Laboratory,\7\
that was used in the engineering analysis. (NEEA, No. 16 at p. 2;
Hussmann, No. 11 at p. 1)
---------------------------------------------------------------------------
\7\ https://windows.lbl.gov/software/window/window.html.
---------------------------------------------------------------------------
True and Southern Store Fixtures noted that self-serve counter
display cases may be fitted with see-through mirror-finish, or glass
reflective panels, which would affect the transparency of the doors
depending on the measurement angle and direction. (Southern Store
Fixtures, Public Meeting Transcript, No. 7 at p. 53; True, Public
Meeting Transcript, No. 7 at p. 55)
True also noted that the majority of losses through transparent
doors were a result of the difference in insulation capacities between
the glass door and the solid door, and that only a small portion of the
losses were due to light entering through transparent doors. True
therefore opined that treating a glass door as solid, irrespective of
its transparency, was inaccurate. (True, Public Meeting Transcript, No.
7 at p. 51)
DOE appreciates the suggestions by commenters. In response to
Continental's concern regarding the potential complexity of a
quantitative method for determining a transparent
[[Page 22287]]
material, rather than a definition based on the intent or application
of the material, DOE notes that the method to determine transparency of
a material is not mandatory for equipment classification or testing. In
the October 2013 test procedure NOPR, DOE noted that determination of
the light transmittance of a transparent material is not required in
all cases to classify a basic model of commercial refrigeration
equipment as equipment with transparent doors and clarified that
manufacturers may continue to specify equipment as belonging to a
transparent equipment class (e.g., vertical closed transparent or
horizontal closed transparent) or a solid without testing because, in
most cases, it will be obvious whether a material is transparent or
not; therefore, testing would not be necessary to verify the
classification of a material as transparent or not. 78 FR at 64302
(Oct. 28, 2013). Thus, incorporation of a quantitative test procedure
is not anticipated to add to the complexity and burden of conducting
the DOE test procedure for most models of commercial refrigeration
equipment.
DOE agrees with Continental that DOE has the obligation and the
right to challenge the classification of certain materials as
transparent. However, there may be cases in which the material is not
obviously transparent or solid, such as basic models with special
decals or opaque glass. DOE prefers to use a quantitative, objective
method to determine transparency of a material and subsequent equipment
classification, which will also provide certainty to the regulated
industry. Therefore, DOE is adopting in this final rule a definition of
``transparent'' based on the evaluation of that material in accordance
with ASTM Standard E 1084-86 (Reapproved 2009).
In response to the comments from NEEA, True, and Hussmann
expressing concern about the inclusion of Low-E and high-performance
glass as a ``transparent'' material when such fenestration products may
have visible transmittance values as low as 45 percent, DOE researched
available high-performance glass door products for commercial
refrigeration equipment to determine an appropriate threshold for light
transmittance. While some Low-E glass with reflective coatings designed
for extremely sunny environments can have visible transmittance values
as low as 0.2 (meaning 20 percent transparent), DOE finds that it is
unlikely commercial refrigeration equipment would incorporate such
material since this equipment is not typically installed in extremely
sunny environments. In addition, such a low visible transmittance value
would significantly diminish the ability of consumers to see through
the glass to the contents inside the unit, which is the intent of
including transparent material in a given CRE design. Therefore, DOE is
adopting a threshold for determining a transparent material of 45
percent light transmittance as determined in accordance with ASTM
Standard E 1084-86 (Reapproved 2009).
Regarding comments by True and Southern Store Fixtures, DOE
acknowledges that some glass may be available with a mirrored finish to
prevent viewing or light transmittance when viewed from one side of the
glass, but not the other. DOE does not intend to treat such glass as
solid, as it provides the function of transparent material (i.e., being
able to see through to the internal contents of the case) when viewed
from one side of the glass. In the equipment described by commenters,
this would be when viewed at an angle of incidence normal (90 degrees)
to the plane of the case and from the exterior. DOE believes that
reflective glass would fully meet the definition of ``transparent''
when tested at normal incidence and in the intended direction of
viewing. Therefore, to clarify the orientation of glass when testing
using ASTM Standard E 1084-86 (Reapproved 2009), DOE is incorporating
language into the definition of ``transparent'' to specify that the
material is to be tested at normal incidence and in the intended
direction of viewing.
Definition of Equipment With Transparent Doors Versus Solid Doors
In the energy conservation standards specified at 10 CFR 431.66,
DOE refers to equipment families using the terms ``closed solid'' and
``closed transparent'' (for example, vertical closed solid (VCS) and
vertical closed transparent (VCT)). In the October 2013 test procedure
NOPR, DOE proposed definitions for ``closed transparent'' and ``closed
solid'' to clarify what factors differentiate a CRE basic model as a
transparent-door model or a solid-door model. DOE based its proposed
definitions on a percentage of outer surface area of all doors that are
transparent. Specifically, DOE proposed that if 75 percent or more of
the outer surface area of all doors on a CRE unit is transparent, that
unit would be considered closed transparent. Conversely, DOE proposed
that ``closed solid'' would refer to CRE equipment with doors, and in
which more than 75 percent of the outer surface area of all doors is
not transparent. 78 FR at 64318 (Oct. 28, 2013). As DOE presented at
the December 2013 test procedure NOPR public meeting, DOE intended for
the definition of ``closed solid'' to include equipment in which more
than 25 percent of the outer surface area of all doors on a unit are
not transparent, and notes that the inclusion of the 75 percent figure
in the October 2013 test procedure NOPR was a typographical error.
DOE received several comments from interested parties in response
to the categorization of closed transparent versus closed solid
equipment families proposed in the October 2013 test procedure NOPR.
Hill Phoenix, AHRI, and Hussmann commented that a case that has a
transparent door on the front and a solid door on the side or back,
where approximately 50 percent of the door surface area is transparent
and approximately 50 percent of the door surface area is solid, was not
adequately addressed by DOE's proposed definitions. Hill Phoenix, AHRI,
and Hussmann further suggested that a CRE model where 25 percent or
more of the outer surface area of all doors on the unit are transparent
should be treated as a transparent case and that any case that has more
than 75 percent of the door area as solid should be subject to the
closed solid energy conservation standards. (Hill Phoenix, No. 13 at p.
2; AHRI, No. 15 at p. 4; Hussmann, No. 11 at p. 2)
Continental commented that DOE's proposed definitions do not
correlate with the way commercial refrigeration systems are typically
designed for units with transparent doors. Continental further
commented that if more than 25 percent of the doors on a unit are
transparent, the refrigeration systems are commonly ``upsized'' to
provide the increased cooling capacity required. Thus, Continental
suggested that DOE's definition should align with industry practice and
adopt a 25 percent threshold or, at most, a 32 percent level.
(Continental, No. 14 at p. 2)
Traulsen recommended that the definition of ``closed transparent''
refer to CRE models in which 75 percent or more of the transparent area
of the doors on the customer side of the pass-through or the operator/
customer side of the reach-in \8\ style unit is transparent, and
``closed solid'' be defined as equipment in which more than 75 percent
of the outer surface area of all the doors on each side of the unit is
not transparent. Traulsen added that transparent doors and the design
and operation of closed transparent equipment carry a higher
[[Page 22288]]
energy penalty and DOE should be cautious of creating definitions that
classify equipment with transparent doors as closed solid equipment.
Traulsen further recommended ignoring other doors on the backside of
the unit when classifying closed transparent equipment, similar to the
treatment of pass-through-type equipment in ASHRAE Standard 72-2005,
where only doors on the one side of the pass-through should be operated
during the test. (Traulsen, No. 17 at p. 2)
---------------------------------------------------------------------------
\8\ The comment submitted by Traulsen referenced ``read-in''
style units. DOE believes Traulsen meant to reference ``reach-in''
style units and has amended the submitted comment to reflect this.
---------------------------------------------------------------------------
Hussmann suggested that DOE further clarify what ``the outer
surface area of the door'' is and whether it includes mullions and door
frames. (Hussmann, No. 11 at p. 2)
Alternatively, Zero Zone offered that the ENERGY STAR[supreg] \9\
program uses definitions that describes a number of additional details
about glass door equipment and recommended that DOE should consider
these definitions. For example, Zero Zone stated that it manufactures a
CRE model with transparent doors on the front and solid doors on the
back, and that the ENERGY STAR definitions would classify such a case
as a glass door cabinet and DOE's proposed definitions would qualify
such as case as a solid door cabinet. In addition, Zero Zone suggested
that DOE perform an engineering analysis to assess the impact and
feasibility of reduced energy conservation standard levels for closed
transparent equipment with a small percent of transparent area. (Zero
Zone, No. 18 at pp. 1-2)
---------------------------------------------------------------------------
\9\ ENERGY STAR is a joint program of the U.S. Environmental
Protection Agency and DOE that establishes a voluntary rating,
certification, and labeling program for highly energy efficient
consumer products and commercial equipment. Information on the
program is available at www.energystar.gov/index.cfm?c=home.index.
---------------------------------------------------------------------------
In response to comments regarding the fraction of transparent
surface area of all outer doors on a given CRE model that
differentiates closed transparent equipment from closed solid
equipment, DOE acknowledges comments from interested parties regarding
the increased energy use associated with closed transparent equipment
due to the increased thermal conductance of glass as compared to
insulated case walls and other design and operation features. In
determining the fraction of transparent door surface area to qualify a
basic model of commercial refrigeration equipment as equipment with
transparent doors, DOE proposed a transparent surface area higher than
50 percent to ensure that only doors with a majority of transparent
surface area were considered transparent doors. 78 FR at 64302 (Oct.
28, 2013). However, DOE finds the suggestions of Traulsen, Hill
Phoenix, AHRI, and Hussmann--that equipment with transparent doors on
one side of the cabinet and solid doors on another be treated as
transparent equipment--reasonable and consistent with DOE's intended
application of closed transparent equipment. That is, equipment with
only one transparent door and the remaining sides consisting of solid
insulated case wall and similar equipment with two doors, one that is
transparent and one on another side that is solid, should be treated
equivalently for the purposes of testing and compliance with DOE energy
conservation standards. However, DOE finds the suggestion of Traulsen
to address only the customer-side of a CRE model to be inconsistent and
impractical to implement given the variety of door configurations that
could be present on other sides of the CRE unit. DOE believes it is
most appropriate to address the outer surface area of all the doors
that may be present on any of the sides of a CRE model when determining
whether the equipment belongs in the closed solid or closed transparent
equipment family.
Regarding Hussmann's request that DOE provide additional clarity as
to the definition of ``outer surface area,'' DOE used the term ``outer
surface area'' to refer to the surface area on only one side of a door.
DOE acknowledges that solid and transparent doors installed on
commercial refrigeration equipment are physically three-dimensional
objects, with surface area measurements on each of six sides: Four
edges and two faces. DOE used the term ``outer surface area'' to refer
to the side of the door facing out of, rather than into, the cabinet.
In response to Hussmann's comment inquiring whether the outer surface
area of the door included mullions and door frames, DOE is clarifying
that the outer surface area to be accounted for is that of the door
itself, as defined in section III.A.2.a, as a unique component of the
CRE model. In this case, the door consists of the door frame and any
transparent area that represents the ``moveable panel'' that
``facilitates access to the refrigerated space.'' This would not
include mullions, which are fixed portions of the CRE model's envelope
on which the doors are mounted. DOE has specified how to determine the
applicability of transparent equipment families to a given model in
section 1.2 of each appendix.
In response to Zero Zone's suggestion that DOE consider the ENERGY
STAR[supreg] definitions for solid door cabinet, glass door cabinet,
and mixed solid/glass door cabinet, DOE reviewed the definitions in the
ENERGY STAR ``Version 2.1 Program Requirements for Commercial
Refrigerators and Freezers'' \10\ (Version 2.1 Program Requirements),
as well as associated stakeholder comments received during the
development of the ENERGY STAR Version 2.1 Program Requirements in
developing the proposed definitions for closed solid and closed
transparent.\11\ The primary difference between the ENERGY STAR
classification scheme and that proposed by DOE is the treatment of CRE
models with mixed solid and transparent doors on at least one side of
the unit. In DOE's proposal, cases with mixed solid and transparent
doors would be treated as either solid or transparent cases, based on
the outer surface area of the doors, whereas ENERGY STAR treats this
equipment in a separate equipment category.
---------------------------------------------------------------------------
\10\ U.S. Environmental Protection Agency. ENERGY STAR[supreg]
Program Requirements for Commercial Refrigerators and Freezers:
Eligibility Criteria; Version 2.1. Effective January 1, 2010. (Last
accessed August 15, 2013.) https://www.energystar.gov/ia/partners/product_specs/program_reqs/Commercial_Refrigerator_and_Freezer_Program_Requirements.pdf?dae6-ef7c.
\11\ See Continental Refrigerator, Comments on Specification for
Commercial Refrigerators and Freezers, Version 2.0 Draft 3. Dated
January 7, 2009. Available at: https://www.energystar.gov/ia/partners/prod_development/revisions/downloads/refrig/Continental_Comments.pdf?f45c-2369. Beverage-Air Corporation, Beverage-Air
Comments re: ENERGY VERSION 2.0--DRAFT 3, Dated January 8, 2009.
Available at: https://www.energystar.gov/ia/partners/prod_development/revisions/downloads/refrig/Beverage-Air_Comments.pdf?f45c-2369. Anonymous, Comments on Draft 2. Dated
September 15, 2008. Available at: https://www.energystar.gov/ia/partners/prod_development/revisions/downloads/refrig/Anonymous_Comments.pdf?f45c-2369. True Manufacturing, Comments on Draft 2.
Dated September 17, 2008. Available at: https://www.energystar.gov/ia/partners/prod_development/revisions/downloads/refrig/True_Comments.pdf?f45c-2369. Traulsen, Comments on Draft 1. Dated April
18, 2008. Available at: https://www.energystar.gov/ia/partners/prod_development/revisions/downloads/refrig/Traulsen_Comments.pdf?f45c-2369.
---------------------------------------------------------------------------
DOE believes the definitions proposed in the October 2013 test
procedure NOPR are straightforward and would unambiguously address
equipment categorization. 78 FR at 64318 (Oct. 28, 2013). In addition,
setting the threshold for transparent surface area of all outer doors
at greater than 25 percent makes it unlikely that equipment with
substantial amounts of transparent area will be categorized in the
closed solid equipment family. For example, equipment that has one door
that is half-transparent and half-solid would be treated as ``closed
transparent'' and would have to meet the energy conservation standard
for the appropriate equipment class based on its volume or TDA. As a
result, DOE
[[Page 22289]]
does not anticipate issues associated with equipment with small
transparent areas that cannot meet the applicable energy conservation
standard. Also, these definitions are consistent with the equipment
categorization methodology DOE uses to establish standards for covered
equipment. As such, DOE believes defining terms that are used directly
in the description and determination of equipment classes for
commercial refrigeration equipment is the most clear, unambiguous
method for defining and categorizing equipment as closed transparent or
closed solid, and DOE does not see a need to establish a unique
equipment category for mixed solid/transparent equipment.
c. Hybrid Equipment and Commercial Refrigerator-Freezers
At 10 CFR 431.62, DOE defines a commercial hybrid refrigerator,
freezer, or refrigerator-freezer as having two or more chilled and/or
frozen compartments that are in two or more different equipment
families, contained in one cabinet, and sold as a single unit. In the
October 2013 test procedure NOPR, DOE proposed to replace the
definition of ``commercial hybrid refrigerator, freezer, and
refrigerator-freezer'' with a definition of ``commercial hybrid,'' and
introduce a new definition of ``commercial refrigerator-freezer'' to
clarify DOE's definitions and equipment categories. 78 FR at 64303-
64304, 64318 (Oct. 28, 2013).
In response to the definitions proposed in the October 2013 test
procedure NOPR, DOE received comments from interested parties regarding
DOE's definition for commercial hybrid and the applicability of the
definition of commercial hybrid to certain equipment. Continental
commented that the proposed definition of ``commercial hybrid'' should
specify that the ``two compartments'' are separated by an insulated
partition to isolate them for different storage applications, as this
would limit confusion with multiple section cabinets, which may have
non-insulated partitions or ducting between them purely for air
distribution, shared throughout the entire unit. (Continental, No. 14
at p. 2)
True noted that DOE's definition did not explicitly state that dual
temperature units were separated by a vertical partition, and therefore
might include solid-shelf units. (True, Public Meeting Transcript, No.
7 at p. 71) Similarly, National expressed confusion over the
application of the DOE rule in cases where two sections of a unit were
at different temperatures, but potentially use the same evaporator coil
or share air between the two spaces. (National, Public Meeting
Transcript, No. 7 at p. 75) National commented that some two-door units
are built with airflow down the middle and panels with louvers to
distribute air. (National, Public Meeting Transcript, No. 7 at p. 79)
Hussmann agreed with DOE's proposed definitions of commercial
hybrid and commercial refrigerator-freezer, but requested clarification
on how to classify or handle a piece of equipment that contains at
least one section or compartment that is not covered by the DOE test
procedure (e.g., salad bars and buffet tables). (Hussmann, No. 11 at p.
2) Royston noted that in many hybrid units such as salad bars, it was
unclear what percentage of the unit would be considered refrigerated.
(Royston, Public Meeting Transcript, No. 7 at p. 82)
In response to Continental's suggestion that DOE consider
specifying that the compartments in a commercial hybrid refrigerator,
freezer, or refrigerator freezer be separated by an insulated partition
or be thermally isolated from one another, DOE agrees that the intent
of the commercial hybrid equipment provisions is to address equipment
with thermally distinct compartments from different equipment families
(e.g., vertical closed transparent and vertically closed solid). As
such, DOE is adopting language to specify that commercial hybrid
equipment is equipment consisting of two or more thermally separated
refrigerated compartments that are in two or more different equipment
families that is sold as a single unit.
In regard to clarification on how to classify or handle a piece of
equipment that contains at least one section or compartment that is not
covered by the DOE test procedure (e.g., salad bars and buffet tables),
DOE clarifies that this type of equipment is not hybrid equipment
because it does not consist of two or more different equipment
families. Only the compartment(s) of the piece of commercial
refrigeration equipment that is covered by one of DOE's existing
equipment classes is included in DOE's equipment family definitions.
The compartment that is not covered by DOE's existing standards for
commercial refrigeration equipment is not included in DOE's equipment
family definitions and, thus, such a unit would not meet the definition
of commercial hybrid. Using the example presented in Hussmann's
comment, consider a commercial refrigerator that contains one
compartment that falls into the vertical closed solid equipment family
and a thermally separate compartment that offers accessible
refrigerated bins for the purposes of preparing sandwiches or holding
buffet items. As presented in section III.A.1.a, sandwich prep tables
and buffet tables are not currently regulated under DOE's existing
energy conservation standards or subject to DOE's test procedure for
commercial refrigeration equipment. As such, this CRE model would be
covered under DOE's existing energy conservation standards as a
commercial refrigerator in the vertical closed solid equipment family
based on the refrigerated volume of only the refrigerated compartment
comprising the vertical closed solid commercial refrigerator. This CRE
model would be tested under the DOE test procedure for commercial
refrigeration equipment as a commercial refrigerator, and the
compartment containing the sandwich prep or buffet table bins would be
disabled and not included in the determination of energy consumption
for that equipment. If the same refrigeration system serves both
compartments and the refrigeration of the sandwich/buffet compartment
cannot be disabled, manufacturers may apply for a test procedure waiver
for such equipment if the measured energy use would not be
representative of the commercial refrigerator, freezer, or
refrigerator-freezer portion of the CRE basic model.
3. Relationship Among Rating Temperature, Operating Temperature, and
Integrated Average Temperature
Currently, the table at 10 CFR 431.66(d)(1) describing the energy
conservation standards for equipment other than hybrid equipment,
refrigerator-freezers, and wedge cases refers to the ``rating
temperature'' and ``operating temperature'' of equipment, and the table
describing the applicable test procedure for covered equipment at 10
CFR 431.64(b)(3) refers to the term ``integrated average temperature.''
