Energy Conservation Program: Test Procedure for Automatic Commercial Ice Makers, 1591-1614 [2012-218]
Download as PDF
1591
Rules and Regulations
Federal Register
Vol. 77, No. 7
Wednesday, January 11, 2012
This section of the FEDERAL REGISTER
contains regulatory documents having general
applicability and legal effect, most of which
are keyed to and codified in the Code of
Federal Regulations, which is published under
50 titles pursuant to 44 U.S.C. 1510.
The Code of Federal Regulations is sold by
the Superintendent of Documents. Prices of
new books are listed in the first FEDERAL
REGISTER issue of each week.
DEPARTMENT OF ENERGY
10 CFR Part 431
[Docket No. EERE–2010–BT–TP–0036]
RIN 1904–AC38
Energy Conservation Program: Test
Procedure for Automatic Commercial
Ice Makers
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
On April 4, 2011, the U.S.
Department of Energy (DOE or the
Department) issued a notice of proposed
rulemaking (NOPR) to amend the test
procedure for automatic commercial ice
makers (ACIM). That NOPR serves as
the basis for today’s action. This final
rule amends the current test procedure
for automatic commercial ice makers.
The changes include updating the
incorporation by reference of industry
test procedures to the most current
published versions, expanding coverage
of the test procedure to all batch type
and continuous type ice makers with
capacities between 50 and 4,000 pounds
of ice per 24 hours, standardizing test
results based on ice hardness for
continuous type ice makers, clarifying
the test methods and reporting
requirements for automatic ice makers
designed to be connected to a remote
compressor rack, and discontinuing the
use of a clarified energy use equation.
DATES: The effective date of this rule is
February 10, 2012. The final rule
changes will be mandatory for
equipment testing starting January 7,
2013. Representations either in writing
or in any broadcast advertisement
respecting energy consumption of
automatic commercial ice makers must
also be made using the revised DOE test
procedure on January 7, 2013.
pmangrum on DSK3VPTVN1PROD with RULES
SUMMARY:
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
The incorporation by reference of
certain publications listed in this final
rule is approved by the Director of the
Office of the Federal Register as of
February 10, 2012.
ADDRESSES: The docket is available for
review at regulations.gov, including
Federal Register notices, public meeting
attendee lists and transcripts,
comments, and other supporting
documents/materials. All documents in
the docket are listed in the regulations.
gov index. However, not all documents
listed in the index may be publicly
available, such as information that is
exempt from public disclosure.
A link to the docket Web page can be
found at: https://www1.eere.energy.gov/
buildings/appliance_standards/
commercial/automatic_ice_making_
equipment.html. This Web page will
contain a link to the docket for this
notice on the regulations.gov site. The
regulations.gov Web page will contain
simple instructions on how to access all
documents, including public comments,
in the docket. For further information
on how to review the docket, contact
Ms. Brenda Edwards at (202) 586–2945
or by email: Brenda.Edwards@ee.doe.
gov.
FOR FURTHER INFORMATION CONTACT: Mr.
Charles Llenza, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Program, EE–2J, 1000
Independence Avenue SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–2192. Email:
Charles.Llenza@ee.doe.gov.
Mr. Ari Altman, U.S. Department of
Energy, Office of the General Counsel,
GC–71, 1000 Independence Avenue
SW., Washington, DC 20585–0121.
Telephone: (202) 287–6307. Email: Ari.
Altman@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final
rule incorporates by reference into Part
431 the following industry standards:
(1) Air Conditioning, Heating, and
Refrigeration Institute (AHRI) Standard
810–2007 with Addendum 1,
‘‘Performance Rating of Automatic
Commercial Ice-Makers,’’ March 2011;
and
(2) American National Standards
Institute (ANSI)/American Society of
Heating, Refrigerating and AirConditioning Engineers (ASHRAE)
Standard 29–2009, ‘‘Method of Testing
Automatic Ice Makers,’’ (including
Errata Sheets 1 and 2, issued April 8,
PO 00000
Frm 00001
Fmt 4700
Sfmt 4700
2010 and April 12, 2011), approved
January 28, 2009.
Copies of AHRI standards can be
obtained from the Air-Conditioning,
Heating, and Refrigeration Institute,
2111 Wilson Blvd., Suite 500, Arlington,
VA 22201, (703) 524–8800, ahri@
ahrinet.org, or https://www.ahrinet.org.
Copies of ASHRAE standards can be
purchased from the American Society of
Heating, Refrigerating and AirConditioning Engineers, Inc., 1791
Tullie Circle NE., Atlanta, GA 30329,
(404) 636–8400, ashrae@ashrae.org, or
https://www.ashrae.org.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Summary of the Final Rule
III. Discussion
A. Amendments to the Test Procedure
1. Update References to Industry Standards
to Most Current Versions
2. Expand Capacity Range to Larger
Capacity Equipment
3. Include Test Methods for Continuous
Type Ice Makers
a. Definitions and Referenced Industry Test
Methods
b. Standardize Ice Hardness for Continuous
Type Ice Makers
c. Ice Hardness Versus Ice Quality
d. Sub-Cooled Ice
e. Ice Hardness Testing of Batch Type Ice
Makers
f. Variability of the Ice Hardness
Measurement
g. Perforated Containers for Continuous
Type Ice Makers
4. Clarify the Test Method and Reporting
Requirements for Remote Condensing
Automatic Commercial Ice Makers
5. Discontinue Use of a Clarified Energy
Rate Calculation
6. Test Procedure Compliance Date
B. Notice of Proposed Rulemaking
Comment Summary and DOE Responses
1. Test Method for Modulating Capacity
Automatic Commercial Ice Makers
2. Treatment of Tube Type Ice Machines
3. Quantification of Auxiliary Energy Use
4. Measurement of Storage Bin
Effectiveness
5. Establishment of a Metric for Potable
Water Used to Produce Ice
6. Standardization of Water Hardness for
Measurement of Potable Water Used in
Making Ice
7. Testing of Batch Type Ice Makers at the
Highest Purge Setting
8. Consideration of Space Conditioning
Loads
9. Burden Due to Cost of Testing
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
E:\FR\FM\11JAR1.SGM
11JAR1
1592
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
V. Approval of the Office of the Secretary
pmangrum on DSK3VPTVN1PROD with RULES
I. Authority and Background
A. Authority
Title III of the Energy Policy and
Conservation Act (42 U.S.C. 6291, et
seq.; ‘‘EPCA’’) sets forth a variety of
provisions designed to improve energy
efficiency. (All references to EPCA refer
to the statute as amended through the
Energy Independence and Security Act
of 2007 (EISA 2007), Public Law 110–
140 (Dec. 19, 2007)). Part C of Title III,
which was subsequently redesignated as
Part A–1 in the U.S. Code for editorial
reasons (42 U.S.C. 6311–6317),
establishes an energy conservation
program for certain industrial
equipment. This includes automatic
commercial ice makers, the subject of
today’s rulemaking.
DOE’s energy conservation program,
established under EPCA, consists
essentially of four parts: (1) Testing; (2)
labeling; (3) Federal energy conservation
standards; and (4) certification and
enforcement procedures. The testing
requirements consist of test procedures
that manufacturers of covered
equipment must use (1) as the basis for
certifying to DOE that their equipment
complies with the applicable energy
conservation standards adopted under
EPCA; and (2) for making
representations about the efficiency of
those pieces of equipment. Similarly,
DOE must use these test requirements to
determine whether the equipment
complies with relevant standards
promulgated under EPCA. (42 U.S.C.
6315(b), 6295(s), and 6316(a)) The
current test procedure for automatic
commercial ice makers appears under
title 10 of the Code of Federal
Regulations (CFR) part 431, subpart H.
EPCA prescribes that the test
procedure for automatic commercial ice
makers shall be the Air-Conditioning
and Refrigeration Institute (ARI)
Standard 810–2003, ‘‘Performance
Rating of Automatic Commercial Ice-
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
Makers.’’ (42 U.S.C. 6314(a)(7)(A)) EPCA
also provides that if ARI Standard 810–
2003 is revised, the Secretary of Energy
(Secretary) shall amend the DOE test
procedure as necessary to be consistent
with the amended ARI Standard unless
the Secretary determines, by rule, that to
do so would not meet the requirements
for test procedures set forth in EPCA.
(42 U.S.C. 6314(a)(7)(B)) Because ARI
Standard 810 has been updated from the
2003 version, DOE must amend the DOE
test procedure to reflect these updates,
unless doing so would not meet the
requirements for a test procedure, as set
forth in EPCA. (42 U.S.C.
6314(a)(7)(B)(i))
In addition, EPCA prescribes energy
conservation standards for automatic
commercial ice makers that produce
cube type ice with capacities between
50 and 2,500 pounds of ice per 24-hour
period. (42 U.S.C. 6313(d)(1)) EPCA also
requires the Secretary to review these
standards and determine, by January 1,
2015, whether amending the applicable
standards is technically feasible and
economically justified. (42 U.S.C.
6313(d)(3)) DOE is currently
undertaking a standards rulemaking
(Docket No. EERE–2010–BT–STD–
0037), concurrent with this test
procedure rulemaking, to determine if
amended standards are technically
feasible and economically justified for
automatic commercial ice makers
covered by the standards set in the
Energy Policy Act of 2005 (EPACT
2005). In the energy conservation
standards rulemaking, DOE is also
proposing, under 42 U.S.C. 6313(d)(2),
to adopt standards for other types of ice
makers that are not covered in 42 U.S.C.
6313(d)(1) and to expand the covered
capacity range to ice makers with
capacities up to 4,000 pounds of ice per
24 hours. In this final rule, DOE is
amending the test procedure for
automatic commercial ice makers to be
consistent with the expanded scope
being considered in the ACIM energy
conservation standards rulemaking.
In addition, EPCA requires DOE to
conduct an evaluation of each class of
covered equipment at least once every
7 years to determine whether, among
other things, to amend the test
procedure for such equipment. (42
U.S.C. 6314(a)(1)(A)) The review and
amendment of the test procedure for
automatic commercial ice makers in this
final rule notice fulfills DOE’s obligation
under EPCA to evaluate the test
procedure for automatic commercial ice
makers every 7 years. EPCA also
requires that if DOE determines that a
test procedure amendment is warranted,
it must publish proposed test
procedures and offer the public an
PO 00000
Frm 00002
Fmt 4700
Sfmt 4700
opportunity to present oral and written
comments on them. (42 U.S.C. 6314(b))
B. Background
EPCA, as amended by EPACT 2005,
prescribes that the test procedure for
automatic commercial ice makers shall
be the ARI Standard 810–2003,
‘‘Performance Rating of Automatic
Commercial Ice-Makers.’’ (42 U.S.C.
6314(a)(7)(A)) Pursuant to EPCA, on
December 8, 2006, DOE published a
final rule (the 2006 en masse final rule)
that, among other things, adopted the
test procedure specified in ARI
Standard 810–2003, with a revised
method for calculating energy use. DOE
adopted a clarified energy use rate
equation to specify that the energy use
be calculated using the entire mass of
ice produced during the testing period,
normalized to 100 pounds of ice
produced. 71 FR 71340, 71350 (Dec. 8,
2006). The DOE test procedure also
incorporated by reference the ANSI/
ASHRAE Standard 29–1988 (Reaffirmed
2005) (ASHRAE Standard 29–1988 (RA
2005)), ‘‘Method of Testing Automatic
Ice Makers,’’ as the method of test.
Since the publication of the 2006 en
masse final rule, ARI merged with the
Gas Appliance Manufacturers
Association (GAMA) to form the AirConditioning, Heating, and Refrigeration
Institute (AHRI) and updated its ice
maker test procedure to reflect changes
in the industry. The new test procedure,
AHRI Standard 810–2007, amends the
previous test procedure, ARI Standard
810–2003, to:
1. Expand the capacity range of
covered equipment to between 50 and
4,000 pounds of ice per 24 hours at
standard rating conditions;
2. Provide definitions and specific test
procedures for batch type and
continuous type ice makers; and
3. Provide a definition for ice
hardness factor, which is the fraction of
frozen ice in the ice product of
continuous type ice machines.
The industry test procedure being
considered in this rulemaking, AHRI
Standard 810–2007, references the
previous ANSI/ASHRAE Standard 29–
1988 (RA 2005). The current DOE test
procedure also references ANSI/
ASHRAE Standard 29–1988 (RA 2005).
However, ASHRAE updated its test
procedure in 2009 to ANSI/ASHRAE
Standard 29–2009 to include provisions
for measuring the performance of batch
type and continuous type ice makers.1
1 ASHRAE has also issued two errata sheets to
ANSI/ASHRAE Standard 29–2009, issued April 8,
2010 and April 12, 2010, respectively. These errata
serve only to clarify equations that are part of the
ice hardness calculation described in normative
annex A, Table A1; they do not change the content
E:\FR\FM\11JAR1.SGM
11JAR1
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
pmangrum on DSK3VPTVN1PROD with RULES
In March 2011, AHRI published an
addendum to AHRI Standard 810–2007,
AHRI Standard 810 with Addendum 1.
This addendum revised the definition of
‘‘potable water use rate’’ and added new
definitions of ‘‘purge or dump water’’
and ‘‘harvest water’’ that more
accurately describe the water
consumption of automatic commercial
ice makers. This change only affects
measurement of the potable water use of
automatic commercial ice makers.
Because the amended DOE test
procedure adopted in this final rule
does not require the measurement of
potable water, this change does not
impact the DOE test procedure for
automatic commercial ice makers.
EPCA requires that if DOE determines
that a test procedure amendment is
warranted, DOE must publish proposed
test procedures and offer the public an
opportunity to present oral and written
comments on them. (42 U.S.C. 6314(b))
In accordance with this requirement,
DOE published the proposed test
procedure amendments in the ACIM test
procedure NOPR, which was published
in the Federal Register on April 4, 2011.
76 FR 18428 (April 2011 NOPR). On
April 29, 2011, DOE held a public
meeting (April 2011 NOPR public
meeting) to discuss the amendments
proposed in the April 2011 NOPR and
provide an opportunity for interested
parties to comment. DOE also received
written comments from interested
parties regarding the proposed
amendments to the test procedure for
automatic commercial ice makers and
has considered both the oral comments
received at the public meeting and the
written comments, to the extent
possible, when finalizing this final rule.
These comments and DOE’s responses
are presented in section III, Discussion.
II. Summary of the Final Rule
This final rule amends the existing
test procedure for automatic commercial
ice makers. Specifically, DOE is
incorporating revisions to the DOE test
procedure that:
1. Update the industry test procedure
references to AHRI Standard 810–2007
with Addendum 1 and ANSI/ASHRAE
Standard 29–2009;
2. Expand the scope of the test
procedure to include equipment with
capacities from 50 to 4,000 pounds of
ice per 24 hours;
3. Provide test methods for
continuous type ice makers and
standardize the measurement of energy
or results of the test procedure. In this document,
all subsequent references to ‘‘ANSI/ASHRAE
Standard 29–2009’’ will refer to ANSI/ASHRAE
Standard 29–2009, including all errata presented in
Errata Sheets 1 and 2.
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
and water use for continuous type ice
makers with respect to ice hardness;
4. Clarify the test method and
reporting requirements for remote
condensing automatic commercial ice
makers designed for connection to
remote compressor racks; and
5. Discontinue the use of a clarified
energy use rate calculation and instead
calculate energy use per 100 pounds of
ice as specified in ANSI/ASHRAE
Standard 29–2009.
These amendments make changes to
the definitions set forth in 10 CFR
431.132 and to the current test
procedures in 10 CFR 431.134.
The amended test procedure
established in today’s final rule will
become effective 30 days after
publication in the Federal Register.
DOE believes the test procedure
amendments adopted in today’s final
rule will not alter the measured energy
consumption and condenser water
consumption of any covered equipment.
As such, for automatic commercial ice
makers for which energy conservation
standards were set in EPACT 2005, use
of the revised test procedure for
showing compliance with DOE’s energy
conservation standards will be required
starting 360 days after publication in the
Federal Register. For equipment not
covered by the standards set forth in
EPACT 2005, use of the amended test
procedure to show compliance with
energy conservation standards will be
required on the compliance date of any
energy conservation standards
established for that equipment.
Consistent with EPCA, representations
either in writing or in any broadcast
advertisement respecting energy
consumption of any automatic
commercial ice makers covered under
this test procedure final rule will be
required to be made based on the
amended test procedure starting 360
days after publication of this final rule
in the Federal Register. (42 U.S.C.
6314(d)(1)) For more specific
information on DOE’s conclusion that
the amended test procedure will not
affect the measured energy or water
consumption of covered equipment and
further discussion of compliance dates,
see the DATES section and section III.A.6
of this document.
III. Discussion
Section III.A discusses all the
revisions to the test procedure
incorporated in this final rule and
discusses the test procedure compliance
date. This section also presents the
comments received on these topics
during the April 2011 NOPR public
meeting and in the associated comment
period and DOE’s responses to them.
PO 00000
Frm 00003
Fmt 4700
Sfmt 4700
1593
Responses to comments addressing
topics other than test procedure
revisions adopted in this final rule
appear in section III.B, which provides
responses to comments in the following
subject areas:
1. Test Method for Modulating Capacity
Automatic Commercial Ice Makers
2. Treatment of Tube Type Ice Machines
3. Quantification of Auxiliary Energy
Use
4. Measurement of Storage Bin
Effectiveness
5. Establishment of a Metric for Potable
Water Used in Making Ice
6. Standardization of Water Hardness
for Measurement of Potable Water
Used in Making Ice
7. Testing of Batch Type Ice Makers at
the Highest Purge Setting
8. Consideration of Space Conditioning
Loads
9. Burden Due to Cost of Testing
A. Amendments to the Test Procedure
Today’s final rule contains the
following amendments to the test
procedure in 10 CFR 431, subpart H.
1. Update References to Industry
Standards to Most Current Versions
The current DOE test procedure for
automatic commercial ice makers,
established in the 2006 en masse final
rule, adopts ARI Standard 810–2003 as
the test procedure used to measure the
energy consumption of a piece of
equipment to establish compliance with
energy conservation standards set in
EPACT 2005. 71 FR at 71350 (Dec. 8,
2006). The DOE test procedure also
references ANSI/ASHRAE Standard 29–
1988 (RA 2005).
Since publication of the 2006 en
masse final rule, AHRI and ASHRAE
have published revised standards,
namely AHRI Standard 810–2007 with
Addendum 1 and ANSI/ASHRAE
Standard 29–2009 (including Errata
Sheets 1 and 2). AHRI Standard 810–
2007 with Addendum 1 and ANSI/
ASHRAE Standard 29–2009 amend the
previous test procedures by expanding
the capacity range to 4,000 pounds per
day and providing for the testing of
continuous type ice makers. AHRI
Standard 810–2007 with Addendum 1
and ANSI/ASHRAE Standard 29–2009
are designed to be used together to test
automatic commercial ice makers. AHRI
Standard 810–2007 with Addendum 1
specifies the standard rating conditions
and provides relevant definitions of
equipment, scope, and calculated or
measured values. ANSI/ASHRAE
Standard 29 specifies how to conduct
the test procedure, including the
technical requirements and calculations.
E:\FR\FM\11JAR1.SGM
11JAR1
1594
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
pmangrum on DSK3VPTVN1PROD with RULES
In the April 2011 NOPR, DOE
proposed to adopt AHRI Standard 810–
2007 and ANSI/ASHRAE Standard 29–
2009 as the DOE test procedure. 76 FR
at 18431 (April 4, 2011). AHRI Standard
810–2007 with Addendum 1 was not
published in time for DOE to include it
in the NOPR. At the April 2011 NOPR
public meeting and in subsequent
written comments, AHRI, Manitowoc
Ice (Manitowoc), Scotsman Industries
(Scotsman), Follett Corporation (Follett),
and the Northwest Energy Efficiency
Alliance (NEEA) supported this
proposal (AHRI, No. 0005 at p. 23;
Manitowoc, No. 0009 at p. 1; Scotsman,
No. 0010 at p. 1; Follett, No. 0008 at p.
1; NEEA, No. 0013 at p. 2) 2 Pacific Gas
& Electric, Southern California Edison,
San Diego Gas and Electric, and
Southern California Gas Company,
hereafter referred to as the California
Investor Owned Utilities (CA IOUs),
submitted a joint comment that also
supported adopting AHRI Standard
810–2007 and ASHRAE Standard 29–
2009. (CA IOUs, No. 0011 at pp. 1–2)
AHRI also recommended that DOE
adopt AHRI standard 810–2007 with
Addendum 1, pointing out that the
addendum was added in March 2011
and has new definitions for ‘‘dump and
purge water’’ and ‘‘harvest water.’’ AHRI
added that the addendum also clarifies
how potable water usage rate is
calculated. (AHRI, No. 0015 at p. 1) DOE
did not receive any dissenting
comments generally regarding reference
to the updated industry standards, nor
regarding AHRI Standard 810–2007
with Addendum 1.
DOE reviewed AHRI 810–2007 with
Addendum 1 and determined that this
revised version of the AHRI Standard
810–2007 test procedure meets the
EPCA requirements for a test procedure
in that it is reasonably designed to
produce test results that reflect the
energy use of covered equipment during
a representative cycle of use and is not
unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
DOE believes AHRI Standard 810–
2007 with Addendum 1 and ANSI/
ASHRAE Standard 29–2009 are the
most up-to-date and commonly used
test procedures for automatic
commercial ice makers in the industry
and are the most appropriate to cover all
equipment included in the scope of this
2 In the following discussion, comments will be
presented along with a notation in the form ‘‘AHRI,
No. 0005 at p. 23,’’ which identifies a written
comment DOE received and included in the docket
of this rulemaking. DOE refers to comments based
on when the comment was submitted in the
rulemaking process. This particular notation refers
to a comment (1) By AHRI, (2) in document number
0005 of the docket (available at regulations.gov),
and (3) appearing on page 23.
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
rulemaking. Thus, in today’s final rule,
DOE is updating the DOE test procedure
for automatic commercial ice makers to
reference the most current versions of
the industry test procedures, AHRI
Standard 810–2007 with Addendum 1
and ANSI/ASHRAE Standard 29–2009.
2. Expand Capacity Range to Larger
Capacity Equipment
DOE’s existing test procedure
references ARI Standard 810–2003,
which limits the testing provisions to a
capacity range of 50 to 2,500 pounds of
ice per 24 hours. In AHRI Standard 810–
2007, AHRI expanded the capacity
range to include automatic commercial
ice makers having a harvest capacity
between 50 and 4,000 pounds of ice per
24 hours at standard rating conditions
due to changes in the products offered
by manufacturers. Specifically, some
manufacturers offer larger capacity units
that exceed the capacity range of the
previous test procedure. AHRI’s
expansion of the capacity range does not
affect the way ice makers are tested; it
only provides for the same test
procedure to be applied to larger
capacity ice makers.
Consistent with referenced industry
test procedures, DOE proposed in the
April 2011 NOPR to expand the
capacity range of the DOE test
procedure to include automatic
commercial ice makers with harvest
rates between 50 and 4,000 pounds of
ice per 24 hours. 76 FR at 18431 (April
4, 2011). In response to this proposal,
Manitowoc, AHRI, Follett, Scotsman,
the CA IOUs, and NEEA commented
that 50 to 4,000 pounds per day was an
appropriate capacity range for this
equipment. (Manitowoc, No. 0009 at p.
1; AHRI, No. 0005; Follett, No. 0008 at
p. 1; Scotsman, No. 0010 at p. 1; CA
IOUs, No. 0011 at pp. 1–2; NEEA, No.
0013 at p. 1) Manitowoc further
commented that there are some
industrial applications of ice makers, at
airports or other venues with very high
ice consumption, but that larger
capacity industrial-scale equipment was
already inherently more efficient.
(Manitowoc, No. 0005 at p. 26) NEEA
commented that it is inclined to agree
that equipment with capacities greater
than 4,000 pounds of ice per day need
not be included in the scope of coverage
because, while these types of machines
can probably be rated using the test
procedure, environmental chamber
issues would impose a potentially
significant burden on manufacturers
who are not so equipped. NEEA also
agreed with Manitowoc that machines
of capacities greater than 4,000 pounds
per day are inherently at least a little
more energy efficient per pound of ice
PO 00000
Frm 00004
Fmt 4700
Sfmt 4700
produced than similar smaller
machines. (NEEA, No. 0013 at pp. 1–2)
AHRI added that ice makers producing
more than 4000 pounds of ice per 24
hours are usually used in industrial
applications that are outside the scope
of this rulemaking, as justified by the
EPACT 2005, which gives DOE the
authority to develop energy
conservation standards for automatic
commercial ice makers only. (AHRI, No.
0015 at p. 2)
DOE agrees with commenters that
4,000 pounds of ice produced per a 24
hour period is a reasonable maximum
capacity limit for automatic commercial
ice makers. Consequently, DOE is
establishing in this final rule the
applicable capacity range of the test
procedure for automatic commercial ice
makers as the same capacity range
established in AHRI 810–2007 with
Addendum 1, namely 50 to 4,000
pounds of ice per 24 hours.
3. Include Test Methods for Continuous
Type Ice Makers
In the April 2011 NOPR, DOE
proposed including test methods as
defined in AHRI Standard 810–2007
and ANSI/ASHRAE Standard 29–2009
for continuous type ice makers, as well
as an additional method to scale their
energy consumption and water
consumption with respect to the latent
heat capacity contained in the ice
compared to the latent heat capacity of
the same mass of completely frozen ice.
