Energy Conservation Program for Consumer Products: Test Procedure for Residential Central Air Conditioners and Heat Pumps, 59906-59934 [07-5142]
Download as PDF
59906
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Part 430
[Docket No. EE–RM/TP–02–002]
RIN 1904–AB55
Energy Conservation Program for
Consumer Products: Test Procedure
for Residential Central Air
Conditioners and Heat Pumps
Department of Energy.
Final rule.
AGENCY:
pwalker on PROD1PC71 with RULES3
ACTION:
SUMMARY: The Department of Energy
(DOE) is amending its test procedure for
residential central air conditioners and
heat pumps. This final rule implements
test procedure changes for small-duct,
high-velocity systems, two-capacity
units, and updates references to the
current American Society of Heating,
Refrigerating, and Air-Conditioning
Engineers (ASHRAE) standards. Today’s
rule also clarifies issues associated with
sampling tested systems and rating
untested split-system combinations.
DATES: This rule is effective April 21,
2008. Incorporation by reference of
certain publications in the final rule is
approved by the Director of the Federal
Register as of April 21, 2008.
ADDRESSES: You may review copies of
all materials related to this rulemaking
at the U.S. Department of Energy,
Forrestal Building, Room 1J–018
(Resource Room of the Building
Technologies Program), 1000
Independence Avenue, SW.,
Washington, DC, (202) 586–9127,
between 9 a.m. and 4 p.m., Monday
through Friday, except Federal holidays.
Please call Ms. Brenda Edwards-Jones at
the above telephone number for
additional information regarding
visiting the Resource Room. Please note:
DOE’s Freedom of Information Reading
Room (formerly Room 1E–190 at the
Forrestal Building) is no longer housing
rulemaking materials.
FOR FURTHER INFORMATION CONTACT:
Michael G. Raymond, U.S. Department
of Energy, Office of Energy Efficiency
and Renewable Energy, EE–2J, 1000
Independence Avenue, SW.,
Washington, DC 20585–0121, (202) 586–
9611, e-mail:
michael.raymond@ee.doe.gov; or
Francine Pinto, Esq., U.S. Department of
Energy, Office of the General Counsel,
GC–72, 1000 Independence Avenue,
SW., Washington, DC 20585–0121, (202)
586–9507, e-mail:
Francine.Pinto@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
I. Introduction
A. Authority
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
B. Background
C. Summary of the Test Procedure
Revisions
II. Discussion of Comments
A. Frost Accumulation Test Duration
B. Multiple-Split Systems
C. Defining ‘‘Repeatable’’ for Cyclic Tests
D. Outdoor Air Test Conditions for Units
Having a Two-Capacity Compressor
E. Air Volume Rate Less Than
Manufacturer’s Specified Value
F. Updating References to Industry
Standards
G. Maximum and Minimum Speed Values
for Calculating NQ and NE
H. Using the Default or Tested Value of
Cyclic-Degradation Coefficient
I. Guidance on the Inclusion of PreProduction Units in the Sample
Population
J. Clarification of the Sample Population
Used To Validate the Rated Seasonal
Energy Efficiency Ratio and Heating
Seasonal Performance Factor of Heat
Pumps
K. Clarification of the Definition of a
‘‘Highest-Sales-Volume Combination’’
L. Upper Limit on the Difference Between
Calculated and Tested Seasonal Energy
Efficiency Ratio and Heating Seasonal
Performance Factor Values
M. Clarification of the Published Ratings
for Untested Split-System Combinations
N. Ratings That Are Based on Using a
Particular Furnace or Ducted Air Mover
O. Revisions to the Definition of ‘‘Coil
Family’’
III. Summary of Other Additions, Changes,
and Corrections to the Department of
Energy Residential Central Air
Conditioner and Heat Pump Test
Procedure
IV. Effect of Test Procedure Revisions on
Compliance With Standards
V. Procedural Requirements
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under the Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
VI. Approval of the Office of the Secretary
I. Introduction
A. Authority
Part B of Title III of the Energy Policy
and Conservation Act (EPCA)
established the Energy Conservation
Program for Consumer Products Other
Than Automobiles (Program). (42 U.S.C.
6291 et seq.) The products currently
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
subject to this Program (covered
products) include central air
conditioners and heat pumps, the
subject of today’s final rule.
Under EPCA, the Program consists of
three parts: Testing, labeling, and the
Federal energy conservation standards.
DOE, in consultation with the National
Institute of Standards and Technology
(NIST), is authorized to establish or
amend test procedures as appropriate
for each of the covered products. (42
U.S.C. 6293) The purpose of these test
procedures is to measure energy
efficiency, energy use, or estimated
annual operating cost of a covered
product during a representative, average
use cycle or period of use. The test
procedure must not be unduly
burdensome to conduct. (42 U.S.C.
6293(b)(3))
If a test procedure is amended, DOE
is required to determine to what extent,
if any, the proposed new test procedure
would alter the measured energy
efficiency of any covered product as
determined under the existing test
procedure. (42 U.S.C. 6293(e)(1)) If DOE
determines that an amended test
procedure would alter the measured
energy efficiency of a covered product,
DOE is required to amend the applicable
energy conservation standard with
respect to such test procedure. In
determining any such amended energy
conservation standard, DOE is required
to measure the energy efficiency or
energy use of a representative sample of
covered products that minimally
comply with the existing standard. The
average efficiency or energy use of this
representative sample, tested using the
amended test procedure, constitutes the
amended standard. (42 U.S.C.
6293(e)(2)) DOE has determined that
today’s amended test procedure does
not alter the measured efficiency or
measured energy use of minimally
compliant central air conditioners and
heat pumps.
Beginning 180 days after a test
procedure for a covered product is
prescribed, no manufacturer,
distributor, retailer, or private labeler
may make representations with respect
to the energy use, efficiency, or cost of
energy consumed by such product,
except as reflected in tests conducted
according to the DOE procedure. (42
U.S.C. 6293(c)(2)) Any manufacturer,
distributor, retailer, or private labeler
may petition the Secretary of Energy for
an extension of not more than 180 days
to test and make representations in
accordance with the amended DOE test
procedure. (42 U.S.C. 6293(c)(3)) In
addition, all existing waivers
concerning residential multi-split
E:\FR\FM\22OCR3.SGM
22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
systems terminate on the effective date
of today’s final rule.
pwalker on PROD1PC71 with RULES3
B. Background
A final rule published on October 11,
2005, updated and completely reorganized the DOE residential central
air conditioner and heat pump test
procedure. 70 FR 59122. During this
prior rulemaking, a few issues were
identified too late in the process to
allow them due consideration. DOE
investigated these issues and considered
additional topics that could further
improve the testing and rating process.
As a result of these efforts, DOE issued
a Notice of Proposed Rulemaking on
July 20, 2006 (hereafter referred to as the
July 2006 proposed rule). 71 FR 41320.
Although the majority of the proposed
changes pertained to the test procedure
set forth in appendix M to subpart B of
Title 10, Code of Federal Regulations,
Part 430 (10 CFR part 430), DOE also
proposed revisions to sections of
subparts B and F of 10 CFR part 430 that
concern the sampling of tested units and
the ratings of untested split-system
combinations. 10 CFR 430.24 and
430.62. DOE held a public meeting on
the July 2006 proposed rule on August
23, 2006.
On October 10, 2006, DOE published
a Federal Register notice correcting two
inadvertent omissions in the July 2006
proposed rule. 71 FR 59410. These
omissions contained the regulatory
language governing the criterion for
using an air volume rate that is less than
the manufacturer’s specified value: One
case covered air conditioners and heat
pumps, the other case covered heatingonly heat pumps. This change was
described in the preamble of the July
2006 proposed rule, but was not
included in the regulatory language. In
addition to publishing the corrected
regulatory language in the Federal
Register, the omitted regulatory
language was distributed at the August
23, 2006, public meeting.
C. Summary of the Test Procedure
Revisions
The revisions adopted in today’s final
rule include the following changes to
appendix M of Subpart B of 10 CFR part
430: (1) Adding new testing
requirements for small-duct, highvelocity systems; (2) reinstating the
optional testing to determine the cyclicdegradation coefficient (CD) of a twocapacity unit when cycling on and off
at high capacity; (3) shortening the
maximum duration of the Frost
Accumulation Tests; (4) allowing the
use of default equations to approximate
the capacity and power of a twocapacity unit when operating at low-
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
capacity/stage and at an outdoor
temperature of 35 degrees Fahrenheit
(°F); (5) implementing modifications
and additions that specifically address
elements unique to testing and rating
modulating multi-split systems; (6)
allowing indoor capacities used in
calculating Seasonal Energy Efficiency
Ratio (SEER) and Heating Seasonal
Performance Factor (HSPF) to be
corrected for duct losses; (7) defining
the term ‘‘standard air;’’ (8) changing the
outdoor temperature conditions used for
one of the low-capacity, steady-state,
cooling mode tests on a two-capacity
unit; (9) renaming ‘‘Cooling and Heating
Certified Air Volume Rates’’ to ‘‘FullLoad Air Volume Rates;’’ (10) modifying
the criterion for using an air volume rate
less than the manufacturer’s specified
value; (11) updating the references to
current versions of the Air-Conditioning
and Refrigeration Institute (ARI) and
ASHRAE standards; (12) adding
language to better explain the SEER and
HSPF calculation steps for variablespeed equipment; and (13) adding text
to clarify the provision to use the
default value of the cyclic-degradation
coefficient if it is lower than the tested
value.
Today’s final rule also amends
sections 430.2, 430.24 and 430.62 of 10
CFR part 430, as follows: (1) It expands
the options for meeting the data
submission requirements when
verifying an alternative rating method
(ARM); (2) it clarifies the sample
population to be used to validate the
rated SEER and rated HSPF of a heat
pump; (3) it clarifies the definition of a
‘‘highest-sales-volume combination’’
(HSVC); (4) it clarifies DOE’s role in
verifying ratings for untested split
system combinations; (5) it clarifies how
to apply the ARM to obtain published
ratings for untested, split-system
combinations; (6) it adds the
requirement that ratings for an air
conditioner or heat pump tested with a
furnace or similar ducted air mover
include the model number of the air
mover as part of the overall equipment
model number; (7) it clarifies the
responsibilities of private labelers; (8) it
adds the statutory definition of ‘‘private
labeler;’’ and (9) it adds definitions for
terms, including ‘‘indoor unit’’,
‘‘outdoor unit’’, and ‘‘ARM/simulation
adjustment factor.’’
II. Discussion of Comments
In addition to the comments received
at the August 23, 2006, public meeting,
DOE received written comments to the
July, 2006 proposed rule from ARI,
Nordyne, Mitsubishi, Fujitsu General
Limited (Fujitsu), Carrier Corporation
(Carrier), the American Council for an
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
59907
Energy-Efficient Economy (ACEEE),
Sanyo Fisher Service Corporation
(Sanyo), Lennox International (Lennox),
and the China WTO/TBT National
Notification and Enquiry Center (China).
The comments and the DOE response to
them are discussed below. References to
section numbers within this document
refer to the section numbers of
Appendix M to Subpart B of 10 CFR
part 430–Uniform Test Method for
Measuring the Energy Consumption of
Central Air Conditioners and Heat
Pumps (Appendix M).
A. Frost Accumulation Test Duration
DOE proposed shortening the
maximum test interval of a Frost
Accumulation Test from 12 hours to 6
hours when testing a two-capacity heat
pump at low capacity. ARI supported
DOE’s proposal to lessen the test
burden, but recommended that the
maximum duration be further shortened
to 3 hours. (ARI, No. 21 at p. 2)1 ARI
stated that ‘‘preliminary testing done by
manufacturers shows a variation in
HSPF of less than one tenth 2 when the
test is reduced from 12 to 3 hours.’’
(ARI, Id.) In a follow-up
communication, ARI clarified that its 3hour recommendation applies to all
Frost Accumulation Tests, not just the
test at low-capacity. (ARI, No. 25 at p.
2) ARI provided a table showing the
percentage of the total interval allocated
to defrosting for cycles lasting 6, 7, 8, 9,
and 10 minutes; percentages were
calculated for complete (frost + defrost)
intervals ranging from 1 hour to 12
hours. As an example, for tests lasting
12, 6, and 3 hours, the percentages of
time spent defrosting are 1.1, 2.2, and
4.4 percent, respectively, if the defrost
lasts 8 minutes in all cases. (ARI, No. 25
at p. 3) In addition to recommending
that any change be applied to all Frost
Accumulation Tests, Nordyne and
Carrier recommended manufacturers be
given the option of using either the
procedure specified in ASHRAE
Standard 37 (which uses a maximum
test interval of 3 hours) or the algorithm
specified in the DOE test procedure.
(Nordyne, No. 19 at p. 2; Carrier, No. 17
1 A notation in the form ‘‘ARI, No.21 at p. 2’’
identifies a written comment the Department has
received and has included in the docket of this
rulemaking. This particular notation refers to a
comment (1) by the Air-Conditioning and
Refrigeration Institute (ARI), (2) in document
number 21 in the docket of this rulemaking
(maintained in the Resource Room of the Building
Technologies Program), and (3) appearing on page
2 of document number 21. Likewise, ‘‘Public
Hearing Tr., p. 178,’’ for example, would refer to
page 178 of the transcript of the ‘‘Public Meeting
on Test Procedures for Central Air Conditioners’’
held in Washington, DC, August 23, 2006.
2 This means an absolute variation in HSPF of 0.1,
such as between 8.1 and 8.2.
E:\FR\FM\22OCR3.SGM
22OCR3
pwalker on PROD1PC71 with RULES3
59908
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
at p. 2) In summary, the stakeholders
recommended applying changes to all
Frost Accumulation Tests (not just to
the one low-capacity test, as proposed),
reducing the maximum duration to 3
hours instead of 6 hours, and adding an
alternative test method.
DOE believes that if all three changes
were adopted, the HSPF ratings of heat
pumps would be changed, since the
ASHRAE Standard 37 ‘‘T’’ Test
Procedure may terminate after 0, 1, 2, or
3 complete cycles whereas the DOE
Frost Accumulation Test is either 0 or
1 complete cycle. The different cycles in
the ASHRAE and DOE test methods can
yield different average heating capacity
and power consumption results at the
DOE-specified 35 °F dry-bulb/33 °F wetbulb outdoor test conditions which
would affect the HSPF rating. As for
shortening the maximum test time to 3
hours, such a change may benefit heat
pumps (i.e., give a higher average
heating capacity) that initiate a defrost
of the outdoor coils between 3 and 6
hours after the start of the test. In such
cases, the heat pump’s average heating
capacity will not account for the energy
used for defrosting. By not accounting
for the defrost energy, the shorter test
time would overstate the heating
capacity and HSPF. Thus, DOE will not
reduce the maximum test duration by
the additional 3 hours or add the
ASHRAE Standard 37 procedure as an
alternate test method as part of this final
rule.
DOE agrees with comments
recommending the same maximum limit
for all Frost Accumulation Tests. The
low-capacity Frost Accumulation Test is
projected to be the most likely of the 35
°F tests to approach the proposed 6-hour
limit, followed by the required Frost
Accumulation Test at the intermediate
speed when testing a variable-speed
heat pump. All other Frost
Accumulation Tests are more likely to
build frost and are likely to result in the
unit defrosting in less time than it
would at the intermediate speed. Thus,
triggering the 6-hour limit is less likely
when applied to these other cases.
Finally, DOE concludes that 6 hours
offers a sufficiently long duration for
evaluating performance in all cases. As
noted in the July 2006 proposed rule, if
a heat pump has not defrosted in 6
hours, it is either not building frost or
is completely frosted and probably has
been so for more than half of the
interval. In both cases, the benefits from
continuing to run the test past 6 hours
are minimal. Therefore, DOE reduces
the maximum duration of all Frost
Accumulation Tests from 12 hours to 6
hours. This change appears in section
3.9 of Appendix M.
VerDate Aug<31>2005
18:36 Oct 19, 2007
Jkt 214001
B. Multiple-Split Systems
DOE received comments on issues
related to the testing and rating of
multiple-split air-conditioning systems
(multi-split systems), including: (1)
Rating multi-split systems based on
SEER (if they compete primarily with
ducted central air conditioners), or
rating them based on EER (if they
compete with room air conditioners)
(SEER or EER); (2) adopting a separate
test procedure for multi-split systems,
such as Draft ARI Standard 1230 (ARI
1230); (3) allowing one or more indoor
coils to turn off during any test, if
representative of normal operation
(Coils active during test); (4) allowing
the manufacturer to specify the
compressor speed used during the
minimum-speed, intermediate-speed
and maximum-speed tests (Compressor
speed); (5) extending multi-split system
test procedure changes to one-to-one
ducted systems (One-to-one
applicability); and (6) adding the term
‘‘tested combination’’ within 10 CFR
430.2 for determining the combination
of indoor units to be tested when testing
a multi-split outdoor unit, and the
appropriate rating of the tested
combination (Tested combination).
SEER or EER. DOE received several
comments on whether multi-split
systems compete primarily with ducted
residential central air conditioners and
heat pumps and as such, should be
rated based on SEER and HSPF, or if
they compete with room air
conditioners and should be rated in
terms of EER and COP. Trane argues
that residential size multi-split systems
compete for the same markets as ducted
residential central systems: both serve
multiple rooms, one ducts air whereas
the second ‘‘ducts’’ refrigerant. (Public
Hearing Tr., p. 178) Carrier and ACEEE
support rating conventional central air
conditioners and heat pumps and multisplit systems using the same
descriptors. (Carrier, No. 17 at p. 1 and
ACEEE, No. 16 at p. 3) According to
Mitsubishi, ‘‘ductless split-systems,
including ductless multi-split systems,
are used for room or spot cooling
applications while the rest of the USE
[unitary small equipment] equipment
(i.e., central systems) is applied in a
ducted environment for multiple rooms
or whole houses.’’ (Mitsubishi, No. 20 at
p. 3) DOE believes residential-size
multi-split systems compete with
ducted central systems and that the
consumer will be best served if multisplit systems can be compared with
central air conditioners and central airconditioning heat pumps. Therefore,
DOE concludes that SEER and HSPF are
better descriptors than EER and COP.
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
ARI 1230. ARI, Sanyo, Fujitsu,
Mitsubishi, and Daikin AC (Americas),
Inc. (Daikin) urged DOE to adopt Draft
ARI Standard 1230, ‘‘Performance
Rating of Multi-Split Air-Conditioning
and Heat Pump Equipment’’ in lieu of
the proposed rule. (ARI, No. 21 at p. 3;
Sanyo, No. 15 at pp. 2–3; Fujitsu, No.
13 at p. 3; Mitsubishi, No. 20 at pp. 4–
5; Public Hearing Tr., pp. 153–154)
China recommends that DOE not cover
multi-split systems within the
residential central air conditioner and
heat pump test procedure until all the
technical issues have been resolved.
(China, No. 14 at p. 1) Copeland
recommends that DOE review and
consider the approaches being taken by
China and the European Union on how
to test and rate multi-split systems.
(Public Hearing Tr., p. 64) Nordyne
supports the changes proposed in the
July 2006 proposed rule to cover multisplit systems as an interim solution, but
states that further study is needed for a
long term solution. (Nordyne, No. 19 at
p. 2) Lennox, on the other hand,
believes that multi-split systems should
be rated using the current test procedure
for central air conditioners and central
air conditioning heat pumps. (Lennox,
No. 22 at p. 2) Sanyo and Fujitsu point
out that the test procedure does not
address units that can simultaneously
cool and heat; the test procedure does
not specify how many indoor units are
turned off during a given test; and
doubts whether the current DOE tests
for variable-speed systems can
approximate the unit’s ‘‘performance
map.’’ 3 (Sanyo, No. 15 at pp. 2–3;
Fujitsu, No. 13 at pp. 2–3; Public
Hearing Tr., pp. 94–95, 110)
DOE is not convinced that residentialsize multi-split systems require a
separate test procedure from the current
test procedure found in Appendix M.
While it is true that the current test
procedure fails to account for the energy
savings derived from a simultaneous
cooling and heating mode, the current
test procedure is adaptable and DOE
believes the tests for variable-speed
systems in Appendix M offer a
reasonable starting point for producing
energy efficiency and energy use
estimates. Once data become available
that provides insight as to the energy
use and efficiency benefits of
simultaneous cooling and heating, and
alternative or additional tests to
estimate these benefits are formulated,
DOE will then consider further
3 Performance map refers to a plot that shows the
effect of compressor speed, number of indoor unit
turned on versus off, and outdoor temperature
conditions on the unit’s space conditioning
capacity and power consumption.
E:\FR\FM\22OCR3.SGM
22OCR3
pwalker on PROD1PC71 with RULES3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
amendments to the test procedure.
Accordingly, DOE is not adopting a new
test procedure and energy efficiency and
energy use ratings will continue to be
based on the test procedure found in
Appendix M.
Regarding the stakeholder
recommendation to adopt draft ARI
Standard 1230, the current draft (as
distributed in June 2007), is less
complete for residential multi-split
systems than the DOE test procedure in
today’s final rule. For example, ARI
Standard 1230 (June 2007 draft) lacks
information on how to conduct
intermediate speed tests, whether any
indoor units are to be turned off for partload tests, how to interpolate EER and
COP in the intermediate speed range,
and generally how to calculate SEER
and HSPF. Furthermore, ARI has not
finalized ARI Standard 1230 and, as
such it cannot be incorporated by
reference since it could be amended
prior to being adopted in final form.
Therefore, for the reasons discussed
above, DOE is not adopting ARI
Standard 1230 (June 2007 draft) in
today’s final rule.
As for considering changes that are
modeled on the approaches taken in
China and the European Union, DOE
sees their potential use as limited given
the current EPCA requirement to
calculate annual measures of energy
consumption. The European Union
HVAC trade association, Eurovent, lists
ratings for residential-size multi-splits
that are based on full load EER and COP
and their European SEER (ESEER) is
thus far limited to liquid chilling
packages, not unitary air conditioners
(i.e., residential central air conditioners
and central air conditioning heat
pumps). The ESEER is actually a
variation of ARI Standard 340/360’s
IPLV, which is used to quantify the partload performance of larger, nonresidential systems. An IPLV equivalent
is also used in China. Neither
international resource explicitly
addresses the number of indoor units to
be turned off during a given part-load
test; such information would be
necessary in order to get an accurate
measure of equipment efficiency for
comparison purposes.
Coils active during test. Concerning
the issue of whether one or more indoor
units should be turned off during any
given test, Daikin commented that you
cannot rely on the unit’s controls to
make the decision when operated in a
laboratory environment. (Public Hearing
Tr., p. 62) Given this, DOE offered, at
the public meeting, an algorithm for
specifying the number of indoor units
that are turned on for a given test. This
algorithm is shown in Table 1, below.
VerDate Aug<31>2005
18:36 Oct 19, 2007
Jkt 214001
59909
or nominal rated speed because
performance at that compressor speed is
used in sizing and selling the product.
ARI and Sanyo supported DOE’s
proposal to allow the manufacturer to
specify the compressor speed used for
the minimum-speed and intermediatespeed tests. (ARI, No. 21 at p. 2; Sanyo,
No. 15 at p. 2) Sanyo and ARI,
moreover, both believe that test
laboratories must accept the task of
providing test facilities that can
maintain steady test room conditions
and accurately measure capacity at very
low loads. (ARI, No. 21 on pp. 2–3;
Sanyo, No. 15 on p. 2)
Regarding the maximum and
minimum compressor speed issue, DOE
reviewed test procedure waivers
processed in the 1980’s, and the 1988
test procedure rulemaking that first
added coverage for air conditioners and
heat pumps having a variable-speed
compressor. (53 FR 8304, March 14,
1988) None of these actions explicitly
defined maximum and minimum
compressor speed. Instead, the
manufacturer was allowed to define
these speeds for its particular units. The
evolution to include maximum and
TABLE 1.—APPROACH TO REGULATING minimum compressor speeds among
those elements that are ‘‘conducted in
THE NUMBER OF ACTIVE INDOOR
accordance with the manufacturer’s
UNITS
instructions’’ occurred because of the
(Example Case of a Multi-Split System Having test laboratory’s need for a mechanism
4 Identical Indoor Units)
to override the unit’s normal controls,
so that the compressor can be forced to
Number of
Percentage output relative to
operate at fixed speeds for the DOEoperating
full load capacity
specified lab tests. As part of today’s
indoor units
final rule, DOE considered adopting a
75% to 100% ........................
4 specific definition for maximum speed
50% to 75% ..........................
3 and requiring additional lab verification
25% to 50% ..........................
2 tests, but has decided against it because
0% to 25% ............................
1 there is no compelling technical
argument for doing so. The current
(DOE, No. 12.3 at p. 12)
approach effectively allows the
DOE recognizes that when field
manufacturer to de-rate the unit’s
installed, a multi-split system will often maximum capacity in order to raise its
operate with one or more of its indoor
performance descriptor. As long as that
units turned off. In an effort to have the
de-rated capacity is used for sizing the
DOE test procedure capture this partparticular multi-split combination, then
load operating mechanism, today’s final the practice is acceptable. DOE,
rule requires that at least one indoor
however, does not agree with
unit must be turned off for tests
substituting ‘‘nominal’’ or ‘‘rated’’
conducted at minimum compressor
compressor speed for ‘‘maximum’’
speed. In addition, the manufacturer
compressor speed, as that will not allow
may elect to have one or more indoor
for test results that can be used to
units turned off for tests conducted at
generate a performance map
the intermediate compressor speed. In
representing how particular multi-split
all cases, the manufacturer specifies the combinations will operate in the field.
particular indoor unit(s) that is turned
The DOE test procedure will continue
off.
to require variable-speed systems to be
Compressor speed. ARI, Sanyo,
tested at their minimum compressor
Fujitsu, and Mitsubishi opposed DOE’s
speed. Manufacturers will be relied
proposed definition of maximum
upon to provide the independent testing
compressor speed. (ARI, No. 21 at p. 2;
laboratory with a means for conducting
Sanyo, No. 15 at p. 2; Fujitsu, No. 13 at
tests at this speed. Minimum speed may
p. 2; Mitsubishi, No. 20 at p. 4) They
not be the absolute minimum speed at
recommended using the rated capacity
which the compressor can operate, but
To evaluate the effect of such an
algorithm, Fujitsu conducted
simulations in which it modeled the
performance of a unit if operated at the
DOE test procedure cooling mode
conditions. Fujitsu considered cases
where the number of indoor units
turned on for the two minimum speed
and one intermediate speed tests
changed. Fujitsu reported results for
three cases: the first case, all four indoor
units are on for all tests; the second
case, three indoor units are on for the
intermediate speed test and two indoor
units are on for the minimum speed
tests; and the third case, two indoor
units are on for the intermediate-speed
test and one indoor unit is on for the
minimum speed tests. (Fujitsu, No. 13 at
pp. 1–2) Using the simulated data,
Fujitsu reported that the first case yields
the highest SEER. In comparison,
Fujitsu reported that the SEER drops by
4.7 percent for the second case and by
11.6 percent for the third case. Fujitsu
concluded that the number of operating
indoor units may have a great impact on
the result, and that the operating ranges
in Table 1 were not appropriate.
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
E:\FR\FM\22OCR3.SGM
22OCR3
pwalker on PROD1PC71 with RULES3
59910
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
it is expected to be a speed below which
the compressor would rarely operate.
