Energy Conservation Program for Consumer Products: Test Procedures for Refrigerators, Refrigerator-Freezers, and Freezers, 3559-3579 [2012-1341]
Download as PDF
3559
Rules and Regulations
Federal Register
Vol. 77, No. 16
Wednesday, January 25, 2012
This section of the FEDERAL REGISTER
contains regulatory documents having general
applicability and legal effect, most of which
are keyed to and codified in the Code of
Federal Regulations, which is published under
50 titles pursuant to 44 U.S.C. 1510.
The Code of Federal Regulations is sold by
the Superintendent of Documents. Prices of
new books are listed in the first FEDERAL
REGISTER issue of each week.
DEPARTMENT OF ENERGY
10 CFR Part 430
[Docket No. EERE–2009–BT–TP–0003]
RIN 1904–AB92
Energy Conservation Program for
Consumer Products: Test Procedures
for Refrigerators, RefrigeratorFreezers, and Freezers
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
This rulemaking amends the
interim final rule for test procedures for
refrigerators, refrigerator-freezers, and
freezers, issued on December 16, 2010.
Specifically, it amends test procedures
at subpart B, appendices A and B, by
incorporating changes to the interim
final rule that will apply to all
measurements of energy consumption of
newly manufactured products starting
September 15, 2014.
These amendments modify the
required test period for the second part
of the test for products with cycling
compressor systems and long-time
automatic defrost or variable defrost
control and adjust the default values of
maximum and minimum compressor
run time for products with variable
defrost. These changes will ensure a
more accurate measurement of the
energy use of products with variable
defrost control.
DATES: The amendments are effective
February 24, 2012 and are required to
establish compliance with the
applicable energy conservation
standards starting on September 15,
2014.
ADDRESSES: The docket is available for
review at regulations.gov, including
Federal Register notices, framework
documents, public meeting attendee
lists and transcripts, comments, and
sroberts on DSK4TPTVN1PROD with RULES
SUMMARY:
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
other supporting documents/materials.
All documents in the docket are listed
in the regulations.gov index. However,
not all documents listed in the index
may be publicly available, such as
information that is exempt from public
disclosure.
A link to the docket web page can be
found at: https://www.regulations.gov/
#!docketDetail;dct=FR%252BPR%
252BN%252BO%252BSR;rpp=10;
po=0;D=EERE-2009-BT-TP-0003.
This web page will contain a link to
the docket for this rulemaking on the
regulations.gov site. The regulations.gov
web page will contain simple
instructions on how to access all
documents, including public comments,
in the docket.
For further information on how to
review the docket, contact Ms. Brenda
Edwards at (202) 586–2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Mr.
Lucas Adin, U.S. Department of Energy,
Office of Energy Efficiency and
Renewable Energy, Building
Technologies Program, EE–2J, 1000
Independence Avenue SW.,
Washington, DC 20585–0121, (202) 287–
1317, email: Lucas.Adin@ee.doe.gov or
Mr. Michael Kido, U.S. Department of
Energy, Office of the General Counsel,
GC–71, 1000 Independence Avenue
SW., Washington, DC 20585–0121, (202)
586–8145, email:
Michael.Kido@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
Table of Contents
I. Background and Authority
II. Summary of the Final Rule
III. Discussion
A. Products Covered by the Final Rule
B. Compliance Dates for the Amended Test
Procedures
C. Test Procedure Amendments
Incorporated in This Final Rule
1. Default Values for CTL and CTM
2. Modification of Long-Time and Variable
Defrost Test Method To Fully Capture
Energy Use for Temperature Recovery
D. Other Issues
1. Anti-Circumvention Language
2. Refrigeration Products Designed for Sale
With or Without Icemakers
3. Wine Storage and Combination Wine
Storage Products
4. Multiple Compressor Systems
5. Triangulation
E. Compliance With Other EPCA
Requirements
1. Test Burden
2. Changes in Measured Energy Use
PO 00000
Frm 00001
Fmt 4700
Sfmt 4700
IV. Procedural Requirements
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under the Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
V. Approval of the Office of the Secretary
I. Background and Authority
Title III of the Energy Policy and
Conservation Act (42 U.S.C. 6291, et
seq.; ‘‘EPCA’’ or, ‘‘the Act’’) sets forth a
variety of provisions designed to
improve energy efficiency. (All
references to EPCA refer to the statute
as amended through the Energy
Independence and Security Act of 2007
(EISA 2007), Public Law 110–140 (Dec.
19, 2007)). Part B of title III (42 U.S.C.
6291–6309), which was subsequently
redesignated as Part A for editorial
reasons, establishes the ‘‘Energy
Conservation Program for Consumer
Products Other Than Automobiles.’’
Refrigerators, refrigerator-freezers, and
freezers (collectively referred to below
as ‘‘refrigeration products’’) are all
treated as ‘‘covered products’’ under
this Part. (42 U.S.C. 6291(1)–(2) and
6292(a)(1)) Under the Act, this program
consists essentially of three parts: (1)
Testing, (2) labeling, and (3) Federal
energy conservation standards. The
testing requirements consist of test
procedures that manufacturers of
covered products must use (1) as the
basis for certifying to the U.S.
Department of Energy (DOE) that their
products comply with the applicable
energy conservation standards adopted
under EPCA, and (2) for making
representations about the efficiency of
those products. Similarly, DOE must use
these test requirements to determine
whether the products comply with any
relevant standards promulgated under
EPCA.
By way of background, the National
Appliance Energy Conservation Act of
1987 (NAECA), Public Law 100–12,
E:\FR\FM\25JAR1.SGM
25JAR1
sroberts on DSK4TPTVN1PROD with RULES
3560
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
amended EPCA by including, among
other things, performance standards for
refrigeration products. (42 U.S.C.
6295(b)) On November 17, 1989, DOE
amended these performance standards
for products manufactured on or after
January 1, 1993. 54 FR 47916. DOE
subsequently published a correction to
revise these new standards for three
product classes. 55 FR 42845 (October
24, 1990). DOE again updated the
performance standards for refrigeration
products on April 28, 1997, for products
manufactured on or after July 1, 2001.
62 FR 23102.
EISA 2007 amended EPCA by
requiring DOE to publish a final rule
determining whether to amend the
energy conservation standards for
refrigeration products manufactured
starting in 2014. (42 U.S.C. 6295(b)(4))
Consistent with this requirement, DOE
issued on September 18, 2008, a
framework document that outlined a
series of issues related to its
examination of potential amendments to
the standards for refrigeration products.
73 FR 54089. On September 29, 2008,
DOE held a public workshop to discuss
the framework document and the issues
it raised. The framework document
identified several test procedure issues,
including: (1) Compartment temperature
changes; (2) modified volume
calculation methods; (3) products that
deactivate energy-using features during
energy testing; (4) variable anti-sweat
heaters; (5) references to the updated
AHAM Standard HRF–1–2008, (‘‘HRF–
1–2008’’), ‘‘Energy and Internal Volume
of Refrigerating Appliances (2008),’’
developed by the Association of Home
Appliance Manufacturers (AHAM),
including the ‘‘Errata to Energy and
Internal Volume of Refrigerating
Appliances, Correction Sheet’’ issued on
November 17, 2009; (6) convertible
compartments; and (7) harmonization
with international test procedures.
(‘‘Energy Conservation Standards
Rulemaking Framework Document for
Residential Refrigerators, RefrigeratorFreezers, and Freezers,’’ RIN 1904–
AB79, Docket No. EERE–2008–BT–
STD–0012). DOE conducted analyses
and developed new energy conservation
standards for refrigeration products that
led to the eventual publication of the
final rule adopting new energy
conservation standards for refrigeration
products manufactured starting
September 15, 2014. See 76 FR 59516
(Sept. 15, 2011) (‘‘standards final rule’’)
and 76 FR 70865 (Nov. 16, 2011) (date
correction notice).
DOE initiated the test procedure
rulemaking in part to address the issues
identified in the framework document,
and published a notice of proposed
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
rulemaking on May 27, 2010, hereafter
referred to as ‘‘the NOPR.’’ 75 FR 29824.
In response to issue (3) above, as
applied to automatic icemakers, DOE
separately published a guidance
document addressing various aspects
related to the icemaker, including the
proper manner in which to render an
icemaker inoperative for the energy
consumption test. See 75 FR 2122 (Jan.
14, 2010). DOE held a public meeting to
discuss the NOPR proposals on June 22,
2010 and subsequently published the
combined final/interim-final rule on
December 16, 2010. 75 FR 78810. The
final rule (or ‘‘December 2010 final
rule’’) implemented test procedure
amendments applicable to products
manufactured before the effective date
of the new energy conservation
standards that DOE had been
considering, and the interim final rule
(or ‘‘interim final rule’’) implemented
on an interim basis test procedure
amendments applicable to products
subject to the new energy conservation
standards—i.e., those products
manufactured starting September 15,
2014. Id. DOE adopted this split
approach in response to industry
requests to provide an additional
opportunity to comment on final aspects
related to the interim final rule. Id. at
78845.
General Test Procedure Rulemaking
Process
Under 42 U.S.C. 6293, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered products.
EPCA provides in relevant part that
‘‘[a]ny test procedures prescribed or
amended under this section shall be
reasonably designed to produce test
results which measure energy
efficiency, energy use * * * or
estimated annual operating cost of a
covered product during a representative
average use cycle or period of use, as
determined by the Secretary [of Energy],
and shall not be unduly burdensome to
conduct.’’ (42 U.S.C. 6293(b)(3))
In addition, if DOE determines that a
test procedure amendment is warranted,
it must publish proposed test
procedures and offer the public an
opportunity to present oral and written
comments. (42 U.S.C. 6293(b)(2)) When
considering amending a test procedure,
DOE must determine ‘‘to what extent, if
any, the proposed test procedure would
alter the * * * measured energy use
* * * of any covered product as
determined under the existing test
procedure.’’ (42 U.S.C. 6293(e)(1)) If
DOE determines that the amended test
procedure would alter the measured
energy use of a covered product, DOE
PO 00000
Frm 00002
Fmt 4700
Sfmt 4700
must also amend the applicable energy
conservation standard accordingly. (42
U.S.C. 6293(e)(2))
With respect to today’s rulemaking,
DOE has determined that none of the
amendments adopted in this final rule
notice is likely to significantly change
the measured energy use of refrigeration
products when compared to the test
procedure set forth in the interim final
rule. In such situations, EPCA does not
require a standards rulemaking to
address such changes in measured
energy efficiency. (42 U.S.C. 6293(e)(2)).
Today’s rule also fulfills DOE’s
obligation to periodically review its test
procedures under 42 U.S.C.
6293(b)(1)(A). DOE anticipates that its
next evaluation of this test procedure
will occur in a manner consistent with
the timeline set out in this provision.
Refrigerators and Refrigerator-Freezers
DOE’s test procedures for refrigerators
and refrigerator-freezers are found at 10
CFR part 430, subpart B, appendices A1
(currently in effect) and A (required for
rating of products starting September
15, 2014). DOE initially established its
test procedures for refrigerators and
refrigerator-freezers in a final rule
published in the Federal Register on
September 14, 1977. 42 FR 46140.
Industry representatives viewed these
test procedures as too complex and
eventually developed alternative test
procedures in conjunction with AHAM
that were incorporated into the 1979
version of HRF–1, ‘‘Household
Refrigerators, Combination RefrigeratorFreezers, and Household Freezers’’
(HRF–1–1979). Using this industrycreated test procedure, DOE revised its
test procedures on August 10, 1982. 47
FR 34517. On August 31, 1989, DOE
published a final rule establishing test
procedures for variable defrost control
(a control type in which the time
interval between successive defrost
cycles is determined by operating
conditions indicating the need for
defrost rather than by compressor run
time), dual compressor refrigeratorfreezers, and freezers equipped with
‘‘quick-freeze’’ (a manually-initiated
feature that bypasses the thermostat and
runs the compressor continuously until
terminated). 54 FR 36238. DOE
amended the test procedures again on
March 7, 2003, by modifying the test
period used for products equipped with
long-time automatic defrost (a control
type in which defrost cycles are
separated by 14 hours or more of
compressor run time) or variable
defrost. 68 FR 10957. The test
procedures include provisions for
determining the annual energy use in
E:\FR\FM\25JAR1.SGM
25JAR1
sroberts on DSK4TPTVN1PROD with RULES
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
kilowatt-hours (kWh) and the
accompanying annual operating costs.
DOE further amended the test
procedures on December 16, 2010. 75
FR 78810. These amendments helped
clarify how to test products for
compliance with the applicable
standards. The amendments clarified
certain elements in Appendix A1 to
ensure that regulated entities fully
understand how to apply and
implement the test procedure. These
changes included clarifying how
refrigeration products equipped with
special compartments and/or more than
one fresh food compartment or more
than one freezer compartment should be
tested. The amendments also accounted
for the various waivers granted by DOE,
specifically with regard to variable antisweat heater controls. The final rule also
modified the regulatory definition of
‘‘electric refrigerator-freezer’’ to require
that storage temperatures in the fresh
food compartment be at a level that
would effectively exclude coverage of
combination wine storage-freezer
products. See 10 CFR 430.2. The
definition for ‘‘electric refrigerator’’ was
also changed to clarify the
characteristics that distinguish it from
related products such as wine storage
products. DOE is considering modifying
its product definitions to address wine
storage products in a separate future
rulemaking.
In that same notice, DOE also
established a new Appendix A, via an
interim final rule. The new Appendix A
included a number of comprehensive
changes to help improve the
measurement of energy consumption of
refrigerators and refrigerator-freezers.
These changes included, among other
things: (1) New compartment
temperatures and volume adjustment
factors, (2) new methods for measuring
compartment volumes, (3) a
modification of the long-time automatic
defrost test procedure to ensure that the
test procedure measures all energy use
associated with the defrost function,
and (4) test procedures for products
with a single compressor and multiple
evaporators with separate active defrost
cycles. DOE noted that the compartment
temperature changes introduced by
Appendix A would significantly impact
the measured energy use and affect the
calculated adjusted volume and energy
factor (i.e. adjusted volume divided by
energy use) values. Lastly, the interim
final rule also addressed icemaking
energy use by including a fixed value
for manufacturers to add when
calculating the energy consumption of
those products equipped with an
automatic icemaker. DOE may consider
revising this approach once a more
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
appropriate means of accounting for this
feature’s energy consumption is
developed.
Freezers
DOE’s test procedures for freezers are
found at 10 CFR part 430, subpart B,
appendices B1 (currently in effect) and
B (required for the rating of products
starting in 2014). DOE established its
test procedures for freezers in a final
rule published in the Federal Register
on September 14, 1977. 42 FR 46140. As
with DOE’s test procedures for
refrigerators and refrigerator-freezers,
industry representatives viewed the
freezer test procedures as too complex
and worked with AHAM to develop
alternative test procedures, which were
incorporated into the 1979 version of
HRF–1. DOE revised its test procedures
for freezers based on this AHAM
standard on August 10, 1982. 47 FR
34517. The subsequent August 31, 1989
final rule established test procedures for
freezers with variable defrost control
and freezers with the quick-freeze
feature. 54 FR 36238. A subsequent
amendment occurred to correct that
rule’s effective date. 54 FR 38788 (Sept.
20, 1989). The current test procedures
include provisions for determining the
annual energy use in kWh and annual
electrical operating costs for freezers.
The December 16, 2010 notice also
clarified compliance testing
requirements for freezers under
Appendix B1 and created a new
Appendix B, the latter of which would
apply in 2014. That new procedure
changed a number of aspects to the
procedure detailed in Appendix B1,
including, among other things: (1) The
freezer volume adjustment factor, (2)
methods for measuring compartment
volumes, and (3) the long-time
automatic defrost test procedure. In
addition, Appendix B also addresses
icemaking energy use by implementing
the same procedure as for refrigeratorfreezers in which a fixed energy use
value is applied when calculating the
energy consumption of freezers with
automatic icemakers.
Finalization of the Test Procedure
Rulemaking for Products Manufactured
Starting in 2014
The interim final rule established
comprehensive changes to the manner
in which the test procedures are
conducted by creating new Appendices
A and B. In addition to the changes
discussed above, these appendices
incorporate the recent changes made to
Appendices A1 and B1. These new
appendices also incorporate the
modifications to Appendices A1 and B1
PO 00000
Frm 00003
Fmt 4700
Sfmt 4700
3561
that were finalized and adopted on
December 16, 2010.
DOE had provided an initial comment
period on the interim final rule that
ended on February 14, 2011. DOE
subsequently reopened the comment
period on September 15, 2011 (76 FR
57612) to allow further public feedback
in response to the promulgation of the
final energy conservation standards that
were published on the same day. 76 FR
57516. DOE reopened the comment
period to permit interested parties to
comment on the interplay between the
test procedure and the energy
conservation standards in order to
permit DOE to make any final changes
that may be needed to the final test
procedure for products that will be
manufactured starting in 2014. 76 FR
57612–57613 (Sept. 15, 2011). The
comment period ended on October 17,
2011.
Three stakeholders submitted
comments in response to both
supplemental comment periods that
DOE provided for additional feedback—
the Association of Home Appliance
Manufacturers (AHAM), Sub Zero-Wolf,
Inc. (Sub Zero), and Whirlpool
Corporation (Whirlpool). Table I.1
below identifies these commenters and
their affiliation. No other comments
were received.
TABLE I.1—STAKEHOLDERS THAT SUBMITTED COMMENTS ON THE INTERIM
FINAL RULE
Name
Acronym
Association of
Home Appliance
Manufacturers.
Sub Zero-Wolf, Inc
Whirlpool Corporation.
AHAM ..............
IR
Sub Zero ..........
Whirlpool ..........
M
M
* IR:
Industry
Manufacturer.
Representative;
Type*
M:
DOE also considered comments
related to a petition for a test procedure
waiver (RF–018, Samsung) that had a
direct bearing on elements of the test
procedures used in Appendix A. See 76
FR 16760 (March 25, 2011).
II. Summary of the Final Rule
Today’s rulemaking finalizes the test
procedures that manufacturers must
follow when certifying basic models as
compliant with the new energy
conservation standards starting in 2014.
In finalizing these procedures, DOE
made minor changes to the procedure
laid out in the December 2010 interim
final rule to account for comments from
interested parties. The changes will not
result in a significant change in
measured energy use when compared to
E:\FR\FM\25JAR1.SGM
25JAR1
3562
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
the procedure detailed in the interim
final rule. The December 2010
amendments for Appendices A1 and B1
are unchanged by today’s rulemaking
and continue to apply to products
manufactured through September 14,
2014. (Those aspects of the December
2010 notice were not reopened for
comment as they were not part of the
interim final rule. 75 FR at 78813–78815
(Dec. 16, 2010).) In addition, other
amendments made in the December
2010 final rule, including modified
definitions, anti-circumvention
language, applying the anti-sweat heater
switch credit to energy use
measurements, and rounding off energy
test results also were not part of the
interim final rule and were not
reopened for comment. Accordingly,
these aspects of the December 2010
notice remain unchanged.