76 FR at 18432 (April 4, 2011). The
following sections discuss DOE’s
specific proposals, comments submitted
by interested parties on these proposals,
DOE’s responses, and the amendments
DOE is adopting in today’s final rule.
a. Definitions and Referenced Industry
Test Methods
AHRI Standard 810–2007 with
Addendum 1 and ANSI/ASHRAE
Standard 29–2009 have provisions that
allow for the testing of continuous type
ice makers. The previous versions of
these standards, ARI Standard 810–2003
and ANSI/ASHRAE Standard 29–1988
(RA 2005), as referenced in the current
DOE test procedure, do not include a
method for testing continuous type ice
makers. The revised ANSI/ASHRAE
Standard 29–2009 adopts definitions for
a ‘‘continuous type ice maker’’ and a
‘‘batch type ice maker.’’ A continuous
type ice maker is defined as an ice
maker that continually freezes and
harvests ice at the same time.
Continuous type ice makers primarily
produce flake and nugget ice. A batch
type ice maker is defined as an ice
maker that has alternate freezing and
harvesting periods, including machines
E:\FR\FM\11JAR1.SGM
11JAR1
pmangrum on DSK3VPTVN1PROD with RULES
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
that produce cube type ice, tube type
ice, and fragmented ice. AHRI Standard
810–2007 with Addendum 1 adopts the
same definition for a continuous type
ice maker, but refers to ice makers that
have alternate freezing and harvesting
periods as ‘‘cube type ice makers.’’ The
AHRI Standard 810–2007 definition
further clarifies that in this definition
the word ‘‘cube’’ does not refer to the
specific shape or size of ice produced.
Because of this, ANSI/ASHRAE
Standard 29–2009 includes the
statement that batch type ice makers are
also referred to as cube type ice makers.
In the April 2011 NOPR, DOE
proposed to refer to an ice maker with
alternate freezing and harvesting
periods as a ‘‘batch type ice maker,’’ so
that it is not confused with an ice maker
that produces only cube type ice. DOE
believes that referring to this type of ice
maker as a ‘‘cube type ice maker’’ could
be confusing, since not all batch type ice
makers produce ice that fits the ‘‘cube
type ice’’ definition established in the
2006 en masse final rule. 71 FR at 71372
(Dec. 8, 2006). Rather, batch type ice
makers include, but are not limited to,
cube type ice makers. DOE wishes to
establish this differentiation because ice
makers that produce cube type ice with
capacities between 50 and 2,500 pounds
of ice per 24 hours are currently covered
by energy conservation standards that
are established in EPCA, while batch
type ice makers that produce other than
cube type ice and cube type ice makers
with capacities between 2,500 and 4,000
pounds of ice per 24 hours are not
currently covered by DOE energy
conservation standards. In the April
2011 NOPR (76 FR at 18444 (April 4,
2011)), DOE proposed adding
definitions to 10 CFR 431.132 for ‘‘batch
type ice maker,’’ which would refer to
ice makers that alternate freezing and
harvesting periods, and ‘‘continuous
type ice maker, ’’ which would refer to
ice makers that continuously freeze and
harvest at the same time.
In addition to these definitions, DOE
proposed to adopt AHRI Standard 810–
2007 as the referenced DOE test
procedure, including referencing ANSI/
ASHRAE Standard 29–2009 as the
method of test. 76 FR at 18432 (April 4,
2011). This would expand the current
DOE test procedure to provide a method
for testing continuous type ice makers,
in addition to batch type ice makers.
At the April 2011 NOPR public
meeting and in written comments, both
energy efficiency advocates and
manufacturers agreed that continuous
type ice makers should be included in
the standards. (Follett, No. 0008 at p. 1;
Manitowoc, No. 0009 at p. 1; Scotsman,
No. 0010 at p. 1; CA IOUs, No. 0011 at
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
pp. 1–2; NEEA, No. 0013 at p. 1) The
CA IOUs and Manitowoc added that the
coverage of continuous type equipment
is important because continuous type
machines represent up to 20 percent of
the total market based on energy use
today and continue to grow in market
share; thus, establishing a test procedure
in this rulemaking and corresponding
energy conservation standards for these
equipment types would ensure that
significant energy savings are captured.
(CA IOUs, No. 0011 at p. 2; Manitowoc,
No. 0009 at p. 1)
DOE agrees with commenters that it is
logical and appropriate to include test
procedures for continuous type ice
makers in this test procedure revision.
In today’s final rule, DOE is adopting
definitions and test procedures for batch
type and continuous type ice makers.
The test procedure for testing
continuous type ice makers will be used
in conjunction with any potential
energy conservation standards for
automatic commercial ice makers that
produce flake or nugget ice.
To remove any uncertainty regarding
the current applicability of standards for
ice makers that produce cube type ice
with capacities between 50 and 2,500
pounds per 24 hours, DOE is slightly
modifying the proposed definition for
batch type ice makers, as well as adding
language to the definition for cube type
ice and scope in the final rule.
Specifically, DOE is removing the
clarification of AHRI’s definition of
cube type ice maker in the definition of
batch type ice maker, specifying that
where there is inconsistency between
AHRI and DOE’s definitions of cube
type ice, the DOE definition takes
precedence, and noting that all
references to cube type ice makers in
AHRI Standard 810–2007 shall apply to
all batch type automatic commercial ice
makers only. DOE believes this removes,
to the extent possible, any potential
ambiguity regarding the nomenclature
and coverage of batch type ice makers
that produce cube type ice and batch
type ice makers that produce other than
cube type ice (such as fragmented ice
makers) in the DOE test procedure. DOE
is also updating the definition for
continuous type ice makers to be
consistent with that adopted in AHRI
Standard 810–2007 with Addendum 1
and ANSI/ASHRAE Standard 29–2009.
b. Standardize Ice Hardness for
Continuous Type Ice Makers
Continuous type ice makers typically
produce ice that is not completely
frozen. This means that there is some
liquid water content in the total mass of
ice product produced by continuous
type ice makers. The specific liquid
PO 00000
Frm 00005
Fmt 4700
Sfmt 4700
1595
water content can be described in terms
of ice hardness or ice quality and is
usually quantified in terms of percent of
completely frozen ice in the total ice
product. Ice quality can vary
significantly across different continuous
ice makers, from less than 70 percent to
more than 100 percent. DOE
understands that the percentage of
liquid water in the product of
continuous ice makers is directly related
to the measured energy consumption of
these machines, since more refrigeration
is required to freeze a greater percentage
of the ice product.
To provide comparability and
repeatability of results, in the April
2011 NOPR, DOE proposed to
standardize the energy consumption
and condenser water use measurements
of continuous ice makers based on the
ratio of enthalpy reduction of the water/
ice product achieved in the machine
(incoming water enthalpy less ice
product enthalpy) to the enthalpy
reduction that would be achieved if the
ice were produced at 32 °F with no
liquid water content. DOE proposed to
base the adjustment on the ice quality
of continuous type ice makers, as
measured using the ‘‘Procedure for
Determining Ice Quality’’ in section A.3
of normative annex A in ANSI/ASHRAE
Standard 29–2009. DOE proposed that
the calorimeter constant, defined and
measured using ANSI/ASHRAE
Standard 29–2009, be used to calculate
an ‘‘ice quality adjustment factor.’’ This
factor is a ratio of the refrigeration
required to cool water from 70 °F to 32
°F and freeze all of the water compared
to the refrigeration required to cool 70
°F water to the mixture of frozen ice and
liquid water produced by the ice maker
under test. The reported (adjusted)
energy consumption would be equal to
the ice quality adjustment factor
multiplied by the energy consumption
per 100 pounds of ice measured using
ANSI/ASHRAE Standard 29–2009. The
condenser water use would be adjusted
in the same way. 76 FR at 18432–33
(April 4, 2011). DOE did not propose
similar adjustment for the harvest rate.
Interested parties, including
Manitowoc, Howe Corporation (Howe),
and NEEA, generally supported this
approach. (Manitowoc, No. 0005 at p.
41; Howe, No. 0017 at pp. 2–3; NEEA,
No. 0013 at p. 2) However, Scotsman
commented that normalization of energy
and water consumption with respect to
ice hardness could result in selection of
higher energy consumption products by
the consumer because when a consumer
fills a glass or cooler with ice, they do
so based on the volume of space the ice
occupies, not the cooling power it
provides. Scotsman added that, in rating
E:\FR\FM\11JAR1.SGM
11JAR1
1596
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
pmangrum on DSK3VPTVN1PROD with RULES
ice machines based on the total weight
of the product of ice and water rather
than just the ice content, the consumer
gets a more accurate measurement of the
amount of energy consumed to produce
the nugget of ice that is in the cup or
cooler, while ‘‘normalizing’’ to 32 °F ice
with no water content gives a more
accurate measure of the energy used to
produce a certain amount of cooling
power contained in the ice, but is not
representative of how the ice is typically
used. (Scotsman, No. 0010 at p. 1)
Scotsman also asked if DOE intended to
require ice hardness reporting.
(Scotsman, No. 0010 at p. 1)
DOE maintains that, because energy
and condenser water consumption are
directly related to ice hardness,
measurement and normalization with
respect to ice hardness is necessary to
compare equipment from different
manufacturers accurately. In response to
Scotsman’s concern, DOE notes that this
test method will not affect the
availability of automatic commercial ice
makers that produce lower quality ice;
it will simply provide a method by
which automatic commercial ice maker
energy consumption and condenser
water use results can be compared to a
baseline ice quality. DOE acknowledges
that, if consumers value total pounds of
ice rather than the cooling that can be
provided by the ice, the unadjusted
energy and water consumption data may
provide a better indication of the energy
use per quantity valued by the
customer. However, DOE believes that
scaling energy and water consumption
with respect to ice quality will result in
more comparable values for determining
compliance with DOE’s energy
conservation standards. The harvest rate
of these ice makers will not be adjusted
with respect to ice hardness. In
addition, DOE is not considering
changes to the certification
requirements in this test procedure
rulemaking. Thus, in this final rule,
DOE is adopting the provisions
proposed in the April 2011 NOPR to
scale the energy and water consumption
measured in ANSI/ASHRAE Standard
29–2009 based on a ratio of the
refrigeration required to cool water from
70 °F to 32 °F and freeze all of the water
compared to the refrigeration required
to cool 70 °F water to the mixture of
frozen ice and liquid water produced by
the ice maker under test.
c. Ice Hardness Versus Ice Quality
As discussed above, DOE in the April
2011 NOPR proposed that the
calorimeter constant, determined using
ANSI/ASHRAE Standard 29–2009, be
used to determine an ‘‘ice quality
adjustment factor.’’ 76 FR at 18433
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
(April 4, 2011). Scotsman, Manitowoc,
and Hoshizaki all commented that the
term ‘‘ice quality’’ should instead be
referred to as ‘‘ice hardness,’’ as defined
in AHRI Standard 810–2007. (Scotsman,
No. 0005 at p. 38; Manitowoc, No. 0005
at p. 40; Hoshizaki, No. 0005 at pp. 44–
45) Howe countered that ‘‘ice
hardness,’’ as defined in the AHRI
standard, should not be used to replace
the proposed ‘‘ice quality’’ used in the
ASHRAE standard because the term ‘‘ice
hardness’’ is confusing and is a
misstatement. (Howe, No. 0017 at p. 8)
In response to comments from
interested parties, DOE is using the term
‘‘ice hardness’’ in place of the term ‘‘ice
quality’’ throughout this rule, since it is
defined in AHRI Standard 810–2007
and seems to be the preferred term
within the industry. Specifically, DOE is
defining the ‘‘ice hardness adjustment
factor,’’ as opposed to the previously
defined ‘‘ice quality adjustment factor,’’
which will be calculated in order to
scale energy consumption and
condenser water use. DOE
acknowledges Howe’s comment that
this may cause confusion, but contends
that the terms ‘‘ice hardness’’ and ‘‘ice
quality’’ are used interchangeably in the
industry, and understands the two terms
to have the same meaning.
d. Sub-Cooled Ice
Just as ice makers that produce less
than 100 percent hardness ice will use
less energy than ice makers that produce
100 percent 32 °F ice, ice makers that
produce sub-cooled ice, or higher than
100 percent hardness ice, require more
energy to produce a given mass of ice
product. At the April 2011 NOPR public
meeting and in subsequent written
comments, Manitowoc, Howe, and
NEEA all commented that the
adjustment of energy and water
consumption with respect to ice
hardness should be allowed for subcooled ice as well as low hardness ice.
(Manitowoc, No. 0005 at p. 42; Howe,
No. 0005 at pp. 45–46; NEEA, No. 0013
at p. 2)
DOE agrees with interested parties
that the energy content of sub-cooled ice
should also be adjusted with respect to
32 °F ice of 100 percent hardness.
However, DOE notes that the
measurement of ice hardness is not
limited to low hardness ice and that
quantification of the ice hardness for
sub-cooled ice is possible using the
adopted procedure for ice hardness
normalization. Rather, the adopted test
procedure already accounts for the
additional cooling associated with
production of sub-cooled ice. DOE
clarifies that ice hardness testing of ice
makers that produce sub-cooled ice can
PO 00000
Frm 00006
Fmt 4700
Sfmt 4700
be conducted using the ice hardness test
procedure adopted in today’s final rule
and that the energy use and condenser
water use measurements for ice makers
that produce sub-cooled ice can and
should be adjusted using the ice
hardness adjustment factor.
e. Ice Hardness Testing of Batch Type
Ice Makers
AHRI Standard 810–2007 with
Addendum 1 and ANSI/ASHRAE
Standard 29–2009 both specify that ice
hardness testing is only to be performed
for continuous type ice makers. In the
April 2011 NOPR, DOE also proposed
that measurement and scaling of energy
and water consumption values based on
ice hardness only be required for
continuous type ice makers. 76 FR at
18433 (April 4, 2011).
In written comments submitted in
response to the April 2011 NOPR,
Follett recommended that the ice
quality adjustment be applied to batch
type ice makers as well as continuous
type. (Follett, No. 0008 at p. 1)
DOE agrees with Follett that there
would be value in requiring batch
machines to perform the ice hardness
measurement and scale their energy
consumption accordingly. Testing and
normalizing energy and water
consumption values for ice hardness
would account for the additional energy
consumption of batch type commercial
ice makers that produce sub-cooled ice
and would allow for the most consistent
results across all ice makers. In
addition, some batch type automatic
commercial ice makers may produce
cube type ice with some liquid water
content. DOE believes that this would
account for the additional energy
consumption of batch type commercial
ice makers that produce sub-cooled ice
and would allow for the most consistent
results across all ice makers. However,
DOE does not have any data or
information regarding the existence of
batch type ice makers that vary from 100
percent hardness or the extent to which
their hardness departs from 100 percent.
DOE believes that, for most batch type
ice makers, the ice hardness will be
nearly 100 percent and any departure
from 100 percent will be within the
statistical accuracy of the ice hardness
measurement. Lacking sound
information, DOE is unable to justify the
additional burden associated with
requiring ice hardness measurement and
scaling of energy and water
consumption for batch type ice makers
at this time. Thus, in today’s final rule
DOE specifies that only continuous type
ice makers are required to measure ice
hardness and adjust the energy
E:\FR\FM\11JAR1.SGM
11JAR1
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
1597
AHRI Standard 810–2007 with
Addendum 1 specifies that the ice
hardness factor is the latent heat
capacity of ice harvested in British
thermal units per pound (Btu/lb), as
defined in ANSI/ASHRAE Standard 29,
Table A1, line 15, divided by 144 Btu/
lb, multiplied by 100, presented as a
percent. DOE believes that this value
should also be multiplied by the
calorimeter constant, line 18 of Table
A1, as determined in section A2 at the
beginning of that day’s tests. This is
equivalent to line 19 in ANSI/ASHRAE
Standard 29–2009 Table A1, although it
is not clear that the calibration constant
used in line 18 is to be determined with
seasoned block ice during the
calibration procedure. To clarify this
procedure, DOE will require that the ice
hardness factor, as defined in AHRI
Standard 810–2007 with Addendum 1,
be calculated, except that it shall
reference the corrected net cooling effect
per pound of ice, line 19 of ANSI/
ASHRAE Standard 29–2009 Table A1,
and the calorimeter constant used in
line 18 shall be that determined in
section A2 using seasoned, block ice.
The ice hardness factor will be used
to determine an adjustment factor based
on the energy required to cool ice from
70 °F to 32 °F and produce a given
amount of ice, as shown in the
following:
The measured energy consumption
per 100 pounds of ice and the measured
condenser water consumption per 100
pounds of ice, as determined using
ANSI/ASHRAE Standard 29–2009, will
be multiplied by the ice hardness
adjustment factor to yield the adjusted
energy and condenser water
consumption values, respectively. These
values will be reported to DOE to show
compliance with the energy
conservation standard.
DOE explored the variation in both
the calibration procedure and the
procedure for determining an ice
maker’s ice hardness factor in laboratory
testing. DOE hypothesized the following
variables, which could contribute to
variability in the test procedure:
• How to ensure that ice is
‘‘seasoned’’
• Thermal conductivity and specific
heat of bucket
• Frequency and timing of calibration
• Vigorousness of ice stirring
• Location of temperature sensor in
the ice bucket
• Variation in ambient conditions
• Difference between water
temperature and ambient air
temperature
• Time allowed between production
of ice and initiation of ice hardness test
DOE conducted testing to determine
the significance of these variables on the
calorimeter constant result. DOE
believes standardization and tolerances
are important because otherwise there is
no indicator of how close a
measurement must be to the specified
value in order to comply with the test
procedure.
In section A2 of ANSI/ASHRAE
Standard 29–2009, which specifies the
calibration procedure for the
calorimeter, DOE found that the type of
‘‘seasoned’’ ice used significantly
affected the calibration of the device,
but that variation of all other factors
examined did not have a significant
effect provided they were maintained
within a reasonable range. DOE believes
‘‘seasoned’’ ice is ice that is 32 °F
throughout with as little entrained water
as possible. A single block of seasoned
ice is used to minimize the amount of
water on the surface of the ice due to the
low surface area to volume ratio. If
multiple, smaller cubes are used, and
seasoned in the same manner, it is much
more difficult to ensure that the surface
liquid is removed so that a calorimeter
3 Hoffman, M. Personal Communication.
Consortium for and Energy Efficiency, Boston, MA.
Letter to Christopher Kent, U.S. Environmental
Protection Agency, regarding written comments
submitted in response to the ENERGY STAR
Commercial Ice Machines Version 2 Draft 1
Specification, June 11, 2011. https://
www.energystar.gov/ia/partners/
prod_development/revisions/downloads/
commercial_ice_machines/
ACIM_Draft_1_V_2.0_Comments_-_CEE.pdf.
pmangrum on DSK3VPTVN1PROD with RULES
f. Variability of the Ice Hardness
Measurement
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
PO 00000
Frm 00007
Fmt 4700
Sfmt 4700
E:\FR\FM\11JAR1.SGM
11JAR1
ER11JA12.045
DOE is aware of concerns regarding
the accuracy and repeatability of the ice
hardness test. These concerns were
voiced during the U.S. Environmental
Protection Agency (EPA) ENERGY
STAR® discussions with interested
parties regarding revisions to the
ENERGY STAR specification for
automatic commercial ice makers.3 In
written comments received during the
comment period that followed the
publication of the April 2011 NOPR,
Scotsman recommended the tolerance
for the ice hardness factor be ± 5 rather
than ± 5 percent, as test data Scotsman
has indicates that ± 5 percent is too tight
when accounting for water mineral
content, which can have a substantial
impact on ice hardness. (Scotsman, No.
0010 at pp. 2–3)
As part of this rulemaking and the
ongoing energy conservation standards
rulemaking (Docket No. EERE–2010–
BT–STD–0037), DOE conducted testing
of ice makers, including running the ice
hardness tests. In conducting this
testing, DOE wished to better
understand the source of any variability
in ANSI/ASHRAE Standard 29–2009
normative annex A. Specifically, DOE
wished to discern the variability, if any,
in the measurement of ice hardness that
could be attributed specifically to
inaccuracy in the test method, rather
than inherent variability in the hardness
of ice produced by a given ice maker.
DOE determined that the fundamental
test procedure established in ANSI/
ASHRAE Standard 29–2009 is sound.
However, DOE believes that several
areas of the test procedure are unclear
and could be misinterpreted. This
includes confusing nomenclature and
references in normative annex A, as
well as specification of the specific
temperatures, weights, and tolerances to
be used in the test procedure.
DOE believes ANSI/ASHRAE
Standard 29–2009 normative annex A
specifies two procedures:
1. Section A2, ‘‘Procedure,’’ which
specifies the calibration of the
calorimeter device and the calculation
of the calorimeter constant for the
device; and
2. Section A3, ‘‘Procedure for
Determining Quality of Harvested Ice,’’
which is used to determine the ice
hardness of a given ice maker’s ice
product, defined as the ‘‘ice hardness
factor’’ in AHRI Standard 810–2007
with Addendum 1.
DOE also believes there is confusion
in determining the ice hardness factor of
a given ice sample using section A3.
consumption and condenser water use
based on the ice hardness measurement.
pmangrum on DSK3VPTVN1PROD with RULES
1598
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
constant of less than 1.02 can be
obtained.
DOE believes the calorimeter constant
should be viewed as a calibration
constant that is representative of the
specific heat of the calorimeter device.
This calorimeter constant shall not be
greater than 1.02 when determined with
seasoned block ice. This limit
establishes that the calorimetry
procedure is being performed correctly
and all equipment is accurately
calibrated.
ANSI/ASHRAE Standard 29–2009
normative annex A specifies the
temperature difference between the air
and water, the weight of water, and the
weight of ice, but does not specify
acceptable tolerances for any of these
parameters. For example, ANSI/
ASHRAE Standard 29–2009 normative
annex A does not specify an initial
water temperature or ambient air
temperature. Instead, the initial water
temperature is specified as 20 °F above
room temperature. Also, this
temperature differential does not have
an associated tolerance. Similarly, the
weights to determine the calorimeter
constant in section A2, 30 pounds of
water and 6 pounds of ice, do not have
specified tolerances.
DOE found that changes in the
ambient temperature, the temperature
difference between the air and water,
the weight of ice, and the weight of
water did not affect the calorimeter
constant significantly. However, DOE
still must specify tolerances in order to
ensure compliance with the test
procedure. As such, DOE assumes the
tolerances specified in section 6 of
ANSI/ASHRAE Standard 29–2009,
‘‘Test Methods,’’ also apply to the
normative annex, namely water and air
temperature shall be within 1 °F of the
specified value and the measured
weights of ice and water shall be within
± 2 percent of the quantity measured.
DOE believes that the ice hardness
measurement should be conducted at
the same ambient temperature as the
other testing, namely 70 °F. This will
increase the accuracy and repeatability
of the measurement. DOE believes that
a temperature differential of 20 °F is
appropriate, as it minimizes heat flow
into and out of the water. DOE does not
believe maintaining 70 °F ± 1 °F ambient
air temperature and obtaining 90 °F ± 1
°F initial water temperature will be
burdensome for manufacturers as it is
commensurate with the ambient
requirements already called for in the
energy consumption and condenser
water consumption test, and 90 °F water
is easily attainable from a standard
water heater. As such, DOE is clarifying
in today’s final rule that normative
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
annex A of ANSI/ASHRAE Standard
29–2009 shall be performed at 70 °F ± 1
°F ambient air temperature with an
initial water temperature of 90 °F ± 1 °F
and weights shall be accurate to within
±2 percent of the quantity measured.
With these changes and assumptions,
DOE was able to produce a repeatable
calorimeter constant measurement of
less than 1.02 when testing using
seasoned ice. While there may be
variations in ice hardness inherent to
the machine, for given hardness of ice,
DOE was able to produce ice hardness
results that agree within 1.3 percent.
In response to Scotsman’s comment
regarding tolerances of the ice hardness
factor, as defined in AHRI Standard
810–2007 with Addendum 1, DOE
believes that ±5 percent variability for a
given basic model should be sufficient
given the data DOE has collected on ice
hardness measurements. DOE does not
have data to validate the need for or
support the development of a different
tolerance for the ice hardness of
continuous type ice makers. The
variance on the ice hardness factor is
only relevant to the extent that it
impacts the calculation of energy
consumption or condenser water use.
With respect to the reported energy and
condenser water use, manufacturers
must meet DOE’s certification,
compliance, and enforcement (CCE)
regulations for automatic commercial
ice makers, which established the
relevant sampling plans and tolerances
for the certified ratings of energy and
water consumption values. 76 FR 12422
(March 7, 2011).
In summary, DOE believes there is
sufficient accuracy and precision in the
test procedure for determining ice
hardness prescribed in ANSI/ASHRAE
Standard 29–2009 normative annex A,
with the exception that the test shall be
conducted at an ambient air temperature
of 70 °F ± 1 °F, with an initial water
temperature of 90 °F ± 1 °F, and weights
shall be accurate to within ± 2 percent
of the quantity measured. DOE believes
adding these specifications and
tolerances will allow for greater
repeatability and standardization
without significant additional burden
on manufacturers. All other potential
sources of variability were found to not
significantly affect the calculated ice
hardness.
g. Perforated Containers for Continuous
Type Ice Makers
As mentioned previously, continuous
type ice makers produce ice that is not
100 percent frozen and contains some
liquid water. In the current industry test
procedures, a non-perforated container
is used to capture the ice product so that
PO 00000
Frm 00008
Fmt 4700
Sfmt 4700
all of the ice/water mixture is included
in the harvest rate and the ice hardness
measurement.