DOE defines ``integrated average temperature'' as ``the average
temperature of all the test package measurements taken during the
test.'' 10 CFR 431.62.
In the October 2013 test procedure NOPR, DOE proposed explicit
definitions for ``rating temperature'' as the IAT at which a model of
commercial refrigeration equipment should be evaluated in accordance
with the DOE test procedure, and ``operating temperature'' as the range
of IATs at which the unit of commercial refrigeration equipment is
capable of operating. In addition, DOE noted that while the operating
temperature range
[[Page 22290]]
of equipment is used to establish the appropriate equipment class for
CRE basic models based on the standards table at 10 CFR 431.66(d)(1),
only the definition of ``ice-cream freezer'' explicitly identifies the
appropriate operating range (i.e., at or below -5 [deg]F). 10 CFR
431.62 Therefore, DOE also proposed definitions of ``commercial
refrigerator'' and ``commercial freezer'' that reference the operating
temperature range of each category of equipment. 78 FR at 64303-64304,
64318 (Oct. 28, 2013).
In response to DOE's proposed definitions for commercial
refrigerator, commercial freezer, and commercial refrigerator-freezer,
Continental commented that the use of the term ``capable of''
introduced confusion and does not accurately reflect industry
practices. Continental offered the example of a piece of equipment that
is designed and marketed as a refrigerator, but includes an oversized
refrigeration system that may be necessary to hold products at
temperatures near 32 [deg]F that would allow the refrigerator to be
capable of operating below 32 [deg]F in some applications, although it
is not intended to be operated that way. As such, Continental suggested
that DOE define the commercial refrigerator operating range as ``all
refrigerated compartments in the unit are designed, marketed or
intended for operating at or above 32[emsp14][deg]F.'' (Continental,
No. 14 at p. 2) Similarly, Hussmann suggested DOE replace ``capable of
operating'' with ``designed, marketed, or intended to be operated by
the manufacturer.'' (Hussmann, No. 11 at p. 2)
DOE acknowledges comments from interested parties, but notes that
DOE prefers to have an objective method for determining coverage of
equipment under DOE's equipment classes. DOE believes that relying on
how a piece of equipment is ``designed, marketed, or intended to be
used'' provides too much flexibility for manufacturers to specify how a
CRE basic model is ``intended to be used,'' without consideration of
how the equipment actually can be used. As such, DOE maintains that,
for self-contained equipment and remote equipment with thermostats, DOE
will establish the operating range of equipment based on the operating
temperatures the commercial refrigeration equipment is capable of
maintaining. DOE will determine the operating range of covered
equipment based on the maximum and minimum thermostat set points.
However, DOE acknowledges that, for equipment with an operating
temperature range that is primarily in, for example, the commercial
refrigerator operating temperature range (i.e., at or above 32 [deg]F),
but has a minimum operating temperature in the commercial freezer range
slightly below 32 [deg]F (e.g., 30 [deg]F), it may not be appropriate
to require such equipment to be certified as both a commercial
refrigerator and a commercial freezer. DOE believes that equipment
should be categorized in the equipment class most representative of the
operating temperature range of that equipment. As such, DOE is adopting
a tolerance on the minimum and maximum IAT that categorizes equipment
as a commercial refrigerator, commercial freezer, or commercial ice
cream freezer. DOE believes a tolerance of 2 [deg]F would
allow sufficient flexibility that equipment with an operating
temperature range that is substantially representative of one equipment
class, but with a minimum or maximum operating temperature that extends
slightly into the operating temperature range of another equipment
class, is not required to be certified in both equipment classes. This
tolerance is also consistent with the tolerance on the rating
temperatures for the relevant equipment classes. Therefore, in this
final rule, DOE will establish in 10 CFR 431.66 operating temperature
ranges of greater than or equal to 32 [deg]F (2 [deg]F) for
commercial refrigerators, less than 32[emsp14][deg]F (2
[deg]F) for commercial freezers, and less than or equal to -5 [deg]F
(2 [deg]F) for ice cream freezers.
DOE acknowledges that for remote equipment the operating range of
equipment could be much broader, as it is based on the operating
parameters of the compressor system much more than the case design.
Manufacturers may design a case that could optimize performance for
operation as a freezer, but customers would be able to adjust the
compressor operating characteristics to operate the case at
refrigerator temperatures, even though it is not intended to be used
that way. As such, in this test procedure final rule DOE adopts
additional language to clarify that for remote condensing equipment,
the operating temperature range is based on the range of IATs at which
a piece of commercial refrigeration equipment is marketed, designed, or
intended to be used. DOE does not see the need to establish such a
definition for self-contained equipment with thermostats and will
maintain the definition of ``operating temperature'' proposed in the
NOPR based on the IATs at which a piece of commercial refrigeration
equipment is capable of operating.
Traulsen recommended changing all referenced temperature thresholds
from 32 [deg]F to 25 [deg]F, since some equipment, including meat
refrigerators, is intended to be operated as low as 25 [deg]F.
(Traulsen, No. 17 at p. 3)
In response to Traulsen's recommendation regarding establishing
equipment categories based on operating ranges of greater than or equal
to 25 [deg]F for commercial refrigerators, below 25 [deg]F for
commercial freezers, and a combination of the two for commercial
refrigerator-freezers, DOE believes that 32 [deg]F is a more
appropriate temperature threshold for differentiating chilled from
frozen food storage equipment. Equipment that can operate at 25 [deg]F
is functionally a freezer, since food is primarily composed of liquid
water and water freezes at 32 [deg]F. In addition, an operating
temperature threshold of 32 [deg]F was determined in the 2009 CRE
energy conservation standards final rule and has been in place
historically for the purposes of compliance with those standards since
January 1, 2012. 74 FR 1092, 1099-1100 (Jan. 9, 2009). DOE notes that
the equipment mentioned by Traulsen, which operates both at or above 32
[deg]F and below 32 [deg]F, would qualify as both a commercial
refrigerator and a commercial freezer and would have to be certified in
both equipment categories. To the extent that the equipment was not
able to reach the rating temperature for commercial freezers of 0
[deg]F, the equipment would be tested at its LAPT for certification as
a freezer.
In the October 2013 test procedure NOPR, DOE recognized that some
basic models may have operating characteristics that include an
operating temperature range that spans multiple equipment classes, and
proposed language to clarify that equipment meeting the definition of
multiple equipment classes when operated as intended by the
manufacturer would have to be tested and certified as each of these
equipment classes to demonstrate compliance with DOE's energy
conservation standards. 78 FR at 64304 (Oct. 28, 2013).
Zero Zone and AHRI disagreed with DOE's proposal that the equipment
capable of operating in two or more operating temperature ranges be
tested and certified as complying with both equipment classes. Zero
Zone and AHRI suggested that these cases be tested and certified at
their lowest published operating temperature, which would be reflective
of the highest energy use mode. (Zero Zone, No. 18 at p. 2; AHRI, No.
15 at p. 4) Zero Zone added that if DOE requires equipment to be tested
at all the published operating temperature ranges, more-complex
controls may be required to reduce energy so the equipment can meet the
energy conservation standards for both
[[Page 22291]]
equipment categories, and suggested that DOE consider the increased
cost of these controls compared to the benefits to consumers. Zero Zone
added that, in general, remote freezers can be operated inefficiently
as a refrigerator by customer settings on the remote condensing unit,
but added that it does not condone such operation. As such, Zero Zone
suggested DOE use the term ``marketed operating temperature'' to avoid
having equipment potentially tested at two different temperature
classes because it can be operated at two or more temperature class
operating ranges even though it is not designed for use in these
operating temperature ranges. (Zero Zone, No. 18 at p. 2)
In contrast, NEEA supported DOE's proposal that equipment intended
to operate in multiple equipment classes be tested and certified in
each equipment class to demonstrate compliance with DOE's energy
conservation standards because NEEA believed it will allow a level
playing field for manufacturers to produce energy compliant
refrigeration equipment. (NEEA, No. 16 at p. 2)
DOE considered comments submitted by interested parties regarding
the potential for commercial refrigeration equipment classified into
two equipment categories. Zero Zone and AHRI both suggested that
equipment instead be deemed compliant based on testing and
certification in the more-stringent configuration or most energy-
consuming mode. Zero Zone also discussed the example of a dual
temperature unit that can operate as a commercial refrigerator or a
commercial freezer. DOE notes that, while the freezer configuration
would represent the most energy-consuming mode, determining the more-
stringent standard level is less straightforward. Although the freezer
configuration may use more energy, the energy conservation standard
level for the refrigerator configuration may in fact be more stringent.
This would especially be true if the operating range of the case was
such that the CRE model could not be tested at the rating temperature
of 0 [deg]F for freezers. For example, in the case of a piece of
commercial refrigeration equipment that has an operating temperature
range of 10 to 50 [deg]F, the unit can operate as a refrigerator, at or
above 32 [deg]F, or be converted to operate as a freezer, but only down
to 10 [deg]F. Thus, the unit cannot operate at the rating temperature
for freezers of 0 [deg]F and would be certified at the equipment's LAPT
of 10 [deg]F. However, the equipment, when tested at the LAPT, would
still be subject to the same energy conservation standard and, as such,
the freezer energy conservation standard would be much easier to meet.
In addition, rating the equipment as a freezer may or may not
accurately represent the use of the equipment in the field. That is,
dual temperature equipment may spend considerable operating hours as a
refrigerator and less significant operating hours as a freezer. This
may be the case in a commercial kitchen, for example, where freezer
space is necessary at the beginning of the week when new product
arrives, but is converted to refrigerator space over the course of the
week as food is prepared and stored for more immediate use. DOE does
not find it tenable that dual temperature equipment operating
inefficiently as a refrigerator most of the time could be compliant
with DOE's energy conservation standards due to its certification as a
commercial freezer only.
DOE acknowledges Zero Zone's concern that equipment that can
operate as a refrigerator or a freezer may require more-complex
controls to meet DOE's energy conservation standards as both a
refrigerator and a freezer. However, based on the difficulty in
determining the ``more-stringent'' standard and the potential for
certification of otherwise non-compliant equipment, DOE believes that
this incremental burden is justified to ensure compliance with DOE's
energy conservation standards. Further, DOE notes that equipment that
can operate as both a refrigerator and a freezer competes directly with
equipment in both categories and, as such, must be certified to meet
the energy conservation standard for both equipment categories to
provide a fair and level playing field when selling this equipment in
the market.
In this test procedure final rule, DOE continues to require that
self-contained equipment or remote condensing equipment with
thermostats capable of operating at IATs that span multiple equipment
categories be certified and comply with DOE's regulations for each
applicable equipment category. Similarly, DOE adopts requirements for
remote condensing equipment without a thermostat that specify that if a
given basic model of CRE is marketed, designed, or intended to operate
at IATs spanning multiple equipment categories, the CRE basic model
must be certified and comply with the relevant energy conservation
standards for all applicable equipment categories.
4. Proper Configuration and Use of Components or Features in the DOE
Test Procedure
In response to several inquiries from interested parties regarding
the proper configuration and use of certain components or features
specified in the DOE test procedure, DOE proposed specific provisions
in the October 2013 test procedure NOPR for the treatment of energy
management systems and case lighting when conducting the DOE test
procedure. 78 FR at 64304-64306 (Oct. 28, 2013). In addition, DOE also
addressed and clarified the appropriate temperatures of test packages
when loaded into the test unit. 78 FR at 64306 (Oct. 28, 2013). These
proposals, comments received by interested parties, and DOE's responses
are summarized in the subsequent sections.
a. Energy Management Systems
The DOE test procedure specifies that all devices that would
normally be used in the field must be installed and operated in the
same manner during the test unless such installation and operation is
inconsistent with any requirement of the test procedure.\12\ Such
devices include energy management systems. In the October 2013 test
procedure NOPR, DOE presented its interpretation of energy management
systems as electronic devices that control specific systems in
commercial refrigeration equipment to save energy, for example,
automatic controls that are capable of turning off cabinet lights on a
predetermined schedule or in response to an external variable,
increasing the temperature setting of the thermostat (in refrigerators
that store non-perishable items) during non-merchandizing hours, or
activating and deactivating anti-sweat heaters, pan heaters, or defrost
heaters. 78 FR at 64304 (Oct. 28, 2013).
---------------------------------------------------------------------------
\12\ ASHRAE 72-2005, section 6.1.1, ``Accessories,'' as
incorporated by reference into the DOE test procedure at 10 CFR
431.64.
---------------------------------------------------------------------------
In the October 2013 test procedure NOPR, DOE further proposed that,
if normal field installation or operation of any device would be
inconsistent with any test procedure requirement, then the specific
function of that device that causes inconsistency with the DOE test
procedure provisions must be disabled for the duration of the test. In
addition, if the device is designed for multiple functions, only those
functions of the device that cause inconsistency with the DOE test
procedure requirements must be disabled. 78 FR at 64321 (Oct. 28,
2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of energy management systems during the
DOE test procedure and, as such, is adopting the proposal presented in
the October
[[Page 22292]]
2013 test procedure NOPR with no modifications.
b. Lighting
The DOE test procedure specifies that all devices that would
normally be used in the field must be installed and operated in the
same manner during the test. 10 CFR 431.64. Specifically, due to
language and provisions in ARI 1200-2006 (as incorporated by reference
in the 2006 test procedure final rule) and AHRI 1200-2010 (as
incorporated by reference in the 2012 test procedure final rule and
this test procedure update) regarding case lighting, DOE believes that
the energy consumption associated with lights installed on a model of
commercial refrigeration equipment are intended to be captured during
testing. In addition, the DOE test procedure requires that all standard
components, such as shelves, end enclosures, lights, anti-condensate
heaters, racks, and similar items that would normally be used during
shopping or working periods, shall be installed and used as recommended
by the manufacturer, which DOE interprets to mean that if lighting is
installed on the case, the lighting should be operated as intended to
be used in the field. However, due to the variety of types of lighting
controls and schemes available on the market, the existing provisions
for ``accessories'' may prove insufficient to yield consistent results
during testing. Therefore, in the 2012 test procedure final rule, DOE
established specific periods in the test during which these variable
lights may be turned off or dimmed to account for energy savings due to
installed occupancy sensors or scheduled lighting controls. 77 FR at
10319-10320 (Feb. 21, 2012).
In the October 2013 test procedure NOPR, to clarify the treatment
of lighting under DOE's test procedure, DOE proposed to specify in
Appendix A to Subpart C that all lighting must be energized to the
maximum illumination level for the duration of testing for commercial
refrigeration equipment except for closed solid models of commercial
refrigeration equipment that include automatic controls that disable
case lighting when the door is closed, the use of which is specified by
the manufacturer instructions. DOE also proposed to specify in Appendix
B to Subpart C, which will be required for equipment testing on or
after the compliance date of any amended energy conservation standards,
that case lighting shall be energized to its maximum illumination level
except for when a model of commercial refrigeration equipment is
equipped with lighting occupancy sensors and/or scheduled controls, or
when the a model is outfitted with other permanently installed,
automatic energy management systems that control case lighting. 78 FR
at 64305-64306 (Oct. 28, 2013).
Zero Zone commented that they agree with DOE's proposed exception
for solid door models that utilize an automatic control to disable case
lighting when the door is closed. However, Zero Zone did not believe
DOE's treatment of manual case lighting adjustment, such as light
switches, is consistent with its treatment of manually deployable night
curtains for open cases. (Zero Zone, No. 18 at p. 3) In addition, Zero
Zone was concerned that an open case model with several lighting
options would be tested with all lights installed for the test
procedure, but the customer may choose to have a select amount of the
lights on in the operation of the installed case. Zero Zone inquired if
each lighting scheme in the open case model would be considered a base
model and tested separately. (Zero Zone, Public Meeting Transcript, No.
7 at pp. 153-154) True commented that certain occupancy sensors with a
learning curve built into them would not be able to be accurately
tested since there is no activity near the unit during testing. True
added that they can be programmed to override the sensor if needed.
(True, Public Meeting Transcript, No. 7 at pp. 155-156)
DOE acknowledges Zero Zone's comment regarding the consistency of
the DOE test procedure as it relates to the treatment of manual
lighting controls and manual night curtains. DOE addressed this issue
in the 2012 test procedure final rule, in which DOE stated that night
curtains represent an incremental cost and explicit energy management
feature that must be uniquely specified on commercial refrigeration
equipment, making it unlikely that customers would purchase a case with
night curtains and not employ them. By contrast, manual light switches
may be installed for a variety of energy- or utility-related reasons
and typically come standard on a baseline unit of commercial
refrigeration equipment. As such, DOE finds it less likely that
customers will employ manual light switches to adjust case lighting
during unoccupied periods with any regularity. 77 FR at 10299-10300
(Feb. 21, 2012). DOE continues to maintain that the incremental cost of
night curtains and dedicated use as an energy-efficiency feature make
them unique from manual light switches and justify different treatment
in the DOE test procedure.
In response to Zero Zone's comment regarding the variety of
lighting options available for installation on a given model of
commercial refrigeration equipment, DOE notes that these different
lighting schemes will have an impact on the measured daily energy
consumption of the case. As such, each light option could be treated as
an individual basic model and be tested and certified as such. However,
to the extent that manufacturers do not wish to account for the reduced
energy consumption associated with reduced lighting configurations, all
lighting configurations may be grouped into a CRE basic model. In this
case, the CRE basic model would be tested and certified based on the
lighting configuration with the maximum lighting energy usage and all
individual models certified under that basic model would receive that
rating.
In response to True's comment regarding lighting controls that are
triggered by occupancy sensors, these lighting controls should
currently be tested with all the controlled lighting turned on to the
maximum illumination level and the occupancy sensor disabled to
determine whether the model complies with existing energy conservation
standards, as reflected in Appendix A. Beginning on the compliance date
of any amended energy conservation standards for commercial
refrigeration equipment, manufacturers shall use the prescribed test
provisions for cases with lighting occupancy sensors included in
Appendix B.
c. Test Package Temperatures
The ASHRAE 72-2005 method of test, as referenced by ARI 1200-2006
and AHRI 1200-2010, and thus incorporated by the DOE test procedure at
10 CFR 431.64, provides specific instruction at section 6.2 as to the
loading of test simulators and filler packages. ASHRAE 72-2005 also
requires temperature stabilization before the formal test period
begins, as detailed in section 7.4. After steady-state operation is
reached, the unit must then operate for another period of 12 hours
without any adjustment to the controls before it is deemed to be
stabilized and the testing can begin. These established stabilization
requirements are designed to ensure that the product simulators and
test packages are cooled to the test temperature prior to initiation of
the test period and data collection, and the unit of commercial
refrigeration equipment under test is not operating in a pull-down
application during any part of the DOE test procedure.
In response to inquiries received by interested parties, DOE
presented clarification of these stabilization requirements in the
October 2013 test
[[Page 22293]]
procedure NOPR, but did not find that the test procedure required more
explicit clarification. 78 FR at 64306 (Oct. 28, 2013). DOE did not
receive any comments from interested parties on its proposal regarding
treatment of test package temperatures during the DOE test procedure
and, as such, is adopting the proposal presented in the October 2013
test procedure NOPR with no modifications.
5. Treatment of Other Specific Equipment Features and Accessories
During Testing
During the negotiated rulemaking for certification of commercial
heating, ventilation, air conditioning, refrigeration, and water
heating equipment, stakeholders raised a number of issues regarding the
treatment during the DOE test procedure of specific features,
components, and accessories that may be in place on certain basic
models of commercial refrigeration equipment. In the October 2013 test
procedure NOPR, DOE presented proposals that resulted from the
negotiations regarding the treatment of specific features, components,
and accessories. 78 FR at 64306-64308 (Oct. 28, 2013). The specific
proposals and the resultant amendments adopted in this final rule are
discussed in the following sections.
a. Customer Display Signs/Lights
Manufacturers stated that some customers, when ordering commercial
refrigeration equipment, may wish to add additional exterior signage,
outside of the body of the refrigerated cabinet, to certain units of a
given model to advertise the product inside. This lighting and signage
is optional and is not integral to the cabinet. Further, this auxiliary
signage does not illuminate product inside the body of the cabinet.
