Energy Conservation Program: Test Procedures for Walk-In Coolers and Walk-In Freezers, 21580-21612 [2011-8690]
Download as PDF
21580
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Part 431
[Docket No. EERE–2008–BT–TP–0014]
RIN 1904–AB85
Energy Conservation Program: Test
Procedures for Walk-In Coolers and
Walk-In Freezers
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
On January 4, 2010, the U.S.
Department of Energy (DOE) issued a
notice of proposed rulemaking (January
2010 NOPR) to establish new test
procedures for walk-in coolers and
walk-in freezers (WICF or walk-ins). On
September 9, 2010, DOE issued a
supplemental notice of proposed
rulemaking (September 2010 SNOPR) to
propose changes to the test procedures
that it proposed in the NOPR. Those
proposed rulemakings serve as the basis
for today’s action. DOE is issuing a final
rule that establishes new test procedures
for measuring the energy efficiency of
certain walk-in cooler and walk-in
freezer components including panels,
doors, and refrigeration systems. These
test procedures will be mandatory for
product testing to demonstrate
compliance with energy standards that
DOE is establishing in a separate, but
concurrent rulemaking, and for
representations starting 180 days after
publication. This final rule incorporates
by reference industry test procedures
that, along with calculations established
in the rule, can be used to measure the
energy consumption or performance
characteristics of certain components of
walk-in coolers and walk-in freezers.
Additionally, the final rule clarifies the
definitions of ‘‘Display door,’’ ‘‘Display
panel,’’ ‘‘Door,’’ ‘‘Envelope,’’ ‘‘K-factor,’’
‘‘Panel,’’ ‘‘Refrigerated,’’ ‘‘Refrigeration
system,’’ ‘‘U-factor,’’ ‘‘Automatic door
opener/closer,’’ ‘‘Core region,’’ ‘‘Edge
region,’’ ‘‘Surface area,’’ ‘‘Rating
condition,’’ and ‘‘Percent time off’’ as
applicable to walk-in coolers and walkin freezers.
DATES: The effective date of this rule is
May 16, 2011. The final rule changes
will be mandatory for product testing
starting October 12, 2011.
The incorporation by reference of
certain publications listed in this rule
was approved by the Director of the
Federal Register on May 16, 2011.
ADDRESSES: The public may review
copies of all materials related to this
rulemaking at the U.S. Department of
Energy, Resource Room of the Building
srobinson on DSKHWCL6B1PROD with RULES3
SUMMARY:
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
Technologies Program, 950 L’Enfant
Plaza, SW., Suite 600, Washington, DC
(202) 586–2945, between 9 a.m. and
4 p.m., Monday through Friday, except
Federal holidays. Please contact Ms.
Brenda Edwards at the above telephone
number, or by e-mail at
Brenda_Edwards@ee.doe.gov, for
additional information regarding
visiting the Resource Room.
Docket: The docket is available for
review at regulations.gov, including
Federal Register notices, framework
documents, public meeting attendee
lists and transcripts, comments, and
other supporting documents/materials.
All documents in the docket are listed
in the regulations.gov index. However,
not all documents listed in the index
may be publicly available, such as
information that is exempt from public
disclosure.
A link to the docket web page can be
found at: https://www1.eere.energy.gov/
buildings/appliance_standards/
commercial/wicf.html. This web page
will contain a link to the docket for this
notice on the regulations.gov site. The
regulations.gov web page will contain
simple instructions on how to access all
documents, including public comments,
in the docket.
FOR FURTHER INFORMATION CONTACT:
Mr. Charles Llenza, U.S. Department of
Energy, Office of Energy Efficiency
and Renewable Energy, Building
Technologies Program, EE–2J, 1000
Independence Avenue, SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–2192. E-mail:
Charles.Llenza@ee.doe.gov.
Mr. Michael Kido, U.S. Department of
Energy, Office of the General Counsel,
GC–71, 1000 Independence Avenue,
SW., Washington, DC 20585–0121.
Telephone: (202) 586–8145. E-mail:
Michael.Kido@hq.doe.gov or Ms.
Elizabeth Kohl, U.S. Department of
Energy, Office of the General Counsel,
GC–71, 1000 Independence Avenue,
SW., Washington, DC 20585–0121.
Telephone: (202) 586–7796. E-mail:
Elizabeth.Kohl@hq.doe.gov.
This final
rule incorporates by reference into
subpart R of Title 10, Code of Federal
Regulations, part 431 (10 CFR part 431),
the following industry standards:
(1) AHRI 1250 (I–P)–2009, ‘‘2009
Standard for Performance Rating of
Walk-In Coolers and Freezers,’’
approved 2009.
(2) ASTM C1363–05, ‘‘Standard Test
Method for Thermal Performance of
Building Materials and Envelope
Assemblies by Means of a Hot Box
Apparatus,’’ approved May 1, 2005.
SUPPLEMENTARY INFORMATION:
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
(3) DIN EN 13164:2009–02, ‘‘Thermal
insulation products for buildings—
Factory made products of extruded
polystyrene foam (XPS)—Specification,’’
approved February 2009.
(4) DIN EN 13165:2009–02, ‘‘Thermal
insulation products for buildings—
Factory made rigid polyurethane foam
(PUR) products—Specification,’’
approved February 2009.
(5) NFRC 100–2010[E0A1],
‘‘Procedure for Determining Fenestration
Product U-factors,’’ approved 2010.
Copies of ASTM standards can be
obtained from ASTM International, 100
Barr Harbor Drive, West Conshohocken,
PA 19428–2959, (610) 832–9585, or
https://www.astm.org.
Copies of AHRI standards can be
obtained from AHRI. Air-Conditioning,
Heating and Refrigeration Institute, 2111
Wilson Boulevard, Suite 500, Arlington,
VA 22201, (703) 600–0366, or https://
www.ahrinet.org.
Copies of DIN EN standards can be
obtained from CEN. European
Committee for Standardization (French:
Norme or German: Norm), Avenue
Marnix 17, B–1000 Brussels, Belgium,
Tel: + 32 2 550 08 11, Fax: + 32 2 550
08 19 or https://www.cen.eu.
Copies of NFRC standards can be
obtained from NFRC. National
Fenestration Rating Council, 6305 Ivy
Lane, Ste. 140, Greenbelt, MD 20770,
(301) 589–1776, or https://www.nfrc.org.
You can also view copies of these
standards at the U.S. Department of
Energy, Resource Room of the Building
Technologies Program, 950 L’Enfant
Plaza, SW., 6th Floor, Washington, DC
20024, (202) 586–2945, between 9 a.m.
and 4 p.m., Monday through Friday,
except Federal holidays.
Table of Contents
I. Authority and Background
II. Summary of the Final Rule
III. Discussion
A. Overall Approach: Component-Based
Testing
1. Test Metrics
2. Responsibility for Testing and
Compliance
3. Basic Model
B. Test Procedures for Envelope
Components
1. Definition of Envelope
2. Heat Transfer Through Panels
3. Energy Use of Doors
4. Heat Transfer via Air Infiltration
5. Electrical Components
C. Test Procedures for Refrigeration
Systems
1. Definition of Refrigeration System
2. Refrigeration Test Procedure: AHRI 1250
(I–P)–2009
3. Alternative Efficiency Determination
Method
D. Other Issues—Definition of Walk-In
Cooler or Freezer
E:\FR\FM\15APR3.SGM
15APR3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
srobinson on DSKHWCL6B1PROD with RULES3
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
1. Statement of the Need for, and
Objectives of, the Rule
2. Summary of the Significant Issues
Raised by the Public Comments, DOE’s
Response to These Issues, and Any
Changes Made in the Proposed Rule as
a Result of Such Comments
3. Description and Estimated Number of
Small Entities Regulated
4. Description and Estimate of Compliance
Requirements and Description of Steps
To Minimize the Economic Impact on
Small Entities
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
N. Approval of the Office of the Secretary
I. Authority and Background
Title III of the Energy Policy and
Conservation Act (42 U.S.C. 6291–6317;
‘‘EPCA’’ or, ‘‘the Act’’) sets forth a variety
of provisions designed to improve
energy efficiency. (All references to
EPCA refer to the statute as amended
through the Energy Independence and
Security Act of 2007 (EISA 2007), Public
Law 110–140 (Dec. 19, 2007)). Part C of
Title III (42 U.S.C. 6311–6317), which
was subsequently redesignated as Part
A–1 for editorial reasons, establishes an
energy conservation program for certain
industrial equipment. This includes
walk-in coolers and walk-in freezers, the
subject of today’s notice. (42 U.S.C.
6311(1), (20), 6313(f), and 6314(a)(9))
Under EPCA, this program consists
essentially of three parts: (1) Testing, (2)
labeling, and (3) Federal energy
conservation standards. The testing
requirements consist of test procedures
that manufacturers of covered products
or equipment must use (1) as the basis
for certifying compliance with the
applicable energy conservation
standards adopted under EPCA, and (2)
for making representations about the
efficiency of those products. Similarly,
DOE must use these test requirements to
determine whether the products comply
with any relevant standards
promulgated under EPCA.
Section 312 of the Energy
Independence and Security Act of 2007
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
(‘‘EISA 2007’’) amended EPCA by adding
certain equipment to this energy
conservation program, including walkin coolers and walk-in freezers
(collectively ‘‘walk-in equipment,’’
‘‘walk-ins,’’ or ‘‘WICF.’’). (42 U.S.C.
6311(1), (20), 6313(f), and 6314(a)(9)) As
amended by EISA 2007, EPCA requires
DOE to establish new test procedures to
measure the energy use of walk-in
coolers and walk-in freezers. (42 U.S.C.
6314(a)(9)(B)(i)) The new test
procedures for WICF equipment are the
subject of this rulemaking. EPCA also
directs DOE to publish performancebased standards and promulgate
labeling requirements (42 U.S.C.
6313(f)(4)(A) and 42 U.S.C. 6315(e),
respectively). These actions will be
covered in separate rulemakings.
In the notice of proposed rulemaking
published January 4, 2010 (January 2010
NOPR or, in context, NOPR), DOE
proposed to establish test procedures to
measure the energy efficiency of walkin coolers and freezers. 75 FR 186. DOE
identified several issues in its proposal
based on the public comments
submitted in response to the January
2010 NOPR and further research. These
issues included: (1) The proposed
definition of a walk-in cooler or freezer
with regards to the upper temperature
limit; (2) the proposal to create test
procedures for the envelope and
refrigeration system of a walk-in cooler
or freezer; (3) the proposal to group
walk-in envelopes and refrigeration
systems with essentially identical
construction methods, materials, and
components into a single basic model;
and (4) the proposed calculation
methodology for determining the energy
consumption of units within the same
basic model. 75 FR 186, (Jan. 4, 2010).
On March 1, 2010, DOE held a public
meeting to receive comments, data, and
information on the January 2010 NOPR.
Through their comments, interested
parties raised significant issues and
suggested changes to the proposed test
procedures. DOE determined that some
of these comments warranted further
consideration and published a
supplemental notice of proposed
rulemaking on September 9, 2010
(September 2010 SNOPR or, in context,
SNOPR). 75 FR 55068. DOE received 22
written comments on the September
2010 SNOPR. This final rule addresses
comments from the January 2010 NOPR
that were not addressed in the
September 2010 SNOPR and comments
received on the September 2010
SNOPR.
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
21581
General Test Procedure Rulemaking
Process
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered equipment.
EPCA provides that test procedures
‘‘shall be reasonably designed to
produce test results which reflect energy
efficiency, energy use and estimated
annual operating costs of a type of
industrial equipment (or class thereof)
during a representative average use
cycle as determined by the Secretary [of
Energy], and shall not be unduly
burdensome to conduct.’’ (42 U.S.C.
6314(a)(2))
Additionally, EPCA notes that if the
procedure determines estimated annual
operating costs, the procedure ‘‘shall
provide that such costs shall be
calculated from measurements of energy
use in a representative average use cycle
(as determined by the Secretary), and
from representative average-unit costs of
the energy needed to operate such
equipment during such cycle.’’ (42
U.S.C. 63114(a)(3)) Further, the statute
provides that DOE ‘‘shall provide
information to manufacturers of covered
equipment respecting representative
average unit costs of energy.’’ Id.
With respect to today’s rulemaking,
the test procedure DOE is prescribing
today is a new test procedure. Today’s
rule establishes a comprehensive testing
regime to ensure minimum levels of
performance by applying the
component-based approach detailed in
EISA 2007. The separate but concurrent
energy conservation standards
rulemaking for walk-in coolers and
walk-in freezers will be based on the
performance of walk-in coolers and
walk-in freezers as measured by the test
procedure set forth in this final rule.
II. Summary of the Final Rule
Today’s final rule establishes a new
test procedure for measuring the energy
efficiency of walk-in cooler and walk-in
freezer equipment. The test procedure is
essentially composed of tests for the
principal components that make up a
walk-in: Panels, doors, and refrigeration.
Testing individual components of walkin coolers and walk-in freezers is
simpler and less burdensome to
manufacturers than testing an entire
walk-in. In this test procedure, DOE also
provides a method for calculating the
energy use of an entire envelope, or the
efficiency of a refrigeration system,
based on the results of the component
tests.
The test procedure incorporates by
reference the industry test procedures
ASTM C1363–05, ‘‘Standard Test
E:\FR\FM\15APR3.SGM
15APR3
21582
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
srobinson on DSKHWCL6B1PROD with RULES3
Method for Thermal Performance of
Building Materials and Envelope
Assemblies by Means of a Hot Box
Apparatus,’’DIN EN 13164:2009–02,
‘‘Thermal insulation products for
buildings—Factory made products of
extruded polystyrene foam (XPS)—
Specification,’’ DIN EN 13165:2009–02,
‘‘Thermal insulation products for
buildings—Factory made rigid
polyurethane foam (PUR) products—
Specification,’’ NFRC 100–2010[E0A1],
‘‘Procedure for Determining Fenestration
Product U-factors,’’ and AHRI 1250 (I–
P)–2009, ‘‘2009 Standard for
Performance Rating of Walk-In Coolers
and Freezers.’’
Concurrently, DOE is undertaking an
energy conservation standards
rulemaking to address the statutory
requirement to establish performance
standards for walk-in equipment by
2012. (42 U.S.C. 6313(f)(4)(A)) DOE will
use this test procedure in the concurrent
process of evaluating potential
performance standards for the
equipment. After the compliance date of
the performance standards, this walk-in
cooler and walk-in freezer test
procedure, along with any future
statistical sampling plans that may be
adopted, must be used by manufacturers
to determine compliance with the
standards, and by DOE to ascertain
compliance with the standards in any
enforcement action. Moreover, once any
final test procedure is effective, any
representation of the energy use of walkin equipment or components must
reflect the results of testing that
equipment using the test procedure.
III. Discussion
In this section, DOE describes the
overall approach it followed in
developing today’s test procedure for
walk-in cooler and freezer equipment,
including envelope components and
refrigeration systems. The following
section also addresses issues raised by
interested parties, which consisted of
the following entities:
• Manufacturers: American Panel,
Craig Industries, CrownTonka, Heatcraft
Refrigeration Products (Heatcraft), Hill
Phoenix, International Cold Storage
(ICS), Kysor Panel Systems (Kysor
Panel), Manitowoc, Master-Bilt, Owens
Corning, Nor-Lake, ThermalRite,
Thermo-Kool, and Zero Zone;
• Material suppliers: Carpenter
Company (Carpenter);
• Trade associations: AHRI, Center
for the Polyurethanes Industry (CPI);
• Utility companies: Pacific Gas &
Electric Company (PG&E), Southern
California Edison (SCE), Sacramento
Municipal Utility District (SMUD), and
San Diego Gas and Electric (SDG&E);
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
• Advocacy groups: Appliance
Standards Awareness Project (ASAP),
Alliance to Save Energy (ASE),
American Council for an EnergyEfficient Economy (ACEEE), Natural
Resources Defense Council (NRDC),
Northeast Energy Efficiency
Partnerships (NEEP), and Northwest
Energy Efficiency Alliance (NEEA);
• Other parties: Oak Ridge National
Laboratory (ORNL), and the Small
Business Administration (SBA).
A. Overall Approach: Component-Based
Testing
In the framework document, DOE
contemplated developing a single test
for an entire walk-in cooler or freezer.
See https://www1.eere.energy.gov/
buildings/appliance_standards/
commercial/pdfs/
wicf_framework_doc.pdf. However,
feedback from interested parties
indicated that a single test procedure for
the entire WICF would not be practical
because many walk-ins are assembled
on site with components from different
manufacturers, which would make onsite testing infeasible. DOE then
proposed in the January 2010 NOPR and
September 2010 SNOPR to develop
separate tests for the envelope and
refrigeration system of a walk-in, which
in aggregate would represent the
performance of the entire walk-in (75 FR
186, 191 (Jan. 4, 2010) and 75 FR 55068,
55070 (Sept. 9, 2010)). DOE proposed to
have one metric for the refrigeration
system, which would be an efficiency
metric, and one metric for the envelope,
which would be an energy use metric.
The envelope metric would account for
electrical use of envelope components,
as well as any energy used by the
refrigeration system to reject the heat
contributed by conduction, infiltration,
and other heat sources. In this way, DOE
intended to capture the energy impact of
components, such as panels, that do not
themselves consume electricity.
DOE received comments on the
September 2010 SNOPR from interested
parties stating that the walk-in cooler
and walk-in freezer main components
could be further broken down into their
own constituent components: panels
and doors of envelopes and unit coolers
and condensing units of refrigeration
systems. Commenters explained that all
of these components could be produced
by separate manufacturers and then
assembled into a complete walk-in.
Because of this situation, it would be
difficult to determine who should test
the walk-in envelope, the refrigeration
system, or both. It would also be
difficult to determine who would be
best positioned to ensure the walk-in
cooler or freezer complied with an
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
energy conservation standard. DOE
acknowledges these and similar
concerns from the stakeholders.
Based on the information provided by
commenters and DOE’s own research,
DOE has determined that a componentbased approach would address the
unique challenges posed in regulating
the energy efficiency performance of
walk-in envelopes. As noted above,
these challenges include the fact that
walk-in units are frequently assembled
using components made by multiple
manufacturers, and walk-in installers
may not be equipped to test all the
components that comprise a walk-in.
These factors indicate that a componentbased approach would not only help
ensure compliance with whatever
energy conservation standards that DOE
sets, but also reduce the overall testing
burden on the manufacturers, including
small businesses who are involved in
producing walk-in units, either in full or
in part.
Moreover, DOE notes that the
adoption of such an approach is
consistent with the component-based
approach that Congress took when it
enacted EISA 2007. Thus, DOE is
adopting a component-level approach
for this rule and discusses the specific
component metrics in greater detail in
section III.A.1.
1. Test Metrics
As stated previously, DOE initially
proposed separate test procedures for
envelopes and refrigeration systems of
walk-ins along with different test
metrics for each. The metric for the
refrigeration system would be an
efficiency metric, and the metric for the
envelope would be an energy use metric
that would account for the electrical use
of envelope components and the energy
used by the refrigeration system to reject
the heat contributed by conduction,
infiltration, and other heat sources. To
account for different sizes of envelopes,
DOE further proposed that the result of
the envelope test procedure should be a
normalized energy use metric—the total
energy use divided by the external
surface area of the envelope (energy use
per square foot).
Several interested parties disagreed
with the proposed metrics. NEEA stated
that regulating walk-in coolers and
walk-in freezers on the basis of annual
energy use would not accurately
estimate actual energy use, and
therefore such estimates would be
misleading for almost all installed
systems. NEEA suggested using an
overall U-value for the entire envelope
and a spreadsheet that calculates the
overall U-factor of a walk-in by
weighted area. (NEEA, No. 0061.1 at
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
p. 1 and 9; NEEA, No. 0061.2 at p. 1)
(In this and subsequent citations, the
document number refers to the number
of the comment in the Docket for the
DOE rulemaking on test procedures for
walk-in coolers and freezers, Docket No.
EERE–2008–BT–TP–0014; and the page
references refer to the place in the
document where the statement
preceding appears.) NRDC also
disagreed with the annual energy use
metric because of the number of
assumptions that would be required and
the potential to confuse customers.
(NRDC, No. 0064.1 at p. 7) NRDC further
stated that normalizing energy use to the
surface area would be unusual and may
not be useful. (NRDC, No. 0064.1 at p.
2) NEEA suggested that the envelope
metric should be a U-factor (which is a
characterization of the heat loss
performance). (NEEA, No. 0061.1 at p.
7) A comment submitted jointly by SCE,
SDG&E, PG&E, and SMUD, hereafter
referred to as the Joint Utilities,
suggested an area-based conductance
metric for the envelope that would
consider both opaque and transparent
surfaces. (The Joint Utilities, No. 0059.1
at p. 2) NRDC also suggested a metric for
refrigeration systems that would
encompass the total equivalent warming
impact and measure the heat loads from
refrigeration systems impacting a
building’s heating, ventilation, and air
conditioning (HVAC) system. (NRDC,
No. 0064.1 at p. 8) A comment
submitted jointly by ACEEE, ASAP,
ASE, NRDC, NEEP, and NEEA on the
September 2010 SNOPR (hereafter
referred to as The Joint SNOPR
comment) stated that the energy
conservation standard for envelopes
should be the overall heat gain (Uoverall) with separate standards for
walk-in coolers and walk-in freezers.
(Joint SNOPR Comment, No. 0074.1 at
p. 2)
While other interested parties
suggested specific metrics for walk-in
components, manufacturers also offered
suggestions for overall walk-in metrics.
Craig Industries recommended
combining the envelope and
refrigeration calculations to calculate
the overall efficiency of the complete
walk-in system and labeling each walkin with that efficiency metric. (Craig,
No. 0068.1 at p. 6) Zero Zone stated that
the test procedure should include
performance testing to verify adequate
temperatures inside the walk-in. (Zero
Zone, No. 0077.1 at p. 1)
In view of the component-level
approach being adopted today, DOE is
not establishing an overall energy use
metric for the envelope in this test
procedure. Instead, DOE is establishing
separate metrics for the individual
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
components of the walk-in: the wall and
ceiling panels (hereafter referred to as
non-floor panels); floor panels; the
display and non-display doors; and the
refrigeration system. Regarding Zero
Zone’s suggestion that the procedure
verify that adequate internal
temperatures are used in evaluating a
walk-in unit’s efficiency, DOE does not
believe that such a requirement is
necessary in light of the componentbased approach being adopted today.
The panel metric determined by the
test procedure accounts for the
conductance and is in terms of U-factor
(that is, the thermal transmittance)
measured in Btu/h-ft2-°F, as NEEA, the
Joint SNOPR Comment, and the Joint
Utilities recommended. The metric for
display and non-display doors accounts
for the thermal transmittance through
the door and the electricity use of any
electrical components associated with
the door, and is in terms of energy use,
measured in kWh/day. DOE believes
that requiring separate metrics for
specific individual walk-in components
does not constitute a substantive change
from what was proposed in the
September 2010 SNOPR because this
Final Rule only requires tests that were
proposed for components in the
September 2010 SNOPR. Also, the
September 2010 SNOPR and this final
rule contain similar calculation
methodologies.
2. Responsibility for Testing and
Compliance
DOE proposed to adopt separate tests
for the envelope and refrigeration
system of a walk-in and require the
manufacturers of each to test and certify
the part they manufacture. 75 FR 186,
191 (Jan. 4, 2010) and 75 FR 55068,
55070 (Sept. 9, 2010). In response to this
proposed approach, DOE received
multiple comments regarding who
should assume testing, certification, and
compliance responsibilities. The Joint
SNOPR Comment recommended that
DOE focus on factory-produced
products (i.e. kits) instead of walk-ins
that are assembled on-site from
components from different
manufacturers. (Joint SNOPR Comment,
No. 0074.1 at p. 1) The Joint SNOPR
Comment further suggested that panel,
refrigeration system, and door
manufacturers each be responsible for
compliance and certification
responsibilities for their own products.
(Joint SNOPR Comment, No. 0074.1 at
pp. 2–3) Thermo-Kool agreed with this
approach and submitted a copy of a
regulatory framework proposed by
NEEA, in which envelope, door, and
refrigeration manufacturers would be
responsible for testing and complying
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
21583
with the standards for the components
they manufacture. (Thermo-Kool, No.
0072.1 at p. 1)
DOE received several other comments
which it summarized in the
certification, compliance, and
enforcement (CCE) final rule, published
on March 7, 2011. 76 FR 12422, 12444.
In brief, some of those comments agreed
with the approach suggested by the Joint
SNOPR Comment and Thermo-Kool that
individual component manufacturers
should test, certify, and ensure
compliance of their respective
components. Other commenters
recommended that the manufacturer,
the assembler, or the system designer of
the overall walk-in should be
responsible for the compliance of the
walk-in with the standards. 76 FR
12442–12446.
In the CCE final rule, DOE addressed
these comments by defining the
manufacturer of a walk-in at 10 CFR
431.302. 76 FR 12504.
The definition extends the
compliance responsibility to both the
component manufacturer and the
assembler. In the CCE final rule, DOE
clarified that component manufacturers
would be the entity responsible for
certifying compliance of the
components they manufacture for walkin applications and ensuring
compliance with the applicable Federal
standards of those components.
Assemblers of the complete walk-in
system are required to use only
components that are certified to meet
the applicable Federal standards. DOE
also adopted a flexible enforcement
framework in which it will determine
who is responsible for noncompliance
on a case-by-case basis. 76 FR 12444.
DOE notes that the provisions and
clarifications in the CCE final rule were
made in the context of component
manufacturers certifying their
components to the existing standards in
EPCA, which prescribe requirements on
a component-level basis. DOE has
decided to continue this approach in
developing test procedures and
performance-based standards for walkin coolers and freezers. DOE believes
that, within the very limited context of
walk in equipment, EPCA created a
means for DOE to set performance-based
standards for certain walk-in component
manufacturers. In particular, because
Congress set requirements for specific
components used in walk-in
applications, it provided DOE with the
implicit authority to set performancebased standards at the component level
for these specific components. This
unique ability stems from the manner in
which Congress set standards for walkin equipment by prescribing, among
E:\FR\FM\15APR3.SGM
15APR3
21584
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
srobinson on DSKHWCL6B1PROD with RULES3
other things, specific performance-based
requirements for wall, ceiling, door, and
floor insulation panels used in walk-ins.
See 42 U.S.C. 6313(f).
Because interested parties, including
entities who produce these components
and are subject to today’s requirements,
have indicated to DOE that the energy
efficiency performance of WICF
components would be most readily and
easily tested and certified by component
manufacturers, DOE intends to take this
approach for WICF test procedures and
performance standards. DOE
acknowledges the numerous difficulties
that commenters have noted with
alternative proposed approaches. By
requiring individual component
manufacturers to certify that their
components satisfy specified
performance-based standards, DOE can
ease the overall burden on walk-in
manufacturers relative to the
alternatives that were under
consideration as part of the January
2010 NOPR and September 2010
SNOPR. Therefore, in this test
procedure, DOE is establishing tests for
the components of a walk-in (i.e. panels,
doors, and refrigeration systems) and
anticipates that component
manufacturers will test their equipment
using the applicable procedure and, in
the future, will certify that they comply
with the appropriate standard. DOE
emphasizes that until performance
standards are established,
manufacturers are not required to use
this test procedure to certify equipment
to DOE (although they must use this test
procedure in making representations as
to the performance of their
components). However, because the
prescriptive standards established by
the 2007 amendments to EPCA are
already in effect, manufacturers must
demonstrate compliance with them
using the method specified in the CCE
final rule. 76 FR 12422.
3. Basic Model
DOE proposed a definition of basic
model for both envelopes and
refrigeration systems. 75 FR 186, 188–
189 (Jan. 4, 2010) and 75 FR 55068,
55071–55073 (Sept. 9, 2010). DOE
received comments from interested
parties on the definition and
summarized them in the CCE final rule.
76 FR 12422. Consistent with its
component-level approach to
certification, discussed in section
III.A.2, and taking the comments from
interested parties into consideration,
DOE decided to define a basic model for
each of the key components of a walkin, rather than defining a basic model
for the entire walk-in. DOE emphasized
that although the term ‘‘basic model’’ is
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
defined on the component level, it is
still implemented in the same manner
as it is in the rest of DOE’s appliance
standards program; that is, a basic
model consists of equipment that is
essentially the same with respect to
energy consumption, efficiency, or other
measure of performance. 76 FR 12444–
12446.
DOE provided, in relevant part, the
definition of basic model in the CCE
final rule at 76 FR 12504 (providing
definition of ‘‘basic model’’ for walk-ins)
(to be codified at 10 CFR 431.302).
DOE believes applying the basic
model concept at the component level
will reduce the testing burden on
manufacturers while ensuring that their
products meet any applicable standard,
because it removes the difficulty of
testing and/or certifying different sized
walk-ins that would have different
energy consumption levels. 76 FR
12445. The CCE final rule provides that
manufacturers may elect to group
individual models into basic models at
their discretion to the extent the models
have essentially identical characteristics
that affect energy efficiency or energy
consumption. Manufacturers may also
rate models conservatively—i.e. the
tested performance of the model(s) must
be at least as good as the certified
rating—after applying the appropriate
sampling plan. 76 FR 12429. The basic
model concept is applied slightly
differently to panels, doors, and
refrigeration systems because of their
different characteristics. These
differences are explained below.
a. Basic Model of Panels
Panels are construction components
that are not doors and that are used to
construct the envelope of the walk-in.
These components comprise the
elements separating the interior
refrigerated environment of the walk-in
from the exterior environment. In this
test procedure, panels are classified as
either floor panels, non-floor panels, or
display panels. A display panel is a
panel that is entirely or partially
comprised of glass, a transparent
material, or both and is used for display
purposes. Floor and non-floor panels are
mostly comprised of insulating material
and are not primarily used for display
purposes. For all types of panels, the
energy efficiency metric is the U-factor,
which is a measure of conductive,
convective, and radiative heat transfer
and which takes into account composite
panel characteristics, which may
include the insulation type, structural
members, any type of transparent
material (e.g. glass), and panel
thickness. See section III.B.2 for details
on how the U-factor is determined. DOE
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
considers a panel basic model to
include panels which do not have any
differing features or characteristics that
affect the U-factor. 76 FR 12504.