DOE concurs with Sanyo and ARI and
expects test laboratories to measure
performance over the wide modulation
range that is characteristic of multisplits. Thus, to the issue of what
compressor speed to use when
conducting minimum speed and
maximum speed tests, DOE is
maintaining the current test procedure
language in sections 3.2.4 and 3.6.4 of
Appendix M.
DOE adopts the July 2006 proposed
change of allowing the manufacturer to
specify the compressor speed used for
the cooling and heating intermediate
speed/capacity tests. This change
provides the manufacturer an
opportunity to select and verify the
peak-efficiency of the unit being tested.
Coupled with this change, and as also
proposed in the July 2006 notice,
steady-state efficiency (EER and COP)
over the intermediate-speed range shall
be calculated using piece-wise linear
fits: a line connecting the minimumand intermediate-speed balance points
and a line connecting the intermediateand maximum-speed balance points.
One-to-one applicability. Carrier
noted the need for transparency in
testing and manufacturer test results so
that interested parties can verify the
performance claims without having to
consult the manufacturer. (Carrier, No.
17 at p. 2) Trane and ARI pointed out
that any steps introduced to facilitate
testing and rating modulating multisplit systems should also be allowed for
modulating one-to-one ducted systems
to promote comparability. (Public
Hearing Tr., pp. 87 and 118; ARI, No. 21
at p. 3) With respect to Carrier’s
comment, variable-speed systems do not
lend themselves to being tested by a
third party who does not have the
cooperation of the outdoor unit
manufacturer. Third-party certification
programs thus become especially
important as they offer the primary
pathway for independent verification.
For those multi-split products that are
not covered by a third-party certification
program, DOE can request from the
manufacturer the information needed to
conduct such testing along with
reviewing the lab test results maintained
by the manufacturer, that substantiate
the multi-split system’s ratings. 10 CFR
430.62(d).
Of the changes being implemented
today to allow testing and rating of
residential modulating multi-split
systems, two changes could be applied
to variable-speed one-to-one units.
Together, these two changes would
allow the manufacturer to specify the
compressor speed used for the
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
intermediate-speed tests and then use
linear fits for calculating COP and EER
within the intermediate-speed operating
range. Adopting these two changes for
variable-speed one-to-one units would
create a second compliance path that
would likely cause different SEER and
HSPF ratings than the current test
procedure. Therefore, in adopting these
changes, DOE is not extending them to
variable-speed one-to-one units.
Although DOE expects the current test
procedure to yield the higher ratings for
one-to-one units, it will rely on the
waiver process if any manufacturer
seeks to adopt these two multi-split test
procedure changes for use in rating
variable-speed one-to-one units.
Tested combination. On the issue of
the ‘‘tested combination’’—the
equipment configuration that can be
tested in the laboratory and thereby
provide a common basis for
comparison—Sanyo, Fujitsu,
Mitsubishi, and ARI recommended
deleting the requirement that the
selected indoor units ‘‘represent the
highest-sales-volume type models’’ and
replacing it with ‘‘represent the highest
sales model family.’’ (Sanyo, No. 15 at
p. 3; Fujitsu, No. 13 at p. 4; Mitsubishi,
No. 20 at pp. 5 and 6; ARI, No. 21 at
p. 6) In addition, Sanyo, Fujitsu,
Mitsubishi, and ARI recommended that
provisions be made in the event that
five of the largest model indoor coils
from the selected model family cannot
provide a cumulative indoor capacity
that is more than 95 percent of the
outdoor unit’s nominal capacity. As to
references in the proposed definition
that a manufacturer will know the
capacity of each indoor unit and each
outdoor unit, Copeland Corporation
(Copeland) questioned how the
manufacturer would determine
component capacities. (Public Hearing
Tr., pp. 217–221) Finally, with regard to
the proposal that all of the tested indoor
units ‘‘have the same external static
pressure,’’ Trane asked how to interpret
that requirement if testing a ducted
multi-split system having indoor units
that have different minimum external
static pressure requirements. (Public
Hearing Tr., p. 229)
DOE accepts the stakeholder
recommendation of substituting the
phrase ‘‘represent the highest sales
model family’’ for the originally
proposed wording, ‘‘represent the
highest sales volume type models,’’
because it has essentially the same
meaning, but is clearer. Although it is
more an issue with commercial multisplit systems, DOE accepts the proposed
wording to clarify the tested
combination since it is more important
to obtain a cumulative indoor capacity
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
that matches the outdoor unit than it is
to restrict selection to units from the
highest sales model family, for cases
where both criteria cannot be met. As
for Copeland’s statement that the
definition includes references to the
capacity of the outdoor unit and the
cumulative capacities of the indoor
units even though no prescriptions are
given to evaluate these capacities, DOE
agrees but nonetheless will allow their
use in this particular definition.
Manufacturers are able to estimate the
rated capacities of the separate
components without conducting the
rigorous testing associated with ARI
Standards 410 (‘‘Forced-Circulation AirCooling and Air-Heating Coils’’) and 540
(‘‘Performance Rating of Positive
Displacement Refrigerant Compressors
and Compressor Units’’) on each new
model. Finally, the last element of the
proposed definition of ‘‘tested
combination’’ will be changed from ‘‘all
have the same external static pressure’’
to ‘‘all be subject to the same minimum
external static pressure requirement
(i.e., 0 inches of water column for nonducted, see Table 2 in Appendix M for
ducted indoor units) while being
configurable to produce the same static
pressure at the exit of each outlet
plenum when manifolded as per section
2.4.1 of Appendix M.’’ This additional
information is provided so that the test
laboratory may conduct the lab testing
by manifolding the outlets of all the
indoor units together and using one
airflow measuring apparatus to
determine the cumulative air volume
rate.
At the August 23, 2006, public
meeting, DOE restated its proposed
interim solution for assigning SEER and
HSPF ratings for untested multi-split
combinations. This interim solution—to
assign the rating measured for the tested
combination to every other combination
using the same outdoor unit—was
included as part of the March 24, 2006,
Federal Register notice that published a
petition for waiver from the residential
package air conditioner and heat pump
test procedures that was received from
Mitsubishi Electric and Electronics
USA, Inc. (Case No. CAC–012). 71 FR
14858. This provision was not in the
July 2006 proposed rule, but was
discussed at the public meeting and
relevant comments were received in the
course of the waiver process. Lennox
and Copeland commented that the rated
system’s combination of indoor units
could be very different from those in the
tested system, and the ratings agreement
would be poor in this case. (Public
Hearing Tr., pp. 245–246)
Because of the difficulty of
prescribing similarity of indoor unit
E:\FR\FM\22OCR3.SGM
22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
pwalker on PROD1PC71 with RULES3
combinations, and with the belief that a
rating that reflects the ‘‘highest sales
model family’’ is better than no rating,
DOE is including this ratings provision
in the final rule, with the additional
stipulation that multi-split
manufacturers must test two or more
combinations with each outdoor unit
unless they have an approved ARM (in
which case, they only need to test one
combination). 10 CFR 430.24(m)(2). One
system shall be tested using only nonducted indoor units that meet the
definition of a tested combination. The
second system shall be tested using only
ducted indoor units that meet the
definition of a tested combination. The
rating given to any untested multi-split
system combination having the same
outdoor unit and all non-ducted indoor
units shall be set equal to the rating of
the tested system having all non-ducted
indoor units. The rating given to any
untested multi-split system combination
having the same outdoor unit and all
ducted indoor units shall be set equal to
the rating of the tested system having all
ducted indoor units. Finally, the rating
given to any untested multi-split system
combination having the same outdoor
unit and a mix of non-ducted and
ducted indoor units shall be set equal to
the average of the ratings for the two
required tested combinations. 10 CFR
430.24(m)(2)(ii). Furthermore, DOE
notes that it is including a provision for
the use of an alternate rating method.
While DOE is not aware of any
algorithms appropriate for rating the
energy efficiency of untested multi-split
system combinations, DOE expects that
as more laboratory test data and field
use data become available, such
algorithms will be developed.
Today’s final rule contains a minor
update that was introduced in the July
2006 proposed rule, removing the limit
on having only one indoor test room. No
comments were received on this
proposed change.
Today’s final rule sufficiently
addresses issues that led to the
requesting and granting of test
procedure waivers for several models of
residential multi-split systems.
Therefore, all existing waivers
concerning residential modulating
multi-split systems terminate on the
effective date of today’s final rule.
Multi-split manufacturers may use the
waiver process described in 10 CFR
430.27 to petition for modification of
today’s test procedure, if necessary.
C. Defining ‘‘Repeatable’’ for Cyclic
Tests
The July 2006 proposed rule
contained two provisions that further
defined repeatable performance during
cyclic tests. One was the requirement
VerDate Aug<31>2005
19:03 Oct 19, 2007
Jkt 214001
that the time-integrated air temperature
difference across the indoor unit for
consecutive ‘‘on’’ cycles must change by
0.05 °F hr or less while the other was
for the average system power
consumption for the complete ‘‘OFF/
ON’’ interval to change by 10 watts or
less from one cycle to the next.
ARI, Sanyo, Carrier, and Nordyne
commented that repeatability should be
addressed by ASHRAE’s Standards
Project Committee (SPC) 116, ‘‘Method
of Testing for Rating Seasonal Efficiency
of Unitary Air Conditioners and Heat
Pumps,’’ not by the DOE test procedure
(ARI, No. 21 at p. 3; Sanyo, No. 15 at
p. 5; Carrier, No. 17 at p. 2; Nordyne,
No. 19 at p. 2) Finally, ACEEE supports
DOE’s efforts to capture the essence of
industry best practices for cyclic testing.
(ACEEE, No. 16 at p. 4)
DOE recognizes that variability is
inherent in testing products for energy
efficiency, including central air
conditioners and central air
conditioning heat pumps. In order to
reduce test variability and increase
repeatability of test results, DOE has set
specific requirements for test set-up and
measurement to reduce variability.
However, even with these requirements,
test variability remains. Furthermore,
DOE notes that the less repeatable the
test, either more units need to be tested
to support an energy efficiency rating
that is representative of the units true
energy efficiency or, if less testing is
done, the product must be rated
conservatively (i.e., lower energy
efficiency rating).4 Test variability can
be further reduced by, for example,
including more specific requirements in
the DOE test procedures as well as
through industry actions, such as
ASHRAE Standard 116. However,
changes to the DOE test procedures to
deal with test variability could increase
the burden and cost of testing. Since the
purpose of this requirement was to
reduce variability and there are
alternative approaches manufacturers
can take to reduce variability, DOE is
not adopting the cyclic changes
proposed. Therefore, as part of today’s
final rule, DOE makes no changes on
defining repeatability during cyclic
tests.
D. Outdoor Air Test Conditions for Units
Having a Two-Capacity Compressor
The July 2006 proposed rule included
provisions that dealt with the outdoor
test conditions for three low-capacity
4 SEER and HSPF values, per the sampling plan
in 10 CFR 430.24, are to be based on the lower 90
percent confidence limit of the true mean divided
by 0.95 (as opposed to the sample mean), thus the
more variability in test results, the more likely that
a product’s SEER and HSPF ratings will have to be
reduced from the true mean.
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
59911
cooling mode tests. The three lowcapacity tests are conducted at different
outdoor dry bulb temperatures (i.e.,
steady-state, wet-coil test at 95 °F
outdoor dry bulb temperature (the A1
Test); the steady-state, dry-coil test at 82
°F (the C1 Test); and the cyclic, dry-coil
test at 82 °F (the D1 Test)). The July 2006
proposal was to have all three of these
tests replaced by equivalent tests
conducted at an outdoor dry bulb
temperature of 67 °F.
ARI, Carrier, and Nordyne supported
replacing the A1 Test with the steadystate, wet-coil, F1 Test at 67 °F because
the change will close a potential
loophole in the current test procedure.
(ARI, No. 21 at p. 3; Carrier, No. 17 at
p. 2; Nordyne, No. 19 at p. 2) This
loophole allowed manufacturers a way
to increase the measured SEER by
disproportionately increasing the
electrical power consumption during
the A1 Test. ACEEE supported the
change in the temperature in the A1 test,
but expressed its concern that the
change may downgrade the importance
of high temperature performance.
(ACEEE, No. 16 at p. 4) ARI, Carrier, and
Nordyne commented that the change in
the C1 and D1 tests is unnecessary since
these tests are optional and the changes
will do very little to improve the
accuracy of SEER. (ARI, No. 21 at p. 3;
Carrier, No. 17 at p. 2; Nordyne, No. 19
at p. 2) Carrier also expressed its
concern that products designed and
tested under the current methodology
may have to be re-rated as a result of the
proposal. (Carrier, No. 17 at p. 2) In
terms of the test procedure, Carrier is
concerned that a different cyclicdegradation coefficient (CD) may result
from replacing the C1 and D1 Tests with
equivalent tests at 67°F.
Collectively, the three proposed
changes make the test conditions for
two-capacity units consistent with the
test conditions specified for variablespeed systems. Implementing all three
changes would result in a more normal
test progression for most two-capacity
units: all wet coil tests followed by the
dry coil test; start with high capacity
tests and end with the low capacity
tests; and start at 95 °F, progress to 82
°F, and then end with 67 °F. These
benefits, however, cannot be realized
because of the possibility of causing a
change in the SEER ratings of some twocapacity units. Thus, DOE agrees with
the general position of the comments
that the proposal to change the outdoor
test conditions for the two optional drycoil CD tests (C1 and D1 tests) is not
warranted.
E:\FR\FM\22OCR3.SGM
22OCR3
59912
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
pwalker on PROD1PC71 with RULES3
Therefore, today’s final rule replaces
the A1 Test with the F1 Test, as
proposed. The F1 Test requires an
outdoor dry bulb temperature of 67 °F,
and for those few cases where it applies,
an outdoor wet bulb temperature of 53.5
°F. The amendments discussed above
are found in sections 3.2.3 and 4.1.3 of
Appendix M.
E. Air Volume Rate Less Than
Manufacturer’s Specified Value
In the July 2006 proposed rule, and
the October 10, 2006, correction notice,
DOE proposed modifications to the
criteria for using an air volume rate that
is less than the manufacturer’s specified
value. The proposal was made to
account for the variability in fan motors,
housings, and wheels. In brief, the
proposed set-up process for the test
procedure provides for making
incremental adjustments in the indoor
fan speed until the indoor unit provides
an external static pressure that is equal
to or greater than the applicable DOE
minimum (i.e., 0.1, 0.15, or 0.20 inch of
water column, if a non-small-duct, highvelocity (SDHV) system), while
operating at the manufacturer-specified
air volume rate or, if needed, at the air
volume rate between 95 percent and 100
percent that produces the corresponding
DOE minimum static pressure value.
For comparison, the current algorithm
in the DOE test procedure does not
allow the air volume rate to be reduced
from 100 percent for the case where the
external static pressure is less than
specified by the test procedure. The
proposed criteria apply to all ducted
blower-coil systems, except those
having a variable-speed motor that is
controlled based on maintaining a
constant air volume rate. The proposed
criteria include two cases where the test
laboratory is instructed to operate at an
air volume rate less than that specified
by the manufacturer: (1) If the highest
indoor fan speed setting cannot yield
the DOE-specified external static
pressure minimum while supplying the
manufacturer-specified air volume rate,
and (2) if the manufacturer’s specified
air volume rate yields a ratio higher
than 37.5 standard cubic feet per minute
(scfm) per 1000 Btu/h.
Nordyne, Carrier and Rheem
supported the proposed criteria for
using an air volume rate that is less than
the manufacturer’s specified value.
(Nordyne, No. 19 at p. 2; Carrier, No. 17
at p. 3; Public Hearing Tr., p. 135; and
Public Hearing Tr., pp. 134–135) ACEEE
commented that since the proposed
language specified which product
designs would be subject to this
requirement, they recommended that
the wording for the types of indoor
VerDate Aug<31>2005
19:03 Oct 19, 2007
Jkt 214001
blowers that are affected by this change
be as generic as possible so as not to
impede product innovation. (Public
Hearing Tr., pp. 132–133)
DOE agrees with ACEEE that the
proposed language could limit
innovation since the proposed
amendment was intended to apply to
designs that are not adequately
addressed by the current air volume
requirements. Since it is impossible to
predict what product designs may enter
the marketplace, specifying the designs
subject to the new provisions may, in
fact, limit innovation. Therefore, in
response to ACEEE’s comment, DOE
restructured the air volume criteria to
indicate that the change applies to all
designs, except variable-speed,
constant-air-volume-rate blowers. In this
way, the variable-speed, constantvolume-rate blowers, which the existing
test procedure adequately addresses,
continue to be subject to the existing
requirement.
F. Updating References to Industry
Standards
The July 2006 proposed rule included
updates to references to current industry
test standards, including ASHRAE
Standard 23–2005, ‘‘Methods of Testing
for Rating Positive Displacement
Refrigerant Compressors and
Condensing Units,’’ ASHRAE Standard
37–2005, ‘‘Methods of Testing for Rating
Electrically Driven Unitary AirConditioning and Heat Pump
Equipment,’’ and ASHRAE Standard
116–1995 (RA2005), ‘‘Methods of
Testing for Rating Seasonal Efficiency of
Unitary Air Conditioners and Heat
Pumps.’’ Nordyne commented in
support of this proposal. (Nordyne, No.
19 at p. 2)
In addition, subsequent to the
publication of the July 2006 proposed
rule, ARI released an updated version of
ARI Standard 210/240, ‘‘Performance
Rating of Unitary Air-Conditioning and
Air-Source Heat Pump Equipment.’’ The
updated version of ARI Standard 210/
240 included references to the DOE test
procedure as amended by the final rule
published on October 11, 2005. This
latest version of ARI Standard 210/240
had not been released at the time that
the content of the July 2006 proposed
rule had been finalized. Since the
updated test procedures do not affect
the measure of efficiency and provide
manufacturers with current test
standards, DOE moves today to adopt
the 2006 version of ARI Standard 210/
240.
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
G. Maximum and Minimum Speed
Values for Calculating NQ and NE
Rheem inquired as to whether the
minimum and maximum speed
quantities needed to evaluate Appendix
M equations 4.1.3–1 and 4.1.3–3 are to
be determined directly from additional
lab testing or from interpolating data
from required tests lab tests at 67 °F, 82
°F, and 95 °F. (NIST, No. 24 at p. 2) In
response, for cooling performance, DOE
modified section 4.1.4 to explicitly state
˙
that the capacities and Qck=1 (87) and
˙
Qck=2 (87), which are used as part of the
algorithm for approximating the slope of
the intermediate compressor speed
(k=v) capacity curve, are determined by
evaluating equations 4.1.3–1 and 4.1.3–
3, respectively, for Tj = 87. Similar
direction is provided for determining
˙
the power consumption quantities Eck=1
˙
(87) and Eck=2 (87) that appear within
the section 4.1.4 equation for NE. For
heating performance, such direction
already exists within the section on
calculating the HSPF for a variablespeed heat pump, with regard to the
source of the minimum speed quantities
at 35 °F.
This change does not affect the
calculated SEER. The revised text is
found following the equation for NE in
section 4.1.4 of Appendix M.
H. Using the Default or Tested Value of
Cyclic-Degradation Coefficient
Carrier asked if the manufacturer
elects to run the optional tests, and the
resulting CD exceeds the 0.25 default
value, is the manufacturer obligated to
use the tested value. (Public Hearing Tr.,
p. 31) The current test procedure
addresses this scenario for most cases
where a CD is used in the SEER and
HSPF calculations. Specifically,
sections 4.1.1, 4.1.2.1, 4.1.3.1, 4.1.4.1,
4.2.1, and 4.2.3.1, direct that if the
optional test(s) are not conducted, the
cooling (heating) cyclic-degradation
coefficient, CDc (CDh), is to be set to the
default value of 0.25. If the optional
test(s) are conducted, CDc (CDh) must to
be set to the lower of: the value
calculated per the test or the default
value of 0.25. In response to Carrier’s
comment, DOE has added similar
wording to sections 4.1.3.3 and 4.2.3.3,
the only sections that did not include
the clarifying language found in the
sections referenced above.
Furthermore, in reviewing the
organization of the current test
procedure while considering this
update, DOE found that the information
would be better placed in the earlier
sections (within section 3) with the
instructions as to which tests to conduct
based on the type of equipment (i.e.,
E:\FR\FM\22OCR3.SGM
22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
single-speed, two-capacity, variablespeed, etc). Therefore, language has
been added in the test procedure to
clarify that if the tested cyclicdegradation coefficient is higher than
the default value, the default value is to
be used to calculate SEER and HSPF.
(see sections 3.2.1, 3.2.2.1, 3.2.3, 3.2.4,
3.5.3, 3.6.1, 3.6.2, 3.6.3, 3.6.4, 3.8.1,
4.1.3.3, and 4.2.3.3).
pwalker on PROD1PC71 with RULES3
I. Guidance on the Inclusion of PreProduction Units in the Sample
Population
As part of the July 2006 proposed
rule, DOE proposed that only preproduction units fabricated using the
same tooling used for the eventual fullproduction units could be used as part
of the tested sample population to
obtain the certified ratings of fullproduction units.
ARI, Nordyne, and Carrier
commented that the proposed wording
is too narrow, and recommended that
the current regulatory language not be
changed. (ARI, No. 21 at p. 4; Nordyne,
No. 19 at p. 3; Carrier, No. 17 at p. 2)
ARI and Trane explained that the
tooling used for pre-production units is
often different than that used for
production units. (Public Hearing Tr.,
pp. 192–193) Trane stated that preproduction units must have the same
configuration as the production unit to
be included in the sample population,
while Carrier suggested using wording
such as that in the ARI Certification
Program Operational Manual to define
the configuration (e.g., same
compressor, same air flow, etc.). (Public
Hearing Tr., pp. 192, 198–199) Rheem
commented that the ARI internal
process handles ratings derived from
pre-production units by making the
model subject to certification testing
immediately after production starts.
(Public Hearing Tr., p. 202)
DOE agrees that the proposed
criterion is too narrow, and that
different tooling can yield equivalent
machinery. Moreover, DOE believes that
spot checks conducted under an
industry certification program, such as
the ARI Certification Program, provide a
safeguard against the performance of the
production unit deviating appreciably
from ratings derived from testing preproduction units. For these reasons,
DOE is not amending the existing
requirements and will continue to allow
manufacturers to test pre-production
units.
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
J. Clarification of the Sample Population
Used To Validate the Rated Seasonal
Energy Efficiency Ratio and Heating
Seasonal Performance Factor of Heat
Pumps
DOE proposed that a manufacturer
must include the cooling and heating
results from each heat pump of the
sample population when obtaining the
certified SEER and HSPF ratings. This
requirement disallows testing multiple
heat pumps and then using a subset of
results for assigning the certified SEER
rating and a different subset of results
for determining the certified HSPF
rating. The proposal provided one
exception, which would allow
additional testing in just one mode,
cooling or heating, if the manufacturer
elected to discontinue testing in the
other mode at some point in the sample
sequence.
ACEEE, Nordyne, and Carrier
supported the intent of clarifying the
sample population used for determining
heat pump ratings. (ACEEE, No. 16 at p.
5; Nordyne, No. 19 at p. 3; Carrier, No.
17 at p. 2) Carrier and the ACEEE,
however, recommended deleting the
exception, noting that additional testing
is insignificant as compared to the
potential for misrepresented ratings.
(Carrier, No. 17 at p. 2; ACEEE, No. 16
at p. 5)
DOE is aware of the testing burden on
manufacturers, but agrees with Carrier
and the ACEEE that this particular
attempt at marginally reducing the test
burden is not worthwhile. Thus, today’s
final rule adopts the proposal that all
units of the sample population must be
tested in both the cooling and heating
modes and the results used for
determining the heat pump’s certified
SEER and HSPF ratings without
adopting the proposed exception for
additional testing.
K. Clarification of the Definition of a
‘‘Highest-Sales-Volume Combination’’
DOE proposed amendments to the
definition of the Highest-Sales-Volume
Combination (HSVC) to require that a
single-speed, split-system air
conditioner must include the coil-only
indoor unit likely to have the largest
volume of retail sales with the particular
model of outdoor unit. Proposed 10 CFR
430.24(m)(2). In addition, DOE
proposed exceptions to this requirement
to provide for equipment designed
exclusively for blower-coil installations:
mini-splits; multi-splits; small-duct,
high-velocity systems; through-the-wall
units; and condensing units having
features (e.g., proprietary interfaces) that
prevent their installation with thirdparty, coil-only indoor units. This
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
59913
proposal was made in recognition that
coil-only units represent the
overwhelming majority of installations
of central air conditioners and, as such,
the highest-sales-volume should reflect
standard practice. The proposal also
minimizes instances where the highestsales volume combination of a splitsystem air conditioner could be defined
as one with a ‘‘blower-coil’’ in order to
meet Federal minimum energy
efficiency standards and then have the
outdoor unit combined with coil-only
indoor units where the combination
would not meet the Federal energy
efficiency standards.
ACEEE, Carrier and ARI agreed that
some clarification to the test procedure
was needed in order to avoid such
situations. (ACEEE, No. 16 at p. 5; ARI,
No. 21 at p. 4; Public Hearing Tr., pp.
208–209) ACEEE supported the goal of
not having outdoor units installed with
coil-only indoor units where the
combination does not meet the energy
efficiency standard. (ACEEE, No. 16 at
p. 5) Instead of the proposed text, ARI
and Carrier recommended that DOE
adopt the wording from the 2006 ARI
Certification Program Operational
Manual for Unitary Air Conditioners &
Air-Source Unitary Heat Pumps (Rated
Below 65,000 Btu/h Cooling). (ARI, No.
21 at p. 4; Public Hearing Tr., pp. 208–
209) Carrier and ARI commented that
the proposed exception for outdoor
units that prevent installations with
coil-only units with a proprietary
interface should be eliminated because
it is not enforceable. Nordyne strongly
objected to the entire proposal, stating
that it restricts a manufacturer’s use of
technology. (Nordyne, No. 19 at pp. 3–
4) Moreover, to implement such a
change, Nordyne asserted that DOE
needs to analyze the impact of
minimally compliant units. Nordyne,
however, did note its support for the
proposed exception for blower coils
having a proprietary interface.
ARI and Carrier recommended the
following alternative text to the July
2006 proposed rule:
HSVTC, Highest-sales-volume Tested
Combination. For Unitary Air-Conditioners
below 14 SEER, the HSVTC must be an RCUA-C combination, except for through-the-wall
and ductless equipment (RCU-A-CBO). For
Unitary Air-Conditioners 14 SEER and above,
every outdoor model number must have a
coil-only rating. Coil-only ratings offered for
sale must be publicly viewable. Coil-only
ratings not offered for sale are viewable only
to ARI staff. Non-viewable ratings fall under
all compliance guidelines except the
challenge procedure. If a non-publicly
viewable rating falls below NAECA
minimum, then the manufacturer must
submit a coil-only rating that meets NAECA
minimum and is verified through ARI testing.
E:\FR\FM\22OCR3.SGM
22OCR3
59914
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
pwalker on PROD1PC71 with RULES3
Until then, the Basic Model Group ratings
will not be listed in the ARI directory.
Historically, the highest sales volume
combination for most split-system air
conditioners has had a coil-only indoor
unit. Both the June 2006 proposed rule
and the ARI alternative maintain this
historical practice. DOE, however,
believes ARI’s approach is arbitrary and
results in uncertainties to
manufacturers. Furthermore, DOE
believes it would be difficult to
implement the above ARI algorithm.
