Transmission Planning Reliability Standards, 63036-63052 [2013-24828]
Download as PDF
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
(vii) 7.12.4.1. If the base/stand
supports the bassinet bed in any
unlocked position, place the
inclinometer on the mattress support at
the approximate center of the mattress
support. Care should be taken to avoid
seams, snap fasteners, or other items
that may affect the measurement
reading. Record the angle measurement.
(viii) 7.12.4.2. If the base/stand
supports the bassinet bed and the angle
of the mattress support surface
measured in 7.12.4.1 is less than 20
degrees from a horizontal plane,
evaluate whether the bassinet has a false
latch/lock visual indicator per 6.10.4.
(ix) 7.12.4.3. If the base/stand
supports the bassinet bed, and the angle
of the mattress support surface
measured in 7.12.4.1 is less than 20
degrees from a horizontal plane, and the
bassinet does not contain a false latch/
lock visual indicator, test the unit in
accordance with sections 7.4.2 through
7.4.7.
(x) 7.12.5. Repeat 7.12.2 through
7.12.4 for all of the manufacturer’s base/
stand recommended positions and use
modes.
(xi) 7.12.6. Repeat 7.12.4 through
7.12.5 with the bassinet bed rotated 180
degrees from the manufacturers
recommended use orientation, if the
base/stand supports the bassinet bed in
this orientation.
(A) Rationale. (1) This test
requirement addresses fatal and nonfatal
incidents involving bassinet beds that
tipped over or fell off their base/stand
when they were not properly locked/
latched to their base/stand or the latch
failed to engage as intended. Products
that appear to be in an intended use
position when the lock or latch is not
properly engaged can create a false
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
sense of security by appearing to be
stable. Unsecured or misaligned lock/
latch systems are a hidden hazard
because they are not easily seen by
consumers due to being located beneath
the bassinet or covered by decorative
skirts. In addition, consumers will avoid
activating lock/latch mechanisms for
numerous reasons if a bassinet bed
appears stable when placed on a stand/
base. Because of these foreseeable use
conditions, this requirement has been
added to ensure that bassinets with a
removable bassinet bed feature will be
inherently stable or it is obvious that
they are not properly secured.
(2) 6.10 allows bassinet bed designs
that:
(i) Cannot be supported by the base/
stand in an unlocked configuration,
(ii) Automatically lock and cannot be
placed in an unlocked position on the
base/stand,
(iii) Are clearly and obviously
unstable when the lock/latch is
misaligned or unused,
(iv) Provide a visual warning to
consumers when the product is not
properly locked onto the base/stand, or
(v) Have lock/latch mechanisms that
are not necessary to provide needed
stability.
(B) [Reserved]
Dated: September 30, 2013.
Todd A. Stevenson,
Secretary, Consumer Product Safety
Commission.
[FR Doc. 2013–24203 Filed 10–22–13; 8:45 am]
BILLING CODE 6355–01–P
PO 00000
Frm 00078
Fmt 4700
Sfmt 4700
DEPARTMENT OF ENERGY
Federal Energy Regulatory
Commission
18 CFR Part 40
[Docket Nos. RM12–1–000 and RM13–9–
000; Order No. 786]
Transmission Planning Reliability
Standards
Federal Energy Regulatory
Commission, Energy.
ACTION: Final rule.
AGENCY:
Under section 215 of the
Federal Power Act, the Federal Energy
Regulatory Commission approves
Transmission Planning (TPL) Reliability
Standard TPL–001–4, submitted by the
North American Electric Reliability
Corporation, the Commission-certified
Electric Reliability Organization.
Reliability Standard TPL–001–4
introduces significant revisions and
improvements by requiring annual
assessments addressing near-term and
long-term planning horizons for steady
state, short circuit and stability
conditions. Reliability Standard TPL–
001–4 also includes a provision that
allows a transmission planner to plan
for non-consequential load loss
following a single contingency by
providing a blend of specific
quantitative and qualitative parameters
for the permissible use of planned nonconsequential load loss to address bulk
electric system performance issues,
including firm limitations on the
maximum amount of load that an entity
may plan to shed, safeguards to ensure
against inconsistent results and arbitrary
determinations that allow for the
planned non-consequential load loss,
SUMMARY:
E:\FR\FM\23OCR1.SGM
23OCR1
ER23OC13.001
tkelley on DSK3SPTVN1PROD with RULES
63036
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
and a more specifically defined, open
and transparent, verifiable, and
enforceable stakeholder process. The
Commission finds in the Final Rule that
the proposed Reliability Standard is
just, reasonable, not unduly
discriminatory or preferential, and in
the public interest. In addition, the
Commission directs NERC to modify
Reliability Standard TPL–001–4 to
address the concern that the standard
could exclude planned maintenance
outages of significant facilities from
future planning assessments and directs
NERC to change the TPL–001–4,
Requirement R1 Violation Risk Factor
from medium to high.
DATES: This rule will become effective
December 23, 2013.
FOR FURTHER INFORMATION CONTACT:
Eugene Blick (Technical Information),
Office of Electric Reliability, Federal
Energy Regulatory Commission, 888
First Street, NE., Washington, DC
20426, Telephone: (202) 502–8066,
Eugene.Blick@ferc.gov.
Robert T. Stroh (Legal Information),
Office of the General Counsel, Federal
Energy Regulatory Commission, 888
First Street, NE., Washington, DC
20426, Telephone: (202) 502–8473,
Robert.Stroh@ferc.gov.
SUPPLEMENTARY INFORMATION:
145 FERC ¶ 61,051
tkelley on DSK3SPTVN1PROD with RULES
Before Commissioners: Jon Wellinghoff,
Chairman; Philip D. Moeller, John R.
Norris, Cheryl A. LaFleur, and Tony Clark.
(Issued October 17, 2013)
1. Under section 215(d) of the Federal
Power Act (FPA), the Commission
approves Transmission Planning (TPL)
Reliability Standard TPL–001–4,
submitted by the North American
Electric Reliability Corporation (NERC),
the Commission-certified Electric
Reliability Organization (ERO).1 The
Commission finds that Reliability
Standard TPL–001–4 introduces
significant revisions and improvements
to the TPL Reliability Standards,
including increased specificity of data
required for modeling conditions, and
requires annual assessments addressing
near-term and long-term planning
horizons for steady state, short circuit
and stability conditions. Further, we
find that the Reliability Standard
generally addresses the Commission
directives set forth in Order No. 693 and
subsequent Commission orders.2 We
agree with NERC that Reliability
1 16
U.S.C. 824o(d) (2006).
Reliability Standards for the BulkPower System, Order No. 693, FERC Stats. & Regs.
¶ 31,242, order on reh’g, Order No. 693–A, 120
FERC ¶ 61,053 (2007).
2 Mandatory
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
Standard TPL–001–4 includes specific
improvements over the currentlyeffective Transmission Planning
Reliability Standards and is responsive
to the Commission’s directives.
2. Further, in response to Order No.
762,3 Reliability Standard TPL–001–4
includes a provision that allows a
transmission planner to plan for nonconsequential load loss following a
single contingency. While the
Reliability Standard provides that ‘‘an
objective of the planning process is to
limit the likelihood and magnitude of
Non-Consequential Load Loss following
planning events,’’ the standard also
recognizes that ‘‘[i]n limited
circumstances, Non-Consequential Load
Loss may be needed throughout the
planning horizon to ensure that BES
performance requirements are met.’’ 4
Thus, for such limited circumstances,
Reliability Standard TPL–001–4
provides a blend of specific quantitative
and qualitative parameters for the
permissible use of planned nonconsequential load loss to address bulk
electric system performance issues,
including firm limitations on the
maximum amount of load that an entity
may plan to shed, safeguards to ensure
against inconsistent results and arbitrary
determinations that allow for the
planned non-consequential load loss,
and a more specifically defined, open
and transparent, verifiable, and
enforceable stakeholder process.
3. For the reasons discussed in detail
below, the Commission finds that
Reliability Standard TPL–001–4 is just,
reasonable, not unduly discriminatory
or preferential, and in the public
interest. Therefore, pursuant to section
215(d) of the FPA the Commission
approves proposed Reliability Standard
TPL–001–4. Thus, the Commission
approves footnote 12 to Table 1 of the
Reliability Standard (formerly referred
to as footnote ‘b’). In addition, as
discussed below, the Commission finds
NERC’s explanation on protection
system failures versus relay failures,
assessment of backup or redundant
protection systems, single line to ground
faults and the Order No. 693 directives
to be reasonable. However, the
Commission has concerns about two
issues and directs NERC to modify
Reliability Standard TPL–001–4 to
address the concern that the standard
3 Transmission Planning Reliability Standards,
Order No. 762, 139 FERC ¶ 61,060 (2012) (Order
No. 762), order on reconsideration, 140 FERC ¶
61,101 (2012). See also Transmission Planning
Reliability Standards, 139 FERC ¶ 61,059 (2012)
(April 2012 NOPR).
4 Reliability Standard TPL–001–4, Table I (Steady
State and Stability Performance Extreme Events),
n.12.
PO 00000
Frm 00079
Fmt 4700
Sfmt 4700
63037
could exclude planned maintenance
outages of significant facilities from
future planning assessments and directs
NERC to change the TPL–001–4,
Requirement R1 VRF from medium to
high.
I. Background
A. Regulatory History
4. In Order No. 693, the Commission
accepted the Version 0 TPL Reliability
Standards.5 Further, pursuant to FPA
section 215(d)(5), the Commission
directed NERC to develop modifications
through the Reliability Standards
development process to address certain
issues identified by the Commission. In
addition, the Commission neither
approved nor remanded Reliability
Standards TPL–005–0 and TPL–006–0
because these two standards applied
only to regional reliability
organizations, the predecessors to the
statutorily recognized Regional Entities.
With regard to Reliability Standard
TPL–002–0b, Table 1, footnote ‘b,’
which applies to planned nonconsequential load loss, the
Commission directed NERC to clarify
footnote ‘b’ regarding the planned nonconsequential load loss for a single
contingency event.6 In a March 18, 2010
order, the Commission directed NERC to
submit a modification to footnote ‘b’
responsive to the Commission’s
directive in Order No. 693 by June 30,
2010.7 In a June 11, 2010 order, the
Commission extended the compliance
deadline until March 31, 2011.8
Remand of Footnote b of the Version 1
TPL Reliability Standard (RM11–18–
000)
5. On March 31, 2011, NERC
submitted proposed Reliability Standard
TPL–002–1 (Version 1). NERC proposed
to modify Table 1, footnote ‘b’ to permit
planned non-consequential load loss
when documented and subjected to an
open stakeholder process.9 In Order No.
5 Order No. 693, FERC Stats. & Regs. ¶ 31,242 at
PP 1840, 1845. The currently-effective versions of
the TPL Reliability Standards are as follows: TPL–
001–0.1, TPL–002–0b, TPL–003–0a, and TPL–004–
0.
6 Order No. 693, FERC Stats. & Regs. ¶ 31,242 at
P 1792.
7 Mandatory Reliability Standards for the Bulk
Power System, 130 FERC ¶ 61,200 (2010).
8 Mandatory Reliability Standards for the Bulk
Power System, 131 FERC ¶ 61,231 (2010).
9 See Order No. 693, FERC Stats. & Regs. ¶ 31,242
at P 1794. Non-consequential load loss includes the
removal, by any means, of any planned firm load
that is not directly served by the elements that are
removed from service as a result of the contingency.
Currently-effective footnote ‘b’ deals with both
consequential load loss and non-consequential load
loss. NERC’s proposed footnote ‘b’ characterized
both types of load loss as ‘‘firm demand.’’
E:\FR\FM\23OCR1.SGM
23OCR1
63038
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
762, the Commission remanded to
NERC the proposed modification to
footnote ‘b,’ concluding that the
proposed revisions did not meet the
Commission’s Order No. 693 directives,
nor did the revisions achieve an equally
effective and efficient alternative.10 The
Commission stated that the proposal did
not adequately clarify or define the
circumstances in which an entity can
use planned non-consequential load
loss as a mitigation plan to meet
performance requirements for single
contingency events. The Commission
also explained that the procedural and
substantive parameters of NERC’s
proposal were too undefined to provide
assurances that the process will be
effective in determining when it is
appropriate to plan for nonconsequential load loss, did not contain
NERC-defined criteria on circumstances
to determine when an exception for
planned non-consequential load loss is
permissible, and could result in
inconsistent results in implementation.
Accordingly, the Commission remanded
the filing to NERC and directed NERC
to develop revisions to footnote ‘b’ that
would address the Commission’s
concerns. Additionally, in Order No.
762, the Commission directed NERC to
‘‘identify the specific instances of any
planned interruptions of firm demand
under footnote ‘b’ and how frequently
the provision has been used.’’ 11
Proposed Remand of Version 2 of the
TPL Reliability Standard (RM12–1–000)
6. On October 19, 2011, NERC
submitted a petition seeking approval of
a revised and consolidated TPL
Reliability Standard that combined the
four currently-effective TPL Reliability
Standards into a single standard, TPL–
001–2 (Version 2).12 The Version 2
standard included language similar to
NERC’s Version 1 proposal with regard
to utilizing non-consequential load loss.
The Version 2 standard included a nonconsequential load loss provision in
Table 1—Steady State & Stability
Performance Footnotes (Planning Events
and Extreme Events), footnotes 9 and
12.13
10 Order
No. 762, 139 FERC ¶ 61,060.
P 20.
12 NERC’s October 2011 petition sought approval
of Reliability Standard TPL–001–2, the associated
implementation plan and Violation Risk Factors
(VRFs) and Violation Severity Levels (VSLs), as
well as five new definitions to be added to the
NERC Glossary of Terms. NERC also requested
approval to retire four currently-effective TPL
Reliability Standards: TPL–001–1, TPL–002–1b,
TPL–003–1a; and TPL–004–1. In addition, NERC
requested to withdraw two pending Reliability
Standards: TPL–005–0 and TPL–006–0.1.
13 NERC’s October 2011 Petition at 12. NERC’s
proposal in Docket No. RM11–18–000, Table 1,
tkelley on DSK3SPTVN1PROD with RULES
11 Id.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
7. On the same day that the
Commission issued Order No. 762, the
Commission issued a notice of proposed
rulemaking (April 2012 NOPR) stating
that, notwithstanding that proposed
Version 2 included specific
improvements over the currentlyeffective Transmission Planning
Reliability Standards, footnote 12
‘‘allow[s] for transmission planners to
plan for non-consequential load loss
following a single contingency without
adequate safeguards [and] undermines
the potential benefits the proposed
Reliability Standard may provide.’’ 14
Thus, the Commission stated that its
concerns regarding the stakeholder
process set forth in footnote 12 required
a proposal to remand the entire
Reliability Standard. The Commission
added that resolution of the footnote 12
concerns ‘‘would allow the industry,
NERC and the Commission to go
forward with the consideration of other
improvements contained in proposed
Version 2.’’ 15 In addition, the April
2012 NOPR asked for comment on
various aspects of the consolidated
Version 2 Reliability Standard.
Comments on the NOPR were due by
July 20, 2012. The following entities
submitted comments: NERC, the Edison
Electric Institute (EEI), ISO/RTOs,16 ITC
Companies,17 Midcontinent
Independent System Operator Inc.
(MISO),18 American Transmission
Company LLC (ATCLLC), Powerex
Corporation (Powerex), Bonneville
Power Administration (BPA), and Hydro
One Networks and the Independent
Electricity System Operator (Hydro One
and IESO).
Proposed Reliability Standard TPL–
001–4—Version 4 (RM13–9–000)
8. On February 28, 2013, NERC
submitted proposed Reliability Standard
TPL–001–4 (Version 4) in response to
the Commission’s remand in Order No.
762 and concerns with regard to Table
footnote ‘b’ referred to planned load shed as
planned ‘‘interruption of Firm Demand.’’ In
footnote 12, proposed to replace footnote ‘b,’ NERC
changed the term from ‘‘interruption of Firm
Demand’’ to utilization of ‘‘Non-Consequential Load
Loss.’’
14 April 2012 NOPR, 139 FERC ¶ 61,059 at P 55.
15 Id. P 3.
16 The ISO/RTOs consist of Electric Reliability
Council of Texas, Inc., ISO New England, Inc.,
Midcontinent Independent Transmission System
Operator Inc., New York Independent System
Operator, Inc., PJM Interconnection L.L.C., and
Southwest Power Pool, Inc.
17 ITC Companies consist of ITCTransmission,
Michigan Electric Transmission Company LLC, ITC
Midwest LLC, and ITC Great Plains.
18 Effective April 26, 2013, MISO changed its
name from ‘‘Midwest Independent Transmission
System Operator, Inc.’’ to ‘‘Midcontinent
Independent System Operator, Inc.’’
PO 00000
Frm 00080
Fmt 4700
Sfmt 4700
1 footnote 12 identified in the April
2012 NOPR.19 Reliability Standard
TPL–001–4 includes eight requirements
and Table 1: 20
Requirement R1: Requires the
transmission planner and planning
coordinator to maintain system models
and provides a specific list of items
required for the system models and that
the models represent projected system
conditions. The planner is required to
model the items that are variable, such
as load and generation dispatch, based
specifically on the expected system
conditions.
Requirement R2: Requires each
transmission planner and planning
coordinator to prepare an annual
planning assessment of its portion of the
bulk electric system and must use
current or qualified past studies,
document assumptions, and document
summarized results of the steady state
analyses, short circuit analyses, and
stability analyses. Requirement R2, Part
2.1.3 requires the planner to assess
system performance utilizing a current
annual study or qualified past study for
each known outage with a duration of
at least six months for certain events. It
also clarifies that qualified past studies
can be utilized in the analysis while
tightly defining the qualifications for
those studies. Requirement R2 includes
a new part 2.7.3 that allows
transmission planners and planning
coordinators to utilize nonconsequential load loss to meet
performance requirements if the
applicable entities are unable to
complete a corrective action plan due to
circumstances beyond their control.
Requirements R3 and R4:
Requirement R3 describes the
requirements for steady state studies
and Requirement R4 explains the
requirements for stability studies.
Requirement R3 and Requirement R4
also require that simulations duplicate
what will occur in an actual power
system based on the expected
performance of the protection systems.
19 In its filing, NERC stated that the Version 4
standard, i.e., TPL–001–4, modifies the pending
Version 2 consolidated standard, TPL–001–2. NERC
also submitted, alternatively, a group of four TPL
standards (TPL–001–3, TPL–002–2b, TPL–003–2a,
and TPL–004–2, collectively, the Version 3 TPL
standards) that would modify ‘‘footnote b’’ of the
currently-effective TPL standards, ‘‘[i]n the event
the Commission does not approve the Consolidated
TPL Standards [Version 4].’’ NERC Petition at 4.
Because we approve TPL–001–4, references
throughout this Final Rule are to the Version 4
standard.
20 The filed proposed Reliability Standard is not
attached to the Final Rule but is available on the
Commission’s eLibrary document retrieval system
in Docket Nos. RM12–1–000 and RM13–9–000 and
are available on NERC’s Web site, https://
www.nerc.com.
E:\FR\FM\23OCR1.SGM
23OCR1
tkelley on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
Requirement R3 and Requirement R4
also include new parts that require the
planners to conduct an evaluation of
possible actions designed to reduce the
likelihood or the consequences of
extreme events that cause cascading.
Requirement R5: Requirement R5
deals with voltage criteria and voltage
performance. NERC proposes in
Requirement R5 that each transmission
planner and planning coordinator must
have criteria for acceptable system
steady state voltage limits, postcontingency voltage deviations, and the
transient voltage response for its system.
For transient voltage response the
criteria must specify a low-voltage level
and a maximum length of time that
transient voltages may remain below
that level. This requirement will
establish more robust transmission
planning for organizations and greater
consistency as these voltage criteria are
shared.
Requirement R6: Specifies that an
entity must define and document the
criteria or methodology used to identify
system instability for conditions such as
cascading, voltage instability, or
uncontrolled islanding within its
planning assessment.
Requirement R7: Mandates
coordination of individual and joint
responsibilities for the planning
coordinator and the transmission
planner which is intended to eliminate
confusion regarding the responsibilities
of the applicable entities and assures
that all elements needed for regional
and wide area studies are defined with
a specific entity responsible for each
element and that no gaps will exist in
planning for the Bulk-Power System.
Requirement R8: Addresses the
sharing of planning assessments with
neighboring systems. The requirement
ensures that information is shared with
and input received from adjacent
entities and other entities with a
reliability related need that may be
affected by an entity’s system planning.
Table 1: Similar to the currentlyeffective TPL Reliability Standard, the
revised standard contains a series of
planning events and describes system
performance requirements in Table 1 for
a range of potential system
contingencies required to be evaluated
by the planner. Table 1 includes three
parts: Steady State & Stability
Performance Planning Events, Steady
State & Stability Performance Extreme
Events, and Steady State & Stability
Performance Footnotes. Table 1
categorizes the events as either
‘‘planning events’’ or ‘‘extreme events.’’
The proposed table lists seven
contingency planning events that
require steady-state and stability
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
analysis as well as five extreme event
contingencies.
9. NERC modified footnote 12 of
Table 1 to provide specific parameters
for the permissible use of planned nonconsequential load loss to address bulk
electric system performance issues,
including: (1) Firm limitations on the
maximum amount of load that an entity
may plan to shed, (2) safeguards to
ensure against inconsistent results and
arbitrary determinations that allow for
the planned non-consequential load
loss, and (3) a more specifically defined,
open and transparent, verifiable, and
enforceable stakeholder process.
Footnote 12 as modified provides:
An objective of the planning process is to
minimize the likelihood and magnitude of
Non-Consequential Load Loss following
planning events. In limited circumstances,
Non-Consequential Load Loss may be needed
throughout the planning horizon to ensure
that BES performance requirements are met.
However, when Non-Consequential Load
Loss is utilized under footnote 12 within the
Near-Term Transmission Planning Horizon to
address BES performance requirements, such
interruption is limited to circumstances
where the Non-Consequential Load Loss
meets the conditions shown in Attachment 1.
In no case can the planned NonConsequential Load Loss under footnote 12
exceed 75 MW for US registered entities. The
amount of planned Non-Consequential Load
Loss for a non-US Registered Entity should
be implemented in a manner that is
consistent with, or under the direction of, the
applicable governmental authority or its
agency in the non-US jurisdiction.
10. Attachment 1 to TPL–001–4,
referenced in footnote 12 has three
sections: (I) Stakeholder process, (II)
information an entity must provide to
stakeholders, and (III) instances for
which regulatory review of planned
non-consequential load loss under
footnote 12 is required. Section I
describes five criteria that apply to the
open and transparent stakeholder
process that an entity must implement
when it seeks to use footnote 12. Section
I provides that an entity does not have
to repeat the stakeholder process for a
specific application of footnote 12 with
respect to subsequent planning
assessments unless conditions have
materially changed for that specific
application.
11. Section II of Attachment 1
specifies eight categories of information
that entities must provide to
stakeholders, including estimated
amount, frequency and duration of
planned non-consequential load loss
under footnote 12. An entity must also
provide information on alternatives
considered and future plans to alleviate
the need for planned non-consequential
load loss.
PO 00000
Frm 00081
Fmt 4700
Sfmt 4700
63039
12. Section III of Attachment 1
describes the process for planned nonconsequential load loss greater than 25
MW. Specifically, planned nonconsequential load loss between 25 MW
and 75 MW, or any planned nonconsequential load loss at the 300 kV
level or above would receive greater
scrutiny by regulatory authorities and
the ERO. Where these parameters apply,
‘‘the Transmission Planner or Planning
Coordinator must ensure that applicable
regulatory authorities or governing
bodies responsible for retail electric
service issues do not object to the use
of Non-Consequential Load Loss under
footnote 12.’’ 21 Further, ‘‘[o]nce
assurance has been received that the
applicable regulatory authorities . . .
responsible for retail electric service
issues do not object . . . the Planning
Coordinator or Transmission Planner
must submit the information [in Section
II of Attachment 1] to the ERO for a
determination of whether there are any
Adverse Reliability Impacts’’ caused by
the responsible entity’s request to use
footnote 12.22 According to NERC, this
provision provides safeguards against
arbitrary or inconsistent determinations,
and also ‘‘preserves, to the extent
practicable, the role of Retail
Regulators,’’ while allowing ERO review
for possible adverse reliability
impacts.23
13. NERC stated that the combination
of numerical limitations and other
considerations, such as costs and
alternatives, guards against a
determination based solely on a
quantitative threshold becoming an
acceptable de facto interpretation of
planned non-consequential load loss.
According to NERC, the procedures in
footnote 12 would enable acceptable,
but limited, circumstances of planned
non-consequential load loss after a
thorough stakeholder review and
approval and ERO review.
14. NERC also stated that, because
footnote 12 differs from footnote ‘b’
included in the currently-effective TPL
Reliability Standards, data do not yet
exist on the frequency of instances of
planned non-consequential load loss
under the new footnote 12.
Consequently, NERC stated that it will
monitor the use of footnote 12 and will
report the results of this monitoring
21 NERC Petition, Exhibit A, proposed Reliability
Standard TPL–001–4, Attachment I, section 3.