During the negotiations, stakeholders inquired regarding how this
lighting or signage should be treated during testing.
In the October 2013 test procedure NOPR, DOE proposed that under
the DOE test procedure, all lighting that is integral to the
refrigerated cabinet or illuminates the product contained within must
be operational during the test, and DOE proposed to add clarifying
language in the regulatory text to address customer display signs/
lights. Under DOE's proposal, supplemental lighting that exists solely
for the purposes of advertising or drawing attention to the case and is
not integral to the case would not be operated during testing under the
DOE test procedure. 78 FR at 64306 (Oct. 28, 2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of customer display signs/lights during
the DOE test procedure and, as such, is adopting the proposal presented
in the October 2013 test procedure NOPR with no modifications.
b. Condensate Pan Heaters and Pumps
Commercial refrigeration equipment captures water from the air
entering the cabinet during operation by causing the water to condense
and then freeze on the evaporator coil of the equipment. During a
defrost cycle, this frost is melted and the meltwater produced must be
removed from the unit. In many types of equipment, this meltwater is
collected in a pan beneath the unit. Some models of commercial
refrigeration equipment come equipped with electric resistance heaters
that evaporate this water out of the pan and into the ambient air.
Other models may come equipped with pumps that send meltwater to an
external drain.
In the October 2013 test procedure NOPR, DOE proposed that, during
the DOE test procedure, these electric resistance heaters and
condensate pumps must be installed and operational during the entire
test (as per section 6.1.1, ``Accessories,'' of ASHRAE 72-2005) and
clarified that the ``entire test'' includes stabilization (including
pull-down), steady-state, and performance testing periods. Prior to the
start of the stabilization period, as defined by ASHRAE 72-2005, the
condensate pan should be dry, and during the entire test following the
start of the stabilization period, any condensate moisture generated
should be allowed to accumulate in the pan as it would during normal
operation, with no manual removal of water at any time during the
entire test. DOE proposed that if a manufacturer offers a given basic
model for sale with an available condensate pan heater or pump, the
manufacturer must make representations of the performance of the basic
model as tested with the feature in place, and DOE proposed clarifying
language in the regulatory text to address condensate pan heaters and
pumps. 78 FR at 64306 (Oct. 28, 2013).
In response to DOE's proposal in the October 2013 test procedure
NOPR, AHRI, Hussmann, and Zero Zone commented that condensate pan
heaters should not be required to be tested for remote equipment, since
they are not accounted for in the energy conservation standard
engineering analysis. (AHRI, No. 15 at p. 3; Hussmann, No. 11 at p. 4;
Zero Zone, No. 18 at p. 2) AHRI commented that condensate pan heaters
or pumps are usually added in the field to fulfill specific needs of
commercial customers and are typically installed on less than 5 percent
of the total remote cases sold within the U.S. AHRI further commented
that it is unreasonable to require manufacturers to test potentially
all remote equipment with condensate pan heaters to certify its basic
models to DOE, if those models may be sold with condensate pan heaters
in some specific applications. (AHRI, No. 15 at p. 3) Hussmann
corroborated that remote equipment shipped with condensate pan heaters
represents less than 1 percent of case volume for Hussmann and stated
its belief that the discussions during the negotiated rulemaking
(Docket No. EERE-2013-BT-NOC-0023) were primarily surrounding self-
contained equipment. (Hussmann, No. 11 at p. 4)
Zero Zone added that if case manufacturers are deterred from
supplying condensate pan heaters, end users will work around this by
buying condensate pans from third parties that typically are not
Underwriters Laboratories (UL) Recognized or UL Listed and do not come
with protective covers. (Zero Zone, No. 18 at pp. 2-3)
DOE acknowledges the opinions of interested parties and agrees that
condensate pan heaters and pumps are not common on remote equipment. As
such, DOE agrees that determination of daily energy consumption for
remote cases with condensate pan heaters may not be the most
representative configuration. Thus, DOE is adopting language in this
final rule applying the requirements for testing with condensate pan
heaters and pumps in place for self-contained equipment only.
DOE notes that whether or not condensate pan heaters were included
in DOE's engineering analysis and energy modeling to support standard
development is not dispositive as to what features are included and
accounted for when testing a given basic model of commercial
refrigeration equipment. DOE models a representative model for each
equipment class, but manufacturers may deviate from that assumed
representative model in any number of ways, including the addition of
features and accessories that improve the utility of cases in specific
applications, such as condensate pan heaters and pumps.
c. Anti-Sweat Door Heaters
Many transparent-door cases come equipped with anti-sweat electric
resistance heaters that serve to evaporate any water that condenses on
the transparent surface of the door
[[Page 22294]]
during operation. In some instances, manufacturers may equip their
cases with higher-powered anti-sweat heaters in anticipation of
potential adverse operating conditions.
In the October 2013 test procedure NOPR, DOE proposed that anti-
sweat heaters should be operational during testing under the DOE test
procedure and proposed adding clarifying language in the regulatory
text to address anti-sweat door heaters. Models with a user-selectable
setting must be tested with the anti-sweat heaters turned on and set to
the maximum usage position and models featuring an automatic, non-user
adjustable controller that turns on or off based on environmental
conditions must be tested with the controller operating in the
automatic state. Additionally, DOE proposed that, if a unit is not
shipped with a controller from the point of manufacture, and is
intended to be used with a controller, the manufacturer must make
representations of the basic model based on the rated performance of
that basic model as tested when equipped with a controller intended by
the manufacturer for use with the unit. 78 FR at 64306-64307 (Oct. 28,
2013).
NEEA stated that it supports DOE's proposal that anti-sweat heaters
be in operation during testing unless controls are shipped with the
unit and can be turned off by these controls during testing. (NEEA, No.
16 at pp. 2-3) DOE did not receive any negative comments from
interested parties on its proposal regarding treatment anti-sweat door
heater in the DOE test procedure and, as such, is adopting the proposal
presented in the October 2013 test procedure NOPR with no
modifications.
d. Ultraviolet Lights
Some manufacturers equip certain models of commercial refrigeration
equipment with ultraviolet lights, which can be operated by end users
to neutralize pathogens and ensure case cleanliness. Manufacturers
inquired as to how these will be addressed by the DOE test procedure.
In the October 2013 test procedure NOPR, DOE proposed that ultraviolet
lights should not be turned on during the test procedure and proposed
adding regulatory text to clarify this position. 78 FR at 64307 (Oct.
28, 2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of ultraviolet lights during the DOE test
procedure and, as such, is adopting the proposal presented in the
October 2013 test procedure NOPR with no modifications.
e. Illuminated Temperature Displays and Alarms
Manufacturers may equip some commercial refrigeration equipment
models with illuminated displays that provide visual information to the
equipment operator regarding, for example, the temperature inside the
refrigerated case or if the case temperature falls outside of a
specified range. DOE understands these items to be features integral to
the design of the given model and proposed that they should be enabled
during the test as they would be during normal field operation. In the
October 2013 test procedure NOPR, DOE proposed to add clarifying
language in the regulatory text to address illuminated temperature
displays and alarms. 78 FR at 64307 (Oct. 28, 2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of illuminated temperature displays and
alarms during the DOE test procedure and, as such, is adopting the
proposal presented in the October 2013 test procedure NOPR with no
modifications.
f. Condenser Filters
Manufacturers may offer models equipped with non-permanent filters
over a model's condenser coil to prevent particulates such as flour
from blocking the condenser coil and reducing airflow. In the October
2013 test procedure NOPR, DOE proposed that these filters should be
removed during the DOE test procedure and proposed to add clarifying
language as part of the regulatory text. 78 FR at 64307 (Oct. 28,
2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of condensate filters during the DOE test
procedure and, as such, is adopting the proposal presented in the
October 2013 test procedure NOPR with no modifications.
g. Refrigeration System Security Covers
Manufacturers may offer for sale with a basic model an option to
include straps or other devices to secure the condensing unit and
prevent theft or tampering. In the October 2013 test procedure NOPR,
DOE proposed that these security devices should be removed during
testing under the DOE test procedure and proposed to add clarifying
language as part of the regulatory text to clarify this provision. 78
FR 64307 (Oct. 28, 2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of refrigeration system security covers
during the DOE test procedure and, as such, is adopting the proposal
presented in the October 2013 test procedure NOPR with no
modifications.
h. Night Curtains and Covers
Night curtains and night covers are defined at 10 CFR 431.62 as a
device that is deployed temporarily to decrease air exchange and heat
transfer between the refrigerated case and the surrounding environment.
In the October 2013 test procedure NOPR, DOE stated that the proper
treatment of these components during the DOE test procedure is
discussed in the current text of the DOE test procedure, 10 CFR 431.64,
as amended by the 2012 DOE test procedure final rule. DOE also added
these provisions at section 1.2.10 in Appendix B and proposed adding
language to clarify that night curtains may not be used when testing
under Appendix A. 78 FR at 64307 (Oct. 28, 2013).
DOE did not receive any comments from interested parties regarding
treatment of night curtains and covers during the DOE test procedure
and, as such, is adopting the proposal presented in the October 2013
test procedure NOPR with no modifications.
i. Grill Options
Manufacturers may offer for sale with a basic model optional grills
that are used to direct airflow in unique applications, such as when a
unit is mounted close to a rear wall and the airflow needs to be
directed upwards. In the October 2013 test procedure NOPR, DOE proposed
that, if present, non-standard grills should be removed during testing
under the DOE test procedure and proposed to add clarifying language as
part of the regulatory text. 78 FR at 64307 (Oct. 28, 2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of grill options during the DOE test
procedure and, as such, is adopting the proposal presented in the
October 2013 test procedure NOPR with no modifications.
j. Coated Coils
Coated coils, generally specified for use in units that will be
subjected to environments in which acids or oxidizers are present, are
treated with an additional coating (such as a layer of epoxy or
polymer) as a barrier to protect the bare metal of the coil from
deterioration through environmental contact. In the October 2013 test
procedure NOPR, DOE presented its belief that the existing DOE test
procedure accurately accounts for the
[[Page 22295]]
performance of all types of coils, including those with coatings, and
that no additional accommodations or clarifications are needed in the
test procedure. Commercial refrigeration equipment with coated coils
shall be tested in accordance with the DOE test procedure, as specified
at appendices A and B to subpart C of 10 CFR part 431. 78 FR at 64307
(Oct. 28, 2013).
DOE did not receive any comments from interested parties regarding
treatment of coated coils during the DOE test procedure and, as such,
is adopting the proposal presented in the October 2013 test procedure
NOPR with no modifications.
k. Internal Secondary Coolant Circuits
The use of internal, secondary, working fluid that is cooled by a
remote condensing unit is a proprietary design that purportedly allows
for greater control of unit temperature, and may present other
attributes desirable to a customer. In the October 2013 test procedure
NOPR, DOE stated that it found no evidence indicating that this design
could not be tested using the DOE test procedure as written, as the
operation of equipment with internal secondary coolant circuits would
be effectively the same as that of a standard remote condensing case
from the perspective of the test procedure. 78 FR at 64307 (Oct. 28,
2013).
DOE did not receive any comments from interested parties regarding
treatment of internal secondary coolant circuits during the DOE test
procedure and, as such, is adopting the proposal presented in the
October 2013 test procedure NOPR with no modifications.
l. Wedge Cases
Wedge cases are models of commercial refrigeration equipment that
fit between two other cases to fill a gap (such as in a corner) in a
continuous case lineup. They may require air spillover from adjacent
cases to meet the manufacturer's design temperatures. During the
negotiation proceedings, manufacturers inquired as to how wedge cases
should be treated under the DOE test procedure.
DOE considered the coverage and testing of wedge cases in the 2009
energy conservation standards final rule. 74 FR 1092, 1102-1103 (Dec.
9, 2009). Based on that assessment, DOE understands that wedge cases
meet the definition of commercial refrigeration equipment and fall into
existing CRE equipment classes. In the October 2013 test procedure
NOPR, DOE stated that it is unaware of any technical attributes that
prevent wedge cases from being tested using the DOE test procedure, or
that the DOE test procedure is not representative of the energy use of
a given basic model of wedge case. 78 FR at 64307 (Oct. 28, 2013).
DOE did not receive any comments from interested parties regarding
treatment of wedge cases during the DOE test procedure and, as such, is
adopting the proposal presented in the October 2013 test procedure NOPR
with no modifications.
m. Misting or Humidification Systems
Manufacturers may offer for sale with a basic model optional
misting or humidification systems, which dispense a water mist used to
maintain the optimal quality of products. These are commonly used with
cases containing, for example, fresh produce, meat, or seafood. In the
October 2013 test procedure NOPR, DOE proposed that, if present, these
systems should be inactive during testing under the DOE test procedure
and proposed to add clarifying language as part of the regulatory text.
78 FR at 64307-64308 (Oct. 28, 2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of misting or humidification systems
during the DOE test procedure and, as such, is adopting the proposal
presented in the October 2013 test procedure NOPR with no
modifications.
n. Air Purifiers
Manufacturers may offer for sale purifying systems to remove
contaminants from air recirculated within the interior of a
refrigerated case. In the October 2013 test procedure NOPR, DOE
proposed that air purifiers should be inactive during testing under the
DOE test procedure and proposed to add clarifying language as part of
the regulatory text. 78 FR at 64308 (Oct. 28, 2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of air purifiers during the DOE test
procedure and, as such, is adopting the proposal presented in the
October 2013 test procedure NOPR with no modifications.
o. General Purpose Outlets
Some commercial refrigeration equipment may be offered for sale
with integrated general purpose electrical outlets, which may be used
to power additional equipment such as scales or slicers. In the October
2013 test procedure NOPR, DOE proposed that, during testing under the
DOE test procedure, no external load should be connected to the general
purpose outlets contained within a unit and proposed to add clarifying
language as part of the regulatory text. 78 FR at 64308 (Oct. 28,
2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of general purpose outlets during the DOE
test procedure and, as such, is adopting the proposal presented in the
October 2013 test procedure NOPR with no modifications.
p. Crankcase Heaters
Some models of self-contained commercial refrigeration equipment
feature electric resistance heaters designed to keep the compressor
warm in order to maintain the refrigerant contained within at optimal
conditions when the unit is operating at low ambient temperatures. In
the October 2013 test procedure NOPR, DOE proposed that, if present,
crankcase heaters should be operational during the test. Under this
proposal, if a control system, such as a thermostat or electronic
controller, is used to modulate the operation of the crankcase heater,
it should be used as intended per the manufacturer's instructions. DOE
proposed to add clarifying language regarding testing units with
crankcase heaters. 78 FR at 64308 (Oct. 28, 2013).
DOE did not receive any comments from interested parties on its
proposal regarding treatment of crankcase heaters during the DOE test
procedure and, as such, is adopting the proposal presented in the
October 2013 test procedure NOPR with no modifications.
q. Interior/Exterior Liners
Manufacturers may offer for sale a variety of different interior or
exterior liner materials with a given CRE basic model. These liners, by
virtue of differences in thickness, composition, and other physical
attributes, could change the insulative properties of the case walls
and thus alter the energy consumption of the case. The test procedure
estimates the heat loss from the refrigerated space to the surroundings
by measuring the amount of energy needed to maintain the refrigerated
space at the given rating temperature. In the October 2013 test
procedure NOPR, DOE presented its belief that the DOE test procedure
adequately accounts for variability in the energy consumption of models
with different liner types just as it accounts for the energy
performance of models with varying levels of insulation. Therefore, DOE
did not propose any additional measures to accommodate these equipment
features. 78 FR at 64308 (Oct. 28, 2013).
DOE did not receive any comments from interested parties on its
proposal
[[Page 22296]]
regarding treatment of interior/exterior liners during the DOE test
procedure and, as such, is adopting the proposal presented in the
October 2013 test procedure NOPR with no modifications.
r. Crankcase Pressure Regulators
During the 2013 Working Group meetings, stakeholders mentioned that
they sometimes equip the compressors of self-contained commercial
refrigeration units with devices called crankcase pressure regulators.
The function of these devices is to maintain optimal gas pressure
within the compressor crankcase in instances where the voltage input to
the compressor may not be uniform. This often is the case, for example,
in rural locations where the transmission system may experience
interruptions or fluctuations resulting in line voltage drops. Working
Group members agreed unanimously that manufacturers should offer an
identical model without this feature for the purposes of testing. DOE
plans to address this through guidance.
s. Other Comments Received From Interested Parties
In response to the October 2013 test procedure NOPR, DOE received
several additional comments pertaining to its treatment of accessories
generally. Zero Zone agreed with DOE's accommodations of some specific
accessories and features proposed in the October 2013 test procedure
NOPR. However, Zero Zone questioned why DOE did not make allowances for
customers with high ambient humidities and allow the use of higher
anti-sweat heat for those applications. Zero Zone recommended that, to
be consistent, DOE should require testing with the options it plans to
exclude in this rulemaking, and if the equipment can't pass the energy
standard with these options installed, customers need to modify their
stores to avoid the need for the equipment modifications. (Zero Zone,
No. 18 at p. 3)
The government of the People's Republic of China (China)
recommended that all non-core energy-consuming accessories, such as
lighting associated with short-term opening and closing of the
refrigerator door, networking and standby, or operation of the
deodorizing system, should be left out and not included in the
measurement of daily energy consumption. (China, No. 10 at p. 2) In
addition, China recommended that, if a manufacturer included in their
product literature information that the operation of some functions was
auxiliary to the effective operation of the refrigeration equipment,
their energy consumption would account for a small proportion of total
energy consumption and could be excluded from the calculation of total
or combined daily energy consumption. (China, No. 10 at p. 4)
In response to Zero Zone's comment regarding accounting for the use
of anti-sweat heaters at high humidities in the DOE test procedure, DOE
notes that its test procedure is meant to represent an average cycle of
use. The ambient temperatures required in the DOE test procedure are
75[emsp14][deg]F and 45 percent relative humidity. These ambient
conditions apply to all equipment and are meant to be representative of
the typical installation conditions for most commercial refrigeration
equipment. DOE does not believe that the additional complexity and
burden associated with testing at additional or different ambient
temperature conditions for some equipment is justified to capture
additional use of anti-sweat heaters. DOE notes that, as presented in
section III.A.5.c, this final rule establishes provisions that anti-
sweat door heaters that do not have automatic controls should be
energized when testing in accordance with the DOE test procedure and
that energy use due to anti-sweat door heaters that have automatic
controls will be captured based on the control algorithm associated
with the automatic control scheme.
In response to China's comment regarding the treatment of non-core
or auxiliary accessories, DOE believes that, to a large extent, the
provisions adopted in this section address the appropriate treatment of
specific non-core and auxiliary accessories. DOE notes that, to ensure
consistent and repeatable testing, it is beneficial to adopt specific
test provisions for the treatment of specific accessories. The
proposals adopted in this test procedure final rule address specific
accessories agreed upon as a result of negotiations between DOE and
interested parties. DOE does not believe adopting more-general
provisions for the treatment of ``non-core'' accessories, as suggested
by China, is necessary. In addition, DOE believes such ambiguous
provisions may result in misinterpretation and lack of consistency in
implementation of the test procedure. Therefore, DOE is not adopting
provisions for testing of accessories other than those proposed in the
October 2013 test procedure NOPR. 78 FR at 64306-08 (Oct. 28, 2013).
6. Rounding of Test Results and Certified Ratings
The current DOE test procedure, which incorporates by reference
provisions from ARI 1200-2006 and AHRI 1200-2010, requires that the
calculated daily energy consumption (CDEC), for remote condensing
equipment, and the total daily energy consumption (TDEC), for self-
contained refrigeration equipment, be expressed in terms of kilowatt-
hours (kWh) per day and must be stated in increments of 0.01 kWh per
day. This is consistent with the number of significant figures
expressed in the energy conservation standards listed at 10 CFR 431.66.