DOE notes that manufacturers who
make customized panels may
experience a higher certification burden
than manufacturers of standardized
panels. For example, under today’s
procedure, a panel’s U-factor is a surface
area-independent metric, which implies
that variation in panel width and height
alone would not be expected to affect
the U-factor rating if all other
characteristics were equal. In those
instances where no changes in energy
efficiency would occur, these panels
could be grouped as a basic model. In
contrast, smaller floor and non-floor
panels may have a higher proportion of
framing material to non-framing
material, or other structural members,
which could affect the overall panel Ufactor rating if the framing material or
framing geometry has different thermal
conductivity performance than the
neighboring insulation. Therefore, for
two or more floor or non-floor panels
that are equivalent in materials and
other characteristics but differ in their
frame to insulation proportions such
that they have different U-factor ratings,
the panels would be considered
different basic models and would need
to be certified independently to DOE, if
the manufacturer chooses to claim
different U-factor ratings. However, DOE
emphasizes that as explained in section
III.3, manufacturers may group models
into basic models at their discretion as
long as the tested performance of the
models is at least as good as the certified
rating.
DOE has also introduced additional
provisions to reduce the testing and
certification burden on floor and nonfloor panel manufacturers. See section
III.B.2.a for details.
As explained above, the energy
efficiency metric for display panels is
the U-factor, as for floor and non-floor
panels. However, unlike a floor, ceiling,
or wall panel, a display panel is
essentially a window. Therefore, in this
test procedure, DOE is requiring the Ufactor of display panels to be tested
using NFRC 100–2010[E0A1],
‘‘Procedure for Determining Fenestration
Product U-factors,’’ which DOE
proposed in the SNOPR for measuring
the U-factor of doors and windows,
including their framing materials. 75 FR
55083. (Sept. 9, 2010) As with floor and
non-floor panels, the basic model
concept allows manufacturers to group
display panels that are essentially
identical in U-factor into one basic
model, which DOE anticipates will
reduce the testing burden on display
E:\FR\FM\15APR3.SGM
15APR3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
srobinson on DSKHWCL6B1PROD with RULES3
panel manufacturers. Also, NFRC 100–
2010[E0A1] allows verified computer
models to simulate a display panel’s
energy consumption, another factor that
reduces the manufacturer’s testing
burden.
b. Basic Model of Doors
A door is an assembly installed in an
opening on an interior or exterior wall
that is used to allow access or close off
the opening and that is movable in a
sliding, pivoting, hinged, or revolving
manner of movement. For walk-in
coolers and walk-in freezers, a door
includes the door panel, glass, framing
materials, door plug, mullion, and any
other elements that form the door or
part of its connection to the wall. This
test procedure defines two types of
doors, display and non-display doors.
Display doors are doors designed for
product movement, display, or both,
rather than the passage of persons, and
non-display doors are considered to be
all other types of doors. For all doors,
the energy consumption metric that
DOE is adopting in today’s rule
incorporates the U-factor and any
electrical components built into the
door. (See section I.A.1.a for details.)
Calculating this metric requires the use
of NFRC 100–2010[E0A1], ‘‘Procedure
for Determining Fenestration Product Ufactors,’’ which DOE proposed in the
SNOPR for measuring the U-factor of
doors and windows, including their
framing materials. 75 FR 55083. (Sept. 9,
2010) Applying the NFRC test yields an
overall U-factor for the tested door.
Then, through calculations outlined in
Appendix A, the U-factor and the
electrical energy consumption are
combined to create a rating for the door.
As with panels, doors with essentially
identical energy consumption levels
may be grouped into a basic model and
rated conservatively. 76 FR 12429 and
12504. The basic model concept can be
used to reduce the testing and
certification burdens by allowing
manufacturers to group doors that are
essentially identical in energy
consumption but cosmetically different.
The NFRC procedure also permits either
a physical test or a verified computer
model to be used when determining the
U-factor of the door. The latter of these
options would be expected to reduce
testing burden because only a series of
calculations would need to be run by an
NFRC-approved computer modeling
program. DOE also notes that the
calculations for energy consumption of
door components are not based on
testing, which reduces the general
testing burden for doors. Any results
from physical tests, computer
simulations, and calculations must be
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
retained as required by the CCE final
rule. 76 FR 12494.
c. Basic Model of Refrigeration Systems
The refrigeration system consists
primarily of a compressor, condenser,
unit cooler, valves, and piping. It is
considered a component under the
component level approach (see section
III.A) that DOE is adopting in today’s
final rule. As with the panels and doors,
and consistent with the approach
promulgated in the CCE final rule,
manufacturers may elect to group
individual models into basic models at
their discretion to the extent the models
have essentially identical electrical,
physical, and functional characteristics
that affect energy efficiency or energy
consumption. Furthermore,
manufacturers may rate models
conservatively, meaning the tested
performance of the model(s) must be at
least as good as the certified rating, after
applying the appropriate sampling plan.
76 FR 12429. DOE believes these
provisions will reduce the burden of
testing for refrigeration manufacturers,
including those who make customized
equipment. DOE may also consider
methods which allow manufacturers to
use an alternate method of determining
the energy use of the refrigeration
system in a future rulemaking. This
concept is further discussed in section
III.C.3.
B. Test Procedures for Envelope
Components
The envelope consists of the insulated
box in which items are stored and
refrigerated. In the NOPR and SNOPR,
DOE proposed methods for evaluating
the performance characteristics of
insulation, testing thermal energy gains
related to air infiltration, and
determining direct electricity use and
heat gain due to internal electrical
components. The proposed procedure
used these methods to determine the
energy use associated with the envelope
by calculating the effect of the
envelope’s characteristics and
components on the energy consumption
of the walk-in as a whole. Those
characteristics and components
included the energy consumption of
electrical components present in the
envelope (such as lights) and variation
in the energy consumption of the
refrigeration system due to heat loads
introduced as a function of envelope
performance (such as conduction of heat
through the walls of the envelope). The
impact on the refrigeration system
energy consumption was determined by
calculating the energy consumption of a
theoretical or ‘‘nominal’’ refrigeration
system when paired with the tested
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
21585
envelope. 75 FR 186, 191 (Jan. 4, 2010)
and 75 FR 55068, 55074 (Sept. 9, 2010).
As described in section III.A, DOE is
no longer requiring manufacturers to
determine the energy consumption of
the entire envelope in this final rule.
Rather, DOE is establishing metrics for
the principal components of the
envelope (i.e. the panels and doors) as
described in section III.A.1. In doing so,
DOE is requiring manufacturers to use
the same physical tests for the
components that it proposed in the
NOPR and SNOPR, but is introducing
revisions to the calculations in
Appendix A of the new procedure.
These revisions will enable
manufacturers to calculate the required
component metrics from the results of
those tests.
For panels, DOE is adopting separate
approaches depending on whether a
given panel is a display or non-display
panel. Display panels are panels that are
primarily made of transparent material
and used for display purposes. Display
panels are considered equivalent to
windows because of their transparent
characteristics and associated thermal
heat transfer properties, and therefore
the U-factor will be measured by NFRC
100–2010[E0A1], ‘‘Procedure for
Determining Fenestration Product Ufactors,’’ which DOE proposed in the
SNOPR for measuring the U-factor of
doors and windows, including their
framing materials. 75 FR 55083. (Sept. 9,
2010) Non-display panels are floor and
non-floor panels. Since both floor and
non-floor panels are typically made out
of a composite of insulation, framing,
and facer material, both types of panels
will be tested using the same
methodology. In today’s rule, the
physical tests pertaining to the
performance of non-display panels are
from ASTM C1363–05, ‘‘Standard Test
Method for Thermal Performance of
Building Materials and Envelope
Assemblies by Means of a Hot Box
Apparatus’’ and, for foams that
experience aging, DIN EN 13164:2009–
02, ‘‘Thermal insulation products for
buildings—Factory made products of
extruded polystyrene foam (XPS)—
Specification’’ or DIN EN 13165:2009–
02, ‘‘Thermal insulation products for
buildings—Factory made rigid
polyurethane foam (PUR) products—
Specification,’’ as applicable. These tests
were proposed in the SNOPR. 75 FR
55068, 55075–55076 and 55081 (Sept. 9,
2010). In this final rule, panel
performance is denoted by its overall Ufactor, or thermal transmittance, which
is determined by the test procedures
and calculation methodologies
described in section III.B.2.
E:\FR\FM\15APR3.SGM
15APR3
21586
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
DOE is requiring one test for door
performance, NFRC 100–2010[E0A1],
‘‘Procedure for Determining Fenestration
Product U-factors,’’ which was proposed
in the SNOPR. 75 FR 55083 (Sept. 9,
2010). This test measures conduction
through a door, whether it is a display
door or a non-display door. The total
energy consumption of a door is
calculated as the effect of a door’s
thermal load on the refrigeration system
combined with the door’s electrical
energy use, as described in section 4.5
and section 4.4 of Appendix A of this
final rule. The effect on the refrigeration
system is determined by calculating the
energy consumption that a theoretical or
‘‘nominal’’ refrigeration system would
use to reject the heat that was
transmitted through the door. The
energy that would be used by the
theoretical refrigeration system to reject
a given amount of heat is represented by
the energy efficiency ratio (EER) of the
refrigeration system. The test procedure
uses the same nominal refrigeration
system EER for all tested doors to enable
direct comparisons of the performance
of walk-in doors across a range of sizes,
product classes, and features. The
nominal EER values for cooler and
freezer refrigeration (i.e. 12.4 Btu/W-h
and 6.3 Btu/W-h for coolers and
freezers, respectively) are the same as
those proposed in the SNOPR for
calculating the energy use of the
envelope. See 75 FR 55013 (Sept. 9,
2010).
1. Definition of Envelope
In the January 2010 NOPR, DOE
proposed the following definition of
‘‘envelope:’’
srobinson on DSKHWCL6B1PROD with RULES3
Envelope means (1) a piece of equipment
that is the portion of a walk-in cooler or
walk-in freezer that isolates the interior,
refrigerated environment from the ambient,
external environment; and (2) all energyconsuming components of the walk-in cooler
or walk-in freezer that are not part of its
refrigeration system.
75 FR 186, 192 (Jan. 4, 2010).
The walk-in envelope was proposed
to include, but not be limited to, walls,
floors, ceilings, seals, windows, doors,
or any combination thereof, composed
of single or composite materials. DOE
did not propose any changes to this
definition in the September 2010
SNOPR.
Master-Bilt, BASF, ThermalRite,
ACEEE, and ICS submitted written
comments supporting the proposed
definition for the walk-in envelope.
(Master-Bilt, No. 0027.1 at p. 1; BASF,
No. 0021.1 at p. 3; ThermalRite, No.
0049.1 at p. 1; ACEEE, No. 0052.1 at p.
2; ICS, No. 0045.1 at p. 1) However, NorLake asked that the definition of
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
envelope exclude components of the
envelope purchased separately by the
end user to enable the manufacturer of
the envelope to avoid compliance
responsibility for the performance of
those components. (Nor-Lake, No.
0023.1 at p. 2) ICS requested
clarification on the preemption of
energy codes by building, electrical, and
mechanical codes and stated that the
definition must allow for structural and
electrical safety code compliance over
energy compliance when in conflict.
(ICS, No. 0045.1 at p. 1) A
representative from Gonzaga Law
argued that the definition proposed by
the DOE was too inclusive but did not
propose an alternative definition.
(Gonzaga Law, No. 0018 at p. 1) At the
public meeting for the January 2010
NOPR, ICS suggested that DOE’s
standards and definitions should align
with NSF’s (formerly known as the
National Sanitation Foundation)
definition of envelope and
requirements. (ICS, Public Meeting
Transcript, 0016 at p. 30) (In this and
subsequent citations, ‘‘Public Meeting
Transcript’’ refers to the transcript of the
March 1, 2010, public meeting on the
proposed test procedures for walk-in
coolers and freezers. ‘‘No. 0016’’ refers to
the document number of the transcript
in the Docket for the DOE rulemaking
on test procedures for walk-in coolers
and freezers, Docket No. EERE–2008–
BT–TP–0014; and the page number
refers to the place in the transcript
where the statement preceding appears.)
DOE notes the comments and
suggestions from Master-Bilt, BASF,
ThermalRite, ACEEE, ICS, and Gonzaga
Law. However, because DOE is taking a
component-based approach, the
proposed envelope definition is no
longer applicable for the purpose of this
test procedure. As suggested by ICS,
when evaluating potential standards
applicable to walk-ins, DOE will also
consider their related requirements that
manufacturers need to satisfy. In
response to Nor-Lake’s comment
regarding components not supplied by
the envelope manufacturer, DOE
clarifies that each component
manufacturer is responsible for testing
its component with the appropriate test
procedure as discussed in section
III.A.2. The envelope component
manufacturer is not responsible for the
end user’s implementation of the
component; rather, the manufacturer
would be responsible only for the
component’s compliance as designed.
Also, the envelope assembler is
responsible for using WICF-compliant
components to assemble the total
envelope.
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
2. Heat Transfer through Panels
a. U-Factor of Composite Panels
Including Structural Members of Panels
EPCA specifies that ASTM C518–04,
‘‘Standard Test Method for Steady-State
Thermal Transmission Properties by
Means of the Heat Flow Meter
Apparatus,’’ must be used to determine
the K-factor of walk-in insulation. The
statute defines the R-value as equal to
the value of 1/K-factor multiplied by the
thickness of the panel. (42 U.S.C. 6314
(a)(9)(A)(i)¥(ii)) In response to the
January 2010 NOPR, interested parties
commented that the heat conduction
through structural members must be
considered because this factor could
affect the conductance through the
composite walk-in insulation panel.
Accordingly, DOE proposed in the
September 2010 SNOPR to use ASTM
C1363–05, ‘‘Standard Test Method for
Thermal Performance of Building
Materials and Envelope Assemblies by
Means of a Hot Box Apparatus,’’ to
measure the overall U-factor of fully
assembled panels to help account for
the impact that structural members have
on the overall U-factor. 75 FR 55074.
Several interested parties—NEEA,
AHRI, Master-Bilt, Thermo-Kool,
Carpenter, and Bally—supported the use
of ASTM C1363–05 to measure the
overall panel U-factor. (NEEA, No.
0061.1 at p. 2; AHRI, No. 0070.1 at p.
2; Master-Bilt, No. 0069.1 at p. 1;
Thermo-Kool, No. 0072.1 at p. 1;
Carpenter, No. 0070.1 at p.2; Bally, No.
0078.1 at p. 2))
Other interested parties, however,
disagreed with DOE’s proposal to use
ASTM C1363–05 to measure panel
performance. At least some of these
concerns were premised on a mistaken
belief that DOE’s proposal would result
in the elimination of structural members
embedded into panels. For example, a
comment submitted jointly by the
manufacturers CrownTonka,
ThermalRite, and ICS (collectively
referred to as the Joint Manufacturers)
recommended that structural members
be excluded from the stated R-value
requirements for overall envelope
thermal resistance. The Joint
Manufacturers explained that many
walk-ins require the use of structural
members to comply with building codes
and to help support loads placed on the
building from factors such as snow and
wind. The Joint Manufacturers stated
that ASTM C518–04 should be used to
measure the K-factor of foam, as
specified in EPCA. (42 U.S.C. 6314
(a)(9)(A)(i)–(ii)) (Joint Manufacturers,
No. 0062.1 at p. 1)
While American Panel agreed with
DOE’s general approach that the R-value
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
of structural members should be
considered in determining the overall
U-factor and submit data to demonstrate
the impact of structural members on the
overall U-factor, it stated that the
composite panel must meet the
minimum R-value requirement.
American Panel continued to state that
the R-value should be calculated by
using a weighted percentage of foam Rvalue and structural R-value based on
the percentage each material represents
in the panel. (American Panel, No.
0057.1 at p. 1; American Panel, No.
0057.1 at p. 2; American Panel, No.
0057.3 at p. 1) It asserted that ASTM
C1363–05 is not the appropriate test
method for measuring the insulating
values of foam, and added, along with
Craig Industries and Carpenter, that
ASTM C518–04 should be used to
measure heat conduction through
panels. (American Panel, No. 0057.1 at
p. 2; Craig, No. 0068.1 at p. 2; Carpenter,
No. 0067.1 at p. 2) Craig Industries was
concerned that using ASTM C1363–05
to calculate the heat conduction through
structural members may not take the
reduction of joints (that is, panel to
panel interfacing members) into
consideration. Craig Industries
recommended that the structural
members should be tested with a
procedure to represent the real R-value,
which would replace the R-value of the
insulation where it is replaced with
structural members. (Craig, No. 0057.13
at p. 2) Carpenter further asserted that
ASTM C518–04 is simpler and less
costly to perform than C1363–05.
(Carpenter, No. 0067.1 at p. 2) ThermoKool, on the other hand, disagreed with
the approach of using R-value testing of
different components of the composite
panel to determine heat loss. (ThermoKool, No. 0072.1 at p. 1) Bally, who
agreed with DOE’s proposed approach,
requested clarification specifically
regarding how the two tested areas
would be used to represent the
performance of a panel. (Bally, No.
0078.1 at p. 2)
None of the interested parties offered
any further explanation for their views
other than those already described.
In this final rule, the terms ‘‘foam’’ and
‘‘insulation’’ are used synonymously, but
a panel is the fully manufactured
product that contains, but is not limited
to, the insulating material, metal skin,
framing material, other structural
members, or any combination thereof.
To address the Joint Manufacturers’
concerns about the potential elimination
of structural members, DOE emphasizes
that the overall U-factor testing required
by today’s final rule will not prevent
manufacturers from including structural
members in panels because the existing
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
standards in EPCA only regulate the Rvalue of the foam and do not restrict the
overall panel U-factor or the R-value of
the structural components. The R-value
of insulation, which is 1/K-factor as
determined by ASTM C518–04, will still
have to comply with the existing EPCA
requirements for insulation. (42 U.S.C.
6314 (a)(9)(A)(i)–(ii)) However, the
overall U-factor of the fully assembled
panel, including structural members,
may be used to meet an energy
conservation standard for panels, which
will be determined in a parallel
rulemaking. Including ASTM C1363–05
will provide a more accurate means to
represent the overall heat transfer
performance of panels. DOE believes
this procedure will be beneficial
because it will capture the effects of
structural members that incorporate
insulation or otherwise contribute to the
efficiency of the walk-in.
Additionally, while DOE
acknowledges the concerns raised by
American Panel, the Joint
Manufacturers, Craig Industries, and
Carpenter, the final rule includes ASTM
C1363–05 as part of the test procedure
in order to determine the overall Ufactor of the panel. DOE is including
this protocol as part of the test
procedure because heat conduction
through structural members is a
significant panel characteristic that is
not addressed under the statutorilyprescribed testing requirements (i.e.
ASTM C518–04). While ASTM C518–04
could be used to individually measure
the R-value of structural members, or
any other material, as Craig Industries
suggested, DOE believes that this
approach would be more costly because
of the many materials that could
comprise a panel and the need to test
each material separately under that
approach. Furthermore, DOE believes
that panel geometry could make
calculations to combine the R-value of
each material into an overall panel Rvalue complicated and burdensome.
DOE also acknowledges Craig
Industries’ concern that ASTM C1363–
05 does not account for the reduction of
joints (that is, panel to panel interfacing
members). Since DOE is adopting an
approach to ensure the energy efficiency
performance of particular components,
an approach suggested by numerous
commenters, and is no longer
considering the effects of infiltration,
panel joint issues are outside of this
approach.
DOE notes that American Panel
supported the inclusion of structural
members in calculating the overall Ufactor. Furthermore, DOE would like to
clarify the calculation methodology to
address the comment from Bally.
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
21587
Today’s final rule adopts a weighted
percentage of the panel edge (which
may contain structural members) and
panel core region (which may also
include structural members) in order to
calculate the panel’s total U-factor. DOE
believes that using the weighted
percentage of edge U-factor and core Ufactor to calculate the total U-factor will
help reduce the manufacturer’s testing
burden.
In applying this weighted percentage
approach, today’s final rule provides
that for floor or non-floor panels of the
same thickness, construction methods,
and materials, manufacturers must test
a pair of 4 ft. by 8 ft. ‘‘test panels’’ to
obtain a core U-factor and an edge Ufactor. The manufacturer must then
calculate the overall U-factor of other
floor or non-floor panels with the same
panel thickness, construction methods,
and materials using the U-factor results
for the core and edge region ‘‘test
panels.’’ For example, a manufacturer
tests a 4 ft. by 8 ft. test panel and finds
the edge region and core region Ufactors. The same manufacturer also
produces 6 ft. by 8 ft. panels that have
identical core and edge region
thickness, construction methods and
materials. Therefore, the manufacturer
may apply the core and edge region
factors to the 6 ft. by 8 ft. panel to
calculate the overall U-factor of the 6 ft.
by 8 ft. panel instead of performing an
additional test. DOE notes that any
calculations that support the certified
ratings must be retained along with the
test data for the ‘‘test panels’’ for all basic
models pursuant to the requirements for
the maintenance of records promulgated
in the CCE final rule. 76 FR 12494. DOE
expects that, based on the information it
has collected, including information
made available by manufacturers on
their Web sites and submitted
comments, most manufacturers use the
same panel thickness, materials, and
construction methods for many of their
panels, which results in a minimal
testing burden.
In regard to American Panel’s
comment that the composite panel must
meet the minimum R-value
requirement, DOE clarifies that EPCA
states that only the insulation material
(that is, the foam) must meet the
prescribed R-value. (42 U.S.C.
6313(f)(1)(C)) The test procedure is
prescribing ASTM C1363–05 as a
method of measuring the overall Ufactor of the entire panel. For EPCA
compliance, the R-value of the
insulation must be separately
determined in accordance with ASTM
C518–04 as specified in EPCA. (42
U.S.C. 6313(f)(1)(C))
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
21588
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
Finally, interested parties suggested
changes to the test methodology DOE
proposed. NRDC stated that irregular or
non-homogeneous foam products
should be tested for actual R-value
where there is no quality control to
maintain the orientation of the foam in
the finished product. To clarify, DOE
believes that when NRDC noted the
concern about the orientation of the
foam, they were referring to bun-stock
foam products. Bun-stock products are
manufactured in ‘‘buns’’ that may have
foam cell structure similar to the grains
in wood. Like wood, depending on how
the buns are cut into boards, the
orientation of the cell ‘‘grains’’ may vary
by finished board. NRDC continued to
suggest that if a foam product cannot be
tested, then the stated R-value should be
a conservative number representing the
lowest R-value for a tested material.
(NRDC, No. 0064.1 at p. 4) NRDC also
suggested that DOE review the impact of
testing the final fabricated panel rather
than requiring manufacturers to
specially construct units for testing,
because specially constructed units may
not represent the typical product.
(NRDC, No. 0064.1 at p. 4) Master-Bilt
suggested changing the width and
length of the panel to 8 x 4 ft. +/- 1 ft.
to have more tolerance and allow for the
testing of standard width panels.
(Master-Bilt, No. 0069.1 at p. 2)
In response to NRDC’s comment about
irregular or non-homogeneous foam
products, DOE anticipates that the
prescribed sampling procedures for
certification will accurately capture the
foam’s R-value. A sampling plan is
intended to ensure accurate and
statistically repeatable results are
achieved when using the test procedure.
DOE notes NRDC’s concern that
specifically constructed units may not
represent an actual product. However,
in order to reduce the testing burden
presented by ASTM C1365–05, DOE is
maintaining the approach of specifying
two test regions of a pair of
representative panels. At one test
region, the tester measures the U-factor
of the perimeter that may contain
structural members and panel-to-panel
interface area (the ‘‘Panel Edge’’), while
at the other region the tester measures
the U-factor of the core area of the panel
(the ‘‘Panel Core’’) which may also
contain structural members. The Ufactor for each region is then applied to
panels of the same type (that is, same
foam type, framing material, and panel
thickness) to obtain an overall U-factor
that is representative of actual products
sold by the panel manufacturer. DOE
applies a calculation methodology to
extrapolate the core and edge U-factor to
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
determine the U-factor of any panel
produced by a manufacturer.
In response to Master-Bilt’s comment,
DOE agrees that increasing the tolerance
of the 8 ft x 4 ft test panel to +/¥ 1 ft
will provide manufacturers with a
greater range of standard sized panels.
DOE conducted a mathematical analysis
to determine how changing the
tolerance would affect the U-factor as
determined by ASTM C1363–05. DOE
found that increasing the size tolerance
of the test panel results in less than a
0.5 percent change to the U-factor as
determined by ASTM C1363–05.
Therefore, DOE has amended the
standard size of a test panel for ASTM
C1363–05 to be 8 ft x 4 ft +/¥ 1 ft.
b. Long-Term Thermal Resistance
In the January 2010 NOPR and
September 2010 SNOPR, DOE cited
several studies that conclude that lateral
gas diffusion, which causes a reduction
in R-value, occurs in impermeably faced
foams. See 75 FR 192–194 and 75 FR
55075–55079. These types of foams are
common to walk-ins. The lateral gas
diffusion occurs over time and affects
the energy efficiency performance of the
foam as diffusion continues. To account
for this aging effect on a foam’s
insulation performance—and, by
extension, the energy consumption of a
walk-in due to thermal losses
attributable to this reduced
performance—DOE, consistent with its
proposed approach, is adopting a
method to account for this phenomenon
in walk-in applications. Hill Phoenix
added that different methods of
manufacturing panels should be taken
into account when determining the test
procedure. (Hill Phoenix, No. 0063.1 at
p. 2)
The most significant factor affecting
the efficiency of a walk-in panel is the
insulating foam in a panel, and
accurately capturing the foam’s R-value
is critical to measuring the overall
performance of the panel. Panels can be
in use for 10 to 20 or more years before
they are replaced. Performance metrics
for a panel based on initial foam R-value
will tend to overestimate the amount of
energy saved over this equipment’s
lifetime. Research on panel aging has
shown that a 5-year aged R-value found
by LTTR testing is representative of the
panel’s insulation performance over its
lifetime, and there are industry tests for
walk-in foam that estimate the aged Rvalue over time. Using these industrydeveloped protocols will enable
manufacturers to more accurately
capture the lifetime performance of a
walk-in panel.
Incorporating a long term thermal
resistance degradation factor improves
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
the reliability of test results for walk-in
panels. While EPCA contains standards
for the R-value or insulating
performance of the foam, these
standards do not specify when the
insulating foam must be tested. (42
U.S.C. 6313(f)(1)(C)) Variables that
impact the time at which panels are
tested include shipping time,
production time, shipment of completed
panels to test lab, and test facility
availability. Changing any one of these
variables could result in significantly
different test results and measured Rvalues. This is in contrast to most other
types of equipment within the appliance
standards program, which would not
exhibit significant differences in
performance based on the length of time
between manufacture and testing.
Because of the unique aging profile of
certain foam types, the timing of a walkin panel test would affect both
manufacturers’ certification of the panel
U-factors and any enforcement testing
undertaken by DOE. Therefore, using
LTTR values to measure foam
performance eliminates the ‘‘time’’
variable that could affect whether a
panel is shown to comply with an
overall performance standard that DOE
may set. The purpose of the LTTR
testing is to accelerate foam aging to the
point where the R-value changes
relatively slowly over time and to then
measure its performance, thus
improving the repeatability of the test
because the timing of the test is no
longer critical.
In the January 2010 NOPR, DOE
proposed to use ASTM C1303–08,
‘‘Standard Test Method for Predicting
Long-Term Thermal Resistance of
Closed-Cell Foam Insulation,’’ to
calculate the long-term thermal
resistance (LTTR) of walk-in foam
insulation. 75 FR 186, 193–94 (Jan. 4,
2010). In the September 2010 SNOPR,
DOE proposed to use the updated
version of ASTM C1303–08, which was
ASTM C1303–10. 75 FR 55068, 55075
(Sept. 9, 2010). In that notice, DOE also
offered an alternative method, Annex C
of either DIN EN 13164:2009–02,
‘‘Thermal insulation products for
buildings— Factory made products of
extruded polystyrene foam (XPS)—
Specification’’ or DIN EN 13165:2009–
02, ‘‘Thermal insulation products for
buildings—Factory made rigid
polyurethane foam (PUR) products—
Specification,’’ as applicable, to test for
the LTTR. This alternative was offered
in response to concerns raised in
response to the NOPR. The SNOPR
requested comments on both of these
alternative methods. 75 FR 55079 (Sept.
9, 2010).
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
In light of the comments that DOE
received on all of these various testing
methods, which are addressed below,
DOE has decided to adopt DIN EN
13165:2009–02 or DIN EN 13164:2009–
02, as applicable, as the test procedure
for determining LTTR. The LTTR value
determined by DIN EN 13165:2009–02
or DIN EN 13164:2009–02 will be used
to determine a degradation factor, which
will be the LTTR R-value divided by the
initial R-value of the foam. The initial
R-value will be determined in
accordance with ASTM C518–04 as
specified in the EISA 2007 amendments
to EPCA and used to establish
compliance with those statutorilyprescribed requirements. (42 U.S.C.
6313(f)(1)(C)) The degradation factor is
applied to the U-factor of the panel
found by ASTM C1365–05; see section
4.2 and 4.3 in Appendix A.These
protocols are preferable to ASTM
C1303–10 because they account for the
effect of impermeable facers, which
ASTM C1303–10 does not.
In response to this approach, DOE
received a number of comments.
Thermo-Kool noted the general need to
consider LTTR. It also suggested that the
potential for thermal degradation is
more likely to occur at the panel joints
than from actual polyurethane (i.e.
foam) issues. (Thermo-Kool, 0072.1 at p.
1) The Joint Manufacturers
recommended that structural members
be considered in the long-term thermal
resistance performance of any panels
with structural edges because they may
lessen or slow off-gassing over time.
(The Joint Manufacturers, No. 0062.1 at
p. 1).
American Panel and Bally opposed
DOE’s inclusion of a test procedure that
measured LTTR. (American Panel, No.
0057.2 at p. 1; Bally, No. 0078.1 at p. 2)
American Panel explained that
impermeable or metal skins protect the
polyurethane foam from aging and that
little change will occur in the long term
R-value. In support of its claim that
impermeably faced metal skins protect
foam from aging, American Panel
submitted the results of a study
conducted by Carpenter. That study
found a 3.6 percent loss in insulating
value of a panel after 9 years in a walkin application. (American Panel, No.
0057.2 at p. 1) American Panel also
asserted that none of its customers
complained about R-value loss in the
panels that American Panel sold to
them. (American Panel, No. 0057.1 at p.
2)
One interested party recommended
that DOE collect test data before
prescribing a particular test method.
Bally stated that more data from actual
walk-in panels with intact metal skins
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
and sealed edges should be collected
before DOE includes a test procedure for
long-term thermal resistance. (Bally, No.
0078.1 at p. 2)
DOE acknowledges Thermo-Kool’s
assertion that most aging occurs at the
panel joints and Bally’s suggestion that
DOE collect more data to support long
term thermal aging. DOE notes,
however, that polyurethane itself has
the potential to age significantly. DOE
cited multiple studies, in both the
January 2010 NOPR and September
2010 SNOPR, that conclude that aging
occurs in most types of foams
commonly used in walk-in applications,
including polyurethane. 75 FR 192–194
(Jan. 4, 2010) and 75 FR 55075–55079
(Sept. 9, 2010). In response to the Joint
Manufacturers’ comment about
accounting for the effect structural
members have on LTTR, DOE also notes
that no known test procedures are
available that address edge sealing at
this time but that this factor could be
considered in a future rulemaking.
