Energy Conservation Program: Test Procedures for Walk-In Coolers and Walk-In Freezers, 186-218 [E9-30884]
Download as PDF
186
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
DEPARTMENT OF ENERGY
10 CFR Part 431
[Docket No. EERE–2008–BT–TP–0014]
RIN 1904–AB85
Energy Conservation Program: Test
Procedures for Walk-In Coolers and
Walk-In Freezers
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
AGENCY: Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Notice of proposed rulemaking
and public meeting.
SUMMARY: Pursuant to the Energy Policy
and Conservation Act, as amended, the
U.S. Department of Energy (DOE) is
proposing test procedures for measuring
the energy consumption of walk-in
coolers and walk-in freezers
(collectively ‘‘walk-in equipment’’ or
‘‘walk-in(s)’’), definitions to delineate
the products covered by the test
procedures, and provisions (including a
sampling plan) for manufacturers to
implement the test procedures. The
notice also addresses enforcement
issues as they relate to walk-in
equipment. Concurrently, DOE is
undertaking an energy conservation
standards rulemaking for this
equipment. Any data gathered through
the use of the test procedure adopted by
DOE will be used in evaluating any
potential standards for this equipment.
Once these standards are promulgated,
the adopted test procedures will be used
to determine equipment efficiency and
compliance with the standards.
DATES: DOE will hold a public meeting
in Washington, DC on Thursday,
February 11, 2010, beginning at 9 a.m.
DOE must receive requests to speak at
the meeting before 4 p.m., Thursday,
January 28, 2010. DOE must receive a
signed original and an electronic copy
of statements to be given at the public
meeting before 4 p.m., Thursday,
January 28, 2010.
DOE will accept comments, data, and
information regarding this notice of
proposed rulemaking (NOPR) before or
after the public meeting, but no later
than March 22, 2010. See section V,
‘‘Public Participation,’’ of this NOPR for
details.
ADDRESSES: The public meeting will be
held at the U.S. Department of Energy,
Forrestal Building, Room 8E–089, 1000
Independence Avenue, SW.,
Washington, DC 20585–0121. To attend
the public meeting, please notify Ms.
Brenda Edwards at (202) 586–2945.
Please note that foreign nationals
participating in the public meeting are
subject to advance security screening
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
procedures, requiring a 30-day advance
notice. If you are a foreign national and
wish to participate in the public
meeting, please inform DOE as soon as
possible by contacting Ms. Brenda
Edwards at (202) 586–2945 so that the
necessary procedures can be completed.
Any comments submitted must
identify the NOPR for Test Procedures
for Walk-in Coolers and Freezers, and
provide docket number EERE–2008–
BT–TP–0014 and/or Regulation
Identifier Number (RIN) 1904–AB85.
Comments may be submitted using any
of the following methods:
1. Federal eRulemaking Portal: https://
www.regulations.gov. Follow the
instructions for submitting comments.
2. E-mail: WICF-2008-TP0014@hq.doe.gov. Include the docket
number EERE–2008–BT–TP–0014 and/
or RIN 1904–AB85 in the subject line of
the message.
3. Postal Mail: Ms. Brenda Edwards,
U.S. Department of Energy, Building
Technologies Program, Mailstop EE–2J,
1000 Independence Avenue, SW.,
Washington, DC 20585–0121. Please
submit one signed original paper copy.
4. Hand Delivery/Courier: Ms. Brenda
Edwards, U.S. Department of Energy,
Building Technologies Program, 950
L’Enfant Plaza, SW., 6th Floor,
Washington, DC 20024. Please submit
one signed original paper copy.
For detailed instructions on
submitting comments and additional
information on the rulemaking process,
see section V, ‘‘Public Participation,’’ of
this document.
Docket: For access to the docket to
read background documents or
comments received, visit the U.S.
Department of Energy, Resource Room
of the Building Technologies Program,
950 L’Enfant Plaza, SW., 6th Floor,
Washington, DC 20024, (202) 586–2945,
between 9 a.m. and 4 p.m. Monday
through Friday, except Federal holidays.
Please call Ms. Brenda Edwards at the
above telephone number for additional
information regarding visiting the
Resource Room.
FOR FURTHER INFORMATION CONTACT: Mr.
Charles Llenza, U.S. Department of
Energy, Building Technologies Program,
EE–2J, 1000 Independence Avenue,
SW., Washington, DC 20585–0121, (202)
586–2192, Charles.Llenza@ee.doe.gov or
Mr. Michael Kido, Esq., U.S.
Department of Energy, Office of General
Counsel, GC–72, 1000 Independence
Avenue, SW., Washington, DC 20585–
0121, (202) 586–8145,
Michael.Kido@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
Table of Contents
I. Authority and Background
PO 00000
Frm 00002
Fmt 4701
Sfmt 4702
II. Summary of the Proposal
III. Discussion
A. Overall Approach
1. Basic Model
2. Approach Option 1: Test the Unit as a
Whole
3. Approach Option 2: Allow
Manufacturers To Use Alternative
Energy Determination Methods (AEDMs)
4. Proposed Option and Recommendation:
Separate Envelope and Refrigeration
Tests
B. Envelope
1. Overview of the Test Procedure
2. Test Methods
a. Insulation
b. Air Infiltration
c. Steady-State Infiltration Test
3. Calculations
a. Energy Efficiency Ratio
b. Heat Gain Through the Envelope Due to
Conduction
c. Heat Gain Due to Infiltration
d. Envelope Component Electrical Loads
e. Normalization
f. Daily Energy Consumption Coefficients
C. Refrigeration System
1. Overview of the Test Procedure
2. Test Conditions
3. Test Methods
4. Measurements and Calculations
D. Compliance, Certification, and
Enforcement
1. Provisions for Energy Conservation
Standards Developed by the Department
of Energy
2. Provisions for Existing Design Standards
Prescribed by Congress
IV. Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the National
Environmental Policy Act
C. Review Under the Regulatory Flexibility
Act
D. Review Under the Paperwork Reduction
Act
E. Review Under the Unfunded Mandates
Reform Act of 1995
F. Review Under the Treasury and General
Government Appropriations Act, 1999
G. Review Under Executive Order 13132
H. Review Under Executive Order 12988
I. Review Under the Treasury and General
Government Appropriations Act, 2001
J. Review Under Executive Order 13211
K. Review Under Executive Order 12630
L. Review Under Section 32 of the Federal
Energy Administration (FEA) Act of 1974
V. Public Participation
A. Attendance at Public Meeting
B. Procedure for Submitting Requests to
Speak
C. Conduct of Public Meeting
D. Submission of Comments
E. Issues on Which DOE Seeks Comment
1. Test Procedure Improvements
2. Basic Model
3. Separate Envelope and Refrigeration
Tests
4. Definition of Envelope
5. Effect of Impermeable Skins on LongTerm R Value
6. Measuring Long-Term R Value Using
American Society for Testing and
Materials (ASTM) C1303–08
7. Infiltration
E:\FR\FM\04JAP2.SGM
04JAP2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
8. Nominal Coefficient of Performance of
Refrigeration
9. Measuring the U Value of glass
10. Floor R Value
11. Electrical Duty Cycle
12. Normalization Factor
13. Daily Energy Consumption Coefficients
14. Definition of Refrigeration System
15. Measurements and Calculations of
Energy Use of Refrigeration Systems
16. Impacts on Small Businesses
VI. Approval of the Office of the Secretary
I. Authority and Background
Title III of the Energy Policy and
Conservation Act of 1975, as amended
(EPCA or the Act) sets forth a variety of
provisions designed to improve energy
efficiency. Part B of Title III (42 U.S.C.
6291–6309) provides for the Energy
Conservation Program for Consumer
Products Other Than Automobiles. The
National Energy Conservation Policy
Act (NECPA), Public Law 95–619,
amended EPCA to add Part C of Title III,
which established an energy
conservation program for certain
industrial equipment. (42 U.S.C. 6311–
6317) (These parts were subsequently
redesignated as Parts A and A–1,
respectively, for editorial reasons.)
Section 312 of the Energy Independence
and Security Act of 2007 (EISA 2007)
further amended EPCA by adding
certain equipment to this energy
conservation program, including walkin coolers and walk-in freezers
(collectively ‘‘walk-in equipment’’ or
‘‘walk-ins’’), the subject of this
rulemaking. (42 U.S.C. 6311(1), (2),
6313(f) and 6314(a)(9))
EPCA defines walk-in equipment as
follows:
(A) In general.—
The terms ‘‘walk-in cooler’’ and
‘‘walk-in freezer’’ mean an enclosed
storage space refrigerated to
temperatures, respectively, above, and
at or below 32 degrees Fahrenheit that
can be walked into, and has a total
chilled storage area of less than 3,000
square feet.
(B) Exclusion.—
The terms ‘‘walk-in cooler’’ and
‘‘walk-in freezer’’ do not include
products designed and marketed
exclusively for medical, scientific, or
research purposes. (42 U.S.C. 6311(20))
Walk-ins covered by this rulemaking
may be located indoors or outdoors.
They may be used exclusively for
storage, but they may also have
transparent doors or panels for the
purpose of displaying stored items.
Examples of items that may be stored in
walk-ins include, but are not limited to,
food, beverages, and flowers. DOE notes
that any equipment that meets the above
definition is potentially subject to
regulation.
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
Under the Act, the overall program
consists essentially of the following
parts: testing, labeling, and Federal
energy conservation standards. The
testing requirements for covered
equipment consist of test procedures,
prescribed under EPCA. These test
procedures are used in several different
ways: (1) Any data from the use of these
procedures are used as a basis in
developing standards for covered
products or equipment; (2) the test
procedure is used when determining
equipment compliance with those
standards; and (3) manufacturers of
covered equipment must use the
procedure to establish that their
equipment complies with energy
conservation standards promulgated
pursuant to EPCA and when making
representations about equipment
efficiency.
Section 343 of EPCA (42 U.S.C. 6314)
sets forth generally applicable criteria
and procedures for DOE’s adoption and
amendment of such test procedures.
That provision requires that the test
procedures promulgated by DOE be
reasonably designed to produce test
results which reflect energy efficiency,
energy use, and estimated operating
costs of the covered equipment during
a representative average use cycle. It
also requires that the test procedure not
be unduly burdensome to conduct. See
42 U.S.C. 6314(a)(2). As part of the
process for promulgating a test
procedure, DOE must publish the
procedure that it plans to propose and
offer the public an opportunity to
present oral and written comments on
them. Consistent with Executive Order
12889 and EPCA (see 42 U.S.C. 6314(b)),
DOE provides a minimum comment
period of 75 days on a proposed test
procedure. As to the test procedures for
walk-in equipment, EPCA prescribes the
following requirements:
(A) In general.—
For the purpose of test procedures for
walk-in coolers and walk-in freezers:
(i) The R value shall be the 1/K factor
multiplied by the thickness of the panel.
(ii) The K factor shall be based on
ASTM [American Society for Testing
and Materials] test procedure C518–
2004.
(iii) For calculating the R value for
freezers, the K factor of the foam at 20
°F (average foam temperature) shall be
used.
(iv) For calculating the R value for
coolers, the K factor of the foam at 55
°F (average foam temperature) shall be
used.
(B) Test Procedure.—
(i) In general.—Not later than January
1, 2010, the Secretary shall establish a
test procedure to measure the energy-
PO 00000
Frm 00003
Fmt 4701
Sfmt 4702
187
use of walk-in coolers and walk-in
freezers.
(ii) Computer modeling.—The test
procedure may be based on computer
modeling, if the computer model or
models have been verified using the
results of laboratory tests on a
significant sample of walk-in coolers
and walk-in freezers. (42 U.S.C.
6314(a)(9))
On February 4, 2009, DOE held a
public meeting on the framework
document it issued concerning the DOE
rulemaking to evaluate walk-in
equipment for energy conservation
standards. See 74 FR 411 (Jan. 6, 2009)
and 74 FR 1992 (Jan. 14, 2009). Both the
framework document and meeting
discussed the possible test procedures
for this equipment that DOE was
considering at that time, and gave
interested parties an opportunity to
submit comments. Today’s notice
addresses those comments and proposes
test procedures for walk-in equipment.
II. Summary of the Proposal
In today’s notice, DOE proposes to
adopt new test procedures for
determining the energy use of walk-in
cooler and walk-in freezer equipment to
address the statutory requirement to
establish a test procedure by January 1,
2010. (42 U.S.C. 6314(a)(9)(B))
Concurrently, DOE is undertaking an
energy conservation standards
rulemaking for walk-in equipment to
address the statutory requirement to
establish performance standards no later
than January 1, 2012. (42 U.S.C.
6313(f)(4)(A)) DOE will use any data
resulting from use of the test procedure
that DOE adopts to evaluate potential
performance standards for this
equipment. Furthermore, once
performance standards are issued,
manufacturers would be required to use
the test procedures to determine
compliance with such standards and for
any representations regarding the energy
use of walk-in equipment they produce.
This test procedure, once adopted,
would serve as the means for
ascertaining compliance with the
appropriate standards in an enforcement
action.
For the reasons described below, DOE
proposes to adopt a test procedure that
contains two separate test methods. This
approach is necessary because there are
typically two manufacturers of walk-in
equipment: One who manufactures the
envelope (i.e., the insulated box in
which the refrigerated or frozen items
are stored) and one who manufactures
the refrigeration system (i.e., the
mechanism that provides the means by
which to feed chilled air into the
envelope). One method determines the
E:\FR\FM\04JAP2.SGM
04JAP2
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
188
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
energy consumption of the refrigeration
system of the walk-in cooler or freezer.
The other method determines the energy
consumption of the envelope, which is
the sum of the energy use associated
with heat transmission through the
envelope in the form of conduction
through the walls and air infiltration
through openings, and the power
consumed by electrical components that
are part of the envelope. Each of the two
components, the refrigeration system
and the envelope, is considered
separately and the energy consumption
of each component is calculated using
the applicable test procedure. DOE
believes that the approach is consistent
with the requirements in EPCA because
the results of the two tests will
represent, in the aggregate, the total
energy consumption of walk-in coolers
and freezers.
Using this approach, DOE believes
that the proposed test procedures will
adequately measure the energy
consumption of walk-in equipment by
capturing the energy consumption of
both components. However, DOE
requests comment from stakeholders on
improvements or changes to the
proposed test procedures and will
consider modifications that improve the
accuracy, appropriateness for the
equipment being tested, repeatability of
test results for the same or similar units,
comparability of results for different
types of units, burden on manufacturers,
precision of language, or other elements
of the procedures. In submitting
comments, interested parties should
state the nature of the recommended
modification and explain how it would
improve upon the test procedure
proposed in this NOPR. Commenters
should also submit data, if any, to
support their positions.
DOE’s adoption of the proposed test
procedures, which would be applicable
to all walk-in equipment, would not
necessarily mean that DOE would adopt
a single energy conservation standard or
set of labeling requirements for all walkin equipment. In the separate
rulemaking proceeding concerning
energy conservation standards for walkin equipment, DOE may divide such
equipment into classes and may
conclude that standards are not
warranted for some classes of
equipment that are within the scope of
today’s test procedure. Furthermore,
DOE may create a separate standard for
each class of equipment that includes a
utility- or performance-related feature
that another equipment class lacks, and
that affects energy consumption.
DOE also notes that the National
Technology Transfer and Advancement
Act of 1995 (Pub. L. 104–113) directs
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
Federal agencies to use voluntary
consensus standards in lieu of
Government standards whenever
possible. Consequently, as described in
the following paragraphs, DOE
attempted to incorporate by reference in
its test procedures generally accepted
rules or recognized industry standards
such as those issued by the AirConditioning, Heating and Refrigeration
Institute (AHRI), the American Society
of Heating, Refrigerating, and Air
Conditioning Engineers (ASHRAE), the
American National Standards Institute
(ANSI), and/or ASTM International
(ASTM), that provide either specific
aspect(s) of the test procedure, or the
complete test procedure, for the
specified equipment.
III. Discussion
In the following section, DOE
describes the overall approach it
proposes to follow with respect to the
adoption of a test procedure for walkins. This approach results from the
characteristics of walk-in equipment
and is based in part on the basic model
definition that DOE currently uses to
help establish testing requirements for
manufacturers to follow. The following
section also addresses issues raised by
commenters, which included:
Manufacturers (Craig Industries (Craig),
Manitowoc, Nor-Lake); trade
associations (AHRI); utility companies
(Southern California Edison (SCE),
Sacramento Municipal Utility District
(SMUD), San Diego Gas and Electric
(SDG&E)); and advocacy groups
(Appliance Standards Awareness
Project (ASAP), American Council for
an Energy-Efficient Economy (ACEEE),
Natural Resources Defense Council
(NRDC), Northwest Energy Efficiency
Alliance (NEEA)).
A. Overall Approach
DOE developed today’s proposed test
procedure to set forth the testing
requirements for walk-in equipment. In
the framework document, DOE
considered two overall approaches
manufacturers could take to determine
the energy consumption of walk-in
coolers and freezers. First, DOE
considered using a modified version of
the Air-Conditioning and Refrigeration
Institute (ARI) Standard 1200–2006,
‘‘Performance Rating of Commercial
Refrigerated Display Merchandisers and
Storage Cabinets’’ (ARI 1200–2006),
which uses the test method described in
the American National Standards
Institute/American Society of Heating,
Refrigerating, and Air Conditioning
Engineers (ANSI/ASHRAE) Standard
72–2005, ‘‘Method of Testing
Commercial Refrigerators and Freezers’’
PO 00000
Frm 00004
Fmt 4701
Sfmt 4702
(ANSI/ASHRAE 72–2005). Second, DOE
considered allowing manufacturers to
determine the efficiency of some of their
products using alternative efficiency
determination methods (AEDMs).
(An AEDM is a predictive mathematical
model, developed from engineering
analyses of design data and
substantiated by actual test data, which
represents the energy consumption
characteristics of one or more basic
models.)
DOE received comments on these
proposed approaches, many of which
were opposed to both approaches. The
comments DOE received, and DOE’s
responses, are discussed in more detail
below. After considering these
comments and reviewing the matter
further, DOE is proposing separate test
procedures for the envelope (insulated
box) and the refrigeration system. DOE
discusses the details of its proposals and
addresses manufacturer comments in
the following subsections.
1. Basic Model
Under EPCA, which prohibits the
distribution in commerce of covered
equipment that do not comply with the
applicable standard, each model of
covered equipment is potentially subject
to energy efficiency testing consistent
with the relevant requirements for that
equipment. However, walk-in
manufacturers typically make numerous
envelope models and, even within a
single model, the units are often
customized in multiple ways. To reduce
this potential burden, DOE proposes
following the approach it has used for
other equipment by allowing
manufacturers to group equipment or
models with essentially identical energy
consumption characteristics into a
single family of models, called a basic
model. This concept has been
established both for residential
appliances and commercial and
industrial equipment covered under
EPCA. (See Title 10 of the Code of
Federal Regulations (10 CFR) 430.2,
which covers 26 products, and 10 CFR
431.12, 431.62, 431.132, 431.172,
431.192, 431.202, 431.222, 431.262, and
431.292, which cover various
equipment.)
Walk-in refrigeration systems are
often manufactured according to the
same basic blueprint design, and any
particular model could incorporate
modifications that do not significantly
affect the energy efficiency of the
system. For example, manufacturers
often sell systems that are designed to
operate at different voltages. This allows
them to market to customers with
different electrical capabilities. The
operating voltage affects the energy
E:\FR\FM\04JAP2.SGM
04JAP2
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
efficiency of the system, but very
minimally. If manufacturers were
required to test the efficiency of each
model with a different feature, the
testing burden would be significant, but
yield effectively redundant results.
Therefore, DOE provides for testing of a
basic model of refrigeration systems that
may not be identical, but would not
have any electrical, physical, or
functional characteristics that
significantly affect energy consumption.
Features that may affect the energy
consumption of walk-in cooler and
freezer refrigeration systems include
compressor size, fan motor type, and
heat exchanger coil dimensions.
Walk-in envelopes are often
manufactured according to the same
basic design, but the equipment is so
highly customized that each walk-in a
manufacturer builds may be unique, and
potentially subject to testing as a
separate basic model. For instance,
changing the size of the envelope would
affect the energy consumption obtained
by the test procedure, even if the
construction methods and materials
were the same. To address this
possibility, DOE proposes (1) grouping
walk-in envelopes with essentially
identical construction methods,
materials, and components into a single
basic model, and (2) adopting a
calculation methodology for
determining the energy consumption of
units within the basic model. This
methodology would require a
manufacturer to test one unit of the
basic model and then calculate daily
energy consumption coefficients
(DECCs) for that basic model according
to the test procedure. The manufacturer
could then apply those DECCs to other
units within a basic model even if those
units were not identical, to obtain the
energy consumption of those units.
Although units within a basic model
need not share identical dimensions,
finishes, and non-energy-related
features (e.g., shelving or door kick
plates), they must have been
manufactured using substantially the
same construction methods, materials,
and components. A few examples of
factors that would necessitate a different
basic model include changing the type
of insulating foam, the method of
locking together the panels of the walkin envelope, or the electrical
characteristics of the lighting. Examples
of factors that may not constitute a
different basic model include the type of
exterior metal finish, the dimensions of
the envelope, and the number of doors
of the same type. The exterior metal
finish would not have a substantial
impact on the efficiency of the
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
envelope. Dimensions and number of
doors, on the other hand, would be
accounted for in the energy
consumption calculation using the
DECCs from the unit of the basic model
that was tested. (See section III.B.3.f for
further discussion of DECCs.)
All of the equipment included in a
basic model must be within the same
equipment class. Components of similar
design may be substituted in a basic
model without requiring additional
testing if the represented energy
consumption measurements continue to
satisfy the provisions for sampling and
testing. Only representative samples
within each basic model would be
tested.
For walk-ins, DOE is considering
adopting the following definition of
‘‘basic model:’’ ‘‘Basic Model means all
units of a given type of walk-in
equipment manufactured by a single
manufacturer, and—(1) With respect to
envelopes, which do not have any
differing construction methods,
materials, components, or other
characteristics that significantly affect
the energy consumption characteristics.
(2) With respect to refrigeration systems,
which have the same primary energy
source and which do not have any
differing electrical, physical, or
functional characteristics that
significantly affect energy
consumption.’’ DOE requests comment
on its proposed basic model approach.
2. Approach Option 1: Test the Unit as
a Whole
In the framework document, DOE
considered developing a test procedure
for walk-ins by adapting an existing test
procedure for commercial refrigeration
equipment, such as ARI 1200–2006.
This approach would require an entire
walk-in cooler or freezer to be
physically tested within a controlled
test chamber in order to evaluate its
energy consumption over a period of
time. During the standards framework
public meeting, DOE requested
comments on the feasibility of this
approach. Interested parties responded
with significant reservations about using
a modified version of the ARI 1200–
2006 test procedure, citing crucial
differences between walk-ins and
commercial refrigeration equipment.
In particular, interested parties noted
that walk-ins are physically different
from commercial refrigerators in ways
that make a full-system test burdensome
or impractical. Manitowoc stated that
for very large walk-ins, around the
3,000-square-foot limit in the EPCA
definition, manufacturers might not
have a large enough test facility to make
the measurements necessary for the ARI
PO 00000
Frm 00005
Fmt 4701
Sfmt 4702
189
1200–2006 test procedure in a
controlled environment. (Manitowoc,
Public Meeting Transcript, No. 15 at p.
59) (In this and subsequent citations,
‘‘Public Meeting Transcript’’ refers to
the transcript of the February 4, 2009,
public meeting on standards for walk-in
coolers and freezers. ‘‘No. 15’’ refers to
the document number of the transcript
in the Docket for the DOE rulemaking
on standards for walk-in coolers and
freezers, Docket No. EERE–2008–BT–
TP–0014; and the page references refer
to the place in the transcript where the
statement preceding appears.) Kason
Industries also stated that it would be
practically impossible to have a large
enough controlled climate enclosure to
test medium to large walk-ins, and
added that if a walk-in were a freestanding structure, testing it as a whole
building would not be practical. (Kason,
No. 16 at pp. 1, 4) (In this and
subsequent citations, the document
number refers to the number of the
comment in the Docket for the DOE
rulemaking on standards for walk-in
coolers and freezers, Docket No. EERE–
2008–BT–TP–0014; and the page
references refer to the place in the
document where the statement
preceding appears.) The AirConditioning, Heating, and Refrigeration
Institute (AHRI) stated that the proposed
test procedures were not practical
because it would be costly to physically
test walk-ins. (AHRI, No. 33 at p. 2)
Commenters also noted that the
market for walk-in coolers and freezers
is structured differently from the market
for commercial refrigeration equipment,
making a direct comparison between
these types of equipment difficult.
Manitowoc stated that the envelope of a
particular unit of walk-in equipment
may be manufactured by one company
and the refrigeration system by another
company. ARI 1200–2006 would require
the two systems to be integrated before
running the test, which would place the
burden on the installer or someone
beyond the manufacturer of the
subsystems. (Manitowoc, Public
Meeting Transcript, No. 15 at p. 59)
AHRI agreed that the ARI 1200–2006
standard might not be the right
approach and that DOE would need to
separate the mechanical system from the
envelope. (AHRI, Public Meeting
Transcript, No. 15 at p. 62)
In addition to these concerns,
commenters identified a deficiency in
the ARI 1200–2006 test procedure. SCE
stated that the majority of potential
energy savings can be achieved using
floating head pressure and variablespeed evaporator fans, both of which
have varying effects depending on the
time of day and the regional climate
E:\FR\FM\04JAP2.SGM
04JAP2
190
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
because the savings associated with
each feature can depend on the ambient
temperature and usage patterns of the
walk-in over the course of a day.
Because ARI 1200–2006 is a steady-state
test, it would not capture the energy
savings from either option. (SCE, Public
Meeting Transcript, No. 15 at p. 63)
AHRI agreed that the test procedure
should capture savings from a control
strategy or variable-speed components,
both of which could optimize the
operation of the walk-in for a variety of
ambient conditions and usage patterns.
An example of optimization would be
allowing elements of the refrigeration
system to turn off or reduce their
operation at night when the walk-in is
not being accessed. (AHRI, No. 33 at p.
2)
After considering these comments,
DOE believes that an adapted version of
ARI 1200–2006 would be inadequate to
use as the test procedure for walk-in
equipment. ARI 1200–2006 contains too
many limitations and practical
difficulties that would make it very
difficult to effectively implement as a
workable test procedure for walk-in.
Therefore, DOE is no longer considering
this approach.
3. Approach Option 2: Allow
Manufacturers To Use Alternative
Energy Determination Methods
(AEDMs)
DOE’s framework document also
presented an alternative that would
permit the use of an AEDM when
determining walk-in energy
consumption to help relieve the testing
burden on manufacturers. An AEDM is
a predictive mathematical model,
developed from engineering analyses of
design data and substantiated by actual
test data which represents the energy
consumption characteristics of one or
more basic models. After confirming the
accuracy of an AEDM, the manufacturer
would apply the AEDM to basic models
to determine their energy consumption
without conducting any physical
testing.
Applying this approach, the
manufacturer would confirm the
accuracy of the AEDM using the
following method. First, the
manufacturer would determine through
actual testing the energy consumption of
a certain number of its basic models that
would be selected in accordance with
criteria specified in the procedure.
Second, the manufacturer would apply
the AEDM to these same basic models.
The AEDM would be considered
sufficiently accurate only if: (1) The
predicted total energy consumption of
each of these basic models, calculated
by applying the AEDM, is within a
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
certain percentage of the total energy
consumption determined from the
testing of that basic model; and (2) the
average of the predicted total energy
consumption for the tested basic
models, calculated by applying the
AEDM, is within a certain percent of the
average of the total energy consumption
determined from testing these basic
models. Under this approach, once the
manufacturer verifies the accuracy of
the AEDM, the manufacturer can use the
AEDM to determine the energy
consumption of other basic models
without having to test those models.
DOE requested comments on this
approach during the framework public
meeting, both in terms of how to
implement the approach and whether
such an approach was valid for walk-ins
at all. DOE received several relevant
comments, which are described and
addressed below.
Given the unprecedented nature of
using an AEDM to rate this type of
equipment, DOE needed to determine
both an appropriate sample size for
verifying an AEDM and an acceptable
minimum accuracy percentage for an
AEDM. During the framework public
meeting, DOE requested comments on
these two values. AHRI could not
provide feedback on how accurate the
AEDM should be because DOE had not
yet determined the test metric to apply.
(AHRI, Public Meeting Transcript, No.
15 at p. 69) Manitowoc agreed that the
test methodology needs to be
established and experiments conducted
to collect data that would be used to
validate AEDMs. (Manitowoc, Public
Meeting Transcript, No. 15 at p. 70) In
a written comment, Kason Industries
stated that an AEDM with a minimum
accuracy of 66 percent would
encompass a majority of the wide range
of walk-in cooler and freezer
applications. (Kason, No. 16 at p. 2) No
commenter provided substantive data
that DOE would use in its analysis to
help support a particular sample size.
Accordingly, DOE did not receive
enough data from stakeholders that
could help it determine an appropriate
sample size or accuracy range to
substantiate an AEDM.
During the public meeting, DOE also
requested comments on the possibility
of allowing manufacturers to take this
approach to rate their walk-ins. Kason
stated that an AEDM procedure would
be preferable to using a physical test
because the majority of walk-ins are
custom-made by size, ambient
temperature, and refrigeration demands.
