Interconnection for Wind Energy, 75005-75016 [05-24173]
Download as PDF
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
FOR FURTHER INFORMATION CONTACT:
FOR FURTHER INFORMATION CONTACT:
Jeffrey Lee, Aerospace Engineer, Boston
Aircraft Certification Office, FAA,
Engine and Propeller Directorate, 12
New England Executive Park,
Burlington, MA 01803–5299; telephone:
781–238–7161; fax: 781–238–7170.
SUPPLEMENTARY INFORMATION: A final
rule AD, FR Doc. 05–19941, that applies
to Aviointeriors S.p.A. (formerly
ALVEN), series 312 box mounted seats,
was published in the Federal Register
on October 12, 2005 (70 FR 59243). The
following correction is needed:
Bruce A. Poole (Technical Information),
Office of Markets, Tariffs and Rates,
Federal Energy Regulatory
Commission, 888 First Street, NE.,
Washington, DC 20426. (202) 502–
8468.
G. Patrick Rooney (Technical
Information), Office of Markets,
Tariffs and Rates, Federal Energy
Regulatory Commission, 888 First
Street, NE., Washington, DC 20426.
(202) 502–6205.
P. Kumar Agarwal (Technical
Information), Office of Markets,
Tariffs and Rates, Federal Energy
Regulatory Commission, 888 First
Street, NE., Washington, DC 20426.
(202) 502–8923.
LaChelle Brooks (Technical
Information), Office of Markets,
Tariffs and Rates, Federal Energy
Regulatory Commission, 888 First
Street, NE., Washington, DC 20426.
(202) 502–6522.
Jeffery S. Dennis (Legal Information),
Office of the General Counsel, Federal
Energy Regulatory Commission, 888
First Street, NE., Washington, DC
20426. (202) 502–6027.
SUPPLEMENTARY INFORMATION:
§ 39.13
[Corrected]
On page 59243, in the third column,
under § 39.13 [Amended], paragraph 2.,
fourth line, ‘‘2005–20–06’’ is corrected
to read ‘‘2005–20–26’’.
I
Issued in Burlington, MA, on December 13,
2005.
Peter A. White,
Acting Manager, Engine and Propeller
Directorate, Aircraft Certification Service.
[FR Doc. 05–24194 Filed 12–16–05; 8:45 am]
BILLING CODE 4910–13–P
DEPARTMENT OF ENERGY
Order No. 661–A; Order on Rehearing
and Clarification
1. On June 2, 2005, the Commission
issued Order No. 661, the Final Rule on
Interconnection for Wind Energy (Final
Rule).1 Several entities have filed timely
requests for rehearing and clarification
of the Final Rule.2 In this order, the
Commission grants in part and denies in
part the requests for rehearing and
clarification.
Federal Energy Regulatory
Commission
18 CFR Part 35
[Docket No. RM05–4–001; Order No. 661–
A]
Interconnection for Wind Energy
Issued December 12, 2005.
Federal Energy Regulatory
Commission, DOE.
ACTION: Order on rehearing and
clarification.
AGENCY:
SUMMARY: The Federal Energy
Regulatory Commission is granting in
part and denying in part the requests for
rehearing and clarification of its Final
Rule on Interconnection for Wind
Energy, Order No. 661. Order No. 661
requires public utilities that own,
control, or operate facilities for
transmitting electric energy in interstate
commerce to append to their standard
large generator interconnection
procedures and large generator
interconnection agreements in their
open access transmission tariffs
standard procedures and technical
requirements for the interconnection of
large wind generation.
DATES: Effective Date: Changes made to
Order No. 661 in this order on rehearing
and clarification will become effective
on January 18, 2006.
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
I. Background
2. In Order No. 2003,3 the
Commission adopted standard
procedures and a standard agreement
for the interconnection of large
1 Interconnection for Wind Energy, Order No. 661,
70 FR 34993 (June 16, 2005), FERC Stats. & Regs.
¶ 31,186 (2005) (Final Rule); see also Order
Granting Extension of Effective Date and Extending
Compliance Date, 70 FR 47093 (Aug. 12, 2005), 112
FERC ¶ 61,173 (2005).
2 Those entities requesting rehearing and/or
clarification, and the acronyms used to refer to
them in this order, are listed in Appendix A to this
order.
3 Standardization of Generator Interconnection
Agreements and Procedures, Order No. 2003, 68 FR
49845 (Aug. 19, 2003), FERC Stats. & Regs.,
Regulations Preambles ¶ 31,146 (2003) (Order No.
2003), order on reh’g, 69 FR 15,932 (Mar. 24, 2004),
FERC Stats & Regs., Regulations Preambles ¶ 31,160
(2004) (Order No. 2003–A), order on reh’g, 70 FR.
265 (January 4, 2005), FERC Stats & Regs.,
Regulations Preambles ¶ 31,171 (2004) (Order No.
2003–B), order on reh’g, 70 FR 37661 (June 30,
2005), FERC Stats. & Regs. ¶ 31,190 (2005) (Order
No. 2003–C); see also Notice Clarifying Compliance
Procedures, 106 FERC ¶ 61,009 (2004).
PO 00000
Frm 00011
Fmt 4700
Sfmt 4700
75005
generation facilities. The Commission
required public utilities that own,
control, or operate facilities for
transmitting electric energy in interstate
commerce to file revised Open Access
Transmission Tariffs (OATTs)
containing these standard provisions,
and use them to provide
interconnection service to generating
facilities having a capacity of more than
20 megawatts.
3. In Order No. 2003–A, on rehearing,
the Commission noted that the standard
interconnection procedures and
agreement were based on the needs of
traditional generation facilities and that
a different approach might be more
appropriate for generators relying on
other technologies, such as wind
plants.4 Accordingly, the Commission
granted certain clarifications, and also
added a blank Appendix G to the
standard Large Generation
Interconnection Agreement (LGIA) for
future adoption of requirements specific
to other technologies.5
4. The Commission issued a Notice of
Proposed Rulemaking (NOPR) that
proposed technical standards applicable
to the interconnection of large wind
generating plants 6 to be included in
Appendix G of the LGIA.7 We proposed
the standards in light of our findings in
Order No. 2003–A noted above and in
response to a petition submitted by the
American Wind Energy Association
(AWEA).8 Specifically, the Commission
proposed to establish uniform standards
in Appendix G that would require large
wind plants seeking to interconnect to
the grid to: (1) Demonstrate low voltage
ride-through capability; in other words,
show that the plant can remain on line
during voltage disturbances up to
specified time periods and associated
voltage levels; (2) have supervisory
control and data acquisition (SCADA)
capability to transmit data and receive
instructions from the Transmission
Provider; and (3) maintain a power
factor within the range of 0.95 leading
4 Order
No. 2003–A at P 407, n.85.
5 Id.
6 Large wind generating plants are those with an
output rated at more than 20 MW at the point of
interconnection. The interconnection requirements
for small generators rated at 20 MW or less are set
forth in Standardization of Small Generator
Interconnection Agreements and Procedures, Order
No. 2006, 70 FR 34190 (June 13, 2005), FERC Stats.
& Regs. ¶ 31,180 (2005), reh’g pending.
7 See Interconnection for Wind Energy and Other
Alternative Technologies, Notice of Proposed
Rulemaking, 70 FR 4791 (Jan. 31, 2005), 110 FERC
¶ 61,036 (2005) (NOPR).
8 See Petition for Rulemaking or, in the
Alternative, Request for Clarification of Order No.
2003–A, and Request for Technical Conference of
the American Wind Energy Association (May 20,
2004), filed in Docket Nos. RM02–1–005 and PL04–
15–000 (AWEA Petition).
E:\FR\FM\19DER1.SGM
19DER1
75006
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
to 0.95 lagging, measured at the high
voltage side of the substation
transformers. The Commission proposed
to permit the Transmission Provider to
waive the low voltage ride-through
requirement on a comparable and not
unduly discriminatory basis. We
proposed to permit the Transmission
Provider to waive or defer compliance
with the power factor requirement
where it is not necessary. The
Commission did not propose to adopt a
proposal by AWEA to allow a wind
generator to ‘‘enter the interconnection
queue and conduct its own Feasibility
Study, having obtained the information
necessary to do so upon paying the
initial deposit and submitting its
interconnection application’’ (referred
to as ‘‘self-study’’ provisions).9 The
Commission did, however, ask for
comments on how to balance the need
of wind generators to obtain certain data
from the Transmission Provider before
completing their Interconnection
Requests with the need to protect
critical energy infrastructure
information and commercially sensitive
data against unwarranted disclosure.
5. In the Final Rule, the Commission
adopted final standard procedures and
technical requirements for the
interconnection of large wind plants in
Appendix G, and required all public
utilities that own, control, or operate
facilities for transmitting electric energy
in interstate commerce to append
Appendix G to the Large Generator
Interconnection Procedures (LGIPs) and
LGIAs in their OATTs. As described in
more detail below, the Commission
adopted provisions establishing
standards for low voltage ride-through
and power factor design criteria, and
requiring that wind plants meet those
standards if the Transmission Provider
shows, in the System Impact Study, that
they are needed to ensure the safety or
reliability of the transmission system.
Additionally, the Appendix G adopted
by the Commission included a SCADA
requirement applicable to all wind
plants. Finally, as described in more
detail below, the Commission adopted
in Appendix G to the LGIP limited
special interconnection procedures
applicable to wind plants.
II. Requests for Rehearing and
Clarification and Commission
Conclusions
A. Low Voltage Ride-Through Provisions
6. In the Final Rule, the Commission
adopted a low voltage ride-through
standard, but provided that a wind plant
is required to meet the standard only if
9 See
AWEA Petition at 13.
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
the Transmission Provider shows, in the
System Impact Study, that low voltage
ride-through capability is needed to
ensure safety or reliability. The standard
(adopted in Figure 1 of Appendix G to
the LGIA), if applicable, requires the
wind plant to stay online for specified
time periods and at associated voltage
levels where there is a disturbance on
the transmission system. The Final Rule
requires that the required voltage levels
be measured at the Point of
Interconnection.
7. Several entities requested rehearing
of various aspects of the low voltage
ride-through requirement and standard
included in the Final Rule, including:
(1) Provisions that require low voltage
ride-though only when the System
Impact Study shows that such capability
is necessary for safety or reliability; (2)
the specific low voltage ride-through
standard adopted in the Final Rule; (3)
the point of measurement for the
standard; and (4) arguments that
Transmission Providers should be
permitted to adopt other provisions of
the German low voltage ride-through
standard (which the Commission
referenced in the Final Rule).
8. However, as described in more
detail below, NERC and AWEA jointly
requested that the Commission delay
the effective date of the Final Rule to
give them time to resolve concerns
expressed by NERC regarding the low
voltage ride-through provisions. The
Commission granted this extension, and
on September 19, 2005, NERC and
AWEA submitted a joint report with
recommended revisions.
1. Case-by-Case Application/Burden of
Proof for Applying the Low Voltage
Ride-Through Standard
9. Prior to the NERC/AWEA joint
report, several entities objected on
rehearing to the Final Rule’s adoption of
a low voltage ride-through requirement
on a case-by-case basis, placing the
burden of proof on the Transmission
Provider to show that low voltage ridethrough capability is needed. ATC, EEI,
NERC, NRECA/APPA, and SCE, among
others, urged the Commission to return
to the approach in the NOPR, which
would have required low voltage ridethrough for all wind plants unless
waived by the Transmission Provider on
a not unduly discriminatory basis. ATC
noted that interconnection studies only
consider a snapshot of the transmission
system, and do not take into account
changes in the future that may cause a
need for low voltage ride-through
capability to ensure reliability. ATC, as
well as EEI and SCE, argued that under
the case-by-case approach adopted in
the Final Rule, Transmission Providers
PO 00000
Frm 00012
Fmt 4700
Sfmt 4700
will need to perform additional analyses
to determine if a reliability need will
exist over the life of the wind plant.
SCE, for example, noted that while a
particular System Impact Study may not
conclusively demonstrate that low
voltage ride-through is needed at that
time, if other generation projects are
built, the first wind plant may come to
need low voltage ride-through.
According to various entities, the
additional analyses needed to take these
scenarios into account will increase the
time, cost and complexity of wind plant
interconnections and could be a barrier
to their development.10
10. Furthermore, ATC asserted that
the case-by-case approach imposes the
responsibility for resolving reliability
concerns that arise in the future on the
Transmission Provider because wind
generating plants cannot be retrofitted
with low voltage ride-through
capability. Similarly, NRECA/APPA
argued that this approach unduly
discriminates in favor of wind plants in
that low voltage ride-through capability
may not be ‘‘necessary’’ (and therefore
required) for a specific plant because
other generators or Transmission
Providers can ‘‘make up the
difference.’’ 11 ATC also contended that
the case-by-case approach may require
the Transmission Provider to incur
capital costs that should have been
incurred by the wind plant.
11. EEI and NU argued that the caseby-case approach adopted by the
Commission in the Final Rule ‘‘lowers
the bar for reliability.’’ 12 NERC
similarly asserted that requiring
Transmission Providers to justify
common elements of good utility
practice on a case-by-case basis is
unwise and may deter Transmission
Providers from implementing and
following good utility practice.13
Southern Company states that the
Transmission Provider, as the entity
responsible for maintaining reliability,
should not bear the burden of proof to
establish what is required to maintain
system reliability. Southern Company
states that it supports the Commission’s
statement that Transmission Providers
should not be permitted to require wind
plants to install costly equipment that is
not needed for reliability, but argues
10 New York ISO asserts that the case-by-case
approach could lead to acute problems in New
York, where it has received interconnection
applications from wind plants totaling over 5000
MW of generation. According to New York ISO,
conducting case-by-case reviews for each of these
projects could greatly complicate the study process
and result in substantial delays.
11 Request for Rehearing of NRECA/APPA at 6.
12 Request for Rehearing of EEI at 8.
13 New York ISO states that it adopts NERC’s
position on this issue.
E:\FR\FM\19DER1.SGM
19DER1
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
that the burden of proof should be
shifted, and the System Impact Study
should establish that such equipment is
not required. Also, NRECA/APPA
argued that the case-by-case approach
imposes unreasonable reliability risks,
and effectively voids the requirement
that wind plants have low voltage ridethrough capability ‘‘in a broad range of
circumstances.’’ 14
12. Those requesting rehearing raised
several other arguments regarding the
case-by-case approach and burden of
proof for applying the low voltage ridethrough standard. NERC believed that
the case-by-case approach could
unintentionally create a ‘‘patchwork’’ of
varying requirements. EEI and NU also
suggested that requiring a showing of
need may introduce prolonged
uncertainties into the interconnection
process if parties disagree as to the
study assumptions. SCE asserted that
rather than limiting opportunities for
undue discrimination, the requirement
of a showing of need could result in
discriminatory treatment in areas with
large amounts of wind generation
because projects lower in the queue may
be responsible for additional costs since
the need for low voltage ride-through
could not be demonstrated for earlier
projects. EEI contended that Order No.
2003 already contains provisions
allowing the parties to an
interconnection to exercise their
discretion in complying with system
reliability obligations, and that there is
no evidence of problems with these
procedures that justifies such a
significant departure from them in the
Final Rule. Further, EEI argued that the
Final Rule was a significant departure
from the NOPR and that the
Commission should not adopt it without
providing an opportunity for comments
on it. Finally, NRECA/APPA argued that
the Commission has not explained how
this approach is consistent with NERC
and WECC standards.
2. Specific Low Voltage Ride-Through
Standard
13. Certain requests for rehearing and
clarification also addressed the specific
low voltage ride-through standard
adopted by the Commission in the Final
Rule. In its request for rehearing, NERC
asserted that the standard in Figure 1 of
the Final Rule is not appropriate. More
specifically, NERC contended that
Figure 1, by allowing a wind plant to
disconnect from the transmission
system when the voltage drops below 15
percent of the nominal voltage, could
result in violation of NERC Reliability
Standard TPL–002–0. This standard
14 Request
for Rehearing of NRECA/APPA at 6.