DOE also considered the merits of the
submissions in support of American
Panel’s contention that impermeably
faced foams do not undergo significant
aging. After evaluating this information,
however, DOE continues to believe that
the inclusion of LTTR testing in the test
procedure is necessary to accurately
measure the R-value of foam. DOE notes
that the samples in the Carpenter study
cited by American Panel were taken
from the center of the panel. As DOE
noted in the SNOPR, another study (the
Ottens study, ‘‘Industrial Experiences
with CO2 Blown Polyurethane Foams in
the Manufacture of Metal Faced
Sandwich Panels’’) found that core
samples do not represent the overall
aging of foam in panels because most
aging occurs at the panel’s perimeter. 75
FR 55068, 55077 (Sept. 9, 2010) (citing
Ottens et al., ‘‘Industrial Experiences
with CO2 Blown Polyurethane Foams in
the Manufacture of Metal Faced
Sandwich Panels,’’ Polyurethane World,
1997.) As a result, the data from this
study indicate that the Carpenter study’s
results do not necessarily provide an
accurate portrayal of the likely effects of
panel aging.
Additionally, while American Panel
asserted that the lack of customer
complaints about R-value loss in panels
indicates that the deterioration of LTTR
values is insignificant, the lack of
customer complaints may be influenced
by a variety of factors. For example, a
panel is normally only replaced when
visibly damaged. However, a panel may
have reduced thermal performance
without any accompanying visual cues
suggesting problems with the panel.
Accordingly, DOE does not believe that
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
21589
the statements and materials cited by
American Panel support the premise
that LTTR of foam is negligible for walkin panels.
Interested parties also made
comments on the specific test methods
that DOE proposed. DOE received some
comments from interested parties in
favor of using ASTM C1303–10 to
determine the LTTR of foam insulation.
Owens Corning agreed that DOE should
use the most current version of
whichever ASTM standards it planned
to use. (Owens Corning, No. 0058.1 at p.
1) Craig Industries agreed with the use
of ATSM C1303–10, but stated that DOE
should evaluate if ASTM C1303–10 is
appropriate for all present and future
foam insulation products. (Craig, No.
0068.1 at p. 4) NRDC supported testing
insulated products to determine
whether the R-value degraded over time,
and stated that the proposed ASTM
standard is acceptable and known in the
industry. (NRDC, No. 0064.1 at p. 4)
NEEA stated that although some
interested parties have concerns about
LTTR values derived from ASTM
C1303–10, NEEA believed that carefully
specifying the physical characteristics of
the tested panel samples will address
their concerns. (NEEA, No. 0061.1 at
p. 2)
Some interested parties disapproved
of ASTM C1303–10. American Panel,
Hill Phoenix, Thermo-Kool, and the
Joint Manufacturers opposed using
ASTM C1303–10 as the test procedure
to measure LTTR. (American Panel, No.
0057.1 at p. 2; Hill Phoenix, No. 0063.1
at p. 2; Thermo-Kool, 0072.1 at p. 1; the
Joint Manufacturers, No. 0062.1 at p. 1)
American Panel asserted that any testing
to determine R-value must allow the
foamed-in-place polyurethane to remain
encapsulated by the metal facers to
resemble the real-world application.
(American Panel, No. 0057.1 at p. 2) Hill
Phoenix and Thermo-Kool did not
recommend the use of ASTM C1303–10
because, as noted in section 1.3 of
ASTM C1303–10, the standard does not
apply to impermeably faced foams;
therefore, applying the results from
ASTM C1303–10 to impermeably faced
foams would be misleading. Hill
Phoenix also suggested that ASTM
C1303–10 would significantly
overestimate foam aging of foamed-inplace polyurethane panels. (Hill
Phoenix, No. 0063.1 at p. 2) The Joint
Manufacturers opposed the use of
ASTM C1303–10 for measuring longterm R-value decline because it is not
intended for use with faced panels and
unfairly penalizes foamed-in-place
polyurethane that has minimal or zero
exposure of permeable surfaces (the
Joint Manufacturers, No. 0062.1 at p. 1)
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
21590
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
Owens Corning stated that the
prescriptive and research methods of
ASTM C1303–10 are not comparable
and will not generate comparable
results. It added that the Canadian test
procedure CAN/ULC S770, which is
based on various versions of ASTM
C1303, has a positive bias and may overpredict foam aging, and submitted foam
aging data and an article about the CAN/
ULC S770 test to support this comment.
(Owens Corning, No. 0058.1 at p. 2;
Owens Corning, No. 0058.1 at p. 1;
Owens Corning, No. 0058.5 at p. 19;
Owens Corning, No. 0058.2 at p. 2)
Carpenter and Master-Bilt also
opposed the use of ASTM C1303–10 for
LTTR testing and suggested possible
alternatives. Carpenter suggested testing
initial and aged K-factors per ASTM
C518 at 20 °F and 55 °F for freezers and
coolers, respectively. (Carpenter, No.
0067.1 at p. 3) Carpenter stated that
ASTM C1303–10 would underestimate
the LTTR of impermeably faced panels
and that LTTR tests should be
performed on samples with intact
facers. (Carpenter, No. 0067.1 at p. 2)
Similarly, Master-Bilt explained that
panel edges are not 100 percent
exposed, but are tight against one
another and sealed with caulk and vinyl
gaskets. Collectively, the caulk and
gaskets significantly reduce gas
migration, thus reducing the effects of
aging. Therefore, in its view, the testing
of skinned panels with exposed edges
still considerably overstates the
insulation degradation. Master-Bilt
suggested that a formula based on test
data from actual walk-in panels that
have been installed could be used
instead of ASTM C1303–10. (MasterBilt, No. 0068.1 at p. 2)
DOE agrees with the assessment that
ASTM C1303–10 is not adequate for
testing impermeably faced foams. DOE
believes that the concerns about ASTM
C1303–10 expressed by American Panel,
Hill Phoenix, Thermo-Kool, Master-Bilt,
the Joint Manufacturers, Carpenter, and
Owens Corning are addressed by DIN
EN 13165:2009–02 and DIN EN
13164:2009–02, which account for
impermeably faced foams, reduce the
testing burden, and are appropriate for
different types of foam. DIN EN
13165:2009–02 and DIN EN
13164:2009–02 partially rely on a
formula based on test data, as suggested
by Master-Bilt. DOE agrees with Owens
Corning that the prescriptive and
research methods of ASTM C1303–10
are not comparable, and notes that DIN
EN 13165:2009–02 and DIN EN
13164:2009–02 do not have this
problem.
One interested party expressed
concerns about two of the studies DOE
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
referenced in the September 2010
SNOPR. One study was the Ottens
study, in which an experiment was
completed on polyurethane foamed-inplace panels to assess their long-term
insulating behavior. 75 FR 55068, 55077
(Sept. 9, 2010). (Ottens et al., ‘‘Industrial
Experiences with CO2 Blown
Polyurethane Foams in the Manufacture
of Metal Faced Sandwich Panels,’’
Polyurethane World, 1997.) In the
SNOPR, DOE estimated that the test was
likely representative of panels aged for
at least 5 years. 75 FR at 55077 (Sept.
9, 2010). ORNL challenged this estimate
and stated that the results from the
Ottens study cannot be correlated to a
particular aging period. (ORNL, No.
0060.1 at p. 2)
The second study DOE referenced was
a round robin test using CAN/ULC–
S770–03, a standard with the same test
methodology as a previous version of
ASTM C1303. DOE referenced the test
to address concerns raised by various
interested parties that the thin slicing
method, CAN/ULC–S770–03. Results
from the round-robin study predicted
that polyurethane would perform at a
lower level than extruded polystyrene
or even at a level as low as expanded
polystyrene. 75 FR 55079 (Sept. 9,
2010). ORNL stated the testing used in
the referenced study relied on the
original version of S770, which has been
shown to over-predict thermal
resistance. ORNL added that the test
was performed on foams created with
blowing agents that are no longer used,
and the results are not representative of
current products. (ORNL, 0060.1 at p. 2)
Regarding ORNL’s comment about the
Ottens study, DOE agrees that the
method in the study cannot be
accurately correlated to a particular
aging period. However, in DOE’s view,
the conclusions reached in those studies
illustrate that impermeably faced foams
are subject to aging. DOE agrees with
ORNL’s evaluation of the flaws in the
round robin test data but notes that the
same test was used on each type of foam
evaluated, which permits a comparison
of the results from each type of tested
foam. DOE used the results of the round
robin test to demonstrate that there were
no performance differences between
polyurethane and polystyrene foams—
not to predict the level of thermal
resistance over time.
Interested parties also commented on
the specific testing conditions for ASTM
C1303–10. ORNL proposed that, if
adopted, ASTM C1303–10 should be
modified to allow the user to take
multiple 12 inch x 12 inch specimens
from the 48 inch x 96 inch panel, at
least 12 inches away from the edge of
the 48 inch x 96 inch source. (ORNL,
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
No. 0060.1 at p. 2) ORNL suggested
specifying the aging conditioning
temperatures for foam insulation. ORNL
explained that while most insulation
foams must follow aging condition
requirements, the conditions used to age
bun stock foam, which is used in
producing foam insulation, may be
freely modified. This situation could
lead to skewed comparisons between
products. (ORNL, No. 0060.1 at p. 2)
Manufacturers also offered views
regarding these proposed testing
conditions. Craig Industries, Carpenter,
and Owens Corning stated that the
procedures detailed in ASTM C1303–10
should be conducted at the specified
EPCA mean temperatures 55 °F and 20
°F for a cooler and freezer, respectively.
(Craig Industries, 0068.1 at p. 4;
Carpenter, No. 0067.1 at p. 3; Owens
Corning, No. 0058.1 at p. 2) Carpenter
also suggested modifying DOE’s
proposal by adding a provision for
molding test panels using unprimed
aluminum facers. (Carpenter, No. 0067.1
at p. 3) NRDC asserted that the proposed
temperatures for testing insulation
needed to be substantiated. (NRDC,
0064.1 at p. 4) Craig Industries asserted
that the modifications to ASTM C1303–
10 proposed by DOE in the September
2010 SNOPR test were acceptable, but
wanted DOE to ensure that the changes
would also apply to expanded
polystyrene insulation. (Craig
Industries, No. 0068.1 at p. 4) Bally
suggested that the initial panel size
should be changed to 48 inches ± 3
inches and 96 inches ± 2 inches so that
a standard panel configuration could be
used for the test panel. Bally stated that
manufacturers could incur significant
costs from manufacturing test panels.
(Bally, No. 0078.1 at p. 2)
While DOE appreciates ORNL’s and
Bally’s suggested improvements to
ASTM C1303–10, these
recommendations are no longer relevant
since DOE has decided to adopt DIN EN
13165:2009–02 and DIN EN
13164:2009–02, which collectively
address some of the shortcomings of
ASTM C1303–10. For example, DIN EN
13165:2009–02 and DIN EN
13164:2009–02 provide for inclusion of
metal facers, while ASTM C1303–10
does not. In regard to Bally’s concern
about the size of the test panel, a test
panel is no longer required to be a
certain size as long as the panel is large
enough for the test sample to be cut
from its geometric center, as prescribed
in Appendix A. Additionally, given the
comments from Craig Industries,
Carpenter, Owens Corning, and NRDC
about the temperature conditions for
testing, DOE has decided to adopt the
EPCA mean temperatures of 55 °F and
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
20 °F for a cooler and freezer,
respectively for the DIN EN
13165:2009–09 and DIN EN
13164:2009–02 testing conditions. This
means that when a manufacturer tests a
panel for LTTR, the manufacturer will
determine the initial and aged R-value
as specified by DIN EN 13165:2009–09
and DIN EN 13164:2009–02 except the
panel will be rated at 55 °F and 20 °F
for a cooler and freezer, respectively. By
deviating from the temperature
condition specified in DIN EN
13165:2009–09 and DIN EN
13164:2009–02, the fixed increment
values and safety increment values will
be slightly more conservative than the
values that would be expected if the
LTTR test were performed at the
temperature condition specified in DIN
EN 13165:2009–09 and DIN EN
13164:2009–02, when applied to freezer
panels.
In response to Craig Industries’
comment that whatever method is
adopted should be applicable to
expanded polystyrene foam, DOE notes
that the foam aging procedures it
proposed are only applicable to foams
that rely on low conductivity blowing
agents that are intended to stay within
the foam for the life of the product.
Because it is DOE’s understanding that
expanded polystyrene foam is not
blown with low conductivity blowing
agents that are intended to remain in the
product for its usable life and does not
exhibit long term changes in thermal
resistance, these tests would not apply,
nor would they be needed to assess the
long term thermal resistance of this type
of foam.
One commenter did not agree with
the proposed use of any of the protocols.
Thermo-Kool disagreed with both
ASTM C1303–10 and DIN EN
13165:2009–02 and DIN EN
13164:2009–02 because none of these
protocols, in its view, is designated for
testing composite panels faced with
metal skins. (Thermo-Kool, 0072.1 at p.
1) DOE agrees with Thermo-Kool that
ASTM C1303–10 was not designed to
test panels with metal facers. However,
DIN EN 13165:2009–02 and DIN EN
13164:2009–02 were designed to
account for metal facers on foam. DIN
EN 13165:2009–02 and DIN EN
13164:2009–02 allow all metal skins or
facers to remain on the foam during
aging and testing. See, e.g., DIN EN
13165:2009–02, Annex C (instructing in
relevant part to ‘‘select a product sample
including any product facing.’’).
DOE notes that many of the interested
parties that opposed using ASTM
C1303–10 to measure LTTR supported
using DIN EN 13165:2009–02 and DIN
EN 13164:2009–02 instead. Carpenter
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
agreed with using DIN EN 13165:2009–
02 and DIN EN 13164:2009–02 as an
alternative to ASTM C1303–10.
(Carpenter, No. 0067.1 at p. 2) Hill
Phoenix and AHRI requested more time
to review the European test procedure,
but Hill Phoenix’s initial assessment
was that DIN EN 13165:2009–02 was a
better option than ASTM C1303–10.
(Hill Phoenix, No. 0063.1 at p. 2; AHRI,
No. 0070.1 at p. 2) Hill Phoenix added
that DOE should adopt test procedures
that are appropriate for the insulation
materials that could be found in walkin panels, which DOE interprets to
mean that Hill Phoenix is suggesting
that DOE adopt both DIN EN
13165:2009–02 and DIN EN
13164:2009–02 if DOE uses these
standards instead of ASTM C1303–10.
(Hill Phoenix, No. 0063.1 at p. 2)
Master-Bilt also stated DIN EN
13165:2009–02 and DIN EN
13164:2009–02 seemed to better account
for long-term degradation of foam
performance, though they
acknowledged they did not fully
understand DIN EN 13165:2009–02 and
DIN EN 13164:2009–02. (Master-Bilt,
No. 0069.1 at p. 2)
Other stakeholders had reservations
about DIN EN 13165:2009–02 and DIN
EN 13164:2009–02. Craig Industries
stated that the alternatives to ASTM
C1303–10 may ignore the fact that
different plastic foam product
insulations in the marketplace respond
differently to heat. (Craig Industries, No.
0068.1 at p. 4) It added that DOE should
prevent foamed-in-place walk-in
manufacturers from picking the most
efficient part of the panel for testing.
(Craig, No. 0068.1 at p. 4) Owens
Corning noted that DIN EN 13165:2009–
02 and DIN EN 13164:2009–02 appeared
to be material standards and not test
methods, and Owens Corning asked for
clarification on what the test method
would be. (Owens Corning, 0058.1 at p.
1) NRDC suggested that DOE review the
proposed standards, ASTM C1303–10,
DIN EN 13165:2009–02, and DIN EN
13164:2009–02, to determine which
standard yields better results, and what
the related testing burden would be to
adopt a foreign standard. (NRDC, No.
0064.1 at p. 4)
DOE notes Carpenter’s, Hill
Phoenix’s, AHRI’s, and Master-Bilt’s
approval of DIN EN 13165:2009–02 and
DIN EN 13164:2009–02, and in light of
the criticisms that DOE has received
about ASTM C1303–10 and the support
for DIN EN 13165:2009–02 and DIN EN
13164:2009–02, DOE has decided to
adopt DIN EN 13165:2009–02 and DIN
EN 13164:2009–02 as the test procedure
for determining LTTR of polyurethane
products and extruded polystyrene
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
21591
products, respectively (polyisocyanurate
products are covered by the test for
polyurethane products). Today’s final
rule provides that the LTTR value
determined by Annex C of DIN EN
13165:2009–02 or DIN EN 13164:2009–
02 shall be used to determine a
degradation factor. The degradation
factor will be the LTTR R-value divided
by the original R-value of the foam. The
original R-value of the foam will be
tested with ASTM C518–04, as specified
by the EISA 2007 amendments to EPCA,
and can be used for compliance with the
relevant R-value requirement
established by those amendments. (42
U.S.C. 6313(f)(1)(C)) The degradation
factor is applied to the U-factor of the
panel found by ASTM C1365–05; see
section 4.2 and 4.3 in Appendix A.
In response to Owens Corning’s
comment that DIN EN 13165:2009–02
and DIN EN 13164:2009–02 appeared to
be material standards and not test
methods, DOE notes that Annex C of
both DIN EN 13165:2009–02 and DIN
EN 13164:2009–02 provide the
methodology for testing. DOE also notes
Craig Industries’ concern about using
heat to test for LTTR and NRDC’s
recommendation that DOE compare the
different standards that were proposed;
however, DOE believes DIN EN
13165:2009–02 and DIN EN
13164:2009–02 are more accurate and
appropriate for assessing the long-term
performance of impermeably faced
foams used in walk-in coolers and
freezers because they permit panels to
be tested with their facers, and accounts
for impermeably faced foam. Also, to
address Craig Industries’ concern about
manufacturers not all choosing the same
part of the panel, DOE is requiring that
this test sample should be taken from
the geometric center of the test
specimen.
DOE is largely incorporating DIN EN
13165:2009–02 and DIN EN
13164:2009–02 except for the
requirement that the thermal resistance
measurement is conducted at a mean
temperature of 10 °C. DOE has decided
to adopt the EPCA mean temperatures of
55 °F and 20 °F for a cooler and freezer,
respectively for the DIN EN
13165:2009–09 and DIN EN
13164:2009–02 testing conditions.
However, the manufacturer will still
have to follow any applicable aging
conditions prescribed by DIN EN
13165:2009–09 and DIN EN
13164:2009–02. By deviating from the
temperature condition specified in DIN
EN 13165:2009–09 and DIN EN
13164:2009–02, the fixed increment
values and safety increment values will
be slightly more conservative than the
values that would be expected if the
E:\FR\FM\15APR3.SGM
15APR3
21592
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
srobinson on DSKHWCL6B1PROD with RULES3
LTTR test were performed at the
temperature condition specified in DIN
EN 13165:2009–09 and DIN EN
13164:2009–02, when applied to freezer
panels.
c. Moisture Absorption
In the January 2010 NOPR, DOE
discussed the possibility of testing the
impact of moisture absorption on the Rvalue of different insulation materials,
evaluated various tests developed by
ASTM, and reviewed a research paper
completed by the U.S. Army Corps of
Engineers’ Cold Regions Research and
Engineering Laboratory (CRREL), which
Owens Corning submitted to the docket.
(Owens Corning, No. 0054.3 at p. 1)
DOE initially concluded that testing the
effect of moisture absorption on the Rvalue of insulation foam would be
complex, costly, and time-consuming,
and that there was no well-accepted
testing method. As a result, DOE
proposed that the impact of water
absorption on R-value not be included
in the test procedure. 75 FR 186, 194
(Jan. 4, 2010).
DOE received many comments from
interested parties that supported the
inclusion of some means to account for
the effect of water infiltration. At the
NOPR public meeting, and in several
written comments, Craig Industries
urged DOE to test for and include the
impact of moisture absorption in foam.
(Craig Industries, Public Meeting
Transcript, No. 0016 at p. 248; Craig
Industries, No. 0035.1 at p. 3; Craig
Industries, No. 0068.1 at p. 5; Craig
Industries, No. 0057.13 at p. 5) ACEEE
also stated that it was imperative to
include the effect of moisture
absorption. (ACEE, No. 0052.1 at p. 2)
Kysor maintained that moisture did not
affect the R-value of poured-in-place
polyurethane, but laminated panels
would be severely affected by water
because of the water-based glue used to
bond the insulation to the metal skins.
(Kysor, No. 0053.1 at p. 3)
Some interested parties suggested
possible tests and studies that could be
used to measure the effect of water
absorption. For example, Craig
Industries and Owens Corning referred
to the CRREL study for information
about the performance of various
materials with water. (Craig Industries,
No. 0054.1 at p. 2; Owens Corning,
Public Meeting Transcript, No. 0016 at
p. 250) Nor-Lake suggested that an
adequate test for water absorption
would be ASTM D2842–06, ‘‘Standard
Test Method for Water Absorption of
Rigid Cellular Plastics.’’ (Nor-Lake, No.
0047.1 at p. 3) Owens Corning suggested
that ASTM E96, ‘‘Standard Test Methods
for Water Vapor Transmission of
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
Materials,’’ could be used to test water
vapor permeability rates and determine
the effect of moisture absorption on
foam. (Owens Corning, Public Meeting
Transcript, No. 0016 at p. 253; Owens
Corning, No. 0048.1 at p. 1; Owens
Corning, No. 0032.1 at p. 3) Owens
Corning also suggested that ASTM E96
could be used to identify suitable
materials for walk-in cooler and walk-in
freezer applications. (Owens Corning,
No. 0048.1 at p. 1 and No. 0032.1 at p.
3)
Additionally, joint comments filed by
SCE, SMUD, SDG&E, and SCG on the
January 2010 NOPR, hereafter referred
to as the Joint Comment, added that
although ASTM E96 produces a
conservatively low estimate of moisture
permeance at high vapor pressures, DOE
should evaluate whether using ASTM
E96 is better than not accounting for the
effect of moisture on insulating foam.
(Joint Comment, No. 0037.1 at p. 11)
The Joint Comment added that there
may be difficulties in testing and
characterizing R-value deterioration in
foams due to moisture absorption, but
DOE should still consider a requirement
for testing vapor permeability. (Joint
Comment, No. 0037.1 at p. 1) Owens
Corning also stated that, since DOE
raised the proposed relative humidity
assumption for the test condition from
45 percent to 75 percent in the
September 2010 SNOPR, DOE implicitly
acknowledged the high humidity
conditions present in walk-in cooler and
freezer environments, which, in its
view, supported the consideration of the
impact of moisture on the thermal
performance of a walk-in over its
lifetime. (Owens Corning, No. 0058.1 at
p. 2) ACEEE suggested that because a
major threat to moisture control for
panels is the integrity of the exterior
skin, a minimally intrusive method to
determine the impact of moisture
absorption would be to assess the vapor
diffusion integrity of the sealed panel.
(ACEEE, No. 0052.1 at p. 2)
Other interested parties did not
support including water absorption in
the test procedure. ThermalRite stated
that moisture infiltration was unlikely
to occur in properly constructed panels,
water infiltration would most likely be
the result of improper materials or
manufacturing, and that moisture
infiltration should be considered
inconsequential and removed from
proposed test procedures. (ThermalRite,
No. 0045.1 at p.1; ThermalRite, No.
0045.1 at p. 2; ThermalRite, No. 0049.1
at p.2) ICS commented that water
infiltration is related to panel
installation and that there were no data
to support that moisture infiltration is
caused by the walk-in’s manufacture or
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
design. (ICS, Public Meeting Transcript,
No. 0016 at p. 253; ICS, No. 0045.1 at
p. 1) ICS went on to state that, under
actual and average usage conditions,
water absorption in foam is negligible
and it recommended that the impact of
moisture absorption should be removed
from the proposed test procedure. (ICS,
No. 0045.1 at p. 1; ICS, No. 0045.1 at p.
2) Hill Phoenix commented that
moisture absorption was not an issue
and any moisture issues were generally
reported by the walk-in cooler or walkin freezer user and were quickly
repaired. (Hill Phoenix, No. 0041.1 at p.
2) Carpenter agreed with DOE that the
impact of water absorption of foam
would be difficult to study and quantify,
and added that polyurethane foam has
an inherently low permeability, which
would minimize water absorption.
(Carpenter, No. 0043.1 at p. 2) TAFCO
concurred that moisture infiltration into
polyurethane foam is not an issue, and
that it would not cause the R-value to
degrade significantly over time.
(TAFCO, No. 0040.1 at p. 2) TAFCO also
stated that they have installed panels in
high-humidity environments and they
did not encounter any cases of water
absorption by panels. It urged that DOE
not pursue this issue further. (TAFCO,
No. 0040.1 at p. 2)
DOE understands that interested
parties have concerns regarding the
potential impact of moisture absorption
on the thermal performance of
insulating material over the lifetime of
a walk-in cooler or freezer. Prior to the
publication of the January 2010 NOPR,
DOE reviewed several methods for
testing vapor permeance and water
absorption in foam insulation materials.
However, this review of various test
methods showed that there were
disparities among the different methods,
and that there was no general agreement
upon a single approach. 75 FR 186, 194
(Jan. 4, 2010). Moreover, while these
tests are designed to measure the
performance of insulating foam by itself,
they would not account for the many
unique construction methods and
combinations of materials employed by
manufacturers of panels to minimize
moisture infiltration.
At this time, test procedures for
measuring the impact of water on foam
R-value are not yet recognized by a
national organization such as ASTM.
DOE notes that because of the absence
of any nationally recognized testing
standards, it would need to develop
such a protocol. To this end, one of
DOE’s national labs is in the process of
developing procedures to evaluate the
impact of moisture on insulation Rvalues. Accordingly, because of the
potential ambiguities that are currently
E:\FR\FM\15APR3.SGM
15APR3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
present with respect to the means by
which to assess the impact of moisture
absorption on the thermal performance
of insulating material over time, DOE is
not incorporating a method to account
for moisture absorption at this time.
DOE may, however, consider adopting
such a procedure in the future.
d. Display Panels
In the September 2010 SNOPR, DOE
proposed that glass walls (‘‘display
panels’’) would be tested using NFRC
100–2001–E0A to measure their thermal
transmittance, or U-factor. 75 FR 55068,
55098 (Sept. 9, 2010). Display panels are
typically found on beer caves and share
many characteristics with display doors.
Notably, they are readily tested or
simulated using the procedure in NFRC
100–2001–E0A. DOE received no
comments regarding its proposed
approach for display panels.
Consequently, DOE is including this test
procedure (to be codified in section 4.1
of Appendix A) to measure the thermal
transmittance of display panels or walls.
Additionally, to improve clarity, DOE is
defining ‘‘display panels’’ as a panel that
is entirely or partially comprised of
glass, a transparent material, or both and
is used for display purposes.
e. Open Areas of Walk-Ins
The test procedure DOE is
establishing today contains tests for
components of walk-ins that separate
the interior refrigerated environment of
the walk-in from the exterior. Zero Zone
stated that the test procedure should
include a method to determine the
energy use for walk-ins that have open
areas to display food. (Zero Zone, No.
0077.1 at p. 1) Because an open area
does not, by definition, separate the
interior refrigerated environment of the
walk-in from the exterior, an open area
is not a component of the walk-in that
is covered under this test procedure.
Accordingly, DOE is not adopting Zero
Zone’s suggestion.
3. Energy Use of Doors
srobinson on DSKHWCL6B1PROD with RULES3
a. U-Factor of Doors
In the September 2010 SNOPR, DOE
proposed to rate the total thermal
transmittance (i.e. U-factor) of doors,
including their framing materials or
complete door plug, using the test
procedure NFRC 100–2010[E0A1],
‘‘Procedure for Determining Fenestration
Product U-factors.’’ 75 FR 55068, 55083
(Sept. 9, 2010). DOE specified internal
and external rating conditions for the
test procedure to closely match
conditions that would be experienced
by the door when it is part of a walkin.
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
NEEA strongly supported DOE’s use
of NFRC 100–2010[E0A1] procedures
for testing the performance of walk-in
cooler and freezer doors. (NEEA, No.
0061.1 at p. 2) NRDC agreed with DOE’s
use of NFRC 100–2010[E0A1] for rating
doors with the proposed changes to the
temperatures used for the testing
procedure. (NRDC, No. 0064.1 at p. 6)
DOE notes NEEA’s and NRDC’s
support and has incorporated the use of
NFRC 100–2001–E0A1 in this final rule.
DOE also notes that none of the
interested parties submitted comments
that disagreed with using NFRC 100–
2001–E0A1. The thermal transmittance
result from NFRC 100–2001–E0A1 is
then used to calculate the corresponding
energy consumption of a refrigeration
system whose efficiency is given in
sections 4.4 and 4.5 of Appendix A for
display and non-display doors,
respectively. This energy metric is
combined with the electricity
consumption from electrical door
components to calculate the door’s total
energy consumption.
b. Electrical Components of Doors
As described in section III.A.1, the
test metric for doors includes the energy
consumed by electrical components
associated with a walk-in door. The
electricity consumed by the door will be
the sum of the rated power associated
with each electricity consuming device
multiplied by the assumed time the
device will be operational. Percent time
off (PTO) assumptions are given in
sections 4.4.2 and 4.5.2 of Appendix A
for display and non-display doors,
respectively. PTO assumptions are
specified for some electrical
components, such as anti-sweat heater
wire. For any electricity consuming
devices for which a PTO is not specified
in Appendix A, today’s final rule
provides that if a manufacturer can
demonstrate that the device is
controlled by a preinstalled timer,
control system or other auto-shut-off
system, the PTO is assumed to be 25
percent. For example, if a door has a
thermometer mounted on it that
consumes electricity, but the
thermometer has a built in timer so that
it shuts off at certain times, then the
manufacturer of the door can use the
PTO value of 25 percent when
calculating the energy consumption of
the thermometer.
The test procedure also provides a
means for measuring the heat generation
of door electrical components that are
located on the inside surface of the
door. This heat is added to the heat
transmitted through the door and the
corresponding refrigeration energy use
is calculated using the method
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
21593
described in section III.B.3.c. The
refrigeration energy use is added to the
electrical energy use to calculate the
total energy consumption of the door.
