Decision and Order Granting a Waiver Granted to Fujitsu General Limited From the Department of Energy Commercial Package Air Conditioner and Heat Pump Test Procedures, 68752-68754 [2012-27927]
Download as PDF
68752
Federal Register / Vol. 77, No. 222 / Friday, November 16, 2012 / Notices
Format (PDF). To use PDF you must
have Adobe Acrobat Reader, which is
available free at the site.
You may also access documents of the
Department published in the Federal
Register by using the article search
feature at: www.federalregister.gov.
Specifically, through the advanced
search feature at this site, you can limit
your search to documents published by
the Department.
Dated: November 9, 2012.
John Q. Easton,
Director, Institute of Education Sciences.
[FR Doc. 2012–27845 Filed 11–15–12; 8:45 am]
BILLING CODE 4000–01–P
DEPARTMENT OF ENERGY
Notice of Intent To Grant Exclusive
License Between National Energy
Technology Laboratory and Corrosion
Solutions
National Energy Technology
Laboratory, Department of Energy.
ACTION: Notice of Intent To Grant
Exclusive License.
AGENCY:
This notice is issued in
accordance with 35 U.S.C. 209(c)(1) and
37 CFR 404.7(a)(1)(i). The National
Energy Technology Laboratory (NETL)
hereby gives notice of its intent to grant
an exclusive license to practice the
inventions described and claimed in
U.S. Patent No 7,553,517, issued June
30, 2009, entitled ‘‘Method of applying
a cerium diffusion coating to a metallic
alloy,’’ to Corrosion Solutions having its
principal place of business in Eugene,
Oregon. The inventions are owned by
the United States of America as
represented by the Department of
Energy (DOE). The prospective
exclusive license will comply with the
terms and conditions of 35 U.S.C. 209
and 37 CFR 404.7.
DATES: Written comments or
nonexclusive license applications are to
be received at the address listed below
no later than December 3, 2012.
Objections submitted in response to this
notice will not be made available to the
public for inspection and, to the extent
permitted by law, will not be released
under the Freedom of Information Act,
5 U.S.C. 552.
ADDRESSES: Objections relating to the
prospective exclusive license may be
submitted to the Office of Chief
Counsel, National Energy Technology
Laboratory, P.O. Box 10940, Pittsburgh,
PA 15236, or via facsimile at (412) 386–
5949.
FOR FURTHER INFORMATION CONTACT:
Jessica Sosenko, Technology Transfer
mstockstill on DSK4VPTVN1PROD with NOTICES
SUMMARY:
VerDate Mar<15>2010
15:43 Nov 15, 2012
Jkt 229001
Program Manager, U.S. Department of
Energy, National Energy Technology
Laboratory, P.O. Box 10940, Pittsburgh,
PA 15236; Telephone (412) 386–7417;
Email: jessica.sosenko@netl.doe.gov.
Section
209(c) gives DOE with authority to grant
exclusive or partially exclusive licenses
in department-owned inventions, where
a determination can be made, among
other things, that the desired practical
application of the invention has not
been achieved, or is not likely
expeditiously to be achieved, under a
nonexclusive license. The statute and
implementing regulations (37 CFR 404)
require that the necessary
determinations be made after public
notice and opportunity for filing written
objections.
Corrosion Solutions, a new small
business, has applied for an exclusive
license to practice the inventions and
has a plan for commercialization of the
invention. DOE intends to grant the
license, upon a final determination in
accordance with 35 U.S.C. 209(c),
unless, within 15 days of publication of
this notice, NETL’s Office of Chief
Counsel (contact information listed
above) receives in writing any of the
following, together with the supporting
documents:
SUPPLEMENTARY INFORMATION:
(i) A statement from any person setting
forth reasons why it would not be in the best
interest of the United States to grant the
proposed license; or
(ii) An application for a nonexclusive
license to the invention, in which the
applicant states that it already has brought
the invention to practical application or is
likely to bring the invention to practical
application expeditiously.
The proposed license would be exclusive,
subject to a license and other rights retained
by the U.S. Government, and subject to a
negotiated royalty. DOE will review all
timely written responses to this notice and
will grant the license if, after expiration of
the 15-day notice period and after
consideration of any written responses to this
notice, a determination is made in
accordance with Section 209(c) that the
license is in the public interest.
Dated: October 26, 2012.
Anthony V. Cugini,
Director, National Energy Technology
Laboratory.
[FR Doc. 2012–27928 Filed 11–15–12; 8:45 am]
BILLING CODE 6450–01–P
PO 00000
Frm 00022
Fmt 4703
Sfmt 4703
DEPARTMENT OF ENERGY
Office of Energy Efficiency and
Renewable Energy
[Case No. CAC–039]
Decision and Order Granting a Waiver
Granted to Fujitsu General Limited
From the Department of Energy
Commercial Package Air Conditioner
and Heat Pump Test Procedures
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Decision and Order.