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
requires transmission planners to ensure
that the system will remain stable and
within applicable thermal and voltage
ratings, with no loss of demand or
curtailment of firm transfers, where
there is a normally cleared fault on a
single element, which is typically four
to eight cycles or 0.067 to 0.133 seconds
(67 to 133 milliseconds). According to
NERC, a fault occurring on a
transmission line near a wind plant
could cause the voltage at that point to
drop to zero for this clearing time. NERC
stated that because Figure 1 would
allow the wind plant to disconnect
when the voltage drops below 15
percent of the nominal voltage, the loss
of the single grid element (the
transmission line) would be
compounded by the loss of the real
power (and any reactive power)
produced by the wind plant. This
‘‘double contingency event’’ (loss of
both the transmission line and wind
plant) violates Reliability Standard
TPL–002–0, NERC asserted.
14. To remedy this problem, NERC
requested that the Commission simply
require wind plants to meet NERC and
regional reliability council
requirements.15 Alternatively, NERC
argued that the rule should be modified
to require wind plants to remain
connected through a normally cleared
single line to ground or three phase
fault. Specifically, NERC asserted that
Figure 1 should be altered to require a
wind plant to remain online for 0.167
seconds (167 milliseconds), or ten
cycles, if voltage at the high side of the
wind plant step-up transformer is
reduced to zero. After 0.167 seconds
(167 milliseconds), but before 0.625
seconds (625 milliseconds), NERC
argued that Figure 1 should require the
wind plant to stay connected as long at
the voltage is at or above 15 percent of
the nominal voltage. NERC contended
that these modifications would reduce
the risk to the reliability of the electric
system to an acceptable level.16
15. Similarly, NU asserted that wind
plants should be required to ‘‘remain
on-line for all faults cleared by normal
operation of all protective equipment
unless clearing the fault * * * isolates
the plant from the rest of the grid.’’ 17
According to NU, this change would
15 ISO–NE argued that the Commission should
have required wind plants to be subject to the same
system performance standards that are applied to
other generating technologies.
16 ISO–NE also suggested that, if the Commission
adopted a low voltage ride-through standard, it be
modified to require the wind plant to be connected
at zero voltage for ‘‘a time period associated with
the typical clearing time of a normal design
contingency fault.’’ Request for Rehearing of ISO–
NE at 4.
17 Request for Rehearing of NU at 5.
PO 00000
Frm 00013
Fmt 4700
Sfmt 4700
75007
require generators to have low voltage
ride-through capability down to zero
percent of the nominal voltage at the
Point of Interconnection. CenterPoint
also contend that wind plants should be
required to maintain low voltage ridethrough capability down to zero percent
of the rated line voltage 150
milliseconds (.150 seconds) (the time
generally needed for the transmission
system protective equipment to clear the
fault). NU and CenterPoint argued that
this change would reduce the likelihood
that a low voltage event would escalate
to a cascading outage or voltage
collapse. NU also asserted that this
requirement is similar to those
applicable to other generators, and
could be achieved by wind turbines that
are currently available. NU stated that
the standard adopted in the Final Rule
would threaten reliability by allowing a
wind plant to reduce output, or trip
offline, simply due to a typical system
fault.
16. NRECA/APPA also objected to the
low voltage ride-through standard
adopted in the Final Rule. Specifically,
they contended that the Final Rule
should not have established the low
voltage ride-through curve as an
absolute standard, and instead should
have permitted Transmission Providers
to adopt an alternative curve (subject to
review by the Commission if there is a
dispute) when the System Impact Study
shows that it is necessary. ISO–NE,
going further, requested that if the
Commission adopted a low voltage ridethrough standard, it should be only a
guideline for wind turbine
manufacturers. NRECA/APPA asserted
that the Final Rule did not conclude
that the low voltage ride-through
standard will protect reliability or
address the technical concerns raised by
comments, and, by stating that the
Commission might consider an
alternative low voltage ride-through
standard, recognizes that it may not be
adequate to preserve reliability in all
circumstances. Alternatively, NRECA/
APPA asked that the Commission clarify
that Transmission Providers may
support variations from the low voltage
ride-through curve in the Final Rule,
based on local and subregional
reliability conditions, under the three
variation standards adopted in the Final
Rule.
17. EEI asserted that the technical
challenges presented by wind
generation are being considered by the
industry worldwide, and that many
international standards differ from the
Commission’s Final Rule. Both EEI and
SCE objected to the specific low voltage
ride-through standard through
comparison to the German
E:\FR\FM\19DER1.SGM
19DER1
75008
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
interconnection guidelines. Particularly,
EEI noted that the German grid code
requires wind plants to remain
connected to the grid following a fault
that results in the voltage at the Point of
Interconnection dropping to 15 percent
of the nominal voltage for as long as
0.15 seconds. According to EEI,
revisions to the German grid code are
nearing completion that will require
wind plants to remain connected to the
transmission system following a fault
that drops the voltage at the Point of
Interconnection to zero percent of the
nominal voltage for as long at 0.15
seconds. Further, EEI reported that the
´
Hydro-Quebec requirements for wind
farm interconnection are stricter than
the Commission’s Final Rule; they
require wind plants to ride through a
fault resulting in a voltage drop to zero
percent of nominal voltage for as long as
0.15 seconds. Finally, EEI noted that
Ireland requires wind plants to stay
online after a fault that drops the voltage
to 15 percent of nominal voltage for as
long as 0.15 seconds. SCE additionally
asserted that the requirement that low
voltage ride-through be shown to be
necessary in the System Impact Study
conflicts with the German wind
interconnection guidelines because
those guidelines assume that all
generation will meet the low voltage
ride-through standard. SCE stated that
the Final Rule should adopt low voltage
ride-through capability as a governing
standard, with exceptions approved by
the governing technical body (NERC or
the Western Electricity Coordinating
Council (WECC), a regional reliability
council), as in the German standard.
18. In the Final Rule, the Commission
stated that ‘‘the low voltage ride-through
requirement, and the time periods and
associated voltage levels set forth in
Appendix G, Figure 1, apply to threephase faults.’’ ATC sought clarification
as to whether the low voltage ridethrough requirement applied only to
three-phase faults. Assuming that is the
case, ATC asked whether there was a
requirement for single-phase and
double-phase faults.
3. Point of Measurement for the Low
Voltage Ride-Through Standard
19. NERC argued on rehearing that
because the Point of Interconnection
may be some distance from a wind
plant, the plant might actually
disconnect at voltages higher than 15
percent of the nominal voltage at the
high side of the wind plant step-up
transformer. According to NERC, this
could create a further risk of a double
contingency event.18 To avoid this risk,
18 See
supra, P 13.
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
NERC contended that low voltage ridethrough capability should be measured
at the high voltage terminal of the wind
plant step-up transformer. Southern
Company stated that a revision to
section A.i.2 of the LGIA Appendix G
was necessary to reflect the
Commission’s decision in the Final Rule
to adopt the Point of Interconnection as
the measurement point.
4. Adoption of Other Provisions From
the German Standards
20. SCE noted that while the Final
Rule adopted a low voltage ride-through
standard based on the German wind
interconnection guidelines, the
Commission did not adopt the related
requirements in the German guidelines.
It noted several provisions of the
German guidelines that it stated go
hand-in-hand with the low voltage ridethrough standard.19 SCE asked the
Commission to clarify that Transmission
Providers may implement these other
guidelines in the German standard.
5. NERC/AWEA Recommended
Revisions to Low Voltage Ride-Through
Provisions
21. As noted above, NERC filed a
request for rehearing of the Final Rule
contending, in part, that the specific low
voltage ride-through standard adopted
by the Commission would permit
violations of a NERC system
performance standard.20 On August 4,
2005, NERC and AWEA filed a request
to extend the effective date of the Final
Rule to allow for discussions to resolve
the reliability concerns expressed by
NERC. They committed to submitting to
the Commission a joint final report on
their discussions. On August 5, 2005,
the Commission issued an order
granting this request.21
22. On September 19, 2005, NERC and
AWEA submitted their joint final report,
which recommended revisions to the
low voltage ride-through provisions of
the Final Rule. They state that the
recommended revisions are supported
by the NERC Planning Committee and
AWEA members. NERC states that the
concerns expressed in its request for
rehearing will be resolved if the
Commission adopts the recommended
revisions.
23. Specifically, NERC and AWEA
recommend a different low voltage ridethrough section to be inserted in
Appendix G. The recommended
provisions include a transition period
standard, which would apply to wind
19 See Request for Rehearing and Clarification of
SCE at 9–10.
20 See supra, P 13.
21 Interconnection for Wind Energy, 70 FR 47093
(Aug. 12, 2005), 112 FERC ¶ 61,173 (2005).
PO 00000
Frm 00014
Fmt 4700
Sfmt 4700
plants that either: (a) Have
interconnection agreements signed and
filed with the Commission, filed with
the Commission in unexecuted form, or
filed with the Commission as nonconforming agreements between January
1, 2006 and December 31, 2006, with a
scheduled in-service date no later than
December 31, 2007; or (b) involve wind
turbines subject to a procurement
contract executed before December 31,
2005 for delivery through 2007. During
this transition period, wind plants
would be required to ride through low
voltage events down to 0.15 per unit for
normal clearing times up to a maximum
of nine cycles.
24. Following this transition period,
the NERC/AWEA proposal would
require wind plants to ride through low
voltage events down to a zero voltage
level for ‘‘location-specific’’ clearing
times up to a maximum of nine cycles.
If the fault on the transmission system
remained after this clearing time, the
joint recommendation would permit the
wind plant to disconnect from the
system.
25. Under the joint recommendation
of NERC and AWEA, during both the
transition period and after, low voltage
ride-through capability would be
required for all new wind plant
interconnections, instead of only when
the System Impact Study shows that
such capability is needed for safety or
reliability, as in the Final Rule.
Additionally, in both cases the point of
measurement for the requirement would
be at the high side of the wind plant
step-up transformer, instead of at the
Point of Interconnection, as in the Final
Rule. NERC and AWEA also recommend
eliminating Figure 1 during both the
transition period and after the transition
period because the low voltage ridethrough standard described in their
Joint Report replaces the voltage trace
represented by Figure 1.
26. Finally, NERC and AWEA
recommend limiting the variations to
the low voltage ride-through provisions
that were permitted by the Final Rule.
The Final Rule permits Transmission
Providers to justify variations between
their pro forma tariff and the Final Rule
Appendix G based on the regional
reliability, the ‘‘consistent with or
superior to,’’ or the independent entity
variation standards in Order No. 2003.22
NERC and AWEA recommend that
variations to their proposed low voltage
ride-through provisions be permitted on
an interconnection-wide basis only,
reasoning that such a limitation is
appropriate because the provisions are
intended to satisfy a NERC reliability
22 Final
E:\FR\FM\19DER1.SGM
Rule at P 107, 109.
19DER1
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
standard, and because wind generators
could incur significant additional costs
if they had to meet many different
standards. NERC and AWEA note that
limiting variations would not restrict
the ability to request a deviation in a
specific non-conforming agreement filed
with the Commission (as opposed to a
variation built into a pro forma tariff).
27. The Commission issued notice of
the NERC/AWEA joint report on
September 21, 2005, and provided
interested parties with the opportunity
to submit comments on or before
October 3, 2005. FPL Energy, National
Grid, New York ISO and PJM all filed
comments supporting the technical
recommendations in the joint report.
28. National Grid also asks that the
Commission make two clarifications.
First, it asks the Commission to clarify
that while the point of measurement for
compliance with the low voltage ridethrough standard would be at the high
side of the step-up transformer, the
point of measurement for reactive power
would remain at the Point of
Interconnection. Second, National Grid
requests that the nine cycle maximum
clearing time in the low voltage ridethrough provision applies only to threephase faults. It says that single line-toground faults are typically much longer
than nine cycles, so a general, nonspecified standard is more appropriate
for such faults.
29. New York ISO, while strongly
supporting the technical aspects of the
NERC/AWEA joint recommendations,
urges the Commission to reject the
proposal that variations to the low
voltage ride-through provision be
permitted only on an interconnectionwide basis or through individually-filed
interconnection agreements. It argues
that this could hamper efforts to
preserve reliability in individual
regions, and asserts that satisfying NERC
planning standards is not sufficient to
preserve reliability because New York
State, as well as other regions,
sometimes need more stringent
reliability requirements than those of
NERC. New York ISO says that the
Commission has viewed NERC’s criteria
as being minimum reliability
requirements, which individual regions
may exceed if necessary. Therefore,
New York ISO argues that at a
minimum, the Commission should
permit independent entities to seek
variations from the low voltage ridethrough standards recommended by
NERC and AWEA.
30. Finally, New York ISO asks the
Commission to clarify that, assuming
the NERC/AWEA recommendations are
adopted, the ‘‘filing date’’ for purposes
of the proposed transition period
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
includes the date that conforming
interconnection agreements are fully
and finally executed. New York ISO
notes that executed conforming
agreements need not be filed with the
Commission. Therefore, it contends that
the transition period should apply to
agreements executed within its
timeframe but not filed with the
Commission.
Commission Conclusion on Low Voltage
Ride-Through Provisions
31. The Commission grants rehearing
with regard to the low voltage ridethrough provisions, and adopts the joint
recommendation of NERC and AWEA
without modification. This provides a
standard that will ensure that wind
plants are interconnected to the grid in
a manner that will not degrade system
reliability. Furthermore, this standard
satisfies the reliability concerns
expressed by NERC, and either satisfies
or renders moot many of the rehearing
requests described above, including
those related to the case-by-case
application of the low voltage ridethrough standard and point of
measurement for the low voltage ridethrough standard. Additionally, the
joint recommendation also responds to
the arguments on rehearing of EEI and
SCE regarding comparison to the
German interconnection guidelines.
32. We are eliminating Figure 1 from
Appendix G because the standard we
are adopting in Appendix G replaces
that figure. Accordingly, all references
to Figure 1 in the preamble to the Final
Rule should be read to apply to the
standard now described in Appendix G.
33. We also adopt the NERC/AWEA
proposal to permit variations to the low
voltage ride-through provisions of
Appendix G only on an interconnectionwide basis. The low voltage ridethrough provisions we adopt in this
order on rehearing were crafted
specifically, after negotiation among the
wind industry and NERC, to ensure that
NERC Reliability Standard TPL–002–0
is met in all regions. While other
interconnection standards may be more
susceptible to variation among
Transmission Providers or independent
entities, the close connection of this
standard to an industry-wide reliability
standard persuades us that limiting
variations to those made on an
interconnection-wide basis will best
ensure that reliability is protected.
Accordingly, we reject SCE’s request
that we clarify that Transmission
Providers may implement other
guidelines from the German
interconnection standard. Adoption of
other guidelines from the German
standard on a Transmission Provider-
PO 00000
Frm 00015
Fmt 4700
Sfmt 4700
75009
specific basis could result in varying
requirements that may not meet
established reliability standards. For the
same reasons, we also reject New York
ISO’s assertion that the Commission
should continue to permit variations to
the low voltage ride-through provisions
under the three variation standards in
the Final Rule, and particularly the
independent entity variation. We note,
however, that under section 1211 of the
Energy Policy Act of 2005, the State of
New York ‘‘may establish rules that
result in greater reliability within that
State, as long as such action does not
result in lesser reliability outside the
State than that provided by the
reliability standards.’’ 23 Therefore, the
Commission will consider proposed
variations from the State of New York
under this statutory provision.
34. In response to the arguments of
NRECA/APPA that the Final Rule
should have permitted Transmission
Providers to adopt alternative low
voltage ride-through standards, and ISONE’s contention that the standard in the
Final Rule should be only a guideline,
we find that the definitive standard we
adopt here will provide certainty to
wind developers and manufacturers and
ensure that reliability is maintained and
NERC planning standards are met. If
another standard is necessary for a
specific wind plant interconnection to
maintain reliability, a non-conforming
agreement may be filed with the
Commission.
