Interpretation of Transmission Planning Reliability Standard, 14386-14390 [2010-6565]
Download as PDF
14386
Federal Register / Vol. 75, No. 57 / Thursday, March 25, 2010 / Proposed Rules
prescribing regulations to assign the use
of airspace necessary to ensure the
safety of aircraft and the efficient use of
airspace. This proposed regulation is
within the scope of that authority as it
proposes to remove Class D and E
airspace at Panama City-Bay County
Airport, Panama City, FL.
SUPPLEMENTARY INFORMATION:
DEPARTMENT OF ENERGY
Federal Energy Regulatory
Commission
18 CFR Part 40
[Docket No. RM10–6–000]
List of Subjects in 14 CFR Part 71
Interpretation of Transmission
Planning Reliability Standard
Airspace, Incorporation by reference,
Navigation (Air).
March 18, 2010.
The Proposed Amendment
Accordingly, pursuant to the
authority delegated to me, the Federal
Aviation Administration proposes to
amend 14 CFR Part 71 as follows:
PART 71 —DESIGNATION OF CLASS
A, B, C, D, AND E AIRSPACE AREAS;
AIR TRAFFIC SERVICE ROUTES; AND
REPORTING POINTS
1. The authority citation for Part 71
continues to read as follows:
Authority: 49 U.S.C. 106(g); 40103, 40113,
40120; E.O. 10854, 24 FR 9565, 3 CFR, 1959–
1963 Comp., p. 389.
§ 71.1
[Amended]
2. The incorporation by reference in
14 CFR 71.1 of Federal Aviation
Administration Order 7400.9T, Airspace
Designations and Reporting Points,
signed August 27, 2009, and effective
September 15, 2009, is amended as
follows:
Paragraph 5000
Class D Airspace.
*
*
*
*
*
ASO FL D
Panama City, FL [Removed]
*
*
*
*
*
Paragraph 6004 Class E Airspace
Designated as an Extension to a Class D
Surface Area.
*
*
*
ASO FL E4
*
*
*
*
Panama City, FL [Removed]
*
*
*
Paragraph 6005 Class E Airspace Areas
Extending Upward from 700 feet or More
Above the Surface of the Earth.
*
*
*
mstockstill on DSKH9S0YB1PROD with PROPOSALS
ASO FL E5
*
*
Panama City, FL [Removed]
Issued in College Park, Georgia, on March
17, 2010.
Michael Vermuth,
Acting Manager, Operations Support Group,
Eastern Service Center, Air Traffic
Organization.
[FR Doc. 2010–6665 Filed 3–24–10; 8:45 am]
BILLING CODE 4910–13–P
VerDate Nov<24>2008
17:55 Mar 24, 2010
Jkt 220001
AGENCY: Federal Energy Regulatory
Commission.
ACTION: Notice of Proposed Rulemaking.
SUMMARY: Requirement R1.3.10 of the
Commission-approved transmission
planning Reliability Standard TPL–002–
0 provides that planning authorities and
transmission planners must consider in
their planning studies the effects of the
operation of their protection systems,
including backup and redundant
protection systems. The North American
Electric Reliability Corporation (NERC),
the Commission-certified electric
reliability organization, requests
approval of an interpretation of
Reliability Standard TPL–002–0. In this
order, the Commission proposes to
reject NERC’s proposed interpretation of
Requirement R1.3.10 of Reliability
Standard TPL–002–0 and, instead,
proposes an alternative interpretation of
the provision.
DATES: Comments are due May 10, 2010.
ADDRESSES: You may submit comments,
identified by docket number by any of
the following methods:
• Agency Web Site: https://ferc.gov.
Documents created electronically using
word processing software should be
filed in native applications or print-toPDF format and not in a scanned format.
• Mail/Hand Delivery: Commenters
unable to file comments electronically
must mail or hand deliver an original
and 14 copies of their comments to:
Federal Energy Regulatory Commission,
Secretary of the Commission, 888 First
Street, NE., Washington, DC 20426.
FOR FURTHER INFORMATION CONTACT:
Ron LeComte (Legal Information), Office
of General Counsel, 888 First Street,
NE., Washington, DC 20426,
ron.lecomte@ferc.gov.
Eugene Blick (Technical Information),
Office of Electric Reliability, 888 First
Street, NE., Washington, DC 20426,
eugene.blick@ferc.gov.
Edward Franks (Technical Information),
Office of Electric Reliability, 888 First
Street, NE., Washington, DC 20426,
edward.franks@ferc.gov.
Lauren Rosenblatt (Legal Information),
Office of Enforcement, 888 First
Street, NE., Washington, DC 20426,
lauren.rosenblatt@ferc.gov.
PO 00000
Frm 00026
Fmt 4702
Sfmt 4702
Notice of Proposed Rulemaking
1. On November 17, 2009, the North
American Electric Reliability
Corporation (NERC) submitted a
petition (NERC Petition) requesting
approval of NERC’s interpretation of
Requirement R1.3.10 of Commissionapproved transmission planning
Reliability Standard TPL–002–0 (System
Performance Following Loss of a Single
Bulk Electric System Element). NERC
developed the interpretation in response
to a request for interpretation submitted
to NERC by PacifiCorp on January 12,
2009. The Commission proposes to
reject the NERC proposed interpretation
of Requirement R1.3.10 of Reliability
Standard TPL–002–0 and, instead,
proposes an alternative interpretation of
the provision.
I. Background
2. Section 215 of the Federal Power
Act (FPA) requires a Commissioncertified Electric Reliability
Organization (ERO) to develop
mandatory and enforceable Reliability
Standards, which are subject to
Commission review and approval.1
Specifically, the Commission may
approve, by rule or order, a proposed
Reliability Standard or modification to a
Reliability Standard if it determines that
the Standard is just, reasonable, not
unduly discriminatory or preferential,
and in the public interest.2 Once
approved, the Reliability Standards may
be enforced by the ERO, subject to
Commission oversight, or by the
Commission independently.3
3. Pursuant to section 215 of the FPA,
the Commission established a process to
select and certify an ERO,4 and
subsequently certified NERC.5 On April
4, 2006, NERC submitted to the
Commission a petition seeking approval
of 107 proposed Reliability Standards.
On March 16, 2007, the Commission
issued a Final Rule, Order No. 693,6
approving 83 of the 107 Reliability
Standards, including transmission
planning Reliability Standards TPL–
1 16
U.S.C. 824.
824o(d)(2).
3 Id. 824o(e)(3).
4 Rules Concerning Certification of the Electric
Reliability Organization; and Procedures for the
Establishment, Approval, and Enforcement of
Electric Reliability Standards, Order No. 672, FERC
Stats. & Regs. ¶ 31,204, order on reh’g, Order No.
672–A, FERC Stats. & Regs. ¶ 31,212 (2006).
5 North American Electric Reliability Corp., 116
FERC ¶ 61,062, order on reh’g & compliance, 117
FERC ¶ 61,126 (2006), aff’d sub nom. Alcoa, Inc.
v. FERC, 564 F.3d 1342 (DC Cir. 2009).
6 Mandatory Reliability Standards for the BulkPower System, Order No. 693, FERC Stats. & Regs.
¶ 31,242, order on reh’g, Order No. 693–A, 120
FERC ¶ 61,053 (2007).
2 Id.
E:\FR\FM\25MRP1.SGM
25MRP1
Federal Register / Vol. 75, No. 57 / Thursday, March 25, 2010 / Proposed Rules
001–0 through TPL–004–0. In addition,
pursuant to section 215(d)(5) of the
FPA,7 the Commission directed NERC to
develop modifications to 56 of the 83
approved Reliability Standards,
including TPL–002–0.8
4. NERC’s Rules of Procedure provide
that a person that is ‘‘directly and
materially affected’’ by Bulk-Power
System reliability may request an
interpretation of a Reliability Standard.9
In response, the ERO will assemble a
team with relevant expertise to address
the requested interpretation and also
form a ballot pool. NERC’s Rules of
Procedure provide that, within 45 days,
the team will draft an interpretation of
the reliability standard and submit it to
the ballot pool. If approved by the ballot
pool and subsequently by the NERC
Board of Trustees (Board), the
interpretation is appended to the
Reliability Standard and filed with the
applicable regulatory authorities for
approval.