AGENCY:
The U.S. Department of
Energy (DOE) gives notice of the
decision and order (Case No. CAC–039)
that grants Fujitsu General Limited
(Fujitsu) a waiver from the DOE
commercial package air-source central
air conditioners and heat pumps test
procedures for determining the energy
consumption set forth in its petition for
waiver. Under today’s decision and
order, Fujitsu shall be required to test
and rate its AIRSTAGE V–II multi-split
heat pump with a capacity of 264,000
Btu/h, and specified compatible indoor
units using American National
Standards Institute (ANSI)/Airconditioning, Heating and Refrigeration
Institute (AHRI) Standard 1230, as
adopted in DOE’s final rule dated May
16, 2012.
DATES: This Decision and Order is
effective November 16, 2012 through
May 12, 2013.
FOR FURTHER INFORMATION CONTACT: Mr.
Bryan Berringer, U.S. Department of
Energy, Building Technologies Program,
Mailstop EE–2J, 1000 Independence
Avenue SW., Washington, DC 20585–
0121. Telephone: (202) 586–0371.
Email: Bryan.Berringer@ee.doe.gov.
Ms. Elizabeth Kohl, U.S. Department
of Energy, Office of the General Counsel,
Mail Stop GC–71, Forrestal Building,
1000 Independence Avenue SW.,
Washington, DC 20585–0103.
Telephone: (202) 586–7796. Email:
mailto:Elizabeth.Kohl@hq.doe.gov.
SUMMARY:
DOE
issues notice of this Decision and Order
in accordance with Title 10 of the Code
of Federal Regulations (10 CFR)
431.401(f)(4). In this Decision and
Order, DOE grants Fujitsu a waiver for
the Airstage V–II multi-split equipment
specified in its waiver submitted on
December 16, 2011. Fujitsu must test
and rate this equipment using ANSI/
AHRI 1230, as adopted in DOE’s final
rule dated May 16, 2012 (77 FR 28928),
as the alternative test procedure. DOE’s
SUPPLEMENTARY INFORMATION:
E:\FR\FM\16NON1.SGM
16NON1
Federal Register / Vol. 77, No. 222 / Friday, November 16, 2012 / Notices
final rule specifies use of ANSI/AHRI
1230, but omits sections 5.1.2 and 6.6.
Today’s decision requires Fujitsu to
make representations concerning the
energy efficiency of this equipment
consistent with the provisions and
restrictions of the alternate test
procedure in the Decision and Order
below, and the representations must
fairly disclose the test results. (42 U.S.C.
6314(d)) The same standard applies to
distributors, retailers, and private
labelers when making representations of
the energy efficiency of this equipment.
Issued in Washington, DC, on November 9,
2012.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
mstockstill on DSK4VPTVN1PROD with NOTICES
Decision and Order
In the Matter of: Fujitsu General
Limited (Fujitsu) (Case No. CAC–039).
I. Background and Authority
Title III, Part C of the Energy Policy
and Conservation Act of 1975 (EPCA),
Pub. L. 94–163 (42 U.S.C. 6311–6317),
established the Energy Conservation
Program for certain industrial
equipment, which includes commercial
air conditioning equipment, the focus of
this decision and order.1 Part C
specifically includes definitions (42
U.S.C. 6311), test procedures (42 U.S.C.
6314), labeling provisions (42 U.S.C.
6315), energy conservation standards
(42 U.S.C. 6313), and the authority to
require information and reports from
manufacturers (42 U.S.C. 6316). With
respect to test procedures, Part C
authorizes the Secretary of Energy (the
Secretary) to prescribe test procedures
that are reasonably designed to produce
results that measure energy efficiency,
energy use, and estimated annual
operating costs, and that are not unduly
burdensome to conduct. (42 U.S.C.
6314(a)(2))
For commercial package airconditioning and heating equipment,
EPCA provides that ‘‘the test procedures
shall be those generally accepted
industry testing procedures or rating
procedures developed or recognized by
the Air-Conditioning and Refrigeration
Institute [ARI] or by the American
Society of Heating, Refrigerating and
Air-Conditioning Engineers [ASHRAE],
as referenced in ASHRAE/IES Standard
90.1 and in effect on June 30, 1992.’’ (42
U.S.C. 6314(a)(4)(A)) If the industry test
procedure for commercial package airconditioning and heating equipment is
amended, EPCA directs the Secretary to
1 For editorial reasons, upon codification in the
U.S. Code, Part C was re-designated Part A–1.
VerDate Mar<15>2010
15:43 Nov 15, 2012
Jkt 229001
amend the corresponding DOE test
procedure unless the Secretary
determines, by rule and based on clear
and convincing evidence, that such a
modified test procedure does not meet
the statutory criteria set forth in 42
U.S.C. 6314(a)(2) and (3). (42 U.S.C.
