Transmission Relay Loadability Reliability Standard, 16914-16956 [2010-6568]
Download as PDF
16914
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
DEPARTMENT OF ENERGY
Federal Energy Regulatory
Commission
18 CFR Part 40
[Docket No. RM08–13–000; Order No. 733]
Transmission Relay Loadability
Reliability Standard
March 18, 2010.
AGENCY: Federal Energy Regulatory
Commission.
ACTION: Final rule.
SUMMARY: Pursuant to section 215 of the
Federal Power Act, the Federal Energy
Regulatory Commission approves the
Transmission Relay Loadability
Reliability Standard (PRC–023–1),
developed by the North American
Electric Reliability Corporation (NERC).
Reliability Standard PRC–023–1
requires transmission owners, generator
owners, and distribution providers to
set load-responsive phase protection
relays according to specific criteria in
order to ensure that the relays reliably
detect and protect the electric network
from all fault conditions, but do not
limit transmission loadability or
interfere with system operators’ ability
to protect system reliability. In addition,
pursuant to section 215(d)(5) of the
Federal Power Act, the Commission
directs NERC to develop modifications
to the Reliability Standard to address
specific concerns identified by the
Commission.
DATES: Effective Date: This rule will
become effective May 17, 2010.
FOR FURTHER INFORMATION CONTACT:
Cynthia Pointer (Technical
Information), Office of Electric
Reliability, Division of Reliability
Standards, Federal Energy Regulatory
Commission, 888 First Street, NE.,
Washington, DC 20426. (202) 502–
6069.
Joshua Konecni (Legal Information),
Office of the General Counsel, Federal
Energy Regulatory Commission, 888
First Street, NE., Washington, DC
20426. (202) 502–6291.
SUPPLEMENTARY INFORMATION:
TABLE OF CONTENTS
Paragraph
Nos.
mstockstill on DSKH9S0YB1PROD with RULES2
I. Background ............................................................................................................................................................................................
II. Reliability Standard PRC–023–1 .........................................................................................................................................................
A. Applicability .................................................................................................................................................................................
B. Requirements ................................................................................................................................................................................
1. Requirement R1 ......................................................................................................................................................................
2. Requirement R2 ......................................................................................................................................................................
3. Requirement R3 ......................................................................................................................................................................
III. Discussion ...........................................................................................................................................................................................
A. Overview .......................................................................................................................................................................................
B. Approval of PRC–023–1 ...............................................................................................................................................................
C. Applicability .................................................................................................................................................................................
D. Generator Step-Up and Auxiliary Transformers .........................................................................................................................
1. Omission From the Reliability Standard ..............................................................................................................................
2. Generator Step-Up Transformer Relays as Back-up Protection ..........................................................................................
E. Need to Address Additional Issues .............................................................................................................................................
1. Zone 3/Zone 2 Relays Applied as Remote Circuit Breaker Failure and Backup Protection ............................................
2. Protective Relays Operating Unnecessarily due to Stable Power Swings ..........................................................................
F. Requirement R1 .............................................................................................................................................................................
1. Sub-Requirement R1.1 ...........................................................................................................................................................
2. Sub-Requirement R1.2 ...........................................................................................................................................................
3. Sub-Requirement R1.10 .........................................................................................................................................................
4. Sub-Requirement R1.12 .........................................................................................................................................................
G. Requirement R2 ............................................................................................................................................................................
H. Requirement R3 and Its Sub-Requirements ................................................................................................................................
1. Role of the Planning Coordinator .........................................................................................................................................
2. Sub-Requirement R3.3 ...........................................................................................................................................................
I. Attachment A .................................................................................................................................................................................
1. Section 2: Evaluation of Out-of-Step Blocking Schemes .....................................................................................................
2. Section 3: Protection Systems Excluded from the Reliability Standard ............................................................................
J. Effective Date .................................................................................................................................................................................
K. Violation Risk Factors ..................................................................................................................................................................
L. Violation Severity Levels .............................................................................................................................................................
M. Miscellaneous ..............................................................................................................................................................................
1. Purpose of the Reliability Standard ......................................................................................................................................
2. Transmission Facility Design Margin ...................................................................................................................................
IV. Information Collection Statement ......................................................................................................................................................
V. Environmental Analysis ......................................................................................................................................................................
VI. Regulatory Flexibility Act ..................................................................................................................................................................
VII. Document Availability ......................................................................................................................................................................
VIII. Effective Date and Congressional Notification ...............................................................................................................................
Before Commissioners: Jon Wellinghoff,
Chairman; Marc Spitzer, Philip D. Moeller,
and John R. Norris.
1. Pursuant to section 215 of the
Federal Power Act (FPA),1 the
Commission approves the Transmission
1 16 U.S.C. 824o. The Commission is not adding
any new or modified text to its regulations.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
2
5
6
8
9
10
11
12
12
13
20
98
98
109
115
116
130
174
175
178
190
213
227
230
231
235
238
239
249
273
285
298
313
313
316
318
329
330
345
348
Relay Loadability Reliability Standard
(PRC–023–1), developed by the North
American Electric Reliability
Corporation (NERC) in its capacity as
the Electric Reliability Organization
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
(ERO).2 Reliability Standard PRC–023–1
requires transmission owners, generator
owners, and distribution providers to
set load-responsive phase protection
relays according to specific criteria in
order to ensure that the relays reliably
detect and protect the electric network
from all fault conditions, but do not
limit transmission loadability or
interfere with system operators’ ability
to protect system reliability.3 In
addition, pursuant to section 215(d)(5)
of the FPA,4 the Commission directs the
ERO to develop modifications to PRC–
023–1 to address specific concerns
identified by the Commission and sets
specific deadlines for these
modifications.
mstockstill on DSKH9S0YB1PROD with RULES2
I. Background
2. Protective relays are devices that
detect and initiate the removal of faults
on an electric system.5 They are
designed to read electrical
measurements, such as current, voltage,
and frequency, and can be set to
recognize certain measurements as
indicating a fault. When a protective
relay detects a fault on an element of the
system under its protection, it sends a
signal to an interrupting device(s) (such
as a circuit breaker) to disconnect the
element from the rest of the system.6
Impedance relays (also known as
distance relays) are the most common
type of load-responsive phase protection
relays used to protect transmission
lines. Impedance relays can also provide
backup protection and protection
against remote circuit breaker failure.
3. Following the August 2003
blackout that affected parts of the
Midwest and Northeast United States,
2 Section 215(e)(3) of the FPA directs the
Commission to certify an ERO to develop
mandatory and enforceable Reliability Standards,
subject to Commission review and approval. 16
U.S.C. 824o(e)(3). Following a selection process, the
Commission selected and certified NERC as the
ERO. North American Electric Reliability Corp., 116
FERC ¶ 61,062 (ERO Certification Order), order on
reh’g & compliance, 117 FERC ¶ 61,126 (ERO
Rehearing Order) (2006), aff’d sub nom. Alcoa, Inc.
v. FERC, 564 F.3d 1342 (DC Cir. 2009).
3 Loadability refers to the ability of protective
relays to refrain from operating under load
conditions.
4 16 U.S.C. 824o(d)(5).
5 Protective relays are one type of equipment used
in protection systems. The NERC definition of
protection systems also includes communication
systems associated with protective relays, voltage
and current sensing devices, station batteries, and
DC control circuitry. See NERC Glossary of Terms
Used in Reliability Standards at 14.
6 Coordination of protection through distance
settings and time delays ensures that the relay
closest to a fault operates before a relay farther away
from the fault, thereby ensuring that the more
distant relay does not disconnect both the
transmission equipment necessary to remove the
fault and ‘‘healthy’’ equipment that should remain
in service.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
and Ontario, Canada, NERC and the
U.S.-Canada Power System Outage Task
Force (Task Force) concluded that a
substantial number of transmission lines
disconnected during the blackout when
load-responsive phase-protection
backup distance and phase relays
operated unnecessarily, i.e. under nonfault conditions. Although these relays
operated according to their settings, the
Task Force determined that the
operation of these relays for non-fault
conditions contributed to cascading
outages at the start of the blackout and
accelerated the geographic spread of the
cascade.7
4. Seeking to prevent or minimize the
scope of future blackouts, both NERC
and the Task Force made
recommendations to ensure that these
types of protective relays do not
contribute to future blackouts.
Recommendation 8A of the NERC
Report addresses the need to evaluate
load-responsive protection zone 3
relays 8 to determine whether they will
operate under extreme emergency
conditions:
All transmission owners shall, no later
than September 30, 2004, evaluate the zone
3 relay settings on all transmission lines
operating at 230 kV and above for the
purpose of verifying that each zone 3 relay
is not set to trip on load under extreme
emergency conditions[ ]. In each case that a
zone 3 relay is set so as to trip on load under
extreme conditions, the transmission
operator shall reset, upgrade, replace, or
otherwise mitigate the overreach of those
relays as soon as possible and on a priority
basis, but no later than December 31, 2005.
Upon completing analysis of its application
of zone 3 relays, each transmission owner
may no later than December 31, 2004 submit
justification to NERC for applying zone 3
relays outside of these recommended
parameters. The Planning Committee shall
review such exceptions to ensure they do not
increase the risk of widening a cascading
failure of the power system.9
Recommendation No. 21A of the Task
Force Final Blackout Report (Final
Blackout Report) urges NERC to expand
7 U.S.-Canada Power System Outage Task Force,
Final Report on the August 14, 2003 Blackout in the
United States and Canada: Causes and
Recommendations, at 80 (2004) (Final Blackout
Report).
8 Multiple impedance relays are installed at each
end of a transmission line, with each used to
protect a certain percentage, or zone, of the local
transmission line and remote lines. Zone 3 relays
and zone 2 relays set to operate like zone 3 relays
(zone 3/zone 2 relays) are typically set to reach 100
percent of the protected transmission line and more
than 100 percent of the longest line (including any
series elements such as transformers) that emanates
from the remote buses.
9 August 14, 2003 Blackout: NERC Actions to
Prevent and Mitigate the Impacts of Future
Cascading Blackouts, at 13 (2004) (NERC Report).
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
16915
the scope of its review to include certain
operationally significant facilities:
NERC [should] broaden the review
[described in Recommendation 8A of the
NERC Report] to include operationally
significant 115 kV and 138 kV lines, e.g.,
lines that are part of monitored flowgates or
interfaces. Transmission owners should also
look for zone 2 relays set to operate like zone
3 [relays].10
In its petition, NERC states that PRC–
023–1 is intended to specifically
address these recommendations.
II. Reliability Standard PRC–023–1
5. Reliability Standard PRC–023–1
requires transmission owners, generator
owners, and distribution providers to
set load-responsive phase protection
relays according to specific criteria in
order to ensure that the relays reliably
detect and protect the electric network
from all fault conditions, but do not
operate during non-fault load
conditions.
A. Applicability
6. As proposed by NERC, the
Reliability Standard applies to relay
settings on: (1) All transmission lines
and transformers with low-voltage
terminals operated or connected at or
above 200 kV; 11 and (2) those
transmission lines and transformers
with low-voltage terminals operated or
connected between 100 kV and 200
kV 12 that are designated by planning
coordinators as critical to the reliability
of the bulk electric system.13
10 Final
Blackout Report at 158.
explains in general that it decided to
make PRC–023–1 voltage-level-specific because the
definition of what is included in the ‘‘bulk electric
system’’ varies throughout the eight Regional
Entities and because the effects of PRC–023–1 are
not constrained to regional boundaries. For
example, if one Region has purely performancebased criteria and an adjoining Region has voltagebased criteria, these criteria may not permit
consideration of the effects of protective relay
operation in one Region upon the behavior of
facilities in the adjoining Region. NERC Petition at
18–19, 39–41.
12 In this Final Rule, we occasionally use the
shorthand ‘‘100 kV–200 kV facilities’’ to refer to
transmission lines and transformers with lowvoltage terminals operated or connected between
100 kV and 200 kV.
13 In this Final Rule, we use the terms ‘‘bulk
electric system’’ and ‘‘Bulk-Power System.’’ ‘‘Bulk
electric system’’ is defined in the NERC Glossary of
Terms Used in Reliability Standards, and generally
includes facilities operated at voltages at and above
100 kV. See NERC Glossary of Terms Used in
Reliability Standards at 2. ‘‘Bulk-Power System’’ is
defined in section 215 of the FPA, and does not
include a voltage threshold. See 16 U.S.C.
824o(a)(1). In Order No. 693, the Commission
explained that while it would rely on the NERC
definition of bulk electric system during the startup phase of the mandatory Reliability Standard
regime, the statutory Bulk-Power System
encompasses more facilities than are included in
11 NERC
E:\FR\FM\02APR2.SGM
Continued
02APR2
16916
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
7. Attachment A to the Reliability
Standard specifies which protection
systems are subject to and excluded
from the Standard’s Requirements.
Section 1 of Attachment A provides that
the Reliability Standard applies to any
protective functions that can operate
with or without time delay, on load
current, including but not limited to: (1)
Phase distance; (2) out-of-step tripping;
(3) switch-on-to-fault; (4) overcurrent
relays; and (5) communication-aided
protection applications.14 Section 2
states that the Reliability Standard
requires evaluation of out-of-step
blocking schemes 15 to ensure that they
do not operate for faults during the
loading conditions defined in the
Standard’s Requirements. Finally,
section 3 expressly excludes from the
Reliability Standard’s Requirements: (1)
Relay elements enabled only when other
relays or associated systems fail (e.g.,
overcurrent elements enabled only
during abnormal system conditions or a
loss of communications); (2) protection
relay systems intended for the detection
of ground fault conditions or for
protection during stable power swings;
(3) generator protection relays
susceptible to load; (4) relay elements
used only for special protection systems
applied and approved in accordance
with Reliability Standards PRC–012
through PRC–017; 16 (5) protection relay
systems designed to respond only in
time periods that allow operators 15
minutes or longer to respond to
overload conditions; (6) thermal
emulation relays used in conjunction
with dynamic facility ratings; (7) relay
elements associated with DC line; and
(8) relay elements associated with DC
converter transformers.
mstockstill on DSKH9S0YB1PROD with RULES2
B. Requirements
8. Reliability Standard PRC–023–1
consists of three Requirements.
Requirement R1 directs entities to set
their relays according to one of the
options set forth in sub-requirements
NERC’s definition of the bulk electric system.
Mandatory Reliability Standards for the Bulk-Power
System, Order No. 693, FERC Stats. & Regs.
¶ 31,242, at P 75–76; order on reh’g, Order No. 693–
A, 120 FERC ¶ 61,053 (2007).
14 Section 1.5 specifies that the communications
aided applications subject to the Reliability
Standard include, but are not limited to: (1)
Permissive overreach transfer trip; (2) permissive
under-reach transfer trip; (3) directional comparison
blocking; and (4) directional comparison
unblocking.
15 ‘‘Out-of-step blocking’’ refers to a protection
system that is capable distinguishing between a
fault and a power swing. If a power swing is
detected, the protection system, ‘‘blocks,’’ or
prevents the tripping of its associated transmission
facilities.
16 The Commission has not yet acted on PRC–
012–0, PRC–013–0, or PRC–014–0 because it is
awaiting further information from the ERO.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
R1.1 through R1.13. Requirement R2
contains directives for entities that set
their relays according to subrequirements R1.6 through R1.9, R1.12,
or R1.13. Requirement R3 directs
planning coordinators to designate
which facilities operated between 100
kV and 200 kV are critical to the
reliability of the bulk electric system
and therefore must have their relays set
according to one of the options in
Requirement R1.
1. Requirement R1
9. Requirement R1 directs entities to
set their relays according to one of
thirteen specific settings (subrequirements R1.1 through R1.13)
intended to maximize loadability while
maintaining Reliable Operation of the
bulk electric system for all fault
conditions. Entities must evaluate relay
loadability at 0.85 per unit voltage and
a power factor angle of 30 degrees and
set their transmission line relays so that
they do not operate:
R1.1. [A]t or below 150 [percent] of the
highest seasonal [f]acility [r]ating of a circuit,
for the available defined loading duration
nearest 4 hours (expressed in amperes)[;]
R1.2. [A]t or below 115 [percent] of the
highest seasonal 15-minute [f]acility
[r]atingof a circuit (expressed in
amperes)[;] 17
R1.3. [A]t or below 115 [percent] of the
maximum theoretical power transfer
capability (using a 90-degree angle between
the sending-end and receiving-end voltages
and either reactance or complex impedance)
of the circuit (expressed in amperes) using
one of the following to perform the power
transfer calculation:
R1.3.1. An infinite source (zero source
impedance) with a 1.00 per unit bus voltage
at each end of the line[;] [or]
R1.3.2. An impedance at each end of the
line, which reflects the actual system source
impedance with a 1.05 per unit voltage
behind each source impedance[;]
R1.4. [O]n series compensated
transmission lines[,] * * * at or below the
maximum power transfer capability of the
line, determined as the greater of:
[a.] 115 [percent] of the highest emergency
rating of the series capacitor[;] [or]
[b.] 115 [percent] of the maximum power
transfer capability of the circuit (expressed in
amperes), calculated in accordance with
R1.3, using the full line inductive reactance[;]
R1.5. [O]n weak source systems[,] * * * at
or below 170 [percent] of the maximum endof-line three-phase fault magnitude
(expressed in amperes)[;]
R1.6. [On] transmission line relays applied
on transmission lines connected to
generation stations remote to load[,] * * * at
or below 230 [percent] of the aggregated
generation nameplate capability[;]
17 NERC
includes a footnote that states ‘‘[w]hen a
15-minute rating has been calculated and published
for use in real-time operations, the 15-minute rating
can be used to establish the loadability requirement
for the protective relays.’’
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
R1.7. [On] transmission line relays applied
at the load center terminal, remote from
generation stations, * * * at or below 115
[percent] of the maximum current flow from
the load to the generation source under any
system configuration[;]
R1.8. [On] transmission line relays applied
on the bulk system-end of transmission lines
that serve load remote to the system[,] * * *
at or below 115 [percent] of the maximum
current flow from the system to the load
under any system configuration[;]
R1.9. [On] transmission line relays applied
on the load-end of transmission lines that
serve load remote to the bulk system[,] * * *
at or below 115 [percent] of the maximum
current flow from the load to the system
under any system configuration[;]
R1.10. [On] transformer fault protection
relays and transmission line relays on
transmission lines terminated only with a
transformer[,] * * * at or below the greater
of:
[a.] 150 [percent] of the applicable
maximum transformer nameplate rating
(expressed in amperes), including the forced
cooled ratings corresponding to all installed
supplemental cooling equipment[;] [or]
[b.] 115 [percent] of the highest operator
established emergency transformer rating[;]
R1.11. For transformer overload protection
relays that do not comply with R1.10[,] [the
entity must either]. * * *
[a.] Set the relays to allow the transformer
to be operated at an overload level of at least
150 [percent] of the maximum applicable
nameplate rating, or 115 [percent] of the
highest operator established emergency
transformer rating, whichever is greater. The
protection must allow this overload for at
least 15 minutes to allow for the operator to
take controlled action to relieve the
overload[;] [or]
[b.] Install supervision for the relays using
either a top oil or simulated winding hot spot
temperature element. The setting should be
no less than 100° C for the top oil or 140°
C for the winding hot spot temperature[;] 18
R1.12. When the desired transmission line
capability is limited by the requirement to
adequately protect the transmission line, set
the transmission line distance relays to a
maximum of 125 [percent] of the apparent
impedance (at the impedance angle of the
transmission line) subject to the following
constraints:
R1.12.1. Set the maximum torque angle
(MTA) to 90 degrees or the highest supported
by the manufacturer[;]
R1.12.2. Evaluate the relay loadability in
amperes at the relay trip point at 0.85 per
unit voltage and a power factor angle of 30
degrees[;] [and]
R1.12.3. Include a relay setting component
of 87 [percent] of the current calculated in
R1.12.2 in the [f]acility [r]ating determination
for the circuit[;]
R1.13. [Finally,] [w]here other situations
present practical limitations on circuit
capability, [entities can] set the phase
18 NERC includes a footnote that states: ‘‘IEEE
[S]tandard C57.115, Table 3, specifies that
transformers are to be designed to withstand a
winding hot spot temperature of 180 degrees C, and
cautions that bubble formation may occur above
140 degrees C.’’
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
protection relays so they do not operate at or
below 115 [percent] of such limitations.
2. Requirement R2
10. Requirement R2 provides that
entities that set their relays according to
sub-requirements R1.6 through R1.9,
R1.12, or R1.13 must use the calculated
circuit capability as the circuit’s facility
rating and must obtain the agreement of
the planning coordinator, transmission
operator, and reliability coordinator
with authority over the facility as to the
calculated circuit capability.
3. Requirement R3
11. Requirement R3 directs planning
coordinators to designate which
facilities operated between 100 kV and
200 kV are critical to the reliability of
the bulk electric system and therefore
must have their relays set according to
one of the options in Requirement R1.
Sub-requirement R3.1 requires planning
coordinators to have a process to
identify critical facilities. Subrequirement R3.1.1 specifies that the
process must consider input from
adjoining planning coordinators and
affected reliability coordinators. Subrequirements R3.2 and R3.3 require
planning coordinators to maintain a list
of critical facilities and provide it to
reliability coordinators, transmission
owners, generator owners, and
distribution providers within 30 days of
initially establishing it, and 30 days of
any subsequent change.
III. Discussion
A. Overview
12. The Commission approves PRC–
023–1, finding that it is just and
reasonable, not unduly discriminatory
or preferential and in the public
interest. The Commission also directs
the ERO to develop modifications to
PRC–023–1 through its Reliability
Standards development process to
address specific concerns identified by
the Commission and sets specific
deadlines for these modifications.
Similar to our approach in Order No.
693,19 we view such directives as
separate from approval, consistent with
our authority under section 215(d)(5) of
the FPA to direct the ERO to develop a
modification to a Reliability Standard.
mstockstill on DSKH9S0YB1PROD with RULES2
B. Approval of PRC–023–1
1. NOPR Proposal
13. On May 21, 2009, the Commission
issued a Notice of Proposed Rulemaking
(NOPR) proposing to approve PRC–023–
1 as mandatory and enforceable.20 As a
19 See
supra n.13.
Relay Loadability Reliability
Standard, Notice of Proposed Rulemaking, 74 FR
20 Transmission
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
separate action, pursuant to section
215(d)(5) of the FPA, the Commission
proposed to direct certain modifications
to the Reliability Standard.
2. Comments
14. While commenters universally
support the Commission’s proposal to
approve PRC–023–1,21 most
commenters oppose the majority of the
Commission’s proposed modifications.
Some commenters argue that the
Commission’s proposed modifications
violate Order No. 693 because they
prescribe specific changes that would
dictate the content of the modified
Reliability Standard.
3. Commission Determination
15. Pursuant to section 215(d)(2) of
the FPA,22 the Commission approves
PRC–023–1 as just, reasonable, not
unduly discriminatory or preferential,
and in the public interest. The
Commission finds that PRC–023–1 is a
significant step toward improving the
reliability of the Bulk-Power System in
North America because it requires loadresponsive phase protection relay
settings to provide essential facility
protection for faults, while allowing the
Bulk-Power System to be operated in
accordance with established facility
ratings.
16. Also, pursuant to section 215(d)(5)
of the FPA, the Commission adopts
some of the proposed modifications in
the NOPR and thus directs certain
modifications to the Reliability
Standard. Unless stated otherwise, the
Commission directs the ERO to submit
these modifications no later than one
year from the date of this Final Rule. We
will address each proposal and the
specific comments received on each
proposal in the remainder of this Final
Rule.
17. With regard to the concerns raised
by some commenters about the
prescriptive nature of the Commission’s
proposed modifications, we agree that,
consistent with Order No. 693, a
direction for modification should not be
so overly prescriptive as to preclude the
consideration of viable alternatives in
the ERO’s Reliability Standards
development process. However, some
guidance is necessary, as the
Commission explained in Order No.
693:
[I]n identifying a specific matter to be
addressed in a modification * * * it is
important that the Commission provide
35830 (Jul. 21, 2009), FERC Stats. & Regs. ¶ 32,642
(2009) (NOPR).
21 See, e.g., NERC Comments, EEI, TAPS, APPA,
NARUC, EPSA, Exelon.
22 16 U.S.C. 824o(d)(2).
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
16917
sufficient guidance so that the ERO has an
understanding of the Commission’s concerns
and an appropriate, but not necessarily
exclusive, outcome to address those
concerns. Without such direction and
guidance, a Commission proposal to modify
a Reliability Standard might be so vague that
the ERO would not know how to adequately
respond.23
18. Thus, in some instances, while we
provide specific details regarding the
Commission’s expectations, we intend
by doing so to provide useful guidance
to assist in the Reliability Standards
development process, not to impede it.
As we explained in Order No. 693, we
find that this is consistent with statutory
language that authorizes the
Commission to order the ERO to submit
a modification ‘‘that addresses a specific
matter’’ if the Commission considers it
appropriate to carry out section 215 of
the FPA.24 In this Final Rule, we have
considered commenters’ concerns and,
where a directive for modification
appears to be determinative of the
outcome, the Commission provides
flexibility by directing the ERO to
address the underlying issue through
the Reliability Standards development
process without mandating a specific
change to PRC–023–1.25 Consequently,
consistent with Order No. 693, we
clarify that where the Final Rule
identifies a concern and offers a specific
approach to address that concern, we
will consider an equivalent alternative
approach provided that the ERO
demonstrates that the alternative will
adequately address the Commission’s
underlying concern or goal as efficiently
and effectively as the Commission’s
proposal.26
19. Consistent with section 215 of the
FPA, our regulations, and Order No.
693, any modification to a Reliability
Standard, including a modification that
addresses a Commission directive, must
be developed and fully vetted through
NERC’s Reliability Standards
development process.27
C. Applicability
20. As proposed by NERC, PRC–023–
1 does not apply to any facility operated
or connected between 100 kV and 200
kV unless the relevant planning
coordinator designates the facility as
‘‘critical’’ to the reliability of the bulk
electric system. In the NOPR, the
23 Order No. 693, FERC Stats. & Regs. ¶ 31,242 at
P 185.
24 Id. P 186.
25 Id.
26 Id.
27 Id. P 187.
E:\FR\FM\02APR2.SGM
02APR2
16918
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
mstockstill on DSKH9S0YB1PROD with RULES2
Commission described this as an ‘‘add
in’’ approach to applicability.28
21. Requirement R3 of PRC–023–1
directs planning coordinators to
determine which 100 kV–200 kV
facilities are critical to the reliability of
the bulk electric system, and therefore
subject to the Reliability Standard; it
does not, however, define ‘‘critical to the
reliability of the bulk electric system’’ or
provide planning coordinators with a
test to identify critical facilities.
1. NOPR Proposal
22. In the NOPR, the Commission
stated that it expects planning
coordinators to use a process to carry
out Requirement R3 that is consistent
across regions and robust enough to
identify all facilities that should be
subject to PRC–023–1. The Commission
expressed concern that, based on the
information in NERC’s petition, the ‘‘add
in’’ approach proposed by NERC would
fail to meet these expectations.
23. The Commission explained that
since approximately 85 percent of
circuit miles of electric transmission are
operated at or below 253 kV, the ‘‘add
in’’ approach could, at the outset,
effectively exempt from the Reliability
Standard’s requirements a large
percentage of facilities that should
otherwise be subject to the Standard.
The Commission also cited a letter from
NERC to industry stakeholders
discussing the results of an ‘‘add in’’
approach in the context of industry’s
self-identification of Critical Cyber
Assets. According to the Commission,
the letter was an acknowledgement from
NERC that the ‘‘add in’’ approach failed
to produce a comprehensive list of
Critical Cyber Assets.29 The
Commission further observed that NERC
failed to provide a technical basis for
the ‘‘add in’’ approach, and did not
support its claim that expanded
application of PRC–023–1 would double
implementation costs and distract
industry resources from more important
areas. The Commission added that PRC–
023–1 was developed to prevent
cascading outages, and that no area has
a greater impact on the reliability of the
bulk electric system than the prevention
of cascading outages.
24. The Commission emphasized that
PRC–023–1 must apply to relay settings
on all critical facilities for it to achieve
its intended reliability objective.30 In
order to meet this goal, the Commission
stated that the process for identifying
critical 100 kV–200 kV facilities must
include the same system simulations
28 NOPR,
FERC Stats. & Regs. ¶ 32,642 at P 40.
29 Id.
30 Id.
P 42.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
and assessments as the Transmission
Planning (TPL) Reliability Standards for
reliable operation for all categories of
contingencies used in transmission
planning for all operating conditions.
The Commission also stated that it
expects a comprehensive review to
identify nearly every 100 kV–200 kV
facility as a critical facility. In light of
this expectation, and coupled with its
concern about the ‘‘add in’’ approach,
the Commission proposed to direct the
ERO to adopt a ‘‘rule out’’ approach to
applicability; that is, to modify PRC–
023–1 so that it applies to relay settings
on all 100 kV–200 kV facilities, with the
possibility of case-by-case exceptions
for facilities that are not critical to the
reliability of the bulk electric system
and demonstrably would not result in
cascading outages, instability,
uncontrolled separation, violation of
facility ratings, or interruption of firm
transmission service.31
25. Finally, the Commission proposed
to direct the ERO to adopt an ‘‘add in’’
approach to sub-100 kV facilities that
Regional Entities have identified as
critical to the reliability of the bulk
electric system.32 The Commission
explained that owners and operators of
such facilities are defined as
transmission owners/operators for the
purposes of NERC’s Compliance
Registry,33 and that sub-100 kV facilities
can be included in regional definitions
of the bulk electric system.34 The
Commission also stated that NERC
failed to provide a sufficient technical
record to justify excluding such
31 Id.
P 43.
P 45.
33 NERC’s Compliance Registry is a listing of
organizations subject to compliance with
mandatory Reliability Standards. See NERC Rules
of Procedure, Section 500. NERC’s Statement of
Compliance Registry Criteria, which sets forth
thresholds for registration, defines ‘‘transmission
owner/operator’’ as:
III.d.1 An entity that owns or operates an
integrated transmission element associated with the
bulk power system 100 kV and above, or lower
voltage as defined by the Regional Entity necessary
to provide for the reliable operation of the
interconnected transmission grid; or
III.d.2 An entity that owns/operates a
transmission element below 100 kV associated with
a facility that is included on a critical facilities list
defined by the Regional Entity.
See NERC Statement of Compliance Registry
Criteria at 9.
34 NERC defines the bulk electric system as
follows:
As defined by the Regional Reliability
Organization, the electrical generation resources,
transmission lines, interconnections with
neighboring systems, and associated equipment,
generally operated at voltages of 100 kV or higher.
Radial transmission facilities serving only load with
one transmission source are generally not included
in this definition.
See NERC Glossary of Terms Used in Reliability
Standards at 2.
32 Id.
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
facilities from the scope of the
Reliability Standard.
2. Comments
26. In response to the NOPR, the
Commission received comments
addressing its remarks about the test
that planning coordinators must use to
implement Requirement R3 and its
proposals to direct the ERO to adopt the
‘‘rule out’’ approach for 100 kV–200 kV
facilities and the ‘‘add in’’ approach for
sub-100 kV facilities.
a. Comments on the Test That Planning
Coordinators Must Use To Implement
Requirement R3
27. Commenters generally agree with
the Commission that the process for
identifying critical facilities pursuant to
Requirement R3 should include the
same simulation and assessments
required by the TPL Reliability
Standards for all operating conditions.
However, commenters disagree with the
Commission’s expectation that planning
coordinators will identify nearly every
100 kV–200 kV facility as a critical
facility. For example, Duke reports that
it has applied the existing TPL
standards to its Midwest and Carolina
systems and has not identified any sub200 kV facility as a critical facility (i.e.,
there have been no showings that the
loss of any such facilities could result in
cascading outages, instability, or
uncontrolled separation). Other
commenters maintain that the
Commission’s expectation is not
supported by any technical evidence
and depends on a circular definition
between ‘‘above 100 kV’’ and ‘‘critical to
the reliability of the bulk electric
system.’’ 35
28. NERC recognizes the need for
consistent criteria across North America
for identifying critical 100 kV–200 kV
facilities and proposes to work through
industry to develop it.36 Although
NERC did not propose a test in PRC–
023–1, in its comments it did provide
the suggestions for identifying
operationally significant 100 kV–200 kV
facilities that the NERC System
Protection and Control Task Force
provided to Regional Entities in 2004
and 2005 during the voluntary Beyond
Zone 3 relay review and mitigation
program.37 During that program, NERC
suggested that Regional Entities
identify:
All circuits that are elements of
flowgates[38] in the Eastern Interconnection,
35 See,
e.g., Basin, Exelon, and WECC.
Comments at 12.
37 For a discussion of the Beyond Zone 3 relay
review and mitigation program, see infra P 34.
38 A ‘‘flowgate’’ is a single or group of
transmission elements intended to model MW flow
36 NERC
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
Commercially Significant Constraints in the
Texas Interconnection, or Rated Paths in the
Western Interconnection. This includes both
the monitored and outage element for OTDF
[Outage Transfer Distribution Factor] sets.[39]
All circuits that are elements of system
operating limits (SOLs) and interconnection
reliability operating limits (IROLs), including
both monitored and outage elements.
All circuits that are directly related to offsite power supply to nuclear plants. Any
circuit whose outage causes unacceptable
voltages on the off-site power bus at a nuclear
plant must be included, regardless of its
proximity to the plant.
All circuits of the first 5 limiting elements
(monitored and outaged elements) for
transfer interfaces[40] determined by regional
and interregional transmission reliability
studies. If fewer than 5 limiting elements are
found before reaching studied transfers, all
should be listed.
Other circuits determined and agreed to by
the reliability authority/coordinator and the
Regional Reliability Organizations.
29. In its comments, APPA proposes
that the Commission direct NERC to
develop a process whereby each region
can develop a specific methodology to
ensure consistent, verifiable
identification of critical facilities.
b. Comments on the ‘‘Rule Out’’
Approach
mstockstill on DSKH9S0YB1PROD with RULES2
30. Commenters unanimously oppose
the ‘‘rule out’’ approach. In general, they
argue that it is unnecessary, extremely
costly, and potentially detrimental to
reliability.
31. NERC, EEI, and WECC argue that
the cascade of 138 kV lines that
occurred during the August 2003
blackout would not have occurred if the
345 kV lines in their vicinity had not
tripped, and that the 345 kV lines would
not have tripped if PRC–023–1 had been
in effect prior to the blackout.41 EEI,
PG&E, and SRP add that whenever a
facility between 100 kV and 200 kV
trips on load, it is almost always
impact relating to transmission limitations and
transmission service outage. See Final Black Report
at 214. Flowgates are operationally significant for
the purpose of ensuring desirable system
performance because an actual outage would
present the modeled physical limitations on the
bulk electric system.
39 In the post-contingency configuration of a
system under study, Outage Transfer Distribution
Factor refers to the measure of the responsiveness
or change (expressed in percent) in electrical
loadings on transmission system facilities due to a
change in electric power transfer from one area to
another with one or more system facilities removed
from service.
40 An ‘‘interface’’ is the specific set of transmission
elements between two areas or between two areas
comprising one or more electrical systems. See
Final Blackout Report at 215. An interface is
operationally significant for the purpose of ensuring
desirable system performance because an outage of
an interface would affect IROLs.
41 See, e.g., NERC Comments at 10, 16.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
because of preceding faults at higher
voltages.
32. Some commenters argue that the
majority of facilities between 100 kV
and 200 kV are not critical to the
reliability of the bulk electric system
and are unlikely to contribute to
cascading outages at higher voltages.
APPA, EEI, and WECC state that most
wide-area bulk power transfers flow on
high voltage facilities, while most sub200 kV facilities support local
distribution service.42 SRP asserts that a
malfunction on a 100 kV–200 kV line
typically causes an outage only for the
load connected to the faulted part of the
line, leaving the rest of the line
unaffected; PG&E makes the related
claim that the tripping of a 100 kV–200
kV facility generally has a low impact
on the reliability of higher voltage
systems, even when the two systems run
in parallel. APPA argues that cascading
outages at higher voltages are unlikely
to be arrested by relay action at lower
voltages. EEI adds that many 100 kV–
200 kV facilities are designed to support
local distribution service and their
related protection systems are set to
ensure separation, including load
shedding, if disturbances or system
events take place. EEI asserts that these
systems ensure ‘‘controlled separation’’
that, by definition, does not involve the
Bulk-Power System.
33. Commenters also argue that the
‘‘rule out’’ approach is a costly and
inefficient use of limited industry
resources that will place an
unreasonable burden on small entities
and require utilities to incur
unnecessary upfront costs, forego other
important initiatives, and direct money
and personnel away from the work
necessary to ensure the day-to-day
reliability of the bulk electric system.
34. NERC states that it modeled PRC–
023–1 on two post-blackout relay review
and mitigation programs (the Zone 3
Review and Beyond Zone 3 Review) that
focused primarily on facilities operated
at or above 200 kV, and that these
programs give it a basis for concluding
that the costs of the ‘‘rule out’’ approach
are extremely high.43 NERC reports that
these programs took over three years to
complete, required close to 150,000
hours of labor, cost almost $18 million,
42 SRP and Y–WEA emphasize that this is
especially true in the western interconnection,
where sub-200 kV facilities are generally used as
localized means for distributing electricity to
moderately sized and geographically distant load
centers. See also ElectriCities and NWCP.
43 The Zone 3 Review examined 10,914 terminals
operating at or above 200 kV. The Beyond Zone 3
Review examined 12,273 terminals operating at or
above 200 kV and operationally significant
terminals operating between 100 kV and 200 kV.
NERC Comments at 9–16.
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
16919
and resulted in mitigation costs
(equipment change-outs or additions) of
approximately $65 million, or $111,500
per terminal. Based on a survey of
industry conducted after the NOPR,
NERC estimates that a review and
mitigation program for all facilities
between 100 kV and 200 kV would far
exceed these costs in time and money.
NERC estimates that such a program
would entail review of approximately
53,000 terminals, require close to
340,000 hours of labor, and cost almost
$41 million.44 Based on the results of
the previous review programs, NERC
estimates that at least 11,400 terminals
could be out-of-compliance and that
mitigation could take between 5 and 10
years and cost approximately $590
million.45 In contrast, NERC estimates
that the ‘‘add in’’ approach would entail
review of only 2,400 terminals and
require mitigation for approximately
500, roughly 240 of which would
require equipment replacement.46
35. Some commenters argue that the
‘‘rule out’’ approach may adversely affect
reliability. Exelon is concerned that the
‘‘rule out’’ approach may unintentionally
result in the over-inclusion of facilities
subject to PRC–023–1. Exelon believes
that such over-inclusion will take a
known and successful backup
protection scheme and make it less
effective. Exelon explains that overinclusion will increase the risk of
certain instances of backup relaying not
tripping when it should, thus allowing
what would otherwise be a minor
disturbance to expand unnecessarily.47
Consumers Energy and Entergy argue
that the ‘‘rule out’’ approach will require
entities to divert scarce resources from
other duties that are essential to
reliability, thereby adversely affecting
reliability. Basin argues that the
complexity of integrating PRC–023–1
with other Reliability Standards for
lower voltage lines will divert personnel
from more important aspects of the
Reliability Standards and adversely
affect reliability.
36. In addition to these arguments,
commenters oppose the ‘‘rule out’’
approach on the grounds that it: (1)
Fails to give due weight to the technical
expertise of the ERO, as required by
section 215(d)(2) of the FPA; (2) violates
Order No. 693 because it prescribes a
specific change that will dictate the
content of the modified Reliability
44 Id. at 13–14. NERC adds that 114 transmission
owners operating 100 kV–200 kV lines responded
to the survey.
45 Id. at 14.
46 Id. at 15.
47 See also Ameren at 8.
E:\FR\FM\02APR2.SGM
02APR2
16920
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
mstockstill on DSKH9S0YB1PROD with RULES2
Standard; 48 (3) is inconsistent with the
Commission’s statements in Order No.
