Energy Efficiency Program for Certain Commercial and Industrial Equipment: Test Procedures for Commercial Refrigeration Equipment, 71596-71613 [2010-29210]
Download as PDF
71596
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
[FR Doc. 2010–28793 Filed 11–23–10; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF ENERGY
10 CFR Part 431
[Docket No. EERE–2010–BT–TP–0034]
RIN 1904–AC40
Energy Efficiency Program for Certain
Commercial and Industrial Equipment:
Test Procedures for Commercial
Refrigeration Equipment
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Notice of proposed rulemaking
and public meeting.
AGENCY:
The U.S. Department of
Energy (DOE) proposes amendments to
its test procedure for commercial
refrigeration equipment (CRE). The
amendments would update the
referenced industry test procedures to
the most current version, incorporate
methods to evaluate the energy impacts
resulting from the use of night curtains
and lighting occupancy sensors, and
allow testing of certain commercial
refrigerators at their lowest application
product temperature. These test
procedures will apply to commercial
refrigerators, freezers, and refrigeratorfreezers, as defined in the Energy Policy
and Conservation Act of 1975 (EPCA),
as amended. Use of any amended test
procedures will be required on the
compliance date of any standards
developed in the associated energy
conservation standard rulemaking. DOE
will hold a public meeting to receive
and discuss comments on the proposal.
DATES: DOE will hold a public meeting
in Washington, DC on Thursday,
January 6, 2011, from 9 a.m. to 4 p.m.
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
SUMMARY:
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
Additionally, DOE plans to conduct the
public meeting via webinar. DOE will
accept comments, data, and other
information regarding this notice of
proposed rulemaking (NOPR) before or
after the public meeting, but no later
than January 24, 2011. See section V,
‘‘Public Participation,’’ of this NOPR for
details.
You can attend the public meeting via
webinar, and registration information,
participant instructions, and
information about the capabilities
available to webinar participants will be
published on the following Web site:
https://www1.gotomeeting.com/join/
638471849. Participants are responsible
for ensuring their systems are
compatible with the webinar software.
The purpose of the meeting is to
receive comments and to help DOE
understand potential issues associated
with this proposed rulemaking. DOE
must receive requests to speak at the
meeting before 4 p.m., Thursday,
December 22, 2010. DOE must receive a
signed original and an electronic copy
of statements to be given at the public
meeting before 4 p.m., Thursday,
December 29, 2010.
ADDRESSES: The public meeting will be
held at the U.S. Department of Energy,
Forrestal Building, Room 1E–245, 1000
Independence Avenue, SW.,
Washington, DC 20585–0121. Please
note that foreign nationals planning to
participate in the public meeting are
subject to advance security screening
procedures which require advance
notice of 30 days prior to attendance of
the public meeting. If a foreign national
wishes to participate in the public
meeting, please inform DOE of this fact
as soon as possible by contacting Ms.
Brenda Edwards at (202) 586–2945 so
that the necessary procedures can be
completed.
Interested parties may submit
comments, identified by docket number
EERE–2010–BT–TP–0034 or Regulation
Identifier Number (RIN) 1904–AC40, by
any of the following methods:
• Federal eRulemaking Portal: https://
www.regulations.gov. Follow the
instructions for submitting comments.
PO 00000
Frm 00030
Fmt 4702
Sfmt 4702
high-frequency ballasts and 0.9 for lowfrequency ballasts.
7.3. Calculate Power Factor (PF).
• E-mail: CRE–2010–TP–
0034@ee.doe.gov. Include the docket
number EERE–2010–BT–TP–0034 and/
or RIN 1904–AC40 in the subject line of
the message.
• Postal Mail: Ms. Brenda Edwards,
U.S. Department of Energy, Building
Technologies Program, Mailstop EE–2J,
1000 Independence Avenue, SW.,
Washington, DC 20585–0121. Please
submit one signed paper original.
• Hand Delivery/Courier: Ms. Brenda
Edwards, U.S. Department of Energy,
Building Technologies Program, 6th
Floor, 950 L’Enfant Plaza, SW.,
Washington, DC 20024. Telephone:
(202) 586–2945. Please submit one
signed paper original.
Written comments regarding the
burden-hour estimates or other aspects
of the collection-of-information
requirements contained in this proposed
rule may be submitted to Office of
Energy Efficiency and Renewable
Energy through the methods listed
above and by e-mail to
Christine_J._Kymn@omb.eop.gov.
Instructions: All submissions must
include the docket number or RIN for
this rulemaking. For detailed
instructions on submitting comments
and additional information on the
rulemaking process, see section V,
‘‘Public Participation,’’ of this document.
Docket: For access to the docket to
read background documents or
comments received, visit the U.S.
Department of Energy, 6th Floor, 950
L’Enfant Plaza, SW., Washington, DC
20024, (202) 586–2945, between 9 a.m.
and 4 p.m., Monday through Friday,
except Federal holidays. Please call Ms.
Brenda Edwards at (202) 586–2945 for
additional information regarding
visiting the Resource Room.
FOR FURTHER INFORMATION CONTACT: Mr.
Charles Llenza, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies, EE–2J, 1000
Independence Avenue, SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–2192,
Charles_Llenza@ee.doe.gov. In the
Office of General Council contact Mr.
E:\FR\FM\24NOP1.SGM
24NOP1
EP24NO10.388
Where:
Ballast input power is determined in
accordance with section 6.2.6, input
voltage is determined in accordance with
section 6.2.7, and input current in
determined in accordance with section
6.2.8.
ballast as determined by section 6.2.5,
ballast input power is as determined by
section 6.2.6, and b is equal to 1.0 for
EP24NO10.387
Where:
Total Lamp Arc Power is the sum of the lamp
arc powers for all lamps operated by the
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
Michael Kido, U.S. Department of
Energy, Office of General Counsel,
GC–71, 1000 Independence Avenue,
SW., Washington, DC 20585–0121, (202)
586–8145, Michael.Kido@hq.doe.gov; or
Ms. Elizabeth Kohl, U.S. Department of
Energy, Office of General Counsel,
GC–71, 1000 Independence Avenue,
SW., Washington, DC 20585–0121, (202)
586–7796, Elizabeth.Kohl@hq.doe.gov.
For information on how to submit or
review public comments and on how to
participate in the public meeting,
contact Ms. Brenda Edwards, U.S.
Department of Energy, Office of Energy
Efficiency and Renewable Energy,
Building Technologies Program, EE–2J,
1000 Independence Avenue, SW.,
Washington, DC 20585–0121.
Telephone (202) 586–2945. E-mail:
Brenda.Edwards@ee.doe.gov.
SUPPLEMENTARY INFORMATION:
I. Authority and Background
A. Authority
B. Background
C. Standby Mode and Off Mode
II. Summary of the Proposed Rule
III. Discussion
A. Framework Comment Summary and
DOE Responses
1. Coordination With Other Programs
2. Coordination With the Air-Conditioning,
Heating and Refrigeration Institute
3. Burden of Testing
4. Testing of Transient Technologies and at
Variable Refrigeration Load
5. Rating Temperatures
6. Energy Efficiency Features
B. Summary of the Test Procedure
Revisions
1. Update References to Industry Test
Procedures to Most Current Versions
2. Include Method for Determining Energy
Savings Due to the Use of Night Curtains
on Open Cases
3. Include Calculation for Determining
Energy Savings Due to Use of Lighting
Occupancy Sensors or Controls
4. Include Provision for Testing at Lowest
Application Product Temperature.
IV. Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the National
Environmental Policy Act
C. Review Under the Regulatory Flexibility
Act
D. Review Under the Paperwork Reduction
Act
E. Review Under the Unfunded Mandates
Reform Act of 1995
F. Review Under the Treasury and General
Government Appropriations Act, 1999
G. Review Under Executive Order 13132
H. Review Under Executive Order 12988
I. Review Under the Treasury and General
Government Appropriations Act, 2001
J. Review Under Executive Order 13211
K. Review Under Executive Order 12630
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
V. Public Participation
A. Attendance at Public Meeting
B. Procedure for Submitting Requests to
Speak
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
C. Conduct of Public Meeting
D. Submission of Comments
E. Issues on Which DOE Seeks Comment
VI. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III of EPCA (42 U.S.C. 6291 et
seq.) as amended by the Energy Policy
Act of 2005 (EPACT 2005) establishes
an energy conservation program for
certain commercial and industrial
equipment (42 U.S.C. 6311–6317). EPCA
prescribes energy conservation
standards for certain self-contained
commercial refrigerators, freezers, and
refrigerator-freezers with solid or
transparent doors and designed for a
pull-down or holding temperature
application. (42 U.S.C. 6313(c)(2)–(3))
EPCA also requires DOE to develop
standards for ice-cream freezers; selfcontained commercial refrigerators,
freezers, and refrigerator-freezers
without doors; and remote condensing
commercial refrigerators, freezers, and
refrigerator-freezers. (42 U.S.C.
6313(c)(4)(A)) DOE published a final
rule establishing standards for these
equipment classes on January 9, 2009.
74 FR 1091.
Manufacturers of covered equipment,
including commercial refrigeration
equipment, must use prescribed test
procedures to measure energy efficiency
or use and certify to DOE that
equipment complies with energy
conservation standards. (42 U.S.C.
6311(3) and (4)) The current test
procedures for commercial refrigeration
equipment appear under Title 10 of the
Code of Federal Regulations (CFR) part
431, subpart C.
EPCA requires DOE to conduct an
evaluation of each class of covered
equipment at least once every 7 years to
determine whether to, among other
things, amend the test procedures for
such equipment. Any amended test
procedures must be reasonably designed
to produce test results that reflect
energy efficiency, energy use, and
estimated operating costs during a
representative average use cycle and
must not be unduly burdensome to
conduct. (42 U.S.C. 6314(a)(2))
In addition, EPCA contains specific
provisions relating to test procedures for
commercial refrigeration equipment.
Test procedures for commercial
refrigerators, freezers, and refrigeratorfreezers must be: (1) The test procedures
determined to be generally accepted
industry testing procedures; or (2) rating
procedures developed or recognized by
the American Society of Heating,
Refrigerating and Air-Conditioning
Engineers (ASHRAE) or by the
American National Standards Institute
PO 00000
Frm 00031
Fmt 4702
Sfmt 4702
71597
(ANSI). (42 U.S.C. 6314(a)(6)(A)(i))
EPCA also establishes initial test
procedures for self-contained
refrigerators, freezers, and refrigeratorfreezers with doors. These test
procedures are the ASHRAE 117 test
procedures that went into effect on
January 1, 2005. (42 U.S.C.
6314(a)(6)(A)(ii))
If ASHRAE 117 is amended, however,
the Secretary must, by rule, amend the
DOE test procedure to ensure
consistency with the amended ASHRAE
117 unless certain findings are made by
clear and convincing evidence. In
addition, if a test procedure other than
ASHRAE 117 is approved by ANSI, the
Secretary must review the relative
strengths and weaknesses of the new
test procedure relative to the ASHRAE
117 test procedure and, based on that
review, adopt one new test procedure
for use in the standards program. (42
U.S.C. 6314(a)(6)(E)–(F))
In 2006 DOE published a final rule
that adopted ANSI/Air-Conditioning
and Refrigeration Institute (ARI)
Standard 1200–2006 (hereafter
referenced as ARI Standard 1200–2006)
as the referenced test procedure for
measuring energy consumption and
ANSI/Association of Home Appliance
Manufacturers (AHAM) Standard HRF–
1–2004 (hereafter referred to as AHAM
HRF–1–2004) for measuring refrigerated
compartment volume. 71 FR 71370.
These industry standards for
commercial refrigeration equipment
have since been updated from the
procedures currently referenced in the
regulations. As stated previously, EPCA
authorizes DOE to review the merits of
the updated industry test procedures. If
DOE determines that a test procedure
amendment is warranted, DOE must
publish proposed test procedures and
offer the public an opportunity to
present oral and written comments on
the amendment. (42 U.S.C. 6314(b))
B. Background
ASHRAE Standard 117–2002,
‘‘Method of Testing Closed
Refrigerators,’’ was the test procedure for
commercial refrigeration equipment for
which standards were specified in
EPACT 2005. EPACT 2005 mandated
use of the ASHRAE 117 standard in
effect on January 1, 2005. (42 U.S.C.
6314(a)(6)(A)(ii)) Subsequently,
ASHRAE amended this test procedure
and adopted ASHRAE Standard 72–
2005, ‘‘Method of Testing Commercial
Refrigerators and Freezers,’’ which was
approved by ANSI on July 29, 2005.
DOE reviewed ASHRAE Standard 72–
2005, as well as ARI Standard 1200–
2006, which was approved by ANSI on
August 28, 2006. (42 U.S.C.
E:\FR\FM\24NOP1.SGM
24NOP1
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
71598
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
6314(a)(6)(E)–(F)) DOE determined that
ARI Standard 1200–2006 includes the
test procedures in ASHRAE Standard
72–2005 as well as the rating
temperatures prescribed in EPACT
2005. As a result, DOE published a final
rule on December 8, 2006 in which it
adopted ARI Standard 1200–2006,
‘‘Performance Rating of Commercial
Refrigerated Display Merchandisers and
Storage Cabinets,’’ as the DOE test
procedure for commercial refrigeration
equipment. 71 FR 71370; 10 CFR
431.63–431.64. ARI Standard 1200–
2006 contains rating temperature
specifications of 38 degrees Fahrenheit
(°F) (±2 °F) for commercial refrigerators
and refrigerator compartments, 0 °F (±2
°F) for commercial freezers and freezer
compartments, and ¥5 °F (±2 °F) for
commercial ice-cream freezers. In the
test procedure final rule, DOE adopted
a ¥15 °F (±2 °F) rating temperature for
commercial ice-cream freezers, rather
than the ¥5 °F (±2 °F) prescribed in the
ARI Standard 1200–2006. During the
2006 test procedure rulemaking, DOE
determined that testing at a ¥15 °F (±2
°F) rating temperature was more
representative of the actual energy
consumption of commercial freezers
specifically designed for ice cream
application. 71 FR 71357. In addition,
DOE adopted AHAM Standard HRF–1–
2004, ‘‘Energy, Performance and
Capacity of Household Refrigerators,
Refrigerator-Freezers and Freezers,’’ for
measuring compartment volumes for
equipment covered under this rule. 71
FR 71370 (Dec. 8, 2006).
Since the publication of the final rule,
ARI has merged with the Gas Appliance
Manufacturers Association (GAMA) to
form the Air-Conditioning, Heating and
Refrigeration Institute (AHRI) and
updated its test procedure, the most
recent version of which is AHRI
Standard 1200–2010. AHRI Standard
1200–2010 includes changes to the
equipment class nomenclature used in
the test procedure, the method of
normalizing equipment energy
consumption, the ice-cream freezer test
temperature, and other minor
differences. These changes aligned the
AHRI test procedure with the
nomenclature and methodology used in
DOE’s 2009 standards rulemaking on
commercial refrigeration equipment.
DOE proposes to reference AHRI 1200–
2010, the test procedure currently used
in industry.
Similarly, AHAM has updated
Standard HRF–1–2004 to the most
recent version, AHAM HRF–1–2008.
The changes to this standard are mostly
editorial and involved reorganizing
some of the sections for simplicity and
usability. As part of the reorganization,
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
the HRF–1–2004 section numbers that
are referenced within the DOE test
procedure were updated to the structure
in HRF–1–2008. However, the content
of those sections was not substantially
changed. The newly updated AHRI
Standard 1200–2010 references the most
recent version of the AHAM standard,
AHAM HRF–1–2008. As such, DOE
proposes to update the referenced test
procedure to adopt AHAM HRF–1–2008
as the prescribed method for
determining refrigerated compartment
volume.
DOE also proposes changes to the test
procedure to better address certain
energy efficiency features for which the
current test procedure cannot account.
During the 2009 energy conservation
standards rulemaking, DOE screened
out several energy efficiency
technologies because their effects were
not captured by the current test
procedure. 72 FR 41162, 41179–80 (July
26, 2007). DOE proposes modifications
to its test procedure to better address
some of these technologies. Specific
changes include provisions for
measuring the impact of night curtains
and lighting occupancy sensors and
controls.
On May 18, 2010, DOE held a public
meeting (the May 2010 Framework
public meeting) to discuss the
rulemaking framework for the
concurrent commercial refrigeration
equipment (CRE) energy conservation
standard (docket number EERE–2010–
BT–STD–0003). During this May 2010
Framework public meeting, DOE
received comments from several
interested parties that additional rating
temperatures should be considered in
the test procedure. Some equipment is
designed for storing goods such as wine,
candy, and flowers at temperatures that
are held constant, but are higher than
the temperatures typically used in
commercial refrigerators. The
commenters stated that some covered
refrigeration equipment designed for
operation at higher temperatures is not
able to be tested at the prescribed 38 °F,
and they suggested that DOE consider
this in the test procedures and standards
rulemakings. Consequently, DOE
proposes provisions for testing
commercial refrigeration equipment that
is designed to operate at temperatures
higher than 38 °F at the lowest possible
application product temperature.
C. Standby Mode and Off Mode
The Energy Independence and
Security Act of 2007 (EISA 2007; Pub.
L. 110–140) amended EPCA to require
DOE, for each covered product for
which current test procedures do not
account for standby and off mode
PO 00000
Frm 00032
Fmt 4702
Sfmt 4702
energy consumption, to modify the test
procedures to integrate such energy
consumption into the energy
descriptor(s) for that product, if
technically feasible. Otherwise, DOE
must prescribe a separate standby and
off mode energy use test procedure, if
technically feasible. (42 U.S.C.
6295(gg)(2)(A)) EISA 2007 also requires
any final rule to establish or revise a
standard for a covered product, adopted
after July 1, 2010, to incorporate standby
mode and off mode energy use into a
single amended or new standard, if
feasible. (42 U.S.C. 6295(gg)(3)(A)) DOE
currently believes that the ‘‘off mode’’
and ‘‘standby mode’’ conditions of
operation do not apply to the equipment
covered by this rulemaking because the
provision within EISA which stipulates
that off mode and standby mode energy
usage must be quantified only appears
in relation to consumer products and is
not required for commercial equipment.
Additionally, commercial refrigeration
equipment, whether in retail,
foodservice, or other applications,
operates 24 hours a day, 7 days a week
to maintain product at the necessary
temperature for safe storage or retailing.
Therefore, standby and off modes will
not be considered for commercial
refrigeration equipment.
II. Summary of the Proposed Rule
DOE is considering modifications to
its test procedure to incorporate the
current industry-accepted test
procedures, address certain energy
efficiency features that currently are not
accounted for in the test procedure
(light occupancy sensors and night
curtains), and allow testing of
commercial refrigeration equipment that
cannot be tested at one of the three
currently specified product test
temperatures.
EPCA prescribes that if any
rulemaking amends a test procedure,
DOE must determine ‘‘to what extent, if
any, the proposed test procedure would
alter the measured energy efficiency
* * * of any covered product as
determined under the existing test
procedure.’’ (42 U.S.C. 6293(e)(1);
6314(a)(6)) Further, if DOE determines
that the amended test procedure would
alter the measured efficiency of a
covered product, DOE must amend the
applicable energy conservation standard
accordingly. (42 U.S.C. 6293(e)(2);
6314(a)(6)) DOE recognizes that the
proposed test procedure amendments
would affect the measured energy use of
commercial refrigeration equipment.
DOE is considering amending the
standards currently in effect for
commercial refrigeration equipment in a
concurrent rulemaking. DOE will
E:\FR\FM\24NOP1.SGM
24NOP1
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
consider these proposed test procedure
amendments as any final energy
conservation standards are developed.