At the April 2011 NOPR public
meeting, Howe commented that the
container that is used for continuous ice
should be a perforated container rather
than a solid container to remove chilled
water that is not usable ice from the test
procedure process. (Howe, No. 0005 at
p. 48) Howe noted that, beyond
beverage dispensing, there is no useful
application for the cooled liquid water
content of low hardness ice. (Howe, No.
0005 at p. 56) Scotsman and Hoshizaki
commented that when consumers use
ice, they usually do so based on volume
of both ice and water, so there is value
in both the water and the ice portion.
(Scotsman, No. 0005 at p. 39; Hoshizaki,
No. 0005 at p. 45) Manitowoc provided
the example of low quality ice being
useful in beverage dispensers and
packing fish. (Manitowoc, No. 0005 at
pp. 55–56)
In response to Howe’s suggestion that
perforated containers be used for
continuous type ice makers, Scotsman
commented that it may not be practical
to use a perforated container to capture
continuous ice because the liquid water
is infused in the ice and it takes a long
time for it to drain out, and the ice
would melt over that period. (Scotsman,
No. 0005 at pp. 50–51) Hoshizaki noted
that with a perforated container the size
of the perforations would need to be
defined because very small bits of ice,
called ‘‘dust ice,’’ may fall through the
perforations, causing a loss of good
quality ice. (Hoshizaki, No. 0005 at p.
51) Hoshizaki added that the
calorimetry test already accounts for the
differences between low hardness ice
and high hardness ice. (Hoshizaki, No.
0005 at pp. 51–52) Manitowoc agreed
with Hoshizaki with respect to the
calorimetry test being sufficient to
differentiate low hardness and high
hardness ice. (Manitowoc, No. 0005 at
p. 52) NEEA commented that a
perforated basket should not be required
for continuous type ice makers because
only a fraction of the product that is not
fully hardened (chilled water) will
escape the matrix of the hardened
product in a reasonable period. In
addition, NEEA commented that this
would introduce an unfortunate degree
of test complexity and variability in the
results and that any improvement in the
product accounting should be worth
this additional complexity and
variability. (NEEA, No. 0013 at p. 2)
DOE believes that, as Manitowoc,
Scotsman, and Hoshizaki stated, there is
clear value and customer utility in the
liquid water content of low hardness ice
and that this should be measured as part
E:\FR\FM\11JAR1.SGM
11JAR1
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
pmangrum on DSK3VPTVN1PROD with RULES
of the ice product when determining the
harvest rate. DOE also believes that the
proposed procedure for adjusting energy
and water consumption measurements
with respect to ice hardness, defined in
section III.A.3.b, is sufficient to describe
the differences between ice with
different amounts of water content.
Further, if a perforated container were
used for testing continuous type ice
makers, this would not be representative
of the ‘‘ice product’’ consumers receive
and expect. DOE is not requiring testing
of continuous type ice makers with a
perforated container in today’s final rule
and instead is maintaining the industryaccepted method of testing continuous
type ice makers with a non-perforated
container to measure harvest rate and
test for ice hardness.
4. Clarify the Test Method and
Reporting Requirements for Remote
Condensing Automatic Commercial Ice
Makers
EPCA establishes energy conservation
standards for two types of remote
condensing automatic commercial ice
makers: (1) Remote condensing (but not
remote compressor) and (2) remote
condensing and remote compressor. (42
U.S.C. 6313(d)(1)) Remote condensing
(but not remote compressor) ice makers
are sold and operated with a dedicated
remote condenser that is in a separate
section from the ice-making mechanism
and compressor. Remote condensing
and remote compressor automatic
commercial ice makers may be operated
with a dedicated remote condensing
unit or connected to a remote
compressor rack. Units designed for
connection to a compressor rack may
also be sold with dedicated condensing
units, but some rack-connection units
are sold only for rack connection,
without a dedicated refrigeration
system. The energy use of such
equipment is often reported without
including the compressor or condenser
energy use, since manufacturers
generally do not have a compressor rack
at their disposal for testing purposes. In
the April 2011 NOPR, DOE proposed
that remote condensing ice makers that
are designed to be used with a remote
condensing rack would be tested with a
sufficiently sized dedicated remote
condensing unit. This approach was
proposed to ensure that ratings for such
equipment represent all of the energy
use incurred by such machines for
making ice, including the compressor
and condenser energy use. 76 FR at
18433–34 (April 4, 2011).
Howe, Manitowoc, NEEA, Follett, CA
IOUs, and the Natural Resources
Defense Council (NRDC) all agreed with
DOE’s proposal to test remote
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
condensing ice makers designed to be
connected to a remote condensing rack
using dedicated remote condensing
units and reporting the energy
consumption of the ice-making
mechanism, condenser, and compressor.
(Howe, No. 0005 at p. 63; Manitowoc,
No. 0005 at p. 64; NEEA, No. 0005 at p.
64; Follett, No. 0008 at p. 1; CA IOUs,
No. 0011 at p. 2; NRDC, No. 0012 at p.
1) Earthjustice and NRDC both
recommended that DOE provide clear
guidance on how to select a remote
condensing unit to pair with a given ice
maker for such a test. (Earthjustice, No.
0005 at p. 75; NRDC, No. 0012 at p. 1)
However, the CA IOUs and NEEA
commented that, given that ice
production performance is closely tied
to the refrigerant system specifications,
as manifested in the ice-making head,
manufacturers will likely select
compressor/condenser components that
are properly matched to the
requirements of the balance of the
system, since any significant deviation
from this would likely change ice
production performance and adversely
affect the energy performance rating of
the system. (CA IOUs, No. 0011 at p. 2;
NEEA, No. 0013 at pp. 2–3) NEEA
suggested that one possible guideline for
selecting the balance-of-system
components might simply be to require
that the ice-making head be tested with
the compressor/condenser components
that would be shipped with it if sold
with a dedicated condenser; however,
NEEA also commented that this is a
minor issue. (NEEA, No. 0013 at
pp. 2–3)
Hoshizaki stated that, generally, a
rack unit ice machine is similar in
construction to other ice machines that
are designed to be paired with a remote
condensing unit, but that is not
necessarily the case every time.
(Hoshizaki, No. 0005 at p. 67) Hoshizaki
continued that it does not have a
condensing unit designed for use with
its largest rack unit machine and it
would have to develop such a
condensing unit to test the ice maker as
proposed. (Hoshizaki, No. 0005 at pp.
67–68) Scotsman stated that it also
manufactures products that are meant to
be connected to rack systems for which
it does not offer a dedicated condensing
unit, and that it would be problematic
for Scotsman to develop a companion
condensing unit for it. Scotsman added
that such a rating would be arbitrary
because it would not represent what
was actually sold. (Scotsman, No. 0005
at pp. 72–73) Scotsman recommended
that only the power of the ice-making
mechanism should be reported for units
that do not have matched dedicated
PO 00000
Frm 00009
Fmt 4700
Sfmt 4700
1599
condensing units, because reporting
power for the condensing units for those
machines would require manufacturers
to either design and build or purchase
a condenser that would never be offered
for sale. (Scotsman, No. 0010 at p. 2)
Manitowoc agreed that, in most
situations, manufacturers will use the
same basic evaporator section and
controls for both a parallel rack and
remote condensing/compressor, so the
inclusion of the remote system with a
dedicated condensing unit will
effectively cover the testing and
regulation of the majority of automatic
commercial ice machines, even if they
are matched to a parallel rack system.
Manitowoc recommended that the test
method only include matched remote
condensing systems with a designated
condensing unit, and that any
evaporator section that is sold only for
application with a remote parallel rack
is outside of the scope of the
regulations. (Manitowoc, No. 0009 at p.
2) Howe stated that many of the units
it manufactures are designed solely for
use with remote, field-built refrigeration
systems, and it does not have
condensing units available to test these
units. Howe contended that this would
leave them and other small
manufacturers with no choice but to
discontinue models, thus decreasing
sales and severely harming their
financial viability. (Howe, No. 0017 at
pp. 4–5)
DOE believes that testing all remote
condensing and remote compressor
automatic commercial ice makers that
are designed to be connected to a remote
compressor rack with a sufficiently
sized dedicated remote condensing unit
will adequately represent the energy
consumption of this equipment without
introducing undue burden. DOE notes
that typically a remote condensing and
compressor ice maker is designed to be
paired with only one type of dedicated
condensing unit and agrees with
interested parties that manufacturers
will be encouraged to test the ice maker
using this paring as it will ensure the ice
maker operates most efficiently. Thus,
DOE does not believe further
specification as to the pairing of remote
condensing and remote compressor icemaking mechanisms and dedicated
remote condensing units is required. For
remote condensing and remote
compressor ice makers that can be sold
either with a matched dedicated
condensing unit or for connection to a
remote compressor rack, this method
provides a straightforward and
consistent way to compare the
performance of remote condensing and
remote compressor ice makers. Even
E:\FR\FM\11JAR1.SGM
11JAR1
1600
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
they do not meet the definition of an
automatic commercial ice maker under
the statute. Hence, the test procedure
final rule does not address such
products. DOE notes that remote
condensing automatic commercial ice
makers designed to be connected to a
remote rack constitute a small market
share and are typically more efficient
than similar, smaller capacity ice
makers. DOE also notes that there is
interest by manufacturers and the
ENERGY STAR program for DOE to
provide a test method for these types of
systems. Consequently, DOE will
address testing of remote condensing
automatic commercial ice makers
designed to be connected to a remote
rack in its ENERGY STAR test
procedure development process, which
is separate from this rulemaking.
In summary, DOE clarifies in this
final rule that remote condensing
automatic commercial ice makers that
are sold exclusively to be connected to
remote compressor racks do not meet
the definition of an automatic
commercial ice maker set forth under 42
U.S.C. 6311(19) and, as such, are not
subject to DOE regulations.
DOE further notes that ice makers that
could be connected to remote
compressor racks but are also sold with
dedicated condensing units are covered
by DOE regulations in their
configuration when sold with dedicated
condensing units.
At the September 2006 public meeting
for the 2006 en masse proposed rule,
ARI supported DOE’s proposal to adopt
ARI Standard 810–2003 as the test
procedure for automatic commercial ice
makers with the revised energy use rate
equation. However, ARI further stated
that the ARI and ASHRAE standards
have been used without the
clarification. (Docket No. EE–RM/TP–
05–500, ARI, Public Meeting Transcript,
No. 18.8 at pp. 45–46)
The equation contained in ANSI/
ASHRAE Standard 29–1988 (RA 2005),
as adopted, directs that the energy
consumption shall be calculated as the
weight of ice produced during three
specified time periods divided by the
power consumed during those same
three time periods. The specified time
periods are defined as three complete
cycles for batch type ice makers and
three 14.4-minute periods for
continuous type ice makers. The
verbatim equation from ANSI/ASHRAE
Standard 29–1988 (RA 2005) is as
follows:
In the above equation, ‘‘kWh/100 lb
ice’’ refers to the desired energy
consumption rate normalized per 100
pounds of ice produced; 8.2a refers to
the data to be recorded for the capacity
test, specifically weight in pounds of ice
produced for three prescribed periods of
collection; and 8.4a refers to the section
of the standard that describes the data
to be recorded for the calculation of
energy consumption, specifically the
energy input in kilowatt-hours for the
same periods prescribed for
measurement of capacity. This equation
did not change in the update of ANSI/
ASHRAE Standard 29–1988 (RA 2005)
to the most recent ANSI/ASHRAE
Standard 29–2009.
In the April 2011 NOPR, DOE
concluded that the procedure specified
in ANSI/ASHRAE Standard 29–2009 is
clear and unambiguous. As a result,
DOE proposed to remove the
clarification for the calculation of
energy consumption rate in this
rulemaking. 76 FR at 18434–35 (April 4,
2011). AHRI, NEEA, Manitowoc, Follett,
Hoshizaki, and Scotsman all supported
DOE’s proposal to remove the
calculation for energy consumption.
(AHRI, No. 0015 at p. 3; NEEA, No. 0013
at p. 3; Manitowoc, No. 0009 at p. 3;
Follett, No. 0008 at p. 1; Hoshizaki, No.
0005 at p. 93; Scotsman, No. 0005 at
p. 93)
DOE believes the ANSI/ASHRAE
Standard 29–2009 test procedure clearly
states that the mass of ice collected will
be recorded for each of the three
complete periods specified. ANSI/
ASHRAE Standard 29–2009 also states
that the power consumption will be
recorded for the same three periods.
DOE believes that this statement is clear
and does not provide opportunity for
misinterpretation. Additionally, DOE
acknowledges that this method may
show more consistency in the average
energy use rate calculation and, further,
is the method typically used in industry
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
PO 00000
Frm 00010
Fmt 4700
Sfmt 4700
5. Discontinue Use of a Clarified Energy
Rate Calculation
E:\FR\FM\11JAR1.SGM
11JAR1
ER11JA12.047
The current DOE test procedure
references ARI Standard 810–2003, with
an amended calculation for determining
the energy consumption rate for the
purposes of compliance with DOE’s
energy conservation standards. ARI
Standard 810–2003 references ANSI/
ASHRAE Standard 29–1988 (RA 2005)
as the method of test for this equipment,
including the equations for calculating
the energy consumption rate per 100
pounds of ice produced. In the 2006 en
masse proposed rule, DOE found the
language in ANSI/ASHRAE Standard
29–1988 (RA 2005) unclear and
proposed that the energy consumption
rate be normalized to 100 pounds of ice
instead and be determined as shown in
the following equation. 71 FR at 71350
(Dec. 8, 2006).
ER11JA12.046
pmangrum on DSK3VPTVN1PROD with RULES
though DOE believes that the dedicated
condensing unit and ice maker will be
a unique combination and further
specificity in the test procedure is
unnecessary, DOE notes that the ratings
for each basic model must be based on
the least efficient individual model
combination.
For remote condensing and remote
compressor ice makers that are never
sold with a dedicated condensing unit,
DOE considered Manitowoc’s comment
that ice makers designed only for
connection to remote compressor racks
are out of the scope of the regulations.
DOE concurs with this comment,
finding that these units are inconsistent
with the definition of ‘‘automatic
commercial ice maker’’ in EPCA. EPCA
defines an automatic commercial ice
maker as ‘‘a factory-made assembly (not
necessarily shipped in one package)
that—(1) consists of a condensing unit
and ice-making section operating as an
integrated unit, with means for making
and harvesting ice.’’ (42 U.S.C.
6311(19)) Because remote condensing
automatic commercial ice makers that
are solely designed to be connected to
a remote rack are not sold or
manufactured with a condensing unit,
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
pmangrum on DSK3VPTVN1PROD with RULES
today. In this final rule, DOE is
removing the language that clarifies the
calculation of energy consumption rate.
6. Test Procedure Compliance Date
EPCA, as amended, requires that any
amended test procedures for automatic
commercial ice makers shall comply
with section 6293(e) of the same title (42
U.S.C. 6314(a)(7)(C)), which in turn
prescribes that if any rulemaking
amends a test procedure, DOE must
determine ‘‘to what extent, if any, the
proposed test procedure would alter the
measured energy efficiency * * * of
any covered product as determined
under the existing test procedure.’’ (42
U.S.C. 6293(e)(1)) Further, if DOE
determines that the amended test
procedure would alter the measured
efficiency of a covered product, DOE
must amend the applicable energy
conservation standard accordingly. (42
U.S.C. 6293(e)(2))
In accordance with 42 U.S.C. 6293(e),
DOE evaluated the amended test
procedure, as adopted in today’s final
rule, to determine if it will affect the
measured energy efficiency of a covered
piece of equipment determined under
the existing test procedure. DOE
believes that the amendments set forth
in today’s final rule will not change the
measured energy consumption of any
covered piece of equipment. The
reasoning for this determination is set
forth in the following section.
When the revised ACIM test
procedure final rule goes into effect, 30
days from today’s publication in the
Federal Register, the energy
conservation standards set in EPACT
2005 for automatic commercial ice
makers that produce cube type ice of
capacities between 50 and 2,500 pounds
of ice per 24 hours will be in effect. DOE
believes that the only test procedure
amendments adopted in this final rule
applicable to automatic commercial ice
makers covered under EPACT 2005
standards are those that update the
references to industry test procedures to
their most current versions and
discontinue the use of a clarified energy
use rate equation. DOE believes that
these amendments would not
significantly affect the measured energy
or water use of equipment for which
standards are currently in place.
The amendment that updates the
references to industry test procedures to
their most current versions is not
anticipated to affect the measured
energy consumption or condenser water
use of covered equipment determined
by DOE’s existing test procedure. The
updated industry test procedures, AHRI
Standard 810–2007 with Addendum 1
and ANSI/ASHRAE Standard 29–2009,
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
primarily expand the test procedure to
continuous type ice makers and ice
makers with capacities up to 4,000
pounds of ice per 24 hours, which does
not affect the test procedure for ice
makers that make cube type ice with
capacities between 50 and 2,500 pounds
of ice per 24 hours. AHRI Standard 810–
2007 with Addendum 1 revised the
definition of ‘‘potable water use rate’’
and added new definitions of ‘‘purge or
dump water’’ and ‘‘harvest water’’ that
more accurately describe the water
consumption of automatic commercial
ice makers. This change only affects
measurement of the potable water use of
automatic commercial ice makers and,
as such, does not impact the DOE test
procedure for automatic commercial ice
makers. The amendment that
discontinues the use of the clarified
energy use rate equation is primarily
editorial and does not fundamentally
affect the way automatic commercial ice
makers are tested. These amendments
are described in more detail in sections
III.A.1 and III.A.5. DOE notes that if
manufacturers test a given basic model
using the amended test procedure and
find it results in a more consumptive
rating than its certified value, they are
required to recertify the given basic
model with the Department.
In this final rule, DOE also adopts
other test procedure amendments that
are only applicable to types of automatic
commercial ice makers for which energy
conservation standards do not currently
exist. In the concurrent ACIM energy
conservation standards rulemaking
(Docket No. EERE–2010–BT–STD–
0037), DOE is considering establishing
energy conservation standards for batch
type and continuous type ice makers
with capacities up to 4,000 pounds of
ice per 24 hours. This includes new
energy conservation standards for batch
type ice makers that produce cube type
ice with capacities between 2,500 and
4,000 pounds of ice per 24 hours, batch
type ice makers that produce other than
cube type ice with capacities between
50 and 4,000 pounds of ice per 24
hours, and continuous type ice makers
with capacities between 50 and 4,000
pounds of ice per 24 hours. Because
there currently are no standards for the
aforementioned types of ice makers, 42
U.S.C. 6293(e) does not apply to test
procedure amendments that affect only
those equipment types.
1601
procedure proposed rulemaking, but
which are not among the amendments
discussed above and included in this
final rule. The additional matters on
which DOE received comments are as
follows:
1. Test Method for Modulating Capacity
Automatic Commercial Ice Makers
2. Treatment of Tube Type Ice Machines
3. Quantification of Auxiliary Energy
Use
4. Measurement of Storage Bin
Effectiveness
5. Establishment of a Metric for Potable
Water Used in Making Ice
6. Standardization of Water Hardness
for Measurement of Potable Water
Used in Making Ice
7. Testing of Batch Type Ice Makers at
the Highest Purge Setting
8. Consideration of Space Conditioning
Loads
9. Burden Due to Cost of Testing
This section discusses these
comments and DOE’s responses to them.
1. Test Method for Modulating Capacity
Automatic Commercial Ice Makers
An ice maker could theoretically be
designed for multiple capacity levels,
either using a single compressor capable
of multiple or variable capacities, or
using multiple compressors. This may
be advantageous since ice makers
operate at full capacity for only a small
portion of the time, if at all. Such a
system could potentially produce ice
more efficiently when operating at a low
capacity level because there would be
more heat exchanger surface area
available relative to the mass flow of
refrigerant, which would reduce
temperature differences in the heat
exchangers and result in operation of
the compressor with lower pressure lift.
DOE is not aware of any evidence that
such a system has been sold or tested
anywhere in the world. However, the
basic concept is illustrated by the
current use of different capacity models
using the same heat exchangers with
different capacity compressors. For such
product pairs, the lower capacity
machine is generally more efficient.
In the April 2011 NOPR, DOE
proposed an optional test procedure to
measure energy and water use of
variable or multiple capacity systems.
The proposed procedure involved
measuring energy use in kilowatt-hours
per 100 pounds of ice and water use in
B. Notice of Proposed Rulemaking
gallons per 100 pounds of ice of at least
Comment Summary and DOE Responses two production rates and calculating
weighted average energy use and water
At the April 2011 NOPR public
use values. DOE proposed that, for
meeting and in the ensuing comment
modulating capacity systems, testing
period, DOE received comments from
would be done at the maximum and
interested parties that were in response
minimum capacity settings. These
to issues discussed in the ACIM test
PO 00000
Frm 00011
Fmt 4700
Sfmt 4700
E:\FR\FM\11JAR1.SGM
11JAR1
1602
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
pmangrum on DSK3VPTVN1PROD with RULES
values would then be averaged to
determine the energy consumption and
condenser water consumption of the ice
maker. DOE proposed equal weighting
of the measurements at different
capacities (as represented by the
average) and requested information and
data that might be used to develop a
weighting scheme more representative
of field use. 76 FR at 18434 (April 4,
2011).
At the April 2011 NOPR public
meeting and in subsequent written
comments, interested parties all agreed
that DOE was premature in establishing
test procedures for a technology that
was not on the market, or even in
development, and that DOE should wait
until there is more information about
how these machines would function
before establishing a test procedure.
(AHRI, No. 0005 at p. 85; Scotsman, No.
0010 at p. 2; NRDC, No. 0012 at p. 1;
NEEA, No. 0013 at p. 3; Howe, No. 0017
at p. 5) NRDC and NEEA offered that
manufacturers are free in the future to
seek waivers from established test
procedures if and when they need to do
so to certify such a product complies
with DOE’s energy conservation
standards. (NRDC, No. 0012 at p. 1;
NEEA, No. 0013 at p. 3) NEEA also
offered to consider acquiring some ice
maker end-use metering data to
determine ice maker duty cycles to shed
some light on how to weight tested
energy use values in the future. (NEEA,
No. 0013 at p. 3)
DOE acknowledges the comments of
interested parties and concedes that
incorporating a method for
accommodating modulating capacity ice
makers may be premature, since
modulating capacity ice makers
currently do not exist and there is
limited information about how such
equipment would function. DOE will
not incorporate a test method for testing
automatic commercial ice makers at
multiple capacity ranges at this time. If
a manufacturer develops such an ice
maker, DOE encourages that
manufacturer to follow the test
procedure waiver process in 10 CFR
431.401.
2. Treatment of Tube Type Ice Machines
In the April 2011 NOPR, DOE
proposed to clarify in the DOE test
procedure that tube and other batch
technologies can be tested by the
current industry test procedures using
the batch type test method. 76 FR at
18436 (April 4, 2011). Scotsman,
Manitowoc, and Follett supported
DOE’s approach of treating all non-cube
batch type ice makers consistently using
the test procedure for batch type ice
makers. (Scotsman, No. 0005 at p. 97;
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
Manitowoc, No. 0005 at p. 97; Follett,
No. 0008 at p. 1) The CA IOUs asked
DOE to clarify in the DOE test procedure
that tube, cracked, and other batch type
technologies will be included by the
proposed DOE definitions and test
method. (CA IOUs, No. 0011 at p. 2)
DOE agrees with the comments from
Scotsman, Manitowoc, and Follett
regarding categorization of tube type ice
machines, and finds that tube type
machines can be tested under the
currently available test procedures.
Therefore, DOE is clarifying in the DOE
test procedure that tube and other batch
technologies can be tested by the
current industry test procedures using
the batch type test method. DOE will
treat all batch type machines, as defined
previously in the proposed rule, the
same. This will include tube type, cube
type, and other batch type automatic
commercial ice makers.
3. Quantification of Auxiliary Energy
Use
In the April 2011 NOPR, DOE referred
to energy consumed when an ice maker
is not producing ice as auxiliary energy
consumption. 76 FR at 18436 (April 4,
2011). DOE also noted that the
magnitude of this energy use is less than
one percent of the total daily ice maker’s
energy consumption, assuming typical
auxiliary power levels and ice maker
duty cycle (i.e. portion of time in a day
that the ice maker produces ice). Thus,
DOE did not propose incorporating the
measurement of auxiliary energy use in
the test procedure since DOE could not
find economic justification in the
potential energy savings generated when
considering the additional test
procedure burden associated with
auxiliary power testing. 76 FR at 18436
(April 4, 2011).
Follett, Scotsman, and the CA IOUs
supported DOE’s determination that an
additional test procedure to quantify
auxiliary energy consumption is not
justified. (Scotsman, No. 0010 at p. 3;
Follett, No. 0008 at p. 2; CA IOUs, No.
0011 at p. 2) Manitowoc agreed with
DOE’s finding that auxiliary energy use
represents an insignificant contribution
to the total energy consumption of a
commercial ice machine.4 Manitowoc
further stated that any attempt to
incorporate these minor standby losses
would require definition of the
percentage of time the ice machine is
operating in a typical installation,
would require laboratories to measure
power consumption at levels below 1
4 At the Framework Document public meeting,
Manitowoc mentioned that standby energy use due
to sensors could represent an electrical load as high
as 10 watts in some units. (Docket No. EERE–2010–
BT–STD–0037, Manitowoc Ice, No. 0016 at p. 143)
PO 00000
Frm 00012
Fmt 4700
Sfmt 4700
percent of operating input power, and in
the end would at most change the
energy efficiency value for the machine
by an amount well below the tolerances
allowed in the reference test standards.