II. Transmission Planning Reliability
Standards
5. Each of the transmission planning
Reliability Standards, TPL–001–0
through TPL–004–0, requires the
planning authorities and transmission
planners (planner) to provide a ‘‘valid
assessment’’ that would ‘‘ensure that
reliable systems are developed that meet
specified performance requirements’’
both in the near-term (years one through
five) and in the longer-term (years six
through ten, or as needed). For each of
these Reliability Standards, entities
must adequately assess a range of
operating conditions on their systems
and plan to meet certain performance
criteria that the Reliability Standards
specify for each of four classes of
contingencies.10 The principles that
planners must apply to the design of the
assessment and of the supporting
studies are set forth in the Requirements
of the specific Reliability Standard.
6. Table I, which is incorporated into
each TPL Reliability Standards, sets
forth the different types of contingencies
that planners must study pursuant to
the specific Reliability Standard, and
the performance criteria the system
must meet when experiencing those
mstockstill on DSKH9S0YB1PROD with PROPOSALS
7 16
U.S.C. 824o(d)(5).
No. 693, FERC Stats & Regs. ¶ 31,242 at
P 1797.
9 NERC Rules of Procedure, Appendix 3A,
Reliability Standards Development Procedure,
Version 6.1, at 26–27 (2007).
10 TPL–001–0 through TPL–004–0 each includes
the same Table I, titled ‘‘Transmission System
Standards—Normal and Emergency Conditions,’’
which identifies the classes of contingencies as
Category A through Category D. TPL–002–0
addresses Category B contingencies.
8 Order
VerDate Nov<24>2008
16:39 Mar 24, 2010
Jkt 220001
contingencies to reliably meet all
projected customer demand.
7. Reliability Standard TPL–002–0
requires planners to assess system
performance subject to Category B
contingencies (‘‘event resulting in the
loss of a single element’’) outlined in
Table I. As provided in Table I, Category
B contingencies include:
(1) A single-line-to-ground (SLG) or
three-phase (3;) fault with ‘‘normal
clearing’’ that removes from service
either a generator, transmission circuit
or transformer;11
(2) Loss of an element without a fault;
or
(3) Outage of a single pole (direct
current) line with normal clearing.
8. Requirement R1 of Reliability
Standard TPL–002–0 states:
R1. The Planning Authority and
Transmission Planner shall each demonstrate
through a valid assessment that its portion of
the interconnected transmission system is
planned such that the Network can be
operated to supply projected customer
demands and projected Firm (non-recallable
reserved) Transmission Services, at all
demand levels over the range of forecast
system demands, under the contingency
conditions as defined in Category B. To be
valid, the Planning Authority and
Transmission Planner assessments shall:
* * *
9. Requirement R1 proceeds with subRequirements R1.1 through R1.5, which
provide the criteria that must be met to
qualify the assessment directed by
Requirement R1 as valid. In particular,
Requirement R1.3 mandates that the
assessment shall
[b]e supported by a current or past study
and/or system simulation testing that
addresses each of the following categories,
showing system performance following
Category B. The specific elements selected
(from each of the following categories) for
inclusion in these studies and simulations
shall be acceptable to the associated Regional
Reliability Organization(s).
Further, Requirement R1.3.10 requires
the planner to
[i]nclude the effects of existing and planned
protection systems, including any backup or
redundant systems.
10. In sum, Requirement R1 provides
the parameters of a valid assessment of
system performance when experiencing
a single contingency; Requirement R1.3
defines the criteria for the ‘‘base cases’’
that must be included in the studies to
support the assessment.12 Requirement
R1.3.10 provides as a base case criteria
that the studies must include the effects
11 See, Section IV. C. for the definition of normal
clearing.
12 Requirement R1.3 uses the term ‘‘categories’’ to
define the criteria that must be included in the base
cases.
PO 00000
Frm 00027
Fmt 4702
Sfmt 4702
14387
of existing and planned protection
systems, including any backup or
redundant systems.
11. Requirement R1.3.10 requires that
planners study how a utility’s
protection system,13 which isolates
faults within a defined geographic area,
would operate under circumstances
‘‘including backup or redundant
systems.’’ A utility designs its protection
system with ‘‘primary’’ protection,14 and
may also employ ‘‘redundant’’ protection
that operates for a primary protection
system component that fails. Utilities
also use ‘‘backup’’ protection that
functions to isolate a fault when the
primary protection system does not
operate. Depending on the specific
design, backup may remove more
elements, or take longer to isolate the
fault than the primary protection
system.15
III. NERC Proposed Interpretation
12. In the NERC Petition, NERC
explains that it received a request from
PacifiCorp for an interpretation of
Reliability Standard TPL–002–0,
Requirement R1.3.10, addressing three
specific questions. Below, we restate the
PacifiCorp questions and NERC
interpretations:
Question 1: Does TPL–002–0 R1.3.10
require that all elements that are
expected to be removed from service
through normal operation of the
protection systems be removed in
simulations?
Response 1: TPL–002–0 requires that
System studies or simulations be made
to assess the impact of single
Contingency operation with Normal
Clearing. TPL–002–0, R1.3.10 does
require that all elements expected to be
removed from service through normal
operations of the Protection Systems be
removed in simulations.
Question 2: Is a Category B
disturbance limited to faults with
[N]ormal [C]learing where the
protection system operates as designed
13 A protection system consists of protective
relays, associated communication systems, voltage
and current sensing devices, station batteries and
DC control circuitry for the protection of bulk
electric system elements. It detects faults and
initiates operation of circuit breakers, thereby
isolating the faulted element(s) from the remainder
of the interconnected transmission system.
14 A primary protection scheme is the first line of
defense designed to remove the minimum number
of elements in the shortest time.
15 A backup protection system isolates the fault or
disturbance by removing additional elements some
period of time after the non-redundant primary
protection system would do so, operating because
that primary protection system did not function
properly. Remote backup protection refers to
protection systems that operate breakers distant
from the site of the contingency and therefore result
in the isolation of a larger portion of the bulk
electric system.
E:\FR\FM\25MRP1.SGM
25MRP1
14388
Federal Register / Vol. 75, No. 57 / Thursday, March 25, 2010 / Proposed Rules
mstockstill on DSKH9S0YB1PROD with PROPOSALS
in the time expected with proper
functioning of the protection system(s)
or do Category B disturbances extend to
protection system misoperations and
failures?
Response 2: This standard does not
require an assessment of the
Transmission System performance due
to a Protection System failure or
Protection System misoperation.
Protection System failure or Protection
System misoperation is addressed in
TPL–003–0—System Performance
following Loss of Two or More Bulk
Electric System Elements (Category C)
and TPL–004–0—System Performance
Following Extreme Events Resulting in
the Loss of Two or More Bulk Electric
System (BES) Elements (Category D).
Question 3: Does TPL–002–0, R1.3.10
require that planning for Category B
[C]ontingencies assume a [C]ontingency
that results in something other than a
[N]ormal [C]learing event even though
the TPL–002–0 Table I—Category B
matrix uses the phrase ‘‘SLG or 3-Phase
Fault, with Normal Clearing?’’
Response 3: TPL–002–0, R1.3.10 does
not require simulating anything other
than Normal Clearing when assessing
the impact of a Single Line Ground
(SLG) or 3-Phase (3;) Fault on the
performance of the Transmission
System.16
13. In support of its request for
approval, NERC contends that the
proposed interpretation directly
supports the reliability purpose of TPL–
002–0 because it clarifies what is
required for the ‘‘System simulations’’
cited in the main requirement without
expanding the reach of the standard.17
NERC maintains that the proposed
interpretation clearly identifies what
needs to be done—that all elements
expected to be removed from service
through normal operation of the
protection system must be removed in
simulations and that only normal
clearing is required in the simulations.