672 about the cost of Reliability
Standards; 49 (4) rests on the
unsupported assumption that planning
coordinators will fail to produce a
comprehensive list of critical facilities;
and (5) mischaracterizes NERC’s letter
expressing concern about the use of an
‘‘add in’’ approach in the Critical Cyber
Assets survey.50
37. In the event that the Commission
adopts the ‘‘rule out’’ approach,
commenters argue that the Commission
should immediately confirm the
following exclusions: (1) Facilities that
are not part of a defined and routinely
monitored flowgate; (2) radial
transmission lines, because they are
specifically excluded from the bulk
electric system and are not critical to the
reliability of the bulk electric system; 51
and (3) Category D Contingencies,
because they involve the loss of
multiple transmission facilities caused
by the outage of transmission facilities
other than those relevant to the
Reliability Standard.
38. Commenters also disagree with
what they describe as the Commission’s
5-part test for case-by-case exceptions
from the ‘‘rule out’’ approach, that is, its
proposal to permit exceptions for
facilities that demonstrably would not
result in: (1) Cascading outages; (2)
instability; (3) uncontrolled separation;
(4) violation of facility ratings; or (5)
interruption of firm transmission
service.
39. At the outset, commenters assert
that they do not understand the
relationship between the 5-part test for
exceptions from the ‘‘rule out’’ approach
and the Commission’s insistence that
the ‘‘add in’’ process must include the
same simulations and assessments as
the TPL Reliability Standards.
Commenters are unsure whether the 5part test is in addition to, or in lieu of,
the TPL assessments.
48 See e.g., TAPS, APPA, EEI, Ameren, Manitoba
Hydro, Georgia Transmission, Tri-State, CRC, EEI,
APPA, Ameren, TANC, Fayetteville Public Works
Commission, and LES.
49 In Order No. 672, the Commission stated that
‘‘[a] proposed Reliability Standard does not
necessarily have to reflect the optimal method, or
‘best practice,’ for achieving its reliability goal
without regard to implementation cost. * * * [but]
should[,] however[,] achieve its reliability goal
effectively and efficiently;’’ Rules Concerning
Certification of the Electric Reliability Organization;
and Procedures for the Establishment, Approval,
and Enforcement of Electric Reliability Standards,
Order No. 672, FERC Stats. & Regs. ¶ 31,204, at P
328, order on reh’g, Order No. 672–A, FERC Stats.
& Regs. ¶ 31,212 (2006).
50 See e.g., Exelon, PG&E, EEI, Basin, and TAPS.
51 See e.g., ElectriCities, NWCP, Palo Alto, PSEG
Companies, Pacific Northwest State Commissions,
Y–WEA, and Filing Cooperatives.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
40. Commenters also challenge the
substance of the 5-part test, generally
arguing that it requires more than a
showing that a facility is unlikely to
contribute to cascading thermal outages
and introduces more rigorous
requirements than those in the TPL
Reliability Standards. Specifically,
APPA, Duke, Exelon, and TAPS argue
that interruption of firm transmission
service and violation of facility ratings
do not belong as elements of the test
because: (1) They do not result in
instability, uncontrolled separation, or
cascading failures, and are absent from
the definition of ‘‘Reliable Operation’’ in
section 215 of the FPA; 52 (2) avoiding
an interruption of firm transmission
service is a business issue; (3) a
requirement specifying that the loss of
a 138 kV line cannot result in
interruption of local load goes beyond
the requirements of existing Reliability
Standards; (4) the loss of a 138 kV line
does not show a loss of bulk electric
system reliability; and (5) ‘‘violation of
facility ratings’’ is unduly vague and
over-broad because it is not restricted to
bulk electric system facilities other than
the facility in question and is not
focused on violation of emergency
ratings caused by an outage of the
facility in question.
41. Commenters also argue that NERC
should develop the test for exclusions
and that there should be some
mechanism for entities to challenge
criticality determinations. For example,
APPA argues that the Regional Entity
should establish a process for entities to
challenge criticality determinations.
c. Comments on Proposal To Include
Sub-100 kV Facilities
42. Commenters also address the
Commission’s proposal to direct the
ERO to adopt an ‘‘add in’’ approach to
sub-100 kV facilities, with most
objecting to what they perceive as the
Commission’s view of the Compliance
Registry.53 NERC argues that the
Commission mischaracterized the
nature and purpose of the Compliance
Registry by suggesting that entities on
the Registry must comply with all
Reliability Standards for all of their
facilities.54 NERC explains that the
Compliance Registry does not specify
52 Section 215 defines ‘‘Reliable Operation’’ as
‘‘operating the elements of the bulk-power system
within equipment and electric system thermal,
voltage, and stability limits so that instability,
uncontrolled separation, or cascading failures of
such system will not occur as a result of a sudden
disturbance, including a cybersecurity incident, or
unanticipated failure of system elements.’’ 16 U.S.C.
824o(a)(4).
53 See e.g., NERC, EEI, TAPS, TANC, Ontario
Generation, SWTDUG, and APPA.
54 See also TANC and Ontario Generation.
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
which entities must comply with any
particular Reliability Standard, but that
each individual Standard specifies the
entities and the facilities that are subject
to it. TAPS and APPA assert that a
facility may be ‘‘critical’’ for the purpose
of inclusion on the Compliance
Registry, but not ‘‘operationally
significant’’ for the purpose of avoiding
cascading thermal outages. For example,
TAPS states that a sub-100 kV line that
connects to a black start unit and is
designated as part of a transmission
operator’s restoration plan would be
deemed critical for Compliance Registry
purposes, but may not be operationally
significant for purposes of thermal
cascading outages.55
43. Several commenters request that
the Commission confirm their
understanding of what is required if the
Commission adopts its proposal. ERCOT
and TAPS request confirmation that the
Reliability Standard will apply only to
those sub-100 kV facilities that are
already in the Compliance Registry, and
that future registration will be subject to
a case-by-case demonstration of
criticality. Likewise, SWTDUG is
concerned that the Commission’s
proposal will require non-registered
public power entities with sub-100 kV
facilities to become Registered Entities.
ERCOT also requests confirmation that
the only required revision to the
Reliability Standard would be the
addition of sub-100 kV facilities to the
applicability section. ISO New England
requests confirmation that the
Commission does not intend to create
an enforceable obligation against
Regional Entities by directing them to
undertake—solely for the purpose of
compliance with PRC–023–1—a process
to determine which sub-100 kV facilities
are critical to the reliability of the bulk
electric system. ISO New England
asserts that NERC has already delegated
to Regional Entities the role of
designating critical sub-100 kV facilities
as part of the Compliance Registry
process.56 ISO New England seeks
clarification that the Commission’s
proposal merely requires the addition of
a cross-reference to previous
designations of criticality made
pursuant to the Compliance Registry
process.
44. ITC, IRC, and IESO/Hydro One
support the Commission’s proposal.
These commenters argue that a
proactive approach should be used to
identify any facilities critical to the
reliability of the bulk electric system.
45. NERC and EEI oppose the
Commission’s proposal; however, both
55 TAPS
56 ISO
E:\FR\FM\02APR2.SGM
at 16; see also APPA at 28.
New England at 3.
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
concede that it may have merit and
should be studied through the
Reliability Standards development
process.57 SWTDUG and TAPS oppose
the Commission’s proposal and argue
that the Final Blackout Report does not
support extending the Reliability
Standard to relay settings on sub-100 kV
facilities. TAPS maintains that the
Commission must give ‘‘due weight’’ to
NERC’s exclusion of sub-100 kV
facilities.
46. EPSA argues that the
Commission’s proposal lacks technical
support and fails to identify a specific
reliability gap. EPSA contends that the
Commission should use ‘‘Reliability
Engineering’’ to determine if its project
has a technical basis. EEI argues that
few sub-100 kV facilities are critical to
the reliability of the bulk electric
system. EEI states that because it usually
requires multiple 69 kV lines to replace
one 138 kV line, it is highly unlikely
that sub-100 kV facilities will cause a
major cascade. EEI asserts that it is
much more likely that sub-100 kV
facilities will trip to end a cascade, as
occurred during the August 2003
blackout.
3. Commission Determination
47. As discussed more fully below, we
decline to direct the ERO to adopt the
‘‘rule out’’ approach for 100 kV–200 kV
facilities. However, we adopt the NOPR
proposal and direct the ERO to modify
PRC–023–1 to apply an ‘‘add in’’
approach to certain sub-100 kV facilities
that Regional Entities have already
identified or will identify in the future
as critical facilities for the purposes the
Compliance Registry.58 Finally, we
direct the ERO to modify Requirement
R3 of the Reliability Standard to include
the test that planning coordinators must
use to identify sub-200 kV facilities that
are critical to the reliability of the bulk
electric system.
mstockstill on DSKH9S0YB1PROD with RULES2
a. ‘‘Rule Out’’ Approach
48. We will not direct the ERO to
adopt the ‘‘rule out’’ approach. After
further consideration, we conclude that
our concerns about the ‘‘add in’’
approach can be addressed by directing
the ERO to modify Requirement R3 of
the Reliability Standard to specify a
comprehensive and rigorous test that all
planning coordinators must use to
identify all critical facilities.
49. In the NOPR, the Commission
explained that PRC–023–1 must apply
to relay settings on all critical facilities
57 NERC
Comments at 18–19; EEI at 17–18.
58 Examples of such facilities include black start
generation and the ‘‘cranking path’’ from the
generators to the bulk electric system.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
between 100 kV and 200 kV for it to
achieve its intended reliability
objective. The Commission also stated
that planning coordinators must use a
process to carry out Requirement R3
that is consistent across regions and
robust enough to identify all facilities
that should be subject to the Reliability
Standard. The Commission expressed
concern, however, that NERC’s ‘‘add in’’
approach could effectively exempt from
the Reliability Standard’s Requirements
a large percentage of facilities that
should otherwise be subject to the
Standard. Since NERC did not propose
any test for the Commission to consider,
the Commission proposed the ‘‘rule out’’
approach to ensure that planning
coordinators identify all critical
facilities between 100 kV and 200 kV.
50. After reflecting on the rationale
behind the ‘‘rule out’’ approach—
namely, the goal of ensuring that
planning coordinators identify all
critical facilities between 100 kV and
200 kV—and considering the comments,
we conclude that, from a reliability
standpoint, it should not matter whether
PRC–023–1 employs an ‘‘add in’’
approach or a ‘‘rule out’’ approach
because both approaches should
ultimately result in the same list of
critical facilities. In other words, given
a uniform and robust test, the facilities
that would be ‘‘added in’’ under an ‘‘add
in’’ approach should be the same as the
facilities that would remain subject to
the Reliability Standard after noncritical facilities are ruled out under the
‘‘rule out’’ approach. Instead of
concerning ourselves with the merits of
an ‘‘add in’’ or ‘‘rule out’’ approach, the
Commission will focus on the test
methodology that a planning
coordinator uses to either ‘‘add in’’ or
‘‘rule out’’ a facility. If that test is
lacking, PRC–023–1’s reliability
objective will not be achieved regardless
of whether an ‘‘add in’’ approach or a
‘‘rule out’’ approach is adopted.
Consequently, we decline to adopt the
NOPR proposal and will not require the
ERO to adopt the ‘‘rule out’’ approach.
Instead, as discussed below, we direct
the ERO to modify Requirement R3 of
the Reliability Standard to specify the
test that planning coordinators must use
to identify all critical facilities.
51. In light of our decision, we do not
need to address commenters’ objections
to the ‘‘rule out’’ approach or
speculation about the number of 100
kV–200 kV facilities that are critical to
the reliability of the Bulk-Power System.
Nevertheless, we do not accept the
claim that if PRC–023–1 had been in
effect at the time of the August 2003
blackout, it would have prevented the
345 kV lines from tripping and therefore
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
16921
prevented the 100 kV–200 kV lines from
tripping. We also disagree with
commenters’ claim that the majority of
facilities between 100 kV and 200 kV
are unlikely to contribute to cascading
outages at higher voltages.
52. We disagree with commenters’
assertion that if PRC–023–1 had been in
effect at the time of the August 2003
blackout, it would have prevented the
345 kV lines from tripping and therefore
prevented the 100 kV–200 kV lines from
tripping. On the day of the blackout, the
Harding-Chamberlin, Hanna-Juniper,
and Star-South Canton 345 kV lines all
tripped in a span of less than 45
minutes. Each of these lines tripped and
locked out because of contact with an
overgrown tree.59 As each line failed, its
outage increased the load on the
remaining 138 kV and 345 kV lines,
including the 345 kV Sammis-Star
line,60 and shifted power flows to other
transmission paths. Starting at 15:39
EDT, the first of an eventual sixteen 138
kV lines began to fail. The tripping of
these 138 kV lines occurred because the
loss of the combination of the HardinChamberlin, Hanna-Juniper, and StarSouth Canton 345 kV lines overloaded
the 138 kV system with electricity
flowing toward the Akron and
Cleveland loads.61 In other words, the
cascade of 138 kV lines was precipitated
by faults caused by tree contact, not
protective relays, and would not have
been prevented if PRC–023–1 had been
in effect before the blackout.
53. As the 138 kV lines opened, they
blacked out customers in Akron and in
the area west and south of Akron,
ultimately dropping about 600 MW of
load.62 Even this load shedding was not
enough to offset the cumulative effect of
the 138 kV line outages on the increased
loadings of the 345 kV Sammis-Star
line. The Sammis-Star line tripped at
16:05:57 EDT and triggered a cascade of
interruptions on the high voltage
system, causing electrical fluctuations
and facility trips such that within seven
minutes the blackout rippled from the
Cleveland-Akron area across much of
the northeast United States.63
54. Unlike the Hardin-Chamberlin,
Hanna-Juniper, and Star-South Canton
lines, which tripped because of tree
contact, the Sammis-Star line tripped
due to protective zone 3 relay action
that measured low apparent impedance
(depressed voltage divided by
59 Final
Blackout Report at 57–61; 63–64.
at 70.
61 Id. at 69–70.
62 Id. at 68.
63 Id. at 74.
60 Id.
E:\FR\FM\02APR2.SGM
02APR2
16922
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
abnormally high line current).64 There
was no fault and no major power swing
at the time of the trip; rather, high flows
above the line’s emergency rating
together with depressed voltage caused
the overload to appear to the protective
relays as a remote fault on the system.65
In effect, the relay could no longer
differentiate between a remote threephase fault and an exceptionally high
loading condition. The relay operated as
it was designed to do.66
55. To the extent that commenters’
argument is that PRC–023–1 would have
prevented the loss of the Sammis-Star
line, and therefore the subsequent
spread of the blackout, we do not think
that it is possible to definitively reach
these conclusions on the present record.
56. Requirement R1 of PRC–023–1
directs entities to evaluate relay
loadability at 0.85 per unit voltage and
a power factor angle of 30 degrees.
Figure 6.4 of the Final Blackout Report
indicates that the power factor angle
recorded at the time the Sammis-Star
line tripped was about 27 degrees.
Although the system was in a
marginally stable operating stage, it
would not require major changes to
effect a further change on the loading or
further increasing the power factor angle
on this line to beyond 30 degrees. In
other words, purely from the power
factor angle viewpoint, the Sammis-Star
line trip may still have occurred even if
the relay loadability evaluation
requirement of 30 degrees was met. In
fact, in a white paper explaining the
engineering assumptions and rationales
behind the Requirements in PRC–023–1,
the NERC System Protection and
Control Task Force specifically stated
that:
mstockstill on DSKH9S0YB1PROD with RULES2
[T]he most important point to understand
[about the relay loadability evaluation
requirement in Requirement R1] is that the
loadability recommendations are not absolute
system conditions. They represent a typical
system operation point during an extreme
system condition. The voltage at the relay
may be below the 0.85 per unit voltage and
the power factor angle may be greater than
30 degrees. It is up to the relay settings
engineer to provide the necessary margin as
is done in all relay settings.67
We agree with the NERC System
Protection and Control Task Force, and
caution that setting relays pursuant to
PRC–023–1 simply based on a static and
typical system operation point, without
validating the relay settings based on
64 Id.
65 Id.
at 77–78. See Figure 6.4.
at 77.
66 Id.
67 NERC Planning Committee, System Protection
and Control Task Force, ‘‘Increase Line Loadability
by Enabling Load Encroachment Functions of
Digital Relays,’’ December 7, 2005 at A–1.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
system conditions that the relays could
experience, and without acceptable
margins applied to the minimum
voltages and power factor angles, may
not achieve the reliability goals
intended by PRC–023–1.
57. Consequently, we believe that it is
not possible to conclude whether the
Sammis-Star line would have tripped on
loadability if PRC–023–1 had been in
effect without first setting its zone 3
relay pursuant to PRC–023–1 and then
validating the setting against the
voltages, currents, and power factor
angles that were recorded during the
August 2003 Blackout. In fact, it is our
view that a similar process should be
followed for the 345 kV lines in
Michigan that tripped following the loss
of Sammis-Star line to determine
whether PRC–023–1 would have
prevented the blackout.
58. We also disagree with
commenters’ assertion that that majority
of facilities between 100 kV and 200 kV
are unlikely to contribute to cascading
outages at higher voltages. Prior to the
dynamic cascading stage that began
with the loss of the 345 kV Sammis-Star
line, when the system was still in a
marginally stable operating state (albeit
not within IROLs, as shown in Figure
5.12 in the Final Blackout Report), it
was the loss of several 138 kV facilities
that contributed to the subsequent
increased loading on the 345 kV
Sammis-Star line and resulted in its
tripping.68 A more recent example of a
cascade initiating at the 138 kV voltage
level and spreading to higher voltages is
the Florida Power and Light 2008
blackout event. This event started at the
138 kV level and cascaded into
additional 138 kV, 230 kV, and 500 kV
facilities. Because the operation of the
protective relay is dependent on the
apparent impedance, i.e. voltage and
current quantities as measured by the
relay irrespective of voltage class,
application of PRC–023–1 at only the
higher voltage would not have
prevented these events. We believe that
only a valid assessment with an
acceptable set of test criteria could
determine whether 100 kV–200 kV
facilities are critical facilities, and
therefore whether they need to be set
pursuant to PRC–023–1 to prevent such
undesirable system performance.
59. Finally we agree with APPA that
cascading outages at higher voltages are
unlikely to be arrested by relay action at
lower voltages. Reliability Standard
PRC–023–1 is for preventing inadvertent
tripping of Bulk-Power System facilities
which could then initiate cascading
68 Final
PO 00000
Blackout Report at 64.
Frm 00010
Fmt 4701
Sfmt 4700
outages at any voltage level, and not for
arresting cascading outages.
b. ‘‘Add in’’ Approach to Sub-100 kV
Facilities
60. With respect to sub-100 kV
facilities, we adopt the NOPR proposal
and direct the ERO to modify PRC–023–
1 to apply an ‘‘add in’’
approach to sub-100 kV facilities that
are owned or operated by currentlyRegistered Entities or entities that
become Registered Entities in the future,
and are associated with a facility that is
included on a critical facilities list
defined by the Regional Entity.69 We
also direct that additions to the Regional
Entities’ critical facility list be tested for
their applicability to PRC–023–1 and
made subject to the Reliability Standard
as appropriate.
61. Most of the comments opposing
the Commission’s proposal regarding
sub-100 kV facilities relate to what
commenters perceive to be the
Commission’s view of the relationship
between individual Reliability
Standards and the Compliance Registry.
For example, NERC argues that the
Commission mischaracterized the
nature and purpose of the Compliance
Registry by suggesting that entities on
the Registry must comply with all
Reliability Standards for all of their
facilities without regard to the
applicability provisions of individual
Standards. We did not intend to create
this impression. We agree with NERC
that the Compliance Registry does not
specify which entities must comply
with any particular Reliability Standard.
Rather, the applicability provision of
each individual Standard specifies the
categories of entities, i.e., functions, and
at times the categories of facilities that
are subject to it.
62. We also agree with TAPS and
APPA that it is possible, at least in
theory, that a sub-100 kV facility that
has been identified by a Regional Entity
as critical for the purposes of the
Compliance Registry might not be
‘‘critical’’ with respect to PRC–023–1.
Thus, we clarify that we do not require
the modified Reliability Standard to
apply to all sub-100 kV facilities that
have been identified by Regional
Entities as critical facilities, but only to
those that have been identified by
Regional Entities as critical facilities
and are also identified by planning
coordinators, pursuant to the test
69 As mentioned above, section III.d.2 of the
Statement of Compliance Registry Criteria defines
‘‘transmission owner/operator’’ as: ‘‘[a]n entity that
owns/operates a transmission element below 100
kV associated with a facility that is included on a
critical facilities list defined by the Regional
Entity.’’
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
directed to be developed herein, as
critical to the reliability of the BulkPower System. In other words, the
modification that we direct in this Final
Rule extends the scope of the Reliability
Standard to include any sub-100 kV
facility that is: (1) Owned or operated by
a currently-Registered Entity or an
entity that becomes a Registered Entity
in the future; (2) associated with a
facility that is included on a critical
facilities list defined by the Regional
Entity; (3) employing load-responsive
phase protection relays in its protection
system(s); and (4) identified by the test
directed to be developed herein.70
63. Along these same lines, ERCOT,
SWTDUG, and TAPS are concerned that
the Commission’s proposal will require
non-registered public power entities
with sub-100 kV facilities to become
Registered Entities. As we have said, our
directive applies only to sub-100 kV
facilities that are owned or operated by
currently-Registered Entities or entities
that become Registered Entities in the
future, and are associated with a facility
that is included on a critical facilities
list defined by the Regional Entity; it is
not intended to supplant the process
that Regional Entities use to determine
if a sub-100 kV facility should be
identified as a critical facility or if an
entity should be a Registered Entity.
Similarly, our purpose is not to extend
the definition or the scope of the bulk
electric system sub rosa; it is to ensure
that PRC–023–1 applies to all critical
facilities as identified in the
applicability section so that the
Reliability Standard can achieve its
reliability objective. Consequently, we
do not intend to require any nonRegistered Entity to register on account
of PRC–023–1. Nevertheless, there
might be sub-100 kV facilities that are
owned or operated by non-Registered
Entities that are identified by planning
coordinators, pursuant to the test
directed to be developed herein, as
critical facilities. While we do not
require that these entities become
Registered Entities solely due to PRC–
023–1, if a planning coordinator
applying the test directed to be
developed herein identifies a sub-100
kV facility that belongs to a nonRegistered Entity as a critical facility,
we expect that the planning coordinator
will inform the Regional Entity and that
the Regional Entity will consider this
70 Consistent with Order No. 716, we expect that
sub-100 kV facilities that are needed to supply the
auxiliary power system of a Nuclear Power plant
will be included in both determinations. See
Mandatory Reliability Standard for Nuclear Plant
Interface Coordination, Order No. 716, 125 FERC
¶ 61,065 (2008), at P 51–53, order on reh’g, Order
No. 716–A, 126 FERC ¶ 61,122 (2009).
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
information in light of its existing
registration guidelines and
procedures.71 Similarly, we expect that
Regional Entities will consider this
information when determining whether
a sub-100 kV facility should be included
in a regional definition of the bulk
electric system.72
64. With respect to ISO New
England’s request for confirmation that
the Commission does not intend to
create an enforceable obligation against
Regional Entities by directing them to
undertake—solely for the purpose of
compliance with PRC–023–1—a process
to determine which sub-100 kV facilities
are critical to the reliability of the BulkPower System, it should be clear from
what we have already said that we do
not intend to create such an obligation.
As we have explained, our directive
requires planning coordinators, not
Regional Entities, to determine which
sub-100 kV facilities should be subject
to the Reliability Standard. Moreover,
we agree with ISO New England’s
assertion that Regional Entities have
already been delegated by NERC the role
of designating critical sub-100 kV
facilities as part of the Compliance
Registry process.73
65. Some commenters question the
technical basis for extending PRC–023–
1 to sub-100 kV facilities. For example,
EEI argues that because it usually
requires multiple 69 kV lines to replace
one 138 kV line, it is highly unlikely
that sub-100 kV facilities will cause a
major cascade and much more likely
that sub-100 kV facilities will trip to end
a cascade, as occurred during the
August 2003 blackout. EPSA argues that
the Commission should apply
‘‘Reliability Engineering’’ to determine
whether there is a technical basis for its
proposal. SWTDUG and TAPS argue
that the Final Blackout Report does not
support extending the Reliability
Standard to relay settings on sub-100 kV
facilities.
66. We will not follow EPSA’s
suggestion to use Reliability Engineering
to identify critical facilities. In our view,
it is more appropriate to identify critical
sub-100 kV facilities (and, for that
matter, critical 100 kV–200 kV facilities)
by using established criteria specific to
the electric industry.74 The TPL
71 In general, we expect that the results of the
planning coordinator analysis and the processes
used by the Regional Entities to identify critical
facilities would have similar outcomes.
72 We note that the definition of the bulk electric
system is subject to change. See Order No. 693,
FERC Stats. & Regs. ¶ 31,242 at P 77.
73 ISO New England at 3. See also Order No. 693,
FERC Stats. & Regs. ¶ 31,242, at P 101.
74 EPSA states that ‘‘Reliability Engineering’’ is
currently used to develop modeling and
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
16923
Reliability Standards establish desired
system performance requirements
specific to a set of contingencies under
a set of base cases that cover critical
system conditions of the Bulk-Power
System, while Reliability Engineering,
as described by EPSA, is primarily used
in reliability-centered maintenance to
assess the optimum intervals and
practices for facility maintenance. We
strongly believe that, for the purposes of
PRC–023–1, it is appropriate to use
requirements that are specific to the
electric industry and that are supported
by decades of foundational planning
and operating principles and
experiences and that are embedded in
the TPL Reliability Standards rather
than criteria that may be more
appropriate to maintenance practices.
67. We also reject EEI’s claim that
there is no technical basis for extending
PRC–023–1 to sub-100 kV facilities.
Relay settings on such facilities should
be subject to PRC–023–1 because their
loss can also affect the reliability of the
Bulk-Power System. We also reject
TAPS’s assertion that the Commission
must exclude sub-100 kV facilities since
the Commission is required under
section 215(d)(2) of the FPA to give ‘‘due
weight’’ to the technical expertise of the
ERO. NERC has not provided a
sufficient technical justification to
support the exclusion of sub-100 kV
facilities. In its comments, NERC states
that extending PRC–023–1 to sub-100
kV facilities ‘‘may have merit’’ and
‘‘would require further study,’’ 75
indicating that it did not affirmatively
consider subjecting certain sub-100 kV
facilities to the Reliability Standard and
then reject the idea on the basis of its
technical expertise. Moreover, NERC
has not offered a technical basis for
opposing the Commission’s proposal.
NERC’s comments on the Commission’s
proposal pertain exclusively to the
relationship between the Compliance
Registry and entities’ obligations to
comply with Reliability Standards.
Contrary to TAPS’s assertion, NERC
does not offer a technical argument
against including certain sub-100 kV
facilities in PRC–023–1.
68. Similarly, with respect to EEI’s
and NERC’s claim that any expansion of
the Reliability Standard must be
developed through the Reliability
Standards development process, we
clarify that, as with our other directives
in this Final Rule, we do not prescribe
this specific change as an exclusive
maintenance strategies for complex systems,
including multiple failure testing, which has been
applied to systems such as oil pipelines and civil
infrastructures. EPSA at 6.
75 NERC Comments at 18.
E:\FR\FM\02APR2.SGM
02APR2
16924
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
solution to our reliability concerns
regarding sub-100 kV facilities. As we
have stated, the ERO can propose an
alternative solution that it believes is an
equally effective and efficient approach
to addressing the Commission’s
reliability concerns about the absence of
sub-100 kV facilities from PRC–023–1.
Moreover, while we expect planning
coordinators to use the same test to
identify critical sub-100 kV facilities as
they use to identify critical 100 kV–200
kV facilities, the ERO is free, pursuant
to Order No. 693, to propose a modified
Reliability Standard that contains a
different test for sub-100 kV facilities,
provided that the test represents an
‘‘equivalent alternative approach.’’
mstockstill on DSKH9S0YB1PROD with RULES2
c. Test for Identifying Sub-200 kV
Facilities
i. Overview
69. Finally, pursuant to section
215(d)(5) of the FPA, we direct the ERO
to modify Requirement R3 of the
Reliability Standard to specify the test
that planning coordinators must use to
determine whether a sub-200 kV facility
is critical to the reliability of the BulkPower System. We direct the ERO to file
its test, and the results of applying the
test to a representative sample of
utilities from each of the three
Interconnections, for Commission
approval no later than one year from the
date of this Final Rule.76
70. As we explained above, the
Commission proposed to direct the ERO
to adopt the ‘‘rule out’’ approach for 100
kV–200 kV facilities because it was
concerned that NERC’s ‘‘add in’’
approach would effectively exempt a
large percentage of facilities that should
otherwise be subject to the Reliability
Standard. Contrary to the suggestion of
some commenters, the Commission’s
concern was not based on a latent
distrust of planning coordinators, but on
the absence of a mandatory test in the
Reliability Standard for planning
coordinators to use to identify critical
facilities.77 Without such a test, the
Commission has no way of determining
whether the ‘‘add in’’ approach will
result in a comprehensive list of critical
facilities. As we also explained above,
because the ‘‘rule out’’ approach and the
‘‘add in’’ approach should ultimately
result in the same list of critical
facilities, the choice between them is
less important, from a reliability
standpoint, than the test that planning
76 We expect that the representative samples will
include large and small, rural and metropolitan
entities reflecting various topologies.
77 NERC agrees that there must be consistent
criteria for determining which 100 kV-200 kV
facilities are critical facilities. Id. at 12.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
coordinators must use to determine
whether a facility is a critical facility.
We conclude, therefore, that the lack of
such a mandatory test is a matter that
must be addressed by the ERO to ensure
that the Reliability Standard meets its
reliability objective. Otherwise, there is
no guarantee that all planning
coordinators will use comprehensive
and rigorous criteria that is consistent
across regions to identify all critical sub200 kV facilities, leaving the BulkPower System vulnerable to similar
problems that resulted in the cascade
during the August 2003 blackout.
71. Consistent with Order No. 693, we
provide ‘‘sufficient guidance so that the
ERO has an understanding of the
Commission’s concerns and an
appropriate, but not necessarily
exclusive, outcome to address those
concerns.’’ 78 In this way, we ensure that
the Commission’s directive is not ‘‘so
vague that the ERO would not know
how to adequately respond.’’ 79 Thus,
below we provide guidance for the
development of a test to determine
critical facilities.80
72. We first observe that PRC–023–1
directs planning coordinators to identify
facilities that are ‘‘critical to the
reliability of the bulk electric system.’’
In contrast, Recommendation 21A of the
Final Blackout Report refers to
‘‘operationally significant’’ facilities.
APPA, Exelon, and TAPS argue that, in
the context of the Reliability Standard,
‘‘critical to the reliability of the bulk
electric system’’ and ‘‘operationally
significant’’ carry the same meaning and
describe the same facilities. Exelon adds
that drafting history confirms that the
Reliability Standard drafting team
intended this interpretation.
73. We agree. In our view, ‘‘critical to
the reliability of the bulk electric
system’’ in PRC–023–1 and
‘‘operationally significant’’ in
Recommendation 21A are intended to
have the same meaning because PRC–
023–1 was developed to implement
Recommendation 21A. This conclusion
sheds some light on what facilities
should be identified as ‘‘critical to the
reliability of the bulk electric system’’
because, in Recommendation 21A, the
Task Force listed lines that are part of
78 Order No. 693, FERC Stats. & Regs. ¶ 31,242 at
P 185.
79 Id.
80 While the ERO is free to submit a modified
Reliability Standard that adopts the guidance set
forth below as the mandatory test, we will also
consider ‘‘an equivalent alternative approach
provided that the ERO demonstrates that the
alternative will adequately address the
Commission’s underlying concern or goal as
efficiently and effectively as the Commission’s
proposal’’ and is consistent with our guidance. Id.
P 186.
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
monitored flowgates and interfaces as
examples of ‘‘operationally significant’’
facilities. Importantly, the Task Force
did not recommend that NERC limit its
extended review only to monitored
flowgates and interfaces; it merely cited
monitored flowgates and interfaces as
examples of ‘‘operationally significant’’
facilities. If a facility trips on relay
loadability following an initiating event
and contributes to undesirable system
performance similar to what occurred
during the August 2003 blackout (e.g.,
cascading outages and loss of load) in
the same way that the loss of monitored
flowgates and interfaces contributed to
the August 2003 blackout, the facility is
operationally significant for the
purposes of Recommendation 21A, and
therefore critical to the reliability of the
bulk electric system for the purposes of
PRC–023–1. For example, the 138 kV
lines shown in Figure 5.12 of the Final
Blackout Report were not part of the
monitored flowgate of the 345 kV
Sammis-Star line or any other flowgate
in FirstEnergy, but the loss of these 138
kV facilities affected loading on
Sammis-Star, and the loss of SammisStar was the point at which the blackout
went into its dynamic cascading phase.
Thus, we reject assertions, made in the
context of comments on the ‘‘rule out’’
approach, that facilities that are not part
of a defined and routinely monitored
flowgate should automatically be
excluded from the Reliability Standard’s
scope.
ii. Guidance on the Test
74. Neither the Final Blackout Report
nor the Reliability Standard establishes
a mandatory test for planning
coordinators to use to determine if a
facility is ‘‘operationally significant’’ or
‘‘critical to the reliability of the bulk
electric system’’ with respect to relay
settings and the prevention of cascading
outages. However, in its comments on
the NOPR, NERC includes the guidance
for identifying operationally significant
100 kV–200 kV facilities that the NERC
System Protection and Control Task
Force supplied to Regional Entities
during the voluntary Beyond Zone 3
relay review and mitigation program.
This guidance advised Regional Entities
to identify:
All circuits that are elements of flowgates
in the Eastern Interconnection, Commercially
Significant Constraints in the Texas
Interconnection, or Rated Paths in the
Western Interconnection. This includes both
the monitored and outage element for OTDF
sets.
All circuits that are elements of system
operating limits (SOLs) and interconnection
reliability operating limits (IROLs), including
both monitored and outage elements.
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
All circuits that are directly related to offsite power supply to nuclear plants. Any
circuit whose outage causes unacceptable
voltages on the off-site power bus at a nuclear
plant must be included, regardless of its
proximity to the plant.
All circuits of the first 5 limiting elements
(monitored and outaged elements) for
transfer interfaces determined by regional
and interregional transmission reliability
studies. If fewer than 5 limiting elements are
found before reaching studied transfers, all
should be listed.
Other circuits determined and agreed to by
the reliability authority/coordinator and the
Regional Reliability Organizations.
mstockstill on DSKH9S0YB1PROD with RULES2
75. After careful review, we conclude
that the guidance provided by the NERC
System Protection and Control Task
Force, if applied appropriately, would
identify some, but likely not all, critical
sub-200 kV facilities. There are some
critical facilities that the guidance
would not identify and would need to
identify in order for it to be a fully
acceptable test and meet the reliability
objectives of PRC–023–1.
76. In the Commission’s view, the
NERC System Protection and Control
Task Force guidance focuses primarily
on identifying facilities that are
‘‘operationally significant’’ between
regions (e.g., between ECAR and SERC)
or between sub-regions (e.g., between
Southern and Entergy) and would not
necessarily identify operationally
significant facilities within a sub-region
or a company.81 In order to achieve its
objective, however, PRC–023–1 must
apply to relay settings on all
operationally significant sub-200 kV
facilities that could trip on relay
loadability and contribute to cascading
outages and the loss of load, including
those within a sub-region or a company.
The ERO could refine the NERC System
Protection and Control Task Force’s
guidance into an acceptable mandatory
test by, among other things, revising it
to include the assessment and
identification of facilities within a
region, sub-region, or company, whose
inadvertent outage due to relay
loadability could result in undesirable
system performance.82
81 We understand that some interregional studies
include only a portion of all the lines with the
remaining modeled as equivalents. Such an analysis
could not possibly address the operational
significance of the lines that were modeled only as
equivalents.
82 The ERO is not limited to proposing a revised
version of the NERC System Protection and Control
Task Force’s guidance as the mandatory test. It can
also develop a new test to identify critical sub-200
kV facilities or refine other aspects of the System
Protection and Control Task Force test. Any test
that the ERO submits, including one based on the
NERC System Protection and Control Task Force’s
guidance, must be consistent with the general
guidelines set forth in this Final Rule.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
77. The test for identifying
operationally significant/critical sub200 kV facilities should identify
facilities that must have their relays set
in accordance with PRC–023–1 to avoid
the undesirable system performance that
Recommendation 21A was intended to
prevent. It should also describe the
steady state and dynamic base cases that
planning coordinators must use in their
assessment.
78. Recommendation 21A of the Final
Blackout Report was developed to
prevent undesirable system performance
like the undesirable performance that
occurred during the August 2003
blackout. During the blackout, the
inadvertent tripping of facilities due to
loadability resulted in undesirable
system performance in the form of
cascading outages and the loss of load.
Since PRC–023–1 implements Final
Blackout Recommendation No. 21A, it
too must prevent the undesirable system
performance that would include, among
other performance factors, cascading
outages and the loss of load.
79. To achieve this goal, the test to
determine which sub-200 kV facilities
are subject to PRC–023–1 must include
or be consistent with the system
simulations and assessments that are
required by the TPL Reliability
Standards and meet the system
performance levels for all Category of
Contingencies used in transmission
planning. As discussed in the NOPR,
the Commission expects that the base
cases used to determine the facilities
subject to PRC–023–1 will include
various generation dispatches,
topologies, and maintenance outages
assumed in the planning time frame,
and will consider the effect of
redundant and backup protection
systems.83 As such, the base cases shall
bracket all stable operating conditions.
80. Thus, the ERO must develop a test
that: (a) Defines expectations of
desirable system performance; and (b)
describes the steady state and dynamic
base cases that the planning coordinator
must use in its assessments to carry out
Requirement R3. The goal of the test
must be consistent with the general
reliability principles embedded in the
existing series of TPL, Transmission
Operations (TOP), Reliability
Coordination (IRO), and Protection and
Control (PRC) Reliability Standards.
This is, in fact, good utility practice
worldwide in that, if an initiating
83 NOPR, FERC Stats. & Regs. ¶ 32,642 at P 43,
n.71. A ‘‘base case’’ refers to the transmission system
model used for performing planning studies.
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
16925
event 84 results in inadvertent outage 85
or the tripping of other non-faulted
facilities that would result in cascading
outages or loss of load, or violation of
any of the applicable criteria, these
facilities must be identified for remedial
actions (such as equipment
modifications, or a reduction in IROLs
or SOLs) to ensure Reliable Operation.
We provide guidance on both features of
the test below.
iii. Desirable System Performance
81. During the August 2003 blackout,
facilities (regardless of the voltage class
and whether or not they were part of
monitored flowgates) inadvertently
tripped due to loadability conditions,
resulting in undesirable system
performance under the TPL Reliability
Standards in the form of exceeding SOL
and IROL limits, cascading outages, and
the loss of load. Consequently,
consistent with the TPL Reliability
Standards, the first component of
desirable system performance that the
test must seek to maintain is the
continuity of all firm load supply except
for supply directly served by the faulted
facility. In other words, it is the
Commission’s view that the test must
identify facilities necessary to achieve
the reliability performance for Category
B and Category C contingencies—which
would include no non-consequential
load loss (for Category B) and no
cascading outages (for Category B and
Category C) for all stable operating
conditions.86
82. The TPL Reliability Standards
address, among other things, the type of
simulations and assessments that must
be performed to ensure that reliable
systems are developed to meet present
and future systems needs.87 Table 1 of
the TPL Reliability Standards
establishes the desired system
performance requirements for a range of
contingencies grouped according to the
number of elements forced out of
service as a result of the contingency.
84 In power systems, an ‘‘initiating event’’
generally refers to any event on the electric system
that begins a series of actions. For transmission
planning purposes, an initiating event is usually
modeled as a type of fault. A ‘‘fault’’ is defined in
the NERC Glossary of Terms used in Reliability
Standards as ‘‘[a]n event occurring on an electric
system such as a short circuit, a broken wire, or an
intermittent connection.’’ See NERC Glossary of
Terms used in Reliability Standards at 7.
85 An ‘‘inadvertent outage’’ generally refers to an
unplanned outage of a facility. For the purposes of
PRC–023–1, an inadvertent outage is the tripping of
a facility due to loadability conditions.
86 In Order No. 693, the Commission explained
that the term ‘‘consequential load loss’’ refers to
‘‘load that is directly served by the elements that are
removed from service as a result of the
contingency.’’ Order No. 693, FERC Stats. & Regs.
¶ 31,242 at P 1794, n.461.