35. In response to ATC and National
Grid, we clarify that the low voltage
ride-through provisions we are adopting
apply to all types of faults, not just to
three-phase faults. The standard refers
to three-phase faults with normal
clearing as well as single line to ground
faults with delayed clearing. In response
to National Grid’s specific concern, we
clarify that the nine cycle maximum
clearing time expressed in the low
voltage ride-through provisions applies
only to three-phase faults. Single line to
ground faults have typically much
longer clearing times, as National Grid
notes, and the low voltage ride-through
provisions adopted here recognize this
difference by specifically referring to
‘‘single line to ground faults with
delayed clearing.’’ This non-specified
standard is appropriate for those types
of faults.
B. Power Factor (Reactive Power)
Provisions
36. In the Final Rule, the Commission
adopted in Appendix G to the LGIA a
power factor standard applicable to
23 Energy Policy Act of 2005, Pub. L. 109–58,
§ 1211, 119 Stat. 594, 945 (2005).
E:\FR\FM\19DER1.SGM
19DER1
75010
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
wind plants. The Final Rule provides
that wind plants are required to meet
this standard only if the Transmission
Provider shows, in the System Impact
Study, that reactive power capability is
necessary to ensure the safety or
reliability of the transmission system.
The specific power factor standard in
Appendix G to the LGIA, if applicable,
requires a wind plant to maintain a
power factor within the range of 0.95
leading to 0.95 lagging (hereinafter +/
¥0.95), to be measured at the Point of
Interconnection.
37. Requests for rehearing and/or
clarification of these provisions concern
whether wind plants should have to
maintain a required power factor only
where the System Impact Study shows
that it is required for reliability or
safety, and whether the power factor
standard and point of measurement
adopted by the Commission in the Final
Rule are appropriate.
1. Case-by-Case Application/Burden of
Proof for Applying the Power Factor
Standard
38. Several entities object to the
provisions in the Final Rule that require
wind plants to maintain the required
power factor only when the
Transmission Provider, in the System
Impact Study, shows that it is necessary
to ensure safety or reliability. NERC
objects to this approach because it may
deter Transmission Providers from
implementing and following good
utility practice and could create a
‘‘patchwork’’ of varying requirements.
NU argues that this approach ‘‘lowers
the bar for reliability,’’ and will add
complexity, cost and delay to the
generator interconnection process
because Transmission Providers will be
required to perform more studies to
determine whether reactive power
capability is necessary for reliability or
safety. Southern Company states that
the Transmission Provider, as the entity
responsible for maintaining reliability,
should not bear the burden of proof to
establish what is required to maintain
system reliability. It supports the
Commission’s statement that
Transmission Providers should not be
permitted to require wind plants to
install costly equipment that is not
needed for reliability, but argues that
the burden of proof should be shifted to
the generator.
39. NRECA/APPA notes that
traditional generators are required to
meet the power factor standard not
because reactive power is needed in
every case to preserve reliability, but
instead because the transmission system
is dynamic and requires flexibility over
time to maintain reliability. They state
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
that the need for reactive power in the
future under a variety of operating
conditions cannot be determined with
perfect certainty in the System Impact
Study. The case-by-case approach, they
contend, grants an undue preference to
wind plants, imposes risks to system
reliability, and shifts costs to consumers
and other generating plants. The risk to
system reliability is that the Final Rule
may only require a wind plant to
provide reactive power after other wind
plants have been installed without such
capability, and that at that point the
resources from that single plant may not
be enough to protect the transmission
system. NRECA/APPA also asserts that
the case-by-case approach increases
uncertainty, contrary to the
Commission’s conclusion in the Final
Rule, because each wind plant will face
different requirements based on the
outcome of the System Impact Study.
Additionally, it contends that this
approach creates more opportunities for
discrimination because it would permit
wind plants to be treated differently.
40. ATC contends that the
Commission has offered no guidance as
to what power factor range would be
acceptable if a reliability need is not
identified (and thus reactive power is
not required), and whether wind plants
in this instance must operate within any
particular reactive power operating
band. Similarly, NU expresses concern
that wind plants could operate at any
power factor in the absence of a
showing of need in the System Impact
Study, and thus avoid a physical
requirement for delivering power onto
the transmission system. According to
ATC, the rule could be interpreted to
permit wind plants to operate at any
power factor they choose. It claims that
reactive power is needed for each
generator, and that each generator
should be obligated to operate within a
range of power factors, regardless of
whether the transmission system as a
whole needs additional reactive power
capability. ATC recommends that at a
minimum, the Commission require all
wind plants to meet a power factor
range of 0.95 leading to 1.0 (unity), and
allow the Transmission Provider to
require a range of 1.0 (unity) to 0.95
lagging if the System Impact Study
shows that there is a reliability need.
Commission Conclusion
41. The Commission will not modify
the Final Rule to require wind plants to
meet the power factor standard without
a showing by the Transmission
Provider, through the System Impact
Study, that it is needed for safety or
reliability. The case-by-case approach to
a reliability needs assessment adopted
PO 00000
Frm 00016
Fmt 4700
Sfmt 4700
in the Final Rule will not threaten
reliability, as several of those seeking
rehearing argue. As we noted in the
Final Rule, if reactive power is
necessary to maintain the safety or
reliability of the transmission system,
the System Impact Study performed by
the Transmission Provider will establish
that need.24 We stated in the Final Rule,
and reiterate here, that the System
Impact Study is the appropriate study
for determining whether reactive power
capability is needed.25 Furthermore, we
reasoned in the Final Rule that requiring
wind plants to maintain the power
factor standard only if the System
Impact Study shows it to be necessary
will not only ensure that increased
reliance on wind power will not
degrade system safety or reliability, but
also will limit opportunities for undue
discrimination by ensuring that
Transmission Providers do not require
costly equipment that is not necessary
for reliability.26
42. NERC states that the decision in
Order No. 661 to use a case-by-case
approach may deter Transmission
Providers from following Good Utility
Practice, and may have the unintended
consequence of spawning a patchwork
of varying requirements. We agree with
NERC that Transmission Providers must
follow Good Utility Practice when
interconnecting all generating plants,
including wind plants, and that not
following Good Utility Practice when
performing System Impact Studies
could lead to problems. However, the
Commission points out that every
Transmission Provider is required under
Order No. 2003 to follow Good Utility
Practice. Transmission Providers are
required to complete a detailed System
Impact Study, and are required to
ensure that NERC reliability standards
are met in all instances. This includes
performing studies to determine what is
necessary to ensure that the
interconnection of a wind generating
facility does not degrade grid reliability.
The Commission recognizes that the
industry (and particularly NERC) is
continuing to address technical issues
involved in the interconnection of wind
plants. If NERC through its stakeholders
and Board approval process develops a
new standard, the Commission will
entertain such a standard. Finally, we
disagree with NRECA/APPA’s
suggestion that the Final Rule threatens
the reliability of the transmission
system because it may require only
wind plants later in the queue to
provide reactive power, which may not
24 Final
Rule at P 51.
25 Id.
26 Id.
E:\FR\FM\19DER1.SGM
19DER1
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
be sufficient to protect the grid. The
System Impact Study will take into
account the system’s need for reactive
power, both as it exists today and under
reasonable anticipated assumptions.
NRECA/APPA has not explained how
assessing the need for reactive power
through the System Impact Study
process will result in too little reactive
power being available in the future.
Whenever a new generator is added to
its system, the Transmission Provider
must complete a new System Impact
Study to ensure that reliability
requirements are met; this may require
a new wind generator later in the queue
to meet the reactive power requirement.
43. We also reject arguments that the
case-by-case approach is inappropriate
because of the dynamic nature of the
transmission system. The fact that the
transmission system is constantly
changing is not new or unique to the
study of wind plant interconnections.
The studies that are part of the
interconnection process should take
into account likely circumstances that
could occur on the Transmission
Provider’s system, whether the studies
are conducted in connection with a
proposed wind plant or another type of
generating facility.
44. Furthermore, we are not
persuaded that the approach adopted in
the Final Rule will result in additional
studies, increased costs and delays, and
cost shifts. First, as noted previously,
the System Impact Study, as well as the
other interconnection studies, should
take into account a variety of
assumptions concerning anticipated
transmission system conditions. If
additional or expanded studies are
needed to determine whether the power
factor standard is necessary, the
Commission does not believe that the
additional burden will outweigh the
cost considerations underlying the caseby-case approach. Finally, although the
case-by-case approach may result in
some delay, we remind the parties to a
wind plant interconnection, like other
interconnections, that they are still
required to meet the milestones set forth
in the LGIP. Any increased costs from
completing expanded or additional
studies within the timeframe required
by this rule will be borne by the wind
plant Interconnection Customer, as
provided in Order No. 2003, which will
leave other generators and the
Transmission Provider unharmed.
45. The Commission also rejects
arguments that the case-by-case
approach provides more opportunities
for discrimination. As we noted in the
Final Rule Appendix G was adopted to
take into account the technical
differences between wind plants and
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
traditional generating plants. One of
these differences is that for wind plants,
reactive power capability is a significant
added cost, while it is not a significant
additional cost for traditional
generators. Given these technical
differences, treating wind plants
differently with regard to reactive power
requirements is not unduly
discriminatory or preferential.
Additionally, we note that the outcome
of the System Impact Study, which
determines whether reactive power will
be required, can be challenged, which
will serve to minimize the opportunities
for discrimination by the Transmission
Provider. Also, the wind plant
Interconnection Customer will have
recourse to the Commission if it believes
the Transmission Provider has acted in
a discriminatory manner.
46. The Commission declines to adopt
ATC’s request that all wind plants, at a
minimum, operate within a power factor
range of 0.95 leading to 1.0 (unity). This
requirement would essentially require
reactive power in every case, which we
have already rejected. If reactive power
capability is needed, including a power
factor range of 0.95 leading to 1.0
(unity), the System Impact Study will
demonstrate this need.
2. Specific Power Factor Standard
47. NRECA/APPA argues that the
Commission should clarify that wind
generators must meet the same reactive
power requirements as other generators,
provided the requirements are imposed
in a nondiscriminatory manner. It notes
that some Transmission Providers
impose a power factor range wider that
+/¥0.95 on all new generation, and
argues that in such cases, the same
range should be applied to wind plants.
It argues that not imposing the same
range threatens reliability and shifts the
costs of preserving reliability to
customers or competing generators.
48. EEI and NU assert that wind
plants should regulate voltage to a set
point established by the Transmission
Provider, as do synchronous generators.
EEI contends that the language it offered
in its initial comments would provide
this necessary clarity, while also
maintaining the flexibility provided in
Order No. 2003 so that individual, sitespecific conditions may be addressed.27
NU states that wind turbines have this
capability, either inherently (doubly fed
27 EEI’s March 2, 2005 comments in this
proceeding suggest that we require the wind plant
to maintain a power factor within the range
specified by the Transmission Provider ‘‘from time
to time,’’ but would not require that it operate
outside of the 0.95 leading to 0.95 lagging range.
See Comments of EEI (March 2, 2005) at 5–6.
PO 00000
Frm 00017
Fmt 4700
Sfmt 4700
75011
induction generators) or through
external equipment.
49. NRECA/APPA also expresses
concern that the phrase ‘‘taking into
account any limitations due to voltage
level, real power output, etc.’’ in the
power factor requirements section of
Appendix G could create operational
problems for Transmission Providers
with wind plants on their systems.
Specifically, it is concerned that this
language could exempt wind plants
from their reactive power requirements
during startup and low output periods,
which could degrade reliability during a
system contingency.
Commission Conclusion
50. With regard to NRECA/APPA’s
request for clarification that wind
generators must meet a wider power
factor range because some Transmission
Providers impose a power factor range
wider that +/¥0.95 on all new
generation, we note that if we were to
allow the Transmission Provider to
impose a wider power factor range as a
matter of routine, that would defeat the
purpose of adopting a reactive power
standard for wind generators. However,
we note that if the System Impact Study
shows the need for a power factor range
wider than +/¥0.95 for safety or
reliability, the Transmission Provider
must file a non-conforming agreement,
as Order No. 2003 permits. The
Commission will consider these nonconforming agreements on a case by
case basis. If a Transmission Provider
has a different power factor range in its
LGIA and wishes to apply that same
range in Appendix G, it may seek a
variation from the Commission under
the variation standards approved in the
Final Rule.28 We remind Transmission
Providers, however, that the
Commission has adopted a specific
power factor standard for wind plants
because of their technical differences.
Any proposed variations will be viewed
in light of these technical differences.
51. In response to the assertion of EEI
and NU that wind plants should
regulate voltage to a set point
established by the Transmission
Provider, we note that in the Final Rule
we concluded that article 9.6.2 of the
LGIA (which applies to all plants,
including wind plants) already requires
that the ‘‘Interconnection Customer
* * * operate the Large Generating
Facility to maintain the specified output
voltage or power factor at the Point of
Interconnection.’’ 29
52. Finally, the Commission
addressed in the Final Rule the
28 Final
29 Id.
E:\FR\FM\19DER1.SGM
Rule at P 109.
at P 55.
19DER1
75012
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
concerns raised by NRECA/APPA
regarding the phrase ‘‘taking into
account any limitations due to voltage
level, real power output, etc.’’ We stated
that this language was necessary due to
the technical limitations of wind
generating technology.30 We noted that
all wind generating equipment vendors
cannot meet the required power factor
range at all levels of output. We reiterate
that these technical differences make
the disputed language necessary.
Furthermore, without this language, a
Transmission Provider could
discriminate against a wind plant by
requiring that it operate at the stated
power factor at voltages where it is
technically infeasible to do so.
3. Point of Measurement of Power
Factor
53. National Grid asks that if the
Commission adopts the recommended
revisions to the low voltage ride-through
provisions filed jointly by AWEA and
NERC, it clarify that while the point of
measurement for compliance with the
low voltage ride-through standard
would be at the high-side of the step-up
transformer, the point of measurement
for reactive power is at the Point of
Interconnection.
Commission Conclusion
54. We clarify that the point of
measurement for the reactive power
standard is at the Point of
Interconnection.
C. Self-Study of Interconnection
Feasibility
55. In the Final Rule, the Commission
adopted special interconnection
procedures that allow the wind plant
Interconnection Customer, when
completing the Interconnection Request
form required by section 3.3 of the LGIP,
to provide the Transmission Provider
with a simplified set of preliminary data
depicting the wind plant as a single
equivalent generator.31 Once the wind
generator has provided this data and
satisfied all other applicable
Interconnection Request conditions, the
special procedures permit the wind
plant to enter the queue and receive the
base case data as provided for in the
LGIP. Finally, the special procedures
adopted in the Final Rule require the
wind plant Interconnection Customer to
submit, within six months of submitting
the Interconnection Request, completed
detailed electrical design specifications
and other data (including collector
30 Id.
at P 56.
equivalent generator’’ information is
design data that represents the aggregate electrical
characteristics of the individual wind generators as
a single generator.
31 ‘‘Single
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
system layout data) needed by the
Transmission Provider to complete the
System Impact Study.
56. Southern Company argues on
rehearing that these provisions give
wind developers a special preference
that unfairly disfavors other generating
technologies.
57. EEI, NU and Southern Company
contend that the ‘‘self-study’’ provisions
of the Final Rule will add further
complexity and uncertainty to the queue
process and make queue management
and assignment of cost responsibilities
more difficult for Transmission
Providers with large wind-powered
generation projects in their queue.
Southern Company adds that the selfstudy provisions could increase costs to
market participants because the
Transmission Provider will have to run
multiple studies. EEI argues that until
the industry can fully address the issues
raised by these provisions in a technical
forum, the Commission should remove
the provisions from Appendix G. EEI
and NU assert that the provisions do not
protect against a wind plant
Interconnection Customer making
significant revisions to its project
proposal. If the Commission does not
remove the provisions entirely, EEI and
NU suggest that the Commission allow
the Transmission Provider to determine
whether the detailed electrical design
specifications later submitted by the
wind plant Interconnection Customer
are a material modification to the initial
proposal, which would result in the
initial Interconnection Application
being withdrawn.