DOE's requirements for calculating test results and certified
ratings for covered commercial refrigeration equipment are found at 10
CFR 431.64 and 10 CFR 429.42, respectively. The DOE test procedure
currently requires that results for CDEC or TDEC resulting from testing
a single unit be rounded to 0.01 kWh per day. In the case where the
reported value is derived from testing, at least two or more units
should be tested pursuant to 429.42 and the appropriate sampling
statistics must be applied in order to develop the represented value.
DOE is adopting in this final rule provisions to clarify that the
represented value should also be rounded to the nearest 0.01 kWh per
day after application of the sampling statistics. For commercial
refrigeration equipment rated using an AEDM, the certified rating must
be derived pursuant to 429.70 and rounded to 0.01 kWh per day.
In the October 2013 test procedure NOPR, DOE proposed to clarify 10
CFR 431.64 by specifying that all calculations in the DOE test
procedure must be carried out using raw, measured values, and the
results from the testing of a single unit of a given basic model should
be expressed in 0.01 kWh per day. DOE also proposed to update the
language at 10 CFR 429.42 to reflect the same rounding requirements,
namely that certified ratings be expressed in 0.01 kWh per day
increments. 78 FR at 64308 (Oct. 28, 2013).
In response to this proposal, Traulsen suggested that, in lieu of
leaving an ambiguous rounding factor that may result in inconsistencies
between manufacturers or reporting entities, DOE require all
calculations to be carried out to the third decimal point and rounding
to the second decimal point for the purposes of certification and
compliance with DOE's energy conservation standards. (Traulsen, No. 17
at p. 3) Southern Store Fixtures commented that the rounding of test
results and the raw data, per ASHRAE Standard 72, is carried to one
decimal point and should be consistent with this test procedure.
(Southern Store Fixtures, Public Meeting Transcript, No. 7 at p. 165)
[[Page 22297]]
In response to Southern Store Fixtures' comment regarding values in
ASHRAE 72-2005 that are carried to the first decimal point, DOE notes
that pressure and temperature measurements are specified to the first
decimal point and reporting these values to the third decimal point may
be inappropriate. However, these values are not used directly in the
calculation of TDEC or CDEC, and the number of significant digits past
the decimal is not relevant. For these quantities, the number of
significant digits to be carried through calculations is dictated by
the number of significant digits in the value as a whole, and at least
three significant digits are expected for all these quantities.
In this final rule, DOE is not modifying the proposal presented in
the October 2013 test procedure NOPR, and is adopting in this test
procedure final rule language that all calculations in the DOE test
procedure must be carried out using raw, measured values and the
results from the testing of a single unit of a given basic model should
be expressed in 0.01 kWh per day.
7. Testing at the Lowest Application Product Temperature
In the 2012 test procedure final rule, DOE establishes provisions
for testing equipment that is not capable of achieving the prescribed
rating temperature for its respective equipment class: 38 [deg]F
(2 [deg]F) for commercial refrigerators, 0 [deg]F (2 [deg]F) for commercial freezers, and -15 [deg]F (2
[deg]F) for ice-cream freezers. 77 FR at 10320 (Feb. 21, 2012). This
equipment includes, for example, floral cases and ice storage cases,
which do not have operating temperatures that are low enough to meet
their respective rating temperature requirements. The 2012 test
procedure amendments specify that such equipment must be tested at its
LAPT, instead of the specified rating temperature for its given
equipment class. 77 FR at 10320 (Feb. 21, 2012). DOE regulations at 10
CFR 431.62 define LAPT as the integrated average temperature closest to
the specified rating temperature for a given piece of equipment
achievable and repeatable such that the IAT of a given unit is within
2 [deg]F of the average of all IAT values for that basic
model. For cases with thermostats, this will be the lowest thermostat
set point.
a. Definition of Lowest Application Product Temperature
In the October 2013 test procedure NOPR, DOE clarified the
definition and intent of the LAPT for equipment that cannot maintain
the prescribed rating temperature. 78 FR at 64308-09 (Oct. 28, 2013).
That is, DOE specified the LAPT is the lowest temperature at which a
given basic model is capable of operating, and equipment rated under
the LAPT provisions must be tested in accordance with all the
requirements of the DOE test procedure, except that the rating
temperature for this equipment will be the LAPT and the IAT measured
during the test will be within 2 [deg]F of the LAPT instead
of within 2 [deg]F of the prescribed rating temperature for
that equipment class. DOE acknowledged that the lowest operating
temperature for a given unit may vary slightly for specific units
tested under a given basic model due to manufacturing tolerances,
refrigerant charge, or other minor differences among units of a given
CRE basic model. However, the LAPT should be specified such that, if
DOE were to select a representative unit of this model randomly to test
for compliance purposes, DOE would be able to test the unit by setting
the unit to operate as cold as possible and achieve an integrated
average temperature that is 2 [deg]F of the LAPT. 78 FR
64308-09 (Oct. 28, 2013).
In response to DOE's proposed clarification of LAPT in the October
2013 NOPR, interested parties had several suggestions regarding the
definition of LAPT. Traulsen recommended the following clarification to
the LAPT definition: The term ``LAPT'' is attained by adjusting the
unit thermostat to the lowest operating temperature where the ``IAT''
is maintained at a condition of 2 [deg]F over the duration
of the test procedure. The LAPT value is equal to or greater than the
rating temperature based on refrigeration system capacity or lowest
possible thermostat set point. (Traulsen, No. 15 at p. 3) Hussmann
recommended that DOE change the definition of LAPT for remote equipment
without a thermostat from ``adjusted dew point'' to ``dew point,''
since that is what is controlled in a test environment. Hussmann also
stated that it believed the LAPT should not be below the manufacturer's
lowest specified operating temperature and that testing of the LAPT as
the ``temperature achieved with the adjusted dew point temperature (as
defined in AHRI Standard 1200 (I-P)-2010) set to 5 degrees colder than
that required to maintain the manufacturers lowest specified operating
temperature'' will only result in an unsuccessful, unrepeatable, non-
steady state test due to excessive ice build-up on the evaporator coil.
(Hussmann, No. 11 at p. 3)
DOE appreciates the recommendations submitted by interested parties
regarding the definition and specification of LAPT. Specifically, DOE
believes that Traulsen's recommended language is generally incorporated
into the existing definition and procedure proposed in the October 2013
test procedure NOPR. Further, DOE notes that the term ``LAPT'' should
be defined so as to describe the characteristics and specification of
the lowest IAT a CRE basic model is capable of achieving, rather than
the procedure for determining LAPT, which is described in the relevant
section of 10 CFR 431.64. DOE also notes that the LAPT for a given CRE
basic model does not have to be ``maintained'' throughout the test
procedure, but rather the IAT resulting from conducting the test
procedure should be within 2 [deg]F of the specified LAPT.
In addition, in response to Hussmann's recommendation regarding the
LAPT provisions for remote equipment that does not have a thermostat,
DOE agrees with Hussmann that it may be more appropriate to specify the
dew point, as opposed to the adjusted dew point for remote equipment.
AHRI 1200-2010 defines the dew point as the refrigerant vapor
saturation temperature at a specified pressure. This corresponds
typically to the temperature in the evaporator. Conversely, the
adjusted dew point is defined in AHRI 1200-2010 as a temperature lower
than the actual dew point to account for suction line pressure losses
and represents the saturated suction temperature at the compressor.
This is more representative of the refrigerant temperature entering the
compressor and is the value used to specify compressor performance for
the purposes of determining the CDEC for remote cases in AHRI 1200-
2010. AHRI 1200-2010 further specifies the adjusted dew point as 2
[deg]F lower than the evaporator dew point for commercial refrigerators
and 3 [deg]F lower than the evaporator dew point for commercial
freezers, when applying standardized assumptions regarding condensing
rack performance (see Table 1 in section 5, ``Rating Requirements for
Remote Commercial Refrigerated Display Merchandisers and Storage
Cabinets,'' of AHRI 1200-2010). While the dew point and the adjusted
dew point are dependent on one another, DOE acknowledges that the dew
point controls the internal refrigerated temperature directly and is
what is directly controlled in a test environment. DOE notes that
specifying
[[Page 22298]]
the dew point, rather than the adjusted dew point, as 5 degrees below
that required to maintain the manufacturer's lowest specified operating
temperature will not change the resultant LAPT value for remote
equipment, as the two values are dependent on one another.
Specifically, the adjusted dew point is specified as 3 [deg]F lower
than the dew point for commercial freezers and ice-cream freezers and 2
[deg]F lower than the dew point for commercial refrigerators.
In response to Hussmann's comment that specifying the adjusted dew
point as 5 degrees colder than that required to maintain the
manufacturer's lowest specified operating temperature will result in
internal refrigerated temperatures that may be lower than the
manufacturer's lowest specified operating temperature, which could lead
to ice buildup on the evaporator coil, DOE acknowledges that this may
be a concern but notes that this may be an issue for only a small
number of basic models. If a model is not able to operate consistently
at a temperature 5 degrees below the dew point required to maintain the
manufacturer's lowest specified operating temperature, a manufacturer
must request a test procedure waiver.
DOE notes that it adopted such language in the 2012 test procedure
final rule to ensure that the achieved LAPT represented a conservative
rating for remote equipment. DOE believed this was necessary because
the internal refrigerated temperature for remote equipment is so
variable and dependent on the remote condensing rack capacity and
operation. 77 FR at 10305 (Feb. 21, 2012). DOE is reluctant to revise
the LAPT for remote equipment without a thermostat as the dew point
required to achieve the necessary integrated average temperature inside
the case for that basic model. As recommended by Hussmann, this
approach would allow manufacturers to specify virtually any temperature
as the LAPT for a given CRE basic model, including a temperature not
representative of the lowest temperature the CRE model can achieve. As
such, DOE is adopting language that continues to establish the LAPT for
remote equipment without a thermostat based on specifying the dew point
as 5 degrees below the temperature required to maintain the lowest
specified operating temperature of that equipment.
b. Incorporation by Reference of ASHRAE 72-2005
Although ASHRAE 72-2005 is currently evoked as the DOE method of
test through DOE's incorporation by reference of ARI 1200-2006 and AHRI
1200-2010 as the test procedure for commercial refrigeration equipment,
DOE has never specifically incorporated by reference ASHRAE 72-2005.
Due to the explicit reference of ASHRAE 72-2005 in the proposed
definition of LAPT in the October 2013 test procedure NOPR, DOE
proposed to incorporate by reference ASHRAE 72-2005 at 10 CFR 431.63.
78 FR at 64309 (Oct. 28, 2013).
In response to DOE's proposal to incorporate by reference ASHRAE
72-2005, ASHRAE recommended that DOE update the reference of ANSI/
ASHRAE 72-2005 to the 2013 edition of this standard. (ASHRAE, No. 8 at
p. 1) DOE notes that, at this time, a new edition of ASHRAE 72 is not
available. DOE is aware that ASHRAE 72 is intended to be published
soon, but DOE is not electing to delay publication of this final rule
to accommodate ASHRAE's publication timeline. When a new edition of
ASHRAE 72 is available, DOE will review the revised test protocol and
consider amending DOE's test procedure to reference the updated ASHRAE
72 version, as appropriate.
8. Clarifications in Response to Interpretations to AHRI 1200-2010
The 2012 test procedure final rule amends the DOE test procedure
for commercial refrigeration equipment to reference AHRI 1200-2010 as
the method of test to be used as of the compliance date of the amended
standards established published in the March 2014 energy conservation
standards final rule. 77 FR at 10295-10296 (Feb. 21, 2012); 79 FR
17726, 17734 (Mar. 28, 2014).
In the October 2013 test procedure NOPR, DOE discussed five
interpretations to AHRI 1200-2010 that AHRI had recently published.
AHRI issued interpretations 1 through 4 to AHRI 1200-2010 to clarify
the method for calculation of TDA. Interpretation 5 to AHRI 1200-2010
clarifies the approach for testing commercial refrigeration equipment
with two independent refrigeration sections. 78 FR at 64309-64310 (Oct.
28, 2013). In the October 2013 test procedure NOPR, DOE presented its
belief that the TDA should be measured as the ``projected visible
area'' and discussed how Interpretations 1, 3, and 4 were consistent
with this method. Specifically, Interpretation 1 specifies that TDA
should not include any transparent areas where the view is blocked by
solid features, Interpretation 3 describes how to treat silk screens
and other semi-transparent coverings on transparent doors or panels,
and Interpretation 4 provides guidance to determine the area and length
of commercial refrigeration equipment with curved fronts. DOE did not
propose further clarification of the DOE test procedure beyond the
definition of ``transparent'' proposed in section III.B.2.a of the
October 2013 test procedure NOPR, believing that the existing test
instructions contained in ARI 1200-2006, AHRI 1200-2010, and the DOE
test procedure were sufficient to specify clearly how to calculate TDA
for cases with solid features covering portions of projected area or
for cases with non-rectangular geometries. 78 FR at 64310 (Oct. 28,
2013). However, DOE found Interpretation 2, which includes solid
features in the calculation of TDA such as door frames and mullions, to
be inconsistent with DOE's method of calculating TDA. DOE's proposed
method, comments received by interested parties, and DOE's responses
are laid out in more detail in section III.A.9.
DOE also reviewed Interpretation 5, which clarifies the method for
evaluating commercial refrigeration equipment with more than one
refrigerated section, and found that AHRI's Interpretation 5 is
consistent with the DOE test procedure for these systems, as specified
at 10 CFR 431.66(d)(2)(i), which explains how to test commercial
refrigeration equipment with more than one refrigerated compartment or
section. 78 FR at 64310 (Oct. 28, 2013).
In response to DOE's discussion of the AHRI interpretations in the
October 2013 test procedure NOPR, China recommended adding clarifying
language to specify how to calculate the TDA for curved front cases and
suggested that the TDA for these cases be based on the effective
projected area. (China, No. 10 at p. 3)
DOE acknowledges China's suggestion that the DOE test procedure
provide more-explicit guidance for how to calculate TDA for cases with
unique, non-rectangular geometries. DOE notes that AHRI Interpretation
4 lays out clearly the approach for doing so. DOE discussed this
approach in the October 2013 test procedure NOPR and determined that it
was consistent with the DOE test procedure and did not need
clarification. 78 FR at 64310 (Oct. 28, 2013). However, based on
China's request, DOE notes that some interested parties may find
additional clarification useful. As such, DOE is adopting additional
clarification in the DOE test procedure for cases with curved front
geometries.
DOE notes that, on October 1, 2013, ANSI approved a revised edition
of the AHRI 1200 test procedure, AHRI 1200-2013, which incorporates a
new graphic
[[Page 22299]]
to Appendix D describing the measurement of TDA for cases with curved-
fronts and adds language clarifying the calculation of the height
dimension (Dh). Specifically, AHRI 1200-2013 specifies that
the dimension L shall be taken as the arc length of the curves section
of visible product area. AHRI 1200-2013 also adopted language to
Appendix D that reads ``when measuring Dh, only the visible
dimension shall be considered. Opaque door frames, light shades, non-
transparent silk screens, and the like that impede visibility shall be
excluded from the measurement.'' AHRI 1200-2013 did not make any other
changes to the methods, nomenclature, or layout of AHRI 1200, and is
otherwise consistent with ARI 1200-2006 and AHRI 1200-2010, the test
procedures currently incorporated by reference into the DOE test
procedure.
In the 2012 test procedure final rule, DOE incorporated by
reference AHRI 1200-2010 as the test procedure for commercial
refrigeration equipment manufactured on or after the compliance date of
the amended energy conservation standards adopted in the March 2014
energy conservation standards final rule.\13\ 77 FR at 10295, 10308-09,
10318-21 (Feb. 21, 2012); 79 FR 17726, 17734 (Mar. 28, 2014). DOE also
maintained the incorporation by reference of ARI 1200-2006 for
equipment certified prior to March 28, 2017. 77 FR at 10318-10320 (Feb.
21, 2012). In the 2012 test procedure final rule, DOE discussed the
changes made between ARI 1200-2006 and AHRI 1200-2010 as including both
editorial and technical changes to (1) the equipment class nomenclature
used within the test procedure; (2) the integrated average rating
temperature for ice-cream freezers; and (3) the method of normalizing
and reporting units for equipment energy consumption. 77 FR at 10296
(Feb. 21, 2012). AHRI 1200-2013 differs from AHRI 1200-2010 in adopting
(1) a new definition of ``transparent surface,'' which is a surface
with a minimum of 65 percent light transmission or 65 percent clear
surface; (2) a new statement in Appendix D specifying that when
calculating Dh only the visible dimension shall be
considered; and (3) an additional figure, Figure D18, providing
clarification regarding the calculation of TDA for radius cases with
transparent sides.
---------------------------------------------------------------------------
\13\ In the 2012 test procedure final rule, DOE adopted a
specific date (January 1, 2016), which was the anticipated
compliance date for any standards amended as a result of the ongoing
CRE energy conservation standards rulemaking (Docket No. EERE-2010-
BT-STD-0003). However, DOE discussed in the preamble to the 2012
test procedure final rule that the intent was to require compliance
with the test procedure amendments adopted in that final rule
consistent with the compliance of any new or amended standards. 77
FR 10292, 10295, 10308-9, 10318-21 (Feb. 21, 2012).
---------------------------------------------------------------------------
DOE finds the amendments adopted in AHRI 1200-2013 to be generally
consistent with the DOE test procedure for commercial refrigeration
equipment, except DOE finds the need for additional clarity surrounding
the description of how TDA is to be calculated for radius cases the
definition of ``transparent surface.'' For radius cases, DOE maintains
that TDA shall be calculated as the projection of visible product, as
described in section III.A.9. To clarify the method for calculating TDA
for equipment with curved-front geometries, DOE is adopting a new
figure specifying the dimensions Dh, L, and area
Ae are to be determined as planar projections of the area of
visible product when viewed at an angle normal to the transparent area
for radius cases. Regarding the definition of ``transparent surface,''
as discussed in section III.A.2.b, DOE adopts a definition of
``transparent'' based on a light transmittance of 45 percent when
measured in accordance with ASTM Standard E 1084-86 (Reapproved 2009).
9. Clarification of Methodology for Measuring Total Display Area
DOE uses TDA to determine the applicable performance standard for
remote condensing commercial refrigeration equipment with transparent
doors or no doors. Appendix D of ARI 1200-2006 and AHRI 1200-2010, as
incorporated by reference by DOE at 10 CFR 431.63, provides a
definition and instructions on determining TDA. AHRI 1200-2013 provides
the same definition and instructions, and specifies that when
calculating Dh, only the visible dimension shall be
considered, an additional figure, Figure D18, provides clarification
regarding the calculation of TDA for radius cases with transparent
sides. Appendix D of ARI 1200-2006, AHRI 1200-2010, and AHRI 1200-2013
defines TDA as follows:
``Total Display Area (TDA) is the sum of the projected area(s)
for visible product.''
Moreover, Appendix D provides a general equation for calculating
the ``projected area(s),'' in the form of:
TDA = Dh*L + Ae,
Where:
Ae = Projected area from visible product through end
walls
Dh = Dimension of projected visible product
L = Length of Commercial Refrigerated Display Merchandiser
Figures D1 through D16 of Appendix D of ARI 1200-2006, AHRI 1200-
2010, and AHRI 1200-2013 provide instructions on the measurement of
Dh, L, and Ae for various geometries of
commercial refrigerated display merchandisers. These figures show that
TDA includes only those areas through which displayed product is
visible for the Ae and Dh dimension, irrespective
of the presence of other transparent areas through which product cannot
be viewed. As Interpretations 1, 3, and 4 of AHRI 1200-2010 and the
amendments adopted in AHRI 1200-2013 make clear, the converse is also
true--areas of the product zone that cannot be viewed as part of a
direct projection through a transparent area are not to be included in
any measurement of Dh. The term ``direct projection'' refers
to the view at an angle perpendicular to the plane of product
presentation (facing area). ARI 1200-2006, AHRI 1200-2010, and AHRI
1200-2013 all define the third variable, ``L'', as the ``length of
commercial refrigerated display merchandiser.'' However, Appendix D
contains no figures or illustrations instructing a user how to perform
this measurement.