22 NERC Petition, Exhibit A, proposed Reliability
Standard TPL–001–4, Attachment I, section 3.
NERC defines ‘‘Adverse Reliability Impact’’ as
‘‘[t]he impact of an event that results in frequencyrelated instability; unplanned tripping of load or
generation; or uncontrolled separation or cascading
outages that affects a widespread area of the
Interconnection.’’ NERC Glossary at 4.
23 NERC February 2013 Petition at 19.
E:\FR\FM\23OCR1.SGM
23OCR1
tkelley on DSK3SPTVN1PROD with RULES
63040
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
after the first two years of the footnote’s
implementation.24
15. NERC requested that requirements
R1 and R7 of the Version 4 Reliability
Standard as well as the definitions
become effective on the first day of the
first calendar quarter twelve months
after applicable regulatory approval. In
addition, except as indicated below,
NERC requested that Requirements R2
through R6 and Requirement R8
including Table 1—Steady State &
Stability Performance Planning Events,
Table 1—Steady State & Stability
Performance Extreme Events, Table 1—
Steady State & Stability Performance
Footnotes (Planning Events & Extreme
Events) and Attachment 1 become
effective and subject to compliance on
the first day of the first calendar quarter,
24 months after applicable regulatory
approval.
16. NERC also proposed that, for 84
calendar months beginning the first day
of the first calendar quarter following
applicable regulatory approval,
concurrent with the 24 month effective
date of Requirement R2, corrective
action plans applying to specific
categories of contingencies and events
identified in TPL–001–4, Table 1 are
allowed to include non-consequential
load loss and curtailment of firm
transmission service (in accordance
with Requirement R2, Part 2.7.3) that
would not otherwise be permitted by
the requirements of the Version 4
Reliability Standard. Further, NERC
stated that Requirement R2, Part 2.7.3
addresses situations that are beyond the
control of the planner that prevent the
implementation of a corrective action
plan in the required timeframe. Some
examples of situations beyond the
control of the planner could include a
state road widening project taking
substation land that was targeted for
expansion or a ruling preventing the
entity from condemning the land
necessary for a project.
17. NERC also requested approval to
retire the currently-effective TPL
Reliability Standards and to withdraw
two pending TPL Reliability Standards,
TPL–005–0 and TPL–006–0.1, because it
transferred the requirements of the
pending Reliability Standards to
sections 803 and 804 of NERC’s Rules of
Procedure. NERC proposed to retire TPL
Reliability Standards TPL–001–0.1,
TPL–002–0b, TPL–003–0a, and TPL–
004–0 on midnight of the day
immediately prior to the effective date
of TPL–001–4. However, during the 24month implementation period, all
aspects of the currently-effective TPL
Reliability Standards, TPL–001–0.1
24 NERC’s
February 2013 Petition at 11.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
through TPL–004–0 will remain in
effect for compliance monitoring. NERC
stated that the 24 month period is to
allow entities to develop, perform and/
or validate new or modified studies
necessary to implement and meet
Reliability Standard TPL–001–4. NERC
explained that the specified effective
dates allow sufficient time for proper
assessment of the available options
necessary to create a viable corrective
action plan that is compliant with the
new TPL Reliability Standard.
Supplemental NOPR
18. On May 16, 2013, the Commission
issued a Supplemental NOPR which
proposed to approve the Version 4 TPL
Reliability Standard, TPL–001–4, as
just, reasonable, not unduly
discriminatory or preferential, and in
the public interest.25 In the
Supplemental NOPR, the Commission
suggested that, while NERC’s proposal
differs from the Commission directives
on the matter of utilizing nonconsequential load loss, NERC’s
proposal adequately addresses the
underlying reliability concerns raised in
Order No. 693, Order No. 762 and the
April 2012 NOPR and, thus, is an
equally effective and efficient
alternative to address the Commission’s
directives.26 In the Supplemental
NOPR, the Commission proposed to
find that proposed footnote 12 would
improve reliability by providing a blend
of specific quantitative and qualitative
parameters for the permissible use of
planned non-consequential load loss to
address bulk electric system
performance issues. In addition, the
Commission stated that the stakeholder
process appears to be adequately
defined and includes specific criteria
and guidelines that a responsible entity
must follow before it may use planned
non-consequential load loss to meet
Reliability Standard TPL–001–4
performance requirements for a single
contingency event. Further, the
Supplemental NOPR indicated that
NERC’s proposal provides reasonable
safeguards, including a review process
by NERC, to protect against adverse
reliability impacts that could otherwise
result from planned non-consequential
load loss.27
19. In the Supplemental NOPR, the
Commission proposed to direct that
NERC submit a report on the use of
footnote 12, due at the end of the first
calendar quarter after the first two years
25 Transmission Planning Reliability Standards,
Notice of Proposed Rulemaking, 143 FERC ¶ 61,136
(2013) (Supplemental NOPR).
26 Supplemental NOPR, 143 FERC ¶ 61,136 at P
18.
27 Id. P 19.
PO 00000
Frm 00082
Fmt 4700
Sfmt 4700
of implementation of footnote 12 to
provide an analysis of the use of
footnote 12, including but not limited to
information on the duration, frequency
and magnitude of planned nonconsequential load loss, and typical
(and if significant, atypical) scenarios
where entities plan for nonconsequential load loss. The
Commission proposed that the report
should also address the effectiveness of
the stakeholder process and the use and
effectiveness of the local regulatory
review and NERC review.28
20. Comments on the Supplemental
NOPR were due on June 24, 2013.
NERC, MISO and ITC Companies filed
comments in response to the
Supplemental NOPR.
II. Discussion
21. Pursuant to FPA section 215(d),
we find that Reliability Standard TPL–
001–4 is just, reasonable, not unduly
discriminatory or preferential, and in
the public interest. While NERC’s
proposal differs from the Commission
directives, we find that NERC
adequately addressed the directives and
underlying reliability concerns of Order
No. 693, Order No. 762 and the April
2012 NOPR and, thus, is an equally
effective and efficient alternative to
address the Commission’s concerns.29
We find that the revised TPL Reliability
Standard improves uniformity and
transparency in the transmission
planning process and clarifies the
instances where planners may utilize
planned load loss in establishing
transmission planning performance
requirements for reliable bulk electric
system operations across normal and
contingency conditions. We also find
that Reliability Standard TPL–001–4
will serve as a foundation for annual
planning assessments conducted by
planning coordinators and transmission
planners to plan the bulk electric system
reliably in response to a range of
potential contingencies. Further, we
find that the Reliability Standard
presents clear, measurable, and
enforceable requirements that each
planning coordinator and transmission
planner must follow when planning its
system.
22. In the Supplemental NOPR, the
Commission stated it would issue a final
rule that addresses the consolidated
transmission planning Reliability
Standard, TPL–001–4. Therefore, this
Final Rule addresses the modified
footnote 12 and comments received in
response to the Supplemental NOPR as
28 Id.
P 20.
Order No. 693, FERC Stats. & Regs. ¶
31,242 at P 1792.
29 See
E:\FR\FM\23OCR1.SGM
23OCR1
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
well as other aspects of the consolidated
TPL Reliability Standard raised in the
April 2012 NOPR.
tkelley on DSK3SPTVN1PROD with RULES
A. Footnote 12 and Planned Use of NonConsequential Load Loss NOPR
Proposal
23. In the Supplemental NOPR, the
Commission proposed to approve
footnote 12. The Commission indicated
that the proposal differs from the
Commission directives but adequately
addresses the underlying reliability
concerns raised in Order No. 693, Order
No. 762 and the April 2012 NOPR and,
thus, is an equally effective and efficient
alternative to address the Commission’s
directives.30 The Supplemental NOPR
indicated that proposed footnote 12
would improve reliability by providing
a blend of specific quantitative and
qualitative parameters for the
permissible use of planned nonconsequential load loss to address bulk
electric system performance issues. In
addition, the Supplemental NOPR
stated that the stakeholder process
appeared to be adequately defined and
includes specific criteria and guidelines
that a responsible entity must follow
before it may use planned nonconsequential load loss to meet
Reliability Standard TPL–001–4
performance requirements for a single
contingency event. Further, the
Supplemental NOPR stated that NERC’s
proposal provides reasonable
safeguards, including a review process
by NERC, to protect against adverse
reliability impacts that could otherwise
result from planned non-consequential
load loss.
Comments
24. NERC supports the Commission’s
proposal in the Supplemental NOPR.
NERC also commits to monitor the use
of footnote 12 and issue a report
containing the findings of the
monitoring by the end of the first
calendar quarter following the first two
years of implementation. ITC
Companies believe NERC’s proposal is a
significant improvement over the
currently-effective standard and support
approval. ITC Companies urge the
Commission to clarify that the use of
planned non-consequential load loss
should be used rarely and should not be
considered a de facto planning solution.
25. MISO supports Reliability
Standard TPL–001–4 as an
improvement over the current standard
but has two concerns regarding
Attachment 1, referenced in footnote 12.
30 See Order No. 693, FERC Stats. & Regs. ¶
31,242 at P 1792; Mandatory Reliability Standards
for the Bulk Power System, 131 FERC ¶ 61,231 at
P 21.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
First, MISO argues that the Commission
should direct NERC to eliminate or
clarify the requirement that requires
interaction with and approval by
applicable regulatory authorities or
government bodies responsible for retail
electric service. MISO claims that such
a requirement adds an additional layer
of complexity and administrative
burden to compliance of proposed
Reliability Standard TPL–001–4 without
any attendant benefit. According to
MISO, the reference in Attachment 1 to
‘‘applicable regulatory authorities or
governing bodies’’ is not clear. MISO
states that, while these terms could
encompass a state’s public service
commission or public utility
commission, the terms could also
potentially include other state bodies or
agencies such as consumer advocacy
and protection bodies, state legislatures,
and city or municipal bodies. According
to MISO, if these other entities would be
considered ‘‘governing bodies
responsible for retail electric issues,’’ a
transmission planner would need to
seek and receive assurances from each
of these bodies. MISO also suggests that,
prior to finalization of its transmission
expansion plan each year, a planner
could obtain the assent of the applicable
public utility commission, and yet have
its transmission plans subsequently
upended because it did not obtain
additional assent from a different state
agency that has some involvement in
retail electric matters.
26. MISO also questions what it
means to ensure that an applicable
regulatory authority or governing body
‘‘does not object’’ to the inclusion of
non-consequential load loss in the
planning process. MISO suggests that it
could mean input of agency staff or a
more formal decision that is voted on by
the agency’s commissioners. MISO
argues that use of an open stakeholder
process that allows for robust input by
any interested parties will ensure that
all interested state agencies will have a
say in the process, and that any
objections of such agencies to the
inclusion of non-consequential load loss
will be incorporated into the relevant
planning decisions.
27. Alternatively, MISO requests that
the Commission clarify or direct NERC
to clarify the ‘‘does not object’’ language
to mean that: (1) The phrase ‘‘applicable
regulatory authorities or governing
bodies’’ means only the public utility
commission or public service
commission in the affected states, and
does not refer to any other state entity;
and (2) comments or other input
submitted by the affected state public
service commission or public utility
commission in the Attachment 1
PO 00000
Frm 00083
Fmt 4700
Sfmt 4700
63041
stakeholder process indicating that the
agency ‘‘does not object’’ to the
inclusion of non-consequential load loss
in the planning process are sufficient to
satisfy the ‘‘does not object’’
requirement.
28. Further, MISO requests that the
Commission clarify, or direct NERC to
clarify, the language in section II of
Attachment 1 that requires planning
coordinators and transmission planners
to provide stakeholders all assessments
of ‘‘potential overlapping uses of
footnote 12 including overlaps with
adjacent Transmission Planners and
Planning Coordinators.’’ MISO believes
that this phrase suggests that there are
other ‘‘potential overlapping uses’’ that
are encompassed by the requirement.
MISO states it is not clear what these
other overlapping uses might be or how
they might be incorporated into the
planning process.
Commission Determination
29. We approve Reliability Standard,
TPL–001–4 with footnote 12 because it
satisfies the concerns raised in the
Supplemental NOPR. Footnote 12
provides a blend of specific quantitative
and qualitative parameters for the
permissible use of planned nonconsequential load loss to address bulk
electric system performance issues,
including firm limitations on the
maximum amount of load that an entity
may plan to shed, safeguards to ensure
against inconsistent results and arbitrary
determinations that allow for the
planned non-consequential load loss,
and a more specifically defined, open
and transparent, verifiable, and
enforceable stakeholder process. Use of
planned non-consequential load loss
should be rare and must be used
consistent with the process established
here.
30. We disagree with MISO that
Attachment 1 to footnote 12 adds an
additional layer of complexity and
administrative burden to compliance
without any attendant benefit.
Commenters have stated in prior
proceedings that a blend of quantitative
and qualitative parameters ‘‘should not
overly burden NERC or Regional Entity
resources as utilization of the planned
load shed exception is—and would be—
rarely utilized.’’ 31 Further, the
Commission directs NERC to report on
the use of footnote 12 including the use
and effectiveness of the local regulatory
review and NERC review. This report is
important because it will provide an
analysis of the use of footnote 12,
including but not limited to information
on the duration, frequency and
31 Order
E:\FR\FM\23OCR1.SGM
No. 762, 139 FERC ¶ 61,060 at P 55.
23OCR1
63042
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
magnitude of planned nonconsequential load loss, and typical
(and if significant, atypical) scenarios
where entities plan for nonconsequential load loss. Further, the
report will serve as a tool to evaluate the
usefulness and effectiveness of local
regulatory and ERO review, and identify
whether MISO’s concern or other issues
arise that need to be addressed.
31. We decline to direct NERC to limit
the meaning of the phrase ‘‘applicable
regulatory authorities or governing
bodies.’’ Because each state and locality
has different entities that are
responsible for reliability of retail
electric service, we are reluctant to
further define who may participate.
NERC’s report should identify any
issues with respect to how effective and
efficient the review process is working.
With regard to MISO’s request that
input by the affected regulatory body is
sufficient to satisfy the language in the
Attachment 1 stakeholder process
indicating that the agency ‘‘does not
object’’ to the inclusion of nonconsequential load loss, we note that
during the standard development
process NERC ‘‘modified the footnote to
require regulatory authority review
rather than approval.’’ 32 Use of an open
stakeholder process that allows for
robust input and review will ensure that
all interested state agencies will have a
say in the process, and that any
objections of such agencies to the
inclusion of non-consequential load loss
will be considered in the relevant
planning decisions. With regard to
MISO’s requested clarification of the
phrase ‘‘potential overlapping uses,’’ we
note that Attachment 1 section II
encompasses potential overlapping uses
of footnote 12 either within the
responsible entity or with adjacent
transmission planners and planning
coordinators.33 Accordingly, no further
clarification is required.
tkelley on DSK3SPTVN1PROD with RULES
B. Reliability Issues Raised in the April
2012 NOPR
32. In the April 2012 NOPR, the
Commission sought comments regarding
the following issues regarding the
proposed Version 2 Reliability
Standard: (1) Planned maintenance
outages, (2) violation risk factors, (3)
protection system failures versus relay
failures, (4) assessment of backup or
redundant protection systems, (5) single
32 NERC’s
Petition, Exhibit H, Consideration of
Comments, period from July 31, 2012 through
August 29, 2012 at 73.
33 Proposed TPL–001–4 Reliability Standard,
Attachment 1, section II, category 8: ‘‘Assessment
of potential overlapping uses of footnote 12
including overlaps with adjacent Transmission
Planners and Planning Coordinators.’’
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
line to ground faults and (6) Order No.
693 directives. The Version 4 TPL
standard that we approve in this Final
Rule contains the same provisions as the
Version 2 standard, with the exception
of footnote 12, Attachment 1 and the
VRF for Requirement R6. Accordingly,
we address below the issues raised in
the April 2012 NOPR.
1. Planned Maintenance Outages NERC
Petition
33. NERC proposed new language in
TPL–001–2, Requirement R1 to remove
an ambiguity in the current standard
concerning what the planner needs to
include in the specific studies.
Requirement R1 also requires the
planner to evaluate six-month or longer
duration planned outages within its
system. NERC states that, while
Requirement R1.3.12 of the currentlyeffective TPL–002–0b includes planned
outages (including maintenance
outages) in the planning studies and
requires simulations at the demands
levels for which the planned outages are
performed, it is not appropriate to have
the planner select specific planned
outages for inclusion in their studies.34
Consequently, NERC proposes a brightline test to determine whether a planned
outage should be included in the system
models.
NOPR
34. In the April 2012 NOPR, the
Commission expressed concern that,
under proposed Requirement R1,
planned maintenance outages with a
duration of less than six months would
be excluded from future planning
assessments. As a result, any potential
impact to bulk electric system reliability
from these outages would be
unknown.35 The Commission sought
comment on whether the proposed six
month threshold would materially
change the number of planned outages
included in planning assessments
compared to the number included in
planning assessments under the
currently-effective standard, and
whether the threshold would exclude
nuclear plant refueling, large fossil and
hydro generating station maintenance,
and spring and fall transmission
construction projects from future
planning assessments. The Commission
also sought comment on possible
alternatives.
35. In the NOPR, the Commission
noted that, with respect to protection
system maintenance, currently-effective
Reliability Standard TPL–002–0,
Requirement R1.3.12 requires the
34 NERC’s
35 April
PO 00000
October 2011 Petition at 35.
2012 NOPR, 139 FERC ¶ 61,059 at P 18.
Frm 00084
Fmt 4700
Sfmt 4700
planner to ‘‘[i]nclude the planned
(including maintenance) outage of any
bulk electric equipment (including
protection systems or their components)
at those demand levels for which
planned (including maintenance)
outages are performed.’’ 36 NERC
explained in the petition that this
language did not carry over because
protection system maintenance or other
outages are not anticipated to last six
months. The Commission indicated in
the NOPR that it is critical to plan the
system so that a protection system can
be removed for maintenance and still be
operated reliably and sought comment
on whether protection systems are
necessary to be included as a type of
planned outage.
Comments
36. NERC and EEI state that the
proposed Reliability Standard will not
materially change the number of
planned outages that must be reflected
in initial system conditions as compared
to the existing standards. NERC states
that applying existing Requirement
R1.3.12, planners have traditionally
only included those planned outages in
their category ‘‘P0 or N–0’’ system
condition that resulted from
catastrophic equipment failures or
extended outage conditions associated
with construction or maintenance
projects that place their system in an
abnormal starting condition.37 NERC
believes that going beyond those
scenarios would consider ‘‘hypothetical
planned outages,’’ and doing so in a
planning study horizon would
introduce multiple contingency
conditions within the existing standard.
Further, NERC states that planners will
establish sensitivity cases around key
generation unit outages, and when
applying the category P3 planning event
to those sensitivity cases, it will further
cover multiple generator unit outages.
Similarly, transmission maintenance
outages are covered in the planning
events when applying the category P6
planning events.
37. BPA believes the six-month
planned outage window is workable but
that it may be too short to consider in
system planning models and suggests a
one-year planned outage window. BPA
states that planned outages with
duration of less than one year should be
36 Reliability Standard TPL–002–0, Requirement
R1.3.12.
37 Table 1 of the TPL Reliability Standard
contains a series of planning events and describes
system performance requirements and lists seven
categories of contingency planning events,
identified as P0 through P6. P0 is the ‘‘No
Contingency,’’ normal system condition. Reliability
Standard TPL–001–4, Table 1.
E:\FR\FM\23OCR1.SGM
23OCR1
tkelley on DSK3SPTVN1PROD with RULES
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
dealt with operationally by determining
new operating limits and taking other
actions to mitigate the planned outage.
According to Hydro One, it is not
necessary to include planned outage of
less than six months since long-term
planning is intended to assess
transmission expansion needs in the
usual three to ten year timeframe. Hydro
One states that the inclusion of planned
outages of less than six months will not
increase the accuracy of the results as
these are moving targets and there are
operational planning measures to
provide the required transmission
transfer capability to meet forecast
demand.
38. On the other hand, ITC
Companies, MISO and ATCLLC express
concern that some planned outages of
less than six months are relevant and
should not be eliminated from
consideration in planning evaluations.
ATCLLC states that, although the
number of planned outages may not
materially change, the impact of
eliminating pertinent planned outages
of less than six months in duration is
perhaps more material than the impact
of outages six months in duration or
longer. Some planned outages of less
than six months in duration may also
result in relevant impacts during one or
both of the seasonal off-peak periods.
ITC Companies state that, in some
instances, certain transmission elements
may be so critical that when taken out
of service for system maintenance or to
facilitate a new capital project, a
subsequent single unplanned
transmission outage could result in the
loss of firm system load. ITC Companies
adds that including only known
maintenance outages of six months or
longer in the transmission models could
be a step backwards from the current
standard. Since these unplanned
outages can have consequential impacts
on transmission customers, prudent
transmission planning should include
providing an adequate transmission
system to avoid these undesired
outcomes.
39. MISO suggests that limiting
planning studies to only include known
outages of generation or transmission
with duration of at least six months may
have a detrimental impact to bulk
electric system reliability. According to
MISO, proper transmission system
planning should ensure that the removal
of a facility for maintenance purposes
can be accomplished without the need
to deny or re-schedule such
maintenance to prevent the loss of firm
load resulting from the types of
contingencies enumerated in the TPL
Reliability Standards. MISO requests
that the Commission direct NERC to
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
further expand the base planning
conditions and assumptions by
requiring inclusion of unscheduled,
planned outages of any element when
applying at a minimum P0 and P1
events to the off-peak cases.
Commission Determination
40. Pursuant to section 215(d)(5) of
the FPA, we direct NERC to modify
Reliability Standard TPL–001–4 to
address the concern that the six month
threshold could exclude planned
maintenance outages of significant
facilities from future planning
assessments.
41. For the reasons discussed below,
the Commission finds that planned
maintenance outages of less than six
months in duration may result in
relevant impacts during one or both of
the seasonal off-peak periods. Prudent
transmission planning should consider
maintenance outages at those load levels
when planned outages are performed to
allow for a single element to be taken
out of service for maintenance without
compromising the ability of the system
to meet demand without loss of load.38
We agree with commenters such as
MISO and ATCLLC that certain
elements may be so critical that, when
taken out of service for system
maintenance or to facilitate a new
capital project, a subsequent unplanned
outage initiated by a single-event could
result in the loss of non-consequential
load or may have a detrimental impact
to the bulk electric system reliability. A
properly planned transmission system
should ensure the known, planned
removal of facilities (i.e., generation,
transmission or protection system
facilities) for maintenance purposes
without the loss of non-consequential
load or detrimental impacts to system
reliability such as cascading, voltage
instability or uncontrolled islanding.
42. We remain concerned that
proposed Reliability Standard TPL–
001–4 will materially change the
number of planned outages that must be
reflected in initial system conditions as
compared to the existing standards.
Planned outages lasting less than six
months are common, and yet could be
overlooked for planning purposes under
the proposal. These planned outages are
not ‘‘hypothetical planned outages,’’
and should not be treated as multiple
contingency conditions within the
planning standard. The Commission’s
directive is to include known generator
and transmission planned maintenance
outages in planning assessments, not
hypothetical planned outages.
38 ITC
PO 00000
Companies Comments at 5.
Frm 00085
Fmt 4700
Sfmt 4700
63043
43. While NERC has flexibility on
how to address the identified concern,
we believe that acceptable approaches
include eliminating the six-month
threshold altogether; decreasing the
threshold to fewer months to include
additional significant planned outages;
or including parameters on what
constitutes a significant planned outage
based, for example, on MW or facility
ratings.
44. Further, we disagree with NERC’s
position that category P3 contingencies
cover generator maintenance outages
and category P6 covers transmission
maintenance outages. P3 and P6 both
consist of multiple contingencies, e.g.,
loss of a generating unit or transmission
circuit followed by system adjustments
and then the loss of another generator or
transmission circuit. In approving
NERC’s interpretation of Requirement
R1.3.12 of TPL–002–0 and TPL–003–0,
the Commission stated that ‘‘planned
(including maintenance) outages are not
contingencies and are required to be
addressed in transmission planning for
any bulk electric equipment at demand
levels for which the planned outages are
performed.’’ 39 The Commission further
stated that it ‘‘understands that planned
maintenance outages tend to be for a
relatively short duration and are
routinely planned at a time that
provides favorable system conditions,
i.e., off-peak conditions. Given that all
transmission and generation facilities
require maintenance at some point
during their service lives, these
‘potential’ planned outages must be
addressed, so long as their planned start
times and durations may be anticipated
as occurring for some period of time
during the planning time [horizon]’’
required in the TPL Reliability
Standards.40
45. With regard to BPA’s comment,
we disagree that planned outages of less
than one year in duration should be
addressed operationally by determining
new operating limits and taking other
actions to mitigate the planned outage.
The Commission understands that some
planned outages such as planned
generation outages are known more than
one year in advance.41 As a result, the
Commission believes the planning time
horizon of the TPL Reliability Standards
offers more flexibility to assess planned
maintenance outages than the
39 North American Electric Reliability Corp., 131
FERC ¶ 61,068, at P 39 (2010) (approving
interpretation of Reliability Standards TPL–002–0
and TPL–003–0).