DOE received a comment challenging
its assumptions about heat from
electrical devices. Zero Zone disagreed
with the assumption that all anticondensate heat contributes to the walkin heat load, and instead suggested that
50 to 75 percent of the anti-condensate
heat going into the display case would
be a more appropriate assumption. (Zero
Zone, No. 0077.1 at p. 2) After further
analysis, DOE agrees with Zero Zone’s
observation that not all anti-condensate
heat necessarily contributes to the walkin heat load because the anti-condensate
heat is applied to the transparent
surface of the display case. Because one
side of the transparent surface is in
contact with the surrounding external
environment, a portion of the heat is
transmitted from the display case to the
surrounding environment. Therefore,
DOE has revised the equations in
sections 4.4.2and 4.5.2of Appendix A to
capture only 75 percent of the power
from anti-sweat heaters as an additional
compressor load.
c. Energy Efficiency Ratio
In the January 2010 NOPR, DOE
proposed to require that manufacturers
measure the energy use of walk-in
cooler and walk-in freezer envelopes in
kWh/day. However, most metrics used
to describe heat transfer losses are in
units of British thermal units (Btu) per
unit time. In order to convert the
thermal energy transmission calculation
(Btu/hr) into a measure of electrical
energy consumed by the refrigeration
equipment, DOE proposed to use an
energy efficiency ratio based on a
nominal efficiency of an assumed
refrigeration system. The EER values
proposed for coolers and freezers were
12.4 Btu/W-h and 6.3 Btu/W-h
respectively. The values were selected
to provide a means of comparison and
were not intended to represent the
actual efficiency of the refrigeration
system with which the envelope would
ultimately be paired. 75 FR 186, 197
(Jan. 4, 2010). Although the test
procedure no longer requires one to
calculate the overall envelope energy,
the concept is still relevant for
calculating door energy.
DOE received comments in response
to the January 2010 NOPR regarding the
use of an EER value, the assumptions
used to calculate the EER value, and the
proposed EER values for coolers and
freezers. BASF commented that the
proposed EER assumptions were
reasonable. (BASF, No. 0021.1 at p. 4)
Nor-Lake agreed with DOE’s use of a
E:\FR\FM\15APR3.SGM
15APR3
21594
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
srobinson on DSKHWCL6B1PROD with RULES3
nominal EER value to convert the
thermal energy transmission to
electrical energy consumption. (NorLake, No. 0047.1 at p. 5) Master-Bilt also
agreed with the proposed use of a
nominal EER but stated that the
proposed EER values are not achievable.
(Master-Bilt, No. 0027.1 at p. 2) Kason
requested that the nominal EER values
be reassessed to represent real world
values. (Kason, No. 0055.1 at p. 4) NorLake commented that the EER values on
their refrigeration models did not match
DOE’s proposed nominal values. (NorLake, 0023.1 at p. 4)
DOE considered these comments and,
in conjunction with the supportive
comments from Master-Bilt, Nor-Lake,
and BASF, continues to use an EER
value to relate the thermal energy
transmission to the electrical energy
consumed for doors. Despite the
comments from Kason, Master-Bilt, and
Nor-Lake, DOE finds 12.4 Btu/W-h and
6.3 Btu/W-h to be appropriate
conversions for walk-in coolers and
walk-in freezers, respectively, because
these EER values correspond to nominal
EER values contained in the
refrigeration test procedure for unit
coolers connected to multiplex
condensing systems (AHRI 1250 (I–P)–
2009). DOE is aware that the nominal
values for this configuration may not
represent all walk-ins, but notes that
these EER values are intended to
provide a means of comparison and not
directly reflect a real walk-in
installation. In particular, these EER
assumptions are not intended to
represent the expected efficiency of any
particular refrigeration system produced
by a manufacturer and are provided as
a method to converting thermal energy
to electrical energy consumed by a
refrigeration system.
4. Heat Transfer via Air Infiltration
In the January 2010 NOPR, DOE
stated that, compared with other energy
consumption factors such as conduction
losses through insulation, air infiltration
may be the largest contributing factor to
envelope thermal load. That notice
identified two infiltration pathways:
steady state leakage and air losses due
to door-opening events. To address this
issue, DOE proposed to include test
procedures to measure the steady state
infiltration and infiltration from door
opening events and subsequently
modified these test procedures in
response to comments to the September
2010 SNOPR. See 75 FR 196–197 (Jan.
4, 2010) and 75 FR 55084–55086 (Sept.
9, 2010). Interested parties submitted
comments pertaining to the topic of
envelope infiltration, including steady
state infiltration, door opening
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
infiltration, calculations, and empirical
methodologies for quantifying the
effects of infiltration.
a. Steady State Infiltration
In the January 2010 NOPR, DOE
proposed that steady state infiltration of
fully assembled envelopes must be
tested using the method described in
ASTM E741–06, ‘‘Standard Test Method
for Determining Air Change in a Single
Zone by Means of a Tracer Gas
Dilution.’’ 75 FR 196 (Jan. 4, 2010).
Some interested parties stated that
steady state infiltration should not be
included in the test procedure. Hill
Phoenix maintained that an insufficient
amount of infiltration would occur in a
properly installed walk-in, essentially
suggesting that DOE abandon the
inclusion of infiltration in the test. (Hill
Phoenix, No. 0063.1 at p. 2) AHRI
concurred, stating that a steady-state
infiltration test is not necessary due to
the insignificant amount of infiltration
present in a walk-in * * * (AHRI, No.
0070.1 at p. 3) Master-Bilt agreed,
suggesting that testing steady-state
infiltration is unnecessary because this
infiltration is insignificant compared
with infiltration from door openings.
(Master-Bilt, No. 0069.1 at p. 2) NRDC
suggested that DOE confirm the
assumption that the impact of
infiltration and exfiltration through the
envelope is minimal compared to the
infiltration through the doors, and
suggested that DOE should weigh each
impact. (NRDC, No. 0064.1 at p. 6)
Other interested parties commented
on the specific test methods DOE
proposed in the January 2010 NOPR for
measuring steady-state infiltration of
walk-in envelopes. TAFCO stated that
ASTM E741–06, Standard Test Method
for Determining Air Change in a Single
Zone by Means of a Tracer Gas Dilution,
is an acceptable method for determining
steady state air infiltration. (TAFCO, No.
0040.1 at p. 3) ACEEE also agreed with
using ASTM E741–06. (ACEEE, 0052.1
at p. 3) NEEA commented that either
ASTM E741–06 or a standard blower
test is a reasonable method of
calculating steady state infiltration, but
noted that the blower test would be
faster and less costly to administer.
Therefore, NEEA recommended that
DOE test ASTM E741–06 and the
standard blower door test before
prescribing which methodology must be
used. (NEEA, No. 0061.1 at p. 2) Kysor,
on the other hand, stated that it is
neither necessary nor cost effective to
assemble an entire walk-in to test for air
infiltration. Kysor stated that each
component should be tested separately
and recommended that DOE use ASTM
E1424–08, Standard Test Method for
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
Determining the Rate of Air Leakage
Through Exterior Windows, Curtain
Walls, and Doors Under Specified
Pressure and Temperature Differences
Across the Specimen, and ASTM
E2357–05, Standard Test Method for
Determining Air Leakage of Air Barrier
Assemblies, because either can test any
assembly that will become part of a
walk-in. (Kysor, No. 0053.1 at p. 3)
In the January 2010 NOPR, DOE
proposed that ASTM E741–06 should be
used to measure infiltration; however,
in the September SNOPR, DOE
determined that ASTM E741–06 could
present an undue burden for
manufacturers with respect to the many
door combinations that are possible.
Therefore, DOE proposed in its
September 2010 SNOPR to also consider
measuring steady state infiltration
through doors using NFRC 400–2010–
E0A1, ‘‘Procedure for Determining
Fenestration Product Air Leakage.’’ 75
FR 55068, 55084 (Sept. 9, 2010).
Interested parties commented on
NFRC 400–2010–E0A1 and suggested
alternatives. NRDC agreed with using
NFRC 400–2010–E0A1 to determine
infiltration of individual envelope
components, but also recommended
using a pressurization test to determine
infiltration of fully assembled
envelopes, based on ASTM D6670,
‘‘Standard Practice for Full-Scale
Chamber Determination of Volatile
Organic Emissions from Indoor
Materials/Products.’’ (NRDC, No. 2.3.008
at p. 6) AHRI recommended that
infiltration could be estimated for a
family of doors by using a scaling
methodology based on a limited number
of tests. AHRI cautioned DOE against
requiring the manufacturer to test every
single door because it would be
burdensome. (AHRI, No. 2.3.015 at p.3)
Some interested parties commented on
the prescribed testing conditions to be
implemented with NFRC 400–2010–
E0A1. American Panel stated that the
proposed steady state infiltration test
unit is not representative of the average
walk-in size and suggested a more
representative size of 8 feet by 12 feet
by 8 feet high. (American Panel, No.
2.3.001 at p. 3) American Panel, NEEA,
and Bally concurred with DOE’s
assumption of 75 percent relative
humidity, which DOE proposed as a
condition of testing. (American Panel,
No. 2.3.001 at p. 3; NEEA, No. 2.3.005
at p. 5; Bally, No. 0078.1 at p.2)
DOE notes the specific comments and
suggestions from TAFCO, NEEA,
ACEEE, Kysor, NRDC, AHRI, and
American Panel, but has decided not to
include steady state infiltration in the
WICF test procedure at this time. In
response to NRDC’s suggestion that DOE
E:\FR\FM\15APR3.SGM
15APR3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
srobinson on DSKHWCL6B1PROD with RULES3
weigh the impact of steady-state
infiltration against other sources of
infiltration, DOE believes that the
contribution of steady state infiltration
towards the aggregate energy
consumption of a well-constructed
factory-built walk-in unit is most likely
negligible compared to other energy
consumption pathways for current
WICF designs. Higher steady-state
infiltration across the envelope for siteassembled walk-in coolers and freezers
appears to be generally caused by poor
installation and construction practices.
As such, DOE is not incorporating an
overall infiltration measurement, which
is a factor that relies heavily on on-site
assembly practices rather than the
performance of individual components.
Given that today’s final rule includes a
means to assess the performance of
specific individual components, the
performance of these components will
be captured under the new procedure
and should be sufficiently adequate
prior to their installation as part of a
completed walk-in unit. Should this
prove not to be the case, DOE may reexamine the procedure and consider
modifications to address its potential
shortcomings.
b. Door Opening Infiltration
In the January 2010 NOPR, DOE
proposed to calculate air infiltration
associated with each door-opening
event using established analytical
methods based on equations and
computational values published in the
ASHRAE Refrigeration Handbook. DOE
also made several assumptions in the
test procedure that could have a
significant impact on the predicted air
exchange. The assumptions with the
most impact were the number of
doorway passages (the number of dooropening cycles for a given door), door
open-close time, and the amount of time
the door is held or propped open. 75 FR
186, 196 (Jan. 4, 2010). In the September
2010 SNOPR, DOE did not propose to
change the basic methodology, but
modified some of the assumptions in
order to differentiate door types. 75 FR
55068, 55085 (Sept. 9, 2010).
Some interested parties supported the
proposed method. Hired Hand agreed
with the methodology used for
calculating the air infiltration from door
openings. (Hired Hand, Public Meeting
Transcript, No. 0016 at p. 309) Hired
Hand emphasized that air infiltration
may be the largest contributing factor to
envelope energy losses. (Hired Hand,
Public Meeting Transcript, No. 0016 at
p. 28; Hired Hand, Public Meeting
Transcript, No. 0016 at p. 279; Hired
Hand, Public Meeting Transcript, No.
0016 at p. 285) American Panel
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
suggested the use of ASHRAE values for
heat load as the best way to account for
the effects of air infiltration. (American
Panel, No. 0042.1 at p. 2) ThermalRite,
Nor-Lake, and Master-Bilt agreed with
American Panel’s suggestion.
(ThermalRite, No. 0049.1 at p. 2; NorLake, No. 0047.1 at p.4; Master-Bilt,
Public Meeting Transcript, No. 0016 at
p. 311) Master-Bilt and Zero Zone also
agreed with DOE’s assumptions
regarding infiltration attributed to door
openings. (Master-Bilt, No. 0069.1 at p.
2; Zero Zone, No. 0077.1 at p. 2)
Other interested parties questioned
the applicability of the method to walkin cooler and freezer doors, or
questioned DOE’s assumptions in
calculating door opening infiltration.
Schott Gemtron contended that
ASHRAE equations may be based on
supermarket display cases, implying
that they may not be applicable to some
walk-in doors. (Schott Gemtron, Public
Meeting Transcript, No. 0016 at p. 314)
Hired Hand was concerned that the
proposed test procedures do not account
for the effect of fast-acting doors on air
infiltration. (Hired Hand, Public
Meeting Transcript, No. 0016 at p. 286)
SCE and Hired Hand both stated that the
parameters used to calculate air
infiltration should clearly show the
benefit of fast-acting doors. (SCE, Public
Meeting Transcript, No. 0016 at p. 320;
Hired Hand, Public Meeting Transcript,
No. 0016 at p. 320) Hired Hand also
recommended that the equations used to
calculate air infiltration should be based
on the operational time the doors are
opened over an assumed 24-hour day.
(Hired Hand, No. 0051.1 at p. 4) Zero
Zone stated that any air infiltration
calculations should include additional
air infiltration if the evaporator is
discharging air in the direction of the
display doors. (Zero Zone, No. 0077.1 at
p. 1) Bally stated that hybrid walk-ins,
that is, walk-ins sited within another
walk-in, should be given beneficial
consideration. Bally explained that a
walk-in freezer sited inside a walk-in
cooler would experience less infiltration
because of the smaller temperature
differential between the interior and
exterior of the freezer. (Bally, No. 0078.1
at p.2)
Interested parties also made specific
comments on the effect of infiltration
reduction devices (IRDs). ACEEE and
ThermalRite supported the infiltration
device effectiveness test methodology.
(ACEEE, No. 0052.1 at p. 3;
ThermalRite, No. 0049.1 at p. 2) TAFCO
also stated that ASTM E741–06 is an
acceptable method for determining IRD
effectiveness. (TAFCO, No. 0040.1 at p.
3) NRDC stated that the proposed door
opening infiltration calculation from
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
21595
ASHRAE Fundamentals 2009 is
acceptable for conventional doors, but
when doorways are protected by an air
curtain or other infiltration reduction
device, calculations should include the
effect of such devices on energy use.
(NRDC, No. 0064.1 at p. 6)
Master-Bilt commented that air
infiltration from door openings cannot
be modeled in a meaningful way and
should be excluded from the test
methodology. (Master-Bilt, No. 0027.1 at
p. 2) Hill Phoenix noted that the panel
manufacturer has no bearing on door
opening frequency, which accounts for
the majority of the infiltration. (Hill
Phoenix, No. 0063.1 at p. 2) NEEA
suggested that DOE should not make
assumptions about the nature of the use
of a particular walk-in. (NEEA, No.
0061.1 at p. 5) Instead, it recommended
that DOE include a prescriptive
requirement for infiltration reduction
devices. (NEEA, No. 0061.1 at p. 5)
DOE has decided not to include any
test procedure for door opening
infiltration following its decision to
have component-level test procedures
and standards. Door infiltration is
primarily reduced by incorporating a
separate infiltration reduction device at
the assembly stage of the complete
walk-in. Based on DOE’s understanding
of the door manufacturing industry, a
typical door manufacturer has very few
direct means for reducing the door
infiltration on its own since IRDs are
generally designed and manufactured
independently from doors and they
require proper field installation to
achieve rated performance.
Consequently, at this time, DOE is not
incorporating provisions that would
require measuring the effectiveness of
the infiltration reduction devices and
door infiltration, as suggested by
Master-Bilt, Hill Phoenix, and NEEA.
Likewise, reduction of door infiltration
due to the location of the walk-in is not
captured, as suggested by Bally.
In response to NEEA’s comment
recommending a prescriptive standard,
DOE notes that EPCA has already
established a prescriptive requirement
for infiltration reduction devices, and
there may be limited if any benefit to
DOE adding additional prescriptive
standards for infiltration reduction
devices. (42 U.S.C. 6313(f)(1)(B))
Nevertheless, DOE will consider the
need for these types of standards within
the context of its ongoing energy
standards rulemaking.
5. Electrical Components
In the January 2010 NOPR, DOE
proposed to calculate the energy
consumption of electrical devices using
their nameplate rating and duty cycle
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
21596
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
assumptions about their daily operation.
In addition, the heat loads from
electrical devices were factored into the
envelope refrigeration load calculations.
DOE proposed to incorporate 100
percent of the electrical energy
consumed to operate the devices that
are internally located and to convert the
electrical energy consumed to a thermal
load. The associated thermal load was
then used to calculate the additional
refrigeration load using the nominal
refrigeration EER values described in
section III.B.3.c. DOE also proposed a
variety of PTO values in the NOPR to
account for reductions in energy use
due to component control and hours of
usage. 75 FR 186, 198 (Jan. 4, 2010).
BASF supported including electricity
consumption as part of the energy
calculation, and concurred with the
duty cycle assumptions. (BASF, No.
0021.1 at p. 5) Master-Bilt and Nor-Lake
also agreed with the electrical duty
cycle equation proposed by DOE.
(Master-Bilt, No. 0027.1 at p. 2; NorLake, No. 0023.1 at p. 4) ACEEE
supported the methods and assumptions
for PTO values and electrical loads and
agreed with the use of nameplate power
ratings because it encouraged load
reduction. (ACEEE, No. 0052.1 at p. 3)
ThermalRite noted that while it did not
fully understand how the proposed PTO
values listed in the January 2010 NOPR
were developed, it believed that the
proposed values represented a fair
method of comparison among
manufacturers because the same
assumptions are made for all users.
ThermalRite asked that DOE ensure that
the values include all device types.
(ThermalRite, No. 0049.1 at p. 2) ORNL
requested that DOE include the ground
heater below the floor insulation as part
of the energy use calculation. (ORNL,
No. 0028.1 at p. 2) Craig Industries
requested that DOE accommodate highefficiency heater wires that apply heat
on demand. (Craig Industries, Public
Meeting Transcript, No. 0016 at p. 325
and No. 0054.1 at p. 3) Finally, NorLake expressed the opinion that the
proposed PTO values for lights are low
because in most applications the lights
would be shut off each night for 8 hours.
(Nor-Lake, No. 0047.1 at p. 5)
DOE notes support from BASF,
Master-Bilt, Nor-Lake, ACEEE, and
ThermalRite for its methodology and
assumptions. DOE is also aware of the
concerns presented by ORNL, Craig
Industries, and Nor-Lake. However,
since DOE will implement a
component-based standard, electrical
components not part of a door are not
included in the component test or
component metric. DOE notes that
assemblers or manufacturers of
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
complete walk-ins must still use
lighting that complies with the efficacy
standard prescribed in EPCA. (42 U.S.C.
6313(f)(1)(G)) DOE will continue to use
the method proposed in the January
2010 NOPR to calculate the energy
consumption of lights, sensors, and
other miscellaneous electrical devices
associated with walk-in doors.
Regarding Craig Industries’ specific
comment about door heater wire, DOE’s
PTO assumptions take into account
demand-based control of components,
which includes the loads from door
heater wires. PTO assumptions are
given in sections 4.4.2 and 4.5.2 of
Appendix A for display and non-display
doors, respectively. See section III.B.3.b
for further discussion of electrical
components of doors.
C. Test Procedures for Refrigeration
Systems
The refrigeration system is the
equipment that performs the mechanical
work necessary to cool the interior
space of a walk-in cooler or freezer. As
previously discussed, DOE considers
the refrigeration system an individual
component of the walk-in cooler or
walk-in freezer. Therefore, in this test
procedure, DOE establishes a test of the
performance of a refrigeration system
itself, assuming nominal envelope
characteristics. In the concurrent
standards rulemaking, DOE intends to
establish energy conservation standards
for the refrigeration system. See
generally 75 FR 17080 (April 5, 2010).
The following sections address issues
raised by interested parties on the
January 2010 NOPR and September
2010 SNOPR.
1. Definition of Refrigeration System
In the January 2010 NOPR, DOE
proposed a definition of refrigeration
system that described three types of
systems that would be covered: (1)
Single-package systems containing the
condensing and evaporator units; (2)
split systems with the condensing unit
and unit cooler physically separated
and connected via refrigerant piping; or
(3) unit coolers that receive refrigerant
from a compressor rack system shared
with other refrigeration equipment. 75
FR at 200 (Jan. 4, 2010). In the
September 2010 SNOPR, DOE proposed
minor revisions to that definition to
clarify some of these terms. That notice
proposed the following definitions:
Refrigeration system means the mechanism
(including all controls and other components
integral to the system’s operation) used to
create the refrigerated environment in the
interior of a walk-in cooler or freezer,
consisting of (1) a packaged system where the
unit cooler and condensing unit are
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
integrated into a single piece of equipment,
(2) a split system with separate unit cooler
and condensing unit sections, or (3) a unit
cooler that is connected to a multiplex
condensing system.
75 FR 55068, 55093 (Sept. 9, 2010).
NRDC, Craig Industries, and MasterBilt agreed with the revisions proposed
in the September 2010 SNOPR. (NRDC,
No. 0064.1 at p. 7; Craig Industries, No.
0068.1 at p. 5; Master-Bilt, No. 0069.1 at
p. 3) Other interested parties did not
agree with the classification contained
in the definition or the types of systems
covered. NEEA stated that the three
refrigeration types do not accurately
represent the market, and recommended
that the equipment classification should
instead match the classifications
contained in DOE’s regulations for
commercial refrigeration equipment.
(NEEA, No. 0061.1 at pp. 2 and 4) The
Joint Utilities also disagreed with the
concept of defining systems as
‘‘matched’’ (‘‘packaged’’ or ‘‘split’’
systems as termed in the proposed
definition) or ‘‘remote’’ (a unit cooler
connected to a multiplex condensing
system as in the proposed definition).
(Joint Utilities, No. 0059.1 at p. 2) Like
NEEA, the Joint Utilities suggested that
DOE change its proposed definition by
adopting the approach taken with the
commercial refrigeration equipment
efficiency regulations: ‘‘packaged’’
systems should be termed ‘‘selfcontained condensing units’’ and all
other condensing units should be
considered ‘‘remote condensing units.’’
The Joint SNOPR comment also agreed
with this approach, suggesting that DOE
classify refrigeration systems as selfcontained (packaged systems) or unit
coolers connected to remote condensing
units (both dedicated and multiplex). It
also suggested that for remote
condensing systems, any applicable
energy conservation standards should
only apply to the unit cooler. (Joint
SNOPR Comment, No. 0074.1 at p. 3)
DOE believes the three types of
refrigeration systems described in the
definition accurately represent the range
of refrigeration equipment that is used
in walk-in coolers and freezers.
Although the definition differs from the
definition for commercial refrigeration
equipment, there are key differences
between commercial refrigeration
equipment refrigeration systems and
walk-in refrigeration systems that make
a new definition necessary. NEEA and
the Joint Utilities refer to two common
types of commercial refrigeration
equipment refrigeration units. Some are
‘‘self-contained’’ (meaning the entire
refrigeration system is built into the
case). Others are ‘‘remote condensing’’
(meaning the unit cooler is built into the
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
case, but the whole case is connected to
a central system of compressors and
condensers (called a ‘‘rack’’ or
‘‘multiplex condensing system’’) that is
connected to most or all of the
refrigeration units in a building). The
latter configuration is common in
supermarkets. For all remote
condensing systems, the commercial
refrigeration equipment test procedure
rulemaking assumed a certain efficiency
of the multiplex condensing system and
the standards rulemaking did not
regulate this part of the equipment. 71
FR 71340 and 74 FR 1092.
However, ‘‘remote condensing’’ can
also refer to a configuration in which
the unit cooler is connected to a
dedicated (that is, only serving that one
unit) compressor and condenser that are
located somewhere away from the walkin. This configuration is very rare for
commercial refrigeration equipment but
comprises a large proportion of walk-in
refrigeration system applications. For
this reason, DOE does not agree with the
suggestion of NEEA and the Joint
Utilities that this configuration should
be classified as ‘‘remote condensing’’
and does not agree that the compressor
and condenser parts should not be
covered under the walk-in coolers and
freezers rulemaking. Rather, DOE
believes that a dedicated condensing
unit should be included in the rule,
even if it is remotely located, because it
could be viewed as part of the walk-in
cooler as long as it is connected only to
that cooler and not to other refrigeration
equipment. For systems where the walkin is connected to a multiplex
condensing system that runs multiple
pieces of equipment, the compressor
and condenser would not be covered
because they are not exclusively part of
the walk-in.
In consideration of the above, DOE
believes the commercial refrigeration
equipment definition cannot be applied
to walk-ins, because there is a certain
type of walk-in refrigeration—namely, a
split system with a dedicated but
remotely located condensing unit—that
is highly represented in walk-ins but
rarely, if ever, represented in
commercial refrigeration equipment.
Thus, while the Joint Comment
compares walk-in refrigeration systems
to commercial refrigeration equipment,
DOE believes this is not a relevant
comparison. A closer comparison would
be to residential central air
conditioners—an example of equipment
that almost always has a dedicated, but
remotely located, condensing unit. In
that instance, DOE’s definition covers
this type of remote condensing unit.
Furthermore, DOE notes that
manufacturers can optimize the
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
dedicated, remote condensing unit with
the unit cooler to take advantage of
certain conditions such as low ambient
outdoor temperatures. Therefore, DOE
has retained the proposed definition’s
coverage of dedicated remote
condensing systems. To further clarify
this coverage, DOE has added the term
‘‘dedicated’’ to describe packaged
systems and split systems in the
definition it is adopting today.
2. Refrigeration Test Procedure: AHRI
1250 (I–P)–2009
DOE proposed to incorporate the
industry standard AHRI 1250–2009,
‘‘2009 Standard for Performance Rating
of Walk-In Coolers and Freezers,’’ into
the test procedure. (The January 2010
NOPR referred to the preliminary
version of this standard, AHRI 1250P–
2009. The SNOPR updated this
reference to the final version.) 75 FR
186, 200–201 (Jan. 4, 2010) and 75 FR
55068, 55086 (Sept. 9, 2010). DOE
proposed that manufacturers use this
standard to rate the refrigeration
systems of walk-in coolers and freezers.
AHRI 1250–2009 covers the testing of
refrigeration systems for walk-in coolers
and freezers, which includes unit
coolers and condensing units that are
sold together as a matched system, unit
coolers and condensing units that are
sold separately, and unit coolers
connected to compressor racks. The
procedure describes the method for
measuring the refrigeration capacity and
the electrical energy consumption for
the condensing unit and the unit cooler,
as well as the off-cycle fan energy and
the defrost subsystem under specified
test conditions. The standard test
conditions specify the dry-bulb and wetbulb temperatures of the air surrounding
the unit cooler and the condensing unit.
The standard test conditions are
different for indoor and outdoor
locations for the condensing unit and
for coolers and freezers.
The AHRI procedure also specifies the
calculations used to ascertain the
nominal box loads under typical lowload and high-load conditions,
expressed as a function of the ambient
air temperature. (The ‘‘nominal box
load’’ refers to the refrigeration load
imposed on the system by the walk-in
envelope.) During the test, the system
must operate under steady-state
conditions. For systems in which the
condensing unit is located outdoors, the
test procedure uses bin temperature data
and bin hour data to represent the
impact of the seasonal variation in
outside ambient air temperature on
energy use. The test procedure provides
a calculation methodology to compute
an annual walk-in efficiency factor
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
21597
(AWEF) for the refrigeration system
under a specified load profile. For unit
coolers and condensing units sold
separately, the test procedure allows for
testing the components individually and
then calculating the system AWEF from
the component test results.
Several interested parties agreed with
DOE’s proposed methodology. AHRI
urged DOE to allow a rating of walk-in
refrigeration systems using the
calculation methodologies in the
proposed protocols contained in AHRI
1250. (AHRI, No. 0070.1 at p. 2)
American Panel, Thermo-Kool, Bally,
and NRDC also supported DOE’s
proposal to allow the evaporator and
condensing unit to be tested separately
according to the proposed methodology.
(American Panel, No. 0057.1 at p. 1;
Thermo-Kool, No. 0072.1 at p. 1; Bally,
No. 0078.1 at p. 3; NRDC, No. 0064.1 at
p. 3) Craig Industries supported a
formula that would allow the efficiency
of the refrigeration system to be
calculated from testing data provided by
each component supplier. (Craig, No.
0068.1 at p. 3) Heatcraft advised that the
refrigeration system procedure should
allow for testing new components.
(Heatcraft, No. 0065.1 at p. 1) However,
the Joint Utilities disagreed with the
assumption in AHRI 1250–2009 that
unit coolers and remote condensing
units that are sold separately will be
matched and installed together, and
stated that AHRI 1250–2009 does not
allow unit coolers to be compared with
each other unless they have been tested
on the same condensing unit. (Joint
Utilities, No. 0059.1 at p. 2) No parties
opposed DOE’s proposal to allow
evaporator and condensing unit to be
tested separately.
DOE notes the support of AHRI,
American Panel, and NRDC for the
proposed method and incorporates it
into this final rule. In response to
Heatcraft’s suggestion that the
procedure should allow for testing new
components, DOE anticipates that the
method will lead to manufacturers
testing unit coolers and condensing
units when they are manufactured
separately, so that they can be used in
new systems. Regarding the issues
raised by Craig Industries and the Joint
Utilities, DOE emphasizes that the
proposed procedure contains a
calculation method by which the overall
refrigeration performance can be
calculated using testing data from a
condensing unit and unit cooler, even if
the two components are provided by
different suppliers. The test results for
a unit cooler or condensing unit are
independent from whichever
condensing unit or unit cooler is
matched with the tested component. In
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
21598
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
contrast, the test results for each
component are in the form of a
performance curve to facilitate
calculation of matched performance,
which, as suggested by the Joint
Utilities, does not lend itself to
meaningful comparisons between unit
coolers without matching the particular
unit coolers with the same condensing
unit. DOE acknowledges this limitation
but believes it is important to maintain
the results in terms of the performance
curve to facilitate calculation of the
performance of the system as a whole,
because the entire refrigeration system
is treated as a component under the
approach adopted in today’s final rule.
Given that the refrigeration system is
treated as a single component under the
procedure, the procedure offers a simple
method for determining the energy
efficiency profile of the walk-in
refrigeration system because it allows
the unit cooler and condensing unit to
be tested separately.
Additionally, DOE notes that if unit
coolers are tested and rated as if they
were to be combined with a multiplex
condensing system, they could be
compared against each other. The test
data for unit coolers in a mix-match
system include the data necessary for
calculating the unit cooler’s
performance when paired with a
multiplex condensing system. Thus, it
would be relatively simple for
manufacturers of unit coolers to provide
both the performance data for matching
purposes and the performance as
connected to a multiplex condensing
system. DOE may consider requiring
this information as part of any related
labeling requirements for WICF
equipment.