NERC states that the proposed
interpretation clearly distinguishes that
misoperations and failures of the
protection system are not part of
Reliability Standard TPL–002–0, but are
addressed in other standards. NERC
states that the interpretation will result
in ensuring that an adequate level of
reliability for the Bulk-Power System
16 NERC Petition at 10. In support for its request
for an interpretation, PacifiCorp states that ‘‘[i]f
TPL–002–0, R1.3.10 requires that planning for
Category B Contingencies must assume failure or
misoperation of all existing and planned protection
systems, protection system failures previously
identified as Category C [ ] Contingencies or
Category D [ ] Contingencies would now become
Category B Contingencies * * *’’ Id. at Appendix A
at 1–2.
17 NERC Petition at 11.
VerDate Nov<24>2008
16:39 Mar 24, 2010
Jkt 220001
will be achieved and maintained by
providing clarity and certainty in
support of the objective.
14. In approving the proposed
interpretation, the NERC Board stated
that it applied a standard of strict
construction that does not expand the
reach of the Reliability Standard or
correct a perceived gap or deficiency in
the standard.18 The NERC Board
recommended that any gaps or
deficiencies in a Reliability Standard
that are evident through the
interpretation process be addressed
promptly by the standards drafting
team. NERC states that it will examine
any gaps or deficiencies in Reliability
Standard TPL–002–0 in its
consideration of the next version of this
standard through the Reliability
Standards Development Procedure.19
IV. Discussion
15. We propose to reject NERC’s
proposed interpretation of Reliability
Standard TPL–002–0, Requirement
R1.3.10. NERC proposes to interpret that
simulations to assess the impact of
single contingency operation ‘‘do[ ] not
require an assessment of the
Transmission System performance due
to a Protection System failure or
Protection System misoperation’’ to be
in compliance with Requirement
R1.3.10 of Reliability Standard TPL–
002–0. NERC’s proposed interpretation
miscategorizes non-operation of nonredundant primary protection systems
as protection system failure which is
addressed in TPL–003–0 and TPL–004–
0. However, pursuant to TPL–002–0,
planners are required to study the
effects of existing and planned
protection systems, including backup
and redundant systems. Accordingly, by
categorizing the non-operation of nonredundant primary protection systems
as a protection system failure, NERC’s
proposed interpretation misses studying
the effects of backup and redundant
protection systems pursuant to
Requirement R1.3.10 of TPL–002–0.
Rather, for the reasons discussed below,
we believe that the Requirement R1.3.10
of TPL–002–0 requires that planners
study, in their system assessments, the
non-operation of primary protection
systems in order to ascertain whether
and how reliance on the as-designed
backup or redundant protection systems
affects reliability. Accordingly, we
propose an interpretation of
Requirement R1.3.10 of Reliability
at 5.
states that this standard is included in
Project 2006–02—Assess Transmission Future
Needs and Develop Transmission Plans that is
expected to be completed in the first half of 2010.
Standard TPL–002–0 consistent with
our understanding.
16. In support of our proposed
interpretation, we explain that planning
assessments are developed through base
case simulations. We then distinguish a
contingency from the base case, and
conclude that the non-operation of a
non-redundant primary protection
system is not a contingency. Finally, we
explain that normal clearing of a
contingency depends on the protection
system that operates to clear the
contingency, and that only by modeling
the non-operation of non-redundant
primary protection systems in the base
case would the planner include the
effects of existing and planned
protection systems, including backup or
redundant systems. For these reasons,
our proposed interpretation would
require modeling of the non-operation
of primary protection systems to be in
compliance with Requirement R1.3.10
of Reliability Standard TPL–002–000,
and not by the requirements to be in
compliance with Reliability Standards
TPL–003–0 and TPL–004–0.
A. Assessment Through Base Case
Simulations
17. Reliability Standard TPL–002–0
requires that planning authorities and
planners demonstrate, through a valid
assessment, that their portion of the
interconnected transmission system will
supply the projected customer demands
and projected firm transmission service
over a variety of conditions. A planner
performs the assessment of its portion of
the interconnected transmission system
through computer modeling and
simulations, in which the planner first
creates base cases that reflect an array of
system operating conditions. Using
these base cases as a starting point, the
planner then assesses the performance
of the system and tests the base cases by
subjecting them through computer
modeling and simulations to various
Category B Contingencies outlined in
Table I.
18. Performance of the system as
modeled, assuming all of the
Contingencies taken one at a time and
at any location in the bulk electric
system, must meet the performance
criteria specified in Table I for Category
B Contingencies. The performance
criteria in Table I specifies that, in the
event of a Category B Contingency, the
system (1) remains stable and both
thermal and voltage limits remain
within applicable ratings; 20 (2)
18 Id.
19 NERC
PO 00000
Frm 00028
Fmt 4702
Sfmt 4702
20 TPL–002–0, Table I defines ‘‘applicable ratings’’
in its footnote ‘‘a’’. If other than normal ratings are
applied, the planner must show that the bulk
electric system can withstand the next contingency
E:\FR\FM\25MRP1.SGM
25MRP1
Federal Register / Vol. 75, No. 57 / Thursday, March 25, 2010 / Proposed Rules
continues to serve all firm demand and
firm transfers; 21 and (3) does not have
any cascading outages. If the studies or
system simulation tests show that, for
Category B Contingencies, any of the
system base cases do not meet these
performance criteria, pursuant to
Requirement R2 of Reliability Standard
TPL–002–0, the planner must determine
and document a modification.
B. Distinguishing a Contingency From
the Base Case
mstockstill on DSKH9S0YB1PROD with PROPOSALS
19. As previously discussed, Table I
of Reliability Standard TPL–002–0 sets
forth the Category B Contingencies that
a planner must assess pursuant to
Reliability Standard TPL–002–0. Table I
defines contingencies in terms of their
‘‘initiating event(s)’’ and the elements
the initiating event takes out of service.
The determination of what elements
would be taken out of service as a result
of a Category B Contingency should not
be confused with the number of
elements ultimately taken out of service
by the system’s response to the
initiating event.22 For example, a
contingency may involve a fault at a
transformer at a generating unit. In
response to the fault, operation of the
primary protection system at the unit
transformer, as designed, removes both
the unit transformer and the associated
generator from service. This scenario
qualifies as a single contingency
because there is only one initiating
event involving one element—the
transformer—even though the end state
of the system includes the loss of two
system elements—a unit transformer
and a generator.
20. It is also important to distinguish
an element taken out of service by a
contingency or the operation of a
protection system from an element or
protection system component that the
base case assumes is not in operation.
Transmission elements that are not in
service and generators that are not
dispatched or that are assumed to be
‘‘out of service’’ in the base case are not
considered to be contingencies. For
example, if the base case assumes that
three generators and one line will be out
through system adjustments that do not result in the
loss of firm load or firm transfers. System
adjustments for Category B Contingencies do not
include tripping of capacity resources.
21 See Order No. 693, FERC Stats & Regs. ¶ 31,242
at P 1791–1795.
22 In Order No. 693, the Commission explained,
‘‘a single contingency consists of a failure of a single
element that faithfully duplicates what will happen
in the actual system. * * *. Thus, if the system is
designed such that failure of a single element
removes from service multiple elements in order to
isolate the faulted element, then that is what should
be simulated to assess system performance.’’ Order
No. 693, FERC Stats & Regs. ¶ 31,242 at P 1716.
VerDate Nov<24>2008
16:39 Mar 24, 2010
Jkt 220001
of service for load conditions or
maintenance, the base case system
without those facilities in service is the
normal operating condition.