40 Id. P 39.
41 See, e.g., Commissioner-Led Reliability
Technical Conference, Docket Nos. AD13–6–000,
RC11–6–004, RR13–2–000, July 9, 2013, Volume I
at 242.
E:\FR\FM\23OCR1.SGM
23OCR1
63044
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
operational time horizon. Further, we
disagree with Hydro One’s comment
that including planned outages of less
than six months is unnecessary since
long-term planning to assess
transmission expansion occurs in the
three to ten year timeframe. The
Commission recognizes that the TPL–
001–4 Reliability Standard addresses
near-term and long-term transmission
planning horizons and, for the near-term
horizon, requires annual assessments for
years one through five. Accordingly,
known planned facility outages (i.e.
generation, transmission or protection
system facilities) of less than six months
should be addressed so long as their
planned start times and durations may
be anticipated as occurring for some
period of time during the planning time
horizon.
2. Violation Risk Factors
a. Requirement R1
NERC Petition
46. NERC assigned a ‘‘medium’’
violation risk factor (VRF) for proposed
Requirement R1. NERC maintains that
Requirements R1.3.5, R1.3.7, R1.3.8, and
R1.3.9 of the currently-effective
Reliability Standard carry a VRF of
‘‘medium’’ and are similar in purpose
and effect to proposed Reliability
Standard, Requirement R1 because they
refer to planning models that include
firm transfers, existing and planned
facilities, and reactive power
requirements.42
tkelley on DSK3SPTVN1PROD with RULES
NOPR Proposal
47. In the April 2012 NOPR, the
Commission expressed that, if system
models are not properly modeled or
maintained, the analysis required in the
Reliability Standard that uses the
models in Requirement R1 may lose
their validity and could directly cause
or contribute to Bulk-Power System
instability, separation, or a cascading
sequence of failures, or could place the
Bulk-Power System at an unacceptable
risk of instability, separation, or
cascading, or hinder restoration to a
normal condition.43 The Commission
noted that Requirement R1 of the
Version 0 TPL Standard, which is
assigned a ‘‘high’’ VRF, explicitly
establishes Category A as the normal
system in Table 1, which also creates
the model of the normal system prior to
any contingency and stated its belief
that Requirement R1 of the proposed
Reliability Standard and Requirement 1
of currently-effective standard both
42 NERC October 2011 Petition at Exhibit C,
Table 1.
43 April 2012 NOPR, 139 FERC ¶ 61,059 at P 21.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
establish the normal system planning
model that serves as the foundation for
all other conditions and contingencies
that are required to be studied and
evaluated in a planning assessment. In
the NOPR, the Commission sought
comment on why Requirement R1 of
proposed Reliability Standard carries a
VRF of ‘‘medium’’ while Requirement
R1 of the currently-effective standard
carries a VRF of ‘‘high.’’
Comments
48. NERC states that Requirement R1
of the currently-effective standard
directly relates to Requirement R2 of the
proposed standard, which has a High
VRF. NERC states that Requirement R1
of the proposed standard is a new
requirement that addresses the models
needed for planning assessments and
therefore can have a different VRF.
NERC states that while the accuracy of
the transmission system model plays a
key role in the TPL Reliability
Standards, it is ‘‘a model, an
approximation constructed and built
with multiple entity inputs within a
controlled process (e.g., Multiregional
Model Working Group).’’ 44 NERC states
the base model in proposed
Requirement R1 must be modified by
adjusting load forecasts and generation
dispatch to better assess the range of
probable outcomes that the transmission
system may experience for various
contingency scenarios.
49. ISO/RTOs state that proposed
Requirement R1 relates to model
maintenance, a necessary condition to
being able to perform an assessment,
which is a different matter from the
current Requirement R1. According to
ISO/RTOs Requirement R1 of the
currently-effective standard, relating to
performing an assessment, corresponds
to Requirement R2 of the proposed
standard, both of which carry a VRF of
‘‘high.’’
50. EEI does not believe that proposed
Requirement R1 aligns with
Requirement R1 of the currentlyeffective standard. According to EEI,
however, Requirement R1 does obligate
‘‘Transmission Planners and Planning
Coordinators to maintain system models
within their respective area for
performing studies needed to complete
its Planning Assessments.’’ 45 EEI
further notes that these studies establish
a baseline (Category P0) by which all
other studies are based. EEI advocates
that, if this requirement is not adhered
to, faulty studies could result, possibly
leading to misoperation of the system.
For this reason, EEI believes the VRF
44 NERC
45 EEI
PO 00000
Comments at 8.
Comments at 5.
Frm 00086
Fmt 4700
was improperly categorized as a
medium risk VRF and suggests
consideration be given to increasing the
VRF to ‘‘high.’’
Commission Determination
51. We direct NERC to modify
Reliability Standard TPL–001–4,
Requirement R1 and change its VRF
from medium to high. As discussed in
the April 2012 NOPR, Requirement R1
establishes the normal system planning
model that serves as the foundation for
all other conditions and contingencies
that are required to be studied and
evaluated in a planning assessment. The
Commission agrees with EEI that if the
baseline studies established in
Requirement R1 are not adhered to,
faulty studies could result, possibly
leading to misoperation of the system.
52. The Commission is not persuaded
by NERC’s argument that Reliability
Standard TPL–001–4, Requirement R1
warrants a medium VRF because the
base model in Requirement R1 must be
modified by adjusting load forecasts and
generation dispatch for various
contingency scenarios. Rather, the
Commission finds that Requirement R1
and its sub-parts require system models
to represent projected system conditions
including items such as resources
required for load, and real and reactive
load forecasts, all of which ‘‘establishes
Category P0 as the normal condition in
Table 1.’’ 46 Although the Commission
agrees with NERC that the accuracy of
the system model plays a key role in the
TPL Reliability Standards and that a
system model is ‘‘a model, an
approximation constructed and built
with multiple entity inputs within a
controlled process,’’ the Commission
finds that the system model of
Requirement R1 establishes a baseline
(Category P0) for which all other studies
are based and if not adhered to, faulty
studies could result, possibly leading to
misoperation of the system.
53. Further, the Commission disagrees
with ISO/RTOs that proposed
Requirement R1 is a different matter
from the current Requirement R1. The
Commission stated in the April 2012
NOPR that Requirement R1 of the
Version 0 TPL Standard, which is
assigned a ‘‘high’’ VRF, explicitly
establishes Category A as the normal
system in Table 1 that serves as the
foundation for all other conditions and
contingencies that are required to be
studied and evaluated in a planning
assessment. Accordingly, the
Commission believes that TPL–001–4,
Requirement R1 similarly establishes
46 NERC’s February 2013 Petition, Exhibit A,
TPL–001–4, Requirement R1.
Sfmt 4700
E:\FR\FM\23OCR1.SGM
23OCR1
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
Category P0 as the normal system in
Table 1 that serves as the foundation for
all other conditions and contingencies
that are required to be studied and
evaluated in a planning assessment. For
these reasons, the Commission directs
NERC to modify the VRF assigned to
Requirement R1 from medium to high.
b. VRF for Requirement R6
NERC Petition
54. NERC proposed to assign a ‘‘low’’
VRF for Requirement R6 47 because
‘‘failure to have established criteria for
determining System instability is an
administrative requirement affecting a
planning time frame.’’ 48 NERC explains
that Requirement R6 is a new
requirement and that violations would
not be expected to adversely affect the
electrical state or capability of the bulk
electric system.
NOPR Proposal
55. In the NOPR, the Commission
recognized that documenting criteria or
methodology is an administrative act
but stated that defining the criteria or
methodology to be used is not an
administrative act. The Commission
sought clarification why the VRF level
assigned to Requirement R6 is ‘‘low’’
since it appears that Requirement R6
requires more than a purely
administrative task.
Comments
56. NERC agrees that proposed TPL–
001–2 Requirement R6 is not strictly an
administrative task, and therefore the
VRF should be adjusted to medium. In
its February 28, 2013 Petition, NERC
revised the VRF for Reliability Standard
TPL–001–4, Requirement R6 from low
to medium.
57. EEI and ISO/RTOs contend that
Requirement R6 was correctly assigned
a ‘‘low’’ VRF because ‘‘defining and
documenting’’ is an administrative task.
According to EEI, the fact that the
planner poorly documented the criteria
and methodology does not mean that
their assessment was not conducted
appropriately or that it placed the bulk
electric system at risk.
Commission Determination
tkelley on DSK3SPTVN1PROD with RULES
58. The Commission agrees with
NERC that TPL–001–4, Requirement R6
47 NERC’s February 2013 Petition, Exhibit A,
TPL–001–4, Requirement R6 states ‘‘[e]ach
Transmission Planner and Planning Coordinator
shall define and document, within their Planning
Assessment, the criteria or methodology used in the
analysis to identify System instability for
conditions such as Cascading, voltage instability, or
uncontrolled islanding.’’
48 NERC’s October 2011 Petition, Exhibit C, at
110.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
is not strictly an administrative task and
approves the change from a low VRF to
a medium VRF. The Commission
disagrees with commenters that TPL–
001–4 Reliability Standard,
Requirement R6 is purely an
administrative task of documentation of
criteria and methodologies.
Requirement R6 goes beyond
documentation by requiring planners to
apply engineering judgment and
analysis to ‘‘define…the criteria or
methodology used in the analysis to
identify system instability for
conditions such as cascading, voltage
instability or uncontrolled islanding.’’ 49
3. Protection System Failures versus
Relay Failures
NERC Petition
59. NERC’s proposal includes
modifications to the planning
contingency categories in Table 1. NERC
explains that the modifications are
intended to add clarity and consistency
regarding the modeling of a delayed
fault clearing in a planning study. NERC
stated that the basic elements of any
protection system design involve inputs
to protective relays and outputs from
protective relays and that reliability
issues associated with improper clearing
of a fault on the bulk electric system can
result from the failure of hundreds of
individual protection system
components in a substation. According
to NERC, while the population of
components that could fail and result in
improper clearing is large, the
population can be reduced dramatically
by eliminating those components which
share failure modes with other
components. NERC stated that the
critical components in protection
systems are the protective relays
themselves, and a failure of a nonredundant protective relay will often
result in undesired consequences during
a fault. According to NERC, other
protection system components related to
the protective relay could fail and lead
to a bulk electric system issue, but the
event that would be studied is identical,
from both transient and steady state
perspectives, to the event resulting from
a protective relay failure if an adequate
population of protective relays is
considered.50
NOPR Proposal
60. In the April 2012 NOPR, the
Commission expressed that, based on
various protection system designs, the
planner will have to choose which
protection system component failure
49 Proposed TPL–001–4 Reliability Standard,
Requirement R6.
50 NERC’s October 2011 Petition at 48.
PO 00000
Frm 00087
Fmt 4700
Sfmt 4700
63045
would have the most significant impact
on the Bulk-Power System because asbuilt designs are not standardized and
the most critical component failure may
not always be the relay.51 The
Commission sought comment on
whether the proposed provisions
pertaining to study of multiple
contingencies limits the planners’
assessment of a protection system
failure because the proposed provisions
only include the contingency of a faulty
relay component. The Commission also
sought comment on whether the relay is
always the larger contingency and how
the loss of protection system
components that is integral to multiple
protection systems impacts reliability.
Comments
61. NERC states that the proposed
Reliability Standard addresses the
existing ambiguity requiring a study of
a stuck breaker or protection system
failure by specifying that both a stuck
breaker and protection system failure
must be evaluated. NERC states that its
solution ensures that simulations of
both categories are performed, reducing
the probability of multiple contingency
events leading to cascading and
uncontrolled islanding. Similarly,
Hydro One and EEI contend that a
planner does not need to choose which
protection system component failure
would have the most significant impact
on the Bulk-Power System in the
planning assessment. According to
Hydro One, the contingencies stipulated
in Table 1, P5 of the proposed TPL
Standard are appropriate for the
conditions and events to be assessed in
the P5 groups which focus on the
combination of a single line to ground
fault coupled with delayed clearing that
may be caused by a protection system
failing to open to clear the fault. Hydro
One also states that what causes the
protection system to fail is irrelevant in
the context of delayed clearing by the
backup protection system to clear the
fault. EEI expresses concern that
expanding planning studies to include
all manner of protection system failures
could create a scenario where planners
would have to conduct unlimited and
unbounded studies.’;
62. In contrast, MISO agrees with the
NOPR that the more severe or larger
contingency may not be assessed
because the proposed Reliability
Standard limits the planners’
assessment of a protection system
failure since it only includes the
contingency of a faulty relay
component. MISO suggests expanding
the assessment of relay failures to
51 April
E:\FR\FM\23OCR1.SGM
2012 NOPR, 139 FERC ¶ 61,059 at P 31.
23OCR1
tkelley on DSK3SPTVN1PROD with RULES
63046
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
include all components of a protection
system, including instrument
transformers, protective relays, auxiliary
relays and communications systems.
63. With regard to the Commission’s
question whether, based on protection
system as-built designs, the relay may
not always be the larger contingency,
NERC states that the proposed Table 1,
category P5 (fault plus relay failure to
operate) planning event requires
evaluation of the failure of the
protection system relays whose failure
is most likely to cause cascading or
uncontrolled islanding of the bulk
electric system.
64. Hydro One recognizes that a
number of components necessary to
operate properly may fail to render a
protection system failing to operate
when needed, and that such component
failures may result in disabling more
than one protective relay and the impact
of multiple relay failures may be more
severe than the SLG fault on a bulk
electric system facility with delayed
clearing. According to Hydro One, the
more severe consequences of an initial
bulk electric system facility contingency
combined with multiple or more severe
protection system failures would more
appropriately be considered or included
in the extreme events category.
65. ISO/RTOs agree that the range of
potential assessments should be
expanded to include all components of
a protection system including
instrument transformers, protective
relays, auxiliary relays and
communications systems for the
purpose of category P–5 contingencies,
but because these devices are often in
series, consideration of all of these
components will not necessarily have
any significant impact on analyses.
66. With regard to the question of how
does the loss of a protection system
component integral to multiple
protection systems impact reliability,
NERC states that the loss of a relay that
is integral to multiple protection
systems would require simulation of the
full impact of that relay’s failure on the
system for the event being studied
under the category P5 planning event.
With respect to whether there is a
reliability concern regarding single
points of failure on protection systems,
NERC indicates that it has a project
underway to assess that question.52
67. Hydro One views the avoidance of
having single component failure
affecting more than one protection
system as a protection system design
issue. Hydro One states that some
regional reliability organizations have in
place criteria to ensure protection
52 NERC
Comments at 10.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
systems operate properly and to avoid
failure of a single component affecting
multiple protection systems.
Commission Determination
68. The Commission agrees with
NERC’s statement that Reliability
Standard-TPL–001–4 addresses the
existing ambiguity of the currentlyeffective TPL Reliability Standards
requiring a study of a stuck breaker or
protection system failure. We find that
Reliability Standard TPL–001–4,
specifying that both a stuck breaker and
a relay failure must be evaluated, is
reasonable to remove the ambiguity.
Further, as explained by NERC, the loss
of a relay that is integral to multiple
protection systems would require
simulation of the full impact of that
relay’s failure on the system for the
event being studied under the category
P5 planning event. In addition,
Reliability Standard TPL–001–4
requires study and evaluation of both a
stuck breaker (Table 1, Category P4) and
a relay failure (Table 1, Category P5) and
that simulations of both categories
reduce the probability of multiple
contingency events leading to
cascading, instability or uncontrolled
islanding.
69. The Commission does not find the
need to take any further action with
regard to this issue. We note, however,
that an assessment of a relay component
failure may not necessarily assess the
more severe or larger contingency,
compared to a protection system failure
under the currently-effective TPL
Standards. Based on various protection
system as-built designs, NERC has
indicated that the planner should use
‘‘engineering judgment in its selection
of the protection system component
failures for evaluation that would
produce the more severe system results
or impact. . . . The evaluation would
include addressing all protection
systems affected by the selected
component. A protection system
component failure that impacts one or
more protection systems and increases
the total fault clearing time requires the
[planner] to simulate the full impact
(clearing time and facilities removed) on
the Bulk Electric System
performance.’’ 53 However, the
Commission will not direct NERC to
modify the standard at this time,
pending completion of NERC’s work on
53 NERC Petition For The Approval of An
Interpretation to Reliability Standards TPL–003–0a
and TPL–004–0, April 12, 2013 at 13, Docket No.
RD13–8–000, approved by unpublished letter order
June 20, 3013.
PO 00000
Frm 00088
Fmt 4700
Sfmt 4700
single points of failure on protection
systems.54
4. Assessment of Backup or Redundant
Protection Systems NOPR Proposal
70. Requirement R3, Part 3.3.1 and
Requirement R4, Part 4.3.1 of Reliability
Standard TPL–001–4 require that
simulations duplicate what will happen
in an actual power system based on the
expected performance of the protection
systems.55 According to NERC, these
requirements ensure that, for a
protection system designed ‘‘to remove
multiple Elements from service for an
event that the simulation will be run
with all of those Elements removed from
service.’’ 56 In the NOPR, the
Commission observed that these
provisions do not explicitly refer to
‘‘backup or redundant systems’’ as in
the currently-effective Reliability
Standards and sought clarification
whether the proposal includes backup
and redundant protection systems.
Comments
71. NERC clarifies that proposed
Requirement R3, Part 3.3.1 and
Requirement R4, Part 4.3.1 ‘‘require the
consideration of all protection systems
that are relevant to the contingency
studied,’’ which includes ‘‘backup and
redundant systems.’’ 57 EEI believes that
the language is sufficiently clear to
ensure a common understanding that
backup and redundant protection
system impacts needed to be studied
regardless of whether the specific words
as found in the currently active standard
were used. ISO/RTOs and MISO believe
that if a protection system is not fully
redundant, contingencies should be
studied to simulate both delayed
clearing and operation of remote backup
protection to trip additional facilities
when required. MISO states that if a
protection system is fully redundant,
that is, if a single failure of any
component in the protection system
(other than monitored DC voltage)
would not result in delayed or failed
tripping it should not be necessary to
analyze the redundant protection
system failure.
Commission Determination
72. The Commission agrees with
NERC and finds that Requirement R3,
Part 3.3.1 and Requirement R4, Part
4.3.1 include the assessments of backup
protection systems. The Commission
54 March 15, 2012 NERC Informational Filing in
Docket No. RM10–6–000 at 5, 7, stating that NERC
has initiated a data request to evaluate potential
exposure to types of protection system failures.
55 NERC’s October 2011 Petition at 20.
56 Id.
57 NERC Comments at 11.
E:\FR\FM\23OCR1.SGM
23OCR1
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
73. In the April 2012 NOPR, the
Commission sought clarification
whether ‘‘fault types’’ in Table 1 refers
to the initiating event.58
load models and proxies to simulate
cascade.59
77. The Commission is satisfied and
agrees with the comments submitted by
NERC, EEI and ISO/RTO on issues
regarding controlled load interruption
(i.e., third parties must have the same
non-consequential load loss options as
available to the planner), dynamic load
models (i.e., documentation of dynamic
load models used in system studies and
the supporting rationale for their use is
required) and proxies to simulate
cascade (i.e., planners must define and
document their criteria or methodology
including proxies that are used in
planning assessments due to modeling
and simulation limitations). Below, we
address in greater detail the comments
on peer review of planning assessments,
spare equipment strategy, range of
extreme events, and footnote ‘a.’
Comments
a. Peer Review of Planning Assessments
74. NERC, EEI, BPA and ISO/RTOs all
concur that ‘‘fault types’’ refer to the
initiating fault to be studied, not to what
the fault may evolve into as a result of
the simulated conditions. According to
NERC, the possibility of a single-line-toground fault evolving into a three-phase
fault is addressed by requiring the study
of a three-phase fault as the initial fault.
NOPR Proposal
78. The Commission stated in Order
No. 693 that, because neighboring
systems may adversely impact one
another, such systems should be
involved in determining and reviewing
system conditions and contingencies to
be assessed under the currently-effective
TPL Reliability Standards.60 In its
petition, NERC stated the proposed
Reliability Standard does not include a
‘‘peer review’’ of planning assessments
but instead includes an equally effective
and efficient manner to provide for the
appropriate sharing of information with
neighboring systems in proposed
Requirement R3, Part 3.4.1,
Requirement R4, Part 4.4.1, and
Requirement R8.61
79. In the April 2012 NOPR, the
Commission sought clarification on how
the NERC proposal ensures the early
input of peers into the planning
assessments or any type of coordination
among peers will occur. The
Commission also sought comment on
whether and how neighboring systems
can sufficiently evaluate and provide
feedback to the planners on the
development and result of assessments
and whether it requires input on the
comments to be included in the results
or the development of the planning
assessments.
agrees with ISOs/RTOs and MISO that
if a primary protection system has a
fully redundant backup protection
system, assessments of the primary
protection system is required, but not of
the fully redundant backup protection
system since the assessment results will
be identical. Further, we agree that if a
protection system is not fully
redundant, contingencies are studied to
simulate both delayed clearing and
operation of remote backup protection
which may trip additional facilities
when required.
P5 Single Line to Ground Faults
NOPR Proposal
Commission Determination’
75. The Commission finds that the
explanation of NERC and others, i.e.,
‘‘fault types’’ in Reliability Standard
TPL–001–4, Table 1—Steady State &
Stability Performance Planning Events
means the type of fault that initiated the
event, is reasonable. For example, if the
initiating fault type is a single-line-toground fault and it evolves into a threephase fault, the single-line-to-ground
fault is still evaluated as the initiating
fault type. If a three-phase fault occurs
as the initiating event, the fault is
assessed as a three phase fault.
Regardless of what the initiating fault
type becomes, it does not change the
initiating fault type.
tkelley on DSK3SPTVN1PROD with RULES
6. Order No. 693 Directives
76. In the April 2012 NOPR, the
Commission indicated that the Version
4 TPL Standard appeared responsive to
the Order No. 693 directives regarding
the TPL Reliability Standards. However,
the Commission sought clarification and
comment on the following issues: (a)
Peer review of planning assessments, (b)
spare equipment strategy, (c) range of
extreme events, (d) footnote ‘a’ and (e)
controlled load interruption, dynamic
58 April
2012 NOPR, 139 FERC ¶ 61,059 at P 38.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
Comments
80. NERC and EEI state that, prior to
sharing planning assessment results in
Requirement R8, Requirement R3, Part
59 April
2012 NOPR, 139 FERC ¶ 61,059 at PP 39–
54.
60 Order No. 693, FERC Stats. & Regs. ¶ 31,242 at
P 1750.
61 NERC’s October 2011 Petition at 21.
PO 00000
Frm 00089
Fmt 4700
Sfmt 4700
63047
3.4.1 and Requirement R4, Part 4.4.1
require planners to coordinate with
adjacent planners to develop
contingency lists for steady state and
stability analysis. EEI states it is most
beneficial to planners if coordination
occurs earlier in the planning
assessment process.
81. NERC and EEI also explain that
Requirements R2 through R6 provide
adjacent entities sufficient information
on how the assessment was performed
and expected system performance to
effectively evaluate the assessment
results and to provide feedback. Further,
Requirement R8 requires that each
planner must distribute its planning
assessment results to adjacent planners
within 90 calendar days of completing
its assessment.
82. 1BPA states that, while adjacent
planners and coordinators should have
a stake in the results of an affected
planning assessment, they should not be
allowed to second guess the
transmission planner’s or planning
coordinator’s studies and
methodologies. BPA adds that it is
important for adjacent planners to have
input on how other planning
assessments will affect them, and the
proposed Reliability Standards allows
such input.
Commission Determination
83. The Commission agrees with
NERC and EEI that coordination of
contingency lists with adjacent planners
under TPL–001–4 Reliability Standard,
Requirement R3, Part 3.4.1 and
Requirement R4, Part 4.4.1 ensures that
contingencies on adjacent systems that
impact other systems are developed and
included in the planners’ steady state
and stability analysis planning
assessments.62 Coordination of
contingency lists provides one aspect of
early coordination among planners.
84. We are satisfied with the
explanation of NERC and EEI that TPL–
001–4 Reliability Standard,
Requirement R8 allows planners to
coordinate and distribute conditions to
adjacent planners as part of their
planning assessment and to provide
feedback to other planners. While we
also agree with BPA that adjacent
planners should be informed of and
have a stake in the results of another
planner’s assessment, we disagree with
BPA’s characterization that a planner
‘‘should not be allowed to second
guess’’ another planner’s studies or
62 Because neighboring systems may be adversely
impacted by other systems, such systems should be
involved early in determining and reviewing
conditions and contingencies in planning
assessments. Order No. 693, FERC Stats. & Regs. ¶
31,242 at PP 1750, 1754.
