Medicare and Medicaid Programs; Fire Safety Requirements for Long Term Care Facilities, Automatic Sprinkler Systems, 47075-47092 [E8-18670]
Download as PDF
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
Dated: July 31, 2008.
Donald R. Stubbs,
Acting Director, Registration Division, Office
of Pesticide Programs.
requires affected facilities to maintain
their automatic sprinkler systems once
they are installed.
DATES: These regulations are effective
on October 14, 2008. The incorporation
by reference listed in the rule is
approved by the Director of the Federal
Register October 14, 2008.
FOR FURTHER INFORMATION CONTACT:
Danielle Shearer, (410) 786–6617; James
Merrill, (410) 786–6998; Marcia
Newton, (410) 786–5265; or Jeannie
Miller, (410) 786–3164.
SUPPLEMENTARY INFORMATION:
Therefore, 40 CFR chapter I is
amended as follows:
I
PART 180—[AMENDED]
1. The authority citation for part 180
continues to read as follows:
I
Authority: 21 U.S.C. 321(q), 346a and 371.
2. Section 180.439 is amended by
alphabetically adding the following
commodities to the table in paragraph
(a) to read as follows:
I
I. Background
§180.439 Thifensulfuron methyl;
tolerances for residues.
(a) * * *
Commodity
*
Parts per million
*
*
*
*
Barley, hay
*
*
*
*
0.8
*
Oat, forage
*
*
*
*
0.2
*
Oat, hay
*
*
*
*
0.05
*
Wheat, forage
*
*
*
*
2.5
*
Wheat, hay
*
*
*
*
0.7
*
*
*
*
*
*
[FR Doc. E8–18457 Filed 8–12–08; 8:45 am]
BILLING CODE 6560–50–S
DEPARTMENT OF HEALTH AND
HUMAN SERVICES
Centers for Medicare & Medicaid
Services
42 CFR Part 483
[CMS–3191–F]
RIN 0938–AN79
Medicare and Medicaid Programs; Fire
Safety Requirements for Long Term
Care Facilities, Automatic Sprinkler
Systems
Centers for Medicare &
Medicaid Services (CMS), HHS.
ACTION: Final rule.
hsrobinson on PROD1PC76 with RULES
AGENCY:
SUMMARY: This final rule requires all
long term care facilities to be equipped
with sprinkler systems by August 13,
2013. Additionally, this final rule
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
A. Overview of the Life Safety Code
The Life Safety Code (LSC), published
by the National Fire Protection
Association (NFPA), a private, nonprofit
organization dedicated to reducing loss
of life due to fire, is a compilation of fire
safety requirements. The LSC contains
fire safety requirements for both new
and existing buildings. It is updated
through a consensus process and
generally published every 3 years.
Sections 1819(d)(2)(B) and 1919(d)(2)(B)
of the Social Security Act (the Act)
require that long term care facilities
participating in the Medicare and
Medicaid programs generally meet the
applicable provisions of the edition of
the LSC that is adopted by the Secretary.
Beginning with the adoption of the
1967 edition of the LSC in 1971,
Medicare and Medicaid regulations
have historically incorporated the LSC
requirements by reference for all long
term care facilities as well as other
providers, while providing the
opportunity for a Secretarial waiver of a
requirement under certain
circumstances. The statutory basis for
incorporating NFPA’s LSC for our other
providers is under the Secretary’s
general rulemaking authority at sections
1102 and 1871 of the Act, and under
provider-specific provisions of title
XVIII that permit us to issue regulations
to protect the health and safety of
participants in Medicare and Medicaid.
We adopted the LSC to ensure that
patients and residents are consistently
protected from fire, regardless of the
location in which they receive care.
Since adopting and enforcing the 1967
and subsequent editions of the LSC,
there has been a significant decline in
the number of multiple death fires,
indicating that the LSC has been
effective in improving fire safety in
health care facilities.
On October 26, 2001, we published a
proposed rule (66 FR 54179), and on
January 10, 2003, we published a final
rule in the Federal Register, entitled
‘‘Fire Safety Requirements for Certain
PO 00000
Frm 00049
Fmt 4700
Sfmt 4700
47075
Health Care Facilities’’ (68 FR 1374). In
that final rule, we adopted the 2000
edition of the LSC provisions as the
standard governing Medicare and
Medicaid health care facilities,
including long term care facilities. The
final rule required all existing long term
care facilities to comply with the 2000
edition of the LSC.
The 2000 edition of the LSC required
all newly constructed buildings
containing health care facilities to have
an automatic sprinkler system installed
throughout the building. However, like
all previous editions, the LSC did not
require existing buildings to install
automatic sprinkler systems throughout
if they met certain construction
standards, ranging from the size of the
buildings to the types of material used
in their construction.
In accordance with the 2000 edition
of the LSC, an existing building that
meets the above-mentioned construction
standards must install sprinklers if it
undergoes a major renovation. However,
in such cases, it is required to install
sprinklers only in the renovated
section(s). Therefore, a building may
have sprinklers only on one floor or in
one wing. We did not receive any timely
public comments in response to the
October 2001 proposed rule that
addressed the issue of installing
automatic sprinkler systems in
buildings not undergoing major
renovations. That is to say, no public
comments supported, questioned or
challenged our proposal to incorporate
this LSC provision by reference.
In the 2006 edition of the LSC, the
NFPA decided to include an automatic
sprinkler system requirement for all
long term care facilities. We support the
NFPA in its decision. We decided to
proceed with this rule, without
proposing adoption of the NFPA 2006
edition of the LSC, because we want to
avoid further delay in requiring an
automatic sprinkler system in long term
care facilities. As stated in the October
27, 2006 proposed rule (71 FR 62957,
62960), given the large scope of the LSC,
we would not be able to adopt and
enforce compliance with the 2006
edition of the LSC until 2009 or 2010.
Therefore, we decided at this time to
proceed with rulemaking that does not
include adoption of the NFPA 2006
LSC.
We will continue to work with the
NFPA to revise and refine each edition
of the LSC. We are currently working
with the NFPA through its consensus
process to revise and refine the 2009
edition of the LSC. Once the 2009
edition is issued, we will review the
code in its entirety and explore the
possibility of adopting it for all
E:\FR\FM\13AUR1.SGM
13AUR1
47076
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
hsrobinson on PROD1PC76 with RULES
Medicare and Medicaid-participating
health care facilities.
B. Recent Fire Safety Developments
A Government Accountability Office
(GAO) report entitled ‘‘Nursing Home
Fire Safety: Recent Fires Highlight
Weaknesses in Federal Standards and
Oversight’’ (GAO–04–660, July 16, 2004,
https://www.gao.gov/new.items/
d04660.pdf) examined two long term
care facility fires (Hartford and
Nashville) in 2003 that resulted in 31
total resident deaths. The report
examined Federal fire safety standards
and enforcement procedures, as well as
results from the fire investigations of
these two incidents. The report
recommended that fire safety standards
for unsprinklered facilities be
strengthened and the report cited the
effectiveness of smoke detectors’ and
sprinklers’ fire protection features for
long term care facilities.
In response to a recommendation
made in the GAO report, on March 25,
2005, we published an interim final rule
with comment period in the Federal
Register entitled, ‘‘Fire Safety
Requirements for Certain Health Care
Facilities; Amendment’’ (70 FR 15229).
This interim final rule added paragraph
(a)(7) to § 483.70, to require long term
care facilities, at minimum, to install
battery-operated smoke detectors in
resident sleeping rooms and public
areas, unless they had a hard-wired
smoke detector system in resident
rooms and public areas or a sprinkler
system installed throughout the facility.
This IFC was finalized September 22,
2006 (71 FR 55326).
Structural fires in long term care
facilities are relatively common events.
From 1994 to 1999, an average of 2,300
long term care facilities reported a
structural fire each year (2004 GAO
Report). Although approximately 2,300
facilities per year reported fires, those
fires resulted in an average of only 5
fatalities nationwide per year (2004
GAO Report). The likelihood of a
fatality occurring due to a long term care
facility fire was quite low.
From 1990 to 2002, there were no
fires in long term care facilities that
resulted in more than one or two
fatalities. During that time period there
were no fires in long term care facilities
that resulted in a loss of life comparable
to that of the Hartford and Nashville
fires.
We believe the low number of firerelated fatalities each year is
attributable, in part, to the increasing
use of automatic sprinkler systems in
long term care facilities as a fire
protection method. State and local
jurisdictions often adopt an edition of
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
the LSC or a comparable fire safety code
shortly after it is published. Therefore,
a building constructed in the early
1990s likely met the requirements of the
1991 edition of the LSC or another
comparable code. Beginning with the
1991 edition of the LSC, all newly built
facilities were required to have
automatic sprinkler systems. In
addition, beginning with the 1991
edition of the LSC, all facilities
undergoing major renovations were also
required by the LSC to install automatic
sprinkler systems at least in those
renovated areas. Therefore, as new
facilities have replaced old facilities,
and as facilities have been renovated,
the number of residents protected by
automatic sprinkler systems has
increased. The increase in the number
of automatic sprinkler systems and the
number of residents residing in
sprinklered buildings has decreased
significantly the likelihood of a fatality
occurring due to fire.
According to NFPA data cited in the
2004 GAO report, there is an 82 percent
reduction in the chance of death
occurring in a sprinklered building
when compared to the chance of death
occurring in an unsprinklered building.
In addition, we note that there has never
been a multiple death fire in a long term
care facility that had an automatic
sprinkler system installed throughout
the facility.
Automatic sprinkler systems are
effective in reducing the risk of fatalities
due to fire because they limit the size of
a developing fire and prevent the fire
from growing and spreading beyond the
area where the fire ignited. In addition,
impeding the fire’s growth gives the
facility staff and residents and the local
fire department more time to respond to
the situation.
Automatic fire suppression through
sprinklers also alleviates some of the
current heavy reliance on facility staff to
implement the facility’s emergency
plan. Fires often occur at night, as both
the Hartford and Tennessee fires did,
when staffing levels are lowest.
Investigators of the Hartford fire
determined that the facility’s staff did
not fully implement the facility’s
emergency plan, which may have
contributed to the number of fatalities in
that fire. The 2004 GAO report
concluded that ‘‘reliance on staff
response as a key component of fire
protection may not always be realistic,
particularly in an unsprinklered
facility.’’ Limiting the area of a building
affected by a fire may result in less of
a need to evacuate or relocate residents.
The effectiveness of automatic
sprinkler systems has prompted some
States, including Virginia, Connecticut,
PO 00000
Frm 00050
Fmt 4700
Sfmt 4700
and Tennessee, to require that all long
term care facilities have sprinklers. The
NFPA also requires all long term care
facilities to have automatic sprinkler
systems as part of the 2006 edition of
the LSC.
II. Provisions of the Proposed
Regulations
We published a proposed rule in the
Federal Register on October 27, 2006
(71 FR 62957) that would require all
long term care facilities to be equipped
with sprinkler systems. That proposed
rule also requested public comments on
the duration of a phase-in period to
allow such facilities to install such
systems.
For the reasons described in section I
of this preamble, we proposed a rule
with three main components. First, the
regulation proposed to add a sunset
provision to paragraph (a)(7) in § 483.70
that would correspond to the phase-in
date of the sprinkler requirement. This
sunset provision would provide that, as
of the phase-in date, we would no
longer enforce the requirement that
facilities have and maintain at least
battery-operated smoke alarms. We
proposed to add the sunset date because
the requirements of § 483.70(a)(7) apply
only to unsprinklered and partially
sprinklered long term care facilities.
Once all long term care facilities are
fully sprinklered, there would not be
any unsprinklered or partially
sprinklered facilities to which
§ 483.70(a)(7) would apply.
Second, we proposed to require every
long term care facility to install an
approved, supervised automatic
sprinkler system in accordance with the
1999 edition of NFPA 13, Standard for
the Installation of Sprinkler Systems,
throughout the facility if it did not have
such a system already. If a long term
care facility was part of another
building, such as a hospital, then the
building would be required to have
sprinklers only in the long term care
facility section. The NFPA 13 specifies
how to properly design and install
sprinkler systems using the proper
components. The standards of NFPA 13
cover a wide variety of factors that are
involved in designing and installing
sprinkler systems. The NFPA 13 is
divided into 10 main chapters governing
the design and installation phases of
automatic sprinkler systems, and the
October 2006 proposed rule
summarized the content of these
chapters.
The NFPA 13 is a very detailed
document, with a wide variety of
standards and exceptions to those
standards. The document provides
many options for the design and
E:\FR\FM\13AUR1.SGM
13AUR1
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
hsrobinson on PROD1PC76 with RULES
installation of sprinkler systems so that
each system may be tailored to the
building in which it is installed.
Third, the regulation proposed to
require every long term care facility to
test, inspect, and maintain an approved,
supervised automatic sprinkler system
in accordance with the 1998 edition of
NFPA 25, Standard for the Inspection,
Testing and Maintenance of WaterBased Fire Protection Systems. Proper
inspections, tests, and maintenance of
sprinkler systems are critical to ensuring
that sprinkler systems function properly
on a continuous basis. Fires are, by
nature, unpredictable, and sprinkler
systems must be operable at all times to
ensure that buildings are protected
whenever and wherever fires occur.
NFPA 25 covers a wide variety of
testing, inspection, and maintenance
requirements for the numerous types of
sprinkler systems that facilities may
install and the auxiliary equipment that
may be necessary for some facilities. We
summarized the content of NFPA 25 in
the proposed rule.
The proposed requirements of this
regulation include three technical terms:
‘‘approved,’’ ‘‘automatic,’’ and
‘‘supervised.’’ These terms are terms of
art in the fire safety community and are
included in NFPA 101, Life Safety Code,
with which long term care facilities
must already comply. There may be,
however, individuals who are not
familiar with the terms. Their
definitions, as used in the fire safety
community, are as follows:
• Approved means acceptable to the
authority having jurisdiction (from 2000
edition of NFPA 101, the LSC).
• Automatic means that which
provides a function without the
necessity of human intervention (from
2000 edition of NFPA 101, the LSC).
• Supervised means that the system
and particular components of the
system are monitored by a device with
auditory and visual signals that are
capable of alerting facility staff should
the system or one of its components
become inoperable for any reason
(adapted from 1999 edition of NFPA 13,
Standard for the Installation of
Sprinkler Systems).
III. Analysis of and Responses to Public
Comments
We received 107 comments from the
public on the October 27, 2006
proposed rule. The comments received
and our responses to those comments
are discussed below.
Comment: The vast majority of
commenters strongly supported our
intent to require automatic sprinkler
systems throughout all long term care
facilities. Conversely, a small minority
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
of commenters disagreed with the
proposed rule, citing the expense of
purchasing and installing sprinklers and
the availability of other fire safety
features such as water-based fire-proof
coatings and fire walls as reasons for not
requiring sprinklers in all long term care
facilities.
Response: We appreciate the strong
support expressed by most commenters.
While we agree that there are other
methods for improving fire safety in
long term care facilities, these other
methods do not achieve the same high
level of fire safety as automatic sprinkler
systems. We are proceeding with this
final rule requiring all long term care
facilities to install and maintain
automatic sprinkler systems because we
agree with the GAO that such systems
are the single most effective fire safety
method currently available and that the
presence of such systems will help save
lives and property.
Comment: Several commenters
submitted comments related to the
specific facilities that are, or should be,
affected by this final rule. One
commenter explicitly supported our
decision to apply the proposed sprinkler
requirements to all affected long term
care facilities, regardless of their size.
Some commenters requested that this
rule be expanded to apply to any
residential facility that cares for
individuals on a 24-hour basis. One
commenter suggested that the rule
should apply to federally operated
nursing homes as well, such as those
operated by the U.S. Department of
Veterans Affairs. Another commenter
suggested that the rule should apply to
inpatient facilities such as hospitals and
critical access hospitals with swing
beds. Still other commenters asked
whether the requirements of the final
rule will affect adult day care centers.
Response: We proposed to require all
long term care facilities to install
automatic sprinkler systems regardless
of their size because their recent fire
history and current staffing levels
indicated the need for additional fire
safety features. We do not believe it is
necessary for us to require sprinkler
systems in other facility types, such as
intermediate care facilities, adult day
care facilities, or critical access
hospitals at this time because there is no
demonstrated need for such regulation.
While we agree that it may be
appropriate for federally operated
nursing homes, such as those operated
by the U.S. Department of Veterans
Affairs, to install automatic sprinkler
systems, we do not have regulatory
authority over these facilities. Therefore,
we are unable to promulgate a
regulation applying to them.
PO 00000
Frm 00051
Fmt 4700
Sfmt 4700
47077
Comment: Numerous commenters
discussed the financial impact that the
proposed rule will have on long term
care facilities, and suggested a variety of
methods to offset the expected impact.
Of these commenters, several suggested
that CMS should support legislation in
the Congress that will provide financial
incentives for long term care facilities to
install sprinkler systems. A few
commenters indicated that they are
actively working with the Congress to
obtain financial assistance for long term
care facilities in implementing the
requirements of this final rule. Other
commenters suggested that CMS should
make financial assistance available to
facilities, with some suggesting that
such assistance should be limited to
those facilities with not-for-profit status
or those that are not profitable. Still
another commenter suggested that CMS
should compel State Medicaid programs
to increase reimbursement rates to fund
capital improvements in long term care
facilities.
Response: We recognize that
purchasing and installing an automatic
sprinkler system throughout a long term
care facility requires a substantial
capital investment. We defer to the
Congress and States to provide financial
assistance to long term care facilities to
complete the purchase and installation
process, whether such assistance comes
in the form of loans, grants, tax relief,
and/or increased reimbursement rates.
We have included a 5 year phase-in
period in this final rule. This phase-in
period allows facilities the time and
flexibility to install sprinkler systems in
a manner that is sensitive to the
individual circumstances of each
facility. We believe this phase-in period
will help mitigate the financial impact
of this final rule.
Comment: Numerous commenters
stated that this final rule should provide
additional discussion of the role that
State and locally imposed building and
fire safety codes play in protecting long
term care facility residents.
Response: We acknowledge that State
and local authorities use their authority
to require long term care facilities to
meet building and fire safety codes
independent of the codes applied to
facilities through Federal regulations.
State and local authorities often adopt
more recent editions of such codes than
those required by Federal rules. Until
2003, Federal fire safety regulations
referenced simultaneously Life Safety
Code provisions from several editions
including the editions of 1967, 1973,
and 1985. However, health care
facilities were not being built to these
older standards because State and local
jurisdictions adopted and enforced far
E:\FR\FM\13AUR1.SGM
13AUR1
hsrobinson on PROD1PC76 with RULES
47078
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
more recent editions of building and fire
safety codes. Such prompt adoption of
updated codes by State and local
jurisdictions likely has led to the large
number of long term care facilities that
currently have automatic sprinkler
systems throughout their facilities. We
continue to support the right of State
and local authorities to impose building
and fire safety codes independent of
these Federal requirements and will
continue to monitor all efforts to
improve safety for long term care facility
residents.