Therefore, it would be very difficult to
create a test procedure that encompasses
the range of walk-in equipment. (Kason,
No. 16 at p. 1) Kason suggested that, as
PO 00000
Frm 00006
Fmt 4701
Sfmt 4702
an alternative to testing the system as a
whole, an AEDM could be based on
determining efficiencies and
performance characteristics for the
principal components of a walk-in
considering three factors: insulation and
air tightness of the external envelope
and door, efficiency of the refrigeration
system for steady-state storage load
(similar to the efficiency rating system
for HVAC), and performance of the
refrigeration system for removal of
process heat and equipment-generated
heat. (Kason, No. 16 at p. 2)
Other interested parties commented
that allowing manufacturers to develop
their own calculation methodology or
software program as an AEDM could be
problematic. Owens Corning questioned
whether there could be a comparison
among ratings published by
manufacturers that developed different
AEDMs. (Owens Corning, Public
Meeting Transcript, No. 15 at p. 64)
Craig stated that manufacturers who
devise their own test procedures could
write them in a way that benefits their
own company. (Craig, Public Meeting
Transcript, No. 15 at pp. 68–69) SCE
stated that allowing manufacturers to
develop their own software as an AEDM
could be unfair to manufacturers with
fewer resources, because the software is
expensive and time-consuming to
develop. Instead, SCE suggested that it
would be better to have a transparent
analysis method with the algorithms
available to all participants and the data
in a standardized format. (SCE, Public
Meeting Transcript, No. 15 at p. 71)
Craig replied that many manufacturers
have sizing programs, which may be
proprietary, to calculate the total load of
the walk-in, accessories, and product
load, and to size the refrigeration system
properly for the energy requirements of
the envelope. (Craig, Public Meeting
Transcript, No. 15 at pp. 77–78 and No.
22 at p. 4) However, Craig stressed that
requiring manufacturers to follow the
same model developed or approved by
DOE, would be fair to different
manufacturers and provide consistent
information to end users. (Craig, Public
Meeting Transcript, No. 15 at p. 94 and
No. 22 at p. 5)
ACEEE asserted that it would be
difficult for DOE to work with many
proprietary models, some of which
might be difficult to verify. (ACEEE,
Public Meeting Transcript, No. 15 at p.
94) NEEA also said that if an AEDM
were used, the software should be
equally available to all manufacturers
and code officials for the purpose of
determining compliance. (NEEA, No. 18
at p. 3) Crown Tonka stated that a
standard configuration and standard test
should be developed to create a baseline
E:\FR\FM\04JAP2.SGM
04JAP2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
for energy usage, with normalizing
factors associated with configuration
changes. (Crown Tonka, No. 23 at p. 1)
Owens Corning reiterated that a single
AEDM should be accepted to keep
comparisons consistent. (Owens
Corning, No. 31 at p. 2)
DOE had previously understood that
manufacturers would develop their own
AEDMs and would verify their accuracy
by testing a small number of walk-in
models. However, as discussed above,
most interested parties indicated that
allowing manufacturers to develop their
own rating calculations or software
could be problematic, despite the fact
that the calculations and software
would need to be verified. Therefore,
DOE does not propose to allow
manufacturers to develop their own
AEDMs. Instead, DOE developed its
own calculation methodology for
manufacturers to use in rating similar,
but not identical, units of walk-in
equipment. For further discussion on
this methodology, see section III.B.3.f.
4. Proposed Option and
Recommendation: Separate Envelope
and Refrigeration Tests
Both methods described above were
predicated on the assumption that an
entire walk-in unit is manufactured by
a single entity, which could either test
the walk-in as a whole according to ARI
Standard 1200–2006, or calculate the
overall efficiency using an AEDM. In
fact, as DOE learned, most walk-ins
have two main manufacturers: One who
manufactures the envelope and one who
manufactures the refrigeration system
that cools the interior of the envelope.
(Other manufacturers may be involved
in producing secondary components
—such as fan assemblies or lighting—
that are then purchased by the main
manufacturers and incorporated as part
of the refrigeration system or envelope.)
These two parts are manufactured
separately, and are often assembled
together in the field by a third-party
contractor who may not have been
responsible for the manufacture of
either part, and who may not have
testing or evaluation capabilities.
Because of this situation, DOE
developed, and is proposing, a different
approach for testing walk-ins, as
described below.
Specifically, DOE proposes separate
test procedures for the envelope and the
refrigeration system. The envelope
manufacturer would be responsible for
testing the envelope according to the
envelope test procedure, and the
refrigeration system manufacturer
would be responsible for testing the
refrigeration system according to the
refrigeration system test procedure.
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
Such an approach would be more likely
to generate usable data in support of
standards for both the envelope and the
refrigeration system during the
development of any energy conservation
standards for walk-in coolers and
freezers. The two test procedures are
described in sections III.B and III.C,
respectively.
There are several advantages to this
approach. First, having separate test
procedures would allow individual
component manufacturers to test their
components—the envelope and the
refrigeration system. These component
manufacturers would be more likely to
have access to the resources, equipment,
and personnel needed to conduct the
tests. On the other hand, the
‘‘manufacturer’’ of an entire walk-in
system (i.e., envelope and refrigeration
system combined), could be a third
party: A contractor who assembles the
walk-in from the separate components
and/or installs it in the field. This thirdparty assembler may even be the enduser or owner of the equipment. If a
walk-in is assembled in the field, testing
of the entire assembled system may not
be feasible due to lack of expertise and
the need for additional testing
equipment.
Second, this approach would result in
a significantly reduced testing burden
while ensuring compliance with any
standard DOE may develop. There are
many more assemblers and installers of
walk-ins than there are component
manufacturers. Because EPCA requires
manufacturers to demonstrate
compliance with energy conservation
standards, interpreting the term
‘‘manufacturer’’ to include assemblers
and installers, who may be contractors
or end-users, to demonstrate compliance
with a standard would impose the
compliance burden on entities who,
more likely than not, may not have
participated in the design and
manufacture (and therefore energy
efficiency) of the component parts.
Furthermore, this approach would
create substantial difficulties for DOE to
enforce any standards it promulgates for
walk-in equipment. While DOE
considered the possibility that including
assemblers and installers as parties
involved in the manufacture of this
equipment could encourage these
parties to take steps to ensure that
compliant equipment is installed, at this
time, DOE believes that the testing
burdens are best met by the envelope
and refrigeration system manufacturers
for the reasons discussed above.
Accordingly, under today’s proposal,
only envelope and refrigeration system
manufacturers would need to
demonstrate compliance with any
PO 00000
Frm 00007
Fmt 4701
Sfmt 4702
191
proposed standard through the use of
the test procedure. (DOE notes that
possible remedial action for failing to
satisfy these requirements include civil
penalties and injunctive relief to
prevent the continued sale and
distribution of noncompliant
equipment.) (42 U.S.C. 6303–6304)
DOE requests comment on this
proposed approach and whether it is
appropriate for walk-ins.
B. Envelope
As described earlier, the envelope
consists of the insulated box in which
the stored items reside. The following
discussion describes in greater detail the
test procedure DOE is proposing for the
walk-in envelope. DOE also addresses
issues raised by interested parties.
This procedure contains the proposed
methodology for evaluating the
performance characteristics of the
insulation as well as methods for testing
thermal energy gains related to air
infiltration caused by use (door
openings) and imperfections in wall
interfaces or door gasketing material.
Heat gain due to internal electrical
components is an additional
consideration.
The proposed procedure utilizes the
data obtained to calculate a measure of
energy use associated with the
envelope. In other words, the test
procedure calculates the effect of the
envelope’s characteristics and
components on the energy consumption
of the walk-in as a whole. This includes
the energy consumption of electrical
components present in the envelope
(such as lights) and variation in the
energy consumption of the refrigeration
system due to heat loads introduced as
a function of envelope performance,
such as conduction of heat through the
walls of the envelope. The effect on the
refrigeration system is determined by
calculating the energy consumption of a
theoretical, or nominal, refrigeration
system, were it to be paired with the
tested envelope. Using the same
nominal refrigeration system
characteristics allows for direct
comparison of the performance of walkin envelopes across a range of sizes,
product classes, and levels of feature
implementation.
The test procedure obtains a metric of
energy use associated with the envelope
of a walk-in cooler or freezer, consistent
with the statutory requirement (42
U.S.C. 6314(a)(9)(B)(i)). For purposes of
this rulemaking, DOE interprets the
term ‘‘energy use’’ to describe the sum
of (a) the electrical energy consumption
of envelope components and (b) the
energy consumption of the walk-in
refrigeration equipment that is
E:\FR\FM\04JAP2.SGM
04JAP2
192
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
and details of the proposed test methods
are described in the following sections.
1. Overview of the Test Procedure
In accordance with EPCA, DOE is
developing test procedures to evaluate
the energy use associated with the
envelope of walk-in coolers and
freezers. The walk-in envelope includes,
but may not be limited to, walls, floor,
ceiling, seals, windows, and/or doors
comprised of single or composite
materials designed to isolate the
interior, refrigerated environment from
the ambient, external environment. For
the purposes of developing this test
procedure and evaluating potential
performance standards for walk-in
equipment, DOE considers the envelope
to also include lighting and other
energy-consuming components of the
walk-in that are not part of its
refrigeration system (e.g., motors for
automatic doors, anti-sweat heaters,
etc.). DOE is considering the following
definition for ‘‘envelope,’’ which would
be inserted into 10 CFR part 431:
(1) The portion of a walk-in cooler or
walk-in freezer that isolates the interior,
refrigerated environment from the
ambient, external environment; and
(2) All energy-consuming components
of the walk-in cooler or walk-in freezer
that are not part of its refrigeration
system.
DOE requests comments on this
proposed definition.
DOE also evaluated several available
industry test procedures to measure the
energy performance of various
components of the walk-in envelope,
but was unable to find a test procedure
that would evaluate the entire envelope
system. Consequently, DOE developed
its own methodology, including a
prescriptive calculation procedure,
which incorporates specific component
tests and allows for an overall energy
performance value of the envelope to be
determined. The proposed test
measurements and accompanying
calculation procedures to ascertain the
overall energy performance value are
described in the following sections.
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
contributed by the performance of the
envelope.
a. Insulation
Insulation comprises a significant
component of walk-in units. EPCA
specifies that ASTM C518–04,
‘‘Standard Test Method for Steady-State
Thermal Transmission Properties by
Means of the Heat Flow Meter
Apparatus,’’ must be used, along with
specific foam temperatures for freezer or
cooler applications specified in EPCA,
to determine the R value of individual
walk-in envelope insulation materials.
(42 U.S.C. 6314(a)(9)(A)) Commenters
identified two issues of significance for
DOE to consider when developing a test
procedure for insulation: aging and
moisture absorption. DOE discusses
these issues in the subsections that
follow.
2. Test Methods
As discussed above, DOE was unable
to find a single, existing comprehensive
test procedure for evaluating walk-in
cooler and freezer envelopes. However,
DOE identified and evaluated many
recognized industry standards that
could be applied to the testing of certain
components and characteristics of walkin envelopes. DOE incorporated an
insulation test and an air infiltration
test, with some modifications, into the
proposed test procedure. The evaluation
process, the results of the evaluation,
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
i. Aging of Foam Insulation
EPCA requires that the test procedure
for walk-ins use an R value that shall be
the 1/K factor multiplied by the
thickness of the panel. (42 U.S.C.
6314(a)(9)(A)) The Act does not specify
when the R value should be calculated,
a key issue interested parties raised at
the framework public meeting.
Specifying when the R-value should be
calculated is a critical consideration
because several sources indicate that the
R-value of certain materials can change
over time.
Craig stated that R values tend to
deteriorate over time and that different
materials exhibit unique rates of
deterioration. (Craig, Public Meeting
Transcript, No. 15 at p. 215 and No. 8
at p. 1) Craig expressed concern that
using an initial R value (R value as
measured within two weeks of
manufacture) to determine compliance
would ignore deterioration that occurs
in blown foams over time. Craig argued
that underestimating the energy use of
walk-ins would be the likely outcome of
using initial R-value, that it would be
misleading for end-users, and that it
would be inconsistent with the goals of
the EISA 2007 legislation and the
rulemaking process. (Craig, Public
Meeting Transcript, No.15 at p. 215) A
comment submitted jointly by
representatives of ASAP, ACEEE, and
NRDC (hereafter referred to as the ‘‘Joint
Comment’’) stated that the test
procedures used should account for the
potential degradation of panel
insulation and door seals over time.
(Joint Comment, No. 21 at p. 2) Craig
also recommended that DOE develop an
accelerated test procedure that
represents lifetime energy use and can
be completed within 6 months. (Craig,
No. 8 at p. 1)
PO 00000
Frm 00008
Fmt 4701
Sfmt 4702
In the context of foam insulation for
walk-ins and the building industry,
long-term thermal resistance (LTTR),
described in greater detail below, refers
to the impact of diffusion on the thermal
resistance of insulation materials. In
other words, the concentration of
gaseous blowing agents contained in the
foam, and which provide the foam with
much of its insulating value, is reduced
by both the diffusion of air into the foam
and the secondary process of the
blowing agent diffusing out of the foam.
Because air has a significantly lower
insulating value, the increased ratio of
air to blowing agent reduces the foam
insulation performance (this process is
also known as ‘‘aging’’). This diffusion
process causes foam to lose insulating
value, which is represented by its Rvalue. As a concept, LTTR represents
the R-value of foam material over its
lifetime by describing insulating
performance changes due to diffusion
over time.
DOE investigated the issue of aging in
foam insulation and found that it is
widely accepted that the material
properties of foam insulation made with
gaseous blowing agents, other than air
and including HFC–134a, HFC–245fa,
HFC–365mfc, cyclopentanes, change
over time. The amount of degradation
can range from roughly 10–35 percent
within 2 years of manufacture. Because
use of ASTM C518–04 reflects the
properties of a material at the time it is
tested, using ASTM C518–04 to measure
the insulating performance of a foam
material at the time of manufacture
would yield a result that differs from
that produced by the same test
conducted at some later point in time.
Additionally, research has found that
the vast majority of diffusion into and
out of foam materials manufactured
with blowing agents other than air
occurs within the first 5 years of
manufacture. Because the rate of
diffusion follows an exponential curve,
the majority occurs within the first year,
after which the diffusion curve changes
very little as it asymptotically
approaches the equilibrium point.
DOE found that various methods of
‘‘conditioning’’ foam prior to measuring
its insulating ability with American
Society for Testing and Materials
(ASTM) C518 have been developed in
order to test aged insulating value, or
LTTR. These standards are contained in
five foam material specifications:
(1) ASTM C578–09, ‘‘Standard
Specification for Rigid, Cellular
Polystyrene Thermal Insulation;’’
(2) ASTM C591–08a, ‘‘Standard
Specification for Unfaced Preformed
Rigid Cellular Polyisocyanurate
Thermal Insulation;’’
E:\FR\FM\04JAP2.SGM
04JAP2
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
(3) ASTM C1029–08, ‘‘Standard
Specification for Spray-Applied Rigid
Cellular Polyurethane Thermal
Insulation;’’
(4) ASTM C1126–04, ‘‘Standard
Specification for Faced or Unfaced Rigid
Cellular Phenolic Thermal Insulation;’’
and
(5) ASTM C1289–08, ‘‘Standard
Specification for Faced Rigid Cellular
Polyisocyanurate Thermal Insulation
Board.’’
DOE found that since their
development in the 1980s, the most
widely accepted conditioning methods
are the 180-day conditioning at 73 °F or
a 90-day conditioning at 140 °F. The
goal of the 90-day conditioning method
was to achieve the same aging result as
the 180-day method in a shorter period
of time. 180-day conditioning is used by
ASTM C591–08a and ASTM C578–09
and the 90-day condition is typically
used for ASTM C1089–08 and ASTM
C1126–04. By accelerating the
conditioning, the 90-day test sought to
reduce the time and cost burdens for
manufacturers. Although elevating the
temperature of foams did achieve a
faster rate of aging, subsequent research
found that the results were not reliable
indicators of actual aging because the
relationship between the diffusion
coefficient (a proportionality constant
that describes the force or rate of
diffusion for a given substance) and
temperature are different for each gas.
(Therese Stovall, ‘‘Measuring the Impact
of Experimental Parameters upon the
Estimated Thermal Conductivity of
Closed-Cell Foam Insulation Subjected
to an Accelerated Aging Protocol: TwoYear Results,’’ p. 1)
DOE found that efforts to develop an
accelerated aging method that did not
use elevated temperatures resulted in
the creation of ASTM C1303, which in
1995 introduced the slicing and scaling
method, also known as the ‘‘thin
slicing’’ method (a technique used to
slice the foam so that it ages more
rapidly as a function of reduced
thickness). In contrast to ASTM C578–
09, ASTM C591–08a, ASTM C1029–08,
ASTM C1126–04, and ASTM C1289–08,
which specify the use of either the 180day conditioning method or 90-day
accelerate conditioning method to age
the foam before measuring its thermal
resistance. In contrast, the thin slicing
method used in ASTM C1303–08 (the
most recent version of ASTM C1303)
was designed specifically to test the
aging of foam insulation in duration
shorter than 180 days, and without the
temperature elevation methodology
used in the 90-day test. (ASTM C1303–
08, section 5.3, at p. 3) By reducing the
length of the pathway for diffusion to
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
take place, the ‘‘aging’’ can be
accelerated without the confounding
effects caused by unique gas properties
of the material and blowing agent. The
results are used to determine the Rvalue of foam 5 years after manufacture,
a value that has been shown to correlate
strongly with the average R-value of
foam 15 years after manufacture. (ASTM
C1303–08, section 5.4, at p. 3)
In early 2000, the National Research
Council Canada and Institute for
Research in Construction (NRC–IRC)
developed CAN/ULC–S770–00. CAN/
ULC–S770–00 incorporated elements of
ASTM C1303–95 (the first version of
ASTM C1303) but altered that standard
by clarifying the slicing procedure used
in ASTM C1303–95, as differing
interpretations of the previous
procedure were thought to be causing
variations in the test results among
third-party testing facilities. These
changes sought to eliminate
inconsistency in the interpretation of
the slicing procedure and test setup to
ensure uniformity across testing labs. In
December 2000, CAN/ULC–S770–00
became the Canadian national
mandatory test for calculating the LTTR
of all foam insulation products (this test
has since been updated; the most recent
version is CAN/ULC–S770–03).
Members of the U.S.-based
Polyisocyanurate Insulation
Manufacturers Association (PIMA)
began to test their products using the
same procedure on January 1, 2003. The
LTTR calculated from this test
procedure is used for all building
insulation product labeling in Canada
and PIMA products in the United States.
Also in 2000, ASTM C1303–95 was
updated as ASTM C1303–00.
In a 2005 rule by the U.S. Federal
Trade Commission (FTC) in which the
FTC considered requiring ASTM
C1303–00 (the most recent version at
that time) for product labeling on all
foam insulation products, the FTC’s
review process revealed several
unresolved issues related to the test
procedure. (70 FR 31258 (May 31, 2005);
16 CFR Part 460, Labeling and
Advertising of Home Insulation: Trade
Regulation Rule, Final Rule)
Subsequently, ASTM C1303–00 was
updated to address these issues, which
included foam stack composition,
minimum slice thickness and slice
source, the time between manufacture
and test initiation, preparation of foamin-place samples, and other
clarifications of the procedure. This
updated version was published as
ASTM C1303–08 and is the most recent
version of the standard to date.
Some commenters noted during the
framework meeting that the application
PO 00000
Frm 00009
Fmt 4701
Sfmt 4702
193
of an impermeable vapor barrier to the
surface of the foam could reduce the
impact of aging. Depending on its end
use, foam insulation may have facers or
skins applied to act as a vapor barrier
and/or to enhance the bond of
construction glues. Kysor stated that
proper use of skins eliminates aging and
the associated reduction of R-value in
polyurethane panels. (Kysor
(attachment), No. 29 at p. 1)
DOE examined this issue and found
that foams used in walk-in panels are
sometimes protected by impermeable
barriers designed to prevent vapor and/
or air exchange into or out of the foam
or the interior of the walk-in. DOE
found research conducted by the
National Resource Council Canada
(NRCC) suggesting that impermeable
facers do not eliminate aging but may
delay the rate of aging and/or the final
equilibrium of the aged state.
(Mukhopadhyaya, P.; Bomberg, M.T.;
Kumaran, M.K.; Drouin, M.; Lackey, J.;
van Reenen, D.; Normandin, N., ‘‘LongTerm Thermal Resistance of
Polyisocyanurate Foam Insulation With
Impermeable Facers’’; Mukhopadhyaya,
P.; Bomberg, M.T.; Kumaran, M.K.;
Drouin, M.; Lackey, J.; van Reenen, D.;
Normandin, N., ‘‘Long-Term Thermal
Resistance of Polyisocyanurate Foam
Insulation With Gas Barrier’’;
Mukhopadhyaya, P.; Kumaran, M.K.
‘‘Long-Term Thermal Resistance Of
Closed-Cell Foam Insulation: Research
Update From Canada.’’) In one of the
summary observations of ‘‘Long-Term
Thermal Resistance of Polyisocyanurate
Foam Insulation With Gas Barrier,’’ the
NRCC noted, ‘‘a considerable amount of
aging occurred in thin slice specimens
despite having untouched impermeable
facers, as well as a glass plate at the
bottom of the specimens and edges
sealed completely with epoxy coating.’’
Additionally, the relationship
between the skin and the rate of aging
in foam depends on preserving the
integrity of both the skin surface and the
bonding between the skin and
insulation. Punctures, made to allow for
the installation of light fixtures, doors,
and shelving, undermine the integrity of
the skin. Walk-in insulation panels and
their skins also typically separate over
time due to shrinkage of foam materials
after manufacture. While most foam
materials contract by less than 1 percent
of their total volume, shrinkage at this
level is enough to create significant air
gaps. DOE found that current methods
of conditioning foam materials do not
account for impermeable facers.
Finally, like the conditioning
standards that are currently in use,
ASTM C1303–08 is not designed to test
impermeably faced foams that may be
E:\FR\FM\04JAP2.SGM
04JAP2
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
194
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
used with walk-ins. Significant research
has been underway by the NRCC but no
known test procedure is currently
available that accounts for the effect of
impermeable barriers. DOE requests
feedback on this issue, including the
submission of test results on the impact
of impermeable skins on long-term Rvalue. DOE specifically requests that
interested parties submit or identify
peer-reviewed, published data on this
issue.
DOE also requests feedback on the use
of ASTM C1303–08 with impermeably
faced foams. DOE may recommend the
use of a test procedure specifically
designed for impermeably faced foam if
one is developed.
As a result of this evaluation, DOE
proposes requiring manufacturers to use
ASTM C1303–08 to determine the LTTR
of walk-in foam insulation for the
purposes of calculating the energy
consumption of walk-in equipment.
DOE requests comments on this
proposal.
DOE is also proposing and seeking
comment on the following exceptions to
ASTM C1303–08:
(1) Section 6.6.2 of C1303–08 suggests
that two standards for measuring the
thermal resistance may be used. DOE
proposes to allow use only of ASTM
C518–04 (in EPCA, an incorrect form of
the date suffix was used, e.g., ASTM
C518–[20]04), as specified in EPCA. (42
U.S.C. 6314(a)(9)(A)(ii))
(2) In section 6.6.2.1, in reference to
ASTM C518–04, the mean test
temperature of the foam during R-value
measurement would be ¥6.7 ± 2 °C (20
± 4 °F) with a temperature difference of
22 ± 2 °C (40 ± 4 °F) for freezers and
12.8 ± 2 °C (55 ± 4 °F) with a
temperature difference of 22 ± 2 °C (40
± 4 °F) for coolers. This change replaces
the standard mean temperature of 75 °F
for ASTM C518–04 with the EPCA
specified values.
(3) For the purposes of preparing
samples with foam-in-place method,
section A2 should be followed exactly
except for the following modifications
to accommodate foam-in-place methods
that may be used during the
manufacture of walk-in panels:
• (3.1) Instead of following A2.3,
which specifies that the foam be
sprayed onto a single sheet of wood, the
sample shall be foamed into a fully
closed box of internal dimension 60 cm
x 60 cm by desired product thickness
(2ft x 2ft x Desired thickness). The box
shall be made of 3⁄4 inch plywood and
internal surfaces wrapped in 4 to 6 mil
polyethylene film to prevent the foam
from adhering to the box material.
• (3.2) Instead of following section
A2.4, which specifies the spraying of
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
foam layers onto a open sheet of
plywood, the cavity shall be filled using
the manufacturer’s typical foam-in-place
method through a standard injection
port or other process typically used to
foam the product being tested.
• (3.3) In section A2.6, which defines
the single surface in contact with the
board to be the ‘‘surface,’’ the definition
of the foam’s ‘‘surface’’ shall be the two
surface regions in contact with the 60 x
60 cm sections of the box.
• (3.4) Section A2.8 shall not be
followed because the prepared sample
will not have any ‘‘free rise’’
component.
DOE proposes that manufacturers
select foam test thicknesses based on
design specifications and practice. If a
foam’s thickness as manufactured varies
from the tested product thickness, DOE
proposes that the R-value of that foam
at its manufactured thickness may be
interpolated using the results of ASTM
C1303–08, provided that the
manufactured thickness does not vary
from the tested product thickness by
more than ± 0.5 inches. For example, if
4-inch and 6-inch products were
prepared, interpolation between 3.5 and
4.5 inches would be allowed for the 4inch foam and 5.5 and 6.5 inches for the
6-inch foam. If the manufacturer
determines that final foam thickness
should be outside of the tested range,
then additional testing would be
necessary to fit the criterion for
interpolation. Manufacturers should
make their sample selections
accordingly to avoid the need for
additional testing. DOE requests
feedback on the use of interpolation
within the specified ± 0.5 inch range.
DOE proposes that the results for each
of the sample sets of three stacks should
be reported as specified by ASTM
C1303–08. As defined by ASTM C1303–
08, after thin slices of foam are cut, the
slices are organized into ‘‘stacks’’ of
slices to match the original overall
thickness of the sample. The procedure
defines three stack types: (1) Stacks
comprised of only surface slices of
foam, (2) stacks of only core slices and
(3) a mixture of core and surface slices.
A ‘‘surface’’ slice and a ‘‘core’’ slice are
defined in ASTM C1303 as ‘‘a thin-slice
foam specimen that was originally
adjacent to the surface of the fullthickness product and that includes any
facing that was adhered to the surface of
the original full-thickness product’’ and
‘‘a thin-slice foam specimen that was
taken at least 5 mm (0.2 in.) or 25% of
the product thickness, whichever is
greater, away from the surface of the full
thickness product,’’ respectively. The Rvalue of only the mixed stack would be
used to calculate the energy
PO 00000
Frm 00010
Fmt 4701
Sfmt 4702
performance of walk-ins. DOE requests
feedback on this approach. ASTM is
currently conducting a 5-year
‘‘ruggedness’’ test. Upon completion of
the test, DOE may consider a
rulemaking to modify the required
number of stacks and/or which stack is
best suited for labeling and calculating
energy performance. DOE requests
feedback on the use of the mixed stack
R-value for the purpose of calculating
walk-in energy use.
Additionally, DOE notes that ASTM
C1303–08 is specifically intended for
measuring the LTTR of foam materials.
In light of this situation, the process
contained in this standard would not
apply to advanced insulation
technologies such as vacuum insulated
panels (VIPs) or aerogels. However,
ASTM C518–04 can be used to measure
the thermal properties of these new
technologies, which, as specified in
EPCA, is the required test for measuring
insulating performance. (42 U.S.C.
6314(a)(9)(A)(ii)) DOE requests feedback
on whether non-foam advanced
technologies, such as VIPs or aerogels,
would be likely to be used for walk-ins
in the next 5 years. If DOE determines
that these materials may be used in
walk-ins in the next 5 years, DOE may
consider alternative test procedures for
capturing the long-term insulating value
of any non-foam materials.
ii. Water Absorption in Foam
At the framework public meeting,
interested parties raised the issue of Rvalue deterioration in foams due to
moisture absorption. Craig stated that
moisture penetration causes a decline in
the R-value of foam insulation, at a rate
that depends on the type of foam used.
(Craig, No. 22 at p. 3) As is the case with
aging, insulating foams exhibit different
characteristics in the presence of
moisture. Polystyrene foam is highly
resistant to water absorption, whereas
polyurethanes and polyisocyanurates
are more easily damaged by exposure to
moisture. In general, the solution to
moisture issues involves creating an
impermeable barrier between the
insulation and the moisture source.
However, Owens Corning asserted that
customers routinely puncture metal
skins to allow for the installation of
lighting fixtures, shelving, and doors,
creating holes that allow moisture to
enter the insulation. (Owens Corning,
Public Meeting Transcript, No. 15 at p.
61)
Although vapor permeance and water
absorption tests exist, they are designed
for measuring specific material
properties rather than measuring system
performance of composite structures
like walk-ins. For a variety of reasons,
E:\FR\FM\04JAP2.SGM
04JAP2
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
these tests would be complex, costly,
and time consuming to use because
several sub-methods would need to be
developed to quantify the impact of
water on walk-ins. For every unique
construction method and/or
combination of materials (e.g., blowing
agent, foam type, barriers, gasketing
materials, panel joint type, and method),
the following considerations exemplify
the challenges inherent in accounting
for and quantifying insulating
performance: (1) The rate at which the
walk-in envelope collects water over its
life must be measured or predicted
using an accelerated test; (2) a saturation
level or maximum absorption, if any,
must be determined; and (3) a
correlation between water absorption
levels and insulation performance must
be quantified. At this time, test
procedures for each of these
considerations are not yet recognized by
a nationally recognized organization
such as ASTM.