With the ARI approach, the
manufacturer may have to re-test in a
coil-only configuration after having
tested in a blower-coil configuration, if
the expected SEER of 14 or higher is not
realized in laboratory testing. In
addition, if DOE were to adopt the ARI
alternative and the minimum energy
efficiency standards were amended,
DOE would have to modify the
requirement, since the new minimum
could be higher than the 14 SEER
requirement in the ARI alternative.
Conversely, in formulating the approach
proposed in the July 2006 proposed
rulemaking, DOE first considered
requiring that all split-system air
conditioners be tested with a coil-only
indoor unit. DOE recognized, however,
that in addition to the exceptions such
as equipment designed exclusively for
blower-coil installations, other
exceptions would have to be recognized.
These other exceptions include twocapacity and variable-speed units,
because they are always much more
efficient than 14 SEER, and do not risk
having a coil-only combination that
would not meet the DOE efficiency
standards. Therefore, DOE applied the
coil-only requirement only to split
system air conditioners having a singlespeed compressor.
Returning to the issue of listed
exceptions, DOE agrees with ARI and
Carrier that the proposed exception for
combinations that prevent applications
with third-party coil-only indoor units
would be prohibitively difficult to
define, verify, and enforce. DOE
believes that its proposal to substitute
the words ‘‘mini-splits’’ and ‘‘multisplits’’ for ‘‘ductless equipment,’’ is
somewhat more comprehensive because
it includes ducted multi-split systems.
Finally, SDHV manufacturers, at
present, only manufacture indoor coils
and do not manufacture outdoor units.
Since SDHV manufacturers do not offer
for sale complete systems, they are not
subject to specifying HSVC’s. Thus,
SDHV systems do not need to be
included as an exception.
As to Nordyne’s objections, DOE
stands by its position as stated in the
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
July 2006 proposed rule. DOE believes
that its proposal, which is adopted in
today’s final rule, increases the
likelihood that the outdoor unit, in
combination with any compatible
indoor unit, will meet the federal energy
efficiency standards. This is because the
proposal which is adopted today
ensures that the tested combinations,
upon which most ratings are based,
reflect the outdoor-indoor combinations
most likely to be sold. Furthermore, this
language does not limit technology
options to manufacturers, since the test
procedure allows for representations of
other than the highest-sales-volume
combination.
With regard to Nordyne’s comment
that DOE needs to analyze the impact of
the clarifications on minimally
compliant units, DOE fails to see how
the clarification in the definition will
alter the rating of a particular splitsystem air conditioner. The clarification
ensures that the highest-sales-volume
split-system air conditioner—which is
subject to testing—yields ratings
reflective of the outdoor-indoor
combinations most likely to be sold. For
split-system air conditioners
‘‘representative’’ and ‘‘highest sales’’
historically equate to coil-only indoor
units. Only mini-splits, multi-splits, and
through-the-wall units can currently
argue for an exception, since, in these
cases, the outdoor units would be sold
in combination with specific indoor
units which would include a fan and a
coil.
Therefore, DOE is adopting the
language of the July 2006 proposed rule,
to require that the highest sales volume
combination of a single-speed, splitsystem air conditioner must include the
coil-only indoor unit likely to have the
largest volume of retail sales with the
particular model of outdoor unit. The
only change from the proposed rule is
to limit the exceptions to mini-splits,
multi-splits, and through-the-wall units.
L. Upper Limit on the Difference
Between Calculated and Tested
Seasonal Energy Efficiency Ratio and
Heating Seasonal Performance Factor
Values
DOE proposed setting a 5 percent
limit on the amount that a rating for an
untested split-system combination
could exceed the rating of the
corresponding HSVC. 71 FR 41330, July
20, 2006. The proposed limit only
applied to applications where both
combinations used coil-only indoor
units. Ratings based on testing are not
subject to the 5 percent limit.
Manufacturers seeking a rating that
exceeds the 5 percent limit can do so by
testing the particular coil-only
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
combination. The proposed approach
applied to untested combinations
offered by system manufacturers and by
independent coil manufacturers (ICM’s).
ACEEE commented in support of the
proposal to limit the difference between
calculated and tested SEER and HSPF
values. (ACEEE, No. 16 at p. 5) Carrier
and Nordyne also supported the DOE
proposal for SEER ratings but Carrier
does not believe a similar cap is
required for HSPF ratings. (Carrier, No.
17 at p. 3; Nordyne, No. 19 at p. 4)
Using data from the September 2006
ARI Online Directory, Carrier found that
the proposed 5 percent SEER limit
would affect the ratings of 1.05 percent
of OEM coil-only combinations and
13.87 percent of ICM coil-only
combinations. (Carrier, No. 17 at p. 4) At
the public meeting, Carrier offered
similar statistics to show that ICM’s, in
general, rate condenser-coil
combinations employing the same
condenser at higher efficiencies than the
OEM’s. Carrier also offered statistics to
show that a small number of ICM’s
provide most of the ratings that are more
than 5 percent higher than the OEM
rating for the highest-sales combination.
(Public Hearing Tr., p. 265) Carrier also
cites the September 2006 NIST ‘‘Survey
of SEER Ratings for Independent Coil
Manufacturer Mixed Systems’’ as
demonstrating the need to address the
issue. (Carrier, No. 17 at p. 3)
Lennox disagrees with the June 2006
proposal. Lennox points out that the
proposed 5 percent limit is not
technically supported and that the
practical limit is more likely 13 percent
than 5 percent. Lennox notes that the
NIST report referenced above states that
‘‘maximum gains in SEER associated
with coil capacity and improved
expansion devices are approximately 10
percent and 2.5 percent, respectively.’’
(Lennox, No. 22 at p. 1) Lennox reports
that an independent laboratory tested
two different condensing units having
13 SEER HSVC ratings with an alternate,
non-HSVC, evaporator coil. According
to Lennox, the non-HSVC tested
combinations produced SEER ratings
7.9 and 11.8 percent higher than the
13.0 SEER rating of the HSVC units.
Lennox argues that data analysis
conducted by Carrier is incomplete and
that having to test combinations that are
projected to exceed the 5 percent limit
will be overly burdensome. Lennox
further stated that the combination of
DOE approval of the ARM,
governmentally enforceable penalties
for overrating, and an industrysponsored certification program ‘‘ensure
a reasonable level of rating integrity and
result in a full availability of cost
E:\FR\FM\22OCR3.SGM
22OCR3
pwalker on PROD1PC71 with RULES3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
effective, higher efficiency combinations
for consumers.’’ (Lennox, No. 22 at p. 2)
ARI commented that the DOE
proposed 5 percent upper limit is
arbitrary and will unduly penalize
manufacturers who participate in the
ARI certification program. Furthermore,
ARI commented that inconsistent
ratings for untested split-system
combinations have been discussed at
length with the appropriate ARI
committees for quite some time, and,
based on these discussions, significant
changes were made to strengthen the
credibility of the ARI certification
program. (ARI, No. 21 at p. 5) For
example, ARI commented that coil-only
combinations (system manufacturers
and ICMs) with SEER ratings that are 6
percent above the SEER rating of the
highest-sales-volume tested
combination are automatically subject to
testing as part of the ARI certification
program. (ARI, No. 21 at p. 5)
The analysis conducted by Carrier
and NIST certainly justifies further
scrutiny of ratings of untested
combinations of split-system central air
conditioners. The SEER ratings reported
by Lennox raise a few questions, while
suggesting that the proposed mechanism
and 5 percent limit may not be
adequate, but Lennox doesn’t offer an
alternative. For example, how much of
the ratings difference is a result of the
better performance of the mixed system
indoor units? How much of the ratings
difference results from the HSVC rating
being conservative ‘‘ i.e., although rated
at 13.0, the tested SEER of the HSVCs
is likely higher? If the percent
differences reported by Lennox had
been based on the measured SEER of the
HSVC, the respective magnitudes would
likely have been less, possibly much
less.
As for Lennox’s comment that the
NIST report supports a higher
percentage, DOE notes that the NIST
analysis only commented on the effect
of increased coil capacity and an
improved expansion device, two factors
that increase SEER. The impact of the
larger coil on compressor power
consumption, however, was believed
negligible even though it too would
typically increase. Thus, for the nominal
case where a power increase
accompanies the capacity gain, the
maximum SEER increase predicted by
the long-standing NIST ARM is in the 9
to 10 percent range, higher than the 5
percent limit proposed in the NOPR, but
less than the maximum increase stated
by Lennox.
Upon consideration of the above
comments, DOE believes that its 5
percent limit, as proposed, is deficient.
DOE still believes that more scrutiny of
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
untested combination ratings is
warranted. However, DOE finds, from a
review of the data and comments
received, that the ratings of some nonHSVCs are higher that what would seem
warranted. DOE supports the steps
recently implemented by ARI’s
certification program to more frequently
check combinations having suspect
ratings. Moreover, DOE is amending the
test procedure to emphasize its right to
obtain information that is the basis for
any manufacturer’s rating. DOE will
require documentation to justify ratings
more than 6 percent higher that the
rated efficiency of the HSVC unit. If
DOE questions the rating, the
manufacturer will be responsible for
verifying the ARM, and supplying to
DOE the ARM used and furnishing the
specific input parameters used for each
condenser-evaporator combination, the
energy efficiency rating of the HSVC,
the energy efficiency results of the
ARM, and the rated energy efficiency of
the units in question. Furthermore, the
manufacturer must be prepared to
provide the information source and/or
justification for any input parameter.
In summary, DOE is not adopting the
proposed 5 percent limit on the
maximum amount that a rating for an
untested coil-only split-system can
exceed the rating of the HSVC. Instead,
DOE will evaluate the improvements
available through using new and
improved ARMs and the results from
internal changes made as part of the ARI
Certification Program. DOE will give
follow-up priority to individual
combinations having questionably high
ratings (for example, a coil-only system
having a rating that exceeds the rating
of a coil-only highest sales volume
combination by more than 6 percent).
The text that sets forth DOE’s authority
to examine ratings for untested split
system combinations is found in 10 CFR
430.24(m)(5) of today’s rule.
M. Clarification of the Published Ratings
for Untested Split-System Combinations
DOE proposed amendments to 10 CFR
430.24(m)(4) to require published
ratings for an untested split-system
combination to be equal to, or lower
than, the value calculated using the
DOE-approved ARM. 71 FR 41336. The
proposed language specifically
recognized that a manufacturer may use
laboratory data from the HSVC testing to
adjust or ‘‘tune’’ its ARM, or a
simulation subcomponent, when
calculating the ratings for untested
combinations that use the same outdoor
unit. Under the proposal, the amount of
adjustment is limited to a 5 percent
increase in the calculated rating
compared to the rating obtained using
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
59915
the ARM without the adjustment/tuning
factor. The purpose is to limit the
amount of manufacturer’s ‘‘tuning’’ of
ARMs, without resubmitting the ARM
for DOE review in accordance with 10
CFR 430.24(m)(5). DOE is concerned
that the ‘‘tuned’’ ARMs will result in a
different model than the one the
Department had reviewed and approved
under 10 CFR 430.24(m)(5). The
changes were proposed to improve the
current regulatory language that states
the ARM must be used to obtain
‘‘representative values of the measures
of energy consumption.’’ 10 CFR
430.24(m)(2)(ii).
ARI commented that ‘‘untested’’
combinations are subject to verification
testing in the ARI Certification Program
and so placing a limit on the adjustment
factor is unwarranted for combinations
listed in the ARI directory. (ARI, No. 21
at p. 5) Carrier commented that any
adjustment based on actual testing to be
not only allowable but desirable.
(Carrier, No. 17 at p. 3) Nordyne was
willing to consider the concept of a
maximum allowable adjustment but
stated that the exact values and the
specific wording needed further review.
(Nordyne, No. 19 at p. 4)
In reviewing its files of ARMs that
DOE has approved, DOE finds that none
reference an ARM/simulation
adjustment factor, or equivalent. Yet,
the use of such adjustment factors
appears to be common. This situation,
along with the fact that most
manufacturers’ ARMs have not been
updated in many years, and that most,
if not all, of the models upon which the
ARMs were based have been removed
from the marketplace because they did
not meet the 13 SEER standard leads
DOE to conclude that it is likely some
ARMs need the adjustment factor in
order to correctly predict the efficiency
of untested combinations.
In view of the foregoing, DOE is
amending 10 CFR 430.24(m)(5) to
require published ratings for an
untested split-system combination to be
equal to, or lower than, the value
calculated using the DOE-approved
ARM. The practice of ‘‘tuning’’ an ARM
or computer simulation by using
laboratory data from tests on the HSVC
or any other split-system combination
tested in accordance with the sample
plan of 10 CFR 430.24(m), and then
using the tuned ARM to calculate the
ratings for untested combinations that
use the same outdoor unit, is now
referenced in 10 CFR 430.24(m)(4).
DOE, however, is not adopting a limit
on how much the SEER/HSPF rating,
calculated using an ARM, may exceed
the rating obtained without using the
adjustment factor.
E:\FR\FM\22OCR3.SGM
22OCR3
59916
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
N. Ratings That Are Based on Using a
Particular Furnace or Ducted Air Mover
DOE proposed having manufacturers
document those published ratings that
are based on a complete system
consisting of a coil-only air conditioner
or heat pump and a particular model of
furnace. The model number of the
furnace would be published, most likely
in addition to the indoor unit model
number.
ACEEE supported the measure, as
originally proposed. (ACEEE, No. 16 at
p. 5) Nordyne and ARI also supported
the measure but suggest replacing the
word ‘‘furnace’’ with a more generic
term so that the requirement is extended
to all indoor air movers. (Nordyne, No.
19 at p. 4; ARI, No. 21 at p. 6) Nordyne
suggests using ‘‘indoor blower’’ and ARI
suggests ‘‘ducted air mover.’’
DOE accepts the recommendation of
using generic wording to clearly convey
the equipment components that
contribute to the published rating, and
selects the description ‘‘ducted air
mover.’’ DOE adopts revised text for 10
CFR 430.62(a)(4)(i) and (ii) that
explicitly states that the model number
of the ducted air mover, if applicable,
must be included among the
manufacturer’s model numbers
submitted on the certification report to
DOE. Compared to the wording
proposed in the July 2006 proposed
rule, today’s revision is simpler, in that
it does not repeat text from 10 CFR
430.62(a)(4) in sections 430.62(a)(4)(i)
and (a)(4)(ii).
pwalker on PROD1PC71 with RULES3
O. Revisions to the Definition of ‘‘Coil
Family’’
DOE proposed minor modifications to
the existing definition of ‘‘coil family,’’
to improve its readability and make it
easier to understand. 71 FR 41335.
Nordyne and Rheem asked for
clarifications to the proposed language.
(Nordyne, No. 19 at p. 4)
Concerning Nordyne’s comment, DOE
had no intention other than to offer a
few editorial improvements, and to
heighten awareness of the definition
among stakeholders, given the related
discussion of ARMs. As proposed, DOE
viewed the substantive content of the
definition as adequate for the purpose of
designating what split systems may be
used for verifying an ARM. There was
no change proposed to the definition of
‘‘coil family’’ with respect to coil
circuitry. In both the current and
proposed test procedures, ‘‘coil
circuitry’’ is included in a list of design
features that affect heat exchanger
performance. In responding to the
question raised by Rheem, NIST asked
attendees at the public meeting how to
VerDate Aug<31>2005
18:36 Oct 19, 2007
Jkt 214001
define coil circuitry. Trane responded
that if this coil differentiating feature
were deleted then it wouldn’t have to be
defined. (Public Hearing Tr., p. 297)
In considering the comments
received, DOE finds the proposed
amendments to the definition cause
more confusion than the existing
definition, therefore, DOE is not
amending the definition of coil circuitry
at this time.
III. Summary of Other Additions,
Changes, and Corrections to the
Department of Energy Residential
Central Air Conditioner and Heat Pump
Test Procedure
The following discussion summarizes
revisions that were proposed in the July
2006 proposed rule and received no
substantive comments.
Small-duct, high-velocity (SDHV)
systems. Today’s final rule adopts the
following five changes that apply
exclusively to small-duct, high-velocity
(SDHV) systems:
—The minimum external-static-pressure
levels that must be equaled or
exceeded during the first test on any
SDHV system will be 1.0 inches of
water column higher than the
minimum that is required of nonSDHV units. For example, for
equipment having rated cooling
capacities from 29,000 to 42,500 Btu/
h, the minimum external static
pressure is 1.15 inches of water
column for SDHV systems, compared
to 0.15 inches of water column for
conventional blower-coil systems.
This change is found in section
3.1.4.1.1 of Appendix M.
—All balance dampers or restrictor
devices on or inside the unit must be
set fully open or on the lowest
restriction setting. This change is
found in section 2.2 of Appendix M.
—The size of the duct connected to the
outlet of the indoor unit must not
exceed prescribed limits. This change
is found in section 2.4.1 of Appendix
M.
—When a closed-loop, air-enthalpy test
apparatus is used on the indoor side,
the test laboratory must limit the
airflow resistance on the inlet-side of
the indoor blower-coil to a maximum
value of 0.1 inches of water column.
The balance of the airflow resistance
must be imposed on the outlet-side of
the indoor blower. This change is
found in section 3.1.4.1.1 of
Appendix M.
—The test setup must include an
adjustable air damper that is
positioned immediately upstream of
the airflow measuring apparatus that
limits the differential pressure
between the inside of the duct and the
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
surrounding ambient to 0.5 inches of
water column or less. If the particular
test setup permits, the outlet air
damper box used for cyclic tests can
double as the adjustable air damper.
This change is found in section
2.5.4.3 of Appendix M.
Optional high-capacity cyclicdegradation coefficient (CD). Today’s
final rule reinstates the optional highcapacity cyclic-degradation coefficient
(CD) testing for two-capacity units that
lock out low-capacity operation at
outdoor temperatures where the unit is
otherwise projected to modulate
between low and high capacities/
compressor stages. In lieu of testing, the
default value for the high-capacity CD
will be the value of the low-capacity CD.
The specific change is reflected in
sections 3.2.3, 3.4, 3.5, 3.5.3, 3.6.3, 3.8,
3.8.1, 4.1.3.3, and 4.2.3.3 of Appendix
M.
Two-capacity heat pump default
equations. Instead of conducting the
laboratory test, default equations are
now provided to approximate the
performance of a two-capacity heat
pump operating at low capacity and
35 °F outdoor temperature. The default
equations appear in section 3.6.3 of
Appendix M.
Duct loss correction. Except as noted
below, DOE adopts the practice of
applying a duct loss correction to the
cooling and heating capacities
determined using the indoor air
enthalpy method. The losses occur
within the section of insulated duct that
extends between the outlet of the indoor
unit and the test facility’s outlet
temperature grid. The correction,
however, does not apply to the two
indoor capacities used for calculating a
cyclic-degradation coefficient, CD. The
change affects sections 3.3, 3.4, 3.7,
3.9.1, and 3.11 of Appendix M and is
implemented by referencing sections
7.3.3.3 and 7.3.4.3 of ASHRAE Standard
37–2005 for cooling and heating tests,
respectively.
Air volume. DOE adopts the definition
of ‘‘standard air’’ as given in ASHRAE
Standard 37–2005. This change affects
section 1.37 of Appendix M and causes
standard air volume rates to be
expressed in terms of dry air, not moist
air. DOE replaces the proper names
containing the words ‘‘Certified Air
Volume Rate’’ with ‘‘Full-load Air
Volume Rate.’’ The change will
eliminate confusion over whether the
air volume rates specified in the test
procedure are certified values, which
they are not. This change appears in
numerous places within the DOE test
procedure, mostly in section 3 and
E:\FR\FM\22OCR3.SGM
22OCR3
pwalker on PROD1PC71 with RULES3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
Tables 3 to 6 and Tables 9 to 12 of
Appendix M.
ARMs. DOE adopts revised language
for 10 CFR 430.24(m)(6) that describes
the specific information the
manufacturer must include in its
submittal when requesting DOE’s
approval of the manufacturer’s ARM.
The revision expands the options
regarding the data used to evaluate and
verify the ARM and provides a
compliance path for manufacturers who
offer indoor units from only one coil
family.
Definitions. DOE incorporates the
definition for ‘‘private labelers’’ from
EPCA, 42 U.S.C. 6291(15) into 10 CFR
430.2. Definitions for the terms ‘‘indoor
unit,’’ ‘‘outdoor unit,’’ and ‘‘ARM/
simulation adjustment factor’’ have also
been added. Under 10 CFR
430.24(m)(5), DOE adopts revised
language to specify that the
requirements also apply to private
labelers, and not just to manufacturers.
For example, private labelers, like
manufacturers, are responsible for
ensuring that reported ratings for
untested split-system combinations are
based on a DOE-approved ARM.
October 2005 final rule. In addition,
DOE is correcting two errors that were
mistakenly introduced in the test
procedure final rule published on
October 11, 2005. 70 FR 59122. The
October 2005 final rule incorrectly
specifies the outdoor test conditions
used for the optional low-capacity
heating-mode cyclic test for twocapacity heat pumps. The temperatures
for this test are incorrectly specified in
the October 2005 final rule as 62 °F db/
56.5°F wb. These temperatures should
have remained as they were, with the
values 47°F db/43°F wb. This error was
unfortunately not discovered until after
the final rule became effective on April
10, 2006. DOE has been informed that
several new models of two-capacity heat
pumps have been rated for HSPF based
on conducting the low-capacity heating
mode cyclic test at 62 °F db/56.5 °F wb.
In implementing the test condition
correction, DOE will not require that
these affected models of two-capacity
heat pumps be retested and rerated
since the difference in energy efficiency
is very slight, (i.e., tenths of HSPF). This
correction appears in section 3.6.3b and
Table 11 of Appendix M.
The second correction affects two
equations used for calculating the HSPF
of a variable-speed heat pump. Within
section 4.2.4 of Appendix M of the final
rule published on October 11, 2005, the
terms NQ and NE are incorrectly
positioned within the equations for MQ
and ME, respectively. MQ and ME
correspond to the slopes of the capacity
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
and power curves when the heat pump
is operated at the intermediate
compressor speed, k = v. These
intermediate speed slopes are derived
from the slopes of the minimum and
maximum speed curves, weighting each
accordingly. The terms NQ and NE are
the weighting factors for the maximum
speed slopes.
In the October 2005 final rule, section
4.2.4 of Appendix M, the equations for
MQ and ME each consist of the sum of
two expressions in square brackets. In
the right-hand bracketed expression of
both equations, the divisor line is too
long. It should not extend under NQ in
the equation for MQ, nor should it
extend under NE in the equation for ME.
The divisor line is being shortened so
that the equation returns to its format
established in the 1988 revision of the
test procedure. (53 FR 8304, March 14,
1988). The same misprint did not occur
within the comparable cooling mode
equations.
IV. Effect of Test Procedure Revisions
on Compliance With Standards
In amending a test procedure, section
323(e) of EPCA directs DOE to
determine to what extent, if any, the test
procedure would alter the measured
energy efficiency of the covered product
and if the amended test procedure alters
the measured efficiency, the Secretary is
to amend the applicable energy
conservation standard to the extent the
amended test procedure changes the
energy efficiency of products that
minimally comply with the existing
standard. (42 U.S.C. 6293(e)) In
recognition of this requirement, the July
2006 proposed rule requested comments
on whether any of the proposed changes
would affect the measures of energy
efficiency, and, if so, to what extent,
when tested under the current test
procedure. DOE received no comments
in response. The issue was also raised
at the public hearing, and DOE again
received no comments that any models
would fail to meet the standard when
tested using the new test procedure.
Since DOE did not receive comments on
this issue, and based on the discussion
below, DOE concludes that the
amendments to the central air
conditioner and central air conditioning
test procedures adopted in today’s final
rule do not change the measure of
energy efficiency of central air
conditioners and central air
conditioning heat pumps that minimally
comply with the existing standard.
Therefore, amendments to the existing
energy efficiency standard are not
required.
Some revisions in today’s final rule
are expected to slightly change the
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
59917
ratings of two-capacity systems. Since
two-capacity systems are inherently
more energy efficient, DOE concludes
that these amendments would only
affect higher efficiency systems and,
therefore, not require DOE to amend its
energy conservation standards.
The change to allow the use of default
equations instead of conducting a lowcapacity Frost Accumulation Test will
negatively impact the measured HSPF.
DOE estimates that the HSPF could be
as much as 0.3 point lower if the default
equations are used to obtain the value
corresponding to climate Region IV and
the minimum design-heating
requirement instead of testing. This
change will not affect the HSPF of a
currently rated heat pump because use
of the default equations is optional and
DOE understands manufacturers test
products instead of using the default
value and, therefore, there is no change
as a result of today’s revisions.
Changing the maximum duration of
all Frost Accumulation Tests from 12
hours to 6 hours is expected to only
affect the average space heating capacity
and power at 35 °F by causing a
minimal, systematic increase in the
derived HSPF for the rare case where
the heat pump remains completely
frosted beyond 6 hours. DOE believes
such a situation is extremely unlikely,
especially for tests at full-load.
DOE does not expect that adopting the
practice of applying a duct loss
correction to the cooling and heating
capacities determined using the indoor
air enthalpy method to cause an
increase in SEER or HSPF. This is
because the test procedure is simply
catching up with current practice.
Making the definition of ‘‘standard
air’’ consistent with the definition in
ASHRAE Standard 37–2005 will have
no effect on the SEER and HSPF as
calculated using the October 2005 final
rule. 70 FR 59122 (October 11, 2005).
Finally, changing the one steady-state,
low-capacity cooling-mode test
condition from 95 °F to 67 °F for twocapacity units is projected to change the
calculated SEER very minimally—
within ± 0.1 SEER point—in most cases.
However, the reduction in SEER could
be very considerable if the power
consumption during the 95 °F test at low
capacity is increased in an effort to
obtain lower estimates, through
extrapolation, of the power
consumption for low-capacity at
temperatures less than 82 °F. In general,
the impact of the change will be
measurable if the unit’s electrical power
draw increases atypically at higher
outdoor temperatures when operating at
low capacity. However, two-capacity
compressors are inherently more energy
E:\FR\FM\22OCR3.SGM
22OCR3
59918
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
efficient and are not used in minimally
compliant units, and, therefore, DOE
concludes that this amendment to the
test procedure will not change the
energy efficiency of marginally
compliant units.
V. Procedural Requirements
A. Review Under Executive Order 12866
Today’s regulatory action is not a
‘‘significant regulatory action’’ under
section 3(f) of Executive Order 12866,
Regulatory Planning and Review, 58 FR
51735 (October 4, 1993). Accordingly,
this action was not subject to review
under the Executive Order by the Office
of Information and Regulatory Affairs in
the Office of Management and Budget.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility
analysis for any rule that by law must
be proposed for public comment, unless
the agency certifies that the rule, if
promulgated, will not have a significant
economic impact on a substantial
number of small entities. As required by
Executive Order 13272, Proper
Consideration of Small Entities in
Agency Rulemaking, 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the
rulemaking process. (68 FR 7990) The
DOE procedures and policies are
available on the Office of General
Counsel’s Web site: https://
www.gc.doe.gov.