DOE also proposes to require use of
any amended test procedures to be
consistent with the compliance date of
any revised energy conservation
standards. DOE would add language to
any final test procedure amendments to
the effect that the amendments need not
be performed at that time to determine
compliance with the current energy
conservation standards. Instead,
manufacturers would be required to use
the amended test procedures to
demonstrate compliance with DOE’s
energy conservation standards on the
compliance date of any final rule
establishing amended energy
conservation standards for commercial
refrigeration equipment.
Further clarification would also be
provided that, as of 360 days after
publication of any test procedure final
rule, representations as to the energy
consumption of any covered products
would need to be based on results
generated using the amended test
procedure. (42 U.S.C. 6314(d))
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
III. Discussion
As part of the current rulemaking on
the energy conservation standard for
commercial refrigeration equipment,
DOE held a public meeting on May 18,
2010 to present its framework document
(https://www1.eere.energy.gov/buildings/
appliance_standards/commercial/pdfs/
cre_framework_04–30–10.pdf and to
receive comments from interested
parties. DOE considered the comments
received as a result of the framework
document public meeting and
incorporated recommendations, where
appropriate, that applied to the test
procedure.
In Section 0, DOE provides responses
to comments in the following subject
areas:
1. Coordination With Other Programs;
2. Coordination with AHRI;
3. Burden of Testing;
4. Transient Testing;
5. Rating Temperatures; and
6. Energy Efficiency Features.
Section III.B provides a summary of
the proposed revisions to the test
procedure at 10 CFR part 431, subpart
C, ‘‘Uniform test method for measuring
the energy consumption of commercial
refrigerators, freezers, and refrigeratorfreezers.’’ These proposed revisions
include:
1. Update References to Industry Test
Procedures to Most Current Version;
2. Include Method for Determining
Energy Savings Due to the Use of Night
Curtains on Open Cases;
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
3. Include Calculation for
Determining Energy Savings Due to Use
of Lighting Occupancy Sensors or
Controls;
4. Include Provision for Testing at
Lowest Application Product
Temperature.
Comments relevant to these subject
areas are also addressed in section III.B.
A. Framework Comment Summary and
DOE Responses
1. Coordination With Other Programs
During the Framework public
meeting, DOE received several
comments regarding the potential
overlap between testing performed for
the purposes of compliance with DOE
standards and testing performed for
certification for voluntary energy
efficiency programs. Continental stated
that testing requirements should be
unified between ENERGY STAR® and
DOE standards. (Continental, No.
1.2.006 at p. 190 1) Continental also
stated that a common database of
certified equipment should be shared
between DOE and the U.S.
Environmental Protection Agency
ENERGY STAR program. (Continental,
No. 1.2.006 at pp. 190¥191)
The use of common test procedures,
reporting, and test data repository
pertains to many commercial and
residential products, including
commercial refrigeration equipment.
ENERGY STAR currently requires
testing according to ASHRAE Standard
72–2005. ASHRAE Standard 72–2005 is
referenced as the method of test in ARI
Standard 1200–2006, DOE’s current
referenced test procedure, as well as
AHRI Standard 1200–2010, which DOE
proposes to incorporate by reference in
today’s test procedure. As a result, DOE
believes that testing according to ARI
standard 1200–2006 or 1200–2010
would be sufficient for purposes of
ENERGY STAR certification.
DOE acknowledges that
manufacturers may have to submit
separate reports for showing compliance
with ENERGY STAR and DOE energy
conservation standards. Reporting
requirements for the purposes of
certification and compliance with DOE
1 In the following discussion, comments will be
presented along with a notation in the form
‘‘Continental, No. 1.2.006 at p. 190,’’ which
identifies a written comment DOE received and
included in the docket of this rulemaking. DOE
refers to comments based on when the comment
was submitted in the rulemaking process. Section
1.1.XXX refers to Federal Register documents,
section 1.2.XXX refers public meeting support
documents, and 1.3.XXX refers to comments
submitted by interested parties. This particular
notation refers to a comment (1) By Continental, (2)
in document number 6 in the public meeting
support materials, and (3) appearing on page 190.
PO 00000
Frm 00033
Fmt 4702
Sfmt 4702
71599
energy conservation standards are
currently being addressed under a
separate rulemaking (docket number
EERE–2010–BT–STD–0003). DOE
believes that further analysis or effort to
coordinate a common database or other
aspects with the ENERGY STAR
program pertain to many covered
products, both commercial and
residential, and should be addressed in
the context of that rulemaking rather
than this test procedure rulemaking.
2. Coordination with the AirConditioning, Heating and Refrigeration
Institute
Many interested parties provided DOE
with comments regarding coordination
between DOE and AHRI in the
development of test procedures. AHRI
reminded stakeholders that AHRI
Standard 1200, which is referenced in
the DOE test procedure, is under
constant review, and invited interested
parties, including DOE, to participate in
this review. (AHRI, No. 1.2.006 at p. 71,
No. 1.3.008 at p. 3) AHRI also expressed
support for DOE’s plan to adopt the
2008 version of AHRI Standard 1200.
(AHRI, No. 1.3.008 at p. 3) Similarly,
DOE was encouraged to participate in
the ASHRAE and AHRI standards
revision processes to ensure continuity
between Federal and industry
standards. (True, No. 1.2.006 at p. 72)
California Codes and Standards likewise
agreed that DOE should coordinate with
AHRI to update AHRI Standard 1200.
(California Codes and Standards, No.
1.3.005 at pp. 2–3) A joint comment
submitted by the Northwest Energy
Efficiency Alliance and the Northwest
Power and Conservation Council
(Northwest Joint Comment) agreed with
the use of AHRI Standard 1200 as the
basis for testing, but urged DOE to begin
updating its own test procedure in
parallel with its efforts to clarify
equipment classes. (Adjuvant
Consulting, No. 1.3.003 at p. 3) Further,
the Northwest Joint Comment stated
that AHRI Standard 1200 will need
updating for this rulemaking because it
excludes some equipment classes, may
not have universally applicable test
conditions, and is unable to quantify the
effects of some technology options. The
Northwest Joint Comment also stated
that AHRI Standard 1200 should be
modified to capture the impacts of all
technologies considered by DOE in the
rulemaking and appropriate operating
regimes. (Adjuvant Consulting, No.
1.3.003 at pp. 2–3)
During the development of these
proposed test procedures amendments,
DOE closely followed the activities of
engineering committees that oversee
AHRI Standard 1200 and ASHRAE
E:\FR\FM\24NOP1.SGM
24NOP1
71600
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
Standard 72 and will continue to stay
abreast of AHRI and ASHRAE efforts to
revise and update their respective test
procedures and standards. In the
interest of coordinating with AHRI, DOE
proposes to update the references in the
DOE test procedure to the most recent
version of AHRI Standard 1200, AHRI
Standard 1200–2010. DOE also proposes
to amend aspects of this testing protocol
as part of the DOE procedure to capture
the performance of certain energy
efficiency features, as described in
section III.B. Regarding equipment
classes that may be excluded from AHRI
Standard 1200, DOE believes that all
equipment classes for which DOE
intends to set standards are able to be
tested using AHRI Standard 1200–2010.
Also, DOE believes the test conditions
currently prescribed in AHRI Standard
1200–2010 are applicable to all
commercial refrigeration equipment
covered under this rulemaking with the
exception of equipment that cannot be
tested at the 38 °F integrated average
product temperature, see further
discussion in sections III.A.5 and III.B.4.
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
3. Burden of Testing
During the Framework public
meeting, and in written comments,
several interested parties expressed
concern regarding the burden of testing.
Master-Bilt stated that transitioning to a
system of third-party testing would
more than double its testing costs.
(Master-Bilt, No. 1.2.006 at p. 200) Zero
Zone commented that changes to the
test procedure would make existing test
data invalid, would possibly require
multiple tests at different
configurations, and would increase
costs. (Zero Zone, No. 1.3.007 at p. 1)
True expressed a concern that there is
a learning curve associated with how to
test equipment at standard conditions
(True, No. 1.2.006 at pp. 133–134) and
that introducing additional test
conditions would significantly increase
the cost and burden of testing. (True,
No. 1.2.006 at pp. 131–132)
DOE understands that amending test
procedures or including additional
provisions in those test procedures
could increase the burden on
manufacturers to quantify the
performance of their equipment. EPCA
requires that the test procedures
promulgated by DOE be reasonably
designed to produce test results that
reflect energy efficiency, energy use,
and estimated operating costs of the
covered equipment during a
representative average use cycle. It also
requires that the test procedure not be
unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
DOE has analyzed the expected
incremental cost of the proposed test
procedure changes and its impact on
manufacturers. The proposed changes to
the test procedure consist of: Updating
the referenced industry test procedures
to the most current versions; testing
requirements for units sold with night
curtains and lighting occupancy sensors
or controls installed; and provisions for
testing units that cannot operate at the
specified 38 °F integrated average
product temperature.
All commercial refrigeration
equipment for which standards were set
in EPACT 2005 are currently required to
be tested using the DOE test procedure
to show compliance with the EPACT
2005 standard levels. Equipment for
which standards were set in the 2009
final rule will similarly be required to
test units using the DOE test procedure
to show compliance with the 2009
standards levels beginning January 1,
2012. The current DOE test procedure
references AHRI Standard 1200–2006
and AHAM HRF–1–2004. This test
procedure consists of one 24-hour test at
standard rating conditions to determine
daily energy consumption.
The updated versions of AHRI
Standard 1200–2010 and AHAM HRF–
1–2008 do not vary substantially from
the previously referenced versions.
Aligning the DOE test procedure with
the most recent industry test procedures
currently in use—AHRI standard 1200–
2010 and AHAM HRF–1–2008—will
simplify testing requirements and
reduce the burden of testing for both
small and large manufacturers.
For equipment that could be sold with
night curtains installed, the current test
procedure requires one 24-hour test
without the night curtain installed. To
minimize the additional burden of test
on manufacturers, under the proposed
revisions, if a unit is tested and shows
compliance with the relevant energy
conservation standard without night
curtains installed, that unit can also be
sold with night curtains installed
without additional testing. In addition,
if a manufacturer chose to sell cases
only with night curtains installed, only
one 24-hour test would be required. If,
however, a piece of equipment does not
meet DOE’s energy conservation
standards without night curtains
installed, DOE proposes to allow the
unit to be tested a second time with
night curtains installed. In this instance,
assuming the energy conservation
standard is met, the case would also be
required to be sold with night curtains
installed. This would require an
increased burden of test on only those
units that cannot show compliance with
DOE energy conservation standards
PO 00000
Frm 00034
Fmt 4702
Sfmt 4702
without night curtains installed. As
DOE proposes to incorporate provisions
for testing a unit with night curtains
installed into the same 24-hour test, the
burden of conducting the test with and
without night curtains is approximately
the same.
For units sold with lighting
occupancy sensors and scheduled
controls installed, no additional testing
or measurements will be required.
Manufacturers will use a calculation
method to determine the energy savings
due to lighting occupancy sensors and
scheduled controls. DOE believes that
additional calculations will only require
a few additional minutes of testing time,
which represents approximately a 25percent increase in the calculation
intensity of the test. When compared to
the physical testing segment of the
procedure, which takes, a minimum of
24 hours, the additional calculations
required by the lighting occupancy
sensor and scheduled control
requirements would increase the total
burden of the test by less than an
estimated 0.01 percent. In addition, this
additional burden would be required
only for units that cannot comply with
the energy conservation standard with
lighting occupancy sensors or controls
installed. Thus, DOE believes that the
proposed additional calculations for
lighting occupancy sensors and controls
would not significantly increase the
burden of test for manufacturers of
covered products.
For equipment that cannot be tested at
the 38 °F integrated average product
temperature, manufacturers are
currently required to test the unit using
AHRI Standard 1200 at the 38 °F test
temperature. Under the proposed
revisions, these manufacturers would be
allowed to test units that cannot meet
the 38 °F test temperature to be tested
at the lowest application product
temperature, with the only difference
being the integrated average product
temperature. Since the same test is
being performed in both cases, DOE
believes that this will not increase the
burden of test for those manufacturers
and is likely to lead to more
representative energy consumption
values. DOE notes that AHRI Standard
1200–2010 test is often already
performed by a manufacturer for
participation in voluntary programs,
independent collection of energy
consumption information, or other
reasons.
The proposed changes to the test
procedure for commercial refrigeration
equipment were chosen to help
minimize the impact of additional
testing while updating industry
standards to reflect the most current
E:\FR\FM\24NOP1.SGM
24NOP1
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
versions, capture new energy efficiency
technologies, and provide more accurate
test procedures for equipment that
cannot be tested at the currently
prescribed integrated average product
temperature. For the reasons stated
above, DOE believes that the proposed
test procedures would not be unduly
burdensome to conduct.
For further discussion of the
economic impact of additional testing
on the small CRE manufacturers, as the
entities that would be the most
impacted from additional testing
requirements, please see section IV.C of
today’s NOPR.
DOE requests comment on its
conclusion that the proposed test
procedure changes would not be unduly
burdensome to conduct.
4. Testing of Transient Technologies
and at Variable Refrigeration Load
During the Framework public meeting
and comment period, several interested
parties commented on incorporating
provisions into the test procedure to
capture the effects of features that
operate to reduce energy consumption
at variable refrigeration load or at
variable time periods. California Codes
and Standards stated that ASHRAE
Standard 72 is only a steady-state test,
and that the test would not capture a
number of transient measures that may
produce significant energy savings in
the field. (California Codes and
Standards, No. 1.2.006 at p. 13) The
American Council for an EnergyEfficient Economy (ACEEE) emphasized
that it believes that a single metric is not
adequate to describe CRE operation and
that DOE should at least look at partload and full-load metrics. (ACEEE, No.
1.2.006 at pp. 69–70) California Codes
and Standards also stated that test
methods should be developed for the
purpose of measuring the maximum
possible energy savings, and that this
should include a part-load test.
(California Codes and Standards, No.
1.3.005 at p. 1)
DOE finds that there are two types of
transient technologies: Those that
operate as a function of variable ambient
conditions and those that operate at
variable times to reduce refrigeration
load. DOE discussed the technologies
that operate at variable times (night
curtains and occupancy sensors) in
section A.3 above; a discussion of the
technologies that operate as a function
of variable ambient conditions is
provided below.
Technologies that operate as a
function of variable ambient conditions
can reduce annual energy consumption
of commercial refrigeration equipment
by adapting to changes in refrigeration
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
load that result from changes in ambient
conditions. These variable load, or partload, technologies include higher
efficiency expansion valves, condenser
fan motor controllers, and anti-sweat
heater controllers. ASHRAE Standard
72–2005 calls for testing at a single
ambient temperature and relative
humidity, so technologies that are
designed to reduce energy use under
variable ambient conditions will not
affect the measured combined daily
energy consumption (CDEC) per the
existing test procedure.
An independent test to quantify the
performance of technologies that
decrease energy use at variable
refrigeration load would most likely
involve testing a unit at different
ambient conditions, including lower
temperatures and humidities. However,
section 342 of EPCA requires that test
procedures ‘‘shall be reasonably
designed to produce test results which
reflect energy efficiency, energy use,
and estimated operating costs of a type
of industrial equipment (or class
thereof) during a representative average
cycle of use (as determined by the
Secretary), and shall not be unduly
burdensome to conduct.’’ (42 U.S.C.
6314(2))
It is DOE’s understanding that,
although ASHRAE Standard 72–2005 is
a steady-state test, some variation in
refrigeration load is experienced in
display cases with doors as part of the
door opening requirement included in
that test. When the doors are opened,
the refrigeration load increases because
warm ambient air has entered the case.
If the equipment being tested has more
efficient operation at variable
refrigeration load, the case will use less
energy overall. In this way, the effects
of variable load, or part-load, features
are already captured to some degree in
the current test procedure for
commercial refrigeration equipment
with doors. Similarly, if the test
procedure is altered to capture
decreased energy consumption as a
result of night curtain use, the efficacy
of many part-load technologies in open
cases will also be captured.
Further, additional independent or
explicit part-load testing will result in
increased cost and burden for
manufacturers of covered products.
During the May 2010 Framework public
meeting, True expressed a concern that
there is a learning curve associated with
how to test equipment at standard
conditions (True, No. 1.2.006 at pp.
133–134) and that introducing
additional test conditions would
significantly increase the cost and
burden of testing. (True, No. 1.2.006 at
pp. 131–132) From conversations with
PO 00000
Frm 00035
Fmt 4702
Sfmt 4702
71601
manufacturers, DOE estimates that partload testing at additional rating
conditions could more than double the
cost and burden of testing for all
commercial refrigeration equipment.
DOE believes that explicit testing at
multiple sets of conditions is not
justified because of this increased
burden. Thus, the DOE test procedure
will continue to rely on one standard
rating condition, relying on the transient
effects inherent in the proposed test
procedure to capture part-load
performance.
5. Rating Temperatures
During the Framework public
meeting, True stated that the current
standard only directly addresses a
standard ambient test condition of 75 °F
and 55 percent relative humidity, but
that the Food and Drug Administration
and NSF standards also include an 80
°F ambient condition. (NSF
International was founded in 1944 as
the National Sanitation Foundation; the
organization’s name is now simply
NSF.) True also stated that higher realworld operating temperatures will
impact the energy use of commercial
refrigeration equipment in some
applications. (True, No. 1.2.006 at p. 38)
California Codes and Standards added
that it is important to verify that systems
operating under extreme ambient
conditions can perform safely at those
temperatures and humidities.
(California Codes and Standards, No.
1.2.006 at p. 133) True further asserted
that equipment tested at 75 °F and 55
percent relative humidity will perform
differently than if operated at 95 °F and
95 percent relative humidity. (True, No.
1.2.006 at p. 129) ACEEE added that
perhaps there should be an adverse
temperature and humidity rating
condition to ensure that equipment will
operate effectively in those scenarios.
(ACEEE, No. 1.2.006 at p. 131) Southern
Store Fixtures commented that if
additional test conditions are used,
equipment that operates outside of these
conditions should be exempt. (Southern
Store Fixtures, No. 1.2.006 at p. 133)
Zero Zone, however, stated that testing
at a variety of ambient conditions could
become burdensome and the 75/55
condition is a sound compromise. (Zero
Zone, No. 1.2.006 at p. 130)
DOE received similar comments on
the 2009 CRE energy conservation
standard NOPR. Those comments
encouraged DOE to differentiate
between NSF Type I equipment, which
is tested at standard test conditions, and
NSF Type II equipment, which is tested
at 80 °F. DOE found that the relative
difference between Type I equipment
designed to be operated at the standard
E:\FR\FM\24NOP1.SGM
24NOP1
71602
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
test condition of 75 °F and Type II
equipment designed to operate at 80 °F
would not significantly impact the
energy use of the equipment as tested at
the 75 °F test condition. Thus, DOE
concluded it was unnecessary to
institute a distinction between Type I
and Type II commercial refrigeration
equipment. 74 FR 1092, 1117 (Jan. 9,
2009).
The current DOE test procedure
requires that energy consumption
testing for all commercial refrigeration
equipment covered in these rulemakings
be conducted according to ASHRAE
Standard 72–2005, which prescribes
specific ambient conditions. DOE
believes that equipment classified as
NSF Type II can be tested at the
standard rating conditions prescribed in
the DOE test procedure without any
significant additional burden on
manufacturers. Accordingly, DOE
proposes to continue to rate all
commercial refrigeration equipment at
the standard rating condition prescribed
in the referenced industry test
procedure.
DOE requests comment on the burden
to manufacturers associated with testing
NSF Type II equipment at the standard
test condition.
6. Energy Efficiency Features
DOE received a number of comments
from stakeholders concerning energy
efficiency features that exist for the
explicit purpose of lowering energy
consumption, such as lighting
occupancy sensors and controls, night
curtains, higher efficiency expansion
valves, condenser fan motor controllers,
and anti-sweat heater controllers. The
Northwest Joint Comment stated that
the current test procedure does not have
the capacity to test all of the equipment
classes and technology options that are
likely to be within the scope of coverage
for this rulemaking. (Adjuvant
Consulting, No. 1.3.003 at pp. 1–2) True
commented that the test procedure
should represent a baseline level of
energy consumption with no energy
efficiency devices enabled. (True, No.
