Energy Conservation Program for Consumer Products: Decision and Order Granting a Waiver to Electrolux Home Products, Inc. From the Department of Energy Residential Refrigerator and Refrigerator-Freezer Test Procedure, 22584-22586 [2010-9973]
Download as PDF
mstockstill on DSKH9S0YB1PROD with NOTICES
22584
Federal Register / Vol. 75, No. 82 / Thursday, April 29, 2010 / Notices
• Compatible Indoor Units For Above
Listed Outdoor Units:
Æ FXAQ Series wall mounted indoor
units with nominally rated capacities of
7,000, 9,000, 12,000, 18,000 and 24,000
Btu/hr.
Æ FXLQ Series floor mounted indoor
units with nominally rated capacities of
12,000, 18,000 and 24,000 Btu/hr.
Æ FXNQ Series concealed floor
mounted indoor units with nominally
rated capacities of 12,000, 18,000 and
24,000 Btu/hr.
Æ FXDQ Series low static ducted
indoor units with nominally rated
capacities of 7,000, 9,000, 12,000,
18,000 and 24,000 Btu/hr.
Æ FXSQ Series medium static ducted
indoor units with nominally rated
capacities of 7,000, 9,000, 12,000,
18,000, 24,000, 30,000, 36,000 and
48,000 Btu/hr.
Æ FXMQ–M Series high static ducted
indoor units with nominally rated
capacities of 30,000, 36,000, 48,000,
72,000 and 96,000 Btu/hr.
Æ FXMQ–P Series high static ducted
indoor units with nominally rated
capacities of 7,000, 9,000, 12,000,
18,000, 24,000, 30,000, 36,000 and
48,000 Btu/hr.
Æ FXMQ–MF Series Outdoor Air
Processing indoor units with nominally
rated capacities of 48,000, 72,000 and
96,000 Btu/hr.
Æ FXTQ–P Series Vertical Air
Handler indoor units with nominally
rated capacities of 12,000, 18,000,
24,000, 30,000, 36,000, 42,000, 48,000
and 54,000 Btu/hr.
Æ FXZQ Series recessed cassette
indoor units with nominally rated
capacities of 7,000, 9,000, 12,000,
18,000 and 24,000 Btu/hr.
Æ FXFQ Series recessed cassette
indoor units with nominally rated
capacities of 12,000, 18,000, 24,000,
30,000 and 36,000 Btu/hr.
Æ FXHQ Series ceiling suspended
indoor units with nominally rated
capacities of 12,000, 24,000 and 36,000
Btu/hr.
(3) Alternate test procedure.
(A) Daikin is required to test the
products listed in paragraph (2) above
according to the test procedure for
central air conditioners and heat pumps
prescribed by DOE at 10 CFR part 431
(ISO Standard 13256–1 (1998)
(incorporated by reference in 10 CFR
431.95(b)(3)), except that Daikin shall
test a tested combination selected in
accordance with the provisions of
subparagraph (3)(B). For every other
system combination using the same
outdoor unit as the tested combination,
Daikin shall make representations
concerning the VRV–WIII products
VerDate Mar<15>2010
16:19 Apr 28, 2010
Jkt 220001
covered in this waiver according to the
provisions of subparagraph (C) below.
(B) Tested combination. The term
tested combination means a sample
basic model comprised of units that are
production units, or are representative
of production units, of the basic model
being tested. For the purposes of this
waiver, the tested combination shall
have the following features:
(i) The basic model of a variable
refrigerant flow system used as a tested
combination shall consist of an outdoor
unit that is matched with between two
and five indoor units. For multi-split
systems, each of these indoor units shall
be designed for individual operation.
(ii) The indoor units shall:
(a) Represent the highest sales model
family, or another indoor model family
if the highest sales model family does
not provide sufficient capacity (see b);
(b) Together, have a nominal cooling
capacity that is between 95 percent and
105 percent of the nominal cooling
capacity of the outdoor unit;
(c) Not, individually, have a nominal
cooling capacity greater than 50 percent
of the nominal cooling capacity of the
outdoor unit;
(d) Operate at fan speeds that are
consistent with the manufacturer’s
specifications; and
(e) Be subject to the same minimum
external static pressure requirement.