DOE reviewed today’s final rule under
the provisions of the Regulatory
Flexibility Act and the procedures and
policies published on February 19,
2003. 68 FR 7990. DOE certified in the
July 20, 2006, proposed rule that the
proposed rule would not impose a
significant economic impact on a
substantial number of small entities. (66
FR 6780) DOE received no comments on
this issue, and after considering the
potential small entity impact of this
final rule, DOE affirms the certification
that this rule will not have a significant
economic impact on a substantial
number of small entities.
pwalker on PROD1PC71 with RULES3
C. Review Under the Paperwork
Reduction Act of 1995
This rulemaking imposes no new
information or record keeping
requirements. Accordingly, Office of
Management and Budget (OMB)
clearance is not required under the
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
Paperwork Reduction Act. (44 U.S.C.
3501 et seq.)
D. Review Under the National
Environmental Policy Act of 1969
DOE has determined that this rule
falls into a class of actions that are
categorically excluded from review
under the National Environmental
Policy Act of 1969 (42 U.S.C. 4321 et
seq.) and DOE’s implementing
regulations at 10 CFR part 1021. This
rule amends an existing rule without
changing its environmental effect, and,
therefore, is covered by the Categorical
Exclusion in paragraph A5 to subpart D,
10 CFR part 1021. Accordingly, neither
an environmental assessment nor an
environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999) imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have federalism implications. The
Executive Order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive Order also requires agencies
to have an accountable process to
ensure meaningful and timely input by
State and local officials in the
development of regulatory policies that
have federalism implications. On March
14, 2000, DOE published a statement of
policy describing the intergovernmental
consultation process it will follow in the
development of such regulations. (65 FR
13735) DOE examined this final rule
and determined that it does not have a
substantial direct effect on the States, on
the relationship between the national
government and the States, or on the
distribution of power and
responsibilities among the various
levels of government. Executive Order
13132 requires no further action.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform’’ 61 FR 4729 (February 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; and
(3) provide a clear legal standard for
affected conduct rather than a general
standard and promote simplification
and burden reduction. Section 3(b) of
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in section 3(a) and section
3(b) to determine whether they are met
or it is unreasonable to meet one or
more of them. DOE has completed the
required review and determined that, to
the extent permitted by law, this rule
meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (Pub. L. 104–4)
(UMRA) requires each Federal agency to
assess the effects of Federal regulatory
actions on State, local, and Tribal
governments and the private sector. For
a proposed regulatory action that may
result in the expenditure by State, local
and Tribal governments, in the
aggregate, or by the private sector of
$100 million or more (adjusted annually
for inflation), section 202 of UMRA
requires a Federal agency to publish
estimates of the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a),(b)) UMRA
also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA (62 FR
12820) (also available at https://
www.gc.doe.gov). The rule published
today contains neither an
intergovernmental mandate, nor a
mandate that may result in an
expenditure of $100 million or more in
any year, so these requirements do not
apply.
E:\FR\FM\22OCR3.SGM
22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
rule would not have any impact on the
autonomy or integrity of the family as
an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
energy supply, distribution, or use
should the proposal be implemented,
and of reasonable alternatives to the
action and their expected benefits on
energy supply, distribution, and use.
Today’s regulatory action would not
have a significant adverse effect on the
supply, distribution, or use of energy
and, therefore, is not a significant
energy action. Accordingly, DOE has not
prepared a Statement of Energy Effects.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 18, 1988), that this regulation
would not result in any takings which
might require compensation under the
Fifth Amendment to the United States
Constitution.
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91), the Department of Energy must
comply with section 32 of the Federal
Energy Administration Act of 1974
(FEAA), as amended by the Federal
Energy Administration Authorization
Act of 1977. (15 U.S.C. 788) Section 32
provides in essence that, where a
proposed rule contains or involves use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. This final rule updates
references to the most recent versions of
four commercial standards, as discussed
in section II.F of this preamble.
The Department has evaluated these
standards and is unable to conclude
whether they fully comply with the
requirements of section 32(b) of the
FEAA, i.e., that they were developed in
a manner which fully provides for
public participation, comment and
review. As required by section 32(c) of
the FEAA, the Department has
consulted with the Attorney General
and the Chairman of the Federal Trade
Commission concerning the impact of
these four standards on competition,
and neither recommended against
incorporation of these standards.
pwalker on PROD1PC71 with RULES3
J. Review Under the Treasury and
General Government Appropriations
Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) requires
agencies to review most disseminations
of information to the public under
guidelines established by each agency
pursuant to general guidelines issued by
OMB. OMB’s guidelines were published
at 67 FR 8452 (February 22, 2002), and
DOE’s guidelines were published at 67
FR 62446 (October 7, 2002). DOE has
reviewed today’s notice under the OMB
and DOE guidelines and has concluded
that it is consistent with applicable
policies in those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OIRA, a
Statement of Energy Effects for any
proposed significant energy action. A
‘‘significant energy action’’ is defined as
any action by an agency that
promulgated or is expected to lead to
promulgation of a final rule, and that:
(1) Is a significant regulatory action
under Executive Order 12866, or any
successor order; and (2) is likely to have
a significant adverse effect on the
supply, distribution, or use of energy, or
(3) is designated by the Administrator of
OIRA as a significant energy action. For
any proposed significant energy action,
the agency must give a detailed
statement of any adverse effects on
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of today’s rule prior to its effective date.
The report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
VI. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
List of Subjects in 10 CFR Part 430
Administrative practice and
procedure, Energy conservation,
Household appliances, Incorporation by
reference.
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
59919
Issued in Washington, DC, on September
27, 2007.
Alexander A. Karsner,
Assistant Secretary, Energy Efficiency and
Renewable Energy.
For the reasons set forth in the
preamble, Part 430 of Chapter II of Title
10, Code of Federal Regulations is
amended as set forth below:
PART 430—ENERGY CONSERVATION
PROGRAM FOR CONSUMER
PRODUCTS
1. The authority citation for part 430
continues to read as follows:
I
Authority: 42 U.S.C. 6291–6309; 28 U.S.C.
2461 note.
2. Section 430.2 is amended in
subpart A by adding definitions of
‘‘ARM/simulation adjustment factor,’’
‘‘indoor unit,’’ ‘‘outdoor unit,’’ ‘‘private
labeler,’’ and ‘‘tested combination,’’ in
alphabetical order, to read as follows:
I
§ 430.2
Definitions.
*
*
*
*
*
ARM/simulation adjustment factor
means a factor used as part of a DOEapproved alternative rating method
(ARM) to improve the accuracy of the
calculated ratings for untested splitsystem central air conditioners or heat
pumps. The adjustment factor
associated with each outdoor unit must
be set such that it reduces the difference
between the SEER (HSPF) determined
using the ARM and a split-system
combination tested in accordance with
§ 430.24(m)(1). The ARM/simulation
adjustment factor is an integral part of
the ARM and must be a DOE-approved
element in accordance with 10 CFR
430.24(m)(4) to (m)(6).
*
*
*
*
*
Indoor unit means a component of a
split-system central air conditioner or
heat pump that is designed to transfer
heat between the refrigerant and the
indoor air, and which consists of an
indoor coil, a cooling mode expansion
device, and may include an air moving
device.
*
*
*
*
*
Outdoor unit means a component of
a split-system central air conditioner or
heat pump that is designed to transfer
heat between the refrigerant and the
outdoor air, and which consists of an
outdoor coil, compressor(s), an air
moving device, and in addition for heat
pumps, a heating mode expansion
device, reversing valve, and defrost
controls.
*
*
*
*
*
Private labeler means an owner of a
brand or trademark on the label of a
consumer product which bears a private
E:\FR\FM\22OCR3.SGM
22OCR3
59920
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
label. A consumer product bears a
private label if:
(1) Such product (or its container) is
labeled with the brand or trademark of
a person other than a manufacturer of
such product;
(2) The person with whose brand or
trademark such product (or container) is
labeled has authorized or caused such
product to be so labeled; and
(3) The brand or trademark of a
manufacturer of such product does not
appear on such label.
*
*
*
*
*
Tested combination means a multisplit system with multiple indoor coils
having the following features:
(1) The basic model of a system used
as a tested combination shall consist of
one outdoor unit, with one or more
compressors, that is matched with
between 2 and 5 indoor units; for multisplit systems, each of these indoor units
shall be designed for individual
operation.
(2) The indoor units shall—
(i) Represent the highest sales model
family, or another indoor model family
if the highest sales model family does
not provide sufficient capacity (see ii);
(ii) Together, have a nominal capacity
that is between 95% and 105% of the
nominal capacity of the outdoor unit;
(iii) Not, individually, have a capacity
that is greater than 50% of the nominal
capacity of the outdoor unit;
(iv) Operate at fan speeds that are
consistent with the manufacturer’s
specifications; and
(v) All be subject to the same
minimum external static pressure
requirement (i.e., 0 inches of water
column for non-ducted, see Table 2 in
Appendix M to Subpart B of this part for
ducted indoor units) while being
configurable to produce the same static
pressure at the exit of each outlet
plenum when manifolded as per section
2.4.1 of Appendix M.
*
*
*
*
*
§ 430.22
[Amended]
3. Section 430.22 is amended as
follows:
I a. Paragraph (b)(5)2. is amended by
removing ‘‘23–1993’’ and adding in its
place ‘‘23–2005.’’
I b. Paragraph (b)(5)3. is amended by
removing ‘‘37–1988’’ and adding in its
place ‘‘37–2005.’’
I c. Paragraph (b)(5)8. is amended by
removing ‘‘116–1995’’ and adding in its
place ‘‘116–1995 (RA 2005).’’
I d. Paragraph (b)(8) is amended by
removing ‘‘210/240–2003’’ and adding
in its place ‘‘210/240–2006.’’
pwalker on PROD1PC71 with RULES3
I
4. Section 430.23 is amended in
subpart B by revising paragraph (m)(5)
to read as follows:
I
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
§ 430.23 Test procedures for the
measurement of energy and water
consumption.
*
*
*
*
*
(m) * * *
(5) All measures of energy
consumption must be determined by the
test method as set forth in appendix M
to this subpart; or by an alternative
rating method set forth in § 430.24(m)(4)
as approved by the Assistant Secretary
for Energy Efficiency and Renewable
Energy in accordance with
§ 430.24(m)(5).
*
*
*
*
*
5. Section 430.24 is amended in
subpart B by revising paragraph (m) to
read as follows:
I
§ 430.24
Units to be tested.
*
*
*
*
*
(m)(1) For central air conditioners and
heat pumps, each single-package system
and each condensing unit (outdoor unit)
of a split-system, when combined with
a selected evaporator coil (indoor unit)
or a set of selected indoor units, must
have a sample of sufficient size tested in
accordance with the applicable
provisions of this subpart. The
represented values for any model of
single-package system, any model of a
tested split-system combination, any
model of a tested mini-split system
combination, or any model of a tested
multi-split system combination must be
assigned such that —
(i) Any represented value of estimated
annual operating cost, energy
consumption or other measure of energy
consumption of the central air
conditioner or heat pump for which
consumers would favor lower values
must be no less than the higher of:
(A) The mean of the sample; or
(B) The upper 90-percent confidence
limit of the true mean divided by 1.05;
(ii) Any represented value of the
energy efficiency or other measure of
energy consumption of the central air
conditioner or heat pump for which
consumers would favor higher values
must be no greater than the lower of:
(A) The mean of the sample; or
(B) The lower 90-percent confidence
limit of the true mean divided by 0.95;
(iii) For heat pumps, all units of the
sample population must be tested in
both the cooling and heating modes and
the results used for determining the heat
pump’s certified SEER and HSPF ratings
in accordance with paragraph (m)(1)(ii)
of this section.
(2) For split-system air conditioners
and heat pumps, the condenserevaporator coil combination selected for
tests pursuant to paragraph (m)(1) of
this section shall include the evaporator
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
coil that is likely to have the largest
volume of retail sales with the particular
model of condensing unit. For minisplit condensing units that are designed
to always be installed with more than
one indoor unit, a ‘‘tested combination’’
as defined in 10 CFR 430.2 shall be used
for tests pursuant to paragraph (m)(1) of
this section. For multi-split systems,
each model of condensing unit shall be
tested with two different sets of indoor
units. For one set, a ‘‘tested
combination’’ composed entirely of nonducted indoor units shall be used. For
the second set, a ‘‘tested combination’’
composed entirely of ducted indoor
units shall be used. Components of
similar design may be substituted
without requiring additional testing if
the represented measures of energy
consumption continue to satisfy the
applicable sampling provisions of
paragraphs (m)(1)(i) and (m)(1)(ii) of this
section. However, for any split-system
air conditioner having a single-speed
compressor, the condenser-evaporator
coil combination selected for tests
pursuant to paragraph (m)(1) of this
section shall include the indoor coilonly unit that is likely to have the
largest volume of retail sales with the
particular model of outdoor unit. This
coil-only requirement does not apply to
split-system air conditioners that are
only sold and installed with blower-coil
indoor units, specifically mini-splits,
multi-splits, and through-the-wall units.
This coil-only requirement does not
apply to any split-system heat pumps.
For every other split-system
combination that includes the same
model of condensing unit but a different
model of evaporator coil and for every
other mini-split and multi-split system
that includes the same model of
condensing unit but a different set of
evaporator coils, whether the evaporator
coil(s) is manufactured by the same
manufacturer or by a component
manufacturer, either—
(i) A sample of sufficient size,
comprised of production units or
representing production units, must be
tested as complete systems with the
resulting ratings for the outdoor unitindoor unit(s) combination obtained in
accordance with paragraphs (m)(1)(i)
and (m)(1)(ii) of this section; or
(ii) The representative values of the
measures of energy efficiency must be
assigned as follows,
(A) Using an alternative rating method
(ARM) that has been approved by DOE
in accordance with the provisions of
paragraphs (m)(4) through (m)(6) of this
section; or
(B) For multi-split systems composed
entirely of non-ducted indoor units, set
equal to the system tested in accordance
E:\FR\FM\22OCR3.SGM
22OCR3
pwalker on PROD1PC71 with RULES3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
with paragraph (m)(1) of this section
whose tested combination was entirely
non-ducted indoor units;
(C) For multi-split systems composed
entirely of ducted indoor units, set
equal to the system tested in accordance
with paragraph (m)(1) of this section
whose tested combination was entirely
ducted indoor units; and
(D) For multi-split systems having a
mix of non-ducted and ducted indoor
units, set equal to the mean of the
values for the two systems — one
having the tested combination of all
non-ducted units and the second having
the tested combination of all ducted
indoor units — tested in accordance
with paragraph (m)(1) of this section.
(3) Whenever the representative
values of the measures of energy
consumption, as determined by the
provisions of paragraph (m)(2)(ii) of this
section, do not agree within 5 percent of
the representative values of the
measures of energy consumption as
determined by actual testing, the
representative values determined by
actual testing must be used to comply
with section 323(c) of the Act or to
comply with rules under section 324 of
the Act.
(4) The basis of the ARM referred to
in paragraph (m)(2)(ii) of this section
must be a representation of the test data
and calculations of a mechanical vaporcompression refrigeration cycle. The
major components in the refrigeration
cycle must be modeled as ‘‘fits’’ to
manufacturer performance data or by
graphical or tabular performance data.
Heat transfer characteristics of coils may
be modeled as a function of face area,
number of rows, fins per inch,
refrigerant circuitry, air-flow rate and
entering-air enthalpy. Additional
performance-related characteristics to be
considered may include type of
expansion device, refrigerant flow rate
through the expansion device, power of
the indoor fan and cyclic-degradation
coefficient. Ratings for untested
combinations must be derived from the
ratings of a combination tested in
accordance with paragraph (m)(1) of this
section. The seasonal energy efficiency
ratio (SEER) and/or heating seasonal
performance factor (HSPF) ratings for an
untested combination must be set equal
to or less than the lower of the SEER
and/or HSPF calculated using the
applicable DOE-approved alternative
rating method (ARM). If the method
includes an ARM/simulation
adjustment factor(s), determine the
value(s) of the factors(s) that yield the
best match between the SEER/HSPF
determined using the ARM versus the
SEER/HSPF determined from testing in
accordance with paragraph (m)(1) of this
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
section. Thereafter, apply the ARM
using the derived adjustment factor(s)
only when determining the ratings for
untested combinations having the same
outdoor unit.
(5) Manufacturers or private labelers
who elect to use an ARM for
determining measures of energy
consumption under paragraphs
(m)(2)(ii)(A) and (m)(4) of this section
must submit a request for DOE to review
the ARM. Send the request to the
Assistant Secretary of Energy Efficiency
and Renewable Energy, 1000
Independence Avenue, SW.,
Washington, DC 20585–0121. Approval
must be received from the Assistant
Secretary to use the ARM before the
ARM may be used for rating splitsystem central air conditioners and heat
pumps. If a manufacturer has a DOEapproved ARM for products also
distributed in commerce by a private
labeler, the ARM may also be used by
the private labeler for rating these
products. Once an ARM is approved,
DOE may contact a manufacturer to
learn if their ARM has been modified in
any way and to verify that the ARM is
being applied as approved. DOE will
give follow-up priority to individual
combinations having questionably high
ratings (e.g., a coil-only system having a
rating that exceeds the rating of a coilonly highest sales volume combination
by more than 6 percent).
(6) Each request to DOE for approval
of an alternative rating method must
include:
(i) The name, mailing address,
telephone number, and e-mail address
of the official representing the
manufacturer.
(ii) Complete documentation of the
alternative rating method to allow DOE
to evaluate its technical adequacy. The
documentation must include a
description of the methodology, state
any underlying assumptions, and
explain any correlations. The
documentation should address how the
method accounts for the cyclicdegradation coefficient, the type of
expansion device, and, if applicable, the
indoor fan-off delay. The requestor must
submit any computer programs—
including spreadsheets—having less
than 200 executable lines that
implement the ARM. Longer computer
programs must be identified and
sufficiently explained, as specified
above, but their inclusion in the initial
submittal package is optional.
Applicability or limitations of the ARM
(e.g., only covers single-speed units
when operating in the cooling mode,
covers units with rated capacities of 3
tons or less, not applicable to the
manufacturer’s product line of non-
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
59921
ducted systems, etc.) must be stated in
the documentation.
(iii) Complete test data from
laboratory tests on four mixed (i.e., nonhighest-sales-volume combination)
systems per each ARM.
(A) The four mixed systems must
include four different indoor units and
at least two different outdoor units. A
particular model of outdoor unit may be
tested with up to two of the four indoor
units. The four systems must include
two low-capacity mixed systems and
two high-capacity mixed systems. The
low-capacity mixed systems may have
any capacity. The rated capacity of each
high-capacity mixed system must be at
least a factor of two higher than its
counterpart low-capacity mixed system.
The four mixed systems must meet the
applicable energy conservation standard
in § 430.32(c) in effect at the time of the
rating.
(B) The four indoor units must come
from at least two different coil families,
with a maximum of two indoor units
coming from the same coil family. Data
for two indoor units from the same coil
family, if submitted, must come from
testing with one of the ‘‘low-capacity
mixed systems’’ and one of the ‘‘high
capacity mixed systems.’’ A mixed
system indoor coil may come from the
same coil family as the highest-salesvolume-combination indoor unit (i.e.,
the ‘‘matched’’ indoor unit) for the
particular outdoor unit. Data on mixed
systems where the indoor unit is now
obsolete will be accepted towards the
ARM-validation submittal requirement
if it is from the same coil family as other
indoor units still in production.
(C) The first two sentences of
paragraph (m)(6)(iii)(B) of this section
do not apply if the manufacturer offers
indoor units from only one coil family.
In this case only, all four indoor coils
must be selected from this one coil
family. If approved, the ARM will be
specifically limited to applications for
this one coil family.
(iv) All product information on each
mixed system indoor unit, each
matched system indoor unit, and each
outdoor unit needed to implement the
proposed ARM. The calculated ratings
for the four mixed systems, as
determined using the proposed ARM,
must be provided along with any other
related information that will aid the
verification process.
(v) If request for approval is for an
updated ARM, manufacturers must
identify modifications made to the ARM
since the last submittal, including any
ARM/simulation adjustment factor(s)
added since the ARM was last approved
by DOE.
E:\FR\FM\22OCR3.SGM
22OCR3
59922
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
(7) Manufacturers that elect to use an
alternative rating method for
determining measures of energy
consumption under paragraphs
(m)(2)(ii)(A) and (m)(4) of this section
must either subject a sample of their
units to independent testing on a regular
basis, e.g., through a voluntary
certification program, or have the
representations reviewed and certified
by an independent state-registered
professional engineer who is not an
employee of the manufacturer. The
registered professional engineer is to
certify that the results of the alternative
rating procedure accurately represent
the energy consumption of the unit(s).
The manufacturer is to keep the
registered professional engineer’s
certifications on file for review by DOE
for as long as said combination is made
available for sale by the manufacturer.
Any proposed change to the alternative
rating method must be approved by
DOE prior to its use for rating.
(8) Manufacturers who choose to use
computer simulation or engineering
analysis for determining measures of
energy consumption under paragraphs
(m)(2)(ii)(A) and (m)(4) through (m)(7)
of this section must permit
representatives of the Department of
Energy to inspect for verification
purposes the simulation method(s) and
computer program(s) used. This
inspection may include conducting
simulations to predict the performance
of particular outdoor unit ‘‘ indoor unit
combinations specified by DOE,
analysis of previous simulations
conducted by the manufacturer, or both.
*
*
*
*
*
Appendix M—[Amended]
6. Appendix M to subpart B of part
430 is amended:
I a. In section 1. Definitions:
I 1. Section 1.3 is amended by
removing ‘‘210/240–2003’’ and adding
in its place ‘‘210/240–2006’’; and by
removing ‘‘2003’’ and adding in its
place ‘‘2006.’’
I 2. Section 1.5 is amended by
removing ‘‘23–93’’ and adding in its
place ‘‘23–2005’’; and by removing
‘‘1993’’ and adding in its place ‘‘2005.’’
I 3. Section 1.6 is amended by
removing ‘‘37–88’’ and adding in its
place ‘‘37–2005’’; and by removing
‘‘1988’’ and adding in its place ‘‘2005.’’
I 4. Section 1.12 is amended by adding
‘‘RA(05)’’ after ‘‘116–95’’; and adding
‘‘and reaffirmed in 2005’’ after ‘‘1995.’’
I 5. Section 1.35 is amended by
removing ‘‘certified’’ and adding in its
place ‘‘full-load.’’
I 6. Section 1.37 is revised to read as set
forth below.
pwalker on PROD1PC71 with RULES3
I
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
b. In section 2, Testing Conditions:
1. Sections 2.1a, 2.2a, 2.2b, 2.2.3,
2.2.5, 2.4.1, and 2.4.2 are revised to read
as set forth below.
I 2. Section 2.3.1b is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load.’’
I 3. Section 2.5.3 is amended by
revising the first sentence to read as set
forth below.
I 4. New section 2.5.4.3 is added to read
as set forth below.
I 5. Section 2.6a is amended by adding
in the first sentence ‘‘(RA05)’’ after
‘‘116–95.’’
I 6. Section 2.6b is amended in the
second sentence, and in the last
sentence, by removing ‘‘37–88’’ and
adding in its place ‘‘37–2005;’’ and by
removing ‘‘ARI Standard 210/240–
2003’’ and adding in its place ‘‘ARI
Standard 210/240–2006’’ in the second
sentence.
I 7. Section 2.7 is amended by
removing ‘‘ARI Standard 210/240–
2003’’ and adding in its place ‘‘ARI
Standard 210/240–2006.’’
I 8. Section 2.10.2 is amended in the
third and fourth sentences, by removing
‘‘37–88’’ and adding in its place ‘‘37–
2005.’’
I 9. Section 2.10.3 is amended in the
second sentence, by removing ‘‘7.6.2,’’
and adding in its place ‘‘7.5.2,’’ and by
removing ‘‘37–88’’ and adding in its
place ‘‘37–2005’’ in the second and
third sentences.
I 10. Section 2.11a is amended in the
first sentence, by removing ‘‘37–88’’ and
adding in its place ‘‘37–2005.’’
I 11. Section 2.13 is amended in the
second sentence, by removing ‘‘37–88’’
and adding in its place ‘‘37–2005.’’
I c. In section 3, Testing Procedures:
I 1. Section 3.1.1 is amended by
revising the seventh sentence to read as
set forth below.
I 2. Section 3.1.3 is amended by
removing ‘‘ARI Standard 210/240–
2003’’ and adding in its place ‘‘ARI
Standard 210/240–2006.’’
I 3. Section 3.1.4.1 is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load.’’
I 4. Section 3.1.4.1.1, from its title to
the end of paragraph a., and Table 2, are
revised to read as set forth below.
I 4a. Section 3.1.4.1.1b is amended by
revising the first sentence to read as set
forth below.
I 5. Amend sections 3.1.4.1.1b and
3.1.4.1.1c by removing ‘‘Certified’’ and
adding in its place ‘‘Full-load.’’
I 6. Section 3.1.4.1.2 is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load’’ in two locations.
I 7. Section 3.1.4.2a is amended by
revising the ‘‘Cooling Minimum Air Vol.
Rate’’ equation to read as set forth
below.
I
I
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
8. Section 3.1.4.2b is amended by
revising the equation for minimum
external static pressure to read as set
forth below.
I 9. Section 3.1.4.2c is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load.’’
I 10. Section 3.1.4.3a is amended by
revising the ‘‘Cooling Intermediate Air
Volume Rate’’ equation to read as set
forth below.
I 11. Section 3.1.4.3b is amended by
revising the ‘‘Ev Test DPst ’’ equation to
read as set forth below.
I 12. Section 3.1.4.4 is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load.’’
I 13. Section 3.1.4.4.1 is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load’’ in three locations.
I 14. Section 3.1.4.4.2 is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load’’ and revising the
‘‘Heating Certified Air Volume Rate’’
equation to read as set forth below.
I 14a. Section 3.1.4.4.2a is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load.’’
I 15. Section 3.1.4.4.2b is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load’’ in three locations, and
revising the ‘‘Heating Certified DPst’’
equation to read as set forth below.
I 16. Section 3.1.4.4.2c is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load’’ in three locations.
I 17. Sections 3.1.4.4.3 and 3.1.4.4.3a
are revised to read as set forth below.
I 17a. Sections 3.1.4.4.3b is amended by
revising the first sentence to read as set
forth below.
I 18. Amend sections 3.1.4.4.3b,
3.1.4.4.3c and 3.1.4.4.4 by removing
‘‘Certified’’ and adding in its place
‘‘Full-load.’’
I 19. Section 3.1.4.5a is amended by
revising the ‘‘Heating Minimum Air
Volume Rate’’ equation to read as set
forth below.
I 20. Section 3.1.4.5b is amended by
revising the ‘‘H01, H11, H21, H31, Test
DPst’’ equation to read as set forth below.
I 21. Section 3.1.4.5d is amended by
removing Certified and adding in its
place Full-load in two locations.
I 22. Section 3.1.4.6a is amended by
revising the ‘‘Heating Intermediate Air
Volume Rate’’ equation to read as set
forth below.
I 23. Section 3.1.4.6b is amended by
revising the ‘‘H2v Test DPst’’ equation to
read as set forth below.
I 24. Section 3.1.4.7 is amended by
revising the ‘‘Heating Nominal Air
Volume Rate’’ equation and the ‘‘H1N
Test DPst’’ equation to read as set forth
below.
I 25. Section 3.1.5 is amended in the
first sentence by removing ‘‘37–88’’ and
adding in its place ‘‘37–2005.’’
