DEPARTMENT OF ENERGY
Office of Energy Efficiency and
Renewable Energy
10 CFR Part 430
[Docket No. EE–RM/TP–02–002]
RIN 1904–AB55
Energy Conservation Program for
Consumer Products: Test Procedure
for Residential Central Air
Conditioners and Heat Pumps;
Correction
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Proposed Rule; technical
correction and reopening of comment
period.
AGENCY:
SUMMARY: A notice of proposed
rulemaking (NOPR), to amend the
Department of Energy (DOE) test
procedures for residential central air
conditioners and heat pumps, was
published in the Federal Register on
July 20, 2006. The Department has
identified two errors in that proposed
rulemaking and this notice corrects
those errors and reopens the comment
period.
DOE will accept comments until
November 9, 2006.
FOR FURTHER INFORMATION CONTACT:
Michael Raymond, Project Manager,
Test Procedures for Residential Central
Air Conditioners and Heat Pumps,
Docket No. EE–RM/TP–02–002, U.S.
Department of Energy, Office of Energy
Efficiency and Renewable Energy,
Building Technologies Program, EE–2J,
1000 Independence Avenue, SW.,
Washington, DC 20585–0121,
Telephone Number: (202) 586–9611, email: Michael.Raymond@ee.doe.gov;
Francine Pinto, Esq., U.S. Department
of Energy, Office of the General Counsel,
GC–72, 1000 Independence Avenue,
SW., Washington, DC 20585–0121, (202)
586–9507, e-mail:
Francine.Pinto@hq.doe.gov
jlentini on PROD1PC65 with PROPOSAL
DATES:
VerDate Aug<31>2005
16:33 Oct 06, 2006
Jkt 211001
SUPPLEMENTARY INFORMATION:
Background
A notice of proposed rulemaking
(NOPR), to amend the DOE test
procedures for residential central air
conditioners and heat pumps, was
published in the Federal Register on
July 20, 2006. (71 FR 41320) DOE has
become aware that two corrections need
to be made:
(1) An amendment to section 3.1.4.1.1
of the regulatory language of the test
procedure, which was omitted in the
NOPR. The NOPR amendments to
section 3.1.4.1.1 of the test procedure in
Appendix M include only a change to
the title and to Table 2. In addition, the
introductory text and paragraph (a) of
section 3.1.4.1.1 are revised, as set forth
below; and
(2) An amendment to section 3.1.4.4.3
of the regulatory language of the test
procedure, which was omitted in the
NOPR. Discussion of these changes was
included in the preamble to the July 20,
2006, NOPR.
The comment period originally was
scheduled to end on September 18,
2006. The Department will accept
comments for 30 days following
publication of this notice. The extension
was announced at the August 23, 2006,
public meeting.
Corrections: In FR Doc. 06–6320
appearing on page 41319 in the Federal
Register dated July 20, 2006, the
following corrections are made:
1. On page 41338, first column, in
Part 430, Energy Conservation Program
for Consumer Products, Appendix M,
amendatory instruction 5.c.2 is
corrected to read as follows:
‘‘Section 3.1.4.1.1 title, introductory
text, paragraph (a) and Table 2 to
paragraph (c) is revised to read as set
forth below.’’
2. On page 41338, first column, in
Part 430, Energy Conservation Program
for Consumer Products, Appendix M, a
new amendatory instruction 5.c.3 is
added and the remaining amendatory
instructions for 5.c are renumbered
accordingly. The new instruction reads
as follows:
‘‘Section 3.1.4.4.3 is revised to read as
set forth below.’’
The revisions and additions read as
follows:
Appendix M [Corrected]
3. Testing Procedures
*
PO 00000
*
*
Frm 00001
*
Fmt 4702
*
Sfmt 4702
3.1.4.1.1 Cooling Full-Load Air
Volume Rate for Ducted Units.
