Exelon Generation Company, LLC, Peach Bottom Atomic Power Station, Unit Nos. 2 and 3; Exemption, 19476-19488 [2011-8317]
Download as PDF
19476
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
Use of the Information: For NSF Form
192, information will be used in order
to verify eligibility and qualifications for
the award. For NSF Form 250,
information will be used to verify
attendance at Advanced Study Institute
and will be included in Division
reports.
Estimate of Burden: Form 192—1.5
hours; Form 250—2 hours
Respondents: Individuals.
Estimated Number of Responses per
Award: 150 responses, broken down as
follows: For NSF Form 250, 75
respondents; for NSF Form 192, 75
respondents.
Estimated Total Annual Burden on
Respondents: 262.5 hours, broken down
by 150 hours for NSF Form 250 (2 hours
per 75 respondents); and 112.5 hours for
NSF Form 192 (1.5 hours per 75
respondents).
Frequency of Responses: Annually.
Comments: Comments are invited on
(a) whether the proposed collection of
information is necessary for the proper
performance of the functions of the
Agency, including whether the
information shall have practical utility;
(b) the accuracy of the Agency’s
estimate of the burden of the proposed
collection of information; (c) ways to
enhance the quality, utility, and clarity
of the information on respondents,
including through the use of automated
collection techniques or other forms of
information technology; or (d) ways to
minimize the burden of the collection of
information on those who are to
respond, including through the use of
appropriate automated, electronic,
mechanical, or other technological
collection techniques or other forms of
information technology.
Dated: April 4, 2011.
Suzanne H. Plimpton,
Reports Clearance Officer, National Science
Foundation.
[FR Doc. 2011–8277 Filed 4–6–11; 8:45 am]
BILLING CODE 7555–01–P
NUCLEAR REGULATORY
COMMISSION
[Docket Nos. 50–277 and 50–278; NRC–
2010–0303]
mstockstill on DSKH9S0YB1PROD with NOTICES
Exelon Generation Company, LLC,
Peach Bottom Atomic Power Station,
Unit Nos. 2 and 3; Exemption
1.0 Background
Exelon Generation Company, LLC (the
licensee, Exelon) is the holder of
Renewed Facility Operating License
Nos. DPR–44 and DPR–56, which
authorizes operation of the Peach
Bottom Atomic Power Station (PBAPS),
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
Units 2 and 3. The license provides,
among other things, that the facility is
subject to all rules, regulations, and
orders of the Nuclear Regulatory
Commission (NRC, the Commission)
now or hereafter in effect.
The facility consists of two boilingwater reactors located partly in Peach
Bottom Township, York County, partly
in Drumore Township, Lancaster
County, and partly in Fulton Township,
Lancaster County, in southeastern
Pennsylvania.
2.0 Request/Action
Title 10 of the Code of Federal
Regulations (10 CFR), Part 50, Section
50.48(b), requires that nuclear power
plants that were licensed before January
1, 1979, satisfy the requirements of 10
CFR Part 50, Appendix R, ‘‘Fire
Protection Program for Nuclear Power
Facilities Operating Prior to January 1,
1979,’’ Section III.G, ‘‘Fire protection of
safe shutdown capability.’’ PBAPS,
Units 2 and 3 were licensed to operate
prior to January 1, 1979. As such, the
licensee’s Fire Protection Program (FPP)
must provide the established level of
protection as intended by Section III.G
of 10 CFR Part 50, Appendix R.
By letter dated March 6, 2009,
‘‘Request for Exemption from 10 CFR 50,
Appendix R, Section III.G, ‘Fire
Protection of Safe Shutdown
Capability’ ’’ available at Agencywide
Documents Access and Management
System (ADAMS), Accession No.
ML090680141, and supplemented by
letter dated February 12, 2010,
‘‘Response to Request for Additional
Information Request for Exemption from
10 CFR 50, Appendix R, Section III.G,
‘Fire Protection of Safe Shutdown
Capability’ ’’ (ADAMS Accession No.
ML100470774), the licensee requested
an exemption for PBAPS, Units 2 and 3,
from certain technical requirements of
10 CFR Part 50, Appendix R, Section
III.G.2 (III.G.2) for the use of operator
manual actions (OMAs) in lieu of
meeting the circuit separation and
protection requirements contained in
III.G.2 for Fire Areas 2, 6N, 6S, 13N, 26,
30, 36, 37, 43, 50, and 58 at the plant.
3.0 Discussion
Pursuant to 10 CFR 50.12, the
Commission may, upon application by
any interested person or upon its own
initiative, grant exemptions from the
requirements of 10 CFR Part 50 when:
(1) The exemptions are authorized by
law, will not present an undue risk to
public health or safety, and are
consistent with the common defense
and security; and (2) when special
circumstances are present. The licensee
has stated that special circumstances are
PO 00000
Frm 00170
Fmt 4703
Sfmt 4703
present in that the application of the
regulation in this particular
circumstance is not necessary to achieve
the underlying purpose of the rule,
which is consistent with the language
included in 10 CFR 50.12(a)(2)(ii).
In letters dated March 6, 2009, and
February 12, 2010, the licensee
discussed financial implications
associated with plant modifications that
may be necessary to comply with the
regulation. 10 CFR 50.12(a)2(iii) states
that if such costs have been shown to be
significantly in excess of those
contemplated at the time the regulation
was adopted, or are significantly in
excess of those incurred by others
similarly situated, this may be
considered a basis for considering an
exemption request. However, financial
implications were not considered in the
regulatory review of the request since no
substantiation was provided regarding
such financial implications. Even
though no financial substantiation was
provided, the licensee did submit
sufficient regulatory basis to support a
technical review of the exemption
request in that the application of the
regulation in this particular
circumstance is not necessary to achieve
the underlying purpose of the rule.
In accordance with 10 CFR 50.48(b),
nuclear power plants licensed before
January 1, 1979, are required to meet
Section III.G, of 10 CFR Part 50,
Appendix R. The underlying purpose of
Section III.G of 10 CFR Part 50,
Appendix R, is to ensure that the ability
to achieve and maintain safe shutdown
is preserved following a fire event. The
regulation intends for licensees to
accomplish this by extending the
concept of defense-in-depth to:
(1) Prevent fires from starting;
(2) Rapidly detect, control, and
extinguish promptly those fires that do
occur;
(3) Provide protection for structures,
systems, and components important to
safety, so that a fire that is not promptly
extinguished by the fire suppression
activities will not prevent the safe
shutdown of the plant.
The stated purpose of 10 CFR Part 50,
Appendix R, Section III.G.2 (III.G.2) is to
ensure that one of the redundant trains
necessary to achieve and maintain hot
shutdown conditions remains free of
fire damage in the event of a fire. III.G.2
requires one of the following means to
ensure that a redundant train of safe
shutdown cables and equipment is free
of fire damage, where redundant trains
are located in the same fire area outside
of primary containment:
a. Separation of cables and equipment
by a fire barrier having a 3-hour rating;
E:\FR\FM\07APN1.SGM
07APN1
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
mstockstill on DSKH9S0YB1PROD with NOTICES
b. Separation of cables and equipment
by a horizontal distance of more than 20
feet with no intervening combustibles or
fire hazards and with fire detectors and
an automatic fire suppression system
installed in the fire area; or
c. Enclosure of cables and equipment
of one redundant train in a fire barrier
having a 1-hour rating and with fire
detectors and an automatic fire
suppression system installed in the fire
area.
Exelon has requested an exemption
from the requirements of III.G.2 for
PBAPS, Units 2 and 3 to the extent that
one of the redundant trains of systems
necessary to achieve and maintain hot
shutdown is not maintained free of fire
damage in accordance with one of the
required means, for a fire occurring in
Fire Areas 2 (Radwaste Building), 6S
(Unit 2 Reactor Building), 6N (Unit 2
Reactor Building, North side), 13N (Unit
3 Reactor Building), 26 (Unit 3 MotorGenerator (MG) Set Ventilation
Equipment Room), 30 (Unit 3 B/D
Battery Room), 36 (E42 Switchgear
Room), 37 (E22 Switchgear Room), 43
(E–4 Emergency Diesel Generator
Room), 50 (Turbine Building), and 58
(Unit 3 MG Set Room).
In its submittals, the licensee
described elements of the FPP that
provide justification that the concept of
defense-in-depth that is in place in the
above fire areas is consistent with that
intended by the regulation. To
accomplish this, the licensee utilizes
various protective measures.
Specifically, the licensee stated that the
purpose of its request was to credit the
use of OMAs, in conjunction with other
defense-in-depth features, in lieu of the
separation and protective measures
required by III.G.2 for a fire in the fire
areas stated above.
3.1 Fire Prevention
In its March 6, 2009, and February 12,
2010, letters, the licensee provided an
analysis that described how fire
prevention is addressed for each of the
fire areas for which the OMAs may be
required. Unless noted otherwise in
Section 3.4 below, all of the fire areas
included in this exemption have a
combustible fuel load that is considered
to be low with fuel sources consisting
primarily of fire retardant cable
insulation and limited floor-based
combustibles. Unless noted otherwise,
there are no high energy ignition
sources located in the areas. The fire
areas included in the exemption are not
shop areas, so hot work activities are
infrequent with administrative control
programs (e.g., hot work permits, fire
watch, and supervisory controls). The
administrative control programs are
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
described in the PBAPS FPP, which is
incorporated into the Updated Final
Safety Analysis Report.
3.2 Detection, Control and
Extinguishment
PBAPS has been divided into fire
areas, as described in the PBAPS FPP.
Three-hour fire barriers are normally
used to provide fire resistive separation
between adjacent fire areas. In some
cases, barriers with a fire resistance
rating of less than 3 hours are credited,
but exemptions have been approved or
engineering evaluations performed in
accordance with Generic Letter 86–10,
‘‘Implementation of Fire Protection
Requirements,’’ to demonstrate that the
barriers are sufficient for the hazard.
Walls separating rooms and zones
within fire areas are typically
constructed of concrete. In addition to
these boundaries, the licensee provided
a hazard analysis that described how
detection, control, and extinguishment
of fire are addressed for each of the fire
areas for which the OMAs may be
required.
Unless noted otherwise below, fire
areas are provided with ionization
smoke detectors in various locations
within a particular fire area. Although
not installed in accordance with a
recognized standard with regard to
spacing, the detectors are located near
equipment such that they are likely to
adequately detect a fire. Upon detecting
smoke, the detectors initiate an alarm in
the Control Room enabling fire brigade
response. The licensee stated that in
most cases, no automatic fire
suppression systems are provided in the
areas included in this exemption but
that fire suppression systems are
installed in plant areas with significant
fire hazards, such as lube oil.
Suppression systems have also been
installed in areas with 1-hour barrier
walls and 1-hour rated electrical
raceway encapsulation.
The automatic suppression systems
are not credited in reducing fire
exposure to redundant equipment
unless they are indicated as being fullarea or specifically described as being
effective for redundant equipment.
Equipment operators are trained fire
brigade members and would likely
identify and manually suppress or
extinguish a fire using the portable fire
extinguishers and manual hose stations
located throughout the fire areas.
3.3 Preservation of Safe Shutdown
Capability
Each OMA included in this review
consists of a sequence of tasks that
occur in various fire areas. The OMAs
are initiated upon confirmation of a fire
PO 00000
Frm 00171
Fmt 4703
Sfmt 4703
19477
in a particular fire area. The licensee
stated that the postulated fire events
that may require the use of the OMAs
would include multiple failures of
various components or equipment. In
most cases, it is considered highly
unlikely that the sequence of events
required to necessitate the OMAs would
fully evolve because of the fire
prevention, fire protection, and physical
separation features in place. However,
in the event that the sequence does
evolve, the OMAs are available to
provide assurance that safe shutdown
can be achieved.
This analysis postulates that OMAs
may be needed to assure safe shutdown
capability in addition to the traditional
fire protection features described above.
For each of the fire areas included in
this exemption, the licensee evaluated
the OMAs against the criteria of
NUREG–1852, ‘‘Demonstrating the
Feasibility and Reliability of Operator
Manual Actions in Response to Fire,’’
October 2007, in the March 6, 2009,
submittal. A Fire Hazards Analysis was
provided for each of the OMAs in the
licensee’s February 12, 2010,
supplement.
3.3.1 Licensee’s Bases for Establishing
Feasibility and Reliability
The licensee’s analysis addresses
factors such as environmental concerns,
equipment functionality and
accessibility, available indications,
communications, portable equipment,
personnel protection equipment,
procedures and training, staffing and
demonstrations.
In its March 6, 2009, submittal, and
further supported by its February 12,
2010, supplement, the licensee stated
that environmental considerations such
as radiological concerns, emergency
lighting, temperature and humidity
conditions and smoke and toxic gases
were evaluated and found to not
represent a negative impact on the
operators’ abilities to complete the
OMA. The licensee stated that the dose
limits contained in 10 CFR Part 20 are
never challenged at any point along the
travel path of any of the OMAs included
in this exemption.
The licensee confirmed that each of
the OMA locations addressed by this
exemption is provided with emergency
lighting that illuminates both the
location where the manual action is
performed and the access route to the
manual action location. Where travel is
required to buildings outside of the
power block, portable lights are staged
in the fire safe shutdown equipment
locker which is inventoried and
maintained by performance of a
periodic routine test. The emergency
E:\FR\FM\07APN1.SGM
07APN1
mstockstill on DSKH9S0YB1PROD with NOTICES
19478
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
lights are periodically checked for
operation and aim at the target location.
The licensee also confirmed that
temperature and humidity conditions
will not challenge the operators
performing the OMAs. Additionally, the
licensee indicated that heat and smoke
or gas generation from a fire will not
impact the operator performing the
OMAs. This is further supported by the
fact that the locations of the postulated
fire events are in different fire areas than
the locations for where the actions are
performed. In most cases, the initiating
fire area and manual action location fire
area are in separate buildings and have
separate ventilation systems. Other than
smoke, CO2 is another toxic gas that
could present a hazard. However, all of
the CO2 fire suppression systems at
PBAPS are manually actuated to prevent
an inadvertent discharge of a system.
The licensee stated that the
equipment to be operated as part of the
OMAs will be functional and
maintained free of fire damage and will
be accessible to the operators
performing the action. Additionally,
PBAPS maintains Transient Response
Implementing Plan procedures and T–
300 Fire Guides. T–300 Fire Guides
provide the operators with specific
instructions in the event of a fire in a
specific fire area. The T–300 Fire Guides
provide a list of the key protected
instruments available for a fire in the
fire area and list any ‘‘prompt’’ actions
that are needed to restore an instrument
for a fire in that area (i.e., those that
need to be performed within 30
minutes). The applicable T–300 Fire
Guide lists the ‘‘prompt’’ actions at the
front of the document. In addition, the
licensee stated that where specific
indications may be lost due to a
postulated event, the applicable T–300
Fire Guide for that fire area identifies
which indications may be lost and how
to recover the loss of that indication.
Most required shutdown parameter
indications are provided by multiple
instruments; therefore, even with the
loss of certain instruments or power
supplies, redundant instruments are
available to provide indications to assist
operators.
With regard to communications, the
licensee stated that PBAPS has radios
and phones available as part of the
normal communications between the
Control Room and the operators.
Although the communication system is
not specifically hardened for post-fire
survivability, the radio and phone
systems are robustly designed such that
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
they will be available following most
fire scenarios. In the event that the radio
and phone systems are inoperable, faceto-face communication, and adequate
time, is available to dispatch the safe
shutdown operators from the Control
Room to perform the tasks and return to
the Control Room for reassignment
when the task is complete. With the
exception of Action H, none of the
operator manual actions addressed by
this exemption require immediate or
concurrent coordination with the
Control Room while performing the
task.
The licensee stated that if any keys,
tools or equipment are required to
perform the OMAs, the T–300 Fire
Guides provide instructions on where to
find them and how to use them. In
addition, the licensee stated that
operators are provided with standard
personal protective equipment (PPE)
(i.e., hardhat, safety glasses, hearing
protection, gloves, etc.) and that
additional PPE is not required for any of
the OMAs, with the exception of actions
that require that an electrical enclosure
be opened to manipulate an insulated
handle of a manual transfer switch. For
these tasks, a PBAPS corporate safety
procedure requires the use of additional
electrical safety PPE when performing
this task.
The licensee stated that the T–300
Fire Guides provide in-depth safe
shutdown direction for fires in specific
fire areas and that the procedures
included in the guides include specific
instructions on assessing plant
indications and events as well as
instructions on how to perform each of
the OMAs. The procedures are then
used to train the operators on the
OMAs, which consist primarily of
activities that are considered to be
similar to those performed as part of
typical work activity and are considered
straightforward with minimal training
demands. In addition, the licensee
stated that licensed operators are trained
biennially on the use of the T–300 Fire
Guides using simulator scenarios that
start with a fire in a specific fire area.