Requirement R1.3.10 requires the
system planner to study the effects of
the non-operation of the non-redundant
primary protection system in the base
case simulations, not the effects of
protection systems that are out of
service.23
21. The Commission proposes to
interpret that the non-operation of a
non-redundant primary protection
system is not a contingency and
Requirement R1.3.10 requires that the
planner model, as a condition in the
base case, the non-operation of the
primary protection system, accounting
for operation of the redundant
protection system or, alternatively, the
fact that the protection system is not
redundant, as appropriate. Only by
modeling and simulating system
conditions with base cases representing
element outages and clearing times
associated with non-operation of the
primary protection system will a
planner comply with Requirement
R1.3.10 of Reliability Standard TPL–
002–0, that is, to study the ‘‘effects of
* * * any backup or redundant
[protection] systems’’ on Category B
contingencies. The Commission intends
its proposed interpretation to ensure
that the phrase is not rendered a nullity.
C. Normal Versus Delayed Clearing of
the Contingency
22. Requirement R1.3.10 also requires
that a planner’s studies and simulations
model the Category B Contingencies
with normal clearing. Footnote ‘‘e’’ of
Table I defines ‘‘normal’’ and ‘‘delayed’’
clearing as follows:
Normal clearing is when the protection
system operates as designed and the Fault is
cleared in the time normally expected with
proper functioning of the installed protection
system. Delayed clearing of a Fault is due to
failure of any protection system component
such as a relay, circuit breaker, or current
transformer, and not because of an
intentional design delay.
23. The assumptions in a base case as
to which protection system will operate
to clear the contingency against which
the base case is tested determines the
amount of time associated with
‘‘operate[] as designed.’’ Thus, the base
case assumptions determine which
method of clearing constitutes normal
clearing. If the base case being tested
assumes the primary protection system
operates, normal clearing of the
23 TPL–002–0, R.1.3.12 provides for the inclusion
of a planned (including maintenance) outage of any
bulk electric equipment (including protection
systems or their components).
PO 00000
Frm 00029
Fmt 4702
Sfmt 4702
14389
contingency will be the clearing that is
consistent with the as-designed
operation of the primary protection
system. If the base case assumes the
primary protection system will not
operate, normal clearing will be that
clearing that is consistent with the
redundant protection, if provided, or asdesigned backup protection for that
primary protection system.24 In a study
or simulation test, how the protection
systems operate will determine which
circuit breakers will open and the times
it takes for specific breakers to open.
The changes in system topology due to
the opening of circuit breakers (which
takes elements out of service), the
operating times in which those circuit
breakers open, and the total time
required to clear the fault from the
system all affect how the bulk electric
system performs.
24. Delayed clearing of the
contingency results only when the
protection system in service in the base
case (whether primary or back-up) does
not operate as-designed due to a failure,
such as a relay failing to operate (one
form of relay misoperation), stuck
breaker or other disabling condition.
The concepts of normal and delayed
clearing apply in the same manner to
non-redundant primary protection
systems. An example of normal clearing
with longer clearing times is if the nonoperation of a primary protection
system disables both the primary
protection and its breaker-failureinitiate protection. The backup
protection that the system base case
must test would be the next level of
backup that would operate in the event
of the contingency. The next level of
backup protection may, for example, be
the protection systems located at the
adjacent substations, and will typically
take longer to operate the necessary
breakers by removing more elements to
clear the fault than the operation of the
primary or breaker-failure-initiate
protection systems.25 These longer
clearing times do not constitute or
create a situation of delayed clearing,
however, because the longer clearing
times are the as-designed operating
24 For example, for a fault near one end of a line
protected by distance relaying without
communications, normal clearing from the end
close to the fault will be zone 1 or times associated
with primary clearing while the remote end will be
zone 2 or times associated with back-up clearing.
Both of these times are normal clearing as they are
in accordance with design criteria.
25 In the circumstance of this example, the
Commission refers to the system that initiates
breaker failure protection as the backup protection
system that is coordinated to operate when the nonredundant primary protection system does not
operate within a specified period of time.
E:\FR\FM\25MRP1.SGM
25MRP1
14390
Federal Register / Vol. 75, No. 57 / Thursday, March 25, 2010 / Proposed Rules
times of the backup protection system
being utilized.
25. With this understanding, the
Commission proposes to interpret
Requirement R1.3.10 as requiring a
planner to study the effects of the asdesigned backup protection system, and
a planner must consider whether this
clearing is consistent with the asdesigned normal clearing of the
protection system being studied. It
follows that where a study’s base case
is designed to test the effects of backup
protection systems, the base case
assumption that the backup protection
system operates in the time normally
expected is not equivalent to delayed
clearing due to a primary protection
system component failure.
26. Rather, the backup protection
system becomes the analytical starting
point for the examined normal operating
conditions, i.e., the base case, and any
additional time and elements removed
from service resulting from operation of
that backup protection beyond those the
primary protection system would
require is intentional and as designed.
The operating characteristics (i.e., time
and elements removed) of the primary
protection system are simply no longer
part of the analysis. Delayed clearing in
the case of simulating the effects of
backup protection systems only results
when there is a failure of a protection
system component in the protection
systems being simulated.
27. Finally, we propose that the
interpretation of R1.3.10 discussed
herein will apply prospectively from the
effective date of any Final Rule and no
entity will be subject to financial
penalties for having operated in a
manner inconsistent with this proposed
interpretation prior to the effective date
of any Final Rule.
D. Related Discussion in Order No. 693
mstockstill on DSKH9S0YB1PROD with PROPOSALS
28. The Commission did not
specifically discuss a protection system
failure or misoperation in Order No.
693. However, the Commission
discussed the issue of a single point of
protection system failure and how it
factors into planning studies under the
System Protection Coordination (PRC)
Reliability Standards. The Commission
stated:
With respect to MISO’s comment that
virtually all protection systems have backups
and therefore the Commission’s proposals are
not necessary, unless the backup protection
has the same design goals and capabilities as
the primary protection, a relay failure in the
primary protection may still threaten system
reliability. Further, we note that while the
[Protection and Control] Reliability
Standards do not specifically require
protection systems consisting of redundant
VerDate Nov<24>2008
16:39 Mar 24, 2010
Jkt 220001
and independent protection groups for each
critical element in the Bulk-Power System,
such requirements are included as one
potential solution in the TPL Reliability
Standards.26
29. Therefore, the Commission has
recognized the effect that non-operation
of primary protection systems may have
on reliability in the context of observing
that redundant or backup protection
systems may minimize the reliability
risks that non-operation of primary
protection systems poses. Consistent
with the concern the Commission
discussed regarding the PRC Reliability
Standards, Requirement R1.3.10 of
Reliability Standard TPL–002–0
provides that the effect of non-operation
of primary protection systems be
studied for a valid assessment of system
reliability.
V. Comment Procedures
30. The Commission invites interested
persons to submit comments on the
matters and issues proposed in this
notice to be adopted, including any
related matters or alternative proposals
that commenters may wish to discuss.
Comments are due May 10, 2010.
Comments must refer to Docket No.
RM10–6–000, and must include the
commenter’s name, the organization
they represent, if applicable, and their
address in their comments.
31. The Commission encourages
comments to be filed electronically via
the eFiling link on the Commission’s
Web site at https://www.ferc.gov. The
Commission accepts most standard
word processing formats. Documents
created electronically using word
processing software should be filed in
native applications or print-to-PDF
format and not in a scanned format.
Commenters filing electronically do not
need to make a paper filing.
32. Commenters that are not able to
file comments electronically must send
an original and 14 copies of their
comments to: Federal Energy Regulatory
Commission, Secretary of the
Commission, 888 First Street, NE.,
Washington, DC 20426.
33. All comments will be placed in
the Commission’s public files and may
be viewed, printed, or downloaded
remotely as described in the Document
Availability section below. Commenters
on this proposal are not required to
serve copies of their comments on other
commenters.
26 Order No. 693, FERC Stats & Regs. ¶ 31,242 at
P 1436, n.380 (if delayed clearing results in
reliability criteria violations, one solution can be
the use of redundant relay systems, citing TPL–
002–0 Table I, footnote e).
