Energy Conservation Program: Energy Conservation Standards for Residential Clothes Dryers and Room Air Conditioners, 20842-20844 [2013-08074]
Download as PDF
20842
Federal Register / Vol. 78, No. 67 / Monday, April 8, 2013 / Proposed Rules
after [insert date 180 days after date of
publication of faucets and showerheads test
procedure final rule] must be made based
upon results generated using this test
procedure. Any representation related to
water consumption of water closets or urinals
made between [insert date 30 days after date
of publication of water closets and urinals
test procedure final rule] and [insert date 180
days after date of publication of water closets
and urinals test procedure final rule] must be
based upon results generated either under
this test procedure or upon the test procedure
as it appeared at 10 CFR part 430, subpart B,
appendix T, as contained in the 10 CFR parts
200 to 499 edition revised as of January 1,
2012.
mstockstill on DSK4VPTVN1PROD with PROPOSALS
*
*
*
*
*
2. Test Apparatus and General Instructions
a. The test apparatus and instructions for
testing water closets shall conform to the
requirements specified in section 7.1,
‘‘General,’’ in sections 7.1.1, 7.1.2, 7.1.3,
7.1.4, and 7.1.5 of ASME A112.19.2
(incorporated by reference, see § 430.3).
Measurements shall be recorded at the
resolution of the test instrumentation.
Calculations of water consumption for each
tested unit shall be rounded off to the same
number of significant digits as the previous
step.
b. The test apparatus and instructions for
testing urinals shall conform to the
requirements specified in section 8.2, ‘‘Test
Apparatus and General Instructions,’’ of
ASME A112.19.2–2008 (incorporated by
reference, see § 430.3). Measurements shall
be recorded at the resolution of the test
instrumentation. Calculations of water
consumption for each tested unit shall be
rounded off to the same number of significant
digits as the previous step.
3. Test Measurement
a. Water closets:
(i) Measurement of water flush volume:
The measurement of the water flush volume
for water closets, expressed in gallons per
flush (gpf) or liters per flush (Lpf), shall be
conducted in accordance with the test
requirements specified in section 7.4, ‘‘Water
Consumption Test,’’ of ASME A112.19.2
(incorporated by reference, see § 430.3).
(ii) Static pressure requirements: The water
consumption tests of siphonic and blowout
water closets shall be conducted at two static
pressures. For flushometer valve water
closets with a siphonic bowl, the test
pressures shall be 80 psi and 35 psi. For
flushometer valve water closets with a
blowout bowl, the test pressures shall be 80
psi and 45 psi. The test shall be run three
times at each pressure as specified in section
7.4.3, ‘‘Procedure,’’ of ASME A112.19.2
(incorporated by reference, see § 430.3).
(iii) Flush volume and tank trim
component adjustments: For gravity flush
tank water closets, trim components that can
be adjusted to cause an increase in flush
volume, including (but not limited to) the
flapper valve, fill valve, and float, shall be set
in accordance with the printed installation
instructions supplied by the manufacturer. If
the installation instructions for the model to
be tested do not specify trim setting
adjustments, these trim components shall be
VerDate Mar<15>2010
16:58 Apr 05, 2013
Jkt 229001
adjusted to the maximum water use setting
so that the maximum flush volume is
produced without causing the water closet to
malfunction or leak. The water level in the
tank shall be set to the maximum water line
designated in the printed installation
instructions supplied by the manufacturer or
the designated water line on the tank itself,
whichever is higher. If the printed
installation instructions or the water closet
tank do not indicate a water level, the water
level shall be adjusted to 1 ± 0.1 inches
below the top of the overflow tube or 1 ± 0.1
inches below the top rim of the water
containing vessel (for gravity flush tank water
closets that do not contain an overflow tube)
for each designated pressure specified in
Table 5 of ASME A112.19.2 (incorporated by
reference, see § 430.3).