E:\FR\FM\23OCR1.SGM
23OCR1
63048
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
methodologies. Rather, early peer input
in the planning assessments and
coordination among peers to identify
possible interdependent or adverse
impacts on neighboring systems are
essential to the reliable operation of the
bulk electric system.63
Spare Equipment Strategy
NOPR Proposal
85. In Order No. 693, the Commission
directed NERC to develop a
modification ‘‘to require assessments of
outages of critical long lead-time
equipment, consistent with the entity’s
spare equipment strategy.’’ 64 In
response, NERC developed proposed
Requirement 2, Part 2.1.5 which
addresses steady state conditions to
determine system response when
equipment is unavailable for prolonged
periods of time.
86. In the NOPR, the Commission
raised the concern that the proposed
spare equipment strategy appears to be
limited to ‘‘steady state analysis’’ and
sought clarification why ‘‘stability
analysis’’ conditions are not mentioned.
Comments
87. NERC, ISOs/RTOs, and EEI
comment that the burden of additional
stability analyses would not provide
significant reliability benefits because
stability analysis already required under
‘‘category P6’’ will produce more
definitive tests of longer-term
equipment unavailability. They also
claim that any potential stability
impacts related to an entity’s spare
equipment strategy will be observed in
the normal planning process driven by
other requirements.
tkelley on DSK3SPTVN1PROD with RULES
Commission Determination
88. The Commission agrees that NERC
has met the spare equipment strategy
directive for steady state analysis under
Reliability Standard TPL–001–4,
Requirement R2, Part 2.1.5. However,
the Commission finds that a spare
equipment strategy for stability analysis
is not addressed under category P6.
89. The spare equipment strategy for
steady state analysis under Reliability
Standard TPL–001–4, Requirement R2,
Part 2.1.5 requires that steady state
studies be performed for the P0, P1 and
P2 categories identified in Table 1 with
the conditions that the system is
63 Order No. 693, FERC Stats. & Regs. ¶ 31,242 at
P 1754: ‘‘Given that neighboring systems
assessments by one entity may identify possible
interdependant or adverse impacts on its
neighboring systems, this peer review will provide
an early opportunity to provide input and
coordinate plans.’’
64 Order No. 693, FERC Stats. & Regs. ¶ 31,242 at
P 1786.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
expected to experience during the
possible unavailability of the long lead
time equipment. The Commission
believes that a similar spare equipment
strategy for stability analysis should
exist that requires studies to be
performed for P0, P1 and P2 categories
with the conditions that the system is
expected to experience during the
possible unavailability of the long lead
time equipment. Further, we are not
persuaded by the explanation of NERC
and others that a similar spare
equipment strategy for stability analysis
would cause unjustified burden because
stability analysis is already required
under category P6. The Commission
notes that the category P2 contingencies
studied under the spare equipment
strategy for steady state analysis are
different than the contingencies studied
under category P6. For example, under
the spare equipment strategy for steady
state, a planner would study a long leadtime piece of equipment out of service
(e.g., a transformer) along with a bus
section fault contingency (i.e., category
P2, event 2). The study of this same
condition for stability analysis under
category P6 is not addressed. However,
the Commission will not direct a change
and instead directs NERC to consider a
similar spare equipment strategy for
stability analysis upon the next review
cycle of Reliability Standard TPL–001–
4.
Comments
C. Range of Extreme Events
91. NERC asserts that it addressed the
Order No. 693 directive to expand the
range of events considered in the
planning assessment by adding a new
category ‘‘wide area events’’ as extreme
events. NERC contends that it is raising
the bar concerning extreme events by
requiring the planners to evaluate the
loss of two generating stations for a
wide range of external events that could
cause the loss of all generating units at
two generating stations. NERC adds that
extreme events in item 3b of Table 1
means that the planner will consider
even more extreme events (i.e., the loss
of more facilities than the loss of two
generating stations) based upon
operating experience and knowledge of
its system.
92. EEI agrees with the Commission
that there are conditions that provide far
more serious impacts to the grid than
that which is described in item 3a of
Table 1 of the proposed standard.
However, those conditions are largely
area specific thereby making it
impossible to describe or address all
possibilities in a Standard. EEI,
therefore, supports NERC’s approach
which obligates planners to consider, as
stated in Item 3b, ‘‘[o]ther events based
upon operating experience that may
result in wide area disturbances.’’ EEI
believes that Table 1, Item No. 3b
provides the necessary backstop to
ensure that extreme events are fully
captured from a planning standpoint.67
NOPR Proposal
Commission Determination
90. In Order No. 693, the Commission
directed NERC to modify the Version 0
Reliability Standard, TPL–004–0, to
require that, in determining the range of
the extreme events to be assessed, the
contingency list of category D would be
expanded to include recent events such
as hurricanes and ice storms.65 In the
April 2012 NOPR, the Commission
indicated that, while the proposed
Version 4 TPL Standard appropriately
expands the list of extreme event
examples in Table 1, the list limits these
items to the loss of two generating
stations under Item No. 3a. The
Commission sought clarification on
conditioning extreme events on the loss
of two generating stations.66 The
Commission also sought clarification
regarding whether the ‘‘two generation
stations’’ limitation would adequately
capture a scenario where an extreme
event can impact more than two
generation stations.
93. The Commission is satisfied with
the explanation of NERC and EEI that
Table 1, item No. 3b provides the
necessary backstop to ensure that
extreme events are fully captured from
a planning standpoint including
extreme events that can impact more
than two generating stations and that a
planner will consider even more
extreme events based on operating
experience and knowledge of its system.
65 Order No. 693, FERC Stats. & Regs. ¶ 31,242 at
P 1834.
66 April 2012 NOPR, 139 FERC ¶ 61,059 at P 48.
PO 00000
Frm 00090
Fmt 4700
Sfmt 4700
d. Footnote ‘a’
NOPR Proposal
94. In Order No. 693, the Commission
directed NERC to modify footnote ‘a’ of
Table 1 with regard to ‘‘applicability of
emergency ratings and consistency of
normal ratings and voltages with values
obtained from other reliability
standards.’’ 68 In its petition, NERC
noted that proposed Table 1, header
note ‘e,’ which provides that planned
system adjustments must be executable
67 EEI
Comments at 14–15.
No. 693, FERC Stats. & Regs. ¶ 31,242 at
68 Order
P 1770.
E:\FR\FM\23OCR1.SGM
23OCR1
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES
within the time duration applicable to
facility ratings. Further, according to
NERC, header note ‘f,’ which states
applicable facility ratings shall not be
exceeded, meets the Order No. 693
directive pertaining to footnote ‘a’ in the
current standard.
95. In the NOPR the Commission
observed that the proposed standard
applies header note ‘e’ to ‘‘Steady State
and Stability,’’ while header note ‘f’ is
excluded from ‘‘Stability’’ and only
applies to ‘‘Steady State’’ studies.
Accordingly, the Commission sought
clarification regarding the rationale for
excluding header note ‘f’ from
‘‘Stability’’ studies. In addition, for
Table 1, header notes ‘e’ and ‘f,’ the
Commission sought comment on
whether the normal facility ratings align
with Reliability Standard FAC–008–1
and normal voltage ratings align with
Reliability Standard VAR–001–1.
Furthermore, the Commission sought
clarification whether facility ratings
used in planning assessments align with
other reliability standards such as
Reliability Standards NUC–001–2, BAL–
001–0.1a and the PRC Reliability
Standards for UFLS and UVLS.
Comments
96. NERC states that it excluded
header note ‘f’ from stability studies
because facility ratings are defined for a
finite period which may be between a
few minutes and several hours, or
longer. According to NERC, in stability
studies the analysis is conducted over a
few seconds and because facility ratings
are established based on the overheating
of elements, the few seconds in the
stability timeframe is not significant to
the overheating of elements.69
97. ISO/RTO states that the
observation of facility trip ratings (i.e.,
relay trip ratings) are valid in the
stability simulation time frame, and
should be considered if associated
protective relay schemes are sensitive to
power swings (e.g., impedance relays
with no out-of step trip blocking for
stable swings, etc.). Further, ISO/RTO
believes that there is no reason to
include a requirement to observe
thermal facility ratings in stability
studies, but also believes that facility
trip ratings should be observed in
stability studies.
98. NERC and EEI also explain that
the values used for facility ratings
within transmission planning models
are developed in accordance with
standard FAC–008–1 ‘‘Facility Ratings
Methodology’’ and communicated to
other functional entities as required by
69 See also BPA Comments at 5, EEI Comments
at 15 and ISO/RTOs Comments at 11.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
FAC–009–1 ‘‘Establish and
Communicate Facility Ratings.’’
99. In response to the Commission’s
request for clarification whether facility
ratings used in planning assessments
align with other Reliability Standards,
commenters generally stated that facility
ratings used in the TPL standard are
consistent throughout the NERC
standards. Further, commenters stated
that Reliability Standard VAR–001–2 is
not a ratings standard but an operational
(real-time) standard to ensure voltage
levels, reactive flows and reactive
resources are monitored, controlled and
maintained within the limits of the
equipment.70
Commission Determination
100. The Commission is satisfied with
commenters’ explanation and agrees
that it is not necessary to include a
requirement to observe thermal facility
ratings in stability studies. The
Commission agrees with ISO/RTO that
facility trip ratings (i.e., relay trip
ratings) are valid ratings in the stability
simulation time frame, and should be
considered in the planning assessment
if associated protective relay schemes
are sensitive to power swings (e.g.,
impedance relays with no out-of step
trip blocking for stable swings). Further,
the Commission accepts the explanation
of NERC and others that facility ratings
used in planning assessments are
determined in accordance with
Reliability Standard FAC–008–3,71
which states that a ‘‘Facility Rating shall
respect the most limiting applicable
Equipment Rating of the individual
equipment that comprises that Facility.’’
C. Other Matters Raised by Commenters
101. Powerex states that additional
clarification is needed with respect to
Footnote 9 to Table 1 in order to provide
clarity and ensure consistent
interpretation as to when transmission
planners may plan to curtail firm
transmission service. Powerex is
concerned that the revised TPL
Standard may provide transmission
planners with broad discretion to plan
for the curtailment of firm transmission
service without providing purchaseselling entities with the notice and
certainty they need to make appropriate
alternate arrangements. Powerex
believes that the phrase in footnote 9
‘‘resources obligated to re-dispatch’’
should be clarified as referring to a
70 See NERC Comments at 16 and EEI Comments
at 15.
71 In ‘‘Order Approving Reliability Standard’’
issued November 17, 2011 (Docket No. RD11–10–
000), the Commission approved FAC–008–3
Reliability Standard and the retirement of FAC–
008–1 and FAC–009–1 Reliability Standards.
PO 00000
Frm 00091
Fmt 4700
Sfmt 4700
63049
formal agreement between the
transmission provider and a generation
owner, located on the load side of a
transmission constraint, to resupply the
load that had been receiving energy
from a remote source before the firm
transmission service was curtailed.
Commission Determination
102. We will not direct NERC to
modify footnote 9. We find NERC’s
explanation satisfactory that ‘‘the
planner must be able to show that the
curtailment is supported by a valid redispatch of generation that would be
‘obligated to redispatch’ . . . [t]herefore,
the planner cannot simply re-dispatch
units outside the area of control for the
transmission system for which it is
reviewing—the re-dispatch must be
valid and realistic.’’ 72
III. Information Collection Statement
103. The Office of Management and
Budget (OMB) regulations require that
OMB approve certain reporting and
recordkeeping (collections of
information) imposed by an agency.73
Upon approval of a collection(s) of
information, OMB will assign an OMB
control number and expiration date.
Respondents subject to the filing
requirements of this rule will not be
penalized for failing to respond to these
collections of information unless the
collections of information display a
valid OMB control number.
104. The Commission is submitting
these reporting and recordkeeping
requirements to OMB for its review and
approval under section 3507(d) of
Paperwork Reduction Act of 1995. The
Commission solicited comments on the
need for and the purpose of the
information contained in Reliability
Standard TPL–001–4 and the
corresponding burden to implement the
Reliability Standard. The Commission
received comments on specific
requirements in the Reliability
Standard, which we address in this
Final Rule. However, the Commission
did not receive any comments on our
reporting burden estimates. The Final
Rule approves Reliability Standard
TPL–001–4.
105. Public Reporting Burden: The
burden and cost estimates below are
based on the increase in the reporting
and recordkeeping burden imposed by
the proposed Reliability Standards. Our
estimates are based on the NERC
Compliance Registry as of February 28,
2013, which indicate that NERC has
72 NERC Petition, Consideration of Comments on
Assess Transmission Future Needs and Develop
Transmission Plans—Project 2006–02, draft 6, pp.
78–79.
73 5 CFR 1320.11.
E:\FR\FM\23OCR1.SGM
23OCR1
63050
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
registered 183 transmission planners
and planning coordinators.
Number and type of
entity 75
Number of annual
responses per entity
Average number of
paperwork hours per
response
Total burden hours
(1)
(2)
(3)
(1)*(2)*(3)
Year 1 .......................
183 Transmission
Planners and Planning Coordinators.
1 response ................
9 (5 engineer hours
and 4 record keeping hours).
1,647
Year 2 and Year 3 ....
183 Transmission
Planners and Planning Coordinators.
183 Transmission
Planners and Planning Coordinators.
1 response ................
5 (3 engineer hours
and 2 record keeping hours).
145 (84 engineer
hours, 61 record
keeping hours).
915
183 Transmission
Planners and Planning Coordinators.
1 Transmission Planner and Planning
Coordinator.
1 response ................
15,372
1 Transmission Planner and Planning
Coordinator.
4 responses to Attachment 1, Sections I, II, and III.
84 (45 engineer
hours, 39 record
keeping hours).
63 (40 engineer
hours, 17 record
keeping hours, 6
legal hours).
68 (40 engineer
hours, 20 record
keeping hours, 8
legal hours).
Improved
requirement 74
Identification of Joint
Responsibilities and
System Modeling
Enhancements 76.
New Assessments,
Simulations, Studies, Modeling Enhancements and associated Documentation77.
Year
Year 2 .......................
Year 3 .......................
Attachment 1 stakeholder process.
Year 3 .......................
Year 3 .......................
tkelley on DSK3SPTVN1PROD with RULES
Costs To Comply With Paperwork
Requirements
• Year 1: $77,592.
• Year 2: $1,312,659.
• Year 3 and ongoing: $820,149.
106. Year 1 costs include the
implementation of those improved
requirements that become effective on
the first day of the first calendar quarter,
12 months after applicable regulatory
approval, which include requirements
such as coordination between entities
and incremental system modeling
enhancements. Year 2 costs include a
portion of year 1 reoccurring costs plus
the implementation of the remaining
improved requirements that become
effective on the first day of the first
calendar quarter, 24 months after
applicable regulatory approval, which
74 Each requirement identifies a reliability
improvement by proposed Reliability Standard
TPL–001–4.
75 NERC registered transmission planners and
planning coordinators responsible for the improved
requirement. Further, if a single entity is registered
as both a transmission planner and planning
coordinator, that entity is counted as one unique
entity.
76 The Commission estimates a reduction in
burden hours from year 1 to year 2 because year 1
represents a portion of one-time tasks not repeated
in subsequent years.
77 The Commission estimates a reduction in
burden hours from year 2 to year 3 because year 2
represents a portion of one-time tasks not repeated
in subsequent years.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
1 response ................
12 responses to Attachment 1, sections I and II.
include requirements such as sensitivity
studies for steady state and stability
analysis, implementation of a spare
equipment strategy, short circuit
studies, an expansion of contingencies
and extreme events, and all associated
system modeling enhancements and
documentation. Year 3 costs include a
portion of year 2 reoccurring costs plus
an estimated cost for Attachment 1
stakeholder process, if needed.
107. For the burden categories above,
the loaded (salary plus benefits) costs
are: $60/hour for an engineer; $31/hour
for recordkeeping; and $128/hour for
legal.78 The estimated breakdown of
annual cost is as follows:
• Year 1
Æ Identification of Joint
Responsibilities and System Modeling
Enhancements: 183 entities * [(5 hours/
response * $60/hour) + (4 hours/
response * $31/hour)] = $77,592.
• Year 2
Æ Identification of Joint
Responsibilities and System Modeling
Enhancements: 183 entities * [(3 hours/
response * $60/hour) + (2 hours/
response * $31/hour)] = $44,286.
78 Labor rates from Bureau of Labor Statistics
(BLS) (https://bls.gov/oes/current/naics2_22.htm).
Loaded costs are BLS rates divided by 0.703 and
rounded to the nearest dollar (https://www.bls.gov/
news.release/ecec.nr0.htm).
PO 00000
Frm 00092
Fmt 4700
Sfmt 4700
26,535
756
272
Æ New Assessments, Simulations,
Studies, Modeling Enhancements and
associated Documentation: 183 entities
* [(84 hours/response * $60/hour) + (61
hours/response * $31/hour)] =
$1,268,373.
• Year 3
Æ Identification of Joint
Responsibilities and System Modeling
Enhancements: 183 entities * [(3 hours/
response * $60/hour) + (2 hours/
response * $31/hour)] = $44,286.
Æ New Assessments, Simulations,
Studies, Modeling Enhancements and
associated Documentation: 183 entities
* [(45 hours/response * $60/hour) + (39
hours/response * $31/hour)] = $715,347.
Æ Implementation of footnote 12 and
the stakeholder process: {12 responses *
[(40 hours/response * $60/hour) + (17
hours/response * $31/hour) + (6 hours/
response * $128/hour)]} + {4 responses
* [(40 hours/response * $60/hr) + (20
hours/response * $31/hour) + (8 hours/
response * $128/hour)]} = $60,516.
Title: 725N, Mandatory Reliability
Standards: Reliability Standard TPL–
001–4.79
79 The Supplemental NOPR used the identifier
FERC–725A (OMB Control No. 1902–0244).
However, for administrative purposes and to submit
the information collection requirements to OMB
timely, the requirements were labeled FERC–725N
(OMB Control No. 1902–0264) in the submittal to
OMB associated with the NOPR. We are using
E:\FR\FM\23OCR1.SGM
23OCR1
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
tkelley on DSK3SPTVN1PROD with RULES
Action: Proposed Collection FERC–
725N.
OMB Control No: 1902–0264.
Respondents: Business or other for
profit, and not for profit institutions.
Frequency of Responses: Annually
and one-time.
Necessity of the Information: The
approved Reliability Standard TPL–
001–4 implements the Congressional
mandate of the Energy Policy Act of
2005 to develop mandatory and
enforceable Reliability Standards to
better ensure the reliability of the
nation’s Bulk-Power System.
Specifically, the Reliability Standard
ensures that planning coordinators and
transmission planners establish
transmission system planning
performance requirements within the
planning horizon to develop a bulk
electric system that will operate
reliability and meet specified
performance requirements over a broad
spectrum of system conditions to meet
present and future system needs.
Internal review: The Commission has
reviewed the revised Reliability
Standard TPL–001–4 and made a
determination that its action is
necessary to implement section 215 of
the FPA. The Commission has assured
itself, by means of its internal review,
that there is specific, objective support
for the burden estimates associated with
the information requirements.
Interested persons may obtain
information on the reporting
requirements by contacting the
following: Federal Energy Regulatory
Commission, 888 First Street NE.,
Washington, DC 20426 [Attention: Ellen
Brown, Office of the Executive Director,
email: DataClearance@ferc.gov, phone:
202–502–8663, fax: 202–273–0873]. For
submitting comments concerning the
collection(s) of information and the
associated burden estimate(s), please
send your comments to the Commission
and to the Office of Management and
Budget, Office of Information and
Regulatory Affairs, Washington, DC
20503 [Attention: Desk Officer for the
Federal Energy Regulatory Commission,
phone: 202–395–4638, fax: 202–395–
7285]. For security reasons, comments
to OMB should be submitted by email
to: oira_submission@omb.eop.gov.
Comments submitted to OMB should
include FERC–725N and Docket Nos.
RM12–1–000 and RM13–9–000.
IV. Environmental Analysis
108. The Commission is required to
prepare an Environmental Assessment
or an Environmental Impact Statement
FERC–725N in this Final Rule and in the associated
submittal to OMB.
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
for any action that may have a
significant adverse effect on the human
environment.80 The Commission has
categorically excluded certain actions
from this requirement as not having a
significant effect on the human
environment. Included in the exclusion
are rules that are clarifying, corrective,
or procedural or that do not
substantially change the effect of the
regulations being amended.81 The
actions proposed herein fall within this
categorical exclusion in the
Commission’s regulations.
V. Regulatory Flexibility Act Analysis
109. The Regulatory Flexibility Act of
1980 (RFA) 82 generally requires a
description and analysis of final rules
that will have significant economic
impact on a substantial number of small
entities. The RFA mandates
consideration of regulatory alternatives
that accomplish the stated objectives of
a proposed rule and that minimize any
significant economic impact on a
substantial number of small entities.
The Small Business Administration’s
(SBA) Office of Size Standards develops
the numerical definition of a small
business.83 The SBA has established a
size standard for electric utilities,
stating that a firm is small if, including
its affiliates, it is primarily engaged in
the transmission, generation and/or
distribution of electric energy for sale
and its total electric output for the
preceding twelve months did not exceed
four million megawatt hours.84
110. As discussed above, Reliability
Standard TPL–001–4 would apply to
183 transmission planners and planning
coordinators identified in the NERC
Compliance Registry. Comparison of the
NERC Compliance Registry with data
submitted to the Energy Information
Administration on Form EIA–861
indicates that, of the 183 registered
transmission planners and planning
coordinators registered by NERC, 41
may qualify as small entities.
111. The Commission estimates that,
on average, each of the 41 small entities
affected will have an estimated cost of
$1,324 in Year 1, $16,953 in Year 2 85
and $11,471 in Year 3 (without
Attachment 1). In addition, based on the
80 Regulations Implementing the National
Environmental Policy Act of 1969, Order No. 486,
FERC Stats. & Regs. ¶ 30,783 (1987).
81 18 CFR 380.4(a)(2)(ii).
82 5 U.S.C. 601–12.
83 13 CFR 121.101.
84 13 CFR 121.201, Sector 22, Utilities & n.1.
85 The increase in Year 2 costs include a portion
of year 1 recurring costs plus the implementation
of the remaining improved requirements that
become effective on the first day of the first
calendar quarter, 24 months after applicable
regulatory approval.
PO 00000
Frm 00093
Fmt 4700
Sfmt 4700
63051
results of NERC’s data request
approximately 10 percent of all
registered transmission planners and
planning coordinators used planned
non-consequential load loss under the
currently-effective TPL Reliability
Standards. The Commission estimates
that approximately 4 of the 41 small
entities would use the stakeholder
process set forth in Attachment 1. The
total estimated cost per response for
each of these 4 small entities in Year 3
is approximately $19,500 if Attachment
1, sections I and II are used, or $20,000
if Attachment 1, sections I, II and III are
used. These figures are based on
information collection costs plus
additional costs for compliance. Based
on this estimate, the Commission
certifies that Reliability Standard TPL–
001–4 will not have a significant
economic impact on a substantial
number of small entities. Accordingly,
no regulatory flexibility analysis is
required.
VI. Document Availability
112. In addition to publishing the full
text of this document in the Federal
Register, the Commission provides all
interested persons an opportunity to
view and/or print the contents of this
document via the Internet through
FERC’s Home Page (https://
www.ferc.gov) and in FERC’s Public
Reference Room during normal business
hours (8:30 a.m. to 5:00 p.m. Eastern
time) at 888 First Street NE., Room 2A,
Washington, DC 20426.
113. From FERC’s Home Page on the
Internet, this information is available on
eLibrary. The full text of this document
is available on eLibrary in PDF and
Microsoft Word format for viewing,
printing, and/or downloading. To access
this document in eLibrary, type the
docket number excluding the last three
digits of this document in the docket
number field.
114. User assistance is available for
eLibrary and the FERC’s Web site during
normal business hours from FERC
Online Support at 202–502–6652 (toll
free at 1–866–208–3676) or email at
ferconlinesupport@ferc.gov, or the
Public Reference Room at (202) 502–
8371, TTY (202) 502–8659. Email the
Public Reference Room at
public.referenceroom@ferc.gov.
VII. Effective Date and Congressional
Notification
115. These regulations are effective
December 23, 2013. The Commission
has determined that this rule is not a
‘‘major rule’’ as defined in section 351
of the Small Business Regulatory
Enforcement Fairness Act of 1996.
E:\FR\FM\23OCR1.SGM
23OCR1
63052
Federal Register / Vol. 78, No. 205 / Wednesday, October 23, 2013 / Rules and Regulations
By the Commission.
Nathaniel J. Davis, Sr.,
Deputy Secretary.
[FR Doc. 2013–24828 Filed 10–22–13; 8:45 am]
BILLING CODE 6717–01–P
DEPARTMENT OF HOMELAND
SECURITY
U.S. Customs and Border Protection
DEPARTMENT OF THE TREASURY
19 CFR Parts 10, 24, 162, 163, and 178
[USCBP–2013–0040; CBP Dec. 13–17]
RIN 1515–AD93
United States-Panama Trade
Promotion Agreement
U.S. Customs and Border
Protection, Department of Homeland
Security; Department of the Treasury.
ACTION: Interim regulations; solicitation
of comments.