While interested parties generally
agreed with the adoption of AHRI 1250–
2009, others disagreed with how that
method would be applied to different
system configurations. The Joint
Utilities and NEEA both recommended
that all remote condensing systems be
tested using the ‘‘walk-in unit cooler
match to parallel rack system’’ test
method and noted that the matched
system approach only be used for selfcontained condensing units. (Joint
Utilities, No. 0059.1 at p. 3; NEEA, No.
0061.1 at p. 4) The Joint Utilities further
stated that the proposed AHRI 1250–
2009 test method for rating dedicated
remote condensing systems would
create confusion and additional testing
burden because there are many different
test methods and categories for different
locations and types of condensing units.
(Joint Utilities, No. 0059.1 at pp. 2 and
5) Other interested parties questioned
the methodology for rating unit coolers
connected to multiplex condensing
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
systems. American Panel stated that the
exemption of multiplex equipment
would give that equipment an unfair
advantage over single piece equipment.
(American Panel, No. 0057.1 at p. 3)
Master-Bilt stated that the multiplex
exemption seemed to suggest that any
condensing unit connected to more than
one unit cooler would not be covered.
(Master-Bilt, No. 0069.1 at p. 3) NRDC
stated that the proposed equations for
evaluating the energy use of units with
indoor condensing units and those
connected to multiplex condensing
systems should account for differences
in the systems’ ability to reject heat.
(NRDC, No. 0064.1 at p. 7)
Addressing the comments from the
Joint Utilities and NEEA, as discussed
in section III.C.1, DOE considers
dedicated remote condensing units as
distinct from multiplex condensing
systems in that dedicated remote
condensers are part of only one walk-in,
while multiplex condensing systems are
connected to more than one walk-in or
other unit of refrigeration equipment.
DOE believes that dedicated remote
condensing units represent a substantial
opportunity for energy savings in a
regulation for walk-in components
because the configuration of a dedicated
remote condensing unit is widespread
in several market segments such as
restaurants. Manufacturers can optimize
the dedicated remote condensing unit
with the unit cooler to take advantage of
certain conditions such as low ambient
outdoor temperatures. The approach
suggested by the Joint Utilities and
NEEA would exclude dedicated remote
condensing units from this regulation,
but DOE views these units as part of the
walk-in cooler or freezer if the unit is
connected only to the walk-in and not
to any other refrigeration equipment.
Therefore, the test procedure for walkin refrigeration equipment accounts for
these units.
To address Master-Bilt’s request for
clarification, for systems where the
walk-in is connected to a central
multiplex condensing system that runs
multiple pieces of equipment, the
compressor and condenser would not be
covered because they are not
exclusively part of the walk-in. DOE
realizes there are certain condensing
units that are connected to more than
one unit cooler inside a single walk-in.
These systems would not be considered
‘‘multiplex condensing systems’’ because
they are connected to a single walk-in.
However, if the condensing unit were
connected to more than one unit cooler
inside more than one walk-in or other
piece of equipment, DOE would
consider that a multiplex condensing
system because the system’s
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
performance could not be attributed to
one walk-in alone. While DOE
understands American Panel’s concern
that multiplex condensing systems
could have an advantage because those
condensing units would not need to be
tested, the condensing unit and
compressor part of a multiplex
condensing system is not exclusively
part of a walk-in unit. Therefore, DOE
is not covering them in this test
procedure. DOE notes that unit coolers
connected to the multiplex condensing
systems would still be considered part
of the walk-in and would need to be
tested. The procedure considers the
different performance of multiplex
condensing systems and indoor
condensing systems as recommended by
NRDC. For multiplex condensing
systems, the calculation of energy use
includes a nominal efficiency that
accounts for that type of system’s ability
to reject heat. The rating conditions for
indoor condensing units provide an
opportunity for crediting energy savings
that result from an increased ability to
reject heat.
Finally, one interested party proposed
to expand the test procedure to provide
more information than DOE previously
proposed. NRDC suggested that testing
data should be input into standardized
calculations that would determine the
overall system performance for each
application and recommended that
performance data should be able to be
interpolated or extrapolated for hot
climates. (NRDC, No. 0064.1 at p. 3)
DOE notes that standardized rating
conditions are not typically applicationspecific and may not be useful for
determining the performance of the
system in conditions outside the rating
conditions. To provide this flexibility,
as suggested by NRDC, the AHRI 1250
test procedure contains provisions for
conducting testing with application
ratings to obtain the performance for a
particular application. However, DOE
emphasizes that the standardized rating
conditions are useful for comparing
systems with each other and must be
used for evaluating a product’s
compliance with a particular standard.
3. Alternative Efficiency Determination
Method
For some covered equipment, DOE
has allowed manufacturers to use their
own methods, whether a calculation or
computer simulation, to rate their
equipment after they substantiate those
calculation or simulation methods with
test data. The purpose of this provision
is to reduce the burden of testing
customized, low-volume equipment.
DOE has allowed rating methods in the
form of alternate rating methods (ARMs)
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
or alternative efficiency determination
methods (AEDMs). An ARM, which is
allowed for rating residential central air
conditioners and heat pumps, must be
a representation of the test data and
calculations of a mechanical vaporcompression refrigeration cycle.
Manufacturers may use an ARM after
submitting documentation to DOE and
receiving specific approval from DOE to
use that ARM to rate their equipment.
(10 CFR 430.24(m)(4)-(6)) An AEDM,
which is allowed for certain products
and commercial equipment—including
electric motors, distribution
transformers, and commercial heating,
ventilating, air-conditioning, and water
heating (HVAC and WH) equipment—is
a rating method derived from a
mathematical model that represents the
mechanical and electrical characteristics
of the equipment and is based on
engineering or statistical analysis,
computer simulation or modeling, or
other analytical evaluations of
performance data. An AEDM must be
substantiated by test data before it can
be used to rate equipment. (10 CFR
431.17(a)(2)–(3); 10 CFR 431.197(a)(2);
and 10 CFR 431.197(a)(2)–(3))
For the walk-in coolers and freezers
rulemaking, DOE introduced the
concept of an AEDM at the Framework
public meeting (February 4, 2009) and
requested comment on whether it could
be applied to walk-ins. At the
Framework public meeting, DOE asked
how an AEDM could be implemented
for walk-ins, what a sufficient test
sample size for validating an AEDM
would be, and how accurate (to what
percentage) an AEDM should be. DOE
did not receive any feedback regarding
these questions. Several interested
parties did, however, raise concerns in
written comments on the Framework
and during the Framework public
meeting about the potential for
inconsistency among manufacturers’
rating methods. For example, Owens
Corning stated that a single AEDM
should be accepted to keep comparisons
consistent (instead of different AEDMs
from different manufacturers), and Craig
said that requiring manufacturers to
follow the same model (that is, not
allowing manufacturers to use their own
AEDMs) would provide consistent
information to end users. (Owens
Corning, No. EERE–2008–BT–STD–
0015–0034.1 at p. 2; Craig, No. EERE–
2008–BT–STD–0015–0025.1 at p. 5)
DOE summarized and addressed these
comments in the January NOPR. 75 FR
186, 190 (Jan. 4, 2010).As a result, DOE
did not propose any specific provisions
regarding AEDMs or any other
provisions that would allow
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
manufacturers to develop their own
rating methods for walk-ins. Instead,
DOE proposed its own calculation
methodology for manufacturers to use in
rating similar units of walk-in
equipment. 75 FR 186, 191 (Jan. 4,
2010).
While the procedure divides the
envelope into its major components, the
refrigeration system is considered as a
single component. Consistent with this
approach, DOE is incorporating a single
metric to cover the performance of the
refrigeration system. DOE noted in the
September 2010 SNOPR that the
proposed refrigeration test procedure,
AHRI 1250 (I–P)-2009, ‘‘2009 Standard
for Performance Rating of Walk-In
Coolers and Freezers,’’ allows
manufacturers to test condensing units
and unit coolers separately in certain
situations, and to calculate the
performance of the combined system.
DOE anticipated that this approach
would reduce the overall testing burden
by eliminating the need to test the many
possible unit cooler and condensing
unit combinations that could comprise
a complete refrigeration system. 75 FR
55073 (Sept. 9, 2010). In proposing this
approach, DOE also recognized that
there could still be some burdens due to
system variations. To mitigate these
burdens, DOE noted that it might
consider allowing manufacturers of
refrigeration to use AEDMs to rate their
equipment. 75 FR 55089 (Sept. 9, 2010).
In comments on the September 2010
SNOPR, interested parties commented
on the burden of testing refrigeration
systems because a manufacturer’s
product line may have many different
condensing units and unit coolers,
which may be similar, but not identical,
and need to be tested individually. Craig
Industries stated that even if unit
coolers and condensing units could be
tested separately, testing each
component with all the options
available would substantially increase
the need for testing and would
discourage manufacturers from
improving their equipment. (Craig
Industries, No. 0068.1 at p. 3) AHRI
requested that DOE allow manufacturers
to rate their equipment and demonstrate
compliance with the Federal standard
through the use of an AEDM to
minimize testing burden. (AHRI, No.
0070.1 at p. 3) Manufacturers were also
concerned about how they would rate
custom units. Heatcraft stated that
refrigeration system manufacturers
would face an undue testing burden and
asserted that manufacturers would not
be able to sell a particular piece of
equipment if it had been tested.
(Heatcraft, No. 0065.1 at p. 2) DOE
acknowledges that when a refrigeration
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
21599
system is tested, it undergoes some
modifications in order to accommodate
the apparatus for taking test
measurements. As a result, these units
can no longer be sold as new equipment
after testing and are typically destroyed.
This situation, in Heatcraft’s view,
would prevent them from selling
custom equipment if the inclusion of a
custom piece requires a separate test of
the refrigeration system.
DOE recognizes the potential for
variability with respect to walk-in
components, in terms of their physical
characteristics and, consequently, their
energy performance or efficiency. To
address Craig’s concern that testing all
equipment variations would be
burdensome, and AHRI’s request that
DOE allow manufacturers to use
AEDMs, DOE will continue to consider
the application of AEDMs or ARMs.
DOE recognizes the value of permitting
the use of AEDMs and ARMs in limited
instances and may consider the
adoption of such methods for walk-in
equipment, including the statistical
basis and the sample size required to
validate them, in a future rulemaking.
D. Other Issues—Definition of Walk-In
Cooler or Freezer
EPCA defines walk-in equipment at
42 U.S.C. 6311(20), codified at 10 CFR
431.302.
During the public meeting for the
January 2010 NOPR, Hired Hand and
several interested parties stated that
DOE should clarify the definition of
walk-in coolers and walk-in freezers
with respect to temperature limits.
Multiple interested parties commented
that DOE should set an upper
temperature limit for walk-ins. After
reviewing the comments from interested
parties, DOE proposed in the September
2010 SNOPR to modify the definition of
‘‘refrigerated’’ within the definition of
walk-in cooler or freezer to mean at or
below 55 °F. 75 FR 55068, 55069 (Sept.
9, 2010).
The Joint Utilities, AHRI, American
Panel, the Joint Manufacturers, NEEA,
Craig Industries, Thermo-Kool, MasterBilt, and Bally agreed to the proposed
upper temperature limit of 55 °F for
walk-ins. (Joint Utilities, No. 0059.1 at
p. 6; AHRI, No. 0070.1 at p. 1; American
Panel, No. 0057.1 at p. 1; Joint
Manufacturers, No. 0062.1 at p. 1,
NEEA, No. 0061.1 at p. 2; Craig
Industries, No. 0068.1 at p. 1; ThermoKool, No. 0072.1 at p. 1; Master-Bilt, No.
0069.1 at p. 1; Bally, No. 0078.1 at p. 1)
The Joint Utilities also recommended
that DOE develop definitions for walkin coolers and freezers that are similar
to California Title 24, Buildings
Efficiency Standards, which contain a
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
21600
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
definition for ‘‘refrigerated warehouse’’
that clarifies a temperature of 55 degrees
or less. (Joint Utilities, No. 0059.1 at p.
6) NEEA suggested that walk-in coolers
and freezers are essentially buildings
and should be modeled as such. (NEEA,
No. 0061.1 at p. 5)
DOE notes that any regulation it
develops must be consistent with, and
fall within the parameters of, the
statutory provisions set by Congress.
Working within the confines of the
statutorily-prescribed definition of the
walk-in definition, DOE is clarifying
what the term ‘‘refrigerated’’ means in
the context of the walk-in definition to
help address the concerns raised by
commenters. In particular, DOE is
defining ‘‘refrigerated’’ for purposes of
walk-ins to mean ‘‘held at a temperature
at or below 55 degrees Fahrenheit using
a refrigeration system’’ as suggested by
commenters. Adopting this approach
should enable DOE to sufficiently
account for the range of walk-in
equipment that exist.
In comments on the January 2010
NOPR, interested parties expressed
concern about the potential for abuse in
light of the breadth of the exclusion in
the statute and requested that DOE
clarify the scope of this clause. At the
public meeting for the January 2010
NOPR, Craig Industries stated that the
definition of ‘‘medical, scientific, and
research walk-ins’’ should be better
defined, and Hired Hand agreed that the
definition is unclear. (Craig Industries,
Public Meeting Transcript, No. 0016 at
p. 19; Hired Hand, Public Meeting
Transcript, No. 0016 at p. 26) These
commenters were concerned because
the current statutory language does not
account for the fact that, in practice,
walk-ins may be used interchangeably
for either food storage or medical,
scientific, or research usage. Because a
given walk-in sold by a company could
be used in any of these types of
applications, Craig Industries and Hired
Hand were both concerned that a
company could market its walk-in as
medical equipment and avoid having to
meet any energy efficiency standards.
Craig Industries and Hired Hand
requested that DOE work to improve the
definition of exempted uses for walk-ins
because the definition could create
ambiguity and loopholes. (Craig
Industries, Public Meeting Transcript,
No. 0016 at p. 4; Hired Hand, No. 0051.1
at p. 2)
DOE is sensitive to the potential for
abuse regarding walk-ins. To ensure that
such abuse does not occur and to help
clarify the scope of the exclusion
created by Congress, DOE notes that for
any walk-in—including those
components that are covered by today’s
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
test procedure and any applicable
standards that DOE may promulgate—a
manufacturer seeking to avail itself of
the statutory exclusion would,
consistent with the statute, need to
affirmatively demonstrate to DOE that
its equipment is ‘‘designed and
marketed exclusively for medical,
scientific, or research purposes.’’ 42
U.S.C. 6311(20)(B). Further, while DOE
is currently unaware of any instances
where this exclusion is being abused,
DOE will monitor the situation and take
steps to prevent these types of activities
from occurring when it receives
sufficient information substantiating the
existence of such activities. In
examining whether a given walk-in
satisfies the statutory exclusion, DOE
may consider a number of factors,
including, but not limited to, how a
particular walk-in has been designed,
how it has been marketed, to whom the
equipment has been distributed, and
steps taken by manufacturers.
Accordingly, while DOE appreciates the
concerns raised by Craig Industries and
Hired Hand, DOE has decided that, at
this time, the exclusion set by Congress
is sufficiently clear. DOE may revisit
this issue in the future if necessary.
One commenter requested
clarification of the 3,000 square foot
provision. Bally suggested that DOE add
a corroborating cubic foot threshold,
and stated that the large variability in
panel heights could impact the energy
conservation standards. (Bally, No.
0078.1 at p. 1) Under the componentlevel test procedures established today,
a cubic foot threshold for a walk-in is
not necessary. Rather, a panel is
considered as an individual component
and its dimensions, including its height,
are accounted for in the calculation
methodology that DOE developed.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Order 12866
The Office of Management and Budget
has determined that test procedure
rulemakings do not constitute
‘‘significant regulatory actions’’ under
section 3(f) of Executive Order 12866,
Regulatory Planning and Review, 58 FR
51735 (Oct. 4, 1993). Accordingly, this
action was not subject to review under
the Executive Order by the Office of
Information and Regulatory Affairs
(OIRA) in the Office of Management and
Budget (OMB).
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
analysis (IFRA) for any rule that by law
must be proposed for public comment,
unless the agency certifies that the rule,
if promulgated, will not have a
significant economic impact on a
substantial number of small entities. As
required by Executive Order 13272,
‘‘Proper Consideration of Small Entities
in Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s Web site: https://
www.gc.doe.gov.
DOE reviewed the test procedures
considered in today’s final rule under
the provisions of the Regulatory
Flexibility Act and the procedures and
policies published on February 19,
2003.
As discussed in detail below, DOE
found that because these test procedures
have not previously been required of
manufacturers, all manufacturers,
including small manufacturers, could
experience a financial burden associated
with new testing requirements. While
examining this issue, DOE determined
that it could not certify that this rule
would not have a significant effect on a
substantial number of small entities.
Therefore, DOE prepared an Initial
Regulatory Flexibility Analysis (IRFA)
for this rulemaking. 75 FR 55068, 55087.
The Final Regulatory Flexibility
Analysis (FRFA) set forth below, which
describes potential impacts on small
businesses associated with walk-in
cooler and freezer testing requirements,
incorporates the IRFA and changes
made to the IRFA in response to the
comments from interested parties,
including the Small Business
Administration (SBA), on the September
2010 SNOPR.
1. Statement of the Need for, and
Objectives of, the Rule
A statement of the need for, and
objectives of, the rule is stated
elsewhere in the preamble and not
repeated here.
2. Summary of the Significant Issues
Raised by the Public Comments, DOE’s
Response to These Issues, and Any
Changes Made in the Proposed Rule as
a Result of Such Comments
The comments received on the IRFA
and the economic impacts of the rule
and responses thereto are provided in
the analysis below.
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
3. Description and Estimated Number of
Small Entities Regulated
DOE uses the SBA small business size
standards published on January 31,
1996, as amended, to determine whether
any small entities would be required to
comply with the rule. 61 FR 3286; see
also 65 FR 30836, 30850 (May 15, 2000),
as amended. 65 FR 53533, 53545
(September 5, 2000). The size standards
are codified at 13 CFR Part 121. The
standards are listed by North American
Industry Classification System (NAICS)
code and industry description and are
available at https://www.sba.gov/idc/
groups/public/documents/
sba_homepage/serv_sstd_tablepdf.pdf.
In the January 2010 NOPR and
September 2010 SNOPR, DOE classified
walk-in cooler and freezer equipment
manufacturing under NAICS 333415,
‘‘Air-Conditioning and Warm Air
Heating Equipment and Commercial
and Industrial Refrigeration Equipment
Manufacturing,’’ which has a size
standard of 750 employees. 75 FR 186,
204 (Jan. 4, 2010) and 75 FR 55068,
55087 (Sept. 9, 2010). After reviewing
industry sources and publicly available
data, DOE identified at least 37 small
manufacturers of walk-in cooler and
freezer envelopes and at least 5 small
manufacturers of walk-in cooler and
freezer refrigeration systems that met
this criterion. DOE also noted that the
walk-in industry can be characterized
by a few manufacturers that are
subsidiaries of much larger companies
(that would not be considered small
businesses) and a large number of small
companies as categorized by NAICS
code 333415. Furthermore, more than
half of small walk-in manufacturers
have 100 or fewer employees. 75 FR at
55088 (Sept. 9, 2010).
Interested parties commented on the
market characterization DOE presented
in the September 2010 SNOPR. SBA
agreed with DOE’s characterization of
the walk-in manufacturing industry.
(SBA, No. 0066.1 at p. 2) American
Panel stated that most walk-in
companies are small businesses and
would be at a disadvantage compared to
the large conglomerates. American
Panel characterized the majority of
small walk-in manufacturers as making
between $10 and $25 million in sales
while large manufacturers represent $75
million in walk-in sales and $250
million in overall sales. (American
Panel, No. 0057.1 at p. 3) American
Panel stated that the cost of testing
would be passed down to the product
selling price, which would trickle down
and seriously impact small business
restaurant owners. (American Panel, No.
0057.1 at p. 4) Zero Zone agreed that
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
small manufacturers would be impacted
by the regulations and stated that many
will not be able to stay in business once
they are burdened with the costs of
certification. (Zero Zone, No. 0077.1 at
p. 2)
In response to comments on the
January 2010 NOPR and September
2010 SNOPR regarding DOE’s proposed
standards for WICF, DOE is taking a
component-level approach in the WICF
test procedure rulemaking. Specifically,
DOE is establishing test procedures for
individual components of a walk-in:
Panels, doors, and refrigeration systems.
Manufacturers of these components will
be required to test the components they
manufacture for walk-ins and certify
that they meet any applicable
component performance standard. This
approach will mitigate the overall
burdens posed by this regulation and
ensure that those burdens are borne on
those manufacturers who are best suited
and positioned to conduct these types of
tests. See section III.A for further details
on this approach.
As a result of this approach, DOE reevaluated the number of small
manufacturers it identified in the
September 2010 SNOPR for this final
rule. Because DOE is considering
refrigeration systems as a single
component under the proposed
approach, DOE estimates that there are
4 small manufacturers of refrigeration
systems. Furthermore, DOE notes that
entities it previously considered walk-in
envelope manufacturers also
manufacture the panels. As a result,
DOE estimates that there are 37 small
manufacturers of panels. For doors, DOE
notes that some of the panel
manufacturers make doors and others
buy doors from suppliers. DOE
researched manufacturers who solely
manufacture the doors of WICF, and
estimates that there are four small
manufacturers of walk-in doors who do
not also manufacture panels. DOE notes
SBA’s and American Panel’s
characterization of the walk-in industry
as being composed mainly of small
manufacturers. DOE believes the new
approach of regulating WICFs at the
component level will reduce burden on
small manufacturers because the testing
and compliance burden will be reduced
due to an enhanced ability to apply the
basic model concept. See section
III.A.3.a for details. In response to
American Panel’s comment that the cost
of testing would affect small restaurant
owners, DOE notes that this analysis
considers entities who are directly
regulated by this test procedure
rulemaking (i.e., manufacturers). The
concurrent energy conservation
standards rulemaking will address
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
21601
effects on walk-in manufacturers’
customers.
4. Description and Estimate of
Compliance Requirements and
Description of Steps To Minimize the
Economic Impact on Small Entities
DOE recognizes the particular burden
of the test procedures on small
manufacturers. DOE does not expect
that small manufacturers would have
fewer basic models or component types
than large manufacturers. Therefore, a
small manufacturer could have the same
total cost of testing as a large
manufacturer, but this cost would be a
higher percentage of a small
manufacturer’s annual revenues. Thus,
the differential impact associated with
walk-in cooler and walk-in freezer test
procedures on small businesses may be
significant even if the overall testing
burden is reduced as described
elsewhere in the preamble.
Due to the nature of walk-in coolers
and freezers within the appliance
standards program, DOE is considering
use of a component-based approach to
walk-in standards, setting individual
performance standards for each
component. This approach would
require the component manufacturers to
test the components they manufacture
for walk-in applications, comply with
the applicable performance standard for
those components, and certify to DOE
that those components meet the
standard. See section III.A for details on
this approach. At this time there are no
performance standards in place for
walk-in equipment, as those standards
are being developed in a concurrent
rulemaking. Details on the performance
standards rulemaking can be found on
the DOE Web site at https://
www1.eere.energy.gov/buildings/
appliance_standards/commercial/
wicf.html. However, manufacturers will
be required to use these test procedures
to certify performance once any final
standards are issued and must use the
test procedures outlined in this final
rule if they make representations as to
the performance of their components.
To further address concerns about
costs, DOE is anticipating developing a
sampling plan in a future rulemaking to
determine how many units of each
walk-in component must be tested. In
such a rulemaking, DOE will consider
the impacts to small businesses.
a. Panel and Door Manufacturer Testing
Impacts
In the September 2010 SNOPR, DOE
proposed to require envelope
manufacturers to test their equipment in
accordance with several industry test
standards: ASTM C1363–05, ‘‘Standard
E:\FR\FM\15APR3.SGM
15APR3
srobinson on DSKHWCL6B1PROD with RULES3
21602
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
Test Method for Thermal Performance
of Building Materials and Envelope
Assemblies by Means of a Hot Box
Apparatus;’’ DIN EN 13164:2009–02,
‘‘Thermal insulation products for
buildings—Factory made products of
extruded polystyrene foam (XPS)—
Specification;’’ DIN EN 13165:2009–02,
‘‘Thermal insulation products for
buildings—Factory made rigid
polyurethane foam (PUR) products—
Specification;’’ and NFRC 100–
2010[E0A1], ‘‘Procedure for Determining
Fenestration Product U-factors.’’
DOE spoke with industry experts to
determine the approximate cost of each
test. Under the new component level
approach to testing, entire walk-ins are
not required to be tested or certified.
Rather, component manufacturers are
required to test and certify their own
components. Therefore, DOE evaluated
the cost of each test to the component
manufacturer. For foam used in panels,
a test using DIN EN 13164:2009–02 or
DIN EN 13165:2009–02 costs
approximately $5,000 for each type of
foam, though DOE has found that most
manufacturers use only one type. The
test result would be used to calculate
the LTTR for all the manufacturer’s
panels that use that type of foam. For
the panels themselves, a test using
ASTM C1363–05 costs approximately
$5,000. Manufacturers would need to
test the core and edge U-factor of a pair
of 4 ft. by 8 ft. panels, for each foam
type, frame type, and panel thickness
they manufacture. DOE estimated that
manufacturers use either one or two
types of foam and may have up to nine
different combinations of frame type
and panel thickness. Using this
estimate, the total cost of testing
compliance with a panel standard could
be up to an average of $5,000–$10,000
for the foam panels and $45,000 to test
the U-factors of the different panel
configurations. However, for
manufacturers who have fewer unique
combinations of frame type and panel
thickness, the testing cost would be
substantially less. DOE has incorporated
other burden reducing measures to
reduce cost. Specifically, it incorporated
a method that allows manufacturers to
test a reference panel that is 4 ft. by 8
ft. and then calculate the U-factor of
other panels of different dimensions
from those test results as long as certain
aspects of the panels are the same. See
section III.B.2 for details.
For doors, a test of door U-factor using
NFRC 100 costs approximately $5,000.
DOE estimates that a typical door
manufacturer would have to certify up
to 20 to 40 basic models of doors, which
would cost $100,000 to $200,000 if each
door were to be physically tested.
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
However, NFRC 100 also permits
computer modeling of a door’s U-factor,
which could further reduce the testing
cost. See section III.B.3 for discussion of
the NFRC testing requirements for
doors.
The estimated costs only include the
cost of one test on each basic model,
and do not include additional testing on
the same basic model that may be
required as part of a sampling plan. As
mentioned above, DOE anticipates
developing sampling plans in a future
rulemaking to determine how many
tests need to be performed on the same
type of envelope component, to ensure
the test results are repeatable and
statistically valid.
b. Refrigeration System Manufacturer
Testing Impacts
The test procedure for refrigeration
systems will require manufacturers to
perform testing in accordance with a
single industry test standard: AHRI 1250
(I–P)–2009, ‘‘2009 Standard for
Performance Rating of Walk-In Coolers
and Freezers.’’ DOE researched the cost
of performing this test and, based on
discussions with experts, estimates that
a test using AHRI 1250 (I–P)–2009
would likely cost approximately $8,500.
DOE estimates that the total testing cost
for a typical refrigeration manufacturer
could be approximately $425,000, based
on an estimate of 50 basic models, but
that it could be higher for manufacturers
of more customized equipment. For
instance, a manufacturer with 200 basic
models would incur a testing cost of
approximately $1.7 million.
To address concerns of manufacturer
impact, DOE is including burdenreducing measures for refrigeration
system manufacturers. The test
procedure referenced in this final rule,
AHRI 1250–2009, allows for rating the
condensing unit and the unit cooler
separately and then calculating their
combined efficiency. This reduces
testing burden by not requiring testing
of every combination. Allowing such a
calculation to be used will significantly
decrease the number of tests. See
section III.C.2 for details. DOE also
notes that the CCE final rule, published
March 7, 2011, allows that in general,
manufacturers may elect to group
individual models of equipment into
basic models at their discretion to the
extent the models have essentially
identical electrical, physical, and
functional characteristics that affect
energy efficiency or energy
consumption. Furthermore,
manufacturers may rate models
conservatively, meaning the tested
performance of the model(s) must be at
least as good as the certified rating, after
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
applying the appropriate sampling plan.
76 FR 12429. DOE believes these
provisions will reduce the burden of
testing for refrigeration manufacturers
because they will reduce the number of
basic models a manufacturer must test.
DOE may also consider allowing
manufacturers to use validated
alternative methods to rate their
equipment. See section III.C.3 for
further discussion of these methods.
DOE also considered a number of
alternatives to these test procedures,
including test procedures that
incorporate industry test standards
other than the referenced standards, DIN
EN 13164:2009–02, DIN EN
13165:2009–02, ASTM C1363–05, and
AHRI 1250–2009, all previously
described in section III. (DOE also notes
that NFRC 100, the test method adopted
for determining the U-factor of doors,
was the least burdensome test DOE
identified.) Instead of requiring DIN EN
13164:2009–02 or DIN EN 13165:2009–
02 for testing the long-term thermal
properties of insulation, DOE could
require only ASTM C518–04, ‘‘Standard
Test Method for Steady-State Thermal
Transmission Properties by Means of
the Heat Flow Meter Apparatus,’’ which
tests the thermal properties of insulation
at a certain point in time (that is, the
point of manufacture). This test could
also be used in place of ASTM 1363–05.
A test conducted as per ASTM C518–04
would cost approximately $500 to
$1,000, as compared to $5,000 for a test
conducted as per DIN EN 13164:2009–
02 or DIN EN 13165:2009–02 and $5,000
for a test conducted as per ASTM
C1363–05. DOE is including ASTM
C1363–05 as part of the test procedure
because heat conduction through
structural members is a significant panel
characteristic that is not addressed
under ASTM C518–04. See section
III.B.2.a for details. DOE is including
DIN EN 13164:2009–02 and DIN EN
13165:2009–02 as part of the test
procedure because these methods
account for the effect of aging on foam’s
insulation performance, a phenomenon
that is not captured under ASTM C518–
04. See section III.B.2.b for details.
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of walk-in cooler and
walk-in freezer components must certify
to DOE that their equipment complies
with any applicable energy conservation
standard. In certifying compliance,
manufacturers must test their
equipment according to the DOE test
procedure for walk-in cooler and walkin freezer components, including any
amendments adopted for that test
procedure. DOE has adopted regulations
E:\FR\FM\15APR3.SGM
15APR3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
srobinson on DSKHWCL6B1PROD with RULES3
for the certification and recordkeeping
requirements for all covered consumer
products and commercial equipment,
including walk-in cooler and walk-in
freezer components. 76 FR 12442
(March 7, 2011). The collection-ofinformation requirement for the
certification and recordkeeping has been
approved by OMB under control
number 1910–1400. The public
reporting burden for the certification is
estimated to average 20 hours per
response, including the time for
reviewing instructions, searching
existing data sources, gathering and
maintaining the data needed, and
completing and reviewing the collection
of information.