In the October 2013 test procedure NOPR, DOE discussed the
calculation of TDA for various CRE models and, at the public meeting
presented figures, to illustrate the concept that the measurement of
TDA in practice should be consistent with its definition as the
``dimension of projected visible product.'' (DOE, No. 3 at pp. 68-71)
DOE clarified that this included the dimension L, which corresponds to
the total length of the transparent area of the merchandiser through
which product can be seen; areas of opaque material that overhang the
product zone and well as areas of transparent material that do not
project upon a zone occupied by product, should not be included in this
length. To clarify the calculation of TDA, DOE proposed to add
clarifying text and figures to the test procedure explaining that the
measurement of TDA should be representative of the ``dimension of
projected visible product'' and that no opaque materials or areas of
transparent material through which product cannot be viewed should be
included in the calculation of TDA. 78 FR at 64310-64312 (Oct. 28,
2013).
In response to DOE's proposal to clarify the method of calculating
TDA, DOE received several comments from interested parties objecting to
DOE's interpretation and offering suggestions for other methods of
calculating the dimension L when determining TDA of a CRE basic model
with transparent doors or no doors. AHRI, Hill Phoenix, Hussmann, and
Zero Zone disagreed
[[Page 22300]]
with DOE's definition of the length of a commercial refrigerated
display merchandiser and stated that industry has always treated the
length ``L'' as the ``length of the commercial refrigerated display
merchandiser'' from inside wall to inside wall, disregarding the
presence of non-transparent mullions and door frames. AHRI, Hill
Phoenix, Hussmann, and Zero Zone further believed, and provided
quantitative justification to support, that DOE must have used case
length in the engineering analysis for the 2009 and the current
rulemaking. (Docket No. EERE-2012-BT-STD-0003) The commenters stated it
is impossible to have a typical 30-inch by 67-inch door have 13 square
feet of TDA without including the mullions and door frames and provided
analysis to support this viewpoint. The commenters added that using TDA
as DOE described in the October 2013 test procedure NOPR instead of
case length would reduce the standard level by 10 to 12.5 percent.
(AHRI, No. 15 at pp. 1-3; Hill Phoenix, No. 13 at pp. 2-6; Hussmann,
No. 11 at pp. 3-4; Zero Zone, No. 18 at pp. 3-4) Hussmann expressed
concern that changing the method for calculating TDA without changing
the standards would unfairly penalize manufacturers. (Hussmann, Public
Meeting Transcript, No. 7 at p. 190)
Arneg and Zero Zone commented that the TDA is dependent on the
distance the observer is located from the door and their orientation of
viewing. (Arneg, Public Meeting Transcript, No. 7 at p. 196; Zero Zone,
Public Meeting Transcript, No. 7 at pp. 196-198)
To be consistent with current industry practice and DOE's energy
conservation standard rulemaking analysis (Docket No. EERE-2010-BT-STD-
0003), AHRI, Hill Phoenix, and Hussmann suggested that DOE use the
interior refrigerated length, calculated from inside wall to inside
wall, except for when a case has greater than 5 inches of non-
transparent area. For CRE models with more than 5 inches of non-
transparent length in the dimension L, the commenters recommended that
DOE use total length of transparent area plus 5 inches. (AHRI, No. 15
at pp. 1-3; Hill Phoenix, No. 13 at pp. 2-6; Hussmann, No. 11 at p. 4)
Zero Zone recommended that DOE adjust the energy conservation
standard to account for the reduction in TDA associated with not
including the door frames and mullions in the calculation of TDA. If
DOE elects not to adjust the energy conservation standard commensurate
with the change in calculation of TDA, Zero Zone recommended that DOE
not alter the calculation of TDA from that assumed in the engineering
analysis for the ongoing energy conservation standard rulemaking
(Docket No. EERE-2010-BT-STD-0003) and noted that the market place will
sort out the value and utility of equipment that has more or less
visible product. (Zero Zone, No. 18 at p. 4) Zero Zone suggested that
DOE incorporate a TDA-dependent component in the formula for energy,
and another component considering non-TDA space or volume, noting that
this is a unique design, although something similar has been done for
ice cases. (Zero Zone, Public Meeting Transcript, No. 7 at pp. 206-207)
Traulsen suggested using volume to calculate energy consumption for
glass door remotes, effectively bypassing the TDA discussion, or
suggested leaving TDA as a square-footage calculated wall-to-wall, top
to bottom while ignoring the depth dimension. (Traulsen, Public Meeting
Transcript, No. 7 at pp. 209-211)
Southern Store Fixtures expressed concern that setting the
precedent of eliminating mullions could result in the elimination from
the calculation of TDA of other components in the refrigerated space
that occupy space not containing merchandise. Southern Store Fixtures
asserted that this could eventually cause the calculation to become
complicated and burdensome for manufacturers. (Southern Store Fixtures,
Public Meeting Transcript, No. 7 at pp. 207-208)
Hussmann, True, and Zero Zone agreed that, for the majority of
cases observed in the field, calculating L using the length of the
interior refrigerated volume or the continuous length of the
transparent doors (including mullions and doorframes) would be the
same. (Hussmann, Public Meeting Transcript, No. 7 at pp. 217-218; True,
Public Meeting Transcript, No. 7 at p. 218; Zero Zone, Public Meeting
Transcript, No. 7 at pp. 219-220)
In response to the suggestions offered by interested parties, DOE
finds that calculating TDA to include portions of non-transparent area
is inconsistent with the stated definition of TDA. However, DOE
acknowledges that defining TDA as strictly the total length of
transparent area may be inconsistent with the method used by industry
to calculate TDA today. As a compromise, DOE is adopting in this final
rule, a method for calculating the TDA of CRE basic models that is
representative of the dimension through which product can be viewed,
but which accommodates small non-transparent areas that are part of the
doors themselves and are typically included in the calculation of TDA
by manufacturers today. With regards to the calculation of TDA for the
vertical closed transparent case modeled in DOE's engineering analysis
supporting the March 2014 energy conservation standards final rule, DOE
notes that the case modeled represents a typical multi-deck
refrigerated merchandiser with five doors of 13 square feet each, for a
TDA of 65 square feet (see appendix 5A of the technical support
document for March 2014 energy conservation standards rulemaking final
rule, Docket No. EERE-2010-BT-STD-0003). DOE based its calculation of
representative door TDA upon the continuous length of transparent area
of the CRE model, which included mullions and door frames, but excluded
any additional case wall present on the front face of the unit. In
other words, DOE included the entire length of the transparent doors,
including minor non-transparent areas, in its calculation of case TDA.
DOE notes that, for the case modeled, the interior length of the
refrigerated volume would be the same as the continuous length of
transparent area when measured from door edge to door edge. DOE
emphasizes that the model is meant to be representative of the energy
use of a given type of commercial refrigeration equipment, and not to
represent all the different design options available for any given
model within an equipment category.
DOE agrees with interested parties that if the dimension L were
determined strictly as the length of transparent area, not including
any non-transparent mullions or door frames, the difference may be on
the order of 10 percent. However, to respond to the concerns of
interested parties, DOE is not adopting such a strict definition of L,
but rather a ``continuous'' length of transparent area to be consistent
with the continuous dimension of Dh. DOE believes that, to
be consistent with the definition and intent of TDA, the dimension L
should represent the continuous length of transparent area, as proposed
in the October 2013 test procedure NOPR. 78 FR at 64321 (Oct. 28,
2013). However, DOE acknowledges that some unique case designs may
feature large sections of case wall or other non-transparent area
between sections of transparent area and agrees with interested parties
that some threshold is necessary to ensure only materials with a
significant majority of transparent area are included in the dimension
L (e.g., transparent doors with thin door mullions or other non-
transparent hardware). DOE has reviewed the suggestion, submitted by
interested parties that 5-inches or less of
[[Page 22301]]
non-transparent length be allowed in the measurement of L. DOE finds
that a threshold of 5-inches or less is not sufficient to accommodate
the non-transparent lengths for a large number of transparent-door CRE
models with more than 3 doors. In addition, DOE notes that a fixed
threshold of 5-inches for cases, regardless of the size of the case and
the length of the dimension ``L'' does not treat all cases
equivalently. However, DOE acknowledges that the concept of a threshold
for non-transparent area, as suggested by interested parties, prevents
cases with significant portions of non-transparent area between
transparent doors or cases with transparent doors significantly inset
from the case end walls from calculating an unrepresentatively high
TDA, as would be the case if only interior refrigerated case length was
used. As such, DOE believes a more consistent approach would be to
apply a threshold of non-transparent area that may be included in the
dimension ``L'' based on a percentage of the interior refrigerated case
length that is not transparent. DOE is adopting in this final rule a
threshold of 10 percent of non-transparent area that may be included in
the dimension L. DOE believes this will more equitably treat the
variety of case designs available on the market. DOE also notes that
the 10 percent threshold is less stringent than the 5-inch threshold
recommended by manufacturers. That is, a threshold of 10 percent
accommodates greater amounts of non-transparent area in the dimension
``L'' for a majority of CRE models. In addition, a threshold of 10
percent is consistent with the modeling performed in the CRE energy
conservation standard rulemaking (Docket No. EERE-2010-BT-STD-0003).
For those cases with greater than 10 percent of non-transparent
area in the interior refrigerated length of the CRE model, DOE agrees
with the general approach recommended by interested parties that the
dimension L should be determined as the total length, along the axis of
the merchandiser, of portions through which product can be viewed from
an angle normal to the transparent area (i.e., the projected linear
dimension(s) of visible product) plus 10 percent, to provide equitable
treatment of cases with different door configurations.
Therefore, in this final rule, DOE adopts instructions for
calculating TDA that define L as the interior length of the CRE model,
provided no more than 10 percent of that length consists of non-
transparent material. For those cases with greater than 10 percent of
non-transparent area, L shall be determined as the projected linear
dimension(s) of visible product plus 10 percent of non-transparent
area.
DOE believes this instruction is consistent with and clarifies
current industry practice and the existing provisions of the DOE test
procedure and, as such, believes that this amendment should not change
the measured energy consumption of covered equipment. Therefore, DOE is
adopting these amendments in both Appendix A, which is the test
procedure required for equipment testing to demonstrate compliance with
current energy conservation standards, and Appendix B, which will be
required for testing on March 28, 2017, consistent with the compliance
date of the amended energy conservation standards established in the
March 2014 energy conservation standards final rule. 79 FR 17726, 17727
(Mar. 28, 2014).
10. Compliance Date of Test Procedure Amendments
In this final rule, DOE also reorganizes the test procedure
requirements at 10 CFR 431.64 so that they are easier to understand,
and updates the compliance date to be consistent with the compliance
date of the amended standards established in the March 2014 energy
conservation standards final rule. 79 FR 17726, 17727 (Mar. 28, 2014).
EPCA prescribes that if any rulemaking amends a test procedure, DOE
must determine to what extent, if any, the proposed test procedure
would alter the measured energy efficiency of any covered equipment as
determined under the existing test procedure. (42 U.S.C. 6314(a)(6))
Further, if DOE determines that the amended test procedure would alter
the measured efficiency of covered equipment, DOE must amend the
applicable energy conservation standard accordingly. (42 U.S.C.
6314(a)(6))
In the 2012 test procedure final rule, DOE stated that some test
procedure amendments will change the measured energy consumption of
some covered equipment. 77 FR at 10295 and 10309 (Feb. 21, 2012).
Specifically, DOE determined the provisions to accommodate testing of
night curtains and lighting occupancy sensors and controls altered the
measured energy consumption of covered equipment. 77 FR at 10309 (Feb.
21, 2012). As such, DOE established in the 2012 test procedure final
rule that use of the amended test procedure for compliance with DOE
energy conservation standards or representations with respect to energy
consumption of commercial refrigeration equipment would be required on
the compliance date of the revised energy conservation standards
established in the March 2014 energy conservation standards final rule.
77 FR at 10309 (Feb. 21, 2012); 79 FR 17726, 17727 (Mar. 28, 2014).
To improve clarity, in the October 2013 test procedure NOPR, DOE
proposed to reorganize the language at 10 CFR 431.64 into Appendices A
and B. In the October 2013 test procedure NOPR, Appendix A contained
the test procedure for commercial refrigeration equipment established
in the 2006 test procedure final rule and Appendix B included the
amended test procedure established in the 2012 test procedure final
rule that will be required to be used on March 28, 2014, consistent
with the compliance date of the amended standards established in the
March 2014 energy conservation standards final rule. 78 FR at 64318-
64325 (Oct. 28, 2013); 79 FR 17726, 17727 (Mar. 28, 2014).
In response to DOE's proposal, Hussmann stated that is does not
understand why DOE cannot allow energy-saving features adopted in the
2012 test procedure final rule to demonstrate compliance with current
energy conservation standards. (Hussmann, No. 11 at p. 3) Hussmann
further stated that it believes that the provision allowing
manufacturers to rate equipment conservatively that were tested at a
temperature lower than the required 38 2 [deg]F provided
the basic model still meets the applicable energy conservation standard
should be included in Appendix A (effective 30 days after publication
of a final rule in the Federal Register) as well as Appendix B.
Hussmann added that this will reduce testing burden for manufacturers
without sacrificing efficiency. (Hussmann, No. 11 at p. 3) Zero Zone
commented that it agreed with DOE's proposed approach to test remote
cases under the LAPT and suggested that the test method should be
included as part of Appendix A and immediately become part of DOE's
test procedure. (Zero Zone, No. 18 at p. 3)
With regard to permitting early use of the test procedure
amendments established in the 2012 test procedure final rule, DOE
acknowledges Hussmann's request and notes that DOE has published
guidance establishing that, while manufacturers need not comply with a
new or amended test procedure prior to the compliance date established
for that test procedure, manufacturers may voluntarily use amended test
procedures to rate and certify their products prior to the compliance
date if they also comply
[[Page 22302]]
with energy conservation standards based on that test procedure. See
https://www1.eere.energy.gov/buildings/appliance_standards/pdfs/tp_faq_2012-06-29.pdf. DOE cannot permit amended test procedure
provisions that affect the measured energy consumption to be used to
demonstrate compliance with energy conservation standards that were not
set based on that test procedure. Specifically, the provisions adopted
in Appendix B in this final rule may be used prior to the compliance
date established in this final rule as long as the equipment also
demonstrates compliance with the amended standards established in the
March 2014 energy conservation standards final rule, which used that
test procedure as a basis. 79 FR 17726, 17734 (Mar. 28, 2014).
Manufacturers may not use the test procedure established in Appendix B
to demonstrate compliance with existing energy conservation standards.
In response to Hussmann's request to include allowances for
conservatively rating commercial refrigerators at temperatures lower
than the specified rating temperature of 38 2 [deg]F in
Appendix A as well as Appendix B, DOE acknowledges that, in addition to
testing and certification to comply with DOE's energy conservation
standards, commercial refrigeration equipment that is marketed to hold
perishable food items must also be classified and certified by NSF/
ANSI-7, ``Commercial Refrigerators and Freezers'' (hereafter referred
to as NSF-7), a food safety standard issued by NSF.\14\ NSF-7
establishes two classes for commercial display cases: Type I, which is
tested at ASHRAE Standard 72 standard ambient conditions (75 [deg]F dry
bulb and 64 [deg]F wet bulb temperature), and Type II, which is tested
at higher ambient conditions (80 [deg]F dry bulb and 68 [deg]F wet bulb
temperature). These two test conditions are also reported in terms of
dry bulb temperature and percentage relative humidity. Type I
corresponds to 75 [deg]F and 55 percent relative humidity, and Type II
corresponds to 80 [deg]F and 60 percent relative humidity. NSF-7 also
requires Type I and Type II equipment to be tested such that the
average temperature of each test package containing an individual
temperature sensor does not exceed 41 [deg]F and no single temperature
sensor exceeds a reading of 43 [deg]F at any time during the test. NSF-
7 does not specify a required average temperature for all test sensors
or the measurement of energy consumption during the test. On the other
hand, DOE does require an integrated average test temperature of 38
[deg]F 2 [deg]F. However, manufacturers have reported that
they test cases at lower IATs than that specified by DOE to ensure the
NSF-7 requirements are met. In the 2012 test procedure final rule, DOE
establishes provisions that allow manufacturers to optionally test
equipment at internal or ambient conditions more stringent than the
prescribed DOE rating temperatures and conditions for that equipment
class, to reduce the repetitive test burden of testing at both DOE and
NSF-7 conditions. 77 FR at 10305-07 (Feb. 21, 2012).
---------------------------------------------------------------------------
\14\ NSF International. ``NSF/ASNI 7--2009: Commercial
Refrigerators and Freezers.'' Ann Arbor, MI. https://www.nsf.org/business/food_equipment/standards.asp.
---------------------------------------------------------------------------
DOE believes that accommodating Hussmann's request and including
the provisions regarding certification of equipment at conservative
IATs in both Appendix A and Appendix B won't affect the measured energy
consumption of covered equipment or the stringency of the applicable
energy conservation standard, as the provision is voluntary and thus is
not required for equipment testing. In addition, DOE believes that
allowing manufacturers to implement this conservative rating approach
as of 30 days after publication of a final rule in the Federal Register
will significantly reduce the burden associated with testing equipment
that must be certified to both DOE's energy conservation standards and
NSF's food safety standard. Therefore, DOE is adopting optional
provisions to allow manufacturers to conservatively rate equipment at
internal or ambient temperatures more stringent than the rating
temperature or ambient conditions prescribed for their equipment class,
provided the basic model still meets the applicable energy conservation
standard, in both Appendix A and Appendix B. DOE notes that all other
test procedure requirements must be satisfied to ensure a valid test;
only the IAT and rating conditions may be adjusted.
In response to Zero Zone's recommendation that DOE include the
provisions for testing equipment that cannot be tested at the specified
rating temperature at the LAPT in Appendix A in addition to Appendix B,
DOE is incorporating the LAPT provisions into both Appendix A and
Appendix B as part of this final rule.
B. Other Notice of Proposed Rulemaking Comments and DOE Responses
In response to the October 2013 test procedure NOPR, DOE received
comments from interested parties regarding several issues that pertain
to the CRE test procedure, but not to specific provisions or
amendments. Specifically, DOE received comments on the ambient
temperatures used for testing commercial refrigeration equipment at
standard rating conditions and the burden of testing.
1. Ambient Test Temperatures
DOE's test procedure for commercial refrigeration equipment
establishes standard rating conditions for testing covered equipment of
75 [deg]F and 55 percent relative humidity. Commercial refrigeration
equipment that is marketed to hold perishable food items is classified
and certified by NSF/ANSI-7, ``Commercial Refrigerators and Freezers''
(hereafter referred to as NSF-7), a food safety standard issued by NSF.
NSF-7 establishes two classes for commercial display cases: Type I,
which is tested at ASHRAE Standard 72 standard ambient conditions (75
[deg]F dry bulb and 64 [deg]F wet bulb temperature), and Type II, which
is tested at higher ambient conditions (80 [deg]F dry bulb and 68
[deg]F wet bulb temperature). These two test conditions are also
reported in terms of dry bulb temperature and percentage relative
humidity. Type I corresponds to 75 [deg]F and 55 percent relative
humidity, and Type II corresponds to 80 [deg]F and 60 percent relative
humidity. NSF-7 also requires Type I and Type II equipment to be tested
such that the average temperature of each test package containing an
individual temperature sensor does not exceed 41 [deg]F and no single
temperature sensor exceeds a reading of 43 [deg]F at any time during
the test. NSF-7 does not specify a required average temperature for all
test sensors or the measurement of energy consumption during the test.