[FR Doc. 2013–08073 Filed 4–5–13; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF ENERGY
10 CFR Part 430
[Docket Number EERE–2013–BT–STD–
0020]
RIN 1904–AC98
Energy Conservation Program: Energy
Conservation Standards for
Residential Clothes Dryers and Room
Air Conditioners
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Proposed rule.
AGENCY:
This proposed rule would
correct the energy conservation
standards for room air conditioners. In
the direct final rule establishing
amended energy conservation standards
for residential clothes dryers and room
air conditioners, published in the
Federal Register on April 21, 2011, and
the subsequent notices of effective date
and compliance dates for the direct final
rule and amendment of compliance
dates, published on August 24, 2011,
the Department of Energy (DOE)
erroneously specified the maximum
cooling capacity for product class 5a for
room air conditioners without reverse
cycle and with louvered sides as 24,999
British thermal units per hour (Btu/h),
and the minimum cooling capacity for
product class 5b for room air
conditioners without reverse cycle and
with louvered sides as 25,000 Btu/h,
rather than 27,999 Btu/h and 28,000
Btu/h, respectively.
DATES: DOE will accept comments, data,
and information regarding the proposed
standards no later than May 8, 2013.
ADDRESSES: Any comments submitted
must identify the proposed rule for
Energy Conservation Standards for
SUMMARY:
PO 00000
Frm 00023
Fmt 4702
Sfmt 4702
Residential Clothes Dryers and Room
Air Conditioners, and provide docket
number EERE–2013–BT–STD–0020
and/or regulatory information number
(RIN) number 1904–AC98. Comments
may be submitted using any of the
following methods:
1. Federal eRulemaking Portal:
https://www.regulations.gov. Follow the
instructions for submitting comments.
2. Email:
DFRCorrRCDRAC@ee.doe.gov. Include
the docket number and/or RIN in the
subject line of the message.
3. Mail: Ms. Brenda Edwards, U.S.
Department of Energy, Building
Technologies Program, Mailstop EE–2J,
1000 Independence Avenue SW.,
Washington, DC 20585–0121. If
possible, please submit all items on a
CD. It is not necessary to include
printed copies.
4. Hand Delivery/Courier: Ms. Brenda
Edwards, U.S. Department of Energy,
Building Technologies Program, 950
L’Enfant Plaza SW., Suite 600,
Washington, DC 20024. Telephone:
(202) 586–2945. If possible, please
submit all items on a CD. It is not
necessary to include printed copies.
Docket: The docket for this
rulemaking is available for review at
www.regulations.gov/
#!docketDetail;D=EERE-2013-BT-STD0020. The docket for the direct final rule
establishing the standards for room air
conditioners is also available for review
at regulations.gov, including Federal
Register notices, framework documents,
public meeting attendee lists and
transcripts, comments, and other
supporting documents/materials. All
documents in the docket are listed in
the regulations.gov index. Not all
documents listed in the index may be
publicly available, such as information
that is exempt from public disclosure.
For further information on how to
submit or review public comments,
contact Ms. Brenda Edwards at (202)
586–2945 or email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT:
Stephen L. Witkowski, U.S. Department
of Energy, Office of Energy Efficiency
and Renewable Energy, Building
Technologies Program, EE–2J, 1000
Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–7463. Email:
Stephen.Witkowski@ee.doe.gov.
Elizabeth Kohl, Esq., U.S. Department of
Energy, Office of General Counsel,
GC–71, 1000 Independence Avenue
SW., Washington, DC 20585–0121.
Telephone: (202) 586–7796. Email:
Elizabeth.Kohl@hq.doe.gov.
E:\FR\FM\08APP1.SGM
08APP1
20843
Federal Register / Vol. 78, No. 67 / Monday, April 8, 2013 / Proposed Rules
DOE
published a direct final rule to establish
amended energy conservation standards
for residential clothes dryers and room
air conditioners on April 21, 2011. 76
FR 22454.