(Manitowoc, No. 0009 at p. 3)
Manitowoc added that there actually is
no auxiliary energy consumption in an
automatic commercial ice maker, since
ice makers are all electrically powered
and all of the electricity use is measured
while they operate during a test.
(Manitowoc, No. 0005 at pp. 109–110)
The CA IOUs and NEEA stated that,
based on the definition of standby (i.e.,
connected to a power source and not
performing any of its primary
functions), DOE should call this mode
‘‘standby mode’’ instead of ‘‘auxiliary
mode.’’ (CA IOUs, No. 0011 at p. 2;
NEEA, No. 0013 at pp. 3–4)
AHRI agreed with DOE’s conclusion
that the auxiliary energy use during the
non-ice-making period is very small and
that its quantification is not justified.
AHRI offered that ‘‘standby mode’’
energy consumption represents a very
small portion of the energy usage and is
negligible. AHRI also stated that EPCA
does not give DOE the authority to
regulate ‘‘standby mode’’ and ‘‘off
mode’’ energy for commercial
equipment because section 42 U.S.C.
6295 of EPCA, as amended by EISA
2007, specifically deals with consumer
products (i.e., residential equipment)
and not commercial equipment. (AHRI,
No. 0015 at p. 3)
NRDC and Earthjustice disagreed with
AHRI and commented that the statutory
direction regarding standby for
consumer products requires that it be
considered for implementation when
test procedures for consumer products
are revised, but that this does not
preclude DOE from considering standby
or other aspects of auxiliary energy use
in commercial products. (NRDC, No.
0005 at p. 107; Earthjustice, No. 0014 at
p. 1) Earthjustice also noted that,
although Congress did not specifically
mandate the development of standby
and off mode energy consumption
metrics for commercial equipment, 10
watts is consistent with the baseline
levels of standby energy consumption
that Congress considered significant
enough to merit regulation in residential
products. Earthjustice pointed to 73 FR
62052 (Oct. 17, 2008), where baseline
standby power for microwave ovens was
given as 4 watts, and 75 FR 64627 (Oct.
20, 2010), where baseline standby and
off mode electricity consumption of
furnaces was given as ranging from 2 to
10 watts. Earthjustice added that, even
if measuring and regulating the
between-cycle energy consumption of
ice makers would at best reduce the
E:\FR\FM\11JAR1.SGM
11JAR1
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
pmangrum on DSK3VPTVN1PROD with RULES
total energy consumption of this
equipment by no more than 1 percent,
promulgating ice maker standards that
fail to capture these energy savings, if
technologically feasible and
economically justified, would be
inconsistent with EPCA’s direction to
maximize energy savings. (42 U.S.C.
6295(o)(2)(A)) Earthjustice also stated
that including provisions in the test
procedure to measure the energy
consumption of ice makers in between
ice-producing cycles is needed to
comport with the EPCA requirement
that test procedures accurately depict
real-world energy consumption (42
U.S.C. 6314(a)(2)), as the consumers of
this equipment are unlikely to unplug
their ice makers when the ice storage
bin is full. (Earthjustice, No. 0014
at p. 1)
NRDC and NEEA both recommended
that DOE incorporate a measure of
auxiliary energy use into the test
procedure, as consumption levels as
high as 10 watts certainly warrant
measurement, and incorporate this
measure into the efficiency standard if
justified. (NRDC, No. 0012 at p. 2;
NEEA, No. 0005 at p. 99) NEEA also
stated that this energy consumption
should be called ‘‘standby energy
consumption,’’ and disagreed that the
measurement of standby energy use
represents anything more than a minor
additional testing burden, as the
equipment required to measure it
precisely is inexpensive and the test, as
spelled out in International
Electrotechnical Commission (IEC)
62301, is simple to conduct. (NEEA, No.
0013 at pp. 3–4)
DOE agrees with commenters that
auxiliary energy use could also be
referred to as standby energy
consumption. DOE has been unable,
however, to collect sufficient
information regarding standby mode
energy use to support the promulgation
of a standby mode test procedure within
the scope of this rulemaking.
4. Measurement of Storage Bin
Effectiveness
A common metric used to quantify ice
meltage in the ice storage bin is storage
bin effectiveness. Storage bin
effectiveness is defined as a theoretical
expression of the fraction of ice that
under specific rating conditions would
be expected to remain in the ice storage
bin 24 hours after it is produced, stated
as a percentage of total ice deposited in
the bin. AHRI has a standard, AHRI
820–2000, that describes a test method
for quantifying the effectiveness of ice
storage bins. This method, or a similar
method, is also used in the Canadian
and Australian test procedures for
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
automatic commercial ice makers to
quantify ice storage bin effectiveness.
In the April 2011 NOPR, DOE stated
that, while quantifying the additional
energy use associated with ice storage
losses could contribute to additional
energy savings, doing so would result in
an inconsistency between the standards
for self-contained and remote
condensing ice makers or ice-making
heads because DOE would only be
addressing the ice storage losses
associated with the storage bins that are
shipped with the ice making mechanism
from the point of manufacturer (i.e., selfcontained ice makers). Consequently
DOE noted that there could be an
increased burden resulting from testing
for storage bin effectiveness for
manufacturers of self-contained units
only. DOE proposed, for these reasons,
to not include a quantification of
meltage in the storage bin in this
rulemaking. 76 FR at 18436 (April 4,
2011).
Howe, Manitowoc, Hoshizaki, and
Scotsman commented that ice storage
bins are typically not specified by the
manufacturer, are separate devices, have
different lifetimes, and can be paired
with one automatic commercial ice
machine in many different
combinations based on a variety of enduser requirements. These manufacturers
all contended that it would be difficult
to include ice storage bins as a part of
the test procedure for ice-making
equipment, and testing all possible
combinations would be excessively
burdensome and costly for all
manufacturers. (Howe, No. 0017 at p. 4;
Manitowoc, No. 0009 at p. 3; Hoshizaki,
No. 0005 at pp. 124–125; Scotsman, No.
0010 at p. 3) Howe further commented
that ice storage bins are often sold
separately from the automatic
commercial ice makers, and many small
manufacturers only produce ice storage
bins, not ice machines. (Howe, No. 0017
at p. 4) In addition, Howe, Follett, and
Manitowoc all commented that ice
storage bin efficiencies are outside the
scope of this proposed rule and
suggested that if a test procedure for ice
storage bin effectiveness is established,
it should be separate from the ACIM test
procedure. (Howe, No. 0017 at p. 4;
Follett, No. 0008 at p. 1; Manitowoc, No.
0005 at p. 116) AHRI expressed its
opinion that DOE lacks the authority to
regulate the effectiveness of storage bins
because EPACT 2005 only addresses the
energy consumption of commercial ice
makers and nothing else. (AHRI, No.
0015 at p. 2)
Earthjustice commented that there is
precedent for DOE to adopt test
procedures and standards for products
that account for such indirect forms of
PO 00000
Frm 00013
Fmt 4700
Sfmt 4700
1603
energy consumption. (Earthjustice, No.
0014 at p. 2) Earthjustice further
commented that the statute’s definition
of automatic commercial ice maker
states that an automatic commercial ice
maker may include a means for storing
ice, dispensing ice, or storing and
dispensing ice. Earthjustice added that
while Congress did not establish
standards applicable to the storage of
ice, it did provide DOE with a
requirement to amend standards for
automatic commercial ice makers, and if
storage is a part of the ice maker, clearly
the Department has the authority.
(Earthjustice, No. 0005 at p. 119) NRDC
and the Appliance Standards Awareness
Project (ASAP) commented that DOE
should not preclude coverage of storage
bins in the standards rulemaking by not
covering them in the test procedure.
(NRDC, No. 0005 at p. 119; ASAP, No.
0005 at p. 129) The CA IOUs, NEEA,
and NRDC recommended that the
Department include a measure of ice
storage bin effectiveness in the test
procedure, applicable to units shipped
with an integral bin, since ineffective
storage contributes to additional energy
use, condenser water use, and potable
water use for a given end-user demand
for finished ice. (NRDC, No. 0012 at p.
2; NEEA, No. 0005 at p. 124; CA IOUs,
No. 0011 at p. 3) NRDC and NEEA
further stated that the concern over
additional test burden is misguided
given that an AHRI test method for
quantifying the effectiveness of storage
bins has long been available and
Canadian standards already require
manufacturers to conduct this test.
(NRDC, No. 0012 at p. 2; NEEA, No.
0005 at p. 124) NEEA further stated that
it sees no problem in measuring storage
bin effectiveness only for self-contained
equipment, as there are other test
procedure inconsistencies between
classes already and this one is
appropriate to the equipment. In
response to manufacturer comments
that one ice-making head may be
shipped with any one of a number of
storage bins, NEEA offered that a
separate efficiency metric for the storage
bins could easily work in practice.
(NEEA, No. 0013 at p. 4)
While DOE acknowledges
stakeholders’ concerns regarding storage
bin effectiveness, DOE has determined
that it will not pursue a measure for
storage bin effectiveness at this time.
Many ice makers (ice-making heads and
remote compressing ice makers) can be
paired with any number of storage bins,
often produced by other manufacturers,
and are typically paired in the field
upon installation. In these cases, the
effectiveness of such storage bins is
E:\FR\FM\11JAR1.SGM
11JAR1
1604
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
beyond the control of the manufacturer
of the ice making head or remote
compressing ice maker.
Furthermore, if DOE were to regulate
self-contained ice makers only, it could
disincentivize the manufacturing of
such devices, effectively eliminating a
feature (built-in ice storage bins). See 42
U.S.C. 6295(o)(4). In order to avoid this
outcome, DOE is choosing not to
regulate self-contained ice makers only.
Therefore, DOE believes it would be
more consistent to promulgate test
procedures and subsequent standards
for ice storage bins and the bins of selfcontained ice makers at the same time.
Due to market complexities inherent in
the pairing of ice makers and storage
bins, DOE is declining to include a
quantification of meltage in the storage
bin as part of this rulemaking.
pmangrum on DSK3VPTVN1PROD with RULES
5. Establishment of a Metric for Potable
Water Used To Produce Ice
The current DOE energy conservation
standard for automatic commercial ice
makers established metrics of energy
use per 100 pounds of ice for all
equipment classes, and condenser water
use per 100 pounds of ice produced for
water-cooled models only. However,
automatic commercial ice makers
consume potable water to produce ice as
well. AHRI Standard 810–2007 with
Addendum 1 defines ‘‘potable water use
rate’’ as the amount of potable water
used in making ice, including ‘‘dump or
purge water’’ and ‘‘harvest water.’’ AHRI
Standard 810–2007 with Addendum 1
defines ‘‘dump or purge water’’ as the
water from the ice-making process that
was not frozen at the end of the freeze
cycle and is discharged from a batch
type automatic commercial ice maker
and ‘‘harvest water’’ as the water that
has been collected with the ice used to
measure the machine’s capacity.
Including potable water used to
produce ice in the overall water metric
could produce significant water savings
and additional energy savings. The
current EPA ENERGY STAR standard
for automatic ice makers limits water
use in air-cooled machines to less than
25 gallons per 100 pounds of ice for
remote condensing automatic
commercial ice makers and 35 gallons
per 100 pounds of ice for self-contained
equipment.5 In addition, both the
previously referenced ARI Standard
810–2003 and the updated AHRI
Standard 810–2007 with Addendum 1
provide a test method to measure the
5 U.S. Environmental Protection Agency.
Commercial Ice Machines Key Product Criteria.
2008. (Last accessed March 5, 2011.) https://
www.energystar.gov/index.cfm?c=comm_
ice_machines.pr_crit_comm_ice_machines
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
amount of water used in making ice in
units of gallons per 100 pounds of ice.
In the April 2011 NOPR, DOE stated
that it had examined the statutory
authority in EPCA for the establishment
of test procedures and energy and water
conservation standards for automatic
commercial ice makers and determined
that the Department does not have a
direct mandate from Congress to
regulate potable water use under 42
U.S.C. 6313. Therefore, in the April
2011 NOPR, DOE proposed not to
regulate potable water used in making
ice in this rulemaking. 76 FR at 18437
(April 4, 2011).
AHRI commented that potable water
consumption information is already
available in the AHRI online database,
which is publicly available, and
recommended against requiring potable
water testing in the DOE test procedure
due to the increased burden of meeting
DOE’s CCE regulations. (AHRI, No. 0005
at pp. 139–140) AHRI, Follett, and
Scotsman agreed that potable water use
should not be regulated as part of this
rulemaking. (AHRI, No. 0015 at pp. 3–
4; Follett, No. 0008 at p. 2; Scotsman,
No. 0010 at p. 3) Manitowoc added that,
for continuous type machines,
essentially all potable water is
converted to ice product, so there is no
significant variation among available
models; and for batch machines, potable
water use is related to energy efficiency,
which drives manufacturers to
minimize potable water use in achieving
higher energy efficiency. Manitowoc
also offered that, depending on the
design of the batch ice machine, there
is an optimum range where further
reduction in potable water use can
dramatically affect the reliability of the
ice machine and the quality of the ice
that it produces, and stated that
establishing regulations on potable
water use without understanding these
limits and trade-offs could significantly
affect life-cycle cost to the end user.
(Manitowoc, No. 0009 at p. 3)
Conversely, Howe contended that
there should be a calculation for potable
water use in ice machines because
chilled waste water is currently
collected along with ice and is included
in the measured production capacity of
some ice machines, while waste water is
ignored in other machines. (Howe, No.
0005 at p. 132; Howe, No. 0005 at pp.
145–146) Howe also contended that this
requirement should apply to batch type
and continuous type ice machines.
(Howe, No. 0017 at pp. 5–6)
NEEA and NRDC stated that
establishing a measurement for potable
water in the test procedure would be
beneficial, but that standards for potable
water consumption may not be required.
PO 00000
Frm 00014
Fmt 4700
Sfmt 4700
(NEEA, No. 0005 at pp. 136–137; NRDC,
No. 0005 at p. 135) The CA IOUs,
NRDC, and NEEA recommended that
DOE adopt in this test procedure
rulemaking the test method to measure
potable water as outlined in the AHRI/
ASHRAE standards, and disagreed with
DOE regarding the Department’s
authority to regulate potable water, as
prescribed in EPCA. (CA IOUs, No. 0011
at p. 3; NRDC, No. 0012 at p.2; NEEA,
No. 0013 at pp. 4–5) The CA IOUs, ICF
International (ICF), and NEEA further
stated that the potable water use of more
than half of commercial ice makers
shipped in the United States is currently
being measured and reported by
manufacturers for ENERGY STAR
qualification and, as such, adding a
method to measure the potable water
use should not significantly increase the
testing burden for manufacturers. (CA
IOUs, No. 0011 at p. 3; ICF, No. 0005 at
p. 141; NEEA, No. 0013 at pp. 4–5)
Earthjustice, NEEA, and NRDC
commented that, although Congress has
not directly instructed the Department
to regulate potable water use, DOE has
the authority to do so in accordance
with the purposes of EPCA and with
Congress’ intent to achieve energy
savings by regulating automatic
commercial ice makers. Earthjustice and
NRDC also stated that the reporting of
potable water consumption data would
be valuable in its own right for
specifiers, end users, and water supply
utilities. (NRDC, No. 0012 at p. 2; NEEA,
No. 0013 at pp. 4–5; Earthjustice, No.
0005 at p. 150)
Earthjustice also responded to DOE’s
interpretation that the footnote to the
table at 42 U.S.C. 6313(d)(1) suggests
that Congress specifically considered
potable water use, and excluded it.
(Earthjustice, No. 0005 at p. 132)
Earthjustice claimed that DOE’s
admission that EPCA has left a ‘‘gray
area’’ surrounding the Department’s
authority to adopt potable water
standards for ice makers suggests that
DOE views this issue as one of
interpreting an ambiguous statute—an
activity in which courts grant
substantial deference to the executive
branch. Earthjustice pointed to Chevron
v. NRDC, 467 U.S. 837, 843–44 (1984),
as the controlling precedent.
Earthjustice stated that it would be
unreasonable to conclude that Congress
intended to prohibit DOE from adopting
potable water standards for ice makers,
as the note following the table in 42
U.S.C. 6313(d)(1) by its own terms
applies only to the initial standards
codified in EPACT 2005, and had
Congress intended to restrict DOE’s
authority to adopt water consumption
standards encompassing potable water
E:\FR\FM\11JAR1.SGM
11JAR1
pmangrum on DSK3VPTVN1PROD with RULES
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
use, it could have easily provided that
DOE is only authorized to adopt revised
energy use and condenser water use
standards. Instead, argued Earthjustice,
the fact that Congress clarified the
inapplicability of the EPACT 2005
standards to potable water consumption
but did not enact express language to
similarly limit DOE’s authority in
subsequent rulemakings indicates that
DOE is authorized to require the
measurement and regulation of potable
water consumption. (Earthjustice, No.
0014 at pp. 2–3)
DOE acknowledges the commenters’
concerns regarding the coverage of
potable water consumption in the ACIM
test procedure. Regarding DOE’s
authority to promulgate an ACIM test
procedure addressing potable water use,
DOE notes that 42 U.S.C. 6313(d) does
not require DOE to develop a water
conservation test procedure or standard
for potable water use in cube type ice
makers or other automatic commercial
ice makers. Rather, it sets forth energy
and condenser water use standards for
cube type ice makers at 42 U.S.C.
6313(d)(1), and allows, but does not
require, the Secretary to issue analogous
standards for other types of automatic
commercial ice makers under 42 U.S.C.
6313(d)(2).
Ambiguous statutory language may
lead to multiple interpretations in the
development of regulations. As the U.S.
Supreme Court has held, ‘‘[i]f [a] statute
is ambiguous on [a] point, we defer
* * * to the agency’s interpretation so
long as the construction is ‘a reasonable
policy choice for the agency to make.’ ’’
Nat’l Cable & Telecomms. Ass’n v.
Brand X Internet Servs., 545 U.S. 967,
986 (2005) (quoting Chevron U.S.A. Inc.
v. Natural Res. Def. Council, Inc., 467
U.S. 837, 845 (1984)). DOE believes that
it is unclear whether the footnote on
potable water use that appears in 42
U.S.C. 6313(d)(1) has a controlling effect
on 42 U.S.C. 6313(d)(2) and 42 U.S.C.
6313(d)(3). Potable water use is not
referenced anywhere else in 42 U.S.C.
6313(d), and thus it is difficult to
determine whether this footnote is a
clarification or a mandate in regard to
cube type ice makers, and furthermore,
whether it would apply to the regulation
of other types of automatic commercial
ice makers. Without a clear mandate
from Congress on potable water use
generally, and given that Congress chose
not to regulate potable water use for
cube type ice makers by statute, DOE
exercises its discretion in choosing not
to include potable water use in its test
procedure for automatic commercial ice
makers.
While there is generally a positive
relationship between energy use and
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
potable water use, DOE understands
that at a certain point the relationship
between potable water use and energy
consumption reverses due to scaling.
Based on this fact, and given the added
complexity inherent to the regulation of
potable water use and the concomitant
burden on commercial ice maker
manufacturers, DOE will not regulate or
require testing and reporting of the
potable water use of automatic
commercial ice makers at this time.
Although AHRI Standard 810–2007
with Addendum 1 already includes a
measurement of potable water
consumption, and reporting of potable
water use is required by the ENERGY
STAR program, neither performance of
AHRI Standard 810–2007 nor
participation in the ENERGY STAR
program is mandatory. Because DOE test
procedures are mandatory for all
equipment sold in the United States,
DOE must be more cognizant of burden
and the limitation of products or
features when determining the test
procedures and energy conservation
standards for covered equipment.
Earthjustice, NRDC, and NEEA noted
that among the stated purposes of EPCA,
as amended by EPACT 1992, is the
conservation of water in certain
plumbing products and appliances
under 42 U.S.C. 6201(8). (Earthjustice,
No. 0014 at pp. 2–3; NRDC, No. 0012 at
p.2; NEEA, No. 0013 at pp. 4–5) At the
time of its adoption, the language of 42
U.S.C. 6201(8) supported DOE’s
regulation of water use efficiency in
plumbing products such as
showerheads, faucets, water closets, and
urinals. Congress added the regulation
of automatic commercial ice makers
later, in EPACT 2005. Given that
Congress often amends portions of
statutes in subsequent legislation, courts
have had to examine how to interpret
unchanged parts of the statute in light
of amended sections of the same statute.
The U.S. Supreme Court has held that
‘‘a specific policy embodied in a later
Federal statute should control
construction of the earlier statute.’’ Food
& Drug Admin. v. Brown & Williamson
Tobacco Corp., 529 U.S. 120, 143
(2000). Congress set forth the general
purposes of its energy and water
conservation program for appliances in
42 U.S.C. 6201, but later established
more specific requirements for certain
products, including automatic
commercial ice makers. In EPACT 2005,
Congress required DOE to issue
standards for automatic commercial ice
makers, but excluded consideration of
potable water use. Earthjustice noted
that DOE currently regulates water use
in residential clothes washers
PO 00000
Frm 00015
Fmt 4700
Sfmt 4700
1605
(Earthjustice, No. 0014 at pp. 2–3), but
again, this is not controlled by 42 U.S.C.
6201(8). DOE did not regulate water use
for residential clothes washers under 42
U.S.C. 6295(g) until directed to by
Congress in EISA 2007, section
311(a)(2). Thus, DOE chooses today to
interpret 42 U.S.C. 6201(8) consistently
with how it has interpreted the
provision in the past: as a general
guiding principle that is implemented
through provisions within EPACT 1992
and subsequent amendments for
specific products and equipment.
In summary, DOE is using its
discretion to not cover potable water in
this rulemaking to limit the burden on
manufacturers, especially considering
that standards for potable water do not
currently exist and are not being
considered in the concurrent ACIM
energy conservation standards
rulemaking (Docket No. EERE–2010–
BT–STD–0037).
6. Standardization of Water Hardness
for Measurement of Potable Water Used
in Making Ice
Differences in water hardness can
cause ice machines to use more or less
energy and water. Harder water has a
greater concentration of total dissolved
solids and chemical ions, which affects
the thermal properties of the water.
Harder water depresses the freezing
temperature of water and results in
increased energy use to produce the
same quantity of ice. In addition, harder
water requires a higher purge setting to
prevent scaling and a decrease in ice
clarity. While DOE recognizes that
differences in water hardness can affect
the energy and water consumption of an
automatic commercial ice maker, DOE
believes that there is still uncertainty in
the causal relationship between total
dissolved solids, ion concentration, and
ice maker performance. Given the
uncertainty in the relationship between
water hardness and water and energy
consumption, DOE proposed in the
April 2011 NOPR not to standardize
water hardness in the test procedure,
but requested additional data that
would support evaluation of the need
for a standardized water hardness test.
Specifically, DOE requested additional
data or information regarding (1) The
relationship between total dissolved
solids, ion concentration, and energy
and water use; (2) the magnitude of
these effects; and (3) specific testing
methodologies that would produce
repeatable results. 76 FR at 18437 (April
4, 2011).
Manitowoc, Follett, and NEEA
supported DOE’s recommendation to
not bring water hardness into the
rulemaking. (Manitowoc, No. 0005 at p.
E:\FR\FM\11JAR1.SGM
11JAR1
pmangrum on DSK3VPTVN1PROD with RULES
1606
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
154; Follett, No. 0008 at p. 2; NEEA, No.
0013 at p. 5) Manitowoc and NEEA
agreed that water hardness or quality
has a greater effect on reliability and
maintenance than it does on energy
efficiency of commercial ice makers and
felt it would be a significant effort to
properly define and obtain ‘‘standard
hardness’’ water for testing purposes.
(Manitowoc, No. 0009 at p. 3; NEEA,
No. 0013 at p. 5) Scotsman suggested
that, if water hardness were indeed a
significant factor in energy
consumption, it would become apparent
in the certification and enforcement
actions related to the equipment and the
Department could move to standardize
it at that time, after DOE had collected
more information. (Scotsman, No. 0005
at pp. 158–159) Scotsman also offered
that it knows anecdotally that water
hardness will impact the hardness of
flake and nugget ice, but does not have
data at this time to present a correlation.
(Scotsman, No. 0010 at p. 3) NRDC
suggested that the Department consider
a range of acceptable water hardness
values as a condition for the test
procedure. (NRDC, No. 0005 at p. 154)
Hoshizaki suggested that if DOE
considers a band of water hardness
values that are acceptable to test within,
it should make sure that water of a value
within the band is geographically
available everywhere across the United
States. (Hoshizaki, No. 0005 at p. 162)
DOE appreciates interested parties’
comments and agrees that there is still
uncertainty in the causal relationship
between total dissolved solids, ion
concentration, and ice maker
performance. Specifically, it is not clear
whether total dissolved solids or ion
concentration is more significant in
impacting the energy performance of an
ice maker. DOE did not receive any
additional data that would suggest the
proper test procedure specifications for
water hardness. As such, DOE maintains
that an appropriate standardized water
hardness for use in a test procedure
cannot be accurately specified at this
time, and even if it could, applying such
a test procedure would increase the
testing burden for manufacturers. In
addition, the primary effect of
increasing water hardness would be
increased potable water used in making
ice. This is because the potential for
scale formation increases with higher
water hardness, requiring an increase in
the dump water used in batch type ice
machines that produce cube type ice.
Since DOE is not addressing potable
water in this rulemaking, DOE is not
standardizing water hardness in the test
procedure at this time, but requests
additional data that would support
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
evaluation of the need for a
standardized water hardness test.