6314(a)(4)(B))
On December 8, 2006, DOE published
a final rule adopting test procedures for
commercial package air-conditioning
and heating equipment, effective
January 8, 2007. 71 FR 71340. Table 1
to Title 10 of the Code of Federal
Regulations (10 CFR) 431.96 directs
manufacturers of commercial package
air conditioning and heating equipment
to use the appropriate procedure when
measuring energy efficiency of this
equipment. For commercial package airsource equipment with capacities
between 65,000 and 760,000 Btu/h, ARI
Standard 340/360–2004 is the
applicable test procedure.
DOE’s regulations for covered
products and equipment permit a
person to seek a waiver from the test
procedure requirements for covered
commercial equipment if at least one of
the following conditions is met: (1) The
petitioner’s basic model contains one or
more design characteristics that prevent
testing according to the prescribed test
procedures; or (2) the prescribed test
procedures may evaluate the basic
model in a manner so unrepresentative
of its true energy consumption as to
provide materially inaccurate
comparative data. 10 CFR 431.401(a)(1).
Petitioners must include in their
petition any alternate test procedures
known to the petitioner to evaluate the
basic model in a manner representative
of its energy consumption. 10 CFR
431.401(b)(1)(iii). The Assistant
Secretary for Energy Efficiency and
Renewable Energy (Assistant Secretary)
may grant a waiver subject to
conditions, including adherence to
alternate test procedures. 10 CFR
431.401(f)(4). Waivers remain in effect
according to the provisions of 10 CFR
431.401(g).
On December 16, 2011, Fujitsu
submitted a petition for waiver from the
DOE test procedure applicable to
commercial package air-source and
water-source central air conditioners
and heat pumps set forth in 10 CFR
431.96. Fujitsu requested the waiver for
specified basic model of Fujitsu
AIRSTAGE V–II multi-split heat pump
with a capacity of 264,000 Btu/h, and
specified compatible indoor units. The
applicable test procedure for these heat
pumps is ARI 340/360–2004.
Manufacturers are directed to use these
test procedures pursuant to Table 1 of
10 CFR 431.96. Fujitsu seeks a waiver
PO 00000
Frm 00023
Fmt 4703
Sfmt 4703
68753
from the applicable test procedures
under 10 CFR 431.96 on the grounds
that its AIRSTAGE V–II multi-split heat
pumps contain design characteristics
that prevent testing according to the
current DOE test procedures. Fujitsu
requested that DOE allow it to test and
rate its Airstage V–II multi-split heat
pump with a capacity of 264,000 Btu/h,
and specified compatible indoor units
according to the American National
Standards Institute (ANSI)/Airconditioning, Heating and Refrigeration
Institute (AHRI) Standard 1230–2010:
Performance Rating of Variable
Refrigerant Flow (VRF) Multi-Split AirConditioning and Heat Pump
Equipment (AHRI 1230).
On May 16, 2012, DOE published a
final rule (77 FR 28928) adopting
American Society of Heating,
Refrigerating, and Air-Conditioning
Engineers (ASHRAE) Standard 90.1–
2010 (ASHRAE final rule). The
ASHRAE final rule incorporated by
reference ANSI/AHRI 1230–2010 but
omits sections 5.1.2 and 6.6 for the
products addressed in this waiver
request. The rule was effective on July
16, 2012 and requires use of the test
procedure on or after May 13, 2013.
This decision and order (D&O) requires
Fujitsu to use ANSI/AHRI 1230–2010 as
addressed in the DOE’s May 16, 2012
final rule (77 FR 28928) to test and rate
specified models in order to be
consistent with future test procedure
requirements.
II. Fujitsu’s Petition for Waiver:
Assertions and Determinations
In its December 16, 2011 petition,
Fujitsu seeks a waiver from the
applicable test procedures under 10 CFR
431.96 on the grounds that its
AIRSTAGE V–II multi-split heat pumps
contain design characteristics that
prevent testing according to the current
DOE test procedures. Specifically,
Fujitsu asserts that the two primary
factors that prevent testing of its
AIRSTAGE V–II multi-split variable
speed products are the same factors
stated in the waivers that DOE granted
to Mitsubishi Electric & Electronics
America USA, Inc. (Mitsubishi) and
other manufacturers for similar lines of
commercial multi-split air-conditioning
systems:
• Testing laboratories cannot test
products with so many indoor units;
and
• There are too many possible
combinations of indoor and outdoor
units to test. See, e.g., 72 FR 17528
(April 9, 2007) (Mitsubishi); 76 FR
19069 (April 6, 2011) (Daikin); 76 FR
19078 (April 6, 2011) (Mitsubishi); 76
FR 31951 (June 2, 2011) (Carrier); 76 FR
E:\FR\FM\16NON1.SGM
16NON1
68754
Federal Register / Vol. 77, No. 222 / Friday, November 16, 2012 / Notices
50204 (August 12, 2011) (Fujitsu
General Limited); 76 FR 65710 (October
24, 2011) (Mitsubishi).