87 Id. at P 1683.
E:\FR\FM\02APR2.SGM
02APR2
16926
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
mstockstill on DSKH9S0YB1PROD with RULES2
Consistent with Table 1 of the TPL
Reliability Standards, with the
exception of extreme contingency
events, the system should always be
stable and within both thermal and
voltage limits for Reliable Operation.88
This is the second component of
desirable system performance that the
test must seek to determine.
83. Finally, while the curtailment of
firm transfers is permitted to prepare for
the next contingency, it is generally not
the desired system performance for
single contingencies required by Table 1
of the TPL Reliability Standards. Thus,
continuity of all firm transfers is the
third component of desirable system
performance.89
84. In sum, because the Bulk-Power
System is planned and operated as a
minimum criterion to maintain Reliable
Operation for the single contingency
loss of any transmission facility,90 for
Category B contingencies, desirable
system performance includes: (1)
Continuity of all firm load supply
except for supply directly served by the
faulted facility and no cascading
outages; (2) the maintenance of all
facilities within their applicable
thermal, voltage, or stability ratings
(short time ratings are applicable); and
(3) the continuance of all firm
transfers.91 For Category C
contingencies, desirable system
performance includes: (1) Continuity of
all firm load supply except for planned
interruptions and no cascading outages;
(2) the maintenance of all facilities
within their applicable thermal, voltage,
or stability ratings (short time ratings are
applicable); and (3) the continuance of
all firm transfers that are not part of
planned interruptions.92
88 Extreme contingency events are the loss of two
or more (multiple) elements (Category D).
89 See Reliability Standard TPL–002–0. Footnote
b of Table 1 allows for the interruption of firm load
for consequential load loss. This footnote is
currently the subject of an order setting a deadline
for required revisions in RM06–16–009.
90 Reliability Standard TOP–002–0, Normal
Operations Planning, Requirement R6 establishes
that each balancing authority and transmission
operator shall plan to meet unscheduled changes in
syst em configuration and generation dispatch (at a
minimum N–1 Contingency Planning) in
accordance with NERC, Regional Reliability
Organization, sub-regional, and local reliability
requirements.
91 See Reliability Standard TPL–002–0. Footnote
b of Table 1 allows for the interruption of firm load
for consequential load loss.
92 See Reliability Standard TPL–003–0. Footnote
c of Table 1 allows for the controlled interruption
of electric supply to customers (load shedding), the
planned removal from service of certain generators,
and/or the curtailment of contracted Firm (nonrecallable reserved) electric power transfers
necessary to maintain the overall reliability of the
interconnected transmission systems.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
iv. Steady State and Dynamic Base
Cases
85. With respect to the steady state
and dynamic base cases that planning
coordinators must use as part of their
assessments, the Commission stated in
the NOPR that it expects planning
coordinators to use base cases that
include various generation dispatches,
topologies, and maintenance outages,
and that consider the effect of
redundant and backup protection
systems. The Commission also stated
that the process for identifying critical
facilities must include the same system
simulations and assessments as the TPL
Reliability Standards for all stable
operating conditions. The TPL
Reliability Standards establish the types
of simulations and assessments that
must be performed to ensure that
reliable systems are developed to meet
present and future system needs. It is
through these simulations and
assessments that the planning authority
and transmission planner demonstrate
that their portion of the interconnected
transmission system is planned for
Reliable Operation under contingency
conditions. In order to produce a ‘‘valid’’
assessment, the planning authority or
transmission planner must demonstrate
that its network can be operated to
supply projected customer demands and
projected firm transmission service, at
all demand levels, over the range of
forecast system demands, and under the
contingency conditions defined in Table
1.93 The Commission understands that
Category B contingencies would cover
most of the primary relay applications
and Category C contingencies would
cover most of the backup and remote
circuit breaker failure relay
applications. However, if a portion of a
system is expected to be operated
differently than the minimal TPL base
cases, additional base cases should be
included to include all stable operating
conditions.
86. In addition to the TPL Reliability
Standards, the TOP Reliability
Standards are relevant to the steady
state and dynamic base cases that
reliability entities must use as part of
their assessments. The TOP Reliability
Standards establish, among other things,
the responsibilities and decision-making
authority for Reliable Operation in realtime. Reliability Standard TOP–002–0
establishes requirements for operation
plans and procedures essential for
Reliable Operation, including
93 In order for a planning authority and
transmission provider to produce a ‘‘valid’’
assessment, the assessment must be demonstrated
as satisfying each of the criteria established in TPL–
002–0 through TPL–004–0, Requirement R1.
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
development of SOLs and IROLs that
will result in acceptable system
responses for unplanned events.
87. At a minimum, the Bulk-Power
System is planned and operated to
maintain Reliable Operation for the
single contingency loss of any
transmission facility.94 Consequently,
the base cases that planning
coordinators must use in their
assessments for PRC–023–1
applicability should represent, at a
minimum, the fundamental base case
categories to plan for Reliable Operation
and the real-time response for Reliable
Operation. Fundamental base case
categories may be more extensive than
those that are central to meeting the
performance requirements established
in TPL–002–0, Requirement R1 if they
do not include all reliable operating
conditions. We believe that initiating
events that represent all feasible types
and locations of faults, including
evolving faults, must be simulated in
each of the fundamental base case
categories to determine the performance
of the system. This is necessary for
PRC–023–1 applicability because any of
these initiating events can occur and
must be included in determining
performance. It is also consistent with
the development of valid transmission
assessments required by the TPL
Reliability Standards.95 Under this
approach, a facility would be identified
as a critical facility if, during a
simulation starting with the base cases,
its removal from service following an
initiating event would prevent desirable
system performance, as we have defined
it here.
88. With this in mind, base case
categories in the application of a test to
identify critical facilities must:
(1) Represent the full range of demand
and transfer levels. This is consistent
with TPL–002–0, Requirement R1.3.5
(which requires that all projected firm
transfers be modeled) and TPL–002–1,
Requirement R1.3.6 (which requires that
all studies and simulations be
performed and evaluated for selected
demand levels over the range of forecast
system demands);
(2) Include all stable operating
conditions and allowable topologies,
94 See Reliability Standard TPL–002–0, System
Performance Following Loss of a Single BES
Element. See also Reliability Standard TOP–002–0,
Normal Operations Planning, Requirement R6 that
establishes that each balancing authority and
transmission operator shall plan to meet
unscheduled changes in system configuration and
generation dispatch (at a minimum N–1
Contingency Planning) in accordance with NERC,
Regional Reliability Organization, sub-regional, and
local reliability requirements.
95 See Order No. 693, FERC Stats. & Regs.
¶ 32,642 at P 1683.
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
such as all allowable planned outages.
This is consistent with TPL–002–0,
Requirement R1.3.12 (which requires
that the planned (including
maintenance) outage of any bulk electric
equipment (including protection
systems or their components) be
included at those demand levels for
which planned (including maintenance)
outages are performed); and TOP–004
Requirement R4 (which requires
operating the actual system in a known
operating state);
(3) Include the effects of the
protection system design and settings of
the as designed protection systems with
identification of those that are not
within the Requirements of PRC–023–1.
This is consistent with TPL–002–0,
Requirement R1.3.8 with regard to
existing and planned protection
systems;
(4) Include the effects of the failure of
a single component within the as
designed Protection Systems, consistent
with TPL–002–0 Requirement R1.3.10,
but with regard to backup and
redundant protection systems; and
(5) Include various generation
dispatch patterns. This is consistent
with TOP–002–0 Requirement R6
(which requires that each balancing
authority and transmission operator
plan to meet unscheduled changes in
system configuration and generation
dispatch (at a minimum N–1
contingency planning) in accordance
with NERC, Regional Reliability
Organization, sub-regional and local
reliability requirements).
89. Our guidance above for
developing a test to determine
operationally significant facilities that
should be subject to PRC–023–1 is
consistent with Recommendation No.
21A of the Final Blackout Report and
with planning and operating practices
for Reliable Operation of the BulkPower System. Using a flowgate as an
example, to derive the IROL of a given
flowgate under a given range of system
conditions, the TOP operations planner,
in carrying out day-ahead reliability
assessments, would simulate
contingencies on critical facilities at a
given loading on the flowgate,
proceeding through the list of all critical
and operationally significant facilities
that form the monitored flowgates or
other facilities as determined to be
applicable, either by actual simulation
tests or engineering judgment, to
eliminate the less critical facilities that
are not binding to the IROL and
facilities that are not part of that
flowgate. The derived IROLs would be
valid only if none of the remaining
flowgate facilities inadvertently trip
with the binding facility or facilities on
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
which the contingency is applied.
Similarly, for the purposes of the test
described above, the facilities that are
not ‘‘operationally significant,’’ and
therefore can be excluded from PRC–
023–1, would be those that trip due to
loadability conditions at the same time
as an initiating event involving a critical
or operationally significant facility but
do not impede desirable system
performance.
90. For the particular flowgate under
analysis by the TOP operations planner,
the limiting facilities are those that
result in the lowest IROL, and thus are
commonly referred to as critical
facilities. All the remaining flowgate
facilities and other facilities that are not
part of the flowgate under analysis are
operationally significant for two main
conditions: (i) Following a contingency
on a binding or critical facility, they will
not trip inadvertently and result in an
increase in the loadings on other
facilities and/or stable power swings
that could result in additional trips,
thereby invalidating the derived
IROL; 96 and (ii) the outage of these
operationally significant facilities would
reduce the IROL since the flowgate
would have one less element before a
contingency on the critical facility is
applied. Similar analysis would be
conducted for other facilities that are
not part of a flowgate.
v. Response to Relevant Comments
91. The Commission received
comments pertaining to its statements
about the process for identifying critical
100 kV–200 kV facilities and its
proposal to permit case-by-case
exceptions for the limited number of
facilities that are not critical to the
reliability of the bulk electric system
and that would not result in cascading
outages, instability, uncontrolled
separation, violation of facility ratings,
or interruption of firm transmission
service.97 While some comments are no
longer relevant given the Commission’s
decision not to adopt the ‘‘rule out’’
approach, others bear on how to
understand the designation ‘‘critical to
the reliability of the bulk electric
system’’ in the context of Requirement
R3.
92. For example, APPA argues that
the Commission should allow some
diversity in regional definitions of
critical facilities to account for physical
differences in network topology, design,
and performance. To this end, APPA
96 In Order No. 693, the Commission explained
that ‘‘[i]n deriving SOLs and IROLs * * * the
functions, settings, and limitations of protection
systems are recognized and integrated.’’ Order No.
693, FERC Stats. & Regs. ¶ 31,242 at P 1435.
97 NOPR, FERC Stats. & Regs. ¶ 32,642 at P 43.
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
16927
proposes that the Commission direct
NERC to develop a process whereby
each region can develop a common
region-wide approach to identifying
critical facilities.98 We believe that the
test set forth above is best implemented
uniformly across all regions. We direct
a uniform approach rather than the one
suggested by APPA because, as NERC
comments in its petition, the effects of
PRC–023–1 are not constrained to
regional boundaries.99 Any test to
identify critical facilities must be
consistent across regions so that the
effects of protective relay operation are
consistent across regions.
93. Duke comments that application
of the existing TPL standards to its
Midwest and Carolina systems has not
identified any sub-200 kV facilities as
critical (i.e., there have been no
showings that the loss of any such
facilities could result in cascading
outages, instability, or uncontrolled
separation).100 As we have explained,
however, the test that would be
developed by the ERO and that would
adhere to the guidance we provide in
this Final Rule would take into
consideration both the desired system
performance that PRC–023–1 was
developed to achieve and the desired
system performance required by the TPL
Reliability Standards for Reliable
Operation.
94. We also note that some
commenters argue that the Reliability
Standard should not apply to radial
transmission lines and Category D
Contingencies. With regard to radial
transmission lines, we note that the
NERC definition of ‘‘bulk electric
system’’ does not include radial
transmission facilities serving load with
only one transmission source. We
reiterate that we do not intend to
expand the applicability of PRC–023–1
beyond NERC’s Statement of Registry
Criteria.
95. Additionally, we do not conclude
that the applicability of PRC–023–1
should be determined based on Category
D contingencies (pursuant to Table I of
the TPL Reliability Standards). We
understand that relay settings cannot be
determined with great certainty for
extreme multi-contingency conditions—
the types of conditions consistent with
the Category D contingencies of the TPL
98 APPA
at 17, 26–27.
Petition at 18–19, 39–41.
100 Duke adds that potential revisions to the TPL
Reliability Standards appear as though they will
raise the bar in clarifying the requirements for firm
transmission service (i.e., it appears that there will
be more restrictions on loss of local load that is not
connected to a faulted system element), but are
unlikely to result in many facilities under 200 kV
being considered critical to bulk electric system
reliability.
99 NERC
E:\FR\FM\02APR2.SGM
02APR2
16928
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
Reliability Standards. In fact, Reliability
Standard TPL–004–0 requires that the
planning authority and transmission
planner demonstrate through a valid
assessment and documentation that
their portion of the interconnected
electric system is evaluated only for the
risks and consequences of such events.
96. Some commenters argue that
violation of facility ratings and
interruption of firm transmission service
should not be part of the applicability
test. We are not persuaded by this
argument because, as previously
discussed, these are included in the
three reliability components of desirable
system performance.
97. Finally, commenters argue that
there should be some mechanism for
entities to challenge criticality
determinations. We agree that such a
mechanism is appropriate and direct the
ERO to develop an appeals process (or
point to a process in its existing
procedures) and submit it to the
Commission no later than one year after
the date of this Final Rule.
D. Generator Step-Up and Auxiliary
Transformers
1. Omission From the Reliability
Standard
98. NERC stated that generator stepup transformer relay loadability was
intentionally omitted from PRC–023–1
and would be addressed in a future
Reliability Standard.101
mstockstill on DSKH9S0YB1PROD with RULES2
a. NOPR Proposal
99. In the NOPR, the Commission
stated that the ERO must address
generator step-up and auxiliary
transformer relay loadability in a timely
manner and proposed directing the ERO
to modify PRC–023–1 to include these
issues. The Commission also requested
comments suggesting a reasonable time
frame for the ERO to either modify PRC–
023–1 to address generator step-up and
auxiliary transformer relay loadability
or to develop a new Reliability Standard
addressing these issues.
b. Comments
100. NERC states that within two
years it expects to submit to the
Commission a Reliability Standard that
addresses generator relay loadability.
NERC explains that a team under the
NERC System Protection and Control
Subcommittee is working with the
Institute of Electrical and Electronics
Engineers (IEEE) Power System Relay
101 The Commission notes that in its comments
NERC refers to ‘‘generator relay loadability.’’ In the
context of our determination, we understand
‘‘generator step-up and auxiliary transformer
loadability’’ and ‘‘generator relay loadability’’ to
refer to the same thing.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
Committee on a technical reference
document (Power Plant and
Transmission System Protection and
Coordination) that addresses
transmission protection coordination
with generation protection systems,
provides technical guidance for the
revision of PRC–001,102 and includes
technically based loadability
requirements.103 NERC adds that
generator relay loadability is just a
single facet of the total system
protection coordination requirement
between generators and transmission
lines, and recommends that all
coordination issues between generators
and transmission lines, including
generator step-up and auxiliary
transformer relay loadability, reside in
PRC–001–2.
101. Many commenters agree that
generator step-up and auxiliary
transformer relay loadability must be
addressed in a timely manner, but in a
separate Reliability Standard from PRC–
023–1. In general, these commenters
argue that properly addressing generator
step-up and auxiliary transformer relay
loadability requires in-depth technical
analysis and careful consideration of
related protection and coordination
issues and should not be rushed to
accommodate PRC–023–1.
102. Entergy argues that the NOPR
appears to treat generator step-up and
auxiliary transformers as transmissionrelated facilities, contrary to the
Commission’s ratemaking precedent.
Entergy explains that generator step-up
and auxiliary transformers are not
transmission facilities, and that their
function is to connect generation
capacity to the transmission grid at
appropriate voltage levels. Entergy adds
that when generation is off-line, neither
generator step-up transformers nor
auxiliary transformers are required for
transmission throughput.
103. The PSEG Companies argue that
developing generator step-up and
auxiliary transformer loadability
requirements requires a significant effort
by NERC and generation companies,
and once developed, may require
generation companies to conduct
specific engineering studies for each of
their generator step-up transformers.
The PSEG Companies suggest that the
Commission direct NERC to consider
whether it can establish and determine
a generic rating percentage.
102 The purpose of PRC–001 is to ensure that
system protection is coordinated among operating
entities.
103 NERC presented a draft of the technical
reference document at its September 2009 meeting.
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
c. Commission Determination
104. We decline to adopt the NOPR
proposal and will not direct the ERO to
modify PRC–023–1 to address generator
step-up and auxiliary transformer
loadability. After further consideration,
we conclude that it does not matter if
generator step-up and auxiliary
transformer loadability is addressed in a
separate Reliability Standard, so long as
the ERO addresses the issue in a timely
manner and in a way that is coordinated
with the Requirements and expected
outcomes of PRC–023–1.
105. In light of the ERO’s statement
that within two years it expects to
submit to the Commission a proposed
Reliability Standard addressing
generator relay loadability, we direct the
ERO to submit to the Commission an
updated and specific timeline
explaining when it expects to develop
and submit this proposed Standard.
While we recognize that generator relay
loadability is a complex issue that
presents different challenges than
transmission relay loadability, we note
that more than six years have passed
since the August 2003 blackout and
there is still no Reliability Standard that
addresses generator relay loadability.
With this in mind, the Commission will
not hesitate to direct the development of
a new Reliability Standard if the ERO
fails to propose a Standard in a timely
manner. While the ERO is developing a
technical reference document to
facilitate the development of a
Reliability Standard for generator
protection systems, only Reliability
Standards create enforceable obligations
under section 215 of the FPA.
106. We also expect that the ERO will
develop the Reliability Standard
addressing generator relay loadability as
a new Standard, with its own individual
timeline, and not as a revision to an
existing Standard. While we agree that
PRC–001–1 requires, among other
things, the coordination of generator
and transmission protection systems, we
think that generator relay loadability,
like transmission relay loadability,
should be addressed in its own
Reliability Standard if it is not to be
addressed with transmission relay
loadability.
107. Additionally, although we do not
adopt the NOPR proposal, we reject
Entergy’s claim that including generator
and transmission relay loadability in the
same Reliability Standard would
conflict with how the Commission treats
generator step-up transformers for the
purposes of ratemaking. The
Commission’s primary objectives in
ratemaking differ from its central
objectives concerning reliability
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
mstockstill on DSKH9S0YB1PROD with RULES2
regulation. In the ratemaking context,
the Commission is concerned that
jurisdictional generator step-up and
auxiliary transformers are classified in a
way that ensures just and reasonable
rates. In the reliability context,
addressing transmission and generator
relay loadability in the same Reliability
Standard facilitates the reliability goal
of ensuring coordination between
transmission and generator protection
systems, as required by PRC–001–1.
108. Finally, the PSEG Companies
suggest that the ERO consider whether
a generic rating percentage can be
established for generator step-up
transformers and, if so, determine that
percentage. Although we do not adopt
the NOPR proposal, we encourage the
ERO to consider the PSEG Companies’
suggestion in developing a Reliability
Standard that addresses generator relay
loadability.
to provide backup protection to
transmission lines. The commenters
assert that because phase fault back-up
protection on the low voltage side of a
generator step-up transformer is
designed to detect un-cleared faults on
the system, with the primary function of
protecting the generator and the
transformer from supplying a prolonged
fault current, the relays discussed by the
Commission are set pursuant to IEEE
Standard C37.102 instead of PRC–023–
1.
c. Commission Determination
112. We reiterate that the
requirements of PRC–023–1 apply to all
protection systems as described in
Attachment A that are intended to
provide protection to the facilities
defined in section 4.1.1 through 4.1.4 of
the Reliability Standard, regardless of
whether the protection systems provide
primary or backup protection and
2. Generator Step-Up Transformer
regardless of their physical location.
Relays as Back-Up Protection
Our interpretation is based on the fact
that protective relays are applied to
a. Commission’s Statements in the
protect specific system elements and, it
NOPR
is consistent with approved Reliability
109. In describing PRC–023–1 in the
Standards,105 the zones of protection
NOPR, the Commission emphasized
principle on which relaying schemes are
that:
designed,106 and NERC’s voluntary
[T]he requirements of PRC–023–1 apply to
Beyond Zone 3 Review, which
all protection systems as described in
examined all primary and backup
Attachment A that provide protection to the
protection systems.107
facilities defined in sections 4.1.1 through
113. We also clarify that protective
4.1.4 of PRC–023–1, regardless of whether the
relays can be applied as back-up
protection systems provide primary or
protection in two different ways: They
backup protection and regardless of their
physical location. * * * For example, a
can be physically located at the
protective relay physically installed on the
generator terminal on the low-voltage
low-voltage side of a generator step-up
side of a generator step-up transformer
transformer with the purpose of providing
and provide backup protection for a
backup protection to a transmission line
Bulk-Power System element (i.e., for a
operated above 200 kV must be set in
transmission line outside of the
accordance with the requirements of PRC–
generator zone of protection), as
023–1 because it is applied to protect a
discussed in the NOPR, or provide backfacility defined in [] PRC–023–1.104
up protection for the generator and the
b. Comments
step-up transformer (i.e., within the
110. EPSA and Ontario Generation
generator zone of protection), as the
disagree with the Commission’s
commenters discuss. In this Reliability
statements and argue that the
Standard, the Commission is referring to
Commission’s example contains an
the first type of relays; i.e., relays that
error. Ontario Generation asserts that
are applied to provide back-up
protective relaying that does not directly protection to Bulk-Power System
sense a current flow on a particular
elements and that would sense
transmission circuit cannot affect its
increased current flow due to a fault on
loadability. In that respect, Ontario
105 See, e.g., Reliability Standard PRC–001–1,
Generation argues that the Reliability
Requirement R1 (requiring that ‘‘[e]ach
Standard’s existing requirements
Transmission Operator, Balancing Authority, and
correctly refer to protection systems at
Generator Operator shall be familiar with the
specific circuit terminals.
purpose and limitations of protection system
111. EPSA and Ontario Generation
schemes applied in its area’’ (emphasis added)).
106 Protective relays are applied to protect specific
also challenge the Commission’s
elements within its zone of protection on the
implication that generator step-up
electric system. The ‘‘zone of protection’’ principle
transformer relays are subject to the
is used to ensure that each element on the electric
Reliability Standard if their purpose is
system is provided, at most primary, and at least
104 NOPR,
FERC Stats. & Regs. ¶ 32,642 at P 33
(emphasis added).
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
backup, protection so that there are no unprotected
areas.
107 NERC Comments at 13.
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
16929
a Bulk-Power System transmission
circuit. In the NOPR, the Commission
explained that distance relays
physically located at the generator
terminal that are applied to protect
Bulk-Power System facilities must be
coordinated with primary protection
systems for a transmission line and be
set to see through 108 the step-up
transformer, providing backup
protection for un-cleared faults on the
Bulk-Power System. Consequently,
these relays will sense increased current
flow and may trip on high load and
therefore must also be set pursuant to
PRC–023–1. If the primary protection
system of the transmission line fails to
operate, or does not operate within a
certain time, the backup protection
operates and trips Bulk-Power System
elements that it is applied to protect.
114. Our statement that such relays
are subject to the Reliability Standard is
not in conflict with the use of a
protection system to protect the
generator/step-up transformer in the
context of other industry standards,
such as IEEE Standard C37.102,109 or
with the exclusion in section 3.4 of
Attachment A to PRC–023–1 of
generator relays that are susceptible to
load. The relays that we referred to in
the NOPR, while they may be physically
located at the generator terminal or on
the low-voltage side of the generator
step-up transformer, are applied to
provide backup protection for BulkPower System elements. This
application is different from ‘‘generator
relays,’’ which are also physically
located at the generator, but are applied
to protect the generator.
E. Need To Address Additional Issues
115. In the NOPR, the Commission
identified two additional issues that the
ERO must address to ensure Reliable
Operation of the Bulk-Power System: (1)
Zone 3/zone 2 relays applied as remote
circuit breaker failure and backup
protection; and (2) protective relays
operating unnecessarily due to stable
power swings.
1. Zone 3/Zone 2 Relays Applied as
Remote Circuit Breaker Failure and
Back-Up Protection
a. NOPR Proposal
116. In the NOPR, the Commission
expressed concern about the impact that
108 To ‘‘see through’’ refers to a protective relay
setting where, based on the apparent impedance as
measured by the relay, the relay will detect faults
beyond, i.e., ‘‘see through,’’ a bulk electric system
element.
109 IEEE Standard C37.102 (IEEE Guide for AC
Generator Protection) provides generally accepted
forms of relay protection applied to protect the
synchronous generator and its excitation system.
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
16930
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
zone 3/zone 2 relays applied as remote
circuit breaker failure and backup
protection can have on reliability when
they operate without a time delay or for
non-fault conditions. The Commission
explained that if a zone 3/zone 2 relay
detects a fault on an adjacent
transmission line within its reach, and
the relay on the faulted line fails to
operate, the zone 3/zone 2 relay will
operate as a backup and remove the
fault; when it does, however, it will
disconnect both the faulted
transmission line and ‘‘healthy’’
facilities that should have remained in
service. The Commission noted that
zone 3/zone 2 relays are typically set to
operate after a time delay in order to
ensure coordination of protection and
avoid unnecessarily disconnecting
‘‘healthy’’ facilities.110
117. The Commission also explained
that the large reach of a zone 3/zone 2
relay makes it susceptible to operating
for certain non-fault conditions, such as
very high loading and large, but stable
power swings, because the current and
voltage as measured by the impedance
relay may fall within the very large
magnitude and phase setting of the
relay.111 The Commission cited the Task
Force’s finding that fourteen 345 kV and
138 kV transmission lines disconnected
during the August 2003 blackout
because of zone 3/zone 2 relays applied
as remote circuit breaker failure and
backup protection,112 including several
zone 2 relays in Michigan that
overreached their protected lines by
more than 200 percent and operated
without a time delay.113 The
Commission noted that while these
relays operated according to their
settings, the Task Force concluded that
they operated so quickly that they
impeded the natural ability of the
electric system to hold together and did
not allow time for operators to try to
stop the cascade.114
118. The Commission acknowledged
NERC’s claim that PRC–023–1 is silent
on the application of zone 3/zone 2
relays as remote circuit breaker failure
and backup protection because it
establishes requirements for any loadresponsive relay regardless of its
protective function.115 Nevertheless,
given the Task Force’s conclusions
about the role of zone 3/zone 2 relays
in the August 2003 blackout, the
Commission proposed to direct the ERO
to develop a maximum allowable reach
110 NOPR,
FERC Stats. & Regs. ¶ 32,642 at P 50.
P 52.
112 Final Blackout Report at 80.
113 Id.
114 Id.
115 See NERC Petition at 38–39.
111 Id.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
for zone 3/zone 2 relays applied as
remote circuit breaker failure and
backup protection.116
b. Comments
119. NERC and other commenters
argue that PRC–023–1 already addresses
the Commission’s concerns because it
establishes loadability limits based on
protection-zone-specific limitations,
such as equipment thermal ratings and
maximum power transfer capability, for
all load responsive relays, independent
of their application.117
120. EEI states that an entity will first
develop protective relay settings that
ensure adequate protection of its facility
or facilities and then apply Requirement
R1. EEI states that if the entity cannot
satisfy Requirement R1, it must change
its relay scheme to accommodate the
need for protection and to comply with
PRC–023–1.118 EEI maintains that
Requirement R1 addresses the
Commission’s concern in the NOPR
because no exemption is given to relays
that are set to cover adjacent lines in the
event of breaker failure. EEI contends,
therefore, that PRC–023–1 does not need
to identify any maximum reach
allowable outside of the impact on
loadability. EEI further argues that
issues of protective relay settings that
over reach adjacent lines and trip with
insufficient delay are coordination
issues and not transmission relay
loadability issues. EEI adds that, if
remote back-up relays cannot provide
adequate breaker failure coverage and
still comply with PRC–023–1, then local
breaker failure relaying must be
applied.119
121. BPA explains that by complying
with one of the sub-requirements in
Requirement R1 (R1.1 through R1.13),
entities’ zone 3/zone 2 relay settings
will be based on the real load carrying
requirements of the line to which they
are applied, but will not operate for
allowable line loads. BPA argues that a
blanket maximum reach limit would
nullify the thirteen sub-requirements in
Requirement R1, prevent entities from
optimizing their relay settings for each
situation, and unnecessarily reduce
protection. Exelon states that PRC–023–
1 allows entities to assess their relays’
loadability based on the most severe
line ratings at severely depressed
voltage, and either includes a margin
beyond these ratings or is based on the
ability of a circuit to actually carry a
load given its length and/or location
116 NOPR,
FERC Stats. & Regs. ¶ 32,642 at P 53.
Consumers Energy, Dominion, Duke,
Entergy, Exelon, EEI, Oncor, PG&E, SCEG,
Southern, TAPS.
118 EEI at 19.
119 Id. at 20.
117 See
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
within the system. Entergy asserts that
maximum reaches are affected by the
inherent capabilities of the relays, such
as where load encroachment is present.
122. ATC argues that the
Commission’s proposal may put an
arbitrarily low loading limit on some
transmission lines. ATC explains that
on a short transmission line, a relay
setting of several times the line’s
impedance would not limit the loading
of the line, whereas on a long
transmission line the same impedance
setting would limit loading. ATC argues
that a maximum allowable reach is
immaterial because the security of a
relay’s setting is determined by the
relay’s load-sensitive trip point, together
with an appropriate load margin with
respect to the maximum load carrying
capability of the protected transmission
system element.
123. WECC maintains that the
appropriate use of readily available
technology will completely addresses
the Commission’s concerns. WECC
observes that the relay operations
identified by the Task Force and
referenced by the Commission occurred
mostly with relays that used traditional
mho circle characteristics.120 WECC
explains that the mho relay
characteristic always includes a
substantial resistive reach (in the
direction of load, at least half the
reactive reach) along with the necessary
reactive reach (in the direction of
possible faults). WECC states that in
modern microprocessor-based relays,
several different methods are available
to limit the relays’ resistive (load) reach
without sacrificing the ability to detect
remote faults (reactive reach), including
non-circular characteristic shapes (e.g.,
lens, rectangle), offset mho, blinders,
and specific load encroachment
elements.
124. Many commenters, including
NERC, assert that establishing a shorter
maximum reach for zone 3/zone 2 relays
applied as remote circuit breaker failure
and backup protection may adversely
impact reliability. In general, these
commenters assert that when the level
of backup protection is reduced, there is
an increased probability that faults will
not be cleared and system stability will
suffer.
125. Commenters also stress the
problems associated with setting a
uniform maximum reach. Southern
states that it would be difficult to
establish an arbitrary maximum reach
that fits all system configurations
because the setting for a zone 3/zone 2
relay is based on the location of the
120 ‘‘Mho-circle’’ refers to the circular operating
characteristic of a phase distance protection relay.
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
mstockstill on DSKH9S0YB1PROD with RULES2
relevant relay and the structure of the
protection scheme for the pertinent
system. Duke argues that an arbitrary
relay reach limit would not provide the
necessary protection flexibility to align
protection needs with all primary
system configurations and electrical
characteristics. EEI and ITC argue that it
is not technically possible with current
system configurations to enact the
Commission’s proposal and maintain
reliability and ensure fault detection.
EEI states that the electric industry’s
technically preferred approach is to set
specific fault conditions.
126. The PSEG Companies speculate
that the Commission’s proposal will
translate into a requirement to replace
zone 3 relays with expensive
communication-based schemes. The
PSEG Companies state that such a
requirement would be impractical and
ineffective with respect to facilities
below 200 kV. Nevertheless, the PSEG
Companies support limits on the reach
of zone 3/zone 2 relays for circuits that
are truly critical, provided that the
circuits are identified through an open
process and their designation supported
by a proper engineering analysis by the
Regional Entity.
c. Commission Determination
127. We decline to adopt the NOPR
proposal and will not direct the ERO to
develop a maximum zone 3/zone 2
reach. After further consideration, we
agree with commenters, especially
NERC and EEI, that PRC–023–1, which
interacts with existing FAC, IRO, and
TOP Reliability Standards while
ensuring adequate circuit breaker failure
protection, sufficiently addresses the
Commission’s concern.
128. In its petition, NERC stated that
the interactions between PRC–023–1
and existing FAC, IRO, and TOP
Reliability Standards require entities
and operators to establish limits for all
system elements, operate interconnected
systems within these limits, take
immediate action to mitigate operation
outside these limits, and set protective
relays to refrain from operating until the
observed condition on their protected
element exceeds these limits.121 EEI
maintains that Requirement R1
addresses the Commission’s concern
because no exemption is given to relays
that are set to cover adjacent lines in the
event of breaker failure. EEI contends,
therefore, that PRC–023–1 does not need
to identify any maximum reach
allowable outside of the impact on
loadability. EEI adds that, if remote
back-up relays cannot provide adequate
breaker failure coverage and still
121 NERC
Petition at 15–16.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
comply with PRC–023–1, then local
breaker failure relaying must be applied.
129. We agree with NERC and EEI that
if an entity chooses to use remote
breaker failure protection, it must
comply with PRC–023–1 and its
protection settings, derived pursuant to
PRC–023–1, must interact with other
relevant Reliability Standards to ensure
Reliable Operation. EEI asserts that if
remote backup relays cannot provide
adequate breaker failure coverage and
still comply with PRC–023–1, then local
breaker failure relaying must be applied.
We agree. This assertion addresses our
concern that entities would continue to
rely on the use of remote breaker failure
protection and simply comply with
PRC–023–1 without ensuring whether:
(i) it provides adequate circuit breaker
failure protection coverage; and (ii) that
the limitation of remote circuit breaker
failure protection and the settings so
derived to comply with PRC–023–1 are
reflected in the derivation of IROLs and
SOLs that are used in real time
operations.
2. Protective Relays Operating
Unnecessarily Due to Stable Power
Swings
130. In the NOPR, the Commission
stated that the cascade during the
August 2003 blackout was accelerated
by zone 3/zone 2 relays that operated
because they could not distinguish
between a dynamic, but stable power
swing and an actual fault. The
Commission observed that PRC–023–1
does not address stable power swings,
and pointed out that currently available
protection applications and relays, such
as pilot wire differential, phase
comparison and blinder-blocking
applications and relays, and impedance
relays with non-circular operating
characteristics, are demonstrably less
susceptible to operating unnecessarily
because of stable power swings. Given
the availability of alternatives, the
Commission stated that the use of
protective relay systems that cannot
differentiate between faults and stable
power swings constitutes miscoordination of the protection system
and is inconsistent with entities’
obligations under existing Reliability
Standards. The Commission explained
that a protective relay system that
cannot refrain from operating under
non-fault conditions because of a
technological impediment is unable to
achieve the performance required for
Reliable Operation. Consequently, the
Commission requested comments on
whether it should direct the ERO to
develop a new Reliability Standard or a
modification to PRC–023–1 that requires
the use of protective relay systems that
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
16931
can differentiate between faults and
stable power swings and phases out
protective relay systems that cannot
meet this requirement.122
a. Comments
131. NERC opposes addressing stable
power swings in a modification to PRC–
023–1. NERC argues that while it is
possible to employ protection systems
that are immune from stable power
swings, the Commission should not
require the use of these systems at the
expense of diminishing the ability of
protective relays to dependably trip for
faults or detect unstable power swings.
According to NERC, there are two ways
to prevent protective relays from
operating during stable power swings:
(1) Select a protection system that will
differentiate between faults and stable
power swings, but will not trip for any
power swing, such as current
differential or phase comparison; or (2)
utilize an impedance-based protection
system that relies on careful selection of
the protective relay trip characteristic,
including shape (e.g., mho circle, lens)
and sensitivity, to differentiate between
faults, stable swings, and unstable
swings. NERC adds that selection of the
trip characteristic requires coordination
based on fault coordination and
transient stability studies between the
protection system designer and the
transmission planner.
132. While NERC acknowledges that
PRC–023–1 is designed to address the
steady-state aspects of relay loadability,
it also claims that PRC–023–1 has
positive effects in relation to relays and
stable power swings. Specifically, the
modifications required by PRC–023–1 to
increase steady state loadability
necessarily decrease the likelihood that
relays will trip on stable power swings.
133. NERC cautions that it must
carefully study and analyze the
relationship between stable power
swings and protective relays, and
consult with IEEE and other
organizations before developing a
Reliability Standard addressing stable
power swings. NERC requests that the
Commission allow PRC–023–1 to
remain focused on steady state relay
loadability and leave stable power
swings to be specifically addressed in a
different Reliability Standard.
134. Other commenters agree with the
concerns identified by the Commission.
None, however, think that the
Commission should direct the ERO to
modify PRC–023–1 to address stable
122 NOPR,
E:\FR\FM\02APR2.SGM
FERC Stats. & Regs. ¶ 32,642 at P 60.
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
16932
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
power swings.123 Many commenters
agree with NERC and urge the
Commission to allow the ERO to
address stable power swings in a
different Reliability Standard, after the
ERO has had the opportunity to further
study the issue. EEI and Southern argue
that PRC–023–1 addresses the steadystate aspects of relay loadability, not
transient system conditions such as
stable or unstable power swings. The
PSEG Companies reflect the view of
many commenters when they argue that
issues related to stable power swings are
too complex to be addressed in PRC–
023–1. Dominion adds that if the
Commission did direct the ERO to
address stable power swings in PRC–
023–1, the final implementation of the
Reliability Standard would be
significantly delayed. TAPS argues that
the Commission should give due weight
to NERC’s decision not to address stable
power swings in PRC–023–1. APPA
asserts that the Commission can require
only that the ERO examine the
Commission’s concerns about stable
power swings and cannot direct the
ERO to implement a specific solution.
135. Several commenters challenge
the Commission’s reasoning and
assumptions in the NOPR. Exelon
challenges the Commission’s assertion
that a protective relay system that
cannot refrain from operating under
non-fault conditions because of a
technological impediment is unable to
achieve the performance required for
reliable operation, arguing that it
ignores many years of reliable and stable
operation of mho-circle relays. Exelon
adds that it is unaware of any instance
in the entire history of its ComEd or
PECO operating companies when mhotype distance relays tripped because of
a stable power swing, and that none of
its stability studies have ever identified
lines that would trip on a stable power
swing.
136. ElectriCities, the MDEA Cities,
and the Six California Cities challenge
the Commission’s assertion that the use
of protective relays that cannot
differentiate between faults and stable
power swings is mis-coordination of the
protection system and is inconsistent
with an entity’s obligations under
existing Reliability Standards. In their
view, the Commission should not use
this proceeding to interpret existing
Reliability Standards to require the use
of specific protection technologies and
proscribe the use of others; ElectriCities
asserts that interpreting Reliability
123 See, e.g., EEI; APPA; PG&E; ATC; Ameren;
BPA; Duke; Oncor; and TAPS.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
Standards not at issue may violate the
Administrative Procedure Act.124
137. Consumers Energy disagrees with
the Commission’s assertion that stable
power swings contributed to the cascade
in the August 2003 blackout. Consumers
Energy states that it extensively studied
the events discussed in the NOPR and
concluded that communications-based
relay systems operated because of the
extremely heavy reactive power
consumption of the lines, not stable
power swings. Consumers Energy states
that its studies also show that relay
systems designed to be less susceptible
to stable power swings would still have
operated under these conditions, as the
extreme reactive power consumption
appeared to both terminals of each line
as an internal fault.
138. WECC claims that PRC–023–1
provides indirect, but highly effective
protection against stable power swings.
WECC asserts that the real problem that
occurred during the August 2003
blackout was that zone 3/zone 2 relays
operated and disconnected facilities
because of high loading. WECC argues
that if those zone 3/zone 2 trips had
been prevented, significant system
oscillations would not have occurred
and ‘‘healthy’’ transmission lines would
not have unnecessarily tripped. WECC
asserts that PRC–023–1 is specifically
designed to prevent zone 3/zone 2 trips
due to high loading. EEI argues that
PRC–023–1 is ‘‘well suited’’ to prevent
the unnecessary operation of relays
during stable power swings because as
relay loadability is increased, the proper
response to stable power swings is
enhanced.