Comment: Some commenters
expressed concern that this final rule
will preempt State and local fire safety
requirements. Of these commenters, a
few expressed concern that this Federal
rulemaking preempted State and local
efforts and did not respond to the
unique needs of different localities.
Furthermore, some of these commenters
requested a more detailed discussion of
Executive Order 13132 (Federalism) as
it relates to this rulemaking action.
Conversely, several commenters
indicated that they agreed with our
conclusion that this rule is in
accordance with the actions of State and
local governments, and that it is
appropriate for the Federal government
to require automatic sprinkler systems
in Medicare and Medicaid-participating
long term care facilities.
Response: The Federal regulations for
long term care facilities are considered
to be the minimum standards that a
facility must meet in order to participate
in the Medicare and Medicaid programs.
As such, they will not preempt more
stringent State and local requirements.
For example, if a State or local authority
requires a long term care facility to
install an automatic sprinkler system
within 3 years after adoption of a law
requiring it, then a facility must comply
with that shorter time frame, even
though this Federal regulation allows a
facility up to 5 years to install an
automatic sprinkler system. However, if
a State or local authority requires a long
term care facility to install an automatic
sprinkler system only in hazardous
areas, then a facility must go beyond the
State or local requirement and install an
automatic sprinkler system throughout
its building in order to participate in
Medicare or Medicaid. We believe that
all facilities must install an automatic
sprinkler system throughout a facility by
2013, regardless of the State or locality
where a facility is located. In order to
achieve this goal, it is necessary to
promulgate a Federal regulation. State
and local jurisdictions have always had
the authority to require automatic
sprinkler systems in existing long term
care facilities. However, few States have
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
taken action to require existing long
term care facilities to retrofit their
buildings with such systems. Thus, we
believe it is necessary to take this
Federal action.
In addition, this rule adopts the
sprinkler installation and maintenance
requirements established by the NFPA.
The NFPA is a national standard setting
body with representatives from all
members of the fire safety community,
including State and local jurisdictions.
As such, these representatives had
active input in the content and
framework of the NFPA sprinkler
standards. The standards allow
flexibility in the design, installation,
and maintenance of sprinkler systems to
adapt to the needs of individual
facilities as well as jurisdictions.
Facilities are required by the NFPA
standards to submit their design and
installation plans to the appropriate
authorities having jurisdiction. This
allows local and State authorities the
opportunity to ensure that such plans
meet their individual needs. Since this
action does not impinge upon a State or
local jurisdiction’s authority to impose
more stringent fire safety requirements
upon long term care facilities in
response to the unique needs and
concerns of the particular area, and
gives State and local authorities the
opportunity to provide further input
into individual sprinkler planning
activities, we do not believe this final
rule has Federalism implications as
described in Executive Order 13132.
Furthermore, we regularly
communicate with State and local
officials and with the long term care
provider community through Open Door
Forums, as well as through responses to
letters, informal phone calls, and
informal e-mails. Through these
communications, as well as through the
public comment process for this
proposed rule, we believe we have
sufficiently consulted with all affected
parties, including State and local
jurisdictions, as is required by Executive
Order 13132.
Comment: Several commenters
submitted views regarding the
assumptions and estimates we used in
the impact analysis for the proposed
rule. Commenters questioned our
estimates of the cost per square foot, the
projected number of facilities affected,
and the projected number of lives saved.
Response: We appreciate the
suggestions that we received, and we
considered them as we revised the
impact analysis for this final rule. The
final impact analysis reflects an increase
in our estimate of the cost per square
foot, from a high of $6.10 to a high of
$7.95, to reflect inflation since the
PO 00000
Frm 00052
Fmt 4700
Sfmt 4700
publication of the proposed rule. The
final analysis also revises the number of
facilities that are affected by this rule by
replacing projections of future sprinkler
system installations with the actual
number of facilities lacking automatic
sprinkler systems as of December 2007.
The final impact analysis does not
revise the method for estimating future
lives saved by this rule. Although a
commenter questioned this
methodology, the commenter did not
offer an alternative methodology that
would more accurately estimate this
number. Since we are not aware of an
alternative method to estimate the
number of lives that will be saved, we
have retained the method used in the
proposed rule.
Comment: Some commenters agreed
with our proposal to require automatic
sprinkler systems in all facilities, while
a small number of commenters
requested that certain long term care
facilities be exempt from the
requirements of this final rule.
Response: Automatic sprinkler
systems are generally considered to be
the single most effective fire protection
feature in a building. As such, we
believe all long term care facilities,
regardless of their size or location in
relationship to another type of health
care facility, should be required to have
sprinklers. Exempting a particular class
of long term care facilities, regardless of
the criteria used, will not provide a
consistent level of fire safety across the
country.
Comment: Several commenters
submitted comments regarding CMS
enforcement of this final rule. Some of
these commenters sought assurance that
surveyors would be appropriately
trained to enforce the new sprinkler
requirement. One commenter suggested
that we should survey each facility
annually to ensure compliance with this
rule. Other commenters asked about the
enforcement remedies that would be
available if a facility was non-compliant
with the requirements of this final rule,
going so far as to suggest that noncompliant facilities should receive
reduced payments from Medicare and
Medicaid. Still other commenters
requested that additional information
about the sprinkler status of particular
facilities and facilities as a whole be
included on CMS’ Nursing Home
Compare Web site.
Response: We agree that it is essential
to ensure that surveyors are
appropriately trained to survey facilities
for compliance with all fire safety
requirements, including automatic
sprinkler systems. To that end, we
conduct annual training sessions for
surveyors to educate them on, among
E:\FR\FM\13AUR1.SGM
13AUR1
hsrobinson on PROD1PC76 with RULES
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
other things, fire safety requirements
and appropriate survey procedures. This
training ensures surveyor competency
in this area. We also agree that frequent
surveys of long term care facilities are
key to ensuring continued compliance
with these requirements. By law, we are
required to survey long term care
facilities every 15 months to ensure
compliance with all health and safety
requirements, and we will incorporate
this new requirement into the existing
survey process. If a facility is found to
be non-compliant with the provisions of
this final rule, we have the full
complement of enforcement remedies
available to ensure that a facility comes
into compliance. In addition to
termination of the provider agreement,
available remedies include the
following: (1) Temporary management
(that is, the temporary appointment by
CMS or the State of a temporary director
or administrator of a facility); (2) denial
of payment, including denial of
payment for all individuals, imposed by
CMS upon a skilled nursing facility for
Medicare payments, by a State for
Medicaid payments, or denial of
payment for all new admissions; (3)
civil money penalties; (4) State
monitoring; (5) transfer of residents; or
(6) transfer of residents and closure of
the facility. CMS currently includes
information about a facility’s sprinkler
status on the Nursing Home Compare
Web site to enable consumers to make
an informed decision.
Comment: A commenter suggested
that installation of sprinkler systems
should be limited to pre-approved
companies with proven fire safety
records. Another commenter suggested
that we should create a special task
force in each State to visit each facility
and examine the information used to
design the facility’s sprinkler system.
Response: While we agree that long
term care facilities should look for
qualified contractors to design and
install their sprinkler systems, we do
not believe it is appropriate to, nor do
we have the authority to, select or
approve such contractors. In addition,
we do not believe it is appropriate for
us to develop task forces in each State
to review a facility’s research and design
plan. There are numerous qualified
designers who are capable of designing
sprinkler systems that fulfill facilityspecific specifications. It is incumbent
upon facilities to assure that their
automatic sprinkler systems meet their
specific facility needs as identified
during a thorough review of their
current fire and building safety features
and various other factors.
Comment: A few commenters
submitted additional information on
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
their own fire safety features and
requirements (for example State
sprinkler requirements and facilityspecific fire safety plans).
Response: We appreciate the
additional information provided by the
commenters. It validates our
understanding of current fire safety
efforts, both on the facility and State
levels.
Comment: A commenter suggested
that staffing levels may also impact
facility fire safety, and that we should
require additional staffing during the
phase-in period to ensure that facility
residents are protected from fire.
Response: We agree that sufficient
staffing is necessary to ensure resident
health and safety, including fire safety.
Ensuring resident health and safety,
which is closely tied to facility staffing,
is already required in § 483.15, ‘‘Quality
of life,’’ § 483.30, ‘‘Nursing services,’’
and § 483.70, ‘‘Physical environment.’’
We believe these regulations ensure
sufficient staffing levels in long term
care facilities to promote and protect
resident health and safety in all
circumstances.
Comment: A commenter questioned
the conclusions of the GAO report
regarding the two multiple death fires in
Connecticut and Tennessee. The
commenter stated that the GAO report
did not demonstrate the superiority of
sprinklers over smoke alarms. The
commenter also stated that the number
of multiple death fires before 1990 was
zero, and that the installation of
sprinklers in new facilities after 1990
thus had no bearing on the number of
fires between 1990 and 1992.
Response: While we recognize that
the commenter disagrees with the data
analysis of current fire safety levels in
long term care facilities presented by the
GAO, we continue to support the GAO’s
data, collection methodology, analytic
methodology, and conclusions. We
concur with the GAO that smoke alarms
are necessary in unsprinklered facilities;
we now require unsprinklered facilities
to have such alarms in accordance with
the requirements of § 483.70(a)(7). We
also concur with the GAO that before
1990, multiple death fires occurred on
a more frequent basis. As stated in the
GAO report, ‘‘When the federal
government first adopted the NFPA fire
safety standards in 1971, the number of
multiple-death fires in nursing homes
was about 15 to 18 per year. With the
adoption and enforcement of these
standards, including the requirement for
sprinklers in homes that were not highly
fire resistant, the number of fire-related
nursing home fatalities dropped
dramatically.’’ (p. 14; we note that the
average annual number of long term
PO 00000
Frm 00053
Fmt 4700
Sfmt 4700
47079
care facility fire fatalities, according to
the GAO report, is now 5.) Furthermore,
we concur with the GAO that sprinklers
improve the level of fire safety beyond
that which is provided by smoke alarms,
and we are implementing this final rule
to require sprinklers in all long term
care facilities.
Comment: A commenter suggested
that all facilities that currently have
automatic sprinkler systems throughout
their buildings be required to maintain
those systems in accordance with the
requirements of NFPA 25.
Response: Long term care facilities are
required to meet the standards of the
LSC, which requires facilities with
existing sprinklers to maintain those
sprinklers in accordance with the
requirements of NFPA 25. We agree
with the commenter and are adopting
NFPA 25 by reference at
§ 483.70(a)(8)(ii).
Comment: A commenter stated that
NFPA 101, NFPA 13, and NFPA 25 can
all be viewed without charge at https://
www.nfpa.org/freecodes/
free_access_document.asp.
Response: We thank the commenter
for providing this Web site citation.
Unfortunately, the citation provided
does not link to the documents that a
long term care facility will need to
comply with this final rule. Instead, an
alternative, free Web site for this
information is https://www.nfpa.org/
aboutthecodes/
list_of_codes_and_standards.asp.
Comment: A few commenters
suggested that facilities be permitted to
have a reduced water supply that does
not meet the specifications of the NFPA
requirements for health care facilities
when an adequate level of safety can be
assured with less water.
Response: The NFPA uses a
consensus process to establish the
requirements of its sprinkler installation
and maintenance codes. It would not be
in the best interests of long term care
facilities and their residents to reduce
the NFPA standards. We believe that the
NFPA standards represent the absolute
minimum standards that long term care
facilities must meet, and that lowering
the standards below those of the NFPA
would jeopardize long term care facility
resident and staff safety.
Comment: A commenter requested a
90-day extension of the public comment
period.
Response: We do not believe it is
necessary to extend the standard
comment period. We received 107
unique comments, as well as numerous
duplicate comments, from interested
parties during the comment period, and
we believe these comments adequately
reflect public sentiment on this matter.
E:\FR\FM\13AUR1.SGM
13AUR1
hsrobinson on PROD1PC76 with RULES
47080
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
Comment: A few commenters
suggested additional requirements to
which long term care facilities should
be held. One commenter suggested that,
in addition to installing and
maintaining automatic sprinkler
systems, long term care facilities should
be required to install and maintain
automatic fire alarm systems
incorporating commercial smoke
detectors that comply with the audio
and visual notification standards of the
Americans with Disabilities Act.
Another commenter suggested that long
term care facilities should be required to
have mattresses that comply with
certain fire safety standards.
Response: We agree with the
commenters that numerous additional
options are available to long term care
facilities that wish to further enhance
their fire safety levels. Long term care
facilities may explore these options in
addition to meeting all requirements of
the LSC and this final rule.
Comment: A small number of
commenters submitted comments on the
existing provision that a State may
apply to CMS to use its own alternative
fire safety code imposed by State law if
that code adequately protects patients.
The commenters inquired as to the
status of their own particular
applications for a waiver under this
provision.
Response: CMS actively considers any
application submitted by a State
regarding the use of an alternate fire
safety code in health care facilities.
However, these applications have no
bearing on the requirements of this final
rule because this final rule requires
automatic sprinklers independent of the
requirements of the LSC.
Comment: A commenter asked us to
present a list of those States in the early
1990s that adopted the 1991 or later
edition of the LSC or another code
requiring newly constructed long term
care facilities to install automatic
sprinkler systems.
Response: We do not believe it is
necessary to present such a list of
information regarding the requirements
of individual States. While such a list
may provide additional historic
background on fire safety requirements
in the United States, all unsprinklered
long term care facilities must install and
maintain automatic sprinkler systems.
Comment: A commenter suggested
that, instead of requiring all long term
care facilities to install an automatic
sprinkler system, we should permit
such facilities an exemption if they have
all of the following features: Smoke
detectors, mattresses that meet certain
fire safety requirements, and
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
upholstered furniture that meets certain
fire safety requirements.
Response: The fire safety measures
noted above are valuable tools for
enhancing fire safety in long term care
facilities. However, none of these
features serve the same purpose as an
automatic sprinkler system, which is to
actively suppress a fire once it is
ignited. Thus, we do not believe the
suggested options achieve the same
level of fire safety as automatic
sprinklers.
Comment: A commenter suggested
that we should include regulatory
language that endorses standardization
and provides for system
interconnectivity.
Response: We are not clear regarding
the commenter’s suggestion. If the
commenter is referring to the
standardization of installation and
maintenance requirements, we believe
that referencing the NFPA installation
and maintenance standards does
endorse standardization of fire safety
across long term care facilities.
Comment: Many commenters
submitted comments regarding the
placement of smoke alarms in long term
care facilities. In September 2006 we
published a final rule requiring all
unsprinklered long term care facilities
to, at minimum, install and maintain
battery-operated smoke alarms in all
resident rooms and common areas. In
the October 2006 proposed sprinkler
rule, we proposed to add a sunset date
to this smoke alarm requirement. The
smoke alarm requirement would,
according to our proposal, cease to be
effective on the phase-in date of the
sprinkler requirement. Many
commenters disagreed with our
proposal to add a sunset date to the
smoke alarm requirement. Furthermore,
many of these commenters stated that
all long term care facilities should be
required to have both automatic
sprinkler systems throughout their
buildings and smoke alarms in resident
rooms and common areas. Conversely,
several commenters agreed with our
proposal to add a sunset provision to
the smoke alarm requirement. Of these
commenters, many requested that the
sunset date be flexible for individual
long term care facilities. These
commenters suggested that, rather than
having a single sunset date, the final
rule should state that a long term care
facility is no longer required to meet the
smoke alarm provision as soon as it
installs and begins using an automatic
sprinkler system. Additionally, one
commenter sought clarification of the
relationship between the CMS smoke
alarm requirement and the smoke alarm
requirement of the 2000 edition of the
PO 00000
Frm 00054
Fmt 4700
Sfmt 4700
Life Safety Code that long term care
facilities are required to meet.
Response: The proposed smoke alarm
sunset provision appears to have caused
significant confusion and concern, and
we thank the commenters for the
opportunity to clarify our intent. The
smoke alarm requirements of paragraph
(a)(7) apply only to unsprinklered or
partially sprinklered long term care
facilities. This final rule will require all
facilities to be fully sprinklered. Thus,
there will no longer be any facilities that
are unsprinklered or partially
sprinklered. Since (a)(7) applies only to
unsprinklered or partially sprinklered
facilities, it will be a moot requirement.
Nonetheless, we believe that it is
appropriate to retain the requirements of
paragraph (a)(7) until the end of the 5year phase-in period. At the end of this
period we will consider proposing a
rule which would delete both this
provision and reference to the phase-in
period.
Moreover, facilities that are required
to have smoke alarms or smoke
detection systems in accordance with
the requirements of the 2000 edition of
the LSC as incorporated by reference in
paragraph § 483.70(a)(1) must continue
to comply with those existing LSC
standards.
A significant number of commenters
advocated for smoke alarms and/or
smoke detection systems in all long
term care facilities, even those that have
automatic sprinkler systems throughout
their buildings. All long term care
facilities may consider installing smoke
detection systems in their facilities in
addition to installing automatic
sprinkler systems. We may consider the
appropriateness of such a requirement
in future rulemaking.
Comment: We received a large
number of public comments regarding
the appropriate length of a phase-in
period for the sprinkler installation
requirement. Commenter suggestions for
the length of the phase-in period ranged
from as little as 18 months to as long as
15 years. The most frequently suggested
phase-in period was 3–5 years. Other
commenters made more general
recommendations such as ‘‘the sooner
the better’’ and ‘‘sooner rather than
later.’’ Additionally, many commenters
suggested that nursing homes should be
allowed phase-in waivers on a case-bycase basis to provide additional time to
those nursing homes who make a good
faith effort to comply within the stated
timeframe, but who do not do so. One
commenter suggested that we include
an additional requirement that long
term care facility owners file a statement
with CMS detailing their intent to
E:\FR\FM\13AUR1.SGM
13AUR1
hsrobinson on PROD1PC76 with RULES
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
comply with the final rule within 180
days of publication of the final rule.
Response: We agree with commenters
that a phase-in period is necessary to
allow long term care facilities sufficient
time to purchase and install automatic
sprinkler systems throughout their
buildings. While we recognize that a
relatively short phase-in period (such as
18 months-3 years) will rapidly increase
the level of fire safety in long term care
facilities, we believe such a short time
frame will not allow facilities enough
time to comply with the provisions of
this final rule. Re-allocating and/or
securing financial resources, securing
the services of a system designer and
installation contractor, purchasing
system components, securing any
necessary permits, completing ancillary
projects, and completing the actual
installation process can take a
substantial amount of time. We do not
believe an 18-month to 3-year phase-in
period allows enough time for all of
these tasks to be completed in all
affected facilities. Furthermore, we do
not believe it is appropriate to allow
waivers of this important requirement.