58. Midwest ISO agrees with the
Commission that a wind plant should be
able to enter the queue and receive base
case data based on preliminary design
specifications. However, it seeks
rehearing of the provision that permits
a wind plant to wait up to six months
before submitting final design
specifications. It argues that this
procedure promotes inefficiency
because the Transmission Provider may
be able to evaluate the proposed
interconnection, but cannot do so
because it lacks necessary data. Midwest
ISO requests that the Commission revise
the Appendix G self-study provisions to
permit the Transmission Provider to
notify the wind plant Interconnection
Customer of its intent to start the
System Impact Study. Once this notice
is given, the wind plant developer
would have five business days to
‘‘submit either actual design
specifications or generic specifications
based on typical equipment used in the
industry.’’ 32 Further, Midwest ISO
proposes that if the wind plant
Interconnection Customer submits
generic specifications, it should have to
accept cost uncertainty, because
additional facilities may be required
when the actual design specifications
are taken into account. Midwest ISO
asserts that this would limit delays in
the study process and would allow the
Transmission Provider to identify
potential problems or eliminate tenuous
or technically deficient projects earlier
and to better use its resources to study
proposed interconnections.
Commission Conclusion
59. The Commission will deny these
requests for rehearing. We will make
one minor revision to label these special
interconnection procedures for wind
plants as ‘‘Appendix 7’’ to the LGIP, as
discussed in more detail below.
60. In response to arguments that the
self-study procedures for wind plants
give these plants a preference, we
reiterate that these procedures were
developed to recognize the technical
differences of wind plants. Unlike
conventional generators, wind plant
design specifications and configurations
can change significantly based on their
placement on the transmission
system.33 For example, the placement of
wind turbines, voltage support devices,
transformers, and other equipment
(including the layout of the medium
voltage collector system) depend on the
location of the wind plant, the location
of other generators on the transmission
system, and other information included
in the base case data.34 To accommodate
these differences, the Final Rule permits
wind plants to enter the interconnection
queue with a set of preliminary
electrical design specifications
depicting the wind plant as a single
generator, instead of providing detailed
design specifications as required by
Order No. 2003. Treating wind plants
differently in this regard is not unduly
discriminatory or preferential, but as
noted elsewhere, simply recognizes that
wind plants have different technical
characteristics than the more traditional
forms of generation that the LGIP and
LGIA were designed to accommodate.
We continue to believe that without this
reasonable accommodation,
Transmission Providers could frustrate
the interconnection of wind plants by
requiring them to submit detailed
design data, which they cannot do until
later in the interconnection process.
61. We are not persuaded that the
reasonable self-study provision we
adopted will make the interconnection
33 Final
32 Request
PO 00000
for Rehearing of Midwest ISO at 4.
Frm 00018
Fmt 4700
Sfmt 4700
Rule at P 97.
34 Id.
E:\FR\FM\19DER1.SGM
19DER1
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
queue process significantly more
difficult or complex. Wind plant
Interconnection Customers who provide
the preliminary single generator
equivalent data are required to provide
final detailed electrical design
specifications no later than six months
after submitting the initial
Interconnection Request. This sixmonth time period takes into account
the procedures needed before the start
of the System Impact Study, including
the Feasibility Study and negotiation of
study agreements. Therefore, the
Transmission Provider will receive from
the wind plant the detailed design
information needed to conduct the
System Impact Study. For this reason,
we also deny Midwest ISO’s request to
modify the six-month deadline. If we
adopted Midwest ISO’s proposed
modifications, the Transmission
Provider could request that the wind
plant provide detailed design
specifications at any time it believes it
is ready to begin the System Impact
Study, even a day after the initial
Interconnection Request is submitted.
As a result, this modification would
defeat the purpose of permitting wind
plants to submit preliminary design
specifications, and could allow
Transmission Providers to frustrate the
interconnection of wind plants.
62. With respect to the alternative
suggestion by EEI and NU that the
Transmission Provider be permitted to
determine that a detailed design
specification later submitted by the
wind plant Interconnection Customer is
a material modification of the
Interconnection Request, we note that
section 4.4 of the LGIP already
addresses modifications and will apply
to wind plants as well as other
generating technologies. When applying
this section to wind plant
Interconnection Requests that first
submit preliminary design
specifications, Transmission Providers
are not to consider the detailed design
data provided later by the wind plant
Interconnection Customer to be a
material modification unless it
significantly departs from the
preliminary specifications provided. In
other words, the detailed design
provided later should be substantially
the same as the initial single-generator
equivalent design in terms of its costs
and effect on the transmission system.
63. Finally, to avoid confusion, the
Commission will rename the Appendix
G to the LGIP it adopted in the Final
Rule as ‘‘Appendix 7, Interconnection
Procedures for a Wind Generating
Plant.’’ Accordingly, when complying
with the Final Rule and this order on
rehearing, public utilities must adopt
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
the special interconnection procedures
applicable to wind plants as Appendix
7 to their LGIPs. The low voltage ridethrough, power factor design criteria
and SCADA provisions should continue
to be labeled ‘‘Appendix G’’ to the
LGIA.
D. Adoption of Appendix G on an
Interim Basis Only
64. EEI and NU each generally argue
that the Commission should apply
Appendix G only on an interim basis,
and should defer to NERC and Institute
of Electrical and Electronics Engineers
(IEEE) processes to develop formal
technical standards. Southern Company
argues that the Commission should
defer to NERC, regional reliability
councils, and other technical
organizations to develop technical
requirements for wind plants, and
should suspend application of the Final
Rule and formally request that these
entities develop technical standards.
Southern Company argues that this
would avoid the problems that result
from having the Commission review
each variation to Appendix G as the
technical standards are developed and
revised. It also asserts that the
Commission should not be the arbiter of
technical disputes, such as the outcome
of the System Impact Study or specific
SCADA requirements, as the Final Rule
provides.
65. As noted above, NERC similarly
argues that the Commission should only
require wind plants to meet NERC and
regional reliability council
requirements, noting that Figure 1 is
likely to remain static over time, which
could hamper the development of wind
generator technology. EEI notes that
NERC has established a Wind Generator
Task Force that is examining existing
standards and will make proposals later
this year. It states that the industry
worldwide is addressing technical
challenges presented by wind
generation. Significant modifications are
being developed for the German grid
´
code, and Hydro-Quebec is considering
several reliability issues regarding wind
generator interconnection. NERC further
´
notes that Hydro-Quebec requires the
same dynamic performance of wind
plants that it requires of other
generating facilities, and that major
wind turbine manufacturers have shown
that they can meet this requirement. EEI
proposes that the industry conduct a
technical forum to resolve issues related
to wind plant interconnection,
concluding with formal
recommendations to the Commission
that could be used in a new NOPR, or
to develop formal proposals for NERC or
IEEE standards.
PO 00000
Frm 00019
Fmt 4700
Sfmt 4700
75013
Commission Conclusion
66. The Commission denies these
requests for rehearing, and others noted
earlier, that ask us to adopt Appendix G
only on an interim basis. Standards are
needed today because no nationwide
standard is currently in place and it is
uncertain when such a standard will be
finalized. Without a firm standard in
place, the current ad hoc practices for
wind interconnection requirements may
frustrate the interconnection of wind
plants. As we noted in the Final Rule,
Appendix G is necessary to recognize
the technical differences between wind
plants and traditional plants to ensure
that the entry of wind generation into
markets is not unnecessarily inhibited.
67. We recognize, however, that the
industry continues to study and address
issues raised by the interconnection and
operation of wind plants. For that
reason, the Commission stated in the
Final Rule that if another entity
develops an alternate standard, a
Transmission Provider may seek to
justify adopting it as a variation from
Appendix G.35 We also stated that we
would consider a future industry
petition to revise Appendix G to
conform to a NERC-developed
standard.36 We reiterate both of those
statements here, and also note that
under the Energy Policy Act of 2005, the
Commission will be addressing
mandatory reliability standards.37
E. Transition Period
68. In the Final Rule, the Commission
adopted a transition period that applies
to the low voltage ride-through, power
factor design criteria and SCADA
requirements. These technical
requirements in the Final Rule
Appendix G, if applicable, apply only to
LGIAs signed, filed with the
Commission in unexecuted form, or
filed as non-conforming agreements, on
or after January 1, 2006, or the date six
months after publication of the Final
Rule in the Federal Register, whichever
is later.38 The Commission adopted this
transition period to allow wind
35 Id. at P 34. We note that in this order on
rehearing, variations to the low voltage ride-through
standard will only be permitted on an
interconnection-wide basis. As we note above,
however, non-conforming agreements may be
submitted to the Commission. See P 33–34, supra.
36 Id.
37 See Energy Policy Act of 2005, Pub. L. 109–58,
§ 1211, 119 Stat. 594, 941 (2005).
38 The Final Rule was published in the Federal
Register on June 16, 2005. Thus, the low voltage
ride-through, power factor design criteria and
reactive power provisions in the Final Rule, as
revised herein, will apply to LGIAs signed, filed
with the Commission in unexecuted form, or filed
as non-conforming agreements, on or after January
1, 2006.
E:\FR\FM\19DER1.SGM
19DER1
75014
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
equipment currently in the process of
being manufactured to be completed
without delay or added expense, and to
ensure that the Final Rule did not
interrupt the supply of wind turbines.
69. NRECA/APPA argues that the
transition period is arbitrary, capricious,
and unduly discriminatory. NRECA/
APPA asserts that the Commission
adopted the transition period with no
technical justification and no
explanation of how the transition period
will maintain the reliability of the
transmission system. They contend that
the transition period requires
transmission customers and competing
generators to bear the reliability effects
of wind plants interconnected during
the transition period. While NRECA/
APPA state that there are ‘‘valid
commercial considerations’’ that should
be taken into account for the existing
inventory of wind equipment, they
contend that such determinations
should be made on a case-by-case basis.
Commission Conclusion
70. The Commission declines to
remove the transition period as NRECA/
APPA request. We adopted this
reasonable transition mechanism to
allow wind turbines in the process of
being manufactured to be completed
without delay or additional expense.39
The transition period ensures that the
supply of wind turbines is not unfairly
or unreasonably interrupted.40
Furthermore, contrary to NRECA/
APPA’s contention, the Commission
considered the possible reliability
effects of the transition period, and
concluded that the remaining provisions
of Order No. 2003 will adequately
protect reliability.41 The remaining
provisions of Order No. 2003 will also
ensure that other generators or the
Transmission Provider will not bear the
reliability effects of a wind plant
because that rule, and the LGIA and
LGIP contained in it, ensure that
generating facilities are not
interconnected in a manner that
degrades reliability.
Street, NE., Room 2A, Washington, DC
20426.
72. From the Commission’s Home
Page on the Internet, this information is
available in the Commission’s document
management system, eLibrary. The full
text of this document is available on
eLibrary in PDF and Microsoft Word
format for viewing, printing, and/or
downloading. To access this document
in eLibrary, type the docket number
excluding the last three digits of this
document in the docket number field.
73. User assistance is available for
eLibrary and the Commission’s Web site
during normal business hours. For
assistance, please contact FERC Online
Support at 1–866–208–3676 (toll free) or
202–502–6652 (e-mail at
FERCOnlineSupport@FERC.gov), or the
Public Reference Room at 202–502–
8371, TTY 202–502–8659 (e-mail at
public.referenceroom@ferc.gov).
IV. Effective Date
74. As noted above, on August 5,
2005, the Commission issued an order
extending the effective date of the Final
Rule to October 14, 2005.42 Those
provisions of the Final Rule not revised
in this order on rehearing and
clarification are effective as of that date.
Changes made to the Final Rule in this
order on rehearing and compliance will
become effective on January 18, 2006.
V. Compliance With the Final Rule and
Order on Rehearing and Clarification
75. In the Commission’s August 5,
2005 order extending the effective date
of the Final Rule, the Commission also
extended to November 14, 2005, the
date by which all public utilities that
own, control, or operate transmission
facilities in interstate commerce are to
adopt, in their OATTS, the Final Rule
Appendix 7 (as described above) 43 as an
amendment to the LGIP, and Final Rule
Appendix G as an amendment to the
LGIA. By further notice issued October
28, 2005, the Commission extended this
date further, to December 30, 2005.
Public utilities who have already filed a
Final Rule Appendix G as amendments
to the LGIPs and LGIAs in their OATTs
must file, by December 30, 2005, the
revisions to the Final Rule Appendix G
to the LGIA made in this order on
rehearing.
III. Document Availability
71. In addition to publishing the full
text of this document in the Federal
Register, the Commission provides all
interested persons an opportunity to
view and/or print the contents of this
document via the Internet through
FERC’s Home Page (https://www.ferc.gov) List of Subjects in 18 CFR Part 35
and in FERC’s Public Reference Room
during normal business hours (8:30 a.m.
Electric power rates; Electric utilities.
to 5 p.m. Eastern time) at 888 First
39 Final
42 Order Granting Extension of Effective Date and
Extending Compliance Date, 70 FR 47093 (Aug. 12,
2005), 112 FERC ¶ 61,173 (2005).
43 See supra, P 60.
Rule at P 115.
40 Id.
41 Id.
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
PO 00000
Frm 00020
Fmt 4700
Sfmt 4700
By the Commission. Chairman Kelliher
dissenting in part with a separate statement
attached.
Magalie R. Salas,
Secretary.
In consideration of the foregoing, the
Commission revises part 35, Chapter I,
Title 18 of the Code of Federal
Regulations as follows.
I
PART 35—FILING OF RATE
SCHEDULES
1. The authority citation for part 35
continues to read as follows:
I
Authority: 16 U.S.C. 791a–825r, 2601–
2645; 31 U.S.C. 9701; 42 U.S.C. 7101–7352.
2. In § 35.28, revise paragraph (f)(1) to
read as follows:
I
§ 35.28 Non-discriminatory open access
transmission tariff.
*
*
*
*
*
(f) Standard generator
interconnection procedures and
agreements. (1) Every public utility that
is required to have on file a nondiscriminatory open access transmission
tariff under this section must amend
such tariff by adding the standard
interconnection procedures and
agreement contained in Order No. 2003,
FERC Stats. & Regs. & 31,146 (Final Rule
on Generator Interconnection), as
amended by the Commission in Order
No. 661, FERC Stats. & Regs. ¶ 31,186
(Final Rule on Interconnection for Wind
Energy), and the standard small
generator interconnection procedures
and agreement contained in Order No.
2006, FERC Stats. & Regs. ¶ 31,180
(Final Rule on Small Generator
Interconnection), or such other
interconnection procedures and
agreements as may be approved by the
Commission consistent with Order No.
2003, FERC Stats. & Regs. & 31,146
(Final Rule on Generator
Interconnection) and Order No. 2006,
FERC Stats. & Regs. ¶ 31,180 (Final Rule
on Small Generator Interconnection).
(i) The amendment to implement the
Final Rule on Generator Interconnection
required by the preceding subsection
must be filed no later than January 20,
2004.
(ii) The amendment to implement the
Final Rule on Small Generator
Interconnection required by the
preceding subsection must be filed no
later than August 12, 2005.
(iii) The amendment to implement the
Final Rule on Interconnection for Wind
Energy required by the preceding
subsection must be filed no later than
December 30, 2005.
(iv) Any public utility that seeks a
deviation from the standard
interconnection procedures and
E:\FR\FM\19DER1.SGM
19DER1
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
agreement contained in Order No. 2003,
FERC Stats. & Regs. & 31,146 (Final Rule
on Generator Interconnection), as
amended by the Commission in Order
No. 661, FERC Stats. & Regs. ¶ 31,186
(Final Rule on Interconnection for Wind
Energy), or the standard small generator
interconnection procedures and
agreement contained in Order No. 2006,
FERC Stats. & Regs. ¶ 31,180 (Final Rule
on Small Generator Interconnection),
must demonstrate that the deviation is
consistent with the principles of either
Order No. 2003, FERC Stats. & Regs. &
31,146 (Final Rule on Generator
Interconnection) or Order No. 2006,
FERC Stats. & Regs. ¶ 31,180 (Final Rule
on Small Generator Interconnection).