The manufacturer must specify the
Cooling Full-load Air Volume Rate. Use
this value as long as the following two
requirements are satisfied. First, when
conducting the A or A2 Test
(exclusively), the measured air volume
rate, when divided by the measured
indoor air-side total cooling capacity
must not exceed 37.5 cubic feet per
minute of standard air (scfm) per 1000
Btu/h. If this ratio is exceeded, reduce
the air volume rate until this ratio is
equaled. Use this reduced air volume
rate for all tests that call for using the
Cooling Full-load Air Volume Rate. The
second requirement is as follows:
a. For ducted units that are tested
with a fixed-speed, multi-speed, or
variable-speed variable-air-volume-rate
indoor fan installed. The second
requirement applies exclusively to the A
or A2 Test and is met as follows.
1. Achieve the Cooling Full-load Air
Volume Rate, determined in accordance
with the previous paragraph;
2. Measure the external static
pressure;
3. If this pressure is equal to or greater
than the applicable minimum external
static pressure cited in Table 2, the
second requirement is satisfied. Use the
current air volume rate for all tests that
require the Cooling Full-load Air
Volume Rate.
4. If the Table 2 minimum is not
equaled or exceeded,
4a. Reduce the air volume rate until
the applicable Table 2 minimum is
equaled or
4b. Until the measured air volume
rate equals 95 percent of the air volume
rate from step #1, whichever occurs
first.
5. If the conditions of step #4a occur
first, the second requirement is satisfied.
Use the step #4a reduced air volume
rate for all tests that require the Cooling
Full-load Air Volume Rate.
6. If the conditions of step #4b occur
first, make an incremental change to the
set-up of the indoor fan (e.g., next
highest fan motor pin setting, next
highest fan motor speed) and repeat the
evaluation process beginning at above
step #1. If the indoor fan set-up cannot
be further changed, reduce the air
volume rate until the applicable Table 2
minimum is equaled. Use the reduced
air volume rate for all tests that require
the Cooling Full-load Air Volume Rate.
*
*
*
*
*
E:\FR\FM\10OCP1.SGM
10OCP1
jlentini on PROD1PC65 with PROPOSAL
Federal Register / Vol. 71, No. 195 / Tuesday, October 10, 2006 / Proposed Rules
c. * * *
Table 2. * * *
*
*
*
*
*
3.1.4.4.3 Ducted heating-only heat
pumps. The manufacturer must specify
the Heating Full-load Air Volume Rate.
Use this value when the following two
requirements are satisfied. First, when
conducting the H1 and H12 Test
(exclusively), the measured air volume
rate, when divided by the measured
indoor air-side total heating capacity,
must not exceed 37.5 cubic feet per
minute of standard air (scfm) per 1000
Btu/h. If this ratio is exceeded, reduce
the air volume rate until this ratio is
equaled. Use this reduced air volume
rate for all tests of heating-only heat
pumps that call for the Heating Fullload Air Volume Rate. The second
requirement is as follows:
a. For heating-only heat pumps that
are tested with a fixed-speed, multispeed, or variable-speed variable-airvolume-rate indoor fan installed. The
second requirement applies exclusively
to the H1 or H12 Test and is met as
follows.
1. Achieve the Heating Full-load Air
Volume Rate, determined in accordance
with the paragraph a. of this section;
2. Measure the external static
pressure;
3. If this pressure is equal to or greater
than the Table 2 minimum external
static pressure that applies given the
heating-only heat pump’s rated heating
capacity, the second requirement is
satisfied. Use the current air volume rate
for all tests that require the Heating
Full-load Air Volume Rate.
4. If the Table 2 minimum is not
equaled or exceeded,
4a. Reduce the air volume rate until
the applicable Table 2 minimum is
equaled or
4b. Until the measured air volume
rate equals 95 percent of the air volume
rate from step #1, whichever occurs
first.
5. If the conditions of step #4a occurs
first, the second requirement is satisfied.
Use the step #4a reduced air volume
rate for all tests that require the Heating
Full-load Air Volume Rate.
6. If the conditions of step #4b occur
first, make an incremental change to the
set-up of the indoor fan (e.g., next
highest fan motor pin setting, next
highest fan motor speed) and repeat the
evaluation process beginning at above
step #1. If the indoor fan set-up cannot
be further changed, reduce the air
volume rate until the applicable Table 2
minimum is equaled. Use the reduced
VerDate Aug<31>2005
17:50 Oct 06, 2006
Jkt 211001
air volume rate for all tests that require
the Heating Full-load Air Volume Rate.