Likewise, we do not believe it will be
appropriate to allow long term care
facilities 7 or more years to install
automatic sprinkler systems, as some
commenters suggested. While such a
lengthy phase-in period will allow more
than ample time for facilities to
complete the installation process, it may
also unnecessarily encourage facilities
to postpone this much-needed fire
safety improvement. In light of these
considerations, we are finalizing a 5year phase-in period. A long term care
facility has 5 years from the date of
publication of this final rule to purchase
and install a fully-operational automatic
sprinkler system throughout its
building. A 5-year phase-in period
balances our dual goals of improved fire
safety and feasibility. It ensures that
facilities begin planning for installation
within a short period of time from the
publication of this final rule and allows
sufficient time for all facilities to
complete the full installation process.
Comment: Numerous commenters
submitted comments regarding the exact
fire safety codes that should be used in
long term care facilities. Many of these
commenters supported our proposal to
require facilities to meet the
requirements of the 1999 edition of
NFPA 13 and the 1998 edition of NFPA
25. Some of the commenters suggested
that we require facilities to meet more
recent editions of the NFPA standards.
Other commenters questioned the role
of the building codes issued by the
International Code Council (ICC). Of
these commenters, some suggested that
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
we require facilities to meet the ICC
codes in place of the NFPA codes.
Others suggested that States, local
jurisdictions, and/or facilities be given
the option to meet either the NFPA or
ICC codes.
Response: While we agree that more
recent editions of NFPA sprinkler codes
or sprinkler codes issued by other codesetting bodies may include appropriate
installation and maintenance
requirements for automatic sprinkler
systems in long term care facilities, we
believe it is most appropriate to require
long term care facilities to comply with
the 1998 and 1999 editions of the NFPA
sprinkler codes. If we require facilities
to meet more recent editions of the
sprinkler codes, we could be placing
them out of compliance with the
provisions of the 2000 edition of the
LSC. Similarly, if we were to require or
permit facilities to meet another
sprinkler code issued by a separate
code-setting body, the standards could
be incompatible with the 2000 edition
of the LSC. We do not believe this will
be in the best interest of facilities and
their residents.
Comment: A substantial number of
commenters submitted thoughts in
response to our discussion of potentially
adopting the 2006 edition of the LSC,
which requires existing long term care
facilities to install automatic sprinkler
systems. Commenters were nearly
evenly divided in their support of or
opposition to adopting the 2006 LSC.
The commenters who supported
adopting the 2006 LSC stressed that this
edition is the most recent version and
has the potential to increase fire safety
levels in all health care facilities. The
commenters who did not support
adopting the 2006 LSC cited potential
delays in implementing the automatic
sprinkler requirement and overall
facility burden as key factors in their
recommendation.
Response: The 2006 edition of the
LSC made numerous changes to the
requirements applicable to long term
care facilities. The most substantial
change in the 2006 LSC is the
requirement that all long term care
facilities must have automatic sprinkler
systems. However, since we are
addressing that issue in this rulemaking,
we do not believe it should affect our
evaluation of the overall merits of the
2006 LSC. We do not believe that the
other changes in the 2006 edition of the
LSC offers substantial improvements in
the level of fire safety in long term care
facilities that outweigh the additional
burden to facilities of complying with
the requirements of a newer edition of
the LSC at this time. Therefore, we are
not adopting the 2006 edition of the LSC
PO 00000
Frm 00055
Fmt 4700
Sfmt 4700
47081
at this time. We will continue to
participate in the NFPA consensus
process as the NFPA revises and refines
subsequent editions of the LSC.
Additionally, we will carefully examine
the 2009 edition of the LSC when it is
published for possible incorporation by
reference in our regulations governing
long term care facilities and a variety of
other health care provider types.
IV. Provisions of the Final Regulations
In this final rule we are adopting the
provisions as set forth in the October 27,
2006 proposed rule with the following
revisions:
• Deleted proposed § 483.70(a)(7)(iv),
the sunset provision.
• Added a 5-year phase-in date to
§ 483.70(2)(8)(i).
V. Collection of Information
Requirements
Under the Paperwork Reduction Act
of 1995, we are required to provide 30day notice in the Federal Register and
solicit public comment before a
collection of information requirement is
submitted to the Office of Management
and Budget (OMB) for review and
approval. In order to fairly evaluate
whether an information collection
should be approved by OMB, section
3506(c)(2)(A) of the Paperwork
Reduction Act of 1995 requires that we
solicit comment on the following issues:
• The need for the information
collection and its usefulness in carrying
out the proper functions of our agency.
• The accuracy of our estimate of the
information collection burden.
• The quality, utility, and clarity of
the information to be collected.
• Recommendations to minimize the
information collection burden on the
affected public, including automated
collection techniques.
We solicited public comment on each
of these issues for the following sections
of this document that contain
information collection requirements:
In summary, § 483.70(a)(8)(ii) requires
that all long term care facilities test,
inspect, and maintain an approved,
supervised automatic sprinkler system
in accordance with the 1998 edition of
NFPA 25, Standard for the Inspection,
Testing, and Maintenance of WaterBased Fire Protection Systems. This
section states that facilities will be
required by this proposed rule to
comply with all applicable chapters of
NFPA 25 once they have installed their
sprinkler systems in accordance with
the requirements of NFPA 13.
We believe facilities will utilize the
services of a contractor for all
inspection, testing, and maintenance
activities, including documentation of
E:\FR\FM\13AUR1.SGM
13AUR1
47082
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
those activities. Therefore, no burden
will be associated with the development
of the documentation. The burden
associated with this requirement, is the
time and effort necessary for facilities to
maintain documentation of inspections,
tests, and maintenance activities in
accordance with the standards outlined
in the NFPA 25.
The burden associated with these
requirements is estimated to be 1 hour
per long term care facility. Therefore,
we estimate it will take 2,446 total
annual hours (1 hour × 2,446 estimated
affected long term care facilities) to
satisfy this burden.
These requirements are not effective
until they are approved by OMB.
VI. Regulatory Impact Analysis
hsrobinson on PROD1PC76 with RULES
A. Overall Impact
We have examined the impacts of this
rule as required by Executive Order
12866 (September 1993, Regulatory
Planning and Review), the Regulatory
Flexibility Act (RFA) (September 16,
1980, Pub. L. 96–354), section 1102(b) of
the Social Security Act, the Unfunded
Mandates Reform Act of 1995 (Pub. L.
104–4), Executive Order 13132 on
Federalism, and the Congressional
Review Act (5 U.S.C. 804(2)).
Executive Order 12866 directs
agencies to assess all costs and benefits
of available regulatory alternatives and,
if regulation is necessary, to select
regulatory approaches that maximize
net benefits (including potential
economic, environmental, public health
and safety effects, distributive impacts,
and equity). A regulatory impact
analysis (RIA) must be prepared for
major rules with economically
significant effects ($100 million or more
in any 1 year). We have examined this
rule, and we have determined that this
rule would meet the criteria to be
considered economically significant,
and it would meet the criteria for a
major rule. This determination is based
on 2,446 long term care facilities being
required to install automatic sprinkler
systems at an estimated cost of $7.95 per
square foot, for a total cost of about $847
million over the 5-year phase-in period.
Hence, in any one year costs in excess
of $100 million will be incurred
regardless of the decisions of individual
facilities as to when to make the
investment.
The estimated cost for installing a
sprinkler system throughout an existing
average size unsprinklered facility
(50,000 square feet to be sprinklered at
$7.95 per square foot) will be $397,500.
Because these systems are capital
investments, their costs are properly
amortized over time in estimating their
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
impact on facility finances. We believe
that a reasonable estimate of the useful
life of a sprinkler system is 20 years.
The projected installation cost of this
requirement will account for
approximately one fourth of one percent
of an average unsprinklered facility’s
actual revenue over a 20-year period.
The estimated cost for installing a
sprinkler system throughout an existing
average size partially sprinklered
facility (37,125 square feet to be
sprinklered at $7.95 per square foot)
will be $295,143. The projected
installation cost of this requirement will
account for approximately one fifth of
one percent of an average partially
sprinklered facility’s actual revenue
over a 20-year period.
The RFA requires agencies to analyze
options for regulatory relief of small
entities. For purposes of the RFA, small
entities include small businesses,
nonprofit organizations, and small
government jurisdictions (including
tribal governments). Individuals and
States are not included in the definition
of a small entity. For purposes of the
RFA, most long term care facilities are
considered to be small entities, either by
virtue of their nonprofit or government
status or by having revenues of less than
$12.5 million in any one year. The latest
SBA size standards classify a ‘‘Nursing
Care Facility’’ under North American
Industry Classification System (NAICS)
as code 623110, and as ‘‘small’’ if its
annual revenues fall below $12.5
million (for details, see the Small
Business Administration’s Table of
Small Business Size Standards at
https://www.sba.gov/idc/groups/public/
documents/sba_homepage/
serv_sstd_tablepdf.pdf.) According to
our statistics, long term care facilities,
all of which will be required to have
sprinkler systems throughout their
buildings, received a total of $124.9
billion in revenue in 2006 (National
Health Expenditures Accounts, https://
www.cms.hhs.gov/
NationalHealthExpendData/
02_NationalHealth
AccountsHistorical.asp). Also according
to CMS data, there were 15,941 nursing
facilities in operation at that time. The
average facility therefore had annual
revenue of $7.8 million and thus fell
well below the SBA size threshold.
Taking into account both typical
revenue, and that non-profit facilities of
any size are ‘‘small entities’’ within the
meaning of the RFA, we assume for
purposes of our analysis that all LTC
facilities are ‘‘small entities’’ for
purposes of the RFA. Although the
average LTC facility has revenues well
below the SBA size threshold, we have,
PO 00000
Frm 00056
Fmt 4700
Sfmt 4700
as described in what follows, also
analyzed impacts on entities that fall
even farther below the size threshold.
(Note: In the following paragraphs the
terms ‘‘average facility’’ and ‘‘smaller
facility’’ are strictly based on a revenue
metric, just as are most of the SBA size
thresholds, including that for NAICS
code 623110. That is, the terms only
describe facilities in terms of the
amount of annual revenue.)
Long term care facilities vary in a
number of ways, ranging from the
number of residents to the predominant
source of payment for those residences.
For the purposes of our analysis, we
chose to assess the financial impact of
this final rule on a facility with average
revenue and a facility with a much
smaller revenue (50 percent below the
mean). An average facility had
approximately $7,837,714 in revenue in
2006. A facility with revenue 50 percent
below this average received $3,918,857,
or less than one third of the amount set
by SBA to define ‘‘small.’’ Over the 20year amortization period revenues of an
average facility will be about $157
million. The ‘‘smaller’’ facility will have
revenues of about $78 million over the
same 20-year amortization period. We
calculate that the projected cost of this
requirement will account for about one
fourth of one percent of an average
unsprinklered ‘‘smaller’’ facility’s actual
revenue over the 20-year period. Taking
into account their smaller size and
lower investment cost, the projected
cost of this requirement will account
about one fifth of one percent of a
partially sprinklered ‘‘smaller’’ facility’s
actual revenue over the 20-year period.
We are assuming that a smaller facility’s
square footage and number of beds are
50 percent less than an average facility’s
square footage because there is a strong
correlation between the size of a facility,
as reflected by the number of resident
beds it has, and the facility’s revenue
level. According to CMS data from
December 2007, there (see Table 3 later
in this analysis) the median bed size of
LTC facilities is about 100 beds, and
there are 433 unsprinklered or partially
sprinklered long term care facilities that
have fewer than 50 beds and
presumably meet our revenue definition
of a ‘‘smaller facility.’’ Hence, there are
relatively few very small (‘‘smaller’’)
facilities that will be affected by this
rule. That said, a total of about 2,446
unsprinklered or partially sprinklered
facilites will be affected, and the great
majority of these (we assume all) are
‘‘small entities’’ under the RFA (again,
see Table 3 for the size distribution of
affected entities).
As a result of these calculations, and
because we normally only regard an
E:\FR\FM\13AUR1.SGM
13AUR1
hsrobinson on PROD1PC76 with RULES
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
impact that reaches several percent of
annual revenue as ‘‘significant’’ under
the RFA, we certify that this final rule
would not have a significant impact on
a substantial number of small entities.
However, some facilities may face
financing or other problems that
concentrate the impact and make its
effect proportionally much larger than
would otherwise be the case. While we
do not believe that there would be a
substantial number of facilities in this
circumstance, we have prepared a
voluntary regulatory flexibility analysis.
This Regulatory Impact Analysis
section, taken together with the
remainder of the preamble, constitutes
this analysis.
In addition, section 1102(b) of the Act
requires us to prepare a regulatory
impact analysis if a rule may have a
significant impact on the operations of
a substantial number of small rural
hospitals. This analysis must conform to
the provisions of section 604 of the
RFA. For purposes of section 1102(b) of
the Act, we define a small rural hospital
as a hospital that is located outside of
a metropolitan statistical area and has
fewer than 100 beds. We know that 8.41
percent of long term care facilities,
1,332 nationwide, are located in
hospitals, but we do not know how
many of those hospitals are small rural
hospitals. However, it is likely that the
affected number is quite small.
Applying the same percentages that
apply to the long term care universe to
the 1,332 long term care facilities
located in hospitals, we estimate that
1,125 are fully sprinklered, 176 are
partially sprinklered, and only 31 are
not sprinklered. Using these estimates
and the preceding cost amortization
calculations, we have concluded that
this final rule will not have a significant
impact on the operations of a substantial
number of small rural hospitals and that
a regulatory flexibility analysis is not
required. Our voluntary analysis,
however, applies equally to facilities
regardless of location or affiliation and
hence covers hospital-based facilities.
Section 202 of the Unfunded
Mandates Reform Act of 1995 (UMRA)
also requires that agencies assess
anticipated costs and benefits before
issuing any rule whose mandates
require spending in any one year by
either the private sector or by State,
local, and tribal governments of $100
million in 1995 dollars, updated
annually for inflation. That threshold
level is currently approximately $130
million. This final rule does contain
mandates that will impose annual
spending costs on private long term care
facilities of $154 million, and on public
long term care facilities of $16 million,
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
based on an estimated cost of about
$847 million distributed over a 5-year
phase-in period, for an average annual
cost of about $170 million for all public
and private facilities. Estimated impacts
on State, local, and tribal governments
are well below the UMRA threshold,
since over ninety percent of long term
care facilities are privately owned, as
shown the Federalism analysis that
follows. With respect to private sector
facilities, this Regulatory Impact
Section, together with the remainder of
the preamble, constitutes the analysis
required under UMRA.
Note: For a more detailed discussion of the
cost estimates, see part B.2 of this section.)
In the proposed rule we estimated that this
rule would cost $47.8 to $69.9 million, $73.5
to $107.5 million, and $107.7 to $157.6
million annually. These estimates were based
on example phase-in periods of 10 years, 7
years, and 5 years, and cost-per-square-foot
estimates of $4.10, $5.50, and $6.10,
respectively. We sought public comment on
the length of an appropriate phase-in period,
and received suggestions ranging from 18
months to 15 years. The most frequently
suggested phase-in period was 3–5 years. We
selected the longer phase-in period, 5 years,
to help mitigate the impact of this rule upon
long term care facilities. We also increased
our cost-per-square-foot estimates to reflect
increases in construction costs that have
occurred since publication of the proposed
rule.
Executive Order 13132 establishes
certain requirements that an agency
must meet when it promulgates a final
rule that imposes substantial direct
compliance costs on State or local
governments, preempts State law, or
otherwise has Federalism implications.
Of the 2,446 facilities that will be
affected by this final rule, 216 facilities
(8.83 percent of all affected facilities)
are owned by State and local
governments. The majority of these
facilities (188) are already partially
sprinklered. Of the 188 partially
sprinklered facilities, 31 have less than
50 resident beds, 43 have 50–99 resident
beds, 63 have 100–199 resident beds,
and 49 have 200 or more resident beds.
We estimate that it will cost on average
about $14.24 million annually for 5
years to install sprinklers throughout
the unsprinklered portions of these
facilities. Of the remaining 30
completely unsprinklered facilities, 13
have less than 50 resident beds, 8 have
50–99 resident beds, 7 have 100–199
resident beds, and 2 have 200 or more
resident beds. We estimate that it will
cost on average about $2.12 million
annually for 5 years to install sprinklers
throughout these unsprinklered
facilities. The total of these annual
average cost estimates, about $16
million, is negligible in the context of
PO 00000
Frm 00057
Fmt 4700
Sfmt 4700
47083
overall State and local budgets and as a
capital expense can be financed over a
period of years by borrowing. Therefore,
we believe that this final rule will not
impose substantial direct compliance
costs on State or local governments, and
thus has no Federalism implications.
B. Anticipated Effects
1. Benefits
a. Decreasing Loss of Life
We believe that installing an
approved, supervised automatic
sprinkler system in accordance with
NFPA 13, Standard for the Installation
of Sprinkler Systems, throughout a long
term care facility will have a positive
impact on resident safety. According to
the July 2004 GAO report discussed
above, installing sprinklers decreases
the chances of fire-related deaths by 82
percent. In unsprinklered facilities,
there are 10.8 deaths per 1,000 fires. In
sprinklered facilities, there are 1.9
deaths per 1,000 fires.
The 2003 fires in Hartford and
Nashville resulted in more fire related
deaths (31) than there were for several
previous years combined. Both of these
fires occurred in unsprinklered
buildings. If sprinklers had been
installed in these facilities, and if they
were properly maintained, we estimate
that 82 percent of those fire-related
deaths may have been prevented, based
on an 82 percent reduction in the
chances of death occurring in a
sprinklered facility. We estimate that,
based on this reduction, 25 (82 percent
of 31 deaths = 25) lives could have been
saved by sprinklers in these two fires, or
13 lives in the Hartford fire and 12 lives
in the Nashville fire.
According to the U.S. Census Bureau,
in 2006, the average age of a long term
care facility resident was 83.2 years.
This number reflects the overall
demographic trend in long term care
facilities toward an older patient
population. In 2003 (the most recent
year of data available), the average life
expectancy for an individual at age 85
was 6.6 years (Older Americans Update
2006: Key Indicators of Well-Being.
Federal Interagency Forum on AgingRelated Statistics. https://
www.agingstats.gov/agingstatsdotnet/
Main_Site/Data/2006_Documents/
Health_Status.pdf). This means that an
85-year-old long term care facility
resident could expect to live an average
of 6.6 more years. We acknowledge that
the average age of a long term care
facility resident (83.2 years) is slightly
younger than the 85 year data point
used to assess average life expectancy;
however, we believe that using the life
expectancy of an 85 year old is an
E:\FR\FM\13AUR1.SGM
13AUR1
47084
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
acceptable proxy for the life expectancy
of an 83.2 year old.
Based on a life expectancy at age 85
of 6.6 years, we estimate that sprinklers
in these two fires would have added 165
life years (25 lives saved × 6.6 life years
per life saved).
While the number of deaths in these
two fires is not typical of the number of
fire-related deaths in long term care
facilities as a whole, we believe that
they should still be taken into
consideration when discussing the
impact on the general long term care
facility resident population.