Public comment is sought regarding:
Whether this proposed collection of
information is necessary for the proper
performance of the functions of the
agency, including whether the
information shall have practical utility;
the accuracy of the burden estimate;
ways to enhance the quality, utility, and
clarity of the information to be
collected; and ways to minimize the
burden of the collection of information,
including through the use of automated
collection techniques or other forms of
information technology. Send comments
on these or any other aspects of the
collection of information to Charles
Llenza (see ADDRESSES) and by e-mail to
Christine_J._Kymn@omb.eop.gov.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE establishes a
new test procedure for walk-in coolers
and walk-in freezers. DOE has
determined that this rule falls into a
class of actions that are categorically
excluded from review under the
National Environmental Policy Act of
1969 (42 U.S.C. 4321 et seq.) and DOE’s
implementing regulations at 10 CFR part
1021. Specifically, this rule establishes
a test procedure without affecting the
amount, quality or distribution of
energy usage, and, therefore, will not
result in any environmental impacts.
Thus, this rulemaking is covered by
Categorical Exclusion A5 under 10 CFR
part 1021, subpart D, which applies to
any rulemaking that does not result in
any environmental impacts.
Accordingly, neither an environmental
assessment nor an environmental
impact statement is required.
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999) imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have Federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have Federalism implications. On
March 14, 2000, DOE published a
statement of policy describing the
intergovernmental consultation process
it will follow in the development of
such regulations. 65 FR 13735. DOE
examined this final rule and determined
that it will not have a substantial direct
effect on the States, on the relationship
between the national government and
the States, or on the distribution of
power and responsibilities among the
various levels of government. EPCA
governs and prescribes Federal
preemption of State regulations as to
energy conservation for the products
that are the subject of today’s final rule.
States can petition DOE for exemption
from such preemption to the extent, and
based on criteria, set forth in EPCA. (42
U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
21603
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, this final rule
meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
regulatory action resulting in a rule that
may cause the expenditure by State,
local, and Tribal governments, in the
aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR
12820; also available at https://
www.gc.doe.gov. DOE examined today’s
final rule according to UMRA and its
statement of policy and determined that
the rule contains neither an
intergovernmental mandate, nor a
mandate that may result in the
expenditure of $100 million or more in
any year, so these requirements do not
apply.
H. Review Under theTreasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
E:\FR\FM\15APR3.SGM
15APR3
21604
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
that may affect family well-being.
Today’s final rule will not have any
impact on the autonomy or integrity of
the family as an institution.
Accordingly, DOE has concluded that it
is not necessary to prepare a Family
Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights’’ 53 FR 8859
(March 18, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
srobinson on DSKHWCL6B1PROD with RULES3
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). DOE has reviewed
today’s final rule under the OMB and
DOE guidelines and has concluded that
it is consistent with applicable policies
in those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB, a
Statement of Energy Effects for any
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgated or is
expected to lead to promulgation of a
final rule, and that: (1) Is a significant
regulatory action under Executive Order
12866, or any successor order; and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy; or (3) is designated by the
Administrator of OIRA as a significant
energy action. For any significant energy
action, the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use if the
regulation is implemented, and of
reasonable alternatives to the action and
their expected benefits on energy
supply, distribution, and use.
Today’s regulatory action is not a
significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; FEAA) Section 32 essentially
provides in relevant part that, where a
proposed rule authorizes or requires use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (FTC)
concerning the impact of the
commercial or industry standards on
competition.
The procedures addressed by this
action incorporate the following
commercial standards: ASTM C1363–
05, AHRI 1250 (I–P)–2009, DIN EN
13164:2009–02, DIN EN 13165:2009–02,
and NFRC 100–2010[E0A1]. DOE has
evaluated these standards and is unable
to conclude whether they fully comply
with the requirements of section 32(b) of
the FEAA (i.e. whether they were
developed in a manner that fully
provides for public participation,
comment, and review.) DOE has
consulted with both the Attorney
General and the Chairman of the FTC
about the impact on competition of
using the methods contained in these
standards and has received no
comments objecting to their use.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of today’s rule before its effective date.
The report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
N. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
List of Subjects in 10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Incorporation by reference, Reporting
and recordkeeping requirements.
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
Issued in Washington, DC, on March 30,
2011.
Kathleen Hogan,
Deputy Assistant Secretary for Energy
Efficiency, Office of Technology
Development, Energy Efficiency and
Renewable Energy.
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 431
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317.
2. Section 431.302 is amended by
adding, in alphabetical order, new
definitions for ‘‘Display door,’’ ‘‘Display
panel,’’ ‘‘Door’’, ‘‘Envelope,’’ ‘‘K-factor,’’
‘‘Panel,’’ ‘‘Refrigerated,’’ ‘‘Refrigeration
system,’’ and ‘‘U-factor’’ to read as
follows:
■
§ 431.302 Definitions concerning walk-in
coolers and walk-in freezers.
*
*
*
*
*
Display door means a door designed
for product movement, display, or both,
rather than the passage of persons.
Display panel means a panel that is
entirely or partially comprised of glass,
a transparent material, or both and is
used for display purposes.
Door means an assembly installed in
an opening on an interior or exterior
wall that is used to allow access or close
off the opening and that is movable in
a sliding, pivoting, hinged, or revolving
manner of movement. For walk-in
coolers and walk-in freezers, a door
includes the door panel, glass, framing
materials, door plug, mullion, and any
other elements that form the door or
part of its connection to the wall.
Envelope means—
(1) The portion of a walk-in cooler or
walk-in freezer that isolates the interior,
refrigerated environment from the
ambient, external environment; and
(2) All energy-consuming components
of the walk-in cooler or walk-in freezer
that are not part of its refrigeration
system.
K-factor means the thermal
conductivity of a material.
*
*
*
*
*
Panel means a construction
component that is not a door and is
used to construct the envelope of the
walk-in, i.e., elements that separate the
interior refrigerated environment of the
walk-in from the exterior.
Refrigerated means held at a
temperature at or below 55 degrees
Fahrenheit using a refrigeration system.
Refrigeration system means the
mechanism (including all controls and
other components integral to the
E:\FR\FM\15APR3.SGM
15APR3
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
*
*
*
*
*
(b) AHRI. Air-Conditioning, Heating,
and Refrigeration Institute, 2111 Wilson
Boulevard, Suite 500, Arlington, VA
22201, (703) 600–0366, or https://
www.ahrinet.org.
(1) AHRI 1250 (I–P)-2009, (‘‘AHRI
1250’’), 2009 Standard for Performance
Rating of Walk-In Coolers and Freezers,
approved 2009, IBR approved for
§ 431.304.
srobinson on DSKHWCL6B1PROD with RULES3
where tj and n represent the outdoor
temperature at each bin j and the number
of hours in each bin j, respectively, for
˚
˚
where BLH and BLL for refrigerator and
freezer systems are defined in sections
6.2.1 and 6.2.2, respectively, of AHRI
1250 and the annual walk-in energy
factor is calculated from the results of
VerDate Mar<15>2010
19:41 Apr 14, 2011
Jkt 223001
the temperature bins listed in Table D1
of AHRI 1250.
(ii) For systems consisting of a
packaged dedicated system or a split
the test procedures set forth in AHRI
1250.
(iii) For systems consisting of a single
unit cooler or a set of multiple unit
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
and (b)(4), respectively, and by adding
new paragraphs (b)(5), (b)(6), (b)(7), and
(b)(8) to read as follows.
§ 431.304 Uniform test method for the
measurement of energy consumption of
walk-in coolers and walk-in freezers.
*
*
*
*
*
(b) * * *
(5) Determine the U-factor,
conduction load, and energy use of
walk-in cooler and walk-in freezer
display panels, floor panels, and nonfloor panels by conducting the test
procedure set forth in Appendix A to
this subpart, sections 4.1, 4.2, and 4.3,
respectively.
(6) Determine the energy use of walkin cooler and walk-in freezer display
doors and non-display doors by
conducting the test procedure set forth
in Appendix A to this subpart, sections
4.4 and 4.5, respectively.
(7) Determine the Annual Walk-in
Energy Factor of walk-in cooler and
walk-in freezer refrigeration systems by
conducting the test procedure set forth
in AHRI 1250 (incorporated by
reference; see § 431.303).
(8) Determine the annual energy
consumption of walk-in cooler and
walk-in freezer refrigeration systems:
(i) For systems consisting of a
packaged dedicated system or a split
dedicated system, where the condensing
unit is located outdoors, by conducting
the test procedure set forth in AHRI
1250 and recording the annual energy
consumption term in the equation for
annual walk-in energy factor in section
7 of AHRI 1250:
dedicated system where the condensing
unit is located in a conditioned space,
by performing the following calculation:
coolers serving a single piece of
equipment and connected to a multiplex
condensing system, by performing the
following calculation:
E:\FR\FM\15APR3.SGM
15APR3
ER15AP11.025
§ 431.303 Materials incorporated by
reference.
(2) [Reserved]
(c) * * *
(2) ASTM C1363–05, (‘‘ASTM
C1363’’), Standard Test Method for
Thermal Performance of Building
Materials and Envelope Assemblies by
Means of a Hot Box Apparatus,
approved May 1, 2005, IBR approved for
Appendix A to Subpart R of part 431.
(d) CEN. European Committee for
Standardization (French: Norme or
German: Norm), Avenue Marnix 17, B–
1000 Brussels, Belgium, Tel: + 32 2 550
08 11, Fax: + 32 2 550 08 19 or
https://www.cen.eu/.
(1) DIN EN 13164:2009–02, (‘‘DIN EN
13164’’), Thermal insulation products
for buildings—Factory made products of
extruded polystyrene foam (XPS)—
Specification, approved February 2009,
IBR approved for Appendix A to
Subpart R of part 431.
(2) DIN EN 13165:2009–02, (‘‘DIN EN
13165’’), Thermal insulation products
for buildings—Factory made rigid
polyurethane foam (PUR) products—
Specification, approved February 2009,
IBR approved for Appendix A to
Subpart R of part 431.
(e) NFRC. National Fenestration
Rating Council, 6305 Ivy Lane, Ste. 140,
Greenbelt, MD 20770, (301) 589–1776,
or https://www.nfrc.org/.
(1) NFRC 100–2010[E0A1], (‘‘NFRC
100’’), Procedure for Determining
Fenestration Product U-factors,
approved June 2010, IBR approved for
Appendix A to Subpart R of part 431.
(2) [Reserved]
■ 4. Section 431.304 is amended by
redesignating paragraphs (b)(2), (b)(3),
(b)(4), and (b)(5) as (b)(1), (b)(2), (b)(3),
ER15AP11.024
system’s operation) used to create the
refrigerated environment in the interior
of a walk-in cooler or freezer, consisting
of:
(1) A packaged dedicated system
where the unit cooler and condensing
unit are integrated into a single piece of
equipment; or
(2) A split dedicated system with
separate unit cooler and condensing
unit sections; or
(3) A unit cooler that is connected to
a multiplex condensing system.
U-factor means the heat transmission
in a unit time through a unit area of a
specimen or product and its boundary
air films, induced by a unit temperature
difference between the environments on
each side.
*
*
*
*
*
■ 3. Section 431.303 is amended by:
■ a. Redesignating paragraph (b) as
paragraph (c);
■ b. Adding at the end of the sentence
in redesignated paragraph (c)(1), ‘‘and
Appendix A to Subpart R of Part 431’’.
■ c. Adding new paragraphs (b), (c)(2),
(d), and (e) to read as follows.
21605
21606
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
˚
˚
where BLHand BLL for refrigerator and
freezer systems are defined in section
7.9.2.2 and 7.9.2.3, respectively, of AHRI
1250 and the annual walk-in energy
factor is calculated from the results of
the test procedures set forth in AHRI
1250.
freezer rating conditions and the external
conditions are the cooler rating conditions.
3.6 Percent time off (PTO) means the
percent of time that an electrical device is
assumed to be off.
3.0 Additional Definitions
3.1 Automatic door opener/closer means
a device or control system that
‘‘automatically’’ opens and closes doors
without direct user contact, such as a motion
sensor that senses when a forklift is
approaching the entrance to a door and opens
it, and then closes the door after the forklift
has passed.
3.2 Core region means the part of the
panel that is not the edge region.
3.3 Edge region means a region of the
panel that is wide enough to encompass any
framing members and edge effects. If the
panel contains framing members (e.g. a wood
frame) then the width of the edge region must
be as wide as any framing member plus 2 in.
± 0.25 in. If the panel does not contain
framing members then the width of the edge
region must be 4 in. ± 0.25 in. For walk-in
panels that utilize vacuum insulated panels
(VIP) for insulation, the width of the edge
region must be the lesser of 4.5 in. ± 1 in.
or the maximum width that does not cause
the VIP to be pierced by the cutting device
when the edge region is cut.
3.4 Surface area means the area of the
surface of the walk-in component that would
be external to the walk-in. For example, for
panel, the surface area would be the area of
the side of the panel that faces the outside
of the walk-in. It would not include edges of
the panel that are not exposed to the outside
of the walk-in.
3.5 Rating conditions means, unless
explicitly stated otherwise, all conditions
shown in Table A.1. For installations where
two or more walk-in envelope components
share any surface(s), the ‘‘external
conditions’’ of the shared surface(s) must
reflect the internal conditions of the adjacent
walk-in. For example, if a walk-in component
divides a walk-in freezer from a walk-in
cooler, then the internal conditions are the
Where:
TDB,ext,dp = dry-bulb air external temperature,
°F, as prescribed in Table A.1; and
TDB,int, dp = dry-bulb air temperature internal
to the cooler or freezer, °F, as prescribed
in Table A.1.
(d) Calculate the conduction load through
the display panel, Qcond-dp, Btu/h, as follows:
Where:
Udp = thermal transmittance, U-factor, of the
display panel in accordance with section
5.3 of this appendix, Btu/h-ft2¥°F.
(e) Select Energy Efficiency Ratio (EER), as
follows:
(1) For coolers, use EER = 12.4 Btu/W-h
(2) For freezers, use EER = 6.3 Btu/W-h
(f) Calculate the total daily energy
consumption, Edp, kWh/day, as follows:
4.2
(b) Calculate the surface area, as defined in
section 3.4 of this appendix, of the floor
panel core, as defined in section 3.2, Afp core,
ft2, with standard geometric formulas or
srobinson on DSKHWCL6B1PROD with RULES3
Adp= surface area of the walk-in display
panel, ft2;
DTdp= temperature differential between
refrigerated and adjacent zones, °F; and
Where:
Qcond, dp = the conduction load through the
display panel, Btu/h; and
EER = EER of walk-in (cooler or freezer), Btu/
W-h.
VerDate Mar<15>2010
19:45 Apr 14, 2011
Jkt 223001
Floor Panels
(a) Calculate the surface area, as defined in
section 3.4 of this appendix, of the floor
panel edge, as defined in section 3.3, Afp edge,
ft2, with standard geometric formulas or
engineering software as directed in section
5.1 of this appendix.
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
4.0
35 °F
¥10 °F
75 °F
55 °F
Calculation Instructions
4.1 Display Panels
(a) Calculate the U-factor of the display
panel in accordance with section 5.3 of this
appendix, Btu/h-ft2¥°F.
(b) Calculate the display panel surface area,
as defined in section 3.4 of this appendix,
Adp, ft2, with standard geometric formulas or
engineering software.
(c) Calculate the temperature differential,
DTdp, °F, for the display panel, as follows:
ER15AP11.029
2.0 Definitions
The definitions contained in § 431.302 are
applicable to this appendix.
Internal Temperatures (cooled
space within the envelope):
Cooler Dry Bulb Temperature ..
Freezer Dry Bulb Temperature
External Temperatures (space external to the envelope):
Freezer and Cooler Dry Bulb
Temperatures.
Subfloor Temperatures:
Freezer and Cooler Dry Bulb
Temperatures.
E:\FR\FM\15APR3.SGM
15APR3
ER15AP11.028
1.0 Scope
This appendix covers the test requirements
used to measure the energy consumption of
the components that make up the envelope
of a walk-in cooler or walk-in freezer.
Value
ER15AP11.027
Appendix A to Subpart R of Part 431—
Uniform Test Method for the
Measurement of Energy Consumption of
the Components of Envelopes of WalkIn Coolers and Walk-In Freezers
TABLE A.1—TEMPERATURE
CONDITIONS
ER15AP11.026
5.Appendix A to subpart R of part 431
is added to read as follows:
■
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
transmittance of foam, ULT,fp core, Btu/hft2¥°F, as follows:
Where:
Text, fp = subfloor temperature, °F, as
prescribed in Table A.1; and
TDB,int, fp = dry-bulb air internal temperature,
°F, as prescribed in Table A.1. If the
panel spans both cooler and freezer
temperatures, the freezer temperature
must be used.
(e) Calculate the floor foam degradation
factor, DFfp, unitless, as follows:
Where:
RLTTR,fp = the long term thermal resistance
R-value of the floor panel foam in
accordance with section 5.2 of this
appendix, h-ft2-°F/Btu; and
Ro,fp = the R-value of foam determined in
accordance with ASTM C518
(incorporated by reference; see section
§ 431.303) for purposes of compliance
with the appropriate energy conservation
standard, h-ft2-°F/Btu.
(f) Calculate the U-factor for panel core
region modified by the long term thermal
Where:
Afp edge = area of floor panel edge, ft2;
Ufp edge = U-factor for panel edge area in
accordance with section 5.1 of this
appendix, Btu/h-ft2-°F;
Afp core = area of floor panel core, ft2;
ULT,fp core = U-factor for panel core region
modified by the long term thermal
transmittance of foam, Btu/h-ft2-°F; and
Afp = total area of the floor panel, ft2.
(h) Calculate the conduction load through
floor panels, Qcond-fp, Btu/h,
Where:
DTfp = temperature differential across the
floor panels, °F;
Afp = total area of the floor panel, ft2; and
Ufp = overall U-factor of the floor panel, Btu/
h-ft2-°F.
(i) Select Energy Efficiency Ratio (EER), as
follows:
(1) For coolers, use EER = 12.4 Btu/W-h
(2) For freezers, use EER = 6.3 Btu/W-h
(j) Calculate the total daily energy
consumption, Efp, kWh/day, as follows:
Where:
Qcond-fp = the conduction load through the
floor panel, Btu/h; and
EER = EER of walk-in (cooler or freezer), Btu/
W-h.
defined in section 3.3, Anf edge, ft2, with
standard geometric formulas or engineering
software as directed in section 5.1 of this
appendix.
(b) Calculate the surface area, as defined in
section 3.4, of the non-floor panel core, as
defined in section 3.2, Anf core, ft2, with
standard geometric formulas or engineering
software as directed in section 5.1 of this
appendix.
(c) Calculate total non-floor panel area, Anf,
ft2:
srobinson on DSKHWCL6B1PROD with RULES3
(a) Calculate the surface area, as defined in
section 3.4, of the non-floor panel edge, as
Where:
TDB,ext, nf = dry-bulb air external temperature,
°F, as prescribed in Table A.1; and
TDB,int, nf = dry-bulb air internal temperature,
°F, as prescribed in Table A.1. If the nonfloor panel spans both cooler and freezer
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
temperatures, then the freezer
temperature must be used.
(e) Calculate the non-floor foam
degradation factor, DFnf, unitless, as follows:
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
ER15AP11.039
ER15AP11.038
ER15AP11.037
ER15AP11.036
ER15AP11.035
ER15AP11.034
ER15AP11.033
Non-Floor Panels
Where:
Anf edge = non-floor paneledge area,ft2; and
Anf core = non-floor panel core area, ft2.
(d) Calculate temperature differential, DTnf,
°F:
ER15AP11.032
4.3
Where:
Ufp core = the U-factor in accordance with
section 5.1 of this appendix, Btu/h-ft2-°F;
and
DFfp = floor foam degradation factor, unitless.
(g) Calculate the overall U-factor of the
floor panel, Ufp, Btu/h-ft2-°F, as follows:
Where:
RLTTR,nf = the R-value of the non-floor panel
foam in accordance with section 5.2 of
this appendix, h-ft2-°F/Btu; and
E:\FR\FM\15APR3.SGM
15APR3
ER15AP11.031
Where:
Afp core = floor panel core area, ft2; and
Afp edge = floor panel edge area, ft2.
(d) Calculate the temperature differential of
the floor panel, DTfp, °F, as follows:
ER15AP11.030
engineering software as directed in section
5.1 of this appendix.
(c) Calculate the total area of the floor
panel, Afp, ft2, as follows:
21607
21608
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
Ro,nf = the R-value of foam determined in
accordance with ASTM C518
(incorporated by reference; see section
§ 431.303) for purposes of compliance
with the appropriate energy conservation
standard, h-ft2-°F/Btu.
(f) Calculate the U-factor, ULT,nf core, Btu/hft2-°F, as follows:
Where:
Anf edge = area of non-floor panel edge, ft2;
Unf edge = U-factor for non-floor panel edge
area in accordance with section 5.1 of
this appendix, Btu/h-ft2-°F;
Anf core = area of non-floor panel core, ft2;
ULT,nf core = U-factor for non-floor panel core
region modified by the long term thermal
transmittance of foam, Btu/h-ft2-°F; and
Anf = total area of the non- floor panel, ft2.
(h) Calculate the conduction load through
non-floor panels, Qcond-nf, Btu/h,
Where:
DTnf = temperature differential across the
non-floor panels, °F;
Anf = total area of the non-floor panel, ft2; and
Unf = overall U-factor of the non-floor panel,
Btu/h-ft2-°F.
(i) Select Energy Efficiency Ratio (EER), as
follows:
(1) For coolers, use EER = 12.4 Btu/W-h
(2) For freezers, use EER = 6.3 Btu/W-h
(j) Calculate the total daily energy
consumption, Enf, kWh/day, as follows:
Where:
Qcond-nf = the conduction load through the
non-floor panel, Btu/h; and
EER = EER of walk-in (cooler or freezer), Btu/
W-h.
4.4
(b) Calculate the surface area, as defined in
section 3.4 of this appendix, of the display
door, Add, ft2, with standard geometric
formulas or engineering software.
(c) Calculate the temperature differential,
DTdd, °F, for the display door as follows:
Where:
TDB,ext, dd = dry-bulb air temperature external
to the display door, °F, as prescribed in
Table A.1; and
TDB,int, dd = dry-bulb air temperature internal
to the display door, °F, as prescribed in
Table A.1.
(d) Calculate the conduction load through
the display doors, Qcond-dd, Btu/h, as follows:
Where:
DTdd = temperature differential between
refrigerated and adjacent zones, °F;
Add = surface area walk-in display doors, ft2;
and
Udd = thermal transmittance, U-factor of the
door, in accordance with section 5.3 of
this appendix, Btu/h-ft2-°F.
door lighting systems); control system units;
and sensors.
(a) Select the required value for percent
time off (PTO) for each type of electricity
consuming device, PTOt (%)
(1) For lights without timers, control
system or other demand-based control, PTO
= 25 percent. For lighting with timers,
control system or other demand-based
control, PTO = 50 percent.
(2) For anti-sweat heaters on coolers (if
included): Without timers, control system or
other demand-based control, PTO = 0
percent. With timers, control system or other
demand-based control, PTO = 75 percent. For
anti-sweat heaters on freezers (if included):
Without timers, control system or other autoshut-off systems, PTO = 0 percent. With
timers, control system or other demand-based
control, PTO = 50 percent.
(3) For all other electricity consuming
devices: Without timers, control system, or
other auto-shut-off systems, PTO = 0 percent.
If it can be demonstrated that the device is
controlled by a preinstalled timer, control
system or other auto-shut-off system, PTO =
25 percent.
(b) Calculate the power usage for each type
of electricity consuming device, Pdd-comp,u,t,
kWh/day, as follows:
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
E:\FR\FM\15APR3.SGM
15APR3
ER15AP11.045
ER15AP11.044
ER15AP11.043
Conduction Through Display Doors
(a) Calculate the U-factor of the door in
accordance with section 5.3 of this appendix,
Btu/h-ft2-°F
ER15AP11.042
4.4.1
ER15AP11.041
Electrical components associated with
display doors could include, but are not
limited to: Heater wire (for anti-sweat or antifreeze application); lights (including display
Display Doors
ER15AP11.040
srobinson on DSKHWCL6B1PROD with RULES3
4.4.2 Direct Energy Consumption of
Electrical Component(s) of Display Doors
Where:
Unf core = the U-factor, in accordance with
section 5.1 of this appendix, of non-floor
panel, Btu/h- ft2-°F; and
DFnf = the non-floor foam degradation factor,
unitless.
(g) Calculate the overall U-factor of the
non-floor panel, Unf, Btu/h-ft2-°F, as follows:
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
21609
Where:
t = index for each type of electricity
consuming device with identical rated
power;
Pdd-comp,int, t = the energy usage for an
electricity consuming device sited on the
interior facing side of or in the display
door, of type t, kWh/day; and
Pdd-comp,ext, t = the energy usage for an
electricity consuming device sited on the
external facing side of the display door,
of type t, kWh/day.
(d) Calculate the total electrical energy
consumption, Pdd-tot, (kWh/day), as follows:
Where:
Pdd-tot,int = the total interior electrical energy
usage for the display door, kWh/day; and
Pdd-tot,ext = the total exterior electrical energy
usage for the display door, kWh/day.
4.4.3 Total Indirect Electricity Consumption
Due to Electrical Devices
(a) Select Energy Efficiency Ratio (EER), as
follows:
(1) For coolers, use EER = 12.4 Btu/Wh
(2) For freezers, use EER = 6.3 Btu/Wh
(b) Calculate the additional refrigeration
energy consumption due to thermal output
from electrical components sited inside the
display door, Cdd-load, kWh/day, as follows:
Where:
EER = EER of walk-in cooler or walk-in
freezer, Btu/W-h; and
Pdd-tot,int = The total internal electrical energy
consumption due for the display door,
kWh/day.
4.4.4 Total Display Door Energy
Consumption
(2) For freezers, use EER = 6.3 Btu/W-h
(b) Calculate the total daily energy
consumption due to conduction thermal
load, Edd, thermal, kWh/day, as follows:
Where:
Qcond, dd = the conduction load through the
display door, Btu/h; and
EER = EER of walk-in (cooler or freezer), Btu/
W-h.
ER15AP11.048
ER15AP11.047
(c) Calculate the total energy, Edd,tot, kWh/
day,
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
E:\FR\FM\15APR3.SGM
15APR3
ER15AP11.046
srobinson on DSKHWCL6B1PROD with RULES3
ER15AP11.049
(a) Select Energy Efficiency Ratio (EER), as
follows:
(1) For coolers, use EER = 12.4 Btu/W-h
ER15AP11.052
Prated,u,t = rated power of each component, of
type t, kW;
PTOu,t = percent time off, for device of type
t, %; and
nu,t = number of devices at the rated power
of type t, unitless.
(c) Calculate the total electrical energy
consumption for interior and exterior power,
Pdd-tot, int (kWh/day) and Pdd-tot, ext (kWh/day),
respectively, as follows:
ER15AP11.051
index is represented by u = ext. If the
electrical component is both on the
interior and exterior side of the display
door then u = int. For anti-sweat heaters
sited anywhere in the display door, 75
percent of the total power is be attributed
to u = int and 25 percent of the total
power is attributed to u = ext;
t = index for each type of electricity
consuming device with identical rated
power;
ER15AP11.050
Where:
u = the index for each of type of electricityconsuming device located on either
(1) the interior facing side of the display
door or within the inside portion of the
display door, (2) the exterior facing side
of the display door, or (3) any
combination of (1) and (2). For purposes
of this calculation, the interior index is
represented by u = int and the exterior
21610
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
components contained within the
display door, kWh/day.
display door, And, ft2, with standard
geometric formulas or with engineering
software.
(b) Calculate the temperature differential of
the non-display door, DTnd,°F, as follows:
Where:
TDB,ext, nd = dry-bulb air external temperature,
°F, as prescribed by Table A.1; and
TDB,int, nd = dry-bulb air internal temperature,
°F, as prescribed by Table A.1. If the
component spans both cooler and freezer
spaces, the freezer temperature must be
used.
(c) Calculate the conduction load through
the non-display door: Qcond-nd, Btu/h,
Where:
DTnd = temperature differential across the
non-display door, °F;
Und = thermal transmittance, U-factor of the
door, in accordance with section 5.3 of
this appendix, Btu/h-ft2-°F; and
And = area of non-display door, ft2.
4.5.2 Direct Energy Consumption of
Electrical Components of Non-Display Doors
Electrical components associated with a
walk-in non-display door comprise any
components that are on the non-display door
and that directly consume electrical energy.
This includes, but is not limited to, heater
wire (for anti-sweat or anti-freeze
application), control system units, and
sensors.
(a) Select the required value for percent
time off for each type of electricity
consuming device, PTOt (%)
(1) For lighting without timers, control
system or other demand-based control, PTO
= 25 percent. For lighting with timers,
control system or other demand-based
control, PTO = 50 percent.
(2) For anti-sweat heaters on coolers (if
included): Without timers, control system or
other demand-based control, PTO = 0
percent. With timers, control system or other
demand-based control, PTO = 75 percent. For
anti-sweat heaters on freezers (if included):
Without timers, control system or other autoshut-off systems, PTO = 0 percent. With
timers, control system or other demand-based
control, PTO = 50 percent.
(3) For all other electricity consuming
devices: Without timers, control system, or
other auto-shut-off systems, PTO = 0 percent.
If it can be demonstrated that the device is
controlled by a preinstalled timer, control
system or other auto-shut-off system, PTO =
25 percent.
(b) Calculate the power usage for each type
of electricity consuming device, Pnd-comp,u,t,
kWh/day, as follows:
Where:
u = the index for each type of electricityconsuming device located on either (1)
the interior facing side of the display
door or within the inside portion of the
display door, (2) the exterior facing side
of the display door, or (3) any
combination of (1) and (2). For purposes
of this calculation, the interior index is
represented by u = int and the exterior
index is represented by u = ext. If the
electrical component is both on the
interior and exterior side of the display
door then u = int. For anti-sweat heaters
sited anywhere in the display door, 75
percent of the total power is attributed to
u = int and 25 percent of the total power
is attributed to u = ext;
t = index for each type of electricity
consuming device with identical rated
power;
Prated,u,t = rated power of each component, of
type t, kW;
PTOu,t = percent time off, for device of type
t, %; and
nu,t = number of devices at the rated power
of type t, unitless.