With regard to staffing, the licensee
stated that PBAPS maintains a
minimum of three operators on each
shift to perform safe shutdown duties in
the event of a fire, which may be
comprised of equipment operators,
reactor operators or senior reactor
operators. Additionally, the licensee
stated that PBAPS performed several
demonstrations using what is
considered to be the most challenging
PO 00000
Frm 00172
Fmt 4703
Sfmt 4703
initiating fire area, the Turbine Building
(Fire Area 50), because it encompasses
both Unit 2 and Unit 3, includes an
action that is a prompt action in other
fire areas, and includes a number of
OMAs to perform within the first 60
minutes.
3.3.2 NRC Staff Evaluation of
Feasibility
The NRC staff has determined that the
licensee’s analysis demonstrates that,
for the expected scenarios, the OMAs
can be diagnosed and executed within
the amount of time necessary to
complete them. The licensee’s analysis
also demonstrates that various factors,
as discussed above, have been
considered to address uncertainties in
estimating the time available. Therefore,
the NRC staff finds that the OMAs
included in this review are feasible
because there is adequate time available
for the operator to perform the required
OMAs to achieve and maintain hot
shutdown following a postulated fire
event. The following table summarizes
the ‘‘required’’ verses ‘‘allowable’’ times
for each OMA. Where a diagnosis time
has been identified, it is included as
part of the required time for a particular
action. Where an action has multiple
times or contingencies associated with
the ‘‘allowable’’ completion time, the
lesser time is used. This approach is
considered to represent a conservative
approach to analyzing the timelines
associated with each of the OMAs with
regard to the feasibility and reliability of
the actions included in this exemption.
In some cases, the margin between the
required time and allowable time is
small. Specifically actions D, U, V, and
X, have 20 percent or less margin. This
limited margin is based on using the
most limiting information from the
licensee. For example, if the licensee
postulated up to 30 minutes for
diagnosis, the higher value of the
required time range noted in the table
below includes the time to complete the
action plus the full 30 minutes.
Finally, these numbers should not be
considered without the understanding
that the manual actions are a fall back
in the unlikely event that the fire
protection defense-in-depth features are
insufficient. In most cases, there is no
credible fire scenario that would
necessitate the performance of these
OMAs. The licensee provided a
discussion of the times and
circumstances associated with each of
the actions in its March 6, 2009, and
February 12, 2010, correspondence.
E:\FR\FM\07APN1.SGM
07APN1
19479
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
Fire area of fire origin
Fire Area 2 (Radwaste Building) .....................................................................
Fire
Fire
Fire
Fire
Fire
Fire
Fire
Fire
Fire
Area
Area
Area
Area
Area
Area
Area
Area
Area
Required
time (min)
OMA
6S (Unit 2 Reactor Building) ...........................................................
6N (Unit 2 Reactor Building, North Side) .......................................
13N (Unit 3 Reactor Building) .........................................................
26 (Unit 3 MG Set Ventilation Equipment Room) ..........................
30 (Unit 3 B/D Battery Room) ........................................................
36 (E42 Switchgear Room) ............................................................
37 (E22 Switchgear Room) ............................................................
43 (E–4 Emergency Diesel Generator Room) ...............................
50 (Turbine Building) ......................................................................
Fire Area 58 (Unit 3 MG Set Room) ...............................................................
Action
Action
Action
Action
Action
Action
Action
Action
Action
Action
Action
Action
Action
Action
Action
Action
Action
B ..............................................
C .............................................
D .............................................
G .............................................
H .............................................
J ..............................................
K ..............................................
M .............................................
R .............................................
S ..............................................
T ..............................................
U .............................................
V ..............................................
X ..............................................
Y ..............................................
BB ...........................................
CC ...........................................
15—45*
15
18—48*
14—44*
7
12—42*
12—42*
9—39*
12—42*
12—42*
9—39*
26—56*
26—56*
24—54*
15—45*
12—42*
12
Allowable
time (min)
120
25 **
60
60
25 **
60
60
60
60
60
60
60
60
60
120
60
25**
* The higher value of the required time range accounts for a generic 30-minute diagnosis time to assess the need for OMAs.
** Prompt actions are those having allowable completion times of 30 minutes or less.
Detection, Control, and Extinguishment
3.3.3 NRC Staff Evaluation of
Reliability
The completion times noted in the
table above provide reasonable
assurance that the OMAs can reliably be
performed under a wide range of
conceivable conditions by different
plant crews. This is because the
completion time, in conjunction with
the time margins associated with each
action and other installed fire protection
features, account for sources of
uncertainty such as variations in fire
and plant conditions, factors unable to
be recreated in demonstrations and
human-centered factors. Therefore, the
NRC staff finds that the OMAs included
in this review are reliable because there
is adequate time available to account for
uncertainties not only in estimates of
the time available, but also in estimates
of how long it takes to diagnose a fire
and execute the OMAs (i.e., as based, at
least in part, on a plant demonstration
of the actions under non-fire
conditions).
For each of the fire areas included in
this exemption, the postulated fire
scenarios and pertinent details are
summarized in Section 3.4 below.
3.4
3.4.1
NRC Staff Fire Area Evaluations
Fire Area 2 (Radwaste Building)
mstockstill on DSKH9S0YB1PROD with NOTICES
Fire Prevention
The licensee stated that the floorbased combustibles include health
physics cleaning supplies, such as
mops, vacuums and other Class A
combustibles as well as several steel
carts containing new resins in paper or
plastic bags. The total weight of the
plastic bags is estimated to be less than
5 pounds and empty resin bags are
immediately removed.
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
OMAs Credited for a Fire in This Area
The licensee stated that Fire Area 2
has fire suppression systems installed
within the fire area but not within the
rooms containing redundant cables. The
licensee has further stated that the
detection systems in the rooms
containing redundant cables are not
code compliant in terms of overall
spacing in the fire area. However, a
smoke detector is located within 5 feet
of redundant cable ZA2B1021A. There
is also a smoke detector located within
15 feet of both cables ZD3A1806A and
ZD3A1321A. The licensee also stated
that the Radwaste Control Room is
located directly adjacent to these three
rooms and that it is normally occupied
by an equipment operator. Because of
this, it is likely that any fire would be
quickly identified by an operator in the
area. Additionally, the licensee stated
that a fully trained onsite fire brigade is
provided, which is dispatched via plant
page in the event of a fire. The fire
brigade is composed of plant operators
that are separate from operators
assigned safe shutdown duties and are
instructed to provide information about
a fire event over the operations radio to
assist in mitigating the event. Fire Area
2 is provided with manual fire fighting
equipment such as portable fire
extinguishers and manual hose stations
throughout the area.
Action B
The licensee stated that the redundant
cables located in Fire Area 2 (cables
ZA2B1021A and ZD3B1321A or
ZD3A1806A) are located a minimum of
approximately 30 feet from each other
and that no intervening combustibles
are present between the two trains of
cables. This physical separation with
the available fire detection system will
provide the site fire brigade an
opportunity to extinguish the fire before
redundant trains are damaged. The
licensee also stated that the cables are
located a minimum of approximately 9
feet above the floor and that they are
enclosed in rigid conduit, such that
transient fire exposures and self-ignited
cable fires are unlikely to affect the
circuits.
In the unlikely event that both trains
of cable are lost due to a fire in Fire Area
2, an OMA (Action B) is available to
restore or maintain the necessary
function to the effected equipment (SU–
25 Breaker). Action B directs an
operator to transfer SU–25 breaker
auxiliary equipment from the normal
power source to its alternate power
source, by operating manual transfer
switch 00S306, which is located in the
Unit 2 Startup Building. The Unit 2
Startup Building is located in the
exterior yard area.
Preservation of Safe Shutdown
Capability
The licensee stated that Fire Area 2 is
a large fire area containing a number of
rooms on several elevations and that
spatial separation of redundant cables is
provided as discussed below.
PO 00000
Frm 00173
Fmt 4703
Sfmt 4703
Action C
The potential need to perform this
action is low since this action is only
needed if two of three offsite power
sources are unavailable, power to the
2SU transformer tap changer is lost, and
the tap changer is in the wrong position.
The licensee stated that offsite power is
provided to each of the 4kV Class 1E
switchgear by two of three redundant
E:\FR\FM\07APN1.SGM
07APN1
mstockstill on DSKH9S0YB1PROD with NOTICES
19480
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
sources (2SU, 3SU, and 343SU) and that
control cables for the sources have been
physically separated by rerouting
selected cables, such that one of the
redundant sources remains free of fire
damage for fires in most plant areas. In
particular, the licensee stated that cables
associated with the 2SU source have
been relocated out of the Turbine
Building (Fire Area 50), and portions of
the Radwaste Building (Fire Areas 2 and
58).
The licensee stated that balance of
plant (BOP) cables are routed through
Fire Area 2, but that the routing of the
cables was not part of the analysis. In
the licensee’s February 12, 2010,
supplement, the licensee described the
circumstances that would determine the
availability of the safe shutdown
equipment located in this area; namely
the 2SU power source, which includes
a transformer tap changer that is
powered by BOP power. Since the BOP
cable routing was not part of the
analysis, the loss of BOP power was
assumed for a fire in these three fire
areas. The licensee’s analysis also
assumed that the transformer tap
changer, which is powered by the BOP
and responsible for maintaining power
to the 4kV Bus, was not in the correct
position. When the tap changer is not in
the correct position, the voltage could
vary resulting in actuation of the 4kV
trip relays.
In the unlikely event that all of the
conditions discussed above exist and
fire damage occurs to the redundant
cables, Action C can be utilized, which
directs operators to pull the fuse blocks
for the degraded voltage trip relays to
ensure that the 4kV busses remain
available. Action C is a ‘‘prompt’’ action,
with an allowable completion time of 30
minutes or less, however, the licensee
stated that its analysis assumed that the
redundant cables were lost regardless of
their location and that the tap changer
was not in the correct position. The
licensee stated that the loss of certain
equipment in a fire area due to a fire
will result in a Control Room alert. Off
Normal procedure ON–114, ‘‘Actual Fire
Reported in the Power Block, Diesel
Generator Building, Emergency Pump,
Inner Screen or Emergency Cooling
Tower Structures,’’ is immediately
entered upon confirmation of a fire
condition. Procedure ON–114 directs
immediate entry into the Fire Guide for
the affected fire area. The licensee also
stated that a note is provided in the
applicable safe shutdown fire guide
series (T–300 Fire Guides) providing
guidance on how to determine whether
the 2SU transformer tap changer has lost
power using indications within the
Control Room. Therefore, the Control
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
Room will know immediately if this
action is required and a generic
diagnosis time is not necessary.
The licensee’s T–300 Fire Guides also
provide the following guidance to assist
operators in evaluating a postulated
event, ‘‘If 2SU is the only offsite power
source available, and a loss of power to
the 2SU Transformer Tap Change has
occurred, then perform the manual
action to remove the fuses.’’
Additionally, the 2SU transformer and
associated auxiliaries are located in the
yard area and would not be exposed by
a fire in Fire Area 2. Lastly, the location
of the OMA to remove the fuses in the
4kV Switchgear Rooms is in a separate
fire area, with ventilation systems that
are separate from Fire Area 2.
Action D
The licensee stated that this action
would only be required if the conduit
containing cable, which is located above
the suspended ceiling with the only
exposing combustible being a tray with
fire retardant cables, is damaged by fire.
There is a lack of ignition sources and
a relatively short length (approximately
6 feet) of cable that passes through Fire
Area 2. In addition, there is a smoke
detector located within 5 feet of the
conduit containing the cable, which
would result in rapid plant notification
of an exposure fire.
In the unlikely event that a fire in Fire
Area 2 damages cable ZA2B1014A,
normal power to the 2AD003 battery
charger could be lost, which is needed
to maintain long term DC power through
the station batteries. A loss of
ZA2B1014A would necessitate a manual
action to transfer battery charger
2AD003 to an alternate power source
within 60 minutes since the batteries
can operate for 60 minutes prior to the
initiation of recharging. The alternate
power source is routed in separate fire
areas, so a single fire cannot damage
both the normal and alternate power
feed. Action D is available to transfer
the alternate power supply to the battery
charger 2AD003. The action entails
closing a breaker located in the E13 4kV
Switchgear Room (Fire Area 33) and
then operating a manual transfer switch
located in the E32 4kV Switchgear
Room (Fire Area 38), both of which are
separate fire areas from Fire Area 2.
NRC Staff Evaluation
Given the limited amount of
combustible materials and ignition
sources, it is unlikely that a fire would
occur and go undetected by the smoke
detection system noted above or
unsuppressed by personnel, and damage
the safe shutdown equipment. Even if
such circumstances exist, Actions B, C,
PO 00000
Frm 00174
Fmt 4703
Sfmt 4703
and D are available to provide
additional assurance that safe shutdown
capability is maintained.
3.4.2 Fire Area 6S (Unit 2 Reactor
Building)
Fire Prevention
The licensee stated that conduits are
routed primarily through a transient
combustible-free zone where a permit
and review are required prior to the
placement of combustibles in this area.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 6S
has ionization smoke detectors installed
in the overhead area but that these
smoke detectors do not have code
compliant spacing due to ceiling height
and beam pockets. However, there are
three smoke detectors located above the
general routing of the redundant cable
conduits, which would be expected to
activate in the event of a fire occurring
in close proximity to the redundant
cables. Additionally, the licensee stated
that a fully trained onsite fire brigade is
provided, which is dispatched via plant
page in the event of a fire. The fire
brigade is composed of plant operators
that are separate from operators
assigned safe shutdown duties and are
instructed to provide information about
a fire event over the operations radio to
assist in mitigating the event.
Preservation of Safe Shutdown
Capability
The licensee stated that Room 403 in
Fire Area 6S has a ceiling height of
approximately 29’ and an approximate
floor area of 6,848 square feet, so it is
unlikely that smoke and heat would
accumulate at the height of the safe
shutdown equipment and cause a
failure due to fire damage.
OMAs Credited for a Fire in This Area
Action G
The licensee stated that recent plant
experience with faults and malfunctions
in similar load centers has been that
even when energetic failures have
occurred, its damage has been contained
within the breaker cubicle, with some
heat and smoke damage to immediately
adjacent cubicles. Therefore, it is
considered unlikely that the cables
routed above the load centers would be
affected by a fault within the load
centers since there is not a credible fire
scenario that would be capable of
damaging the cables within the
conduits.
A fire in Fire Area 6S has the
potential to damage cables ZA2B1014A,
ZA2A1505A, and ZA2B1021A. The
licensee stated that there are three 480V
E:\FR\FM\07APN1.SGM
07APN1
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
load centers in the room containing the
redundant cables and that the cables are
routed to one of the load centers. As a
result, each cable is routed over a 480V
load center and in two cases the conduit
passes over two load centers prior to
entering the third load center. The
conduits are located above the two
adjacent load centers, which consist of
a 4kv to 480v sealed gas cooled stepdown transformer and a 480v
switchgear.
The loss of these cables could result
in a loss of the normal power supply to
the 2AD003 battery charger, which is
needed to maintain long term DC power
through the station batteries. A loss of
ZA2B1014A, ZA2A1505A, and
ZA2B1021A would necessitate a manual
action to transfer battery charger
2AD003 to an alternate power source
within 60 minutes since the batteries
can operate for 60 minutes prior to the
initiation of recharging. The alternate
power source is routed in separate fire
areas, so a single fire cannot damage
both the normal and alternate power
feed. Action G is available to transfer
the alternate power supply to the battery
charger 2AD003. The action entails
closing a breaker located in the E13 4kV
Switchgear Room (Fire Area 33) and
then operating a manual transfer switch
located in the E32 4kV Switchgear
Room (Fire Area 38), both of which are
separate fire areas from Fire Area 6S.
NRC Staff Evaluation
Given the limited amount of
combustible materials, ignition sources,
and the large volume of the space, it is
unlikely that a fire would occur and go
undetected by the smoke detection
system noted above or unsuppressed by
personnel, and damage the safe
shutdown equipment. Even if such
circumstances exist, Action G is
available to provide additional
assurance that safe shutdown capability
is maintained.
3.4.3 Fire Area 6N (Unit 2 Reactor
Building, North side)
mstockstill on DSKH9S0YB1PROD with NOTICES
Fire Prevention
The licensee stated that the only floorbased combustibles in this area are trash
cans and cables. Trash can lids are
designed to provide self-extinguishing
capability to the trash cans. Cables in
the area are qualified to the Institute of
Electrical and Electronics Engineers,
Inc. Standard-383, ‘‘IEEE Standard For
Qualifying Class 1E Electrical Cables
And Field Splices for Nuclear Power
Generating Stations’’ (IEEE 383), or
equivalent.
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
Detection, Control, and Extinguishment
The licensee stated that Fire Area 6N
has a smoke detection system installed,
but that the spacing is not in
compliance with National Fire
Protection Association Code 72,
‘‘National Fire Alarm and Signaling
Code’’ (NFPA 72), due to deep beam
pockets at the ceiling of this area.