In a typical year from 1994 through
1999, about 2,300 long term care
facilities report structural fires (July
2004 GAO report). We estimate that 25
percent (575) of the 2,300 facilities that
reported fires annually during the 1994–
1999 time period did not have
sprinklers installed throughout their
buildings. This estimate is based on the
results of the 2004 GAO report and a
nationwide survey of long term care
facilities conducted by CMS following
the results of the GAO report.
Based on the rate of 10.8 deaths per
1,000 unsprinklered facility fires, we
estimate that 6 deaths occurred in 575
fires in unsprinklered and partially
sprinklered facilities annually. (575
facilities = 57.5 percent of 1,000
facilities; 57.5 percent of 10.8 deaths =
6 deaths). This estimate differs slightly
from the average number of deaths (5)
that occurred due to long term care
facility fires, as presented in the July
2004 GAO report, because this estimate
predicts the number of deaths that
statistically would be expected to occur,
based on established percentages, rather
than the average number of deaths that
occurred annually in the past. This
estimate is prospective, whereas the
2004 GAO figure is retrospective.
If these unsprinklered or partially
sprinklered facilities install sprinklers
throughout their buildings and those
sprinklers are properly maintained, then
we estimate that there will be 1 death
(57.5 percent × 1.9 deaths per 1,000
fully sprinklered facility fires according
to the 2004 GAO report = 1) in those
same 575 facilities. Installing sprinklers
in unsprinklered and partially
sprinklered buildings would, based on
these estimates, save 5 lives annually.
TABLE 1—ESTIMATED ANNUAL FIRE DEATHS
Number of estimated annual fire-related
deaths in unsprinklered long term care
facilities
Number of estimated annual fire-related
deaths if those facilities were sprinklered
Number of estimated annual lives saved by
sprinklers
6
1
5
Given the estimate described above
that installing and maintaining sprinkler
systems in existing long term care
facilities will save 5 lives annually, we
estimate that sprinklers will save 33 life
years annually (5 lives saved × 6.6 years
gained per life).
the value of a statistical life and derived
from this figure values of between
$213,000 (at a 3 percent discount rate)
and $373,000 (at a 7 percent discount
rate) for a quality adjusted life-year
(QALY). (See the FDA Final Rule on
‘‘Medical Devices: Patient Examination
and Surgeon’s Gloves; Test Procedures
and Acceptance Criteria,’’ December 19,
2006, 71 FR 75865, as corrected January
19, 2007, 72 FR 2436.) These are
intended to be rough estimates of
societal willingness to pay for saving a
‘‘statistical life’’ (not a particular person)
or for adding a year of life that does not
involve total disability. It is not a settled
issue in the literature of valuation of life
as to how well these estimates fit an
elderly population, and we use them
here only to provide a rough estimate as
to one of the major benefits of this final
rule in the same dollar metric as costs.
Applying these estimates, the lifesaving benefits of this final rule once all
facilities are compliant will be
approximately $25 million dollars
annually based on a value of $5 million
per statistical life saved. These benefits
accrue over the entire 20-year horizon
during which automatic sprinkler
systems save lives. Hence, undiscounted
future benefits from life saving would be
as much as $500 million ($5 million
times 5 lives times 20 years).
There are additional life-year benefits,
to the extent that residents who survive
a fire are nonetheless physically injured
in ways that that greatly reduce their
future quality of life. For example, a
person who spends months in the
hospital recovering from burn injuries
and the remainder of his life partially
incapacitated by those injuries, or a
person whose lungs are permanently
damaged by smoke inhalation, do not
have the same good health that they
would have enjoyed absent the fire. We
do not have at this time any basis for
estimating the amount of severe
morbidity caused by facility fires that
sprinklers can mitigate, but it could be
very substantial, likely approaching and
perhaps exceeding the number of lifeyears lost to mortality. For purposes of
this analysis, we assume that it equals
the mortality QALYs, and that total
benefits from morbidity reduction range
from $7 to $10 million a year (33 life
years times 20 years time either
$213,000 or $373,000).
The FDA estimates were based on a
‘‘willingness to pay’’ analysis of wage
differentials necessary to attract labor to
riskier occupations. Such analyses have
shown that people demand significantly
higher wages to accept even a small
additional risk of death. The estimated
value of an additional year of life is
based on life expectancy in the FDA
analysis. However, there are other ways
to create such estimates and many
studies have done so. For example, an
estimate using data on rural interstate
highway driving speeds found that the
value of a statistical life could be
estimated as between $1.6 and $5.9
million (Orley Ashenfelter, ‘‘Measuring
the Value of a Statistical Life: Problems
TABLE 2—LIFE YEARS
Number of life years
gained annually
6.6
hsrobinson on PROD1PC76 with RULES
Number of life years
gained per life saved
33
There are a wide variety of estimates
regarding the statistical value of a life or
of a quality-adjusted life year. For
example, there are numerous studies
that attempt to quantify how much
individuals and society are willing to
pay to gain a single, quality year of life,
known as a quality-adjusted life year.
These studies, using one or more of four
different methodologies, have estimated
that individuals and society are willing
to pay between $50,000 and $450,000
for a quality-adjusted life year (see R.A.
Hirth, et al, ‘‘Willingness to Pay for
Quality-Adjusted Life Year: In Search of
a Standard,’’ Medical Decision Making,
Volume 20, Number 3, July–Sep. 2000).
Due to the fact that there is no widely
accepted standard value, we refrained in
the proposed rule from estimating the
statistical value of each life or life year
that will be gained as a result of a final
rule requiring sprinklers in all long term
care facilities. However, a recent FDA
rule used an estimate of $5 million as
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
PO 00000
Frm 00058
Fmt 4700
Sfmt 4700
E:\FR\FM\13AUR1.SGM
13AUR1
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
hsrobinson on PROD1PC76 with RULES
and Prospects,’’ Working Paper 11916,
National Bureau of Economic Research,
January 2006). As another example, a
recent study of the willingness to pay
for better health care found that a
reasonable estimate of the value of a
QALY lies between $183,000 and
$264,000 per life year (R. Scott
Braithwaite, et al, ‘‘What Does the Value
of Modern Medicine Say About the
$50,000 per Quality-Adjusted Life-Year
Decision Rule?,’’ Medical Care, Volume
46, Number 4, April 2008). Thus, the
estimates used by the FDA, and in this
CMS analysis, are broadly consistent
with estimates from other sources, such
as the Hirth and Braithwaite studies.
The reasonableness of applying such
estimates to an elderly population is
unclear, particularly when that
population is, by definition, at least
temporarily unable to live outside an
institutional setting. However, the
general approach used most often in the
literature is to use the same value of a
statistical life for persons of all ages. As
to value of a life-year, there is
considerable evidence in the literature
that the kinds of disabilities most
commonly found in nursing homes,
such as mobility and mental
impairments, do not substantially
reduce the value of a life-year (see
Chaim M. Bell, et al, ‘‘An Off-the-Shelf
Help List: A comprehensive Catalog of
Preference Scores from Published CostUtility Analyses,’’ Medical Decision
Making, Volume 21, Number 4, JulyAugust 2001). For example, on a scale
of zero to 1, where zero is represented
by a persistent vegetative state and 1 is
best attainable health, this synthesis
shows that disability after a hip fracture
is rated at .8, and even after major stroke
from .2 to .5. Absent a compelling
rationale to the contrary, we therefore
use the full values of a statistical life
and a QALY in our analysis.
A few commenters questioned our
methodology for assessing the potential
life-saving benefits of installing and
maintaining automatic sprinkler
systems. However, these commenters
did not suggest an alternate method for
assessing these potential benefits.
Therefore, we reaffirm the methodology
and results described above.
b. Decreasing Loss of Property
As a result of installing and properly
maintaining sprinklers, we anticipate
that facilities that experience fires
would lose less property. While the
amount of property damage and loss
that would be prevented by installing
and maintaining sprinklers is not
readily quantifiable from existing data,
we believe that the amount of damage
prevented will be substantial, and that
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
this prevention will benefit affected
long term care facilities.
Preventing property damage and loss
may also reduce the amount of money
paid by insurers to cover fire-related
losses. Such reductions may help
control long term care facility insurance
costs and reduce any spill-over effect for
other insurance markets. Again, these
benefits are not easy to estimate reliably
from existing data. However, we believe
that they should be considered as part
of the overall analysis of the benefits of
purchasing, installing, and maintaining
automatic sprinkler systems in long
term care facilities.
For purposes of estimating overall
benefits and costs, we believe that an
estimate of about $26 million a year
would not be unreasonable. We base
this on the following calculations. First,
as previously discussed there are
approximately 2,300 structural fires
annually in long term care facilities, a
rate of about one fire per every seven
facilities. However, we estimate that the
number of fires in unsprinklered or
partially sprinklered facilities is far
higher, with these 2,446 facilities
accounting for one fourth of all
structural fires, or about one fire per
every four such facilities (575 fires in
2,446 facilities). Assuming that the rate
could be reduced to the 13 percent rate
in fully sprinklered facilities (1,725 fires
in 13,495 facilities), approximately 260
structural fires a year would be
prevented. We have no specific data for
estimating the dollar cost of fighting
these fires and restoring the properties,
but assuming illustratively that the
average cost of a structural fire is
$100,000, total annual savings would be
on the order of $26 million a year.
c. Decreasing Fire Recovery Disruption
and Time
In addition to losing less property due
to fire, we anticipate that long term care
facilities that experience fires will be
able to recover more quickly with fewer
disturbances to residents. Because
sprinkler heads generally activate only
in the area immediately near the fire
source, the area that will be damaged by
a fire will likely be much smaller in a
sprinklered building than it would be in
a building without sprinklers, thus
reducing recovery costs. In addition, by
limiting the area affected by the fire,
there would be fewer disturbances to
residents during the recovery time. In
particular, fewer residents would be
forced into a change in residence, a
disruption that often affects residents’
physical and mental well-being
severely. Finally, by limiting the
affected area and duration of disruption,
an affected facility will reduce the
PO 00000
Frm 00059
Fmt 4700
Sfmt 4700
47085
number of paid patient-days that it
loses. While we cannot quantify most of
these benefits to long term care facilities
and their residents, we believe that they
are substantial. Assuming illustratively
that they equal half the cost of a fire
prevented, annual savings would be on
the order of $6.5 million a year.
d. Decreasing Legal Liability and
Insurance Cost
As a result of installing sprinklers,
facilities will greatly reduce their
potential exposure to legal costs and
legal damages, as well as reduce their
costs for liability insurance. Again, we
cannot quantify these benefits but they
could be very substantial. For example,
were a court to find that a facility was
negligent either in not installing a stateof-the-art system, or in being unable to
save residents who would have been
saved had such a system been in place,
tort liability could be imposed. Absent
any way to predict what might occur
(which might depend, for example, not
only on specific factual circumstances
but also on the tort law in the state in
which such a fire might occur), we do
not estimate the dollar value of these
benefits.
e. Reducing Major Medical Care Costs
Fires cause morbidity as well as
mortality. Not all residents who suffer
deadly burns die immediately.
Treatment of severely burned persons is
among the most expensive kinds of
medical care. Other effects of fires that
require medical treatment include
smoke inhalation and injuries cause by
falls when fleeing from rooms affected
by fire or smoke. No data are available
to us on the extent of these medical
costs, and hence on costs prevented by
this final rule, but they are likely to be
substantial. Assuming illustratively that
there are ten expensive medical care
cases prevented for each death
prevented by this rule, and that such
cases average $100,000, annual benefits
would be $5 million (5 × 10 × $100,000).
2. Costs
This final rule requires a long term
care facility to install an approved,
supervised automatic sprinkler system
in accordance with NFPA 13, Standard
for the Installation of Sprinkler Systems,
throughout the building. This final rule
also allows long term care facilities to
install automatic sprinkler systems over
a 5-year phase-in period.
Number and Size of Affected Facilities
Following publication of the GAO
report, CMS incorporated a data
collection element on the long term care
facility survey form. When completing a
E:\FR\FM\13AUR1.SGM
13AUR1
47086
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
survey, a long term care facility
surveyor must note whether the facility
is fully sprinklered, partially
sprinklered, or unsprinklered. Based on
data collected during the survey
process, we know that 13,391 facilities
are fully sprinklered, 2,086 facilities are
partially sprinklered, and 360 facilities
are unsprinklered. The following table
groups the partially and unsprinklered
facilities by the number of beds.
TABLE 3—NUMBER OF AFFECTED FACILITIES BY SIZE
<50 beds
hsrobinson on PROD1PC76 with RULES
Partially sprinklered .........................................................................................
Unsprinklered ...................................................................................................
The number of resident beds in a
facility strongly corresponds to its
physical size. Simply put, larger
buildings have more resident beds, and
smaller buildings have fewer resident
beds. Therefore, based on the number of
beds in a facility, we are able to estimate
the square footage of a long term care
facility. For purposes of our analysis, we
estimate that a long term care facility
has 500 total square feet for each
resident bed. This estimate, which
includes space for the resident’s room,
community spaces, and administrative
spaces, is based on discussions with
architects and engineers who are
familiar with the design of older long
term care facilities. Therefore, for
purposes of our analysis, an average
facility with fewer than 50 beds is
24,500 sq ft, 50–99 beds is 37,000 sq ft,
100–199 beds is 74,500 sq ft, and 200+
beds is 99,501 sq ft. When estimating
the cost of installing an automatic
sprinkler system in an unsprinklered
facility, we use these square footage
estimates.
However, these estimates do not
reflect the area that must still be
sprinklered in a partially sprinklered
long term care facility. By definition, a
partially sprinklered facility already has
an automatic sprinkler system in one or
more sections of the facility. For
purposes of this impact analysis, we
assume that a partially sprinklered
building is 25 percent sprinklered,
leaving 75 percent of the building to be
sprinklered in accordance with this
final rule. Buildings in this category
may have more or less sprinkler
coverage than this assumption.
For facilities with fewer than 50
resident beds, we estimate that
sprinklers will be installed for 18,375
square feet (75 percent of maximum
square footage in this size category). For
facilities with 50 to 99 resident beds, we
estimate that sprinklers will be installed
for 27,750 square feet (75 percent of
average square footage in this size
category). For facilities with 100 to 199
resident beds, we estimate that
sprinklers will be installed for 55,875
square feet (75 percent of average square
footage in this size category). For
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
315
118
facilities with more than 199 resident
beds, we estimate that sprinklers will be
installed for 75,000 square feet (75
percent of minimum square footage in
this size category).
a. Installation Cost per Square Foot
Purchasing and installing a sprinkler
system according to the requirements of
NFPA 13 encompasses a wide variety of
factors, including those briefly
described in section II of this final rule.
Within the requirements of NFPA 13,
there are numerous variables that can
impact the purchase and installation
costs for a facility. Each facility has
different needs that must be addressed
when purchasing and installing a
sprinkler system, and this cost estimate
cannot address each particular need or
combination of needs. Therefore, we are
basing our cost estimates not on the
individual requirements of NFPA 13 for
an individual facility, but on a bundled
purchase and installation estimate for
an average facility, as described below.
Individual facilities may have costs
above or below those of this average
facility due to facility size and facilityspecific sprinkler system needs. Long
term care facilities that are based in
other health care facilities, such as
hospitals, are required by this final rule
only to have sprinklers in the long term
care facility section of the building.
Therefore, we do not believe that
facility-based long term care facilities
will have different installation costs
than freestanding facilities with similar
resident bed and square footage
numbers.
We estimate that it will cost $7.95 per
square foot to purchase and install a
sprinkler in an existing facility.
According to the Architects,
Contractors, Engineers Guide to
Construction Costs, 2008 Edition by
Design and Construction Resources,
purchasing and installing sprinklers in
new long term care facilities costs $2.65
per square foot. This cost estimate
incorporates all contractor costs such as
labor, materials, and a 20 percent
overhead fee; 35 percent taxes and
insurance on labor, equipment, and
tools; and 5 percent sales tax.
PO 00000
Frm 00060
Fmt 4700
Sfmt 4700
50–99 beds
675
128
100–199 beds
870
102
200+ beds
226
12
Although we recognize that capital
and interest costs may increase the cost
of purchasing and installing automatic
sprinkler systems in long term care
facilities, these costs are not included in
our estimates. Due to the individual
circumstances of each facility, unknown
future interest rates, and various other
factors, we are unable to accurately
estimate the capital and interest costs of
installing sprinkler systems. Therefore,
we have chosen to exclude these costs
from our estimates while acknowledging
that they do exist and will play a role
to some degree in the decisions of long
term care facilities that will be affected
by this final rule. Note, however, that
the economic costs of financing this
capital investment would not be the
gross cost of borrowing, but the much
smaller opportunity cost of the capital
devoted to sprinklers rather than some
other investment. Furthermore, to the
potentially substantial extent that
facilities gain from this investment
(reduced disruption, revenue loss, etc.
as previously discussed) the
opportunity cost may be very low.
Renovation costs are typically two to
three times higher than new
construction costs because installing the
sprinkler system must be completed in
a piecemeal fashion while the building
remains occupied. This increases the
length of the construction time and,
thus, increases its costs. In addition,
renovations to add sprinkler systems
often require upgrading or adding
related building components such as
water lines and fire pumps. The
upgrades and additions require more
capital investment and construction
time. Increased investment and
construction time also increases costs.
For purposes of this impact analysis,
we assume that renovating a typical
facility to add sprinklers would cost
three times more than purchasing and
installing sprinklers in new long term
care facilities. In the proposed rule, we
presented a range of cost per square foot
estimates from two to three times the
costs of installation in a new building.
Commenters indicated that the lower
estimates in this range did not reflect
the actual costs incurred by existing
E:\FR\FM\13AUR1.SGM
13AUR1
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
long term care facilities. Therefore, we
eliminated the lower range and only use
the highest estimate (three times the
cost of installing sprinklers in new
construction, $7.95).
b. Cost Estimates
The cost estimates for both
unsprinklered and partially sprinklered
facilities are presented in the following
tables. They are based on all of the
above-described estimates about the
number of facilities that would be
47087
affected, the sizes of those facilities, and
the installation cost per square foot. We
estimate that this final rule will cost
$846,680,105 over the 5-year phase-in
period, or an average of $169,336,021
annually for 5 years for all affected
partially sprinklered and unsprinklered
long term care facilities.
TABLE 4—ONE-TIME INSTALLATION COST FOR PARTIALLY SPRINKLERED FACILITIES AT $7.95 PER SQUARE FOOT BY SIZE
>50 beds
(18,375 sq ft to be
sprinklered)
Cost per facility ........................................................................
Number of affected facilities ....................................................
Cost for all facilities .................................................................
50–99 beds
(27,750 sq ft to be
sprinklered)
100–199 beds
(55,875 sq ft to be
sprinklered)
200+ beds
(75,000 sq ft to be
sprinklered)
$146,081
315
$46,015,515
$220,613
675
$148,913,775
$444,206
870
$386,459,220
$596,250
226
$134,752,500
TABLE 5—ONE-TIME COST FOR UNSPRINKLERED FACILITIES AT $7.95 PER SQUARE FOOT BY SIZE
>50 beds
(24,500 sq ft to be
sprinklered)
Cost per facility ........................................................................