139. Several commenters challenge
the Commission’s assumption that
preventing relays from operating due to
stable power swings will improve
reliability. TAPS explains that an
important secondary function of
protective relaying is protecting
equipment and safety in the event of
multiple or extreme contingencies.
TAPS states that the power system is
operated to account for single and
double contingencies, but that extreme
contingencies can occur and overload
facilities to well beyond their
emergency ratings. TAPS contends that
it is impractical to rely on operators to
manually operate the system beyond
single and double contingencies, so
automatic equipment is needed to
protect the system when extreme
contingencies occur. TAPS maintains
that while impedance/distance relays
are susceptible to operating for stable
power swings, they are often the only
protection for facilities loaded beyond
124 5
PO 00000
U.S.C. 551, et seq.
Frm 00020
Fmt 4701
Sfmt 4700
emergency ratings. TAPS argues that the
Commission’s proposal would reduce
reliability because it would expose the
system to longer-term outages due to
equipment damage. TAPS also claims
that overloading due to multiple or
extreme contingencies can create the
same safety issues the Commission
discussed in the NOPR with respect to
sub-requirement R1.10.
140. E.ON argues that the Commission
may have elevated the operational
reliability of the bulk electric system
over public safety and the transmission
asset owner’s interest in ensuring that
its assets remain in working order and
available for service. E.ON explains that
relay settings must ensure the
maintenance of minimum vertical safety
clearances, and that modifying relaying
schemes to accommodate non-fault
related transient overloads might leave
system elements exposed to excessive
loading longer than is prudent. E.ON
further explains that because
transmission facilities are located in
diverse environments, it is appropriate
to maintain a specified vertical line
clearance at the maximum conductor
temperature for which the line is
designed to operate. E.ON states that
what the Commission described as a
‘‘technological impediment’’ may be a
desired design feature intended to
address unique equipment protection
issues or public safety concerns.
141. Exelon asserts that phasing out
step distance relays with mho circle
operating characteristics could leave the
electric system without any reliable
backup for transmission lines with
failed communication or other
equipment failures, thereby exposing
the system to faults that cannot be
cleared and potentially resulting in
larger outages and/or equipment
damage. TAPS adds that the
Commission’s proposal would result in
the loss of zone 3/zone 2 relays as backup protection in the event of a stuck
breaker and/or a failure of a transfer trip
scheme for a stuck breaker.
142. The PSEG Companies speculate
that the post-blackout relay mitigation
programs conducted by NERC may have
already mitigated the unexpected
tripping of the transmission lines during
the August 2003 blackout. The PSEG
Companies add that it is possible that
the only reason the blackout stopped
was because these lines unexpectedly
tripped. The PSEG Companies assert
that the approach to stable power
swings should be all encompassing and
include the development and
implementation of ‘‘islanding’’ strategies
in conjunction with out-of-step blocking
(or tripping) requirements.
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
143. Several commenters dispute the
virtues of the protection schemes
discussed by the Commission in the
NOPR. Ameren states that, in its
experience, many of the applications
identified by the Commission in the
NOPR are less reliable than the step
distance and directional comparison
methods used in distance relays. Duke
casts doubt on manufacturers’ claims
that newer relay technology is able to
differentiate between stable power
swings and out-of-step conditions,
pointing out that much of the newer
technology is essentially the same as
traditional out-of-step relay blocking
schemes with variable timers. Duke also
observes that some new protection
systems still require relays to be set to
operate on high load conditions and
block tripping for a fault during a stable
power swing. EEI states that the
protection schemes cited by the
Commission are prone to mis-operation
due to loss of communication or timing
differences in a transmit-and-receive
communication path. EEI explains that
on September 18, 2007, the protection
schemes identified by the Commission
actually created a major disturbance in
the MRO region due to problems with
communication circuits.125
144. EEI argues that subject matter
experts in the electric industry have
found that the protection schemes cited
by the Commission in the NOPR are
significantly more difficult to install and
maintain than step distance and
directional comparison schemes using
distance relays. EEI states, for example,
that while line differential relays have
been reliable when applied over fiber
communications systems, the necessary
schemes are expensive to install.
Ameren adds that line differential relays
are not as reliable as phase distance
relays, which would still need to be
installed to backup the communications
system. Ameren also states that
installation of fiber optics on existing
transmission lines would require
lengthy construction delays, and
therefore create a reliability risk and
delay compliance with PRC–023–1.
145. EEI and Ameren also point out
the limitations of out-of-step tripping
and power swing blocking. They
explain that in a 2005 report, the IEEE
Power System Relaying Committee
found that out-of-step tripping and
power swing blocking cannot be set
reliably under extreme multicontingency conditions where the
trajectories of power swings are
unpredictable, because they must be set
based on specific system contingencies
and the results of stability simulations.
125 EEI
at 21–22.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
146. Exelon argues that the
technology identified by the
Commission may not be helpful in a
situation like the August 2003 blackout.
Exelon explains that experienced relay
protection engineers can apply the
technology to distinguish between
stable and unstable power swings in the
cases of Category A, B, C and even some
Category D contingencies as detailed in
the TPL Reliability Standards, but that
these are discrete contingencies that can
be simulated with a great deal of
certainty. Exelon states that simulating
the types of swings that occurred during
the August 2003 blackout would involve
many scenarios, occurring in different
possible sequences. Exelon claims that
it is virtually impossible to accurately
predict the exact sequence of events for
major disturbances involving extreme
events, and that without accurate
simulations of the ‘‘right’’ disturbances,
replacing relays would not provide any
benefit.
147. WECC and Tri-State make the
related point that there were at least
fourteen line outages before the stable
swings began in the August 2003
blackout, and that it is unlikely that the
multiple contingency scenarios that
developed would ever have been
studied under the current TPL
Reliability Standards. WECC adds that
even if the TPL Reliability Standards
required prior study and relay
coordination for such extensive outages,
it is entirely plausible that the power
swing blocking settings appropriate for
a system that included 2 or 3
contingencies would not work
appropriately for the same system after
14 or 40 outages.
148. Multiple commenters claim that
the Commission’s proposal would place
an undue and unnecessary financial
hardship on utilities because it would
require significant expenditures and an
exceptional amount of skilled labor
without commensurate benefits. Exelon
argues that any type of a proposed
phase-out would affect a majority of the
relays in North America. With respect to
its PECO and ComEd operating
companies, Exelon estimates that it
would cost PECO approximately $45
million to comply for roughly 180
terminals between 230 kV and 500 kV
($250,000 per terminal) and 33 percent
more if the phase-out applied to 138 kV
lines. As for ComEd, Exelon estimates
that it would cost approximately $65
million to comply for roughly 260
terminals between 345 kV and 765 kV,
and three times more if the phase-out
applied 138 kV lines. Portland General
states that it would cost $6 million to
replace its 40 relays. TAPS points out
that Order No. 672 states that NERC may
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
16933
consider the cost of compliance when
developing a Reliability Standard,
provided that the Standard does not
reflect the ‘‘lowest common
denominator.’’ TAPS argues that PRC–
023–1 does not reflect the ‘‘lowest
common denominator.’’
149. EEI argues that the Commission’s
proposal will require the unreasonable
removal of a large number of
electromechanical relays that effectively
function, and that electric utilities
should replace electromechanical relays
only when necessary. Oncor argues that
is unnecessary to mandate a phase out
because as utilities upgrade their
protection systems on a voluntary basis
they will eliminate relays that cannot
differentiate between faults and stable
power swings. TAPS states that the
Commission’s proposal, in combination
with its proposal to eliminate the
exclusions in Attachment A of PRC–
023–1 (particularly subsection (3.1)),
would require redundant high speed
protective systems for every
transmission line, even when they are
not needed for critical clearing time
purposes. TAPS also argues that
requiring the addition of new protective
relay systems runs up against the
prohibitions in sections 215 (a)(3) and
(i)(2) of the FPA on Reliability
Standards that require the enlargement
of facilities or the addition of generation
or transmission capacity.
b. Commission Determination
150. We will not direct the ERO to
modify PRC–023–1 to address stable
power swings. However, because both
NERC and the Task Force have
identified undesirable relay operation
due to stable power swings as a
reliability issue, we direct the ERO to
develop a Reliability Standard that
requires the use of protective relay
systems that can differentiate between
faults and stable power swings and,
when necessary, phases out protective
relay systems that cannot meet this
requirement. We also direct the ERO to
file a report no later than 120 days of
this Final Rule addressing the issue of
protective relay operation due to power
swings. The report should include an
action plan and timeline that explains
how and when the ERO intends to
address this issue through its Reliability
Standards development process.
151. According to the NERC System
Protection and Control Task Force, it is
a well established principle of
protection that Bulk-Power System
elements, such as generators,
transmission lines, transformers, and DC
transmission or shunt devices, should
not trip inadvertently for expected and
potential non-fault loading conditions,
E:\FR\FM\02APR2.SGM
02APR2
16934
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
mstockstill on DSKH9S0YB1PROD with RULES2
including normal and emergency
loading conditions and stable power
swings.126 Before Congress’ directive in
section 215 of the FPA to establish
mandatory and enforceable Reliability
Standards, this reliability principle was
considered good utility practice and was
documented in the voluntary NERC
Planning Standards as one of the System
and Protection and Control
Transmission Protection Systems
Guides.127 However, the ERO has not
yet proposed to translate this principle
into a mandatory and enforceable
directive by including it in a Reliability
Standard.
152. Additionally, as we explained in
the NOPR, while zone 3/zone 2 relays
operated during the August 2003
blackout according to their settings and
specifications, the inability of these
relays to distinguish between a
dynamic, but stable power swing and an
actual fault contributed to the
cascade.128 The Task Force also
identified dynamic power swings and
the resulting system instability as the
reason why the cascade spread.129 Since
PRC–023–1 does not address relays
operating unnecessarily because of
stable power swings, we are concerned
that relays set according to PRC–023–1
remain susceptible to problems like
those that occurred during the August
2003 blackout.
153. While we recognize that
addressing stable power swings is a
complex issue, we note that more than
six years have passed since the August
2003 blackout and there is still no
Reliability Standard that addresses
relays tripping due to stable power
swings. Additionally, NERC has long
identified undesirable relay operation
due to stable power swings as a
reliability issue. Consequently, pursuant
to section 215(d)(5) of the FPA, we find
that undesirable relay operation due to
stable power swings is a specific matter
that the ERO must address to carry out
the goals of section 215, and we direct
the ERO to develop a Reliability
Standard addressing undesirable relay
operation due to stable power swings.
126 NERC Planning Committee, System Protection
and Control Task Force, ‘‘Relay Loadability
Exceptions—Determination and Application of
Practical Relaying Loadability Ratings,’’ Version 1.2,
at 3 (Aug. 8, 2005).
127 See NERC Planning Standards, Section III:
System and Protection and Control, Part A:
Transmission Protection Systems, G.12 (1997)
(‘‘Generation and transmission protection systems
should avoid tripping for stable power swings on
the interconnected transmission systems.’’). Under
the voluntary planning standards and operating
policies, a ‘‘Guide’’ described good planning
practices and considerations.
128 NOPR, FERC Stats. & Regs. ¶ 32,642 at P 58.
129 See Final Blackout Report at 81–82.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
154. We note that NERC stated in its
petition that PRC–023–1 interacts with
several existing FAC, IRO, and TOP
Reliability Standards, and that these
interactions require limits to be
established for all system elements,
interconnected systems to be operated
within these limits, operators to take
immediate action to mitigate operation
outside of these limits, and protective
relays to refrain from operating until the
observed condition on their protected
element exceeds these limits.130 We
agree, and add that entities must also
validate protection settings set pursuant
to PRC–023–1 through: (1) Using the
settings as an input into the valid
assessments required for compliance
with the TPL Reliability Standards for
contingencies; (2) including the settings
in the derivation of SOLs and IROLs;
and (3) complying with the TOP, IRO,
and FAC Reliability Standards for
Category B contingencies, and for the
subset of multiple contingencies (if any)
identified in TPL–003 that result in
stability limits identified by the
planning authority. These steps will
ensure Reliable Operation until the ERO
develops the new Reliability Standard
addressing unnecessary relay operation
due to stable power swings.
155. Although we do not direct the
ERO to modify PRC–023–1 to address
stable power swings, we disagree with
those commenters who suggest that
relay performance during stable power
swings is outside the scope of relay
loadability. Reliability Standard PRC–
023–1 was developed by industry
experts using well thought-out
guidelines based on static system
conditions. These guidelines apply only
to the situation in which the electric
system after a disturbance has returned
to a steady state condition. This means
that currents and voltages on BulkPower System elements vary with a
large degree of predictability. Under this
scenario, compliance with PRC–023–1
will prevent relays from inadvertently
tripping because of increases in static
loadings; hence, the term ‘‘loadability.’’
156. However, protective relays will
respond to real-time system conditions,
regardless of whether they are set for
static loadings (loadability) or dynamic
loadings, such as stable power swings.
During transient conditions, a protective
relay set assuming steady-state system
conditions will measure the prevailing
voltage and current quantities resulting
from a stable power swing, and if its
trajectory falls within the relay settings
(reach and time delay) so derived from
PRC–023–1, it will operate and
inadvertently trip the healthy Bulk130 NERC
PO 00000
Petition at 15–16.
Frm 00022
Fmt 4701
Sfmt 4700
Power System element it is protecting.
Consequently, the relay may operate for
transient conditions, even if set
pursuant to PRC–023–1. Thus, relay
operation because of stable power
swings is within the scope of relay
loadability and must be considered
when the relay is set to ensure Reliable
Operation.
157. Exelon states that its stability
studies for ComEd and PECO have never
identified lines that would trip on stable
power swings. There are two potential
reasons why not: (1) Exelon’s protection
systems are designed so that it is
unnecessary to establish longer reach
settings for protective relays; or (2) its
electric systems consist primarily of
short transmission lines.
158. Initially, we note that ComEd
and PECO may have historically
adopted a good utility practice in
protection that requires two groups
(both of equivalent high speed) of
redundant and duplicated
communications-based protection
systems for each high voltage line while
relying on the use of local breaker
failure protection.131 If this were the
case, they would not need to set their
relays to overreach by large margins to
provide remote circuit breaker failure
and backup protection because they
designed around the problem. In
addition, the high voltage lines in
ComEd and PECO may be relatively
short. Electric systems comprised of
long transmission lines are more likely
to experience larger stable power swings
than those comprised of short
transmission lines. These two factors—
relative short protection reach in their
Zone 1 and Zone 2 relays due to
application of more sophisticated
protection systems and not relying on
the use of remote breaker failure
protection, as well as, smaller stable
power swings due to shorter
transmission lines—are likely to be the
key reasons why they have never
identified lines that would trip on stable
power swings.
159. We find unpersuasive Consumers
Energy’s claim that heavy reactive
power consumption, not stable power
swings, contributed to the cascade
during the August 2003 blackout. In the
Final Blackout Report, the Task Force
131 See NERC Planning Standards, Section III:
System and Protection and Control, Part A:
Transmission Protection Systems, G.5 (1997)
(‘‘Physical and electrical separation should be
maintained between redundant protection systems,
where practical, to reduce the possibility of both
systems being disabled by a single event or
condition.’’). While this is considered a good utility
practice and used worldwide, it may not have
necessarily been used by other entities in the past
and is currently not required by any Reliability
Standard.
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
addressed this issue and concluded that,
as the cascade progressed beyond Ohio,
it spread due not to insufficient reactive
power and a voltage collapse, but
because of dynamic power swings and
the resulting system instability.132
While extreme reactive power
consumption may have resulted in the
operation of some communicationsbased relays, the Final Blackout Report
confirms that zone 3/zone 2 relays
without communications or an
uncoordinated time delay operated
unnecessarily when they recognized
dynamic, but stable, power swings as a
fault. As the Task Force explained, this
undesirable operation contributed to the
cascade and the spread of the blackout.
160. WECC argues that PRC–023–1
provides indirect protection against
stable power swings because it prevents
relays from tripping due to high loading,
and that this protection could have
prevented the tripping of the zone 3/
zone 2 relays during the blackout and
prevented the oscillations that caused
‘‘healthy’’ transmission lines to
unnecessarily trip. While we agree that
increasing loadability by applying the
settings set forth in PRC–023–1
decreases the likelihood of relays
tripping on load, it does not necessarily
decrease the likelihood of zone 3/zone
2 relays applied as remote circuit
breaker failure and backup protection
tripping on stable power swings and
would not have prevented the trips that
spread the August 2003 blackout. Zone
3/zone 2 relays applied as remote circuit
breaker failure and backup protection
require large protective reach settings.
The protective reach setting is
determined by the apparent impedance
of the system as measured by the relay.
When the apparent impedance as
measured by the relay falls within the
setting of the relay, the relay will
operate after its set time delay. While a
fault typically moves through the
characteristic of a relay reach setting
very fast, the speed at which a power
swing moves through the characteristic
of a relay reach setting is typically much
slower. When a power swing occurs, it
is the time that it takes the power swing
to pass through the characteristic of the
relay’s protective reach setting that
makes the relay susceptible to
operation. As we explained in the
NOPR, the Final Blackout Report found
that several zone 2 relays applied as
remote circuit breaker failure and
backup protection were set to overreach
their protected lines by more than 200
percent without any time delay.133
When the dynamic, yet stable, power
swings occurred prior to system
cascade, these relays operated
unnecessarily.134
161. The PSEG Companies suggest
that NERC’s post-blackout relay
mitigation programs may have
addressed the unexpected tripping of
lines that occurred during the August
2003 blackout, and that it is possible
that the only reason the blackout
stopped was because these lines
unexpectedly tripped. We disagree,
based on two facts documented in the
Final Blackout Report. First, the
unexpected tripping of these lines in
Ohio and Michigan accelerated the
geographic spread of the cascade instead
of stopping it.135 Second, relays on long
lines that are not highly integrated into
the electrical network, such as the
Homer City-Watercure and the Homer
City-Stolle Road 345-kV lines in
Pennsylvania, tripped quickly and split
the grid between the sections that
blacked out and those that recovered
without further propagating the cascade.
We also disagree with the PSEG
Companies’ assertion that NERC’s postblackout relay mitigation programs may
have addressed the unexpected tripping
of lines that occurred during the August
2003 blackout for two main reasons: (i)
The programs did not include on a
general basis sub-200 kV facilities that
are considered as critical or
operationally significant facilities; 136
and (ii) the programs did not explicitly
address inadvertent tripping on nonfaulted facilities due to stable power
swings.
162. The PSEG Companies also assert
that the Commission’s approach to
stable power swings should be inclusive
and include ‘‘islanding’’ strategies in
conjunction with out-of-step blocking or
tripping requirements. We agree with
the PSEG Companies and direct the ERO
to consider ‘‘islanding’’ strategies that
achieve the fundamental performance
for all islands in developing the new
Reliability Standard addressing stable
power swings.
163. We also clarify that our directive
does not in any way involve a tradeoff
between reliability and public safety as
suggested by E.ON’s concerns about the
maintenance of minimum vertical safety
clearances and TAPS’s concerns about
modifying relaying schemes to
accommodate non-fault-related transient
overloads. First, while the maintenance
of minimum vertical safety clearances
for personnel safety consideration is
outside of Commission jurisdiction, the
134 Id.
at 82.
at 80.
136 The Beyond Zone 3 review included sub-200
kV facilities on a limited basis.
135 Id.
132 Final
133 Id.
Blackout Report at 81.
at 80.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
16935
development of line ratings consistent
with FAC–008–1 (Facility Ratings
Methodology) must include the limiting
factors, such as line design, ambient
conditions and system loading
conditions. For these ratings to be valid
there must be adequate clearances
between line conductors and
surrounding objects to prevent flashover
in addition to maintaining adequate
vertical clearance from the ground.
Reliability Standard FAC–003–1
Requirement R1.2.1 also includes a
provision for ‘‘worker approach distance
requirements’’ as part of the minimum
clearances which include vertical safety
clearance. Therefore, we do not see how
our directive would in any way involve
a tradeoff between reliability and safety
as these are addressed separately and
interactively between the relevant
Reliability Standards.
164. Second, we do not see how the
Commission’s goal of avoiding
inadvertent tripping of non-faulted
Bulk-Power System elements due to
stable power swings can be interpreted
as requiring modifying relaying schemes
to accommodate non-fault related
transient overloads, as TAPS claims. In
addition to our explanation above,
NERC stated in its petition, and we
agree, that PRC–023–1 interacts with
existing FAC, IRO, and TOP Reliability
Standards; these interactions require
limits to be established for all system
elements, interconnected systems to be
operated within these limits, operators
to take immediate action to mitigate
operation outside of these limits (i.e.,
overloads), and protective relays to
refrain from operating until the
observed condition on their protected
element exceeds these limits.137 In
addition, each planning authority and
transmission planner is required to
demonstrate through a valid assessment
only that its portion of the
interconnected electric system is
evaluated for the risks and
consequences of such extreme, multicontingency events and for corrective
actions. For these reasons, we also reject
TAPS’s comments that the NOPR
proposal would create safety issues due
to overloading from multiple or extreme
contingencies. If protection systems
already respect safety issues, they will
not be affected by following the
evaluation of these extreme
contingencies.
165. We also disagree with
commenters’ claims that our directive
could harm reliability. Exelon asserts
that phasing out step distance relays
with mho circle operating
characteristics could leave the electric
137 NERC
E:\FR\FM\02APR2.SGM
Petition at 15–16.
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
16980
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
system without any reliable backup for
transmission lines with failed
communication or other equipment
failures, thereby exposing the system to
faults that cannot be cleared and
potentially resulting in larger outages
and/or equipment damage. TAPS adds
that the Commission’s proposal would
result in the loss of zone 3/zone 2 relays
as back-up protection in the event of a
stuck breaker and/or a failure of a
transfer trip scheme for a stuck breaker.
166. Exelon incorrectly interprets our
statement that ‘‘a protective relay system
that cannot refrain from operating under
non-fault conditions because of a
technological impediment is unable to
achieve the performance required for
reliable operation’’ as a proposal for
‘‘leaving the electric system without any
reliable backup for transmission.’’ TAPS’
similar assertion implies the same. We
disagree that the Commission’s proposal
would result in the loss of relays as
back-up protection. Our statement
merely points out the fundamentals
required for Reliable Operation under
currently approved Reliability
Standards. As we state in the previous
discussion, PRC–023–1 interacts with
existing FAC, IRO, and TOP Reliability
Standards to ensure Reliable Operation;
these interactions require limits to be
established for all system elements,
interconnected systems to be operated
within these limits, operators to take
immediate action to mitigate operation
outside of these limits, and protective
relays to refrain from operating until the
observed condition on their protected
element exceeds these limits. Protection
relays include primary and backup
relays. If zone 2/zone 3 relays are used
by entities as part of their protection
systems designed to achieve the system
performance, they can remain as backup
protection as long as they do not
inadvertently trip non-faulted facilities
due to stable power swings.
167. Several commenters dispute the
virtues of the protection schemes
discussed by the Commission in the
NOPR. In general, these commenters
argue that the applications identified by
the Commission in the NOPR are less
reliable than the step distance and
directional comparison methods used in
distance relays. We clarify that the
protection systems discussed in the
NOPR are merely examples of systems
that can differentiate between faults and
stable power swings. We leave it to the
ERO to determine the appropriate
protection systems to be discussed in
the new Reliability Standard through
application of its technical expertise.
168. Some commenters argue that the
technology identified by the
Commission may not be helpful in a
VerDate Nov<24>2008
17:36 Apr 01, 2010
Jkt 220001
situation like the August 2003 blackout
because that event involved so many
contingencies that it would be almost
impossible to simulate and thus
unlikely to be studied under the TPL
Reliability Standards. We realize that
relays cannot be set reliably under
extreme multi-contingency conditions
covered by the Category D contingencies
of the TPL Reliability Standards. In fact,
Reliability Standard TPL–004–0
requires the planning authority and
transmission planner to demonstrate
through a valid assessment that its
portion of the interconnected electric
system is evaluated only for the risks
and consequences of such events; it
does not require corrective actions. We
recognize that, because of the operating
characteristic of the impedance relay,
regardless of whether a power swing is
stable or unstable, the relay may
potentially operate under Category D
contingencies. Thus, the NOPR
proposed alternative protection
applications and relays that are less
susceptible to transient or dynamic
power swings. This is consistent with
Order No. 693, where the Commission
stated that it is not realistic to expect the
ERO to develop Reliability Standards
that anticipate every conceivable critical
operating condition applicable to
unknown future configurations for
regions with various configurations and
operating characteristics.138
169. Some commenters oppose a new
Reliability Standard because they are
concerned that it would require the
removal of a large number of electromechanical relays that are in service
and functioning today. Likewise, other
commenters argue that the cost of
phasing out protection systems that
cannot distinguish between faults and
stable power swings is excessive. While
we appreciate these concerns, they are
not persuasive reasons to reconsider our
decision to direct the ERO to develop a
Reliability Standard addressing
undesirable relay operation due to
stable power swings. In this Final Rule,
we have explained why a relay’s
inability to distinguish between actual
faults and stable power swings is a
specific matter that the ERO must
address in order to carry out the goals
of section 215 of the FPA, in part by
showing how such relays contributed to
the spread of the August 2003 blackout.
The fact that many such relays are in
current use does not mitigate the threat
they pose to Reliable Operation or
change the role they played in spreading
the August 2003 blackout. Moreover,
while we direct the ERO to develop a
Reliability Standard that phases out
such relays where necessary if they do
not meet the reliability goal, the ERO is
free to develop an alternative solution to
our reliability concerns regarding
undesirable relay operation due to
stable power swings, provided that it is
an equally effective and efficient
approach.139
170. Because we direct the ERO to
develop the new Reliability Standard in
this Final Rule, it would be premature
for the Commission to now rule on
issues related to the cost of the new
Standard. In the first place, the
Reliability Standard is not yet written;
the ERO has not yet worked out the
details of a phase-out, or even decided
if it will propose a phase-out or some
other equally effective and efficient
solution to the Commission’s reliability
concerns. It is impossible for the
Commission to evaluate the costs of a
proposal that has not yet been
developed, let alone one that has not
has yet been presented to the
Commission. Entities will have the
opportunity to raise their cost concerns
throughout the Reliability Standards
development process and before the
Commission when NERC submits the
new Reliability Standard for
Commission approval. As a general
matter, however, we repeat our
statement in Order No. 672: Proposed
Reliability Standards must not simply
reflect a compromise in the ERO’s
Reliability Standard development
process based on the least effective
North American practice—the so-called
‘‘lowest-common denominator’’—if such
practice does not adequately protect
Bulk-Power System reliability.140 While
a Reliability Standard may take into
account the size of the entity that must
comply and the costs of
implementation, the ERO should not
propose a ‘‘lowest common
denominator’’ Reliability Standard that
would achieve less than excellence in
operating system reliability solely to
protect against reasonable expenses for
supporting vital national
infrastructure.141 The Commission has
also explained that the Reliability
Standard development process should
consider, at a high level, the potential
costs and other risks to society of a
Bulk-Power System failure if action is
not taken to establish and implement a
new or modified Reliability Standard in
response to previous blackouts and the
139 Id.
P 186.
No. 672, FERC Stats. & Regs. ¶ 31,204
140 Order
138 See Order No. 693, FERC Stats. & Regs. ¶
31,242 at P 1706.
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
at P 329.
141 Id. P 330.
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
economic impacts associated with such
blackouts.142
171. We also disagree with TAPS’s
claim that the Commission’s proposal,
in combination with its proposal to
eliminate the exclusions in Attachment
A of PRC–023–1 (particularly subsection
3.1), would require redundant high
speed protective systems for every
transmission line, even when they are
not needed for critical clearing time
purposes. As we have explained
previously in this Final Rule, the TPL
Reliability Standards require annual
system assessments to determine if the
system meets the desired system
performance requirement established by
the TPL Standards. This assessment
includes the interaction of approved
Reliability Standards such as, PRC, IRO,
and TOP. If an entity is not able to
achieve the desired system performance,
consistent with the TPL Reliability
Standards, corrective action plans must
be developed and implemented. Thus, it
is left to the entity to determine how
best to meet desired system performance
when it develops its corrective action
plans; contrary to TAPS’s argument, our
directives in this Final Rule do not
require entities to adopt redundant high
speed protective systems for every
transmission line as a specific corrective
action plan.
172. Finally, we reject TAPS’s
assertion that requiring entities to use
protection systems that can distinguish
between faults and stable power swings
violates sections 215(a)(3) and (i)(2) of
the FPA, which prohibit the
Commission from requiring in a
Reliability Standard the enlargement of
facilities or the addition of generation or
transmission capacity. Replacing a
protection system that does not ensure
Reliable Operation in this instance is
necessary to achieve the goals of the
statute and does not equate to an
expansion of facilities or the
construction of new generation or
transmission capacity.
173. In sum, we adopt the NOPR
proposal and direct the ERO to develop
a new Reliability Standard that prevents
protective relays from operating
unnecessarily due to stable power
swings by requiring the use of protective
relay systems that can differentiate
between faults and stable power swings
and, when necessary, phases-out relays
that cannot meet this requirement.
NERC requests that the Commission
allow PRC–023–1 to remain focused on
steady state relay loadability and leave
stable power swings to be specifically
addressed in a different Reliability
142 ERO
Rehearing Order, 117 FERC ¶ 61,126 at
P 97.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
Standard. We agree that this is a
reasonable approach. Meanwhile, to
maintain reliability, the Commission
expects entities to continue to include
the effects of protection settings in TPL
and TOP assessments for future systems
and in the determination of IROLs and
SOLs.143
F. Requirement R1
174. Requirement R1 directs each
subject entity to set its relays according
to one of the criteria prescribed in subrequirements R1.1 through R1.13. In the
NOPR, the Commission expressed
concerns about the implementation of
three of these criteria: sub-requirements
R1.2, R1.10, and R1.12. In its comments,
Palo Alto raised concerns about subrequirement R1.1.
1. Sub-Requirement R1.1
175. Sub-requirement R1.1 specifies
transmission line relay settings based on
the highest seasonal facility rating using
the 4-hour thermal rating of a
transmission line, plus a design margin
of 150 percent.
a. Comments
176. Palo Alto states that, in the
interest of maximum reliability, many
municipal utilities install lines and
transformers rated to handle the worstcase emergency load, i.e., the load
resulting from the failure of an adjacent
line or transformer. Palo Alto explains
that load-sensitive overcurrent relays
are typically set between 115 and 125
percent of the highest line or equipment
rating, and argues that changing these
settings to comply with sub-requirement
R1.1 will result in longer fault clearing
times and unnecessarily compromise
line and transformer protection. Palo
Alto adds that longer fault clearing
times could result in increased arc flash
exposure. Palo Alto recommends that
the Commission direct NERC to revise
sub-requirement R1.1 to state that
transmission relays can be set to not
operate at or below 150 percent of the
transmission line/transformer rating
instead of the highest seasonal facility
rating of a circuit, or at 120 percent of
the maximum expected emergency load
on the transmission line or transformer.
143 Requirement R1.3.10 of Reliability Standard
TPL–002–0 requires that a valid assessment shall
include, among other things, the effects of existing
and planned protection systems. Requirement R6 of
Reliability Standard TOP–002–0 requires that, as a
minimum criterion, the bulk electric system is
planned and operated to maintain reliable operation
for the single contingency loss of any transmission
facility. In Order No. 693, the Commission
explained that ‘‘[i]n deriving SOLs and IROLs,
moreover, the functions, settings, and limitations of
protection systems are recognized and integrated.’’
Order No. 693, FERC Stats. & Regs. ¶ 31,242 at P
1435.
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
16937
b. Commission Determination
177. Palo Alto identifies a technical
disagreement with sub-requirement
R1.1. We expect such technical
disagreements to be resolved either in
the Reliability Standards development
process or by the disagreeing entity
requesting an exception from NERC.
Moreover, giving ‘‘due weight’’ to the
technical expertise of the ERO, we find
no reason to direct a change to subrequirement R1.1.
2. Sub-Requirement R1.2
178. Sub-requirement R1.2 requires
relays to be set not to operate at or
below 115 percent of the highest
seasonal 15-minute facility rating of a
circuit. A footnote attached to subrequirement R1.2 provides that ‘‘[w]hen
a 15-minute rating has been calculated
and published for use in real-time
operations, the 15-minute rating can be
used to establish the loadability
requirement for the protective relays.’’
a. NOPR Proposal
179. In the NOPR, the Commission
expressed concern that sub-requirement
R1.2 might conflict with Requirement
R4 of existing Reliability Standard TOP–
004–1 (Transmission Operations),
which states that ‘‘if a transmission
operator enters an unknown operating
state, it will be considered to be in an
emergency and shall restore operations
to respect proven reliability power
system limits within 30 minutes.’’ 144
The Commission explained that the
transmission operator (or any other
reliability entity affected by the facility)
might conclude that it has 30 minutes
to restore the system to normal when in
fact it has only 15 minutes because the
relay settings for certain transmission
facilities have been set to operate at the
15-minute rating in accordance with
sub-requirement R1.2. In order to avoid
confusion and protect reliability, the
Commission proposed to direct the ERO
to revise sub-requirement R1.2 to give
transmission operators the same amount
of time as in Reliability Standard TOP–
004–1; develop a new requirement that
transmission owners, generation
owners, and distribution providers give
their transmission operators a list of
transmission facilities that implement
sub-requirement R1.2; or propose an
equally effective and efficient way to
avoid the potential conflict.
b. Comments
180. NERC urges the Commission to
adopt sub-requirement R1.2 without
directing a change. NERC states that the
144 See Reliability Standard TOP–004–1,
Requirement R4.
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
16938
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
purpose of the footnote is to inform the
user that, if it decides to implement subrequirement R1.2, it must have a
procedure that operators implement and
follow. NERC states that some system
operators use a 15-minute rating during
system contingencies, which is a more
stringent requirement than that
established in TOP–004–1. NERC also
claims that use of the 15-minute rating
to establish loadability reflects a
commitment on the part of the entity to
operate to the 15-minute rating and to
respond to rating violations within the
15 minutes because the entity can use
the 15-minute rating only if it has
calculated and published it for use in
real-time operations.145
181. Oncor states that the
Commission’s concerns seem reasonable
and that a simple solution to the conflict
would be to provide system operators
with a copy of those lines that have a
15-minute rating along with the 30minute rating of transmission lines as
described in TOP–004–1.146 IESO and
Hydro One argue that if the Commission
acts on its proposal, creating a new
requirement is the preferred approach in
order to avoid having a requirement
specified in one Reliability Standard
actually applying to another Standard.
182. Some commenters maintain that
entities that use the 15-minute rating are
fully capable of operating within this
constraint. Duke explains that
transmission operators are trained to
operate the system within the ratings
established and communicated to them
pursuant to FAC–009–1, and adds that
reliability coordinators, planning
authorities, transmission planners, and
transmission operators already receive
these ratings pursuant to Requirements
R1 and R2 of FAC–009–1. Southern
states that general industry practice,
which is reflected in Reliability
Standard TOP–004–1, is to return the
electric system to a normal and reliable
state in less than 30 minutes.
183. Several commenters challenge
the Commission’s claim that there is a
conflict between PRC–023–1 and TOP–
004–1 and that transmission operators
might conclude that they have 30
minutes to restore the system to normal
when in fact they have only 15 minutes
because the relay settings for certain
transmission facilities have been set to
operate at the highest seasonal 15minute rating in accordance with subrequirement R1.2. As an initial matter,
Dominion points out that the
Commission’s statement
mischaracterizes sub-requirement R1.2;
rather than allow for relays to operate at
145 NERC
146 Oncor
Comments at 28.
at 5.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
the 15-minute rating, sub-requirement
R1.2 specifies that relays must be set so
that they do not operate at or below 115
percent of the 15- minute rating. APPA,
Ameren, BPA, Dominion, EEI, and
WECC further explain that subrequirement R1.2 does not establish a
time limit before relays trip; instead, it
specifies the level of loading used to
develop the relay’s setting. In other
words, according to these commenters,
the 15-minute rating does not mean that
the relays will trip after 15 minutes.
APPA clarifies that 15 minutes is the
time that the facility ratings
methodology has determined the line
can safely be loaded at that level. BPA,
Dominion, EEI, and WECC explain that
relays set according to sub-requirement
R1.2 will not trip until loading exceeds
115 percent of the 15-minute rating,
which will always be higher than the
30-minute rating. EEI and Ameren
acknowledge that using 115 percent of
the highest seasonal 15-minute rating
creates more conservative relay load
limits, but point out that this does not
limit the operator’s response time to 15
minutes.
184. TAPS and Dominion contend
that the time periods identified in subrequirement R1.2 and TOP–004–1 refer
to two distinct operating situations.
TAPS and Dominion state that the 15minute rating referenced in subrequirement R1.2 refers to the time to
respond to a contingency in a known
state (i.e., within the emergency rating),
while the 30-minute period in TOP–
004–1 refers to the time to respond to
an unknown state (i.e., in a situation
where the operating limits are
unknown, typically a state that has not
been studied in stability studies to
identify stability limits).
185. Duke, EEI, and the PSEG
Companies challenge what they
perceive to be the Commission’s
assumption that sub-requirement R1.2 is
for overload protection. They state that
overcurrent relays are designed and
applied for fault protection and not for
overload protection. EEI adds that the
Commission should recognize that subrequirement R1.11 is the requirement
addressing overload protection. The
PSEG Companies assert that it is widely
recognized by industry that the purpose
of PRC–023–1 is to ensure that lines
refrain from tripping for maximum
loading conditions; once the maximum
loading conditions are exceeded the
relays are free to operate for a fault.
c. Commission Determination
186. We decline to adopt the NOPR
proposal to require the ERO to revise
sub-requirement R1.2 to mirror
Reliability Standard TOP–004–1.
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
However, we will adopt the NOPR
proposal to direct the ERO to modify
PRC–023–1 to require that transmission
owners, generator owners, and
distribution providers give their
transmission operators a list of
transmission facilities that implement
sub-requirement R1.2. We agree with
Oncor that this is a simple approach to
addressing the potential for confusion
identified by the Commission in the
NOPR. Consistent with Order No. 693,
we do not prescribe this specific change
as an exclusive solution to our concerns
regarding sub-requirement R1.2. As the
Commission stated in Order No. 693,
where, as here, ‘‘the Final Rule identifies
a concern and offers a specific approach
to address the concern, we will consider
an equivalent alternative approach
provided that the ERO demonstrates
that the alternative will address the
Commission’s underlying concern or
goal as efficiently and effectively as the
Commission’s proposal.’’ 147 As
discussed in the NOPR, the Commission
is concerned that the transmission
operator (or any other reliability entity
affected by the facility) might conclude
that it has 30 minutes to restore the
system to normal when in fact they may
have less than 30 minutes because the
relay settings applied to protect certain
transmission facilities may have been
set to operate applying a 15-minute
rating in accordance with subrequirement R1.2.
187. Contrary to some commenters’
assertions, the Commission has not
misunderstood the purpose of the 15minute rating and the relay set points in
sub-requirement R1.2. We realize that
the 15-minute and 4-hour ratings are the
times that the entity’s rating
methodology has determined that a
facility can safely be loaded at that level
and does not correlate to the operating
time of the protective relay. We also
realize that the protective relays on
these facilities should not operate until
loading on the facility exceeds the
protective relay settings, including
impedance or current settings and time
delays. Moreover, we understand that
sub-requirement R1.2 is not for overload
protection, and we agree that entities
that use the 15-minute rating are
expected to be capable of operating
within this constraint. Our goal with
directing a modification to subrequirement R1.2 is simply to ensure
that the transmission operator has full
knowledge of which facilities are
applying a 15-minute rating instead of a
4-hour rating so that the transmission
147 Order No. 693, FERC Stats. & Regs. ¶ 31,242
at P 186.
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
mstockstill on DSKH9S0YB1PROD with RULES2
operator can factor this information into
any necessary emergency actions.
188. We also agree with TAPS and
Dominion that the 15 minutes referred
to in sub-requirement R1.2 is for
operating to a known 15-minute limit
and therefore serves a purpose different
from the 30 minutes allowed in TOP–
004–1 for operators in an unknown
operating state that must return to a
known operating state. However, once
the relay settings of a facility that
implements sub-requirement R1.2 go
above 115 percent of the facility’s 15minute rating, the facility may trip and
add to the outages that the transmission
operator must address. Simply put, the
Commission is directing this
modification so that the requirement
includes what Duke and others said
they expect would be necessary for the
operator to have sufficient information
to reliably operate the system—
knowledge of which facilities
implement PRC–023–1 criteria applying
a 15-minute rating so that the operator
can utilize the system for the 15 minutes
that the rating allows. Therefore, the
Commission agrees that, while the time
periods identified in PRC–023–1 and
TOP–004–1 are for different purposes,
the operator’s response time for both
and the consequences of inaction are
effectively the same.