However, there is a smoke detector
within the vicinity (approximately 25
feet) of each of the cases where cable
ZA2Q1280B and a ‘‘B’’ residual heat
removal (RHR) cable intersect, which
would be expected to activate in the
event of a fire in close proximity to the
redundant equipment. There is also an
automatic water curtain on the west side
of the Unit 2 Reactor Building that
separates Fire Area 6N from Fire Area
6S, thus reducing any anticipated
exposure from Fire Area 6S.
Additionally, the licensee stated that a
fully trained onsite fire brigade is
provided, which is dispatched via plant
page in the event of a fire. The fire
brigade is composed of plant operators
that are separate from operators
assigned safe shutdown duties and are
instructed to provide information about
a fire event over the operations radio to
assist in mitigating the event.
Preservation of Safe Shutdown
Capability
The licensee stated that Fire Area 6N
is the Unit 2 Reactor Building 135’
elevation, north side, which is in a
separate building from the Cable
Spreading Room, Fire Area 25, which is
the location of the OMA.
OMAs Credited for a Fire in This Area
Action H
The licensee stated that the cables
associated with ‘‘B’’ RHR are located in
trays and in conduit and that cables for
both ‘‘A’’ and ‘‘B’’ RHR trains cross
within 2 feet of each other. However,
there are no high energy ignition
sources where cable ZA2Q1280B and a
‘‘B’’ RHR train cable cross and only a
small amount of combustibles in the
area overall. Therefore, it is unlikely
that a single fire could damage both the
‘‘A’’ train RHR cable and ‘‘B’’ RHR cables
and necessitate the use of Action H.
Action H, which requires coordination
with the control room, directs an
operator to insert a plug-in test switch
into Panel 20C032, located in the Cable
Spreading Room (Fire Area 25), to
bypass the reactor low pressure
permissive for opening MO–2–025A.
In the unlikely event that a fire does
damage the pressure permissive
instrumentation circuit for opening
MO–2–025A, operators will be aware of
PO 00000
Frm 00175
Fmt 4703
Sfmt 4703
19481
the condition, either by electronic
indications in the Control Room, a
smoke detection alarm annunciation in
the Control Room, or physical
observation by operators, and will
initiate Action H, which is the only
OMA required to achieve hot shutdown
for a fire in Fire Area 6N. Therefore, the
Control Room will know immediately if
this action is required and a generic
diagnosis time is not necessary.
A fire in Fire Area 6N has the
potential to damage cable ZA2Q1280B.
This cable is associated with the
pressure permissive circuit needed to
open valve MO–2–10–025A. This valve
needs to open to permit injection of Low
Pressure Core Injection (‘‘A’’ train RHR)
following depressurization. Fire Area
6N also contains a number of cables
associated with the ‘‘B’’ train of RHR.
Any number of ‘‘B’’ RHR train cables
could be damaged as a result of a fire
in Fire Area 6N, so the licensee’s
analysis assumed that the ‘‘B’’ RHR was
considered to be unavailable for a fire in
Fire Area 6N.
NRC Staff Evaluation
Given the limited amount of
combustible materials and ignition
sources, it is unlikely that a fire would
occur and go unsuppressed by
personnel, and damage the safe
shutdown equipment. Even if such
circumstances exist, Action H is
available to provide additional
assurance that safe shutdown capability
is maintained.
3.4.4 Fire Area 13N (Unit 3 Reactor
Building)
Fire Prevention
The licensee stated that limited
amounts of Class A combustible
materials, including step-off pads, are
present in this area. The three cables
addressed in this area are routed such
that they terminate at either a 480V load
center or a motor control center (MCC)
cabinet or both.
Detection, Control, and Extinguishment
The licensee stated that both
elevations containing redundant
equipment within Fire Area 13N have
smoke detection systems installed that
produce an alarm in the Control Room,
but that due to the room height and steel
beams at the ceiling, the spacing of the
smoke detectors on both elevations does
not meet the spacing listed in NFPA 72.
Although not entirely compliant with
NFPA 72, this system is considered to
provide adequate coverage to detect a
fire and alert operators of a fire.
Additionally, the licensee stated that a
fully trained onsite fire brigade is
provided, which is dispatched via plant
E:\FR\FM\07APN1.SGM
07APN1
19482
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
page in the event of a fire. The fire
brigade is composed of plant operators
that are separate from operators
assigned safe shutdown duties and are
instructed to provide information about
a fire event over the operations radio to
assist in mitigating the event.
Preservation of Safe Shutdown
Capability
The licensee stated that the 135’
elevation of Fire Area 13N has a ceiling
height of approximately 29’ and an
approximate floor area of 4,033 square
feet and the 165’ elevation has a ceiling
height of approximately 29’ and an
approximate floor area of 6,848 square
feet, so it is unlikely that smoke and
heat would accumulate at the height of
the safe shutdown equipment and cause
a failure due to fire damage.
OMAs Credited for a Fire in This Area
mstockstill on DSKH9S0YB1PROD with NOTICES
Action J
The licensee stated that while it is
possible that any one of the three
redundant cables located in Fire Area
13N could potentially be damaged as a
result of a fault or failure within its
associated 480V load center or MCC, the
impact of a fire on the ability to perform
this action is low since Fire Area 13N
is in a separate building with a separate
ventilation system from the E43 4kV
Switchgear Room and ample time is
available to complete the action.
However, the other installed fire
protection features such as the smoke
detection system, cable conduit, and fire
brigade response would likely minimize
the impact of a fire on the cables
themselves.
A fire in Fire Area 13N has the
potential to damage cables ZD3B1313A,
ZD3A1806A, and ZD3B3983A. The loss
of any of these cables could result in a
loss of the normal power supply to the
3DD003 battery charger. A loss of
ZD3B1313A, ZD3A1806A, or
ZD3B3983A, would necessitate a
manual action to transfer battery charger
3DD003 to an alternate power source to
within 60 minutes since the batteries
can operate for 60 minutes prior to the
initiation of recharging. Battery charger
3DD003 can also be fed from an
alternate power source, which is routed
in separate fire areas, so a single fire
cannot damage both the normal and
alternate power feed. Action J is
available to transfer the alternate power
supply to the battery charger 3DD003.
The action entails first closing a breaker
and then operating a manual transfer
switch. The breaker and manual transfer
switch are located in the E43 4kV
Switchgear Room (Fire Area 34).
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
NRC Staff Evaluation
Given the limited amount of
combustible materials, ignition sources,
and the large volume of the space, it is
unlikely that a fire would occur and go
undetected by the smoke detection
system noted above or unsuppressed by
personnel, and damage the safe
shutdown equipment. Even if such
circumstances exist, Action J is
available to provide additional
assurance that safe shutdown capability
is maintained.
3.4.5 Fire Area 26 (Unit 3 MG Set
Ventilation Equipment Room)
Fire Prevention
The licensee stated that the primary
combustible material in Fire Area 26 is
fire retardant cable insulation and that
there are no in situ ignition sources in
the vicinity of the cables.
Detection, Control, and Extinguishment
The licensee stated that in Fire Area
26, there are two ionization smoke
detectors located in the portion of the
room containing the cables of concern,
but that the overall detector placement
for the fire area as a whole does not
comply with the layout and spacing
requirements of NFPA 72; however, the
two smoke detectors are located in the
immediate vicinity of the cables and
would provide an alarm of a fire
condition. Additionally, the licensee
stated that a fully trained onsite fire
brigade is provided, which is
dispatched via plant page in the event
of a fire. The fire brigade is composed
of plant operators that are separate from
operators assigned safe shutdown duties
and are instructed to provide
information about a fire event over the
operations radio to assist in mitigating
the event.
Preservation of Safe Shutdown
Capability
The licensee stated that Fire Area 26
has a ceiling height of approximately 25’
and an approximate floor area of 2,100
square feet, so it is unlikely that smoke
and heat would accumulate at the
height of the safe shutdown equipment
and cause a failure due to fire damage.
OMAs Credited for a Fire in This Area
Action K
The licensee stated that it is unlikely
that Action K will be necessary because
there is reasonable assurance that both
of the cables would not be damaged in
the event of a fire in Fire Area 26 since
there are no in situ ignition sources in
Fire Area 26 in the vicinity of the
cables, there are no combustible
materials, other than fire retardant cable
PO 00000
Frm 00176
Fmt 4703
Sfmt 4703
insulation exposing the two cables, and
there are two smoke detectors provided
in the area to notify operators of a fire.
In the event that the action is necessary,
the impact of a fire on the ability to
perform this action is low since Fire
Area 26N is in a separate building with
a separate ventilation system from the
E43 4kV Switchgear Room and ample
time is available to complete the action.
A fire in Fire Area 26 has the
potential to damage cables ZD3B1313A,
ZD3A1806A, and ZD3B3983A. The loss
of any of these cables could result in a
loss of the normal power supply to the
3DD003 battery charger. A loss of
ZD3B1313A, ZD3A1806A, or
ZD3B3983A, would necessitate a
manual action to transfer battery charger
3DD003 to an alternate power source
within 60 minutes since the batteries
can operate for 60 minutes prior to the
initiation of recharging. Battery charger
3DD003 can also be fed from an
alternate power source, which is routed
in separate fire areas, so a single fire
cannot damage both the normal and
alternate power feed. Action K is
available to transfer the alternate power
supply to the battery charger 3DD003.
The action entails first closing a breaker
and then operating a manual transfer
switch. The breaker and the manual
transfer switch are located in the E43
4kV Switchgear Room (Fire Area 34).
NRC Staff Evaluation
Given the limited amount of
combustible materials, ignition sources,
and the large volume of the space, it is
unlikely that a fire would occur and go
undetected by the smoke detection
system noted above or unsuppressed by
personnel, and damage the safe
shutdown equipment. Even if such
circumstances exist, Action K is
available to provide additional
assurance that safe shutdown capability
is maintained.
3.4.6 Fire Area 30 (Unit 3 B/D Battery
Room)
Fire Prevention
The licensee stated that the
combustible loading in this area is
considered to be low with the primary
combustible material in this area being
liquid filled plastic battery cases and
that there are no cables in trays in this
fire area. Additionally, the potential for
hydrogen buildup due to the battery
charging process is mitigated by the
ventilation system in the room. The
ventilation system is monitored,
alarmed, and programmatically
controlled. The licensee also stated that
there are no significant ignition sources
in this area.
E:\FR\FM\07APN1.SGM
07APN1
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
Detection, Control, and Extinguishment
The licensee stated that for Fire Area
30 there are three smoke detectors
located in the room and that the spacing
of the detectors is compliant with NFPA
72 with regard to ceiling height, beam
configuration and air flow.
Additionally, two of the three smoke
detectors are located directly above the
encapsulated conduits that contain
redundant cables. Additionally, the
licensee stated that a fully trained onsite
fire brigade is provided, which is
dispatched via plant page in the event
of a fire. The fire brigade is composed
of plant operators that are separate from
operators assigned safe shutdown duties
and are instructed to provide
information about a fire event over the
operations radio to assist in mitigating
the event.
Preservation of Safe Shutdown
Capability
The licensee stated that Fire Area 30
has a ceiling height of approximately 14′
and an approximate floor area of 525
square feet, so it is unlikely that smoke
and heat would accumulate at the
height of the safe shutdown equipment
and cause a failure due to fire damage.
mstockstill on DSKH9S0YB1PROD with NOTICES
OMAs Credited for a Fire in This Area
Action M
The licensee stated that it is unlikely
that both of the redundant cables
located in Fire Area 30 would be
damaged in the event of a fire in Fire
Area 30 since the conduits containing
cables ZA3B1014A and ZA3A1505A are
both encapsulated in abandoned
Thermo-Lag, the primary combustible
material in the room is liquid filled
plastic battery cases, there are no cable
trays or high voltage components
located in the fire area, there are three
smoke detectors located in close
proximity to the cables, and the
potential for hydrogen release from the
battery charging process is mitigated by
the ventilation system that is monitored
for operation and addressed by the
Technical Requirements Manual.
A fire in Fire Area 30 has the
potential to damage cables ZA3B1014A
and ZA3A1505A, which the licensee
stated are located approximately 16
inches from one another at their closest
location. The loss of either of these
cables could result in a loss of the
normal power supply to the 3AD003
battery charger (located in Fire Area 32).
A loss of ZA3B1014A or ZA3A1505A
would necessitate a manual action to
transfer battery charger 3AD003 to an
alternate power source within 60
minutes since batteries can operate for
60 minutes prior to the initiation of
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
recharging. Battery charger 3AD003 can
also be fed from an alternate power
source, which is routed in separate fire
areas, so a single fire cannot damage
both the normal and alternate power
feed. Action M is available to transfer
the alternate power supply to the battery
charger 3AD003. The action entails
operating a manual transfer switch
located in the E33 4kV Switchgear
Room (located in a different fire area).
NRC Staff Evaluation
Given the ventilation system located
in the room, limited amount of
combustible materials, lack of ignition
sources, and the volume of the space, it
is unlikely that a fire would occur and
go undetected by the smoke detection
system noted above or unsuppressed by
personnel, and damage the safe
shutdown equipment. Even if such
circumstances exist, Action M is
available to provide additional
assurance that safe shutdown capability
is maintained.
3.4.7 Fire Area 36 (E42 Switchgear
Room)
Fire Prevention
The licensee stated that the cables in
this area are qualified to IEEE 383, or
equivalent. The licensee also indicated
that there are several sections of
Thermo-Lag in the room. Thermo-Lag is
a fire barrier material that is also
considered a combustible. The licensee
determined that this material does not
create a credible fire exposure to the
conduit and that the overall combustible
material loading for the area is low.
Additionally, Fire Area 36 contains 4kV
switchgear which can create a high
energy fault in the event of a failure and
is considered an ignition source.
However, the conduit containing the
cables of concern is routed 4 feet
horizontally from the front of the
switchgear cabinet, not routed over the
switchgear, and is not expected to be
damaged in the event of a switchgear
failure. Conduit containing four cables
of concern is routed over two battery
chargers, which convert 480 volt AC
into 125 volt DC for the batteries.
However, these chargers are not
anticipated to provide a sustained fault
current like a 4kV switchgear, but heat
from a failure could expose the conduit
and, therefore, represent an ignition
source.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 36
has an NFPA 72-compliant smoke
detection system installed, comprised of
six smoke detectors, and that the room
is also provided with a pre-action
sprinkler system designed in accordance
PO 00000
Frm 00177
Fmt 4703
Sfmt 4703
19483
with NFPA Standard 13, ‘‘Standard for
the Installation of Sprinkler Systems’’
(NFPA 13). Additionally, the licensee
stated that a fully trained onsite fire
brigade is provided, which is
dispatched via plant page in the event
of a fire. The fire brigade is composed
of plant operators that are separate from
operators assigned safe shutdown duties
and are instructed to provide
information about a fire event over the
operations radio to assist in mitigating
the event.
Preservation of Safe Shutdown
Capability
The licensee stated that Fire Area 36
has a ceiling height of approximately 14′
and an approximate floor area of 525
square feet, so it is unlikely that smoke
and heat would accumulate at the
height of the safe shutdown equipment
and cause a failure due to fire damage.
OMAs Credited for a Fire in This Area
Action R
The licensee stated that while it is
possible that the redundant cables
located in Fire Area 36 could potentially
be damaged by heat resulting from a
battery charger failure, it is unlikely that
the cables within the conduits would be
damaged since Fire Area 36 has full area
smoke detection and pre-action
sprinkler systems, the conduit is not
routed directly above the 4kV
switchgear, the combustible loading in
the room is low consisting primarily of
fire retardant cable insulation and
Thermo-Lag, and there are no cable
trays routed below the conduit.
A fire in Fire Area 36 has the
potential to damage cables ZA2A1501E,
ZA2A1501F, ZA2A1508E, and
ZA2A1508F, which the licensee stated
are routed together in a single conduit,
located approximately 9 feet above the
floor, for their entire length in Fire Area
36. The loss of these cables could result
in the loss of power to the E12 bus from
the E1 Emergency Diesel Generator.
Since Fire Area 36 is the E42 4kV
Switchgear Room, the switchgear in this
room is primarily associated with the B
and D electrical trains. Therefore, a fire
in this room is assumed to result in the
loss of the components associated with
the B and D trains. In the event that
these are lost due to a fire in Fire Area
36, Action R is available, which directs
an operator to enter the E12 Switchgear
Room (located in Fire Area 39) and pull
two fuse blocks, open two breakers by
depressing the mechanical breaker trip
button and taking a Main Control Room
breaker control switch to ‘‘Close.’’
E:\FR\FM\07APN1.SGM
07APN1
19484
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
NRC Staff Evaluation
Given the limited amount of
combustible materials and the volume
of the space, it is unlikely that a fire
would occur and go undetected by the
smoke detection system noted above or
unsuppressed by personnel, and damage
the safe shutdown equipment. Even if
such circumstances exist, Action R is
available to provide additional
assurance that safe shutdown capability
is maintained.