Number of affected facilities ....................................................
Cost for all facilities .................................................................
50–99 beds
(37,000 sq ft to be
sprinklered)
100–199 beds
(74,500 sq ft to be
sprinklered)
00+ beds
(99,501 sq ft to be
sprinklered)
$194,775
118
$22,983,450
$294,150
128
$37,651,200
$592,275
102
$60,412,050
$791,033
12
$9,492,395
TABLE 6—TOTAL ONE-TIME INSTALLATION COST FOR ALL FACILITIES BY SIZE
>50 beds
50–99 beds
100–199 beds
200+ beds
$46,015,515
22,983,450
$148,913,775
37,651,200
$386,459,220
60,412,050
$134,752,500
9,492,395
Total ..................................................................................
hsrobinson on PROD1PC76 with RULES
Partially sprinklered .................................................................
Unsprinklered ...........................................................................
68,998,965
186,564,975
446,871,270
144,244,895
We do not expect all affected long
term care facilities to have all necessary
resources immediately available to
purchase and install automatic sprinkler
systems. Therefore, we are allowing all
facilities up to five years from the date
of publication of this final rule to
purchase and install sprinklers. While
we will encourage all facilities to
immediately begin the process of
purchasing and installing sprinklers, we
understand that some facilities will
choose to wait until later in the phasein period to begin this process.
Therefore, we expect that the one-time
cost of this final rule will be distributed
over a period of several years as
facilities nationwide will likely stagger
their installation schedules to meet their
individual needs and circumstances. We
estimate that long term care facilities
will spend, on average, $169,336,021
annually for five years to purchase and
install automatic sprinkler systems
throughout their facilities.
c. Maintenance
After installing an approved,
supervised automatic sprinkler system
in accordance with the 1999 edition of
NFPA 13 throughout the building, all
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
long term care facilities must test,
inspect, and maintain their sprinkler
systems in accordance with the 1998
edition NFPA 25. We estimate that long
term care facilities will conduct
quarterly inspections of their sprinkler
systems and annual trip tests. We
assume that each inspection will take 4
hours to complete, at a cost of $150 per
inspection. We also assume that each
trip test will take 6 hours, at a cost of
$250. Based on these assumptions, we
estimate that long term care facilities
will spend $850 annually to test and
inspect their sprinkler systems. In
addition, we assume that long term care
facilities will spend an additional $150
annually to perform any necessary
maintenance duties.
Individuals who perform these
testing, inspection, and maintenance
duties will have to be properly trained
and, in some States and local
jurisdictions, they will have to be
licensed. Generally, long term care
facilities will not have enough sprinkler
system work needs to directly employ
someone with the necessary skills,
training, and licensure. Therefore, we
believe that long term care facilities will
PO 00000
Frm 00061
Fmt 4700
Sfmt 4700
likely contract with another company to
meet their testing, inspection, and
maintenance needs. However, long term
care facilities are not required by this
rule to contract for these services. In
addition to actually conducting the
necessary testing, inspection, and
maintenance activities, we believe that
a contract will also include a provision
that the contractor prepares adequate
documentation of the activities
conducted. We estimate that the total
cost of meeting these requirements will
be $1,000 ($150 × 4 quarterly
inspections = $600 + $250 annual trip
test + $150 general maintenance costs =
$1,000). We estimate that the total
maintenance cost for all affected
facilities will be $2,446,000. We
recognize that some commenters
suggested that this estimate is not
sufficient to capture the cost of
maintaining an automatic sprinkler
system. However, the commenters did
not suggest a more suitable method for
assessing the potential maintenance
costs or a more suitable dollar estimate
for such costs. Therefore, we reaffirm
our original estimates.
E:\FR\FM\13AUR1.SGM
13AUR1
47088
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
hsrobinson on PROD1PC76 with RULES
In addition, all long term care
facilities that will be affected by this
final regulation are required to maintain
documentation of all inspection,
maintenance, and testing activities. The
burden associated with these
requirements is estimated to be 1 hour
per long term care facility. Therefore,
we estimate it will take 2,446 total
annual hours (1 hour × 2,446 estimated
affected long term care facilities) to meet
this requirement. This documentation
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
maintenance requirement will cost an
affected facility $19 a year, based on an
hourly rate of $19 for an office employee
($19 per hour × 1 hour). The total
annual cost of this final documentation
requirement will be $46,474 ($19 per
facility × 2,446 facilities).
3. Summary of Estimated Costs and
Benefits
Taking into account all these
categories of benefits and costs, and
PO 00000
Frm 00062
Fmt 4700
Sfmt 4700
their timing, we believe that this final
rule creates a substantial excess of
benefits over costs at a social discount
rate of 3 percent and a slight excess of
benefits over costs at 7 percent. As
shown in the table, costs are heavily
concentrated in the first five years (we
assume one-fifth is invested in each of
the five years allowed for compliance)
while benefits accrue over the entire
20-year life of these investments.
E:\FR\FM\13AUR1.SGM
13AUR1
VerDate Aug<31>2005
17:08 Aug 12, 2008
Jkt 214001
PO 00000
Frm 00063
Fmt 4700
Sfmt 4700
..................
1
2
3
4
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
90
..................
..................
Statistical
lives saved
..................
6.6
13.2
19.8
26.4
33
33
33
33
33
33
33
33
33
33
33
33
33
33
33
33
594
..................
..................
Life years
saved from
mortality
reduction
..................
6.6
13.2
19.8
26.4
33
33
33
33
33
33
33
33
33
33
33
33
33
33
33
33
594
..................
..................
Life years
saved from
morbidity
reduction
..................
5
10
15
20
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
450.0
..................
..................
Monetized
statistical
lives
($M)
7%
1
3
4
6
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
126.5
3%
..................
Monetized
morbidity
reduction
($M)*
Benefits
..................
5
13
16
21
26
26
26
26
26
26
26
26
26
26
26
26
26
26
26
26
470.6
..................
..................
Decreasing
loss of
property
($M)
....................
2.6
6.5
7.8
10.4
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
235.3
....................
....................
Decreasing
fire recovery
disruption
and time
($M)
..................
1
2
3
4
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
90.0
..................
..................
Reducing
major
medical
costs
($M)
TABLE 7—TOTAL FIRE SPRINKLER SYSTEM COSTS AND BENEFITS
722.4
15.2
34.3
45.6
60.8
76.0
76.0
76.0
76.0
76.0
76.0
76.0
76.0
76.0
76.0
76.0
76.0
76.0
76.0
76.0
76.0
1,372.4
991.4
................
Total
benefits
($M)
* Estimate at 3% discount rate, shown in table, uses a value of $213,000 per QALY; estimate at 7% uses a value of $373,000 per QALY.
1 .....................................
2 .....................................
3 .....................................
4 .....................................
5 .....................................
6 .....................................
7 .....................................
8 .....................................
9 .....................................
10 ...................................
11 ...................................
12 ...................................
13 ...................................
14 ...................................
15 ...................................
16 ...................................
17 ...................................
18 ...................................
19 ...................................
20 ...................................
Undiscounted Total ........
Net Present Value at 3%
Discount Rate ................
Net Present Value at 7%
Discount Rate* ...........
Year
hsrobinson on PROD1PC76 with RULES
....................
169
169
169
169
169
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
845.0
....................
....................
Installation
($M)
......................
0.5
1.0
1.5
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
45.0
......................
......................
Maintenance
($M)
Costs
715.0
169.5
170.0
170.5
171.0
171.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
890.0
806.4
..............
Total
costs
($M)
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
E:\FR\FM\13AUR1.SGM
13AUR1
47089
hsrobinson on PROD1PC76 with RULES
47090
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
The Office of Management and Budget
has stated that the value of a statistical
life could be put anywhere between $1
and $10 million (in practice a number
as low as $1 million is almost never
used). Clearly using the lower end of
this range would greatly reduce the
benefits of this final rule, and using the
higher end would greatly increase those
benefits. Broad (though not equally
broad) ranges of comparisons could be
made for most categories of benefits.
However, only if the most conservative
possible estimates were used for almost
every category of benefits would total
discounted benefits fall below
discounted costs at a discount rate of 3
percent. Therefore, we have chosen not
to present a detailed sensitivity analysis.
Our installation cost estimates, in
contrast, do not pose remotely as wide
a range of possibilities. In our view we
have estimated these quite
conservatively, and actual costs could
easily be ten or twenty percent lower
than the estimates we use. For example,
the five year compliance horizon we
provide means that many facilities will
be able to combine sprinkler installation
with other major renovations such that
the cost of sprinkler installation will be
considerably less. In fact, during the
next five years it is quite likely that a
considerable fraction of long term care
providers in the older facilities most
affected by this final rule will for
unrelated business reasons decide to
move to new facilities and dispose of
their older facility buildings. We have
not attempted to estimate the effects of
such estimate-reducing actions.
Finally, there is an alternative way to
estimate and present the effects of this
rule. Approaching these estimates from
the perspective of cost-effectiveness
analysis (CEA), Table 7 shows that we
estimate a total of 1,188 undiscounted
life years saved from both mortality and
morbidity reductions. Subtracting from
total monetary costs the monetary
benefits from reduced property damage,
disruption, and medical costs, the net
undiscounted costs are $94.1 million.
Undiscounted, the cost per life-year
saved is $79,000. Discounting both life
years and costs to present value, the cost
per life-year saved would be $270,000 at
a 3 percent discount rate, and $553,000
at a 7 percent discount rate. These
results are markedly sensitive to the
discount rate because the benefits of the
rule accrue roughly evenly over time,
while the costs are highly concentrated
in the early years. Despite the fact that
this mostly elderly population has
relatively few years of life expectancy
compared to an average population,
even at a 7 percent discount rate the
cost per life-year saved, while higher
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
than the most widely used values for a
QALY, is within the range of accepted
‘‘willingness to pay’’ values (e.g., the
Hirsch study published in 2000 presents
$450,000 as an accepted value, which
adjusted for inflation roughly equals our
estimate of $553,000).
C. Alternatives Considered
1. Maintain Current Fire Safety
Requirements
We currently require long term care
facilities to comply with the fire safety
requirements in the LSC. In addition,
we currently require long term care
facilities that do not have sprinklers
installed throughout the building to
have and maintain at least battery
operated smoke alarms in resident
rooms and public areas. We believe that
these requirements are a solid
foundation for ensuring that all long
term care facility residents are protected
from the threat of fire.
We also believe that these current
measures do not go far enough to protect
long term care facility residents. Both
the Hartford and Nashville facilities
were in substantial compliance with the
LSC, yet both facilities experienced
severe fires with large numbers of
fatalities.
The smoke alarm requirement that we
published in the Federal Register on
March 25, 2005 (70 FR 15229) after
these fires was a step toward improving
fire safety and avoiding another
devastating fire. Unfortunately, single
station smoke alarms can only warn
facility staff and residents of the fire.
They cannot suppress a fire or prevent
it from spreading to other areas.
Long-term care facility residents often
have multiple or severe health problems
that complicate the facility’s ability to
ensure their safety in the event of a fire.
For example, frail elderly residents may
rely on facility staff to assist them in
transferring and otherwise moving about
the facility. These types of residents are
unable to independently protect
themselves from the threat of fire by
moving away from the danger. They are
dependent on facility staff, who are also
responsible for ensuring the safety of
dozens of other residents. A rapidly
growing fire can overwhelm both the
staff and residents, leading to tragic
consequences.
However, a properly designed,
installed, and maintained sprinkler
system effectively prevents a fire from
spreading to other areas and
overwhelming the staff and residents.
Containing a fire reduces the threat to
residents in other portions of the
building and allows facility staff to
focus their energy on the area that is
PO 00000
Frm 00064
Fmt 4700
Sfmt 4700
most affected by the fire, without worry
about the fire spreading to other areas
and threatening other residents.
Sprinkler systems have consistently
served this function for many years, and
they are commonly recognized as the
single most effective fire safety device
currently available.
Given the past success of sprinkler
systems and their potential for saving
lives in the future, we believe that
maintaining the existing fire safety
requirements without adding sprinkler
requirements does not ensure the safety
of long term care facility residents to the
greatest extent possible.
In addition, maintaining the existing
fire safety requirements will have left
decisions regarding more stringent fire
safety measures in the hands of State
and local governments. State and local
governments have, in the past, made
very different decisions about fire safety
requirements in long-term care facilities.
For example, some States, such as
Tennessee and Virginia, already require
all long-term care facilities to have
sprinklers throughout their buildings. In
contrast, other States, such as South
Dakota, Michigan, and the District of
Columbia, do not have such
requirements, resulting in almost 50
percent or more of their long-term care
facilities lacking sprinklers throughout
their buildings. This level of variability
is not acceptable because residents of
long-term care facilities should be
assured the same minimum level of fire
safety regardless of what State or
locality they reside in. Federal
regulation is the most efficient and
expedient manner for achieving the goal
of uniform nationwide minimum fire
safety standards; therefore, we chose to
pursue Federal regulation rather than
depending on State and local
governments.
2. Exempt Smaller Facilities
The Medicare Conditions of
Participation are the minimum
requirements that providers are required
to meet in order to be Medicare and
Medicaid certified. Many other
standards setting organizations have
requirements that go beyond what
Medicare and Medicaid require.
Facilities may choose to strive for these
higher standards, although Medicare
and Medicaid do not require them to do
so.
Exempting any facility from this final
minimum requirement will be a
disservice to the residents of that
facility. Residents deserve to be safe
from the threat of fire, whether they
reside in a large facility or a smaller one.
The final sprinkler requirement will
ensure that, regardless of the size or
E:\FR\FM\13AUR1.SGM
13AUR1
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
hsrobinson on PROD1PC76 with RULES
location of their residence, all residents
are protected by the same basic
minimum fire safety requirements.
However, we did consider whether
there might be some size or other
threshold creating a ‘‘cut off’’ point
below which some facilities might be
exempted on the grounds that the cost
of sprinkler installation is prohibitively
expensive in relation to the number of
residents to be protected. We were
unable to identify any such threshold
from the GAO study, our own analysis,
or the comments we received. To the
contrary, it appears that there is a linear
or near linear relationship among
facility revenue, facility size, number of
facility residents, and cost of installing
automated sprinkler systems. Nor are
there any data suggesting that risk or
rates of fire vary with facility size. The
one certainty is that automated sprinkler
systems are the most certainly effective
method of preventing and controlling
expansion of fires.
We believe that the 5-year phase-in
period will substantially help to
mitigate the costs of installing sprinklers
for small facilities by providing
substantial flexibility to coordinate
sprinkler decisions with other business
arrangements, including financing and
renovation decisions. Therefore, we
have no reasonable basis to exempt any
particular type of facility, including
smaller facilities, from this requirement.
3. Require Compliance in Less Than or
More Than Five Years
Requiring compliance with this final
rule in less than five years would, we
believe, be a hardship for affected long
term care facilities. Allocating
resources, designing a sprinkler system,
purchasing it, obtaining necessary
permits, installing it, and testing it all
require a significant amount of time. In
15 states, 20% or more of all long term
care facilities will be required to go
through this process, potentially
increasing the wait time permit
applications and for the availability of
qualified system designers and
installers. For these reasons, and to
provide flexibility to coordinate with
other business decisions, we have
chosen to allow up to 5 years to
complete this process.
Allowing facilities more than 5 years
to complete the sprinkler process could
encourage facilities to unnecessarily
delay the installation process. Such
delays could unduly jeopardize resident
and staff safety. Therefore, we believe
that a phase-in period of more than five
years would not be in the best interest
of long term care facility resident and
staff safety and would not accomplish
the goals of this final rule.
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
D. Accounting Statement
As Required by OMB Circular A–4
(available at https://
www.whitehouse.gov/omb/circulars/
a004/a-4.pdf), in Table 7 below, we
have prepared an accounting statement
showing the classification of the costs
and benefits associated with the
provisions of this final rule. This table
is based on our best estimate of the
undiscounted total cost of $845 million,
over a five year phase in period, for the
2,446 long term care facilities being
required to install automatic sprinkler
systems at an estimated cost of $7.95 per
square foot, plus an additional $45
million undiscounted for maintenance
costs of about $2.5 million annually.
After discounting to present value, total
costs are estimated to be $806 million at
a 3 percent discount rate, and $715
million at a 7 percent discount rate. The
table also reflects total benefits of $1,372
million undiscounted, $991 million
discounted to present value at 3 percent,
and $722 million discounted to present
value at 7 percent.
TABLE 7—ACCOUNTING STATEMENT
Primary
estimate
($M)
Category
Monetized Costs ($ Millions):
Total Cost Over 20-Year Period (PV at 0% discount
rate) ...................................
Total Cost Over 20-Year Period (PV at 3% discount
rate) ...................................
Total Cost Over 20-Year Period (PV at 7% discount
rate) ...................................
Monetized Benefits:
Total Benefits (PV at 0% discount rate) .........................
Total Benefits (PV at 3% discount rate) .........................
Total Benefits (PV at 7% discount rate) .........................
$890
806
715
1372
991
722
E. Conclusion
We estimate that this regulation will
result in private sector expenditures of
$846,680,105, over a 5-year phase-in
period, or $169,336,021 annually for 5
years, to purchase and install automatic
sprinkler systems throughout affected
long-term care facilities. We also
estimate that this regulation will result
in private sector expenditures of
$2,492,474 ($2,446,000 for maintenance
+ $46,474 for documentation) annually
to maintain those automatic sprinkler
systems. While the effects of this
regulation are substantial, they are
necessary to protect the safety of longterm care facility residents and staff.
PO 00000
Frm 00065
Fmt 4700
Sfmt 4700
47091
In accordance with the provisions of
Executive Order 12866, this regulation
was reviewed by the Office of
Management and Budget.
List of Subjects in 42 CFR Part 483
Grant programs—health, Health
facilities, Health professions, Health
records, Incorporation by Reference,
Medicaid, Medicare, Nursing homes,
Nutrition, Reporting and recordkeeping
requirements, Safety.
I For the reasons set forth in the
preamble, the Centers for Medicare &
Medicaid Services amends 42 CFR
chapter IV as set forth below:
PART 483—REQUIREMENTS FOR
STATES AND LONG-TERM CARE
FACILITIES
1. The authority citation for part 483
continues to read as follows:
I
Authority: Secs. 1102 and 1871 of the
Social Security Act (42 U.S.C. 1302 and
1395hh).
Subpart B—Requirements for LongTerm Care Facilities
2. In § 483.70, add new paragraph
(a)(8) to read as follows:
I
§ 483.70
Physical environment.