189. Mandatory Reliability Standards
should be clear and unambiguous
regarding what is required and who is
required to comply.148 This is not the
case with sub-requirement R1.2. For
example, the ERO states in its comments
that entities that implement subrequirement R1.2 commit to operate to
the 15-minute rating and to respond to
rating violations within the 15
minutes.149 While we agree with the
ERO, EEI and Ameren do not interpret
sub-requirement R1.2 to limit the
operator’s response time to 15 minutes.
Because there are different
understandings with regard to the
implementation of sub-requirement
R1.2, we adopt the NOPR proposal and
direct the ERO to develop a new
requirement that transmission owners,
generator owners, and distribution
providers give their transmission
operators a list of transmission facilities
that implement sub-requirement R1.2.
3. Sub-Requirement R1.10
190. Sub-requirement R1.10 provides
criteria for transformer fault relays and
transmission line relays on transmission
lines that terminate in a transformer. It
requires that relays be set so that the
148 Order No. 672, FERC Stats. & Regs. ¶ 31,204
at P 325.
149 NERC Comments at 28.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
transformer fault relays and
transmission line relays do not operate
at or below the greater of 150 percent of
the applicable maximum transformer
name-plate rating (expressed in
amperes), including the forced cooled
ratings corresponding to all installed
supplemental cooling equipment, or 115
percent of the highest owner-established
emergency transformer rating.
a. NOPR Proposal
191. In the NOPR, the Commission
expressed concern that overloading
facilities at any time, but especially
during system faults, could lower
reliability and present a safety concern.
The Commission explained that the
application of a transmission line
terminated in a transformer enables the
transmission owner to avoid installing a
bus and local circuit breaker on both
sides of the transformer. The
Commission stated that, for this
topology, protective relay settings
implemented according to subrequirement R1.10 would allow the
transformer to be subjected to overloads
higher than its established ratings for
unspecified periods of time. The
Commission stated that this negatively
impacts reliability and raises safety
concerns because transformers that have
been subjected to currents over their
maximum rating have been recorded as
failing violently, resulting in substantial
fires. The Commission acknowledged
that safety considerations are outside of
its jurisdiction, but asserted that
requirements in a Reliability Standard
should not be interpreted as requiring
unsafe actions or designs. The
Commission proposed, therefore, to
direct the ERO to submit a modification
that requires any entity that implements
sub-requirement R1.10 to either verify
that the limiting piece of equipment is
capable of sustaining the anticipated
overload current for the longest clearing
time associated with the fault from the
facility owner or alter its protection
system or topology.
b. Comments
192. NERC states that the primary
source of technical information for subrequirement R1.10 is IEEE Standard
C37.91–2008, IEEE Guide for Protecting
Power Transformers (specifically,
sections 8.6 and 8.6.1 and Appendix
A).150 NERC explains that phase
150 NERC explains that sections 8.6 and 8.6.1 of
the Guide address the settings of transformer phase
overcurrent protection, and Appendix A contains
through-fault duration curves for various size power
transformers that provide fault current durations as
plotted against transformer base current. Section 8.6
states:
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
16939
overcurrent devices must coordinate
with duration curves, and that
minimum current stated on the curves
must equal two times transformer base
current. NERC argues that PRC–023–1 is
consistent with IEEE Standard C37.91–
2008 and IEEE Standard C57.109–1993
(which is referenced in Appendix A of
IEEE Standard C37.91–2008) because it
requires entities that use overcurrent
relays to consider loadability (a nonfault induced transformer loading), and
because a setting of 150 percent of the
transformer nameplate rating or 115
percent of the highest operatorestablished emergency rating will
always be less than 200 percent of the
transformer forced-cooled nameplate
rating.151
193. TAPS describes the
Commission’s assertion that a
‘‘Reliability Standard should not be
interpreted as requiring unsafe actions
or designs’’ as a ‘‘jurisdictional
bootstrap’’ that nevertheless fails to
remove questions about the
Commission’s authority to require a
modification that addresses safety
concerns. TAPS explains that section
215(i)(2) of the FPA provides that states
retain jurisdiction over safety concerns,
8.6. Protection of a transformer against damage
due to the failure to clear an external fault should
always be carefully considered. This damage
usually manifests itself as internal, thermal, or
mechanical damage caused by fault current flowing
through the transformer. The curves in Annex A
show through-fault-current duration curves to limit
damage to the transformer. Through-faults that can
cause damage to the transformer include restricted
faults or those some distance away from the station.
The fault current, in terms of the transformer rating,
tends to be low (approximately 0.5 to 5.0 times
transformer rating) and the bus voltage tends to
remain at relatively high values. The fault current
will be superimposed on load current,
compounding the thermal load on the transformer.
Several factors will influence the decision as to how
much and what kind of backup is required for the
transformer under consideration. Significant factors
are the operating experience with regard to clearing
remote faults, the cost effectiveness to provide this
coverage considering the size and location of the
transformer, and the general protection
philosophies used by the utility.
Section 8.6.1 states
8.6.1. When overcurrent relays are used for
transformer backup, their sensitivity is limited
because they should be set above maximum load
current. Separate ground relays may be applied
with the phase relays to provide better sensitivity
for some ground faults. Usual considerations for
setting overcurrent relays are described in 8.3.
When overcurrent relays are applied to the highvoltage side of transformers with three or more
windings, they should have pickup values that will
permit the transformer to carry its rated load plus
margin for overload. * * * When two or more
transformers are operated in parallel to share a
common load, the overcurrent relay settings should
consider the short-time overloads on one
transformer upon loss of the other transformer.
Relays on individual transformers may require
pickup levels greater than twice the forced cooled
rating of the transformer to avoid tripping.
151 NERC Comments at 30.
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
16940
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
a point that the Commission
acknowledged in the NOPR.
194. Several commenters point out
that protective relays are designed to
protect the system from faults, not
overloads.152 Ameren, EEI, and Duke
observe that other protection methods,
such as temperature monitors, are
typically employed for thermal
protection. WECC observes that subrequirement R1.11 addresses overload
protection. EEI adds that there is no
loadability issue if a remote breaker can
provide adequate protection and the
asset owner can still comply with PRC–
023–1.
195. Consumers Energy, EEI, and
NERC argue that the mitigation of
thermal overloads is best left to operator
response, not to automatic devices, so
that the operator may take wellreasoned action that best supports the
Reliable Operation of the bulk electric
system while addressing the overload.
Consumers Energy argues that any
entity that wishes to establish automatic
actions for overload conditions should
apply devices designed specifically for
that purpose, with response times
appropriate for overload, or should
develop and install a special protection
system in accordance PRC–012–0 to
detect and take actions to relieve the
overload. EEI maintains that any
transformer requiring overload
protection should have it specifically
applied regardless of transmission line
protection, or system configuration.
Ameren and EEI contend that providing
adequate transformer protection is in
the best interest of the asset owner. The
PSEG Companies argue that the
Commission’s proposal is beyond the
scope of PRC–023–1 because it is
responsibility of the protection system
designer to employ good engineering
practice to ensure protection for faulted
systems. Similarly, the PSEG Companies
argue that system operations groups are
responsible for ensuring that equipment
is properly protected and loaded within
limits.
196. NERC states that overcurrent
relays are typically used only for backup
detection of through-faults outside of
the primary protective zone. NERC
maintains that a transformer subjected
to a through-fault for an extended
period of time may compromise its
design, but that if an entity wishes to
provide overload protection for its
transformer, such protection should be
provided by devices designed for that
purpose and have response times
appropriate for overload protection (e.g.,
several seconds and longer). BPA makes
152 See, e.g., Ameren, BPA, Duke, EEI, Exelon,
NERC, and WECC.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
the similar claim that the overload
current capability required by PRC–
023–1 for transformers is not a safety
concern for moderate time durations.
BPA explains that these setting levels
(or higher) have been common in the
industry to prevent relay operation on
load. BPA acknowledges that, over
prolonged periods, these overload
currents could cause overheating which
could reduce the life of the transformer.
BPA states, however, that protective
relays are not intended to protect for
these currents because ample time is
available for system operators to make
system changes to mitigate the
transformer overload in a controlled
manner, which is preferable to
automatic relay operation. BPA adds
that there are other protective relays to
protect the transformer from internal
faults or large through-currents due to
faults outside of the transformer.
197. Several commenters argue that
the Commission’s proposal is
unnecessary. EEI argues that the
Commission’s proposal is unnecessary
because zone 2 time-delayed relays are
typically set to operate in less than one
second, while IEEE Standard C57.109–
1993 establishes the thermal damage
curve for transformers above 30 MVA
and allows 25 times rated transformer
current for two seconds. EEI also states
that all transformers have an overload
capability that has been covered by
system dispatcher action regardless of
its connection method. EEI points out
that sub-requirement R1.10 requires
load responsive transformer relays to be
set to carry at least 150 percent of the
transformer nameplate rating, and that
system dispatcher response time is
based on the degree of overload, not the
connection method. EEI states that subrequirement R1.10 allows conservative
line protection, which improves the
setting at which relays can be set to
sense fault conditions. Duke adds that
facility ratings, including transformer
facility ratings, are established and
communicated to reliability
coordinators, planning authorities,
transmission planners, and transmission
operators in accordance with FAC–009–
1, Requirements R1 and R2, and that
each transmission operator is trained to
operate the system within the ratings
that are established and communicated
to it pursuant to FAC–009–1.
198. Exelon claims that the
Commission’s description of subrequirement R1.10 is inaccurate. Exelon
maintains that sub-requirement R1.10
will not allow transformers to be
subjected to overloads higher than their
ratings for unspecified periods. Exelon
claims that sub-requirement R1.10
addresses fault protection for lines
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
terminated with a transformer—not
transformer loading. Exelon states that
the protection systems that protect
against faults are different from the
protection systems that protect against
overloads.
199. Exelon claims, moreover, that the
Commission’s proposed modification is
imprecise. Exelon explains that the term
‘‘the longest clearing time associated
with the fault from the facility owner’’
leaves open the question of what
assumptions should be used. For
example, Exelon states that it is unclear
whether the time period to be measured
is based on normal backup clearing time
or some other interval. Exelon contends
that without such precision, compliance
with any modified requirement will be
impossible.
200. Basin agrees that the Commission
has a valid concern when it comes to
establishing overload limits without
regard to whether the limiting piece of
equipment is capable of sustaining the
overload for the longest clearing time
associated with the fault. Basin argues,
however, that the Commission’s mixture
of terminologies in the NOPR (e.g.,
thermal ratings, fault current, load
current and faults) is misleading in
terms of cause and effect and risk
management. Basin requests, therefore,
that the Commission direct NERC to
make the change using language that is
clear and consistent.
201. Basin argues, however, that the
Commission should not impose any
additional requirements on lines
terminating in transformers. Basin
explains that while this equipment is
susceptible to damage from overloads,
other equipment also is subject to
overload-related damage and the
Commission should not address this
issue on a piecemeal basis. Basin
contends that the safety issue related to
lines terminating in transformers merits
unique consideration and is outside the
scope of this proceeding. Basin argues,
therefore, that the Commission should
not direct any specific actions with
respect to such equipment in this
docket.
202. Tri-State agrees with the
Commission that it is prudent to ensure
that relays operate before the
appropriate transformer damage curve is
intersected. Tri-State adds that it finds
little difference in the proposed
allowable current sensing settings used
in sub-requirements R1.10 and R1.11
except for the use of the term ‘‘fault
protection’’ in sub-requirement R1.10
and ‘‘overload protection’’ in subrequirement R1.11.
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
c. Commission Determination
203. We adopt the NOPR proposal
and direct the ERO to modify subrequirement R1.10 so that it requires
entities to verify that the limiting piece
of equipment is capable of sustaining
the anticipated overload for the longest
clearing time associated with the
fault.153 As with our other directives in
this Final Rule, we do not prescribe this
specific change as an exclusive solution
to our reliability concerns regarding
sub-requirement R1.10. As we have
stated, the ERO can propose an
alternative solution that it believes is an
equally effective and efficient approach
to addressing the Commission’s concern
that entities respect facility limits when
implementing sub-requirement R1.10.
204. At the outset, we acknowledge
that section 215 of the FPA does not
authorize the Commission to set and
enforce compliance with standards for
the safety of electric facilities or
services.154 While the NOPR identified
a potential safety issue with subrequirement R1.10, we clarify that we
do not rest our decision to adopt the
NOPR proposal on safety concerns and
reject TAPS’s contrary assertion.
205. We also clarify that the
Commission’s use of the term ‘‘overload’’
in the NOPR refers to the combination
of load and fault current external to the
transformer zone of protection (throughcurrent) that can flow through the
transformer. These overload currents
can be higher than the transformer’s
established ratings, subjecting the
transformer to possible thermal damage.
As discussed in the NOPR, and as NERC
and Basin confirm, subjecting
transformers to overloads over their
maximum rating compromises their
design and subjects the transformer to
overload-related damage. Thus, we
reject Exelon’s assertion that subrequirement R1.10 will not allow
transformers to be subjected to throughcurrents that would overload the
transformer.
206. Since sub-requirement R1.10
applies to the topology where there is
no breaker installed on the high-voltage
side of the transformer, faults within the
transformer or at the low-voltage side of
the transformer are cleared by tripping
the remote breaker on the transmission
line and the transformer low-voltage
breaker. Because faults on the lowvoltage side of the transformer will
generally be lower in magnitude as
measured at the remote breaker due to
the large impedance of the transformer,
fault protection relays set at 150 percent
153 Order No. 693, FERC Stats. & Regs. ¶ 31,242
at P 186.
154 16 U.S.C. 824o(i)(2).
VerDate Nov<24>2008
17:36 Apr 01, 2010
Jkt 220001
of the transformer nameplate rating or
115 percent of the highest operator
established emergency transformer
rating may be set too high to operate for
faults on the low-voltage side of the
transformer. Consequently, delayed
clearing of faults (i.e., the longest
clearing time associated with the faults)
from the high-voltage side of the
transformer may occur and subject the
transformer to overloads, i.e., throughcurrents higher than the transformer’s
rating. Overcurrent relays used for
transformer protection have a limited
ability to detect these types of faults
because they are set above the
maximum load current 155 for entities
that set these relays following the IEEE
Standards. It is for this reason that the
ability of the transformer to sustain
overloads, i.e., through-currents, for the
longest clearing time associated with the
fault must be verified.
207. NERC and others state that subrequirement R1.10 is consistent with
IEEE Standards C37.91–2008 and
C57.109–1993. While the Commission
has approved Reliability Standards that
reference other industry standards,156
Reliability Standard PRC–023–1 does
not reference either IEEE Standard.
Thus, neither IEEE Standard is
mandatory and enforceable under
section 215 of the FPA.
208. Moreover, we have several
concerns about relying on the IEEE
Standards to address the reliability issue
we have identified. First, an entity
could provide a facility rating that was
just within the voluntary requirements
in the IEEE Standards, however, when
setting protection relays according to
sub-requirement R1.10, the transformer
could be subject to currents above its
capability as previously described.
Second, the IEEE Standards may not
apply to transformers manufactured
before 1993 because the guidelines
established in C57.109–1993 do not
apply to transformers manufactured
before 1993.
209. We are not persuaded by the
ERO’s statement that ‘‘a setting of 150
percent of the transformer nameplate
rating or 115 percent of the highest
operator established emergency rating
will always be less than 200 percent of
the transformer forced-cooled nameplate
rating.’’ Referring to section 8.6.1 of IEEE
Standard C37.91, we point out that this
155 Section 8.6.1 of IEEE Standard C37.91–2008
states that ‘‘[w]hen overcurrent relays are used for
transformer backup, their sensitivity is limited
because they should be set above maximum load
current.’’
156 E.g., Reliability Standard FAC–003–1,
Transmission Vegetation Management Program,
Footnote 1 (reference to ANSI A300, Tree Care
Operations).
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
16985
statement applies only to the specific
configuration where ‘‘two or more
transformers are operated in parallel to
share a common load,’’ which may not
be the configuration for every
transformer on the Bulk-Power System.
We also note that section 8.6.1 further
states that ‘‘[r]elays on individual
transformers may require pickup levels
greater than twice the force cooled
rating of the transformer to avoid
tripping.’’ Since Requirement R1.10
applies to any topology, it must be
robust enough to address the reliability
issues of any topology. Section 8.6.1 of
IEEE Standard C37.91 applies only to
two or more transformers that are
operated in parallel. Consequently, we
reject NERC’s assertion that it is not
possible to exceed the rating of a single
transformer.
210. Adopting the NOPR proposal to
require entities that implement subrequirement R1.10 to verify that the
limiting piece of equipment is capable
of sustaining the anticipated overload
current for the longest clearing time
associated with the fault would address
the Commission’s reliability concerns.
Applying protection systems that do not
respect the actual or verified capability
of the limiting facility will result in a
degradation of system reliability. In this
instance, applying sub-requirement
R1.10 without regard to the topology
and capability of each transformer could
cause the transformer to fail. Failure of
the transformer may not be limited to
only the affected transformer, but may
also affect other Bulk-Power Systems
elements in its vicinity, further
degrading the reliability of the BulkPower System.
211. While NERC explains that subrequirement R1.10 is intended for
specific transformer fault protection
relays that are set to protect for fault
conditions and not excessive load
conditions, sub-requirement R1.10 does
not identify that intent.157 Additionally,
sub-requirement R1.11 of PRC–023–1
establishes criteria for transformer
overload protection relays that do not
comply with sub-requirement R1.10.
Because sub-requirement R1.11
establishes that the protection must
allow an overload for 15 minutes, we
disagree with WECC that subrequirement R1.11 addresses the
Commission’s reliability concern with
overloads.
212. We acknowledge that relays can
be set to protect for faults as well as
overloads and that the operation of
relays for fault conditions is much faster
than for overload conditions. This is
because faults need to be removed
157 NERC
E:\FR\FM\02APR2.SGM
Petition at 11.
02APR2
16942
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
quickly from the Bulk-Power System to
limit the severity and spread of system
disturbances and prevent possible
damage to protected elements, while
overload relays are designed to operate
more slowly, and when applicable,
allow time for operators to implement
operator control actions to mitigate the
overloaded facility. Nevertheless, both
fault and overload relays are loadresponsive relays. Thus, we agree with
those commenters that state that manual
mitigation of thermal overloads is best
left to system operators, who can take
appropriate actions to support Reliable
Operation of the Bulk-Power System.
Moreover, because both types of relays
are load-responsive relays, we disagree
with PSEG that the Commission’s
proposal is beyond the scope of PRC–
023–1.
mstockstill on DSKH9S0YB1PROD with RULES2
4. Sub-Requirement R1.12
213. Sub-requirement R1.12
establishes relay loadability criteria
when the desired transmission line
capability is limited by the requirement
to adequately protect the transmission
line. In these cases, the line distance
relays are still required to provide
adequate protection, but the
implemented relay settings will limit
the desired loading capability of the
circuit. In its petition, NERC stated that
if an essential fault protection imposes
a more constraining limit on the system,
the limit imposed by the fault protection
is reflected within the facility rating.158
NERC also stated that PRC–023–1
should cause no undue negative effect
on competition or restrict the grid
beyond what is necessary for
reliability.159
a. NOPR Proposal
214. In the NOPR, the Commission
expressed concern that sub-requirement
R1.12 allows entities to technically
comply with the Reliability Standard
without achieving its stated purpose.
The Commission explained that because
entities can set their relays to limit the
load carrying capability of a
transmission line, any line with relays
set according to sub-requirement R1.12
will not be utilized to its full potential
in response to sudden increases in line
loadings or power swings. The
Commission stated this will make the
natural response of the Bulk-Power
System less robust in the case of system
disturbances. The Commission added
that an entity that uses a protection
system that requires it to set its relays
pursuant to sub-requirement R1.12 may
not be able to satisfy its reliability
158 Id.
at 14.
159 Id. at 27.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
obligations. Consequently, the
Commission requested comments on
whether the use of such a protection
system is consistent with the Reliability
Standard’s objectives, and whether it
should direct a modification that would
require entities that employ such a
protection system to use a different
system.
b. Comments
215. NERC opposes the Commission’s
proposal and disagrees with the
Commission’s assertion that subrequirement R1.12 allows entities to
comply with the Reliability Standard
without achieving its purpose. NERC
states that the Reliability Standard’s
objectives include ensuring reliable
detection of all network faults and
preventing undesired protective relay
operation that interferes with the system
operator’s ability to take remedial
action. NERC explains that use of subrequirement R1.12 is restricted to cases
where adequate line protection cannot
be achieved without restricting the
loadability of the protected transmission
element.
216. NERC and Consumers Energy
argue that sub-requirement R1.12 could
have helped mitigate the August 2003
blackout. NERC and Consumers Energy
explain that many of the lines that
tripped during the blackout were below
their emergency rating and tripped
because of loading limitations imposed
by relay settings. NERC and Consumers
Energy state that these lines tripped
without warning to system operators,
who were unaware of loading
limitations imposed by relay settings.
NERC and Consumers Energy note that
sub-requirement R1.12 mandates that
facility ratings reflect relay loadability
limitations and speculate that, if this
had been the case on the day of the
blackout, system operators would have
known that they were approaching the
relay loadability limitation and could
have taken mitigating action.160
217. Other commenters share NERC’s
view that sub-requirement R1.12 is
consistent with the Reliability
Standard’s purpose.161 Ameren argues
that sub-requirement R1.12
appropriately recognizes that priority
must be given to fault detection over
loadability because undetected faults
can result in generation and load
instability, outages, and increased
damage and repair time. Basin states
that while sub-requirement R1.12 may
lead to relay settings that limit a line’s
160 Consumers Energy at 12–13; NERC Comments
at 32.
161 See also Ameren, Basin, EEI, McDonald, and
WECC.
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
full potential in response to sudden
increases in line loadings or power
swings, it maximizes loadability to the
extent possible without compromising
the primary zone of protection.
218. Commenters also claim that subrequirement R1.12 is intended to
provide acceptable protection for
uncommon configurations.162 EEI,
WECC, and Consumers Energy speculate
that sub-requirement R1.12 will most
commonly apply to lines with three or
more terminals, which usually require
larger zone 2 settings than two-terminal
lines. Consumers Energy states that such
configurations are actually selected for
reliability, not cost, such that removal of
a line will simultaneously remove other
components that could not be reliably
served in the absence of that line. Oncor
states that the purpose of subrequirement R1.12 is to handle those
less common system configurations
where operating the system at the
maximum capacity of the equipment in
the configuration is within the operating
range of the protective relay settings to
detect and clear all faults in the
protected configuration.
219. Some commenters argue that
utilities should have the flexibility to
decide what is necessary for their
systems. For example, South Carolina
E&G maintains that utilities should be
allowed to either restrict line loadability
for protection or use a different
protection system appropriate for the
particular situation. TVA argues that a
utility should be able to establish
facility ratings based on thermal or relay
limits, and that as long as facility ratings
are applied in system studies correctly
(and such studies show no violations),
a utility should not be required to
change its protective schemes to allow
a higher facility rating based on thermal
limits.
220. TAPS describes sub-requirement
R1.12 as an example of NERC and
industry experts properly exercising
flexibility to balance a number of
reliability factors, including cost, as the
Commission recognized is appropriate
in Order No. 672. TAPS reiterates that
in Order No. 672 the Commission stated
that a proposed Reliability Standard
need not reflect the optimal method, or
‘‘best practice,’’ for achieving its
reliability goal without regard to
implementation cost or historical
regional infrastructure design.163 TAPS
argues that in assessing whether the
Reliability Standard achieves its
reliability goal efficiently and
effectively, the Commission should give
162 See,
e.g., Consumers Energy, EEI, and Oncor.
at 26 (citing Order No. 672, FERC Stats.
& Regs. ¶ 31,204 at P 328).
163 TAPS
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
due weight to NERC’s balancing of
competing factors. TAPS also claims
that the Commission’s proposal to
require a broad change of equipment is
expensive and ‘‘run[s] afoul’’ of sections
215(a)(3) 164 and (i)(2) of the FPA, which
limit Reliability Standards that require
expansion of facilities.
221. APPA states that the
Commission’s proposal appears to
require NERC to prohibit protection
systems that would require the use of
sub-requirement R1.12, effectively
writing sub-requirement R1.12 out of
the Reliability Standard. APPA argues
that the Commission is proposing to
direct NERC to adopt a specific
modification that may not be the best or
most efficient way to address the
Commission’s concerns. APPA states
that it agrees with the Commission
raising the issue to the extent that the
Commission is concerned about the
adverse impact of sub-requirement
R1.12 on Available Transfer Capability.
APPA contends, however, that having
raised the issue, the Commission should
direct NERC as the ERO to develop
solutions rather than dictate a solution
in the first instance.
222. The PSEG Companies argue that
it is impractical to require entities to
replace existing impedance relay
systems without evidence that their
continued use will have a negative
reliability impact. The PSEG Companies
contend that protection systems should
be replaced only if reliability studies
show that the limits imposed on the
system by the use of sub-requirement
R1.12 will truly impede reliability.
Oncor argues that a modification that
would require entities that employ
impedance relays to replace them with
a current differential or pilot wire relay
system that is immune to load or stable
power swings would eliminate the
valuable backup feature of the
impedance relay and actually reduce the
reliability of the grid serving the
atypical configuration.
223. EEI and WECC assert that subrequirement R1.12 can reasonably be
interpreted as the first step in
implementing the Commission’s
proposal to limit the reach of zone 3/
zone 2 relays.165 EEI and WECC explain
that sub-requirement R1.12 imposes a
maximum reach for distance relays of
125 percent of the apparent length of the
protected line, which allows relays to
dependably detect faults. EEI and WECC
add that use of sub-requirement R1.12
may prevent entities from using timedelayed, over reaching zone 3 relays as
remote backup protection, unless they
164 16
U.S.C. 824o(a)(3).
at 25; WECC at 5–6.
165 EEI
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
employ other load limiting relay
features. EEI and WECC argue that even
with this single possible limitation, this
loadability method is consistent with
the Reliability Standard’s objectives.
c. Commission Determination
224. We decline to adopt the NOPR
proposal. After further consideration,
we think that it is incumbent on entities
that implement sub-requirement R1.12
to ensure that they implement it in a
manner that is consistent and
coordinated with the Requirements of
existing Reliability Standards and that
achieves performance results consistent
with their obligations under existing
Standards. While we are not adopting
the NOPR proposal, we direct the ERO
to document, subject to audit by the
Commission, and to make available for
review to users, owners and operators of
the Bulk-Power System, by request, a
list of those facilities that have
protective relays set pursuant to subrequirement R1.12. We believe that this
transparency will allow users, owners,
and operators of the Bulk-Power System
to know which facilities have protective
relay settings, implementing R1.12, that
limit the facility’s capability.
225. We also disagree with
commenters who argue that the few
instances where a protection system
implements sub-requirement R1.12 are
not a threat to the reliability of the BulkPower System unless they have been
declared critical circuits. Protective
relays on Bulk-Power Systems elements
are an integral part of Reliable
Operation.166 Any instance of a
protection system that does not ensure
Reliable Operation is a reliability
concern, not only to prevent and limit
the severity and spread of disturbances,
but also to prevent possible damage to
protected elements.167
226. We also disagree with EEI’s and
WECC’s assertion that sub-requirement
R1.12 can reasonably be interpreted as
the first step in implementing the
Commission’s proposal to limit the
reach of zone 3/zone 2 relays.168 Subrequirement R1.12 establishes
loadability criteria for distance relays
when the desired transmission line
capability is limited by the requirement
to protect the transmission line, and not
explicitly for the application of zone 3/
zone 2 distance relays applied as remote
166 Order No. 693, FERC Stats. & Regs. ¶ 31,242
at P 1435.
167 Id.
168 As discussed previously, the Commission has
decided not to adopt the NOPR proposal for
establishing a maximum allowable reach for the
application of zone 3/zone 2 relays applied as
remote circuit breaker failure and backup protection
upon consideration of comments.
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
16943
circuit breaker failure and backup
protection. As discussed previously, the
Commission proposed to establish a
maximum allowable reach for such
relays because that their large reaches
make the relays susceptible to tripping
from load.
G. Requirement R2
227. Requirement R2 states that
entities that use a circuit with the
protective relay settings determined by
the practical limitations described in
sub-requirements R1.6 through R1.9,
R1.12, or R1.13 must use the calculated
circuit capability as the circuit’s facility
rating. The entities also must obtain the
agreement of the planning coordinator,
transmission operator, and reliability
coordinator as to the calculated circuit
capability. The Commission did not
make any proposal regarding
Requirement R2.
1. Comments
228. ERCOT and IRC state that the
Commission should clarify that the
‘‘agreement’’ contemplated in
Requirement R2 only means that the
entity calculating the circuit capability
is required to provide the circuit
capability to the relevant functional
entities. ERCOT notes that because it is
the planning coordinator, transmission
operator and reliability coordinator in
the ERCOT region, it would be
responsible for reviewing and approving
the calculated circuit capabilities under
Requirement R2. ERCOT states that it
lacks the necessary analysis tools and
data (e.g., conductor sag software and
transmission design data to determine
emergency ratings) to provide an
informed opinion on the circuit
capabilities calculated by transmission
owners, generator owners, or
distribution owners pursuant to
Requirement R2. ERCOT argues that the
entities that own the facilities are in the
best position to establish those limits,
and that planning coordinators,
transmission operators, and reliability
coordinators should not be required to
approve them. ERCOT contends that
planning coordinators, transmission
operators, and reliability coordinators
should merely be made aware of the
limits in order to respect them while
executing their duties. IRC makes the
similar claim that the term ‘‘agreement’’
in Requirement R2 requires only a data
check or confirmation, such that
planning coordinators, transmission
operators, and reliability coordinators
must simply agree that they will use the
circuit capability provided by the
transmission owner, generator owner, or
distribution owner. IRC argues that this
interpretation is consistent with both
E:\FR\FM\02APR2.SGM
02APR2
16944
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
FAC–008–1, which requires
transmission and generator owners to
establish facility rating methodologies
for their facilities and provide them to
reliability coordinators, transmission
operators, transmission planners, and
planning authorities, and FAC–009–0,
which requires transmission and
generator owners to provide the
resultant facility ratings to the same
entities.
mstockstill on DSKH9S0YB1PROD with RULES2
2. Commission Determination
229. We do not agree with ERCOT and
IRC that an entity’s obligation to obtain
the ‘‘agreement’’ of the planning
coordinator, transmission operator, or
reliability coordinator with the
calculated circuit capability only means
that the entity calculating the circuit
capability is required to provide the
circuit capability to the relevant
functional entities. We interpret the
language ‘‘shall obtain the agreement’’ in
Requirement R2 to require that the
entity calculating the circuit capability
must reach an understanding with the
relevant functional entity that the
calculated circuit capability is capable
of achieving the reliability goal of PRC–
023–1. Since PRC–023–1 is intended to
ensure that protective relay settings do
not limit transmission loadability or
interfere with system operators’ ability
to take remedial action to protect system
reliability, and to ensure that relays
reliably detect all fault conditions and
protect the electrical network from these
faults, we expect the agreement to
center around achieving these purposes.
H. Requirement R3 and Its SubRequirements
230. Requirement R3 directs planning
coordinators to identify which sub-200
kV facilities are critical to the reliability
of the bulk electric system and therefore
subject to Requirement R1.169 Subrequirement R3.1 directs planning
coordinators to have a process to
identify critical facilities. Subrequirement R3.1.1 specifies that the
process must consider input from
adjoining planning coordinators and
affected reliability coordinators. Subrequirements R3.2 and R3.3 direct
planning coordinators to maintain a list
of critical facilities and provide it to
reliability coordinators, transmission
owners, generator owners, and
distribution providers within 30 days of
169 As proposed by NERC, Requirement R3 directs
planning coordinators to identify the 100 kV–200
kV facilities that should be subject to Requirement
R1. As we have explained, in this Final Rule we
direct that the ERO revise Requirement R3 so that
planning coordinators also identify sub-100 kV
facilities that should be subject to the Reliability
Standard.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
establishing it, and within 30 days of
making any change to it.
1. Role of the Planning Coordinator
a. Comments
231. ERCOT argues that the
Commission should follow the example
of the Critical Infrastructure Protection
(CIP) Reliability Standards and direct
the ERO to make facility owners, rather
than planning coordinators, responsible
for identifying critical sub-200 kV
facilities and for maintaining and
distributing the critical facilities list.
ERCOT contends that while planning
coordinators and other functional
entities must receive all relevant
information about facilities in their
region, facility owners have the right
and obligation to make criticality
determinations about their facilities.
ERCOT argues that the CIP Reliability
Standards support its position, as they
require facility owners to identify
critical assets.
232. ERCOT also requests
confirmation that sub-requirement
R3.1.1 does not apply to the ERCOT
region because it is not synchronously
interconnected with any other control
area and because ERCOT is the only
planning coordinator and reliability
coordinator within the region.
b. Commission Determination
233. We disagree with ERCOT and
will not direct the ERO to make facility
owners responsible for identifying
critical sub-200 kV facilities or for
maintaining and distributing the critical
facilities list. We also reject ERCOT’s
comparison between PRC–023–1 and
the CIP Reliability Standards. Facility
owners are responsible for maintaining
only their own facilities. Planning
coordinators, on the other hand, are
charged with assessing the long-term
reliability of their planning authority
areas.170 Consequently, planning
coordinators are better prepared and
equipped to make the comprehensive
criticality determinations for their areas
for the purposes of PRC–023–1. We thus
agree with the ERO that planning
coordinators are better suited to make
the criticality determinations for the
purposes of PRC–023–1.
234. Finally, while we acknowledge
that ERCOT is not synchronously
interconnected with any other control
area and that it is the only planning
coordinator and reliability coordinator
in its region, we clarify that any request
for a regional exemption from PRC–023–
1 is an applicability matter that must be
raised in the Reliability Standards
development process and included in a
170 See
PO 00000
NERC Function Model, Version 3 at 14.
Frm 00032
Fmt 4701
Sfmt 4700
modified Reliability Standard.171
Consequently, Requirement R3 and its
sub-requirements apply to ERCOT.
2. Sub-Requirement R3.3
a. NOPR Proposal
235. The Commission proposed to
direct the ERO to add Regional Entities
to the list of entities that receive the
critical facilities list pursuant to subrequirement R3.3.
b. Comments
236. NERC and WECC agree with the
Commission that the Regional Entity
should receive the critical facilities list.
EEI acknowledges that the
Commission’s proposal may have merit,
but opposes a modification. EEI
explains that the Regional Entity can
already request the data from planning
authorities and reliability coordinators
at any time, and argues that it is not
necessary to formalize the process.
c. Commission Determination
237. We adopt the NOPR proposal
and direct the ERO to modify the
Reliability Standard to add the Regional
Entity to the list of entities that receive
the critical facilities list. The Regional
Entity must know which facilities in its
area have been identified as
operationally significant and could
contribute to cascading outages and the
loss of load. Additionally, providing
Regional Entities with the critical
facilities list will aid in the overall
coordination of planning and
operational studies among planning
coordinators, transmission owners,
generator owners, distribution
providers, and Regional Entities. As
with our other directives in this Final
Rule, we do not prescribe this specific
change as an exclusive solution to our
reliability concerns regarding subrequirement R3.3. As we have stated,
the ERO can propose an alternative
solution that it believes is an equally
effective and efficient approach to
addressing the Commission’s reliability
concerns.172
I. Attachment A
238. Attachment A of the Reliability
Standard contains three sections: (1) A
non-exhaustive list of load-responsive
relays subject to the Standard; (2) a
statement that out-of-step blocking
protective schemes are subject to the
Standard and shall be evaluated to
ensure that they do not block trip for
fault during the loading conditions
defined within the Standard’s
171 Order No. 693, FERC Stats. & Regs. ¶ 31,242
at P 1125.
172 Id. P 186.
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
16945
requirements; and (3) a list of protective
systems that are expressly excluded
from the Standard’s requirements. In the
NOPR, the Commission expressed
concerns about sections 2 and 3.
blocking relays are ‘‘transmission line
relays’’ addressed in Requirement R1.
Oncor argues that section 2 is already a
requirement because it is in an
attachment instead of an appendix.
Reliability Standard and must be set
pursuant to Requirement R1.
1. Section 2: Evaluation of Out-of-Step
Blocking Schemes
239. Section 2 of Attachment A states
that the ‘‘[Reliability Standard] includes
out-of-step blocking schemes which
shall be evaluated to ensure that they do
not block trip for faults during the
loading conditions defined within the
requirements.’’
c. Commission Determination
249. Section 3 lists certain protection
systems that are excluded from the
requirements of PRC–023–1. These
systems are specified in sections 3.1
through 3.9.
mstockstill on DSKH9S0YB1PROD with RULES2
a. NOPR Proposal
240. In the NOPR, the Commission
stated that since the ERO intends to
require the evaluation of out-of-step
blocking applications, language to this
effect should be included in PRC–023–
1 as a Requirement. To this end, the
Commission proposed to direct the ERO
to add section 2 of Attachment A to
PRC–023–1 as an additional
Requirement with the appropriate
violation risk factor and violation
severity level assignments.
b. Comments
241. NERC agrees that the proposed
modification is appropriate and
proposes to implement it through the
full Reliability Standards development
process in the next modification of
PRC–023–1. In the meantime, NERC
requests that the Commission approve
Attachment A as currently written.173
242. WECC asserts that the
Commission’s proposal is reasonable
because the obligation to evaluate outof-step blocking schemes is part of PRC–
023–1, but carries no penalty without a
violation risk factor and violation
severity level. WECC suggests that the
Commission take the same approach
with respect to out-of-step tripping
(section 1.2). WECC explains that
without appropriate load supervision,
out-of-step tripping may subject circuit
breakers to excessive over-voltages, if it
occurs at all.
243. Dominion, EEI, and Oncor
disagree with the Commission’s
proposal. Rather than make it a
Requirement, Dominion argues that the
statement about out-of-step blocking
schemes should be removed from PRC–
023–1 and included in a Reliability
Standard that addresses stable power
swings. EEI asserts that section 2
appropriately appears in Attachment A
because Attachment A identifies the
types of transmission line relays and
relay schemes that are subject to the
Reliability Standard, and out of step
173 See
also Duke and IESO/Hydro One.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
244. We adopt the NOPR proposal
and direct the ERO to include section 2
of Attachment A in the modified
Reliability Standard as an additional
Requirement with the appropriate
violation risk factor and violation
severity level.
245. EEI correctly states that
Attachment A is a compilation of the
types of transmission line relays and
relay schemes that are subject to PRC–
023–1, and that section 2 specifies that
out-of-step blocking schemes are subject
to it. However, section 2 also creates an
obligation to evaluate out-of-step
blocking schemes to ensure that they do
not block trip for faults during the
loading conditions defined within the
Reliability Standard’s Requirements.
This is an obligation that is not stated
in, or referenced by, any Requirement in
the Reliability Standard. Consequently,
this obligation is not currently
associated with a violation risk factor or
violation severity level.
246. Although the obligation to
evaluate out-of-step blocking schemes is
currently not stated in a Requirement, it
nevertheless remains an obligation
imposed on entities by PRC–023–1
because it is a part of Attachment A and
therefore a part of PRC–023–1.
Consequently, we clarify that entities
must comply with this obligation while
the ERO modifies PRC–023–1 to include
it as a Requirement.
247. We disagree with Dominion’s
suggestion that the Commission direct
the ERO to remove section 2 from PRC–
023–1 and include it in a Reliability
Standard that addresses stable power
swings. It is appropriate to include
section 2 as a Requirement in PRC–023–
1 because out-of-step blocking schemes
must be allowed to trip for faults during
the loading conditions defined within
PRC–023–1. Otherwise, faults that occur
during a power swing may result in
system instability if not cleared.