PO 00000
Frm 00030
Fmt 4702
Sfmt 4702
VI. Document Availability
34. In addition to publishing the full
text of this document in the Federal
Register, the Commission provides all
interested persons an opportunity to
view and/or print the contents of this
document via the Internet through
FERC’s Home Page (https://www.ferc.gov)
and in FERC’s Public Reference Room
during normal business hours (8:30 a.m.
to 5 p.m. Eastern time) at 888 First
Street, NE., Room 2A, Washington DC
20426.
35. From FERC’s Home Page on the
Internet, this information is available on
eLibrary. The full text of this document
is available on eLibrary in PDF and
Microsoft Word format for viewing,
printing, and/or downloading. To access
this document in eLibrary, type the
docket number excluding the last three
digits of this document in the docket
number field.
36. User assistance is available for
eLibrary and the FERC’s Web site during
normal business hours from FERC
Online Support at 202–502–6652 (toll
free at 1–866–208–3676) or e-mail at
ferconlinesupport@ferc.gov, or the
Public Reference Room at (202) 502–
8371, TTY (202) 502–8659. E-mail the
Public Reference Room at
public.referenceroom@ferc.gov.
By direction of the Commission.
Kimberly D. Bose,
Secretary.
[FR Doc. 2010–6565 Filed 3–24–10; 8:45 am]
BILLING CODE 6717–01–P
DEPARTMENT OF HOUSING AND
URBAN DEVELOPMENT
24 CFR Part 1000
[Docket No. FR–5275–C–07]
Native American Housing Assistance
and Self-Determination
Reauthorization Act of 2008:
Negotiated Rulemaking Committee
Meeting; Correction
AGENCY: Office of the Assistant
Secretary for Public and Indian
Housing, HUD.
ACTION: Notice of Negotiated
Rulemaking Committee Meeting;
correction.
SUMMARY: HUD published a document
in the Federal Register on March 19,
2010, announcing a meeting of the
Native American Housing Assistance &
Self-Determination Negotiated
Rulemaking Committee. The document
contained an incorrect telephone
number for the location where the
meeting is to take place. The location,
E:\FR\FM\25MRP1.SGM
25MRP1
Agencies
[Federal Register Volume 75, Number 57 (Thursday, March 25, 2010)]
[Proposed Rules]
[Pages 14386-14390]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2010-6565]
=======================================================================
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
Federal Energy Regulatory Commission
18 CFR Part 40
[Docket No. RM10-6-000]
Interpretation of Transmission Planning Reliability Standard
March 18, 2010.
AGENCY: Federal Energy Regulatory Commission.
ACTION: Notice of Proposed Rulemaking.
-----------------------------------------------------------------------
SUMMARY: Requirement R1.3.10 of the Commission-approved transmission
planning Reliability Standard TPL-002-0 provides that planning
authorities and transmission planners must consider in their planning
studies the effects of the operation of their protection systems,
including backup and redundant protection systems. The North American
Electric Reliability Corporation (NERC), the Commission-certified
electric reliability organization, requests approval of an
interpretation of Reliability Standard TPL-002-0. In this order, the
Commission proposes to reject NERC's proposed interpretation of
Requirement R1.3.10 of Reliability Standard TPL-002-0 and, instead,
proposes an alternative interpretation of the provision.
DATES: Comments are due May 10, 2010.
ADDRESSES: You may submit comments, identified by docket number by any
of the following methods:
Agency Web Site: https://ferc.gov. Documents created
electronically using word processing software should be filed in native
applications or print-to-PDF format and not in a scanned format.
Mail/Hand Delivery: Commenters unable to file comments
electronically must mail or hand deliver an original and 14 copies of
their comments to: Federal Energy Regulatory Commission, Secretary of
the Commission, 888 First Street, NE., Washington, DC 20426.
FOR FURTHER INFORMATION CONTACT:
Ron LeComte (Legal Information), Office of General Counsel, 888 First
Street, NE., Washington, DC 20426, ron.lecomte@ferc.gov.
Eugene Blick (Technical Information), Office of Electric Reliability,
888 First Street, NE., Washington, DC 20426, eugene.blick@ferc.gov.
Edward Franks (Technical Information), Office of Electric Reliability,
888 First Street, NE., Washington, DC 20426, edward.franks@ferc.gov.
Lauren Rosenblatt (Legal Information), Office of Enforcement, 888 First
Street, NE., Washington, DC 20426, lauren.rosenblatt@ferc.gov.
SUPPLEMENTARY INFORMATION:
Notice of Proposed Rulemaking
1. On November 17, 2009, the North American Electric Reliability
Corporation (NERC) submitted a petition (NERC Petition) requesting
approval of NERC's interpretation of Requirement R1.3.10 of Commission-
approved transmission planning Reliability Standard TPL-002-0 (System
Performance Following Loss of a Single Bulk Electric System Element).
NERC developed the interpretation in response to a request for
interpretation submitted to NERC by PacifiCorp on January 12, 2009. The
Commission proposes to reject the NERC proposed interpretation of
Requirement R1.3.10 of Reliability Standard TPL-002-0 and, instead,
proposes an alternative interpretation of the provision.
I. Background
2. Section 215 of the Federal Power Act (FPA) requires a
Commission-certified Electric Reliability Organization (ERO) to develop
mandatory and enforceable Reliability Standards, which are subject to
Commission review and approval.\1\ Specifically, the Commission may
approve, by rule or order, a proposed Reliability Standard or
modification to a Reliability Standard if it determines that the
Standard is just, reasonable, not unduly discriminatory or
preferential, and in the public interest.\2\ Once approved, the
Reliability Standards may be enforced by the ERO, subject to Commission
oversight, or by the Commission independently.\3\
---------------------------------------------------------------------------
\1\ 16 U.S.C. 824.
\2\ Id. 824o(d)(2).
\3\ Id. 824o(e)(3).
---------------------------------------------------------------------------
3. Pursuant to section 215 of the FPA, the Commission established a
process to select and certify an ERO,\4\ and subsequently certified
NERC.\5\ On April 4, 2006, NERC submitted to the Commission a petition
seeking approval of 107 proposed Reliability Standards. On March 16,
2007, the Commission issued a Final Rule, Order No. 693,\6\ approving
83 of the 107 Reliability Standards, including transmission planning
Reliability Standards TPL-
[[Page 14387]]
001-0 through TPL-004-0. In addition, pursuant to section 215(d)(5) of
the FPA,\7\ the Commission directed NERC to develop modifications to 56
of the 83 approved Reliability Standards, including TPL-002-0.\8\
---------------------------------------------------------------------------
\4\ Rules Concerning Certification of the Electric Reliability
Organization; and Procedures for the Establishment, Approval, and
Enforcement of Electric Reliability Standards, Order No. 672, FERC
Stats. & Regs. ] 31,204, order on reh'g, Order No. 672-A, FERC
Stats. & Regs. ] 31,212 (2006).
\5\ North American Electric Reliability Corp., 116 FERC ]
61,062, order on reh'g & compliance, 117 FERC ] 61,126 (2006), aff'd
sub nom. Alcoa, Inc. v. FERC, 564 F.3d 1342 (DC Cir. 2009).
\6\ Mandatory Reliability Standards for the Bulk-Power System,
Order No. 693, FERC Stats. & Regs. ] 31,242, order on reh'g, Order
No. 693-A, 120 FERC ] 61,053 (2007).
\7\ 16 U.S.C. 824o(d)(5).
\8\ Order No. 693, FERC Stats & Regs. ] 31,242 at P 1797.
---------------------------------------------------------------------------
4. NERC's Rules of Procedure provide that a person that is
``directly and materially affected'' by Bulk-Power System reliability
may request an interpretation of a Reliability Standard.\9\ In
response, the ERO will assemble a team with relevant expertise to
address the requested interpretation and also form a ballot pool.