7. Testing of Batch Type Ice Makers at
the Highest Purge Setting
At the energy conservation standard
Framework document public meeting,
ASAP cautioned that installers may
install cube type ice makers with a
purge setting in the highest water use
position, which may substantially
increase water consumption in the field
compared to the manufacturer tested
water consumption. (Docket No. EERE–
2010–BT–STD–0037, ASAP, No. 0013 at
p. 16) DOE does not have data to
validate these claims and believes that
the manufacturer-specified purge setting
is how ice makers are meant to be
installed in the field. Also, as DOE did
not propose to regulate potable water
used in making ice in the April 2011
NOPR, DOE did not believe it was
justified to require testing of automatic
commercial ice makers at the highest
purge setting. Instead, DOE proposed to
continue to require testing of automatic
commercial ice makers in accordance
with AHRI 810–2007 and ANSI/
ASHRAE Standard 29–2009. DOE also
committed to investigate the magnitude
and effects of this issue by gathering
data related to national water hardness,
the difference between manufacturer
recommended and maximum purge
settings, and the way ice makers are
typically installed in the field. 76 FR at
18437–38 (April 4, 2011).
In commenting on the April 2011
NOPR, Manitowoc, Hoshizaki, and
Follett supported the current AHRI and
industry practice to test ice makers at
the water purge setting as instructed in
the manufacturer’s installation and
operation manual for ‘‘normal’’ quality
potable water. (Manitowoc, No. 0009 at
p. 4; Hoshizaki, No. 0005 at p. 165;
Follett, No. 0008 at p. 2) Scotsman
suggested that if DOE were going to
consider a standard that included
variability in the level of purge, testing
should be done at both a maximum
flush level setting and a minimum flush
level setting, to give manufacturers
credit for water conserving purge
options. (Scotsman, No. 0005 at p. 167)
NRDC commented that both energy
and water consumption can vary
considerably across the range of fieldadjustable purge settings, ±3 percent for
energy consumption and ±20 percent for
potable water consumption, and
recommended that ice makers be tested
in their highest water consumption
purge setting. (NRDC, No. 0012 at p. 2)
The CA IOUs agreed that DOE should
require testing of ice makers at the purge
setting that uses the most water. (CA
IOUs, No. 0011 at p. 4) NEEA
PO 00000
Frm 00016
Fmt 4700
Sfmt 4700
commented that the specification to test
ice machines with the ‘‘as shipped’’
purge setting would lead to all units
being shipped in the minimum purge
mode, resulting in very unrepresentative
potable water use measurements. NEEA
cautioned that this would violate the
spirit, if not the letter, of 42 U.S.C.
6214(a)(2). (NEEA, No. 0013 at p. 5)
NEEA and NRDC stated that the
Department’s proposal simply to allow
manufacturers to specify the purge
setting for testing purposes fails to
maintain the integrity of the testing
process and reduces the incentive to
innovate in this area of machine
performance. (NRDC, No. 0012 at p. 2;
NEEA, No. 0013 at p. 5) Howe stated
that, in order to standardize energy
consumption and water usage, it is
necessary to test at the highest purge
setting, especially because energy usage
increases as the purge setting increases.
(Howe, No. 0017 at p. 6)
Although both AHRI 810–2007 and
ANSI/ASHRAE Standard 29–2009
require that the ice makers be set up
pursuant to the manufacturer’s
instruction, DOE acknowledges that this
may not capture the maximum potable
water consumption of the unit or,
perhaps, the most common water
consumption setting of the unit. DOE
found that the manufacturers
recommended purge setting is typically
an intermediate purge setting which is
adequate for most parts of the U.S. Also,
DOE found that some manufacturers
who offered adjustable purge settings
offered low purge settings, in addition
to high purge settings, to conserve water
in those places with low water
hardness.
However, DOE has found no data or
information related to how ice makers
are currently installed in the field.
Further, all previous test data are from
tests conducted at this default test
setting, and requiring testing at another
level will make historical comparisons
difficult and significantly increase the
testing burden for all manufacturers,
since manufacturers would be required
to recertify all their models using the
new test procedure. Also, changes in
purge setting most strongly affect
potable water consumption and affect
energy use to a lesser degree. As DOE
will not regulate potable water used in
making ice in this rulemaking, and the
preponderance of previous data come
from tests conducted at the
manufacturer recommended purge
setting, DOE will require testing of
automatic commercial ice makers in
accordance with AHRI 810–2007 with
Addendum 1 and ANSI/ASHRAE
Standard 29–2009 in this final rule and
E:\FR\FM\11JAR1.SGM
11JAR1
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
will not further specify the required
purge setting.
pmangrum on DSK3VPTVN1PROD with RULES
8. Consideration of Space Conditioning
Loads
In written comments submitted in
response to the April 2011 NOPR, Howe
commented that the majority of aircooled self-contained automatic
commercial ice makers are located
within air conditioned spaces (e.g.,
motels/hotels, restaurants, bars, retail
food markets, institutions, and airports).
Howe opined that the total heat
rejection of the automatic commercial
ice maker, including the heat removed
at the evaporator, heat related to
suction-cooled hermetic and semihermetic compressors, and the fan/
motor efficiency related heat, should be
tested and published so that consulting
engineers can accurately calculate the
sensible heat gain to the air conditioned
space.
Howe illustrated, saying a 970 pound
per 24 hour output automatic
commercial ice maker located in a 70 °F
space supplied with 50 °F water adds
the total rejected heat of 8,450 Btu to the
space, which must be removed by the
building cooling system, while the
energy consumption of this automatic
commercial ice maker is 3.8 kWh per
100 pounds of ice. The energy
consumed by the building cooling
system to remove this sensible internal
heat gain to the conditioned space is
estimated to be 0.85 kWh, or 22 percent
of the energy consumed by the ice
maker in question. Howe also stated that
no intermediate cooling is required if
this heat is rejected directly to outdoor
air and provided the four examples of
water cooled condensers, remote air
cooled condensers, remote dedicated
split condensing units, and an ice
machine that is field-connected to a
remote compressor rack (field-built
refrigeration system) that serves other
evaporators throughout the building.
(Howe, No. 0017 at pp. 8–9)
DOE acknowledges that the total
rejection of heat indoors for air-cooled
self-contained and ice-making head
automatic commercial ice makers may
impact space cooling loads, but DOE
expects changes from revised and new
ice maker standards to be negligible. In
chapter 2 of the preliminary technical
support document for commercial
refrigeration equipment that DOE
published on March 30, 2011, DOE
determined that the effect of efficiency
improvements in self-contained
commercial refrigeration equipment on
space conditioning loads was
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
negligible.6 DOE expects the impact of
efficiency improvements in automatic
commercial ice makers to be less than
that of commercial refrigeration
equipment because there are typically
fewer automatic commercial ice makers
per building.7 In addition, there is a
high degree of variability in the impact
of this rejected heat on the total building
heating and cooling load due to
differences in weather, building size,
and building type. In cold climates, the
additional heat rejected by the ice maker
may decrease building space heating
loads. Moreover, requiring testing and
reporting of the total heat rejection of
automatic commercial ice makers would
increase the testing and reporting
burden for self-contained and icemaking head equipment. DOE does not
believe this increase in testing burden
for some ice makers is justified given
the magnitude of impact ice makers are
expected to have on space conditioning
loads. Manufacturers may publish total
heat rejection information and engineers
may request this information when it is
required, but DOE does not believe it
will be required in all cases and, further,
believes that it is not relevant to DOE’s
standards for automatic commercial ice
makers. DOE is not including testing or
reporting for total heat rejection of
automatic commercial ice makers in this
final rule.
9. Burden Due to Cost of Testing
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered equipment.
EPCA requires that the test procedures
promulgated by DOE be reasonably
designed to produce test results that
reflect energy efficiency, energy use,
and estimated operating costs of the
covered equipment during a
representative average use cycle. EPCA
also requires that the test procedure not
be unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
6 U.S. Department of Energy—Office of Energy
Efficiency and Renewable Energy. Preliminary
Technical Support Document (TSD): Energy
Conservation Program for Certain Commercial and
Industrial Equipment: Commercial Refrigeration
Equipment, Chapter 2: Analytical Framework,
Comments from Interested Parties, and DOE
Responses. March 2011. Washington, DC https://
www1.eere.energy.gov/buildings/
appliance_standards/commercial/pdfs/cre_pa_
tsd_ch2_analytical_framework.pdf.
7 Navigant Consulting, Inc. Energy Savings
Potential and R&D Opportunities for Commercial
Refrigeration, Final Report. 2009. Prepared for the
U.S. Department of Energy—Office of Energy
Efficiency and Renewable Energy, Washington, DC
https://apps1.eere.energy.gov/buildings/
publications/pdfs/corporate/commercial_refrig_
report_10-09.pdf.
PO 00000
Frm 00017
Fmt 4700
Sfmt 4700
1607
At the April 2011 NOPR public
meeting and in subsequent written
comments, many interested parties
commented on the burden of testing for
manufacturers of automatic commercial
ice makers. AHRI commented that the
issue of regulatory burden is not
associated with conducting the test
itself, but with DOE’s CCE requirements.
AHRI emphasized that, accounting for
DOE’s CCE requirements, the cost to
comply with the Federal standard
would be 10 or 100 times what DOE
projected. (AHRI, No. 0005 at p. 179)
AHRI suggested that alternative energy
determination methods, although not
currently available for ice makers, could
be developed to help manufacturers
comply with DOE’s regulations and
reduce the burden on manufacturers.
(AHRI, No. 0005 at p. 180)
Howe commented that, using DOE
calculations of the cost of testing, the
cost to Howe would range from
$620,000 to $930,000 in the first year,
and stated that this amount vastly
exceeds what would be reasonable for a
small manufacturer to absorb. Howe
further commented that the costs of
testing for small manufacturers as
estimated in the NOPR are significantly
understated for several reasons,
including the fact that small
manufacturers typically produce large,
custom equipment that they are unable
to test in current test facilities. Howe
suggested that manufacturers of remote
automatic commercial ice machines be
allowed to test the most commonly sold
remote ice maker configuration (ice
maker, compressor, and condenser) for
each productive capacity of automatic
commercial ice maker and apply those
energy consumption ratings to similar
remote automatic commercial ice
makers of the same productive capacity.
(Howe, No. 0017 at pp. 6–8)
Conversely, NEEA contended that the
testing required by AHRI Standards 810
and 820 is not overly burdensome to
conduct, even including tests for
potable water use and standby energy
consumption. NEEA further stated that
the tests proposed by the Department,
along with a test for potable water
consumption, standby energy use, and
storage bin effectiveness, seem to be the
minimum required to fully characterize
the energy and water use of these
products, and are the same tests that the
manufacturers are already doing,
whether it be for Canadian standards,
ENERGY STAR, or AHRI product
listings. (NEEA, No. 0013 at p. 5)
DOE notes that this final rule
addresses only the incremental burden
of the test procedure changes. DOE does
not believe these test procedure
amendments will significantly increase
E:\FR\FM\11JAR1.SGM
11JAR1
pmangrum on DSK3VPTVN1PROD with RULES
1608
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
the burden on manufacturers, and the
amended test procedure is the minimum
required to fully characterize and
compare the performance of automatic
commercial ice makers. DOE maintains
that it is not possible to further limit the
burden within the test procedure and
still meet the requirements of EPCA that
the test procedure be representative of
ice maker performance during a typical
period of use. (42 U.S.C. 6314(a)(2))
The purpose of this assessment of the
burden of testing is to identify the
changes in burden arising solely from
the proposed changes in the test
procedure. DOE acknowledges that
other recent rulemakings also impact
the overall burden on manufacturers to
test and certify equipment for
compliance with DOE’s Appliances and
Commercial Equipment Standards
program. In the final rule DOE
published on March 7, 2011, which
established certification, compliance,
and enforcement regulations for covered
equipment (the CCE final rule), DOE
established requirements for
determining the number of units that
must be tested and for designing a
sampling plan for reliable testing. 76 FR
at 12422. Currently, manufacturers must
test a minimum of two units of each
basic model to arrive at the maximum
energy use rating for that basic model,
unless otherwise specified. 76 FR at
12480 (March 7, 2011). Due to issues
raised by some manufacturers of larger,
custom equipment, including automatic
commercial ice makers, on June 22,
2011 DOE published a revised final rule
establishing new compliance dates for
certification of automatic commercial
ice makers, which is 18 months from
publication in the Federal Register. 76
FR 38287 (June 30, 2011). DOE notes
that the CCE final rule published March
7, 2011 is only applicable to automatic
commercial ice makers for which
standards were set in EPACT 2005,
namely automatic commercial ice
makers that produce cube type ice with
capacities between 50 and 2,500 pounds
of ice per 24 hours. For other types of
ice makers covered under this test
procedure final rule, CCE requirements
have not yet been established and will
be considered in a separate rulemaking.
DOE acknowledges manufacturers’
concerns about the burden associated
with the overall testing and certification
of automatic commercial ice makers. To
help reduce test burden on
manufacturers of low production
volume, such as highly customized
equipment like automatic commercial
ice makers, DOE is considering
alternative energy determination
methods or alternative rating methods
for automatic commercial ice makers.
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
DOE recently issued a request for
information on this issue. 76 FR 21673
(April 18, 2011).
In response to Howe’s comment, this
test procedure rulemaking does not
describe sampling plans or define basic
model requirements for automatic
commercial ice makers, because that
information is in the CCE final rule.
DOE notes that the CCE final rule
establishes basic model definitions that
allow manufacturers to group individual
models with similar, but not exactly the
same, energy performance
characteristics into a basic model for
purposes of fulfilling the Department’s
testing and certification requirements.
The Department encourages
manufacturers to group similar
individual models as they would in
current industry practice, provided all
models identified in a certification
report as being the same basic model
have the same certified efficiency rating.
The CCE final rule also establishes that
the efficiency rating of a basic model
must be based on the least efficient or
most energy consuming individual
model, or, put another way, all
individual models within a basic model
must be at least as good as the certified
rating. The regulations also require
certification of a new basic model if a
modification results in an increase in
energy or water consumption beyond
the rated amount. 76 FR at 12428–29
(March 7, 2011).
The specific burden on small
manufacturers is discussed in DOE’s
revised final regulatory flexibility
analysis, which can be found in section
IV.B of this document.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Order 12866
The Office of Management and Budget
(OMB) has determined that test
procedure rulemakings do not constitute
‘‘significant regulatory actions’’ under
section 3(f) of Executive Order 12866,
‘‘Regulatory Planning and Review,’’ 58
FR 51735 (Oct. 4, 1993). Accordingly,
this action was not subject to review
under the Executive Order by the Office
of Information and Regulatory Affairs
(OIRA) in the OMB.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility
analysis (IRFA) whenever an agency is
required to publish a general notice of
proposed rulemaking. When an agency
promulgates a final rule after being
required to publish a general notice of
PO 00000
Frm 00018
Fmt 4700
Sfmt 4700
proposed rulemaking, the agency must
prepare a final regulatory flexibility
analysis (FRFA). The requirement to
prepare these analyses does not apply to
any proposed or final rule if the agency
certifies that the rule will not, if
promulgated, have a significant
economic impact on a substantial
number of small entities. If the agency
makes such a certification, the agency
must publish the certification in the
Federal Register along with the factual
basis for such certification.
As required by Executive Order
13272, ‘‘Proper Consideration of Small
Entities in Agency Rulemaking,’’ 67 FR
53461 (Aug. 16, 2002), DOE published
procedures and policies on February 19,
2003, so that the potential impacts of its
rules on small entities are properly
considered during the rulemaking
process. 68 FR 7990. DOE has made its
procedures and policies available on the
Office of the General Counsel’s Web
site: https://www.gc.doe.gov.
DOE reviewed the proposed rule to
amend the test procedure for automatic
commercial ice makers under the
provisions of the Regulatory Flexibility
Act and the procedures and policies
published on February 19, 2003. DOE
certified that the proposed rule, if
adopted, would not result in a
significant impact on a substantial
number of small entities. DOE received
comments on the economic impacts of
the test procedure and responds to these
comments in section III.B.9. After
consideration of these comments, DOE
continues to certify that the test
procedure amendments set forth in
today’s final rule will not have a
significant impact on a substantial
number of small entities. The factual
basis for this certification is set forth
below.
For manufacturers of automatic
commercial ice makers, the Small
Business Administration (SBA) has set a
size threshold, which defines those
entities classified as ‘‘small businesses’’
for the purposes of the statute. DOE
used the SBA’s size standards published
on January 31, 1996, as amended, to
determine whether any small entities
would be required to comply with the
rule. See 13 CFR part 121. The
standards are listed by North American
Industry Classification System (NAICS)
code and industry description and are
available at https://www.sba.gov/sites/
default/files/Size_Standards_Table.pdf.
ACIM manufacturers are classified
under NAICS 333415, ‘‘AirConditioning and Warm Air Heating
Equipment and Commercial and
Industrial Refrigeration Equipment
Manufacturing.’’ The SBA sets a
threshold of 750 employees or less for
E:\FR\FM\11JAR1.SGM
11JAR1
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
an entity to be considered as a small
business for this category.
DOE conducted a market survey using
all available public information to
identify potential small manufacturers
who could be impacted by today’s final
rule. DOE reviewed industry trade
association membership directories
(including the Association of Home
Appliance Manufacturers (AHAM)),
product databases (e.g., Federal Trade
Commission (FTC), the Thomas
Register, California Energy Commission
(CEC) and ENERGY STAR databases),
individual company Web sites, and
marketing research tools (e.g., Dun and
Bradstreet reports) to create a list of
companies that manufacture or sell
automatic commercial ice makers
covered by this rulemaking. DOE
reviewed this data to determine whether
the entities met the SBA’s definition of
a small business and manufactured
automatic commercial ice makers. DOE
screened out companies that do not
offer products covered by this
rulemaking, do not meet the definition
of a ‘‘small business,’’ or are foreign
owned and operated.
DOE initially identified 24
manufacturers of automatic commercial
ice makers available in the United
States. Of these 24 companies, 10 were
determined to be foreign owned or have
more than 750 employees, meaning that
they would not qualify as small
1609
businesses. Of the remaining 14 entities,
5 manufacture ice makers for residential
uses and 1 has filed for bankruptcy.
Thus, DOE identified 8 manufacturers
that produce covered automatic
commercial ice makers and can be
considered small businesses.
Table IV.1 stratifies the small
businesses according to their number of
employees. The smallest company has 5
employees and the largest has 175
employees. The majority of the small
businesses affected by this rulemaking
(75 percent) have fewer than 50
employees and all but one of the small
businesses have fewer than 100
employees.
TABLE IV.1—SMALL BUSINESS SIZE BY NUMBER OF EMPLOYEES
Number of small
businesses
Number of employees
pmangrum on DSK3VPTVN1PROD with RULES
1–50 ...........................................................................................................................
51–100 .......................................................................................................................
101–150 .....................................................................................................................
151–200 .....................................................................................................................
This final rule amends the test
procedure for automatic commercial ice
makers. Specifically, DOE is
incorporating revisions to the DOE test
procedure that:
1. Update the references to AHRI
Standard 810–2007 with Addendum 1
and ANSI/ASHRAE Standard 29–2009;
2. Expand the scope of the test
procedure to include equipment with
capacities from 50 to 4,000 pounds of
ice per 24 hours;
3. Provide test methods for
continuous type ice makers and
standardize the measurement of energy
and water use for continuous type ice
makers with respect to ice hardness;
4. Clarify the test method and
reporting requirements for remote
condensing automatic commercial ice
makers designed for connection to
remote compressor racks; and
5. Discontinue the use of a clarified
energy use rate calculation and instead
calculate energy use per 100 pounds of
ice as specified in ANSI/ASHRAE
Standard 29–2009.
Changes to the existing rule as
described in the preceding paragraph
have potential impacts on
manufacturers who will be required to
revise their current testing program to
comply with DOE’s energy conservation
standards. DOE has analyzed these
impacts on small businesses and
presents its findings in the remainder of
this section.
Currently, only automatic commercial
ice makers that produce cube type ice
with capacities between 50 and 2,500
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
6
1
0
1
pounds of ice per 24 hours must be
tested using the DOE test procedure to
show compliance with energy
conservation standards established in
EPACT 2005. Automatic commercial ice
makers with larger capacities, batch
type ice makers that produce other than
cube type ice, and continuous type ice
makers of any capacity have not been
subject to this rule. This rulemaking
would institute new testing
requirements for automatic commercial
batch type ice makers that produce cube
type ice with capacities between 2,500
and 4,000 pounds of ice per 24 hours,
batch type ice makers that produce
other than cube type ice with capacities
between 50 and 4,000 pounds of ice per
24 hours, and continuous type ice
makers with capacities between 50 and
4,000 pounds of ice per 24 hours. The
costs to manufacturers associated with
these test procedures were estimated to
range from $5,000 to $7,500 per tested
model. This estimate is based on input
from manufacturers and third-party
testing laboratories for completing a test
as specified by AHRI Standard 810–
2007 with Addendum 1 on automatic
commercial ice makers. Additional
testing requirements will be mandatory
for continuous type ice makers to assess
ice hardness, as discussed in the
following paragraph.
The additional test methods required
for continuous type ice makers will
standardize energy and water use with
respect to ice hardness. This test will
consist of performing an additional
PO 00000
Frm 00019
Fmt 4700
Sfmt 4700
Percentage of
small businesses
76
13
0
13
Cumulative
percentage
75
88
88
100
calorimetry test, as specified in
ASHRAE Standard 29–2009, normative
annex A. DOE estimates that performing
this test will require 2 additional hours
of laboratory time, including the time to
perform necessary calculations, per
unit. Costs associated with the
calorimetry test have been estimated by
DOE to equal approximately 10 percent
of the AHRI 810 test or $500 to $740.
These costs would not include those
associated with transportation,
assuming that the unit would be
analyzed at the same time as the
required AHRI 810 test. DOE estimates
that 28 percent of all automatic
commercial ice makers would be subject
to this additional test procedure. This
estimate was developed based on
publicly available listings of automatic
commercial ice makers (e.g., AHRI and
CEC databases) and manufacturer Web
sites.
The primary cost for small businesses
under this rulemaking would result
from the aforementioned additional
testing requirements. These costs were
applied to the number of existing
designs subject to testing requirements
outlined in this rulemaking, which DOE
estimated at 30 models (for all small
businesses combined) in the April 2011
NOPR. DOE based the April 2011 NOPR
estimate on an estimate of fundamental
ACIM individual model offerings,
consolidated into basic models based on
similar features. For example, DOE
estimated that each capacity of each
unique product line (typically
E:\FR\FM\11JAR1.SGM
11JAR1
1610
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
new models for testing). Thus, costs are
higher in the first year following
implementation of the new testing
requirements as existing models are
tested but decline in future years as the
requirements are applied only to new
models. Two scenarios were developed
to reflect the low- and high-end cost
estimates for each test presented
previously in this section. Based on
these assumptions, testing costs for
small businesses were estimated at $1.4
to $2.0 million in 2015 and $41,120 to
$60,858 in 2016 through 2019. DOE
presents the costs for the testing of all
of these models in Table IV.2. As
discussed below, however, DOE notes
that based on grouping of similar basic
models, the total number of models to
be tested is likely to be significantly
smaller.
In addition to testing costs, DOE
estimates an additional $24,572 in
review and filing costs over the 5-year
analysis time horizon. DOE bases its
estimate on the assumptions that it
would take an engineer 2 hours to
determined by SKU numbers)
represented a separate basic model that
was required to be certified. DOE
researched manufacturer catalogs and
publically available databases to
determine the number of unique
product lines and capacities
manufacturers offered to arrive at the
estimate of 30 basic models for all small
businesses.
Based on DOE’s review of public
comments in response to the April 2011
NOPR and a detailed discussion of
model characteristics with one small
manufacturer, the number of models
affected by these test procedures was
increased to 264 models for all small
manufacturers. This increase was based
on the number of different features
offered within each product line that
DOE did not account for in the April
2011 NOPR estimate, such as different
refrigerants. Further, DOE assumes that
each company would introduce a new
base model (8 new models for testing)
in each year of the 5-year (2015–2019)
analysis time horizon (for a total of 40
communicate with the testing
laboratory, review test results, prepare
adequate documentation, and file the
report. The average hourly salary for an
engineer completing these tasks is
estimated at $38.74.8 Fringe benefits are
estimated at 30 percent of total
compensation, which brings the hourly
costs to employers associated with
review and filing of reports to $55.34.9
The incremental costs incurred by
small businesses to implement the
requirements of this rulemaking are
summarized in Table IV.2. Total costs to
small businesses are estimated at $1.5 to
$2.3 million over the 5-year analysis
time horizon. The present value costs of
this rulemaking on small businesses are
estimated at $1.2 to $1.7 million, or
$144,989 to $213,477 per small
business, for an average annual cost of
$28,998–$42,695. Annual costs are
discounted using a 7-percent real
discount rate, as recommended in OMB
Circular A–94.
TABLE IV.2—ANNUAL COSTS OF COMPLIANCE FOR SMALL BUSINESSES (2015–2019)
Testing costs
Year
Low end
High end
.........................................................
.........................................................
.........................................................
.........................................................
.........................................................
$1,356,960
41,120
41,120
41,120
41,120
$2,008,301
60,858
60,858
60,858
60,858
Totals ................................................
1,521,440
2,251,731
Review/filing
costs
Total costs
Discounted costs
Low end
High end
Low end
High end
$21,916
664
664
664
664
$1,378,876
41,784
41,784
41,784
41,784
$2,030,217
61,522
61,522
61,522
61,522
$1,051,938
29,791
27,843
26,021
24,319
$1,548,843
43,864
40,995
38,313
35,806
24,572
1,546,012
2,276,303
1,159,912
1,707,820
Average Cost per Small Business ...................................................................................................................................