[Note: The Appendices will not be
published in the Code of Federal
Regulations]
Appendix A—List of Entities
Requesting Rehearing and/or
Clarification or Submitting Comments
and Acronyms
ATC—American Transmission Company
LLC.
CenterPoint—CenterPoint Energy Houston
Electric, LLC.
EEI—Edison Electric Institute.
FPL Energy—FPL Energy, LLC.
ISO–NE—ISO New England, Inc.
Midwest ISO—Midwest Independent
Transmission System Operator, Inc.
National Grid—National Grid USA.
NERC—North American Electric Reliability
Council.
New York ISO—New York Independent
System Operator, Inc.
NRECA/APPA—National Rural Electric
Cooperative Association and American
Public Power Association.
NU—Northeast Utilities.
PJM—PJM Interconnection, L.L.C.
SCE—Southern California Edison Company.
Southern Company—Southern Company
Services, Inc.
Appendix B
[Note: These Provisions to be Adopted as
Appendix G to the LGIA.]
Appendix G—Interconnection
Requirements for a Wind Generating
Plant
Appendix G sets forth requirements and
provisions specific to a wind generating
plant. All other requirements of this LGIA
continue to apply to wind generating plant
interconnections.
A. Technical Standards Applicable to a Wind
Generating Plant
i. Low Voltage Ride-Through (LVRT)
Capability
A wind generating plant shall be able to
remain online during voltage disturbances up
to the time periods and associated voltage
levels set forth in the standard below. The
LVRT standard provides for a transition
period standard and a post-transition period
standard.
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
Transition Period LVRT Standard
The transition period standard applies to
wind generating plants subject to FERC Order
661 that have either: (i) Interconnection
agreements signed and filed with the
Commission, filed with the Commission in
unexecuted form, or filed with the
Commission as non-conforming agreements
between January 1, 2006 and December 31,
2006, with a scheduled in-service date no
later than December 31, 2007, or (ii) wind
generating turbines subject to a wind turbine
procurement contract executed prior to
December 31, 2005, for delivery through
2007.
1. Wind generating plants are required to
remain in-service during three-phase faults
with normal clearing (which is a time period
of approximately 4–9 cycles) and single line
to ground faults with delayed clearing, and
subsequent post-fault voltage recovery to
prefault voltage unless clearing the fault
effectively disconnects the generator from the
system. The clearing time requirement for a
three-phase fault will be specific to the wind
generating plant substation location, as
determined by and documented by the
transmission provider. The maximum
clearing time the wind generating plant shall
be required to withstand for a three-phase
fault shall be 9 cycles at a voltage as low as
0.15 p.u., as measured at the high side of the
wind generating plant step-up transformer
(i.e. the transformer that steps the voltage up
to the transmission interconnection voltage
or ‘‘GSU’’), after which, if the fault remains
following the location-specific normal
clearing time for three-phase faults, the wind
generating plant may disconnect from the
transmission system.
2. This requirement does not apply to
faults that would occur between the wind
generator terminals and the high side of the
GSU or to faults that would result in a
voltage lower than 0.15 per unit on the high
side of the GSU serving the facility.
3. Wind generating plants may be tripped
after the fault period if this action is intended
as part of a special protection system.
4. Wind generating plants may meet the
LVRT requirements of this standard by the
performance of the generators or by installing
additional equipment (e.g., Static VAr
Compensator, etc.) within the wind
generating plant or by a combination of
generator performance and additional
equipment.
5. Existing individual generator units that
are, or have been, interconnected to the
network at the same location at the effective
date of the Appendix G LVRT Standard are
exempt from meeting the Appendix G LVRT
Standard for the remaining life of the existing
generation equipment. Existing individual
generator units that are replaced are required
to meet the Appendix G LVRT Standard.
Post-Transition Period LVRT Standard
All wind generating plants subject to FERC
Order No. 661 and not covered by the
transition period described above must meet
the following requirements:
1. Wind generating plants are required to
remain in-service during three-phase faults
with normal clearing (which is a time period
of approximately 4–9 cycles) and single line
PO 00000
Frm 00021
Fmt 4700
Sfmt 4700
75015
to ground faults with delayed clearing, and
subsequent post-fault voltage recovery to
prefault voltage unless clearing the fault
effectively disconnects the generator from the
system. The clearing time requirement for a
three-phase fault will be specific to the wind
generating plant substation location, as
determined by and documented by the
transmission provider. The maximum
clearing time the wind generating plant shall
be required to withstand for a three-phase
fault shall be 9 cycles after which, if the fault
remains following the location-specific
normal clearing time for three-phase faults,
the wind generating plant may disconnect
from the transmission system. A wind
generating plant shall remain interconnected
during such a fault on the transmission
system for a voltage level as low as zero volts,
as measured at the high voltage side of the
wind GSU.
2. This requirement does not apply to
faults that would occur between the wind
generator terminals and the high side of the
GSU.
3. Wind generating plants may be tripped
after the fault period if this action is intended
as part of a special protection system.
4. Wind generating plants may meet the
LVRT requirements of this standard by the
performance of the generators or by installing
additional equipment (e.g., Static VAr
Compensator) within the wind generating
plant or by a combination of generator
performance and additional equipment.
5. Existing individual generator units that
are, or have been, interconnected to the
network at the same location at the effective
date of the Appendix G LVRT Standard are
exempt from meeting the Appendix G LVRT
Standard for the remaining life of the existing
generation equipment. Existing individual
generator units that are replaced are required
to meet the Appendix G LVRT Standard.
ii. Power Factor Design Criteria (Reactive
Power)
A wind generating plant shall maintain a
power factor within the range of 0.95 leading
to 0.95 lagging, measured at the Point of
Interconnection as defined in this LGIA, if
the Transmission Provider’s System Impact
Study shows that such a requirement is
necessary to ensure safety or reliability. The
power factor range standard can be met by
using, for example, power electronics
designed to supply this level of reactive
capability 606 (taking into account any
limitations due to voltage level, real power
output, etc.) or fixed and switched capacitors
if agreed to by the Transmission Provider, or
a combination of the two. The
Interconnection Customer shall not disable
power factor equipment while the wind plant
is in operation. Wind plants shall also be able
to provide sufficient dynamic voltage support
in lieu of the power system stabilizer and
automatic voltage regulation at the generator
excitation system if the System Impact Study
shows this to be required for system safety
or reliability.
iii. Supervisory Control and Data Acquisition
(SCADA) Capability
The wind plant shall provide SCADA
capability to transmit data and receive
instructions from the Transmission Provider
E:\FR\FM\19DER1.SGM
19DER1
75016
Federal Register / Vol. 70, No. 242 / Monday, December 19, 2005 / Rules and Regulations
to protect system reliability. The
Transmission Provider and the wind plant
Interconnection Customer shall determine
what SCADA information is essential for the
proposed wind plant, taking into account the
size of the plant and its characteristics,
location, and importance in maintaining
generation resource adequacy and
transmission system reliability in its area.
Appendix C
[Note: These provisions to be adopted as
APPENDIX 7 to the LGIP]
Appendix 7 —Interconnection
Procedures for a Wind Generating Plant
Appendix 7 sets forth procedures specific
to a wind generating plant. All other
requirements of this LGIP continue to apply
to wind generating plant interconnections.
A. Special Procedures Applicable to Wind
Generators
The wind plant Interconnection Customer,
in completing the Interconnection Request
required by section 3.3 of this LGIP, may
provide to the Transmission Provider a set of
preliminary electrical design specifications
depicting the wind plant as a single
equivalent generator. Upon satisfying these
and other applicable Interconnection Request
conditions, the wind plant may enter the
queue and receive the base case data as
provided for in this LGIP.
No later than six months after submitting
an Interconnection Request completed in this
manner, the wind plant Interconnection
Customer must submit completed detailed
electrical design specifications and other data
(including collector system layout data)
needed to allow the Transmission Provider to
complete the System Impact Study.
Joseph T. Kelliher, Chairman, dissenting in
part:
I vote for this order because it constitutes
an improvement over the final rule. I agree
with the Commission’s decision to grant
rehearing with respect to the low voltage
ride-through (LVRT) provisions and to adopt
the joint recommendation of NERC and
AWEA. As the order points out, by adopting
a definitive, uniform, LVRT standard, the
Commission ‘‘provide[s] certainty’’ to the
industry and ‘‘ensure[s] that reliability is
maintained and NERC planning standards are
met.’’ 1
Unfortunately, the Commission’s decision
on LVRT contrasts with its decision to
exempt wind generators from compliance
with the same power factor standard as all
other generators. The Commission requires
all non-wind generators to maintain a power
factor within the range of 0.95 leading to 0.95
lagging, which NERC has determined to be
‘‘within a range required by Good Utility
Practice.’’ 2 Order No. 661, however, singles
out wind generators for special treatment by
exempting them from meeting the standard
power factor requirement unless the
Transmission Provider demonstrates in the
System Impact Study that reactive power
capability is necessary to ensure the safety or
1 Order
2 Order
at P34.
No. 2003 at P541.
VerDate Aug<31>2005
17:05 Dec 16, 2005
Jkt 208001
reliability of the transmission system. In my
view, exempting only wind generators from
the power factor standard does not provide
certainty to the industry, results in an undue
preference for wind generators and does not
adequately ensure that reliability of the
transmission system is maintained.
Section 205 of the Federal Power Act
broadly precludes public utilities, in any
transmission or sale subject to the
Commission’s jurisdiction, from ‘‘mak[ing] or
grant[ing] any undue preference or advantage
to any person or subject[ing] any person to
any undue prejudice or
disadvantage. * * *’’ 3 In my view, Order No.
661 gives preferential treatment to wind
generators, since it exempts wind generators
from meeting the same power factor
requirement as all other non-wind generators.
The issue is whether the preferential
treatment afforded to wind generators is
undue.
I do not believe that either the record or
the explanation offered in this order provides
a basis for giving preferential treatment to
wind generators when it comes to meeting
the power factor requirement. The order’s
attempt to justify discriminating in favor of
wind generators as an accommodation for
‘‘technical differences’’ 4 is not convincing.
The only ‘‘technical’’ difference identified is
the assertion that compliance with reactive
power capability is more expensive for wind
generators than for other generator
resources.5 While one can understand why
wind generators would like to be relieved of
the added cost of complying with the same
power factor standard as all other non-wind
generators, I fail to see how the desire to
avoid incurring the costs of complying with
the Commission’s standardized power factor
requirement constitutes a technological
difference warranting discriminatory
treatment.
Equally troubling, I disagree with the
Commission’s decision to brush aside the
concerns raised by NERC and other protesters
that the Commission has ‘‘lowered the bar’’
for reliability by shifting the burden to the
Transmission Provider to justify the need for
wind generators to comply with the same
power factor requirement as non-wind
generators. I find little comfort in the
Commission’s view that any reliability
concerns can be addressed in the System
Impact Study if the Transmission Provider
proves that a wind generator’s compliance
with the reactive power factor standard is
necessary. In my view, shifting the burden to
Transmission Providers to make such a
showing simply cannot be reconciled with
the approach taken by the Commission in
Order No. 2003 which presumes the need for
all generators to comply with power factor
requirement under ‘‘Good Utility Practice.’’ 6
As a result, I would have granted rehearing
and returned to the approach proposed by
the Commission in the NOPR of requiring all
3 16
U.S.C. 824d(b).
at P45.
5 Id. (‘‘One of these [technical] differences is that
for wind plants, reactive power capability is a
significant added cost, while it is not a significant
additional cost for traditional generators.’’).
6 Order No. 2003 at PP541–42.
4 Order
PO 00000
Frm 00022
Fmt 4700
Sfmt 4700
generators to meet the same power factor
standard absent a waiver by the Transmission
Provider. Accordingly, I dissent in part from
the order.
Joseph T. Kelliher.
[FR Doc. 05–24173 Filed 12–16–05; 8:45 am]
BILLING CODE 6717–01–P
DEPARTMENT OF HEALTH AND
HUMAN SERVICES
Food and Drug Administration
21 CFR Part 520
Oral Dosage Form New Animal Drugs;
Moxidectin Gel; Moxidectin and
Praziquantel Gel
AGENCY:
Food and Drug Administration,
HHS.
ACTION:
Final rule.
SUMMARY: The Food and Drug
Administration (FDA) is amending the
animal drug regulations to reflect
approval of two supplemental new
animal drug applications (NADAs) filed
by Fort Dodge Animal Health, Division
of Wyeth. The supplemental NADAs
provide for oral use of moxidectin gel or
moxidectin and praziquantel gel in
horses and ponies for the treatment and
control of two additional species of
small strongyles.
DATES: This rule is effective December
19, 2005.
FOR FURTHER INFORMATION CONTACT:
Melanie R. Berson, Center for Veterinary
Medicine (HFV–110), Food and Drug
Administration, 7500 Standish Pl.,
Rockville, MD 20855, 301–827–7543, email: mberson@cvm.fda.gov.
SUPPLEMENTARY INFORMATION: Fort
Dodge Animal Health, Division of
Wyeth, 800 Fifth St. NW., Fort Dodge,
IA 50501, filed a supplement to NADA
141–087 for QUEST (moxidectin 2.0%)
Gel and to NADA 141–216 for QUEST
Plus (moxidectin 2.0%/praziquantel
12.5%) Gel. Both products are used for
the treatment and control of various
species of internal parasites in horses
and ponies. The supplements provide
for the addition of two new species of
adult small strongyles to product
labeling. The supplemental NADAs are
approved as of November 23, 2005, and
21 CFR 520.1452 and 520.1453 are
amended to reflect the approval. The
basis of approval is discussed in the
freedom of information summaries.
In accordance with the freedom of
information provisions of 21 CFR part
20 and 21 CFR 514.11(e)(2)(ii),
summaries of safety and effectiveness
data and information submitted to
support approval of these applications
E:\FR\FM\19DER1.SGM
19DER1
Agencies
[Federal Register Volume 70, Number 242 (Monday, December 19, 2005)]
[Rules and Regulations]
[Pages 75005-75016]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 05-24173]
=======================================================================
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
Federal Energy Regulatory Commission
18 CFR Part 35
[Docket No. RM05-4-001; Order No. 661-A]
Interconnection for Wind Energy
Issued December 12, 2005.
AGENCY: Federal Energy Regulatory Commission, DOE.
ACTION: Order on rehearing and clarification.
-----------------------------------------------------------------------
SUMMARY: The Federal Energy Regulatory Commission is granting in part
and denying in part the requests for rehearing and clarification of its
Final Rule on Interconnection for Wind Energy, Order No. 661. Order No.
661 requires public utilities that own, control, or operate facilities
for transmitting electric energy in interstate commerce to append to
their standard large generator interconnection procedures and large
generator interconnection agreements in their open access transmission
tariffs standard procedures and technical requirements for the
interconnection of large wind generation.
DATES: Effective Date: Changes made to Order No. 661 in this order on
rehearing and clarification will become effective on January 18, 2006.
FOR FURTHER INFORMATION CONTACT:
Bruce A. Poole (Technical Information), Office of Markets, Tariffs and
Rates, Federal Energy Regulatory Commission, 888 First Street, NE.,
Washington, DC 20426. (202) 502-8468.
G. Patrick Rooney (Technical Information), Office of Markets, Tariffs
and Rates, Federal Energy Regulatory Commission, 888 First Street, NE.,
Washington, DC 20426. (202) 502-6205.
P. Kumar Agarwal (Technical Information), Office of Markets, Tariffs
and Rates, Federal Energy Regulatory Commission, 888 First Street, NE.,
Washington, DC 20426. (202) 502-8923.
LaChelle Brooks (Technical Information), Office of Markets, Tariffs and
Rates, Federal Energy Regulatory Commission, 888 First Street, NE.,
Washington, DC 20426. (202) 502-6522.
Jeffery S. Dennis (Legal Information), Office of the General Counsel,
Federal Energy Regulatory Commission, 888 First Street, NE.,
Washington, DC 20426. (202) 502-6027.