DOE reviewed several methods for
testing vapor permeance and water
absorption in foam insulation materials
including ASTM E96, ‘‘Standard Test
Methods for Water Vapor Transmission
of Materials,’’ ASTM C209, ‘‘Standard
Test Methods for Cellulosic Fiber
Insulation Board,’’ ASTM C272–01
(2007), ‘‘Standard Test Method for
Water Absorption of Core Materials for
Structural Sandwich Constructions,’’
and ASTM D2842–06, ‘‘Standard Test
Method for Water Absorption of Rigid
Cellular Plastics.’’ Each of these
standards describes a method for
submerging a sample in water for a
specified amount of time and then
measuring the amount of water absorbed
on a volume or weight basis. However,
each one specifies significantly different
immersion durations (ranging from 2 to
96 hours) and methods of weighing
samples (blotting surfaces before
measurement or using a buoyancy
measurement). DOE believes that using
the longest test period, 96 hours, would
likely result in near worst case or
maximum water absorption, but it is
unclear how this directly translates to
reduction in insulation performance for
various materials.
Additionally, ASTM E96–05 measures
vapor permeance under low vapor
pressure gradient conditions. However,
the temperature differentials in which
walk-ins operate cause a high vapor
pressure gradient, which has the effect
of continuously driving moisture
through the envelope. Neither ASTM
E96–05 nor any other known procedures
currently provide a methodology to
accurately calculate the vapor
permeance in walk-ins at the pressure
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
gradients typically experienced in the
field.
Some research has been completed,
including a major study by the Cold
Regions Research and Engineering Lab
(CRREL). The CRREL study developed
and applied a method for creating a
vapor pressure gradient across various
materials to quantify the rate at which
these materials absorb and retain water
over time. The insulating performance
of the materials was also tested at
various levels of moisture content to
develop equations for the purpose of
calculating the insulating properties at
any moisture percentage relative to its
dry weight. No other testing body has
applied CRREL’s testing procedures to
replicate the results and most of
CRREL’s research was completed nearly
20 years ago. One of DOE’s national labs
has also begun development of
procedures to evaluate the impact of
moisture on insulation R-values, but
this activity remains incomplete.
Given the discussion above, DOE does
not propose to include the impact of
water absorption on R-value in the test
procedure because no well-accepted
method has been developed. However,
DOE will evaluate such a procedure if
it is developed in the future.
b. Air Infiltration
Another major pathway for energy
loss in walk-ins is air infiltration, or air
exchanged into and out of a walk-in
while all access points are closed or
during door-opening cycles (i.e., the
openings of doors for the removal or
stocking of product, or passage of
customers, personnel, and/or
machinery, also referred to as ‘‘dooropening events’’). Compared with other
energy consumption factors such as
conduction losses through insulation,
air infiltration may be the largest
contributing factor to envelope energy
losses. Air infiltration can occur through
steady-state leakage or from door
opening events. As a result, designs and
technologies that reduce infiltration
during steady-state operation and dooropening events should be considered to
reduce these losses.
EPCA includes prescriptive
requirements for doors used on walkins, recognizing that a major portion of
energy is lost through door opening
cycles. All walk-in coolers or freezers
‘‘manufactured on or after January 1,
2009, shall (A) have automatic door
closers that firmly close all walk-in
doors that have been closed to within 1
inch of full closure, except * * * doors
wider than 3 feet 9 inches or taller than
7 feet; [and] (B) have strip doors, spring
hinged doors, or other method of
minimizing infiltration when doors are
PO 00000
Frm 00011
Fmt 4701
Sfmt 4702
195
open * * *’’ (42 U.S.C. 6313(f)(1))
During the framework public meeting,
interested parties suggested methods for
calculating infiltration from dooropening events within the test
procedure.
These two infiltration pathways,
steady-state leakage, and air losses due
to door-opening events, are mitigated
using distinct methods.
Steady-state infiltration (the air
exchanged between the interior and
exterior of a walk-in while all doors are
closed, also referred to as ‘‘leakage’’)
occurs because of the significant
pressure gradient caused by the large
temperature difference between the
refrigerated space and the external
environment. This pressure differential
continuously induces air movement
from the outside to the inside of a walkin where leakage pathways exist.
Leakage typically occurs through door
frames, door gaskets, wall panel-topanel interfaces, and wall-to-floor and
wall-to-ceiling junctions. While
considered minimal for small walk-ins,
leakage becomes more significant as the
walk-in size increases.
Air infiltration due to door openings
is mostly a function of door area,
opening frequency, duration, and air
density. The primary means of reducing
the amount of infiltration is by the use
of active or passive infiltration
reduction devices and devices that help
reduce the time that doors are left
accidentally ajar. Air curtains and strip
curtains are good examples of active
versus passive devices. The sections
below describe the methods for testing
the effectiveness of such devices and
procedure for calculating air
infiltration’s impact on energy use in
walk-ins.
Hired Hand recommended that the
energy analysis for warehouse coolers
and freezers include the performance of
the door, including the number of dooropening cycles each day or week and
factoring in optional door configurations
such as automatic doors with or without
strip curtains. (Hired Hand, No. 27 at p.
1) Eliason recommended that DOE
consider average door cycling and doorajar conditions in its test procedure.
(Eliason, No. 19 at p. 1) Eliason noted
that both of these conditions are part of
the company’s internal life-cycling test
and represent real-world conditions.
(Eliason, No. 19 at p. 1) Hired Hand
stated that a simple rating for door
infiltration performance could be based
on door-opening cycles per week. (Hired
Hand, No. 27 at p. 2) Hired Hand also
suggested that DOE require consumer
labeling to indicate the cost per minute
of leaving the door open based on door
E:\FR\FM\04JAP2.SGM
04JAP2
196
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
size and application. (Hired Hand, No.
27 at p. 2)
Based on stakeholder comments and
DOE review of the impact of air
infiltration on energy use, DOE
identified two methods that could be
used to measure air infiltration in walkins: the blower door method and the gas
tracer method. These methods are
described in the following subsections.
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
i. Blower Door Method
DOE reviewed ASTM E1827–96
(2007), ‘‘Standard Test Methods for
Determining Airtightness of Buildings
Using an Orifice Blower Door,’’ as a
possible candidate test procedure for
testing walk-ins. This method
pressurizes or depressurizes the internal
space using a large fan, typically placed
in a doorway. The infiltration rate of the
space can be directly calculated by
measuring the pressure difference
between the exterior and interior space
and the air-flow rate through the fan.
After reviewing this test method, DOE
identified reasons why the test might
not be suitable for walk-ins. The blower
door method is better suited for
structures with relatively high rates of
infiltration, such as buildings and
homes, rather than the relatively low
levels typically observed in walk-ins. In
addition, known calibration curves for
the blower door method require small
temperature differentials (generally less
than 10 °F) between the inside and
outside of the envelope. However, walkins typically operate with a far greater
differential that is normally greater than
40 °F. Another drawback to using this
method with walk-ins is that the test
setup procedure requires blocking a
main entrance to the structure with the
blower door. Because infiltration around
the main door is a key source of
infiltration in walk-ins and would not
be measured as part of the test, this
approach would not adequately capture
the majority of the infiltration. For these
reasons, DOE does not propose the use
of the blower door method for
measuring the air infiltration of walkins.
ii. Gas Tracer Method
DOE also reviewed ASTM E741–06,
‘‘Standard Test Method for Determining
Air Change in a Single Zone by Means
of a Tracer Gas Dilution.’’ Although not
as widely used as the blower door
method, the gas tracer method has been
used for decades by the building
industry. The test is conducted by
injecting a tracer gas, such as carbon
dioxide or perfluorocarbons, into the
internal space and measuring its
concentration at recorded times. From
these measurements, the average air
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
change rate can be determined. While
manual tools, such as syringes, or
automated systems can be used to
sample the air spaces, the test procedure
lends itself to automation both for
calibration and data collection.
Depending on the gas and sampling
method used, the gas concentration can
be measured immediately with portable
equipment. This method is also more
accurate than the blower door method
because it allows for direct
measurement of infiltration without
modification of the design conditions.
(ASTM, ASTM E741–06 (2006),
‘‘Determining Air Change in a Single
Zone by Means of a Tracer Gas
Dilution,’’ section 5.6, p. 3)
c. Steady-State Infiltration Test
For the reasons described above, DOE
proposes using the gas tracer method
described in ASTM–E741–06 for
measuring the steady-state air
infiltration of walk-ins, with the
following six exceptions:
First, DOE proposes using the
‘‘concentration decay method’’ instead
of other available options described in
ASTM E741–06. DOE considers this
method to be the simplest, fastest, most
cost efficient, and most accurate.
Second, carbon dioxide (CO2) is the
recommended gas tracer for all testing
because of the few human hazards
related to its use, and the availability
and relative cost of sampling
equipment.
Third, the test would use the ‘‘average
air change rate’’ method, in changes per
hour (1/h), rather than the ‘‘average air
change flow’’ method described in
ASTM E741–06. The ‘‘air change flow’’
method allows for the direct measure of
the exchange of air in cubic feet per
hour and does not require measurement
of the internal volume of the space but
requires a more complex test setup and
sampling method. In contrast, the ‘‘air
change rate’’ method measures the rate
of exchange of air per unit of time can
be completed using relatively simple
equipment. However, converting this
value to a measurement of the flow, e.g.,
volume of air exchanged per unit time,
requires a precise measurement of
internal volume. Since the precise
internal volume of a given walk-in is
readily available, DOE considers the
‘‘air change rate’’ method preferable to
the ‘‘air change flow’’ method because
the equipment is less expensive and the
measurements are easier to obtain.
Fourth, ASTM E741–06 describes the
importance of verifying proper gas
mixing but does not describe where or
how many spatial locations should be
sampled. DOE proposes that spatial
measurements shall be taken in a
PO 00000
Frm 00012
Fmt 4701
Sfmt 4702
minimum of six locations or one
location per 20 square feet (ft2) of floor
area (whichever results in a greater
number of measurements), at a height of
3 ft ± 0.5 ft, or a minimum of 2 ft ± 0.5
ft from the inside wall of the walk-in
envelope, to verify that the air space is
uniformly mixed.
Fifth, DOE proposes the test be
completed close to operational
temperature to mimic the thermally
induced pressure gradient seen in walkins. The internal air temperature shall
be ¥23.3 (¥10 °F) ± 2 °C (4 °F) for
freezers and 1.7 (35 °F) ± 2 °C (4 °F) for
coolers. The external air temperature
should be 24 °C (75 °F) ± 2.5 °C (5 °F).
Sixth, the test should be completed
with all doors closed. The resulting
measurement shall be in units of
changes per hour.
DOE requests feedback on its proposal
to use ASTM E741–06 as the method for
determining air infiltration and on the
proposed exceptions to the test
procedure.
For the purposes of administering the
test, DOE considered the following
options for the location of the test: (1)
Require testing at a third-party testing
facility. DOE believes that requiring that
manufacturers to ship every walk-in
manufactured, or a representative
model, to a third-party facility for
testing, would place a substantial
burden on manufacturers; (2) require
testing by a third party on site at a walkin manufacturing facility. Completing
the infiltration test at the manufacturing
facility reduces logistical complexity
and costs associated with testing. Since
the equipment used to complete
infiltration testing was originally
designed for testing the performance of
buildings, the equipment and protocols
are designed to be mobile.
DOE believes that the most viable
option is allowing testing to occur at the
manufacturing facility, if preferred by
the manufacturer. DOE requests
feedback on the flexibility of location
required for completion of any
infiltration test.
iii. Door Infiltration Reduction Device
Test
DOE is considering incorporating a
door-opening test to quantify the impact
of technologies such as strip curtains,
air curtains, or other infiltration
reduction devices during door-opening
events. Due to the limited data available
on these devices and the variety of
technologies, DOE believes a
standardized test would provide a more
comprehensive and accurate picture
regarding the effectiveness of these
devices when compared to simply using
effectiveness assumptions.
E:\FR\FM\04JAP2.SGM
04JAP2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
Vrate,with-device
Vrate,without-device
×100%
Eq. 1
Where:
Vrate,with-device = air infiltration rate, with door
open and reduction device active, using
4.2, 1/h;
Vrate,without-device = air infiltration rate, with
door open and reduction device disabled
or removed, using 4.2, 1/h.
This calculation will yield a value
between 0 and 100 percent, with 100
percent meaning that the device
prevents all air infiltration when the
door is open. DOE proposes using this
calculated effectiveness for every
unique door-device combination that a
manufacturer may offer. DOE requests
feedback on the proposed method for
measuring the effectiveness of an
infiltration reduction device.
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
iv. Infiltration Due to Door Openings
DOE does not propose to require
manufacturers to measure the
infiltration from all door-opening
events. The complexity of testing, the
variation of walk-in design, and various
end-use behavior factors would make
such a recommendation very difficult to
execute. Instead, DOE proposes using
analytical methods based on equations
published in the ASHRAE Refrigeration
Handbook in combination with assumed
door-opening frequency, and duration of
door cycles, to calculate the air
infiltration associated with each dooropening event.
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
(
)
⎢ P × θp + ( 60 × θο ) ⎥
⎦
Dt = ⎣
3600 × θd ]
[
Eq. 2
Where:
Dt = fractional door opening,
P = the number of doorway passages (or
number of door-opening cycles for a
given door),
qp = the door open-close time,
qo = the time the door stands open, and
qd = daily time period.
Dt is important for properly
calculating the energy impact of air
infiltration due to door-opening events.
Therefore, the assumed values of P, qp,
and qo will drive the result. The daily
time period, qd, is simply assumed to be
24 hours.
For display glass doors, a P of 72 per
day, qp of 8 seconds per passage, qo of
0 minutes and qd of 24 hours could be
used. P of 72 per day is based on
comments by Hired Hand and research
on cold store infiltration. Hired Hand
commented that the reach in frequency
is approximately 400–600 per week (or
one passage every 20 minutes assuming
18 hours per day per week). (Hired
Hand, Public Meeting Transcript, No. 15
at p. 154) However, DOE identified a
study by A.R. East, P.B. Jeffrey, and D.J.
Cleland, ‘‘Air Infiltration into Walk-in
Cold Rooms,’’ which suggested that this
number should be closer to one passage
every 10 minutes (assuming 18 hours
per day per week). DOE suggests that
the average of the two values of one
passage every 15 minutes or P of 72 per
day could be used. DOE chose the value
of 8 seconds per passage but seeks
comment on whether another value may
be more appropriate.
For all other door or access types, a
P of 60 per day, qp of 12 seconds per
passage, qo of 15 minutes, and qd of 24
hours could be used. The number of
passages reflects that other door types
are typically accessed less frequently
than glass doors. The value of 12
seconds per passage was selected based
on the assumption that non-glass doors,
such as those through which forklifts
are driven in order to load product, will
be open for longer periods of time than
a typical display door. DOE selected the
qo of 15 minutes due to the probability
PO 00000
Frm 00013
Fmt 4701
Sfmt 4702
that a non-glass door will be propped
open accidentally or intentionally. If an
automatic door opener/closer is used for
doors larger than 7 feet tall and 3 feet,
9 inches wide, then a qp of 10 seconds
should be used.
DOE recognizes that with the variety
of walk-in types and end-users, the
frequency and duration of door-opening
events is likely to vary significantly. As
a result, DOE requests comments on the
DOE assumed values for P, qp, and qo.
3. Calculations
In this section, DOE proposes a
calculation methodology for using the
results obtained from the measurements
in the aforementioned tests, along with
other known quantities, to calculate an
energy use metric associated with the
envelope. The steps in the proposed
methodology are explained below.
a. Energy Efficiency Ratio
EPCA requires that the test procedure
‘‘measure the energy use of walk-in
coolers and walk-in freezers.’’ (42 U.S.C.
6314(a)(9)(B)(i)) However, EPCA does
not specify the units of measurement or
units for reporting that are required.
Based on a review of commonly used
energy consumption metrics, DOE
recommends the use of kWh/day as this
unit is commonly recognized by endusers, manufacturers and other
interested parties. However, a majority
of metrics used to describe heat transfer
losses are in units of British Thermal
Units (BTU) per unit time. Therefore, to
convert the British Thermal Units per
hour (BTU/h) thermal energy
transmission calculation into a measure
of electrical energy consumed by the
refrigeration equipment to remove the
heat, DOE proposes using an energy
efficiency ratio (EER) conversion based
on a nominal efficiency of an assumed
refrigeration system.
Because an envelope manufacturer
cannot control where the refrigeration
equipment is sited and the EER is
intended to provide a means of
comparison and not directly reflect a
real walk-in installation, DOE proposes
that the EER be 12.4 Btu per Watt hour
(Btu/W-h) for coolers and 6.3 Btu/W-h
for freezers. The difference in EER for
coolers and freezers reflects the relative
efficiency of the refrigeration equipment
for the associated application. As the
temperature of the air surrounding the
evaporator coil drops (that is, when
considering a freezer relative to a
cooler), thermodynamics dictates that
the system effectiveness at removing
heat per unit of electrical input energy
decreases. DOE requests feedback on the
relative EERs of refrigeration equipment
for a comparison basis.
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.026
E=
ASHRAE recommends using Gosney
and Olama’s (1975) air exchange
equations for fully established flow
through door openings (Equation 2).
Several key assumptions have the
greatest impact on predicated air
exchange and are related to the
calculation of the decimal portion or
time a doorway is open, Dt. (ASHRAE,
Refrigeration Handbook, 2006, section
13.5)
EP04JA10.025
DOE proposes a two-part test to
account for the effect of the door
infiltration reduction device. First,
measurements should be taken once the
tracer gas has uniformly dispersed in
the internal space using the
methodology described in ASTM E741–
06. Within 3 minutes ± 30 seconds, with
the infiltration reduction device in
place, a door should be opened at an
angle of 90 degrees over a period no
longer than 3 seconds, then held at 90
degrees in the open position for 5
minutes ± 5 seconds, then closed over
a period no longer than 3 seconds. The
gas concentration should be sampled
again after the door has been closed.
Samples should continue being taken
until the gas concentration is once again
uniformly mixed within the walk-in.
Second, the test should be repeated
exactly as described above with the
infiltration reduction device removed or
deactivated.
Using the measured infiltration with
the device in place and without the
device in place, the infiltration
reduction effectiveness can be directly
calculated:
197
198
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
b. Heat Gain Through the Envelope Due
to Conduction
The energy calculation for all
components that comprise the external
surface area of the walk-in may be
determined using the measured surface
area, the measured foam R-value for the
walls and ceiling, the R-value (or Uvalue) for glass doors, the design
operation temperature, and the average
ambient air temperature. Then, the
associated heat transfer due to
conduction can then be directly
calculated.
i. Conduction Through Glass Display
Doors
The heat conduction through the glass
is one of the largest single contributors
to energy consumption for walk-ins
with a high ratio of glass surface area to
non-glass surface. The thermal
conductivity, the inverse of thermal
resistivity or R-value, is commonly
represented by the U-value in units of
Btu/ft2-°F-h. The thermal conductivity
for most glass products, such as glass
doors and windows used in buildings,
is certified by a third party organization
such as the National Fenestration Rating
Council (NFRC). After certification, the
product is granted a NFRC label and
thermal conductivity performance
rating. This rating represents an overall
component performance including but
not limited to the glass and the glass
frame. However, in the case of glass
products manufactured for the use in
walk-ins, such as display doors, inset
window and glass walls, DOE believes
that glass component manufacturers
currently do not participate in any third
party rating programs nor do they
provide products with performance
labels. In addition, the performance data
of these products is not readily available
able in product literature.
In order for the thermal conductivity
performance of glass products be
incorporated into the walk-in test
procedure, DOE proposes these two
options: (1) If manufacturers of glass
doors used in walk-ins participate in the
same NFRC rating program, the
performance of the door shall be simply
read from its label and used for
calculations in this test procedure. If
glass door manufacturers do not
participate in the same NFRC rating
program, then (2) DOE would require
manufacturers to use the free software
package Window 5.2 (available here:
https://windows.lbl.gov/software/
window/window.html), that calculates
the U-value, or thermal conductivity, of
a glass door given precise specifications
such as the size of the door, the number
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
of panes of glass, the gas fill between the
panes, etc. This tool was developed by
Lawrence Berkeley National Lab (LBNL)
and is known in the glass component
industry to accurately predict glass door
thermal performance from the given
door characteristics. It has been used for
many years and has been heavily
verified by empirical test data. In order
to ensure that inputs used to calculate
overall door performance are not being
manipulated by manufacturers, DOE
intends to require the walk-in
manufacturer to report the exact inputs
and settings used in Window 5.2 to
represent the door materials and glazing
system. This will ensure transparency
and accuracy by enabling other
manufacturers and DOE to verify the
integrity of the data and calculated
performance.
DOE seeks comment on the
availability of performance data on glass
products used in walk-in applications,
glass component manufacturers’
participation in third party certification
programs such as NFRC, and the
proposed method for predicting the
thermal performance of glass
components using LBNL’s Window 5.2
software package.
ii. Conduction Through Floors
In general, walk-in coolers are
installed on top of concrete surfaces
regardless of the walk-in type. For a
walk-in cooler that does not have a floor
supplied by the manufacturer, the
average insulating performance of
concrete will be assumed for the floor
surface of the walk-in. Therefore, DOE
proposes using an R-value of 0.6 ft2F-h/Btu for calculating the energy lost
assuming the walk-in cooler are sited on
6-inch concrete floors of 150 lb/ft3
density (ASHRAE Fundamentals
Handbook). DOE requests feedback on
the use of this R-value for coolers that
are not shipped with an insulated floor.
Generally, walk-in manufacturers that
sell large freezers do not install freezer
floors. This task is normally
subcontracted by the end-user before the
walk-in is installed to ensure EPCA
compliance. Therefore, DOE proposes
using the minimum R-value specified in
EPCA for walk-in freezer floors, R–28
ft2-F-h/Btu, for energy performance
calculations if the manufacture does not
supply a floor to ensure EPCA
compliance. (42 U.S.C. 6313(f)(1)(D))
DOE requests comments on the use of
this proposed R-value for freezer floors.
c. Heat Gain Due to Infiltration
The amount of embodied energy in an
air sample is primarily a function of its
PO 00000
Frm 00014
Fmt 4701
Sfmt 4702
temperature and density or what is
typically referred to as the enthalpy in
a thermodynamic system such as a
walk-in. The required amount of energy
needed to remove heat from the air is
calculated as the difference between the
enthalpy of air entering the refrigerated
space and enthalpy of the air inside the
refrigerated space. This calculation is
commonly used when designing walkins and typically uses dry-bulb and wetbulb temperatures. The difference, per
unit mass or volume of air, is calculated
using the functional relationship
between temperature and enthalpy.
Using the measured infiltration rate
from the required steady-state test
described above or calculated analytical
value for air infiltration for dooropening events and the calculated
internal and external enthalpy, a rate of
energy lost per hour (Btu/h) due to air
exchange can be calculated.
d. Envelope Component Electrical Loads
Because the energy use of the walk-in
refrigeration equipment is being
analyzed separately from the envelope
energy use, DOE is considering
calculating the electricity consumption
of lights, sensors, and other
miscellaneous electrical devices using
name-plate rating and assumptions
about their daily operation, all of which
would be incorporated into the
evaluation of envelope energy use. In
addition, because the test procedure for
the refrigeration system will not include
heating loads caused by lighting, heater
wires, and other miscellaneous
components, the thermal load from
these components will be factored into
the envelope calculations. DOE
proposes as part of the test procedure
calculations that 100 percent of the
electrical energy consumed to operate
the devices that are internal located in
the walk-in, will be converted to
thermal energy. This assumption is
accurate since at steady-state, all the
input electrical energy is converted
completely into heat adhering to the
physical laws of conservation of energy.
While some electrical energy, which has
been converted into light, may escape
the controlled space via translucent
glass display doors, this escaping energy
is negligible. The associated thermal
energy will then be used to calculate an
additional compressor load that would
be required to remove the additional
heat generated by these components.
DOE recommends using the following
equation to calculate the power usage
for each electricity-consuming device
type, Pcomp, (kWh):
E:\FR\FM\04JAP2.SGM
04JAP2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
DOE proposes that the rated power
must be read from each electricityconsuming device product data sheet or
name plate, and the nt is the number of
identical devices for which the Pcomp
calculation is being made.
DOE further proposes the use of the
following equation to calculate
additional compressor load due to heat
generated by electrical components,
Cload, (kWh):
Cload = P ,int ×
tot
3.412 Btu
EER Wh
Eq. 4
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
Where:
EER = EER of walk-in (cooler = 12.4 or
freezer = 6.3), Btu/W-h
Ptot,int = The total electrical load due to
components sited inside the walk-in
envelope
The percent time off (PTO) value
accounts for the reduction in energy use
in walk-ins with component control
systems installed and to specify the
possible number of hours for various
component types. While this value may
not reflect behaviorally related energy
consumption, such as how long an enduser typically leaves the lights on, it
will provide a means for comparison of
walk-in performance. To address the
wide variety of devices that could be
employed in a walk-in unit, DOE
proposes the following PTO values:
(1) For lights, DOE proposes a PTO
value of 25 percent for systems without
timers or other auto shut-off systems
and 50 percent for systems with timers
or other auto shut-off systems installed.
(2) For anti-sweat heaters, DOE
proposes a PTO value of 0 percent for
all systems without direct or indirect
relative humidity sensing controls. DOE
further proposes that a PTO value of 75
percent be used for walk-in coolers, and
50 percent for walk-in freezers with
these controls. (Focus on Energy, BP–
3429–0304, ‘‘Anti-Sweat Heater
Controls,’’ 2004, p. 1)
(3) For electrically powered devices
(such as air curtains) that mitigate air
infiltration but are not actively
controlled based on door open or closed
positions, DOE proposes a PTO value of
25 percent.
(4) For electrically powered devices
that mitigate air infiltration that are also
actively controlled based on door open
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
or closed position for display doors,
DOE proposes a PTO value of 99.33
percent.
(5) For electrically powered devices
that mitigate air infiltration that are also
actively controlled based on door open
or closed position for all other doors,
DOE proposes a PTO value of 99.17
percent.
(6) For all other devices, DOE
proposes a PTO value of 0 percent,
unless the walk-in manufacturer can
demonstrate that the device is
controllable by a preset control system.
If this can be demonstrated, then DOE
proposes a value of 25 percent for the
device in question.
DOE seeks comments on these
assumptions.
e. Normalization
A single metric would make
comparing the energy use of walk-ins
much more straightforward. DOE
proposes using a calculation for energy
consumption per unit time and a
normalization factor to account for
differences in glass and non-glass
external surface area depending on the
product class. During the framework
public meeting and in written
comments, some interested parties
recommended that DOE use volume as
the normalization factor for performance
standards. (Manitowoc, Public Meeting
Transcript, No. 15 at p. 56; EEI, Public
Meeting Transcript, No. 15 at p. 116;
NEEA, No. 18 at p. 3) Crown Tonka, in
a written comment, recommended that
the test metric be kWh per cubic foot
(i.e., energy consumption normalized by
volume). (Crown Tonka, No. 23 at p. 1)
The Joint Comment recommended that
DOE use surface area as the
normalization factor. (Joint Comment,
No. 21 at p. 2) A comment submitted
jointly by representatives of SCE,
SMUD, and SDG&E (hereafter referred to
as the Utilities Joint Comment) also
stated that DOE should use surface area
as a normalization factor. (Utilities Joint
Comment, No. 32 at p. 7)
Many established metrics use a perday time scale normalized by product
volume. However, surface area is the
key geometric characteristic related to
both conduction and infiltration
because volumetric normalization
cannot directly account for the higher
conduction and infiltration losses
associated with glass doors and
windows. Conduction and infiltration
losses through glass become particularly
important considerations as the ratio of
glass door area to total wall area
PO 00000
Frm 00015
Fmt 4701
Sfmt 4702
increases, as is the case in walk-ins
designed for customer access. Using
surface area as the normalization factor
would account for these losses through
any glass door or window used in a
walk-in. Therefore, DOE proposes the
use of surface area as a normalization
factor for performance calculations of
walk-ins. DOE requests comments on
this proposed normalization method.
f. Daily Energy Consumption
Coefficients
As discussed in section III.A.1, DOE
proposes allowing manufacturers to
group similar units together into a single
‘‘basic model.’’ This approach would
reduce the testing burden as only one
unit of each basic model would be
subject to testing. However, in the case
of envelopes, the equipment is so highly
customized that each unit a
manufacturer builds may be unique. For
example, units may have identical
materials, components, or construction
methods, but may be built to varied
dimensions, which could result in
different energy consumption values
being obtained using the proposed test
methods.
In order to compare units that are
similar enough to be included in the
same basic model, but that are not
identical, the test procedure allows for
calculating daily energy consumption
coefficients (or DECCs), using test
results from a particular unit within a
basic model, and then applying these
DECCs to other units within a basic
model to calculate the energy
consumption of the other units. DECCs
are essentially scaling factors that allow
a manufacturer to change certain
parameters of an envelope and calculate
the corresponding change in energy
consumption. In the case of today’s
proposed procedure, these parameters
would be wall surface area, non-glass
door surface area, glass display door
surface area, glass wall and inset
window surface area, infiltration due to
opening of non-display type doors and
infiltration reduction due to reduction
devices in place on non-display doors,
infiltration due to opening of display
type doors and infiltration reduction
due to reduction devices in place on
display doors, and electrical energy
consumption due to devices including,
but not limited to, lights, anti-sweat
heaters, and motors to drive air mixing
fans. The expression for daily energy
consumption is formulated on the
assumptions that: (1) Energy
consumption due to conduction losses
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.028
Where:
Prated,t = rated power of each component,
PTOt = percent time off, and
nt = the number of devices at the rated
power.
Eq. 3
EP04JA10.027
Pcomp,t = Prated,t × (1 − PTOt ) × nt × 24
199
200
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
scales linearly with surface area; (2)
energy consumption due to infiltration
scales linearly with the number of doors
of each type and total wall surface area;
(3) energy consumption of anti-sweat
door heaters scales linearly with total
door surface area; and (4) energy
consumption of other electrical
components including lighting and
stirring fans scales linearly with the
interior volume of the envelope.