On the other hand, DOE does require an integrated average test
temperature of 38 [deg]F 2 [deg]F. However, manufacturers
have reported that they test cases at lower IATs than that specified by
DOE to ensure the NSF-7 requirements are met.
Continental commented that commercial refrigeration equipment is
designed primarily to keep food safe in harsh conditions and added that
most commercial kitchens have multiple pieces of heat-generating
cooking equipment near the refrigeration equipment and ambient
temperatures much higher than 75 [deg]F. Continental suggested that DOE
utilize ambient test temperatures and allowable energy consumption
levels cognizant of public health and safety. (Continental, No. 14 at
p. 2)
In response to the comment from Continental, DOE believes that the
existing test conditions specified within the ASHRAE 72 test procedure
and
[[Page 22303]]
accepted by industry are generally representative of field conditions.
With respect to equipment designed to operate in harsher ambient
conditions, DOE previously considered NSF Type II equipment in the 2012
test procedure final rule and found that the compressor systems can
effectively operate at test temperatures. In the 2012 test procedure
final rule, DOE agreed with interested parties that testing cases at an
ambient temperature of 80 [deg]F, rather than the currently specified
75 [deg]F, will not have a significant impact on energy consumption for
cases with doors and recognized that the impact on open cases may be
greater than on closed cases, but did not believe that equipment will
have operation or performance issues if tested at a the temperatures
prescribed by the DOE test procedure. 77 FR at 10305-10307 (Feb. 21,
2012). DOE maintains that the energy consumption of a case should scale
with ambient temperature and does not believe these issues will prevent
units from being tested using the DOE-prescribed test temperatures or
complying with any existing or amended DOE energy conservation
standards.
2. Burden of Testing
Felix Storch, Inc. (FSI) expressed concern that there would be an
undue burden on small business to conduct the proposed test procedures.
FSI's opinion was that DOE has not calculated the full extent to which
the proposed test procedures revisions will affect small manufacturers.
FSI further commented that small businesses have limited R&D budgets
and expertise to understand and carry out the proposed test procedures
effectively. (FSI, No. 12 at p. 1)
FSI recommended, to limit burden on small business, that: (1) Small
businesses be allowed to use a single test for each basic model; (2)
DOE provide free consulting help to small businesses to interpret test
procedures and be bound in enforcement cases by the interpretations it
provides; (3) DOE, upon issuance of notices or rulemaking documents, be
required to notify affected small businesses of new or revised
regulations, and no enforcement be permitted against small business
absent such notification; and (4) CCMS submission be optional, not
required, for small businesses as this represents a large burden with
little benefit to the consumer community. (FSI, No. 12 at p. 3)
Finally, FSI stated that small businesses, such as FSI, serve small
niche markets and increase customer choice by providing customizable
solutions. (FSI, No. 12 at p. 3)
DOE understands that amending test procedures or including
additional provisions in those test procedures could increase the
burden on manufacturers to quantify the performance of their equipment.
EPCA requires that the test procedures promulgated by DOE be reasonably
designed to produce test results that reflect energy efficiency, energy
use, and estimated operating costs of the covered equipment during a
representative average use cycle. EPCA also requires that the test
procedure not be unduly burdensome to conduct. (42 U.S.C. 6314(a)(2))
DOE has analyzed the expected incremental cost of the test
procedure amendments adopted in this final rule and its impact on
manufacturers. All commercial refrigeration equipment covered by this
rule is currently required to be tested using the DOE test procedure to
show compliance with applicable energy conservation standards. The DOE
test procedure, as amended by the 2012 test procedure final rule,
consists of one 24-hour test at standard rating conditions to determine
daily energy consumption.
In addition, the 2012 test procedure final rule amends the test
procedure for commercial refrigeration equipment to update the
referenced industry test procedures to their most current versions
(AHRI 1200-2010 and AHAM HRF-1-2008); incorporates provisions for
testing certain energy efficiency features, including night curtains
and lighting occupancy sensor and scheduled controls; and provides a
test procedure for specialty equipment that cannot be tested at the
prescribed rating temperature. As part of that rulemaking, DOE
considered the burden associated with the test procedure amendments and
certified that the rule would not have a ``significant economic impact
on a substantial number of small entities,'' and the preparation of a
regulatory flexibility analysis was not warranted. 77 FR at 10314-10316
(Feb. 21, 2012).
The test procedure amendments adopted in this final rule only
reorganize and clarify the existing requirements in the DOE test
procedure, both those established in the 2006 test procedure final rule
and those established in the 2012 test procedure final rule; they do
not alter or affect any of the test procedure requirements or technical
provisions in any way. DOE does not believe that the proposed test
procedure amendments would affect the way in which any covered
commercial refrigeration equipment is tested, nor would they impact the
burden of conducting such a test.
In this test procedure final rule, DOE is also allowing
manufacturers to test at the internal temperatures and/or ambient
conditions required for NSF-7 testing within 30 days of publication of
this final rule in the Federal Register. This will dramatically reduce
the burden for manufacturers that produce equipment for food storage,
as under the amended test procedure these two 24-hour tests can be
combined. The NSF-7 test is similar in length and burden to the DOE
test, but is performed at slightly different internal and external
temperatures. Certification of equipment tested at NSF-7 test
temperatures for the purposes of compliance with DOE energy
conservation standards will only be possible for equipment that is able
to meet the DOE energy conservation standard at the more stringent NSF-
7 test conditions. However, DOE believes this provision can still
potentially decrease the burden of test for some manufacturers.
The amendments to the test procedure for commercial refrigeration
equipment were chosen to help minimize the impact of additional testing
while clarifying and reorganizing the DOE test procedure to provide
more accurate and repeatable test methods. Because none of these
amendments significantly increase the burden of a test, DOE believes
that the test procedure finalized here will not be unduly burdensome to
conduct.
In response to FSI's comments regarding this impact of DOE's test
procedure for commercial refrigeration equipment on small businesses,
DOE notes that the bulk of FSI's recommendations address CCE provisions
that were established in a previous rulemaking (76 FR at 12446-12449
(March 7, 2011)) and are not addressed in this final rule. DOE provided
a robust analysis of the estimated burden of the test procedure
clarifications and amendments adopted in this final rule and determined
that these changes would not cause an undue burden on small
manufacturers. This analysis is presented in section IV.B of this final
rule.
With regard to burden on small manufacturers associated with
previously promulgated rulemakings, DOE is only analyzing the
incremental burden associated with the amendments and provisions
adopted as a result of this final rule. However, DOE notes that
previous rulemakings, such as those that accounted for the impact of
CCE requirements on CRE manufacturers, including small businesses, have
accounted for the incremental burden associated with these requirements
and, in each case, found the burden to not
[[Page 22304]]
have a significant impact on a substantial number of small entities.
Specifically, with regard to an allowance for small businesses to use a
single test for each basic model, DOE established a sample size of not
less than two in the CCE final rule for all manufacturers regardless of
size to ensure a suitable representation of model variability. 76 FR at
12453 (March 7, 2011). Regarding the availability of free consulting
help for small businesses to interpret test procedures, DOE has
established a guidance process whereby interested parties may submit
questions to DOE at any time regarding proper conduct of the DOE test
procedure or compliance with relevant certification requirements. DOE
also maintains a database of issues on which DOE has issued guidance
for reference.\15\ When DOE issues notices or rulemaking documents,
these documents are immediately available on DOE's Web site for
Appliance and Commercial Equipment Standards \16\ and are publicly
available via the Federal Register. DOE seeks to be as open as possible
in conducting rulemakings and invites interested parties to participate
openly. Regarding CCMS submission of certified ratings for small
businesses, DOE has the same requirements for small businesses as for
large entities and is under the same requirements to verify compliance
with applicable energy conservation standards. Without certification
reports, DOE has no record of compliance for applicable covered
products. Further, DOE has attempted to design the CCMS templates to be
as simple and straightforward as possible to minimize burden on
manufacturers required to use these templates. Therefore, DOE continues
to require certification of the TDEC or CDEC of covered basic models of
commercial refrigeration equipment based on the testing of at least two
unique units and the submittal of certification reports using DOE's
CCMS templates.
---------------------------------------------------------------------------
\15\ U.S. Department of Energy Appliance & Commercial Equipment
Standards Program Guidance and Frequently Asked Questions, available
at: https://www1.eere.energy.gov/guidance/default.aspx?pid=2&spid=1.
\16\ https://energy.gov/node/773531/about_appliance_and_equipment.html.
---------------------------------------------------------------------------
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget (OMB) has determined that test
procedure rulemakings do not constitute ``significant regulatory
actions'' under section 3(f) of Executive Order 12866, ``Regulatory
Planning and Review,'' 58 FR 51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under the Executive Order by the
Office of Information and Regulatory Affairs (OIRA) in the OMB.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq.) requires
preparation of an initial regulatory flexibility act analysis (IRFA)
whenever an agency is required to publish a general notice of proposed
rulemaking. When an agency promulgates a final rule after being
required to publish a general notice of proposed rulemaking, the agency
must prepare a final regulatory flexibility analysis. The requirement
to prepare these analyses does not apply to any proposed or final rule
if the agency certifies that the rule will not, if promulgated, have a
significant economic impact on a substantial number of small entities.
If the agency makes such a certification, the agency must publish the
certification in the Federal Register along with the factual basis for
such certification.
As required by Executive Order 13272, ``Proper Consideration of
Small Entities in Agency Rulemaking,'' 67 FR 53461 (Aug. 16, 2002), DOE
published procedures and policies on February 19, 2003, so that the
potential impacts of its rules on small entities are properly
considered during the rulemaking process. 68 FR 7990 (Feb. 12, 2003).
DOE has made its procedures and policies available on the Office of the
General Counsel's Web site at https://energy.gov/gc/office-general-counsel.
In the October 2013 test procedure NOPR, DOE reviewed the proposed
rule to amend the test procedure for commercial refrigeration
equipment, under the provisions of the Regulatory Flexibility Act and
the procedures and policies published on February 19, 2003. DOE
certified that the proposed rule, if adopted, would not result in a
significant impact on a substantial number of small entities. 78 FR at
64313 (October 28, 2013). DOE received comments on its certification
and the economic impacts of the test procedure, and has responded to
these comments in section III.B.2. After consideration of these
comments, DOE certifies that the test procedure amendments set forth in
this final rule will not have a significant impact on a substantial
number of small entities. The factual basis for this certification is
set forth below.
For the commercial refrigeration industry, the Small Business
Association (SBA) has set a size threshold, which defines those
entities classified as ``small businesses'' for the purpose of the
statute. DOE used the SBA's size standards to determine whether any
small entities would be required to comply with the rule. The size
standards are codified at 13 CFR Part 121. The standards are listed by
North American Industry Classification System (NAICS) code and industry
description and are available at https://www.sba.gov/sites/default/files/files/Size_Standards_Table.pdf. Commercial refrigeration
equipment manufacturing is classified under NAICS 333415, ``Air-
Conditioning and Warm Air Heating Equipment and Commercial and
Industrial Refrigeration Equipment Manufacturing.'' Small entities
within this industry description are those with 750 employees or fewer.
DOE conducted a market survey to determine whether any small
business manufacturers of equipment would be covered by this
rulemaking. During its market survey, DOE used all available public
information to identify potential small manufacturers. DOE's research
involved the review of industry trade association membership
directories (including AHRI), equipment databases (e.g., Federal Trade
Commission (FTC), the Thomas Register, California Energy Commission
(CEC), and ENERGY STAR databases), individual company Web sites, and
marketing research tools (e.g., Dunn and Bradstreet reports, Manta) to
create a list of companies that manufacture or sell commercial
refrigeration equipment covered by this rulemaking. DOE also referred
to a list of small businesses that manufacture commercial refrigeration
equipment, supplied by Traulsen in a written comment provided in
response to the NOPR proposing amendments to the DOE test procedure for
commercial refrigeration equipment published November 24, 2010 (Docket
No. EERE-2010-BT-TP-0034, Traulsen, No. 9 at pp. 4-5). Using these
sources, DOE identified 61 manufacturers of commercial refrigeration
equipment.
DOE then reviewed this data to determine whether the entities met
the SBA's definition of a small business manufacturer of commercial
refrigeration equipment and screened out companies that do not offer
equipment covered by this rulemaking, do not meet the definition of a
``small business,'' or are foreign owned and operated. Based on this
review, DOE has identified 26 companies that would be considered small
manufacturers and will be directly regulated by this rule, which
represents 43 percent of national CRE manufacturers. Although 43
percent would be considered a substantial number of small entities,
[[Page 22305]]
further analysis of incremental costs associated with this rulemaking
determined no significant impact on these manufacturers. Specifically,
the changes to the test procedure adopted in this final rule consist
only of clarifications regarding:
1. The applicability of the test procedure and related energy
conservation standards to certain types of equipment;
2. the definitions of ``hybrid commercial refrigeration
equipment,'' ``commercial refrigeration equipment with drawers,'' and
``commercial refrigeration equipment with solid and/or transparent
doors'';
3. the relationship among the rating temperature, operating
temperature, and integrated average temperature;
4. the proper configuration and use of energy management systems,
lighting controls, and test packages in the DOE test procedure for
commercial refrigeration equipment;
5. the treatment of various features, components, and accessories
under the DOE test procedure;
6. the rounding requirements for test results and certified
ratings;
7. the provision adopted in the 2012 test procedure final rule to
allow testing at the lowest application product temperature for
equipment that cannot operate at the prescribed rating temperature for
its equipment class;
8. clarifications raised by Interpretations 1, 2, 3, 4, and 5 of
AHRI 1200-2010;
9. the methodology used to determine total display area; and
10. the compliance date of certain amendments established in the
2012 test procedure final rule.
All commercial refrigeration equipment covered by this rule is
currently required to be tested using the DOE test procedure to show
compliance with established energy conservation standards. The DOE test
procedure manufacturers must use to demonstrate compliance with
existing standards is that established in the 2006 test procedure final
rule, which references ARI 1200-2006 and AHAM HRF-1-2004. This test
procedure consists of one 24-hour test at standard rating conditions to
determine daily energy consumption.
The 2012 test procedure final rule amends the test procedure for
commercial refrigeration equipment to update the referenced industry
test procedures to their most current versions (AHRI 1200-2010 and AHAM
HRF-1-2008); incorporates provisions for testing certain energy
efficiency features, including night curtains and lighting occupancy
sensor and scheduled controls; and provides a test procedure for
specialty equipment that cannot be tested at the prescribed rating
temperature. As part of that rulemaking, DOE considered the burden
associated with the test procedure amendments and certified that the
rule would not have a ``significant economic impact on a substantial
number of small entities,'' and the preparation of a regulatory
flexibility analysis was not warranted. 77 FR at 10314-10316 (Feb. 21,
2012).
The test procedure amendments adopted in this final rule only
reorganize and clarify the existing requirements in the DOE test
procedure, both those established in the 2006 test procedure final rule
and those established in the 2012 test procedure final rule; they do
not alter or affect any of the test procedure requirements or
provisions in any way. DOE does not believe that the proposed test
procedure amendments would affect the way in which any covered
commercial refrigeration equipment is tested, nor would they increase
the burden of conducting such a test.
Rather, some of the provisions adopted in this final rule will
reduce the burden associated with testing and certifying commercial
refrigeration equipment. Specifically, this final rule allows
manufacturers to reduce burden by testing and certifying equipment and
internal and ambient test conditions that satisfy both the DOE test
procedure and the NSF-7 test procedure effective 30 days after
publication of this final rule in the Federal Register. This may
significantly decrease the amount of testing manufacturers must do to
demonstrate compliance with both programs.
DOE also notes that the amendments regarding the treatment of
various features, components, and accessories under the DOE test
procedure were the result of a series of negotiations that occurred
between DOE, manufacturers, and energy efficiency advocates and, thus,
represent a mutually agreed upon approach for each of these features.
DOE believes adoption of these clarifications will streamline testing
and make DOE's test procedure easier and more straightforward to
implement.
The negotiations also resulted in a recently published final rule
adopting amended regulations governing AEDMs, basic model definition,
and compliance for commercial HVAC, refrigeration, and WH equipment.
The AEDM provisions allow an alternative method for determining
compliance in lieu of conducting actual physical testing. 78 FR 79579,
79590. Commercial refrigeration equipment previously were required to
test two units of each basic model, so the addition of an AEDM option
reduces the number of units for which manufacturers will need to
conduct this test procedure. The 2013 AEDM final rule also clarified
its basic model definitions, which give manufacturers the flexibility
to group individual models based on certain characteristics into an
individual basic model for the purposes of demonstrating compliance
with DOE's energy conservation standards. DOE notes that the AEDM and
basic model provisions adopted in the 2013 AEDM final rule will reduce
the burden of demonstrating compliance with DOE's energy conservation
standards in general, such that the burden estimates for testing
discussed here represent a worse case. The specific reductions in
burden accomplished in the 2013 AEDM final rule are discussed in more
detail in that rule. 78 FR 79590-79591 (Dec. 31, 2013).
Based on this factual basis, DOE continues to certify that this
rule will not have a ``significant economic impact on a substantial
number of small entities,'' and the preparation of a regulatory
flexibility analysis is not warranted. DOE has transmitted the
certification and supporting statement of factual basis to the Chief
Counsel for Advocacy of the Small Business Administration for review
under 5 U.S.C. 605(b).
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of commercial refrigeration equipment must certify to
DOE that their products comply with any applicable energy conservation
standards. In certifying compliance, manufacturers must test their
products according to the DOE test procedure for commercial
refrigeration equipment, including any amendments adopted for that test
procedure. DOE has established regulations for the certification and
recordkeeping requirements for all covered consumer products and
commercial equipment, including commercial refrigeration equipment. 76
FR 12422 (March 7, 2011). The collection-of-information requirement for
the certification and recordkeeping is subject to review and approval
by OMB under the Paperwork Reduction Act (PRA). This requirement has
been approved by OMB under OMB Control Number 1910-1400. Public
reporting burden for the certification is estimated to average 20 hours
per response, including the time for reviewing instructions, searching
existing data sources, gathering and maintaining the data needed, and
completing and reviewing the collection of information.
[[Page 22306]]
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
In this final rule, DOE amends its test procedure for commercial
refrigeration equipment. DOE has determined that this rule falls into a
class of actions that are categorically excluded from review under the
National Environmental Policy Act of 1969 (NEPA; 42 U.S.C. 4321 et
seq.). The rule is covered by Categorical Exclusion A5, for rulemakings
that interpret or amend an existing rule without changing the
environmental effect, as set forth in DOE's NEPA regulations in
appendix A to subpart D, 10 CFR part 1021. This rule will not affect
the quality or distribution of energy usage and therefore will not
result in any environmental impacts. Accordingly, neither an
environmental assessment nor an environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (Aug. 4, 1999),
imposes certain requirements on agencies formulating and implementing
policies or regulations that preempt State law or that have Federalism
implications. The Executive Order requires agencies to examine the
constitutional and statutory authority supporting any action that would
limit the policymaking discretion of the States and to carefully assess
the necessity for such actions. The Executive Order also requires
agencies to have an accountable process to ensure meaningful and timely
input by State and local officials in the development of regulatory
policies that have Federalism implications. On March 14, 2000, DOE
published a statement of policy describing the intergovernmental
consultation process it will follow in the development of such
regulations. 65 FR at 13735 (March 14, 2000). DOE has examined this
final rule and has determined that it would not have a substantial
direct effect on the States, on the relationship between the national
government and the States, or on the distribution of power and
responsibilities among the various levels of government. EPCA governs
and prescribes Federal preemption of State regulations as to energy
conservation for the products that are the subject of this final rule.