(c) Calculate the total electrical energy
consumption for interior and exterior power,
Pnd-tot, int (kWh/day) and Pnd-tot, ext (kWh/day),
respectively, as follows:
Where:
t = index for each type of electricity
consuming device with identical rated
power;
Pnd-comp,int, t = the energy usage for an
electricity consuming device sited on the
internal facing side or internal to the
ER15AP11.057
4.5 Non-Display Doors
4.5.1 Conduction Through Non-Display
Doors
(a) Calculate the surface area, as defined in
section 3.4 of this appendix, of the non-
17:52 Apr 14, 2011
Jkt 223001
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
E:\FR\FM\15APR3.SGM
15APR3
ER15AP11.054
ER15AP11.055
VerDate Mar<15>2010
ER15AP11.053
srobinson on DSKHWCL6B1PROD with RULES3
ER15AP11.056
Where:
Edd, thermal = the total daily energy
consumption due to thermal load for the
display door, kWh/day;
Pdd-tot = the total electrical load, kWh/day;
and
Cdd-load = additional refrigeration load due to
thermal output from electrical
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
non-display door, of type t, kWh/day;
and
Pnd-comp,ext, t = the energy usage for an
electricity consuming device sited on the
external facing side of the non-display
door, of type t, kWh/day. For anti-sweat
heaters,
21611
(d) Calculate the total electrical energy
consumption, Pnd-tot, kWh/day, as follows:
Where:
Pnd-tot,int = the total interior electrical energy
usage for the non-display door, of type
t, kWh/day; and
Pnd-tot,ext = the total exterior electrical energy
usage for the non-display door, of type
t, kWh/day.
4.5.3 Total Indirect Electricity Consumption
Due to Electrical Devices
Where:
EER = EER of walk-in cooler or freezer, Btu/
W-h; and
Pnd-tot,int = the total interior electrical energy
consumption for the non-display door,
kWh/day.
4.5.4 Total Non-Display Door Energy
Consumption
Where:
Qcond-nd = the conduction load through the
non-display door, Btu/hr; and
EER = EER of walk-in (cooler or freezer), Btu/
W-h.
(c) Calculate the total energy, End,tot, kWh/
day, as follows:
Where:
End, thermal = the total daily energy
consumption due to thermal load for the
non-display door, kWh/day;
Pnd-tot = the total electrical energy
consumption, kWh/day; and
Cnd-load = additional refrigeration load due to
thermal output from electrical
components contained on the inside face
of the non-display door, kWh/day.
(1) Test Sample Geometry Requirements
(i) Two (2) panels, 8 ft. ± 1 ft. long and
4 ft. ± 1 ft. wide must be used.
(ii) The panel edges must be joined using
the manufacturer’s panel interface joining
system (e.g., camlocks, standard gasketing,
etc.).
(iii) The Panel Edge Test Region, see figure
1, must be cut using the following
dimensions:
1. If the panel contains framing members
(e.g. a wood frame), then the width of edge
(W) must be as wide as any framing member
plus 2 in. ± 0.25 in. For example, if the face
of the panel contains 1.5 in. thick framing
members around the edge of the panel, then
width of edge (W) = 3.5 in. ± 0.25 in and the
Panel Edge Test Region would be 7 in.
± 0.5 in. wide.
2. If the panel does not contain framing
members, then the width of edge (W) must
be 4 in. ± 0.25 in.
3. Walk-in panels that utilize vacuum
insulated panels (VIP) for insulation, width
of edge (W) = the lesser of 4.5 in. ± 1 in. or
the maximum width that does not cause the
VIP to be pierced by the cutting device when
the edge region is cut.
(iv) Panel Core Test Region of length Y and
height Z, see Figure 1, must also be cut from
one of the two panels such that panel length
= Y + X, panel height = Z + X where X =
2W.
ER15AP11.061
ER15AP11.059
ER15AP11.060
(a) Select Energy Efficiency Ratio (EER), as
follows:
(1) For coolers, use EER = 12.4 Btu/W-h
(2) For freezers, use EER = 6.3 Btu/W-h
(b) Calculate the total daily energy
consumption due to thermal load, End, thermal,
kWh/day, as follows:
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
E:\FR\FM\15APR3.SGM
15APR3
ER15AP11.058
srobinson on DSKHWCL6B1PROD with RULES3
5.0 Test Methods and Measurements
5.1 Measuring Floor and Non-Floor Panel
U-Factors
Follow the test procedure in ASTM C1363,
(incorporated by reference; see § 431.303),
exactly, with these exceptions:
(a) Select Energy Efficiency Ratio (EER), as
follows:
(1) For coolers, use EER = 12.4 Btu/Wh
(2) For freezers, use EER = 6.3 Btu/Wh
(b) Calculate the additional refrigeration
energy consumption due to thermal output
from electrical components associated with
the non-display door, Cnd-load, kWh/day, as
follows:
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules and Regulations
(2) Testing Conditions
(i) The air temperature on the ‘‘hot side’’,
as denoted in ASTM C1363, of the non-floor
panel should be maintained at 75 °F ± 1 °F.
1. Exception: When testing floor panels,
the air temperature should be maintained at
55 °F ± 1 °F.
(ii) The temperature on the ‘‘cold side’’, as
denoted in ASTM C1363, of the panel should
be maintained at 35 °F ± 1 °F for the panels
used for walk-in coolers and ¥10 °F ± 1 °F
for panels used for walk-in freezers.
(iii) The air velocity must be maintained as
natural convection conditions as described in
ASTM C1363. The test must be completed
using the masked method and with surround
panel in place as described in ASTM C1363.
(3) Required Test Measurements
(i) Non-floor Panels
1. Panel Edge Region U-factor: Unf, edge
2. Panel Core Region U-factor: Unf, core
(ii) Floor Panels
1. Floor Panel Edge Region U-factor:
Ufp, edge
2. Floor Panel Core Region U-factor: Ufp, core
srobinson on DSKHWCL6B1PROD with RULES3
5.2 Measuring Long Term Thermal
Resistance (LTTR) of Insulating Foam
Follow the test procedure in Annex C of
DIN EN 13164 or Annex C of DIN EN 13165
VerDate Mar<15>2010
17:52 Apr 14, 2011
Jkt 223001
(as applicable), (incorporated by reference;
see § 431.303), exactly, with these
exceptions:
(1) Temperatures During Thermal
Resistance Measurement
(i) For freezers: 35 °F ± 1 °F must be used
(ii) For coolers: 55 °F ± 1 must be used
(2) Sample Panel Preparation
(i) A 800mm × 800mm square (× thickness
of the panel) section cut from the geometric
center of the panel that is being tested must
be used as the sample for completing DIN EN
13165.
(ii) A 500mm × 500mm square (× thickness
of the panel) section cut from the geometric
center of the panel that is being tested must
be used as the sample for completing DIN EN
13164.
(3) Required Test Measurements
(i) Non-floor Panels
1. Long Term Thermal Resistance: RLTTR,nf
(ii) Floor Panels
1. Long Term Thermal Resistance: RLTTR,fp
surfaces of the door should be based on the
coefficients described in section 4.3 of NFRC
100.
(2) Internal conditions:
(i) Air temperature of 35 °F (1.7 °C) for
cooler doors and ¥10 °F (¥23.3 °C) for
freezer doors
(ii) Mean inside radiant temperature must
be the same as shown in section 5.3(a)(2)(i),
above.
(3) External conditions
(i) Air temperature of 75 °F (23.9 °C)
(ii) Mean outside radiant temperature must
be the same as section 5.3(a)(3)(i), above.
(4) Direct solar irradiance = 0 W/m2 (Btu/
h-ft2).
(b) Required Test Measurements
(i) Display Doors and Display Panels
1. Thermal Transmittance: Udd
(ii) Non-Display Door
1. Thermal Transmittance: Und
5.3 U-factor of Doors and Display Panels
(a) Follow the procedure in NFRC 100,
(incorporated by reference; see § 431.303),
exactly, with these exceptions:
(1) The average convective heat transfer
coefficient on both interior and exterior
[FR Doc. 2011–8690 Filed 4–14–11; 8:45 am]
PO 00000
Frm 00034
Fmt 4701
Sfmt 9990
BILLING CODE 6450–01–P
E:\FR\FM\15APR3.SGM
15APR3
ER15AP11.062
21612
Agencies
[Federal Register Volume 76, Number 73 (Friday, April 15, 2011)]
[Rules and Regulations]
[Pages 21580-21612]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2011-8690]
[[Page 21579]]
Vol. 76
Friday,
No. 73
April 15, 2011
Part III
Department of Energy
-----------------------------------------------------------------------
10 CFR Part 431
Energy Conservation Program: Test Procedures for Walk-In Coolers and
Walk-In Freezers; Final Rule
Federal Register / Vol. 76, No. 73 / Friday, April 15, 2011 / Rules
and Regulations
[[Page 21580]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Part 431
[Docket No. EERE-2008-BT-TP-0014]
RIN 1904-AB85
Energy Conservation Program: Test Procedures for Walk-In Coolers
and Walk-In Freezers
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: On January 4, 2010, the U.S. Department of Energy (DOE) issued
a notice of proposed rulemaking (January 2010 NOPR) to establish new
test procedures for walk-in coolers and walk-in freezers (WICF or walk-
ins). On September 9, 2010, DOE issued a supplemental notice of
proposed rulemaking (September 2010 SNOPR) to propose changes to the
test procedures that it proposed in the NOPR. Those proposed
rulemakings serve as the basis for today's action. DOE is issuing a
final rule that establishes new test procedures for measuring the
energy efficiency of certain walk-in cooler and walk-in freezer
components including panels, doors, and refrigeration systems. These
test procedures will be mandatory for product testing to demonstrate
compliance with energy standards that DOE is establishing in a
separate, but concurrent rulemaking, and for representations starting
180 days after publication. This final rule incorporates by reference
industry test procedures that, along with calculations established in
the rule, can be used to measure the energy consumption or performance
characteristics of certain components of walk-in coolers and walk-in
freezers. Additionally, the final rule clarifies the definitions of
``Display door,'' ``Display panel,'' ``Door,'' ``Envelope,'' ``K-
factor,'' ``Panel,'' ``Refrigerated,'' ``Refrigeration system,'' ``U-
factor,'' ``Automatic door opener/closer,'' ``Core region,'' ``Edge
region,'' ``Surface area,'' ``Rating condition,'' and ``Percent time
off'' as applicable to walk-in coolers and walk-in freezers.
DATES: The effective date of this rule is May 16, 2011. The final rule
changes will be mandatory for product testing starting October 12,
2011.
The incorporation by reference of certain publications listed in
this rule was approved by the Director of the Federal Register on May
16, 2011.
ADDRESSES: The public may review copies of all materials related to
this rulemaking at the U.S. Department of Energy, Resource Room of the
Building Technologies Program, 950 L'Enfant Plaza, SW., Suite 600,
Washington, DC (202) 586-2945, between 9 a.m. and 4 p.m., Monday
through Friday, except Federal holidays. Please contact Ms. Brenda
Edwards at the above telephone number, or by e-mail at Brenda_Edwards@ee.doe.gov, for additional information regarding visiting the
Resource Room.
Docket: The docket is available for review at regulations.gov,
including Federal Register notices, framework documents, public meeting
attendee lists and transcripts, comments, and other supporting
documents/materials. All documents in the docket are listed in the
regulations.gov index. However, not all documents listed in the index
may be publicly available, such as information that is exempt from
public disclosure.
A link to the docket web page can be found at: https://www1.eere.energy.gov/buildings/appliance_standards/commercial/wicf.html. This web page will contain a link to the docket for this
notice on the regulations.gov site. The regulations.gov web page will
contain simple instructions on how to access all documents, including
public comments, in the docket.
FOR FURTHER INFORMATION CONTACT:
Mr. Charles Llenza, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Program, EE-2J,
1000 Independence Avenue, SW., Washington, DC 20585-0121. Telephone:
(202) 586-2192. E-mail: Charles.Llenza@ee.doe.gov.
Mr. Michael Kido, U.S. Department of Energy, Office of the General
Counsel, GC-71, 1000 Independence Avenue, SW., Washington, DC 20585-
0121. Telephone: (202) 586-8145. E-mail: Michael.Kido@hq.doe.gov or Ms.
Elizabeth Kohl, U.S. Department of Energy, Office of the General
Counsel, GC-71, 1000 Independence Avenue, SW., Washington, DC 20585-
0121. Telephone: (202) 586-7796. E-mail: Elizabeth.Kohl@hq.doe.gov.
SUPPLEMENTARY INFORMATION: This final rule incorporates by reference
into subpart R of Title 10, Code of Federal Regulations, part 431 (10
CFR part 431), the following industry standards:
(1) AHRI 1250 (I-P)-2009, ``2009 Standard for Performance Rating of
Walk-In Coolers and Freezers,'' approved 2009.
(2) ASTM C1363-05, ``Standard Test Method for Thermal Performance
of Building Materials and Envelope Assemblies by Means of a Hot Box
Apparatus,'' approved May 1, 2005.
(3) DIN EN 13164:2009-02, ``Thermal insulation products for
buildings--Factory made products of extruded polystyrene foam (XPS)--
Specification,'' approved February 2009.
(4) DIN EN 13165:2009-02, ``Thermal insulation products for
buildings--Factory made rigid polyurethane foam (PUR) products--
Specification,'' approved February 2009.
(5) NFRC 100-2010[E0A1], ``Procedure for Determining Fenestration
Product U-factors,'' approved 2010.
Copies of ASTM standards can be obtained from ASTM International,
100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, (610) 832-
9585, or https://www.astm.org.
Copies of AHRI standards can be obtained from AHRI. Air-
Conditioning, Heating and Refrigeration Institute, 2111 Wilson
Boulevard, Suite 500, Arlington, VA 22201, (703) 600-0366, or https://www.ahrinet.org.
Copies of DIN EN standards can be obtained from CEN. European
Committee for Standardization (French: Norme or German: Norm), Avenue
Marnix 17, B-1000 Brussels, Belgium, Tel: + 32 2 550 08 11, Fax: + 32 2
550 08 19 or https://www.cen.eu.
Copies of NFRC standards can be obtained from NFRC. National
Fenestration Rating Council, 6305 Ivy Lane, Ste. 140, Greenbelt, MD
20770, (301) 589-1776, or https://www.nfrc.org.
You can also view copies of these standards at the U.S. Department
of Energy, Resource Room of the Building Technologies Program, 950
L'Enfant Plaza, SW., 6th Floor, Washington, DC 20024, (202) 586-2945,
between 9 a.m. and 4 p.m., Monday through Friday, except Federal
holidays.
Table of Contents
I. Authority and Background
II. Summary of the Final Rule
III. Discussion
A. Overall Approach: Component-Based Testing
1. Test Metrics
2. Responsibility for Testing and Compliance
3. Basic Model
B. Test Procedures for Envelope Components
1. Definition of Envelope
2. Heat Transfer Through Panels
3. Energy Use of Doors
4. Heat Transfer via Air Infiltration
5. Electrical Components
C. Test Procedures for Refrigeration Systems
1. Definition of Refrigeration System
2. Refrigeration Test Procedure: AHRI 1250 (I-P)-2009
3. Alternative Efficiency Determination Method
D. Other Issues--Definition of Walk-In Cooler or Freezer
[[Page 21581]]
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
1. Statement of the Need for, and Objectives of, the Rule
2. Summary of the Significant Issues Raised by the Public
Comments, DOE's Response to These Issues, and Any Changes Made in
the Proposed Rule as a Result of Such Comments
3. Description and Estimated Number of Small Entities Regulated
4. Description and Estimate of Compliance Requirements and
Description of Steps To Minimize the Economic Impact on Small
Entities
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
N. Approval of the Office of the Secretary
I. Authority and Background
Title III of the Energy Policy and Conservation Act (42 U.S.C.
6291-6317; ``EPCA'' or, ``the Act'') sets forth a variety of provisions
designed to improve energy efficiency. (All references to EPCA refer to
the statute as amended through the Energy Independence and Security Act
of 2007 (EISA 2007), Public Law 110-140 (Dec. 19, 2007)). Part C of
Title III (42 U.S.C. 6311-6317), which was subsequently redesignated as
Part A-1 for editorial reasons, establishes an energy conservation
program for certain industrial equipment. This includes walk-in coolers
and walk-in freezers, the subject of today's notice. (42 U.S.C.
6311(1), (20), 6313(f), and 6314(a)(9))
Under EPCA, this program consists essentially of three parts: (1)
Testing, (2) labeling, and (3) Federal energy conservation standards.
The testing requirements consist of test procedures that manufacturers
of covered products or equipment must use (1) as the basis for
certifying compliance with the applicable energy conservation standards
adopted under EPCA, and (2) for making representations about the
efficiency of those products. Similarly, DOE must use these test
requirements to determine whether the products comply with any relevant
standards promulgated under EPCA.
Section 312 of the Energy Independence and Security Act of 2007
(``EISA 2007'') amended EPCA by adding certain equipment to this energy
conservation program, including walk-in coolers and walk-in freezers
(collectively ``walk-in equipment,'' ``walk-ins,'' or ``WICF.''). (42
U.S.C. 6311(1), (20), 6313(f), and 6314(a)(9)) As amended by EISA 2007,
EPCA requires DOE to establish new test procedures to measure the
energy use of walk-in coolers and walk-in freezers. (42 U.S.C.
6314(a)(9)(B)(i)) The new test procedures for WICF equipment are the
subject of this rulemaking. EPCA also directs DOE to publish
performance-based standards and promulgate labeling requirements (42
U.S.C. 6313(f)(4)(A) and 42 U.S.C. 6315(e), respectively). These
actions will be covered in separate rulemakings.
In the notice of proposed rulemaking published January 4, 2010
(January 2010 NOPR or, in context, NOPR), DOE proposed to establish
test procedures to measure the energy efficiency of walk-in coolers and
freezers. 75 FR 186. DOE identified several issues in its proposal
based on the public comments submitted in response to the January 2010
NOPR and further research. These issues included: (1) The proposed
definition of a walk-in cooler or freezer with regards to the upper
temperature limit; (2) the proposal to create test procedures for the
envelope and refrigeration system of a walk-in cooler or freezer; (3)
the proposal to group walk-in envelopes and refrigeration systems with
essentially identical construction methods, materials, and components
into a single basic model; and (4) the proposed calculation methodology
for determining the energy consumption of units within the same basic
model. 75 FR 186, (Jan. 4, 2010). On March 1, 2010, DOE held a public
meeting to receive comments, data, and information on the January 2010
NOPR. Through their comments, interested parties raised significant
issues and suggested changes to the proposed test procedures. DOE
determined that some of these comments warranted further consideration
and published a supplemental notice of proposed rulemaking on September
9, 2010 (September 2010 SNOPR or, in context, SNOPR). 75 FR 55068. DOE
received 22 written comments on the September 2010 SNOPR. This final
rule addresses comments from the January 2010 NOPR that were not
addressed in the September 2010 SNOPR and comments received on the
September 2010 SNOPR.
General Test Procedure Rulemaking Process
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered equipment. EPCA provides that test procedures ``shall be
reasonably designed to produce test results which reflect energy
efficiency, energy use and estimated annual operating costs of a type
of industrial equipment (or class thereof) during a representative
average use cycle as determined by the Secretary [of Energy], and shall
not be unduly burdensome to conduct.'' (42 U.S.C. 6314(a)(2))
Additionally, EPCA notes that if the procedure determines estimated
annual operating costs, the procedure ``shall provide that such costs
shall be calculated from measurements of energy use in a representative
average use cycle (as determined by the Secretary), and from
representative average-unit costs of the energy needed to operate such
equipment during such cycle.'' (42 U.S.C. 63114(a)(3)) Further, the
statute provides that DOE ``shall provide information to manufacturers
of covered equipment respecting representative average unit costs of
energy.'' Id.
With respect to today's rulemaking, the test procedure DOE is
prescribing today is a new test procedure. Today's rule establishes a
comprehensive testing regime to ensure minimum levels of performance by
applying the component-based approach detailed in EISA 2007. The
separate but concurrent energy conservation standards rulemaking for
walk-in coolers and walk-in freezers will be based on the performance
of walk-in coolers and walk-in freezers as measured by the test
procedure set forth in this final rule.
II. Summary of the Final Rule
Today's final rule establishes a new test procedure for measuring
the energy efficiency of walk-in cooler and walk-in freezer equipment.
The test procedure is essentially composed of tests for the principal
components that make up a walk-in: Panels, doors, and refrigeration.
Testing individual components of walk-in coolers and walk-in freezers
is simpler and less burdensome to manufacturers than testing an entire
walk-in. In this test procedure, DOE also provides a method for
calculating the energy use of an entire envelope, or the efficiency of
a refrigeration system, based on the results of the component tests.
The test procedure incorporates by reference the industry test
procedures ASTM C1363-05, ``Standard Test
[[Page 21582]]
Method for Thermal Performance of Building Materials and Envelope
Assemblies by Means of a Hot Box Apparatus,''DIN EN 13164:2009-02,
``Thermal insulation products for buildings--Factory made products of
extruded polystyrene foam (XPS)--Specification,'' DIN EN 13165:2009-02,
``Thermal insulation products for buildings--Factory made rigid
polyurethane foam (PUR) products--Specification,'' NFRC 100-2010[E0A1],
``Procedure for Determining Fenestration Product U-factors,'' and AHRI
1250 (I-P)-2009, ``2009 Standard for Performance Rating of Walk-In
Coolers and Freezers.''
Concurrently, DOE is undertaking an energy conservation standards
rulemaking to address the statutory requirement to establish
performance standards for walk-in equipment by 2012. (42 U.S.C.
6313(f)(4)(A)) DOE will use this test procedure in the concurrent
process of evaluating potential performance standards for the
equipment. After the compliance date of the performance standards, this
walk-in cooler and walk-in freezer test procedure, along with any
future statistical sampling plans that may be adopted, must be used by
manufacturers to determine compliance with the standards, and by DOE to
ascertain compliance with the standards in any enforcement action.
Moreover, once any final test procedure is effective, any
representation of the energy use of walk-in equipment or components
must reflect the results of testing that equipment using the test
procedure.
III. Discussion
In this section, DOE describes the overall approach it followed in
developing today's test procedure for walk-in cooler and freezer
equipment, including envelope components and refrigeration systems. The
following section also addresses issues raised by interested parties,
which consisted of the following entities:
Manufacturers: American Panel, Craig Industries,
CrownTonka, Heatcraft Refrigeration Products (Heatcraft), Hill Phoenix,
International Cold Storage (ICS), Kysor Panel Systems (Kysor Panel),
Manitowoc, Master-Bilt, Owens Corning, Nor-Lake, ThermalRite, Thermo-
Kool, and Zero Zone;
Material suppliers: Carpenter Company (Carpenter);
Trade associations: AHRI, Center for the Polyurethanes
Industry (CPI);
Utility companies: Pacific Gas & Electric Company (PG&E),
Southern California Edison (SCE), Sacramento Municipal Utility District
(SMUD), and San Diego Gas and Electric (SDG&E);
Advocacy groups: Appliance Standards Awareness Project
(ASAP), Alliance to Save Energy (ASE), American Council for an Energy-
Efficient Economy (ACEEE), Natural Resources Defense Council (NRDC),
Northeast Energy Efficiency Partnerships (NEEP), and Northwest Energy
Efficiency Alliance (NEEA);
Other parties: Oak Ridge National Laboratory (ORNL), and
the Small Business Administration (SBA).
A. Overall Approach: Component-Based Testing
In the framework document, DOE contemplated developing a single
test for an entire walk-in cooler or freezer. See https://www1.eere.energy.gov/buildings/appliance_standards/commercial/pdfs/wicf_framework_doc.pdf. However, feedback from interested parties
indicated that a single test procedure for the entire WICF would not be
practical because many walk-ins are assembled on site with components
from different manufacturers, which would make on-site testing
infeasible. DOE then proposed in the January 2010 NOPR and September
2010 SNOPR to develop separate tests for the envelope and refrigeration
system of a walk-in, which in aggregate would represent the performance
of the entire walk-in (75 FR 186, 191 (Jan. 4, 2010) and 75 FR 55068,
55070 (Sept. 9, 2010)). DOE proposed to have one metric for the
refrigeration system, which would be an efficiency metric, and one
metric for the envelope, which would be an energy use metric. The
envelope metric would account for electrical use of envelope
components, as well as any energy used by the refrigeration system to
reject the heat contributed by conduction, infiltration, and other heat
sources. In this way, DOE intended to capture the energy impact of
components, such as panels, that do not themselves consume electricity.
DOE received comments on the September 2010 SNOPR from interested
parties stating that the walk-in cooler and walk-in freezer main
components could be further broken down into their own constituent
components: panels and doors of envelopes and unit coolers and
condensing units of refrigeration systems. Commenters explained that
all of these components could be produced by separate manufacturers and
then assembled into a complete walk-in. Because of this situation, it
would be difficult to determine who should test the walk-in envelope,
the refrigeration system, or both. It would also be difficult to
determine who would be best positioned to ensure the walk-in cooler or
freezer complied with an energy conservation standard. DOE acknowledges
these and similar concerns from the stakeholders.
Based on the information provided by commenters and DOE's own
research, DOE has determined that a component-based approach would
address the unique challenges posed in regulating the energy efficiency
performance of walk-in envelopes. As noted above, these challenges
include the fact that walk-in units are frequently assembled using
components made by multiple manufacturers, and walk-in installers may
not be equipped to test all the components that comprise a walk-in.
These factors indicate that a component-based approach would not only
help ensure compliance with whatever energy conservation standards that
DOE sets, but also reduce the overall testing burden on the
manufacturers, including small businesses who are involved in producing
walk-in units, either in full or in part.
Moreover, DOE notes that the adoption of such an approach is
consistent with the component-based approach that Congress took when it
enacted EISA 2007. Thus, DOE is adopting a component-level approach for
this rule and discusses the specific component metrics in greater
detail in section III.A.1.
1. Test Metrics
As stated previously, DOE initially proposed separate test
procedures for envelopes and refrigeration systems of walk-ins along
with different test metrics for each. The metric for the refrigeration
system would be an efficiency metric, and the metric for the envelope
would be an energy use metric that would account for the electrical use
of envelope components and the energy used by the refrigeration system
to reject the heat contributed by conduction, infiltration, and other
heat sources. To account for different sizes of envelopes, DOE further
proposed that the result of the envelope test procedure should be a
normalized energy use metric--the total energy use divided by the
external surface area of the envelope (energy use per square foot).
Several interested parties disagreed with the proposed metrics.
NEEA stated that regulating walk-in coolers and walk-in freezers on the
basis of annual energy use would not accurately estimate actual energy
use, and therefore such estimates would be misleading for almost all
installed systems. NEEA suggested using an overall U-value for the
entire envelope and a spreadsheet that calculates the overall U-factor
of a walk-in by weighted area. (NEEA, No. 0061.1 at
[[Page 21583]]
p. 1 and 9; NEEA, No. 0061.2 at p. 1) (In this and subsequent
citations, the document number refers to the number of the comment in
the Docket for the DOE rulemaking on test procedures for walk-in
coolers and freezers, Docket No. EERE-2008-BT-TP-0014; and the page
references refer to the place in the document where the statement
preceding appears.) NRDC also disagreed with the annual energy use
metric because of the number of assumptions that would be required and
the potential to confuse customers. (NRDC, No. 0064.1 at p. 7) NRDC
further stated that normalizing energy use to the surface area would be
unusual and may not be useful. (NRDC, No. 0064.1 at p. 2) NEEA
suggested that the envelope metric should be a U-factor (which is a
characterization of the heat loss performance). (NEEA, No. 0061.1 at p.
7) A comment submitted jointly by SCE, SDG&E, PG&E, and SMUD, hereafter
referred to as the Joint Utilities, suggested an area-based conductance
metric for the envelope that would consider both opaque and transparent
surfaces. (The Joint Utilities, No. 0059.1 at p. 2) NRDC also suggested
a metric for refrigeration systems that would encompass the total
equivalent warming impact and measure the heat loads from refrigeration
systems impacting a building's heating, ventilation, and air
conditioning (HVAC) system. (NRDC, No. 0064.1 at p. 8) A comment
submitted jointly by ACEEE, ASAP, ASE, NRDC, NEEP, and NEEA on the
September 2010 SNOPR (hereafter referred to as The Joint SNOPR comment)
stated that the energy conservation standard for envelopes should be
the overall heat gain (U-overall) with separate standards for walk-in
coolers and walk-in freezers. (Joint SNOPR Comment, No. 0074.1 at p. 2)
While other interested parties suggested specific metrics for walk-
in components, manufacturers also offered suggestions for overall walk-
in metrics. Craig Industries recommended combining the envelope and
refrigeration calculations to calculate the overall efficiency of the
complete walk-in system and labeling each walk-in with that efficiency
metric. (Craig, No. 0068.1 at p. 6) Zero Zone stated that the test
procedure should include performance testing to verify adequate
temperatures inside the walk-in. (Zero Zone, No. 0077.1 at p. 1)
In view of the component-level approach being adopted today, DOE is
not establishing an overall energy use metric for the envelope in this
test procedure. Instead, DOE is establishing separate metrics for the
individual components of the walk-in: the wall and ceiling panels
(hereafter referred to as non-floor panels); floor panels; the display
and non-display doors; and the refrigeration system. Regarding Zero
Zone's suggestion that the procedure verify that adequate internal
temperatures are used in evaluating a walk-in unit's efficiency, DOE
does not believe that such a requirement is necessary in light of the
component-based approach being adopted today.
The panel metric determined by the test procedure accounts for the
conductance and is in terms of U-factor (that is, the thermal
transmittance) measured in Btu/h-ft\2\-[deg]F, as NEEA, the Joint SNOPR
Comment, and the Joint Utilities recommended. The metric for display
and non-display doors accounts for the thermal transmittance through
the door and the electricity use of any electrical components
associated with the door, and is in terms of energy use, measured in
kWh/day. DOE believes that requiring separate metrics for specific
individual walk-in components does not constitute a substantive change
from what was proposed in the September 2010 SNOPR because this Final
Rule only requires tests that were proposed for components in the
September 2010 SNOPR. Also, the September 2010 SNOPR and this final
rule contain similar calculation methodologies.
2. Responsibility for Testing and Compliance
DOE proposed to adopt separate tests for the envelope and
refrigeration system of a walk-in and require the manufacturers of each
to test and certify the part they manufacture. 75 FR 186, 191 (Jan. 4,
2010) and 75 FR 55068, 55070 (Sept. 9, 2010). In response to this
proposed approach, DOE received multiple comments regarding who should
assume testing, certification, and compliance responsibilities. The
Joint SNOPR Comment recommended that DOE focus on factory-produced
products (i.e. kits) instead of walk-ins that are assembled on-site
from components from different manufacturers. (Joint SNOPR Comment, No.