3.4.8 Fire Area 37 (E22 Switchgear
Room)
Fire Prevention
The licensee stated that the cables in
this area are qualified to IEEE 383, or
equivalent. Thermo-Lag is also present,
but does not create a credible fire
exposure to the conduit. The licensee
determined that this material does not
create a credible fire exposure to the
conduit and that the overall combustible
material loading for the area is low. Fire
Area 37 also contains 4kV switchgear
which can create a high energy fault in
the event of a failure and is considered
an ignition source. However, the
conduit containing the cables of concern
is routed 4 feet horizontally from the
front of the switchgear cabinet, not
routed over the switchgear, and is not
expected to be damaged in the event of
a switchgear failure. Additionally, a
bank of 480V MCCs exposes conduit
containing four cables of concern to an
exposure hazard in the event that an
MCC fails.
mstockstill on DSKH9S0YB1PROD with NOTICES
Detection, Control, and Extinguishment
The licensee stated that Fire Area 37
has an NFPA 72-compliant smoke
detection system installed, comprised of
three smoke detectors, and that the
room is also provided with a pre-action
sprinkler system designed in accordance
with NFPA 13. Additionally, the
licensee stated that a fully trained onsite
fire brigade is provided, which is
dispatched via plant page in the event
of a fire. The fire brigade is composed
of plant operators that are separate from
operators assigned safe shutdown duties
and are instructed to provide
information about a fire event over the
operations radio to assist in mitigating
the event.
Preservation of Safe Shutdown
Capability
The licensee stated that Fire Area 37
has a ceiling height of approximately 14’
and an approximate floor area of 525
square feet, so it is unlikely that smoke
and heat would accumulate at the
height of the safe shutdown equipment
and cause a failure due to fire damage.
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
OMAs Credited for a Fire in This Area
Action S
The licensee stated that while it is
possible that the redundant cables
located in Fire Area 37 could potentially
be damaged by failure of the bank of
480V MCCs located below the conduit,
it is unlikely that the cables within the
conduits would be damaged since Fire
Area 37 has full area smoke detection
and pre-action sprinkler systems, the
conduit is not routed directly above the
4kV switchgear, the combustible loading
in the room is low consisting primarily
of fire retardant cable insulation and
Thermo-Lag, and there are no cable
trays routed below the conduit.
A fire in Fire Area 37 has the
potential to damage cables ZA2A1501E,
ZA2A1501F, ZA2A1508E, and
ZA2A1508F, which the licensee stated
are routed together in a single conduit,
located approximately 9 feet above the
floor, for their entire length in Fire Area
37. The loss of these cables could result
in the loss of power to the E12 bus from
the E1 Emergency Diesel Generator.
Since Fire Area 37 is the E22 4kV
Switchgear Room, the switchgear in this
room is primarily associated with the B
and D electrical trains, so a fire in this
room is assumed to result in the loss of
the components associated with the B
and D trains. In the event that these are
lost due to a fire in Fire Area 36, Action
R is available, which directs an operator
to enter the E12 Switchgear Room
(located in Fire Area 39) and pull two
fuse blocks, open two breakers by
depressing the mechanical breaker trip
button and taking a Main Control Room
breaker control switch to ‘‘Close.’’
NRC Staff Evaluation
Given the limited amount of
combustible materials and the volume
of the space, it is unlikely that a fire
would occur and go undetected by the
smoke detection system noted above or
unsuppressed by personnel, and damage
the safe shutdown equipment. Even if
such circumstances exist, Action S is
available to provide additional
assurance that safe shutdown capability
is maintained.
3.4.9 Fire Area 43 (E–4 Emergency
Diesel Generator Room)
Fire Prevention
The licensee stated that other than the
diesel fuel and lube oil in the EDG
Rooms, the combustible material
loading is considered to be low. The
fuel oil day tank is located within the
fire area, but in a separate room with
heavy concrete walls and a 3-hour
Underwriters Laboratory (UL)-listed fire
door. Additionally, failure of an
PO 00000
Frm 00178
Fmt 4703
Sfmt 4703
operating diesel generator represents a
significant ignition source. There are
also high voltage electrical components
associated with the generator in the
room. However, these ignition sources
are only credible when the diesel is in
operation. During routine diesel
operations, an equipment operator is
stationed in the room to monitor the
diesel and would be available to
immediately suppress any small fires
that occurred, or to secure the diesel if
a significant malfunction occurred.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 43
has eight heat detectors installed that
annunciate an alarm in the Control
Room and that the room also has a
manually-actuated carbon dioxide (CO2)
fire suppression system installed.
Additionally, the licensee stated that a
fully trained on-site fire brigade is
provided, which is dispatched via plant
page in the event of a fire. The fire
brigade is composed of plant operators
that are separate from operators
assigned safe shutdown duties and are
instructed to provide information about
a fire event over the operations radio to
assist in mitigating the event.
Preservation of Safe Shutdown
Capability
The licensee stated that the
emergency diesel generator rooms are
located in a separate building from the
rest of the plant and that each of the
emergency diesel generators are
separated from one another with a threehour rated fire barrier. Additionally, the
OMA for this area is performed in the
E42 Switchgear room, Fire Area 36,
which is located in the turbine building.
OMAs Credited for a Fire in This Area
Action T
The licensee stated that while it is
possible that the redundant cables in
Fire Area 43 could potentially be
damaged by a lube or fuel oil fire, it is
unlikely that the cables within the
conduits would be damaged since they
are located in conduit that is embedded
in the floor slab for much of the length
they are in Fire Area 43, and there
would have to be a sufficient amount of
oil present on the floor which then
spreads across the floor to expose the
control panels. Even if these two
circumstances occur, a manuallyactuated CO2 fire suppression system is
available to extinguish any fires in the
area.
A fire in Fire Area 43 has the
potential to damage cables ZD2A1807E
or ZD2A1807H, which the licensee
stated are located in conduits embedded
in the concrete floor slab, control
E:\FR\FM\07APN1.SGM
07APN1
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
panels, and a junction box. Failure of
these cables via a hot short could cause
the Unit 2 emergency diesel generator
breaker to close into the E42 bus, either
out of phase or not running, which
would cause a protective trip of the E42
bus. This could result in a loss of the
normal power supply to the 2DD003
battery charger. The battery charger is
needed to maintain long term DC power
through the station batteries. The
batteries can operate for 60 minutes
prior to the initiation of recharging.
Battery charger 2DD003 can also be fed
from an alternate power source, which
is routed in separate fire areas, so a
single fire cannot damage both the
normal and alternate power feed. Action
T is available to transfer the alternate
power supply to the battery charger
2DD003 (located in Fire Area 36). The
action entails operating a manual
transfer switch located in the E42 4kV
Switchgear Room which is a separate
fire area in a separate building.
NRC Staff Evaluation
Given the limited amount of
combustible materials and monitoring of
credible ignition sources in this area, it
is unlikely that a fire would occur and
go undetected by the heat detection
system or unsuppressed by the
suppression system noted above or by
personnel, and damage the safe
shutdown equipment. Even if such
circumstances exist, Action T is
available to provide additional
assurance that safe shutdown capability
is maintained.
3.4.10
Fire Area 50 (Turbine Building)
mstockstill on DSKH9S0YB1PROD with NOTICES
Fire Prevention
The licensee stated that limited
amounts of Thermo-Lag and various
Class A combustible materials are
present in the fire area. The licensee
also stated that the room containing the
cables of concern contains two rows of
13kV switchgear cabinets, which would
be capable of exposing the cables in the
event of a 13 kV switchgear failure.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 50
includes most of the Unit 2 and Unit 3
Turbine Building and as such is a large
fire area including several rooms located
on multiple elevations. However, the
cables of concern with regard to the
associated OMA are only routed through
Room 126. This room contains a full
room smoke detection system with
spacing in accordance with NFPA 72. In
addition, a full room pre-action
sprinkler system is provided in Room
126 with sprinkler head placement in
accordance with NFPA 13. There is also
an automatic sprinkler system in the
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
adjacent open areas of the Turbine
Building. The remainder of the Turbine
Building is separated from Room 126 by
heavy concrete radiation barriers and a
water curtain (which is part of the Room
126 pre-action system) at the doorways.
Additionally, the licensee stated that a
fully trained onsite fire brigade is
provided, which is dispatched via plant
page in the event of a fire. The fire
brigade is composed of plant operators
that are separate from operators
assigned safe shutdown duties and are
instructed to provide information about
a fire event over the operations radio to
assist in mitigating the event.
Preservation of Safe Shutdown
Capability
The primary basis for preserving safe
shutdown capability is included in the
discussion of prevention, detection,
suppression, and control above or
included in the OMAs discussed below.
OMAs Credited for a Fire in This Area
Action U
The licensee stated that while it is
possible that one of the redundant
cables located in Fire Area 50 could
potentially be damaged by failure of the
13kV switchgear, it is unlikely that
additional redundant cables would be
damaged since the conduit containing
cable ZD2A1807E runs above the 13kV
switchgear, there is approximately 5 feet
of separation between it and the next
closest conduit which contains cable
ZA2A1503E, and this conduit is not
located above the 13kV switchgear. The
area is also provided with a smoke
detection system and a pre-action
sprinkler system and the presence of
abandoned, but intact, Thermo-Lag to
protect the cables that are needed to
ensure power to the ‘‘A’’ and ‘‘C’’ train
switchgear to power credited shutdown
components.
There is a cable associated with each
of the four 4kV busses routed through
Fire Area 50. There is the potential for
any of the four diesel generator output
breakers to spuriously close, rendering
the bus unavailable until the diesel
generator breaker is opened and
lockouts are reset. The four cables
associated with the Unit 2 4kV busses
are: Bus E12 breaker cable ZA2A1503E;
bus E22 breaker cable ZB2A1606E; bus
E32 breaker ZC2A1704E; and bus E42
breaker cable ZD2A1807E. Loss of any
one of these cables will only affect the
associated 4kV bus and all four cables
are routed in separate conduits. Cables
ZA2A2503E and ZC2A1704E are routed
in conduits that remain encapsulated in
abandoned Thermo-Lag for their entire
routing through Fire Area 50 while
PO 00000
Frm 00179
Fmt 4703
Sfmt 4703
19485
cables ZB2A1606E and ZD2A1807E are
routed in conduit that is not
encapsulated. The conduit containing
cable ZB2A1606E is located within 5
feet of the conduits containing cables
ZA2B1503E and ZD2A1807E.
Only cables ZA2A1503E and
ZC2A1704E are necessary to power the
busses credited for safe shutdown.
However, Action U would restore power
to all four busses. Only three of the four
busses would require restoration within
60 minutes and only one bus is assumed
to require restoration, since only one
bus is assumed to spuriously operate.
Nevertheless, a 26-minute performance
time is credited for restoration of all
four Unit 2 busses.
In the unlikely event that a fire does
occur and goes undetected by the smoke
detection system or unsuppressed by
the suppression system and damages
multiple redundant cables, Action U is
available to restore power to the busses,
which entails tripping the breaker and
pulling a fuse block for each of the
busses. The location of Action U is in
the associated Switchgear Room for
each associated bus. Additionally, the
Switchgear Rooms are separate fire areas
from the Turbine Building and from
each other and have separate ventilation
systems from the Turbine Building.
Therefore, a fire in Fire Area 50 would
not impact the location of the action.
Action V
Action V is the same as Action U
above but for Unit 3. There is a cable
associated with each of the four 4kV
busses routed through Fire Area 50.
There is the potential for any of the four
diesel generator output breakers to
spuriously close, rendering the bus
unavailable until the diesel generator
breaker is opened and lockouts are reset.
The four cables associated with the Unit
3 4kV busses are: bus E13 breaker cable
ZA3A1503E; bus E23 breaker cable
ZB3A1606E; bus E33 breaker cable
ZC3A1704E; and bus E43 breaker cable
ZD3A1807E. Loss of any one of these
cables will only affect the associated
4kV bus and all four cables are routed
in separate conduits. Cables
ZA3A1503E and ZC3A1704E are routed
in conduits that remain encapsulated in
abandoned Thermo-Lag for their entire
routing through Fire Area 50 while
cables ZB3A1606E and ZD3A1807E are
routed in conduit that is not
encapsulated. The conduit containing
cable ZB3A1606E is located within 5
feet of the conduits containing cables
ZA3A1503E and ZC3A1704E.
Only cables ZA3A1503E and
ZC3A1704E are necessary to power the
busses credited for safe shutdown.
However, Action V would restore power
E:\FR\FM\07APN1.SGM
07APN1
19486
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
mstockstill on DSKH9S0YB1PROD with NOTICES
to all four busses. Only three of the four
busses would require restoration within
60 minutes and only one bus is assumed
to require restoration, since only one
bus is assumed to spuriously operate.
Nevertheless, a 26-minute performance
time is credited for restoration of all
four Unit 3 busses. The licensee stated
that while it is possible that one of the
cables could potentially be damaged by
failure of the 13kV switchgear since the
conduit containing cable ZD2A1807E
runs above the 13kV switchgear, there is
approximately 5 feet of separation
between it and the next closest conduit
which contains cable ZA2A1503E, and
this conduit is not located above the
13kV switchgear. Therefore, it is
unlikely that the cables required for safe
shut down would be damaged by a fire
resulting from failure of the 13kV
switchgear since the area is also
provided with a smoke detection system
and a pre-action sprinkler system and
the presence of abandoned, but intact,
Thermo-Lag to protect the cables that
are needed to ensure power to the ‘‘A’’
and ‘‘C’’ train switchgear to power
credited shutdown components.
In the unlikely event that a fire does
occur and goes undetected by the smoke
detection system or unsuppressed by
the suppression system and damages
multiple redundant cables, Action V is
available to restore power to the busses,
which entails tripping the breaker and
pulling a fuse block for each of the
busses. The location of Action U is in
the associated Switchgear Room for
each associated bus. Additionally, the
Switchgear Rooms are separate fire areas
from the Turbine Building and from
each other and have separate ventilation
systems from the Turbine Building.
Therefore, a fire in Fire Area 50 would
not impact the location of the action.
Action X
The potential need to perform this
action is low since this action is only
needed if two of three other offsite
power sources are unavailable, power to
the 2SU transformer tap changer is lost,
and the tap changer is in the wrong
position. The licensee stated that offsite
power is provided to each of the 4kV
Class 1E switchgear by two of three
redundant sources (2SU, 3SU, and
343SU) and that control cables for the
sources have been physically separated
by rerouting selected cables, such that
one of the redundant sources remains
free of fire damage for fires in most
plant areas. In particular, the licensee
stated that cables associated with the
2SU source have been relocated out of
the Turbine Building (Fire Area 50), and
portions of the Radwaste Building (Fire
Areas 2 and 58).
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
The licensee stated that BOP cables
are routed through Fire Area 50 but that
the routing of the cables was not part of
its analysis. In its February 12, 2010,
supplement, the licensee described the
circumstances that would determine the
availability of the safe shutdown
equipment located in this area; namely
the 2SU power source, which includes
a transformer tap changer that is
powered by BOP power. Since the BOP
cable routing was not part of the
analysis, the loss of BOP power was
assumed for a fire in these three fire
areas. The licensee’s analysis also
assumed that the transformer tap
changer, which is powered by the BOP
and responsible for maintaining power
to the 4kV Bus 2SU, was not in the
correct position. When the tap changer
is not in the correct position, the voltage
could vary resulting in 4kV trip relays
actuating.
In the unlikely event that all of the
conditions discussed above exist and
fire damage occurs to the redundant
cables, Action X can be utilized, which
directs operators to pull the fuse blocks
for the degraded voltage trip relays to
ensure that the 4kV busses remain
available.
The licensee’s T–300 Fire Guides
provide the following guidance to assist
operators in evaluating a postulated
event, ‘‘If 2SU is the only offsite power
source available, and a loss of power to
the 2SU Transformer Tap Change has
occurred, then perform the manual
action to remove the fuses.’’
A note is also provided in the Fire
Guide for this step providing guidance
on how to determine if the 2SU
transformer tap changer has lost power
using indications within the Control
Room. Therefore, the Control Room will
know if this action is required.
Additionally, the 2SU transformer and
associated auxiliaries are located in the
yard area and would not be exposed by
a fire in Fire Area 50. Lastly, the
location of the OMA to remove the fuses
in the 4kV Switchgear Rooms is in a
separate fire area, with separate
ventilation systems, from Fire Area 50.
addition, the area is provided with a
smoke detection system, as well as a
pre-action sprinkler system.
The licensee stated that the redundant
cables located in Fire Area 50 (cables
ZA2B1021B and ZD3B1321B or
ZD3A1321D) are located approximately
5 feet from each other and that no
intervening combustibles are present
between the two trains of cables.
Additionally, the conduit containing
cable ZA2B1021B remains encapsulated
in abandoned Thermo-Lag for the entire
routing through Fire Area 50. The
licensee also stated that the conduits
containing the cables associated with
this OMA are routed directly above
(approximately 5 feet) the 13kV
switchgear cabinets in the room and that
the conduits are assumed to be located
within the anticipated heat plume in the
event of a 13kV switchgear failure.