NERC's Rules of Procedure provide that, within 45 days, the team will
draft an interpretation of the reliability standard and submit it to
the ballot pool. If approved by the ballot pool and subsequently by the
NERC Board of Trustees (Board), the interpretation is appended to the
Reliability Standard and filed with the applicable regulatory
authorities for approval.
---------------------------------------------------------------------------
\9\ NERC Rules of Procedure, Appendix 3A, Reliability Standards
Development Procedure, Version 6.1, at 26-27 (2007).
---------------------------------------------------------------------------
II. Transmission Planning Reliability Standards
5. Each of the transmission planning Reliability Standards, TPL-
001-0 through TPL-004-0, requires the planning authorities and
transmission planners (planner) to provide a ``valid assessment'' that
would ``ensure that reliable systems are developed that meet specified
performance requirements'' both in the near-term (years one through
five) and in the longer-term (years six through ten, or as needed). For
each of these Reliability Standards, entities must adequately assess a
range of operating conditions on their systems and plan to meet certain
performance criteria that the Reliability Standards specify for each of
four classes of contingencies.\10\ The principles that planners must
apply to the design of the assessment and of the supporting studies are
set forth in the Requirements of the specific Reliability Standard.
---------------------------------------------------------------------------
\10\ TPL-001-0 through TPL-004-0 each includes the same Table I,
titled ``Transmission System Standards--Normal and Emergency
Conditions,'' which identifies the classes of contingencies as
Category A through Category D. TPL-002-0 addresses Category B
contingencies.
---------------------------------------------------------------------------
6. Table I, which is incorporated into each TPL Reliability
Standards, sets forth the different types of contingencies that
planners must study pursuant to the specific Reliability Standard, and
the performance criteria the system must meet when experiencing those
contingencies to reliably meet all projected customer demand.
7. Reliability Standard TPL-002-0 requires planners to assess
system performance subject to Category B contingencies (``event
resulting in the loss of a single element'') outlined in Table I. As
provided in Table I, Category B contingencies include:
(1) A single-line-to-ground (SLG) or three-phase (3[Oslash]) fault
with ``normal clearing'' that removes from service either a generator,
transmission circuit or transformer;\11\
---------------------------------------------------------------------------
\11\ See, Section IV. C. for the definition of normal clearing.
---------------------------------------------------------------------------
(2) Loss of an element without a fault; or
(3) Outage of a single pole (direct current) line with normal
clearing.
8. Requirement R1 of Reliability Standard TPL-002-0 states:
R1. The Planning Authority and Transmission Planner shall each
demonstrate through a valid assessment that its portion of the
interconnected transmission system is planned such that the Network
can be operated to supply projected customer demands and projected
Firm (non-recallable reserved) Transmission Services, at all demand
levels over the range of forecast system demands, under the
contingency conditions as defined in Category B. To be valid, the
Planning Authority and Transmission Planner assessments shall: * * *
9. Requirement R1 proceeds with sub-Requirements R1.1 through R1.5,
which provide the criteria that must be met to qualify the assessment
directed by Requirement R1 as valid. In particular, Requirement R1.3
mandates that the assessment shall
[b]e supported by a current or past study and/or system simulation
testing that addresses each of the following categories, showing
system performance following Category B. The specific elements
selected (from each of the following categories) for inclusion in
these studies and simulations shall be acceptable to the associated
Regional Reliability Organization(s).
Further, Requirement R1.3.10 requires the planner to
[i]nclude the effects of existing and planned protection systems,
including any backup or redundant systems.
10. In sum, Requirement R1 provides the parameters of a valid
assessment of system performance when experiencing a single
contingency; Requirement R1.3 defines the criteria for the ``base
cases'' that must be included in the studies to support the
assessment.\12\ Requirement R1.3.10 provides as a base case criteria
that the studies must include the effects of existing and planned
protection systems, including any backup or redundant systems.
---------------------------------------------------------------------------
\12\ Requirement R1.3 uses the term ``categories'' to define the
criteria that must be included in the base cases.
---------------------------------------------------------------------------
11. Requirement R1.3.10 requires that planners study how a
utility's protection system,\13\ which isolates faults within a defined
geographic area, would operate under circumstances ``including backup
or redundant systems.'' A utility designs its protection system with
``primary'' protection,\14\ and may also employ ``redundant''
protection that operates for a primary protection system component that
fails. Utilities also use ``backup'' protection that functions to
isolate a fault when the primary protection system does not operate.
Depending on the specific design, backup may remove more elements, or
take longer to isolate the fault than the primary protection
system.\15\
---------------------------------------------------------------------------
\13\ A protection system consists of protective relays,
associated communication systems, voltage and current sensing
devices, station batteries and DC control circuitry for the
protection of bulk electric system elements. It detects faults and
initiates operation of circuit breakers, thereby isolating the
faulted element(s) from the remainder of the interconnected
transmission system.
\14\ A primary protection scheme is the first line of defense
designed to remove the minimum number of elements in the shortest
time.
\15\ A backup protection system isolates the fault or
disturbance by removing additional elements some period of time
after the non-redundant primary protection system would do so,
operating because that primary protection system did not function
properly. Remote backup protection refers to protection systems that
operate breakers distant from the site of the contingency and
therefore result in the isolation of a larger portion of the bulk
electric system.
---------------------------------------------------------------------------
III. NERC Proposed Interpretation
12. In the NERC Petition, NERC explains that it received a request
from PacifiCorp for an interpretation of Reliability Standard TPL-002-
0, Requirement R1.3.10, addressing three specific questions. Below, we
restate the PacifiCorp questions and NERC interpretations:
Question 1: Does TPL-002-0 R1.3.10 require that all elements that
are expected to be removed from service through normal operation of the
protection systems be removed in simulations?
Response 1: TPL-002-0 requires that System studies or simulations
be made to assess the impact of single Contingency operation with
Normal Clearing. TPL-002-0, R1.3.10 does require that all elements
expected to be removed from service through normal operations of the
Protection Systems be removed in simulations.
Question 2: Is a Category B disturbance limited to faults with
[N]ormal [C]learing where the protection system operates as designed
[[Page 14388]]
in the time expected with proper functioning of the protection
system(s) or do Category B disturbances extend to protection system
misoperations and failures?
Response 2: This standard does not require an assessment of the
Transmission System performance due to a Protection System failure or
Protection System misoperation. Protection System failure or Protection
System misoperation is addressed in TPL-003-0--System Performance
following Loss of Two or More Bulk Electric System Elements (Category
C) and TPL-004-0--System Performance Following Extreme Events Resulting
in the Loss of Two or More Bulk Electric System (BES) Elements
(Category D).
Question 3: Does TPL-002-0, R1.3.10 require that planning for
Category B [C]ontingencies assume a [C]ontingency that results in
something other than a [N]ormal [C]learing event even though the TPL-
002-0 Table I--Category B matrix uses the phrase ``SLG or 3-Phase
Fault, with Normal Clearing?''
Response 3: TPL-002-0, R1.3.10 does not require simulating anything
other than Normal Clearing when assessing the impact of a Single Line
Ground (SLG) or 3-Phase (3[Oslash]) Fault on the performance of the
Transmission System.\16\
---------------------------------------------------------------------------
\16\ NERC Petition at 10. In support for its request for an
interpretation, PacifiCorp states that ``[i]f TPL-002-0, R1.3.10
requires that planning for Category B Contingencies must assume
failure or misoperation of all existing and planned protection
systems, protection system failures previously identified as
Category C [ ] Contingencies or Category D [ ] Contingencies would
now become Category B Contingencies * * *'' Id. at Appendix A at 1-
2.