I
E:\FR\FM\22OCR3.SGM
22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
26. Section 3.1.6 is amended in the
first and second sentences, by removing
‘‘7.8.3.1 and 7.8.3.2’’ and adding in its
place ‘‘7.7.2.1 and 7.7.2.2,’’ and in the
first sentence, by removing ‘‘37–88’’ and
adding in its place ‘‘37–2005,’’ and by
adding a new sentence after the second
sentence, to read as set forth below.
I 27. Section 3.1.7 is amended by
removing ‘‘certified’’ and adding in its
place ‘‘Full-load’’ in four locations.
I 28. Section 3.1.9 is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load.’’
I 28a. Section 3.2.1 is amended by
revising the fourth sentence to read as
set forth below.
I 29. Table 3 to Section 3.2.1 is
amended by removing ‘‘certified’’ and
adding in its place ‘‘full-load’’ in three
locations in the last column.
I 29a. Section 3.2.2.1 is amended by
revising the third sentence to read as set
forth below.
I 30. Table 4 to Section 3.2.2.1 is
amended by removing ‘‘certified’’ and
adding in its place ‘‘full-load’’ in two
locations in the last column.
I 31. Section 3.2.2.2 is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load.’’
I 32. Sections 3.2.3a is revised as set
forth below.
I 33. Section 3.2.3b is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load.’’
I 34. Section 3.2.3d is revised as set
forth below.
I 35. Table 5 to section 3.2.3 is revised
as set forth below.
I 36. Section 3.2.4.a is amended by
revising the third sentence to read as set
forth below.
I 37. Section 3.2.4b is amended by
removing ‘‘Certified’’ and adding in its
place ‘‘Full-load.’’
I 38. Table 6 to section 3.2.4 is revised
as set forth below.
I 39. Section 3.2.4 is amended by
adding a new paragraph (c) as set forth
below.
I 40. Section 3.3b is amended in both
the first and second sentences, by
removing ‘‘Table 5,’’ and adding in its
place ‘‘Table 3,’’ and in the first
sentence by removing ‘‘37–88’’ and
adding in its place ‘‘37–2005.’’
I 41. Section 3.3c is amended in the
first sentence by removing ‘‘section
7.3.3.1 of ASHRAE Standard 37–88,’’
and adding in its place ‘‘sections 7.3.3.1
and 7.3.3.3 of ASHRAE Standard 37–
2005.’’
I 42. The titles of sections 3.4 and 3.5
are revised as set forth below.
I 43. Section 3.4b is revised to read as
set forth below.
I 44. Section 3.5.3 is amended by
revising the introductory text to read as
set forth below.
pwalker on PROD1PC71 with RULES3
I
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
45. Section 3.6.1 is amended by
revising the second, third, and fourth
sentences to read as set forth below.
I 46. Table 9 to Section 3.6.1 is
amended by removing ‘‘Certified’’ and
adding in its place ‘‘Full-load’’ in three
locations.
I 47. Section 3.6.2 is amended by
revising the introductory text to read as
set forth below.
I 48. Table 10 to Section 3.6.2 is
amended by removing ‘‘Certified’’ and
adding in its place ‘‘Full-load’’ in three
locations.
I 49. Section 3.6.3 is revised as set forth
below.
I 50. Table 11 to section 3.6.3 is revised
as set forth below.
I 51. Section 3.6.4 is amended by
revising the third, fourth, and fifth
sentences of paragraph a. and adding a
new paragraph c. to read as set forth
below.
I 52. Table 12 to section 3.6.4 is revised
to read as set forth below.
I 53. Section 3.7a is amended in the
fifth sentence by removing ‘‘Table 5 of
ASHRAE Standard 37–88’’ and adding
in its place ‘‘Table 3 of ASHRAE
Standard 37–2005,’’ and in the sixth
sentence, by removing ‘‘Table 5’’ and
adding in its place ‘‘Table 3.’’
I 54. Section 3.7b is amended by
revising the first sentence to read as set
forth below.
I 55. The title of section 3.8 is revised
to read as set forth below.
I 56. The introductory text and the first
equation of section 3.8.1 are revised to
read as set forth below.
I 57. Section 3.9c is revised to read as
set forth below.
I 58. Section 3.9f is amended by
revising the fifth sentence and adding a
parenthetical immediately following it
to read as set forth below.
I 59. Section 3.9.1a is amended by
adding a new sentence at the end of the
section directly before section 3.9.1.b to
read as set forth below.
I 60. Section 3.9.2b is amended by
replacing ‘‘Certified’’ with ‘‘Full-load.’’
I 61. Section 3.11 is amended by
removing the introductory text
following the paragraph heading, which
is republished below.
I 62. Section 3.11.1.3b is revised to read
as set forth below.
I 63. Section 3.11.2a is amended by
revising the seventh sentence to read as
set forth below.
I 64. Section 3.11.2b is revised to read
as set forth below.
I 65. Section 3.11.3 is revised to read as
set forth below.
I d. In section 4, CALCULATIONS OF
SEASONAL PERFORMANCE
DESCRIPTORS:
I
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
59923
1. Sections 4.1.2.1a and 4.1.2.1d are
amended by removing ‘‘Certified’’ and
adding in its place ‘‘Full-load.’’
I 2. Section 4.1.3 is amended by
revising the introductory text, equations
4.1.3–1 and 4.1.3–2, the paragraph
preceding equation 4.1.3–3, and
equation 4.1.3–3 to read as set forth
below.
I 3. Section 4.1.3.3 is amended by
revising the equation for PLFj and the
text following the equation to read as set
forth below.
I 4. Section 4.1.4 is amended by
revising everything except for the
equations for calculating MQ and ME, to
read as set forth below.
I 5. Section 4.1.4.1 is amended by
revising the second sentence after the
explanation of terms in the equations
(‘‘Use Equations 4.1.3–1 and 4.1.3–2,
˙
respectively, to evaluate Qck=1 (Tj)’’ and
˙
Eck=1 (Tj) to read as set forth below.
I 6. Section 4.1.4.2 is amended by
revising the equation numbers
referenced in the descriptions of the
quantities T1 and Tv, revising the
equation numbers referred to in the
equations for EERk=1 (T1) and EERk=v
(Tv), and adding text at the end of the
section to read as set forth below.
I 7. Section 4.2.3.3 is amended by
revising the equation for PLFj and the
text following the equation to read as set
forth below.
I 8. The Section 4.2.4 equations for MQ
and ME are revised to read as set forth
below.
I 9. Section 4.2.4.2 is amended by
adding text at the end of the section to
read as set forth below.
The additions and revisions read as
follows:
I
Appendix M to Subpart B of Part 430—
Uniform Test Method for Measuring the
Energy Consumption of Central Air
Conditioners and Heat Pumps
*
*
*
*
*
1. Definitions
*
*
*
*
*
1.37 Standard air means dry air
having a mass density of 0.075 lb/ft3.
*
*
*
*
*
2. Testing Conditions
*
*
*
*
*
2.1 Test room requirements. a. Test
using two side-by-side rooms, an indoor
test room and an outdoor test room. For
multiple-split air conditioners and heat
pumps (see Definition 1.30), however,
use as many available indoor test rooms
as needed to accommodate the total
number of indoor units. These rooms
must comply with the requirements
specified in sections 8.1.2 and 8.1.3 of
ASHRAE Standard 37–2005
E:\FR\FM\22OCR3.SGM
22OCR3
59924
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
(incorporated by reference, see
§ 430.22).
*
*
*
*
*
2.2 Test unit installation
requirements. a. Install the unit
according to section 8.2 of ASHRAE
Standard 37–2005 (incorporated by
reference, see § 430.22). With respect to
interconnecting tubing used when
testing split systems, however, follow
the requirements given in section 6.1.3.5
of ARI Standard 210/240–2006
(incorporated by reference, see
§ 430.22). When testing triple-split
systems (see Definition 1.44), use the
tubing length specified in section 6.1.3.5
of ARI Standard 210/240–2006
(incorporated by reference, see § 430.22)
to connect the outdoor coil, indoor
compressor section, and indoor coil
while still meeting the requirement of
exposing 10 feet of the tubing to outside
conditions. When testing split systems
having multiple indoor coils, connect
each indoor fan-coil to the outdoor unit
using: (a) 25 feet of tubing, or (b) tubing
furnished by the manufacturer,
whichever is longer. If they are needed
to make a secondary measurement of
capacity, install refrigerant pressure
measuring instruments as described in
section 8.2.5 of ASHRAE Standard 37–
2005 (incorporated by reference, see
§ 430.22). Refer to section 2.10 of this
Appendix to learn which secondary
methods require refrigerant pressure
measurements. At a minimum, insulate
the low-pressure line(s) of a split-system
with insulation having an inside
diameter that matches the refrigerant
tubing and a nominal thickness of 0.5
inch.
b. For units designed for both
horizontal and vertical installation or
for both up-flow and down-flow vertical
installations, the manufacturer must
specify the orientation used for testing.
Conduct testing with the following
installed:
(1) the most restrictive filter(s);
(2) supplementary heating coils; and
(3) other equipment specified as part
of the unit, including all hardware used
by a heat comfort controller if so
equipped (see Definition 1.28). For
small-duct, high-velocity systems,
configure all balance dampers or
restrictor devices on or inside the unit
to fully open or lowest restriction.
*
*
*
*
*
2.2.3 Special requirements for multisplit air conditioners and heat pumps,
and systems composed of multiple
mini-split units (outdoor units located
side-by-side) that would normally
operate using two or more indoor
thermostats. For any test where the
system is operated at part load (i.e., one
or more compressors ‘‘off’’, operating at
the intermediate or minimum
compressor speed, or at low compressor
capacity), the manufacturer shall
designate the particular indoor coils that
are turned off during the test. For
variable-speed systems, the
manufacturer must designate at least
one indoor unit that is turned off for all
tests conducted at minimum compressor
speed. For all other part-load tests, the
manufacturer shall choose to turn off
zero, one, two, or more indoor units.
The chosen configuration shall remain
unchanged for all tests conducted at the
same compressor speed/capacity. For
any indoor coil that is turned off during
a test, take steps to cease forced airflow
through this indoor coil and block its
outlet duct. Because these types of
systems will have more than one indoor
fan and possibly multiple outdoor fans
and compressor systems, references in
this test procedure to a single indoor
fan, outdoor fan, and compressor means
all indoor fans, all outdoor fans, and all
compressor systems that are turned on
during the test.
*
*
*
*
*
2.2.5 Additional refrigerant charging
requirements. Charging according to the
‘‘manufacturer’s published
instructions,’’ as stated in section 8.2 of
ASHRAE Standard 37–2005
(incorporated by reference, see
§ 430.22), means the manufacturer’s
installation instructions that come
packaged with the unit. * * *
*
*
*
*
*
2.4.1 Outlet plenum for the indoor
unit. a. Attach a plenum to the outlet of
the indoor coil. (NOTE: for some
packaged systems, the indoor coil may
be located in the outdoor test room.)
b. For systems having multiple indoor
coils, attach a plenum to each indoor
coil outlet. Connect two or more outlet
plenums to a single common duct so
that each indoor coil ultimately
connects to an airflow measuring
apparatus (section 2.6). If using more
than one indoor test room, do likewise,
creating one or more common ducts
within each test room that contains
multiple indoor coils. At the plane
where each plenum enters a common
duct, install an adjustable airflow
damper and use it to equalize the static
pressure in each plenum. Each outlet air
temperature grid (section 2.5.4) and
airflow measuring apparatus are located
downstream of the inlet(s) to the
common duct.
c. For small-duct, high-velocity
systems, install an outlet plenum that
has a diameter that is equal to or less
than the value listed below. The limit
depends only on the cooling Full-Load
Air Volume Rate (see section 3.1.4.1.1)
and is effective regardless of the flange
dimensions on the outlet of the unit (or
an air supply plenum adapter accessory,
if installed in accordance with the
manufacturer’s installation
instructions).
d. Add a static pressure tap to each
face of the (each) outlet plenum, if
rectangular, or at four evenly distributed
locations along the circumference of an
oval or round plenum. Create a
manifold that connects the four static
pressure taps. Figure 1 shows two of the
three options allowed for the manifold
configuration; the third option is the
broken-ring, four-to-one manifold
configuration that is shown in Figure 7a
of ASHRAE Standard 37–2005
(incorporated by reference, see
§ 430.22). See Figures 7a, 7b, 7c, and 8
of ASHRAE Standard 37–2005
(incorporated by reference, see § 430.22)
for the cross-sectional dimensions and
minimum length of the (each) plenum
and the locations for adding the static
pressure taps for units tested with and
without an indoor fan installed.
Maximum diameter* of
outlet plenum
(inches)
pwalker on PROD1PC71 with RULES3
Cooling full-load air volume rate
(scfm)
≤500 .....................................................................................................................................................................................
501 to 700 ............................................................................................................................................................................
701 to 900 ............................................................................................................................................................................
901 to 1100 ..........................................................................................................................................................................
1101 to 1400 ........................................................................................................................................................................
1401 to 1750 ........................................................................................................................................................................
6
7
8
9
10
11
*If the outlet plenum is rectangular, calculate its equivalent diameter using (4A)/P, where A is the area and P is the perimeter of the rectangular plenum, and compare it to the listed maximum diameter.
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
E:\FR\FM\22OCR3.SGM
22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
2.4.2 Inlet plenum for the indoor
unit. Install an inlet plenum when
testing a coil-only indoor unit or a
packaged system where the indoor coil
is located in the outdoor test room. Add
static pressure taps at the center of each
face of this plenum, if rectangular, or at
four evenly distributed locations along
the circumference of an oval or round
plenum. Make a manifold that connects
the four static-pressure taps using one of
the three configurations specified in
section 2.4.1. See Figures 7b, 7c, and
Figure 8 of ASHRAE Standard 37–2005
(incorporated by reference, see § 430.22)
for cross-sectional dimensions, the
minimum length of the inlet plenum,
and the locations of the static-pressure
taps. When testing a ducted unit having
an indoor fan (and the indoor coil is in
the indoor test room), the manufacturer
has the option to test with or without an
inlet plenum installed. Space
limitations within the test room may
dictate that the manufacturer choose the
latter option. If used, construct the inlet
plenum and add the four static-pressure
taps as shown in Figure 8 of ASHRAE
Standard 37–2005 (incorporated by
reference, see § 430.22). Manifold the
four static-pressure taps using one of the
three configurations specified in section
2.4.1. Never use an inlet plenum when
testing a non-ducted system.
*
*
*
*
*
2.5.3 Section 6.5.2 of ASHRAE
Standard 37–2005 (incorporated by
reference, see § 430.22) describes the
method for fabricating static-pressure
taps. * * *
*
*
*
*
*
2.5.4.3 Minimizing air leakage. For
small-duct, high-velocity systems,
install an air damper near the end of the
interconnecting duct, just prior to the
transition to the airflow measuring
apparatus of section 2.6. To minimize
air leakage, adjust this damper such that
the pressure in the receiving chamber of
the airflow measuring apparatus is no
more than 0.5 inch of water higher than
the surrounding test room ambient. In
lieu of installing a separate damper, use
the outlet air damper box of sections 2.5
and 2.5.4.1 if it allows variable
positioning. Also apply these steps to
any conventional indoor blower unit
that creates a static pressure within the
receiving chamber of the airflow
measuring apparatus that exceeds the
test room ambient pressure by more
than 0.5 inches of water column.
*
*
*
*
*
3. Testing Procedures
*
*
*
*
*
3.1.1 Primary and secondary test
methods. * * *
For this capacity comparison, use the
Indoor Air Enthalpy Method capacity
that is calculated in section 7.3 of
ASHRAE Standard 37–2005
(incorporated by reference, see § 430.22)
(and, if testing a coil-only unit, do not
make the after-test fan heat adjustments
described in section 3.3, 3.4, 3.7, and
3.10 of this Appendix). * * *
*
*
*
*
*
3.1.4.1.1 Cooling Full-Load Air
Volume Rate for Ducted Units. The
manufacturer must specify the Cooling
Full-load Air Volume Rate. Use this
value as long as the following two
requirements are satisfied. First, when
conducting the A or A2 Test
(exclusively), the measured air volume
rate, when divided by the measured
indoor air-side total cooling capacity
must not exceed 37.5 cubic feet per
minute of standard air (scfm) per 1000
Btu/h. If this ratio is exceeded, reduce
the air volume rate until this ratio is
equaled. Use this reduced air volume
rate for all tests that call for using the
Cooling Full-load Air Volume Rate. The
second requirement is as follows:
59925
a. For all ducted units tested with an
indoor fan installed, except those
having a variable-speed, constant-airvolume-rate indoor fan. The second
requirement applies exclusively to the A
or A2 Test and is met as follows.
1. Achieve the Cooling Full-load Air
Volume Rate, determined in accordance
with the previous paragraph;
2. Measure the external static
pressure;
3. If this pressure is equal to or greater
than the applicable minimum external
static pressure cited in Table 2, this
second requirement is satisfied. Use the
current air volume rate for all tests that
require the Cooling Full-load Air
Volume Rate.
4. If the Table 2 minimum is not
equaled or exceeded,
4a. reduce the air volume rate until
the applicable Table 2 minimum is
equaled or
4b. until the measured air volume rate
equals 95 percent of the air volume rate
from step 1, whichever occurs first.
5. If the conditions of step 4a occur
first, this second requirement is
satisfied. Use the step 4a reduced air
volume rate for all tests that require the
Cooling Full-load Air Volume Rate.
6. If the conditions of step 4b occur
first, make an incremental change to the
set-up of the indoor fan (e.g., next
highest fan motor pin setting, next
highest fan motor speed) and repeat the
evaluation process beginning at above
step 1. If the indoor fan set-up cannot
be further changed, reduce the air
volume rate until the applicable Table 2
minimum is equaled. Use this reduced
air volume rate for all tests that require
the Cooling Full-load Air Volume Rate.
b. For ducted units that are tested
with a variable-speed, constant-airvolume-rate indoor fan installed. * * *
*
*
*
*
*
TABLE 2.—MINIMUM EXTERNAL STATIC PRESSURE FOR DUCTED SYSTEMS TESTED WITH AN INDOOR FAN INSTALLED
Minimum external resistance 3
(Inches of water)
Rated Cooling 1 or Heating 2 Capacity
(Btu/h)
All other systems
Small-duct, highvelocity systems 4,5
0.10
0.15
0.20
1.10
1.15
1.20
pwalker on PROD1PC71 with RULES3
Up Thru 28,800 ................................................................................................................................................
29,000 to 42,500 ..............................................................................................................................................
43,000 and Above ...........................................................................................................................................
1 For air conditioners and heat pumps, the value cited by the manufacturer in published literature for the unit’s capacity when operated at the A
or A2 Test conditions.
2 For heating-only heat pumps, the value the manufacturer cites in published literature for the unit’s capacity when operated at the H1 or H1
2
Test conditions.
3 For ducted units tested without an air filter installed, increase the applicable tabular value by 0.08 inch of water.
4 See Definition 1.35 to determine if the equipment qualifies as a small-duct, high-velocity system.
5 If a closed-loop, air-enthalpy test apparatus is used on the indoor side, limit the resistance to airflow on the inlet side of the indoor blower coil
to a maximum value of 0.1 inch of water. Impose the balance of the airflow resistance on the outlet side of the indoor blower.
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
E:\FR\FM\22OCR3.SGM
22OCR3
59926
*
*
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
*
*
*
3.1.4.2 Cooling Minimum Air
Volume Rate. a. * * *
Cooling Minimum Air Vol. Rate = Cooling Full-load Air Vol. Rate ×
a
* * *
Cooling Minimum Fan Speed
,
A 2 Test Fan Speed
b. * * *
2
Cooling Minimum Air Volume Rate
A1 , B1 , C1 , F1 , & G1 Test ∆Pst = ∆Pst , A2 ×
,
Cooling Full-load Air Volume Rate
*
*
*
*
*
3.1.4.3 Cooling Intermediate Air
Volume Rate. a. * * *
Cooling Intermediate Air Vol. Rate = Cooling Full-load Air Vol. Rate ×
o
* * *
E V Test Fan Speed
,
A 2 Test Fan Speed
b. * * *
2
Cooling Intermediate Air Volume Rate
E V Test ∆Pst = ∆Pst , A2 ×
,
Cooling Full-load Air Volume Rate
Volume Rates are different due to
indoor fan operation. a. * * *
pwalker on PROD1PC71 with RULES3
*
*
*
*
*
3.1.4.4.3 Ducted heating-only heat
pumps. The manufacturer must specify
the Heating Full-load Air Volume Rate.
a. For all ducted heating-only heat
pumps tested with an indoor fan
installed, except those having a
variable-speed, constant-air-volume-rate
indoor fan. Conduct the following steps
only during the first test, the H1 or H12
Test.
1. Achieve the Heating Full-load Air
Volume Rate.
2. Measure the external static
pressure.
3. If this pressure is equal to or greater
than the Table 2 minimum external
static pressure that applies given the
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
heating-only heat pump’s rated heating
capacity, use the current air volume rate
for all tests that require the Heating
Full-load Air Volume Rate.
4. If the Table 2 minimum is not
equaled or exceeded,
4a. reduce the air volume rate until
the applicable Table 2 minimum is
equaled or
4b. until the measured air volume rate
equals 95 percent of the manufacturerspecified Full-load Air Volume Rate,
whichever occurs first.
5. If the conditions of step 4a occurs
first, use the step 4a reduced air volume
rate for all tests that require the Heating
Full-load Air Volume Rate.
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
6. If the conditions of step 4b occur
first, make an incremental change to the
set-up of the indoor fan (e.g., next
highest fan motor pin setting, next
highest fan motor speed) and repeat the
evaluation process beginning at above
step 1. If the indoor fan set-up cannot
be further changed, reduce the air
volume rate until the applicable Table 2
minimum is equaled. Use this reduced
air volume rate for all tests that require
the Heating Full-load Air Volume Rate.
b. For ducted heating-only heat
pumps that are tested with a variablespeed, constant-air-volume-rate indoor
fan installed. * * *
*
*
*
*
*
E:\FR\FM\22OCR3.SGM
22OCR3
ER22OC07.070
2
Heating Full-load Air Volume Rate
Heating Full-load ∆Pst = Cooling Full-load ∆Pst ×
,
Cooling Full-load Air Volume Rate
ER22OC07.069
b. * * *
ER22OC07.068
* * *
H1 or H12 Test Fan Speed
,
A or A 2 Test Fan Speed
ER22OC07.067
Heating Full-load Air Volume Rate = Cooling Full-load Air Volume Rate ×
l
ER22OC07.066
*
*
*
*
3.1.4.4.2 Ducted heat pumps where
the Heating and Cooling Full-load Air
ER22OC07.065
*
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
59927
3.1.4.5 Heating Minimum Air
Volume Rate. a. * * *
Heating Minimum Air Vol. Rate = Heating Full-load Air Vol. Rate ×
* * *
Heating Minimum Fan Speed
,
H12 Test Fan Speed
b. * * *
2
Htg Minimum Air Vol. Rate
H01 , H11 , H 21 , H31 , Test ∆Pst = ∆Pst, H12 ×
,
Htg Full-load Air Vol. Rate
*
*
*
*
*
3.1.4.6 Heating Intermediate Air
Volume Rate. a. * * *
Heating Intermediate Air Volume Rate = Heating Full-load Air Volume Rate ×
* * *
H 2V Test Fan Speed
,
H12 Test Fan Speed
b. * * *
2
Heating Intermediate Air Volume Rate
H 2V Test ∆Pst ∆Pst , H12 ×
,
Heating Full-load Air Volume Rate
H1N Test Fan Speed
,
H12 Test Fan Speed
2
Heating Nominal Air Volume Rate
H1N Test ∆Pst = ∆Pst , H12 ×
,
Heating Full-load Air Volume Rate
*
*
*
*
*
3.1.6 * * * (Note: In the first
printing of ASHRAE Standard 37–2005,
the second IP equation for Qmi should
read,
pwalker on PROD1PC71 with RULES3
1097CA n Pv v′ .) * * *
n
* * *
*
*
*
*
*
3.2.1 * * * If the two optional tests
are conducted but yield a tested CDc that
exceeds the default CDc or if the two
optional tests are not conducted, assign
CDc the default value of 0.25. * * *
*
*
*
*
*
3.2.2.1 * * * If the two optional
tests are conducted but yield a tested
CDc that exceeds the default CDc or if the
two optional tests are not conducted,
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
assign CDc the default value of 0.25.
* * *
*
*
*
*
*
3.2.3 Tests for a unit having a twocapacity compressor. (See Definition
1.45.)
a. Conduct four steady-state wet coil
tests: the A2, B2, B1, and F1 Tests. Use
the two optional dry-coil tests, the
steady-state C1 Test and the cyclic D1
Test, to determine the cooling-mode
cyclic-degradation coefficient, CDc. If the
two optional tests are conducted but
yield a tested CDc that exceeds the
default CDc or if the two optional tests
are not conducted, assign CDc the
default value of 0.25. Table 5 specifies
test conditions for these six tests.
*
*
*
*
*
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
d. If a two-capacity air conditioner or
heat pump locks out low-capacity
operation at higher outdoor
temperatures, then use the two optional
dry-coil tests, the steady-state C2 Test
and the cyclic D2 Test, to determine the
cooling-mode cyclic-degradation
coefficient that only applies to on/off
cycling from high capacity, CDc(k=2). If
the two optional tests are conducted but
yield a tested CDc(k=2) that exceeds the
default CDc(k=2) or if the two optional
tests are not conducted, assign CDc(k=2)
the default value. The default CDc(k=2)
is the same value as determined or
assigned for the low-capacity cyclicdegradation coefficient, CDc [or
equivalently, CDc(k=1)].
E:\FR\FM\22OCR3.SGM
22OCR3
ER22OC07.076
Heating Nominal Air Volume Rate = Heating Full-load Air Volume Rate ×
m
ER22OC07.077
3.1.4.7 Heating Nominal Air Volume
Rate. * * *
ER22OC07.075
*
ER22OC07.074
*
ER22OC07.073
*
ER22OC07.072
*
ER22OC07.071
*
59928
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
TABLE 5.—COOLING MODE TEST CONDITIONS FOR UNITS HAVING A TWO-CAPACITY COMPRESSOR
Air entering indoor unit
temperature (°F)
A2 Test—required
(steady, wet coil)
B2 Test—required
(steady, wet coil)
B1 Test—required
(steady, wet coil)
C2 Test—optional
(steady, dry-coil)
D2 Test—optional
(cyclic, dry-coil)
C1 Test—optional
(steady, dry-coil)
D1 Test—optional
(cyclic, dry-coil)
F1 Test—required
(steady, wet coil)
Air entering outdoor unit
temperature (°F)
Dry bulb
Test description
Dry bulb
Wet bulb
Compressor
capacity
Cooling air volume rate
Wet bulb
................................
80
67
95
1 75
High .............
Cooling Full-Load.2
................................
80
67
82
1 65
High .............
Cooling Full-Load.2
................................
80
67
82
1 65
Low .............
Cooling Minimum.3
................................
80
(4)
82
......................
High .............
Cooling Full-Load.2
................................
80
(4)
82
......................
High .............
(5)
................................
80
(4)
82
......................
Low ..............
Cooling Minimum.3
................................
80
(4)
82
......................
Low ..............
(6)
................................