AGENCY:
This rule amends the U.S.
Customs and Border Protection (CBP)
regulations on an interim basis to
implement the preferential tariff
treatment and other customs-related
provisions of the United States-Panama
Trade Promotion Agreement entered
into by the United States and the
Republic of Panama.
DATES: Interim rule effective October 23,
2013; comments must be received by
December 23, 2013.
ADDRESSES: You may submit comments,
identified by docket number, by one of
the following methods:
• Federal eRulemaking Portal: https://
www.regulations.gov. Follow the
instructions for submitting comments
via docket number USCBP–2013–0040.
• Mail: Trade and Commercial
Regulations Branch, Regulations and
Rulings, Office of International Trade,
U.S. Customs and Border Protection, 90
K Street NE., 10th Floor, Washington,
DC 20229–1177.
Instructions: All submissions received
must include the agency name and
docket number for this rulemaking. All
comments received will be posted
without change to https://
www.regulations.gov, including any
personal information provided. For
detailed instructions on submitting
comments and additional information
on the rulemaking process, see the
‘‘Public Participation’’ heading of the
SUPPLEMENTARY INFORMATION section of
this document.
Docket: For access to the docket to
read background documents or
tkelley on DSK3SPTVN1PROD with RULES
SUMMARY:
VerDate Mar<15>2010
16:30 Oct 22, 2013
Jkt 232001
comments received, go to https://
www.regulations.gov. Submitted
comments may also be inspected during
regular business days between the hours
of 9 a.m. and 4:30 p.m. at the Trade and
Commercial Regulations Branch,
Regulations and Rulings, Office of
International Trade, U.S. Customs and
Border Protection, 90 K Street NE., 10th
Floor, Washington, DC. Arrangements to
inspect submitted comments should be
made in advance by calling Mr. Joseph
Clark at (202) 325–0118.
FOR FURTHER INFORMATION CONTACT:
Textile Operational Aspects: Diane
Liberta, Textile Operations Branch,
Office of International Trade, (202) 863–
6241.
Other Operational Aspects: Katrina
Chang, Trade Policy and Programs,
Office of International Trade, (202) 863–
6532.
Legal Aspects: Karen Greene,
Regulations and Rulings, Office of
International Trade, (202) 325–0041.
SUPPLEMENTARY INFORMATION:
Public Participation
Interested persons are invited to
participate in this rulemaking by
submitting written data, views, or
arguments on all aspects of the interim
rule. U.S. Customs and Border
Protection (CBP) also invites comments
that relate to the economic,
environmental, or federalism effects that
might result from this interim rule.
Comments that will provide the most
assistance to CBP in developing these
regulations will reference a specific
portion of the interim rule, explain the
reason for any recommended change,
and include data, information, or
authority that support such
recommended change. See ADDRESSES
above for information on how to submit
comments.
Background
On June 28, 2007, the United States
and the Republic of Panama (the
‘‘Parties’’) signed the United StatesPanama Trade Promotion Agreement
(‘‘PANTPA’’ or ‘‘Agreement’’).
On October 21, 2011, the President
signed into law the United StatesPanama Trade Promotion Agreement
Implementation Act (the ‘‘Act’’), Public
Law 112–43, 125 Stat. 497 (19 U.S.C.
3805 note), which approved and made
statutory changes to implement the
PANTPA. Section 103 of the Act
requires that regulations be prescribed
as necessary to implement the
provisions of the PANTPA.
On October 29, 2012, the President
signed Proclamation 8894 to implement
the PANTPA. The Proclamation, which
PO 00000
Frm 00094
Fmt 4700
Sfmt 4700
was published in the Federal Register
on November 5, 2012, (77 FR 66507),
modified the Harmonized Tariff
Schedule of the United States
(‘‘HTSUS’’) as set forth in Annexes I and
II of Publication 4349 of the U.S.
International Trade Commission. The
modifications to the HTSUS included
the addition of new General Note 35,
incorporating the relevant PANTPA
rules of origin as set forth in the Act,
and the insertion throughout the HTSUS
of the preferential duty rates applicable
to individual products under the
PANTPA where the special program
indicator ‘‘PA’’ appears in parenthesis
in the ‘‘Special’’ rate of duty subcolumn.
The modifications to the HTSUS also
included a new Subchapter XIX to
Chapter 99 to provide for temporary
tariff-rate quotas and applicable
safeguards implemented by the
PANTPA, as well as modifications to
Subchapter XXII of Chapter 98. After the
Proclamation was signed, CBP issued
instructions to the field and the public
implementing the Agreement by
allowing the trade to receive the benefits
under the PANTPA effective on or after
October 31, 2012.
CBP is responsible for administering
the provisions of the PANTPA and the
Act that relate to the importation of
goods into the United States from the
Republic of Panama (‘‘Panama’’). Those
customs-related PANTPA provisions,
which require implementation through
regulation, include certain tariff and
non-tariff provisions within Chapter
One (Initial Provisions), Chapter Two
(General Definitions), Chapter Three
(National Treatment and Market Access
for Goods), Chapter Four (Rules of
Origin and Origin Procedures), and
Chapter Five (Customs Administration
and Trade Facilitation).
Certain general definitions set forth in
Chapter Two of the PANTPA have been
incorporated into the PANTPA
implementing regulations. These
regulations also implement Article 3.6
(Goods Re-entered after Repair or
Alteration) of the PANTPA.
Chapter Three of the PANTPA sets
forth provisions relating to trade in
textile and apparel goods between
Panama and the United States. The
provisions within Chapter Three that
require regulatory action by CBP are
Articles 3.21 (Customs Cooperation),
Article 3.25 (Rules of Origin and Related
Matters), and Article 3.30 (Definitions).
Chapter Four of the PANTPA sets
forth the rules for determining whether
an imported good is an originating good
of a Party and, as such, is therefore
eligible for preferential tariff (duty-free
or reduced duty) treatment under the
PANTPA as specified in the Agreement
E:\FR\FM\23OCR1.SGM
23OCR1
Agencies
[Federal Register Volume 78, Number 205 (Wednesday, October 23, 2013)]
[Rules and Regulations]
[Pages 63036-63052]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2013-24828]
=======================================================================
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
Federal Energy Regulatory Commission
18 CFR Part 40
[Docket Nos. RM12-1-000 and RM13-9-000; Order No. 786]
Transmission Planning Reliability Standards
AGENCY: Federal Energy Regulatory Commission, Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: Under section 215 of the Federal Power Act, the Federal Energy
Regulatory Commission approves Transmission Planning (TPL) Reliability
Standard TPL-001-4, submitted by the North American Electric
Reliability Corporation, the Commission-certified Electric Reliability
Organization. Reliability Standard TPL-001-4 introduces significant
revisions and improvements by requiring annual assessments addressing
near-term and long-term planning horizons for steady state, short
circuit and stability conditions. Reliability Standard TPL-001-4 also
includes a provision that allows a transmission planner to plan for
non-consequential load loss following a single contingency by providing
a blend of specific quantitative and qualitative parameters for the
permissible use of planned non-consequential load loss to address bulk
electric system performance issues, including firm limitations on the
maximum amount of load that an entity may plan to shed, safeguards to
ensure against inconsistent results and arbitrary determinations that
allow for the planned non-consequential load loss,
[[Page 63037]]
and a more specifically defined, open and transparent, verifiable, and
enforceable stakeholder process. The Commission finds in the Final Rule
that the proposed Reliability Standard is just, reasonable, not unduly
discriminatory or preferential, and in the public interest. In
addition, the Commission directs NERC to modify Reliability Standard
TPL-001-4 to address the concern that the standard could exclude
planned maintenance outages of significant facilities from future
planning assessments and directs NERC to change the TPL-001-4,
Requirement R1 Violation Risk Factor from medium to high.
DATES: This rule will become effective December 23, 2013.
FOR FURTHER INFORMATION CONTACT:
Eugene Blick (Technical Information), Office of Electric Reliability,
Federal Energy Regulatory Commission, 888 First Street, NE.,
Washington, DC 20426, Telephone: (202) 502-8066, Eugene.Blick@ferc.gov.
Robert T. Stroh (Legal Information), Office of the General Counsel,
Federal Energy Regulatory Commission, 888 First Street, NE.,
Washington, DC 20426, Telephone: (202) 502-8473, Robert.Stroh@ferc.gov.
SUPPLEMENTARY INFORMATION:
145 FERC ] 61,051
Before Commissioners: Jon Wellinghoff, Chairman; Philip D. Moeller,
John R. Norris, Cheryl A. LaFleur, and Tony Clark.
(Issued October 17, 2013)
1. Under section 215(d) of the Federal Power Act (FPA), the
Commission approves Transmission Planning (TPL) Reliability Standard
TPL-001-4, submitted by the North American Electric Reliability
Corporation (NERC), the Commission-certified Electric Reliability
Organization (ERO).\1\ The Commission finds that Reliability Standard
TPL-001-4 introduces significant revisions and improvements to the TPL
Reliability Standards, including increased specificity of data required
for modeling conditions, and requires annual assessments addressing
near-term and long-term planning horizons for steady state, short
circuit and stability conditions. Further, we find that the Reliability
Standard generally addresses the Commission directives set forth in
Order No. 693 and subsequent Commission orders.\2\ We agree with NERC
that Reliability Standard TPL-001-4 includes specific improvements over
the currently-effective Transmission Planning Reliability Standards and
is responsive to the Commission's directives.
---------------------------------------------------------------------------
\1\ 16 U.S.C. 824o(d) (2006).
\2\ Mandatory Reliability Standards for the Bulk-Power System,
Order No. 693, FERC Stats. & Regs. ] 31,242, order on reh'g, Order
No. 693-A, 120 FERC ] 61,053 (2007).
---------------------------------------------------------------------------
2. Further, in response to Order No. 762,\3\ Reliability Standard
TPL-001-4 includes a provision that allows a transmission planner to
plan for non-consequential load loss following a single contingency.
While the Reliability Standard provides that ``an objective of the
planning process is to limit the likelihood and magnitude of Non-
Consequential Load Loss following planning events,'' the standard also
recognizes that ``[i]n limited circumstances, Non-Consequential Load
Loss may be needed throughout the planning horizon to ensure that BES
performance requirements are met.'' \4\ Thus, for such limited
circumstances, Reliability Standard TPL-001-4 provides a blend of
specific quantitative and qualitative parameters for the permissible
use of planned non-consequential load loss to address bulk electric
system performance issues, including firm limitations on the maximum
amount of load that an entity may plan to shed, safeguards to ensure
against inconsistent results and arbitrary determinations that allow
for the planned non-consequential load loss, and a more specifically
defined, open and transparent, verifiable, and enforceable stakeholder
process.
---------------------------------------------------------------------------
\3\ Transmission Planning Reliability Standards, Order No. 762,
139 FERC ] 61,060 (2012) (Order No. 762), order on reconsideration,
140 FERC ] 61,101 (2012). See also Transmission Planning Reliability
Standards, 139 FERC ] 61,059 (2012) (April 2012 NOPR).
\4\ Reliability Standard TPL-001-4, Table I (Steady State and
Stability Performance Extreme Events), n.12.
---------------------------------------------------------------------------
3. For the reasons discussed in detail below, the Commission finds
that Reliability Standard TPL-001-4 is just, reasonable, not unduly
discriminatory or preferential, and in the public interest. Therefore,
pursuant to section 215(d) of the FPA the Commission approves proposed
Reliability Standard TPL-001-4. Thus, the Commission approves footnote
12 to Table 1 of the Reliability Standard (formerly referred to as
footnote `b'). In addition, as discussed below, the Commission finds
NERC's explanation on protection system failures versus relay failures,
assessment of backup or redundant protection systems, single line to
ground faults and the Order No. 693 directives to be reasonable.
However, the Commission has concerns about two issues and directs NERC
to modify Reliability Standard TPL-001-4 to address the concern that
the standard could exclude planned maintenance outages of significant
facilities from future planning assessments and directs NERC to change
the TPL-001-4, Requirement R1 VRF from medium to high.
I. Background
A. Regulatory History
4. In Order No. 693, the Commission accepted the Version 0 TPL
Reliability Standards.\5\ Further, pursuant to FPA section 215(d)(5),
the Commission directed NERC to develop modifications through the
Reliability Standards development process to address certain issues
identified by the Commission. In addition, the Commission neither
approved nor remanded Reliability Standards TPL-005-0 and TPL-006-0
because these two standards applied only to regional reliability
organizations, the predecessors to the statutorily recognized Regional
Entities. With regard to Reliability Standard TPL-002-0b, Table 1,
footnote `b,' which applies to planned non-consequential load loss, the
Commission directed NERC to clarify footnote `b' regarding the planned
non-consequential load loss for a single contingency event.\6\ In a
March 18, 2010 order, the Commission directed NERC to submit a
modification to footnote `b' responsive to the Commission's directive
in Order No. 693 by June 30, 2010.\7\ In a June 11, 2010 order, the
Commission extended the compliance deadline until March 31, 2011.\8\
---------------------------------------------------------------------------
\5\ Order No. 693, FERC Stats. & Regs. ] 31,242 at PP 1840,
1845. The currently-effective versions of the TPL Reliability
Standards are as follows: TPL-001-0.1, TPL-002-0b, TPL-003-0a, and
TPL-004-0.
\6\ Order No. 693, FERC Stats. & Regs. ] 31,242 at P 1792.
\7\ Mandatory Reliability Standards for the Bulk Power System,
130 FERC ] 61,200 (2010).
\8\ Mandatory Reliability Standards for the Bulk Power System,
131 FERC ] 61,231 (2010).
---------------------------------------------------------------------------
Remand of Footnote b of the Version 1 TPL Reliability Standard (RM11-
18-000)
5. On March 31, 2011, NERC submitted proposed Reliability Standard
TPL-002-1 (Version 1). NERC proposed to modify Table 1, footnote `b' to
permit planned non-consequential load loss when documented and
subjected to an open stakeholder process.\9\ In Order No.
[[Page 63038]]
762, the Commission remanded to NERC the proposed modification to
footnote `b,' concluding that the proposed revisions did not meet the
Commission's Order No. 693 directives, nor did the revisions achieve an
equally effective and efficient alternative.\10\ The Commission stated
that the proposal did not adequately clarify or define the
circumstances in which an entity can use planned non-consequential load
loss as a mitigation plan to meet performance requirements for single
contingency events. The Commission also explained that the procedural
and substantive parameters of NERC's proposal were too undefined to
provide assurances that the process will be effective in determining
when it is appropriate to plan for non-consequential load loss, did not
contain NERC-defined criteria on circumstances to determine when an
exception for planned non-consequential load loss is permissible, and
could result in inconsistent results in implementation. Accordingly,
the Commission remanded the filing to NERC and directed NERC to develop
revisions to footnote `b' that would address the Commission's concerns.
Additionally, in Order No. 762, the Commission directed NERC to
``identify the specific instances of any planned interruptions of firm
demand under footnote `b' and how frequently the provision has been
used.'' \11\
---------------------------------------------------------------------------
\9\ See Order No. 693, FERC Stats. & Regs. ] 31,242 at P 1794.
Non-consequential load loss includes the removal, by any means, of
any planned firm load that is not directly served by the elements
that are removed from service as a result of the contingency.
Currently-effective footnote `b' deals with both consequential load
loss and non-consequential load loss. NERC's proposed footnote `b'
characterized both types of load loss as ``firm demand.''
\10\ Order No. 762, 139 FERC ] 61,060.
\11\ Id. P 20.
---------------------------------------------------------------------------
Proposed Remand of Version 2 of the TPL Reliability Standard (RM12-1-
000)
6. On October 19, 2011, NERC submitted a petition seeking approval
of a revised and consolidated TPL Reliability Standard that combined
the four currently-effective TPL Reliability Standards into a single
standard, TPL-001-2 (Version 2).\12\ The Version 2 standard included
language similar to NERC's Version 1 proposal with regard to utilizing
non-consequential load loss. The Version 2 standard included a non-
consequential load loss provision in Table 1--Steady State & Stability
Performance Footnotes (Planning Events and Extreme Events), footnotes 9
and 12.\13\
---------------------------------------------------------------------------
\12\ NERC's October 2011 petition sought approval of Reliability
Standard TPL-001-2, the associated implementation plan and Violation
Risk Factors (VRFs) and Violation Severity Levels (VSLs), as well as
five new definitions to be added to the NERC Glossary of Terms. NERC
also requested approval to retire four currently-effective TPL
Reliability Standards: TPL-001-1, TPL-002-1b, TPL-003-1a; and TPL-
004-1. In addition, NERC requested to withdraw two pending
Reliability Standards: TPL-005-0 and TPL-006-0.1.
\13\ NERC's October 2011 Petition at 12. NERC's proposal in
Docket No. RM11-18-000, Table 1, footnote `b' referred to planned
load shed as planned ``interruption of Firm Demand.'' In footnote
12, proposed to replace footnote `b,' NERC changed the term from
``interruption of Firm Demand'' to utilization of ``Non-
Consequential Load Loss.''
---------------------------------------------------------------------------
7. On the same day that the Commission issued Order No. 762, the
Commission issued a notice of proposed rulemaking (April 2012 NOPR)
stating that, notwithstanding that proposed Version 2 included specific
improvements over the currently-effective Transmission Planning
Reliability Standards, footnote 12 ``allow[s] for transmission planners
to plan for non-consequential load loss following a single contingency
without adequate safeguards [and] undermines the potential benefits the
proposed Reliability Standard may provide.'' \14\ Thus, the Commission
stated that its concerns regarding the stakeholder process set forth in
footnote 12 required a proposal to remand the entire Reliability
Standard. The Commission added that resolution of the footnote 12
concerns ``would allow the industry, NERC and the Commission to go
forward with the consideration of other improvements contained in
proposed Version 2.'' \15\ In addition, the April 2012 NOPR asked for
comment on various aspects of the consolidated Version 2 Reliability
Standard. Comments on the NOPR were due by July 20, 2012. The following
entities submitted comments: NERC, the Edison Electric Institute (EEI),
ISO/RTOs,\16\ ITC Companies,\17\ Midcontinent Independent System
Operator Inc. (MISO),\18\ American Transmission Company LLC (ATCLLC),
Powerex Corporation (Powerex), Bonneville Power Administration (BPA),
and Hydro One Networks and the Independent Electricity System Operator
(Hydro One and IESO).
---------------------------------------------------------------------------
\14\ April 2012 NOPR, 139 FERC ] 61,059 at P 55.
\15\ Id. P 3.
\16\ The ISO/RTOs consist of Electric Reliability Council of
Texas, Inc., ISO New England, Inc., Midcontinent Independent
Transmission System Operator Inc., New York Independent System
Operator, Inc., PJM Interconnection L.L.C., and Southwest Power
Pool, Inc.
\17\ ITC Companies consist of ITCTransmission, Michigan Electric
Transmission Company LLC, ITC Midwest LLC, and ITC Great Plains.
\18\ Effective April 26, 2013, MISO changed its name from
``Midwest Independent Transmission System Operator, Inc.'' to
``Midcontinent Independent System Operator, Inc.''
---------------------------------------------------------------------------
Proposed Reliability Standard TPL-001-4--Version 4 (RM13-9-000)
8. On February 28, 2013, NERC submitted proposed Reliability
Standard TPL-001-4 (Version 4) in response to the Commission's remand
in Order No. 762 and concerns with regard to Table 1 footnote 12
identified in the April 2012 NOPR.\19\ Reliability Standard TPL-001-4
includes eight requirements and Table 1: \20\
---------------------------------------------------------------------------
\19\ In its filing, NERC stated that the Version 4 standard,
i.e., TPL-001-4, modifies the pending Version 2 consolidated
standard, TPL-001-2. NERC also submitted, alternatively, a group of
four TPL standards (TPL-001-3, TPL-002-2b, TPL-003-2a, and TPL-004-
2, collectively, the Version 3 TPL standards) that would modify
``footnote b'' of the currently-effective TPL standards, ``[i]n the
event the Commission does not approve the Consolidated TPL Standards
[Version 4].'' NERC Petition at 4. Because we approve TPL-001-4,
references throughout this Final Rule are to the Version 4 standard.
\20\ The filed proposed Reliability Standard is not attached to
the Final Rule but is available on the Commission's eLibrary
document retrieval system in Docket Nos. RM12-1-000 and RM13-9-000
and are available on NERC's Web site, https://www.nerc.com.
---------------------------------------------------------------------------
Requirement R1: Requires the transmission planner and planning
coordinator to maintain system models and provides a specific list of
items required for the system models and that the models represent
projected system conditions. The planner is required to model the items
that are variable, such as load and generation dispatch, based
specifically on the expected system conditions.
Requirement R2: Requires each transmission planner and planning
coordinator to prepare an annual planning assessment of its portion of
the bulk electric system and must use current or qualified past
studies, document assumptions, and document summarized results of the
steady state analyses, short circuit analyses, and stability analyses.
Requirement R2, Part 2.1.3 requires the planner to assess system
performance utilizing a current annual study or qualified past study
for each known outage with a duration of at least six months for
certain events. It also clarifies that qualified past studies can be
utilized in the analysis while tightly defining the qualifications for
those studies. Requirement R2 includes a new part 2.7.3 that allows
transmission planners and planning coordinators to utilize non-
consequential load loss to meet performance requirements if the
applicable entities are unable to complete a corrective action plan due
to circumstances beyond their control.
Requirements R3 and R4: Requirement R3 describes the requirements
for steady state studies and Requirement R4 explains the requirements
for stability studies. Requirement R3 and Requirement R4 also require
that simulations duplicate what will occur in an actual power system
based on the expected performance of the protection systems.
[[Page 63039]]
Requirement R3 and Requirement R4 also include new parts that require
the planners to conduct an evaluation of possible actions designed to
reduce the likelihood or the consequences of extreme events that cause
cascading.
Requirement R5: Requirement R5 deals with voltage criteria and
voltage performance. NERC proposes in Requirement R5 that each
transmission planner and planning coordinator must have criteria for
acceptable system steady state voltage limits, post-contingency voltage
deviations, and the transient voltage response for its system. For
transient voltage response the criteria must specify a low-voltage
level and a maximum length of time that transient voltages may remain
below that level. This requirement will establish more robust
transmission planning for organizations and greater consistency as
these voltage criteria are shared.
Requirement R6: Specifies that an entity must define and document
the criteria or methodology used to identify system instability for
conditions such as cascading, voltage instability, or uncontrolled
islanding within its planning assessment.
Requirement R7: Mandates coordination of individual and joint
responsibilities for the planning coordinator and the transmission
planner which is intended to eliminate confusion regarding the
responsibilities of the applicable entities and assures that all
elements needed for regional and wide area studies are defined with a
specific entity responsible for each element and that no gaps will
exist in planning for the Bulk-Power System.
Requirement R8: Addresses the sharing of planning assessments with
neighboring systems. The requirement ensures that information is shared
with and input received from adjacent entities and other entities with
a reliability related need that may be affected by an entity's system
planning.
Table 1: Similar to the currently-effective TPL Reliability
Standard, the revised standard contains a series of planning events and
describes system performance requirements in Table 1 for a range of
potential system contingencies required to be evaluated by the planner.
Table 1 includes three parts: Steady State & Stability Performance
Planning Events, Steady State & Stability Performance Extreme Events,
and Steady State & Stability Performance Footnotes. Table 1 categorizes
the events as either ``planning events'' or ``extreme events.'' The
proposed table lists seven contingency planning events that require
steady-state and stability analysis as well as five extreme event
contingencies.
9. NERC modified footnote 12 of Table 1 to provide specific
parameters for the permissible use of planned non-consequential load
loss to address bulk electric system performance issues, including: (1)
Firm limitations on the maximum amount of load that an entity may plan
to shed, (2) safeguards to ensure against inconsistent results and
arbitrary determinations that allow for the planned non-consequential
load loss, and (3) a more specifically defined, open and transparent,
verifiable, and enforceable stakeholder process. Footnote 12 as
modified provides:
An objective of the planning process is to minimize the
likelihood and magnitude of Non-Consequential Load Loss following
planning events. In limited circumstances, Non-Consequential Load
Loss may be needed throughout the planning horizon to ensure that
BES performance requirements are met. However, when Non-
Consequential Load Loss is utilized under footnote 12 within the
Near-Term Transmission Planning Horizon to address BES performance
requirements, such interruption is limited to circumstances where
the Non-Consequential Load Loss meets the conditions shown in
Attachment 1. In no case can the planned Non-Consequential Load Loss
under footnote 12 exceed 75 MW for US registered entities. The
amount of planned Non-Consequential Load Loss for a non-US
Registered Entity should be implemented in a manner that is
consistent with, or under the direction of, the applicable
governmental authority or its agency in the non-US jurisdiction.
10. Attachment 1 to TPL-001-4, referenced in footnote 12 has three
sections: (I) Stakeholder process, (II) information an entity must
provide to stakeholders, and (III) instances for which regulatory
review of planned non-consequential load loss under footnote 12 is
required. Section I describes five criteria that apply to the open and
transparent stakeholder process that an entity must implement when it
seeks to use footnote 12. Section I provides that an entity does not
have to repeat the stakeholder process for a specific application of
footnote 12 with respect to subsequent planning assessments unless
conditions have materially changed for that specific application.