---------------------------------------------------------------------------
13. In support of its request for approval, NERC contends that the
proposed interpretation directly supports the reliability purpose of
TPL-002-0 because it clarifies what is required for the ``System
simulations'' cited in the main requirement without expanding the reach
of the standard.\17\ NERC maintains that the proposed interpretation
clearly identifies what needs to be done--that all elements expected to
be removed from service through normal operation of the protection
system must be removed in simulations and that only normal clearing is
required in the simulations. NERC states that the proposed
interpretation clearly distinguishes that misoperations and failures of
the protection system are not part of Reliability Standard TPL-002-0,
but are addressed in other standards. NERC states that the
interpretation will result in ensuring that an adequate level of
reliability for the Bulk-Power System will be achieved and maintained
by providing clarity and certainty in support of the objective.
---------------------------------------------------------------------------
\17\ NERC Petition at 11.
---------------------------------------------------------------------------
14. In approving the proposed interpretation, the NERC Board stated
that it applied a standard of strict construction that does not expand
the reach of the Reliability Standard or correct a perceived gap or
deficiency in the standard.\18\ The NERC Board recommended that any
gaps or deficiencies in a Reliability Standard that are evident through
the interpretation process be addressed promptly by the standards
drafting team. NERC states that it will examine any gaps or
deficiencies in Reliability Standard TPL-002-0 in its consideration of
the next version of this standard through the Reliability Standards
Development Procedure.\19\
---------------------------------------------------------------------------
\18\ Id. at 5.
\19\ NERC states that this standard is included in Project 2006-
02--Assess Transmission Future Needs and Develop Transmission Plans
that is expected to be completed in the first half of 2010.
---------------------------------------------------------------------------
IV. Discussion
15. We propose to reject NERC's proposed interpretation of
Reliability Standard TPL-002-0, Requirement R1.3.10. NERC proposes to
interpret that simulations to assess the impact of single contingency
operation ``do[ ] not require an assessment of the Transmission System
performance due to a Protection System failure or Protection System
misoperation'' to be in compliance with Requirement R1.3.10 of
Reliability Standard TPL-002-0. NERC's proposed interpretation
miscategorizes non-operation of non-redundant primary protection
systems as protection system failure which is addressed in TPL-003-0
and TPL-004-0. However, pursuant to TPL-002-0, planners are required to
study the effects of existing and planned protection systems, including
backup and redundant systems. Accordingly, by categorizing the non-
operation of non-redundant primary protection systems as a protection
system failure, NERC's proposed interpretation misses studying the
effects of backup and redundant protection systems pursuant to
Requirement R1.3.10 of TPL-002-0. Rather, for the reasons discussed
below, we believe that the Requirement R1.3.10 of TPL-002-0 requires
that planners study, in their system assessments, the non-operation of
primary protection systems in order to ascertain whether and how
reliance on the as-designed backup or redundant protection systems
affects reliability. Accordingly, we propose an interpretation of
Requirement R1.3.10 of Reliability Standard TPL-002-0 consistent with
our understanding.
16. In support of our proposed interpretation, we explain that
planning assessments are developed through base case simulations. We
then distinguish a contingency from the base case, and conclude that
the non-operation of a non-redundant primary protection system is not a
contingency. Finally, we explain that normal clearing of a contingency
depends on the protection system that operates to clear the
contingency, and that only by modeling the non-operation of non-
redundant primary protection systems in the base case would the planner
include the effects of existing and planned protection systems,
including backup or redundant systems. For these reasons, our proposed
interpretation would require modeling of the non-operation of primary
protection systems to be in compliance with Requirement R1.3.10 of
Reliability Standard TPL-002-000, and not by the requirements to be in
compliance with Reliability Standards TPL-003-0 and TPL-004-0.
A. Assessment Through Base Case Simulations
17. Reliability Standard TPL-002-0 requires that planning
authorities and planners demonstrate, through a valid assessment, that
their portion of the interconnected transmission system will supply the
projected customer demands and projected firm transmission service over
a variety of conditions. A planner performs the assessment of its
portion of the interconnected transmission system through computer
modeling and simulations, in which the planner first creates base cases
that reflect an array of system operating conditions. Using these base
cases as a starting point, the planner then assesses the performance of
the system and tests the base cases by subjecting them through computer
modeling and simulations to various Category B Contingencies outlined
in Table I.
18. Performance of the system as modeled, assuming all of the
Contingencies taken one at a time and at any location in the bulk
electric system, must meet the performance criteria specified in Table
I for Category B Contingencies. The performance criteria in Table I
specifies that, in the event of a Category B Contingency, the system
(1) remains stable and both thermal and voltage limits remain within
applicable ratings; \20\ (2)
[[Page 14389]]
continues to serve all firm demand and firm transfers; \21\ and (3)
does not have any cascading outages. If the studies or system
simulation tests show that, for Category B Contingencies, any of the
system base cases do not meet these performance criteria, pursuant to
Requirement R2 of Reliability Standard TPL-002-0, the planner must
determine and document a modification.
---------------------------------------------------------------------------
\20\ TPL-002-0, Table I defines ``applicable ratings'' in its
footnote ``a''. If other than normal ratings are applied, the
planner must show that the bulk electric system can withstand the
next contingency through system adjustments that do not result in
the loss of firm load or firm transfers. System adjustments for
Category B Contingencies do not include tripping of capacity
resources.
\21\ See Order No. 693, FERC Stats & Regs. ] 31,242 at P 1791-
1795.
---------------------------------------------------------------------------
B. Distinguishing a Contingency From the Base Case
19. As previously discussed, Table I of Reliability Standard TPL-
002-0 sets forth the Category B Contingencies that a planner must
assess pursuant to Reliability Standard TPL-002-0. Table I defines
contingencies in terms of their ``initiating event(s)'' and the
elements the initiating event takes out of service. The determination
of what elements would be taken out of service as a result of a
Category B Contingency should not be confused with the number of
elements ultimately taken out of service by the system's response to
the initiating event.\22\ For example, a contingency may involve a
fault at a transformer at a generating unit. In response to the fault,
operation of the primary protection system at the unit transformer, as
designed, removes both the unit transformer and the associated
generator from service. This scenario qualifies as a single contingency
because there is only one initiating event involving one element--the
transformer--even though the end state of the system includes the loss
of two system elements--a unit transformer and a generator.
---------------------------------------------------------------------------
\22\ In Order No. 693, the Commission explained, ``a single
contingency consists of a failure of a single element that
faithfully duplicates what will happen in the actual system. * * *.
Thus, if the system is designed such that failure of a single
element removes from service multiple elements in order to isolate
the faulted element, then that is what should be simulated to assess
system performance.'' Order No. 693, FERC Stats & Regs. ] 31,242 at
P 1716.
---------------------------------------------------------------------------
20. It is also important to distinguish an element taken out of
service by a contingency or the operation of a protection system from
an element or protection system component that the base case assumes is
not in operation. Transmission elements that are not in service and
generators that are not dispatched or that are assumed to be ``out of
service'' in the base case are not considered to be contingencies. For
example, if the base case assumes that three generators and one line
will be out of service for load conditions or maintenance, the base
case system without those facilities in service is the normal operating
condition. Requirement R1.3.10 requires the system planner to study the
effects of the non-operation of the non-redundant primary protection
system in the base case simulations, not the effects of protection
systems that are out of service.\23\
---------------------------------------------------------------------------
\23\ TPL-002-0, R.1.3.12 provides for the inclusion of a planned
(including maintenance) outage of any bulk electric equipment
(including protection systems or their components).
---------------------------------------------------------------------------
21. The Commission proposes to interpret that the non-operation of
a non-redundant primary protection system is not a contingency and
Requirement R1.3.10 requires that the planner model, as a condition in
the base case, the non-operation of the primary protection system,
accounting for operation of the redundant protection system or,
alternatively, the fact that the protection system is not redundant, as
appropriate. Only by modeling and simulating system conditions with
base cases representing element outages and clearing times associated
with non-operation of the primary protection system will a planner
comply with Requirement R1.3.10 of Reliability Standard TPL-002-0, that
is, to study the ``effects of * * * any backup or redundant
[protection] systems'' on Category B contingencies. The Commission
intends its proposed interpretation to ensure that the phrase is not
rendered a nullity.