1.2.006 at pp. 63–64) Southern Store
Fixtures commented that some of these
devices, such as night curtains, may not
be used by 24-hour stores (Southern
Store Fixtures, No. 1.2.006 at pp. 66–
67), and also suggested that DOE consult
with end users of these energy
efficiency features before considering
them. (Southern Store Fixtures, No.
1.2.006 at p. 67) True stated that energy
controls have a variety of different
features and energy conservation levels,
and that they are sometimes already
tested by manufacturers. (True, No.
1.2.006 at p. 65) The Northwest Joint
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
Comment added that a percent time off
assumption or scaling factor might not
be adequate to capture the effects of all
time-dependent technology options.
(Adjuvant Consulting, No. 1.3.003 at p.
3)
As part of this rulemaking effort, DOE
has evaluated technology options
suggested by interested parties and has
developed provisions to quantify the
performance of those options that can be
specifically addressed while still
meeting the statutory requirements of a
test procedure. Specific proposed
changes include provisions for
measuring the energy impacts of
lighting occupancy sensors and
controls, and night curtains. Other
technologies, such as higher efficiency
expansion valves, condenser fan motor
controllers, and anti-sweat heater
controllers, are technologies that
function to reduce energy consumption
at part-load conditions. As discussed in
section III.A.4, ‘‘Testing of Transient
Technologies and at Variable
Refrigeration Load,’’ the energy saving
potential of these technologies is
already captured to some degree in the
current test procedure. Further, DOE
believes that explicit testing for these
energy efficiency technologies that
reduce energy consumption at part load
is not justified because it would
significantly increase the testing burden.
DOE requests comment on the burden
to test energy efficiency technologies
other than those explicitly accounted for
in this test procedure revision, namely
night curtains and lighting occupancy
sensors and scheduled control.
B. Summary of the Test Procedure
Revisions
Today’s proposed rule contains the
following proposed changes to the test
procedure in 10 CFR part 431, subpart
C.
1. Update References to Industry Test
Procedures to Most Current Versions
The current DOE test procedure for
commercial refrigeration equipment
adopted ARI Standard 1200–2006, with
additional provisions for testing icecream freezers at ¥15 °F, as the test
procedure used to measure the energy
consumption of a piece of commercial
refrigeration equipment to establish
compliance with the applicable energy
conservation standard. Since the
publication of the 2006 test procedure
final rule, AHRI has released an updated
version of the test procedure, AHRI
Standard 1200–2010. The updated test
procedure includes both editorial and
technical changes to the equipment
class nomenclature used within the test
procedure, the test product temperature
PO 00000
Frm 00036
Fmt 4702
Sfmt 4702
for ice-cream freezers, and the method
of normalizing and reporting units for
equipment energy consumption. These
changes align the test procedure with
the nomenclature and methodology
used in the 2009 DOE energy
conservation standard final rule. AHRI
Standard 1200–2010 is the test
procedure currently used in industry,
and DOE proposes to adopt it as the
DOE test procedure.
The current DOE test procedure also
references AHAM HRF–1–2004 as the
protocol for determining refrigerated
compartment volume. AHAM has also
updated its Standard HRF–1–2004. The
most recent version is AHAM HRF–1–
2008, which makes editorial changes
including reorganizing some of the
sections for simplicity and usability.
The newly updated AHRI 1200–2010
also references AHAM HRF–1–2008. For
consistency, DOE proposes to adopt the
more recent AHAM HRF–1–2008 for
measuring refrigerated compartment
volume.
DOE requests comment on updating
the referenced industry test procedures
to the most current versions.
2. Include Method for Determining
Energy Savings Due to the Use of Night
Curtains on Open Cases
The current test procedure, ARI
Standard 1200–2006, and method of
test, ASHRAE Standard 72–2005, do not
account for potential energy savings
resulting from the use of night curtains
on open cases. Night curtains are
devices made of an insulating material,
typically insulated aluminum fabric,
designed to be pulled down over the
open front of the case (similar to the
way a window shade operates) when the
merchandizing establishment is closed
or the customer traffic is significantly
decreased. The insulating shield, or
night curtain, decreases infiltration and
mixing of the cool air inside the case
with the relatively warm, humid air in
the store interior. It also reduces
conductive and radiative heat transfer
into the case. This can reduce
compressor loads and defrost cycles,
significantly decreasing energy use. A
1997 study by the Southern California
Edison Refrigeration Technology and
Test Center found that, when used for
6 hours per day, night curtains reduce
total energy use of the case by
approximately 8 percent.2
To allow manufacturers to account for
the possible energy savings of cases sold
2 Southern California Edison, Refrigeration and
Technology and Test Center, Energy Efficiency
Division. Effects of the Low Emissivity Shields on
Performance and Power Use of a Refrigerated
Display Case. August 1997. Available at https://
www.econofrost.com/acrobat/sce_report_long.pdf.
E:\FR\FM\24NOP1.SGM
24NOP1
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
71603
Where:
LECsc = lighting energy consumption of
internal case lights with lighting
occupancy sensors and controls
deployed (kilowatt-hours);
Pli = rated power of lights when they are fully
on (watts);
Pli(off) = power of lights when they are off
(watts);
Pli(dim) = power of lights when they are
dimmed (watts);
tsc = time period when lighting is fully on
with lighting occupancy sensors and
controls enabled (hours);
toff = time period which the lights are off due
to the use of lighting occupancy sensors
or scheduled controls (hours); and
tdim = time period which the lights are
dimmed due to the use of lighting
occupancy sensors or scheduled controls
(hours).
In equation 1, toff and tdim are
determined based on the sum of any
contribution from lighting occupancy
sensors and scheduled controls that turn
off or dim lighting, respectively. These
values are summed, as shown in
equation 2, to determine the total
amount of time lighting is dimmed or
off.
3 U.S. Department of Energy. Demonstration
Assessment of Light-Emitting Diode (LED) Freezer
Case Lighting. October 2009. Prepared by Pacific
Northwest National Laboratory for the U.S. DOE
Solid State Lighting Technology Demonstration
GATEWAY Program. Available at https://
apps1.eere.energy.gov/buildings/publications/pdfs/
ssl/gateway_freezer-case.pdf.
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
DOE proposes a 6-hour test period to
approximate the typical usage of a night
curtain. In studies analyzing the effects
of night curtain use, such as the
previously cited 1997 study by the
Southern California Edison
Refrigeration Technology and Test
Center, a similar 6-hour time period has
been used. The test for night curtains
would apply only to cases sold with
night curtains installed. The
assumptions made in the testing of night
curtains may not reflect their use in the
field in all applications. However, this
test would be a standard for all cases
sold with night curtains, regardless of
their anticipated use.
DOE requests comment on the
proposal for the incorporation of night
curtains into the DOE test procedure.
3. Include Calculation for Determining
Energy Savings Due to Use of Lighting
Occupancy Sensors or Controls
PO 00000
Frm 00037
Fmt 4702
Sfmt 4702
E:\FR\FM\24NOP1.SGM
24NOP1
EP24NO10.364
Night Curtain Requirements. For open
display cases sold with night curtains
installed, the night curtain shall be employed
according to manufacturer instructions for a
total of 6 hours, 3 hours after the start of a
defrost period. Upon the completion of the 6hour period, the night curtain shall be raised
until the completion of the 24-hour test
period.
The current test procedure, ARI
Standard 1200–2006, and method of
test, ASHRAE Standard 72–2005, do not
account for potential energy savings
resulting from the use of lighting
occupancy sensors and scheduled
controls. The energy savings due to the
use of occupancy-based sensors or
schedule-based controls will vary in the
field due to differing environmental and
operating conditions. However, studies,
including a demonstration project
conducted through the DOE GATEWAY
program, have shown that lighting
occupancy sensors or controls could
reduce the total energy use of a typical
refrigerated merchandising unit
operating in a grocery store by up to 40
percent.3
Lighting occupancy sensors and
schedule-based control systems are
designed to reduce the amount of time
that lights are on within commercial
refrigeration equipment. Lighting
occupancy sensors use passive infrared,
ultrasonic, or other motion-sensing
technology to detect the presence of a
customer or employee. These sensors
turn off or dim the lights within the
equipment when no motion is detected
in the sensor’s coverage area. Schedulebased lighting controls allow lights to be
turned off or dimmed at scheduled
times throughout the day. The energy
efficiency benefits from reducing case
lighting energy use are two-fold,
because both the direct electricity
consumption of the lights and the heat
load on the refrigeration system are
decreased. Light-emitting diode
technology, used in much of today’s
new commercial refrigeration
equipment, lends itself to rapid on/off
cycling or dimming, which enables the
use of occupancy sensors or scheduled
controls, or both. Lighting occupancy
sensors and scheduled controls can be
addressed similarly based on available
energy usage data.
DOE proposes using an analytical
method similar to equation 4, section
5.2.3 of AHRI Standard 1200–2010, to
calculate the energy use of lighting
within the refrigerated volume.
Equation 1 presents a method to
calculate the direct lighting energy
consumption (LECsc) with lighting
occupancy sensors and controls
deployed for either remote condensing
or self-contained units.
with night curtains, DOE intends to
adopt a standardized physical test
method. A physical test would
accurately capture differences in energy
use reduction as a function of similar
technologies and case dimensions. It is
important to capture the differences in
energy use reduction from similar
technologies because of the large
performance disparities that can exist.
For example, night curtains made of
low-emissivity materials, such as
aluminum, decrease the radiative losses
from the case and therefore are much
more effective at reducing heat loss than
night curtains made of plastic, linoleum,
or other non-reflective materials. In
addition, each night curtain may reduce
infiltration differently depending on its
insulating characteristics and design.
The case dimensions and default
infiltration load also impact night
curtain performance. As such, a
physical test will also accurately
capture differences in the energy
conservation utility of night curtains as
a function of case dimension.
DOE proposes using the following
physical test method, as specified by
ASHRAE Standard 72–2005. This
method would be similar to section 7.2
in ASHRAE Standard 72–2005, ‘‘DoorOpening Requirements,’’ and would
read as follows:
71604
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
Where:
toff = time period which the lights are off due
to the use of lighting occupancy sensors
or scheduled controls (hours);
tdim = time period which the lights are dim
due to the use of lighting occupancy
sensors or scheduled controls (hours);
toff,controls = time case lighting is off due to the
use of lighting controls (hours);
tdim,controls = time case lighting is dimmed due
to the use of lighting controls (hours);
toff,sensors = time case lighting is off due to the
use of lighting occupancy sensors
(hours); and
tdim,sensors = time case lighting is dimmed due
to the use of lighting occupancy sensors
(hours).
tl = time lighting would be on without
lighting occupancy sensors or controls
(24 hours); and
EER = energy efficiency ratio from Table 1 in
AHRI Standard 1200–2010 for remote
condensing equipment and the values
shown in Table III.1 of this document for
self-contained equipment (British
thermal units/watt).
TABLE III.1. EER FOR SELF-CONTAINED COMMERCIAL REFRIGERATED
DISPLAY
MERCHANDISERS
AND
STORAGE CABINETS
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
PO 00000
Frm 00038
Fmt 4702
Sfmt 4702
Operating temperature
class
Medium ...............................
Low .....................................
E:\FR\FM\24NOP1.SGM
24NOP1
EER
Btu/W
11.26
7.14
EP24NO10.366
Where:
CECA= Alternate Compressor Energy
Consumption (kilowatt-hours);
LECsc = lighting energy consumption of
internal case lights with lighting
occupancy sensors and controls
deployed (kilowatt-hours);
Pli = rated power of lights when they are fully
on (watts);
As the test procedure is for 24-hour
time period, the sum of tsc, Toff, and tdim
should equal 24 hours. DOE also
proposes that the total time period
during which the lights are off or
dimmed shall not exceed 10.8 hours
based on the maximum estimated
energy savings from lighting occupancy
sensors and controls. This limit is
established to prevent double counting
of energy savings in equipment where
both lighting occupancy sensors and
schedule based controls are installed.
EP24NO10.367
project conducted through the DOE
GATEWAY program.
Equations 1, 2, and 3 can be used to
calculate the energy use of CRE whether
the equipment utilizes lighting
occupancy sensors or control, and
whether the light settings are set at fully
on, fully off, or dimmed. For example,
consider a situation in which lighting
that is dimmed throughout the day by
occupancy sensors and is turned off
completely by scheduled controls
during closing hours. In this example,
tdim for the dimmed occupancy sensor
would be 2.8 hours, and toff for the
scheduled lighting control, which turns
off the lights, would be 8 hours. The
sum of toff and tdim would be equal to the
maximum 10.8 hours. In this example,
both tdim,controls and toff,sensors would equal
zero.
In addition to conserving energy
directly through decreased lighting
electrical load, occupancy sensors also
decrease the heat load from lights that
are located inside the refrigerated space
on the refrigeration equipment.
Therefore, a second calculation is
necessary to account for these energy
impacts. This second calculation
quantifies the reduced compressor
energy use, which is then used to
calculate total energy use, as described
below.
For remote condensing equipment,
the calculation of Alternate Component
Indirect Effect in section 5.4 of AHRI
Standard 1200–2010 can be used to
measure the energy impacts on the
compressor. Thus, for remote
condensing equipment, equation 4, from
AHRI Standard 1200 equations 5.4 and
5.4.2, can be applied to calculate the
decreased compressor power due to use
of lighting occupancy sensors and
controls.
EP24NO10.365
Where:
toff = time period which the lights are off due
to the use of lighting occupancy sensors
or scheduled controls (hours);
tdim = time period which the lights are
dimmed due to the use of lighting
occupancy sensors or scheduled controls
(hours);
tsc= time period when lighting is fully on
with lighting occupancy sensors and
controls enabled (hours);
tl = time period when lighting would be on
without lighting occupancy sensors or
controls (24 hours);
with the sum of all toff and tdim from both
lighting occupancy sensors and controls not
to exceed 10.8 hours.
In equation 2, the time the case
lighting is dimmed or off due to
scheduled lighting controls (toff,controls or
tdim,controls, as applicable) will be 8 hours
for those cases with lighting controls
installed. This will depend on whether
the controls dim or turn off lights. A
time off period of 8 hours was chosen
for scheduled controls to approximate
the typical usage of lighting control
products based on comments received
during previous DOE rulemakings for
this equipment. Specifically, during the
previous rulemaking for commercial
refrigeration equipment, California
Utilities commented that 8 hours
reflected the California predicted ‘‘low
load’’ period. (Docket number EERE–
2006–BT–STD–0126, California Joint
Comment, No. 41, at p. 12)
The time the case lighting is off or
dimmed due to lighting occupancy
sensors (toff,sensors or tdim,sensors, as
applicable) will be 2.8 or 10.8 hours for
cases with lighting occupancy sensors
installed, depending on whether
scheduled controls are also installed.
For equipment with only lighting
occupancy sensors installed toff,sensors or
tdim,sensors, as applicable, will be 10.8
hours. For equipment with both lighting
occupancy sensors and lighting controls
installed, the lighting controls will be
assumed to override the occupancy
sensor during the time the lighting
control is used to reduce case lighting.
Thus, the time the case lighting is off or
dimmed due to lighting occupancy
sensors (toff,sensors or tdim,sensors, as
applicable) will be 2.8 hours for
equipment with lighting occupancy
sensors and lighting controls installed.
The time off period for lighting
occupancy sensors was derived based
on the previously cited demonstration
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
Where:
CDEC = combined daily energy consumption
(kilowatt-hours);
CECR = reduced compressor energy
consumption (kilowatt-hours);
FEC = fan energy consumption (kilowatthours);
LECsc = lighting energy consumption with
lighting sensors and controls deployed
(kilowatt-hours);
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
Where:
TDECo = total daily energy consumption with
lights fully on, as measured by AHRI
Standard 1200–2010 (kilowatt-hours);
Pli = rated power of lights when they are fully
on (watts);
tl = time period when lights would be on
without lighting occupancy sensors or
controls (24 hours); and
LECsc = lighting energy consumption with
lighting occupancy sensors and controls
deployed (kilowatt-hours).
The test procedure modifications to
account for lighting occupancy sensors
and controls would only apply to
commercial refrigeration equipment
sold with lighting occupancy sensors
and controls installed by the
manufacturers. However, this analytical
method would place the least additional
burden on manufacturers and would be
a standard for all commercial
refrigeration equipment sold with
lighting occupancy sensors and
controls, regardless of their anticipated
use.
DOE requests comment on the
proposed calculation method for
treatment of lighting occupancy sensors
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
AEC = anti-condensate energy consumption
(kilowatt-hours);
DEC = defrost energy consumption (kilowatthours); and
PEC = condensate evaporator pan energy
consumption (kilowatt-hours).
For self-contained equipment, the
CECA and LECsc would be calculated as
above and then used directly with the
and controls in the DOE test procedure
for commercial refrigeration equipment.
Specifically, DOE requests comment on
the values assumed for the time period
when lighting is off or reduced due to
lighting occupancy sensors or controls
and the factor used to scale the amount
of heat produced by case lighting.
4. Include Provision for Testing at
Lowest Application Product
Temperature
During the Framework public meeting
and Framework comment period of the
2009 energy conservation standard
rulemaking, DOE received comments on
the inclusion of ‘‘application
temperatures’’ for commercial
refrigeration equipment. Application
temperatures are rating temperatures
other than the standard rating
temperatures prescribed by DOE’s test
procedures (38 °F for commercial
refrigerators, 0 °F for commercial
freezers, and ¥15 °F for commercial icecream freezers). Interested parties
commented that allowing for an
application temperature category is
PO 00000
Frm 00039
Fmt 4702
Sfmt 4702
The CECR and LECsc value would then
be substituted for the lighting
energy consumption (LEC) and CEC
without controls or sensors in the
calculation of CDEC for remote
condensing cases as shown in
equation 6.
total daily energy consumption as
measured by AHRI Standard 1200–2010,
with the lights fully on to determine the
daily energy consumption used to show
compliance with the DOE energy
conservation standard for this
equipment as shown in equation 7. For
self-contained equipment:
essential because operating temperature
plays a key role in equipment energy
consumption. However, interested
parties stated that the application
temperature category should be reserved
for equipment that cannot operate at
0 °F or at 38 °F; that DOE should not
regulate equipment that has few
shipments; and that appropriate Federal
standards and rating temperatures
should be developed for equipment
with large numbers of shipments.
DOE analyzed the shipments data
provided by ARI during the Framework
comment period of the 2009
rulemaking. DOE found that, excluding
equipment for which EPACT 2005
amended EPCA to set standards (selfcontained commercial refrigerators and
commercial freezers with doors), only
1.7 percent of units under the previous
rulemaking were equipment that operate
at ‘‘application temperatures,’’ namely
45 °F, 20 °F, 10 °F, or ¥30 °F. Of these,
units that operate at 45 °F (typically
‘‘wine chillers’’) had the highest
shipments, and these were
predominantly remote condensing
E:\FR\FM\24NOP1.SGM
24NOP1
EP24NO10.370
The CECA includes a multiplication
factor of 0.75 to account for the fact that
not all of the heat produced from the
Operating temperature
EER
class
Btu/W
lights will impact the compressor load.
The factor of 0.75 was suggested by
Ice Cream ...........................