SUPPLEMENTARY INFORMATION:
Order No. 661-A; Order on Rehearing and Clarification
1. On June 2, 2005, the Commission issued Order No. 661, the Final
Rule on Interconnection for Wind Energy (Final Rule).\1\ Several
entities have filed timely requests for rehearing and clarification of
the Final Rule.\2\ In this order, the Commission grants in part and
denies in part the requests for rehearing and clarification.
---------------------------------------------------------------------------
\1\ Interconnection for Wind Energy, Order No. 661, 70 FR 34993
(June 16, 2005), FERC Stats. & Regs. ] 31,186 (2005) (Final Rule);
see also Order Granting Extension of Effective Date and Extending
Compliance Date, 70 FR 47093 (Aug. 12, 2005), 112 FERC ] 61,173
(2005).
\2\ Those entities requesting rehearing and/or clarification,
and the acronyms used to refer to them in this order, are listed in
Appendix A to this order.
---------------------------------------------------------------------------
I. Background
2. In Order No. 2003,\3\ the Commission adopted standard procedures
and a standard agreement for the interconnection of large generation
facilities. The Commission required public utilities that own, control,
or operate facilities for transmitting electric energy in interstate
commerce to file revised Open Access Transmission Tariffs (OATTs)
containing these standard provisions, and use them to provide
interconnection service to generating facilities having a capacity of
more than 20 megawatts.
---------------------------------------------------------------------------
\3\ Standardization of Generator Interconnection Agreements and
Procedures, Order No. 2003, 68 FR 49845 (Aug. 19, 2003), FERC Stats.
& Regs., Regulations Preambles ] 31,146 (2003) (Order No. 2003),
order on reh'g, 69 FR 15,932 (Mar. 24, 2004), FERC Stats & Regs.,
Regulations Preambles ] 31,160 (2004) (Order No. 2003-A), order on
reh'g, 70 FR. 265 (January 4, 2005), FERC Stats & Regs., Regulations
Preambles ] 31,171 (2004) (Order No. 2003-B), order on reh'g, 70 FR
37661 (June 30, 2005), FERC Stats. & Regs. ] 31,190 (2005) (Order
No. 2003-C); see also Notice Clarifying Compliance Procedures, 106
FERC ] 61,009 (2004).
---------------------------------------------------------------------------
3. In Order No. 2003-A, on rehearing, the Commission noted that the
standard interconnection procedures and agreement were based on the
needs of traditional generation facilities and that a different
approach might be more appropriate for generators relying on other
technologies, such as wind plants.\4\ Accordingly, the Commission
granted certain clarifications, and also added a blank Appendix G to
the standard Large Generation Interconnection Agreement (LGIA) for
future adoption of requirements specific to other technologies.\5\
---------------------------------------------------------------------------
\4\ Order No. 2003-A at P 407, n.85.
\5\ Id.
---------------------------------------------------------------------------
4. The Commission issued a Notice of Proposed Rulemaking (NOPR)
that proposed technical standards applicable to the interconnection of
large wind generating plants \6\ to be included in Appendix G of the
LGIA.\7\ We proposed the standards in light of our findings in Order
No. 2003-A noted above and in response to a petition submitted by the
American Wind Energy Association (AWEA).\8\ Specifically, the
Commission proposed to establish uniform standards in Appendix G that
would require large wind plants seeking to interconnect to the grid to:
(1) Demonstrate low voltage ride-through capability; in other words,
show that the plant can remain on line during voltage disturbances up
to specified time periods and associated voltage levels; (2) have
supervisory control and data acquisition (SCADA) capability to transmit
data and receive instructions from the Transmission Provider; and (3)
maintain a power factor within the range of 0.95 leading
[[Page 75006]]
to 0.95 lagging, measured at the high voltage side of the substation
transformers. The Commission proposed to permit the Transmission
Provider to waive the low voltage ride-through requirement on a
comparable and not unduly discriminatory basis. We proposed to permit
the Transmission Provider to waive or defer compliance with the power
factor requirement where it is not necessary. The Commission did not
propose to adopt a proposal by AWEA to allow a wind generator to
``enter the interconnection queue and conduct its own Feasibility
Study, having obtained the information necessary to do so upon paying
the initial deposit and submitting its interconnection application''
(referred to as ``self-study'' provisions).\9\ The Commission did,
however, ask for comments on how to balance the need of wind generators
to obtain certain data from the Transmission Provider before completing
their Interconnection Requests with the need to protect critical energy
infrastructure information and commercially sensitive data against
unwarranted disclosure.
---------------------------------------------------------------------------
\6\ Large wind generating plants are those with an output rated
at more than 20 MW at the point of interconnection. The
interconnection requirements for small generators rated at 20 MW or
less are set forth in Standardization of Small Generator
Interconnection Agreements and Procedures, Order No. 2006, 70 FR
34190 (June 13, 2005), FERC Stats. & Regs. ] 31,180 (2005), reh'g
pending.
\7\ See Interconnection for Wind Energy and Other Alternative
Technologies, Notice of Proposed Rulemaking, 70 FR 4791 (Jan. 31,
2005), 110 FERC ] 61,036 (2005) (NOPR).
\8\ See Petition for Rulemaking or, in the Alternative, Request
for Clarification of Order No. 2003-A, and Request for Technical
Conference of the American Wind Energy Association (May 20, 2004),
filed in Docket Nos. RM02-1-005 and PL04-15-000 (AWEA Petition).
\9\ See AWEA Petition at 13.
---------------------------------------------------------------------------
5. In the Final Rule, the Commission adopted final standard
procedures and technical requirements for the interconnection of large
wind plants in Appendix G, and required all public utilities that own,
control, or operate facilities for transmitting electric energy in
interstate commerce to append Appendix G to the Large Generator
Interconnection Procedures (LGIPs) and LGIAs in their OATTs. As
described in more detail below, the Commission adopted provisions
establishing standards for low voltage ride-through and power factor
design criteria, and requiring that wind plants meet those standards if
the Transmission Provider shows, in the System Impact Study, that they
are needed to ensure the safety or reliability of the transmission
system. Additionally, the Appendix G adopted by the Commission included
a SCADA requirement applicable to all wind plants. Finally, as
described in more detail below, the Commission adopted in Appendix G to
the LGIP limited special interconnection procedures applicable to wind
plants.
II. Requests for Rehearing and Clarification and Commission Conclusions
A. Low Voltage Ride-Through Provisions
6. In the Final Rule, the Commission adopted a low voltage ride-
through standard, but provided that a wind plant is required to meet
the standard only if the Transmission Provider shows, in the System
Impact Study, that low voltage ride-through capability is needed to
ensure safety or reliability. The standard (adopted in Figure 1 of
Appendix G to the LGIA), if applicable, requires the wind plant to stay
online for specified time periods and at associated voltage levels
where there is a disturbance on the transmission system. The Final Rule
requires that the required voltage levels be measured at the Point of
Interconnection.
7. Several entities requested rehearing of various aspects of the
low voltage ride-through requirement and standard included in the Final
Rule, including: (1) Provisions that require low voltage ride-though
only when the System Impact Study shows that such capability is
necessary for safety or reliability; (2) the specific low voltage ride-
through standard adopted in the Final Rule; (3) the point of
measurement for the standard; and (4) arguments that Transmission
Providers should be permitted to adopt other provisions of the German
low voltage ride-through standard (which the Commission referenced in
the Final Rule).
8. However, as described in more detail below, NERC and AWEA
jointly requested that the Commission delay the effective date of the
Final Rule to give them time to resolve concerns expressed by NERC
regarding the low voltage ride-through provisions. The Commission
granted this extension, and on September 19, 2005, NERC and AWEA
submitted a joint report with recommended revisions.
1. Case-by-Case Application/Burden of Proof for Applying the Low
Voltage Ride-Through Standard
9. Prior to the NERC/AWEA joint report, several entities objected
on rehearing to the Final Rule's adoption of a low voltage ride-through
requirement on a case-by-case basis, placing the burden of proof on the
Transmission Provider to show that low voltage ride-through capability
is needed. ATC, EEI, NERC, NRECA/APPA, and SCE, among others, urged the
Commission to return to the approach in the NOPR, which would have
required low voltage ride-through for all wind plants unless waived by
the Transmission Provider on a not unduly discriminatory basis. ATC
noted that interconnection studies only consider a snapshot of the
transmission system, and do not take into account changes in the future
that may cause a need for low voltage ride-through capability to ensure
reliability. ATC, as well as EEI and SCE, argued that under the case-
by-case approach adopted in the Final Rule, Transmission Providers will
need to perform additional analyses to determine if a reliability need
will exist over the life of the wind plant. SCE, for example, noted
that while a particular System Impact Study may not conclusively
demonstrate that low voltage ride-through is needed at that time, if
other generation projects are built, the first wind plant may come to
need low voltage ride-through. According to various entities, the
additional analyses needed to take these scenarios into account will
increase the time, cost and complexity of wind plant interconnections
and could be a barrier to their development.\10\
---------------------------------------------------------------------------
\10\ New York ISO asserts that the case-by-case approach could
lead to acute problems in New York, where it has received
interconnection applications from wind plants totaling over 5000 MW
of generation. According to New York ISO, conducting case-by-case
reviews for each of these projects could greatly complicate the
study process and result in substantial delays.
---------------------------------------------------------------------------
10. Furthermore, ATC asserted that the case-by-case approach
imposes the responsibility for resolving reliability concerns that
arise in the future on the Transmission Provider because wind
generating plants cannot be retrofitted with low voltage ride-through
capability. Similarly, NRECA/APPA argued that this approach unduly
discriminates in favor of wind plants in that low voltage ride-through
capability may not be ``necessary'' (and therefore required) for a
specific plant because other generators or Transmission Providers can
``make up the difference.'' \11\ ATC also contended that the case-by-
case approach may require the Transmission Provider to incur capital
costs that should have been incurred by the wind plant.
---------------------------------------------------------------------------
\11\ Request for Rehearing of NRECA/APPA at 6.
---------------------------------------------------------------------------
11. EEI and NU argued that the case-by-case approach adopted by the
Commission in the Final Rule ``lowers the bar for reliability.'' \12\
NERC similarly asserted that requiring Transmission Providers to
justify common elements of good utility practice on a case-by-case
basis is unwise and may deter Transmission Providers from implementing
and following good utility practice.\13\ Southern Company states that
the Transmission Provider, as the entity responsible for maintaining
reliability, should not bear the burden of proof to establish what is
required to maintain system reliability. Southern Company states that
it supports the Commission's statement that Transmission Providers
should not be permitted to require wind plants to install costly
equipment that is not needed for reliability, but argues
[[Page 75007]]
that the burden of proof should be shifted, and the System Impact Study
should establish that such equipment is not required. Also, NRECA/APPA
argued that the case-by-case approach imposes unreasonable reliability
risks, and effectively voids the requirement that wind plants have low
voltage ride-through capability ``in a broad range of circumstances.''
\14\
---------------------------------------------------------------------------
\12\ Request for Rehearing of EEI at 8.
\13\ New York ISO states that it adopts NERC's position on this
issue.
\14\ Request for Rehearing of NRECA/APPA at 6.
---------------------------------------------------------------------------
12. Those requesting rehearing raised several other arguments
regarding the case-by-case approach and burden of proof for applying
the low voltage ride-through standard. NERC believed that the case-by-
case approach could unintentionally create a ``patchwork'' of varying
requirements. EEI and NU also suggested that requiring a showing of
need may introduce prolonged uncertainties into the interconnection
process if parties disagree as to the study assumptions. SCE asserted
that rather than limiting opportunities for undue discrimination, the
requirement of a showing of need could result in discriminatory
treatment in areas with large amounts of wind generation because
projects lower in the queue may be responsible for additional costs
since the need for low voltage ride-through could not be demonstrated
for earlier projects. EEI contended that Order No. 2003 already
contains provisions allowing the parties to an interconnection to
exercise their discretion in complying with system reliability
obligations, and that there is no evidence of problems with these
procedures that justifies such a significant departure from them in the
Final Rule. Further, EEI argued that the Final Rule was a significant
departure from the NOPR and that the Commission should not adopt it
without providing an opportunity for comments on it. Finally, NRECA/
APPA argued that the Commission has not explained how this approach is
consistent with NERC and WECC standards.
2. Specific Low Voltage Ride-Through Standard
13. Certain requests for rehearing and clarification also addressed
the specific low voltage ride-through standard adopted by the
Commission in the Final Rule. In its request for rehearing, NERC
asserted that the standard in Figure 1 of the Final Rule is not
appropriate. More specifically, NERC contended that Figure 1, by
allowing a wind plant to disconnect from the transmission system when
the voltage drops below 15 percent of the nominal voltage, could result
in violation of NERC Reliability Standard TPL-002-0. This standard
requires transmission planners to ensure that the system will remain
stable and within applicable thermal and voltage ratings, with no loss
of demand or curtailment of firm transfers, where there is a normally
cleared fault on a single element, which is typically four to eight
cycles or 0.067 to 0.133 seconds (67 to 133 milliseconds). According to
NERC, a fault occurring on a transmission line near a wind plant could
cause the voltage at that point to drop to zero for this clearing time.
NERC stated that because Figure 1 would allow the wind plant to
disconnect when the voltage drops below 15 percent of the nominal
voltage, the loss of the single grid element (the transmission line)
would be compounded by the loss of the real power (and any reactive
power) produced by the wind plant. This ``double contingency event''
(loss of both the transmission line and wind plant) violates
Reliability Standard TPL-002-0, NERC asserted.
14. To remedy this problem, NERC requested that the Commission
simply require wind plants to meet NERC and regional reliability
council requirements.\15\ Alternatively, NERC argued that the rule
should be modified to require wind plants to remain connected through a
normally cleared single line to ground or three phase fault.
Specifically, NERC asserted that Figure 1 should be altered to require
a wind plant to remain online for 0.167 seconds (167 milliseconds), or
ten cycles, if voltage at the high side of the wind plant step-up
transformer is reduced to zero. After 0.167 seconds (167 milliseconds),
but before 0.625 seconds (625 milliseconds), NERC argued that Figure 1
should require the wind plant to stay connected as long at the voltage
is at or above 15 percent of the nominal voltage. NERC contended that
these modifications would reduce the risk to the reliability of the
electric system to an acceptable level.\16\
---------------------------------------------------------------------------
\15\ ISO-NE argued that the Commission should have required wind
plants to be subject to the same system performance standards that
are applied to other generating technologies.
\16\ ISO-NE also suggested that, if the Commission adopted a low
voltage ride-through standard, it be modified to require the wind
plant to be connected at zero voltage for ``a time period associated
with the typical clearing time of a normal design contingency
fault.'' Request for Rehearing of ISO-NE at 4.
---------------------------------------------------------------------------
15. Similarly, NU asserted that wind plants should be required to
``remain on-line for all faults cleared by normal operation of all
protective equipment unless clearing the fault * * * isolates the plant
from the rest of the grid.'' \17\ According to NU, this change would
require generators to have low voltage ride-through capability down to
zero percent of the nominal voltage at the Point of Interconnection.
CenterPoint also contend that wind plants should be required to
maintain low voltage ride-through capability down to zero percent of
the rated line voltage 150 milliseconds (.150 seconds) (the time
generally needed for the transmission system protective equipment to
clear the fault). NU and CenterPoint argued that this change would
reduce the likelihood that a low voltage event would escalate to a
cascading outage or voltage collapse. NU also asserted that this
requirement is similar to those applicable to other generators, and
could be achieved by wind turbines that are currently available. NU
stated that the standard adopted in the Final Rule would threaten
reliability by allowing a wind plant to reduce output, or trip offline,
simply due to a typical system fault.
---------------------------------------------------------------------------
\17\ Request for Rehearing of NU at 5.