144,989
213,477
pmangrum on DSK3VPTVN1PROD with RULES
2015
2016
2017
2018
2019
DOE also estimated costs to small
businesses using CCE basic model
definitions, which allow manufacturers
to group individual models with
similar, but not exactly the same, energy
performance characteristics into basic
models for purposes of compliance with
DOE’s regulations. 76 FR at 12428–29
(March 7, 2011). DOE reviewed product
literature and manufacturer Web sites to
determine, on average, the number of
individual models that could be
grouped together into representative
basic models. DOE determined that, for
automatic commercial ice makers, an
average of eight individual models
could be grouped into basic models for
the purposes of compliance with DOE’s
energy conservation standards, thus
reducing the number of models that
would require testing from 264 to 33.
DOE’s CCE requirements also require
that each model be tested twice. Using
the provisions for basic model grouping
established in DOE’s CCE final rule,
DOE estimated the costs to small
businesses to be between $673,596 and
$994,332 over the 5-year analysis time
horizon. The present value costs of this
rulemaking on all small businesses
under this scenario are estimated at
$475,126 to $701,360, or $59,391 to
$87,670 per small business, for an
average annual cost of $11,878 to
$17,534.
The findings of the DOE analysis
suggest that small business
manufacturers of automatic commercial
ice makers would not be
disproportionally impacted by the test
procedure amendments, relative to their
competition. Testing procedures are
required for each base model and only
models produced by manufacturers that
are covered by this rule would be
required to be tested. DOE research
indicates that the small entities affected
by this regulation produce fewer
automatic commercial ice makers, on
average, when compared to larger
businesses. Small businesses
manufacture, on average, 264 individual
models and 33 basic models covered by
this rule, while large businesses
manufacture an average of 2,176
individual models and 272 basic
models. Thus, small businesses are
subject to fewer testing procedures, and
testing costs for large businesses are
estimated to be approximately 8.2 times
higher than costs for small businesses.
DOE has, therefore, concluded that large
and small entities would incur a
8 U.S. Department of Labor, Bureau of Labor
Statistics. National Occupational Employment and
Wage Estimates. 2009. Washington, DC.
9 U.S. Department of Labor, Bureau of Labor
Statistics. Employer Costs for Employee
Compensation—Management, Professional, and
Related Employees. 2010. Washington, DC.
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
PO 00000
Frm 00020
Fmt 4700
Sfmt 4700
E:\FR\FM\11JAR1.SGM
11JAR1
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
proportional distribution of costs
associated with the new testing
requirements.
DOE conducted an analysis to
measure the maximum testing cost
burden relative to the gross profits of
small manufacturers. The costs used in
this analysis are the total cost to small
businesses if they were to test each
individual model, as presented in Table
IV.2. DOE notes that these testing costs
could be reduced by grouping
individual models into basic models for
the purpose of certification with
existing energy conservation standards,
as explained above. The analysis
utilized financial data gathered from
other public sources to derive the
average annual gross profits of the small
businesses impacted by this rule. The
average industry gross profit margin was
estimated at 29.0 percent.10 The
annualized costs associated with this
rulemaking were then compared to
estimated gross profits to determine the
magnitude of the cost impacts of this
regulation on small businesses. Based
on this analysis, DOE estimates that the
total increase in testing burden amounts
to approximately 0.5 to 0.7 percent of
gross profit for the small manufacturers
affected by this rule. DOE further
estimates that the cost burden of the
testing procedures is equal to
approximately 0.1 to 0.2 percent of
average annual sales ($8.9 million 11)
per small entity affected by this
regulation. DOE concludes that these
values do not represent a significant
economic impact.
Based on the criteria outlined above,
DOE continues to certify that the test
procedure amendments would not have
a ‘‘significant economic impact on a
substantial number of small entities.’’
DOE has transmitted the certification
and supporting statement of factual
basis to the Chief Counsel for Advocacy
of the Small Business Administration
for review under 5 U.S.C. 605(b).
pmangrum on DSK3VPTVN1PROD with RULES
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of automatic
commercial ice makers must certify to
DOE that their equipment complies with
any applicable energy conservation
standards. In certifying compliance,
manufacturers must test their
equipment according to the DOE test
10 BizStats.
Free Business Statistics and Financial
Ratios. Industry Income-Expense Statements. (Last
accessed February 17, 2011.) .
11 Calculated based on data obtained from
https://www.manta.com and Dun and Bradstreet
reports.
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
procedure for automatic commercial ice
makers, including any amendments
adopted for the test procedure. DOE has
established regulations for the
certification and record-keeping
requirements for all covered consumer
products and commercial equipment,
including automatic commercial ice
makers. 76 FR 12422 (March 7, 2011).
The collection-of-information
requirement for the certification and
recordkeeping is subject to review and
approval by OMB under the Paperwork
Reduction Act (PRA). This requirement
has been approved by OMB under OMB
Control Number 1910–1400. Public
reporting burden for the certification is
estimated to average 20 hours per
response, including the time for
reviewing instructions, searching
existing data sources, gathering and
maintaining the data needed, and
completing and reviewing the collection
of information.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE amends its test
procedure for automatic commercial ice
makers. DOE has determined that this
rule falls into a class of actions that are
categorically excluded from review
under the National Environmental
Policy Act of 1969 (42 U.S.C. 4321 et
seq.) and DOE’s implementing
regulations at 10 CFR part 1021.
Specifically, this rule amends an
existing rule without affecting the
amount, quality, or distribution of
energy usage, and therefore will not
result in any environmental impacts.
Thus, this rulemaking is covered by
Categorical Exclusion A5 under 10 CFR
part 1021, subpart D, which applies to
any rulemaking that interprets or
amends an existing rule without
changing the environmental effect of
that rule. Accordingly, neither an
environmental assessment nor an
environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (Aug. 4, 1999), imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have Federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
PO 00000
Frm 00021
Fmt 4700
Sfmt 4700
1611
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have Federalism implications. On
March 14, 2000, DOE published a
statement of policy describing the
intergovernmental consultation process
it will follow in the development of
such regulations. 65 FR at 13735. DOE
examined this final rule and determined
that it will not have a substantial direct
effect on the States, on the relationship
between the national government and
the States, or on the distribution of
power and responsibilities among the
various levels of government. EPCA
governs and prescribes Federal
preemption of State regulations as to
energy conservation for the equipment
that is the subject of today’s final rule.
States can petition DOE for exemption
from such preemption to the extent, and
based on criteria, set forth in EPCA. (42
U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
E:\FR\FM\11JAR1.SGM
11JAR1
1612
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
review and determined that, to the
extent permitted by law, this final rule
meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA) requires
each Federal agency to assess the effects
of Federal regulatory actions on state,
local, and tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
regulatory action resulting in a rule that
may cause the expenditure by state,
local, and tribal governments, in the
aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of state,
local, and tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR at
12820; also available at https://
www.gc.doe.gov. DOE examined today’s
final rule according to UMRA and its
statement of policy and determined that
the rule contains neither an
intergovernmental mandate, nor a
mandate that may result in the
expenditure of $100 million or more in
any year, so these requirements do not
apply.
pmangrum on DSK3VPTVN1PROD with RULES
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being.
Today’s final rule will not have any
impact on the autonomy or integrity of
the family as an institution.
Accordingly, DOE has concluded that it
is not necessary to prepare a Family
Policymaking Assessment.
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 18, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). DOE has reviewed
today’s final rule under the OMB and
DOE guidelines and has concluded that
it is consistent with applicable policies
in those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB a Statement
of Energy Effects for any significant
energy action. A ‘‘significant energy
action’’ is defined as any action by an
agency that promulgated or is expected
to lead to promulgation of a final rule,
and that: (1) Is a significant regulatory
action under Executive Order 12866, or
any successor order; and (2) is likely to
have a significant adverse effect on the
supply, distribution, or use of energy; or
(3) is designated by the Administrator of
OIRA as a significant energy action. For
any significant energy action, the agency
must give a detailed statement of any
adverse effects on energy supply,
distribution, or use if the regulation is
implemented, and of reasonable
alternatives to the action and their
expected benefits on energy supply,
distribution, and use.
Today’s regulatory action is not a
significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
PO 00000
Frm 00022
Fmt 4700
Sfmt 4700
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; FEAA) Section 32 provides in
relevant part that, where a proposed
rule authorizes or requires use of
commercial standards, the NOPR must
inform the public of the use and
background of such standards. In
addition, section 32(c) requires DOE to
consult with the Attorney General and
the Chairman of the FTC concerning the
impact of the commercial or industry
standards on competition.
This final rule incorporates testing
methods contained in the following
commercial standards:
1. AHRI Standard 810–2007 with
Addendum 1, which supersedes AHRI
Standard 810–2003, ‘‘2007 Standard for
Performance Rating of Automatic
Commercial Ice Makers,’’ section 3,
‘‘Definitions,’’ section 4, ‘‘Test
Requirements,’’ and section 5, ‘‘Rating
Requirements’’ into 10 CFR 431.134(b);
and
2. ANSI/ASHRAE Standard 29–2009,
which supersedes ANSI/ASHRAE
Standard 29–1988 (RA 2005), ‘‘Method
of Testing Automatic Ice Makers,’’ 10
CFR 431.134(b) and (b)(2).
DOE has consulted with both the
Attorney General and the Chairman of
the FTC about the impact on
competition of using the methods
contained in these standards and has
received no comments objecting to their
use.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of today’s rule before its effective date.
The report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
List of Subjects in 10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation test
procedures, Incorporation by reference,
Reporting and recordkeeping
requirements.
E:\FR\FM\11JAR1.SGM
11JAR1
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
For the reasons set forth in the
preamble, DOE amends part 431 of title
10, Code of Federal Regulations to read
as follows:
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
§ 431.133 Materials incorporated by
reference.
1. The authority citation for part 431
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
2. Section 431.132 is amended by
adding in alphabetical order the
definitions of ‘‘batch type ice maker,’’
‘‘continuous type ice maker,’’ and ‘‘ice
hardness factor,’’ and revising the
definitions of ‘‘cube type ice’’ and
‘‘energy use’’ to read as follows:
■
§ 431.132 Definitions concerning
automatic commercial ice makers.
pmangrum on DSK3VPTVN1PROD with RULES
*
*
*
*
*
Batch type ice maker means an ice
maker having alternate freezing and
harvesting periods. This includes
automatic commercial ice makers that
produce cube type ice and other batch
technologies. Referred to as cubes type
ice maker in AHRI 810 (incorporated by
reference, see § 431.133).
Continuous type ice maker means an
ice maker that continually freezes and
harvests ice at the same time.
Cube type ice means ice that is fairly
uniform, hard, solid, usually clear, and
generally weighs less than two ounces
(60 grams) per piece, as distinguished
from flake, crushed, or fragmented ice.
Note that this conflicts and takes
precedence over the definition
established in AHRI 810 (incorporated
by reference, see § 431.133), which
indicates that ‘‘cube’’ does not reference
a specific size or shape.
Energy use means the total energy
consumed, stated in kilowatt hours per
one-hundred pounds (kWh/100 lb) of
ice stated in multiples of 0.1. For remote
condensing (but not remote compressor)
automatic commercial ice makers and
remote condensing and remote
compressor automatic commercial ice
makers, total energy consumed shall
include the energy use of the ice-making
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
mechanism, the compressor, and the
remote condenser or condensing unit.
*
*
*
*
*
Ice hardness factor means the latent
heat capacity of harvested ice, in British
thermal units per pound of ice (Btu/lb),
divided by 144 Btu/lb, expressed as a
percent.
*
*
*
*
*
■ 3. Section 431.133 is revised to read
as follows:
(a) General. We incorporate by
reference the following standards into
Subpart H of Part 431. The material
listed has been approved for
incorporation by reference by the
Director of the Federal Register in
accordance with 5 U.S.C. 552(a) and 1
CFR part 51. Any subsequent
amendment to a standard by the
standard-setting organization will not
affect the DOE regulations unless and
until amended by DOE. Material is
incorporated as it exists on the date of
the approval and a notice of any change
in the material will be published in the
Federal Register. All approved material
is available for inspection at the U.S.
Department of Energy, Office of Energy
Efficiency and Renewable Energy,
Building Technologies Program, 6th
Floor, 950 L’Enfant Plaza SW.,
Washington, DC 20024, (202) 586–2945,
or go to: https://www1.eere.energy.gov/
buildings/appliance_standards/. Also,
this material is available for inspection
at National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call (202) 741–6030
or go to https://www.archives.gov/
federal_register/code_of_federal_
regulations/ibr_locations.html.
Standards can be obtained from the
sources listed below.
(b) AHRI. Air-Conditioning, Heating,
and Refrigeration Institute, 2111 Wilson
Blvd., Suite 500, Arlington, VA 22201,
(703) 524–8800, ahri@ahrinet.org, or
https://www.ahrinet.org.
(1) AHRI Standard 810–2007 with
Addendum 1, (‘‘AHRI 810’’),
Performance Rating of Automatic
Commercial Ice-Makers, March 2011;
IBR approved for §§ 431.132 and
431.134.
(2) [Reserved].
(c) ASHRAE. American Society of
Heating, Refrigerating and Air-
PO 00000
Frm 00023
Fmt 4700
Sfmt 4725
Conditioning Engineers, Inc., 1791
Tullie Circle NE., Atlanta, GA 30329,
(404) 636–8400, ashrae@ashrae.org, or
https://www.ashrae.org.
(1) ANSI/ASHRAE Standard 29–2009,
(‘‘ANSI/ASHRAE 29’’), Method of
Testing Automatic Ice Makers,
(including Errata Sheets issued April 8,
2010 and April 21, 2010), approved
January 28, 2009; IBR approved for
§ 431.134.
(2) [Reserved].
4. Section 431.134 is revised to read
as follows:
■
§ 431.134 Uniform test methods for the
measurement of energy and water
consumption of automatic commercial ice
makers.
(a) Scope. This section provides the
test procedures for measuring, pursuant
to EPCA, the energy use in kilowatt
hours per 100 pounds of ice (kWh/100
lb ice) and the condenser water use in
gallons per 100 pounds of ice (gal/100
lb ice) of automatic commercial ice
makers with capacities between 50 and
4,000 pounds of ice per 24 hours.
(b) Testing and Calculations. Measure
the energy use and the condenser water
use of each covered product by
conducting the test procedures set forth
in AHRI 810, section 3, ‘‘Definitions,’’
section 4, ‘‘Test Requirements,’’ and
section 5, ‘‘Rating Requirements’’
(incorporated by reference, see
§ 431.133). Where AHRI 810 references
‘‘ASHRAE Standard 29,’’ ANSI/
ASHRAE Standard 29–2009
(incorporated by reference, see
§ 431.133) shall be used. All references
to cube type ice makers in AHRI 810
apply to all batch type automatic
commercial ice makers.
(1) For batch type automatic
commercial ice makers, the energy use
and condenser water use will be
reported as measured in this paragraph
(b), including the energy and water
consumption, as applicable, of the icemaking mechanism, the compressor,
and the condenser or condensing unit.
(2)(i) For continuous type automatic
commercial ice makers, determine the
energy use and condenser water use by
multiplying the energy consumption or
condenser water use as measured in this
paragraph (b) by the ice hardness
adjustment factor, determined using the
following equation:
E:\FR\FM\11JAR1.SGM
11JAR1
ER11JA12.048
Issued in Washington, DC, on December
20, 2011.
Kathleen B. Hogan,
Deputy Assistant Secretary, Energy Efficiency
and Renewable Energy.
1613
1614
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 / Rules and Regulations
(ii) Determine the ice hardness factor
by following the procedure specified in
the ‘‘Procedure for Determining Ice
Quality’’ in section A.3 of normative
annex A of ANSI/ASHRAE 29
(incorporated by reference, see
§ 431.133), except that the test shall be
conducted at an ambient air temperature
of 70 °F ± 1 °F, with an initial water
temperature of 90 °F ± 1 °F, and weights
shall be accurate to within ± 2 percent
of the quantity measured. The ice
hardness factor is equivalent to the
corrected net cooling effect per pound of
ice, line 19 in ANSI/ASHRAE 29 Table
A1, where the calorimeter constant used
in line 18 shall be that determined in
section A2 using seasoned, block ice.
[FR Doc. 2012–218 Filed 1–10–12; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF TRANSPORTATION
Federal Aviation Administration
14 CFR Part 25
[Docket No. FAA–2010–1193; Amdt. No. 25–
136]
RIN 2120–AJ80
Harmonization of Airworthiness
Standards for Transport Category
Airplanes—Landing Gear Retracting
Mechanisms and Pilot Compartment
View
Federal Aviation
Administration (FAA), DOT.
ACTION: Final rule.
AGENCY:
The Federal Aviation
Administration amends the
airworthiness standards for transport
category airplanes on landing gear
retracting mechanisms and the pilot
compartment view. For the landing gear
retracting mechanism, this rulemaking
adopts the 1-g stall speed as a reference
stall speed instead of the minimum
speed obtained in a stalling maneuver
and adds an additional requirement to
keep the landing gear and doors in the
correct retracted position in flight. For
the pilot compartment view, this
rulemaking revises the requirements for
pilot compartment view in precipitation
conditions. This action eliminates
regulatory differences between the
airworthiness standards of the U.S. and
the European Aviation Safety Agency
(EASA), without affecting current
industry design practices.
DATES: Effective March 12, 2012.
ADDRESSES: For information on where to
obtain copies of rulemaking documents
and other information related to this
final rule, see ‘‘How To Obtain
pmangrum on DSK3VPTVN1PROD with RULES
SUMMARY:
VerDate Mar<15>2010
12:38 Jan 10, 2012
Jkt 226001
Additional Information’’ in the
section of
this document.
FOR FURTHER INFORMATION CONTACT: For
technical questions concerning this
action, contact Mahinder Wahi, Federal
Aviation Administration, Propulsion
and Mechanical Systems Branch, ANM–
112, Transport Airplane Directorate,
Aircraft Certification Service, 1601 Lind
Avenue SW., Renton, WA 98057;
telephone (425) 227–1262; facsimile
(425) 227–1320, email
mahinder.wahi@faa.gov.
For legal questions about this
proposed rule, contact Doug Anderson,
FAA, Office of the Regional Counsel
(ANM–7), 1601 Lind Avenue SW.,
Renton, Washington 98057; telephone
(425) 227–2166; facsimile (425) 227–
1007; email Douglas.Anderson@faa.gov.
SUPPLEMENTARY INFORMATION:
SUPPLEMENTARY INFORMATION
Authority for This Rulemaking
The FAA’s authority to issue rules on
aviation safety is found in Title 49 of the
United States Code. Subtitle I, Section
106 describes the authority of the FAA
Administrator. Subtitle VII, Aviation
Programs, describes in more detail the
scope of the agency’s authority.
This rulemaking is promulgated
under the authority described in
Subtitle VII, Part A, Subpart III, Section
44701, ‘‘General requirements.’’ Under
that section, the FAA is charged with
promoting safe flight of civil aircraft in
air commerce by prescribing regulations
and minimum standards for the design
and performance of aircraft that the
Administrator finds necessary for safety
in air commerce. This regulation is
within the scope of that authority. It
prescribes new safety standards for the
design and operation of transport
category airplanes.
List of Abbreviations Frequently Used
in This Document
Term Definition
VS the stalling speed or the minimum
steady flight speed at which the airplane is
controllable.
VS1 the stalling speed or the minimum
steady flight speed obtained in a specific
configuration.
VSR reference stall speed and may not be
less than a 1-g stall speed.
VSR1 reference stall speed in a specific
configuration.
1-g stall speed minimum speed at which
the airplane can develop the usable
maximum lift force capable of supporting
the weight of the airplane.
List of Acronyms Frequently Used in
This Document
ALPA Airline Pilots Association
ˆ
ANAC Agencia Nacional de Aviacao Civil
¸˜
ARAC Aviation Rulemaking Advisory
Committee
PO 00000
Frm 00024
Fmt 4700
Sfmt 4700
EASA European Aviation Safety Agency
FAA Federal Aviation Administration
ICAO International Civil Aviation
Organization
JAA European Joint Aviation Authorities
NPRM Notice of Proposed Rulemaking
RFA Regulatory Flexibility Act
SBREFA Small Business Regulatory
Enforcement Fairness Act
I. Overview of Final Rule
This action harmonizes airworthiness
certification standards for landing gear
mechanisms and pilot compartment
view for transport category airplanes
with those of EASA. Harmonizing these
airworthiness standards reduces costs to
airplane manufacturers and operators
while retaining the level of safety.
II. Background
A. Statement of the Problem
This rulemaking results from an
agreement between the European Joint
Aviation Authorities (JAA), the
predecessor to EASA, and the FAA to
harmonize certain airworthiness
standards between the two authorities.
Differences between the regulations of
the FAA and foreign certification
authorities increase the cost and
complexity of certification without
contributing significantly to safety.
These rules result from the
recommendations of the Aviation
Rulemaking Advisory Committee,
through its Mechanical Systems
Harmonization Working Group
(MSHWG).
B. Summary of the NPRM
The FAA published a notice of
proposed rulemaking (NPRM), Docket
No. FAA–2010–1193; Notice No. 10–19
in the Federal Register on January 5,
2011 (76 FR 472). The NPRM proposed
to amend the standards for landing gear
retraction mechanism and pilot
compartment view to harmonize with
the corresponding EASA standards. The
proposed standards for landing gear
addressed reference stall speed, positive
means to keep the landing gear and
doors in the correct retracted position,
gear position indication, and protection
of equipment on the landing gear and in
the wheel well. The proposed standards
for pilot compartment view addressed
single failures of rain removal systems,
alternatives to the openable side
window requirement and certain
environmental conditions.
The comment period for the NPRM
ended on April 5, 2011.
C. General Overview of Comments
The FAA received comments from
Airbus, Boeing Company, Bombardier,
Cessna Aircraft Company, Embraer,
E:\FR\FM\11JAR1.SGM
11JAR1
Agencies
[Federal Register Volume 77, Number 7 (Wednesday, January 11, 2012)]
[Rules and Regulations]
[Pages 1591-1614]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2012-218]
========================================================================
Rules and Regulations
Federal Register
________________________________________________________________________
This section of the FEDERAL REGISTER contains regulatory documents
having general applicability and legal effect, most of which are keyed
to and codified in the Code of Federal Regulations, which is published
under 50 titles pursuant to 44 U.S.C. 1510.
The Code of Federal Regulations is sold by the Superintendent of Documents.
Prices of new books are listed in the first FEDERAL REGISTER issue of each
week.
========================================================================
Federal Register / Vol. 77, No. 7 / Wednesday, January 11, 2012 /
Rules and Regulations
[[Page 1591]]
DEPARTMENT OF ENERGY
10 CFR Part 431
[Docket No. EERE-2010-BT-TP-0036]
RIN 1904-AC38
Energy Conservation Program: Test Procedure for Automatic
Commercial Ice Makers
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: On April 4, 2011, the U.S. Department of Energy (DOE or the
Department) issued a notice of proposed rulemaking (NOPR) to amend the
test procedure for automatic commercial ice makers (ACIM). That NOPR
serves as the basis for today's action. This final rule amends the
current test procedure for automatic commercial ice makers. The changes
include updating the incorporation by reference of industry test
procedures to the most current published versions, expanding coverage
of the test procedure to all batch type and continuous type ice makers
with capacities between 50 and 4,000 pounds of ice per 24 hours,
standardizing test results based on ice hardness for continuous type
ice makers, clarifying the test methods and reporting requirements for
automatic ice makers designed to be connected to a remote compressor
rack, and discontinuing the use of a clarified energy use equation.
DATES: The effective date of this rule is February 10, 2012. The final
rule changes will be mandatory for equipment testing starting January
7, 2013. Representations either in writing or in any broadcast
advertisement respecting energy consumption of automatic commercial ice
makers must also be made using the revised DOE test procedure on
January 7, 2013.
The incorporation by reference of certain publications listed in
this final rule is approved by the Director of the Office of the
Federal Register as of February 10, 2012.
ADDRESSES: The docket is available for review at regulations.gov,
including Federal Register notices, public meeting attendee lists and
transcripts, comments, and other supporting documents/materials. All
documents in the docket are listed in the regulations.gov index.
However, not all documents listed in the index may be publicly
available, such as information that is exempt from public disclosure.
A link to the docket Web page can be found at: https://www1.eere.energy.gov/buildings/appliance_standards/commercial/automatic_ice_making_equipment.html. This Web page will contain a
link to the docket for this notice on the regulations.gov site. The
regulations.gov Web page will contain simple instructions on how to
access all documents, including public comments, in the docket. For
further information on how to review the docket, contact Ms. Brenda
Edwards at (202) 586-2945 or by email: Brenda.Edwards@ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Mr. Charles Llenza, U.S. Department of
Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Program, EE-2J, 1000 Independence Avenue SW., Washington,
DC 20585-0121. Telephone: (202) 586-2192. Email:
Charles.Llenza@ee.doe.gov.
Mr. Ari Altman, U.S. Department of Energy, Office of the General
Counsel, GC-71, 1000 Independence Avenue SW., Washington, DC 20585-
0121. Telephone: (202) 287-6307. Email: Ari.Altman@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final rule incorporates by reference
into Part 431 the following industry standards:
(1) Air Conditioning, Heating, and Refrigeration Institute (AHRI)
Standard 810-2007 with Addendum 1, ``Performance Rating of Automatic
Commercial Ice-Makers,'' March 2011; and
(2) American National Standards Institute (ANSI)/American Society
of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE)
Standard 29-2009, ``Method of Testing Automatic Ice Makers,''
(including Errata Sheets 1 and 2, issued April 8, 2010 and April 12,
2011), approved January 28, 2009.