The AIRSTAGE V–II systems have
operational characteristics similar to the
commercial multi-split products
manufactured by other manufacturers.
As indicated above, DOE has already
granted waivers for these products. The
AIRSTAGE V–II system consists of
multiple indoor units connected to an
air-cooled outdoor unit. These multisplits are used in zoned systems where
an outdoor or water-source unit can be
connected with up to 45 separate indoor
units, which need not be the same
models. According to Fujitsu, the
various indoor and outdoor models can
be connected in a multitude of
configurations, with many thousands of
possible combinations. Consequently,
Fujitsu requested that DOE grant a
waiver from the applicable test
procedures for its AIRSTAGE V–II
product designs until a suitable test
method is prescribed.
For the reasons discussed above, and
because DOE prescribed ANSI/AHRI
1230 as the alternate test procedure in
waivers granted to other manufacturers
(including the grant of Fujitsu’s interim
waiver request (77 FR 13107, Mar. 5,
2012)), DOE determined that the
equipment specified in Fujitsu’s
December 16, 2011 petition contains
design characteristics that prevent
testing according to the DOE test
procedure, and that allowing Fujitsu to
use as an alternate test procedure ANSI/
AHRI 1230, as adopted in DOE’s final
rule dated May 16, 2012 (77 FR 28928),
addresses these testing difficulties.
Consultations With Other Agencies
DOE consulted with the Federal Trade
Commission (FTC) staff concerning the
Fujitsu petition for waiver. The FTC
staff did not have any objections to
granting a waiver to Fujitsu.
mstockstill on DSK4VPTVN1PROD with NOTICES
III. Conclusion
After careful consideration of all the
material that was submitted by Fujitsu
and consultation with the FTC staff, it
is ordered that:
(1) The petition for waiver submitted
by Fujitsu (Case No. CAC–039) is hereby
granted as set forth in the following
paragraphs.
(2) Fujitsu shall be required to test
and rate the following basic model
groups according to the alternate test
procedure set forth in paragraph (3) of
this section.
VerDate Mar<15>2010
15:43 Nov 15, 2012
Jkt 229001
Add-on system
models
AOUA264RLBVG .....
(Module models)
(AOUA72RLBV +
AOUA96RLBV +
AOUA96RLBV)
With nominal cooling capacity of 264,000
Btu/h.
Compatible indoor units for the above
listed outdoor units:
Compact cassette:
AUUA7RLAV, AUUA9RLAV,
AUUA12RLAV, AUUA14RLAV,
AUUA18RLAV and AUUA24RLAV with
nominal cooling capacities of 7,500,
9,500, 12,000, 14,000, 18,000 and 24,000
Btu/hr respectively
Cassette:
AUUB30RLAV and AUUB36RLAV with
nominal cooling capacities of 30,000 and
36,000 Btu/hr respectively
Slim cassette:
AUUB18RLAV and AUUB24RLAV with
nominal cooling capacities of 18,000 and
24,000 Btu/hr respectively
Compact wall mounted:
ASUA7RLAV, ASUE7RLAV,
ASUA9RLAV, ASUE9RLAV,
ASUA12RLAV, ASUE12RLAV,
ASUA14RLAV and ASUE14RLAV with
nominal cooling capacities of 7,500,
7,500, 9,500, 9,500, 12,000, 12,000,
14,000 and 14,000 Btu/hr respectively
Wall mounted:
ASUB18RLAV and ASUB24RLAV with
nominal cooling capacities of 18,000 and
24,000 Btu/hr respectively
Floor/Ceiling (Universal):
ABUA12RLAV, ABUA14RLAV,
ABUA18RLAV and ABUA24RLAV with
nominal cooling capacities of 12,000,
14,000, 18,000, 24,000 Btu/hr
respectively
Ceiling:
ABUA30RLAV and ABUA36RLAV with
nominal cooling capacities of 30,000 and
36,000 Btu/hr respectively
Slim duct:
ARUL7RLAV, ARUL9RLAV,
ARUL12RLAV, ARUL14RLAV and
ARUL18RLAV with nominal cooling
capacities of 7,500, 9,500, 12,000, 14,000
and 18,000 Btu/hr respectively
Middle static pressure duct:
ARUM24RLAV, ARUM30RLAV,
ARUM36RLAV, ARUM48RLAV and
ARUM54RLAV with nominal cooling
capacities of 24,000, 30,000, 36,000,
48,000 and 54,000 Btu/hr respectively
High static pressure duct:
ARUH36RLAV, ARUH48RLAV,
ARUH54RLAV, ARUH60RLAV,
ARUH72RLAV, ARUH90RLAV and
ARUH96RLAV with nominal cooling
capacities of 36,000, 48,000, 60,000,
72,000, 90,000 and 96,000 Btu/hr
respectively
(3) Fujitsu shall not be required to test
the products listed in paragraph (2) of
this section according to the test
procedure for commercial package air
conditioners and heat pumps prescribed
by DOE at 10 CFR 431.96 (ARI Standard
340/360–2004 (incorporated by
PO 00000
Frm 00024
Fmt 4703
Sfmt 9990
reference in 10 CFR 431.95(b)(2)–(3)),
but instead shall use as the alternate test
procedure ANSI/AHRI 1230–2010 as
adopted in DOE’s final rule dated May
16, 2012 (77 FR 28928).