EPCA (42 U.S.C. 6291 et seq.), as
amended, grants DOE authority to issue
a final rule (hereinafter referred to as a
‘‘direct final rule’’) establishing an
energy conservation standard on receipt
of a statement submitted jointly by
interested persons that are fairly
representative of relevant points of view
(including representatives of
manufacturers of covered products,
States, and efficiency advocates) as
determined by the Secretary, that
contains recommendations with respect
to an energy conservation standard that
are in accordance with the provisions of
42 U.S.C. 6295(o). EPCA also requires a
NOPR that proposes an identical energy
conservation standard to be published
simultaneously with the final rule. A
public comment period of at least 110
days must be provided. 42 U.S.C.
6295(p)(4). Not later than 120 days after
issuance of the direct final rule, if one
or more adverse comments or an
alternative joint recommendation are
received relating to the direct final rule,
the Secretary must determine whether
the comments or alternative
recommendation may provide a
reasonable basis for withdrawal under
42 U.S.C. 6295(o) or other applicable
law. If the Secretary makes such a
determination, DOE must withdraw the
direct final rule and proceed with the
simultaneously published notice of
proposed rulemaking. DOE must
publish in the Federal Register the
reason why the direct final rule was
withdrawn. Id.
During the rulemaking proceeding to
develop amended standards for
residential clothes dryers and room air
conditioners, DOE received the
‘‘Agreement on Minimum Federal
Efficiency Standards, Smart Appliances,
Federal Incentives and Related Matters
for Specified Appliances’’ (the ‘‘Joint
Petition’’), a comment submitted by
groups representing manufacturers (the
Association of Home Appliance
Manufacturers (AHAM), Whirlpool
Corporation (Whirlpool), General
Electric Company (GE), Electrolux, LG
Electronics, Inc. (LG), BSH Home
Appliances (BSH), Alliance Laundry
mstockstill on DSK4VPTVN1PROD with PROPOSALS
SUPPLEMENTARY INFORMATION:
VerDate Mar<15>2010
16:58 Apr 05, 2013
Jkt 229001
Systems (ALS), Viking Range, Sub-Zero
Wolf, Friedrich A/C, U-Line, Samsung,
Sharp Electronics, Miele, Heat
Controller, AGA Marvel, Brown Stove,
Haier, Fagor America, Airwell Group,
Arcelik, Fisher & Paykel, Scotsman Ice,
Indesit, Kuppersbusch, Kelon, and
DeLonghi); energy and environmental
advocates (American Council for an
Energy Efficient Economy (ACEEE),
Appliance Standards Awareness Project
(ASAP), Natural Resources Defense
Council (NRDC), Alliance to Save
Energy (ASE), Alliance for Water
Efficiency (AWE), Northwest Power and
Conservation Council (NPCC), and
Northeast Energy Efficiency
Partnerships (NEEP)); and consumer
groups (Consumer Federation of
America (CFA) and the National
Consumer Law Center (NCLC))
(collectively, the ‘‘Joint Petitioners’’).
This collective set of comments, which
DOE refers to in this notice as the ‘‘Joint
Petition’’ 1 or ‘‘Consensus Agreement’’
recommended specific energy
conservation standards for residential
clothes dryers and room air conditioners
that, in the commenters’ view, satisfied
the EPCA requirements in 42 U.S.C.
6295(o). The Joint Petition also set forth
compliance dates for these
recommended standards of June 1, 2014
(room air conditioners) and January 1,
2015 (clothes dryers).
As discussed in the direct final rule,
DOE determined that the relevant
criteria under 42 U.S.C. 6295(p)(4) were
satisfied and adopted the amended
energy conservation standards for
clothes dryers and room air conditioners
through the direct final rule. 76 FR
22454 (April 21, 2011). After
considering comments received, DOE
subsequently published a document in
the Federal Register confirming
adoption of the standards set forth in
the direct final rule and announcing the
effective date of the direct final rule. 76
FR 52856 (Aug. 24, 2011).