---------------------------------------------------------------------------
16. NRECA/APPA also objected to the low voltage ride-through
standard adopted in the Final Rule. Specifically, they contended that
the Final Rule should not have established the low voltage ride-through
curve as an absolute standard, and instead should have permitted
Transmission Providers to adopt an alternative curve (subject to review
by the Commission if there is a dispute) when the System Impact Study
shows that it is necessary. ISO-NE, going further, requested that if
the Commission adopted a low voltage ride-through standard, it should
be only a guideline for wind turbine manufacturers. NRECA/APPA asserted
that the Final Rule did not conclude that the low voltage ride-through
standard will protect reliability or address the technical concerns
raised by comments, and, by stating that the Commission might consider
an alternative low voltage ride-through standard, recognizes that it
may not be adequate to preserve reliability in all circumstances.
Alternatively, NRECA/APPA asked that the Commission clarify that
Transmission Providers may support variations from the low voltage
ride-through curve in the Final Rule, based on local and subregional
reliability conditions, under the three variation standards adopted in
the Final Rule.
17. EEI asserted that the technical challenges presented by wind
generation are being considered by the industry worldwide, and that
many international standards differ from the Commission's Final Rule.
Both EEI and SCE objected to the specific low voltage ride-through
standard through comparison to the German
[[Page 75008]]
interconnection guidelines. Particularly, EEI noted that the German
grid code requires wind plants to remain connected to the grid
following a fault that results in the voltage at the Point of
Interconnection dropping to 15 percent of the nominal voltage for as
long as 0.15 seconds. According to EEI, revisions to the German grid
code are nearing completion that will require wind plants to remain
connected to the transmission system following a fault that drops the
voltage at the Point of Interconnection to zero percent of the nominal
voltage for as long at 0.15 seconds. Further, EEI reported that the
Hydro-Qu[eacute]bec requirements for wind farm interconnection are
stricter than the Commission's Final Rule; they require wind plants to
ride through a fault resulting in a voltage drop to zero percent of
nominal voltage for as long as 0.15 seconds. Finally, EEI noted that
Ireland requires wind plants to stay online after a fault that drops
the voltage to 15 percent of nominal voltage for as long as 0.15
seconds. SCE additionally asserted that the requirement that low
voltage ride-through be shown to be necessary in the System Impact
Study conflicts with the German wind interconnection guidelines because
those guidelines assume that all generation will meet the low voltage
ride-through standard. SCE stated that the Final Rule should adopt low
voltage ride-through capability as a governing standard, with
exceptions approved by the governing technical body (NERC or the
Western Electricity Coordinating Council (WECC), a regional reliability
council), as in the German standard.
18. In the Final Rule, the Commission stated that ``the low voltage
ride-through requirement, and the time periods and associated voltage
levels set forth in Appendix G, Figure 1, apply to three-phase
faults.'' ATC sought clarification as to whether the low voltage ride-
through requirement applied only to three-phase faults. Assuming that
is the case, ATC asked whether there was a requirement for single-phase
and double-phase faults.
3. Point of Measurement for the Low Voltage Ride-Through Standard
19. NERC argued on rehearing that because the Point of
Interconnection may be some distance from a wind plant, the plant might
actually disconnect at voltages higher than 15 percent of the nominal
voltage at the high side of the wind plant step-up transformer.
According to NERC, this could create a further risk of a double
contingency event.\18\ To avoid this risk, NERC contended that low
voltage ride-through capability should be measured at the high voltage
terminal of the wind plant step-up transformer. Southern Company stated
that a revision to section A.i.2 of the LGIA Appendix G was necessary
to reflect the Commission's decision in the Final Rule to adopt the
Point of Interconnection as the measurement point.
---------------------------------------------------------------------------
\18\ See supra, P 13.
---------------------------------------------------------------------------
4. Adoption of Other Provisions From the German Standards
20. SCE noted that while the Final Rule adopted a low voltage ride-
through standard based on the German wind interconnection guidelines,
the Commission did not adopt the related requirements in the German
guidelines. It noted several provisions of the German guidelines that
it stated go hand-in-hand with the low voltage ride-through
standard.\19\ SCE asked the Commission to clarify that Transmission
Providers may implement these other guidelines in the German standard.
---------------------------------------------------------------------------
\19\ See Request for Rehearing and Clarification of SCE at 9-10.
---------------------------------------------------------------------------
5. NERC/AWEA Recommended Revisions to Low Voltage Ride-Through
Provisions
21. As noted above, NERC filed a request for rehearing of the Final
Rule contending, in part, that the specific low voltage ride-through
standard adopted by the Commission would permit violations of a NERC
system performance standard.\20\ On August 4, 2005, NERC and AWEA filed
a request to extend the effective date of the Final Rule to allow for
discussions to resolve the reliability concerns expressed by NERC. They
committed to submitting to the Commission a joint final report on their
discussions. On August 5, 2005, the Commission issued an order granting
this request.\21\
---------------------------------------------------------------------------
\20\ See supra, P 13.
\21\ Interconnection for Wind Energy, 70 FR 47093 (Aug. 12,
2005), 112 FERC ] 61,173 (2005).
---------------------------------------------------------------------------
22. On September 19, 2005, NERC and AWEA submitted their joint
final report, which recommended revisions to the low voltage ride-
through provisions of the Final Rule. They state that the recommended
revisions are supported by the NERC Planning Committee and AWEA
members. NERC states that the concerns expressed in its request for
rehearing will be resolved if the Commission adopts the recommended
revisions.
23. Specifically, NERC and AWEA recommend a different low voltage
ride-through section to be inserted in Appendix G. The recommended
provisions include a transition period standard, which would apply to
wind plants that either: (a) Have interconnection agreements signed and
filed with the Commission, filed with the Commission in unexecuted
form, or filed with the Commission as non-conforming agreements between
January 1, 2006 and December 31, 2006, with a scheduled in-service date
no later than December 31, 2007; or (b) involve wind turbines subject
to a procurement contract executed before December 31, 2005 for
delivery through 2007. During this transition period, wind plants would
be required to ride through low voltage events down to 0.15 per unit
for normal clearing times up to a maximum of nine cycles.
24. Following this transition period, the NERC/AWEA proposal would
require wind plants to ride through low voltage events down to a zero
voltage level for ``location-specific'' clearing times up to a maximum
of nine cycles. If the fault on the transmission system remained after
this clearing time, the joint recommendation would permit the wind
plant to disconnect from the system.
25. Under the joint recommendation of NERC and AWEA, during both
the transition period and after, low voltage ride-through capability
would be required for all new wind plant interconnections, instead of
only when the System Impact Study shows that such capability is needed
for safety or reliability, as in the Final Rule. Additionally, in both
cases the point of measurement for the requirement would be at the high
side of the wind plant step-up transformer, instead of at the Point of
Interconnection, as in the Final Rule. NERC and AWEA also recommend
eliminating Figure 1 during both the transition period and after the
transition period because the low voltage ride-through standard
described in their Joint Report replaces the voltage trace represented
by Figure 1.
26. Finally, NERC and AWEA recommend limiting the variations to the
low voltage ride-through provisions that were permitted by the Final
Rule. The Final Rule permits Transmission Providers to justify
variations between their pro forma tariff and the Final Rule Appendix G
based on the regional reliability, the ``consistent with or superior
to,'' or the independent entity variation standards in Order No.
2003.\22\ NERC and AWEA recommend that variations to their proposed low
voltage ride-through provisions be permitted on an interconnection-wide
basis only, reasoning that such a limitation is appropriate because the
provisions are intended to satisfy a NERC reliability
[[Page 75009]]
standard, and because wind generators could incur significant
additional costs if they had to meet many different standards. NERC and
AWEA note that limiting variations would not restrict the ability to
request a deviation in a specific non-conforming agreement filed with
the Commission (as opposed to a variation built into a pro forma
tariff).
---------------------------------------------------------------------------
\22\ Final Rule at P 107, 109.
---------------------------------------------------------------------------
27. The Commission issued notice of the NERC/AWEA joint report on
September 21, 2005, and provided interested parties with the
opportunity to submit comments on or before October 3, 2005. FPL
Energy, National Grid, New York ISO and PJM all filed comments
supporting the technical recommendations in the joint report.
28. National Grid also asks that the Commission make two
clarifications. First, it asks the Commission to clarify that while the
point of measurement for compliance with the low voltage ride-through
standard would be at the high side of the step-up transformer, the
point of measurement for reactive power would remain at the Point of
Interconnection. Second, National Grid requests that the nine cycle
maximum clearing time in the low voltage ride-through provision applies
only to three-phase faults. It says that single line-to-ground faults
are typically much longer than nine cycles, so a general, non-specified
standard is more appropriate for such faults.
29. New York ISO, while strongly supporting the technical aspects
of the NERC/AWEA joint recommendations, urges the Commission to reject
the proposal that variations to the low voltage ride-through provision
be permitted only on an interconnection-wide basis or through
individually-filed interconnection agreements. It argues that this
could hamper efforts to preserve reliability in individual regions, and
asserts that satisfying NERC planning standards is not sufficient to
preserve reliability because New York State, as well as other regions,
sometimes need more stringent reliability requirements than those of
NERC. New York ISO says that the Commission has viewed NERC's criteria
as being minimum reliability requirements, which individual regions may
exceed if necessary. Therefore, New York ISO argues that at a minimum,
the Commission should permit independent entities to seek variations
from the low voltage ride-through standards recommended by NERC and
AWEA.
30. Finally, New York ISO asks the Commission to clarify that,
assuming the NERC/AWEA recommendations are adopted, the ``filing date''
for purposes of the proposed transition period includes the date that
conforming interconnection agreements are fully and finally executed.
New York ISO notes that executed conforming agreements need not be
filed with the Commission. Therefore, it contends that the transition
period should apply to agreements executed within its timeframe but not
filed with the Commission.
Commission Conclusion on Low Voltage Ride-Through Provisions
31. The Commission grants rehearing with regard to the low voltage
ride-through provisions, and adopts the joint recommendation of NERC
and AWEA without modification. This provides a standard that will
ensure that wind plants are interconnected to the grid in a manner that
will not degrade system reliability. Furthermore, this standard
satisfies the reliability concerns expressed by NERC, and either
satisfies or renders moot many of the rehearing requests described
above, including those related to the case-by-case application of the
low voltage ride-through standard and point of measurement for the low
voltage ride-through standard. Additionally, the joint recommendation
also responds to the arguments on rehearing of EEI and SCE regarding
comparison to the German interconnection guidelines.
32. We are eliminating Figure 1 from Appendix G because the
standard we are adopting in Appendix G replaces that figure.
Accordingly, all references to Figure 1 in the preamble to the Final
Rule should be read to apply to the standard now described in Appendix
G.
33. We also adopt the NERC/AWEA proposal to permit variations to
the low voltage ride-through provisions of Appendix G only on an
interconnection-wide basis. The low voltage ride-through provisions we
adopt in this order on rehearing were crafted specifically, after
negotiation among the wind industry and NERC, to ensure that NERC
Reliability Standard TPL-002-0 is met in all regions. While other
interconnection standards may be more susceptible to variation among
Transmission Providers or independent entities, the close connection of
this standard to an industry-wide reliability standard persuades us
that limiting variations to those made on an interconnection-wide basis
will best ensure that reliability is protected. Accordingly, we reject
SCE's request that we clarify that Transmission Providers may implement
other guidelines from the German interconnection standard. Adoption of
other guidelines from the German standard on a Transmission Provider-
specific basis could result in varying requirements that may not meet
established reliability standards. For the same reasons, we also reject
New York ISO's assertion that the Commission should continue to permit
variations to the low voltage ride-through provisions under the three
variation standards in the Final Rule, and particularly the independent
entity variation. We note, however, that under section 1211 of the
Energy Policy Act of 2005, the State of New York ``may establish rules
that result in greater reliability within that State, as long as such
action does not result in lesser reliability outside the State than
that provided by the reliability standards.'' \23\ Therefore, the
Commission will consider proposed variations from the State of New York
under this statutory provision.
---------------------------------------------------------------------------
\23\ Energy Policy Act of 2005, Pub. L. 109-58, Sec. 1211, 119
Stat. 594, 945 (2005).
---------------------------------------------------------------------------
34. In response to the arguments of NRECA/APPA that the Final Rule
should have permitted Transmission Providers to adopt alternative low
voltage ride-through standards, and ISO-NE's contention that the
standard in the Final Rule should be only a guideline, we find that the
definitive standard we adopt here will provide certainty to wind
developers and manufacturers and ensure that reliability is maintained
and NERC planning standards are met. If another standard is necessary
for a specific wind plant interconnection to maintain reliability, a
non-conforming agreement may be filed with the Commission.
35. In response to ATC and National Grid, we clarify that the low
voltage ride-through provisions we are adopting apply to all types of
faults, not just to three-phase faults. The standard refers to three-
phase faults with normal clearing as well as single line to ground
faults with delayed clearing. In response to National Grid's specific
concern, we clarify that the nine cycle maximum clearing time expressed
in the low voltage ride-through provisions applies only to three-phase
faults. Single line to ground faults have typically much longer
clearing times, as National Grid notes, and the low voltage ride-
through provisions adopted here recognize this difference by
specifically referring to ``single line to ground faults with delayed
clearing.'' This non-specified standard is appropriate for those types
of faults.
B. Power Factor (Reactive Power) Provisions
36. In the Final Rule, the Commission adopted in Appendix G to the
LGIA a power factor standard applicable to
[[Page 75010]]
wind plants. The Final Rule provides that wind plants are required to
meet this standard only if the Transmission Provider shows, in the
System Impact Study, that reactive power capability is necessary to
ensure the safety or reliability of the transmission system. The
specific power factor standard in Appendix G to the LGIA, if
applicable, requires a wind plant to maintain a power factor within the
range of 0.95 leading to 0.95 lagging (hereinafter +/-0.95), to be
measured at the Point of Interconnection.
37. Requests for rehearing and/or clarification of these provisions
concern whether wind plants should have to maintain a required power
factor only where the System Impact Study shows that it is required for
reliability or safety, and whether the power factor standard and point
of measurement adopted by the Commission in the Final Rule are
appropriate.
1. Case-by-Case Application/Burden of Proof for Applying the Power
Factor Standard
38. Several entities object to the provisions in the Final Rule
that require wind plants to maintain the required power factor only
when the Transmission Provider, in the System Impact Study, shows that
it is necessary to ensure safety or reliability. NERC objects to this
approach because it may deter Transmission Providers from implementing
and following good utility practice and could create a ``patchwork'' of
varying requirements. NU argues that this approach ``lowers the bar for
reliability,'' and will add complexity, cost and delay to the generator
interconnection process because Transmission Providers will be required
to perform more studies to determine whether reactive power capability
is necessary for reliability or safety. Southern Company states that
the Transmission Provider, as the entity responsible for maintaining
reliability, should not bear the burden of proof to establish what is
required to maintain system reliability. It supports the Commission's
statement that Transmission Providers should not be permitted to
require wind plants to install costly equipment that is not needed for
reliability, but argues that the burden of proof should be shifted to
the generator.
39. NRECA/APPA notes that traditional generators are required to
meet the power factor standard not because reactive power is needed in
every case to preserve reliability, but instead because the
transmission system is dynamic and requires flexibility over time to
maintain reliability. They state that the need for reactive power in
the future under a variety of operating conditions cannot be determined
with perfect certainty in the System Impact Study. The case-by-case
approach, they contend, grants an undue preference to wind plants,
imposes risks to system reliability, and shifts costs to consumers and
other generating plants. The risk to system reliability is that the
Final Rule may only require a wind plant to provide reactive power
after other wind plants have been installed without such capability,
and that at that point the resources from that single plant may not be
enough to protect the transmission system. NRECA/APPA also asserts that
the case-by-case approach increases uncertainty, contrary to the
Commission's conclusion in the Final Rule, because each wind plant will
face different requirements based on the outcome of the System Impact
Study. Additionally, it contends that this approach creates more
opportunities for discrimination because it would permit wind plants to
be treated differently.
40. ATC contends that the Commission has offered no guidance as to
what power factor range would be acceptable if a reliability need is
not identified (and thus reactive power is not required), and whether
wind plants in this instance must operate within any particular
reactive power operating band. Similarly, NU expresses concern that
wind plants could operate at any power factor in the absence of a
showing of need in the System Impact Study, and thus avoid a physical
requirement for delivering power onto the transmission system.