Copies of AHRI standards can be obtained from the Air-Conditioning,
Heating, and Refrigeration Institute, 2111 Wilson Blvd., Suite 500,
Arlington, VA 22201, (703) 524-8800, ahri@ahrinet.org, or https://www.ahrinet.org.
Copies of ASHRAE standards can be purchased from the American
Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.,
1791 Tullie Circle NE., Atlanta, GA 30329, (404) 636-8400,
ashrae@ashrae.org, or https://www.ashrae.org.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Summary of the Final Rule
III. Discussion
A. Amendments to the Test Procedure
1. Update References to Industry Standards to Most Current
Versions
2. Expand Capacity Range to Larger Capacity Equipment
3. Include Test Methods for Continuous Type Ice Makers
a. Definitions and Referenced Industry Test Methods
b. Standardize Ice Hardness for Continuous Type Ice Makers
c. Ice Hardness Versus Ice Quality
d. Sub-Cooled Ice
e. Ice Hardness Testing of Batch Type Ice Makers
f. Variability of the Ice Hardness Measurement
g. Perforated Containers for Continuous Type Ice Makers
4. Clarify the Test Method and Reporting Requirements for Remote
Condensing Automatic Commercial Ice Makers
5. Discontinue Use of a Clarified Energy Rate Calculation
6. Test Procedure Compliance Date
B. Notice of Proposed Rulemaking Comment Summary and DOE
Responses
1. Test Method for Modulating Capacity Automatic Commercial Ice
Makers
2. Treatment of Tube Type Ice Machines
3. Quantification of Auxiliary Energy Use
4. Measurement of Storage Bin Effectiveness
5. Establishment of a Metric for Potable Water Used to Produce
Ice
6. Standardization of Water Hardness for Measurement of Potable
Water Used in Making Ice
7. Testing of Batch Type Ice Makers at the Highest Purge Setting
8. Consideration of Space Conditioning Loads
9. Burden Due to Cost of Testing
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
[[Page 1592]]
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
V. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III of the Energy Policy and Conservation Act (42 U.S.C.
6291, et seq.; ``EPCA'') sets forth a variety of provisions designed to
improve energy efficiency. (All references to EPCA refer to the statute
as amended through the Energy Independence and Security Act of 2007
(EISA 2007), Public Law 110-140 (Dec. 19, 2007)). Part C of Title III,
which was subsequently redesignated as Part A-1 in the U.S. Code for
editorial reasons (42 U.S.C. 6311-6317), establishes an energy
conservation program for certain industrial equipment. This includes
automatic commercial ice makers, the subject of today's rulemaking.
DOE's energy conservation program, established under EPCA, consists
essentially of four parts: (1) Testing; (2) labeling; (3) Federal
energy conservation standards; and (4) certification and enforcement
procedures. The testing requirements consist of test procedures that
manufacturers of covered equipment must use (1) as the basis for
certifying to DOE that their equipment complies with the applicable
energy conservation standards adopted under EPCA; and (2) for making
representations about the efficiency of those pieces of equipment.
Similarly, DOE must use these test requirements to determine whether
the equipment complies with relevant standards promulgated under EPCA.
(42 U.S.C. 6315(b), 6295(s), and 6316(a)) The current test procedure
for automatic commercial ice makers appears under title 10 of the Code
of Federal Regulations (CFR) part 431, subpart H.
EPCA prescribes that the test procedure for automatic commercial
ice makers shall be the Air-Conditioning and Refrigeration Institute
(ARI) Standard 810-2003, ``Performance Rating of Automatic Commercial
Ice-Makers.'' (42 U.S.C. 6314(a)(7)(A)) EPCA also provides that if ARI
Standard 810-2003 is revised, the Secretary of Energy (Secretary) shall
amend the DOE test procedure as necessary to be consistent with the
amended ARI Standard unless the Secretary determines, by rule, that to
do so would not meet the requirements for test procedures set forth in
EPCA. (42 U.S.C. 6314(a)(7)(B)) Because ARI Standard 810 has been
updated from the 2003 version, DOE must amend the DOE test procedure to
reflect these updates, unless doing so would not meet the requirements
for a test procedure, as set forth in EPCA. (42 U.S.C.
6314(a)(7)(B)(i))
In addition, EPCA prescribes energy conservation standards for
automatic commercial ice makers that produce cube type ice with
capacities between 50 and 2,500 pounds of ice per 24-hour period. (42
U.S.C. 6313(d)(1)) EPCA also requires the Secretary to review these
standards and determine, by January 1, 2015, whether amending the
applicable standards is technically feasible and economically
justified. (42 U.S.C. 6313(d)(3)) DOE is currently undertaking a
standards rulemaking (Docket No. EERE-2010-BT-STD-0037), concurrent
with this test procedure rulemaking, to determine if amended standards
are technically feasible and economically justified for automatic
commercial ice makers covered by the standards set in the Energy Policy
Act of 2005 (EPACT 2005). In the energy conservation standards
rulemaking, DOE is also proposing, under 42 U.S.C. 6313(d)(2), to adopt
standards for other types of ice makers that are not covered in 42
U.S.C. 6313(d)(1) and to expand the covered capacity range to ice
makers with capacities up to 4,000 pounds of ice per 24 hours. In this
final rule, DOE is amending the test procedure for automatic commercial
ice makers to be consistent with the expanded scope being considered in
the ACIM energy conservation standards rulemaking.
In addition, EPCA requires DOE to conduct an evaluation of each
class of covered equipment at least once every 7 years to determine
whether, among other things, to amend the test procedure for such
equipment. (42 U.S.C. 6314(a)(1)(A)) The review and amendment of the
test procedure for automatic commercial ice makers in this final rule
notice fulfills DOE's obligation under EPCA to evaluate the test
procedure for automatic commercial ice makers every 7 years. EPCA also
requires that if DOE determines that a test procedure amendment is
warranted, it must publish proposed test procedures and offer the
public an opportunity to present oral and written comments on them. (42
U.S.C. 6314(b))
B. Background
EPCA, as amended by EPACT 2005, prescribes that the test procedure
for automatic commercial ice makers shall be the ARI Standard 810-2003,
``Performance Rating of Automatic Commercial Ice-Makers.'' (42 U.S.C.
6314(a)(7)(A)) Pursuant to EPCA, on December 8, 2006, DOE published a
final rule (the 2006 en masse final rule) that, among other things,
adopted the test procedure specified in ARI Standard 810-2003, with a
revised method for calculating energy use. DOE adopted a clarified
energy use rate equation to specify that the energy use be calculated
using the entire mass of ice produced during the testing period,
normalized to 100 pounds of ice produced. 71 FR 71340, 71350 (Dec. 8,
2006). The DOE test procedure also incorporated by reference the ANSI/
ASHRAE Standard 29-1988 (Reaffirmed 2005) (ASHRAE Standard 29-1988 (RA
2005)), ``Method of Testing Automatic Ice Makers,'' as the method of
test.
Since the publication of the 2006 en masse final rule, ARI merged
with the Gas Appliance Manufacturers Association (GAMA) to form the
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) and
updated its ice maker test procedure to reflect changes in the
industry. The new test procedure, AHRI Standard 810-2007, amends the
previous test procedure, ARI Standard 810-2003, to:
1. Expand the capacity range of covered equipment to between 50 and
4,000 pounds of ice per 24 hours at standard rating conditions;
2. Provide definitions and specific test procedures for batch type
and continuous type ice makers; and
3. Provide a definition for ice hardness factor, which is the
fraction of frozen ice in the ice product of continuous type ice
machines.
The industry test procedure being considered in this rulemaking,
AHRI Standard 810-2007, references the previous ANSI/ASHRAE Standard
29-1988 (RA 2005). The current DOE test procedure also references ANSI/
ASHRAE Standard 29-1988 (RA 2005). However, ASHRAE updated its test
procedure in 2009 to ANSI/ASHRAE Standard 29-2009 to include provisions
for measuring the performance of batch type and continuous type ice
makers.\1\
---------------------------------------------------------------------------
\1\ ASHRAE has also issued two errata sheets to ANSI/ASHRAE
Standard 29-2009, issued April 8, 2010 and April 12, 2010,
respectively. These errata serve only to clarify equations that are
part of the ice hardness calculation described in normative annex A,
Table A1; they do not change the content or results of the test
procedure. In this document, all subsequent references to ``ANSI/
ASHRAE Standard 29-2009'' will refer to ANSI/ASHRAE Standard 29-
2009, including all errata presented in Errata Sheets 1 and 2.
---------------------------------------------------------------------------
[[Page 1593]]
In March 2011, AHRI published an addendum to AHRI Standard 810-
2007, AHRI Standard 810 with Addendum 1. This addendum revised the
definition of ``potable water use rate'' and added new definitions of
``purge or dump water'' and ``harvest water'' that more accurately
describe the water consumption of automatic commercial ice makers. This
change only affects measurement of the potable water use of automatic
commercial ice makers. Because the amended DOE test procedure adopted
in this final rule does not require the measurement of potable water,
this change does not impact the DOE test procedure for automatic
commercial ice makers.
EPCA requires that if DOE determines that a test procedure
amendment is warranted, DOE must publish proposed test procedures and
offer the public an opportunity to present oral and written comments on
them. (42 U.S.C. 6314(b)) In accordance with this requirement, DOE
published the proposed test procedure amendments in the ACIM test
procedure NOPR, which was published in the Federal Register on April 4,
2011. 76 FR 18428 (April 2011 NOPR). On April 29, 2011, DOE held a
public meeting (April 2011 NOPR public meeting) to discuss the
amendments proposed in the April 2011 NOPR and provide an opportunity
for interested parties to comment. DOE also received written comments
from interested parties regarding the proposed amendments to the test
procedure for automatic commercial ice makers and has considered both
the oral comments received at the public meeting and the written
comments, to the extent possible, when finalizing this final rule.
These comments and DOE's responses are presented in section III,
Discussion.
II. Summary of the Final Rule
This final rule amends the existing test procedure for automatic
commercial ice makers. Specifically, DOE is incorporating revisions to
the DOE test procedure that:
1. Update the industry test procedure references to AHRI Standard
810-2007 with Addendum 1 and ANSI/ASHRAE Standard 29-2009;
2. Expand the scope of the test procedure to include equipment with
capacities from 50 to 4,000 pounds of ice per 24 hours;
3. Provide test methods for continuous type ice makers and
standardize the measurement of energy and water use for continuous type
ice makers with respect to ice hardness;
4. Clarify the test method and reporting requirements for remote
condensing automatic commercial ice makers designed for connection to
remote compressor racks; and
5. Discontinue the use of a clarified energy use rate calculation
and instead calculate energy use per 100 pounds of ice as specified in
ANSI/ASHRAE Standard 29-2009.
These amendments make changes to the definitions set forth in 10
CFR 431.132 and to the current test procedures in 10 CFR 431.134.
The amended test procedure established in today's final rule will
become effective 30 days after publication in the Federal Register. DOE
believes the test procedure amendments adopted in today's final rule
will not alter the measured energy consumption and condenser water
consumption of any covered equipment. As such, for automatic commercial
ice makers for which energy conservation standards were set in EPACT
2005, use of the revised test procedure for showing compliance with
DOE's energy conservation standards will be required starting 360 days
after publication in the Federal Register. For equipment not covered by
the standards set forth in EPACT 2005, use of the amended test
procedure to show compliance with energy conservation standards will be
required on the compliance date of any energy conservation standards
established for that equipment. Consistent with EPCA, representations
either in writing or in any broadcast advertisement respecting energy
consumption of any automatic commercial ice makers covered under this
test procedure final rule will be required to be made based on the
amended test procedure starting 360 days after publication of this
final rule in the Federal Register. (42 U.S.C. 6314(d)(1)) For more
specific information on DOE's conclusion that the amended test
procedure will not affect the measured energy or water consumption of
covered equipment and further discussion of compliance dates, see the
DATES section and section III.A.6 of this document.
III. Discussion
Section III.A discusses all the revisions to the test procedure
incorporated in this final rule and discusses the test procedure
compliance date. This section also presents the comments received on
these topics during the April 2011 NOPR public meeting and in the
associated comment period and DOE's responses to them.
Responses to comments addressing topics other than test procedure
revisions adopted in this final rule appear in section III.B, which
provides responses to comments in the following subject areas:
1. Test Method for Modulating Capacity Automatic Commercial Ice Makers
2. Treatment of Tube Type Ice Machines
3. Quantification of Auxiliary Energy Use
4. Measurement of Storage Bin Effectiveness
5. Establishment of a Metric for Potable Water Used in Making Ice
6. Standardization of Water Hardness for Measurement of Potable Water
Used in Making Ice
7. Testing of Batch Type Ice Makers at the Highest Purge Setting
8. Consideration of Space Conditioning Loads
9. Burden Due to Cost of Testing
A. Amendments to the Test Procedure
Today's final rule contains the following amendments to the test
procedure in 10 CFR 431, subpart H.
1. Update References to Industry Standards to Most Current Versions
The current DOE test procedure for automatic commercial ice makers,
established in the 2006 en masse final rule, adopts ARI Standard 810-
2003 as the test procedure used to measure the energy consumption of a
piece of equipment to establish compliance with energy conservation
standards set in EPACT 2005. 71 FR at 71350 (Dec. 8, 2006). The DOE
test procedure also references ANSI/ASHRAE Standard 29-1988 (RA 2005).
Since publication of the 2006 en masse final rule, AHRI and ASHRAE
have published revised standards, namely AHRI Standard 810-2007 with
Addendum 1 and ANSI/ASHRAE Standard 29-2009 (including Errata Sheets 1
and 2). AHRI Standard 810-2007 with Addendum 1 and ANSI/ASHRAE Standard
29-2009 amend the previous test procedures by expanding the capacity
range to 4,000 pounds per day and providing for the testing of
continuous type ice makers. AHRI Standard 810-2007 with Addendum 1 and
ANSI/ASHRAE Standard 29-2009 are designed to be used together to test
automatic commercial ice makers. AHRI Standard 810-2007 with Addendum 1
specifies the standard rating conditions and provides relevant
definitions of equipment, scope, and calculated or measured values.
ANSI/ASHRAE Standard 29 specifies how to conduct the test procedure,
including the technical requirements and calculations.
[[Page 1594]]
In the April 2011 NOPR, DOE proposed to adopt AHRI Standard 810-
2007 and ANSI/ASHRAE Standard 29-2009 as the DOE test procedure. 76 FR
at 18431 (April 4, 2011). AHRI Standard 810-2007 with Addendum 1 was
not published in time for DOE to include it in the NOPR. At the April
2011 NOPR public meeting and in subsequent written comments, AHRI,
Manitowoc Ice (Manitowoc), Scotsman Industries (Scotsman), Follett
Corporation (Follett), and the Northwest Energy Efficiency Alliance
(NEEA) supported this proposal (AHRI, No. 0005 at p. 23; Manitowoc, No.
0009 at p. 1; Scotsman, No. 0010 at p. 1; Follett, No. 0008 at p. 1;
NEEA, No. 0013 at p. 2) \2\ Pacific Gas & Electric, Southern California
Edison, San Diego Gas and Electric, and Southern California Gas
Company, hereafter referred to as the California Investor Owned
Utilities (CA IOUs), submitted a joint comment that also supported
adopting AHRI Standard 810-2007 and ASHRAE Standard 29-2009. (CA IOUs,
No. 0011 at pp. 1-2) AHRI also recommended that DOE adopt AHRI standard
810-2007 with Addendum 1, pointing out that the addendum was added in
March 2011 and has new definitions for ``dump and purge water'' and
``harvest water.'' AHRI added that the addendum also clarifies how
potable water usage rate is calculated. (AHRI, No. 0015 at p. 1) DOE
did not receive any dissenting comments generally regarding reference
to the updated industry standards, nor regarding AHRI Standard 810-2007
with Addendum 1.
---------------------------------------------------------------------------
\2\ In the following discussion, comments will be presented
along with a notation in the form ``AHRI, No. 0005 at p. 23,'' which
identifies a written comment DOE received and included in the docket
of this rulemaking. DOE refers to comments based on when the comment
was submitted in the rulemaking process. This particular notation
refers to a comment (1) By AHRI, (2) in document number 0005 of the
docket (available at regulations.gov), and (3) appearing on page 23.
---------------------------------------------------------------------------
DOE reviewed AHRI 810-2007 with Addendum 1 and determined that this
revised version of the AHRI Standard 810-2007 test procedure meets the
EPCA requirements for a test procedure in that it is reasonably
designed to produce test results that reflect the energy use of covered
equipment during a representative cycle of use and is not unduly
burdensome to conduct. (42 U.S.C. 6314(a)(2))
DOE believes AHRI Standard 810-2007 with Addendum 1 and ANSI/ASHRAE
Standard 29-2009 are the most up-to-date and commonly used test
procedures for automatic commercial ice makers in the industry and are
the most appropriate to cover all equipment included in the scope of
this rulemaking. Thus, in today's final rule, DOE is updating the DOE
test procedure for automatic commercial ice makers to reference the
most current versions of the industry test procedures, AHRI Standard
810-2007 with Addendum 1 and ANSI/ASHRAE Standard 29-2009.
2. Expand Capacity Range to Larger Capacity Equipment
DOE's existing test procedure references ARI Standard 810-2003,
which limits the testing provisions to a capacity range of 50 to 2,500
pounds of ice per 24 hours. In AHRI Standard 810-2007, AHRI expanded
the capacity range to include automatic commercial ice makers having a
harvest capacity between 50 and 4,000 pounds of ice per 24 hours at
standard rating conditions due to changes in the products offered by
manufacturers. Specifically, some manufacturers offer larger capacity
units that exceed the capacity range of the previous test procedure.
AHRI's expansion of the capacity range does not affect the way ice
makers are tested; it only provides for the same test procedure to be
applied to larger capacity ice makers.
Consistent with referenced industry test procedures, DOE proposed
in the April 2011 NOPR to expand the capacity range of the DOE test
procedure to include automatic commercial ice makers with harvest rates
between 50 and 4,000 pounds of ice per 24 hours. 76 FR at 18431 (April
4, 2011). In response to this proposal, Manitowoc, AHRI, Follett,
Scotsman, the CA IOUs, and NEEA commented that 50 to 4,000 pounds per
day was an appropriate capacity range for this equipment. (Manitowoc,
No. 0009 at p. 1; AHRI, No. 0005; Follett, No. 0008 at p. 1; Scotsman,
No. 0010 at p. 1; CA IOUs, No. 0011 at pp. 1-2; NEEA, No. 0013 at p. 1)
Manitowoc further commented that there are some industrial applications
of ice makers, at airports or other venues with very high ice
consumption, but that larger capacity industrial-scale equipment was
already inherently more efficient. (Manitowoc, No. 0005 at p. 26) NEEA
commented that it is inclined to agree that equipment with capacities
greater than 4,000 pounds of ice per day need not be included in the
scope of coverage because, while these types of machines can probably
be rated using the test procedure, environmental chamber issues would
impose a potentially significant burden on manufacturers who are not so
equipped. NEEA also agreed with Manitowoc that machines of capacities
greater than 4,000 pounds per day are inherently at least a little more
energy efficient per pound of ice produced than similar smaller
machines. (NEEA, No. 0013 at pp. 1-2) AHRI added that ice makers
producing more than 4000 pounds of ice per 24 hours are usually used in
industrial applications that are outside the scope of this rulemaking,
as justified by the EPACT 2005, which gives DOE the authority to
develop energy conservation standards for automatic commercial ice
makers only. (AHRI, No. 0015 at p. 2)
DOE agrees with commenters that 4,000 pounds of ice produced per a
24 hour period is a reasonable maximum capacity limit for automatic
commercial ice makers. Consequently, DOE is establishing in this final
rule the applicable capacity range of the test procedure for automatic
commercial ice makers as the same capacity range established in AHRI
810-2007 with Addendum 1, namely 50 to 4,000 pounds of ice per 24
hours.
3. Include Test Methods for Continuous Type Ice Makers
In the April 2011 NOPR, DOE proposed including test methods as
defined in AHRI Standard 810-2007 and ANSI/ASHRAE Standard 29-2009 for
continuous type ice makers, as well as an additional method to scale
their energy consumption and water consumption with respect to the
latent heat capacity contained in the ice compared to the latent heat
capacity of the same mass of completely frozen ice. 76 FR at 18432
(April 4, 2011). The following sections discuss DOE's specific
proposals, comments submitted by interested parties on these proposals,
DOE's responses, and the amendments DOE is adopting in today's final
rule.
a. Definitions and Referenced Industry Test Methods
AHRI Standard 810-2007 with Addendum 1 and ANSI/ASHRAE Standard 29-
2009 have provisions that allow for the testing of continuous type ice
makers. The previous versions of these standards, ARI Standard 810-2003
and ANSI/ASHRAE Standard 29-1988 (RA 2005), as referenced in the
current DOE test procedure, do not include a method for testing
continuous type ice makers. The revised ANSI/ASHRAE Standard 29-2009
adopts definitions for a ``continuous type ice maker'' and a ``batch
type ice maker.'' A continuous type ice maker is defined as an ice
maker that continually freezes and harvests ice at the same time.
Continuous type ice makers primarily produce flake and nugget ice. A
batch type ice maker is defined as an ice maker that has alternate
freezing and harvesting periods, including machines
[[Page 1595]]
that produce cube type ice, tube type ice, and fragmented ice. AHRI
Standard 810-2007 with Addendum 1 adopts the same definition for a
continuous type ice maker, but refers to ice makers that have alternate
freezing and harvesting periods as ``cube type ice makers.'' The AHRI
Standard 810-2007 definition further clarifies that in this definition
the word ``cube'' does not refer to the specific shape or size of ice
produced. Because of this, ANSI/ASHRAE Standard 29-2009 includes the
statement that batch type ice makers are also referred to as cube type
ice makers.
In the April 2011 NOPR, DOE proposed to refer to an ice maker with
alternate freezing and harvesting periods as a ``batch type ice
maker,'' so that it is not confused with an ice maker that produces
only cube type ice. DOE believes that referring to this type of ice
maker as a ``cube type ice maker'' could be confusing, since not all
batch type ice makers produce ice that fits the ``cube type ice''
definition established in the 2006 en masse final rule. 71 FR at 71372
(Dec. 8, 2006). Rather, batch type ice makers include, but are not
limited to, cube type ice makers. DOE wishes to establish this
differentiation because ice makers that produce cube type ice with
capacities between 50 and 2,500 pounds of ice per 24 hours are
currently covered by energy conservation standards that are established
in EPCA, while batch type ice makers that produce other than cube type
ice and cube type ice makers with capacities between 2,500 and 4,000
pounds of ice per 24 hours are not currently covered by DOE energy
conservation standards. In the April 2011 NOPR (76 FR at 18444 (April
4, 2011)), DOE proposed adding definitions to 10 CFR 431.132 for
``batch type ice maker,'' which would refer to ice makers that
alternate freezing and harvesting periods, and ``continuous type ice
maker, '' which would refer to ice makers that continuously freeze and
harvest at the same time.
In addition to these definitions, DOE proposed to adopt AHRI
Standard 810-2007 as the referenced DOE test procedure, including
referencing ANSI/ASHRAE Standard 29-2009 as the method of test. 76 FR
at 18432 (April 4, 2011). This would expand the current DOE test
procedure to provide a method for testing continuous type ice makers,
in addition to batch type ice makers.
At the April 2011 NOPR public meeting and in written comments, both
energy efficiency advocates and manufacturers agreed that continuous
type ice makers should be included in the standards. (Follett, No. 0008
at p. 1; Manitowoc, No. 0009 at p. 1; Scotsman, No. 0010 at p. 1; CA
IOUs, No. 0011 at pp. 1-2; NEEA, No. 0013 at p. 1) The CA IOUs and
Manitowoc added that the coverage of continuous type equipment is
important because continuous type machines represent up to 20 percent
of the total market based on energy use today and continue to grow in
market share; thus, establishing a test procedure in this rulemaking
and corresponding energy conservation standards for these equipment
types would ensure that significant energy savings are captured. (CA
IOUs, No. 0011 at p. 2; Manitowoc, No. 0009 at p. 1)
DOE agrees with commenters that it is logical and appropriate to
include test procedures for continuous type ice makers in this test
procedure revision. In today's final rule, DOE is adopting definitions
and test procedures for batch type and continuous type ice makers. The
test procedure for testing continuous type ice makers will be used in
conjunction with any potential energy conservation standards for
automatic commercial ice makers that produce flake or nugget ice.