4.80
manufacturers during discussions with
Note:
the AHRI Standard 1200 engineering
1 EER values for operating temperature
committee.
classes are calculated based on the average
For remote condensing commercial
EER value of all equipment in that class which
was analyzed as part of the previous (2009) refrigerators, freezers, and refrigeratorrulemaking. This does not include equipment freezers with lighting occupancy
for which standards were set by Congress in
EPACT 2005 (VCT, VCS, HCT, HCS, and sensors, controls, or both installed, the
SOC at M and L temperatures) or classes for revised compressor energy consumption
which standards were set using extension (CECR) shall be the CECA added to the
multipliers in the 2009 rulemaking (VOP.SC.L,
SVO.SC.L, VOP.SC.I, SVO.SC.I, HZO.SC.I, compressor energy consumption (CEC)
VOP.SC.I, SVO.SC.I, HZO.SC.I, HCS.SC.I, measured in AHRI Standard 1200–2010,
SOC.SC.I).
as shown in equation 5.
Where:
CECR = reduced compressor energy
consumption (kilowatt-hours);
CEC = compressor energy consumption as
measured by AHRI Standard 1200
(kilowatt-hours); and
CECA = alternate compressor energy
consumption (kilowatt-hours).
EP24NO10.369
2 These values only represent compressor
EER and do not include condenser fan energy
use.
EP24NO10.368
TABLE III.1. EER FOR SELF-CONTAINED COMMERCIAL REFRIGERATED
DISPLAY
MERCHANDISERS
AND
STORAGE CABINETS—Continued
71605
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
71606
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
equipment. Given the relatively low
shipment volumes of equipment that
operates at application temperatures,
DOE did not develop separate standards
for equipment that operates at an
application temperature different than
one of the three prescribed rating
temperatures. 72 FR 41162, 41168–69
(July 26, 2007).
During the May 2010 Framework
public meeting, several parties again
commented that some equipment
covered under this rulemaking is
designed to operate at significantly
higher temperatures than the designated
temperature for that product class.
Specifically, California Codes and
Standards stated that DOE should
review test methods for niche
equipment that may require different
temperature criteria and schedules.
(California Codes and Standards, No.
1.3.005 at p. 3) Structural Concepts also
stated that some types of equipment,
such as candy and wine cases, operate
at 55 or 60 °F, yet would have to be
tested at 38 °F to meet a standard. This
is an issue because these units are not
designed to operate at that temperature.
(Structural Concepts, No. 1.2.006 at p.
59).
DOE recognizes that this type of
equipment may not be able to maintain
an integrated average temperature of
38 °F, as required by the current DOE
test procedure. DOE also acknowledges
that self-contained commercial
refrigerators comprise most of the
equipment that operates at temperatures
higher than the 38 °F rating
temperature. However, these equipment
classes were not included in the 2009
rulemaking analysis of products that
operate at application temperature
because they were not included in the
scope of that rulemaking. Because selfcontained refrigerators are included in
the current energy conservation
standard rulemaking, the shipment
volume of this equipment that operates
at temperatures higher than 38 °F may
increase.
AHRI Standard 1200–2010 has
provisions for such equipment to be
rated at the application product
temperature. For equipment that
operates at a temperature that is not one
of the specified rating temperatures,
DOE believes that allowing such
equipment to be tested at its application
product temperature could create a
loophole that would allow
manufacturers to certify less-efficient
equipment. This loophole would enable
a manufacturer to sell equipment that
can operate at one of the prescribed test
temperatures, but would not comply
with the standard if tested at that test
temperature because that equipment
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
would comply when tested at the higher
application temperature.
However, equipment that operates at
temperatures greater than the 38 °F
rating temperature may be able to
become more efficient if allowed to be
tested at temperatures other than 38 °F
and may represent a large enough
shipment volume to warrant a separate
rating temperature. Thus, DOE proposes
including a provision for rating
refrigerators that cannot operate at the
prescribed 38 °F integrated average
product temperature at the lowest
application product temperature. In the
context of this rulemaking, the ‘‘lowest
application product temperature’’ would
be defined as the lowest temperature
setting that can be maintained for the
duration of the test. In this case, the
integrated average product temperature
achieved during the test should be
recorded. Equipment tested at the
lowest application product temperature
will still be required to comply with the
standard for its respective equipment
class.
DOE requests comment on the
provision for testing commercial
refrigerators that cannot be tested at
38 °F at the lowest application product
temperature.
IV. Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget
has determined that test procedure
rulemakings do not constitute
‘‘significant regulatory actions’’ under
section 3(f) of Executive Order 12866,
Regulatory Planning and Review, 58 FR
51735 (Oct. 4, 1993). Accordingly, this
proposed action was not subject to
review under the Executive Order by the
Office of Information and Regulatory
Affairs (OIRA) in the Office of
Management and Budget (OMB).
B. Review Under the National
Environmental Policy Act
In this proposed rule, DOE proposes
amendments to test procedures that may
be used to implement future energy
conservation standards for commercial
refrigeration equipment. DOE has
determined that this rule falls into a
class of actions that are categorically
excluded from review under the
National Environmental Policy Act of
1969 (NEPA; 42 U.S.C. 4321 et seq.).
The rule is covered by Categorical
Exclusion A5, for rulemakings that
interpret or amend an existing rule
without changing the environmental
effect, as set forth in DOE’s NEPA
regulations in appendix A to subpart D,
10 CFR part 1021. This rule will not
affect the quality or distribution of
PO 00000
Frm 00040
Fmt 4702
Sfmt 4702
energy usage and therefore will not
result in any environmental impacts.
Accordingly, neither an environmental
assessment nor an environmental
impact statement is required.
C. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act
(5 U.S.C. 601 et seq.) requires
preparation of an initial regulatory
flexibility analysis for any rule proposed
for public comment, unless the agency
certifies that the rule, if promulgated,
will not have a significant economic
impact on a substantial number of small
entities. As required by Executive Order
13272, ‘‘Proper Consideration of Small
Entities in Agency Rulemaking,’’ 67 FR
53461 (August 16, 2002), DOE
published procedures and policies on
February 19, 2003, so that the potential
impacts of its rules on small entities are
properly considered during the
rulemaking process. 68 FR 7990
(February 12, 2003). DOE has made its
procedures and policies available on the
Office of the General Counsel’s Web
site: https://www.gc.doe.gov.
DOE reviewed today’s proposed rule,
which would amend the test procedures
for commercial refrigeration equipment,
under the provisions of the Regulatory
Flexibility Act and the procedures and
policies published on February 19,
2003. DOE tentatively concludes and
certifies that the proposed rule, if
adopted, would not result in a
significant impact on a substantial
number of small entities. The factual
basis for this certification is set forth
below.
DOE used the small business size
standards published on January 31,
1996, as amended, by the SBA to
determine whether any small entities
would be required to comply with the
rule. 61 FR 3286; see also 65 FR 30836,
30848 (May 15, 2000), as amended at 65
FR 53533, 53544 (September 5, 2000).
The size standards are codified at 13
CFR part 121. The standards are listed
by NAICS code and industry description
and are available at https://www.sba.gov/
idc/groups/public/documents/
sba_homepage/serv_sstd_tablepdf.pdf.
Commercial refrigeration equipment
manufacturing is classified under
NAICS 333415, ‘‘Air-Conditioning and
Warm Air Heating Equipment and
Commercial and Industrial Refrigeration
Equipment Manufacturing.’’ 70 FR
12395 (March 11, 2005). Small entities
within this industry description are
those with 750 employees or fewer.
Analysis of the manufacturers in the
commercial refrigeration equipment
market identified 22 small
manufacturers that will be directly
E:\FR\FM\24NOP1.SGM
24NOP1
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
regulated by this rule. DOE seeks
comment on its estimate of the number
of small businesses in the CRE market.
The proposed changes to the test
procedure consist of updating the
referenced industry test procedures to
the most current versions; testing
requirements for units sold with night
curtains and lighting occupancy sensors
or controls installed; and provisions for
testing units that cannot operate at the
specified 38 °F integrated average
product temperature.
All commercial refrigeration
equipment for which standards were set
in EPACT 2005 are currently required to
be tested using the DOE test procedure
to show compliance with the EPACT
2005 standard levels. Manufacturers of
equipment for which standards were set
in the 2009 final rule will similarly be
required to test units using the DOE test
procedure to show compliance with the
2009 standards levels beginning January
1, 2012. The current DOE test procedure
references AHRI Standard 1200–2006
and AHAM HRF–1–2004. This test
procedure consists of one 24-hour test at
standard rating conditions to determine
daily energy consumption. Aligning the
DOE test procedure with the most recent
industry test procedures currently in
use—AHRI standard 1200–2010 and
AHAM HRF–1–2008—will simplify
testing requirements and reduce the
burden of testing for both small and
large manufacturers.
For equipment that could be sold with
night curtains installed, the current test
procedure requires one 24-hour test
without the night curtain installed. To
minimize the additional burden of test
on manufacturers, under the proposed
revisions, if a unit is tested and shows
compliance with the relevant energy
conservation standard without night
curtains installed, that unit can also be
sold with night curtains installed
without additional testing. In addition,
if a manufacturer chose to sell cases
only with night curtains installed, only
one 24-hour test would be required. If,
however, a piece of equipment does not
meet DOE’s energy conservation
standards without night curtains
installed, DOE proposes to allow the
unit to be tested a second time with
night curtains installed. In this instance,
assuming the energy conservation
standard is met, the case would also be
required to be sold with night curtains
installed. This would require an
increased burden of test on only those
units that cannot show compliance with
DOE energy conservation standards
without night curtains installed. As
DOE proposes to incorporate provisions
for testing a unit with night curtains
installed into the same 24-hour test, the
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
burden of conducting the test with and
without night curtains is approximately
the same.
DOE estimates that testing a single
unit in accordance with the current DOE
test procedure takes 1 week of
laboratory time and costs approximately
$5,000. If two tests are required, there
will be an increase of approximately
$5,000 per unit tested. This estimate is
based on information from
manufacturers and private testing
services quoted on behalf of DOE in the
last 2 years for completing a test
according to AHRI Standard 1200–2006
on commercial refrigerators, freezers,
and refrigerator-freezers.
DOE also researched the number of
CRE manufacturers that sell open cases,
which would potentially be sold with a
night curtain. DOE found that larger
manufacturers typically offer more
unique individual basic models than
smaller manufacturers. DOE also found
that the larger manufacturers sell more
open cases than smaller manufacturers.
DOE estimates that for both small and
large manufacturers who offer open
cases, open cases that could be sold
with night curtains comprised about 20
percent of total models, or
approximately between 1 and 50
models. While testing with and without
night curtains will not be required for
all these models, at this time DOE
cannot predict the number of cases that
will require two tests because the
standards with which this test
procedure will be used to show
compliance have not been established.
Therefore, assuming conservatively that
half of the open cases that could be sold
with night curtains will not meet the
new energy conservation standards and
will require two tests, DOE’s analysis
found that the incremental cost of
running the extra tests ranged from
approximately $2,500 to $125,000.
Further, DOE identified that a single
small manufacturer produces the
majority of all open cases produced by
small manufacturers. In fact, many
small manufacturers identified by DOE
did not sell open cases at all.
DOE understands, however, that small
manufacturers have less expendable
capital available and may be more
affected by the additional cost of testing.
To estimate the additional cost of testing
due to night curtains for small
manufacturers, DOE estimated the
average cost of additional testing for all
open cases compared to the average
annual value added statistic. The
average value added statistic is
representative of an entity’s annual
gross operating margin and is calculated
by subtracting the cost of materials,
supplies, containers, fuel, purchased
PO 00000
Frm 00041
Fmt 4702
Sfmt 4702
71607
electricity, and contract work from the
value of shipments. DOE analyzed the
impact on the smallest manufacturers of
commercial refrigeration equipment
since these manufacturers would likely
be the most vulnerable to cost increases.
For CRE manufacturers, the two
smallest entities were in the 25 to 49
and 50 to 99 employee size category in
NAICS 333415 as reported by the U.S.
Census.4 The average annual value
added for manufacturers in these size
ranges from the census data was $2.97
to $6.38 million in 2001$, per the 2002
Economic Census, or approximately
$3.56 to $7.64 million per year in 2010$
after adjusting for inflation using the
implicit price deflator for gross
domestic product.5
DOE also examined the average value
added statistic provided by Census for
all manufacturers with between 100 and
249 employees in this NAICS
classification as the most representative
value from the 2002 Economic Census
data of the CRE manufacturers. More
than half (13 manufacturers) of the
identified small manufacturers fell into
this category, including the
manufacturer that has the greatest
percentage of open cases that could be
sold with night curtains. The average
annual value added statistic for all small
manufacturers with between 100 and
249 employees was $16.3 million
(2010$).
Given this data, and assuming the
estimate of $5,000 for the additional
testing costs is accurate, DOE concluded
that the additional costs for testing
under the proposed requirements would
be approximately 0.4 percent of annual
value added for the two smallest firms.
The additional costs would be
approximately 0.3 percent of the average
annual value added for representative
small CRE manufacturers with between
100 and 249 employees. For the
manufacturer that sells the greatest
percentage of open cases that could be
sold with a night curtain, 56 percent,
DOE estimates the additional cost of
testing would equal $80,000, or 0.6
percent of the average annual value
added.
The requirements for units sold with
lighting occupancy sensors and controls
will not include additional testing.
4 U.S. Bureau of the Census, American Factfinder,
2002 Economic Census, Manufacturing, Industry
Series, Industry Statistics by Employment Size,
available at https://factfinder.census.gov/servlet/
IBQTable?_bm=y&-ds_name=EC0231I4&ib_type=NAICS2002&-NAICS2002=333415&geo_id=&-_industry=333415&NAICS2002sector=8699171&-_lang=en&fds_name=EC0200A1.
5 U.S. Department of Commerce Bureau of
Economic Analysis, available at https://
www.bea.gov/national/nipaweb/SelectTable.asp.
E:\FR\FM\24NOP1.SGM
24NOP1
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
71608
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
Instead, DOE proposes incorporating a
calculation method that will determine
the energy impact of lighting occupancy
sensors and controls. Again,
manufacturers will only be required to
show compliance of a unit with lighting
occupancy sensors or controls installed
if the equivalent unit without lighting
occupancy sensors and controls does
not comply with the applicable energy
conservation standard. DOE believes
that additional calculations will only
require a few additional minutes of
testing time, which represents about a
15 percent increase in the calculation
intensity of the test. However, the
physical test requirements are the far
more burdensome and time-intensive
portion of the test. When including the
time of physical testing, a minimum of
24 hours, DOE estimates that the
additional calculations required by the
lighting occupancy sensor and
scheduled control requirements would
increase the total burden of test by less
than 0.01 percent. Assuming the current
cost of testing would be $5,000 and a
0.01 increase cost in testing, this would
represent an addition $50 per unit. If
additional calculation is required for a
conservative 50 percent of units, the
total incremental increase in cost of
testing will range from $50 to $6,500
and will be less 0.0005 percent of the
annual average value added for all CRE
manufacturers, including small
manufacturers.
For equipment that cannot be tested at
the 38 °F integrated average product
temperature, manufacturers currently
are required to test the unit using AHRI
Standard 1200 at the 38 °F test
temperature. Under the proposed
revisions, these manufacturers would be
allowed to test units that cannot meet
the 38 °F test temperature to be tested
at the lowest application product
temperature, with the only difference
being the integrated average product
temperature. Since the same test is
being performed in both cases, DOE
believes that this will not increase the
burden of test for those manufacturers
and, in fact, will lead to more
representative energy consumption
values. In addition, the provision for
testing units that cannot operate at the
specified 38 °F integrated average
product temperate will affect only a
small percentage of units. DOE believes
there would not be an incremental
increase in testing burden, for small or
large manufacturers, due to this
provision.
DOE believes that the total increase in
testing burden resulting from the test
procedure amendments proposed in this
NOPR are almost exclusively due to the
provisions for testing night curtains.
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
DOE estimates that the total increase in
testing burden does not exceed 0.6
percent of average annual value added
for any manufacturer of commercial
refrigeration equipment, small or large.
As the average value added statistic is
representative of an entities annual
gross operating margin, DOE concludes
that 0.6 percent of this value is not a
significant economic impact. Further,
0.6 percent of annual average value
added was found for only the most
impacted small manufacturer. DOE
believes that one does not represent a
substantial number.
Based on the factual basis stated
above, DOE believes that the proposed
test procedure amendments would not
have a significant economic impact on
a substantial number of small entities,
and the preparation of a regulatory
flexibility analysis is not required. DOE
will transmit the certification and
supporting statement of factual basis to
the Chief Counsel for Advocacy of the
Small Business Administration for
review under 5 U.S.C. 605(b).
DOE seeks comment on its
certification that the proposed test
procedure changes will not have a
significant impact on a substantial
number of small entities.
D. Review Under the Paperwork
Reduction Act
Manufacturers of commercial
refrigeration equipment must certify to
DOE that their equipment complies with
any applicable energy conservation
standard. In certifying compliance,
manufacturers must test their
equipment according to the DOE test
procedure for commercial refrigeration
equipment, including any amendments
adopted for that test procedure. DOE has
proposed regulations for the
certification and recordkeeping
requirements for all covered consumer
products and commercial equipment,
including commercial refrigeration
equipment. 75 FR 56796 (Sept. 16,
2010). The collection-of-information
requirement for the certification and
recordkeeping is subject to review and
approval by OMB under the Paperwork
Reduction Act (PRA). This requirement
has been submitted to OMB for
approval. Public reporting burden for
the certification is estimated to average
20 hours per response, including the
time for reviewing instructions,
searching existing data sources,
gathering and maintaining the data
needed, and completing and reviewing
the collection of information.
Public comment is sought regarding:
Whether this proposed collection of
information is necessary for the proper
performance of the functions of the
PO 00000
Frm 00042
Fmt 4702
Sfmt 4702
agency, including whether the
information shall have practical utility;
the accuracy of the burden estimate;
ways to enhance the quality, utility, and
clarity of the information to be
collected; and ways to minimize the
burden of the collection of information,
including through the use of automated
collection techniques or other forms of
information technology. Send comments
on these or any other aspects of the
collection of information to Charlie
Llenza (see ADDRESSES) and by e-mail to
Christine_J._Kymn@omb.eop.gov.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
E. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (UMRA; Pub. L.
104–4) requires each Federal agency to
assess the effects of Federal regulatory
actions on State, local, and Tribal
governments and the private sector. For
proposed regulatory actions likely to
result in a rule that may cause
expenditures by State, local, and Tribal
governments in the aggregate or by the
private sector of $100 million or more
in any one year (adjusted annually for
inflation), section 202 of UMRA requires
a Federal agency to publish estimates of
the resulting costs, benefits, and other
effects on the national economy. (2
U.S.C. 1532(a),(b)) The UMRA also
requires a Federal agency to develop an
effective process to permit timely input
by elected officers of State, local, and
Tribal governments on a proposed
‘‘significant intergovernmental mandate’’
and requires an agency plan for giving
notice and opportunity for timely input
to potentially affected small
governments before establishing any
requirements that might significantly or
uniquely affect small governments. On
March 18, 1997, DOE published a
statement of policy on its process for
intergovernmental consultation under
UMRA. 62 FR 12820. (This policy is
also available at https://www.gc.doe.gov/
.) DOE reviewed today’s proposed rule
pursuant to UMRA and its policy and
determined that the rule contains
neither an intergovernmental mandate
nor a mandate that may result in the
expenditure of $100 million or more in
any year, so these requirements do not
apply.
E:\FR\FM\24NOP1.SGM
24NOP1
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
F. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any
proposed rule that may affect family
well-being. Today’s proposed rule
would not have any impact on the
autonomy or integrity of the family as
an institution. Accordingly, DOE has
concluded that it is unnecessary to
prepare a Family Policymaking
Assessment.
G. Review Under Executive Order 13132
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999) imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have federalism implications. On March
14, 2000, DOE published a statement of
policy describing the intergovernmental
consultation process it will follow in the
development of such regulations. 65 FR
13735. DOE has examined today’s
proposed rule and has determined that
it does not preempt State law and does
not have a substantial direct effect on
the States, on the relationship between
the national government and the States,
or on the distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the equipment that is the subject of
today’s proposed rule. States can
petition DOE for a waiver of such
preemption to the extent, and based on
criteria, set forth in EPCA. (42 U.S.C.