Today’s rulemaking makes a series of
changes that include (a) modifying the
default values of CTL and CTM,
parameters, which represent the
minimum and maximum compressor
run time between defrosts, for products
with variable defrost that do not have
values for these parameters specified in
their control algorithms, and (b)
modifying the test period for products
with cycling compressors and long-time
or variable defrost to ensure the
procedure accurately captures energy
use associated with temperature
recovery after defrost. The rulemaking
also makes changes to clarify how to
apply the second part of the test for
products with long-time or variable
defrost.
III. Discussion
The following section discusses in
further detail the various issues
addressed by today’s rulemaking. These
issues center chiefly on issues raised in
commenter submissions. Section A
identifies the products covered by the
rule; section B specifies the compliance
dates for the test procedure amendments
made; section C discusses the test
procedure amendments; and section D
discusses stakeholder comments not
associated with new amendments.
sroberts on DSK4TPTVN1PROD with RULES
A. Products Covered by the Final Rule
Today’s amendments cover those
products that meet the definitions for
refrigerator, refrigerator-freezer, and
freezer, as codified in 10 CFR 430.2. The
definitions for refrigerator and
refrigerator-freezer were amended in the
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
December 2010 final rule on December
16, 2010. 75 FR 78810, 78817.
Today’s rulemaking does not change
any of the definitions for refrigeration
products that DOE amended as part of
the December 2010 final rule. While
DOE appreciates the concerns raised by
commenters, these particular issues
were not completely vetted through the
rulemaking process. DOE may, however,
revisit and more closely examine these
issues as part of a future rulemaking
activity. Section D.3 discusses the
comments related to wine storage and
wine storage combination products,
including the amended definitions for
refrigerator and refrigerator-freezer.
B. Compliance Dates for the Amended
Test Procedures
Manufacturers will need to use new
Appendices A and B to rate refrigeration
products once they are required to
comply with the amended energy
conservation standards—i.e. September
15, 2014. Likewise, Appendices A and
B will be mandatory for representations
regarding energy use or operating cost of
these products starting on that date.
C. Test Procedure Amendments
Incorporated in This Final Rule
Today’s rulemaking finalizes
Appendices A and B, with some
amendments. These amendments are
described in greater detail below.
1. Default Values for CTL and CTM
Refrigeration products with variable
defrost vary the frequency of defrost by
reducing this frequency to save energy
when the frost accumulation rate on the
evaporator drops—such as when the
number of door openings is reduced or
when ambient humidity is low. Defrost
frequency is characterized by the
compressor run time between defrosts,
CT, which is expressed in the test
procedure in hours rounded to the
nearest tenth of an hour. Variable
defrost control algorithms vary CT as
the defrost need changes. These
algorithms may specify a minimum CT
value (CTL) and a maximum CT value
(CTM), consistent with the minimum
and maximum defrost frequencies
required for specific products to provide
reliable defrost performance while
minimizing energy use. The DOE test
procedure calculates the energy use of
variable defrost products using a
weighted average of the algorithm’s CTL
and CTM. See 75 FR at 78857, 78865
(Dec. 16, 2010) (detailing requirements
PO 00000
Frm 00004
Fmt 4700
Sfmt 4700
of section 5.2.1.3 of new Appendix A
and existing Appendix A1,
respectively). To address those products
that may have control algorithms that do
not use specific maximum and
minimum values for the compressor run
time between defrost cycles, the test
procedure specifies a CTL value of 12
hours and a CTM value of 84 hours. See
id. These values remained the same for
both Appendix A1 (final rule) and
Appendix A (interim final rule).
AHAM argued that the default CTL
and CTM values for the variable defrost
control algorithm should be changed to
6 and 96 hours in order to maintain
consistency with HRF–1–2008. (AHAM,
No. 39 at p. 5) AHAM did not provide
any supporting data to show that these
values would be more representative of
the operation of refrigeration products
with variable defrost control algorithms
without specific CT values, nor did it
provide any justification for the change
other than to maintain consistency with
HRF–1–2008.
In light of AHAM’s comments, DOE
reviewed the certification data
submitted by refrigeration product
manufacturers in August 2011 and
specifically examined the submissions
of those products with variable defrost
to determine the prevalence of different
values for CTL and CTM. DOE also
investigated whether the certification
data showed any evidence of products
without specified CT values, since these
would be the products whose energy
use measurement would be affected by
the change suggested by AHAM. Of
2,674 records in the database, 1,397
products were identified as having
variable defrost. None of the records for
these products included undeclared
values for CTL and CTM. Table III.1
below shows the default CTL and CTM
values of the current test procedure and
of HRF–1–2008. It also shows the
average, mean, and most prevalent
values for CTL and CTM gleaned from
available certification records. For each
of these CTL and CTM combinations, the
calculated CT value is also presented.
The summary table shows that neither
the 12 and 84 default values nor the
AHAM-suggested values of 6 and 96
provide an exact representation of the
products in the database. However, the
data below also suggest that using 6 and
96 as default values more closely
approximates the recorded values of
those refrigeration products from the
database than 12 and 84.
E:\FR\FM\25JAR1.SGM
25JAR1
3563
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
TABLE III.1—VALUES OF CTL, CTM AND CT
CTL
Current DOE Test Procedure Default .............................................................................
HRF–1–2008 Default .......................................................................................................
Database Average ...........................................................................................................
Database Median .............................................................................................................
Database Most Prevalent Values ....................................................................................
CTM
12.0
6.0
8.0
8.0
8.0
CT
84.0
96.0
82.3
96.0
96.0
38.2
24.0
*28.8
30.0
30.0
* This is the CT calculated using the average CTM and CTL values. The average of the CT values calculated individually for each database
record is 28.2.
Further, the use of the default CTL
and CTM values is prescribed for those
products that do not have specific
values for these parameters in the
product’s control algorithm. Since the
algorithm for such a product
presumably does not explicitly set a
minimum value for this time period, it
is conceivable that the compressor run
time between defrosts could at times be
lower than the 6 hours specified in the
test procedure as a minimum for CTL
(see section 5.2.1.3 of Appendix A1 or
A). When operating in this mode, such
a product would be using more energy
for defrost than would a product with
an algorithm-defined CTL of 6 hours,
due to the higher defrost frequency.
Hence, DOE concludes that to ensure
that the test procedure provides a
conservative estimate of energy use
associated with defrost (i.e. at least as
high as the actual energy use), it is
reasonable to require use of a lower
default CTL value when calculating
energy use for products that do not have
algorithm-specified CTL values. For this
reason, because the HRF–1–2008 default
values are more representative of the
refrigeration products in the database
than the current default values, and in
order to maintain consistency with this
industry standard, DOE is changing the
default values to 6 and 96 in this final
rule. This change is being made for
refrigerators, refrigerator-freezers, and
freezers in both Appendices A and B.
2. Modification of Long-Time and
Variable Defrost Test Method To Fully
Capture Energy Use for Temperature
Recovery
sroberts on DSK4TPTVN1PROD with RULES
Background
The interim final rule amended the
test procedure for products with longtime and variable defrost by modifying
the second part of the test to better
capture energy use associated with
precooling and temperature recovery. 75
FR 78810, 78832–78836 (Dec. 16, 2010).
A test procedure waiver petition
submitted by Samsung (see 76 FR 17670
(March 25, 2011)) has raised the
question of whether DOE should
consider further changes to the second
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
part of the test procedure for these
products.
As described in DOE’s December 2010
notice, precooling involves cooling the
compartment(s) of a refrigerator-freezer
to temperatures significantly lower than
the user-selected temperature settings
prior to an automatic defrost cycle. Id.
at 78832. The document also noted that
the two-part test served as a means to
reduce the burden on testing long-time
and variable defrost products. Id. These
products initiate defrost cycles after
significantly longer periods of
compressor run time than conventional
automatic defrost products. Long-time
defrost products initiate defrost after
more than 14 hours of compressor run
time, and variable defrost products
adjust defrost frequency based on
whether defrost is needed, potentially
delaying the next defrost up to 96 hours
of compressor run time. The second part
of the test measures the energy use
consumed during a defrost cycle.
The two-part test and procedures for
the second part of the test were initially
established in 1982. 47 FR 34521–34522
(Aug. 10, 1982). Since that time, more
sophisticated controls have replaced the
mechanical defrost timers that were
generally used. 68 FR 10958 (March 7,
2003). Consequently, the initial
procedures for the second part of the
test did not fully capture or consider the
high level of sophistication that is now
possible and made available with the
use of modern electronic control
systems. The defrost controls in use
when the second part of the test was
first established consisted of a
mechanical defrost timer energized to
advance when the compressor is
energized. The initial two-part test
specified that the second part starts
when the heater energizes, which is
coincident with the time the compressor
turns off in a product using a
mechanical timer control. 68 FR 10957–
10958 (March 7, 2003). The first
adjustment of the test procedure
considering the potential for more
sophisticated control was made on
March 7, 2003. This amendment of the
test procedure revised the second part of
the test to allow it to start when the
PO 00000
Frm 00005
Fmt 4700
Sfmt 4700
compressor turns off prior to activation
of the defrost heater, which is typical of
an approach enabled by more
sophisticated electronic controls. Id.
The interim final rule made
additional amendments to the second
part of the test to address precooling,
another defrost control feature requiring
more sophisticated control than a
mechanical timer. 75 FR 78832–78836
(Dec. 16, 2010). The amendments also
addressed partial temperature recovery,
which refers to a case in which the
compartment temperatures of a
refrigerator partially recover, but do not
reach, their steady-state operating
temperatures. For the purposes of
testing, a product is considered to reach
a state of partial temperature recovery
when compartment temperatures do not
reach the steady-state operating
temperature by the end of the second
part of the test (as previously specified
in the test procedure) after the rise in
compartment temperature associated
with defrost. The amendments require,
for a system with a cycling compressor,
that the average compartment
temperatures for the compressor cycles
occurring immediately before and after
the test period for the second part of the
test be within 0.5 °F of the compartment
temperature measured for the first part
of the test. Under the interim final rule’s
procedure, the modified test period
would start at the end of a compressor
‘‘on’’ cycle and end at the start of a
compressor ‘‘on’’ cycle. Id. at 73885
Additional Issue Identified During
Review of Samsung Waiver
After publication of the interim final
rule, an additional issue associated with
the two-part test was raised during the
agency’s review of a test procedure
waiver petition submitted by Samsung
Electronics America, Inc. (Samsung).
That petition sought a waiver from the
current test requirements for the
company’s products that use dual
evaporators. 76 FR 16760 (March 25,
2011).1 These products use a variable
1 The evaporator is the component of a
refrigeration system that cools the cabinet air. Most
conventional refrigerators use a single evaporator
E:\FR\FM\25JAR1.SGM
Continued
25JAR1
3564
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
sroberts on DSK4TPTVN1PROD with RULES
defrost strategy that employs multiple
defrost cycle types, which the interim
final rule’s procedure addresses for
products starting in 2014. 75 FR at
78836–78838 (Dec. 16, 2010). DOE
explained in the December 2010 notice
that Appendices A1 and B1 do not
address such products and
manufacturers seeking to certify these
types of products as compliant prior to
2014 must first obtain a test procedure
waiver to enable them to test these
products. Id. at 78838. Samsung sought
a waiver to permit the company to use
the Appendix A procedures for products
with multiple defrost cycle types when
rating current products. 76 FR at 16763
(March 25, 2011).
Whirlpool commented in response to
Samsung’s waiver petition that applying
the second part of the test to the fresh
food defrost of one of these products
results in an energy credit. (Whirlpool,
Samsung Petition for Test Procedure
Waiver, Case No. RF–018, Docket No.
EERE–2011–BT–WAV–0017, No. 4 at p.
3) 2 Whirlpool’s waiver comments
discuss the data from testing performed
by the Canadian Standards Association
that examined the energy consumption
of a Samsung model that uses multiple
defrost cycles—Samsung model No.
RFG297AAPN. Whirlpool asserts that
the test results are illogical because the
energy use contribution of the fresh food
compartment defrost is negative (i.e. an
energy credit), and adds that the energy
use contribution of the freezer
compartment defrost is underestimated.
(Id. at p. 4) Whirlpool recommended
that the test period for the second
(defrost) part of the test for the fresh
food defrost should end at the end of the
second compressor ‘‘on’’ cycle after
defrost, and that such a change to the
test procedure only for the fresh food
defrost would increase the measured
energy use of the product by 1.6
percent. (Id. at pp. 5–6)
Samsung’s response to Whirlpool’s
comment pointed out that the potential
energy credit issue had been raised by
DOE in its test procedure NOPR public
meeting on June 22, 2010. (Samsung,
Samsung Petition for Test Procedure
Waiver, Case No. RF–018, Docket No.
EERE–2011–BT–WAV–0017, No. 5 at
p. 2) In its view, this issue had been
that cools the freezer compartment, transferring
cold freezer air to the fresh food compartment to
cool the latter compartment. Samsung’s dual
evaporator approach uses separate evaporators in
the freezer and fresh food compartments and does
not exchange air between the compartments.
2 The Samsung waiver docket items have been
consolidated and loaded into the docket for this
refrigerator test procedure rulemaking, see
‘‘Documents Related to Samsung Waiver—Case No.
RF–018, Docket No. EERE–2011–BT–WAV–0017’’,
No. 45.
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
presented by DOE for discussion and
consideration by all interested parties—
including Whirlpool. The company
pointed out that the test procedure DOE
ultimately selected had received the
support of Whirlpool. Id. See also
Whirlpool, No. 13 at p. 6.
DOE’s Previous Discussion Regarding
the Appropriate End of the Test Period
As indicated by Samsung, DOE raised
this issue of Appendix A1’s potential
inability to capture all energy usage
during defrost cycles when using the
second (defrost) part of the test. (NOPR
Public Meeting Presentation, No. 9 at p.
53) DOE recognized this possibility
during its evaluation of the energy use
associated with the fresh food
compartment defrost of a Samsung
product similar to the products
addressed in the company’s test
procedure waiver request. That
evaluation indicated that the calculated
energy use contribution from the fresh
food defrost was often negative, which
resulted in an energy use ‘‘credit’’. DOE
evaluated alternative test periods and
concluded that more reasonable results
are obtained when the test period ends
at the end of a compressor cycle after
the defrost cycle. (Id.) DOE sought
comment during its public meeting to
seek additional information on the
issues associated with the long-time
defrost test method that were presented.
(Id. at p. 55)
DOE’s presentation also indicated that
it projected that the impact on measured
energy use of the test procedure change
would be an increase of approximately
3 percent, if applied to both defrosts of
the Samsung product that was the focus
of the discussion. (Id. at p. 53) This 3
percent impact was determined based
on moving the end of the test period for
the second part of the test from the
second compressor start after defrost to
the second compressor stop. DOE again
reviewed the same data and concluded
that the test procedure change
associated with this final rule would
reduce this measured energy use
differential by half (i.e. 1.5 percent).
(‘‘Summary of Energy Use
Measurements for a Refrigerator-Freezer
with two Defrost Cycle Types’’, No. 46)
The interim final rule test procedure
applied to this product does not allow
the second part of the test to end at the
second compressor start after defrost,
due to the requirement that the average
temperature for the compressor cycle
immediately following the test period be
within 0.5 °F of the average temperature
measured for the first part of the test.
(See Appendix A, section 4.2.1.1)
Hence, the impact on energy use
measurement associated with test
PO 00000
Frm 00006
Fmt 4700
Sfmt 4700
procedure changes to address the
observed negative energy use
measurement associated with freshfood-only defrost cycles depends on
details of the compared test periods.
Stakeholders generally supported the
test procedure approach as proposed in
the Notice of Proposed Rulemaking
(NOPR)—and as adopted in the interim
final rule—and none suggested that the
test period of the second part of the test
should be changed to address the
anomaly presented, i.e. that
measurements for a specific product
showed a negative energy use
contribution associated with the fresh
food defrost. Hence, DOE concluded
that the anomaly was associated with an
insignificant number of products and
thus not generally significant to the test
procedure for products tested using the
two-part test. Consequently, in the
interim final rule, DOE did not amend
the end of the test period for the second
part of the test to coincide with the end
of a compressor ‘‘on’’ cycle (rather than
the start of that cycle).
Comment Submitted in Response to the
Reopening of the Comment Period
After considering Whirlpool’s waiver
petition comments suggesting that DOE
modify the second part of the test, DOE
specifically requested comment on this
topic when it reopened the interim final
rule comment period. 76 FR 57613–
57614 (Sept. 15, 2011). DOE received
one comment on this topic, from
Whirlpool, which suggested that the end
of the second part of the test be moved
so that it coincides with the end of a
compressor ‘‘on’’ cycle. (Whirlpool, No.
44 at pp. 1–2) Whirlpool asserted that
this change should be made for all
defrosts, whether they are for fresh food
compartments or freezer compartments.
Whirlpool indicated that, for at least
one product, the impact of this test
procedure change on the measured
energy use for a product having a
separate defrost for the fresh food
compartment would be an increase of
approximately 3 percent. Although
Whirlpool did not identify the
manufacturer of that product, it
mentioned that its concerns are an
extension of those concerns it raised
earlier in response to a waiver request
made by a competitor—i.e. Samsung.
The 3 percent impact cited by
Whirlpool matches the CSA data
presented in Whirlpool’s comments
regarding the Samsung waiver petition:
the waiver comments indicate that the
tested product’s energy use increases
from 572.5 kWh to 592.1 kWh per year
(an increase of 3.4 percent) with the
modified test procedure, i.e. when
ending the second part of the test at the
E:\FR\FM\25JAR1.SGM
25JAR1
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
sroberts on DSK4TPTVN1PROD with RULES
end rather than the start of the second
compressor ‘‘on’’ cycle after the defrost.
(Whirlpool, Samsung Petition for Test
Procedure Waiver, Case No. RF–018,
Docket No. EERE–2011–BT–WAV–0017,
No. 4 at p. 5) This projected impact on
the measured energy use is consistent
with DOE’s own conclusions regarding
Samsung products with multiple
defrosts. See NOPR Public Meeting
Presentation, No. 9 at p. 53. However, as
discussed above, it overestimates the
measurement impact associated with
the amendments made in this final rule.
Assessment of the Suggested Test Period
Modification
Whirlpool’s interim final rule
comments provided little or no
explanation of how and why the
suggested test period will result in more
accurate test results. Instead, the
comments indicate that the ‘‘underlying
principle when measuring the energy
consumption of any product which
operates in cycles is to measure from the
same point in one cycle to the same
point in a successor cycle,’’ and assert
that the test procedure of Appendix A
measures from a compressor stop to a
compressor start for products with
cycling compressors. However,
Whirlpool did not provide any
explanation supporting the concept of
measuring from a point in one cycle to
the same point in a successor cycle.