*
*
*
*
*
Issued in Washington, DC, on September
29, 2006.
Alexander A. Karsner,
Assistant Secretary, Energy Efficiency and
Renewable Energy.
[FR Doc. E6–16648 Filed 10–6–06; 8:45 am]
BILLING CODE 6450–01–P
59411
Lender Oversight, Small Business
Administration, 409 3rd Street, SW., 8th
floor, Washington, DC 20416.
FOR FURTHER INFORMATION CONTACT: John
M. White, Deputy Associate
Administrator, Office of Lender
Oversight at (202) 205–3049,
john.white@sba.gov; or Paul Bishop,
Financial Analyst, Office of Lender
Oversight, (202) 205–7516;
paul.bishop@sba.gov.
(Authority: 15 U.S.C. 363)
SMALL BUSINESS ADMINISTRATION
13 CFR Part 120
RIN 3245–AF49
Business Loan Program; Lender
Examination and Review Fees
U.S. Small Business
Administration (SBA).
ACTION: Proposed rule, notice of
reopening of comment period and
correction.
Dated: October 4, 2006.
Michael W. Hager,
Associate Deputy Administrator for the Office
of Capital Access.
[FR Doc. E6–16750 Filed 10–6–06; 8:45 am]
BILLING CODE 8025–01–P
AGENCY:
On September 5, 2006, SBA
published in the Federal Register a
proposed rule on Business Loan
Program; Lender Examination and
Review Fees (71 FR 52296). This
proposed rule implements a recent
amendment to the Small Business Act
authorizing SBA to assess fees to
lenders participating in SBA’s 7(a) loan
guarantee program to cover the costs of
examinations, reviews, and other
Lender Oversight activities. The original
comment period was from September 5,
2006, through October 5, 2006. SBA is
reopening the comment period until
November 9, 2006. Given the significant
level of interest the proposed rule has
generated, SBA believes the affected
parties would find it beneficial to have
more time to review the proposal and
prepare their comments.
In addition SBA is correcting the
Addresses section of the proposed rule
by eliminating the Agency Web Site
address and amending the E-mail
address to Proposedfeerule@sba.gov.
DATES: Comments on the proposed rule
on Business Loan Program, Lender
Examination and Review Fees, 71 FR
52296, must be received on or before
November 9, 2006.
ADDRESSES: You may submit comments,
identified by RIN number 3245-AF49,
by any of the following methods:
• Federal eRulemaking Portal: https://
www.regulations.gov. Follow the
instructions for submitting comments.
• E-mail: Proposedfeerule@sba.gov.
• Fax: (202) 205–6831.
• Mail/ Hand Delivery/Courier: Bryan
Hooper, Associate Administrator for
SUMMARY:
PO 00000
Frm 00002
Fmt 4702
Sfmt 4702
DEPARTMENT OF DEFENSE
Office of the Secretary
32 CFR Part 144
[DOD–2006–OS–0204]
RIN 0790–AI07
Service by Members of the Armed
Forces on State and Local Juries
Department of Defense.
Proposed rule.
AGENCY:
ACTION:
SUMMARY: This part implements 10
U.S.C 982 to establish uniform DoD
policies for jury service by members of
the Armed Forces on active duty. The
provisions of this part impact activeduty members of the Armed Forces.
This updated rule contains editorial
changes only as required for internal
Department of Defense mandated
reconsideration every 5 years.
DATES: Comments must be received by
December 11, 2006.
ADDRESSES: You may submit comments,
identified by docket number and or RIN
number and title, by any of the
following methods:
• Federal eRulemaking Portal: https://
www.regulations.gov. Follow the
instructions for submitting comments.
• Mail: Federal Docket Management
System Office, 1160 Defense Pentagon,
Washington, DC 20301–1160.