6297) No further action is required by
Executive Order 13132.
H. Review Under Executive Order 12988
With respect to the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (February 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
71609
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort so that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, the proposed
rule meets the relevant standards of
Executive Order 12988.
Executive Order 12866, or any successor
order; and (2) is likely to have a
significant adverse effect on the supply,
distribution, or use of energy; or (3) is
designated by the Administrator of
OIRA as a significant energy action. For
any proposed significant energy action,
the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use
should the proposal be implemented,
and of reasonable alternatives to the
action and their expected benefits on
energy supply, distribution, and use.
Today’s regulatory action would not
have a significant adverse effect on the
supply, distribution, or use of energy
and therefore it is not a significant
energy action. Accordingly, DOE has not
prepared a Statement of Energy Effects.
I. Review Under the Treasury and
General Government Appropriations
Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516, note)
provides for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. The OMB’s
guidelines were published in 67 FR
8452 (February 22, 2002), and DOE’s
guidelines were published in 67 FR
62446 (October 7, 2002). DOE has
reviewed today’s proposed rule under
the OMB and DOE guidelines and has
concluded that it is consistent with
applicable policies in those guidelines.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
J. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to the Office of
Information and Regulatory Affairs
(OIRA), Office of Management and
Budget, a Statement of Energy Effects for
any proposed significant energy action.
A ‘‘significant energy action’’ is defined
as any action by an agency that
promulgated or is expected to lead to
promulgation of a final rule, and that (1)
is a significant regulatory action under
PO 00000
Frm 00043
Fmt 4702
Sfmt 4702
K. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 15, 1988), that this proposed
regulation, if promulgated as a final
rule, would not result in any takings
that might require compensation under
the Fifth Amendment to the U.S.
Constitution.
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91), DOE must comply with section 32
of the Federal Energy Administration
Act of 1974 (Pub. L. 93–275), as
amended by the Federal Energy
Administration Authorization Act of
1977. When a proposed rule contains or
involves use of commercial standards,
the rulemaking must inform the public
of the use and background of such
standards. (15 U.S.C. 788 32)
The proposed rule incorporates
testing methods contained in the
following commercial standards: (1) ARI
Standard 1200–2010 ‘‘Performance
Rating of Commercial Refrigerated
Display Merchandisers and Storage
Cabinets;’’ and (2) AHAM Standard
HRF–1–2008, ‘‘Energy, Performance and
Capacity of Household Refrigerators,
Refrigerator-Freezers and Freezers’’
section 3.21, ‘‘Volume,’’ and sections 4.1
through 4.3, ‘‘Method for Computing
Refrigerated Volume of Refrigerators,
Refrigerator-Freezers, Wine Chillers,
and Freezers.’’ DOE has evaluated these
standards and is unable to conclude
whether they fully comply with the
requirements of section 323(b) of the
Federal Energy Administration Act (i.e.,
whether they were developed in a
E:\FR\FM\24NOP1.SGM
24NOP1
71610
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
manner that fully provides for public
participation, comment, and review).
As required by section 32(c) of the
Federal Energy Administration Act of
1974 as amended, DOE will consult
with the Attorney General and the
Chairman of the Federal Trade
Commission about the impact on
competition of using the methods
contained in these standards before
prescribing a final rule.
V. Public Participation
A. Attendance at Public Meeting
The time and date of the public
meeting are listed in the DATES and
ADDRESSES sections at the beginning of
this NOPR. The public meeting will be
held at the U.S. Department of Energy,
Forrestal Building, Room 1E–245, 1000
Independence Avenue, SW.,
Washington, DC 20585–0121. To attend
the public meeting, please notify Ms.
Brenda Edwards at (202) 586–2945. Any
foreign national wishing to participate
in the meeting should advise DOE of
this fact as soon as possible by
contacting Ms. Brenda Edwards to
initiate the necessary procedures.
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
B. Procedure for Submitting Requests to
Speak
Any person who has an interest in
today’s notice or who is a representative
of a group or class of persons that has
an interest in these issues may request
an opportunity to make an oral
presentation. Such persons may handdeliver requests to speak, along with a
computer diskette or CD in WordPerfect,
Microsoft Word, PDF, or text (ASCII) file
format to the address shown in the
ADDRESSES section at the beginning of
this NOPR between 9 a.m. and 4 p.m.
Monday through Friday, except Federal
holidays. Requests may also be sent by
mail or e-mail to
Brenda.Edwards@ee.doe.gov.
Persons requesting to speak should
briefly describe the nature of their
interest in this rulemaking and provide
a telephone number for contact. DOE
requests persons selected to be heard to
submit an advance copy of their
statements at least two weeks before the
public meeting. At its discretion, DOE
may permit any person who cannot
supply an advance copy of their
statement to participate, if that person
has made advance alternative
arrangements with the Building
Technologies Program. The request to
give an oral presentation should ask for
such alternative arrangements.
C. Conduct of Public Meeting
DOE will designate a DOE official to
preside at the public meeting and may
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
also employ a professional facilitator to
aid discussion. The meeting will not be
a judicial or evidentiary-type public
hearing, but DOE will conduct it in
accordance with section 336 of EPCA.
(42 U.S.C. 6306) A court reporter will
record the proceedings and prepare a
transcript. DOE reserves the right to
schedule the order of presentations and
to establish the procedures governing
the conduct of the public meeting. After
the public meeting, interested parties
may submit further comments on the
proceedings as well as on any aspect of
the rulemaking until the end of the
comment period.
The public meeting will be conducted
in an informal conference style. DOE
will present summaries of comments
received before the public meeting,
allow time for presentations by
participants, and encourage all
interested parties to share their views on
issues affecting this rulemaking. Each
participant will be allowed to make a
prepared general statement (within
DOE-determined time limits) prior to
the discussion of specific topics. DOE
will permit other participants to
comment briefly on any general
statements.
At the end of all prepared statements
on a topic, DOE will permit participants
to clarify their statements briefly and
comment on statements made by others.
Participants should be prepared to
answer questions from DOE and other
participants concerning these issues.
DOE representatives may also ask
questions of participants concerning
other matters relevant to this
rulemaking. The official conducting the
public meeting will accept additional
comments or questions from those
attending, as time permits. The
presiding official will announce any
further procedural rules or modification
of the above procedures that may be
needed for the proper conduct of the
public meeting.
DOE will make the entire record of
this proposed rulemaking, including the
transcript from the public meeting,
available for inspection at the U.S.
Department of Energy, 6th Floor, 950
L’Enfant Plaza, SW., Washington, DC
20024, (202) 586–2945, between 9 a.m.
and 4 p.m. Monday through Friday,
except Federal holidays. The transcript
will also be available on DOE’s Web site
at: https://www1.eere.energy.gov/
buildings/appliance_standards/
commercial/
refrigeration_equipment.html.
D. Submission of Comments
DOE will accept comments, data, and
other information regarding the
proposed rule before or after the public
PO 00000
Frm 00044
Fmt 4702
Sfmt 4702
meeting, but no later than the date
provided at the beginning of this NOPR.
Please submit comments, data, and
other information electronically to CRE–
2010–TP–0034@ee.doe.gov. Submit
electronic comments in WordPerfect,
Microsoft Word, PDF, or text (ASCII) file
format and avoid the use of special
characters or any form of encryption.
Comments in electronic format should
be identified by the docket number
EERE–2010–BT–TP–0034 and/or RIN
1904–AC40 and wherever possible carry
the electronic signature of the author.
No telefacsimiles (faxes) will be
accepted.
According to 10 CFR 1004.11, any
person submitting information that he
or she believes to be confidential and
exempt by law from public disclosure
should submit two copies: One copy of
the document including all the
information believed to be confidential
and one copy of the document with the
information believed to be confidential
deleted. DOE will make its own
determination as to the confidential
status of the information and treat it
according to its determination.
Factors of interest to DOE when
evaluating requests to treat submitted
information as confidential include (1)
A description of the items; (2) whether
and why such items are customarily
treated as confidential within the
industry; (3) whether the information is
generally known by or available from
other sources; (4) whether the
information has previously been made
available to others without obligation
concerning its confidentiality; (5) an
explanation of the competitive injury to
the submitting person which would
result from public disclosure; (6) a date
upon which such information might
lose its confidential nature due to the
passage of time; and (7) why disclosure
of the information would be contrary to
the public interest.
E. Issues on Which DOE Seeks Comment
Although comments are welcome on
all aspects of this rulemaking, DOE is
particularly interested in receiving
comments on following issues:
1. DOE’s conclusion that the proposed
test procedure changes would not be
unduly burdensome to conduct.
2. The burden to manufacturers
associated with testing NSF Type II
equipment at the standard test
condition.
3. The burden to test other energy
efficiency technologies other than those
explicitly accounted for in this test
procedure revision, namely night
curtains and lighting occupancy sensors
and scheduled control.
E:\FR\FM\24NOP1.SGM
24NOP1
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
4. Updating the referenced industry
test procedures to the most current
version.
5. The proposal for the incorporation
of night curtains into the DOE test
procedure.
6. The proposed calculation method
for treatment of lighting occupancy
sensors and controls in the DOE test
procedure for commercial refrigeration
equipment. Specifically, DOE requests
comment on the values assumed for the
time period when lighting is off or
reduced due to lighting occupancy
sensors or controls and the factor used
to scale the amount of heat produced by
case lighting.
7. The provision for testing
commercial refrigerators that cannot be
tested at 38 °F at the lowest application
product temperature.
8. The number of small businesses in
the CRE market.
9. The certification that the proposed
test procedure changes will not have a
significant impact on a substantial
number of small entities.
VI. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this NOPR.
List of Subjects in 10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation test
procedures, Incorporation by reference,
Reporting and recordkeeping
requirements.
Issued in Washington, DC, on November
10, 2010.
Cathy Zoi,
Assistant Secretary, Energy Efficiency and
Renewable Energy.
For the reasons set forth in the
preamble, DOE proposes to amend part
431 of title 10, Code of Federal
Regulations, to read as follows:
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 431
continues to read as follows:
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
Authority: 42 U.S.C. 6291–6317.
2. Section 431.62 is amended by
adding in alphabetical order the
definitions of ‘‘lighting control’’,
‘‘lighting occupancy sensor’’, ‘‘lowest
application product temperature’’, and
‘‘night curtain’’ to read as follows’’:
§ 431.62 Definitions concerning
commercial refrigerators, freezers and
refrigerator-freezers.
*
*
*
VerDate Mar<15>2010
*
*
15:12 Nov 23, 2010
Jkt 223001
Lighting control means an electronic
device that automatically adjusts the
lighting in a display case at scheduled
times throughout the day.
Lighting occupancy sensor means an
electronic device that uses passive
infrared, ultrasonic, or other motionsensing technology to detect the
presence of a customer or employee,
allowing the lights within the
equipment to be turned off or dimmed
when no motion is detected in the
sensor’s coverage area.
Lowest application product
temperature means the lowest
integrated average product temperature
achievable and maintainable within ±2
°F for the duration of the test.
Night curtain means a device that is
temporarily employed to decrease air
exchange and heat transfer between the
refrigerated case and the surrounding
environment.
*
*
*
*
*
3. Section 431.63 is amended by
revising paragraphs (b)(1), (c)
introductory text, and (c)(1) to read as
follows:
§ 431.63 Materials incorporated by
reference.
*
*
*
*
*
(b) * * *
(1) ANSI/AHAM HRF–1–2008,
(‘‘HRF–1–2008’’), Energy and Internal
Volume of Refrigerating Appliances,
including errata issued November 17,
2009, IBR approved for § 431.64.
*
*
*
*
*
(c) AHRI. Air-Conditioning, Heating
and Refrigeration Institute, 2111 Wilson
Blvd, Suite 500, Arlington, VA 22201,
(703) 524–8800, ahri@ahrinet.org, or
https://www.ahrinet.org/Content/
StandardsProgram_20.aspx.
(1) AHRI Standard 1200–2010 (‘‘AHRI
Standard 1200–2010’’), Performance
Rating of Commercial Refrigerated
Display Merchandisers and Storage
Cabinets, 2010, IBR approved for
§§ 431.64 and 431.66.
*
*
*
*
*
4. Section 431.64 is amended by
revising paragraph (b) to read as follows:
§ 431.64 Uniform test method for the
measurement of energy consumption of
commercial refrigerators, freezers, and
refrigerator-freezers.
*
*
*
*
*
(b) Testing and calculations.
Determine the daily energy
consumption of each covered
commercial refrigerator, freezer, or
refrigerator-freezer by conducting the
test procedure set forth in the AirConditioning and Refrigeration Institute
(ARI) Standard 1200–2010,
‘‘Performance Rating of Commercial
PO 00000
Frm 00045
Fmt 4702
Sfmt 4702
71611
Refrigerated Display Merchandisers and
Storage Cabinets,’’ section 3,
‘‘Definitions,’’ section 4, ‘‘Test
Requirements,’’ and section 7, ‘‘Symbols
and Subscripts.’’ (Incorporated by
reference, see § 431.63) For each
commercial refrigerator, freezer, or
refrigerator-freezer with a self-contained
condensing unit, also use ARI Standard
1200–2010, section 6, ‘‘Rating
Requirements for Self-contained
Commercial Refrigerated Display
Merchandisers and Storage Cabinets.’’
(Incorporated by reference, see § 431.63)
For each commercial refrigerator,
freezer, or refrigerator-freezer with a
remote condensing unit, also use ARI
Standard 1200–2006, section 5, ‘‘Rating
Requirements for Remote Commercial
Refrigerated Display Merchandisers and
Storage Cabinets.’’ (Incorporated by
reference, see § 431.63)
(1) For open display cases sold with
night curtains installed, the night
curtain shall be employed for 6 hours,
3 hours after the start of a defrost
period. Upon the completion of the 6hour period, the night curtain shall be
raised until the completion of the 24hour test period.
(2) For commercial refrigerators,
freezers, and refrigerator-freezers sold
with lighting occupancy sensors,
scheduled lighting controls, or lighting
occupancy sensors and scheduled
lighting controls installed on the unit,
the effect on daily energy consumption
will be calculated using the variables
that are defined as:
CECA is the Alternate Compressor
Energy Consumption (kilowatt-hours);
LECsc is the lighting energy
consumption of internal case lights with
lighting occupancy sensors and controls
deployed (kilowatt-hours);
Pli is the rated power of lights when
they are fully on (watts);
Pli(off) is the power of lights when they
are off (watts);
Pli(dim) is the power of lights when
they are dimmed (watts);
‘TDECo is the total daily energy
consumption with lights fully on, as
measured by AHRI Standard 1200–2010
(kilowatt-hours);
tdim is the time period which the lights
are dimmed due to the use of lighting
occupancy sensors or scheduled
controls (hours);
tdim,controls is the time case lighting is
dimmed due to the use of lighting
controls (hours);
tdim,sensors is the time case lighting is
dimmed due to the use of lighting
occupancy sensors (hours);
tl is the time period when lights
would be on without lighting occupancy
sensors or controls (24 hours);
E:\FR\FM\24NOP1.SGM
24NOP1
71612
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
during which the lights are off or
dimmed shall not exceed 10.8 hours.
The time the case lighting is off or
dimmed due to scheduled lighting
controls (toff,controls or tdim,controls, as
applicable) will be 8 hours for those
cases with lighting controls installed.
The time the case lighting is off or
dimmed due to lighting occupancy
sensors (toff,sensors or tdim,sensors, as
applicable) will be 10.8 hours for cases
with lighting occupancy sensors
installed. For cases with lighting
occupancy sensors and scheduled
lighting controls installed, the time the
case lighting is off or dimmed due to
lighting occupancy sensors (toff,sensors or
tdim,sensors, as applicable) will be 2.8
hours and the time the case lighting is
off or dimmed due to scheduled lighting
controls (toff,controls or tdim,controls, as
applicable) will be 8 hours.
(B) Calculate the CECA using the
following equation:
1 EER values for operating temperature
classes are calculated based on the average
EER value of all equipment in that class which
was analyzed as part of the previous (2009)
rulemaking. This does not include equipment
for which standards were set by Congress in
EPACT 2005 (VCT, VCS, HCT, HCS, and
SOC at M and L temperatures) or classes for
which standards were set using extension
multipliers in the 2009 rulemaking (VOP.SC.L,
SVO.SC.L, VOP.SC.I, SVO.SC.I, HZO.SC.I,
VOP.SC.I, SVO.SC.I, HZO.SC.I, HCS.SC.I,
SOC.SC.I).
2 These values only represent compressor
EER and do not include condenser fan energy
use.
reference, see § 431.63) The CDEC for
the entire case shall be the sum of the
CECR and LECsc (as calculated above)
and the fan energy consumption (FEC),
anti-condensate energy consumption
(AEC), defrost energy consumption
(DEC), and condensate evaporator pan
energy consumption (PEC) (as measured
in AHRI Standard 1200–2010).
(iii) For self-contained commercial
refrigerators, freezers, and refrigeratorfreezers with lighting occupancy
sensors, controls, or lighting occupancy
sensors and controls installed, the TDEC
for the entire case shall be the sum of
total daily energy consumption as
measured by the AHRI Standard 1200–
2010 (incorporated by reference, see
§ 431.63) test with the lights fully on
(TDECo) and CECA, less the decrease in
lighting energy use due to occupancy
sensors and controls, as shown in the
following equation.
The sum of tsc, toff, and tdim should equal
24 hours and the total time period
Where EER represents the energy
efficiency ratio from Table 1 in AHRI
Standard 1200–2010 (incorporated by
reference, see § 431.63) for remote
condensing equipment or the values
shown in the following table for selfcontained equipment:
EER FOR SELF-CONTAINED COMMERCIAL REFRIGERATED DISPLAY MERCHANDISERS AND STORAGE CABINETS
Operating temperature
class
Medium ...............................
Low .....................................
Ice Cream ...........................
EER
Btu/W
11.26
7.14
4.80
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
Note:
(3) Conduct the testing required in
paragraphs (b)(1) and (2) of this section,
and determine the daily energy
consumption, at the applicable
integrated average temperature in the
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
(ii) For remote condensing
commercial refrigerators, freezers, and
refrigerator-freezers with lighting
occupancy sensors, controls, or lighting
occupancy sensors and controls
installed, the revised compressor energy
consumption (CECR) shall be the CECA
added to the compressor energy
consumption (CEC) measured in AHRI
Standard 1200–2010. (Incorporated by
following table. The integrated average
temperature is determined using the
required test method. If a refrigerator or
medium temperature unit is not able to
be tested at the specified integrated
PO 00000
Frm 00046
Fmt 4702
Sfmt 4702
average temperature of 38 °F, the unit
may be tested at the lowest application
product temperature, as defined in
§ 431.61.
E:\FR\FM\24NOP1.SGM
24NOP1
EP24NO10.373
In the equation toff and tdim are
determined based on the sum of any
contribution from lighting occupancy
sensors and scheduled controls which
dim or turn off lighting, respectively, as
shown in the following equation:
EP24NO10.374
(i) For both self-contained and remote
condensing commercial refrigerators,
freezers, and refrigerator-freezers—
(A) Calculate the LECsc using the
following equation:
EP24NO10.372
toff,sensors is the time case lighting is off
due to the use of lighting occupancy
sensors (hours); and
tsc is the time period when lighting is
fully on with lighting occupancy
sensors and controls enabled (hours).
EP24NO10.371
toff is the time period which the lights
are off due to the use of lighting
occupancy sensors or scheduled
controls (hours);
toff,controls is the time case lighting is off
due to the use of lighting controls
(hours);
Federal Register / Vol. 75, No. 226 / Wednesday, November 24, 2010 / Proposed Rules
Category
Integrated average
temperatures
Test procedure
(i) Refrigerator with Solid Door(s) .....................................................