In the unlikely event that a fire does
occur and goes undetected by the smoke
detection system or unsuppressed by
the suppression system and both trains
of cable are lost, an OMA (Action V) is
available to restore or maintain the
necessary function to the effected
equipment (SU–25 Breaker). Action V
directs an operator to transfer SU–25
breaker auxiliary equipment from the
normal power source to its alternate
power source, by operating manual
transfer switch 00S306, which is located
in the Unit 2 Startup Building, which is
located in the exterior yard area.
Action Y
The licensee stated that while it is
possible that the redundant cables in
Fire Area 50 could potentially be
damaged by a fire resulting from a 13kV
switchgear failure, it is unlikely that
both of the cables within the conduits
would be damaged since the conduit
containing cable ZA2B1021B remains
encapsulated in Thermo-Lag for the
entire length above the 13kV switchgear,
the cable ZA2B1021B is not located
within the same conduit as cables
ZD3B1321B and ZD3B1321D. In
Fire Prevention
The licensee stated that the
combustible loading in Fire Area 58 is
considered to be moderate and consists
primarily of lube oil from the MG set.
Other combustible materials in the area
include fire retardant cable insulation
and Thermo-Lag. Additionally, the MG
set and the MCCs located in the room
represent ignition sources.
PO 00000
Frm 00180
Fmt 4703
Sfmt 4703
NRC Staff Evaluation
Given the limited amount of
combustible materials and the volume
of the space, it is unlikely that a fire
would occur and go undetected by the
smoke detection system noted above or
unsuppressed by the suppression
systems noted above or by personnel,
and damage the safe shutdown
equipment. Even if such circumstances
exist, Actions U, V, X, and Y are
available to provide additional
assurance that safe shutdown capability
is maintained.
3.4.11 Fire Area 58 (Unit 3 MG Set
Room)
Detection, Control, and Extinguishment
The licensee stated that Fire Area 58
has a pre-action sprinkler system
E:\FR\FM\07APN1.SGM
07APN1
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
installed that is designed to provide
localized protection of the MG set with
sprinkler heads located over the MG set
itself and not at the ceiling. Although
this is not considered to be an area-wide
system and does not comply with NFPA
13, this system was an original plant
installation designed to provide
localized protection of the MG set. The
pre-action system is actuated
automatically by any one of the six
smoke detectors in the room, which are
also located directly above the MG set
and not at the ceiling. Since the
detectors are not located at the ceiling
level, the smoke detection system does
not comply with NFPA 72, but still
provides some smoke detection
capability for the area as a whole and
would be expected to alert operators of
the credible fire scenarios for this area.
Additionally, the licensee stated that a
fully trained onsite fire brigade is
provided, which is dispatched via plant
page in the event of a fire. The fire
brigade is composed of plant operators
that are separate from operators
assigned safe shutdown duties and are
instructed to provide information about
a fire event over the operations radio to
assist in mitigating the event.
Preservation of Safe Shutdown
Capability
The licensee stated that Fire Area 58
has a ceiling height of approximately 29’
and an approximate floor area of 3,525
square feet, so it is unlikely that smoke
and heat would accumulate at the
height of the safe shutdown equipment
and cause a failure due to fire damage.
OMAs Credited for a Fire in This Area
mstockstill on DSKH9S0YB1PROD with NOTICES
Action BB
The licensee stated that while it is
possible that the two redundant cables
in Fire Area 58 associated with the
normal power supply to the 3DD003
battery charger could potentially be
damaged by a lube oil or MG set fire, it
is unlikely that the cables within the
conduits would be damaged since the
conduit containing cable ZD3B3983A is
not located above the MG set. In
addition, there is a smoke detection
system provided in the area, as well as
a pre-action sprinkler system located
above the MG set. In the unlikely event
that both cables are lost, the location of
the action is in a different fire area from
Fire Area 58.
A fire in Fire Area 58 has the
potential to damage cables ZD3A1806A
and ZD3B3983A, which the licensee
stated are located in conduits embedded
in the concrete floor slab, control
panels, and a junction box. The loss of
either of these cables could result in a
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
loss of the normal power supply to the
3DD003 battery charger. The battery
charger is needed to maintain long term
DC power through the station batteries.
The batteries can operate for 60 minutes
prior to the initiation of recharging.
Battery charger 3DD003 can also be fed
an alternate power source, which is
routed in separate fire areas, so a single
fire cannot damage both the normal and
alternate power feed.
In the unlikely event that a fire does
occur and goes undetected by the smoke
detection system or unsuppressed by
the suppression system and the cables
are damaged, Action BB is available to
transfer the alternate power supply to
battery charger 3DD003. The action
entails closing a breaker and then
operating a manual transfer switch, both
located in the E43 4kV Switchgear
Room (Fire Area 34), which is a separate
fire area from Fire Area 58.
Action CC
The potential need to perform this
action is low since this action is only
needed if two of three other offsite
power sources are unavailable, power to
the 2SU transformer tap changer lost,
and the tap changer is in the wrong
position. The licensee stated that offsite
power is provided to each of the 4kV
Class 1E switchgear by two of three
redundant sources (2SU, 3SU, and
343SU) and that control cables for the
sources have been physically separated
by rerouting selected cables, such that
one of the redundant sources remains
free of fire damage for fires in most
plant areas. In particular, the licensee
stated that cables associated with the
2SU source have been relocated out of
the Turbine Building (Fire Area 50), and
portions of the Radwaste Building (Fire
Areas 2 and 58).
The licensee stated that BOP cables
are routed through Fire Area 58 but that
the routing of the cables was not part of
its analysis. In its February 12, 2010,
supplement, the licensee described the
circumstances that would determine the
availability of the safe shutdown
equipment located in this area; namely
the 2SU power source, which includes
a transformer tap changer that is
powered by BOP power. Since the BOP
cable routing was not part of the
analysis, the loss of BOP was assumed
for a fire in these three fire areas. The
licensee’s analysis also assumed that the
transformer tap changer, which is
powered by the BOP and responsible for
maintaining power to the 4kV Bus 2SU,
was not in the correct position. When
the tap changer is not in the correct
position, the voltage could vary
resulting in the actuation of the 4kV trip
relays.
PO 00000
Frm 00181
Fmt 4703
Sfmt 4703
19487
In the unlikely event that a fire does
occur and goes undetected by the smoke
detection system or unsuppressed by
the suppression system and fire damage
occurs to the redundant cables, Action
CC can be utilized, which directs
operators to pull the fuse blocks for the
degraded voltage trip relays to ensure
that the 4kV busses remain available.
Action CC is a ‘‘prompt’’ action,
however, the licensee stated that its
analysis assumed that the redundant
cables were lost regardless of their
location and that the tap changer was
not in the correct position. The licensee
also stated that a note is provided in the
applicable T–300 Fire Guide providing
guidance on how to determine whether
the 2SU transformer tap changer has lost
power using indications within the
Control Room. Therefore, the Control
Room will know immediately if this
action is required and a generic
diagnosis time is not necessary.
The licensee’s T–300 Fire Guides also
provide the following guidance to assist
operators in evaluating a postulated
event, ‘‘If 2SU is the only offsite power
source available and a loss of power to
the 2SU Transformer Tap Changer has
occurred, then perform the manual
action to remove the fuses.’’
Additionally, the 2SU transformer
and associated auxiliaries are located in
the yard area and would not be exposed
by a fire in Fire Area 58. Lastly, the
location of the OMA to remove the fuses
in the 4kV Switchgear Rooms is in a
separate fire area, with separate
ventilation systems, from Fire Area 58.
NRC Staff Evaluation
Given the moderate amount of
combustible materials, ignition sources,
and the large volume of the space, it is
unlikely that a fire would occur and go
undetected by the smoke detection
system noted above or unsuppressed by
the suppression system noted above or
by personnel, and damage the safe
shutdown equipment. Even if such
circumstances exist, Actions BB and CC
are available to provide additional
assurance that safe shutdown capability
is maintained.
3.5 Summary of Defense-in-Depth and
Operator Manual Actions
In summary, the NRC staff finds that
the defense-in-depth concept for a fire
in the fire areas discussed above
provides a level of safety that results in
the unlikely occurrence of fires, rapid
detection, control and extinguishment
of fires that do occur and the protection
of structures, systems and components
important to safety. As discussed above,
the licensee has provided preventative
and protective measures in addition to
E:\FR\FM\07APN1.SGM
07APN1
19488
Federal Register / Vol. 76, No. 67 / Thursday, April 7, 2011 / Notices
feasible and reliable OMAs that together
demonstrate the licensee’s ability to
preserve or maintain safe shutdown
capability in the event of a fire in the
analyzed fire areas.
Authorized by Law
This exemption would allow PBAPS
to rely on OMAs, in conjunction with
the other installed fire protection
features, to ensure that at least one
means of achieving and maintaining hot
shutdown remains available during and
following a postulated fire event, as part
of its FPP, in lieu of meeting the
requirements specified in III.G.2 for a
fire in the analyzed fire areas. As stated
above, 10 CFR 50.12 allows the NRC to
grant exemptions from the requirements
of 10 CFR Part 50. The NRC staff has
determined that granting of this
exemption will not result in a violation
of the Atomic Energy Act of 1954, as
amended, or the Commission’s
regulations. Therefore, the exemption is
authorized by law.
mstockstill on DSKH9S0YB1PROD with NOTICES
No Undue Risk to Public Health and
Safety
The underlying purpose of 10 CFR
Part 50, Appendix R, Section III.G is to
ensure that at least one means of
achieving and maintaining hot
shutdown remains available during and
following a postulated fire event. Based
on the above, no new accident
precursors are created by the use of the
specific OMAs, in conjunction with the
other installed fire protection features,
in response to a fire in the analyzed fire
areas. Thus, the probability of
postulated accidents is not increased.
Also, based on the above, the
consequences of postulated accidents
are not increased. Therefore, there is no
undue risk to public health and safety.
Consistent with Common Defense and
Security
The proposed exemption would allow
PBAPS to credit the use of the specific
OMAs, in conjunction with the other
installed fire protection features, in
response to a fire in the analyzed fire
areas, discussed above, in lieu of
meeting the requirements specified in
III.G.2. This change, to the operation of
the plant, has no relation to security
issues. Therefore, the common defense
and security is not diminished by this
exemption.
Special Circumstances
Pursuant to 10 CFR 50.12(a)(2)(ii)
special circumstances are present
whenever application of the regulation
in the particular circumstances is not
necessary to achieve the underlying
purpose of the rule. The underlying
VerDate Mar<15>2010
19:53 Apr 06, 2011
Jkt 223001
purpose of 10 CFR Part 50, Appendix R,
Section III.G is to ensure that at least
one means of achieving and maintaining
hot shutdown remains available during
and following a postulated fire event.
Therefore, since the underlying purpose
of Appendix R, Section III.G is
achieved, the special circumstances for
granting an exemption from 10 CFR Part
50, Appendix R, Section III.G exist, as
required by 10 CFR 50.12(a)(2)(ii).
4.0
Conclusion
Accordingly, the Commission has
determined that, pursuant to 10 CFR
50.12(a), the exemption is authorized by
law, will not present an undue risk to
the public health and safety, and is
consistent with the common defense
and security. Also, special
circumstances are present. Therefore,
the Commission hereby grants Exelon
an exemption from the requirements of
Section III.G.2 of Appendix R of 10 CFR
Part 50, to utilize the OMAs discussed
above at PBAPS.
Pursuant to 10 CFR 51.32, the
Commission has determined that the
granting of this exemption will not have
a significant effect on the quality of the
human environment (75 FR 58445).
This exemption is effective upon
issuance.
Dated at Rockville, Maryland, this 30th day
of March 2011.
For The Nuclear Regulatory Commission.
Joseph G. Giitter,
Director, Division of Operating Reactor
Licensing, Office of Nuclear Reactor
Regulation.
[FR Doc. 2011–8317 Filed 4–6–11; 8:45 am]
BILLING CODE 7590–01–P
NUCLEAR REGULATORY
COMMISSION
[Docket No. 50–219; NRC–2010–0200]
Exelon Generation Company, LLC,
Oyster Creek Nuclear Generating
Station; Exemption
1.0
Background
Exelon Generation Company, LLC
(Exelon or the licensee) is the holder of
Facility Operating License No. DPR–16
that authorizes operation of the Oyster
Creek Nuclear Generating Station
(Oyster Creek). The license provides,
among other things, that the facility is
subject to all rules, regulations, and
orders of the U.S. Nuclear Regulatory
Commission (NRC or the Commission)
now or hereafter in effect.
The facility consists of a boiling-water
reactor located in Ocean County, New
Jersey.
PO 00000
Frm 00182
Fmt 4703
Sfmt 4703
2.0
Request/Action
Title 10 of the Code of Federal
Regulations (10 CFR), Part 50, Section
50.48 requires that nuclear power plants
that were licensed before January 1,
1979, must satisfy the requirements of
10 CFR Part 50, Appendix R, Section
III.G, ‘‘Fire protection of safe shutdown
capability.’’ Oyster Creek was licensed
to operate prior to January 1, 1979. As
such, the licensee’s Fire Protection
Program must provide the established
level of protection as intended by
Section III.G of 10 CFR Part 50,
Appendix R.
By letter dated March 4, 2009,
‘‘Request for Exemption from 10 CFR 50,
Appendix R, Section III.G, ‘Fire
Protection of Safe Shutdown Capability
(Phase 2)’ ’’ available at Agencywide
Documents Access and Management
System (ADAMS), Accession No.
ML090640225, and supplemented by
letter dated April 2, 2010, ‘‘Response to
Request for Additional Information
Request for Exemption from 10 CFR Part
50, Appendix R, Section III.G, ‘Fire
Protection of Safe Shutdown
Capability’ ’’ (ADAMS Accession No.
ML100920370), the licensee requested
an exemption for Oyster Creek from
certain technical requirements of 10
CFR Part 50, Appendix R, Section III.G.2
(III.G.2) for the use of operator manual
actions (OMAs) in lieu of meeting the
circuit separation and protection
requirements contained in III.G.2 for the
following 22 plant areas: CW–FA–14,
OB–FA–9, OB–FZ–6A, OB–FZ–6B, OB–
FZ–8A, OB–FZ–8B, OB–FZ–8C, OB–
FZ–10A, RB–FZ–1D, RB–FZ–1E, RB–
FZ–1F3, RB–FZ–1F5, RB–FZ–1G, TB–
FA–3A, TB–FA–26, TB–FZ–11B, TB–
FZ–11C, TB–FZ–11D, TB–FZ–11E, TB–
FZ–11F, TB–FZ–11H, and Yard. The 22
plant areas noted above are the subject
of this exemption.
3.0
Discussion
Pursuant to 10 CFR 50.12, the
Commission may, upon application by
any interested person or upon its own
initiative, grant exemptions from the
requirements of 10 CFR Part 50 when:
(1) The exemptions are authorized by
law, will not present an undue risk to
public health or safety, and are
consistent with the common defense
and security; and (2) when special
circumstances are present. The licensee
has stated that special circumstances are
present in that the application of the
regulation in this particular
circumstance is not necessary to achieve
the underlying purpose of the rule,
which is consistent with the language
included in 10 CFR 50.12(a)(2)(ii).
E:\FR\FM\07APN1.SGM
07APN1
Agencies
[Federal Register Volume 76, Number 67 (Thursday, April 7, 2011)]
[Notices]
[Pages 19476-19488]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2011-8317]
=======================================================================
-----------------------------------------------------------------------
NUCLEAR REGULATORY COMMISSION
[Docket Nos. 50-277 and 50-278; NRC-2010-0303]
Exelon Generation Company, LLC, Peach Bottom Atomic Power
Station, Unit Nos. 2 and 3; Exemption
1.0 Background
Exelon Generation Company, LLC (the licensee, Exelon) is the holder
of Renewed Facility Operating License Nos. DPR-44 and DPR-56, which
authorizes operation of the Peach Bottom Atomic Power Station (PBAPS),
Units 2 and 3. The license provides, among other things, that the
facility is subject to all rules, regulations, and orders of the
Nuclear Regulatory Commission (NRC, the Commission) now or hereafter in
effect.
The facility consists of two boiling-water reactors located partly
in Peach Bottom Township, York County, partly in Drumore Township,
Lancaster County, and partly in Fulton Township, Lancaster County, in
southeastern Pennsylvania.
2.0 Request/Action
Title 10 of the Code of Federal Regulations (10 CFR), Part 50,
Section 50.48(b), requires that nuclear power plants that were licensed
before January 1, 1979, satisfy the requirements of 10 CFR Part 50,
Appendix R, ``Fire Protection Program for Nuclear Power Facilities
Operating Prior to January 1, 1979,'' Section III.G, ``Fire protection
of safe shutdown capability.'' PBAPS, Units 2 and 3 were licensed to
operate prior to January 1, 1979. As such, the licensee's Fire
Protection Program (FPP) must provide the established level of
protection as intended by Section III.G of 10 CFR Part 50, Appendix R.