(C) Representations. In making
representations about the energy
efficiency of its VRV–WIII multi-split
products, for compliance, marketing, or
other purposes, Daikin must fairly
disclose the results of testing under the
DOE test procedure in a manner
consistent with the provisions outlined
below:
(i) For VRV–WIII multi-split
combinations tested in accordance with
this alternate test procedure, Daikin may
make representations based on these test
results.
(ii) For VRV–WIII multi-split
combinations that are not tested, Daikin
may make representations based on the
testing results for the tested
combination and that are consistent
with either of the two following
methods:
(a) Representation of non-tested
combinations according to an
alternative rating method approved by
DOE; or
(b) Representation of non-tested
combinations at the same energy
efficiency level as the tested
combination with the same outdoor
unit.
(4) This waiver shall remain in effect
from the date this order is issued,
consistent with the provisions of 10 CFR
431.401(g).
PO 00000
Frm 00035
Fmt 4703
Sfmt 4703
(5) This waiver is issued on the
condition that the statements,
representations, and documentary
materials provided by the petitioner are
valid. DOE may revoke or modify the
waiver at any time if it determines that
the factual basis underlying the Petition
for Waiver is incorrect, or the results
from the alternate test procedure are
unrepresentative of the basic models’
true energy consumption characteristics.
Issued in Washington, DC on April 22,
2010.
Cathy Zoi,
Assistant Secretary, Energy Efficiency and
Renewable Energy.
[FR Doc. 2010–9972 Filed 4–28–10; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF ENERGY
Office of Energy Efficiency and
Renewable Energy
[Case No. RF–012]
Energy Conservation Program for
Consumer Products: Decision and
Order Granting a Waiver to Electrolux
Home Products, Inc. From the
Department of Energy Residential
Refrigerator and Refrigerator-Freezer
Test Procedure
AGENCY: Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Decision and order.
SUMMARY: The U.S. Department of
Energy (DOE) gives notice of the
decision and order (Case No. RF–012)
that grants to Electrolux Home Products,
Inc. (Electrolux) a waiver from the DOE
electric refrigerator and refrigeratorfreezer test procedure for certain basic
models containing relative humidity
sensors and adaptive control anti-sweat
heaters. Under today’s decision and
order, Electrolux shall be required to
test and rate its refrigerator-freezers with
adaptive control anti-sweat heaters
using an alternate test procedure that
takes this technology into account when
measuring energy consumption.
DATES: This Decision and Order is
effective April 29, 2010.
FOR FURTHER INFORMATION CONTACT: Dr.
Michael G. Raymond, U.S. Department
of Energy, Building Technologies
Program, Mailstop EE–2J, 1000
Independence Avenue, SW.,
Washington, DC 20585–0121.
Telephone: (202) 586–9611, E-mail:
AS_Waiver_Requests@ee.doe.gov. Betsy
Kohl, U.S. Department of Energy, Office
of the General Counsel, Mail Stop GC–
71, 1000 Independence Avenue, SW.,
E:\FR\FM\29APN1.SGM
29APN1
Federal Register / Vol. 75, No. 82 / Thursday, April 29, 2010 / Notices
Washington, DC 20585–0103, (202) 586–
9507, E-mail:
Elizabeth.Kohl@hq.doe.gov.
SUPPLEMENTARY INFORMATION: In
accordance with Title 10 of the Code of
Federal Regulations (10 CFR) 430.27(l),
DOE gives notice of the issuance of its
decision and order as set forth below.
The decision and order grants
Electrolux a waiver from the applicable
residential refrigerator and refrigeratorfreezer test procedures in 10 CFR part
430, subpart B, appendix A1 for certain
basic models of refrigerator-freezers
with relative humidity sensors and
adaptive control anti-sweat heaters,
provided that Electrolux tests and rates
such products using the alternate test
procedure described in this notice.
Today’s decision prohibits Electrolux
from making representations concerning
the energy efficiency of these products
unless the product has been tested
consistent with the provisions and
restrictions in the alternate test
procedure set forth in the decision and
order below, and the representations
fairly disclose the test results.
Distributors, retailers, and private
labelers are held to the same standard
when making representations regarding
the energy efficiency of these products.
42 U.S.C. 6293(c).
Issued in Washington, DC, on April 22,
2010.
Cathy Zoi,
Assistant Secretary, Energy Efficiency and
Renewable Energy.
mstockstill on DSKH9S0YB1PROD with NOTICES
Decision and Order
In the Matter of: Electrolux Home
Products, Inc. (Case No. RF–012).