Once the DECCs are calculated from
a tested walk-in envelope, they are
combined to provide a linear expression
of the daily energy consumption of any
walk-in envelope of the same basic
model as the tested envelope (that is,
having the same construction methods,
materials, components, and other energy
consumption characteristics as the
tested envelope), as follows:
Etot,system = DECCnon-glass × Anon-glass,tot + DECCglass × Aglass, tot + DECCinfilt,disp_dr_opn ×
Adisp_doors + DECCdisp_dr_device × ndisp_doors + DECCinfilt,non-display,dr_opn × Anon-display-doors +
Eq. 5
DECCnon-display-dr_device × nnon-display-doors + DECClight × Vref_space + DECCASH × Adisp_doors +
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
Where:
DECCnon-glass = DECC for non-glass,
Anon-glass,tot = total non-glass surface area,
DECCglass,door = DECC for glass doors,
Aglass,glass, tot = total glass surface area, and
DECCglass,wall = DECC for glass walls and inset
windows,
Aglass,wall, tot = total glass wall and inset
window surface area, and
DECCinfilt,disp_dr_opn = DECC for opening of
display type doors,
Adisp_doors = total area of display doors,
DECC disp_dr_device = DECC for infiltration
reduction device in place for display
doors,
ndisp_doors = total number of display doors,
DECCinfilt,non-display_,dr_opn = DECC for nondisplay type doors,
Anon-display_doors = total area of non-display
type doors,
DECCnon-display_dr_device = DECC for infiltration
reduction device in place for non-display
doors,
nnon-display_doors = total number of non-display
doors,
DECClight = DECC for lights,
Vref_space = total enclosed refrigerated
volume(ft3),
DECCASH = DECC for anti-sweat heaters,
DECCstir_fan = DECC for motors used to drive
air mixing fans, and
DECCother = DECC for other electricity
consuming devices.
Only applicable DECCs shall be used.
For example, if a certain basic model
did not have glass display doors, DECCs
and variables pertaining to glass display
doors would not be calculated, nor
would they be included in the equation
of energy consumption.
DOE believes that this approach
would reduce the testing burden on
manufacturers because it would not
require manufacturers to test every unit
produced with slight variations due to
customer specification. However, by
specifying a calculation methodology
that manufacturers must use, the
approach reduces the potential for
inconsistency among manufacturers’
rating methods, a concern that
interested parties raised about DOE’s
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
previous idea to allow each
manufacturer to develop its own AEDM
for rating similar, but not identical,
equipment. (See section III.A.3 for
discussion of comments about this
issue.) DOE requests comment on the
proposed approach of specifying a
formula based on DECCs, and on the
assumptions that DOE made in
generating this formula. DOE also asks
if there are other parameters it should
consider when calculating DECCs.
C. Refrigeration System
As previously discussed, a
differentiation was made for the
purposes of this test procedure between
the envelope or structure of the walk-in
cooler or freezer and the mechanical
refrigeration system performing the
physical work necessary to cool the
interior space. The refrigeration system
in this context is further subdivided into
three categories, consisting of singlepackage systems containing both the
condensing and evaporator units, split
systems with the condensing unit and
unit cooler physically separated and
connected via refrigerant piping, and
rack systems utilizing unit coolers,
which receive refrigerant from a shared
loop. The proposed test procedure
contains separate specific provisions for
the standardized testing of each
refrigeration system type. Later sections
provide a general overview of the test
procedure for refrigeration systems of
walk-in coolers and freezers and address
some of the technical issues pertinent to
the proposed test procedure. The
following section also addresses issues
raised by interested parties.
1. Overview of the Test Procedure
In accordance with EPCA, DOE
proposes to adopt a test procedure for
measuring the energy consumption of
the refrigeration system of walk-in
coolers and freezers. (42 U.S.C.
6314(a)(9)(B)(i)) DOE is considering
PO 00000
Frm 00016
Fmt 4701
Sfmt 4702
adding the following definition for
‘‘refrigeration system’’ to 10 CFR part
431, subpart R: ‘‘Refrigeration system
means the mechanism used to create the
refrigerated environment in the interior
of a walk-in cooler or freezer, consisting
of an integrated single-package
refrigeration unit, or a split system with
separate unit cooler and condensing
unit sections, or a unit cooler that is
connected to a central rack system; and
including all controls and other
components integral to the operation of
this mechanism.’’ DOE requests
comments on this proposed definition.
In the framework document, DOE
examined in detail six test procedures
developed either by AHRI or ASHRAE
that relate to the measurement of energy
consumption of refrigeration equipment
to determine whether they could apply
to walk-in refrigeration systems.
Although the six procedures collectively
covered all of the components of the
refrigeration systems of walk-in coolers
and freezers (i.e., the compressor, the
condenser, the condensing unit or the
unit cooler), each of these existing
procedures covered only one or some of
the components, and none applied to
the testing of the complete refrigeration
system. The rating conditions specified
in those procedures also are generally
not representative of typical conditions
found in walk-in equipment.
During the framework public meeting
and in a written comment, AHRI
informed DOE that it has begun
developing a standard for the
performance rating of walk-in cooler
and freezer refrigeration systems. (AHRI,
Public Meeting Transcript, No. 15 at p.
50; AHRI, No. 33 at p. 3) This standard,
AHRI Standard 1250P, ‘‘2009 Standard
for Performance Rating of Walk in
Coolers and Freezers,’’ was published in
September of 2009. DOE has reviewed
the final, published version of AHRI
Standard 1250P and proposes to
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.029
DECCstir_fan × Vref_space + DECCother × Vref_space
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
incorporate it by reference into this test
procedure.
The test procedure DOE proposes to
adopt covers testing of refrigeration
systems for walk-in coolers and freezers,
including unit coolers and condensing
units that are sold together as a matched
system (i.e., paired with each other in a
way that optimizes the performance of
the system), as well as unit coolers and
condensing units sold separately,
including unit coolers connected to
compressor racks. The procedure
describes the method for measuring the
refrigeration capacity and the electrical
energy consumption for the condensing
unit and the unit cooler, as well as the
off-cycle fan energy and the defrost
subsystem under specified test
conditions. The standard test conditions
specify the dry-bulb and wet-bulb
temperatures, the relative humidity for
both the unit cooler and the condensing
unit, and require that the system must
operate under steady-state conditions.
The test procedure groups walk-in
cooler and freezer systems into four
categories by distinguishing between
indoor and outdoor locations for the
condensing unit, and between coolers
and freezers. The test procedure also
specifies calculations for the nominal
box loads for each of the four categories
under typical low- and high-load
conditions, expressed as a function of
the ambient air temperature. (The
‘‘nominal box load’’ refers to the
refrigeration load imposed on the
system by the walk-in envelope. Similar
to the way in which the envelope was
assumed to be paired with a
refrigeration system of a given EER to
provide a means of comparison between
different envelopes, DOE assumes that
the refrigeration system is paired with
an envelope of given heat transfer
characteristics. This assumption is made
for comparison purposes. See section
III.B.3.a for further discussion of this
concept.) For systems in which the
condensing unit is located outdoors, the
test procedure uses bin temperature data
and bin hour data to represent the
impact of the seasonal variation in
outside ambient air temperature on
energy use. The test procedure
computes an annual walk-in efficiency
factor, or AWEF, for the refrigeration
system under a specified thermal load
profile over a 24-hour operation period.
2. Test Conditions
DOE received several comments on
test conditions. The Utilities Joint
Comment stated that most of the
potential energy savings can be
achieved using floating head pressure
and variable-speed evaporator fans, both
of which are time-varying and weather
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
dependent, and a steady-state test may
not capture these savings adequately.
(Utilities Joint Comment, No. 32 at p. 4)
Manitowoc stated that energy usage can
depend on the heat load in the box
consisting of defrost energy and fan
energy, both of which depend on the
refrigeration system control strategy.
(Manitowoc, Public Meeting Transcript,
No. 15 at p. 76) NEEA stated that the
test conditions should reflect variations
in the location of the condensing unit,
thermal load conditions, and outdoor air
temperature. (NEEA, No. 18 at p. 3)
The test procedure DOE proposes
specific conditions for both the interior
and exterior of the walk-in to determine
the net refrigeration capacity. The
interior conditions of the unit cooler are
specified as nominal temperature and
humidity conditions: 2 °C dry-bulb and
less than 50 percent relative humidity
(RH) for coolers, and ¥23 °C dry-bulb
and less than 50 percent RH for freezers.
The proposed test procedure would
measure both net refrigeration capacity
and off-cycle fan power at those
conditions for the unit cooler. For the
condenser, the test procedure would
specify three different ambient
conditions for dry-bulb and wet-bulb
temperatures: Hot (35 °C/24 °C),
moderate (15 °C/12 °C) and cold (2 °C/
1 °C). The purpose of specifying three
sets of ambient conditions is to capture
the variation in capacity under different
ambient temperatures.
For two-capacity condensing units,
the test procedure would measure the
net refrigeration capacity under the
same set of ambient conditions for the
condenser at both the minimum and
maximum capacity levels. Variablespeed condensing units would also have
their refrigeration capacities measured
at an additional intermediate capacity
level. Because the test procedure
provides for measurement of the
compressor power and the fan power at
two compressor capacity levels for twospeed systems and at three capacity
levels for variable-speed systems at
multiple outside ambient air
temperature levels, DOE believes that
the proposed test conditions reasonably
reflect the energy savings that may be
achieved through the control strategies
referred to by interested parties. Also, as
mentioned above, the proposed
procedure includes a measurement of
off-cycle fan power, which would
account for energy savings due to
variable-speed evaporator fans.
The Joint Comment stated that test
procedures should account for partialload conditions as well as maximum
loading, and that test methods limited to
maximum load conditions at steadystate operation are insufficient. (Joint
PO 00000
Frm 00017
Fmt 4701
Sfmt 4702
201
Comment, No. 21 at p. 2) ACEEE also
stated that the efficiency metric of the
refrigeration system should reflect partload conditions. (ACEEE, Public
Meeting Transcript, No. 15 at p. 99) In
the proposed test procedure, DOE has
provided for testing of two-capacity and
variable-capacity condensing units at
the minimum capacity level, which
would correspond to the appropriate
low-load level condition for an
appropriately sized unit. However, for a
single-capacity unit, low-load
conditions would lead to a higher
frequency of equipment cycling because
the equipment would be sized for a
much larger load; that is, a load
consistent with worst-case conditions.
For single-speed equipment, the
proposed test procedures do not capture
the impact of this cyclic degradation.
DOE believes that capturing the cyclic
degradation is not necessary because,
averaged over representative locations
in the entire country, walk-in coolers
may operate for many hours at the fullload condition. For instance, the daily
pull-down-load in typical walk-in
cooler and freezer installations is met
over a period of 5 to 8 hours of full-load
operation for a properly sized unit.
Consequently, the impact of the cyclic
degradation is not very significant for
the walk-in cooler or freezer
refrigeration system.
Craig noted that the refrigeration
systems of walk-in equipment are often
oversized to account for the worst
weather conditions and additional pulldown load (Craig, Public Meeting
Transcript, No. 15 at p. 97). Nor-Lake
stated that its methodology for
determining the refrigeration load for
the walk-in takes into account the worst
conditions over the typical annual
cycle, as well as product load, pulldown load, the number of door
openings, and duration (Nor-Lake, No.
30 at p. 2). The proposed test procedure
computes the energy use on the basis of
a nominal box load, which takes into
account product load, infiltration load
due to door openings, and transmission
load through the box walls and roof.
DOE believes that the values for the
nominal box loads adequately reflect
typical oversizing values. The proposed
annual energy efficiency metric is based
on weather conditions that are
considered representative of the
population-weighted average weather
conditions of the country as a whole.
3. Test Methods
The net refrigeration capacity of the
system is determined by one of the
following test methods: (1) DX Dual
Instrumentation measures the enthalpy
change and the mass flow rate of the
E:\FR\FM\04JAP2.SGM
04JAP2
202
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
refrigerant across the unit cooler using
two independent measuring systems; or
(2) DX Calibrated Box measures the
enthalpy change and the mass flow rate
of the refrigerant across the unit cooler
and the heat input to the calibrated box.
In the first method, the test unit cooler
and the matched condensing unit are
kept inside separate environmental
chambers. In the second method, the
condensing unit is placed inside the
environmental chamber, while the unit
cooler is kept inside a calibrated box,
which is inside a temperaturecontrolled enclosure.
DOE believes the test methods are
appropriate for walk-ins because they
were adapted from AHRI Standard 420–
2008, ‘‘Performance rating of forcedcirculation free-delivery unit coolers for
refrigeration,’’ and ASHRAE Standard
23, ‘‘Methods of Testing for Rating
Positive Displacement Refrigerant
Compressors and Condensing Units,’’
and have been widely used in the
refrigeration industry for many years.
Furthermore, these test methods were
developed and approved by the industry
and published by the industry trade
association as a sufficiently adequate
means of assessing the net refrigeration
capacity of equipment that share many
functional similarities with walk-ins,
such as components, materials, and
substances (e.g., the refrigerant) that
provide the mechanical means of
refrigeration. The test methods DOE is
proposing today also account for ways
in which walk-in refrigeration systems
differ from commercial refrigeration
equipment; as in their operating
conditions, configurations, or patterns
of use. For example, condensing units of
walk-in refrigeration systems may be
located outdoors and experience a wider
range of operating temperatures than
commercial refrigeration, which is
generally located indoors; the walk-in
refrigeration test procedure specifies
three different ambient temperatures at
which to test, in order to approximate
actual conditions under which the
system might operate. Furthermore,
DOE’s proposed methods improve upon
previously developed refrigeration test
methods by accounting for the energysaving effects of advanced technologies
such as variable-speed fans and defrost
control strategies.
4. Measurements and Calculations
The test procedure DOE proposes to
adopt, AHRI Standard 1250P–2009,
measures certain parameters, including
the net refrigeration capacity and the
off-cycle fan power for both coolers and
freezers. The defrost power and thermal
energy transferred to the defrost drain
water are measured for a defrost cycle
for freezers only. Separate calculation
procedures for single-capacity, twocapacity, and variable-capacity
equipment are included in the test
procedure. The test procedure
determines the annual walk-in energy
factor, or AWEF, as the ratio of the
annual net heat removed from the box,
which includes the internal heat gains
from non-refrigeration components but
excludes the heat gains from the
refrigeration components in the box, to
the annual electrical energy
consumption. The final metric
determined by this procedure is a
measure of efficiency. However, DOE is
required by EPCA to establish ‘‘a test
procedure to measure * * * energy
use.’’ (42 U.S.C. 6314(a)(9)(B)(i)) In light
of this requirement, DOE proposes that
manufacturers determine both the
AWEF and the annual energy
consumption of their equipment using
the test procedure, which will enable
n
AWEF = ∑ ⎡ BL ( t j ) / E ( t j ) ⎤,
⎣
⎦
the test procedure to be consistent with
the requirements of EPCA to develop
test procedures that measure the energy
consumption of walk-in equipment.
In the AHRI Standard 1250P–2009
calculations, the annual net heat
removed from the nominal box is
represented as a function of ambient
temperature surrounding the condenser
and the measured net refrigeration
capacity at the highest test temperature.
For refrigeration systems consisting of a
unit cooler and a dedicated condensing
unit, the annual net heat removed from
the box can be calculated from the
system capacity and, for systems located
outdoors, the net heat removed from the
nominal box at a given bin temperature
weighted by the number of hours
corresponding to the bin temperature.
The temperature bin data listed in Table
D1 of AHRI Standard 1250P–2009 has
been constructed from the ambient
temperatures over a typical
meteorological year for a specified
location, corresponding closely to the
use cycle parameters prescribed in other
DOE standards. For refrigeration
systems consisting of a unit cooler
connected to a remote rack, the net heat
removed is a function of the unit cooler
capacity at the test points specified in
AHRI Standard 1250P–2009.
DOE is considering deriving the
expressions for the annual net heat
removed from the box, that is, the
numerator of the equations for energy
consumption, by simplifying the
equations in AHRI Standard 1250P–
2009. As an example, the calculation
methodology for indoor coolers using
AHRI Standard 1250P–2009 would be as
follows:
The AWEF, for walk-in cooler systems
with dedicated condensing units located
indoors, is determined by
Eq. 6
j=1
the year, and S[E(tj)] is the annual energy
consumption of the system. Thus,
n
n
∑ E ( t ) = ∑ BL ( t ) /AWEF.
j
j
Eq. 7
EP04JA10.032
j=1
AWEF is calculated directly using the test
procedure, while BL(tj) is calculated by:
BL ( t j ) = ⎡0.33 × BLH ( t j ) + 0.67 × BLL ( t j ) ⎤ × n j .
⎣
⎦
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
PO 00000
Frm 00018
Fmt 4701
Sfmt 4725
EP04JA10.031
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
j=1
Eq. 8
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.030
Where S[BL(tj)] is the annual net heat
removed from the box over the course of
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
Eq. 9
Eq. 10
and
Annual Energy Consumption =
DOE requests comment on using these
equations to derive annual energy
consumption.
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
D. Compliance, Certification, and
Enforcement
Finally, DOE addresses below
compliance, certification, and
enforcement issues involving walk-ins.
At this time, DOE is not proposing any
specific requirements for this
equipment. As discussed below, DOE
will consider addressing these issues in
a separate rulemaking. Any data on
which a manufacturer relies for the
purposes of certifying compliance with
any applicable standards that DOE
promulgates for this equipment would
be derived from the test procedure that
DOE adopts. The adopted procedure
would also be used by DOE during
enforcement-related testing.
1. Provisions for Energy Conservation
Standards Developed by the Department
of Energy
The purpose of establishing
compliance, certification, and
enforcement regulations is to provide
reasonable assurance that manufacturers
appropriately test and accurately
represent the performance
characteristics of commercial
equipment. DOE recently incorporated
the standards prescribed by EISA 2007,
including those for walk-ins, into 10
CFR parts 430 and 431. 74 FR 12074
(March 23, 2009). However, DOE has
not yet proposed or issued amended
energy conservation standards for walkins. DOE will consider issuing
compliance, certification, and
enforcement provisions for walk-ins in
a future rulemaking. Therefore, today’s
notice proposes no certification,
compliance, or enforcement provisions
for energy conservation standards for
walk-ins.
2. Provisions for Existing Design
Standards Prescribed by Congress
DOE is responsible for enforcing
Federal energy standards, whether those
standards were developed through a
DOE rulemaking pursuant to EPCA or
prescribed by Congress. In EISA 2007,
Congress prescribed design standards
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
0.30 × q ss ( 90 oF ) × 8760
AWEF
specifically for walk-ins that took effect
on January 1, 2009. Typically, DOE
establishes specific enforcement
regulations for each product covered by
existing standards, which may require
manufacturers to file documents such as
a compliance statement and a
certification report. In a compliance
statement, the manufacturer certifies its
products meet the requirements. In a
certification report, the manufacturer
provides product-specific information
that would enable DOE to determine
whether the product meets the standard.
DOE has already established compliance
and certification requirements for other
products.
Until DOE finalizes regulations that
require compliance statements and
certification reports for walk-ins,
manufacturers will not be required to
report data to DOE, but they must still
meet all prescribed design standards
that went into effect on January 1, 2009.
If there is a question on compliance
with design standards, the manufacturer
must make a reasonable case that the
equipment meets those standards.
To address concerns about the EISA
2007 design requirements for walk-ins,
DOE maintains a Frequently Asked
Questions page on the DOE Web site at
https://www1.eere.energy.gov/buildings/
appliance_standards/commercial/
wicf_faqs.html.
IV. Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget
has determined that test procedure
rulemakings do not constitute
‘‘significant regulatory actions’’ under
Executive Order 12866, ‘‘Regulatory
Planning and Review,’’ 58 FR 51735
(October 4, 1993). Accordingly, this
action was not subject to review under
that Executive Order by the Office of
Information and Regulatory Affairs
(OIRA) of the Office of Management and
Budget (OMB).
B. Review Under the National
Environmental Policy Act
In this proposed rule, DOE proposes
to adopt test procedures and related
provisions for walk-in equipment. The
PO 00000
Frm 00019
Fmt 4701
Sfmt 4702
.
Eq. 11
test procedures would be used initially
for the purpose of considering the
adoption of energy conservation
standards for walk-ins, and DOE would
require their use only if standards were
subsequently adopted. The proposed
test procedures will not affect the
quality or distribution of energy and,
therefore, will not result in
environmental impacts. Therefore, DOE
determined that this rule falls into a
class of actions that are categorically
excluded from review under the
National Environmental Policy Act of
1969 (42 U.S.C. 4321 et seq.) and the
Department’s implementing regulations
at 10 CFR part 1021. More specifically,
today’s proposed rule is covered by the
Categorical Exclusion in paragraph A6
to subpart D, 10 CFR part 1021.
Accordingly, neither an environmental
assessment nor an environmental
impact statement is required.
C. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility
analysis (IRFA) for any rule that by law
must be proposed for public comment,
unless the agency certifies that the rule,
if promulgated, will not have a
significant economic impact on a
substantial number of small entities. As
required by Executive Order 13272,
‘‘Proper Consideration of Small Entities
in Agency Rulemaking’’ (67 FR 53461
(August 16, 2002)), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of General
Counsel’s Web site, https://
www.gc.doe.gov.
DOE reviewed the test procedures
considered in today’s notice of proposed
rulemaking under the provisions of the
Regulatory Flexibility Act and the
procedures and policies published on
February 19, 2003. As discussed in more
detail below, DOE found that because
the proposed test procedures have not
previously been required of
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.035
BLL = 0.1× q ss ( 90 oF ) ,
Where qss(90 °F) is the system steady state
refrigeration capacity at 90 °F. When
terms are combined and the expression
simplified, the equation for annual
energy consumption becomes
EP04JA10.034
BLH = 0.7 × q ss ( 90 oF )
EP04JA10.033
For indoor units, tj is assumed to be constant;
thus, nj = 8760, the total number of hours
in a year. BLH and BLL are given by,
respectively,
203
204
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
manufacturers, all manufacturers,
including small manufacturers, could
potentially experience a financial
burden associated with new testing
requirements. While examining this
issue, DOE determined that it could not
certify that the proposed rule, if
promulgated, would not have a
significant effect on a substantial
number of small entities. Therefore,
DOE has prepared an IRFA for this
rulemaking. The IRFA describes
potential impacts on small businesses
associated with walk-in cooler and
freezer testing requirements.
DOE has transmitted a copy of this
IRFA to the Chief Counsel for Advocacy
of the Small Business Administration
for review.
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
1. Reasons for the Proposed Rule
Title III of the EPCA sets forth a
variety of provisions designed to
improve energy efficiency. Part B of
Title III (42 U.S.C. 6291–6309) provides
for the Energy Conservation Program for
Consumer Products Other Than
Automobiles. NECPA (Pub. L. 95–619)
amended EPCA to add Part C of title III,
which established an energy
conservation program for certain
industrial equipment. (42 U.S.C. 6311–
6317) (These parts were subsequently
redesignated as Parts A and A–1,
respectively, for editorial reasons.)
Section 312 of EISA 2007 further
amended EPCA by adding certain
equipment to this energy conservation
program, including walk-in coolers and
walk-in freezers (collectively ‘‘walk-in
equipment’’ or ‘‘walk-ins’’), the subject
of this rulemaking. (42 U.S.C 6311(1),
(2), 6313(f) and 6314(a)(9)) The
proposed rule would establish a test
procedure for walk-in coolers and walkin freezers.
2. Objectives of, and Legal Basis for, the
Proposed Rule
Under EPCA, the overall energy
conservation program consists
essentially of the following parts:
Testing, labeling, and Federal energy
conservation standards. The testing
requirements for covered equipment
consist of test procedures, prescribed
under EPCA. The test procedures, if
adopted, would be used in one of three
ways: (1) Any data from the use of the
test procedure, would be used by DOE
as a basis for developing standards for
walk-in equipment; (2) the procedure
would be used by DOE when
determining equipment compliance
with those standards; and (3)
manufacturers of covered equipment
would be required to use the procedure
as the basis for establishing that their
equipment complies with the relevant
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
energy conservation standards
promulgated pursuant to EPCA and
when making representations regarding
equipment efficiency.
Section 343 of EPCA (42 U.S.C. 6314)
sets forth generally applicable criteria
and procedures for DOE’s adoption and
amendment of test procedures for
covered equipment. That provision
requires that the test procedures
promulgated by DOE be reasonably
designed to produce test results which
reflect energy efficiency, energy use,
and estimated operating costs of the
covered equipment during a
representative average use cycle. It also
requires that the test procedure not be
unduly burdensome to conduct. (42
U.S.C. 6314(a)(2)) Further information
concerning the background of this
rulemaking is provided in Section I of
this preamble.
3. Description and Estimated Number of
Small Entities Regulated
Small businesses, as defined by the
Small Business Administration (SBA)
for the walk-in cooler and freezer
manufacturing industry, are
manufacturing enterprises with 750
employees or fewer. DOE used the small
business size standards published on
January 31, 1996, as amended, by the
SBA to determine whether any small
entities would be required to comply
with the rule. 61 FR 3286; see also 65
FR 30836, 30850 (May 15, 2000), as
amended at 65 FR 53533, 53545
(September 5, 2000). The size standards
are codified at 13 CFR Part 121. The
standards are listed by North American
Industry Classification System (NAICS)
code and industry description and are
available at https://www.sba.gov/idc/
groups/public/documents/
sba_homepage/serv_sstd_tablepdf.pdf.
Walk-in cooler and freezer equipment
manufacturing is classified under
NAICS 333415, Air-Conditioning and
Warm Air Heating Equipment and
Commercial and Industrial Refrigeration
Equipment Manufacturing.
DOE reviewed AHRI’s listing of
commercial refrigeration equipment
manufacturer members and surveyed
the industry to develop a list of
domestic manufacturers. DOE also
asked stakeholders and AHRI
representatives within the industry if
they were aware of any other small
business manufacturers. DOE then
examined publicly available data,
including regulatory databases such as
state databases and the National
Sanitation Foundation (NSF) Section 7
database. DOE identified at least 37
small manufacturers of walk-in cooler
and freezer envelopes, and at least 5
small manufacturers of walk-in cooler
PO 00000
Frm 00020
Fmt 4701
Sfmt 4702
and freezer refrigeration systems.
However, some manufacturers that DOE
interviewed indicated that there could
be many more small business
manufacturers than were publicly listed.
Such unlisted manufacturers could be
very small (< 50 employees) and serve
only a local market. They also may not
submit any information to state or
national regulators such as NSF.
Therefore, DOE believes there may be
more affected small entities than it
estimated and seeks comment on the
number of small entities that may be
impacted by the test procedure.
4. Description and Estimate of
Compliance Requirements
Potential impacts of the proposed test
procedures on manufacturers, including
small businesses, come from impacts
associated with the cost of testing. In
this test procedure NOPR, DOE
proposes measures to reduce the
financial burden of testing on all
manufacturers, including small business
manufacturers. First, where the
procedure gives manufacturers options
in terms of materials, equipment, or
methodology to be used in performing
the test, DOE proposes to allow
manufacturers to use the lowest-cost
option, where possible. For instance,
ASTM E741–06 allows manufacturers to
use any of about 12 tracer gases. DOE
specifies a tracer gas to ensure that all
manufacturers report at the same
accuracy, but specifies the use of carbon
dioxide, which would be the lowest cost
option. Second, DOE proposes to reduce
the total number of tests manufacturers
would have to perform by allowing
them to group similar equipment into a
single family, or basic model, and only
requiring them to test one unit of each
basic model. (See section III.A.1 for a
more detailed discussion of the basic
model proposal.)
The proposed test procedure for
envelopes would require manufacturers
to perform testing in accordance with
two industry test standards: ASTM
C1303–08, ‘‘Standard Test Method of
Predicting Long-Term Thermal
Resistance of Closed-Cell Foam
Insulation,’’ and ASTM E741–06,
‘‘Standard Test Method for Determining
Air Change in a Single Zone by Means
of a Tracer Gas Dilution.’’ DOE spoke
with industry experts to determine the
approximate cost of each test and
determined that a test using ASTM
C1303–08 costs between approximately
$5,000 and $10,000, and a test using
ASTM E741–06 costs between $1,000
and $5,000. A typical manufacturer
would have approximately 8 basic
models, so the total cost of compliance
would be approximately $84,000.
E:\FR\FM\04JAP2.SGM
04JAP2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
The proposed test procedure for
refrigeration systems would require
manufacturers to perform testing in
accordance with a single industry test
standard: AHRI Standard 1250P–2009,
‘‘2009 Standard for Performance Rating
of Walk-In Coolers and Freezers.’’
Because this test was recently
developed by the industry and has not
yet been widely used to test
refrigeration systems, DOE could not
determine how much the test currently
costs. However, DOE researched the cost
of other, similar standards and
subsequently estimated that a test using
AHRI Standard 1250P–2009 would
likely cost approximately $5,000. A
typical refrigeration manufacturer could
have approximately 50 basic models,
making the total cost of compliance
approximately $250,000.
Because the cost of running each test
is the same for all manufacturers, and
because DOE has proposed measures to
reduce burden on all manufacturers,
DOE believes that all manufacturers
would incur comparable costs as a
result of the proposed test procedures.
However, DOE does not expect that
small manufacturers would have fewer
basic models than large manufacturers,
because the equipment is highly
customized throughout the industry. A
small manufacturer could have the same
total cost of testing as a large
manufacturer, but this cost would be a
higher percentage of a small
manufacturer’s annual revenues. Thus,
DOE cannot certify that the differential
impact associated with walk-in cooler
and freezer test procedures on small
businesses would not be significant.