According to ATC, the rule could be interpreted to permit wind plants
to operate at any power factor they choose. It claims that reactive
power is needed for each generator, and that each generator should be
obligated to operate within a range of power factors, regardless of
whether the transmission system as a whole needs additional reactive
power capability. ATC recommends that at a minimum, the Commission
require all wind plants to meet a power factor range of 0.95 leading to
1.0 (unity), and allow the Transmission Provider to require a range of
1.0 (unity) to 0.95 lagging if the System Impact Study shows that there
is a reliability need.
Commission Conclusion
41. The Commission will not modify the Final Rule to require wind
plants to meet the power factor standard without a showing by the
Transmission Provider, through the System Impact Study, that it is
needed for safety or reliability. The case-by-case approach to a
reliability needs assessment adopted in the Final Rule will not
threaten reliability, as several of those seeking rehearing argue. As
we noted in the Final Rule, if reactive power is necessary to maintain
the safety or reliability of the transmission system, the System Impact
Study performed by the Transmission Provider will establish that
need.\24\ We stated in the Final Rule, and reiterate here, that the
System Impact Study is the appropriate study for determining whether
reactive power capability is needed.\25\ Furthermore, we reasoned in
the Final Rule that requiring wind plants to maintain the power factor
standard only if the System Impact Study shows it to be necessary will
not only ensure that increased reliance on wind power will not degrade
system safety or reliability, but also will limit opportunities for
undue discrimination by ensuring that Transmission Providers do not
require costly equipment that is not necessary for reliability.\26\
---------------------------------------------------------------------------
\24\ Final Rule at P 51.
\25\ Id.
\26\ Id.
---------------------------------------------------------------------------
42. NERC states that the decision in Order No. 661 to use a case-
by-case approach may deter Transmission Providers from following Good
Utility Practice, and may have the unintended consequence of spawning a
patchwork of varying requirements. We agree with NERC that Transmission
Providers must follow Good Utility Practice when interconnecting all
generating plants, including wind plants, and that not following Good
Utility Practice when performing System Impact Studies could lead to
problems. However, the Commission points out that every Transmission
Provider is required under Order No. 2003 to follow Good Utility
Practice. Transmission Providers are required to complete a detailed
System Impact Study, and are required to ensure that NERC reliability
standards are met in all instances. This includes performing studies to
determine what is necessary to ensure that the interconnection of a
wind generating facility does not degrade grid reliability. The
Commission recognizes that the industry (and particularly NERC) is
continuing to address technical issues involved in the interconnection
of wind plants. If NERC through its stakeholders and Board approval
process develops a new standard, the Commission will entertain such a
standard. Finally, we disagree with NRECA/APPA's suggestion that the
Final Rule threatens the reliability of the transmission system because
it may require only wind plants later in the queue to provide reactive
power, which may not
[[Page 75011]]
be sufficient to protect the grid. The System Impact Study will take
into account the system's need for reactive power, both as it exists
today and under reasonable anticipated assumptions. NRECA/APPA has not
explained how assessing the need for reactive power through the System
Impact Study process will result in too little reactive power being
available in the future. Whenever a new generator is added to its
system, the Transmission Provider must complete a new System Impact
Study to ensure that reliability requirements are met; this may require
a new wind generator later in the queue to meet the reactive power
requirement.
43. We also reject arguments that the case-by-case approach is
inappropriate because of the dynamic nature of the transmission system.
The fact that the transmission system is constantly changing is not new
or unique to the study of wind plant interconnections. The studies that
are part of the interconnection process should take into account likely
circumstances that could occur on the Transmission Provider's system,
whether the studies are conducted in connection with a proposed wind
plant or another type of generating facility.
44. Furthermore, we are not persuaded that the approach adopted in
the Final Rule will result in additional studies, increased costs and
delays, and cost shifts. First, as noted previously, the System Impact
Study, as well as the other interconnection studies, should take into
account a variety of assumptions concerning anticipated transmission
system conditions. If additional or expanded studies are needed to
determine whether the power factor standard is necessary, the
Commission does not believe that the additional burden will outweigh
the cost considerations underlying the case-by-case approach. Finally,
although the case-by-case approach may result in some delay, we remind
the parties to a wind plant interconnection, like other
interconnections, that they are still required to meet the milestones
set forth in the LGIP. Any increased costs from completing expanded or
additional studies within the timeframe required by this rule will be
borne by the wind plant Interconnection Customer, as provided in Order
No. 2003, which will leave other generators and the Transmission
Provider unharmed.
45. The Commission also rejects arguments that the case-by-case
approach provides more opportunities for discrimination. As we noted in
the Final Rule Appendix G was adopted to take into account the
technical differences between wind plants and traditional generating
plants. One of these differences is that for wind plants, reactive
power capability is a significant added cost, while it is not a
significant additional cost for traditional generators. Given these
technical differences, treating wind plants differently with regard to
reactive power requirements is not unduly discriminatory or
preferential. Additionally, we note that the outcome of the System
Impact Study, which determines whether reactive power will be required,
can be challenged, which will serve to minimize the opportunities for
discrimination by the Transmission Provider. Also, the wind plant
Interconnection Customer will have recourse to the Commission if it
believes the Transmission Provider has acted in a discriminatory
manner.
46. The Commission declines to adopt ATC's request that all wind
plants, at a minimum, operate within a power factor range of 0.95
leading to 1.0 (unity). This requirement would essentially require
reactive power in every case, which we have already rejected. If
reactive power capability is needed, including a power factor range of
0.95 leading to 1.0 (unity), the System Impact Study will demonstrate
this need.
2. Specific Power Factor Standard
47. NRECA/APPA argues that the Commission should clarify that wind
generators must meet the same reactive power requirements as other
generators, provided the requirements are imposed in a
nondiscriminatory manner. It notes that some Transmission Providers
impose a power factor range wider that +/-0.95 on all new generation,
and argues that in such cases, the same range should be applied to wind
plants. It argues that not imposing the same range threatens
reliability and shifts the costs of preserving reliability to customers
or competing generators.
48. EEI and NU assert that wind plants should regulate voltage to a
set point established by the Transmission Provider, as do synchronous
generators. EEI contends that the language it offered in its initial
comments would provide this necessary clarity, while also maintaining
the flexibility provided in Order No. 2003 so that individual, site-
specific conditions may be addressed.\27\ NU states that wind turbines
have this capability, either inherently (doubly fed induction
generators) or through external equipment.
---------------------------------------------------------------------------
\27\ EEI's March 2, 2005 comments in this proceeding suggest
that we require the wind plant to maintain a power factor within the
range specified by the Transmission Provider ``from time to time,''
but would not require that it operate outside of the 0.95 leading to
0.95 lagging range. See Comments of EEI (March 2, 2005) at 5-6.
---------------------------------------------------------------------------
49. NRECA/APPA also expresses concern that the phrase ``taking into
account any limitations due to voltage level, real power output, etc.''
in the power factor requirements section of Appendix G could create
operational problems for Transmission Providers with wind plants on
their systems. Specifically, it is concerned that this language could
exempt wind plants from their reactive power requirements during
startup and low output periods, which could degrade reliability during
a system contingency.
Commission Conclusion
50. With regard to NRECA/APPA's request for clarification that wind
generators must meet a wider power factor range because some
Transmission Providers impose a power factor range wider that +/-0.95
on all new generation, we note that if we were to allow the
Transmission Provider to impose a wider power factor range as a matter
of routine, that would defeat the purpose of adopting a reactive power
standard for wind generators. However, we note that if the System
Impact Study shows the need for a power factor range wider than +/-0.95
for safety or reliability, the Transmission Provider must file a non-
conforming agreement, as Order No. 2003 permits. The Commission will
consider these non-conforming agreements on a case by case basis. If a
Transmission Provider has a different power factor range in its LGIA
and wishes to apply that same range in Appendix G, it may seek a
variation from the Commission under the variation standards approved in
the Final Rule.\28\ We remind Transmission Providers, however, that the
Commission has adopted a specific power factor standard for wind plants
because of their technical differences. Any proposed variations will be
viewed in light of these technical differences.
---------------------------------------------------------------------------
\28\ Final Rule at P 109.
---------------------------------------------------------------------------
51. In response to the assertion of EEI and NU that wind plants
should regulate voltage to a set point established by the Transmission
Provider, we note that in the Final Rule we concluded that article
9.6.2 of the LGIA (which applies to all plants, including wind plants)
already requires that the ``Interconnection Customer * * * operate the
Large Generating Facility to maintain the specified output voltage or
power factor at the Point of Interconnection.'' \29\
---------------------------------------------------------------------------
\29\ Id. at P 55.
---------------------------------------------------------------------------
52. Finally, the Commission addressed in the Final Rule the
[[Page 75012]]
concerns raised by NRECA/APPA regarding the phrase ``taking into
account any limitations due to voltage level, real power output, etc.''
We stated that this language was necessary due to the technical
limitations of wind generating technology.\30\ We noted that all wind
generating equipment vendors cannot meet the required power factor
range at all levels of output. We reiterate that these technical
differences make the disputed language necessary. Furthermore, without
this language, a Transmission Provider could discriminate against a
wind plant by requiring that it operate at the stated power factor at
voltages where it is technically infeasible to do so.
---------------------------------------------------------------------------
\30\ Id. at P 56.
---------------------------------------------------------------------------
3. Point of Measurement of Power Factor
53. National Grid asks that if the Commission adopts the
recommended revisions to the low voltage ride-through provisions filed
jointly by AWEA and NERC, it clarify that while the point of
measurement for compliance with the low voltage ride-through standard
would be at the high-side of the step-up transformer, the point of
measurement for reactive power is at the Point of Interconnection.
Commission Conclusion
54. We clarify that the point of measurement for the reactive power
standard is at the Point of Interconnection.
C. Self-Study of Interconnection Feasibility
55. In the Final Rule, the Commission adopted special
interconnection procedures that allow the wind plant Interconnection
Customer, when completing the Interconnection Request form required by
section 3.3 of the LGIP, to provide the Transmission Provider with a
simplified set of preliminary data depicting the wind plant as a single
equivalent generator.\31\ Once the wind generator has provided this
data and satisfied all other applicable Interconnection Request
conditions, the special procedures permit the wind plant to enter the
queue and receive the base case data as provided for in the LGIP.
Finally, the special procedures adopted in the Final Rule require the
wind plant Interconnection Customer to submit, within six months of
submitting the Interconnection Request, completed detailed electrical
design specifications and other data (including collector system layout
data) needed by the Transmission Provider to complete the System Impact
Study.
---------------------------------------------------------------------------
\31\ ``Single equivalent generator'' information is design data
that represents the aggregate electrical characteristics of the
individual wind generators as a single generator.
---------------------------------------------------------------------------
56. Southern Company argues on rehearing that these provisions give
wind developers a special preference that unfairly disfavors other
generating technologies.
57. EEI, NU and Southern Company contend that the ``self-study''
provisions of the Final Rule will add further complexity and
uncertainty to the queue process and make queue management and
assignment of cost responsibilities more difficult for Transmission
Providers with large wind-powered generation projects in their queue.
Southern Company adds that the self-study provisions could increase
costs to market participants because the Transmission Provider will
have to run multiple studies. EEI argues that until the industry can
fully address the issues raised by these provisions in a technical
forum, the Commission should remove the provisions from Appendix G. EEI
and NU assert that the provisions do not protect against a wind plant
Interconnection Customer making significant revisions to its project
proposal. If the Commission does not remove the provisions entirely,
EEI and NU suggest that the Commission allow the Transmission Provider
to determine whether the detailed electrical design specifications
later submitted by the wind plant Interconnection Customer are a
material modification to the initial proposal, which would result in
the initial Interconnection Application being withdrawn.
58. Midwest ISO agrees with the Commission that a wind plant should
be able to enter the queue and receive base case data based on
preliminary design specifications. However, it seeks rehearing of the
provision that permits a wind plant to wait up to six months before
submitting final design specifications. It argues that this procedure
promotes inefficiency because the Transmission Provider may be able to
evaluate the proposed interconnection, but cannot do so because it
lacks necessary data. Midwest ISO requests that the Commission revise
the Appendix G self-study provisions to permit the Transmission
Provider to notify the wind plant Interconnection Customer of its
intent to start the System Impact Study. Once this notice is given, the
wind plant developer would have five business days to ``submit either
actual design specifications or generic specifications based on typical
equipment used in the industry.'' \32\ Further, Midwest ISO proposes
that if the wind plant Interconnection Customer submits generic
specifications, it should have to accept cost uncertainty, because
additional facilities may be required when the actual design
specifications are taken into account. Midwest ISO asserts that this
would limit delays in the study process and would allow the
Transmission Provider to identify potential problems or eliminate
tenuous or technically deficient projects earlier and to better use its
resources to study proposed interconnections.
---------------------------------------------------------------------------
\32\ Request for Rehearing of Midwest ISO at 4.
---------------------------------------------------------------------------
Commission Conclusion
59. The Commission will deny these requests for rehearing. We will
make one minor revision to label these special interconnection
procedures for wind plants as ``Appendix 7'' to the LGIP, as discussed
in more detail below.
60. In response to arguments that the self-study procedures for
wind plants give these plants a preference, we reiterate that these
procedures were developed to recognize the technical differences of
wind plants. Unlike conventional generators, wind plant design
specifications and configurations can change significantly based on
their placement on the transmission system.\33\ For example, the
placement of wind turbines, voltage support devices, transformers, and
other equipment (including the layout of the medium voltage collector
system) depend on the location of the wind plant, the location of other
generators on the transmission system, and other information included
in the base case data.\34\ To accommodate these differences, the Final
Rule permits wind plants to enter the interconnection queue with a set
of preliminary electrical design specifications depicting the wind
plant as a single generator, instead of providing detailed design
specifications as required by Order No. 2003. Treating wind plants
differently in this regard is not unduly discriminatory or
preferential, but as noted elsewhere, simply recognizes that wind
plants have different technical characteristics than the more
traditional forms of generation that the LGIP and LGIA were designed to
accommodate. We continue to believe that without this reasonable
accommodation, Transmission Providers could frustrate the
interconnection of wind plants by requiring them to submit detailed
design data, which they cannot do until later in the interconnection
process.
---------------------------------------------------------------------------
\33\ Final Rule at P 97.
\34\ Id.
---------------------------------------------------------------------------
61. We are not persuaded that the reasonable self-study provision
we adopted will make the interconnection
[[Page 75013]]
queue process significantly more difficult or complex. Wind plant
Interconnection Customers who provide the preliminary single generator
equivalent data are required to provide final detailed electrical
design specifications no later than six months after submitting the
initial Interconnection Request. This six-month time period takes into
account the procedures needed before the start of the System Impact
Study, including the Feasibility Study and negotiation of study
agreements. Therefore, the Transmission Provider will receive from the
wind plant the detailed design information needed to conduct the System
Impact Study. For this reason, we also deny Midwest ISO's request to
modify the six-month deadline. If we adopted Midwest ISO's proposed
modifications, the Transmission Provider could request that the wind
plant provide detailed design specifications at any time it believes it
is ready to begin the System Impact Study, even a day after the initial
Interconnection Request is submitted. As a result, this modification
would defeat the purpose of permitting wind plants to submit
preliminary design specifications, and could allow Transmission
Providers to frustrate the interconnection of wind plants.
62. With respect to the alternative suggestion by EEI and NU that
the Transmission Provider be permitted to determine that a detailed
design specification later submitted by the wind plant Interconnection
Customer is a material modification of the Interconnection Request, we
note that section 4.4 of the LGIP already addresses modifications and
will apply to wind plants as well as other generating technologies.
When applying this section to wind plant Interconnection Requests that
first submit preliminary design specifications, Transmission Providers
are not to consider the detailed design data provided later by the wind
plant Interconnection Customer to be a material modification unless it
significantly departs from the preliminary specifications provided. In