Instructions: All submissions received
must include the agency name and
docket number or Regulatory
Information Number (RIN) for this
Federal Register document. The general
policy for comments and other
submissions from members of the public
E:\FR\FM\10OCP1.SGM
10OCP1
Agencies
[Federal Register Volume 71, Number 195 (Tuesday, October 10, 2006)]
[Proposed Rules]
[Pages 59410-59411]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: E6-16648]
========================================================================
Proposed Rules
Federal Register
________________________________________________________________________
This section of the FEDERAL REGISTER contains notices to the public of
the proposed issuance of rules and regulations. The purpose of these
notices is to give interested persons an opportunity to participate in
the rule making prior to the adoption of the final rules.
========================================================================
Federal Register / Vol. 71, No. 195 / Tuesday, October 10, 2006 /
Proposed Rules
[[Page 59410]]
DEPARTMENT OF ENERGY
Office of Energy Efficiency and Renewable Energy
10 CFR Part 430
[Docket No. EE-RM/TP-02-002]
RIN 1904-AB55
Energy Conservation Program for Consumer Products: Test Procedure
for Residential Central Air Conditioners and Heat Pumps; Correction
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Proposed Rule; technical correction and reopening of comment
period.
-----------------------------------------------------------------------
SUMMARY: A notice of proposed rulemaking (NOPR), to amend the
Department of Energy (DOE) test procedures for residential central air
conditioners and heat pumps, was published in the Federal Register on
July 20, 2006. The Department has identified two errors in that
proposed rulemaking and this notice corrects those errors and reopens
the comment period.
DATES: DOE will accept comments until November 9, 2006.
FOR FURTHER INFORMATION CONTACT: Michael Raymond, Project Manager, Test
Procedures for Residential Central Air Conditioners and Heat Pumps,
Docket No. EE-RM/TP-02-002, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Program, EE-2J,
1000 Independence Avenue, SW., Washington, DC 20585-0121, Telephone
Number: (202) 586-9611, e-mail: Michael.Raymond@ee.doe.gov;
Francine Pinto, Esq., U.S. Department of Energy, Office of the
General Counsel, GC-72, 1000 Independence Avenue, SW., Washington, DC
20585-0121, (202) 586-9507, e-mail: Francine.Pinto@hq.doe.gov
SUPPLEMENTARY INFORMATION:
Background
A notice of proposed rulemaking (NOPR), to amend the DOE test
procedures for residential central air conditioners and heat pumps, was
published in the Federal Register on July 20, 2006. (71 FR 41320) DOE
has become aware that two corrections need to be made:
(1) An amendment to section 3.1.4.1.1 of the regulatory language of
the test procedure, which was omitted in the NOPR. The NOPR amendments
to section 3.1.4.1.1 of the test procedure in Appendix M include only a
change to the title and to Table 2. In addition, the introductory text
and paragraph (a) of section 3.1.4.1.1 are revised, as set forth below;
and
(2) An amendment to section 3.1.4.4.3 of the regulatory language of
the test procedure, which was omitted in the NOPR. Discussion of these
changes was included in the preamble to the July 20, 2006, NOPR.
The comment period originally was scheduled to end on September 18,
2006. The Department will accept comments for 30 days following
publication of this notice. The extension was announced at the August
23, 2006, public meeting.
Corrections: In FR Doc. 06-6320 appearing on page 41319 in the
Federal Register dated July 20, 2006, the following corrections are
made:
1. On page 41338, first column, in Part 430, Energy Conservation
Program for Consumer Products, Appendix M, amendatory instruction 5.c.2
is corrected to read as follows:
``Section 3.1.4.1.1 title, introductory text, paragraph (a) and
Table 2 to paragraph (c) is revised to read as set forth below.''
2. On page 41338, first column, in Part 430, Energy Conservation
Program for Consumer Products, Appendix M, a new amendatory instruction
5.c.3 is added and the remaining amendatory instructions for 5.c are
renumbered accordingly. The new instruction reads as follows:
``Section 3.1.4.4.3 is revised to read as set forth below.''