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
5. Duplication, Overlap, and Conflict
With Other Rules and Regulations
DOE is not aware of any rules or
regulations that duplicate, overlap, or
conflict with the rule being considered
today.
6. Significant Alternatives to the Rule
DOE considered a number of
alternatives to the proposed test
procedure, including test procedures
that incorporate industry test standards
other than the three proposed standards,
ASTM C1303–08, ASTM E741–06, and
AHRI Standard 1250P–2009, described
above. Instead of requiring ASTM
C1303–08 for testing the long-term
thermal properties of insulation, DOE
could require only ASTM C518–04,
‘‘Standard Test Method for Steady-State
Thermal Transmission Properties by
Means of the Heat Flow Meter
Apparatus,’’ which tests the thermal
properties of insulation at a certain
point in time (i.e., the point of
manufacture). (Because ASTM C1303–
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
08 incorporates ASTM C518–04,
requiring ASTM C1303–08 is consistent
with the statutory requirement for
basing measurement of the thermal
conductivity of the insulation on ASTM
C518–04.) (42 U.S.C. 6314(a)(9)(A)) A
test of ASTM C518–04 alone costs
approximately $500–$1,000. However,
DOE is considering ASTM C1303 for
other reasons; namely, the concern that
ASTM C518–04 alone does not capture
the performance characteristics of a
walk-in over the period of its use,
because it does not account for
significant changes in the thermal
properties of insulation over time. For
more discussion on this issue, see
Section III.B.2.a.
DOE also considered ASTM E1827–
96(2007), ‘‘Standard Test Methods for
Determining Airtightness of Buildings
Using an Orifice Blower Door,’’ instead
of ASTM E741–06, for testing
infiltration. ASTM E1827–96(2007)
costs about $300–$500 for a single test.
However, DOE believes that ASTM
E1827–96(2007) is not appropriate for
walk-ins because it is conducted by
placing test equipment in the door, and
thus does not account for in infiltration
through the door, which is a major
component of infiltration in walk-ins. In
addition, it is not intended for testing
envelope systems, such as a walk-in,
that have a large temperature difference
between the internal and external air.
Therefore, to complete a blower-door
test, the walk-in would not be able to be
tested at or close to operational
temperatures, resulting in a test that
does not accurately reflect its
performance. For more discussion on
this issue, see Section III.B.2.b.
In the framework document, DOE
considered adapting an existing test
procedure for commercial refrigeration
equipment, such as ARI Standard 1200–
2006, ‘‘Performance Rating of
Commercial Refrigerated Display
Merchandisers and Storage Cabinets,’’
as an alternative to AHRI Standard
1250P–2009. The two tests are based on
a similar methodology for rating
refrigeration equipment in general, but
ARI Standard 1200–2006 requires
testing at only one set of ambient
conditions, whereas AHRI Standard
1250P–2009 requires testing at 3 sets of
ambient conditions for refrigeration
systems with the condensing units
located outdoors. The additional time
required to test the system at 3 sets of
conditions would incur additional cost
and could make AHRI Standard 1250P–
2009 more burdensome than ARI
Standard 1200–2006. However, DOE
believes that AHRI Standard 1250P–
2009 is more appropriate for testing
walk-ins than ARI Standard 1200–2006.
PO 00000
Frm 00021
Fmt 4701
Sfmt 4702
205
A test procedure based on ARI Standard
1200–2006 would require the entire
walk-in to be tested as a whole, but
manufacturers might not have a large
enough test facility to make the
measurements necessary for the ARI
1200–2006 test procedure in a
controlled environment. Also, the
refrigeration system is often
manufactured separately from the
insulated envelope. In this case,
whoever assembled the two components
would bear the burden of conducting
ARI 1200–2006; this party might not be
the manufacturer of the refrigeration
system. In contrast, AHRI 1250P–2009
tests only the refrigeration system. It
does not require a larger test chamber
than other, similar tests, and can be
conducted by the manufacturer of the
refrigeration system. Furthermore,
because AHRI 1250P–2009 requires the
system to be tested at 3 ambient
temperatures, it captures energy savings
from features (for example, floating head
pressure) that allow the system to use
less energy at lower ambient
temperatures. For more discussion on
this issue, see Section III.A.2.
DOE requests comment on the
impacts to small business manufacturers
for these and any other possible
alternatives to the proposed rule. DOE
will consider any comments received
regarding impacts to small business
manufacturers for all the alternatives
identified.
D. Review Under the Paperwork
Reduction Act
Today’s proposed rule contains no
record-keeping requirements. Therefore,
today’s notice of proposed rulemaking
would not impose any new reporting
requirements requiring clearance by
OMB under the Paperwork Reduction
Act, 44 U.S.C. 3501 et seq. The
Department recognizes, however, that if
it adopts standards for walk-in coolers
and walk-in freezers, once the standards
become operative, manufacturers may
become subject to record-keeping
requirements associated with
compliance with the standards.
Therefore, the Department will comply
with the record-keeping requirements of
the Paperwork Reduction Act if and
when energy conservation standards are
adopted.
E. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (Pub. L. 104–4)
(UMRA) requires each Federal agency to
assess the effects of Federal regulatory
actions on State, local, and tribal
governments and the private sector.
With respect to a proposed regulatory
E:\FR\FM\04JAP2.SGM
04JAP2
206
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
action that may result in the
expenditure by State, local and tribal
governments, in the aggregate, or by the
private sector of $100 million or more
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish estimates of the resulting
costs, benefits, and other effects on the
national economy. (2 U.S.C. 1532(a), (b))
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA (62 FR
12820) (also available at https://
www.gc.doe.gov). The proposed rule
published today does not provide for
any Federal mandate likely to result in
an aggregate expenditure of $100
million or more. Therefore, the UMRA
does not require a cost benefit analysis
of today’s proposal.
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
F. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
proposed rule would not have any
impact on the autonomy or integrity of
the family as an institution.
Accordingly, DOE has concluded that it
is not necessary to prepare a Family
Policymaking Assessment.
G. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999) imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have federalism implications. On March
14, 2000, DOE published a statement of
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
policy describing the intergovernmental
consultation process it will follow in the
development of such regulations (65 FR
13735). DOE has examined today’s
proposed rule and has determined that
it does not preempt State law and does
not have a substantial direct effect on
the States, on the relationship between
the national government and the States,
or on the distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of
today’s proposed rule. States can
petition DOE for exemption from such
preemption to the extent, and based on
criteria, set forth in EPCA. (42 U.S.C.
6297) No further action is required by
Executive Order 13132.
H. Review Under Executive Order 12988
With respect to the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform’’ (61 FR 4729, February 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity, (2) write
regulations to minimize litigation, and
(3) provide a clear legal standard for
affected conduct rather than a general
standard and promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in section 3(a) and section
3(b) to determine whether they are met
or it is unreasonable to meet one or
more of them. DOE has completed the
required review and determined that, to
the extent permitted by law, this
proposed rule meets the relevant
standards of Executive Order 12988.
I. Review Under the Treasury and
General Government Appropriations
Act, 2001
The Treasury and General
Government Appropriations Act, 2001
PO 00000
Frm 00022
Fmt 4701
Sfmt 4702
(44 U.S.C. 3516, note) provides for
agencies to review most disseminations
of information to the public under
guidelines established by each agency
pursuant to general guidelines issued by
OMB. OMB’s guidelines were published
at 67 FR 8452 (February 22, 2002), and
DOE’s guidelines were published at 67
FR 62446 (October 7, 2002). DOE has
reviewed today’s notice under the OMB
and DOE guidelines and has concluded
that it is consistent with applicable
policies in those guidelines.
J. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001) requires Federal agencies to
prepare and submit to the Office of
Information and Regulatory Affairs
(OIRA), Office of Management and
Budget, a Statement of Energy Effects for
any proposed significant energy action.
A ‘‘significant energy action’’ is defined
as any action by an agency that
promulgated or is expected to lead to
promulgation of a final rule, and that (1)
Is a significant regulatory action under
Executive Order 12866, or any successor
order; and (2) is likely to have a
significant adverse effect on the supply,
distribution, or use of energy; or (3) is
designated by the Administrator of
OIRA as a significant energy action. For
any proposed significant energy action,
the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use
should the proposal be implemented,
and of reasonable alternatives to the
action and their expected benefits on
energy supply, distribution, and use.
Today’s regulatory action is not a
significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy. The Administrator of OIRA
also did not designate today’s action as
a significant energy action. Therefore, it
is not a significant energy action, and
DOE has not prepared a Statement of
Energy Effects.
K. Review Under Executive Order 12630
DOE has determined pursuant to
Executive Order 12630, ‘‘Governmental
Actions and Interference with
Constitutionally Protected Property
Rights,’’ 53 FR 8859 (March 18, 1988)
that this proposed rule would not result
in any takings which might require
compensation under the Fifth
Amendment to the United States
Constitution.
E:\FR\FM\04JAP2.SGM
04JAP2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
L. Review Under Section 32 of the
Federal Energy Administration (FEA)
Act of 1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91), DOE must comply with section 32
of the Federal Energy Administration
Act of 1974, as amended by the Federal
Energy Administration Authorization
Act of 1977. (15 U.S.C. 788) Section 32
provides in part that, where a proposed
rule contains or involves use of
commercial standards, the rulemaking
must inform the public of the use and
background of such standards. The rule
proposed in this notice incorporates
testing methods contained in the
following commercial standards: ASTM
C1303–08, ‘‘Standard Test Method of
Predicting Long-Term Thermal
Resistance of Closed-Cell Foam
Insulation;’’ ASTM E741–06, ‘‘Standard
Test Method for Determining Air
Change in a Single Zone by Means of a
Tracer Gas Dilution;’’ and AHRI
Standard 1250P, ‘‘2009 Standard for
Performance Rating of Walk in Coolers
and Freezers.’’ The Department has
evaluated these standards and is unable
to conclude whether they fully comply
with the requirements of section 32(b) of
the Federal Energy Administration Act,
i.e., whether they were developed in a
manner that fully provides for public
participation, comment, and review. As
required by section 32(c) of the Federal
Energy Administration Act, of 1974, as
amended, DOE will consult with the
Attorney General and the Chairman of
the Federal Trade Commission before
prescribing a final rule concerning the
impact on competition of requiring
manufacturers to use the methods
contained in these standards to test
walk-in equipment.
V. Public Participation
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
A. Attendance at Public Meeting
The time, date, and location of the
public meeting are provided in the
DATES and ADDRESSES sections at the
beginning of this document. Anyone
who wants to attend the public meeting
must notify Ms. Brenda Edwards at
(202) 586–2945. As explained in the
ADDRESSES section, foreign nationals
visiting DOE headquarters are subject to
advance security screening procedures.
B. Procedure for Submitting Requests To
Speak
Any person who has an interest in the
topics addressed in this notice, or who
is a representative of a group or class of
persons that has an interest in these
issues, may request an opportunity to
make an oral presentation at the public
meeting. Such persons may hand-
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
deliver requests to speak to the address
shown in the ADDRESSES section at the
beginning of this notice between 9 a.m.
and 4 p.m., Monday through Friday,
except Federal holidays. Requests may
also be sent by mail or email to: Ms.
Brenda Edwards, U.S. Department of
Energy, Building Technologies Program,
Mailstop EE–2J, 1000 Independence
Avenue, SW., Washington, DC 20585–
0121, or Brenda.Edwards@ee.doe.gov.
Persons who wish to speak should
include in their request a computer
diskette or CD in WordPerfect, Microsoft
Word, PDF, or text (ASCII) file format
that briefly describes the nature of their
interest in this rulemaking and the
topics they wish to discuss. Such
persons should also provide a daytime
telephone number where they can be
reached.
DOE requests that those persons who
are scheduled to speak submit a copy of
their statements at least one week prior
to the public meeting. DOE may permit
any person who cannot supply an
advance copy of this statement to
participate, if that person has made
alternative arrangements with the
Building Technologies Program in
advance. When necessary, the request to
give an oral presentation should ask for
such alternative arrangements.
C. Conduct of Public Meeting
DOE will designate a DOE official to
preside at the public meeting and may
also employ a professional facilitator to
aid discussion. The public meeting will
be conducted in an informal, conference
style. The meeting will not be a judicial
or evidentiary public hearing, but DOE
will conduct it in accordance with
section 336 of EPCA (42 U.S.C. 6306).
Discussion of proprietary information,
costs or prices, market share, or other
commercial matters regulated by U.S.
anti-trust laws is not permitted.
DOE reserves the right to schedule the
order of presentations and to establish
the procedures governing the conduct of
the public meeting. A court reporter will
record the proceedings and prepare a
transcript.
At the public meeting, DOE will
present summaries of comments
received before the public meeting,
allow time for presentations by
participants, and encourage all
interested parties to share their views on
issues affecting this rulemaking. Each
participant may present a prepared
general statement (within time limits
determined by DOE) before the
discussion of specific topics. Other
participants may comment briefly on
any general statements. At the end of
the prepared statements on each specific
topic, participants may clarify their
PO 00000
Frm 00023
Fmt 4701
Sfmt 4702
207
statements briefly and comment on
statements made by others. Participants
should be prepared to answer questions
from DOE and other participants. DOE
representatives may also ask questions
about other matters relevant to this
rulemaking. The official conducting the
public meeting will accept additional
comments or questions from those
attending, as time permits. The
presiding official will announce any
further procedural rules or modification
of procedures needed for the proper
conduct of the public meeting.
DOE will make the entire record of
this proposed rulemaking, including the
transcript from the public meeting,
available for inspection at the U.S.
Department of Energy, 6th Floor, 950
L’Enfant Plaza, SW., Washington, DC
20024, (202) 586–2945, between 9 a.m.
and 4 p.m., Monday through Friday,
except Federal holidays. Anyone may
purchase a copy of the transcript from
the transcribing reporter.
D. Submission of Comments
DOE will accept comments, data, and
information regarding the proposed rule
no later than the date provided at the
beginning of this notice. Comments,
data, and information submitted to
DOE’s e-mail address for this
rulemaking should be provided in
WordPerfect, Microsoft Word, PDF, or
text (ASCII) file format. Interested
parties should avoid the use of special
characters or any form of encryption,
and wherever possible, comments
should include the electronic signature
of the author. Absent an electronic
signature, comments submitted
electronically must be followed and
authenticated by submitting a signed
original paper document to the address
provided at the beginning of this notice.
Comments, data, and information
submitted to DOE via mail or hand
delivery/courier should include one
signed original paper copy. No
telefacsimiles (faxes) will be accepted.
According to 10 CFR 1004.11, any
person submitting information that he
or she believes to be confidential and
exempt by law from public disclosure
should submit two copies: One copy of
the document including all the
information believed to be confidential,
and one copy of the document with the
information believed to be confidential
deleted. DOE will make its own
determination as to the confidential
status of the information and treat it
according to its determination.
Factors of interest to DOE when
evaluating requests to treat submitted
information as confidential include (1)
A description of the items, (2) whether
and why such items are customarily
E:\FR\FM\04JAP2.SGM
04JAP2
208
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
treated as confidential within the
industry, (3) whether the information is
generally known by or available from
other sources, (4) whether the
information has previously been made
available to others without obligation
concerning its confidentiality, (5) an
explanation of the competitive injury to
the submitting person which would
result from public disclosure, (6) a date
upon which such information might
lose its confidential nature due to the
passage of time, and (7) why disclosure
of the information would be contrary to
the public interest.
E. Issues on Which DOE Seeks Comment
DOE is particularly interested in
receiving comments on the following
issues:
1. Test Procedure Improvements
DOE requests comments on
improvements in the test procedures
that it should consider. In submitting
comments, interested parties should
state the nature of the recommended
modification and an explanation of how
it improves upon the test procedure
proposed in this NOPR. See section II
for details.
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
2. Basic Model
Because walk-in equipment tends to
be highly customized, DOE is
considering allowing manufacturers to
group similar walk-in equipment under
a single ‘‘basic model’’ and only
subjecting one unit of each basic model
to testing. DOE will use the term ‘‘basic
model’’ to represent a single family of
walk-in equipment, consisting of walkin equipment or models of equipment
that do not have any differentiating
electrical, physical, or functional
features that significantly affect energy
consumption characteristics. DOE
requests comments on the proposed
basic model approach. See section
III.A.1 for details.
3. Separate Envelope and Refrigeration
Tests
For any walk-in, two different
manufacturers may make the two main
components: The envelope, or insulated
box, and the refrigeration system. In this
notice, DOE proposes separate test
procedures for the envelope and the
refrigeration system. The envelope
manufacturer would be responsible for
testing the envelope according to the
envelope test procedure, and the
refrigeration system manufacturer
would be responsible for testing the
refrigeration system according to the
refrigeration system test procedure. The
purpose of this provision is to
accurately reflect the structure of the
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
walk-in market and assign testing
responsibilities to the equipment
manufacturers. DOE requests comments
on the proposed approach to develop
separate test procedures. See section
III.A.4 for details.
4. Definition of Envelope
DOE requests comments on the
following definition of ‘‘envelope:’’ ‘‘(1)
a piece of equipment that is the portion
of a walk-in cooler or walk-in freezer
that isolates the interior, refrigerated
environment from the ambient, external
environment; and (2) all energyconsuming components of the walk-in
cooler or walk-in freezer that are not
part of its refrigeration system.’’ See
section III.B.1 for details.
5. Effect of Impermeable Skins on LongTerm R-Value
DOE received many comments on the
framework document regarding longterm R-value. After researching the
issue, DOE determined that the R-value
of insulating foams diminish after
manufacture at rates that vary by
material type and environmental
conditions. Diffusion of gases and
moisture infiltration are the key
mechanisms of R-value decline. Many
manufacturers seek to prevent or delay
diffusion and moisture infiltration by
sealing the foam in a ‘‘skin,’’ typically
a metal material. DOE received
comments suggesting that these skins
can be made fully impermeable while
other comments argued that full
impermeability cannot be achieved due
to imperfect sealing at panel joints,
imperfect adherence of foam to metal
during manufacture, deliberate
punctures for fixtures and shelving,
and/or inadvertent punctures that
typically occur in the field. DOE
requests feedback on this issue,
including the submission of test results
on the impact of impermeable skins on
long-term R-value. Specifically, DOE
requests that interested parties submit
or identify any peer-reviewed,
published data pertaining to the efficacy
of skins in preventing or delaying Rvalue decline. See section III.B.2.a for
details.
6. Measuring Long-Term R-Value Using
American Society for Testing and
Materials (ASTM) C1303–08
DOE proposes accounting for R-value
decline due to diffusion of gases by
requiring manufacturers to condition
their foam prior to testing. DOE
proposes requiring manufacturers to
condition foam using ASTM C1303–08,
which conditions foam using an
accelerated aging method prior to
testing its R-value. Because ASTM
PO 00000
Frm 00024
Fmt 4701
Sfmt 4702
C1303–08 uses ASTM C518–2004, using
ASTM C1303–08 would be consistent
with EPCA. (42 U.S.C. 6314(a)(9)(A)(ii))
DOE requests feedback on the proposal
to require conditioning and testing foam
using ASTM C1303–08. DOE recognizes
that ASTM C1303–08 is designed for
unfaced and permeably faced foams
rather than the impermeably faced
foams typical of walk-ins. DOE requests
feedback on the use of ASTM C1303–08
for foams that will be impermeably
faced.
DOE is considering several exceptions
and clarifications to ASTM C1303–08 to
satisfy requirements of EPCA and to
make the test procedure more applicable
to walk-ins. DOE requests feedback on
the number of samples and sample
thicknesses, the use of interpolation of
results for foam thicknesses within the
specified ±0.5 inch range, and the use of
the core stack R-value out of a sample
size of three stacks for the purpose of
calculating walk-in energy use.
Lastly, ASTM C1303–08 cannot be
used for non-foam materials, but DOE is
not aware of any non-foam materials
currently being used as insulation in
walk-in coolers or freezers. DOE
requests comment on whether non-foam
technologies, such as vacuum insulated
panels or aerogels, are likely to be
commercially available for walk-ins
within the next 5 years. See section
III.B.2.a for details.
7. Infiltration
Air infiltration causes a substantial
amount of heat gain through the
envelope. After evaluating several
methods of testing and measuring the
air infiltration, DOE proposes requiring
ASTM E741–06, also referred to as the
gas tracer method, as the test procedure
for measuring steady-state infiltration
and the effectiveness of infiltration
reduction devices (for air infiltration
unrelated to door opening events).
Because door opening also contributes
to infiltration, DOE proposes accounting
for this infiltration pathway. DOE does
not, however, propose to require
manufacturers to individually measure
the infiltration from door opening
events, due to the complexity of this
type of testing and the availability of
accurate analytical models, which
would make a test procedure very
difficult to implement. DOE proposes
using analytical methods based on
ASHRAE fundamentals as well as
assumed door-opening frequency and
duration and the measured infiltration
barrier effectiveness to calculate the air
infiltration associated with each dooropening event. DOE requests comments
on the proposed test method for steadystate infiltration. DOE requests input
E:\FR\FM\04JAP2.SGM
04JAP2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
and feedback on the calculations and
assumptions proposed for determining
infiltration from door-opening events.
See section III.B.2.b for details on the
proposed analytical methods.
8. Nominal Coefficient of Performance
of Refrigeration
In developing a test procedure for the
envelope alone, without a refrigeration
system, DOE had to determine the
energy consumption associated with
heat gain through the envelope due to
conduction and infiltration. DOE
proposes to assume a nominal EER for
the refrigeration system to convert the
heat gain through the box into a
measure of the energy consumption of a
theoretical refrigeration system that
would be removing this heat from the
box. For comparison purposes, DOE
recommends that the EER be 12.4 Btu
per watt hour (Btu/Wh) for coolers and
6.3 Btu/Wh for freezers because these
are typical EER values. DOE requests
comments on this proposal and on the
assumed value for the EER. See section
III.B.3.a for details.
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
9. Measuring the U-Value of Glass
Because conduction through glass
components can be a significant source
of heat transfer through walk-in
envelopes, DOE seeks to order to
account for improvements in glass
performance in the test procedure. DOE
proposes two options for manufacturers:
(1) If manufacturers of glass doors used
in walk-ins participate in the NFRC
rating program, the performance of the
door shall be simply read from its label
and used for calculations in this test
procedure. If glass door manufacturers
do not participate in the NFRC rating
program, then (2) DOE proposes to
require manufacturers to use the LBNL’s
publicly available Window 5.2 software
package to calculate glass door
performance. DOE seeks comment on
the availability of performance data on
glass products used in walk-in
applications, glass component
manufacturers’ participation in third
party certification programs such as
NFRC, and the proposed method for
predicting the thermal performance of
glass components using Window 5.2.
See section III.B.3.b for more
information.
10. Floor R-Value
EPCA does not require walk-in cooler
floors to meet a specific R-value. In
many instances, walk-in coolers are
shipped without additional insulating
floors and are simply placed on top of
an existing surface, such as a concrete
slab. Since concrete is the floor surface
most commonly used with floorless
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
walk-in coolers DOE is considering
using the R-value of 6-inch concrete to
calculate energy lost through these
floors. DOE proposes using an R-value
of 0.6 ft2-° F-hr/Btu for 6-inch concrete.
Since walk-in freezers are required to
have a floor insulation of R–28, DOE
will assume this R-value for purposes of
calculating the energy loss through
walk-in freezer floors if the
manufacturer does not provide any
additional insulating surface. DOE
requests comments on these
assumptions. See section III.B.3.b for
details.
11. Electrical Duty Cycle
As part of the envelope test
procedure, DOE recommends
calculating the electricity consumption
of lights, sensors, and other
miscellaneous electrical devices not
considered part of the refrigeration
equipment using name-plate rating and
an assumed daily operation. DOE
incorporates assumed duty cycles of
lights, anti-sweat heaters, and other
devices based on whether they are
controlled by a preset control system.
While these assumptions may not reflect
the actual behaviorally related energy
consumption, they will provide a means
for comparison. DOE requests comments
on whether the duty cycle assumptions
are appropriate. See section III.B.3.d for
details.
12. Normalization Factor
For the envelope test procedure, DOE
proposes to normalize the energy
consumption by a certain factor related
to the size of the walk-in so that
manufacturers of larger walk-ins and
walk-ins with glass doors are not
unfairly penalized. DOE believes that
the surface area of the envelope is an
appropriate normalization factor,
because surface area is the key
geometric characteristic related to both
conduction and infiltration and is
particularly important as the ratio of
glass door area to wall area increases.
DOE requests comments on the proposal
to normalize the energy consumption by
the surface area of the walk-in. See
section III.B.3.e for details.
13. Daily Energy Consumption
Coefficients
In order to compare envelopes that are
similar enough to be included in the
same basic model but are not identical,
the test procedure allows for calculating
Daily Energy Consumption Coefficients,
or DECCs, using test results from a
particular envelope within a basic
model, and then applying these DECCs
to other envelopes within a basic model
to calculate the energy consumption of
PO 00000
Frm 00025
Fmt 4701
Sfmt 4702
209
the other units. DECCs are essentially
scaling factors that allow a manufacturer
to change certain parameters of an
envelope and calculate the
corresponding change in energy
consumption. DOE believes that this
approach would reduce the testing
burden on manufacturers because it
would not require manufacturers to test
every unit produced with slight
variations due to customer specification.
DOE requests comment on this rating
methodology. For formulas and more
information, see section III.B.3.f.
14. Definition of Refrigeration System
DOE requests comments on the
following definition of ‘‘refrigeration
system:’’ ‘‘the mechanism used to create
the refrigerated environment in the
interior of a walk-in cooler or freezer,
consisting of an integrated singlepackage refrigeration unit, or a split
system with separate unit cooler and
condensing unit sections, or a unit
cooler that is connected to a central rack
system; and including all controls and
other components integral to the
operation of this mechanism.’’ See
section III.C.1 for details.
15. Measurements and Calculations of
Energy Use of Refrigeration Systems
The test procedure DOE proposes to
adopt, AHRI Standard 1250P–2009,
determines the annual walk-in energy
factor, or AWEF, which is a measure of
the efficiency of a walk-in’s refrigeration
system. However, DOE is required by
EPCA to establish ‘‘a test procedure to
measure * * * energy use.’’ (42 U.S.C.
6314(a)(9)(B)(i)) In light of this
requirement, DOE proposes that
manufacturers determine both the
AWEF and the annual energy
consumption of their equipment using
the test procedure, which will enable
the test procedure to be consistent with
the requirements of EPCA to develop
test procedures that measure the energy
consumption of walk-in equipment.
DOE is considering satisfying the
statutory requirement by deriving the
energy consumption of the walk-in
refrigeration system from data obtained
when the test procedure is performed.
DOE’s derivation process, and further
information, can be found in section
III.C.4.
16. Impacts on Small Businesses
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility
analysis (IRFA) for any rule that by law
must be proposed for public comment,
unless the agency certifies that the rule,
if promulgated, will not have a
significant economic impact on a
E:\FR\FM\04JAP2.SGM
04JAP2
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
substantial number of small entities.
Upon examination of this NOPR, DOE
could not certify that the rule, if
promulgated, would not have a
significant economic impact on a
substantial number of small entities;
therefore, DOE prepared an IRFA for
this rule. DOE requests comment on the
number of small businesses affected by
the proposed rule, and seeks comment
on impacts to small business
manufacturers for any possible
alternatives to the proposed rule. More
information, along with the text of the
IRFA, can be found in section IV.C.
VI. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this proposed rule.
List of Subjects in 10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Reporting and recordkeeping
requirements.
Issued in Washington, DC, on December
14, 2009.
Cathy Zoi,
Assistant Secretary, Energy Efficiency and
Renewable Energy.
For the reasons stated in the
preamble, DOE proposes to amend part
431 of chapter II of title 10, of the Code
of Federal Regulations, to read as set
forth below.
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 431
continues to read as follows:
Authority: 42 U.S.C. 6291–6317.
§ 431.302 Definitions concerning walk-in
coolers and walk-in freezers.
Basic Model means all units of a given
type of walk-in equipment
manufactured by a single manufacturer,
and—
(1) With respect to envelopes, which
do not have any differing construction
methods, materials, components, or
other characteristics that significantly
affect the energy consumption
characteristics.
(2) With respect to refrigeration
systems, which have the same primary
energy source and which do not have
any differing electrical, physical, or
functional characteristics that
significantly affect energy consumption.
Envelope means (1) the portion of a
walk-in cooler or walk-in freezer that
isolates the interior, refrigerated
environment from the ambient, external
environment; and (2) all energyconsuming components of the walk-in
cooler or walk-in freezer that are not
part of its refrigeration system.
Refrigeration system means the
mechanism used to create the
refrigerated environment in the interior
of a walk-in cooler or freezer, consisting
of an integrated single-package
refrigeration unit, or a split system with
separate unit cooler and condensing
unit sections, or a unit cooler that is
connected to a central rack system; and
including all controls and other
components integral to the operation of
this mechanism.
*
*
*
*
*
Walk-in equipment means either the
envelope or the refrigeration system of
a walk-in cooler or freezer.
3. Section 431.303 is amended by
adding new paragraphs (b)(2), (b)(3),
and (c) to read as follows:
§ 431.303 Materials incorporated by
reference.
*
*
*
*
*
(b) * * *
(2) ASTM C1303–08, Standard Test
Method of Predicting Long Term
Thermal Resistance of Closed-Cell Foam
Insulation, approved September 15,
2008, IBR approved for § 431.304.