Background
Title III of the Energy Policy and
Conservation Act (EPCA) sets forth a
variety of provisions concerning energy
efficiency. Part A of Title III provides for
the ‘‘Energy Conservation Program for
Consumer Products Other Than
Automobiles.’’ 42 U.S.C. 6291–6309.
Part A includes definitions, test
procedures, labeling provisions, energy
conservation standards, and the
authority to require information and
reports from manufacturers. Further,
Part A authorizes the Secretary of
Energy to prescribe test procedures that
are reasonably designed to produce
results that measure energy efficiency,
energy use, or estimated operating costs,
and that are not unduly burdensome to
conduct. Id. § 6293(b)(3).
Today’s notice involves residential
products under Part A. The test
procedure for residential electric
refrigerator-freezers relevant to the
current petition for waiver is contained
VerDate Mar<15>2010
16:19 Apr 28, 2010
Jkt 220001
in 10 CFR part 430, subpart B, appendix
A1.
DOE’s regulations contain provisions
allowing a person to seek a waiver from
the test procedure requirements for
covered consumer products when (1)
the petitioner’s basic model contains
one or more design characteristics that
prevent testing according to the
prescribed test procedure, or (2) when
prescribed test procedures may evaluate
the basic model in a manner so
unrepresentative of its true energy
consumption characteristics as to
provide materially inaccurate
comparative data. 10 CFR 430.27(a)(1).
Petitioners must include in their
petition any alternate test procedures
known to the petitioner to evaluate the
basic model in a manner representative
of its energy consumption
characteristics. § 430.27(b)(1)(iii).
The Assistant Secretary for Energy
Efficiency and Renewable Energy (the
Assistant Secretary) may grant a waiver
subject to conditions, including
adherence to alternate test procedures.
§ 430.27(l). Waivers remain in effect
pursuant to the provisions of 10 CFR
430.27(m).
The waiver process also allows any
interested person who has submitted a
petition for waiver to file an application
for interim waiver of the applicable test
procedure requirements. § 430.27(a)(2).
The Assistant Secretary will grant an
interim waiver request if it is
determined that the applicant will
experience economic hardship if the
interim waiver is denied, if it appears
likely that the petition for waiver will be
granted, and/or the Assistant Secretary
determines that it would be desirable for
public policy reasons to grant
immediate relief pending a
determination on the petition for
waiver. § 430.27(g).
On November 6, 2008, Electrolux filed
a petition for waiver from the test
procedures applicable to residential
refrigerators and refrigerator-freezers.
Electrolux’s petition was published in
the Federal Register on June 4, 2009. 74
FR 26853. In that notice, DOE
announced its grant of an interim
waiver to Electrolux, and expanded that
waiver to include four additional
models after receiving supplemental
information from the company. On July
13, 2009, Electrolux filed a petition for
waiver for additional, similar models of
residential refrigerators and refrigeratorfreezers. Electrolux’s petition was
published in the Federal Register on
December 15, 2009. Id. at 66344. In the
same Federal Register notice, DOE
extended the June 4, 2009, interim
waiver to these additional models.
PO 00000
Frm 00036
Fmt 4703
Sfmt 4703
22585
On December 4, 2009, Electrolux filed
a third petition for waiver from the test
procedure applicable to residential
electric refrigerators and refrigeratorfreezers set forth in 10 CFR part 430,
subpart B, appendix A1. All three
Electrolux petitions pertain to new
refrigerators and refrigerator-freezers
that contain variable anti-sweat heater
controls. These controls detect a broad
range of temperature and humidity
conditions and respond by activating
adaptive heaters, as needed, to
evaporate excess moisture. According to
the petitioner, Electrolux’s technology is
similar to that used by General Electric
Company (GE) and Whirlpool
Corporation (Whirlpool) for refrigeratorfreezers which were the subject of
petitions for waiver published April 17,
2007 (72 FR 19189) and July 10, 2008
(73 FR 39684), respectively. GE’s waiver
was granted on February 27, 2008 (73
FR 10425). Whirlpool’s waiver was
granted on May 5, 2009 (74 FR 20695).
DOE granted the first two Electrolux
waivers on December 15, 2009 (74 FR
66338), and March 11, 2010 (75 FR
11530).