(4) Representations. In making
representations about the energy
efficiency of its Airstage V–II multi-split
equipment, for compliance, marketing,
or other purposes, Fujitsu must fairly
disclose the results of testing under the
DOE test procedure in a manner
consistent with the provisions outlined
below:
(i) For multi-split combinations tested
in accordance with this alternate test
procedure, Fujitsu may make
representations based on those test
results.
(ii) For multi-split combinations that
are not tested, Fujitsu may make
representations based on the testing
results for the tested combination and
that are consistent with one of the
following methods:
(a) Rating of non-tested combinations
according to an alternative rating
method approved by DOE; or
(b) Rating of non-tested combinations
having the same outdoor unit and all
non-ducted indoor units shall be set
equal to the rating of the tested system
having all non-ducted indoor units.
(c) Rating of non-tested combinations
having the same outdoor unit and all
ducted indoor units shall be set equal to
the rating of the tested system having all
ducted indoor units. To be considered a
ducted unit, the indoor unit must be
intended to be connected with ductwork
and have a rated external static pressure
capability greater than zero (0).
(d) Rating of non-tested combinations
having the same outdoor unit and a mix
of non-ducted and ducted indoor units
shall be set equal to the average of the
ratings for the two required tested
combinations.
(5) This waiver amendment shall
remain in effect from the date this
Decision and Order is issued, consistent
with the provisions of 10 CFR
431.401(g). Compliance with the
ASHRAE final rule, (77 FR 28928, May
16, 2012), is required as of May 13,
2013. Therefore, this Decision and
Order is valid through May 12, 2013.
Beginning on May 13, 2013, all
manufacturers must use the ASHRAE
procedures to determine the energy use
of this type of equipment.
Issued in Washington, DC, on November 9,
2012.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
[FR Doc. 2012–27927 Filed 11–15–12; 8:45 am]
BILLING CODE 6450–01–P
E:\FR\FM\16NON1.SGM
16NON1
Agencies
[Federal Register Volume 77, Number 222 (Friday, November 16, 2012)]
[Notices]
[Pages 68752-68754]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2012-27927]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
Office of Energy Efficiency and Renewable Energy
[Case No. CAC-039]
Decision and Order Granting a Waiver Granted to Fujitsu General
Limited From the Department of Energy Commercial Package Air
Conditioner and Heat Pump Test Procedures
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Decision and Order.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (DOE) gives notice of the
decision and order (Case No. CAC-039) that grants Fujitsu General
Limited (Fujitsu) a waiver from the DOE commercial package air-source
central air conditioners and heat pumps test procedures for determining
the energy consumption set forth in its petition for waiver. Under
today's decision and order, Fujitsu shall be required to test and rate
its AIRSTAGE V-II multi-split heat pump with a capacity of 264,000 Btu/
h, and specified compatible indoor units using American National
Standards Institute (ANSI)/Air-conditioning, Heating and Refrigeration
Institute (AHRI) Standard 1230, as adopted in DOE's final rule dated
May 16, 2012.
DATES: This Decision and Order is effective November 16, 2012 through
May 12, 2013.
FOR FURTHER INFORMATION CONTACT: Mr. Bryan Berringer, U.S. Department
of Energy, Building Technologies Program, Mailstop EE-2J, 1000
Independence Avenue SW., Washington, DC 20585-0121. Telephone: (202)
586-0371. Email: Bryan.Berringer@ee.doe.gov.
Ms. Elizabeth Kohl, U.S. Department of Energy, Office of the
General Counsel, Mail Stop GC-71, Forrestal Building, 1000 Independence
Avenue SW., Washington, DC 20585-0103. Telephone: (202) 586-7796.
Email: mailto:Elizabeth.Kohl@hq.doe.gov.