(Whirlpool, No. 44 at pp. 1–2)
Nevertheless, Whirlpool’s waiver
comments note the unintended
consequences associated with the
negative energy use contribution
measured for the fresh food defrost of
the Samsung product when using the
interim final rule’s version of the
Appendix A test period as
demonstrating that the test period
contained in the interim final rule is
inappropriate. (Whirlpool, Samsung
Petition for Test Procedure Waiver, Case
No. RF–018, Docket No. EERE–2011–
BT–WAV–0017, No. 4 at p. 5)
DOE had provided data in its NOPR
public meeting presentation supporting
the use of the modified test period,
ending when the compressor stops. This
situation was illustrated both for the
fresh food defrost contribution alone
and for the total defrost energy use
contribution, including both fresh food
and freezer compartment defrosts. The
data showed that a test period that both
starts and ends when the compressor
stops matched the energy expended by
the defrost heater during a fresh food
defrost—and provided a closer match of
energy use measured from one initiation
of the combined defrost cycle (the
defrost cycle involving both the fresh
food and freezer compartments) to the
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
next initiation of the combined defrost
cycle than the Appendix A1 procedure.
(NOPR Public Meeting Presentation, No.
9 at p. 53) More recently, DOE prepared
an assessment demonstrating that a test
period for the second part of the test
both starting and ending at the end of
a compressor ‘‘on’’ cycle is consistent
with the full-cycle measurement
specified for testing non-variable
automatic defrost products. See
(‘‘Refrigerator Test Procedure:
Adjustments to Second Part of Test’’,
No. 47) This document shows
mathematically that a calculation of
energy use using the ‘‘section 4.2’’ test
period (‘‘full test period’’) matches the
two-part calculation only when the
second part of the test ends at the end
of a compressor ‘‘on’’ cycle.
Part of the justification for modifying
the test procedure in the manner
suggested by Whirlpool is based on the
observation that when using the test
period prescribed by the interim final
rule, the average compartment
temperature would be warmer at the
end of the test period than at its start for
a system with a cycling compressor. The
interim final rule test procedure
includes a provision to verify that the
product does not employ partial
recovery. Using this provision requires
examining the full compressor cycle
immediately after the test period to
ensure that it is a regular compressor
cycle, i.e. a compressor cycle associated
with steady state operation. However,
the test does not account for the
additional temperature recovery
associated with a regular compressor
‘‘on’’ cycle. The December 2010 notice
indicates that the test period T2 starts
when the compartment is at its typical
minimum temperature associated with
steady state cycling operation. This
minimum temperature is represented by
the lower horizontal line of the
temperature plot in Figure 1 of
Appendix A. 75 FR at 78855 (Dec. 16,
2010) (see temperature plot of Figure 1,
‘‘Long-time Automatic Defrost Diagram
for Cycling Compressors’’).
On the other hand, the compartment
temperature is at its typical steady-state
cycling maximum (the higher horizontal
line of the temperature plot) when test
period T2 ends. Hence, while the
compartment temperature has recovered
to the range within which it varies
during steady state operation, it has not
recovered to the temperature state
associated with the start of the test
period—i.e. the temperature is warmer
than at the start of the test period. In
order to allow recovery to the start-oftest-period temperature, the test period
would have to continue till the end of
the compressor ‘‘on’’ cycle. These
PO 00000
Frm 00007
Fmt 4700
Sfmt 4700
3565
arguments illustrate that the test period
prescribed by the interim final rule for
the second part of the test is unlikely to
fully account for energy use associated
with temperature recovery.
DOE concludes that the test period for
the second part of the test that is
specified in the interim final rule for
products with cycling compressors and
long-time or variable defrost may not
accurately represent energy use
associated with defrost, which
necessitates a change to enhance the
accuracy of the measurement. DOE
received no other comments on this
topic. Hence, in light of this new
information, and its own review, DOE is
adopting the approach suggested by
Whirlpool to help ensure the procedure
in Appendix A provides a greater level
of accuracy.
Four-Hour Time Limit
DOE also considered whether to
retain the four-hour time limit that the
current test imposes on the second part
of the test. This limit applies to the
elapsed time after the defrost heater is
energized.3 (See Appendix A section
4.2.1.1 or Figure 1) The four-hour limit
terminates the test period when
recovery from defrost and return to
steady-state cycling operation takes an
unusually long time. During its review
of the test period for the second part of
the test, DOE noticed that for some
products, the extension of the test
period associated with the test period
revision recommended by Whirlpool led
to a test period invoking the four-hour
limit (i.e. the desired end of the test
period was more than four hours later
than activation of the defrost heater).
DOE notes that modern data
collection is performed almost
exclusively using automated data
acquisition systems. This approach to
recording data significantly reduces the
test burden that could potentially be
associated with extending the test
beyond the four-hour limit, allowing a
product to fully complete its
temperature recovery after defrost
during testing. Test technicians do not
need to observe product behavior during
the test from minute to minute to ensure
that data are recorded. Instead,
technicians are more likely to
periodically check the status of a given
test once or twice a day to determine
whether a defrost has occurred and
whether the test period has been
completed. With modern variabledefrost products, a full refrigerator test
3 Note that the elapsed time after the defrost
heater is energized is not the same as T2, since the
test period generally starts prior to activation of the
heater for testing in accordance with Appendix A.
E:\FR\FM\25JAR1.SGM
25JAR1
3566
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
can take a week to complete because of
the duration of the time intervals
between defrosts. The compressor run
time between defrosts can last as long as
96 hours for variable defrost products
(see Appendix A, section 5.2.1.3
regarding the maximum allowable
duration for CTM, the maximum
compressor run time between defrosts).
At a typical compressor on-time of 50
percent, the time involved in waiting for
a defrost cycle can be days. With the use
of automated data acquisition
equipment by test labs necessitating
only periodic status checks, the need for
24-hour staffing for data recording has
been effectively eliminated.4
Further, the continued application of
the four-hour limit is likely to reduce
measurement accuracy, since the limit
could cause a significant portion of the
compressor ‘‘on’’ cycle to be dropped
from the measurement.5 In light of the
more advanced capabilities of testing
labs and the operation of modern
refrigeration products, DOE believes
that the four-hour time limit of the
second part of the test is obsolete as a
means to limit test burden and may in
fact prevent the accurate measurement
of energy consumption of these
products. Because of the impact of the
four-hour time limit on test
measurement accuracy, and because it is
no longer needed to reduce test burden,
DOE is eliminating this provision of the
test procedure for Appendices A and B
in this notice. Making this change will
also fully address the potential problem
identified by Whirlpool by eliminating
any incentives by some manufacturers
to exploit potential limitations
presented by a procedure that
artificially limits the overall testing
duration without fully capturing that
product’s energy consumption.
sroberts on DSK4TPTVN1PROD with RULES
Recovery for Both Compartments of a
Refrigerator or Refrigerator-Freezer
The interim final rule requirements
for confirming that the second part of
the test does not include events
associated with precooling and
temperature recovery provide a means
to compare the temperatures of ‘‘the
compartment’’ measured during the first
part of the test with the average
temperatures of ‘‘the compartment’’ for
compressor cycles preceding and
4 Personal communication, Detlef Westphalen of
Navigant Consulting, Inc. with Terry Drew, CSA
International, 12/5/11.
5 For example, suppose the test period criteria for
temperature recovery are met at the end of the third
compressor ‘‘on’’ cycle after the defrost, but the four
hour limit ends the test period just after the start
of the third compressor ‘‘on’’ cycle. In this case, a
significant portion of compressor energy use is
eliminated from the measurement for the second
part of the test.
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
following the second part of the test.
(See Appendix A, section 4.2.1.1) The
language does not specify which
compartment must be evaluated in this
fashion. In order to assure that the test
procedure properly accounts for energy
use associated with precooling and
temperature recovery of the entire
product, the language of section 4 of
Appendix A is modified to clarify that
these requirements apply to both
compartments (i.e. the freezer
compartment and the fresh food
compartment), regardless of which
compartment’s evaporator undergoes
defrost. DOE is making this clarification
to assure testing accuracy.
Modification of Figure 2 of Appendices
A and B
The interim final rule includes a
figure for both Appendices A and B that
illustrates the second part of the test for
products with non-cycling compressors.
That figure, Figure 2, includes two
horizontal lines in the temperature plot
that have no meaning. In this final rule,
these lines of Figure 2 have been
removed. DOE is making this change to
avoid confusion and to ensure the
accuracy of the measured test results.
This amendment represents no change
to the specified test procedure.
Addition of Minor Edits for Clarification
While reviewing the modified new
sections 4.2.1.1 and 4.2.1.2
incorporating the changes discussed
above, DOE concluded that some minor
adjustments to the language would be
needed to clarify the test procedure and
to ensure the overall consistency of the
procedure. These adjustments include
the following:
• In the first and second lines of both
sections, changing ‘‘* * * the second
part starts * * *’’ to ‘‘* * * the second
part of the test starts * * *’’.
• In section 4.2.1.1, changing ‘‘* * *
first part’s temperature * * *’’ to
‘‘* * * average temperature for the first
part of the test * * *’’
These changes are made in parallel
sections to both Appendices A and B.
Impact of the Test Procedure Change on
Measured Energy Use
Whirlpool estimated that modifying
the test procedure to address the
observed negative energy use associated
with fresh food compartment defrosts
would increase the measured energy use
of a tested competitor’s product by 3
percent. (Whirlpool, No. 44 at p. 2)
These results are consistent with the
results DOE observed, as reported in the
NOPR public meeting. (NOPR Public
Meeting Presentation, No. 9 at p. 53).
However, as discussed above, DOE has
PO 00000
Frm 00008
Fmt 4700
Sfmt 4700
re-examined the available data and now
projects that the increase in energy use
for such a product is only 1.5 percent
applying the amended procedure made
in this final rule. This latter estimate
more accurately reflects the differences
in the test period of the second part of
the tests as represented by the interim
final rule and today’s final rule.
(‘‘Summary of Energy Use
Measurements for a Refrigerator-Freezer
with two Defrost Cycle Types’’, No. 46)
In addition, as discussed further below,
DOE has determined that the impact of
the test procedure change on energy use
measurement for most affected products
is near 1 percent. DOE also notes that
the energy use impact of this change
would apply only for those variable
defrost products that use cycling
compressors.
To assess the potential impact on the
measured energy use associated with
the test procedure change suggested by
Whirlpool, DOE reviewed the data it
collected to support the test procedure’s
development and data collected as part
of its compliance efforts. The analysis
DOE conducted drew from two separate
sets of test reports. The first set included
tests conducted using the current test
procedures of Appendix A1. For this set
of tests, the applicable temperature
settings did not permit one to calculate
a weighted-average energy use at the
Appendix A standardized compartment
temperatures of 0 °F for the freezer
compartment, and 39 °F for the fresh
food compartment, because the
measured compartment temperatures for
the two tests conducted at different
temperature control settings (i.e. median
setting and either warmest or coldest
settings prescribed in the temperature
control setting requirements of
Appendix A1, section 3) did not
generally bound these standardized
temperatures. The second set of tests, in
contrast, included measurements at
temperature settings allowing
calculation of results consistent with the
Appendix A standardized compartment
temperatures. These tests involved the
use of temperature control settings
suitable for the Appendix A
standardized temperatures.
For the first set of tests, DOE
evaluated the impact of the test
procedure change only for the coldest
compartment temperature setting used
in the test, which was typically the
median setting. The compartment
temperatures of these tests fell within
3°F of the Appendix A standardized
temperatures. While this difference
represents a deviation from the
Appendix A test requirements, DOE still
considers these results to be a good
predictor of the expected operation of
E:\FR\FM\25JAR1.SGM
25JAR1
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
these products under standardized
compartment temperature conditions for
two reasons—(1) the small size of the
temperature deviations and (2) the
measured data demonstrate that the
influence of compartment temperature
on the estimated impact of the test
procedure change was negligible.
The analysis focused on four key
refrigerator-freezer product classes: class
3 (refrigerator-freezers—automatic
defrost with top-mounted freezer
without through-the-door ice service),
class 5 products without exception
relief (refrigerator-freezers—automatic
defrost with bottom-mounted freezer
without through-the-door ice service),
class 5 with exception relief to account
for through-the-door ice service (for the
purposes of this discussion, designated
product class 5A under the recently
promulgated standards for 2014), and
class 7 (refrigerator-freezers—automatic
defrost with side-mounted freezer with
through-the-door ice service). These
product classes were chosen because
they represent significant market share,
have automatic defrost, and are the most
likely products to have variable defrost,
thus indicating that they would be more
likely candidates to be tested using the
two-part test. The assessment focused
solely on products with cycling
compressors and variable defrost, since
3567
the test procedure change does not
affect energy use measurement for other
products.
DOE re-evaluated the test results for
both sets of data using the modified test
period for the second part of the test as
described in this section, including both
shifting the end of the test period to a
compressor stop (rather than a
compressor start) and removing the
four-hour time limit. Table III.2
summarizes the results of this
assessment for both sets of data and
does not include any data covering
Samsung products. The average
measurement impact for these 25
products is under 1 percent.
TABLE III.2—MEASURED ENERGY USE INCREASE
First set of tests
Second set of tests
Number of units
Product class
Average energy
use impact
(percent)
Number of units
Average energy
use impact
(percent)
6
2
3
6
17
0.99
1.05
1.08
0.73
0.92
2
1
2
3
8
0.90
0.89
1.21
0.85
0.95
3 .......................................................................................................
5 .......................................................................................................
5A .....................................................................................................
7 .......................................................................................................
All Units ............................................................................................
weighted average percentages. Because
the certification data do not distinguish
between cycling and non-cycling
compressor systems, these percentages
include both types and for that reason
provide a conservative (i.e. larger)
estimate regarding the market share of
affected products. (As discussed above,
only products with variable defrost and
cycling compressors will be affected by
the test procedure change.) The table
also shows the market share of Samsung
products by product class based on sales
data purchased from the NPD Group6
for the years 2007 and 2008. DOE
calculated the shipment-weighted
average impact of the test procedure
change as follows.
this calculation of weighted average
energy use impact for the four product
classes. The percentage impact varies
from less than 0.5 percent to just above
1 percent. From these projections, DOE
concludes that the level of change in the
measurement does not necessitate a
change in the energy conservation
standards, as discussed in section
III.E.2.
6 NPD Group, Inc. https://www.npd.com/
corpServlet?nextpage=corp_welcome.html.
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
PO 00000
Frm 00009
Fmt 4700
Sfmt 4700
E:\FR\FM\25JAR1.SGM
25JAR1
ER25JA12.009
Shipment-Weighted Impact of the Test
Procedure Change on Measured Energy
Use
DOE developed estimates of
shipment-weighted impacts on the
measured energy use of the test
procedure change for the four product
classes highlighted in Table III.2. The
test procedure amendments apply only
to variable defrost products with cycling
compressors. Table III.3 summarizes the
percentage of models with variable
defrost for the evaluated refrigeratorfreezer product classes as reported to
DOE in August 2011 as part of the
annual certification data submission.
DOE used these percentages of basic
models as a proxy for shipment-
In this equation, SS is the Samsung
market share and SV is the variable
defrost market share. DOE assumed that
the Samsung products all have variable
defrost. Table III.3 shows the results of
sroberts on DSK4TPTVN1PROD with RULES
DOE also separately evaluated data for
six Samsung products falling into
classes 5A and 7, for which the overall
average measured impact was 1.55
percent. DOE believes that the reason
for the greater sensitivity of Samsung
products to this test procedure change
as compared with other products is that
these products have two defrosts (one
combined defrost of both the freezer and
fresh food compartment evaporators and
one defrost of only the fresh food
evaporator) occurring in the same
amount of time that other products use
one defrost.
3568
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
TABLE III.3—WEIGHTED IMPACT
Percent of
basic models
with variable
defrost
Product class
3 .......................................................................................................................................
5 .......................................................................................................................................
5A .....................................................................................................................................
7 .......................................................................................................................................
D. Other Issues
This section discusses comments
made by stakeholders regarding items
for which DOE has not made
corresponding changes in the test
procedure.
sroberts on DSK4TPTVN1PROD with RULES
1. Anti-Circumvention Language
In the December 2010 final rule, DOE
added anti-circumvention language to
10 CFR 430.23, in section (a)(10)
addressing refrigerators and refrigeratorfreezers and in section (b)(7) addressing
freezers. 75 FR 78818–78820 (Dec. 16,
2010). AHAM commented that the anticircumvention language has significant
differences as compared with the
language of HRF–1–2008 and that the
exact language of HRF–1–2008 should
be adopted. (AHAM, No. 39 at p. 4) The
language identified by AHAM appears
in a section that provides general
guidance for manufacturers to consider
with respect to potential anticircumvention issues. The specific
language changes AHAM recommended
include the following:
1. ‘‘Energy saving features that are
designed to be activated by a lack of
door openings shall not be functional
during the energy test.’’ should read
‘‘Energy saving features that are
designed to operate when there are no
door openings for long periods of time
shall not be functional during the
energy test.’’
2. ‘‘The defrost heater should not
either function or turn off differently
during the energy test than it would
when operating in typical room
conditions.’’ should read ‘‘The defrost
heater shall not either function or turn
off differently during the energy test
than it would when operating in typical
room conditions. Also, the product shall
not recover differently during the
defrost recovery period than it would in
typical room conditions.’’
3. In ‘‘Electric heaters that would
normally operate at typical room
conditions with door openings should
also operate during the energy test.’’ the
‘‘should’’ should be replaced with
‘‘shall.’’
As noted earlier, amendments to 10
CFR 430.23 as part of the December 16,
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
2010 notice were made as part of the
December 2010 final rule. These issues
were not fully vetted as part of the reopening notice, which focused on issues
related to Appendices A and B. DOE
notes, however, that it developed this
limited guidance in reliance on the 2007
version of HRF–1. (Compare section
HRF–1–2007, section 1.2 with HRF–1–
2008, section 1.2). Should DOE need to
clarify the application of these
conditions, it may do so in the future.
2. Refrigeration Products Designed for
Sale With or Without Icemakers
In the standards final rule, DOE
discussed issues raised by AHAM
regarding refrigeration products
designed for sale with or without
icemakers (‘‘kitable models’’). Such
products may leave the factory with an
icemaker installed, but could also leave
the factory without an icemaker and
instead have an icemaker installed
downstream in the distribution chain,
by the retailer, or even by a customer
after purchase of the product. 76 FR at
57538 (Sept. 15, 2011). Icemakers can
also be produced by third-party
manufacturers separate from the
refrigeration products’ manufacturers.