(a) * * *
(8) A long term care facility must:
(i) Install an approved, supervised
automatic sprinkler system in
accordance with the 1999 edition of
NFPA 13, Standard for the Installation
of Sprinkler Systems, as incorporated by
reference, throughout the building by
August 13, 2013. The Director of the
Office of the Federal Register has
approved the NFPA 13 1999 edition of
the Standard for the Installation of
Sprinkler Systems, issued July 22, 1999
for incorporation by reference in
accordance with 5 U.S.C. 552(a) and 1
CFR part 51. A copy of the Code is
available for inspection at the CMS
Information Resource Center, 7500
Security Boulevard, Baltimore, MD or at
the National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/
code_of_federal_regulations/
ibr_locations.html. Copies may be
obtained from the National Fire
Protection Association, 1 Batterymarch
Park, Quincy, MA 02269.
(ii) Test, inspect, and maintain an
approved, supervised automatic
sprinkler system in accordance with the
1998 edition of NFPA 25, Standard for
the Inspection, Testing, and
Maintenance of Water-Based Fire
E:\FR\FM\13AUR1.SGM
13AUR1
47092
Federal Register / Vol. 73, No. 157 / Wednesday, August 13, 2008 / Rules and Regulations
Protection Systems, as incorporated by
reference. The Director of the Office of
the Federal Register has approved the
NFPA 25, Standard for the Inspection,
Testing, and Maintenance of WaterBased Fire Protection Systems, 1998
edition, issued January 16, 1998 for
incorporation by reference in
accordance with 5 U.S.C. 552(a) and 1
CFR part 51. A copy of the Code is
available for inspection at the CMS
Information Resource Center, 7500
Security Boulevard, Baltimore, MD or at
the National Archives and Records
Administration (NARA). For
information on the availability of this
material at NARA, call 202–741–6030,
or go to: https://www.archives.gov/
federal_register/
code_of_federal_regulations/
ibr_locations.html. Copies may be
obtained from the National Fire
Protection Association, 1 Batterymarch
Park, Quincy, MA 02269.
*
*
*
*
*
(Catalog of Federal Domestic Assistance
Program No. 93.778, Medical Assistance
Program) (Catalog of Federal Domestic
Assistance Program No. 93.773, Medicare—
Hospital Insurance; and Program No. 93.774,
Medicare—Supplementary Medical
Insurance Program)
Dated: March 6, 2008.
Kerry Weems,
Acting Administrator, Centers for Medicare
& Medicaid Services.
Approved: May 6, 2008.
Michael O. Leavitt,
Secretary.
[FR Doc. E8–18670 Filed 8–8–08; 3:30 pm]
BILLING CODE 4120–01–P
DEPARTMENT OF THE INTERIOR
Fish and Wildlife Service
50 CFR Part 21
[FWS–R9–MB–2007–0012; 91200–1231–
9BPP]
RIN 1018–AV35
Migratory Bird Permits; Revisions to
Migratory Bird Import and Export
Regulations
Fish and Wildlife Service,
Interior.
ACTION: Final rule.
hsrobinson on PROD1PC76 with RULES
AGENCY:
SUMMARY: We, the U.S. Fish and
Wildlife Service, change the regulations
governing migratory bird permitting. We
amend 50 CFR part 21 to allow the
export of lawfully-acquired, captivebred raptors without obtaining a
migratory bird export permit; to resolve
problems related to export of species
VerDate Aug<31>2005
15:55 Aug 12, 2008
Jkt 214001
Background
therefore difficult to read and
understand.
We proposed revisions to the
regulations governing import and export
of migratory birds on November 19,
2007 (72 FR 64981). Among other
things, we wanted to: Address the
export of species covered by CITES;
allow the export of lawfully-acquired,
captive-bred raptors without an export
permit; allow the importation and
possession without a migratory bird
import permit of legally-acquired
migratory game birds in the families
Anatidae, Columbidae, Gruidae,
Rallidae, and Scolopacidae that were
lawfully hunted in a foreign country;
extend the maximum time for which a
migratory bird import and export permit
is valid from 3 to 5 years; and reorganize
and reword the regulations to make
them easier to understand. We revised
the proposed regulations to address
comments we received, but we made no
major changes to the proposed rule.
The U.S. Fish and Wildlife Service is
the Federal agency that has been
delegated the responsibility to carry out
the Migratory Bird Treaty Act (MBTA)
(16 U.S.C. 703 et seq.), which
implements conventions with Great
Britain (for Canada), Mexico, Japan, and
the Soviet Union (Russia). Raptors
(birds of prey) are afforded Federal
protection by the 1972 amendment to
the Convention for the Protection of
Migratory Birds and Game Animals,
February 7, 1936, United States-Mexico,
as amended; the Convention between
the United States and Japan for the
Protection of Migratory Birds in Danger
of Extinction and Their Environment,
September 19, 1974; and the Convention
Between the United States of America
and the Union of Soviet Socialist
Republics (Russia) Concerning the
Conservation of Migratory Birds and
Their Environment, November 26, 1976.
Among other things, we manage the
import and export of migratory birds
and their parts, eggs, and nests. The
regulations at 50 CFR 21.21 set forth the
requirements for import and export
permits for migratory birds and their
parts, eggs, and nests, including
requirements for import and export
permits, application procedures for
these permits, additional permit
conditions, and the term for which a
permit is valid. These regulations are 18
years old and are, in part, outdated. In
particular, these regulations do not
mention the requirements associated
with CITES, addressed in part 23 of our
regulations. In addition, many of the
requirements currently set forth at
§ 21.21 simply reference another part or
section of our regulations. They are
Changes in the Migratory Bird Import
and Export Regulations
General requirements (§ 21.21(a)):
Current § 21.21(a) provides the general
requirements for import and export
permits, as well as the exceptions to
these requirements. We reorganize
current § 21.21 to separate the general
requirements (§ 21.21(a)) from the
exceptions to the requirements
(§ 21.21(b), (c) and (d)). In § 21.21(a), we
acknowledge all of the regulations,
including the CITES regulations at 50
CFR part 23, that apply to imports and
exports of migratory birds and their
parts, eggs, and nests. These revisions
will help ensure that importers and
exporters of migratory birds or their
parts, eggs, or nests understand all the
requirements applicable to their imports
and exports.
Exceptions for import permits
(§ 21.21(b)): Current § 21.21(a)(1)
provides the requirements for import
permits; it does not provide any
exceptions to import permit
requirements for migratory birds or their
parts, eggs, or nests. Current
§ 21.21(a)(2) does have one import
permit exception for raptors for falconry
that will be discussed later in this
document. We add, in a new § 21.21(b),
a provision to allow the importation and
possession without an import permit of
migratory game birds in the families
Anatidae, Columbidae, Gruidae,
Rallidae, and Scolopacidae that were
lawfully hunted in a foreign country.
The imported specimens can be
carcasses, skins, or mounts. They must
be accompanied by evidence of lawful
export from the country of origin and by
any other necessary permits, such as a
covered by Convention on International
Trade in Endangered Species of Wild
Fauna and Flora (CITES) permits or
certificates; to allow the importation
and possession without an import
permit of legally-acquired migratory
game birds in the families Anatidae,
Columbidae, Gruidae, Rallidae, or
Scolopacidae that were lawfully hunted
in a foreign country; to extend the
maximum time for which an import and
export permit is valid from 3 to 5 years;
and to reorganize and reword the
regulations to make them easier to
understand.
This rule is effective on
September 12, 2008.
DATES:
Dr.
George T. Allen, Division of Migratory
Bird Management, U.S. Fish and
Wildlife Service, 703–358–1825.
SUPPLEMENTARY INFORMATION:
FOR FURTHER INFORMATION CONTACT:
PO 00000
Frm 00066
Fmt 4700
Sfmt 4700
E:\FR\FM\13AUR1.SGM
13AUR1
Agencies
[Federal Register Volume 73, Number 157 (Wednesday, August 13, 2008)]
[Rules and Regulations]
[Pages 47075-47092]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: E8-18670]
=======================================================================
-----------------------------------------------------------------------
DEPARTMENT OF HEALTH AND HUMAN SERVICES
Centers for Medicare & Medicaid Services
42 CFR Part 483
[CMS-3191-F]
RIN 0938-AN79
Medicare and Medicaid Programs; Fire Safety Requirements for Long
Term Care Facilities, Automatic Sprinkler Systems
AGENCY: Centers for Medicare & Medicaid Services (CMS), HHS.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: This final rule requires all long term care facilities to be
equipped with sprinkler systems by August 13, 2013. Additionally, this
final rule requires affected facilities to maintain their automatic
sprinkler systems once they are installed.
DATES: These regulations are effective on October 14, 2008. The
incorporation by reference listed in the rule is approved by the
Director of the Federal Register October 14, 2008.
FOR FURTHER INFORMATION CONTACT: Danielle Shearer, (410) 786-6617;
James Merrill, (410) 786-6998; Marcia Newton, (410) 786-5265; or
Jeannie Miller, (410) 786-3164.
SUPPLEMENTARY INFORMATION:
I. Background
A. Overview of the Life Safety Code
The Life Safety Code (LSC), published by the National Fire
Protection Association (NFPA), a private, nonprofit organization
dedicated to reducing loss of life due to fire, is a compilation of
fire safety requirements. The LSC contains fire safety requirements for
both new and existing buildings. It is updated through a consensus
process and generally published every 3 years. Sections 1819(d)(2)(B)
and 1919(d)(2)(B) of the Social Security Act (the Act) require that
long term care facilities participating in the Medicare and Medicaid
programs generally meet the applicable provisions of the edition of the
LSC that is adopted by the Secretary.
Beginning with the adoption of the 1967 edition of the LSC in 1971,
Medicare and Medicaid regulations have historically incorporated the
LSC requirements by reference for all long term care facilities as well
as other providers, while providing the opportunity for a Secretarial
waiver of a requirement under certain circumstances. The statutory
basis for incorporating NFPA's LSC for our other providers is under the
Secretary's general rulemaking authority at sections 1102 and 1871 of
the Act, and under provider-specific provisions of title XVIII that
permit us to issue regulations to protect the health and safety of
participants in Medicare and Medicaid.
We adopted the LSC to ensure that patients and residents are
consistently protected from fire, regardless of the location in which
they receive care. Since adopting and enforcing the 1967 and subsequent
editions of the LSC, there has been a significant decline in the number
of multiple death fires, indicating that the LSC has been effective in
improving fire safety in health care facilities.
On October 26, 2001, we published a proposed rule (66 FR 54179),
and on January 10, 2003, we published a final rule in the Federal
Register, entitled ``Fire Safety Requirements for Certain Health Care
Facilities'' (68 FR 1374). In that final rule, we adopted the 2000
edition of the LSC provisions as the standard governing Medicare and
Medicaid health care facilities, including long term care facilities.
The final rule required all existing long term care facilities to
comply with the 2000 edition of the LSC.
The 2000 edition of the LSC required all newly constructed
buildings containing health care facilities to have an automatic
sprinkler system installed throughout the building. However, like all
previous editions, the LSC did not require existing buildings to
install automatic sprinkler systems throughout if they met certain
construction standards, ranging from the size of the buildings to the
types of material used in their construction.
In accordance with the 2000 edition of the LSC, an existing
building that meets the above-mentioned construction standards must
install sprinklers if it undergoes a major renovation. However, in such
cases, it is required to install sprinklers only in the renovated
section(s). Therefore, a building may have sprinklers only on one floor
or in one wing. We did not receive any timely public comments in
response to the October 2001 proposed rule that addressed the issue of
installing automatic sprinkler systems in buildings not undergoing
major renovations. That is to say, no public comments supported,
questioned or challenged our proposal to incorporate this LSC provision
by reference.
In the 2006 edition of the LSC, the NFPA decided to include an
automatic sprinkler system requirement for all long term care
facilities. We support the NFPA in its decision. We decided to proceed
with this rule, without proposing adoption of the NFPA 2006 edition of
the LSC, because we want to avoid further delay in requiring an
automatic sprinkler system in long term care facilities. As stated in
the October 27, 2006 proposed rule (71 FR 62957, 62960), given the
large scope of the LSC, we would not be able to adopt and enforce
compliance with the 2006 edition of the LSC until 2009 or 2010.
Therefore, we decided at this time to proceed with rulemaking that does
not include adoption of the NFPA 2006 LSC.
We will continue to work with the NFPA to revise and refine each
edition of the LSC. We are currently working with the NFPA through its
consensus process to revise and refine the 2009 edition of the LSC.
Once the 2009 edition is issued, we will review the code in its
entirety and explore the possibility of adopting it for all
[[Page 47076]]
Medicare and Medicaid-participating health care facilities.
B. Recent Fire Safety Developments
A Government Accountability Office (GAO) report entitled ``Nursing
Home Fire Safety: Recent Fires Highlight Weaknesses in Federal
Standards and Oversight'' (GAO-04-660, July 16, 2004, https://
www.gao.gov/new.items/d04660.pdf) examined two long term care facility
fires (Hartford and Nashville) in 2003 that resulted in 31 total
resident deaths. The report examined Federal fire safety standards and
enforcement procedures, as well as results from the fire investigations
of these two incidents. The report recommended that fire safety
standards for unsprinklered facilities be strengthened and the report
cited the effectiveness of smoke detectors' and sprinklers' fire
protection features for long term care facilities.
In response to a recommendation made in the GAO report, on March
25, 2005, we published an interim final rule with comment period in the
Federal Register entitled, ``Fire Safety Requirements for Certain
Health Care Facilities; Amendment'' (70 FR 15229). This interim final
rule added paragraph (a)(7) to Sec. 483.70, to require long term care
facilities, at minimum, to install battery-operated smoke detectors in
resident sleeping rooms and public areas, unless they had a hard-wired
smoke detector system in resident rooms and public areas or a sprinkler
system installed throughout the facility. This IFC was finalized
September 22, 2006 (71 FR 55326).
Structural fires in long term care facilities are relatively common
events. From 1994 to 1999, an average of 2,300 long term care
facilities reported a structural fire each year (2004 GAO Report).
Although approximately 2,300 facilities per year reported fires, those
fires resulted in an average of only 5 fatalities nationwide per year
(2004 GAO Report). The likelihood of a fatality occurring due to a long
term care facility fire was quite low.
From 1990 to 2002, there were no fires in long term care facilities
that resulted in more than one or two fatalities. During that time
period there were no fires in long term care facilities that resulted
in a loss of life comparable to that of the Hartford and Nashville
fires.
We believe the low number of fire-related fatalities each year is
attributable, in part, to the increasing use of automatic sprinkler
systems in long term care facilities as a fire protection method. State
and local jurisdictions often adopt an edition of the LSC or a
comparable fire safety code shortly after it is published. Therefore, a
building constructed in the early 1990s likely met the requirements of
the 1991 edition of the LSC or another comparable code. Beginning with
the 1991 edition of the LSC, all newly built facilities were required
to have automatic sprinkler systems. In addition, beginning with the
1991 edition of the LSC, all facilities undergoing major renovations
were also required by the LSC to install automatic sprinkler systems at
least in those renovated areas. Therefore, as new facilities have
replaced old facilities, and as facilities have been renovated, the
number of residents protected by automatic sprinkler systems has
increased. The increase in the number of automatic sprinkler systems
and the number of residents residing in sprinklered buildings has
decreased significantly the likelihood of a fatality occurring due to
fire.
According to NFPA data cited in the 2004 GAO report, there is an 82
percent reduction in the chance of death occurring in a sprinklered
building when compared to the chance of death occurring in an
unsprinklered building. In addition, we note that there has never been
a multiple death fire in a long term care facility that had an
automatic sprinkler system installed throughout the facility.
Automatic sprinkler systems are effective in reducing the risk of
fatalities due to fire because they limit the size of a developing fire
and prevent the fire from growing and spreading beyond the area where
the fire ignited. In addition, impeding the fire's growth gives the
facility staff and residents and the local fire department more time to
respond to the situation.
Automatic fire suppression through sprinklers also alleviates some
of the current heavy reliance on facility staff to implement the
facility's emergency plan. Fires often occur at night, as both the
Hartford and Tennessee fires did, when staffing levels are lowest.
Investigators of the Hartford fire determined that the facility's staff
did not fully implement the facility's emergency plan, which may have
contributed to the number of fatalities in that fire. The 2004 GAO
report concluded that ``reliance on staff response as a key component
of fire protection may not always be realistic, particularly in an
unsprinklered facility.'' Limiting the area of a building affected by a
fire may result in less of a need to evacuate or relocate residents.
The effectiveness of automatic sprinkler systems has prompted some
States, including Virginia, Connecticut, and Tennessee, to require that
all long term care facilities have sprinklers. The NFPA also requires
all long term care facilities to have automatic sprinkler systems as
part of the 2006 edition of the LSC.
II. Provisions of the Proposed Regulations
We published a proposed rule in the Federal Register on October 27,
2006 (71 FR 62957) that would require all long term care facilities to
be equipped with sprinkler systems. That proposed rule also requested
public comments on the duration of a phase-in period to allow such
facilities to install such systems.
For the reasons described in section I of this preamble, we
proposed a rule with three main components. First, the regulation
proposed to add a sunset provision to paragraph (a)(7) in Sec. 483.70
that would correspond to the phase-in date of the sprinkler
requirement. This sunset provision would provide that, as of the phase-
in date, we would no longer enforce the requirement that facilities
have and maintain at least battery-operated smoke alarms. We proposed
to add the sunset date because the requirements of Sec. 483.70(a)(7)
apply only to unsprinklered and partially sprinklered long term care
facilities. Once all long term care facilities are fully sprinklered,
there would not be any unsprinklered or partially sprinklered
facilities to which Sec. 483.70(a)(7) would apply.
Second, we proposed to require every long term care facility to
install an approved, supervised automatic sprinkler system in
accordance with the 1999 edition of NFPA 13, Standard for the
Installation of Sprinkler Systems, throughout the facility if it did
not have such a system already. If a long term care facility was part
of another building, such as a hospital, then the building would be
required to have sprinklers only in the long term care facility
section. The NFPA 13 specifies how to properly design and install
sprinkler systems using the proper components. The standards of NFPA 13
cover a wide variety of factors that are involved in designing and
installing sprinkler systems. The NFPA 13 is divided into 10 main
chapters governing the design and installation phases of automatic
sprinkler systems, and the October 2006 proposed rule summarized the
content of these chapters.
The NFPA 13 is a very detailed document, with a wide variety of
standards and exceptions to those standards. The document provides many
options for the design and
[[Page 47077]]
installation of sprinkler systems so that each system may be tailored
to the building in which it is installed.
Third, the regulation proposed to require every long term care
facility to test, inspect, and maintain an approved, supervised
automatic sprinkler system in accordance with the 1998 edition of NFPA
25, Standard for the Inspection, Testing and Maintenance of Water-Based
Fire Protection Systems. Proper inspections, tests, and maintenance of
sprinkler systems are critical to ensuring that sprinkler systems
function properly on a continuous basis. Fires are, by nature,
unpredictable, and sprinkler systems must be operable at all times to
ensure that buildings are protected whenever and wherever fires occur.
NFPA 25 covers a wide variety of testing, inspection, and maintenance
requirements for the numerous types of sprinkler systems that
facilities may install and the auxiliary equipment that may be
necessary for some facilities. We summarized the content of NFPA 25 in
the proposed rule.