(ii) Refrigerator with Transparent Door(s) .........................................
(iii) Freezer with Solid Door(s) ..........................................................
(iv) Freezer with Transparent Door(s) ..............................................
(v) Refrigerator-Freezer with Solid Door(s) ......................................
ARI
ARI
ARI
ARI
ARI
(vi) Commercial Refrigerator with a Self-Contained Condensing
Unit Designed for Pull-Down Temperature Applications and
Transparent Doors.
(vii) Ice-Cream Freezer .....................................................................
(viii) Commercial Refrigerator, Freezer, and Refrigerator-Freezer
with a Self-Contained Condensing Unit and without Doors.
38 °F (±2 °F).
38 °F (±2 °F).
0 °F (±2 °F).
0 °F (±2 °F).
38 °F (±2 °F) for refrigerator compartment.
0 °F (±2 °F) for freezer compartment.
38 °F (±2 °F).
ARI Standard 1200–2010*
(ix) Commercial Refrigerator, Freezer, and Refrigerator-Freezer
with a Remote Condensing Unit.
Standard
Standard
Standard
Standard
Standard
71613
1200–2010*
1200–2010*
1200–2010*
1200–2010*
1200–2010*
ARI Standard 1200–2010*
ARI Standard 1200–2010*
ARI Standard 1200–2010* ....
¥15.0 °F (±2 °F).
(A) For low temperature applications, the integrated average temperature of all test
package averages shall be 0 °F (±2 °F).
(B) For medium temperature applications,
the integrated average temperature of all
test package averages shall be 38.0 °F
(±2 °F).
(A) For low temperature applications, the integrated average temperature of all test
package averages shall be 0 °F (±2 °F).
(B) For medium temperature applications,
the integrated average temperature of all
test package averages shall be 38.0 °F
(±2 °F).
* Incorporated by reference, see § 431.63.
(4) Determine the volume of each
covered commercial refrigerator, freezer,
or refrigerator-freezer using the
methodology set forth in the AHAM
HRF–1–2008, ‘‘Energy and Internal
Volume of Refrigerating Appliances,’’
(incorporated by reference, see § 431.63)
section 3.30, ‘‘Volume,’’ and sections 4.1
through 4.3, ‘‘Method for Computing
Refrigerated Volume of Refrigerators,
Refrigerator-Freezers, Wine Chillers and
Freezers.’’
[FR Doc. 2010–29210 Filed 11–23–10; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF ENERGY
Federal Energy Regulatory
Commission
18 CFR Part 40
[Docket No. RM10–15–000]
Mandatory Reliability Standards for
Interconnection Reliability Operating
Limits
November 18, 2010.
Federal Energy Regulatory
Commission.
ACTION: Notice of proposed rulemaking.
jdjones on DSK8KYBLC1PROD with PROPOSALS-1
AGENCY:
Under section 215 of the
Federal Power Act, the Federal Energy
Regulatory Commission proposes to
approve three new Interconnection
Reliability Operations and Coordination
Reliability Standards and seven revised
Reliability Standards related to
Emergency Preparedness and
SUMMARY:
VerDate Mar<15>2010
15:12 Nov 23, 2010
Jkt 223001
Operations, Interconnection Reliability
Operations and Coordination, and
Transmission Operations. These
proposed Reliability Standards were
submitted to the Commission for
approval by the North American Electric
Reliability Corporation, which the
Commission has certified as the Electric
Reliability Organization responsible for
developing and enforcing mandatory
Reliability Standards. The proposed
Reliability Standards were designed to
prevent instability, uncontrolled
separation, or cascading outages that
adversely impact the reliability of the
interconnection by ensuring prompt
action to prevent or mitigate instances
of exceeding Interconnection Reliability
Operating Limits. The Commission also
proposes to approve the addition of two
new terms to the NERC Glossary of
Terms. In addition, pursuant to section
215(d)(5) of the Federal Power Act, the
Commission proposes to direct NERC to
develop a modification to the proposed
term ‘‘Real-time Assessment’’ to address
a specific concern identified by the
Commission. The Commission raises
some concerns with regard to certain
aspects of NERC’s proposals and, based
on the responses from NERC and
industry, may choose to direct certain
modifications to the proposed new and
revised Reliability Standard, as well as
the new Glossary Terms, as discussed
below.
DATES: Comments are due January 24,
2011.
ADDRESSES: You may submit comments,
identified by docket number and in
PO 00000
Frm 00047
Fmt 4702
Sfmt 4702
accordance with the requirements
posted on the Commission’s Web site,
https://www.ferc.gov. Comments may be
submitted by any of the following
methods:
• Agency Web site: Documents
created electronically using word
processing software should be filed in
native applications or print-to-PDF
format, and not in a scanned format, at
https://www.ferc.gov/docs-filing/
efiling.asp.
• Mail/Hand Delivery: Commenters
unable to file comments electronically
must mail or hand-deliver an original
copy of their comments to: Federal
Energy Regulatory Commission,
Secretary of the Commission, 888 First
Street, NE., Washington, DC 20426.
These requirements can be found on the
Commission’s Web site, see, e.g., the
‘‘Quick Reference Guide for Paper
Submissions,’’ available at
https://www.ferc.gov/docs-filing/
efiling.asp or via phone from FERC
Online Support at (202) 502–6652 or
toll-free at 1–866–208–3676.
FOR FURTHER INFORMATION CONTACT:
Darrell Piatt (Technical Information),
Office of Electric Reliability, Division
of Reliability Standards, Federal
Energy Regulatory Commission, 888
First Street, NE., Washington, DC
20426, Telephone: (202) 502–6687;
A. Cory Lankford (Legal Information),
Office of the General Counsel, Federal
Energy Regulatory Commission, 888
First Street, NE. Washington, DC
20426, Telephone: (202) 502–6711;
William Edwards (Legal Information),
Office of the General Counsel, Federal
E:\FR\FM\24NOP1.SGM
24NOP1
Agencies
[Federal Register Volume 75, Number 226 (Wednesday, November 24, 2010)]
[Proposed Rules]
[Pages 71596-71613]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2010-29210]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Part 431
[Docket No. EERE-2010-BT-TP-0034]
RIN 1904-AC40
Energy Efficiency Program for Certain Commercial and Industrial
Equipment: Test Procedures for Commercial Refrigeration Equipment
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Notice of proposed rulemaking and public meeting.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (DOE) proposes amendments to its
test procedure for commercial refrigeration equipment (CRE). The
amendments would update the referenced industry test procedures to the
most current version, incorporate methods to evaluate the energy
impacts resulting from the use of night curtains and lighting occupancy
sensors, and allow testing of certain commercial refrigerators at their
lowest application product temperature. These test procedures will
apply to commercial refrigerators, freezers, and refrigerator-freezers,
as defined in the Energy Policy and Conservation Act of 1975 (EPCA), as
amended. Use of any amended test procedures will be required on the
compliance date of any standards developed in the associated energy
conservation standard rulemaking. DOE will hold a public meeting to
receive and discuss comments on the proposal.
DATES: DOE will hold a public meeting in Washington, DC on Thursday,
January 6, 2011, from 9 a.m. to 4 p.m. Additionally, DOE plans to
conduct the public meeting via webinar. DOE will accept comments, data,
and other information regarding this notice of proposed rulemaking
(NOPR) before or after the public meeting, but no later than January
24, 2011. See section V, ``Public Participation,'' of this NOPR for
details.
You can attend the public meeting via webinar, and registration
information, participant instructions, and information about the
capabilities available to webinar participants will be published on the
following Web site: https://www1.gotomeeting.com/join/638471849.
Participants are responsible for ensuring their systems are compatible
with the webinar software.
The purpose of the meeting is to receive comments and to help DOE
understand potential issues associated with this proposed rulemaking.
DOE must receive requests to speak at the meeting before 4 p.m.,
Thursday, December 22, 2010. DOE must receive a signed original and an
electronic copy of statements to be given at the public meeting before
4 p.m., Thursday, December 29, 2010.
ADDRESSES: The public meeting will be held at the U.S. Department of
Energy, Forrestal Building, Room 1E-245, 1000 Independence Avenue, SW.,
Washington, DC 20585-0121. Please note that foreign nationals planning
to participate in the public meeting are subject to advance security
screening procedures which require advance notice of 30 days prior to
attendance of the public meeting. If a foreign national wishes to
participate in the public meeting, please inform DOE of this fact as
soon as possible by contacting Ms. Brenda Edwards at (202) 586-2945 so
that the necessary procedures can be completed.
Interested parties may submit comments, identified by docket number
EERE-2010-BT-TP-0034 or Regulation Identifier Number (RIN) 1904-AC40,
by any of the following methods:
Federal eRulemaking Portal: https://www.regulations.gov.
Follow the instructions for submitting comments.
E-mail: CRE-2010-TP-0034@ee.doe.gov. Include the docket
number EERE-2010-BT-TP-0034 and/or RIN 1904-AC40 in the subject line of
the message.
Postal Mail: Ms. Brenda Edwards, U.S. Department of
Energy, Building Technologies Program, Mailstop EE-2J, 1000
Independence Avenue, SW., Washington, DC 20585-0121. Please submit one
signed paper original.
Hand Delivery/Courier: Ms. Brenda Edwards, U.S. Department
of Energy, Building Technologies Program, 6th Floor, 950 L'Enfant
Plaza, SW., Washington, DC 20024. Telephone: (202) 586-2945. Please
submit one signed paper original.
Written comments regarding the burden-hour estimates or other
aspects of the collection-of-information requirements contained in this
proposed rule may be submitted to Office of Energy Efficiency and
Renewable Energy through the methods listed above and by e-mail to
Christine_J._Kymn@omb.eop.gov.
Instructions: All submissions must include the docket number or RIN
for this rulemaking. For detailed instructions on submitting comments
and additional information on the rulemaking process, see section V,
``Public Participation,'' of this document.
Docket: For access to the docket to read background documents or
comments received, visit the U.S. Department of Energy, 6th Floor, 950
L'Enfant Plaza, SW., Washington, DC 20024, (202) 586-2945, between 9
a.m. and 4 p.m., Monday through Friday, except Federal holidays. Please
call Ms. Brenda Edwards at (202) 586-2945 for additional information
regarding visiting the Resource Room.
FOR FURTHER INFORMATION CONTACT: Mr. Charles Llenza, U.S. Department of
Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies, EE-2J, 1000 Independence Avenue, SW., Washington, DC
20585-0121. Telephone: (202) 586-2192, Charles_Llenza@ee.doe.gov. In
the Office of General Council contact Mr.
[[Page 71597]]
Michael Kido, U.S. Department of Energy, Office of General Counsel, GC-
71, 1000 Independence Avenue, SW., Washington, DC 20585-0121, (202)
586-8145, Michael.Kido@hq.doe.gov; or Ms. Elizabeth Kohl, U.S.
Department of Energy, Office of General Counsel, GC-71, 1000
Independence Avenue, SW., Washington, DC 20585-0121, (202) 586-7796,
Elizabeth.Kohl@hq.doe.gov.
For information on how to submit or review public comments and on
how to participate in the public meeting, contact Ms. Brenda Edwards,
U.S. Department of Energy, Office of Energy Efficiency and Renewable
Energy, Building Technologies Program, EE-2J, 1000 Independence Avenue,
SW., Washington, DC 20585-0121. Telephone (202) 586-2945. E-mail:
Brenda.Edwards@ee.doe.gov.
SUPPLEMENTARY INFORMATION:
I. Authority and Background
A. Authority
B. Background
C. Standby Mode and Off Mode
II. Summary of the Proposed Rule
III. Discussion
A. Framework Comment Summary and DOE Responses
1. Coordination With Other Programs
2. Coordination With the Air-Conditioning, Heating and
Refrigeration Institute
3. Burden of Testing
4. Testing of Transient Technologies and at Variable
Refrigeration Load
5. Rating Temperatures
6. Energy Efficiency Features
B. Summary of the Test Procedure Revisions
1. Update References to Industry Test Procedures to Most Current
Versions
2. Include Method for Determining Energy Savings Due to the Use
of Night Curtains on Open Cases
3. Include Calculation for Determining Energy Savings Due to Use
of Lighting Occupancy Sensors or Controls
4. Include Provision for Testing at Lowest Application Product
Temperature.
IV. Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the National Environmental Policy Act
C. Review Under the Regulatory Flexibility Act
D. Review Under the Paperwork Reduction Act
E. Review Under the Unfunded Mandates Reform Act of 1995
F. Review Under the Treasury and General Government
Appropriations Act, 1999
G. Review Under Executive Order 13132
H. Review Under Executive Order 12988
I. Review Under the Treasury and General Government
Appropriations Act, 2001
J. Review Under Executive Order 13211
K. Review Under Executive Order 12630
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
V. Public Participation
A. Attendance at Public Meeting
B. Procedure for Submitting Requests to Speak
C. Conduct of Public Meeting
D. Submission of Comments
E. Issues on Which DOE Seeks Comment
VI. Approval of the Office of the Secretary
I. Authority and Background
A. Authority
Title III of EPCA (42 U.S.C. 6291 et seq.) as amended by the Energy
Policy Act of 2005 (EPACT 2005) establishes an energy conservation
program for certain commercial and industrial equipment (42 U.S.C.
6311-6317). EPCA prescribes energy conservation standards for certain
self-contained commercial refrigerators, freezers, and refrigerator-
freezers with solid or transparent doors and designed for a pull-down
or holding temperature application. (42 U.S.C. 6313(c)(2)-(3)) EPCA
also requires DOE to develop standards for ice-cream freezers; self-
contained commercial refrigerators, freezers, and refrigerator-freezers
without doors; and remote condensing commercial refrigerators,
freezers, and refrigerator-freezers. (42 U.S.C. 6313(c)(4)(A)) DOE
published a final rule establishing standards for these equipment
classes on January 9, 2009. 74 FR 1091.
Manufacturers of covered equipment, including commercial
refrigeration equipment, must use prescribed test procedures to measure
energy efficiency or use and certify to DOE that equipment complies
with energy conservation standards. (42 U.S.C. 6311(3) and (4)) The
current test procedures for commercial refrigeration equipment appear
under Title 10 of the Code of Federal Regulations (CFR) part 431,
subpart C.
EPCA requires DOE to conduct an evaluation of each class of covered
equipment at least once every 7 years to determine whether to, among
other things, amend the test procedures for such equipment. Any amended
test procedures must be reasonably designed to produce test results
that reflect energy efficiency, energy use, and estimated operating
costs during a representative average use cycle and must not be unduly
burdensome to conduct. (42 U.S.C. 6314(a)(2))
In addition, EPCA contains specific provisions relating to test
procedures for commercial refrigeration equipment. Test procedures for
commercial refrigerators, freezers, and refrigerator-freezers must be:
(1) The test procedures determined to be generally accepted industry
testing procedures; or (2) rating procedures developed or recognized by
the American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE) or by the American National Standards Institute
(ANSI). (42 U.S.C. 6314(a)(6)(A)(i)) EPCA also establishes initial test
procedures for self-contained refrigerators, freezers, and
refrigerator-freezers with doors. These test procedures are the ASHRAE
117 test procedures that went into effect on January 1, 2005. (42
U.S.C. 6314(a)(6)(A)(ii))
If ASHRAE 117 is amended, however, the Secretary must, by rule,
amend the DOE test procedure to ensure consistency with the amended
ASHRAE 117 unless certain findings are made by clear and convincing
evidence. In addition, if a test procedure other than ASHRAE 117 is
approved by ANSI, the Secretary must review the relative strengths and
weaknesses of the new test procedure relative to the ASHRAE 117 test
procedure and, based on that review, adopt one new test procedure for
use in the standards program. (42 U.S.C. 6314(a)(6)(E)-(F))
In 2006 DOE published a final rule that adopted ANSI/Air-
Conditioning and Refrigeration Institute (ARI) Standard 1200-2006
(hereafter referenced as ARI Standard 1200-2006) as the referenced test
procedure for measuring energy consumption and ANSI/Association of Home
Appliance Manufacturers (AHAM) Standard HRF-1-2004 (hereafter referred
to as AHAM HRF-1-2004) for measuring refrigerated compartment volume.
71 FR 71370. These industry standards for commercial refrigeration
equipment have since been updated from the procedures currently
referenced in the regulations. As stated previously, EPCA authorizes
DOE to review the merits of the updated industry test procedures. If
DOE determines that a test procedure amendment is warranted, DOE must
publish proposed test procedures and offer the public an opportunity to
present oral and written comments on the amendment. (42 U.S.C. 6314(b))
B. Background
ASHRAE Standard 117-2002, ``Method of Testing Closed
Refrigerators,'' was the test procedure for commercial refrigeration
equipment for which standards were specified in EPACT 2005. EPACT 2005
mandated use of the ASHRAE 117 standard in effect on January 1, 2005.
(42 U.S.C. 6314(a)(6)(A)(ii)) Subsequently, ASHRAE amended this test
procedure and adopted ASHRAE Standard 72-2005, ``Method of Testing
Commercial Refrigerators and Freezers,'' which was approved by ANSI on
July 29, 2005. DOE reviewed ASHRAE Standard 72-2005, as well as ARI
Standard 1200-2006, which was approved by ANSI on August 28, 2006. (42
U.S.C.
[[Page 71598]]
6314(a)(6)(E)-(F)) DOE determined that ARI Standard 1200-2006 includes
the test procedures in ASHRAE Standard 72-2005 as well as the rating
temperatures prescribed in EPACT 2005. As a result, DOE published a
final rule on December 8, 2006 in which it adopted ARI Standard 1200-
2006, ``Performance Rating of Commercial Refrigerated Display
Merchandisers and Storage Cabinets,'' as the DOE test procedure for
commercial refrigeration equipment. 71 FR 71370; 10 CFR 431.63-431.64.
ARI Standard 1200-2006 contains rating temperature specifications of 38
degrees Fahrenheit ([deg]F) (2 [deg]F) for commercial
refrigerators and refrigerator compartments, 0 [deg]F (2
[deg]F) for commercial freezers and freezer compartments, and -5 [deg]F
(2 [deg]F) for commercial ice-cream freezers. In the test
procedure final rule, DOE adopted a -15 [deg]F (2 [deg]F)
rating temperature for commercial ice-cream freezers, rather than the -
5 [deg]F (2 [deg]F) prescribed in the ARI Standard 1200-
2006. During the 2006 test procedure rulemaking, DOE determined that
testing at a -15 [deg]F (2 [deg]F) rating temperature was
more representative of the actual energy consumption of commercial
freezers specifically designed for ice cream application. 71 FR 71357.
In addition, DOE adopted AHAM Standard HRF-1-2004, ``Energy,
Performance and Capacity of Household Refrigerators, Refrigerator-
Freezers and Freezers,'' for measuring compartment volumes for
equipment covered under this rule. 71 FR 71370 (Dec. 8, 2006).
Since the publication of the final rule, ARI has merged with the
Gas Appliance Manufacturers Association (GAMA) to form the Air-
Conditioning, Heating and Refrigeration Institute (AHRI) and updated
its test procedure, the most recent version of which is AHRI Standard
1200-2010. AHRI Standard 1200-2010 includes changes to the equipment
class nomenclature used in the test procedure, the method of
normalizing equipment energy consumption, the ice-cream freezer test
temperature, and other minor differences. These changes aligned the
AHRI test procedure with the nomenclature and methodology used in DOE's
2009 standards rulemaking on commercial refrigeration equipment. DOE
proposes to reference AHRI 1200-2010, the test procedure currently used
in industry.