248. Finally, we will not direct the
ERO to make section 1.2 into a
Requirement as WECC suggests. Section
1 of Attachment A is a non-exhaustive
list of relays and protection systems that
are subject to Attachment A; unlike
section 2, section 1 does not create
substantive obligations that are neither
stated in nor referenced by the
Requirements. Section 1.2 merely lists
out-of-step tripping systems as one of
the systems that are subject to the
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
2. Section 3: Protection Systems
Excluded From the Reliability Standard
a. NOPR Proposal
250. In the NOPR, the Commission
stated that it could not determine
whether the exclusions in section 3 are
justified because NERC did not provide
the technical rationale behind any of the
exclusions.174
251. The Commission also raised
specific concerns about section 3.1,
which excludes from the Reliability
Standard’s requirements relay elements
that are enabled only when other relays
or associated systems fail, such as those
overcurrent elements enabled only
during loss of potential conditions or
elements enabled only during the loss of
communications. The Commission
expressed concern that section 3.1 could
be interpreted to exclude certain
protection systems that use
communications to compare current
quantities and directions at both ends of
a transmission line, such as pilot wire
protection or current differential
protection systems supervised by fault
detector relays. The Commission
explained that if supervising fault
detector relays are not subject to the
Reliability Standard, and they are set
below the rating of the protected
element, the loss of communications
and heavy line loading conditions that
approach the line rating would cause
them to operate and unnecessarily
disconnect the line; adjacent
transmission lines with similar
protection systems and settings would
also operate unnecessarily, resulting in
cascading outages. The Commission
requested comments, therefore, on
whether the exclusions in section 3 are
technically justified and whether it
should direct the ERO to modify PRC–
023–1 by deleting specific sections in
section 3. The Commission also
requested comment on whether it
should direct the ERO to modify section
3.1 to clarify that it does not exclude
from the requirements of PRC–023–1
pilot wire protection or current
174 The exclusion of protection systems intended
for the detection of ground fault conditions appears
to be unnecessary because these systems are not
load-responsive.
E:\FR\FM\02APR2.SGM
02APR2
16946
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
differential protection systems
supervised by fault detector relays.175
mstockstill on DSKH9S0YB1PROD with RULES2
b. Comments
252. While NERC acknowledges that
specific justification should be included
for those protection systems that
ultimately remain excluded from the
Reliability Standard’s requirements,
NERC opposes removing any of the
exclusions.176
253. With respect to section 3.1,
NERC does not share the Commission’s
concern and urges it not to direct the
removal of supervising fault detector
relays from the list of exclusions. NERC
explains that section 3.1 excludes
elements that: (1) Do not respond to
load current; (2) are in use only during
very short periods of time to address
short-term conditions; or (3) supervise
operation of relay elements that
themselves are subject to the Reliability
Standard. NERC explains that if the
supervised relay element itself does not
operate in these cases, the operation of
the supervising element should have no
impact on reliability. NERC asserts that
if a communications system is lost, the
transmission element must be protected
and may need to be tripped for low
magnitude faults approaching load
current. NERC argues that it is
preferable to trip one line for loss of
communications than not trip at all,
thereby causing mis-coordination and/
or stability problems. NERC adds that
the failure of a communications-based
protection system is typically an
isolated event.
254. EEI speculates that the intent
behind specifically excluding
overcurrent elements enabled only
during loss of potential conditions and
elements enabled only during a loss of
communications (the specific examples
listed in section 3.1) is to exclude relay
system failures that, for normal utility
practice, would result in either
emergency call outs and repairs or nextday call outs and repairs. EEI concludes
that these failures are rare enough to
have a limited impact on the BulkPower System.
255. EEI and Ameren support section
3.1 as technically justified because it
allows transmission lines to remain in175 The Commission also noted that section 3.5
excludes from the requirements of PRC–023–1
‘‘relay elements used only for [s]pecial [p]rotection
[s]ystems applied and approved in accordance with
NERC Reliability Standards PRC–012 through PRC–
017.’’ Since PRC–012–0, PRC–013–0 and PRC–014–
0 are currently proposed Reliability Standards
pending before the Commission, the particular relay
elements they involve remain subject to PRC–023–
1 until the relevant Standards are approved by the
Commission. Order No. 693–A, 120 FERC ¶ 61,053
at P 138.
176 NERC Comments at 35.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
service with a level of fault protection
while the failure that required activation
of the section 3.1 relays is repaired, and
that the alternative would be to take the
lines or buses out of service.177 Ameren
cautions that this alternative would put
the system in a less reliable N–1 or Nmany state.
256. EEI adds that many long
transmission lines proposed to support
the creation of the national grid will
require backup protection for the types
of failures discussed in section 3.1. EEI
explains that, for very long lines, the
fault currents can be below rated
continuous capability without the 150
percent margin, and that simple
schemes are required for the small
periods of time when the backup
protection will be in-service following a
loss of potential conditions or
communications. EEI contends that
these exceptions only impact one
facility at a time and do not present
more risk than removing the facility.
257. Exelon, Consumers Energy, and
IESO/Hydro One also claim that the
exclusions in section 3.1 are justified.
Exelon asserts that the Reliability
Standard’s goal is to address protective
relays that have a history of contributing
to cascades, and that relays enabled
only when other relays or associated
systems fail are extremely unlikely to be
a factor in a disturbance because they
are enabled so infrequently. Consumers
Energy cautions that the relays excluded
in section 3.1 must be able to respond
to relay failures without regard to relay
loadability; otherwise, there is a risk
that faults will not be cleared and there
will be cascading outages. IESO/Hydro
One argue that the Commission should
approve section 3.1 because the relays it
excludes are incapable of independently
opening the circuit breaker; that is, they
require the action of other relays.
258. TAPS argues that NERC should
reconsider section 3.1 because the
exclusion of relay elements enabled
only when other relays or associated
systems fail depends on the successful
operation of a potential source
(potential transformer or capacitor
coupled voltage transformer (CCVT)) or
a communication system.178 TAPS
explains that the TPL Reliability
Standards require planners to plan the
system as if a potential source or
communication system has failed (e.g.,
TPL–003–0). Although potential sources
and communication systems fail
infrequently, TAPS states that it might
be consistent with the TPL Standards
for NERC to reconsider the balance of
these factors. TAPS argues, however,
177 EEI
at 27–28; Ameren at 15.
Attachment 1 at 17.
178 TAPS,
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
that the Commission should not require
NERC to eliminate section 3.1.
259. In general, commenters contend
that the rest of the exclusions in section
3 have a sound technical basis. Basin
argues that the exclusions address
protection systems that have no
significant impact on the reliability of
the bulk electric system, and suggests
that the Commission consider the
following criteria in determining
whether a system should be subject to
PRC–023–1: (1) The frequency with
which that system is enabled; (2) the
probability that the system will be
activated when it is enabled; and (3) the
effects that the protection system will
have on the Bulk-Power System when it
is activated.179 Basin argues that
protection systems that have a low
probability of being activated when
enabled should be excluded from the
Reliability Standard. Likewise, those
that, when activated, have an
inconsequential effect on system
stability should also be excluded from
the Reliability Standard. The PSEG
Companies argue that PRC–023–1
reasonably balances risks with the
potential expenditure of substantial and
costly changes to protection systems.180
260. Exelon and Consumers Energy
argue that section 3.2, which excludes
relays that are designed to detect ground
fault conditions, is justified because
such relays have no significant history
of contributing to cascades. Consumers
Energy claims that it would be a waste
of resources to identify, study, and
document the behavior of devices
intended for the detection of ground
faults, when such devices are immune
to tripping for load currents.
261. Duke asserts that it is unclear
whether section 3.3, which excludes
protection systems intended for
protection during stable power swings,
is meant for tripping or to block
tripping. Duke states that if the
protection is to block tripping, the
exclusion is in conflict with section 2 of
Attachment A, as many relays use the
same logic to block for out-of-step
conditions and for stable power swings.
262. Exelon states that the relays
identified in section 3.5, which
excludes relays used for special
protection systems applied and
approved in accordance with Reliability
Standards PRC–012 through PRC–017,
are designed along with specific relay
settings to assure that a given power
system meets NERC performance
requirements. Consumers Energy asserts
that these relay systems are intended for
a specific set of conditions and already
179 Basin
180 PSEG
E:\FR\FM\02APR2.SGM
at 12–13.
Companies at 12.
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
mstockstill on DSKH9S0YB1PROD with RULES2
undergo a stringent review, such that
additional review under PRC–023–1 is
unnecessary and creates the risk that a
special protection system approved
under PRC–012 through PRC–017 may
be found non-compliant under PRC–
023–1. Dominion adds that relay
elements used only for special
protection systems applied and
approved in accordance with PRC–012
through PRC–017 do not present a risk
to the reliability of the grid because the
instances in which they operate are rare
events that are addressed and corrected
in a timely manner.181
263. TAPS argues that the exclusions
in sections 3.2 through 3.8 are designed
to ensure that PRC–023–1 applies where
it is needed to address loadability
concerns, but does not interfere with
relays that are not tripped by load
current. TAPS adds that section 3.9,
which excludes relay elements
associated with DC converter
transformers, is justified because the
output of generators and DC line
converters is not changed significantly
with the loss of other facilities.182
c. Commission Determination
264. After further consideration, and
in light of the comments, we will not
direct the ERO to remove any exclusion
from section 3, except for the exclusion
of supervising relay elements in section
3.1. Consequently, we direct the ERO to
revise section 1 of Attachment A to
include supervising relay elements on
the list of relays and protection systems
that are specifically subject to the
Reliability Standard. As with our other
directives in this Final Rule, we do not
prescribe this specific change as an
exclusive solution to our reliability
concerns regarding the exclusion of
supervising relay elements. As we have
stated, the ERO can propose an
alternative solution that it believes is an
equally effective and efficient approach
to addressing the Commission’s
reliability concerns.183
265. Supervising elements ensure that
a protection system is secure and does
not operate when it should not operate.
When a supervising relay is in place, it
acts as a check on the supervised
protection system because both must
operate to trip a facility. If a supervising
relay is set below the rating of the line,
high loading conditions will cause it to
be ‘‘picked-up,’’ i.e., continuously
energized and ready to operate. When
this occurs, the supervising relay will
no longer be able to act as a check on
181 Dominion
at 8.
at 27–28.
183 Order No. 693, FERC Stats. & Regs. ¶ 31,242
at P 186.
182 TAPS
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
the other protection system because the
supervising relay will already have
registered that it should operate. At that
point, the supervising relay will be
waiting for the supervised relay to
become energized before tripping the
protected facility.184
266. For example, current differential
protection systems use communication
systems to transmit and compare
information between relays located at
both terminals and to initiate the highspeed tripping of a facility when the
difference of currents at the sending end
and receiving end exceeds a threshold
setting usually set at a small fraction of
the normal line loading. Since these
protection systems are dependent on
communication systems, the protected
facility will trip if communication is
lost, even when the line continues to
carry its normal load current, because
the difference of the currents as seen at
either end will be the load current
which is much larger than the threshold
setting. Consequently, overcurrent
relays are typically used as supervising
relays to prevent the protected facility
from tripping if communication is lost.
However, if the supervising relays are
energized due to loading conditions,
and then communication is lost, the
current differential protection system
will operate in the absence of a fault and
the protected facility will trip.
267. NERC asserts that it is preferable
to trip one line for loss of
communications than not trip at all,
thereby causing mis-coordination and/
or stability problems. We disagree.
Protective relays should not operate
during non-fault conditions. The
tripping of facilities for non-fault
conditions, like NERC describes, or in
the case of the August 2003 blackout is
not desirable system performance.
268. We also disagree with IESO/
Hydro One’s assertion that the exclusion
of supervising relays from PRC–023–1 is
appropriate because such relays are not
capable of independently opening the
circuit breaker. While a supervising
relay is not designed to independently
trip a facility by initiating the opening
of the circuit breaker, if that relay is
picked up and energized during nonfault conditions, it is no longer capable
of ensuring the security of a protection
system and may result in the
unnecessary tripping of the facility it is
protecting. As we explained, if
supervising relays are not subject to the
Reliability Standard, and are set below
the rating of the protected element, the
loss of communications and heavy line
loading conditions that approach the
line rating would cause them to operate
and unnecessarily disconnect the
line.185 A more recent example is an
event that occurred on June 27, 2007
where 138 kV transmission lines in the
NPCC region resulted in sequential
tripping of the four 138 kV cablecircuits. The event resulted in the
interruption of service to about 137,000
customers as well as the loss of five
generators and six 138 kV transmission
lines. This event is the type of situation
that PRC–023–1 is intended to prevent,
and illustrates why we must direct the
ERO to modify Attachment A to include
supervising relays.
269. Although we do not direct the
ERO to remove section 3.1 from the list
of excluded protection systems, we find
it necessary to address some comments
made in the context of the
Commission’s proposal. For example,
we disagree with those commenters that
suggest that the Commission should
approve section 3.1 because it excludes
from the Reliability Standard’s scope
relays and protection systems that rarely
operate. These commenters appear to
suggest that protection systems that
rarely operate do not pose a risk to the
reliability of the Bulk-Power System.
We disagree. A protective relay, as an
integral part of the Bulk-Power System,
must be dependable and secure; it must
operate correctly when required to clear
a fault and refrain from operating
unnecessarily, i.e., during non-fault
conditions or for faults outside of its
zone of protection, regardless of how
many times the relay must actually
operate.186 Relays must meet this
expectation to contribute to ensuring
Reliable Operation of the Bulk-Power
System. Consequently, the notion that
any specific relay should be excluded
from the Reliability Standard’s scope
because it may operate only on rare
occasions is inconsistent with the
fundamental principles that make
protective relays an integral part of
ensuring Reliable Operation.
270. We also disagree with Ameren’s
assertion that removing section 3.1 from
the list of exclusions would put the
Bulk-Power System in a ‘‘less reliable
N–1state.’’ As we discuss above, if
supervising relays that are used in
185 NOPR,
184 It
works like an ‘‘and’’ condition (0 + 0 = no
trip line, 1 + 1 = trip line, 1 + 0 = no trip line).
For a supervising relay like a fault detector to be
always ‘‘picked up’’ means that the relay is
energized (it is always a ‘‘1’’) and is waiting for
another relay to also become energized before
tripping a facility.
PO 00000
Frm 00035
Fmt 4701
Sfmt 4700
16947
FERC Stats. & Regs. ¶ 32,642 at P 79.
fundamental objectives for protection
systems are consistent if not identical with the ones
stated in NERC Planning Standards III: System
Protection and Control, at 43: Dependability—a
measure of certainty to operate when required,
Security—a measure of certainty not to operate
falsely.
186 These
E:\FR\FM\02APR2.SGM
02APR2
16948
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
schemes; 187 and (3) 24 months from
notification by the planning coordinator
that, pursuant to the ‘‘add in’’ approach,
a facility has been added to the planning
coordinator’s list of critical facilities.
For Requirement R3, NERC proposed an
effective date of 18 months following
applicable regulatory approvals.
274. NERC also proposed to include a
footnote (exceptions footnote) to the
‘‘Effective Dates’’ section honoring
temporary exceptions from enforcement
actions approved by the NERC Planning
Committee before NERC proposed the
Reliability Standard.188
J. Effective Date
mstockstill on DSKH9S0YB1PROD with RULES2
current differential schemes are
excluded from PRC–023–1 and set much
below the line rating, they will trip the
protected lines inadvertently following
the loss of communication system
forming part of the protection system.
271. Finally, Duke asserts that section
3.3 is ambiguous with respect to
whether it excludes protection meant
for tripping or to block tripping, and
that if it excludes protection meant to
block tripping, it is in conflict with
section 2 because many relays use the
same logic to block for out-of-step
conditions and for stable power swings.
We clarify that we do not find a conflict
between section 3.3, which excludes
from the Reliability Standard’s scope
any protection system intended for
protection during stable power swings,
and section 2, which ensures that outof-step blocking schemes do not block
tripping during the loading conditions
defined within PRC–023–1.
272. Out-of-step schemes, blocking
and tripping, are generally associated
with power swing protection
applications. Out-of-step tripping
schemes allow controlled tripping
during loss of synchronism during
unstable power swings while out-of-step
blocking schemes block tripping during
stable power swings. Because out-ofstep tripping relays are supervised by
load-responsive overcurrent relays, its
applicability to the requirements of
PRC–023–1 is appropriate. Because the
reliability objective of Requirement R1
is to set protective relays while
‘‘maintaining reliable protection of the
bulk-electric system for all fault
conditions,’’ as previously determined,
out-of-step blocking schemes must
allow tripping for faults during the
loading conditions defined within PRC–
023–1. Thus, the reliability goal of the
two schemes for the purposes of PRC–
023–1 is different, and consequently, we
find no conflict within the Standard.
187 ‘‘Switch-on-to-fault schemes’’ are protection
systems designed to trip a transmission line breaker
when the breaker is closed into a fault. Because the
current fault detectors for these systems must be set
low enough to detect ‘‘zero-voltage’’ faults, i.e.,
close-in, three-phase faults, these systems may be
susceptible to operate on load.
188 The footnote states:
Temporary Exceptions that have already been
approved by the NERC Planning Committee via the
NERC System and Protection and Control Task
Force prior to the approval of this [Reliability
Standard] shall not result in either findings of noncompliance or sanctions if all of the following
apply: (1) The approved requests for Temporary
Exceptions include a mitigation plan (including
schedule) to come into full compliance, and (2) the
non-conforming relay settings are mitigated
according to the approved mitigation plan.
189 NOPR, FERC Stats. & Regs. ¶ 32,642 at P 85–
86.
273. NERC proposed the following
effective dates for Requirements R1 and
R2: (1) The beginning of the first
calendar quarter following applicable
regulatory approvals for all transmission
lines and transformers with low-voltage
terminals operated/connected at and
above 200 kV, except for switch-on-to
fault-schemes; (2) the beginning of the
first calendar quarter 39 months after
applicable regulatory approvals for all
transmission lines and transformers
with low-voltage terminals operated/
connected between 100 kV and 200 kV,
including switch-on-to fault-
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
1. NOPR Proposal
275. In the NOPR, the Commission
proposed to approve NERC’s
implementation plan for facilities
operated at and above 200 kV. In light
of its applicability proposals, the
Commission proposed to reject the rest
of NERC’s implementation plan and
require, for all sub-200 kV facilities, an
effective date of 18 months following
applicable regulatory approvals. The
Commission also proposed to direct
NERC to remove the exceptions
footnote, explaining that discussions
about potential enforcement actions are
best left out of a Reliability Standard
and instead handled by NERC’s
compliance and enforcement
program.189
2. Comments on Effective Date
Proposals
276. In general, commenters support
the Commission’s proposal to adopt the
effective date proposed by NERC for
facilities operated at and above 200 kV,
but overwhelmingly oppose the
Commission’s proposal for an 18 month
effective date for sub-200 kV facilities,
regardless of whether the Commission
directs the ERO to adopt the ‘‘rule out’’
approach or approves NERC’s ‘‘add in’’
PO 00000
Frm 00036
Fmt 4701
Sfmt 4700
approach.190 Commenters generally
argue that the Commission should adopt
NERC’s proposal of an effective date of
the beginning of the first calendar
quarter 39 months after applicable
regulatory approvals for 100 kV-200 kV
facilities.
277. NERC argues that planning
coordinators will require at least 18
months to identify the 100 kV-200 kV
facilities that should be subject to the
Reliability Standard, and possibly an
additional 18 to 24 months to complete
any design and construction changes
necessary to comply with the Standard.
Consumers Energy, EEI, and Oncor offer
similar estimates.
278. APPA argues that NERC’s
implementation plan gives planning
coordinators the time necessary to
perform in-depth studies to identify
which facilities are critical to the
reliability of the bulk electric system,
and gives affected entities the time to
make any necessary costly upgrades.
APPA adds that only a limited number
of experienced industry experts and
consultants will be available to assist
entities in complying with the
Reliability Standard, and speculates that
their time will be in high demand.
279. TAPS observes that Order No.
672 recognizes that implementation
timelines must balance any urgency in
the need to implement a Reliability
Standard with the reasonableness of the
time allowed for those who must
comply to develop the necessary
procedures, software, facilities, staffing
or other relevant capability.191 TAPS
argues that the Commission should give
due weight to NERC’s expert assessment
of that balance and adopt the effective
dates proposed by NERC.
3. Comments on Exceptions Footnote
280. EEI argues that the Commission’s
proposal to direct the ERO to remove
the exceptions footnote is too
prescriptive given the Commission’s
statutory role in the Reliability Standard
development process. EEI argues that
the Commission has gone much farther
than identifying its concern because its
proposal does not allow for the ERO to
develop equally effective alternatives.192
281. Oncor and Consumers Energy
agree with the Commission’s proposal.
Oncor argues that the need for the
temporary exemption has expired and
therefore should be removed from the
Reliability Standard.
190 Commenters argue that a ‘‘rule out’’ approach
would require a much longer implementation
period, with estimates of up to 12 years.
191 TAPS at 29 (citing Order No. 672, FERC Stats.
& Regs. ¶ 31,204 at P 333).
192 EEI at 28.
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
4. Commission Determination
282. We decline to fully adopt the
NOPR proposal and approve all of
NERC’s proposed effective dates,
including its proposal of 39 months
from the beginning of the first calendar
quarter after applicable regulatory
approvals for 100 kV–200 kV facilities.
In light of our decision to approve the
‘‘add in’’ approach for 100 kV–200 kV
facilities, and after consideration of the
comments, we agree with NERC that
this is an appropriate effective date.
283. Additionally, in light of our
directive to the ERO to expand the
Reliability Standard’s scope to include
sub-100 kV facilities that Regional
Entities have already identified as
necessary to the reliability of the BulkPower System through inclusion in the
Compliance Registry, we direct the ERO
to modify the Reliability Standard to
include an implementation plan for sub100 kV facilities.
284. We also direct the ERO to remove
the exceptions footnote from the
‘‘Effective Dates’’ section. As the
Commission stated in the NOPR, the
exceptions footnote is addressed to
potential enforcement actions, and is
therefore best left out of the Reliability
Standard and addressed in NERC’s
compliance and enforcement program.
Moreover, we agree with Oncor that the
need for the temporary exemption has
expired and therefore should be
removed from the Reliability Standard.
We add that entities are free to request
exceptions through NERC’s existing
process, subject to Commission review
and approval.
mstockstill on DSKH9S0YB1PROD with RULES2
K. Violation Risk Factors
285. Requirement R1 directs entities
to set their relays according to one of the
options set forth in sub-requirements
R1.1 through R1.13. NERC assigned
Requirement R1 a ‘‘high’’ violation risk
factor, but did not assign violation risk
factors to sub-requirements R1.1
through R1.13.
286. Requirement R2 provides that
entities that set their relays according to
sub-requirements R1.6 through R1.9,
R1.12, or R1.13 must use the calculated
circuit capability as the circuit’s facility
rating and must obtain the agreement of
the planning coordinator, transmission
operator, and reliability coordinator as
to the calculated circuit capability.
NERC assigned Requirement R2 a
‘‘medium’’ violation risk factor.
287. Requirement R3 requires
planning coordinators to determine
which sub-200 kV facilities are critical
to the reliability of the bulk electric
system and therefore subject to
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
Requirement R1.193 NERC assigned
Requirement R3 a ‘‘medium’’ violation
risk factor.
1. NOPR Proposal
288. In the NOPR, the Commission
listed the five guidelines that it uses to
evaluate proposed violation risk factor
assignments (Violation Risk Factor
Guidelines). According to these
Guidelines, violation risk factor
assignments should be consistent: (1)
With the conclusions of the Final
Blackout Report; (2) within a Reliability
Standard; (3) among Reliability
Standards with similar Requirements;
and (4) with NERC’s definition of the
violation risk factor level; the
Commission also stated that (5) the
violation risk factor levels for
Requirements that co-mingle a higher
risk reliability objective and a lower risk
reliability objective must not be watered
down to reflect the lower risk level
associated with the less important
reliability objective.194
289. The Commission agreed with
NERC that Requirement R1 should be
assigned a ‘‘high’’ violation risk factor.
The Commission added, however, that
violation of any of the criteria in subrequirements R1.1 through R1.13
present the same reliability risk as a
violation of Requirement R1 because
they set forth the options for compliance
with Requirement R1. Consequently, the
Commission proposed to direct the ERO
to assign a ‘‘high’’ violation risk factor to
each sub-requirement.
290. The Commission also proposed
to direct the ERO to modify the
violation risk factor assigned to
Requirement R3 and its subrequirements to reflect the
Commission’s applicability proposals.
2. Comments
291. NERC and other commenters
oppose the Commission’s proposal to
assign a separate violation risk factor to
sub-requirements R1.1 through R1.13.
These commenters argue that the subrequirements are alternative ways to
comply with Requirement R1, not
separate Requirements that must be
complied with in their own right. The
193 As proposed by NERC, Requirement R3 directs
planning coordinators to identify the 100 kV–200
kV facilities that should be subject to Requirement
R1. As we have explained, in this Final Rule we
direct that the ERO revise Requirement R3 so that
planning coordinators also identify sub-100 kV
facilities that should be subject to the Reliability
Standard.
194 NOPR, FERC Stats. & Regs. ¶ 32,642 at P 88.
For a complete discussion of each guideline, see
North American Electric Reliability Corp., 119 FERC
¶ 61,145, P 19–36 (Violation Risk Factor Order),
order on reh’g and compliance filing, 120 FERC
¶ 61,145 (2007) (Violation Risk Factor Rehearing
Order).
PO 00000
Frm 00037
Fmt 4701
Sfmt 4700
16949
commenters point out that each subrequirement is intended to address a
different operating condition or system
design condition and that, for any
specific circuit, entities will set their
relays pursuant to only one of the subrequirements. NERC adds that its
proposal to assign violation risk factors
only to Requirement R1 is consistent
with its informational filing in Docket
No. RM08–11–000, where it described
more fully its plans for a new,
comprehensive approach to assigning
violation risk factors.195
292. An individual commenter,
Michael McDonald, argues that
Requirement R1 should have a
‘‘medium’’ violation risk factor, rather
than a ‘‘high’’ violation risk factor,
because actions taken since the August
2003 blackout have reduced the
likelihood that a relay loadability issue
will cause a cascading outage.
3. Commission Determination
293. We approve NERC’s assignment
of a ‘‘high’’ violation risk factor to
Requirement R1 and a ‘‘medium’’
violation risk factor to Requirement R2.
These violation risk factor assignments
are consistent with the Violation Risk
Factor Guidelines.
294. We disagree with Michael
McDonald, who argues that
Requirement R1 should have a
‘‘medium’’ violation risk factor rather
than a ‘‘high’’ violation risk factor.
Violation risk factor assignments
represent the risk a violation of a
Requirement presents to the Bulk-Power
System.196 Although the Commission,
the ERO, and industry have taken
actions since the August 2003 blackout
to reduce the likelihood that relay
outages will cause cascading outages,
these actions do not mitigate the risk of
non-compliance with Requirement R1.
In our view, a violation of Requirement
R1 has the potential to put the BulkPower System at the risk of cascading
outages like those that occurred during
the August 2003 blackout.
Consequently, we agree with the ERO
that Requirement R1 should be assigned
a ‘‘high’’ violation risk factor.
295. We will not require the ERO to
assign a violation risk factor to each subrequirement of Requirement R1 because
we agree with the ERO that the subrequirements are alternative ways, based
on different operating or design
configurations, of complying with
Requirement R1. Consequently, an
entity’s failure to appropriately apply
195 In its informational filing, NERC indicates that
NERC drafting teams will develop ‘‘rolled up’’
violation risk factors and violation severity levels.
196 North American Electric Reliability Corp., 121
FERC ¶ 61,179, at P 38 (2007).
E:\FR\FM\02APR2.SGM
02APR2
16950
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
mstockstill on DSKH9S0YB1PROD with RULES2
one of the sub-requirements of
Requirement R1 to a specific operating
design or configuration is, as a violation
of Requirement R1, subject to a ‘‘high’’
violation risk factor. While the
Commission generally expects that the
ERO will assign a violation risk factor to
each Requirement and sub-requirement
of a Reliability Standard, we will accept
the ERO’s proposal not to assign
violation risk factors to subrequirements R1.1 through R1.13 as an
exception to our current policy because
we are satisfied that the subrequirements do not constitute
independent compliance requirements
separate from Requirement R1.197
296. We also agree with the ERO’s
decision to assign Requirement R2 a
‘‘medium’’ violation risk factor.
Requirement R2 comprises two
reliability obligations: (1) The required
use of the calculated circuit capability
as the facility rating of the circuit for
entities that set their relays according to
sub-requirements R1.6 through R1.9,
R1.12, or R1.13; and (2) the entities’
obligation to obtain the agreement of the
planning coordinator, transmission
operator, and reliability coordinator as
to the calculated circuit capability.
Requirement R2 co-mingles more than
one reliability obligation and, consistent
with Violation Risk Factor Guideline 5,
the assigned violation risk factor reflects
the reliability risk of a violation of the
higher reliability obligation (i.e., the
requirement to use the calculated circuit
capability as the facility rating of the
circuit).
297. Finally, we direct the ERO to
assign a ‘‘high’’ violation risk factor to
Requirement R3. The Commission
expects consistency between violation
risk factors assigned to Requirements
that address similar reliability goals.198
NERC assigned a ‘‘high’’ violation risk
factor to Requirement R1, which
requires entities to set their relays
according to one of the criteria in subrequirements R1.1 through R1.13.
Requirement R3 directs planning
coordinators to determine which sub200 kV facilities will be subject to
Requirement R1. Since the facilities
197 NERC’s assignment of violation risk factors in
Reliability Standard PRC–023–1 appears to be
consistent with the approach to assigning violation
risk factors set forth in NERC’s informational filing
in Docket No. RM08–11–000. At NERC’s request,
the Commission has not acted on the informational
filing. The Commission understands, however, that
NERC anticipates formally filing a comprehensive
‘‘roll up’’ plan in the second quarter of 2010.
Consequently, we direct the ERO to re-file the
violation risk factors associated with the
Requirements of PRC–023–1 when it submits its
comprehensive plan.
198 Violation Risk Factor Order, 119 FERC
¶ 61,145 at P 25.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
identified by the planning coordinator
pursuant to Requirement R3 are
required to meet Requirement R1, we
conclude that the reliability risk to the
Bulk-Power System of a violation of
Requirement R3 is the same as a
violation of Requirement R1. We direct
the ERO to file the new violation risk
factor no later than 30 days after the
date of this Final Rule.
L. Violation Severity Levels
298. NERC proposed violation
severity levels for Requirements R1, R2,
and R3, but not for sub-requirements
R1.1 through R1.13 or R3.1 through
R3.3.
299. For Requirement R1, NERC
proposed: (1) A ‘‘moderate’’ violation
severity level when an entity complies
with a sub-requirement of Requirement
R1, but has incomplete or incorrect
evidence of compliance; and (2) a
‘‘severe’’ violation severity level when
an entity fails to comply with a subrequirement of Requirement R1, or
when the entity lacks any evidence of
compliance.
300. NERC designated Requirement
R2 as a ‘‘binary’’ Requirement and
proposed a ‘‘lower’’ violation severity
level when an entity sets its relays
pursuant to sub-requirements R1.6
through R1.9, R1.12, or R1.13, but lacks
evidence that it obtained the agreement
of the planning coordinator,
transmission operator, and reliability
coordinator as to the calculated circuit
capability.199
301. For Requirement R3, NERC
proposed: (1) A ‘‘severe’’ violation
severity level when an entity lacks a
process to identify critical facilities; and
(2) ‘‘moderate’’ and ‘‘high’’ violation
severity levels based on the number of
days that a planning coordinator is late
in providing the critical facilities list to
the entities that must receive it.
1. NOPR Proposal
302. In the NOPR, the Commission
listed the four guidelines that it uses to
evaluate proposed violation severity
levels (Violation Severity Level
Guidelines).200 According to these
Guidelines, violation severity levels
should: (1) Avoid the unintended
consequence of lowering the current
level of compliance; (2) ensure
uniformity and consistency among all
199 ‘‘Binary’’ Requirements are Requirements
where compliance is defined in terms of ‘‘pass’’ or
‘‘fail.’’
200 For a complete discussion of each guideline,
see North American Electric Reliability Corporation,
123 FERC ¶ 61,284, at P 19–36 (Violation Severity
Level Order), order on reh’g and compliance filing,
125 FERC ¶ 61,212 (2008) (Violation Severity Level
Rehearing Order).
PO 00000
Frm 00038
Fmt 4701
Sfmt 4700
approved Reliability Standards in the
determination of penalties; 201 (3) be
consistent with the corresponding
Requirement; and (4) be based on a
single violation, not on a cumulative
number of violations.
303. The Commission observed that
the violation severity levels assigned to
Requirements R1 and R2 appear to be
inconsistent with Violation Severity
Level Guideline 3. The Commission
noted that the two violation severity
levels proposed for Requirement R1
address both: (1) The severity of a
violation (i.e., the fact that relay settings
do not comply with Requirement R1);
and (2) facts necessarily associated with
evaluating compliance (i.e., the
existence of evidence that relay settings
comply with Requirement R1). The
Commission explained that
Requirement R1 does not require
evidence of compliance, only
compliance. Similarly, the Commission
stated that the single violation severity
level proposed for Requirement R2 does
not reflect the severity of a violation of
Requirement R2, but the severity of
lacking evidence of compliance with
Requirement R2. Consequently, the
Commission proposed to direct the ERO
to: (1) Adopt a binary approach to
Requirement R1; i.e., assign a violation
severity level based on whether or not
the entity complies with Requirement
R1; and (2) assign a violation severity
level for Requirement R2 that addresses
an entity’s failure to comply with the
entire Requirement; i.e., its failure to
calculate circuit capability as the facility
rating and obtain agreement on that
rating with the required entities. The
Commission also proposed to direct the
ERO to assign a single violation severity
level to each sub-requirement in
Requirement R1.
201 In the Violation Severity Level Order, the
Commission identified two specific concerns with
the uniformity and consistency of the violation
severity level assignments then under review: (a)
The single violation severity levels assigned to
individual binary requirements were not consistent;
and (b) the violation severity level assignments
contained ambiguous language. With respect to
concern identified in (a), which the Commission
referred to as ‘‘Guideline 2a,’’ the Commission
explained that NERC assigned different violation
severity levels to different binary Requirements (i.e.
pass/fail Requirements) without justifying the
different assignments or explaining how they were
consistent with the application of a basic pass/fail
test. The Commission directed NERC to modify the
violation severity levels by either: (1) Consistently
applying the same severity level to each binary
Requirement; or (2) changing from a binary
approach to a gradated approach. Violation Severity
Level Order 123 FERC ¶ 61,284 at P 23–27, 45–47.
In its compliance filing, NERC chose the first option
and proposed to apply a ‘‘severe’’ violation severity
level to each of the binary Requirements. The
Commission agreed with this approach. North
American Electric Reliability Corporation, 127
FERC ¶ 61,293, at P 5, 11 (2009).
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
304. The Commission also stated that
the single violation severity level
assigned to Requirement R2 appears to
be inconsistent with NERC’s Guideline
2a compliance filing in Docket No.
RR08–4–004.202 The Commission
explained that, in that docket, NERC
assigned ‘‘severe’’ violation severity
levels to binary Requirements. The
Commission added that it expects the
violation severity levels assigned to
binary requirements to be consistent,
and proposed to direct the ERO to revise
the violation severity level assigned to
Requirement R2 to be consistent with
Guideline 2a.
305. Finally, in light of its proposals
to direct the ERO to modify
Requirement R3 and its subrequirements, the Commission proposed
to direct the ERO to assign new
violation severity levels to Requirement
R3 and its sub-requirements, consistent
with the Violation Severity Level
Guidelines.
2. Comments
306. NERC agrees with the
Commission’s proposal to review the
violation severity levels in accordance
with the Violation Severity Level
Guidelines.203 Other commenters
oppose the Commission’s proposal to
assign a violation severity level to each
sub-requirement in Requirement R1 for
the same reasons that they oppose
assigning a violation risk factor to each
sub-requirement in Requirement R1.
307. Consumers Energy makes the
general argument that ‘‘evidence’’ should
be included in Requirements only when
the compliance monitor (e.g., the
Regional Entity or NERC) uses it for a
reliability purpose. Consumers Energy
argues that if evidence is used only to
determine whether an entity is in
compliance with a Reliability Standard,
the evidence should be instead
represented in a Measure as reflected in
PRC–023–1.
mstockstill on DSKH9S0YB1PROD with RULES2
3. Commission Determination
308. We adopt the NOPR proposals
with respect to the violation severity
levels assigned to Requirements R1 and
R2. As we explained in the NOPR, the
violation severity levels assigned to
Requirement R1 are inconsistent with
Violation Severity Guideline 3 because
they are based in part on the amount of
evidence of compliance that an entity
can produce, even though Requirement
R1 does not require entities to have
evidence of compliance. Consequently,
we direct the ERO to assign a single
202 See
supra n. 202.
Comments at 40.
203 NERC
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
violation severity level of ‘‘severe’’ for
violations of Requirement R1.
309. While we adopt the NOPR
proposal with respect to Requirement
R1, we do not adopt the NOPR proposal
to direct the ERO to assign individual
violation severity levels to the subrequirements of Requirement R1. As we
explained with respect to the violation
risk factors, we will make an exception
to our general policy because we are
satisfied that the sub-requirements of
Requirement R1 do not constitute
independent compliance requirements
separate from Requirement R1.204
310. We also adopt the NOPR
proposal with respect to the violation
severity level assigned to Requirement
R2. As the Commission pointed out in
the NOPR, the single violation severity
level assigned to Requirement R2 suffers
from the same problem as the two
violation severity levels assigned to
Requirement R1; namely, it is based in
part on whether an entity has evidence
of compliance with the Requirement,
even though the Requirement itself does
not require an entity to have evidence
of compliance. Additionally,
Requirement R2 is a binary
Requirement, and NERC’s assignment of
a ‘‘lower’’ violation severity level rather
than a ‘‘severe’’ violation severity level is
inconsistent with its Guideline 2a
compliance filing in Docket No. RR08–
4–004. In that filing, NERC assigned a
‘‘severe’’ violation severity level to
binary Requirements. As the
Commission stated when discussing
Guideline 2a in the Violation Severity
Level Order, single violation severity
levels assigned to binary requirements
should be consistent. Accordingly, we
direct the ERO to change the violation
severity level assigned to Requirement
R2 from ‘‘lower’’ to ‘‘severe’’ to be
consistent with Guideline 2a.
311. Finally, we direct the ERO to
assign a ‘‘severe’’ violation severity level
to Requirement R3. Requirement R3
directs planning coordinators to identify
the critical sub-200 kV facilities that are
subject to the Reliability Standard.
Similar to our determination for
Requirement R2, it is our view that
Requirement R3 is a binary requirement;
either the planning coordinator
identified critical facilities or it did not.
Consequently, we find that Requirement
R3 must have a single violation severity
level of ‘‘severe.’’
312. We direct the ERO to file the new
violation severity levels described in
204 Consistent with our treatment of violation risk
factors, we direct the ERO to re-file the violation
severity factors associated with the Requirements of
PRC–023–1 when it submits its comprehensive
plan.
PO 00000
Frm 00039
Fmt 4701
Sfmt 4700
16951
our discussion no later than 30 days
after the date of this Final Rule.
M. Miscellaneous
1. Purpose of the Reliability Standard
313. The Reliability Standard’s stated
purpose is to ‘‘require[] certain
transmission owners, generator owners,
and distribution providers to set
protective relays according to specific
criteria in order to ensure that the relays
reliably detect and protect the electric
network from all fault conditions, but
do not limit transmission loadability or
interfere with system operators’ ability
to protect system reliability.’’
a. Comments
314. BPA argues that the Commission
should direct the ERO to revise the
Reliability Standard’s stated purpose
because the Standard requires only that
certain protective relays refrain from
operating during permissible load
conditions and does not require that
protective relays reliably detect and
protect the electric network from all
fault conditions. BPA asserts that subrequirement R1.12 touches on the
subject of adequately detecting faults by
allowing the loadability requirements of
relay settings to be relaxed in order to
allow adequate protection, but adds that
neither sub-requirement R1.12 nor any
other sub-requirement requires relays to
be set to reliably detect ‘‘all’’ fault
conditions and protect the electrical
network from these faults. BPA argues
that the class of relays covered by the
Reliability Standard is not even capable
of detecting ‘‘all’’ fault conditions. BPA
requests, therefore, that the Commission
direct the ERO to revise the Reliability
Standard’s stated purpose to be: ‘‘[t]o
prevent certain protective relays from
operating under permissible
transmission line and equipment
loads.’’ 205
b. Commission Determination
315. We disagree with BPA.
Requirement R1 directs entities to set
their relays according to one of its subrequirements (R1.1 through R1.13),
based on their transmission
configurations. No matter what setting
entities choose, they are required to
apply it while ‘‘maintaining reliable
protection of the bulk electric system for
all fault conditions.’’ Thus, any subrequirement that an entity implements
must protect the electric network from
all fault conditions.