The revisions and additions read as follows:
Appendix M [Corrected]
3. Testing Procedures
* * * * *
3.1.4.1.1 Cooling Full-Load Air Volume Rate for Ducted Units.
The manufacturer must specify the Cooling Full-load Air Volume
Rate. Use this value as long as the following two requirements are
satisfied. First, when conducting the A or A2 Test
(exclusively), the measured air volume rate, when divided by the
measured indoor air-side total cooling capacity must not exceed 37.5
cubic feet per minute of standard air (scfm) per 1000 Btu/h. If this
ratio is exceeded, reduce the air volume rate until this ratio is
equaled. Use this reduced air volume rate for all tests that call for
using the Cooling Full-load Air Volume Rate. The second requirement is
as follows:
a. For ducted units that are tested with a fixed-speed, multi-
speed, or variable-speed variable-air-volume-rate indoor fan installed.
The second requirement applies exclusively to the A or A2
Test and is met as follows.
1. Achieve the Cooling Full-load Air Volume Rate, determined in
accordance with the previous paragraph;
2. Measure the external static pressure;
3. If this pressure is equal to or greater than the applicable
minimum external static pressure cited in Table 2, the second
requirement is satisfied. Use the current air volume rate for all tests
that require the Cooling Full-load Air Volume Rate.
4. If the Table 2 minimum is not equaled or exceeded,
4a. Reduce the air volume rate until the applicable Table 2 minimum
is equaled or
4b. Until the measured air volume rate equals 95 percent of the air
volume rate from step 1, whichever occurs first.
5. If the conditions of step 4a occur first, the second
requirement is satisfied. Use the step 4a reduced air volume
rate for all tests that require the Cooling Full-load Air Volume Rate.
6. If the conditions of step 4b occur first, make an
incremental change to the set-up of the indoor fan (e.g., next highest
fan motor pin setting, next highest fan motor speed) and repeat the
evaluation process beginning at above step 1. If the indoor
fan set-up cannot be further changed, reduce the air volume rate until
the applicable Table 2 minimum is equaled. Use the reduced air volume
rate for all tests that require the Cooling Full-load Air Volume Rate.
* * * * *
[[Page 59411]]
c. * * *
Table 2. * * *
* * * * *
3.1.4.4.3 Ducted heating-only heat pumps. The manufacturer must
specify the Heating Full-load Air Volume Rate. Use this value when the
following two requirements are satisfied. First, when conducting the H1
and H12 Test (exclusively), the measured air volume rate,
when divided by the measured indoor air-side total heating capacity,
must not exceed 37.5 cubic feet per minute of standard air (scfm) per
1000 Btu/h. If this ratio is exceeded, reduce the air volume rate until
this ratio is equaled. Use this reduced air volume rate for all tests
of heating-only heat pumps that call for the Heating Full-load Air
Volume Rate. The second requirement is as follows:
a. For heating-only heat pumps that are tested with a fixed-speed,
multi-speed, or variable-speed variable-air-volume-rate indoor fan
installed. The second requirement applies exclusively to the H1 or
H12 Test and is met as follows.
1. Achieve the Heating Full-load Air Volume Rate, determined in
accordance with the paragraph a. of this section;
2. Measure the external static pressure;
3. If this pressure is equal to or greater than the Table 2 minimum
external static pressure that applies given the heating-only heat
pump's rated heating capacity, the second requirement is satisfied. Use
the current air volume rate for all tests that require the Heating
Full-load Air Volume Rate.
4. If the Table 2 minimum is not equaled or exceeded,
4a. Reduce the air volume rate until the applicable Table 2 minimum
is equaled or
4b. Until the measured air volume rate equals 95 percent of the air
volume rate from step 1, whichever occurs first.
5. If the conditions of step 4a occurs first, the second
requirement is satisfied. Use the step 4a reduced air volume
rate for all tests that require the Heating Full-load Air Volume Rate.
6. If the conditions of step 4b occur first, make an
incremental change to the set-up of the indoor fan (e.g., next highest
fan motor pin setting, next highest fan motor speed) and repeat the
evaluation process beginning at above step 1. If the indoor
fan set-up cannot be further changed, reduce the air volume rate until
the applicable Table 2 minimum is equaled. Use the reduced air volume
rate for all tests that require the Heating Full-load Air Volume Rate.
* * * * *
Issued in Washington, DC, on September 29, 2006.
Alexander A. Karsner,
Assistant Secretary, Energy Efficiency and Renewable Energy.
[FR Doc. E6-16648 Filed 10-6-06; 8:45 am]
BILLING CODE 6450-01-P