By letter dated March 6, 2009, ``Request for Exemption from 10 CFR
50, Appendix R, Section III.G, `Fire Protection of Safe Shutdown
Capability' '' available at Agencywide Documents Access and Management
System (ADAMS), Accession No. ML090680141, and supplemented by letter
dated February 12, 2010, ``Response to Request for Additional
Information Request for Exemption from 10 CFR 50, Appendix R, Section
III.G, `Fire Protection of Safe Shutdown Capability' '' (ADAMS
Accession No. ML100470774), the licensee requested an exemption for
PBAPS, Units 2 and 3, from certain technical requirements of 10 CFR
Part 50, Appendix R, Section III.G.2 (III.G.2) for the use of operator
manual actions (OMAs) in lieu of meeting the circuit separation and
protection requirements contained in III.G.2 for Fire Areas 2, 6N, 6S,
13N, 26, 30, 36, 37, 43, 50, and 58 at the plant.
3.0 Discussion
Pursuant to 10 CFR 50.12, the Commission may, upon application by
any interested person or upon its own initiative, grant exemptions from
the requirements of 10 CFR Part 50 when: (1) The exemptions are
authorized by law, will not present an undue risk to public health or
safety, and are consistent with the common defense and security; and
(2) when special circumstances are present. The licensee has stated
that special circumstances are present in that the application of the
regulation in this particular circumstance is not necessary to achieve
the underlying purpose of the rule, which is consistent with the
language included in 10 CFR 50.12(a)(2)(ii).
In letters dated March 6, 2009, and February 12, 2010, the licensee
discussed financial implications associated with plant modifications
that may be necessary to comply with the regulation. 10 CFR
50.12(a)2(iii) states that if such costs have been shown to be
significantly in excess of those contemplated at the time the
regulation was adopted, or are significantly in excess of those
incurred by others similarly situated, this may be considered a basis
for considering an exemption request. However, financial implications
were not considered in the regulatory review of the request since no
substantiation was provided regarding such financial implications. Even
though no financial substantiation was provided, the licensee did
submit sufficient regulatory basis to support a technical review of the
exemption request in that the application of the regulation in this
particular circumstance is not necessary to achieve the underlying
purpose of the rule.
In accordance with 10 CFR 50.48(b), nuclear power plants licensed
before January 1, 1979, are required to meet Section III.G, of 10 CFR
Part 50, Appendix R. The underlying purpose of Section III.G of 10 CFR
Part 50, Appendix R, is to ensure that the ability to achieve and
maintain safe shutdown is preserved following a fire event. The
regulation intends for licensees to accomplish this by extending the
concept of defense-in-depth to:
(1) Prevent fires from starting;
(2) Rapidly detect, control, and extinguish promptly those fires
that do occur;
(3) Provide protection for structures, systems, and components
important to safety, so that a fire that is not promptly extinguished
by the fire suppression activities will not prevent the safe shutdown
of the plant.
The stated purpose of 10 CFR Part 50, Appendix R, Section III.G.2
(III.G.2) is to ensure that one of the redundant trains necessary to
achieve and maintain hot shutdown conditions remains free of fire
damage in the event of a fire. III.G.2 requires one of the following
means to ensure that a redundant train of safe shutdown cables and
equipment is free of fire damage, where redundant trains are located in
the same fire area outside of primary containment:
a. Separation of cables and equipment by a fire barrier having a 3-
hour rating;
[[Page 19477]]
b. Separation of cables and equipment by a horizontal distance of
more than 20 feet with no intervening combustibles or fire hazards and
with fire detectors and an automatic fire suppression system installed
in the fire area; or
c. Enclosure of cables and equipment of one redundant train in a
fire barrier having a 1-hour rating and with fire detectors and an
automatic fire suppression system installed in the fire area.
Exelon has requested an exemption from the requirements of III.G.2
for PBAPS, Units 2 and 3 to the extent that one of the redundant trains
of systems necessary to achieve and maintain hot shutdown is not
maintained free of fire damage in accordance with one of the required
means, for a fire occurring in Fire Areas 2 (Radwaste Building), 6S
(Unit 2 Reactor Building), 6N (Unit 2 Reactor Building, North side),
13N (Unit 3 Reactor Building), 26 (Unit 3 Motor-Generator (MG) Set
Ventilation Equipment Room), 30 (Unit 3 B/D Battery Room), 36 (E42
Switchgear Room), 37 (E22 Switchgear Room), 43 (E-4 Emergency Diesel
Generator Room), 50 (Turbine Building), and 58 (Unit 3 MG Set Room).
In its submittals, the licensee described elements of the FPP that
provide justification that the concept of defense-in-depth that is in
place in the above fire areas is consistent with that intended by the
regulation. To accomplish this, the licensee utilizes various
protective measures. Specifically, the licensee stated that the purpose
of its request was to credit the use of OMAs, in conjunction with other
defense-in-depth features, in lieu of the separation and protective
measures required by III.G.2 for a fire in the fire areas stated above.
3.1 Fire Prevention
In its March 6, 2009, and February 12, 2010, letters, the licensee
provided an analysis that described how fire prevention is addressed
for each of the fire areas for which the OMAs may be required. Unless
noted otherwise in Section 3.4 below, all of the fire areas included in
this exemption have a combustible fuel load that is considered to be
low with fuel sources consisting primarily of fire retardant cable
insulation and limited floor-based combustibles. Unless noted
otherwise, there are no high energy ignition sources located in the
areas. The fire areas included in the exemption are not shop areas, so
hot work activities are infrequent with administrative control programs
(e.g., hot work permits, fire watch, and supervisory controls). The
administrative control programs are described in the PBAPS FPP, which
is incorporated into the Updated Final Safety Analysis Report.
3.2 Detection, Control and Extinguishment
PBAPS has been divided into fire areas, as described in the PBAPS
FPP. Three-hour fire barriers are normally used to provide fire
resistive separation between adjacent fire areas. In some cases,
barriers with a fire resistance rating of less than 3 hours are
credited, but exemptions have been approved or engineering evaluations
performed in accordance with Generic Letter 86-10, ``Implementation of
Fire Protection Requirements,'' to demonstrate that the barriers are
sufficient for the hazard. Walls separating rooms and zones within fire
areas are typically constructed of concrete. In addition to these
boundaries, the licensee provided a hazard analysis that described how
detection, control, and extinguishment of fire are addressed for each
of the fire areas for which the OMAs may be required.
Unless noted otherwise below, fire areas are provided with
ionization smoke detectors in various locations within a particular
fire area. Although not installed in accordance with a recognized
standard with regard to spacing, the detectors are located near
equipment such that they are likely to adequately detect a fire. Upon
detecting smoke, the detectors initiate an alarm in the Control Room
enabling fire brigade response. The licensee stated that in most cases,
no automatic fire suppression systems are provided in the areas
included in this exemption but that fire suppression systems are
installed in plant areas with significant fire hazards, such as lube
oil. Suppression systems have also been installed in areas with 1-hour
barrier walls and 1-hour rated electrical raceway encapsulation.
The automatic suppression systems are not credited in reducing fire
exposure to redundant equipment unless they are indicated as being
full-area or specifically described as being effective for redundant
equipment. Equipment operators are trained fire brigade members and
would likely identify and manually suppress or extinguish a fire using
the portable fire extinguishers and manual hose stations located
throughout the fire areas.
3.3 Preservation of Safe Shutdown Capability
Each OMA included in this review consists of a sequence of tasks
that occur in various fire areas. The OMAs are initiated upon
confirmation of a fire in a particular fire area. The licensee stated
that the postulated fire events that may require the use of the OMAs
would include multiple failures of various components or equipment. In
most cases, it is considered highly unlikely that the sequence of
events required to necessitate the OMAs would fully evolve because of
the fire prevention, fire protection, and physical separation features
in place. However, in the event that the sequence does evolve, the OMAs
are available to provide assurance that safe shutdown can be achieved.
This analysis postulates that OMAs may be needed to assure safe
shutdown capability in addition to the traditional fire protection
features described above. For each of the fire areas included in this
exemption, the licensee evaluated the OMAs against the criteria of
NUREG-1852, ``Demonstrating the Feasibility and Reliability of Operator
Manual Actions in Response to Fire,'' October 2007, in the March 6,
2009, submittal. A Fire Hazards Analysis was provided for each of the
OMAs in the licensee's February 12, 2010, supplement.
3.3.1 Licensee's Bases for Establishing Feasibility and Reliability
The licensee's analysis addresses factors such as environmental
concerns, equipment functionality and accessibility, available
indications, communications, portable equipment, personnel protection
equipment, procedures and training, staffing and demonstrations.
In its March 6, 2009, submittal, and further supported by its
February 12, 2010, supplement, the licensee stated that environmental
considerations such as radiological concerns, emergency lighting,
temperature and humidity conditions and smoke and toxic gases were
evaluated and found to not represent a negative impact on the
operators' abilities to complete the OMA. The licensee stated that the
dose limits contained in 10 CFR Part 20 are never challenged at any
point along the travel path of any of the OMAs included in this
exemption.
The licensee confirmed that each of the OMA locations addressed by
this exemption is provided with emergency lighting that illuminates
both the location where the manual action is performed and the access
route to the manual action location. Where travel is required to
buildings outside of the power block, portable lights are staged in the
fire safe shutdown equipment locker which is inventoried and maintained
by performance of a periodic routine test. The emergency
[[Page 19478]]
lights are periodically checked for operation and aim at the target
location.
The licensee also confirmed that temperature and humidity
conditions will not challenge the operators performing the OMAs.
Additionally, the licensee indicated that heat and smoke or gas
generation from a fire will not impact the operator performing the
OMAs. This is further supported by the fact that the locations of the
postulated fire events are in different fire areas than the locations
for where the actions are performed. In most cases, the initiating fire
area and manual action location fire area are in separate buildings and
have separate ventilation systems. Other than smoke, CO2 is
another toxic gas that could present a hazard. However, all of the
CO2 fire suppression systems at PBAPS are manually actuated
to prevent an inadvertent discharge of a system.
The licensee stated that the equipment to be operated as part of
the OMAs will be functional and maintained free of fire damage and will
be accessible to the operators performing the action. Additionally,
PBAPS maintains Transient Response Implementing Plan procedures and T-
300 Fire Guides. T-300 Fire Guides provide the operators with specific
instructions in the event of a fire in a specific fire area. The T-300
Fire Guides provide a list of the key protected instruments available
for a fire in the fire area and list any ``prompt'' actions that are
needed to restore an instrument for a fire in that area (i.e., those
that need to be performed within 30 minutes). The applicable T-300 Fire
Guide lists the ``prompt'' actions at the front of the document. In
addition, the licensee stated that where specific indications may be
lost due to a postulated event, the applicable T-300 Fire Guide for
that fire area identifies which indications may be lost and how to
recover the loss of that indication. Most required shutdown parameter
indications are provided by multiple instruments; therefore, even with
the loss of certain instruments or power supplies, redundant
instruments are available to provide indications to assist operators.
With regard to communications, the licensee stated that PBAPS has
radios and phones available as part of the normal communications
between the Control Room and the operators. Although the communication
system is not specifically hardened for post-fire survivability, the
radio and phone systems are robustly designed such that they will be
available following most fire scenarios. In the event that the radio
and phone systems are inoperable, face-to-face communication, and
adequate time, is available to dispatch the safe shutdown operators
from the Control Room to perform the tasks and return to the Control
Room for reassignment when the task is complete. With the exception of
Action H, none of the operator manual actions addressed by this
exemption require immediate or concurrent coordination with the Control
Room while performing the task.
The licensee stated that if any keys, tools or equipment are
required to perform the OMAs, the T-300 Fire Guides provide
instructions on where to find them and how to use them. In addition,
the licensee stated that operators are provided with standard personal
protective equipment (PPE) (i.e., hardhat, safety glasses, hearing
protection, gloves, etc.) and that additional PPE is not required for
any of the OMAs, with the exception of actions that require that an
electrical enclosure be opened to manipulate an insulated handle of a
manual transfer switch. For these tasks, a PBAPS corporate safety
procedure requires the use of additional electrical safety PPE when
performing this task.
The licensee stated that the T-300 Fire Guides provide in-depth
safe shutdown direction for fires in specific fire areas and that the
procedures included in the guides include specific instructions on
assessing plant indications and events as well as instructions on how
to perform each of the OMAs. The procedures are then used to train the
operators on the OMAs, which consist primarily of activities that are
considered to be similar to those performed as part of typical work
activity and are considered straightforward with minimal training
demands. In addition, the licensee stated that licensed operators are
trained biennially on the use of the T-300 Fire Guides using simulator
scenarios that start with a fire in a specific fire area.
With regard to staffing, the licensee stated that PBAPS maintains a
minimum of three operators on each shift to perform safe shutdown
duties in the event of a fire, which may be comprised of equipment
operators, reactor operators or senior reactor operators. Additionally,
the licensee stated that PBAPS performed several demonstrations using
what is considered to be the most challenging initiating fire area, the
Turbine Building (Fire Area 50), because it encompasses both Unit 2 and
Unit 3, includes an action that is a prompt action in other fire areas,
and includes a number of OMAs to perform within the first 60 minutes.
3.3.2 NRC Staff Evaluation of Feasibility
The NRC staff has determined that the licensee's analysis
demonstrates that, for the expected scenarios, the OMAs can be
diagnosed and executed within the amount of time necessary to complete
them. The licensee's analysis also demonstrates that various factors,
as discussed above, have been considered to address uncertainties in
estimating the time available. Therefore, the NRC staff finds that the
OMAs included in this review are feasible because there is adequate
time available for the operator to perform the required OMAs to achieve
and maintain hot shutdown following a postulated fire event. The
following table summarizes the ``required'' verses ``allowable'' times
for each OMA. Where a diagnosis time has been identified, it is
included as part of the required time for a particular action. Where an
action has multiple times or contingencies associated with the
``allowable'' completion time, the lesser time is used. This approach
is considered to represent a conservative approach to analyzing the
timelines associated with each of the OMAs with regard to the
feasibility and reliability of the actions included in this exemption.
In some cases, the margin between the required time and allowable time
is small. Specifically actions D, U, V, and X, have 20 percent or less
margin. This limited margin is based on using the most limiting
information from the licensee. For example, if the licensee postulated
up to 30 minutes for diagnosis, the higher value of the required time
range noted in the table below includes the time to complete the action
plus the full 30 minutes.
Finally, these numbers should not be considered without the
understanding that the manual actions are a fall back in the unlikely
event that the fire protection defense-in-depth features are
insufficient. In most cases, there is no credible fire scenario that
would necessitate the performance of these OMAs. The licensee provided
a discussion of the times and circumstances associated with each of the
actions in its March 6, 2009, and February 12, 2010, correspondence.
[[Page 19479]]
------------------------------------------------------------------------
Required Allowable
Fire area of fire origin OMA time (min) time (min)
------------------------------------------------------------------------
Fire Area 2 (Radwaste Action B....... 15--45* 120
Building).
Action C....... 15 25 **
Action D....... 18--48* 60
Fire Area 6S (Unit 2 Reactor Action G....... 14--44* 60
Building).
Fire Area 6N (Unit 2 Reactor Action H....... 7 25 **
Building, North Side).
Fire Area 13N (Unit 3 Reactor Action J....... 12--42* 60
Building).
Fire Area 26 (Unit 3 MG Set Action K....... 12--42* 60
Ventilation Equipment Room).
Fire Area 30 (Unit 3 B/D Action M....... 9--39* 60
Battery Room).
Fire Area 36 (E42 Switchgear Action R....... 12--42* 60
Room).
Fire Area 37 (E22 Switchgear Action S....... 12--42* 60
Room).
Fire Area 43 (E-4 Emergency Action T....... 9--39* 60
Diesel Generator Room).
Fire Area 50 (Turbine Action U....... 26--56* 60
Building).
Action V....... 26--56* 60
Action X....... 24--54* 60
Action Y....... 15--45* 120
Fire Area 58 (Unit 3 MG Set Action BB...... 12--42* 60
Room).
Action CC...... 12 25**
------------------------------------------------------------------------
* The higher value of the required time range accounts for a generic 30-
minute diagnosis time to assess the need for OMAs.
** Prompt actions are those having allowable completion times of 30
minutes or less.
3.3.3 NRC Staff Evaluation of Reliability
The completion times noted in the table above provide reasonable
assurance that the OMAs can reliably be performed under a wide range of
conceivable conditions by different plant crews. This is because the
completion time, in conjunction with the time margins associated with
each action and other installed fire protection features, account for
sources of uncertainty such as variations in fire and plant conditions,
factors unable to be recreated in demonstrations and human-centered
factors. Therefore, the NRC staff finds that the OMAs included in this
review are reliable because there is adequate time available to account
for uncertainties not only in estimates of the time available, but also
in estimates of how long it takes to diagnose a fire and execute the
OMAs (i.e., as based, at least in part, on a plant demonstration of the
actions under non-fire conditions).
For each of the fire areas included in this exemption, the
postulated fire scenarios and pertinent details are summarized in
Section 3.4 below.