The proposed requirements of this regulation include three
technical terms: ``approved,'' ``automatic,'' and ``supervised.'' These
terms are terms of art in the fire safety community and are included in
NFPA 101, Life Safety Code, with which long term care facilities must
already comply. There may be, however, individuals who are not familiar
with the terms. Their definitions, as used in the fire safety
community, are as follows:
Approved means acceptable to the authority having
jurisdiction (from 2000 edition of NFPA 101, the LSC).
Automatic means that which provides a function without the
necessity of human intervention (from 2000 edition of NFPA 101, the
LSC).
Supervised means that the system and particular components
of the system are monitored by a device with auditory and visual
signals that are capable of alerting facility staff should the system
or one of its components become inoperable for any reason (adapted from
1999 edition of NFPA 13, Standard for the Installation of Sprinkler
Systems).
III. Analysis of and Responses to Public Comments
We received 107 comments from the public on the October 27, 2006
proposed rule. The comments received and our responses to those
comments are discussed below.
Comment: The vast majority of commenters strongly supported our
intent to require automatic sprinkler systems throughout all long term
care facilities. Conversely, a small minority of commenters disagreed
with the proposed rule, citing the expense of purchasing and installing
sprinklers and the availability of other fire safety features such as
water-based fire-proof coatings and fire walls as reasons for not
requiring sprinklers in all long term care facilities.
Response: We appreciate the strong support expressed by most
commenters. While we agree that there are other methods for improving
fire safety in long term care facilities, these other methods do not
achieve the same high level of fire safety as automatic sprinkler
systems. We are proceeding with this final rule requiring all long term
care facilities to install and maintain automatic sprinkler systems
because we agree with the GAO that such systems are the single most
effective fire safety method currently available and that the presence
of such systems will help save lives and property.
Comment: Several commenters submitted comments related to the
specific facilities that are, or should be, affected by this final
rule. One commenter explicitly supported our decision to apply the
proposed sprinkler requirements to all affected long term care
facilities, regardless of their size. Some commenters requested that
this rule be expanded to apply to any residential facility that cares
for individuals on a 24-hour basis. One commenter suggested that the
rule should apply to federally operated nursing homes as well, such as
those operated by the U.S. Department of Veterans Affairs. Another
commenter suggested that the rule should apply to inpatient facilities
such as hospitals and critical access hospitals with swing beds. Still
other commenters asked whether the requirements of the final rule will
affect adult day care centers.
Response: We proposed to require all long term care facilities to
install automatic sprinkler systems regardless of their size because
their recent fire history and current staffing levels indicated the
need for additional fire safety features. We do not believe it is
necessary for us to require sprinkler systems in other facility types,
such as intermediate care facilities, adult day care facilities, or
critical access hospitals at this time because there is no demonstrated
need for such regulation. While we agree that it may be appropriate for
federally operated nursing homes, such as those operated by the U.S.
Department of Veterans Affairs, to install automatic sprinkler systems,
we do not have regulatory authority over these facilities. Therefore,
we are unable to promulgate a regulation applying to them.
Comment: Numerous commenters discussed the financial impact that
the proposed rule will have on long term care facilities, and suggested
a variety of methods to offset the expected impact. Of these
commenters, several suggested that CMS should support legislation in
the Congress that will provide financial incentives for long term care
facilities to install sprinkler systems. A few commenters indicated
that they are actively working with the Congress to obtain financial
assistance for long term care facilities in implementing the
requirements of this final rule. Other commenters suggested that CMS
should make financial assistance available to facilities, with some
suggesting that such assistance should be limited to those facilities
with not-for-profit status or those that are not profitable. Still
another commenter suggested that CMS should compel State Medicaid
programs to increase reimbursement rates to fund capital improvements
in long term care facilities.
Response: We recognize that purchasing and installing an automatic
sprinkler system throughout a long term care facility requires a
substantial capital investment. We defer to the Congress and States to
provide financial assistance to long term care facilities to complete
the purchase and installation process, whether such assistance comes in
the form of loans, grants, tax relief, and/or increased reimbursement
rates.
We have included a 5 year phase-in period in this final rule. This
phase-in period allows facilities the time and flexibility to install
sprinkler systems in a manner that is sensitive to the individual
circumstances of each facility. We believe this phase-in period will
help mitigate the financial impact of this final rule.
Comment: Numerous commenters stated that this final rule should
provide additional discussion of the role that State and locally
imposed building and fire safety codes play in protecting long term
care facility residents.
Response: We acknowledge that State and local authorities use their
authority to require long term care facilities to meet building and
fire safety codes independent of the codes applied to facilities
through Federal regulations. State and local authorities often adopt
more recent editions of such codes than those required by Federal
rules. Until 2003, Federal fire safety regulations referenced
simultaneously Life Safety Code provisions from several editions
including the editions of 1967, 1973, and 1985. However, health care
facilities were not being built to these older standards because State
and local jurisdictions adopted and enforced far
[[Page 47078]]
more recent editions of building and fire safety codes. Such prompt
adoption of updated codes by State and local jurisdictions likely has
led to the large number of long term care facilities that currently
have automatic sprinkler systems throughout their facilities. We
continue to support the right of State and local authorities to impose
building and fire safety codes independent of these Federal
requirements and will continue to monitor all efforts to improve safety
for long term care facility residents.
Comment: Some commenters expressed concern that this final rule
will preempt State and local fire safety requirements. Of these
commenters, a few expressed concern that this Federal rulemaking
preempted State and local efforts and did not respond to the unique
needs of different localities. Furthermore, some of these commenters
requested a more detailed discussion of Executive Order 13132
(Federalism) as it relates to this rulemaking action. Conversely,
several commenters indicated that they agreed with our conclusion that
this rule is in accordance with the actions of State and local
governments, and that it is appropriate for the Federal government to
require automatic sprinkler systems in Medicare and Medicaid-
participating long term care facilities.
Response: The Federal regulations for long term care facilities are
considered to be the minimum standards that a facility must meet in
order to participate in the Medicare and Medicaid programs. As such,
they will not preempt more stringent State and local requirements. For
example, if a State or local authority requires a long term care
facility to install an automatic sprinkler system within 3 years after
adoption of a law requiring it, then a facility must comply with that
shorter time frame, even though this Federal regulation allows a
facility up to 5 years to install an automatic sprinkler system.
However, if a State or local authority requires a long term care
facility to install an automatic sprinkler system only in hazardous
areas, then a facility must go beyond the State or local requirement
and install an automatic sprinkler system throughout its building in
order to participate in Medicare or Medicaid. We believe that all
facilities must install an automatic sprinkler system throughout a
facility by 2013, regardless of the State or locality where a facility
is located. In order to achieve this goal, it is necessary to
promulgate a Federal regulation. State and local jurisdictions have
always had the authority to require automatic sprinkler systems in
existing long term care facilities. However, few States have taken
action to require existing long term care facilities to retrofit their
buildings with such systems. Thus, we believe it is necessary to take
this Federal action.
In addition, this rule adopts the sprinkler installation and
maintenance requirements established by the NFPA. The NFPA is a
national standard setting body with representatives from all members of
the fire safety community, including State and local jurisdictions. As
such, these representatives had active input in the content and
framework of the NFPA sprinkler standards. The standards allow
flexibility in the design, installation, and maintenance of sprinkler
systems to adapt to the needs of individual facilities as well as
jurisdictions. Facilities are required by the NFPA standards to submit
their design and installation plans to the appropriate authorities
having jurisdiction. This allows local and State authorities the
opportunity to ensure that such plans meet their individual needs.
Since this action does not impinge upon a State or local jurisdiction's
authority to impose more stringent fire safety requirements upon long
term care facilities in response to the unique needs and concerns of
the particular area, and gives State and local authorities the
opportunity to provide further input into individual sprinkler planning
activities, we do not believe this final rule has Federalism
implications as described in Executive Order 13132.
Furthermore, we regularly communicate with State and local
officials and with the long term care provider community through Open
Door Forums, as well as through responses to letters, informal phone
calls, and informal e-mails. Through these communications, as well as
through the public comment process for this proposed rule, we believe
we have sufficiently consulted with all affected parties, including
State and local jurisdictions, as is required by Executive Order 13132.
Comment: Several commenters submitted views regarding the
assumptions and estimates we used in the impact analysis for the
proposed rule. Commenters questioned our estimates of the cost per
square foot, the projected number of facilities affected, and the
projected number of lives saved.
Response: We appreciate the suggestions that we received, and we
considered them as we revised the impact analysis for this final rule.
The final impact analysis reflects an increase in our estimate of the
cost per square foot, from a high of $6.10 to a high of $7.95, to
reflect inflation since the publication of the proposed rule. The final
analysis also revises the number of facilities that are affected by
this rule by replacing projections of future sprinkler system
installations with the actual number of facilities lacking automatic
sprinkler systems as of December 2007. The final impact analysis does
not revise the method for estimating future lives saved by this rule.
Although a commenter questioned this methodology, the commenter did not
offer an alternative methodology that would more accurately estimate
this number. Since we are not aware of an alternative method to
estimate the number of lives that will be saved, we have retained the
method used in the proposed rule.
Comment: Some commenters agreed with our proposal to require
automatic sprinkler systems in all facilities, while a small number of
commenters requested that certain long term care facilities be exempt
from the requirements of this final rule.
Response: Automatic sprinkler systems are generally considered to
be the single most effective fire protection feature in a building. As
such, we believe all long term care facilities, regardless of their
size or location in relationship to another type of health care
facility, should be required to have sprinklers. Exempting a particular
class of long term care facilities, regardless of the criteria used,
will not provide a consistent level of fire safety across the country.
Comment: Several commenters submitted comments regarding CMS
enforcement of this final rule. Some of these commenters sought
assurance that surveyors would be appropriately trained to enforce the
new sprinkler requirement. One commenter suggested that we should
survey each facility annually to ensure compliance with this rule.
Other commenters asked about the enforcement remedies that would be
available if a facility was non-compliant with the requirements of this
final rule, going so far as to suggest that non-compliant facilities
should receive reduced payments from Medicare and Medicaid. Still other
commenters requested that additional information about the sprinkler
status of particular facilities and facilities as a whole be included
on CMS' Nursing Home Compare Web site.
Response: We agree that it is essential to ensure that surveyors
are appropriately trained to survey facilities for compliance with all
fire safety requirements, including automatic sprinkler systems. To
that end, we conduct annual training sessions for surveyors to educate
them on, among
[[Page 47079]]
other things, fire safety requirements and appropriate survey
procedures. This training ensures surveyor competency in this area. We
also agree that frequent surveys of long term care facilities are key
to ensuring continued compliance with these requirements. By law, we
are required to survey long term care facilities every 15 months to
ensure compliance with all health and safety requirements, and we will
incorporate this new requirement into the existing survey process. If a
facility is found to be non-compliant with the provisions of this final
rule, we have the full complement of enforcement remedies available to
ensure that a facility comes into compliance. In addition to
termination of the provider agreement, available remedies include the
following: (1) Temporary management (that is, the temporary appointment
by CMS or the State of a temporary director or administrator of a
facility); (2) denial of payment, including denial of payment for all
individuals, imposed by CMS upon a skilled nursing facility for
Medicare payments, by a State for Medicaid payments, or denial of
payment for all new admissions; (3) civil money penalties; (4) State
monitoring; (5) transfer of residents; or (6) transfer of residents and
closure of the facility. CMS currently includes information about a
facility's sprinkler status on the Nursing Home Compare Web site to
enable consumers to make an informed decision.
Comment: A commenter suggested that installation of sprinkler
systems should be limited to pre-approved companies with proven fire
safety records. Another commenter suggested that we should create a
special task force in each State to visit each facility and examine the
information used to design the facility's sprinkler system.
Response: While we agree that long term care facilities should look
for qualified contractors to design and install their sprinkler
systems, we do not believe it is appropriate to, nor do we have the
authority to, select or approve such contractors. In addition, we do
not believe it is appropriate for us to develop task forces in each
State to review a facility's research and design plan. There are
numerous qualified designers who are capable of designing sprinkler
systems that fulfill facility-specific specifications. It is incumbent
upon facilities to assure that their automatic sprinkler systems meet
their specific facility needs as identified during a thorough review of
their current fire and building safety features and various other
factors.
Comment: A few commenters submitted additional information on their
own fire safety features and requirements (for example State sprinkler
requirements and facility-specific fire safety plans).
Response: We appreciate the additional information provided by the
commenters. It validates our understanding of current fire safety
efforts, both on the facility and State levels.
Comment: A commenter suggested that staffing levels may also impact
facility fire safety, and that we should require additional staffing
during the phase-in period to ensure that facility residents are
protected from fire.
Response: We agree that sufficient staffing is necessary to ensure
resident health and safety, including fire safety. Ensuring resident
health and safety, which is closely tied to facility staffing, is
already required in Sec. 483.15, ``Quality of life,'' Sec. 483.30,
``Nursing services,'' and Sec. 483.70, ``Physical environment.'' We
believe these regulations ensure sufficient staffing levels in long
term care facilities to promote and protect resident health and safety
in all circumstances.
Comment: A commenter questioned the conclusions of the GAO report
regarding the two multiple death fires in Connecticut and Tennessee.
The commenter stated that the GAO report did not demonstrate the
superiority of sprinklers over smoke alarms. The commenter also stated
that the number of multiple death fires before 1990 was zero, and that
the installation of sprinklers in new facilities after 1990 thus had no
bearing on the number of fires between 1990 and 1992.
Response: While we recognize that the commenter disagrees with the
data analysis of current fire safety levels in long term care
facilities presented by the GAO, we continue to support the GAO's data,
collection methodology, analytic methodology, and conclusions. We
concur with the GAO that smoke alarms are necessary in unsprinklered
facilities; we now require unsprinklered facilities to have such alarms
in accordance with the requirements of Sec. 483.70(a)(7). We also
concur with the GAO that before 1990, multiple death fires occurred on
a more frequent basis. As stated in the GAO report, ``When the federal
government first adopted the NFPA fire safety standards in 1971, the
number of multiple-death fires in nursing homes was about 15 to 18 per
year. With the adoption and enforcement of these standards, including
the requirement for sprinklers in homes that were not highly fire
resistant, the number of fire-related nursing home fatalities dropped
dramatically.'' (p. 14; we note that the average annual number of long
term care facility fire fatalities, according to the GAO report, is now
5.) Furthermore, we concur with the GAO that sprinklers improve the
level of fire safety beyond that which is provided by smoke alarms, and
we are implementing this final rule to require sprinklers in all long
term care facilities.
Comment: A commenter suggested that all facilities that currently
have automatic sprinkler systems throughout their buildings be required
to maintain those systems in accordance with the requirements of NFPA
25.
Response: Long term care facilities are required to meet the
standards of the LSC, which requires facilities with existing
sprinklers to maintain those sprinklers in accordance with the
requirements of NFPA 25. We agree with the commenter and are adopting
NFPA 25 by reference at Sec. 483.70(a)(8)(ii).
Comment: A commenter stated that NFPA 101, NFPA 13, and NFPA 25 can
all be viewed without charge at https://www.nfpa.org/freecodes/free_
access_document.asp.
Response: We thank the commenter for providing this Web site
citation. Unfortunately, the citation provided does not link to the
documents that a long term care facility will need to comply with this
final rule. Instead, an alternative, free Web site for this information
is https://www.nfpa.org/aboutthecodes/list_of_codes_and_
standards.asp.
Comment: A few commenters suggested that facilities be permitted to
have a reduced water supply that does not meet the specifications of
the NFPA requirements for health care facilities when an adequate level
of safety can be assured with less water.
Response: The NFPA uses a consensus process to establish the
requirements of its sprinkler installation and maintenance codes. It
would not be in the best interests of long term care facilities and
their residents to reduce the NFPA standards. We believe that the NFPA
standards represent the absolute minimum standards that long term care
facilities must meet, and that lowering the standards below those of
the NFPA would jeopardize long term care facility resident and staff
safety.
Comment: A commenter requested a 90-day extension of the public
comment period.
Response: We do not believe it is necessary to extend the standard
comment period. We received 107 unique comments, as well as numerous
duplicate comments, from interested parties during the comment period,
and we believe these comments adequately reflect public sentiment on
this matter.
[[Page 47080]]
Comment: A few commenters suggested additional requirements to
which long term care facilities should be held. One commenter suggested
that, in addition to installing and maintaining automatic sprinkler
systems, long term care facilities should be required to install and
maintain automatic fire alarm systems incorporating commercial smoke
detectors that comply with the audio and visual notification standards
of the Americans with Disabilities Act. Another commenter suggested
that long term care facilities should be required to have mattresses
that comply with certain fire safety standards.
Response: We agree with the commenters that numerous additional
options are available to long term care facilities that wish to further
enhance their fire safety levels. Long term care facilities may explore
these options in addition to meeting all requirements of the LSC and
this final rule.
Comment: A small number of commenters submitted comments on the
existing provision that a State may apply to CMS to use its own
alternative fire safety code imposed by State law if that code
adequately protects patients. The commenters inquired as to the status
of their own particular applications for a waiver under this provision.
Response: CMS actively considers any application submitted by a
State regarding the use of an alternate fire safety code in health care
facilities. However, these applications have no bearing on the
requirements of this final rule because this final rule requires
automatic sprinklers independent of the requirements of the LSC.
Comment: A commenter asked us to present a list of those States in
the early 1990s that adopted the 1991 or later edition of the LSC or
another code requiring newly constructed long term care facilities to
install automatic sprinkler systems.
Response: We do not believe it is necessary to present such a list
of information regarding the requirements of individual States. While
such a list may provide additional historic background on fire safety
requirements in the United States, all unsprinklered long term care
facilities must install and maintain automatic sprinkler systems.
Comment: A commenter suggested that, instead of requiring all long
term care facilities to install an automatic sprinkler system, we
should permit such facilities an exemption if they have all of the
following features: Smoke detectors, mattresses that meet certain fire
safety requirements, and upholstered furniture that meets certain fire
safety requirements.
Response: The fire safety measures noted above are valuable tools
for enhancing fire safety in long term care facilities. However, none
of these features serve the same purpose as an automatic sprinkler
system, which is to actively suppress a fire once it is ignited. Thus,
we do not believe the suggested options achieve the same level of fire
safety as automatic sprinklers.
Comment: A commenter suggested that we should include regulatory
language that endorses standardization and provides for system
interconnectivity.
Response: We are not clear regarding the commenter's suggestion. If
the commenter is referring to the standardization of installation and
maintenance requirements, we believe that referencing the NFPA
installation and maintenance standards does endorse standardization of
fire safety across long term care facilities.