11. Section II of Attachment 1 specifies eight categories of
information that entities must provide to stakeholders, including
estimated amount, frequency and duration of planned non-consequential
load loss under footnote 12. An entity must also provide information on
alternatives considered and future plans to alleviate the need for
planned non-consequential load loss.
12. Section III of Attachment 1 describes the process for planned
non-consequential load loss greater than 25 MW. Specifically, planned
non-consequential load loss between 25 MW and 75 MW, or any planned
non-consequential load loss at the 300 kV level or above would receive
greater scrutiny by regulatory authorities and the ERO. Where these
parameters apply, ``the Transmission Planner or Planning Coordinator
must ensure that applicable regulatory authorities or governing bodies
responsible for retail electric service issues do not object to the use
of Non-Consequential Load Loss under footnote 12.'' \21\ Further,
``[o]nce assurance has been received that the applicable regulatory
authorities . . . responsible for retail electric service issues do not
object . . . the Planning Coordinator or Transmission Planner must
submit the information [in Section II of Attachment 1] to the ERO for a
determination of whether there are any Adverse Reliability Impacts''
caused by the responsible entity's request to use footnote 12.\22\
According to NERC, this provision provides safeguards against arbitrary
or inconsistent determinations, and also ``preserves, to the extent
practicable, the role of Retail Regulators,'' while allowing ERO review
for possible adverse reliability impacts.\23\
---------------------------------------------------------------------------
\21\ NERC Petition, Exhibit A, proposed Reliability Standard
TPL-001-4, Attachment I, section 3.
\22\ NERC Petition, Exhibit A, proposed Reliability Standard
TPL-001-4, Attachment I, section 3. NERC defines ``Adverse
Reliability Impact'' as ``[t]he impact of an event that results in
frequency-related instability; unplanned tripping of load or
generation; or uncontrolled separation or cascading outages that
affects a widespread area of the Interconnection.'' NERC Glossary at
4.
\23\ NERC February 2013 Petition at 19.
---------------------------------------------------------------------------
13. NERC stated that the combination of numerical limitations and
other considerations, such as costs and alternatives, guards against a
determination based solely on a quantitative threshold becoming an
acceptable de facto interpretation of planned non-consequential load
loss. According to NERC, the procedures in footnote 12 would enable
acceptable, but limited, circumstances of planned non-consequential
load loss after a thorough stakeholder review and approval and ERO
review.
14. NERC also stated that, because footnote 12 differs from
footnote `b' included in the currently-effective TPL Reliability
Standards, data do not yet exist on the frequency of instances of
planned non-consequential load loss under the new footnote 12.
Consequently, NERC stated that it will monitor the use of footnote 12
and will report the results of this monitoring
[[Page 63040]]
after the first two years of the footnote's implementation.\24\
---------------------------------------------------------------------------
\24\ NERC's February 2013 Petition at 11.
---------------------------------------------------------------------------
15. NERC requested that requirements R1 and R7 of the Version 4
Reliability Standard as well as the definitions become effective on the
first day of the first calendar quarter twelve months after applicable
regulatory approval. In addition, except as indicated below, NERC
requested that Requirements R2 through R6 and Requirement R8 including
Table 1--Steady State & Stability Performance Planning Events, Table
1--Steady State & Stability Performance Extreme Events, Table 1--Steady
State & Stability Performance Footnotes (Planning Events & Extreme
Events) and Attachment 1 become effective and subject to compliance on
the first day of the first calendar quarter, 24 months after applicable
regulatory approval.
16. NERC also proposed that, for 84 calendar months beginning the
first day of the first calendar quarter following applicable regulatory
approval, concurrent with the 24 month effective date of Requirement
R2, corrective action plans applying to specific categories of
contingencies and events identified in TPL-001-4, Table 1 are allowed
to include non-consequential load loss and curtailment of firm
transmission service (in accordance with Requirement R2, Part 2.7.3)
that would not otherwise be permitted by the requirements of the
Version 4 Reliability Standard. Further, NERC stated that Requirement
R2, Part 2.7.3 addresses situations that are beyond the control of the
planner that prevent the implementation of a corrective action plan in
the required timeframe. Some examples of situations beyond the control
of the planner could include a state road widening project taking
substation land that was targeted for expansion or a ruling preventing
the entity from condemning the land necessary for a project.
17. NERC also requested approval to retire the currently-effective
TPL Reliability Standards and to withdraw two pending TPL Reliability
Standards, TPL-005-0 and TPL-006-0.1, because it transferred the
requirements of the pending Reliability Standards to sections 803 and
804 of NERC's Rules of Procedure. NERC proposed to retire TPL
Reliability Standards TPL-001-0.1, TPL-002-0b, TPL-003-0a, and TPL-004-
0 on midnight of the day immediately prior to the effective date of
TPL-001-4. However, during the 24-month implementation period, all
aspects of the currently-effective TPL Reliability Standards, TPL-001-
0.1 through TPL-004-0 will remain in effect for compliance monitoring.
NERC stated that the 24 month period is to allow entities to develop,
perform and/or validate new or modified studies necessary to implement
and meet Reliability Standard TPL-001-4. NERC explained that the
specified effective dates allow sufficient time for proper assessment
of the available options necessary to create a viable corrective action
plan that is compliant with the new TPL Reliability Standard.
Supplemental NOPR
18. On May 16, 2013, the Commission issued a Supplemental NOPR
which proposed to approve the Version 4 TPL Reliability Standard, TPL-
001-4, as just, reasonable, not unduly discriminatory or preferential,
and in the public interest.\25\ In the Supplemental NOPR, the
Commission suggested that, while NERC's proposal differs from the
Commission directives on the matter of utilizing non-consequential load
loss, NERC's proposal adequately addresses the underlying reliability
concerns raised in Order No. 693, Order No. 762 and the April 2012 NOPR
and, thus, is an equally effective and efficient alternative to address
the Commission's directives.\26\ In the Supplemental NOPR, the
Commission proposed to find that proposed footnote 12 would improve
reliability by providing a blend of specific quantitative and
qualitative parameters for the permissible use of planned non-
consequential load loss to address bulk electric system performance
issues. In addition, the Commission stated that the stakeholder process
appears to be adequately defined and includes specific criteria and
guidelines that a responsible entity must follow before it may use
planned non-consequential load loss to meet Reliability Standard TPL-
001-4 performance requirements for a single contingency event. Further,
the Supplemental NOPR indicated that NERC's proposal provides
reasonable safeguards, including a review process by NERC, to protect
against adverse reliability impacts that could otherwise result from
planned non-consequential load loss.\27\
---------------------------------------------------------------------------
\25\ Transmission Planning Reliability Standards, Notice of
Proposed Rulemaking, 143 FERC ] 61,136 (2013) (Supplemental NOPR).
\26\ Supplemental NOPR, 143 FERC ] 61,136 at P 18.
\27\ Id. P 19.
---------------------------------------------------------------------------
19. In the Supplemental NOPR, the Commission proposed to direct
that NERC submit a report on the use of footnote 12, due at the end of
the first calendar quarter after the first two years of implementation
of footnote 12 to provide an analysis of the use of footnote 12,
including but not limited to information on the duration, frequency and
magnitude of planned non-consequential load loss, and typical (and if
significant, atypical) scenarios where entities plan for non-
consequential load loss. The Commission proposed that the report should
also address the effectiveness of the stakeholder process and the use
and effectiveness of the local regulatory review and NERC review.\28\
---------------------------------------------------------------------------
\28\ Id. P 20.
---------------------------------------------------------------------------
20. Comments on the Supplemental NOPR were due on June 24, 2013.
NERC, MISO and ITC Companies filed comments in response to the
Supplemental NOPR.
II. Discussion
21. Pursuant to FPA section 215(d), we find that Reliability
Standard TPL-001-4 is just, reasonable, not unduly discriminatory or
preferential, and in the public interest. While NERC's proposal differs
from the Commission directives, we find that NERC adequately addressed
the directives and underlying reliability concerns of Order No. 693,
Order No. 762 and the April 2012 NOPR and, thus, is an equally
effective and efficient alternative to address the Commission's
concerns.\29\ We find that the revised TPL Reliability Standard
improves uniformity and transparency in the transmission planning
process and clarifies the instances where planners may utilize planned
load loss in establishing transmission planning performance
requirements for reliable bulk electric system operations across normal
and contingency conditions. We also find that Reliability Standard TPL-
001-4 will serve as a foundation for annual planning assessments
conducted by planning coordinators and transmission planners to plan
the bulk electric system reliably in response to a range of potential
contingencies. Further, we find that the Reliability Standard presents
clear, measurable, and enforceable requirements that each planning
coordinator and transmission planner must follow when planning its
system.
---------------------------------------------------------------------------
\29\ See Order No. 693, FERC Stats. & Regs. ] 31,242 at P 1792.
---------------------------------------------------------------------------
22. In the Supplemental NOPR, the Commission stated it would issue
a final rule that addresses the consolidated transmission planning
Reliability Standard, TPL-001-4. Therefore, this Final Rule addresses
the modified footnote 12 and comments received in response to the
Supplemental NOPR as
[[Page 63041]]
well as other aspects of the consolidated TPL Reliability Standard
raised in the April 2012 NOPR.
A. Footnote 12 and Planned Use of Non-Consequential Load Loss NOPR
Proposal
23. In the Supplemental NOPR, the Commission proposed to approve
footnote 12. The Commission indicated that the proposal differs from
the Commission directives but adequately addresses the underlying
reliability concerns raised in Order No. 693, Order No. 762 and the
April 2012 NOPR and, thus, is an equally effective and efficient
alternative to address the Commission's directives.\30\ The
Supplemental NOPR indicated that proposed footnote 12 would improve
reliability by providing a blend of specific quantitative and
qualitative parameters for the permissible use of planned non-
consequential load loss to address bulk electric system performance
issues. In addition, the Supplemental NOPR stated that the stakeholder
process appeared to be adequately defined and includes specific
criteria and guidelines that a responsible entity must follow before it
may use planned non-consequential load loss to meet Reliability
Standard TPL-001-4 performance requirements for a single contingency
event. Further, the Supplemental NOPR stated that NERC's proposal
provides reasonable safeguards, including a review process by NERC, to
protect against adverse reliability impacts that could otherwise result
from planned non-consequential load loss.
---------------------------------------------------------------------------
\30\ See Order No. 693, FERC Stats. & Regs. ] 31,242 at P 1792;
Mandatory Reliability Standards for the Bulk Power System, 131 FERC
] 61,231 at P 21.
---------------------------------------------------------------------------
Comments
24. NERC supports the Commission's proposal in the Supplemental
NOPR. NERC also commits to monitor the use of footnote 12 and issue a
report containing the findings of the monitoring by the end of the
first calendar quarter following the first two years of implementation.
ITC Companies believe NERC's proposal is a significant improvement over
the currently-effective standard and support approval. ITC Companies
urge the Commission to clarify that the use of planned non-
consequential load loss should be used rarely and should not be
considered a de facto planning solution.
25. MISO supports Reliability Standard TPL-001-4 as an improvement
over the current standard but has two concerns regarding Attachment 1,
referenced in footnote 12. First, MISO argues that the Commission
should direct NERC to eliminate or clarify the requirement that
requires interaction with and approval by applicable regulatory
authorities or government bodies responsible for retail electric
service. MISO claims that such a requirement adds an additional layer
of complexity and administrative burden to compliance of proposed
Reliability Standard TPL-001-4 without any attendant benefit. According
to MISO, the reference in Attachment 1 to ``applicable regulatory
authorities or governing bodies'' is not clear. MISO states that, while
these terms could encompass a state's public service commission or
public utility commission, the terms could also potentially include
other state bodies or agencies such as consumer advocacy and protection
bodies, state legislatures, and city or municipal bodies. According to
MISO, if these other entities would be considered ``governing bodies
responsible for retail electric issues,'' a transmission planner would
need to seek and receive assurances from each of these bodies. MISO
also suggests that, prior to finalization of its transmission expansion
plan each year, a planner could obtain the assent of the applicable
public utility commission, and yet have its transmission plans
subsequently upended because it did not obtain additional assent from a
different state agency that has some involvement in retail electric
matters.
26. MISO also questions what it means to ensure that an applicable
regulatory authority or governing body ``does not object'' to the
inclusion of non-consequential load loss in the planning process. MISO
suggests that it could mean input of agency staff or a more formal
decision that is voted on by the agency's commissioners. MISO argues
that use of an open stakeholder process that allows for robust input by
any interested parties will ensure that all interested state agencies
will have a say in the process, and that any objections of such
agencies to the inclusion of non-consequential load loss will be
incorporated into the relevant planning decisions.
27. Alternatively, MISO requests that the Commission clarify or
direct NERC to clarify the ``does not object'' language to mean that:
(1) The phrase ``applicable regulatory authorities or governing
bodies'' means only the public utility commission or public service
commission in the affected states, and does not refer to any other
state entity; and (2) comments or other input submitted by the affected
state public service commission or public utility commission in the
Attachment 1 stakeholder process indicating that the agency ``does not
object'' to the inclusion of non-consequential load loss in the
planning process are sufficient to satisfy the ``does not object''
requirement.
28. Further, MISO requests that the Commission clarify, or direct
NERC to clarify, the language in section II of Attachment 1 that
requires planning coordinators and transmission planners to provide
stakeholders all assessments of ``potential overlapping uses of
footnote 12 including overlaps with adjacent Transmission Planners and
Planning Coordinators.'' MISO believes that this phrase suggests that
there are other ``potential overlapping uses'' that are encompassed by
the requirement. MISO states it is not clear what these other
overlapping uses might be or how they might be incorporated into the
planning process.
Commission Determination
29. We approve Reliability Standard, TPL-001-4 with footnote 12
because it satisfies the concerns raised in the Supplemental NOPR.
Footnote 12 provides a blend of specific quantitative and qualitative
parameters for the permissible use of planned non-consequential load
loss to address bulk electric system performance issues, including firm
limitations on the maximum amount of load that an entity may plan to
shed, safeguards to ensure against inconsistent results and arbitrary
determinations that allow for the planned non-consequential load loss,
and a more specifically defined, open and transparent, verifiable, and
enforceable stakeholder process. Use of planned non-consequential load
loss should be rare and must be used consistent with the process
established here.
30. We disagree with MISO that Attachment 1 to footnote 12 adds an
additional layer of complexity and administrative burden to compliance
without any attendant benefit. Commenters have stated in prior
proceedings that a blend of quantitative and qualitative parameters
``should not overly burden NERC or Regional Entity resources as
utilization of the planned load shed exception is--and would be--rarely
utilized.'' \31\ Further, the Commission directs NERC to report on the
use of footnote 12 including the use and effectiveness of the local
regulatory review and NERC review. This report is important because it
will provide an analysis of the use of footnote 12, including but not
limited to information on the duration, frequency and
[[Page 63042]]
magnitude of planned non-consequential load loss, and typical (and if
significant, atypical) scenarios where entities plan for non-
consequential load loss. Further, the report will serve as a tool to
evaluate the usefulness and effectiveness of local regulatory and ERO
review, and identify whether MISO's concern or other issues arise that
need to be addressed.
---------------------------------------------------------------------------
\31\ Order No. 762, 139 FERC ] 61,060 at P 55.
---------------------------------------------------------------------------
31. We decline to direct NERC to limit the meaning of the phrase
``applicable regulatory authorities or governing bodies.'' Because each
state and locality has different entities that are responsible for
reliability of retail electric service, we are reluctant to further
define who may participate. NERC's report should identify any issues
with respect to how effective and efficient the review process is
working. With regard to MISO's request that input by the affected
regulatory body is sufficient to satisfy the language in the Attachment
1 stakeholder process indicating that the agency ``does not object'' to
the inclusion of non-consequential load loss, we note that during the
standard development process NERC ``modified the footnote to require
regulatory authority review rather than approval.'' \32\ Use of an open
stakeholder process that allows for robust input and review will ensure
that all interested state agencies will have a say in the process, and
that any objections of such agencies to the inclusion of non-
consequential load loss will be considered in the relevant planning
decisions. With regard to MISO's requested clarification of the phrase
``potential overlapping uses,'' we note that Attachment 1 section II
encompasses potential overlapping uses of footnote 12 either within the
responsible entity or with adjacent transmission planners and planning
coordinators.\33\ Accordingly, no further clarification is required.
---------------------------------------------------------------------------
\32\ NERC's Petition, Exhibit H, Consideration of Comments,
period from July 31, 2012 through August 29, 2012 at 73.
\33\ Proposed TPL-001-4 Reliability Standard, Attachment 1,
section II, category 8: ``Assessment of potential overlapping uses
of footnote 12 including overlaps with adjacent Transmission
Planners and Planning Coordinators.''
---------------------------------------------------------------------------
B. Reliability Issues Raised in the April 2012 NOPR
32. In the April 2012 NOPR, the Commission sought comments
regarding the following issues regarding the proposed Version 2
Reliability Standard: (1) Planned maintenance outages, (2) violation
risk factors, (3) protection system failures versus relay failures, (4)
assessment of backup or redundant protection systems, (5) single line
to ground faults and (6) Order No. 693 directives. The Version 4 TPL
standard that we approve in this Final Rule contains the same
provisions as the Version 2 standard, with the exception of footnote
12, Attachment 1 and the VRF for Requirement R6. Accordingly, we
address below the issues raised in the April 2012 NOPR.
1. Planned Maintenance Outages NERC Petition
33. NERC proposed new language in TPL-001-2, Requirement R1 to
remove an ambiguity in the current standard concerning what the planner
needs to include in the specific studies. Requirement R1 also requires
the planner to evaluate six-month or longer duration planned outages
within its system. NERC states that, while Requirement R1.3.12 of the
currently-effective TPL-002-0b includes planned outages (including
maintenance outages) in the planning studies and requires simulations
at the demands levels for which the planned outages are performed, it
is not appropriate to have the planner select specific planned outages
for inclusion in their studies.\34\ Consequently, NERC proposes a
bright-line test to determine whether a planned outage should be
included in the system models.
---------------------------------------------------------------------------
\34\ NERC's October 2011 Petition at 35.
---------------------------------------------------------------------------
NOPR
34. In the April 2012 NOPR, the Commission expressed concern that,
under proposed Requirement R1, planned maintenance outages with a
duration of less than six months would be excluded from future planning
assessments. As a result, any potential impact to bulk electric system
reliability from these outages would be unknown.\35\ The Commission
sought comment on whether the proposed six month threshold would
materially change the number of planned outages included in planning
assessments compared to the number included in planning assessments
under the currently-effective standard, and whether the threshold would
exclude nuclear plant refueling, large fossil and hydro generating
station maintenance, and spring and fall transmission construction
projects from future planning assessments. The Commission also sought
comment on possible alternatives.
---------------------------------------------------------------------------
\35\ April 2012 NOPR, 139 FERC ] 61,059 at P 18.
---------------------------------------------------------------------------
35. In the NOPR, the Commission noted that, with respect to
protection system maintenance, currently-effective Reliability Standard
TPL-002-0, Requirement R1.3.12 requires the planner to ``[i]nclude the
planned (including maintenance) outage of any bulk electric equipment
(including protection systems or their components) at those demand
levels for which planned (including maintenance) outages are
performed.'' \36\ NERC explained in the petition that this language did
not carry over because protection system maintenance or other outages
are not anticipated to last six months. The Commission indicated in the
NOPR that it is critical to plan the system so that a protection system
can be removed for maintenance and still be operated reliably and
sought comment on whether protection systems are necessary to be
included as a type of planned outage.
---------------------------------------------------------------------------
\36\ Reliability Standard TPL-002-0, Requirement R1.3.12.
---------------------------------------------------------------------------
Comments
36. NERC and EEI state that the proposed Reliability Standard will
not materially change the number of planned outages that must be
reflected in initial system conditions as compared to the existing
standards. NERC states that applying existing Requirement R1.3.12,
planners have traditionally only included those planned outages in
their category ``P0 or N-0'' system condition that resulted from
catastrophic equipment failures or extended outage conditions
associated with construction or maintenance projects that place their
system in an abnormal starting condition.\37\ NERC believes that going
beyond those scenarios would consider ``hypothetical planned outages,''
and doing so in a planning study horizon would introduce multiple
contingency conditions within the existing standard. Further, NERC
states that planners will establish sensitivity cases around key
generation unit outages, and when applying the category P3 planning
event to those sensitivity cases, it will further cover multiple
generator unit outages. Similarly, transmission maintenance outages are
covered in the planning events when applying the category P6 planning
events.
---------------------------------------------------------------------------
\37\ Table 1 of the TPL Reliability Standard contains a series
of planning events and describes system performance requirements and
lists seven categories of contingency planning events, identified as
P0 through P6. P0 is the ``No Contingency,'' normal system
condition. Reliability Standard TPL-001-4, Table 1.
---------------------------------------------------------------------------
37. BPA believes the six-month planned outage window is workable
but that it may be too short to consider in system planning models and
suggests a one-year planned outage window. BPA states that planned
outages with duration of less than one year should be
[[Page 63043]]
dealt with operationally by determining new operating limits and taking
other actions to mitigate the planned outage. According to Hydro One,
it is not necessary to include planned outage of less than six months
since long-term planning is intended to assess transmission expansion
needs in the usual three to ten year timeframe. Hydro One states that
the inclusion of planned outages of less than six months will not
increase the accuracy of the results as these are moving targets and
there are operational planning measures to provide the required
transmission transfer capability to meet forecast demand.
38. On the other hand, ITC Companies, MISO and ATCLLC express
concern that some planned outages of less than six months are relevant
and should not be eliminated from consideration in planning
evaluations. ATCLLC states that, although the number of planned outages
may not materially change, the impact of eliminating pertinent planned
outages of less than six months in duration is perhaps more material
than the impact of outages six months in duration or longer. Some
planned outages of less than six months in duration may also result in
relevant impacts during one or both of the seasonal off-peak periods.
ITC Companies state that, in some instances, certain transmission
elements may be so critical that when taken out of service for system
maintenance or to facilitate a new capital project, a subsequent single
unplanned transmission outage could result in the loss of firm system
load. ITC Companies adds that including only known maintenance outages
of six months or longer in the transmission models could be a step
backwards from the current standard. Since these unplanned outages can
have consequential impacts on transmission customers, prudent
transmission planning should include providing an adequate transmission
system to avoid these undesired outcomes.
39. MISO suggests that limiting planning studies to only include
known outages of generation or transmission with duration of at least
six months may have a detrimental impact to bulk electric system
reliability. According to MISO, proper transmission system planning
should ensure that the removal of a facility for maintenance purposes
can be accomplished without the need to deny or re-schedule such
maintenance to prevent the loss of firm load resulting from the types
of contingencies enumerated in the TPL Reliability Standards. MISO
requests that the Commission direct NERC to further expand the base
planning conditions and assumptions by requiring inclusion of
unscheduled, planned outages of any element when applying at a minimum
P0 and P1 events to the off-peak cases.
Commission Determination
40. Pursuant to section 215(d)(5) of the FPA, we direct NERC to
modify Reliability Standard TPL-001-4 to address the concern that the
six month threshold could exclude planned maintenance outages of
significant facilities from future planning assessments.
41. For the reasons discussed below, the Commission finds that
planned maintenance outages of less than six months in duration may
result in relevant impacts during one or both of the seasonal off-peak
periods. Prudent transmission planning should consider maintenance
outages at those load levels when planned outages are performed to
allow for a single element to be taken out of service for maintenance
without compromising the ability of the system to meet demand without
loss of load.\38\ We agree with commenters such as MISO and ATCLLC that
certain elements may be so critical that, when taken out of service for
system maintenance or to facilitate a new capital project, a subsequent
unplanned outage initiated by a single-event could result in the loss
of non-consequential load or may have a detrimental impact to the bulk
electric system reliability. A properly planned transmission system
should ensure the known, planned removal of facilities (i.e.,
generation, transmission or protection system facilities) for
maintenance purposes without the loss of non-consequential load or
detrimental impacts to system reliability such as cascading, voltage
instability or uncontrolled islanding.
---------------------------------------------------------------------------
\38\ ITC Companies Comments at 5.
---------------------------------------------------------------------------
42. We remain concerned that proposed Reliability Standard TPL-001-
4 will materially change the number of planned outages that must be
reflected in initial system conditions as compared to the existing
standards. Planned outages lasting less than six months are common, and
yet could be overlooked for planning purposes under the proposal. These
planned outages are not ``hypothetical planned outages,'' and should
not be treated as multiple contingency conditions within the planning
standard. The Commission's directive is to include known generator and
transmission planned maintenance outages in planning assessments, not
hypothetical planned outages.
43. While NERC has flexibility on how to address the identified
concern, we believe that acceptable approaches include eliminating the
six-month threshold altogether; decreasing the threshold to fewer
months to include additional significant planned outages; or including
parameters on what constitutes a significant planned outage based, for
example, on MW or facility ratings.