(For example, the third party brand
Aquafresh is advertised as a
replacement for all major icemaker
brands. See ‘‘Aquafresh RIM900 Ice
Maker Information,’’ No. 48 at p. 1)
AHAM commented in response to the
energy standards NOPR that kitable
models should be treated as if they have
the icemaker installed. (AHAM,
Refrigeration Products Energy
Conservation Standard Rulemaking,
Docket Number EE–2008–BT–STD–
0012, No. 73 at p. 6) DOE responded to
these claims by noting that such
products could be purchased either with
or without the icemaker, that the field
energy use for products without an
icemaker would be less by the amount
of energy use associated with icemaking
(which is represented by a fixed value
of 84 kWh in the interim final rule test
procedure) and that better consistency
with the test procedure would be
established if such products were
required to be certified both with and
PO 00000
Frm 00010
Fmt 4700
Sfmt 4700
Percent
Samsung
products
36
90
100
95
Weighted
average energy
use impact
0
18
24
6
0.36
1.00
1.13
0.98
without the icemaker. 76 FR at 57538–
57539 (Sept. 15, 2011).
AHAM strongly opposed the DOE
approach and its comments to DOE
stressed that the approach would create
unnecessary burden and cost with no
public benefit. AHAM cited the
following reasons in support of its
position:
• As far as AHAM is aware,
manufacturers typically assign kitable
models a single model number
regardless of whether the icemaker is
installed when the product leaves the
factory. Requiring certification of the
model with and without the icemaker
might require establishing a second
model number for each such product,
which would represent a great cost to
manufacturers.
• The approach is overly burdensome
because it requires twice the test burden
and twice as much reporting.
• Consumers that install an icemaker
after purchase of a refrigerator would
not be aware of the additional energy
use associated with icemaking.
• If manufacturers maintain a single
model number for the product with and
without the icemaker, there might be
confusion if consumers see two different
energy use values indicated for the same
model (i.e. one for the unit with the
icemaker and one for the unit without
the icemaker).
• The manufacturer may not have any
control over whether an icemaker is
installed in the unit after it leaves the
factory, making it difficult to ensure that
the correct energy label is included with
the unit.
AHAM’s approach would be to treat
kitable models as if they have an
icemaker. Such an approach would
ensure that a purchaser of a kitable
model would receive a product that
would have energy use no more than the
rated value. This approach would also
mean that there would be only one
energy use value associated with each
model number, and would avoid
multiple testing and reporting. (AHAM,
No. 43 at pp. 6–7)
DOE is declining to adopt AHAM’s
approach within the context of today’s
notice.
E:\FR\FM\25JAR1.SGM
25JAR1
sroberts on DSK4TPTVN1PROD with RULES
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
DOE acknowledges, however, that
manufacturers may have no control of
events occurring after a product leaves
their factory, and, hence, may not know
which label to ship with a product, if
the label were required to accurately
reflect whether the product has an
icemaker installed. Further, although
AHAM claims that this approach is
burdensome, its claim that such
products would have to be tested twice
is incorrect—a single test would
indicate product performance with and
without the icemaker, because it would
include a measurement of the product
without an icemaker. Calculating the
energy use for an icemaker-equipped
product would be a matter of adding a
fixed value to calculate this value, as
specified by the Appendix A test
procedure (see section 6.2.2.2).
Additionally, AHAM did not quantify
the burden involved. Without such
quantification, or a meaningful
explanation as to why a second set of
tests would be needed, DOE has little
information with which to judge the
merits of AHAM’s recommendations or
its claims. DOE also notes that product
labeling is the jurisdiction of the FTC
and that any contents of those labels lie
primarily within the province of that
agency’s rulemaking authority.
Further, DOE notes that any approach
eventually adopted for kitable models
must ensure that both versions of the
kitable model (i.e. sold either with or
without the icemaker) meet their
respective energy standards. DOE notes
that this goal would automatically be
achieved with the new standards and
the new test procedures as represented
by the September 2011 standards final
rule and this test procedure final rule
notice, since both the test procedure and
the standards apply a fixed value of 84
kWh (to represent icemaker energy
consumption) to the measured energy
use of a product when configured
without an icemaker—this new value
represents the energy use of an
icemaker-equipped version of that
product. This situation will likely
change once a laboratory-based
procedure is implemented for
measuring icemaking energy use, as is
contemplated in a future rulemaking.
Consideration of an approach to address
kitable models would, in all likelihood,
be more appropriately addressed as part
of a future rulemaking to decide
whether to incorporate such a
laboratory-based icemaking energy use
measurement. DOE adds that the full
rulemaking process would allow the
issues associated with kitable models to
be thoroughly considered and reviewed
by stakeholders, thus ensuring that the
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
adopted approach is vetted and
acceptable to all affected parties.
Accordingly, DOE is declining to adopt
AHAM’s suggestion.
3. Wine Storage and Combination Wine
Storage Products
This section addresses issues
associated with wine storage products
and combination wine storage products.
The latter are refrigeration products
combining wine storage with fresh food
and/or freezer compartments.
Definitions for Refrigerator and
Refrigerator-Freezer
DOE amended the definitions for
refrigerator and refrigerator-freezer as
part of the final rule published in the
December 16, 2010 notice. See 75 FR at
78817. The modified definitions did two
things that the previous definitions did
not. First, they clarified that products
that combine freezer compartments with
compartments not designed to be
capable of 39 °F storage temperature
(but include no other types of
compartments) are not refrigeratorfreezers. Second, the definitions
clarified the requirements for fresh food
compartments of refrigerators and
refrigerator-freezers. Regarding this
second item, the revised definitions
clarified that a product is not
necessarily disqualified from status as a
refrigerator or refrigerator-freezer if its
fresh food compartments can maintain
average temperatures above 39 °F for
some temperature control settings. Id.
The amendments did not include
language specifying that products
incorporating wine storage
compartments—for the purpose of this
discussion, compartments that are not
designed to be capable of maintaining
storage temperatures below 39 °F—in
products that would otherwise be
refrigerators or refrigerator-freezers
under the definition would be treated as
something other than these covered
products. Id. at 78817. Wine chillers are
typically designed to operate between
50 °F and 60 °F to ensure the proper
storage temperature for bottled wine.
DOE subsequently posted on its Web
site a guidance document explaining its
interpretation of the amended
definitions. (‘‘Guidance on Scope of
Coverage for Hybrid (Wine Storage)
Refrigeration Products Issued Feb. 10,
2011’’, No. 49). The Guidance clarified
DOE’s interpretation of the definitions
and explained that adding a wine
storage compartment to a refrigerator or
a refrigerator-freezer does not change its
status as a refrigerator or refrigeratorfreezer under the regulations.
AHAM objected to this interpretation
of the test procedure final rule
PO 00000
Frm 00011
Fmt 4700
Sfmt 4700
3569
definitions. (AHAM, No. 43 at pp. 4–5).
It argued that DOE’s interpretation is
inequitable because it treats freezers
differently than refrigerators and
refrigerator-freezers. AHAM also argued
that the Guidance was, in its view,
inconsistent with the separate
rulemaking approach that DOE had
indicated it was considering applying to
wine chillers. AHAM argued further
that establishing coverage through
interpretation, which it believed was
performed by the Guidance, was
inappropriate, and stated that such steps
should be taken only through the
established rulemaking process.
At the outset, DOE notes that these
definitions were established as part of
the December 2010 final rule. Because
of the limited nature of the re-opening
of the comment period, which focused
on those issues related to the conduct of
the test procedures detailed in
Appendices A and B, these particular
issues were not completely vetted
through the rulemaking process. Hence,
DOE may revisit and reconsider these
issues as part of a future rulemaking
activity.
DOE further notes that AHAM does
not contest the validity of the text of the
definitions themselves but only how
DOE may choose to apply these
definitions to a small group of products
that have yet to comprise any significant
share of the overall refrigeration product
market. DOE’s research was able to
identify only seven distinct products
that are clearly part of this product
group. (‘‘Wine Storage Combination
Products’’, No. 50).
With respect to the definitions, the
coverage of refrigeration products has
been clarified through guidance to help
explain that products that meet a
specific set of performance criteria
would be treated as covered products.
Any product meeting these criteria are
subject to the regulations covering these
products. These criteria were
established through a lengthy notice and
comment process associated with this
test procedure rulemaking that began in
May 2010 and on which manufacturers
had ample opportunity to comment.
DOE adds that, consistent with its prior
statements, it fully intends to initiate a
wine-chiller-specific rulemaking to
address potential standards for these
products.
DOE also notes that there are some
key technical differences between
freezers and refrigerators/refrigeratorfreezers. These differences require that
different approaches be considered
when deciding how to treat those
refrigeration products that include a
wine storage compartment. In
particular, the standardized temperature
E:\FR\FM\25JAR1.SGM
25JAR1
sroberts on DSK4TPTVN1PROD with RULES
3570
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
for a freezer is 0 °F, while the
standardized temperature for the fresh
food compartment of a refrigeratorfreezer is 45 °F under current test
procedures and 39 °F under test
procedures that manufacturers will need
to use for compliance purposes in 2014.
A wine storage compartment can be
expected to approach a 45 °F
temperature during testing, but
approaching 0 °F would be extremely
unlikely given the nature of the
product—specifically, the technical
requirements for designing a
compartment of a product to achieve a
0 °F temperature differs significantly
from those required to achieve the much
higher temperature (39 °F) needed for
the safe storage of fresh food—or the
even higher standardized temperature
(45 °F) required by the current test
procedure during the testing of these
products. These differences not only
require different design considerations,
but they also result in very different
energy consumption characteristics.
Moreover, the definitions for these
three products (refrigerator, refrigeratorfreezer, and freezer), which DOE
adopted with full input from the public,
including manufacturers, contain clear
differences with respect to the inclusion
of separate compartments. Both the
refrigerator and refrigerator-freezer
definitions explicitly contemplate the
inclusion of compartments with more
than one temperature range, while the
freezer definition does not. See 10 CFR
430.2. As a result, a freezer-wine chiller
combination product does not fall
squarely into any of these definitions. In
contrast, a wine chiller combined with
either a refrigerator or refrigeratorfreezer would fall within the definitions
for those two products. Treating these
three products in the exact same manner
as suggested by AHAM—i.e., to exclude
them from any coverage—would ignore
these differences as well as the technical
differences noted above. Accordingly,
because of these differences, a freezerwine chiller product should not be
treated in the same manner as a
refrigerator-wine chiller or refrigeratorfreezer-wine chiller products.
DOE recognizes, however, that some
combination wine storage products may
have characteristics that would make
attempts at testing them with the wine
storage compartment approaching 45 °F
provide non-representative results. For
such products, manufacturers may still
market such items by first petitioning
DOE for an appropriate test procedure
waiver. DOE highlighted this option
when it issued its February 2011
Guidance. Also, in the case of those
products that may be unable to comply
with the applicable standards,
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
manufacturers have the option of
applying for exception relief with the
Office of Hearings and Appeals. See 42
U.S.C. 7194 and 10 CFR part 1003.
Federal Energy Conservation Standards
for Wine Chillers
In the energy conservation standards
NOPR (‘‘standards NOPR’’), and again in
the standards final rule, DOE explained
its interpretation that wine chillers are
not covered products under the
definition for electric refrigerator, and
thus are not covered by the energy
conservation standards for refrigeration
products. 75 FR 59470, 59486 (Sept. 27,
2010) and 76 FR 57516, 57534 (Sept. 15,
2011). As noted in the standards final
rule, several stakeholders submitted
comments favoring the regulation of
wine chiller products. DOE noted that it
may consider initiating a rulemaking to
establish coverage and energy standards
for these products. Id.
In its comments on the interim final
rule, AHAM reiterated its support for a
rulemaking to regulate wine storage
products, and indicated that such a
rulemaking should include products in
which wine storage compartments are
combined with fresh food and/or freezer
compartments. (AHAM, No. 43 at p. 4).
Sub Zero requested that DOE conduct a
comprehensive analysis, with full
stakeholder input, leading to a Federal
efficiency standard for all wine storage
products and combination/hybrid that
include wine chillers. (Sub Zero, No. 42
at p. 2).
Consistent with earlier statements,
DOE will consider conducting
rulemakings addressing coverage, test
procedures, and energy conservation
standards for wine chiller and related
products. DOE has already taken an
initial step in this process by publishing
a coverage determination proposal to
establish coverage for refrigeration
products that do not have compressors
and condensers integrated with their
cabinets—many of which include wine
chillers. 76 FR 69147 (Nov. 8, 2011).
Such products cannot be immediately
covered under the authority granted to
DOE by EPCA to regulate conventional
refrigeration products, which
necessitates a separate coverage
determination to address these noncondenser/compressor products. (42
U.S.C. 6292(a)(1)).
4. Multiple Compressor Systems
In the test procedure NOPR, DOE
proposed to address certain
inconsistencies in the test procedure for
dual compressor systems. 75 FR at
29841 (May 27, 2010). These systems
have separate refrigeration systems
serving the fresh food and freezer
PO 00000
Frm 00012
Fmt 4700
Sfmt 4700
compartments. AHAM commented that
DOE should simplify this test procedure
and suggested an alternative test
procedure addressing such products.
(AHAM, No. 16 at p. 7). DOE explained
that it could not adopt the AHAM
proposal in the interim final rule
because the AHAM procedure
represents a significant departure from
the proposal that was presented in the
NOPR, and that stakeholders were not
provided an adequate opportunity to
comment on the procedure to allow its
adoption. 75 FR at 78831 (Dec. 16,
2010). DOE noted, however, that it may
consider this approach in a future
rulemaking that would more fully revise
the test procedure. See id.
AHAM raised this issue in all three of
its written comments submitted in
response to the interim final rule.
(AHAM, No. 39 at p. 4; AHAM, No. 40
at pp. 1–2; AHAM, No. 43 at pp. 2–3).
AHAM’s recommendations regarding
how this test procedure should measure
the energy consumption of multiple
compressor-based systems has changed
each time it has provided specific test
procedure recommendations. See
AHAM, No. 16 at p. 7 (Aug. 10, 2010),
AHAM, No. 40 at pp. 1–2 (March 4,
2011), and AHAM, No. 43 at pp. 2–3
(Oct. 17, 2011). In spite of its
continually evolving position, AHAM
urged DOE to modify the dual
compressor test procedure because, in
its view, the DOE test procedure
contains specific problems that relate to
its requirement that a manufacturer
separately measure the energy use of the
two separate systems.7 The group made
two assertions in support of its view.
First, AHAM argued that this
requirement posed a significant test
burden. Second, AHAM asserted that
many dual compressor products do not
work in the manner that the test
procedure assumes they do—i.e. as
separate independent systems. Instead,
AHAM argued that many of these
products use shared systems. (AHAM,
No. 40 at p. 2). Sub-Zero supported the
alternative approach incorporated in
AHAM’s October 17, 2011 comments
and asserted that it provided a practical,
accurate, and repeatable test procedure
that should be incorporated into the
final rule.8 (Sub Zero, No. 42 at pp. 1–
2).
7 DOE notes that the requirement for separate
measurement of the two systems for dual
compressor products is not new. It was initially
established in the test procedure on August 31,
1989. 54 FR 36238.
8 Sub Zero’s comments mention that they have
submitted a petition for a test procedure waiver to
obtain relief for their dual-compressor products
from use of the current test procedure (see 76 FR
71335 (Nov. 17, 2011)), which they claim are
E:\FR\FM\25JAR1.SGM
25JAR1
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
sroberts on DSK4TPTVN1PROD with RULES
AHAM added that Appendix A1
should be modified to include the
revised test procedure for dual
compressor system products it
suggested that DOE adopt. (AHAM, No.
43 at p. 2).
DOE notes that modifications to the
Appendix A1 test procedure for dual
compressor systems implemented in the
December 16, 2010 notice were made as
part of the final rule. Because of the
limited nature of the reopening notice,
which focused on issues related to
Appendices A and B, these suggested
changes to Appendix A1 were not fully
vetted for consideration in this
rulemaking.
DOE further notes that the current
procedure’s requirement that each
compressor system of a dual compressor
system be separately measured was first
established in 1989. See 54 FR 36238,
36241 (Aug. 31, 1989). Manufacturers
are, by now, very familiar with this
procedure and how to most efficiently
and accurately perform it. The issues
that AHAM initially raised in its August
10, 2010, comments regarding the
burden associated with this test (which
AHAM did not detail) require additional
consideration and a more fulsome
evaluation. Additionally, the constantly
changing nature of AHAM’s
recommended approach highlights the
unsettled nature of that approach and
underscores the complexity of this
issue. In DOE’s view, these facts tend to
indicate that the adoption of any one of
AHAM’s three suggested alternatives
would likely be premature, particularly
without further public input. Hence,
DOE is declining to adopt any of
AHAM’s suggestions at this time.
DOE notes that AHAM did not
indicate that its approach will be
applicable to freezers. Consequently,
DOE did not evaluate the
appropriateness of this approach for
those products. DOE is unaware of any
freezer products that employ a dual
compressor system.
5. Triangulation
During the test procedure NOPR
public meeting, stakeholders introduced
the concept of triangulation in the
context of setting a refrigeration
product’s temperature controls for
testing. The triangulation approach
involves conducting tests at three
temperature control setting
combinations as opposed to the two
settings generally required in the
current test procedures. By properly
difficult or impossible to conduct. (Sub Zero, No.
44 at pp. 1–2). The waiver process is the
appropriate step in addressing such products that
cannot properly be tested using the DOE test
procedures.
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
setting the controls for the three tests
and calculating the appropriate
weighted average of the energy use
measurements of those tests,
triangulation allows one to calculate the
projected level of energy use if both the
fresh food and freezer compartment
temperatures matched their
standardized temperatures (i.e. 0 °F in
the freezer compartment and 39 °F in
the fresh food compartment for a
refrigerator-freezer tested according to
Appendix A). In comparison, the
current DOE test procedure provides a
more conservative measurement (i.e.
potentially higher value) of energy use
at the standardized temperatures that
reduces the overall testing burdens by
limiting the number of required tests
from three under the triangulation
approach to two.9
Stakeholders suggested in oral and
written comments on the NOPR that
triangulation should be introduced into
the DOE test procedures. See 75 FR at
78822 (Dec. 16, 2010). DOE indicated in
the interim final rule that this test
procedure approach has not been
subject to stakeholder evaluation and
comment and that it could not be
adopted at the time for that reason. Id.
AHAM commented again that
triangulation should be adopted in the
test procedures, indicating that it should
be introduced as an optional approach
for setting temperature controls for
testing. AHAM also indicated that DOE
could have put this topic up for
stakeholder comment in the interim
final rule, and added that if the DOE
adopts triangulation for certification
purposes, it should also be required for
enforcement purposes. (AHAM, No. 39
at pp. 3–4)
DOE believes the triangulation
approach departs enough from current
procedures for setting temperature
controls that it would have been
inappropriate for DOE to incorporate it
based solely on the strength of the
NOPR comments, which were sparse
and contained little to no supporting
data. Those technical differences,
coupled with the lack of any
opportunity for all interested parties to
9 A more conservative (i.e. larger) estimate of
energy usage is most likely to occur in situations
where a tested product’s temperature controls have
not been tuned—without such tuning, the two
calculations of energy use of Appendix A, section
6.2.2.2 using the fresh food compartment
temperature for one calculation and the freezer
compartment temperature for the other can differ
significantly from each other. For such a product,
the two compartments attain their standardized
temperatures at very different positions within the
range of their temperature controls (e.g. the fresh
food compartment may attain 39 °F with its control
at the mid setting while the freezer compartment
control may have to be in its coldest position to
achieve 0 °F in the compartment).