2. Section 431.302 is amended by
adding, in alphabetical order,
definitions for ‘‘Basic model,’’
‘‘Envelope,’’ ‘‘Refrigeration system,’’
and ‘‘Walk-in equipment’’ to read as
follows:
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
Annual Energy Consumption ( coolers ) =
Annual Energy Consumption ( freezers ) =
Where qss (90 °F) is the steady state net
refrigeration capacity measured at
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
PO 00000
Fmt 4701
§ 431.304 Uniform test method for the
measurement of energy consumption of
walk-in coolers and walk-in freezers.
(a) Scope. This section provides test
procedures for measuring, pursuant to
EPCA, the energy consumption of walkin coolers and walk-in freezers.
(b) Testing and Calculations.
(1) Determine the energy consumption
of walk-in cooler and walk-in freezer
envelopes by conducting the test
procedure specified in Appendix A to
this subpart.
(2) Determine the U-value of glass
components from the product label in
compliance with the National
Fenestration Rating Council’s Product
Certification Program, PCP–2007, or by
using the Window 5.2 software to
calculate the performance of the glass.
(3) Determine the Annual Walk-in
Efficiency Factor of walk-in cooler and
walk-in freezer refrigeration systems by
conducting the test procedure set forth
in AHRI Standard 1250P–2009
(incorporated by reference, see
§ 431.303).
(4) Determine the energy consumption
of walk-in cooler and walk-in freezer
refrigeration systems by:
(i) For refrigeration systems with the
condensing unit located inside a
conditioned space, performing the
following calculations for coolers and
freezers, respectively:
0.30 × q ss ( 90 oF ) × 8760
Annual Walk-in Efficiency Factor
0.53 × q ss ( 90 oF ) × 8760
Annual Walk-in Efficiency Factor
an ambient condition of 90 °F, and
the Annual Walk-In Efficiency
Frm 00026
(3) ASTM E741–06, Standard Test
Method for Determining Air Change in
a Single Zone by Means of a Tracer Gas
Dilution, approved October 1, 2006, IBR
approved for § 431.304.
(c) AHRI. Air-Conditioning, Heating,
and Refrigeration Institute, 2111 Wilson
Boulevard, Suite 500, Arlington, VA
22201, (703) 600–0366, or https://
www.ahrinet.org.
(1) AHRI Standard 1250P–2009, 2009
Standard for Performance Rating of
Walk-In Coolers and Freezers, approved
September 2009, IBR approved for
§ 431.304.
(2) Reserved.
4. Section 431.304 is revised to read
as follows:
Sfmt 4702
Factor is calculated from the results
of the test procedures set forth in
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.036
210
211
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
(ii) For refrigeration systems with the
condensing unit located outdoors,
performing the following calculations
for coolers and freezers, respectively:
(
⎡
qss ( 95 oF ) × t j − 35
⎢0.24 × qss ( 95 oF ) + 0.06 ×
∑⎢
60
j=1 ⎣
Annual Energy Consumption (coolers) =
Annual Walk-in Efficency Factor
n
(
)⎤× n
⎥
j
)⎤× n
⎥
j
⎡
qss ( 95 oF ) × t j + 10
⎢0.28 × qss ( 95 oF ) + 0.25 ×
∑⎢
105
j=1 ⎣
Annual Energy Consumption (freezers) =
Annual Walk-in Efficency Factor
n
bins listed in Table D1 of AHRI
Standard 1250P–2009 (incorporated
by reference, see § 431.303); and the
Annual Walk-In Efficiency Factor is
calculated from the results of the
test procedures set forth in AHRI
Annual Energy Consumption (coolers) =
Annual Energy Consumption (freezers) =
f
Where qmix,evap is the net capacity of the
evaporator coil, determined by
testing the unit cooler at the 25 °F
suction dewpoint for a cooler and
the ¥20 °F suction dewpoint for a
freezer, at the maximum evaporator
fan speed, according to AHRI
standard 1250P–2009 (incorporated
by reference, see § 431.303); and the
Annual Walk-in Efficiency Factor is
calculated from the results of the
test procedures set forth in AHRI
Standard 1250P–2009 (incorporated
by reference, see § 431.303).
5. Appendix A is added to subpart R
of part 431 to read as follows:
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
Appendix A to Subpart R of Part 431—
Uniform Test Method for the
Measurement of Energy Consumption of
the Envelopes of Walk-In Coolers and
Walk-In Freezers
1.0
Scope
2.0
0.30 × qmix,evap × 8760
Annual Walk-in Efficiency Factor
0.53 × qmix,evap × 8760
Annual Walk-in Efficiency Factor
Definitions
20:56 Dec 31, 2009
Jkt 220001
TABLE A.1—TEMPERATURE AND
RELATIVE HUMIDITY CONDITIONS
Value
Additional Definitions
(a) Unless explicitly stated otherwise, the
surface area for all measurements is the area
as measured on the external surface of the
walk-in.
(b) A device or control system that
‘‘automatically’’ opens and closes doors
without direct user contact (i.e., a motion
sensor that senses when a forklift is
approaching the entrance to a door, opens,
and then closes after the forklift has passed).
(c) Unless explicitly stated otherwise, all
calculations and test procedure
measurements shall use the temperature and
relative humidity data shown in Table A.1.
For installations where two or more walk-in
envelopes share any surface(s), the ‘‘external
conditions’’ of the shared surface(s) should
reflect the internal conditions of the
neighboring walk-in.
This appendix covers the test requirements
used to measure the energy consumption of
the envelopes of walk-in coolers and walk-in
freezers.
VerDate Nov<24>2008
Standard 1250P–2009 (incorporated
by reference, see § 431.303).
(iii) For refrigeration systems
consisting of a unit cooler connected to
a rack system, performing the following
calculations for coolers and freezers,
respectively:
The definitions contained in § 431.302 are
applicable to this appendix.
2.1
PO 00000
⎥
⎦
Frm 00027
Fmt 4701
Sfmt 4700
Units
Internal Conditions (cooled space within
envelope)
Cooler:
Dry Bulb Temperature ...
Relative Humidity ..........
Freezer:
Dry Bulb Temperature ...
Relative Humidity ..........
35
60
F
%
¥10
60
F
%
External Conditions (space external to the
envelope)
Freezer and Cooler:
Dry Bulb Temperature ...
Relative Humidity ..........
75
40
F
%
3.0
Test Apparatus and General Instructions
3.1
Conduction Heat Gain
3.1.1 Glass Doors
(a) All dimensional measurements for glass
doors include the door frame and glass.
(b) Calculate the individual and total glass
door surface area (Aglass) as follows:
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.038
Where qss (95 °F) is the steady state net
refrigeration capacity measured at
an ambient condition of 95 °F; tj
and nj represent the outdoor
temperature at each bin j and the
number of hours in each bin j,
respectively, for the temperature
⎥
⎦
EP04JA10.037
AHRI Standard 1250P–2009
(incorporated by reference, see
§ 431.303).
212
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
A glass,i = ( Wglass, i × H glass, i ) × n i
( 3-1)
i
A glass,tot = ∑ ( Wglass, i × H glass, i ) × n i
( 3-2 )
l
Where:
i = index for each type of unique glass door
used in cooler or freezer being tested,
ni = number of identical glass doors of type
i,
Wglass,i = width of glass door (including door
frame), and
Hglass,i = height of glass door (including door
frame).
(c) Calculate the temperature differential(s)
DTi for each unique glass door (°F) as follows:
ΔTi = TDB,int,i − TDB,ext,i
(3-3)
Where:
i
Qcond-glass,door = ∑ A glass,i × ΔTi × U glass,i × n i
i = Index for each type of unique glass door
used in cooler or freezer being tested,
TDB,int,i = dry-bulb air temperature inside the
cooler or freezer, °F
TDB,ext,i = dry-bulb air temperature external to
cooler or freezer, °F
(d) Calculate the conduction load through
the glass doors, (Qcond-glass,door):
(3-4)
l
Aglass,i = total surface area of all walk-in glass
doors of type i, ft2; and
DT1 = temperature differential between
refrigerated and adjacent zones, °F.
A glass,wall,i = ( Wglass,wall,i × H glass,wall,i ) × n i
3.1.2
Wall Glass and Doors With Inset Glass
(a) Calculate the individual and total glass
surface area (Aglass,wall), as follows:
(3-5)
TDB,int,glass,wall,i = dry-bulb air temperature
inside the cooler or freezer, °F
TDB,ext,glass,wall,i = dry-bulb air temperature
external to cooler or freezer, °F
(c) Calculate the conduction load through
the glass walls and glass insets,
(Qcond-glass,wall), as follows:
i
Qcond -glass, wall = ∑ Aglass,wall,i × ΔTglass,wall,i × Uglass,wall,i × ni
(3-8)
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
l
Where:
ni = number of identical glass walls or insets
of type i;
Uglass,wall,i = thermal transmittance, U-value of
the glass wall, of type i, Btu/h-ft2-°F;
Aglass,wall,i = total surface area of all walk-in
glass walls and insets of type i, ft2; and
DTglass,wall,i = temperature differential
between refrigerated and adjacent zones,
°F.
i
j
k
1
l
Non-Glass Envelope Components
(a) Calculate the total surface area of the
walk-in non-glass envelope (Anon-glass,tot), as
follows:
l
l
3.1.3
l
Anon-glass,tot = ∑ Awalls,i + ∑ Afloor , j + ∑ Aceiling,k + ∑ Anon-glass doors,l
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
PO 00000
Frm 00028
Fmt 4701
Sfmt 4725
E:\FR\FM\04JAP2.SGM
(3-9)
04JAP2
EP04JA10.045
EP04JA10.044
Where:
i = Index for each type of unique glass door
used in cooler or freezer
(3-7)
-
EP04JA10.043
ΔTglass, wall,i = TDB,int,glass, wall,i − TDB,ext ,glass, wall,i
(b) Calculate the temperature differential(s)
DTglass,wall,i for each unique glass wall (°F), as
follows:
EP04JA10.042
Wglass,wall,,i = width of glass wall (including
glass framing)
Hglass,wall,i = height of glass wall (including
glass framing)
EP04JA10.041
Where:
i = index for each type of unique glass door
used in cooler or freezer being tested,
ni = number of identical glass walls or insets
of type i,
EP04JA10.046
(3-6)
l
EP04JA10.040
i
A glass,wall,tot = ∑ ( Wglass,wall,i × H glass,wall,i ) × n i
EP04JA10.039
Where:
ni = number of identical glass doors of type
i;
Uglass,i = thermal transmittance, U-value of
the door, of type i, Btu/h-ft2-°F;
213
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
Aceiling ,k
l
R non-glass,ceil,k
3.2
Infiltration Heat Gain
3.2.1
Steady State Infiltration Calculations
(a) Convert dry-bulb internal and external
air temperatures from °F to Rankine (°R), as
follows:
(
⎡⎛ C
Pws = exp ⎢⎜ 8
⎢⎜
⎣⎝ TDB,R
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
(3-13)
R non-glass,door,l
3.1.4
Total Conduction Load
(3-11)
1
Where:
TDB-int,R = the dry-bulb temperature of
internal walk-in air, °R; and
TDB-ext,R = the average dry-bulb temperature
of air surrounding the walk-in, °R.
(b) Calculate the water vapor saturation
pressure for the external air and the internal
refrigerated air, as follows:
(1) If TDB,R < 491.67 °R (32 °F), using
following equation to calculate water vapor
saturation pressure (Pws in psia):
) (
) (
C2 = ¥4.8932428 E+00,
C3 = ¥5.3765794 E–03,
C4 = 1.9202377 E–07,
C5 = 3.5575832 E–10,
C6 = ¥9.0344688 E–14, and
(
Jkt 220001
) (
) (
(c) Calculate the absolute humidity ratio, w,
as follows:
(
(
)⎤
⎥
)⎥
⎦
⎡ 0.62198 × RH × P
ws
ω= ⎢
⎢ 14.696 − RH × P
ws
⎣
(3-16)
)
Frm 00029
Fmt 4701
(3-14)
⎦
Sfmt 4700
(3-15)
RH = relative humidity in decimal format
(e.g., 0.40 for 40 percent) (for the internal
or external air), and
Pws = water vapor saturation pressure.
(d) Calculate air specific volume, n, (ft3/lb),
as follows:
Where:
PO 00000
⎤
)⎥
⎥
C7 = 4.1635019 E+00.
(2) If TDB,R > 491.67 °R (32 °F), use the
following equation to calculate water vapor
saturation pressure (Pws in psia):
⎤
⎞
3
2
⎟ + C9 + ( C10 × TDB,R ) + C11 × TDB,R + C12 × TDB,R + C13 × 1n ( TDB,R ) ⎥
⎟
⎥
⎠
⎦
Where:
TDB,R = dry-bulb temperature (for the internal
and external air), °R;
C8 = ¥1.0440397 E+04;
C9 = ¥1.1294650 E+01;
C10 = ¥2.7022355 E–02;
C11 = 1.2890360 E–05;
C12 = 2.4780681 E–09; and
C13 = 6.5459673 E+00.
20:56 Dec 31, 2009
) (
(3-10)
(a) Calculate total conduction load, Qcond,
(Btu/h), as follows:
⎞
4
2
3
⎟ + C2 + ( C3 × TDB,R ) + C4 × TDB,R + C5 × TDB,R + C6 × TDB,R + C 7× 1n ( TDB,R )
⎟
⎠
Where:
TDB,R = dry-bulb temperature in Rankine (for
the internal or external air),
C1 = ¥1.0214165 E+04,
VerDate Nov<24>2008
(3-12)
TDB-ext,R = TDB-ext + 459.67 oF
⎡⎛ C
Pws = exp ⎢⎜ 1
⎢⎜ TDB,R
⎣⎝
TDB-int,R = TDB-int + 459.67 oF
l
ΔTk = dry bulb temperature differential
between internal and external air, of type
k, °F
ΔTl = dry bulb temperature differential
between internal and external air, of type
l, °F
Qcond = Qcond-non-glass + Qcond-glass,wall + Qcond-glass,door
Where:
Qcond-non-glass = conduction load through nonglass components of walk-in, Btu/h; and
Qcond-glass,wall = total conduction load through
walk-in glass walls and inset windows,
Btu/h.
Qcond-glass,door = total conduction load through
walk-in glass doors, Btu/h.
Anon-glass doors,l
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.052
Afloor,j = area of floor, of thickness and
underlying materials of type j;
Aceiling,k = area of ceiling, of thickness and
underlying materials of type k; and
Anon-glass door,l = area of doors, of thickness
and underlying materials of type l.
ΔTi = dry bulb temperature differential
between internal and external air, of type
i, °F
ΔTj = dry bulb temperature differential
between internal and external air, of type
j, °F
l
+ ∑ ΔTl ×
EP04JA10.051
Where:
Rnon-glass,wall, i = R-value of foam used in wall
panels, of type i, h-ft2-°F/Btu;
Rnon-glass,floor, j = R-value of foam used in floor
panels, of type j, h-ft2-°F/Btu;
Rnon-glass,ceil, k = R-value of foam used in
ceiling panels, of type k, h-ft2-°F/Btu;
Rnon-glass,door, l = R-value of foam used in nonglass doors, of type l, h-ft2-°F/Btu;
Awalls,i = area of wall, of thickness and
underlying materials of type i;
l
R non-glass,floor,j
k
+ ∑ ΔTk ×
EP04JA10.050
l
R non-glass,wall,i
Afloor , j
+ ∑ ΔTj ×
EP04JA10.049
Awalls,i
EP04JA10.048
j
i
Qcond-non-glass = ∑ ΔTi ×
Anon-glass door,l = area of doors, of thickness
and underlying materials of type l.
(b) Determine the R-value (Thermal
resistance) of the walls, ceiling, and floor
foam per 4.1, as follows:
(c) Calculate the conduction or
transmission load through all non-glass
components (Qcond-non-glass), as follows:
thickness or of two different foam
insulation products, i=2;
Awalls,i = area of walls, of thickness and
underlying materials of type i;
Afloor,j = area of floor, of thickness and
underlying materials of type j;
Aceiling,k = area of ceiling, of thickness and
underlying materials of type k; and
EP04JA10.047
Where:
i,j,k,l = number of identical surface area
regions of walls, floors, ceilings and nonglass doors, respectively, comprised of
the same thickness and underlying
materials and temperature differential—
for example, if a walk-in has wall
sections that are of two different
214
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
ν = ⎢(0.025210942) × TDB,R × (1 + (1.6078 × ω)) ⎥
⎣
⎦
(e) Calculate air density, air density (lb/ft3),
as follows:
(3-18)
(
)
h = ( 0.240 × TDB,F ) + ⎢ω × 1061 + ( 0.444 × TDB,F ) ⎥
⎣
⎦
˙
(h) Convert Vrate to V, (ft3/h), as follows:
(3-20)
Where:
3.2.2
Door Opening Infiltration Calculations
(a) Calculate the portion of time each
doorway is open, Dt, as follows:
(
)
⎢ P × θp + ( 60 × θο ) ⎥
⎦
Dt,i = ⎣
[3600 × θd ]
(3-22)
Where:
i = index for each unique door. A unique
door must be of the same geometry,
underlying materials, function, and have
(
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
qi = 795.6 × Ai × hext ,i − hint,i
Where:
i = index for each unique door
Ai = doorway area, of door type i, ft2;
hint,i = internal air enthalpy, of door type i,
Btu/lb;
hext,i = external air enthalpy, of door type i,
Btu/lb;
rint,i = internal air density, of door type i, lb/
ft3;
rext,i = external air density, of door type i, lb/
ft3;
Hi = doorway height, of door type i, ft;
Fm,i = density factor, of door type i, and
g = acceleration of gravity, 32.174 ft/s2.
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
)
3/2
Fm,i
⎡
⎤
⎢
⎥
⎢
⎥
2
=⎢
1/3 ⎥
⎢ ⎛ ρint,i ⎞ ⎥
⎢1 + ⎜
⎟ ⎥
⎜
⎟
⎢ ⎝ ρext ,i ⎠ ⎥
⎣
⎦
Frm 00030
(3-23)
Where:
i = index for each unique door
rint,i = internal air density, of door type i, lb/
ft3; and
rext,i = external air density, of door type i, lb/
ft3.
(c) Calculate the infiltration load for fully
established flow through each door, qi (Btu/
h), as follows:
1/2
⎛ ρext ,i ⎞
1/2
× ρint,i × ⎜1 −
× ( g × Hi ) × Fm,i
⎜ ρint,i ⎟
⎟
⎝
⎠
(d) Calculate the doorway infiltration
reduction device effectiveness, E (%), at the
same test conditions as described in steadystate infiltration section, as follows:
(1) A sample set must be taken once the
tracer gas has uniformly dispersed in the
internal space using the methodology
described in 4.2.
(2) The test should be repeated exactly as
described with the infiltration reduction
device removed or deactivated.
(3) Calculate the infiltration reduction
effectiveness:
PO 00000
(b) Calculate the density factor, Fm, for
each door, as follows:
Fmt 4701
Sfmt 4700
(3-24)
E=
Vrate,with-device
Vrate,without-device
(3-25)
Where:
Vrate,with-device = air infiltration rate, with door
open and reduction device active, using
4.2, 1/h;
Vrate,without-device = air infiltration rate, with
door open and reduction device disabled
or removed, using 4.2, 1/h.
(e) Calculate the total door opening
infiltration load for a single door, Qopen,
(Btu/h), as follows:
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.061
the same temperature difference across
the door
P = number of doorway passages (i.e.,
number of doors opening events);
qp = door open-close time, seconds per
opening P;
qo = time door stands open, minutes; and
qd = daily time period, h.
(1) Number of doorway passages: For
display glass doors, P = 72, and all other
doors, P= 60
(2) Door open-close time: For display glass
doors, qp = 8 seconds. For non-glass doors,
if an automatic door opener/closer is used, qp
= 10 seconds and all other doors, qp = 15
seconds.
(3) Time door stands open: Display glass
doors, qo = 0 minutes and all other doors, qo
= 15 minutes.
(4) Daily time period: All walk-ins, qd = 24
hours.
EP04JA10.057
Where:
˙
V = the infiltration rate measured from 4.2,
ft3/h;
rint = internal air density, lb/ft3;
rext = external air density, lb/ft3;
hint = internal air enthalpy, Btu/lb; and
hext = external air enthalpy, Btu/lb.
(3-21)
EP04JA10.060
)
EP04JA10.059
(
Qinfilt = ρext × hext − ρ int × hint × V
EP04JA10.058
V = Vrate × Vref -space
Vref-space = the total enclosed volume of the
walk-in, ft3
Vrate = the infiltration rate per 4.2, 1/h
(i) Calculate the total infiltration load due
to steady-state infiltration, Qinfilt, (Btu/h), as
follows:
EP04JA10.056
Where:
TDB,F = dry-bulb temperature (for the internal
or external air), °F; and
w = absolute humidity ratio.
(g) Measure the steady-state infiltration rate
per 4.2., Vrate(1/h)
(3-19)
EP04JA10.055
1
ν
EP04JA10.054
ρ=
Where:
n = specific volume of air, ft3/lb.
(f) Calculate the enthalpy for the internal
and external air, h, (Btu/lb), as follows:
EP04JA10.053
Where:
TDB,R = dry-bulb temperature (for the internal
or external air), °R, and
w = absolute humidity ratio.
(3-17)
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
Qopen ,i = qi × Dt ,i × Df × (1 − Ei ) × ni
i
(3-27)
1
3.3 Energy Consumption Due To Total Heat
Gain
(a) Calculate the total thermal load, Qtot,
(Btu/h), as follows:
(3-28)
Where:
(3-31)
components contained within the envelope,
Cload, (kWh), as follows:
l
Where:
t = index for each type of electricity
consuming device with identical rated
power;
Pcomp,int, t = the energy usage for an electricity
consuming device sited inside the walkin envelope, of type t, kWh.
Pcomp,ext, t = the energy usage for an electricity
consuming device sited outside the
walk-in envelope, of type t, kWh.
3.4.2 Total Indirect Electricity Consumption
Due to Electrical Devices
(a) Calculate the additional compressor
load due to thermal output from electrical
Where:
EER = EER of walk-in (cooler=12.4 or
freezer=6.3), Btu/Wh;
Ptot,int = The total electrical load due to
components sited inside the walk-in
envelope.
3.5
3.5.1
Total Normalized Energy Consumption
Total Energy Load
(a) Calculate the total energy load of the
walk-in envelope per unit of surface area, Etot
(kWh/ft2), as follows:
EP04JA10.070
EP04JA10.069
EP04JA10.063
l
(3-32)
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
PO 00000
Frm 00031
Fmt 4701
Sfmt 4725
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.062
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
t
Ptot ,int = ∑ P
comp,int,t
(3-30)
t
Ptot ,ext = ∑ P
comp,ext ,t
control by door open or closed position for
display doors, PTO = 99.33 percent. With
control by door open or closed position for
other doors, PTO = 99.17 percent.
(4) For all other electricity consuming
devices: Without timers, control system, or
other auto-shut-off systems, PTO = 0 percent.
If it can be demonstrated that the device is
controlled by preinstalled timers, control
system or other auto-shut-off systems, PTO =
25 percent.
(b) Calculate the power usage for each type
of electricity consuming device, Pcomp,t,
(kWh), as follows:
EP04JA10.068
(1) For lights without timers, control
system or other demand-based control, PTO
= 25 percent. For lighting with timers,
control system or other demand-based
control, PTO = 50 percent.
(2) For anti-sweat heaters on coolers (if
required): Without timers, control system or
other demand-based control, PTO = 0
percent. With timers, control system or other
demand-based control, PTO = 75 percent. For
anti-sweat heaters on freezers (if required):
Without timers, control system or other autoshut-off systems, PTO = 0 percent. With
timers, control system or other demand-based
control, PTO = 50 percent
(3) For active infiltration reduction
devices: Without control by door open or
closed position, PTO = 25 percent. With
Pcomp,t = Prated,t × (1 − PTOt ) × nt × 24
Where:
t = index for each type of electricity
consuming device with identical rated
power;
Prated,t = rated power of each component, of
type t, kW;
PTOt = percent time off, for device of type t,
%; and
nt = number of devices at the rated power of
type t.
(c) Calculate the total electrical energy
consumption, Ptot, (kWh), as follows:
(3-29)
EP04JA10.067
Q tot
24 kW
h
×
×
×
EER 1000 W day
EP04JA10.066
Qtot = Q infilt + Qopen + Qcond
Qinfilt = total load due to steady-state
infiltration, Btu/h;
Qcond = total load due to conduction, Btu/h;
and
Qopen= total load due to door opening
infiltration, Btu/h.
(b) Select Energy Efficiency Ratio (EER), as
follows:
(1) For coolers, use EER = 12.4 Btu/Wh
(2) For freezers, use EER = 6.3 Btu/Wh
(c) Calculate the total daily energy
consumption due to thermal load, Qtot,EER,
(kWh/day), as follows:
EP04JA10.065
Qopen = ∑ Qopen ,i
Q tot,EER =
Where:
Qtot = total thermal load, Btu/h; and
EER = EER of walk-in (cooler or freezer), Btu/
Wh.
3.4 Energy Consumption Related To
Electrical Components. Electrical
components contained within a walk-in
could include, but are not limited to: heater
wire (for anti-sweat or anti-freeze
application); lights (including display door
lighting systems); control system units; and
sensors.
3.4.1 Direct Energy Consumption of
Electrical Components
(a) Select the required value for percent
time off for each type of electricity
consuming device, PTOt (%)
(3-26)
EP04JA10.064
Where:
q = infiltration load for fully established
flow, Btu/h;
Dt = doorway open-time factor;
Df = doorway flow factor, 0.8 for freezers and
coolers (from ASHRAE Fundamentals);
E = effectiveness of doorway protective
device, as measured by gas tracer test, %;
and
ni = number of doors (of the type i being
considered in calculation).
(f) Calculate the total load due to door
opening infiltration for all doors, Qopen, (Btu/
h), as follows:
215
216
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
4.2
Steady State Infiltration Testing
(a) Follow the test procedure in ASTM
E741–06 exactly, except for these changes
and exceptions to the procedure,
(incorporated by reference, see § 431.303):
(1) Concentration decay method: The
‘‘concentration decay method’’ must be used
instead of other available options described
in ASTM E741–06.
(2) Gas Tracer: CO2 must be used as the gas
tracer for all testing.
(3) Air change rate: Measure the air change
rate in ft3/h, rather than the air change flow
described in ASTM E741–06, (incorporated
by reference, see § 431.303).
(4) Spatial measurements: Spatial
measurements must be taken in a minimum
of six locations or one location/20 ft2 of floor
area (whichever results in a greater number
of measurements) at a height of 3 ft ± 0.5 ft,
at a minimum distance of 2 ft ± 0.5 ft from
the walk-in walls or doors.
(b) The internal air temperature for freezers
and for coolers shall be ± 2 °C (4 °F) of the
values shown in Table A.1.
(c) The external air temperature must be
24 °C (75 °F) ± 2.5 °C (5 °F) surrounding the
walk-in.
Etot,system = DECCnon-glass × Anon-glass,tot + DECCglass × Aglass, tot + DECCinfilt,disp_dr_opn ×
Adisp_doors + DECCdisp_dr_device × ndisp_doors + DECCinfilt,non-display,dr_opn × Anon-display-doors +
Eq. 5-1
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
DECCnon-display-dr_device × nnon-display-doors + DECClight × Vref_space + DECCASH × Adisp_doors +
DECCstir_fan × Vref_space + DECCother × Vref_space
Where:
DECCnon-glass = DECC for non-glass,
Anon-glass,tot = total non-glass surface area,
DECCglass,door = DECC for glass doors,
Aglass,glass, tot = total glass surface area, and
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
DECCglass,wall = DECC for glass walls and
inset windows,
Aglass,wall, tot = total glass wall and inset
window surface area, and
DECCinfilt,disp_dr_opn = DECC for opening of
display type doors,
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
Adisp_doors = total area of display doors,
DECCdisp_dr_device = DECC for infiltration
reduction device in place for display doors,
ndisp_doors = total number of display doors,
DECCinfilt,non-display_,dr_opn = DECC for nondisplay type doors,
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.074
R-Value Testing and Measurements
4.1.1 Measuring R-Value of Insulating Foam
(a) Follow the test procedure in ASTM
C1303–08 exactly, except for these
exceptions, (incorporated by reference, see
§ 431.303):
(1) Section 6.6.2, where several types of hot
plate methods are recommended, ASTM
C518–04, (incorporated by reference, see
§ 431.303), must be used for measuring the
R-value
(2) Section 6.6.2.1, in reference to ASTM
C518–04, the mean test temperature of the
foam during R-value measurement must be:
(i) For freezers: ¥ 6.7 ± 2 °C (20 ± 4 °F)
with a temperature difference of 22 ± 2 °C (40
± 4 °F)
(ii) For coolers: 12.8 ± 2 °C (55 ± 4 °F) with
a temperature difference of 22 ± 2 °C (40 ±
4 °F)
(b) At least one sample set must be
prepared, comprised of three stacks, while
adhering to all preparation methods and
uniformity specifications described in ASTM
C1303–08, (incorporated by reference, see
§ 431.303).
(c) The value resulting LTTR for the foam
shall be reported as Rfoam, but for the
purposes of calculations in this test
procedure calculations, it will be converted
to Rnon-glass, as follows:
(a) For walk-ins in which the floor is
concrete instead of insulated panels and has
not been supplied by the walk-in
manufacturer:
(1) Coolers: Use an R-value of 0.6 for floors
of walk-in coolers.
(2) Freezers: Use an R-value of 28 for floors
of walk-in freezers.
EP04JA10.073
4.1.2 Determining R-Value of Concrete
Floors
EP04JA10.072
4.1
Where:
Rfoam = R-value of foam as measured by
ASTM C1303–08, h-ft2¥°F/Btu-in.