Assertions and Determinations
Electrolux’s Petition for Waiver
In its December 2009 petition,
Electrolux sought a waiver from the
existing DOE test procedure applicable
to refrigerators and refrigerator-freezers
under 10 CFR part 430 because it takes
neither ambient humidity nor adaptive
technology into account. Electrolux
sought similar waivers in its July and
November 2009 petitions, which were
granted. Electrolux asserts these new
products are identical in function and
operation to the basic models listed in
Electrolux’s earlier petitions with
respect to the properties that made those
products eligible for a waiver. DOE did
not receive any comments on the
Electrolux petition.
Electrolux requested it be permitted to
use the same alternate test procedure
DOE prescribed for GE, Whirlpool and
Electrolux refrigerators and refrigeratorfreezers equipped with a similar
technology. The alternate test procedure
applicable to the GE, Whirlpool and
Electrolux products simulates the
energy used by the adaptive heaters in
a typical consumer household, as
explained in the GE decision and order
referenced above. As DOE has stated in
the past, it is in the public interest to
have similar products tested and rated
for energy consumption on a
comparable basis.
E:\FR\FM\29APN1.SGM
29APN1
22586
Federal Register / Vol. 75, No. 82 / Thursday, April 29, 2010 / Notices
Consultations With Other Agencies
DOE consulted with the Federal Trade
Commission (FTC) staff concerning the
Electrolux petition for waiver. The FTC
staff did not have any objections to
granting a waiver to Electrolux.
CRS23***
CRS26***
FFHS23****
FFUS23****
FGHS23****
FGUS23****
FPHS23****
FPUS23****
EI23SS****
EW23SS****
FFHC23****
FFCU23****
FGHC23****
FGCU23****
FPHC23****
FPCU23****
FFSC23****
EI23CS****
EW23CS****
E23CS****
FFHS26****
FFUS26****
(3) Electrolux shall be required to test
the products listed in paragraph (2)
above according to the test procedures
for electric refrigerator-freezers
prescribed by DOE at 10 CFR part 430,
appendix A1, except that, for the
Electrolux products listed in paragraph
(2) only:
(A) The following definition is added
at the end of Section 1:
1.13 Variable anti-sweat heater control
means an anti-sweat heater where power
supplied to the device is determined by an
operating condition variable(s) and/or
ambient condition variable(s).
(B) Section 2.2 is revised to read as
follows:
mstockstill on DSKH9S0YB1PROD with NOTICES
2.2 Operational conditions. The electric
refrigerator or electric refrigerator-freezer
shall be installed and its operating conditions
maintained in accordance with HRF–1–1979,
section 7.2 through section 7.4.3.3. except
that the vertical ambient temperature
gradient at locations 10 inches (25.4 cm) out
from the centers of the two sides of the unit
being tested is to be maintained during the
test. Unless shields or baffles obstruct the
area, the gradient is to be maintained from 2
inches (5.1 cm) above the floor or supporting
platform to a height 1 foot (30.5 cm) above
the unit under test. Defrost controls are to be
operative. The anti-sweat heater switch is to
be off during one test and on during the
second test. In the case of an electric
refrigerator-freezer equipped with variable
anti-sweat heater control, the result of the
second test will be derived by performing the
calculation described in 6.2.3. Other
exceptions are noted in 2.3, 2.4, and 5.1
below.
(C) New section 6.2.3 is inserted after
section 6.2.2.2.
6.2.3 Variable anti-sweat heater control
test. The energy consumption of an electric
refrigerator-freezer with a variable anti-sweat
heater control in the on position (Eon),
expressed in kilowatt-hours per day, shall be
calculated equivalent to:
VerDate Mar<15>2010
Conclusion
After careful consideration of all the
material that was submitted by
Electrolux and consultation with the
FTC staff, it is ordered that:
(1) The petition for waiver submitted
by Electrolux Home Products, Inc. (Case
No. RF–012) is hereby granted as set
forth in the paragraphs below.
16:19 Apr 28, 2010
Jkt 220001
FGHS26****
FGUS26****
FPHS26****
FPUS26****
EI26SS****
EW26SS****
FGHF23****
FGUB23****
FPHF23****
FPUB23****
FGHN23****
FGUN23****
FPHN23****
FPUN23****
EI23BC****
EW23BC****
E23BC*****
FFHB26****
FFUB26****
FFHN26****
FFUN26****
EI26BS****
EON = E + (Correction Factor)
where E is determined by sections 6.2.1.1,
6.2.1.2, 6.2.2.1, or 6.2.2.2, whichever is
appropriate, with the anti-sweat heater
switch in the off position.