PO 00000
Frm 00013
Fmt 4700
Sfmt 4700
3571
fully evaluate this issue, weigh in favor
of not incorporating the triangulation
approach into DOE’s test procedure at
this time. Consequently, DOE did not
adopt it in either the December 2010
final rule or the interim final rule.
Additionally, introducing
triangulation could have unforeseen
implications, as alluded to in AHAM’s
comments, which suggested that, if
adopted, it should also be used for
enforcement purposes. (Id. at p. 4)
Testing using triangulation could, in
certain circumstances, yield different
results as compared with the approach
of the current DOE test procedure.
Those differences could be significant
enough to affect whether a given
product complies with an applicable
standard. This complication alone
merits a more thorough consideration by
the agency before the triangulation
approach is adopted. For these reasons,
DOE is declining to adopt the
triangulation method into the test
procedures of Appendix A at this time.
DOE, may, however, consider the
incorporation of this method when it
considers potential changes to the test
procedure as periodically required
under 42 U.S.C. 6293(b).
E. Compliance With Other EPCA
Requirements
In addition to the issues discussed
above, DOE examined its other
obligations under EPCA in developing
the amendments in today’s notice.
These requirements are addressed in
greater detail below.
1. Test Burden
EPCA requires that the test
procedures DOE prescribes or amends
be reasonably designed to produce test
results which measure the energy
efficiency, energy use, or estimated
annual operating cost of a covered
product during a representative average
use cycle or period of use. These
procedures must also not be unduly
burdensome to conduct. See 42 U.S.C.
6293(b)(3). DOE has concluded that the
amendments being adopted today
satisfy this requirement. In large part,
today’s rule simply finalizes the interim
final rule of December 16, 2010. Where
the interim final rule has been modified,
the amendments require no changes to
the current requirements for equipment
and instrumentation for testing.
While the amendments adopted today
have the potential to slightly extend the
testing time for some products that use
long-time or variable defrost, this
extended duration is likely to represent
an insignificant impact on the overall
test burden. In particular, while the
duration of the second part of the test
E:\FR\FM\25JAR1.SGM
25JAR1
3572
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
sroberts on DSK4TPTVN1PROD with RULES
will extend for those products that use
cycling compressors—the test period
will be extended typically for the
duration of a compressor ‘‘on’’ cycle,
but may be longer in the limited number
of cases where the four-hour time limit
between defrost heater activation and
the end of the test period under the
current test procedure applies. The
amended procedure will, in the vast
majority of cases, not extend the testing
duration for products. DOE estimates
that any products that would be affected
by these changes would have an
extended testing duration of between 1
and 2 hours. Given that most, if not all,
modern testing is conducted using
automated data acquisition equipment
and that these tests typically last a full
week for a typical product, the addition
of this amount of time is unlikely to
result in any significant added burden.
As described in section C.2, in tests
conducted using automated data
acquisition, a test technician does not
actively monitor the test minute to
minute. Instead, the test status is
checked periodically during the test,
perhaps once or twice per day. At the
time of such a check, the test generally
would have completed the next defrost
cycle to be measured, or alternatively,
the next defrost cycle would not yet
have started, in which case the test
would be checked again later. In few, if
any, cases would extension of the
defrost part of the test by 1 or 2 hours
significantly lengthen the overall test
time. The extension of the test period of
the second part of the test would cause
delay only if, during such status check,
the latest defrost cycle has started but
not ended. Also, for such a case, a twohour extension of the test, if it did
occur, would represent about a 1
percent increase in test time, assuming
a one-week average test duration.
Consequently, DOE concludes that the
possible small increase in test time is
more than outweighed by the improved
accuracy of the test represented by the
test procedure amendment.
The test procedure changes modifying
the default values for CTL and CTM and
revising the reference to the test data
records requirements impose no
changes in test burden.
2. Changes in Measured Energy Use
In this final rule, DOE is amending
the test period for the second part of the
test. This test is conducted as part of the
two-part test for products with longtime or variable-defrost and cycling
compressor systems. DOE estimates that
this test procedure change will increase
measured energy use roughly 1 percent
for affected standard-size refrigeratorfreezers. The other test procedure
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
amendments made in this final rule will
not affect energy use measurement.
When DOE modifies test procedures,
it must determine to what extent, if any,
the new test procedure would alter the
measured energy use of covered
products. (42 U.S.C. 6293(e)(1)) In this
case, DOE has determined that the
projected impact on the measured
energy use of covered products that are
affected would be altered by
approximately 1 percent. DOE considers
this an insignificant impact on
measured energy use. Accordingly, DOE
has determined that an adjustment to
the applicable standard is not required.
IV. Procedural Requirements
A. Review Under Executive Order 12866
The Office of Management and Budget
has determined that test procedure
rulemakings do not constitute
‘‘significant regulatory actions’’ under
section 3(f) of Executive Order 12866,
Regulatory Planning and Review, 58 FR
51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under
the Executive Order by the Office of
Information and Regulatory Affairs
(OIRA) in the Office of Management and
Budget (OMB).
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601, et seq.) requires preparation
of an initial regulatory flexibility
analysis for any rule that by law must
be proposed for public comment, unless
the agency certifies that the proposed
rule, if promulgated, will not have a
significant economic impact on a
substantial number of small entities. As
required by Executive Order 13272,
‘‘Proper Consideration of Small Entities
in Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s Web site (https://
www.gc.doe.gov).
DOE reviewed the test procedures in
today’s final rule under the provisions
of the Regulatory Flexibility Act and the
procedures and policies published on
February 19, 2003. This final rule
prescribes test procedures that will be
used to test compliance with energy
conservation standards for the products
that are the subject of this rulemaking.
The Small Business Administration
(SBA) considers an entity to be a small
business if, together with its affiliates, it
PO 00000
Frm 00014
Fmt 4700
Sfmt 4700
employs less than a threshold number of
workers specified in 13 CFR part 121,
which relies on size standards and
codes established by the North
American Industry Classification
System (NAICS). The threshold number
for NAICS code 335222, which applies
to Household Refrigerator and Home
Freezer Manufacturing, is 1,000
employees.
DOE searched the SBA Web site
(https://dsbs.sba.gov/dsbs/search/
dsp_dsbs.cfm) to identify manufacturers
within this NAICS code that produce
refrigerators, refrigerator-freezers, and/
or freezers. Most of the manufacturers
supplying these products are large
multinational corporations with more
than 1,000 employees. There are several
small businesses involved in the sale of
refrigeration products that are listed on
the SBA Web site under the NAICS code
for this industry. However, DOE
believes that only U-Line Corporation of
Milwaukee, Wisconsin is a small
business that manufactures these
products. U-Line primarily
manufactures compact refrigerators and
related compact products such as wine
chillers and stand-alone icemakers—
these icemakers differ from the
automatic icemakers installed in many
refrigeration products in that they are
complete icemaking appliances
designed solely for the production and
storage of ice, using either typical
residential icemaking technology or a
reduced-scale version of the icemaking
technology used extensively in
commercial icemakers.
DOE had initially concluded in its
December 2010 notice that the final rule
will not have a significant impact on
small manufacturers under the
provisions of the Regulatory Flexibility
Act. DOE received no comments
objecting to this conclusion.
DOE concludes also that the test
procedure amendments of today’s notice
will not have a significant impact on
small manufacturers under the
provisions of the Act. These
amendments do not require use of test
facilities or test equipment that differ in
any substantive way from the test
facilities or test equipment that
manufacturers currently use to evaluate
the energy efficiency of these products.
Further, the amended test procedures
will not be significantly more difficult
or time-consuming to conduct than
current DOE energy test procedures.
For these reasons, DOE concludes and
certifies that the rule would not have a
significant economic impact on a
substantial number of small entities.
Accordingly, DOE has not prepared a
regulatory flexibility analysis for this
rulemaking. DOE has transmitted the
E:\FR\FM\25JAR1.SGM
25JAR1
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
certification and supporting statement
of factual basis to the Chief Counsel for
Advocacy of the SBA for review under
5 U.S.C. 605(b).
sroberts on DSK4TPTVN1PROD with RULES
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of refrigeration
products must certify to DOE that their
products comply with any applicable
energy conservation standard. In
certifying compliance, manufacturers
must test their products according to the
DOE test procedure for refrigeration
products, including any amendments
adopted for that test procedure. The
collection-of-information requirement
for the certification and recordkeeping
is subject to review and approval by
OMB under the Paperwork Reduction
Act (PRA). This requirement has been
submitted to OMB for approval. DOE
received OMB approval to collect this
information and has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including the
refrigeration products addressed by
today’s final rule. 76 FR 12422 (March
7, 2011). The public reporting burden
for the certification is estimated to
average 20 hours per response,
including the time for reviewing
instructions, searching existing data
sources, gathering and maintaining the
data needed, and completing and
reviewing the collection of information.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
In this notice, DOE amends its test
procedure for refrigerators, refrigeratorfreezers, and freezers. These
amendments will improve the ability of
DOE’s procedures to more accurately
account for the energy consumption of
products that incorporate a variety of
new technologies that were not
contemplated when the current
procedure was promulgated. The
amendments also will be used to
develop and implement future energy
conservation standards for refrigeration
products. DOE has determined that this
final rule falls into a class of actions that
are categorically excluded from review
under the National Environmental
Policy Act of 1969 (42 U.S.C. 4321 et
seq.) and DOE’s implementing
regulations at 10 CFR part 1021.
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
Specifically, this rule amends an
existing rule without changing its
environmental effect, and, therefore, is
covered by the Categorical Exclusion in
10 CFR part 1021, subpart D, appendix
A6. See 76 FR 63764, 63788 (Oct. 13,
2011). The exclusion applies because
this rule establishes a strictly procedural
requirement by revising existing test
procedures. These revisions will not
affect the amount, quality, or
distribution of energy usage, and,
therefore, will not result in any
environmental impacts. Accordingly,
neither an environmental assessment
nor an environmental impact statement
is required.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
imposes certain requirements on
agencies formulating and implementing
policies or regulations that preempt
State law or that have Federalism
implications. 64 FR 43255 (Aug. 10,
1999). The Executive Order requires
agencies to examine the constitutional
and statutory authority supporting any
action that would limit the
policymaking discretion of the States
and to carefully assess the necessity for
such actions. The Executive Order also
requires agencies to have an accountable
process to ensure meaningful and timely
input by State and local officials in the
development of regulatory policies that
have Federalism implications. On
March 14, 2000, DOE published a
statement of policy describing the
intergovernmental consultation process
that it will follow in developing such
regulations. 65 FR 13735. DOE
examined this final rule and determined
that it will not have a substantial direct
effect on the States, on the relationship
between the national government and
the States, or on the distribution of
power and responsibilities among the
various levels of government. EPCA
governs and prescribes Federal
preemption of State regulations as to
energy conservation for the products
that are the subject of today’s final rule.
States can petition DOE for exemption
from such preemption to the extent, and
based on criteria, set forth in EPCA. (42
U.S.C. 6297) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
PO 00000
Frm 00015
Fmt 4700
Sfmt 4700
3573
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation specifies the following: (1)
The preemptive effect, if any; (2) any
effect on existing Federal law or
regulation; (3) a clear legal standard for
affected conduct while promoting
simplification and burden reduction; (4)
the retroactive effect, if any; (5)
definitions of key terms; and (6) other
important issues affecting clarity and
general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or
whether it is unreasonable to meet one
or more of them. DOE has completed the
required review and determined that, to
the extent permitted by law, this final
rule meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA) (Pub. L.
104–4; 2 U.S.C. 1501 et seq.) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. For a regulatory action
resulting in a rule that may cause the
expenditure by State, local, and Tribal
governments, in the aggregate, or by the
private sector of $100 million or more
in any one year (adjusted annually for
inflation), section 202 of UMRA requires
a Federal agency to publish estimates of
the resulting costs, benefits, and other
effects on the national economy. (2
U.S.C. 1532(a)–(b)) UMRA also requires
a Federal agency to develop an effective
process to permit timely input by
elected officers of State, local, and
Tribal governments on a proposed
‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially-affected
small governments before establishing
any requirements that might
significantly or uniquely affect such
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR
12820. (The policy is also available at
www.gc.doe.gov). Today’s final rule
contains neither an intergovernmental
mandate nor a mandate that may result
E:\FR\FM\25JAR1.SGM
25JAR1
3574
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
in an expenditure of $100 million or
more in any year, so these requirements
do not apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being.
Today’s final rule would not have any
impact on the autonomy or integrity of
the family as an institution.
Accordingly, DOE has concluded that it
is not necessary to prepare a Family
Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 18, 1988), that this regulation
would not result in any takings that
might require compensation under the
Fifth Amendment to the U.S.
Constitution.
sroberts on DSK4TPTVN1PROD with RULES
J. Review Under the Treasury and
General Government Appropriations
Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). DOE has reviewed
today’s rule under OMB and DOE
guidelines and has concluded that it is
consistent with applicable policies in
those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OIRA a Statement
of Energy Effects for any significant
energy action. A ‘‘significant energy
action’’ is defined as any action by an
agency that promulgates or is expected
to lead to promulgation of a final rule
and that (1) is a significant regulatory
action under Executive Order 12866, or
any successor order; and (2) is likely to
have a significant adverse effect on the
supply, distribution, or use of energy; or
(3) is designated by the Administrator of
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
OIRA as a significant energy action. For
any significant energy action, the agency
must give a detailed statement of any
adverse effects on energy supply,
distribution, or use if the regulation is
implemented, and of reasonable
alternatives to the action and their
expected benefits on energy supply,
distribution, and use. Today’s regulatory
action is not a significant regulatory
action under Executive Order 12866. It
has likewise not been designated as a
significant energy action by the
Administrator of OIRA. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy. Therefore, it is not a
significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the DOE
Organization Act (Pub. L. 95–91; 42
U.S.C. 7101 et seq.), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977 (FEAA).
(15 U.S.C. 788) Section 32 essentially
provides in part that, where a rule
authorizes or requires use of commercial
standards, the rulemaking must inform
the public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (FTC)
concerning the impact of the
commercial or industry standards on
competition.
Today’s action does not incorporate
testing methods contained in any new
commercial standards not already
referenced by the current regulations on
which the Attorney General and FTC
have not already been previously
consulted earlier during this rulemaking
process.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of today’s rule before its effective date.
The report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of these final rules.
List of Subjects in 10 CFR Part 430
Administrative practice and
procedure, Confidential business
information, Energy conservation,
PO 00000
Frm 00016
Fmt 4700
Sfmt 4700
Household appliances, Imports,
Intergovernmental relations, Small
businesses.
Issued in Washington, DC, on January 9,
2012.
Kathleen B. Hogan,
Deputy Assistant Secretary, Energy Efficiency
and Renewable Energy.
For the reasons stated in the
preamble, DOE amends part 430 of
chapter II of title 10, of the Code of
Federal Regulations, as set forth below:
PART 430—ENERGY CONSERVATION
PROGRAM FOR CONSUMER
PRODUCTS
1. The authority citation for part 430
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6309; 28 U.S.C.
2461 note.
2. Appendix A to subpart B of part
430 is amended by:
■ a. Revising section 4.2.1.1, including
figure 1;
■ b. Revising section 4.2.1.2, including
figure 2;
■ c. Revising 4.2.4; and
■ d. Revising sections 5.2.1.3 and
5.2.1.5.
The revisions read as follows:
■
Appendix A to Subpart B of Part 430—
Uniform Test Method for Measuring the
Energy Consumption of Electric
Refrigerators and Electric RefrigeratorFreezers
*
*
*
*
*
*
*
4. Test Period
*
*
*
4.2.1.1 Cycling Compressor System. For a
system with a cycling compressor, the second
part of the test starts at the termination of the
last regular compressor ‘‘on’’ cycle. The
average temperatures of the fresh food and
freezer compartments measured from the
termination of the previous compressor ‘‘on’’
cycle to the termination of the last regular
compressor ‘‘on’’ cycle must both be within
0.5 °F (0.3 °C) of their average temperatures
measured for the first part of the test. If any
compressor cycles occur prior to the defrost
heater being energized that cause the average
temperature in either compartment to deviate
from its average temperature for the first part
of the test by more than 0.5 °F (0.3 °C), these
compressor cycles are not considered regular
compressor cycles and must be included in
the second part of the test. As an example,
a ‘‘precooling’’ cycle, which is an extended
compressor cycle that lowers the
temperature(s) of one or both compartments
prior to energizing the defrost heater, must be
included in the second part of the test. The
test period for the second part of the test ends
at the termination of the first regular
compressor ‘‘on’’ cycle after both
compartment temperatures have fully
recovered to their stable conditions. The
average temperatures of the compartments
E:\FR\FM\25JAR1.SGM
25JAR1
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
3575
°C) of their average temperatures measured
for the first part of the test. See Figure 1.
freezer compartments are within 0.5 °F
(0.3 °C) of their average temperatures
measured for the first part of the test. The
second part stops at a time after defrost
during stable operation when the
temperatures of both compartments are
within 0.5 °F (0.3 °C) of their average
temperatures measured for the first part of
the test. See Figure 2.
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
PO 00000
Frm 00017
Fmt 4700
Sfmt 4700
E:\FR\FM\25JAR1.SGM
25JAR1
ER25JA12.004
termination of the next regular compressor
‘‘on’’ cycle must both be within 0.5 °F (0.3
4.2.1.2 Non-cycling Compressor System.
For a system with a non-cycling compressor,
the second part of the test starts at a time
before defrost during stable operation when
the temperatures of both fresh food and
sroberts on DSK4TPTVN1PROD with RULES
measured from this termination of the first
regular compressor ‘‘on’’ cycle until the
3576
*
*
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
*
*
*
4.2.4 Systems with Multiple Defrost
Frequencies. This section applies to models
with long-time automatic or variable defrost
control with multiple defrost cycle types,
such as models with single compressors and
multiple evaporators in which the
evaporators have different defrost
frequencies. The two-part method in 4.2.1
shall be used. The second part of the method
will be conducted separately for each distinct
defrost cycle type.
*
*
*
*
*
5. Test Measurements
*
*
*
*
*
*
*
*
5.2.1.5 Long-time or Variable Defrost
Control for Systems with Multiple Defrost
cycle Types. The energy consumption in
kilowatt-hours per day shall be calculated
equivalent to:
ER25JA12.006
*
nearest tenth of an hour (greater than
CTL but not more than 96 hours);
F = ratio of per day energy consumption in
excess of the least energy and the
maximum difference in per-day energy
consumption and is equal to 0.20.