205 BPA
E:\FR\FM\02APR2.SGM
at 1–2.
02APR2
16952
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
2. Transmission Facility Design Margin
a. Comments
316. Basin interprets the
Commission’s statement in the NOPR
that ‘‘[s]ub-requirement R1.1 specifies
transmission line relay settings based on
the highest seasonal facility rating using
the 4-hour thermal rating of a line, plus
a design margin of 150 percent’’ to
suggest that the Commission incorrectly
assumed that relay margins include an
additional transmission facility design
margin, and that additional Total
Transfer Capability (TTC) can be
achieved with different relay settings.
Basin states that relay operations do not
affect the calculation of TTC because
relay settings are established above the
level of standard operation of the system
and will not operate when facilities are
loaded at their maximum ratings.
b. Commission Determination
317. We clarify that the Commission
did not assume that ‘‘design margin,’’ as
it is used in the context of the
Reliability Standard, equates to
additional TTC on the transmission
facility. The statement in the NOPR that
Basin refers to is a direct quote from
NERC where NERC describes ‘‘design
margin’’ in the context of the margin
(percentage) over the 4-hour facility
rating protective relay setting criteria for
sub-requirement R1.1.206 The ‘‘design
margin’’ described in this requirement is
different than the ‘‘transmission
reliability margin’’ that accounts for the
inherent uncertainty in bulk electric
system conditions in the calculation of
TTC established in the Modeling, Data,
and Analysis (MOD) Reliability
Standards.
IV. Information Collection Statement
318. The Office of Management and
Budget (OMB) regulations require that
OMB approve certain reporting and
recordkeeping (collections of
information) imposed by an agency.207
The information collection requirements
in this Final Rule are identified under
the Commission data collection, FERC–
725G ‘‘Transmission Relay Loadability
Mandatory Reliability Standard for the
Bulk Power System.’’ Under section
3507(d) of the Paperwork Reduction Act
of 1995,208 the proposed reporting
requirements in the subject rulemaking
will be submitted to OMB for review.
Interested persons may obtain
information on the reporting
requirements by contacting the Federal
Energy Regulatory Commission, 888
First Street, NE., Washington, DC 20426
(Attention: Michael Miller, Office of the
Executive Director, 202–502–8415) or
from the Office of Management and
Budget (Attention: Desk Officer for the
Federal Energy Regulatory Commission,
fax: 202–395–7285, e-mail:
oira_submission@omb.eop.gov).
319. The ‘‘public protection’’
provisions of the Paperwork Reduction
Act of 1995 requires each agency to
display a currently valid control number
and inform respondents that a response
is not required unless the information
collection displays a valid OMB control
number on each information collection
or provides a justification as to why the
Number of
respondents
Data collection
FERC–725G:
M1—TOs, GOs and DPs must ‘‘have evidence’’ to
show that each of its transmission relays are set according to Requirement R1.
Number of
responses
information collection number cannot
be displayed. In the case of information
collections published in regulations, the
control number is to be published in the
Federal Register.
320. Public Reporting Burden: In the
NOPR, the Commission based its
estimate of the Public Reporting Burden
on the NERC Compliance Registry, as of
March 3, 2009, and on NERC’s July 30,
2008 petition for approval of PRC–023–
1. The Commission stated that, as of
March 3, 2009, NERC had registered in
its Compliance Registry: (1) 568
distribution providers; (2) 825 generator
owners; (3) 324 transmission owners;
and (4) 79 planning authorities. The
Commission also noted that the
Reliability Standard does not apply to
all transmission owners, generator
owners, and distribution providers, but
only to those with load-responsive
phase protection systems as described
in Attachment A of the Standard,
applied to all transmission lines and
transformers with low-voltage terminals
operated or connected at 200 kV and
above and between 100 kV and 200 kV
as identified by the planning
coordinator as critical to the reliability
of the bulk electric system. The
Commission further noted that some
entities are registered for multiple
functions, so there is some overlap
between the entities registered as
distribution providers, transmission
owners, and generator owners. Given
these parameters, the Commission
estimated the Public Reporting Burden
as follows:
Hours per respondent
Total annual hours
1
Reporting: 0 ...................
Reporting: 0.
M2—Certain TOs, GOs and DPs must have evidence
that a facility rating was agreed to by PA, TOP and
RC.
166
1
Recordkeeping: 100 .......
Reporting: 0 ...................
Recordkeeping: 45,000.
Reporting: 0.
M3—PC must document process for determining critical facilities and (2) a current list of such facilities.
79
1
Recordkeeping: 10 .........
175 .................................
Recordkeeping: 1,660.
13,825.
Total .........................................................................
mstockstill on DSKH9S0YB1PROD with RULES2
450
........................
........................
........................................
60,485.
Based on the available information
from the compliance registry, the
Commission estimated that 525 entities
would be responsible for compliance
with the Reliability Standard.209 The
Commission also estimated that it
would require 60,485 total annual hours
Petition at 9.
CFR 1320.11.
for collection (reporting and
recordkeeping) and that the average
annualized cost of compliance would be
$2,419,400 ($40/hour for 60,485 hours;
the Commission based the $40/hour
estimate on $17/hour for a file/record
clerk and $23/hour for a supervisor).210
206 NERC
208 44
207 5
209 NOPR,
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
PO 00000
U.S.C. 3507(d).
FERC Stats. & Regs. ¶ 32,642 at P 117.
Frm 00040
Fmt 4701
Sfmt 4700
321. Several commenters express
concern with the burden to be imposed
by the Reliability Standard. Some of
these comments address the Reliability
Standard’s potential impact on small
entities; because these comments are
also the subject of the analysis
210 BPA notes that the NOPR erroneously showed
this figure as $241,940 rather than $2,419,400.
E:\FR\FM\02APR2.SGM
02APR2
mstockstill on DSKH9S0YB1PROD with RULES2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
performed under the Regulatory
Flexibility Act, the Commission has
provided a response under that section
of this rulemaking. Other comments
question the Commission’s initial
burden estimate.
322. APPA argues that the
Commission has grossly underestimated
the Public Reporting Burden and
requests that the Commission develop a
more accurate estimate. APPA notes that
the Commission provided a breakdown
by category of registered entities for a
total of 1,717 entities, but then asserts
that only 525 entities will be subject to
PRC–023–1 as proposed by NERC.
APPA states that it cannot assess how
the Commission came up with this
lower number, as the Commission
provided no explanation of its
methodology or the data it used to reach
this conclusion. APPA states that the
Commission’s initial estimate appears to
be based on the Reliability Standard as
proposed by NERC, and therefore fails
to account for the Commission’s
proposals to expand the Standard’s
applicability. APPA argues that the
Commission must assess the Public
Reporting Burden created by its
proposals.
323. APPA also claims that the
Commission’s estimate of labor costs is
so low as to be completely erroneous for
burden evaluation purposes. Based on
an informal survey of its members that
own or operate transmission facilities
above 100 kV, APPA states that 21 out
of nearly 300 registered public power
utilities would need to evaluate 791
terminals to comply with the
Commission’s proposals. At an
estimated cost of between $500 and
$1,200 per location, APPA estimates
that the cost of compliance for these 21
members would be between $395,500
and $949,200; the Commission
estimated $2,419,400 for the entire
industry. APPA adds that entities will
need seasoned and expensive electrical
engineers and outside consultants to
comply with the Commission’s
proposals, not file/record clerks who are
paid $17 per hour or supervisory
personnel who are paid $23 per hour.
APPA reports that one of its members
estimates that it would have to use
engineers, managers and even directorlevel personnel to carry out the required
tasks, at an estimated cost of $55–$75
per hour. APPA expects that the cost of
external consultants could reach $200
per hour.
324. BPA states that the loaded cost
for an engineer is approximately $80 per
hour, twice the $40 per hour the
Commission estimated for a file clerk
and a supervisor. BPA observes that this
would double the estimated annual cost
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
of the Reliability Standard to
$4,838,800. BPA also questions the
estimate of 100 hours annually for each
respondent to comply with Requirement
R1. BPA states that it could take
thousands of hours for larger utilities.
325. EEI argues that the Commission’s
estimate of hours for reporting and
recordkeeping substantially
underestimates the actual cost, in both
time and money, required to comply
with the Commission’s modifications.
EEI reports that one smaller investorowned utility has estimated that it
would take 4–8 hours of engineering
time, per relay terminal, to review the
more than 850 line terminals on its
system operated between 100 kV and
200 kV. EEI states that it would take an
additional 6–12 hours of engineering
time per terminal if, as the utility
expects, about one third of its line
terminals require mitigation, and
another 6–12 hours of operations and
maintenance staff hours to implement
relay settings for terminals requiring
mitigation.
326. EEI asserts that it could cost
$40,000 to replace each terminal in
order to comply with the Commission’s
modifications. EEI states that there are
more than 100,000 line terminals in the
U.S. on facilities between 100 kV and
200 kV that would have to be checked
if the Commission adopts a ‘‘rule out’’
approach. EEI estimates that this review
could take 1.5 million labor hours, and
another 750,000 hours if just one-half of
the terminals must be replaced. EEI
states that the aggregate cost to replace
these terminals could exceed $2.4
billion.
327. Given the Commission’s decision
not to adopt the ‘‘rule out’’ approach,
most of these comments are no longer
relevant. However, in response to the
comments that remain relevant, and
upon further review, we have revised
our initial estimates as reflected below.
Information Collection Costs: The
Commission sought comments about the
information collection costs needed to
comply with PRC–023–1. Since many of
the comments the Commission received
estimated costs based on the ‘‘rule out’’
approach, they are no longer applicable
given our decision in this Final Rule not
to require the ‘‘rule out’’ approach.
However, some commenters argue, apart
from the ‘‘rule out’’ approach, that the
NOPR underestimated the hours
required to comply and the estimated
cost of labor. After further
consideration, with respect to the costs
of labor, we agree that the $40/hour
estimate for file/record clerks and
supervisory employees is not correct.
We also agree with commenters that
electrical engineers will be required to
PO 00000
Frm 00041
Fmt 4701
Sfmt 4700
16953
comply with PRC–023–1. Therefore, we
have revised estimates as indicated
below:
• Number of line terminals to be
reviewed: 53,000.
• Number of hours per terminal: 6.4.
• Hourly rate for review by engineers:
$120.
Total Cost for review = (terminals to be
reviewed × hours per terminal) × hourly
rate for review by engineers = (53,000 ×
6.4) × ($120/hour) = 339,200 hours ×
120/hour = $40,704,000.
Sources
• Title: FERC–725–G ‘‘Mandatory
Reliability Standard for Transmission
Relay Loadability.’’
• Action: Proposed Collection of
Information.
• OMB Control No: [To be
determined.]
• Respondents: Business or other for
profit, and/or not for profit institutions.
• Frequency of Responses: On
Occasion.
• Necessity of the Information: The
Transmission Relay Loadability
Reliability Standard, if adopted, would
implement the Congressional mandate
of the Energy Policy Act of 2005 to
develop mandatory and enforceable
Reliability Standards to better ensure
the reliability of the nation’s BulkPower System. Specifically, the
proposed Reliability Standard would
ensure that protective relays are set
according to specific criteria to ensure
that relays reliably detect and protect
the electric network from all fault
conditions, but do not limit
transmission loadability or interfere
with system operator’s ability to protect
system reliability.
328. Interested persons may obtain
information on the reporting
requirements by contacting: Federal
Energy Regulatory Commission, 888
First Street, NE., Washington, DC 20426
[Attention: Michael Miller, Office of the
Executive Director, Phone: (202) 502–
8415, fax: (202) 273–0873, e-mail:
michael.miller@ferc.gov]. Comments on
the requirements of the proposed rule
may also be sent to the Office of
Information and Regulatory Affairs,
Office of Management and Budget,
Washington, DC 20503 [Attention: Desk
Officer for the Federal Energy
Regulatory Commission], e-mail:
oira_submission@omb.eop.gov.
V. Environmental Analysis
329. The Commission is required to
prepare an Environmental Assessment
or an Environmental Impact Statement
for any action that may have a
significant adverse effect on the human
E:\FR\FM\02APR2.SGM
02APR2
16954
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
environment.211 The Commission has
categorically excluded certain actions
from this requirement as not having a
significant effect on the human
environment. The actions proposed here
fall within the categorical exclusion in
the Commission’s regulations for rules
that are clarifying, corrective or
procedural, for information gathering,
analysis, and dissemination.212
Accordingly, neither an environmental
impact statement nor environmental
assessment is required.
VI. Regulatory Flexibility Act
mstockstill on DSKH9S0YB1PROD with RULES2
330. The Regulatory Flexibility Act of
1980 (RFA) 213 generally requires a
description and analysis of any final
rule that will have significant economic
impact on a substantial number of small
entities. The RFA does not mandate any
particular outcome in a rulemaking, but
rather requires consideration of
alternatives that are less burdensome to
small entities and an agency
explanation of why alternatives were
rejected.
331. In drafting a rule, an agency is
required to: (1) Assess the effect that its
regulation will have on small entities;
(2) analyze effective alternatives that
may minimize a regulation’s impact;
and (3) make the analyses available for
public comment.214 In its NOPR, the
agency must either include an Initial
Regulatory Flexibility Act Analysis
(Initial Analysis) 215 or certify that the
proposed rule will not have a
‘‘significant impact on a substantial
number of small entities.’’216
332. If, in preparing the NOPR, an
agency determines that the proposal
could have a significant impact on a
substantial number of small entities, the
agency shall ensure that small entities
will have an opportunity to participate
in the rulemaking procedure.217
333. In its Final Rule, the agency must
also either prepare a Final Regulatory
Flexibility Act Analysis (Final Analysis)
or make the requisite certification.
Based on the comments the agency
receives on the NOPR, it can alter its
original position as expressed in the
NOPR but it is not required to make any
substantive changes to the proposed
regulation.
334. The statute provides for judicial
review of an agency’s final RFA
211 Order No. 486, Regulations Implementing the
National Environmental Policy Act, 52 FR 47,897
(Dec. 17, 1987), FERC Stats. & Regs. ¶ 30,783 (1987).
212 18 CFR 380.4(a)(5) (2009).
213 5 U.S.C. 601–612.
214 5 U.S.C. 601–604.
215 5 U.S.C. 603(a).
216 5 U.S.C. 605(b).
217 5 U.S.C. 609(a).
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
certification or Final Analysis.218 An
agency must file a Final Analysis
demonstrating a ‘‘reasonable, good-faith
effort’’ to carry out the RFA mandate.219
However, the RFA is a procedural, not
a substantive, mandate. An agency is
only required to demonstrate a
reasonable, good faith effort to review
the impact the proposed rule would
place on small entities, any alternatives
that would address the agency’s and
small entities’ concerns and their
impact, provide small entities the
opportunity to comment on the
proposals, and review and address
comments. An agency is not required to
adopt the least burdensome rule.
Further, the RFA does not require an
agency to assess the impact of a rule on
all small entities that may be affected by
the rule, only on those entities that the
agency directly regulates and that are
subject to the requirements of the
rule.220
A. NOPR Proposal
335. In the NOPR, the Commission
asserted that most of the entities, i.e.,
transmission owners, generator owners,
distribution providers, and ‘‘planning
coordinators,’’ or alternatively ‘‘planning
authorities,’’ to which the requirements
of this rule will apply, do not fall within
the applicable definition of ‘‘small
entities.’’ The Commission also stated
that, based on available information
regarding NERC’s compliance registry,
approximately 525 entities will be
responsible for compliance with the
new Reliability Standard. Consequently,
the Commission certified that the
Reliability Standard will not have a
significant adverse impact on a
substantial number of small entities and
that no RFA analysis was required.
B. Comments
336. APPA, TAPS, NRECA, and
SWTDUG argue that the ‘‘rule out’’
approach for 100 kV–200 kV facilities
and the ‘‘add in’’ approach for sub-100
kV facilities will cause the Reliability
Standard to have a significant adverse
impact on a substantial number of small
entities.
337. NRECA argues that the
Commission’s Initial Analysis is
inadequate and its conclusion
premature given the Commission’s
proposals to expand the Reliability
Standard’s applicability. NRECA argues
that the Commission cannot develop an
adequate Final Analysis without an
218 5
U.S.C. 611.
Cellular Corp. v. FCC, 254 F.3d 78, 88
(DC Cir. 2001); Alenco Commc’ns, Inc. v. FCC, 201
F.3d 608, 625 (5th Cir. 2000).
220 Mid-Tex Elec. Coop., Inc. v. FERC, 773 F.2d
327 (DC Cir. 1985).
219 United
PO 00000
Frm 00042
Fmt 4701
Sfmt 4700
Initial Analysis that lays the proper
foundation for eliciting comments and
seeking information. APPA argues that
the Commission’s Initial Analysis is
flawed and fails to: (1) Assess the effect
the regulation will have on small
entities; (2) analyze effective
alternatives that might minimize the
regulation’s impact; and (3) make such
an analysis available for public
comment.
338. APPA and NRECA also argue
that the Commission failed to: (1)
Provide its basis for claiming that only
525 entities from the NERC Compliance
Registry will be required to comply with
the Reliability Standard; (2) justify its
assertion that the majority of the
expected 525 entities required to
comply do not qualify as small entities
under the Small Business Act; (3) state
how many of the 525 affected entities
are small entities; and (4) identify the
registered entities that are required to
comply. APPA argues that the
Commission’s expectation that 525
facilities will be required to comply
with the Reliability Standard is based
on the Reliability Standard as proposed
by NERC, and does not account for the
Commission’s potentially broader
applicability proposals. APPA states
that 261 of its members are registered
entities and qualify as small entities.
NRECA adds that a substantial majority
of its approximately 930 rural electric
cooperative members are small entities
that would be adversely impacted by the
proposed rule.
339. TAPS argues that the ‘‘rule out’’
approach will increase the burden on
small systems and may force the
Commission to depart from the
Compliance Registry criteria that formed
the basis for its RFA certification in
Order No. 693. TAPS explains that if the
‘‘rule out’’ approach will make all 100
kV facilities subject to the Reliability
Standard, including radial transmission
lines, then the Standard will apply to
unregistered small entities that have not
previously been considered part of the
bulk electric system and therefore do
not appear on the Compliance Registry
that served as the basis for the
Commission’s small entity impacts
analysis.
C. Commission Determination
340. As discussed previously in this
Final Rule, the Commission will not
adopt the NOPR proposal to make PRC–
023 applicable to all facilities operated
at or above 100 kV, ‘‘ruling out’’ those
facilities that would not demonstrably
result in cascading outages, instability,
uncontrolled separation, violation of
facility ratings, or interruption of firm
transmission service. Accordingly, to
E:\FR\FM\02APR2.SGM
02APR2
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
the extent that the Commission has
decided to abandon the ‘‘rule out’’
approach in favor of an ‘‘add-in’’
approach, as discussed in previous
portions of this Final Rule, the
Commission expects that many of the
concerns and impact estimates
submitted by commenters are moot or
no longer accurate.
341. Nonetheless, the Commission
does find it appropriate to address
commenters’ concern regarding the
number of entities that the Commission
estimates will be subject to PRC–023–1
as proposed by NERC. Based on the
Compliance Registry dated November
30, 2009, there are 573 entities
registered as Distribution Providers, 821
entities registered as Generator Owners,
323 entities registered as Transmission
Owners, and 80 entities registered as
Planning Authorities. However, the
Commission notes that some entities are
registered for multiple functions, and
therefore recognizes that there is some
overlap between the entities registered
as a Distribution Provider, Transmission
Owner, Generator Owner, and/or
Planning Authority. Therefore, after
eliminating any duplicative
registrations, the Commission finds that
there are 1301 entities that are registered
as engaging in one or more of the
applicable functions within the scope of
PRC–023–1.
342. Reliability Standard PRC–023–1
applies to Transmission Owners,
Generator Owners, and Distribution
Providers with load-responsive phase
protection systems as described in
Attachment A of the Reliability
Standard, applied to facilities defined in
requirements 4.1.1 through 4.1.4.221 The
Reliability Standard applies to facilities
100 kV and above and to transformers
with low-voltage terminals 200 kV and
above. Because there are no commercial
generators with a terminal voltage as
high as 100 kV and all generator step-
up and auxiliary power transformers
have low-voltage windings well below
200 kV, PRC–023–1 excludes generators
and all generator step-up and auxiliary
transformers. Therefore, no generator
owner that is not also a transmission
owner and/or a distribution provider
will be subject to PRC–023–1.
Accordingly, the Commission calculates
that the potential applicability of the
Final Rule may be reduced by 623,
which is the total number of entities
registered solely as a generator owner.
Thus, the Commission anticipates that
the Final Rule will apply to
approximately 678 entities overall.222
343. According to the Department of
Energy’s Energy Information
Administration (EIA), there were 3271
electric utility companies in the United
States in 2007,223 and approximately
3012 of these electric utilities qualify as
small entities under the Small Business
Act (SBA) definition.224 Of those 3012
small entities, only 80 entities also
appear in the NERC Compliance
Registry. Accordingly, the Commission
estimates that the Reliability Standard
will affect a maximum of 80 SBUs, or
approximately 12 percent of those
entities estimated to be subject to the
requirements of the Final Rule.
344. Based upon on this revised
analysis, we certify that this Final Rule
will not have a significant economic
impact on a substantial number of small
entities. Accordingly, no further RFA
analysis is required.
VII. Document Availability
345. In addition to publishing the full
text of this document in the Federal
Register, the Commission provides all
interested persons an opportunity to
view and/or print the contents of this
document via the Internet through
FERC’s Home Page (https://www.ferc.gov)
and in FERC’s Public Reference Room
during normal business hours (8:30 a.m.
16955
to 5 p.m. Eastern time) at 888 First
Street, NE., Room 2A, Washington, DC
20426.
346. From FERC’s Home Page on the
Internet, this information is available on
eLibrary. The full text of this document
is available on eLibrary in PDF and
Microsoft Word format for viewing,
printing, and/or downloading. To access
this document in eLibrary, type the
docket number excluding the last three
digits of this document in the docket
number field.
347. User assistance is available for
eLibrary and the FERC’s Web site during
normal business hours from FERC
Online Support at 202–502–6652 (toll
free at 1–866–208–3676) or e-mail at
ferconlinesupport@ferc.gov, or the
Public Reference Room at (202) 502–
8371, TTY (202) 502–8659. E-mail the
Public Reference Room at
public.referenceroom@ferc.gov.
VIII. Effective Date and Congressional
Notification
348. These regulations are effective 45
days from publication in Federal
Register for non-major rules and 60 days
from the later of the date Congress
receives the agency notice or the date
the rule is published in the Federal
Register. The Commission has
determined, with the concurrence of the
Administrator of the Office of
Information and Regulatory Affairs of
OMB, that this rule is not a ‘‘major rule’’
as defined in section 351 of the Small
Business Regulatory Enforcement
Fairness Act of 1996.
List of Subjects in 18 CFR Part 40
By the Commission.
Kimberly D. Bose,
Secretary.
Note: The following Appendix will not
appear in the Code of Federal Regulations.
APPENDIX A—COMMENTERS
mstockstill on DSKH9S0YB1PROD with RULES2
Abbreviation
Commenter
Alcoa ...............................................................
Ameren ...........................................................
APPA ..............................................................
ATC ................................................................
Austin Energy .................................................
Basin ...............................................................
BPA ................................................................
California Commission ...................................
City Utilities of Springfield ..............................
221 As proposed, the Commission notes PRC–023–
1 is applicable to Generator Owners with loadresponsive phase protection systems as described in
Attachment A, applied to facilities defined in 4.1.1
through 4.1.4., however, excludes generator
protection relays that are susceptible to load in
Section (3) of Attachment A.
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
Alcoa, Inc.
Ameren Services Company.
American Public Power Association.
American Transmission Company, LLC.
City of Austin, Texas.
Basin Electric Cooperative.
Bonneville Power Administration.
Public Utilities Commission of the State of California.
City Utilities of Springfield, Missouri.
222 The Commission derives this result by using
the following equation: 1301 applicable entities
(entities registered as one of more of the following
functions: Distribution Provider, Transmission
Owner, Generator Owner, and Planning
Authority)—623 entities registered solely as a
Generator Owner = 678.
PO 00000
Frm 00043
Fmt 4701
Sfmt 4700
223 See U.S. Energy Information Administration,
Form EIA–861, Dept. of Energy (2007), available at
https://www.eia.doe.gov/cneaf/electricity/page/
eia861.html.
224 According to the SBA, a small electric utility
is defined as one that has a total electric output of
less than four million MWh in the preceeding year.
E:\FR\FM\02APR2.SGM
02APR2
16956
Federal Register / Vol. 75, No. 63 / Friday, April 2, 2010 / Rules and Regulations
APPENDIX A—COMMENTERS—Continued
Abbreviation
Commenter
Consumers Energy .........................................
CRC ................................................................
Dominion ........................................................
Duke ...............................................................
EEI ..................................................................
ElectriCities .....................................................
Entergy ...........................................................
E.ON ...............................................................
EPSA ..............................................................
ERCOT ...........................................................
Exelon .............................................................
Fayetteville Public Works Commission ..........
Filing Cooperatives .........................................
Consumers Energy Company.
Colorado River Commission of Nevada.
Dominion Resources, Inc.
Duke Energy Corporation.
Edison Electric Institute.
ElectriCities of North Carolina, Inc.
Entergy Services, Inc.
E.ON U.S. LLC.
Electric Power Supply Association.
Electric Reliability Council of Texas, Inc.
Exelon Corporation.
Fayetteville Public Works Commission.
Mohave Electric Cooperative, Inc., Trico Electric Cooperative, inc., Navopache Electric Cooperative, Inc., and Sulphur Springs Valley Electric Cooperative, Inc.
Georgia Transmission Corporation.
Independent Electricity System Operator and Hydro One Networks Inc.
The ISO/RTO Council.
ISO New England Inc.
International Transmission Company.
Independent Electricity System Operator, PJM Interconnection L.L.C., Southwest Power Pool,
and Midwest Independent Transmission Operator.
Lincoln Electric System.
Manitoba Hydro.
Michael McDonald.
Mississippi Delta Energy Agency, Clarksdale Public Utilities Commission of the City of Clarksdale, Mississippi, and the Public Service Commission of Yazoo City of the City of Yazoo City,
Mississippi.
Municipal Electric Authority of Georgia.
National Association of Regulatory Utility Commissioners.
North American Electric Reliability Corporation.
New York State Public Service Commission.
National Rural Electric Cooperative Association.
NV Energy.
Northern Wasco County People’s Utility District.
Oncor Electric Delivery Company LLC.
Ontario Power Generation Inc.
PacifiCorp.
Washington Utilities and Transportation Commission, Idaho Public Utilities Commission, Public
Utility Commission of Oregon, and Montana Public Service Commission.
City of Palo Alto, California.
Pacific Gas & Electric Company.
Portland General Electric Company.
Public Service Electric & Gas Company, PSEG Energy Resources & Trade LLC, PSEG Power
LLC.
Public Power Council.
Seattle City Light.
Cities of Anaheim, Azusa, Banning, Colton, Pasadena, and Riverside, California.
Southern California Edison Company.
South Carolina Electric & Gas Company.
Southern Company Services, Inc.
Salt River Project Agricultural Improvement and Power District.
Southwest Transmission Dependent Utility Group.
Transmission Agency of Northern California.
Transmission Access Policy Study Group.
Tri-State Generation & Transmission Association.
Tennessee Valley Authority.
Western Area Power Administration-Rocky Mountain Region.
Western Electricity Coordinating Council Relay Work Group.
Y–W Electric Association, Inc.
Georgia Transmission ....................................
IESO/Hydro One ............................................
IRC .................................................................
ISO New England ...........................................
ITC ..................................................................
Joint Commenters ..........................................
LES .................................................................
Manitoba Hydro ..............................................
McDonald .......................................................
MDEA Cities ...................................................
MEAG .............................................................
NARUC ...........................................................
NERC .............................................................
New York Commission ...................................
NRECA ...........................................................
NV Energy ......................................................
NWCP .............................................................
Oncor ..............................................................
Ontario Generation .........................................
PacifiCorp .......................................................
Pacific Northwest State Commissions ...........
Palo Alto .........................................................
PG&E ..............................................................
Portland General ............................................
PSEG Companies ..........................................
Public Power Council .....................................
Seattle City Light ............................................
Six California Cities ........................................
SoCalEd .........................................................
South Carolina E&G .......................................
Southern .........................................................
SRP ................................................................
SWTDUG ........................................................
TANC ..............................................................
TAPS ..............................................................
Tri-State ..........................................................
TVA .................................................................
WAPA–RMR ...................................................
WECC .............................................................
Y–WEA ...........................................................
mstockstill on DSKH9S0YB1PROD with RULES2
[FR Doc. 2010–6568 Filed 4–1–10; 8:45 am]
BILLING CODE 6717–01–P
VerDate Nov<24>2008
16:46 Apr 01, 2010
Jkt 220001
PO 00000
Frm 00044
Fmt 4701
Sfmt 9990
E:\FR\FM\02APR2.SGM
02APR2
Agencies
[Federal Register Volume 75, Number 63 (Friday, April 2, 2010)]
[Rules and Regulations]
[Pages 16914-16956]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2010-6568]
[[Page 16913]]
-----------------------------------------------------------------------
Part II
Department of Energy
-----------------------------------------------------------------------
Federal Energy Regulatory Commission
-----------------------------------------------------------------------
18 CFR Part 40
Transmission Relay Loadability Reliability Standard; Final Rule
Federal Register / Vol. 75 , No. 63 / Friday, April 2, 2010 / Rules
and Regulations
[[Page 16914]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
Federal Energy Regulatory Commission
18 CFR Part 40
[Docket No. RM08-13-000; Order No. 733]
Transmission Relay Loadability Reliability Standard
March 18, 2010.
AGENCY: Federal Energy Regulatory Commission.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: Pursuant to section 215 of the Federal Power Act, the Federal
Energy Regulatory Commission approves the Transmission Relay
Loadability Reliability Standard (PRC-023-1), developed by the North
American Electric Reliability Corporation (NERC). Reliability Standard
PRC-023-1 requires transmission owners, generator owners, and
distribution providers to set load-responsive phase protection relays
according to specific criteria in order to ensure that the relays
reliably detect and protect the electric network from all fault
conditions, but do not limit transmission loadability or interfere with
system operators' ability to protect system reliability. In addition,
pursuant to section 215(d)(5) of the Federal Power Act, the Commission
directs NERC to develop modifications to the Reliability Standard to
address specific concerns identified by the Commission.
DATES: Effective Date: This rule will become effective May 17, 2010.
FOR FURTHER INFORMATION CONTACT:
Cynthia Pointer (Technical Information), Office of Electric
Reliability, Division of Reliability Standards, Federal Energy
Regulatory Commission, 888 First Street, NE., Washington, DC 20426.
(202) 502-6069.
Joshua Konecni (Legal Information), Office of the General Counsel,
Federal Energy Regulatory Commission, 888 First Street, NE.,
Washington, DC 20426. (202) 502-6291.
SUPPLEMENTARY INFORMATION:
Table of Contents
Paragraph
Nos.
I. Background............................................... 2
II. Reliability Standard PRC-023-1.......................... 5
A. Applicability........................................ 6
B. Requirements......................................... 8
1. Requirement R1................................... 9
2. Requirement R2................................... 10
3. Requirement R3................................... 11
III. Discussion............................................. 12
A. Overview............................................. 12
B. Approval of PRC-023-1................................ 13
C. Applicability........................................ 20
D. Generator Step-Up and Auxiliary Transformers......... 98
1. Omission From the Reliability Standard........... 98
2. Generator Step-Up Transformer Relays as Back-up 109
Protection.........................................
E. Need to Address Additional Issues.................... 115
1. Zone 3/Zone 2 Relays Applied as Remote Circuit 116
Breaker Failure and Backup Protection..............
2. Protective Relays Operating Unnecessarily due to 130
Stable Power Swings................................
F. Requirement R1....................................... 174
1. Sub-Requirement R1.1............................. 175
2. Sub-Requirement R1.2............................. 178
3. Sub-Requirement R1.10............................ 190
4. Sub-Requirement R1.12............................ 213
G. Requirement R2....................................... 227
H. Requirement R3 and Its Sub-Requirements.............. 230
1. Role of the Planning Coordinator................. 231
2. Sub-Requirement R3.3............................. 235
I. Attachment A......................................... 238
1. Section 2: Evaluation of Out-of-Step Blocking 239
Schemes............................................
2. Section 3: Protection Systems Excluded from the 249
Reliability Standard...............................
J. Effective Date....................................... 273
K. Violation Risk Factors............................... 285
L. Violation Severity Levels............................ 298
M. Miscellaneous........................................ 313
1. Purpose of the Reliability Standard.............. 313
2. Transmission Facility Design Margin.............. 316
IV. Information Collection Statement........................ 318
V. Environmental Analysis................................... 329
VI. Regulatory Flexibility Act.............................. 330
VII. Document Availability.................................. 345
VIII. Effective Date and Congressional Notification......... 348
Before Commissioners: Jon Wellinghoff, Chairman; Marc Spitzer,
Philip D. Moeller, and John R. Norris.
1. Pursuant to section 215 of the Federal Power Act (FPA),\1\ the
Commission approves the Transmission Relay Loadability Reliability
Standard (PRC-023-1), developed by the North American Electric
Reliability Corporation (NERC) in its capacity as the Electric
Reliability Organization
[[Page 16915]]
(ERO).\2\ Reliability Standard PRC-023-1 requires transmission owners,
generator owners, and distribution providers to set load-responsive
phase protection relays according to specific criteria in order to
ensure that the relays reliably detect and protect the electric network
from all fault conditions, but do not limit transmission loadability or
interfere with system operators' ability to protect system
reliability.\3\ In addition, pursuant to section 215(d)(5) of the
FPA,\4\ the Commission directs the ERO to develop modifications to PRC-
023-1 to address specific concerns identified by the Commission and
sets specific deadlines for these modifications.
---------------------------------------------------------------------------
\1\ 16 U.S.C. 824o. The Commission is not adding any new or
modified text to its regulations.
\2\ Section 215(e)(3) of the FPA directs the Commission to
certify an ERO to develop mandatory and enforceable Reliability
Standards, subject to Commission review and approval. 16 U.S.C.
824o(e)(3). Following a selection process, the Commission selected
and certified NERC as the ERO. North American Electric Reliability
Corp., 116 FERC ] 61,062 (ERO Certification Order), order on reh'g &
compliance, 117 FERC ] 61,126 (ERO Rehearing Order) (2006), aff'd
sub nom. Alcoa, Inc. v. FERC, 564 F.3d 1342 (DC Cir. 2009).
\3\ Loadability refers to the ability of protective relays to
refrain from operating under load conditions.
\4\ 16 U.S.C. 824o(d)(5).
---------------------------------------------------------------------------
I. Background
2. Protective relays are devices that detect and initiate the
removal of faults on an electric system.\5\ They are designed to read
electrical measurements, such as current, voltage, and frequency, and
can be set to recognize certain measurements as indicating a fault.
When a protective relay detects a fault on an element of the system
under its protection, it sends a signal to an interrupting device(s)
(such as a circuit breaker) to disconnect the element from the rest of
the system.\6\ Impedance relays (also known as distance relays) are the
most common type of load-responsive phase protection relays used to
protect transmission lines. Impedance relays can also provide backup
protection and protection against remote circuit breaker failure.
---------------------------------------------------------------------------
\5\ Protective relays are one type of equipment used in
protection systems. The NERC definition of protection systems also
includes communication systems associated with protective relays,
voltage and current sensing devices, station batteries, and DC
control circuitry. See NERC Glossary of Terms Used in Reliability
Standards at 14.
\6\ Coordination of protection through distance settings and
time delays ensures that the relay closest to a fault operates
before a relay farther away from the fault, thereby ensuring that
the more distant relay does not disconnect both the transmission
equipment necessary to remove the fault and ``healthy'' equipment
that should remain in service.
---------------------------------------------------------------------------
3. Following the August 2003 blackout that affected parts of the
Midwest and Northeast United States, and Ontario, Canada, NERC and the
U.S.-Canada Power System Outage Task Force (Task Force) concluded that
a substantial number of transmission lines disconnected during the
blackout when load-responsive phase-protection backup distance and
phase relays operated unnecessarily, i.e. under non-fault conditions.
Although these relays operated according to their settings, the Task
Force determined that the operation of these relays for non-fault
conditions contributed to cascading outages at the start of the
blackout and accelerated the geographic spread of the cascade.\7\
---------------------------------------------------------------------------
\7\ U.S.-Canada Power System Outage Task Force, Final Report on
the August 14, 2003 Blackout in the United States and Canada: Causes
and Recommendations, at 80 (2004) (Final Blackout Report).
---------------------------------------------------------------------------
4. Seeking to prevent or minimize the scope of future blackouts,
both NERC and the Task Force made recommendations to ensure that these
types of protective relays do not contribute to future blackouts.
Recommendation 8A of the NERC Report addresses the need to evaluate
load-responsive protection zone 3 relays \8\ to determine whether they
will operate under extreme emergency conditions:
\8\ Multiple impedance relays are installed at each end of a
transmission line, with each used to protect a certain percentage,
or zone, of the local transmission line and remote lines. Zone 3
relays and zone 2 relays set to operate like zone 3 relays (zone 3/
zone 2 relays) are typically set to reach 100 percent of the
protected transmission line and more than 100 percent of the longest
line (including any series elements such as transformers) that
emanates from the remote buses.
All transmission owners shall, no later than September 30, 2004,
evaluate the zone 3 relay settings on all transmission lines
operating at 230 kV and above for the purpose of verifying that each
zone 3 relay is not set to trip on load under extreme emergency
conditions[ ]. In each case that a zone 3 relay is set so as to trip
on load under extreme conditions, the transmission operator shall
reset, upgrade, replace, or otherwise mitigate the overreach of
those relays as soon as possible and on a priority basis, but no
later than December 31, 2005. Upon completing analysis of its
application of zone 3 relays, each transmission owner may no later
than December 31, 2004 submit justification to NERC for applying
zone 3 relays outside of these recommended parameters. The Planning
Committee shall review such exceptions to ensure they do not
increase the risk of widening a cascading failure of the power
---------------------------------------------------------------------------
system.\9\
\9\ August 14, 2003 Blackout: NERC Actions to Prevent and
Mitigate the Impacts of Future Cascading Blackouts, at 13 (2004)
(NERC Report).
Recommendation No. 21A of the Task Force Final Blackout Report (Final
Blackout Report) urges NERC to expand the scope of its review to
---------------------------------------------------------------------------
include certain operationally significant facilities:
NERC [should] broaden the review [described in Recommendation 8A
of the NERC Report] to include operationally significant 115 kV and
138 kV lines, e.g., lines that are part of monitored flowgates or
interfaces. Transmission owners should also look for zone 2 relays
set to operate like zone 3 [relays].\10\
---------------------------------------------------------------------------
\10\ Final Blackout Report at 158.
In its petition, NERC states that PRC-023-1 is intended to
specifically address these recommendations.
II. Reliability Standard PRC-023-1
5. Reliability Standard PRC-023-1 requires transmission owners,
generator owners, and distribution providers to set load-responsive
phase protection relays according to specific criteria in order to
ensure that the relays reliably detect and protect the electric network
from all fault conditions, but do not operate during non-fault load
conditions.