Similarly, AHAM has updated Standard HRF-1-2004 to the most recent
version, AHAM HRF-1-2008. The changes to this standard are mostly
editorial and involved reorganizing some of the sections for simplicity
and usability. As part of the reorganization, the HRF-1-2004 section
numbers that are referenced within the DOE test procedure were updated
to the structure in HRF-1-2008. However, the content of those sections
was not substantially changed. The newly updated AHRI Standard 1200-
2010 references the most recent version of the AHAM standard, AHAM HRF-
1-2008. As such, DOE proposes to update the referenced test procedure
to adopt AHAM HRF-1-2008 as the prescribed method for determining
refrigerated compartment volume.
DOE also proposes changes to the test procedure to better address
certain energy efficiency features for which the current test procedure
cannot account. During the 2009 energy conservation standards
rulemaking, DOE screened out several energy efficiency technologies
because their effects were not captured by the current test procedure.
72 FR 41162, 41179-80 (July 26, 2007). DOE proposes modifications to
its test procedure to better address some of these technologies.
Specific changes include provisions for measuring the impact of night
curtains and lighting occupancy sensors and controls.
On May 18, 2010, DOE held a public meeting (the May 2010 Framework
public meeting) to discuss the rulemaking framework for the concurrent
commercial refrigeration equipment (CRE) energy conservation standard
(docket number EERE-2010-BT-STD-0003). During this May 2010 Framework
public meeting, DOE received comments from several interested parties
that additional rating temperatures should be considered in the test
procedure. Some equipment is designed for storing goods such as wine,
candy, and flowers at temperatures that are held constant, but are
higher than the temperatures typically used in commercial
refrigerators. The commenters stated that some covered refrigeration
equipment designed for operation at higher temperatures is not able to
be tested at the prescribed 38 [deg]F, and they suggested that DOE
consider this in the test procedures and standards rulemakings.
Consequently, DOE proposes provisions for testing commercial
refrigeration equipment that is designed to operate at temperatures
higher than 38 [deg]F at the lowest possible application product
temperature.
C. Standby Mode and Off Mode
The Energy Independence and Security Act of 2007 (EISA 2007; Pub.
L. 110-140) amended EPCA to require DOE, for each covered product for
which current test procedures do not account for standby and off mode
energy consumption, to modify the test procedures to integrate such
energy consumption into the energy descriptor(s) for that product, if
technically feasible. Otherwise, DOE must prescribe a separate standby
and off mode energy use test procedure, if technically feasible. (42
U.S.C. 6295(gg)(2)(A)) EISA 2007 also requires any final rule to
establish or revise a standard for a covered product, adopted after
July 1, 2010, to incorporate standby mode and off mode energy use into
a single amended or new standard, if feasible. (42 U.S.C.
6295(gg)(3)(A)) DOE currently believes that the ``off mode'' and
``standby mode'' conditions of operation do not apply to the equipment
covered by this rulemaking because the provision within EISA which
stipulates that off mode and standby mode energy usage must be
quantified only appears in relation to consumer products and is not
required for commercial equipment. Additionally, commercial
refrigeration equipment, whether in retail, foodservice, or other
applications, operates 24 hours a day, 7 days a week to maintain
product at the necessary temperature for safe storage or retailing.
Therefore, standby and off modes will not be considered for commercial
refrigeration equipment.
II. Summary of the Proposed Rule
DOE is considering modifications to its test procedure to
incorporate the current industry-accepted test procedures, address
certain energy efficiency features that currently are not accounted for
in the test procedure (light occupancy sensors and night curtains), and
allow testing of commercial refrigeration equipment that cannot be
tested at one of the three currently specified product test
temperatures.
EPCA prescribes that if any rulemaking amends a test procedure, DOE
must determine ``to what extent, if any, the proposed test procedure
would alter the measured energy efficiency * * * of any covered product
as determined under the existing test procedure.'' (42 U.S.C.
6293(e)(1); 6314(a)(6)) Further, if DOE determines that the amended
test procedure would alter the measured efficiency of a covered
product, DOE must amend the applicable energy conservation standard
accordingly. (42 U.S.C. 6293(e)(2); 6314(a)(6)) DOE recognizes that the
proposed test procedure amendments would affect the measured energy use
of commercial refrigeration equipment. DOE is considering amending the
standards currently in effect for commercial refrigeration equipment in
a concurrent rulemaking. DOE will
[[Page 71599]]
consider these proposed test procedure amendments as any final energy
conservation standards are developed.
DOE also proposes to require use of any amended test procedures to
be consistent with the compliance date of any revised energy
conservation standards. DOE would add language to any final test
procedure amendments to the effect that the amendments need not be
performed at that time to determine compliance with the current energy
conservation standards. Instead, manufacturers would be required to use
the amended test procedures to demonstrate compliance with DOE's energy
conservation standards on the compliance date of any final rule
establishing amended energy conservation standards for commercial
refrigeration equipment.
Further clarification would also be provided that, as of 360 days
after publication of any test procedure final rule, representations as
to the energy consumption of any covered products would need to be
based on results generated using the amended test procedure. (42 U.S.C.
6314(d))
III. Discussion
As part of the current rulemaking on the energy conservation
standard for commercial refrigeration equipment, DOE held a public
meeting on May 18, 2010 to present its framework document (https://www1.eere.energy.gov/buildings/appliance_standards/commercial/pdfs/cre_framework_04-30-10.pdf and to receive comments from interested
parties. DOE considered the comments received as a result of the
framework document public meeting and incorporated recommendations,
where appropriate, that applied to the test procedure.
In Section 0, DOE provides responses to comments in the following
subject areas:
1. Coordination With Other Programs;
2. Coordination with AHRI;
3. Burden of Testing;
4. Transient Testing;
5. Rating Temperatures; and
6. Energy Efficiency Features.
Section III.B provides a summary of the proposed revisions to the
test procedure at 10 CFR part 431, subpart C, ``Uniform test method for
measuring the energy consumption of commercial refrigerators, freezers,
and refrigerator-freezers.'' These proposed revisions include:
1. Update References to Industry Test Procedures to Most Current
Version;
2. Include Method for Determining Energy Savings Due to the Use of
Night Curtains on Open Cases;
3. Include Calculation for Determining Energy Savings Due to Use of
Lighting Occupancy Sensors or Controls;
4. Include Provision for Testing at Lowest Application Product
Temperature.
Comments relevant to these subject areas are also addressed in
section III.B.
A. Framework Comment Summary and DOE Responses
1. Coordination With Other Programs
During the Framework public meeting, DOE received several comments
regarding the potential overlap between testing performed for the
purposes of compliance with DOE standards and testing performed for
certification for voluntary energy efficiency programs. Continental
stated that testing requirements should be unified between ENERGY
STAR[supreg] and DOE standards. (Continental, No. 1.2.006 at p. 190
\1\) Continental also stated that a common database of certified
equipment should be shared between DOE and the U.S. Environmental
Protection Agency ENERGY STAR program. (Continental, No. 1.2.006 at pp.
190-191)
---------------------------------------------------------------------------
\1\ In the following discussion, comments will be presented
along with a notation in the form ``Continental, No. 1.2.006 at p.
190,'' which identifies a written comment DOE received and included
in the docket of this rulemaking. DOE refers to comments based on
when the comment was submitted in the rulemaking process. Section
1.1.XXX refers to Federal Register documents, section 1.2.XXX refers
public meeting support documents, and 1.3.XXX refers to comments
submitted by interested parties. This particular notation refers to
a comment (1) By Continental, (2) in document number 6 in the public
meeting support materials, and (3) appearing on page 190.
---------------------------------------------------------------------------
The use of common test procedures, reporting, and test data
repository pertains to many commercial and residential products,
including commercial refrigeration equipment. ENERGY STAR currently
requires testing according to ASHRAE Standard 72-2005. ASHRAE Standard
72-2005 is referenced as the method of test in ARI Standard 1200-2006,
DOE's current referenced test procedure, as well as AHRI Standard 1200-
2010, which DOE proposes to incorporate by reference in today's test
procedure. As a result, DOE believes that testing according to ARI
standard 1200-2006 or 1200-2010 would be sufficient for purposes of
ENERGY STAR certification.
DOE acknowledges that manufacturers may have to submit separate
reports for showing compliance with ENERGY STAR and DOE energy
conservation standards. Reporting requirements for the purposes of
certification and compliance with DOE energy conservation standards are
currently being addressed under a separate rulemaking (docket number
EERE-2010-BT-STD-0003). DOE believes that further analysis or effort to
coordinate a common database or other aspects with the ENERGY STAR
program pertain to many covered products, both commercial and
residential, and should be addressed in the context of that rulemaking
rather than this test procedure rulemaking.
2. Coordination with the Air-Conditioning, Heating and Refrigeration
Institute
Many interested parties provided DOE with comments regarding
coordination between DOE and AHRI in the development of test
procedures. AHRI reminded stakeholders that AHRI Standard 1200, which
is referenced in the DOE test procedure, is under constant review, and
invited interested parties, including DOE, to participate in this
review. (AHRI, No. 1.2.006 at p. 71, No. 1.3.008 at p. 3) AHRI also
expressed support for DOE's plan to adopt the 2008 version of AHRI
Standard 1200. (AHRI, No. 1.3.008 at p. 3) Similarly, DOE was
encouraged to participate in the ASHRAE and AHRI standards revision
processes to ensure continuity between Federal and industry standards.
(True, No. 1.2.006 at p. 72) California Codes and Standards likewise
agreed that DOE should coordinate with AHRI to update AHRI Standard
1200. (California Codes and Standards, No. 1.3.005 at pp. 2-3) A joint
comment submitted by the Northwest Energy Efficiency Alliance and the
Northwest Power and Conservation Council (Northwest Joint Comment)
agreed with the use of AHRI Standard 1200 as the basis for testing, but
urged DOE to begin updating its own test procedure in parallel with its
efforts to clarify equipment classes. (Adjuvant Consulting, No. 1.3.003
at p. 3) Further, the Northwest Joint Comment stated that AHRI Standard
1200 will need updating for this rulemaking because it excludes some
equipment classes, may not have universally applicable test conditions,
and is unable to quantify the effects of some technology options. The
Northwest Joint Comment also stated that AHRI Standard 1200 should be
modified to capture the impacts of all technologies considered by DOE
in the rulemaking and appropriate operating regimes. (Adjuvant
Consulting, No. 1.3.003 at pp. 2-3)
During the development of these proposed test procedures
amendments, DOE closely followed the activities of engineering
committees that oversee AHRI Standard 1200 and ASHRAE
[[Page 71600]]
Standard 72 and will continue to stay abreast of AHRI and ASHRAE
efforts to revise and update their respective test procedures and
standards. In the interest of coordinating with AHRI, DOE proposes to
update the references in the DOE test procedure to the most recent
version of AHRI Standard 1200, AHRI Standard 1200-2010. DOE also
proposes to amend aspects of this testing protocol as part of the DOE
procedure to capture the performance of certain energy efficiency
features, as described in section III.B. Regarding equipment classes
that may be excluded from AHRI Standard 1200, DOE believes that all
equipment classes for which DOE intends to set standards are able to be
tested using AHRI Standard 1200-2010. Also, DOE believes the test
conditions currently prescribed in AHRI Standard 1200-2010 are
applicable to all commercial refrigeration equipment covered under this
rulemaking with the exception of equipment that cannot be tested at the
38 [deg]F integrated average product temperature, see further
discussion in sections III.A.5 and III.B.4.
3. Burden of Testing
During the Framework public meeting, and in written comments,
several interested parties expressed concern regarding the burden of
testing. Master-Bilt stated that transitioning to a system of third-
party testing would more than double its testing costs. (Master-Bilt,
No. 1.2.006 at p. 200) Zero Zone commented that changes to the test
procedure would make existing test data invalid, would possibly require
multiple tests at different configurations, and would increase costs.
(Zero Zone, No. 1.3.007 at p. 1) True expressed a concern that there is
a learning curve associated with how to test equipment at standard
conditions (True, No. 1.2.006 at pp. 133-134) and that introducing
additional test conditions would significantly increase the cost and
burden of testing. (True, No. 1.2.006 at pp. 131-132)
DOE understands that amending test procedures or including
additional provisions in those test procedures could increase the
burden on manufacturers to quantify the performance of their equipment.
EPCA requires that the test procedures promulgated by DOE be reasonably
designed to produce test results that reflect energy efficiency, energy
use, and estimated operating costs of the covered equipment during a
representative average use cycle. It also requires that the test
procedure not be unduly burdensome to conduct. (42 U.S.C. 6314(a)(2))
DOE has analyzed the expected incremental cost of the proposed test
procedure changes and its impact on manufacturers. The proposed changes
to the test procedure consist of: Updating the referenced industry test
procedures to the most current versions; testing requirements for units
sold with night curtains and lighting occupancy sensors or controls
installed; and provisions for testing units that cannot operate at the
specified 38 [deg]F integrated average product temperature.
All commercial refrigeration equipment for which standards were set
in EPACT 2005 are currently required to be tested using the DOE test
procedure to show compliance with the EPACT 2005 standard levels.
Equipment for which standards were set in the 2009 final rule will
similarly be required to test units using the DOE test procedure to
show compliance with the 2009 standards levels beginning January 1,
2012. The current DOE test procedure references AHRI Standard 1200-2006
and AHAM HRF-1-2004. This test procedure consists of one 24-hour test
at standard rating conditions to determine daily energy consumption.
The updated versions of AHRI Standard 1200-2010 and AHAM HRF-1-2008
do not vary substantially from the previously referenced versions.
Aligning the DOE test procedure with the most recent industry test
procedures currently in use--AHRI standard 1200-2010 and AHAM HRF-1-
2008--will simplify testing requirements and reduce the burden of
testing for both small and large manufacturers.
For equipment that could be sold with night curtains installed, the
current test procedure requires one 24-hour test without the night
curtain installed. To minimize the additional burden of test on
manufacturers, under the proposed revisions, if a unit is tested and
shows compliance with the relevant energy conservation standard without
night curtains installed, that unit can also be sold with night
curtains installed without additional testing. In addition, if a
manufacturer chose to sell cases only with night curtains installed,
only one 24-hour test would be required. If, however, a piece of
equipment does not meet DOE's energy conservation standards without
night curtains installed, DOE proposes to allow the unit to be tested a
second time with night curtains installed. In this instance, assuming
the energy conservation standard is met, the case would also be
required to be sold with night curtains installed. This would require
an increased burden of test on only those units that cannot show
compliance with DOE energy conservation standards without night
curtains installed. As DOE proposes to incorporate provisions for
testing a unit with night curtains installed into the same 24-hour
test, the burden of conducting the test with and without night curtains
is approximately the same.
For units sold with lighting occupancy sensors and scheduled
controls installed, no additional testing or measurements will be
required. Manufacturers will use a calculation method to determine the
energy savings due to lighting occupancy sensors and scheduled
controls. DOE believes that additional calculations will only require a
few additional minutes of testing time, which represents approximately
a 25-percent increase in the calculation intensity of the test. When
compared to the physical testing segment of the procedure, which takes,
a minimum of 24 hours, the additional calculations required by the
lighting occupancy sensor and scheduled control requirements would
increase the total burden of the test by less than an estimated 0.01
percent. In addition, this additional burden would be required only for
units that cannot comply with the energy conservation standard with
lighting occupancy sensors or controls installed. Thus, DOE believes
that the proposed additional calculations for lighting occupancy
sensors and controls would not significantly increase the burden of
test for manufacturers of covered products.
For equipment that cannot be tested at the 38 [deg]F integrated
average product temperature, manufacturers are currently required to
test the unit using AHRI Standard 1200 at the 38 [deg]F test
temperature. Under the proposed revisions, these manufacturers would be
allowed to test units that cannot meet the 38 [deg]F test temperature
to be tested at the lowest application product temperature, with the
only difference being the integrated average product temperature. Since
the same test is being performed in both cases, DOE believes that this
will not increase the burden of test for those manufacturers and is
likely to lead to more representative energy consumption values. DOE
notes that AHRI Standard 1200-2010 test is often already performed by a
manufacturer for participation in voluntary programs, independent
collection of energy consumption information, or other reasons.
The proposed changes to the test procedure for commercial
refrigeration equipment were chosen to help minimize the impact of
additional testing while updating industry standards to reflect the
most current
[[Page 71601]]
versions, capture new energy efficiency technologies, and provide more
accurate test procedures for equipment that cannot be tested at the
currently prescribed integrated average product temperature. For the
reasons stated above, DOE believes that the proposed test procedures
would not be unduly burdensome to conduct.
For further discussion of the economic impact of additional testing
on the small CRE manufacturers, as the entities that would be the most
impacted from additional testing requirements, please see section IV.C
of today's NOPR.
DOE requests comment on its conclusion that the proposed test
procedure changes would not be unduly burdensome to conduct.
4. Testing of Transient Technologies and at Variable Refrigeration Load
During the Framework public meeting and comment period, several
interested parties commented on incorporating provisions into the test
procedure to capture the effects of features that operate to reduce
energy consumption at variable refrigeration load or at variable time
periods. California Codes and Standards stated that ASHRAE Standard 72
is only a steady-state test, and that the test would not capture a
number of transient measures that may produce significant energy
savings in the field. (California Codes and Standards, No. 1.2.006 at
p. 13) The American Council for an Energy-Efficient Economy (ACEEE)
emphasized that it believes that a single metric is not adequate to
describe CRE operation and that DOE should at least look at part-load
and full-load metrics. (ACEEE, No. 1.2.006 at pp. 69-70) California
Codes and Standards also stated that test methods should be developed
for the purpose of measuring the maximum possible energy savings, and
that this should include a part-load test. (California Codes and
Standards, No. 1.3.005 at p. 1)
DOE finds that there are two types of transient technologies: Those
that operate as a function of variable ambient conditions and those
that operate at variable times to reduce refrigeration load. DOE
discussed the technologies that operate at variable times (night
curtains and occupancy sensors) in section A.3 above; a discussion of
the technologies that operate as a function of variable ambient
conditions is provided below.
Technologies that operate as a function of variable ambient
conditions can reduce annual energy consumption of commercial
refrigeration equipment by adapting to changes in refrigeration load
that result from changes in ambient conditions. These variable load, or
part-load, technologies include higher efficiency expansion valves,
condenser fan motor controllers, and anti-sweat heater controllers.
ASHRAE Standard 72-2005 calls for testing at a single ambient
temperature and relative humidity, so technologies that are designed to
reduce energy use under variable ambient conditions will not affect the
measured combined daily energy consumption (CDEC) per the existing test
procedure.
An independent test to quantify the performance of technologies
that decrease energy use at variable refrigeration load would most
likely involve testing a unit at different ambient conditions,
including lower temperatures and humidities. However, section 342 of
EPCA requires that test procedures ``shall be reasonably designed to
produce test results which reflect energy efficiency, energy use, and
estimated operating costs of a type of industrial equipment (or class
thereof) during a representative average cycle of use (as determined by
the Secretary), and shall not be unduly burdensome to conduct.'' (42
U.S.C. 6314(2))
It is DOE's understanding that, although ASHRAE Standard 72-2005 is
a steady-state test, some variation in refrigeration load is
experienced in display cases with doors as part of the door opening
requirement included in that test. When the doors are opened, the
refrigeration load increases because warm ambient air has entered the
case. If the equipment being tested has more efficient operation at
variable refrigeration load, the case will use less energy overall. In
this way, the effects of variable load, or part-load, features are
already captured to some degree in the current test procedure for
commercial refrigeration equipment with doors. Similarly, if the test
procedure is altered to capture decreased energy consumption as a
result of night curtain use, the efficacy of many part-load
technologies in open cases will also be captured.
Further, additional independent or explicit part-load testing will
result in increased cost and burden for manufacturers of covered
products. During the May 2010 Framework public meeting, True expressed
a concern that there is a learning curve associated with how to test
equipment at standard conditions (True, No. 1.2.006 at pp. 133-134) and
that introducing additional test conditions would significantly
increase the cost and burden of testing. (True, No. 1.2.006 at pp. 131-
132) From conversations with manufacturers, DOE estimates that part-
load testing at additional rating conditions could more than double the
cost and burden of testing for all commercial refrigeration equipment.