For variable defrost models with no values
for CTL and CTM in the algorithm, the default
values of 6 and 96 shall be used, respectively.
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
PO 00000
Frm 00018
Fmt 4700
Sfmt 4725
E:\FR\FM\25JAR1.SGM
25JAR1
ER25JA12.005
sroberts on DSK4TPTVN1PROD with RULES
*
5.2.1.3 Variable Defrost Control. The
energy consumption in kilowatt-hours per
day shall be calculated equivalent to:
ET = (1440 × EP1/T1) + (EP2 ¥ (EP1 × T2/
T1)) × (12/CT),
Where:
1440 is defined in 5.2.1.1 and EP1, EP2, T1,
T2, and 12 are defined in 5.2.1.2;
CT = (CTL × CTM)/(F × (CTM ¥ CTL) + CTL);
CTL = least or shortest compressor run time
between defrosts in hours rounded to the
nearest tenth of an hour (greater than or
equal to 6 but less than or equal to 12
hours);
CTM = maximum compressor run time
between defrosts in hours rounded to the
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
sroberts on DSK4TPTVN1PROD with RULES
Where:
1440 is defined in 5.2.1.1 and EP1, T1, and
12 are defined in 5.2.1.2;
i is a variable that can equal 1, 2, or more
that identifies the distinct defrost cycle
types applicable for the refrigerator or
refrigerator-freezer;
EP2i = energy expended in kilowatt-hours
during the second part of the test for
defrost cycle type i;
T2i = length of time in minutes of the second
part of the test for defrost cycle type i;
CTi is the compressor run time between
instances of defrost cycle type i, for longtime automatic defrost control equal to a
fixed time in hours rounded to the
nearest tenth of an hour, and for variable
defrost control equal to
(CTLi × CTMi)/(F × (CTMi ¥ CTLi) + CTLi);
CTLi = least or shortest compressor run time
between instances of defrost cycle type
i in hours rounded to the nearest tenth
of an hour (CTL for the defrost cycle type
with the longest compressor run time
between defrosts must be greater than or
equal to 6 but less than or equal to
12 hours);
CTMi = maximum compressor run time
between instances of defrost cycle type
i in hours rounded to the nearest tenth
of an hour (greater than CTLi but not
more than 96 hours);
For cases in which there are more than one
fixed CT value (for long-time defrost models)
or more than one CTM and/or CTL value (for
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
variable defrost models) for a given defrost
cycle type, an average fixed CT value or
average CTM and CTL values shall be selected
for this cycle type so that 12 divided by this
value or values is the frequency of
occurrence of the defrost cycle type in a
24 hour period, assuming 50% compressor
run time.
F = default defrost energy consumption
factor, equal to 0.20.
For variable defrost models with no values
for CT Li and CTMi in the algorithm, the
default values of 6 and 96 shall be used,
respectively.
D is the total number of distinct defrost cycle
types.
3. Appendix B to subpart B of part 430
is amended by:
■ a. Revising section 4.2.1.1 including
figure 1;
■ b. Revising section 4.2.1.2, including
figure 2; and
■ c. Revising section 5.2.1.3.
The revisions read as follows:
■
Appendix B to Subpart B of Part 430—
Uniform Test Method for Measuring the
Energy Consumption of Freezers
*
*
*
*
*
*
*
4. Test Period
*
*
*
4.2.1.1 Cycling Compressor System. For a
system with a cycling compressor, the second
PO 00000
Frm 00019
Fmt 4700
Sfmt 4700
3577
part of the test starts at the termination of the
last regular compressor ‘‘on’’ cycle. The
average temperature of the compartment
measured from the termination of the
previous compressor ‘‘on’’ cycle to the
termination of the last regular compressor
‘‘on’’ cycle must be within 0.5 °F (0.3 °C) of
the average temperature of the compartment
measured for the first part of the test. If any
compressor cycles occur prior to the defrost
heater being energized that cause the average
temperature in the compartment to deviate
from the average temperature for the first part
of the test by more than 0.5 °F (0.3 °C), these
compressor cycles are not considered regular
compressor cycles and must be included in
the second part of the test. As an example,
a ‘‘precooling’’ cycle, which is an extended
compressor cycle that lowers the
compartment temperature prior to energizing
the defrost heater, must be included in the
second part of the test. The test period for the
second part of the test ends at the
termination of the first regular compressor
‘‘on’’ cycle after the compartment
temperatures have fully recovered to their
stable conditions. The average temperature of
the compartment measured from this
termination of the first regular compressor
‘‘on’’ cycle until the termination of the next
regular compressor ‘‘on’’ cycle must be
within 0.5 °F (0.3 °C) of the average
temperature of the compartment measured
for the first part of the test. See Figure 1.
E:\FR\FM\25JAR1.SGM
25JAR1
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
sroberts on DSK4TPTVN1PROD with RULES
4.2.1.2 Non-cycling Compressor System.
For a system with a non-cycling compressor,
the second part of the test starts at a time
before defrost during stable operation when
the compartment temperature is within 0.5 °F
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
(0.3 °C) of the average temperature of the
compartment measured for the first part of
the test. The second part stops at a time after
defrost during stable operation when the
compartment temperature is within 0.5 °F
PO 00000
Frm 00020
Fmt 4700
Sfmt 4700
(0.3 °C) of the average temperature of the
compartment measured for the first part of
the test. See Figure 2.
E:\FR\FM\25JAR1.SGM
25JAR1
ER25JA12.007
3578
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 / Rules and Regulations
*
*
*
*
5. Test Measurements
sroberts on DSK4TPTVN1PROD with RULES
*
*
*
*
*
5.2.1.3 Variable Defrost Control. The
energy consumption in kilowatt-hours per
day shall be calculated equivalent to:
ET = (1440 × K × EP1/T1) + (EP2¥(EP1 × T2/
T1)) × K × (12/CT),
Where:
ET, K, and 1440 are defined in section
5.2.1.1;
EP1, EP2, T1, T2, and 12 are defined in
section 5.2.1.2;
CT = (CTL × CTM)/(F × (CTM¥CTL) + CTL)
Where:
CTL = least or shortest compressor run time
between defrosts in hours rounded to the
nearest tenth of an hour (greater than or
equal to 6 hours but less than or equal
to 12 hours);
CTM = maximum compressor run time
between defrosts in hours rounded to the
nearest tenth of an hour (greater than
CTL but not more than 96 hours);
VerDate Mar<15>2010
21:03 Jan 24, 2012
Jkt 226001
F = ratio of per day energy consumption in
excess of the least energy and the
maximum difference in per-day energy
consumption and is equal to 0.20.
For variable defrost models with no values
for CTL and CTM in the algorithm, the default
values of 6 and 96 shall be used, respectively.
*
*
*
*
*
[FR Doc. 2012–1341 Filed 1–24–12; 8:45 am]
DEPARTMENT OF TRANSPORTATION
Federal Aviation Administration
14 CFR Part 39
[Docket No. FAA–2011–0219; Directorate
Identifier 2010–NM–228–AD; Amendment
39–16921; AD 2012–01–09]
RIN 2120–AA64
BILLING CODE 6450–01–P
PO 00000
Airworthiness Directives; The Boeing
Company Airplanes
Federal Aviation
Administration (FAA), DOT.
ACTION: Final rule.
AGENCY:
We are adopting a new
airworthiness directive (AD) for certain
The Boeing Company Model 757–200,
–200CB, and –300 series airplanes with
off-wing escape slide systems installed.
This AD was prompted by reports of inflight loss of the off-wing escape slide.
SUMMARY:
Frm 00021
Fmt 4700
Sfmt 4700
E:\FR\FM\25JAR1.SGM
25JAR1
ER25JA12.008
*
3579
Agencies
[Federal Register Volume 77, Number 16 (Wednesday, January 25, 2012)]
[Rules and Regulations]
[Pages 3559-3579]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2012-1341]
========================================================================
Rules and Regulations
Federal Register
________________________________________________________________________
This section of the FEDERAL REGISTER contains regulatory documents
having general applicability and legal effect, most of which are keyed
to and codified in the Code of Federal Regulations, which is published
under 50 titles pursuant to 44 U.S.C. 1510.
The Code of Federal Regulations is sold by the Superintendent of Documents.
Prices of new books are listed in the first FEDERAL REGISTER issue of each
week.
========================================================================
Federal Register / Vol. 77, No. 16 / Wednesday, January 25, 2012 /
Rules and Regulations
[[Page 3559]]
DEPARTMENT OF ENERGY
10 CFR Part 430
[Docket No. EERE-2009-BT-TP-0003]
RIN 1904-AB92
Energy Conservation Program for Consumer Products: Test
Procedures for Refrigerators, Refrigerator-Freezers, and Freezers
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: This rulemaking amends the interim final rule for test
procedures for refrigerators, refrigerator-freezers, and freezers,
issued on December 16, 2010. Specifically, it amends test procedures at
subpart B, appendices A and B, by incorporating changes to the interim
final rule that will apply to all measurements of energy consumption of
newly manufactured products starting September 15, 2014.
These amendments modify the required test period for the second
part of the test for products with cycling compressor systems and long-
time automatic defrost or variable defrost control and adjust the
default values of maximum and minimum compressor run time for products
with variable defrost. These changes will ensure a more accurate
measurement of the energy use of products with variable defrost
control.
DATES: The amendments are effective February 24, 2012 and are required
to establish compliance with the applicable energy conservation
standards starting on September 15, 2014.
ADDRESSES: The docket is available for review at regulations.gov,
including Federal Register notices, framework documents, public meeting
attendee lists and transcripts, comments, and other supporting
documents/materials. All documents in the docket are listed in the
regulations.gov index. However, not all documents listed in the index
may be publicly available, such as information that is exempt from
public disclosure.
A link to the docket web page can be found at: https://www.regulations.gov/#!docketDetail;dct=FR%252BPR%252BN%252BO%252BSR;rpp=10;po=0;D=EERE-
2009-BT-TP-0003.
This web page will contain a link to the docket for this rulemaking
on the regulations.gov site. The regulations.gov web page will contain
simple instructions on how to access all documents, including public
comments, in the docket.
For further information on how to review the docket, contact Ms.
Brenda Edwards at (202) 586-2945 or by email:
Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Mr. Lucas Adin, U.S. Department of
Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Program, EE-2J, 1000 Independence Avenue SW., Washington,
DC 20585-0121, (202) 287-1317, email: Lucas.Adin@ee.doe.gov or Mr.
Michael Kido, U.S. Department of Energy, Office of the General Counsel,
GC-71, 1000 Independence Avenue SW., Washington, DC 20585-0121, (202)
586-8145, email: Michael.Kido@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
Table of Contents
I. Background and Authority
II. Summary of the Final Rule
III. Discussion
A. Products Covered by the Final Rule
B. Compliance Dates for the Amended Test Procedures
C. Test Procedure Amendments Incorporated in This Final Rule
1. Default Values for CTL and CTM
2. Modification of Long-Time and Variable Defrost Test Method To
Fully Capture Energy Use for Temperature Recovery
D. Other Issues
1. Anti-Circumvention Language
2. Refrigeration Products Designed for Sale With or Without
Icemakers
3. Wine Storage and Combination Wine Storage Products
4. Multiple Compressor Systems
5. Triangulation
E. Compliance With Other EPCA Requirements
1. Test Burden
2. Changes in Measured Energy Use
IV. Procedural Requirements
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under the Treasury and General Government
Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
V. Approval of the Office of the Secretary
I. Background and Authority
Title III of the Energy Policy and Conservation Act (42 U.S.C.
6291, et seq.; ``EPCA'' or, ``the Act'') sets forth a variety of
provisions designed to improve energy efficiency. (All references to
EPCA refer to the statute as amended through the Energy Independence
and Security Act of 2007 (EISA 2007), Public Law 110-140 (Dec. 19,
2007)). Part B of title III (42 U.S.C. 6291-6309), which was
subsequently redesignated as Part A for editorial reasons, establishes
the ``Energy Conservation Program for Consumer Products Other Than
Automobiles.'' Refrigerators, refrigerator-freezers, and freezers
(collectively referred to below as ``refrigeration products'') are all
treated as ``covered products'' under this Part. (42 U.S.C. 6291(1)-(2)
and 6292(a)(1)) Under the Act, this program consists essentially of
three parts: (1) Testing, (2) labeling, and (3) Federal energy
conservation standards. The testing requirements consist of test
procedures that manufacturers of covered products must use (1) as the
basis for certifying to the U.S. Department of Energy (DOE) that their
products comply with the applicable energy conservation standards
adopted under EPCA, and (2) for making representations about the
efficiency of those products. Similarly, DOE must use these test
requirements to determine whether the products comply with any relevant
standards promulgated under EPCA.
By way of background, the National Appliance Energy Conservation
Act of 1987 (NAECA), Public Law 100-12,
[[Page 3560]]
amended EPCA by including, among other things, performance standards
for refrigeration products. (42 U.S.C. 6295(b)) On November 17, 1989,
DOE amended these performance standards for products manufactured on or
after January 1, 1993. 54 FR 47916. DOE subsequently published a
correction to revise these new standards for three product classes. 55
FR 42845 (October 24, 1990). DOE again updated the performance
standards for refrigeration products on April 28, 1997, for products
manufactured on or after July 1, 2001. 62 FR 23102.
EISA 2007 amended EPCA by requiring DOE to publish a final rule
determining whether to amend the energy conservation standards for
refrigeration products manufactured starting in 2014. (42 U.S.C.
6295(b)(4)) Consistent with this requirement, DOE issued on September
18, 2008, a framework document that outlined a series of issues related
to its examination of potential amendments to the standards for
refrigeration products. 73 FR 54089. On September 29, 2008, DOE held a
public workshop to discuss the framework document and the issues it
raised. The framework document identified several test procedure
issues, including: (1) Compartment temperature changes; (2) modified
volume calculation methods; (3) products that deactivate energy-using
features during energy testing; (4) variable anti-sweat heaters; (5)
references to the updated AHAM Standard HRF-1-2008, (``HRF-1-2008''),
``Energy and Internal Volume of Refrigerating Appliances (2008),''
developed by the Association of Home Appliance Manufacturers (AHAM),
including the ``Errata to Energy and Internal Volume of Refrigerating
Appliances, Correction Sheet'' issued on November 17, 2009; (6)
convertible compartments; and (7) harmonization with international test
procedures. (``Energy Conservation Standards Rulemaking Framework
Document for Residential Refrigerators, Refrigerator-Freezers, and
Freezers,'' RIN 1904-AB79, Docket No. EERE-2008-BT-STD-0012). DOE
conducted analyses and developed new energy conservation standards for
refrigeration products that led to the eventual publication of the
final rule adopting new energy conservation standards for refrigeration
products manufactured starting September 15, 2014. See 76 FR 59516
(Sept. 15, 2011) (``standards final rule'') and 76 FR 70865 (Nov. 16,
2011) (date correction notice).
DOE initiated the test procedure rulemaking in part to address the
issues identified in the framework document, and published a notice of
proposed rulemaking on May 27, 2010, hereafter referred to as ``the
NOPR.'' 75 FR 29824. In response to issue (3) above, as applied to
automatic icemakers, DOE separately published a guidance document
addressing various aspects related to the icemaker, including the
proper manner in which to render an icemaker inoperative for the energy
consumption test. See 75 FR 2122 (Jan. 14, 2010). DOE held a public
meeting to discuss the NOPR proposals on June 22, 2010 and subsequently
published the combined final/interim-final rule on December 16, 2010.
75 FR 78810. The final rule (or ``December 2010 final rule'')
implemented test procedure amendments applicable to products
manufactured before the effective date of the new energy conservation
standards that DOE had been considering, and the interim final rule (or
``interim final rule'') implemented on an interim basis test procedure
amendments applicable to products subject to the new energy
conservation standards--i.e., those products manufactured starting
September 15, 2014. Id. DOE adopted this split approach in response to
industry requests to provide an additional opportunity to comment on
final aspects related to the interim final rule. Id. at 78845.
General Test Procedure Rulemaking Process
Under 42 U.S.C. 6293, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered products. EPCA provides in relevant part that ``[a]ny test
procedures prescribed or amended under this section shall be reasonably
designed to produce test results which measure energy efficiency,
energy use * * * or estimated annual operating cost of a covered
product during a representative average use cycle or period of use, as
determined by the Secretary [of Energy], and shall not be unduly
burdensome to conduct.'' (42 U.S.C. 6293(b)(3))
In addition, if DOE determines that a test procedure amendment is
warranted, it must publish proposed test procedures and offer the
public an opportunity to present oral and written comments. (42 U.S.C.
6293(b)(2)) When considering amending a test procedure, DOE must
determine ``to what extent, if any, the proposed test procedure would
alter the * * * measured energy use * * * of any covered product as
determined under the existing test procedure.'' (42 U.S.C. 6293(e)(1))
If DOE determines that the amended test procedure would alter the
measured energy use of a covered product, DOE must also amend the
applicable energy conservation standard accordingly. (42 U.S.C.
6293(e)(2))
With respect to today's rulemaking, DOE has determined that none of
the amendments adopted in this final rule notice is likely to
significantly change the measured energy use of refrigeration products
when compared to the test procedure set forth in the interim final
rule. In such situations, EPCA does not require a standards rulemaking
to address such changes in measured energy efficiency. (42 U.S.C.
6293(e)(2)).
Today's rule also fulfills DOE's obligation to periodically review
its test procedures under 42 U.S.C. 6293(b)(1)(A). DOE anticipates that
its next evaluation of this test procedure will occur in a manner
consistent with the timeline set out in this provision.
Refrigerators and Refrigerator-Freezers
DOE's test procedures for refrigerators and refrigerator-freezers
are found at 10 CFR part 430, subpart B, appendices A1 (currently in
effect) and A (required for rating of products starting September 15,
2014). DOE initially established its test procedures for refrigerators
and refrigerator-freezers in a final rule published in the Federal
Register on September 14, 1977. 42 FR 46140. Industry representatives
viewed these test procedures as too complex and eventually developed
alternative test procedures in conjunction with AHAM that were
incorporated into the 1979 version of HRF-1, ``Household Refrigerators,
Combination Refrigerator-Freezers, and Household Freezers'' (HRF-1-
1979). Using this industry-created test procedure, DOE revised its test
procedures on August 10, 1982. 47 FR 34517. On August 31, 1989, DOE
published a final rule establishing test procedures for variable
defrost control (a control type in which the time interval between
successive defrost cycles is determined by operating conditions
indicating the need for defrost rather than by compressor run time),
dual compressor refrigerator-freezers, and freezers equipped with
``quick-freeze'' (a manually-initiated feature that bypasses the
thermostat and runs the compressor continuously until terminated). 54
FR 36238. DOE amended the test procedures again on March 7, 2003, by
modifying the test period used for products equipped with long-time
automatic defrost (a control type in which defrost cycles are separated
by 14 hours or more of compressor run time) or variable defrost. 68 FR
10957. The test procedures include provisions for determining the
annual energy use in
[[Page 3561]]
kilowatt-hours (kWh) and the accompanying annual operating costs.