In today’s rule, DOE proposes to
correct certain room air conditioner
product class definitions that were
inadvertently different than those that
were provided in the Joint Petition and
which were the basis of DOE’s analysis
for the previous final rules. Specifically,
DOE proposes to correct the product
1 DOE
Docket No. EERE–2007–BT–STD–0010,
Comment 35.
PO 00000
Frm 00024
Fmt 4702
Sfmt 4702
class definitions for room air
conditioners without reverse cycle and
with louvered sides as follows:
Product class
Definition
5a ..............................
Without reverse
cycle, with louvered
sides, and 20,000
to 27,999 Btu/h.
Without reverse
cycle, with louvered
sides, and 28,000
Btu/h or more.
5b ..............................
Procedural Issues and Regulatory
Review
The regulatory reviews conducted for
this rulemaking are identical to those set
forth in the DOE’s direct final rule
published on April 21, 2011
establishing amended energy
conservation standards. The
amendments in the direct final rule
become effective June 1, 2014.
List of Subjects in 10 CFR Part 430
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Intergovernmental relations, Reporting
and recordkeeping requirements, and
Small businesses.
Issued in Washington, DC, on April 2,
2013.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
For the reasons stated in the
preamble, DOE is proposing to amend
part 430 of title 10 of the Code of
Federal Regulations, as set forth below:
PART 430—ENERGY CONSERVATION
PROGRAM FOR CONSUMER
PRODUCTS
1. The authority citation for part 430
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6309; 28 U.S.C.
2461 note.
2. Section 430.32 is amended by
revising paragraph (b) to read as follows:
■
§ 430.32 Energy and water conservation
standards and their effective dates.
*
*
*
*
*
(b) Room air conditioners.
E:\FR\FM\08APP1.SGM
08APP1
20844
Federal Register / Vol. 78, No. 67 / Monday, April 8, 2013 / Proposed Rules
Energy efficiency
ratio, effective from
Oct. 1, 2000 to May
31, 2014
Combined energy
efficiency ratio, effective as of June
1, 2014
less than 6,000 Btu/h .............................................
6,000 to 7,999 Btu/h ..............................................
8,000 to 13,999 Btu/h ............................................
14,000 to 19,999 Btu/h ..........................................
9.7
9.7
9.8
9.7
11.0
11.0
10.9
10.7
5a. Without reverse cycle, with louvered sides, and 20,000 to 27,999 Btu/h ........................................
8.5
9.4
5b. Without reverse cycle, with louvered sides, and 28,000 Btu/h or more ...........................................
................................
9.0
6. Without reverse cycle, without louvered sides, and less than 6,000 Btu/h ........................................
7. Without reverse cycle, without louvered sides, and 6,000 to 7,999 Btu/h .........................................
9.0
9.0
10.0
10.0
8a. Without reverse cycle, without louvered sides, and 8,000 to 10,999 Btu/h .....................................
8.5
9.6
8b. Without reverse cycle, without louvered sides, and 11,000 to 13,999 Btu/h ...................................
................................
9.5
9. Without reverse cycle, without louvered sides, and 14,000 to 19,999 Btu/h .....................................
10. Without reverse cycle, without louvered sides, and 20,000 Btu/h or more ......................................
11. With reverse cycle, with louvered sides, and less than 20,000 Btu/h ..............................................
12. With reverse cycle, without louvered sides, and less than 14,000 Btu/h .........................................
13. With reverse cycle, with louvered sides, and 20,000 Btu/h or more ................................................
14. With reverse cycle, without louvered sides, and 14,000 Btu/h or more ...........................................
15. Casement-Only ..................................................................................................................................
16. Casement-Slider ................................................................................................................................
8.5
8.5
9.0
8.5
8.5
8.0
8.7
9.5
9.3
9.4
9.8
9.3
9.3
8.7
9.5
10.4
Product class
1.
2.
3.
4.