Comment: Many commenters submitted comments regarding the placement
of smoke alarms in long term care facilities. In September 2006 we
published a final rule requiring all unsprinklered long term care
facilities to, at minimum, install and maintain battery-operated smoke
alarms in all resident rooms and common areas. In the October 2006
proposed sprinkler rule, we proposed to add a sunset date to this smoke
alarm requirement. The smoke alarm requirement would, according to our
proposal, cease to be effective on the phase-in date of the sprinkler
requirement. Many commenters disagreed with our proposal to add a
sunset date to the smoke alarm requirement. Furthermore, many of these
commenters stated that all long term care facilities should be required
to have both automatic sprinkler systems throughout their buildings and
smoke alarms in resident rooms and common areas. Conversely, several
commenters agreed with our proposal to add a sunset provision to the
smoke alarm requirement. Of these commenters, many requested that the
sunset date be flexible for individual long term care facilities. These
commenters suggested that, rather than having a single sunset date, the
final rule should state that a long term care facility is no longer
required to meet the smoke alarm provision as soon as it installs and
begins using an automatic sprinkler system. Additionally, one commenter
sought clarification of the relationship between the CMS smoke alarm
requirement and the smoke alarm requirement of the 2000 edition of the
Life Safety Code that long term care facilities are required to meet.
Response: The proposed smoke alarm sunset provision appears to have
caused significant confusion and concern, and we thank the commenters
for the opportunity to clarify our intent. The smoke alarm requirements
of paragraph (a)(7) apply only to unsprinklered or partially
sprinklered long term care facilities. This final rule will require all
facilities to be fully sprinklered. Thus, there will no longer be any
facilities that are unsprinklered or partially sprinklered. Since
(a)(7) applies only to unsprinklered or partially sprinklered
facilities, it will be a moot requirement. Nonetheless, we believe that
it is appropriate to retain the requirements of paragraph (a)(7) until
the end of the 5-year phase-in period. At the end of this period we
will consider proposing a rule which would delete both this provision
and reference to the phase-in period.
Moreover, facilities that are required to have smoke alarms or
smoke detection systems in accordance with the requirements of the 2000
edition of the LSC as incorporated by reference in paragraph Sec.
483.70(a)(1) must continue to comply with those existing LSC standards.
A significant number of commenters advocated for smoke alarms and/
or smoke detection systems in all long term care facilities, even those
that have automatic sprinkler systems throughout their buildings. All
long term care facilities may consider installing smoke detection
systems in their facilities in addition to installing automatic
sprinkler systems. We may consider the appropriateness of such a
requirement in future rulemaking.
Comment: We received a large number of public comments regarding
the appropriate length of a phase-in period for the sprinkler
installation requirement. Commenter suggestions for the length of the
phase-in period ranged from as little as 18 months to as long as 15
years. The most frequently suggested phase-in period was 3-5 years.
Other commenters made more general recommendations such as ``the sooner
the better'' and ``sooner rather than later.'' Additionally, many
commenters suggested that nursing homes should be allowed phase-in
waivers on a case-by-case basis to provide additional time to those
nursing homes who make a good faith effort to comply within the stated
timeframe, but who do not do so. One commenter suggested that we
include an additional requirement that long term care facility owners
file a statement with CMS detailing their intent to
[[Page 47081]]
comply with the final rule within 180 days of publication of the final
rule.
Response: We agree with commenters that a phase-in period is
necessary to allow long term care facilities sufficient time to
purchase and install automatic sprinkler systems throughout their
buildings. While we recognize that a relatively short phase-in period
(such as 18 months-3 years) will rapidly increase the level of fire
safety in long term care facilities, we believe such a short time frame
will not allow facilities enough time to comply with the provisions of
this final rule. Re-allocating and/or securing financial resources,
securing the services of a system designer and installation contractor,
purchasing system components, securing any necessary permits,
completing ancillary projects, and completing the actual installation
process can take a substantial amount of time. We do not believe an 18-
month to 3-year phase-in period allows enough time for all of these
tasks to be completed in all affected facilities. Furthermore, we do
not believe it is appropriate to allow waivers of this important
requirement. Likewise, we do not believe it will be appropriate to
allow long term care facilities 7 or more years to install automatic
sprinkler systems, as some commenters suggested. While such a lengthy
phase-in period will allow more than ample time for facilities to
complete the installation process, it may also unnecessarily encourage
facilities to postpone this much-needed fire safety improvement. In
light of these considerations, we are finalizing a 5-year phase-in
period. A long term care facility has 5 years from the date of
publication of this final rule to purchase and install a fully-
operational automatic sprinkler system throughout its building. A 5-
year phase-in period balances our dual goals of improved fire safety
and feasibility. It ensures that facilities begin planning for
installation within a short period of time from the publication of this
final rule and allows sufficient time for all facilities to complete
the full installation process.
Comment: Numerous commenters submitted comments regarding the exact
fire safety codes that should be used in long term care facilities.
Many of these commenters supported our proposal to require facilities
to meet the requirements of the 1999 edition of NFPA 13 and the 1998
edition of NFPA 25. Some of the commenters suggested that we require
facilities to meet more recent editions of the NFPA standards. Other
commenters questioned the role of the building codes issued by the
International Code Council (ICC). Of these commenters, some suggested
that we require facilities to meet the ICC codes in place of the NFPA
codes. Others suggested that States, local jurisdictions, and/or
facilities be given the option to meet either the NFPA or ICC codes.
Response: While we agree that more recent editions of NFPA
sprinkler codes or sprinkler codes issued by other code-setting bodies
may include appropriate installation and maintenance requirements for
automatic sprinkler systems in long term care facilities, we believe it
is most appropriate to require long term care facilities to comply with
the 1998 and 1999 editions of the NFPA sprinkler codes. If we require
facilities to meet more recent editions of the sprinkler codes, we
could be placing them out of compliance with the provisions of the 2000
edition of the LSC. Similarly, if we were to require or permit
facilities to meet another sprinkler code issued by a separate code-
setting body, the standards could be incompatible with the 2000 edition
of the LSC. We do not believe this will be in the best interest of
facilities and their residents.
Comment: A substantial number of commenters submitted thoughts in
response to our discussion of potentially adopting the 2006 edition of
the LSC, which requires existing long term care facilities to install
automatic sprinkler systems. Commenters were nearly evenly divided in
their support of or opposition to adopting the 2006 LSC. The commenters
who supported adopting the 2006 LSC stressed that this edition is the
most recent version and has the potential to increase fire safety
levels in all health care facilities. The commenters who did not
support adopting the 2006 LSC cited potential delays in implementing
the automatic sprinkler requirement and overall facility burden as key
factors in their recommendation.
Response: The 2006 edition of the LSC made numerous changes to the
requirements applicable to long term care facilities. The most
substantial change in the 2006 LSC is the requirement that all long
term care facilities must have automatic sprinkler systems. However,
since we are addressing that issue in this rulemaking, we do not
believe it should affect our evaluation of the overall merits of the
2006 LSC. We do not believe that the other changes in the 2006 edition
of the LSC offers substantial improvements in the level of fire safety
in long term care facilities that outweigh the additional burden to
facilities of complying with the requirements of a newer edition of the
LSC at this time. Therefore, we are not adopting the 2006 edition of
the LSC at this time. We will continue to participate in the NFPA
consensus process as the NFPA revises and refines subsequent editions
of the LSC. Additionally, we will carefully examine the 2009 edition of
the LSC when it is published for possible incorporation by reference in
our regulations governing long term care facilities and a variety of
other health care provider types.
IV. Provisions of the Final Regulations
In this final rule we are adopting the provisions as set forth in
the October 27, 2006 proposed rule with the following revisions:
Deleted proposed Sec. 483.70(a)(7)(iv), the sunset
provision.
Added a 5-year phase-in date to Sec. 483.70(2)(8)(i).
V. Collection of Information Requirements
Under the Paperwork Reduction Act of 1995, we are required to
provide 30-day notice in the Federal Register and solicit public
comment before a collection of information requirement is submitted to
the Office of Management and Budget (OMB) for review and approval. In
order to fairly evaluate whether an information collection should be
approved by OMB, section 3506(c)(2)(A) of the Paperwork Reduction Act
of 1995 requires that we solicit comment on the following issues:
The need for the information collection and its usefulness
in carrying out the proper functions of our agency.
The accuracy of our estimate of the information collection
burden.
The quality, utility, and clarity of the information to be
collected.
Recommendations to minimize the information collection
burden on the affected public, including automated collection
techniques.
We solicited public comment on each of these issues for the
following sections of this document that contain information collection
requirements:
In summary, Sec. 483.70(a)(8)(ii) requires that all long term care
facilities test, inspect, and maintain an approved, supervised
automatic sprinkler system in accordance with the 1998 edition of NFPA
25, Standard for the Inspection, Testing, and Maintenance of Water-
Based Fire Protection Systems. This section states that facilities will
be required by this proposed rule to comply with all applicable
chapters of NFPA 25 once they have installed their sprinkler systems in
accordance with the requirements of NFPA 13.
We believe facilities will utilize the services of a contractor for
all inspection, testing, and maintenance activities, including
documentation of
[[Page 47082]]
those activities. Therefore, no burden will be associated with the
development of the documentation. The burden associated with this
requirement, is the time and effort necessary for facilities to
maintain documentation of inspections, tests, and maintenance
activities in accordance with the standards outlined in the NFPA 25.
The burden associated with these requirements is estimated to be 1
hour per long term care facility. Therefore, we estimate it will take
2,446 total annual hours (1 hour x 2,446 estimated affected long term
care facilities) to satisfy this burden.
These requirements are not effective until they are approved by
OMB.
VI. Regulatory Impact Analysis
A. Overall Impact
We have examined the impacts of this rule as required by Executive
Order 12866 (September 1993, Regulatory Planning and Review), the
Regulatory Flexibility Act (RFA) (September 16, 1980, Pub. L. 96-354),
section 1102(b) of the Social Security Act, the Unfunded Mandates
Reform Act of 1995 (Pub. L. 104-4), Executive Order 13132 on
Federalism, and the Congressional Review Act (5 U.S.C. 804(2)).
Executive Order 12866 directs agencies to assess all costs and
benefits of available regulatory alternatives and, if regulation is
necessary, to select regulatory approaches that maximize net benefits
(including potential economic, environmental, public health and safety
effects, distributive impacts, and equity). A regulatory impact
analysis (RIA) must be prepared for major rules with economically
significant effects ($100 million or more in any 1 year). We have
examined this rule, and we have determined that this rule would meet
the criteria to be considered economically significant, and it would
meet the criteria for a major rule. This determination is based on
2,446 long term care facilities being required to install automatic
sprinkler systems at an estimated cost of $7.95 per square foot, for a
total cost of about $847 million over the 5-year phase-in period.
Hence, in any one year costs in excess of $100 million will be incurred
regardless of the decisions of individual facilities as to when to make
the investment.
The estimated cost for installing a sprinkler system throughout an
existing average size unsprinklered facility (50,000 square feet to be
sprinklered at $7.95 per square foot) will be $397,500. Because these
systems are capital investments, their costs are properly amortized
over time in estimating their impact on facility finances. We believe
that a reasonable estimate of the useful life of a sprinkler system is
20 years. The projected installation cost of this requirement will
account for approximately one fourth of one percent of an average
unsprinklered facility's actual revenue over a 20-year period. The
estimated cost for installing a sprinkler system throughout an existing
average size partially sprinklered facility (37,125 square feet to be
sprinklered at $7.95 per square foot) will be $295,143. The projected
installation cost of this requirement will account for approximately
one fifth of one percent of an average partially sprinklered facility's
actual revenue over a 20-year period.
The RFA requires agencies to analyze options for regulatory relief
of small entities. For purposes of the RFA, small entities include
small businesses, nonprofit organizations, and small government
jurisdictions (including tribal governments). Individuals and States
are not included in the definition of a small entity. For purposes of
the RFA, most long term care facilities are considered to be small
entities, either by virtue of their nonprofit or government status or
by having revenues of less than $12.5 million in any one year. The
latest SBA size standards classify a ``Nursing Care Facility'' under
North American Industry Classification System (NAICS) as code 623110,
and as ``small'' if its annual revenues fall below $12.5 million (for
details, see the Small Business Administration's Table of Small
Business Size Standards at https://www.sba.gov/idc/groups/public/
documents/sba_homepage/serv_sstd_tablepdf.pdf.) According to our
statistics, long term care facilities, all of which will be required to
have sprinkler systems throughout their buildings, received a total of
$124.9 billion in revenue in 2006 (National Health Expenditures
Accounts, https://www.cms.hhs.gov/NationalHealthExpendData/02_
NationalHealth AccountsHistorical.asp). Also according to CMS data,
there were 15,941 nursing facilities in operation at that time. The
average facility therefore had annual revenue of $7.8 million and thus
fell well below the SBA size threshold. Taking into account both
typical revenue, and that non-profit facilities of any size are ``small
entities'' within the meaning of the RFA, we assume for purposes of our
analysis that all LTC facilities are ``small entities'' for purposes of
the RFA. Although the average LTC facility has revenues well below the
SBA size threshold, we have, as described in what follows, also
analyzed impacts on entities that fall even farther below the size
threshold. (Note: In the following paragraphs the terms ``average
facility'' and ``smaller facility'' are strictly based on a revenue
metric, just as are most of the SBA size thresholds, including that for
NAICS code 623110. That is, the terms only describe facilities in terms
of the amount of annual revenue.)
Long term care facilities vary in a number of ways, ranging from
the number of residents to the predominant source of payment for those
residences. For the purposes of our analysis, we chose to assess the
financial impact of this final rule on a facility with average revenue
and a facility with a much smaller revenue (50 percent below the mean).
An average facility had approximately $7,837,714 in revenue in 2006. A
facility with revenue 50 percent below this average received
$3,918,857, or less than one third of the amount set by SBA to define
``small.'' Over the 20-year amortization period revenues of an average
facility will be about $157 million. The ``smaller'' facility will have
revenues of about $78 million over the same 20-year amortization
period. We calculate that the projected cost of this requirement will
account for about one fourth of one percent of an average unsprinklered
``smaller'' facility's actual revenue over the 20-year period. Taking
into account their smaller size and lower investment cost, the
projected cost of this requirement will account about one fifth of one
percent of a partially sprinklered ``smaller'' facility's actual
revenue over the 20-year period. We are assuming that a smaller
facility's square footage and number of beds are 50 percent less than
an average facility's square footage because there is a strong
correlation between the size of a facility, as reflected by the number
of resident beds it has, and the facility's revenue level. According to
CMS data from December 2007, there (see Table 3 later in this analysis)
the median bed size of LTC facilities is about 100 beds, and there are
433 unsprinklered or partially sprinklered long term care facilities
that have fewer than 50 beds and presumably meet our revenue definition
of a ``smaller facility.'' Hence, there are relatively few very small
(``smaller'') facilities that will be affected by this rule. That said,
a total of about 2,446 unsprinklered or partially sprinklered facilites
will be affected, and the great majority of these (we assume all) are
``small entities'' under the RFA (again, see Table 3 for the size
distribution of affected entities).
As a result of these calculations, and because we normally only
regard an
[[Page 47083]]
impact that reaches several percent of annual revenue as
``significant'' under the RFA, we certify that this final rule would
not have a significant impact on a substantial number of small
entities. However, some facilities may face financing or other problems
that concentrate the impact and make its effect proportionally much
larger than would otherwise be the case. While we do not believe that
there would be a substantial number of facilities in this circumstance,
we have prepared a voluntary regulatory flexibility analysis. This
Regulatory Impact Analysis section, taken together with the remainder
of the preamble, constitutes this analysis.
In addition, section 1102(b) of the Act requires us to prepare a
regulatory impact analysis if a rule may have a significant impact on
the operations of a substantial number of small rural hospitals. This
analysis must conform to the provisions of section 604 of the RFA. For
purposes of section 1102(b) of the Act, we define a small rural
hospital as a hospital that is located outside of a metropolitan
statistical area and has fewer than 100 beds. We know that 8.41 percent
of long term care facilities, 1,332 nationwide, are located in
hospitals, but we do not know how many of those hospitals are small
rural hospitals. However, it is likely that the affected number is
quite small. Applying the same percentages that apply to the long term
care universe to the 1,332 long term care facilities located in
hospitals, we estimate that 1,125 are fully sprinklered, 176 are
partially sprinklered, and only 31 are not sprinklered. Using these
estimates and the preceding cost amortization calculations, we have
concluded that this final rule will not have a significant impact on
the operations of a substantial number of small rural hospitals and
that a regulatory flexibility analysis is not required. Our voluntary
analysis, however, applies equally to facilities regardless of location
or affiliation and hence covers hospital-based facilities.
Section 202 of the Unfunded Mandates Reform Act of 1995 (UMRA) also
requires that agencies assess anticipated costs and benefits before
issuing any rule whose mandates require spending in any one year by
either the private sector or by State, local, and tribal governments of
$100 million in 1995 dollars, updated annually for inflation. That
threshold level is currently approximately $130 million. This final
rule does contain mandates that will impose annual spending costs on
private long term care facilities of $154 million, and on public long
term care facilities of $16 million, based on an estimated cost of
about $847 million distributed over a 5-year phase-in period, for an
average annual cost of about $170 million for all public and private
facilities. Estimated impacts on State, local, and tribal governments
are well below the UMRA threshold, since over ninety percent of long
term care facilities are privately owned, as shown the Federalism
analysis that follows. With respect to private sector facilities, this
Regulatory Impact Section, together with the remainder of the preamble,
constitutes the analysis required under UMRA.
Note: For a more detailed discussion of the cost estimates, see
part B.2 of this section.) In the proposed rule we estimated that
this rule would cost $47.8 to $69.9 million, $73.5 to $107.5
million, and $107.7 to $157.6 million annually. These estimates were
based on example phase-in periods of 10 years, 7 years, and 5 years,
and cost-per-square-foot estimates of $4.10, $5.50, and $6.10,
respectively. We sought public comment on the length of an
appropriate phase-in period, and received suggestions ranging from
18 months to 15 years. The most frequently suggested phase-in period
was 3-5 years. We selected the longer phase-in period, 5 years, to
help mitigate the impact of this rule upon long term care
facilities. We also increased our cost-per-square-foot estimates to
reflect increases in construction costs that have occurred since
publication of the proposed rule.
Executive Order 13132 establishes certain requirements that an
agency must meet when it promulgates a final rule that imposes
substantial direct compliance costs on State or local governments,
preempts State law, or otherwise has Federalism implications. Of the
2,446 facilities that will be affected by this final rule, 216
facilities (8.83 percent of all affected facilities) are owned by State
and local governments. The majority of these facilities (188) are
already partially sprinklered. Of the 188 partially sprinklered
facilities, 31 have less than 50 resident beds, 43 have 50-99 resident
beds, 63 have 100-199 resident beds, and 49 have 200 or more resident
beds. We estimate that it will cost on average about $14.24 million
annually for 5 years to install sprinklers throughout the unsprinklered
portions of these facilities. Of the remaining 30 completely
unsprinklered facilities, 13 have less than 50 resident beds, 8 have
50-99 resident beds, 7 have 100-199 resident beds, and 2 have 200 or
more resident beds. We e