States can petition DOE for exemption from such preemption to the
extent, and based on criteria, set forth in EPCA. (42 U.S.C. 6297(d))
No further action is required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
Eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically requires that Executive agencies make every reasonable
effort to ensure that the regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly specifies any effect on existing
Federal law or regulation; (3) provides a clear legal standard for
affected conduct while promoting simplification and burden reduction;
(4) specifies the retroactive effect, if any; (5) adequately defines
key terms; and (6) addresses other important issues affecting clarity
and general draftsmanship under any guidelines issued by the Attorney
General. Section 3(c) of Executive Order 12988 requires Executive
agencies to review regulations in light of applicable standards in
sections 3(a) and 3(b) to determine whether they are met or it is
unreasonable to meet one or more of them. DOE has completed the
required review and determined that, to the extent permitted by law,
the final rule meets the relevant standards of Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (UMRA; Pub.
104-4 sec. 201 (codified at 2 U.S.C. 1531) requires each Federal agency
to assess the effects of Federal regulatory actions on State, local,
and Tribal governments and the private sector. For proposed regulatory
actions likely to result in a rule that may cause expenditures by
State, local, and Tribal governments in the aggregate or by the private
sector of $100 million or more in any one year (adjusted annually for
inflation), section 202 of UMRA requires a Federal agency to publish
estimates of the resulting costs, benefits, and other effects on the
national economy. (2 U.S.C. 1532(a), (b)) The UMRA also requires a
Federal agency to develop an effective process to permit timely input
by elected officers of State, local, and Tribal governments on a
proposed ``significant intergovernmental mandate'' and requires an
agency plan for giving notice and opportunity for timely input to
potentially affected small governments before establishing any
requirements that might significantly or uniquely affect small
governments. On March 18, 1997, DOE published a statement of policy on
its process for intergovernmental consultation under UMRA. 62 FR 12820.
(This policy is also available at https://energy.gov/gc/office-general-counsel.) DOE reviewed this final rule pursuant to UMRA and its policy
and determined that the rule contains neither an intergovernmental
mandate nor a mandate that may result in the expenditure of $100
million or more in any year, so these requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This final rule would not have any impact on the autonomy or integrity
of the family as an institution. Accordingly, DOE has concluded that it
is not necessary to prepare a Family Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights,'' 53 FR 8859 (March 15, 1988), that this regulation will not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516, note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. The OMB's guidelines were published in 67 FR 8452 (Feb. 22, 2002),
and DOE's guidelines were published in 67 FR 62446 (Oct. 7, 2002). DOE
has reviewed this final rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
[[Page 22307]]
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to
OIRA, Office of Management and Budget, a Statement of Energy Effects
for any proposed significant energy action. A ``significant energy
action'' is defined as any action by an agency that promulgated or is
expected to lead to promulgation of a final rule, and that (1) is a
significant regulatory action under Executive Order 12866, or any
successor order; and (2) is likely to have a significant adverse effect
on the supply, distribution, or use of energy; or (3) is designated by
the Administrator of OIRA as a significant energy action. For any
proposed significant energy action, the agency must give a detailed
statement of any adverse effects on energy supply, distribution, or use
should the proposal be implemented, and of reasonable alternatives to
the action and their expected benefits on energy supply, distribution,
and use. This regulatory action would not have a significant adverse
effect on the supply, distribution, or use of energy and therefore it
is not a significant energy action. Accordingly, DOE has not prepared a
Statement of Energy Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91), DOE must comply with section 32 of the Federal Energy
Administration Act of 1974 (Pub. L. 93-275), as amended by the Federal
Energy Administration Authorization Act of 1977. When a proposed rule
contains or involves use of commercial standards, the rulemaking must
inform the public of the use and background of such standards. (15
U.S.C. 788 Section 32)
This final rule incorporates testing methods contained in ASTM
Standard E 1084-86 (Reapproved 2009), ``Standard Test Method for Solar
Transmittance (Terrestrial) of Sheet Materials Using Sunlight,'' and
ASHRAE 72-2005, ``Method of Testing Commercial Refrigerators and
Freezers.'' DOE has evaluated these standards and is unable to conclude
whether they fully comply with the requirements of section 323(b) of
the Federal Energy Administration Act (i.e., whether they were
developed in a manner that fully provides for public participation,
comment, and review).
As required by section 32(c) of the Federal Energy Administration
Act of 1974 as amended, DOE has consulted with the Attorney General and
the Chairman of the Federal Trade Commission about the impact on
competition of using the methods contained in these standards before
prescribing a final rule.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will report to Congress on the
promulgation of this rule before its effective date. The report will
state that it has been determined that the rule is not a ``major rule''
as defined by 5 U.S.C. 804(2).
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this final
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Reporting and
recordkeeping requirements.
10 CFR Part 431
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Incorporation by reference, Intergovernmental relations, Small
businesses.
Issued in Washington, DC, on April 10, 2014.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
For the reasons set forth in the preamble, DOE amends parts 429 and
431 of chapter II of title 10, of the Code of Federal Regulations, as
set forth below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317.
Sec. 429.42 [Amended]
0
2. Section 429.42 is amended by adding in paragraphs (b)(2)(i), (ii),
and (iii), the words ``increments of 0.01'' before the phrase
``kilowatt hours per day (kWh/day).''
PART 431--ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND
INDUSTRIAL EQUIPMENT
0
3. The authority citation for part 431 continues to read as follows:
Authority: 42 U.S.C. 6291-6317.
0
4. Section 431.62 is amended by:
0
a. Removing the definition for ``commercial hybrid refrigerator,
freezer, and refrigerator-freezer'';
0
b. Adding in alphabetical order the definitions for ``chef base or
griddle stand,'' ``closed solid,'' ``closed transparent,'' ``commercial
freezer,'' ``commercial hybrid,'' ``commercial refrigerator,''
``commercial refrigerator-freezer,'' ``door,'' ``operating
temperature,'' ``rating temperature,'' and ''transparent''; and
0
c. Revising the definitions for ``ice-cream freezer'' and ``lowest
application product temperature.''
The additions and revision read as follows:
Sec. 431.62 Definitions concerning commercial refrigerators, freezers
and refrigerator-freezers.
* * * * *
Chef base or griddle stand means commercial refrigeration equipment
that is designed and marketed for the express purpose of having a
griddle or other cooking appliance placed on top of it that is capable
of reaching temperatures hot enough to cook food.
Closed solid means equipment with doors, and in which more than 75
percent of the outer surface area of all doors on a unit are not
transparent.
Closed transparent means equipment with doors, and in which 25
percent or more of the outer surface area of all doors on the unit are
transparent.
Commercial freezer means a unit of commercial refrigeration
equipment in which all refrigerated compartments in the unit are
capable of operating below 32 [deg]F (2 [deg]F).
Commercial hybrid means a unit of commercial refrigeration
equipment:
(1) That consists of two or more thermally separated refrigerated
compartments that are in two or more different equipment families, and
(2) That is sold as a single unit.
Commercial refrigerator means a unit of commercial refrigeration
equipment in which all refrigerated compartments in the unit are
capable of operating at or above 32 [deg]F (2 [deg]F).
Commercial refrigerator-freezer means a unit of commercial
refrigeration equipment consisting of two or more refrigerated
compartments where at least one refrigerated compartment is
[[Page 22308]]
capable of operating at or above 32 [deg]F (2 [deg]F) and
at least one refrigerated compartment is capable of operating below 32
[deg]F (2 [deg]F).
* * * * *
Door means a movable panel that separates the interior volume of a
unit of commercial refrigeration equipment from the ambient environment
and is designed to facilitate access to the refrigerated space for the
purpose of loading and unloading product. This includes hinged doors,
sliding doors, and drawers. This does not include night curtains.
* * * * *
Ice-cream freezer means a commercial freezer that is designed to
operate at or below -5 [deg]F (2 [deg]F) (-21 [deg]C 1.1 [deg]C) and that the manufacturer designs, markets, or
intends for the storing, displaying, or dispensing of ice cream.
* * * * *
Lowest application product temperature means the lowest integrated
average temperature at which a given basic model is capable of
consistently operating (i.e., maintaining so as to comply with the
steady-state stabilization requirements specified in ASHRAE 72-2005
(incorporated by reference, see Sec. 431.63) for the purposes of
testing under the DOE test procedure).
* * * * *
Operating temperature means the range of integrated average
temperatures at which a self-contained commercial refrigeration unit or
remote-condensing commercial refrigeration unit with a thermostat is
capable of operating or, in the case of a remote-condensing commercial
refrigeration unit without a thermostat, the range of integrated
average temperatures at which the unit is marketed, designed, or
intended to operate.
* * * * *
Rating temperature means the integrated average temperature a unit
must maintain during testing (i.e., either as listed in the table at
Sec. 431.66(d)(1) or the lowest application product temperature).
* * * * *
Transparent means greater than or equal to 45 percent light
transmittance, as determined in accordance with the ASTM Standard E
1084-86 (Reapproved 2009), (incorporated by reference, see Sec.
431.63) at normal incidence and in the intended direction of viewing.
* * * * *
0
5. Section 431.63 is amended by:
0
a. Removing ``for Sec. 431.64'' in paragraphs (b)(1) and (b)(2) and
adding in its place, ``for Sec. 431.64 and appendices A and B to
subpart C to part 431'';
0
b. Removing ``and 431.66'' in paragraphs (c)(1) and (2) and adding in
its place, ``431.66, and appendices A and B to subpart C of part 431'';
and
0
c. Adding paragraphs (d) and (e) to read as follows:
Sec. 431.63 Materials incorporated by reference.
* * * * *
(d) ASHRAE. The American Society of Heating, Refrigerating, and
Air-Conditioning Engineers, Inc., 1971 Tullie Circle NE., Atlanta, GA
30329, or https://www.ashrae.org/.
(1) ANSI/ASHRAE Standard 72-2005, (ASHRAE 72-2005), ``Method of
Testing Commercial Refrigerators and Freezers,'' Copyright 2005, IBR
approved for Sec. 431.62, and appendices A and B to subpart C of part
431.
(2) [Reserved]
(e) ASTM. ASTM International, 100 Barr Harbor Drive, P.O. Box C700,
West Conshohocken, PA 19428, (877) 909-2786, or go to https://www.astm.org/.
(1) ASTM E 1084 (Reapproved 2009), ``Standard Test Method for Solar
Transmittance (Terrestrial) of Sheet Materials Using Sunlight,''
approved April 1, 2009, IBR approved for Sec. 431.62.
(2) [Reserved]
0
6. Section 431.64 is amended by revising paragraph (b) to read as
follows:
Sec. 431.64 Uniform test method for the measurement of energy
consumption of commercial refrigerators, freezers, and refrigerator-
freezers.
* * * * *
(b) Testing and calculations. Determine the daily energy
consumption of each covered commercial refrigerator, freezer, or
refrigerator-freezer by conducting the appropriate test procedure set
forth below, in appendix A or B to this subpart. The daily energy
consumption of commercial refrigeration equipment shall be calculated
using raw measured values and the final test results shall be reported
in increments of 0.01 kWh/day.
0
7. Section 431.66 is amended by:
0
a. In the table in paragraph (d)(1) removing every instance of ``>=32''
and adding in its place ``>=32 2'', removing every instance
of ``<32'' and adding in its place ``<32 2'', and removing
``<=-5**'' and adding in its place ``<=-5 2**''
0
b. Adding paragraph (f) to read as follows:
Sec. 431.66 Energy conservation standards and their effective dates.
* * * * *
(f) Exclusions. The energy conservation standards in paragraphs (b)
through (e) of this section do not apply to salad bars, buffet tables,
and chef bases or griddle stands.
0
8. Add appendices A and B to subpart C of part 431 to read as follows:
Appendix A to Subpart C of Part 431--Uniform Test Method for the
Measurement of Energy Consumption of Commercial Refrigerators,
Freezers, and Refrigerator-Freezers
Note: After October 20, 2014 but before March 28, 2017, any
representations made with respect to the energy use or efficiency of
commercial refrigeration equipment must be made in accordance with
the results of testing pursuant to this appendix.
Manufacturers conducting tests of commercial refrigeration
equipment after May 21, 2014 and prior to October 20, 2014, must
conduct such test in accordance with either this appendix or Sec.
431.64 as it appeared at 10 CFR part 430, subpart B, in the 10 CFR
parts 200 to 499 edition revised as of January 1, 2014. Any
representations made with respect to the energy use or efficiency of
such commercial refrigeration equipment must be in accordance with
whichever version is selected. Given that after October 20, 2014
representations with respect to the energy use or efficiency of
commercial refrigeration equipment must be made in accordance with
tests conducted pursuant to this appendix, manufacturers may wish to
begin using this test procedure as soon as possible.
1. Test Procedure
1.1. Determination of Daily Energy Consumption. Determine the
daily energy consumption of each covered commercial refrigerator,
freezer, refrigerator-freezer or ice-cream freezer by conducting the
test procedure set forth in the Air-Conditioning and Refrigeration
Institute (ARI) Standard 1200-2006, ``Performance Rating of
Commercial Refrigerated Display Merchandisers and Storage
Cabinets,'' section 3, ``Definitions,'' section 4, ``Test
Requirements,'' and section 7, ``Symbols and Subscripts''
(incorporated by reference, see Sec. 431.63). For each commercial
refrigerator, freezer, or refrigerator-freezer with a self-contained
condensing unit, also use ARI Standard 1200-2006, section 6,
``Rating Requirements for Self-contained Commercial Refrigerated
Display Merchandisers and Storage Cabinets.'' For each commercial
refrigerator, freezer, or refrigerator-freezer with a remote
condensing unit, also use ARI Standard 1200-2006, section 5,
``Rating Requirements for Remote Commercial Refrigerated Display
Merchandisers and Storage Cabinets.''
1.2. Methodology for Determining Applicability of Transparent
Door Equipment Families. To determine if a door for a given model of
commercial refrigeration equipment is transparent: (1) Calculate the
outer door surface area including frames and mullions; (2) calculate
the transparent surface area within the outer door surface area
excluding frames and mullions; (3) calculate the ratio
[[Page 22309]]
of (2) to (1) for each of the outer doors; and (4) the ratio for the
transparent surface area of all outer doors must be greater than
0.25 to qualify as a transparent equipment family.
1.3. Additional Specifications for Testing of Components and
Accessories. Subject to the provisions regarding specific components
and accessories listed below, all standard components that would be
used during normal operation of the basic model in the field shall
be installed and in operation during testing as recommended by the
manufacturer and representative of their typical operation in the
field unless such installation and operation is inconsistent with
any requirement of the test procedure. The specific components and
accessories listed in the subsequent sections shall be operated as
stated during the test.
1.3.1. Energy Management Systems. Applicable energy management
systems may be activated during the test procedure provided they are
permanently installed on the case, configured as sold and in such a
manner so as to operate automatically without the intervention of
the operator, and do not conflict with any of other requirements for
a valid test as specified in this appendix.
1.3.2. Lighting. Energize all lighting, except customer display
signs/lights as described in section 1.3.3 and UV lighting as
described in section 1.3.6 of this appendix, to the maximum
illumination level for the duration of testing. However, if a closed
solid unit of commercial refrigeration equipment includes an
automatic lighting control system that can turn off internal case
lighting when the door is closed, and the manufacturer recommends
the use of this system in writing in the product literature
delivered with the unit, then the lighting control should be
operated in the automatic setting, even if the model has a manual
switch that disables the automatic lighting control.
1.3.3. Customer display signs/lights. Do not energize
supplemental lighting that exists solely for the purposes of
advertising or drawing attention to the case and is not integral to
the operation of the case.
1.3.4. Condensate pan heaters and pumps. For self-contained
equipment only, all electric resistance condensate heaters and
condensate pumps must be installed and operational during the test.
This includes the stabilization period (including pull-down),
steady-state, and performance testing periods. Prior to the start of
the stabilization period as defined by ASHRAE 72-2005 (incorporated
by reference, see Sec. 431.63), the condensate pan must be dry.
Following the start of the stabilization period, allow any
condensate moisture generated to accumulate in the pan. Do not
manually add or remove water from the condensate pan at any time
during the test.
1.3.5. Anti-sweat door heaters. Anti-sweat door heaters must be
in operation during the entirety of the test procedure. Models with
a user-selectable setting must have the heaters energized and set to
the maximum usage position. Models featuring an automatic, non-user-
adjustable controller that turns on or off based on environmental
conditions must be operating in the automatic state. If a unit is
not shipped with a controller from the point of manufacture and is
intended to be used with an automatic, non-user-adjustable
controller, test the unit with a manufacturer-recommended controller
that turns on or off based on environmental conditions.
1.3.6. Ultraviolet lights. Do not energize ultraviolet lights
during the test.
1.3.7. Illuminated temperature displays and alarms. All
illuminated temperature displays and alarms shall be energized and
operated during the test as they would be during normal field
operation.
1.3.8. Condenser filters. Remove any nonpermanent filters that
are provided to prevent particulates from blocking a model's
condenser coil.
1.3.9. Refrigeration system security covers. Remove any devices
used to secure the condensing unit against unwanted removal.
1.3.10. Night curtains and covers. Do not deploy night curtains
or covers.
1.3.11. Grill options. Remove any optional, non-standard grills
used to direct airflow.
1.3.12. Misting or humidification systems. Misting or
humidification systems must be inactive during the test.
1.3.13. Air purifiers. Air purifiers must be inactive during the
test.
1.3.14. General purpose outlets. During the test, do not connect
any external load to any general purpose outlets contained within a
unit.
1.3.15. Crankcase heaters. Crankcase heaters must be operational
during the test. If a control system, such as a thermostat or
electronic controller, is used to modulate the operation of the
crankcase heater, it must be activated during the test.
1.3.16. Drawers. Drawers are to be treated as identical to doors
when conducting the DOE test procedure. Commercial refrigeration
equipment with drawers should be configured with the drawer pans
that allow for the maximum packing of test simulators and filler
packages without the filler packages and test simulators exceeding
90 percent of the refrigerated volume. Packing of test simulators
and filler packages shall be in accordance with the requirements for
commercial refrigerators without shelves, as specified in section
6.2.3 of ASHRAE 72-2005 (incorporated by reference, see Sec.
431.63).
2. Test Conditions
2.1. Integrated Average Temperatures. Conduct the testing
required in section 1 and 2 of this appendix A, and determine the
daily energy consumption at the applicable integrated average
temperature as found in the following table.
------------------------------------------------------------------------
Integrated
Category Test procedure average
temperature
------------------------------------------------------------------------
(i) Refrigerator with Solid ARI Standard.......... 38 [deg]F (2
[deg]F).
(ii) Refrigerator with ARI Standard.......... 38 [deg]F (2
[deg]F).
(iii) Freezer with Solid ARI Standard.......... 0 [deg]F (2
[deg]F).
(iv) Freezer with Transparent ARI Standard.......... 0 [deg]F (2
[deg]F).
(v) Refrigerator-Freezer with ARI Standard.......... 38 [deg]F (2 [deg]F)
for
refrigerator
compartment. 0
[deg]F (2 [deg]F)
for freezer
compartment.
(vi) Commercial Refrigerator ARI Standard.......... 38 [deg]F (2
Condensing Unit Designed for [deg]F).
Pull-Down Temperature
Applications and Transparent
Doors.
(vii) Ice-Cream Freezer....... ARI Standard.......... -15.0 [deg]F
1200-2006 \1\......... (2
[deg]F).
(viii) Commercial ARI Standard.......... (A) 0 [deg]F
Refrigerator, Freezer, and 1200-2006 \1\......... (2
Refrigerator-Freezer with a [deg]F) for low
Self-Contained Condensing temperature
Unit and without Doors. applications.
(B) 38 [deg]F
(2
[deg]F) for
medium
temperature
applications.
(ix) Commercial Refrigerator, ARI Standard.......... (A) 0 [deg]F
Freezer, and Refrigerator- 1200-2006 \1\......... (2
Freezer with a Remote [deg]F) for low
Condensing Unit. temperature
applications.
(B) 38 [deg]F
(2
[deg]F) for
medium
temperature
applications.