*
Without
Without
Without
Without
reverse
reverse
reverse
reverse
*
*
cycle,
cycle,
cycle,
cycle,
*
with
with
with
with
louvered
louvered
louvered
louvered
sides,
sides,
sides,
sides,
and
and
and
and
*
BILLING CODE 6450–01–P
DEPARTMENT OF TRANSPORTATION
Federal Aviation Administration
14 CFR Part 39
[Docket No. FAA–2013–0216; Directorate
Identifier 2012–NM–206–AD]
RIN 2120–AA64
Airworthiness Directives; Bombardier,
Inc. Airplanes
Federal Aviation
Administration (FAA), DOT.
ACTION: Notice of proposed rulemaking
(NPRM).
AGENCY:
We propose to adopt a new
airworthiness directive (AD) for certain
Bombardier, Inc. Model CL–600–2B19
(Regional Jet Series 100 & 440)
airplanes. This proposed AD was
prompted by a determination that
certain flap actuators require restoration
by installing a redesigned flap actuator
inboard pinion seal. This proposed AD
would require revising the maintenance
program by incorporating new
airworthiness limitation tasks. We are
proposing this AD to prevent flap
system failure, and consequent reduced
landing performance of the airplane.
DATES: We must receive comments on
this proposed AD by May 23, 2013.
mstockstill on DSK4VPTVN1PROD with PROPOSALS
SUMMARY:
VerDate Mar<15>2010
16:58 Apr 05, 2013
You may send comments by
any of the following methods:
• Federal eRulemaking Portal: Go to
https://www.regulations.gov. Follow the
instructions for submitting comments.
• Fax: (202) 493–2251.
• Mail: U.S. Department of
Transportation, Docket Operations, M–
30, West Building Ground Floor, Room
W12–140, 1200 New Jersey Avenue SE.,
Washington, DC 20590.
• Hand Delivery: U.S. Department of
Transportation, Docket Operations, M–
30, West Building Ground Floor, Room
W12–140, 1200 New Jersey Avenue SE.,
Washington, DC, between 9 a.m. and 5
p.m., Monday through Friday, except
Federal holidays.
For service information identified in
this proposed AD, contact Bombardier,
ˆ
Inc., 400 Cote-Vertu Road West, Dorval,
´
Quebec H4S 1Y9, Canada; telephone
514–855–5000; fax 514–855–7401; email
thd.crj@aero.bombardier.com; Internet
https://www.bombardier.com. You may
review copies of the referenced service
information at the FAA, Transport
Airplane Directorate, 1601 Lind Avenue
SW., Renton, WA. For information on
the availability of this material at the
FAA, call 425–227–1221.
ADDRESSES:
[FR Doc. 2013–08074 Filed 4–5–13; 8:45 am]
Jkt 229001
Examining the AD Docket
You may examine the AD docket on
the Internet at https://
www.regulations.gov; or in person at the
Docket Operations office between 9 a.m.
and 5 p.m., Monday through Friday,
except Federal holidays. The AD docket
contains this proposed AD, the
regulatory evaluation, any comments
PO 00000
Frm 00025
Fmt 4702
Sfmt 4702
received, and other information. The
street address for the Docket Operations
office (telephone (800) 647–5527) is in
the ADDRESSES section. Comments will
be available in the AD docket shortly
after receipt.
FOR FURTHER INFORMATION CONTACT:
Luke Walker, Aerospace Engineer,
Airframe and Mechanical Systems
Branch, ANE–171, FAA, New York
Aircraft Certification Office (ACO), 1600
Stewart Avenue, Suite 410, Westbury,
New York 11590; telephone (516) 228–
7363; fax (516) 794–5531.
SUPPLEMENTARY INFORMATION:
Comments Invited
We invite you to send any written
relevant data, views, or arguments about
this proposed AD. Send your comments
to an address listed under the
ADDRESSES section. Include ‘‘Docket No.
FAA–2013–0216; Directorate Identifier
2012–NM–206–AD’’ at the beginning of
your comments. We specifically invite
comments on the overall regulatory,
economic, environmental, and energy
aspects of this proposed AD. We will
consider all comments received by the
closing date and may amend this
proposed AD based on those comments.