Correction Factor = (Anti-sweat Heater Power
× System-loss Factor) × (24 hrs/1 day) ×
(1 kW/1000 W)
Where:
Anti-sweat Heater Power = A1 * (Heater
Watts at 5%RH)
+ A2 * (Heater Watts at 15%RH)
+ A3 * (Heater Watts at 25%RH)
+ A4 * (Heater Watts at 35%RH)
+ A5 * (Heater Watts at 45%RH)
+ A6 * (Heater Watts at 55%RH)
+ A7 * (Heater Watts at 65%RH)
+ A8 * (Heater Watts at 75%RH)
+ A9 * (Heater Watts at 85%RH)
+ A10 * (Heater Watts at 95%RH)
Where A1–A10 are defined in the following
table:
A1
A2
A3
A4
A5
=
=
=
=
=
0.034
0.211
0.204
0.166
0.126
A6 = 0.119
A7 = 0.069
A8 = 0.047
A9 = 0.008
A10 = 0.015
Heater Watts at a specific relative humidity
= the nominal watts used by all heaters at
that specific relative humidity, 72 °F
ambient, and DOE reference temperatures of
fresh food (FF) average temperature of 45 °F
and freezer (FZ) average temperature of 5 °F.
System-loss Factor = 1.3
(4) Representations. Electrolux may
make representations about the energy
use of its adaptive control anti-sweat
heater refrigerator-freezer products for
compliance, marketing, or other
purposes only to the extent that such
products have been tested in accordance
with the provisions outlined above and
such representations fairly disclose the
results of such testing.
(5) This waiver shall remain in effect
consistent with the provisions of 10 CFR
430.27(m).
PO 00000
Frm 00037
Fmt 4703
(2) Electrolux shall not be required to
test or rate the following Electrolux
models on the basis of the current test
procedures contained in 10 CFR part
430, subpart B, appendix A1. Instead, it
shall be required to test and rate such
products according to the alternate test
procedure as set forth in paragraph (3)
below:
Sfmt 4703
FGHB28****
FGUB28****
FPHB28****
FPUB28****
FGHN28****
FGUN28****
FPHN28****
FPUN28****
EI28BS****
EW28BS****
(6) This waiver is issued on the
condition that the statements,
representations, and documentary
materials provided by the petitioner are
valid. DOE may revoke or modify this
waiver at any time if it determines the
factual basis underlying the petition for
waiver is incorrect, or the results from
the alternate test procedure are
unrepresentative of the basic models’
true energy consumption characteristics.
Issued in Washington, DC on April 22,
2010.
Cathy Zoi,
Assistant Secretary,
Energy Efficiency and Renewable Energy.
[FR Doc. 2010–9973 Filed 4–28–10; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF ENERGY
Office of Energy Efficiency and
Renewable Energy
[Case No. RF–015]
Energy Conservation Program for
Consumer Products: Notice of Petition
for Waiver of General Electric
Company (GE) From the Department of
Energy Residential Refrigerator and
Refrigerator-Freezer Test Procedure
AGENCY: Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Notice of petition for waiver and
request for comments.
SUMMARY: This notice announces receipt
of and publishes the GE petition for
waiver (hereafter, ‘‘petition’’) from parts
of the U.S. Department of Energy (DOE)
test procedure for determining the
energy consumption of electric
refrigerators and refrigerator-freezers.
Through this document, DOE is
E:\FR\FM\29APN1.SGM
29APN1
Agencies
[Federal Register Volume 75, Number 82 (Thursday, April 29, 2010)]
[Notices]
[Pages 22584-22586]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2010-9973]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
Office of Energy Efficiency and Renewable Energy
[Case No. RF-012]
Energy Conservation Program for Consumer Products: Decision and
Order Granting a Waiver to Electrolux Home Products, Inc. From the
Department of Energy Residential Refrigerator and Refrigerator-Freezer
Test Procedure
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Decision and order.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (DOE) gives notice of the
decision and order (Case No. RF-012) that grants to Electrolux Home
Products, Inc. (Electrolux) a waiver from the DOE electric refrigerator
and refrigerator-freezer test procedure for certain basic models
containing relative humidity sensors and adaptive control anti-sweat
heaters. Under today's decision and order, Electrolux shall be required
to test and rate its refrigerator-freezers with adaptive control anti-
sweat heaters using an alternate test procedure that takes this
technology into account when measuring energy consumption.