44. Further, we disagree with NERC's position that category P3
contingencies cover generator maintenance outages and category P6
covers transmission maintenance outages. P3 and P6 both consist of
multiple contingencies, e.g., loss of a generating unit or transmission
circuit followed by system adjustments and then the loss of another
generator or transmission circuit. In approving NERC's interpretation
of Requirement R1.3.12 of TPL-002-0 and TPL-003-0, the Commission
stated that ``planned (including maintenance) outages are not
contingencies and are required to be addressed in transmission planning
for any bulk electric equipment at demand levels for which the planned
outages are performed.'' \39\ The Commission further stated that it
``understands that planned maintenance outages tend to be for a
relatively short duration and are routinely planned at a time that
provides favorable system conditions, i.e., off-peak conditions. Given
that all transmission and generation facilities require maintenance at
some point during their service lives, these `potential' planned
outages must be addressed, so long as their planned start times and
durations may be anticipated as occurring for some period of time
during the planning time [horizon]'' required in the TPL Reliability
Standards.\40\
---------------------------------------------------------------------------
\39\ North American Electric Reliability Corp., 131 FERC ]
61,068, at P 39 (2010) (approving interpretation of Reliability
Standards TPL-002-0 and TPL-003-0).
\40\ Id. P 39.
---------------------------------------------------------------------------
45. With regard to BPA's comment, we disagree that planned outages
of less than one year in duration should be addressed operationally by
determining new operating limits and taking other actions to mitigate
the planned outage. The Commission understands that some planned
outages such as planned generation outages are known more than one year
in advance.\41\ As a result, the Commission believes the planning time
horizon of the TPL Reliability Standards offers more flexibility to
assess planned maintenance outages than the
[[Page 63044]]
operational time horizon. Further, we disagree with Hydro One's comment
that including planned outages of less than six months is unnecessary
since long-term planning to assess transmission expansion occurs in the
three to ten year timeframe. The Commission recognizes that the TPL-
001-4 Reliability Standard addresses near-term and long-term
transmission planning horizons and, for the near-term horizon, requires
annual assessments for years one through five. Accordingly, known
planned facility outages (i.e. generation, transmission or protection
system facilities) of less than six months should be addressed so long
as their planned start times and durations may be anticipated as
occurring for some period of time during the planning time horizon.
---------------------------------------------------------------------------
\41\ See, e.g., Commissioner-Led Reliability Technical
Conference, Docket Nos. AD13-6-000, RC11-6-004, RR13-2-000, July 9,
2013, Volume I at 242.
---------------------------------------------------------------------------
2. Violation Risk Factors
a. Requirement R1
NERC Petition
46. NERC assigned a ``medium'' violation risk factor (VRF) for
proposed Requirement R1. NERC maintains that Requirements R1.3.5,
R1.3.7, R1.3.8, and R1.3.9 of the currently-effective Reliability
Standard carry a VRF of ``medium'' and are similar in purpose and
effect to proposed Reliability Standard, Requirement R1 because they
refer to planning models that include firm transfers, existing and
planned facilities, and reactive power requirements.\42\
---------------------------------------------------------------------------
\42\ NERC October 2011 Petition at Exhibit C, Table 1.
---------------------------------------------------------------------------
NOPR Proposal
47. In the April 2012 NOPR, the Commission expressed that, if
system models are not properly modeled or maintained, the analysis
required in the Reliability Standard that uses the models in
Requirement R1 may lose their validity and could directly cause or
contribute to Bulk-Power System instability, separation, or a cascading
sequence of failures, or could place the Bulk-Power System at an
unacceptable risk of instability, separation, or cascading, or hinder
restoration to a normal condition.\43\ The Commission noted that
Requirement R1 of the Version 0 TPL Standard, which is assigned a
``high'' VRF, explicitly establishes Category A as the normal system in
Table 1, which also creates the model of the normal system prior to any
contingency and stated its belief that Requirement R1 of the proposed
Reliability Standard and Requirement 1 of currently-effective standard
both establish the normal system planning model that serves as the
foundation for all other conditions and contingencies that are required
to be studied and evaluated in a planning assessment. In the NOPR, the
Commission sought comment on why Requirement R1 of proposed Reliability
Standard carries a VRF of ``medium'' while Requirement R1 of the
currently-effective standard carries a VRF of ``high.''
---------------------------------------------------------------------------
\43\ April 2012 NOPR, 139 FERC ] 61,059 at P 21.
---------------------------------------------------------------------------
Comments
48. NERC states that Requirement R1 of the currently-effective
standard directly relates to Requirement R2 of the proposed standard,
which has a High VRF. NERC states that Requirement R1 of the proposed
standard is a new requirement that addresses the models needed for
planning assessments and therefore can have a different VRF. NERC
states that while the accuracy of the transmission system model plays a
key role in the TPL Reliability Standards, it is ``a model, an
approximation constructed and built with multiple entity inputs within
a controlled process (e.g., Multiregional Model Working Group).'' \44\
NERC states the base model in proposed Requirement R1 must be modified
by adjusting load forecasts and generation dispatch to better assess
the range of probable outcomes that the transmission system may
experience for various contingency scenarios.
---------------------------------------------------------------------------
\44\ NERC Comments at 8.
---------------------------------------------------------------------------
49. ISO/RTOs state that proposed Requirement R1 relates to model
maintenance, a necessary condition to being able to perform an
assessment, which is a different matter from the current Requirement
R1. According to ISO/RTOs Requirement R1 of the currently-effective
standard, relating to performing an assessment, corresponds to
Requirement R2 of the proposed standard, both of which carry a VRF of
``high.''
50. EEI does not believe that proposed Requirement R1 aligns with
Requirement R1 of the currently-effective standard. According to EEI,
however, Requirement R1 does obligate ``Transmission Planners and
Planning Coordinators to maintain system models within their respective
area for performing studies needed to complete its Planning
Assessments.'' \45\ EEI further notes that these studies establish a
baseline (Category P0) by which all other studies are based. EEI
advocates that, if this requirement is not adhered to, faulty studies
could result, possibly leading to misoperation of the system. For this
reason, EEI believes the VRF was improperly categorized as a medium
risk VRF and suggests consideration be given to increasing the VRF to
``high.''
---------------------------------------------------------------------------
\45\ EEI Comments at 5.
---------------------------------------------------------------------------
Commission Determination
51. We direct NERC to modify Reliability Standard TPL-001-4,
Requirement R1 and change its VRF from medium to high. As discussed in
the April 2012 NOPR, Requirement R1 establishes the normal system
planning model that serves as the foundation for all other conditions
and contingencies that are required to be studied and evaluated in a
planning assessment. The Commission agrees with EEI that if the
baseline studies established in Requirement R1 are not adhered to,
faulty studies could result, possibly leading to misoperation of the
system.
52. The Commission is not persuaded by NERC's argument that
Reliability Standard TPL-001-4, Requirement R1 warrants a medium VRF
because the base model in Requirement R1 must be modified by adjusting
load forecasts and generation dispatch for various contingency
scenarios. Rather, the Commission finds that Requirement R1 and its
sub-parts require system models to represent projected system
conditions including items such as resources required for load, and
real and reactive load forecasts, all of which ``establishes Category
P0 as the normal condition in Table 1.'' \46\ Although the Commission
agrees with NERC that the accuracy of the system model plays a key role
in the TPL Reliability Standards and that a system model is ``a model,
an approximation constructed and built with multiple entity inputs
within a controlled process,'' the Commission finds that the system
model of Requirement R1 establishes a baseline (Category P0) for which
all other studies are based and if not adhered to, faulty studies could
result, possibly leading to misoperation of the system.
---------------------------------------------------------------------------
\46\ NERC's February 2013 Petition, Exhibit A, TPL-001-4,
Requirement R1.
---------------------------------------------------------------------------
53. Further, the Commission disagrees with ISO/RTOs that proposed
Requirement R1 is a different matter from the current Requirement R1.
The Commission stated in the April 2012 NOPR that Requirement R1 of the
Version 0 TPL Standard, which is assigned a ``high'' VRF, explicitly
establishes Category A as the normal system in Table 1 that serves as
the foundation for all other conditions and contingencies that are
required to be studied and evaluated in a planning assessment.
Accordingly, the Commission believes that TPL-001-4, Requirement R1
similarly establishes
[[Page 63045]]
Category P0 as the normal system in Table 1 that serves as the
foundation for all other conditions and contingencies that are required
to be studied and evaluated in a planning assessment. For these
reasons, the Commission directs NERC to modify the VRF assigned to
Requirement R1 from medium to high.
b. VRF for Requirement R6
NERC Petition
54. NERC proposed to assign a ``low'' VRF for Requirement R6 \47\
because ``failure to have established criteria for determining System
instability is an administrative requirement affecting a planning time
frame.'' \48\ NERC explains that Requirement R6 is a new requirement
and that violations would not be expected to adversely affect the
electrical state or capability of the bulk electric system.
---------------------------------------------------------------------------
\47\ NERC's February 2013 Petition, Exhibit A, TPL-001-4,
Requirement R6 states ``[e]ach Transmission Planner and Planning
Coordinator shall define and document, within their Planning
Assessment, the criteria or methodology used in the analysis to
identify System instability for conditions such as Cascading,
voltage instability, or uncontrolled islanding.''
\48\ NERC's October 2011 Petition, Exhibit C, at 110.
---------------------------------------------------------------------------
NOPR Proposal
55. In the NOPR, the Commission recognized that documenting
criteria or methodology is an administrative act but stated that
defining the criteria or methodology to be used is not an
administrative act. The Commission sought clarification why the VRF
level assigned to Requirement R6 is ``low'' since it appears that
Requirement R6 requires more than a purely administrative task.
Comments
56. NERC agrees that proposed TPL-001-2 Requirement R6 is not
strictly an administrative task, and therefore the VRF should be
adjusted to medium. In its February 28, 2013 Petition, NERC revised the
VRF for Reliability Standard TPL-001-4, Requirement R6 from low to
medium.
57. EEI and ISO/RTOs contend that Requirement R6 was correctly
assigned a ``low'' VRF because ``defining and documenting'' is an
administrative task. According to EEI, the fact that the planner poorly
documented the criteria and methodology does not mean that their
assessment was not conducted appropriately or that it placed the bulk
electric system at risk.
Commission Determination
58. The Commission agrees with NERC that TPL-001-4, Requirement R6
is not strictly an administrative task and approves the change from a
low VRF to a medium VRF. The Commission disagrees with commenters that
TPL-001-4 Reliability Standard, Requirement R6 is purely an
administrative task of documentation of criteria and methodologies.
Requirement R6 goes beyond documentation by requiring planners to apply
engineering judgment and analysis to ``define[hellip]the criteria or
methodology used in the analysis to identify system instability for
conditions such as cascading, voltage instability or uncontrolled
islanding.'' \49\
---------------------------------------------------------------------------
\49\ Proposed TPL-001-4 Reliability Standard, Requirement R6.
---------------------------------------------------------------------------
3. Protection System Failures versus Relay Failures
NERC Petition
59. NERC's proposal includes modifications to the planning
contingency categories in Table 1. NERC explains that the modifications
are intended to add clarity and consistency regarding the modeling of a
delayed fault clearing in a planning study. NERC stated that the basic
elements of any protection system design involve inputs to protective
relays and outputs from protective relays and that reliability issues
associated with improper clearing of a fault on the bulk electric
system can result from the failure of hundreds of individual protection
system components in a substation. According to NERC, while the
population of components that could fail and result in improper
clearing is large, the population can be reduced dramatically by
eliminating those components which share failure modes with other
components. NERC stated that the critical components in protection
systems are the protective relays themselves, and a failure of a non-
redundant protective relay will often result in undesired consequences
during a fault. According to NERC, other protection system components
related to the protective relay could fail and lead to a bulk electric
system issue, but the event that would be studied is identical, from
both transient and steady state perspectives, to the event resulting
from a protective relay failure if an adequate population of protective
relays is considered.\50\
---------------------------------------------------------------------------
\50\ NERC's October 2011 Petition at 48.
---------------------------------------------------------------------------
NOPR Proposal
60. In the April 2012 NOPR, the Commission expressed that, based on
various protection system designs, the planner will have to choose
which protection system component failure would have the most
significant impact on the Bulk-Power System because as-built designs
are not standardized and the most critical component failure may not
always be the relay.\51\ The Commission sought comment on whether the
proposed provisions pertaining to study of multiple contingencies
limits the planners' assessment of a protection system failure because
the proposed provisions only include the contingency of a faulty relay
component. The Commission also sought comment on whether the relay is
always the larger contingency and how the loss of protection system
components that is integral to multiple protection systems impacts
reliability.
---------------------------------------------------------------------------
\51\ April 2012 NOPR, 139 FERC ] 61,059 at P 31.
---------------------------------------------------------------------------
Comments
61. NERC states that the proposed Reliability Standard addresses
the existing ambiguity requiring a study of a stuck breaker or
protection system failure by specifying that both a stuck breaker and
protection system failure must be evaluated. NERC states that its
solution ensures that simulations of both categories are performed,
reducing the probability of multiple contingency events leading to
cascading and uncontrolled islanding. Similarly, Hydro One and EEI
contend that a planner does not need to choose which protection system
component failure would have the most significant impact on the Bulk-
Power System in the planning assessment. According to Hydro One, the
contingencies stipulated in Table 1, P5 of the proposed TPL Standard
are appropriate for the conditions and events to be assessed in the P5
groups which focus on the combination of a single line to ground fault
coupled with delayed clearing that may be caused by a protection system
failing to open to clear the fault. Hydro One also states that what
causes the protection system to fail is irrelevant in the context of
delayed clearing by the backup protection system to clear the fault.
EEI expresses concern that expanding planning studies to include all
manner of protection system failures could create a scenario where
planners would have to conduct unlimited and unbounded studies.';
62. In contrast, MISO agrees with the NOPR that the more severe or
larger contingency may not be assessed because the proposed Reliability
Standard limits the planners' assessment of a protection system failure
since it only includes the contingency of a faulty relay component.
MISO suggests expanding the assessment of relay failures to
[[Page 63046]]
include all components of a protection system, including instrument
transformers, protective relays, auxiliary relays and communications
systems.
63. With regard to the Commission's question whether, based on
protection system as-built designs, the relay may not always be the
larger contingency, NERC states that the proposed Table 1, category P5
(fault plus relay failure to operate) planning event requires
evaluation of the failure of the protection system relays whose failure
is most likely to cause cascading or uncontrolled islanding of the bulk
electric system.
64. Hydro One recognizes that a number of components necessary to
operate properly may fail to render a protection system failing to
operate when needed, and that such component failures may result in
disabling more than one protective relay and the impact of multiple
relay failures may be more severe than the SLG fault on a bulk electric
system facility with delayed clearing. According to Hydro One, the more
severe consequences of an initial bulk electric system facility
contingency combined with multiple or more severe protection system
failures would more appropriately be considered or included in the
extreme events category.
65. ISO/RTOs agree that the range of potential assessments should
be expanded to include all components of a protection system including
instrument transformers, protective relays, auxiliary relays and
communications systems for the purpose of category P-5 contingencies,
but because these devices are often in series, consideration of all of
these components will not necessarily have any significant impact on
analyses.
66. With regard to the question of how does the loss of a
protection system component integral to multiple protection systems
impact reliability, NERC states that the loss of a relay that is
integral to multiple protection systems would require simulation of the
full impact of that relay's failure on the system for the event being
studied under the category P5 planning event. With respect to whether
there is a reliability concern regarding single points of failure on
protection systems, NERC indicates that it has a project underway to
assess that question.\52\
---------------------------------------------------------------------------
\52\ NERC Comments at 10.
---------------------------------------------------------------------------
67. Hydro One views the avoidance of having single component
failure affecting more than one protection system as a protection
system design issue. Hydro One states that some regional reliability
organizations have in place criteria to ensure protection systems
operate properly and to avoid failure of a single component affecting
multiple protection systems.
Commission Determination
68. The Commission agrees with NERC's statement that Reliability
Standard-TPL-001-4 addresses the existing ambiguity of the currently-
effective TPL Reliability Standards requiring a study of a stuck
breaker or protection system failure. We find that Reliability Standard
TPL-001-4, specifying that both a stuck breaker and a relay failure
must be evaluated, is reasonable to remove the ambiguity. Further, as
explained by NERC, the loss of a relay that is integral to multiple
protection systems would require simulation of the full impact of that
relay's failure on the system for the event being studied under the
category P5 planning event. In addition, Reliability Standard TPL-001-4
requires study and evaluation of both a stuck breaker (Table 1,
Category P4) and a relay failure (Table 1, Category P5) and that
simulations of both categories reduce the probability of multiple
contingency events leading to cascading, instability or uncontrolled
islanding.
69. The Commission does not find the need to take any further
action with regard to this issue. We note, however, that an assessment
of a relay component failure may not necessarily assess the more severe
or larger contingency, compared to a protection system failure under
the currently-effective TPL Standards. Based on various protection
system as-built designs, NERC has indicated that the planner should use
``engineering judgment in its selection of the protection system
component failures for evaluation that would produce the more severe
system results or impact. . . . The evaluation would include addressing
all protection systems affected by the selected component. A protection
system component failure that impacts one or more protection systems
and increases the total fault clearing time requires the [planner] to
simulate the full impact (clearing time and facilities removed) on the
Bulk Electric System performance.'' \53\ However, the Commission will
not direct NERC to modify the standard at this time, pending completion
of NERC's work on single points of failure on protection systems.\54\
---------------------------------------------------------------------------
\53\ NERC Petition For The Approval of An Interpretation to
Reliability Standards TPL-003-0a and TPL-004-0, April 12, 2013 at
13, Docket No. RD13-8-000, approved by unpublished letter order June
20, 3013.
\54\ March 15, 2012 NERC Informational Filing in Docket No.
RM10-6-000 at 5, 7, stating that NERC has initiated a data request
to evaluate potential exposure to types of protection system
failures.
---------------------------------------------------------------------------
4. Assessment of Backup or Redundant Protection Systems NOPR Proposal
70. Requirement R3, Part 3.3.1 and Requirement R4, Part 4.3.1 of
Reliability Standard TPL-001-4 require that simulations duplicate what
will happen in an actual power system based on the expected performance
of the protection systems.\55\ According to NERC, these requirements
ensure that, for a protection system designed ``to remove multiple
Elements from service for an event that the simulation will be run with
all of those Elements removed from service.'' \56\ In the NOPR, the
Commission observed that these provisions do not explicitly refer to
``backup or redundant systems'' as in the currently-effective
Reliability Standards and sought clarification whether the proposal
includes backup and redundant protection systems.
---------------------------------------------------------------------------
\55\ NERC's October 2011 Petition at 20.
\56\ Id.
---------------------------------------------------------------------------
Comments
71. NERC clarifies that proposed Requirement R3, Part 3.3.1 and
Requirement R4, Part 4.3.1 ``require the consideration of all
protection systems that are relevant to the contingency studied,''
which includes ``backup and redundant systems.'' \57\ EEI believes that
the language is sufficiently clear to ensure a common understanding
that backup and redundant protection system impacts needed to be
studied regardless of whether the specific words as found in the
currently active standard were used. ISO/RTOs and MISO believe that if
a protection system is not fully redundant, contingencies should be
studied to simulate both delayed clearing and operation of remote
backup protection to trip additional facilities when required. MISO
states that if a protection system is fully redundant, that is, if a
single failure of any component in the protection system (other than
monitored DC voltage) would not result in delayed or failed tripping it
should not be necessary to analyze the redundant protection system
failure.
---------------------------------------------------------------------------
\57\ NERC Comments at 11.
---------------------------------------------------------------------------
Commission Determination
72. The Commission agrees with NERC and finds that Requirement R3,
Part 3.3.1 and Requirement R4, Part 4.3.1 include the assessments of
backup protection systems. The Commission
[[Page 63047]]
agrees with ISOs/RTOs and MISO that if a primary protection system has
a fully redundant backup protection system, assessments of the primary
protection system is required, but not of the fully redundant backup
protection system since the assessment results will be identical.
Further, we agree that if a protection system is not fully redundant,
contingencies are studied to simulate both delayed clearing and
operation of remote backup protection which may trip additional
facilities when required.
P5 Single Line to Ground Faults
NOPR Proposal
73. In the April 2012 NOPR, the Commission sought clarification
whether ``fault types'' in Table 1 refers to the initiating event.\58\
---------------------------------------------------------------------------
\58\ April 2012 NOPR, 139 FERC ] 61,059 at P 38.
---------------------------------------------------------------------------
Comments
74. NERC, EEI, BPA and ISO/RTOs all concur that ``fault types''
refer to the initiating fault to be studied, not to what the fault may
evolve into as a result of the simulated conditions. According to NERC,
the possibility of a single-line-to-ground fault evolving into a three-
phase fault is addressed by requiring the study of a three-phase fault
as the initial fault.
Commission Determination'
75. The Commission finds that the explanation of NERC and others,
i.e., ``fault types'' in Reliability Standard TPL-001-4, Table 1--
Steady State & Stability Performance Planning Events means the type of
fault that initiated the event, is reasonable. For example, if the
initiating fault type is a single-line-to-ground fault and it evolves
into a three-phase fault, the single-line-to-ground fault is still
evaluated as the initiating fault type. If a three-phase fault occurs
as the initiating event, the fault is assessed as a three phase fault.
Regardless of what the initiating fault type becomes, it does not
change the initiating fault type.
6. Order No. 693 Directives
76. In the April 2012 NOPR, the Commission indicated that the
Version 4 TPL Standard appeared responsive to the Order No. 693
directives regarding the TPL Reliability Standards. However, the
Commission sought clarification and comment on the following issues:
(a) Peer review of planning assessments, (b) spare equipment strategy,
(c) range of extreme events, (d) footnote `a' and (e) controlled load
interruption, dynamic load models and proxies to simulate cascade.\59\
---------------------------------------------------------------------------
\59\ April 2012 NOPR, 139 FERC ] 61,059 at PP 39-54.
---------------------------------------------------------------------------
77. The Commission is satisfied and agrees with the comments
submitted by NERC, EEI and ISO/RTO on issues regarding controlled load
interruption (i.e., third parties must have the same non-consequential
load loss options as available to the planner), dynamic load models
(i.e., documentation of dynamic load models used in system studies and
the supporting rationale for their use is required) and proxies to
simulate cascade (i.e., planners must define and document their
criteria or methodology including proxies that are used in planning
assessments due to modeling and simulation limitations). Below, we
address in greater detail the comments on peer review of planning
assessments, spare equipment strategy, range of extreme events, and
footnote `a.'
a. Peer Review of Planning Assessments
NOPR Proposal
78. The Commission stated in Order No. 693 that, because
neighboring systems may adversely impact one another, such systems
should be involved in determining and reviewing system conditions and
contingencies to be assessed under the currently-effective TPL
Reliability Standards.\60\ In its petition, NERC stated the proposed
Reliability Standard does not include a ``peer review'' of planning
assessments but instead includes an equally effective and efficient
manner to provide for the appropriate sharing of information with
neighboring systems in proposed Requirement R3, Part 3.4.1, Requirement
R4, Part 4.4.1, and Requirement R8.\61\
---------------------------------------------------------------------------
\60\ Order No. 693, FERC Stats. & Regs. ] 31,242 at P 1750.
\61\ NERC's October 2011 Petition at 21.
---------------------------------------------------------------------------
79. In the April 2012 NOPR, the Commission sought clarification on
how the NERC proposal ensures the early input of peers into the
planning assessments or any type of coordination among peers will
occur. The Commission also sought comment on whether and how
neighboring systems can sufficiently evaluate and provide feedback to
the planners on the development and result of assessments and whether
it requires input on the comments to be included in the results or the
development of the planning assessments.
Comments
80. NERC and EEI state that, prior to sharing planning assessment
results in Requirement R8, Requirement R3, Part 3.4.1 and Requirement
R4, Part 4.4.1 require planners to coordinate with adjacent planners to
develop contingency lists for steady state and stability analysis. EEI
states it is most beneficial to planners if coordination occurs earlier
in the planning assessment process.
81. NERC and EEI also explain that Requirements R2 through R6
provide adjacent entities sufficient information on how the assessment
was performed and expected system performance to effectively evaluate
the assessment results and to provide feedback. Further, Requirement R8
requires that each planner must distribute its planning assessment
results to adjacent planners within 90 calendar days of completing its
assessment.
82. 1BPA states that, while adjacent planners and coordinators
should have a stake in the results of an affected planning assessment,
they should not be allowed to second guess the transmission planner's
or planning coordinator's studies and methodologies. BPA adds that it
is important for adjacent planners to have input on how other planning
assessments will affect them, and the proposed Reliability Standards
allows such input.
Commission Determination
83. The Commission agrees with NERC and EEI that coordination of
contingency lists with adjacent planners under TPL-001-4 Reliability
Standard, Requirement R3, Part 3.4.1 and Requirement R4, Part 4.4.1
ensures that contingencies on adjacent systems that impact other
systems are developed and included in the planners' steady state and
stability analysis planning assessments.\62\ Coordination of
contingency lists provides one aspect of early coordination among
planners.