We will post all comments we
receive, without change, to https://
www.regulations.gov, including any
personal information you provide. We
will also post a report summarizing each
substantive verbal contact we receive
about this proposed AD.
E:\FR\FM\08APP1.SGM
08APP1
Agencies
[Federal Register Volume 78, Number 67 (Monday, April 8, 2013)]
[Proposed Rules]
[Pages 20842-20844]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2013-08074]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Part 430
[Docket Number EERE-2013-BT-STD-0020]
RIN 1904-AC98
Energy Conservation Program: Energy Conservation Standards for
Residential Clothes Dryers and Room Air Conditioners
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Proposed rule.
-----------------------------------------------------------------------
SUMMARY: This proposed rule would correct the energy conservation
standards for room air conditioners. In the direct final rule
establishing amended energy conservation standards for residential
clothes dryers and room air conditioners, published in the Federal
Register on April 21, 2011, and the subsequent notices of effective
date and compliance dates for the direct final rule and amendment of
compliance dates, published on August 24, 2011, the Department of
Energy (DOE) erroneously specified the maximum cooling capacity for
product class 5a for room air conditioners without reverse cycle and
with louvered sides as 24,999 British thermal units per hour (Btu/h),
and the minimum cooling capacity for product class 5b for room air
conditioners without reverse cycle and with louvered sides as 25,000
Btu/h, rather than 27,999 Btu/h and 28,000 Btu/h, respectively.
DATES: DOE will accept comments, data, and information regarding the
proposed standards no later than May 8, 2013.
ADDRESSES: Any comments submitted must identify the proposed rule for
Energy Conservation Standards for Residential Clothes Dryers and Room
Air Conditioners, and provide docket number EERE-2013-BT-STD-0020 and/
or regulatory information number (RIN) number 1904-AC98. Comments may
be submitted using any of the following methods:
1. Federal eRulemaking Portal: https://www.regulations.gov. Follow
the instructions for submitting comments.
2. Email: DFRCorrRCDRAC@ee.doe.gov. Include the docket number and/
or RIN in the subject line of the message.
3. Mail: Ms. Brenda Edwards, U.S. Department of Energy, Building
Technologies Program, Mailstop EE-2J, 1000 Independence Avenue SW.,
Washington, DC 20585-0121. If possible, please submit all items on a
CD. It is not necessary to include printed copies.
4. Hand Delivery/Courier: Ms. Brenda Edwards, U.S. Department of
Energy, Building Technologies Program, 950 L'Enfant Plaza SW., Suite
600, Washington, DC 20024. Telephone: (202) 586-2945. If possible,
please submit all items on a CD. It is not necessary to include printed
copies.
Docket: The docket for this rulemaking is available for review at
www.regulations.gov/#!docketDetail;D=EERE-2013-BT-STD-0020. The docket
for the direct final rule establishing the standards for room air
conditioners is also available for review at regulations.gov, including
Federal Register notices, framework documents, public meeting attendee
lists and transcripts, comments, and other supporting documents/
materials. All documents in the docket are listed in the
regulations.gov index. Not all documents listed in the index may be
publicly available, such as information that is exempt from public
disclosure.
For further information on how to submit or review public comments,
contact Ms. Brenda Edwards at (202) 586-2945 or email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT:
Stephen L. Witkowski, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Program, EE-2J,
1000 Independence Avenue SW., Washington, DC 20585-0121. Telephone:
(202) 586-7463. Email: Stephen.Witkowski@ee.doe.gov.
Elizabeth Kohl, Esq., U.S. Department of Energy, Office of General
Counsel, GC-71, 1000 Independence Avenue SW., Washington, DC 20585-
0121. Telephone: (202) 586-7796. Email: Elizabeth.Kohl@hq.doe.gov.
[[Page 20843]]
SUPPLEMENTARY INFORMATION: DOE published a direct final rule to
establish amended energy conservation standards for residential clothes
dryers and room air conditioners on April 21, 2011. 76 FR 22454.