DATES: This Decision and Order is effective April 29, 2010.
FOR FURTHER INFORMATION CONTACT: Dr. Michael G. Raymond, U.S.
Department of Energy, Building Technologies Program, Mailstop EE-2J,
1000 Independence Avenue, SW., Washington, DC 20585-0121. Telephone:
(202) 586-9611, E-mail: AS_Waiver_Requests@ee.doe.gov. Betsy Kohl,
U.S. Department of Energy, Office of the General Counsel, Mail Stop GC-
71, 1000 Independence Avenue, SW.,
[[Page 22585]]
Washington, DC 20585-0103, (202) 586-9507, E-mail:
Elizabeth.Kohl@hq.doe.gov.
SUPPLEMENTARY INFORMATION: In accordance with Title 10 of the Code of
Federal Regulations (10 CFR) 430.27(l), DOE gives notice of the
issuance of its decision and order as set forth below. The decision and
order grants Electrolux a waiver from the applicable residential
refrigerator and refrigerator-freezer test procedures in 10 CFR part
430, subpart B, appendix A1 for certain basic models of refrigerator-
freezers with relative humidity sensors and adaptive control anti-sweat
heaters, provided that Electrolux tests and rates such products using
the alternate test procedure described in this notice. Today's decision
prohibits Electrolux from making representations concerning the energy
efficiency of these products unless the product has been tested
consistent with the provisions and restrictions in the alternate test
procedure set forth in the decision and order below, and the
representations fairly disclose the test results. Distributors,
retailers, and private labelers are held to the same standard when
making representations regarding the energy efficiency of these
products. 42 U.S.C. 6293(c).
Issued in Washington, DC, on April 22, 2010.
Cathy Zoi,
Assistant Secretary, Energy Efficiency and Renewable Energy.
Decision and Order
In the Matter of: Electrolux Home Products, Inc. (Case No. RF-012).
Background
Title III of the Energy Policy and Conservation Act (EPCA) sets
forth a variety of provisions concerning energy efficiency. Part A of
Title III provides for the ``Energy Conservation Program for Consumer
Products Other Than Automobiles.'' 42 U.S.C. 6291-6309. Part A includes
definitions, test procedures, labeling provisions, energy conservation
standards, and the authority to require information and reports from
manufacturers. Further, Part A authorizes the Secretary of Energy to
prescribe test procedures that are reasonably designed to produce
results that measure energy efficiency, energy use, or estimated
operating costs, and that are not unduly burdensome to conduct. Id.
Sec. 6293(b)(3).
Today's notice involves residential products under Part A. The test
procedure for residential electric refrigerator-freezers relevant to
the current petition for waiver is contained in 10 CFR part 430,
subpart B, appendix A1.
DOE's regulations contain provisions allowing a person to seek a
waiver from the test procedure requirements for covered consumer
products when (1) the petitioner's basic model contains one or more
design characteristics that prevent testing according to the prescribed
test procedure, or (2) when prescribed test procedures may evaluate the
basic model in a manner so unrepresentative of its true energy
consumption characteristics as to provide materially inaccurate
comparative data. 10 CFR 430.27(a)(1). Petitioners must include in
their petition any alternate test procedures known to the petitioner to
evaluate the basic model in a manner representative of its energy
consumption characteristics. Sec. 430.27(b)(1)(iii).
The Assistant Secretary for Energy Efficiency and Renewable Energy
(the Assistant Secretary) may grant a waiver subject to conditions,
including adherence to alternate test procedures. Sec. 430.27(l).
Waivers remain in effect pursuant to the provisions of 10 CFR
430.27(m).
The waiver process also allows any interested person who has
submitted a petition for waiver to file an application for interim
waiver of the applicable test procedure requirements. Sec.
430.27(a)(2). The Assistant Secretary will grant an interim waiver
request if it is determined that the applicant will experience economic
hardship if the interim waiver is denied, if it appears likely that the
petition for waiver will be granted, and/or the Assistant Secretary
determines that it would be desirable for public policy reasons to
grant immediate relief pending a determination on the petition for
waiver. Sec. 430.27(g).