---------------------------------------------------------------------------
\62\ Because neighboring systems may be adversely impacted by
other systems, such systems should be involved early in determining
and reviewing conditions and contingencies in planning assessments.
Order No. 693, FERC Stats. & Regs. ] 31,242 at PP 1750, 1754.
---------------------------------------------------------------------------
84. We are satisfied with the explanation of NERC and EEI that TPL-
001-4 Reliability Standard, Requirement R8 allows planners to
coordinate and distribute conditions to adjacent planners as part of
their planning assessment and to provide feedback to other planners.
While we also agree with BPA that adjacent planners should be informed
of and have a stake in the results of another planner's assessment, we
disagree with BPA's characterization that a planner ``should not be
allowed to second guess'' another planner's studies or
[[Page 63048]]
methodologies. Rather, early peer input in the planning assessments and
coordination among peers to identify possible interdependent or adverse
impacts on neighboring systems are essential to the reliable operation
of the bulk electric system.\63\
---------------------------------------------------------------------------
\63\ Order No. 693, FERC Stats. & Regs. ] 31,242 at P 1754:
``Given that neighboring systems assessments by one entity may
identify possible interdependant or adverse impacts on its
neighboring systems, this peer review will provide an early
opportunity to provide input and coordinate plans.''
---------------------------------------------------------------------------
Spare Equipment Strategy
NOPR Proposal
85. In Order No. 693, the Commission directed NERC to develop a
modification ``to require assessments of outages of critical long lead-
time equipment, consistent with the entity's spare equipment
strategy.'' \64\ In response, NERC developed proposed Requirement 2,
Part 2.1.5 which addresses steady state conditions to determine system
response when equipment is unavailable for prolonged periods of time.
---------------------------------------------------------------------------
\64\ Order No. 693, FERC Stats. & Regs. ] 31,242 at P 1786.
---------------------------------------------------------------------------
86. In the NOPR, the Commission raised the concern that the
proposed spare equipment strategy appears to be limited to ``steady
state analysis'' and sought clarification why ``stability analysis''
conditions are not mentioned.
Comments
87. NERC, ISOs/RTOs, and EEI comment that the burden of additional
stability analyses would not provide significant reliability benefits
because stability analysis already required under ``category P6'' will
produce more definitive tests of longer-term equipment unavailability.
They also claim that any potential stability impacts related to an
entity's spare equipment strategy will be observed in the normal
planning process driven by other requirements.
Commission Determination
88. The Commission agrees that NERC has met the spare equipment
strategy directive for steady state analysis under Reliability Standard
TPL-001-4, Requirement R2, Part 2.1.5. However, the Commission finds
that a spare equipment strategy for stability analysis is not addressed
under category P6.
89. The spare equipment strategy for steady state analysis under
Reliability Standard TPL-001-4, Requirement R2, Part 2.1.5 requires
that steady state studies be performed for the P0, P1 and P2 categories
identified in Table 1 with the conditions that the system is expected
to experience during the possible unavailability of the long lead time
equipment. The Commission believes that a similar spare equipment
strategy for stability analysis should exist that requires studies to
be performed for P0, P1 and P2 categories with the conditions that the
system is expected to experience during the possible unavailability of
the long lead time equipment. Further, we are not persuaded by the
explanation of NERC and others that a similar spare equipment strategy
for stability analysis would cause unjustified burden because stability
analysis is already required under category P6. The Commission notes
that the category P2 contingencies studied under the spare equipment
strategy for steady state analysis are different than the contingencies
studied under category P6. For example, under the spare equipment
strategy for steady state, a planner would study a long lead-time piece
of equipment out of service (e.g., a transformer) along with a bus
section fault contingency (i.e., category P2, event 2). The study of
this same condition for stability analysis under category P6 is not
addressed. However, the Commission will not direct a change and instead
directs NERC to consider a similar spare equipment strategy for
stability analysis upon the next review cycle of Reliability Standard
TPL-001-4.
C. Range of Extreme Events
NOPR Proposal
90. In Order No. 693, the Commission directed NERC to modify the
Version 0 Reliability Standard, TPL-004-0, to require that, in
determining the range of the extreme events to be assessed, the
contingency list of category D would be expanded to include recent
events such as hurricanes and ice storms.\65\ In the April 2012 NOPR,
the Commission indicated that, while the proposed Version 4 TPL
Standard appropriately expands the list of extreme event examples in
Table 1, the list limits these items to the loss of two generating
stations under Item No. 3a. The Commission sought clarification on
conditioning extreme events on the loss of two generating stations.\66\
The Commission also sought clarification regarding whether the ``two
generation stations'' limitation would adequately capture a scenario
where an extreme event can impact more than two generation stations.
---------------------------------------------------------------------------
\65\ Order No. 693, FERC Stats. & Regs. ] 31,242 at P 1834.
\66\ April 2012 NOPR, 139 FERC ] 61,059 at P 48.
---------------------------------------------------------------------------
Comments
91. NERC asserts that it addressed the Order No. 693 directive to
expand the range of events considered in the planning assessment by
adding a new category ``wide area events'' as extreme events. NERC
contends that it is raising the bar concerning extreme events by
requiring the planners to evaluate the loss of two generating stations
for a wide range of external events that could cause the loss of all
generating units at two generating stations. NERC adds that extreme
events in item 3b of Table 1 means that the planner will consider even
more extreme events (i.e., the loss of more facilities than the loss of
two generating stations) based upon operating experience and knowledge
of its system.
92. EEI agrees with the Commission that there are conditions that
provide far more serious impacts to the grid than that which is
described in item 3a of Table 1 of the proposed standard. However,
those conditions are largely area specific thereby making it impossible
to describe or address all possibilities in a Standard. EEI, therefore,
supports NERC's approach which obligates planners to consider, as
stated in Item 3b, ``[o]ther events based upon operating experience
that may result in wide area disturbances.'' EEI believes that Table 1,
Item No. 3b provides the necessary backstop to ensure that extreme
events are fully captured from a planning standpoint.\67\
---------------------------------------------------------------------------
\67\ EEI Comments at 14-15.
---------------------------------------------------------------------------
Commission Determination
93. The Commission is satisfied with the explanation of NERC and
EEI that Table 1, item No. 3b provides the necessary backstop to ensure
that extreme events are fully captured from a planning standpoint
including extreme events that can impact more than two generating
stations and that a planner will consider even more extreme events
based on operating experience and knowledge of its system.
d. Footnote `a'
NOPR Proposal
94. In Order No. 693, the Commission directed NERC to modify
footnote `a' of Table 1 with regard to ``applicability of emergency
ratings and consistency of normal ratings and voltages with values
obtained from other reliability standards.'' \68\ In its petition, NERC
noted that proposed Table 1, header note `e,' which provides that
planned system adjustments must be executable
[[Page 63049]]
within the time duration applicable to facility ratings. Further,
according to NERC, header note `f,' which states applicable facility
ratings shall not be exceeded, meets the Order No. 693 directive
pertaining to footnote `a' in the current standard.
---------------------------------------------------------------------------
\68\ Order No. 693, FERC Stats. & Regs. ] 31,242 at P 1770.
---------------------------------------------------------------------------
95. In the NOPR the Commission observed that the proposed standard
applies header note `e' to ``Steady State and Stability,'' while header
note `f' is excluded from ``Stability'' and only applies to ``Steady
State'' studies. Accordingly, the Commission sought clarification
regarding the rationale for excluding header note `f' from
``Stability'' studies. In addition, for Table 1, header notes `e' and
`f,' the Commission sought comment on whether the normal facility
ratings align with Reliability Standard FAC-008-1 and normal voltage
ratings align with Reliability Standard VAR-001-1. Furthermore, the
Commission sought clarification whether facility ratings used in
planning assessments align with other reliability standards such as
Reliability Standards NUC-001-2, BAL-001-0.1a and the PRC Reliability
Standards for UFLS and UVLS.
Comments
96. NERC states that it excluded header note `f' from stability
studies because facility ratings are defined for a finite period which
may be between a few minutes and several hours, or longer. According to
NERC, in stability studies the analysis is conducted over a few seconds
and because facility ratings are established based on the overheating
of elements, the few seconds in the stability timeframe is not
significant to the overheating of elements.\69\
---------------------------------------------------------------------------
\69\ See also BPA Comments at 5, EEI Comments at 15 and ISO/RTOs
Comments at 11.
---------------------------------------------------------------------------
97. ISO/RTO states that the observation of facility trip ratings
(i.e., relay trip ratings) are valid in the stability simulation time
frame, and should be considered if associated protective relay schemes
are sensitive to power swings (e.g., impedance relays with no out-of
step trip blocking for stable swings, etc.). Further, ISO/RTO believes
that there is no reason to include a requirement to observe thermal
facility ratings in stability studies, but also believes that facility
trip ratings should be observed in stability studies.
98. NERC and EEI also explain that the values used for facility
ratings within transmission planning models are developed in accordance
with standard FAC-008-1 ``Facility Ratings Methodology'' and
communicated to other functional entities as required by FAC-009-1
``Establish and Communicate Facility Ratings.''
99. In response to the Commission's request for clarification
whether facility ratings used in planning assessments align with other
Reliability Standards, commenters generally stated that facility
ratings used in the TPL standard are consistent throughout the NERC
standards. Further, commenters stated that Reliability Standard VAR-
001-2 is not a ratings standard but an operational (real-time) standard
to ensure voltage levels, reactive flows and reactive resources are
monitored, controlled and maintained within the limits of the
equipment.\70\
---------------------------------------------------------------------------
\70\ See NERC Comments at 16 and EEI Comments at 15.
---------------------------------------------------------------------------
Commission Determination
100. The Commission is satisfied with commenters' explanation and
agrees that it is not necessary to include a requirement to observe
thermal facility ratings in stability studies. The Commission agrees
with ISO/RTO that facility trip ratings (i.e., relay trip ratings) are
valid ratings in the stability simulation time frame, and should be
considered in the planning assessment if associated protective relay
schemes are sensitive to power swings (e.g., impedance relays with no
out-of step trip blocking for stable swings). Further, the Commission
accepts the explanation of NERC and others that facility ratings used
in planning assessments are determined in accordance with Reliability
Standard FAC-008-3,\71\ which states that a ``Facility Rating shall
respect the most limiting applicable Equipment Rating of the individual
equipment that comprises that Facility.''
---------------------------------------------------------------------------
\71\ In ``Order Approving Reliability Standard'' issued November
17, 2011 (Docket No. RD11-10-000), the Commission approved FAC-008-3
Reliability Standard and the retirement of FAC-008-1 and FAC-009-1
Reliability Standards.
---------------------------------------------------------------------------
C. Other Matters Raised by Commenters
101. Powerex states that additional clarification is needed with
respect to Footnote 9 to Table 1 in order to provide clarity and ensure
consistent interpretation as to when transmission planners may plan to
curtail firm transmission service. Powerex is concerned that the
revised TPL Standard may provide transmission planners with broad
discretion to plan for the curtailment of firm transmission service
without providing purchase-selling entities with the notice and
certainty they need to make appropriate alternate arrangements. Powerex
believes that the phrase in footnote 9 ``resources obligated to re-
dispatch'' should be clarified as referring to a formal agreement
between the transmission provider and a generation owner, located on
the load side of a transmission constraint, to resupply the load that
had been receiving energy from a remote source before the firm
transmission service was curtailed.
Commission Determination
102. We will not direct NERC to modify footnote 9. We find NERC's
explanation satisfactory that ``the planner must be able to show that
the curtailment is supported by a valid re-dispatch of generation that
would be `obligated to redispatch' . . . [t]herefore, the planner
cannot simply re-dispatch units outside the area of control for the
transmission system for which it is reviewing--the re-dispatch must be
valid and realistic.'' \72\
---------------------------------------------------------------------------
\72\ NERC Petition, Consideration of Comments on Assess
Transmission Future Needs and Develop Transmission Plans--Project
2006-02, draft 6, pp. 78-79.
---------------------------------------------------------------------------
III. Information Collection Statement
103. The Office of Management and Budget (OMB) regulations require
that OMB approve certain reporting and recordkeeping (collections of
information) imposed by an agency.\73\ Upon approval of a collection(s)
of information, OMB will assign an OMB control number and expiration
date. Respondents subject to the filing requirements of this rule will
not be penalized for failing to respond to these collections of
information unless the collections of information display a valid OMB
control number.
---------------------------------------------------------------------------
\73\ 5 CFR 1320.11.
---------------------------------------------------------------------------
104. The Commission is submitting these reporting and recordkeeping
requirements to OMB for its review and approval under section 3507(d)
of Paperwork Reduction Act of 1995. The Commission solicited comments
on the need for and the purpose of the information contained in
Reliability Standard TPL-001-4 and the corresponding burden to
implement the Reliability Standard. The Commission received comments on
specific requirements in the Reliability Standard, which we address in
this Final Rule. However, the Commission did not receive any comments
on our reporting burden estimates. The Final Rule approves Reliability
Standard TPL-001-4.
105. Public Reporting Burden: The burden and cost estimates below
are based on the increase in the reporting and recordkeeping burden
imposed by the proposed Reliability Standards. Our estimates are based
on the NERC Compliance Registry as of February 28, 2013, which indicate
that NERC has
[[Page 63050]]
registered 183 transmission planners and planning coordinators.
--------------------------------------------------------------------------------------------------------------------------------------------------------
Average number of
Improved requirement \74\ Year Number and type of Number of annual paperwork hours per Total burden hours
entity \75\ responses per entity response
...................... (1)................... (2).................. (3).................. (1)*(2)*(3)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Identification of Joint Year 1................ 183 Transmission 1 response........... 9 (5 engineer hours 1,647
Responsibilities and System Planners and Planning and 4 record keeping
Modeling Enhancements \76\. Coordinators. hours).
Year 2 and Year 3..... 183 Transmission 1 response........... 5 (3 engineer hours 915
Planners and Planning and 2 record keeping
Coordinators. hours).
New Assessments, Simulations, Year 2................ 183 Transmission 1 response........... 145 (84 engineer 26,535
Studies, Modeling Enhancements and Planners and Planning hours, 61 record
associated Documentation\77\. Coordinators. keeping hours).
Year 3................ 183 Transmission 1 response........... 84 (45 engineer 15,372
Planners and Planning hours, 39 record
Coordinators. keeping hours).
Attachment 1 stakeholder process... Year 3................ 1 Transmission Planner 12 responses to 63 (40 engineer 756
and Planning Attachment 1, hours, 17 record
Coordinator. sections I and II. keeping hours, 6
legal hours).
Year 3................ 1 Transmission Planner 4 responses to 68 (40 engineer 272
and Planning Attachment 1, hours, 20 record
Coordinator. Sections I, II, and keeping hours, 8
III. legal hours).
--------------------------------------------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------
\74\ Each requirement identifies a reliability improvement by
proposed Reliability Standard TPL-001-4.
\75\ NERC registered transmission planners and planning
coordinators responsible for the improved requirement. Further, if a
single entity is registered as both a transmission planner and
planning coordinator, that entity is counted as one unique entity.
\76\ The Commission estimates a reduction in burden hours from
year 1 to year 2 because year 1 represents a portion of one-time
tasks not repeated in subsequent years.
\77\ The Commission estimates a reduction in burden hours from
year 2 to year 3 because year 2 represents a portion of one-time
tasks not repeated in subsequent years.
---------------------------------------------------------------------------
Costs To Comply With Paperwork Requirements
Year 1: $77,592.
Year 2: $1,312,659.
Year 3 and ongoing: $820,149.
106. Year 1 costs include the implementation of those improved
requirements that become effective on the first day of the first
calendar quarter, 12 months after applicable regulatory approval, which
include requirements such as coordination between entities and
incremental system modeling enhancements. Year 2 costs include a
portion of year 1 reoccurring costs plus the implementation of the
remaining improved requirements that become effective on the first day
of the first calendar quarter, 24 months after applicable regulatory
approval, which include requirements such as sensitivity studies for
steady state and stability analysis, implementation of a spare
equipment strategy, short circuit studies, an expansion of
contingencies and extreme events, and all associated system modeling
enhancements and documentation. Year 3 costs include a portion of year
2 reoccurring costs plus an estimated cost for Attachment 1 stakeholder
process, if needed.
107. For the burden categories above, the loaded (salary plus
benefits) costs are: $60/hour for an engineer; $31/hour for
recordkeeping; and $128/hour for legal.\78\ The estimated breakdown of
annual cost is as follows:
---------------------------------------------------------------------------
\78\ Labor rates from Bureau of Labor Statistics (BLS) (https://bls.gov/oes/current/naics2_22.htm). Loaded costs are BLS rates
divided by 0.703 and rounded to the nearest dollar (https://www.bls.gov/news.release/ecec.nr0.htm).
---------------------------------------------------------------------------
Year 1
[cir] Identification of Joint Responsibilities and System Modeling
Enhancements: 183 entities * [(5 hours/response * $60/hour) + (4 hours/
response * $31/hour)] = $77,592.
Year 2
[cir] Identification of Joint Responsibilities and System Modeling
Enhancements: 183 entities * [(3 hours/response * $60/hour) + (2 hours/
response * $31/hour)] = $44,286.
[cir] New Assessments, Simulations, Studies, Modeling Enhancements
and associated Documentation: 183 entities * [(84 hours/response * $60/
hour) + (61 hours/response * $31/hour)] = $1,268,373.
Year 3
[cir] Identification of Joint Responsibilities and System Modeling
Enhancements: 183 entities * [(3 hours/response * $60/hour) + (2 hours/
response * $31/hour)] = $44,286.
[cir] New Assessments, Simulations, Studies, Modeling Enhancements
and associated Documentation: 183 entities * [(45 hours/response * $60/
hour) + (39 hours/response * $31/hour)] = $715,347.
[cir] Implementation of footnote 12 and the stakeholder process:
{12 responses * [(40 hours/response * $60/hour) + (17 hours/response *
$31/hour) + (6 hours/response * $128/hour)]{time} + {4 responses *
[(40 hours/response * $60/hr) + (20 hours/response * $31/hour) + (8
hours/response * $128/hour)]{time} = $60,516.
Title: 725N, Mandatory Reliability Standards: Reliability Standard
TPL-001-4.\79\
---------------------------------------------------------------------------
\79\ The Supplemental NOPR used the identifier FERC-725A (OMB
Control No. 1902-0244). However, for administrative purposes and to
submit the information collection requirements to OMB timely, the
requirements were labeled FERC-725N (OMB Control No. 1902-0264) in
the submittal to OMB associated with the NOPR. We are using FERC-
725N in this Final Rule and in the associated submittal to OMB.
---------------------------------------------------------------------------
[[Page 63051]]
Action: Proposed Collection FERC-725N.
OMB Control No: 1902-0264.
Respondents: Business or other for profit, and not for profit
institutions.
Frequency of Responses: Annually and one-time.
Necessity of the Information: The approved Reliability Standard
TPL-001-4 implements the Congressional mandate of the Energy Policy Act
of 2005 to develop mandatory and enforceable Reliability Standards to
better ensure the reliability of the nation's Bulk-Power System.
Specifically, the Reliability Standard ensures that planning
coordinators and transmission planners establish transmission system
planning performance requirements within the planning horizon to
develop a bulk electric system that will operate reliability and meet
specified performance requirements over a broad spectrum of system
conditions to meet present and future system needs.
Internal review: The Commission has reviewed the revised
Reliability Standard TPL-001-4 and made a determination that its action
is necessary to implement section 215 of the FPA. The Commission has
assured itself, by means of its internal review, that there is
specific, objective support for the burden estimates associated with
the information requirements.
Interested persons may obtain information on the reporting
requirements by contacting the following: Federal Energy Regulatory
Commission, 888 First Street NE., Washington, DC 20426 [Attention:
Ellen Brown, Office of the Executive Director, email:
DataClearance@ferc.gov, phone: 202-502-8663, fax: 202-273-0873]. For
submitting comments concerning the collection(s) of information and the
associated burden estimate(s), please send your comments to the
Commission and to the Office of Management and Budget, Office of
Information and Regulatory Affairs, Washington, DC 20503 [Attention:
Desk Officer for the Federal Energy Regulatory Commission, phone: 202-
395-4638, fax: 202-395-7285]. For security reasons, comments to OMB
should be submitted by email to: oira_submission@omb.eop.gov. Comments
submitted to OMB should include FERC-725N and Docket Nos. RM12-1-000
and RM13-9-000.
IV. Environmental Analysis
108. The Commission is required to prepare an Environmental
Assessment or an Environmental Impact Statement for any action that may
have a significant adverse effect on the human environment.\80\ The
Commission has categorically excluded certain actions from this
requirement as not having a significant effect on the human
environment. Included in the exclusion are rules that are clarifying,
corrective, or procedural or that do not substantially change the
effect of the regulations being amended.\81\ The actions proposed
herein fall within this categorical exclusion in the Commission's
regulations.
---------------------------------------------------------------------------
\80\ Regulations Implementing the National Environmental Policy
Act of 1969, Order No. 486, FERC Stats. & Regs. ] 30,783 (1987).
\81\ 18 CFR 380.4(a)(2)(ii).
---------------------------------------------------------------------------
V. Regulatory Flexibility Act Analysis
109. The Regulatory Flexibility Act of 1980 (RFA) \82\ generally
requires a description and analysis of final rules that will have
significant economic impact on a substantial number of small entities.
The RFA mandates consideration of regulatory alternatives that
accomplish the stated objectives of a proposed rule and that minimize
any significant economic impact on a substantial number of small
entities. The Small Business Administration's (SBA) Office of Size
Standards develops the numerical definition of a small business.\83\
The SBA has established a size standard for electric utilities, stating
that a firm is small if, including its affiliates, it is primarily
engaged in the transmission, generation and/or distribution of electric
energy for sale and its total electric output for the preceding twelve
months did not exceed four million megawatt hours.\84\
---------------------------------------------------------------------------
\82\ 5 U.S.C. 601-12.
\83\ 13 CFR 121.101.
\84\ 13 CFR 121.201, Sector 22, Utilities & n.1.
---------------------------------------------------------------------------
110. As discussed above, Reliability Standard TPL-001-4 would apply
to 183 transmission planners and planning coordinators identified in
the NERC Compliance Registry. Comparison of the NERC Compliance
Registry with data submitted to the Energy Information Administration
on Form EIA-861 indicates that, of the 183 registered transmission
planners and planning coordinators registered by NERC, 41 may qualify
as small entities.
111. The Commission estimates that, on average, each of the 41
small entities affected will have an estimated cost of $1,324 in Year
1, $16,953 in Year 2 \85\ and $11,471 in Year 3 (without Attachment 1).
In addition, based on the results of NERC's data request approximately
10 percent of all registered transmission planners and planning
coordinators used planned non-consequential load loss under the
currently-effective TPL Reliability Standards. The Commission estimates
that approximately 4 of the 41 small entities would use the stakeholder
process set forth in Attachment 1. The total estimated cost per
response for each of these 4 small entities in Year 3 is approximately
$19,500 if Attachment 1, sections I and II are used, or $20,000 if
Attachment 1, sections I, II and III are used. These figures are based
on information collection costs plus additional costs for compliance.
Based on this estimate, the Commission certifies that Reliability
Standard TPL-001-4 will not have a significant economic impact on a
substantial number of small entities. Accordingly, no regulatory
flexibility analysis is required.
---------------------------------------------------------------------------
\85\ The increase in Year 2 costs include a portion of year 1
recurring costs plus the implementation of the remaining improved
requirements that become effective on the first day of the first
calendar quarter, 24 months after applicable regulatory approval.
---------------------------------------------------------------------------
VI. Document Availability
112. In addition to publishing the full text of this document in
the Federal Register, the Commission provides all interested persons an
opportunity to view and/or print the contents of this document via the
Internet through FERC's Home Page (https://www.ferc.gov) and in FERC's
Public Reference Room during normal business hours (8:30 a.m. to 5:00
p.m. Eastern time) at 888 First Street NE., Room 2A, Washington, DC
20426.
113. From FERC's Home Page on the Internet, this information is
available on eLibrary. The full text of this document is available on
eLibrary in PDF and Microsoft Word format for viewing, printing, and/or
downloading. To access this document in eLibrary, type the docket
number excluding the last three digits of this document in the docket
number field.
114. User assistance is available for eLibrary and the FERC's Web
site during normal business hours from FERC Online Support at 202-502-
6652 (toll free at 1-866-208-3676) or email at
ferconlinesupport@ferc.gov, or the Public Reference Room at (202) 502-
8371, TTY (202) 502-8659. Email the Public Reference Room at
public.referenceroom@ferc.gov.
VII. Effective Date and Congressional Notification
115. These regulations are effective December 23, 2013. The
Commission has determined that this rule is not a ``major rule'' as
defined in section 351 of the Small Business Regulatory Enforcement
Fairness Act of 1996.
[[Page 63052]]
By the Commission.
Nathaniel J. Davis, Sr.,
Deputy Secretary.
[FR Doc. 2013-24828 Filed 10-22-13; 8:45 am]
BILLING CODE 6717-01-P