EPCA (42 U.S.C. 6291 et seq.), as amended, grants DOE authority to
issue a final rule (hereinafter referred to as a ``direct final rule'')
establishing an energy conservation standard on receipt of a statement
submitted jointly by interested persons that are fairly representative
of relevant points of view (including representatives of manufacturers
of covered products, States, and efficiency advocates) as determined by
the Secretary, that contains recommendations with respect to an energy
conservation standard that are in accordance with the provisions of 42
U.S.C. 6295(o). EPCA also requires a NOPR that proposes an identical
energy conservation standard to be published simultaneously with the
final rule. A public comment period of at least 110 days must be
provided. 42 U.S.C. 6295(p)(4). Not later than 120 days after issuance
of the direct final rule, if one or more adverse comments or an
alternative joint recommendation are received relating to the direct
final rule, the Secretary must determine whether the comments or
alternative recommendation may provide a reasonable basis for
withdrawal under 42 U.S.C. 6295(o) or other applicable law. If the
Secretary makes such a determination, DOE must withdraw the direct
final rule and proceed with the simultaneously published notice of
proposed rulemaking. DOE must publish in the Federal Register the
reason why the direct final rule was withdrawn. Id.
During the rulemaking proceeding to develop amended standards for
residential clothes dryers and room air conditioners, DOE received the
``Agreement on Minimum Federal Efficiency Standards, Smart Appliances,
Federal Incentives and Related Matters for Specified Appliances'' (the
``Joint Petition''), a comment submitted by groups representing
manufacturers (the Association of Home Appliance Manufacturers (AHAM),
Whirlpool Corporation (Whirlpool), General Electric Company (GE),
Electrolux, LG Electronics, Inc. (LG), BSH Home Appliances (BSH),
Alliance Laundry Systems (ALS), Viking Range, Sub-Zero Wolf, Friedrich
A/C, U-Line, Samsung, Sharp Electronics, Miele, Heat Controller, AGA
Marvel, Brown Stove, Haier, Fagor America, Airwell Group, Arcelik,
Fisher & Paykel, Scotsman Ice, Indesit, Kuppersbusch, Kelon, and
DeLonghi); energy and environmental advocates (American Council for an
Energy Efficient Economy (ACEEE), Appliance Standards Awareness Project
(ASAP), Natural Resources Defense Council (NRDC), Alliance to Save
Energy (ASE), Alliance for Water Efficiency (AWE), Northwest Power and
Conservation Council (NPCC), and Northeast Energy Efficiency
Partnerships (NEEP)); and consumer groups (Consumer Federation of
America (CFA) and the National Consumer Law Center (NCLC))
(collectively, the ``Joint Petitioners''). This collective set of
comments, which DOE refers to in this notice as the ``Joint Petition''
\1\ or ``Consensus Agreement'' recommended specific energy conservation
standards for residential clothes dryers and room air conditioners
that, in the commenters' view, satisfied the EPCA requirements in 42
U.S.C. 6295(o). The Joint Petition also set forth compliance dates for
these recommended standards of June 1, 2014 (room air conditioners) and
January 1, 2015 (clothes dryers).
---------------------------------------------------------------------------
\1\ DOE Docket No. EERE-2007-BT-STD-0010, Comment 35.
---------------------------------------------------------------------------
As discussed in the direct final rule, DOE determined that the
relevant criteria under 42 U.S.C. 6295(p)(4) were satisfied and adopted
the amended energy conservation standards for clothes dryers and room
air conditioners through the direct final rule. 76 FR 22454 (April 21,
2011). After considering comments received, DOE subsequently published
a document in the Federal Register confirming adoption of the standards
set forth in the direct final rule and announcing the effective date of
the direct final rule. 76 FR 52856 (Aug. 24, 2011).