DOE further amended the test procedures on December 16, 2010. 75 FR
78810. These amendments helped clarify how to test products for
compliance with the applicable standards. The amendments clarified
certain elements in Appendix A1 to ensure that regulated entities fully
understand how to apply and implement the test procedure. These changes
included clarifying how refrigeration products equipped with special
compartments and/or more than one fresh food compartment or more than
one freezer compartment should be tested. The amendments also accounted
for the various waivers granted by DOE, specifically with regard to
variable anti-sweat heater controls. The final rule also modified the
regulatory definition of ``electric refrigerator-freezer'' to require
that storage temperatures in the fresh food compartment be at a level
that would effectively exclude coverage of combination wine storage-
freezer products. See 10 CFR 430.2. The definition for ``electric
refrigerator'' was also changed to clarify the characteristics that
distinguish it from related products such as wine storage products. DOE
is considering modifying its product definitions to address wine
storage products in a separate future rulemaking.
In that same notice, DOE also established a new Appendix A, via an
interim final rule. The new Appendix A included a number of
comprehensive changes to help improve the measurement of energy
consumption of refrigerators and refrigerator-freezers. These changes
included, among other things: (1) New compartment temperatures and
volume adjustment factors, (2) new methods for measuring compartment
volumes, (3) a modification of the long-time automatic defrost test
procedure to ensure that the test procedure measures all energy use
associated with the defrost function, and (4) test procedures for
products with a single compressor and multiple evaporators with
separate active defrost cycles. DOE noted that the compartment
temperature changes introduced by Appendix A would significantly impact
the measured energy use and affect the calculated adjusted volume and
energy factor (i.e. adjusted volume divided by energy use) values.
Lastly, the interim final rule also addressed icemaking energy use by
including a fixed value for manufacturers to add when calculating the
energy consumption of those products equipped with an automatic
icemaker. DOE may consider revising this approach once a more
appropriate means of accounting for this feature's energy consumption
is developed.
Freezers
DOE's test procedures for freezers are found at 10 CFR part 430,
subpart B, appendices B1 (currently in effect) and B (required for the
rating of products starting in 2014). DOE established its test
procedures for freezers in a final rule published in the Federal
Register on September 14, 1977. 42 FR 46140. As with DOE's test
procedures for refrigerators and refrigerator-freezers, industry
representatives viewed the freezer test procedures as too complex and
worked with AHAM to develop alternative test procedures, which were
incorporated into the 1979 version of HRF-1. DOE revised its test
procedures for freezers based on this AHAM standard on August 10, 1982.
47 FR 34517. The subsequent August 31, 1989 final rule established test
procedures for freezers with variable defrost control and freezers with
the quick-freeze feature. 54 FR 36238. A subsequent amendment occurred
to correct that rule's effective date. 54 FR 38788 (Sept. 20, 1989).
The current test procedures include provisions for determining the
annual energy use in kWh and annual electrical operating costs for
freezers.
The December 16, 2010 notice also clarified compliance testing
requirements for freezers under Appendix B1 and created a new Appendix
B, the latter of which would apply in 2014. That new procedure changed
a number of aspects to the procedure detailed in Appendix B1,
including, among other things: (1) The freezer volume adjustment
factor, (2) methods for measuring compartment volumes, and (3) the
long-time automatic defrost test procedure. In addition, Appendix B
also addresses icemaking energy use by implementing the same procedure
as for refrigerator-freezers in which a fixed energy use value is
applied when calculating the energy consumption of freezers with
automatic icemakers.
Finalization of the Test Procedure Rulemaking for Products Manufactured
Starting in 2014
The interim final rule established comprehensive changes to the
manner in which the test procedures are conducted by creating new
Appendices A and B. In addition to the changes discussed above, these
appendices incorporate the recent changes made to Appendices A1 and B1.
These new appendices also incorporate the modifications to Appendices
A1 and B1 that were finalized and adopted on December 16, 2010.
DOE had provided an initial comment period on the interim final
rule that ended on February 14, 2011. DOE subsequently reopened the
comment period on September 15, 2011 (76 FR 57612) to allow further
public feedback in response to the promulgation of the final energy
conservation standards that were published on the same day. 76 FR
57516. DOE reopened the comment period to permit interested parties to
comment on the interplay between the test procedure and the energy
conservation standards in order to permit DOE to make any final changes
that may be needed to the final test procedure for products that will
be manufactured starting in 2014. 76 FR 57612-57613 (Sept. 15, 2011).
The comment period ended on October 17, 2011.
Three stakeholders submitted comments in response to both
supplemental comment periods that DOE provided for additional
feedback--the Association of Home Appliance Manufacturers (AHAM), Sub
Zero-Wolf, Inc. (Sub Zero), and Whirlpool Corporation (Whirlpool).
Table I.1 below identifies these commenters and their affiliation. No
other comments were received.
Table I.1--Stakeholders That Submitted Comments on the Interim Final
Rule
------------------------------------------------------------------------
Name Acronym Type*
------------------------------------------------------------------------
Association of Home Appliance AHAM................. IR
Manufacturers.
Sub Zero-Wolf, Inc................ Sub Zero............. M
Whirlpool Corporation............. Whirlpool............ M
------------------------------------------------------------------------
* IR: Industry Representative; M: Manufacturer.
DOE also considered comments related to a petition for a test
procedure waiver (RF-018, Samsung) that had a direct bearing on
elements of the test procedures used in Appendix A. See 76 FR 16760
(March 25, 2011).
II. Summary of the Final Rule
Today's rulemaking finalizes the test procedures that manufacturers
must follow when certifying basic models as compliant with the new
energy conservation standards starting in 2014. In finalizing these
procedures, DOE made minor changes to the procedure laid out in the
December 2010 interim final rule to account for comments from
interested parties. The changes will not result in a significant change
in measured energy use when compared to
[[Page 3562]]
the procedure detailed in the interim final rule. The December 2010
amendments for Appendices A1 and B1 are unchanged by today's rulemaking
and continue to apply to products manufactured through September 14,
2014. (Those aspects of the December 2010 notice were not reopened for
comment as they were not part of the interim final rule. 75 FR at
78813-78815 (Dec. 16, 2010).) In addition, other amendments made in the
December 2010 final rule, including modified definitions, anti-
circumvention language, applying the anti-sweat heater switch credit to
energy use measurements, and rounding off energy test results also were
not part of the interim final rule and were not reopened for comment.
Accordingly, these aspects of the December 2010 notice remain
unchanged.
Today's rulemaking makes a series of changes that include (a)
modifying the default values of CTL and CTM,
parameters, which represent the minimum and maximum compressor run time
between defrosts, for products with variable defrost that do not have
values for these parameters specified in their control algorithms, and
(b) modifying the test period for products with cycling compressors and
long-time or variable defrost to ensure the procedure accurately
captures energy use associated with temperature recovery after defrost.
The rulemaking also makes changes to clarify how to apply the second
part of the test for products with long-time or variable defrost.
III. Discussion
The following section discusses in further detail the various
issues addressed by today's rulemaking. These issues center chiefly on
issues raised in commenter submissions. Section A identifies the
products covered by the rule; section B specifies the compliance dates
for the test procedure amendments made; section C discusses the test
procedure amendments; and section D discusses stakeholder comments not
associated with new amendments.
A. Products Covered by the Final Rule
Today's amendments cover those products that meet the definitions
for refrigerator, refrigerator-freezer, and freezer, as codified in 10
CFR 430.2. The definitions for refrigerator and refrigerator-freezer
were amended in the December 2010 final rule on December 16, 2010. 75
FR 78810, 78817.
Today's rulemaking does not change any of the definitions for
refrigeration products that DOE amended as part of the December 2010
final rule. While DOE appreciates the concerns raised by commenters,
these particular issues were not completely vetted through the
rulemaking process. DOE may, however, revisit and more closely examine
these issues as part of a future rulemaking activity. Section D.3
discusses the comments related to wine storage and wine storage
combination products, including the amended definitions for
refrigerator and refrigerator-freezer.
B. Compliance Dates for the Amended Test Procedures
Manufacturers will need to use new Appendices A and B to rate
refrigeration products once they are required to comply with the
amended energy conservation standards--i.e. September 15, 2014.
Likewise, Appendices A and B will be mandatory for representations
regarding energy use or operating cost of these products starting on
that date.
C. Test Procedure Amendments Incorporated in This Final Rule
Today's rulemaking finalizes Appendices A and B, with some
amendments. These amendments are described in greater detail below.
1. Default Values for CTL and CTM
Refrigeration products with variable defrost vary the frequency of
defrost by reducing this frequency to save energy when the frost
accumulation rate on the evaporator drops--such as when the number of
door openings is reduced or when ambient humidity is low. Defrost
frequency is characterized by the compressor run time between defrosts,
CT, which is expressed in the test procedure in hours rounded to the
nearest tenth of an hour. Variable defrost control algorithms vary CT
as the defrost need changes. These algorithms may specify a minimum CT
value (CTL) and a maximum CT value (CTM),
consistent with the minimum and maximum defrost frequencies required
for specific products to provide reliable defrost performance while
minimizing energy use. The DOE test procedure calculates the energy use
of variable defrost products using a weighted average of the
algorithm's CTL and CTM. See 75 FR at 78857,
78865 (Dec. 16, 2010) (detailing requirements of section 5.2.1.3 of new
Appendix A and existing Appendix A1, respectively). To address those
products that may have control algorithms that do not use specific
maximum and minimum values for the compressor run time between defrost
cycles, the test procedure specifies a CTL value of 12 hours
and a CTM value of 84 hours. See id. These values remained
the same for both Appendix A1 (final rule) and Appendix A (interim
final rule).
AHAM argued that the default CTL and CTM
values for the variable defrost control algorithm should be changed to
6 and 96 hours in order to maintain consistency with HRF-1-2008. (AHAM,
No. 39 at p. 5) AHAM did not provide any supporting data to show that
these values would be more representative of the operation of
refrigeration products with variable defrost control algorithms without
specific CT values, nor did it provide any justification for the change
other than to maintain consistency with HRF-1-2008.
In light of AHAM's comments, DOE reviewed the certification data
submitted by refrigeration product manufacturers in August 2011 and
specifically examined the submissions of those products with variable
defrost to determine the prevalence of different values for
CTL and CTM. DOE also investigated whether the
certification data showed any evidence of products without specified CT
values, since these would be the products whose energy use measurement
would be affected by the change suggested by AHAM. Of 2,674 records in
the database, 1,397 products were identified as having variable
defrost. None of the records for these products included undeclared
values for CTL and CTM. Table III.1 below shows
the default CTL and CTM values of the current
test procedure and of HRF-1-2008. It also shows the average, mean, and
most prevalent values for CTL and CTM gleaned
from available certification records. For each of these CTL
and CTM combinations, the calculated CT value is also
presented. The summary table shows that neither the 12 and 84 default
values nor the AHAM-suggested values of 6 and 96 provide an exact
representation of the products in the database. However, the data below
also suggest that using 6 and 96 as default values more closely
approximates the recorded values of those refrigeration products from
the database than 12 and 84.
[[Page 3563]]
Table III.1--Values of CTL, CTM and CT
----------------------------------------------------------------------------------------------------------------
CTL CTM CT
----------------------------------------------------------------------------------------------------------------
Current DOE Test Procedure Default........................ 12.0 84.0 38.2
HRF-1-2008 Default........................................ 6.0 96.0 24.0
Database Average.......................................... 8.0 82.3 *28.8
Database Median........................................... 8.0 96.0 30.0
Database Most Prevalent Values............................ 8.0 96.0 30.0
----------------------------------------------------------------------------------------------------------------
* This is the CT calculated using the average CTM and CTL values. The average of the CT values calculated
individually for each database record is 28.2.
Further, the use of the default CTL and CTM
values is prescribed for those products that do not have specific
values for these parameters in the product's control algorithm. Since
the algorithm for such a product presumably does not explicitly set a
minimum value for this time period, it is conceivable that the
compressor run time between defrosts could at times be lower than the 6
hours specified in the test procedure as a minimum for CTL
(see section 5.2.1.3 of Appendix A1 or A). When operating in this mode,
such a product would be using more energy for defrost than would a
product with an algorithm-defined CTL of 6 hours, due to the
higher defrost frequency. Hence, DOE concludes that to ensure that the
test procedure provides a conservative estimate of energy use
associated with defrost (i.e. at least as high as the actual energy
use), it is reasonable to require use of a lower default CTL
value when calculating energy use for products that do not have
algorithm-specified CTL values. For this reason, because the
HRF-1-2008 default values are more representative of the refrigeration
products in the database than the current default values, and in order
to maintain consistency with this industry standard, DOE is changing
the default values to 6 and 96 in this final rule. This change is being
made for refrigerators, refrigerator-freezers, and freezers in both
Appendices A and B.
2. Modification of Long-Time and Variable Defrost Test Method To Fully
Capture Energy Use for Temperature Recovery
Background
The interim final rule amended the test procedure for products with
long-time and variable defrost by modifying the second part of the test
to better capture energy use associated with precooling and temperature
recovery. 75 FR 78810, 78832-78836 (Dec. 16, 2010). A test procedure
waiver petition submitted by Samsung (see 76 FR 17670 (March 25, 2011))
has raised the question of whether DOE should consider further changes
to the second part of the test procedure for these products.
As described in DOE's December 2010 notice, precooling involves
cooling the compartment(s) of a refrigerator-freezer to temperatures
significantly lower than the user-selected temperature settings prior
to an automatic defrost cycle. Id. at 78832. The document also noted
that the two-part test served as a means to reduce the burden on
testing long-time and variable defrost products. Id. These products
initiate defrost cycles after significantly longer periods of
compressor run time than conventional automatic defrost products. Long-
time defrost products initiate defrost after more than 14 hours of
compressor run time, and variable defrost products adjust defrost
frequency based on whether defrost is needed, potentially delaying the
next defrost up to 96 hours of compressor run time. The second part of
the test measures the energy use consumed during a defrost cycle.
The two-part test and procedures for the second part of the test
were initially established in 1982. 47 FR 34521-34522 (Aug. 10, 1982).
Since that time, more sophisticated controls have replaced the
mechanical defrost timers that were generally used. 68 FR 10958 (March
7, 2003). Consequently, the initial procedures for the second part of
the test did not fully capture or consider the high level of
sophistication that is now possible and made available with the use of
modern electronic control systems. The defrost controls in use when the
second part of the test was first established consisted of a mechanical
defrost timer energized to advance when the compressor is energized.
The initial two-part test specified that the second part starts when
the heater energizes, which is coincident with the time the compressor
turns off in a product using a mechanical timer control. 68 FR 10957-
10958 (March 7, 2003). The first adjustment of the test procedure
considering the potential for more sophisticated control was made on
March 7, 2003. This amendment of the test procedure revised the second
part of the test to allow it to start when the compressor turns off
prior to activation of the defrost heater, which is typical of an
approach enabled by more sophisticated electronic controls. Id.
The interim final rule made additional amendments to the second
part of the test to address precooling, another defrost control feature
requiring more sophisticated control than a mechanical timer. 75 FR
78832-78836 (Dec. 16, 2010). The amendments also addressed partial
temperature recovery, which refers to a case in which the compartment
temperatures of a refrigerator partially recover, but do not reach,
their steady-state operating temperatures. For the purposes of testing,
a product is considered to reach a state of partial temperature
recovery when compartment temperatures do not reach the steady-state
operating temperature by the end of the second part of the test (as
previously specified in the test procedure) after the rise in
compartment temperature associated with defrost. The amendments
require, for a system with a cycling compressor, that the average
compartment temperatures for the compressor cycles occurring
immediately before and after the test period for the second part of the
test be within 0.5 [deg]F of the compartment temperature measured for
the first part of the test. Under the interim final rule's procedure,
the modified test period would start at the end of a compressor ``on''
cycle and end at the start of a compressor ``on'' cycle. Id. at 73885
Additional Issue Identified During Review of Samsung Waiver
After publication of the interim final rule, an additional issue
associated with the two-part test was raised during the agency's review
of a test procedure waiver petition submitted by Samsung Electronics
America, Inc. (Samsung). That petition sought a waiver from the current
test requirements for the company's products that use dual evaporators.
76 FR 16760 (March 25, 2011).\1\ These products use a variable
[[Page 3564]]
defrost strategy that employs multiple defrost cycle types, which the
interim final rule's procedure addresses for products starting in 2014.
75 FR at 78836-78838 (Dec. 16, 2010). DOE explained in the December
2010 notice that Appendices A1 and B1 do not address such products and
manufacturers seeking to certify these types of products as compliant
prior to 2014 must first obtain a test procedure waiver to enable them
to test these products. Id. at 78838. Samsung sought a waiver to permit
the company to use the Appendix A procedures for products with multiple
defrost cycle types when rating current products. 76 FR at 16763 (March
25, 2011).
---------------------------------------------------------------------------
\1\ The evaporator is the component of a refrigeration system
that cools the cabinet air. Most conventional refrigerators use a
single evaporator that cools the freezer compartment, transferring
cold freezer air to the fresh food compartment to cool the latter
compartment. Samsung's dual evaporator approach uses separate
evaporators in the freezer and fresh food compartments and does not
exchange air between the compartments.
---------------------------------------------------------------------------
Whirlpool commented in response to Samsung's waiver petition that
applying the second part of the test to the fresh food defrost of one
of these products results in an energy credit. (Whirlpool, Samsung
Petition for Test Procedure Waiver, Case No. RF-018, Docket No. EERE-
2011-BT-WAV-0017, No. 4 at p. 3) \2\ Whirlpool's waiver comments
discuss the data from testing performed by the Canadian Standards
Association that examined the energy consumption of a Samsung model
that uses multiple defrost cycles--Samsung model No. RFG297AAPN.
Whirlpool asserts that the test results are illogical because the
energy use contribution of the fresh food compartment defrost is
negative (i.e. an energy credit), and adds that the energy use
contribution of the freezer compartment defrost is underestimated. (Id.
at p. 4) Whirlpool recommended that the test period for the second
(defrost) part of the test for the fresh food defrost should end at the
end of the second compressor ``on'' cycle after defrost, and that such
a change to the test procedure only for the fresh food defrost would
increase the measured energy use of the product by 1.6 percent. (Id. at
pp. 5-6)
---------------------------------------------------------------------------
\2\ The Samsung waiver docket items have been consolidated and
loaded into the docket for this refrigerator test procedure
rulemaking, see ``Documents Related to Samsung Waiver--Case No. RF-
018, Docket No. EERE-2011-BT-WAV-0017'', No. 45.