DOE believes that explicit testing at multiple sets of conditions is
not justified because of this increased burden. Thus, the DOE test
procedure will continue to rely on one standard rating condition,
relying on the transient effects inherent in the proposed test
procedure to capture part-load performance.
5. Rating Temperatures
During the Framework public meeting, True stated that the current
standard only directly addresses a standard ambient test condition of
75 [deg]F and 55 percent relative humidity, but that the Food and Drug
Administration and NSF standards also include an 80 [deg]F ambient
condition. (NSF International was founded in 1944 as the National
Sanitation Foundation; the organization's name is now simply NSF.) True
also stated that higher real-world operating temperatures will impact
the energy use of commercial refrigeration equipment in some
applications. (True, No. 1.2.006 at p. 38) California Codes and
Standards added that it is important to verify that systems operating
under extreme ambient conditions can perform safely at those
temperatures and humidities. (California Codes and Standards, No.
1.2.006 at p. 133) True further asserted that equipment tested at 75
[deg]F and 55 percent relative humidity will perform differently than
if operated at 95 [deg]F and 95 percent relative humidity. (True, No.
1.2.006 at p. 129) ACEEE added that perhaps there should be an adverse
temperature and humidity rating condition to ensure that equipment will
operate effectively in those scenarios. (ACEEE, No. 1.2.006 at p. 131)
Southern Store Fixtures commented that if additional test conditions
are used, equipment that operates outside of these conditions should be
exempt. (Southern Store Fixtures, No. 1.2.006 at p. 133) Zero Zone,
however, stated that testing at a variety of ambient conditions could
become burdensome and the 75/55 condition is a sound compromise. (Zero
Zone, No. 1.2.006 at p. 130)
DOE received similar comments on the 2009 CRE energy conservation
standard NOPR. Those comments encouraged DOE to differentiate between
NSF Type I equipment, which is tested at standard test conditions, and
NSF Type II equipment, which is tested at 80 [deg]F. DOE found that the
relative difference between Type I equipment designed to be operated at
the standard
[[Page 71602]]
test condition of 75 [deg]F and Type II equipment designed to operate
at 80 [deg]F would not significantly impact the energy use of the
equipment as tested at the 75 [deg]F test condition. Thus, DOE
concluded it was unnecessary to institute a distinction between Type I
and Type II commercial refrigeration equipment. 74 FR 1092, 1117 (Jan.
9, 2009).
The current DOE test procedure requires that energy consumption
testing for all commercial refrigeration equipment covered in these
rulemakings be conducted according to ASHRAE Standard 72-2005, which
prescribes specific ambient conditions. DOE believes that equipment
classified as NSF Type II can be tested at the standard rating
conditions prescribed in the DOE test procedure without any significant
additional burden on manufacturers. Accordingly, DOE proposes to
continue to rate all commercial refrigeration equipment at the standard
rating condition prescribed in the referenced industry test procedure.
DOE requests comment on the burden to manufacturers associated with
testing NSF Type II equipment at the standard test condition.
6. Energy Efficiency Features
DOE received a number of comments from stakeholders concerning
energy efficiency features that exist for the explicit purpose of
lowering energy consumption, such as lighting occupancy sensors and
controls, night curtains, higher efficiency expansion valves, condenser
fan motor controllers, and anti-sweat heater controllers. The Northwest
Joint Comment stated that the current test procedure does not have the
capacity to test all of the equipment classes and technology options
that are likely to be within the scope of coverage for this rulemaking.
(Adjuvant Consulting, No. 1.3.003 at pp. 1-2) True commented that the
test procedure should represent a baseline level of energy consumption
with no energy efficiency devices enabled. (True, No. 1.2.006 at pp.
63-64) Southern Store Fixtures commented that some of these devices,
such as night curtains, may not be used by 24-hour stores (Southern
Store Fixtures, No. 1.2.006 at pp. 66-67), and also suggested that DOE
consult with end users of these energy efficiency features before
considering them. (Southern Store Fixtures, No. 1.2.006 at p. 67) True
stated that energy controls have a variety of different features and
energy conservation levels, and that they are sometimes already tested
by manufacturers. (True, No. 1.2.006 at p. 65) The Northwest Joint
Comment added that a percent time off assumption or scaling factor
might not be adequate to capture the effects of all time-dependent
technology options. (Adjuvant Consulting, No. 1.3.003 at p. 3)
As part of this rulemaking effort, DOE has evaluated technology
options suggested by interested parties and has developed provisions to
quantify the performance of those options that can be specifically
addressed while still meeting the statutory requirements of a test
procedure. Specific proposed changes include provisions for measuring
the energy impacts of lighting occupancy sensors and controls, and
night curtains. Other technologies, such as higher efficiency expansion
valves, condenser fan motor controllers, and anti-sweat heater
controllers, are technologies that function to reduce energy
consumption at part-load conditions. As discussed in section III.A.4,
``Testing of Transient Technologies and at Variable Refrigeration
Load,'' the energy saving potential of these technologies is already
captured to some degree in the current test procedure. Further, DOE
believes that explicit testing for these energy efficiency technologies
that reduce energy consumption at part load is not justified because it
would significantly increase the testing burden.
DOE requests comment on the burden to test energy efficiency
technologies other than those explicitly accounted for in this test
procedure revision, namely night curtains and lighting occupancy
sensors and scheduled control.
B. Summary of the Test Procedure Revisions
Today's proposed rule contains the following proposed changes to
the test procedure in 10 CFR part 431, subpart C.
1. Update References to Industry Test Procedures to Most Current
Versions
The current DOE test procedure for commercial refrigeration
equipment adopted ARI Standard 1200-2006, with additional provisions
for testing ice-cream freezers at -15 [deg]F, as the test procedure
used to measure the energy consumption of a piece of commercial
refrigeration equipment to establish compliance with the applicable
energy conservation standard. Since the publication of the 2006 test
procedure final rule, AHRI has released an updated version of the test
procedure, AHRI Standard 1200-2010. The updated test procedure includes
both editorial and technical changes to the equipment class
nomenclature used within the test procedure, the test product
temperature for ice-cream freezers, and the method of normalizing and
reporting units for equipment energy consumption. These changes align
the test procedure with the nomenclature and methodology used in the
2009 DOE energy conservation standard final rule. AHRI Standard 1200-
2010 is the test procedure currently used in industry, and DOE proposes
to adopt it as the DOE test procedure.
The current DOE test procedure also references AHAM HRF-1-2004 as
the protocol for determining refrigerated compartment volume. AHAM has
also updated its Standard HRF-1-2004. The most recent version is AHAM
HRF-1-2008, which makes editorial changes including reorganizing some
of the sections for simplicity and usability. The newly updated AHRI
1200-2010 also references AHAM HRF-1-2008. For consistency, DOE
proposes to adopt the more recent AHAM HRF-1-2008 for measuring
refrigerated compartment volume.
DOE requests comment on updating the referenced industry test
procedures to the most current versions.
2. Include Method for Determining Energy Savings Due to the Use of
Night Curtains on Open Cases
The current test procedure, ARI Standard 1200-2006, and method of
test, ASHRAE Standard 72-2005, do not account for potential energy
savings resulting from the use of night curtains on open cases. Night
curtains are devices made of an insulating material, typically
insulated aluminum fabric, designed to be pulled down over the open
front of the case (similar to the way a window shade operates) when the
merchandizing establishment is closed or the customer traffic is
significantly decreased. The insulating shield, or night curtain,
decreases infiltration and mixing of the cool air inside the case with
the relatively warm, humid air in the store interior. It also reduces
conductive and radiative heat transfer into the case. This can reduce
compressor loads and defrost cycles, significantly decreasing energy
use. A 1997 study by the Southern California Edison Refrigeration
Technology and Test Center found that, when used for 6 hours per day,
night curtains reduce total energy use of the case by approximately 8
percent.\2\
---------------------------------------------------------------------------
\2\ Southern California Edison, Refrigeration and Technology and
Test Center, Energy Efficiency Division. Effects of the Low
Emissivity Shields on Performance and Power Use of a Refrigerated
Display Case. August 1997. Available at https://www.econofrost.com/acrobat/sce_report_long.pdf.
---------------------------------------------------------------------------
To allow manufacturers to account for the possible energy savings
of cases sold
[[Page 71603]]
with night curtains, DOE intends to adopt a standardized physical test
method. A physical test would accurately capture differences in energy
use reduction as a function of similar technologies and case
dimensions. It is important to capture the differences in energy use
reduction from similar technologies because of the large performance
disparities that can exist. For example, night curtains made of low-
emissivity materials, such as aluminum, decrease the radiative losses
from the case and therefore are much more effective at reducing heat
loss than night curtains made of plastic, linoleum, or other non-
reflective materials. In addition, each night curtain may reduce
infiltration differently depending on its insulating characteristics
and design. The case dimensions and default infiltration load also
impact night curtain performance. As such, a physical test will also
accurately capture differences in the energy conservation utility of
night curtains as a function of case dimension.
DOE proposes using the following physical test method, as specified
by ASHRAE Standard 72-2005. This method would be similar to section 7.2
in ASHRAE Standard 72-2005, ``Door-Opening Requirements,'' and would
read as follows:
Night Curtain Requirements. For open display cases sold with
night curtains installed, the night curtain shall be employed
according to manufacturer instructions for a total of 6 hours, 3
hours after the start of a defrost period. Upon the completion of
the 6-hour period, the night curtain shall be raised until the
completion of the 24-hour test period.
DOE proposes a 6-hour test period to approximate the typical usage
of a night curtain. In studies analyzing the effects of night curtain
use, such as the previously cited 1997 study by the Southern California
Edison Refrigeration Technology and Test Center, a similar 6-hour time
period has been used. The test for night curtains would apply only to
cases sold with night curtains installed. The assumptions made in the
testing of night curtains may not reflect their use in the field in all
applications. However, this test would be a standard for all cases sold
with night curtains, regardless of their anticipated use.
DOE requests comment on the proposal for the incorporation of night
curtains into the DOE test procedure.
3. Include Calculation for Determining Energy Savings Due to Use of
Lighting Occupancy Sensors or Controls
The current test procedure, ARI Standard 1200-2006, and method of
test, ASHRAE Standard 72-2005, do not account for potential energy
savings resulting from the use of lighting occupancy sensors and
scheduled controls. The energy savings due to the use of occupancy-
based sensors or schedule-based controls will vary in the field due to
differing environmental and operating conditions. However, studies,
including a demonstration project conducted through the DOE GATEWAY
program, have shown that lighting occupancy sensors or controls could
reduce the total energy use of a typical refrigerated merchandising
unit operating in a grocery store by up to 40 percent.\3\
---------------------------------------------------------------------------
\3\ U.S. Department of Energy. Demonstration Assessment of
Light-Emitting Diode (LED) Freezer Case Lighting. October 2009.
Prepared by Pacific Northwest National Laboratory for the U.S. DOE
Solid State Lighting Technology Demonstration GATEWAY Program.
Available at https://apps1.eere.energy.gov/buildings/publications/pdfs/ssl/gateway_freezer-case.pdf.
---------------------------------------------------------------------------
Lighting occupancy sensors and schedule-based control systems are
designed to reduce the amount of time that lights are on within
commercial refrigeration equipment. Lighting occupancy sensors use
passive infrared, ultrasonic, or other motion-sensing technology to
detect the presence of a customer or employee. These sensors turn off
or dim the lights within the equipment when no motion is detected in
the sensor's coverage area. Schedule-based lighting controls allow
lights to be turned off or dimmed at scheduled times throughout the
day. The energy efficiency benefits from reducing case lighting energy
use are two-fold, because both the direct electricity consumption of
the lights and the heat load on the refrigeration system are decreased.
Light-emitting diode technology, used in much of today's new commercial
refrigeration equipment, lends itself to rapid on/off cycling or
dimming, which enables the use of occupancy sensors or scheduled
controls, or both. Lighting occupancy sensors and scheduled controls
can be addressed similarly based on available energy usage data.
DOE proposes using an analytical method similar to equation 4,
section 5.2.3 of AHRI Standard 1200-2010, to calculate the energy use
of lighting within the refrigerated volume. Equation 1 presents a
method to calculate the direct lighting energy consumption (LECsc) with
lighting occupancy sensors and controls deployed for either remote
condensing or self-contained units.
[GRAPHIC] [TIFF OMITTED] TP24NO10.364
Where:
LECsc = lighting energy consumption of internal case lights with
lighting occupancy sensors and controls deployed (kilowatt-hours);
Pli = rated power of lights when they are fully on (watts);
Pli(off) = power of lights when they are off (watts);
Pli(dim) = power of lights when they are dimmed (watts);
tsc = time period when lighting is fully on with lighting occupancy
sensors and controls enabled (hours);
toff = time period which the lights are off due to the use of
lighting occupancy sensors or scheduled controls (hours); and
tdim = time period which the lights are dimmed due to the use of
lighting occupancy sensors or scheduled controls (hours).
In equation 1, toff and tdim are determined based on the
sum of any contribution from lighting occupancy sensors and scheduled
controls that turn off or dim lighting, respectively. These values are
summed, as shown in equation 2, to determine the total amount of time
lighting is dimmed or off.
[[Page 71604]]
[GRAPHIC] [TIFF OMITTED] TP24NO10.365
Where:
toff = time period which the lights are off due to the use of
lighting occupancy sensors or scheduled controls (hours);
tdim = time period which the lights are dim due to the use of
lighting occupancy sensors or scheduled controls (hours);
toff,controls = time case lighting is off due to the use of lighting
controls (hours);
tdim,controls = time case lighting is dimmed due to the use of
lighting controls (hours);
toff,sensors = time case lighting is off due to the use of lighting
occupancy sensors (hours); and
tdim,sensors = time case lighting is dimmed due to the use of
lighting occupancy sensors (hours).
As the test procedure is for 24-hour time period, the sum of
tsc, Toff, and tdim should equal 24 hours. DOE also proposes
that the total time period during which the lights are off or dimmed
shall not exceed 10.8 hours based on the maximum estimated energy
savings from lighting occupancy sensors and controls. This limit is
established to prevent double counting of energy savings in equipment
where both lighting occupancy sensors and schedule based controls are
installed.
[GRAPHIC] [TIFF OMITTED] TP24NO10.366
Where:
toff = time period which the lights are off due to the use of
lighting occupancy sensors or scheduled controls (hours);
tdim = time period which the lights are dimmed due to the use of
lighting occupancy sensors or scheduled controls (hours);
tsc= time period when lighting is fully on with lighting occupancy
sensors and controls enabled (hours);
tl = time period when lighting would be on without lighting
occupancy sensors or controls (24 hours);
with the sum of all toff and tdim from both lighting occupancy
sensors and controls not to exceed 10.8 hours.
In equation 2, the time the case lighting is dimmed or off due to
scheduled lighting controls (toff,controls or tdim,controls, as
applicable) will be 8 hours for those cases with lighting controls
installed. This will depend on whether the controls dim or turn off
lights. A time off period of 8 hours was chosen for scheduled controls
to approximate the typical usage of lighting control products based on
comments received during previous DOE rulemakings for this equipment.
Specifically, during the previous rulemaking for commercial
refrigeration equipment, California Utilities commented that 8 hours
reflected the California predicted ``low load'' period. (Docket number
EERE-2006-BT-STD-0126, California Joint Comment, No. 41, at p. 12)
The time the case lighting is off or dimmed due to lighting
occupancy sensors (toff,sensors or tdim,sensors, as applicable) will be
2.8 or 10.8 hours for cases with lighting occupancy sensors installed,
depending on whether scheduled controls are also installed. For
equipment with only lighting occupancy sensors installed toff,sensors
or tdim,sensors, as applicable, will be 10.8 hours. For equipment with
both lighting occupancy sensors and lighting controls installed, the
lighting controls will be assumed to override the occupancy sensor
during the time the lighting control is used to reduce case lighting.
Thus, the time the case lighting is off or dimmed due to lighting
occupancy sensors (toff,sensors or tdim,sensors, as applicable) will be
2.8 hours for equipment with lighting occupancy sensors and lighting
controls installed. The time off period for lighting occupancy sensors
was derived based on the previously cited demonstration project
conducted through the DOE GATEWAY program.
Equations 1, 2, and 3 can be used to calculate the energy use of
CRE whether the equipment utilizes lighting occupancy sensors or
control, and whether the light settings are set at fully on, fully off,
or dimmed. For example, consider a situation in which lighting that is
dimmed throughout the day by occupancy sensors and is turned off
completely by scheduled controls during closing hours. In this example,
tdim for the dimmed occupancy sensor would be 2.8 hours, and toff for
the scheduled lighting control, which turns off the lights, would be 8
hours. The sum of toff and tdim would be equal to the maximum 10.8
hours. In this example, both tdim,controls and toff,sensors would equal
zero.
In addition to conserving energy directly through decreased
lighting electrical load, occupancy sensors also decrease the heat load
from lights that are located inside the refrigerated space on the
refrigeration equipment. Therefore, a second calculation is necessary
to account for these energy impacts. This second calculation quantifies
the reduced compressor energy use, which is then used to calculate
total energy use, as described below.
For remote condensing equipment, the calculation of Alternate
Component Indirect Effect in section 5.4 of AHRI Standard 1200-2010 can
be used to measure the energy impacts on the compressor. Thus, for
remote condensing equipment, equation 4, from AHRI Standard 1200
equations 5.4 and 5.4.2, can be applied to calculate the decreased
compressor power due to use of lighting occupancy sensors and controls.
[GRAPHIC] [TIFF OMITTED] TP24NO10.367
Where:
CECA= Alternate Compressor Energy Consumption (kilowatt-hours);
LECsc = lighting energy consumption of internal case lights with
lighting occupancy sensors and controls deployed (kilowatt-hours);
Pli = rated power of lights when they are fully on (watts);
tl = time lighting would be on without lighting occupancy sensors or
controls (24 hours); and
EER = energy efficiency ratio from Table 1 in AHRI Standard 1200-
2010 for remote condensing equipment and the values shown in Table
III.1 of this document for self-contained equipment (British thermal
units/watt).
Table III.1. EER for Self-Contained Commercial Refrigerated Display
Merchandisers and Storage Cabinets
------------------------------------------------------------------------
Operating temperature class EER Btu/W
------------------------------------------------------------------------
Medium.................................................. 11.26
Low..................................................... 7.14
[[Page 71605]]
Ice Cream............................................... 4.80
------------------------------------------------------------------------
Note:
\1\ EER values for operating temperature classes are calculated based on
the average EER value of all equipment in that class which was
analyzed as part of the previous (2009) rulemaking. This does not
include equipment for which standards were set by Congress in EPACT
2005 (VCT, VCS, HCT, HCS, and SOC at M and L temperatures) or classes
for which standards were set using extension multipliers in the 2009
rulemaking (VOP.SC.L, SVO.SC.L, VOP.SC.I, SVO.SC.I, HZO.SC.I,
VOP.SC.I, SVO.SC.I, HZO.SC.I, HCS.SC.I, SOC.SC.I).
\2\ These values only represent compressor EER and do not include
condenser fan energy use.
The CECA includes a multiplication factor of 0.75 to account for
the fact that not all of the heat produced from the lights will impact
the compressor load. The factor of 0.75 was suggested by manufacturers
during discussions with the AHRI Standard 1200 engineering committee.
For remote condensing commercial refrigerators, freezers, and
refrigerator-freezers with lighting occupancy sensors, controls, or
both installed, the revised compressor energy consumption (CECR) shall
be the CECA added to the compressor energy consumption (CEC) measured
in AHRI Standard 1200-2010, as shown in equation 5.
[G