80
67
67
1 53.5
Low .............
Cooling Minimum.3
1 The
specified test condition only applies if the unit rejects condensate to the outdoor coil.
in section 3.1.4.1.
3 Defined in section 3.1.4.2.
4 The entering air must have a low enough moisture content so no condensate forms on the indoor coil. DOE recommends using an indoor air
wet-bulb temperature of 57 °F or less.
5 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the C2 Test.
6 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the C1 Test.
2 Defined
specified for a minimum compressor
speed, at least one indoor unit must be
turned off. The manufacturer shall
designate the particular indoor unit(s)
that is turned off. The manufacturer
must also specify the compressor speed
used for the Table 6 EV Test, a coolingmode intermediate compressor speed
that falls within 1⁄4 and 3⁄4 of the
difference between the maximum and
3.2.4 Tests for a unit having a
variable-speed compressor. a. * * * If
the two optional tests are conducted but
yield a tested CDc that exceeds the
default CDc or if the two optional tests
are not conducted, assign CDc the
default value of 0.25. * * *
c. For multiple-split air conditioners
and heat pumps (except where noted),
the following procedures supersede the
above requirements: For all Table 6 tests
minimum cooling-mode speeds. The
manufacturer should prescribe an
intermediate speed that is expected to
yield the highest EER for the given EV
Test conditions and bracketed
compressor speed range. The
manufacturer can designate that one or
more indoor units are turned off for the
EV Test.
*
*
*
*
*
TABLE 6.—COOLING MODE TEST CONDITION FOR UNITS HAVING A VARIABLE-SPEED COMPRESSOR
Air entering indoor unit
temperature (°F)
Air entering outdoor unit
temperature (°F)
Dry bulb
Test description
Dry bulb
A2 Test—required ..........................
(steady, wet coil)
B2 Test—required ..........................
(steady, wet coil)
EV Test—required ..........................
(steady, wet coil)
B1 Test—required ..........................
(steady, wet coil)
F1 Test—required ...........................
(steady, wet coil)
G1 Test 5—optional .........................
(steady, dry-coil)
I1 Test 5—optional ..........................
(cyclic, dry-coil)
Wet bulb
Compressor
speed
80
67
95
1 75
Maximum ..........
Cooling Full-Load2
80
67
82
1 65
Maximum ..........
Cooling Full-Load2
80
67
87
1 69
Intermediate .....
Cooling Intermediate 3
80
67
82
1 65
Minimum ...........
Cooling Minimum 4
80
67
67
1 53.5
Minimum ...........
Cooling Minimum 4
80
(6)
67
......................
Minimum ...........
Cooling Minimum 4
80
(6)
67
......................
Minimum ...........
(6)
1 The
pwalker on PROD1PC71 with RULES3
Cooling air volume rate
Wet bulb
specified test condition only applies if the unit rejects condensate to the outdoor coil.
in section 3.1.4.1.
in section 3.1.4.3.
4 Defined in section 3.1.4.2.
5 The entering air must have a low enough moisture content so no condensate forms on the indoor coil. DOE recommends using an indoor air
wet bulb temperature of 57°F or less.
6 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure difference or velocity
pressure as measured during the G1 Test.
2 Defined
3 Defined
VerDate Aug<31>2005
19:03 Oct 19, 2007
Jkt 214001
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
E:\FR\FM\22OCR3.SGM
22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
59929
*
*
*
*
*
3.4 Test procedures for the optional
steady-state dry-coil cooling-mode tests
(the C, C1, C2, and G1 Tests).
*
*
*
*
*
b. Denote the resulting total space
cooling capacity and electrical power
˙
˙
derived from the test as Qss,dry and Ess,dry.
With regard to a section 3.3 deviation,
˙
do not adjust Qss,dry for duct losses (i.e.,
do not apply section 7.3.3.3 of ASHRAE
Standard 37–2005 (incorporated by
reference, see § 430.22)). In preparing
for the section 3.5 cyclic tests, record
the
Ô average indoor-side air volume rate,
V, specific heat of the air, Cp,a
(expressed on dry air basis), specific
volume of the air at the nozzles, v′n,
humidity ratio at the nozzles, Wn, and
either pressure difference or velocity
pressure for the flow nozzles. For units
having a variable-speed indoor fan (that
provides either a constant or variable air
volume rate) that will or may be tested
during the cyclic dry coil cooling mode
test with the indoor fan turned off (see
section 3.5), include the electrical
power used by the indoor fan motor
among the recorded parameters from the
30-minute test.
3.5 Test procedures for the optional
cyclic dry-coil cooling-mode tests (the
D, D1, D2, and I1 Tests).
*
*
*
*
*
3.5.3 Cooling-mode cyclicdegradation coefficient calculation. Use
the two optional dry-coil tests to
determine the cooling-mode cyclicdegradation coefficient, CDc. Append
‘‘(k=2)’’ to the coefficient if it
corresponds to a two-capacity unit
cycling at high capacity. If the two
optional tests are conducted but yield a
tested CDc that exceeds the default CDc
or if the two optional tests are not
conducted, assign CDc the default value
of 0.25. The default value for twocapacity units cycling at high capacity,
however, is the low-capacity coefficient,
i.e., CDc(k=2)=CDc. Evaluate CDc using
the above results and those from the
section 3.4 dry-coil steady-state test.
*
*
*
*
*
3.6.1 * * * Conduct the optional
High Temperature Cyclic (H1C) Test to
determine the heating mode cyclicdegradation coefficient, CDh. If this
optional test is conducted but yields a
tested CDh that exceeds the default CDh
or if the optional test is not conducted,
assign CDh the default value of 0.25. Test
conditions for the four tests are
specified in Table 9. * * *
*
*
*
*
*
3.6.2 Tests for a heat pump having a
single-speed compressor and a variablespeed, variable-air-volume-rate indoor
fan: capacity modulation correlates with
outdoor dry bulb temperature. Conduct
five tests: two High Temperature Tests
(H12 and H11), one Frost Accumulation
Test (H22), and two Low Temperature
Tests (H32 and H31). Conducting an
additional Frost Accumulation Test
(H21) is optional. Conduct the optional
High Temperature Cyclic (H1C1) Test to
determine the heating mode cyclic-
degradation coefficient, CDh. If this
optional test is conducted but yields a
tested CDh that exceeds the default CDh
or if the optional test is not conducted,
assign CDh the default value of 0.25. Test
conditions for the seven tests are
specified in Table 10. If the optional H21
Test is not performed, use the following
equations to approximate the capacity
and electrical power of the heat pump
at the H21 test conditions:
*
*
*
*
*
3.6.3 Tests for a heat pump having a
two-capacity compressor (see Definition
1.45), including two-capacity, northern
heat pumps (see Definition 1.46). a.
Conduct one Maximum Temperature
Test (H01), two High Temperature Tests
(H12 and H11), one Frost Accumulation
Test (H22), and one Low Temperature
Test (H32). Conduct an additional Frost
Accumulation Test (H21) and Low
Temperature Test (H31) if both of the
following conditions exist:
1. Knowledge of the heat pump’s
capacity and electrical power at low
compressor capacity for outdoor
temperatures of 37°F and less is needed
to complete the section 4.2.3 seasonal
performance calculations; and
2.The heat pump’s controls allow
low-capacity operation at outdoor
temperatures of 37°F and less.
If the above two conditions are met,
an alternative to conducting the H21
Frost Accumulation is to use the
following equations to approximate the
capacity and electrical power:
˙
Determine the quantities Qhk=1 (47)
˙
and Ehk=1 (47) from the H11 Test and
evaluate them according to Section 3.7.
˙
Determine the quantities Qhk=1 (17) and
˙
Ehk=1 (17) from the H31 Test and
evaluate them according to Section 3.10.
b. Conduct the optional High
Temperature Cyclic Test (H1C1) to
determine the heating-mode cyclicdegradation coefficient, CDh. If this
optional test is conducted but yields a
tested CDh that exceeds the default CDh
or if the optional test is not conducted,
assign CDh the default value of 0.25. If
a two-capacity heat pump locks out low
capacity operation at lower outdoor
temperatures, conduct the optional High
Temperature Cyclic Test (H1C2) to
determine the high-capacity heatingmode cyclic-degradation coefficient, CDh
(k=2). If this optional test at high
capacity is conducted but yields a tested
CDh (k=2) that exceeds the default CDh
(k=2) or if the optional test is not
conducted, assign CDh the default value.
The default CDh (k=2) is the same value
as determined or assigned for the lowcapacity cyclic-degradation coefficient,
CDh [or equivalently, CDh (k=1)]. Table
11 specifies test conditions for these
nine tests.
TABLE 11.—HEATING MODE TEST CONDITIONS FOR UNITS HAVING A TWO-CAPACITY COMPRESSOR
Air entering indoor unit
temperature (°F)
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
Dry bulb
Wet bulb
Compressor
capacity
Heating air volume rate
Wet bulb
70
60(max)
62
56.5
Low ..............
Heating Minimum.1
70
60(max)
47
43
High .............
Heating Full-Load.2
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
E:\FR\FM\22OCR3.SGM
22OCR3
ER22OC07.078
pwalker on PROD1PC71 with RULES3
H01 Test ..............................................
(required, steady)
H12 Test ..............................................
(required, steady)
Air entering outdoor unit
temperature (°F)
Dry bulb
Test description
59930
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
TABLE 11.—HEATING MODE TEST CONDITIONS FOR UNITS HAVING A TWO-CAPACITY COMPRESSOR—Continued
Air entering indoor unit
temperature (°F)
Air entering outdoor unit
temperature (°F)
Dry bulb
Test description
Dry bulb
Wet bulb
Compressor
capacity
Heating air volume rate
Wet bulb
70
60(max)
47
43
High .............
(3)
70
60(max)
47
43
Low .............
Heating Minimum.1
70
60(max)
47
43
Low ..............
(4)
70
60(max)
35
33
High .............
Heating Full-Load.2
70
60(max)
35
33
Low .............
Heating Minimum.1
70
60(max)
17
15
High .............
Heating Full-Load.2
70
H1C2 Test ............................................
(optional, cyclic)
H11 Test ..............................................
(required)
H1C1 Test ............................................
(optional, cyclic)
H22 Test ..............................................
(required)
H21 Test5,6 ...........................................
(required)
H32 Test ..............................................
(required, steady)
H31 Test 5 ............................................
(required, steady)
60(max)
17
15
Low ..............
Heating Minimum. 1
1 Defined
in section 3.1.4.5.
in section 3.1.4.4.
3 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the H12 Test.
4 Maintain the airflow nozzle(s) static pressure difference or velocity pressure during the ON period at the same pressure or velocity as measured during the H11 Test.
5 Required only if the heat pump’s performance when operating at low compressor capacity and outdoor temperatures less than 37°F is needed to complete the section 4.2.3 HSPF calculations.
˙h
6 If table note #5 applies, the section 3.6.3 equations for Q k=1 (35) and E k=1 (17) may be used in lieu of conducting the H2 Test.
˙h
1
2 Defined
3.6.4 Tests for a heat pump having a
variable-speed compressor. a. * * *
Conduct the optional Maximum
Temperature Cyclic (H0C1) Test to
determine the heating mode cyclicdegradation coefficient, CDh. If this
optional test is conducted but yields a
tested CDh that exceeds the default CDh
or if the optional test is not conducted,
assign CDh the default value of 0.25. Test
conditions for the eight tests are
specified in Table 12. * * *
c. For multiple-split heat pumps
(only), the following procedures
supersede the above requirements. For
all Table 12 tests specified for a
minimum compressor speed, at least
one indoor unit must be turned off. The
manufacturer shall designate the
particular indoor unit(s) that is turned
off. The manufacturer must also specify
the compressor speed used for the Table
12 H2V Test, a heating-mode
intermediate compressor speed that falls
within 1⁄4 and 3⁄4 of the difference
between the maximum and minimum
heating-mode speeds. The manufacturer
should prescribe an intermediate speed
that is expected to yield the highest COP
for the given H2V Test conditions and
bracketed compressor speed range. The
manufacturer can designate that one or
more specific indoor units are turned off
for the H2V Test.
*
*
*
*
*
TABLE 12.—HEATING MODE TEST CONDITIONS FOR UNITS HAVING A VARIABLE-SPEED COMPRESSOR
Air entering indoor unit
temperature (°F)
Air entering outdoor unit
temperature (°F)
Dry bulb
Test description
Dry bulb
pwalker on PROD1PC71 with RULES3
H01 Test .......................
(required, steady)
H0C1 Test ....................
(optional, steady)
H12 Test .......................
(required, steady)
H11 Test .......................
(required, steady)
H1N Test ......................
(optional, steady)
H22 Test .......................
(optional)
H2V Test ......................
(required)
H32 Test .......................
(required, steady)
Wet bulb
Compressor speed
Heating air volume rate
Wet bulb
70
60(max)
62
56.5
Minimum .............................
Heating Minimum.1
70
60(max)
62
56.5
Minimum .............................
(2)
70
60(max)
47
43
Maximum ............................
Heating Full-Load.3
70
60(max)
47
43
Minimum .............................
Heating Minimum.1
70
60(max)
47
43
Cooling Mode Maximum ....
Heating Nominal.4
70
60(max)
35
33
Maximum ............................
Heating Full-Load.3
70
60(max)
35
33
Intermediate .......................
Heating Intermediate.5
70
60(max)
17
15
Maximum ............................
Heating Full-Load.3
1 Defined
in section 3.1.4.5.
the airflow nozzle(s) static pressure difference or velocity pressure during an ON period at the same pressure or velocity as measured during the H01 Test.
3 Defined in section 3.1.4.4.
4 Defined in section 3.1.4.7.
5 Defined in section 3.1.4.6.
2 Maintain
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
E:\FR\FM\22OCR3.SGM
22OCR3
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
1−
Ch =
D
COPcyc
COPss ( Tcyc )
1 − HLF
* * *
*
1097CA n Pv v′ .) * * *
n
*
*
*
*
*
3.9.1 Average space heating capacity
and electrical power calculations.
a. * * *
To account for the effect of duct losses
between the outlet of the indoor unit
and the section 2.5.4 dry-bulb
˙
temperature grid, adjust Qhk(35) in
accordance with section 7.3.4.3 of
ASHRAE Standard 37–2005
(incorporated by reference, see
§ 430.22).
*
*
*
*
*
3.11 Additional requirements for the
secondary test methods.
3.11.1 If using the Outdoor Air
Enthalpy Method as the secondary test
method.
*
*
*
*
*
3.11.1.3 Official test.
*
*
*
*
*
b. For space cooling tests, calculate
capacity from the outdoor air-enthalpy
measurements as specified in sections
7.3.3.2 and 7.3.3.3 of ASHRAE Standard
37–2005 (incorporated by reference, see
§ 430.22). Calculate heating capacity
based on outdoor air-enthalpy
measurements as specified in sections
7.3.4.2 and 7.3.3.4.3 of the same
ASHRAE Standard. Adjust the outdoorside capacity according to section
7.3.3.4 of ASHRAE Standard 37–2005
(incorporated by reference, see § 430.22)
to account for line losses when testing
split systems. Use the outdoor unit fan
power as measured during the official
test and not the value measured during
the preliminary test, as described in
section 8.6.2 of ASHRAE Standard 37–
2005 (incorporated by reference, see
§ 430.22), when calculating the capacity.
3.11.2 If using the Compressor
Calibration Method as the secondary
test method.
a. * * * Otherwise, conduct the
calibration tests according to ASHRAE
Standard 23–05 (incorporated by
reference, see § 430.22), ASHRAE
Standard 41.9–2000 (incorporated by
reference, see § 430.22), and section 7.4
of ASHRAE Standard 37–2005
(incorporated by reference, see
§ 430.22).
b. Calculate space cooling and space
heating capacities using the compressor
calibration method measurements as
specified in section 7.4.5 and 7.4.6
respectively, of ASHRAE Standard 37–
2005 (incorporated by reference, see
§ 430.22).
3.11.3 If using the RefrigerantEnthalpy Method as the secondary test
method. Conduct this secondary method
according to section 7.5 of ASHRAE
Standard 37–2005 (incorporated by
reference, see § 430.22). Calculate space
cooling and heating capacities using the
refrigerant-enthalpy method
measurements as specified in sections
7.5.4 and 7.5.5, respectively, of the same
ASHRAE Standard.
*
*
*
*
*
*
4. Calculations of Seasonal
Performance Descriptors
*
*
*
*
*
4.1.3 SEER calculations for an air
conditioner or heat pump having a twocapacity compressor. Calculate SEER
using Equation 4.1–1. Evaluate the
˙
space cooling capacity, Qck=1 (Tj), and
˙
electrical power consumption, Eck=1 (Tj),
of the test unit when operating at low
compressor capacity and outdoor
temperature Tj using,
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
PO 00000
Frm 00027
Fmt 4701
Sfmt 4725
E:\FR\FM\22OCR3.SGM
22OCR3
ER22OC07.096
ER22OC07.098
*
*
*
3.9 * * *
c. The official test period begins when
the preliminary test period ends, at
defrost termination. The official test
period ends at the termination of the
next occurring automatic defrost cycle.
When testing a heat pump that uses a
time-adaptive defrost control system
(see Definition 1.42), however, manually
initiate the defrost cycle that ends the
official test period at the instant
pwalker on PROD1PC71 with RULES3
*
indicated by instructions provided by
the manufacturer. If the heat pump has
not undergone a defrost after 6 hours,
immediately conclude the test and use
the results from the full 6-hour period
to calculate the average space heating
capacity and average electrical power
consumption.
For heat pumps that turn the indoor
fan off during the defrost cycle, take
steps to cease forced airflow through the
indoor coil and block the outlet duct
whenever the heat pump’s controls
cycle off the indoor fan. If it is installed,
use the outlet damper box described in
section 2.5.4.1 to affect the blocked
outlet duct.
*
*
*
*
*
f. * * * Sample measurements used
in calculating the air volume rate (refer
to sections 7.7.2.1 and 7.7.2.2 of
ASHRAE Standard 37–2005
(incorporated by reference, see
§ 430.22)) at equal intervals that span 10
minutes or less. (Note: In the first
printing of ASHRAE Standard 37–2005,
the second IP equation for Qmi should
read: .)
ER22OC07.080
*
*
*
*
3.7 Test procedures for steady-state
Maximum Temperature and High
Temperature heating mode tests (the
H01, H1, H12, H11, and H1N Tests). a.
* * *
b. Calculate indoor-side total heating
capacity as specified in sections 7.3.4.1
and 7.3.4.3 of ASHRAE Standard 37–
2005 (incorporated by reference, see
§ 430.22). * * *
*
*
*
*
*
3.8 Test procedures for the optional
cyclic heating mode tests (the H0C1,
H1C, H1C1 and H1C2 Tests).
*
*
*
*
*
3.8.1 Heating mode cyclicdegradation coefficient calculation. Use
the results from the optional cyclic test
and the required steady-state test that
were conducted at the same test
conditions to determine the heatingmode cyclic-degradation coefficient CDh.
Add ‘‘(k=2)’’ to the coefficient if it
corresponds to a two-capacity unit
cycling at high capacity. For the below
calculation of the heating mode cyclic
degradation coefficient, do not include
the duct loss correction from section
7.3.3.3 of ASHRAE Standard 37–2005
(incorporated by reference, see § 430.22)
˙
in determining Qhk(Tcyc) (or qcyc). If the
optional cyclic test is conducted but
yields a tested CDh that exceeds the
default CDh or if the optional test is not
conducted, assign CDh the default value
of 0.25. The default value for twocapacity units cycling at high capacity,
however, is the low-capacity coefficient,
i.e., CDh (k=2) = CDh. The tested CDh is
calculated as follows:
ER22OC07.079
*
59931
59932
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
˙
˙
where Qck=1 (82) and Eck=1 (82) are
˙
determined from the B1 Test, Qck=1 (67)
˙
and Eck=1 (67) are determined from the
F1 Test, and all four quantities are
calculated as specified in section 3.3.
Evaluate the space cooling capacity,
˙
Qck=2 (Tj), and electrical power
˙
consumption, Eck=2 (Tj), of the test unit
when operating at high compressor
capacity and outdoor temperature Tj
using,
*
optional tests are conducted, set CDc
(k=2) to the lower of:
a. the CDc (k=2) value calculated as
per section 3.5.3; or
b. the section 3.5.3 default value for
CDc (k=2) .
*
*
*
*
*
4.1.4 SEER calculations for an air
conditioner or heat pump having a
variable-speed compressor. Calculate
SEER using Equation 4.1–1. Evaluate the
˙
space cooling capacity, Qck=1 (Tj), and
˙
electrical power consumption Eck=1 (Tj),
of the test unit when operating at
minimum compressor speed and
outdoor temperature Tj. Use Equations
4.1.3–1 and 4.1.3–2, respectively, where
˙
˙
Qck=1 (82) and Eck=1 (82) are determined
˙
˙
from the B1 Test, Qck=1 (67) and Eck=1
(67) are determined from the F1 Test,
and all four quantities are calculated as
specified in section 3.3. Evaluate the
˙
space cooling capacity, Qck=2 (Tj), and
˙
electrical power consumption, Eck=2 (Tj),
of the test unit when operating at
maximum compressor speed and
outdoor temperature Tj. Use Equations
4.1.3–3 and 4.1.3–4, respectively, where
˙
˙
Qck=2 (95) and Eck=2 (95) are determined
˙
˙
from the A2 Test, Qck=2 (82) and Eck=2
(82) are determined from the B2 Test,
and all four quantities are calculated as
specified in section 3.3. Calculate the
˙
space cooling capacity, Qck=v (Tj), and
˙
electrical power consumption, Eck=v (Tj),
of the test unit when operating at
outdoor temperature Tj and the
intermediate compressor speed used
during the section 3.2.4 (and Table 6) EV
Test using,
˙
˙
where Qck=v (87) and Eck=v (87) are
determined from the Ev Test and
calculated as specified in section 3.3.
Approximate the slopes of the k = v
intermediate speed cooling capacity and
electrical power input curves, MQ and
ME, as follows: * * *
where,
Use Equations 4.1.3–1 and 4.1.3–2 for Tj
˙
˙
= 87°F to determine Qck=l (87) and Eck=l
(87), respectively. Use Equations 4.1.3–
3 and 4.1.3–4 for Tj = 87°F to determine
˙
˙
Qck=2 (87) and Eck=2 (87), respectively.
Calculating Equation 4.1–1 quantities
*
4.1.3.3
*
*
* * *
*
PLFj = 1 − Cc (k = 2) ⋅ 1 − X k = 2 (Tj ) ,
D
the part load factor, dimensionless.
Obtain the fraction bin hours for the
cooling season,
nj
N
,
pwalker on PROD1PC71 with RULES3
ER22OC07.083
ec (Tj )
N
4.1.4.3) in responding to the building
load. Use Equation 4.1–2 to calculate
the building load, BL(Tj), for each
temperature bin.
4.1.4.1 * * * Use Equations 4.1.3–1
and 4.1.3–2, respectively, to evaluate
˙
˙
Qck=l (Tj) and Eck=l (Tj).
4.1.4.2 * * *
A = EER k =2 (T2 ) − B ⋅ T2 − C ⋅ T22
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
PO 00000
Frm 00028
Fmt 4701
Sfmt 4725
E:\FR\FM\22OCR3.SGM
ER22OC07.097
differs depending upon whether the test
unit would operate at minimum speed
(section 4.1.4.1), operate at an
intermediate speed (section 4.1.4.2), or
operate at maximum speed (section
and
ER22OC07.082
N
22OCR3
ER22OC07.081
q c (Tj )
ER22OC07.084
ER22OC07.085
ER22OC07.086
ER22OC07.087
from Table 16. Use Equations 4.1.3–3
and 4.1.3–4, respectively, to evaluate
˙
˙
Qck=2 (Tj) and Eck=2 (Tj). If the optional
C2 and D2 Tests described in section
3.2.3 and Table 5 are not conducted, set
CDc (k=2) equal to the default value
specified in section 3.5.3. If these
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
59933
where,
T1 = the outdoor temperature at which
the unit, when operating at minimum
compressor speed, provides a space
cooling capacity that is equal to the
˙
building load (Qck=l (Tl) = BL(T1)), °F.
Determine T1 by equating Equations
4.1.3–1 and 4.1–2 and solving for
outdoor temperature. Tv = the outdoor
temperature at which the unit, when
operating at the intermediate
compressor speed used during the
section 3.2.4 EV Test, provides a space
cooling capacity that is equal to the
˙
building load (Qck=v (Tv) = BL(Tv)), °F.
Determine Tv by equating Equations
4.1.4–1 and 4.1–2 and solving for
outdoor temperature. * * *
*
procedures supersede the above
requirements for calculating EERk=i (Tj).
For each temperature bin where Tl < Tj
< Tv,
*
*
*
*
For multiple-split air conditioners
and heat pumps (only), the following
EER k =i (Tj ) = EER k =1 (T1 ) +
*
*
*
*
*
4.2.3.3
EER k = v (Tv ) − EER k =1 (T1 )
⋅ (Tj − T1 ).
Tv − T1
* * *
If this optional test is conducted, set CDh
(k=2) to the lower of:
a. the CDh (k=2) value calculated as
per section 3.8.1; or
b. the section 3.8.1 default value for
CDh (k=2).
Determine the low temperature cutout factor, d (Tj), using Equation 4.2.3–
3.
*
*
*
*
*
4.2.4 * * *
*
For multiple-split heat pumps (only),
the following procedures supersede the
above requirements for calculating
COPhk=i (Tj). For each temperature bin
where T3 > Tj > Tvh,
*
COPhk = v ( Tvh ) − COPhk =1 ( T3 )
Tvh − T3
⋅ ( Tj − T3 ) .
For each temperature bin where Tvh ≥ Tj
> T4,
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
PO 00000
ER22OC07.089
pwalker on PROD1PC71 with RULES3
COPhk =i ( Tj ) = COPhk =1 ( T3 ) +
ER22OC07.090
*
*
* * *
Frm 00029
Fmt 4701
Sfmt 4700
E:\FR\FM\22OCR3.SGM
22OCR3
ER22OC07.088
*
4.2.4.2
ER22OC07.091
ER22OC07.092
ER22OC07.093
If the optional H1C2 Test described in
section 3.6.3 and Table 11 is not
conducted, set CDh (k=2) equal to the
default value specified in section 3.8.1.
ER22OC07.094
PLFj = 1 − Ch ( k = 2 ) ⋅ 1 − X k = 2 (Tj ) .
D
59934
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 / Rules and Regulations
*
*
*
*
*
7. Section 430.62 is amended in
subpart F by revising paragraphs (a)(4)(i)
and (ii) to read as follows:
I
§ 430.62
Submission of data.
pwalker on PROD1PC71 with RULES3
(a) * * *
(4) * * *
(i) Central air conditioners, the
seasonal energy efficiency ratio. For
central air conditioners whose seasonal
energy efficiency ratio is based on an
VerDate Aug<31>2005
17:58 Oct 19, 2007
Jkt 214001
COPhk = 2 ( T4 ) − COPhk = v ( Tvh )
T4 − Tvh
installation that includes a particular
model of ducted air mover (e.g., furnace,
air handler, blower kit, etc.), the model
number of this ducted air mover must
be included among the model numbers
listed on the certification report.