3.4 NRC Staff Fire Area Evaluations
3.4.1 Fire Area 2 (Radwaste Building)
Fire Prevention
The licensee stated that the floor-based combustibles include
health physics cleaning supplies, such as mops, vacuums and other Class
A combustibles as well as several steel carts containing new resins in
paper or plastic bags. The total weight of the plastic bags is
estimated to be less than 5 pounds and empty resin bags are immediately
removed.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 2 has fire suppression systems
installed within the fire area but not within the rooms containing
redundant cables. The licensee has further stated that the detection
systems in the rooms containing redundant cables are not code compliant
in terms of overall spacing in the fire area. However, a smoke detector
is located within 5 feet of redundant cable ZA2B1021A. There is also a
smoke detector located within 15 feet of both cables ZD3A1806A and
ZD3A1321A. The licensee also stated that the Radwaste Control Room is
located directly adjacent to these three rooms and that it is normally
occupied by an equipment operator. Because of this, it is likely that
any fire would be quickly identified by an operator in the area.
Additionally, the licensee stated that a fully trained onsite fire
brigade is provided, which is dispatched via plant page in the event of
a fire. The fire brigade is composed of plant operators that are
separate from operators assigned safe shutdown duties and are
instructed to provide information about a fire event over the
operations radio to assist in mitigating the event. Fire Area 2 is
provided with manual fire fighting equipment such as portable fire
extinguishers and manual hose stations throughout the area.
Preservation of Safe Shutdown Capability
The licensee stated that Fire Area 2 is a large fire area
containing a number of rooms on several elevations and that spatial
separation of redundant cables is provided as discussed below.
OMAs Credited for a Fire in This Area
Action B
The licensee stated that the redundant cables located in Fire Area
2 (cables ZA2B1021A and ZD3B1321A or ZD3A1806A) are located a minimum
of approximately 30 feet from each other and that no intervening
combustibles are present between the two trains of cables. This
physical separation with the available fire detection system will
provide the site fire brigade an opportunity to extinguish the fire
before redundant trains are damaged. The licensee also stated that the
cables are located a minimum of approximately 9 feet above the floor
and that they are enclosed in rigid conduit, such that transient fire
exposures and self-ignited cable fires are unlikely to affect the
circuits.
In the unlikely event that both trains of cable are lost due to a
fire in Fire Area 2, an OMA (Action B) is available to restore or
maintain the necessary function to the effected equipment (SU-25
Breaker). Action B directs an operator to transfer SU-25 breaker
auxiliary equipment from the normal power source to its alternate power
source, by operating manual transfer switch 00S306, which is located in
the Unit 2 Startup Building. The Unit 2 Startup Building is located in
the exterior yard area.
Action C
The potential need to perform this action is low since this action
is only needed if two of three offsite power sources are unavailable,
power to the 2SU transformer tap changer is lost, and the tap changer
is in the wrong position. The licensee stated that offsite power is
provided to each of the 4kV Class 1E switchgear by two of three
redundant
[[Page 19480]]
sources (2SU, 3SU, and 343SU) and that control cables for the sources
have been physically separated by rerouting selected cables, such that
one of the redundant sources remains free of fire damage for fires in
most plant areas. In particular, the licensee stated that cables
associated with the 2SU source have been relocated out of the Turbine
Building (Fire Area 50), and portions of the Radwaste Building (Fire
Areas 2 and 58).
The licensee stated that balance of plant (BOP) cables are routed
through Fire Area 2, but that the routing of the cables was not part of
the analysis. In the licensee's February 12, 2010, supplement, the
licensee described the circumstances that would determine the
availability of the safe shutdown equipment located in this area;
namely the 2SU power source, which includes a transformer tap changer
that is powered by BOP power. Since the BOP cable routing was not part
of the analysis, the loss of BOP power was assumed for a fire in these
three fire areas. The licensee's analysis also assumed that the
transformer tap changer, which is powered by the BOP and responsible
for maintaining power to the 4kV Bus, was not in the correct position.
When the tap changer is not in the correct position, the voltage could
vary resulting in actuation of the 4kV trip relays.
In the unlikely event that all of the conditions discussed above
exist and fire damage occurs to the redundant cables, Action C can be
utilized, which directs operators to pull the fuse blocks for the
degraded voltage trip relays to ensure that the 4kV busses remain
available. Action C is a ``prompt'' action, with an allowable
completion time of 30 minutes or less, however, the licensee stated
that its analysis assumed that the redundant cables were lost
regardless of their location and that the tap changer was not in the
correct position. The licensee stated that the loss of certain
equipment in a fire area due to a fire will result in a Control Room
alert. Off Normal procedure ON-114, ``Actual Fire Reported in the Power
Block, Diesel Generator Building, Emergency Pump, Inner Screen or
Emergency Cooling Tower Structures,'' is immediately entered upon
confirmation of a fire condition. Procedure ON-114 directs immediate
entry into the Fire Guide for the affected fire area. The licensee also
stated that a note is provided in the applicable safe shutdown fire
guide series (T-300 Fire Guides) providing guidance on how to determine
whether the 2SU transformer tap changer has lost power using
indications within the Control Room. Therefore, the Control Room will
know immediately if this action is required and a generic diagnosis
time is not necessary.
The licensee's T-300 Fire Guides also provide the following
guidance to assist operators in evaluating a postulated event, ``If 2SU
is the only offsite power source available, and a loss of power to the
2SU Transformer Tap Change has occurred, then perform the manual action
to remove the fuses.'' Additionally, the 2SU transformer and associated
auxiliaries are located in the yard area and would not be exposed by a
fire in Fire Area 2. Lastly, the location of the OMA to remove the
fuses in the 4kV Switchgear Rooms is in a separate fire area, with
ventilation systems that are separate from Fire Area 2.
Action D
The licensee stated that this action would only be required if the
conduit containing cable, which is located above the suspended ceiling
with the only exposing combustible being a tray with fire retardant
cables, is damaged by fire. There is a lack of ignition sources and a
relatively short length (approximately 6 feet) of cable that passes
through Fire Area 2. In addition, there is a smoke detector located
within 5 feet of the conduit containing the cable, which would result
in rapid plant notification of an exposure fire.
In the unlikely event that a fire in Fire Area 2 damages cable
ZA2B1014A, normal power to the 2AD003 battery charger could be lost,
which is needed to maintain long term DC power through the station
batteries. A loss of ZA2B1014A would necessitate a manual action to
transfer battery charger 2AD003 to an alternate power source within 60
minutes since the batteries can operate for 60 minutes prior to the
initiation of recharging. The alternate power source is routed in
separate fire areas, so a single fire cannot damage both the normal and
alternate power feed. Action D is available to transfer the alternate
power supply to the battery charger 2AD003. The action entails closing
a breaker located in the E13 4kV Switchgear Room (Fire Area 33) and
then operating a manual transfer switch located in the E32 4kV
Switchgear Room (Fire Area 38), both of which are separate fire areas
from Fire Area 2.
NRC Staff Evaluation
Given the limited amount of combustible materials and ignition
sources, it is unlikely that a fire would occur and go undetected by
the smoke detection system noted above or unsuppressed by personnel,
and damage the safe shutdown equipment. Even if such circumstances
exist, Actions B, C, and D are available to provide additional
assurance that safe shutdown capability is maintained.
3.4.2 Fire Area 6S (Unit 2 Reactor Building)
Fire Prevention
The licensee stated that conduits are routed primarily through a
transient combustible-free zone where a permit and review are required
prior to the placement of combustibles in this area.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 6S has ionization smoke
detectors installed in the overhead area but that these smoke detectors
do not have code compliant spacing due to ceiling height and beam
pockets. However, there are three smoke detectors located above the
general routing of the redundant cable conduits, which would be
expected to activate in the event of a fire occurring in close
proximity to the redundant cables. Additionally, the licensee stated
that a fully trained onsite fire brigade is provided, which is
dispatched via plant page in the event of a fire. The fire brigade is
composed of plant operators that are separate from operators assigned
safe shutdown duties and are instructed to provide information about a
fire event over the operations radio to assist in mitigating the event.
Preservation of Safe Shutdown Capability
The licensee stated that Room 403 in Fire Area 6S has a ceiling
height of approximately 29' and an approximate floor area of 6,848
square feet, so it is unlikely that smoke and heat would accumulate at
the height of the safe shutdown equipment and cause a failure due to
fire damage.
OMAs Credited for a Fire in This Area
Action G
The licensee stated that recent plant experience with faults and
malfunctions in similar load centers has been that even when energetic
failures have occurred, its damage has been contained within the
breaker cubicle, with some heat and smoke damage to immediately
adjacent cubicles. Therefore, it is considered unlikely that the cables
routed above the load centers would be affected by a fault within the
load centers since there is not a credible fire scenario that would be
capable of damaging the cables within the conduits.
A fire in Fire Area 6S has the potential to damage cables
ZA2B1014A, ZA2A1505A, and ZA2B1021A. The licensee stated that there are
three 480V
[[Page 19481]]
load centers in the room containing the redundant cables and that the
cables are routed to one of the load centers. As a result, each cable
is routed over a 480V load center and in two cases the conduit passes
over two load centers prior to entering the third load center. The
conduits are located above the two adjacent load centers, which consist
of a 4kv to 480v sealed gas cooled step-down transformer and a 480v
switchgear.
The loss of these cables could result in a loss of the normal power
supply to the 2AD003 battery charger, which is needed to maintain long
term DC power through the station batteries. A loss of ZA2B1014A,
ZA2A1505A, and ZA2B1021A would necessitate a manual action to transfer
battery charger 2AD003 to an alternate power source within 60 minutes
since the batteries can operate for 60 minutes prior to the initiation
of recharging. The alternate power source is routed in separate fire
areas, so a single fire cannot damage both the normal and alternate
power feed. Action G is available to transfer the alternate power
supply to the battery charger 2AD003. The action entails closing a
breaker located in the E13 4kV Switchgear Room (Fire Area 33) and then
operating a manual transfer switch located in the E32 4kV Switchgear
Room (Fire Area 38), both of which are separate fire areas from Fire
Area 6S.
NRC Staff Evaluation
Given the limited amount of combustible materials, ignition
sources, and the large volume of the space, it is unlikely that a fire
would occur and go undetected by the smoke detection system noted above
or unsuppressed by personnel, and damage the safe shutdown equipment.
Even if such circumstances exist, Action G is available to provide
additional assurance that safe shutdown capability is maintained.
3.4.3 Fire Area 6N (Unit 2 Reactor Building, North side)
Fire Prevention
The licensee stated that the only floor-based combustibles in this
area are trash cans and cables. Trash can lids are designed to provide
self-extinguishing capability to the trash cans. Cables in the area are
qualified to the Institute of Electrical and Electronics Engineers,
Inc. Standard-383, ``IEEE Standard For Qualifying Class 1E Electrical
Cables And Field Splices for Nuclear Power Generating Stations'' (IEEE
383), or equivalent.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 6N has a smoke detection system
installed, but that the spacing is not in compliance with National Fire
Protection Association Code 72, ``National Fire Alarm and Signaling
Code'' (NFPA 72), due to deep beam pockets at the ceiling of this area.
However, there is a smoke detector within the vicinity (approximately
25 feet) of each of the cases where cable ZA2Q1280B and a ``B''
residual heat removal (RHR) cable intersect, which would be expected to
activate in the event of a fire in close proximity to the redundant
equipment. There is also an automatic water curtain on the west side of
the Unit 2 Reactor Building that separates Fire Area 6N from Fire Area
6S, thus reducing any anticipated exposure from Fire Area 6S.
Additionally, the licensee stated that a fully trained onsite fire
brigade is provided, which is dispatched via plant page in the event of
a fire. The fire brigade is composed of plant operators that are
separate from operators assigned safe shutdown duties and are
instructed to provide information about a fire event over the
operations radio to assist in mitigating the event.
Preservation of Safe Shutdown Capability
The licensee stated that Fire Area 6N is the Unit 2 Reactor
Building 135' elevation, north side, which is in a separate building
from the Cable Spreading Room, Fire Area 25, which is the location of
the OMA.
OMAs Credited for a Fire in This Area
Action H
The licensee stated that the cables associated with ``B'' RHR are
located in trays and in conduit and that cables for both ``A'' and
``B'' RHR trains cross within 2 feet of each other. However, there are
no high energy ignition sources where cable ZA2Q1280B and a ``B'' RHR
train cable cross and only a small amount of combustibles in the area
overall. Therefore, it is unlikely that a single fire could damage both
the ``A'' train RHR cable and ``B'' RHR cables and necessitate the use
of Action H. Action H, which requires coordination with the control
room, directs an operator to insert a plug-in test switch into Panel
20C032, located in the Cable Spreading Room (Fire Area 25), to bypass
the reactor low pressure permissive for opening MO-2-025A.
In the unlikely event that a fire does damage the pressure
permissive instrumentation circuit for opening MO-2-025A, operators
will be aware of the condition, either by electronic indications in the
Control Room, a smoke detection alarm annunciation in the Control Room,
or physical observation by operators, and will initiate Action H, which
is the only OMA required to achieve hot shutdown for a fire in Fire
Area 6N. Therefore, the Control Room will know immediately if this
action is required and a generic diagnosis time is not necessary.
A fire in Fire Area 6N has the potential to damage cable ZA2Q1280B.
This cable is associated with the pressure permissive circuit needed to
open valve MO-2-10-025A. This valve needs to open to permit injection
of Low Pressure Core Injection (``A'' train RHR) following
depressurization. Fire Area 6N also contains a number of cables
associated with the ``B'' train of RHR. Any number of ``B'' RHR train
cables could be damaged as a result of a fire in Fire Area 6N, so the
licensee's analysis assumed that the ``B'' RHR was considered to be
unavailable for a fire in Fire Area 6N.
NRC Staff Evaluation
Given the limited amount of combustible materials and ignition
sources, it is unlikely that a fire would occur and go unsuppressed by
personnel, and damage the safe shutdown equipment. Even if such
circumstances exist, Action H is available to provide additional
assurance that safe shutdown capability is maintained.
3.4.4 Fire Area 13N (Unit 3 Reactor Building)
Fire Prevention
The licensee stated that limited amounts of Class A combustible
materials, including step-off pads, are present in this area. The three
cables addressed in this area are routed such that they terminate at
either a 480V load center or a motor control center (MCC) cabinet or
both.
Detection, Control, and Extinguishment
The licensee stated that both elevations containing redundant
equipment within Fire Area 13N have smoke detection systems installed
that produce an alarm in the Control Room, but that due to the room
height and steel beams at the ceiling, the spacing of the smoke
detectors on both elevations does not meet the spacing listed in NFPA
72. Although not entirely compliant with NFPA 72, this system is
considered to provide adequate coverage to detect a fire and alert
operators of a fire. Additionally, the licensee stated that a fully
trained onsite fire brigade is provided, which is dispatched via plant
[[Page 19482]]
page in the event of a fire. The fire brigade is composed of plant
operators that are separate from operators assigned safe shutdown
duties and are instructed to provide information about a fire event
over the operations radio to assist in mitigating the event.
Preservation of Safe Shutdown Capability
The licensee stated that the 135' elevation of Fire Area 13N has a
ceiling height of approximately 29' and an approximate floor area of
4,033 square feet and the 165' elevation has a ceiling height of
approximately 29' and an approximate floor area of 6,848 square feet,
so it is unlikely that smoke and heat would accumulate at the height of
the safe shutdown equipment and cause a failure due to fire damage.
OMAs Credited for a Fire in This Area
Action J
The licensee stated that while it is possible that any one of the
three redundant cables located in Fire Area 13N could potentially be
damaged as a result of a fault or failure within its associated 480V
load center or MCC, the impact of a fire on the ability to perform this
action is low since Fire Area 13N is in a separate building with a
separate ventilation system from the E43 4kV Switchgear Room and ample
time is available to complete the action. However, the other installed
fire protection features such as the smoke detection system, cable
conduit, and fire brigade response would likely minimize the impact of
a fire on the cables themselves.
A fire in Fire Area 13N has the potential to damage cables
ZD3B1313A, ZD3A1806A, and ZD3B3983A. The loss of any of these cables
could result in a loss of the normal power supply to the 3DD003 battery
charger. A loss of ZD3B1313A, ZD3A1806A, or ZD3B3983A, would
necessitate a manual action to transfer battery charger 3DD003 to an
alternate power source to within 60 minutes since the batteries can
operate for 60 minutes prior to the initiation of recharging. Battery
charger 3DD003 can also be fed from an alternate power source, which is
routed in separate fire areas, so a single fire cannot damage both the
normal and alternate power feed. Action J is available to transfer the
alternate power supply to the battery charger 3DD003. The action
entails first closing a breaker and then operating a manual transfer
switch. The breaker and manual transfer switch are located in the E43
4kV Switchgear Room (Fire Area 34).
NRC Staff Evaluation
Given the limited amount of combustible materials, ignition
sources, and the large volume of the space, it is unlikely that a fire
would occur and go undetected by the smoke detection system noted above
or unsuppressed by personnel, and damage the safe shutdown equipment.