C. Normal Versus Delayed Clearing of the Contingency
22. Requirement R1.3.10 also requires that a planner's studies and
simulations model the Category B Contingencies with normal clearing.
Footnote ``e'' of Table I defines ``normal'' and ``delayed'' clearing
as follows:
Normal clearing is when the protection system operates as
designed and the Fault is cleared in the time normally expected with
proper functioning of the installed protection system. Delayed
clearing of a Fault is due to failure of any protection system
component such as a relay, circuit breaker, or current transformer,
and not because of an intentional design delay.
23. The assumptions in a base case as to which protection system
will operate to clear the contingency against which the base case is
tested determines the amount of time associated with ``operate[] as
designed.'' Thus, the base case assumptions determine which method of
clearing constitutes normal clearing. If the base case being tested
assumes the primary protection system operates, normal clearing of the
contingency will be the clearing that is consistent with the as-
designed operation of the primary protection system. If the base case
assumes the primary protection system will not operate, normal clearing
will be that clearing that is consistent with the redundant protection,
if provided, or as-designed backup protection for that primary
protection system.\24\ In a study or simulation test, how the
protection systems operate will determine which circuit breakers will
open and the times it takes for specific breakers to open. The changes
in system topology due to the opening of circuit breakers (which takes
elements out of service), the operating times in which those circuit
breakers open, and the total time required to clear the fault from the
system all affect how the bulk electric system performs.
---------------------------------------------------------------------------
\24\ For example, for a fault near one end of a line protected
by distance relaying without communications, normal clearing from
the end close to the fault will be zone 1 or times associated with
primary clearing while the remote end will be zone 2 or times
associated with back-up clearing. Both of these times are normal
clearing as they are in accordance with design criteria.
---------------------------------------------------------------------------
24. Delayed clearing of the contingency results only when the
protection system in service in the base case (whether primary or back-
up) does not operate as-designed due to a failure, such as a relay
failing to operate (one form of relay misoperation), stuck breaker or
other disabling condition. The concepts of normal and delayed clearing
apply in the same manner to non-redundant primary protection systems.
An example of normal clearing with longer clearing times is if the non-
operation of a primary protection system disables both the primary
protection and its breaker-failure-initiate protection. The backup
protection that the system base case must test would be the next level
of backup that would operate in the event of the contingency. The next
level of backup protection may, for example, be the protection systems
located at the adjacent substations, and will typically take longer to
operate the necessary breakers by removing more elements to clear the
fault than the operation of the primary or breaker-failure-initiate
protection systems.\25\ These longer clearing times do not constitute
or create a situation of delayed clearing, however, because the longer
clearing times are the as-designed operating
[[Page 14390]]
times of the backup protection system being utilized.
---------------------------------------------------------------------------
\25\ In the circumstance of this example, the Commission refers
to the system that initiates breaker failure protection as the
backup protection system that is coordinated to operate when the
non-redundant primary protection system does not operate within a
specified period of time.
---------------------------------------------------------------------------
25. With this understanding, the Commission proposes to interpret
Requirement R1.3.10 as requiring a planner to study the effects of the
as-designed backup protection system, and a planner must consider
whether this clearing is consistent with the as-designed normal
clearing of the protection system being studied. It follows that where
a study's base case is designed to test the effects of backup
protection systems, the base case assumption that the backup protection
system operates in the time normally expected is not equivalent to
delayed clearing due to a primary protection system component failure.
26. Rather, the backup protection system becomes the analytical
starting point for the examined normal operating conditions, i.e., the
base case, and any additional time and elements removed from service
resulting from operation of that backup protection beyond those the
primary protection system would require is intentional and as designed.
The operating characteristics (i.e., time and elements removed) of the
primary protection system are simply no longer part of the analysis.
Delayed clearing in the case of simulating the effects of backup
protection systems only results when there is a failure of a protection
system component in the protection systems being simulated.
27. Finally, we propose that the interpretation of R1.3.10
discussed herein will apply prospectively from the effective date of
any Final Rule and no entity will be subject to financial penalties for
having operated in a manner inconsistent with this proposed
interpretation prior to the effective date of any Final Rule.
D. Related Discussion in Order No. 693
28. The Commission did not specifically discuss a protection system
failure or misoperation in Order No. 693. However, the Commission
discussed the issue of a single point of protection system failure and
how it factors into planning studies under the System Protection
Coordination (PRC) Reliability Standards. The Commission stated:
With respect to MISO's comment that virtually all protection
systems have backups and therefore the Commission's proposals are
not necessary, unless the backup protection has the same design
goals and capabilities as the primary protection, a relay failure in
the primary protection may still threaten system reliability.
Further, we note that while the [Protection and Control] Reliability
Standards do not specifically require protection systems consisting
of redundant and independent protection groups for each critical
element in the Bulk-Power System, such requirements are included as
one potential solution in the TPL Reliability Standards.\26\
---------------------------------------------------------------------------
\26\ Order No. 693, FERC Stats & Regs. ] 31,242 at P 1436, n.380
(if delayed clearing results in reliability criteria violations, one
solution can be the use of redundant relay systems, citing TPL-002-0
Table I, footnote e).
29. Therefore, the Commission has recognized the effect that non-
operation of primary protection systems may have on reliability in the
context of observing that redundant or backup protection systems may
minimize the reliability risks that non-operation of primary protection
systems poses. Consistent with the concern the Commission discussed
regarding the PRC Reliability Standards, Requirement R1.3.10 of
Reliability Standard TPL-002-0 provides that the effect of non-
operation of primary protection systems be studied for a valid
assessment of system reliability.
V. Comment Procedures
30. The Commission invites interested persons to submit comments on
the matters and issues proposed in this notice to be adopted, including
any related matters or alternative proposals that commenters may wish
to discuss. Comments are due May 10, 2010. Comments must refer to
Docket No. RM10-6-000, and must include the commenter's name, the
organization they represent, if applicable, and their address in their
comments.
31. The Commission encourages comments to be filed electronically
via the eFiling link on the Commission's Web site at https://www.ferc.gov. The Commission accepts most standard word processing
formats. Documents created electronically using word processing
software should be filed in native applications or print-to-PDF format
and not in a scanned format. Commenters filing electronically do not
need to make a paper filing.
32. Commenters that are not able to file comments electronically
must send an original and 14 copies of their comments to: Federal
Energy Regulatory Commission, Secretary of the Commission, 888 First
Street, NE., Washington, DC 20426.
33. All comments will be placed in the Commission's public files
and may be viewed, printed, or downloaded remotely as described in the
Document Availability section below. Commenters on this proposal are
not required to serve copies of their comments on other commenters.
VI. Document Availability
34. In addition to publishing the full text of this document in the
Federal Register, the Commission provides all interested persons an
opportunity to view and/or print the contents of this document via the
Internet through FERC's Home Page (https://www.ferc.gov) and in FERC's
Public Reference Room during normal business hours (8:30 a.m. to 5 p.m.
Eastern time) at 888 First Street, NE., Room 2A, Washington DC 20426.
35. From FERC's Home Page on the Internet, this information is
available on eLibrary. The full text of this document is available on
eLibrary in PDF and Microsoft Word format for viewing, printing, and/or
downloading. To access this document in eLibrary, type the docket
number excluding the last three digits of this document in the docket
number field.
36. User assistance is available for eLibrary and the FERC's Web
site during normal business hours from FERC Online Support at 202-502-
6652 (toll free at 1-866-208-3676) or e-mail at
ferconlinesupport@ferc.gov, or the Public Reference Room at (202) 502-
8371, TTY (202) 502-8659. E-mail the Public Reference Room at
public.referenceroom@ferc.gov.
By direction of the Commission.
Kimberly D. Bose,
Secretary.
[FR Doc. 2010-6565 Filed 3-24-10; 8:45 am]
BILLING CODE 6717-01-P