(d) The test must be completed with all
reach or walk-in doors closed.
(e) For testing the effectiveness ASTM
E741–06 will be used, with the following
changes or exceptions to the procedure:
(1) Within 3 minutes ± 30 seconds, with
the infiltration reduction device in place, a
hinged door should be opened at an angle
greater than or equal to 90 degrees. The
elapsed time, from zero degrees position
(closed) to greater than or equal to 90 degrees
(open) must be no longer than 5 seconds. The
door must then be held at an angle greater
than or equal to 90 degrees for 5 min ±5
seconds and then closed over a period no
longer than 5 seconds. For non-hinged doors,
the door must reach its maximum opened
position, be held open, and reach a fully
closed position for the same elapsed time as
described above for hinge-type doors.
(2) The gas concentration must be sampled
again after the door has been closed. Samples
should continue being taken until the gas
concentration is once again uniform within
the walk-in.
5.0 Calculation of Daily Energy
Consumption Coefficients (DECC)
The calculation procedures described in
this section are based on the test
measurements and other performance
parameters discussed and described in the
previous sections. The Daily Energy
Consumption Coefficients are each combined
to provide a linear expression of the daily
energy consumption of any walk-in system
with the construction features or component
design parameters of a tested walk-in design
with similar components and features. The
DECC figures established using
measurements on the test unit may be used
to derive the daily electrical energy
consumption of other walk-in systems in the
same class constructed with similar
components of construction as follows:
EP04JA10.071
Where:
Qtot,EER = the total thermal load, kWh;
Ptot = the total electrical load, kWh;
Anon-glass,tot = total surface area of the nonglass envelope, ft2;
Aglass,tot = total surface area glass envelope,
ft2.
Cload = additional compressor load due to
thermal output from electrical
components contained within the
envelope, kWh.
4.0 Test Methods and Measurements
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
217
nnon-display_doors = total number of nondisplay doors,
DECClight = DECC for lights,
Vref_space = total enclosed refrigerated
volume (ft3),
DECCASH = DECC for anti-sweat heaters,
DECCstir_fan = DECC for motors used to
drive air mixing fans, and
DECCother = DECC for other electricity
consuming devices.
(a) Calculate DECCnon-glass as follows:
Where:
Qcond,non-glass = conduction load due to nonglass surface area,
Qcond,glass,wall = conduction load due to glass
wall and inset window surface area,
Qcond,glass,door = conduction load due to glass
door surface area,
Qinfilt = load due to steady-state infiltration,
Anon-glass,tot = total non-glass surface area,
Aglass,wall,tot = total glass wall and inset
window surface area,
Aglass,door,tot = total glass door surface area,
EER = energy efficiency ratio for freezer or
cooler, as described 3.3(b)
(b) Calculate DECCglass,door as follows:
Where:
Qcond,non-glass = conduction load due to nonglass surface area,
Qcond,glass,wall = conduction load due to glass
wall and inset window surface area,
Qcond,glass,door = conduction load due to glass
door surface area,
Qinfilt = load due to steady-state infiltration,
Anon-glass,tot = total non-glass surface area,
Aglass,wall,tot = total glass wall and inset
window surface area,
Aglass,door,tot = total glass door surface area,
EER = energy efficiency ratio for freezer or
cooler, as described 3.3(b)
(c) Calculate DECCglass,wall as follows:
Where:
Qcond,non-glass = conduction load due to nonglass surface area,
Qcond,glass,wall = conduction load due to glass
wall and inset window surface area,
Qcond,glass,door = conduction load due to glass
door surface area,
Qinfilt = load due to steady-state infiltration,
Anon-glass,tot = total non-glass surface area,
Aglass,wall,tot = total glass wall and inset
window surface area,
Aglass,door,tot = total glass door surface area,
EER = energy efficiency ratio for freezer or
cooler, as described 3.3(b)
20:56 Dec 31, 2009
Jkt 220001
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.076
EP04JA10.077
VerDate Nov<24>2008
EP04JA10.075
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
EP04JA10.078
EP04JA10.079
EP04JA10.080
EP04JA10.081
EP04JA10.082
EP04JA10.083
Anon-display_doors = total area of non-display
type doors,
DECCnon-display_dr_device = DECC for
infiltration reduction device in place for nondisplay doors,
218
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 / Proposed Rules
(d) Compute DECCglass in an identical
manner to DECCglass,door, described above.
(e) Compute DECCinfilt,disp_dr_opn and
DECCdisp_dr_device as follows:
Where:
Qopen,disp_dr = total infiltration load calculated
for display door-opening events, and
EER = energy efficiency ratio for freezer or
cooler
(f) Determine DECCdisp_dr_device as follows:
(1) For passive infiltration reduction
devices (e.g., strip curtains), the
DECCdisp_dr_device is zero.
(2) For active infiltration reduction devices
(e.g., air curtains), DECCdisp_dr_device = Pcomp
where Pcomp is determined as in section 3.4.1
using the appropriate PTO (percent time off)
(g) Compute DECCinfilt, non-display_dr_opn and
DECC non-display_dr_device in the same manner as
DECCinfilt, disp_dr_opn and DECCdisp_dr_device
above.
(h) Compute DECCASH in the following
manner:
Where:
Pcomp,ASH = total energy consumed by antisweat heaters (per section 3.4.1), and
Adisp-door = total surface area of display doors.
(i) Compute DECCstir_fan, for stirring (nonevaporator) fans in the following manner:
Where:
Vref_space = total volume of the refrigerated
space (ft 3), and
Pcomp,stirring_fan = total energy consumed by
stir fan(s) (per 3.4.1).
(j) Compute DECCother for all other
electricity consuming devices: For all lights
and other electrical loads, Pcomp,j is
determined per the provisions of the section
3.4.1 and the DECCother is obtained by
dividing the respective Pcomp,j by Vref_spac.
[FR Doc. E9–30884 Filed 12–31–09; 8:45 am]
EP04JA10.086
EP04JA10.085
VerDate Nov<24>2008
20:56 Dec 31, 2009
Jkt 220001
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
E:\FR\FM\04JAP2.SGM
04JAP2
EP04JA10.084
mstockstill on DSKH9S0YB1PROD with PROPOSALS2
EP04JA10.087
BILLING CODE 6450–01–P
Agencies
[Federal Register Volume 75, Number 1 (Monday, January 4, 2010)]
[Proposed Rules]
[Pages 186-218]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: E9-30884]
[[Page 185]]
-----------------------------------------------------------------------
Part II
Department of Energy
-----------------------------------------------------------------------
10 CFR Part 431
Energy Conservation Program: Test Procedures for Walk-In Coolers and
Walk-In Freezers; Proposed Rule
Federal Register / Vol. 75, No. 1 / Monday, January 4, 2010 /
Proposed Rules
[[Page 186]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Part 431
[Docket No. EERE-2008-BT-TP-0014]
RIN 1904-AB85
Energy Conservation Program: Test Procedures for Walk-In Coolers
and Walk-In Freezers
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Notice of proposed rulemaking and public meeting.
-----------------------------------------------------------------------
SUMMARY: Pursuant to the Energy Policy and Conservation Act, as
amended, the U.S. Department of Energy (DOE) is proposing test
procedures for measuring the energy consumption of walk-in coolers and
walk-in freezers (collectively ``walk-in equipment'' or ``walk-
in(s)''), definitions to delineate the products covered by the test
procedures, and provisions (including a sampling plan) for
manufacturers to implement the test procedures. The notice also
addresses enforcement issues as they relate to walk-in equipment.
Concurrently, DOE is undertaking an energy conservation standards
rulemaking for this equipment. Any data gathered through the use of the
test procedure adopted by DOE will be used in evaluating any potential
standards for this equipment. Once these standards are promulgated, the
adopted test procedures will be used to determine equipment efficiency
and compliance with the standards.
DATES: DOE will hold a public meeting in Washington, DC on Thursday,
February 11, 2010, beginning at 9 a.m. DOE must receive requests to
speak at the meeting before 4 p.m., Thursday, January 28, 2010. DOE
must receive a signed original and an electronic copy of statements to
be given at the public meeting before 4 p.m., Thursday, January 28,
2010.
DOE will accept comments, data, and information regarding this
notice of proposed rulemaking (NOPR) before or after the public
meeting, but no later than March 22, 2010. See section V, ``Public
Participation,'' of this NOPR for details.
ADDRESSES: The public meeting will be held at the U.S. Department of
Energy, Forrestal Building, Room 8E-089, 1000 Independence Avenue, SW.,
Washington, DC 20585-0121. To attend the public meeting, please notify
Ms. Brenda Edwards at (202) 586-2945. Please note that foreign
nationals participating in the public meeting are subject to advance
security screening procedures, requiring a 30-day advance notice. If
you are a foreign national and wish to participate in the public
meeting, please inform DOE as soon as possible by contacting Ms. Brenda
Edwards at (202) 586-2945 so that the necessary procedures can be
completed.
Any comments submitted must identify the NOPR for Test Procedures
for Walk-in Coolers and Freezers, and provide docket number EERE-2008-
BT-TP-0014 and/or Regulation Identifier Number (RIN) 1904-AB85.
Comments may be submitted using any of the following methods:
1. Federal eRulemaking Portal: https://www.regulations.gov. Follow
the instructions for submitting comments.
2. E-mail: WICF-2008-TP-0014@hq.doe.gov. Include the docket number
EERE-2008-BT-TP-0014 and/or RIN 1904-AB85 in the subject line of the
message.
3. Postal Mail: Ms. Brenda Edwards, U.S. Department of Energy,
Building Technologies Program, Mailstop EE-2J, 1000 Independence
Avenue, SW., Washington, DC 20585-0121. Please submit one signed
original paper copy.
4. Hand Delivery/Courier: Ms. Brenda Edwards, U.S. Department of
Energy, Building Technologies Program, 950 L'Enfant Plaza, SW., 6th
Floor, Washington, DC 20024. Please submit one signed original paper
copy.
For detailed instructions on submitting comments and additional
information on the rulemaking process, see section V, ``Public
Participation,'' of this document.
Docket: For access to the docket to read background documents or
comments received, visit the U.S. Department of Energy, Resource Room
of the Building Technologies Program, 950 L'Enfant Plaza, SW., 6th
Floor, Washington, DC 20024, (202) 586-2945, between 9 a.m. and 4 p.m.
Monday through Friday, except Federal holidays. Please call Ms. Brenda
Edwards at the above telephone number for additional information
regarding visiting the Resource Room.
FOR FURTHER INFORMATION CONTACT: Mr. Charles Llenza, U.S. Department of
Energy, Building Technologies Program, EE-2J, 1000 Independence Avenue,
SW., Washington, DC 20585-0121, (202) 586-2192,
Charles.Llenza@ee.doe.gov or Mr. Michael Kido, Esq., U.S. Department of
Energy, Office of General Counsel, GC-72, 1000 Independence Avenue,
SW., Washington, DC 20585- 0121, (202) 586-8145,
Michael.Kido@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
Table of Contents
I. Authority and Background
II. Summary of the Proposal
III. Discussion
A. Overall Approach
1. Basic Model
2. Approach Option 1: Test the Unit as a Whole
3. Approach Option 2: Allow Manufacturers To Use Alternative
Energy Determination Methods (AEDMs)
4. Proposed Option and Recommendation: Separate Envelope and
Refrigeration Tests
B. Envelope
1. Overview of the Test Procedure
2. Test Methods
a. Insulation
b. Air Infiltration
c. Steady-State Infiltration Test
3. Calculations
a. Energy Efficiency Ratio
b. Heat Gain Through the Envelope Due to Conduction
c. Heat Gain Due to Infiltration
d. Envelope Component Electrical Loads
e. Normalization
f. Daily Energy Consumption Coefficients
C. Refrigeration System
1. Overview of the Test Procedure
2. Test Conditions
3. Test Methods
4. Measurements and Calculations
D. Compliance, Certification, and Enforcement
1. Provisions for Energy Conservation Standards Developed by the
Department of Energy
2. Provisions for Existing Design Standards Prescribed by
Congress
IV. Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the National Environmental Policy Act
C. Review Under the Regulatory Flexibility Act
D. Review Under the Paperwork Reduction Act
E. Review Under the Unfunded Mandates Reform Act of 1995
F. Review Under the Treasury and General Government
Appropriations Act, 1999
G. Review Under Executive Order 13132
H. Review Under Executive Order 12988
I. Review Under the Treasury and General Government
Appropriations Act, 2001
J. Review Under Executive Order 13211
K. Review Under Executive Order 12630
L. Review Under Section 32 of the Federal Energy Administration
(FEA) Act of 1974
V. Public Participation
A. Attendance at Public Meeting
B. Procedure for Submitting Requests to Speak
C. Conduct of Public Meeting
D. Submission of Comments
E. Issues on Which DOE Seeks Comment
1. Test Procedure Improvements
2. Basic Model
3. Separate Envelope and Refrigeration Tests
4. Definition of Envelope
5. Effect of Impermeable Skins on Long-Term R Value
6. Measuring Long-Term R Value Using American Society for
Testing and Materials (ASTM) C1303-08
7. Infiltration
[[Page 187]]
8. Nominal Coefficient of Performance of Refrigeration
9. Measuring the U Value of glass
10. Floor R Value
11. Electrical Duty Cycle
12. Normalization Factor
13. Daily Energy Consumption Coefficients
14. Definition of Refrigeration System
15. Measurements and Calculations of Energy Use of Refrigeration
Systems
16. Impacts on Small Businesses
VI. Approval of the Office of the Secretary
I. Authority and Background
Title III of the Energy Policy and Conservation Act of 1975, as
amended (EPCA or the Act) sets forth a variety of provisions designed
to improve energy efficiency. Part B of Title III (42 U.S.C. 6291-6309)
provides for the Energy Conservation Program for Consumer Products
Other Than Automobiles. The National Energy Conservation Policy Act
(NECPA), Public Law 95-619, amended EPCA to add Part C of Title III,
which established an energy conservation program for certain industrial
equipment. (42 U.S.C. 6311-6317) (These parts were subsequently
redesignated as Parts A and A-1, respectively, for editorial reasons.)
Section 312 of the Energy Independence and Security Act of 2007 (EISA
2007) further amended EPCA by adding certain equipment to this energy
conservation program, including walk-in coolers and walk-in freezers
(collectively ``walk-in equipment'' or ``walk-ins''), the subject of
this rulemaking. (42 U.S.C. 6311(1), (2), 6313(f) and 6314(a)(9))
EPCA defines walk-in equipment as follows:
(A) In general.--
The terms ``walk-in cooler'' and ``walk-in freezer'' mean an
enclosed storage space refrigerated to temperatures, respectively,
above, and at or below 32 degrees Fahrenheit that can be walked into,
and has a total chilled storage area of less than 3,000 square feet.
(B) Exclusion.--
The terms ``walk-in cooler'' and ``walk-in freezer'' do not include
products designed and marketed exclusively for medical, scientific, or
research purposes. (42 U.S.C. 6311(20))
Walk-ins covered by this rulemaking may be located indoors or
outdoors. They may be used exclusively for storage, but they may also
have transparent doors or panels for the purpose of displaying stored
items. Examples of items that may be stored in walk-ins include, but
are not limited to, food, beverages, and flowers. DOE notes that any
equipment that meets the above definition is potentially subject to
regulation.
Under the Act, the overall program consists essentially of the
following parts: testing, labeling, and Federal energy conservation
standards. The testing requirements for covered equipment consist of
test procedures, prescribed under EPCA. These test procedures are used
in several different ways: (1) Any data from the use of these
procedures are used as a basis in developing standards for covered
products or equipment; (2) the test procedure is used when determining
equipment compliance with those standards; and (3) manufacturers of
covered equipment must use the procedure to establish that their
equipment complies with energy conservation standards promulgated
pursuant to EPCA and when making representations about equipment
efficiency.
Section 343 of EPCA (42 U.S.C. 6314) sets forth generally
applicable criteria and procedures for DOE's adoption and amendment of
such test procedures. That provision requires that the test procedures
promulgated by DOE be reasonably designed to produce test results which
reflect energy efficiency, energy use, and estimated operating costs of
the covered equipment during a representative average use cycle. It
also requires that the test procedure not be unduly burdensome to
conduct. See 42 U.S.C. 6314(a)(2). As part of the process for
promulgating a test procedure, DOE must publish the procedure that it
plans to propose and offer the public an opportunity to present oral
and written comments on them. Consistent with Executive Order 12889 and
EPCA (see 42 U.S.C. 6314(b)), DOE provides a minimum comment period of
75 days on a proposed test procedure. As to the test procedures for
walk-in equipment, EPCA prescribes the following requirements:
(A) In general.--
For the purpose of test procedures for walk-in coolers and walk-in
freezers:
(i) The R value shall be the 1/K factor multiplied by the thickness
of the panel.
(ii) The K factor shall be based on ASTM [American Society for
Testing and Materials] test procedure C518-2004.
(iii) For calculating the R value for freezers, the K factor of the
foam at 20 [deg]F (average foam temperature) shall be used.
(iv) For calculating the R value for coolers, the K factor of the
foam at 55 [deg]F (average foam temperature) shall be used.
(B) Test Procedure.--
(i) In general.--Not later than January 1, 2010, the Secretary
shall establish a test procedure to measure the energy-use of walk-in
coolers and walk-in freezers.
(ii) Computer modeling.--The test procedure may be based on
computer modeling, if the computer model or models have been verified
using the results of laboratory tests on a significant sample of walk-
in coolers and walk-in freezers. (42 U.S.C. 6314(a)(9))
On February 4, 2009, DOE held a public meeting on the framework
document it issued concerning the DOE rulemaking to evaluate walk-in
equipment for energy conservation standards. See 74 FR 411 (Jan. 6,
2009) and 74 FR 1992 (Jan. 14, 2009). Both the framework document and
meeting discussed the possible test procedures for this equipment that
DOE was considering at that time, and gave interested parties an
opportunity to submit comments. Today's notice addresses those comments
and proposes test procedures for walk-in equipment.
II. Summary of the Proposal
In today's notice, DOE proposes to adopt new test procedures for
determining the energy use of walk-in cooler and walk-in freezer
equipment to address the statutory requirement to establish a test
procedure by January 1, 2010. (42 U.S.C. 6314(a)(9)(B)) Concurrently,
DOE is undertaking an energy conservation standards rulemaking for
walk-in equipment to address the statutory requirement to establish
performance standards no later than January 1, 2012. (42 U.S.C.
6313(f)(4)(A)) DOE will use any data resulting from use of the test
procedure that DOE adopts to evaluate potential performance standards
for this equipment. Furthermore, once performance standards are issued,
manufacturers would be required to use the test procedures to determine
compliance with such standards and for any representations regarding
the energy use of walk-in equipment they produce. This test procedure,
once adopted, would serve as the means for ascertaining compliance with
the appropriate standards in an enforcement action.
For the reasons described below, DOE proposes to adopt a test
procedure that contains two separate test methods. This approach is
necessary because there are typically two manufacturers of walk-in
equipment: One who manufactures the envelope (i.e., the insulated box
in which the refrigerated or frozen items are stored) and one who
manufactures the refrigeration system (i.e., the mechanism that
provides the means by which to feed chilled air into the envelope). One
method determines the
[[Page 188]]
energy consumption of the refrigeration system of the walk-in cooler or
freezer. The other method determines the energy consumption of the
envelope, which is the sum of the energy use associated with heat
transmission through the envelope in the form of conduction through the
walls and air infiltration through openings, and the power consumed by
electrical components that are part of the envelope. Each of the two
components, the refrigeration system and the envelope, is considered
separately and the energy consumption of each component is calculated
using the applicable test procedure. DOE believes that the approach is
consistent with the requirements in EPCA because the results of the two
tests will represent, in the aggregate, the total energy consumption of
walk-in coolers and freezers.
Using this approach, DOE believes that the proposed test procedures
will adequately measure the energy consumption of walk-in equipment by
capturing the energy consumption of both components. However, DOE
requests comment from stakeholders on improvements or changes to the
proposed test procedures and will consider modifications that improve
the accuracy, appropriateness for the equipment being tested,
repeatability of test results for the same or similar units,
comparability of results for different types of units, burden on
manufacturers, precision of language, or other elements of the
procedures. In submitting comments, interested parties should state the
nature of the recommended modification and explain how it would improve
upon the test procedure proposed in this NOPR. Commenters should also
submit data, if any, to support their positions.
DOE's adoption of the proposed test procedures, which would be
applicable to all walk-in equipment, would not necessarily mean that
DOE would adopt a single energy conservation standard or set of
labeling requirements for all walk-in equipment. In the separate
rulemaking proceeding concerning energy conservation standards for
walk-in equipment, DOE may divide such equipment into classes and may
conclude that standards are not warranted for some classes of equipment
that are within the scope of today's test procedure. Furthermore, DOE
may create a separate standard for each class of equipment that
includes a utility- or performance-related feature that another
equipment class lacks, and that affects energy consumption.
DOE also notes that the National Technology Transfer and
Advancement Act of 1995 (Pub. L. 104-113) directs Federal agencies to
use voluntary consensus standards in lieu of Government standards
whenever possible. Consequently, as described in the following
paragraphs, DOE attempted to incorporate by reference in its test
procedures generally accepted rules or recognized industry standards
such as those issued by the Air-Conditioning, Heating and Refrigeration
Institute (AHRI), the American Society of Heating, Refrigerating, and
Air Conditioning Engineers (ASHRAE), the American National Standards
Institute (ANSI), and/or ASTM International (ASTM), that provide either
specific aspect(s) of the test procedure, or the complete test
procedure, for the specified equipment.
III. Discussion
In the following section, DOE describes the overall approach it
proposes to follow with respect to the adoption of a test procedure for
walk-ins. This approach results from the characteristics of walk-in
equipment and is based in part on the basic model definition that DOE
currently uses to help establish testing requirements for manufacturers
to follow. The following section also addresses issues raised by
commenters, which included: Manufacturers (Craig Industries (Craig),
Manitowoc, Nor-Lake); trade associations (AHRI); utility companies
(Southern California Edison (SCE), Sacramento Municipal Utility
District (SMUD), San Diego Gas and Electric (SDG&E)); and advocacy
groups (Appliance Standards Awareness Project (ASAP), American Council
for an Energy-Efficient Economy (ACEEE), Natural Resources Defense
Council (NRDC), Northwest Energy Efficiency Alliance (NEEA)).
A. Overall Approach
DOE developed today's proposed test procedure to set forth the
testing requirements for walk-in equipment. In the framework document,
DOE considered two overall approaches manufacturers could take to
determine the energy consumption of walk-in coolers and freezers.
First, DOE considered using a modified version of the Air-Conditioning
and Refrigeration Institute (ARI) Standard 1200-2006, ``Performance
Rating of Commercial Refrigerated Display Merchandisers and Storage
Cabinets'' (ARI 1200-2006), which uses the test method described in the
American National Standards Institute/American Society of Heating,
Refrigerating, and Air Conditioning Engineers (ANSI/ASHRAE) Standard
72-2005, ``Method of Testing Commercial Refrigerators and Freezers''
(ANSI/ASHRAE 72-2005). Second, DOE considered allowing manufacturers to
determine the efficiency of some of their products using alternative
efficiency determination methods (AEDMs). (An AEDM is a predictive
mathematical model, developed from engineering analyses of design data
and substantiated by actual test data, which represents the energy
consumption characteristics of one or more basic models.)
DOE received comments on these proposed approaches, many of which
were opposed to both approaches. The comments DOE received, and DOE's
responses, are discussed in more detail below. After considering these
comments and reviewing the matter further, DOE is proposing separate
test procedures for the envelope (insulated box) and the refrigeration
system. DOE discusses the details of its proposals and addresses
manufacturer comments in the following subsections.
1. Basic Model
Under EPCA, which prohibits the distribution in commerce of covered
equipment that do not comply with the applicable standard, each model
of covered equipment is potentially subject to energy efficiency
testing consistent with the relevant requirements for that equipment.
However, walk-in manufacturers typically make numerous envelope models
and, even within a single model, the units are often customized in
multiple ways. To reduce this potential burden, DOE proposes following
the approach it has used for other equipment by allowing manufacturers
to group equipment or models with essentially identical energy
consumption characteristics into a single family of models, called a
basic model. This concept has been established both for residential
appliances and commercial and industrial equipment covered under EPCA.
(See Title 10 of the Code of Federal Regulations (10 CFR) 430.2, which
covers 26 products, and 10 CFR 431.12, 431.62, 431.132, 431.172,
431.192, 431.202, 431.222, 431.262, and 431.292, which cover various
equipment.)
Walk-in refrigeration systems are often manufactured according to
the same basic blueprint design, and any particular model could
incorporate modifications that do not significantly affect the energy
efficiency of the system. For example, manufacturers often sell systems
that are designed to operate at different voltages. This allows them to
market to customers with different electrical capabilities. The
operating voltage affects the energy
[[Page 189]]
efficiency of the system, but very minimally. If manufacturers were
required to test the efficiency of each model with a different feature,
the testing burden would be significant, but yield effectively
redundant results. Therefore, DOE provides for testing of a basic model
of refrigeration systems that may not be identical, but would not have
any electrical, physical, or functional characteristics that
significantly affect energy consumption. Features that may affect the
energy consumption of walk-in cooler and freezer refrigeration systems
include compressor size, fan motor type, and heat exchanger coil
dimensions.
Walk-in envelopes are often manufactured according to the same
basic design, but the equipment is so highly customized that each walk-
in a manufacturer builds may be unique, and potentially subject to
testing as a separate basic model. For instance, changing the size of
the envelope would affect the energy consumption obtained by the test
procedure, even if the construction methods and materials were the
same. To address this possibility, DOE proposes (1) grouping walk-in
envelopes with essentially identical construction methods, materials,
and components into a single basic model, and (2) adopting a
calculation methodology for determining the energy consumption of units
within the basic model. This methodology would require a manufacturer
to test one unit of the basic model and then calculate daily energy
consumption coefficients (DECCs) for that basic model according to the
test procedure. The manufacturer could then apply those DECCs to other
units within a basic model even if those units were not identical, to
obtain the energy consumption of those units. Although units within a
basic model need not share identical dimensions, finishes, and non-
energy-related features (e.g., shelving or door kick plates), they must
have been manufactured using substantially the same construction
methods, materials, and components. A few examples of factors that
would necessitate a different basic model include changing the type of
insulating foam, the method of locking together the panels of the walk-
in envelope, or the electrical characteristics of the lighting.
Examples of factors that may not constitute a different basic model
include the type of exterior metal finish, the dimensions of the
envelope, and the number of doors of the same type. The exterior metal
finish would not have a substantial impact on the efficiency of the
envelope. Dimensions and number of doors, on the other hand, would be
accounted for in the energy consumption calculation using the DECCs
from the unit of the basic model that was tested. (See section
III.B.3.f for further discussion of DECCs.)
All of the equipment included in a basic model must be within the
same equipment class. Components of similar design may be substituted
in a basic model without requiring additional testing if the
represented energy consumption measurements continue to satisfy the
provisions for sampling and testing. Only representative samples within
each basic model would be tested.
For walk-ins, DOE is considering adopting the following definition
of ``basic model:'' ``Basic Model means all units of a given type of
walk-in equipment manufactured by a single manufacturer, and--(1) With
respect to envelopes, which do not have any differing construction
methods, materials, components, or other characteristics that
significantly affect the energy consumption characteristics. (2) With
respect to refrigeration systems, which have the same primary energy
source and which do not have any differing electrical, physical, or
functional characteristics that significantly affect energy
consumption.'' DOE requests comment on its proposed basic model
approach.
2. Approach Option 1: Test the Unit as a Whole
In the framework document, DOE considered developing a test
procedure for walk-ins by adapting an existing test procedure for
commercial refrigeration equipment, such as ARI 1200-2006. This
approach would require an entire walk-in cooler or freezer to be
physically tested within a controlled test chamber in order to evaluate
its energy consumption over a period of time. During the standards
framework public meeting, DOE requested comments on the feasibility of
this approach. Interested parties responded with significant
reservations about using a modified version of the ARI 1200-2006 test
procedure, citing crucial differences between walk-ins and commercial
refrigeration equipment.
In particular, interested parties noted that walk-ins are
physically different from commercial refrigerators in ways that make a
full-system test burdensome or impractical. Manitowoc stated that for
very large walk-ins, around the 3,000-square-foot limit in the EPCA
definition, manufacturers might not have a large enough test facility
to make the measurements necessary for the ARI 1200-2006 test procedure
in a controlled environment. (Manitowoc, Public Meeting Transcript, No.