0074.1 at p. 1) The Joint SNOPR Comment further suggested that panel,
refrigeration system, and door manufacturers each be responsible for
compliance and certification responsibilities for their own products.
(Joint SNOPR Comment, No. 0074.1 at pp. 2-3) Thermo-Kool agreed with
this approach and submitted a copy of a regulatory framework proposed
by NEEA, in which envelope, door, and refrigeration manufacturers would
be responsible for testing and complying with the standards for the
components they manufacture. (Thermo-Kool, No. 0072.1 at p. 1)
DOE received several other comments which it summarized in the
certification, compliance, and enforcement (CCE) final rule, published
on March 7, 2011. 76 FR 12422, 12444. In brief, some of those comments
agreed with the approach suggested by the Joint SNOPR Comment and
Thermo-Kool that individual component manufacturers should test,
certify, and ensure compliance of their respective components. Other
commenters recommended that the manufacturer, the assembler, or the
system designer of the overall walk-in should be responsible for the
compliance of the walk-in with the standards. 76 FR 12442-12446.
In the CCE final rule, DOE addressed these comments by defining the
manufacturer of a walk-in at 10 CFR 431.302. 76 FR 12504.
The definition extends the compliance responsibility to both the
component manufacturer and the assembler. In the CCE final rule, DOE
clarified that component manufacturers would be the entity responsible
for certifying compliance of the components they manufacture for walk-
in applications and ensuring compliance with the applicable Federal
standards of those components. Assemblers of the complete walk-in
system are required to use only components that are certified to meet
the applicable Federal standards. DOE also adopted a flexible
enforcement framework in which it will determine who is responsible for
noncompliance on a case-by-case basis. 76 FR 12444.
DOE notes that the provisions and clarifications in the CCE final
rule were made in the context of component manufacturers certifying
their components to the existing standards in EPCA, which prescribe
requirements on a component-level basis. DOE has decided to continue
this approach in developing test procedures and performance-based
standards for walk-in coolers and freezers. DOE believes that, within
the very limited context of walk in equipment, EPCA created a means for
DOE to set performance-based standards for certain walk-in component
manufacturers. In particular, because Congress set requirements for
specific components used in walk-in applications, it provided DOE with
the implicit authority to set performance-based standards at the
component level for these specific components. This unique ability
stems from the manner in which Congress set standards for walk-in
equipment by prescribing, among
[[Page 21584]]
other things, specific performance-based requirements for wall,
ceiling, door, and floor insulation panels used in walk-ins. See 42
U.S.C. 6313(f).
Because interested parties, including entities who produce these
components and are subject to today's requirements, have indicated to
DOE that the energy efficiency performance of WICF components would be
most readily and easily tested and certified by component
manufacturers, DOE intends to take this approach for WICF test
procedures and performance standards. DOE acknowledges the numerous
difficulties that commenters have noted with alternative proposed
approaches. By requiring individual component manufacturers to certify
that their components satisfy specified performance-based standards,
DOE can ease the overall burden on walk-in manufacturers relative to
the alternatives that were under consideration as part of the January
2010 NOPR and September 2010 SNOPR. Therefore, in this test procedure,
DOE is establishing tests for the components of a walk-in (i.e. panels,
doors, and refrigeration systems) and anticipates that component
manufacturers will test their equipment using the applicable procedure
and, in the future, will certify that they comply with the appropriate
standard. DOE emphasizes that until performance standards are
established, manufacturers are not required to use this test procedure
to certify equipment to DOE (although they must use this test procedure
in making representations as to the performance of their components).
However, because the prescriptive standards established by the 2007
amendments to EPCA are already in effect, manufacturers must
demonstrate compliance with them using the method specified in the CCE
final rule. 76 FR 12422.
3. Basic Model
DOE proposed a definition of basic model for both envelopes and
refrigeration systems. 75 FR 186, 188-189 (Jan. 4, 2010) and 75 FR
55068, 55071-55073 (Sept. 9, 2010). DOE received comments from
interested parties on the definition and summarized them in the CCE
final rule. 76 FR 12422. Consistent with its component-level approach
to certification, discussed in section III.A.2, and taking the comments
from interested parties into consideration, DOE decided to define a
basic model for each of the key components of a walk-in, rather than
defining a basic model for the entire walk-in. DOE emphasized that
although the term ``basic model'' is defined on the component level, it
is still implemented in the same manner as it is in the rest of DOE's
appliance standards program; that is, a basic model consists of
equipment that is essentially the same with respect to energy
consumption, efficiency, or other measure of performance. 76 FR 12444-
12446.
DOE provided, in relevant part, the definition of basic model in
the CCE final rule at 76 FR 12504 (providing definition of ``basic
model'' for walk-ins) (to be codified at 10 CFR 431.302).
DOE believes applying the basic model concept at the component
level will reduce the testing burden on manufacturers while ensuring
that their products meet any applicable standard, because it removes
the difficulty of testing and/or certifying different sized walk-ins
that would have different energy consumption levels. 76 FR 12445. The
CCE final rule provides that manufacturers may elect to group
individual models into basic models at their discretion to the extent
the models have essentially identical characteristics that affect
energy efficiency or energy consumption. Manufacturers may also rate
models conservatively--i.e. the tested performance of the model(s) must
be at least as good as the certified rating--after applying the
appropriate sampling plan. 76 FR 12429. The basic model concept is
applied slightly differently to panels, doors, and refrigeration
systems because of their different characteristics. These differences
are explained below.
a. Basic Model of Panels
Panels are construction components that are not doors and that are
used to construct the envelope of the walk-in. These components
comprise the elements separating the interior refrigerated environment
of the walk-in from the exterior environment. In this test procedure,
panels are classified as either floor panels, non-floor panels, or
display panels. A display panel is a panel that is entirely or
partially comprised of glass, a transparent material, or both and is
used for display purposes. Floor and non-floor panels are mostly
comprised of insulating material and are not primarily used for display
purposes. For all types of panels, the energy efficiency metric is the
U-factor, which is a measure of conductive, convective, and radiative
heat transfer and which takes into account composite panel
characteristics, which may include the insulation type, structural
members, any type of transparent material (e.g. glass), and panel
thickness. See section III.B.2 for details on how the U-factor is
determined. DOE considers a panel basic model to include panels which
do not have any differing features or characteristics that affect the
U-factor. 76 FR 12504.
DOE notes that manufacturers who make customized panels may
experience a higher certification burden than manufacturers of
standardized panels. For example, under today's procedure, a panel's U-
factor is a surface area-independent metric, which implies that
variation in panel width and height alone would not be expected to
affect the U-factor rating if all other characteristics were equal. In
those instances where no changes in energy efficiency would occur,
these panels could be grouped as a basic model. In contrast, smaller
floor and non-floor panels may have a higher proportion of framing
material to non-framing material, or other structural members, which
could affect the overall panel U-factor rating if the framing material
or framing geometry has different thermal conductivity performance than
the neighboring insulation. Therefore, for two or more floor or non-
floor panels that are equivalent in materials and other characteristics
but differ in their frame to insulation proportions such that they have
different U-factor ratings, the panels would be considered different
basic models and would need to be certified independently to DOE, if
the manufacturer chooses to claim different U-factor ratings. However,
DOE emphasizes that as explained in section III.3, manufacturers may
group models into basic models at their discretion as long as the
tested performance of the models is at least as good as the certified
rating.
DOE has also introduced additional provisions to reduce the testing
and certification burden on floor and non-floor panel manufacturers.
See section III.B.2.a for details.
As explained above, the energy efficiency metric for display panels
is the U-factor, as for floor and non-floor panels. However, unlike a
floor, ceiling, or wall panel, a display panel is essentially a window.
Therefore, in this test procedure, DOE is requiring the U-factor of
display panels to be tested using NFRC 100-2010[E0A1], ``Procedure for
Determining Fenestration Product U-factors,'' which DOE proposed in the
SNOPR for measuring the U-factor of doors and windows, including their
framing materials. 75 FR 55083. (Sept. 9, 2010) As with floor and non-
floor panels, the basic model concept allows manufacturers to group
display panels that are essentially identical in U-factor into one
basic model, which DOE anticipates will reduce the testing burden on
display
[[Page 21585]]
panel manufacturers. Also, NFRC 100-2010[E0A1] allows verified computer
models to simulate a display panel's energy consumption, another factor
that reduces the manufacturer's testing burden.
b. Basic Model of Doors
A door is an assembly installed in an opening on an interior or
exterior wall that is used to allow access or close off the opening and
that is movable in a sliding, pivoting, hinged, or revolving manner of
movement. For walk-in coolers and walk-in freezers, a door includes the
door panel, glass, framing materials, door plug, mullion, and any other
elements that form the door or part of its connection to the wall. This
test procedure defines two types of doors, display and non-display
doors. Display doors are doors designed for product movement, display,
or both, rather than the passage of persons, and non-display doors are
considered to be all other types of doors. For all doors, the energy
consumption metric that DOE is adopting in today's rule incorporates
the U-factor and any electrical components built into the door. (See
section I.A.1.a for details.) Calculating this metric requires the use
of NFRC 100-2010[E0A1], ``Procedure for Determining Fenestration
Product U-factors,'' which DOE proposed in the SNOPR for measuring the
U-factor of doors and windows, including their framing materials. 75 FR
55083. (Sept. 9, 2010) Applying the NFRC test yields an overall U-
factor for the tested door. Then, through calculations outlined in
Appendix A, the U-factor and the electrical energy consumption are
combined to create a rating for the door.
As with panels, doors with essentially identical energy consumption
levels may be grouped into a basic model and rated conservatively. 76
FR 12429 and 12504. The basic model concept can be used to reduce the
testing and certification burdens by allowing manufacturers to group
doors that are essentially identical in energy consumption but
cosmetically different. The NFRC procedure also permits either a
physical test or a verified computer model to be used when determining
the U-factor of the door. The latter of these options would be expected
to reduce testing burden because only a series of calculations would
need to be run by an NFRC-approved computer modeling program. DOE also
notes that the calculations for energy consumption of door components
are not based on testing, which reduces the general testing burden for
doors. Any results from physical tests, computer simulations, and
calculations must be retained as required by the CCE final rule. 76 FR
12494.
c. Basic Model of Refrigeration Systems
The refrigeration system consists primarily of a compressor,
condenser, unit cooler, valves, and piping. It is considered a
component under the component level approach (see section III.A) that
DOE is adopting in today's final rule. As with the panels and doors,
and consistent with the approach promulgated in the CCE final rule,
manufacturers may elect to group individual models into basic models at
their discretion to the extent the models have essentially identical
electrical, physical, and functional characteristics that affect energy
efficiency or energy consumption. Furthermore, manufacturers may rate
models conservatively, meaning the tested performance of the model(s)
must be at least as good as the certified rating, after applying the
appropriate sampling plan. 76 FR 12429. DOE believes these provisions
will reduce the burden of testing for refrigeration manufacturers,
including those who make customized equipment. DOE may also consider
methods which allow manufacturers to use an alternate method of
determining the energy use of the refrigeration system in a future
rulemaking. This concept is further discussed in section III.C.3.
B. Test Procedures for Envelope Components
The envelope consists of the insulated box in which items are
stored and refrigerated. In the NOPR and SNOPR, DOE proposed methods
for evaluating the performance characteristics of insulation, testing
thermal energy gains related to air infiltration, and determining
direct electricity use and heat gain due to internal electrical
components. The proposed procedure used these methods to determine the
energy use associated with the envelope by calculating the effect of
the envelope's characteristics and components on the energy consumption
of the walk-in as a whole. Those characteristics and components
included the energy consumption of electrical components present in the
envelope (such as lights) and variation in the energy consumption of
the refrigeration system due to heat loads introduced as a function of
envelope performance (such as conduction of heat through the walls of
the envelope). The impact on the refrigeration system energy
consumption was determined by calculating the energy consumption of a
theoretical or ``nominal'' refrigeration system when paired with the
tested envelope. 75 FR 186, 191 (Jan. 4, 2010) and 75 FR 55068, 55074
(Sept. 9, 2010).
As described in section III.A, DOE is no longer requiring
manufacturers to determine the energy consumption of the entire
envelope in this final rule. Rather, DOE is establishing metrics for
the principal components of the envelope (i.e. the panels and doors) as
described in section III.A.1. In doing so, DOE is requiring
manufacturers to use the same physical tests for the components that it
proposed in the NOPR and SNOPR, but is introducing revisions to the
calculations in Appendix A of the new procedure. These revisions will
enable manufacturers to calculate the required component metrics from
the results of those tests.
For panels, DOE is adopting separate approaches depending on
whether a given panel is a display or non-display panel. Display panels
are panels that are primarily made of transparent material and used for
display purposes. Display panels are considered equivalent to windows
because of their transparent characteristics and associated thermal
heat transfer properties, and therefore the U-factor will be measured
by NFRC 100-2010[E0A1], ``Procedure for Determining Fenestration
Product U-factors,'' which DOE proposed in the SNOPR for measuring the
U-factor of doors and windows, including their framing materials. 75 FR
55083. (Sept. 9, 2010) Non-display panels are floor and non-floor
panels. Since both floor and non-floor panels are typically made out of
a composite of insulation, framing, and facer material, both types of
panels will be tested using the same methodology. In today's rule, the
physical tests pertaining to the performance of non-display panels are
from ASTM C1363-05, ``Standard Test Method for Thermal Performance of
Building Materials and Envelope Assemblies by Means of a Hot Box
Apparatus'' and, for foams that experience aging, DIN EN 13164:2009-02,
``Thermal insulation products for buildings--Factory made products of
extruded polystyrene foam (XPS)--Specification'' or DIN EN 13165:2009-
02, ``Thermal insulation products for buildings--Factory made rigid
polyurethane foam (PUR) products--Specification,'' as applicable. These
tests were proposed in the SNOPR. 75 FR 55068, 55075-55076 and 55081
(Sept. 9, 2010). In this final rule, panel performance is denoted by
its overall U-factor, or thermal transmittance, which is determined by
the test procedures and calculation methodologies described in section
III.B.2.
[[Page 21586]]
DOE is requiring one test for door performance, NFRC 100-
2010[E0A1], ``Procedure for Determining Fenestration Product U-
factors,'' which was proposed in the SNOPR. 75 FR 55083 (Sept. 9,
2010). This test measures conduction through a door, whether it is a
display door or a non-display door. The total energy consumption of a
door is calculated as the effect of a door's thermal load on the
refrigeration system combined with the door's electrical energy use, as
described in section 4.5 and section 4.4 of Appendix A of this final
rule. The effect on the refrigeration system is determined by
calculating the energy consumption that a theoretical or ``nominal''
refrigeration system would use to reject the heat that was transmitted
through the door. The energy that would be used by the theoretical
refrigeration system to reject a given amount of heat is represented by
the energy efficiency ratio (EER) of the refrigeration system. The test
procedure uses the same nominal refrigeration system EER for all tested
doors to enable direct comparisons of the performance of walk-in doors
across a range of sizes, product classes, and features. The nominal EER
values for cooler and freezer refrigeration (i.e. 12.4 Btu/W-h and 6.3
Btu/W-h for coolers and freezers, respectively) are the same as those
proposed in the SNOPR for calculating the energy use of the envelope.
See 75 FR 55013 (Sept. 9, 2010).
1. Definition of Envelope
In the January 2010 NOPR, DOE proposed the following definition of
``envelope:''
Envelope means (1) a piece of equipment that is the portion of a
walk-in cooler or walk-in freezer that isolates the interior,
refrigerated environment from the ambient, external environment; and
(2) all energy-consuming components of the walk-in cooler or walk-in
freezer that are not part of its refrigeration system.
75 FR 186, 192 (Jan. 4, 2010).
The walk-in envelope was proposed to include, but not be limited
to, walls, floors, ceilings, seals, windows, doors, or any combination
thereof, composed of single or composite materials. DOE did not propose
any changes to this definition in the September 2010 SNOPR.
Master-Bilt, BASF, ThermalRite, ACEEE, and ICS submitted written
comments supporting the proposed definition for the walk-in envelope.
(Master-Bilt, No. 0027.1 at p. 1; BASF, No. 0021.1 at p. 3;
ThermalRite, No. 0049.1 at p. 1; ACEEE, No. 0052.1 at p. 2; ICS, No.
0045.1 at p. 1) However, Nor-Lake asked that the definition of envelope
exclude components of the envelope purchased separately by the end user
to enable the manufacturer of the envelope to avoid compliance
responsibility for the performance of those components. (Nor-Lake, No.
0023.1 at p. 2) ICS requested clarification on the preemption of energy
codes by building, electrical, and mechanical codes and stated that the
definition must allow for structural and electrical safety code
compliance over energy compliance when in conflict. (ICS, No. 0045.1 at
p. 1) A representative from Gonzaga Law argued that the definition
proposed by the DOE was too inclusive but did not propose an
alternative definition. (Gonzaga Law, No. 0018 at p. 1) At the public
meeting for the January 2010 NOPR, ICS suggested that DOE's standards
and definitions should align with NSF's (formerly known as the National
Sanitation Foundation) definition of envelope and requirements. (ICS,
Public Meeting Transcript, 0016 at p. 30) (In this and subsequent
citations, ``Public Meeting Transcript'' refers to the transcript of
the March 1, 2010, public meeting on the proposed test procedures for
walk-in coolers and freezers. ``No. 0016'' refers to the document
number of the transcript in the Docket for the DOE rulemaking on test
procedures for walk-in coolers and freezers, Docket No. EERE-2008-BT-
TP-0014; and the page number refers to the place in the transcript
where the statement preceding appears.)
DOE notes the comments and suggestions from Master-Bilt, BASF,
ThermalRite, ACEEE, ICS, and Gonzaga Law. However, because DOE is
taking a component-based approach, the proposed envelope definition is
no longer applicable for the purpose of this test procedure. As
suggested by ICS, when evaluating potential standards applicable to
walk-ins, DOE will also consider their related requirements that
manufacturers need to satisfy. In response to Nor-Lake's comment
regarding components not supplied by the envelope manufacturer, DOE
clarifies that each component manufacturer is responsible for testing
its component with the appropriate test procedure as discussed in
section III.A.2. The envelope component manufacturer is not responsible
for the end user's implementation of the component; rather, the
manufacturer would be responsible only for the component's compliance
as designed. Also, the envelope assembler is responsible for using
WICF-compliant components to assemble the total envelope.
2. Heat Transfer through Panels
a. U-Factor of Composite Panels Including Structural Members of Panels
EPCA specifies that ASTM C518-04, ``Standard Test Method for
Steady-State Thermal Transmission Properties by Means of the Heat Flow
Meter Apparatus,'' must be used to determine the K-factor of walk-in
insulation. The statute defines the R-value as equal to the value of 1/
K-factor multiplied by the thickness of the panel. (42 U.S.C. 6314
(a)(9)(A)(i)-(ii)) In response to the January 2010 NOPR, interested
parties commented that the heat conduction through structural members
must be considered because this factor could affect the conductance
through the composite walk-in insulation panel. Accordingly, DOE
proposed in the September 2010 SNOPR to use ASTM C1363-05, ``Standard
Test Method for Thermal Performance of Building Materials and Envelope
Assemblies by Means of a Hot Box Apparatus,'' to measure the overall U-
factor of fully assembled panels to help account for the impact that
structural members have on the overall U-factor. 75 FR 55074.
Several interested parties--NEEA, AHRI, Master-Bilt, Thermo-Kool,
Carpenter, and Bally--supported the use of ASTM C1363-05 to measure the
overall panel U-factor. (NEEA, No. 0061.1 at p. 2; AHRI, No. 0070.1 at
p. 2; Master-Bilt, No. 0069.1 at p. 1; Thermo-Kool, No. 0072.1 at p. 1;
Carpenter, No. 0070.1 at p.2; Bally, No. 0078.1 at p. 2))
Other interested parties, however, disagreed with DOE's proposal to
use ASTM C1363-05 to measure panel performance. At least some of these
concerns were premised on a mistaken belief that DOE's proposal would
result in the elimination of structural members embedded into panels.
For example, a comment submitted jointly by the manufacturers
CrownTonka, ThermalRite, and ICS (collectively referred to as the Joint
Manufacturers) recommended that structural members be excluded from the
stated R-value requirements for overall envelope thermal resistance.
The Joint Manufacturers explained that many walk-ins require the use of
structural members to comply with building codes and to help support
loads placed on the building from factors such as snow and wind. The
Joint Manufacturers stated that ASTM C518-04 should be used to measure
the K-factor of foam, as specified in EPCA. (42 U.S.C. 6314
(a)(9)(A)(i)-(ii)) (Joint Manufacturers, No. 0062.1 at p. 1)
While American Panel agreed with DOE's general approach that the R-
value
[[Page 21587]]
of structural members should be considered in determining the overall
U-factor and submit data to demonstrate the impact of structural
members on the overall U-factor, it stated that the composite panel
must meet the minimum R-value requirement. American Panel continued to
state that the R-value should be calculated by using a weighted
percentage of foam R-value and structural R-value based on the
percentage each material represents in the panel. (American Panel, No.
0057.1 at p. 1; American Panel, No. 0057.1 at p. 2; American Panel, No.
0057.3 at p. 1) It asserted that ASTM C1363-05 is not the appropriate
test method for measuring the insulating values of foam, and added,
along with Craig Industries and Carpenter, that ASTM C518-04 should be
used to measure heat conduction through panels. (American Panel, No.
0057.1 at p. 2; Craig, No. 0068.1 at p. 2; Carpenter, No. 0067.1 at p.
2) Craig Industries was concerned that using ASTM C1363-05 to calculate
the heat conduction through structural members may not take the
reduction of joints (that is, panel to panel interfacing members) into
consideration. Craig Industries recommended that the structural members
should be tested with a procedure to represent the real R-value, which
would replace the R-value of the insulation where it is replaced with
structural members. (Craig, No. 0057.13 at p. 2) Carpenter further
asserted that ASTM C518-04 is simpler and less costly to perform than
C1363-05. (Carpenter, No. 0067.1 at p. 2) Thermo-Kool, on the other
hand, disagreed with the approach of using R-value testing of different
components of the composite panel to determine heat loss. (Thermo-Kool,
No. 0072.1 at p. 1) Bally, who agreed with DOE's proposed approach,
requested clarification specifically regarding how the two tested areas
would be used to represent the performance of a panel. (Bally, No.
0078.1 at p. 2)
None of the interested parties offered any further explanation for
their views other than those already described.
In this final rule, the terms ``foam'' and ``insulation'' are used
synonymously, but a panel is the fully manufactured product that
contains, but is not limited to, the insulating material, metal skin,
framing material, other structural members, or any combination thereof.
To address the Joint Manufacturers' concerns about the potential
elimination of structural members, DOE emphasizes that the overall U-
factor testing required by today's final rule will not prevent
manufacturers from including structural members in panels because the
existing standards in EPCA only regulate the R-value of the foam and do
not restrict the overall panel U-factor or the R-value of the
structural components. The R-value of insulation, which is 1/K-factor
as determined by ASTM C518-04, will still have to comply with the
existing EPCA requirements for insulation. (42 U.S.C. 6314
(a)(9)(A)(i)-(ii)) However, the overall U-factor of the fully assembled
panel, including structural members, may be used to meet an energy
conservation standard for panels, which will be determined in a
parallel rulemaking. Including ASTM C1363-05 will provide a more
accurate means to represent the overall heat transfer performance of
panels. DOE believes this procedure will be beneficial because it will
capture the effects of structural members that incorporate insulation
or otherwise contribute to the efficiency of the walk-in.
Additionally, while DOE acknowledges the concerns raised by
American Panel, the Joint Manufacturers, Craig Industries, and
Carpenter, the final rule includes ASTM C1363-05 as part of the test
procedure in order to determine the overall U-factor of the panel. DOE
is including this protocol as part of the test procedure because heat
conduction through structural members is a significant panel
characteristic that is not addressed under the statutorily-prescribed
testing requirements (i.e. ASTM C518-04). While ASTM C518-04 could be
used to individually measure the R-value of structural members, or any
other material, as Craig Industries suggested, DOE believes that this
approach would be more costly because of the many materials that could
comprise a panel and the need to test each material separately under
that approach. Furthermore, DOE believes that panel geometry could make
calculations to combine the R-value of each material into an overall
panel R-value complicated and burdensome.
DOE also acknowledges Craig Industries' concern that ASTM C1363-05
does not account for the reduction of joints (that is, panel to panel
interfacing members). Since DOE is adopting an approach to ensure the
energy efficiency performance of particular components, an approach
suggested by numerous commenters, and is no longer considering the
effects of infiltration, panel joint issues are outside of this
approach.
DOE notes that American Panel supported the inclusion of structural
members in calculating the overall U-factor. Furthermore, DOE would
like to clarify the calculation methodology to address the comment from
Bally. Today's final rule adopts a weighted percentage of the panel
edge (which may contain structural members) and panel core region
(which may also include structural members) in order to calculate the
panel's total U-factor. DOE believes that using the weighted percentage
of edge U-factor and core U-factor to calculate the total U-factor will
help reduce the manufacturer's testing burden.
In applying this weighted percentage approach, today's final rule
provides that for floor or non-floor panels of the same thickness,
construction methods, and materials, manufacturers must test a pair of
4 ft. by 8 ft. ``test panels'' to obtain a core U-factor and an edge U-
factor. The manufacturer must then calculate the overall U-factor of
other floor or non-floor panels with the same panel thickness,
construction methods, and materials using the U-factor results for the
core and edge region ``test panels.'' For example, a manufacturer tests
a 4 ft. by 8 ft. test panel and finds the edge region and core region
U-factors. The same manufacturer also produces 6 ft. by 8 ft. panels
that have identical core and edge region thickness, construction
methods and materials. Therefore, the manufacturer may apply the core
and edge region factors to the 6 ft. by 8 ft. panel to calculate the
overall U-factor of the 6 ft. by 8 ft. panel instead of performing an
additional test. DOE notes that any calculations that support the
certified ratings must be retained along with the test data for the
``test panels'' for all basic models pursuant to the requirements for
the maintenance of records promulgated in the CCE final rule. 76 FR
12494. DOE expects that, based on the information it has collected,
including information made available by manufacturers on their Web
sites and submitted comments, most manufacturers use the same panel
thickness, materials, and construction methods for many of their
panels, which results in a minimal testing burden.
In regard to American Panel's comment that the composite panel must
meet the minimum R-value requirement, DOE clarifies that EPCA states
that only the insulation material (that is, the foam) must meet the
prescribed R-value. (42 U.S.C. 6313(f)(1)(C)) The test procedure is
prescribing ASTM C1363-05 as a method of measuring the overall U-factor
of the entire panel. For EPCA compliance, the R-value of the insulation
must be separately determined in accordance with ASTM C518-04 as
specified in EPCA. (42 U.S.C. 6313(f)(1)(C))
[[Page 21588]]
Finally, interested parties suggested changes to the test
methodology DOE proposed. NRDC stated that irregular or non-homogeneous
foam products should be tested for actual R-value where there is no
quality control to maintain the orientation of the foam in the finished
product. To clarify, DOE believes that when NRDC noted the concern
about the orientation of the foam, they were referring to bun-stock
foam products. Bun-stock products are manufactured in ``buns'' that may
have foam cell structure similar to the grains in wood. Like wood,
depending on how the buns are cut into boards, the orientation of the
cell ``grains'' may vary by finished board. NRDC continued to suggest
that if a foam product cannot be tested, then the stated R-value should
be a conservative number representing the lowest R-value for a tested
material. (NRDC, No. 0064.1 at p. 4) NRDC also suggested that DOE
review the impact of testing the final fabricated panel rather than
requiring manufacturers to specially construct units for testing,
because specially constructed units may not represent the typical
product. (NRDC, No. 0064.1 at p. 4) Master-Bilt suggested changing the
width and length of the panel to 8 x 4 ft. +/- 1 ft. to have more
tolerance and allow for the testing of standard width panels. (Master-
Bilt, No. 0069.1 at p. 2)
In response to NRDC's comment about irregular or non-homogeneous
foam products, DOE anticipates that the prescribed sampling procedures
for certification will accurately capture the foam's R-value. A
sampling plan is intended to ensure accurate and statistically
repeatable results are achieved when using the test procedure. DOE
notes NRDC's concern that specifically constructed units may not
represent an actual product. However, in order to reduce the testing
burden presented by ASTM C1365-05, DOE is maintaining the approach of
specifying two test regions of a pair of representative panels. At one
test region, the tester measures the U-factor of the perimeter that may
contain structural members and panel-to-panel interface area (the
``Panel Edge''), while at the other region the tester measures the U-
factor of the core area of the panel (the ``Panel Core'') which may
also contain structural members. The U-factor for each region is then
applied to panels of the same type (that is, same foam type, framing
material, and panel thickness) to obtain an overall U-factor that is
representative of actual products sold by the panel manufacturer. DOE
applies a calculation methodology to extrapolate the core and edge U-
factor to determine the U-factor of any panel produced by a
manufacturer.
In response to Master-Bilt's comment, DOE agrees that increasing
the tolerance of the 8 ft x 4 ft test panel to +/- 1 ft will provide
manufacturers with a greater range of standard sized panels. DOE
conducted a mathematical analysis to determine how changing the
tolerance would affect the U-factor as determined by ASTM C1363-05. DOE
found that increasing the size tolerance of the test panel results in
less than a 0.5 percent change to the U-factor as determined by ASTM
C1363-05. Therefore, DOE has amended the standard size of a test panel
for ASTM C1363-05 to be 8 ft x 4 ft +/- 1 ft.
b. Long-Term Thermal Resistance
In the January 2010 NOPR and September 2010 SNOPR, DOE cited
several studies that conclude that lateral gas diffusion, which causes
a reduction in R-value, occurs in impermeably faced foams. See 75 FR
192-194 and 75 FR 55075-55079. These types of foams are common to walk-
ins. The lateral gas diffusion occurs over time and affects the energy
efficiency performance of the foam as diffusion continues. To account
for this aging effect on a foam's insulation performance--and, by
extension, the energy consumption of a walk-in due to thermal losses
attributable to this reduced performance--DOE, consistent with its
proposed approach, is adopting a method to account for this phenomenon
in walk-in applications. Hill Phoenix added that different methods of
manufacturing panels should be taken into account when determining the
test procedure. (Hill Phoenix, No. 0063.1 at p. 2)
The most significant factor affecting the efficiency of a walk-in
panel is the insulating foam in a panel, and accurately capturing the
foam's R-value is critical to measuring the overall performance of the
panel. Panels can be in use for 10 to 20 or more years before they are
replaced. Performance metrics for a panel based