On November 6, 2008, Electrolux filed a petition for waiver from
the test procedures applicable to residential refrigerators and
refrigerator-freezers. Electrolux's petition was published in the
Federal Register on June 4, 2009. 74 FR 26853. In that notice, DOE
announced its grant of an interim waiver to Electrolux, and expanded
that waiver to include four additional models after receiving
supplemental information from the company. On July 13, 2009, Electrolux
filed a petition for waiver for additional, similar models of
residential refrigerators and refrigerator-freezers. Electrolux's
petition was published in the Federal Register on December 15, 2009.
Id. at 66344. In the same Federal Register notice, DOE extended the
June 4, 2009, interim waiver to these additional models.
On December 4, 2009, Electrolux filed a third petition for waiver
from the test procedure applicable to residential electric
refrigerators and refrigerator-freezers set forth in 10 CFR part 430,
subpart B, appendix A1. All three Electrolux petitions pertain to new
refrigerators and refrigerator-freezers that contain variable anti-
sweat heater controls. These controls detect a broad range of
temperature and humidity conditions and respond by activating adaptive
heaters, as needed, to evaporate excess moisture. According to the
petitioner, Electrolux's technology is similar to that used by General
Electric Company (GE) and Whirlpool Corporation (Whirlpool) for
refrigerator-freezers which were the subject of petitions for waiver
published April 17, 2007 (72 FR 19189) and July 10, 2008 (73 FR 39684),
respectively. GE's waiver was granted on February 27, 2008 (73 FR
10425). Whirlpool's waiver was granted on May 5, 2009 (74 FR 20695).
DOE granted the first two Electrolux waivers on December 15, 2009 (74
FR 66338), and March 11, 2010 (75 FR 11530).
Assertions and Determinations
Electrolux's Petition for Waiver
In its December 2009 petition, Electrolux sought a waiver from the
existing DOE test procedure applicable to refrigerators and
refrigerator-freezers under 10 CFR part 430 because it takes neither
ambient humidity nor adaptive technology into account. Electrolux
sought similar waivers in its July and November 2009 petitions, which
were granted. Electrolux asserts these new products are identical in
function and operation to the basic models listed in Electrolux's
earlier petitions with respect to the properties that made those
products eligible for a waiver. DOE did not receive any comments on the
Electrolux petition.
Electrolux requested it be permitted to use the same alternate test
procedure DOE prescribed for GE, Whirlpool and Electrolux refrigerators
and refrigerator-freezers equipped with a similar technology. The
alternate test procedure applicable to the GE, Whirlpool and Electrolux
products simulates the energy used by the adaptive heaters in a typical
consumer household, as explained in the GE decision and order
referenced above. As DOE has stated in the past, it is in the public
interest to have similar products tested and rated for energy
consumption on a comparable basis.
[[Page 22586]]
Consultations With Other Agencies
DOE consulted with the Federal Trade Commission (FTC) staff
concerning the Electrolux petition for waiver. The FTC staff did not
have any objections to granting a waiver to Electrolux.
Conclusion
After careful consideration of all the material that was submitted
by Electrolux and consultation with the FTC staff, it is ordered that:
(1) The petition for waiver submitted by Electrolux Home Products,
Inc. (Case No. RF-012) is hereby granted as set forth in the paragraphs
below.
(2) Electrolux shall not be required to test or rate the following
Electrolux models on the basis of the current test procedures contained
in 10 CFR part 430, subpart B, appendix A1. Instead, it shall be
required to test and rate such products according to the alternate test
procedure as set forth in paragraph (3) below:
CRS23*** FFCU23**** FGHS26**** FGUN23**** FGHB28****
CRS26*** FGHC23**** FGUS26**** FPHN23**** FGUB28****
FFHS23**** FGCU23**** FPHS26**** FPUN23**** FPHB28****
FFUS23**** FPHC23**** FPUS26**** EI23BC**** FPUB28****
FGHS23**** FPCU23**** EI26SS**** EW23BC**** FGHN28****
FGUS23**** FFSC23**** EW26SS**** E23BC***** FGUN28****
FPHS23**** EI23CS**** FGHF23**** FFHB26**** FPHN28****
FPUS23**** EW23CS**** FGUB23**** FFUB26**** FPUN28****
EI23SS**** E23CS**** FPHF23**** FFHN26**** EI28BS****
EW23SS**** FFHS26**** FPUB23**** FFUN26**** EW28BS****
FFHC23**** FFUS26**** FGHN23**** EI26BS**** ....................