A. Applicability
6. As proposed by NERC, the Reliability Standard applies to relay
settings on: (1) All transmission lines and transformers with low-
voltage terminals operated or connected at or above 200 kV; \11\ and
(2) those transmission lines and transformers with low-voltage
terminals operated or connected between 100 kV and 200 kV \12\ that are
designated by planning coordinators as critical to the reliability of
the bulk electric system.\13\
---------------------------------------------------------------------------
\11\ NERC explains in general that it decided to make PRC-023-1
voltage-level-specific because the definition of what is included in
the ``bulk electric system'' varies throughout the eight Regional
Entities and because the effects of PRC-023-1 are not constrained to
regional boundaries. For example, if one Region has purely
performance-based criteria and an adjoining Region has voltage-based
criteria, these criteria may not permit consideration of the effects
of protective relay operation in one Region upon the behavior of
facilities in the adjoining Region. NERC Petition at 18-19, 39-41.
\12\ In this Final Rule, we occasionally use the shorthand ``100
kV-200 kV facilities'' to refer to transmission lines and
transformers with low-voltage terminals operated or connected
between 100 kV and 200 kV.
\13\ In this Final Rule, we use the terms ``bulk electric
system'' and ``Bulk-Power System.'' ``Bulk electric system'' is
defined in the NERC Glossary of Terms Used in Reliability Standards,
and generally includes facilities operated at voltages at and above
100 kV. See NERC Glossary of Terms Used in Reliability Standards at
2. ``Bulk-Power System'' is defined in section 215 of the FPA, and
does not include a voltage threshold. See 16 U.S.C. 824o(a)(1). In
Order No. 693, the Commission explained that while it would rely on
the NERC definition of bulk electric system during the start-up
phase of the mandatory Reliability Standard regime, the statutory
Bulk-Power System encompasses more facilities than are included in
NERC's definition of the bulk electric system. Mandatory Reliability
Standards for the Bulk-Power System, Order No. 693, FERC Stats. &
Regs. ] 31,242, at P 75-76; order on reh'g, Order No. 693-A, 120
FERC ] 61,053 (2007).
---------------------------------------------------------------------------
[[Page 16916]]
7. Attachment A to the Reliability Standard specifies which
protection systems are subject to and excluded from the Standard's
Requirements. Section 1 of Attachment A provides that the Reliability
Standard applies to any protective functions that can operate with or
without time delay, on load current, including but not limited to: (1)
Phase distance; (2) out-of-step tripping; (3) switch-on-to-fault; (4)
overcurrent relays; and (5) communication-aided protection
applications.\14\ Section 2 states that the Reliability Standard
requires evaluation of out-of-step blocking schemes \15\ to ensure that
they do not operate for faults during the loading conditions defined in
the Standard's Requirements. Finally, section 3 expressly excludes from
the Reliability Standard's Requirements: (1) Relay elements enabled
only when other relays or associated systems fail (e.g., overcurrent
elements enabled only during abnormal system conditions or a loss of
communications); (2) protection relay systems intended for the
detection of ground fault conditions or for protection during stable
power swings; (3) generator protection relays susceptible to load; (4)
relay elements used only for special protection systems applied and
approved in accordance with Reliability Standards PRC-012 through PRC-
017; \16\ (5) protection relay systems designed to respond only in time
periods that allow operators 15 minutes or longer to respond to
overload conditions; (6) thermal emulation relays used in conjunction
with dynamic facility ratings; (7) relay elements associated with DC
line; and (8) relay elements associated with DC converter transformers.
---------------------------------------------------------------------------
\14\ Section 1.5 specifies that the communications aided
applications subject to the Reliability Standard include, but are
not limited to: (1) Permissive overreach transfer trip; (2)
permissive under-reach transfer trip; (3) directional comparison
blocking; and (4) directional comparison unblocking.
\15\ ``Out-of-step blocking'' refers to a protection system that
is capable distinguishing between a fault and a power swing. If a
power swing is detected, the protection system, ``blocks,'' or
prevents the tripping of its associated transmission facilities.
\16\ The Commission has not yet acted on PRC-012-0, PRC-013-0,
or PRC-014-0 because it is awaiting further information from the
ERO.
---------------------------------------------------------------------------
B. Requirements
8. Reliability Standard PRC-023-1 consists of three Requirements.
Requirement R1 directs entities to set their relays according to one of
the options set forth in sub-requirements R1.1 through R1.13.
Requirement R2 contains directives for entities that set their relays
according to sub-requirements R1.6 through R1.9, R1.12, or R1.13.
Requirement R3 directs planning coordinators to designate which
facilities operated between 100 kV and 200 kV are critical to the
reliability of the bulk electric system and therefore must have their
relays set according to one of the options in Requirement R1.
1. Requirement R1
9. Requirement R1 directs entities to set their relays according to
one of thirteen specific settings (sub-requirements R1.1 through R1.13)
intended to maximize loadability while maintaining Reliable Operation
of the bulk electric system for all fault conditions. Entities must
evaluate relay loadability at 0.85 per unit voltage and a power factor
angle of 30 degrees and set their transmission line relays so that they
do not operate:
R1.1. [A]t or below 150 [percent] of the highest seasonal
[f]acility [r]ating of a circuit, for the available defined loading
duration nearest 4 hours (expressed in amperes)[;]
R1.2. [A]t or below 115 [percent] of the highest seasonal 15-
minute [f]acility [r]atingof a circuit (expressed in amperes)[;]
\17\
---------------------------------------------------------------------------
\17\ NERC includes a footnote that states ``[w]hen a 15-minute
rating has been calculated and published for use in real-time
operations, the 15-minute rating can be used to establish the
loadability requirement for the protective relays.''
---------------------------------------------------------------------------
R1.3. [A]t or below 115 [percent] of the maximum theoretical
power transfer capability (using a 90-degree angle between the
sending-end and receiving-end voltages and either reactance or
complex impedance) of the circuit (expressed in amperes) using one
of the following to perform the power transfer calculation:
R1.3.1. An infinite source (zero source impedance) with a 1.00
per unit bus voltage at each end of the line[;] [or]
R1.3.2. An impedance at each end of the line, which reflects the
actual system source impedance with a 1.05 per unit voltage behind
each source impedance[;]
R1.4. [O]n series compensated transmission lines[,] * * * at or
below the maximum power transfer capability of the line, determined
as the greater of:
[a.] 115 [percent] of the highest emergency rating of the series
capacitor[;] [or]
[b.] 115 [percent] of the maximum power transfer capability of
the circuit (expressed in amperes), calculated in accordance with
R1.3, using the full line inductive reactance[;]
R1.5. [O]n weak source systems[,] * * * at or below 170
[percent] of the maximum end-of-line three-phase fault magnitude
(expressed in amperes)[;]
R1.6. [On] transmission line relays applied on transmission
lines connected to generation stations remote to load[,] * * * at or
below 230 [percent] of the aggregated generation nameplate
capability[;]
R1.7. [On] transmission line relays applied at the load center
terminal, remote from generation stations, * * * at or below 115
[percent] of the maximum current flow from the load to the
generation source under any system configuration[;]
R1.8. [On] transmission line relays applied on the bulk system-
end of transmission lines that serve load remote to the system[,] *
* * at or below 115 [percent] of the maximum current flow from the
system to the load under any system configuration[;]
R1.9. [On] transmission line relays applied on the load-end of
transmission lines that serve load remote to the bulk system[,] * *
* at or below 115 [percent] of the maximum current flow from the
load to the system under any system configuration[;]
R1.10. [On] transformer fault protection relays and transmission
line relays on transmission lines terminated only with a
transformer[,] * * * at or below the greater of:
[a.] 150 [percent] of the applicable maximum transformer
nameplate rating (expressed in amperes), including the forced cooled
ratings corresponding to all installed supplemental cooling
equipment[;] [or]
[b.] 115 [percent] of the highest operator established emergency
transformer rating[;]
R1.11. For transformer overload protection relays that do not
comply with R1.10[,] [the entity must either]. * * *
[a.] Set the relays to allow the transformer to be operated at
an overload level of at least 150 [percent] of the maximum
applicable nameplate rating, or 115 [percent] of the highest
operator established emergency transformer rating, whichever is
greater. The protection must allow this overload for at least 15
minutes to allow for the operator to take controlled action to
relieve the overload[;] [or]
[b.] Install supervision for the relays using either a top oil
or simulated winding hot spot temperature element. The setting
should be no less than 100[deg] C for the top oil or 140[deg] C for
the winding hot spot temperature[;] \18\
---------------------------------------------------------------------------
\18\ NERC includes a footnote that states: ``IEEE [S]tandard
C57.115, Table 3, specifies that transformers are to be designed to
withstand a winding hot spot temperature of 180 degrees C, and
cautions that bubble formation may occur above 140 degrees C.''
---------------------------------------------------------------------------
R1.12. When the desired transmission line capability is limited
by the requirement to adequately protect the transmission line, set
the transmission line distance relays to a maximum of 125 [percent]
of the apparent impedance (at the impedance angle of the
transmission line) subject to the following constraints:
R1.12.1. Set the maximum torque angle (MTA) to 90 degrees or the
highest supported by the manufacturer[;]
R1.12.2. Evaluate the relay loadability in amperes at the relay
trip point at 0.85 per unit voltage and a power factor angle of 30
degrees[;] [and]
R1.12.3. Include a relay setting component of 87 [percent] of
the current calculated in R1.12.2 in the [f]acility [r]ating
determination for the circuit[;]
R1.13. [Finally,] [w]here other situations present practical
limitations on circuit capability, [entities can] set the phase
[[Page 16917]]
protection relays so they do not operate at or below 115 [percent]
of such limitations.
2. Requirement R2
10. Requirement R2 provides that entities that set their relays
according to sub-requirements R1.6 through R1.9, R1.12, or R1.13 must
use the calculated circuit capability as the circuit's facility rating
and must obtain the agreement of the planning coordinator, transmission
operator, and reliability coordinator with authority over the facility
as to the calculated circuit capability.
3. Requirement R3
11. Requirement R3 directs planning coordinators to designate which
facilities operated between 100 kV and 200 kV are critical to the
reliability of the bulk electric system and therefore must have their
relays set according to one of the options in Requirement R1. Sub-
requirement R3.1 requires planning coordinators to have a process to
identify critical facilities. Sub-requirement R3.1.1 specifies that the
process must consider input from adjoining planning coordinators and
affected reliability coordinators. Sub-requirements R3.2 and R3.3
require planning coordinators to maintain a list of critical facilities
and provide it to reliability coordinators, transmission owners,
generator owners, and distribution providers within 30 days of
initially establishing it, and 30 days of any subsequent change.
III. Discussion
A. Overview
12. The Commission approves PRC-023-1, finding that it is just and
reasonable, not unduly discriminatory or preferential and in the public
interest. The Commission also directs the ERO to develop modifications
to PRC-023-1 through its Reliability Standards development process to
address specific concerns identified by the Commission and sets
specific deadlines for these modifications. Similar to our approach in
Order No. 693,\19\ we view such directives as separate from approval,
consistent with our authority under section 215(d)(5) of the FPA to
direct the ERO to develop a modification to a Reliability Standard.
---------------------------------------------------------------------------
\19\ See supra n.13.
---------------------------------------------------------------------------
B. Approval of PRC-023-1
1. NOPR Proposal
13. On May 21, 2009, the Commission issued a Notice of Proposed
Rulemaking (NOPR) proposing to approve PRC-023-1 as mandatory and
enforceable.\20\ As a separate action, pursuant to section 215(d)(5) of
the FPA, the Commission proposed to direct certain modifications to the
Reliability Standard.
---------------------------------------------------------------------------
\20\ Transmission Relay Loadability Reliability Standard, Notice
of Proposed Rulemaking, 74 FR 35830 (Jul. 21, 2009), FERC Stats. &
Regs. ] 32,642 (2009) (NOPR).
---------------------------------------------------------------------------
2. Comments
14. While commenters universally support the Commission's proposal
to approve PRC-023-1,\21\ most commenters oppose the majority of the
Commission's proposed modifications. Some commenters argue that the
Commission's proposed modifications violate Order No. 693 because they
prescribe specific changes that would dictate the content of the
modified Reliability Standard.
---------------------------------------------------------------------------
\21\ See, e.g., NERC Comments, EEI, TAPS, APPA, NARUC, EPSA,
Exelon.
---------------------------------------------------------------------------
3. Commission Determination
15. Pursuant to section 215(d)(2) of the FPA,\22\ the Commission
approves PRC-023-1 as just, reasonable, not unduly discriminatory or
preferential, and in the public interest. The Commission finds that
PRC-023-1 is a significant step toward improving the reliability of the
Bulk-Power System in North America because it requires load-responsive
phase protection relay settings to provide essential facility
protection for faults, while allowing the Bulk-Power System to be
operated in accordance with established facility ratings.
---------------------------------------------------------------------------
\22\ 16 U.S.C. 824o(d)(2).
---------------------------------------------------------------------------
16. Also, pursuant to section 215(d)(5) of the FPA, the Commission
adopts some of the proposed modifications in the NOPR and thus directs
certain modifications to the Reliability Standard. Unless stated
otherwise, the Commission directs the ERO to submit these modifications
no later than one year from the date of this Final Rule. We will
address each proposal and the specific comments received on each
proposal in the remainder of this Final Rule.
17. With regard to the concerns raised by some commenters about the
prescriptive nature of the Commission's proposed modifications, we
agree that, consistent with Order No. 693, a direction for modification
should not be so overly prescriptive as to preclude the consideration
of viable alternatives in the ERO's Reliability Standards development
process. However, some guidance is necessary, as the Commission
explained in Order No. 693:
[I]n identifying a specific matter to be addressed in a
modification * * * it is important that the Commission provide
sufficient guidance so that the ERO has an understanding of the
Commission's concerns and an appropriate, but not necessarily
exclusive, outcome to address those concerns. Without such direction
and guidance, a Commission proposal to modify a Reliability Standard
might be so vague that the ERO would not know how to adequately
respond.\23\
---------------------------------------------------------------------------
\23\ Order No. 693, FERC Stats. & Regs. ] 31,242 at P 185.
18. Thus, in some instances, while we provide specific details
regarding the Commission's expectations, we intend by doing so to
provide useful guidance to assist in the Reliability Standards
development process, not to impede it. As we explained in Order No.
693, we find that this is consistent with statutory language that
authorizes the Commission to order the ERO to submit a modification
``that addresses a specific matter'' if the Commission considers it
appropriate to carry out section 215 of the FPA.\24\ In this Final
Rule, we have considered commenters' concerns and, where a directive
for modification appears to be determinative of the outcome, the
Commission provides flexibility by directing the ERO to address the
underlying issue through the Reliability Standards development process
without mandating a specific change to PRC-023-1.\25\ Consequently,
consistent with Order No. 693, we clarify that where the Final Rule
identifies a concern and offers a specific approach to address that
concern, we will consider an equivalent alternative approach provided
that the ERO demonstrates that the alternative will adequately address
the Commission's underlying concern or goal as efficiently and
effectively as the Commission's proposal.\26\
---------------------------------------------------------------------------
\24\ Id. P 186.
\25\ Id.
\26\ Id.
---------------------------------------------------------------------------
19. Consistent with section 215 of the FPA, our regulations, and
Order No. 693, any modification to a Reliability Standard, including a
modification that addresses a Commission directive, must be developed
and fully vetted through NERC's Reliability Standards development
process.\27\
---------------------------------------------------------------------------
\27\ Id. P 187.
---------------------------------------------------------------------------
C. Applicability
20. As proposed by NERC, PRC-023-1 does not apply to any facility
operated or connected between 100 kV and 200 kV unless the relevant
planning coordinator designates the facility as ``critical'' to the
reliability of the bulk electric system. In the NOPR, the
[[Page 16918]]
Commission described this as an ``add in'' approach to
applicability.\28\
---------------------------------------------------------------------------
\28\ NOPR, FERC Stats. & Regs. ] 32,642 at P 40.
---------------------------------------------------------------------------
21. Requirement R3 of PRC-023-1 directs planning coordinators to
determine which 100 kV-200 kV facilities are critical to the
reliability of the bulk electric system, and therefore subject to the
Reliability Standard; it does not, however, define ``critical to the
reliability of the bulk electric system'' or provide planning
coordinators with a test to identify critical facilities.
1. NOPR Proposal
22. In the NOPR, the Commission stated that it expects planning
coordinators to use a process to carry out Requirement R3 that is
consistent across regions and robust enough to identify all facilities
that should be subject to PRC-023-1. The Commission expressed concern
that, based on the information in NERC's petition, the ``add in''
approach proposed by NERC would fail to meet these expectations.
23. The Commission explained that since approximately 85 percent of
circuit miles of electric transmission are operated at or below 253 kV,
the ``add in'' approach could, at the outset, effectively exempt from
the Reliability Standard's requirements a large percentage of
facilities that should otherwise be subject to the Standard. The
Commission also cited a letter from NERC to industry stakeholders
discussing the results of an ``add in'' approach in the context of
industry's self-identification of Critical Cyber Assets. According to
the Commission, the letter was an acknowledgement from NERC that the
``add in'' approach failed to produce a comprehensive list of Critical
Cyber Assets.\29\ The Commission further observed that NERC failed to
provide a technical basis for the ``add in'' approach, and did not
support its claim that expanded application of PRC-023-1 would double
implementation costs and distract industry resources from more
important areas. The Commission added that PRC-023-1 was developed to
prevent cascading outages, and that no area has a greater impact on the
reliability of the bulk electric system than the prevention of
cascading outages.
---------------------------------------------------------------------------
\29\ Id.
---------------------------------------------------------------------------
24. The Commission emphasized that PRC-023-1 must apply to relay
settings on all critical facilities for it to achieve its intended
reliability objective.\30\ In order to meet this goal, the Commission
stated that the process for identifying critical 100 kV-200 kV
facilities must include the same system simulations and assessments as
the Transmission Planning (TPL) Reliability Standards for reliable
operation for all categories of contingencies used in transmission
planning for all operating conditions. The Commission also stated that
it expects a comprehensive review to identify nearly every 100 kV-200
kV facility as a critical facility. In light of this expectation, and
coupled with its concern about the ``add in'' approach, the Commission
proposed to direct the ERO to adopt a ``rule out'' approach to
applicability; that is, to modify PRC-023-1 so that it applies to relay
settings on all 100 kV-200 kV facilities, with the possibility of case-
by-case exceptions for facilities that are not critical to the
reliability of the bulk electric system and demonstrably would not
result in cascading outages, instability, uncontrolled separation,
violation of facility ratings, or interruption of firm transmission
service.\31\
---------------------------------------------------------------------------
\30\ Id. P 42.
\31\ Id. P 43.
---------------------------------------------------------------------------
25. Finally, the Commission proposed to direct the ERO to adopt an
``add in'' approach to sub-100 kV facilities that Regional Entities
have identified as critical to the reliability of the bulk electric
system.\32\ The Commission explained that owners and operators of such
facilities are defined as transmission owners/operators for the
purposes of NERC's Compliance Registry,\33\ and that sub-100 kV
facilities can be included in regional definitions of the bulk electric
system.\34\ The Commission also stated that NERC failed to provide a
sufficient technical record to justify excluding such facilities from
the scope of the Reliability Standard.
---------------------------------------------------------------------------
\32\ Id. P 45.
\33\ NERC's Compliance Registry is a listing of organizations
subject to compliance with mandatory Reliability Standards. See NERC
Rules of Procedure, Section 500. NERC's Statement of Compliance
Registry Criteria, which sets forth thresholds for registration,
defines ``transmission owner/operator'' as:
III.d.1 An entity that owns or operates an integrated
transmission element associated with the bulk power system 100 kV
and above, or lower voltage as defined by the Regional Entity
necessary to provide for the reliable operation of the
interconnected transmission grid; or
III.d.2 An entity that owns/operates a transmission element
below 100 kV associated with a facility that is included on a
critical facilities list defined by the Regional Entity.
See NERC Statement of Compliance Registry Criteria at 9.
\34\ NERC defines the bulk electric system as follows:
As defined by the Regional Reliability Organization, the
electrical generation resources, transmission lines,
interconnections with neighboring systems, and associated equipment,
generally operated at voltages of 100 kV or higher. Radial
transmission facilities serving only load with one transmission
source are generally not included in this definition.
See NERC Glossary of Terms Used in Reliability Standards at 2.
---------------------------------------------------------------------------
2. Comments
26. In response to the NOPR, the Commission received comments
addressing its remarks about the test that planning coordinators must
use to implement Requirement R3 and its proposals to direct the ERO to
adopt the ``rule out'' approach for 100 kV-200 kV facilities and the
``add in'' approach for sub-100 kV facilities.
a. Comments on the Test That Planning Coordinators Must Use To
Implement Requirement R3
27. Commenters generally agree with the Commission that the process
for identifying critical facilities pursuant to Requirement R3 should
include the same simulation and assessments required by the TPL
Reliability Standards for all operating conditions. However, commenters
disagree with the Commission's expectation that planning coordinators
will identify nearly every 100 kV-200 kV facility as a critical
facility. For example, Duke reports that it has applied the existing
TPL standards to its Midwest and Carolina systems and has not
identified any sub-200 kV facility as a critical facility (i.e., there
have been no showings that the loss of any such facilities could result
in cascading outages, instability, or uncontrolled separation). Other
commenters maintain that the Commission's expectation is not supported
by any technical evidence and depends on a circular definition between
``above 100 kV'' and ``critical to the reliability of the bulk electric
system.'' \35\
---------------------------------------------------------------------------
\35\ See, e.g., Basin, Exelon, and WECC.
---------------------------------------------------------------------------
28. NERC recognizes the need for consistent criteria across North
America for identifying critical 100 kV-200 kV facilities and proposes
to work through industry to develop it.\36\ Although NERC did not
propose a test in PRC-023-1, in its comments it did provide the
suggestions for identifying operationally significant 100 kV-200 kV
facilities that the NERC System Protection and Control Task Force
provided to Regional Entities in 2004 and 2005 during the voluntary
Beyond Zone 3 relay review and mitigation program.\37\ During that
program, NERC suggested that Regional Entities identify:
---------------------------------------------------------------------------
\36\ NERC Comments at 12.
\37\ For a discussion of the Beyond Zone 3 relay review and
mitigation program, see infra P 34.
---------------------------------------------------------------------------
All circuits that are elements of flowgates[\38\] in the Eastern
Interconnection,
[[Page 16919]]
Commercially Significant Constraints in the Texas Interconnection,
or Rated Paths in the Western Interconnection. This includes both
the monitored and outage element for OTDF [Outage Transfer
Distribution Factor] sets.[\39\]
---------------------------------------------------------------------------
\38\ A ``flowgate'' is a single or group of transmission
elements intended to model MW flow impact relating to transmission
limitations and transmission service outage. See Final Black Report
at 214. Flowgates are operationally significant for the purpose of
ensuring desirable system performance because an actual outage would
present the modeled physical limitations on the bulk electric
system.
\39\ In the post-contingency configuration of a system under
study, Outage Transfer Distribution Factor refers to the measure of
the responsiveness or change (expressed in percent) in electrical
loadings on transmission system facilities due to a change in
electric power transfer from one area to another with one or more
system facilities removed from service.
---------------------------------------------------------------------------
All circuits that are elements of system operating limits (SOLs)
and interconnection reliability operating limits (IROLs), including
both monitored and outage elements.
All circuits that are directly related to off-site power supply
to nuclear plants. Any circuit whose outage causes unacceptable
voltages on the off-site power bus at a nuclear plant must be
included, regardless of its proximity to the plant.
All circuits of the first 5 limiting elements (monitored and
outaged elements) for transfer interfaces[\40\] determined by
regional and interregional transmission reliability studies. If
fewer than 5 limiting elements are found before reaching studied
transfers, all should be listed.
---------------------------------------------------------------------------
\40\ An ``interface'' is the specific set of transmission
elements between two areas or between two areas comprising one or
more electrical systems. See Final Blackout Report at 215. An
interface is operationally significant for the purpose of ensuring
desirable system performance because an outage of an interface would
affect IROLs.
---------------------------------------------------------------------------
Other circuits determined and agreed to by the reliability
authority/coordinator and the Regional Reliability Organizations.
29. In its comments, APPA proposes that the Commission direct NERC
to develop a process whereby each region can develop a specific
methodology to ensure consistent, verifiable identification of critical
facilities.
b. Comments on the ``Rule Out'' Approach
30. Commenters unanimously oppose the ``rule out'' approach. In
general, they argue that it is unnecessary, extremely costly, and
potentially detrimental to reliability.
31. NERC, EEI, and WECC argue that the cascade of 138 kV lines that
occurred during the August 2003 blackout would not have occurred if the
345 kV lines in their vicinity had not tripped, and that the 345 kV
lines would not have tripped if PRC-023-1 had been in effect prior to
the blackout.\41\ EEI, PG&E, and SRP add that whenever a facility
between 100 kV and 200 kV trips on load, it is almost always because of
preceding faults at higher voltages.
---------------------------------------------------------------------------
\41\ See, e.g., NERC Comments at 10, 16.
---------------------------------------------------------------------------
32. Some commenters argue that the majority of facilities between
100 kV and 200 kV are not critical to the reliability of the bulk
electric system and are unlikely to contribute to cascading outages at
higher voltages. APPA, EEI, and WECC state that most wide-area bulk
power transfers flow on high voltage facilities, while most sub-200 kV
facilities support local distribution service.\42\ SRP asserts that a
malfunction on a 100 kV-200 kV line typically causes an outage only for
the load connected to the faulted part of the line, leaving the rest of
the line unaffected; PG&E makes the related claim that the tripping of
a 100 kV-200 kV facility generally has a low impact on the reliability
of higher voltage systems, even when the two systems run in parallel.
APPA argues that cascading outages at higher voltages are unlikely to
be arrested by relay action at lower voltages. EEI adds that many 100
kV-200 kV facilities are designed to support local distribution service
and their related protection systems are set to ensure separation,
including load shedding, if disturbances or system events take place.
EEI asserts that these systems ensure ``controlled separation'' that,
by definition, does not involve the Bulk-Power System.
---------------------------------------------------------------------------
\42\ SRP and Y-WEA emphasize that this is especially true in the
western interconnection, where sub-200 kV facilities are generally
used as localized means for distributing electricity to moderately
sized and geographically distant load centers. See also
ElectriCities and NWCP.
---------------------------------------------------------------------------
33. Commenters also argue that the ``rule out'' approach is a
costly and inefficient use of limited industry resources that will
place an unreasonable burden on small entities and require utilities to
incur unnecessary upfront costs, forego other important initiatives,
and direct money and personnel away from the work necessary to ensure
the day-to-day reliability of the bulk electric system.
34. NERC states that it modeled PRC-023-1 on two post-blackout
relay review and mitigation programs (the Zone 3 Review and Beyond Zone
3 Review) that focused primarily on facilities operated at or above 200
kV, and that these programs give it a basis for concluding that the
costs of the ``rule out'' approach are extremely high.\43\ NERC reports
that these programs took over three years to complete, required close
to 150,000 hours of labor, cost almost $18 million, and resulted in
mitigation costs (equipment change-outs or additions) of approximately
$65 million, or $111,500 per terminal. Based on a survey of industry
conducted after the NOPR, NERC estimates that a review and mitigation
program for all facilities between 100 kV and 200 kV would far exceed
these costs in time and money. NERC estimates that such a program would
entail review of approximately 53,000 terminals, require close to
340,000 hours of labor, and cost almost $41 million.\44\ Based on the
results of the previous review programs, NERC estimates that at least
11,400 terminals could be out-of-compliance and that mitigation could
take between 5 and 10 years and cost approximately $590 million.\45\ In
contrast, NERC estimates that the ``add in'' approach would entail
review of only 2,400 terminals and require mitigation for approximately
500, roughly 240 of which would require equipment replacement.\46\
---------------------------------------------------------------------------
\43\ The Zone 3 Review examined 10,914 terminals operating at or
above 200 kV. The Beyond Zone 3 Review examined 12,273 terminals
operating at or above 200 kV and operationally significant terminals
operating between 100 kV and 200 kV. NERC Comments at 9-16.
\44\ Id. at 13-14. NERC adds that 114 transmission owners
operating 100 kV-200 kV lines responded to the survey.
\45\ Id. at 14.
\46\ Id. at 15.
---------------------------------------------------------------------------
35. Some commenters argue that the ``rule out'' approach may
adversely affect reliability. Exelon is concerned that the ``rule out''
approach may unintentionally result in the over-inclusion of facilities
subject to PRC-023-1. Exelon believes that such over-inclusion will
take a known and successful backup protection scheme and make it less
effective. Exelon explains that over-inclusion will increase the risk
of certain instances of backup relaying not tripping when it should,
thus allowing what would otherwise be a minor disturbance to expand
unnecessarily.\47\ Consumers Energy and Entergy argue that the ``rule
out'' approach will require entities to divert scarce resources from
other duties that are essential to reliability, thereby adversely
affecting reliability. Basin argues that the complexity of integrating
PRC-023-1 with other Reliability Standards for lower voltage lines will
divert personnel from more important aspects of the Reliability
Standards and adversely affect reliability.
---------------------------------------------------------------------------
\47\ See also Ameren at 8.
---------------------------------------------------------------------------
36. In addition to these arguments, commenters oppose the ``rule
out'' approach on the grounds that it: (1) Fails to give due weight to
the technical expertise of the ERO, as required by section 215(d)(2) of
the FPA; (2) violates Order No. 693 because it prescribes a specific
change that will dictate the content of the modified Reliability
[[Page 16920]]
Standard; \48\ (3) is inconsistent with the Commission's statements in
Order No. 672 about the cost of Reliability Standards; \49\ (4) rests
on the unsupported assumption that planning coordinators will fail to
produce a comprehensive list of critical facilities; and (5)
mischaracterizes NERC's letter expressing concern about the use of an
``add in'' approach in the Critical Cyber Assets survey.\50\
---------------------------------------------------------------------------
\48\ See e.g., TAPS, APPA, EEI, Ameren, Manitoba Hydro, Georgia
Transmission, Tri-State, CRC, EEI, APPA, Ameren, TANC, Fayetteville
Public Works Commission, and LES.
\49\ In Order No. 672, the Commission stated that ``[a] proposed
Reliability Standard does not necessarily have to reflect the
optimal method, or `best practice,' for achieving its reliability
goal without regard to implementation cost. * * * [but] should[,]
however[,] achieve its reliability goal effectively and
efficiently;'' Rules Concerning Certification of the Electric
Reliability Organization; and Procedures for the Establishment,
Approval, and Enforcement of Electric Reliability Standards, Order
No. 672, FERC Stats. & Regs. ] 31,204, at P 328, order on reh'g,
Order No. 672-A, FERC Stats. & Regs. ] 31,212 (2006).
\50\ See e.g., Exelon, PG&E, EEI, Basin, and TAPS.
---------------------------------------------------------------------------
37. In the event that the Commission adopts the ``rule out''
approach, commenters argue that the Commission should immediately
confirm the following exclusions: (1) Facilities that are not part of a
defined and routinely monitored flowgate; (2) radial transmission
lines, because they are specifically excluded from the bulk electric
system and are not critical to the reliability of the bulk electric
system; \51\ and (3) Category D Contingencies, because they involve the
loss of multiple transmission facilities caused by the outage of
transmission facilities other than those relevant to the Reliability
Standard.
---------------------------------------------------------------------------
\51\ See e.g., ElectriCities, NWCP, Palo Alto, PSEG Companies,
Pacific Northwest State Commissions, Y-WEA, and Filing Cooperatives.
---------------------------------------------------------------------------
38. Commenters also disagree with what they describe as the
Commission's 5-part test for case-by-case exceptions from the ``rule
out'' approach, that is, its proposal to permit exceptions for
facilities that demonstrably would not result in: (1) Cascading
outages; (2) instability; (3) uncontrolled separation; (4) violation of
facility ratings; or (5) interruption of firm transmission service.
39. At the outset, commenters assert that they do not understand
the relationship between the 5-part test for exceptions from the ``rule
out'' approach and the Commission's insistence that the ``add in''
process must include the same simulations and assessments as the TPL
Reliability Standards. Commenters are unsure whether the 5-part test is
in addition to, or in lieu of, the TPL assessments.
40. Commenters also challenge the substance of the 5-part test,
generally arguing that it requires more than a showing that a facility
is unlikely to contribute to cascading thermal outages and introduces
more rigorous requirements than those in the TPL Reliability Standards.
Specifically, APPA, Duke, Exelon, and TAPS argue that interruption of
firm transmission service and violation of facility ratings do not
belong as elements of the test because: (1) They do not result in
instability, uncontrolled separation, or cascading failures, and are
absent from the definition of ``Reliable Operation'' in section 215 of
the FPA; \52\ (2) avoiding an interruption of firm transmission service
is a business issue; (3) a requirement specifying that the loss of a
138 kV line cannot result in interruption of local load goes beyond the
requirements of existing Reliability Standards; (4) the loss of a 138
kV line does not show a loss of bulk electric system reliability; and
(5) ``violation of facility ratings'' is unduly vague and over-broad
because it is not restricted to bulk electric system facilities other
than the facility in question and is not focused on violation of
emergency ratings caused by an outage of the facility in question.
---------------------------------------------------------------------------
\52\ Section 215 defines ``Reliable Operation'' as ``operating
the elements of the bulk-power system within equipment and electric
system thermal, voltage, and stability limits so that instability,
uncontrolled separation, or cascading failures of such system will
not occur as a result of a sudden disturbance, including a
cybersecurity incident, or unanticipated failure of system
elements.'' 16 U.S.C. 824o(a)(4).
---------------------------------------------------------------------------
41. Commenters also argue that NERC should develop the test for
exclusions and that there should be some mechanism for entities to
challenge criticality determinations. For example, APPA argues that the
Regional Entity should establish a process for entities to challenge
criticality determinations.
c. Comments on Proposal To Include Sub-100 kV Facilities
42. Commenters also address the Commission's proposal to direct the
ERO to adopt an ``add in'' approach to sub-100 kV facilities, with most
objecting to what they perceive as the Commission's view of the
Compliance Registry.\53\ NERC argues that the Commission
mischaracterized the nature and purpose of the Compliance Registry by
suggesting that entities on the Registry must comply with all
Reliability Standards for all of their facilities.\54\ NERC explains
that the Compliance Registry does not specify which entities must
comply with any particular Reliability Standard, but that each
individual Standard specifies the entities and the facilities that are
subject to it. TAPS and APPA assert that a facility may be ``critical''
for the purpose of inclusion on the Compliance Registry, but not
``operationally significant'' for the purpose of avoiding cascading
thermal outages. For example, TAPS states that a sub-100 kV line that
connects to a black start unit and is designated as part of a
transmission operator's restoration plan would be deemed critical for
Compliance Registry purposes, but may not be operationally significant
for purposes of thermal cascading outages.\55\
---------------------------------------------------------------------------
\53\ See e.g., NERC, EEI, TAPS, TANC, Ontario Generation,
SWTDUG, and APPA.
\54\ See also TANC and Ontario Generation.
\55\ TAPS at 16; see also APPA at 28.
---------------------------------------------------------------------------
43. Several commenters request that the Commission confirm their
understanding of what is required if the Commission adopts its
proposal. ERCOT and TAPS request confirmation that the Reliability
Standard will apply only to those sub-100 kV facilities that are
already in the Compliance Registry, and that future registration will
be subject to a case-by-case demonstration of criticality. Likewise,
SWTDUG is concerned that the Commission's proposal will require non-
registered public power entities with sub-100 kV facilities to become
Registered Entities. ERCOT also requests confirmation that the only
required revision to the Reliability Standard would be the addition of
sub-100 kV facilities to the applicability section. ISO New England
requests confirmation that the Commission does not intend to create an
enforceable obligation against Regional Entities by directing them to
undertake--solely for the purpose of compliance with PRC-023-1--a
process to determine which sub-100 kV facilities are critical to the
reliability of the bulk electric system. ISO New England asserts that
NERC has already delegated to Regional Entities the role of designating
critical sub-100 kV facilities as part of the Compliance Registry
process.\56\ ISO New England seeks clarification that the Commission's
proposal merely requires the addition of a cross-reference to previous
designations of criticality made pursuant to the Compliance Registry
process.
---------------------------------------------------------------------------
\56\ ISO New England at 3.
---------------------------------------------------------------------------
44. ITC, IRC, and IESO/Hydro One support the Commission's proposal.
These commenters argue that a proactive approach should be used to
identify any facilities critical to the reliability of the bulk
electric system.
45. NERC and EEI oppose the Commission's proposal; however, both
[[Page 16921]]
concede that it may have merit and should be studied through the
Reliability Standards development process.\57\ SWTDUG and TAPS oppose
the Commission's proposal and argue that the Final Blackout Report does
not support extending the Reliability Standard to relay settings on
sub-100 kV facilities. TAPS maintains that the Commission must give
``due weight'' to NERC's exclusion of sub-100 kV facilities.
---------------------------------------------------------------------------
\57\ NERC Comments at 18-19; EEI at 17-18.
---------------------------------------------------------------------------
46. EPSA argues that the Commission's proposal lacks technical
support and fails to identify a specific reliability gap. EPSA contends
that the Commission should use ``Reliability Engineering'' to determine
if its project has a technical basis. EEI argues that few sub-100 kV
facilities are critical to the reliability of the bulk electric system.
EEI states that because it usually requires multiple 69 kV lines to
replace one 138 kV line, it is highly unlikely that sub-100 kV
facilities will cause a major cascade. EEI asserts that it is much more
likely that sub-100 kV facilities will trip to end a cascade, as
occurred during the August 2003 blackout.
3. Commission Determination
47. As discussed more fully below, we decline to direct the ERO to
adopt the ``rule out'' approach for 100 kV-200 kV facilities. However,
we adopt the NOPR proposal and direct the ERO to modify PRC-023-1 to
apply an ``add in'' approach to certain sub-100 kV facilities that
Regional Entities have already identified or will identify in the
future as critical facilities for the purposes the Compliance
Registry.\58\ Finally, we direct the ERO to modify Requirement R3 of
the Reliability Standard to include the test that planning coordinators
must use to identify sub-200 kV facilities that are critical to the
reliability of the bulk electric system.
---------------------------------------------------------------------------
\58\ Examples of such facilities include black start generation
and the ``cranking path'' from the generators to the bulk electric
system.
---------------------------------------------------------------------------
a. ``Rule Out'' Approach
48. We will not direct the ERO to adopt the ``rule out'' approach.
After further consideration, we conclude that our concerns about the
``add in'' approach can be addressed by directing the ERO to modify
Requirement R3 of the Reliability Standard to specify a comprehensive
and rigorous test that all planning coordinators must use to identify
all critical facilities.
49. In the NOPR, the Commission explained that PRC-023-1 must apply
to relay settings on all critical facilities between 100 kV and 200 kV
for it to achieve its intended reliability objective. The Commission
also stated that planning coordinators must use a process to carry out
Requirement R3 that is consistent across regions and robust enough to
identify all facilities that should be subject to the Reliability
Standard. The Commission expressed concern, however, that NERC's ``add
in'' approach could effectively exempt from the Reliability Standard's
Requirements a large percentage of facilities that should otherwise be
subject to the Standard. Since NERC did not propose any test for the
Commission to consider, the Commission proposed the ``rule out''
approach to ensure that planning coordinators identify all critical
facilities between 100 kV and 200 kV.
50. After reflecting on the rationale behind the ``rule out''
approach--namely, the goal of ensuring that planning coordinators
identify all critical facilities between 100 kV and 200 kV--and
considering the comments, we conclude that, from a reliability
standpoint, it should not matter whether PRC-023-1 employs an ``add
in'' approach or a ``rule out'' approach because both approaches should
ultimately result in the same list of critical facilities. In other
words, given a uniform and robust test, the facilities that would be
``added in'' under an ``add in'' approach should be the same as the
facilities that would remain subject to the Reliability Standard after
non-critical facilities are ruled out under the ``rule out'' approach.
Instead of concerning ourselves with the merits of an ``add in'' or
``rule out'' approach, the Commission will focus on the test
methodology that a planning coordinator uses to either ``add in'' or
``rule out'' a facility. If that test is lacking, PRC-023-1's
reliability objective will not be achieved regardless of whether an
``add in'' approach or a ``rule out'' approach is adopted.
Consequently, we decline to adopt the NOPR proposal and will not
require the ERO to adopt the ``rule out'' approach. Instead, as
discussed below, we direct the ERO to modify Requirement R3 of the
Reliability Standard to specify the test that planning coordinators
must use to identify all critical facilities.
51. In light of our decision, we do not need to address commenters'
objections to the ``rule