To remove any uncertainty regarding the current applicability of
standards for ice makers that produce cube type ice with capacities
between 50 and 2,500 pounds per 24 hours, DOE is slightly modifying the
proposed definition for batch type ice makers, as well as adding
language to the definition for cube type ice and scope in the final
rule. Specifically, DOE is removing the clarification of AHRI's
definition of cube type ice maker in the definition of batch type ice
maker, specifying that where there is inconsistency between AHRI and
DOE's definitions of cube type ice, the DOE definition takes
precedence, and noting that all references to cube type ice makers in
AHRI Standard 810-2007 shall apply to all batch type automatic
commercial ice makers only. DOE believes this removes, to the extent
possible, any potential ambiguity regarding the nomenclature and
coverage of batch type ice makers that produce cube type ice and batch
type ice makers that produce other than cube type ice (such as
fragmented ice makers) in the DOE test procedure. DOE is also updating
the definition for continuous type ice makers to be consistent with
that adopted in AHRI Standard 810-2007 with Addendum 1 and ANSI/ASHRAE
Standard 29-2009.
b. Standardize Ice Hardness for Continuous Type Ice Makers
Continuous type ice makers typically produce ice that is not
completely frozen. This means that there is some liquid water content
in the total mass of ice product produced by continuous type ice
makers. The specific liquid water content can be described in terms of
ice hardness or ice quality and is usually quantified in terms of
percent of completely frozen ice in the total ice product. Ice quality
can vary significantly across different continuous ice makers, from
less than 70 percent to more than 100 percent. DOE understands that the
percentage of liquid water in the product of continuous ice makers is
directly related to the measured energy consumption of these machines,
since more refrigeration is required to freeze a greater percentage of
the ice product.
To provide comparability and repeatability of results, in the April
2011 NOPR, DOE proposed to standardize the energy consumption and
condenser water use measurements of continuous ice makers based on the
ratio of enthalpy reduction of the water/ice product achieved in the
machine (incoming water enthalpy less ice product enthalpy) to the
enthalpy reduction that would be achieved if the ice were produced at
32 [deg]F with no liquid water content. DOE proposed to base the
adjustment on the ice quality of continuous type ice makers, as
measured using the ``Procedure for Determining Ice Quality'' in section
A.3 of normative annex A in ANSI/ASHRAE Standard 29-2009. DOE proposed
that the calorimeter constant, defined and measured using ANSI/ASHRAE
Standard 29-2009, be used to calculate an ``ice quality adjustment
factor.'' This factor is a ratio of the refrigeration required to cool
water from 70 [deg]F to 32 [deg]F and freeze all of the water compared
to the refrigeration required to cool 70 [deg]F water to the mixture of
frozen ice and liquid water produced by the ice maker under test. The
reported (adjusted) energy consumption would be equal to the ice
quality adjustment factor multiplied by the energy consumption per 100
pounds of ice measured using ANSI/ASHRAE Standard 29-2009. The
condenser water use would be adjusted in the same way. 76 FR at 18432-
33 (April 4, 2011). DOE did not propose similar adjustment for the
harvest rate.
Interested parties, including Manitowoc, Howe Corporation (Howe),
and NEEA, generally supported this approach. (Manitowoc, No. 0005 at p.
41; Howe, No. 0017 at pp. 2-3; NEEA, No. 0013 at p. 2) However,
Scotsman commented that normalization of energy and water consumption
with respect to ice hardness could result in selection of higher energy
consumption products by the consumer because when a consumer fills a
glass or cooler with ice, they do so based on the volume of space the
ice occupies, not the cooling power it provides. Scotsman added that,
in rating
[[Page 1596]]
ice machines based on the total weight of the product of ice and water
rather than just the ice content, the consumer gets a more accurate
measurement of the amount of energy consumed to produce the nugget of
ice that is in the cup or cooler, while ``normalizing'' to 32 [deg]F
ice with no water content gives a more accurate measure of the energy
used to produce a certain amount of cooling power contained in the ice,
but is not representative of how the ice is typically used. (Scotsman,
No. 0010 at p. 1) Scotsman also asked if DOE intended to require ice
hardness reporting. (Scotsman, No. 0010 at p. 1)
DOE maintains that, because energy and condenser water consumption
are directly related to ice hardness, measurement and normalization
with respect to ice hardness is necessary to compare equipment from
different manufacturers accurately. In response to Scotsman's concern,
DOE notes that this test method will not affect the availability of
automatic commercial ice makers that produce lower quality ice; it will
simply provide a method by which automatic commercial ice maker energy
consumption and condenser water use results can be compared to a
baseline ice quality. DOE acknowledges that, if consumers value total
pounds of ice rather than the cooling that can be provided by the ice,
the unadjusted energy and water consumption data may provide a better
indication of the energy use per quantity valued by the customer.
However, DOE believes that scaling energy and water consumption with
respect to ice quality will result in more comparable values for
determining compliance with DOE's energy conservation standards. The
harvest rate of these ice makers will not be adjusted with respect to
ice hardness. In addition, DOE is not considering changes to the
certification requirements in this test procedure rulemaking. Thus, in
this final rule, DOE is adopting the provisions proposed in the April
2011 NOPR to scale the energy and water consumption measured in ANSI/
ASHRAE Standard 29-2009 based on a ratio of the refrigeration required
to cool water from 70 [deg]F to 32 [deg]F and freeze all of the water
compared to the refrigeration required to cool 70 [deg]F water to the
mixture of frozen ice and liquid water produced by the ice maker under
test.
c. Ice Hardness Versus Ice Quality
As discussed above, DOE in the April 2011 NOPR proposed that the
calorimeter constant, determined using ANSI/ASHRAE Standard 29-2009, be
used to determine an ``ice quality adjustment factor.'' 76 FR at 18433
(April 4, 2011). Scotsman, Manitowoc, and Hoshizaki all commented that
the term ``ice quality'' should instead be referred to as ``ice
hardness,'' as defined in AHRI Standard 810-2007. (Scotsman, No. 0005
at p. 38; Manitowoc, No. 0005 at p. 40; Hoshizaki, No. 0005 at pp. 44-
45) Howe countered that ``ice hardness,'' as defined in the AHRI
standard, should not be used to replace the proposed ``ice quality''
used in the ASHRAE standard because the term ``ice hardness'' is
confusing and is a misstatement. (Howe, No. 0017 at p. 8)
In response to comments from interested parties, DOE is using the
term ``ice hardness'' in place of the term ``ice quality'' throughout
this rule, since it is defined in AHRI Standard 810-2007 and seems to
be the preferred term within the industry. Specifically, DOE is
defining the ``ice hardness adjustment factor,'' as opposed to the
previously defined ``ice quality adjustment factor,'' which will be
calculated in order to scale energy consumption and condenser water
use. DOE acknowledges Howe's comment that this may cause confusion, but
contends that the terms ``ice hardness'' and ``ice quality'' are used
interchangeably in the industry, and understands the two terms to have
the same meaning.
d. Sub-Cooled Ice
Just as ice makers that produce less than 100 percent hardness ice
will use less energy than ice makers that produce 100 percent 32 [deg]F
ice, ice makers that produce sub-cooled ice, or higher than 100 percent
hardness ice, require more energy to produce a given mass of ice
product. At the April 2011 NOPR public meeting and in subsequent
written comments, Manitowoc, Howe, and NEEA all commented that the
adjustment of energy and water consumption with respect to ice hardness
should be allowed for sub-cooled ice as well as low hardness ice.
(Manitowoc, No. 0005 at p. 42; Howe, No. 0005 at pp. 45-46; NEEA, No.
0013 at p. 2)
DOE agrees with interested parties that the energy content of sub-
cooled ice should also be adjusted with respect to 32 [deg]F ice of 100
percent hardness. However, DOE notes that the measurement of ice
hardness is not limited to low hardness ice and that quantification of
the ice hardness for sub-cooled ice is possible using the adopted
procedure for ice hardness normalization. Rather, the adopted test
procedure already accounts for the additional cooling associated with
production of sub-cooled ice. DOE clarifies that ice hardness testing
of ice makers that produce sub-cooled ice can be conducted using the
ice hardness test procedure adopted in today's final rule and that the
energy use and condenser water use measurements for ice makers that
produce sub-cooled ice can and should be adjusted using the ice
hardness adjustment factor.
e. Ice Hardness Testing of Batch Type Ice Makers
AHRI Standard 810-2007 with Addendum 1 and ANSI/ASHRAE Standard 29-
2009 both specify that ice hardness testing is only to be performed for
continuous type ice makers. In the April 2011 NOPR, DOE also proposed
that measurement and scaling of energy and water consumption values
based on ice hardness only be required for continuous type ice makers.
76 FR at 18433 (April 4, 2011).
In written comments submitted in response to the April 2011 NOPR,
Follett recommended that the ice quality adjustment be applied to batch
type ice makers as well as continuous type. (Follett, No. 0008 at p. 1)
DOE agrees with Follett that there would be value in requiring
batch machines to perform the ice hardness measurement and scale their
energy consumption accordingly. Testing and normalizing energy and
water consumption values for ice hardness would account for the
additional energy consumption of batch type commercial ice makers that
produce sub-cooled ice and would allow for the most consistent results
across all ice makers. In addition, some batch type automatic
commercial ice makers may produce cube type ice with some liquid water
content. DOE believes that this would account for the additional energy
consumption of batch type commercial ice makers that produce sub-cooled
ice and would allow for the most consistent results across all ice
makers. However, DOE does not have any data or information regarding
the existence of batch type ice makers that vary from 100 percent
hardness or the extent to which their hardness departs from 100
percent. DOE believes that, for most batch type ice makers, the ice
hardness will be nearly 100 percent and any departure from 100 percent
will be within the statistical accuracy of the ice hardness
measurement. Lacking sound information, DOE is unable to justify the
additional burden associated with requiring ice hardness measurement
and scaling of energy and water consumption for batch type ice makers
at this time. Thus, in today's final rule DOE specifies that only
continuous type ice makers are required to measure ice hardness and
adjust the energy
[[Page 1597]]
consumption and condenser water use based on the ice hardness
measurement.
f. Variability of the Ice Hardness Measurement
DOE is aware of concerns regarding the accuracy and repeatability
of the ice hardness test. These concerns were voiced during the U.S.
Environmental Protection Agency (EPA) ENERGY STAR[supreg] discussions
with interested parties regarding revisions to the ENERGY STAR
specification for automatic commercial ice makers.\3\ In written
comments received during the comment period that followed the
publication of the April 2011 NOPR, Scotsman recommended the tolerance
for the ice hardness factor be 5 rather than
5 percent, as test data Scotsman has indicates that 5
percent is too tight when accounting for water mineral content, which
can have a substantial impact on ice hardness. (Scotsman, No. 0010 at
pp. 2-3)
---------------------------------------------------------------------------
\3\ Hoffman, M. Personal Communication. Consortium for and
Energy Efficiency, Boston, MA. Letter to Christopher Kent, U.S.
Environmental Protection Agency, regarding written comments
submitted in response to the ENERGY STAR Commercial Ice Machines
Version 2 Draft 1 Specification, June 11, 2011. https://
www.energystar.gov/ia/partners/prod_development/revisions/
downloads/commercial_ice_machines/ACIM_Draft_1_V_2.0_
Comments__-CEE.pdf.
---------------------------------------------------------------------------
As part of this rulemaking and the ongoing energy conservation
standards rulemaking (Docket No. EERE-2010-BT-STD-0037), DOE conducted
testing of ice makers, including running the ice hardness tests. In
conducting this testing, DOE wished to better understand the source of
any variability in ANSI/ASHRAE Standard 29-2009 normative annex A.
Specifically, DOE wished to discern the variability, if any, in the
measurement of ice hardness that could be attributed specifically to
inaccuracy in the test method, rather than inherent variability in the
hardness of ice produced by a given ice maker. DOE determined that the
fundamental test procedure established in ANSI/ASHRAE Standard 29-2009
is sound. However, DOE believes that several areas of the test
procedure are unclear and could be misinterpreted. This includes
confusing nomenclature and references in normative annex A, as well as
specification of the specific temperatures, weights, and tolerances to
be used in the test procedure.
DOE believes ANSI/ASHRAE Standard 29-2009 normative annex A
specifies two procedures:
1. Section A2, ``Procedure,'' which specifies the calibration of
the calorimeter device and the calculation of the calorimeter constant
for the device; and
2. Section A3, ``Procedure for Determining Quality of Harvested
Ice,'' which is used to determine the ice hardness of a given ice
maker's ice product, defined as the ``ice hardness factor'' in AHRI
Standard 810-2007 with Addendum 1.
DOE also believes there is confusion in determining the ice
hardness factor of a given ice sample using section A3. AHRI Standard
810-2007 with Addendum 1 specifies that the ice hardness factor is the
latent heat capacity of ice harvested in British thermal units per
pound (Btu/lb), as defined in ANSI/ASHRAE Standard 29, Table A1, line
15, divided by 144 Btu/lb, multiplied by 100, presented as a percent.
DOE believes that this value should also be multiplied by the
calorimeter constant, line 18 of Table A1, as determined in section A2
at the beginning of that day's tests. This is equivalent to line 19 in
ANSI/ASHRAE Standard 29-2009 Table A1, although it is not clear that
the calibration constant used in line 18 is to be determined with
seasoned block ice during the calibration procedure. To clarify this
procedure, DOE will require that the ice hardness factor, as defined in
AHRI Standard 810-2007 with Addendum 1, be calculated, except that it
shall reference the corrected net cooling effect per pound of ice, line
19 of ANSI/ASHRAE Standard 29-2009 Table A1, and the calorimeter
constant used in line 18 shall be that determined in section A2 using
seasoned, block ice.
The ice hardness factor will be used to determine an adjustment
factor based on the energy required to cool ice from 70 [deg]F to 32
[deg]F and produce a given amount of ice, as shown in the following:
[GRAPHIC] [TIFF OMITTED] TR11JA12.045
The measured energy consumption per 100 pounds of ice and the
measured condenser water consumption per 100 pounds of ice, as
determined using ANSI/ASHRAE Standard 29-2009, will be multiplied by
the ice hardness adjustment factor to yield the adjusted energy and
condenser water consumption values, respectively. These values will be
reported to DOE to show compliance with the energy conservation
standard.
DOE explored the variation in both the calibration procedure and
the procedure for determining an ice maker's ice hardness factor in
laboratory testing. DOE hypothesized the following variables, which
could contribute to variability in the test procedure:
How to ensure that ice is ``seasoned''
Thermal conductivity and specific heat of bucket
Frequency and timing of calibration
Vigorousness of ice stirring
Location of temperature sensor in the ice bucket
Variation in ambient conditions
Difference between water temperature and ambient air
temperature
Time allowed between production of ice and initiation of
ice hardness test
DOE conducted testing to determine the significance of these
variables on the calorimeter constant result. DOE believes
standardization and tolerances are important because otherwise there is
no indicator of how close a measurement must be to the specified value
in order to comply with the test procedure.
In section A2 of ANSI/ASHRAE Standard 29-2009, which specifies the
calibration procedure for the calorimeter, DOE found that the type of
``seasoned'' ice used significantly affected the calibration of the
device, but that variation of all other factors examined did not have a
significant effect provided they were maintained within a reasonable
range. DOE believes ``seasoned'' ice is ice that is 32 [deg]F
throughout with as little entrained water as possible. A single block
of seasoned ice is used to minimize the amount of water on the surface
of the ice due to the low surface area to volume ratio. If multiple,
smaller cubes are used, and seasoned in the same manner, it is much
more difficult to ensure that the surface liquid is removed so that a
calorimeter
[[Page 1598]]
constant of less than 1.02 can be obtained.
DOE believes the calorimeter constant should be viewed as a
calibration constant that is representative of the specific heat of the
calorimeter device. This calorimeter constant shall not be greater than
1.02 when determined with seasoned block ice. This limit establishes
that the calorimetry procedure is being performed correctly and all
equipment is accurately calibrated.
ANSI/ASHRAE Standard 29-2009 normative annex A specifies the
temperature difference between the air and water, the weight of water,
and the weight of ice, but does not specify acceptable tolerances for
any of these parameters. For example, ANSI/ASHRAE Standard 29-2009
normative annex A does not specify an initial water temperature or
ambient air temperature. Instead, the initial water temperature is
specified as 20[emsp14] [deg]F above room temperature. Also, this
temperature differential does not have an associated tolerance.
Similarly, the weights to determine the calorimeter constant in section
A2, 30 pounds of water and 6 pounds of ice, do not have specified
tolerances.
DOE found that changes in the ambient temperature, the temperature
difference between the air and water, the weight of ice, and the weight
of water did not affect the calorimeter constant significantly.
However, DOE still must specify tolerances in order to ensure
compliance with the test procedure. As such, DOE assumes the tolerances
specified in section 6 of ANSI/ASHRAE Standard 29-2009, ``Test
Methods,'' also apply to the normative annex, namely water and air
temperature shall be within 1 [deg]F of the specified value and the
measured weights of ice and water shall be within 2
percent of the quantity measured. DOE believes that the ice hardness
measurement should be conducted at the same ambient temperature as the
other testing, namely 70 [deg]F. This will increase the accuracy and
repeatability of the measurement. DOE believes that a temperature
differential of 20 [deg]F is appropriate, as it minimizes heat flow
into and out of the water. DOE does not believe maintaining 70 [deg]F
1 [deg]F ambient air temperature and obtaining 90 [deg]F
1 [deg]F initial water temperature will be burdensome for
manufacturers as it is commensurate with the ambient requirements
already called for in the energy consumption and condenser water
consumption test, and 90 [deg]F water is easily attainable from a
standard water heater. As such, DOE is clarifying in today's final rule
that normative annex A of ANSI/ASHRAE Standard 29-2009 shall be
performed at 70 [deg]F 1 [deg]F ambient air temperature
with an initial water temperature of 90 [deg]F 1 [deg]F
and weights shall be accurate to within 2 percent of the
quantity measured.
With these changes and assumptions, DOE was able to produce a
repeatable calorimeter constant measurement of less than 1.02 when
testing using seasoned ice. While there may be variations in ice
hardness inherent to the machine, for given hardness of ice, DOE was
able to produce ice hardness results that agree within 1.3 percent.
In response to Scotsman's comment regarding tolerances of the ice
hardness factor, as defined in AHRI Standard 810-2007 with Addendum 1,
DOE believes that 5 percent variability for a given basic
model should be sufficient given the data DOE has collected on ice
hardness measurements. DOE does not have data to validate the need for
or support the development of a different tolerance for the ice
hardness of continuous type ice makers. The variance on the ice
hardness factor is only relevant to the extent that it impacts the
calculation of energy consumption or condenser water use. With respect
to the reported energy and condenser water use, manufacturers must meet
DOE's certification, compliance, and enforcement (CCE) regulations for
automatic commercial ice makers, which established the relevant
sampling plans and tolerances for the certified ratings of energy and
water consumption values. 76 FR 12422 (March 7, 2011).
In summary, DOE believes there is sufficient accuracy and precision
in the test procedure for determining ice hardness prescribed in ANSI/
ASHRAE Standard 29-2009 normative annex A, with the exception that the
test shall be conducted at an ambient air temperature of 70 [deg]F
1 [deg]F, with an initial water temperature of 90 [deg]F
1 [deg]F, and weights shall be accurate to within 2 percent of the quantity measured. DOE believes adding these
specifications and tolerances will allow for greater repeatability and
standardization without significant additional burden on manufacturers.
All other potential sources of variability were found to not
significantly affect the calculated ice hardness.
g. Perforated Containers for Continuous Type Ice Makers
As mentioned previously, continuous type ice makers produce ice
that is not 100 percent frozen and contains some liquid water. In the
current industry test procedures, a non-perforated container is used to
capture the ice product so that all of the ice/water mixture is
included in the harvest rate and the ice hardness measurement.
At the April 2011 NOPR public meeting, Howe commented that the
container that is used for continuous ice should be a perforated
container rather than a solid container to remove chilled water that is
not usable ice from the test procedure process. (Howe, No. 0005 at p.
48) Howe noted that, beyond beverage dispensing, there is no useful
application for the cooled liquid water content of low hardness ice.
(Howe, No. 0005 at p. 56) Scotsman and Hoshizaki commented that when
consumers use ice, they usually do so based on volume of both ice and
water, so there is value in both the water and the ice portion.
(Scotsman, No. 0005 at p. 39; Hoshizaki, No. 0005 at p. 45) Manitowoc
provided the example of low quality ice being useful in beverage
dispensers and packing fish. (Manitowoc, No. 0005 at pp. 55-56)
In response to Howe's suggestion that perforated containers be used
for continuous type ice makers, Scotsman commented that it may not be
practical to use a perforated container to capture continuous ice
because the liquid water is infused in the ice and it takes a long time
for it to drain out, and the ice would melt over that period.
(Scotsman, No. 0005 at pp. 50-51) Hoshizaki noted that with a
perforated container the size of the perforations would need to be
defined because very small bits of ice, called ``dust ice,'' may fall
through the perforations, causing a loss of good quality ice.
(Hoshizaki, No. 0005 at p. 51) Hoshizaki added that the calorimetry
test already accounts for the differences between low hardness ice and
high hardness ice. (Hoshizaki, No. 0005 at pp. 51-52) Manitowoc agreed
with Hoshizaki with respect to the calorimetry test being sufficient to
differentiate low hardness and high hardness ice. (Manitowoc, No. 0005
at p. 52) NEEA commented that a perforated basket should not be
required for continuous type ice makers because only a fraction of the
product that is not fully hardened (chilled water) will escape the
matrix of the hardened product in a reasonable period. In addition,
NEEA commented that this would introduce an unfortunate degree of test
complexity and variability in the results and that any improvement in
the product accounting should be worth this additional complexity and
variability. (NEEA, No. 0013 at p. 2)
DOE believes that, as Manitowoc, Scotsman, and Hoshizaki stated,
there is clear value and customer utility in the liquid water content
of low hardness ice and that this should be measured as part
[[Page 1599]]
of the ice product when determining the harvest rate. DOE also believes
that the proposed procedure for adjusting energy and water consumption
measurements with respect to ice hardness, defined in section
III.A.3.b, is sufficient to describe the differences between ice with
different amounts of water content. Further, if a perforated container
were used for testing continuous type ice makers, this would not be
representative of the ``ice product'' consumers receive and expect. DOE
is not requiring testing of continuous type ice makers with a
perforated container in today's final rule and instead is maintaining
the industry-accepted method of testing continuous type ice makers with
a non-perforated container to measure harvest rate and test for ice
hardness.
4. Clarify the Test Method and Reporting Requirements for Remote
Condensing Automatic Commercial Ice Makers
EPCA establishes energy conservation standards for two types of
remote condensing automatic commercial ice makers: (1) Remote
condensing (but not remote compressor) and (2) remote condensing and
remote compressor. (42 U.S.C. 6313(d)(1)) Remote condensing (but not
remote compressor) ice makers are sold and operated with a dedicated
remote condenser that is in a separate section from the ice-making
mechanism and compressor. Remote condensing and remote compressor
automatic commercial ice makers may be operated with a dedicated remote
condensing unit or connected to a remote compressor rack. Units
designed for connection to a compressor rack may also be sold with
dedicated condensing units, but some rack-connection units are sold
only for rack connection, without a dedicated refrigeration system. The
energy use of such equipment is often reported without including the
compressor or condenser energy use, since manufacturers generally do
not have a compressor rack at their disposal for testing purposes. In
the April 2011 NOPR, DOE proposed that remote condensing ice makers
that are designed to be used with a remote condensing rack would be
tested with a sufficiently sized dedicated remote condensing unit. This
approach was proposed to ensure that ratings for such equipment
represent all of the energy use incurred by such machines for making
ice, including the compressor and condenser energy use. 76 FR at 18433-
34 (April 4, 2011).
Howe, Manitowoc, NEEA, Follett, CA IOUs, and the Natural Resources
Defense Council (NRDC) all agreed with DOE's proposal to test remote
condensing ice makers designed to be connected to a remote condensing
rack using dedicated remote condensing units and reporting the energy
consumption of the ice-making mechanism, condenser, and compressor.
(Howe, No. 0005 at p. 63; Manitowoc, No. 0005 at p. 64; NEEA, No. 0005
at p. 64; Follett, No. 0008 at p. 1; CA IOUs, No. 0011 at p. 2; NRDC,
No. 0012 at p. 1) Earthjustice and NRDC both recommended that DOE
provide clear guidance on how to select a remote condensing unit to
pair with a given ice maker for such a test. (Earthjustice, No. 0005 at
p. 75; NRDC, No. 0012 at p. 1) However, the CA IOUs and NEEA commented
that, given that ice production performance is closely tied to the
refrigerant system specifications, as manifested in the ice-making
head, manufacturers will likely select compressor/condenser components
that are properly matched to the requirements of the balance of the
system, since any significant deviation from this would likely change
ice production performance and adversely affect the energy performance
rating of the system. (CA IOUs, No. 0011 at p. 2; NEEA, No. 0013 at pp.
2-3) NEEA suggested that one possible guideline for selecting the
balance-of-system components might simply be to require that the ice-
making head be tested with the compressor/condenser components that
would be shipped with it if sold with a dedicated condenser; however,
NEEA also commented that this is a minor issue. (NEEA, No. 0013 at pp.
2-3)
Hoshizaki stated that, generally, a rack unit ice machine is
similar in construction to other ice machines that are designed to be
paired with a remote condensing unit, but that is not necessarily the
case every time. (Hoshizaki, No. 0005 at p. 67) Hoshizaki continued
that it does not have a condensing unit designed for use with its
largest rack unit machine and it would have to develop such a
condensing unit to test the ice maker as proposed. (Hoshizaki, No. 0005
at pp. 67-68) Scotsman stated that it also manufactures products that
are meant to be connected to rack systems for which it does not offer a
dedicated condensing unit, and that it would be problematic for
Scotsman to develop a companion condensing unit for it. Scotsman added
that such a rating would be arbitrary because it would not represent
what was actually sold. (Scotsman, No. 0005 at pp. 72-73) Scotsman
recommended that only the power of the ice-making mechanism should be
reported for units that do not have matched dedicated condensing units,
because reporting power for the condensing units for those machines
would require manufacturers to either design and build or purchase a
condenser that would never be offered for sale. (Scotsman, No. 0010 at
p. 2) Manitowoc