In today's rule, DOE proposes to correct certain room air
conditioner product class definitions that were inadvertently different
than those that were provided in the Joint Petition and which were the
basis of DOE's analysis for the previous final rules. Specifically, DOE
proposes to correct the product class definitions for room air
conditioners without reverse cycle and with louvered sides as follows:
------------------------------------------------------------------------
Product class Definition
------------------------------------------------------------------------
5a........................................ Without reverse cycle, with
louvered sides, and 20,000
to 27,999 Btu/h.
5b........................................ Without reverse cycle, with
louvered sides, and 28,000
Btu/h or more.
------------------------------------------------------------------------
Procedural Issues and Regulatory Review
The regulatory reviews conducted for this rulemaking are identical
to those set forth in the DOE's direct final rule published on April
21, 2011 establishing amended energy conservation standards. The
amendments in the direct final rule become effective June 1, 2014.
List of Subjects in 10 CFR Part 430
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Intergovernmental relations, Reporting and recordkeeping requirements,
and Small businesses.
Issued in Washington, DC, on April 2, 2013.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
For the reasons stated in the preamble, DOE is proposing to amend
part 430 of title 10 of the Code of Federal Regulations, as set forth
below:
PART 430--ENERGY CONSERVATION PROGRAM FOR CONSUMER PRODUCTS
0
1. The authority citation for part 430 continues to read as follows:
Authority: 42 U.S.C. 6291-6309; 28 U.S.C. 2461 note.
0
2. Section 430.32 is amended by revising paragraph (b) to read as
follows:
Sec. 430.32 Energy and water conservation standards and their
effective dates.
* * * * *
(b) Room air conditioners.
[[Page 20844]]
------------------------------------------------------------------------
Energy efficiency Combined energy
ratio, effective efficiency ratio,
Product class from Oct. 1, 2000 effective as of
to May 31, 2014 June 1, 2014
------------------------------------------------------------------------
1. Without reverse cycle, with 9.7 11.0
louvered sides, and less than
6,000 Btu/h....................
2. Without reverse cycle, with 9.7 11.0
louvered sides, and 6,000 to
7,999 Btu/h....................
3. Without reverse cycle, with 9.8 10.9
louvered sides, and 8,000 to
13,999 Btu/h...................
4. Without reverse cycle, with 9.7 10.7
louvered sides, and 14,000 to
19,999 Btu/h...................
------------------------------------------------------------------------
5a. Without reverse cycle, with 8.5 9.4
louvered sides, and 20,000 to
27,999 Btu/h...................
--------------------------------- -------------------
5b. Without reverse cycle, with .................. 9.0
louvered sides, and 28,000 Btu/
h or more......................
------------------------------------------------------------------------
6. Without reverse cycle, 9.0 10.0
without louvered sides, and
less than 6,000 Btu/h..........
7. Without reverse cycle, 9.0 10.0
without louvered sides, and
6,000 to 7,999 Btu/h...........
------------------------------------------------------------------------
8a. Without reverse cycle, 8.5 9.6
without louvered sides, and
8,000 to 10,999 Btu/h..........
--------------------------------- -------------------
8b. Without reverse cycle, .................. 9.5
without louvered sides, and
11,000 to 13,999 Btu/h.........
------------------------------------------------------------------------
9. Without reverse cycle, 8.5 9.3
without louvered sides, and
14,000 to 19,999 Btu/h.........
10. Without reverse cycle, 8.5 9.4
without louvered sides, and
20,000 Btu/h or more...........
11. With reverse cycle, with 9.0 9.8
louvered sides, and less than
20,000 Btu/h...................
12. With reverse cycle, without 8.5 9.3
louvered sides, and less than
14,000 Btu/h...................
13. With reverse cycle, with 8.5 9.3
louvered sides, and 20,000 Btu/
h or more......................
14. With reverse cycle, without 8.0 8.7
louvered sides, and 14,000 Btu/
h or more......................
15. Casement-Only............... 8.7 9.5
16. Casement-Slider............. 9.5 10.4
------------------------------------------------------------------------
* * * * *
[FR Doc. 2013-08074 Filed 4-5-13; 8:45 am]
BILLING CODE 6450-01-P