(3) Electrolux shall be required to test the products listed in
paragraph (2) above according to the test procedures for electric
refrigerator-freezers prescribed by DOE at 10 CFR part 430, appendix
A1, except that, for the Electrolux products listed in paragraph (2)
only:
(A) The following definition is added at the end of Section 1:
1.13 Variable anti-sweat heater control means an anti-sweat
heater where power supplied to the device is determined by an
operating condition variable(s) and/or ambient condition
variable(s).
(B) Section 2.2 is revised to read as follows:
2.2 Operational conditions. The electric refrigerator or
electric refrigerator-freezer shall be installed and its operating
conditions maintained in accordance with HRF-1-1979, section 7.2
through section 7.4.3.3. except that the vertical ambient
temperature gradient at locations 10 inches (25.4 cm) out from the
centers of the two sides of the unit being tested is to be
maintained during the test. Unless shields or baffles obstruct the
area, the gradient is to be maintained from 2 inches (5.1 cm) above
the floor or supporting platform to a height 1 foot (30.5 cm) above
the unit under test. Defrost controls are to be operative. The anti-
sweat heater switch is to be off during one test and on during the
second test. In the case of an electric refrigerator-freezer
equipped with variable anti-sweat heater control, the result of the
second test will be derived by performing the calculation described
in 6.2.3. Other exceptions are noted in 2.3, 2.4, and 5.1 below.
(C) New section 6.2.3 is inserted after section 6.2.2.2.
6.2.3 Variable anti-sweat heater control test. The energy
consumption of an electric refrigerator-freezer with a variable
anti-sweat heater control in the on position (Eon),
expressed in kilowatt-hours per day, shall be calculated equivalent
to:
EON = E + (Correction Factor)
where E is determined by sections 6.2.1.1, 6.2.1.2, 6.2.2.1, or
6.2.2.2, whichever is appropriate, with the anti-sweat heater switch
in the off position.
Correction Factor = (Anti-sweat Heater Power x System-loss Factor) x
(24 hrs/1 day) x (1 kW/1000 W)
Where:
Anti-sweat Heater Power = A1 * (Heater Watts at 5%RH)
+ A2 * (Heater Watts at 15%RH)
+ A3 * (Heater Watts at 25%RH)
+ A4 * (Heater Watts at 35%RH)
+ A5 * (Heater Watts at 45%RH)
+ A6 * (Heater Watts at 55%RH)
+ A7 * (Heater Watts at 65%RH)
+ A8 * (Heater Watts at 75%RH)
+ A9 * (Heater Watts at 85%RH)
+ A10 * (Heater Watts at 95%RH)
Where A1-A10 are defined in the following table:
------------------------------------------------------------------------
------------------------------------------------------------------------
A1 = 0.034 A6 = 0.119
A2 = 0.211 A7 = 0.069
A3 = 0.204 A8 = 0.047
A4 = 0.166 A9 = 0.008
A5 = 0.126 A10 = 0.015
------------------------------------------------------------------------
Heater Watts at a specific relative humidity = the nominal watts
used by all heaters at that specific relative humidity, 72 [deg]F
ambient, and DOE reference temperatures of fresh food (FF) average
temperature of 45 [deg]F and freezer (FZ) average temperature of 5
[deg]F. System-loss Factor = 1.3
(4) Representations. Electrolux may make representations about the
energy use of its adaptive control anti-sweat heater refrigerator-
freezer products for compliance, marketing, or other purposes only to
the extent that such products have been tested in accordance with the
provisions outlined above and such representations fairly disclose the
results of such testing.
(5) This waiver shall remain in effect consistent with the
provisions of 10 CFR 430.27(m).
(6) This waiver is issued on the condition that the statements,
representations, and documentary materials provided by the petitioner
are valid. DOE may revoke or modify this waiver at any time if it
determines the factual basis underlying the petition for waiver is
incorrect, or the results from the alternate test procedure are
unrepresentative of the basic models' true energy consumption
characteristics.
Issued in Washington, DC on April 22, 2010.
Cathy Zoi,
Assistant Secretary,
Energy Efficiency and Renewable Energy.
[FR Doc. 2010-9973 Filed 4-28-10; 8:45 am]
BILLING CODE 6450-01-P