(ii) Central air conditioning heat
pumps, the seasonal energy efficiency
ratio and heating seasonal performance
factor. For central air conditioning heat
pumps whose seasonal energy efficiency
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
⋅ ( Tj − Tvh ) .’’
ratio and heating seasonal performance
factor are based on an installation that
includes a particular model of ducted
air mover (e.g., furnace, air handler,
blower kit, etc.), the model number of
this ducted air mover must be included
among the model numbers listed on the
certification report.
*
*
*
*
*
[FR Doc. 07–5142 Filed 10–19–07; 8:45 am]
BILLING CODE 6450–01–P
E:\FR\FM\22OCR3.SGM
22OCR3
ER22OC07.095
COPhk =i ( Tj ) = COPhk = v ( Tvh ) +
Agencies
[Federal Register Volume 72, Number 203 (Monday, October 22, 2007)]
[Rules and Regulations]
[Pages 59906-59934]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 07-5142]
[[Page 59905]]
-----------------------------------------------------------------------
Part III
Department of Energy
-----------------------------------------------------------------------
10 CFR Part 430
Energy Conservation Program for Consumer Products: Test Procedure for
Residential Central Air Conditioners and Heat Pumps; Final Rule
Federal Register / Vol. 72, No. 203 / Monday, October 22, 2007 /
Rules and Regulations
[[Page 59906]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Part 430
[Docket No. EE-RM/TP-02-002]
RIN 1904-AB55
Energy Conservation Program for Consumer Products: Test Procedure
for Residential Central Air Conditioners and Heat Pumps
AGENCY: Department of Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: The Department of Energy (DOE) is amending its test procedure
for residential central air conditioners and heat pumps. This final
rule implements test procedure changes for small-duct, high-velocity
systems, two-capacity units, and updates references to the current
American Society of Heating, Refrigerating, and Air-Conditioning
Engineers (ASHRAE) standards. Today's rule also clarifies issues
associated with sampling tested systems and rating untested split-
system combinations.
DATES: This rule is effective April 21, 2008. Incorporation by
reference of certain publications in the final rule is approved by the
Director of the Federal Register as of April 21, 2008.
ADDRESSES: You may review copies of all materials related to this
rulemaking at the U.S. Department of Energy, Forrestal Building, Room
1J-018 (Resource Room of the Building Technologies Program), 1000
Independence Avenue, SW., Washington, DC, (202) 586-9127, between 9
a.m. and 4 p.m., Monday through Friday, except Federal holidays. Please
call Ms. Brenda Edwards-Jones at the above telephone number for
additional information regarding visiting the Resource Room. Please
note: DOE's Freedom of Information Reading Room (formerly Room 1E-190
at the Forrestal Building) is no longer housing rulemaking materials.
FOR FURTHER INFORMATION CONTACT: Michael G. Raymond, U.S. Department of
Energy, Office of Energy Efficiency and Renewable Energy, EE-2J, 1000
Independence Avenue, SW., Washington, DC 20585-0121, (202) 586-9611, e-
mail: michael.raymond@ee.doe.gov; or Francine Pinto, Esq., U.S.
Department of Energy, Office of the General Counsel, GC-72, 1000
Independence Avenue, SW., Washington, DC 20585-0121, (202) 586-9507, e-
mail: Francine.Pinto@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
I. Introduction
A. Authority
B. Background
C. Summary of the Test Procedure Revisions
II. Discussion of Comments
A. Frost Accumulation Test Duration
B. Multiple-Split Systems
C. Defining ``Repeatable'' for Cyclic Tests
D. Outdoor Air Test Conditions for Units Having a Two-Capacity
Compressor
E. Air Volume Rate Less Than Manufacturer's Specified Value
F. Updating References to Industry Standards
G. Maximum and Minimum Speed Values for Calculating
NQ and NE
H. Using the Default or Tested Value of Cyclic-Degradation
Coefficient
I. Guidance on the Inclusion of Pre-Production Units in the
Sample Population
J. Clarification of the Sample Population Used To Validate the
Rated Seasonal Energy Efficiency Ratio and Heating Seasonal
Performance Factor of Heat Pumps
K. Clarification of the Definition of a ``Highest-Sales-Volume
Combination''
L. Upper Limit on the Difference Between Calculated and Tested
Seasonal Energy Efficiency Ratio and Heating Seasonal Performance
Factor Values
M. Clarification of the Published Ratings for Untested Split-
System Combinations
N. Ratings That Are Based on Using a Particular Furnace or
Ducted Air Mover
O. Revisions to the Definition of ``Coil Family''
III. Summary of Other Additions, Changes, and Corrections to the
Department of Energy Residential Central Air Conditioner and Heat
Pump Test Procedure
IV. Effect of Test Procedure Revisions on Compliance With Standards
V. Procedural Requirements
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under the Treasury and General Government
Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
VI. Approval of the Office of the Secretary
I. Introduction
A. Authority
Part B of Title III of the Energy Policy and Conservation Act
(EPCA) established the Energy Conservation Program for Consumer
Products Other Than Automobiles (Program). (42 U.S.C. 6291 et seq.) The
products currently subject to this Program (covered products) include
central air conditioners and heat pumps, the subject of today's final
rule.
Under EPCA, the Program consists of three parts: Testing, labeling,
and the Federal energy conservation standards. DOE, in consultation
with the National Institute of Standards and Technology (NIST), is
authorized to establish or amend test procedures as appropriate for
each of the covered products. (42 U.S.C. 6293) The purpose of these
test procedures is to measure energy efficiency, energy use, or
estimated annual operating cost of a covered product during a
representative, average use cycle or period of use. The test procedure
must not be unduly burdensome to conduct. (42 U.S.C. 6293(b)(3))
If a test procedure is amended, DOE is required to determine to
what extent, if any, the proposed new test procedure would alter the
measured energy efficiency of any covered product as determined under
the existing test procedure. (42 U.S.C. 6293(e)(1)) If DOE determines
that an amended test procedure would alter the measured energy
efficiency of a covered product, DOE is required to amend the
applicable energy conservation standard with respect to such test
procedure. In determining any such amended energy conservation
standard, DOE is required to measure the energy efficiency or energy
use of a representative sample of covered products that minimally
comply with the existing standard. The average efficiency or energy use
of this representative sample, tested using the amended test procedure,
constitutes the amended standard. (42 U.S.C. 6293(e)(2)) DOE has
determined that today's amended test procedure does not alter the
measured efficiency or measured energy use of minimally compliant
central air conditioners and heat pumps.
Beginning 180 days after a test procedure for a covered product is
prescribed, no manufacturer, distributor, retailer, or private labeler
may make representations with respect to the energy use, efficiency, or
cost of energy consumed by such product, except as reflected in tests
conducted according to the DOE procedure. (42 U.S.C. 6293(c)(2)) Any
manufacturer, distributor, retailer, or private labeler may petition
the Secretary of Energy for an extension of not more than 180 days to
test and make representations in accordance with the amended DOE test
procedure. (42 U.S.C. 6293(c)(3)) In addition, all existing waivers
concerning residential multi-split
[[Page 59907]]
systems terminate on the effective date of today's final rule.
B. Background
A final rule published on October 11, 2005, updated and completely
re-organized the DOE residential central air conditioner and heat pump
test procedure. 70 FR 59122. During this prior rulemaking, a few issues
were identified too late in the process to allow them due
consideration. DOE investigated these issues and considered additional
topics that could further improve the testing and rating process. As a
result of these efforts, DOE issued a Notice of Proposed Rulemaking on
July 20, 2006 (hereafter referred to as the July 2006 proposed rule).
71 FR 41320. Although the majority of the proposed changes pertained to
the test procedure set forth in appendix M to subpart B of Title 10,
Code of Federal Regulations, Part 430 (10 CFR part 430), DOE also
proposed revisions to sections of subparts B and F of 10 CFR part 430
that concern the sampling of tested units and the ratings of untested
split-system combinations. 10 CFR 430.24 and 430.62. DOE held a public
meeting on the July 2006 proposed rule on August 23, 2006.
On October 10, 2006, DOE published a Federal Register notice
correcting two inadvertent omissions in the July 2006 proposed rule. 71
FR 59410. These omissions contained the regulatory language governing
the criterion for using an air volume rate that is less than the
manufacturer's specified value: One case covered air conditioners and
heat pumps, the other case covered heating-only heat pumps. This change
was described in the preamble of the July 2006 proposed rule, but was
not included in the regulatory language. In addition to publishing the
corrected regulatory language in the Federal Register, the omitted
regulatory language was distributed at the August 23, 2006, public
meeting.
C. Summary of the Test Procedure Revisions
The revisions adopted in today's final rule include the following
changes to appendix M of Subpart B of 10 CFR part 430: (1) Adding new
testing requirements for small-duct, high-velocity systems; (2)
reinstating the optional testing to determine the cyclic-degradation
coefficient (CD) of a two-capacity unit when cycling on and
off at high capacity; (3) shortening the maximum duration of the Frost
Accumulation Tests; (4) allowing the use of default equations to
approximate the capacity and power of a two-capacity unit when
operating at low-capacity/stage and at an outdoor temperature of 35
degrees Fahrenheit ([deg]F); (5) implementing modifications and
additions that specifically address elements unique to testing and
rating modulating multi-split systems; (6) allowing indoor capacities
used in calculating Seasonal Energy Efficiency Ratio (SEER) and Heating
Seasonal Performance Factor (HSPF) to be corrected for duct losses; (7)
defining the term ``standard air;'' (8) changing the outdoor
temperature conditions used for one of the low-capacity, steady-state,
cooling mode tests on a two-capacity unit; (9) renaming ``Cooling and
Heating Certified Air Volume Rates'' to ``Full-Load Air Volume Rates;''
(10) modifying the criterion for using an air volume rate less than the
manufacturer's specified value; (11) updating the references to current
versions of the Air-Conditioning and Refrigeration Institute (ARI) and
ASHRAE standards; (12) adding language to better explain the SEER and
HSPF calculation steps for variable-speed equipment; and (13) adding
text to clarify the provision to use the default value of the cyclic-
degradation coefficient if it is lower than the tested value.
Today's final rule also amends sections 430.2, 430.24 and 430.62 of
10 CFR part 430, as follows: (1) It expands the options for meeting the
data submission requirements when verifying an alternative rating
method (ARM); (2) it clarifies the sample population to be used to
validate the rated SEER and rated HSPF of a heat pump; (3) it clarifies
the definition of a ``highest-sales-volume combination'' (HSVC); (4) it
clarifies DOE's role in verifying ratings for untested split system
combinations; (5) it clarifies how to apply the ARM to obtain published
ratings for untested, split-system combinations; (6) it adds the
requirement that ratings for an air conditioner or heat pump tested
with a furnace or similar ducted air mover include the model number of
the air mover as part of the overall equipment model number; (7) it
clarifies the responsibilities of private labelers; (8) it adds the
statutory definition of ``private labeler;'' and (9) it adds
definitions for terms, including ``indoor unit'', ``outdoor unit'', and
``ARM/simulation adjustment factor.''
II. Discussion of Comments
In addition to the comments received at the August 23, 2006, public
meeting, DOE received written comments to the July, 2006 proposed rule
from ARI, Nordyne, Mitsubishi, Fujitsu General Limited (Fujitsu),
Carrier Corporation (Carrier), the American Council for an Energy-
Efficient Economy (ACEEE), Sanyo Fisher Service Corporation (Sanyo),
Lennox International (Lennox), and the China WTO/TBT National
Notification and Enquiry Center (China). The comments and the DOE
response to them are discussed below. References to section numbers
within this document refer to the section numbers of Appendix M to
Subpart B of 10 CFR part 430-Uniform Test Method for Measuring the
Energy Consumption of Central Air Conditioners and Heat Pumps (Appendix
M).
A. Frost Accumulation Test Duration
DOE proposed shortening the maximum test interval of a Frost
Accumulation Test from 12 hours to 6 hours when testing a two-capacity
heat pump at low capacity. ARI supported DOE's proposal to lessen the
test burden, but recommended that the maximum duration be further
shortened to 3 hours. (ARI, No. 21 at p. 2)\1\ ARI stated that
``preliminary testing done by manufacturers shows a variation in HSPF
of less than one tenth \2\ when the test is reduced from 12 to 3
hours.'' (ARI, Id.) In a follow-up communication, ARI clarified that
its 3-hour recommendation applies to all Frost Accumulation Tests, not
just the test at low-capacity. (ARI, No. 25 at p. 2) ARI provided a
table showing the percentage of the total interval allocated to
defrosting for cycles lasting 6, 7, 8, 9, and 10 minutes; percentages
were calculated for complete (frost + defrost) intervals ranging from 1
hour to 12 hours. As an example, for tests lasting 12, 6, and 3 hours,
the percentages of time spent defrosting are 1.1, 2.2, and 4.4 percent,
respectively, if the defrost lasts 8 minutes in all cases. (ARI, No. 25
at p. 3) In addition to recommending that any change be applied to all
Frost Accumulation Tests, Nordyne and Carrier recommended manufacturers
be given the option of using either the procedure specified in ASHRAE
Standard 37 (which uses a maximum test interval of 3 hours) or the
algorithm specified in the DOE test procedure. (Nordyne, No. 19 at p.
2; Carrier, No. 17
[[Page 59908]]
at p. 2) In summary, the stakeholders recommended applying changes to
all Frost Accumulation Tests (not just to the one low-capacity test, as
proposed), reducing the maximum duration to 3 hours instead of 6 hours,
and adding an alternative test method.
---------------------------------------------------------------------------
\1\ A notation in the form ``ARI, No.21 at p. 2'' identifies a
written comment the Department has received and has included in the
docket of this rulemaking. This particular notation refers to a
comment (1) by the Air-Conditioning and Refrigeration Institute
(ARI), (2) in document number 21 in the docket of this rulemaking
(maintained in the Resource Room of the Building Technologies
Program), and (3) appearing on page 2 of document number 21.
Likewise, ``Public Hearing Tr., p. 178,'' for example, would refer
to page 178 of the transcript of the ``Public Meeting on Test
Procedures for Central Air Conditioners'' held in Washington, DC,
August 23, 2006.
\2\ This means an absolute variation in HSPF of 0.1, such as
between 8.1 and 8.2.
---------------------------------------------------------------------------
DOE believes that if all three changes were adopted, the HSPF
ratings of heat pumps would be changed, since the ASHRAE Standard 37
``T'' Test Procedure may terminate after 0, 1, 2, or 3 complete cycles
whereas the DOE Frost Accumulation Test is either 0 or 1 complete
cycle. The different cycles in the ASHRAE and DOE test methods can
yield different average heating capacity and power consumption results
at the DOE-specified 35 [deg]F dry-bulb/33 [deg]F wet-bulb outdoor test
conditions which would affect the HSPF rating. As for shortening the
maximum test time to 3 hours, such a change may benefit heat pumps
(i.e., give a higher average heating capacity) that initiate a defrost
of the outdoor coils between 3 and 6 hours after the start of the test.
In such cases, the heat pump's average heating capacity will not
account for the energy used for defrosting. By not accounting for the
defrost energy, the shorter test time would overstate the heating
capacity and HSPF. Thus, DOE will not reduce the maximum test duration
by the additional 3 hours or add the ASHRAE Standard 37 procedure as an
alternate test method as part of this final rule.
DOE agrees with comments recommending the same maximum limit for
all Frost Accumulation Tests. The low-capacity Frost Accumulation Test
is projected to be the most likely of the 35 [deg]F tests to approach
the proposed 6-hour limit, followed by the required Frost Accumulation
Test at the intermediate speed when testing a variable-speed heat pump.
All other Frost Accumulation Tests are more likely to build frost and
are likely to result in the unit defrosting in less time than it would
at the intermediate speed. Thus, triggering the 6-hour limit is less
likely when applied to these other cases. Finally, DOE concludes that 6
hours offers a sufficiently long duration for evaluating performance in
all cases. As noted in the July 2006 proposed rule, if a heat pump has
not defrosted in 6 hours, it is either not building frost or is
completely frosted and probably has been so for more than half of the
interval. In both cases, the benefits from continuing to run the test
past 6 hours are minimal. Therefore, DOE reduces the maximum duration
of all Frost Accumulation Tests from 12 hours to 6 hours. This change
appears in section 3.9 of Appendix M.
B. Multiple-Split Systems
DOE received comments on issues related to the testing and rating
of multiple-split air-conditioning systems (multi-split systems),
including: (1) Rating multi-split systems based on SEER (if they
compete primarily with ducted central air conditioners), or rating them
based on EER (if they compete with room air conditioners) (SEER or
EER); (2) adopting a separate test procedure for multi-split systems,
such as Draft ARI Standard 1230 (ARI 1230); (3) allowing one or more
indoor coils to turn off during any test, if representative of normal
operation (Coils active during test); (4) allowing the manufacturer to
specify the compressor speed used during the minimum-speed,
intermediate-speed and maximum-speed tests (Compressor speed); (5)
extending multi-split system test procedure changes to one-to-one
ducted systems (One-to-one applicability); and (6) adding the term
``tested combination'' within 10 CFR 430.2 for determining the
combination of indoor units to be tested when testing a multi-split
outdoor unit, and the appropriate rating of the tested combination
(Tested combination).
SEER or EER. DOE received several comments on whether multi-split
systems compete primarily with ducted residential central air
conditioners and heat pumps and as such, should be rated based on SEER
and HSPF, or if they compete with room air conditioners and should be
rated in terms of EER and COP. Trane argues that residential size
multi-split systems compete for the same markets as ducted residential
central systems: both serve multiple rooms, one ducts air whereas the
second ``ducts'' refrigerant. (Public Hearing Tr., p. 178) Carrier and
ACEEE support rating conventional central air conditioners and heat
pumps and multi-split systems using the same descriptors. (Carrier, No.
17 at p. 1 and ACEEE, No. 16 at p. 3) According to Mitsubishi,
``ductless split-systems, including ductless multi-split systems, are
used for room or spot cooling applications while the rest of the USE
[unitary small equipment] equipment (i.e., central systems) is applied
in a ducted environment for multiple rooms or whole houses.''
(Mitsubishi, No. 20 at p. 3) DOE believes residential-size multi-split
systems compete with ducted central systems and that the consumer will
be best served if multi-split systems can be compared with central air
conditioners and central air-conditioning heat pumps. Therefore, DOE
concludes that SEER and HSPF are better descriptors than EER and COP.
ARI 1230. ARI, Sanyo, Fujitsu, Mitsubishi, and Daikin AC
(Americas), Inc. (Daikin) urged DOE to adopt Draft ARI Standard 1230,
``Performance Rating of Multi-Split Air-Conditioning and Heat Pump
Equipment'' in lieu of the proposed rule. (ARI, No. 21 at p. 3; Sanyo,
No. 15 at pp. 2-3; Fujitsu, No. 13 at p. 3; Mitsubishi, No. 20 at pp.
4-5; Public Hearing Tr., pp. 153-154) China recommends that DOE not
cover multi-split systems within the residential central air
conditioner and heat pump test procedure until all the technical issues
have been resolved. (China, No. 14 at p. 1) Copeland recommends that
DOE review and consider the approaches being taken by China and the
European Union on how to test and rate multi-split systems. (Public
Hearing Tr., p. 64) Nordyne supports the changes proposed in the July
2006 proposed rule to cover multi-split systems as an interim solution,
but states that further study is needed for a long term solution.
(Nordyne, No. 19 at p. 2) Lennox, on the other hand, believes that
multi-split systems should be rated using the current test procedure
for central air conditioners and central air conditioning heat pumps.
(Lennox, No. 22 at p. 2) Sanyo and Fujitsu point out that the test
procedure does not address units that can simultaneously cool and heat;
the test procedure does not specify how many indoor units are turned
off during a given test; and doubts whether the current DOE tests for
variable-speed systems can approximate the unit's ``performance map.''
\3\ (Sanyo, No. 15 at pp. 2-3; Fujitsu, No. 13 at pp. 2-3; Public
Hearing Tr., pp. 94-95, 110)
---------------------------------------------------------------------------
\3\ Performance map refers to a plot that shows the effect of
compressor speed, number of indoor unit turned on versus off, and
outdoor temperature conditions on the unit's space conditioning
capacity and power consumption.
---------------------------------------------------------------------------
DOE is not convinced that residential-size multi-split systems
require a separate test procedure from the current test procedure found
in Appendix M. While it is true that the current test procedure fails
to account for the energy savings derived from a simultaneous cooling
and heating mode, the current test procedure is adaptable and DOE
believes the tests for variable-speed systems in Appendix M offer a
reasonable starting point for producing energy efficiency and energy
use estimates. Once data become available that provides insight as to
the energy use and efficiency benefits of simultaneous cooling and
heating, and alternative or additional tests to estimate these benefits
are formulated, DOE will then consider further
[[Page 59909]]
amendments to the test procedure. Accordingly, DOE is not adopting a
new test procedure and energy efficiency and energy use ratings will
continue to be based on the test procedure found in Appendix M.
Regarding the stakeholder recommendation to adopt draft ARI
Standard 1230, the current draft (as distributed in June 2007), is less
complete for residential multi-split systems than the DOE test
procedure in today's final rule. For example, ARI Standard 1230 (June
2007 draft) lacks information on how to conduct intermediate speed
tests, whether any indoor units are to be turned off for part-load
tests, how to interpolate EER and COP in the intermediate speed range,
and generally how to calculate SEER and HSPF. Furthermore, ARI has not
finalized ARI Standard 1230 and, as such it cannot be incorporated by
reference since it could be amended prior to being adopted in final
form. Therefore, for the reasons discussed above, DOE is not adopting
ARI Standard 1230 (June 2007 draft) in today's final rule.
As for considering changes that are modeled on the approaches taken
in China and the European Union, DOE sees their potential use as
limited given the current EPCA requirement to calculate annual measures
of energy consumption. The European Union HVAC trade association,
Eurovent, lists ratings for residential-size multi-splits that are
based on full load EER and COP and their European SEER (ESEER) is thus
far limited to liquid chilling packages, not unitary air conditioners
(i.e., residential central air conditioners and central air
conditioning heat pumps). The ESEER is actually a variation of ARI
Standard 340/360's IPLV, which is used to quantify the part-load
performance of larger, non-residential systems. An IPLV equivalent is
also used in China. Neither international resource explicitly addresses
the number of indoor units to be turned off during a given part-load
test; such information would be necessary in order to get an accurate
measure of equipment efficiency for comparison purposes.
Coils active during test. Concerning the issue of whether one or
more indoor units should be turned off during any given test, Daikin
commented that you cannot rely on the unit's controls to make the
decision when operated in a laboratory environment. (Public Hearing
Tr., p. 62) Given this, DOE offered, at the public meeting, an
algorithm for specifying the number of indoor units that are turned on
for a given test. This algorithm is shown in Table 1, below. To
evaluate the effect of such an algorithm, Fujitsu conducted simulations
in which it modeled the performance of a unit if operated at the DOE
test procedure cooling mode conditions. Fujitsu considered cases where
the number of indoor units turned on for the two minimum speed and one
intermediate speed tests changed. Fujitsu reported results for three
cases: the first case, all four indoor units are on for all tests; the
second case, three indoor units are on for the intermediate speed test
and two indoor units are on for the minimum speed tests; and the third
case, two indoor units are on for the intermediate-speed test and one
indoor unit is on for the minimum speed tests. (Fujitsu, No. 13 at pp.
1-2) Using the simulated data, Fujitsu reported that the first case
yields the highest SEER. In comparison, Fujitsu reported that the SEER
drops by 4.7 percent for the second case and by 11.6 percent for the
third case. Fujitsu concluded that the number of operating indoor units
may have a great impact on the result, and that the operating ranges in
Table 1 were not appropriate.
Table 1.--Approach to Regulating the Number of Active Indoor Units
(Example Case of a Multi-Split System Having 4 Identical Indoor Units)
------------------------------------------------------------------------
Number of
Percentage output relative to full load capacity operating
indoor units
------------------------------------------------------------------------
75% to 100%............................................. 4
50% to 75%.............................................. 3
25% to 50%.............................................. 2
0% to 25%............................................... 1
------------------------------------------------------------------------
(DOE, No. 12.3 at p. 12)
DOE recognizes that when field installed, a multi-split system will
often operate with one or more of its indoor units turned off. In an
effort to have the DOE test procedure capture this part-load operating
mechanism, today's final rule requires that at least one indoor unit
must be turned off for tests conducted at minimum compressor speed. In
addition, the manufacturer may elect to have one or more indoor units
turned off for tests conducted at the intermediate compressor speed. In
all cases, the manufacturer specifies the particular indoor unit(s)
that is turned off.
Compressor speed. ARI, Sanyo, Fujitsu, and Mitsubishi opposed DOE's
proposed definition of maximum compressor speed. (ARI, No. 21 at p. 2;
Sanyo, No. 15 at p. 2; Fujitsu, No. 13 at p. 2; Mitsubishi, No. 20 at
p. 4) They recommended using the rated capacity or nominal rated speed
because performance at that compressor speed is used in sizing and
selling the product. ARI and Sanyo supported DOE's proposal to allow
the manufacturer to specify the compressor speed used for the minimum-
speed and intermediate-speed tests. (ARI, No. 21 at p. 2; Sanyo, No. 15
at p. 2) Sanyo and ARI, moreover, both believe that test laboratories
must accept the task of providing test facilities that can maintain
steady test room conditions and accurately measure capacity at very low
loads. (ARI, No. 21 on pp. 2-3; Sanyo, No. 15 on p. 2)
Regarding the maximum and minimum compressor speed issue, DOE
reviewed test procedure waivers processed in the 1980's, and the 1988
test procedure rulemaking that first added coverage for air
conditioners and heat pumps having a variable-speed compressor. (53 FR
8304, March 14, 1988) None of these actions explicitly defined maximum
and minimum compressor speed. Instead, the manufacturer was allowed to
define these speeds for its particular units. The evolution to include
maximum and minimum compressor speeds among those elements that are
``conducted in accordance with the manufacturer's instructions''
occurred because of the test laboratory's need for a mechanism to
override the unit's normal controls, so that the compressor can be
forced to operate at fixed speeds for the DOE-specified lab tests. As
part of today's final rule, DOE considered adopting a specific
definition for maximum speed and requiring additional lab verification
tests, but has decided against it because there is no compelling
technical argument for doing so. The current approach effectively
allows the manufacturer to de-rate the unit's maximum capacity in order
to raise its performance descriptor. As long as that de-rated capacity
is used for sizing the particular multi-split combination, then the
practice is acceptable. DOE, however, does not agree with substituting
``nominal'' or ``rated'' compressor speed for ``maximum'' compressor
speed, as that will not allow for test results that can be used to
generate a performance map representing how particular multi-split
combinations will operate in the field.
The DOE test procedure will continue to require variable-speed
systems to be tested at their minimum compressor speed. Manufacturers
will be relied upon to provide the independent testing laboratory with
a means for conducting tests at this speed. Minimum speed may not be
the absolute minimum speed at which the compressor can operate, but
[[Page 59910]]
it is expected to be a speed below which the compressor would rarely
operate. DOE concurs with Sanyo and ARI and expects test laboratories
to measure performance over the wide modulation range that is
characteristic of multi-splits. Thus, to the issue of what compressor
speed to use when conducting minimum speed and maximum speed tests, DOE
is maintaining the current test procedure language in sections 3.2.4
and 3.6.4 of Appendix M.