Even if such circumstances exist, Action J is available to provide
additional assurance that safe shutdown capability is maintained.
3.4.5 Fire Area 26 (Unit 3 MG Set Ventilation Equipment Room)
Fire Prevention
The licensee stated that the primary combustible material in Fire
Area 26 is fire retardant cable insulation and that there are no in
situ ignition sources in the vicinity of the cables.
Detection, Control, and Extinguishment
The licensee stated that in Fire Area 26, there are two ionization
smoke detectors located in the portion of the room containing the
cables of concern, but that the overall detector placement for the fire
area as a whole does not comply with the layout and spacing
requirements of NFPA 72; however, the two smoke detectors are located
in the immediate vicinity of the cables and would provide an alarm of a
fire condition. Additionally, the licensee stated that a fully trained
onsite fire brigade is provided, which is dispatched via plant page in
the event of a fire. The fire brigade is composed of plant operators
that are separate from operators assigned safe shutdown duties and are
instructed to provide information about a fire event over the
operations radio to assist in mitigating the event.
Preservation of Safe Shutdown Capability
The licensee stated that Fire Area 26 has a ceiling height of
approximately 25' and an approximate floor area of 2,100 square feet,
so it is unlikely that smoke and heat would accumulate at the height of
the safe shutdown equipment and cause a failure due to fire damage.
OMAs Credited for a Fire in This Area
Action K
The licensee stated that it is unlikely that Action K will be
necessary because there is reasonable assurance that both of the cables
would not be damaged in the event of a fire in Fire Area 26 since there
are no in situ ignition sources in Fire Area 26 in the vicinity of the
cables, there are no combustible materials, other than fire retardant
cable insulation exposing the two cables, and there are two smoke
detectors provided in the area to notify operators of a fire. In the
event that the action is necessary, the impact of a fire on the ability
to perform this action is low since Fire Area 26N is in a separate
building with a separate ventilation system from the E43 4kV Switchgear
Room and ample time is available to complete the action.
A fire in Fire Area 26 has the potential to damage cables
ZD3B1313A, ZD3A1806A, and ZD3B3983A. The loss of any of these cables
could result in a loss of the normal power supply to the 3DD003 battery
charger. A loss of ZD3B1313A, ZD3A1806A, or ZD3B3983A, would
necessitate a manual action to transfer battery charger 3DD003 to an
alternate power source within 60 minutes since the batteries can
operate for 60 minutes prior to the initiation of recharging. Battery
charger 3DD003 can also be fed from an alternate power source, which is
routed in separate fire areas, so a single fire cannot damage both the
normal and alternate power feed. Action K is available to transfer the
alternate power supply to the battery charger 3DD003. The action
entails first closing a breaker and then operating a manual transfer
switch. The breaker and the manual transfer switch are located in the
E43 4kV Switchgear Room (Fire Area 34).
NRC Staff Evaluation
Given the limited amount of combustible materials, ignition
sources, and the large volume of the space, it is unlikely that a fire
would occur and go undetected by the smoke detection system noted above
or unsuppressed by personnel, and damage the safe shutdown equipment.
Even if such circumstances exist, Action K is available to provide
additional assurance that safe shutdown capability is maintained.
3.4.6 Fire Area 30 (Unit 3 B/D Battery Room)
Fire Prevention
The licensee stated that the combustible loading in this area is
considered to be low with the primary combustible material in this area
being liquid filled plastic battery cases and that there are no cables
in trays in this fire area. Additionally, the potential for hydrogen
buildup due to the battery charging process is mitigated by the
ventilation system in the room. The ventilation system is monitored,
alarmed, and programmatically controlled. The licensee also stated that
there are no significant ignition sources in this area.
[[Page 19483]]
Detection, Control, and Extinguishment
The licensee stated that for Fire Area 30 there are three smoke
detectors located in the room and that the spacing of the detectors is
compliant with NFPA 72 with regard to ceiling height, beam
configuration and air flow. Additionally, two of the three smoke
detectors are located directly above the encapsulated conduits that
contain redundant cables. Additionally, the licensee stated that a
fully trained onsite fire brigade is provided, which is dispatched via
plant page in the event of a fire. The fire brigade is composed of
plant operators that are separate from operators assigned safe shutdown
duties and are instructed to provide information about a fire event
over the operations radio to assist in mitigating the event.
Preservation of Safe Shutdown Capability
The licensee stated that Fire Area 30 has a ceiling height of
approximately 14' and an approximate floor area of 525 square feet, so
it is unlikely that smoke and heat would accumulate at the height of
the safe shutdown equipment and cause a failure due to fire damage.
OMAs Credited for a Fire in This Area
Action M
The licensee stated that it is unlikely that both of the redundant
cables located in Fire Area 30 would be damaged in the event of a fire
in Fire Area 30 since the conduits containing cables ZA3B1014A and
ZA3A1505A are both encapsulated in abandoned Thermo-Lag, the primary
combustible material in the room is liquid filled plastic battery
cases, there are no cable trays or high voltage components located in
the fire area, there are three smoke detectors located in close
proximity to the cables, and the potential for hydrogen release from
the battery charging process is mitigated by the ventilation system
that is monitored for operation and addressed by the Technical
Requirements Manual.
A fire in Fire Area 30 has the potential to damage cables ZA3B1014A
and ZA3A1505A, which the licensee stated are located approximately 16
inches from one another at their closest location. The loss of either
of these cables could result in a loss of the normal power supply to
the 3AD003 battery charger (located in Fire Area 32). A loss of
ZA3B1014A or ZA3A1505A would necessitate a manual action to transfer
battery charger 3AD003 to an alternate power source within 60 minutes
since batteries can operate for 60 minutes prior to the initiation of
recharging. Battery charger 3AD003 can also be fed from an alternate
power source, which is routed in separate fire areas, so a single fire
cannot damage both the normal and alternate power feed. Action M is
available to transfer the alternate power supply to the battery charger
3AD003. The action entails operating a manual transfer switch located
in the E33 4kV Switchgear Room (located in a different fire area).
NRC Staff Evaluation
Given the ventilation system located in the room, limited amount of
combustible materials, lack of ignition sources, and the volume of the
space, it is unlikely that a fire would occur and go undetected by the
smoke detection system noted above or unsuppressed by personnel, and
damage the safe shutdown equipment. Even if such circumstances exist,
Action M is available to provide additional assurance that safe
shutdown capability is maintained.
3.4.7 Fire Area 36 (E42 Switchgear Room)
Fire Prevention
The licensee stated that the cables in this area are qualified to
IEEE 383, or equivalent. The licensee also indicated that there are
several sections of Thermo-Lag in the room. Thermo-Lag is a fire
barrier material that is also considered a combustible. The licensee
determined that this material does not create a credible fire exposure
to the conduit and that the overall combustible material loading for
the area is low. Additionally, Fire Area 36 contains 4kV switchgear
which can create a high energy fault in the event of a failure and is
considered an ignition source. However, the conduit containing the
cables of concern is routed 4 feet horizontally from the front of the
switchgear cabinet, not routed over the switchgear, and is not expected
to be damaged in the event of a switchgear failure. Conduit containing
four cables of concern is routed over two battery chargers, which
convert 480 volt AC into 125 volt DC for the batteries. However, these
chargers are not anticipated to provide a sustained fault current like
a 4kV switchgear, but heat from a failure could expose the conduit and,
therefore, represent an ignition source.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 36 has an NFPA 72-compliant
smoke detection system installed, comprised of six smoke detectors, and
that the room is also provided with a pre-action sprinkler system
designed in accordance with NFPA Standard 13, ``Standard for the
Installation of Sprinkler Systems'' (NFPA 13). Additionally, the
licensee stated that a fully trained onsite fire brigade is provided,
which is dispatched via plant page in the event of a fire. The fire
brigade is composed of plant operators that are separate from operators
assigned safe shutdown duties and are instructed to provide information
about a fire event over the operations radio to assist in mitigating
the event.
Preservation of Safe Shutdown Capability
The licensee stated that Fire Area 36 has a ceiling height of
approximately 14' and an approximate floor area of 525 square feet, so
it is unlikely that smoke and heat would accumulate at the height of
the safe shutdown equipment and cause a failure due to fire damage.
OMAs Credited for a Fire in This Area
Action R
The licensee stated that while it is possible that the redundant
cables located in Fire Area 36 could potentially be damaged by heat
resulting from a battery charger failure, it is unlikely that the
cables within the conduits would be damaged since Fire Area 36 has full
area smoke detection and pre-action sprinkler systems, the conduit is
not routed directly above the 4kV switchgear, the combustible loading
in the room is low consisting primarily of fire retardant cable
insulation and Thermo-Lag, and there are no cable trays routed below
the conduit.
A fire in Fire Area 36 has the potential to damage cables
ZA2A1501E, ZA2A1501F, ZA2A1508E, and ZA2A1508F, which the licensee
stated are routed together in a single conduit, located approximately 9
feet above the floor, for their entire length in Fire Area 36. The loss
of these cables could result in the loss of power to the E12 bus from
the E1 Emergency Diesel Generator. Since Fire Area 36 is the E42 4kV
Switchgear Room, the switchgear in this room is primarily associated
with the B and D electrical trains. Therefore, a fire in this room is
assumed to result in the loss of the components associated with the B
and D trains. In the event that these are lost due to a fire in Fire
Area 36, Action R is available, which directs an operator to enter the
E12 Switchgear Room (located in Fire Area 39) and pull two fuse blocks,
open two breakers by depressing the mechanical breaker trip button and
taking a Main Control Room breaker control switch to ``Close.''
[[Page 19484]]
NRC Staff Evaluation
Given the limited amount of combustible materials and the volume of
the space, it is unlikely that a fire would occur and go undetected by
the smoke detection system noted above or unsuppressed by personnel,
and damage the safe shutdown equipment. Even if such circumstances
exist, Action R is available to provide additional assurance that safe
shutdown capability is maintained.
3.4.8 Fire Area 37 (E22 Switchgear Room)
Fire Prevention
The licensee stated that the cables in this area are qualified to
IEEE 383, or equivalent. Thermo-Lag is also present, but does not
create a credible fire exposure to the conduit. The licensee determined
that this material does not create a credible fire exposure to the
conduit and that the overall combustible material loading for the area
is low. Fire Area 37 also contains 4kV switchgear which can create a
high energy fault in the event of a failure and is considered an
ignition source. However, the conduit containing the cables of concern
is routed 4 feet horizontally from the front of the switchgear cabinet,
not routed over the switchgear, and is not expected to be damaged in
the event of a switchgear failure. Additionally, a bank of 480V MCCs
exposes conduit containing four cables of concern to an exposure hazard
in the event that an MCC fails.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 37 has an NFPA 72-compliant
smoke detection system installed, comprised of three smoke detectors,
and that the room is also provided with a pre-action sprinkler system
designed in accordance with NFPA 13. Additionally, the licensee stated
that a fully trained onsite fire brigade is provided, which is
dispatched via plant page in the event of a fire. The fire brigade is
composed of plant operators that are separate from operators assigned
safe shutdown duties and are instructed to provide information about a
fire event over the operations radio to assist in mitigating the event.
Preservation of Safe Shutdown Capability
The licensee stated that Fire Area 37 has a ceiling height of
approximately 14' and an approximate floor area of 525 square feet, so
it is unlikely that smoke and heat would accumulate at the height of
the safe shutdown equipment and cause a failure due to fire damage.
OMAs Credited for a Fire in This Area
Action S
The licensee stated that while it is possible that the redundant
cables located in Fire Area 37 could potentially be damaged by failure
of the bank of 480V MCCs located below the conduit, it is unlikely that
the cables within the conduits would be damaged since Fire Area 37 has
full area smoke detection and pre-action sprinkler systems, the conduit
is not routed directly above the 4kV switchgear, the combustible
loading in the room is low consisting primarily of fire retardant cable
insulation and Thermo-Lag, and there are no cable trays routed below
the conduit.
A fire in Fire Area 37 has the potential to damage cables
ZA2A1501E, ZA2A1501F, ZA2A1508E, and ZA2A1508F, which the licensee
stated are routed together in a single conduit, located approximately 9
feet above the floor, for their entire length in Fire Area 37. The loss
of these cables could result in the loss of power to the E12 bus from
the E1 Emergency Diesel Generator. Since Fire Area 37 is the E22 4kV
Switchgear Room, the switchgear in this room is primarily associated
with the B and D electrical trains, so a fire in this room is assumed
to result in the loss of the components associated with the B and D
trains. In the event that these are lost due to a fire in Fire Area 36,
Action R is available, which directs an operator to enter the E12
Switchgear Room (located in Fire Area 39) and pull two fuse blocks,
open two breakers by depressing the mechanical breaker trip button and
taking a Main Control Room breaker control switch to ``Close.''
NRC Staff Evaluation
Given the limited amount of combustible materials and the volume of
the space, it is unlikely that a fire would occur and go undetected by
the smoke detection system noted above or unsuppressed by personnel,
and damage the safe shutdown equipment. Even if such circumstances
exist, Action S is available to provide additional assurance that safe
shutdown capability is maintained.
3.4.9 Fire Area 43 (E-4 Emergency Diesel Generator Room)
Fire Prevention
The licensee stated that other than the diesel fuel and lube oil in
the EDG Rooms, the combustible material loading is considered to be
low. The fuel oil day tank is located within the fire area, but in a
separate room with heavy concrete walls and a 3-hour Underwriters
Laboratory (UL)-listed fire door. Additionally, failure of an operating
diesel generator represents a significant ignition source. There are
also high voltage electrical components associated with the generator
in the room. However, these ignition sources are only credible when the
diesel is in operation. During routine diesel operations, an equipment
operator is stationed in the room to monitor the diesel and would be
available to immediately suppress any small fires that occurred, or to
secure the diesel if a significant malfunction occurred.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 43 has eight heat detectors
installed that annunciate an alarm in the Control Room and that the
room also has a manually-actuated carbon dioxide (CO2) fire
suppression system installed. Additionally, the licensee stated that a
fully trained on-site fire brigade is provided, which is dispatched via
plant page in the event of a fire. The fire brigade is composed of
plant operators that are separate from operators assigned safe shutdown
duties and are instructed to provide information about a fire event
over the operations radio to assist in mitigating the event.
Preservation of Safe Shutdown Capability
The licensee stated that the emergency diesel generator rooms are
located in a separate building from the rest of the plant and that each
of the emergency diesel generators are separated from one another with
a three-hour rated fire barrier. Additionally, the OMA for this area is
performed in the E42 Switchgear room, Fire Area 36, which is located in
the turbine building.
OMAs Credited for a Fire in This Area
Action T
The licensee stated that while it is possible that the redundant
cables in Fire Area 43 could potentially be damaged by a lube or fuel
oil fire, it is unlikely that the cables within the conduits would be
damaged since they are located in conduit that is embedded in the floor
slab for much of the length they are in Fire Area 43, and there would
have to be a sufficient amount of oil present on the floor which then
spreads across the floor to expose the control panels. Even if these
two circumstances occur, a manually-actuated CO2 fire
suppression system is available to extinguish any fires in the area.
A fire in Fire Area 43 has the potential to damage cables ZD2A1807E
or ZD2A1807H, which the licensee stated are located in conduits
embedded in the concrete floor slab, control
[[Page 19485]]
panels, and a junction box. Failure of these cables via a hot short
could cause the Unit 2 emergency diesel generator breaker to close into
the E42 bus, either out of phase or not running, which would cause a
protective trip of the E42 bus. This could result in a loss of the
normal power supply to the 2DD003 battery charger. The battery charger
is needed to maintain long term DC power through the station batteries.
The batteries can operate for 60 minutes prior to the initiation of
recharging. Battery charger 2DD003 can also be fed from an alternate
power source, which is routed in separate fire areas, so a single fire
cannot damage both the normal and alternate power feed. Action T is
available to transfer the alternate power supply to the battery charger
2DD003 (located in Fire Area 36). The action entails operating a manual
transfer switch located in the E42 4kV Switchgear Room which is a
separate fire area in a separate building.
NRC Staff Evaluation
Given the limited amount of combustible materials and monitoring of
credible ignition sources in this area, it is unlikely that a fire
would occur and go undetected by the heat detection system or
unsuppressed by the suppression system noted above or by personnel, and
damage the safe shutdown equipment. Even if such circumstances exist,
Action T is available to provide additional assurance that safe
shutdown capability is maintained.
3.4.10 Fire Area 50 (Turbine Building)
Fire Prevention
The licensee stated that limited amounts of Thermo-Lag and various
Class A combustible materials are present in the fire area. The
licensee also stated that the room containing the cables of concern
contains two rows of 13kV switchgear cabinets, which would be capable
of exposing the cables in the event of a 13 kV switchgear failure.
Detection, Control, and Extinguishment
The licensee stated that Fire Area 50 includes most of the Unit 2
and Unit 3 Turbine Building and as such is a large fire area including
several rooms located on multiple elevations. However, the cables of
concern with regard to the associ