15 at p. 59) (In this and subsequent citations, ``Public Meeting
Transcript'' refers to the transcript of the February 4, 2009, public
meeting on standards for walk-in coolers and freezers. ``No. 15''
refers to the document number of the transcript in the Docket for the
DOE rulemaking on standards for walk-in coolers and freezers, Docket
No. EERE-2008-BT-TP-0014; and the page references refer to the place in
the transcript where the statement preceding appears.) Kason Industries
also stated that it would be practically impossible to have a large
enough controlled climate enclosure to test medium to large walk-ins,
and added that if a walk-in were a free-standing structure, testing it
as a whole building would not be practical. (Kason, No. 16 at pp. 1, 4)
(In this and subsequent citations, the document number refers to the
number of the comment in the Docket for the DOE rulemaking on standards
for walk-in coolers and freezers, Docket No. EERE-2008-BT-TP-0014; and
the page references refer to the place in the document where the
statement preceding appears.) The Air-Conditioning, Heating, and
Refrigeration Institute (AHRI) stated that the proposed test procedures
were not practical because it would be costly to physically test walk-
ins. (AHRI, No. 33 at p. 2)
Commenters also noted that the market for walk-in coolers and
freezers is structured differently from the market for commercial
refrigeration equipment, making a direct comparison between these types
of equipment difficult. Manitowoc stated that the envelope of a
particular unit of walk-in equipment may be manufactured by one company
and the refrigeration system by another company. ARI 1200-2006 would
require the two systems to be integrated before running the test, which
would place the burden on the installer or someone beyond the
manufacturer of the subsystems. (Manitowoc, Public Meeting Transcript,
No. 15 at p. 59) AHRI agreed that the ARI 1200-2006 standard might not
be the right approach and that DOE would need to separate the
mechanical system from the envelope. (AHRI, Public Meeting Transcript,
No. 15 at p. 62)
In addition to these concerns, commenters identified a deficiency
in the ARI 1200-2006 test procedure. SCE stated that the majority of
potential energy savings can be achieved using floating head pressure
and variable-speed evaporator fans, both of which have varying effects
depending on the time of day and the regional climate
[[Page 190]]
because the savings associated with each feature can depend on the
ambient temperature and usage patterns of the walk-in over the course
of a day. Because ARI 1200-2006 is a steady-state test, it would not
capture the energy savings from either option. (SCE, Public Meeting
Transcript, No. 15 at p. 63) AHRI agreed that the test procedure should
capture savings from a control strategy or variable-speed components,
both of which could optimize the operation of the walk-in for a variety
of ambient conditions and usage patterns. An example of optimization
would be allowing elements of the refrigeration system to turn off or
reduce their operation at night when the walk-in is not being accessed.
(AHRI, No. 33 at p. 2)
After considering these comments, DOE believes that an adapted
version of ARI 1200-2006 would be inadequate to use as the test
procedure for walk-in equipment. ARI 1200-2006 contains too many
limitations and practical difficulties that would make it very
difficult to effectively implement as a workable test procedure for
walk-in. Therefore, DOE is no longer considering this approach.
3. Approach Option 2: Allow Manufacturers To Use Alternative Energy
Determination Methods (AEDMs)
DOE's framework document also presented an alternative that would
permit the use of an AEDM when determining walk-in energy consumption
to help relieve the testing burden on manufacturers. An AEDM is a
predictive mathematical model, developed from engineering analyses of
design data and substantiated by actual test data which represents the
energy consumption characteristics of one or more basic models. After
confirming the accuracy of an AEDM, the manufacturer would apply the
AEDM to basic models to determine their energy consumption without
conducting any physical testing.
Applying this approach, the manufacturer would confirm the accuracy
of the AEDM using the following method. First, the manufacturer would
determine through actual testing the energy consumption of a certain
number of its basic models that would be selected in accordance with
criteria specified in the procedure. Second, the manufacturer would
apply the AEDM to these same basic models. The AEDM would be considered
sufficiently accurate only if: (1) The predicted total energy
consumption of each of these basic models, calculated by applying the
AEDM, is within a certain percentage of the total energy consumption
determined from the testing of that basic model; and (2) the average of
the predicted total energy consumption for the tested basic models,
calculated by applying the AEDM, is within a certain percent of the
average of the total energy consumption determined from testing these
basic models. Under this approach, once the manufacturer verifies the
accuracy of the AEDM, the manufacturer can use the AEDM to determine
the energy consumption of other basic models without having to test
those models. DOE requested comments on this approach during the
framework public meeting, both in terms of how to implement the
approach and whether such an approach was valid for walk-ins at all.
DOE received several relevant comments, which are described and
addressed below.
Given the unprecedented nature of using an AEDM to rate this type
of equipment, DOE needed to determine both an appropriate sample size
for verifying an AEDM and an acceptable minimum accuracy percentage for
an AEDM. During the framework public meeting, DOE requested comments on
these two values. AHRI could not provide feedback on how accurate the
AEDM should be because DOE had not yet determined the test metric to
apply. (AHRI, Public Meeting Transcript, No. 15 at p. 69) Manitowoc
agreed that the test methodology needs to be established and
experiments conducted to collect data that would be used to validate
AEDMs. (Manitowoc, Public Meeting Transcript, No. 15 at p. 70) In a
written comment, Kason Industries stated that an AEDM with a minimum
accuracy of 66 percent would encompass a majority of the wide range of
walk-in cooler and freezer applications. (Kason, No. 16 at p. 2) No
commenter provided substantive data that DOE would use in its analysis
to help support a particular sample size. Accordingly, DOE did not
receive enough data from stakeholders that could help it determine an
appropriate sample size or accuracy range to substantiate an AEDM.
During the public meeting, DOE also requested comments on the
possibility of allowing manufacturers to take this approach to rate
their walk-ins. Kason stated that an AEDM procedure would be preferable
to using a physical test because the majority of walk-ins are custom-
made by size, ambient temperature, and refrigeration demands.
Therefore, it would be very difficult to create a test procedure that
encompasses the range of walk-in equipment. (Kason, No. 16 at p. 1)
Kason suggested that, as an alternative to testing the system as a
whole, an AEDM could be based on determining efficiencies and
performance characteristics for the principal components of a walk-in
considering three factors: insulation and air tightness of the external
envelope and door, efficiency of the refrigeration system for steady-
state storage load (similar to the efficiency rating system for HVAC),
and performance of the refrigeration system for removal of process heat
and equipment-generated heat. (Kason, No. 16 at p. 2)
Other interested parties commented that allowing manufacturers to
develop their own calculation methodology or software program as an
AEDM could be problematic. Owens Corning questioned whether there could
be a comparison among ratings published by manufacturers that developed
different AEDMs. (Owens Corning, Public Meeting Transcript, No. 15 at
p. 64) Craig stated that manufacturers who devise their own test
procedures could write them in a way that benefits their own company.
(Craig, Public Meeting Transcript, No. 15 at pp. 68-69) SCE stated that
allowing manufacturers to develop their own software as an AEDM could
be unfair to manufacturers with fewer resources, because the software
is expensive and time-consuming to develop. Instead, SCE suggested that
it would be better to have a transparent analysis method with the
algorithms available to all participants and the data in a standardized
format. (SCE, Public Meeting Transcript, No. 15 at p. 71) Craig replied
that many manufacturers have sizing programs, which may be proprietary,
to calculate the total load of the walk-in, accessories, and product
load, and to size the refrigeration system properly for the energy
requirements of the envelope. (Craig, Public Meeting Transcript, No. 15
at pp. 77-78 and No. 22 at p. 4) However, Craig stressed that requiring
manufacturers to follow the same model developed or approved by DOE,
would be fair to different manufacturers and provide consistent
information to end users. (Craig, Public Meeting Transcript, No. 15 at
p. 94 and No. 22 at p. 5)
ACEEE asserted that it would be difficult for DOE to work with many
proprietary models, some of which might be difficult to verify. (ACEEE,
Public Meeting Transcript, No. 15 at p. 94) NEEA also said that if an
AEDM were used, the software should be equally available to all
manufacturers and code officials for the purpose of determining
compliance. (NEEA, No. 18 at p. 3) Crown Tonka stated that a standard
configuration and standard test should be developed to create a
baseline
[[Page 191]]
for energy usage, with normalizing factors associated with
configuration changes. (Crown Tonka, No. 23 at p. 1) Owens Corning
reiterated that a single AEDM should be accepted to keep comparisons
consistent. (Owens Corning, No. 31 at p. 2)
DOE had previously understood that manufacturers would develop
their own AEDMs and would verify their accuracy by testing a small
number of walk-in models. However, as discussed above, most interested
parties indicated that allowing manufacturers to develop their own
rating calculations or software could be problematic, despite the fact
that the calculations and software would need to be verified.
Therefore, DOE does not propose to allow manufacturers to develop their
own AEDMs. Instead, DOE developed its own calculation methodology for
manufacturers to use in rating similar, but not identical, units of
walk-in equipment. For further discussion on this methodology, see
section III.B.3.f.
4. Proposed Option and Recommendation: Separate Envelope and
Refrigeration Tests
Both methods described above were predicated on the assumption that
an entire walk-in unit is manufactured by a single entity, which could
either test the walk-in as a whole according to ARI Standard 1200-2006,
or calculate the overall efficiency using an AEDM. In fact, as DOE
learned, most walk-ins have two main manufacturers: One who
manufactures the envelope and one who manufactures the refrigeration
system that cools the interior of the envelope. (Other manufacturers
may be involved in producing secondary components --such as fan
assemblies or lighting-- that are then purchased by the main
manufacturers and incorporated as part of the refrigeration system or
envelope.) These two parts are manufactured separately, and are often
assembled together in the field by a third-party contractor who may not
have been responsible for the manufacture of either part, and who may
not have testing or evaluation capabilities. Because of this situation,
DOE developed, and is proposing, a different approach for testing walk-
ins, as described below.
Specifically, DOE proposes separate test procedures for the
envelope and the refrigeration system. The envelope manufacturer would
be responsible for testing the envelope according to the envelope test
procedure, and the refrigeration system manufacturer would be
responsible for testing the refrigeration system according to the
refrigeration system test procedure. Such an approach would be more
likely to generate usable data in support of standards for both the
envelope and the refrigeration system during the development of any
energy conservation standards for walk-in coolers and freezers. The two
test procedures are described in sections III.B and III.C,
respectively.
There are several advantages to this approach. First, having
separate test procedures would allow individual component manufacturers
to test their components--the envelope and the refrigeration system.
These component manufacturers would be more likely to have access to
the resources, equipment, and personnel needed to conduct the tests. On
the other hand, the ``manufacturer'' of an entire walk-in system (i.e.,
envelope and refrigeration system combined), could be a third party: A
contractor who assembles the walk-in from the separate components and/
or installs it in the field. This third-party assembler may even be the
end-user or owner of the equipment. If a walk-in is assembled in the
field, testing of the entire assembled system may not be feasible due
to lack of expertise and the need for additional testing equipment.
Second, this approach would result in a significantly reduced
testing burden while ensuring compliance with any standard DOE may
develop. There are many more assemblers and installers of walk-ins than
there are component manufacturers. Because EPCA requires manufacturers
to demonstrate compliance with energy conservation standards,
interpreting the term ``manufacturer'' to include assemblers and
installers, who may be contractors or end-users, to demonstrate
compliance with a standard would impose the compliance burden on
entities who, more likely than not, may not have participated in the
design and manufacture (and therefore energy efficiency) of the
component parts. Furthermore, this approach would create substantial
difficulties for DOE to enforce any standards it promulgates for walk-
in equipment. While DOE considered the possibility that including
assemblers and installers as parties involved in the manufacture of
this equipment could encourage these parties to take steps to ensure
that compliant equipment is installed, at this time, DOE believes that
the testing burdens are best met by the envelope and refrigeration
system manufacturers for the reasons discussed above. Accordingly,
under today's proposal, only envelope and refrigeration system
manufacturers would need to demonstrate compliance with any proposed
standard through the use of the test procedure. (DOE notes that
possible remedial action for failing to satisfy these requirements
include civil penalties and injunctive relief to prevent the continued
sale and distribution of noncompliant equipment.) (42 U.S.C. 6303-6304)
DOE requests comment on this proposed approach and whether it is
appropriate for walk-ins.
B. Envelope
As described earlier, the envelope consists of the insulated box in
which the stored items reside. The following discussion describes in
greater detail the test procedure DOE is proposing for the walk-in
envelope. DOE also addresses issues raised by interested parties.
This procedure contains the proposed methodology for evaluating the
performance characteristics of the insulation as well as methods for
testing thermal energy gains related to air infiltration caused by use
(door openings) and imperfections in wall interfaces or door gasketing
material. Heat gain due to internal electrical components is an
additional consideration.
The proposed procedure utilizes the data obtained to calculate a
measure of energy use associated with the envelope. In other words, the
test procedure calculates the effect of the envelope's characteristics
and components on the energy consumption of the walk-in as a whole.
This includes the energy consumption of electrical components present
in the envelope (such as lights) and variation in the energy
consumption of the refrigeration system due to heat loads introduced as
a function of envelope performance, such as conduction of heat through
the walls of the envelope. The effect on the refrigeration system is
determined by calculating the energy consumption of a theoretical, or
nominal, refrigeration system, were it to be paired with the tested
envelope. Using the same nominal refrigeration system characteristics
allows for direct comparison of the performance of walk-in envelopes
across a range of sizes, product classes, and levels of feature
implementation.
The test procedure obtains a metric of energy use associated with
the envelope of a walk-in cooler or freezer, consistent with the
statutory requirement (42 U.S.C. 6314(a)(9)(B)(i)). For purposes of
this rulemaking, DOE interprets the term ``energy use'' to describe the
sum of (a) the electrical energy consumption of envelope components and
(b) the energy consumption of the walk-in refrigeration equipment that
is
[[Page 192]]
contributed by the performance of the envelope.
1. Overview of the Test Procedure
In accordance with EPCA, DOE is developing test procedures to
evaluate the energy use associated with the envelope of walk-in coolers
and freezers. The walk-in envelope includes, but may not be limited to,
walls, floor, ceiling, seals, windows, and/or doors comprised of single
or composite materials designed to isolate the interior, refrigerated
environment from the ambient, external environment. For the purposes of
developing this test procedure and evaluating potential performance
standards for walk-in equipment, DOE considers the envelope to also
include lighting and other energy-consuming components of the walk-in
that are not part of its refrigeration system (e.g., motors for
automatic doors, anti-sweat heaters, etc.). DOE is considering the
following definition for ``envelope,'' which would be inserted into 10
CFR part 431:
(1) The portion of a walk-in cooler or walk-in freezer that
isolates the interior, refrigerated environment from the ambient,
external environment; and
(2) All energy-consuming components of the walk-in cooler or walk-
in freezer that are not part of its refrigeration system.
DOE requests comments on this proposed definition.
DOE also evaluated several available industry test procedures to
measure the energy performance of various components of the walk-in
envelope, but was unable to find a test procedure that would evaluate
the entire envelope system. Consequently, DOE developed its own
methodology, including a prescriptive calculation procedure, which
incorporates specific component tests and allows for an overall energy
performance value of the envelope to be determined. The proposed test
measurements and accompanying calculation procedures to ascertain the
overall energy performance value are described in the following
sections.
2. Test Methods
As discussed above, DOE was unable to find a single, existing
comprehensive test procedure for evaluating walk-in cooler and freezer
envelopes. However, DOE identified and evaluated many recognized
industry standards that could be applied to the testing of certain
components and characteristics of walk-in envelopes. DOE incorporated
an insulation test and an air infiltration test, with some
modifications, into the proposed test procedure. The evaluation
process, the results of the evaluation, and details of the proposed
test methods are described in the following sections.
a. Insulation
Insulation comprises a significant component of walk-in units. EPCA
specifies that ASTM C518-04, ``Standard Test Method for Steady-State
Thermal Transmission Properties by Means of the Heat Flow Meter
Apparatus,'' must be used, along with specific foam temperatures for
freezer or cooler applications specified in EPCA, to determine the R
value of individual walk-in envelope insulation materials. (42 U.S.C.
6314(a)(9)(A)) Commenters identified two issues of significance for DOE
to consider when developing a test procedure for insulation: aging and
moisture absorption. DOE discusses these issues in the subsections that
follow.
i. Aging of Foam Insulation
EPCA requires that the test procedure for walk-ins use an R value
that shall be the 1/K factor multiplied by the thickness of the panel.
(42 U.S.C. 6314(a)(9)(A)) The Act does not specify when the R value
should be calculated, a key issue interested parties raised at the
framework public meeting. Specifying when the R-value should be
calculated is a critical consideration because several sources indicate
that the R-value of certain materials can change over time.
Craig stated that R values tend to deteriorate over time and that
different materials exhibit unique rates of deterioration. (Craig,
Public Meeting Transcript, No. 15 at p. 215 and No. 8 at p. 1) Craig
expressed concern that using an initial R value (R value as measured
within two weeks of manufacture) to determine compliance would ignore
deterioration that occurs in blown foams over time. Craig argued that
underestimating the energy use of walk-ins would be the likely outcome
of using initial R-value, that it would be misleading for end-users,
and that it would be inconsistent with the goals of the EISA 2007
legislation and the rulemaking process. (Craig, Public Meeting
Transcript, No.15 at p. 215) A comment submitted jointly by
representatives of ASAP, ACEEE, and NRDC (hereafter referred to as the
``Joint Comment'') stated that the test procedures used should account
for the potential degradation of panel insulation and door seals over
time. (Joint Comment, No. 21 at p. 2) Craig also recommended that DOE
develop an accelerated test procedure that represents lifetime energy
use and can be completed within 6 months. (Craig, No. 8 at p. 1)
In the context of foam insulation for walk-ins and the building
industry, long-term thermal resistance (LTTR), described in greater
detail below, refers to the impact of diffusion on the thermal
resistance of insulation materials. In other words, the concentration
of gaseous blowing agents contained in the foam, and which provide the
foam with much of its insulating value, is reduced by both the
diffusion of air into the foam and the secondary process of the blowing
agent diffusing out of the foam. Because air has a significantly lower
insulating value, the increased ratio of air to blowing agent reduces
the foam insulation performance (this process is also known as
``aging''). This diffusion process causes foam to lose insulating
value, which is represented by its R-value. As a concept, LTTR
represents the R-value of foam material over its lifetime by describing
insulating performance changes due to diffusion over time.
DOE investigated the issue of aging in foam insulation and found
that it is widely accepted that the material properties of foam
insulation made with gaseous blowing agents, other than air and
including HFC-134a, HFC-245fa, HFC-365mfc, cyclopentanes, change over
time. The amount of degradation can range from roughly 10-35 percent
within 2 years of manufacture. Because use of ASTM C518-04 reflects the
properties of a material at the time it is tested, using ASTM C518-04
to measure the insulating performance of a foam material at the time of
manufacture would yield a result that differs from that produced by the
same test conducted at some later point in time. Additionally, research
has found that the vast majority of diffusion into and out of foam
materials manufactured with blowing agents other than air occurs within
the first 5 years of manufacture. Because the rate of diffusion follows
an exponential curve, the majority occurs within the first year, after
which the diffusion curve changes very little as it asymptotically
approaches the equilibrium point.
DOE found that various methods of ``conditioning'' foam prior to
measuring its insulating ability with American Society for Testing and
Materials (ASTM) C518 have been developed in order to test aged
insulating value, or LTTR. These standards are contained in five foam
material specifications:
(1) ASTM C578-09, ``Standard Specification for Rigid, Cellular
Polystyrene Thermal Insulation;''
(2) ASTM C591-08a, ``Standard Specification for Unfaced Preformed
Rigid Cellular Polyisocyanurate Thermal Insulation;''
[[Page 193]]
(3) ASTM C1029-08, ``Standard Specification for Spray-Applied Rigid
Cellular Polyurethane Thermal Insulation;''
(4) ASTM C1126-04, ``Standard Specification for Faced or Unfaced
Rigid Cellular Phenolic Thermal Insulation;'' and
(5) ASTM C1289-08, ``Standard Specification for Faced Rigid
Cellular Polyisocyanurate Thermal Insulation Board.''
DOE found that since their development in the 1980s, the most
widely accepted conditioning methods are the 180-day conditioning at 73
[deg]F or a 90-day conditioning at 140 [deg]F. The goal of the 90-day
conditioning method was to achieve the same aging result as the 180-day
method in a shorter period of time. 180-day conditioning is used by
ASTM C591-08a and ASTM C578-09 and the 90-day condition is typically
used for ASTM C1089-08 and ASTM C1126-04. By accelerating the
conditioning, the 90-day test sought to reduce the time and cost
burdens for manufacturers. Although elevating the temperature of foams
did achieve a faster rate of aging, subsequent research found that the
results were not reliable indicators of actual aging because the
relationship between the diffusion coefficient (a proportionality
constant that describes the force or rate of diffusion for a given
substance) and temperature are different for each gas. (Therese
Stovall, ``Measuring the Impact of Experimental Parameters upon the
Estimated Thermal Conductivity of Closed-Cell Foam Insulation Subjected
to an Accelerated Aging Protocol: Two-Year Results,'' p. 1)
DOE found that efforts to develop an accelerated aging method that
did not use elevated temperatures resulted in the creation of ASTM
C1303, which in 1995 introduced the slicing and scaling method, also
known as the ``thin slicing'' method (a technique used to slice the
foam so that it ages more rapidly as a function of reduced thickness).
In contrast to ASTM C578-09, ASTM C591-08a, ASTM C1029-08, ASTM C1126-
04, and ASTM C1289-08, which specify the use of either the 180-day
conditioning method or 90-day accelerate conditioning method to age the
foam before measuring its thermal resistance. In contrast, the thin
slicing method used in ASTM C1303-08 (the most recent version of ASTM
C1303) was designed specifically to test the aging of foam insulation
in duration shorter than 180 days, and without the temperature
elevation methodology used in the 90-day test. (ASTM C1303-08, section
5.3, at p. 3) By reducing the length of the pathway for diffusion to
take place, the ``aging'' can be accelerated without the confounding
effects caused by unique gas properties of the material and blowing
agent. The results are used to determine the R-value of foam 5 years
after manufacture, a value that has been shown to correlate strongly
with the average R-value of foam 15 years after manufacture. (ASTM
C1303-08, section 5.4, at p. 3)
In early 2000, the National Research Council Canada and Institute
for Research in Construction (NRC-IRC) developed CAN/ULC-S770-00. CAN/
ULC-S770-00 incorporated elements of ASTM C1303-95 (the first version
of ASTM C1303) but altered that standard by clarifying the slicing
procedure used in ASTM C1303-95, as differing interpretations of the
previous procedure were thought to be causing variations in the test
results among third-party testing facilities. These changes sought to
eliminate inconsistency in the interpretation of the slicing procedure
and test setup to ensure uniformity across testing labs. In December
2000, CAN/ULC-S770-00 became the Canadian national mandatory test for
calculating the LTTR of all foam insulation products (this test has
since been updated; the most recent version is CAN/ULC-S770-03).
Members of the U.S.-based Polyisocyanurate Insulation Manufacturers
Association (PIMA) began to test their products using the same
procedure on January 1, 2003. The LTTR calculated from this test
procedure is used for all building insulation product labeling in
Canada and PIMA products in the United States. Also in 2000, ASTM
C1303-95 was updated as ASTM C1303-00.
In a 2005 rule by the U.S. Federal Trade Commission (FTC) in which
the FTC considered requiring ASTM C1303-00 (the most recent version at
that time) for product labeling on all foam insulation products, the
FTC's review process revealed several unresolved issues related to the
test procedure. (70 FR 31258 (May 31, 2005); 16 CFR Part 460, Labeling
and Advertising of Home Insulation: Trade Regulation Rule, Final Rule)
Subsequently, ASTM C1303-00 was updated to address these issues, which
included foam stack composition, minimum slice thickness and slice
source, the time between manufacture and test initiation, preparation
of foam-in-place samples, and other clarifications of the procedure.
This updated version was published as ASTM C1303-08 and is the most
recent version of the standard to date.
Some commenters noted during the framework meeting that the
application of an impermeable vapor barrier to the surface of the foam
could reduce the impact of aging. Depending on its end use, foam
insulation may have facers or skins applied to act as a vapor barrier
and/or to enhance the bond of construction glues. Kysor stated that
proper use of skins eliminates aging and the associated reduction of R-
value in polyurethane panels. (Kysor (attachment), No. 29 at p. 1)
DOE examined this issue and found that foams used in walk-in panels
are sometimes protected by impermeable barriers designed to prevent
vapor and/or air exchange into or out of the foam or the interior of
the walk-in. DOE found research conducted by the National Resource
Council Canada (NRCC) suggesting that impermeable facers do not
eliminate aging but may delay the rate of aging and/or the final
equilibrium of the aged state. (Mukhopadhyaya, P.; Bomberg, M.T.;
Kumaran, M.K.; Drouin, M.; Lackey, J.; van Reenen, D.; Normandin, N.,
``Long-Term Thermal Resistance of Polyisocyanurate Foam Insulation With
Impermeable Facers''; Mukhopadhyaya, P.; Bomberg, M.T.; Kumaran, M.K.;
Drouin, M.; Lackey, J.; van Reenen, D.; Normandin, N., ``Long-Term
Thermal Resistance of Polyisocyanurate Foam Insulation With Gas
Barrier''; Mukhopadhyaya, P.; Kumaran, M.K. ``Long-Term Thermal
Resistance Of Closed-Cell Foam Insulation: Research Update From
Canada.'') In one of the summary observations of ``Long-Term Thermal
Resistance of Polyisocyanurate Foam Insulation With Gas Barrier,'' the
NRCC noted, ``a considerable amount of aging occurred in thin slice
specimens despite having untouched impermeable facers, as well as a
glass plate at the bottom of the specimens and edges sealed completely
with epoxy coating.''
Additionally, the relationship between the skin and the rate of
aging in foam depends on preserving the integrity of both the skin
surface and the bonding between the skin and insulation. Punctures,
made to allow for the installation of light fixtures, doors, and
shelving, undermine the integrity of the skin. Walk-in insulation
panels and their skins also typically separate over time due to
shrinkage of foam materials after manufacture. While most foam
materials contract by less than 1 percent of their total volume,
shrinkage at this level is enough to create significant air gaps. DOE
found that current methods of conditioning foam materials do not
account for impermeable facers.
Finally, like the conditioning standards that are currently in use,
ASTM C1303-08 is not designed to test impermeably faced foams that may
be
[[Page 194]]
used with walk-ins. Significant research has been underway by the NRCC
but no known test procedure is currently available that accounts for
the effect of impermeable barriers. DOE requests feedback on this
issue, including the submission of test results on the impact of
impermeable skins on long-term R-value. DOE specifically requests that
interested parties submit or identify peer-reviewed, published data on
this issue.
DOE also requests feedback on the use of ASTM C1303-08 with
impermeably faced foams. DOE may recommend the use of a test procedure
specifically designed for impermeably faced foam if one is developed.
As a result of this evaluation, DOE proposes requiring
manufacturers to use ASTM C1303-08 to determine the LTTR of walk-in
foam insulation for the purposes of calculating the energy consumption
of walk-in equipment. DOE requests comments on this proposal.
DOE is also proposing and seeking comment on the following
exceptions to ASTM C1303-08:
(1) Section 6.6.2 of C1303-08 suggests that two standards for
measuring the thermal resistance may be used. DOE proposes to allow use
only of ASTM C518-04 (in EPCA, an incorrect form of the date suffix was
used, e.g., ASTM C518-[20]04), as specified in EPCA. (42 U.S.C.
6314(a)(9)(A)(ii))
(2) In section 6.6.2.1, in reference to ASTM C518-04, the mean test
temperature of the foam during R-value measurement would be -6.7 2 [deg]C (20 4 [deg]F) with a temperature
difference of 22 2 [deg]C (40 4 [deg]F) for
freezers and 12.8 2 [deg]C (55 4 [deg]F) with
a temperature difference of 22 2 [deg]C (40 4
[deg]F) for coolers. This change replaces the standard mean temperature
of 75 [deg]F for ASTM C518-04 with the EPCA specified values.
(3) For the purposes of preparing samples with foam-in-place
method, section A2 should be followed exactly except for the following
modifications to accommodate foam-in-place methods that may be used
during the manufacture of walk-in panels:
(3.1) Instead of following A2.3, which specifies that the
foam be sprayed onto a single sheet of wood, the sample shall be foamed
into a fully closed box of internal dimension 60 cm x 60 cm by desired
product thickness (2ft x 2ft x Desired thickness). The box shall be
made of \3/4\ inch plywood and internal surfaces wrapped in 4 to 6 mil
polyethylene film to prevent the foam from adhering to the box
material.
(3.2) Instead of following section A2.4, which specifies
the spraying of foam layers onto a open sheet of plywood, the cavity
shall be filled using the manufacturer's typical foam-in-place method
through a standard injection port or other process typically used to
foam the product being tested.
(3.3) In section A2.6, which defines the single surface in
contact with the board to be the ``surface,'' the definition of the
foam's ``surface'' shall be the two surface regions in contact with the
60 x 60 cm sections of the box.
(3.4) Section A2.8 shall not be followed because the
prepared sample will not have any ``free rise'' component.
DOE proposes that manufacturers select foam test thicknesses based
on design specifications and practice. If a foam's thickness as
manufactured varies from the tested product thickness, DOE proposes
that the R-value of that foam at its manufactured thickness may be
interpolated using the results of ASTM C1303-08, provided that the
manufactured thickness does not vary from the tested product thickness
by more than 0.5 inches. For example, if 4-inch and 6-inch
products were prepared, interpolation between 3.5 and 4.5 inches would
be allowed for the 4-inch foam and 5.5 and 6.5 inches for the 6-inch
foam. If the manufacturer determines that final foam thickness should
be outside of the tested range, then additional testing would be
necessary to fit the criterion for interpolation. Manufacturers should
make their sample selections accordingly to avoid the need for
additional testing. DOE requests feedback on the use of interpolation
within the specified 0.5 inch range.
DOE proposes that the results for each of the sample sets of three
stacks should be reported as specified by ASTM C1303-08. As defined by
ASTM C1303-08, after thin slices of foam are cut, the slices are
organized into ``stacks'' of slices to match the original overall
thickness of the sample. The procedure defines three stack types: (1)
Stacks comprised of only surface slices of foam, (2) stacks of only
core slices and (3) a mixture of core and surface slices. A ``surface''
slice and a ``core'' slice are defined in ASTM C1303 as ``a thin-slice
foam specimen that was originally adjacent to the surface of the full-
thickness product and that includes any facing that was adhered to the
surface of the original full-thickness product'' and ``a thin-slice
foam specimen that was taken at least 5 mm (0.2 in.) or 25% of the
product thickness, whichever is greater, away from the surface of the
full thickness product,'' respectively. The R-value of only the mixed
stack would be used to calculate the energy p