SUPPLEMENTARY INFORMATION: DOE issues notice of this Decision and Order
in accordance with Title 10 of the Code of Federal Regulations (10 CFR)
431.401(f)(4). In this Decision and Order, DOE grants Fujitsu a waiver
for the Airstage V-II multi-split equipment specified in its waiver
submitted on December 16, 2011. Fujitsu must test and rate this
equipment using ANSI/AHRI 1230, as adopted in DOE's final rule dated
May 16, 2012 (77 FR 28928), as the alternative test procedure. DOE's
[[Page 68753]]
final rule specifies use of ANSI/AHRI 1230, but omits sections 5.1.2
and 6.6.
Today's decision requires Fujitsu to make representations
concerning the energy efficiency of this equipment consistent with the
provisions and restrictions of the alternate test procedure in the
Decision and Order below, and the representations must fairly disclose
the test results. (42 U.S.C. 6314(d)) The same standard applies to
distributors, retailers, and private labelers when making
representations of the energy efficiency of this equipment.
Issued in Washington, DC, on November 9, 2012.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
Decision and Order
In the Matter of: Fujitsu General Limited (Fujitsu) (Case No. CAC-
039).
I. Background and Authority
Title III, Part C of the Energy Policy and Conservation Act of 1975
(EPCA), Pub. L. 94-163 (42 U.S.C. 6311-6317), established the Energy
Conservation Program for certain industrial equipment, which includes
commercial air conditioning equipment, the focus of this decision and
order.\1\ Part C specifically includes definitions (42 U.S.C. 6311),
test procedures (42 U.S.C. 6314), labeling provisions (42 U.S.C. 6315),
energy conservation standards (42 U.S.C. 6313), and the authority to
require information and reports from manufacturers (42 U.S.C. 6316).
With respect to test procedures, Part C authorizes the Secretary of
Energy (the Secretary) to prescribe test procedures that are reasonably
designed to produce results that measure energy efficiency, energy use,
and estimated annual operating costs, and that are not unduly
burdensome to conduct. (42 U.S.C. 6314(a)(2))
---------------------------------------------------------------------------
\1\ For editorial reasons, upon codification in the U.S. Code,
Part C was re-designated Part A-1.
---------------------------------------------------------------------------
For commercial package air-conditioning and heating equipment, EPCA
provides that ``the test procedures shall be those generally accepted
industry testing procedures or rating procedures developed or
recognized by the Air-Conditioning and Refrigeration Institute [ARI] or
by the American Society of Heating, Refrigerating and Air-Conditioning
Engineers [ASHRAE], as referenced in ASHRAE/IES Standard 90.1 and in
effect on June 30, 1992.'' (42 U.S.C. 6314(a)(4)(A)) If the industry
test procedure for commercial package air-conditioning and heating
equipment is amended, EPCA directs the Secretary to amend the
corresponding DOE test procedure unless the Secretary determines, by
rule and based on clear and convincing evidence, that such a modified
test procedure does not meet the statutory criteria set forth in 42
U.S.C. 6314(a)(2) and (3). (42 U.S.C. 6314(a)(4)(B))
On December 8, 2006, DOE published a final rule adopting test
procedures for commercial package air-conditioning and heating
equipment, effective January 8, 2007. 71 FR 71340. Table 1 to Title 10
of the Code of Federal Regulations (10 CFR) 431.96 directs
manufacturers of commercial package air conditioning and heating
equipment to use the appropriate procedure when measuring energy
efficiency of this equipment. For commercial package air-source
equipment with capacities between 65,000 and 760,000 Btu/h, ARI
Standard 340/360-2004 is the applicable test procedure.