DOE adopts the July 2006 proposed change of allowing the
manufacturer to specify the compressor speed used for the cooling and
heating intermediate speed/capacity tests. This change provides the
manufacturer an opportunity to select and verify the peak-efficiency of
the unit being tested. Coupled with this change, and as also proposed
in the July 2006 notice, steady-state efficiency (EER and COP) over the
intermediate-speed range shall be calculated using piece-wise linear
fits: a line connecting the minimum- and intermediate-speed balance
points and a line connecting the intermediate- and maximum-speed
balance points.
One-to-one applicability. Carrier noted the need for transparency
in testing and manufacturer test results so that interested parties can
verify the performance claims without having to consult the
manufacturer. (Carrier, No. 17 at p. 2) Trane and ARI pointed out that
any steps introduced to facilitate testing and rating modulating multi-
split systems should also be allowed for modulating one-to-one ducted
systems to promote comparability. (Public Hearing Tr., pp. 87 and 118;
ARI, No. 21 at p. 3) With respect to Carrier's comment, variable-speed
systems do not lend themselves to being tested by a third party who
does not have the cooperation of the outdoor unit manufacturer. Third-
party certification programs thus become especially important as they
offer the primary pathway for independent verification. For those
multi-split products that are not covered by a third-party
certification program, DOE can request from the manufacturer the
information needed to conduct such testing along with reviewing the lab
test results maintained by the manufacturer, that substantiate the
multi-split system's ratings. 10 CFR 430.62(d).
Of the changes being implemented today to allow testing and rating
of residential modulating multi-split systems, two changes could be
applied to variable-speed one-to-one units. Together, these two changes
would allow the manufacturer to specify the compressor speed used for
the intermediate-speed tests and then use linear fits for calculating
COP and EER within the intermediate-speed operating range. Adopting
these two changes for variable-speed one-to-one units would create a
second compliance path that would likely cause different SEER and HSPF
ratings than the current test procedure. Therefore, in adopting these
changes, DOE is not extending them to variable-speed one-to-one units.
Although DOE expects the current test procedure to yield the higher
ratings for one-to-one units, it will rely on the waiver process if any
manufacturer seeks to adopt these two multi-split test procedure
changes for use in rating variable-speed one-to-one units.
Tested combination. On the issue of the ``tested combination''--the
equipment configuration that can be tested in the laboratory and
thereby provide a common basis for comparison--Sanyo, Fujitsu,
Mitsubishi, and ARI recommended deleting the requirement that the
selected indoor units ``represent the highest-sales-volume type
models'' and replacing it with ``represent the highest sales model
family.'' (Sanyo, No. 15 at p. 3; Fujitsu, No. 13 at p. 4; Mitsubishi,
No. 20 at pp. 5 and 6; ARI, No. 21 at p. 6) In addition, Sanyo,
Fujitsu, Mitsubishi, and ARI recommended that provisions be made in the
event that five of the largest model indoor coils from the selected
model family cannot provide a cumulative indoor capacity that is more
than 95 percent of the outdoor unit's nominal capacity. As to
references in the proposed definition that a manufacturer will know the
capacity of each indoor unit and each outdoor unit, Copeland
Corporation (Copeland) questioned how the manufacturer would determine
component capacities. (Public Hearing Tr., pp. 217-221) Finally, with
regard to the proposal that all of the tested indoor units ``have the
same external static pressure,'' Trane asked how to interpret that
requirement if testing a ducted multi-split system having indoor units
that have different minimum external static pressure requirements.
(Public Hearing Tr., p. 229)
DOE accepts the stakeholder recommendation of substituting the
phrase ``represent the highest sales model family'' for the originally
proposed wording, ``represent the highest sales volume type models,''
because it has essentially the same meaning, but is clearer. Although
it is more an issue with commercial multi-split systems, DOE accepts
the proposed wording to clarify the tested combination since it is more
important to obtain a cumulative indoor capacity that matches the
outdoor unit than it is to restrict selection to units from the highest
sales model family, for cases where both criteria cannot be met. As for
Copeland's statement that the definition includes references to the
capacity of the outdoor unit and the cumulative capacities of the
indoor units even though no prescriptions are given to evaluate these
capacities, DOE agrees but nonetheless will allow their use in this
particular definition. Manufacturers are able to estimate the rated
capacities of the separate components without conducting the rigorous
testing associated with ARI Standards 410 (``Forced-Circulation Air-
Cooling and Air-Heating Coils'') and 540 (``Performance Rating of
Positive Displacement Refrigerant Compressors and Compressor Units'')
on each new model. Finally, the last element of the proposed definition
of ``tested combination'' will be changed from ``all have the same
external static pressure'' to ``all be subject to the same minimum
external static pressure requirement (i.e., 0 inches of water column
for non-ducted, see Table 2 in Appendix M for ducted indoor units)
while being configurable to produce the same static pressure at the
exit of each outlet plenum when manifolded as per section 2.4.1 of
Appendix M.'' This additional information is provided so that the test
laboratory may conduct the lab testing by manifolding the outlets of
all the indoor units together and using one airflow measuring apparatus
to determine the cumulative air volume rate.
At the August 23, 2006, public meeting, DOE restated its proposed
interim solution for assigning SEER and HSPF ratings for untested
multi-split combinations. This interim solution--to assign the rating
measured for the tested combination to every other combination using
the same outdoor unit--was included as part of the March 24, 2006,
Federal Register notice that published a petition for waiver from the
residential package air conditioner and heat pump test procedures that
was received from Mitsubishi Electric and Electronics USA, Inc. (Case
No. CAC-012). 71 FR 14858. This provision was not in the July 2006
proposed rule, but was discussed at the public meeting and relevant
comments were received in the course of the waiver process. Lennox and
Copeland commented that the rated system's combination of indoor units
could be very different from those in the tested system, and the
ratings agreement would be poor in this case. (Public Hearing Tr., pp.
245-246)
Because of the difficulty of prescribing similarity of indoor unit
[[Page 59911]]
combinations, and with the belief that a rating that reflects the
``highest sales model family'' is better than no rating, DOE is
including this ratings provision in the final rule, with the additional
stipulation that multi-split manufacturers must test two or more
combinations with each outdoor unit unless they have an approved ARM
(in which case, they only need to test one combination). 10 CFR
430.24(m)(2). One system shall be tested using only non-ducted indoor
units that meet the definition of a tested combination. The second
system shall be tested using only ducted indoor units that meet the
definition of a tested combination. The rating given to any untested
multi-split system combination having the same outdoor unit and all
non-ducted indoor units shall be set equal to the rating of the tested
system having all non-ducted indoor units. The rating given to any
untested multi-split system combination having the same outdoor unit
and all ducted indoor units shall be set equal to the rating of the
tested system having all ducted indoor units. Finally, the rating given
to any untested multi-split system combination having the same outdoor
unit and a mix of non-ducted and ducted indoor units shall be set equal
to the average of the ratings for the two required tested combinations.
10 CFR 430.24(m)(2)(ii). Furthermore, DOE notes that it is including a
provision for the use of an alternate rating method. While DOE is not
aware of any algorithms appropriate for rating the energy efficiency of
untested multi-split system combinations, DOE expects that as more
laboratory test data and field use data become available, such
algorithms will be developed.
Today's final rule contains a minor update that was introduced in
the July 2006 proposed rule, removing the limit on having only one
indoor test room. No comments were received on this proposed change.
Today's final rule sufficiently addresses issues that led to the
requesting and granting of test procedure waivers for several models of
residential multi-split systems. Therefore, all existing waivers
concerning residential modulating multi-split systems terminate on the
effective date of today's final rule. Multi-split manufacturers may use
the waiver process described in 10 CFR 430.27 to petition for
modification of today's test procedure, if necessary.
C. Defining ``Repeatable'' for Cyclic Tests
The July 2006 proposed rule contained two provisions that further
defined repeatable performance during cyclic tests. One was the
requirement that the time-integrated air temperature difference across
the indoor unit for consecutive ``on'' cycles must change by 0.05
[deg]F hr or less while the other was for the average system power
consumption for the complete ``OFF/ON'' interval to change by 10 watts
or less from one cycle to the next.
ARI, Sanyo, Carrier, and Nordyne commented that repeatability
should be addressed by ASHRAE's Standards Project Committee (SPC) 116,
``Method of Testing for Rating Seasonal Efficiency of Unitary Air
Conditioners and Heat Pumps,'' not by the DOE test procedure (ARI, No.
21 at p. 3; Sanyo, No. 15 at p. 5; Carrier, No. 17 at p. 2; Nordyne,
No. 19 at p. 2) Finally, ACEEE supports DOE's efforts to capture the
essence of industry best practices for cyclic testing. (ACEEE, No. 16
at p. 4)
DOE recognizes that variability is inherent in testing products for
energy efficiency, including central air conditioners and central air
conditioning heat pumps. In order to reduce test variability and
increase repeatability of test results, DOE has set specific
requirements for test set-up and measurement to reduce variability.
However, even with these requirements, test variability remains.
Furthermore, DOE notes that the less repeatable the test, either more
units need to be tested to support an energy efficiency rating that is
representative of the units true energy efficiency or, if less testing
is done, the product must be rated conservatively (i.e., lower energy
efficiency rating).\4\ Test variability can be further reduced by, for
example, including more specific requirements in the DOE test
procedures as well as through industry actions, such as ASHRAE Standard
116. However, changes to the DOE test procedures to deal with test
variability could increase the burden and cost of testing. Since the
purpose of this requirement was to reduce variability and there are
alternative approaches manufacturers can take to reduce variability,
DOE is not adopting the cyclic changes proposed. Therefore, as part of
today's final rule, DOE makes no changes on defining repeatability
during cyclic tests.
---------------------------------------------------------------------------
\4\ SEER and HSPF values, per the sampling plan in 10 CFR
430.24, are to be based on the lower 90 percent confidence limit of
the true mean divided by 0.95 (as opposed to the sample mean), thus
the more variability in test results, the more likely that a
product's SEER and HSPF ratings will have to be reduced from the
true mean.
---------------------------------------------------------------------------
D. Outdoor Air Test Conditions for Units Having a Two-Capacity
Compressor
The July 2006 proposed rule included provisions that dealt with the
outdoor test conditions for three low-capacity cooling mode tests. The
three low-capacity tests are conducted at different outdoor dry bulb
temperatures (i.e., steady-state, wet-coil test at 95 [deg]F outdoor
dry bulb temperature (the A1 Test); the steady-state, dry-
coil test at 82 [deg]F (the C1 Test); and the cyclic, dry-
coil test at 82 [deg]F (the D1 Test)). The July 2006
proposal was to have all three of these tests replaced by equivalent
tests conducted at an outdoor dry bulb temperature of 67 [deg]F.
ARI, Carrier, and Nordyne supported replacing the A1
Test with the steady-state, wet-coil, F1 Test at 67 [deg]F
because the change will close a potential loophole in the current test
procedure. (ARI, No. 21 at p. 3; Carrier, No. 17 at p. 2; Nordyne, No.
19 at p. 2) This loophole allowed manufacturers a way to increase the
measured SEER by disproportionately increasing the electrical power
consumption during the A1 Test. ACEEE supported the change
in the temperature in the A1 test, but expressed its concern
that the change may downgrade the importance of high temperature
performance. (ACEEE, No. 16 at p. 4) ARI, Carrier, and Nordyne
commented that the change in the C1 and D1 tests
is unnecessary since these tests are optional and the changes will do
very little to improve the accuracy of SEER. (ARI, No. 21 at p. 3;
Carrier, No. 17 at p. 2; Nordyne, No. 19 at p. 2) Carrier also
expressed its concern that products designed and tested under the
current methodology may have to be re-rated as a result of the
proposal. (Carrier, No. 17 at p. 2) In terms of the test procedure,
Carrier is concerned that a different cyclic-degradation coefficient
(CD) may result from replacing the C1 and
D1 Tests with equivalent tests at 67[deg]F.
Collectively, the three proposed changes make the test conditions
for two-capacity units consistent with the test conditions specified
for variable-speed systems. Implementing all three changes would result
in a more normal test progression for most two-capacity units: all wet
coil tests followed by the dry coil test; start with high capacity
tests and end with the low capacity tests; and start at 95 [deg]F,
progress to 82 [deg]F, and then end with 67 [deg]F. These benefits,
however, cannot be realized because of the possibility of causing a
change in the SEER ratings of some two-capacity units. Thus, DOE agrees
with the general position of the comments that the proposal to change
the outdoor test conditions for the two optional dry-coil CD
tests (C1 and D1 tests) is not warranted.
[[Page 59912]]
Therefore, today's final rule replaces the A1 Test with
the F1 Test, as proposed. The F1 Test requires an
outdoor dry bulb temperature of 67 [deg]F, and for those few cases
where it applies, an outdoor wet bulb temperature of 53.5 [deg]F. The
amendments discussed above are found in sections 3.2.3 and 4.1.3 of
Appendix M.
E. Air Volume Rate Less Than Manufacturer's Specified Value
In the July 2006 proposed rule, and the October 10, 2006,
correction notice, DOE proposed modifications to the criteria for using
an air volume rate that is less than the manufacturer's specified
value. The proposal was made to account for the variability in fan
motors, housings, and wheels. In brief, the proposed set-up process for
the test procedure provides for making incremental adjustments in the
indoor fan speed until the indoor unit provides an external static
pressure that is equal to or greater than the applicable DOE minimum
(i.e., 0.1, 0.15, or 0.20 inch of water column, if a non-small-duct,
high-velocity (SDHV) system), while operating at the manufacturer-
specified air volume rate or, if needed, at the air volume rate between
95 percent and 100 percent that produces the corresponding DOE minimum
static pressure value. For comparison, the current algorithm in the DOE
test procedure does not allow the air volume rate to be reduced from
100 percent for the case where the external static pressure is less
than specified by the test procedure. The proposed criteria apply to
all ducted blower-coil systems, except those having a variable-speed
motor that is controlled based on maintaining a constant air volume
rate. The proposed criteria include two cases where the test laboratory
is instructed to operate at an air volume rate less than that specified
by the manufacturer: (1) If the highest indoor fan speed setting cannot
yield the DOE-specified external static pressure minimum while
supplying the manufacturer-specified air volume rate, and (2) if the
manufacturer's specified air volume rate yields a ratio higher than
37.5 standard cubic feet per minute (scfm) per 1000 Btu/h.
Nordyne, Carrier and Rheem supported the proposed criteria for
using an air volume rate that is less than the manufacturer's specified
value. (Nordyne, No. 19 at p. 2; Carrier, No. 17 at p. 3; Public
Hearing Tr., p. 135; and Public Hearing Tr., pp. 134-135) ACEEE
commented that since the proposed language specified which product
designs would be subject to this requirement, they recommended that the
wording for the types of indoor blowers that are affected by this
change be as generic as possible so as not to impede product
innovation. (Public Hearing Tr., pp. 132-133)
DOE agrees with ACEEE that the proposed language could limit
innovation since the proposed amendment was intended to apply to
designs that are not adequately addressed by the current air volume
requirements. Since it is impossible to predict what product designs
may enter the marketplace, specifying the designs subject to the new
provisions may, in fact, limit innovation. Therefore, in response to
ACEEE's comment, DOE restructured the air volume criteria to indicate
that the change applies to all designs, except variable-speed,
constant-air-volume-rate blowers. In this way, the variable-speed,
constant-volume-rate blowers, which the existing test procedure
adequately addresses, continue to be subject to the existing
requirement.
F. Updating References to Industry Standards
The July 2006 proposed rule included updates to references to
current industry test standards, including ASHRAE Standard 23-2005,
``Methods of Testing for Rating Positive Displacement Refrigerant
Compressors and Condensing Units,'' ASHRAE Standard 37-2005, ``Methods
of Testing for Rating Electrically Driven Unitary Air-Conditioning and
Heat Pump Equipment,'' and ASHRAE Standard 116-1995 (RA2005), ``Methods
of Testing for Rating Seasonal Efficiency of Unitary Air Conditioners
and Heat Pumps.'' Nordyne commented in support of this proposal.
(Nordyne, No. 19 at p. 2)
In addition, subsequent to the publication of the July 2006
proposed rule, ARI released an updated version of ARI Standard 210/240,
``Performance Rating of Unitary Air-Conditioning and Air-Source Heat
Pump Equipment.'' The updated version of ARI Standard 210/240 included
references to the DOE test procedure as amended by the final rule
published on October 11, 2005. This latest version of ARI Standard 210/
240 had not been released at the time that the content of the July 2006
proposed rule had been finalized. Since the updated test procedures do
not affect the measure of efficiency and provide manufacturers with
current test standards, DOE moves today to adopt the 2006 version of
ARI Standard 210/240.
G. Maximum and Minimum Speed Values for Calculating NQ and
NE
Rheem inquired as to whether the minimum and maximum speed
quantities needed to evaluate Appendix M equations 4.1.3-1 and 4.1.3-3
are to be determined directly from additional lab testing or from
interpolating data from required tests lab tests at 67 [deg]F, 82
[deg]F, and 95 [deg]F. (NIST, No. 24 at p. 2) In response, for cooling
performance, DOE modified section 4.1.4 to explicitly state that the
capacities and Qck=1 (87) and
Qck=2 (87), which are used as part of the
algorithm for approximating the slope of the intermediate compressor
speed (k=v) capacity curve, are determined by evaluating equations
4.1.3-1 and 4.1.3-3, respectively, for Tj = 87. Similar
direction is provided for determining the power consumption quantities
Eck=1 (87) and Eck=2 (87)
that appear within the section 4.1.4 equation for NE. For
heating performance, such direction already exists within the section
on calculating the HSPF for a variable-speed heat pump, with regard to
the source of the minimum speed quantities at 35 [deg]F.
This change does not affect the calculated SEER. The revised text
is found following the equation for NE in section 4.1.4 of
Appendix M.
H. Using the Default or Tested Value of Cyclic-Degradation Coefficient
Carrier asked if the manufacturer elects to run the optional tests,
and the resulting CD exceeds the 0.25 default value, is the
manufacturer obligated to use the tested value. (Public Hearing Tr., p.
31) The current test procedure addresses this scenario for most cases
where a CD is used in the SEER and HSPF calculations.
Specifically, sections 4.1.1, 4.1.2.1, 4.1.3.1, 4.1.4.1, 4.2.1, and
4.2.3.1, direct that if the optional test(s) are not conducted, the
cooling (heating) cyclic-degradation coefficient,
CDc (CDh), is to be set to
the default value of 0.25. If the optional test(s) are conducted,
CDc (CDh) must to be set to
the lower of: the value calculated per the test or the default value of
0.25. In response to Carrier's comment, DOE has added similar wording
to sections 4.1.3.3 and 4.2.3.3, the only sections that did not include
the clarifying language found in the sections referenced above.
Furthermore, in reviewing the organization of the current test
procedure while considering this update, DOE found that the information
would be better placed in the earlier sections (within section 3) with
the instructions as to which tests to conduct based on the type of
equipment (i.e.,
[[Page 59913]]
single-speed, two-capacity, variable-speed, etc). Therefore, language
has been added in the test procedure to clarify that if the tested
cyclic-degradation coefficient is higher than the default value, the
default value is to be used to calculate SEER and HSPF. (see sections
3.2.1, 3.2.2.1, 3.2.3, 3.2.4, 3.5.3, 3.6.1, 3.6.2, 3.6.3, 3.6.4, 3.8.1,
4.1.3.3, and 4.2.3.3).
I. Guidance on the Inclusion of Pre-Production Units in the Sample
Population
As part of the July 2006 proposed rule, DOE proposed that only pre-
production units fabricated using the same tooling used for the
eventual full-production units could be used as part of the tested
sample population to obtain the certified ratings of full-production
units.
ARI, Nordyne, and Carrier commented that the proposed wording is
too narrow, and recommended that the current regulatory language not be
changed. (ARI, No. 21 at p. 4; Nordyne, No. 19 at p. 3; Carrier, No. 17
at p. 2) ARI and Trane explained that the tooling used for pre-
production units is often different than that used for production
units. (Public Hearing Tr., pp. 192-193) Trane stated that pre-
production units must have the same configuration as the production
unit to be included in the sample population, while Carrier suggested
using wording such as that in the ARI Certification Program Operational
Manual to define the configuration (e.g., same compressor, same air
flow, etc.). (Public Hearing Tr., pp. 192, 198-199) Rheem commented
that the ARI internal process handles ratings derived from pre-
production units by making the model subject to certification testing
immediately after production starts. (Public Hearing Tr., p. 202)
DOE agrees that the proposed criterion is too narrow, and that
different tooling can yield equivalent machinery. Moreover, DOE
believes that spot checks conducted under an industry certification
program, such as the ARI Certification Program, provide a safeguard
against the performance of the production unit deviating appreciably
from ratings derived from testing pre-production units. For these
reasons, DOE is not amending the existing requirements and will
continue to allow manufacturers to test pre-production units.
J. Clarification of the Sample Population Used To Validate the Rated
Seasonal Energy Efficiency Ratio and Heating Seasonal Performance
Factor of Heat Pumps
DOE proposed that a manufacturer must include the cooling and
heating results from each heat pump of the sample population when
obtaining the certified SEER and HSPF ratings. This requirement
disallows testing multiple heat pumps and then using a subset of
results for assigning the certified SEER rating and a different subset
of results for determining the certified HSPF rating. The proposal
provided one exception, which would allow additional testing in just
one mode, cooling or heating, if the manufacturer elected to
discontinue testing in the other mode at some point in the sample
sequence.
ACEEE, Nordyne, and Carrier supported the intent of clarifying the
sample population used for determining heat pump ratings. (ACEEE, No.
16 at p. 5; Nordyne, No. 19 at p. 3; Carrier, No. 17 at p. 2) Carrier
and the ACEEE, however, recommended deleting the exception, noting that
additional testing is insignificant as compared to the potential for
misrepresented ratings. (Carrier, No. 17 at p. 2; ACEEE, No. 16 at p.
5)
DOE is aware of the testing burden on manufacturers, but agrees
with Carrier and the ACEEE that this particular attempt at marginally
reducing the test burden is not worthwhile. Thus, today's final rule
adopts the proposal that all units of the sample population must be
tested in both the cooling and heating modes and the results used for
determining the heat pump's certified SEER and HSPF ratings without
adopting the proposed exception for additional testing.
K. Clarification of the Definition of a ``Highest-Sales-Volume
Combination''
DOE proposed amendments to the definition of the Highest-Sales-
Volume Combination (HSVC) to require that a single-speed, split-system
air conditioner must include the coil-only indoor unit likely to have
the largest volume of retail sales with the particular model of outdoor
unit. Proposed 10 CFR 430.24(m)(2). In addition, DOE proposed
exceptions to this requirement to provide for equipment designed
exclusively for blower-coil installations: mini-splits; multi-splits;
small-duct, high-velocity systems; through-the-wall units; and
condensing units having features (e.g., proprietary interfaces) that
prevent their installation with third-party, coil-only indoor units.
This proposal was made in recognition that coil-only units represent
the overwhelming majority of installations of central air conditioners
and, as such, the highest-sales-volume should reflect standard
practice. The proposal also minimizes instances where the highest-sales
volume combination of a split-system air conditioner could be defined
as one with a ``blower-coil'' in order to meet Federal minimum energy
efficiency standards and then have the outdoor unit combined with coil-
only indoor units where the combination would not meet the Federal
energy efficiency standards.
ACEEE, Carrier and ARI agreed that some clarification to the test
procedure was needed in order to avoid such situations. (ACEEE, No. 16
at p. 5; ARI, No. 21 at p. 4; Public Hearing Tr., pp. 208-209) ACEEE
supported the goal of not having outdoor units installed with coil-only
indoor units where the combination does not meet the energy efficiency
standard. (ACEEE, No. 16 at p. 5) Instead of the proposed text, ARI and
Carrier recommended that DOE adopt the wording from the 2006 ARI
Certification Program Operational Manual for Unitary Air Conditioners &
Air-Source Unitary Heat Pumps (Rated Below 65,000 Btu/h Cooling). (ARI,
No. 21 at p. 4; Public Hearing Tr., pp. 208-209) Carrier and ARI
commented that the proposed exception for outdoor units that prevent
installations with coil-only units with a proprietary interface should
be eliminated because it is not enforceable. Nordyne strongly objected
to the entire proposal, stating that it restricts a manufacturer's use
of technology. (Nordyne, No. 19 at pp. 3-4) Moreover, to implement such
a change, Nordyne asserted that DOE needs to analyze the impact of
minimally compliant units. Nordyne, however, did note its support for
the proposed exception for blower coils having a proprietary interface.
ARI and Carrier recommended the following alternative text to the
July 2006 proposed rule:
HSVTC, Highest-sales-volume Tested Combination. For Unitary Air-
Conditioners below 14 SEER, the HSVTC must be an RCU-A-C
combination, except for through-the-wall and ductless equipment
(RCU-A-CBO). For Unitary Air-Conditioners 14 SEER and above, every
outdoor model number must have a coil-only rating. Coil-only ratings
offered for sale must be publicly viewable. Coil-only ratings not
offered for sale are viewable only to ARI staff. Non-viewable
ratings fall under all compliance guidelines except the challenge
procedure. If a non-publicly viewable rating falls below NAECA
minimum, then the manufacturer must submit a coil-only rating that
meets NAECA minimum and is verified through ARI testing.
[[Page 59914]]
Until then, the Basic Model Group ratings will not be listed in the
ARI directory.
Historically, the highest sales volume combination for most split-
system air conditioners has had a coil-only indoor unit. Both the June
2006 proposed rule and the ARI alternative maintain this historical
practice. DOE, however, believes ARI's approach is arbitrary and
results in uncertainties to manufacturers. Furthermore, DOE believes it
would be difficult to implement the above ARI algorithm. With the ARI
approach, the manufacturer may have to re-test in a coil-only
configuration after having tested in a blower-coil configuration, if
the expected SEER of 14 or higher is not realized in laboratory
testing. In addition, if DOE were to adopt the ARI alternative and the
minimum energy efficiency standards were amended, DOE would have to
modify the requirement, since the new minimum could be higher than the
14 SEER requirement in the ARI alternative. Conversely, in formulating
the approach proposed in the July 2006 proposed rulemaking, DOE first
considered requiring that all split-system air conditioners be tested
with a coil-only indoor unit. DOE recognized, however, that in addition
to the exceptions such as equipment designed exclusively for blower-
coil installations, other exceptions would have to be recognized. These
other exceptions include two-capacity and variable-speed units, because
they are always much more efficient than 14 SEER, and do not risk
having a coil-only combination that would not meet the DOE efficiency
standards. Therefore, DOE applied the coil-only requirement only to
split system air conditioners having a single-speed compressor.
Returning to the issue of listed exceptions, DOE agrees with ARI
and Carrier that the proposed exception for combinations that prevent
applications with third-party coil-only indoor units would be
prohibitively difficult to define, verify, and enforce. DOE believes
that its proposal to substitute the words ``mini-splits'' and ``multi-
splits'' for ``ductless equipment,'' is somewhat more comprehensive
because it includes ducted multi-split systems. Finally, SDHV
manufacturers, at present, only manufacture indoor coils and do not
manufacture outdoor units. Since SDHV manufacturers do not offer for
sale complete systems, they are not subject to specifying HSVC's. Thus,
SDHV systems do not need to be included as an exception.
As to Nordyne's objections, DOE stands by its position as stated in
the July 2006 proposed rule. DOE believes that its proposal, which is
adopted in today's final rule, increases the likelihood tha