---------------------------------------------------------------------------
Samsung's response to Whirlpool's comment pointed out that the
potential energy credit issue had been raised by DOE in its test
procedure NOPR public meeting on June 22, 2010. (Samsung, Samsung
Petition for Test Procedure Waiver, Case No. RF-018, Docket No. EERE-
2011-BT-WAV-0017, No. 5 at p. 2) In its view, this issue had been
presented by DOE for discussion and consideration by all interested
parties--including Whirlpool. The company pointed out that the test
procedure DOE ultimately selected had received the support of
Whirlpool. Id. See also Whirlpool, No. 13 at p. 6.
DOE's Previous Discussion Regarding the Appropriate End of the Test
Period
As indicated by Samsung, DOE raised this issue of Appendix A1's
potential inability to capture all energy usage during defrost cycles
when using the second (defrost) part of the test. (NOPR Public Meeting
Presentation, No. 9 at p. 53) DOE recognized this possibility during
its evaluation of the energy use associated with the fresh food
compartment defrost of a Samsung product similar to the products
addressed in the company's test procedure waiver request. That
evaluation indicated that the calculated energy use contribution from
the fresh food defrost was often negative, which resulted in an energy
use ``credit''. DOE evaluated alternative test periods and concluded
that more reasonable results are obtained when the test period ends at
the end of a compressor cycle after the defrost cycle. (Id.) DOE sought
comment during its public meeting to seek additional information on the
issues associated with the long-time defrost test method that were
presented. (Id. at p. 55)
DOE's presentation also indicated that it projected that the impact
on measured energy use of the test procedure change would be an
increase of approximately 3 percent, if applied to both defrosts of the
Samsung product that was the focus of the discussion. (Id. at p. 53)
This 3 percent impact was determined based on moving the end of the
test period for the second part of the test from the second compressor
start after defrost to the second compressor stop. DOE again reviewed
the same data and concluded that the test procedure change associated
with this final rule would reduce this measured energy use differential
by half (i.e. 1.5 percent). (``Summary of Energy Use Measurements for a
Refrigerator-Freezer with two Defrost Cycle Types'', No. 46) The
interim final rule test procedure applied to this product does not
allow the second part of the test to end at the second compressor start
after defrost, due to the requirement that the average temperature for
the compressor cycle immediately following the test period be within
0.5 [deg]F of the average temperature measured for the first part of
the test. (See Appendix A, section 4.2.1.1) Hence, the impact on energy
use measurement associated with test procedure changes to address the
observed negative energy use measurement associated with fresh-food-
only defrost cycles depends on details of the compared test periods.
Stakeholders generally supported the test procedure approach as
proposed in the Notice of Proposed Rulemaking (NOPR)--and as adopted in
the interim final rule--and none suggested that the test period of the
second part of the test should be changed to address the anomaly
presented, i.e. that measurements for a specific product showed a
negative energy use contribution associated with the fresh food
defrost. Hence, DOE concluded that the anomaly was associated with an
insignificant number of products and thus not generally significant to
the test procedure for products tested using the two-part test.
Consequently, in the interim final rule, DOE did not amend the end of
the test period for the second part of the test to coincide with the
end of a compressor ``on'' cycle (rather than the start of that cycle).
Comment Submitted in Response to the Reopening of the Comment Period
After considering Whirlpool's waiver petition comments suggesting
that DOE modify the second part of the test, DOE specifically requested
comment on this topic when it reopened the interim final rule comment
period. 76 FR 57613-57614 (Sept. 15, 2011). DOE received one comment on
this topic, from Whirlpool, which suggested that the end of the second
part of the test be moved so that it coincides with the end of a
compressor ``on'' cycle. (Whirlpool, No. 44 at pp. 1-2) Whirlpool
asserted that this change should be made for all defrosts, whether they
are for fresh food compartments or freezer compartments.
Whirlpool indicated that, for at least one product, the impact of
this test procedure change on the measured energy use for a product
having a separate defrost for the fresh food compartment would be an
increase of approximately 3 percent. Although Whirlpool did not
identify the manufacturer of that product, it mentioned that its
concerns are an extension of those concerns it raised earlier in
response to a waiver request made by a competitor--i.e. Samsung. The 3
percent impact cited by Whirlpool matches the CSA data presented in
Whirlpool's comments regarding the Samsung waiver petition: the waiver
comments indicate that the tested product's energy use increases from
572.5 kWh to 592.1 kWh per year (an increase of 3.4 percent) with the
modified test procedure, i.e. when ending the second part of the test
at the
[[Page 3565]]
end rather than the start of the second compressor ``on'' cycle after
the defrost. (Whirlpool, Samsung Petition for Test Procedure Waiver,
Case No. RF-018, Docket No. EERE-2011-BT-WAV-0017, No. 4 at p. 5) This
projected impact on the measured energy use is consistent with DOE's
own conclusions regarding Samsung products with multiple defrosts. See
NOPR Public Meeting Presentation, No. 9 at p. 53. However, as discussed
above, it overestimates the measurement impact associated with the
amendments made in this final rule.
Assessment of the Suggested Test Period Modification
Whirlpool's interim final rule comments provided little or no
explanation of how and why the suggested test period will result in
more accurate test results. Instead, the comments indicate that the
``underlying principle when measuring the energy consumption of any
product which operates in cycles is to measure from the same point in
one cycle to the same point in a successor cycle,'' and assert that the
test procedure of Appendix A measures from a compressor stop to a
compressor start for products with cycling compressors. However,
Whirlpool did not provide any explanation supporting the concept of
measuring from a point in one cycle to the same point in a successor
cycle. (Whirlpool, No. 44 at pp. 1-2) Nevertheless, Whirlpool's waiver
comments note the unintended consequences associated with the negative
energy use contribution measured for the fresh food defrost of the
Samsung product when using the interim final rule's version of the
Appendix A test period as demonstrating that the test period contained
in the interim final rule is inappropriate. (Whirlpool, Samsung
Petition for Test Procedure Waiver, Case No. RF-018, Docket No. EERE-
2011-BT-WAV-0017, No. 4 at p. 5)
DOE had provided data in its NOPR public meeting presentation
supporting the use of the modified test period, ending when the
compressor stops. This situation was illustrated both for the fresh
food defrost contribution alone and for the total defrost energy use
contribution, including both fresh food and freezer compartment
defrosts. The data showed that a test period that both starts and ends
when the compressor stops matched the energy expended by the defrost
heater during a fresh food defrost--and provided a closer match of
energy use measured from one initiation of the combined defrost cycle
(the defrost cycle involving both the fresh food and freezer
compartments) to the next initiation of the combined defrost cycle than
the Appendix A1 procedure. (NOPR Public Meeting Presentation, No. 9 at
p. 53) More recently, DOE prepared an assessment demonstrating that a
test period for the second part of the test both starting and ending at
the end of a compressor ``on'' cycle is consistent with the full-cycle
measurement specified for testing non-variable automatic defrost
products. See (``Refrigerator Test Procedure: Adjustments to Second
Part of Test'', No. 47) This document shows mathematically that a
calculation of energy use using the ``section 4.2'' test period (``full
test period'') matches the two-part calculation only when the second
part of the test ends at the end of a compressor ``on'' cycle.
Part of the justification for modifying the test procedure in the
manner suggested by Whirlpool is based on the observation that when
using the test period prescribed by the interim final rule, the average
compartment temperature would be warmer at the end of the test period
than at its start for a system with a cycling compressor. The interim
final rule test procedure includes a provision to verify that the
product does not employ partial recovery. Using this provision requires
examining the full compressor cycle immediately after the test period
to ensure that it is a regular compressor cycle, i.e. a compressor
cycle associated with steady state operation. However, the test does
not account for the additional temperature recovery associated with a
regular compressor ``on'' cycle. The December 2010 notice indicates
that the test period T2 starts when the compartment is at its typical
minimum temperature associated with steady state cycling operation.
This minimum temperature is represented by the lower horizontal line of
the temperature plot in Figure 1 of Appendix A. 75 FR at 78855 (Dec.
16, 2010) (see temperature plot of Figure 1, ``Long-time Automatic
Defrost Diagram for Cycling Compressors'').
On the other hand, the compartment temperature is at its typical
steady-state cycling maximum (the higher horizontal line of the
temperature plot) when test period T2 ends. Hence, while the
compartment temperature has recovered to the range within which it
varies during steady state operation, it has not recovered to the
temperature state associated with the start of the test period--i.e.
the temperature is warmer than at the start of the test period. In
order to allow recovery to the start-of-test-period temperature, the
test period would have to continue till the end of the compressor
``on'' cycle. These arguments illustrate that the test period
prescribed by the interim final rule for the second part of the test is
unlikely to fully account for energy use associated with temperature
recovery.
DOE concludes that the test period for the second part of the test
that is specified in the interim final rule for products with cycling
compressors and long-time or variable defrost may not accurately
represent energy use associated with defrost, which necessitates a
change to enhance the accuracy of the measurement. DOE received no
other comments on this topic. Hence, in light of this new information,
and its own review, DOE is adopting the approach suggested by Whirlpool
to help ensure the procedure in Appendix A provides a greater level of
accuracy.
Four-Hour Time Limit
DOE also considered whether to retain the four-hour time limit that
the current test imposes on the second part of the test. This limit
applies to the elapsed time after the defrost heater is energized.\3\
(See Appendix A section 4.2.1.1 or Figure 1) The four-hour limit
terminates the test period when recovery from defrost and return to
steady-state cycling operation takes an unusually long time. During its
review of the test period for the second part of the test, DOE noticed
that for some products, the extension of the test period associated
with the test period revision recommended by Whirlpool led to a test
period invoking the four-hour limit (i.e. the desired end of the test
period was more than four hours later than activation of the defrost
heater).
---------------------------------------------------------------------------
\3\ Note that the elapsed time after the defrost heater is
energized is not the same as T2, since the test period generally
starts prior to activation of the heater for testing in accordance
with Appendix A.
---------------------------------------------------------------------------
DOE notes that modern data collection is performed almost
exclusively using automated data acquisition systems. This approach to
recording data significantly reduces the test burden that could
potentially be associated with extending the test beyond the four-hour
limit, allowing a product to fully complete its temperature recovery
after defrost during testing. Test technicians do not need to observe
product behavior during the test from minute to minute to ensure that
data are recorded. Instead, technicians are more likely to periodically
check the status of a given test once or twice a day to determine
whether a defrost has occurred and whether the test period has been
completed. With modern variable-defrost products, a full refrigerator
test
[[Page 3566]]
can take a week to complete because of the duration of the time
intervals between defrosts. The compressor run time between defrosts
can last as long as 96 hours for variable defrost products (see
Appendix A, section 5.2.1.3 regarding the maximum allowable duration
for CTM, the maximum compressor run time between defrosts).
At a typical compressor on-time of 50 percent, the time involved in
waiting for a defrost cycle can be days. With the use of automated data
acquisition equipment by test labs necessitating only periodic status
checks, the need for 24-hour staffing for data recording has been
effectively eliminated.\4\
---------------------------------------------------------------------------
\4\ Personal communication, Detlef Westphalen of Navigant
Consulting, Inc. with Terry Drew, CSA International, 12/5/11.
---------------------------------------------------------------------------
Further, the continued application of the four-hour limit is likely
to reduce measurement accuracy, since the limit could cause a
significant portion of the compressor ``on'' cycle to be dropped from
the measurement.\5\ In light of the more advanced capabilities of
testing labs and the operation of modern refrigeration products, DOE
believes that the four-hour time limit of the second part of the test
is obsolete as a means to limit test burden and may in fact prevent the
accurate measurement of energy consumption of these products. Because
of the impact of the four-hour time limit on test measurement accuracy,
and because it is no longer needed to reduce test burden, DOE is
eliminating this provision of the test procedure for Appendices A and B
in this notice. Making this change will also fully address the
potential problem identified by Whirlpool by eliminating any incentives
by some manufacturers to exploit potential limitations presented by a
procedure that artificially limits the overall testing duration without
fully capturing that product's energy consumption.
---------------------------------------------------------------------------
\5\ For example, suppose the test period criteria for
temperature recovery are met at the end of the third compressor
``on'' cycle after the defrost, but the four hour limit ends the
test period just after the start of the third compressor ``on''
cycle. In this case, a significant portion of compressor energy use
is eliminated from the measurement for the second part of the test.
---------------------------------------------------------------------------
Recovery for Both Compartments of a Refrigerator or Refrigerator-
Freezer
The interim final rule requirements for confirming that the second
part of the test does not include events associated with precooling and
temperature recovery provide a means to compare the temperatures of
``the compartment'' measured during the first part of the test with the
average temperatures of ``the compartment'' for compressor cycles
preceding and following the second part of the test. (See Appendix A,
section 4.2.1.1) The language does not specify which compartment must
be evaluated in this fashion. In order to assure that the test
procedure properly accounts for energy use associated with precooling
and temperature recovery of the entire product, the language of section
4 of Appendix A is modified to clarify that these requirements apply to
both compartments (i.e. the freezer compartment and the fresh food
compartment), regardless of which compartment's evaporator undergoes
defrost. DOE is making this clarification to assure testing accuracy.
Modification of Figure 2 of Appendices A and B
The interim final rule includes a figure for both Appendices A and
B that illustrates the second part of the test for products with non-
cycling compressors. That figure, Figure 2, includes two horizontal
lines in the temperature plot that have no meaning. In this final rule,
these lines of Figure 2 have been removed. DOE is making this change to
avoid confusion and to ensure the accuracy of the measured test
results. This amendment represents no change to the specified test
procedure.
Addition of Minor Edits for Clarification
While reviewing the modified new sections 4.2.1.1 and 4.2.1.2
incorporating the changes discussed above, DOE concluded that some
minor adjustments to the language would be needed to clarify the test
procedure and to ensure the overall consistency of the procedure. These
adjustments include the following:
In the first and second lines of both sections, changing
``* * * the second part starts * * *'' to ``* * * the second part of
the test starts * * *''.
In section 4.2.1.1, changing ``* * * first part's
temperature * * *'' to ``* * * average temperature for the first part
of the test * * *''
These changes are made in parallel sections to both Appendices A
and B.
Impact of the Test Procedure Change on Measured Energy Use
Whirlpool estimated that modifying the test procedure to address
the observed negative energy use associated with fresh food compartment
defrosts would increase the measured energy use of a tested
competitor's product by 3 percent. (Whirlpool, No. 44 at p. 2) These
results are consistent with the results DOE observed, as reported in
the NOPR public meeting. (NOPR Public Meeting Presentation, No. 9 at p.
53). However, as discussed above, DOE has re-examined the available
data and now projects that the increase in energy use for such a
product is only 1.5 percent applying the amended procedure made in this
final rule. This latter estimate more accurately reflects the
differences in the test period of the second part of the tests as
represented by the interim final rule and today's final rule.
(``Summary of Energy Use Measurements for a Refrigerator-Freezer with
two Defrost Cycle Types'', No. 46) In addition, as discussed further
below, DOE has determined that the impact of the test procedure change
on energy use measurement for most affected products is near 1 percent.
DOE also notes that the energy use impact of this change would apply
only for those variable defrost products that use cycling compressors.
To assess the potential impact on the measured energy use
associated with the test procedure change suggested by Whirlpool, DOE
reviewed the data it collected to support the test procedure's
development and data collected as part of its compliance efforts. The
analysis DOE conducted drew from two separate sets of test reports. The
first set included tests conducted using the current test procedures of
Appendix A1. For this set of tests, the applicable temperature settings
did not permit one to calculate a weighted-average energy use at the
Appendix A standardized compartment temperatures of 0 [deg]F for the
freezer compartment, and 39 [deg]F for the fresh food compartment,
because the measured compartment temperatures for the two tests
conducted at different temperature control settings (i.e. median
setting and either warmest or coldest settings prescribed in the
temperature control setting requirements of Appendix A1, section 3) did
not generally bound these standardized temperatures. The second set of
tests, in contrast, included measurements at temperature settings
allowing calculation of results consistent with the Appendix A
standardized compartment temperatures. These tests involved the use of
temperature control settings suitable for the Appendix A standardized
temperatures.
For the first set of tests, DOE evaluated the impact of the test
procedure change only for the coldest compartment temperature setting
used in the test, which was typically the median setting. The
compartment temperatures of these tests fell within 3[deg]F of the
Appendix A standardized temperatures. While this difference represents
a deviation from the Appendix A test requirements, DOE still considers
these results to be a good predictor of the expected operation of
[[Page 3567]]
these products under standardized compartment temperature conditions
for two reasons--(1) the small size of the temperature deviations and
(2) the measured data demonstrate that the influence of compartment
temperature on the estimated impact of the test procedure change was
negligible.
The analysis focused on four key refrigerator-freezer product
classes: class 3 (refrigerator-freezers--automatic defrost with top-
mounted freezer without through-the-door ice service), class 5 products
without exception relief (refrigerator-freezers--automatic defrost with
bottom-mounted freezer without through-the-door ice service), class 5
with exception relief to account for through-the-door ice service (for
the purposes of this discussion, designated product class 5A under the
recently promulgated standards for 2014), and class 7 (refrigerator-
freezers--automatic defrost with side-mounted freezer with through-the-
door ice service). These product classes were chosen because they
represent significant market share, have automatic defrost, and are the
most likely products to have variable defrost, thus indicating that
they would be more likely candidates to be tested using the two-part
test. The assessment focused solely on products with cycling
compressors and variable defrost, since the test procedure change does
not affect energy use measurement for other products.
DOE re-evaluated the test results for both sets of data using the
modified test period for the second part of the test as described in
this section, including both shifting the end of the test period to a
compressor stop (rather than a compressor start) and removing the four-
hour time limit. Table III.2 summarizes the results of this assessment
for both sets of data and does not include any data covering Samsung
products. The average measurement impact for these 25 products is under
1 percent.
Table III.2--Measured Energy Use Increase
----------------------------------------------------------------------------------------------------------------
First set of tests Second set of tests
----------------------------------------------------------------------------------------------------------------
Average energy Average energy
Product class Number of units use impact Number of units use impact
(percent) (percent)
----------------------------------------------------------------------------------------------------------------
3....................................... 6 0.99 2 0.90
5....................................... 2 1.05 1 0.89
5A...................................... 3 1.08 2 1.21
7....................................... 6 0.73 3 0.85
All Units............................... 17 0.92 8 0.95
----------------------------------------------------------------------------------------------------------------
DOE also separately evaluated data for six Samsung products falling
into classes 5A and 7, for which the overall average measured impact
was 1.55 percent. DOE believes that the reason for the greater
sensitivity of Samsung products to this test procedure change as
compared with other products is that these products have two defrosts
(one combined defrost of both the freezer and fresh food compartment
evaporators and one defrost of only the fresh food evaporator)
occurring in the same amount of time that other products use one
defrost.
Shipment-Weighted Impact of the Test Procedure Change on Measured
Energy Use
DOE developed estimates of shipment-weighted impacts on the
measured energy use of the test procedure change for the four product
classes highlighted in Table III.2. The test procedure amendments apply
only to variable defrost products with cycling compressors. Table III.3
summarizes the percentage of models with variable defrost fo