DOE's regulations for covered products and equipment permit a
person to seek a waiver from the test procedure requirements for
covered commercial equipment if at least one of the following
conditions is met: (1) The petitioner's basic model contains one or
more design characteristics that prevent testing according to the
prescribed test procedures; or (2) the prescribed test procedures may
evaluate the basic model in a manner so unrepresentative of its true
energy consumption as to provide materially inaccurate comparative
data. 10 CFR 431.401(a)(1). Petitioners must include in their petition
any alternate test procedures known to the petitioner to evaluate the
basic model in a manner representative of its energy consumption. 10
CFR 431.401(b)(1)(iii). The Assistant Secretary for Energy Efficiency
and Renewable Energy (Assistant Secretary) may grant a waiver subject
to conditions, including adherence to alternate test procedures. 10 CFR
431.401(f)(4). Waivers remain in effect according to the provisions of
10 CFR 431.401(g).
On December 16, 2011, Fujitsu submitted a petition for waiver from
the DOE test procedure applicable to commercial package air-source and
water-source central air conditioners and heat pumps set forth in 10
CFR 431.96. Fujitsu requested the waiver for specified basic model of
Fujitsu AIRSTAGE V-II multi-split heat pump with a capacity of 264,000
Btu/h, and specified compatible indoor units. The applicable test
procedure for these heat pumps is ARI 340/360-2004. Manufacturers are
directed to use these test procedures pursuant to Table 1 of 10 CFR
431.96. Fujitsu seeks a waiver from the applicable test procedures
under 10 CFR 431.96 on the grounds that its AIRSTAGE V-II multi-split
heat pumps contain design characteristics that prevent testing
according to the current DOE test procedures. Fujitsu requested that
DOE allow it to test and rate its Airstage V-II multi-split heat pump
with a capacity of 264,000 Btu/h, and specified compatible indoor units
according to the American National Standards Institute (ANSI)/Air-
conditioning, Heating and Refrigeration Institute (AHRI) Standard 1230-
2010: Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split
Air-Conditioning and Heat Pump Equipment (AHRI 1230).
On May 16, 2012, DOE published a final rule (77 FR 28928) adopting
American Society of Heating, Refrigerating, and Air-Conditioning
Engineers (ASHRAE) Standard 90.1-2010 (ASHRAE final rule). The ASHRAE
final rule incorporated by reference ANSI/AHRI 1230-2010 but omits
sections 5.1.2 and 6.6 for the products addressed in this waiver
request. The rule was effective on July 16, 2012 and requires use of
the test procedure on or after May 13, 2013. This decision and order
(D&O) requires Fujitsu to use ANSI/AHRI 1230-2010 as addressed in the
DOE's May 16, 2012 final rule (77 FR 28928) to test and rate specified
models in order to be consistent with future test procedure
requirements.
II. Fujitsu's Petition for Waiver: Assertions and Determinations
In its December 16, 2011 petition, Fujitsu seeks a waiver from the
applicable test procedures under 10 CFR 431.96 on the grounds that its
AIRSTAGE V-II multi-split heat pumps contain design characteristics
that prevent testing according to the current DOE test procedures.
Specifically, Fujitsu asserts that the two primary factors that prevent
testing of its AIRSTAGE V-II multi-split variable speed products are
the same factors stated in the waivers that DOE granted to Mitsubishi
Electric & Electronics America USA, Inc. (Mitsubishi) and other
manufacturers for similar lines of commercial multi-split air-
conditioning systems:
Testing laboratories cannot test products with so many
indoor units; and
There are too many possible combinations of indoor and
outdoor units to test. See, e.g., 72 FR 17528 (April 9, 2007)
(Mitsubishi); 76 FR 19069 (April 6, 2011) (Daikin); 76 FR 19078 (April
6, 2011) (Mitsubishi); 76 FR 31951 (June 2, 2011) (Carrier); 76 FR
[[Page 68754]]
50204 (August 12, 2011) (Fujitsu General Limited); 76 FR 65710 (October
24, 2011) (Mitsubishi).
The AIRSTAGE V-II systems have operational characteristics similar
to the commercial multi-split products manufactured by other
manufacturers. As indicated above, DOE has already granted waivers for
these products. The AIRSTAGE V-II system consists of multiple indoor
units connected to an air-cooled outdoor unit. These multi-splits are
used in zoned systems where an outdoor or water-source unit can be
connected with up to 45 separate indoor units, which need not be the
same models. According to Fujitsu, the various indoor and outdoor
models can be connected in a multitude of configurations, with many
thousands of possible combinations. Consequently, Fujitsu requested
that DOE grant a waiver from the applicable test procedures for its
AIRSTAGE V-II product designs until a suitable test method is
prescribed.
For the reasons discussed above, and because DOE prescribed ANSI/
AHRI 1230 as the alternate test procedure in waivers granted to other
manufacturers (including the grant of Fujitsu's interim waiver request
(77 FR 13107, Mar. 5, 2012)), DOE determined that the equipment
specified in Fujitsu's December 16, 2011 petition contains design
characteristics that prevent testing according to the DOE test
procedure, and that allowing Fujitsu to use as an alternate test
procedure ANSI/AHRI 1230, as adopted in DOE's final rule dated May 16,
2012 (77 FR 28928), addresses these testing difficulties.
Consultations With Other Agencies
DOE consulted with the Federal Trade Commission (FTC) staff
concerning the Fujitsu petition for waiver. The FTC staff did not have
any objections to granting a waiver to Fujitsu.
III. Conclusion
After careful consideration of all the material that was submitted
by Fujitsu and consultation with the FTC staff, it is ordered that:
(1) The petition for waiver submitted by Fujitsu (Case No. CAC-039)
is hereby granted as set forth in the following paragraphs.
(2) Fujitsu shall be required to test and rate the following basic
model groups according to the alternate test procedure set forth in
paragraph (3) of this section.
Add-on system models (Module models)
AOUA264RLBVG.............................. (AOUA72RLBV + AOUA96RLBV +
AOUA96RLBV)
With nominal cooling capacity of 264,000 Btu/h.