------------------------------------------------------------------------
\1\ Incorporated by reference, see Sec. 431.63.
[[Page 22310]]
2.2. Lowest Application Product Temperature. If a unit of
commercial refrigeration equipment is not able to be operated at the
integrated average temperature specified in the table in paragraph
2.1, test the unit at the lowest application product temperature
(LAPT), as defined in Sec. 431.62. For units equipped with a
thermostat, LAPT is the lowest thermostat setting. For remote
condensing equipment without a thermostat or other means of
controlling temperature at the case, the lowest application product
temperature is the temperature achieved with the dew point
temperature (as defined in AHRI Standard 1200 (I-P)-2010
(incorporated by reference see Sec. 431.63)) set to 5 degrees
colder than that required to maintain the manufacturer's lowest
specified operating temperature.
2.3. Testing at NSF Test Conditions. For commercial
refrigeration equipment that is also tested in accordance with NSF
test procedures (Type I and Type II), integrated average
temperatures and ambient conditions used for NSF testing may be used
in place of the DOE-prescribed integrated average temperatures and
ambient conditions provided they result in a more stringent test.
That is, the measured daily energy consumption of the same unit,
when tested at the rating temperatures and/or ambient conditions
specified in the DOE test procedure, must be lower than or equal to
the measured daily energy consumption of the unit when tested with
the rating temperatures or ambient conditions used for NSF testing.
The integrated average temperature measured during the test may be
lower than the range specified by the DOE applicable temperature
specification provided in paragraph 2.1 of this appendix, but may
not exceed the upper value of the specified range. Ambient
temperatures and/or humidity values may be higher than those
specified in the DOE test procedure.
3. Volume and Total Display Area
3.1. Determination of Volume. Determine the volume of a
commercial refrigerator, freezer, refrigerator-freezer, or ice-cream
freezer using the method set forth in the ANSI/AHAM HRF-1-2004,
``Energy, Performance and Capacity of Household Refrigerators,
Refrigerator-Freezers and Freezers'' (incorporated by reference, see
Sec. 431.63), section 3.21, ``Volume,'' sections 4.1 through 4.3,
``Method for Computing Total Refrigerated Volume and Total Shelf
Area of Household Refrigerators and Household Wine Chillers,'' and
sections 5.1 through 5.3, ``Method for Computing Total Refrigerated
Volume and Total Shelf Area of Household Freezers.''
3.2. Determination of Total Display Area. Determine the total
display area of a commercial refrigerator, freezer, refrigerator-
freezer, or ice-cream freezer using the method set forth in ARI
Standard 1200-2006 (incorporated by reference, see Sec. 431.63),
but disregarding the specification that ``transparent material
(>=65% light transmittance) in Appendix D. Specifically, total
display area shall be the sum of the projected area(s) of visible
product, expressed in ft \2\ (i.e., portions through which product
can be viewed from an angle normal, or perpendicular, to the
transparent area). Determine L as the interior length of the CRE
model, provided no more than 10 percent of that length consists of
non-transparent material. For those cases with greater than 10
percent of non-transparent area, L shall be determined as the
projected linear dimension(s) of visible product plus 10 percent of
non-transparent area.
See Figures A3.1, A3.2, A3.3, A3.4, and A3.5 as examples of how
to calculate the dimensions associated with calculation of total
display area. In the diagrams, Dh and L represent the
dimensions of the projected visible product.
BILLING CODE 6450-01-P
[[Page 22311]]
[GRAPHIC] [TIFF OMITTED] TR21AP14.000
[[Page 22312]]
[GRAPHIC] [TIFF OMITTED] TR21AP14.001
[[Page 22313]]
[GRAPHIC] [TIFF OMITTED] TR21AP14.002
BILLING CODE 6450-01-C
Appendix B to Subpart C of Part 431--Amended Uniform Test Method for
the Measurement of Energy Consumption of Commercial Refrigerators,
Freezers, and Refrigerator-Freezers
Note: Any representations made on or after March 28, 2017, with
respect to the energy use or efficiency of commercial refrigeration
equipment must be made in accordance with the results of testing
pursuant to this appendix.
1. Test Procedure
1.1. Determination of Daily Energy Consumption. Determine the
daily energy consumption of each covered commercial refrigerator,
freezer, refrigerator-freezer or ice-cream freezer by conducting the
test procedure set forth in the AHRI Standard 1200 (I-P)-2010,
section 3, ``Definitions,'' section 4, ``Test Requirements,'' and
section 7, ``Symbols and Subscripts'' (incorporated by reference,
see Sec. 431.63). For each commercial refrigerator, freezer, or
refrigerator-freezer with a self-contained condensing unit, also use
AHRI Standard 1200 (I-P)-2010, section 6, ``Rating Requirements for
Self-contained Commercial Refrigerated Display Merchandisers and
Storage Cabinets.'' For each commercial refrigerator, freezer, or
refrigerator-freezer with a remote condensing unit, also use AHRI
Standard 1200 (I-P)-2010, section 5, ``Rating Requirements for
Remote Commercial Refrigerated Display Merchandisers and Storage
Cabinets.''
1.2. Methodology for Determining Applicability of Transparent Door
Equipment Families
To determine if a door for a given model of commercial
refrigeration equipment is transparent: (1) Calculate the outer door
surface area including frames and mullions; (2) calculate the
transparent surface area within the outer door surface area
excluding frames and mullions; (3) calculate the ratio of (2) to (1)
for each of the outer doors; and (4) the ratio for the transparent
surface area of all outer doors must be greater than 0.25 to qualify
as a transparent equipment family.
1.3. Additional Specifications for Testing of Components and
Accessories. All standard components that would be used during
normal operation of the basic model in the field shall be installed
and used during testing as recommended by the manufacturer and
representative of their typical operation in the field unless such
installation and operation is inconsistent with any requirement of
the test procedure. The specific components and accessories listed
in the subsequent sections shall be operated as stated during the
test.
1.3.1. Energy Management Systems. Applicable energy management
systems may be activated during the test procedure provided they are
permanently installed on the case, configured and sold in such a
manner so as to operate automatically without the intervention of
the operator, and do not conflict with any of other requirements for
a valid test as specified in this appendix.
1.3.2. Lighting. All lighting except for customer display signs/
lights as described in section 1.3.3 and UV lighting as described in
section 1.3.6 of this appendix shall be energized to the maximum
illumination level for the duration of testing for commercial
refrigeration equipment with lighting except when the unit is
equipped with lighting occupancy sensors and controls. If the unit
includes an automatic lighting control system, it should be enabled
during test. If the unit is equipped with lighting occupancy sensors
and controls in should be tested in accordance with section 1.3.2.1
of this appendix.
1.3.2.1. Lighting Occupancy Sensors and Controls. For units with
lighting occupancy sensors and/or scheduled lighting controls
installed on the unit, determine the effect of the controls/sensors
on daily energy consumption by either a physical test or a
calculation method and using the variables that are defined as:
CECA is the alternate compressor energy consumption (kilowatt-
hours);
LECsc is the lighting energy consumption of internal case lights
with lighting occupancy sensors and controls deployed (kilowatt-
hours);
Pli is the rated power of lights when they are fully on (watts);
Pli(off) is the power of lights when they are off (watts);
[[Page 22314]]
Pli(dim) is the power of lights when they are dimmed (watts);
TDECo is the total daily energy consumption with lights fully
on, as measured by AHRI Standard 1200 (I-P)-2010 (kilowatt-hours);
tdim is the time period during which the lights are dimmed due
to the use of lighting occupancy sensors or scheduled lighting
controls (hours);
tdim,controls is the time case lighting is dimmed due to the use
of lighting controls (hours);
tdim,sensors is the time case lighting is dimmed due to the use
of lighting occupancy sensors (hours);
tl is the time period when lights would be on without lighting
occupancy sensors and/or scheduled lighting controls (24 hours);
toff is the time period during which the lights are off due to
the use of lighting occupancy sensors and/or scheduled lighting
controls (hours);
toff,controls is the time case lighting is off due to the use of
scheduled lighting controls (hours);
toff,sensors is the time case lighting is off due to the use of
lighting occupancy sensors (hours); and
tsc is the time period when lighting is fully on with lighting
occupancy sensors and scheduled lighting controls enabled (hours).
1.3.2.1.i. For both a physical test and a calculation method,
determine the estimated time off or dimmed, toff or
tdim, as the sum of contributions from lighting occupancy
sensors and scheduled lighting controls that dim or turn off
lighting, respectively, as shown in the following equation:
[GRAPHIC] [TIFF OMITTED] TR21AP14.003
[GRAPHIC] [TIFF OMITTED] TR21AP14.004
The sum of tsc, toff, and tdim
should equal 24 hours and the total time period during which the
lights are off or dimmed shall not exceed 10.8 hours. For cases with
scheduled lighting controls, the time the case lighting is off and/
or dimmed due to scheduled lighting controls
(toff,controls and/or tdim,controls, as
applicable) shall not exceed 8 hours. For cases with lighting
occupancy sensors installed, the time the case lighting is off and/
or dimmed due to lighting occupancy sensors (toff,sensors
and/or tdim,sensors, as applicable) shall not exceed 10.8
hours. For cases with lighting occupancy sensors and scheduled
lighting controls installed, the time the case lighting is off and/
or dimmed due to lighting occupancy sensors (toff,sensors
and/or tdim,sensors, as applicable) shall not exceed 2.8
hours and the time the case lighting is off and/or dimmed due to
scheduled lighting controls (toff,controls and/or
tdim,controls, as applicable) shall not exceed 8 hours.
1.3.2.1.ii. If using a physical test to determine the daily
energy consumption, turn off the lights for a time period equivalent
to toff and dim the lights for a time period equal to
tdim. If night curtains are also being tested on the
case, the period of lights off and/or dimmed shall begin at the same
time that the night curtain is being deployed and shall continue
consecutively, in that order, for the appropriate number of hours.
1.3.2.1.iii. If using a calculation method to determine the
daily energy consumption--
[GRAPHIC] [TIFF OMITTED] TR21AP14.005
Where EER represents the energy efficiency ratio from Table 1 in
AHRI Standard 1200 (I-P)-2010 (incorporated by reference, see Sec.
431.63) for remote condensing equipment or the values shown in the
following table for self-contained equipment:
EER for Self-Contained Commercial Refrigerated Display Merchandisers and
Storage Cabinets
------------------------------------------------------------------------
Operating temperature class EER Btu/W
------------------------------------------------------------------------
Medium..................................................... 11
Low........................................................ 7
Ice Cream.................................................. 5
------------------------------------------------------------------------
1.3.2.1.iii.C. For remote condensing units, calculate the
revised compressor energy consumption (CECR) by adding
the CECA to the compressor energy consumption (CEC)
measured in AHRI Standard 1200 (I-P)-2010 (incorporated by
reference, see Sec. 431.63). The CDEC for the entire case is the
sum of the CECR and LECsc (as calculated
above) and the fan energy consumption (FEC), anti-condensate energy
consumption (AEC), defrost energy consumption (DEC), and condensate
evaporator pan energy consumption (PEC) (as measured in AHRI
Standard 1200 (I-P)-2010).
1.3.2.1.iii.D. For self-contained units, the TDEC for the entire
case is the sum of total daily energy consumption as measured by the
AHRI Standard 1200 (I-P)-2010 (incorporated by reference, see Sec.
431.63) test with the lights fully on (TDECo) and
CECA, less the decrease in lighting energy use due to
lighting occupancy sensors and scheduled lighting controls, as shown
in following equation.
[GRAPHIC] [TIFF OMITTED] TR21AP14.006
1.3.3. Customer display signs/lights. Do not energize
supplemental lighting that exists solely for the purposes of
advertising or drawing attention to the case and is not integral to
the operation of the case.
1.3.4. Condensate pan heaters and pumps. For self-contained
equipment only, all electric resistance condensate heaters and
[[Page 22315]]
condensate pumps must be installed and in operation during the test.
This includes the stabilization period (including pull-down),
steady-state, and performance testing periods. Prior to the start of
the stabilization period as defined by ASHRAE 72-2005 (incorporated
by reference, see Sec. 431.63), the condensate pan must be dry.
Following the start of the stabilization period, allow any
condensate moisture generated to accumulate in the pan. Do not
manually add or remove water to or from the condensate pan at any
time during the test.
1.3.5. Anti-sweat door heaters. Anti-sweat door heaters must be
operational during the entirety of the test procedure. Models with a
user-selectable setting must have the heaters energized and set to
the maximum usage position. Models featuring an automatic, non-user-
adjustable controller that turns on or off based on environmental
conditions must be operating in the automatic state. If a unit is
not shipped with a controller from the point of manufacture and is
intended to be used with an automatic, non-user-adjustable
controller, test the unit with a manufacturer-recommended controller
that turns on or off based on environmental conditions.
1.3.6. Ultraviolet lights. Do not energize ultraviolet lights
during the test.
1.3.7. Illuminated temperature displays and alarms. All
illuminated temperature displays and alarms shall be energized and
operated during the test as they would be during normal field
operation.
1.3.8. Condenser filters. Remove any nonpermanent filters that
are provided to prevent particulates from blocking a model's
condenser coil.
1.3.9. Refrigeration system security covers. Remove any devices
used to secure the condensing unit against unwanted removal.
1.3.10. Night curtains and covers. For display cases sold with
night curtains installed, the night curtain shall be employed for 6
hours; beginning 3 hours after the start of the first defrost
period. Upon the completion of the 6-hour period, the night curtain
shall be raised until the completion of the 24-hour test period.
1.3.11. Grill options. Remove any optional non-standard grills
used to direct airflow.
1.3.12. Misting or humidification systems. Misting or
humidification systems must be inactive during the test.
1.3.13. Air purifiers. Air purifiers must be inactive during the
test.
1.3.14. General purpose outlets. During the test, do not connect
any external load to any general purpose outlets contained within a
unit.
1.3.15. Crankcase heaters. Crankcase heaters must be operational
during the test. If a control system, such as a thermostat or
electronic controller, is used to modulate the operation of the
crankcase heater, it must be utilized during the test.
1.3.16. Drawers. Drawers are to be treated as identical to doors
when conducting the DOE test procedure. Commercial refrigeration
equipment with drawers should be configured with the drawer pans
that allow for the maximum packing of test simulators and filler
packages without the filler packages and test simulators exceeding
90 percent of the refrigerated volume. Packing of test simulators
and filler packages shall be in accordance with the requirements for
commercial refrigerators without shelves, as specified in section
6.2.3 of ASHRAE 72-2005 (incorporated by reference, see Sec.
431.63).
2. Test Conditions
2.1. Integrated Average Temperatures. Conduct the testing
required in section 1 of this appendix B, and determine the daily
energy consumption at the applicable integrated average temperature
in the following table.
------------------------------------------------------------------------
Integrated average
Category Test procedure temperature
------------------------------------------------------------------------
(i) Refrigerator with Solid AHRI Standard 1200 38 [deg]F (2 [deg]F).
(ii) Refrigerator with AHRI Standard 1200 38 [deg]F (2 [deg]F).
(iii) Freezer with Solid Door(s) AHRI Standard 1200 0 [deg]F (2 [deg]F).
(iv) Freezer with Transparent AHRI Standard 1200 0 [deg]F (2 [deg]F).
(v) Refrigerator-Freezer with AHRI Standard 1200 38 [deg]F (2 [deg]F)
for refrigerator
compartment.
0 [deg]F (2 [deg]F)
for freezer
compartment.
(vi) Commercial Refrigerator AHRI Standard 1200 38 [deg]F (2 [deg]F).
Condensing Unit Designed for
Pull-Down Temperature
Applications and Transparent
Doors.
(vii) Ice-Cream Freezer......... AHRI Standard 1200 -15.0 [deg]F
(I-P)-2010 \1\. (2
[deg]F).
(viii) Commercial Refrigerator, AHRI Standard 1200 (A) 0 [deg]F
Freezer, and Refrigerator- (I-P)-2010 \1\. (2
Freezer with a Self-Contained [deg]F) for low
Condensing Unit and without temperature
Doors. applications.
(B) 38.0 [deg]F
(2
[deg]F) for
medium
temperature
applications.
(ix) Commercial Refrigerator, AHRI Standard 1200 (A) 0 [deg]F
Freezer, and Refrigerator- (I-P)-2010 \1\. (2
Freezer with a Remote [deg]F) for low
Condensing Unit. temperature
applications.
(B) 38.0 [deg]F
(2
[deg]F) for
medium
temperature
applications.
------------------------------------------------------------------------
\1\ Incorporated by reference, see Sec. 431.63.
[[Page 22316]]
2.2. Lowest Application Product Temperature. If a unit of
commercial refrigeration equipment is not able to be operated at the
integrated average temperature specified in the table in paragraph
2.1 of this appendix, test the unit at the lowest application
product temperature (LAPT), as defined in Sec. 431.62. For units
equipped with a thermostat, LAPT is the lowest thermostat setting.
For remote condensing equipment without a thermostat or other means
of controlling temperature at the case, the lowest application
product temperature is the temperature achieved with the dew point
temperature (as defined in AHRI Standard 1200 (I-P)-2010
(incorporated by reference, see Sec. 431.63)) set to 5 degrees
colder than that required to maintain the manufacturer's lowest
specified application temperature.
2.3. Testing at NSF Test Conditions. For commercial
refrigeration equipment that is also tested in accordance with NSF
test procedures (Type I and Type II), integrated average
temperatures and ambient conditions used for NSF testing may be used
in place of the DOE-prescribed integrated average temperatures and
ambient conditions provided they result in a more stringent test.
That is, the measured daily energy consumption of the same unit,
when tested at the rating temperatures and/or ambient conditions
specified in the DOE test procedure, must be lower than or equal to
the measured daily energy consumption of the unit when tested with
the rating temperatures or ambient conditions used for NSF testing.
The integrated average temperature measured during the test may be
lower than the range specified by the DOE applicable temperature
specification provided in paragraph 2.1 of this appendix, but may
not exceed the upper value of the specified range. Ambient
temperatures and/or humidity values may be higher than those
specified in the DOE test procedure.
3. Volume and Total Display Area
3.1. Determination of Volume. Determine the volume of a
commercial refrigerator, freezer, refrigerator-freezer, or ice-cream
freezer using the method set forth in the HRF-1-2008 (incorporated
by reference, see Sec. 431.63), section 3.30, ``Volume,'' and
sections 4.1 through 4.3, ``Method for Computing Refrigerated Volume
of Refrigerators, Refrigerator-Freezers, Wine Chillers and
Freezers.''
3.2. Determination of Total Display Area. Determine the total
display area of a commercial refrigerator, freezer, refrigerator-
freezer, or ice-cream freezer using the method set forth in ARI
Standard 1200-2006 (incorporated by reference, see Sec. 431.63),
but disregarding the specification that ``transparent material
(>=65% light transmittance) in Appendix D. Specifically, total
display area shall be the sum of the projected area(s) of visible
product, expressed in ft\2\ (i.e., portions through which product
can be viewed from an angle normal, or perpendicular, to the
transparent area). Determine L as the interior length of the CRE
model, provided no more than 5 inches of that length consists of
non-transparent material. For those cases with greater than 5 inches
of non-transparent area, L shall be determined as the projected
linear dimension(s) of visible product plus 5 inches of non-
transparent area.
See Figures A3.1, A3.2, and A3.3 as examples of how to calculate
the dimensions associated with calculation of total display area. In
the diagrams, Dh and L represent the dimensions of the
projected visible product.
BILLING CODE 4500-01-P
[GRAPHIC] [TIFF OMITTED] TR21AP14.007
[[Page 22317]]
[GRAPHIC] [TIFF OMITTED] TR21AP14.008
[[Page 22318]]
[GRAPHIC] [TIFF OMITTED] TR21AP14.009
[FR Doc. 2014-08640 Filed 4-18-14; 8:45 am]
BILLING CODE 6450-01-C