Compatible indoor units for the above listed outdoor units:
Compact cassette:
AUUA7RLAV, AUUA9RLAV, AUUA12RLAV, AUUA14RLAV, AUUA18RLAV and
AUUA24RLAV with nominal cooling capacities of 7,500, 9,500, 12,000,
14,000, 18,000 and 24,000 Btu/hr respectively
Cassette:
AUUB30RLAV and AUUB36RLAV with nominal cooling capacities of
30,000 and 36,000 Btu/hr respectively
Slim cassette:
AUUB18RLAV and AUUB24RLAV with nominal cooling capacities of
18,000 and 24,000 Btu/hr respectively
Compact wall mounted:
ASUA7RLAV, ASUE7RLAV, ASUA9RLAV, ASUE9RLAV, ASUA12RLAV,
ASUE12RLAV, ASUA14RLAV and ASUE14RLAV with nominal cooling
capacities of 7,500, 7,500, 9,500, 9,500, 12,000, 12,000, 14,000 and
14,000 Btu/hr respectively
Wall mounted:
ASUB18RLAV and ASUB24RLAV with nominal cooling capacities of
18,000 and 24,000 Btu/hr respectively
Floor/Ceiling (Universal):
ABUA12RLAV, ABUA14RLAV, ABUA18RLAV and ABUA24RLAV with nominal
cooling capacities of 12,000, 14,000, 18,000, 24,000 Btu/hr
respectively
Ceiling:
ABUA30RLAV and ABUA36RLAV with nominal cooling capacities of
30,000 and 36,000 Btu/hr respectively
Slim duct:
ARUL7RLAV, ARUL9RLAV, ARUL12RLAV, ARUL14RLAV and ARUL18RLAV with
nominal cooling capacities of 7,500, 9,500, 12,000, 14,000 and
18,000 Btu/hr respectively
Middle static pressure duct:
ARUM24RLAV, ARUM30RLAV, ARUM36RLAV, ARUM48RLAV and ARUM54RLAV
with nominal cooling capacities of 24,000, 30,000, 36,000, 48,000
and 54,000 Btu/hr respectively
High static pressure duct:
ARUH36RLAV, ARUH48RLAV, ARUH54RLAV, ARUH60RLAV, ARUH72RLAV,
ARUH90RLAV and ARUH96RLAV with nominal cooling capacities of 36,000,
48,000, 60,000, 72,000, 90,000 and 96,000 Btu/hr respectively
(3) Fujitsu shall not be required to test the products listed in
paragraph (2) of this section according to the test procedure for
commercial package air conditioners and heat pumps prescribed by DOE at
10 CFR 431.96 (ARI Standard 340/360-2004 (incorporated by reference in
10 CFR 431.95(b)(2)-(3)), but instead shall use as the alternate test
procedure ANSI/AHRI 1230-2010 as adopted in DOE's final rule dated May
16, 2012 (77 FR 28928).
(4) Representations. In making representations about the energy
efficiency of its Airstage V-II multi-split equipment, for compliance,
marketing, or other purposes, Fujitsu must fairly disclose the results
of testing under the DOE test procedure in a manner consistent with the
provisions outlined below:
(i) For multi-split combinations tested in accordance with this
alternate test procedure, Fujitsu may make representations based on
those test results.
(ii) For multi-split combinations that are not tested, Fujitsu may
make representations based on the testing results for the tested
combination and that are consistent with one of the following methods:
(a) Rating of non-tested combinations according to an alternative
rating method approved by DOE; or
(b) Rating of non-tested combinations having the same outdoor unit
and all non-ducted indoor units shall be set equal to the rating of the
tested system having all non-ducted indoor units.
(c) Rating of non-tested combinations having the same outdoor unit
and all ducted indoor units shall be set equal to the rating of the
tested system having all ducted indoor units. To be considered a ducted
unit, the indoor unit must be intended to be connected with ductwork
and have a rated external static pressure capability greater than zero
(0).
(d) Rating of non-tested combinations having the same outdoor unit
and a mix of non-ducted and ducted indoor units shall be set equal to
the average of the ratings for the two required tested combinations.
(5) This waiver amendment shall remain in effect from the date this
Decision and Order is issued, consistent with the provisions of 10 CFR
431.401(g). Compliance with the ASHRAE final rule, (77 FR 28928, May
16, 2012), is required as of May 13, 2013. Therefore, this Decision and
Order is valid through May 12, 2013. Beginning on May 13, 2013, all
manufacturers must use the ASHRAE procedures to determine the energy
use of this type of equipment.
Issued in Washington, DC, on November 9, 2012.
Kathleen B. Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and
Renewable Energy.
[FR Doc. 2012-27927 Filed 11-15-12; 8:45 am]
BILLING CODE 6450-01-P